Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:37
Tabular Output Report in Format: HTML
Building: RetailStripmall
Environment: RUNPERIOD 1 ** New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860
Simulation Timestamp: 2023-10-16 08:37:31
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:31
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1299.99 | 621.91 | 621.91 |
Net Site Energy | 1299.99 | 621.91 | 621.91 |
Total Source Energy | 3146.21 | 1505.14 | 1505.14 |
Net Source Energy | 3146.21 | 1505.14 | 1505.14 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 2090.32 |
Net Conditioned Building Area | 2090.32 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 466.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 116.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 366.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 60.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 128.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 98.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 63.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 833.91 | 466.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 466.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 116.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 366.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 60.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 128.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 98.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 63.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 466.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 116.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 366.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 60.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 128.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 98.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 63.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 204.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 133.33 | 222.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Other | 61.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 398.94 | 222.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 204.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 133.33 | 222.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Other | 61.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 398.94 | 222.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 833.906 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 833.906 | 100.00 |
Total On-Site and Utility Electric Sources | 833.906 | 100.00 |
Total Electricity End Uses | 833.906 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 87.30 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 87.30 | 100.00 |
Total Water End Uses | 87.30 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 2.17 |
Time Setpoint Not Met During Occupied Cooling | 0.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 2476.83 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTRIPMALL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4A
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_NEWYORK
| Environment |ZoneCoolingSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ZoneHeatingSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ZoneElectricSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |SpaceGainsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |PeakSpaceGainsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |SpaceGainComponentsAtCoolingPeakMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ComfortReportSimple55Monthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |OccupantComfortDataSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |DXReportMonthly
| PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL | PSZ-AC_3:3 COOLING COIL | PSZ-AC_4:4 COOLING COIL | PSZ-AC_5:5 COOLING COIL | PSZ-AC_6:6 COOLING COIL | PSZ-AC_7:7 COOLING COIL | PSZ-AC_8:8 COOLING COIL | PSZ-AC_9:9 COOLING COIL | PSZ-AC_10:10 COOLING COIL |WindowReportMonthly
| LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR |WindowEnergyReportMonthly
| LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR |WindowZoneSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |WindowEnergyZoneSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| GAS TANK1 | GAS TANK2 | GAS TANK3 | GAS TANK4 | GAS TANK5 | GAS TANK6 | GAS TANK7 |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC_1:1 HEATING COIL | PSZ-AC_2:2 HEATING COIL | PSZ-AC_3:3 HEATING COIL | PSZ-AC_4:4 HEATING COIL | PSZ-AC_5:5 HEATING COIL | PSZ-AC_6:6 HEATING COIL | PSZ-AC_7:7 HEATING COIL | PSZ-AC_8:8 HEATING COIL | PSZ-AC_9:9 HEATING COIL | PSZ-AC_10:10 HEATING COIL | PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL | PSZ-AC_3:3 COOLING COIL | PSZ-AC_4:4 COOLING COIL | PSZ-AC_5:5 COOLING COIL | PSZ-AC_6:6 COOLING COIL | PSZ-AC_7:7 COOLING COIL | PSZ-AC_8:8 COOLING COIL | PSZ-AC_9:9 COOLING COIL | PSZ-AC_10:10 COOLING COIL |FanReportMonthly
| PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN |ZoneTemperatureOscillationReportMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |MechanicalVentilationLoadsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:31
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:37 |
RunPeriod | RUNPERIOD 1 |
Weather File | New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860 |
Latitude [deg] | 40.65 |
Longitude [deg] | -73.8 |
Elevation [m] | 5.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Above Ground Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Window Opening Area [m2] | 124.40 | 0.00 | 0.00 | 124.40 | 0.00 |
Gross Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Above Ground Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Above Ground Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Window Opening Area [m2] | 124.40 | 0.00 | 0.00 | 124.40 | 0.00 |
Gross Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Above Ground Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Total | |
Gross Roof Area [m2] | 2090.32 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
LGSTORE1 | 348.39 | Yes | Yes | 1805.20 | 1.00 | 276.30 | 0.00 | 20.77 | 20.77 | 15.3022 | 6.19 | 4.3000 |
SMSTORE1 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.38 | 10.38 | 18.2890 | 6.19 | 4.3000 |
SMSTORE2 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 16.6533 | 6.19 | 4.3000 |
SMSTORE3 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 16.6533 | 6.19 | 4.3000 |
SMSTORE4 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 16.6533 | 6.19 | 4.3000 |
LGSTORE2 | 348.39 | Yes | Yes | 1805.20 | 1.00 | 157.89 | 0.00 | 20.72 | 20.72 | 9.5842 | 6.19 | 4.3000 |
SMSTORE5 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 9.6995 | 6.19 | 4.3000 |
SMSTORE6 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 9.6995 | 6.19 | 4.3000 |
SMSTORE7 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 9.6995 | 6.19 | 4.3000 |
SMSTORE8 | 174.19 | Yes | Yes | 902.60 | 1.00 | 197.36 | 0.00 | 10.36 | 10.36 | 9.6995 | 6.19 | 4.3000 |
Total | 2090.32 | 10831.20 | 1184.15 | 0.00 | 124.40 | 124.40 | 13.0683 | 6.19 | 4.3000 | |||
Conditioned Total | 2090.32 | 10831.20 | 1184.15 | 0.00 | 124.40 | 124.40 | 13.0683 | 6.19 | 4.3000 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
LGSTORE1 | 348.39 | Yes | Yes | 1.00 | LGSTORE1 | GENERAL | LGSTORE1 | 15.3022 | 6.19 | 4.3000 | |
SMSTORE1 | 174.19 | Yes | Yes | 1.00 | SMSTORE1 | GENERAL | SMSTORE1 | 18.2890 | 6.19 | 4.3000 | |
SMSTORE2 | 174.19 | Yes | Yes | 1.00 | SMSTORE2 | GENERAL | SMSTORE2 | 16.6533 | 6.19 | 4.3000 | |
SMSTORE3 | 174.19 | Yes | Yes | 1.00 | SMSTORE3 | GENERAL | SMSTORE3 | 16.6533 | 6.19 | 4.3000 | |
SMSTORE4 | 174.19 | Yes | Yes | 1.00 | SMSTORE4 | GENERAL | SMSTORE4 | 16.6533 | 6.19 | 4.3000 | |
LGSTORE2 | 348.39 | Yes | Yes | 1.00 | LGSTORE2 | GENERAL | LGSTORE2 | 9.5842 | 6.19 | 4.3000 | |
SMSTORE5 | 174.19 | Yes | Yes | 1.00 | SMSTORE5 | GENERAL | SMSTORE5 | 9.6995 | 6.19 | 4.3000 | |
SMSTORE6 | 174.19 | Yes | Yes | 1.00 | SMSTORE6 | GENERAL | SMSTORE6 | 9.6995 | 6.19 | 4.3000 | |
SMSTORE7 | 174.19 | Yes | Yes | 1.00 | SMSTORE7 | GENERAL | SMSTORE7 | 9.6995 | 6.19 | 4.3000 | |
SMSTORE8 | 174.19 | Yes | Yes | 1.00 | SMSTORE8 | GENERAL | SMSTORE8 | 9.6995 | 6.19 | 4.3000 | |
Total | 2090.32 | 13.0683 | 3.10 | 4.3000 | |||||||
Conditioned Total | 2090.32 | 13.0683 | 3.10 | 4.3000 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 2090.32 | 2090.32 | 0.00 | 0.00 | 13.0683 | 6.19 | 4.3000 |
Total | 2090.32 | 2090.32 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:31
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 16-AUG-13:30 | 06-FEB-08:09 | - | - | - | - | - | - | - | - | - | - | 06-JAN-13:09 |
Heating | 0.00 | 233566.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 46987.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 23459.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 8059.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 7942.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 7564.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 94012.95 | 233566.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 233566.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 46987.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 23459.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 8059.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 7942.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 7564.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:31
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 505.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 370.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1161.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 191.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 405.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 310.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 201.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2640.98 | 505.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 241.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 177.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 555.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 91.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 194.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 148.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 96.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1263.43 | 241.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 241.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 177.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 555.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 91.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 194.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 148.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 96.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1263.43 | 241.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:31
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
LGSTORE1 DIRECT AIR | 1.94 |
SMSTORE1 DIRECT AIR | 1.02 |
SMSTORE2 DIRECT AIR | 1.03 |
SMSTORE3 DIRECT AIR | 1.03 |
SMSTORE4 DIRECT AIR | 1.02 |
LGSTORE2 DIRECT AIR | 1.83 |
SMSTORE5 DIRECT AIR | 0.947904 |
SMSTORE6 DIRECT AIR | 0.942927 |
SMSTORE7 DIRECT AIR | 0.938815 |
SMSTORE8 DIRECT AIR | 1.03 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC_1:1 | 1.94 | 1.94 | 1.94 | 1.94 | 1.94 | 1.94 | 1.00 | 1.00 | 1.94 |
PSZ-AC_2:2 | 1.02 | 1.02 | 1.02 | 1.02 | 1.04 | 1.04 | 1.00 | 0.984226 | 1.04 |
PSZ-AC_3:3 | 1.03 | 1.03 | 1.03 | 1.03 | 1.05 | 1.05 | 1.00 | 0.985827 | 1.05 |
PSZ-AC_4:4 | 1.03 | 1.03 | 1.03 | 1.03 | 1.05 | 1.05 | 1.00 | 0.976612 | 1.05 |
PSZ-AC_5:5 | 1.02 | 1.02 | 1.02 | 1.02 | 1.04 | 1.04 | 1.00 | 0.984119 | 1.04 |
PSZ-AC_6:6 | 1.83 | 1.83 | 1.83 | 1.83 | 1.83 | 1.83 | 1.00 | 1.00 | 1.83 |
PSZ-AC_7:7 | 0.947904 | 0.947904 | 0.947904 | 0.947904 | 0.950183 | 0.950183 | 1.00 | 0.997602 | 0.950183 |
PSZ-AC_8:8 | 0.942927 | 0.942927 | 0.942927 | 0.942927 | 0.945526 | 0.945526 | 1.00 | 0.997250 | 0.945526 |
PSZ-AC_9:9 | 0.938815 | 0.938815 | 0.938815 | 0.938815 | 0.942415 | 0.942415 | 1.00 | 0.996180 | 0.942415 |
PSZ-AC_10:10 | 1.03 | 1.03 | 1.03 | 1.03 | 1.04 | 1.04 | 1.00 | 0.991372 | 1.04 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC_1:1_OA_CONTROLLER | 1.94 | 0.411479 |
PSZ-AC_2:2_OA_CONTROLLER | 1.04 | 0.205739 |
PSZ-AC_3:3_OA_CONTROLLER | 1.05 | 0.205739 |
PSZ-AC_4:4_OA_CONTROLLER | 1.05 | 0.205739 |
PSZ-AC_5:5_OA_CONTROLLER | 1.04 | 0.205739 |
PSZ-AC_6:6_OA_CONTROLLER | 1.83 | 0.411479 |
PSZ-AC_7:7_OA_CONTROLLER | 0.950183 | 0.205739 |
PSZ-AC_8:8_OA_CONTROLLER | 0.945526 | 0.205739 |
PSZ-AC_9:9_OA_CONTROLLER | 0.942415 | 0.205739 |
PSZ-AC_10:10_OA_CONTROLLER | 1.04 | 0.205739 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | 1.94 | 2078.68 |
PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | 1.04 | 1152.79 |
PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | 1.05 | 1158.58 |
PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | 1.05 | 1162.60 |
PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | 1.04 | 1151.94 |
PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | 1.83 | 1961.62 |
PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | 0.950183 | 1052.00 |
PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | 0.945526 | 1046.85 |
PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | 0.942415 | 1043.40 |
PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | 1.04 | 1146.36 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC_1:1_UNITARY_PACKAGE_DX | 1.94 | 1.94 | 1.94 | 1.28 | 44486.31 | 60221.18 | 40.00 | 1.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_DX | 1.04 | 1.04 | 1.04 | 0.687204 | 23397.33 | 31332.34 | 40.00 | 1.00 |
PSZ-AC_3:3_UNITARY_PACKAGE_DX | 1.05 | 1.05 | 1.05 | 0.690652 | 23457.67 | 31488.07 | 40.00 | 1.00 |
PSZ-AC_4:4_UNITARY_PACKAGE_DX | 1.05 | 1.05 | 1.05 | 0.693049 | 23518.84 | 31348.78 | 40.00 | 1.00 |
PSZ-AC_5:5_UNITARY_PACKAGE_DX | 1.04 | 1.04 | 1.04 | 0.686693 | 23358.15 | 31312.32 | 40.00 | 1.00 |
PSZ-AC_6:6_UNITARY_PACKAGE_DX | 1.83 | 1.83 | 1.83 | 1.21 | 42329.66 | 57719.57 | 40.00 | 1.00 |
PSZ-AC_7:7_UNITARY_PACKAGE_DX | 0.950183 | 0.950183 | 0.950183 | 0.627121 | 21850.45 | 29575.22 | 40.00 | 1.00 |
PSZ-AC_8:8_UNITARY_PACKAGE_DX | 0.945526 | 0.945526 | 0.945526 | 0.624047 | 21775.75 | 29461.47 | 40.00 | 1.00 |
PSZ-AC_9:9_UNITARY_PACKAGE_DX | 0.942415 | 0.942415 | 0.942415 | 0.621994 | 21683.35 | 29367.52 | 40.00 | 1.00 |
PSZ-AC_10:10_UNITARY_PACKAGE_DX | 1.04 | 1.04 | 1.04 | 0.683366 | 23404.15 | 31372.11 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-AC_1:1 COOLING COIL | 1.94 | 0.971305 | 1.30 | 44486.31 | 22243.15 | 0.726760 | 0.726760 |
PSZ-AC_2:2 COOLING COIL | 1.04 | 0.520609 | 0.694147 | 23397.33 | 11698.67 | 0.733840 | 0.733840 |
PSZ-AC_3:3 COOLING COIL | 1.05 | 0.523221 | 0.697627 | 23457.67 | 11728.83 | 0.734500 | 0.734500 |
PSZ-AC_4:4 COOLING COIL | 1.05 | 0.525037 | 0.700047 | 23518.84 | 11759.42 | 0.734730 | 0.734730 |
PSZ-AC_5:5 COOLING COIL | 1.04 | 0.520222 | 0.693627 | 23358.15 | 11679.08 | 0.734090 | 0.734090 |
PSZ-AC_6:6 COOLING COIL | 1.83 | 0.916604 | 1.22 | 42329.66 | 21164.83 | 0.724570 | 0.724570 |
PSZ-AC_7:7 COOLING COIL | 0.950180 | 0.475092 | 0.633453 | 21850.45 | 10925.23 | 0.725650 | 0.725650 |
PSZ-AC_8:8 COOLING COIL | 0.945530 | 0.472763 | 0.630353 | 21775.75 | 10887.88 | 0.725260 | 0.725260 |
PSZ-AC_9:9 COOLING COIL | 0.942420 | 0.471208 | 0.628280 | 21683.35 | 10841.67 | 0.725510 | 0.725510 |
PSZ-AC_10:10 COOLING COIL | 1.04 | 0.517701 | 0.690267 | 23404.15 | 11702.08 | 0.731250 | 0.731250 |
Design Size Nominal Capacity [W] | |
PSZ-AC_1:1 HEATING COIL | 60221.18 |
PSZ-AC_2:2 HEATING COIL | 31332.34 |
PSZ-AC_3:3 HEATING COIL | 31488.07 |
PSZ-AC_4:4 HEATING COIL | 31348.78 |
PSZ-AC_5:5 HEATING COIL | 31312.32 |
PSZ-AC_6:6 HEATING COIL | 57719.57 |
PSZ-AC_7:7 HEATING COIL | 29575.22 |
PSZ-AC_8:8 HEATING COIL | 29461.47 |
PSZ-AC_9:9 HEATING COIL | 29367.52 |
PSZ-AC_10:10 HEATING COIL | 31372.11 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:31
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
LGSTORE1_WALL_3 | LGSTORE1_WALL_3_DOOR_1 | LGSTORE1_WALL_3_DOOR_2 | |
LGSTORE1_WALL_1 | LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | |
SMSTORE1_WALL_1 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | |
SMSTORE1_WALL_3 | SMSTORE1_WALL_3_DOOR | |
SMSTORE2_WALL_1 | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | |
SMSTORE2_WALL_3 | SMSTORE2_WALL_3_DOOR | |
SMSTORE3_WALL_1 | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | |
SMSTORE3_WALL_3 | SMSTORE3_WALL_3_DOOR | |
SMSTORE4_WALL_1 | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | |
SMSTORE4_WALL_3 | SMSTORE4_WALL_3_DOOR | |
LGSTORE2_WALL_3 | LGSTORE2_WALL_3_DOOR_1 | LGSTORE2_WALL_3_DOOR_2 | |
LGSTORE2_WALL_1 | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | |
SMSTORE5_WALL_1 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | |
SMSTORE5_WALL_3 | SMSTORE5_WALL_3_DOOR | |
SMSTORE6_WALL_1 | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | |
SMSTORE6_WALL_3 | SMSTORE6_WALL_3_DOOR | |
SMSTORE7_WALL_1 | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | |
SMSTORE7_WALL_3 | SMSTORE7_WALL_3_DOOR | |
SMSTORE8_WALL_1 | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR | |
SMSTORE8_WALL_3 | SMSTORE8_WALL_3_DOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:31
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:31
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 14.00 | 7.30 | 3.30 | 1.20 | -0.20 | 5.60 | 10.90 | 16.10 | 21.70 | 25.00 | 24.80 | 19.90 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860 | 40.65 | -73.80 | -5.00 | 5.00 | 101265 | 1.2036 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 12.47 | 25.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RetailStripmall | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 10 | 118 | 48 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | LGSTORE1 | 0.0 | 0.00 | 0.00 | 0.00 | 7.62 | 11.43 | 2.59 | 1 | 1 | 1 | 0.00 | 15.24 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 1805.20 | TARP | TARP | 348.39 | 276.30 | 247.74 | 20.77 | 6 | 8 | 0 | Yes |
2 | SMSTORE1 | 0.0 | 0.00 | 0.00 | 0.00 | 19.05 | 11.43 | 2.59 | 1 | 1 | 1 | 15.24 | 22.86 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.66 | 10.38 | 6 | 4 | 0 | Yes |
3 | SMSTORE2 | 0.0 | 0.00 | 0.00 | 0.00 | 26.67 | 11.43 | 2.59 | 1 | 1 | 1 | 22.86 | 30.48 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
4 | SMSTORE3 | 0.0 | 0.00 | 0.00 | 0.00 | 34.29 | 11.43 | 2.59 | 1 | 1 | 1 | 30.48 | 38.10 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
5 | SMSTORE4 | 0.0 | 0.00 | 0.00 | 0.00 | 41.91 | 11.43 | 2.59 | 1 | 1 | 1 | 38.10 | 45.72 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
6 | LGSTORE2 | 0.0 | 0.00 | 0.00 | 0.00 | 53.34 | 11.43 | 2.59 | 1 | 1 | 1 | 45.72 | 60.96 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 1805.20 | TARP | TARP | 348.39 | 157.89 | 129.41 | 20.72 | 6 | 8 | 0 | Yes |
7 | SMSTORE5 | 0.0 | 0.00 | 0.00 | 0.00 | 64.77 | 11.43 | 2.59 | 1 | 1 | 1 | 60.96 | 68.58 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
8 | SMSTORE6 | 0.0 | 0.00 | 0.00 | 0.00 | 72.39 | 11.43 | 2.59 | 1 | 1 | 1 | 68.58 | 76.20 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
9 | SMSTORE7 | 0.0 | 0.00 | 0.00 | 0.00 | 80.01 | 11.43 | 2.59 | 1 | 1 | 1 | 76.20 | 83.82 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
10 | SMSTORE8 | 0.0 | 0.00 | 0.00 | 0.00 | 87.63 | 11.43 | 2.59 | 1 | 1 | 1 | 83.82 | 91.44 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 197.36 | 183.12 | 10.36 | 6 | 4 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | LGSTORE1 | 348.39 | 56.3 | 6.193 | 0.161 | 15.302 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 19.602 | No |
2 | SMSTORE1 | 174.19 | 28.1 | 6.194 | 0.161 | 18.289 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 22.589 | No |
3 | SMSTORE2 | 174.19 | 28.1 | 6.194 | 0.161 | 16.653 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 20.953 | No |
4 | SMSTORE3 | 174.19 | 28.1 | 6.194 | 0.161 | 16.653 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 20.953 | No |
5 | SMSTORE4 | 174.19 | 28.1 | 6.194 | 0.161 | 16.653 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 20.953 | No |
6 | LGSTORE2 | 348.39 | 56.3 | 6.193 | 0.161 | 9.584 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 13.884 | No |
7 | SMSTORE5 | 174.19 | 28.1 | 6.194 | 0.161 | 9.699 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 13.999 | No |
8 | SMSTORE6 | 174.19 | 28.1 | 6.194 | 0.161 | 9.699 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 13.999 | No |
9 | SMSTORE7 | 174.19 | 28.1 | 6.194 | 0.161 | 9.699 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 13.999 | No |
10 | SMSTORE8 | 174.19 | 28.1 | 6.194 | 0.161 | 9.699 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 13.999 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | LGSTORE1 | TYPE1_OCC_SCH | LGSTORE1 | 348.39 | 56.3 | 56.3 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 56 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | SMSTORE1 | TYPE1_OCC_SCH | SMSTORE1 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | SMSTORE2 | TYPE2_OCC_SCH | SMSTORE2 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | SMSTORE3 | TYPE2_OCC_SCH | SMSTORE3 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | SMSTORE4 | TYPE2_OCC_SCH | SMSTORE4 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | LGSTORE2 | TYPE3_OCC_SCH | LGSTORE2 | 348.39 | 56.3 | 56.3 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 56 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | SMSTORE5 | TYPE3_OCC_SCH | SMSTORE5 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | SMSTORE6 | TYPE3_OCC_SCH | SMSTORE6 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | SMSTORE7 | TYPE3_OCC_SCH | SMSTORE7 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | SMSTORE8 | TYPE3_OCC_SCH | SMSTORE8 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | LGSTORE1_LIGHTS | LTG_SCH_BASE_LPD1 | LGSTORE1 | 348.39 | 56.3 | 3346.345 | 9.605 | 59.490 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3346.345 |
2 | LGSTORE1_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | LGSTORE1 | 348.39 | 56.3 | 1984.726 | 5.697 | 35.284 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1984.726 |
3 | SMSTORE1_LIGHTS | LTG_SCH_BASE_SMALL_LPD1 | SMSTORE1 | 174.19 | 28.1 | 1693.257 | 9.721 | 60.206 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1693.257 |
4 | SMSTORE1_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | SMSTORE1 | 174.19 | 28.1 | 1492.567 | 8.568 | 53.070 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1492.567 |
5 | SMSTORE2_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE2 | 174.19 | 28.1 | 1689.582 | 9.699 | 60.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1689.582 |
6 | SMSTORE2_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE2 | 174.19 | 28.1 | 1211.319 | 6.954 | 43.070 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1211.319 |
7 | SMSTORE3_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE3 | 174.19 | 28.1 | 1689.582 | 9.699 | 60.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1689.582 |
8 | SMSTORE3_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE3 | 174.19 | 28.1 | 1211.319 | 6.954 | 43.070 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1211.319 |
9 | SMSTORE4_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE4 | 174.19 | 28.1 | 1689.582 | 9.699 | 60.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1689.582 |
10 | SMSTORE4_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE4 | 174.19 | 28.1 | 1211.319 | 6.954 | 43.070 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1211.319 |
11 | LGSTORE2_LIGHTS | LTG_SCH_BASE_LPD2 | LGSTORE2 | 348.39 | 56.3 | 3338.998 | 9.584 | 59.359 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3338.998 |
12 | LGSTORE2_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | LGSTORE2 | 348.39 | 56.3 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
13 | SMSTORE5_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE5 | 174.19 | 28.1 | 1689.582 | 9.699 | 60.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1689.582 |
14 | SMSTORE5_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE5 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
15 | SMSTORE6_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE6 | 174.19 | 28.1 | 1689.582 | 9.699 | 60.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1689.582 |
16 | SMSTORE6_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE6 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
17 | SMSTORE7_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE7 | 174.19 | 28.1 | 1689.582 | 9.699 | 60.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1689.582 |
18 | SMSTORE7_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE7 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
19 | SMSTORE8_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE8 | 174.19 | 28.1 | 1689.582 | 9.699 | 60.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1689.582 |
20 | SMSTORE8_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE8 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LGSTORE1_MISCPLUG_EQUIP | TYPE1_EQUIP_SCH | LGSTORE1 | 348.39 | 56.3 | 1498.062 | 4.300 | 26.632 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1498.062 |
2 | SMSTORE1_MISCPLUG_EQUIP | TYPE1_EQUIP_SCH | SMSTORE1 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
3 | SMSTORE2_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE2 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
4 | SMSTORE3_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE3 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
5 | SMSTORE4_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE4 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
6 | LGSTORE2_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | LGSTORE2 | 348.39 | 56.3 | 1498.062 | 4.300 | 26.632 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1498.062 |
7 | SMSTORE5_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE5 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
8 | SMSTORE6_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE6 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
9 | SMSTORE7_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE7 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
10 | SMSTORE8_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE8 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.770 | 0.700 | Rough |
5 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 0.6000 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
6 | LGSTORE1_FLOOR_FFACTOR | 36 | 2 | 7 | 0.167 | 0.1408 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
7 | SMSTORE1_FLOOR_FFACTOR | 37 | 2 | 7 | 0.167 | 0.7972E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
8 | SMSTORE2_FLOOR_FFACTOR | 38 | 2 | 7 | 0.167 | 0.7972E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | SMSTORE3_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.7972E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
10 | SMSTORE4_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.7972E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
11 | LGSTORE2_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.7972E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | SMSTORE5_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.7972E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | SMSTORE6_FLOOR_FFACTOR | 43 | 2 | 7 | 0.167 | 0.7972E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | SMSTORE7_FLOOR_FFACTOR | 44 | 2 | 7 | 0.167 | 0.7972E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | SMSTORE8_FLOOR_FFACTOR | 45 | 2 | 7 | 0.167 | 0.2031 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
6 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
7 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
8 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
10 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.433 |
11 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
12 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 7.024 |
13 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
14 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.47 |
15 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
16 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.47 |
17 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
18 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.47 |
19 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
20 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.47 |
21 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
22 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.47 |
23 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
24 | ~FC_Insulation_7 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.47 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_8 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.47 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_9 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.47 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_10 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.847 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
14 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
15 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
16 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
17 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
18 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
19 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
20 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
21 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
22 | 7 | -0.34128934E-12 | 0.10473450E-14 | -0.10397207E-12 | 0.10371484E-15 |
23 | 6 | 0.30755064E-07 | 0.17217129E-09 | 0.70279215E-08 | -0.14642558E-12 |
24 | 5 | -0.20062951E-03 | 0.14545406E-05 | -0.10304618E-03 | 0.69406843E-08 |
25 | 4 | 0.30437449 | 0.69977658E-03 | 0.10408506 | -0.35305012E-04 |
26 | 3 | -7.5082928 | 0.21456968E-01 | -2.4107259 | 0.30195353E-01 |
27 | 2 | 41.668927 | 0.75582488E-01 | 15.559173 | -0.34222686 |
28 | 1 | -81.156896 | 0.33830739E-01 | -29.405205 | 1.0916426 |
29 | 0 | 46.824335 | 0.67514285E-03 | 16.285023 | |
30 | 7 | -0.30155247E-08 | -0.19705740E-14 | 0.18469307E-14 | -0.46079768E-16 |
31 | 6 | 0.40551627E-05 | 0.26926011E-08 | 0.31944497E-02 | -0.26797721E-04 |
32 | 5 | -0.28496186E-03 | 0.15923452E-05 | -0.22398486 | 0.19584477E-02 |
33 | 4 | 0.65115693E-02 | 0.72427529E-04 | 4.8338806 | -0.45306652E-01 |
34 | 3 | -0.57046066E-01 | 0.57554694E-03 | -38.045903 | 0.39892442 |
35 | 2 | 0.20237164 | 0.95689144E-03 | 116.53161 | -1.4185768 |
36 | 1 | -0.29197338 | 0.29127682E-03 | -143.93536 | 2.0495010 |
37 | 0 | 0.14232195 | 0.70641069E-05 | 60.838472 | |
38 | 7 | -0.53597813E-08 | -0.10943972E-13 | 0.15521545E-14 | -0.37274179E-16 |
39 | 6 | 0.25551035E-05 | 0.15319154E-08 | 0.31991935E-02 | -0.26837516E-04 |
40 | 5 | -0.16700335E-03 | 0.90227195E-06 | -0.22425438 | 0.19608267E-02 |
41 | 4 | 0.37302439E-02 | 0.40957222E-04 | 4.8383675 | -0.45349785E-01 |
42 | 3 | -0.32401395E-01 | 0.32489936E-03 | -38.071239 | 0.39920448 |
43 | 2 | 0.11454695 | 0.53930964E-03 | 116.58090 | -1.4192362 |
44 | 1 | -0.16500402 | 0.16380141E-03 | -143.96437 | 2.0499779 |
45 | 0 | 0.80366526E-01 | 0.39747064E-05 | 60.838472 | |
46 | 7 | -0.53597813E-08 | -0.10943972E-13 | 0.15521547E-14 | -0.37274182E-16 |
47 | 6 | 0.25551035E-05 | 0.15319154E-08 | 0.31991935E-02 | -0.26837516E-04 |
48 | 5 | -0.16700335E-03 | 0.90227195E-06 | -0.22425438 | 0.19608267E-02 |
49 | 4 | 0.37302439E-02 | 0.40957222E-04 | 4.8383675 | -0.45349785E-01 |
50 | 3 | -0.32401395E-01 | 0.32489936E-03 | -38.071239 | 0.39920448 |
51 | 2 | 0.11454695 | 0.53930964E-03 | 116.58090 | -1.4192362 |
52 | 1 | -0.16500402 | 0.16380141E-03 | -143.96437 | 2.0499779 |
53 | 0 | 0.80366526E-01 | 0.39747064E-05 | 60.838472 | |
54 | 7 | -0.53597813E-08 | -0.10943972E-13 | 0.15521549E-14 | -0.37274185E-16 |
55 | 6 | 0.25551035E-05 | 0.15319154E-08 | 0.31991935E-02 | -0.26837516E-04 |
56 | 5 | -0.16700335E-03 | 0.90227195E-06 | -0.22425438 | 0.19608267E-02 |
57 | 4 | 0.37302439E-02 | 0.40957222E-04 | 4.8383675 | -0.45349785E-01 |
58 | 3 | -0.32401395E-01 | 0.32489936E-03 | -38.071239 | 0.39920448 |
59 | 2 | 0.11454695 | 0.53930964E-03 | 116.58090 | -1.4192362 |
60 | 1 | -0.16500402 | 0.16380141E-03 | -143.96437 | 2.0499779 |
61 | 0 | 0.80366526E-01 | 0.39747064E-05 | 60.838472 | |
62 | 7 | -0.53597813E-08 | -0.10943972E-13 | 0.15521548E-14 | -0.37274183E-16 |
63 | 6 | 0.25551035E-05 | 0.15319154E-08 | 0.31991935E-02 | -0.26837516E-04 |
64 | 5 | -0.16700335E-03 | 0.90227195E-06 | -0.22425438 | 0.19608267E-02 |
65 | 4 | 0.37302439E-02 | 0.40957222E-04 | 4.8383675 | -0.45349785E-01 |
66 | 3 | -0.32401395E-01 | 0.32489936E-03 | -38.071239 | 0.39920448 |
67 | 2 | 0.11454695 | 0.53930964E-03 | 116.58090 | -1.4192362 |
68 | 1 | -0.16500402 | 0.16380141E-03 | -143.96437 | 2.0499779 |
69 | 0 | 0.80366526E-01 | 0.39747064E-05 | 60.838472 | |
70 | 7 | -0.53597813E-08 | -0.10943972E-13 | 0.15521547E-14 | -0.37274182E-16 |
71 | 6 | 0.25551035E-05 | 0.15319154E-08 | 0.31991935E-02 | -0.26837516E-04 |
72 | 5 | -0.16700335E-03 | 0.90227195E-06 | -0.22425438 | 0.19608267E-02 |
73 | 4 | 0.37302439E-02 | 0.40957222E-04 | 4.8383675 | -0.45349785E-01 |
74 | 3 | -0.32401395E-01 | 0.32489936E-03 | -38.071239 | 0.39920448 |
75 | 2 | 0.11454695 | 0.53930964E-03 | 116.58090 | -1.4192362 |
76 | 1 | -0.16500402 | 0.16380141E-03 | -143.96437 | 2.0499779 |
77 | 0 | 0.80366526E-01 | 0.39747064E-05 | 60.838472 | |
78 | 7 | -0.53597813E-08 | -0.10943972E-13 | 0.15521547E-14 | -0.37274181E-16 |
79 | 6 | 0.25551035E-05 | 0.15319154E-08 | 0.31991935E-02 | -0.26837516E-04 |
80 | 5 | -0.16700335E-03 | 0.90227195E-06 | -0.22425438 | 0.19608267E-02 |
81 | 4 | 0.37302439E-02 | 0.40957222E-04 | 4.8383675 | -0.45349785E-01 |
82 | 3 | -0.32401395E-01 | 0.32489936E-03 | -38.071239 | 0.39920448 |
83 | 2 | 0.11454695 | 0.53930964E-03 | 116.58090 | -1.4192362 |
84 | 1 | -0.16500402 | 0.16380141E-03 | -143.96437 | 2.0499779 |
85 | 0 | 0.80366526E-01 | 0.39747064E-05 | 60.838472 | |
86 | 7 | -0.53597813E-08 | -0.10943972E-13 | 0.15521545E-14 | -0.37274179E-16 |
87 | 6 | 0.25551035E-05 | 0.15319154E-08 | 0.31991935E-02 | -0.26837516E-04 |
88 | 5 | -0.16700335E-03 | 0.90227195E-06 | -0.22425438 | 0.19608267E-02 |
89 | 4 | 0.37302439E-02 | 0.40957222E-04 | 4.8383675 | -0.45349785E-01 |
90 | 3 | -0.32401395E-01 | 0.32489936E-03 | -38.071239 | 0.39920448 |
91 | 2 | 0.11454695 | 0.53930964E-03 | 116.58090 | -1.4192362 |
92 | 1 | -0.16500402 | 0.16380141E-03 | -143.96437 | 2.0499779 |
93 | 0 | 0.80366526E-01 | 0.39747064E-05 | 60.838472 | |
94 | 7 | -0.53597813E-08 | -0.10943972E-13 | 0.15521547E-14 | -0.37274182E-16 |
95 | 6 | 0.25551035E-05 | 0.15319154E-08 | 0.31991935E-02 | -0.26837516E-04 |
96 | 5 | -0.16700335E-03 | 0.90227195E-06 | -0.22425438 | 0.19608267E-02 |
97 | 4 | 0.37302439E-02 | 0.40957222E-04 | 4.8383675 | -0.45349785E-01 |
98 | 3 | -0.32401395E-01 | 0.32489936E-03 | -38.071239 | 0.39920448 |
99 | 2 | 0.11454695 | 0.53930964E-03 | 116.58090 | -1.4192362 |
100 | 1 | -0.16500402 | 0.16380141E-03 | -143.96437 | 2.0499779 |
101 | 0 | 0.80366526E-01 | 0.39747064E-05 | 60.838472 | |
102 | 7 | -0.20778300E-08 | -0.65167512E-15 | 0.79548166E-14 | -0.12010680E-15 |
103 | 6 | 0.57088823E-05 | 0.38884884E-08 | 0.31895855E-02 | -0.26756916E-04 |
104 | 5 | -0.40892418E-03 | 0.23023551E-05 | -0.22370841 | 0.19560076E-02 |
105 | 4 | 0.93961169E-02 | 0.10478953E-03 | 4.8292766 | -0.45262394E-01 |
106 | 3 | -0.82481111E-01 | 0.83319714E-03 | -38.019897 | 0.39863696 |
107 | 2 | 0.29283299 | 0.13859693E-02 | 116.48099 | -1.4178998 |
108 | 1 | -0.42263540 | 0.42218679E-03 | -143.90557 | 2.0490113 |
109 | 0 | 0.20604930 | 0.10232106E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.362_SHGC_0.359 | 35 | 1 | VerySmooth | 2.057 | 2.057 | 1.000 | 0.360 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 3.63679E-002 | 0.27216 | 0.52074 | 0.52074 | 0.39490 | 0.13813 | 0.18098 | 0.00000 | 0.84000 | 0.84000 | 0.11599 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | GAS TANK1 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
2 | WaterHeater:Mixed | GAS TANK2 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
3 | WaterHeater:Mixed | GAS TANK3 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
4 | WaterHeater:Mixed | GAS TANK4 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
5 | WaterHeater:Mixed | GAS TANK5 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
6 | WaterHeater:Mixed | GAS TANK6 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
7 | WaterHeater:Mixed | GAS TANK7 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | LGSTORE1_WALL_2 | 0 | 118.41 | 56.08 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
2 | LGSTORE1_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
3 | LGSTORE1_WALL_3_DOOR_1 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
4 | LGSTORE1_WALL_3_DOOR_2 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
5 | LGSTORE1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
6 | LGSTORE1_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
7 | LGSTORE1_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
8 | LGSTORE1_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
9 | LGSTORE1_WALL_1_WINDOW_3 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
10 | LGSTORE1_WALL_1_WINDOW_4 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
11 | LGSTORE1_WALL_1_DOOR_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 1 | No | No |
12 | LGSTORE1_WALL_1_DOOR_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 1 | No | No |
13 | LGSTORE1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
14 | LGSTORE1_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
15 | LGSTORE1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
16 | SMSTORE1_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
17 | SMSTORE1_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
18 | SMSTORE1_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
19 | SMSTORE1_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
20 | SMSTORE1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
21 | SMSTORE1_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
22 | SMSTORE1_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
23 | SMSTORE1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
24 | SMSTORE1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
25 | SMSTORE1_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
26 | SMSTORE1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
27 | SMSTORE2_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
28 | SMSTORE2_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
29 | SMSTORE2_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
30 | SMSTORE2_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
31 | SMSTORE2_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
32 | SMSTORE2_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
33 | SMSTORE2_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
34 | SMSTORE2_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
35 | SMSTORE2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
36 | SMSTORE2_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
37 | SMSTORE2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
38 | SMSTORE3_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
39 | SMSTORE3_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
40 | SMSTORE3_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
41 | SMSTORE3_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
42 | SMSTORE3_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
43 | SMSTORE3_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
44 | SMSTORE3_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
45 | SMSTORE3_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
46 | SMSTORE3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
47 | SMSTORE3_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
48 | SMSTORE3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
49 | SMSTORE4_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
50 | SMSTORE4_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
51 | SMSTORE4_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
52 | SMSTORE4_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
53 | SMSTORE4_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
54 | SMSTORE4_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 3 | No | No |
55 | SMSTORE4_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
56 | SMSTORE4_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
57 | SMSTORE4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
58 | SMSTORE4_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
59 | SMSTORE4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
60 | LGSTORE2_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
61 | LGSTORE2_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 4 | No | No |
62 | LGSTORE2_WALL_3_DOOR_1 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
63 | LGSTORE2_WALL_3_DOOR_2 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
64 | LGSTORE2_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
65 | LGSTORE2_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 4 | No | No |
66 | LGSTORE2_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
67 | LGSTORE2_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
68 | LGSTORE2_WALL_1_WINDOW_3 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
69 | LGSTORE2_WALL_1_WINDOW_4 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
70 | LGSTORE2_WALL_1_DOOR_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
71 | LGSTORE2_WALL_1_DOOR_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
72 | LGSTORE2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
73 | LGSTORE2_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
74 | LGSTORE2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
75 | SMSTORE5_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
76 | SMSTORE5_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
77 | SMSTORE5_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
78 | SMSTORE5_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
79 | SMSTORE5_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
80 | SMSTORE5_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
81 | SMSTORE5_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
82 | SMSTORE5_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
83 | SMSTORE5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
84 | SMSTORE5_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
85 | SMSTORE5_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
86 | SMSTORE6_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
87 | SMSTORE6_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
88 | SMSTORE6_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
89 | SMSTORE6_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
90 | SMSTORE6_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
91 | SMSTORE6_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
92 | SMSTORE6_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
93 | SMSTORE6_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
94 | SMSTORE6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
95 | SMSTORE6_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
96 | SMSTORE6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
97 | SMSTORE7_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
98 | SMSTORE7_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
99 | SMSTORE7_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
100 | SMSTORE7_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
101 | SMSTORE7_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
102 | SMSTORE7_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 3 | No | No |
103 | SMSTORE7_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
104 | SMSTORE7_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
105 | SMSTORE7_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
106 | SMSTORE7_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
107 | SMSTORE7_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
108 | SMSTORE8_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 4 | No | No |
109 | SMSTORE8_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 2 | No | No |
110 | SMSTORE8_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 2 | No | No |
111 | SMSTORE8_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 1 | No | No |
112 | SMSTORE8_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
113 | SMSTORE8_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 3 | No | No |
114 | SMSTORE8_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
115 | SMSTORE8_WALL_4 | 0 | 118.41 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 3 | No | No |
116 | SMSTORE8_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
117 | SMSTORE8_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
118 | SMSTORE8_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | LGSTORE1_INFILTRATION | TYPE1_INFIL_SCH | LGSTORE1 | 348.39 | 56.3 | 0.157 | 4.517E-004 | 2.488E-004 | 0.314 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | LGSTORE1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LGSTORE1 | 348.39 | 56.3 | 0.241 | 6.922E-004 | 3.813E-004 | 0.481 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | SMSTORE1_INFILTRATION | TYPE1_INFIL_SCH | SMSTORE1 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | SMSTORE1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE1 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | SMSTORE2_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE2 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | SMSTORE2_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE2 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | SMSTORE3_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE3 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | SMSTORE3_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE3 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | SMSTORE4_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE4 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | SMSTORE4_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE4 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | LGSTORE2_INFILTRATION | TYPE3_INFIL_SCH | LGSTORE2 | 348.39 | 56.3 | 8.993E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | LGSTORE2_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LGSTORE2 | 348.39 | 56.3 | 0.241 | 6.922E-004 | 4.692E-004 | 0.481 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | SMSTORE5_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE5 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | SMSTORE5_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE5 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | SMSTORE6_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE6 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | SMSTORE6_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE6 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | SMSTORE7_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE7 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
18 | SMSTORE7_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE7 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | SMSTORE8_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE8 | 174.19 | 28.1 | 0.112 | 6.453E-004 | 2.994E-004 | 0.448 | 0.000 | 0.000 | 0.224 | 0.000 |
20 | SMSTORE8_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE8 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 3.583E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | LGSTORE1 | Mixing/Well-Stirred |
2 | SMSTORE1 | Mixing/Well-Stirred |
3 | SMSTORE2 | Mixing/Well-Stirred |
4 | SMSTORE3 | Mixing/Well-Stirred |
5 | SMSTORE4 | Mixing/Well-Stirred |
6 | LGSTORE2 | Mixing/Well-Stirred |
7 | SMSTORE5 | Mixing/Well-Stirred |
8 | SMSTORE6 | Mixing/Well-Stirred |
9 | SMSTORE7 | Mixing/Well-Stirred |
10 | SMSTORE8 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone LGSTORE1 | 1.2000 |
3 | Zone SMSTORE1 | 1.2000 |
4 | Zone SMSTORE2 | 1.2000 |
5 | Zone SMSTORE3 | 1.2000 |
6 | Zone SMSTORE4 | 1.2000 |
7 | Zone LGSTORE2 | 1.2000 |
8 | Zone SMSTORE5 | 1.2000 |
9 | Zone SMSTORE6 | 1.2000 |
10 | Zone SMSTORE7 | 1.2000 |
11 | Zone SMSTORE8 | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone LGSTORE1 | 1.2000 |
3 | Zone SMSTORE1 | 1.2000 |
4 | Zone SMSTORE2 | 1.2000 |
5 | Zone SMSTORE3 | 1.2000 |
6 | Zone SMSTORE4 | 1.2000 |
7 | Zone LGSTORE2 | 1.2000 |
8 | Zone SMSTORE5 | 1.2000 |
9 | Zone SMSTORE6 | 1.2000 |
10 | Zone SMSTORE7 | 1.2000 |
11 | Zone SMSTORE8 | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | LGSTORE1 | Cooling | 22044.19772 | 26453.03726 | 1.61884 | 1.94261 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 32.10000 | 1.41196E-002 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
2 | LGSTORE1 | Heating | 25493.11416 | 30591.73699 | 1.09931 | 1.31918 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -10.70000 | 1.50390E-003 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
3 | SMSTORE1 | Cooling | 11969.98937 | 14363.98724 | 0.85400 | 1.02480 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 29.28800 | 1.41146E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
4 | SMSTORE1 | Heating | 11759.94883 | 14111.93860 | 0.50713 | 0.60855 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -10.70000 | 1.50390E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
5 | SMSTORE2 | Cooling | 12050.87448 | 14461.04937 | 0.85968 | 1.03161 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 28.03000 | 1.41123E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
6 | SMSTORE2 | Heating | 11910.33762 | 14292.40515 | 0.51361 | 0.61634 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -10.70000 | 1.50390E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
7 | SMSTORE3 | Cooling | 11981.82038 | 14378.18445 | 0.85460 | 1.02552 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 28.03000 | 1.41123E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
8 | SMSTORE3 | Heating | 11998.81581 | 14398.57898 | 0.51743 | 0.62092 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -10.70000 | 1.50390E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
9 | SMSTORE4 | Cooling | 11963.20831 | 14355.84997 | 0.85327 | 1.02392 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 28.03000 | 1.41123E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
10 | SMSTORE4 | Heating | 12146.27648 | 14575.53177 | 0.52379 | 0.62855 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -10.70000 | 1.50390E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
11 | LGSTORE2 | Cooling | 20805.05788 | 24966.06946 | 1.52767 | 1.83321 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | 31.73000 | 1.41190E-002 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
12 | LGSTORE2 | Heating | 23357.66333 | 28029.19600 | 1.00727 | 1.20873 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -10.70000 | 1.50390E-003 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
13 | SMSTORE5 | Cooling | 11093.24839 | 13311.89807 | 0.78992 | 0.94790 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 29.28800 | 1.41146E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
14 | SMSTORE5 | Heating | 12466.85233 | 14960.22280 | 0.53761 | 0.64514 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -10.70000 | 1.50390E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
15 | SMSTORE6 | Cooling | 11036.54700 | 13243.85639 | 0.78577 | 0.94293 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 29.28800 | 1.41146E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
16 | SMSTORE6 | Heating | 12456.92448 | 14948.30938 | 0.53719 | 0.64462 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -10.70000 | 1.50390E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
17 | SMSTORE7 | Cooling | 10989.56595 | 13187.47914 | 0.78235 | 0.93882 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 29.28800 | 1.41146E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
18 | SMSTORE7 | Heating | 12667.31806 | 15200.78167 | 0.54626 | 0.65551 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -10.70000 | 1.50390E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
19 | SMSTORE8 | Cooling | 11986.14050 | 14383.36860 | 0.85539 | 1.02647 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 29.28800 | 1.41146E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
20 | SMSTORE8 | Heating | 15976.21695 | 19171.46035 | 0.68889 | 0.82667 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -10.70000 | 1.50390E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC_1:1 | Cooling | Sensible | 30132.25 | 1.94261 | 1.94261 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-AC_1:1 | Heating | Sensible | 45974.29 | 1.31918 | 1.31918 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
3 | PSZ-AC_2:2 | Cooling | Sensible | 15944.55 | 1.04122 | 1.04122 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-AC_2:2 | Heating | Sensible | 21820.62 | 0.60855 | 0.60855 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
5 | PSZ-AC_3:3 | Cooling | Sensible | 16004.40 | 1.04644 | 1.04644 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
6 | PSZ-AC_3:3 | Heating | Sensible | 21998.46 | 0.61634 | 0.61634 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
7 | PSZ-AC_4:4 | Cooling | Sensible | 16051.67 | 1.05007 | 1.05007 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
8 | PSZ-AC_4:4 | Heating | Sensible | 22103.09 | 0.62092 | 0.62092 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
9 | PSZ-AC_5:5 | Cooling | Sensible | 15922.70 | 1.04044 | 1.04044 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
10 | PSZ-AC_5:5 | Heating | Sensible | 22277.46 | 0.62855 | 0.62855 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
11 | PSZ-AC_6:6 | Cooling | Sensible | 28526.50 | 1.83321 | 1.83321 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
12 | PSZ-AC_6:6 | Heating | Sensible | 43449.51 | 1.20873 | 1.20873 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
13 | PSZ-AC_7:7 | Cooling | Sensible | 14695.06 | 0.95018 | 0.95018 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
14 | PSZ-AC_7:7 | Heating | Sensible | 22656.56 | 0.64514 | 0.64514 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
15 | PSZ-AC_8:8 | Cooling | Sensible | 14623.80 | 0.94553 | 0.94553 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
16 | PSZ-AC_8:8 | Heating | Sensible | 22644.82 | 0.64462 | 0.64462 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
17 | PSZ-AC_9:9 | Cooling | Sensible | 14599.14 | 0.94242 | 0.94242 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
18 | PSZ-AC_9:9 | Heating | Sensible | 22893.62 | 0.65551 | 0.65551 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
19 | PSZ-AC_10:10 | Cooling | Sensible | 15792.68 | 1.03540 | 1.03540 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
20 | PSZ-AC_10:10 | Heating | Sensible | 26806.07 | 0.82667 | 0.82667 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | LGSTORE1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.94261 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.02480 |
3 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.03161 |
4 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.02552 |
5 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE4 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.02392 |
6 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | LGSTORE2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.83321 |
7 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE5 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.94790 |
8 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.94293 |
9 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE7 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.93882 |
10 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE8 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.02647 |
11 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.94261 |
12 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.94261 |
13 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.94261 |
14 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.94261 |
15 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.94261 |
16 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Main Design Air Flow Rate [m3/s] | 1.94261 |
17 | AirLoopHVAC | PSZ-AC_1:1 | User Heating Air Flow Ratio [] | 1.00000 |
18 | AirLoopHVAC | PSZ-AC_1:1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
19 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.02480 |
20 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.02480 |
21 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.02480 |
22 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.02480 |
23 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.04122 |
24 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Main Design Air Flow Rate [m3/s] | 1.04122 |
25 | AirLoopHVAC | PSZ-AC_2:2 | User Heating Air Flow Ratio [] | 1.00000 |
26 | AirLoopHVAC | PSZ-AC_2:2 | Calculated Heating Air Flow Ratio [] | 0.98423 |
27 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.03161 |
28 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.03161 |
29 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.03161 |
30 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.03161 |
31 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.04644 |
32 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Main Design Air Flow Rate [m3/s] | 1.04644 |
33 | AirLoopHVAC | PSZ-AC_3:3 | User Heating Air Flow Ratio [] | 1.00000 |
34 | AirLoopHVAC | PSZ-AC_3:3 | Calculated Heating Air Flow Ratio [] | 0.98583 |
35 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.02552 |
36 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.02552 |
37 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.02552 |
38 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.02552 |
39 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.05007 |
40 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Main Design Air Flow Rate [m3/s] | 1.05007 |
41 | AirLoopHVAC | PSZ-AC_4:4 | User Heating Air Flow Ratio [] | 1.00000 |
42 | AirLoopHVAC | PSZ-AC_4:4 | Calculated Heating Air Flow Ratio [] | 0.97661 |
43 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.02392 |
44 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.02392 |
45 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.02392 |
46 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.02392 |
47 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.04044 |
48 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Main Design Air Flow Rate [m3/s] | 1.04044 |
49 | AirLoopHVAC | PSZ-AC_5:5 | User Heating Air Flow Ratio [] | 1.00000 |
50 | AirLoopHVAC | PSZ-AC_5:5 | Calculated Heating Air Flow Ratio [] | 0.98412 |
51 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.83321 |
52 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.83321 |
53 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.83321 |
54 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.83321 |
55 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.83321 |
56 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Main Design Air Flow Rate [m3/s] | 1.83321 |
57 | AirLoopHVAC | PSZ-AC_6:6 | User Heating Air Flow Ratio [] | 1.00000 |
58 | AirLoopHVAC | PSZ-AC_6:6 | Calculated Heating Air Flow Ratio [] | 1.00000 |
59 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.94790 |
60 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.94790 |
61 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.94790 |
62 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.94790 |
63 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.95018 |
64 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Main Design Air Flow Rate [m3/s] | 0.95018 |
65 | AirLoopHVAC | PSZ-AC_7:7 | User Heating Air Flow Ratio [] | 1.00000 |
66 | AirLoopHVAC | PSZ-AC_7:7 | Calculated Heating Air Flow Ratio [] | 0.99760 |
67 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.94293 |
68 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.94293 |
69 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.94293 |
70 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.94293 |
71 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.94553 |
72 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Main Design Air Flow Rate [m3/s] | 0.94553 |
73 | AirLoopHVAC | PSZ-AC_8:8 | User Heating Air Flow Ratio [] | 1.00000 |
74 | AirLoopHVAC | PSZ-AC_8:8 | Calculated Heating Air Flow Ratio [] | 0.99725 |
75 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.93882 |
76 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.93882 |
77 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.93882 |
78 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.93882 |
79 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.94242 |
80 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Main Design Air Flow Rate [m3/s] | 0.94242 |
81 | AirLoopHVAC | PSZ-AC_9:9 | User Heating Air Flow Ratio [] | 1.00000 |
82 | AirLoopHVAC | PSZ-AC_9:9 | Calculated Heating Air Flow Ratio [] | 0.99618 |
83 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.02647 |
84 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.02647 |
85 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.02647 |
86 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.02647 |
87 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.03540 |
88 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Main Design Air Flow Rate [m3/s] | 1.03540 |
89 | AirLoopHVAC | PSZ-AC_10:10 | User Heating Air Flow Ratio [] | 1.00000 |
90 | AirLoopHVAC | PSZ-AC_10:10 | Calculated Heating Air Flow Ratio [] | 0.99137 |
91 | AirLoopHVAC | PSZ-AC_1:1 | Design Supply Air Flow Rate [m3/s] | 1.94261 |
92 | AirLoopHVAC | PSZ-AC_2:2 | Design Supply Air Flow Rate [m3/s] | 1.04122 |
93 | AirLoopHVAC | PSZ-AC_3:3 | Design Supply Air Flow Rate [m3/s] | 1.04644 |
94 | AirLoopHVAC | PSZ-AC_4:4 | Design Supply Air Flow Rate [m3/s] | 1.05007 |
95 | AirLoopHVAC | PSZ-AC_5:5 | Design Supply Air Flow Rate [m3/s] | 1.04044 |
96 | AirLoopHVAC | PSZ-AC_6:6 | Design Supply Air Flow Rate [m3/s] | 1.83321 |
97 | AirLoopHVAC | PSZ-AC_7:7 | Design Supply Air Flow Rate [m3/s] | 0.95018 |
98 | AirLoopHVAC | PSZ-AC_8:8 | Design Supply Air Flow Rate [m3/s] | 0.94553 |
99 | AirLoopHVAC | PSZ-AC_9:9 | Design Supply Air Flow Rate [m3/s] | 0.94242 |
100 | AirLoopHVAC | PSZ-AC_10:10 | Design Supply Air Flow Rate [m3/s] | 1.03540 |
101 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.94261 |
102 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41148 |
103 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.94261 |
104 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 2078.68450 |
105 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.94261 |
106 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.94261 |
107 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.94261 |
108 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.28212 |
109 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.94261 |
110 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.97130 |
111 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.29507 |
112 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 44486.31000 |
113 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 22243.15500 |
114 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.72676 |
115 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.72676 |
116 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 44486.31000 |
117 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 60221.17685 |
118 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
119 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
120 | Coil:Heating:Fuel | PSZ-AC_1:1 HEATING COIL | Design Size Nominal Capacity [W] | 60221.17685 |
121 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.04122 |
122 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
123 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.04122 |
124 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1152.79455 |
125 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.04122 |
126 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.04122 |
127 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.04122 |
128 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.68720 |
129 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.04122 |
130 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.52061 |
131 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.69415 |
132 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 23397.33000 |
133 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 11698.66500 |
134 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.73384 |
135 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.73384 |
136 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 23397.33000 |
137 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 31332.33917 |
138 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
139 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
140 | Coil:Heating:Fuel | PSZ-AC_2:2 HEATING COIL | Design Size Nominal Capacity [W] | 31332.33917 |
141 | Controller:OutdoorAir | PSZ-AC_3:3_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.04644 |
142 | Controller:OutdoorAir | PSZ-AC_3:3_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
143 | Fan:SystemModel | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.04644 |
144 | Fan:SystemModel | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1158.57731 |
145 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.04644 |
146 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.04644 |
147 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.04644 |
148 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.69065 |
149 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.04644 |
150 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.52322 |
151 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.69763 |
152 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 23457.67000 |
153 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 11728.83500 |
154 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.73450 |
155 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.73450 |
156 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 23457.67000 |
157 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 31488.06968 |
158 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
159 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
160 | Coil:Heating:Fuel | PSZ-AC_3:3 HEATING COIL | Design Size Nominal Capacity [W] | 31488.06968 |
161 | Controller:OutdoorAir | PSZ-AC_4:4_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.05007 |
162 | Controller:OutdoorAir | PSZ-AC_4:4_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
163 | Fan:SystemModel | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.05007 |
164 | Fan:SystemModel | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1162.59894 |
165 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.05007 |
166 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.05007 |
167 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.05007 |
168 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.69305 |
169 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.05007 |
170 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.52504 |
171 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.70005 |
172 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 23518.84000 |
173 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 11759.42000 |
174 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.73473 |
175 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.73473 |
176 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 23518.84000 |
177 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 31348.78431 |
178 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
179 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
180 | Coil:Heating:Fuel | PSZ-AC_4:4 HEATING COIL | Design Size Nominal Capacity [W] | 31348.78431 |
181 | Controller:OutdoorAir | PSZ-AC_5:5_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.04044 |
182 | Controller:OutdoorAir | PSZ-AC_5:5_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
