Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:37
Tabular Output Report in Format: HTML
Building: RetailStripmall
Environment: RUNPERIOD 1 ** El Paso International Ap Ut TX USA TMY3 WMO#=722700
Simulation Timestamp: 2023-10-16 08:37:11
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:11
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 964.99 | 461.65 | 461.65 |
Net Site Energy | 964.99 | 461.65 | 461.65 |
Total Source Energy | 2930.64 | 1402.01 | 1402.01 |
Net Source Energy | 2930.64 | 1402.01 | 1402.01 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 2090.32 |
Net Conditioned Building Area | 2090.32 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 60.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 177.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 366.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 60.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 128.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 110.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 61.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 904.75 | 60.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 60.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 177.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 366.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 60.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 128.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 110.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 61.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 60.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 177.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 366.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 60.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 128.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 110.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 61.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 204.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 167.37 | 28.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Other | 61.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 432.83 | 28.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 204.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 167.37 | 28.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Other | 61.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 432.83 | 28.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 904.752 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 904.752 | 100.00 |
Total On-Site and Utility Electric Sources | 904.752 | 100.00 |
Total Electricity End Uses | 904.752 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 87.30 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 87.30 | 100.00 |
Total Water End Uses | 87.30 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 0.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 784.33 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTRIPMALL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3B
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_TX_ELPASO
| Environment |ZoneCoolingSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ZoneHeatingSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ZoneElectricSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |SpaceGainsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |PeakSpaceGainsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |SpaceGainComponentsAtCoolingPeakMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ComfortReportSimple55Monthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |OccupantComfortDataSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |DXReportMonthly
| PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL | PSZ-AC_3:3 COOLING COIL | PSZ-AC_4:4 COOLING COIL | PSZ-AC_5:5 COOLING COIL | PSZ-AC_6:6 COOLING COIL | PSZ-AC_7:7 COOLING COIL | PSZ-AC_8:8 COOLING COIL | PSZ-AC_9:9 COOLING COIL | PSZ-AC_10:10 COOLING COIL |WindowReportMonthly
| LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR |WindowEnergyReportMonthly
| LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR |WindowZoneSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |WindowEnergyZoneSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| GAS TANK1 | GAS TANK2 | GAS TANK3 | GAS TANK4 | GAS TANK5 | GAS TANK6 | GAS TANK7 |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC_1:1 HEATING COIL | PSZ-AC_2:2 HEATING COIL | PSZ-AC_3:3 HEATING COIL | PSZ-AC_4:4 HEATING COIL | PSZ-AC_5:5 HEATING COIL | PSZ-AC_6:6 HEATING COIL | PSZ-AC_7:7 HEATING COIL | PSZ-AC_8:8 HEATING COIL | PSZ-AC_9:9 HEATING COIL | PSZ-AC_10:10 HEATING COIL | PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL | PSZ-AC_3:3 COOLING COIL | PSZ-AC_4:4 COOLING COIL | PSZ-AC_5:5 COOLING COIL | PSZ-AC_6:6 COOLING COIL | PSZ-AC_7:7 COOLING COIL | PSZ-AC_8:8 COOLING COIL | PSZ-AC_9:9 COOLING COIL | PSZ-AC_10:10 COOLING COIL |FanReportMonthly
| PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN |ZoneTemperatureOscillationReportMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |MechanicalVentilationLoadsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:11
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:37 |
RunPeriod | RUNPERIOD 1 |
Weather File | El Paso International Ap Ut TX USA TMY3 WMO#=722700 |
Latitude [deg] | 31.77 |
Longitude [deg] | -106.5 |
Elevation [m] | 1186.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Above Ground Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Window Opening Area [m2] | 124.40 | 0.00 | 0.00 | 124.40 | 0.00 |
Gross Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Above Ground Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Above Ground Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Window Opening Area [m2] | 124.40 | 0.00 | 0.00 | 124.40 | 0.00 |
Gross Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Above Ground Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Total | |
Gross Roof Area [m2] | 2090.32 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
LGSTORE1 | 348.39 | Yes | Yes | 1805.20 | 1.00 | 276.30 | 0.00 | 20.77 | 20.77 | 15.3022 | 6.19 | 4.3000 |
SMSTORE1 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.38 | 10.38 | 18.2890 | 6.19 | 4.3000 |
SMSTORE2 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 16.6533 | 6.19 | 4.3000 |
SMSTORE3 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 16.6533 | 6.19 | 4.3000 |
SMSTORE4 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 16.6533 | 6.19 | 4.3000 |
LGSTORE2 | 348.39 | Yes | Yes | 1805.20 | 1.00 | 157.89 | 0.00 | 20.72 | 20.72 | 9.5842 | 6.19 | 4.3000 |
SMSTORE5 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 9.6995 | 6.19 | 4.3000 |
SMSTORE6 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 9.6995 | 6.19 | 4.3000 |
SMSTORE7 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 9.6995 | 6.19 | 4.3000 |
SMSTORE8 | 174.19 | Yes | Yes | 902.60 | 1.00 | 197.36 | 0.00 | 10.36 | 10.36 | 9.6995 | 6.19 | 4.3000 |
Total | 2090.32 | 10831.20 | 1184.15 | 0.00 | 124.40 | 124.40 | 13.0683 | 6.19 | 4.3000 | |||
Conditioned Total | 2090.32 | 10831.20 | 1184.15 | 0.00 | 124.40 | 124.40 | 13.0683 | 6.19 | 4.3000 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
LGSTORE1 | 348.39 | Yes | Yes | 1.00 | LGSTORE1 | GENERAL | LGSTORE1 | 15.3022 | 6.19 | 4.3000 | |
SMSTORE1 | 174.19 | Yes | Yes | 1.00 | SMSTORE1 | GENERAL | SMSTORE1 | 18.2890 | 6.19 | 4.3000 | |
SMSTORE2 | 174.19 | Yes | Yes | 1.00 | SMSTORE2 | GENERAL | SMSTORE2 | 16.6533 | 6.19 | 4.3000 | |
SMSTORE3 | 174.19 | Yes | Yes | 1.00 | SMSTORE3 | GENERAL | SMSTORE3 | 16.6533 | 6.19 | 4.3000 | |
SMSTORE4 | 174.19 | Yes | Yes | 1.00 | SMSTORE4 | GENERAL | SMSTORE4 | 16.6533 | 6.19 | 4.3000 | |
LGSTORE2 | 348.39 | Yes | Yes | 1.00 | LGSTORE2 | GENERAL | LGSTORE2 | 9.5842 | 6.19 | 4.3000 | |
SMSTORE5 | 174.19 | Yes | Yes | 1.00 | SMSTORE5 | GENERAL | SMSTORE5 | 9.6995 | 6.19 | 4.3000 | |
SMSTORE6 | 174.19 | Yes | Yes | 1.00 | SMSTORE6 | GENERAL | SMSTORE6 | 9.6995 | 6.19 | 4.3000 | |
SMSTORE7 | 174.19 | Yes | Yes | 1.00 | SMSTORE7 | GENERAL | SMSTORE7 | 9.6995 | 6.19 | 4.3000 | |
SMSTORE8 | 174.19 | Yes | Yes | 1.00 | SMSTORE8 | GENERAL | SMSTORE8 | 9.6995 | 6.19 | 4.3000 | |
Total | 2090.32 | 13.0683 | 3.10 | 4.3000 | |||||||
Conditioned Total | 2090.32 | 13.0683 | 3.10 | 4.3000 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 2090.32 | 2090.32 | 0.00 | 0.00 | 13.0683 | 6.19 | 4.3000 |
Total | 2090.32 | 2090.32 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:11
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 02-JUN-16:00 | 27-DEC-08:09 | - | - | - | - | - | - | - | - | - | - | 06-JAN-13:09 |
Heating | 0.00 | 115995.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 42114.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 23459.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 8059.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 7642.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 7272.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 88548.95 | 115995.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 115995.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 42114.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 23459.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 8059.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 7642.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 7272.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:11
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 65.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 562.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1161.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 190.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 405.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 350.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 194.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2865.35 | 65.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 31.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 269.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 555.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 90.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 194.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 167.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 93.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1370.77 | 31.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 31.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 269.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 555.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 90.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 194.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 167.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 93.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1370.77 | 31.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:11
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
LGSTORE1 DIRECT AIR | 2.39 |
SMSTORE1 DIRECT AIR | 1.25 |
SMSTORE2 DIRECT AIR | 1.28 |
SMSTORE3 DIRECT AIR | 1.28 |
SMSTORE4 DIRECT AIR | 1.28 |
LGSTORE2 DIRECT AIR | 2.20 |
SMSTORE5 DIRECT AIR | 1.14 |
SMSTORE6 DIRECT AIR | 1.14 |
SMSTORE7 DIRECT AIR | 1.14 |
SMSTORE8 DIRECT AIR | 1.30 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC_1:1 | 2.39 | 2.39 | 2.39 | 2.39 | 2.39 | 2.39 | 1.00 | 1.00 | 2.39 |
PSZ-AC_2:2 | 1.25 | 1.25 | 1.25 | 1.25 | 1.25 | 1.25 | 1.00 | 1.00 | 1.25 |
PSZ-AC_3:3 | 1.28 | 1.28 | 1.28 | 1.28 | 1.28 | 1.28 | 1.00 | 1.000000 | 1.28 |
PSZ-AC_4:4 | 1.28 | 1.28 | 1.28 | 1.28 | 1.28 | 1.28 | 1.00 | 1.00 | 1.28 |
PSZ-AC_5:5 | 1.28 | 1.28 | 1.28 | 1.28 | 1.28 | 1.28 | 1.00 | 1.00 | 1.28 |
PSZ-AC_6:6 | 2.20 | 2.20 | 2.20 | 2.20 | 2.20 | 2.20 | 1.00 | 1.00 | 2.20 |
PSZ-AC_7:7 | 1.14 | 1.14 | 1.14 | 1.14 | 1.14 | 1.14 | 1.00 | 1.00 | 1.14 |
PSZ-AC_8:8 | 1.14 | 1.14 | 1.14 | 1.14 | 1.14 | 1.14 | 1.00 | 1.00 | 1.14 |
PSZ-AC_9:9 | 1.14 | 1.14 | 1.14 | 1.14 | 1.14 | 1.14 | 1.00 | 1.00 | 1.14 |
PSZ-AC_10:10 | 1.30 | 1.30 | 1.30 | 1.30 | 1.30 | 1.30 | 1.00 | 1.00 | 1.30 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC_1:1_OA_CONTROLLER | 2.39 | 0.411479 |
PSZ-AC_2:2_OA_CONTROLLER | 1.25 | 0.205739 |
PSZ-AC_3:3_OA_CONTROLLER | 1.28 | 0.205739 |
PSZ-AC_4:4_OA_CONTROLLER | 1.28 | 0.205739 |
PSZ-AC_5:5_OA_CONTROLLER | 1.28 | 0.205739 |
PSZ-AC_6:6_OA_CONTROLLER | 2.20 | 0.411479 |
PSZ-AC_7:7_OA_CONTROLLER | 1.14 | 0.205739 |
PSZ-AC_8:8_OA_CONTROLLER | 1.14 | 0.205739 |
PSZ-AC_9:9_OA_CONTROLLER | 1.14 | 0.205739 |
PSZ-AC_10:10_OA_CONTROLLER | 1.30 | 0.205739 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | 2.39 | 2561.22 |
PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | 1.25 | 1383.93 |
PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | 1.28 | 1422.63 |
PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | 1.28 | 1414.74 |
PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | 1.28 | 1413.02 |
PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | 2.20 | 2348.77 |
PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | 1.14 | 1264.42 |
PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | 1.14 | 1258.58 |
PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | 1.14 | 1260.41 |
PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | 1.30 | 1433.88 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC_1:1_UNITARY_PACKAGE_DX | 2.39 | 2.39 | 2.39 | 1.58 | 45276.41 | 58814.13 | 40.00 | 1.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_DX | 1.25 | 1.25 | 1.25 | 0.824989 | 23485.02 | 30461.80 | 40.00 | 1.00 |
PSZ-AC_3:3_UNITARY_PACKAGE_DX | 1.28 | 1.28 | 1.28 | 0.848058 | 24133.95 | 31154.76 | 40.00 | 1.00 |
PSZ-AC_4:4_UNITARY_PACKAGE_DX | 1.28 | 1.28 | 1.28 | 0.843356 | 23989.93 | 31013.52 | 40.00 | 1.00 |
PSZ-AC_5:5_UNITARY_PACKAGE_DX | 1.28 | 1.28 | 1.28 | 0.842328 | 23991.93 | 30982.65 | 40.00 | 1.00 |
PSZ-AC_6:6_UNITARY_PACKAGE_DX | 2.20 | 2.20 | 2.20 | 1.45 | 42109.61 | 54877.46 | 40.00 | 1.00 |
PSZ-AC_7:7_UNITARY_PACKAGE_DX | 1.14 | 1.14 | 1.14 | 0.753749 | 21755.53 | 28321.81 | 40.00 | 1.00 |
PSZ-AC_8:8_UNITARY_PACKAGE_DX | 1.14 | 1.14 | 1.14 | 0.750265 | 21670.67 | 28217.14 | 40.00 | 1.00 |
PSZ-AC_9:9_UNITARY_PACKAGE_DX | 1.14 | 1.14 | 1.14 | 0.751354 | 21697.67 | 28249.86 | 40.00 | 1.00 |
PSZ-AC_10:10_UNITARY_PACKAGE_DX | 1.30 | 1.30 | 1.30 | 0.854765 | 23853.43 | 31356.71 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-AC_1:1 COOLING COIL | 2.39 | 1.20 | 1.60 | 45276.41 | 22638.21 | 0.798740 | 0.798740 |
PSZ-AC_2:2 COOLING COIL | 1.25 | 0.624992 | 0.833320 | 23485.02 | 11742.51 | 0.800930 | 0.800930 |
PSZ-AC_3:3 COOLING COIL | 1.28 | 0.642468 | 0.856627 | 24133.95 | 12066.98 | 0.800030 | 0.800030 |
PSZ-AC_4:4 COOLING COIL | 1.28 | 0.638906 | 0.851873 | 23989.93 | 11994.97 | 0.800170 | 0.800170 |
PSZ-AC_5:5 COOLING COIL | 1.28 | 0.638127 | 0.850833 | 23991.93 | 11995.97 | 0.800750 | 0.800750 |
PSZ-AC_6:6 COOLING COIL | 2.20 | 1.10 | 1.46 | 42109.61 | 21054.81 | 0.793240 | 0.793240 |
PSZ-AC_7:7 COOLING COIL | 1.14 | 0.571022 | 0.761360 | 21755.53 | 10877.76 | 0.796480 | 0.796480 |
PSZ-AC_8:8 COOLING COIL | 1.14 | 0.568382 | 0.757840 | 21670.67 | 10835.33 | 0.795250 | 0.795250 |
PSZ-AC_9:9 COOLING COIL | 1.14 | 0.569207 | 0.758940 | 21697.67 | 10848.83 | 0.795320 | 0.795320 |
PSZ-AC_10:10 COOLING COIL | 1.30 | 0.647549 | 0.863400 | 23853.43 | 11926.72 | 0.800430 | 0.800430 |
Design Size Nominal Capacity [W] | |
PSZ-AC_1:1 HEATING COIL | 58814.13 |
PSZ-AC_2:2 HEATING COIL | 30461.80 |
PSZ-AC_3:3 HEATING COIL | 31154.76 |
PSZ-AC_4:4 HEATING COIL | 31013.52 |
PSZ-AC_5:5 HEATING COIL | 30982.65 |
PSZ-AC_6:6 HEATING COIL | 54877.46 |
PSZ-AC_7:7 HEATING COIL | 28321.81 |
PSZ-AC_8:8 HEATING COIL | 28217.14 |
PSZ-AC_9:9 HEATING COIL | 28249.86 |
PSZ-AC_10:10 HEATING COIL | 31356.71 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:11
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
LGSTORE1_WALL_3 | LGSTORE1_WALL_3_DOOR_1 | LGSTORE1_WALL_3_DOOR_2 | |
LGSTORE1_WALL_1 | LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | |
SMSTORE1_WALL_1 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | |
SMSTORE1_WALL_3 | SMSTORE1_WALL_3_DOOR | |
SMSTORE2_WALL_1 | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | |
SMSTORE2_WALL_3 | SMSTORE2_WALL_3_DOOR | |
SMSTORE3_WALL_1 | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | |
SMSTORE3_WALL_3 | SMSTORE3_WALL_3_DOOR | |
SMSTORE4_WALL_1 | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | |
SMSTORE4_WALL_3 | SMSTORE4_WALL_3_DOOR | |
LGSTORE2_WALL_3 | LGSTORE2_WALL_3_DOOR_1 | LGSTORE2_WALL_3_DOOR_2 | |
LGSTORE2_WALL_1 | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | |
SMSTORE5_WALL_1 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | |
SMSTORE5_WALL_3 | SMSTORE5_WALL_3_DOOR | |
SMSTORE6_WALL_1 | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | |
SMSTORE6_WALL_3 | SMSTORE6_WALL_3_DOOR | |
SMSTORE7_WALL_1 | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | |
SMSTORE7_WALL_3 | SMSTORE7_WALL_3_DOOR | |
SMSTORE8_WALL_1 | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR | |
SMSTORE8_WALL_3 | SMSTORE8_WALL_3_DOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:11
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:11
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.30 | 11.20 | 6.80 | 8.10 | 10.30 | 12.50 | 19.20 | 23.80 | 27.90 | 27.50 | 26.30 | 23.40 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | El Paso International Ap Ut TX USA TMY3 WMO#=722700 | 31.77 | -106.50 | -7.00 | 1186.00 | 87865 | 1.0443 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 17.94 | 21.10 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RetailStripmall | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 10 | 118 | 48 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | LGSTORE1 | 0.0 | 0.00 | 0.00 | 0.00 | 7.62 | 11.43 | 2.59 | 1 | 1 | 1 | 0.00 | 15.24 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 1805.20 | TARP | TARP | 348.39 | 276.30 | 247.74 | 20.77 | 6 | 8 | 0 | Yes |
2 | SMSTORE1 | 0.0 | 0.00 | 0.00 | 0.00 | 19.05 | 11.43 | 2.59 | 1 | 1 | 1 | 15.24 | 22.86 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.66 | 10.38 | 6 | 4 | 0 | Yes |
3 | SMSTORE2 | 0.0 | 0.00 | 0.00 | 0.00 | 26.67 | 11.43 | 2.59 | 1 | 1 | 1 | 22.86 | 30.48 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
4 | SMSTORE3 | 0.0 | 0.00 | 0.00 | 0.00 | 34.29 | 11.43 | 2.59 | 1 | 1 | 1 | 30.48 | 38.10 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
5 | SMSTORE4 | 0.0 | 0.00 | 0.00 | 0.00 | 41.91 | 11.43 | 2.59 | 1 | 1 | 1 | 38.10 | 45.72 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
6 | LGSTORE2 | 0.0 | 0.00 | 0.00 | 0.00 | 53.34 | 11.43 | 2.59 | 1 | 1 | 1 | 45.72 | 60.96 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 1805.20 | TARP | TARP | 348.39 | 157.89 | 129.41 | 20.72 | 6 | 8 | 0 | Yes |
7 | SMSTORE5 | 0.0 | 0.00 | 0.00 | 0.00 | 64.77 | 11.43 | 2.59 | 1 | 1 | 1 | 60.96 | 68.58 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
8 | SMSTORE6 | 0.0 | 0.00 | 0.00 | 0.00 | 72.39 | 11.43 | 2.59 | 1 | 1 | 1 | 68.58 | 76.20 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
9 | SMSTORE7 | 0.0 | 0.00 | 0.00 | 0.00 | 80.01 | 11.43 | 2.59 | 1 | 1 | 1 | 76.20 | 83.82 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
10 | SMSTORE8 | 0.0 | 0.00 | 0.00 | 0.00 | 87.63 | 11.43 | 2.59 | 1 | 1 | 1 | 83.82 | 91.44 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 197.36 | 183.12 | 10.36 | 6 | 4 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | LGSTORE1 | 348.39 | 56.3 | 6.193 | 0.161 | 15.302 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 19.602 | No |
2 | SMSTORE1 | 174.19 | 28.1 | 6.194 | 0.161 | 18.289 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 22.589 | No |
3 | SMSTORE2 | 174.19 | 28.1 | 6.194 | 0.161 | 16.653 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 20.953 | No |
4 | SMSTORE3 | 174.19 | 28.1 | 6.194 | 0.161 | 16.653 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 20.953 | No |
5 | SMSTORE4 | 174.19 | 28.1 | 6.194 | 0.161 | 16.653 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 20.953 | No |
6 | LGSTORE2 | 348.39 | 56.3 | 6.193 | 0.161 | 9.584 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 13.884 | No |