183 | Fan:SystemModel | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.04044 |
184 | Fan:SystemModel | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1151.93582 |
185 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.04044 |
186 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.04044 |
187 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.04044 |
188 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.68669 |
189 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.04044 |
190 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.52022 |
191 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.69363 |
192 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 23358.15000 |
193 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 11679.07500 |
194 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.73409 |
195 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.73409 |
196 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 23358.15000 |
197 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 31312.32225 |
198 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
199 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
200 | Coil:Heating:Fuel | PSZ-AC_5:5 HEATING COIL | Design Size Nominal Capacity [W] | 31312.32225 |
201 | Controller:OutdoorAir | PSZ-AC_6:6_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.83321 |
202 | Controller:OutdoorAir | PSZ-AC_6:6_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41148 |
203 | Fan:SystemModel | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.83321 |
204 | Fan:SystemModel | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1961.61828 |
205 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.83321 |
206 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.83321 |
207 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.83321 |
208 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.20992 |
209 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.83321 |
210 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.91660 |
211 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.22214 |
212 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 42329.66000 |
213 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 21164.83000 |
214 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.72457 |
215 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.72457 |
216 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 42329.66000 |
217 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 57719.57467 |
218 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
219 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
220 | Coil:Heating:Fuel | PSZ-AC_6:6 HEATING COIL | Design Size Nominal Capacity [W] | 57719.57467 |
221 | Controller:OutdoorAir | PSZ-AC_7:7_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.95018 |
222 | Controller:OutdoorAir | PSZ-AC_7:7_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
223 | Fan:SystemModel | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.95018 |
224 | Fan:SystemModel | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1052.00364 |
225 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.95018 |
226 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.95018 |
227 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.95018 |
228 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.62712 |
229 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.95018 |
230 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.47509 |
231 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.63345 |
232 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 21850.45000 |
233 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 10925.22500 |
234 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.72565 |
235 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.72565 |
236 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 21850.45000 |
237 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 29575.22169 |
238 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
239 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
240 | Coil:Heating:Fuel | PSZ-AC_7:7 HEATING COIL | Design Size Nominal Capacity [W] | 29575.22169 |
241 | Controller:OutdoorAir | PSZ-AC_8:8_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.94553 |
242 | Controller:OutdoorAir | PSZ-AC_8:8_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
243 | Fan:SystemModel | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.94553 |
244 | Fan:SystemModel | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1046.84763 |
245 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.94553 |
246 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.94553 |
247 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.94553 |
248 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.62405 |
249 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.94553 |
250 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.47276 |
251 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.63035 |
252 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 21775.75000 |
253 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 10887.87500 |
254 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.72526 |
255 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.72526 |
256 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 21775.75000 |
257 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 29461.47093 |
258 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
259 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
260 | Coil:Heating:Fuel | PSZ-AC_8:8 HEATING COIL | Design Size Nominal Capacity [W] | 29461.47093 |
261 | Controller:OutdoorAir | PSZ-AC_9:9_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.94242 |
262 | Controller:OutdoorAir | PSZ-AC_9:9_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
263 | Fan:SystemModel | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.94242 |
264 | Fan:SystemModel | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1043.40321 |
265 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.94242 |
266 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.94242 |
267 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.94242 |
268 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.62199 |
269 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.94242 |
270 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.47121 |
271 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.62828 |
272 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 21683.35000 |
273 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 10841.67500 |
274 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.72551 |
275 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.72551 |
276 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 21683.35000 |
277 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 29367.52322 |
278 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
279 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
280 | Coil:Heating:Fuel | PSZ-AC_9:9 HEATING COIL | Design Size Nominal Capacity [W] | 29367.52322 |
281 | Controller:OutdoorAir | PSZ-AC_10:10_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.03540 |
282 | Controller:OutdoorAir | PSZ-AC_10:10_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
283 | Fan:SystemModel | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.03540 |
284 | Fan:SystemModel | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1146.35515 |
285 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.03540 |
286 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.03540 |
287 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.03540 |
288 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.68337 |
289 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.03540 |
290 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.51770 |
291 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.69027 |
292 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 23404.15000 |
293 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 11702.07500 |
294 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.73125 |
295 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.73125 |
296 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 23404.15000 |
297 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 31372.10669 |
298 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
299 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
300 | Coil:Heating:Fuel | PSZ-AC_10:10 HEATING COIL | Design Size Nominal Capacity [W] | 31372.10669 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | 42956.1 | 11.62 | 11.62 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | 22577.4 | 11.76 | 11.76 | |||
3 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | 22633.7 | 11.76 | 11.76 | |||
4 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | 22692.0 | 11.76 | 11.76 | |||
5 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | 22538.9 | 11.76 | 11.76 | |||
6 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | 40885.4 | 11.64 | 11.64 | |||
7 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | 21101.9 | 11.81 | 11.81 | |||
8 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | 21030.9 | 11.81 | 11.81 | |||
9 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | 20940.9 | 11.81 | 11.81 | |||
10 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | 22588.8 | 11.77 | 11.77 |
Zone Name | # Surfaces | |
1 | LGSTORE1 | 15 |
2 | SMSTORE1 | 11 |
3 | SMSTORE2 | 11 |
4 | SMSTORE3 | 11 |
5 | SMSTORE4 | 11 |
6 | LGSTORE2 | 15 |
7 | SMSTORE5 | 11 |
8 | SMSTORE6 | 11 |
9 | SMSTORE7 | 11 |
10 | SMSTORE8 | 11 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | LGSTORE1_WALL_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.600 | 0.551 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | LGSTORE1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.600 | 0.551 | 71.15 | 78.94 | 71.15 | 0.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | LGSTORE1_WALL_3_DOOR_1 | Door | LGSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
4 | LGSTORE1_WALL_3_DOOR_2 | Door | LGSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
5 | LGSTORE1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
6 | LGSTORE1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.600 | 0.551 | 58.18 | 78.94 | 58.18 | 180.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
7 | LGSTORE1_WALL_1_WINDOW_1 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.362_SHGC_0.359 | N/A | 2.057 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
8 | LGSTORE1_WALL_1_WINDOW_2 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.362_SHGC_0.359 | N/A | 2.057 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
9 | LGSTORE1_WALL_1_WINDOW_3 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.362_SHGC_0.359 | N/A | 2.057 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
10 | LGSTORE1_WALL_1_WINDOW_4 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.362_SHGC_0.359 | N/A | 2.057 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
11 | LGSTORE1_WALL_1_DOOR_1 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.362_SHGC_0.359 | N/A | 2.057 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
12 | LGSTORE1_WALL_1_DOOR_2 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.362_SHGC_0.359 | N/A | 2.057 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
13 | LGSTORE1_FLOOR | Floor | CTF - ConductionTransferFunction | LGSTORE1_FLOOR_FFACTOR | 0.141 | 0.136 | 348.39 | 348.39 | 348.39 | 270.00 | 180.00 | 22.86 | 15.24 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | LGSTORE1_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 348.39 | 348.39 | 348.39 | 270.00 | 0.00 | 22.86 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
15 | LGSTORE1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 696.77 | 696.77 | 696.77 | 0.00 | 90.00 | 696.77 | 1.00 | 0.00 | LGSTORE1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
16 | SMSTORE1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.600 | 0.551 | 29.09 | 39.47 | 29.09 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
17 | SMSTORE1_WALL_1_WINDOW_1 | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.362_SHGC_0.359 | N/A | 2.057 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
18 | SMSTORE1_WALL_1_WINDOW_2 | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.362_SHGC_0.359 | N/A | 2.057 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
19 | SMSTORE1_WALL_1_DOOR | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.362_SHGC_0.359 | N/A | 2.057 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
20 | SMSTORE1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | SMSTORE1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.600 | 0.551 | 35.57 | 39.47 | 35.57 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | SMSTORE1_WALL_3_DOOR | Door | SMSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
23 | SMSTORE1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE2_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | SMSTORE1_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE1_FLOOR_FFACTOR | 7.972E-002 | 7.821E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | SMSTORE1_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
26 | SMSTORE1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
27 | SMSTORE2_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.600 | 0.551 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | SMSTORE2_WALL_1_WINDOW_1 | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.362_SHGC_0.359 | N/A | 2.057 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
29 | SMSTORE2_WALL_1_WINDOW_2 | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.362_SHGC_0.359 | N/A | 2.057 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
30 | SMSTORE2_WALL_1_DOOR | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.362_SHGC_0.359 | N/A | 2.057 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
31 | SMSTORE2_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | SMSTORE2_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.600 | 0.551 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | SMSTORE2_WALL_3_DOOR | Door | SMSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
34 | SMSTORE2_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE3_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | SMSTORE2_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE2_FLOOR_FFACTOR | 7.972E-002 | 7.821E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | SMSTORE2_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | SMSTORE2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | SMSTORE3_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.600 | 0.551 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | SMSTORE3_WALL_1_WINDOW_1 | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.362_SHGC_0.359 | N/A | 2.057 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
40 | SMSTORE3_WALL_1_WINDOW_2 | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.362_SHGC_0.359 | N/A | 2.057 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
41 | SMSTORE3_WALL_1_DOOR | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.362_SHGC_0.359 | N/A | 2.057 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
42 | SMSTORE3_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE2_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | SMSTORE3_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.600 | 0.551 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | SMSTORE3_WALL_3_DOOR | Door | SMSTORE3_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
45 | SMSTORE3_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE4_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | SMSTORE3_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE3_FLOOR_FFACTOR | 7.972E-002 | 7.821E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
47 | SMSTORE3_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
48 | SMSTORE3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
49 | SMSTORE4_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.600 | 0.551 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | SMSTORE4_WALL_1_WINDOW_1 | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.362_SHGC_0.359 | N/A | 2.057 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
51 | SMSTORE4_WALL_1_WINDOW_2 | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.362_SHGC_0.359 | N/A | 2.057 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
52 | SMSTORE4_WALL_1_DOOR | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.362_SHGC_0.359 | N/A | 2.057 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | SMSTORE4_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE3_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | SMSTORE4_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.600 | 0.551 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | SMSTORE4_WALL_3_DOOR | Door | SMSTORE4_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | SMSTORE4_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE2_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | SMSTORE4_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE4_FLOOR_FFACTOR | 7.972E-002 | 7.821E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | SMSTORE4_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | SMSTORE4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | LGSTORE2_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE4_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | LGSTORE2_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.600 | 0.551 | 71.19 | 78.94 | 71.19 | 0.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
62 | LGSTORE2_WALL_3_DOOR_1 | Door | LGSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
63 | LGSTORE2_WALL_3_DOOR_2 | Door | LGSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
64 | LGSTORE2_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE5_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LGSTORE2_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.600 | 0.551 | 58.22 | 78.94 | 58.22 | 180.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
66 | LGSTORE2_WALL_1_WINDOW_1 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.362_SHGC_0.359 | N/A | 2.057 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | LGSTORE2_WALL_1_WINDOW_2 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.362_SHGC_0.359 | N/A | 2.057 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | LGSTORE2_WALL_1_WINDOW_3 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.362_SHGC_0.359 | N/A | 2.057 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | LGSTORE2_WALL_1_WINDOW_4 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.362_SHGC_0.359 | N/A | 2.057 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LGSTORE2_WALL_1_DOOR_1 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.362_SHGC_0.359 | N/A | 2.057 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
71 | LGSTORE2_WALL_1_DOOR_2 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.362_SHGC_0.359 | N/A | 2.057 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
72 | LGSTORE2_FLOOR | Floor | CTF - ConductionTransferFunction | LGSTORE2_FLOOR_FFACTOR | 7.972E-002 | 7.821E-002 | 348.39 | 348.39 | 348.39 | 270.00 | 180.00 | 22.86 | 15.24 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
73 | LGSTORE2_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 348.39 | 348.39 | 348.39 | 270.00 | 0.00 | 22.86 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
74 | LGSTORE2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 696.77 | 696.77 | 696.77 | 0.00 | 90.00 | 696.77 | 1.00 | 0.00 | LGSTORE2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
75 | SMSTORE5_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.600 | 0.551 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | SMSTORE5_WALL_1_WINDOW_1 | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.362_SHGC_0.359 | N/A | 2.057 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
77 | SMSTORE5_WALL_1_WINDOW_2 | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.362_SHGC_0.359 | N/A | 2.057 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | SMSTORE5_WALL_1_DOOR | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.362_SHGC_0.359 | N/A | 2.057 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
79 | SMSTORE5_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE2_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | SMSTORE5_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.600 | 0.551 | 35.59 | 39.47 | 35.59 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | SMSTORE5_WALL_3_DOOR | Door | SMSTORE5_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
82 | SMSTORE5_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE6_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
83 | SMSTORE5_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE5_FLOOR_FFACTOR | 7.972E-002 | 7.821E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
84 | SMSTORE5_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
85 | SMSTORE5_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE5_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | SMSTORE6_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.600 | 0.551 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | SMSTORE6_WALL_1_WINDOW_1 | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.362_SHGC_0.359 | N/A | 2.057 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | SMSTORE6_WALL_1_WINDOW_2 | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.362_SHGC_0.359 | N/A | 2.057 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
89 | SMSTORE6_WALL_1_DOOR | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.362_SHGC_0.359 | N/A | 2.057 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | SMSTORE6_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE5_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | SMSTORE6_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.600 | 0.551 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | SMSTORE6_WALL_3_DOOR | Door | SMSTORE6_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
93 | SMSTORE6_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE7_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | SMSTORE6_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE6_FLOOR_FFACTOR | 7.972E-002 | 7.821E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
95 | SMSTORE6_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
96 | SMSTORE6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
97 | SMSTORE7_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.600 | 0.551 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | SMSTORE7_WALL_1_WINDOW_1 | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.362_SHGC_0.359 | N/A | 2.057 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | SMSTORE7_WALL_1_WINDOW_2 | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.362_SHGC_0.359 | N/A | 2.057 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
100 | SMSTORE7_WALL_1_DOOR | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.362_SHGC_0.359 | N/A | 2.057 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
101 | SMSTORE7_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE6_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
102 | SMSTORE7_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.600 | 0.551 | 35.59 | 39.47 | 35.59 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | SMSTORE7_WALL_3_DOOR | Door | SMSTORE7_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
104 | SMSTORE7_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE8_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | SMSTORE7_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE7_FLOOR_FFACTOR | 7.972E-002 | 7.821E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
106 | SMSTORE7_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
107 | SMSTORE7_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE7_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
108 | SMSTORE8_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.600 | 0.551 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | SMSTORE8_WALL_1_WINDOW_1 | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.362_SHGC_0.359 | N/A | 2.057 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
110 | SMSTORE8_WALL_1_WINDOW_2 | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.362_SHGC_0.359 | N/A | 2.057 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
111 | SMSTORE8_WALL_1_DOOR | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.362_SHGC_0.359 | N/A | 2.057 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
112 | SMSTORE8_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE7_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | SMSTORE8_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.600 | 0.551 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | SMSTORE8_WALL_3_DOOR | Door | SMSTORE8_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
115 | SMSTORE8_WALL_4 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.600 | 0.551 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | SMSTORE8_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE8_FLOOR_FFACTOR | 0.203 | 0.194 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | SMSTORE8_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | SMSTORE8_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE8_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | LGSTORE1 | RunPeriod: RUNPERIOD 1 | 6.7259944813E-002 | 0.3553553528 | Pass | Pass | 8.4378511366E-002 | 0.3890814056 | Pass | Pass |
2 | SMSTORE1 | RunPeriod: RUNPERIOD 1 | 5.2349047459E-002 | 0.2744711219 | Pass | Pass | 0.1077082426 | 0.2526451561 | Pass | Pass |
3 | SMSTORE2 | RunPeriod: RUNPERIOD 1 | 6.8330990383E-002 | 0.3516385133 | Pass | Pass | 3.6600465605E-002 | 0.1072010312 | Pass | Pass |
4 | SMSTORE3 | RunPeriod: RUNPERIOD 1 | 7.5442282613E-002 | 0.3862176742 | Pass | Pass | 3.3921690644E-002 | 0.1015488712 | Pass | Pass |
5 | SMSTORE4 | RunPeriod: RUNPERIOD 1 | 7.9865055972E-002 | 0.4039072012 | Pass | Pass | 3.2386406081E-002 | 0.1008100198 | Pass | Pass |
6 | LGSTORE2 | RunPeriod: RUNPERIOD 1 | 9.0725103456E-002 | 0.4238035944 | Pass | Pass | 3.2764908009E-002 | 0.1166735927 | Pass | Pass |
7 | SMSTORE5 | RunPeriod: RUNPERIOD 1 | 8.9481762965E-002 | 0.4210864541 | Pass | Pass | 2.4993833433E-002 | 8.2262623797E-002 | Pass | Pass |
8 | SMSTORE6 | RunPeriod: RUNPERIOD 1 | 8.9740784641E-002 | 0.4219484226 | Pass | Pass | 5.0986376895E-002 | 0.3232609049 | Pass | Pass |
9 | SMSTORE7 | RunPeriod: RUNPERIOD 1 | 0.1047853744 | 0.4113806433 | Pass | Pass | 3.0580252886E-002 | 0.1087652173 | Pass | Pass |
10 | SMSTORE8 | RunPeriod: RUNPERIOD 1 | 0.2315108843 | 0.4691288202 | Pass | Pass | 0.2581106471 | 0.8668522309 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:31
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 4097.08 | 170.06 | 0.00 | 384.01 | 688.50 | 5339.69 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:31
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | -10.70 | 0.00 | -10.70 | Wetbulb [C] | 7.50 | 320.00 |
NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 32.10 | 7.40 | 23.10 | Wetbulb [C] | 5.60 | 230.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 172.00 | 59 | |||
Feb | 49.00 | 37 | |||
Mar | 40.00 | 38 | |||
Apr | 70.00 | 48 | |||
May | 70.00 | 36 | |||
Jun | 25.00 | 15 | |||
Jul | 64.00 | 20 | |||
Aug | 2.00 | 4 | |||
Sep | 73.00 | 32 | |||
Oct | 7.00 | 8 | |||
Nov | 88.00 | 34 | |||
Dec | 62.00 | 39 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:31
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_2 | NONRES_EXT_WALL_GRD | 0.30 | 0.551 | 0.600 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE1_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.551 | 0.600 | 78.94 | 71.15 | 0.00 | 90.00 | N |
LGSTORE1_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.551 | 0.600 | 78.94 | 58.18 | 180.00 | 90.00 | S |
LGSTORE1_FLOOR | LGSTORE1_FLOOR_FFACTOR | 1.00 | 0.138 | 0.141 | 348.39 | 348.39 | 270.00 | 180.00 | |
LGSTORE1_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 348.39 | 348.39 | 270.00 | 0.00 | |
SMSTORE1_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.551 | 0.600 | 39.47 | 29.09 | 180.00 | 90.00 | S |
SMSTORE1_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.551 | 0.600 | 39.47 | 35.57 | 0.00 | 90.00 | N |
SMSTORE1_FLOOR | SMSTORE1_FLOOR_FFACTOR | 1.00 | 0.079 | 0.080 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE1_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE2_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.551 | 0.600 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE2_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.551 | 0.600 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE2_FLOOR | SMSTORE2_FLOOR_FFACTOR | 1.00 | 0.079 | 0.080 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE2_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE3_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.551 | 0.600 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE3_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.551 | 0.600 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE3_FLOOR | SMSTORE3_FLOOR_FFACTOR | 1.00 | 0.079 | 0.080 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE3_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE4_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.551 | 0.600 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE4_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.551 | 0.600 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE4_FLOOR | SMSTORE4_FLOOR_FFACTOR | 1.00 | 0.079 | 0.080 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE4_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
LGSTORE2_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.551 | 0.600 | 78.94 | 71.19 | 0.00 | 90.00 | N |
LGSTORE2_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.551 | 0.600 | 78.94 | 58.22 | 180.00 | 90.00 | S |
LGSTORE2_FLOOR | LGSTORE2_FLOOR_FFACTOR | 1.00 | 0.079 | 0.080 | 348.39 | 348.39 | 270.00 | 180.00 | |
LGSTORE2_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 348.39 | 348.39 | 270.00 | 0.00 | |
SMSTORE5_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.551 | 0.600 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE5_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.551 | 0.600 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE5_FLOOR | SMSTORE5_FLOOR_FFACTOR | 1.00 | 0.079 | 0.080 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE5_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE6_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.551 | 0.600 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE6_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.551 | 0.600 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE6_FLOOR | SMSTORE6_FLOOR_FFACTOR | 1.00 | 0.079 | 0.080 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE6_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE7_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.551 | 0.600 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE7_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.551 | 0.600 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE7_FLOOR | SMSTORE7_FLOOR_FFACTOR | 1.00 | 0.079 | 0.080 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE7_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE8_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.551 | 0.600 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE8_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.551 | 0.600 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE8_WALL_4 | NONRES_EXT_WALL_GRD | 0.30 | 0.551 | 0.600 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE8_FLOOR | SMSTORE8_FLOOR_FFACTOR | 1.00 | 0.197 | 0.203 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE8_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE1_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE2_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE2_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE3_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE3_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE4_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE4_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
LGSTORE2_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE2_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE5_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE5_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE6_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE6_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE7_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE7_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE8_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 696.77 | 0.00 | 90.00 | N | ||
SMSTORE1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
LGSTORE2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 696.77 | 0.00 | 90.00 | N | ||
SMSTORE5_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE7_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE8_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.362_SHGC_0.359 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.057 | 0.360 | 0.396 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.362_SHGC_0.359 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.057 | 0.360 | 0.396 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_3 | NONRESWINDOW_U_0.362_SHGC_0.359 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.057 | 0.360 | 0.396 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_4 | NONRESWINDOW_U_0.362_SHGC_0.359 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.057 | 0.360 | 0.396 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_DOOR_1 | NONRESWINDOW_U_0.362_SHGC_0.359 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.057 | 0.360 | 0.396 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_DOOR_2 | NONRESWINDOW_U_0.362_SHGC_0.359 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.057 | 0.360 | 0.396 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.362_SHGC_0.359 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.057 | 0.360 | 0.396 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.362_SHGC_0.359 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.057 | 0.360 | 0.396 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_DOOR | NONRESWINDOW_U_0.362_SHGC_0.359 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.057 | 0.360 | 0.396 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.362_SHGC_0.359 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.057 | 0.360 | 0.396 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.362_SHGC_0.359 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.057 | 0.360 | 0.396 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_DOOR | NONRESWINDOW_U_0.362_SHGC_0.359 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.057 | 0.360 | 0.396 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.362_SHGC_0.359 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.057 | 0.360 | 0.396 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.362_SHGC_0.359 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.057 | 0.360 | 0.396 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_DOOR | NONRESWINDOW_U_0.362_SHGC_0.359 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.057 | 0.360 | 0.396 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.362_SHGC_0.359 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.057 | 0.360 | 0.396 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.362_SHGC_0.359 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.057 | 0.360 | 0.396 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_DOOR | NONRESWINDOW_U_0.362_SHGC_0.359 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.057 | 0.360 | 0.396 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.362_SHGC_0.359 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.057 | 0.360 | 0.396 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.362_SHGC_0.359 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.057 | 0.360 | 0.396 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_3 | NONRESWINDOW_U_0.362_SHGC_0.359 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.057 | 0.360 | 0.396 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_4 | NONRESWINDOW_U_0.362_SHGC_0.359 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.057 | 0.360 | 0.396 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_DOOR_1 | NONRESWINDOW_U_0.362_SHGC_0.359 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.057 | 0.360 | 0.396 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_DOOR_2 | NONRESWINDOW_U_0.362_SHGC_0.359 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.057 | 0.360 | 0.396 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.362_SHGC_0.359 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.057 | 0.360 | 0.396 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.362_SHGC_0.359 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.057 | 0.360 | 0.396 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_DOOR | NONRESWINDOW_U_0.362_SHGC_0.359 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.057 | 0.360 | 0.396 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.362_SHGC_0.359 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.057 | 0.360 | 0.396 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.362_SHGC_0.359 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.057 | 0.360 | 0.396 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_DOOR | NONRESWINDOW_U_0.362_SHGC_0.359 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.057 | 0.360 | 0.396 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.362_SHGC_0.359 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.057 | 0.360 | 0.396 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.362_SHGC_0.359 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.057 | 0.360 | 0.396 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_DOOR | NONRESWINDOW_U_0.362_SHGC_0.359 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.057 | 0.360 | 0.396 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.362_SHGC_0.359 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.057 | 0.360 | 0.396 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.362_SHGC_0.359 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.057 | 0.360 | 0.396 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_DOOR | NONRESWINDOW_U_0.362_SHGC_0.359 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.057 | 0.360 | 0.396 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
Total or Average | 124.40 | 2.057 | 0.360 | 0.396 | |||||||||||||||||
North Total or Average | 0.00 | - | - | - | |||||||||||||||||
Non-North Total or Average | 124.40 | 2.057 | 0.360 | 0.396 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
LGSTORE1_WALL_3_DOOR_1 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.90 | LGSTORE1_WALL_3 |
LGSTORE1_WALL_3_DOOR_2 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.90 | LGSTORE1_WALL_3 |
SMSTORE1_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.90 | SMSTORE1_WALL_3 |
SMSTORE2_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE2_WALL_3 |
SMSTORE3_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE3_WALL_3 |
SMSTORE4_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE4_WALL_3 |
LGSTORE2_WALL_3_DOOR_1 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | LGSTORE2_WALL_3 |
LGSTORE2_WALL_3_DOOR_2 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | LGSTORE2_WALL_3 |
SMSTORE5_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE5_WALL_3 |
SMSTORE6_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE6_WALL_3 |
SMSTORE7_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE7_WALL_3 |
SMSTORE8_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE8_WALL_3 |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:31
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
LGSTORE1_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_DOOR_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_DOOR_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_DOOR_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_DOOR_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:31
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
LGSTORE1_LIGHTS | LGSTORE1 | LGSTORE1 | GENERAL | 9.6053 | 348.39 | 3346.35 | LightsWired | LTG_SCH_BASE_LPD1 | 83.91 | 168.00 | 82.62 | 0.0000 | Y | 51.90 |
LGSTORE1_LIGHTS_ALLOWANCE | LGSTORE1 | LGSTORE1 | GENERAL | 5.6969 | 348.39 | 1984.73 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | 97.50 | 112.00 | 94.53 | 0.0000 | Y | 35.22 |
SMSTORE1_LIGHTS | SMSTORE1 | SMSTORE1 | GENERAL | 9.7206 | 174.19 | 1693.26 | LightsWired | LTG_SCH_BASE_SMALL_LPD1 | 85.41 | 168.00 | 84.05 | 0.0000 | Y | 26.72 |
SMSTORE1_LIGHTS_ALLOWANCE | SMSTORE1 | SMSTORE1 | GENERAL | 8.5685 | 174.19 | 1492.57 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | 97.50 | 112.00 | 94.53 | 0.0000 | Y | 26.49 |
SMSTORE2_LIGHTS | SMSTORE2 | SMSTORE2 | GENERAL | 9.6995 | 174.19 | 1689.58 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 68.73 | 168.00 | 65.95 | 0.0000 | Y | 20.92 |
SMSTORE2_LIGHTS_ALLOWANCE | SMSTORE2 | SMSTORE2 | GENERAL | 6.9539 | 174.19 | 1211.32 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 84.29 | 73.25 | 0.0000 | Y | 16.66 |
SMSTORE3_LIGHTS | SMSTORE3 | SMSTORE3 | GENERAL | 9.6995 | 174.19 | 1689.58 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 68.73 | 168.00 | 65.95 | 0.0000 | Y | 20.92 |
SMSTORE3_LIGHTS_ALLOWANCE | SMSTORE3 | SMSTORE3 | GENERAL | 6.9539 | 174.19 | 1211.32 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 84.29 | 73.25 | 0.0000 | Y | 16.66 |
SMSTORE4_LIGHTS | SMSTORE4 | SMSTORE4 | GENERAL | 9.6995 | 174.19 | 1689.58 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 68.73 | 168.00 | 65.95 | 0.0000 | Y | 20.92 |
SMSTORE4_LIGHTS_ALLOWANCE | SMSTORE4 | SMSTORE4 | GENERAL | 6.9539 | 174.19 | 1211.32 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 84.29 | 73.25 | 0.0000 | Y | 16.66 |
LGSTORE2_LIGHTS | LGSTORE2 | LGSTORE2 | GENERAL | 9.5842 | 348.39 | 3339.00 | LightsWired | LTG_SCH_BASE_LPD2 | 62.11 | 168.00 | 59.29 | 0.0000 | Y | 37.16 |
LGSTORE2_LIGHTS_ALLOWANCE | LGSTORE2 | LGSTORE2 | GENERAL | 0.0000 | 348.39 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE5_LIGHTS | SMSTORE5 | SMSTORE5 | GENERAL | 9.6995 | 174.19 | 1689.58 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 60.29 | 0.0000 | Y | 19.12 |
SMSTORE5_LIGHTS_ALLOWANCE | SMSTORE5 | SMSTORE5 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE6_LIGHTS | SMSTORE6 | SMSTORE6 | GENERAL | 9.6995 | 174.19 | 1689.58 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 60.29 | 0.0000 | Y | 19.12 |
SMSTORE6_LIGHTS_ALLOWANCE | SMSTORE6 | SMSTORE6 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE7_LIGHTS | SMSTORE7 | SMSTORE7 | GENERAL | 9.6995 | 174.19 | 1689.58 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 60.29 | 0.0000 | Y | 19.12 |
SMSTORE7_LIGHTS_ALLOWANCE | SMSTORE7 | SMSTORE7 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE8_LIGHTS | SMSTORE8 | SMSTORE8 | GENERAL | 9.6995 | 174.19 | 1689.58 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 60.29 | 0.0000 | Y | 19.12 |
SMSTORE8_LIGHTS_ALLOWANCE | SMSTORE8 | SMSTORE8 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
Interior Lighting Total | 6.5342 | 4180.64 | 27316.92 | 366.68 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 455.59 | AstronomicalClock | - | 42.43 | 42.43 | 3.63 | |
EXTERIOR_LIGHTS_B | 2744.24 | AstronomicalClock | - | 83.64 | 63.04 | 32.47 | |
EXTERIOR_LIGHTS_C | 2307.23 | AstronomicalClock | - | 83.64 | 56.04 | 24.27 | |
Exterior Lighting Total | 5507.06 | 60.37 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:31
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 44486.31 | 32330.87 | 12155.44 | 0.73 | 3.73 | |||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 23397.33 | 17169.90 | 6227.43 | 0.73 | 3.80 | |||
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 23457.67 | 17229.66 | 6228.01 | 0.73 | 3.80 | |||
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 23518.84 | 17280.00 | 6238.84 | 0.73 | 3.80 | |||
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 23358.15 | 17146.98 | 6211.17 | 0.73 | 3.80 | |||
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 42329.66 | 30670.80 | 11658.86 | 0.72 | 3.73 | |||
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 21850.45 | 15855.78 | 5994.67 | 0.73 | 3.80 | |||
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 21775.75 | 15793.08 | 5982.67 | 0.73 | 3.80 | |||
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 21683.35 | 15731.49 | 5951.86 | 0.73 | 3.80 | |||
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 23404.15 | 17114.28 | 6289.87 | 0.73 | 3.80 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC_1:1 COOLING COIL | 42956.1 | 11.62 | 11.62 | ||||
PSZ-AC_2:2 COOLING COIL | 22577.4 | 11.76 | 11.76 | ||||
PSZ-AC_3:3 COOLING COIL | 22633.7 | 11.76 | 11.76 | ||||
PSZ-AC_4:4 COOLING COIL | 22692.0 | 11.76 | 11.76 | ||||
PSZ-AC_5:5 COOLING COIL | 22538.9 | 11.76 | 11.76 | ||||
PSZ-AC_6:6 COOLING COIL | 40885.4 | 11.64 | 11.64 | ||||
PSZ-AC_7:7 COOLING COIL | 21101.9 | 11.81 | 11.81 | ||||
PSZ-AC_8:8 COOLING COIL | 21030.9 | 11.81 | 11.81 | ||||
PSZ-AC_9:9 COOLING COIL | 20940.9 | 11.81 | 11.81 | ||||
PSZ-AC_10:10 COOLING COIL | 22588.8 | 11.77 | 11.77 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | 60221.18 | 0.80 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | 31332.34 | 0.80 | |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | 31488.07 | 0.80 | |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | 31348.78 | 0.80 | |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | 31312.32 | 0.80 | |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | 57719.57 | 0.80 | |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | 29575.22 | 0.80 | |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | 29461.47 | 0.80 | |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | 29367.52 | 0.80 | |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | 31372.11 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 1.94 | 2078.68 | 1070.05 | 1.00 | 1.32 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.04 | 1152.79 | 1107.16 | 1.00 | 1.39 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 |
PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.05 | 1158.58 | 1107.16 | 1.00 | 1.39 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 |
PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.05 | 1162.60 | 1107.16 | 1.00 | 1.39 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 |
PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.04 | 1151.94 | 1107.16 | 1.00 | 1.39 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 |
PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 1.83 | 1961.62 | 1070.05 | 1.00 | 1.33 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.95 | 1052.00 | 1107.16 | 1.00 | 1.42 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 |
PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.95 | 1046.85 | 1107.16 | 1.00 | 1.42 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 |
PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.94 | 1043.40 | 1107.16 | 1.00 | 1.42 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 |
PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.04 | 1146.36 | 1107.16 | 1.00 | 1.39 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
GAS TANK1 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK2 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK3 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK4 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK5 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK6 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK7 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:31
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
LGSTORE1 | 22044.20 | 26453.04 | 75.93 | 1.619 | 1.943 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 23.89 | 23.89 | 0.00981 | 32.10 | 0.01412 | 0.411 | 0.00 |
SMSTORE1 | 11969.99 | 14363.99 | 82.46 | 0.854 | 1.025 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 23.89 | 23.89 | 0.00937 | 29.29 | 0.01411 | 0.206 | 0.00 |
SMSTORE2 | 12050.87 | 14461.05 | 83.02 | 0.860 | 1.032 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 23.89 | 23.89 | 0.00952 | 28.03 | 0.01411 | 0.206 | 0.00 |
SMSTORE3 | 11981.82 | 14378.18 | 82.54 | 0.855 | 1.026 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 23.89 | 23.89 | 0.00951 | 28.03 | 0.01411 | 0.206 | 0.00 |
SMSTORE4 | 11963.21 | 14355.85 | 82.41 | 0.853 | 1.024 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 23.89 | 23.89 | 0.00954 | 28.03 | 0.01411 | 0.206 | 0.00 |
LGSTORE2 | 20805.06 | 24966.07 | 71.66 | 1.528 | 1.833 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | 23.89 | 23.89 | 0.00980 | 31.73 | 0.01412 | 0.411 | 0.00 |
SMSTORE5 | 11093.25 | 13311.90 | 76.42 | 0.790 | 0.948 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 23.89 | 23.88 | 0.00958 | 29.29 | 0.01411 | 0.206 | 0.00 |
SMSTORE6 | 11036.55 | 13243.86 | 76.03 | 0.786 | 0.943 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 23.89 | 23.88 | 0.00960 | 29.29 | 0.01411 | 0.206 | 0.00 |
SMSTORE7 | 10989.57 | 13187.48 | 75.71 | 0.782 | 0.939 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 23.89 | 23.88 | 0.00962 | 29.29 | 0.01411 | 0.206 | 0.00 |
SMSTORE8 | 11986.14 | 14383.37 | 82.57 | 0.855 | 1.026 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 23.89 | 23.88 | 0.00956 | 29.29 | 0.01411 | 0.206 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
LGSTORE1 | 25493.11 | 30591.74 | 87.81 | 1.099 | 1.319 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00648 | -10.70 | 0.00150 | 0.411 | 0.00 |
SMSTORE1 | 11759.95 | 14111.94 | 81.01 | 0.507 | 0.609 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00644 | -10.70 | 0.00150 | 0.206 | 0.00 |
SMSTORE2 | 11910.34 | 14292.41 | 82.05 | 0.514 | 0.616 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00645 | -10.70 | 0.00150 | 0.206 | 0.00 |
SMSTORE3 | 11998.82 | 14398.58 | 82.66 | 0.517 | 0.621 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00646 | -10.70 | 0.00150 | 0.206 | 0.00 |
SMSTORE4 | 12146.28 | 14575.53 | 83.67 | 0.524 | 0.629 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00647 | -10.70 | 0.00150 | 0.206 | 0.00 |
LGSTORE2 | 23357.66 | 28029.20 | 80.45 | 1.007 | 1.209 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00654 | -10.70 | 0.00150 | 0.411 | 0.00 |
SMSTORE5 | 12466.85 | 14960.22 | 85.88 | 0.538 | 0.645 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00650 | -10.70 | 0.00150 | 0.206 | 0.00 |
SMSTORE6 | 12456.92 | 14948.31 | 85.81 | 0.537 | 0.645 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00650 | -10.70 | 0.00150 | 0.206 | 0.00 |
SMSTORE7 | 12667.32 | 15200.78 | 87.26 | 0.546 | 0.656 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00651 | -10.70 | 0.00150 | 0.206 | 0.00 |
SMSTORE8 | 15976.22 | 19171.46 | 110.06 | 0.689 | 0.827 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00651 | -10.70 | 0.00150 | 0.206 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC_1:1 | 1.94 | 1.94 | 1.32 | 1.32 | 1.9426 | 1.9426 | 1.9426 | 1.0000 | 1.0000 |
PSZ-AC_2:2 | 1.04 | 1.04 | 0.61 | 0.61 | 1.0412 | 1.0248 | 1.0412 | 0.9842 | 1.0000 |
PSZ-AC_3:3 | 1.05 | 1.05 | 0.62 | 0.62 | 1.0464 | 1.0316 | 1.0464 | 0.9858 | 1.0000 |
PSZ-AC_4:4 | 1.05 | 1.05 | 0.62 | 0.62 | 1.0501 | 1.0255 | 1.0501 | 0.9766 | 1.0000 |
PSZ-AC_5:5 | 1.04 | 1.04 | 0.63 | 0.63 | 1.0404 | 1.0239 | 1.0404 | 0.9841 | 1.0000 |
PSZ-AC_6:6 | 1.83 | 1.83 | 1.21 | 1.21 | 1.8332 | 1.8332 | 1.8332 | 1.0000 | 1.0000 |
PSZ-AC_7:7 | 0.95 | 0.95 | 0.65 | 0.65 | 0.9502 | 0.9479 | 0.9502 | 0.9976 | 1.0000 |
PSZ-AC_8:8 | 0.95 | 0.95 | 0.64 | 0.64 | 0.9455 | 0.9429 | 0.9455 | 0.9973 | 1.0000 |
PSZ-AC_9:9 | 0.94 | 0.94 | 0.66 | 0.66 | 0.9424 | 0.9388 | 0.9424 | 0.9962 | 1.0000 |
PSZ-AC_10:10 | 1.04 | 1.04 | 0.83 | 0.83 | 1.0354 | 1.0265 | 1.0354 | 0.9914 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 44486.310 | 32330.871 | 1.942610 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 22243.15 | 16203.35 | 1.295073 | 26.49 | 19.04 | 0.01072303 | 12.80 | 12.09 | 0.00850000 | 32.10 | 0.01411964 | 23.13 | 31.7726 | 23.89 | 0.00981022 | 53.0400 | 22044.20 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_1:1 | 60221.177 | 60221.177 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 60221.18 | 60221.18 | 1.942610 | 14.37 | 9.55 | 0.00542965 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 21.1818 | 21.10 | 0.00648466 | 41.7360 | 25493.11 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 23397.330 | 17169.897 | 1.041220 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | 11698.67 | 8626.17 | 0.694147 | 26.39 | 18.92 | 0.01060906 | 12.80 | 12.09 | 0.00850000 | 31.98 | 0.01411942 | 23.10 | 29.6392 | 23.89 | 0.00974243 | 52.6786 | 11791.64 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_2:2 | 31332.339 | 31332.339 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 31332.34 | 31332.34 | 1.041219 | 14.82 | 9.79 | 0.00546075 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 19.7595 | 21.10 | 0.00643514 | 41.4193 | 11759.95 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_3:3 | 23457.670 | 17229.659 | 1.046440 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | 11728.83 | 8656.62 | 0.697627 | 26.36 | 18.90 | 0.01059856 | 12.80 | 12.09 | 0.00850000 | 31.92 | 0.01411931 | 23.08 | 29.4913 | 23.89 | 0.00973516 | 52.6399 | 11840.71 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_3:3 | 31488.070 | 31488.070 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 31488.07 | 31488.07 | 1.046442 | 14.85 | 9.82 | 0.00547669 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 19.6609 | 21.10 | 0.00644893 | 41.5071 | 11910.34 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_4:4 | 23518.840 | 17279.997 | 1.050070 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | 11759.42 | 8684.62 | 0.700047 | 26.36 | 18.90 | 0.01059281 | 12.80 | 12.09 | 0.00850000 | 31.92 | 0.01411931 | 23.08 | 29.3894 | 23.89 | 0.00973162 | 52.6211 | 11880.16 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_4:4 | 31348.784 | 31348.784 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 31348.78 | 31348.78 | 1.050074 | 14.87 | 9.84 | 0.00548628 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 19.5928 | 21.10 | 0.00645666 | 41.5564 | 11998.82 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_5:5 | 23358.150 | 17146.984 | 1.040440 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | 11679.08 | 8610.53 | 0.693627 | 26.37 | 18.91 | 0.01060858 | 12.80 | 12.09 | 0.00850000 | 31.92 | 0.01411931 | 23.08 | 29.6614 | 23.89 | 0.00974134 | 52.6728 | 11771.15 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_5:5 | 31312.322 | 31312.322 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 31312.32 | 31312.32 | 1.040443 | 14.82 | 9.81 | 0.00548773 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 19.7742 | 21.10 | 0.00646968 | 41.6394 | 12146.28 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_6:6 | 42329.660 | 30670.802 | 1.833210 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | 21164.83 | 15317.73 | 1.222140 | 26.56 | 19.11 | 0.01078651 | 12.80 | 12.09 | 0.00850000 | 31.92 | 0.01411931 | 23.08 | 33.6687 | 23.89 | 0.00981951 | 53.0887 | 20734.48 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_6:6 | 57719.575 | 57719.575 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 57719.57 | 57719.57 | 1.833207 | 13.97 | 9.35 | 0.00541203 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 22.4458 | 21.10 | 0.00654313 | 42.1063 | 23357.66 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_7:7 | 21850.450 | 15855.779 | 0.950180 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | 10925.23 | 7917.04 | 0.633453 | 26.53 | 19.09 | 0.01077127 | 12.80 | 12.09 | 0.00850000 | 31.92 | 0.01411931 | 23.08 | 32.4790 | 23.89 | 0.00984205 | 53.2088 | 10747.07 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_7:7 | 29575.222 | 29575.222 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 29575.22 | 29575.22 | 0.950183 | 14.22 | 9.47 | 0.00541589 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 21.6526 | 21.10 | 0.00649703 | 41.8136 | 12466.85 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_8:8 | 21775.750 | 15793.080 | 0.945530 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | 10887.88 | 7881.65 | 0.630353 | 26.54 | 19.10 | 0.01078147 | 12.80 | 12.09 | 0.00850000 | 31.92 | 0.01411931 | 23.08 | 32.6387 | 23.89 | 0.00984840 | 53.2426 | 10686.76 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_8:8 | 29461.471 | 29461.471 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 29461.47 | 29461.47 | 0.945526 | 14.19 | 9.45 | 0.00540995 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 21.7592 | 21.10 | 0.00649625 | 41.8086 | 12456.92 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_9:9 | 21683.350 | 15731.487 | 0.942420 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | 10841.67 | 7847.18 | 0.628280 | 26.53 | 19.10 | 0.01078074 | 12.80 | 12.09 | 0.00850000 | 31.85 | 0.01411920 | 23.06 | 32.7465 | 23.89 | 0.00984659 | 53.2329 | 10665.57 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_9:9 | 29367.523 | 29367.523 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 29367.52 | 29367.52 | 0.942415 | 14.16 | 9.45 | 0.00541974 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 21.8311 | 21.10 | 0.00651336 | 41.9176 | 12667.32 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_10:10 | 23404.150 | 17114.285 | 1.035400 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | 11702.08 | 8535.05 | 0.690267 | 26.35 | 18.97 | 0.01069154 | 12.80 | 12.09 | 0.00850000 | 31.73 | 0.01411898 | 23.03 | 29.8058 | 23.88 | 0.00983842 | 53.1902 | 11715.17 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_10:10 | 31372.107 | 31372.107 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 31372.11 | 31372.11 | 1.035403 | 14.78 | 9.83 | 0.00551560 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 19.8705 | 21.10 | 0.00651042 | 41.9028 | 15976.22 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:37:31
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 44486.310 | 32330.871 | 1.942610 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.7736 | 1004.8586 | 1.2036 | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.942610 | 2.33811561 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | Sensible | 22243.15 | 16203.35 | 1.0000 | 1.55874376 | 1.295073 | 26.49 | 19.04 | 0.01072303 | 53966.6 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 22243.15 | 32.10 | 0.01411964 | 23.13 | 0.41147883 | 31.7726 | 23.89 | 0.00981022 | 23.89 | 0.00981022 | 53.0400 | 22044.20 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 60221.177 | 60221.177 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.942610 | 2.33811561 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 60221.18 | 60221.18 | 1.0000 | 2.33811561 | 1.942610 | 14.37 | 9.55 | 0.00542965 | 28162.0 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 60221.18 | -10.70 | 0.00150390 | -10.70 | 0.41147883 | 21.1818 | 21.11 | 0.00648466 | 21.10 | 0.00648466 | 41.7360 | 25493.11 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 23397.330 | 17169.897 | 1.041220 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.5617 | 1004.8586 | 1.2036 | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.041219 | 1.25320579 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | Sensible | 11698.67 | 8626.17 | 1.0000 | 0.83547144 | 0.694147 | 26.39 | 18.92 | 0.01060906 | 53565.9 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11698.67 | 31.98 | 0.01411942 | 23.10 | 0.20573941 | 29.6392 | 23.89 | 0.00974243 | 23.89 | 0.00974243 | 52.6786 | 11791.64 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 31332.339 | 31332.339 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.041219 | 1.25320579 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 31332.34 | 31332.34 | 1.0000 | 1.25320579 | 1.041219 | 14.82 | 9.79 | 0.00546075 | 28700.3 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 31332.34 | -10.70 | 0.00150390 | -10.70 | 0.20573941 | 19.7595 | 21.11 | 0.00643514 | 21.10 | 0.00643514 | 41.4193 | 11759.95 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 23457.670 | 17229.659 | 1.046440 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.5422 | 1004.8586 | 1.2036 | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.046442 | 1.25949224 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | Sensible | 11728.83 | 8656.62 | 1.0000 | 0.83965996 | 0.697627 | 26.36 | 18.90 | 0.01059856 | 53518.0 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11728.83 | 31.92 | 0.01411931 | 23.08 | 0.20573941 | 29.4913 | 23.89 | 0.00973516 | 23.89 | 0.00973516 | 52.6399 | 11840.71 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 31488.070 | 31488.070 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.046442 | 1.25949224 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 31488.07 | 31488.07 | 1.0000 | 1.25949224 | 1.046442 | 14.85 | 9.82 | 0.00547669 | 28772.5 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 31488.07 | -10.70 | 0.00150390 | -10.70 | 0.20573941 | 19.6609 | 21.11 | 0.00644893 | 21.10 | 0.00644893 | 41.5071 | 11910.34 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 23518.840 | 17279.997 | 1.050070 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.5315 | 1004.8586 | 1.2036 | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.050074 | 1.26386416 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | Sensible | 11759.42 | 8684.62 | 1.0000 | 0.84257265 | 0.700047 | 26.36 | 18.90 | 0.01059281 | 53497.9 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11759.42 | 31.92 | 0.01411931 | 23.08 | 0.20573941 | 29.3894 | 23.89 | 0.00973162 | 23.89 | 0.00973162 | 52.6211 | 11880.16 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 31348.784 | 31348.784 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.050074 | 1.26386416 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 31348.78 | 31348.78 | 1.0000 | 1.26386416 | 1.050074 | 14.87 | 9.84 | 0.00548628 | 28818.7 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 31348.78 | -10.70 | 0.00150390 | -10.70 | 0.20573941 | 19.5928 | 21.11 | 0.00645666 | 21.10 | 0.00645666 | 41.5564 | 11998.82 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 23358.150 | 17146.984 | 1.040440 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.5608 | 1004.8586 | 1.2036 | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.040443 | 1.25227225 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | Sensible | 11679.08 | 8610.53 | 1.0000 | 0.83484558 | 0.693627 | 26.37 | 18.91 | 0.01060858 | 53553.0 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11679.08 | 31.92 | 0.01411931 | 23.08 | 0.20573941 | 29.6614 | 23.89 | 0.00974134 | 23.89 | 0.00974134 | 52.6728 | 11771.15 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 31312.322 | 31312.322 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.040443 | 1.25227225 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 31312.32 | 31312.32 | 1.0000 | 1.25227225 | 1.040443 | 14.82 | 9.81 | 0.00548773 | 28763.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 31312.32 | -10.70 | 0.00150390 | -10.70 | 0.20573941 | 19.7742 | 21.11 | 0.00646968 | 21.10 | 0.00646968 | 41.6394 | 12146.28 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 42329.660 | 30670.802 | 1.833210 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.8916 | 1004.8586 | 1.2036 | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.833207 | 2.20643890 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | Sensible | 21164.83 | 15317.73 | 1.0000 | 1.47096157 | 1.222140 | 26.56 | 19.11 | 0.01078651 | 54196.2 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 21164.83 | 31.92 | 0.01411931 | 23.08 | 0.41147883 | 33.6687 | 23.89 | 0.00981951 | 23.89 | 0.00981951 | 53.0887 | 20734.48 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 57719.575 | 57719.575 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.833207 | 2.20643890 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 57719.57 | 57719.57 | 1.0000 | 2.20643890 | 1.833207 | 13.97 | 9.35 | 0.00541203 | 27710.2 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 57719.57 | -10.70 | 0.00150390 | -10.70 | 0.41147883 | 22.4458 | 21.11 | 0.00654313 | 21.10 | 0.00654313 | 42.1063 | 23357.66 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 21850.450 | 15855.779 | 0.950180 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.8633 | 1004.8586 | 1.2036 | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.950183 | 1.14363574 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | Sensible | 10925.23 | 7917.04 | 1.0000 | 0.76242125 | 0.633453 | 26.53 | 19.09 | 0.01077127 | 54125.2 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10925.23 | 31.92 | 0.01411931 | 23.08 | 0.20573941 | 32.4790 | 23.89 | 0.00984205 | 23.89 | 0.00984205 | 53.2088 | 10747.07 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 29575.222 | 29575.222 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.950183 | 1.14363574 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 29575.22 | 29575.22 | 1.0000 | 1.14363574 | 0.950183 | 14.22 | 9.47 | 0.00541589 | 27975.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 29575.22 | -10.70 | 0.00150390 | -10.70 | 0.20573941 | 21.6526 | 21.11 | 0.00649703 | 21.10 | 0.00649703 | 41.8136 | 12466.85 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 21775.750 | 15793.080 | 0.945530 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.8822 | 1004.8586 | 1.2036 | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.945526 | 1.13803062 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | Sensible | 10887.88 | 7881.65 | 1.0000 | 0.75869011 | 0.630353 | 26.54 | 19.10 | 0.01078147 | 54161.3 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10887.88 | 31.92 | 0.01411931 | 23.08 | 0.20573941 | 32.6387 | 23.89 | 0.00984840 | 23.89 | 0.00984840 | 53.2426 | 10686.76 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 29461.471 | 29461.471 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.945526 | 1.13803062 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 29461.47 | 29461.47 | 1.0000 | 1.13803062 | 0.945526 | 14.19 | 9.45 | 0.00540995 | 27926.4 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 29461.47 | -10.70 | 0.00150390 | -10.70 | 0.20573941 | 21.7592 | 21.11 | 0.00649625 | 21.10 | 0.00649625 | 41.8086 | 12456.92 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 21683.350 | 15731.487 | 0.942420 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.8809 | 1004.8586 | 1.2036 | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.942415 | 1.13428619 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | Sensible | 10841.67 | 7847.18 | 1.0000 | 0.75619466 | 0.628280 | 26.53 | 19.10 | 0.01078074 | 54147.2 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10841.67 | 31.85 | 0.01411920 | 23.06 | 0.20573941 | 32.7465 | 23.89 | 0.00984659 | 23.89 | 0.00984659 | 53.2329 | 10665.57 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 29367.523 | 29367.523 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.942415 | 1.13428619 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 29367.52 | 29367.52 | 1.0000 | 1.13428619 | 0.942415 | 14.16 | 9.45 | 0.00541974 | 27927.9 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 29367.52 | -10.70 | 0.00150390 | -10.70 | 0.20573941 | 21.8311 | 21.11 | 0.00651336 | 21.10 | 0.00651336 | 41.9176 | 12667.32 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 23404.150 | 17114.285 | 1.035400 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.7150 | 1004.8586 | 1.2036 | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.035403 | 1.24620549 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | Sensible | 11702.08 | 8535.05 | 1.0000 | 0.83080150 | 0.690267 | 26.35 | 18.97 | 0.01069154 | 53737.0 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11702.08 | 31.73 | 0.01411898 | 23.03 | 0.20573941 | 29.8058 | 23.89 | 0.00983842 | 23.88 | 0.00983842 | 53.1902 | 11715.17 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 31372.107 | 31372.107 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.035403 | 1.24620549 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 31372.11 | 31372.11 | 1.0000 | 1.24620549 | 1.035403 | 14.78 | 9.83 | 0.00551560 | 28801.9 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 31372.11 | -10.70 | 0.00150390 | -10.70 | 0.20573941 | 19.8705 | 21.10 | 0.00651042 | 21.10 | 0.00651042 | 41.9028 | 15976.22 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:31
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-AC_1:1_OA_CONTROLLER | DifferentialEnthalpy | 0.41 | 1.94 | - | |||
PSZ-AC_2:2_OA_CONTROLLER | DifferentialEnthalpy | 0.21 | 1.04 | - | |||
PSZ-AC_3:3_OA_CONTROLLER | DifferentialEnthalpy | 0.21 | 1.05 | - | |||
PSZ-AC_4:4_OA_CONTROLLER | DifferentialEnthalpy | 0.21 | 1.05 | - | |||
PSZ-AC_5:5_OA_CONTROLLER | DifferentialEnthalpy | 0.21 | 1.04 | - | |||
PSZ-AC_6:6_OA_CONTROLLER | DifferentialEnthalpy | 0.41 | 1.83 | - | |||
PSZ-AC_7:7_OA_CONTROLLER | DifferentialEnthalpy | 0.21 | 0.95 | - | |||
PSZ-AC_8:8_OA_CONTROLLER | DifferentialEnthalpy | 0.21 | 0.95 | - | |||
PSZ-AC_9:9_OA_CONTROLLER | DifferentialEnthalpy | 0.21 | 0.94 | - | |||
PSZ-AC_10:10_OA_CONTROLLER | DifferentialEnthalpy | 0.21 | 1.04 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
LGSTORE1 | 3150.00 | 3671.50 | 1456.00 |
SMSTORE1 | 2421.83 | 3283.67 | 553.33 |
SMSTORE2 | 2093.33 | 2661.00 | 760.67 |
SMSTORE3 | 2140.33 | 2687.67 | 826.00 |
SMSTORE4 | 2201.50 | 2752.83 | 939.00 |
LGSTORE2 | 2261.50 | 2739.50 | 1285.50 |
SMSTORE5 | 2230.33 | 2777.67 | 1312.17 |
SMSTORE6 | 2251.50 | 2809.17 | 1357.00 |
SMSTORE7 | 2355.00 | 2875.50 | 1500.00 |
SMSTORE8 | 2691.17 | 2948.00 | 1860.00 |
Facility | 4029.00 | 4268.67 | 2476.83 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
LGSTORE1 | 6.83 | 0.00 | 2.17 | 0.00 |
SMSTORE1 | 1.17 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 0.50 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 0.67 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 1.00 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 3.00 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 2.83 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 3.17 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 4.83 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 24.17 | 0.00 | 0.00 | 0.00 |
Facility | 30.50 | 0.00 | 2.17 | 0.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:31
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
LGSTORE1 | 16.93 | 56.25 | 1805.20 | 0.931 | 0.236 | 0.000 | 0.000 |
SMSTORE1 | 8.46 | 28.12 | 902.60 | 0.798 | 0.248 | 0.000 | 0.000 |
SMSTORE2 | 7.08 | 28.12 | 902.60 | 0.986 | 0.323 | 0.000 | 0.000 |
SMSTORE3 | 7.08 | 28.12 | 902.60 | 0.982 | 0.323 | 0.000 | 0.000 |
SMSTORE4 | 7.08 | 28.12 | 902.60 | 0.974 | 0.323 | 0.000 | 0.000 |
LGSTORE2 | 24.78 | 56.25 | 1805.20 | 0.948 | 0.310 | 0.000 | 0.000 |
SMSTORE5 | 12.39 | 28.12 | 902.60 | 0.954 | 0.344 | 0.000 | 0.000 |
SMSTORE6 | 12.39 | 28.12 | 902.60 | 0.950 | 0.344 | 0.000 | 0.000 |
SMSTORE7 | 12.39 | 28.12 | 902.60 | 0.945 | 0.344 | 0.000 | 0.000 |
SMSTORE8 | 12.39 | 28.12 | 902.60 | 0.956 | 0.369 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
LGSTORE1 | 16.93 | 56.25 | 1805.20 | 0.000 | 0.000 | 0.000 | 0.000 |
SMSTORE1 | 8.46 | 28.12 | 902.60 | 0.000 | 0.000 | 0.000 | 0.000 |
SMSTORE2 | 7.08 | 28.12 | 902.60 | 0.799 | 0.000 | 0.000 | 0.000 |
SMSTORE3 | 7.08 | 28.12 | 902.60 | 0.799 | 0.000 | 0.000 | 0.000 |
SMSTORE4 | 7.08 | 28.12 | 902.60 | 0.799 | 0.000 | 0.000 | 0.000 |
LGSTORE2 | 24.78 | 56.25 | 1805.20 | 0.799 | 0.000 | 0.000 | 0.000 |
SMSTORE5 | 12.39 | 28.12 | 902.60 | 0.799 | 0.000 | 0.000 | 0.000 |
SMSTORE6 | 12.39 | 28.12 | 902.60 | 0.799 | 0.000 | 0.000 | 0.000 |
SMSTORE7 | 12.39 | 28.12 | 902.60 | 0.799 | 0.000 | 0.000 | 0.000 |
SMSTORE8 | 12.39 | 28.12 | 902.60 | 0.799 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:37:31
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
LGSTORE1 | PSZ-AC_1:1 | 16.93 | 56.25 | 1805.20 | 348.39 | 0.4115 | 0.411 |
SMSTORE1 | PSZ-AC_2:2 | 8.46 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE2 | PSZ-AC_3:3 | 7.08 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE3 | PSZ-AC_4:4 | 7.08 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE4 | PSZ-AC_5:5 | 7.08 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
LGSTORE2 | PSZ-AC_6:6 | 24.78 | 56.25 | 1805.20 | 348.39 | 0.4115 | 0.411 |
SMSTORE5 | PSZ-AC_7:7 | 12.39 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE6 | PSZ-AC_8:8 | 12.39 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE7 | PSZ-AC_9:9 | 12.39 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE8 | PSZ-AC_10:10 | 12.39 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
Total Facility | 120.98 | 337.50 | 10831.20 | 2090.32 | 2.4689 | 2.469 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
LGSTORE1 | 9668586.66 | 0.00 | 9668586.66 | 2905267.86 | 12573854.51 | 12976396.34 | 3163.27 | 4691.17 | 905.56 | 13.12 |
SMSTORE1 | 4142449.24 | 0.00 | 4142449.24 | 1421541.01 | 5563990.25 | 6488198.17 | 4438.88 | 3349.58 | 971.53 | 17.82 |
SMSTORE2 | 3888996.76 | 0.00 | 3888996.76 | 1467297.82 | 5356294.59 | 6488198.17 | 4345.32 | 3712.25 | 702.43 | 63.16 |
SMSTORE3 | 3876252.10 | 0.00 | 3876252.10 | 1467297.82 | 5343549.93 | 6488198.17 | 4345.28 | 3734.50 | 680.22 | 60.89 |
SMSTORE4 | 3841509.13 | 0.00 | 3841509.13 | 1467297.82 | 5308806.95 | 6488198.17 | 4345.60 | 3771.08 | 643.32 | 60.20 |
LGSTORE2 | 6849997.33 | 0.00 | 6849997.33 | 2708743.34 | 9558740.67 | 12976396.34 | 4713.63 | 3466.42 | 579.95 | 48.08 |
SMSTORE5 | 3445486.57 | 0.00 | 3445486.57 | 1479898.30 | 4925384.88 | 6488198.17 | 4713.21 | 3473.42 | 573.38 | 46.85 |
SMSTORE6 | 3432010.53 | 0.00 | 3432010.53 | 1479898.30 | 4911908.83 | 6488198.17 | 4714.23 | 3490.33 | 555.43 | 44.74 |
SMSTORE7 | 3409913.47 | 0.00 | 3409913.47 | 1479898.30 | 4889811.77 | 6488198.17 | 4715.35 | 3520.33 | 524.32 | 39.52 |
SMSTORE8 | 3452749.29 | 0.00 | 3452749.29 | 1880673.34 | 5333422.63 | 6488198.17 | 4714.64 | 3540.83 | 504.53 | 30.84 |
Total Facility | 46007951.09 | 0.00 | 46007951.09 | 17757813.92 | 63765765.01 | 77858378.04 | 4723.45 | 5222.08 | 1204.71 | 138.96 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
LGSTORE1 | 0.4591 | 0.0000 | 0.4591 | 0.1164 | 0.5756 | 0.4115 | 247.64 | 4691.00 | 901.36 |
SMSTORE1 | 0.1966 | 0.0000 | 0.1966 | 0.0612 | 0.2579 | 0.2057 | 1521.76 | 3349.58 | 968.65 |
SMSTORE2 | 0.2430 | 0.0000 | 0.2430 | 0.0797 | 0.3227 | 0.2057 | 0.00 | 3711.92 | 683.08 |
SMSTORE3 | 0.2422 | 0.0000 | 0.2422 | 0.0797 | 0.3219 | 0.2057 | 0.00 | 3733.67 | 661.33 |
SMSTORE4 | 0.2402 | 0.0000 | 0.2402 | 0.0797 | 0.3199 | 0.2057 | 0.00 | 3771.08 | 623.92 |
LGSTORE2 | 0.4676 | 0.0000 | 0.4676 | 0.1532 | 0.6208 | 0.4115 | 0.00 | 3466.25 | 563.75 |
SMSTORE5 | 0.2352 | 0.0000 | 0.2352 | 0.0850 | 0.3201 | 0.2057 | 0.00 | 3473.25 | 556.75 |
SMSTORE6 | 0.2343 | 0.0000 | 0.2343 | 0.0850 | 0.3193 | 0.2057 | 0.00 | 3490.17 | 539.83 |
SMSTORE7 | 0.2330 | 0.0000 | 0.2330 | 0.0850 | 0.3180 | 0.2057 | 0.00 | 3520.17 | 509.83 |
SMSTORE8 | 0.2358 | 0.0000 | 0.2358 | 0.0911 | 0.3269 | 0.2057 | 0.00 | 3540.83 | 489.17 |
Total Facility | 2.7871 | 0.0000 | 2.7871 | 0.9158 | 3.7030 | 2.4689 | 1629.55 | 5220.42 | 1180.91 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-AC_1:1 | 14006751.81 | 0.00 | 14006751.81 | 12976396.34 | 3156.27 | 0.17 | 5603.56 | 13.12 |
PSZ-AC_2:2 | 6001058.44 | 0.00 | 6001058.44 | 6488198.17 | 4375.03 | 3.08 | 4381.89 | 17.66 |
PSZ-AC_3:3 | 5633912.36 | 0.00 | 5633912.36 | 6488198.17 | 4336.92 | 0.83 | 4422.24 | 63.16 |
PSZ-AC_4:4 | 5615446.77 | 0.00 | 5615446.77 | 6488198.17 | 4338.53 | 0.17 | 4421.30 | 60.55 |
PSZ-AC_5:5 | 5565115.99 | 0.00 | 5565115.99 | 6488198.17 | 4340.45 | 0.17 | 4419.38 | 59.95 |
PSZ-AC_6:6 | 9923514.99 | 0.00 | 9923514.99 | 12976396.34 | 4709.26 | 0.50 | 4050.24 | 48.08 |
PSZ-AC_7:7 | 4991419.50 | 0.00 | 4991419.50 | 6488198.17 | 4709.04 | 0.17 | 4050.79 | 46.77 |
PSZ-AC_8:8 | 4971892.97 | 0.00 | 4971892.97 | 6488198.17 | 4710.34 | 0.33 | 4049.32 | 44.74 |
PSZ-AC_9:9 | 4939865.07 | 0.00 | 4939865.07 | 6488198.17 | 4711.54 | 0.50 | 4047.96 | 39.35 |
PSZ-AC_10:10 | 5001853.30 | 0.00 | 5001853.30 | 6488198.17 | 4711.54 | 0.22 | 4048.23 | 30.84 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-AC_1:1 | 0.6651 | 0.0000 | 0.6651 | 0.4115 | 241.64 | 0.17 | 5598.20 |
PSZ-AC_2:2 | 0.2849 | 0.0000 | 0.2849 | 0.2057 | 1459.82 | 3.08 | 4377.09 |
PSZ-AC_3:3 | 0.3520 | 0.0000 | 0.3520 | 0.2057 | 0.00 | 0.00 | 4395.00 |
PSZ-AC_4:4 | 0.3509 | 0.0000 | 0.3509 | 0.2057 | 0.00 | 0.00 | 4395.00 |
PSZ-AC_5:5 | 0.3479 | 0.0000 | 0.3479 | 0.2057 | 0.00 | 0.00 | 4395.00 |
PSZ-AC_6:6 | 0.6774 | 0.0000 | 0.6774 | 0.4115 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_7:7 | 0.3407 | 0.0000 | 0.3407 | 0.2057 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_8:8 | 0.3395 | 0.0000 | 0.3395 | 0.2057 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_9:9 | 0.3376 | 0.0000 | 0.3376 | 0.2057 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_10:10 | 0.3416 | 0.0000 | 0.3416 | 0.2057 | 0.00 | 0.00 | 4030.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-AC_1:1 | 0.00 | 5186.07 | 446.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_2:2 | 0.00 | 4263.69 | 726.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_3:3 | 0.00 | 4117.72 | 340.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_4:4 | 0.00 | 4129.28 | 326.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_5:5 | 0.00 | 4155.63 | 299.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_6:6 | 0.00 | 3838.64 | 239.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_7:7 | 0.00 | 3839.02 | 237.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_8:8 | 0.00 | 3849.82 | 224.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_9:9 | 0.00 | 3868.98 | 200.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_10:10 | 0.00 | 3857.69 | 203.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-AC_1:1 | 0.0000 | 0.6729 | 0.9137 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_2:2 | 0.0000 | 0.3255 | 0.3892 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_3:3 | 0.0000 | 0.3417 | 0.5001 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_4:4 | 0.0000 | 0.3409 | 0.5031 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_5:5 | 0.0000 | 0.3387 | 0.5023 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_6:6 | 0.0000 | 0.6646 | 0.9240 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_7:7 | 0.0000 | 0.3339 | 0.4731 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_8:8 | 0.0000 | 0.3329 | 0.4769 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_9:9 | 0.0000 | 0.3314 | 0.4794 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_10:10 | 0.0000 | 0.3336 | 0.5133 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:31
Surfaces by ClassTotal | Outdoors | |
Wall | 40 | 22 |
Floor | 10 | 10 |
Roof | 10 | 10 |
Internal Mass | 10 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 36 | 36 |
Door | 12 | 12 |
Glass Door | 12 | 12 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 10 |
Conditioned Zones | 10 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 830 |
Defaulted Fields | 823 |
Fields with Defaults | 2682 |
Autosized Fields | 184 |
Autosizable Fields | 458 |
Autocalculated Fields | 128 |
Autocalculatable Fields | 256 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:37:31
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 833.91 | 2102.83 | 08-JAN-07:40 | 94012.95 | 16-AUG-13:30 |
Electricity:Building | 494.83 | 891.83 | 01-JAN-00:20 | 31518.67 | 01-JAN-11:10 |
Electricity:Zone:LGSTORE1 | 113.36 | 148.64 | 01-JAN-00:20 | 5964.88 | 01-JAN-10:10 |
Electricity:SpaceType:GENERAL | 494.83 | 891.83 | 01-JAN-00:20 | 31518.67 | 01-JAN-11:10 |
InteriorLights:Electricity | 366.68 | 450.00 | 01-JAN-00:20 | 23459.17 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:LGSTORE1 | 87.12 | 75.00 | 01-JAN-00:20 | 4621.63 | 01-JAN-10:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 366.68 | 450.00 | 01-JAN-00:20 | 23459.17 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity | 366.68 | 450.00 | 01-JAN-00:20 | 23459.17 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:LGSTORE1 | 87.12 | 75.00 | 01-JAN-00:20 | 4621.63 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 366.68 | 450.00 | 01-JAN-00:20 | 23459.17 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE1 | 66.33 | 74.32 | 01-JAN-00:20 | 3498.69 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE1 | 53.20 | 37.50 | 01-JAN-00:20 | 2827.07 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE1 | 53.20 | 37.50 | 01-JAN-00:20 | 2827.07 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE2 | 47.99 | 74.32 | 01-JAN-00:10 | 3226.84 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE2 | 37.57 | 37.50 | 01-JAN-00:10 | 2555.22 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE2 | 37.57 | 37.50 | 01-JAN-00:10 | 2555.22 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE3 | 47.99 | 74.32 | 01-JAN-00:10 | 3226.84 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE3 | 37.57 | 37.50 | 01-JAN-00:10 | 2555.22 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE3 | 37.57 | 37.50 | 01-JAN-00:10 | 2555.22 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE4 | 47.99 | 74.32 | 01-JAN-00:10 | 3226.84 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE4 | 37.57 | 37.50 | 01-JAN-00:10 | 2555.22 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE4 | 37.57 | 37.50 | 01-JAN-00:10 | 2555.22 | 01-JAN-10:10 |
Electricity:Zone:LGSTORE2 | 56.34 | 148.64 | 01-JAN-00:10 | 4070.21 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:LGSTORE2 | 37.16 | 75.00 | 01-JAN-00:10 | 2726.96 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:LGSTORE2 | 37.16 | 75.00 | 01-JAN-00:10 | 2726.96 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE5 | 28.71 | 74.32 | 01-JAN-00:10 | 2076.09 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE5 | 19.12 | 37.50 | 01-JAN-00:10 | 1404.46 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE5 | 19.12 | 37.50 | 01-JAN-00:10 | 1404.46 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE6 | 28.71 | 74.32 | 01-JAN-00:10 | 2076.09 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE6 | 19.12 | 37.50 | 01-JAN-00:10 | 1404.46 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE6 | 19.12 | 37.50 | 01-JAN-00:10 | 1404.46 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE7 | 28.71 | 74.32 | 01-JAN-00:10 | 2076.09 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE7 | 19.12 | 37.50 | 01-JAN-00:10 | 1404.46 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE7 | 19.12 | 37.50 | 01-JAN-00:10 | 1404.46 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE8 | 28.71 | 74.32 | 01-JAN-00:10 | 2076.09 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE8 | 19.12 | 37.50 | 01-JAN-00:10 | 1404.46 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE8 | 19.12 | 37.50 | 01-JAN-00:10 | 1404.46 | 01-JAN-11:10 |
InteriorEquipment:Electricity | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:LGSTORE1 | 26.25 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-10:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LGSTORE1 | 26.25 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE1 | 13.12 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE1 | 13.12 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE2 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE2 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE3 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE3 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE4 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE4 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:LGSTORE2 | 19.17 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LGSTORE2 | 19.17 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE5 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE5 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE6 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE6 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE7 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE7 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE8 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE8 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
ElectricityPurchased:Facility | 833.91 | 2102.83 | 08-JAN-07:40 | 94012.95 | 16-AUG-13:30 |
ElectricityPurchased:Plant | 833.91 | 2102.83 | 08-JAN-07:40 | 94012.95 | 16-AUG-13:30 |
Cogeneration:ElectricityPurchased | 833.91 | 2102.83 | 08-JAN-07:40 | 94012.95 | 16-AUG-13:30 |
General:Cogeneration:ElectricityPurchased | 833.91 | 2102.83 | 08-JAN-07:40 | 94012.95 | 16-AUG-13:30 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 833.91 | 2102.83 | 08-JAN-07:40 | 94012.95 | 16-AUG-13:30 |
ElectricityNet:Plant | 833.91 | 2102.83 | 08-JAN-07:40 | 94012.95 | 16-AUG-13:30 |
Cogeneration:ElectricityNet | 833.91 | 2102.83 | 08-JAN-07:40 | 94012.95 | 16-AUG-13:30 |
General:Cogeneration:ElectricityNet | 833.91 | 2102.83 | 08-JAN-07:40 | 94012.95 | 16-AUG-13:30 |
Electricity:HVAC | 214.99 | 0.00 | 01-JAN-00:40 | 57064.16 | 08-JUL-12:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 116.95 | 0.00 | 01-JAN-00:10 | 48709.80 | 08-JUL-12:10 |
General:Cooling:Electricity | 116.95 | 0.00 | 01-JAN-00:10 | 48709.80 | 08-JUL-12:10 |
Fans:Electricity | 98.04 | 0.00 | 01-JAN-00:40 | 9170.38 | 06-FEB-08:10 |
General:Fans:Electricity | 98.04 | 0.00 | 01-JAN-00:40 | 9170.38 | 06-FEB-08:10 |
ExteriorLights:Electricity | 60.37 | 0.00 | 01-JAN-07:30 | 5507.06 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 60.37 | 0.00 | 01-JAN-07:30 | 5507.06 | 01-JAN-06:10 |
Electricity:Plant | 63.71 | 1211.00 | 09-JAN-07:10 | 11858.75 | 04-JAN-13:50 |
WaterSystems:Electricity | 63.71 | 1211.00 | 09-JAN-07:10 | 11858.75 | 04-JAN-13:50 |
Water Heater:WaterSystems:Electricity | 63.71 | 1211.00 | 09-JAN-07:10 | 11858.75 | 04-JAN-13:50 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 466.08 | 0.00 | 01-JAN-00:40 | 233566.85 | 06-FEB-08:10 |
NaturalGas:HVAC | 466.08 | 0.00 | 01-JAN-00:40 | 233566.85 | 06-FEB-08:10 |
Heating:NaturalGas | 466.08 | 0.00 | 01-JAN-00:40 | 233566.85 | 06-FEB-08:10 |
General:Heating:NaturalGas | 466.08 | 0.00 | 01-JAN-00:40 | 233566.85 | 06-FEB-08:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water:Plant | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
WaterSystems:Water | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water Heater:WaterSystems:Water | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
MainsWater:Facility | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
MainsWater:Plant | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
WaterSystems:MainsWater | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water Heater:WaterSystems:MainsWater | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 1354.37 | 0.00 | 01-JAN-00:40 | 351760.98 | 06-FEB-08:10 |
EnergyTransfer:Building | 503.17 | 0.00 | 01-JAN-00:40 | 164907.50 | 06-FEB-08:10 |
EnergyTransfer:Zone:LGSTORE1 | 102.20 | 0.00 | 01-JAN-00:10 | 31498.86 | 06-FEB-08:10 |
Heating:EnergyTransfer | 112.40 | 0.00 | 01-JAN-00:40 | 164907.50 | 06-FEB-08:10 |
Heating:EnergyTransfer:Zone:LGSTORE1 | 16.63 | 0.00 | 01-JAN-00:10 | 31498.86 | 06-FEB-08:10 |
General:Heating:EnergyTransfer | 112.40 | 0.00 | 01-JAN-00:40 | 164907.50 | 06-FEB-08:10 |
General:Heating:EnergyTransfer:Zone:LGSTORE1 | 16.63 | 0.00 | 01-JAN-00:10 | 31498.86 | 06-FEB-08:10 |
Cooling:EnergyTransfer | 390.76 | 0.00 | 01-JAN-00:10 | 92467.39 | 18-AUG-13:00 |
Cooling:EnergyTransfer:Zone:LGSTORE1 | 85.57 | 0.00 | 01-JAN-00:10 | 15491.30 | 18-AUG-13:00 |
General:Cooling:EnergyTransfer | 390.76 | 0.00 | 01-JAN-00:10 | 92467.39 | 18-AUG-13:00 |
General:Cooling:EnergyTransfer:Zone:LGSTORE1 | 85.57 | 0.00 | 01-JAN-00:10 | 15491.30 | 18-AUG-13:00 |
EnergyTransfer:Zone:SMSTORE1 | 52.51 | 0.00 | 01-JAN-00:10 | 11635.48 | 06-FEB-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE1 | 4.50 | 0.00 | 01-JAN-00:10 | 11635.48 | 06-FEB-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE1 | 4.50 | 0.00 | 01-JAN-00:10 | 11635.48 | 06-FEB-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE1 | 48.00 | 0.00 | 01-JAN-00:10 | 8961.46 | 22-AUG-22:40 |
General:Cooling:EnergyTransfer:Zone:SMSTORE1 | 48.00 | 0.00 | 01-JAN-00:10 | 8961.46 | 22-AUG-22:40 |
EnergyTransfer:Zone:SMSTORE2 | 41.77 | 0.00 | 01-JAN-00:10 | 14089.14 | 02-JAN-07:10 |
Heating:EnergyTransfer:Zone:SMSTORE2 | 6.26 | 0.00 | 01-JAN-00:10 | 14089.14 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE2 | 6.26 | 0.00 | 01-JAN-00:10 | 14089.14 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:SMSTORE2 | 35.51 | 0.00 | 01-JAN-00:10 | 7997.08 | 18-AUG-13:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE2 | 35.51 | 0.00 | 01-JAN-00:10 | 7997.08 | 18-AUG-13:00 |
EnergyTransfer:Zone:SMSTORE3 | 41.68 | 0.00 | 01-JAN-00:10 | 15521.49 | 02-JAN-07:10 |
Heating:EnergyTransfer:Zone:SMSTORE3 | 6.97 | 0.00 | 01-JAN-00:10 | 15521.49 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE3 | 6.97 | 0.00 | 01-JAN-00:10 | 15521.49 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:SMSTORE3 | 34.71 | 0.00 | 01-JAN-00:10 | 8015.87 | 18-AUG-13:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE3 | 34.71 | 0.00 | 01-JAN-00:10 | 8015.87 | 18-AUG-13:00 |
EnergyTransfer:Zone:SMSTORE4 | 40.86 | 0.00 | 01-JAN-00:10 | 16398.41 | 02-JAN-07:10 |
Heating:EnergyTransfer:Zone:SMSTORE4 | 8.13 | 0.00 | 01-JAN-00:10 | 16398.41 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE4 | 8.13 | 0.00 | 01-JAN-00:10 | 16398.41 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:SMSTORE4 | 32.73 | 0.00 | 01-JAN-00:10 | 7883.98 | 18-AUG-13:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE4 | 32.73 | 0.00 | 01-JAN-00:10 | 7883.98 | 18-AUG-13:00 |
EnergyTransfer:Zone:LGSTORE2 | 69.56 | 0.00 | 01-JAN-00:10 | 32946.80 | 06-FEB-08:10 |
Heating:EnergyTransfer:Zone:LGSTORE2 | 16.84 | 0.00 | 01-JAN-00:10 | 32946.80 | 06-FEB-08:10 |
General:Heating:EnergyTransfer:Zone:LGSTORE2 | 16.84 | 0.00 | 01-JAN-00:10 | 32946.80 | 06-FEB-08:10 |
Cooling:EnergyTransfer:Zone:LGSTORE2 | 52.72 | 0.00 | 01-JAN-00:10 | 14304.43 | 18-AUG-13:00 |
General:Cooling:EnergyTransfer:Zone:LGSTORE2 | 52.72 | 0.00 | 01-JAN-00:10 | 14304.43 | 18-AUG-13:00 |
EnergyTransfer:Zone:SMSTORE5 | 36.40 | 0.00 | 01-JAN-00:10 | 17700.49 | 02-JAN-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE5 | 9.84 | 0.00 | 01-JAN-00:10 | 17700.49 | 02-JAN-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE5 | 9.84 | 0.00 | 01-JAN-00:10 | 17700.49 | 02-JAN-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE5 | 26.56 | 0.00 | 01-JAN-00:10 | 7434.02 | 18-AUG-13:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE5 | 26.56 | 0.00 | 01-JAN-00:10 | 7434.02 | 18-AUG-13:00 |
EnergyTransfer:Zone:SMSTORE6 | 36.20 | 0.00 | 01-JAN-00:10 | 17709.14 | 02-JAN-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE6 | 10.21 | 0.00 | 01-JAN-00:10 | 17709.14 | 02-JAN-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE6 | 10.21 | 0.00 | 01-JAN-00:10 | 17709.14 | 02-JAN-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE6 | 25.99 | 0.00 | 01-JAN-00:10 | 7386.53 | 18-AUG-13:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE6 | 25.99 | 0.00 | 01-JAN-00:10 | 7386.53 | 18-AUG-13:00 |
EnergyTransfer:Zone:SMSTORE7 | 36.69 | 0.00 | 01-JAN-00:10 | 16776.18 | 02-JAN-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE7 | 12.00 | 0.00 | 01-JAN-00:10 | 16776.18 | 02-JAN-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE7 | 12.00 | 0.00 | 01-JAN-00:10 | 16776.18 | 02-JAN-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE7 | 24.68 | 0.00 | 01-JAN-00:10 | 7378.39 | 18-AUG-13:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE7 | 24.68 | 0.00 | 01-JAN-00:10 | 7378.39 | 18-AUG-13:00 |
EnergyTransfer:Zone:SMSTORE8 | 45.31 | 0.00 | 01-JAN-00:40 | 19975.06 | 06-FEB-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE8 | 21.03 | 0.00 | 01-JAN-00:40 | 19975.06 | 06-FEB-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE8 | 21.03 | 0.00 | 01-JAN-00:40 | 19975.06 | 06-FEB-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE8 | 24.28 | 0.00 | 01-JAN-00:10 | 8305.65 | 18-AUG-13:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE8 | 24.28 | 0.00 | 01-JAN-00:10 | 8305.65 | 18-AUG-13:00 |
EnergyTransfer:HVAC | 851.20 | 0.00 | 01-JAN-00:40 | 205126.73 | 08-JUL-12:20 |
HeatingCoils:EnergyTransfer | 372.86 | 0.00 | 01-JAN-00:40 | 186853.48 | 06-FEB-08:10 |
CoolingCoils:EnergyTransfer | 478.34 | 0.00 | 01-JAN-00:10 | 205126.73 | 08-JUL-12:20 |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:31
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
LGSTORE1 | 0.000 | 0.000 | 16.627 | -85.569 | 0.000 | 0.000 | 25.178 | 87.116 | 26.249 | 22.473 | 0.000 | 2.348 | 0.003 | 0.000 | -8.450 | 0.000 | -34.130 | -51.842 |
SMSTORE1 | 0.000 | 0.000 | 4.504 | -48.002 | 0.000 | 0.000 | 12.411 | 53.201 | 13.125 | 11.152 | 0.000 | 1.258 | 0.000 | 0.000 | -4.453 | 0.000 | -16.473 | -26.723 |
SMSTORE2 | 0.000 | 0.000 | 6.255 | -35.514 | 0.000 | 0.000 | 7.545 | 37.572 | 10.421 | 11.136 | 0.000 | 1.241 | 0.001 | 0.000 | -4.403 | 0.000 | -17.038 | -17.216 |
SMSTORE3 | 0.000 | 0.000 | 6.971 | -34.712 | 0.000 | 0.000 | 7.553 | 37.572 | 10.421 | 11.148 | 0.000 | 1.241 | 0.001 | 0.000 | -4.355 | 0.000 | -16.969 | -18.870 |
SMSTORE4 | 0.000 | 0.000 | 8.130 | -32.725 | 0.000 | 0.000 | 7.566 | 37.572 | 10.421 | 11.170 | 0.000 | 1.242 | 0.000 | 0.000 | -4.300 | 0.000 | -16.878 | -22.198 |
LGSTORE2 | 0.000 | 0.000 | 16.840 | -52.721 | 0.000 | 0.000 | 26.015 | 37.162 | 19.173 | 22.432 | 0.000 | 2.243 | 0.008 | 0.000 | -8.317 | 0.000 | -31.045 | -31.783 |
SMSTORE5 | 0.000 | 0.000 | 9.836 | -26.564 | 0.000 | 0.000 | 13.014 | 19.120 | 9.586 | 11.204 | 0.000 | 1.246 | 0.004 | 0.000 | -4.155 | 0.000 | -16.857 | -16.430 |
SMSTORE6 | 0.000 | 0.000 | 10.209 | -25.992 | 0.000 | 0.000 | 13.022 | 19.120 | 9.586 | 11.214 | 0.000 | 1.246 | 0.003 | 0.000 | -4.135 | 0.000 | -16.824 | -17.447 |
SMSTORE7 | 0.000 | 0.000 | 12.005 | -24.681 | 0.000 | 0.000 | 13.042 | 19.120 | 9.586 | 11.240 | 0.000 | 1.246 | 0.002 | 0.000 | -4.067 | 0.000 | -16.720 | -20.772 |
SMSTORE8 | 0.000 | 0.000 | 21.027 | -24.279 | 0.000 | 0.000 | 13.071 | 19.120 | 9.586 | 11.305 | 0.000 | 1.329 | 0.001 | 0.000 | -3.812 | 0.000 | -21.565 | -25.783 |
Total Facility | 0.000 | 0.000 | 112.405 | -390.759 | 0.000 | 0.000 | 138.417 | 366.677 | 128.154 | 134.475 | 0.000 | 14.640 | 0.024 | 0.000 | -50.447 | 0.000 | -204.499 | -249.064 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
LGSTORE1 | 02-SEP-07:02 | 0.00 | 0.00 | 0.00 | -36331.66 | 0.00 | 0.00 | 0.00 | 75.00 | 73.64 | 410.25 | 0.00 | 0.00 | 35920.85 | 0.00 | -0.00 | 0.00 | -148.08 | 0.00 |
SMSTORE1 | 02-SEP-07:02 | 0.00 | 0.00 | 0.00 | -19530.02 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 203.11 | 0.00 | 0.00 | 19325.60 | 0.00 | -0.00 | 0.00 | -73.02 | 0.00 |
SMSTORE2 | 23-AUG-06:02 | 0.00 | 0.00 | 0.00 | -21149.58 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 0.00 | 0.00 | 0.00 | 21116.93 | 0.00 | -29.95 | 0.00 | -11.71 | 0.00 |
SMSTORE3 | 23-AUG-06:02 | 0.00 | 0.00 | 0.00 | -21246.32 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 0.00 | 0.00 | 0.00 | 21214.33 | 0.00 | -30.55 | 0.00 | -11.79 | 0.00 |
SMSTORE4 | 23-AUG-06:02 | 0.00 | 0.00 | 0.00 | -20962.35 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 0.00 | 0.00 | 0.00 | 20928.43 | 0.00 | -28.86 | 0.00 | -11.54 | 0.00 |
LGSTORE2 | 02-SEP-07:02 | 0.00 | 0.00 | 0.00 | -34639.05 | 0.00 | 0.00 | 0.00 | 75.00 | 73.64 | 409.90 | 0.00 | 0.00 | 34213.48 | 0.00 | -0.00 | 0.00 | -132.97 | 0.00 |
SMSTORE5 | 02-SEP-07:02 | 0.00 | 0.00 | 0.00 | -17780.93 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 206.27 | 0.00 | 0.00 | 17570.39 | 0.00 | -0.00 | 0.00 | -70.05 | 0.00 |
SMSTORE6 | 02-SEP-07:02 | 0.00 | 0.00 | 0.00 | -17684.61 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 206.91 | 0.00 | 0.00 | 17472.67 | 0.00 | -0.00 | 0.00 | -69.29 | 0.00 |
SMSTORE7 | 02-SEP-07:02 | 0.00 | 0.00 | 0.00 | -17536.32 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 207.80 | 0.00 | 0.00 | 17321.51 | 0.00 | -0.00 | 0.00 | -67.31 | 0.00 |
SMSTORE8 | 02-SEP-07:02 | 0.00 | 0.00 | 0.00 | -18681.31 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 209.66 | 0.00 | 0.00 | 18474.60 | 0.00 | -0.00 | 0.00 | -77.27 | 0.00 |
Total Facility | 02-SEP-07:02 | 0.00 | 0.00 | 0.00 | -169834.88 | 0.00 | 0.00 | 295.52 | 450.00 | 1450.75 | 2498.70 | 0.00 | 0.00 | 165947.97 | 0.00 | 0.00 | 0.00 | -808.05 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
LGSTORE1 | 06-FEB-08:12 | 0.00 | 0.00 | 60356.15 | 0.00 | 0.00 | 0.00 | 231.22 | 243.23 | 74.62 | 1082.55 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -2254.91 | -59732.87 |
SMSTORE1 | 02-JAN-08:61 | 0.00 | 0.00 | 31383.57 | 0.00 | 0.00 | 0.00 | 134.26 | 37.50 | 37.31 | 285.74 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -811.71 | -31066.66 |
SMSTORE2 | 08-JAN-08:61 | 0.00 | 0.00 | 31532.94 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 37.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -344.02 | 0.00 | -611.18 | -30652.55 |
SMSTORE3 | 08-JAN-08:61 | 0.00 | 0.00 | 31399.08 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 37.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -339.26 | 0.00 | -604.42 | -30530.21 |
SMSTORE4 | 08-JAN-08:61 | 0.00 | 0.00 | 31364.16 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 37.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -334.73 | 0.00 | -597.54 | -30506.70 |
LGSTORE2 | 02-JAN-08:12 | 0.00 | 0.00 | 58142.75 | 0.00 | 0.00 | 0.00 | 0.00 | 75.00 | 73.64 | 890.41 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -1593.09 | -57588.71 |
SMSTORE5 | 02-JAN-08:12 | 0.00 | 0.00 | 29898.89 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 445.02 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -868.72 | -29549.52 |
SMSTORE6 | 02-JAN-08:12 | 0.00 | 0.00 | 29790.53 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 445.27 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -868.10 | -29442.02 |
SMSTORE7 | 02-JAN-08:12 | 0.00 | 0.00 | 29700.84 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 445.63 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -873.12 | -29347.67 |
SMSTORE8 | 06-FEB-08:12 | 0.00 | 0.00 | 31777.90 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 560.58 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -1363.84 | -31048.96 |
Total Facility | 02-JAN-08:61 | 0.00 | 0.00 | 290243.50 | 0.00 | 0.00 | 0.00 | 760.19 | 450.00 | 1452.23 | 3675.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -9530.77 | -287050.67 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:31
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 1.9426 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 1.9426 | 0.2118 | 1.0000 | Not calculated | 0.4115 | 0.2118 | ||
PSZ-AC_2:2 | 1.0248 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0412 | 0.1976 | 1.0000 | Not calculated | 0.2057 | 0.1976 | ||
PSZ-AC_3:3 | 1.0316 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0464 | 0.1966 | 1.0000 | Not calculated | 0.2057 | 0.1966 | ||
PSZ-AC_4:4 | 1.0255 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0501 | 0.1959 | 1.0000 | Not calculated | 0.2057 | 0.1959 | ||
PSZ-AC_5:5 | 1.0239 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0404 | 0.1977 | 1.0000 | Not calculated | 0.2057 | 0.1977 | ||
PSZ-AC_6:6 | 1.8332 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 1.8332 | 0.2245 | 1.0000 | Not calculated | 0.4115 | 0.2245 | ||
PSZ-AC_7:7 | 0.9479 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9502 | 0.2165 | 1.0000 | Not calculated | 0.2057 | 0.2165 | ||
PSZ-AC_8:8 | 0.9429 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9455 | 0.2176 | 1.0000 | Not calculated | 0.2057 | 0.2176 | ||
PSZ-AC_9:9 | 0.9388 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9424 | 0.2183 | 1.0000 | Not calculated | 0.2057 | 0.2183 | ||
PSZ-AC_10:10 | 1.0265 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0354 | 0.1987 | 1.0000 | Not calculated | 0.2057 | 0.1987 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 1.9426 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 1.9426 | 1.0000 | 1.0000 | Not calculated | 0.4115 | 0.2118 | ||
PSZ-AC_2:2 | 1.0248 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0248 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.2008 | ||
PSZ-AC_3:3 | 1.0316 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0316 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1994 | ||
PSZ-AC_4:4 | 1.0255 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0255 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.2006 | ||
PSZ-AC_5:5 | 1.0239 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0239 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.2009 | ||
PSZ-AC_6:6 | 1.8332 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 1.8332 | 1.0000 | 1.0000 | Not calculated | 0.4115 | 0.2245 | ||
PSZ-AC_7:7 | 0.9479 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9479 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.2170 | ||
PSZ-AC_8:8 | 0.9429 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9429 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.2182 | ||
PSZ-AC_9:9 | 0.9388 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9388 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.2191 | ||
PSZ-AC_10:10 | 1.0265 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0265 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.2004 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
LGSTORE1 | PSZ-AC_1:1 | 0.000000 | 56.2505 | 0.001181 | 348.39 | 0.4115 | 1.0000 | 0.4115 | 1.000 | 0.4115 |
SMSTORE1 | PSZ-AC_2:2 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE2 | PSZ-AC_3:3 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE3 | PSZ-AC_4:4 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE4 | PSZ-AC_5:5 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
LGSTORE2 | PSZ-AC_6:6 | 0.000000 | 56.2505 | 0.001181 | 348.39 | 0.4115 | 1.0000 | 0.4115 | 1.000 | 0.4115 |
SMSTORE5 | PSZ-AC_7:7 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE6 | PSZ-AC_8:8 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE7 | PSZ-AC_9:9 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE8 | PSZ-AC_10:10 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC_1:1 | 0.000000 | 56.25 | 0.001181 | 348.3864 | 0.4115 | 0.4115 | 0.4115 |
PSZ-AC_2:2 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_3:3 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_4:4 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_5:5 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_6:6 | 0.000000 | 56.25 | 0.001181 | 348.3864 | 0.4115 | 0.4115 | 0.4115 |
PSZ-AC_7:7 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_8:8 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_9:9 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_10:10 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LGSTORE1 | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.9426 | 1.9426 | 1.9426 | No | 0.4115 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE1 | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0248 | 1.0248 | 1.0248 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE2 | PSZ-AC_3:3 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0316 | 1.0316 | 1.0316 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE3 | PSZ-AC_4:4 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0255 | 1.0255 | 1.0255 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE4 | PSZ-AC_5:5 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0239 | 1.0239 | 1.0239 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LGSTORE2 | PSZ-AC_6:6 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.8332 | 1.8332 | 1.8332 | No | 0.4115 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE5 | PSZ-AC_7:7 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9479 | 0.9479 | 0.9479 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE6 | PSZ-AC_8:8 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9429 | 0.9429 | 0.9429 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE7 | PSZ-AC_9:9 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9388 | 0.9388 | 0.9388 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE8 | PSZ-AC_10:10 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0265 | 1.0265 | 1.0265 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 1.9426 | 1.9426 | 1.9426 | 1.9426 | 0.4115 | 1.0000 |
PSZ-AC_2:2 | 1.0248 | 1.0412 | 1.0248 | 1.0248 | 0.2057 | 1.0000 |
PSZ-AC_3:3 | 1.0316 | 1.0464 | 1.0316 | 1.0316 | 0.2057 | 1.0000 |
PSZ-AC_4:4 | 1.0255 | 1.0501 | 1.0255 | 1.0255 | 0.2057 | 1.0000 |
PSZ-AC_5:5 | 1.0239 | 1.0404 | 1.0239 | 1.0239 | 0.2057 | 1.0000 |
PSZ-AC_6:6 | 1.8332 | 1.8332 | 1.8332 | 1.8332 | 0.4115 | 1.0000 |
PSZ-AC_7:7 | 0.9479 | 0.9502 | 0.9479 | 0.9479 | 0.2057 | 1.0000 |
PSZ-AC_8:8 | 0.9429 | 0.9455 | 0.9429 | 0.9429 | 0.2057 | 1.0000 |
PSZ-AC_9:9 | 0.9388 | 0.9424 | 0.9388 | 0.9388 | 0.2057 | 1.0000 |
PSZ-AC_10:10 | 1.0265 | 1.0354 | 1.0265 | 1.0265 | 0.2057 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LGSTORE1 | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.9426 | 1.9426 | 1.9426 | No | 0.4115 | 0.3119 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE1 | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0248 | 1.0248 | 1.0248 | No | 0.2057 | 0.3381 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE2 | PSZ-AC_3:3 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0316 | 1.0316 | 1.0316 | No | 0.2057 | 0.3338 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE3 | PSZ-AC_4:4 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0255 | 1.0255 | 1.0255 | No | 0.2057 | 0.3313 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE4 | PSZ-AC_5:5 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0239 | 1.0239 | 1.0239 | No | 0.2057 | 0.3273 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LGSTORE2 | PSZ-AC_6:6 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.8332 | 1.8332 | 1.8332 | No | 0.4115 | 0.3404 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE5 | PSZ-AC_7:7 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9479 | 0.9479 | 0.9479 | No | 0.2057 | 0.3189 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE6 | PSZ-AC_8:8 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9429 | 0.9429 | 0.9429 | No | 0.2057 | 0.3192 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE7 | PSZ-AC_9:9 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9388 | 0.9388 | 0.9388 | No | 0.2057 | 0.3139 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE8 | PSZ-AC_10:10 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0265 | 1.0265 | 1.0265 | No | 0.2057 | 0.2489 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 1.9426 | 1.9426 | 1.9426 | 1.9426 | 0.4115 | 1.0000 |
PSZ-AC_2:2 | 1.0248 | 1.0248 | 1.0248 | 1.0248 | 0.2057 | 1.0000 |
PSZ-AC_3:3 | 1.0316 | 1.0316 | 1.0316 | 1.0316 | 0.2057 | 1.0000 |
PSZ-AC_4:4 | 1.0255 | 1.0255 | 1.0255 | 1.0255 | 0.2057 | 1.0000 |
PSZ-AC_5:5 | 1.0239 | 1.0239 | 1.0239 | 1.0239 | 0.2057 | 1.0000 |
PSZ-AC_6:6 | 1.8332 | 1.8332 | 1.8332 | 1.8332 | 0.4115 | 1.0000 |
PSZ-AC_7:7 | 0.9479 | 0.9479 | 0.9479 | 0.9479 | 0.2057 | 1.0000 |
PSZ-AC_8:8 | 0.9429 | 0.9429 | 0.9429 | 0.9429 | 0.2057 | 1.0000 |
PSZ-AC_9:9 | 0.9388 | 0.9388 | 0.9388 | 0.9388 | 0.2057 | 1.0000 |
PSZ-AC_10:10 | 1.0265 | 1.0265 | 1.0265 | 1.0265 | 0.2057 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:31
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860 |
Total gross floor area [m2] | 2090.32 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
LGSTORE1 | 348.39 | 348.39 | 0.00 | 112.00 |
SMSTORE1 | 174.19 | 174.19 | 0.00 | 112.00 |
SMSTORE2 | 174.19 | 174.19 | 0.00 | 84.29 |
SMSTORE3 | 174.19 | 174.19 | 0.00 | 84.29 |
SMSTORE4 | 174.19 | 174.19 | 0.00 | 84.29 |
LGSTORE2 | 348.39 | 348.39 | 0.00 | 77.29 |
SMSTORE5 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE6 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE7 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE8 | 174.19 | 174.19 | 0.00 | 77.29 |
Totals | 2090.32 | 2090.32 | 0.00 |
Data | |
Number of hours heating loads not met | 2.17 |
Number of hours cooling loads not met | 0.00 |
Number of hours not met | 2.17 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 466.08 | 233566.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 116.95 | 48709.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 366.68 | 23459.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 60.37 | 5507.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 128.15 | 8059.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 98.04 | 9170.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 63.71 | 11858.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 128.15 | 833.91 |
Natural Gas | 0.00 | 466.08 |
Additional | 0.00 | 0.00 |
Total | 128.15 | 1299.99 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 175.42 |
Space Heating | 0.00 |
Space Cooling | 55.95 |
Fans (All) | 46.90 |
Service Water Heating | 30.48 |
Receptacle Equipment | 61.31 |
Miscellaneous (All) | 398.94 |
Subtotal | 398.94 |
Natural Gas [MJ/m2] | |
Space Heating | 222.97 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 222.97 |
Subtotal | 222.97 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 28.21 |
Space Heating | 35.85 |
Space Cooling | 9.00 |
Fans (All) | 7.54 |
Service Water Heating | 4.90 |
Receptacle Equipment | 9.86 |
Miscellaneous | 4.64 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
TYPE1_OCC_SCH | 1630. | 5840. |
TYPE2_OCC_SCH | 995. | 4429. |
TYPE3_OCC_SCH | 1709. | 4064. |
LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 3767. | 8760. |
LTG_SCH_BASE_LPD2 | 3238. | 8760. |
LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 3296. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | 5084. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | 5084. | 8760. |
LTG_SCH_BASE_SMALL_LPD1 | 4453. | 8760. |
LTG_SCH_BASE_LPD1 | 4376. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | 3767. | 8760. |
LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 3584. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 4096. | 8760. |
TYPE1_EQUIP_SCH | 4868. | 8760. |
TYPE2_EQUIP_SCH | 3893. | 8760. |
TYPE3_EQUIP_SCH | 3584. | 8760. |
TYPE1_INFIL_SCH | 4302. | 8760. |
TYPE2_INFIL_SCH | 5164. | 8760. |
TYPE3_INFIL_SCH | 5438. | 8760. |
INFIL_DOOR_OPENING_SCH | 2477. | 4380. |
TYPE1_MINOA_MOTORIZEDDAMPER_SCH | 5579. | 5579. |
TYPE2_MINOA_MOTORIZEDDAMPER_SCH | 4429. | 4429. |
TYPE3_MINOA_MOTORIZEDDAMPER_SCH | 4064. | 4064. |
TYPE1_SWH_SCH | 2063. | 6048. |
TYPE2_SWH_SCH | 1831. | 4429. |
TYPE3_SWH_SCH | 1733. | 4064. |
AVERAGE_SWH_SCH | 1863. | 6152. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 7118. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 5839. | 5839. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 7300. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6570. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
TYPE1_HTGSETP_SCH_NO_OPTIMUM | LGSTORE1 DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
TYPE1_CLGSETP_SCH_NO_OPTIMUM | LGSTORE1 DUAL SP CONTROL | July | 23.89 | 365 | 23.89 | 365 |
TYPE2_HTGSETP_SCH_NO_OPTIMUM | SMSTORE2 DUAL SP CONTROL | January | 21.11 | 365 | 15.56 | 365 |
TYPE2_CLGSETP_SCH_NO_OPTIMUM | SMSTORE2 DUAL SP CONTROL | July | 23.89 | 365 | 29.44 | 365 |
TYPE3_HTGSETP_SCH_NO_OPTIMUM | LGSTORE2 DUAL SP CONTROL | January | 21.11 | 365 | 15.56 | 365 |
TYPE3_CLGSETP_SCH_NO_OPTIMUM | LGSTORE2 DUAL SP CONTROL | July | 23.89 | 365 | 29.44 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:31
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
LGSTORE1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 8675.83 | 84.17 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 8665.50 | 94.50 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 8701.50 | 58.50 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 8733.83 | 26.17 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 8740.00 | 20.00 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 8741.33 | 18.67 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 8745.00 | 15.00 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 8737.83 | 22.17 | 0.00 | 0.00 | 0.00 |
Min | 8665.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 94.50 | 0.00 | 0.00 | 0.00 |
Average | 8726.08 | 33.92 | 0.00 | 0.00 | 0.00 |
Sum | 87260.83 | 339.17 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
LGSTORE1 | 89041.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 43777.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 25464.00 | 11.00 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 25464.00 | 11.00 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 25465.83 | 9.17 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 93187.00 | 24.00 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 45902.50 | 9.50 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 45902.50 | 9.50 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 45902.50 | 9.50 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 45901.00 | 11.00 | 0.00 | 0.00 | 0.00 |
Min | 25464.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 93187.00 | 24.00 | 0.00 | 0.00 | 0.00 |
Average | 48600.73 | 9.47 | 0.00 | 0.00 | 0.00 |
Sum | 486007.33 | 94.67 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
LGSTORE1 | 7721.50 | 1038.50 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 8331.50 | 428.50 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 7372.67 | 1387.33 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 7374.33 | 1385.67 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 7367.17 | 1392.83 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 7272.33 | 1487.67 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 7282.50 | 1477.50 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 7282.50 | 1477.50 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 7293.83 | 1466.17 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 7324.50 | 1435.50 | 0.00 | 0.00 | 0.00 |
Min | 7272.33 | 428.50 | 0.00 | 0.00 | 0.00 |
Max | 8331.50 | 1487.67 | 0.00 | 0.00 | 0.00 |
Average | 7462.28 | 1297.72 | 0.00 | 0.00 | 0.00 |
Sum | 74622.83 | 12977.17 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
LGSTORE1 | 83213.00 | 5828.00 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 41735.00 | 2042.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 23773.50 | 1701.50 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 23756.33 | 1718.67 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 23613.17 | 1861.83 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 83116.67 | 10094.33 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 40882.00 | 5030.00 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 40796.33 | 5115.67 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 40610.17 | 5301.83 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 40633.17 | 5278.83 | 0.00 | 0.00 | 0.00 |
Min | 23613.17 | 1701.50 | 0.00 | 0.00 | 0.00 |
Max | 83213.00 | 10094.33 | 0.00 | 0.00 | 0.00 |
Average | 44212.93 | 4397.27 | 0.00 | 0.00 | 0.00 |
Sum | 442129.33 | 43972.67 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:31
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:31
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
For: Environment
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTRIPMALL
For: Environment
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4A
For: Environment
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_NEWYORK
For: Environment
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: ZoneCoolingSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.856156E+09 | 11385.25 | 06-JAN-00:02 | -4.6 | -6.9 | 0.106522E+10 | 1275.40 | 01-JAN-18:00 | -4.6 | -6.9 |
February | 0.805443E+09 | 11356.91 | 03-FEB-00:02 | -4.5 | -7.3 | 0.961523E+09 | 1275.40 | 05-FEB-18:49 | -8.7 | -10.9 |
March | 0.267190E+10 | 9974.44 | 17-MAR-23:03 | -1.7 | -1.9 | 0.107141E+10 | 1432.28 | 03-MAR-13:00 | -1.7 | -1.9 |
April | 0.439814E+10 | 7344.51 | 08-APR-13:00 | 22.80 | 16.08 | 0.114599E+10 | 1685.92 | 09-APR-12:50 | 19.68 | 15.85 |
May | 0.728910E+10 | 11655.86 | 30-MAY-14:00 | 29.40 | 16.93 | 0.134375E+10 | 1685.98 | 29-MAY-16:10 | 29.40 | 16.93 |
June | 0.117130E+11 | 29498.54 | 20-JUN-07:02 | 23.17 | 19.56 | 0.135445E+10 | 1686.01 | 18-JUN-17:30 | 23.17 | 19.56 |
July | 0.152956E+11 | 35816.57 | 11-JUL-07:02 | 22.30 | 16.06 | 0.141282E+10 | 1686.03 | 30-JUL-12:00 | 27.20 | 24.02 |
August | 0.163247E+11 | 31101.62 | 22-AUG-07:02 | 26.20 | 18.45 | 0.139408E+10 | 1686.04 | 18-AUG-12:00 | 26.20 | 18.45 |
September | 0.117814E+11 | 36336.94 | 02-SEP-07:02 | 21.70 | 16.23 | 0.136426E+10 | 1686.02 | 04-SEP-17:40 | 24.07 | 18.97 |
October | 0.917635E+10 | 13300.18 | 06-OCT-07:03 | 20.00 | 18.15 | 0.133984E+10 | 1685.95 | 21-OCT-12:50 | 19.32 | 16.14 |
November | 0.371954E+10 | 10795.75 | 24-NOV-00:02 | -3.3 | -5.8 | 0.107471E+10 | 1685.83 | 04-NOV-12:50 | -3.3 | -5.8 |
December | 0.153810E+10 | 10831.85 | 22-DEC-00:02 | -3.3 | -6.0 | 0.107068E+10 | 1288.59 | 17-DEC-13:00 | -3.3 | -6.0 |
Annual Sum or Average | 0.855694E+11 | 0.145987E+11 | ||||||||
Minimum of Months | 0.805443E+09 | 7344.51 | -4.6 | -7.3 | 0.961523E+09 | 1275.40 | -8.7 | -10.9 | ||
Maximum of Months | 0.163247E+11 | 36336.94 | 29.40 | 19.56 | 0.141282E+10 | 1686.04 | 29.40 | 24.02 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.528540E+09 | 2414.83 | 19-JAN-18:10 | 6.60 | 1.81 | 0.546727E+09 | 756.70 | 29-JAN-18:00 | 0.00 | -2.5 |
February | 0.523025E+09 | 6552.84 | 12-FEB-10:52 | -8.3 | -11.1 | 0.494748E+09 | 779.68 | 20-FEB-18:00 | 3.90 | 2.68 |
March | 0.146418E+10 | 4357.61 | 19-MAR-09:23 | 0.85 | 0.62 | 0.564349E+09 | 842.94 | 26-MAR-17:49 | 10.10 | 9.17 |
April | 0.249387E+10 | 14546.67 | 16-APR-17:09 | 21.93 | 13.37 | 0.601754E+09 | 842.97 | 08-APR-12:00 | 21.93 | 13.37 |
May | 0.434022E+10 | 16814.76 | 27-MAY-22:03 | 18.80 | 10.64 | 0.689218E+09 | 842.97 | 28-MAY-16:00 | 21.10 | 15.12 |
June | 0.676044E+10 | 17621.73 | 26-JUN-07:03 | 23.40 | 18.26 | 0.676411E+09 | 842.98 | 18-JUN-16:10 | 23.40 | 18.26 |
July | 0.843523E+10 | 19406.69 | 11-JUL-07:02 | 22.30 | 16.06 | 0.706415E+09 | 842.99 | 16-JUL-12:30 | 31.70 | 22.52 |
August | 0.885846E+10 | 17885.78 | 19-AUG-07:03 | 21.28 | 16.54 | 0.696599E+09 | 843.00 | 11-AUG-12:00 | 21.28 | 16.54 |
September | 0.670083E+10 | 19531.50 | 02-SEP-07:02 | 21.70 | 16.23 | 0.681386E+09 | 842.98 | 08-SEP-12:09 | 24.90 | 19.74 |
October | 0.504074E+10 | 15866.15 | 15-OCT-18:50 | 17.30 | 11.58 | 0.689839E+09 | 842.96 | 14-OCT-12:30 | 17.30 | 11.58 |
November | 0.194336E+10 | 4221.78 | 21-NOV-09:23 | 1.40 | -0.3 | 0.572466E+09 | 842.90 | 11-NOV-18:00 | 1.40 | -0.3 |
December | 0.913356E+09 | 4193.77 | 09-DEC-09:43 | 1.52 | -0.4 | 0.556960E+09 | 812.42 | 17-DEC-18:00 | 7.80 | 3.53 |
Annual Sum or Average | 0.480022E+11 | 0.747687E+10 | ||||||||
Minimum of Months | 0.523025E+09 | 2414.83 | -8.3 | -11.1 | 0.494748E+09 | 756.70 | 0.00 | -2.5 | ||
Maximum of Months | 0.885846E+10 | 19531.50 | 23.40 | 18.26 | 0.706415E+09 | 843.00 | 31.70 | 22.52 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.290299E+09 | 4683.13 | 06-JAN-19:12 | -0.6 | -3.3 | 0.317180E+09 | 637.68 | 07-JAN-13:30 | 0.60 | -4.2 |
February | 0.289383E+09 | 5766.20 | 05-FEB-11:22 | -5.0 | -7.7 | 0.288103E+09 | 637.68 | 11-FEB-13:00 | 6.10 | 2.34 |
March | 0.111156E+10 | 4802.62 | 17-MAR-09:23 | -1.1 | -2.3 | 0.332501E+09 | 702.43 | 27-MAR-16:30 | 21.65 | 15.87 |
April | 0.187407E+10 | 4334.75 | 08-APR-12:30 | 23.60 | 16.18 | 0.348082E+09 | 842.97 | 08-APR-12:00 | 22.80 | 16.08 |
May | 0.309835E+10 | 8187.46 | 30-MAY-06:03 | 20.47 | 15.45 | 0.413422E+09 | 842.92 | 27-MAY-12:39 | 20.47 | 15.45 |
June | 0.500418E+10 | 17018.38 | 23-JUN-06:03 | 21.38 | 17.00 | 0.416504E+09 | 842.95 | 24-JUN-12:00 | 27.80 | 23.34 |
July | 0.628179E+10 | 19653.72 | 11-JUL-06:02 | 20.87 | 15.63 | 0.419963E+09 | 842.98 | 29-JUL-12:50 | 25.73 | 20.27 |
August | 0.682038E+10 | 21151.43 | 23-AUG-06:02 | 19.18 | 14.64 | 0.431671E+09 | 842.97 | 05-AUG-12:00 | 19.18 | 14.64 |
September | 0.487818E+10 | 19845.18 | 02-SEP-06:02 | 21.70 | 16.19 | 0.410116E+09 | 842.97 | 02-SEP-12:09 | 24.50 | 17.34 |
October | 0.378681E+10 | 10075.85 | 06-OCT-06:03 | 19.50 | 17.97 | 0.404866E+09 | 842.96 | 21-OCT-12:30 | 19.15 | 15.87 |
November | 0.150585E+10 | 3364.15 | 06-NOV-08:61 | 6.38 | 3.40 | 0.325189E+09 | 842.90 | 04-NOV-12:20 | 6.38 | 3.40 |
December | 0.573593E+09 | 4061.69 | 27-DEC-09:43 | 1.78 | 1.22 | 0.316900E+09 | 637.68 | 02-DEC-13:00 | 1.78 | 1.22 |
Annual Sum or Average | 0.355144E+11 | 0.442450E+10 | ||||||||
Minimum of Months | 0.289383E+09 | 3364.15 | -5.0 | -7.7 | 0.288103E+09 | 637.68 | 0.60 | -4.2 | ||
Maximum of Months | 0.682038E+10 | 21151.43 | 23.60 | 17.97 | 0.431671E+09 | 842.98 | 27.80 | 23.34 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.236388E+09 | 5399.02 | 05-JAN-19:12 | -3.7 | -6.6 | 0.317182E+09 | 637.68 | 07-JAN-13:00 | 0.60 | -4.3 |
February | 0.246583E+09 | 5568.41 | 07-FEB-18:33 | -4.4 | -6.9 | 0.288101E+09 | 637.68 | 04-FEB-13:20 | -4.4 | -6.9 |
March | 0.989150E+09 | 3395.13 | 29-MAR-17:20 | 5.73 | 4.14 | 0.331682E+09 | 702.42 | 27-MAR-16:30 | 5.73 | 4.14 |
April | 0.174088E+10 | 4188.41 | 08-APR-12:30 | 23.60 | 16.18 | 0.346696E+09 | 842.97 | 08-APR-12:50 | 23.07 | 16.12 |
May | 0.299152E+10 | 7864.75 | 31-MAY-06:03 | 18.35 | 16.38 | 0.411362E+09 | 842.92 | 27-MAY-12:39 | 18.35 | 16.38 |
June | 0.497776E+10 | 17203.00 | 23-JUN-06:03 | 21.38 | 17.00 | 0.416495E+09 | 842.95 | 24-JUN-12:00 | 27.80 | 23.34 |
July | 0.628440E+10 | 19752.60 | 11-JUL-06:02 | 20.87 | 15.63 | 0.419960E+09 | 842.98 | 22-JUL-12:00 | 26.70 | 23.40 |
August | 0.683593E+10 | 21248.16 | 23-AUG-06:02 | 19.18 | 14.64 | 0.431670E+09 | 842.98 | 05-AUG-12:00 | 19.18 | 14.64 |
September | 0.485232E+10 | 19933.88 | 02-SEP-06:02 | 21.70 | 16.19 | 0.410085E+09 | 842.97 | 02-SEP-12:09 | 24.50 | 17.34 |
October | 0.369228E+10 | 9908.71 | 06-OCT-06:03 | 19.50 | 17.97 | 0.403536E+09 | 842.96 | 21-OCT-12:39 | 19.23 | 16.00 |
November | 0.137969E+10 | 3289.37 | 06-NOV-08:61 | 6.38 | 3.40 | 0.323098E+09 | 842.90 | 04-NOV-12:20 | 6.38 | 3.40 |
December | 0.485862E+09 | 5077.35 | 22-DEC-09:43 | -2.3 | -5.1 | 0.316836E+09 | 637.68 | 02-DEC-13:09 | -2.3 | -5.1 |
Annual Sum or Average | 0.347128E+11 | 0.441670E+10 | ||||||||
Minimum of Months | 0.236388E+09 | 3289.37 | -4.4 | -6.9 | 0.288101E+09 | 637.68 | -4.4 | -6.9 | ||
Maximum of Months | 0.683593E+10 | 21248.16 | 23.60 | 17.97 | 0.431670E+09 | 842.98 | 27.80 | 23.40 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.165739E+09 | 4814.97 | 30-JAN-10:13 | -1.1 | -3.4 | 0.317181E+09 | 637.68 | 07-JAN-13:39 | -1.1 | -3.4 |
February | 0.159191E+09 | 3916.36 | 10-FEB-20:33 | 2.40 | 0.41 | 0.288104E+09 | 637.68 | 04-FEB-13:00 | 2.40 | 0.41 |
March | 0.825681E+09 | 4771.93 | 18-MAR-09:02 | -0.9 | -1.4 | 0.330599E+09 | 702.41 | 27-MAR-17:10 | 20.73 | 15.29 |
April | 0.153384E+10 | 3894.12 | 08-APR-12:40 | 23.33 | 16.15 | 0.344329E+09 | 842.95 | 08-APR-12:20 | 23.33 | 16.15 |
May | 0.276914E+10 | 6514.59 | 31-MAY-06:03 | 18.35 | 16.38 | 0.407699E+09 | 842.92 | 27-MAY-12:39 | 18.35 | 16.38 |
June | 0.477731E+10 | 16007.39 | 26-JUN-06:03 | 21.97 | 17.81 | 0.416448E+09 | 842.94 | 24-JUN-12:00 | 21.97 | 17.81 |
July | 0.610608E+10 | 19484.30 | 11-JUL-06:02 | 20.87 | 15.63 | 0.419926E+09 | 842.98 | 01-JUL-12:39 | 20.87 | 15.63 |
August | 0.665190E+10 | 20964.19 | 23-AUG-06:02 | 19.18 | 14.64 | 0.431635E+09 | 842.97 | 26-AUG-12:09 | 25.10 | 18.26 |
September | 0.465982E+10 | 19646.66 | 02-SEP-06:02 | 21.70 | 16.19 | 0.409958E+09 | 842.97 | 02-SEP-12:09 | 24.50 | 17.34 |
October | 0.349911E+10 | 8723.52 | 06-OCT-06:03 | 19.50 | 17.97 | 0.401225E+09 | 842.95 | 21-OCT-12:50 | 19.32 | 16.14 |
November | 0.121093E+10 | 4787.86 | 22-NOV-20:42 | -1.0 | -3.5 | 0.320254E+09 | 842.90 | 04-NOV-12:20 | -1.0 | -3.5 |
December | 0.366545E+09 | 4357.02 | 27-DEC-20:23 | 0.85 | 0.62 | 0.316799E+09 | 637.68 | 02-DEC-13:39 | 0.85 | 0.62 |
Annual Sum or Average | 0.327253E+11 | 0.440416E+10 | ||||||||
Minimum of Months | 0.159191E+09 | 3894.12 | -1.1 | -3.5 | 0.288104E+09 | 637.68 | -1.1 | -3.5 | ||
Maximum of Months | 0.665190E+10 | 20964.19 | 23.33 | 17.97 | 0.431635E+09 | 842.98 | 25.10 | 18.26 |
Report: ZoneCoolingSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 93228514.38 | 2205.49 | 19-JAN-12:00 | 7.20 | 3.79 | 0.108442E+10 | 1700.53 | 07-JAN-15:39 | 7.20 | 3.79 |
February | 86887524.75 | 2260.40 | 11-FEB-12:00 | 6.10 | 1.69 | 0.987309E+09 | 1700.53 | 04-FEB-15:09 | 6.10 | 1.69 |
March | 0.104236E+10 | 9308.58 | 22-MAR-19:03 | -0.1 | -4.8 | 0.112930E+10 | 1994.91 | 27-MAR-16:00 | 21.10 | 15.41 |
April | 0.225598E+10 | 6653.14 | 12-APR-08:63 | 5.78 | 0.39 | 0.116873E+10 | 2247.80 | 08-APR-14:09 | 5.78 | 0.39 |
May | 0.436402E+10 | 12426.34 | 30-MAY-07:03 | 23.17 | 16.07 | 0.137413E+10 | 2247.83 | 20-MAY-14:09 | 23.17 | 16.07 |
June | 0.788514E+10 | 28219.20 | 26-JUN-07:03 | 23.40 | 18.26 | 0.142875E+10 | 2247.93 | 03-JUN-14:50 | 23.40 | 18.26 |
July | 0.103477E+11 | 34351.26 | 11-JUL-07:02 | 22.30 | 16.06 | 0.143773E+10 | 2248.01 | 01-JUL-14:00 | 22.30 | 16.06 |
August | 0.113773E+11 | 32595.95 | 19-AUG-07:03 | 21.28 | 16.54 | 0.147976E+10 | 2248.00 | 26-AUG-14:00 | 25.60 | 19.37 |
September | 0.766945E+10 | 34644.00 | 02-SEP-07:02 | 21.70 | 16.23 | 0.140717E+10 | 2248.00 | 02-SEP-14:00 | 23.90 | 18.81 |
October | 0.566140E+10 | 13442.95 | 06-OCT-07:03 | 20.00 | 18.15 | 0.135829E+10 | 2247.91 | 14-OCT-14:50 | 18.30 | 16.20 |
November | 0.167062E+10 | 8327.37 | 21-NOV-10:32 | 2.03 | 0.15 | 0.107814E+10 | 2241.42 | 04-NOV-14:09 | 2.03 | 0.15 |
December | 0.267076E+09 | 8841.96 | 15-DEC-10:43 | 0.92 | -2.4 | 0.108625E+10 | 1700.53 | 09-DEC-15:20 | 0.92 | -2.4 |
Annual Sum or Average | 0.527211E+11 | 0.150200E+11 | ||||||||
Minimum of Months | 86887524.75 | 2205.49 | -0.1 | -4.8 | 0.987309E+09 | 1700.53 | 0.92 | -2.4 | ||
Maximum of Months | 0.113773E+11 | 34644.00 | 23.40 | 18.26 | 0.147976E+10 | 2248.01 | 25.60 | 19.37 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 40963771.29 | 3567.79 | 19-JAN-20:23 | 4.15 | 1.12 | 0.542193E+09 | 850.24 | 07-JAN-15:50 | 4.15 | 1.12 |
February | 37070563.68 | 4467.09 | 02-FEB-19:12 | 0.53 | -4.7 | 0.493638E+09 | 850.24 | 04-FEB-15:39 | 1.13 | 0.53 |
March | 0.481663E+09 | 3899.68 | 09-MAR-19:03 | 2.80 | 2.55 | 0.564288E+09 | 997.43 | 27-MAR-16:00 | 21.10 | 15.41 |
April | 0.105890E+10 | 3269.70 | 12-APR-08:63 | 5.78 | 0.39 | 0.582713E+09 | 1123.87 | 08-APR-14:20 | 5.78 | 0.39 |
May | 0.212124E+10 | 5796.00 | 30-MAY-13:00 | 30.00 | 18.00 | 0.684449E+09 | 1123.88 | 20-MAY-14:09 | 30.00 | 18.00 |
June | 0.401581E+10 | 14484.05 | 26-JUN-07:03 | 23.40 | 18.26 | 0.714347E+09 | 1123.93 | 03-JUN-14:50 | 23.40 | 18.26 |
July | 0.532838E+10 | 17638.51 | 11-JUL-07:02 | 22.30 | 16.06 | 0.718830E+09 | 1123.97 | 01-JUL-14:00 | 22.30 | 16.06 |
August | 0.585604E+10 | 15464.51 | 19-AUG-07:03 | 21.28 | 16.54 | 0.739845E+09 | 1123.97 | 26-AUG-14:00 | 25.60 | 19.37 |
September | 0.390500E+10 | 17783.51 | 02-SEP-07:02 | 21.70 | 16.23 | 0.703521E+09 | 1123.97 | 02-SEP-14:00 | 23.90 | 18.81 |
October | 0.280794E+10 | 6193.73 | 06-OCT-07:03 | 20.00 | 18.15 | 0.678044E+09 | 1123.92 | 14-OCT-14:50 | 18.30 | 16.20 |
November | 0.792868E+09 | 4539.44 | 24-NOV-11:23 | 0.30 | -2.7 | 0.538051E+09 | 1114.36 | 04-NOV-14:09 | 0.30 | -2.7 |
December | 0.117861E+09 | 4294.60 | 01-DEC-19:33 | 1.30 | -2.1 | 0.543107E+09 | 850.24 | 16-DEC-15:30 | 9.75 | 4.22 |
Annual Sum or Average | 0.265637E+11 | 0.750303E+10 | ||||||||
Minimum of Months | 37070563.68 | 3269.70 | 0.30 | -4.7 | 0.493638E+09 | 850.24 | 0.30 | -2.7 | ||
Maximum of Months | 0.585604E+10 | 17783.51 | 30.00 | 18.26 | 0.739845E+09 | 1123.97 | 30.00 | 19.37 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 35706094.87 | 3315.02 | 12-JAN-18:23 | 5.30 | 3.03 | 0.542191E+09 | 850.24 | 07-JAN-15:30 | 5.30 | 3.03 |
February | 33696661.85 | 4313.45 | 17-FEB-19:42 | 1.28 | -0.2 | 0.493640E+09 | 850.24 | 04-FEB-15:09 | 1.28 | -0.2 |
March | 0.448883E+09 | 3710.10 | 21-MAR-19:13 | 3.53 | -0.9 | 0.563917E+09 | 997.31 | 27-MAR-16:40 | 21.47 | 15.72 |
April | 0.100398E+10 | 2963.30 | 08-APR-12:30 | 23.60 | 16.18 | 0.581112E+09 | 1123.87 | 08-APR-14:20 | 20.97 | 15.19 |
May | 0.203322E+10 | 5711.33 | 30-MAY-13:00 | 30.00 | 18.00 | 0.681441E+09 | 1123.88 | 20-MAY-14:09 | 30.00 | 18.00 |
June | 0.394435E+10 | 14394.11 | 26-JUN-07:03 | 23.40 | 18.26 | 0.714327E+09 | 1123.93 | 03-JUN-14:50 | 23.40 | 18.26 |
July | 0.526584E+10 | 17542.79 | 11-JUL-07:02 | 22.30 | 16.06 | 0.718822E+09 | 1123.97 | 01-JUL-14:50 | 22.30 | 16.06 |
August | 0.579441E+10 | 15017.69 | 19-AUG-07:03 | 21.28 | 16.54 | 0.739839E+09 | 1123.97 | 26-AUG-14:00 | 25.60 | 19.37 |
September | 0.384290E+10 | 17687.18 | 02-SEP-07:02 | 21.70 | 16.23 | 0.703372E+09 | 1123.97 | 02-SEP-14:00 | 23.90 | 18.81 |
October | 0.273363E+10 | 5748.77 | 06-OCT-07:03 | 20.00 | 18.15 | 0.676151E+09 | 1123.91 | 14-OCT-14:50 | 18.30 | 16.20 |
November | 0.754512E+09 | 3914.43 | 25-NOV-11:23 | 2.75 | 0.83 | 0.536929E+09 | 1106.85 | 04-NOV-14:09 | 2.75 | 0.83 |
December | 0.101353E+09 | 4650.16 | 21-DEC-20:03 | -0.2 | -3.4 | 0.543108E+09 | 850.24 | 02-DEC-15:39 | -0.2 | -3.4 |
Annual Sum or Average | 0.259925E+11 | 0.749485E+10 | ||||||||
Minimum of Months | 33696661.85 | 2963.30 | -0.2 | -3.4 | 0.493640E+09 | 850.24 | -0.2 | -3.4 | ||
Maximum of Months | 0.579441E+10 | 17687.18 | 30.00 | 18.26 | 0.739839E+09 | 1123.97 | 30.00 | 19.37 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 17271699.35 | 3191.89 | 17-JAN-18:03 | 5.82 | 2.28 | 0.542191E+09 | 850.24 | 07-JAN-15:20 | 5.82 | 2.28 |
February | 17092430.24 | 2996.96 | 01-FEB-18:23 | 6.65 | 3.54 | 0.493639E+09 | 850.24 | 11-FEB-15:00 | 5.00 | 2.17 |
March | 0.339304E+09 | 3639.38 | 13-MAR-18:23 | 3.85 | -1.2 | 0.562972E+09 | 983.07 | 27-MAR-16:40 | 21.47 | 15.72 |
April | 0.845880E+09 | 3051.51 | 22-APR-10:13 | 6.47 | 5.31 | 0.577385E+09 | 1123.87 | 08-APR-14:20 | 6.47 | 5.31 |
May | 0.183500E+10 | 5551.70 | 30-MAY-13:00 | 30.00 | 18.00 | 0.673957E+09 | 1123.88 | 20-MAY-14:09 | 30.00 | 18.00 |
June | 0.376763E+10 | 14156.12 | 26-JUN-07:03 | 23.40 | 18.26 | 0.714246E+09 | 1123.93 | 03-JUN-14:50 | 23.40 | 18.26 |
July | 0.516170E+10 | 17380.59 | 11-JUL-07:02 | 22.30 | 16.06 | 0.718806E+09 | 1123.97 | 01-JUL-14:39 | 22.30 | 16.06 |
August | 0.571130E+10 | 14819.70 | 22-AUG-07:02 | 26.20 | 18.45 | 0.739830E+09 | 1123.97 | 26-AUG-14:00 | 25.60 | 19.37 |
September | 0.371256E+10 | 17538.87 | 02-SEP-07:02 | 21.70 | 16.23 | 0.702785E+09 | 1123.97 | 02-SEP-14:00 | 23.90 | 18.81 |
October | 0.256374E+10 | 4952.86 | 04-OCT-13:00 | 25.00 | 18.54 | 0.671511E+09 | 1123.92 | 21-OCT-14:39 | 19.40 | 17.36 |
November | 0.648979E+09 | 3237.83 | 15-NOV-20:23 | 5.60 | 2.95 | 0.534625E+09 | 1091.01 | 04-NOV-14:09 | 5.60 | 2.95 |
December | 60976908.19 | 4204.36 | 01-DEC-18:53 | 1.70 | -1.7 | 0.543110E+09 | 850.24 | 02-DEC-15:09 | 6.60 | 1.36 |
Annual Sum or Average | 0.246814E+11 | 0.747506E+10 | ||||||||
Minimum of Months | 17092430.24 | 2996.96 | 1.70 | -1.7 | 0.493639E+09 | 850.24 | 5.00 | 1.36 | ||
Maximum of Months | 0.571130E+10 | 17538.87 | 30.00 | 18.54 | 0.739830E+09 | 1123.97 | 30.00 | 19.37 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 288759.10 | 214.98 | 19-JAN-12:00 | 7.20 | 3.79 | 0.542193E+09 | 850.24 | 07-JAN-15:39 | 7.20 | 3.79 |
February | 89619.46 | 119.35 | 17-FEB-12:00 | 7.20 | 2.04 | 0.493640E+09 | 850.24 | 11-FEB-15:09 | 7.20 | 2.04 |
March | 0.136437E+09 | 2748.52 | 29-MAR-14:55 | 7.20 | 5.20 | 0.561661E+09 | 945.94 | 27-MAR-16:40 | 7.20 | 5.20 |
April | 0.561087E+09 | 2899.62 | 08-APR-12:20 | 23.87 | 16.21 | 0.573268E+09 | 1123.92 | 08-APR-14:30 | 21.15 | 15.15 |
May | 0.157604E+10 | 5914.29 | 30-MAY-13:00 | 30.00 | 18.00 | 0.661721E+09 | 1123.88 | 20-MAY-14:09 | 30.00 | 18.00 |
June | 0.368067E+10 | 14169.01 | 20-JUN-07:02 | 23.17 | 19.56 | 0.713925E+09 | 1123.96 | 24-JUN-14:00 | 26.10 | 22.54 |
July | 0.549623E+10 | 16189.51 | 11-JUL-07:02 | 22.30 | 16.06 | 0.718836E+09 | 1123.98 | 29-JUL-14:00 | 25.60 | 20.62 |
August | 0.624443E+10 | 15961.47 | 22-AUG-07:02 | 26.20 | 18.45 | 0.739870E+09 | 1123.98 | 26-AUG-14:39 | 25.60 | 19.26 |
September | 0.379580E+10 | 18684.84 | 02-SEP-07:02 | 21.70 | 16.23 | 0.700930E+09 | 1123.98 | 02-SEP-14:00 | 23.90 | 18.81 |
October | 0.234900E+10 | 5298.07 | 04-OCT-13:00 | 25.00 | 18.54 | 0.663814E+09 | 1123.87 | 21-OCT-14:20 | 19.40 | 17.48 |
November | 0.435722E+09 | 2201.14 | 13-NOV-18:15 | 9.60 | 8.74 | 0.532318E+09 | 1079.70 | 04-NOV-14:09 | 9.60 | 8.74 |
December | 4044647.01 | 685.86 | 20-DEC-12:00 | 8.90 | 5.16 | 0.543112E+09 | 850.24 | 02-DEC-15:39 | 8.90 | 5.16 |
Annual Sum or Average | 0.242798E+11 | 0.744529E+10 | ||||||||
Minimum of Months | 89619.46 | 119.35 | 7.20 | 2.04 | 0.493640E+09 | 850.24 | 7.20 | 2.04 | ||
Maximum of Months | 0.624443E+10 | 18684.84 | 30.00 | 19.56 | 0.739870E+09 | 1123.98 | 30.00 | 22.54 |
Report: ZoneHeatingSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.511208E+10 | 60323.05 | 02-JAN-08:61 | -11.0 |
February | 0.477610E+10 | 60356.05 | 06-FEB-08:12 | -12.6 |
March | 0.194807E+10 | 60298.70 | 20-MAR-07:01 | -0.1 |
April | 0.632641E+09 | 60276.86 | 03-APR-07:01 | 3.68 |
May | 68163375.77 | 20554.28 | 01-MAY-07:01 | 10.37 |
June | 21917793.89 | 1611.90 | 26-JUN-07:05 | 23.40 |
July | 25376486.65 | 1665.81 | 11-JUL-07:04 | 22.30 |
August | 27237909.87 | 1640.72 | 19-AUG-07:05 | 21.28 |
September | 24062563.28 | 1707.47 | 02-SEP-07:04 | 21.70 |
October | 55059077.63 | 2570.07 | 29-OCT-07:10 | 2.95 |
November | 0.105157E+10 | 60309.31 | 24-NOV-08:61 | -3.5 |
December | 0.288446E+10 | 60301.66 | 22-DEC-08:61 | -4.1 |
Annual Sum or Average | 0.166267E+11 | |||
Minimum of Months | 21917793.89 | 1611.90 | -12.6 | |
Maximum of Months | 0.511208E+10 | 60356.05 | 23.40 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.153150E+10 | 31383.58 | 02-JAN-08:61 | -11.0 |
February | 0.140271E+10 | 31367.07 | 15-FEB-08:61 | -4.0 |
March | 0.389450E+09 | 31368.43 | 23-MAR-07:01 | -2.9 |
April | 0.111926E+09 | 31355.36 | 03-APR-07:01 | 3.68 |
May | 23664239.11 | 794.21 | 30-MAY-07:07 | 23.17 |
June | 14261389.27 | 1007.18 | 26-JUN-07:05 | 23.40 |
July | 13715271.75 | 1013.02 | 05-JUL-07:05 | 22.30 |
August | 14875702.99 | 1017.48 | 19-AUG-07:05 | 21.28 |
September | 11963904.98 | 979.49 | 02-SEP-07:04 | 21.70 |
October | 23712983.69 | 799.10 | 06-OCT-07:07 | 20.00 |
November | 0.232815E+09 | 31368.38 | 24-NOV-08:61 | -3.5 |
December | 0.733734E+09 | 31369.57 | 22-DEC-08:61 | -4.1 |
Annual Sum or Average | 0.450433E+10 | |||
Minimum of Months | 11963904.98 | 794.21 | -11.0 | |
Maximum of Months | 0.153150E+10 | 31383.58 | 23.40 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.204571E+10 | 31532.94 | 08-JAN-08:61 | -4.3 |
February | 0.177478E+10 | 31517.95 | 26-FEB-08:61 | -6.1 |
March | 0.616119E+09 | 31381.43 | 19-MAR-07:01 | 0.60 |
April | 0.162611E+09 | 31230.54 | 02-APR-07:01 | 4.18 |
May | 24422355.96 | 744.57 | 30-MAY-06:07 | 20.47 |
June | 25494527.45 | 2036.52 | 19-JUN-19:03 | 31.42 |
July | 37289169.93 | 1617.48 | 16-JUL-16:03 | 29.90 |
August | 51888547.75 | 2505.57 | 04-AUG-19:02 | 33.12 |
September | 16224624.21 | 956.03 | 01-SEP-19:12 | 27.03 |
October | 23745481.59 | 796.97 | 06-OCT-06:07 | 19.50 |
November | 0.394256E+09 | 31395.03 | 23-NOV-08:61 | -2.6 |
December | 0.108273E+10 | 31483.94 | 31-DEC-08:61 | -1.7 |
Annual Sum or Average | 0.625527E+10 | |||
Minimum of Months | 16224624.21 | 744.57 | -6.1 | |
Maximum of Months | 0.204571E+10 | 31532.94 | 33.12 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.225053E+10 | 31399.08 | 08-JAN-08:61 | -4.3 |
February | 0.193867E+10 | 31384.21 | 26-FEB-08:61 | -6.1 |
March | 0.708885E+09 | 31247.82 | 19-MAR-07:01 | 0.60 |
April | 0.199109E+09 | 31097.09 | 02-APR-07:01 | 4.18 |
May | 26949260.19 | 976.35 | 01-MAY-07:08 | 10.37 |
June | 25477572.00 | 2038.30 | 19-JUN-19:03 | 31.42 |
July | 37365919.11 | 1618.59 | 16-JUL-16:03 | 29.90 |
August | 51760428.16 | 2506.32 | 04-AUG-19:02 | 33.12 |
September | 16500464.78 | 960.75 | 03-SEP-07:05 | 19.27 |
October | 25039801.69 | 1025.51 | 29-OCT-08:07 | 6.88 |
November | 0.471729E+09 | 31261.21 | 23-NOV-08:61 | -2.6 |
December | 0.121924E+10 | 31350.45 | 31-DEC-08:61 | -1.7 |
Annual Sum or Average | 0.697126E+10 | |||
Minimum of Months | 16500464.78 | 960.75 | -6.1 | |
Maximum of Months | 0.225053E+10 | 31399.08 | 33.12 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.257282E+10 | 31364.16 | 08-JAN-08:61 | -4.3 |
February | 0.219364E+10 | 31349.50 | 26-FEB-08:61 | -6.1 |
March | 0.880843E+09 | 31214.55 | 19-MAR-07:01 | 0.60 |
April | 0.252391E+09 | 31065.02 | 02-APR-07:01 | 4.18 |
May | 31672576.13 | 1025.16 | 01-MAY-06:10 | 7.67 |
June | 24636144.42 | 2043.66 | 19-JUN-19:03 | 31.42 |