7 | SMSTORE5 | 174.19 | 28.1 | 6.194 | 0.161 | 9.699 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 13.999 | No |
8 | SMSTORE6 | 174.19 | 28.1 | 6.194 | 0.161 | 9.699 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 13.999 | No |
9 | SMSTORE7 | 174.19 | 28.1 | 6.194 | 0.161 | 9.699 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 13.999 | No |
10 | SMSTORE8 | 174.19 | 28.1 | 6.194 | 0.161 | 9.699 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 13.999 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | LGSTORE1 | TYPE1_OCC_SCH | LGSTORE1 | 348.39 | 56.3 | 56.3 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 56 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | SMSTORE1 | TYPE1_OCC_SCH | SMSTORE1 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | SMSTORE2 | TYPE2_OCC_SCH | SMSTORE2 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | SMSTORE3 | TYPE2_OCC_SCH | SMSTORE3 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | SMSTORE4 | TYPE2_OCC_SCH | SMSTORE4 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | LGSTORE2 | TYPE3_OCC_SCH | LGSTORE2 | 348.39 | 56.3 | 56.3 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 56 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | SMSTORE5 | TYPE3_OCC_SCH | SMSTORE5 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | SMSTORE6 | TYPE3_OCC_SCH | SMSTORE6 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | SMSTORE7 | TYPE3_OCC_SCH | SMSTORE7 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | SMSTORE8 | TYPE3_OCC_SCH | SMSTORE8 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | LGSTORE1_LIGHTS | LTG_SCH_BASE_LPD1 | LGSTORE1 | 348.39 | 56.3 | 3346.345 | 9.605 | 59.490 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3346.345 |
2 | LGSTORE1_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | LGSTORE1 | 348.39 | 56.3 | 1984.726 | 5.697 | 35.284 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1984.726 |
3 | SMSTORE1_LIGHTS | LTG_SCH_BASE_SMALL_LPD1 | SMSTORE1 | 174.19 | 28.1 | 1693.257 | 9.721 | 60.206 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1693.257 |
4 | SMSTORE1_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | SMSTORE1 | 174.19 | 28.1 | 1492.567 | 8.568 | 53.070 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1492.567 |
5 | SMSTORE2_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE2 | 174.19 | 28.1 | 1689.582 | 9.699 | 60.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1689.582 |
6 | SMSTORE2_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE2 | 174.19 | 28.1 | 1211.319 | 6.954 | 43.070 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1211.319 |
7 | SMSTORE3_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE3 | 174.19 | 28.1 | 1689.582 | 9.699 | 60.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1689.582 |
8 | SMSTORE3_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE3 | 174.19 | 28.1 | 1211.319 | 6.954 | 43.070 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1211.319 |
9 | SMSTORE4_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE4 | 174.19 | 28.1 | 1689.582 | 9.699 | 60.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1689.582 |
10 | SMSTORE4_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE4 | 174.19 | 28.1 | 1211.319 | 6.954 | 43.070 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1211.319 |
11 | LGSTORE2_LIGHTS | LTG_SCH_BASE_LPD2 | LGSTORE2 | 348.39 | 56.3 | 3338.998 | 9.584 | 59.359 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3338.998 |
12 | LGSTORE2_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | LGSTORE2 | 348.39 | 56.3 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
13 | SMSTORE5_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE5 | 174.19 | 28.1 | 1689.582 | 9.699 | 60.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1689.582 |
14 | SMSTORE5_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE5 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
15 | SMSTORE6_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE6 | 174.19 | 28.1 | 1689.582 | 9.699 | 60.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1689.582 |
16 | SMSTORE6_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE6 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
17 | SMSTORE7_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE7 | 174.19 | 28.1 | 1689.582 | 9.699 | 60.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1689.582 |
18 | SMSTORE7_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE7 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
19 | SMSTORE8_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE8 | 174.19 | 28.1 | 1689.582 | 9.699 | 60.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1689.582 |
20 | SMSTORE8_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE8 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LGSTORE1_MISCPLUG_EQUIP | TYPE1_EQUIP_SCH | LGSTORE1 | 348.39 | 56.3 | 1498.062 | 4.300 | 26.632 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1498.062 |
2 | SMSTORE1_MISCPLUG_EQUIP | TYPE1_EQUIP_SCH | SMSTORE1 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
3 | SMSTORE2_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE2 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
4 | SMSTORE3_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE3 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
5 | SMSTORE4_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE4 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
6 | LGSTORE2_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | LGSTORE2 | 348.39 | 56.3 | 1498.062 | 4.300 | 26.632 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1498.062 |
7 | SMSTORE5_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE5 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
8 | SMSTORE6_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE6 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
9 | SMSTORE7_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE7 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
10 | SMSTORE8_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE8 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.2284 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
5 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 0.6887 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
6 | LGSTORE1_FLOOR_FFACTOR | 36 | 2 | 7 | 0.167 | 0.1995 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
7 | SMSTORE1_FLOOR_FFACTOR | 37 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
8 | SMSTORE2_FLOOR_FFACTOR | 38 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | SMSTORE3_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
10 | SMSTORE4_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
11 | LGSTORE2_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | SMSTORE5_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | SMSTORE6_FLOOR_FFACTOR | 43 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | SMSTORE7_FLOOR_FFACTOR | 44 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | SMSTORE8_FLOOR_FFACTOR | 45 | 2 | 7 | 0.167 | 0.2888 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
6 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
7 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
8 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
10 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.218 |
11 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
12 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.937 |
13 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
14 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
15 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
16 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
17 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
18 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
19 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
20 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
21 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
22 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
23 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
24 | ~FC_Insulation_7 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_8 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_9 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_10 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.386 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
14 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
15 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
16 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
17 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
18 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
19 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
20 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
21 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
22 | 7 | -0.33074266E-12 | 0.10604805E-14 | -0.10376772E-12 | 0.10050050E-15 |
23 | 6 | 0.29711555E-07 | 0.19576406E-09 | 0.67975929E-08 | -0.14079383E-12 |
24 | 5 | -0.19537397E-03 | 0.16642354E-05 | -0.10041974E-03 | 0.67165186E-08 |
25 | 4 | 0.29828781 | 0.80514357E-03 | 0.10189302 | -0.34439683E-04 |
26 | 3 | -7.3878975 | 0.24810408E-01 | -2.3749899 | 0.29604922E-01 |
27 | 2 | 41.272027 | 0.87780140E-01 | 15.412956 | -0.33780550 |
28 | 1 | -80.852930 | 0.39442104E-01 | -29.274215 | 1.0851646 |
29 | 0 | 46.824337 | 0.79011109E-03 | 16.288086 | |
30 | 7 | -0.21163652E-08 | -0.68723841E-15 | 0.43910983E-14 | -0.57684426E-16 |
31 | 6 | 0.56109385E-05 | 0.38186281E-08 | 0.31898696E-02 | -0.26759299E-04 |
32 | 5 | -0.40164657E-03 | 0.22608617E-05 | -0.22372456 | 0.19561502E-02 |
33 | 4 | 0.92272104E-02 | 0.10289840E-03 | 4.8295456 | -0.45264980E-01 |
34 | 3 | -0.80993241E-01 | 0.81813938E-03 | -38.021416 | 0.39865375 |
35 | 2 | 0.28754352 | 0.13608947E-02 | 116.48395 | -1.4179393 |
36 | 1 | -0.41499682 | 0.41453381E-03 | -143.90731 | 2.0490399 |
37 | 0 | 0.20232414 | 0.10048102E-04 | 60.838472 | |
38 | 7 | -0.37862368E-08 | -0.38757603E-14 | 0.11479940E-14 | -0.41635801E-16 |
39 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
40 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
41 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
42 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
43 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
44 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
45 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
46 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479937E-14 | -0.41635796E-16 |
47 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
48 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
49 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
50 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
51 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
52 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
53 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
54 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479940E-14 | -0.41635801E-16 |
55 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
56 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
57 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
58 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
59 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
60 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
61 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
62 | 7 | -0.37862368E-08 | -0.38757603E-14 | 0.11479940E-14 | -0.41635801E-16 |
63 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
64 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
65 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
66 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
67 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
68 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
69 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
70 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479937E-14 | -0.41635796E-16 |
71 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
72 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
73 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
74 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
75 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
76 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
77 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
78 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479937E-14 | -0.41635796E-16 |
79 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
80 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
81 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
82 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
83 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
84 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
85 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
86 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479940E-14 | -0.41635801E-16 |
87 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
88 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
89 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
90 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
91 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
92 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
93 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
94 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479936E-14 | -0.41635794E-16 |
95 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
96 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
97 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
98 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
99 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
100 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
101 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
102 | 7 | -0.14484255E-08 | -0.22640907E-15 | 0.11860658E-13 | -0.17473455E-15 |
103 | 6 | 0.80640390E-05 | 0.55493782E-08 | 0.31828288E-02 | -0.26700235E-04 |
104 | 5 | -0.58275339E-03 | 0.32892043E-05 | -0.22332434 | 0.19526176E-02 |
105 | 4 | 0.13421983E-01 | 0.14977251E-03 | 4.8228790 | -0.45200897E-01 |
106 | 3 | -0.11791368 | 0.11914425E-02 | -37.983753 | 0.39823745 |
107 | 2 | 0.41875064 | 0.19825898E-02 | 116.41064 | -1.4169588 |
108 | 1 | -0.60444169 | 0.60433957E-03 | -143.86415 | 2.0483306 |
109 | 0 | 0.29470347 | 0.14596444E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.423_SHGC_0.25 | 35 | 1 | VerySmooth | 2.404 | 2.404 | 1.000 | 0.251 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 2.99333E-002 | 0.16139 | 0.62046 | 0.62046 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 0.12244 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | GAS TANK1 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
2 | WaterHeater:Mixed | GAS TANK2 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
3 | WaterHeater:Mixed | GAS TANK3 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
4 | WaterHeater:Mixed | GAS TANK4 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
5 | WaterHeater:Mixed | GAS TANK5 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
6 | WaterHeater:Mixed | GAS TANK6 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
7 | WaterHeater:Mixed | GAS TANK7 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | LGSTORE1_WALL_2 | 0 | 118.41 | 56.08 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
2 | LGSTORE1_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
3 | LGSTORE1_WALL_3_DOOR_1 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
4 | LGSTORE1_WALL_3_DOOR_2 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
5 | LGSTORE1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
6 | LGSTORE1_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
7 | LGSTORE1_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
8 | LGSTORE1_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
9 | LGSTORE1_WALL_1_WINDOW_3 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
10 | LGSTORE1_WALL_1_WINDOW_4 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
11 | LGSTORE1_WALL_1_DOOR_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 1 | No | No |
12 | LGSTORE1_WALL_1_DOOR_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 1 | No | No |
13 | LGSTORE1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
14 | LGSTORE1_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
15 | LGSTORE1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
16 | SMSTORE1_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
17 | SMSTORE1_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
18 | SMSTORE1_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
19 | SMSTORE1_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
20 | SMSTORE1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
21 | SMSTORE1_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
22 | SMSTORE1_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
23 | SMSTORE1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
24 | SMSTORE1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
25 | SMSTORE1_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
26 | SMSTORE1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
27 | SMSTORE2_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
28 | SMSTORE2_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
29 | SMSTORE2_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
30 | SMSTORE2_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
31 | SMSTORE2_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
32 | SMSTORE2_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
33 | SMSTORE2_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
34 | SMSTORE2_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
35 | SMSTORE2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
36 | SMSTORE2_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
37 | SMSTORE2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
38 | SMSTORE3_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
39 | SMSTORE3_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
40 | SMSTORE3_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
41 | SMSTORE3_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
42 | SMSTORE3_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
43 | SMSTORE3_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
44 | SMSTORE3_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
45 | SMSTORE3_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
46 | SMSTORE3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
47 | SMSTORE3_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
48 | SMSTORE3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
49 | SMSTORE4_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
50 | SMSTORE4_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
51 | SMSTORE4_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
52 | SMSTORE4_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
53 | SMSTORE4_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
54 | SMSTORE4_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 3 | No | No |
55 | SMSTORE4_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
56 | SMSTORE4_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
57 | SMSTORE4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
58 | SMSTORE4_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
59 | SMSTORE4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
60 | LGSTORE2_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
61 | LGSTORE2_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 4 | No | No |
62 | LGSTORE2_WALL_3_DOOR_1 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
63 | LGSTORE2_WALL_3_DOOR_2 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
64 | LGSTORE2_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
65 | LGSTORE2_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 4 | No | No |
66 | LGSTORE2_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
67 | LGSTORE2_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
68 | LGSTORE2_WALL_1_WINDOW_3 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
69 | LGSTORE2_WALL_1_WINDOW_4 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
70 | LGSTORE2_WALL_1_DOOR_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