July | 39042180.55 | 1624.11 | 16-JUL-16:03 | 29.90 |
August | 52605370.01 | 2510.32 | 04-AUG-19:02 | 33.12 |
September | 16741073.32 | 961.64 | 01-SEP-19:12 | 27.03 |
October | 27750242.41 | 1593.29 | 29-OCT-08:05 | 6.88 |
November | 0.586219E+09 | 31227.70 | 23-NOV-08:61 | -2.6 |
December | 0.145201E+10 | 31316.13 | 31-DEC-08:61 | -1.7 |
Annual Sum or Average | 0.813036E+10 | |||
Minimum of Months | 16741073.32 | 961.64 | -6.1 | |
Maximum of Months | 0.257282E+10 | 31364.16 | 33.12 |
Report: ZoneHeatingSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.532528E+10 | 58142.76 | 02-JAN-08:12 | -10.9 |
February | 0.452882E+10 | 58040.43 | 06-FEB-08:12 | -12.6 |
March | 0.188462E+10 | 57874.69 | 14-MAR-07:01 | -1.4 |
April | 0.549513E+09 | 57858.54 | 03-APR-07:01 | 3.68 |
May | 73406696.67 | 39189.77 | 01-MAY-07:01 | 10.37 |
June | 26883195.95 | 1579.45 | 26-JUN-07:05 | 23.40 |
July | 46796762.84 | 3265.91 | 16-JUL-16:03 | 29.90 |
August | 43154374.91 | 3291.92 | 13-AUG-16:02 | 29.90 |
September | 27760873.05 | 1573.77 | 03-SEP-08:05 | 21.38 |
October | 57935074.76 | 11478.95 | 29-OCT-08:62 | 6.88 |
November | 0.123890E+10 | 57875.75 | 24-NOV-08:61 | -3.5 |
December | 0.303671E+10 | 57871.18 | 22-DEC-08:61 | -4.1 |
Annual Sum or Average | 0.168398E+11 | |||
Minimum of Months | 26883195.95 | 1573.77 | -12.6 | |
Maximum of Months | 0.532528E+10 | 58142.76 | 29.90 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.302608E+10 | 29898.90 | 02-JAN-08:12 | -10.9 |
February | 0.260943E+10 | 29813.98 | 06-FEB-08:12 | -12.6 |
March | 0.115199E+10 | 29670.75 | 14-MAR-07:01 | -1.4 |
April | 0.345221E+09 | 29661.76 | 03-APR-07:01 | 3.68 |
May | 42079657.55 | 22325.35 | 01-MAY-07:01 | 10.37 |
June | 13457005.80 | 840.69 | 26-JUN-07:05 | 23.40 |
July | 25029829.51 | 1642.90 | 16-JUL-16:03 | 29.90 |
August | 22265065.87 | 1656.65 | 13-AUG-16:02 | 29.90 |
September | 15500782.57 | 850.99 | 02-SEP-07:04 | 21.70 |
October | 32424121.46 | 7884.19 | 29-OCT-08:62 | 6.88 |
November | 0.760245E+09 | 29670.76 | 24-NOV-08:61 | -3.5 |
December | 0.179178E+10 | 29669.27 | 22-DEC-08:61 | -4.1 |
Annual Sum or Average | 0.983550E+10 | |||
Minimum of Months | 13457005.80 | 840.69 | -12.6 | |
Maximum of Months | 0.302608E+10 | 29898.90 | 29.90 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.310205E+10 | 29790.53 | 02-JAN-08:12 | -10.9 |
February | 0.269222E+10 | 29715.59 | 06-FEB-08:12 | -12.6 |
March | 0.121636E+10 | 29559.84 | 14-MAR-07:01 | -1.4 |
April | 0.374814E+09 | 29550.67 | 03-APR-07:01 | 3.68 |
May | 47702388.22 | 26257.57 | 01-MAY-07:01 | 10.37 |
June | 13294986.10 | 832.93 | 26-JUN-07:05 | 23.40 |
July | 25043002.43 | 1644.36 | 16-JUL-16:03 | 29.90 |
August | 22465125.01 | 1657.72 | 13-AUG-16:02 | 29.90 |
September | 16514214.99 | 845.28 | 02-SEP-07:04 | 21.70 |
October | 33478880.24 | 10255.34 | 29-OCT-08:62 | 6.88 |
November | 0.800814E+09 | 29560.52 | 24-NOV-08:61 | -3.5 |
December | 0.186453E+10 | 29558.44 | 22-DEC-08:61 | -4.1 |
Annual Sum or Average | 0.102093E+11 | |||
Minimum of Months | 13294986.10 | 832.93 | -12.6 | |
Maximum of Months | 0.310205E+10 | 29790.53 | 29.90 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.350269E+10 | 29700.84 | 02-JAN-08:12 | -10.9 |
February | 0.309232E+10 | 29648.20 | 06-FEB-08:12 | -12.6 |
March | 0.150971E+10 | 29471.76 | 23-MAR-07:01 | -2.9 |
April | 0.513508E+09 | 29462.99 | 03-APR-07:01 | 3.68 |
May | 66628058.26 | 29207.14 | 01-MAY-07:01 | 10.37 |
June | 14060225.38 | 807.56 | 26-JUN-07:05 | 23.40 |
July | 25532533.69 | 1647.12 | 16-JUL-16:03 | 29.90 |
August | 22506584.16 | 1658.45 | 13-AUG-16:02 | 29.90 |
September | 19453229.45 | 830.73 | 02-SEP-07:04 | 21.70 |
October | 40266030.60 | 17332.35 | 29-OCT-08:62 | 6.88 |
November | 0.982658E+09 | 29472.58 | 24-NOV-08:61 | -3.5 |
December | 0.221540E+10 | 29469.60 | 22-DEC-08:61 | -4.1 |
Annual Sum or Average | 0.120047E+11 | |||
Minimum of Months | 14060225.38 | 807.56 | -12.6 | |
Maximum of Months | 0.350269E+10 | 29700.84 | 29.90 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.572822E+10 | 31758.38 | 02-JAN-08:12 | -10.9 |
February | 0.526273E+10 | 31777.89 | 06-FEB-08:12 | -12.6 |
March | 0.289657E+10 | 31447.71 | 22-MAR-07:01 | -2.7 |
April | 0.118162E+10 | 31406.92 | 03-APR-07:01 | 3.68 |
May | 0.170186E+09 | 31112.98 | 01-MAY-07:01 | 10.37 |
June | 22370651.29 | 796.36 | 20-JUN-07:04 | 23.17 |
July | 25704632.97 | 1641.82 | 16-JUL-16:03 | 29.90 |
August | 20032453.10 | 1646.94 | 13-AUG-16:02 | 29.90 |
September | 26222706.04 | 919.25 | 02-SEP-07:04 | 21.70 |
October | 94802587.36 | 30728.81 | 29-OCT-08:62 | 6.88 |
November | 0.177054E+10 | 31426.07 | 24-NOV-08:61 | -3.5 |
December | 0.382756E+10 | 31418.66 | 22-DEC-08:61 | -4.1 |
Annual Sum or Average | 0.210265E+11 | |||
Minimum of Months | 20032453.10 | 796.36 | -12.6 | |
Maximum of Months | 0.572822E+10 | 31777.89 | 29.90 |
Report: ZoneElectricSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.739462E+10 | 4621.63 | 01-JAN-10:09 | 0.222596E+10 | 1343.25 | 01-JAN-10:09 |
February | 0.668410E+10 | 4621.63 | 01-FEB-10:09 | 0.201408E+10 | 1343.25 | 01-FEB-10:09 |
March | 0.740180E+10 | 4621.63 | 01-MAR-10:09 | 0.223295E+10 | 1343.25 | 01-MAR-10:09 |
April | 0.716384E+10 | 4621.63 | 01-APR-09:09 | 0.215748E+10 | 1343.25 | 01-APR-09:09 |
May | 0.739462E+10 | 4621.63 | 01-MAY-09:09 | 0.222596E+10 | 1343.25 | 01-MAY-09:09 |
June | 0.716485E+10 | 4621.63 | 01-JUN-09:09 | 0.216232E+10 | 1343.25 | 01-JUN-09:09 |
July | 0.740069E+10 | 4621.63 | 01-JUL-09:09 | 0.222811E+10 | 1343.25 | 01-JUL-09:09 |
August | 0.739513E+10 | 4621.63 | 01-AUG-09:09 | 0.222838E+10 | 1343.25 | 01-AUG-09:09 |
September | 0.717041E+10 | 4621.63 | 01-SEP-09:09 | 0.216205E+10 | 1343.25 | 01-SEP-09:09 |
October | 0.739462E+10 | 4621.63 | 01-OCT-09:09 | 0.222596E+10 | 1343.25 | 01-OCT-09:09 |
November | 0.714323E+10 | 4621.63 | 01-NOV-09:09 | 0.215077E+10 | 1343.25 | 01-NOV-09:09 |
December | 0.740776E+10 | 4621.63 | 01-DEC-10:09 | 0.223509E+10 | 1343.25 | 01-DEC-10:09 |
Annual Sum or Average | 0.871157E+11 | 0.262491E+11 | ||||
Minimum of Months | 0.668410E+10 | 4621.63 | 0.201408E+10 | 1343.25 | ||
Maximum of Months | 0.740776E+10 | 4621.63 | 0.223509E+10 | 1343.25 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.451584E+10 | 2827.07 | 01-JAN-10:09 | 0.111298E+10 | 671.63 | 01-JAN-10:09 |
February | 0.408193E+10 | 2827.07 | 01-FEB-10:09 | 0.100704E+10 | 671.63 | 01-FEB-10:09 |
March | 0.452026E+10 | 2827.07 | 01-MAR-10:09 | 0.111647E+10 | 671.63 | 01-MAR-10:09 |
April | 0.437489E+10 | 2827.07 | 01-APR-09:09 | 0.107874E+10 | 671.63 | 01-APR-09:09 |
May | 0.451584E+10 | 2827.07 | 01-MAY-09:09 | 0.111298E+10 | 671.63 | 01-MAY-09:09 |
June | 0.437556E+10 | 2827.07 | 01-JUN-09:09 | 0.108116E+10 | 671.63 | 01-JUN-09:09 |
July | 0.451952E+10 | 2827.07 | 01-JUL-09:09 | 0.111405E+10 | 671.63 | 01-JUL-09:09 |
August | 0.451617E+10 | 2827.07 | 01-AUG-09:09 | 0.111419E+10 | 671.63 | 01-AUG-09:09 |
September | 0.437891E+10 | 2827.07 | 01-SEP-09:09 | 0.108102E+10 | 671.63 | 01-SEP-09:09 |
October | 0.451584E+10 | 2827.07 | 01-OCT-09:09 | 0.111298E+10 | 671.63 | 01-OCT-09:09 |
November | 0.436230E+10 | 2827.07 | 01-NOV-09:09 | 0.107538E+10 | 671.63 | 01-NOV-09:09 |
December | 0.452388E+10 | 2827.07 | 01-DEC-10:09 | 0.111755E+10 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.532009E+11 | 0.131245E+11 | ||||
Minimum of Months | 0.408193E+10 | 2827.07 | 0.100704E+10 | 671.63 | ||
Maximum of Months | 0.452388E+10 | 2827.07 | 0.111755E+10 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.317044E+10 | 2555.22 | 01-JAN-10:09 | 0.879849E+09 | 671.63 | 01-JAN-10:09 |
February | 0.287181E+10 | 2555.22 | 01-FEB-09:09 | 0.796766E+09 | 671.63 | 01-FEB-09:09 |
March | 0.324295E+10 | 2555.22 | 01-MAR-09:09 | 0.898128E+09 | 671.63 | 01-MAR-09:09 |
April | 0.307694E+10 | 2555.22 | 01-APR-08:09 | 0.853677E+09 | 671.63 | 01-APR-08:09 |
May | 0.320669E+10 | 2555.22 | 01-MAY-08:09 | 0.888989E+09 | 671.63 | 01-MAY-08:09 |
June | 0.313132E+10 | 2555.22 | 01-JUN-08:09 | 0.867387E+09 | 671.63 | 01-JUN-08:09 |
July | 0.315231E+10 | 2555.22 | 01-JUL-08:09 | 0.875279E+09 | 671.63 | 01-JUL-08:09 |
August | 0.324295E+10 | 2555.22 | 01-AUG-08:09 | 0.898128E+09 | 671.63 | 01-AUG-08:09 |
September | 0.307694E+10 | 2555.22 | 01-SEP-08:09 | 0.853677E+09 | 671.63 | 01-SEP-08:09 |
October | 0.317044E+10 | 2555.22 | 01-OCT-09:09 | 0.879849E+09 | 671.63 | 01-OCT-09:09 |
November | 0.307694E+10 | 2555.22 | 01-NOV-08:09 | 0.853679E+09 | 671.63 | 01-NOV-08:09 |
December | 0.315231E+10 | 2555.22 | 01-DEC-09:09 | 0.875279E+09 | 671.63 | 01-DEC-09:09 |
Annual Sum or Average | 0.375720E+11 | 0.104207E+11 | ||||
Minimum of Months | 0.287181E+10 | 2555.22 | 0.796766E+09 | 671.63 | ||
Maximum of Months | 0.324295E+10 | 2555.22 | 0.898128E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.317044E+10 | 2555.22 | 01-JAN-10:09 | 0.879849E+09 | 671.63 | 01-JAN-10:09 |
February | 0.287181E+10 | 2555.22 | 01-FEB-09:09 | 0.796766E+09 | 671.63 | 01-FEB-09:09 |
March | 0.324295E+10 | 2555.22 | 01-MAR-09:09 | 0.898128E+09 | 671.63 | 01-MAR-09:09 |
April | 0.307694E+10 | 2555.22 | 01-APR-08:09 | 0.853677E+09 | 671.63 | 01-APR-08:09 |
May | 0.320669E+10 | 2555.22 | 01-MAY-08:09 | 0.888989E+09 | 671.63 | 01-MAY-08:09 |
June | 0.313132E+10 | 2555.22 | 01-JUN-08:09 | 0.867387E+09 | 671.63 | 01-JUN-08:09 |
July | 0.315231E+10 | 2555.22 | 01-JUL-08:09 | 0.875279E+09 | 671.63 | 01-JUL-08:09 |
August | 0.324295E+10 | 2555.22 | 01-AUG-08:09 | 0.898128E+09 | 671.63 | 01-AUG-08:09 |
September | 0.307694E+10 | 2555.22 | 01-SEP-08:09 | 0.853677E+09 | 671.63 | 01-SEP-08:09 |
October | 0.317044E+10 | 2555.22 | 01-OCT-09:09 | 0.879849E+09 | 671.63 | 01-OCT-09:09 |
November | 0.307694E+10 | 2555.22 | 01-NOV-08:09 | 0.853679E+09 | 671.63 | 01-NOV-08:09 |
December | 0.315231E+10 | 2555.22 | 01-DEC-09:09 | 0.875279E+09 | 671.63 | 01-DEC-09:09 |
Annual Sum or Average | 0.375720E+11 | 0.104207E+11 | ||||
Minimum of Months | 0.287181E+10 | 2555.22 | 0.796766E+09 | 671.63 | ||
Maximum of Months | 0.324295E+10 | 2555.22 | 0.898128E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.317044E+10 | 2555.22 | 01-JAN-10:09 | 0.879849E+09 | 671.63 | 01-JAN-10:09 |
February | 0.287181E+10 | 2555.22 | 01-FEB-09:09 | 0.796766E+09 | 671.63 | 01-FEB-09:09 |
March | 0.324295E+10 | 2555.22 | 01-MAR-09:09 | 0.898128E+09 | 671.63 | 01-MAR-09:09 |
April | 0.307694E+10 | 2555.22 | 01-APR-08:09 | 0.853677E+09 | 671.63 | 01-APR-08:09 |
May | 0.320669E+10 | 2555.22 | 01-MAY-08:09 | 0.888989E+09 | 671.63 | 01-MAY-08:09 |
June | 0.313132E+10 | 2555.22 | 01-JUN-08:09 | 0.867387E+09 | 671.63 | 01-JUN-08:09 |
July | 0.315231E+10 | 2555.22 | 01-JUL-08:09 | 0.875279E+09 | 671.63 | 01-JUL-08:09 |
August | 0.324295E+10 | 2555.22 | 01-AUG-08:09 | 0.898128E+09 | 671.63 | 01-AUG-08:09 |
September | 0.307694E+10 | 2555.22 | 01-SEP-08:09 | 0.853677E+09 | 671.63 | 01-SEP-08:09 |
October | 0.317044E+10 | 2555.22 | 01-OCT-09:09 | 0.879849E+09 | 671.63 | 01-OCT-09:09 |
November | 0.307694E+10 | 2555.22 | 01-NOV-08:09 | 0.853679E+09 | 671.63 | 01-NOV-08:09 |
December | 0.315231E+10 | 2555.22 | 01-DEC-09:09 | 0.875279E+09 | 671.63 | 01-DEC-09:09 |
Annual Sum or Average | 0.375720E+11 | 0.104207E+11 | ||||
Minimum of Months | 0.287181E+10 | 2555.22 | 0.796766E+09 | 671.63 | ||
Maximum of Months | 0.324295E+10 | 2555.22 | 0.898128E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.313454E+10 | 2726.96 | 01-JAN-11:09 | 0.161799E+10 | 1343.25 | 01-JAN-11:09 |
February | 0.283982E+10 | 2726.96 | 01-FEB-10:09 | 0.146554E+10 | 1343.25 | 01-FEB-10:09 |
March | 0.321092E+10 | 2726.96 | 01-MAR-10:09 | 0.165455E+10 | 1343.25 | 01-MAR-10:09 |
April | 0.304266E+10 | 2726.96 | 01-APR-09:09 | 0.157022E+10 | 1343.25 | 01-APR-09:09 |
May | 0.317273E+10 | 2726.96 | 01-MAY-09:09 | 0.163627E+10 | 1343.25 | 01-MAY-09:09 |
June | 0.309995E+10 | 2726.96 | 01-JUN-09:09 | 0.159764E+10 | 1343.25 | 01-JUN-09:09 |
July | 0.311545E+10 | 2726.96 | 01-JUL-09:09 | 0.160885E+10 | 1343.25 | 01-JUL-09:09 |
August | 0.321092E+10 | 2726.96 | 01-AUG-09:09 | 0.165455E+10 | 1343.25 | 01-AUG-09:09 |
September | 0.304266E+10 | 2726.96 | 01-SEP-09:09 | 0.157022E+10 | 1343.25 | 01-SEP-09:09 |
October | 0.313454E+10 | 2726.96 | 01-OCT-10:09 | 0.161799E+10 | 1343.25 | 01-OCT-10:09 |
November | 0.304266E+10 | 2726.96 | 01-NOV-09:09 | 0.157022E+10 | 1343.25 | 01-NOV-09:09 |
December | 0.311545E+10 | 2726.96 | 01-DEC-10:09 | 0.160885E+10 | 1343.25 | 01-DEC-10:09 |
Annual Sum or Average | 0.371623E+11 | 0.191729E+11 | ||||
Minimum of Months | 0.283982E+10 | 2726.96 | 0.146554E+10 | 1343.25 | ||
Maximum of Months | 0.321092E+10 | 2726.96 | 0.165455E+10 | 1343.25 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.161274E+10 | 1404.46 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.146111E+10 | 1404.46 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.165211E+10 | 1404.46 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.156548E+10 | 1404.46 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.163243E+10 | 1404.46 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.159501E+10 | 1404.46 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.160290E+10 | 1404.46 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.165211E+10 | 1404.46 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.156548E+10 | 1404.46 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.161274E+10 | 1404.46 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.156548E+10 | 1404.46 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.160290E+10 | 1404.46 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.191205E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.146111E+10 | 1404.46 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.165211E+10 | 1404.46 | 0.827277E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.161274E+10 | 1404.46 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.146111E+10 | 1404.46 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.165211E+10 | 1404.46 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.156548E+10 | 1404.46 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.163243E+10 | 1404.46 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.159501E+10 | 1404.46 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.160290E+10 | 1404.46 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.165211E+10 | 1404.46 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.156548E+10 | 1404.46 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.161274E+10 | 1404.46 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.156548E+10 | 1404.46 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.160290E+10 | 1404.46 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.191205E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.146111E+10 | 1404.46 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.165211E+10 | 1404.46 | 0.827277E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.161274E+10 | 1404.46 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.146111E+10 | 1404.46 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.165211E+10 | 1404.46 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.156548E+10 | 1404.46 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.163243E+10 | 1404.46 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.159501E+10 | 1404.46 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.160290E+10 | 1404.46 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.165211E+10 | 1404.46 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.156548E+10 | 1404.46 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.161274E+10 | 1404.46 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.156548E+10 | 1404.46 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.160290E+10 | 1404.46 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.191205E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.146111E+10 | 1404.46 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.165211E+10 | 1404.46 | 0.827277E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.161274E+10 | 1404.46 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.146111E+10 | 1404.46 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.165211E+10 | 1404.46 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.156548E+10 | 1404.46 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.163243E+10 | 1404.46 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.159501E+10 | 1404.46 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.160290E+10 | 1404.46 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.165211E+10 | 1404.46 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.156548E+10 | 1404.46 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.161274E+10 | 1404.46 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.156548E+10 | 1404.46 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.160290E+10 | 1404.46 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.191205E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.146111E+10 | 1404.46 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.165211E+10 | 1404.46 | 0.827277E+09 | 671.63 |
Report: SpaceGainsMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.338624E+10 | 0.739462E+10 | 0.222596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.622022E+10 |
February | 0.305697E+10 | 0.668410E+10 | 0.201408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.578679E+10 |
March | 0.335708E+10 | 0.740180E+10 | 0.223295E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.453664E+10 |
April | 0.327081E+10 | 0.716384E+10 | 0.215748E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12838979.17 | 0.282721E+10 |
May | 0.336680E+10 | 0.739462E+10 | 0.222596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 69858084.30 | 0.162191E+10 |
June | 0.325380E+10 | 0.716485E+10 | 0.216232E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.350018E+09 | 0.518685E+09 |
July | 0.339353E+10 | 0.740069E+10 | 0.222811E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.831738E+09 | 86597240.18 |
August | 0.334857E+10 | 0.739513E+10 | 0.222838E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.917265E+09 | 0.145432E+09 |
September | 0.327932E+10 | 0.717041E+10 | 0.216205E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163308E+09 | 0.790027E+09 |
October | 0.338624E+10 | 0.739462E+10 | 0.222596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2988480.44 | 0.219001E+10 |
November | 0.327446E+10 | 0.714323E+10 | 0.215077E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.400288E+10 |
December | 0.340325E+10 | 0.740776E+10 | 0.223509E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.540314E+10 |
Annual Sum or Average | 0.397770E+11 | 0.871157E+11 | 0.262491E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.234801E+10 | 0.341295E+11 |
Minimum of Months | 0.305697E+10 | 0.668410E+10 | 0.201408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86597240.18 |
Maximum of Months | 0.340325E+10 | 0.740776E+10 | 0.223509E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.917265E+09 | 0.622022E+10 |
Report: SpaceGainsMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.169307E+10 | 0.451584E+10 | 0.111298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.298497E+10 |
February | 0.152844E+10 | 0.408193E+10 | 0.100704E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.280341E+10 |
March | 0.167849E+10 | 0.452026E+10 | 0.111647E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.220819E+10 |
April | 0.163536E+10 | 0.437489E+10 | 0.107874E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6913240.51 | 0.138334E+10 |
May | 0.168335E+10 | 0.451584E+10 | 0.111298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37810996.23 | 0.807756E+09 |
June | 0.162685E+10 | 0.437556E+10 | 0.108116E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187096E+09 | 0.221679E+09 |
July | 0.169671E+10 | 0.451952E+10 | 0.111405E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.446089E+09 | 29439309.45 |
August | 0.167424E+10 | 0.451617E+10 | 0.111419E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.490794E+09 | 49751855.92 |
September | 0.163961E+10 | 0.437891E+10 | 0.108102E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 88057186.29 | 0.362711E+09 |
October | 0.169307E+10 | 0.451584E+10 | 0.111298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1612056.41 | 0.106744E+10 |
November | 0.163718E+10 | 0.436230E+10 | 0.107538E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.194362E+10 |
December | 0.170157E+10 | 0.452388E+10 | 0.111755E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.261084E+10 |
Annual Sum or Average | 0.198880E+11 | 0.532009E+11 | 0.131245E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125837E+10 | 0.164731E+11 |
Minimum of Months | 0.152844E+10 | 0.408193E+10 | 0.100704E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29439309.45 |
Maximum of Months | 0.170157E+10 | 0.452388E+10 | 0.111755E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.490794E+09 | 0.298497E+10 |
Report: SpaceGainsMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.317044E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.308507E+10 |
February | 0.914877E+09 | 0.287181E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.288570E+10 |
March | 0.103395E+10 | 0.324295E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.226884E+10 |
April | 0.984131E+09 | 0.307694E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6913300.35 | 0.141152E+10 |
May | 0.102058E+10 | 0.320669E+10 | 0.888989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 37631925.90 | 0.826172E+09 |
June | 0.998711E+09 | 0.313132E+10 | 0.867387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185001E+09 | 0.249822E+09 |
July | 0.100600E+10 | 0.315231E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.437511E+09 | 46243618.20 |
August | 0.103395E+10 | 0.324295E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.485513E+09 | 64229994.57 |
September | 0.984131E+09 | 0.307694E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 86923972.79 | 0.389360E+09 |
October | 0.100722E+10 | 0.317044E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1612251.50 | 0.110507E+10 |
November | 0.973196E+09 | 0.307694E+10 | 0.853679E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.200084E+10 |
December | 0.100600E+10 | 0.315231E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.270483E+10 |
Annual Sum or Average | 0.119700E+11 | 0.375720E+11 | 0.104207E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124111E+10 | 0.170377E+11 |
Minimum of Months | 0.914877E+09 | 0.287181E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46243618.20 |
Maximum of Months | 0.103395E+10 | 0.324295E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.485513E+09 | 0.308507E+10 |
Report: SpaceGainsMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.317044E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.307741E+10 |
February | 0.914877E+09 | 0.287181E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.288031E+10 |
March | 0.103395E+10 | 0.324295E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.226066E+10 |
April | 0.984131E+09 | 0.307694E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6913314.74 | 0.140233E+10 |
May | 0.102058E+10 | 0.320669E+10 | 0.888989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 37632115.65 | 0.815962E+09 |
June | 0.998711E+09 | 0.313132E+10 | 0.867387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.184992E+09 | 0.249476E+09 |
July | 0.100600E+10 | 0.315231E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.437436E+09 | 46490345.40 |
August | 0.103395E+10 | 0.324295E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.485413E+09 | 64611002.07 |
September | 0.984131E+09 | 0.307694E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 86923617.37 | 0.389014E+09 |
October | 0.100722E+10 | 0.317044E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1612327.83 | 0.109774E+10 |
November | 0.973196E+09 | 0.307694E+10 | 0.853679E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.198698E+10 |
December | 0.100600E+10 | 0.315231E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.269841E+10 |
Annual Sum or Average | 0.119700E+11 | 0.375720E+11 | 0.104207E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124092E+10 | 0.169694E+11 |
Minimum of Months | 0.914877E+09 | 0.287181E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46490345.40 |
Maximum of Months | 0.103395E+10 | 0.324295E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.485413E+09 | 0.307741E+10 |
Report: SpaceGainsMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.317044E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.307107E+10 |
February | 0.914877E+09 | 0.287181E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.287577E+10 |
March | 0.103395E+10 | 0.324295E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.225207E+10 |
April | 0.984131E+09 | 0.307694E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6913481.45 | 0.138967E+10 |
May | 0.102058E+10 | 0.320669E+10 | 0.888989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 37632764.00 | 0.798725E+09 |
June | 0.998711E+09 | 0.313132E+10 | 0.867387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185077E+09 | 0.247041E+09 |
July | 0.100600E+10 | 0.315231E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.437739E+09 | 44519138.78 |
August | 0.103395E+10 | 0.324295E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.485728E+09 | 62840180.47 |
September | 0.984131E+09 | 0.307694E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 86934027.81 | 0.386695E+09 |
October | 0.100722E+10 | 0.317044E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1612600.97 | 0.108589E+10 |
November | 0.973196E+09 | 0.307694E+10 | 0.853679E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.197083E+10 |
December | 0.100600E+10 | 0.315231E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.269281E+10 |
Annual Sum or Average | 0.119700E+11 | 0.375720E+11 | 0.104207E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124164E+10 | 0.168779E+11 |
Minimum of Months | 0.914877E+09 | 0.287181E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44519138.78 |
Maximum of Months | 0.103395E+10 | 0.324295E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.485728E+09 | 0.307107E+10 |
Report: SpaceGainsMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.344359E+10 | 0.313454E+10 | 0.161799E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.566252E+10 |
February | 0.313522E+10 | 0.283982E+10 | 0.146554E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.530432E+10 |
March | 0.355148E+10 | 0.321092E+10 | 0.165455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.414775E+10 |
April | 0.338259E+10 | 0.304266E+10 | 0.157022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12450267.05 | 0.253967E+10 |
May | 0.349753E+10 | 0.317273E+10 | 0.163627E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 67735921.35 | 0.143625E+10 |
June | 0.343071E+10 | 0.309995E+10 | 0.159764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.334608E+09 | 0.463884E+09 |
July | 0.344942E+10 | 0.311545E+10 | 0.160885E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.790501E+09 | 83187915.90 |
August | 0.355148E+10 | 0.321092E+10 | 0.165455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.878328E+09 | 0.121398E+09 |
September | 0.338259E+10 | 0.304266E+10 | 0.157022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156765E+09 | 0.719437E+09 |
October | 0.344359E+10 | 0.313454E+10 | 0.161799E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2904781.33 | 0.198370E+10 |
November | 0.331698E+10 | 0.304266E+10 | 0.157022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.361715E+10 |
December | 0.344942E+10 | 0.311545E+10 | 0.160885E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.496536E+10 |
Annual Sum or Average | 0.410346E+11 | 0.371623E+11 | 0.191729E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.224329E+10 | 0.310446E+11 |
Minimum of Months | 0.313522E+10 | 0.283982E+10 | 0.146554E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83187915.90 |
Maximum of Months | 0.355148E+10 | 0.321092E+10 | 0.165455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.878328E+09 | 0.566252E+10 |
Report: SpaceGainsMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.161274E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.308378E+10 |
February | 0.156756E+10 | 0.146111E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.289238E+10 |
March | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.225785E+10 |
April | 0.169125E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6913952.64 | 0.137650E+10 |
May | 0.174872E+10 | 0.163243E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 37639083.80 | 0.772925E+09 |
June | 0.171530E+10 | 0.159501E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185659E+09 | 0.245918E+09 |
July | 0.172466E+10 | 0.160290E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.439071E+09 | 41441950.74 |
August | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.487589E+09 | 61329583.57 |
September | 0.169125E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 87079883.44 | 0.387427E+09 |
October | 0.172174E+10 | 0.161274E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1613476.35 | 0.107200E+10 |
November | 0.165844E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.196188E+10 |
December | 0.172466E+10 | 0.160290E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.270390E+10 |
Annual Sum or Average | 0.205167E+11 | 0.191205E+11 | 0.958644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124556E+10 | 0.168573E+11 |
Minimum of Months | 0.156756E+10 | 0.146111E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41441950.74 |
Maximum of Months | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.487589E+09 | 0.308378E+10 |
Report: SpaceGainsMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.161274E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.308225E+10 |
February | 0.156756E+10 | 0.146111E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.289086E+10 |
March | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.225527E+10 |
April | 0.169125E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6913979.85 | 0.137129E+10 |
May | 0.174872E+10 | 0.163243E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 37639579.56 | 0.764867E+09 |
June | 0.171530E+10 | 0.159501E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185687E+09 | 0.245077E+09 |
July | 0.172466E+10 | 0.160290E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.439192E+09 | 40913399.88 |
August | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.487694E+09 | 60876469.92 |
September | 0.169125E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 87084316.63 | 0.386497E+09 |
October | 0.172174E+10 | 0.161274E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1613572.23 | 0.106637E+10 |
November | 0.165844E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.195762E+10 |
December | 0.172466E+10 | 0.160290E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.270210E+10 |
Annual Sum or Average | 0.205167E+11 | 0.191205E+11 | 0.958644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124582E+10 | 0.168240E+11 |
Minimum of Months | 0.156756E+10 | 0.146111E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40913399.88 |
Maximum of Months | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.487694E+09 | 0.308225E+10 |
Report: SpaceGainsMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.161274E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.307373E+10 |
February | 0.156756E+10 | 0.146111E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.288336E+10 |
March | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.224565E+10 |
April | 0.169125E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6914722.13 | 0.135684E+10 |
May | 0.174872E+10 | 0.163243E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 37641198.09 | 0.744252E+09 |
June | 0.171530E+10 | 0.159501E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185766E+09 | 0.242073E+09 |
July | 0.172466E+10 | 0.160290E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.439477E+09 | 39267784.15 |
August | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.487927E+09 | 59637999.92 |
September | 0.169125E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 87092755.43 | 0.383333E+09 |
October | 0.172174E+10 | 0.161274E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1613668.71 | 0.105176E+10 |
November | 0.165844E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.194588E+10 |
December | 0.172466E+10 | 0.160290E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.269378E+10 |
Annual Sum or Average | 0.205167E+11 | 0.191205E+11 | 0.958644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124643E+10 | 0.167196E+11 |
Minimum of Months | 0.156756E+10 | 0.146111E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39267784.15 |
Maximum of Months | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.487927E+09 | 0.307373E+10 |
Report: SpaceGainsMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.161274E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.395404E+10 |
February | 0.156756E+10 | 0.146111E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.366147E+10 |
March | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.285193E+10 |
April | 0.169125E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7307610.02 | 0.173010E+10 |
May | 0.174872E+10 | 0.163243E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 39457108.05 | 0.931487E+09 |
June | 0.171530E+10 | 0.159501E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.199380E+09 | 0.361996E+09 |
July | 0.172466E+10 | 0.160290E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.467387E+09 | 76348768.51 |
August | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.522155E+09 | 0.117976E+09 |
September | 0.169125E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 91815658.21 | 0.524691E+09 |
October | 0.172174E+10 | 0.161274E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1699520.32 | 0.137714E+10 |
November | 0.165844E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.253578E+10 |
December | 0.172466E+10 | 0.160290E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.344236E+10 |
Annual Sum or Average | 0.205167E+11 | 0.191205E+11 | 0.958644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132920E+10 | 0.215653E+11 |
Minimum of Months | 0.156756E+10 | 0.146111E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76348768.51 |
Maximum of Months | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.522155E+09 | 0.395404E+10 |
Report: PeakSpaceGainsMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 4050.04 | 01-JAN-13:09 | 4621.63 | 01-JAN-10:09 | 1343.25 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 10094.55 | 14-JAN-12:10 |
February | 4050.04 | 03-FEB-13:09 | 4621.63 | 01-FEB-10:09 | 1343.25 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 10603.06 | 06-FEB-12:10 |
March | 4050.04 | 03-MAR-13:09 | 4621.63 | 01-MAR-10:09 | 1343.25 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 7447.13 | 17-MAR-11:10 |
April | 4050.04 | 01-APR-12:09 | 4621.63 | 01-APR-09:09 | 1343.25 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 852.12 | 07-APR-13:00 | 5351.90 | 01-APR-12:00 |
May | 4050.04 | 05-MAY-12:09 | 4621.63 | 01-MAY-09:09 | 1343.25 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1833.64 | 30-MAY-13:00 | 3202.86 | 14-MAY-16:40 |
June | 4050.04 | 02-JUN-12:09 | 4621.63 | 01-JUN-09:09 | 1343.25 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3739.48 | 19-JUN-12:00 | 1780.40 | 03-JUN-17:00 |
July | 4050.04 | 01-JUL-12:09 | 4621.63 | 01-JUL-09:09 | 1343.25 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2906.84 | 07-JUL-12:00 | 517.63 | 23-JUL-17:00 |
August | 4050.04 | 04-AUG-12:09 | 4621.63 | 01-AUG-09:09 | 1343.25 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3038.30 | 24-AUG-15:00 | 859.38 | 06-AUG-12:00 |
September | 4050.04 | 01-SEP-12:09 | 4621.63 | 01-SEP-09:09 | 1343.25 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2113.58 | 01-SEP-14:00 | 2633.92 | 23-SEP-11:10 |
October | 4050.04 | 01-OCT-12:09 | 4621.63 | 01-OCT-09:09 | 1343.25 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 334.90 | 04-OCT-13:00 | 4098.19 | 27-OCT-17:00 |
November | 4050.04 | 03-NOV-12:09 | 4621.63 | 01-NOV-09:09 | 1343.25 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 7248.14 | 22-NOV-18:00 |
December | 4050.04 | 01-DEC-13:09 | 4621.63 | 01-DEC-10:09 | 1343.25 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 9103.48 | 31-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 4050.04 | 4621.63 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 517.63 | |||||
Maximum of Months | 4050.04 | 4621.63 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 3739.48 | 10603.06 |
Report: PeakSpaceGainsMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 01-JAN-13:09 | 2827.07 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 5364.18 | 14-JAN-12:10 |
February | 2024.96 | 03-FEB-13:09 | 2827.07 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 5685.15 | 06-FEB-12:10 |
March | 2024.96 | 03-MAR-13:09 | 2827.07 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 4032.88 | 17-MAR-11:10 |
April | 2024.96 | 01-APR-12:09 | 2827.07 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 461.10 | 07-APR-13:00 | 2939.06 | 01-APR-12:00 |
May | 2024.96 | 05-MAY-12:09 | 2827.07 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 996.88 | 30-MAY-13:00 | 1804.52 | 14-MAY-16:30 |
June | 2024.96 | 02-JUN-12:09 | 2827.07 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2032.99 | 19-JUN-12:00 | 956.78 | 03-JUN-17:00 |
July | 2024.96 | 01-JUL-12:09 | 2827.07 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1592.45 | 07-JUL-12:00 | 282.21 | 23-JUL-17:00 |
August | 2024.96 | 04-AUG-12:09 | 2827.07 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1624.72 | 24-AUG-15:00 | 467.21 | 06-AUG-12:00 |
September | 2024.96 | 01-SEP-12:09 | 2827.07 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1152.34 | 01-SEP-14:00 | 1486.55 | 23-SEP-11:10 |
October | 2024.96 | 01-OCT-12:09 | 2827.07 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 182.09 | 04-OCT-13:00 | 2346.51 | 08-OCT-11:10 |
November | 2024.96 | 03-NOV-12:09 | 2827.07 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3875.85 | 22-NOV-18:00 |
December | 2024.96 | 01-DEC-13:09 | 2827.07 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 4881.11 | 31-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 2827.07 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 282.21 | |||||
Maximum of Months | 2024.96 | 2827.07 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 2032.99 | 5685.15 |
Report: PeakSpaceGainsMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 2555.22 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 5364.18 | 14-JAN-12:10 |
February | 2024.96 | 04-FEB-13:09 | 2555.22 | 01-FEB-09:09 | 671.63 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 5685.15 | 06-FEB-12:10 |
March | 2024.96 | 04-MAR-13:09 | 2555.22 | 01-MAR-09:09 | 671.63 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 4032.88 | 17-MAR-11:10 |
April | 2024.96 | 01-APR-12:09 | 2555.22 | 01-APR-08:09 | 671.63 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 461.11 | 07-APR-13:00 | 2939.06 | 01-APR-12:00 |
May | 2024.96 | 06-MAY-12:09 | 2555.22 | 01-MAY-08:09 | 671.63 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 996.88 | 30-MAY-13:00 | 1730.15 | 14-MAY-16:00 |
June | 2024.96 | 03-JUN-12:09 | 2555.22 | 01-JUN-08:09 | 671.63 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2032.99 | 19-JUN-12:00 | 956.72 | 03-JUN-17:00 |
July | 2024.96 | 01-JUL-12:09 | 2555.22 | 01-JUL-08:09 | 671.63 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1592.45 | 07-JUL-12:00 | 534.81 | 23-JUL-17:00 |
August | 2024.96 | 05-AUG-12:09 | 2555.22 | 01-AUG-08:09 | 671.63 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1624.77 | 24-AUG-15:00 | 703.94 | 06-AUG-17:00 |
September | 2024.96 | 02-SEP-12:09 | 2555.22 | 01-SEP-08:09 | 671.63 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1152.34 | 01-SEP-14:00 | 1495.17 | 23-SEP-11:10 |
October | 2024.96 | 07-OCT-12:09 | 2555.22 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 182.08 | 04-OCT-13:00 | 2323.86 | 28-OCT-11:10 |
November | 2024.96 | 04-NOV-12:09 | 2555.22 | 01-NOV-08:09 | 671.63 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3875.85 | 22-NOV-18:00 |
December | 2024.96 | 02-DEC-13:09 | 2555.22 | 01-DEC-09:09 | 671.63 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 4881.11 | 31-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 2555.22 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 534.81 | |||||
Maximum of Months | 2024.96 | 2555.22 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 2032.99 | 5685.15 |
Report: PeakSpaceGainsMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 2555.22 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 5364.18 | 14-JAN-12:10 |
February | 2024.96 | 04-FEB-13:09 | 2555.22 | 01-FEB-09:09 | 671.63 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 5685.15 | 06-FEB-12:10 |
March | 2024.96 | 04-MAR-13:09 | 2555.22 | 01-MAR-09:09 | 671.63 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 4032.88 | 17-MAR-11:10 |
April | 2024.96 | 01-APR-12:09 | 2555.22 | 01-APR-08:09 | 671.63 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 461.11 | 07-APR-13:00 | 2939.06 | 01-APR-12:00 |
May | 2024.96 | 06-MAY-12:09 | 2555.22 | 01-MAY-08:09 | 671.63 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 996.87 | 30-MAY-13:00 | 1713.23 | 11-MAY-17:00 |
June | 2024.96 | 03-JUN-12:09 | 2555.22 | 01-JUN-08:09 | 671.63 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2032.99 | 19-JUN-12:00 | 956.72 | 03-JUN-17:00 |
July | 2024.96 | 01-JUL-12:09 | 2555.22 | 01-JUL-08:09 | 671.63 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1592.45 | 07-JUL-12:00 | 534.58 | 23-JUL-17:00 |
August | 2024.96 | 05-AUG-12:09 | 2555.22 | 01-AUG-08:09 | 671.63 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1624.78 | 24-AUG-15:00 | 704.56 | 06-AUG-17:00 |
September | 2024.96 | 02-SEP-12:09 | 2555.22 | 01-SEP-08:09 | 671.63 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1152.33 | 01-SEP-14:00 | 1494.31 | 23-SEP-11:10 |
October | 2024.96 | 07-OCT-12:09 | 2555.22 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 182.08 | 04-OCT-13:00 | 2306.42 | 28-OCT-11:10 |
November | 2024.96 | 04-NOV-12:09 | 2555.22 | 01-NOV-08:09 | 671.63 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3875.85 | 22-NOV-18:00 |
December | 2024.96 | 02-DEC-13:09 | 2555.22 | 01-DEC-09:09 | 671.63 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 4881.11 | 31-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 2555.22 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 534.58 | |||||
Maximum of Months | 2024.96 | 2555.22 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 2032.99 | 5685.15 |
Report: PeakSpaceGainsMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 2555.22 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 5364.18 | 14-JAN-12:10 |
February | 2024.96 | 04-FEB-13:09 | 2555.22 | 01-FEB-09:09 | 671.63 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 5685.15 | 06-FEB-12:10 |
March | 2024.96 | 04-MAR-13:09 | 2555.22 | 01-MAR-09:09 | 671.63 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 4032.88 | 17-MAR-11:10 |
April | 2024.96 | 01-APR-12:09 | 2555.22 | 01-APR-08:09 | 671.63 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 461.11 | 07-APR-13:00 | 2939.06 | 01-APR-12:00 |
May | 2024.96 | 06-MAY-12:09 | 2555.22 | 01-MAY-08:09 | 671.63 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 996.87 | 30-MAY-13:00 | 1679.96 | 11-MAY-17:00 |
June | 2024.96 | 03-JUN-12:09 | 2555.22 | 01-JUN-08:09 | 671.63 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2032.99 | 19-JUN-12:00 | 956.71 | 03-JUN-17:00 |
July | 2024.96 | 01-JUL-12:09 | 2555.22 | 01-JUL-08:09 | 671.63 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1592.45 | 07-JUL-12:00 | 524.35 | 23-JUL-17:00 |
August | 2024.96 | 05-AUG-12:09 | 2555.22 | 01-AUG-08:09 | 671.63 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1624.79 | 24-AUG-15:00 | 694.49 | 06-AUG-17:00 |
September | 2024.96 | 02-SEP-12:09 | 2555.22 | 01-SEP-08:09 | 671.63 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1152.33 | 01-SEP-14:00 | 1487.65 | 23-SEP-11:10 |
October | 2024.96 | 07-OCT-12:09 | 2555.22 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 182.07 | 04-OCT-13:00 | 2274.26 | 28-OCT-11:10 |
November | 2024.96 | 04-NOV-12:09 | 2555.22 | 01-NOV-08:09 | 671.63 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3875.85 | 22-NOV-18:00 |
December | 2024.96 | 02-DEC-13:09 | 2555.22 | 01-DEC-09:09 | 671.63 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 4881.11 | 31-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 2555.22 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 524.35 | |||||
Maximum of Months | 2024.96 | 2555.22 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 2032.99 | 5685.15 |
Report: PeakSpaceGainsMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 5400.05 | 07-JAN-15:09 | 2726.96 | 01-JAN-11:09 | 1343.25 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 9675.69 | 14-JAN-12:10 |
February | 5400.05 | 04-FEB-15:09 | 2726.96 | 01-FEB-10:09 | 1343.25 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 10243.06 | 06-FEB-12:10 |
March | 5400.05 | 04-MAR-15:09 | 2726.96 | 01-MAR-10:09 | 1343.25 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 7257.11 | 17-MAR-11:10 |
April | 5400.05 | 01-APR-14:09 | 2726.96 | 01-APR-09:09 | 1343.25 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 829.80 | 07-APR-13:00 | 5279.65 | 01-APR-12:00 |
May | 5400.05 | 06-MAY-14:09 | 2726.96 | 01-MAY-09:09 | 1343.25 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1792.97 | 30-MAY-13:00 | 2895.20 | 13-MAY-16:00 |
June | 5400.05 | 03-JUN-14:09 | 2726.96 | 01-JUN-09:09 | 1343.25 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3656.56 | 19-JUN-12:00 | 1723.20 | 03-JUN-17:00 |
July | 5400.05 | 01-JUL-14:09 | 2726.96 | 01-JUL-09:09 | 1343.25 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2861.50 | 07-JUL-12:00 | 886.19 | 23-JUL-17:00 |
August | 5400.05 | 05-AUG-14:09 | 2726.96 | 01-AUG-09:09 | 1343.25 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2928.18 | 24-AUG-15:00 | 1189.80 | 06-AUG-17:00 |
September | 5400.05 | 02-SEP-14:09 | 2726.96 | 01-SEP-09:09 | 1343.25 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2071.86 | 01-SEP-14:00 | 2649.13 | 23-SEP-11:10 |
October | 5400.05 | 07-OCT-14:09 | 2726.96 | 01-OCT-10:09 | 1343.25 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 327.47 | 04-OCT-13:00 | 4010.18 | 28-OCT-11:10 |
November | 5400.05 | 04-NOV-14:09 | 2726.96 | 01-NOV-09:09 | 1343.25 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 6985.57 | 22-NOV-18:00 |
December | 5400.05 | 02-DEC-15:09 | 2726.96 | 01-DEC-10:09 | 1343.25 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 8794.39 | 31-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 5400.05 | 2726.96 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 886.19 | |||||
Maximum of Months | 5400.05 | 2726.96 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 3656.56 | 10243.06 |
Report: PeakSpaceGainsMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1404.46 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 5364.18 | 14-JAN-12:10 |
February | 2699.95 | 04-FEB-15:09 | 1404.46 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 5685.15 | 06-FEB-12:10 |
March | 2699.95 | 04-MAR-15:09 | 1404.46 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 4032.88 | 17-MAR-11:10 |
April | 2699.95 | 01-APR-14:09 | 1404.46 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 461.09 | 07-APR-13:00 | 2939.06 | 01-APR-12:00 |
May | 2699.95 | 06-MAY-14:09 | 1404.46 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 996.87 | 30-MAY-13:00 | 1597.57 | 13-MAY-16:00 |
June | 2699.95 | 03-JUN-14:09 | 1404.46 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2032.99 | 19-JUN-12:00 | 956.70 | 03-JUN-17:00 |
July | 2699.95 | 01-JUL-14:09 | 1404.46 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1592.45 | 07-JUL-12:00 | 484.51 | 23-JUL-17:00 |
August | 2699.95 | 05-AUG-14:09 | 1404.46 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1624.65 | 24-AUG-15:00 | 651.59 | 06-AUG-17:00 |
September | 2699.95 | 02-SEP-14:09 | 1404.46 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1152.33 | 01-SEP-14:00 | 1468.47 | 23-SEP-11:10 |
October | 2699.95 | 07-OCT-14:09 | 1404.46 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 182.07 | 04-OCT-13:00 | 2221.00 | 28-OCT-11:10 |
November | 2699.95 | 04-NOV-14:09 | 1404.46 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3875.85 | 22-NOV-18:00 |
December | 2699.95 | 02-DEC-15:09 | 1404.46 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 4881.11 | 31-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 484.51 | |||||
Maximum of Months | 2699.95 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 2032.99 | 5685.15 |
Report: PeakSpaceGainsMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1404.46 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 5364.18 | 14-JAN-12:10 |
February | 2699.95 | 04-FEB-15:09 | 1404.46 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 5685.15 | 06-FEB-12:10 |
March | 2699.95 | 04-MAR-15:09 | 1404.46 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 4032.88 | 17-MAR-11:10 |
April | 2699.95 | 01-APR-14:09 | 1404.46 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 461.09 | 07-APR-13:00 | 2939.06 | 01-APR-12:00 |
May | 2699.95 | 06-MAY-14:09 | 1404.46 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 996.86 | 30-MAY-13:00 | 1581.08 | 13-MAY-16:00 |
June | 2699.95 | 03-JUN-14:09 | 1404.46 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2032.99 | 19-JUN-12:00 | 956.70 | 03-JUN-17:00 |
July | 2699.95 | 01-JUL-14:09 | 1404.46 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1592.45 | 07-JUL-12:00 | 481.31 | 23-JUL-17:00 |
August | 2699.95 | 05-AUG-14:09 | 1404.46 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1624.65 | 24-AUG-15:00 | 648.39 | 06-AUG-17:00 |
September | 2699.95 | 02-SEP-14:09 | 1404.46 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1152.33 | 01-SEP-14:00 | 1462.08 | 23-SEP-11:10 |
October | 2699.95 | 07-OCT-14:09 | 1404.46 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 182.09 | 04-OCT-13:00 | 2208.47 | 28-OCT-11:10 |
November | 2699.95 | 04-NOV-14:09 | 1404.46 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3875.85 | 22-NOV-18:00 |
December | 2699.95 | 02-DEC-15:09 | 1404.46 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 4881.11 | 31-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 481.31 | |||||
Maximum of Months | 2699.95 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 2032.99 | 5685.15 |
Report: PeakSpaceGainsMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1404.46 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 5364.18 | 14-JAN-12:10 |
February | 2699.95 | 04-FEB-15:09 | 1404.46 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 5685.15 | 06-FEB-12:10 |
March | 2699.95 | 04-MAR-15:09 | 1404.46 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 4032.88 | 17-MAR-11:10 |
April | 2699.95 | 01-APR-14:09 | 1404.46 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 461.09 | 07-APR-13:00 | 2939.06 | 01-APR-12:00 |
May | 2699.95 | 06-MAY-14:09 | 1404.46 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 996.86 | 30-MAY-13:00 | 1543.00 | 13-MAY-16:00 |
June | 2699.95 | 03-JUN-14:09 | 1404.46 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2032.99 | 19-JUN-12:00 | 956.70 | 03-JUN-17:00 |
July | 2699.95 | 01-JUL-14:09 | 1404.46 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1592.45 | 07-JUL-12:00 | 472.63 | 23-JUL-17:00 |
August | 2699.95 | 05-AUG-14:09 | 1404.46 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1624.65 | 24-AUG-15:00 | 642.71 | 06-AUG-17:00 |
September | 2699.95 | 02-SEP-14:09 | 1404.46 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1152.33 | 01-SEP-14:00 | 1440.84 | 23-SEP-11:10 |
October | 2699.95 | 07-OCT-14:09 | 1404.46 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 182.23 | 04-OCT-13:00 | 2176.74 | 28-OCT-11:10 |
November | 2699.95 | 04-NOV-14:09 | 1404.46 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3875.85 | 22-NOV-18:00 |
December | 2699.95 | 02-DEC-15:09 | 1404.46 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 4881.11 | 31-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 472.63 | |||||
Maximum of Months | 2699.95 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 2032.99 | 5685.15 |
Report: PeakSpaceGainsMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1404.46 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 5783.04 | 14-JAN-12:10 |
February | 2699.95 | 04-FEB-15:09 | 1404.46 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 6045.15 | 06-FEB-12:10 |
March | 2699.95 | 04-MAR-15:09 | 1404.46 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 4222.90 | 17-MAR-11:10 |
April | 2699.95 | 01-APR-14:09 | 1404.46 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 483.40 | 07-APR-13:00 | 3011.31 | 01-APR-12:00 |
May | 2699.95 | 06-MAY-14:09 | 1404.46 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1037.52 | 30-MAY-13:00 | 1567.28 | 11-MAY-17:00 |
June | 2699.95 | 03-JUN-14:09 | 1404.46 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2115.91 | 19-JUN-12:00 | 1013.75 | 03-JUN-17:00 |
July | 2699.95 | 01-JUL-14:09 | 1404.46 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1637.80 | 07-JUL-12:00 | 469.50 | 23-JUL-17:00 |
August | 2699.95 | 05-AUG-14:09 | 1404.46 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1734.72 | 24-AUG-15:00 | 666.68 | 06-AUG-17:00 |
September | 2699.95 | 02-SEP-14:09 | 1404.46 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1194.04 | 01-SEP-14:00 | 1421.14 | 23-SEP-11:10 |
October | 2699.95 | 07-OCT-14:09 | 1404.46 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 189.66 | 04-OCT-13:00 | 2295.96 | 28-OCT-11:10 |
November | 2699.95 | 04-NOV-14:09 | 1404.46 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 4138.42 | 22-NOV-18:00 |
December | 2699.95 | 02-DEC-15:09 | 1404.46 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 5190.19 | 31-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 469.50 | |||||
Maximum of Months | 2699.95 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 2115.91 | 6045.15 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 11385.25 | 06-JAN-00:02 | 1687.52 | 1216.15 | 3731.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.50 |
February | 11356.91 | 03-FEB-00:02 | 1687.52 | 1216.15 | 3731.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 474.22 |
March | 9974.44 | 17-MAR-23:03 | 1350.01 | 9729.72 | 2985.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 237.12 |
April | 7344.51 | 08-APR-13:00 | 4050.04 | 4621.63 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 336.41 |
May | 11655.86 | 30-MAY-14:00 | 2700.03 | 4621.63 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 1646.36 | 0.00 |
June | 29498.54 | 20-JUN-07:02 | 1687.52 | 375.00 | 373.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.69 |
July | 35816.57 | 11-JUL-07:02 | 1687.52 | 375.00 | 373.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.46 |
August | 31101.62 | 22-AUG-07:02 | 2025.02 | 450.00 | 447.75 | 0.00 | 0.00 | 0.00 | 0.00 | 72.32 | 0.00 |
September | 36336.94 | 02-SEP-07:02 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 148.08 |
October | 13300.18 | 06-OCT-07:03 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 245.53 |
November | 10795.75 | 24-NOV-00:02 | 1687.52 | 1216.15 | 3731.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 591.67 |
December | 10831.85 | 22-DEC-00:02 | 1687.52 | 1216.15 | 3731.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 252.33 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 7344.51 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 36336.94 | 4050.04 | 9729.72 | 3731.25 | 0.00 | 0.00 | 0.00 | 0.00 | 1646.36 | 591.67 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2414.83 | 19-JAN-18:10 | 1687.47 | 2827.07 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 412.29 |
February | 6552.84 | 12-FEB-10:52 | 1687.47 | 14135.34 | 3358.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 891.30 |
March | 4357.61 | 19-MAR-09:23 | 1349.97 | 11308.27 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 586.30 |
April | 14546.67 | 16-APR-17:09 | 16199.69 | 22616.54 | 5373.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.41 |
May | 16814.76 | 27-MAY-22:03 | 4724.91 | 19789.47 | 4701.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.12 |
June | 17621.73 | 26-JUN-07:03 | 674.99 | 150.00 | 149.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.38 |
July | 19406.69 | 11-JUL-07:02 | 843.73 | 187.50 | 186.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.54 |
August | 17885.78 | 19-AUG-07:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.31 |
September | 19531.50 | 02-SEP-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.02 |
October | 15866.15 | 15-OCT-18:50 | 8099.84 | 16962.41 | 4029.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 166.04 |
November | 4221.78 | 21-NOV-09:23 | 674.99 | 5951.72 | 1492.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 550.27 |
December | 4193.77 | 09-DEC-09:43 | 674.99 | 5951.72 | 1492.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 488.40 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2414.83 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.12 | |
Maximum of Months | 19531.50 | 16199.69 | 22616.54 | 5373.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 891.30 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4683.13 | 06-JAN-19:12 | 2699.95 | 10220.87 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 646.81 |
February | 5766.20 | 05-FEB-11:22 | 3374.94 | 12776.09 | 3358.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 851.93 |
March | 4802.62 | 17-MAR-09:23 | 1349.97 | 10220.87 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 609.95 |
April | 4334.75 | 08-APR-12:30 | 2024.96 | 2555.22 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.37 |
May | 8187.46 | 30-MAY-06:03 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.98 |
June | 17018.38 | 23-JUN-06:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.93 |
July | 19653.72 | 11-JUL-06:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.75 |
August | 21151.43 | 23-AUG-06:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.71 |
September | 19845.18 | 02-SEP-06:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.34 |
October | 10075.85 | 06-OCT-06:03 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.63 |
November | 3364.15 | 06-NOV-08:61 | 1181.23 | 262.50 | 2611.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 436.74 |
December | 4061.69 | 27-DEC-09:43 | 1012.48 | 7665.65 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 459.22 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3364.15 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.98 | |
Maximum of Months | 21151.43 | 3374.94 | 12776.09 | 3358.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 851.93 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5399.02 | 05-JAN-19:12 | 2699.95 | 10220.87 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 654.90 |
February | 5568.41 | 07-FEB-18:33 | 6749.87 | 10220.87 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 715.46 |
March | 3395.13 | 29-MAR-17:20 | 1687.47 | 2555.22 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 437.81 |
April | 4188.41 | 08-APR-12:30 | 2024.96 | 2555.22 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.37 |
May | 7864.75 | 31-MAY-06:03 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 17203.00 | 23-JUN-06:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.94 |
July | 19752.60 | 11-JUL-06:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.87 |
August | 21248.16 | 23-AUG-06:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.79 |
September | 19933.88 | 02-SEP-06:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.46 |
October | 9908.71 | 06-OCT-06:03 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.62 |
November | 3289.37 | 06-NOV-08:61 | 1181.23 | 262.50 | 2611.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 428.41 |
December | 5077.35 | 22-DEC-09:43 | 1349.97 | 10220.87 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 656.35 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3289.37 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21248.16 | 6749.87 | 10220.87 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 715.46 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4814.97 | 30-JAN-10:13 | 1349.97 | 10220.87 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 606.54 |
February | 3916.36 | 10-FEB-20:33 | 506.24 | 4034.55 | 1119.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.82 |
March | 4771.93 | 18-MAR-09:02 | 1349.97 | 10220.87 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 501.94 |
April | 3894.12 | 08-APR-12:40 | 2024.96 | 2555.22 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.54 |
May | 6514.59 | 31-MAY-06:03 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16007.39 | 26-JUN-06:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.90 |
July | 19484.30 | 11-JUL-06:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.54 |
August | 20964.19 | 23-AUG-06:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.54 |
September | 19646.66 | 02-SEP-06:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.93 |
October | 8723.52 | 06-OCT-06:03 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.50 |
November | 4787.86 | 22-NOV-20:42 | 674.99 | 5379.41 | 1492.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 198.76 |
December | 4357.02 | 27-DEC-20:23 | 674.99 | 5379.41 | 1492.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 114.81 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3894.12 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 20964.19 | 2024.96 | 10220.87 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 606.54 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2205.49 | 19-JAN-12:00 | 2902.53 | 2726.96 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 765.67 |
February | 2260.40 | 11-FEB-12:00 | 3915.04 | 2726.96 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 808.99 |
March | 9308.58 | 22-MAR-19:03 | 2970.03 | 5740.94 | 2985.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 259.46 |
April | 6653.14 | 12-APR-08:63 | 2227.52 | 225.00 | 2238.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 834.23 |
May | 12426.34 | 30-MAY-07:03 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.07 |
June | 28219.20 | 26-JUN-07:03 | 0.00 | 300.00 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.04 |
July | 34351.26 | 11-JUL-07:02 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.62 |
August | 32595.95 | 19-AUG-07:03 | 0.00 | 300.00 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 129.50 |
September | 34644.00 | 02-SEP-07:02 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 132.97 |
October | 13442.95 | 06-OCT-07:03 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 204.47 |
November | 8327.37 | 21-NOV-10:32 | 2970.03 | 10907.84 | 5373.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1011.98 |
December | 8841.96 | 15-DEC-10:43 | 2970.03 | 10907.84 | 5373.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 900.54 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2205.49 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.07 | |
Maximum of Months | 34644.00 | 3915.04 | 10907.84 | 5373.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1011.98 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3567.79 | 19-JAN-20:23 | 1113.73 | 2217.58 | 1119.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.71 |
February | 4467.09 | 02-FEB-19:12 | 3509.93 | 5617.86 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 598.05 |
March | 3899.68 | 09-MAR-19:03 | 2632.45 | 4213.39 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 488.37 |
April | 3269.70 | 12-APR-08:63 | 1113.73 | 112.50 | 1119.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 451.19 |
May | 5796.00 | 30-MAY-13:00 | 2396.20 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 996.87 | 0.00 |
June | 14484.05 | 26-JUN-07:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.08 |
July | 17638.51 | 11-JUL-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.95 |
August | 15464.51 | 19-AUG-07:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.57 |
September | 17783.51 | 02-SEP-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.05 |
October | 6193.73 | 06-OCT-07:03 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 110.82 |
November | 4539.44 | 24-NOV-11:23 | 5804.89 | 5617.86 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 577.77 |
December | 4294.60 | 01-DEC-19:33 | 3509.93 | 5617.86 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 647.81 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3269.70 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17783.51 | 5804.89 | 5617.86 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 996.87 | 647.81 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3315.02 | 12-JAN-18:23 | 3442.43 | 4213.39 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 409.01 |
February | 4313.45 | 17-FEB-19:42 | 3509.93 | 5617.86 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 515.82 |
March | 3710.10 | 21-MAR-19:13 | 1113.73 | 2217.58 | 1119.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 213.08 |
April | 2963.30 | 08-APR-12:30 | 2497.45 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.23 |
May | 5711.33 | 30-MAY-13:00 | 2396.20 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 996.86 | 0.00 |
June | 14394.11 | 26-JUN-07:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.16 |
July | 17542.79 | 11-JUL-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.19 |
August | 15017.69 | 19-AUG-07:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.46 |
September | 17687.18 | 02-SEP-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.29 |
October | 5748.77 | 06-OCT-07:03 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 110.72 |
November | 3914.43 | 25-NOV-11:23 | 5872.39 | 4213.39 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 490.02 |
December | 4650.16 | 21-DEC-20:03 | 1484.97 | 2956.77 | 1492.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.34 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2963.30 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17687.18 | 5872.39 | 5617.86 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 996.86 | 515.82 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3191.89 | 17-JAN-18:03 | 3442.43 | 4213.39 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 344.02 |
February | 2996.96 | 01-FEB-18:23 | 3442.43 | 4213.39 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 406.52 |
March | 3639.38 | 13-MAR-18:23 | 2632.45 | 4213.39 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 518.08 |
April | 3051.51 | 22-APR-10:13 | 5872.39 | 4213.39 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 421.07 |
May | 5551.70 | 30-MAY-13:00 | 2396.20 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 996.86 | 0.00 |
June | 14156.12 | 26-JUN-07:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.71 |
July | 17380.59 | 11-JUL-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.89 |
August | 14819.70 | 22-AUG-07:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 39.59 | 0.00 |
September | 17538.87 | 02-SEP-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.31 |
October | 4952.86 | 04-OCT-13:00 | 2396.20 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 182.23 | 0.00 |
November | 3237.83 | 15-NOV-20:23 | 1113.73 | 2217.58 | 1119.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.97 |
December | 4204.36 | 01-DEC-18:53 | 4589.91 | 5617.86 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 621.99 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2996.96 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17538.87 | 5872.39 | 5617.86 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 996.86 | 621.99 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 214.98 | 19-JAN-12:00 | 1451.22 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 571.68 |
February | 119.35 | 17-FEB-12:00 | 1451.22 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 383.23 |