71 | LGSTORE2_WALL_1_DOOR_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
72 | LGSTORE2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
73 | LGSTORE2_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
74 | LGSTORE2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
75 | SMSTORE5_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
76 | SMSTORE5_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
77 | SMSTORE5_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
78 | SMSTORE5_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
79 | SMSTORE5_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
80 | SMSTORE5_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
81 | SMSTORE5_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
82 | SMSTORE5_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
83 | SMSTORE5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
84 | SMSTORE5_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
85 | SMSTORE5_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
86 | SMSTORE6_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
87 | SMSTORE6_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
88 | SMSTORE6_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
89 | SMSTORE6_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
90 | SMSTORE6_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
91 | SMSTORE6_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
92 | SMSTORE6_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
93 | SMSTORE6_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
94 | SMSTORE6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
95 | SMSTORE6_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
96 | SMSTORE6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
97 | SMSTORE7_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
98 | SMSTORE7_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
99 | SMSTORE7_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
100 | SMSTORE7_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
101 | SMSTORE7_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
102 | SMSTORE7_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 3 | No | No |
103 | SMSTORE7_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
104 | SMSTORE7_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
105 | SMSTORE7_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
106 | SMSTORE7_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
107 | SMSTORE7_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
108 | SMSTORE8_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 4 | No | No |
109 | SMSTORE8_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 2 | No | No |
110 | SMSTORE8_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 2 | No | No |
111 | SMSTORE8_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 1 | No | No |
112 | SMSTORE8_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
113 | SMSTORE8_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 3 | No | No |
114 | SMSTORE8_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
115 | SMSTORE8_WALL_4 | 0 | 118.41 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 3 | No | No |
116 | SMSTORE8_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
117 | SMSTORE8_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
118 | SMSTORE8_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | LGSTORE1_INFILTRATION | TYPE1_INFIL_SCH | LGSTORE1 | 348.39 | 56.3 | 0.157 | 4.517E-004 | 2.488E-004 | 0.314 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | LGSTORE1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LGSTORE1 | 348.39 | 56.3 | 0.241 | 6.922E-004 | 3.813E-004 | 0.481 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | SMSTORE1_INFILTRATION | TYPE1_INFIL_SCH | SMSTORE1 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | SMSTORE1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE1 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | SMSTORE2_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE2 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | SMSTORE2_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE2 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | SMSTORE3_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE3 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | SMSTORE3_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE3 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | SMSTORE4_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE4 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | SMSTORE4_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE4 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | LGSTORE2_INFILTRATION | TYPE3_INFIL_SCH | LGSTORE2 | 348.39 | 56.3 | 8.993E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | LGSTORE2_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LGSTORE2 | 348.39 | 56.3 | 0.241 | 6.922E-004 | 4.692E-004 | 0.481 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | SMSTORE5_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE5 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | SMSTORE5_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE5 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | SMSTORE6_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE6 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | SMSTORE6_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE6 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | SMSTORE7_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE7 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
18 | SMSTORE7_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE7 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | SMSTORE8_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE8 | 174.19 | 28.1 | 0.112 | 6.453E-004 | 2.994E-004 | 0.448 | 0.000 | 0.000 | 0.224 | 0.000 |
20 | SMSTORE8_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE8 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 3.583E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | LGSTORE1 | Mixing/Well-Stirred |
2 | SMSTORE1 | Mixing/Well-Stirred |
3 | SMSTORE2 | Mixing/Well-Stirred |
4 | SMSTORE3 | Mixing/Well-Stirred |
5 | SMSTORE4 | Mixing/Well-Stirred |
6 | LGSTORE2 | Mixing/Well-Stirred |
7 | SMSTORE5 | Mixing/Well-Stirred |
8 | SMSTORE6 | Mixing/Well-Stirred |
9 | SMSTORE7 | Mixing/Well-Stirred |
10 | SMSTORE8 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone LGSTORE1 | 1.2000 |
3 | Zone SMSTORE1 | 1.2000 |
4 | Zone SMSTORE2 | 1.2000 |
5 | Zone SMSTORE3 | 1.2000 |
6 | Zone SMSTORE4 | 1.2000 |
7 | Zone LGSTORE2 | 1.2000 |
8 | Zone SMSTORE5 | 1.2000 |
9 | Zone SMSTORE6 | 1.2000 |
10 | Zone SMSTORE7 | 1.2000 |
11 | Zone SMSTORE8 | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone LGSTORE1 | 1.2000 |
3 | Zone SMSTORE1 | 1.2000 |
4 | Zone SMSTORE2 | 1.2000 |
5 | Zone SMSTORE3 | 1.2000 |
6 | Zone SMSTORE4 | 1.2000 |
7 | Zone LGSTORE2 | 1.2000 |
8 | Zone SMSTORE5 | 1.2000 |
9 | Zone SMSTORE6 | 1.2000 |
10 | Zone SMSTORE7 | 1.2000 |
11 | Zone SMSTORE8 | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | LGSTORE1 | Cooling | 23509.22549 | 28211.07059 | 1.99463 | 2.39356 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 38.10000 | 6.87148E-003 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
2 | LGSTORE1 | Heating | 18523.75936 | 22228.51123 | 0.92072 | 1.10486 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -5.20000 | 2.80840E-003 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
3 | SMSTORE1 | Cooling | 12277.26330 | 14732.71596 | 1.04165 | 1.24998 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 37.99167 | 6.87130E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
4 | SMSTORE1 | Heating | 8704.09977 | 10444.91972 | 0.43264 | 0.51916 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -5.20000 | 2.80840E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
5 | SMSTORE2 | Cooling | 12920.44854 | 15504.53825 | 1.07078 | 1.28494 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 30.95000 | 6.86012E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
6 | SMSTORE2 | Heating | 8824.10636 | 10588.92764 | 0.43860 | 0.52632 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -5.20000 | 2.80840E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
7 | SMSTORE3 | Cooling | 12850.70503 | 15420.84603 | 1.06484 | 1.27781 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 30.95000 | 6.86012E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
8 | SMSTORE3 | Heating | 8925.29928 | 10710.35914 | 0.44363 | 0.53236 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -5.20000 | 2.80840E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
9 | SMSTORE4 | Cooling | 12834.29753 | 15401.15703 | 1.06355 | 1.27625 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 30.95000 | 6.86012E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
10 | SMSTORE4 | Heating | 9102.61381 | 10923.13657 | 0.45244 | 0.54293 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -5.20000 | 2.80840E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
11 | LGSTORE2 | Cooling | 21559.06874 | 25870.88249 | 1.82918 | 2.19502 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 37.88333 | 6.87114E-003 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
12 | LGSTORE2 | Heating | 17731.04957 | 21277.25948 | 0.88132 | 1.05759 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -5.20000 | 2.80840E-003 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
13 | SMSTORE5 | Cooling | 11217.06127 | 13460.47352 | 0.95170 | 1.14204 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 37.88333 | 6.87114E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
14 | SMSTORE5 | Heating | 9415.64011 | 11298.76813 | 0.46800 | 0.56160 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -5.20000 | 2.80840E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
15 | SMSTORE6 | Cooling | 11165.20726 | 13398.24871 | 0.94730 | 1.13676 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 37.88333 | 6.87114E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
16 | SMSTORE6 | Heating | 9412.83424 | 11295.40109 | 0.46786 | 0.56144 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -5.20000 | 2.80840E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
17 | SMSTORE7 | Cooling | 11181.41756 | 13417.70107 | 0.94868 | 1.13841 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 37.88333 | 6.87114E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
18 | SMSTORE7 | Heating | 9680.33227 | 11616.39872 | 0.48116 | 0.57739 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -5.20000 | 2.80840E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
19 | SMSTORE8 | Cooling | 12720.17356 | 15264.20828 | 1.07925 | 1.29510 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | 37.45000 | 6.87043E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
20 | SMSTORE8 | Heating | 11681.26770 | 14017.52124 | 0.58060 | 0.69672 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -5.20000 | 2.80840E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC_1:1 | Cooling | Sensible | 33987.80 | 2.39356 | 2.39356 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-AC_1:1 | Heating | Sensible | 33264.56 | 1.10486 | 1.10486 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
3 | PSZ-AC_2:2 | Cooling | Sensible | 17610.76 | 1.24998 | 1.24998 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-AC_2:2 | Heating | Sensible | 15972.71 | 0.51916 | 0.51916 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
5 | PSZ-AC_3:3 | Cooling | Sensible | 17642.74 | 1.28494 | 1.28494 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
6 | PSZ-AC_3:3 | Heating | Sensible | 16114.62 | 0.52632 | 0.52632 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
7 | PSZ-AC_4:4 | Cooling | Sensible | 17684.95 | 1.27781 | 1.27781 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
8 | PSZ-AC_4:4 | Heating | Sensible | 16234.28 | 0.53236 | 0.53236 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
9 | PSZ-AC_5:5 | Cooling | Sensible | 17556.57 | 1.27625 | 1.27625 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
10 | PSZ-AC_5:5 | Heating | Sensible | 16443.96 | 0.54293 | 0.54293 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
11 | PSZ-AC_6:6 | Cooling | Sensible | 31661.90 | 2.19502 | 2.19502 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
12 | PSZ-AC_6:6 | Heating | Sensible | 32327.26 | 1.05759 | 1.05759 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
13 | PSZ-AC_7:7 | Cooling | Sensible | 16345.99 | 1.14204 | 1.14204 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
14 | PSZ-AC_7:7 | Heating | Sensible | 16814.12 | 0.56160 | 0.56160 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
15 | PSZ-AC_8:8 | Cooling | Sensible | 16284.45 | 1.13676 | 1.13676 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
16 | PSZ-AC_8:8 | Heating | Sensible | 16810.80 | 0.56144 | 0.56144 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
17 | PSZ-AC_9:9 | Cooling | Sensible | 16301.88 | 1.13841 | 1.13841 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
18 | PSZ-AC_9:9 | Heating | Sensible | 17127.13 | 0.57739 | 0.57739 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
19 | PSZ-AC_10:10 | Cooling | Sensible | 17997.46 | 1.29510 | 1.29510 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
20 | PSZ-AC_10:10 | Heating | Sensible | 19493.19 | 0.69672 | 0.69672 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | LGSTORE1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.39356 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.24998 |
3 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.28494 |
4 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.27781 |
5 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE4 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.27625 |
6 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | LGSTORE2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.19502 |
7 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE5 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.14204 |
8 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.13676 |
9 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE7 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.13841 |
10 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE8 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.29510 |
11 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.39356 |
12 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.39356 |
13 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.39356 |
14 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 2.39356 |
15 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.39356 |
16 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Main Design Air Flow Rate [m3/s] | 2.39356 |
17 | AirLoopHVAC | PSZ-AC_1:1 | User Heating Air Flow Ratio [] | 1.00000 |
18 | AirLoopHVAC | PSZ-AC_1:1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
19 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.24998 |
20 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.24998 |
21 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.24998 |
22 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.24998 |
23 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.24998 |
24 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Main Design Air Flow Rate [m3/s] | 1.24998 |
25 | AirLoopHVAC | PSZ-AC_2:2 | User Heating Air Flow Ratio [] | 1.00000 |
26 | AirLoopHVAC | PSZ-AC_2:2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
27 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.28494 |
28 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.28494 |
29 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.28494 |
30 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.28494 |
31 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.28494 |
32 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Main Design Air Flow Rate [m3/s] | 1.28494 |
33 | AirLoopHVAC | PSZ-AC_3:3 | User Heating Air Flow Ratio [] | 1.00000 |
34 | AirLoopHVAC | PSZ-AC_3:3 | Calculated Heating Air Flow Ratio [] | 1.00000 |
35 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.27781 |
36 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.27781 |
37 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.27781 |
38 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.27781 |
39 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.27781 |
40 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Main Design Air Flow Rate [m3/s] | 1.27781 |
41 | AirLoopHVAC | PSZ-AC_4:4 | User Heating Air Flow Ratio [] | 1.00000 |
42 | AirLoopHVAC | PSZ-AC_4:4 | Calculated Heating Air Flow Ratio [] | 1.00000 |
43 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.27625 |
44 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.27625 |
45 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.27625 |
46 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.27625 |
47 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.27625 |
48 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Main Design Air Flow Rate [m3/s] | 1.27625 |
49 | AirLoopHVAC | PSZ-AC_5:5 | User Heating Air Flow Ratio [] | 1.00000 |
50 | AirLoopHVAC | PSZ-AC_5:5 | Calculated Heating Air Flow Ratio [] | 1.00000 |
51 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.19502 |
52 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.19502 |
53 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.19502 |
54 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Heating Design Air Flow Rate [m3/s] | 2.19502 |
55 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.19502 |
56 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Main Design Air Flow Rate [m3/s] | 2.19502 |
57 | AirLoopHVAC | PSZ-AC_6:6 | User Heating Air Flow Ratio [] | 1.00000 |
58 | AirLoopHVAC | PSZ-AC_6:6 | Calculated Heating Air Flow Ratio [] | 1.00000 |
59 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.14204 |
60 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.14204 |
61 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.14204 |
62 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.14204 |
63 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.14204 |
64 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Main Design Air Flow Rate [m3/s] | 1.14204 |
65 | AirLoopHVAC | PSZ-AC_7:7 | User Heating Air Flow Ratio [] | 1.00000 |
66 | AirLoopHVAC | PSZ-AC_7:7 | Calculated Heating Air Flow Ratio [] | 1.00000 |
67 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.13676 |
68 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.13676 |
69 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.13676 |
70 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.13676 |
71 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.13676 |
72 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Main Design Air Flow Rate [m3/s] | 1.13676 |
73 | AirLoopHVAC | PSZ-AC_8:8 | User Heating Air Flow Ratio [] | 1.00000 |
74 | AirLoopHVAC | PSZ-AC_8:8 | Calculated Heating Air Flow Ratio [] | 1.00000 |
75 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.13841 |
76 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.13841 |
77 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.13841 |
78 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.13841 |
79 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.13841 |
80 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Main Design Air Flow Rate [m3/s] | 1.13841 |
81 | AirLoopHVAC | PSZ-AC_9:9 | User Heating Air Flow Ratio [] | 1.00000 |
82 | AirLoopHVAC | PSZ-AC_9:9 | Calculated Heating Air Flow Ratio [] | 1.00000 |
83 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.29510 |
84 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.29510 |
85 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.29510 |
86 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.29510 |
87 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.29510 |
88 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Main Design Air Flow Rate [m3/s] | 1.29510 |
89 | AirLoopHVAC | PSZ-AC_10:10 | User Heating Air Flow Ratio [] | 1.00000 |
90 | AirLoopHVAC | PSZ-AC_10:10 | Calculated Heating Air Flow Ratio [] | 1.00000 |