March | 2748.52 | 29-MAR-14:55 | 4657.41 | 2808.93 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2563.31 |
April | 2899.62 | 08-APR-12:20 | 2497.45 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.25 |
May | 5914.29 | 30-MAY-13:00 | 2396.20 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1037.52 | 0.00 |
June | 14169.01 | 20-JUN-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.15 |
July | 16189.51 | 11-JUL-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.30 |
August | 15961.47 | 22-AUG-07:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 53.91 | 0.00 |
September | 18684.84 | 02-SEP-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.27 |
October | 5298.07 | 04-OCT-13:00 | 2396.20 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 189.66 | 0.00 |
November | 2201.14 | 13-NOV-18:15 | 2294.96 | 2808.93 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 358.72 |
December | 685.86 | 20-DEC-12:00 | 1451.22 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 329.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 119.35 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18684.84 | 4657.41 | 2808.93 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 1037.52 | 2563.31 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.637281E+11 | 56338.92 | 04-JAN-16:40 | 0.121779E+12 | 229411.38 | 02-JAN-08:09 |
February | 0.571846E+11 | 53327.11 | 03-FEB-19:49 | 0.114245E+12 | 233566.85 | 06-FEB-08:09 |
March | 0.621433E+11 | 53898.99 | 03-MAR-19:49 | 0.669983E+11 | 144559.76 | 22-MAR-07:10 |
April | 0.586515E+11 | 58421.99 | 08-APR-12:39 | 0.239997E+11 | 108005.90 | 03-APR-07:10 |
May | 0.630927E+11 | 69755.79 | 31-MAY-13:09 | 0.891822E+09 | 34460.34 | 01-MAY-07:10 |
June | 0.781882E+11 | 90163.00 | 19-JUN-12:09 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 0.942514E+11 | 92582.63 | 08-JUL-11:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.950100E+11 | 94012.95 | 16-AUG-13:30 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.736579E+11 | 78040.20 | 14-SEP-12:39 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 0.646947E+11 | 65467.61 | 04-OCT-13:30 | 0.875445E+09 | 27878.13 | 29-OCT-08:09 |
November | 0.601259E+11 | 53824.04 | 22-NOV-18:00 | 0.449306E+11 | 132567.63 | 25-NOV-08:09 |
December | 0.631781E+11 | 51628.58 | 11-DEC-17:19 | 0.923620E+11 | 164945.35 | 31-DEC-17:00 |
Annual Sum or Average | 0.833906E+12 | 0.466081E+12 | ||||
Minimum of Months | 0.571846E+11 | 51628.58 | 0.00 | 0.00 | ||
Maximum of Months | 0.950100E+11 | 94012.95 | 0.121779E+12 | 233566.85 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.310073E+11 | 0.669409E+10 | 0.108325E+11 | 0.00 | 0.957405E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.562027E+10 | 0.00 |
February | 0.280657E+11 | 0.546825E+10 | 0.980803E+10 | 0.00 | 0.873623E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.510639E+10 | 0.00 |
March | 0.314703E+11 | 0.526005E+10 | 0.110075E+11 | 0.00 | 0.876053E+10 | 0.00 | 0.00 | 3247074.10 | 0.00 | 0.00 | 0.00 | 0.564174E+10 | 0.00 |
April | 0.300741E+11 | 0.429522E+10 | 0.105079E+11 | 0.00 | 0.771974E+10 | 0.00 | 0.00 | 0.725708E+09 | 0.00 | 0.00 | 0.00 | 0.532878E+10 | 0.00 |
May | 0.312330E+11 | 0.384977E+10 | 0.109147E+11 | 0.00 | 0.769422E+10 | 0.00 | 0.00 | 0.401648E+10 | 0.00 | 0.00 | 0.00 | 0.538455E+10 | 0.00 |
June | 0.304143E+11 | 0.343615E+10 | 0.106386E+11 | 0.00 | 0.752278E+10 | 0.00 | 0.00 | 0.210668E+11 | 0.00 | 0.00 | 0.00 | 0.510954E+10 | 0.00 |
July | 0.309042E+11 | 0.363884E+10 | 0.107945E+11 | 0.00 | 0.783019E+10 | 0.00 | 0.00 | 0.359177E+11 | 0.00 | 0.00 | 0.00 | 0.516591E+10 | 0.00 |
August | 0.314595E+11 | 0.412573E+10 | 0.110006E+11 | 0.00 | 0.807040E+10 | 0.00 | 0.00 | 0.351606E+11 | 0.00 | 0.00 | 0.00 | 0.519311E+10 | 0.00 |
September | 0.300847E+11 | 0.474129E+10 | 0.105148E+11 | 0.00 | 0.741084E+10 | 0.00 | 0.00 | 0.158640E+11 | 0.00 | 0.00 | 0.00 | 0.504224E+10 | 0.00 |
October | 0.310073E+11 | 0.572595E+10 | 0.108325E+11 | 0.00 | 0.764166E+10 | 0.00 | 0.00 | 0.419275E+10 | 0.00 | 0.00 | 0.00 | 0.529465E+10 | 0.00 |
November | 0.300409E+11 | 0.626785E+10 | 0.104978E+11 | 0.00 | 0.804628E+10 | 0.00 | 0.00 | 1343001.47 | 0.00 | 0.00 | 0.00 | 0.527163E+10 | 0.00 |
December | 0.309156E+11 | 0.686921E+10 | 0.108050E+11 | 0.00 | 0.903788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.555037E+10 | 0.00 |
Annual Sum or Average | 0.366677E+12 | 0.603724E+11 | 0.128154E+12 | 0.00 | 0.980448E+11 | 0.00 | 0.00 | 0.116949E+12 | 0.00 | 0.00 | 0.00 | 0.637092E+11 | 0.00 |
Minimum of Months | 0.280657E+11 | 0.343615E+10 | 0.980803E+10 | 0.00 | 0.741084E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.504224E+10 | 0.00 |
Maximum of Months | 0.314703E+11 | 0.686921E+10 | 0.110075E+11 | 0.00 | 0.957405E+10 | 0.00 | 0.00 | 0.359177E+11 | 0.00 | 0.00 | 0.00 | 0.564174E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.121779E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.114245E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.669983E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.239997E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.891822E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.875445E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.449306E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.923620E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.466081E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.121779E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 23459.17 | 01-JAN-11:09 | 5507.06 | 01-JAN-06:10 | 8059.50 | 01-JAN-11:09 | 0.00 | 9102.88 | 02-JAN-08:09 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 23459.17 | 01-FEB-10:09 | 5507.06 | 01-FEB-06:10 | 8059.50 | 01-FEB-10:09 | 0.00 | 9170.38 | 06-FEB-08:09 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 23459.17 | 01-MAR-10:09 | 5507.06 | 01-MAR-06:10 | 8059.50 | 01-MAR-10:09 | 0.00 | 7651.45 | 22-MAR-07:10 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 23459.17 | 01-APR-09:09 | 5507.06 | 01-APR-05:10 | 8059.50 | 01-APR-09:09 | 0.00 | 7027.55 | 03-APR-07:10 | 0.00 | 0.00 | 01-APR-00:10 |
May | 23459.17 | 01-MAY-09:09 | 5507.06 | 01-MAY-18:49 | 8059.50 | 01-MAY-09:09 | 0.00 | 5770.48 | 01-MAY-07:10 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 23459.17 | 01-JUN-09:09 | 5507.06 | 01-JUN-19:19 | 8059.50 | 01-JUN-09:09 | 0.00 | 7580.83 | 19-JUN-12:09 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 23459.17 | 01-JUL-09:09 | 5507.06 | 01-JUL-19:30 | 8059.50 | 01-JUL-09:09 | 0.00 | 8359.58 | 08-JUL-12:20 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 23459.17 | 01-AUG-09:09 | 5507.06 | 01-AUG-19:10 | 8059.50 | 01-AUG-09:09 | 0.00 | 8269.25 | 16-AUG-12:00 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 23459.17 | 01-SEP-09:09 | 5507.06 | 01-SEP-05:10 | 8059.50 | 01-SEP-09:09 | 0.00 | 6364.02 | 13-SEP-07:10 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 23459.17 | 01-OCT-10:09 | 5507.06 | 01-OCT-05:10 | 8059.50 | 01-OCT-10:09 | 0.00 | 5659.40 | 29-OCT-08:09 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 23459.17 | 01-NOV-09:09 | 5507.06 | 01-NOV-05:10 | 8059.50 | 01-NOV-09:09 | 0.00 | 7448.04 | 25-NOV-08:09 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 23459.17 | 01-DEC-10:09 | 5507.06 | 01-DEC-06:10 | 8059.50 | 01-DEC-10:09 | 0.00 | 8004.53 | 31-DEC-17:00 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||||
Minimum of Months | 23459.17 | 5507.06 | 8059.50 | 0.00 | 5659.40 | 0.00 | 0.00 | |||||
Maximum of Months | 23459.17 | 5507.06 | 8059.50 | 0.00 | 9170.38 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 11858.75 | 04-JAN-13:50 | 0.00 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 10756.65 | 09-FEB-12:00 | 0.00 |
March | 1151.98 | 27-MAR-16:10 | 0.00 | 0.00 | 0.00 | 11842.65 | 03-MAR-15:09 | 0.00 |
April | 15222.32 | 07-APR-12:00 | 0.00 | 0.00 | 0.00 | 9317.05 | 24-APR-10:50 | 0.00 |
May | 26953.36 | 30-MAY-12:00 | 0.00 | 0.00 | 0.00 | 9441.50 | 30-MAY-18:49 | 0.00 |
June | 47836.30 | 19-JUN-12:09 | 0.00 | 0.00 | 0.00 | 9700.89 | 03-JUN-12:00 | 0.00 |
July | 48709.80 | 08-JUL-12:09 | 0.00 | 0.00 | 0.00 | 7566.75 | 29-JUL-12:50 | 0.00 |
August | 48449.74 | 16-AUG-12:00 | 0.00 | 0.00 | 0.00 | 9685.05 | 09-AUG-12:39 | 0.00 |
September | 35830.45 | 14-SEP-12:00 | 0.00 | 0.00 | 0.00 | 7572.59 | 22-SEP-12:09 | 0.00 |
October | 23998.20 | 04-OCT-12:00 | 0.00 | 0.00 | 0.00 | 8252.20 | 24-OCT-14:50 | 0.00 |
November | 339.21 | 06-NOV-21:30 | 0.00 | 0.00 | 0.00 | 10472.70 | 22-NOV-18:00 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 9513.72 | 02-DEC-14:09 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 7566.75 | 0.00 | ||
Maximum of Months | 48709.80 | 0.00 | 0.00 | 0.00 | 11858.75 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 56338.92 | 04-JAN-16:40 | 23459.17 | 8059.50 | 5507.06 | 0.00 | 7514.38 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 53327.11 | 03-FEB-19:49 | 23459.17 | 8059.50 | 5507.06 | 0.00 | 6622.32 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 53898.99 | 03-MAR-19:49 | 23459.17 | 8059.50 | 5507.06 | 0.00 | 5263.07 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 58421.99 | 08-APR-12:39 | 23459.17 | 8059.50 | 0.00 | 0.00 | 5181.93 | 0.00 | 0.00 | 14130.52 | 0.00 |
May | 69755.79 | 31-MAY-13:09 | 23459.17 | 8059.50 | 0.00 | 0.00 | 5181.93 | 0.00 | 0.00 | 25480.38 | 0.00 |
June | 90163.00 | 19-JUN-12:09 | 23459.17 | 8059.50 | 0.00 | 0.00 | 7580.83 | 0.00 | 0.00 | 47836.30 | 0.00 |
July | 92582.63 | 08-JUL-11:00 | 23459.17 | 8059.50 | 0.00 | 0.00 | 8071.32 | 0.00 | 0.00 | 47558.74 | 0.00 |
August | 94012.95 | 16-AUG-13:30 | 23459.17 | 8059.50 | 0.00 | 0.00 | 7942.27 | 0.00 | 0.00 | 46987.03 | 0.00 |
September | 78040.20 | 14-SEP-12:39 | 23459.17 | 8059.50 | 0.00 | 0.00 | 5726.44 | 0.00 | 0.00 | 35345.11 | 0.00 |
October | 65467.61 | 04-OCT-13:30 | 23459.17 | 8059.50 | 0.00 | 0.00 | 5181.93 | 0.00 | 0.00 | 23316.03 | 0.00 |
November | 53824.04 | 22-NOV-18:00 | 23459.17 | 8059.50 | 5507.06 | 0.00 | 6325.61 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 51628.58 | 11-DEC-17:19 | 23459.17 | 8059.50 | 5507.06 | 0.00 | 7038.11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 51628.58 | 23459.17 | 8059.50 | 0.00 | 0.00 | 5181.93 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 94012.95 | 23459.17 | 8059.50 | 5507.06 | 0.00 | 8071.32 | 0.00 | 0.00 | 47836.30 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 229411.38 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 233566.85 | 06-FEB-08:09 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 144559.76 | 22-MAR-07:10 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 108005.90 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 34460.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 27878.13 | 29-OCT-08:09 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 132567.63 | 25-NOV-08:09 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 164945.35 | 31-DEC-17:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 233566.85 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.67 | 20.43 | 1.00 | 20.44 | 0.00 | 20.44 | 0.00 | 20.44 |
February | 2.83 | 20.38 | 1.17 | 20.37 | 0.00 | 20.37 | 0.00 | 20.37 |
March | 0.50 | 20.52 | 0.00 | 20.52 | 0.00 | 20.52 | 0.00 | 20.52 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.33 | 20.47 | 0.00 | 20.47 | 0.00 | 20.47 | 0.00 | 20.47 |
December | 0.50 | 20.53 | 0.00 | 20.53 | 0.00 | 20.53 | 0.00 | 20.53 |
Annual Sum or Average | 6.83 | 20.42 | 2.17 | 20.42 | 0.00 | 20.42 | 0.00 | 20.42 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.83 | 20.53 | 1.17 | 20.53 | 0.00 | 20.53 | 0.00 | 20.53 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.50 | 20.48 | 0.00 | 20.48 | 0.00 | 20.48 | 0.00 | 20.48 |
February | 0.67 | 20.50 | 0.00 | 20.50 | 0.00 | 20.50 | 0.00 | 20.50 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1.17 | 20.49 | 0.00 | 20.49 | 0.00 | 20.49 | 0.00 | 20.49 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.67 | 20.50 | 0.00 | 20.50 | 0.00 | 20.50 | 0.00 | 20.50 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.33 | 20.39 | 0.00 | 20.39 | 0.00 | 20.39 | 0.00 | 20.39 |
February | 0.17 | 20.40 | 0.00 | 20.40 | 0.00 | 20.40 | 0.00 | 20.40 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.50 | 20.39 | 0.00 | 20.39 | 0.00 | 20.39 | 0.00 | 20.39 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.33 | 20.40 | 0.00 | 20.40 | 0.00 | 20.40 | 0.00 | 20.40 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.33 | 20.24 | 0.00 | 20.24 | 0.00 | 20.24 | 0.00 | 20.24 |
February | 0.33 | 20.42 | 0.00 | 20.42 | 0.00 | 20.42 | 0.00 | 20.42 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.67 | 20.33 | 0.00 | 20.33 | 0.00 | 20.33 | 0.00 | 20.33 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.33 | 20.42 | 0.00 | 20.42 | 0.00 | 20.42 | 0.00 | 20.42 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.50 | 20.22 | 0.00 | 20.22 | 0.00 | 20.22 | 0.00 | 20.22 |
February | 0.50 | 20.40 | 0.00 | 20.40 | 0.00 | 20.40 | 0.00 | 20.40 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1.00 | 20.31 | 0.00 | 20.31 | 0.00 | 20.31 | 0.00 | 20.31 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.50 | 20.40 | 0.00 | 20.40 | 0.00 | 20.40 | 0.00 | 20.40 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.67 | 20.37 | 0.00 | 20.37 | 0.00 | 20.37 | 0.00 | 20.37 |
February | 1.17 | 20.32 | 0.00 | 20.32 | 0.00 | 20.32 | 0.00 | 20.32 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.17 | 20.55 | 0.00 | 20.55 | 0.00 | 20.55 | 0.00 | 20.55 |
Annual Sum or Average | 3.00 | 20.36 | 0.00 | 20.36 | 0.00 | 20.36 | 0.00 | 20.36 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.67 | 20.55 | 0.00 | 20.55 | 0.00 | 20.55 | 0.00 | 20.55 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.67 | 20.36 | 0.00 | 20.36 | 0.00 | 20.36 | 0.00 | 20.36 |
February | 1.17 | 20.33 | 0.00 | 20.33 | 0.00 | 20.33 | 0.00 | 20.33 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2.83 | 20.35 | 0.00 | 20.35 | 0.00 | 20.35 | 0.00 | 20.35 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.67 | 20.36 | 0.00 | 20.36 | 0.00 | 20.36 | 0.00 | 20.36 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.67 | 20.34 | 0.00 | 20.34 | 0.00 | 20.34 | 0.00 | 20.34 |
February | 1.33 | 20.34 | 0.00 | 20.34 | 0.00 | 20.34 | 0.00 | 20.34 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.17 | 20.54 | 0.00 | 20.54 | 0.00 | 20.54 | 0.00 | 20.54 |
Annual Sum or Average | 3.17 | 20.35 | 0.00 | 20.35 | 0.00 | 20.35 | 0.00 | 20.35 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.67 | 20.54 | 0.00 | 20.54 | 0.00 | 20.54 | 0.00 | 20.54 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.50 | 20.36 | 0.00 | 20.36 | 0.00 | 20.36 | 0.00 | 20.36 |
February | 2.17 | 19.91 | 0.00 | 19.91 | 0.00 | 19.91 | 0.00 | 19.91 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.17 | 20.42 | 0.00 | 20.42 | 0.00 | 20.42 | 0.00 | 20.42 |
Annual Sum or Average | 4.83 | 20.16 | 0.00 | 20.16 | 0.00 | 20.16 | 0.00 | 20.16 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.50 | 20.42 | 0.00 | 20.42 | 0.00 | 20.42 | 0.00 | 20.42 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 7.83 | 17.96 | 0.00 | 17.96 | 0.00 | 17.96 | 0.00 | 17.96 |
February | 8.17 | 17.89 | 0.00 | 17.89 | 0.00 | 17.89 | 0.00 | 17.89 |
March | 2.50 | 20.28 | 0.00 | 20.28 | 0.00 | 20.28 | 0.00 | 20.28 |
April | 0.83 | 20.43 | 0.00 | 20.43 | 0.00 | 20.43 | 0.00 | 20.43 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1.17 | 20.32 | 0.00 | 20.32 | 0.00 | 20.32 | 0.00 | 20.32 |
December | 3.67 | 20.13 | 0.00 | 20.13 | 0.00 | 20.13 | 0.00 | 20.13 |
Annual Sum or Average | 24.17 | 18.70 | 0.00 | 18.70 | 0.00 | 18.70 | 0.00 | 18.70 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 8.17 | 20.43 | 0.00 | 20.43 | 0.00 | 20.43 | 0.00 | 20.43 |
Report: ComfortReportSimple55Monthly
For: LGSTORE1
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 496.00 | 21.07 | 308.17 | 21.06 | 308.17 | 21.05 |
February | 448.00 | 21.06 | 325.00 | 21.05 | 325.00 | 21.05 |
March | 495.50 | 21.16 | 119.00 | 21.12 | 119.00 | 21.10 |
April | 415.83 | 21.67 | 46.67 | 21.71 | 27.83 | 21.67 |
May | 254.00 | 22.77 | 96.67 | 23.07 | 27.83 | 23.12 |
June | 109.83 | 23.88 | 416.33 | 23.89 | 101.83 | 23.89 |
July | 134.00 | 23.89 | 494.17 | 23.89 | 134.00 | 23.89 |
August | 56.50 | 23.89 | 468.17 | 23.89 | 56.50 | 23.89 |
September | 47.33 | 23.70 | 358.67 | 23.87 | 25.17 | 23.87 |
October | 246.50 | 22.63 | 216.33 | 23.21 | 29.83 | 23.25 |
November | 472.00 | 21.38 | 66.83 | 21.33 | 66.83 | 21.29 |
December | 496.00 | 21.06 | 234.00 | 21.05 | 234.00 | 21.04 |
Annual Sum or Average | 3671.50 | 21.67 | 3150.00 | 22.24 | 1456.00 | 22.16 |
Minimum of Months | 47.33 | 21.06 | 46.67 | 21.05 | 25.17 | 21.04 |
Maximum of Months | 496.00 | 23.89 | 494.17 | 23.89 | 325.00 | 23.89 |
Report: ComfortReportSimple55Monthly
For: SMSTORE1
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 496.00 | 21.36 | 151.50 | 21.30 | 151.50 | 21.27 |
February | 448.00 | 21.38 | 152.83 | 21.31 | 152.83 | 21.28 |
March | 490.67 | 21.69 | 19.33 | 21.67 | 19.33 | 21.65 |
April | 379.67 | 22.20 | 27.00 | 22.30 | 1.50 | 22.29 |
May | 163.50 | 23.28 | 120.17 | 23.53 | 24.83 | 23.56 |
June | 41.00 | 23.87 | 402.83 | 23.88 | 35.83 | 23.88 |
July | 62.33 | 23.89 | 490.17 | 23.89 | 62.33 | 23.89 |
August | 31.17 | 23.86 | 449.33 | 23.89 | 30.17 | 23.89 |
September | 27.50 | 23.74 | 341.17 | 23.88 | 15.33 | 23.88 |
October | 191.83 | 23.24 | 226.83 | 23.59 | 20.33 | 23.60 |
November | 456.00 | 22.01 | 9.67 | 22.00 | 8.33 | 21.98 |
December | 496.00 | 21.49 | 31.00 | 21.47 | 31.00 | 21.45 |
Annual Sum or Average | 3283.67 | 21.95 | 2421.83 | 22.59 | 553.33 | 22.55 |
Minimum of Months | 27.50 | 21.36 | 9.67 | 21.30 | 1.50 | 21.27 |
Maximum of Months | 496.00 | 23.89 | 490.17 | 23.89 | 152.83 | 23.89 |
Report: ComfortReportSimple55Monthly
For: SMSTORE2
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 371.00 | 21.11 | 166.17 | 21.11 | 166.17 | 21.11 |
February | 336.00 | 21.11 | 169.67 | 21.11 | 169.67 | 21.11 |
March | 376.33 | 21.24 | 39.67 | 21.23 | 39.67 | 21.22 |
April | 298.33 | 21.73 | 23.83 | 21.85 | 5.00 | 21.84 |
May | 153.50 | 22.97 | 85.33 | 23.32 | 23.83 | 23.37 |
June | 63.33 | 24.09 | 323.00 | 24.02 | 59.67 | 24.03 |
July | 104.33 | 24.20 | 369.00 | 24.08 | 104.33 | 24.10 |
August | 51.50 | 24.42 | 362.50 | 24.10 | 51.50 | 24.14 |
September | 35.00 | 23.88 | 279.67 | 23.99 | 22.67 | 24.00 |
October | 153.17 | 22.76 | 174.17 | 23.39 | 17.83 | 23.42 |
November | 349.50 | 21.52 | 22.50 | 21.49 | 22.50 | 21.47 |
December | 369.00 | 21.11 | 77.83 | 21.11 | 77.83 | 21.11 |
Annual Sum or Average | 2661.00 | 21.75 | 2093.33 | 22.45 | 760.67 | 22.42 |
Minimum of Months | 35.00 | 21.11 | 22.50 | 21.11 | 5.00 | 21.11 |
Maximum of Months | 376.33 | 24.42 | 369.00 | 24.10 | 169.67 | 24.14 |
Report: ComfortReportSimple55Monthly
For: SMSTORE3
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 371.00 | 21.11 | 180.00 | 21.11 | 180.00 | 21.11 |
February | 336.00 | 21.11 | 182.67 | 21.11 | 182.67 | 21.11 |
March | 378.67 | 21.24 | 48.17 | 21.22 | 48.17 | 21.21 |
April | 304.50 | 21.72 | 23.83 | 21.83 | 6.83 | 21.81 |
May | 161.17 | 22.86 | 78.33 | 23.22 | 23.83 | 23.28 |
June | 65.67 | 24.09 | 322.67 | 24.02 | 61.67 | 24.03 |
July | 104.33 | 24.20 | 369.00 | 24.08 | 104.33 | 24.10 |
August | 51.50 | 24.42 | 362.33 | 24.10 | 51.50 | 24.14 |
September | 36.00 | 23.87 | 278.67 | 23.99 | 23.00 | 24.00 |
October | 158.83 | 22.71 | 168.83 | 23.34 | 18.17 | 23.37 |
November | 351.00 | 21.47 | 29.33 | 21.44 | 29.33 | 21.41 |
December | 369.00 | 21.11 | 96.50 | 21.11 | 96.50 | 21.11 |
Annual Sum or Average | 2687.67 | 21.74 | 2140.33 | 22.42 | 826.00 | 22.38 |
Minimum of Months | 36.00 | 21.11 | 23.83 | 21.11 | 6.83 | 21.11 |
Maximum of Months | 378.67 | 24.42 | 369.00 | 24.10 | 182.67 | 24.14 |
Report: ComfortReportSimple55Monthly
For: SMSTORE4
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 371.00 | 21.11 | 198.17 | 21.11 | 198.17 | 21.11 |
February | 336.00 | 21.11 | 198.83 | 21.11 | 198.83 | 21.11 |
March | 379.00 | 21.21 | 57.83 | 21.20 | 57.83 | 21.19 |
April | 312.17 | 21.70 | 22.33 | 21.75 | 11.50 | 21.72 |
May | 179.50 | 22.73 | 74.33 | 23.09 | 23.83 | 23.16 |
June | 73.50 | 24.05 | 320.50 | 24.01 | 68.83 | 24.02 |
July | 116.17 | 24.16 | 369.00 | 24.07 | 116.17 | 24.09 |
August | 55.17 | 24.37 | 360.67 | 24.09 | 55.17 | 24.13 |
September | 41.33 | 23.81 | 274.67 | 23.97 | 25.33 | 23.98 |
October | 165.83 | 22.60 | 160.83 | 23.26 | 19.00 | 23.29 |
November | 354.17 | 21.41 | 38.33 | 21.38 | 38.33 | 21.35 |
December | 369.00 | 21.11 | 126.00 | 21.11 | 126.00 | 21.11 |
Annual Sum or Average | 2752.83 | 21.74 | 2201.50 | 22.38 | 939.00 | 22.33 |
Minimum of Months | 41.33 | 21.11 | 22.33 | 21.11 | 11.50 | 21.11 |
Maximum of Months | 379.00 | 24.37 | 369.00 | 24.09 | 198.83 | 24.13 |
Report: ComfortReportSimple55Monthly
For: LGSTORE2
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.11 | 247.33 | 21.11 | 247.33 | 21.11 |
February | 308.00 | 21.11 | 246.67 | 21.11 | 246.67 | 21.11 |
March | 348.00 | 21.18 | 93.33 | 21.16 | 93.33 | 21.16 |
April | 304.83 | 21.70 | 23.83 | 21.71 | 17.67 | 21.68 |
May | 214.83 | 22.71 | 57.67 | 22.95 | 25.67 | 23.01 |
June | 114.50 | 23.94 | 286.33 | 23.92 | 110.17 | 23.93 |
July | 143.00 | 23.98 | 337.33 | 23.96 | 143.00 | 23.96 |
August | 71.67 | 24.00 | 323.50 | 23.95 | 71.67 | 23.96 |
September | 56.00 | 23.73 | 237.83 | 23.89 | 35.67 | 23.89 |
October | 174.33 | 22.54 | 137.00 | 23.13 | 23.67 | 23.19 |
November | 326.33 | 21.30 | 60.00 | 21.27 | 60.00 | 21.25 |
December | 338.00 | 21.11 | 210.67 | 21.11 | 210.67 | 21.11 |
Annual Sum or Average | 2739.50 | 21.82 | 2261.50 | 22.28 | 1285.50 | 22.23 |
Minimum of Months | 56.00 | 21.11 | 23.83 | 21.11 | 17.67 | 21.11 |
Maximum of Months | 348.00 | 24.00 | 337.33 | 23.96 | 247.33 | 23.96 |
Report: ComfortReportSimple55Monthly
For: SMSTORE5
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.11 | 247.33 | 21.11 | 247.33 | 21.11 |
February | 308.00 | 21.11 | 249.17 | 21.11 | 249.17 | 21.11 |
March | 348.00 | 21.18 | 100.33 | 21.16 | 100.33 | 21.15 |
April | 309.00 | 21.71 | 24.83 | 21.70 | 20.67 | 21.67 |
May | 228.50 | 22.73 | 54.83 | 22.94 | 25.50 | 23.00 |
June | 118.00 | 23.93 | 272.50 | 23.92 | 111.67 | 23.93 |
July | 144.33 | 23.98 | 336.00 | 23.96 | 144.33 | 23.96 |
August | 72.83 | 23.99 | 313.83 | 23.95 | 72.83 | 23.95 |
September | 60.33 | 23.74 | 220.83 | 23.89 | 36.83 | 23.89 |
October | 183.17 | 22.58 | 132.17 | 23.13 | 25.00 | 23.18 |
November | 327.50 | 21.29 | 64.17 | 21.26 | 64.17 | 21.24 |
December | 338.00 | 21.11 | 214.33 | 21.11 | 214.33 | 21.11 |
Annual Sum or Average | 2777.67 | 21.84 | 2230.33 | 22.26 | 1312.17 | 22.21 |
Minimum of Months | 60.33 | 21.11 | 24.83 | 21.11 | 20.67 | 21.11 |
Maximum of Months | 348.00 | 23.99 | 336.00 | 23.96 | 249.17 | 23.96 |
Report: ComfortReportSimple55Monthly
For: SMSTORE6
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.11 | 252.00 | 21.11 | 252.00 | 21.11 |
February | 308.00 | 21.11 | 254.17 | 21.11 | 254.17 | 21.11 |
March | 348.00 | 21.17 | 106.00 | 21.16 | 106.00 | 21.15 |
April | 311.83 | 21.70 | 27.17 | 21.69 | 23.33 | 21.65 |
May | 236.33 | 22.69 | 52.50 | 22.89 | 25.50 | 22.94 |
June | 123.33 | 23.93 | 270.17 | 23.92 | 116.50 | 23.93 |
July | 147.50 | 23.97 | 335.67 | 23.96 | 147.50 | 23.96 |
August | 74.67 | 23.99 | 312.50 | 23.95 | 74.67 | 23.95 |
September | 63.33 | 23.73 | 216.83 | 23.88 | 37.50 | 23.89 |
October | 189.17 | 22.56 | 130.33 | 23.10 | 25.67 | 23.16 |
November | 329.00 | 21.29 | 68.33 | 21.26 | 68.33 | 21.24 |
December | 338.00 | 21.11 | 225.83 | 21.11 | 225.83 | 21.11 |
Annual Sum or Average | 2809.17 | 21.84 | 2251.50 | 22.25 | 1357.00 | 22.20 |
Minimum of Months | 63.33 | 21.11 | 27.17 | 21.11 | 23.33 | 21.11 |
Maximum of Months | 348.00 | 23.99 | 335.67 | 23.96 | 254.17 | 23.96 |
Report: ComfortReportSimple55Monthly
For: SMSTORE7
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.11 | 268.33 | 21.11 | 268.33 | 21.11 |
February | 308.00 | 21.11 | 277.83 | 21.11 | 277.83 | 21.11 |
March | 348.00 | 21.16 | 133.67 | 21.15 | 133.67 | 21.14 |
April | 316.33 | 21.67 | 35.00 | 21.63 | 32.67 | 21.59 |
May | 260.00 | 22.62 | 51.50 | 22.78 | 26.00 | 22.82 |
June | 132.50 | 23.92 | 266.50 | 23.92 | 124.33 | 23.92 |
July | 154.00 | 23.97 | 335.50 | 23.95 | 154.00 | 23.96 |
August | 78.17 | 23.98 | 312.17 | 23.95 | 78.17 | 23.95 |
September | 69.67 | 23.69 | 211.33 | 23.87 | 40.00 | 23.87 |
October | 200.83 | 22.49 | 125.83 | 23.02 | 27.67 | 23.09 |
November | 330.00 | 21.26 | 80.67 | 21.23 | 80.67 | 21.21 |
December | 338.00 | 21.11 | 256.67 | 21.11 | 256.67 | 21.11 |
Annual Sum or Average | 2875.50 | 21.85 | 2355.00 | 22.22 | 1500.00 | 22.16 |
Minimum of Months | 69.67 | 21.11 | 35.00 | 21.11 | 26.00 | 21.11 |
Maximum of Months | 348.00 | 23.98 | 335.50 | 23.95 | 277.83 | 23.96 |
Report: ComfortReportSimple55Monthly
For: SMSTORE8
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.11 | 308.50 | 21.11 | 308.50 | 21.11 |
February | 308.00 | 21.11 | 308.00 | 21.11 | 308.00 | 21.11 |
March | 348.00 | 21.14 | 220.17 | 21.13 | 220.17 | 21.12 |
April | 319.17 | 21.61 | 86.67 | 21.51 | 86.67 | 21.44 |
May | 289.33 | 22.50 | 52.83 | 22.62 | 27.00 | 22.63 |
June | 151.33 | 23.89 | 262.33 | 23.90 | 140.17 | 23.90 |
July | 158.00 | 23.97 | 336.83 | 23.96 | 158.00 | 23.96 |
August | 71.00 | 24.01 | 321.50 | 23.95 | 71.00 | 23.96 |
September | 81.67 | 23.55 | 204.00 | 23.82 | 42.67 | 23.83 |
October | 213.50 | 22.34 | 125.33 | 22.88 | 32.83 | 22.94 |
November | 330.00 | 21.23 | 144.83 | 21.19 | 144.83 | 21.17 |
December | 338.00 | 21.11 | 320.17 | 21.11 | 320.17 | 21.11 |
Annual Sum or Average | 2948.00 | 21.84 | 2691.17 | 22.13 | 1860.00 | 22.05 |
Minimum of Months | 71.00 | 21.11 | 52.83 | 21.11 | 27.00 | 21.11 |
Maximum of Months | 348.00 | 24.01 | 336.83 | 23.96 | 320.17 | 23.96 |
Report: OccupantComfortDataSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 496.00000 | 21.06876 | 23.05355 | -0.5815 | 12.43625 |
February | 448.00000 | 21.06051 | 17.74211 | -0.6111 | 13.11431 |
March | 497.00000 | 21.16782 | 29.44400 | -0.4445 | 9.67246 |
April | 479.00000 | 21.95689 | 36.92997 | -0.1743 | 7.74847 |
May | 496.00000 | 23.29426 | 44.09786 | -0.7172 | 17.66465 |
June | 481.00000 | 23.88608 | 55.15750 | -0.3498 | 7.77146 |
July | 495.00000 | 23.88969 | 60.72844 | -0.2579 | 6.47526 |
August | 497.00000 | 23.88837 | 53.80898 | -0.2880 | 6.92928 |
September | 479.00000 | 23.86658 | 48.90778 | -0.3921 | 8.53756 |
October | 496.00000 | 23.25142 | 42.16308 | 0.26201 | 8.40845 |
November | 480.00000 | 21.41989 | 32.20149 | -0.3361 | 8.38185 |
December | 496.00000 | 21.06296 | 22.78448 | -0.5385 | 11.26051 |
Annual Sum or Average | 5840.00000 | 22.49274 | 39.04291 | -0.3678 | 9.85955 |
Minimum of Months | 448.00000 | 21.06051 | 17.74211 | -0.7172 | 6.47526 |
Maximum of Months | 497.00000 | 23.88969 | 60.72844 | 0.26201 | 17.66465 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 496.00000 | 21.35959 | 25.21960 | -0.4534 | 9.78151 |
February | 448.00000 | 21.37684 | 19.90974 | -0.4736 | 10.08855 |
March | 497.00000 | 21.71838 | 30.90485 | -0.2833 | 7.55468 |
April | 479.00000 | 22.54496 | 37.14388 | -0.0203 | 6.89429 |
May | 496.00000 | 23.67162 | 43.03315 | -0.5809 | 12.81955 |
June | 481.00000 | 23.87598 | 52.32971 | -0.3644 | 7.98087 |
July | 495.00000 | 23.88978 | 57.22503 | -0.2871 | 6.84528 |
August | 497.00000 | 23.87837 | 51.48861 | -0.3178 | 7.32715 |
September | 479.00000 | 23.86791 | 47.12129 | -0.3993 | 8.57611 |
October | 496.00000 | 23.62886 | 41.41664 | 0.34487 | 8.48053 |
November | 480.00000 | 22.09975 | 33.02724 | -0.1616 | 7.01048 |
December | 496.00000 | 21.49299 | 24.84907 | -0.3934 | 8.64574 |
Annual Sum or Average | 5840.00000 | 22.79174 | 38.75057 | -0.2815 | 8.49713 |
Minimum of Months | 448.00000 | 21.35959 | 19.90974 | -0.5809 | 6.84528 |
Maximum of Months | 497.00000 | 23.88978 | 57.22503 | 0.34487 | 12.81955 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 21.10973 | 22.66100 | -0.5293 | 11.12298 |
February | 336.00000 | 21.10965 | 17.10667 | -0.5493 | 11.48453 |
March | 379.00000 | 21.25827 | 28.39226 | -0.3899 | 8.67628 |
April | 360.00000 | 22.10275 | 35.33883 | -0.1206 | 7.36124 |
May | 375.00000 | 23.52003 | 42.81235 | -0.6287 | 14.65644 |
June | 366.00000 | 23.99219 | 54.06161 | -0.3186 | 7.43658 |
July | 369.00000 | 24.04312 | 60.13738 | -0.2203 | 6.33024 |
August | 379.00000 | 24.04739 | 52.93054 | -0.2546 | 6.79679 |
September | 360.00000 | 23.96178 | 48.02762 | -0.3641 | 8.17092 |
October | 371.00000 | 23.43743 | 41.35460 | 0.31174 | 8.57010 |
November | 360.00000 | 21.58684 | 31.24377 | -0.2755 | 7.76892 |
December | 369.00000 | 21.11158 | 21.97958 | -0.4905 | 10.11409 |
Annual Sum or Average | 4395.00000 | 22.61852 | 38.16177 | -0.3181 | 9.03379 |
Minimum of Months | 336.00000 | 21.10965 | 17.10667 | -0.6287 | 6.33024 |
Maximum of Months | 379.00000 | 24.04739 | 60.13738 | 0.31174 | 14.65644 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 21.10991 | 22.66012 | -0.5408 | 11.38516 |
February | 336.00000 | 21.10926 | 17.10652 | -0.5597 | 11.72838 |
March | 379.00000 | 21.23913 | 28.43192 | -0.4034 | 8.86538 |
April | 360.00000 | 22.05832 | 35.45472 | -0.1382 | 7.42635 |
May | 375.00000 | 23.45406 | 43.01182 | -0.6566 | 15.67058 |
June | 366.00000 | 23.99115 | 54.10820 | -0.3198 | 7.45343 |
July | 369.00000 | 24.04282 | 60.14532 | -0.2203 | 6.32878 |
August | 379.00000 | 24.04727 | 52.91988 | -0.2540 | 6.79094 |
September | 360.00000 | 23.95910 | 48.05681 | -0.3661 | 8.21190 |
October | 371.00000 | 23.39395 | 41.49605 | 0.29870 | 8.52322 |
November | 360.00000 | 21.52648 | 31.37305 | -0.2982 | 7.93015 |
December | 369.00000 | 21.11043 | 21.98037 | -0.5009 | 10.33014 |
Annual Sum or Average | 4395.00000 | 22.59854 | 38.22023 | -0.3289 | 9.21426 |
Minimum of Months | 336.00000 | 21.10926 | 17.10652 | -0.6566 | 6.32878 |
Maximum of Months | 379.00000 | 24.04727 | 60.14532 | 0.29870 | 15.67058 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 21.10974 | 22.66078 | -0.5554 | 11.72733 |
February | 336.00000 | 21.10993 | 17.10637 | -0.5739 | 12.07328 |
March | 379.00000 | 21.21375 | 28.48226 | -0.4210 | 9.13672 |
April | 360.00000 | 21.98593 | 35.64007 | -0.1641 | 7.50708 |
May | 375.00000 | 23.33876 | 43.37332 | -0.7038 | 17.37757 |
June | 366.00000 | 23.98531 | 54.38162 | -0.3268 | 7.54528 |
July | 369.00000 | 24.03857 | 60.44973 | -0.2251 | 6.35825 |
August | 379.00000 | 24.04302 | 53.11871 | -0.2595 | 6.83633 |
September | 360.00000 | 23.94842 | 48.33980 | -0.3744 | 8.35874 |
October | 371.00000 | 23.31943 | 41.75572 | 0.27737 | 8.42912 |
November | 360.00000 | 21.44583 | 31.55027 | -0.3270 | 8.15937 |
December | 369.00000 | 21.10951 | 21.98143 | -0.5145 | 10.62318 |
Annual Sum or Average | 4395.00000 | 22.56556 | 38.39582 | -0.3463 | 9.50667 |
Minimum of Months | 336.00000 | 21.10951 | 17.10637 | -0.7038 | 6.35825 |
Maximum of Months | 379.00000 | 24.04302 | 60.44973 | 0.27737 | 17.37757 |
Report: OccupantComfortDataSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.11000 | 24.12795 | -0.5971 | 12.72746 |
February | 308.00000 | 21.11000 | 18.53336 | -0.6143 | 13.07508 |
March | 348.00000 | 21.17977 | 30.00657 | -0.4598 | 9.80857 |
April | 330.00000 | 21.86923 | 37.33300 | -0.2124 | 7.72593 |
May | 344.00000 | 23.15056 | 45.25209 | -0.7874 | 20.33666 |
June | 336.00000 | 23.91234 | 56.11754 | -0.3569 | 7.89861 |
July | 338.00000 | 23.94850 | 61.98945 | -0.2540 | 6.52970 |
August | 348.00000 | 23.93280 | 54.40007 | -0.2923 | 7.05633 |
September | 330.00000 | 23.88337 | 49.76209 | -0.4039 | 8.78374 |
October | 340.00000 | 23.18623 | 43.46612 | 0.24214 | 8.23930 |
November | 330.00000 | 21.32686 | 33.17353 | -0.3815 | 8.78952 |
December | 338.00000 | 21.10980 | 23.31066 | -0.5544 | 11.51578 |
Annual Sum or Average | 4030.00000 | 22.48785 | 39.95188 | -0.3883 | 10.20413 |
Minimum of Months | 308.00000 | 21.10980 | 18.53336 | -0.7874 | 6.52970 |
Maximum of Months | 348.00000 | 23.94850 | 61.98945 | 0.24214 | 20.33666 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.10989 | 24.02998 | -0.5948 | 12.66055 |
February | 308.00000 | 21.10985 | 18.43642 | -0.6139 | 13.05822 |
March | 348.00000 | 21.17588 | 29.92707 | -0.4661 | 9.91680 |
April | 330.00000 | 21.84763 | 37.29854 | -0.2259 | 7.78543 |
May | 344.00000 | 23.11455 | 45.28474 | -0.8165 | 21.35847 |
June | 336.00000 | 23.91182 | 56.14648 | -0.3770 | 8.20230 |
July | 338.00000 | 23.94758 | 62.03716 | -0.2773 | 6.78181 |
August | 348.00000 | 23.93195 | 54.41401 | -0.3172 | 7.36404 |
September | 330.00000 | 23.88338 | 49.74956 | -0.4235 | 9.10891 |
October | 340.00000 | 23.17434 | 43.50253 | 0.22685 | 8.11274 |
November | 330.00000 | 21.31382 | 33.10597 | -0.3910 | 8.88963 |
December | 338.00000 | 21.10945 | 23.21496 | -0.5559 | 11.54622 |
Annual Sum or Average | 4030.00000 | 22.48036 | 39.92541 | -0.4018 | 10.39838 |
Minimum of Months | 308.00000 | 21.10945 | 18.43642 | -0.8165 | 6.78181 |
Maximum of Months | 348.00000 | 23.94758 | 62.03716 | 0.22685 | 21.35847 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.10979 | 24.03050 | -0.5985 | 12.75024 |
February | 308.00000 | 21.10982 | 18.43683 | -0.6182 | 13.16959 |
March | 348.00000 | 21.17119 | 29.93829 | -0.4723 | 10.02981 |
April | 330.00000 | 21.82181 | 37.35906 | -0.2366 | 7.85260 |
May | 344.00000 | 23.06299 | 45.45015 | -0.8404 | 22.25489 |
June | 336.00000 | 23.91068 | 56.24960 | -0.3806 | 8.26346 |
July | 338.00000 | 23.94711 | 62.14359 | -0.2799 | 6.81076 |
August | 348.00000 | 23.93162 | 54.47709 | -0.3199 | 7.39979 |
September | 330.00000 | 23.87922 | 49.84486 | -0.4279 | 9.20187 |
October | 340.00000 | 23.14041 | 43.61949 | 0.21593 | 8.07793 |
November | 330.00000 | 21.29719 | 33.13944 | -0.3992 | 8.99273 |
December | 338.00000 | 21.10968 | 23.21469 | -0.5605 | 11.65479 |
Annual Sum or Average | 4030.00000 | 22.46872 | 39.98889 | -0.4090 | 10.53907 |
Minimum of Months | 308.00000 | 21.10968 | 18.43683 | -0.8404 | 6.81076 |
Maximum of Months | 348.00000 | 23.94711 | 62.14359 | 0.21593 | 22.25489 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.10978 | 24.03031 | -0.6130 | 13.12142 |
February | 308.00000 | 21.10984 | 18.43654 | -0.6346 | 13.60491 |
March | 348.00000 | 21.15925 | 29.96236 | -0.4914 | 10.39904 |
April | 330.00000 | 21.76056 | 37.50322 | -0.2633 | 8.07905 |
May | 344.00000 | 22.93350 | 45.86693 | -0.8954 | 24.37111 |
June | 336.00000 | 23.90627 | 56.56639 | -0.3867 | 8.37613 |
July | 338.00000 | 23.94614 | 62.39691 | -0.2806 | 6.81620 |
August | 348.00000 | 23.93111 | 54.65933 | -0.3197 | 7.39981 |
September | 330.00000 | 23.86362 | 50.09315 | -0.4360 | 9.41358 |
October | 340.00000 | 23.05596 | 43.90534 | 0.19153 | 8.04625 |
November | 330.00000 | 21.26369 | 33.20615 | -0.4188 | 9.28348 |
December | 338.00000 | 21.10959 | 23.21482 | -0.5762 | 12.03256 |
Annual Sum or Average | 4030.00000 | 22.43997 | 40.15162 | -0.4262 | 10.91473 |
Minimum of Months | 308.00000 | 21.10959 | 18.43654 | -0.8954 | 6.81620 |
Maximum of Months | 348.00000 | 23.94614 | 62.39691 | 0.19153 | 24.37111 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.11000 | 23.86960 | -0.6763 | 14.87576 |
February | 308.00000 | 21.11000 | 18.28545 | -0.7040 | 15.59228 |
March | 348.00000 | 21.14255 | 29.78786 | -0.5561 | 11.83055 |
April | 330.00000 | 21.68701 | 37.48929 | -0.3246 | 8.94932 |
May | 344.00000 | 22.72497 | 46.35492 | -0.9968 | 28.62343 |
June | 336.00000 | 23.89387 | 57.35038 | -0.3948 | 8.56933 |
July | 338.00000 | 23.94782 | 62.60835 | -0.2621 | 6.61641 |
August | 348.00000 | 23.93332 | 54.51067 | -0.2937 | 7.09853 |
September | 330.00000 | 23.82149 | 50.36323 | -0.4451 | 9.85323 |
October | 340.00000 | 22.90973 | 44.11101 | 0.14802 | 8.15780 |
November | 330.00000 | 21.22943 | 33.06864 | -0.4677 | 10.23940 |
December | 338.00000 | 21.11000 | 23.06208 | -0.6363 | 13.59238 |
Annual Sum or Average | 4030.00000 | 22.39548 | 40.23762 | -0.4664 | 12.00033 |
Minimum of Months | 308.00000 | 21.11000 | 18.28545 | -0.9968 | 6.61641 |
Maximum of Months | 348.00000 | 23.94782 | 62.60835 | 0.14802 | 28.62343 |
Report: DXReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 |
March | 2180440.96 | 628197.91 | 1.00 | 1589175.60 | 591265.36 | 0.00 | 0.07 | 27-MAR-16:10 | 0.00 | 01-MAR-00:10 | 1241.02 | 27-MAR-16:10 | 901.70 | 27-MAR-16:10 | 339.32 | 27-MAR-16:10 | 356.29 | 27-MAR-16:10 | 0.00 | 01-MAR-00:10 |
April | 0.509803E+09 | 0.140236E+09 | 35.67 | 0.442959E+09 | 66844468.66 | 0.00 | 0.52 | 07-APR-13:00 | 0.00 | 01-APR-00:05 | 9813.50 | 07-APR-13:00 | 9021.04 | 07-APR-13:00 | 1802.86 | 08-APR-13:00 | 2703.43 | 07-APR-13:00 | 0.00 | 01-APR-00:05 |
May | 0.306867E+10 | 0.812249E+09 | 150.86 | 0.259774E+10 | 0.470931E+09 | 0.00 | 0.85 | 31-MAY-14:00 | 0.00 | 01-MAY-00:10 | 18596.08 | 31-MAY-14:00 | 15458.66 | 30-MAY-13:00 | 5649.62 | 31-MAY-13:30 | 4551.60 | 31-MAY-14:00 | 0.00 | 01-MAY-00:10 |
June | 0.167799E+11 | 0.419824E+10 | 424.47 | 0.110872E+11 | 0.569271E+10 | 0.00 | 1.00 | 15-JUN-07:03 | 0.00 | 01-JUN-00:10 | 49141.14 | 25-JUN-07:02 | 33486.95 | 20-JUN-07:02 | 23793.14 | 16-JUN-07:03 | 10959.18 | 19-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.307089E+11 | 0.742213E+10 | 496.53 | 0.187365E+11 | 0.119724E+11 | 0.00 | 1.00 | 01-JUL-07:03 | 0.00 | 01-JUL-00:05 | 50355.23 | 22-JUL-07:02 | 35266.26 | 12-JUL-07:02 | 28275.64 | 15-JUL-07:03 | 10856.29 | 10-JUL-07:02 | 0.00 | 01-JUL-00:05 |
August | 0.289289E+11 | 0.711353E+10 | 493.22 | 0.196782E+11 | 0.925074E+10 | 0.00 | 1.00 | 01-AUG-07:02 | 0.00 | 01-AUG-00:10 | 49897.53 | 17-AUG-07:02 | 35776.94 | 22-AUG-07:02 | 24152.88 | 17-AUG-07:03 | 10883.29 | 04-AUG-07:02 | 0.00 | 01-AUG-00:10 |
September | 0.128395E+11 | 0.321561E+10 | 369.40 | 0.906961E+10 | 0.376984E+10 | 0.00 | 1.00 | 01-SEP-07:02 | 0.00 | 01-SEP-00:05 | 49113.64 | 14-SEP-07:02 | 36521.86 | 04-SEP-07:02 | 22300.42 | 13-SEP-07:03 | 10617.20 | 01-SEP-07:02 | 0.00 | 01-SEP-00:05 |
October | 0.321779E+10 | 0.818153E+09 | 151.69 | 0.215232E+10 | 0.106547E+10 | 0.00 | 0.86 | 06-OCT-07:03 | 0.00 | 01-OCT-00:10 | 19203.62 | 06-OCT-07:03 | 12167.87 | 04-OCT-13:20 | 9556.99 | 06-OCT-07:03 | 4317.49 | 06-OCT-07:03 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.960556E+11 | 0.237208E+11 | 2122.84 | 0.637661E+11 | 0.322895E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.307089E+11 | 0.742213E+10 | 496.53 | 0.196782E+11 | 0.119724E+11 | 0.00 | 1.00 | 0.00 | 50355.23 | 36521.86 | 28275.64 | 10959.18 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 |
March | 7299983.60 | 2028834.21 | 3.33 | 5750610.73 | 1549372.87 | 0.00 | 0.15 | 27-MAR-16:10 | 0.00 | 01-MAR-00:10 | 1428.84 | 27-MAR-16:10 | 1061.15 | 27-MAR-21:10 | 377.33 | 27-MAR-16:10 | 394.60 | 27-MAR-16:10 | 0.00 | 01-MAR-00:10 |
April | 0.389809E+09 | 0.102512E+09 | 43.09 | 0.339338E+09 | 50470468.68 | 0.00 | 1.00 | 07-APR-20:01 | 0.00 | 01-APR-00:05 | 23038.38 | 07-APR-20:01 | 21350.88 | 16-APR-17:01 | 4446.43 | 07-APR-20:44 | 4920.86 | 07-APR-20:01 | 0.00 | 01-APR-00:05 |
May | 0.213222E+10 | 0.538803E+09 | 168.71 | 0.184188E+10 | 0.290345E+09 | 0.00 | 1.00 | 09-MAY-20:02 | 0.00 | 01-MAY-00:10 | 23471.55 | 30-MAY-20:02 | 22018.36 | 20-MAY-18:55 | 7016.87 | 30-MAY-20:58 | 4996.28 | 30-MAY-20:02 | 0.00 | 01-MAY-00:10 |
June | 0.968704E+10 | 0.237000E+10 | 437.17 | 0.665878E+10 | 0.302826E+10 | 0.00 | 1.00 | 01-JUN-20:22 | 0.00 | 01-JUN-00:10 | 24949.82 | 27-JUN-07:03 | 20537.96 | 01-JUN-20:28 | 12539.84 | 29-JUN-20:25 | 5610.13 | 19-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.158022E+11 | 0.377817E+10 | 498.02 | 0.101443E+11 | 0.565798E+10 | 0.00 | 1.00 | 01-JUL-07:03 | 0.00 | 01-JUL-00:05 | 25522.48 | 22-JUL-07:02 | 20844.88 | 12-JUL-07:02 | 9792.14 | 22-JUL-07:03 | 5575.04 | 10-JUL-07:02 | 0.00 | 01-JUL-00:05 |
August | 0.150444E+11 | 0.365411E+10 | 489.83 | 0.106649E+11 | 0.437951E+10 | 0.00 | 1.00 | 01-AUG-07:02 | 0.00 | 01-AUG-00:10 | 25242.34 | 17-AUG-07:02 | 22616.16 | 24-AUG-21:50 | 8702.68 | 17-AUG-07:03 | 5597.58 | 17-AUG-07:02 | 0.00 | 01-AUG-00:10 |
September | 0.745327E+10 | 0.182147E+10 | 372.39 | 0.546275E+10 | 0.199052E+10 | 0.00 | 1.00 | 01-SEP-07:02 | 0.00 | 01-SEP-00:05 | 25053.44 | 22-SEP-20:03 | 22149.26 | 10-SEP-17:08 | 13881.06 | 22-SEP-20:03 | 5414.37 | 01-SEP-07:02 | 0.00 | 01-SEP-00:05 |
October | 0.212519E+10 | 0.524058E+09 | 167.66 | 0.143856E+10 | 0.686634E+09 | 0.00 | 1.00 | 03-OCT-20:02 | 0.00 | 01-OCT-00:10 | 24419.00 | 24-OCT-20:10 | 19749.89 | 15-OCT-17:01 | 12727.34 | 24-OCT-20:10 | 5162.73 | 24-OCT-20:10 | 0.00 | 01-OCT-00:10 |
November | 4877918.31 | 1343001.47 | 2.97 | 4419720.81 | 458197.49 | 0.00 | 0.26 | 02-NOV-20:10 | 0.00 | 01-NOV-00:10 | 2256.99 | 02-NOV-20:10 | 2256.99 | 02-NOV-20:10 | 179.06 | 03-NOV-23:10 | 597.10 | 02-NOV-20:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.526464E+11 | 0.127925E+11 | 2183.18 | 0.365607E+11 | 0.160857E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.158022E+11 | 0.377817E+10 | 498.02 | 0.106649E+11 | 0.565798E+10 | 0.00 | 1.00 | 0.00 | 25522.48 | 22616.16 | 13881.06 | 5610.13 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_3:3 COOLING COIL
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 |
March | 1373133.11 | 387914.64 | 1.00 | 1012294.21 | 360838.90 | 0.00 | 0.08 | 27-MAR-16:10 | 0.00 | 01-MAR-00:10 | 765.68 | 27-MAR-16:10 | 563.03 | 27-MAR-16:10 | 202.64 | 27-MAR-16:10 | 215.32 | 27-MAR-16:10 | 0.00 | 01-MAR-00:10 |
April | 0.286704E+09 | 76849719.59 | 33.33 | 0.249777E+09 | 36927220.21 | 0.00 | 0.56 | 08-APR-12:10 | 0.00 | 01-APR-00:05 | 5700.71 | 08-APR-12:10 | 4933.34 | 07-APR-13:00 | 993.83 | 08-APR-13:00 | 1456.71 | 08-APR-12:10 | 0.00 | 01-APR-00:05 |
May | 0.144483E+10 | 0.376599E+09 | 136.36 | 0.125984E+10 | 0.184983E+09 | 0.00 | 0.84 | 31-MAY-14:00 | 0.00 | 01-MAY-00:10 | 9681.37 | 31-MAY-14:00 | 8389.77 | 30-MAY-13:00 | 3423.69 | 31-MAY-06:03 | 2342.85 | 30-MAY-13:00 | 0.00 | 01-MAY-00:10 |
June | 0.740549E+10 | 0.181945E+10 | 338.92 | 0.502289E+10 | 0.238261E+10 | 0.00 | 1.00 | 08-JUN-06:03 | 0.00 | 01-JUN-00:10 | 26465.09 | 25-JUN-07:02 | 19527.38 | 23-JUN-06:03 | 14594.76 | 16-JUN-06:03 | 5551.10 | 19-JUN-06:02 | 0.00 | 01-JUN-00:10 |
July | 0.125039E+11 | 0.296887E+10 | 362.64 | 0.781880E+10 | 0.468515E+10 | 0.00 | 1.00 | 01-JUL-06:03 | 0.00 | 01-JUL-00:05 | 26571.35 | 21-JUL-06:02 | 19921.93 | 12-JUL-06:02 | 14949.11 | 15-JUL-06:02 | 5632.92 | 09-JUL-07:04 | 0.00 | 01-JUL-00:05 |
August | 0.119226E+11 | 0.288475E+10 | 366.69 | 0.832526E+10 | 0.359737E+10 | 0.00 | 1.00 | 01-AUG-06:02 | 0.00 | 01-AUG-00:10 | 26741.34 | 06-AUG-07:02 | 20204.55 | 31-AUG-06:03 | 13953.21 | 06-AUG-07:03 | 5627.37 | 05-AUG-06:01 | 0.00 | 01-AUG-00:10 |
September | 0.550114E+10 | 0.135149E+10 | 289.32 | 0.397335E+10 | 0.152779E+10 | 0.00 | 1.00 | 01-SEP-06:02 | 0.00 | 01-SEP-00:05 | 26121.66 | 14-SEP-06:02 | 20707.82 | 04-SEP-07:02 | 13722.68 | 22-SEP-06:03 | 5511.26 | 01-SEP-06:02 | 0.00 | 01-SEP-00:05 |
October | 0.163707E+10 | 0.408637E+09 | 143.36 | 0.111288E+10 | 0.524190E+09 | 0.00 | 1.00 | 06-OCT-06:03 | 0.00 | 01-OCT-00:10 | 15161.21 | 06-OCT-06:03 | 7673.63 | 06-OCT-06:03 | 7487.58 | 06-OCT-06:03 | 3198.47 | 06-OCT-06:03 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.407032E+11 | 0.988703E+10 | 1671.62 | 0.277638E+11 | 0.129394E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.125039E+11 | 0.296887E+10 | 366.69 | 0.832526E+10 | 0.468515E+10 | 0.00 | 1.00 | 0.00 | 26741.34 | 20707.82 | 14949.11 | 5632.92 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_4:4 COOLING COIL
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 |
March | 602251.65 | 171134.31 | 0.83 | 443336.01 | 158915.64 | 0.00 | 0.05 | 27-MAR-16:10 | 0.00 | 01-MAR-00:10 | 473.32 | 27-MAR-16:10 | 347.73 | 27-MAR-16:10 | 125.58 | 27-MAR-16:10 | 134.18 | 27-MAR-16:10 | 0.00 | 01-MAR-00:10 |
April | 0.265963E+09 | 71578530.65 | 31.33 | 0.232004E+09 | 33959703.57 | 0.00 | 0.54 | 08-APR-12:10 | 0.00 | 01-APR-00:05 | 5534.40 | 08-APR-12:10 | 4759.00 | 07-APR-13:00 | 1031.35 | 08-APR-13:00 | 1420.47 | 08-APR-12:10 | 0.00 | 01-APR-00:05 |
May | 0.140059E+10 | 0.365480E+09 | 132.36 | 0.122047E+10 | 0.180115E+09 | 0.00 | 0.83 | 31-MAY-14:00 | 0.00 | 01-MAY-00:10 | 9650.60 | 31-MAY-14:00 | 8355.09 | 30-MAY-13:00 | 3303.81 | 31-MAY-06:03 | 2336.42 | 30-MAY-13:00 | 0.00 | 01-MAY-00:10 |
June | 0.737086E+10 | 0.181234E+10 | 337.58 | 0.499915E+10 | 0.237171E+10 | 0.00 | 1.00 | 08-JUN-06:03 | 0.00 | 01-JUN-00:10 | 26533.68 | 25-JUN-07:02 | 19754.19 | 23-JUN-06:03 | 14634.88 | 16-JUN-06:03 | 5565.59 | 19-JUN-06:02 | 0.00 | 01-JUN-00:10 |
July | 0.125066E+11 | 0.297068E+10 | 362.81 | 0.782311E+10 | 0.468352E+10 | 0.00 | 1.00 | 01-JUL-06:03 | 0.00 | 01-JUL-00:05 | 26646.20 | 21-JUL-06:02 | 19995.00 | 12-JUL-06:02 | 14985.49 | 15-JUL-06:02 | 5647.60 | 09-JUL-07:04 | 0.00 | 01-JUL-00:05 |
August | 0.119418E+11 | 0.288998E+10 | 367.01 | 0.834224E+10 | 0.359955E+10 | 0.00 | 1.00 | 01-AUG-06:02 | 0.00 | 01-AUG-00:10 | 26814.93 | 06-AUG-07:02 | 20299.18 | 31-AUG-06:03 | 13956.68 | 06-AUG-07:03 | 5642.13 | 05-AUG-06:01 | 0.00 | 01-AUG-00:10 |
September | 0.548037E+10 | 0.134696E+10 | 288.11 | 0.395891E+10 | 0.152146E+10 | 0.00 | 1.00 | 01-SEP-06:02 | 0.00 | 01-SEP-00:05 | 26191.01 | 14-SEP-06:02 | 20788.04 | 04-SEP-07:02 | 13763.30 | 22-SEP-06:03 | 5525.85 | 01-SEP-06:02 | 0.00 | 01-SEP-00:05 |
October | 0.157496E+10 | 0.393781E+09 | 137.28 | 0.107065E+10 | 0.504305E+09 | 0.00 | 1.00 | 06-OCT-06:03 | 0.00 | 01-OCT-00:10 | 14865.30 | 06-OCT-06:03 | 7515.72 | 06-OCT-06:03 | 7349.58 | 06-OCT-06:03 | 3136.29 | 06-OCT-06:03 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.405418E+11 | 0.985098E+10 | 1657.32 | 0.276470E+11 | 0.128948E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.125066E+11 | 0.297068E+10 | 367.01 | 0.834224E+10 | 0.468352E+10 | 0.00 | 1.00 | 0.00 | 26814.93 | 20788.04 | 14985.49 | 5647.60 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_5:5 COOLING COIL
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 |
March | 108348.19 | 30964.16 | 0.33 | 79437.45 | 28910.73 | 0.00 | 0.02 | 27-MAR-16:10 | 0.00 | 01-MAR-00:10 | 180.37 | 27-MAR-16:10 | 132.24 | 27-MAR-16:10 | 48.13 | 27-MAR-16:10 | 51.55 | 27-MAR-16:10 | 0.00 | 01-MAR-00:10 |
April | 0.232426E+09 | 62960389.11 | 29.00 | 0.203215E+09 | 29210647.13 | 0.00 | 0.52 | 08-APR-12:10 | 0.00 | 01-APR-00:05 | 5198.05 | 08-APR-12:10 | 4451.01 | 07-APR-13:00 | 963.10 | 08-APR-13:00 | 1343.94 | 08-APR-12:10 | 0.00 | 01-APR-00:05 |
May | 0.130015E+10 | 0.340125E+09 | 123.19 | 0.112984E+10 | 0.170306E+09 | 0.00 | 0.83 | 31-MAY-14:00 | 0.00 | 01-MAY-00:10 | 9461.89 | 31-MAY-14:00 | 8193.61 | 30-MAY-13:00 | 2865.93 | 31-MAY-13:00 | 2298.29 | 30-MAY-13:00 | 0.00 | 01-MAY-00:10 |
June | 0.713139E+10 | 0.175762E+10 | 334.45 | 0.482010E+10 | 0.231128E+10 | 0.00 | 1.00 | 15-JUN-06:03 | 0.00 | 01-JUN-00:10 | 26338.75 | 25-JUN-07:02 | 17681.40 | 23-JUN-06:03 | 14574.12 | 16-JUN-06:03 | 5527.33 | 19-JUN-06:02 | 0.00 | 01-JUN-00:10 |
July | 0.122599E+11 | 0.291611E+10 | 362.50 | 0.763789E+10 | 0.462202E+10 | 0.00 | 1.00 | 01-JUL-06:03 | 0.00 | 01-JUL-00:05 | 26452.78 | 21-JUL-06:02 | 19726.12 | 12-JUL-06:02 | 14919.59 | 15-JUL-06:02 | 5609.05 | 09-JUL-07:04 | 0.00 | 01-JUL-00:05 |
August | 0.117128E+11 | 0.283790E+10 | 366.61 | 0.815554E+10 | 0.355729E+10 | 0.00 | 1.00 | 01-AUG-06:02 | 0.00 | 01-AUG-00:10 | 26620.35 | 06-AUG-07:02 | 18479.57 | 22-AUG-06:02 | 13991.64 | 06-AUG-07:03 | 5603.43 | 05-AUG-06:01 | 0.00 | 01-AUG-00:10 |
September | 0.527321E+10 | 0.129839E+10 | 283.56 | 0.379381E+10 | 0.147940E+10 | 0.00 | 1.00 | 01-SEP-06:02 | 0.00 | 01-SEP-00:05 | 26003.86 | 14-SEP-06:02 | 20534.10 | 04-SEP-07:02 | 13712.39 | 22-SEP-06:03 | 5487.52 | 01-SEP-06:02 | 0.00 | 01-SEP-00:05 |
October | 0.145298E+10 | 0.364167E+09 | 131.56 | 0.986679E+09 | 0.466304E+09 | 0.00 | 1.00 | 06-OCT-06:03 | 0.00 | 01-OCT-00:10 | 12856.92 | 06-OCT-06:03 | 6449.72 | 06-OCT-06:03 | 6407.19 | 06-OCT-06:03 | 2713.97 | 06-OCT-06:03 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.393630E+11 | 0.957731E+10 | 1631.20 | 0.267271E+11 | 0.126358E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.122599E+11 | 0.291611E+10 | 366.61 | 0.815554E+10 | 0.462202E+10 | 0.00 | 1.00 | 0.00 | 26620.35 | 20534.10 | 14919.59 | 5609.05 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_6:6 COOLING COIL
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 |
March | 46.44 | 13.57 | 0.17 | 33.24 | 13.20 | 0.00 | 0.00 | 27-MAR-16:10 | 0.00 | 01-MAR-00:10 | 0.08 | 27-MAR-16:10 | 0.06 | 27-MAR-16:10 | 0.02 | 27-MAR-16:10 | 0.02 | 27-MAR-16:10 | 0.00 | 01-MAR-00:10 |
April | 0.363230E+09 | 0.100731E+09 | 25.67 | 0.312187E+09 | 51042723.17 | 0.00 | 0.49 | 08-APR-12:00 | 0.00 | 01-APR-00:05 | 8800.74 | 08-APR-12:00 | 7638.71 | 07-APR-13:00 | 1620.26 | 08-APR-13:00 | 2347.36 | 07-APR-13:00 | 0.00 | 01-APR-00:05 |
May | 0.211406E+10 | 0.562716E+09 | 103.36 | 0.179660E+10 | 0.317461E+09 | 0.00 | 0.84 | 31-MAY-07:03 | 0.00 | 01-MAY-00:10 | 17618.47 | 31-MAY-14:10 | 15033.96 | 30-MAY-13:00 | 5762.36 | 31-MAY-13:00 | 4355.02 | 30-MAY-13:00 | 0.00 | 01-MAY-00:10 |
June | 0.123275E+11 | 0.308909E+10 | 317.61 | 0.811605E+10 | 0.421147E+10 | 0.00 | 1.00 | 15-JUN-07:03 | 0.00 | 01-JUN-00:10 | 47845.35 | 25-JUN-08:62 | 31598.05 | 23-JUN-07:03 | 25074.48 | 25-JUN-08:62 | 10434.58 | 19-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.217803E+11 | 0.525239E+10 | 350.67 | 0.131888E+11 | 0.859151E+10 | 0.00 | 1.00 | 01-JUL-07:03 | 0.00 | 01-JUL-00:05 | 47895.23 | 09-JUL-08:62 | 35498.44 | 12-JUL-07:02 | 27599.40 | 24-JUL-07:03 | 10408.17 | 09-JUL-08:03 | 0.00 | 01-JUL-00:05 |
August | 0.211415E+11 | 0.520431E+10 | 360.68 | 0.143756E+11 | 0.676586E+10 | 0.00 | 1.00 | 01-AUG-07:02 | 0.00 | 01-AUG-00:10 | 47273.51 | 06-AUG-08:62 | 33755.20 | 22-AUG-07:02 | 27965.10 | 06-AUG-08:62 | 10357.12 | 04-AUG-07:02 | 0.00 | 01-AUG-00:10 |
September | 0.916567E+10 | 0.229526E+10 | 269.19 | 0.642995E+10 | 0.273572E+10 | 0.00 | 1.00 | 01-SEP-07:02 | 0.00 | 01-SEP-00:05 | 46731.39 | 14-SEP-07:02 | 36166.61 | 04-SEP-08:62 | 20826.21 | 14-SEP-07:02 | 10120.30 | 01-SEP-07:02 | 0.00 | 01-SEP-00:05 |
October | 0.235065E+10 | 0.600096E+09 | 113.25 | 0.155186E+10 | 0.798793E+09 | 0.00 | 0.92 | 06-OCT-07:03 | 0.00 | 01-OCT-00:10 | 19855.48 | 06-OCT-07:03 | 11371.48 | 04-OCT-13:00 | 9858.60 | 06-OCT-07:03 | 4382.86 | 06-OCT-07:03 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.692429E+11 | 0.171046E+11 | 1540.59 | 0.457711E+11 | 0.234719E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.217803E+11 | 0.525239E+10 | 360.68 | 0.143756E+11 | 0.859151E+10 | 0.00 | 1.00 | 0.00 | 47895.23 | 36166.61 | 27965.10 | 10434.58 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_7:7 COOLING COIL
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 |
March | 53.41 | 15.30 | 0.17 | 37.87 | 15.53 | 0.00 | 0.00 | 27-MAR-16:10 | 0.00 | 01-MAR-00:10 | 0.09 | 27-MAR-16:10 | 0.06 | 27-MAR-16:10 | 0.03 | 27-MAR-16:10 | 0.03 | 27-MAR-16:10 | 0.00 | 01-MAR-00:10 |
April | 0.174816E+09 | 47764128.92 | 24.83 | 0.150750E+09 | 24065917.91 | 0.00 | 0.48 | 08-APR-12:00 | 0.00 | 01-APR-00:05 | 4419.53 | 08-APR-12:00 | 3810.48 | 07-APR-13:00 | 802.88 | 08-APR-12:50 | 1160.49 | 08-APR-12:00 | 0.00 | 01-APR-00:05 |
May | 0.105586E+10 | 0.276340E+09 | 99.69 | 0.897959E+09 | 0.157903E+09 | 0.00 | 0.84 | 31-MAY-14:10 | 0.00 | 01-MAY-00:10 | 9050.29 | 31-MAY-14:10 | 7753.77 | 30-MAY-13:00 | 2939.72 | 31-MAY-13:00 | 2205.57 | 30-MAY-13:00 | 0.00 | 01-MAY-00:10 |
June | 0.629115E+10 | 0.155109E+10 | 315.75 | 0.415370E+10 | 0.213745E+10 | 0.00 | 1.00 | 15-JUN-07:03 | 0.00 | 01-JUN-00:10 | 24702.02 | 25-JUN-08:62 | 16166.37 | 20-JUN-07:02 | 12990.67 | 25-JUN-08:62 | 5291.88 | 19-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.111720E+11 | 0.265088E+10 | 350.65 | 0.678659E+10 | 0.438546E+10 | 0.00 | 1.00 | 02-JUL-08:62 | 0.00 | 01-JUL-00:05 | 24733.35 | 09-JUL-08:62 | 18330.38 | 12-JUL-07:02 | 14235.24 | 24-JUL-07:03 | 5278.37 | 09-JUL-08:03 | 0.00 | 01-JUL-00:05 |
August | 0.108430E+11 | 0.262621E+10 | 361.01 | 0.739284E+10 | 0.345021E+10 | 0.00 | 1.00 | 01-AUG-07:02 | 0.00 | 01-AUG-00:10 | 24406.48 | 06-AUG-08:62 | 17463.72 | 22-AUG-07:02 | 14430.79 | 06-AUG-08:62 | 5252.57 | 04-AUG-07:02 | 0.00 | 01-AUG-00:10 |
September | 0.468679E+10 | 0.115416E+10 | 268.92 | 0.329751E+10 | 0.138927E+10 | 0.00 | 1.00 | 01-SEP-07:02 | 0.00 | 01-SEP-00:05 | 24112.85 | 14-SEP-07:02 | 18647.47 | 04-SEP-08:62 | 10728.35 | 14-SEP-07:02 | 5131.95 | 01-SEP-07:02 | 0.00 | 01-SEP-00:05 |
October | 0.116256E+10 | 0.291780E+09 | 110.56 | 0.769649E+09 | 0.392911E+09 | 0.00 | 0.81 | 06-OCT-07:03 | 0.00 | 01-OCT-00:10 | 8805.83 | 06-OCT-07:03 | 5846.74 | 04-OCT-13:00 | 4387.65 | 06-OCT-07:03 | 1973.12 | 06-OCT-07:03 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.353863E+11 | 0.859823E+10 | 1531.58 | 0.234490E+11 | 0.119373E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.111720E+11 | 0.265088E+10 | 361.01 | 0.739284E+10 | 0.438546E+10 | 0.00 | 1.00 | 0.00 | 24733.35 | 18647.47 | 14430.79 | 5291.88 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_8:8 COOLING COIL
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 0.165807E+09 | 45383281.83 | 24.50 | 0.142869E+09 | 22938087.75 | 0.00 | 0.47 | 08-APR-12:00 | 0.00 | 01-APR-00:05 | 4311.64 | 08-APR-12:00 | 3717.15 | 07-APR-13:00 | 784.07 | 08-APR-12:50 | 1134.99 | 08-APR-12:00 | 0.00 | 01-APR-00:05 |
May | 0.101622E+10 | 0.266278E+09 | 96.36 | 0.861805E+09 | 0.154414E+09 | 0.00 | 0.83 | 31-MAY-14:10 | 0.00 | 01-MAY-00:10 | 8973.89 | 31-MAY-14:10 | 7667.07 | 30-MAY-13:00 | 2925.41 | 31-MAY-13:00 | 2185.98 | 30-MAY-13:00 | 0.00 | 01-MAY-00:10 |
June | 0.620493E+10 | 0.153102E+10 | 315.23 | 0.408942E+10 | 0.211550E+10 | 0.00 | 1.00 | 15-JUN-07:03 | 0.00 | 01-JUN-00:10 | 24613.76 | 25-JUN-08:62 | 16064.56 | 20-JUN-07:02 | 12985.21 | 25-JUN-08:62 | 5273.79 | 19-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.110851E+11 | 0.263108E+10 | 350.49 | 0.672047E+10 | 0.436467E+10 | 0.00 | 1.00 | 02-JUL-08:62 | 0.00 | 01-JUL-00:05 | 24646.14 | 09-JUL-08:62 | 18229.78 | 12-JUL-07:02 | 14196.17 | 24-JUL-07:03 | 5260.37 | 09-JUL-08:03 | 0.00 | 01-JUL-00:05 |
August | 0.107659E+11 | 0.260809E+10 | 360.72 | 0.732785E+10 | 0.343801E+10 | 0.00 | 1.00 | 01-AUG-07:02 | 0.00 | 01-AUG-00:10 | 24322.45 | 06-AUG-08:62 | 17390.81 | 22-AUG-07:02 | 14389.67 | 06-AUG-08:62 | 5234.61 | 04-AUG-07:02 | 0.00 | 01-AUG-00:10 |
September | 0.462204E+10 | 0.113888E+10 | 267.76 | 0.324637E+10 | 0.137567E+10 | 0.00 | 1.00 | 01-SEP-07:02 | 0.00 | 01-SEP-00:05 | 24031.06 | 14-SEP-07:02 | 18550.70 | 04-SEP-08:62 | 10739.40 | 14-SEP-07:02 | 5114.34 | 01-SEP-07:02 | 0.00 | 01-SEP-00:05 |
October | 0.111903E+10 | 0.281090E+09 | 106.61 | 0.740580E+09 | 0.378452E+09 | 0.00 | 0.77 | 04-OCT-13:00 | 0.00 | 01-OCT-00:10 | 7979.41 | 04-OCT-13:00 | 5767.64 | 04-OCT-13:00 | 3960.53 | 06-OCT-07:03 | 1917.99 | 04-OCT-13:00 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.349790E+11 | 0.850181E+10 | 1521.66 | 0.231294E+11 | 0.118497E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.110851E+11 | 0.263108E+10 | 360.72 | 0.732785E+10 | 0.436467E+10 | 0.00 | 1.00 | 0.00 | 24646.14 | 18550.70 | 14389.67 | 5273.79 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_9:9 COOLING COIL
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 0.145429E+09 | 39983981.08 | 21.83 | 0.125139E+09 | 20290058.33 | 0.00 | 0.44 | 08-APR-12:00 | 0.00 | 01-APR-00:05 | 4072.58 | 08-APR-12:00 | 3534.71 | 07-APR-13:00 | 734.62 | 08-APR-12:50 | 1079.53 | 07-APR-13:00 | 0.00 | 01-APR-00:05 |
May | 0.928080E+09 | 0.243835E+09 | 90.17 | 0.783242E+09 | 0.144838E+09 | 0.00 | 0.82 | 31-MAY-14:10 | 0.00 | 01-MAY-00:10 | 8801.40 | 31-MAY-14:10 | 7506.20 | 30-MAY-13:00 | 2881.21 | 31-MAY-13:00 | 2147.81 | 30-MAY-13:00 | 0.00 | 01-MAY-00:10 |
June | 0.598561E+10 | 0.148019E+10 | 310.24 | 0.393707E+10 | 0.204854E+10 | 0.00 | 1.00 | 15-JUN-07:03 | 0.00 | 01-JUN-00:10 | 24490.53 | 25-JUN-08:62 | 15875.88 | 20-JUN-07:02 | 13063.17 | 25-JUN-08:62 | 5251.42 | 19-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.109295E+11 | 0.259633E+10 | 350.92 | 0.661259E+10 | 0.431693E+10 | 0.00 | 1.00 | 02-JUL-08:62 | 0.00 | 01-JUL-00:05 | 24527.89 | 09-JUL-08:62 | 18047.35 | 12-JUL-07:02 | 14168.58 | 24-JUL-07:03 | 5238.29 | 09-JUL-08:03 | 0.00 | 01-JUL-00:05 |
August | 0.106425E+11 | 0.257911E+10 | 360.84 | 0.723199E+10 | 0.341047E+10 | 0.00 | 1.00 | 01-AUG-07:02 | 0.00 | 01-AUG-00:10 | 24216.54 | 06-AUG-08:62 | 17295.54 | 22-AUG-07:02 | 14345.44 | 06-AUG-08:62 | 5212.36 | 04-AUG-07:02 | 0.00 | 01-AUG-00:10 |
September | 0.448805E+10 | 0.110659E+10 | 262.81 | 0.314778E+10 | 0.134027E+10 | 0.00 | 1.00 | 01-SEP-07:02 | 0.00 | 01-SEP-00:05 | 23925.30 | 14-SEP-07:02 | 18390.54 | 04-SEP-08:62 | 10819.76 | 14-SEP-07:02 | 5092.02 | 01-SEP-07:02 | 0.00 | 01-SEP-00:05 |
October | 0.102652E+10 | 0.258314E+09 | 98.33 | 0.679571E+09 | 0.346945E+09 | 0.00 | 0.76 | 04-OCT-13:00 | 0.00 | 01-OCT-00:10 | 7821.88 | 04-OCT-13:00 | 5642.69 | 04-OCT-13:00 | 2619.89 | 05-OCT-15:00 | 1885.53 | 04-OCT-13:00 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.341457E+11 | 0.830434E+10 | 1495.14 | 0.225174E+11 | 0.116283E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.109295E+11 | 0.259633E+10 | 360.84 | 0.723199E+10 | 0.431693E+10 | 0.00 | 1.00 | 0.00 | 24527.89 | 18390.54 | 14345.44 | 5251.42 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_10:10 COOLING COIL
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 0.136517E+09 | 37708861.28 | 16.67 | 0.118017E+09 | 18500189.01 | 0.00 | 0.44 | 08-APR-12:00 | 0.00 | 01-APR-00:05 | 4295.54 | 08-APR-12:00 | 3699.52 | 07-APR-13:00 | 731.85 | 08-APR-12:40 | 1140.46 | 08-APR-12:00 | 0.00 | 01-APR-00:05 |
May | 0.887824E+09 | 0.234060E+09 | 80.33 | 0.750417E+09 | 0.137407E+09 | 0.00 | 0.80 | 30-MAY-13:00 | 0.00 | 01-MAY-00:10 | 8937.08 | 31-MAY-14:10 | 7910.22 | 30-MAY-13:00 | 2908.08 | 31-MAY-13:00 | 2267.42 | 30-MAY-13:00 | 0.00 | 01-MAY-00:10 |
June | 0.584480E+10 | 0.145775E+10 | 292.66 | 0.388449E+10 | 0.196031E+10 | 0.00 | 1.00 | 15-JUN-11:40 | 0.00 | 01-JUN-00:10 | 26539.20 | 25-JUN-08:62 | 14726.26 | 20-JUN-07:02 | 14841.33 | 25-JUN-08:62 | 5667.46 | 19-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.114348E+11 | 0.273107E+10 | 350.65 | 0.698833E+10 | 0.444651E+10 | 0.00 | 1.00 | 02-JUL-08:62 | 0.00 | 01-JUL-00:05 | 26856.73 | 22-JUL-07:02 | 16783.78 | 12-JUL-07:02 | 15652.64 | 22-JUL-07:02 | 5651.28 | 09-JUL-08:03 | 0.00 | 01-JUL-00:05 |
August | 0.113720E+11 | 0.276265E+10 | 361.74 | 0.780882E+10 | 0.356322E+10 | 0.00 | 1.00 | 01-AUG-07:02 | 0.00 | 01-AUG-00:10 | 26617.76 | 17-AUG-07:02 | 18762.09 | 22-AUG-07:02 | 15641.78 | 06-AUG-08:62 | 5626.19 | 05-AUG-07:01 | 0.00 | 01-AUG-00:10 |
September | 0.459577E+10 | 0.113520E+10 | 247.07 | 0.326601E+10 | 0.132976E+10 | 0.00 | 1.00 | 01-SEP-07:02 | 0.00 | 01-SEP-00:05 | 26162.58 | 14-SEP-07:02 | 19179.67 | 04-SEP-08:62 | 13365.63 | 14-SEP-07:02 | 5512.50 | 01-SEP-07:02 | 0.00 | 01-SEP-00:05 |
October | 0.100354E+10 | 0.252669E+09 | 84.81 | 0.673169E+09 | 0.330369E+09 | 0.00 | 0.74 | 04-OCT-13:00 | 0.00 | 01-OCT-00:10 | 8260.41 | 04-OCT-13:00 | 6029.25 | 04-OCT-13:00 | 2661.33 | 05-OCT-13:00 | 2000.13 | 04-OCT-13:00 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.352753E+11 | 0.861111E+10 | 1433.92 | 0.234893E+11 | 0.117861E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.114348E+11 | 0.276265E+10 | 361.74 | 0.780882E+10 | 0.444651E+10 | 0.00 | 1.00 | 0.00 | 26856.73 | 19179.67 | 15652.64 | 5667.46 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 84.23 | 55.15 | 29.08 | 87.40 | 79.10 | 0.00 | 0.00 | 0.00 |
February | 111.10 | 73.54 | 37.56 | 118.05 | 77.69 | 0.00 | 0.00 | 0.00 |
March | 100.23 | 55.63 | 44.60 | 113.45 | 55.46 | 0.00 | 0.00 | 0.00 |
April | 77.77 | 30.75 | 47.02 | 91.39 | 41.19 | 0.00 | 0.00 | 0.00 |
May | 68.16 | 14.22 | 53.94 | 84.30 | 27.13 | 0.00 | 0.00 | 0.00 |
June | 63.96 | 9.78 | 54.19 | 89.53 | 14.76 | 0.00 | 0.00 | 0.00 |
July | 67.05 | 11.65 | 55.40 | 103.85 | 7.28 | 0.00 | 0.00 | 0.00 |
August | 89.53 | 33.21 | 56.32 | 138.60 | 10.93 | 0.00 | 0.00 | 0.00 |
September | 97.15 | 50.25 | 46.90 | 133.56 | 22.80 | 0.00 | 0.00 | 0.00 |
October | 133.08 | 83.45 | 49.63 | 171.43 | 40.92 | 0.00 | 0.00 | 0.00 |
November | 92.28 | 55.42 | 36.86 | 103.83 | 57.19 | 0.00 | 0.00 | 0.00 |
December | 91.29 | 64.81 | 26.48 | 98.87 | 71.91 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 89.55 | 44.68 | 44.88 | 111.21 | 41.99 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 63.96 | 9.78 | 26.48 | 84.30 | 7.28 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 133.08 | 83.45 | 56.32 | 171.43 | 79.10 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 84.23 | 55.15 | 29.08 | 87.40 | 79.10 | 0.00 | 0.00 | 0.00 |
February | 111.10 | 73.54 | 37.56 | 118.05 | 77.69 | 0.00 | 0.00 | 0.00 |
March | 100.23 | 55.63 | 44.60 | 113.45 | 55.46 | 0.00 | 0.00 | 0.00 |
April | 77.77 | 30.75 | 47.02 | 91.39 | 41.19 | 0.00 | 0.00 | 0.00 |
May | 68.16 | 14.22 | 53.94 | 84.30 | 27.13 | 0.00 | 0.00 | 0.00 |
June | 63.96 | 9.78 | 54.19 | 89.53 | 14.76 | 0.00 | 0.00 | 0.00 |
July | 67.05 | 11.65 | 55.40 | 103.85 | 7.28 | 0.00 | 0.00 | 0.00 |
August | 89.53 | 33.21 | 56.32 | 138.60 | 10.93 | 0.00 | 0.00 | 0.00 |
September | 97.15 | 50.25 | 46.90 | 133.56 | 22.80 | 0.00 | 0.00 | 0.00 |
October | 133.08 | 83.45 | 49.63 | 171.43 | 40.92 | 0.00 | 0.00 | 0.00 |
November | 92.28 | 55.42 | 36.86 | 103.83 | 57.19 | 0.00 | 0.00 | 0.00 |
December | 91.29 | 64.81 | 26.48 | 98.87 | 71.91 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 89.55 | 44.68 | 44.88 | 111.21 | 41.99 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 63.96 | 9.78 | 26.48 | 84.30 | 7.28 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 133.08 | 83.45 | 56.32 | 171.43 | 79.10 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 84.23 | 55.15 | 29.08 | 87.40 | 79.10 | 0.00 | 0.00 | 0.00 |
February | 111.10 | 73.54 | 37.56 | 118.05 | 77.69 | 0.00 | 0.00 | 0.00 |
March | 100.23 | 55.63 | 44.60 | 113.45 | 55.46 | 0.00 | 0.00 | 0.00 |
April | 77.77 | 30.75 | 47.02 | 91.39 | 41.19 | 0.00 | 0.00 | 0.00 |
May | 68.16 | 14.22 | 53.94 | 84.30 | 27.13 | 0.00 | 0.00 | 0.00 |
June | 63.96 | 9.78 | 54.19 | 89.53 | 14.76 | 0.00 | 0.00 | 0.00 |
July | 67.05 | 11.65 | 55.40 | 103.85 | 7.28 | 0.00 | 0.00 | 0.00 |
August | 89.53 | 33.21 | 56.32 | 138.60 | 10.93 | 0.00 | 0.00 | 0.00 |
September | 97.15 | 50.25 | 46.90 | 133.56 | 22.80 | 0.00 | 0.00 | 0.00 |
October | 133.08 | 83.45 | 49.63 | 171.43 | 40.92 | 0.00 | 0.00 | 0.00 |
November | 92.28 | 55.42 | 36.86 | 103.83 | 57.19 | 0.00 | 0.00 | 0.00 |
December | 91.29 | 64.81 | 26.48 | 98.87 | 71.91 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 89.55 | 44.68 | 44.88 | 111.21 | 41.99 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 63.96 | 9.78 | 26.48 | 84.30 | 7.28 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 133.08 | 83.45 | 56.32 | 171.43 | 79.10 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 84.23 | 55.15 | 29.08 | 87.40 | 79.10 | 0.00 | 0.00 | 0.00 |
February | 111.10 | 73.54 | 37.56 | 118.05 | 77.69 | 0.00 | 0.00 | 0.00 |
March | 100.23 | 55.63 | 44.60 | 113.45 | 55.46 | 0.00 | 0.00 | 0.00 |
April | 77.77 | 30.75 | 47.02 | 91.39 | 41.19 | 0.00 | 0.00 | 0.00 |
May | 68.16 | 14.22 | 53.94 | 84.30 | 27.13 | 0.00 | 0.00 | 0.00 |
June | 63.96 | 9.78 | 54.19 | 89.53 | 14.76 | 0.00 | 0.00 | 0.00 |
July | 67.05 | 11.65 | 55.40 | 103.85 | 7.28 | 0.00 | 0.00 | 0.00 |
August | 89.53 | 33.21 | 56.32 | 138.60 | 10.93 | 0.00 | 0.00 | 0.00 |
September | 97.15 | 50.25 | 46.90 | 133.56 | 22.80 | 0.00 | 0.00 | 0.00 |
October | 133.08 | 83.45 | 49.63 | 171.43 | 40.92 | 0.00 | 0.00 | 0.00 |
November | 92.28 | 55.42 | 36.86 | 103.83 | 57.19 | 0.00 | 0.00 | 0.00 |
December | 91.29 | 64.81 | 26.48 | 98.87 | 71.91 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 89.55 | 44.68 | 44.88 | 111.21 | 41.99 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 63.96 | 9.78 | 26.48 | 84.30 | 7.28 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 133.08 | 83.45 | 56.32 | 171.43 | 79.10 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.26 | 66.30 | 34.95 | 105.47 | 93.92 | 0.00 | 0.00 | 0.00 |
February | 133.55 | 88.40 | 45.15 | 142.40 | 92.27 | 0.00 | 0.00 | 0.00 |
March | 120.49 | 66.87 | 53.62 | 136.81 | 65.87 | 0.00 | 0.00 | 0.00 |
April | 93.50 | 36.97 | 56.53 | 110.18 | 49.01 | 0.00 | 0.00 | 0.00 |
May | 81.94 | 17.09 | 64.85 | 101.56 | 32.35 | 0.00 | 0.00 | 0.00 |
June | 76.89 | 11.75 | 65.14 | 107.65 | 17.66 | 0.00 | 0.00 | 0.00 |
July | 80.60 | 14.00 | 66.60 | 124.70 | 8.78 | 0.00 | 0.00 | 0.00 |
August | 107.63 | 39.92 | 67.71 | 166.43 | 13.16 | 0.00 | 0.00 | 0.00 |
September | 116.78 | 60.41 | 56.38 | 160.58 | 27.28 | 0.00 | 0.00 | 0.00 |
October | 159.98 | 100.32 | 59.66 | 206.34 | 48.83 | 0.00 | 0.00 | 0.00 |
November | 110.94 | 66.62 | 44.31 | 125.14 | 68.06 | 0.00 | 0.00 | 0.00 |
December | 109.75 | 77.91 | 31.83 | 119.21 | 85.46 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 107.65 | 53.71 | 53.95 | 133.89 | 49.98 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 76.89 | 11.75 | 31.83 | 101.56 | 8.78 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 159.98 | 100.32 | 67.71 | 206.34 | 93.92 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.26 | 66.30 | 34.95 | 105.47 | 93.92 | 0.00 | 0.00 | 0.00 |
February | 133.55 | 88.40 | 45.15 | 142.40 | 92.27 | 0.00 | 0.00 | 0.00 |
March | 120.49 | 66.87 | 53.62 | 136.81 | 65.87 | 0.00 | 0.00 | 0.00 |
April | 93.50 | 36.97 | 56.53 | 110.18 | 49.01 | 0.00 | 0.00 | 0.00 |
May | 81.94 | 17.09 | 64.85 | 101.56 | 32.35 | 0.00 | 0.00 | 0.00 |
June | 76.89 | 11.75 | 65.14 | 107.65 | 17.66 | 0.00 | 0.00 | 0.00 |
July | 80.60 | 14.00 | 66.60 | 124.70 | 8.78 | 0.00 | 0.00 | 0.00 |
August | 107.63 | 39.92 | 67.71 | 166.43 | 13.16 | 0.00 | 0.00 | 0.00 |
September | 116.78 | 60.41 | 56.38 | 160.58 | 27.28 | 0.00 | 0.00 | 0.00 |
October | 159.98 | 100.32 | 59.66 | 206.34 | 48.83 | 0.00 | 0.00 | 0.00 |
November | 110.94 | 66.62 | 44.31 | 125.14 | 68.06 | 0.00 | 0.00 | 0.00 |
December | 109.75 | 77.91 | 31.83 | 119.21 | 85.46 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 107.65 | 53.71 | 53.95 | 133.89 | 49.98 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 76.89 | 11.75 | 31.83 | 101.56 | 8.78 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 159.98 | 100.32 | 67.71 | 206.34 | 93.92 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 84.23 | 55.15 | 29.08 | 86.47 | 82.98 | 0.00 | 0.00 | 0.00 |
February | 111.10 | 73.54 | 37.56 | 116.78 | 81.70 | 0.00 | 0.00 | 0.00 |
March | 100.23 | 55.63 | 44.60 | 112.18 | 59.39 | 0.00 | 0.00 | 0.00 |
April | 77.77 | 30.75 | 47.02 | 89.99 | 44.60 | 0.00 | 0.00 | 0.00 |
May | 68.16 | 14.22 | 53.94 | 82.86 | 29.02 | 0.00 | 0.00 | 0.00 |
June | 63.96 | 9.78 | 54.19 | 89.23 | 15.17 | 0.00 | 0.00 | 0.00 |
July | 67.05 | 11.65 | 55.40 | 103.81 | 7.46 | 0.00 | 0.00 | 0.00 |
August | 89.53 | 33.21 | 56.32 | 138.65 | 11.00 | 0.00 | 0.00 | 0.00 |
September | 97.15 | 50.25 | 46.90 | 133.31 | 23.17 | 0.00 | 0.00 | 0.00 |
October | 133.08 | 83.45 | 49.63 | 170.40 | 42.64 | 0.00 | 0.00 | 0.00 |
November | 92.28 | 55.42 | 36.86 | 102.51 | 60.88 | 0.00 | 0.00 | 0.00 |
December | 91.29 | 64.81 | 26.48 | 97.92 | 75.81 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 89.55 | 44.68 | 44.88 | 110.36 | 44.27 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 63.96 | 9.78 | 26.48 | 82.86 | 7.46 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 133.08 | 83.45 | 56.32 | 170.40 | 82.98 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 84.23 | 55.15 | 29.08 | 86.47 | 82.98 | 0.00 | 0.00 | 0.00 |
February | 111.10 | 73.54 | 37.56 | 116.78 | 81.70 | 0.00 | 0.00 | 0.00 |
March | 100.23 | 55.63 | 44.60 | 112.18 | 59.39 | 0.00 | 0.00 | 0.00 |
April | 77.77 | 30.75 | 47.02 | 89.99 | 44.60 | 0.00 | 0.00 | 0.00 |
May | 68.16 | 14.22 | 53.94 | 82.86 | 29.02 | 0.00 | 0.00 | 0.00 |
June | 63.96 | 9.78 | 54.19 | 89.23 | 15.17 | 0.00 | 0.00 | 0.00 |
July | 67.05 | 11.65 | 55.40 | 103.81 | 7.46 | 0.00 | 0.00 | 0.00 |
August | 89.53 | 33.21 | 56.32 | 138.65 | 11.00 | 0.00 | 0.00 | 0.00 |
September | 97.15 | 50.25 | 46.90 | 133.31 | 23.17 | 0.00 | 0.00 | 0.00 |
October | 133.08 | 83.45 | 49.63 | 170.40 | 42.64 | 0.00 | 0.00 | 0.00 |
November | 92.28 | 55.42 | 36.86 | 102.51 | 60.88 | 0.00 | 0.00 | 0.00 |
December | 91.29 | 64.81 | 26.48 | 97.92 | 75.81 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 89.55 | 44.68 | 44.88 | 110.36 | 44.27 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 63.96 | 9.78 | 26.48 | 82.86 | 7.46 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 133.08 | 83.45 | 56.32 | 170.40 | 82.98 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.26 | 66.30 | 34.95 | 104.37 | 98.49 | 0.00 | 0.00 | 0.00 |
February | 133.55 | 88.40 | 45.15 | 140.90 | 96.99 | 0.00 | 0.00 | 0.00 |