91 | AirLoopHVAC | PSZ-AC_1:1 | Design Supply Air Flow Rate [m3/s] | 2.39356 |
92 | AirLoopHVAC | PSZ-AC_2:2 | Design Supply Air Flow Rate [m3/s] | 1.24998 |
93 | AirLoopHVAC | PSZ-AC_3:3 | Design Supply Air Flow Rate [m3/s] | 1.28494 |
94 | AirLoopHVAC | PSZ-AC_4:4 | Design Supply Air Flow Rate [m3/s] | 1.27781 |
95 | AirLoopHVAC | PSZ-AC_5:5 | Design Supply Air Flow Rate [m3/s] | 1.27625 |
96 | AirLoopHVAC | PSZ-AC_6:6 | Design Supply Air Flow Rate [m3/s] | 2.19502 |
97 | AirLoopHVAC | PSZ-AC_7:7 | Design Supply Air Flow Rate [m3/s] | 1.14204 |
98 | AirLoopHVAC | PSZ-AC_8:8 | Design Supply Air Flow Rate [m3/s] | 1.13676 |
99 | AirLoopHVAC | PSZ-AC_9:9 | Design Supply Air Flow Rate [m3/s] | 1.13841 |
100 | AirLoopHVAC | PSZ-AC_10:10 | Design Supply Air Flow Rate [m3/s] | 1.29510 |
101 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.39356 |
102 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41148 |
103 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.39356 |
104 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 2561.22222 |
105 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.39356 |
106 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.39356 |
107 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.39356 |
108 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.57975 |
109 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.39356 |
110 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.19678 |
111 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.59571 |
112 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 45276.41000 |
113 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 22638.20500 |
114 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.79874 |
115 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.79874 |
116 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 45276.41000 |
117 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 58814.13001 |
118 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
119 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
120 | Coil:Heating:Fuel | PSZ-AC_1:1 HEATING COIL | Design Size Nominal Capacity [W] | 58814.13001 |
121 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.24998 |
122 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
123 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.24998 |
124 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1383.93032 |
125 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.24998 |
126 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.24998 |
127 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.24998 |
128 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.82499 |
129 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.24998 |
130 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.62499 |
131 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.83332 |
132 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 23485.02000 |
133 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 11742.51000 |
134 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80093 |
135 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80093 |
136 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 23485.02000 |
137 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 30461.80320 |
138 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
139 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
140 | Coil:Heating:Fuel | PSZ-AC_2:2 HEATING COIL | Design Size Nominal Capacity [W] | 30461.80320 |
141 | Controller:OutdoorAir | PSZ-AC_3:3_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.28494 |
142 | Controller:OutdoorAir | PSZ-AC_3:3_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
143 | Fan:SystemModel | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.28494 |
144 | Fan:SystemModel | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1422.62808 |
145 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.28494 |
146 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.28494 |
147 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.28494 |
148 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.84806 |
149 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.28494 |
150 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.64247 |
151 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.85663 |
152 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 24133.95000 |
153 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 12066.97500 |
154 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80003 |
155 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80003 |
156 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 24133.95000 |
157 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 31154.76250 |
158 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
159 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
160 | Coil:Heating:Fuel | PSZ-AC_3:3 HEATING COIL | Design Size Nominal Capacity [W] | 31154.76250 |
161 | Controller:OutdoorAir | PSZ-AC_4:4_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.27781 |
162 | Controller:OutdoorAir | PSZ-AC_4:4_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
163 | Fan:SystemModel | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.27781 |
164 | Fan:SystemModel | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1414.74026 |
165 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.27781 |
166 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.27781 |
167 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.27781 |
168 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.84336 |
169 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.27781 |
170 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.63891 |
171 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.85187 |
172 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 23989.93000 |
173 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 11994.96500 |
174 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80017 |
175 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80017 |
176 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 23989.93000 |
177 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 31013.51739 |
178 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
179 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
180 | Coil:Heating:Fuel | PSZ-AC_4:4 HEATING COIL | Design Size Nominal Capacity [W] | 31013.51739 |
181 | Controller:OutdoorAir | PSZ-AC_5:5_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.27625 |
182 | Controller:OutdoorAir | PSZ-AC_5:5_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
183 | Fan:SystemModel | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.27625 |
184 | Fan:SystemModel | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1413.01656 |
185 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.27625 |
186 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.27625 |
187 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.27625 |
188 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.84233 |
189 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.27625 |
190 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.63813 |
191 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.85083 |
192 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 23991.93000 |
193 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 11995.96500 |
194 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80075 |
195 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80075 |
196 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 23991.93000 |
197 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 30982.64877 |
198 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
199 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
200 | Coil:Heating:Fuel | PSZ-AC_5:5 HEATING COIL | Design Size Nominal Capacity [W] | 30982.64877 |
201 | Controller:OutdoorAir | PSZ-AC_6:6_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.19502 |
202 | Controller:OutdoorAir | PSZ-AC_6:6_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41148 |
203 | Fan:SystemModel | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.19502 |
204 | Fan:SystemModel | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 2348.77322 |
205 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.19502 |
206 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.19502 |
207 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.19502 |
208 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.44871 |
209 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.19502 |
210 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.09751 |
211 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.46335 |
212 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 42109.61000 |
213 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 21054.80500 |
214 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.79324 |
215 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.79324 |
216 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 42109.61000 |
217 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 54877.46218 |
218 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
219 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
220 | Coil:Heating:Fuel | PSZ-AC_6:6 HEATING COIL | Design Size Nominal Capacity [W] | 54877.46218 |
221 | Controller:OutdoorAir | PSZ-AC_7:7_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.14204 |
222 | Controller:OutdoorAir | PSZ-AC_7:7_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
223 | Fan:SystemModel | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.14204 |
224 | Fan:SystemModel | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1264.42398 |
225 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.14204 |
226 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.14204 |
227 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.14204 |
228 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.75375 |
229 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.14204 |
230 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.57102 |
231 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.76136 |
232 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 21755.53000 |
233 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 10877.76500 |
234 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.79648 |
235 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.79648 |
236 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 21755.53000 |
237 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 28321.81184 |
238 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
239 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
240 | Coil:Heating:Fuel | PSZ-AC_7:7 HEATING COIL | Design Size Nominal Capacity [W] | 28321.81184 |
241 | Controller:OutdoorAir | PSZ-AC_8:8_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.13676 |
242 | Controller:OutdoorAir | PSZ-AC_8:8_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
243 | Fan:SystemModel | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.13676 |
244 | Fan:SystemModel | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1258.57891 |
245 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.13676 |
246 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.13676 |
247 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.13676 |
248 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.75026 |
249 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.13676 |
250 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.56838 |
251 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.75784 |
252 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 21670.67000 |
253 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 10835.33500 |
254 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.79525 |
255 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.79525 |
256 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 21670.67000 |
257 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 28217.14416 |
258 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
259 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
260 | Coil:Heating:Fuel | PSZ-AC_8:8 HEATING COIL | Design Size Nominal Capacity [W] | 28217.14416 |
261 | Controller:OutdoorAir | PSZ-AC_9:9_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.13841 |
262 | Controller:OutdoorAir | PSZ-AC_9:9_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
263 | Fan:SystemModel | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.13841 |
264 | Fan:SystemModel | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1260.40600 |
265 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.13841 |
266 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.13841 |
267 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.13841 |
268 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.75135 |
269 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.13841 |
270 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.56921 |
271 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.75894 |
272 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 21697.67000 |
273 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 10848.83500 |
274 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.79532 |
275 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.79532 |
276 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 21697.67000 |
277 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 28249.86386 |
278 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
279 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
280 | Coil:Heating:Fuel | PSZ-AC_9:9 HEATING COIL | Design Size Nominal Capacity [W] | 28249.86386 |
281 | Controller:OutdoorAir | PSZ-AC_10:10_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.29510 |
282 | Controller:OutdoorAir | PSZ-AC_10:10_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
283 | Fan:SystemModel | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.29510 |
284 | Fan:SystemModel | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1433.87958 |
285 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.29510 |
286 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.29510 |
287 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.29510 |
288 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.85476 |
289 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.29510 |
290 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.64755 |
291 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.86340 |
292 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 23853.43000 |
293 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 11926.71500 |
294 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80043 |
295 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80043 |
296 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 23853.43000 |
297 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 31356.70879 |
298 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
299 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
300 | Coil:Heating:Fuel | PSZ-AC_10:10 HEATING COIL | Design Size Nominal Capacity [W] | 31356.70879 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | 43397.0 | 11.25 | 11.25 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | 22503.6 | 11.40 | 11.40 | |||
3 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | 23125.1 | 11.40 | 11.40 | |||
4 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | 22986.7 | 11.39 | 11.39 | |||
5 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | 22989.9 | 11.40 | 11.40 | |||
6 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | 40385.7 | 11.28 | 11.28 | |||
7 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | 20858.7 | 11.43 | 11.43 | |||
8 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | 20778.0 | 11.43 | 11.43 | |||
9 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | 20803.7 | 11.43 | 11.43 | |||
10 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | 22836.9 | 11.35 | 11.35 |
Zone Name | # Surfaces | |
1 | LGSTORE1 | 15 |
2 | SMSTORE1 | 11 |
3 | SMSTORE2 | 11 |
4 | SMSTORE3 | 11 |
5 | SMSTORE4 | 11 |
6 | LGSTORE2 | 15 |
7 | SMSTORE5 | 11 |
8 | SMSTORE6 | 11 |
9 | SMSTORE7 | 11 |
10 | SMSTORE8 | 11 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | LGSTORE1_WALL_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.689 | 0.624 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | LGSTORE1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.689 | 0.624 | 71.15 | 78.94 | 71.15 | 0.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | LGSTORE1_WALL_3_DOOR_1 | Door | LGSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
4 | LGSTORE1_WALL_3_DOOR_2 | Door | LGSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
5 | LGSTORE1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
6 | LGSTORE1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.689 | 0.624 | 58.18 | 78.94 | 58.18 | 180.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
7 | LGSTORE1_WALL_1_WINDOW_1 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.423_SHGC_0.25 | N/A | 2.404 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
8 | LGSTORE1_WALL_1_WINDOW_2 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.423_SHGC_0.25 | N/A | 2.404 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
9 | LGSTORE1_WALL_1_WINDOW_3 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.423_SHGC_0.25 | N/A | 2.404 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
10 | LGSTORE1_WALL_1_WINDOW_4 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.423_SHGC_0.25 | N/A | 2.404 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
11 | LGSTORE1_WALL_1_DOOR_1 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.423_SHGC_0.25 | N/A | 2.404 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
12 | LGSTORE1_WALL_1_DOOR_2 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.423_SHGC_0.25 | N/A | 2.404 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
13 | LGSTORE1_FLOOR | Floor | CTF - ConductionTransferFunction | LGSTORE1_FLOOR_FFACTOR | 0.199 | 0.190 | 348.39 | 348.39 | 348.39 | 270.00 | 180.00 | 22.86 | 15.24 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | LGSTORE1_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 348.39 | 348.39 | 348.39 | 270.00 | 0.00 | 22.86 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
15 | LGSTORE1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 696.77 | 696.77 | 696.77 | 0.00 | 90.00 | 696.77 | 1.00 | 0.00 | LGSTORE1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
16 | SMSTORE1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.689 | 0.624 | 29.09 | 39.47 | 29.09 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
17 | SMSTORE1_WALL_1_WINDOW_1 | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.423_SHGC_0.25 | N/A | 2.404 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
18 | SMSTORE1_WALL_1_WINDOW_2 | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.423_SHGC_0.25 | N/A | 2.404 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
19 | SMSTORE1_WALL_1_DOOR | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.423_SHGC_0.25 | N/A | 2.404 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
20 | SMSTORE1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | SMSTORE1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.689 | 0.624 | 35.57 | 39.47 | 35.57 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | SMSTORE1_WALL_3_DOOR | Door | SMSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
23 | SMSTORE1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE2_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | SMSTORE1_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE1_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | SMSTORE1_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
26 | SMSTORE1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
27 | SMSTORE2_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.689 | 0.624 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | SMSTORE2_WALL_1_WINDOW_1 | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.423_SHGC_0.25 | N/A | 2.404 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