March | 120.49 | 66.87 | 53.62 | 135.31 | 70.48 | 0.00 | 0.00 | 0.00 |
April | 93.50 | 36.97 | 56.53 | 108.53 | 53.01 | 0.00 | 0.00 | 0.00 |
May | 81.94 | 17.09 | 64.85 | 99.87 | 34.57 | 0.00 | 0.00 | 0.00 |
June | 76.89 | 11.75 | 65.14 | 107.30 | 18.15 | 0.00 | 0.00 | 0.00 |
July | 80.60 | 14.00 | 66.60 | 124.66 | 8.99 | 0.00 | 0.00 | 0.00 |
August | 107.63 | 39.92 | 67.71 | 166.49 | 13.26 | 0.00 | 0.00 | 0.00 |
September | 116.78 | 60.41 | 56.38 | 160.31 | 27.72 | 0.00 | 0.00 | 0.00 |
October | 159.98 | 100.32 | 59.66 | 205.15 | 50.86 | 0.00 | 0.00 | 0.00 |
November | 110.94 | 66.62 | 44.31 | 123.58 | 72.40 | 0.00 | 0.00 | 0.00 |
December | 109.75 | 77.91 | 31.83 | 118.08 | 90.05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 107.65 | 53.71 | 53.95 | 132.90 | 52.66 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 76.89 | 11.75 | 31.83 | 99.87 | 8.99 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 159.98 | 100.32 | 67.71 | 205.15 | 98.49 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 84.23 | 55.15 | 29.08 | 86.63 | 80.82 | 0.00 | 0.00 | 0.00 |
February | 111.10 | 73.54 | 37.56 | 116.90 | 79.81 | 0.00 | 0.00 | 0.00 |
March | 100.23 | 55.63 | 44.60 | 112.42 | 57.70 | 0.00 | 0.00 | 0.00 |
April | 77.77 | 30.75 | 47.02 | 90.31 | 43.42 | 0.00 | 0.00 | 0.00 |
May | 68.16 | 14.22 | 53.94 | 83.05 | 29.09 | 0.00 | 0.00 | 0.00 |
June | 63.96 | 9.78 | 54.19 | 89.05 | 16.26 | 0.00 | 0.00 | 0.00 |
July | 67.05 | 11.65 | 55.40 | 103.41 | 8.85 | 0.00 | 0.00 | 0.00 |
August | 89.53 | 33.21 | 56.32 | 138.26 | 12.49 | 0.00 | 0.00 | 0.00 |
September | 97.15 | 50.25 | 46.90 | 133.23 | 24.41 | 0.00 | 0.00 | 0.00 |
October | 133.08 | 83.45 | 49.63 | 170.65 | 42.77 | 0.00 | 0.00 | 0.00 |
November | 92.28 | 55.42 | 36.86 | 102.90 | 59.24 | 0.00 | 0.00 | 0.00 |
December | 91.29 | 64.81 | 26.48 | 98.09 | 73.90 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 89.55 | 44.68 | 44.88 | 110.43 | 43.86 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 63.96 | 9.78 | 26.48 | 83.05 | 8.85 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 133.08 | 83.45 | 56.32 | 170.65 | 80.82 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 84.23 | 55.15 | 29.08 | 86.63 | 80.82 | 0.00 | 0.00 | 0.00 |
February | 111.10 | 73.54 | 37.56 | 116.90 | 79.81 | 0.00 | 0.00 | 0.00 |
March | 100.23 | 55.63 | 44.60 | 112.42 | 57.70 | 0.00 | 0.00 | 0.00 |
April | 77.77 | 30.75 | 47.02 | 90.31 | 43.42 | 0.00 | 0.00 | 0.00 |
May | 68.16 | 14.22 | 53.94 | 83.05 | 29.09 | 0.00 | 0.00 | 0.00 |
June | 63.96 | 9.78 | 54.19 | 89.05 | 16.26 | 0.00 | 0.00 | 0.00 |
July | 67.05 | 11.65 | 55.40 | 103.41 | 8.85 | 0.00 | 0.00 | 0.00 |
August | 89.53 | 33.21 | 56.32 | 138.26 | 12.49 | 0.00 | 0.00 | 0.00 |
September | 97.15 | 50.25 | 46.90 | 133.23 | 24.41 | 0.00 | 0.00 | 0.00 |
October | 133.08 | 83.45 | 49.63 | 170.65 | 42.77 | 0.00 | 0.00 | 0.00 |
November | 92.28 | 55.42 | 36.86 | 102.90 | 59.24 | 0.00 | 0.00 | 0.00 |
December | 91.29 | 64.81 | 26.48 | 98.09 | 73.90 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 89.55 | 44.68 | 44.88 | 110.43 | 43.86 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 63.96 | 9.78 | 26.48 | 83.05 | 8.85 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 133.08 | 83.45 | 56.32 | 170.65 | 80.82 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 100.70 | 65.94 | 34.76 | 104.01 | 95.42 | 0.00 | 0.00 | 0.00 |
February | 132.82 | 87.92 | 44.91 | 140.27 | 94.25 | 0.00 | 0.00 | 0.00 |
March | 119.83 | 66.51 | 53.32 | 134.86 | 68.12 | 0.00 | 0.00 | 0.00 |
April | 92.99 | 36.77 | 56.22 | 108.31 | 51.35 | 0.00 | 0.00 | 0.00 |
May | 81.49 | 17.00 | 64.49 | 99.55 | 34.46 | 0.00 | 0.00 | 0.00 |
June | 76.47 | 11.69 | 64.78 | 106.51 | 19.32 | 0.00 | 0.00 | 0.00 |
July | 80.16 | 13.92 | 66.24 | 123.51 | 10.57 | 0.00 | 0.00 | 0.00 |
August | 107.04 | 39.70 | 67.34 | 165.14 | 14.93 | 0.00 | 0.00 | 0.00 |
September | 116.15 | 60.08 | 56.07 | 159.35 | 29.01 | 0.00 | 0.00 | 0.00 |
October | 159.11 | 99.77 | 59.34 | 204.32 | 50.73 | 0.00 | 0.00 | 0.00 |
November | 110.33 | 66.26 | 44.07 | 123.38 | 70.07 | 0.00 | 0.00 | 0.00 |
December | 109.15 | 77.49 | 31.66 | 117.64 | 87.33 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 107.07 | 53.41 | 53.65 | 132.26 | 51.89 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 76.47 | 11.69 | 31.66 | 99.55 | 10.57 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 159.11 | 99.77 | 67.34 | 204.32 | 95.42 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 84.23 | 55.15 | 29.08 | 86.76 | 79.90 | 0.00 | 0.00 | 0.00 |
February | 111.10 | 73.54 | 37.56 | 117.03 | 79.00 | 0.00 | 0.00 | 0.00 |
March | 100.23 | 55.63 | 44.60 | 112.59 | 56.94 | 0.00 | 0.00 | 0.00 |
April | 77.77 | 30.75 | 47.02 | 90.54 | 42.73 | 0.00 | 0.00 | 0.00 |
May | 68.16 | 14.22 | 53.94 | 83.32 | 28.61 | 0.00 | 0.00 | 0.00 |
June | 63.96 | 9.78 | 54.19 | 89.07 | 16.21 | 0.00 | 0.00 | 0.00 |
July | 67.05 | 11.65 | 55.40 | 103.40 | 8.89 | 0.00 | 0.00 | 0.00 |
August | 89.53 | 33.21 | 56.32 | 138.24 | 12.56 | 0.00 | 0.00 | 0.00 |
September | 97.15 | 50.25 | 46.90 | 133.25 | 24.35 | 0.00 | 0.00 | 0.00 |
October | 133.08 | 83.45 | 49.63 | 170.81 | 42.36 | 0.00 | 0.00 | 0.00 |
November | 92.28 | 55.42 | 36.86 | 103.16 | 58.36 | 0.00 | 0.00 | 0.00 |
December | 91.29 | 64.81 | 26.48 | 98.21 | 73.09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 89.55 | 44.68 | 44.88 | 110.55 | 43.38 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 63.96 | 9.78 | 26.48 | 83.32 | 8.89 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 133.08 | 83.45 | 56.32 | 170.81 | 79.90 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 84.23 | 55.15 | 29.08 | 86.76 | 79.90 | 0.00 | 0.00 | 0.00 |
February | 111.10 | 73.54 | 37.56 | 117.03 | 79.00 | 0.00 | 0.00 | 0.00 |
March | 100.23 | 55.63 | 44.60 | 112.59 | 56.94 | 0.00 | 0.00 | 0.00 |
April | 77.77 | 30.75 | 47.02 | 90.54 | 42.73 | 0.00 | 0.00 | 0.00 |
May | 68.16 | 14.22 | 53.94 | 83.32 | 28.61 | 0.00 | 0.00 | 0.00 |
June | 63.96 | 9.78 | 54.19 | 89.07 | 16.21 | 0.00 | 0.00 | 0.00 |
July | 67.05 | 11.65 | 55.40 | 103.40 | 8.89 | 0.00 | 0.00 | 0.00 |
August | 89.53 | 33.21 | 56.32 | 138.24 | 12.56 | 0.00 | 0.00 | 0.00 |
September | 97.15 | 50.25 | 46.90 | 133.25 | 24.35 | 0.00 | 0.00 | 0.00 |
October | 133.08 | 83.45 | 49.63 | 170.81 | 42.36 | 0.00 | 0.00 | 0.00 |
November | 92.28 | 55.42 | 36.86 | 103.16 | 58.36 | 0.00 | 0.00 | 0.00 |
December | 91.29 | 64.81 | 26.48 | 98.21 | 73.09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 89.55 | 44.68 | 44.88 | 110.55 | 43.38 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 63.96 | 9.78 | 26.48 | 83.32 | 8.89 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 133.08 | 83.45 | 56.32 | 170.81 | 79.90 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 100.70 | 65.94 | 34.76 | 104.16 | 94.33 | 0.00 | 0.00 | 0.00 |
February | 132.82 | 87.92 | 44.91 | 140.44 | 93.29 | 0.00 | 0.00 | 0.00 |
March | 119.83 | 66.51 | 53.32 | 135.06 | 67.22 | 0.00 | 0.00 | 0.00 |
April | 92.99 | 36.77 | 56.22 | 108.60 | 50.53 | 0.00 | 0.00 | 0.00 |
May | 81.49 | 17.00 | 64.49 | 99.87 | 33.89 | 0.00 | 0.00 | 0.00 |
June | 76.47 | 11.69 | 64.78 | 106.54 | 19.27 | 0.00 | 0.00 | 0.00 |
July | 80.16 | 13.92 | 66.24 | 123.50 | 10.61 | 0.00 | 0.00 | 0.00 |
August | 107.04 | 39.70 | 67.34 | 165.12 | 15.01 | 0.00 | 0.00 | 0.00 |
September | 116.15 | 60.08 | 56.07 | 159.37 | 28.94 | 0.00 | 0.00 | 0.00 |
October | 159.11 | 99.77 | 59.34 | 204.51 | 50.24 | 0.00 | 0.00 | 0.00 |
November | 110.33 | 66.26 | 44.07 | 123.69 | 69.04 | 0.00 | 0.00 | 0.00 |
December | 109.15 | 77.49 | 31.66 | 117.79 | 86.37 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 107.07 | 53.41 | 53.65 | 132.41 | 51.32 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 76.47 | 11.69 | 31.66 | 99.87 | 10.61 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 159.11 | 99.77 | 67.34 | 204.51 | 94.33 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 84.23 | 55.15 | 29.08 | 86.92 | 79.12 | 0.00 | 0.00 | 0.00 |
February | 111.10 | 73.54 | 37.56 | 117.22 | 78.28 | 0.00 | 0.00 | 0.00 |
March | 100.23 | 55.63 | 44.60 | 112.80 | 56.26 | 0.00 | 0.00 | 0.00 |
April | 77.77 | 30.75 | 47.02 | 90.87 | 42.03 | 0.00 | 0.00 | 0.00 |
May | 68.16 | 14.22 | 53.94 | 83.78 | 27.94 | 0.00 | 0.00 | 0.00 |
June | 63.96 | 9.78 | 54.19 | 89.21 | 15.96 | 0.00 | 0.00 | 0.00 |
July | 67.05 | 11.65 | 55.40 | 103.51 | 8.67 | 0.00 | 0.00 | 0.00 |
August | 89.53 | 33.21 | 56.32 | 138.34 | 12.33 | 0.00 | 0.00 | 0.00 |
September | 97.15 | 50.25 | 46.90 | 133.36 | 24.06 | 0.00 | 0.00 | 0.00 |
October | 133.08 | 83.45 | 49.63 | 171.06 | 41.83 | 0.00 | 0.00 | 0.00 |
November | 92.28 | 55.42 | 36.86 | 103.48 | 57.54 | 0.00 | 0.00 | 0.00 |
December | 91.29 | 64.81 | 26.48 | 98.36 | 72.39 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 89.55 | 44.68 | 44.88 | 110.76 | 42.83 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 63.96 | 9.78 | 26.48 | 83.78 | 8.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 133.08 | 83.45 | 56.32 | 171.06 | 79.12 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 84.23 | 55.15 | 29.08 | 86.92 | 79.12 | 0.00 | 0.00 | 0.00 |
February | 111.10 | 73.54 | 37.56 | 117.22 | 78.28 | 0.00 | 0.00 | 0.00 |
March | 100.23 | 55.63 | 44.60 | 112.80 | 56.26 | 0.00 | 0.00 | 0.00 |
April | 77.77 | 30.75 | 47.02 | 90.87 | 42.03 | 0.00 | 0.00 | 0.00 |
May | 68.16 | 14.22 | 53.94 | 83.78 | 27.94 | 0.00 | 0.00 | 0.00 |
June | 63.96 | 9.78 | 54.19 | 89.21 | 15.96 | 0.00 | 0.00 | 0.00 |
July | 67.05 | 11.65 | 55.40 | 103.51 | 8.67 | 0.00 | 0.00 | 0.00 |
August | 89.53 | 33.21 | 56.32 | 138.34 | 12.33 | 0.00 | 0.00 | 0.00 |
September | 97.15 | 50.25 | 46.90 | 133.36 | 24.06 | 0.00 | 0.00 | 0.00 |
October | 133.08 | 83.45 | 49.63 | 171.06 | 41.83 | 0.00 | 0.00 | 0.00 |
November | 92.28 | 55.42 | 36.86 | 103.48 | 57.54 | 0.00 | 0.00 | 0.00 |
December | 91.29 | 64.81 | 26.48 | 98.36 | 72.39 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 89.55 | 44.68 | 44.88 | 110.76 | 42.83 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 63.96 | 9.78 | 26.48 | 83.78 | 8.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 133.08 | 83.45 | 56.32 | 171.06 | 79.12 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 100.70 | 65.94 | 34.76 | 104.35 | 93.40 | 0.00 | 0.00 | 0.00 |
February | 132.82 | 87.92 | 44.91 | 140.67 | 92.44 | 0.00 | 0.00 | 0.00 |
March | 119.83 | 66.51 | 53.32 | 135.33 | 66.42 | 0.00 | 0.00 | 0.00 |
April | 92.99 | 36.77 | 56.22 | 108.99 | 49.71 | 0.00 | 0.00 | 0.00 |
May | 81.49 | 17.00 | 64.49 | 100.42 | 33.10 | 0.00 | 0.00 | 0.00 |
June | 76.47 | 11.69 | 64.78 | 106.70 | 18.97 | 0.00 | 0.00 | 0.00 |
July | 80.16 | 13.92 | 66.24 | 123.64 | 10.36 | 0.00 | 0.00 | 0.00 |
August | 107.04 | 39.70 | 67.34 | 165.24 | 14.74 | 0.00 | 0.00 | 0.00 |
September | 116.15 | 60.08 | 56.07 | 159.50 | 28.60 | 0.00 | 0.00 | 0.00 |
October | 159.11 | 99.77 | 59.34 | 204.82 | 49.62 | 0.00 | 0.00 | 0.00 |
November | 110.33 | 66.26 | 44.07 | 124.07 | 68.07 | 0.00 | 0.00 | 0.00 |
December | 109.15 | 77.49 | 31.66 | 117.97 | 85.53 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 107.07 | 53.41 | 53.65 | 132.66 | 50.68 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 76.47 | 11.69 | 31.66 | 100.42 | 10.36 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 159.11 | 99.77 | 67.34 | 204.82 | 93.40 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 84.23 | 55.15 | 29.08 | 87.62 | 76.80 | 0.00 | 0.00 | 0.00 |
February | 111.10 | 73.54 | 37.56 | 118.12 | 76.16 | 0.00 | 0.00 | 0.00 |
March | 100.23 | 55.63 | 44.60 | 113.54 | 54.43 | 0.00 | 0.00 | 0.00 |
April | 77.77 | 30.75 | 47.02 | 91.65 | 40.40 | 0.00 | 0.00 | 0.00 |
May | 68.16 | 14.22 | 53.94 | 84.58 | 26.57 | 0.00 | 0.00 | 0.00 |
June | 63.96 | 9.78 | 54.19 | 89.28 | 15.22 | 0.00 | 0.00 | 0.00 |
July | 67.05 | 11.65 | 55.40 | 103.38 | 8.03 | 0.00 | 0.00 | 0.00 |
August | 89.53 | 33.21 | 56.32 | 138.24 | 11.66 | 0.00 | 0.00 | 0.00 |
September | 97.15 | 50.25 | 46.90 | 133.43 | 23.30 | 0.00 | 0.00 | 0.00 |
October | 133.08 | 83.45 | 49.63 | 171.54 | 40.72 | 0.00 | 0.00 | 0.00 |
November | 92.28 | 55.42 | 36.86 | 104.22 | 55.74 | 0.00 | 0.00 | 0.00 |
December | 91.29 | 64.81 | 26.48 | 99.02 | 70.41 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 89.55 | 44.68 | 44.88 | 111.23 | 41.42 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 63.96 | 9.78 | 26.48 | 84.58 | 8.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 133.08 | 83.45 | 56.32 | 171.54 | 76.80 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 84.23 | 55.15 | 29.08 | 87.62 | 76.80 | 0.00 | 0.00 | 0.00 |
February | 111.10 | 73.54 | 37.56 | 118.12 | 76.16 | 0.00 | 0.00 | 0.00 |
March | 100.23 | 55.63 | 44.60 | 113.54 | 54.43 | 0.00 | 0.00 | 0.00 |
April | 77.77 | 30.75 | 47.02 | 91.65 | 40.40 | 0.00 | 0.00 | 0.00 |
May | 68.16 | 14.22 | 53.94 | 84.58 | 26.57 | 0.00 | 0.00 | 0.00 |
June | 63.96 | 9.78 | 54.19 | 89.28 | 15.22 | 0.00 | 0.00 | 0.00 |
July | 67.05 | 11.65 | 55.40 | 103.38 | 8.03 | 0.00 | 0.00 | 0.00 |
August | 89.53 | 33.21 | 56.32 | 138.24 | 11.66 | 0.00 | 0.00 | 0.00 |
September | 97.15 | 50.25 | 46.90 | 133.43 | 23.30 | 0.00 | 0.00 | 0.00 |
October | 133.08 | 83.45 | 49.63 | 171.54 | 40.72 | 0.00 | 0.00 | 0.00 |
November | 92.28 | 55.42 | 36.86 | 104.22 | 55.74 | 0.00 | 0.00 | 0.00 |
December | 91.29 | 64.81 | 26.48 | 99.02 | 70.41 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 89.55 | 44.68 | 44.88 | 111.23 | 41.42 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 63.96 | 9.78 | 26.48 | 84.58 | 8.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 133.08 | 83.45 | 56.32 | 171.54 | 76.80 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 84.23 | 55.15 | 29.08 | 87.62 | 76.80 | 0.00 | 0.00 | 0.00 |
February | 111.10 | 73.54 | 37.56 | 118.12 | 76.16 | 0.00 | 0.00 | 0.00 |
March | 100.23 | 55.63 | 44.60 | 113.54 | 54.43 | 0.00 | 0.00 | 0.00 |
April | 77.77 | 30.75 | 47.02 | 91.65 | 40.40 | 0.00 | 0.00 | 0.00 |
May | 68.16 | 14.22 | 53.94 | 84.58 | 26.57 | 0.00 | 0.00 | 0.00 |
June | 63.96 | 9.78 | 54.19 | 89.28 | 15.22 | 0.00 | 0.00 | 0.00 |
July | 67.05 | 11.65 | 55.40 | 103.38 | 8.03 | 0.00 | 0.00 | 0.00 |
August | 89.53 | 33.21 | 56.32 | 138.24 | 11.66 | 0.00 | 0.00 | 0.00 |
September | 97.15 | 50.25 | 46.90 | 133.43 | 23.30 | 0.00 | 0.00 | 0.00 |
October | 133.08 | 83.45 | 49.63 | 171.54 | 40.72 | 0.00 | 0.00 | 0.00 |
November | 92.28 | 55.42 | 36.86 | 104.22 | 55.74 | 0.00 | 0.00 | 0.00 |
December | 91.29 | 64.81 | 26.48 | 99.02 | 70.41 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 89.55 | 44.68 | 44.88 | 111.23 | 41.42 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 63.96 | 9.78 | 26.48 | 84.58 | 8.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 133.08 | 83.45 | 56.32 | 171.54 | 76.80 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 84.23 | 55.15 | 29.08 | 87.62 | 76.80 | 0.00 | 0.00 | 0.00 |
February | 111.10 | 73.54 | 37.56 | 118.12 | 76.16 | 0.00 | 0.00 | 0.00 |
March | 100.23 | 55.63 | 44.60 | 113.54 | 54.43 | 0.00 | 0.00 | 0.00 |
April | 77.77 | 30.75 | 47.02 | 91.65 | 40.40 | 0.00 | 0.00 | 0.00 |
May | 68.16 | 14.22 | 53.94 | 84.58 | 26.57 | 0.00 | 0.00 | 0.00 |
June | 63.96 | 9.78 | 54.19 | 89.28 | 15.22 | 0.00 | 0.00 | 0.00 |
July | 67.05 | 11.65 | 55.40 | 103.38 | 8.03 | 0.00 | 0.00 | 0.00 |
August | 89.53 | 33.21 | 56.32 | 138.24 | 11.66 | 0.00 | 0.00 | 0.00 |
September | 97.15 | 50.25 | 46.90 | 133.43 | 23.30 | 0.00 | 0.00 | 0.00 |
October | 133.08 | 83.45 | 49.63 | 171.54 | 40.72 | 0.00 | 0.00 | 0.00 |
November | 92.28 | 55.42 | 36.86 | 104.22 | 55.74 | 0.00 | 0.00 | 0.00 |
December | 91.29 | 64.81 | 26.48 | 99.02 | 70.41 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 89.55 | 44.68 | 44.88 | 111.23 | 41.42 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 63.96 | 9.78 | 26.48 | 84.58 | 8.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 133.08 | 83.45 | 56.32 | 171.54 | 76.80 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 100.70 | 65.94 | 34.76 | 105.16 | 90.70 | 0.00 | 0.00 | 0.00 |
February | 132.82 | 87.92 | 44.91 | 141.70 | 89.97 | 0.00 | 0.00 | 0.00 |
March | 119.83 | 66.51 | 53.32 | 136.17 | 64.29 | 0.00 | 0.00 | 0.00 |
April | 92.99 | 36.77 | 56.22 | 109.89 | 47.79 | 0.00 | 0.00 | 0.00 |
May | 81.49 | 17.00 | 64.49 | 101.36 | 31.49 | 0.00 | 0.00 | 0.00 |
June | 76.47 | 11.69 | 64.78 | 106.78 | 18.10 | 0.00 | 0.00 | 0.00 |
July | 80.16 | 13.92 | 66.24 | 123.47 | 9.60 | 0.00 | 0.00 | 0.00 |
August | 107.04 | 39.70 | 67.34 | 165.10 | 13.94 | 0.00 | 0.00 | 0.00 |
September | 116.15 | 60.08 | 56.07 | 159.57 | 27.69 | 0.00 | 0.00 | 0.00 |
October | 159.11 | 99.77 | 59.34 | 205.35 | 48.31 | 0.00 | 0.00 | 0.00 |
November | 110.33 | 66.26 | 44.07 | 124.92 | 65.96 | 0.00 | 0.00 | 0.00 |
December | 109.15 | 77.49 | 31.66 | 118.73 | 83.23 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 107.07 | 53.41 | 53.65 | 133.20 | 49.02 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 76.47 | 11.69 | 31.66 | 101.36 | 9.60 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 159.11 | 99.77 | 67.34 | 205.35 | 90.70 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 100.70 | 65.94 | 34.76 | 105.16 | 90.70 | 0.00 | 0.00 | 0.00 |
February | 132.82 | 87.92 | 44.91 | 141.70 | 89.97 | 0.00 | 0.00 | 0.00 |
March | 119.83 | 66.51 | 53.32 | 136.17 | 64.29 | 0.00 | 0.00 | 0.00 |
April | 92.99 | 36.77 | 56.22 | 109.89 | 47.79 | 0.00 | 0.00 | 0.00 |
May | 81.49 | 17.00 | 64.49 | 101.36 | 31.49 | 0.00 | 0.00 | 0.00 |
June | 76.47 | 11.69 | 64.78 | 106.78 | 18.10 | 0.00 | 0.00 | 0.00 |
July | 80.16 | 13.92 | 66.24 | 123.47 | 9.60 | 0.00 | 0.00 | 0.00 |
August | 107.04 | 39.70 | 67.34 | 165.10 | 13.94 | 0.00 | 0.00 | 0.00 |
September | 116.15 | 60.08 | 56.07 | 159.57 | 27.69 | 0.00 | 0.00 | 0.00 |
October | 159.11 | 99.77 | 59.34 | 205.35 | 48.31 | 0.00 | 0.00 | 0.00 |
November | 110.33 | 66.26 | 44.07 | 124.92 | 65.96 | 0.00 | 0.00 | 0.00 |
December | 109.15 | 77.49 | 31.66 | 118.73 | 83.23 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 107.07 | 53.41 | 53.65 | 133.20 | 49.02 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 76.47 | 11.69 | 31.66 | 101.36 | 9.60 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 159.11 | 99.77 | 67.34 | 205.35 | 90.70 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 84.23 | 55.15 | 29.08 | 87.33 | 77.24 | 0.00 | 0.00 | 0.00 |
February | 111.10 | 73.54 | 37.56 | 117.77 | 76.52 | 0.00 | 0.00 | 0.00 |
March | 100.23 | 55.63 | 44.60 | 113.24 | 54.55 | 0.00 | 0.00 | 0.00 |
April | 77.77 | 30.75 | 47.02 | 91.49 | 40.32 | 0.00 | 0.00 | 0.00 |
May | 68.16 | 14.22 | 53.94 | 84.61 | 26.32 | 0.00 | 0.00 | 0.00 |
June | 63.96 | 9.78 | 54.19 | 89.29 | 15.02 | 0.00 | 0.00 | 0.00 |
July | 67.05 | 11.65 | 55.40 | 103.47 | 7.77 | 0.00 | 0.00 | 0.00 |
August | 89.53 | 33.21 | 56.32 | 138.30 | 11.37 | 0.00 | 0.00 | 0.00 |
September | 97.15 | 50.25 | 46.90 | 133.35 | 23.07 | 0.00 | 0.00 | 0.00 |
October | 133.08 | 83.45 | 49.63 | 171.36 | 40.50 | 0.00 | 0.00 | 0.00 |
November | 92.28 | 55.42 | 36.86 | 104.05 | 55.77 | 0.00 | 0.00 | 0.00 |
December | 91.29 | 64.81 | 26.48 | 98.77 | 70.68 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 89.55 | 44.68 | 44.88 | 111.10 | 41.40 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 63.96 | 9.78 | 26.48 | 84.61 | 7.77 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 133.08 | 83.45 | 56.32 | 171.36 | 77.24 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 84.23 | 55.15 | 29.08 | 87.33 | 77.24 | 0.00 | 0.00 | 0.00 |
February | 111.10 | 73.54 | 37.56 | 117.77 | 76.52 | 0.00 | 0.00 | 0.00 |
March | 100.23 | 55.63 | 44.60 | 113.24 | 54.55 | 0.00 | 0.00 | 0.00 |
April | 77.77 | 30.75 | 47.02 | 91.49 | 40.32 | 0.00 | 0.00 | 0.00 |
May | 68.16 | 14.22 | 53.94 | 84.61 | 26.32 | 0.00 | 0.00 | 0.00 |
June | 63.96 | 9.78 | 54.19 | 89.29 | 15.02 | 0.00 | 0.00 | 0.00 |
July | 67.05 | 11.65 | 55.40 | 103.47 | 7.77 | 0.00 | 0.00 | 0.00 |
August | 89.53 | 33.21 | 56.32 | 138.30 | 11.37 | 0.00 | 0.00 | 0.00 |
September | 97.15 | 50.25 | 46.90 | 133.35 | 23.07 | 0.00 | 0.00 | 0.00 |
October | 133.08 | 83.45 | 49.63 | 171.36 | 40.50 | 0.00 | 0.00 | 0.00 |
November | 92.28 | 55.42 | 36.86 | 104.05 | 55.77 | 0.00 | 0.00 | 0.00 |
December | 91.29 | 64.81 | 26.48 | 98.77 | 70.68 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 89.55 | 44.68 | 44.88 | 111.10 | 41.40 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 63.96 | 9.78 | 26.48 | 84.61 | 7.77 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 133.08 | 83.45 | 56.32 | 171.36 | 77.24 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 100.70 | 65.94 | 34.76 | 104.84 | 91.18 | 0.00 | 0.00 | 0.00 |
February | 132.82 | 87.92 | 44.91 | 141.33 | 90.35 | 0.00 | 0.00 | 0.00 |
March | 119.83 | 66.51 | 53.32 | 135.86 | 64.40 | 0.00 | 0.00 | 0.00 |
April | 92.99 | 36.77 | 56.22 | 109.74 | 47.69 | 0.00 | 0.00 | 0.00 |
May | 81.49 | 17.00 | 64.49 | 101.42 | 31.19 | 0.00 | 0.00 | 0.00 |
June | 76.47 | 11.69 | 64.78 | 106.81 | 17.86 | 0.00 | 0.00 | 0.00 |
July | 80.16 | 13.92 | 66.24 | 123.60 | 9.30 | 0.00 | 0.00 | 0.00 |
August | 107.04 | 39.70 | 67.34 | 165.20 | 13.60 | 0.00 | 0.00 | 0.00 |
September | 116.15 | 60.08 | 56.07 | 159.50 | 27.43 | 0.00 | 0.00 | 0.00 |
October | 159.11 | 99.77 | 59.34 | 205.18 | 48.05 | 0.00 | 0.00 | 0.00 |
November | 110.33 | 66.26 | 44.07 | 124.75 | 65.97 | 0.00 | 0.00 | 0.00 |
December | 109.15 | 77.49 | 31.66 | 118.46 | 83.51 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 107.07 | 53.41 | 53.65 | 133.08 | 48.98 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 76.47 | 11.69 | 31.66 | 101.42 | 9.30 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 159.11 | 99.77 | 67.34 | 205.18 | 91.18 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 84.23 | 55.15 | 29.08 | 87.37 | 77.05 | 0.00 | 0.00 | 0.00 |
February | 111.10 | 73.54 | 37.56 | 117.84 | 76.29 | 0.00 | 0.00 | 0.00 |
March | 100.23 | 55.63 | 44.60 | 113.33 | 54.29 | 0.00 | 0.00 | 0.00 |
April | 77.77 | 30.75 | 47.02 | 91.65 | 40.02 | 0.00 | 0.00 | 0.00 |
May | 68.16 | 14.22 | 53.94 | 84.88 | 25.98 | 0.00 | 0.00 | 0.00 |
June | 63.96 | 9.78 | 54.19 | 89.37 | 14.92 | 0.00 | 0.00 | 0.00 |
July | 67.05 | 11.65 | 55.40 | 103.53 | 7.69 | 0.00 | 0.00 | 0.00 |
August | 89.53 | 33.21 | 56.32 | 138.36 | 11.29 | 0.00 | 0.00 | 0.00 |
September | 97.15 | 50.25 | 46.90 | 133.41 | 22.95 | 0.00 | 0.00 | 0.00 |
October | 133.08 | 83.45 | 49.63 | 171.51 | 40.25 | 0.00 | 0.00 | 0.00 |
November | 92.28 | 55.42 | 36.86 | 104.16 | 55.51 | 0.00 | 0.00 | 0.00 |
December | 91.29 | 64.81 | 26.48 | 98.83 | 70.44 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 89.55 | 44.68 | 44.88 | 111.20 | 41.19 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 63.96 | 9.78 | 26.48 | 84.88 | 7.69 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 133.08 | 83.45 | 56.32 | 171.51 | 77.05 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 84.23 | 55.15 | 29.08 | 87.37 | 77.05 | 0.00 | 0.00 | 0.00 |
February | 111.10 | 73.54 | 37.56 | 117.84 | 76.29 | 0.00 | 0.00 | 0.00 |
March | 100.23 | 55.63 | 44.60 | 113.33 | 54.29 | 0.00 | 0.00 | 0.00 |
April | 77.77 | 30.75 | 47.02 | 91.65 | 40.02 | 0.00 | 0.00 | 0.00 |
May | 68.16 | 14.22 | 53.94 | 84.88 | 25.98 | 0.00 | 0.00 | 0.00 |
June | 63.96 | 9.78 | 54.19 | 89.37 | 14.92 | 0.00 | 0.00 | 0.00 |
July | 67.05 | 11.65 | 55.40 | 103.53 | 7.69 | 0.00 | 0.00 | 0.00 |
August | 89.53 | 33.21 | 56.32 | 138.36 | 11.29 | 0.00 | 0.00 | 0.00 |
September | 97.15 | 50.25 | 46.90 | 133.41 | 22.95 | 0.00 | 0.00 | 0.00 |
October | 133.08 | 83.45 | 49.63 | 171.51 | 40.25 | 0.00 | 0.00 | 0.00 |
November | 92.28 | 55.42 | 36.86 | 104.16 | 55.51 | 0.00 | 0.00 | 0.00 |
December | 91.29 | 64.81 | 26.48 | 98.83 | 70.44 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 89.55 | 44.68 | 44.88 | 111.20 | 41.19 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 63.96 | 9.78 | 26.48 | 84.88 | 7.69 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 133.08 | 83.45 | 56.32 | 171.51 | 77.05 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 100.70 | 65.94 | 34.76 | 104.90 | 90.95 | 0.00 | 0.00 | 0.00 |
February | 132.82 | 87.92 | 44.91 | 141.41 | 90.07 | 0.00 | 0.00 | 0.00 |
March | 119.83 | 66.51 | 53.32 | 135.97 | 64.09 | 0.00 | 0.00 | 0.00 |
April | 92.99 | 36.77 | 56.22 | 109.92 | 47.33 | 0.00 | 0.00 | 0.00 |
May | 81.49 | 17.00 | 64.49 | 101.74 | 30.79 | 0.00 | 0.00 | 0.00 |
June | 76.47 | 11.69 | 64.78 | 106.91 | 17.74 | 0.00 | 0.00 | 0.00 |
July | 80.16 | 13.92 | 66.24 | 123.68 | 9.21 | 0.00 | 0.00 | 0.00 |
August | 107.04 | 39.70 | 67.34 | 165.27 | 13.51 | 0.00 | 0.00 | 0.00 |
September | 116.15 | 60.08 | 56.07 | 159.58 | 27.29 | 0.00 | 0.00 | 0.00 |
October | 159.11 | 99.77 | 59.34 | 205.36 | 47.74 | 0.00 | 0.00 | 0.00 |
November | 110.33 | 66.26 | 44.07 | 124.88 | 65.67 | 0.00 | 0.00 | 0.00 |
December | 109.15 | 77.49 | 31.66 | 118.54 | 83.22 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 107.07 | 53.41 | 53.65 | 133.20 | 48.73 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 76.47 | 11.69 | 31.66 | 101.74 | 9.21 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 159.11 | 99.77 | 67.34 | 205.36 | 90.95 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 84.23 | 55.15 | 29.08 | 87.56 | 76.06 | 0.00 | 0.00 | 0.00 |
February | 111.10 | 73.54 | 37.56 | 118.11 | 75.24 | 0.00 | 0.00 | 0.00 |
March | 100.23 | 55.63 | 44.60 | 113.63 | 53.28 | 0.00 | 0.00 | 0.00 |
April | 77.77 | 30.75 | 47.02 | 92.04 | 39.08 | 0.00 | 0.00 | 0.00 |
May | 68.16 | 14.22 | 53.94 | 85.52 | 25.14 | 0.00 | 0.00 | 0.00 |
June | 63.96 | 9.78 | 54.19 | 89.56 | 14.64 | 0.00 | 0.00 | 0.00 |
July | 67.05 | 11.65 | 55.40 | 103.62 | 7.55 | 0.00 | 0.00 | 0.00 |
August | 89.53 | 33.21 | 56.32 | 138.40 | 11.17 | 0.00 | 0.00 | 0.00 |
September | 97.15 | 50.25 | 46.90 | 133.53 | 22.67 | 0.00 | 0.00 | 0.00 |
October | 133.08 | 83.45 | 49.63 | 171.85 | 39.60 | 0.00 | 0.00 | 0.00 |
November | 92.28 | 55.42 | 36.86 | 104.45 | 54.70 | 0.00 | 0.00 | 0.00 |
December | 91.29 | 64.81 | 26.48 | 99.06 | 69.46 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 89.55 | 44.68 | 44.88 | 111.46 | 40.52 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 63.96 | 9.78 | 26.48 | 85.52 | 7.55 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 133.08 | 83.45 | 56.32 | 171.85 | 76.06 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 84.23 | 55.15 | 29.08 | 87.56 | 76.06 | 0.00 | 0.00 | 0.00 |
February | 111.10 | 73.54 | 37.56 | 118.11 | 75.24 | 0.00 | 0.00 | 0.00 |
March | 100.23 | 55.63 | 44.60 | 113.63 | 53.28 | 0.00 | 0.00 | 0.00 |
April | 77.77 | 30.75 | 47.02 | 92.04 | 39.08 | 0.00 | 0.00 | 0.00 |
May | 68.16 | 14.22 | 53.94 | 85.52 | 25.14 | 0.00 | 0.00 | 0.00 |
June | 63.96 | 9.78 | 54.19 | 89.56 | 14.64 | 0.00 | 0.00 | 0.00 |
July | 67.05 | 11.65 | 55.40 | 103.62 | 7.55 | 0.00 | 0.00 | 0.00 |
August | 89.53 | 33.21 | 56.32 | 138.40 | 11.17 | 0.00 | 0.00 | 0.00 |
September | 97.15 | 50.25 | 46.90 | 133.53 | 22.67 | 0.00 | 0.00 | 0.00 |
October | 133.08 | 83.45 | 49.63 | 171.85 | 39.60 | 0.00 | 0.00 | 0.00 |
November | 92.28 | 55.42 | 36.86 | 104.45 | 54.70 | 0.00 | 0.00 | 0.00 |
December | 91.29 | 64.81 | 26.48 | 99.06 | 69.46 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 89.55 | 44.68 | 44.88 | 111.46 | 40.52 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 63.96 | 9.78 | 26.48 | 85.52 | 7.55 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 133.08 | 83.45 | 56.32 | 171.85 | 76.06 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 100.70 | 65.94 | 34.76 | 105.13 | 89.79 | 0.00 | 0.00 | 0.00 |
February | 132.82 | 87.92 | 44.91 | 141.74 | 88.83 | 0.00 | 0.00 | 0.00 |
March | 119.83 | 66.51 | 53.32 | 136.33 | 62.89 | 0.00 | 0.00 | 0.00 |
April | 92.99 | 36.77 | 56.22 | 110.40 | 46.22 | 0.00 | 0.00 | 0.00 |
May | 81.49 | 17.00 | 64.49 | 102.50 | 29.79 | 0.00 | 0.00 | 0.00 |
June | 76.47 | 11.69 | 64.78 | 107.13 | 17.41 | 0.00 | 0.00 | 0.00 |
July | 80.16 | 13.92 | 66.24 | 123.79 | 9.04 | 0.00 | 0.00 | 0.00 |
August | 107.04 | 39.70 | 67.34 | 165.32 | 13.37 | 0.00 | 0.00 | 0.00 |
September | 116.15 | 60.08 | 56.07 | 159.72 | 26.95 | 0.00 | 0.00 | 0.00 |
October | 159.11 | 99.77 | 59.34 | 205.77 | 46.98 | 0.00 | 0.00 | 0.00 |
November | 110.33 | 66.26 | 44.07 | 125.24 | 64.71 | 0.00 | 0.00 | 0.00 |
December | 109.15 | 77.49 | 31.66 | 118.82 | 82.06 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 107.07 | 53.41 | 53.65 | 133.51 | 47.94 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 76.47 | 11.69 | 31.66 | 102.50 | 9.04 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 159.11 | 99.77 | 67.34 | 205.77 | 89.79 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 84.23 | 55.15 | 29.08 | 88.30 | 71.76 | 0.00 | 0.00 | 0.00 |
February | 111.10 | 73.54 | 37.56 | 119.14 | 70.68 | 0.00 | 0.00 | 0.00 |
March | 100.23 | 55.63 | 44.60 | 114.61 | 49.15 | 0.00 | 0.00 | 0.00 |
April | 77.77 | 30.75 | 47.02 | 93.04 | 35.67 | 0.00 | 0.00 | 0.00 |
May | 68.16 | 14.22 | 53.94 | 86.88 | 22.68 | 0.00 | 0.00 | 0.00 |
June | 63.96 | 9.78 | 54.19 | 90.03 | 13.53 | 0.00 | 0.00 | 0.00 |
July | 67.05 | 11.65 | 55.40 | 103.59 | 7.12 | 0.00 | 0.00 | 0.00 |
August | 89.53 | 33.21 | 56.32 | 138.16 | 10.83 | 0.00 | 0.00 | 0.00 |
September | 97.15 | 50.25 | 46.90 | 133.70 | 21.71 | 0.00 | 0.00 | 0.00 |
October | 133.08 | 83.45 | 49.63 | 172.52 | 37.59 | 0.00 | 0.00 | 0.00 |
November | 92.28 | 55.42 | 36.86 | 105.26 | 51.74 | 0.00 | 0.00 | 0.00 |
December | 91.29 | 64.81 | 26.48 | 99.87 | 65.41 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 89.55 | 44.68 | 44.88 | 112.11 | 37.97 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 63.96 | 9.78 | 26.48 | 86.88 | 7.12 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 133.08 | 83.45 | 56.32 | 172.52 | 71.76 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 84.23 | 55.15 | 29.08 | 88.30 | 71.76 | 0.00 | 0.00 | 0.00 |
February | 111.10 | 73.54 | 37.56 | 119.14 | 70.68 | 0.00 | 0.00 | 0.00 |
March | 100.23 | 55.63 | 44.60 | 114.61 | 49.15 | 0.00 | 0.00 | 0.00 |
April | 77.77 | 30.75 | 47.02 | 93.04 | 35.67 | 0.00 | 0.00 | 0.00 |
May | 68.16 | 14.22 | 53.94 | 86.88 | 22.68 | 0.00 | 0.00 | 0.00 |
June | 63.96 | 9.78 | 54.19 | 90.03 | 13.53 | 0.00 | 0.00 | 0.00 |
July | 67.05 | 11.65 | 55.40 | 103.59 | 7.12 | 0.00 | 0.00 | 0.00 |
August | 89.53 | 33.21 | 56.32 | 138.16 | 10.83 | 0.00 | 0.00 | 0.00 |
September | 97.15 | 50.25 | 46.90 | 133.70 | 21.71 | 0.00 | 0.00 | 0.00 |
October | 133.08 | 83.45 | 49.63 | 172.52 | 37.59 | 0.00 | 0.00 | 0.00 |
November | 92.28 | 55.42 | 36.86 | 105.26 | 51.74 | 0.00 | 0.00 | 0.00 |
December | 91.29 | 64.81 | 26.48 | 99.87 | 65.41 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 89.55 | 44.68 | 44.88 | 112.11 | 37.97 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 63.96 | 9.78 | 26.48 | 86.88 | 7.12 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 133.08 | 83.45 | 56.32 | 172.52 | 71.76 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 100.70 | 65.94 | 34.76 | 106.02 | 84.70 | 0.00 | 0.00 | 0.00 |
February | 132.82 | 87.92 | 44.91 | 142.98 | 83.44 | 0.00 | 0.00 | 0.00 |
March | 119.83 | 66.51 | 53.32 | 137.52 | 58.02 | 0.00 | 0.00 | 0.00 |
April | 92.99 | 36.77 | 56.22 | 111.60 | 42.21 | 0.00 | 0.00 | 0.00 |
May | 81.49 | 17.00 | 64.49 | 104.12 | 26.90 | 0.00 | 0.00 | 0.00 |
June | 76.47 | 11.69 | 64.78 | 107.68 | 16.11 | 0.00 | 0.00 | 0.00 |
July | 80.16 | 13.92 | 66.24 | 123.74 | 8.54 | 0.00 | 0.00 | 0.00 |
August | 107.04 | 39.70 | 67.34 | 165.03 | 12.97 | 0.00 | 0.00 | 0.00 |
September | 116.15 | 60.08 | 56.07 | 159.92 | 25.82 | 0.00 | 0.00 | 0.00 |
October | 159.11 | 99.77 | 59.34 | 206.56 | 44.61 | 0.00 | 0.00 | 0.00 |
November | 110.33 | 66.26 | 44.07 | 126.21 | 61.22 | 0.00 | 0.00 | 0.00 |
December | 109.15 | 77.49 | 31.66 | 119.80 | 77.28 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 107.07 | 53.41 | 53.65 | 134.28 | 44.93 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 76.47 | 11.69 | 31.66 | 104.12 | 8.54 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 159.11 | 99.77 | 67.34 | 206.56 | 84.70 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.225599E+09 | 0.147724E+09 | 77875216.61 | 0.234105E+09 | 0.211857E+09 |
February | 0.268761E+09 | 0.177898E+09 | 90863136.84 | 0.285597E+09 | 0.187945E+09 |
March | 0.268453E+09 | 0.148996E+09 | 0.119457E+09 | 0.303866E+09 | 0.148546E+09 |
April | 0.201590E+09 | 79714779.59 | 0.121875E+09 | 0.236884E+09 | 0.106767E+09 |
May | 0.182553E+09 | 38077600.21 | 0.144475E+09 | 0.225777E+09 | 72675407.07 |
June | 0.165794E+09 | 25343284.63 | 0.140450E+09 | 0.232071E+09 | 38253205.04 |
July | 0.179578E+09 | 31192634.82 | 0.148385E+09 | 0.278157E+09 | 19501544.17 |
August | 0.239806E+09 | 88948202.50 | 0.150858E+09 | 0.371235E+09 | 29270120.29 |
September | 0.251801E+09 | 0.130242E+09 | 0.121559E+09 | 0.346179E+09 | 59091605.30 |
October | 0.356445E+09 | 0.223517E+09 | 0.132928E+09 | 0.459155E+09 | 0.109591E+09 |
November | 0.239191E+09 | 0.143646E+09 | 95545382.05 | 0.269138E+09 | 0.148246E+09 |
December | 0.244515E+09 | 0.173590E+09 | 70925763.74 | 0.264826E+09 | 0.192598E+09 |
Annual Sum or Average | 0.282409E+10 | 0.140889E+10 | 0.141520E+10 | 0.350699E+10 | 0.132434E+10 |
Minimum of Months | 0.165794E+09 | 25343284.63 | 70925763.74 | 0.225777E+09 | 19501544.17 |
Maximum of Months | 0.356445E+09 | 0.223517E+09 | 0.150858E+09 | 0.459155E+09 | 0.211857E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.225599E+09 | 0.147724E+09 | 77875216.61 | 0.234105E+09 | 0.211857E+09 |
February | 0.268761E+09 | 0.177898E+09 | 90863136.84 | 0.285597E+09 | 0.187945E+09 |
March | 0.268453E+09 | 0.148996E+09 | 0.119457E+09 | 0.303866E+09 | 0.148546E+09 |
April | 0.201590E+09 | 79714779.59 | 0.121875E+09 | 0.236884E+09 | 0.106767E+09 |
May | 0.182553E+09 | 38077600.21 | 0.144475E+09 | 0.225777E+09 | 72675407.07 |
June | 0.165794E+09 | 25343284.63 | 0.140450E+09 | 0.232071E+09 | 38253205.04 |
July | 0.179578E+09 | 31192634.82 | 0.148385E+09 | 0.278157E+09 | 19501544.17 |
August | 0.239806E+09 | 88948202.50 | 0.150858E+09 | 0.371235E+09 | 29270120.29 |
September | 0.251801E+09 | 0.130242E+09 | 0.121559E+09 | 0.346179E+09 | 59091605.30 |
October | 0.356445E+09 | 0.223517E+09 | 0.132928E+09 | 0.459155E+09 | 0.109591E+09 |
November | 0.239191E+09 | 0.143646E+09 | 95545382.05 | 0.269138E+09 | 0.148246E+09 |
December | 0.244515E+09 | 0.173590E+09 | 70925763.74 | 0.264826E+09 | 0.192598E+09 |
Annual Sum or Average | 0.282409E+10 | 0.140889E+10 | 0.141520E+10 | 0.350699E+10 | 0.132434E+10 |
Minimum of Months | 0.165794E+09 | 25343284.63 | 70925763.74 | 0.225777E+09 | 19501544.17 |
Maximum of Months | 0.356445E+09 | 0.223517E+09 | 0.150858E+09 | 0.459155E+09 | 0.211857E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.225599E+09 | 0.147724E+09 | 77875216.61 | 0.234105E+09 | 0.211857E+09 |
February | 0.268761E+09 | 0.177898E+09 | 90863136.84 | 0.285597E+09 | 0.187945E+09 |
March | 0.268453E+09 | 0.148996E+09 | 0.119457E+09 | 0.303866E+09 | 0.148546E+09 |
April | 0.201590E+09 | 79714779.59 | 0.121875E+09 | 0.236884E+09 | 0.106767E+09 |
May | 0.182553E+09 | 38077600.21 | 0.144475E+09 | 0.225777E+09 | 72675407.07 |
June | 0.165794E+09 | 25343284.63 | 0.140450E+09 | 0.232071E+09 | 38253205.04 |
July | 0.179578E+09 | 31192634.82 | 0.148385E+09 | 0.278157E+09 | 19501544.17 |
August | 0.239806E+09 | 88948202.50 | 0.150858E+09 | 0.371235E+09 | 29270120.29 |
September | 0.251801E+09 | 0.130242E+09 | 0.121559E+09 | 0.346179E+09 | 59091605.30 |
October | 0.356445E+09 | 0.223517E+09 | 0.132928E+09 | 0.459155E+09 | 0.109591E+09 |
November | 0.239191E+09 | 0.143646E+09 | 95545382.05 | 0.269138E+09 | 0.148246E+09 |
December | 0.244515E+09 | 0.173590E+09 | 70925763.74 | 0.264826E+09 | 0.192598E+09 |
Annual Sum or Average | 0.282409E+10 | 0.140889E+10 | 0.141520E+10 | 0.350699E+10 | 0.132434E+10 |
Minimum of Months | 0.165794E+09 | 25343284.63 | 70925763.74 | 0.225777E+09 | 19501544.17 |
Maximum of Months | 0.356445E+09 | 0.223517E+09 | 0.150858E+09 | 0.459155E+09 | 0.211857E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.225599E+09 | 0.147724E+09 | 77875216.61 | 0.234105E+09 | 0.211857E+09 |
February | 0.268761E+09 | 0.177898E+09 | 90863136.84 | 0.285597E+09 | 0.187945E+09 |
March | 0.268453E+09 | 0.148996E+09 | 0.119457E+09 | 0.303866E+09 | 0.148546E+09 |
April | 0.201590E+09 | 79714779.59 | 0.121875E+09 | 0.236884E+09 | 0.106767E+09 |
May | 0.182553E+09 | 38077600.21 | 0.144475E+09 | 0.225777E+09 | 72675407.07 |
June | 0.165794E+09 | 25343284.63 | 0.140450E+09 | 0.232071E+09 | 38253205.04 |
July | 0.179578E+09 | 31192634.82 | 0.148385E+09 | 0.278157E+09 | 19501544.17 |
August | 0.239806E+09 | 88948202.50 | 0.150858E+09 | 0.371235E+09 | 29270120.29 |
September | 0.251801E+09 | 0.130242E+09 | 0.121559E+09 | 0.346179E+09 | 59091605.30 |
October | 0.356445E+09 | 0.223517E+09 | 0.132928E+09 | 0.459155E+09 | 0.109591E+09 |
November | 0.239191E+09 | 0.143646E+09 | 95545382.05 | 0.269138E+09 | 0.148246E+09 |
December | 0.244515E+09 | 0.173590E+09 | 70925763.74 | 0.264826E+09 | 0.192598E+09 |
Annual Sum or Average | 0.282409E+10 | 0.140889E+10 | 0.141520E+10 | 0.350699E+10 | 0.132434E+10 |
Minimum of Months | 0.165794E+09 | 25343284.63 | 70925763.74 | 0.225777E+09 | 19501544.17 |
Maximum of Months | 0.356445E+09 | 0.223517E+09 | 0.150858E+09 | 0.459155E+09 | 0.211857E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.271204E+09 | 0.177586E+09 | 93617999.33 | 0.282500E+09 | 0.251550E+09 |
February | 0.323092E+09 | 0.213861E+09 | 0.109231E+09 | 0.344483E+09 | 0.223211E+09 |
March | 0.322721E+09 | 0.179116E+09 | 0.143605E+09 | 0.366429E+09 | 0.176427E+09 |
April | 0.242342E+09 | 95829437.22 | 0.146513E+09 | 0.285589E+09 | 0.127026E+09 |
May | 0.219456E+09 | 45775137.53 | 0.173681E+09 | 0.272019E+09 | 86640717.04 |
June | 0.199310E+09 | 30466529.75 | 0.168843E+09 | 0.279039E+09 | 45774800.25 |
July | 0.215880E+09 | 37498349.19 | 0.178382E+09 | 0.333995E+09 | 23509170.15 |
August | 0.288284E+09 | 0.106929E+09 | 0.181355E+09 | 0.445754E+09 | 35260869.89 |
September | 0.302704E+09 | 0.156571E+09 | 0.146133E+09 | 0.416233E+09 | 70696802.88 |
October | 0.428502E+09 | 0.268701E+09 | 0.159800E+09 | 0.552652E+09 | 0.130795E+09 |
November | 0.287544E+09 | 0.172684E+09 | 0.114860E+09 | 0.324365E+09 | 0.176407E+09 |
December | 0.293945E+09 | 0.208681E+09 | 85263687.10 | 0.319280E+09 | 0.228899E+09 |
Annual Sum or Average | 0.339499E+10 | 0.169370E+10 | 0.170129E+10 | 0.422234E+10 | 0.157620E+10 |
Minimum of Months | 0.199310E+09 | 30466529.75 | 85263687.10 | 0.272019E+09 | 23509170.15 |
Maximum of Months | 0.428502E+09 | 0.268701E+09 | 0.181355E+09 | 0.552652E+09 | 0.251550E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.271204E+09 | 0.177586E+09 | 93617999.33 | 0.282500E+09 | 0.251550E+09 |
February | 0.323092E+09 | 0.213861E+09 | 0.109231E+09 | 0.344483E+09 | 0.223211E+09 |
March | 0.322721E+09 | 0.179116E+09 | 0.143605E+09 | 0.366429E+09 | 0.176427E+09 |
April | 0.242342E+09 | 95829437.22 | 0.146513E+09 | 0.285589E+09 | 0.127026E+09 |
May | 0.219456E+09 | 45775137.53 | 0.173681E+09 | 0.272019E+09 | 86640717.04 |
June | 0.199310E+09 | 30466529.75 | 0.168843E+09 | 0.279039E+09 | 45774800.25 |
July | 0.215880E+09 | 37498349.19 | 0.178382E+09 | 0.333995E+09 | 23509170.15 |
August | 0.288284E+09 | 0.106929E+09 | 0.181355E+09 | 0.445754E+09 | 35260869.89 |
September | 0.302704E+09 | 0.156571E+09 | 0.146133E+09 | 0.416233E+09 | 70696802.88 |
October | 0.428502E+09 | 0.268701E+09 | 0.159800E+09 | 0.552652E+09 | 0.130795E+09 |
November | 0.287544E+09 | 0.172684E+09 | 0.114860E+09 | 0.324365E+09 | 0.176407E+09 |
December | 0.293945E+09 | 0.208681E+09 | 85263687.10 | 0.319280E+09 | 0.228899E+09 |
Annual Sum or Average | 0.339499E+10 | 0.169370E+10 | 0.170129E+10 | 0.422234E+10 | 0.157620E+10 |
Minimum of Months | 0.199310E+09 | 30466529.75 | 85263687.10 | 0.272019E+09 | 23509170.15 |
Maximum of Months | 0.428502E+09 | 0.268701E+09 | 0.181355E+09 | 0.552652E+09 | 0.251550E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.225599E+09 | 0.147724E+09 | 77875216.61 | 0.231599E+09 | 0.222246E+09 |
February | 0.268761E+09 | 0.177898E+09 | 90863136.84 | 0.282524E+09 | 0.197644E+09 |
March | 0.268453E+09 | 0.148996E+09 | 0.119457E+09 | 0.300465E+09 | 0.159061E+09 |
April | 0.201590E+09 | 79714779.59 | 0.121875E+09 | 0.233250E+09 | 0.115600E+09 |
May | 0.182553E+09 | 38077600.21 | 0.144475E+09 | 0.221936E+09 | 77726031.75 |
June | 0.165794E+09 | 25343284.63 | 0.140450E+09 | 0.231276E+09 | 39315751.57 |
July | 0.179578E+09 | 31192634.82 | 0.148385E+09 | 0.278039E+09 | 19973993.80 |
August | 0.239806E+09 | 88948202.50 | 0.150858E+09 | 0.371352E+09 | 29470226.20 |
September | 0.251801E+09 | 0.130242E+09 | 0.121559E+09 | 0.345527E+09 | 60062818.30 |
October | 0.356445E+09 | 0.223517E+09 | 0.132928E+09 | 0.456395E+09 | 0.114198E+09 |
November | 0.239191E+09 | 0.143646E+09 | 95545382.05 | 0.265700E+09 | 0.157807E+09 |
December | 0.244515E+09 | 0.173590E+09 | 70925763.74 | 0.262265E+09 | 0.203037E+09 |
Annual Sum or Average | 0.282409E+10 | 0.140889E+10 | 0.141520E+10 | 0.348033E+10 | 0.139614E+10 |
Minimum of Months | 0.165794E+09 | 25343284.63 | 70925763.74 | 0.221936E+09 | 19973993.80 |
Maximum of Months | 0.356445E+09 | 0.223517E+09 | 0.150858E+09 | 0.456395E+09 | 0.222246E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.225599E+09 | 0.147724E+09 | 77875216.61 | 0.231599E+09 | 0.222246E+09 |
February | 0.268761E+09 | 0.177898E+09 | 90863136.84 | 0.282524E+09 | 0.197644E+09 |
March | 0.268453E+09 | 0.148996E+09 | 0.119457E+09 | 0.300465E+09 | 0.159061E+09 |
April | 0.201590E+09 | 79714779.59 | 0.121875E+09 | 0.233250E+09 | 0.115600E+09 |
May | 0.182553E+09 | 38077600.21 | 0.144475E+09 | 0.221936E+09 | 77726031.75 |
June | 0.165794E+09 | 25343284.63 | 0.140450E+09 | 0.231276E+09 | 39315751.57 |
July | 0.179578E+09 | 31192634.82 | 0.148385E+09 | 0.278039E+09 | 19973993.80 |
August | 0.239806E+09 | 88948202.50 | 0.150858E+09 | 0.371352E+09 | 29470226.20 |
September | 0.251801E+09 | 0.130242E+09 | 0.121559E+09 | 0.345527E+09 | 60062818.30 |
October | 0.356445E+09 | 0.223517E+09 | 0.132928E+09 | 0.456395E+09 | 0.114198E+09 |
November | 0.239191E+09 | 0.143646E+09 | 95545382.05 | 0.265700E+09 | 0.157807E+09 |
December | 0.244515E+09 | 0.173590E+09 | 70925763.74 | 0.262265E+09 | 0.203037E+09 |
Annual Sum or Average | 0.282409E+10 | 0.140889E+10 | 0.141520E+10 | 0.348033E+10 | 0.139614E+10 |
Minimum of Months | 0.165794E+09 | 25343284.63 | 70925763.74 | 0.221936E+09 | 19973993.80 |
Maximum of Months | 0.356445E+09 | 0.223517E+09 | 0.150858E+09 | 0.456395E+09 | 0.222246E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.271204E+09 | 0.177586E+09 | 93617999.33 | 0.279558E+09 | 0.263799E+09 |
February | 0.323092E+09 | 0.213861E+09 | 0.109231E+09 | 0.340865E+09 | 0.234643E+09 |
March | 0.322721E+09 | 0.179116E+09 | 0.143605E+09 | 0.362419E+09 | 0.188775E+09 |
April | 0.242342E+09 | 95829437.22 | 0.146513E+09 | 0.281298E+09 | 0.137406E+09 |
May | 0.219456E+09 | 45775137.53 | 0.173681E+09 | 0.267494E+09 | 92594749.51 |
June | 0.199310E+09 | 30466529.75 | 0.168843E+09 | 0.278129E+09 | 47033129.09 |
July | 0.215880E+09 | 37498349.19 | 0.178382E+09 | 0.333882E+09 | 24073698.55 |
August | 0.288284E+09 | 0.106929E+09 | 0.181355E+09 | 0.445940E+09 | 35509110.28 |
September | 0.302704E+09 | 0.156571E+09 | 0.146133E+09 | 0.415521E+09 | 71846634.52 |
October | 0.428502E+09 | 0.268701E+09 | 0.159800E+09 | 0.549472E+09 | 0.136215E+09 |
November | 0.287544E+09 | 0.172684E+09 | 0.114860E+09 | 0.320329E+09 | 0.187651E+09 |
December | 0.293945E+09 | 0.208681E+09 | 85263687.10 | 0.316268E+09 | 0.241188E+09 |
Annual Sum or Average | 0.339499E+10 | 0.169370E+10 | 0.170129E+10 | 0.419117E+10 | 0.166073E+10 |
Minimum of Months | 0.199310E+09 | 30466529.75 | 85263687.10 | 0.267494E+09 | 24073698.55 |
Maximum of Months | 0.428502E+09 | 0.268701E+09 | 0.181355E+09 | 0.549472E+09 | 0.263799E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.225599E+09 | 0.147724E+09 | 77875216.61 | 0.232043E+09 | 0.216471E+09 |
February | 0.268761E+09 | 0.177898E+09 | 90863136.84 | 0.282802E+09 | 0.193067E+09 |
March | 0.268453E+09 | 0.148996E+09 | 0.119457E+09 | 0.301099E+09 | 0.154542E+09 |
April | 0.201590E+09 | 79714779.59 | 0.121875E+09 | 0.234078E+09 | 0.112557E+09 |
May | 0.182553E+09 | 38077600.21 | 0.144475E+09 | 0.222438E+09 | 77920228.65 |
June | 0.165794E+09 | 25343284.63 | 0.140450E+09 | 0.230818E+09 | 42144095.57 |
July | 0.179578E+09 | 31192634.82 | 0.148385E+09 | 0.276962E+09 | 23692409.12 |
August | 0.239806E+09 | 88948202.50 | 0.150858E+09 | 0.370320E+09 | 33461745.53 |
September | 0.251801E+09 | 0.130242E+09 | 0.121559E+09 | 0.345341E+09 | 63265277.26 |
October | 0.356445E+09 | 0.223517E+09 | 0.132928E+09 | 0.457062E+09 | 0.114554E+09 |
November | 0.239191E+09 | 0.143646E+09 | 95545382.05 | 0.266719E+09 | 0.153541E+09 |
December | 0.244515E+09 | 0.173590E+09 | 70925763.74 | 0.262717E+09 | 0.197928E+09 |
Annual Sum or Average | 0.282409E+10 | 0.140889E+10 | 0.141520E+10 | 0.348240E+10 | 0.138314E+10 |
Minimum of Months | 0.165794E+09 | 25343284.63 | 70925763.74 | 0.222438E+09 | 23692409.12 |
Maximum of Months | 0.356445E+09 | 0.223517E+09 | 0.150858E+09 | 0.457062E+09 | 0.216471E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.225599E+09 | 0.147724E+09 | 77875216.61 | 0.232043E+09 | 0.216471E+09 |
February | 0.268761E+09 | 0.177898E+09 | 90863136.84 | 0.282802E+09 | 0.193067E+09 |
March | 0.268453E+09 | 0.148996E+09 | 0.119457E+09 | 0.301099E+09 | 0.154542E+09 |
April | 0.201590E+09 | 79714779.59 | 0.121875E+09 | 0.234078E+09 | 0.112557E+09 |
May | 0.182553E+09 | 38077600.21 | 0.144475E+09 | 0.222438E+09 | 77920228.65 |
June | 0.165794E+09 | 25343284.63 | 0.140450E+09 | 0.230818E+09 | 42144095.57 |
July | 0.179578E+09 | 31192634.82 | 0.148385E+09 | 0.276962E+09 | 23692409.12 |
August | 0.239806E+09 | 88948202.50 | 0.150858E+09 | 0.370320E+09 | 33461745.53 |
September | 0.251801E+09 | 0.130242E+09 | 0.121559E+09 | 0.345341E+09 | 63265277.26 |
October | 0.356445E+09 | 0.223517E+09 | 0.132928E+09 | 0.457062E+09 | 0.114554E+09 |
November | 0.239191E+09 | 0.143646E+09 | 95545382.05 | 0.266719E+09 | 0.153541E+09 |
December | 0.244515E+09 | 0.173590E+09 | 70925763.74 | 0.262717E+09 | 0.197928E+09 |
Annual Sum or Average | 0.282409E+10 | 0.140889E+10 | 0.141520E+10 | 0.348240E+10 | 0.138314E+10 |
Minimum of Months | 0.165794E+09 | 25343284.63 | 70925763.74 | 0.222438E+09 | 23692409.12 |
Maximum of Months | 0.356445E+09 | 0.223517E+09 | 0.150858E+09 | 0.457062E+09 | 0.216471E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.269723E+09 | 0.176616E+09 | 93106425.56 | 0.278573E+09 | 0.255585E+09 |
February | 0.321327E+09 | 0.212692E+09 | 0.108635E+09 | 0.339353E+09 | 0.228000E+09 |
March | 0.320958E+09 | 0.178137E+09 | 0.142821E+09 | 0.361206E+09 | 0.182463E+09 |
April | 0.241018E+09 | 95305779.10 | 0.145712E+09 | 0.280751E+09 | 0.133103E+09 |
May | 0.218257E+09 | 45525000.17 | 0.172732E+09 | 0.266630E+09 | 92297447.90 |
June | 0.198220E+09 | 30300045.98 | 0.167920E+09 | 0.276069E+09 | 50072883.43 |
July | 0.214701E+09 | 37293440.18 | 0.177407E+09 | 0.330806E+09 | 28299566.75 |
August | 0.286709E+09 | 0.106345E+09 | 0.180364E+09 | 0.442310E+09 | 39998337.61 |
September | 0.301050E+09 | 0.155715E+09 | 0.145335E+09 | 0.413033E+09 | 75187269.20 |
October | 0.426160E+09 | 0.267233E+09 | 0.158927E+09 | 0.547257E+09 | 0.135867E+09 |
November | 0.285973E+09 | 0.171741E+09 | 0.114233E+09 | 0.319798E+09 | 0.181633E+09 |
December | 0.292339E+09 | 0.207541E+09 | 84797765.31 | 0.315094E+09 | 0.233893E+09 |
Annual Sum or Average | 0.337643E+10 | 0.168444E+10 | 0.169199E+10 | 0.417088E+10 | 0.163640E+10 |
Minimum of Months | 0.198220E+09 | 30300045.98 | 84797765.31 | 0.266630E+09 | 28299566.75 |
Maximum of Months | 0.426160E+09 | 0.267233E+09 | 0.180364E+09 | 0.547257E+09 | 0.255585E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.225599E+09 | 0.147724E+09 | 77875216.61 | 0.232379E+09 | 0.214003E+09 |
February | 0.268761E+09 | 0.177898E+09 | 90863136.84 | 0.283131E+09 | 0.191108E+09 |
March | 0.268453E+09 | 0.148996E+09 | 0.119457E+09 | 0.301552E+09 | 0.152497E+09 |
April | 0.201590E+09 | 79714779.59 | 0.121875E+09 | 0.234691E+09 | 0.110749E+09 |
May | 0.182553E+09 | 38077600.21 | 0.144475E+09 | 0.223171E+09 | 76616066.66 |
June | 0.165794E+09 | 25343284.63 | 0.140450E+09 | 0.230877E+09 | 42028341.72 |
July | 0.179578E+09 | 31192634.82 | 0.148385E+09 | 0.276936E+09 | 23799569.31 |
August | 0.239806E+09 | 88948202.50 | 0.150858E+09 | 0.370270E+09 | 33640107.47 |
September | 0.251801E+09 | 0.130242E+09 | 0.121559E+09 | 0.345391E+09 | 63116863.53 |
October | 0.356445E+09 | 0.223517E+09 | 0.132928E+09 | 0.457492E+09 | 0.113459E+09 |
November | 0.239191E+09 | 0.143646E+09 | 95545382.05 | 0.267395E+09 | 0.151269E+09 |
December | 0.244515E+09 | 0.173590E+09 | 70925763.74 | 0.263039E+09 | 0.195763E+09 |
Annual Sum or Average | 0.282409E+10 | 0.140889E+10 | 0.141520E+10 | 0.348633E+10 | 0.136805E+10 |
Minimum of Months | 0.165794E+09 | 25343284.63 | 70925763.74 | 0.223171E+09 | 23799569.31 |
Maximum of Months | 0.356445E+09 | 0.223517E+09 | 0.150858E+09 | 0.457492E+09 | 0.214003E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.225599E+09 | 0.147724E+09 | 77875216.61 | 0.232379E+09 | 0.214003E+09 |
February | 0.268761E+09 | 0.177898E+09 | 90863136.84 | 0.283131E+09 | 0.191108E+09 |
March | 0.268453E+09 | 0.148996E+09 | 0.119457E+09 | 0.301552E+09 | 0.152497E+09 |
April | 0.201590E+09 | 79714779.59 | 0.121875E+09 | 0.234691E+09 | 0.110749E+09 |
May | 0.182553E+09 | 38077600.21 | 0.144475E+09 | 0.223171E+09 | 76616066.66 |
June | 0.165794E+09 | 25343284.63 | 0.140450E+09 | 0.230877E+09 | 42028341.72 |
July | 0.179578E+09 | 31192634.82 | 0.148385E+09 | 0.276936E+09 | 23799569.31 |
August | 0.239806E+09 | 88948202.50 | 0.150858E+09 | 0.370270E+09 | 33640107.47 |
September | 0.251801E+09 | 0.130242E+09 | 0.121559E+09 | 0.345391E+09 | 63116863.53 |
October | 0.356445E+09 | 0.223517E+09 | 0.132928E+09 | 0.457492E+09 | 0.113459E+09 |
November | 0.239191E+09 | 0.143646E+09 | 95545382.05 | 0.267395E+09 | 0.151269E+09 |
December | 0.244515E+09 | 0.173590E+09 | 70925763.74 | 0.263039E+09 | 0.195763E+09 |
Annual Sum or Average | 0.282409E+10 | 0.140889E+10 | 0.141520E+10 | 0.348633E+10 | 0.136805E+10 |
Minimum of Months | 0.165794E+09 | 25343284.63 | 70925763.74 | 0.223171E+09 | 23799569.31 |
Maximum of Months | 0.356445E+09 | 0.223517E+09 | 0.150858E+09 | 0.457492E+09 | 0.214003E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.269723E+09 | 0.176616E+09 | 93106425.56 | 0.278981E+09 | 0.252658E+09 |
February | 0.321327E+09 | 0.212692E+09 | 0.108635E+09 | 0.339753E+09 | 0.225677E+09 |
March | 0.320958E+09 | 0.178137E+09 | 0.142821E+09 | 0.361756E+09 | 0.180045E+09 |
April | 0.241018E+09 | 95305779.10 | 0.145712E+09 | 0.281487E+09 | 0.130969E+09 |
May | 0.218257E+09 | 45525000.17 | 0.172732E+09 | 0.267505E+09 | 90758008.82 |
June | 0.198220E+09 | 30300045.98 | 0.167920E+09 | 0.276141E+09 | 49936197.19 |
July | 0.214701E+09 | 37293440.18 | 0.177407E+09 | 0.330776E+09 | 28426238.64 |
August | 0.286709E+09 | 0.106345E+09 | 0.180364E+09 | 0.442250E+09 | 40209719.32 |
September | 0.301050E+09 | 0.155715E+09 | 0.145335E+09 | 0.413093E+09 | 75011654.55 |
October | 0.426160E+09 | 0.267233E+09 | 0.158927E+09 | 0.547770E+09 | 0.134572E+09 |
November | 0.285973E+09 | 0.171741E+09 | 0.114233E+09 | 0.320606E+09 | 0.178944E+09 |
December | 0.292339E+09 | 0.207541E+09 | 84797765.31 | 0.315484E+09 | 0.231326E+09 |
Annual Sum or Average | 0.337643E+10 | 0.168444E+10 | 0.169199E+10 | 0.417560E+10 | 0.161853E+10 |
Minimum of Months | 0.198220E+09 | 30300045.98 | 84797765.31 | 0.267505E+09 | 28426238.64 |
Maximum of Months | 0.426160E+09 | 0.267233E+09 | 0.180364E+09 | 0.547770E+09 | 0.252658E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.225599E+09 | 0.147724E+09 | 77875216.61 | 0.232800E+09 | 0.211908E+09 |
February | 0.268761E+09 | 0.177898E+09 | 90863136.84 | 0.283589E+09 | 0.189374E+09 |
March | 0.268453E+09 | 0.148996E+09 | 0.119457E+09 | 0.302134E+09 | 0.150677E+09 |
April | 0.201590E+09 | 79714779.59 | 0.121875E+09 | 0.235546E+09 | 0.108945E+09 |
May | 0.182553E+09 | 38077600.21 | 0.144475E+09 | 0.224405E+09 | 74821949.87 |
June | 0.165794E+09 | 25343284.63 | 0.140450E+09 | 0.231225E+09 | 41368353.36 |
July | 0.179578E+09 | 31192634.82 | 0.148385E+09 | 0.277250E+09 | 23215353.00 |
August | 0.239806E+09 | 88948202.50 | 0.150858E+09 | 0.370541E+09 | 33030025.12 |
September | 0.251801E+09 | 0.130242E+09 | 0.121559E+09 | 0.345669E+09 | 62362368.07 |
October | 0.356445E+09 | 0.223517E+09 | 0.132928E+09 | 0.458174E+09 | 0.112037E+09 |
November | 0.239191E+09 | 0.143646E+09 | 95545382.05 | 0.268226E+09 | 0.149148E+09 |
December | 0.244515E+09 | 0.173590E+09 | 70925763.74 | 0.263445E+09 | 0.193877E+09 |
Annual Sum or Average | 0.282409E+10 | 0.140889E+10 | 0.141520E+10 | 0.349300E+10 | 0.135076E+10 |
Minimum of Months | 0.165794E+09 | 25343284.63 | 70925763.74 | 0.224405E+09 | 23215353.00 |
Maximum of Months | 0.356445E+09 | 0.223517E+09 | 0.150858E+09 | 0.458174E+09 | 0.211908E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.225599E+09 | 0.147724E+09 | 77875216.61 | 0.232800E+09 | 0.211908E+09 |
February | 0.268761E+09 | 0.177898E+09 | 90863136.84 | 0.283589E+09 | 0.189374E+09 |
March | 0.268453E+09 | 0.148996E+09 | 0.119457E+09 | 0.302134E+09 | 0.150677E+09 |
April | 0.201590E+09 | 79714779.59 | 0.121875E+09 | 0.235546E+09 | 0.108945E+09 |
May | 0.182553E+09 | 38077600.21 | 0.144475E+09 | 0.224405E+09 | 74821949.87 |
June | 0.165794E+09 | 25343284.63 | 0.140450E+09 | 0.231225E+09 | 41368353.36 |
July | 0.179578E+09 | 31192634.82 | 0.148385E+09 | 0.277250E+09 | 23215353.00 |
August | 0.239806E+09 | 88948202.50 | 0.150858E+09 | 0.370541E+09 | 33030025.12 |
September | 0.251801E+09 | 0.130242E+09 | 0.121559E+09 | 0.345669E+09 | 62362368.07 |
October | 0.356445E+09 | 0.223517E+09 | 0.132928E+09 | 0.458174E+09 | 0.112037E+09 |
November | 0.239191E+09 | 0.143646E+09 | 95545382.05 | 0.268226E+09 | 0.149148E+09 |
December | 0.244515E+09 | 0.173590E+09 | 70925763.74 | 0.263445E+09 | 0.193877E+09 |
Annual Sum or Average | 0.282409E+10 | 0.140889E+10 | 0.141520E+10 | 0.349300E+10 | 0.135076E+10 |
Minimum of Months | 0.165794E+09 | 25343284.63 | 70925763.74 | 0.224405E+09 | 23215353.00 |
Maximum of Months | 0.356445E+09 | 0.223517E+09 | 0.150858E+09 | 0.458174E+09 | 0.211908E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.269723E+09 | 0.176616E+09 | 93106425.56 | 0.279492E+09 | 0.250175E+09 |
February | 0.321327E+09 | 0.212692E+09 | 0.108635E+09 | 0.340308E+09 | 0.223623E+09 |
March | 0.320958E+09 | 0.178137E+09 | 0.142821E+09 | 0.362461E+09 | 0.177894E+09 |
April | 0.241018E+09 | 95305779.10 | 0.145712E+09 | 0.282510E+09 | 0.128843E+09 |
May | 0.218257E+09 | 45525000.17 | 0.172732E+09 | 0.268978E+09 | 88646967.00 |
June | 0.198220E+09 | 30300045.98 | 0.167920E+09 | 0.276558E+09 | 49161523.56 |
July | 0.214701E+09 | 37293440.18 | 0.177407E+09 | 0.331152E+09 | 27741121.57 |
August | 0.286709E+09 | 0.106345E+09 | 0.180364E+09 | 0.442576E+09 | 39492901.56 |
September | 0.301050E+09 | 0.155715E+09 | 0.145335E+09 | 0.413427E+09 | 74123470.28 |
October | 0.426160E+09 | 0.267233E+09 | 0.158927E+09 | 0.548583E+09 | 0.132897E+09 |
November | 0.285973E+09 | 0.171741E+09 | 0.114233E+09 | 0.321599E+09 | 0.176438E+09 |
December | 0.292339E+09 | 0.207541E+09 | 84797765.31 | 0.315976E+09 | 0.229091E+09 |
Annual Sum or Average | 0.337643E+10 | 0.168444E+10 | 0.169199E+10 | 0.418362E+10 | 0.159813E+10 |
Minimum of Months | 0.198220E+09 | 30300045.98 | 84797765.31 | 0.268978E+09 | 27741121.57 |
Maximum of Months | 0.426160E+09 | 0.267233E+09 | 0.180364E+09 | 0.548583E+09 | 0.250175E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.225599E+09 | 0.147724E+09 | 77875216.61 | 0.234690E+09 | 0.205710E+09 |
February | 0.268761E+09 | 0.177898E+09 | 90863136.84 | 0.285747E+09 | 0.184247E+09 |
March | 0.268453E+09 | 0.148996E+09 | 0.119457E+09 | 0.304099E+09 | 0.145789E+09 |
April | 0.201590E+09 | 79714779.59 | 0.121875E+09 | 0.237547E+09 | 0.104705E+09 |
May | 0.182553E+09 | 38077600.21 | 0.144475E+09 | 0.226549E+09 | 71163996.59 |
June | 0.165794E+09 | 25343284.63 | 0.140450E+09 | 0.231421E+09 | 39452048.69 |
July | 0.179578E+09 | 31192634.82 | 0.148385E+09 | 0.276880E+09 | 21498853.09 |
August | 0.239806E+09 | 88948202.50 | 0.150858E+09 | 0.370253E+09 | 31217952.05 |
September | 0.251801E+09 | 0.130242E+09 | 0.121559E+09 | 0.345854E+09 | 60383337.46 |
October | 0.356445E+09 | 0.223517E+09 | 0.132928E+09 | 0.459464E+09 | 0.109051E+09 |
November | 0.239191E+09 | 0.143646E+09 | 95545382.05 | 0.270127E+09 | 0.144488E+09 |
December | 0.244515E+09 | 0.173590E+09 | 70925763.74 | 0.265206E+09 | 0.188592E+09 |
Annual Sum or Average | 0.282409E+10 | 0.140889E+10 | 0.141520E+10 | 0.350784E+10 | 0.130630E+10 |
Minimum of Months | 0.165794E+09 | 25343284.63 | 70925763.74 | 0.226549E+09 | 21498853.09 |
Maximum of Months | 0.356445E+09 | 0.223517E+09 | 0.150858E+09 | 0.459464E+09 | 0.205710E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.225599E+09 | 0.147724E+09 | 77875216.61 | 0.234690E+09 | 0.205710E+09 |
February | 0.268761E+09 | 0.177898E+09 | 90863136.84 | 0.285747E+09 | 0.184247E+09 |
March | 0.268453E+09 | 0.148996E+09 | 0.119457E+09 | 0.304099E+09 | 0.145789E+09 |
April | 0.201590E+09 | 79714779.59 | 0.121875E+09 | 0.237547E+09 | 0.104705E+09 |
May | 0.182553E+09 | 38077600.21 | 0.144475E+09 | 0.226549E+09 | 71163996.59 |
June | 0.165794E+09 | 25343284.63 | 0.140450E+09 | 0.231421E+09 | 39452048.69 |
July | 0.179578E+09 | 31192634.82 | 0.148385E+09 | 0.276880E+09 | 21498853.09 |
August | 0.239806E+09 | 88948202.50 | 0.150858E+09 | 0.370253E+09 | 31217952.05 |
September | 0.251801E+09 | 0.130242E+09 | 0.121559E+09 | 0.345854E+09 | 60383337.46 |
October | 0.356445E+09 | 0.223517E+09 | 0.132928E+09 | 0.459464E+09 | 0.109051E+09 |
November | 0.239191E+09 | 0.143646E+09 | 95545382.05 | 0.270127E+09 | 0.144488E+09 |
December | 0.244515E+09 | 0.173590E+09 | 70925763.74 | 0.265206E+09 | 0.188592E+09 |
Annual Sum or Average | 0.282409E+10 | 0.140889E+10 | 0.141520E+10 | 0.350784E+10 | 0.130630E+10 |
Minimum of Months | 0.165794E+09 | 25343284.63 | 70925763.74 | 0.226549E+09 | 21498853.09 |
Maximum of Months | 0.356445E+09 | 0.223517E+09 | 0.150858E+09 | 0.459464E+09 | 0.205710E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.225599E+09 | 0.147724E+09 | 77875216.61 | 0.234690E+09 | 0.205710E+09 |
February | 0.268761E+09 | 0.177898E+09 | 90863136.84 | 0.285747E+09 | 0.184247E+09 |
March | 0.268453E+09 | 0.148996E+09 | 0.119457E+09 | 0.304099E+09 | 0.145789E+09 |
April | 0.201590E+09 | 79714779.59 | 0.121875E+09 | 0.237547E+09 | 0.104705E+09 |
May | 0.182553E+09 | 38077600.21 | 0.144475E+09 | 0.226549E+09 | 71163996.59 |
June | 0.165794E+09 | 25343284.63 | 0.140450E+09 | 0.231421E+09 | 39452048.69 |
July | 0.179578E+09 | 31192634.82 | 0.148385E+09 | 0.276880E+09 | 21498853.09 |
August | 0.239806E+09 | 88948202.50 | 0.150858E+09 | 0.370253E+09 | 31217952.05 |
September | 0.251801E+09 | 0.130242E+09 | 0.121559E+09 | 0.345854E+09 | 60383337.46 |
October | 0.356445E+09 | 0.223517E+09 | 0.132928E+09 | 0.459464E+09 | 0.109051E+09 |
November | 0.239191E+09 | 0.143646E+09 | 95545382.05 | 0.270127E+09 | 0.144488E+09 |
December | 0.244515E+09 | 0.173590E+09 | 70925763.74 | 0.265206E+09 | 0.188592E+09 |
Annual Sum or Average | 0.282409E+10 | 0.140889E+10 | 0.141520E+10 | 0.350784E+10 | 0.130630E+10 |
Minimum of Months | 0.165794E+09 | 25343284.63 | 70925763.74 | 0.226549E+09 | 21498853.09 |
Maximum of Months | 0.356445E+09 | 0.223517E+09 | 0.150858E+09 | 0.459464E+09 | 0.205710E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.225599E+09 | 0.147724E+09 | 77875216.61 | 0.234690E+09 | 0.205710E+09 |
February | 0.268761E+09 | 0.177898E+09 | 90863136.84 | 0.285747E+09 | 0.184247E+09 |
March | 0.268453E+09 | 0.148996E+09 | 0.119457E+09 | 0.304099E+09 | 0.145789E+09 |
April | 0.201590E+09 | 79714779.59 | 0.121875E+09 | 0.237547E+09 | 0.104705E+09 |
May | 0.182553E+09 | 38077600.21 | 0.144475E+09 | 0.226549E+09 | 71163996.59 |
June | 0.165794E+09 | 25343284.63 | 0.140450E+09 | 0.231421E+09 | 39452048.69 |
July | 0.179578E+09 | 31192634.82 | 0.148385E+09 | 0.276880E+09 | 21498853.09 |
August | 0.239806E+09 | 88948202.50 | 0.150858E+09 | 0.370253E+09 | 31217952.05 |
September | 0.251801E+09 | 0.130242E+09 | 0.121559E+09 | 0.345854E+09 | 60383337.46 |
October | 0.356445E+09 | 0.223517E+09 | 0.132928E+09 | 0.459464E+09 | 0.109051E+09 |
November | 0.239191E+09 | 0.143646E+09 | 95545382.05 | 0.270127E+09 | 0.144488E+09 |
December | 0.244515E+09 | 0.173590E+09 | 70925763.74 | 0.265206E+09 | 0.188592E+09 |
Annual Sum or Average | 0.282409E+10 | 0.140889E+10 | 0.141520E+10 | 0.350784E+10 | 0.130630E+10 |
Minimum of Months | 0.165794E+09 | 25343284.63 | 70925763.74 | 0.226549E+09 | 21498853.09 |
Maximum of Months | 0.356445E+09 | 0.223517E+09 | 0.150858E+09 | 0.459464E+09 | 0.205710E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.269723E+09 | 0.176616E+09 | 93106425.56 | 0.281672E+09 | 0.242939E+09 |
February | 0.321327E+09 | 0.212692E+09 | 0.108635E+09 | 0.342790E+09 | 0.217646E+09 |
March | 0.320958E+09 | 0.178137E+09 | 0.142821E+09 | 0.364720E+09 | 0.172196E+09 |
April | 0.241018E+09 | 95305779.10 | 0.145712E+09 | 0.284828E+09 | 0.123884E+09 |
May | 0.218257E+09 | 45525000.17 | 0.172732E+09 | 0.271470E+09 | 84349070.11 |
June | 0.198220E+09 | 30300045.98 | 0.167920E+09 | 0.276771E+09 | 46903173.31 |
July | 0.214701E+09 | 37293440.18 | 0.177407E+09 | 0.330712E+09 | 25704997.68 |
August | 0.286709E+09 | 0.106345E+09 | 0.180364E+09 | 0.442206E+09 | 37329020.76 |
September | 0.301050E+09 | 0.155715E+09 | 0.145335E+09 | 0.413599E+09 | 71784409.29 |
October | 0.426160E+09 | 0.267233E+09 | 0.158927E+09 | 0.550018E+09 | 0.129395E+09 |
November | 0.285973E+09 | 0.171741E+09 | 0.114233E+09 | 0.323788E+09 | 0.170978E+09 |
December | 0.292339E+09 | 0.207541E+09 | 84797765.31 | 0.318003E+09 | 0.222912E+09 |
Annual Sum or Average | 0.337643E+10 | 0.168444E+10 | 0.169199E+10 | 0.420058E+10 | 0.154602E+10 |
Minimum of Months | 0.198220E+09 | 30300045.98 | 84797765.31 | 0.271470E+09 | 25704997.68 |
Maximum of Months | 0.426160E+09 | 0.267233E+09 | 0.180364E+09 | 0.550018E+09 | 0.242939E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.269723E+09 | 0.176616E+09 | 93106425.56 | 0.281672E+09 | 0.242939E+09 |
February | 0.321327E+09 | 0.212692E+09 | 0.108635E+09 | 0.342790E+09 | 0.217646E+09 |
March | 0.320958E+09 | 0.178137E+09 | 0.142821E+09 | 0.364720E+09 | 0.172196E+09 |
April | 0.241018E+09 | 95305779.10 | 0.145712E+09 | 0.284828E+09 | 0.123884E+09 |
May | 0.218257E+09 | 45525000.17 | 0.172732E+09 | 0.271470E+09 | 84349070.11 |
June | 0.198220E+09 | 30300045.98 | 0.167920E+09 | 0.276771E+09 | 46903173.31 |
July | 0.214701E+09 | 37293440.18 | 0.177407E+09 | 0.330712E+09 | 25704997.68 |
August | 0.286709E+09 | 0.106345E+09 | 0.180364E+09 | 0.442206E+09 | 37329020.76 |
September | 0.301050E+09 | 0.155715E+09 | 0.145335E+09 | 0.413599E+09 | 71784409.29 |
October | 0.426160E+09 | 0.267233E+09 | 0.158927E+09 | 0.550018E+09 | 0.129395E+09 |
November | 0.285973E+09 | 0.171741E+09 | 0.114233E+09 | 0.323788E+09 | 0.170978E+09 |
December | 0.292339E+09 | 0.207541E+09 | 84797765.31 | 0.318003E+09 | 0.222912E+09 |
Annual Sum or Average | 0.337643E+10 | 0.168444E+10 | 0.169199E+10 | 0.420058E+10 | 0.154602E+10 |
Minimum of Months | 0.198220E+09 | 30300045.98 | 84797765.31 | 0.271470E+09 | 25704997.68 |
Maximum of Months | 0.426160E+09 | 0.267233E+09 | 0.180364E+09 | 0.550018E+09 | 0.242939E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.225599E+09 | 0.147724E+09 | 77875216.61 | 0.233895E+09 | 0.206892E+09 |
February | 0.268761E+09 | 0.177898E+09 | 90863136.84 | 0.284916E+09 | 0.185109E+09 |
March | 0.268453E+09 | 0.148996E+09 | 0.119457E+09 | 0.303305E+09 | 0.146112E+09 |
April | 0.201590E+09 | 79714779.59 | 0.121875E+09 | 0.237155E+09 | 0.104504E+09 |
May | 0.182553E+09 | 38077600.21 | 0.144475E+09 | 0.226617E+09 | 70499358.60 |
June | 0.165794E+09 | 25343284.63 | 0.140450E+09 | 0.231442E+09 | 38929555.78 |
July | 0.179578E+09 | 31192634.82 | 0.148385E+09 | 0.277123E+09 | 20813669.78 |
August | 0.239806E+09 | 88948202.50 | 0.150858E+09 | 0.370427E+09 | 30442688.61 |
September | 0.251801E+09 | 0.130242E+09 | 0.121559E+09 | 0.345641E+09 | 59799183.27 |
October | 0.356445E+09 | 0.223517E+09 | 0.132928E+09 | 0.458970E+09 | 0.108482E+09 |
November | 0.239191E+09 | 0.143646E+09 | 95545382.05 | 0.269688E+09 | 0.144562E+09 |
December | 0.244515E+09 | 0.173590E+09 | 70925763.74 | 0.264532E+09 | 0.189312E+09 |
Annual Sum or Average | 0.282409E+10 | 0.140889E+10 | 0.141520E+10 | 0.350371E+10 | 0.130546E+10 |
Minimum of Months | 0.165794E+09 | 25343284.63 | 70925763.74 | 0.226617E+09 | 20813669.78 |
Maximum of Months | 0.356445E+09 | 0.223517E+09 | 0.150858E+09 | 0.458970E+09 | 0.206892E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.225599E+09 | 0.147724E+09 | 77875216.61 | 0.233895E+09 | 0.206892E+09 |
February | 0.268761E+09 | 0.177898E+09 | 90863136.84 | 0.284916E+09 | 0.185109E+09 |
March | 0.268453E+09 | 0.148996E+09 | 0.119457E+09 | 0.303305E+09 | 0.146112E+09 |
April | 0.201590E+09 | 79714779.59 | 0.121875E+09 | 0.237155E+09 | 0.104504E+09 |
May | 0.182553E+09 | 38077600.21 | 0.144475E+09 | 0.226617E+09 | 70499358.60 |
June | 0.165794E+09 | 25343284.63 | 0.140450E+09 | 0.231442E+09 | 38929555.78 |
July | 0.179578E+09 | 31192634.82 | 0.148385E+09 | 0.277123E+09 | 20813669.78 |
August | 0.239806E+09 | 88948202.50 | 0.150858E+09 | 0.370427E+09 | 30442688.61 |
September | 0.251801E+09 | 0.130242E+09 | 0.121559E+09 | 0.345641E+09 | 59799183.27 |
October | 0.356445E+09 | 0.223517E+09 | 0.132928E+09 | 0.458970E+09 | 0.108482E+09 |
November | 0.239191E+09 | 0.143646E+09 | 95545382.05 | 0.269688E+09 | 0.144562E+09 |
December | 0.244515E+09 | 0.173590E+09 | 70925763.74 | 0.264532E+09 | 0.189312E+09 |
Annual Sum or Average | 0.282409E+10 | 0.140889E+10 | 0.141520E+10 | 0.350371E+10 | 0.130546E+10 |
Minimum of Months | 0.165794E+09 | 25343284.63 | 70925763.74 | 0.226617E+09 | 20813669.78 |
Maximum of Months | 0.356445E+09 | 0.223517E+09 | 0.150858E+09 | 0.458970E+09 | 0.206892E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.269723E+09 | 0.176616E+09 | 93106425.56 | 0.280816E+09 | 0.244228E+09 |
February | 0.321327E+09 | 0.212692E+09 | 0.108635E+09 | 0.341910E+09 | 0.218567E+09 |
March | 0.320958E+09 | 0.178137E+09 | 0.142821E+09 | 0.363892E+09 | 0.172495E+09 |
April | 0.241018E+09 | 95305779.10 | 0.145712E+09 | 0.284449E+09 | 0.123601E+09 |
May | 0.218257E+09 | 45525000.17 | 0.172732E+09 | 0.271631E+09 | 83540021.44 |
June | 0.198220E+09 | 30300045.98 | 0.167920E+09 | 0.276849E+09 | 46285236.42 |
July | 0.214701E+09 | 37293440.18 | 0.177407E+09 | 0.331042E+09 | 24905937.74 |
August | 0.286709E+09 | 0.106345E+09 | 0.180364E+09 | 0.442468E+09 | 36425448.19 |
September | 0.301050E+09 | 0.155715E+09 | 0.145335E+09 | 0.413426E+09 | 71089050.01 |
October | 0.426160E+09 | 0.267233E+09 | 0.158927E+09 | 0.549552E+09 | 0.128694E+09 |
November | 0.285973E+09 | 0.171741E+09 | 0.114233E+09 | 0.323357E+09 | 0.171003E+09 |
December | 0.292339E+09 | 0.207541E+09 | 84797765.31 | 0.317290E+09 | 0.223670E+09 |
Annual Sum or Average | 0.337643E+10 | 0.168444E+10 | 0.169199E+10 | 0.419668E+10 | 0.154450E+10 |
Minimum of Months | 0.198220E+09 | 30300045.98 | 84797765.31 | 0.271631E+09 | 24905937.74 |
Maximum of Months | 0.426160E+09 | 0.267233E+09 | 0.180364E+09 | 0.549552E+09 | 0.244228E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.225599E+09 | 0.147724E+09 | 77875216.61 | 0.234015E+09 | 0.206357E+09 |
February | 0.268761E+09 | 0.177898E+09 | 90863136.84 | 0.285079E+09 | 0.184553E+09 |
March | 0.268453E+09 | 0.148996E+09 | 0.119457E+09 | 0.303543E+09 | 0.145404E+09 |
April | 0.201590E+09 | 79714779.59 | 0.121875E+09 | 0.237546E+09 | 0.103734E+09 |
May | 0.182553E+09 | 38077600.21 | 0.144475E+09 | 0.227344E+09 | 69590527.53 |
June | 0.165794E+09 | 25343284.63 | 0.140450E+09 | 0.231655E+09 | 38667541.12 |
July | 0.179578E+09 | 31192634.82 | 0.148385E+09 | 0.277308E+09 | 20609694.02 |
August | 0.239806E+09 | 88948202.50 | 0.150858E+09 | 0.370580E+09 | 30241604.76 |
September | 0.251801E+09 | 0.130242E+09 | 0.121559E+09 | 0.345802E+09 | 59498198.36 |
October | 0.356445E+09 | 0.223517E+09 | 0.132928E+09 | 0.459368E+09 | 0.107792E+09 |
November | 0.239191E+09 | 0.143646E+09 | 95545382.05 | 0.269975E+09 | 0.143889E+09 |
December | 0.244515E+09 | 0.173590E+09 | 70925763.74 | 0.264701E+09 | 0.188668E+09 |
Annual Sum or Average | 0.282409E+10 | 0.140889E+10 | 0.141520E+10 | 0.350692E+10 | 0.129900E+10 |
Minimum of Months | 0.165794E+09 | 25343284.63 | 70925763.74 | 0.227344E+09 | 20609694.02 |