29 | SMSTORE2_WALL_1_WINDOW_2 | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.423_SHGC_0.25 | N/A | 2.404 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
30 | SMSTORE2_WALL_1_DOOR | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.423_SHGC_0.25 | N/A | 2.404 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
31 | SMSTORE2_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | SMSTORE2_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.689 | 0.624 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | SMSTORE2_WALL_3_DOOR | Door | SMSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
34 | SMSTORE2_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE3_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | SMSTORE2_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE2_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | SMSTORE2_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | SMSTORE2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | SMSTORE3_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.689 | 0.624 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | SMSTORE3_WALL_1_WINDOW_1 | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.423_SHGC_0.25 | N/A | 2.404 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
40 | SMSTORE3_WALL_1_WINDOW_2 | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.423_SHGC_0.25 | N/A | 2.404 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
41 | SMSTORE3_WALL_1_DOOR | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.423_SHGC_0.25 | N/A | 2.404 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
42 | SMSTORE3_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE2_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | SMSTORE3_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.689 | 0.624 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | SMSTORE3_WALL_3_DOOR | Door | SMSTORE3_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
45 | SMSTORE3_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE4_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | SMSTORE3_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE3_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
47 | SMSTORE3_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
48 | SMSTORE3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
49 | SMSTORE4_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.689 | 0.624 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | SMSTORE4_WALL_1_WINDOW_1 | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.423_SHGC_0.25 | N/A | 2.404 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
51 | SMSTORE4_WALL_1_WINDOW_2 | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.423_SHGC_0.25 | N/A | 2.404 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
52 | SMSTORE4_WALL_1_DOOR | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.423_SHGC_0.25 | N/A | 2.404 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | SMSTORE4_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE3_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | SMSTORE4_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.689 | 0.624 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | SMSTORE4_WALL_3_DOOR | Door | SMSTORE4_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | SMSTORE4_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE2_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | SMSTORE4_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE4_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | SMSTORE4_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | SMSTORE4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | LGSTORE2_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE4_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | LGSTORE2_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.689 | 0.624 | 71.19 | 78.94 | 71.19 | 0.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
62 | LGSTORE2_WALL_3_DOOR_1 | Door | LGSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
63 | LGSTORE2_WALL_3_DOOR_2 | Door | LGSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
64 | LGSTORE2_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE5_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LGSTORE2_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.689 | 0.624 | 58.22 | 78.94 | 58.22 | 180.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
66 | LGSTORE2_WALL_1_WINDOW_1 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.423_SHGC_0.25 | N/A | 2.404 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | LGSTORE2_WALL_1_WINDOW_2 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.423_SHGC_0.25 | N/A | 2.404 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | LGSTORE2_WALL_1_WINDOW_3 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.423_SHGC_0.25 | N/A | 2.404 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | LGSTORE2_WALL_1_WINDOW_4 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.423_SHGC_0.25 | N/A | 2.404 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LGSTORE2_WALL_1_DOOR_1 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.423_SHGC_0.25 | N/A | 2.404 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
71 | LGSTORE2_WALL_1_DOOR_2 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.423_SHGC_0.25 | N/A | 2.404 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
72 | LGSTORE2_FLOOR | Floor | CTF - ConductionTransferFunction | LGSTORE2_FLOOR_FFACTOR | 0.112 | 0.109 | 348.39 | 348.39 | 348.39 | 270.00 | 180.00 | 22.86 | 15.24 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
73 | LGSTORE2_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 348.39 | 348.39 | 348.39 | 270.00 | 0.00 | 22.86 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
74 | LGSTORE2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 696.77 | 696.77 | 696.77 | 0.00 | 90.00 | 696.77 | 1.00 | 0.00 | LGSTORE2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
75 | SMSTORE5_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.689 | 0.624 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | SMSTORE5_WALL_1_WINDOW_1 | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.423_SHGC_0.25 | N/A | 2.404 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
77 | SMSTORE5_WALL_1_WINDOW_2 | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.423_SHGC_0.25 | N/A | 2.404 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | SMSTORE5_WALL_1_DOOR | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.423_SHGC_0.25 | N/A | 2.404 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
79 | SMSTORE5_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE2_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | SMSTORE5_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.689 | 0.624 | 35.59 | 39.47 | 35.59 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | SMSTORE5_WALL_3_DOOR | Door | SMSTORE5_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
82 | SMSTORE5_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE6_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
83 | SMSTORE5_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE5_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
84 | SMSTORE5_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
85 | SMSTORE5_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE5_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | SMSTORE6_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.689 | 0.624 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | SMSTORE6_WALL_1_WINDOW_1 | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.423_SHGC_0.25 | N/A | 2.404 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | SMSTORE6_WALL_1_WINDOW_2 | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.423_SHGC_0.25 | N/A | 2.404 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
89 | SMSTORE6_WALL_1_DOOR | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.423_SHGC_0.25 | N/A | 2.404 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | SMSTORE6_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE5_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | SMSTORE6_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.689 | 0.624 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | SMSTORE6_WALL_3_DOOR | Door | SMSTORE6_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
93 | SMSTORE6_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE7_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | SMSTORE6_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE6_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
95 | SMSTORE6_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
96 | SMSTORE6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
97 | SMSTORE7_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.689 | 0.624 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | SMSTORE7_WALL_1_WINDOW_1 | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.423_SHGC_0.25 | N/A | 2.404 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | SMSTORE7_WALL_1_WINDOW_2 | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.423_SHGC_0.25 | N/A | 2.404 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
100 | SMSTORE7_WALL_1_DOOR | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.423_SHGC_0.25 | N/A | 2.404 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
101 | SMSTORE7_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE6_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
102 | SMSTORE7_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.689 | 0.624 | 35.59 | 39.47 | 35.59 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | SMSTORE7_WALL_3_DOOR | Door | SMSTORE7_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
104 | SMSTORE7_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE8_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | SMSTORE7_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE7_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
106 | SMSTORE7_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
107 | SMSTORE7_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE7_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
108 | SMSTORE8_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.689 | 0.624 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | SMSTORE8_WALL_1_WINDOW_1 | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.423_SHGC_0.25 | N/A | 2.404 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
110 | SMSTORE8_WALL_1_WINDOW_2 | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.423_SHGC_0.25 | N/A | 2.404 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
111 | SMSTORE8_WALL_1_DOOR | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.423_SHGC_0.25 | N/A | 2.404 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
112 | SMSTORE8_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE7_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | SMSTORE8_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.689 | 0.624 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | SMSTORE8_WALL_3_DOOR | Door | SMSTORE8_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
115 | SMSTORE8_WALL_4 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.689 | 0.624 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | SMSTORE8_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE8_FLOOR_FFACTOR | 0.289 | 0.270 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | SMSTORE8_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | SMSTORE8_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE8_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | LGSTORE1 | RunPeriod: RUNPERIOD 1 | 6.5446939875E-002 | 7.3324494307E-002 | Pass | Pass | 4.3972147791E-002 | 0.1892114843 | Pass | Pass |
2 | SMSTORE1 | RunPeriod: RUNPERIOD 1 | 4.6011745190E-002 | 7.8851052509E-002 | Pass | Pass | 6.1588215615E-002 | 0.1900157151 | Pass | Pass |
3 | SMSTORE2 | RunPeriod: RUNPERIOD 1 | 6.0379578404E-002 | 8.1725009923E-002 | Pass | Pass | 2.3876476589E-002 | 0.1098234756 | Pass | Pass |
4 | SMSTORE3 | RunPeriod: RUNPERIOD 1 | 5.4782854712E-002 | 6.9023782243E-002 | Pass | Pass | 3.0554805276E-002 | 0.1327606497 | Pass | Pass |
5 | SMSTORE4 | RunPeriod: RUNPERIOD 1 | 5.1358406098E-002 | 6.7026131415E-002 | Pass | Pass | 5.5214863318E-002 | 0.2652540630 | Pass | Pass |
6 | LGSTORE2 | RunPeriod: RUNPERIOD 1 | 5.7076681489E-002 | 0.1218232664 | Pass | Pass | 7.2490968618E-002 | 0.3022305391 | Pass | Pass |
7 | SMSTORE5 | RunPeriod: RUNPERIOD 1 | 5.5176593636E-002 | 0.1330809602 | Pass | Pass | 6.8046953466E-002 | 0.3471697344 | Pass | Pass |
8 | SMSTORE6 | RunPeriod: RUNPERIOD 1 | 5.3444638310E-002 | 0.1463786932 | Pass | Pass | 9.0541420087E-002 | 0.4192316700 | Pass | Pass |
9 | SMSTORE7 | RunPeriod: RUNPERIOD 1 | 4.7178574611E-002 | 0.1434691450 | Pass | Pass | 0.2064275261 | 0.9675320210 | Pass | Pass |
10 | SMSTORE8 | RunPeriod: RUNPERIOD 1 | 5.6311940313E-002 | 0.2275927550 | Pass | Pass | 0.1253044998 | 0.4507992011 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:11
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 3188.95 | 40.88 | 0.00 | 145.52 | 847.57 | 4222.95 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:11
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | -5.20 | 0.00 | -5.20 | Wetbulb [C] | 2.20 | 20.00 |
EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 38.10 | 13.00 | 18.10 | Wetbulb [C] | 3.90 | 280.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 3.00 | 6 | |||
Feb | 3.00 | 4 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 18.00 | 7 | |||
Jul | 27.00 | 16 | |||
Aug | 41.00 | 15 | |||
Sep | 0.00 | 0 | |||
Oct | 23.00 | 18 | |||
Nov | 0.00 | 0 | |||
Dec | 7.00 | 7 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:11
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_2 | NONRES_EXT_WALL_GRD | 0.30 | 0.624 | 0.689 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE1_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.624 | 0.689 | 78.94 | 71.15 | 0.00 | 90.00 | N |
LGSTORE1_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.624 | 0.689 | 78.94 | 58.18 | 180.00 | 90.00 | S |
LGSTORE1_FLOOR | LGSTORE1_FLOOR_FFACTOR | 1.00 | 0.193 | 0.199 | 348.39 | 348.39 | 270.00 | 180.00 | |
LGSTORE1_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 348.39 | 348.39 | 270.00 | 0.00 | |
SMSTORE1_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.624 | 0.689 | 39.47 | 29.09 | 180.00 | 90.00 | S |
SMSTORE1_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.624 | 0.689 | 39.47 | 35.57 | 0.00 | 90.00 | N |
SMSTORE1_FLOOR | SMSTORE1_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE1_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE2_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.624 | 0.689 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE2_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.624 | 0.689 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE2_FLOOR | SMSTORE2_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE2_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE3_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.624 | 0.689 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE3_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.624 | 0.689 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE3_FLOOR | SMSTORE3_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE3_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE4_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.624 | 0.689 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE4_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.624 | 0.689 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE4_FLOOR | SMSTORE4_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE4_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 | |
LGSTORE2_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.624 | 0.689 | 78.94 | 71.19 | 0.00 | 90.00 | N |
LGSTORE2_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.624 | 0.689 | 78.94 | 58.22 | 180.00 | 90.00 | S |
LGSTORE2_FLOOR | LGSTORE2_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 348.39 | 348.39 | 270.00 | 180.00 | |
LGSTORE2_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 348.39 | 348.39 | 270.00 | 0.00 | |
SMSTORE5_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.624 | 0.689 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE5_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.624 | 0.689 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE5_FLOOR | SMSTORE5_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE5_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE6_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.624 | 0.689 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE6_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.624 | 0.689 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE6_FLOOR | SMSTORE6_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE6_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE7_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.624 | 0.689 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE7_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.624 | 0.689 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE7_FLOOR | SMSTORE7_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE7_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE8_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.624 | 0.689 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE8_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.624 | 0.689 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE8_WALL_4 | NONRES_EXT_WALL_GRD | 0.30 | 0.624 | 0.689 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE8_FLOOR | SMSTORE8_FLOOR_FFACTOR | 1.00 | 0.276 | 0.289 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE8_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE1_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE2_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE2_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE3_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE3_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE4_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE4_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
LGSTORE2_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE2_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE5_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE5_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE6_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE6_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE7_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE7_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE8_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 696.77 | 0.00 | 90.00 | N | ||
SMSTORE1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
LGSTORE2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 696.77 | 0.00 | 90.00 | N | ||
SMSTORE5_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE7_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE8_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.423_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.404 | 0.251 | 0.276 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.423_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.404 | 0.251 | 0.276 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_3 | NONRESWINDOW_U_0.423_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.404 | 0.251 | 0.276 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_4 | NONRESWINDOW_U_0.423_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.404 | 0.251 | 0.276 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_DOOR_1 | NONRESWINDOW_U_0.423_SHGC_0.25 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.404 | 0.251 | 0.276 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_DOOR_2 | NONRESWINDOW_U_0.423_SHGC_0.25 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.404 | 0.251 | 0.276 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.423_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.404 | 0.251 | 0.276 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.423_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.404 | 0.251 | 0.276 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_DOOR | NONRESWINDOW_U_0.423_SHGC_0.25 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.404 | 0.251 | 0.276 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.423_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.404 | 0.251 | 0.276 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.423_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.404 | 0.251 | 0.276 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_DOOR | NONRESWINDOW_U_0.423_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.404 | 0.251 | 0.276 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.423_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.404 | 0.251 | 0.276 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.423_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.404 | 0.251 | 0.276 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_DOOR | NONRESWINDOW_U_0.423_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.404 | 0.251 | 0.276 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.423_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.404 | 0.251 | 0.276 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.423_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.404 | 0.251 | 0.276 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_DOOR | NONRESWINDOW_U_0.423_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.404 | 0.251 | 0.276 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.423_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.404 | 0.251 | 0.276 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.423_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.404 | 0.251 | 0.276 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_3 | NONRESWINDOW_U_0.423_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.404 | 0.251 | 0.276 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_4 | NONRESWINDOW_U_0.423_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.404 | 0.251 | 0.276 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_DOOR_1 | NONRESWINDOW_U_0.423_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.404 | 0.251 | 0.276 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_DOOR_2 | NONRESWINDOW_U_0.423_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.404 | 0.251 | 0.276 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.423_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.404 | 0.251 | 0.276 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.423_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.404 | 0.251 | 0.276 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_DOOR | NONRESWINDOW_U_0.423_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.404 | 0.251 | 0.276 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.423_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.404 | 0.251 | 0.276 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.423_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.404 | 0.251 | 0.276 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_DOOR | NONRESWINDOW_U_0.423_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.404 | 0.251 | 0.276 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.423_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.404 | 0.251 | 0.276 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.423_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.404 | 0.251 | 0.276 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_DOOR | NONRESWINDOW_U_0.423_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.404 | 0.251 | 0.276 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.423_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.404 | 0.251 | 0.276 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.423_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.404 | 0.251 | 0.276 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_DOOR | NONRESWINDOW_U_0.423_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.404 | 0.251 | 0.276 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
Total or Average | 124.40 | 2.404 | 0.251 | 0.276 | |||||||||||||||||
North Total or Average | 0.00 | - | - | - | |||||||||||||||||
Non-North Total or Average | 124.40 | 2.404 | 0.251 | 0.276 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
LGSTORE1_WALL_3_DOOR_1 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.90 | LGSTORE1_WALL_3 |
LGSTORE1_WALL_3_DOOR_2 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.90 | LGSTORE1_WALL_3 |
SMSTORE1_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.90 | SMSTORE1_WALL_3 |
SMSTORE2_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE2_WALL_3 |
SMSTORE3_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE3_WALL_3 |
SMSTORE4_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE4_WALL_3 |
LGSTORE2_WALL_3_DOOR_1 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | LGSTORE2_WALL_3 |
LGSTORE2_WALL_3_DOOR_2 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | LGSTORE2_WALL_3 |
SMSTORE5_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE5_WALL_3 |
SMSTORE6_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE6_WALL_3 |
SMSTORE7_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE7_WALL_3 |
SMSTORE8_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE8_WALL_3 |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:11
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
LGSTORE1_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_4 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_DOOR_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_DOOR_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_4 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_DOOR_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_DOOR_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:11
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
LGSTORE1_LIGHTS | LGSTORE1 | LGSTORE1 | GENERAL | 9.6053 | 348.39 | 3346.35 | LightsWired | LTG_SCH_BASE_LPD1 | 83.91 | 168.00 | 82.62 | 0.0000 | Y | 51.90 |
LGSTORE1_LIGHTS_ALLOWANCE | LGSTORE1 | LGSTORE1 | GENERAL | 5.6969 | 348.39 | 1984.73 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | 97.50 | 112.00 | 94.53 | 0.0000 | Y | 35.22 |
SMSTORE1_LIGHTS | SMSTORE1 | SMSTORE1 | GENERAL | 9.7206 | 174.19 | 1693.26 | LightsWired | LTG_SCH_BASE_SMALL_LPD1 | 85.41 | 168.00 | 84.05 | 0.0000 | Y | 26.72 |
SMSTORE1_LIGHTS_ALLOWANCE | SMSTORE1 | SMSTORE1 | GENERAL | 8.5685 | 174.19 | 1492.57 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | 97.50 | 112.00 | 94.53 | 0.0000 | Y | 26.49 |
SMSTORE2_LIGHTS | SMSTORE2 | SMSTORE2 | GENERAL | 9.6995 | 174.19 | 1689.58 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 68.73 | 168.00 | 65.95 | 0.0000 | Y | 20.92 |
SMSTORE2_LIGHTS_ALLOWANCE | SMSTORE2 | SMSTORE2 | GENERAL | 6.9539 | 174.19 | 1211.32 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 84.29 | 73.25 | 0.0000 | Y | 16.66 |
SMSTORE3_LIGHTS | SMSTORE3 | SMSTORE3 | GENERAL | 9.6995 | 174.19 | 1689.58 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 68.73 | 168.00 | 65.95 | 0.0000 | Y | 20.92 |
SMSTORE3_LIGHTS_ALLOWANCE | SMSTORE3 | SMSTORE3 | GENERAL | 6.9539 | 174.19 | 1211.32 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 84.29 | 73.25 | 0.0000 | Y | 16.66 |
SMSTORE4_LIGHTS | SMSTORE4 | SMSTORE4 | GENERAL | 9.6995 | 174.19 | 1689.58 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 68.73 | 168.00 | 65.95 | 0.0000 | Y | 20.92 |
SMSTORE4_LIGHTS_ALLOWANCE | SMSTORE4 | SMSTORE4 | GENERAL | 6.9539 | 174.19 | 1211.32 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 84.29 | 73.25 | 0.0000 | Y | 16.66 |
LGSTORE2_LIGHTS | LGSTORE2 | LGSTORE2 | GENERAL | 9.5842 | 348.39 | 3339.00 | LightsWired | LTG_SCH_BASE_LPD2 | 62.11 | 168.00 | 59.29 | 0.0000 | Y | 37.16 |
LGSTORE2_LIGHTS_ALLOWANCE | LGSTORE2 | LGSTORE2 | GENERAL | 0.0000 | 348.39 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE5_LIGHTS | SMSTORE5 | SMSTORE5 | GENERAL | 9.6995 | 174.19 | 1689.58 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 60.29 | 0.0000 | Y | 19.12 |
SMSTORE5_LIGHTS_ALLOWANCE | SMSTORE5 | SMSTORE5 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE6_LIGHTS | SMSTORE6 | SMSTORE6 | GENERAL | 9.6995 | 174.19 | 1689.58 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 60.29 | 0.0000 | Y | 19.12 |
SMSTORE6_LIGHTS_ALLOWANCE | SMSTORE6 | SMSTORE6 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE7_LIGHTS | SMSTORE7 | SMSTORE7 | GENERAL | 9.6995 | 174.19 | 1689.58 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 60.29 | 0.0000 | Y | 19.12 |
SMSTORE7_LIGHTS_ALLOWANCE | SMSTORE7 | SMSTORE7 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE8_LIGHTS | SMSTORE8 | SMSTORE8 | GENERAL | 9.6995 | 174.19 | 1689.58 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 60.29 | 0.0000 | Y | 19.12 |
SMSTORE8_LIGHTS_ALLOWANCE | SMSTORE8 | SMSTORE8 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
Interior Lighting Total | 6.5342 | 4180.64 | 27316.92 | 366.68 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 455.59 | AstronomicalClock | - | 41.77 | 41.77 | 3.57 | |
EXTERIOR_LIGHTS_B | 2744.24 | AstronomicalClock | - | 83.77 | 62.77 | 32.33 | |
EXTERIOR_LIGHTS_C | 2307.23 | AstronomicalClock | - | 83.77 | 55.77 | 24.15 | |
Exterior Lighting Total | 5507.06 | 60.06 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:11
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 45276.41 | 36164.08 | 9112.33 | 0.80 | 3.73 | |||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 23485.02 | 18809.86 | 4675.16 | 0.80 | 3.80 | |||
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 24133.95 | 19307.88 | 4826.07 | 0.80 | 3.80 | |||
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 23989.93 | 19196.02 | 4793.91 | 0.80 | 3.80 | |||
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 23991.93 | 19211.54 | 4780.39 | 0.80 | 3.80 | |||
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 42109.61 | 33403.03 | 8706.58 | 0.79 | 3.73 | |||
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 21755.53 | 17327.84 | 4427.69 | 0.80 | 3.80 | |||
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 21670.67 | 17233.60 | 4437.07 | 0.80 | 3.80 | |||
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 21697.67 | 17256.59 | 4441.08 | 0.80 | 3.80 | |||
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 23853.43 | 19093.00 | 4760.43 | 0.80 | 3.80 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC_1:1 COOLING COIL | 43397.0 | 11.25 | 11.25 | ||||
PSZ-AC_2:2 COOLING COIL | 22503.6 | 11.40 | 11.40 | ||||
PSZ-AC_3:3 COOLING COIL | 23125.1 | 11.40 | 11.40 | ||||
PSZ-AC_4:4 COOLING COIL | 22986.7 | 11.39 | 11.39 | ||||
PSZ-AC_5:5 COOLING COIL | 22989.9 | 11.40 | 11.40 | ||||
PSZ-AC_6:6 COOLING COIL | 40385.7 | 11.28 | 11.28 | ||||
PSZ-AC_7:7 COOLING COIL | 20858.7 | 11.43 | 11.43 | ||||
PSZ-AC_8:8 COOLING COIL | 20778.0 | 11.43 | 11.43 | ||||
PSZ-AC_9:9 COOLING COIL | 20803.7 | 11.43 | 11.43 | ||||
PSZ-AC_10:10 COOLING COIL | 22836.9 | 11.35 | 11.35 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | 58814.13 | 0.80 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | 30461.80 | 0.80 | |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | 31154.76 | 0.80 | |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | 31013.52 | 0.80 | |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | 30982.65 | 0.80 | |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | 54877.46 | 0.80 | |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | 28321.81 | 0.80 | |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | 28217.14 | 0.80 | |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | 28249.86 | 0.80 | |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | 31356.71 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 2.39 | 2561.22 | 1070.05 | 1.00 | 1.29 | General | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.25 | 1383.93 | 1107.16 | 1.00 | 1.35 | General | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.28 | 1422.63 | 1107.16 | 1.00 | 1.35 | General | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 |
PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.28 | 1414.74 | 1107.16 | 1.00 | 1.35 | General | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.28 | 1413.02 | 1107.16 | 1.00 | 1.35 | General | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 2.20 | 2348.77 | 1070.05 | 1.00 | 1.30 | General | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.14 | 1264.42 | 1107.16 | 1.00 | 1.37 | General | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.14 | 1258.58 | 1107.16 | 1.00 | 1.37 | General | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.14 | 1260.41 | 1107.16 | 1.00 | 1.37 | General | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.30 | 1433.88 | 1107.16 | 1.00 | 1.34 | General | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
GAS TANK1 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK2 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK3 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK4 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK5 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK6 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK7 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:11
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
LGSTORE1 | 23509.23 | 28211.07 | 80.98 | 1.995 | 2.394 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 23.89 | 23.89 | 0.00745 | 38.10 | 0.00687 | 0.411 | 0.00 |
SMSTORE1 | 12277.26 | 14732.72 | 84.58 | 1.042 | 1.250 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 23.89 | 23.89 | 0.00743 | 37.99 | 0.00687 | 0.206 | 0.00 |
SMSTORE2 | 12920.45 | 15504.54 | 89.01 | 1.071 | 1.285 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 23.89 | 23.89 | 0.00770 | 30.95 | 0.00686 | 0.206 | 0.00 |
SMSTORE3 | 12850.71 | 15420.85 | 88.53 | 1.065 | 1.278 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 23.89 | 23.89 | 0.00770 | 30.95 | 0.00686 | 0.206 | 0.00 |
SMSTORE4 | 12834.30 | 15401.16 | 88.41 | 1.064 | 1.276 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 23.89 | 23.89 | 0.00771 | 30.95 | 0.00686 | 0.206 | 0.00 |
LGSTORE2 | 21559.07 | 25870.88 | 74.26 | 1.829 | 2.195 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 23.89 | 23.89 | 0.00749 | 37.88 | 0.00687 | 0.411 | 0.00 |
SMSTORE5 | 11217.06 | 13460.47 | 77.27 | 0.952 | 1.142 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 23.89 | 23.89 | 0.00747 | 37.88 | 0.00687 | 0.206 | 0.00 |
SMSTORE6 | 11165.21 | 13398.25 | 76.92 | 0.947 | 1.137 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 23.89 | 23.89 | 0.00747 | 37.88 | 0.00687 | 0.206 | 0.00 |
SMSTORE7 | 11181.42 | 13417.70 | 77.03 | 0.949 | 1.138 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 23.89 | 23.89 | 0.00747 | 37.88 | 0.00687 | 0.206 | 0.00 |
SMSTORE8 | 12720.17 | 15264.21 | 87.63 | 1.079 | 1.295 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | 23.89 | 23.89 | 0.00741 | 37.45 | 0.00687 | 0.206 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
LGSTORE1 | 18523.76 | 22228.51 | 63.80 | 0.921 | 1.105 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.11 | 0.00688 | -5.20 | 0.00281 | 0.411 | 0.00 |
SMSTORE1 | 8704.10 | 10444.92 | 59.96 | 0.433 | 0.519 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.11 | 0.00678 | -5.20 | 0.00281 | 0.206 | 0.00 |
SMSTORE2 | 8824.11 | 10588.93 | 60.79 | 0.439 | 0.526 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.11 | 0.00679 | -5.20 | 0.00281 | 0.206 | 0.00 |
SMSTORE3 | 8925.30 | 10710.36 | 61.49 | 0.444 | 0.532 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.11 | 0.00680 | -5.20 | 0.00281 | 0.206 | 0.00 |
SMSTORE4 | 9102.61 | 10923.14 | 62.71 | 0.452 | 0.543 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.11 | 0.00682 | -5.20 | 0.00281 | 0.206 | 0.00 |
LGSTORE2 | 17731.05 | 21277.26 | 61.07 | 0.881 | 1.058 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.11 | 0.00690 | -5.20 | 0.00281 | 0.411 | 0.00 |
SMSTORE5 | 9415.64 | 11298.77 | 64.86 | 0.468 | 0.562 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.11 | 0.00684 | -5.20 | 0.00281 | 0.206 | 0.00 |
SMSTORE6 | 9412.83 | 11295.40 | 64.84 | 0.468 | 0.561 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.11 | 0.00684 | -5.20 | 0.00281 | 0.206 | 0.00 |
SMSTORE7 | 9680.33 | 11616.40 | 66.69 | 0.481 | 0.577 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.11 | 0.00686 | -5.20 | 0.00281 | 0.206 | 0.00 |
SMSTORE8 | 11681.27 | 14017.52 | 80.47 | 0.581 | 0.697 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.11 | 0.00692 | -5.20 | 0.00281 | 0.206 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC_1:1 | 2.39 | 2.39 | 1.10 | 1.10 | 2.3936 | 2.3936 | 2.3936 | 1.0000 | 1.0000 |
PSZ-AC_2:2 | 1.25 | 1.25 | 0.52 | 0.52 | 1.2500 | 1.2500 | 1.2500 | 1.0000 | 1.0000 |
PSZ-AC_3:3 | 1.28 | 1.28 | 0.53 | 0.53 | 1.2849 | 1.2849 | 1.2849 | 1.0000 | 1.0000 |
PSZ-AC_4:4 | 1.28 | 1.28 | 0.53 | 0.53 | 1.2778 | 1.2778 | 1.2778 | 1.0000 | 1.0000 |
PSZ-AC_5:5 | 1.28 | 1.28 | 0.54 | 0.54 | 1.2763 | 1.2763 | 1.2763 | 1.0000 | 1.0000 |
PSZ-AC_6:6 | 2.20 | 2.20 | 1.06 | 1.06 | 2.1950 | 2.1950 | 2.1950 | 1.0000 | 1.0000 |
PSZ-AC_7:7 | 1.14 | 1.14 | 0.56 | 0.56 | 1.1420 | 1.1420 | 1.1420 | 1.0000 | 1.0000 |
PSZ-AC_8:8 | 1.14 | 1.14 | 0.56 | 0.56 | 1.1368 | 1.1368 | 1.1368 | 1.0000 | 1.0000 |
PSZ-AC_9:9 | 1.14 | 1.14 | 0.58 | 0.58 | 1.1384 | 1.1384 | 1.1384 | 1.0000 | 1.0000 |