Maximum of Months | 0.356445E+09 | 0.223517E+09 | 0.150858E+09 | 0.459368E+09 | 0.206357E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.225599E+09 | 0.147724E+09 | 77875216.61 | 0.234015E+09 | 0.206357E+09 |
February | 0.268761E+09 | 0.177898E+09 | 90863136.84 | 0.285079E+09 | 0.184553E+09 |
March | 0.268453E+09 | 0.148996E+09 | 0.119457E+09 | 0.303543E+09 | 0.145404E+09 |
April | 0.201590E+09 | 79714779.59 | 0.121875E+09 | 0.237546E+09 | 0.103734E+09 |
May | 0.182553E+09 | 38077600.21 | 0.144475E+09 | 0.227344E+09 | 69590527.53 |
June | 0.165794E+09 | 25343284.63 | 0.140450E+09 | 0.231655E+09 | 38667541.12 |
July | 0.179578E+09 | 31192634.82 | 0.148385E+09 | 0.277308E+09 | 20609694.02 |
August | 0.239806E+09 | 88948202.50 | 0.150858E+09 | 0.370580E+09 | 30241604.76 |
September | 0.251801E+09 | 0.130242E+09 | 0.121559E+09 | 0.345802E+09 | 59498198.36 |
October | 0.356445E+09 | 0.223517E+09 | 0.132928E+09 | 0.459368E+09 | 0.107792E+09 |
November | 0.239191E+09 | 0.143646E+09 | 95545382.05 | 0.269975E+09 | 0.143889E+09 |
December | 0.244515E+09 | 0.173590E+09 | 70925763.74 | 0.264701E+09 | 0.188668E+09 |
Annual Sum or Average | 0.282409E+10 | 0.140889E+10 | 0.141520E+10 | 0.350692E+10 | 0.129900E+10 |
Minimum of Months | 0.165794E+09 | 25343284.63 | 70925763.74 | 0.227344E+09 | 20609694.02 |
Maximum of Months | 0.356445E+09 | 0.223517E+09 | 0.150858E+09 | 0.459368E+09 | 0.206357E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.269723E+09 | 0.176616E+09 | 93106425.56 | 0.280962E+09 | 0.243594E+09 |
February | 0.321327E+09 | 0.212692E+09 | 0.108635E+09 | 0.342107E+09 | 0.217907E+09 |
March | 0.320958E+09 | 0.178137E+09 | 0.142821E+09 | 0.364179E+09 | 0.171656E+09 |
April | 0.241018E+09 | 95305779.10 | 0.145712E+09 | 0.284918E+09 | 0.122691E+09 |
May | 0.218257E+09 | 45525000.17 | 0.172732E+09 | 0.272498E+09 | 82467299.30 |
June | 0.198220E+09 | 30300045.98 | 0.167920E+09 | 0.277104E+09 | 45975561.98 |
July | 0.214701E+09 | 37293440.18 | 0.177407E+09 | 0.331264E+09 | 24664990.42 |
August | 0.286709E+09 | 0.106345E+09 | 0.180364E+09 | 0.442651E+09 | 36186435.92 |
September | 0.301050E+09 | 0.155715E+09 | 0.145335E+09 | 0.413619E+09 | 70732075.90 |
October | 0.426160E+09 | 0.267233E+09 | 0.158927E+09 | 0.550028E+09 | 0.127879E+09 |
November | 0.285973E+09 | 0.171741E+09 | 0.114233E+09 | 0.323699E+09 | 0.170205E+09 |
December | 0.292339E+09 | 0.207541E+09 | 84797765.31 | 0.317495E+09 | 0.222906E+09 |
Annual Sum or Average | 0.337643E+10 | 0.168444E+10 | 0.169199E+10 | 0.420053E+10 | 0.153687E+10 |
Minimum of Months | 0.198220E+09 | 30300045.98 | 84797765.31 | 0.272498E+09 | 24664990.42 |
Maximum of Months | 0.426160E+09 | 0.267233E+09 | 0.180364E+09 | 0.550028E+09 | 0.243594E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.225599E+09 | 0.147724E+09 | 77875216.61 | 0.234521E+09 | 0.203729E+09 |
February | 0.268761E+09 | 0.177898E+09 | 90863136.84 | 0.285733E+09 | 0.182017E+09 |
March | 0.268453E+09 | 0.148996E+09 | 0.119457E+09 | 0.304337E+09 | 0.142697E+09 |
April | 0.201590E+09 | 79714779.59 | 0.121875E+09 | 0.238576E+09 | 0.101290E+09 |
May | 0.182553E+09 | 38077600.21 | 0.144475E+09 | 0.229050E+09 | 67329031.93 |
June | 0.165794E+09 | 25343284.63 | 0.140450E+09 | 0.232136E+09 | 37947474.28 |
July | 0.179578E+09 | 31192634.82 | 0.148385E+09 | 0.277548E+09 | 20228001.63 |
August | 0.239806E+09 | 88948202.50 | 0.150858E+09 | 0.370703E+09 | 29928258.22 |
September | 0.251801E+09 | 0.130242E+09 | 0.121559E+09 | 0.346118E+09 | 58760487.07 |
October | 0.356445E+09 | 0.223517E+09 | 0.132928E+09 | 0.460291E+09 | 0.106053E+09 |
November | 0.239191E+09 | 0.143646E+09 | 95545382.05 | 0.270739E+09 | 0.141787E+09 |
December | 0.244515E+09 | 0.173590E+09 | 70925763.74 | 0.265316E+09 | 0.186041E+09 |
Annual Sum or Average | 0.282409E+10 | 0.140889E+10 | 0.141520E+10 | 0.351507E+10 | 0.127781E+10 |
Minimum of Months | 0.165794E+09 | 25343284.63 | 70925763.74 | 0.229050E+09 | 20228001.63 |
Maximum of Months | 0.356445E+09 | 0.223517E+09 | 0.150858E+09 | 0.460291E+09 | 0.203729E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.225599E+09 | 0.147724E+09 | 77875216.61 | 0.234521E+09 | 0.203729E+09 |
February | 0.268761E+09 | 0.177898E+09 | 90863136.84 | 0.285733E+09 | 0.182017E+09 |
March | 0.268453E+09 | 0.148996E+09 | 0.119457E+09 | 0.304337E+09 | 0.142697E+09 |
April | 0.201590E+09 | 79714779.59 | 0.121875E+09 | 0.238576E+09 | 0.101290E+09 |
May | 0.182553E+09 | 38077600.21 | 0.144475E+09 | 0.229050E+09 | 67329031.93 |
June | 0.165794E+09 | 25343284.63 | 0.140450E+09 | 0.232136E+09 | 37947474.28 |
July | 0.179578E+09 | 31192634.82 | 0.148385E+09 | 0.277548E+09 | 20228001.63 |
August | 0.239806E+09 | 88948202.50 | 0.150858E+09 | 0.370703E+09 | 29928258.22 |
September | 0.251801E+09 | 0.130242E+09 | 0.121559E+09 | 0.346118E+09 | 58760487.07 |
October | 0.356445E+09 | 0.223517E+09 | 0.132928E+09 | 0.460291E+09 | 0.106053E+09 |
November | 0.239191E+09 | 0.143646E+09 | 95545382.05 | 0.270739E+09 | 0.141787E+09 |
December | 0.244515E+09 | 0.173590E+09 | 70925763.74 | 0.265316E+09 | 0.186041E+09 |
Annual Sum or Average | 0.282409E+10 | 0.140889E+10 | 0.141520E+10 | 0.351507E+10 | 0.127781E+10 |
Minimum of Months | 0.165794E+09 | 25343284.63 | 70925763.74 | 0.229050E+09 | 20228001.63 |
Maximum of Months | 0.356445E+09 | 0.223517E+09 | 0.150858E+09 | 0.460291E+09 | 0.203729E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.269723E+09 | 0.176616E+09 | 93106425.56 | 0.281574E+09 | 0.240482E+09 |
February | 0.321327E+09 | 0.212692E+09 | 0.108635E+09 | 0.342896E+09 | 0.214904E+09 |
March | 0.320958E+09 | 0.178137E+09 | 0.142821E+09 | 0.365140E+09 | 0.168456E+09 |
April | 0.241018E+09 | 95305779.10 | 0.145712E+09 | 0.286152E+09 | 0.119807E+09 |
May | 0.218257E+09 | 45525000.17 | 0.172732E+09 | 0.274531E+09 | 79802070.33 |
June | 0.198220E+09 | 30300045.98 | 0.167920E+09 | 0.277678E+09 | 45130014.00 |
July | 0.214701E+09 | 37293440.18 | 0.177407E+09 | 0.331550E+09 | 24218614.68 |
August | 0.286709E+09 | 0.106345E+09 | 0.180364E+09 | 0.442797E+09 | 35820436.35 |
September | 0.301050E+09 | 0.155715E+09 | 0.145335E+09 | 0.413997E+09 | 69864150.24 |
October | 0.426160E+09 | 0.267233E+09 | 0.158927E+09 | 0.551127E+09 | 0.125829E+09 |
November | 0.285973E+09 | 0.171741E+09 | 0.114233E+09 | 0.324616E+09 | 0.167721E+09 |
December | 0.292339E+09 | 0.207541E+09 | 84797765.31 | 0.318238E+09 | 0.219797E+09 |
Annual Sum or Average | 0.337643E+10 | 0.168444E+10 | 0.169199E+10 | 0.421030E+10 | 0.151183E+10 |
Minimum of Months | 0.198220E+09 | 30300045.98 | 84797765.31 | 0.274531E+09 | 24218614.68 |
Maximum of Months | 0.426160E+09 | 0.267233E+09 | 0.180364E+09 | 0.551127E+09 | 0.240482E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.225599E+09 | 0.147724E+09 | 77875216.61 | 0.236499E+09 | 0.192213E+09 |
February | 0.268761E+09 | 0.177898E+09 | 90863136.84 | 0.288215E+09 | 0.170985E+09 |
March | 0.268453E+09 | 0.148996E+09 | 0.119457E+09 | 0.306969E+09 | 0.131640E+09 |
April | 0.201590E+09 | 79714779.59 | 0.121875E+09 | 0.241160E+09 | 92461921.48 |
May | 0.182553E+09 | 38077600.21 | 0.144475E+09 | 0.232695E+09 | 60751957.20 |
June | 0.165794E+09 | 25343284.63 | 0.140450E+09 | 0.233346E+09 | 35073299.25 |
July | 0.179578E+09 | 31192634.82 | 0.148385E+09 | 0.277447E+09 | 19080545.17 |
August | 0.239806E+09 | 88948202.50 | 0.150858E+09 | 0.370056E+09 | 29017379.81 |
September | 0.251801E+09 | 0.130242E+09 | 0.121559E+09 | 0.346554E+09 | 56265827.02 |
October | 0.356445E+09 | 0.223517E+09 | 0.132928E+09 | 0.462070E+09 | 0.100670E+09 |
November | 0.239191E+09 | 0.143646E+09 | 95545382.05 | 0.272839E+09 | 0.134119E+09 |
December | 0.244515E+09 | 0.173590E+09 | 70925763.74 | 0.267502E+09 | 0.175189E+09 |
Annual Sum or Average | 0.282409E+10 | 0.140889E+10 | 0.141520E+10 | 0.353535E+10 | 0.119747E+10 |
Minimum of Months | 0.165794E+09 | 25343284.63 | 70925763.74 | 0.232695E+09 | 19080545.17 |
Maximum of Months | 0.356445E+09 | 0.223517E+09 | 0.150858E+09 | 0.462070E+09 | 0.192213E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.225599E+09 | 0.147724E+09 | 77875216.61 | 0.236499E+09 | 0.192213E+09 |
February | 0.268761E+09 | 0.177898E+09 | 90863136.84 | 0.288215E+09 | 0.170985E+09 |
March | 0.268453E+09 | 0.148996E+09 | 0.119457E+09 | 0.306969E+09 | 0.131640E+09 |
April | 0.201590E+09 | 79714779.59 | 0.121875E+09 | 0.241160E+09 | 92461921.48 |
May | 0.182553E+09 | 38077600.21 | 0.144475E+09 | 0.232695E+09 | 60751957.20 |
June | 0.165794E+09 | 25343284.63 | 0.140450E+09 | 0.233346E+09 | 35073299.25 |
July | 0.179578E+09 | 31192634.82 | 0.148385E+09 | 0.277447E+09 | 19080545.17 |
August | 0.239806E+09 | 88948202.50 | 0.150858E+09 | 0.370056E+09 | 29017379.81 |
September | 0.251801E+09 | 0.130242E+09 | 0.121559E+09 | 0.346554E+09 | 56265827.02 |
October | 0.356445E+09 | 0.223517E+09 | 0.132928E+09 | 0.462070E+09 | 0.100670E+09 |
November | 0.239191E+09 | 0.143646E+09 | 95545382.05 | 0.272839E+09 | 0.134119E+09 |
December | 0.244515E+09 | 0.173590E+09 | 70925763.74 | 0.267502E+09 | 0.175189E+09 |
Annual Sum or Average | 0.282409E+10 | 0.140889E+10 | 0.141520E+10 | 0.353535E+10 | 0.119747E+10 |
Minimum of Months | 0.165794E+09 | 25343284.63 | 70925763.74 | 0.232695E+09 | 19080545.17 |
Maximum of Months | 0.356445E+09 | 0.223517E+09 | 0.150858E+09 | 0.462070E+09 | 0.192213E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.269723E+09 | 0.176616E+09 | 93106425.56 | 0.283971E+09 | 0.226861E+09 |
February | 0.321327E+09 | 0.212692E+09 | 0.108635E+09 | 0.345898E+09 | 0.201847E+09 |
March | 0.320958E+09 | 0.178137E+09 | 0.142821E+09 | 0.368327E+09 | 0.155404E+09 |
April | 0.241018E+09 | 95305779.10 | 0.145712E+09 | 0.289270E+09 | 0.109413E+09 |
May | 0.218257E+09 | 45525000.17 | 0.172732E+09 | 0.278878E+09 | 72048921.54 |
June | 0.198220E+09 | 30300045.98 | 0.167920E+09 | 0.279119E+09 | 41748261.55 |
July | 0.214701E+09 | 37293440.18 | 0.177407E+09 | 0.331419E+09 | 22865490.31 |
August | 0.286709E+09 | 0.106345E+09 | 0.180364E+09 | 0.442012E+09 | 34748621.40 |
September | 0.301050E+09 | 0.155715E+09 | 0.145335E+09 | 0.414513E+09 | 66924555.05 |
October | 0.426160E+09 | 0.267233E+09 | 0.158927E+09 | 0.553246E+09 | 0.119489E+09 |
November | 0.285973E+09 | 0.171741E+09 | 0.114233E+09 | 0.327140E+09 | 0.158678E+09 |
December | 0.292339E+09 | 0.207541E+09 | 84797765.31 | 0.320871E+09 | 0.206974E+09 |
Annual Sum or Average | 0.337643E+10 | 0.168444E+10 | 0.169199E+10 | 0.423467E+10 | 0.141700E+10 |
Minimum of Months | 0.198220E+09 | 30300045.98 | 84797765.31 | 0.278878E+09 | 22865490.31 |
Maximum of Months | 0.426160E+09 | 0.267233E+09 | 0.180364E+09 | 0.553246E+09 | 0.226861E+09 |
Report: WindowZoneSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 560.57 | 504.23 | 539.43 | 353.22 | 186.21 | 0.00 | 0.00 |
February | 757.01 | 495.29 | 711.49 | 470.95 | 240.54 | 0.00 | 0.00 |
March | 727.42 | 353.58 | 641.90 | 356.26 | 285.63 | 0.00 | 0.00 |
April | 585.92 | 262.78 | 498.09 | 196.96 | 301.13 | 0.00 | 0.00 |
May | 540.30 | 173.23 | 436.50 | 91.05 | 345.45 | 0.00 | 0.00 |
June | 573.44 | 94.35 | 409.64 | 62.62 | 347.02 | 0.00 | 0.00 |
July | 664.81 | 46.68 | 429.39 | 74.58 | 354.80 | 0.00 | 0.00 |
August | 887.26 | 70.04 | 573.40 | 212.68 | 360.72 | 0.00 | 0.00 |
September | 855.39 | 145.74 | 622.15 | 321.80 | 300.35 | 0.00 | 0.00 |
October | 1098.39 | 261.33 | 852.29 | 534.45 | 317.84 | 0.00 | 0.00 |
November | 665.62 | 364.89 | 590.99 | 354.92 | 236.07 | 0.00 | 0.00 |
December | 633.91 | 458.55 | 584.66 | 415.07 | 169.59 | 0.00 | 0.00 |
Annual Sum or Average | 712.60 | 267.94 | 573.51 | 286.12 | 287.40 | 0.00 | 0.00 |
Minimum of Months | 540.30 | 46.68 | 409.64 | 62.62 | 169.59 | 0.00 | 0.00 |
Maximum of Months | 1098.39 | 504.23 | 852.29 | 534.45 | 360.72 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 277.31 | 264.44 | 269.71 | 176.61 | 93.10 | 0.00 | 0.00 |
February | 374.47 | 260.39 | 355.74 | 235.47 | 120.27 | 0.00 | 0.00 |
March | 359.67 | 189.25 | 320.95 | 178.13 | 142.82 | 0.00 | 0.00 |
April | 288.50 | 142.21 | 249.04 | 98.48 | 150.56 | 0.00 | 0.00 |
May | 265.59 | 92.61 | 218.25 | 45.52 | 172.73 | 0.00 | 0.00 |
June | 285.76 | 48.48 | 204.82 | 31.31 | 173.51 | 0.00 | 0.00 |
July | 332.27 | 23.90 | 214.69 | 37.29 | 177.40 | 0.00 | 0.00 |
August | 443.79 | 35.26 | 286.70 | 106.34 | 180.36 | 0.00 | 0.00 |
September | 426.92 | 74.06 | 311.08 | 160.90 | 150.17 | 0.00 | 0.00 |
October | 545.95 | 136.13 | 426.15 | 267.22 | 158.92 | 0.00 | 0.00 |
November | 328.60 | 194.16 | 295.50 | 177.46 | 118.04 | 0.00 | 0.00 |
December | 313.92 | 241.66 | 292.33 | 207.53 | 84.80 | 0.00 | 0.00 |
Annual Sum or Average | 353.62 | 141.20 | 286.76 | 143.06 | 143.70 | 0.00 | 0.00 |
Minimum of Months | 265.59 | 23.90 | 204.82 | 31.31 | 84.80 | 0.00 | 0.00 |
Maximum of Months | 545.95 | 264.44 | 426.15 | 267.22 | 180.36 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 277.28 | 257.07 | 269.16 | 176.25 | 92.91 | 0.00 | 0.00 |
February | 374.07 | 253.86 | 355.01 | 234.99 | 120.02 | 0.00 | 0.00 |
March | 359.69 | 183.52 | 320.29 | 177.77 | 142.52 | 0.00 | 0.00 |
April | 288.93 | 138.20 | 248.53 | 98.28 | 150.26 | 0.00 | 0.00 |
May | 265.65 | 92.64 | 217.80 | 45.43 | 172.37 | 0.00 | 0.00 |
June | 284.61 | 51.84 | 204.40 | 31.24 | 173.16 | 0.00 | 0.00 |
July | 330.32 | 28.26 | 214.25 | 37.22 | 177.04 | 0.00 | 0.00 |
August | 441.66 | 39.92 | 286.11 | 106.12 | 179.99 | 0.00 | 0.00 |
September | 425.82 | 77.82 | 310.44 | 160.57 | 149.87 | 0.00 | 0.00 |
October | 545.62 | 136.27 | 425.27 | 266.68 | 158.60 | 0.00 | 0.00 |
November | 329.18 | 188.55 | 294.89 | 177.10 | 117.79 | 0.00 | 0.00 |
December | 313.82 | 235.12 | 291.73 | 207.11 | 84.62 | 0.00 | 0.00 |
Annual Sum or Average | 353.11 | 139.61 | 286.17 | 142.76 | 143.40 | 0.00 | 0.00 |
Minimum of Months | 265.65 | 28.26 | 204.40 | 31.24 | 84.62 | 0.00 | 0.00 |
Maximum of Months | 545.62 | 257.07 | 425.27 | 266.68 | 179.99 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 277.68 | 254.13 | 269.16 | 176.25 | 92.91 | 0.00 | 0.00 |
February | 374.51 | 251.28 | 355.01 | 234.99 | 120.02 | 0.00 | 0.00 |
March | 360.24 | 181.09 | 320.29 | 177.77 | 142.52 | 0.00 | 0.00 |
April | 289.69 | 135.98 | 248.53 | 98.28 | 150.26 | 0.00 | 0.00 |
May | 266.52 | 91.10 | 217.80 | 45.43 | 172.37 | 0.00 | 0.00 |
June | 284.68 | 51.69 | 204.40 | 31.24 | 173.16 | 0.00 | 0.00 |
July | 330.29 | 28.38 | 214.25 | 37.22 | 177.04 | 0.00 | 0.00 |
August | 441.60 | 40.13 | 286.11 | 106.12 | 179.99 | 0.00 | 0.00 |
September | 425.88 | 77.64 | 310.44 | 160.57 | 149.87 | 0.00 | 0.00 |
October | 546.13 | 134.96 | 425.27 | 266.68 | 158.60 | 0.00 | 0.00 |
November | 330.01 | 185.76 | 294.89 | 177.10 | 117.79 | 0.00 | 0.00 |
December | 314.20 | 232.55 | 291.73 | 207.11 | 84.62 | 0.00 | 0.00 |
Annual Sum or Average | 353.51 | 138.08 | 286.17 | 142.76 | 143.40 | 0.00 | 0.00 |
Minimum of Months | 266.52 | 28.38 | 204.40 | 31.24 | 84.62 | 0.00 | 0.00 |
Maximum of Months | 546.13 | 254.13 | 425.27 | 266.68 | 179.99 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 278.18 | 251.64 | 269.16 | 176.25 | 92.91 | 0.00 | 0.00 |
February | 375.12 | 249.00 | 355.01 | 234.99 | 120.02 | 0.00 | 0.00 |
March | 360.93 | 178.93 | 320.29 | 177.77 | 142.52 | 0.00 | 0.00 |
April | 290.74 | 133.77 | 248.53 | 98.28 | 150.26 | 0.00 | 0.00 |
May | 267.99 | 88.97 | 217.80 | 45.43 | 172.37 | 0.00 | 0.00 |
June | 285.11 | 50.89 | 204.40 | 31.24 | 173.16 | 0.00 | 0.00 |
July | 330.66 | 27.69 | 214.25 | 37.22 | 177.04 | 0.00 | 0.00 |
August | 441.93 | 39.41 | 286.11 | 106.12 | 179.99 | 0.00 | 0.00 |
September | 426.22 | 76.72 | 310.44 | 160.57 | 149.87 | 0.00 | 0.00 |
October | 546.94 | 133.28 | 425.27 | 266.68 | 158.60 | 0.00 | 0.00 |
November | 331.04 | 183.15 | 294.89 | 177.10 | 117.79 | 0.00 | 0.00 |
December | 314.69 | 230.30 | 291.73 | 207.11 | 84.62 | 0.00 | 0.00 |
Annual Sum or Average | 354.19 | 136.34 | 286.17 | 142.76 | 143.40 | 0.00 | 0.00 |
Minimum of Months | 267.99 | 27.69 | 204.40 | 31.24 | 84.62 | 0.00 | 0.00 |
Maximum of Months | 546.94 | 251.64 | 425.27 | 266.68 | 179.99 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 560.82 | 488.62 | 538.32 | 352.50 | 185.83 | 0.00 | 0.00 |
February | 755.86 | 484.57 | 710.03 | 469.98 | 240.05 | 0.00 | 0.00 |
March | 726.49 | 346.31 | 640.58 | 355.53 | 285.05 | 0.00 | 0.00 |
April | 586.36 | 257.17 | 497.07 | 196.56 | 300.51 | 0.00 | 0.00 |
May | 541.05 | 169.26 | 435.61 | 90.86 | 344.74 | 0.00 | 0.00 |
June | 570.69 | 97.07 | 408.80 | 62.49 | 346.31 | 0.00 | 0.00 |
July | 660.45 | 51.30 | 428.51 | 74.43 | 354.08 | 0.00 | 0.00 |
August | 883.15 | 74.50 | 572.22 | 212.25 | 359.98 | 0.00 | 0.00 |
September | 852.86 | 148.57 | 620.87 | 321.14 | 299.73 | 0.00 | 0.00 |
October | 1096.88 | 259.48 | 850.55 | 533.35 | 317.19 | 0.00 | 0.00 |
November | 666.70 | 354.90 | 589.78 | 354.19 | 235.59 | 0.00 | 0.00 |
December | 633.52 | 448.10 | 583.46 | 414.22 | 169.24 | 0.00 | 0.00 |
Annual Sum or Average | 711.33 | 263.74 | 572.34 | 285.53 | 286.81 | 0.00 | 0.00 |
Minimum of Months | 541.05 | 51.30 | 408.80 | 62.49 | 169.24 | 0.00 | 0.00 |
Maximum of Months | 1096.88 | 488.62 | 850.55 | 533.35 | 359.98 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 279.50 | 245.67 | 269.16 | 176.25 | 92.91 | 0.00 | 0.00 |
February | 376.88 | 243.38 | 355.01 | 234.99 | 120.02 | 0.00 | 0.00 |
March | 362.34 | 173.51 | 320.29 | 177.77 | 142.52 | 0.00 | 0.00 |
April | 292.73 | 128.32 | 248.53 | 98.28 | 150.26 | 0.00 | 0.00 |
May | 270.63 | 83.83 | 217.80 | 45.43 | 172.37 | 0.00 | 0.00 |
June | 285.39 | 47.90 | 204.40 | 31.24 | 173.16 | 0.00 | 0.00 |
July | 330.53 | 24.84 | 214.25 | 37.22 | 177.04 | 0.00 | 0.00 |
August | 441.80 | 36.33 | 286.11 | 106.12 | 179.99 | 0.00 | 0.00 |
September | 426.20 | 73.57 | 310.44 | 160.57 | 149.87 | 0.00 | 0.00 |
October | 547.90 | 129.05 | 425.27 | 266.68 | 158.60 | 0.00 | 0.00 |
November | 332.84 | 177.52 | 294.89 | 177.10 | 117.79 | 0.00 | 0.00 |
December | 315.99 | 224.87 | 291.73 | 207.11 | 84.62 | 0.00 | 0.00 |
Annual Sum or Average | 355.28 | 131.77 | 286.17 | 142.76 | 143.40 | 0.00 | 0.00 |
Minimum of Months | 270.63 | 24.84 | 204.40 | 31.24 | 84.62 | 0.00 | 0.00 |
Maximum of Months | 547.90 | 245.67 | 425.27 | 266.68 | 179.99 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 279.64 | 245.04 | 269.16 | 176.25 | 92.91 | 0.00 | 0.00 |
February | 377.09 | 242.65 | 355.01 | 234.99 | 120.02 | 0.00 | 0.00 |
March | 362.63 | 172.66 | 320.29 | 177.77 | 142.52 | 0.00 | 0.00 |
April | 293.21 | 127.38 | 248.53 | 98.28 | 150.26 | 0.00 | 0.00 |
May | 271.50 | 82.75 | 217.80 | 45.43 | 172.37 | 0.00 | 0.00 |
June | 285.65 | 47.57 | 204.40 | 31.24 | 173.16 | 0.00 | 0.00 |
July | 330.75 | 24.60 | 214.25 | 37.22 | 177.04 | 0.00 | 0.00 |
August | 441.98 | 36.09 | 286.11 | 106.12 | 179.99 | 0.00 | 0.00 |
September | 426.40 | 73.20 | 310.44 | 160.57 | 149.87 | 0.00 | 0.00 |
October | 548.37 | 128.23 | 425.27 | 266.68 | 158.60 | 0.00 | 0.00 |
November | 333.20 | 176.69 | 294.89 | 177.10 | 117.79 | 0.00 | 0.00 |
December | 316.19 | 224.10 | 291.73 | 207.11 | 84.62 | 0.00 | 0.00 |
Annual Sum or Average | 355.60 | 131.12 | 286.17 | 142.76 | 143.40 | 0.00 | 0.00 |
Minimum of Months | 271.50 | 24.60 | 204.40 | 31.24 | 84.62 | 0.00 | 0.00 |
Maximum of Months | 548.37 | 245.04 | 425.27 | 266.68 | 179.99 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 280.25 | 241.91 | 269.16 | 176.25 | 92.91 | 0.00 | 0.00 |
February | 377.96 | 239.31 | 355.01 | 234.99 | 120.02 | 0.00 | 0.00 |
March | 363.58 | 169.45 | 320.29 | 177.77 | 142.52 | 0.00 | 0.00 |
April | 294.48 | 124.38 | 248.53 | 98.28 | 150.26 | 0.00 | 0.00 |
May | 273.53 | 80.07 | 217.80 | 45.43 | 172.37 | 0.00 | 0.00 |
June | 286.25 | 46.69 | 204.40 | 31.24 | 173.16 | 0.00 | 0.00 |
July | 331.04 | 24.15 | 214.25 | 37.22 | 177.04 | 0.00 | 0.00 |
August | 442.13 | 35.72 | 286.11 | 106.12 | 179.99 | 0.00 | 0.00 |
September | 426.79 | 72.29 | 310.44 | 160.57 | 149.87 | 0.00 | 0.00 |
October | 549.47 | 126.17 | 425.27 | 266.68 | 158.60 | 0.00 | 0.00 |
November | 334.14 | 174.11 | 294.89 | 177.10 | 117.79 | 0.00 | 0.00 |
December | 316.93 | 220.98 | 291.73 | 207.11 | 84.62 | 0.00 | 0.00 |
Annual Sum or Average | 356.43 | 128.98 | 286.17 | 142.76 | 143.40 | 0.00 | 0.00 |
Minimum of Months | 273.53 | 24.15 | 204.40 | 31.24 | 84.62 | 0.00 | 0.00 |
Maximum of Months | 549.47 | 241.91 | 425.27 | 266.68 | 179.99 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 282.62 | 228.23 | 269.16 | 176.25 | 92.91 | 0.00 | 0.00 |
February | 381.25 | 224.79 | 355.01 | 234.99 | 120.02 | 0.00 | 0.00 |
March | 366.73 | 156.32 | 320.29 | 177.77 | 142.52 | 0.00 | 0.00 |
April | 297.68 | 113.56 | 248.53 | 98.28 | 150.26 | 0.00 | 0.00 |
May | 277.88 | 72.26 | 217.80 | 45.43 | 172.37 | 0.00 | 0.00 |
June | 287.74 | 43.17 | 204.40 | 31.24 | 173.16 | 0.00 | 0.00 |
July | 330.91 | 22.78 | 214.25 | 37.22 | 177.04 | 0.00 | 0.00 |
August | 441.35 | 34.64 | 286.11 | 106.12 | 179.99 | 0.00 | 0.00 |
September | 427.32 | 69.23 | 310.44 | 160.57 | 149.87 | 0.00 | 0.00 |
October | 551.59 | 119.78 | 425.27 | 266.68 | 158.60 | 0.00 | 0.00 |
November | 336.74 | 164.70 | 294.89 | 177.10 | 117.79 | 0.00 | 0.00 |
December | 319.55 | 208.09 | 291.73 | 207.11 | 84.62 | 0.00 | 0.00 |
Annual Sum or Average | 358.49 | 120.88 | 286.17 | 142.76 | 143.40 | 0.00 | 0.00 |
Minimum of Months | 277.88 | 22.78 | 204.40 | 31.24 | 84.62 | 0.00 | 0.00 |
Maximum of Months | 551.59 | 228.23 | 425.27 | 266.68 | 179.99 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.150142E+10 | 0.135052E+10 | 0.144480E+10 | 0.946067E+09 | 0.498737E+09 | 0.00 | 0.00 |
February | 0.183135E+10 | 0.119820E+10 | 0.172123E+10 | 0.113931E+10 | 0.581916E+09 | 0.00 | 0.00 |
March | 0.194832E+10 | 0.947038E+09 | 0.171925E+10 | 0.954216E+09 | 0.765038E+09 | 0.00 | 0.00 |
April | 0.151871E+10 | 0.681115E+09 | 0.129105E+10 | 0.510518E+09 | 0.780527E+09 | 0.00 | 0.00 |
May | 0.144714E+10 | 0.463982E+09 | 0.116912E+10 | 0.243861E+09 | 0.925263E+09 | 0.00 | 0.00 |
June | 0.148636E+10 | 0.244562E+09 | 0.106179E+10 | 0.162306E+09 | 0.899488E+09 | 0.00 | 0.00 |
July | 0.178062E+10 | 0.125023E+09 | 0.115007E+10 | 0.199767E+09 | 0.950305E+09 | 0.00 | 0.00 |
August | 0.237645E+10 | 0.187602E+09 | 0.153579E+10 | 0.569652E+09 | 0.966143E+09 | 0.00 | 0.00 |
September | 0.221718E+10 | 0.377760E+09 | 0.161261E+10 | 0.834110E+09 | 0.778504E+09 | 0.00 | 0.00 |
October | 0.294192E+10 | 0.699953E+09 | 0.228278E+10 | 0.143147E+10 | 0.851314E+09 | 0.00 | 0.00 |
November | 0.172528E+10 | 0.945797E+09 | 0.153185E+10 | 0.919951E+09 | 0.611902E+09 | 0.00 | 0.00 |
December | 0.169786E+10 | 0.122819E+10 | 0.156595E+10 | 0.111172E+10 | 0.454230E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.224726E+11 | 0.844975E+10 | 0.180863E+11 | 0.902295E+10 | 0.906337E+10 | 0.00 | 0.00 |
Minimum of Months | 0.144714E+10 | 0.125023E+09 | 0.106179E+10 | 0.162306E+09 | 0.454230E+09 | 0.00 | 0.00 |
Maximum of Months | 0.294192E+10 | 0.135052E+10 | 0.228278E+10 | 0.143147E+10 | 0.966143E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.742755E+09 | 0.708289E+09 | 0.722402E+09 | 0.473034E+09 | 0.249368E+09 | 0.00 | 0.00 |
February | 0.905912E+09 | 0.629928E+09 | 0.860615E+09 | 0.569657E+09 | 0.290958E+09 | 0.00 | 0.00 |
March | 0.963346E+09 | 0.506894E+09 | 0.859627E+09 | 0.477108E+09 | 0.382519E+09 | 0.00 | 0.00 |
April | 0.747797E+09 | 0.368604E+09 | 0.645523E+09 | 0.255259E+09 | 0.390264E+09 | 0.00 | 0.00 |
May | 0.711364E+09 | 0.248046E+09 | 0.584562E+09 | 0.121930E+09 | 0.462631E+09 | 0.00 | 0.00 |
June | 0.740681E+09 | 0.125664E+09 | 0.530897E+09 | 81153099.02 | 0.449744E+09 | 0.00 | 0.00 |
July | 0.889959E+09 | 64020086.49 | 0.575036E+09 | 99883618.84 | 0.475153E+09 | 0.00 | 0.00 |
August | 0.118864E+10 | 94448923.55 | 0.767897E+09 | 0.284826E+09 | 0.483071E+09 | 0.00 | 0.00 |
September | 0.110657E+10 | 0.191972E+09 | 0.806307E+09 | 0.417055E+09 | 0.389252E+09 | 0.00 | 0.00 |
October | 0.146226E+10 | 0.364611E+09 | 0.114139E+10 | 0.715735E+09 | 0.425657E+09 | 0.00 | 0.00 |
November | 0.851730E+09 | 0.503264E+09 | 0.765926E+09 | 0.459975E+09 | 0.305951E+09 | 0.00 | 0.00 |
December | 0.840797E+09 | 0.647263E+09 | 0.782976E+09 | 0.555860E+09 | 0.227115E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.111518E+11 | 0.445301E+10 | 0.904316E+10 | 0.451148E+10 | 0.453168E+10 | 0.00 | 0.00 |
Minimum of Months | 0.711364E+09 | 64020086.49 | 0.530897E+09 | 81153099.02 | 0.227115E+09 | 0.00 | 0.00 |
Maximum of Months | 0.146226E+10 | 0.708289E+09 | 0.114139E+10 | 0.715735E+09 | 0.483071E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.742657E+09 | 0.688526E+09 | 0.720920E+09 | 0.472063E+09 | 0.248857E+09 | 0.00 | 0.00 |
February | 0.904956E+09 | 0.614132E+09 | 0.858849E+09 | 0.568488E+09 | 0.290361E+09 | 0.00 | 0.00 |
March | 0.963402E+09 | 0.491545E+09 | 0.857863E+09 | 0.476129E+09 | 0.381734E+09 | 0.00 | 0.00 |
April | 0.748905E+09 | 0.358217E+09 | 0.644198E+09 | 0.254735E+09 | 0.389463E+09 | 0.00 | 0.00 |
May | 0.711506E+09 | 0.248137E+09 | 0.583362E+09 | 0.121680E+09 | 0.461682E+09 | 0.00 | 0.00 |
June | 0.737704E+09 | 0.134361E+09 | 0.529808E+09 | 80986615.25 | 0.448821E+09 | 0.00 | 0.00 |
July | 0.884729E+09 | 75684025.12 | 0.573856E+09 | 99678709.82 | 0.474178E+09 | 0.00 | 0.00 |
August | 0.118295E+10 | 0.106922E+09 | 0.766322E+09 | 0.284242E+09 | 0.482080E+09 | 0.00 | 0.00 |
September | 0.110371E+10 | 0.201718E+09 | 0.804653E+09 | 0.416199E+09 | 0.388454E+09 | 0.00 | 0.00 |
October | 0.146138E+10 | 0.364975E+09 | 0.113905E+10 | 0.714266E+09 | 0.424784E+09 | 0.00 | 0.00 |
November | 0.853237E+09 | 0.488715E+09 | 0.764355E+09 | 0.459032E+09 | 0.305323E+09 | 0.00 | 0.00 |
December | 0.840528E+09 | 0.629747E+09 | 0.781369E+09 | 0.554720E+09 | 0.226649E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.111357E+11 | 0.440268E+10 | 0.902461E+10 | 0.450222E+10 | 0.452239E+10 | 0.00 | 0.00 |
Minimum of Months | 0.711506E+09 | 75684025.12 | 0.529808E+09 | 80986615.25 | 0.226649E+09 | 0.00 | 0.00 |
Maximum of Months | 0.146138E+10 | 0.688526E+09 | 0.113905E+10 | 0.714266E+09 | 0.482080E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.743737E+09 | 0.680662E+09 | 0.720920E+09 | 0.472063E+09 | 0.248857E+09 | 0.00 | 0.00 |
February | 0.906012E+09 | 0.607891E+09 | 0.858849E+09 | 0.568488E+09 | 0.290361E+09 | 0.00 | 0.00 |
March | 0.964857E+09 | 0.485033E+09 | 0.857863E+09 | 0.476129E+09 | 0.381734E+09 | 0.00 | 0.00 |
April | 0.750868E+09 | 0.352466E+09 | 0.644198E+09 | 0.254735E+09 | 0.389463E+09 | 0.00 | 0.00 |
May | 0.713846E+09 | 0.243989E+09 | 0.583362E+09 | 0.121680E+09 | 0.461682E+09 | 0.00 | 0.00 |
June | 0.737896E+09 | 0.133993E+09 | 0.529808E+09 | 80986615.25 | 0.448821E+09 | 0.00 | 0.00 |
July | 0.884648E+09 | 76025270.15 | 0.573856E+09 | 99678709.82 | 0.474178E+09 | 0.00 | 0.00 |
August | 0.118279E+10 | 0.107490E+09 | 0.766322E+09 | 0.284242E+09 | 0.482080E+09 | 0.00 | 0.00 |
September | 0.110387E+10 | 0.201245E+09 | 0.804653E+09 | 0.416199E+09 | 0.388454E+09 | 0.00 | 0.00 |
October | 0.146275E+10 | 0.361489E+09 | 0.113905E+10 | 0.714266E+09 | 0.424784E+09 | 0.00 | 0.00 |
November | 0.855397E+09 | 0.481482E+09 | 0.764355E+09 | 0.459032E+09 | 0.305323E+09 | 0.00 | 0.00 |
December | 0.841561E+09 | 0.622850E+09 | 0.781369E+09 | 0.554720E+09 | 0.226649E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.111482E+11 | 0.435462E+10 | 0.902461E+10 | 0.450222E+10 | 0.452239E+10 | 0.00 | 0.00 |
Minimum of Months | 0.713846E+09 | 76025270.15 | 0.529808E+09 | 80986615.25 | 0.226649E+09 | 0.00 | 0.00 |
Maximum of Months | 0.146275E+10 | 0.680662E+09 | 0.113905E+10 | 0.714266E+09 | 0.482080E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.745090E+09 | 0.673989E+09 | 0.720920E+09 | 0.472063E+09 | 0.248857E+09 | 0.00 | 0.00 |
February | 0.907486E+09 | 0.602370E+09 | 0.858849E+09 | 0.568488E+09 | 0.290361E+09 | 0.00 | 0.00 |
March | 0.966727E+09 | 0.479246E+09 | 0.857863E+09 | 0.476129E+09 | 0.381734E+09 | 0.00 | 0.00 |
April | 0.753600E+09 | 0.346732E+09 | 0.644198E+09 | 0.254735E+09 | 0.389463E+09 | 0.00 | 0.00 |
May | 0.717788E+09 | 0.238290E+09 | 0.583362E+09 | 0.121680E+09 | 0.461682E+09 | 0.00 | 0.00 |
June | 0.739008E+09 | 0.131898E+09 | 0.529808E+09 | 80986615.25 | 0.448821E+09 | 0.00 | 0.00 |
July | 0.885651E+09 | 74171676.27 | 0.573856E+09 | 99678709.82 | 0.474178E+09 | 0.00 | 0.00 |
August | 0.118366E+10 | 0.105553E+09 | 0.766322E+09 | 0.284242E+09 | 0.482080E+09 | 0.00 | 0.00 |
September | 0.110476E+10 | 0.198848E+09 | 0.804653E+09 | 0.416199E+09 | 0.388454E+09 | 0.00 | 0.00 |
October | 0.146493E+10 | 0.356971E+09 | 0.113905E+10 | 0.714266E+09 | 0.424784E+09 | 0.00 | 0.00 |
November | 0.858050E+09 | 0.474735E+09 | 0.764355E+09 | 0.459032E+09 | 0.305323E+09 | 0.00 | 0.00 |
December | 0.842866E+09 | 0.616845E+09 | 0.781369E+09 | 0.554720E+09 | 0.226649E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.111696E+11 | 0.429965E+10 | 0.902461E+10 | 0.450222E+10 | 0.452239E+10 | 0.00 | 0.00 |
Minimum of Months | 0.717788E+09 | 74171676.27 | 0.529808E+09 | 80986615.25 | 0.226649E+09 | 0.00 | 0.00 |
Maximum of Months | 0.146493E+10 | 0.673989E+09 | 0.113905E+10 | 0.714266E+09 | 0.482080E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.150210E+10 | 0.130872E+10 | 0.144184E+10 | 0.944126E+09 | 0.497714E+09 | 0.00 | 0.00 |
February | 0.182857E+10 | 0.117228E+10 | 0.171770E+10 | 0.113698E+10 | 0.580722E+09 | 0.00 | 0.00 |
March | 0.194583E+10 | 0.927548E+09 | 0.171573E+10 | 0.952258E+09 | 0.763469E+09 | 0.00 | 0.00 |
April | 0.151984E+10 | 0.666588E+09 | 0.128840E+10 | 0.509471E+09 | 0.778926E+09 | 0.00 | 0.00 |
May | 0.144914E+10 | 0.453354E+09 | 0.116672E+10 | 0.243360E+09 | 0.923365E+09 | 0.00 | 0.00 |
June | 0.147922E+10 | 0.251614E+09 | 0.105962E+10 | 0.161973E+09 | 0.897643E+09 | 0.00 | 0.00 |
July | 0.176894E+10 | 0.137405E+09 | 0.114771E+10 | 0.199357E+09 | 0.948355E+09 | 0.00 | 0.00 |
August | 0.236542E+10 | 0.199529E+09 | 0.153264E+10 | 0.568483E+09 | 0.964161E+09 | 0.00 | 0.00 |
September | 0.221061E+10 | 0.385102E+09 | 0.160931E+10 | 0.832399E+09 | 0.776907E+09 | 0.00 | 0.00 |
October | 0.293789E+10 | 0.694995E+09 | 0.227810E+10 | 0.142853E+10 | 0.849568E+09 | 0.00 | 0.00 |
November | 0.172808E+10 | 0.919908E+09 | 0.152871E+10 | 0.918064E+09 | 0.610647E+09 | 0.00 | 0.00 |
December | 0.169683E+10 | 0.120019E+10 | 0.156274E+10 | 0.110944E+10 | 0.453299E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.224325E+11 | 0.831723E+10 | 0.180492E+11 | 0.900444E+10 | 0.904477E+10 | 0.00 | 0.00 |
Minimum of Months | 0.144914E+10 | 0.137405E+09 | 0.105962E+10 | 0.161973E+09 | 0.453299E+09 | 0.00 | 0.00 |
Maximum of Months | 0.293789E+10 | 0.130872E+10 | 0.227810E+10 | 0.142853E+10 | 0.964161E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.748605E+09 | 0.658011E+09 | 0.720920E+09 | 0.472063E+09 | 0.248857E+09 | 0.00 | 0.00 |
February | 0.911739E+09 | 0.588783E+09 | 0.858849E+09 | 0.568488E+09 | 0.290361E+09 | 0.00 | 0.00 |
March | 0.970499E+09 | 0.464717E+09 | 0.857863E+09 | 0.476129E+09 | 0.381734E+09 | 0.00 | 0.00 |
April | 0.758758E+09 | 0.332609E+09 | 0.644198E+09 | 0.254735E+09 | 0.389463E+09 | 0.00 | 0.00 |
May | 0.724865E+09 | 0.224538E+09 | 0.583362E+09 | 0.121680E+09 | 0.461682E+09 | 0.00 | 0.00 |
June | 0.739733E+09 | 0.124144E+09 | 0.529808E+09 | 80986615.25 | 0.448821E+09 | 0.00 | 0.00 |
July | 0.885287E+09 | 66533100.85 | 0.573856E+09 | 99678709.82 | 0.474178E+09 | 0.00 | 0.00 |
August | 0.118332E+10 | 97310208.42 | 0.766322E+09 | 0.284242E+09 | 0.482080E+09 | 0.00 | 0.00 |
September | 0.110471E+10 | 0.190687E+09 | 0.804653E+09 | 0.416199E+09 | 0.388454E+09 | 0.00 | 0.00 |
October | 0.146749E+10 | 0.345658E+09 | 0.113905E+10 | 0.714266E+09 | 0.424784E+09 | 0.00 | 0.00 |
November | 0.862732E+09 | 0.460126E+09 | 0.764355E+09 | 0.459032E+09 | 0.305323E+09 | 0.00 | 0.00 |
December | 0.846351E+09 | 0.602291E+09 | 0.781369E+09 | 0.554720E+09 | 0.226649E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.112041E+11 | 0.415541E+10 | 0.902461E+10 | 0.450222E+10 | 0.452239E+10 | 0.00 | 0.00 |
Minimum of Months | 0.724865E+09 | 66533100.85 | 0.529808E+09 | 80986615.25 | 0.226649E+09 | 0.00 | 0.00 |
Maximum of Months | 0.146749E+10 | 0.658011E+09 | 0.113905E+10 | 0.714266E+09 | 0.482080E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.748991E+09 | 0.656307E+09 | 0.720920E+09 | 0.472063E+09 | 0.248857E+09 | 0.00 | 0.00 |
February | 0.912264E+09 | 0.587011E+09 | 0.858849E+09 | 0.568488E+09 | 0.290361E+09 | 0.00 | 0.00 |
March | 0.971264E+09 | 0.462462E+09 | 0.857863E+09 | 0.476129E+09 | 0.381734E+09 | 0.00 | 0.00 |
April | 0.760008E+09 | 0.330157E+09 | 0.644198E+09 | 0.254735E+09 | 0.389463E+09 | 0.00 | 0.00 |
May | 0.727186E+09 | 0.221648E+09 | 0.583362E+09 | 0.121680E+09 | 0.461682E+09 | 0.00 | 0.00 |
June | 0.740414E+09 | 0.123310E+09 | 0.529808E+09 | 80986615.25 | 0.448821E+09 | 0.00 | 0.00 |
July | 0.885879E+09 | 65884261.48 | 0.573856E+09 | 99678709.82 | 0.474178E+09 | 0.00 | 0.00 |
August | 0.118381E+10 | 96668867.22 | 0.766322E+09 | 0.284242E+09 | 0.482080E+09 | 0.00 | 0.00 |
September | 0.110522E+10 | 0.189728E+09 | 0.804653E+09 | 0.416199E+09 | 0.388454E+09 | 0.00 | 0.00 |
October | 0.146876E+10 | 0.343464E+09 | 0.113905E+10 | 0.714266E+09 | 0.424784E+09 | 0.00 | 0.00 |
November | 0.863648E+09 | 0.457982E+09 | 0.764355E+09 | 0.459032E+09 | 0.305323E+09 | 0.00 | 0.00 |
December | 0.846894E+09 | 0.600239E+09 | 0.781369E+09 | 0.554720E+09 | 0.226649E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.112143E+11 | 0.413486E+10 | 0.902461E+10 | 0.450222E+10 | 0.452239E+10 | 0.00 | 0.00 |
Minimum of Months | 0.727186E+09 | 65884261.48 | 0.529808E+09 | 80986615.25 | 0.226649E+09 | 0.00 | 0.00 |
Maximum of Months | 0.146876E+10 | 0.656307E+09 | 0.113905E+10 | 0.714266E+09 | 0.482080E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.750615E+09 | 0.647938E+09 | 0.720920E+09 | 0.472063E+09 | 0.248857E+09 | 0.00 | 0.00 |
February | 0.914363E+09 | 0.578938E+09 | 0.858849E+09 | 0.568488E+09 | 0.290361E+09 | 0.00 | 0.00 |
March | 0.973812E+09 | 0.453848E+09 | 0.857863E+09 | 0.476129E+09 | 0.381734E+09 | 0.00 | 0.00 |
April | 0.763302E+09 | 0.322385E+09 | 0.644198E+09 | 0.254735E+09 | 0.389463E+09 | 0.00 | 0.00 |
May | 0.732631E+09 | 0.214460E+09 | 0.583362E+09 | 0.121680E+09 | 0.461682E+09 | 0.00 | 0.00 |
June | 0.741948E+09 | 0.121025E+09 | 0.529808E+09 | 80986615.25 | 0.448821E+09 | 0.00 | 0.00 |
July | 0.886647E+09 | 64674503.38 | 0.573856E+09 | 99678709.82 | 0.474178E+09 | 0.00 | 0.00 |
August | 0.118420E+10 | 95676179.74 | 0.766322E+09 | 0.284242E+09 | 0.482080E+09 | 0.00 | 0.00 |
September | 0.110623E+10 | 0.187385E+09 | 0.804653E+09 | 0.416199E+09 | 0.388454E+09 | 0.00 | 0.00 |
October | 0.147171E+10 | 0.337935E+09 | 0.113905E+10 | 0.714266E+09 | 0.424784E+09 | 0.00 | 0.00 |
November | 0.866092E+09 | 0.451294E+09 | 0.764355E+09 | 0.459032E+09 | 0.305323E+09 | 0.00 | 0.00 |
December | 0.848869E+09 | 0.591877E+09 | 0.781369E+09 | 0.554720E+09 | 0.226649E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.112404E+11 | 0.406744E+10 | 0.902461E+10 | 0.450222E+10 | 0.452239E+10 | 0.00 | 0.00 |
Minimum of Months | 0.732631E+09 | 64674503.38 | 0.529808E+09 | 80986615.25 | 0.226649E+09 | 0.00 | 0.00 |
Maximum of Months | 0.147171E+10 | 0.647938E+09 | 0.113905E+10 | 0.714266E+09 | 0.482080E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.756969E+09 | 0.611287E+09 | 0.720920E+09 | 0.472063E+09 | 0.248857E+09 | 0.00 | 0.00 |
February | 0.922328E+09 | 0.543815E+09 | 0.858849E+09 | 0.568488E+09 | 0.290361E+09 | 0.00 | 0.00 |
March | 0.982262E+09 | 0.418681E+09 | 0.857863E+09 | 0.476129E+09 | 0.381734E+09 | 0.00 | 0.00 |
April | 0.771590E+09 | 0.294336E+09 | 0.644198E+09 | 0.254735E+09 | 0.389463E+09 | 0.00 | 0.00 |
May | 0.744268E+09 | 0.193553E+09 | 0.583362E+09 | 0.121680E+09 | 0.461682E+09 | 0.00 | 0.00 |
June | 0.745811E+09 | 0.111895E+09 | 0.529808E+09 | 80986615.25 | 0.448821E+09 | 0.00 | 0.00 |
July | 0.886313E+09 | 61026528.12 | 0.573856E+09 | 99678709.82 | 0.474178E+09 | 0.00 | 0.00 |
August | 0.118212E+10 | 92782849.45 | 0.766322E+09 | 0.284242E+09 | 0.482080E+09 | 0.00 | 0.00 |
September | 0.110762E+10 | 0.179456E+09 | 0.804653E+09 | 0.416199E+09 | 0.388454E+09 | 0.00 | 0.00 |
October | 0.147739E+10 | 0.320828E+09 | 0.113905E+10 | 0.714266E+09 | 0.424784E+09 | 0.00 | 0.00 |
November | 0.872818E+09 | 0.426914E+09 | 0.764355E+09 | 0.459032E+09 | 0.305323E+09 | 0.00 | 0.00 |
December | 0.855874E+09 | 0.557350E+09 | 0.781369E+09 | 0.554720E+09 | 0.226649E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.113054E+11 | 0.381192E+10 | 0.902461E+10 | 0.450222E+10 | 0.452239E+10 | 0.00 | 0.00 |
Minimum of Months | 0.744268E+09 | 61026528.12 | 0.529808E+09 | 80986615.25 | 0.226649E+09 | 0.00 | 0.00 |
Maximum of Months | 0.147739E+10 | 0.611287E+09 | 0.113905E+10 | 0.714266E+09 | 0.482080E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 1.17 | -0.7 | -4.4 | 5.65 | -10.4 | 36.91 | 88.07 | 0.05 |
February | -0.2 | -2.6 | -7.5 | 5.07 | -13.4 | 46.98 | 136.68 | 0.04 |
March | 5.59 | 3.43 | 0.29 | 5.58 | -4.1 | 68.24 | 153.73 | 0.03 |
April | 10.94 | 8.00 | 4.75 | 4.99 | 0.53 | 82.64 | 161.98 | 0.05 |
May | 16.05 | 12.31 | 9.14 | 4.42 | 7.77 | 109.28 | 173.60 | 0.03 |
June | 21.71 | 18.08 | 15.84 | 4.92 | 13.23 | 112.36 | 186.51 | 0.01 |
July | 25.05 | 21.76 | 20.26 | 4.06 | 17.39 | 114.46 | 172.96 | 0.02 |
August | 24.79 | 19.84 | 17.14 | 4.19 | 14.42 | 95.56 | 226.16 | 0.00 |
September | 19.96 | 15.96 | 13.24 | 3.91 | 10.59 | 73.65 | 166.08 | 0.03 |
October | 14.02 | 11.03 | 7.95 | 4.86 | 2.64 | 61.34 | 179.75 | 0.00 |
November | 7.31 | 4.98 | 2.14 | 5.60 | -4.0 | 48.23 | 90.71 | 0.03 |
December | 3.33 | 0.91 | -2.8 | 5.64 | -8.5 | 30.23 | 98.59 | 0.04 |
Annual Sum or Average | 12.55 | 9.49 | 6.43 | 4.91 | 2.28 | 73.48 | 153.05 | 0.03 |
Minimum of Months | -0.2 | -2.6 | -7.5 | 3.91 | -13.4 | 30.23 | 88.07 | 0.00 |
Maximum of Months | 25.05 | 21.76 | 20.26 | 5.65 | 17.39 | 114.46 | 226.16 | 0.05 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 12.20 | 24-JAN-12:20 | 11.81 | 11.50 | 1.00 | 8.15 | 93.67 | 0.00 |
February | 10.00 | 20-FEB-11:00 | 4.36 | -3.3 | 2.60 | -3.9 | 151.50 | 540.00 |
March | 22.20 | 27-MAR-15:00 | 16.34 | 12.80 | 6.70 | 11.65 | 136.50 | 590.00 |
April | 26.70 | 07-APR-12:00 | 16.40 | 9.40 | 6.20 | 11.65 | 179.00 | 713.50 |
May | 30.00 | 30-MAY-12:00 | 18.00 | 10.60 | 5.20 | 17.39 | 233.50 | 730.00 |
June | 36.70 | 19-JUN-11:00 | 24.28 | 19.40 | 5.20 | 24.83 | 185.00 | 771.50 |
July | 33.90 | 07-JUL-11:00 | 23.31 | 18.90 | 3.60 | 23.82 | 331.00 | 570.00 |
August | 33.90 | 24-AUG-14:00 | 20.23 | 12.80 | 8.80 | 21.61 | 240.00 | 432.00 |
September | 31.10 | 01-SEP-13:00 | 17.34 | 8.30 | 4.60 | 18.46 | 182.00 | 662.00 |
October | 25.00 | 04-OCT-12:00 | 18.54 | 15.00 | 5.20 | 11.27 | 171.50 | 695.00 |
November | 17.80 | 04-NOV-12:20 | 12.57 | 8.50 | 3.60 | 6.15 | 182.50 | 595.67 |
December | 12.20 | 17-DEC-12:20 | 4.65 | -6.1 | 4.27 | -4.7 | 53.17 | 801.67 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.00 | 4.36 | -6.1 | 1.00 | -4.7 | 53.17 | 0.00 | |
Maximum of Months | 36.70 | 24.28 | 19.40 | 8.80 | 24.83 | 331.00 | 801.67 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -12.2 | 02-JAN-04:00 | -13.6 | -19.4 | 2.60 | -30.7 | 0.00 | 0.00 |
February | -13.9 | 06-FEB-02:00 | -15.3 | -22.8 | 7.20 | -34.1 | 0.00 | 0.00 |
March | -5.0 | 23-MAR-03:00 | -7.6 | -14.4 | 1.50 | -23.9 | 0.00 | 0.00 |
April | 2.20 | 01-APR-03:00 | 0.57 | -1.7 | 3.10 | -6.6 | 0.00 | 0.00 |
May | 6.10 | 01-MAY-04:00 | 4.33 | 2.20 | 3.60 | -9.7 | 25.50 | 0.00 |
June | 13.30 | 03-JUN-02:00 | 9.35 | 5.60 | 4.60 | -2.1 | 0.00 | 0.00 |
July | 18.30 | 02-JUL-02:00 | 17.54 | 17.20 | 0.00 | 5.33 | 0.00 | 0.00 |
August | 15.00 | 08-AUG-04:00 | 12.47 | 10.60 | 3.10 | 3.06 | 0.00 | 0.00 |
September | 10.00 | 24-SEP-05:00 | 8.56 | 7.20 | 2.60 | -3.4 | 18.50 | 158.50 |
October | 2.20 | 09-OCT-03:00 | 1.71 | 1.10 | 0.00 | -13.7 | 0.00 | 0.00 |
November | -4.4 | 24-NOV-05:00 | -6.2 | -10.0 | 1.50 | -19.7 | 0.00 | 0.00 |
December | -8.3 | 31-DEC-23:00 | -10.6 | -18.9 | 9.30 | -26.2 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -13.9 | -15.3 | -22.8 | 0.00 | -34.1 | 0.00 | 0.00 | |
Maximum of Months | 18.30 | 17.54 | 17.20 | 9.30 | 5.33 | 25.50 | 158.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 11.93 | 24-JAN-11:00 | 12.20 | 11.70 | 1.50 | 8.15 | 103.00 | 0.00 |
February | 6.67 | 28-FEB-09:00 | 7.20 | 6.10 | 4.10 | 2.01 | 101.50 | 0.00 |
March | 16.99 | 27-MAR-12:00 | 20.60 | 15.00 | 3.60 | 10.50 | 295.50 | 565.50 |
April | 17.70 | 09-APR-10:00 | 21.70 | 15.60 | 4.10 | 14.84 | 244.50 | 281.50 |
May | 20.43 | 31-MAY-12:00 | 26.10 | 17.80 | 4.10 | 17.03 | 214.00 | 772.00 |
June | 24.96 | 15-JUN-11:00 | 31.10 | 22.80 | 5.20 | 22.47 | 380.00 | 460.00 |
July | 26.10 | 08-JUL-11:00 | 32.20 | 23.90 | 5.20 | 22.47 | 354.00 | 501.50 |
August | 25.84 | 03-AUG-13:00 | 30.00 | 24.40 | 6.20 | 20.57 | 298.00 | 500.00 |
September | 23.57 | 07-SEP-13:00 | 27.20 | 22.20 | 6.20 | 15.02 | 148.00 | 730.50 |
October | 19.76 | 25-OCT-10:00 | 25.00 | 17.20 | 7.70 | 14.84 | 189.00 | 308.50 |
November | 16.10 | 10-NOV-07:00 | 16.10 | 16.10 | 8.20 | 12.98 | 71.50 | 0.00 |
December | 10.26 | 25-DEC-08:00 | 10.60 | 10.00 | 3.60 | 6.15 | 43.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.67 | 7.20 | 6.10 | 1.50 | 2.01 | 43.00 | 0.00 | |
Maximum of Months | 26.10 | 32.20 | 24.40 | 8.20 | 22.47 | 380.00 | 772.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 11.70 | 18-JAN-15:00 | 12.20 | 11.93 | 14.90 | 8.15 | 22.00 | 2.00 |
February | 6.10 | 28-FEB-10:20 | 7.03 | 6.58 | 3.43 | 1.87 | 109.83 | 0.00 |
March | 15.00 | 27-MAR-12:20 | 18.00 | 16.18 | 3.93 | 10.11 | 271.83 | 611.17 |
April | 15.60 | 09-APR-10:00 | 21.70 | 17.70 | 4.10 | 14.84 | 244.50 | 281.50 |
May | 18.00 | 18-MAY-09:00 | 18.00 | 18.00 | 4.60 | 15.39 | 265.50 | 12.00 |
June | 22.80 | 15-JUN-11:00 | 31.10 | 24.96 | 5.20 | 22.47 | 380.00 | 460.00 |
July | 24.40 | 09-JUL-07:00 | 27.20 | 25.17 | 2.10 | 15.39 | 195.00 | 504.00 |
August | 25.00 | 03-AUG-19:00 | 26.10 | 25.32 | 5.70 | 19.35 | 0.00 | 0.00 |
September | 22.20 | 07-SEP-13:00 | 27.20 | 23.57 | 6.20 | 15.02 | 148.00 | 730.50 |
October | 18.30 | 05-OCT-18:00 | 19.40 | 18.62 | 7.70 | 6.55 | 0.00 | 0.00 |
November | 16.10 | 10-NOV-07:00 | 16.10 | 16.10 | 8.20 | 12.98 | 71.50 | 0.00 |
December | 10.00 | 25-DEC-08:00 | 10.60 | 10.26 | 3.60 | 6.15 | 43.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.10 | 7.03 | 6.58 | 2.10 | 1.87 | 0.00 | 0.00 | |
Maximum of Months | 25.00 | 31.10 | 25.32 | 14.90 | 22.47 | 380.00 | 730.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 10.03 | 13.58 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 9.54 | 21.42 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 10.65 | 30.29 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 13.15 | 37.02 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 16.36 | 45.86 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 19.42 | 49.74 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 21.50 | 48.12 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 22.05 | 49.54 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 20.89 | 34.71 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 18.36 | 29.93 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 15.14 | 17.00 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 12.10 | 12.41 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 15.80 | 32.53 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 9.54 | 12.41 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 22.05 | 49.74 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK1
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.365401E+09 | -240398931.6 | 0.00 | 0.00 | 744.00 | 0.00 | -125002551.4 | 59.00 | 0.00 | 0.00 |
February | 0.333474E+09 | -220480704.7 | 0.00 | 0.00 | 672.00 | 0.00 | -112992804.6 | 58.99 | 0.00 | 0.00 |
March | 0.366231E+09 | -242520336.9 | 0.00 | 0.00 | 744.00 | 0.00 | -123710386.4 | 58.99 | 0.00 | 0.00 |
April | 0.336569E+09 | -219723748.9 | 0.00 | 0.00 | 720.00 | 0.00 | -116845424.5 | 58.99 | 0.00 | 0.00 |
May | 0.327275E+09 | -211558153.9 | 0.00 | 0.00 | 744.00 | 0.00 | -115716594.1 | 58.99 | 0.00 | 0.00 |
June | 0.300993E+09 | -191901370.8 | 0.00 | 0.00 | 720.00 | 0.00 | -109091804.0 | 58.99 | 0.00 | 0.00 |
July | 0.296061E+09 | -184013046.1 | 0.00 | 0.00 | 744.00 | 0.00 | -112047662.8 | 58.99 | 0.00 | 0.00 |
August | 0.297252E+09 | -185224370.5 | 0.00 | 0.00 | 744.00 | 0.00 | -112027693.8 | 58.99 | 0.00 | 0.00 |
September | 0.291821E+09 | -182782989.5 | 0.00 | 0.00 | 720.00 | 0.00 | -109037827.5 | 58.99 | 0.00 | 0.00 |
October | 0.314850E+09 | -199541549.0 | 0.00 | 0.00 | 744.00 | 0.00 | -115308750.9 | 58.99 | 0.00 | 0.00 |
November | 0.326170E+09 | -207782254.3 | 0.00 | 0.00 | 720.00 | 0.00 | -118387872.5 | 58.99 | 0.00 | 0.00 |
December | 0.354789E+09 | -230498296.9 | 0.00 | 0.00 | 744.00 | 0.00 | -124290577.8 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.391089E+10 | -0.251643E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.139446E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.291821E+09 | -242520336.9 | 0.00 | 0.00 | 672.00 | 0.00 | -125002551.4 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.366231E+09 | -182782989.5 | 0.00 | 0.00 | 744.00 | 0.00 | -109037827.5 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK2
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.363581E+09 | -240403526.7 | 0.00 | 0.00 | 744.00 | 0.00 | -123177106.0 | 58.99 | 0.00 | 0.00 |
February | 0.331692E+09 | -220478754.7 | 0.00 | 0.00 | 672.00 | 0.00 | -111213248.7 | 58.99 | 0.00 | 0.00 |
March | 0.363804E+09 | -242520312.1 | 0.00 | 0.00 | 744.00 | 0.00 | -121283479.6 | 58.99 | 0.00 | 0.00 |
April | 0.334169E+09 | -219732154.8 | 0.00 | 0.00 | 720.00 | 0.00 | -114436739.7 | 58.99 | 0.00 | 0.00 |
May | 0.325556E+09 | -211554733.0 | 0.00 | 0.00 | 744.00 | 0.00 | -114001142.8 | 58.99 | 0.00 | 0.00 |
June | 0.300677E+09 | -191903762.9 | 0.00 | 0.00 | 720.00 | 0.00 | -108773441.9 | 58.99 | 0.00 | 0.00 |
July | 0.295855E+09 | -184010335.5 | 0.00 | 0.00 | 744.00 | 0.00 | -111845156.3 | 58.99 | 0.00 | 0.00 |
August | 0.297088E+09 | -185201472.0 | 0.00 | 0.00 | 744.00 | 0.00 | -111886052.2 | 58.99 | 0.00 | 0.00 |
September | 0.291549E+09 | -182788159.3 | 0.00 | 0.00 | 720.00 | 0.00 | -108760602.5 | 58.99 | 0.00 | 0.00 |
October | 0.313331E+09 | -199544812.4 | 0.00 | 0.00 | 744.00 | 0.00 | -113785977.6 | 58.99 | 0.00 | 0.00 |
November | 0.323578E+09 | -207782371.5 | 0.00 | 0.00 | 720.00 | 0.00 | -115795686.8 | 58.99 | 0.00 | 0.00 |
December | 0.352676E+09 | -230503159.9 | 0.00 | 0.00 | 744.00 | 0.00 | -122172997.1 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.389356E+10 | -0.251642E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.137713E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.291549E+09 | -242520312.1 | 0.00 | 0.00 | 672.00 | 0.00 | -123177106.0 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.363804E+09 | -182788159.3 | 0.00 | 0.00 | 744.00 | 0.00 | -108760602.5 | 58.99 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK3
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.336353E+09 | -211385438.8 | 0.00 | 0.00 | 744.00 | 0.00 | -124967857.5 | 59.00 | 0.00 | 0.00 |
February | 0.306722E+09 | -194040336.1 | 0.00 | 0.00 | 672.00 | 0.00 | -112681598.6 | 58.99 | 0.00 | 0.00 |
March | 0.339344E+09 | -216430379.4 | 0.00 | 0.00 | 744.00 | 0.00 | -122913127.9 | 59.00 | 0.00 | 0.00 |
April | 0.308950E+09 | -193252184.4 | 0.00 | 0.00 | 720.00 | 0.00 | -115697334.9 | 58.99 | 0.00 | 0.00 |
May | 0.301830E+09 | -187657780.6 | 0.00 | 0.00 | 744.00 | 0.00 | -114171801.9 | 58.99 | 0.00 | 0.00 |
June | 0.278709E+09 | -170868475.7 | 0.00 | 0.00 | 720.00 | 0.00 | -107841015.9 | 59.00 | 0.00 | 0.00 |
July | 0.271218E+09 | -160875552.2 | 0.00 | 0.00 | 744.00 | 0.00 | -110342935.2 | 58.98 | 0.00 | 0.00 |
August | 0.275803E+09 | -165434538.1 | 0.00 | 0.00 | 744.00 | 0.00 | -110368789.8 | 58.99 | 0.00 | 0.00 |
September | 0.268461E+09 | -160659418.7 | 0.00 | 0.00 | 720.00 | 0.00 | -107801503.9 | 58.99 | 0.00 | 0.00 |
October | 0.289510E+09 | -175495145.9 | 0.00 | 0.00 | 744.00 | 0.00 | -114014376.3 | 58.99 | 0.00 | 0.00 |
November | 0.300871E+09 | -183447875.1 | 0.00 | 0.00 | 720.00 | 0.00 | -117422898.1 | 58.99 | 0.00 | 0.00 |
December | 0.325052E+09 | -201158227.4 | 0.00 | 0.00 | 744.00 | 0.00 | -123894271.3 | 59.01 | 0.00 | 0.00 |
Annual Sum or Average | 0.360282E+10 | -0.222071E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.138212E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.268461E+09 | -216430379.4 | 0.00 | 0.00 | 672.00 | 0.00 | -124967857.5 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.339344E+09 | -160659418.7 | 0.00 | 0.00 | 744.00 | 0.00 | -107801503.9 | 59.01 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK4
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.336757E+09 | -211399723.0 | 0.00 | 0.00 | 744.00 | 0.00 | -125357083.9 | 59.00 | 0.00 | 0.00 |
February | 0.307062E+09 | -194048888.7 | 0.00 | 0.00 | 672.00 | 0.00 | -113013032.7 | 58.99 | 0.00 | 0.00 |
March | 0.339726E+09 | -216442807.9 | 0.00 | 0.00 | 744.00 | 0.00 | -123283114.3 | 58.99 | 0.00 | 0.00 |
April | 0.309352E+09 | -193241677.0 | 0.00 | 0.00 | 720.00 | 0.00 | -116110330.9 | 58.99 | 0.00 | 0.00 |
May | 0.302195E+09 | -187658465.6 | 0.00 | 0.00 | 744.00 | 0.00 | -114536772.0 | 58.99 | 0.00 | 0.00 |
June | 0.278735E+09 | -170929105.5 | 0.00 | 0.00 | 720.00 | 0.00 | -107806275.7 | 58.98 | 0.00 | 0.00 |
July | 0.271195E+09 | -160860813.5 | 0.00 | 0.00 | 744.00 | 0.00 | -110333742.3 | 58.99 | 0.00 | 0.00 |
August | 0.275749E+09 | -165431416.7 | 0.00 | 0.00 | 744.00 | 0.00 | -110317685.5 | 58.99 | 0.00 | 0.00 |
September | 0.268501E+09 | -160668982.7 | 0.00 | 0.00 | 720.00 | 0.00 | -107831897.6 | 58.99 | 0.00 | 0.00 |
October | 0.289771E+09 | -175517056.4 | 0.00 | 0.00 | 744.00 | 0.00 | -114254292.8 | 58.98 | 0.00 | 0.00 |
November | 0.301369E+09 | -183443606.0 | 0.00 | 0.00 | 720.00 | 0.00 | -117925416.9 | 58.99 | 0.00 | 0.00 |
December | 0.325414E+09 | -201190195.1 | 0.00 | 0.00 | 744.00 | 0.00 | -124223773.1 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.360583E+10 | -0.222083E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.138499E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.268501E+09 | -216442807.9 | 0.00 | 0.00 | 672.00 | 0.00 | -125357083.9 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.339726E+09 | -160668982.7 | 0.00 | 0.00 | 744.00 | 0.00 | -107806275.7 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK5
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.326701E+09 | -199803878.3 | 0.00 | 0.00 | 744.00 | 0.00 | -126897075.0 | 58.99 | 0.00 | 0.00 |
February | 0.297901E+09 | -183506418.7 | 0.00 | 0.00 | 672.00 | 0.00 | -114394655.0 | 58.99 | 0.00 | 0.00 |
March | 0.329451E+09 | -204810842.8 | 0.00 | 0.00 | 744.00 | 0.00 | -124639659.0 | 58.99 | 0.00 | 0.00 |
April | 0.300495E+09 | -182875480.3 | 0.00 | 0.00 | 720.00 | 0.00 | -117619915.6 | 58.99 | 0.00 | 0.00 |
May | 0.293679E+09 | -177441683.9 | 0.00 | 0.00 | 744.00 | 0.00 | -116237017.4 | 59.00 | 0.00 | 0.00 |
June | 0.270175E+09 | -161711371.3 | 0.00 | 0.00 | 720.00 | 0.00 | -108463939.8 | 58.99 | 0.00 | 0.00 |
July | 0.263032E+09 | -152127633.0 | 0.00 | 0.00 | 744.00 | 0.00 | -110904594.9 | 58.99 | 0.00 | 0.00 |
August | 0.267485E+09 | -156535344.8 | 0.00 | 0.00 | 744.00 | 0.00 | -110949401.0 | 58.99 | 0.00 | 0.00 |
September | 0.260485E+09 | -152042874.5 | 0.00 | 0.00 | 720.00 | 0.00 | -108441990.7 | 58.99 | 0.00 | 0.00 |
October | 0.281335E+09 | -165872095.6 | 0.00 | 0.00 | 744.00 | 0.00 | -115463223.3 | 58.99 | 0.00 | 0.00 |
November | 0.292753E+09 | -173250629.0 | 0.00 | 0.00 | 720.00 | 0.00 | -119502408.0 | 59.00 | 0.00 | 0.00 |
December | 0.315845E+09 | -190269300.1 | 0.00 | 0.00 | 744.00 | 0.00 | -125576110.6 | 59.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.349934E+10 | -0.210025E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.139909E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.260485E+09 | -204810842.8 | 0.00 | 0.00 | 672.00 | 0.00 | -126897075.0 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.329451E+09 | -152042874.5 | 0.00 | 0.00 | 744.00 | 0.00 | -108441990.7 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK6
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.326620E+09 | -199800521.4 | 0.00 | 0.00 | 744.00 | 0.00 | -126819622.3 | 59.00 | 0.00 | 0.00 |
February | 0.297843E+09 | -183509542.6 | 0.00 | 0.00 | 672.00 | 0.00 | -114333120.5 | 58.99 | 0.00 | 0.00 |
March | 0.329462E+09 | -204814563.8 | 0.00 | 0.00 | 744.00 | 0.00 | -124647817.9 | 58.99 | 0.00 | 0.00 |
April | 0.300587E+09 | -182876209.7 | 0.00 | 0.00 | 720.00 | 0.00 | -117711204.5 | 58.99 | 0.00 | 0.00 |
May | 0.293877E+09 | -177443444.0 | 0.00 | 0.00 | 744.00 | 0.00 | -116433798.7 | 59.00 | 0.00 | 0.00 |
June | 0.270263E+09 | -161711370.1 | 0.00 | 0.00 | 720.00 | 0.00 | -108551199.4 | 58.99 | 0.00 | 0.00 |
July | 0.263140E+09 | -152135282.7 | 0.00 | 0.00 | 744.00 | 0.00 | -111004625.2 | 58.99 | 0.00 | 0.00 |
August | 0.267608E+09 | -156537393.7 | 0.00 | 0.00 | 744.00 | 0.00 | -111070472.4 | 58.99 | 0.00 | 0.00 |
September | 0.260564E+09 | -152042387.4 | 0.00 | 0.00 | 720.00 | 0.00 | -108521795.7 | 58.99 | 0.00 | 0.00 |
October | 0.281467E+09 | -165885383.8 | 0.00 | 0.00 | 744.00 | 0.00 | -115581887.9 | 58.99 | 0.00 | 0.00 |
November | 0.292817E+09 | -173277490.9 | 0.00 | 0.00 | 720.00 | 0.00 | -119539685.4 | 58.99 | 0.00 | 0.00 |
December | 0.315804E+09 | -190282284.1 | 0.00 | 0.00 | 744.00 | 0.00 | -125522212.4 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.350005E+10 | -0.210032E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.139974E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.260564E+09 | -204814563.8 | 0.00 | 0.00 | 672.00 | 0.00 | -126819622.3 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.329462E+09 | -152042387.4 | 0.00 | 0.00 | 744.00 | 0.00 | -108521795.7 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK7
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.326703E+09 | -199804051.5 | 0.00 | 0.00 | 744.00 | 0.00 | -126899309.1 | 58.99 | 0.00 | 0.00 |
February | 0.297945E+09 | -183505774.0 | 0.00 | 0.00 | 672.00 | 0.00 | -114438874.0 | 58.99 | 0.00 | 0.00 |
March | 0.329591E+09 | -204802519.9 | 0.00 | 0.00 | 744.00 | 0.00 | -124788782.5 | 58.99 | 0.00 | 0.00 |
April | 0.300764E+09 | -182870536.5 | 0.00 | 0.00 | 720.00 | 0.00 | -117893802.2 | 58.99 | 0.00 | 0.00 |
May | 0.294146E+09 | -177507474.1 | 0.00 | 0.00 | 744.00 | 0.00 | -116638855.4 | 58.98 | 0.00 | 0.00 |
June | 0.270328E+09 | -161701257.1 | 0.00 | 0.00 | 720.00 | 0.00 | -108626665.4 | 58.99 | 0.00 | 0.00 |
July | 0.263195E+09 | -152127536.8 | 0.00 | 0.00 | 744.00 | 0.00 | -111067182.7 | 58.99 | 0.00 | 0.00 |
August | 0.267657E+09 | -156532263.5 | 0.00 | 0.00 | 744.00 | 0.00 | -111124809.4 | 58.99 | 0.00 | 0.00 |
September | 0.260634E+09 | -152047204.5 | 0.00 | 0.00 | 720.00 | 0.00 | -108586473.6 | 58.99 | 0.00 | 0.00 |
October | 0.281651E+09 | -165885485.0 | 0.00 | 0.00 | 744.00 | 0.00 | -115765521.4 | 58.99 | 0.00 | 0.00 |
November | 0.292959E+09 | -173278716.1 | 0.00 | 0.00 | 720.00 | 0.00 | -119680346.9 | 58.99 | 0.00 | 0.00 |
December | 0.315913E+09 | -190274830.8 | 0.00 | 0.00 | 744.00 | 0.00 | -125638061.7 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.350149E+10 | -0.210034E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.140115E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.260634E+09 | -204802519.9 | 0.00 | 0.00 | 672.00 | 0.00 | -126899309.1 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.329591E+09 | -152047204.5 | 0.00 | 0.00 | 744.00 | 0.00 | -108586473.6 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 199.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 216.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 275.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 261.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 372.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 351.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 365.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 389.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 285.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 305.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 240.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 211.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3472.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 199.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 389.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 HEATING COIL
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.186323E+11 | 60221.18 | 01-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.177808E+11 | 60221.18 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.100766E+11 | 60221.18 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.352727E+10 | 60221.18 | 01-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 32494603.58 | 19997.19 | 01-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 93891237.07 | 8432.66 | 29-OCT-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.659010E+10 | 60221.18 | 15-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.142002E+11 | 60221.18 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.709336E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.186323E+11 | 60221.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 HEATING COIL
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.604826E+10 | 31332.34 | 01-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.575885E+10 | 31332.34 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.282121E+10 | 31332.34 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.745418E+09 | 31332.34 | 02-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 1084604.06 | 861.97 | 28-OCT-08:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.176109E+10 | 31332.34 | 21-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.428631E+10 | 31332.34 | 02-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.214222E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.604826E+10 | 31332.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3 HEATING COIL
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.719152E+10 | 31488.07 | 01-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.676237E+10 | 31488.07 | 01-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.369527E+10 | 31488.07 | 01-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.113575E+10 | 31488.07 | 02-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 1304270.16 | 1089.18 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 8393325.40 | 3610.23 | 29-OCT-08:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.240847E+10 | 31488.07 | 20-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.532946E+10 | 31488.07 | 02-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.265325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.719152E+10 | 31488.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4 HEATING COIL
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.744237E+10 | 31348.78 | 01-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.696226E+10 | 31348.78 | 01-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.389491E+10 | 31348.78 | 01-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.124754E+10 | 31348.78 | 02-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 4170357.67 | 3128.71 | 01-MAY-07:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 15545271.85 | 4021.37 | 29-OCT-08:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.257864E+10 | 31348.78 | 20-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.554637E+10 | 31348.78 | 02-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.276918E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.744237E+10 | 31348.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5 HEATING COIL
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.783526E+10 | 31312.32 | 01-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.730499E+10 | 31312.32 | 01-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.422018E+10 | 31312.32 | 01-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.142700E+10 | 31312.32 | 02-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 13986430.59 | 2828.33 | 01-MAY-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 27357725.79 | 4591.69 | 29-OCT-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.282604E+10 | 31312.32 | 19-NOV-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.589862E+10 | 31312.32 | 02-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.295534E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.783526E+10 | 31312.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6 HEATING COIL
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.152631E+11 | 57719.57 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.141453E+11 | 57719.57 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.850392E+10 | 57719.57 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.307254E+10 | 57719.57 | 01-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 87250053.19 | 39016.63 | 01-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 94265098.47 | 10911.23 | 29-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.584787E+10 | 57719.57 | 13-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116797E+11 | 57719.57 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.586940E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.152631E+11 | 57719.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7 HEATING COIL
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.794887E+10 | 29575.22 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.737655E+10 | 29575.22 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.445253E+10 | 29575.22 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.162439E+10 | 29575.22 | 01-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 54669424.63 | 22281.75 | 01-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 51187676.27 | 7620.85 | 29-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.305996E+10 | 29575.22 | 13-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.608065E+10 | 29575.22 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.306488E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.794887E+10 | 29575.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8 HEATING COIL
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.803145E+10 | 29461.47 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.746376E+10 | 29461.47 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.454905E+10 | 29461.47 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.169130E+10 | 29461.47 | 01-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 72476175.99 | 26328.44 | 01-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 62121436.07 | 10051.31 | 29-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.313477E+10 | 29461.47 | 13-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.617117E+10 | 29461.47 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.311761E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.803145E+10 | 29461.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9 HEATING COIL
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.844475E+10 | 29367.52 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.787456E+10 | 29367.52 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.494277E+10 | 29367.52 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.194123E+10 | 29367.52 | 01-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.126242E+09 | 29367.52 | 01-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 99415723.25 | 17344.13 | 29-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.340863E+10 | 29367.52 | 12-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.655727E+10 | 29367.52 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.333949E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.844475E+10 | 29367.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10 HEATING COIL
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.105851E+11 | 31372.11 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.996627E+10 | 31372.11 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.644222E+10 | 31372.11 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.278729E+10 | 31372.11 | 01-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.320865E+09 | 31372.11 | 01-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.247094E+09 | 31372.11 | 29-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.432889E+10 | 31372.11 | 01-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.813983E+10 | 31372.11 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.428176E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.105851E+11 | 31372.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 2180440.96 | 1589175.60 | 1241.02 | 27-MAR-16:10 | 901.70 | 0.00 |
April | 0.00 | 0.00 | 0.509803E+09 | 0.442959E+09 | 9813.50 | 07-APR-13:00 | 9021.04 | 0.00 |
May | 0.00 | 0.00 | 0.306867E+10 | 0.259774E+10 | 18596.08 | 31-MAY-14:00 | 13033.86 | 0.00 |
June | 0.00 | 0.00 | 0.167799E+11 | 0.110872E+11 | 49141.14 | 25-JUN-07:02 | 26829.68 | 0.00 |
July | 0.00 | 0.00 | 0.307089E+11 | 0.187365E+11 | 50355.23 | 22-JUL-07:02 | 24258.80 | 0.00 |
August | 0.00 | 0.00 | 0.289289E+11 | 0.196782E+11 | 49897.53 | 17-AUG-07:02 | 25932.32 | 0.00 |
September | 0.00 | 0.00 | 0.128395E+11 | 0.906961E+10 | 49113.64 | 14-SEP-07:02 | 27522.33 | 0.00 |
October | 0.00 | 0.00 | 0.321779E+10 | 0.215232E+10 | 19203.62 | 06-OCT-07:03 | 9646.64 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.960556E+11 | 0.637661E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.307089E+11 | 0.196782E+11 | 50355.23 | 27522.33 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 7299983.60 | 5750610.73 | 1428.84 | 27-MAR-16:10 | 1051.50 | 0.00 |
April | 0.00 | 0.00 | 0.389809E+09 | 0.339338E+09 | 23038.38 | 07-APR-20:01 | 19187.79 | 0.00 |
May | 0.00 | 0.00 | 0.213222E+10 | 0.184188E+10 | 23471.55 | 30-MAY-20:02 | 16597.96 | 0.00 |
June | 0.00 | 0.00 | 0.968704E+10 | 0.665878E+10 | 24949.82 | 27-JUN-07:03 | 17560.86 | 0.00 |
July | 0.00 | 0.00 | 0.158022E+11 | 0.101443E+11 | 25522.48 | 22-JUL-07:02 | 15958.20 | 0.00 |
August | 0.00 | 0.00 | 0.150444E+11 | 0.106649E+11 | 25242.34 | 17-AUG-07:02 | 16818.61 | 0.00 |
September | 0.00 | 0.00 | 0.745327E+10 | 0.546275E+10 | 25053.44 | 22-SEP-20:03 | 11172.38 | 0.00 |
October | 0.00 | 0.00 | 0.212519E+10 | 0.143856E+10 | 24419.00 | 24-OCT-20:10 | 11691.66 | 0.00 |
November | 0.00 | 0.00 | 4877918.31 | 4419720.81 | 2256.99 | 02-NOV-20:10 | 2256.99 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.526464E+11 | 0.365607E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.158022E+11 | 0.106649E+11 | 25522.48 | 19187.79 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3 COOLING COIL
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 1373133.11 | 1012294.21 | 765.68 | 27-MAR-16:10 | 563.03 | 0.00 |
April | 0.00 | 0.00 | 0.286704E+09 | 0.249777E+09 | 5700.71 | 08-APR-12:10 | 4837.22 | 0.00 |
May | 0.00 | 0.00 | 0.144483E+10 | 0.125984E+10 | 9681.37 | 31-MAY-14:00 | 6897.10 | 0.00 |
June | 0.00 | 0.00 | 0.740549E+10 | 0.502289E+10 | 26465.09 | 25-JUN-07:02 | 13018.45 | 0.00 |
July | 0.00 | 0.00 | 0.125039E+11 | 0.781880E+10 | 26571.35 | 21-JUL-06:02 | 13124.17 | 0.00 |
August | 0.00 | 0.00 | 0.119226E+11 | 0.832526E+10 | 26741.34 | 06-AUG-07:02 | 12868.83 | 0.00 |
September | 0.00 | 0.00 | 0.550114E+10 | 0.397335E+10 | 26121.66 | 14-SEP-06:02 | 14262.08 | 0.00 |
October | 0.00 | 0.00 | 0.163707E+10 | 0.111288E+10 | 15161.21 | 06-OCT-06:03 | 7673.63 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.407032E+11 | 0.277638E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.125039E+11 | 0.832526E+10 | 26741.34 | 14262.08 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4 COOLING COIL
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 602251.65 | 443336.01 | 473.32 | 27-MAR-16:10 | 347.73 | 0.00 |
April | 0.00 | 0.00 | 0.265963E+09 | 0.232004E+09 | 5534.40 | 08-APR-12:10 | 4691.65 | 0.00 |
May | 0.00 | 0.00 | 0.140059E+10 | 0.122047E+10 | 9650.60 | 31-MAY-14:00 | 6873.75 | 0.00 |
June | 0.00 | 0.00 | 0.737086E+10 | 0.499915E+10 | 26533.68 | 25-JUN-07:02 | 13047.76 | 0.00 |
July | 0.00 | 0.00 | 0.125066E+11 | 0.782311E+10 | 26646.20 | 21-JUL-06:02 | 13184.44 | 0.00 |
August | 0.00 | 0.00 | 0.119418E+11 | 0.834224E+10 | 26814.93 | 06-AUG-07:02 | 12942.24 | 0.00 |
September | 0.00 | 0.00 | 0.548037E+10 | 0.395891E+10 | 26191.01 | 14-SEP-06:02 | 14291.14 | 0.00 |
October | 0.00 | 0.00 | 0.157496E+10 | 0.107065E+10 | 14865.30 | 06-OCT-06:03 | 7515.72 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.405418E+11 | 0.276470E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.125066E+11 | 0.834224E+10 | 26814.93 | 14291.14 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5 COOLING COIL