PSZ-AC_10:10 | 1.30 | 1.30 | 0.70 | 0.70 | 1.2951 | 1.2951 | 1.2951 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 45276.410 | 36164.080 | 2.393560 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 22638.21 | 21708.54 | 1.595707 | 27.34 | 15.12 | 0.00735345 | 12.80 | 9.33 | 0.00700000 | 38.10 | 0.00687148 | 18.17 | 25.7866 | 23.89 | 0.00745351 | 35.0905 | 23509.23 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_1:1 | 58814.130 | 58814.130 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 58814.13 | 58814.13 | 2.393560 | 16.59 | 10.07 | 0.00618326 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 17.1911 | 21.11 | 0.00688388 | 38.4120 | 18523.76 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 23485.020 | 18809.857 | 1.249980 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 11742.51 | 11274.70 | 0.833320 | 27.27 | 15.08 | 0.00734133 | 12.80 | 9.33 | 0.00700000 | 38.10 | 0.00687148 | 18.17 | 24.6891 | 23.89 | 0.00743393 | 34.9992 | 12275.32 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_2:2 | 30461.803 | 30461.803 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 30461.80 | 30461.80 | 1.249984 | 16.78 | 10.10 | 0.00612895 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 16.4594 | 21.11 | 0.00678317 | 37.8561 | 8704.10 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_3:3 | 24133.950 | 19307.884 | 1.284940 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 12066.98 | 11586.77 | 0.856627 | 27.26 | 15.08 | 0.00734085 | 12.80 | 9.33 | 0.00700000 | 38.10 | 0.00687148 | 18.17 | 24.0174 | 23.89 | 0.00743311 | 34.9954 | 12302.32 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_3:3 | 31154.762 | 31154.762 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 31154.76 | 31154.76 | 1.284936 | 16.90 | 10.17 | 0.00615514 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 16.0116 | 21.11 | 0.00679317 | 37.9113 | 8824.11 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_4:4 | 23989.930 | 19196.022 | 1.277810 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 11994.97 | 11518.36 | 0.851873 | 27.26 | 15.08 | 0.00734020 | 12.80 | 9.33 | 0.00700000 | 38.10 | 0.00687148 | 18.17 | 24.1514 | 23.89 | 0.00743200 | 34.9902 | 12337.95 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_4:4 | 31013.517 | 31013.517 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 31013.52 | 31013.52 | 1.277812 | 16.87 | 10.16 | 0.00615857 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 16.1009 | 21.11 | 0.00680150 | 37.9573 | 8925.30 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_5:5 | 23991.930 | 19211.538 | 1.276250 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 11995.97 | 11517.07 | 0.850833 | 27.28 | 15.09 | 0.00734221 | 12.80 | 9.33 | 0.00700000 | 38.10 | 0.00687148 | 18.17 | 24.1809 | 23.89 | 0.00743539 | 35.0060 | 12229.58 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_5:5 | 30982.649 | 30982.649 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 30982.65 | 30982.65 | 1.276255 | 16.87 | 10.17 | 0.00617010 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 16.1206 | 21.11 | 0.00681617 | 38.0383 | 9102.61 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_6:6 | 42109.610 | 33403.027 | 2.195020 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 21054.81 | 20143.02 | 1.463347 | 27.56 | 15.21 | 0.00737756 | 12.80 | 9.33 | 0.00700000 | 38.10 | 0.00687148 | 18.17 | 28.1190 | 23.89 | 0.00749440 | 35.2807 | 21545.91 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_6:6 | 54877.462 | 54877.462 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 54877.46 | 54877.46 | 2.195018 | 16.18 | 9.85 | 0.00613064 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 18.7460 | 21.11 | 0.00689711 | 38.4844 | 17731.05 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_7:7 | 21755.530 | 17327.845 | 1.142040 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 10877.76 | 10423.64 | 0.761360 | 27.49 | 15.18 | 0.00736222 | 12.80 | 9.33 | 0.00700000 | 38.10 | 0.00687148 | 18.17 | 27.0226 | 23.89 | 0.00747016 | 35.1678 | 11207.72 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_7:7 | 28321.812 | 28321.812 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 28321.81 | 28321.81 | 1.142044 | 16.37 | 9.91 | 0.00611440 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 18.0150 | 21.11 | 0.00684084 | 38.1745 | 9415.64 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_8:8 | 21670.670 | 17233.600 | 1.136760 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 10835.33 | 10381.95 | 0.757840 | 27.50 | 15.18 | 0.00736329 | 12.80 | 9.33 | 0.00700000 | 38.10 | 0.00687148 | 18.17 | 27.1481 | 23.89 | 0.00747208 | 35.1767 | 11155.78 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_8:8 | 28217.144 | 28217.144 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 28217.14 | 28217.14 | 1.136765 | 16.35 | 9.90 | 0.00611088 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 18.0987 | 21.11 | 0.00684067 | 38.1736 | 9412.83 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_9:9 | 21697.670 | 17256.591 | 1.138410 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 10848.83 | 10395.17 | 0.758940 | 27.50 | 15.18 | 0.00736299 | 12.80 | 9.33 | 0.00700000 | 38.10 | 0.00687148 | 18.17 | 27.1088 | 23.89 | 0.00747154 | 35.1742 | 11170.49 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_9:9 | 28249.864 | 28249.864 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 28249.86 | 28249.86 | 1.138415 | 16.35 | 9.92 | 0.00612831 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 18.0724 | 21.11 | 0.00686065 | 38.2839 | 9680.33 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_10:10 | 23853.430 | 19093.001 | 1.295100 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | 11926.72 | 11466.08 | 0.863400 | 27.08 | 15.01 | 0.00732756 | 12.80 | 9.33 | 0.00700000 | 37.45 | 0.00687043 | 17.97 | 23.8290 | 23.89 | 0.00741390 | 34.9059 | 12720.17 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_10:10 | 31356.709 | 31356.709 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 31356.71 | 31356.71 | 1.295098 | 16.93 | 10.30 | 0.00626968 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 15.8860 | 21.11 | 0.00692339 | 38.6313 | 11681.27 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:37:11
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 45276.410 | 36164.080 | 2.393560 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.5097 | 1004.8586 | 1.0443 | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.393560 | 2.49967054 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | Sensible | 22638.21 | 21708.54 | 1.0000 | 1.66644711 | 1.595707 | 27.34 | 15.12 | 0.00735345 | 46233.7 | 12.80 | 9.33 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 22638.21 | 38.10 | 0.00687148 | 18.17 | 0.41147883 | 25.7866 | 23.89 | 0.00745351 | 23.89 | 0.00745351 | 35.0905 | 23509.23 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 58814.130 | 58814.130 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.393560 | 2.49967054 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | Sensible | 58814.13 | 58814.13 | 1.0000 | 2.49967054 | 2.393560 | 16.59 | 10.07 | 0.00618326 | 32319.9 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 58814.13 | -5.20 | 0.00280840 | -5.20 | 0.41147883 | 17.1911 | 21.11 | 0.00688388 | 21.11 | 0.00688388 | 38.4120 | 18523.76 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 23485.020 | 18809.857 | 1.249980 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.4872 | 1004.8586 | 1.0443 | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.249984 | 1.30539759 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | Sensible | 11742.51 | 11274.70 | 1.0000 | 0.87026252 | 0.833320 | 27.27 | 15.08 | 0.00734133 | 46132.9 | 12.80 | 9.33 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11742.51 | 38.10 | 0.00687148 | 18.17 | 0.20573941 | 24.6891 | 23.89 | 0.00743393 | 23.89 | 0.00743393 | 34.9992 | 12275.32 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 30461.803 | 30461.803 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.249984 | 1.30539759 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | Sensible | 30461.80 | 30461.80 | 1.0000 | 1.30539759 | 1.249984 | 16.78 | 10.10 | 0.00612895 | 32378.1 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 30461.80 | -5.20 | 0.00280840 | -5.20 | 0.20573941 | 16.4594 | 21.11 | 0.00678317 | 21.11 | 0.00678317 | 37.8561 | 8704.10 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 24133.950 | 19307.884 | 1.284940 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.4863 | 1004.8586 | 1.0443 | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.284936 | 1.34189940 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | Sensible | 12066.98 | 11586.77 | 1.0000 | 0.89460241 | 0.856627 | 27.26 | 15.08 | 0.00734085 | 46126.4 | 12.80 | 9.33 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 12066.98 | 38.10 | 0.00687148 | 18.17 | 0.20573941 | 24.0174 | 23.89 | 0.00743311 | 23.89 | 0.00743311 | 34.9954 | 12302.32 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 31154.762 | 31154.762 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.284936 | 1.34189940 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | Sensible | 31154.76 | 31154.76 | 1.0000 | 1.34189940 | 1.284936 | 16.90 | 10.17 | 0.00615514 | 32564.1 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 31154.76 | -5.20 | 0.00280840 | -5.20 | 0.20573941 | 16.0116 | 21.11 | 0.00679317 | 21.11 | 0.00679317 | 37.9113 | 8824.11 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 23989.930 | 19196.022 | 1.277810 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.4851 | 1004.8586 | 1.0443 | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.277812 | 1.33445918 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | Sensible | 11994.97 | 11518.36 | 1.0000 | 0.88963835 | 0.851873 | 27.26 | 15.08 | 0.00734020 | 46117.9 | 12.80 | 9.33 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11994.97 | 38.10 | 0.00687148 | 18.17 | 0.20573941 | 24.1514 | 23.89 | 0.00743200 | 23.89 | 0.00743200 | 34.9902 | 12337.95 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 31013.517 | 31013.517 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.277812 | 1.33445918 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | Sensible | 31013.52 | 31013.52 | 1.0000 | 1.33445918 | 1.277812 | 16.87 | 10.16 | 0.00615857 | 32548.9 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 31013.52 | -5.20 | 0.00280840 | -5.20 | 0.20573941 | 16.1009 | 21.11 | 0.00680150 | 21.11 | 0.00680150 | 37.9573 | 8925.30 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 23991.930 | 19211.538 | 1.276250 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.4888 | 1004.8586 | 1.0443 | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.276255 | 1.33283330 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | Sensible | 11995.97 | 11517.07 | 1.0000 | 0.88855225 | 0.850833 | 27.28 | 15.09 | 0.00734221 | 46144.0 | 12.80 | 9.33 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11995.97 | 38.10 | 0.00687148 | 18.17 | 0.20573941 | 24.1809 | 23.89 | 0.00743539 | 23.89 | 0.00743539 | 35.0060 | 12229.58 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 30982.649 | 30982.649 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.276255 | 1.33283330 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | Sensible | 30982.65 | 30982.65 | 1.0000 | 1.33283330 | 1.276255 | 16.87 | 10.17 | 0.00617010 | 32572.8 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 30982.65 | -5.20 | 0.00280840 | -5.20 | 0.20573941 | 16.1206 | 21.11 | 0.00681617 | 21.11 | 0.00681617 | 38.0383 | 9102.61 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 42109.610 | 33403.027 | 2.195020 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.5545 | 1004.8586 | 1.0443 | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.195018 | 2.29232715 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | Sensible | 21054.81 | 20143.02 | 1.0000 | 1.52821936 | 1.463347 | 27.56 | 15.21 | 0.00737756 | 46521.9 | 12.80 | 9.33 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 21054.81 | 38.10 | 0.00687148 | 18.17 | 0.41147883 | 28.1190 | 23.89 | 0.00749440 | 23.89 | 0.00749440 | 35.2807 | 21545.91 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 54877.462 | 54877.462 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.195018 | 2.29232715 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | Sensible | 54877.46 | 54877.46 | 1.0000 | 2.29232715 | 2.195018 | 16.18 | 9.85 | 0.00613064 | 31771.1 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 54877.46 | -5.20 | 0.00280840 | -5.20 | 0.41147883 | 18.7460 | 21.11 | 0.00689711 | 21.11 | 0.00689711 | 38.4844 | 17731.05 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 21755.530 | 17327.845 | 1.142040 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.5260 | 1004.8586 | 1.0443 | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.142044 | 1.19267277 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | Sensible | 10877.76 | 10423.64 | 1.0000 | 0.79511241 | 0.761360 | 27.49 | 15.18 | 0.00736222 | 46413.1 | 12.80 | 9.33 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10877.76 | 38.10 | 0.00687148 | 18.17 | 0.20573941 | 27.0226 | 23.89 | 0.00747016 | 23.89 | 0.00747016 | 35.1678 | 11207.72 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 28321.812 | 28321.812 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.142044 | 1.19267277 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | Sensible | 28321.81 | 28321.81 | 1.0000 | 1.19267277 | 1.142044 | 16.37 | 9.91 | 0.00611440 | 31925.3 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28321.81 | -5.20 | 0.00280840 | -5.20 | 0.20573941 | 18.0150 | 21.11 | 0.00684084 | 21.11 | 0.00684084 | 38.1745 | 9415.64 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 21670.670 | 17233.600 | 1.136760 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.5280 | 1004.8586 | 1.0443 | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.136765 | 1.18715939 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | Sensible | 10835.33 | 10381.95 | 1.0000 | 0.79143636 | 0.757840 | 27.50 | 15.18 | 0.00736329 | 46428.0 | 12.80 | 9.33 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10835.33 | 38.10 | 0.00687148 | 18.17 | 0.20573941 | 27.1481 | 23.89 | 0.00747208 | 23.89 | 0.00747208 | 35.1767 | 11155.78 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 28217.144 | 28217.144 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.136765 | 1.18715939 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | Sensible | 28217.14 | 28217.14 | 1.0000 | 1.18715939 | 1.136765 | 16.35 | 9.90 | 0.00611088 | 31894.1 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28217.14 | -5.20 | 0.00280840 | -5.20 | 0.20573941 | 18.0987 | 21.11 | 0.00684067 | 21.11 | 0.00684067 | 38.1736 | 9412.83 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 21697.670 | 17256.591 | 1.138410 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.5274 | 1004.8586 | 1.0443 | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.138415 | 1.18888280 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | Sensible | 10848.83 | 10395.17 | 1.0000 | 0.79258512 | 0.758940 | 27.50 | 15.18 | 0.00736299 | 46423.8 | 12.80 | 9.33 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10848.83 | 38.10 | 0.00687148 | 18.17 | 0.20573941 | 27.1088 | 23.89 | 0.00747154 | 23.89 | 0.00747154 | 35.1742 | 11170.49 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 28249.864 | 28249.864 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.138415 | 1.18888280 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | Sensible | 28249.86 | 28249.86 | 1.0000 | 1.18888280 | 1.138415 | 16.35 | 9.92 | 0.00612831 | 31945.2 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28249.86 | -5.20 | 0.00280840 | -5.20 | 0.20573941 | 18.0724 | 21.11 | 0.00686065 | 21.11 | 0.00686065 | 38.2839 | 9680.33 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 23853.430 | 19093.001 | 1.295100 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.4616 | 1004.8586 | 1.0443 | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.295098 | 1.35251242 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | Sensible | 11926.72 | 11466.08 | 1.0000 | 0.90167602 | 0.863400 | 27.08 | 15.01 | 0.00732756 | 45909.1 | 12.80 | 9.33 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11926.72 | 37.45 | 0.00687043 | 17.97 | 0.20573941 | 23.8290 | 23.89 | 0.00741390 | 23.89 | 0.00741390 | 34.9059 | 12720.17 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 31356.709 | 31356.709 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.295098 | 1.35251242 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | Sensible | 31356.71 | 31356.71 | 1.0000 | 1.35251242 | 1.295098 | 16.93 | 10.30 | 0.00626968 | 32887.4 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 31356.71 | -5.20 | 0.00280840 | -5.20 | 0.20573941 | 15.8860 | 21.11 | 0.00692339 | 21.11 | 0.00692339 | 38.6313 | 11681.27 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:11
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-AC_1:1_OA_CONTROLLER | DifferentialDryBulb | 0.41 | 2.39 | - | |||
PSZ-AC_2:2_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.25 | - | |||
PSZ-AC_3:3_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.28 | - | |||
PSZ-AC_4:4_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.28 | - | |||
PSZ-AC_5:5_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.28 | - | |||
PSZ-AC_6:6_OA_CONTROLLER | DifferentialDryBulb | 0.41 | 2.20 | - | |||
PSZ-AC_7:7_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.14 | - | |||
PSZ-AC_8:8_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.14 | - | |||
PSZ-AC_9:9_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.14 | - | |||
PSZ-AC_10:10_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.30 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
LGSTORE1 | 2342.17 | 2903.00 | 339.33 |
SMSTORE1 | 2112.50 | 2704.33 | 111.50 |
SMSTORE2 | 1746.33 | 2070.33 | 180.67 |
SMSTORE3 | 1761.67 | 2084.33 | 193.83 |
SMSTORE4 | 1757.83 | 2134.00 | 222.17 |
LGSTORE2 | 1603.50 | 2054.33 | 271.17 |
SMSTORE5 | 1555.50 | 2106.00 | 288.67 |
SMSTORE6 | 1564.33 | 2118.17 | 304.00 |
SMSTORE7 | 1612.33 | 2144.33 | 356.83 |
SMSTORE8 | 1895.83 | 2141.17 | 548.00 |
Facility | 2863.17 | 3313.50 | 784.33 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
LGSTORE1 | 0.83 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 0.00 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 1.00 | 0.00 | 0.00 | 0.00 |
Facility | 1.83 | 0.00 | 0.00 | 0.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:11
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
LGSTORE1 | 16.93 | 56.25 | 1805.20 | 1.083 | 0.224 | 0.000 | 0.000 |
SMSTORE1 | 8.47 | 28.12 | 902.60 | 0.956 | 0.239 | 0.000 | 0.000 |
SMSTORE2 | 7.08 | 28.12 | 902.60 | 1.130 | 0.312 | 0.000 | 0.000 |
SMSTORE3 | 7.08 | 28.12 | 902.60 | 1.121 | 0.312 | 0.000 | 0.000 |
SMSTORE4 | 7.08 | 28.12 | 902.60 | 1.104 | 0.312 | 0.000 | 0.000 |
LGSTORE2 | 24.76 | 56.25 | 1805.20 | 1.028 | 0.299 | 0.000 | 0.000 |
SMSTORE5 | 12.38 | 28.12 | 902.60 | 1.035 | 0.332 | 0.000 | 0.000 |
SMSTORE6 | 12.38 | 28.12 | 902.60 | 1.028 | 0.332 | 0.000 | 0.000 |
SMSTORE7 | 12.38 | 28.12 | 902.60 | 1.017 | 0.332 | 0.000 | 0.000 |
SMSTORE8 | 12.38 | 28.12 | 902.60 | 1.043 | 0.351 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
LGSTORE1 | 16.93 | 56.25 | 1805.20 | 0.000 | 0.000 | 0.000 | 0.000 |
SMSTORE1 | 8.47 | 28.12 | 902.60 | 0.000 | 0.000 | 0.000 | 0.000 |
SMSTORE2 | 7.08 | 28.12 | 902.60 | 0.810 | 0.000 | 0.000 | 0.000 |
SMSTORE3 | 7.08 | 28.12 | 902.60 | 0.810 | 0.000 | 0.000 | 0.000 |
SMSTORE4 | 7.08 | 28.12 | 902.60 | 0.810 | 0.000 | 0.000 | 0.000 |
LGSTORE2 | 24.76 | 56.25 | 1805.20 | 0.810 | 0.000 | 0.000 | 0.000 |
SMSTORE5 | 12.38 | 28.12 | 902.60 | 0.810 | 0.000 | 0.000 | 0.000 |
SMSTORE6 | 12.38 | 28.12 | 902.60 | 0.810 | 0.000 | 0.000 | 0.000 |
SMSTORE7 | 12.38 | 28.12 | 902.60 | 0.810 | 0.000 | 0.000 | 0.000 |
SMSTORE8 | 12.38 | 28.12 | 902.60 | 0.810 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:37:11
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
LGSTORE1 | PSZ-AC_1:1 | 16.93 | 56.25 | 1805.20 | 348.39 | 0.4115 | 0.411 |
SMSTORE1 | PSZ-AC_2:2 | 8.47 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE2 | PSZ-AC_3:3 | 7.08 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE3 | PSZ-AC_4:4 | 7.08 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE4 | PSZ-AC_5:5 | 7.08 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
LGSTORE2 | PSZ-AC_6:6 | 24.76 | 56.25 | 1805.20 | 348.39 | 0.4115 | 0.411 |
SMSTORE5 | PSZ-AC_7:7 | 12.38 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE6 | PSZ-AC_8:8 | 12.38 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE7 | PSZ-AC_9:9 | 12.38 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE8 | PSZ-AC_10:10 | 12.38 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
Total Facility | 120.91 | 337.50 | 10831.20 | 2090.32 | 2.4689 | 2.469 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
LGSTORE1 | 11301773.66 | 0.00 | 11301773.66 | 2654284.96 | 13956058.62 | 12976396.34 | 3117.77 | 4286.83 | 1355.39 | 29.02 |
SMSTORE1 | 4996463.64 | 0.00 | 4996463.64 | 1335851.20 | 6332314.84 | 6488198.17 | 4317.30 | 3061.77 | 1380.93 | 34.46 |
SMSTORE2 | 4593056.00 | 0.00 | 4593056.00 | 1373042.31 | 5966098.31 | 6488198.17 | 4277.57 | 3412.42 | 1070.02 | 142.13 |
SMSTORE3 | 4556903.36 | 0.00 | 4556903.36 | 1373042.31 | 5929945.66 | 6488198.17 | 4277.63 | 3438.42 | 1043.95 | 139.48 |
SMSTORE4 | 4483428.41 | 0.00 | 4483428.41 | 1373042.31 | 5856470.72 | 6488198.17 | 4280.81 | 3497.50 | 981.69 | 135.42 |
LGSTORE2 | 7581637.66 | 0.00 | 7581637.66 | 2517504.51 | 10099142.17 | 12976396.34 | 4671.77 | 3311.00 | 777.23 | 93.50 |
SMSTORE5 | 3821109.38 | 0.00 | 3821109.38 | 1381311.82 | 5202421.20 | 6488198.17 | 4670.90 | 3327.17 | 761.93 | 93.16 |
SMSTORE6 | 3797165.20 | 0.00 | 3797165.20 | 1381311.82 | 5178477.02 | 6488198.17 | 4671.57 | 3346.33 | 742.10 | 91.29 |
SMSTORE7 | 3753556.55 | 0.00 | 3753556.55 | 1381311.82 | 5134868.37 | 6488198.17 | 4674.06 | 3394.50 | 691.44 | 86.25 |
SMSTORE8 | 3853687.15 | 0.00 | 3853687.15 | 1677204.46 | 5530891.61 | 6488198.17 | 4673.25 | 3426.92 | 659.83 | 77.71 |
Total Facility | 52738781.01 | 0.00 | 52738781.01 | 16447907.52 | 69186688.53 | 77858378.04 | 4679.29 | 4812.44 | 1698.78 | 254.72 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
LGSTORE1 | 0.5341 | 0.0000 | 0.5341 | 0.1106 | 0.6447 | 0.4115 | 214.73 | 4286.67 | 1338.60 |
SMSTORE1 | 0.2356 | 0.0000 | 0.2356 | 0.0589 | 0.2945 | 0.2057 | 1416.26 | 3061.60 | 1362.14 |
SMSTORE2 | 0.2787 | 0.0000 | 0.2787 | 0.0768 | 0.3555 | 0.2057 | 0.00 | 3412.08 | 982.92 |
SMSTORE3 | 0.2764 | 0.0000 | 0.2764 | 0.0768 | 0.3533 | 0.2057 | 0.00 | 3438.08 | 956.92 |
SMSTORE4 | 0.2723 | 0.0000 | 0.2723 | 0.0768 | 0.3492 | 0.2057 | 0.00 | 3496.67 | 898.33 |
LGSTORE2 | 0.5069 | 0.0000 | 0.5069 | 0.1476 | 0.6545 | 0.4115 | 0.00 | 3310.67 | 719.33 |
SMSTORE5 | 0.2551 | 0.0000 | 0.2551 | 0.0820 | 0.3371 | 0.2057 | 0.00 | 3327.17 | 702.83 |