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 108348.19 | 79437.45 | 180.37 | 27-MAR-16:10 | 132.24 | 0.00 |
April | 0.00 | 0.00 | 0.232426E+09 | 0.203215E+09 | 5198.05 | 08-APR-12:10 | 4386.32 | 0.00 |
May | 0.00 | 0.00 | 0.130015E+10 | 0.112984E+10 | 9461.89 | 31-MAY-14:00 | 6720.16 | 0.00 |
June | 0.00 | 0.00 | 0.713139E+10 | 0.482010E+10 | 26338.75 | 25-JUN-07:02 | 12803.05 | 0.00 |
July | 0.00 | 0.00 | 0.122599E+11 | 0.763789E+10 | 26452.78 | 21-JUL-06:02 | 12925.59 | 0.00 |
August | 0.00 | 0.00 | 0.117128E+11 | 0.815554E+10 | 26620.35 | 06-AUG-07:02 | 12698.36 | 0.00 |
September | 0.00 | 0.00 | 0.527321E+10 | 0.379381E+10 | 26003.86 | 14-SEP-06:02 | 14029.50 | 0.00 |
October | 0.00 | 0.00 | 0.145298E+10 | 0.986679E+09 | 12856.92 | 06-OCT-06:03 | 6449.72 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.393630E+11 | 0.267271E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.122599E+11 | 0.815554E+10 | 26620.35 | 14029.50 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6 COOLING COIL
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 46.44 | 33.24 | 0.08 | 27-MAR-16:10 | 0.06 | 0.00 |
April | 0.00 | 0.00 | 0.363230E+09 | 0.312187E+09 | 8800.74 | 08-APR-12:00 | 7344.45 | 0.00 |
May | 0.00 | 0.00 | 0.211406E+10 | 0.179660E+10 | 17618.47 | 31-MAY-14:10 | 12182.63 | 0.00 |
June | 0.00 | 0.00 | 0.123275E+11 | 0.811605E+10 | 47845.35 | 25-JUN-08:62 | 22770.87 | 0.00 |
July | 0.00 | 0.00 | 0.217803E+11 | 0.131888E+11 | 47895.23 | 09-JUL-08:62 | 23129.19 | 0.00 |
August | 0.00 | 0.00 | 0.211415E+11 | 0.143756E+11 | 47273.51 | 06-AUG-08:62 | 19308.41 | 0.00 |
September | 0.00 | 0.00 | 0.916567E+10 | 0.642995E+10 | 46731.39 | 14-SEP-07:02 | 25905.18 | 0.00 |
October | 0.00 | 0.00 | 0.235065E+10 | 0.155186E+10 | 19855.48 | 06-OCT-07:03 | 9996.89 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.692429E+11 | 0.457711E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.217803E+11 | 0.143756E+11 | 47895.23 | 25905.18 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7 COOLING COIL
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 53.41 | 37.87 | 0.09 | 27-MAR-16:10 | 0.06 | 0.00 |
April | 0.00 | 0.00 | 0.174816E+09 | 0.150750E+09 | 4419.53 | 08-APR-12:00 | 3696.73 | 0.00 |
May | 0.00 | 0.00 | 0.105586E+10 | 0.897959E+09 | 9050.29 | 31-MAY-14:10 | 6267.88 | 0.00 |
June | 0.00 | 0.00 | 0.629115E+10 | 0.415370E+10 | 24702.02 | 25-JUN-08:62 | 11711.35 | 0.00 |
July | 0.00 | 0.00 | 0.111720E+11 | 0.678659E+10 | 24733.35 | 09-JUL-08:62 | 11869.77 | 0.00 |
August | 0.00 | 0.00 | 0.108430E+11 | 0.739284E+10 | 24406.48 | 06-AUG-08:62 | 9975.69 | 0.00 |
September | 0.00 | 0.00 | 0.468679E+10 | 0.329751E+10 | 24112.85 | 14-SEP-07:02 | 13384.50 | 0.00 |
October | 0.00 | 0.00 | 0.116256E+10 | 0.769649E+09 | 8805.83 | 06-OCT-07:03 | 4418.17 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.353863E+11 | 0.234490E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.111720E+11 | 0.739284E+10 | 24733.35 | 13384.50 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8 COOLING COIL
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.165807E+09 | 0.142869E+09 | 4311.64 | 08-APR-12:00 | 3602.11 | 0.00 |
May | 0.00 | 0.00 | 0.101622E+10 | 0.861805E+09 | 8973.89 | 31-MAY-14:10 | 6204.02 | 0.00 |
June | 0.00 | 0.00 | 0.620493E+10 | 0.408942E+10 | 24613.76 | 25-JUN-08:62 | 11628.55 | 0.00 |
July | 0.00 | 0.00 | 0.110851E+11 | 0.672047E+10 | 24646.14 | 09-JUL-08:62 | 11786.91 | 0.00 |
August | 0.00 | 0.00 | 0.107659E+11 | 0.732785E+10 | 24322.45 | 06-AUG-08:62 | 9932.78 | 0.00 |
September | 0.00 | 0.00 | 0.462204E+10 | 0.324637E+10 | 24031.06 | 14-SEP-07:02 | 13291.66 | 0.00 |
October | 0.00 | 0.00 | 0.111903E+10 | 0.740580E+09 | 7979.41 | 04-OCT-13:00 | 5767.64 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.349790E+11 | 0.231294E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.110851E+11 | 0.732785E+10 | 24646.14 | 13291.66 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9 COOLING COIL
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.145429E+09 | 0.125139E+09 | 4072.58 | 08-APR-12:00 | 3401.53 | 0.00 |
May | 0.00 | 0.00 | 0.928080E+09 | 0.783242E+09 | 8801.40 | 31-MAY-14:10 | 6072.65 | 0.00 |
June | 0.00 | 0.00 | 0.598561E+10 | 0.393707E+10 | 24490.53 | 25-JUN-08:62 | 11427.36 | 0.00 |
July | 0.00 | 0.00 | 0.109295E+11 | 0.661259E+10 | 24527.89 | 09-JUL-08:62 | 11625.96 | 0.00 |
August | 0.00 | 0.00 | 0.106425E+11 | 0.723199E+10 | 24216.54 | 06-AUG-08:62 | 9871.10 | 0.00 |
September | 0.00 | 0.00 | 0.448805E+10 | 0.314778E+10 | 23925.30 | 14-SEP-07:02 | 13105.54 | 0.00 |
October | 0.00 | 0.00 | 0.102652E+10 | 0.679571E+09 | 7821.88 | 04-OCT-13:00 | 5642.69 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.341457E+11 | 0.225174E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.109295E+11 | 0.723199E+10 | 24527.89 | 13105.54 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10 COOLING COIL
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.136517E+09 | 0.118017E+09 | 4295.54 | 08-APR-12:00 | 3618.12 | 0.00 |
May | 0.00 | 0.00 | 0.887824E+09 | 0.750417E+09 | 8937.08 | 31-MAY-14:10 | 6212.09 | 0.00 |
June | 0.00 | 0.00 | 0.584480E+10 | 0.388449E+10 | 26539.20 | 25-JUN-08:62 | 11697.87 | 0.00 |
July | 0.00 | 0.00 | 0.114348E+11 | 0.698833E+10 | 26856.73 | 22-JUL-07:02 | 11204.09 | 0.00 |
August | 0.00 | 0.00 | 0.113720E+11 | 0.780882E+10 | 26617.76 | 17-AUG-07:02 | 12143.04 | 0.00 |
September | 0.00 | 0.00 | 0.459577E+10 | 0.326601E+10 | 26162.58 | 14-SEP-07:02 | 12796.96 | 0.00 |
October | 0.00 | 0.00 | 0.100354E+10 | 0.673169E+09 | 8260.41 | 04-OCT-13:00 | 6029.25 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.352753E+11 | 0.234893E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.114348E+11 | 0.780882E+10 | 26856.73 | 12796.96 | 0.00 |
Report: FanReportMonthly
For: PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.189749E+10 | 0.42 | 2078.68 | 01-JAN-08:61 | 0.88 |
February | 0.173606E+10 | 0.43 | 2078.68 | 01-FEB-08:61 | 0.88 |
March | 0.172436E+10 | 0.40 | 2078.68 | 01-MAR-08:61 | 0.88 |
April | 0.153390E+10 | 0.37 | 2078.68 | 01-APR-07:01 | 0.88 |
May | 0.150930E+10 | 0.36 | 1245.63 | 01-MAY-07:01 | 0.68 |
June | 0.147521E+10 | 0.36 | 2078.68 | 19-JUN-07:02 | 0.86 |
July | 0.155206E+10 | 0.36 | 2078.68 | 03-JUL-07:02 | 0.86 |
August | 0.157163E+10 | 0.36 | 2078.68 | 01-AUG-07:02 | 0.87 |
September | 0.146696E+10 | 0.36 | 2078.68 | 01-SEP-07:02 | 0.87 |
October | 0.151057E+10 | 0.36 | 1006.12 | 29-OCT-08:03 | 0.60 |
November | 0.159462E+10 | 0.38 | 2078.68 | 15-NOV-08:61 | 0.88 |
December | 0.180978E+10 | 0.41 | 2078.68 | 01-DEC-08:61 | 0.88 |
Annual Sum or Average | 0.193819E+11 | 0.38 | |||
Minimum of Months | 0.146696E+10 | 0.36 | 1006.12 | 0.60 | |
Maximum of Months | 0.189749E+10 | 0.43 | 2078.68 | 0.88 |
Report: FanReportMonthly
For: PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.760157E+09 | 0.33 | 1152.79 | 01-JAN-08:61 | 0.91 |
February | 0.693969E+09 | 0.33 | 1152.79 | 01-FEB-08:61 | 0.91 |
March | 0.700970E+09 | 0.31 | 1152.79 | 01-MAR-08:61 | 0.91 |
April | 0.675023E+09 | 0.33 | 1152.79 | 02-APR-07:01 | 0.91 |
May | 0.764628E+09 | 0.37 | 516.15 | 31-MAY-07:03 | 0.59 |
June | 0.734622E+09 | 0.38 | 1152.79 | 19-JUN-07:02 | 0.90 |
July | 0.768247E+09 | 0.39 | 1152.79 | 03-JUL-07:02 | 0.90 |
August | 0.777385E+09 | 0.38 | 1152.79 | 01-AUG-07:02 | 0.90 |
September | 0.739150E+09 | 0.37 | 1152.79 | 01-SEP-07:02 | 0.90 |
October | 0.768379E+09 | 0.37 | 573.09 | 06-OCT-07:03 | 0.62 |
November | 0.669151E+09 | 0.32 | 1152.79 | 21-NOV-08:61 | 0.91 |
December | 0.717175E+09 | 0.30 | 1152.79 | 02-DEC-08:61 | 0.91 |
Annual Sum or Average | 0.876886E+10 | 0.35 | |||
Minimum of Months | 0.669151E+09 | 0.30 | 516.15 | 0.59 | |
Maximum of Months | 0.777385E+09 | 0.39 | 1152.79 | 0.91 |
Report: FanReportMonthly
For: PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.829441E+09 | 0.34 | 1158.58 | 01-JAN-08:61 | 0.91 |
February | 0.756569E+09 | 0.34 | 1158.58 | 01-FEB-07:01 | 0.91 |
March | 0.765603E+09 | 0.33 | 1158.58 | 01-MAR-07:01 | 0.91 |
April | 0.675730E+09 | 0.30 | 1158.58 | 02-APR-07:01 | 0.91 |
May | 0.677379E+09 | 0.30 | 487.48 | 01-MAY-07:10 | 0.57 |
June | 0.665329E+09 | 0.30 | 1158.58 | 15-JUN-06:03 | 0.89 |
July | 0.687828E+09 | 0.30 | 1158.58 | 02-JUL-07:03 | 0.89 |
August | 0.711790E+09 | 0.31 | 1158.58 | 01-AUG-06:02 | 0.89 |
September | 0.652366E+09 | 0.30 | 1158.58 | 01-SEP-06:02 | 0.89 |
October | 0.670894E+09 | 0.30 | 622.12 | 06-OCT-06:03 | 0.65 |
November | 0.703828E+09 | 0.31 | 1158.58 | 20-NOV-07:01 | 0.91 |
December | 0.784996E+09 | 0.33 | 1158.58 | 02-DEC-07:01 | 0.91 |
Annual Sum or Average | 0.858175E+10 | 0.31 | |||
Minimum of Months | 0.652366E+09 | 0.30 | 487.48 | 0.57 | |
Maximum of Months | 0.829441E+09 | 0.34 | 1158.58 | 0.91 |
Report: FanReportMonthly
For: PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.838610E+09 | 0.34 | 1162.60 | 01-JAN-08:61 | 0.91 |
February | 0.764309E+09 | 0.34 | 1162.60 | 01-FEB-07:01 | 0.91 |
March | 0.773066E+09 | 0.33 | 1162.60 | 01-MAR-07:01 | 0.91 |
April | 0.680675E+09 | 0.31 | 1162.60 | 02-APR-07:01 | 0.91 |
May | 0.679795E+09 | 0.30 | 534.66 | 01-MAY-07:08 | 0.60 |
June | 0.667508E+09 | 0.30 | 1162.60 | 15-JUN-06:03 | 0.89 |
July | 0.689761E+09 | 0.30 | 1162.60 | 02-JUL-07:03 | 0.89 |
August | 0.713905E+09 | 0.31 | 1162.60 | 01-AUG-06:02 | 0.89 |
September | 0.654584E+09 | 0.30 | 1162.60 | 01-SEP-06:02 | 0.89 |
October | 0.673379E+09 | 0.30 | 605.50 | 06-OCT-06:03 | 0.64 |
November | 0.710294E+09 | 0.31 | 1162.60 | 20-NOV-07:01 | 0.91 |
December | 0.793072E+09 | 0.33 | 1162.60 | 02-DEC-07:01 | 0.91 |
Annual Sum or Average | 0.863896E+10 | 0.31 | |||
Minimum of Months | 0.654584E+09 | 0.30 | 534.66 | 0.60 | |
Maximum of Months | 0.838610E+09 | 0.34 | 1162.60 | 0.91 |
Report: FanReportMonthly
For: PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.839781E+09 | 0.34 | 1151.94 | 01-JAN-08:61 | 0.91 |
February | 0.765043E+09 | 0.35 | 1151.94 | 01-FEB-07:01 | 0.91 |
March | 0.773256E+09 | 0.33 | 1151.94 | 01-MAR-07:01 | 0.91 |
April | 0.678425E+09 | 0.31 | 1151.94 | 02-APR-07:01 | 0.91 |
May | 0.673776E+09 | 0.30 | 523.20 | 01-MAY-07:05 | 0.59 |
June | 0.661015E+09 | 0.30 | 1151.94 | 16-JUN-06:03 | 0.89 |
July | 0.682178E+09 | 0.30 | 1151.94 | 03-JUL-06:03 | 0.89 |
August | 0.705916E+09 | 0.31 | 1151.94 | 01-AUG-06:02 | 0.89 |
September | 0.648365E+09 | 0.30 | 1151.94 | 01-SEP-06:02 | 0.89 |
October | 0.667443E+09 | 0.30 | 562.13 | 29-OCT-08:05 | 0.63 |
November | 0.709307E+09 | 0.32 | 1151.94 | 19-NOV-08:62 | 0.91 |
December | 0.793716E+09 | 0.33 | 1151.94 | 02-DEC-07:01 | 0.91 |
Annual Sum or Average | 0.859822E+10 | 0.31 | |||
Minimum of Months | 0.648365E+09 | 0.30 | 523.20 | 0.59 | |
Maximum of Months | 0.839781E+09 | 0.35 | 1151.94 | 0.91 |
Report: FanReportMonthly
For: PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.135941E+10 | 0.31 | 1961.62 | 01-JAN-09:01 | 0.88 |
February | 0.123755E+10 | 0.31 | 1961.62 | 01-FEB-08:61 | 0.88 |
March | 0.124398E+10 | 0.30 | 1961.62 | 01-MAR-08:61 | 0.88 |
April | 0.107956E+10 | 0.28 | 1961.62 | 01-APR-07:01 | 0.87 |
May | 0.106105E+10 | 0.27 | 1580.24 | 01-MAY-07:01 | 0.79 |
June | 0.104250E+10 | 0.27 | 1961.62 | 19-JUN-07:02 | 0.86 |
July | 0.108505E+10 | 0.27 | 1961.62 | 02-JUL-08:62 | 0.86 |
August | 0.112815E+10 | 0.28 | 1961.62 | 01-AUG-07:02 | 0.87 |
September | 0.102017E+10 | 0.26 | 1961.62 | 01-SEP-07:02 | 0.86 |
October | 0.104990E+10 | 0.26 | 1007.14 | 29-OCT-08:62 | 0.62 |
November | 0.113615E+10 | 0.28 | 1961.62 | 13-NOV-08:61 | 0.88 |
December | 0.128049E+10 | 0.30 | 1961.62 | 01-DEC-08:61 | 0.88 |
Annual Sum or Average | 0.137239E+11 | 0.28 | |||
Minimum of Months | 0.102017E+10 | 0.26 | 1007.14 | 0.62 | |
Maximum of Months | 0.135941E+10 | 0.31 | 1961.62 | 0.88 |
Report: FanReportMonthly
For: PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.731754E+09 | 0.32 | 1052.00 | 01-JAN-09:01 | 0.91 |
February | 0.666434E+09 | 0.33 | 1052.00 | 01-FEB-08:61 | 0.91 |
March | 0.669169E+09 | 0.31 | 1052.00 | 01-MAR-08:61 | 0.91 |
April | 0.580027E+09 | 0.29 | 1052.00 | 01-APR-07:01 | 0.91 |
May | 0.569249E+09 | 0.28 | 896.34 | 01-MAY-07:01 | 0.84 |
June | 0.558948E+09 | 0.28 | 1052.00 | 19-JUN-07:02 | 0.89 |
July | 0.581451E+09 | 0.28 | 1052.00 | 02-JUL-08:62 | 0.89 |
August | 0.604553E+09 | 0.29 | 1052.00 | 01-AUG-07:02 | 0.90 |
September | 0.547045E+09 | 0.27 | 1052.00 | 01-SEP-07:02 | 0.89 |
October | 0.563115E+09 | 0.27 | 583.45 | 29-OCT-08:62 | 0.68 |
November | 0.610665E+09 | 0.29 | 1052.00 | 13-NOV-08:61 | 0.91 |
December | 0.688768E+09 | 0.31 | 1052.00 | 01-DEC-08:61 | 0.91 |
Annual Sum or Average | 0.737118E+10 | 0.29 | |||
Minimum of Months | 0.547045E+09 | 0.27 | 583.45 | 0.68 | |
Maximum of Months | 0.731754E+09 | 0.33 | 1052.00 | 0.91 |
Report: FanReportMonthly
For: PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.730586E+09 | 0.33 | 1046.85 | 01-JAN-09:01 | 0.91 |
February | 0.665632E+09 | 0.33 | 1046.85 | 01-FEB-08:61 | 0.91 |
March | 0.668312E+09 | 0.31 | 1046.85 | 01-MAR-08:61 | 0.91 |
April | 0.578744E+09 | 0.29 | 1046.85 | 01-APR-07:01 | 0.91 |
May | 0.566843E+09 | 0.28 | 980.05 | 01-MAY-07:01 | 0.88 |
June | 0.556071E+09 | 0.28 | 1046.85 | 19-JUN-07:02 | 0.89 |
July | 0.578239E+09 | 0.28 | 1046.85 | 02-JUL-08:62 | 0.89 |
August | 0.601248E+09 | 0.29 | 1046.85 | 01-AUG-07:02 | 0.90 |
September | 0.544312E+09 | 0.27 | 1046.85 | 01-SEP-07:02 | 0.89 |
October | 0.560592E+09 | 0.27 | 633.03 | 29-OCT-08:62 | 0.71 |
November | 0.609518E+09 | 0.30 | 1046.85 | 13-NOV-08:61 | 0.91 |
December | 0.687820E+09 | 0.31 | 1046.85 | 01-DEC-08:61 | 0.91 |
Annual Sum or Average | 0.734792E+10 | 0.29 | |||
Minimum of Months | 0.544312E+09 | 0.27 | 633.03 | 0.71 | |
Maximum of Months | 0.730586E+09 | 0.33 | 1046.85 | 0.91 |
Report: FanReportMonthly
For: PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.737651E+09 | 0.33 | 1043.40 | 01-JAN-09:01 | 0.91 |
February | 0.672785E+09 | 0.33 | 1043.40 | 01-FEB-08:61 | 0.91 |
March | 0.674815E+09 | 0.31 | 1043.40 | 01-MAR-08:61 | 0.91 |
April | 0.582282E+09 | 0.29 | 1043.40 | 01-APR-07:01 | 0.91 |
May | 0.566129E+09 | 0.28 | 1043.40 | 01-MAY-07:01 | 0.90 |
June | 0.553829E+09 | 0.28 | 1043.40 | 19-JUN-07:02 | 0.89 |
July | 0.575748E+09 | 0.27 | 1043.40 | 03-JUL-07:02 | 0.89 |
August | 0.599137E+09 | 0.29 | 1043.40 | 01-AUG-07:02 | 0.90 |
September | 0.542410E+09 | 0.27 | 1043.40 | 01-SEP-07:02 | 0.89 |
October | 0.559547E+09 | 0.27 | 787.09 | 29-OCT-08:62 | 0.80 |
November | 0.613564E+09 | 0.30 | 1043.40 | 12-NOV-09:01 | 0.91 |
December | 0.694207E+09 | 0.31 | 1043.40 | 01-DEC-08:61 | 0.91 |
Annual Sum or Average | 0.737210E+10 | 0.29 | |||
Minimum of Months | 0.542410E+09 | 0.27 | 787.09 | 0.80 | |
Maximum of Months | 0.737651E+09 | 0.33 | 1043.40 | 0.91 |
Report: FanReportMonthly
For: PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.849168E+09 | 0.37 | 1146.36 | 01-JAN-09:01 | 0.91 |
February | 0.777882E+09 | 0.38 | 1146.36 | 01-FEB-08:61 | 0.91 |
March | 0.767000E+09 | 0.32 | 1146.36 | 01-MAR-08:61 | 0.91 |
April | 0.655380E+09 | 0.29 | 1146.36 | 01-APR-07:01 | 0.91 |
May | 0.626067E+09 | 0.28 | 1146.36 | 01-MAY-07:01 | 0.90 |
June | 0.607752E+09 | 0.28 | 1146.36 | 19-JUN-07:02 | 0.89 |
July | 0.629630E+09 | 0.27 | 1146.36 | 03-JUL-07:02 | 0.89 |
August | 0.656680E+09 | 0.29 | 1146.36 | 01-AUG-07:02 | 0.89 |
September | 0.595473E+09 | 0.27 | 1146.36 | 01-SEP-07:02 | 0.89 |
October | 0.617846E+09 | 0.27 | 1146.36 | 29-OCT-08:62 | 0.91 |
November | 0.689179E+09 | 0.30 | 1146.36 | 01-NOV-07:01 | 0.91 |
December | 0.787860E+09 | 0.32 | 1146.36 | 01-DEC-08:61 | 0.91 |
Annual Sum or Average | 0.825992E+10 | 0.30 | |||
Minimum of Months | 0.595473E+09 | 0.27 | 1146.36 | 0.89 | |
Maximum of Months | 0.849168E+09 | 0.38 | 1146.36 | 0.91 |
Report: ZoneTemperatureOscillationReportMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.189749E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.173606E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.172499E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.167413E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.232155E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.567345E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.897419E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.868516E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.468257E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.232872E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.159462E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.180978E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.431027E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.159462E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.897419E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.760157E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.693969E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.702999E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.777535E+09 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.130343E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.310463E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.454642E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.443150E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.256062E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.129244E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.670494E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.717175E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.215614E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.670494E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.454642E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_3:3
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.829441E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.756569E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.765991E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.752580E+09 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.105398E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.248478E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.365670E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.359654E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.200386E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.107953E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.703828E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.784996E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.184688E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.703828E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.365670E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_4:4
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.838610E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.764309E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.773237E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.752254E+09 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.104527E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.247985E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.366045E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.360389E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.200155E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.106716E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.710294E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.793072E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.184899E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.710294E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.366045E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_5:5
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.839781E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.765043E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.773287E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.741386E+09 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.101390E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.241864E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.359828E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.354382E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.194676E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.103161E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.709307E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.793716E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.181755E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.709307E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.359828E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_6:6
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.135941E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.123755E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.124398E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.118029E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.162377E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.413159E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.633744E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.633246E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.331543E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.164999E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.113615E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.128049E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.308286E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.113615E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.633744E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_7:7
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.731754E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.666434E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.669169E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.627791E+09 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.845589E+09 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.211004E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.323234E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.323076E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.170121E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.854895E+09 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.610665E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.688768E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.159694E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.610665E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.323234E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_8:8
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.730586E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.665632E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.668312E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.624127E+09 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.833121E+09 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.208709E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.320932E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.320933E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.168319E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.841683E+09 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.609518E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.687820E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.158497E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.609518E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.320933E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_9:9
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.737651E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.672785E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.674815E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.622266E+09 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.809964E+09 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.203401E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.317207E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.317825E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.164900E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.817861E+09 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.613564E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.694207E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.156764E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.613564E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.317825E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_10:10
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.849168E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.777882E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.767000E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.693089E+09 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.860126E+09 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.206550E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.336070E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.341933E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.173068E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.870515E+09 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.689179E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.787860E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.168710E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.689179E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.341933E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.189749E+10 | 0.00 | 0.186323E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.173606E+10 | 0.00 | 0.177808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.172436E+10 | 2180440.96 | 0.100766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.153390E+10 | 0.509803E+09 | 0.352727E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.150930E+10 | 0.306867E+10 | 32494603.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.147521E+10 | 0.167799E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.155206E+10 | 0.307089E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.157163E+10 | 0.289289E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.146696E+10 | 0.128395E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.151057E+10 | 0.321779E+10 | 93891237.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.159462E+10 | 0.00 | 0.659010E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.180978E+10 | 0.00 | 0.142002E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.193819E+11 | 0.960556E+11 | 0.709336E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.146696E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189749E+10 | 0.307089E+11 | 0.186323E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.760157E+09 | 0.00 | 0.604826E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.693969E+09 | 0.00 | 0.575885E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.700970E+09 | 7299983.60 | 0.282121E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.675023E+09 | 0.382018E+09 | 0.745418E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.764628E+09 | 0.205006E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.734622E+09 | 0.961127E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.768247E+09 | 0.158022E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.777385E+09 | 0.149676E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.739150E+09 | 0.734163E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.768379E+09 | 0.210043E+10 | 1084604.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.669151E+09 | 4877918.31 | 0.176109E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.717175E+09 | 0.00 | 0.428631E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.876886E+10 | 0.522674E+11 | 0.214222E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.669151E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.777385E+09 | 0.158022E+11 | 0.604826E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_3:3
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.829441E+09 | 0.00 | 0.719152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.756569E+09 | 0.00 | 0.676237E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.765603E+09 | 1373133.11 | 0.369527E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.675730E+09 | 0.286704E+09 | 0.113575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.677379E+09 | 0.144483E+10 | 1304270.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.665329E+09 | 0.740549E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.687828E+09 | 0.125039E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.711790E+09 | 0.119226E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.652366E+09 | 0.550114E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.670894E+09 | 0.163707E+10 | 8393325.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.703828E+09 | 0.00 | 0.240847E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.784996E+09 | 0.00 | 0.532946E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.858175E+10 | 0.407032E+11 | 0.265325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.652366E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.829441E+09 | 0.125039E+11 | 0.719152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_4:4
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.838610E+09 | 0.00 | 0.744237E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.764309E+09 | 0.00 | 0.696226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.773066E+09 | 602251.65 | 0.389491E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.680675E+09 | 0.265963E+09 | 0.124754E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.679795E+09 | 0.140059E+10 | 4170357.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.667508E+09 | 0.737086E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.689761E+09 | 0.125066E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.713905E+09 | 0.119418E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.654584E+09 | 0.548037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.673379E+09 | 0.157496E+10 | 15545271.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.710294E+09 | 0.00 | 0.257864E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.793072E+09 | 0.00 | 0.554637E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.863896E+10 | 0.405418E+11 | 0.276918E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.654584E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.838610E+09 | 0.125066E+11 | 0.744237E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_5:5
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.839781E+09 | 0.00 | 0.783526E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.765043E+09 | 0.00 | 0.730499E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.773256E+09 | 108348.19 | 0.422018E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.678425E+09 | 0.232426E+09 | 0.142700E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.673776E+09 | 0.130015E+10 | 13986430.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.661015E+09 | 0.713139E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.682178E+09 | 0.122599E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.705916E+09 | 0.117128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.648365E+09 | 0.527321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.667443E+09 | 0.145298E+10 | 27357725.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.709307E+09 | 0.00 | 0.282604E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.793716E+09 | 0.00 | 0.589862E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.859822E+10 | 0.393630E+11 | 0.295534E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.648365E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.839781E+09 | 0.122599E+11 | 0.783526E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_6:6
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.135941E+10 | 0.00 | 0.152631E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.123755E+10 | 0.00 | 0.141453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.124398E+10 | 46.44 | 0.850392E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.107956E+10 | 0.363230E+09 | 0.307254E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.106105E+10 | 0.211406E+10 | 87250053.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.104250E+10 | 0.123275E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.108505E+10 | 0.217803E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.112815E+10 | 0.211415E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.102017E+10 | 0.916567E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.104990E+10 | 0.235065E+10 | 94265098.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.113615E+10 | 0.00 | 0.584787E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.128049E+10 | 0.00 | 0.116797E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.137239E+11 | 0.692429E+11 | 0.586940E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.102017E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.135941E+10 | 0.217803E+11 | 0.152631E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_7:7
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.731754E+09 | 0.00 | 0.794887E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.666434E+09 | 0.00 | 0.737655E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.669169E+09 | 53.41 | 0.445253E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.580027E+09 | 0.174816E+09 | 0.162439E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.569249E+09 | 0.105586E+10 | 54669424.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.558948E+09 | 0.629115E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.581451E+09 | 0.111720E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.604553E+09 | 0.108430E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.547045E+09 | 0.468679E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.563115E+09 | 0.116256E+10 | 51187676.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.610665E+09 | 0.00 | 0.305996E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.688768E+09 | 0.00 | 0.608065E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.737118E+10 | 0.353863E+11 | 0.306488E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.547045E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.731754E+09 | 0.111720E+11 | 0.794887E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_8:8
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.730586E+09 | 0.00 | 0.803145E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.665632E+09 | 0.00 | 0.746376E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.668312E+09 | 0.00 | 0.454905E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.578744E+09 | 0.165807E+09 | 0.169130E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.566843E+09 | 0.101622E+10 | 72476175.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.556071E+09 | 0.620493E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.578239E+09 | 0.110851E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.601248E+09 | 0.107659E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.544312E+09 | 0.462204E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.560592E+09 | 0.111903E+10 | 62121436.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.609518E+09 | 0.00 | 0.313477E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.687820E+09 | 0.00 | 0.617117E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.734792E+10 | 0.349790E+11 | 0.311761E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.544312E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.730586E+09 | 0.110851E+11 | 0.803145E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_9:9
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.737651E+09 | 0.00 | 0.844475E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.672785E+09 | 0.00 | 0.787456E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.674815E+09 | 0.00 | 0.494277E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.582282E+09 | 0.145429E+09 | 0.194123E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.566129E+09 | 0.928080E+09 | 0.126242E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.553829E+09 | 0.598561E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.575748E+09 | 0.109295E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.599137E+09 | 0.106425E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.542410E+09 | 0.448805E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.559547E+09 | 0.102652E+10 | 99415723.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.613564E+09 | 0.00 | 0.340863E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.694207E+09 | 0.00 | 0.655727E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.737210E+10 | 0.341457E+11 | 0.333949E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.542410E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.737651E+09 | 0.109295E+11 | 0.844475E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_10:10
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.849168E+09 | 0.00 | 0.105851E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.777882E+09 | 0.00 | 0.996627E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.767000E+09 | 0.00 | 0.644222E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.655380E+09 | 0.136517E+09 | 0.278729E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.626067E+09 | 0.887824E+09 | 0.320865E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.607752E+09 | 0.584480E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.629630E+09 | 0.114348E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.656680E+09 | 0.113720E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.595473E+09 | 0.459577E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.617846E+09 | 0.100354E+10 | 0.247094E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.689179E+09 | 0.00 | 0.432889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.787860E+09 | 0.00 | 0.813983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.825992E+10 | 0.352753E+11 | 0.428176E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.595473E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.849168E+09 | 0.114348E+11 | 0.105851E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.189749E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.173606E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.172436E+10 | 0.00 | 0.00 | 0.00 | 628197.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.153390E+10 | 0.00 | 0.00 | 0.00 | 0.140236E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.150930E+10 | 0.00 | 0.00 | 0.00 | 0.812249E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.147521E+10 | 0.00 | 0.00 | 0.00 | 0.419824E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.155206E+10 | 0.00 | 0.00 | 0.00 | 0.742213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.157163E+10 | 0.00 | 0.00 | 0.00 | 0.711353E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.146696E+10 | 0.00 | 0.00 | 0.00 | 0.321561E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.151057E+10 | 0.00 | 0.00 | 0.00 | 0.818153E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.159462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.180978E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.193819E+11 | 0.00 | 0.00 | 0.00 | 0.237208E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.146696E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189749E+10 | 0.00 | 0.00 | 0.00 | 0.742213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.760157E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.693969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.700970E+09 | 0.00 | 0.00 | 0.00 | 2028834.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.675023E+09 | 0.00 | 0.00 | 0.00 | 0.102512E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.764628E+09 | 0.00 | 0.00 | 0.00 | 0.538803E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.734622E+09 | 0.00 | 0.00 | 0.00 | 0.237000E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.768247E+09 | 0.00 | 0.00 | 0.00 | 0.377817E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.777385E+09 | 0.00 | 0.00 | 0.00 | 0.365411E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.739150E+09 | 0.00 | 0.00 | 0.00 | 0.182147E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.768379E+09 | 0.00 | 0.00 | 0.00 | 0.524058E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.669151E+09 | 0.00 | 0.00 | 0.00 | 1343001.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.717175E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.876886E+10 | 0.00 | 0.00 | 0.00 | 0.127925E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.669151E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.777385E+09 | 0.00 | 0.00 | 0.00 | 0.377817E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_3:3
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.829441E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.756569E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.765603E+09 | 0.00 | 0.00 | 0.00 | 387914.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.675730E+09 | 0.00 | 0.00 | 0.00 | 76849719.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.677379E+09 | 0.00 | 0.00 | 0.00 | 0.376599E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.665329E+09 | 0.00 | 0.00 | 0.00 | 0.181945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.687828E+09 | 0.00 | 0.00 | 0.00 | 0.296887E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.711790E+09 | 0.00 | 0.00 | 0.00 | 0.288475E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.652366E+09 | 0.00 | 0.00 | 0.00 | 0.135149E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.670894E+09 | 0.00 | 0.00 | 0.00 | 0.408637E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.703828E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.784996E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.858175E+10 | 0.00 | 0.00 | 0.00 | 0.988703E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.652366E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.829441E+09 | 0.00 | 0.00 | 0.00 | 0.296887E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_4:4
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.838610E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.764309E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.773066E+09 | 0.00 | 0.00 | 0.00 | 171134.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.680675E+09 | 0.00 | 0.00 | 0.00 | 71578530.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.679795E+09 | 0.00 | 0.00 | 0.00 | 0.365480E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.667508E+09 | 0.00 | 0.00 | 0.00 | 0.181234E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.689761E+09 | 0.00 | 0.00 | 0.00 | 0.297068E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.713905E+09 | 0.00 | 0.00 | 0.00 | 0.288998E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.654584E+09 | 0.00 | 0.00 | 0.00 | 0.134696E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.673379E+09 | 0.00 | 0.00 | 0.00 | 0.393781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.710294E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.793072E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.863896E+10 | 0.00 | 0.00 | 0.00 | 0.985098E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.654584E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.838610E+09 | 0.00 | 0.00 | 0.00 | 0.297068E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_5:5
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.839781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.765043E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.773256E+09 | 0.00 | 0.00 | 0.00 | 30964.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.678425E+09 | 0.00 | 0.00 | 0.00 | 62960389.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.673776E+09 | 0.00 | 0.00 | 0.00 | 0.340125E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.661015E+09 | 0.00 | 0.00 | 0.00 | 0.175762E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.682178E+09 | 0.00 | 0.00 | 0.00 | 0.291611E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.705916E+09 | 0.00 | 0.00 | 0.00 | 0.283790E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.648365E+09 | 0.00 | 0.00 | 0.00 | 0.129839E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.667443E+09 | 0.00 | 0.00 | 0.00 | 0.364167E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.709307E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.793716E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.859822E+10 | 0.00 | 0.00 | 0.00 | 0.957731E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.648365E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.839781E+09 | 0.00 | 0.00 | 0.00 | 0.291611E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_6:6
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.135941E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.123755E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.124398E+10 | 0.00 | 0.00 | 0.00 | 13.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.107956E+10 | 0.00 | 0.00 | 0.00 | 0.100731E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.106105E+10 | 0.00 | 0.00 | 0.00 | 0.562716E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.104250E+10 | 0.00 | 0.00 | 0.00 | 0.308909E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.108505E+10 | 0.00 | 0.00 | 0.00 | 0.525239E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.112815E+10 | 0.00 | 0.00 | 0.00 | 0.520431E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.102017E+10 | 0.00 | 0.00 | 0.00 | 0.229526E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.104990E+10 | 0.00 | 0.00 | 0.00 | 0.600096E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.113615E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.128049E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.137239E+11 | 0.00 | 0.00 | 0.00 | 0.171046E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.102017E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.135941E+10 | 0.00 | 0.00 | 0.00 | 0.525239E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_7:7
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.731754E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.666434E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.669169E+09 | 0.00 | 0.00 | 0.00 | 15.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.580027E+09 | 0.00 | 0.00 | 0.00 | 47764128.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.569249E+09 | 0.00 | 0.00 | 0.00 | 0.276340E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.558948E+09 | 0.00 | 0.00 | 0.00 | 0.155109E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.581451E+09 | 0.00 | 0.00 | 0.00 | 0.265088E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.604553E+09 | 0.00 | 0.00 | 0.00 | 0.262621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.547045E+09 | 0.00 | 0.00 | 0.00 | 0.115416E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.563115E+09 | 0.00 | 0.00 | 0.00 | 0.291780E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.610665E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.688768E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.737118E+10 | 0.00 | 0.00 | 0.00 | 0.859823E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.547045E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.731754E+09 | 0.00 | 0.00 | 0.00 | 0.265088E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_8:8
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.730586E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.665632E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.668312E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.578744E+09 | 0.00 | 0.00 | 0.00 | 45383281.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.566843E+09 | 0.00 | 0.00 | 0.00 | 0.266278E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.556071E+09 | 0.00 | 0.00 | 0.00 | 0.153102E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.578239E+09 | 0.00 | 0.00 | 0.00 | 0.263108E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.601248E+09 | 0.00 | 0.00 | 0.00 | 0.260809E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.544312E+09 | 0.00 | 0.00 | 0.00 | 0.113888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.560592E+09 | 0.00 | 0.00 | 0.00 | 0.281090E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.609518E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.687820E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.734792E+10 | 0.00 | 0.00 | 0.00 | 0.850181E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.544312E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.730586E+09 | 0.00 | 0.00 | 0.00 | 0.263108E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_9:9
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.737651E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.672785E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.674815E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.582282E+09 | 0.00 | 0.00 | 0.00 | 39983981.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.566129E+09 | 0.00 | 0.00 | 0.00 | 0.243835E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.553829E+09 | 0.00 | 0.00 | 0.00 | 0.148019E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.575748E+09 | 0.00 | 0.00 | 0.00 | 0.259633E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.599137E+09 | 0.00 | 0.00 | 0.00 | 0.257911E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.542410E+09 | 0.00 | 0.00 | 0.00 | 0.110659E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.559547E+09 | 0.00 | 0.00 | 0.00 | 0.258314E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.613564E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.694207E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.737210E+10 | 0.00 | 0.00 | 0.00 | 0.830434E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.542410E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.737651E+09 | 0.00 | 0.00 | 0.00 | 0.259633E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_10:10
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.849168E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.777882E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.767000E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.655380E+09 | 0.00 | 0.00 | 0.00 | 37708861.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.626067E+09 | 0.00 | 0.00 | 0.00 | 0.234060E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.607752E+09 | 0.00 | 0.00 | 0.00 | 0.145775E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.629630E+09 | 0.00 | 0.00 | 0.00 | 0.273107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.656680E+09 | 0.00 | 0.00 | 0.00 | 0.276265E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.595473E+09 | 0.00 | 0.00 | 0.00 | 0.113520E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.617846E+09 | 0.00 | 0.00 | 0.00 | 0.252669E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.689179E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.787860E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.825992E+10 | 0.00 | 0.00 | 0.00 | 0.861111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.595473E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.849168E+09 | 0.00 | 0.00 | 0.00 | 0.276265E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.515756E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119183E+11 | 0.00 | 0.00 | 0.52 |
February | 0.485592E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113841E+11 | 0.00 | 0.00 | 0.53 |
March | 0.806221E+10 | 0.00 | 0.00 | 54057.62 | 0.00 | 0.518668E+10 | 75464259.28 | 0.00 | 0.53 |
April | 0.647009E+10 | 26868845.48 | 0.00 | 1787447.50 | 0.00 | 0.137475E+10 | 0.137114E+10 | 0.00 | 0.58 |
May | 0.304745E+10 | 0.304062E+09 | 0.00 | 7841856.75 | 0.00 | 0.00 | 0.408590E+10 | 0.00 | 0.73 |
June | 33416329.85 | 0.368695E+10 | 0.00 | 7261397.55 | 0.00 | 0.00 | 0.240374E+10 | 0.00 | 0.76 |
July | 0.00 | 0.100813E+11 | 0.00 | 153294.46 | 0.00 | 0.00 | 10354978.18 | 0.00 | 0.54 |
August | 459217.32 | 0.826710E+10 | 0.00 | 2982172.29 | 0.00 | 0.00 | 0.360216E+09 | 0.00 | 0.60 |
September | 0.221286E+09 | 0.213573E+10 | 0.00 | 11985978.31 | 0.00 | 0.00 | 0.423755E+10 | 0.00 | 0.84 |
October | 0.387645E+10 | 0.182038E+09 | 0.00 | 8957239.23 | 0.00 | 2315631.40 | 0.509468E+10 | 0.00 | 0.77 |
November | 0.836865E+10 | 0.00 | 0.00 | 200392.10 | 0.00 | 0.307931E+10 | 0.223958E+09 | 0.00 | 0.53 |
December | 0.789188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.758545E+10 | 0.00 | 0.00 | 0.53 |
Annual Sum or Average | 0.479854E+11 | 0.246841E+11 | 0.00 | 41223835.81 | 0.00 | 0.405309E+11 | 0.178630E+11 | 0.00 | 0.62 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.52 |
Maximum of Months | 0.836865E+10 | 0.100813E+11 | 0.00 | 11985978.31 | 0.00 | 0.119183E+11 | 0.509468E+10 | 0.00 | 0.84 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.241829E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.373859E+10 | 0.00 | 0.00 | 0.38 |
February | 0.241107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.347293E+10 | 0.00 | 0.00 | 0.38 |
March | 0.353927E+10 | 0.00 | 0.00 | 89264.16 | 0.00 | 0.134322E+10 | 88087008.71 | 0.00 | 0.40 |
April | 0.236914E+10 | 14562464.96 | 0.00 | 1697595.64 | 0.00 | 0.268420E+09 | 0.123364E+10 | 0.00 | 0.51 |
May | 0.727969E+09 | 0.152250E+09 | 0.00 | 5443760.29 | 0.00 | 0.00 | 0.306164E+10 | 0.00 | 0.76 |
June | 64263.39 | 0.185716E+10 | 0.00 | 3364973.57 | 0.00 | 0.00 | 0.102714E+10 | 0.00 | 0.66 |
July | 0.00 | 0.459178E+10 | 0.00 | 44257.95 | 0.00 | 0.00 | 1071041.18 | 0.00 | 0.44 |
August | 92188.35 | 0.377195E+10 | 0.00 | 946544.24 | 0.00 | 0.00 | 86475993.28 | 0.00 | 0.48 |
September | 46158424.71 | 0.104174E+10 | 0.00 | 5903318.86 | 0.00 | 0.00 | 0.211303E+10 | 0.00 | 0.79 |
October | 0.951960E+09 | 0.103306E+09 | 0.00 | 6124946.36 | 0.00 | 0.00 | 0.352328E+10 | 0.00 | 0.78 |
November | 0.330534E+10 | 0.00 | 0.00 | 533396.21 | 0.00 | 0.760070E+09 | 0.464708E+09 | 0.00 | 0.42 |
December | 0.315616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.240341E+10 | 0.00 | 0.00 | 0.38 |
Annual Sum or Average | 0.189255E+11 | 0.115327E+11 | 0.00 | 24148057.27 | 0.00 | 0.119866E+11 | 0.115991E+11 | 0.00 | 0.53 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.353927E+10 | 0.459178E+10 | 0.00 | 6124946.36 | 0.00 | 0.373859E+10 | 0.352328E+10 | 0.00 | 0.79 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.178250E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.467439E+10 | 0.00 | 0.00 | 0.41 |
February | 0.189404E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.430582E+10 | 0.00 | 0.00 | 0.41 |
March | 0.324704E+10 | 0.00 | 0.00 | 24061.54 | 0.00 | 0.188227E+10 | 33442245.85 | 0.00 | 0.42 |
April | 0.251881E+10 | 14261728.66 | 0.00 | 736664.83 | 0.00 | 0.385010E+09 | 0.585134E+09 | 0.00 | 0.47 |
May | 0.108789E+10 | 0.147642E+09 | 0.00 | 2824814.68 | 1426491.79 | 0.00 | 0.171165E+10 | 0.00 | 0.63 |
June | 62073483.52 | 0.154536E+10 | 0.00 | 2120251.94 | 65404989.74 | 0.00 | 0.718730E+09 | 0.00 | 0.60 |
July | 440408.76 | 0.380544E+10 | 0.00 | 376333.55 | 0.203340E+09 | 0.00 | 11165037.52 | 0.00 | 0.43 |
August | 5467859.38 | 0.318398E+10 | 0.00 | 1041049.45 | 0.175204E+09 | 0.00 | 0.173431E+09 | 0.00 | 0.49 |
September | 0.177691E+09 | 0.865451E+09 | 0.00 | 3824350.71 | 39459826.05 | 0.00 | 0.145549E+10 | 0.00 | 0.68 |
October | 0.137644E+10 | 94435558.34 | 0.00 | 3341282.28 | 322510.27 | 281536.03 | 0.192930E+10 | 0.00 | 0.63 |
November | 0.300692E+10 | 0.00 | 0.00 | 133206.96 | 0.00 | 0.129180E+10 | 0.143044E+09 | 0.00 | 0.42 |
December | 0.269910E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.311994E+10 | 0.00 | 0.00 | 0.41 |
Annual Sum or Average | 0.178584E+11 | 0.965657E+10 | 0.00 | 14422015.93 | 0.485158E+09 | 0.156595E+11 | 0.676138E+10 | 0.00 | 0.50 |
Minimum of Months | 440408.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.324704E+10 | 0.380544E+10 | 0.00 | 3824350.71 | 0.203340E+09 | 0.467439E+10 | 0.192930E+10 | 0.00 | 0.68 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.160884E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.484805E+10 | 0.00 | 0.00 | 0.41 |
February | 0.168550E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.451417E+10 | 0.00 | 0.00 | 0.41 |
March | 0.304735E+10 | 0.00 | 0.00 | 16986.51 | 0.00 | 0.208084E+10 | 25968615.06 | 0.00 | 0.42 |
April | 0.246771E+10 | 13969243.37 | 0.00 | 645779.85 | 0.00 | 0.488760E+09 | 0.497008E+09 | 0.00 | 0.47 |
May | 0.111620E+10 | 0.147190E+09 | 0.00 | 2618673.60 | 1419277.44 | 2025214.06 | 0.161708E+10 | 0.00 | 0.62 |
June | 64137744.81 | 0.154109E+10 | 0.00 | 2107315.53 | 65156412.07 | 0.00 | 0.719707E+09 | 0.00 | 0.60 |
July | 394960.06 | 0.380471E+10 | 0.00 | 386359.96 | 0.203060E+09 | 0.00 | 11353095.77 | 0.00 | 0.43 |
August | 5465293.11 | 0.318589E+10 | 0.00 | 1054082.24 | 0.175080E+09 | 0.00 | 0.174054E+09 | 0.00 | 0.49 |
September | 0.181604E+09 | 0.864233E+09 | 0.00 | 3783720.13 | 39357483.43 | 0.00 | 0.144554E+10 | 0.00 | 0.67 |
October | 0.143170E+10 | 92212449.52 | 0.00 | 3191983.54 | 295067.71 | 279527.43 | 0.184227E+10 | 0.00 | 0.63 |
November | 0.287753E+10 | 0.00 | 0.00 | 99849.68 | 0.00 | 0.143424E+10 | 0.100323E+09 | 0.00 | 0.42 |
December | 0.249130E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.332729E+10 | 0.00 | 0.00 | 0.41 |
Annual Sum or Average | 0.169778E+11 | 0.964929E+10 | 0.00 | 13904751.03 | 0.484369E+09 | 0.166957E+11 | 0.643331E+10 | 0.00 | 0.50 |
Minimum of Months | 394960.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.304735E+10 | 0.380471E+10 | 0.00 | 3783720.13 | 0.203060E+09 | 0.484805E+10 | 0.184227E+10 | 0.00 | 0.67 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.126353E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.519333E+10 | 0.00 | 0.00 | 0.41 |
February | 0.136507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.483488E+10 | 0.00 | 0.00 | 0.41 |
March | 0.267140E+10 | 0.00 | 0.00 | 12078.59 | 0.00 | 0.245277E+10 | 18877819.44 | 0.00 | 0.42 |
April | 0.237693E+10 | 13369906.49 | 0.00 | 498421.54 | 0.00 | 0.619635E+09 | 0.402859E+09 | 0.00 | 0.46 |
May | 0.121378E+10 | 0.145048E+09 | 0.00 | 2192181.66 | 1401167.68 | 2357647.24 | 0.138767E+10 | 0.00 | 0.60 |
June | 70185287.70 | 0.150768E+10 | 0.00 | 1974967.30 | 64163257.88 | 0.00 | 0.700493E+09 | 0.00 | 0.60 |
July | 507884.99 | 0.376119E+10 | 0.00 | 345821.00 | 0.201326E+09 | 0.00 | 10985513.64 | 0.00 | 0.43 |
August | 5429491.13 | 0.315837E+10 | 0.00 | 993239.24 | 0.174175E+09 | 0.00 | 0.172920E+09 | 0.00 | 0.49 |
September | 0.203270E+09 | 0.838803E+09 | 0.00 | 3648591.76 | 38866033.35 | 0.00 | 0.139553E+10 | 0.00 | 0.67 |
October | 0.149431E+10 | 87290335.48 | 0.00 | 2885968.99 | 237710.89 | 817109.05 | 0.169676E+10 | 0.00 | 0.61 |
November | 0.267945E+10 | 0.00 | 0.00 | 66975.47 | 0.00 | 0.162370E+10 | 68642670.32 | 0.00 | 0.42 |
December | 0.216211E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.365618E+10 | 0.00 | 0.00 | 0.41 |
Annual Sum or Average | 0.155060E+11 | 0.951174E+10 | 0.00 | 12618245.55 | 0.480170E+09 | 0.183837E+11 | 0.585473E+10 | 0.00 | 0.49 |
Minimum of Months | 507884.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.267945E+10 | 0.376119E+10 | 0.00 | 3648591.76 | 0.201326E+09 | 0.519333E+10 | 0.169676E+10 | 0.00 | 0.67 |
Report: MechanicalVentilationLoadsMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.107645E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109860E+11 | 0.00 | 0.00 | 0.38 |
February | 0.107517E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104602E+11 | 0.00 | 0.00 | 0.38 |
March | 0.403827E+10 | 0.00 | 0.00 | 6250.69 | 0.00 | 0.556570E+10 | 16515000.17 | 0.00 | 0.39 |
April | 0.442096E+10 | 15955615.38 | 0.00 | 610355.81 | 162241.97 | 0.139070E+10 | 0.481164E+09 | 0.00 | 0.41 |
May | 0.258857E+10 | 0.247397E+09 | 0.00 | 2933989.10 | 1595388.76 | 2049332.44 | 0.204140E+10 | 0.00 | 0.51 |
June | 45562154.51 | 0.263562E+10 | 0.00 | 3427855.23 | 35961474.51 | 0.00 | 0.137883E+10 | 0.00 | 0.53 |
July | 1107134.02 | 0.688720E+10 | 0.00 | 409854.03 | 0.107850E+09 | 0.00 | 13266674.04 | 0.00 | 0.39 |
August | 4250819.70 | 0.593526E+10 | 0.00 | 1447580.86 | 76278516.70 | 0.00 | 0.212414E+09 | 0.00 | 0.44 |
September | 0.261095E+09 | 0.150607E+10 | 0.00 | 6039612.71 | 8814983.17 | 0.00 | 0.254324E+10 | 0.00 | 0.58 |
October | 0.280761E+10 | 0.116903E+09 | 0.00 | 4567130.52 | 0.00 | 3136212.25 | 0.285387E+10 | 0.00 | 0.53 |
November | 0.434275E+10 | 0.00 | 0.00 | 61245.73 | 0.00 | 0.369532E+10 | 89158540.51 | 0.00 | 0.38 |
December | 0.237667E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.852983E+10 | 0.00 | 0.00 | 0.38 |
Annual Sum or Average | 0.230385E+11 | 0.173444E+11 | 0.00 | 19503874.68 | 0.230663E+09 | 0.406329E+11 | 0.962986E+10 | 0.00 | 0.44 |
Minimum of Months | 1107134.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.442096E+10 | 0.688720E+10 | 0.00 | 6039612.71 | 0.107850E+09 | 0.109860E+11 | 0.285387E+10 | 0.00 | 0.58 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.478734E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.554084E+10 | 0.00 | 0.00 | 0.38 |
February | 0.436649E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.532050E+10 | 0.00 | 0.00 | 0.38 |
March | 0.186012E+10 | 0.00 | 0.00 | 1720.55 | 0.00 | 0.292962E+10 | 6950884.68 | 0.00 | 0.39 |
April | 0.206817E+10 | 8030121.41 | 0.00 | 285481.64 | 114543.98 | 0.848538E+09 | 0.212338E+09 | 0.00 | 0.41 |
May | 0.132571E+10 | 0.123515E+09 | 0.00 | 1376155.23 | 802994.13 | 4119737.52 | 0.958850E+09 | 0.00 | 0.51 |
June | 27307011.28 | 0.131420E+10 | 0.00 | 1701685.55 | 17638003.49 | 0.00 | 0.701750E+09 | 0.00 | 0.54 |
July | 553273.70 | 0.343830E+10 | 0.00 | 193184.59 | 53228835.57 | 0.00 | 6891273.01 | 0.00 | 0.39 |
August | 2135052.41 | 0.296642E+10 | 0.00 | 709242.77 | 37829949.69 | 0.00 | 0.109516E+09 | 0.00 | 0.44 |
September | 0.137416E+09 | 0.751927E+09 | 0.00 | 3040846.46 | 4311033.07 | 0.00 | 0.128574E+10 | 0.00 | 0.59 |
October | 0.141283E+10 | 56327747.09 | 0.00 | 2289936.67 | 0.00 | 2337420.77 | 0.143572E+10 | 0.00 | 0.54 |
November | 0.199151E+10 | 0.00 | 0.00 | 19955.72 | 0.00 | 0.202055E+10 | 34587303.14 | 0.00 | 0.38 |
December | 0.105647E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.438523E+10 | 0.00 | 0.00 | 0.38 |
Annual Sum or Average | 0.107976E+11 | 0.865872E+10 | 0.00 | 9618209.17 | 0.113925E+09 | 0.210517E+11 | 0.475235E+10 | 0.00 | 0.44 |
Minimum of Months | 553273.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.206817E+10 | 0.343830E+10 | 0.00 | 3040846.46 | 53228835.57 | 0.554084E+10 | 0.143572E+10 | 0.00 | 0.59 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.443928E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.557564E+10 | 0.00 | 0.00 | 0.38 |
February | 0.397030E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.536015E+10 | 0.00 | 0.00 | 0.38 |
March | 0.178675E+10 | 0.00 | 0.00 | 859.91 | 0.00 | 0.300315E+10 | 4628002.44 | 0.00 | 0.39 |
April | 0.202398E+10 | 7925480.62 | 0.00 | 266654.62 | 150888.15 | 0.892227E+09 | 0.201060E+09 | 0.00 | 0.41 |
May | 0.136754E+10 | 0.122684E+09 | 0.00 | 1242660.04 | 806528.46 | 6577101.90 | 0.870732E+09 | 0.00 | 0.50 |
June | 32300330.73 | 0.130250E+10 | 0.00 | 1657371.84 | 17531459.89 | 0.00 | 0.691612E+09 | 0.00 | 0.54 |
July | 534627.20 | 0.342325E+10 | 0.00 | 187237.73 | 53067648.69 | 0.00 | 7117336.17 | 0.00 | 0.39 |
August | 2223287.37 | 0.295738E+10 | 0.00 | 697424.34 | 37774793.44 | 0.00 | 0.109370E+09 | 0.00 | 0.44 |
September | 0.141226E+09 | 0.743655E+09 | 0.00 | 2981136.86 | 4287922.45 | 0.00 | 0.126702E+10 | 0.00 | 0.59 |
October | 0.143680E+10 | 54982016.54 | 0.00 | 2167227.74 | 0.00 | 1496211.39 | 0.138255E+10 | 0.00 | 0.53 |
November | 0.192833E+10 | 0.00 | 0.00 | 12349.88 | 0.00 | 0.208776E+10 | 24317804.84 | 0.00 | 0.38 |
December | 0.957528E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.448426E+10 | 0.00 | 0.00 | 0.38 |
Annual Sum or Average | 0.105182E+11 | 0.861237E+10 | 0.00 | 9212922.97 | 0.113619E+09 | 0.214113E+11 | 0.455840E+10 | 0.00 | 0.44 |
Minimum of Months | 534627.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.202398E+10 | 0.342325E+10 | 0.00 | 2981136.86 | 53067648.69 | 0.557564E+10 | 0.138255E+10 | 0.00 | 0.59 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.262808E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.575673E+10 | 0.00 | 0.00 | 0.38 |
February | 0.199122E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.555804E+10 | 0.00 | 0.00 | 0.38 |
March | 0.142957E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.336036E+10 | 0.00 | 0.00 | 0.39 |
April | 0.178761E+10 | 7520327.87 | 0.00 | 224465.72 | 432227.77 | 0.112101E+10 | 0.180997E+09 | 0.00 | 0.41 |
May | 0.142007E+10 | 0.120261E+09 | 0.00 | 962613.83 | 932323.54 | 31857415.03 | 0.703906E+09 | 0.00 | 0.49 |
June | 39129815.63 | 0.126597E+10 | 0.00 | 1519664.92 | 17672013.64 | 0.00 | 0.672017E+09 | 0.00 | 0.53 |
July | 603810.00 | 0.338760E+10 | 0.00 | 168336.81 | 52742542.63 | 0.00 | 8750236.53 | 0.00 | 0.39 |
August | 1318327.85 | 0.293256E+10 | 0.00 | 716782.43 | 37672335.08 | 0.00 | 0.114091E+09 | 0.00 | 0.44 |
September | 0.175321E+09 | 0.726148E+09 | 0.00 | 2800949.51 | 4224416.40 | 0.00 | 0.120381E+10 | 0.00 | 0.58 |
October | 0.150213E+10 | 51680315.74 | 0.00 | 1919980.80 | 0.00 | 4390819.31 | 0.125041E+10 | 0.00 | 0.52 |
November | 0.170473E+10 | 0.00 | 0.00 | 2871.49 | 0.00 | 0.231493E+10 | 9032710.00 | 0.00 | 0.38 |
December | 0.590050E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.485170E+10 | 0.00 | 0.00 | 0.38 |
Annual Sum or Average | 0.911247E+10 | 0.849174E+10 | 0.00 | 8315665.53 | 0.113676E+09 | 0.229990E+11 | 0.414302E+10 | 0.00 | 0.44 |
Minimum of Months | 603810.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.178761E+10 | 0.338760E+10 | 0.00 | 2800949.51 | 52742542.63 | 0.575673E+10 | 0.125041E+10 | 0.00 | 0.58 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 9122993.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.599055E+10 | 0.00 | 0.00 | 0.38 |
February | 4478091.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.573545E+10 | 0.00 | 0.00 | 0.38 |
March | 0.603300E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.415255E+10 | 0.00 | 0.00 | 0.39 |
April | 0.111388E+10 | 7285084.05 | 0.00 | 182363.73 | 1211713.99 | 0.176003E+10 | 0.158387E+09 | 0.00 | 0.41 |
May | 0.133953E+10 | 0.119560E+09 | 0.00 | 739450.35 | 1502875.79 | 0.134917E+09 | 0.575640E+09 | 0.00 | 0.49 |
June | 65177897.12 | 0.118158E+10 | 0.00 | 1435865.97 | 19233289.39 | 0.00 | 0.677637E+09 | 0.00 | 0.55 |
July | 636294.34 | 0.335263E+10 | 0.00 | 200258.34 | 51922035.26 | 0.00 | 23214642.92 | 0.00 | 0.40 |
August | 1710042.99 | 0.295200E+10 | 0.00 | 719682.24 | 37539476.63 | 0.00 | 0.133021E+09 | 0.00 | 0.46 |
September | 0.270766E+09 | 0.707325E+09 | 0.00 | 2647254.03 | 4131705.13 | 0.00 | 0.112394E+10 | 0.00 | 0.61 |
October | 0.152023E+10 | 52625308.57 | 0.00 | 1695481.86 | 0.00 | 44412884.15 | 0.111042E+10 | 0.00 | 0.52 |
November | 0.110744E+10 | 0.00 | 0.00 | 201.35 | 0.00 | 0.288073E+10 | 3288930.29 | 0.00 | 0.38 |
December | 56125756.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.536659E+10 | 0.00 | 0.00 | 0.38 |
Annual Sum or Average | 0.609240E+10 | 0.837300E+10 | 0.00 | 7620557.87 | 0.115541E+09 | 0.260652E+11 | 0.380555E+10 | 0.00 | 0.44 |
Minimum of Months | 636294.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.152023E+10 | 0.335263E+10 | 0.00 | 2647254.03 | 51922035.26 | 0.599055E+10 | 0.112394E+10 | 0.00 | 0.61 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.110230E+12 | 0.392594E+11 | 0.00 | 0.814545E+11 | 0.243557E+11 |
February | 0.199192E+12 | 0.365903E+11 | 0.00 | 0.778592E+11 | 0.228489E+11 |
March | 0.364824E+12 | 0.292000E+11 | 0.00 | 0.646608E+11 | 0.134145E+11 |
April | 0.410062E+12 | 0.184326E+11 | 0.00 | 0.429913E+11 | 0.819614E+10 |
May | 0.543079E+12 | 0.102865E+11 | 0.00 | 0.308619E+11 | 0.195433E+11 |
June | 0.540813E+12 | -0.492976E+10 | 0.00 | -0.748109E+10 | 0.106095E+12 |
July | 0.532958E+12 | -0.184701E+11 | 0.00 | -0.466192E+11 | 0.186101E+12 |
August | 0.512247E+12 | -0.149633E+11 | 0.00 | -0.376446E+11 | 0.179476E+12 |
September | 0.346288E+12 | 0.604367E+09 | 0.00 | 0.963683E+10 | 0.799698E+11 |
October | 0.318571E+12 | 0.135995E+11 | 0.00 | 0.391610E+11 | 0.210381E+11 |
November | 0.137969E+12 | 0.259145E+11 | 0.00 | 0.552152E+11 | 0.899234E+10 |
December | 0.808490E+11 | 0.345397E+11 | 0.00 | 0.739100E+11 | 0.184724E+11 |
Annual Sum or Average | 0.409708E+13 | 0.170064E+12 | 0.00 | 0.384006E+12 | 0.688504E+12 |
Minimum of Months | 0.808490E+11 | -0.184701E+11 | 0.00 | -0.466192E+11 | 0.819614E+10 |
Maximum of Months | 0.543079E+12 | 0.392594E+11 | 0.00 | 0.814545E+11 | 0.186101E+12 |