SMSTORE6 | 0.2536 | 0.0000 | 0.2536 | 0.0820 | 0.3356 | 0.2057 | 0.00 | 3346.00 | 684.00 |
SMSTORE7 | 0.2509 | 0.0000 | 0.2509 | 0.0820 | 0.3329 | 0.2057 | 0.00 | 3394.33 | 635.67 |
SMSTORE8 | 0.2572 | 0.0000 | 0.2572 | 0.0865 | 0.3437 | 0.2057 | 0.00 | 3426.75 | 603.25 |
Total Facility | 3.1209 | 0.0000 | 3.1209 | 0.8802 | 4.0011 | 2.4689 | 1507.76 | 4810.10 | 1622.24 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-AC_1:1 | 12326082.84 | 0.00 | 12326082.84 | 12976396.34 | 3116.24 | 0.33 | 5643.43 | 29.02 |
PSZ-AC_2:2 | 5449294.49 | 0.00 | 5449294.49 | 6488198.17 | 4297.88 | 3.58 | 4458.54 | 34.46 |
PSZ-AC_3:3 | 5009332.28 | 0.00 | 5009332.28 | 6488198.17 | 4276.20 | 0.33 | 4483.47 | 142.10 |
PSZ-AC_4:4 | 4969903.87 | 0.00 | 4969903.87 | 6488198.17 | 4276.30 | 0.33 | 4483.37 | 139.32 |
PSZ-AC_5:5 | 4889769.99 | 0.00 | 4889769.99 | 6488198.17 | 4278.64 | 0.58 | 4480.78 | 135.14 |
PSZ-AC_6:6 | 8268782.25 | 0.00 | 8268782.25 | 12976396.34 | 4670.65 | 0.25 | 4089.10 | 93.33 |
PSZ-AC_7:7 | 4167423.73 | 0.00 | 4167423.73 | 6488198.17 | 4669.82 | 0.25 | 4089.93 | 92.83 |
PSZ-AC_8:8 | 4141305.02 | 0.00 | 4141305.02 | 6488198.17 | 4670.57 | 0.33 | 4089.10 | 90.96 |
PSZ-AC_9:9 | 4093728.10 | 0.00 | 4093728.10 | 6488198.17 | 4672.39 | 0.50 | 4087.11 | 86.25 |
PSZ-AC_10:10 | 4202911.41 | 0.00 | 4202911.41 | 6488198.17 | 4672.25 | 0.17 | 4087.58 | 77.54 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-AC_1:1 | 0.5825 | 0.0000 | 0.5825 | 0.4115 | 213.62 | 0.33 | 5626.05 |
PSZ-AC_2:2 | 0.2570 | 0.0000 | 0.2570 | 0.2057 | 1396.84 | 3.58 | 4439.58 |
PSZ-AC_3:3 | 0.3039 | 0.0000 | 0.3039 | 0.2057 | 0.00 | 0.00 | 4395.00 |
PSZ-AC_4:4 | 0.3015 | 0.0000 | 0.3015 | 0.2057 | 0.00 | 0.00 | 4395.00 |
PSZ-AC_5:5 | 0.2970 | 0.0000 | 0.2970 | 0.2057 | 0.00 | 0.00 | 4395.00 |
PSZ-AC_6:6 | 0.5528 | 0.0000 | 0.5528 | 0.4115 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_7:7 | 0.2783 | 0.0000 | 0.2783 | 0.2057 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_8:8 | 0.2766 | 0.0000 | 0.2766 | 0.2057 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_9:9 | 0.2737 | 0.0000 | 0.2737 | 0.2057 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_10:10 | 0.2805 | 0.0000 | 0.2805 | 0.2057 | 0.00 | 0.00 | 4030.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-AC_1:1 | 0.00 | 5091.82 | 593.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_2:2 | 0.00 | 4367.87 | 1003.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_3:3 | 0.00 | 4022.86 | 514.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_4:4 | 0.00 | 4038.66 | 495.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_5:5 | 0.00 | 4067.16 | 462.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_6:6 | 0.00 | 3794.53 | 328.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_7:7 | 0.00 | 3802.31 | 320.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_8:8 | 0.00 | 3810.94 | 310.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_9:9 | 0.00 | 3833.32 | 282.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_10:10 | 0.00 | 3834.60 | 272.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-AC_1:1 | 0.0000 | 0.5813 | 0.7801 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_2:2 | 0.0000 | 0.2761 | 0.3041 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_3:3 | 0.0000 | 0.2910 | 0.4274 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_4:4 | 0.0000 | 0.2890 | 0.4251 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_5:5 | 0.0000 | 0.2852 | 0.4249 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_6:6 | 0.0000 | 0.5363 | 0.7809 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_7:7 | 0.0000 | 0.2698 | 0.3976 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_8:8 | 0.0000 | 0.2685 | 0.3961 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_9:9 | 0.0000 | 0.2658 | 0.4023 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_10:10 | 0.0000 | 0.2708 | 0.4405 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:11
Surfaces by ClassTotal | Outdoors | |
Wall | 40 | 22 |
Floor | 10 | 10 |
Roof | 10 | 10 |
Internal Mass | 10 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 36 | 36 |
Door | 12 | 12 |
Glass Door | 12 | 12 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 10 |
Conditioned Zones | 10 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 830 |
Defaulted Fields | 823 |
Fields with Defaults | 2682 |
Autosized Fields | 184 |
Autosizable Fields | 458 |
Autocalculated Fields | 128 |
Autocalculatable Fields | 256 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:37:11
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 904.75 | 2102.83 | 01-JAN-07:20 | 88548.95 | 02-JUN-17:00 |
Electricity:Building | 494.83 | 891.83 | 01-JAN-00:20 | 31518.67 | 01-JAN-11:10 |
Electricity:Zone:LGSTORE1 | 113.36 | 148.64 | 01-JAN-00:20 | 5964.88 | 01-JAN-10:10 |
Electricity:SpaceType:GENERAL | 494.83 | 891.83 | 01-JAN-00:20 | 31518.67 | 01-JAN-11:10 |
InteriorLights:Electricity | 366.68 | 450.00 | 01-JAN-00:20 | 23459.17 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:LGSTORE1 | 87.12 | 75.00 | 01-JAN-00:20 | 4621.63 | 01-JAN-10:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 366.68 | 450.00 | 01-JAN-00:20 | 23459.17 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity | 366.68 | 450.00 | 01-JAN-00:20 | 23459.17 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:LGSTORE1 | 87.12 | 75.00 | 01-JAN-00:20 | 4621.63 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 366.68 | 450.00 | 01-JAN-00:20 | 23459.17 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE1 | 66.33 | 74.32 | 01-JAN-00:20 | 3498.69 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE1 | 53.20 | 37.50 | 01-JAN-00:20 | 2827.07 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE1 | 53.20 | 37.50 | 01-JAN-00:20 | 2827.07 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE2 | 47.99 | 74.32 | 01-JAN-00:10 | 3226.84 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE2 | 37.57 | 37.50 | 01-JAN-00:10 | 2555.22 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE2 | 37.57 | 37.50 | 01-JAN-00:10 | 2555.22 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE3 | 47.99 | 74.32 | 01-JAN-00:10 | 3226.84 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE3 | 37.57 | 37.50 | 01-JAN-00:10 | 2555.22 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE3 | 37.57 | 37.50 | 01-JAN-00:10 | 2555.22 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE4 | 47.99 | 74.32 | 01-JAN-00:10 | 3226.84 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE4 | 37.57 | 37.50 | 01-JAN-00:10 | 2555.22 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE4 | 37.57 | 37.50 | 01-JAN-00:10 | 2555.22 | 01-JAN-10:10 |
Electricity:Zone:LGSTORE2 | 56.34 | 148.64 | 01-JAN-00:10 | 4070.21 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:LGSTORE2 | 37.16 | 75.00 | 01-JAN-00:10 | 2726.96 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:LGSTORE2 | 37.16 | 75.00 | 01-JAN-00:10 | 2726.96 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE5 | 28.71 | 74.32 | 01-JAN-00:10 | 2076.09 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE5 | 19.12 | 37.50 | 01-JAN-00:10 | 1404.46 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE5 | 19.12 | 37.50 | 01-JAN-00:10 | 1404.46 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE6 | 28.71 | 74.32 | 01-JAN-00:10 | 2076.09 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE6 | 19.12 | 37.50 | 01-JAN-00:10 | 1404.46 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE6 | 19.12 | 37.50 | 01-JAN-00:10 | 1404.46 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE7 | 28.71 | 74.32 | 01-JAN-00:10 | 2076.09 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE7 | 19.12 | 37.50 | 01-JAN-00:10 | 1404.46 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE7 | 19.12 | 37.50 | 01-JAN-00:10 | 1404.46 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE8 | 28.71 | 74.32 | 01-JAN-00:10 | 2076.09 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE8 | 19.12 | 37.50 | 01-JAN-00:10 | 1404.46 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE8 | 19.12 | 37.50 | 01-JAN-00:10 | 1404.46 | 01-JAN-11:10 |
InteriorEquipment:Electricity | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:LGSTORE1 | 26.25 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-10:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LGSTORE1 | 26.25 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE1 | 13.12 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE1 | 13.12 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE2 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE2 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE3 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE3 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE4 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE4 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:LGSTORE2 | 19.17 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LGSTORE2 | 19.17 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE5 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE5 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE6 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE6 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE7 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE7 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE8 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE8 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
ElectricityPurchased:Facility | 904.75 | 2102.83 | 01-JAN-07:20 | 88548.95 | 02-JUN-17:00 |
ElectricityPurchased:Plant | 904.75 | 2102.83 | 01-JAN-07:20 | 88548.95 | 02-JUN-17:00 |
Cogeneration:ElectricityPurchased | 904.75 | 2102.83 | 01-JAN-07:20 | 88548.95 | 02-JUN-17:00 |
General:Cogeneration:ElectricityPurchased | 904.75 | 2102.83 | 01-JAN-07:20 | 88548.95 | 02-JUN-17:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 904.75 | 2102.83 | 01-JAN-07:20 | 88548.95 | 02-JUN-17:00 |
ElectricityNet:Plant | 904.75 | 2102.83 | 01-JAN-07:20 | 88548.95 | 02-JUN-17:00 |
Cogeneration:ElectricityNet | 904.75 | 2102.83 | 01-JAN-07:20 | 88548.95 | 02-JUN-17:00 |
General:Cogeneration:ElectricityNet | 904.75 | 2102.83 | 01-JAN-07:20 | 88548.95 | 02-JUN-17:00 |
Electricity:HVAC | 288.42 | 0.00 | 01-JAN-00:10 | 50263.85 | 15-JUN-15:00 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 177.71 | 0.00 | 01-JAN-00:10 | 42459.82 | 02-JUN-16:20 |
General:Cooling:Electricity | 177.71 | 0.00 | 01-JAN-00:10 | 42459.82 | 02-JUN-16:20 |
Fans:Electricity | 110.71 | 0.00 | 01-JAN-00:10 | 8786.70 | 27-DEC-08:10 |
General:Fans:Electricity | 110.71 | 0.00 | 01-JAN-00:10 | 8786.70 | 27-DEC-08:10 |
ExteriorLights:Electricity | 60.06 | 0.00 | 01-JAN-07:20 | 5507.06 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 60.06 | 0.00 | 01-JAN-07:20 | 5507.06 | 01-JAN-06:10 |
Electricity:Plant | 61.44 | 1211.00 | 02-JAN-08:10 | 11810.58 | 05-JAN-12:40 |
WaterSystems:Electricity | 61.44 | 1211.00 | 02-JAN-08:10 | 11810.58 | 05-JAN-12:40 |
Water Heater:WaterSystems:Electricity | 61.44 | 1211.00 | 02-JAN-08:10 | 11810.58 | 05-JAN-12:40 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 60.23 | 0.00 | 01-JAN-00:10 | 115995.83 | 27-DEC-08:10 |
NaturalGas:HVAC | 60.23 | 0.00 | 01-JAN-00:10 | 115995.83 | 27-DEC-08:10 |
Heating:NaturalGas | 60.23 | 0.00 | 01-JAN-00:10 | 115995.83 | 27-DEC-08:10 |
General:Heating:NaturalGas | 60.23 | 0.00 | 01-JAN-00:10 | 115995.83 | 27-DEC-08:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water:Plant | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
WaterSystems:Water | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water Heater:WaterSystems:Water | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
MainsWater:Facility | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
MainsWater:Plant | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
WaterSystems:MainsWater | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water Heater:WaterSystems:MainsWater | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 1305.65 | 0.00 | 01-JAN-00:10 | 238167.63 | 03-JUL-14:10 |
EnergyTransfer:Building | 599.65 | 0.00 | 01-JAN-00:10 | 98004.03 | 03-JUL-13:00 |
EnergyTransfer:Zone:LGSTORE1 | 127.76 | 0.00 | 01-JAN-00:10 | 16725.87 | 07-AUG-16:10 |
Heating:EnergyTransfer | 18.17 | 0.00 | 01-JAN-00:10 | 82436.93 | 27-DEC-08:10 |
Heating:EnergyTransfer:Zone:LGSTORE1 | 2.01 | 0.00 | 01-JAN-00:10 | 15737.34 | 03-FEB-08:10 |
General:Heating:EnergyTransfer | 18.17 | 0.00 | 01-JAN-00:10 | 82436.93 | 27-DEC-08:10 |
General:Heating:EnergyTransfer:Zone:LGSTORE1 | 2.01 | 0.00 | 01-JAN-00:10 | 15737.34 | 03-FEB-08:10 |
Cooling:EnergyTransfer | 581.48 | 0.00 | 01-JAN-00:10 | 98004.03 | 03-JUL-13:00 |
Cooling:EnergyTransfer:Zone:LGSTORE1 | 125.75 | 0.00 | 01-JAN-00:10 | 16725.87 | 07-AUG-16:10 |
General:Cooling:EnergyTransfer | 581.48 | 0.00 | 01-JAN-00:10 | 98004.03 | 03-JUL-13:00 |
General:Cooling:EnergyTransfer:Zone:LGSTORE1 | 125.75 | 0.00 | 01-JAN-00:10 | 16725.87 | 07-AUG-16:10 |
EnergyTransfer:Zone:SMSTORE1 | 68.66 | 0.00 | 01-JAN-00:10 | 9436.93 | 20-APR-22:00 |
Heating:EnergyTransfer:Zone:SMSTORE1 | 0.48 | 0.00 | 01-JAN-00:10 | 4419.03 | 03-FEB-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE1 | 0.48 | 0.00 | 01-JAN-00:10 | 4419.03 | 03-FEB-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE1 | 68.18 | 0.00 | 01-JAN-00:10 | 9436.93 | 20-APR-22:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE1 | 68.18 | 0.00 | 01-JAN-00:10 | 9436.93 | 20-APR-22:00 |
EnergyTransfer:Zone:SMSTORE2 | 52.06 | 0.00 | 01-JAN-00:10 | 8336.03 | 03-JUL-13:00 |
Heating:EnergyTransfer:Zone:SMSTORE2 | 1.21 | 0.00 | 01-JAN-00:10 | 5525.04 | 28-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE2 | 1.21 | 0.00 | 01-JAN-00:10 | 5525.04 | 28-JAN-07:10 |
Cooling:EnergyTransfer:Zone:SMSTORE2 | 50.85 | 0.00 | 01-JAN-00:10 | 8336.03 | 03-JUL-13:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE2 | 50.85 | 0.00 | 01-JAN-00:10 | 8336.03 | 03-JUL-13:00 |
EnergyTransfer:Zone:SMSTORE3 | 51.60 | 0.00 | 01-JAN-00:10 | 8418.97 | 03-JUL-13:00 |
Heating:EnergyTransfer:Zone:SMSTORE3 | 1.32 | 0.00 | 01-JAN-00:10 | 5809.86 | 27-DEC-07:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE3 | 1.32 | 0.00 | 01-JAN-00:10 | 5809.86 | 27-DEC-07:10 |
Cooling:EnergyTransfer:Zone:SMSTORE3 | 50.28 | 0.00 | 01-JAN-00:10 | 8418.97 | 03-JUL-13:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE3 | 50.28 | 0.00 | 01-JAN-00:10 | 8418.97 | 03-JUL-13:00 |
EnergyTransfer:Zone:SMSTORE4 | 49.40 | 0.00 | 01-JAN-00:10 | 8326.31 | 03-JUL-13:00 |
Heating:EnergyTransfer:Zone:SMSTORE4 | 1.53 | 0.00 | 01-JAN-00:10 | 6526.15 | 27-DEC-07:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE4 | 1.53 | 0.00 | 01-JAN-00:10 | 6526.15 | 27-DEC-07:10 |
Cooling:EnergyTransfer:Zone:SMSTORE4 | 47.87 | 0.00 | 01-JAN-00:10 | 8326.31 | 03-JUL-13:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE4 | 47.87 | 0.00 | 01-JAN-00:10 | 8326.31 | 03-JUL-13:00 |
EnergyTransfer:Zone:LGSTORE2 | 81.57 | 0.00 | 01-JAN-00:10 | 15927.43 | 27-DEC-08:10 |
Heating:EnergyTransfer:Zone:LGSTORE2 | 2.62 | 0.00 | 01-JAN-00:10 | 15927.43 | 27-DEC-08:10 |
General:Heating:EnergyTransfer:Zone:LGSTORE2 | 2.62 | 0.00 | 01-JAN-00:10 | 15927.43 | 27-DEC-08:10 |
Cooling:EnergyTransfer:Zone:LGSTORE2 | 78.95 | 0.00 | 01-JAN-00:10 | 15415.52 | 03-JUL-13:00 |
General:Cooling:EnergyTransfer:Zone:LGSTORE2 | 78.95 | 0.00 | 01-JAN-00:10 | 15415.52 | 03-JUL-13:00 |
EnergyTransfer:Zone:SMSTORE5 | 41.60 | 0.00 | 01-JAN-00:10 | 8268.28 | 27-DEC-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE5 | 1.50 | 0.00 | 01-JAN-00:10 | 8268.28 | 27-DEC-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE5 | 1.50 | 0.00 | 01-JAN-00:10 | 8268.28 | 27-DEC-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE5 | 40.10 | 0.00 | 01-JAN-00:10 | 8098.18 | 03-JUL-14:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE5 | 40.10 | 0.00 | 01-JAN-00:10 | 8098.18 | 03-JUL-14:10 |
EnergyTransfer:Zone:SMSTORE6 | 41.06 | 0.00 | 01-JAN-00:10 | 8456.15 | 27-DEC-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE6 | 1.61 | 0.00 | 01-JAN-00:10 | 8456.15 | 27-DEC-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE6 | 1.61 | 0.00 | 01-JAN-00:10 | 8456.15 | 27-DEC-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE6 | 39.45 | 0.00 | 01-JAN-00:10 | 8069.64 | 03-JUL-14:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE6 | 39.45 | 0.00 | 01-JAN-00:10 | 8069.64 | 03-JUL-14:10 |
EnergyTransfer:Zone:SMSTORE7 | 40.25 | 0.00 | 01-JAN-00:10 | 9485.86 | 27-DEC-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE7 | 2.02 | 0.00 | 01-JAN-00:10 | 9485.86 | 27-DEC-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE7 | 2.02 | 0.00 | 01-JAN-00:10 | 9485.86 | 27-DEC-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE7 | 38.22 | 0.00 | 01-JAN-00:10 | 8135.45 | 03-JUL-13:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE7 | 38.22 | 0.00 | 01-JAN-00:10 | 8135.45 | 03-JUL-13:00 |
EnergyTransfer:Zone:SMSTORE8 | 45.69 | 0.00 | 01-JAN-00:10 | 13895.14 | 02-MAR-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE8 | 3.87 | 0.00 | 01-JAN-00:10 | 13895.14 | 02-MAR-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE8 | 3.87 | 0.00 | 01-JAN-00:10 | 13895.14 | 02-MAR-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE8 | 41.82 | 0.00 | 01-JAN-00:10 | 9678.61 | 03-JUL-12:50 |
General:Cooling:EnergyTransfer:Zone:SMSTORE8 | 41.82 | 0.00 | 01-JAN-00:10 | 9678.61 | 03-JUL-12:50 |
EnergyTransfer:HVAC | 706.00 | 0.00 | 01-JAN-00:10 | 142956.24 | 26-JUL-14:10 |
HeatingCoils:EnergyTransfer | 48.19 | 0.00 | 01-JAN-00:10 | 92796.67 | 27-DEC-08:10 |
CoolingCoils:EnergyTransfer | 657.81 | 0.00 | 01-JAN-00:10 | 142956.24 | 26-JUL-14:10 |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:11
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
LGSTORE1 | 0.000 | 0.000 | 2.009 | -125.752 | 0.000 | 0.000 | 24.102 | 87.116 | 26.249 | 21.627 | 0.000 | 7.115 | 0.000 | 0.000 | -7.337 | 0.000 | -12.881 | -22.248 |
SMSTORE1 | 0.000 | 0.000 | 0.482 | -68.181 | 0.000 | 0.000 | 11.888 | 53.201 | 13.125 | 10.743 | 0.000 | 3.828 | 0.000 | 0.000 | -3.839 | 0.000 | -6.290 | -14.957 |
SMSTORE2 | 0.000 | 0.000 | 1.213 | -50.846 | 0.000 | 0.000 | 7.208 | 37.572 | 10.421 | 10.694 | 0.000 | 3.770 | 0.001 | 0.000 | -3.855 | 0.000 | -6.430 | -9.747 |
SMSTORE3 | 0.000 | 0.000 | 1.319 | -50.280 | 0.000 | 0.000 | 7.221 | 37.572 | 10.421 | 10.705 | 0.000 | 3.769 | 0.002 | 0.000 | -3.821 | 0.000 | -6.376 | -10.529 |
SMSTORE4 | 0.000 | 0.000 | 1.528 | -47.870 | 0.000 | 0.000 | 7.241 | 37.572 | 10.421 | 10.732 | 0.000 | 3.772 | 0.000 | 0.000 | -3.765 | 0.000 | -6.290 | -13.341 |
LGSTORE2 | 0.000 | 0.000 | 2.617 | -78.950 | 0.000 | 0.000 | 24.931 | 37.162 | 19.173 | 21.564 | 0.000 | 6.825 | 0.002 | 0.000 | -7.261 | 0.000 | -11.475 | -14.586 |
SMSTORE5 | 0.000 | 0.000 | 1.505 | -40.098 | 0.000 | 0.000 | 12.475 | 19.120 | 9.586 | 10.782 | 0.000 | 3.791 | 0.001 | 0.000 | -3.612 | 0.000 | -6.204 | -7.347 |
SMSTORE6 | 0.000 | 0.000 | 1.606 | -39.452 | 0.000 | 0.000 | 12.486 | 19.120 | 9.586 | 10.793 | 0.000 | 3.792 | 0.000 | 0.000 | -3.592 | 0.000 | -6.175 | -8.165 |
SMSTORE7 | 0.000 | 0.000 | 2.022 | -38.223 | 0.000 | 0.000 | 12.514 | 19.120 | 9.586 | 10.815 | 0.000 | 3.793 | 0.001 | 0.000 | -3.541 | 0.000 | -6.097 | -9.990 |
SMSTORE8 | 0.000 | 0.000 | 3.865 | -41.821 | 0.000 | 0.000 | 12.545 | 19.120 | 9.586 | 10.828 | 0.000 | 4.034 | 0.001 | 0.000 | -3.370 | 0.000 | -7.959 | -6.829 |
Total Facility | 0.000 | 0.000 | 18.167 | -581.473 | 0.000 | 0.000 | 132.612 | 366.677 | 128.154 | 129.283 | 0.000 | 44.488 | 0.009 | 0.000 | -43.992 | 0.000 | -76.177 | -117.739 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
LGSTORE1 | 02-OCT-07:02 | 0.00 | 0.00 | 0.00 | -40233.18 | 0.00 | 0.00 | 172.43 | 75.00 | 74.62 | 0.00 | 0.00 | 0.00 | 40097.93 | 0.00 | -83.79 | 0.00 | -103.02 | 0.00 |
SMSTORE1 | 02-OCT-07:02 | 0.00 | 0.00 | 0.00 | -20804.23 | 0.00 | 0.00 | 85.63 | 37.50 | 37.31 | 0.00 | 0.00 | 0.00 | 20739.45 | 0.00 | -42.59 | 0.00 | -53.07 | 0.00 |
SMSTORE2 | 06-JUN-06:02 | 0.00 | 0.00 | 0.00 | -22730.65 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 0.00 | 0.00 | 0.00 | 22674.26 | 0.00 | -12.38 | 0.00 | -5.55 | 0.00 |
SMSTORE3 | 23-AUG-06:02 | 0.00 | 0.00 | 0.00 | -23056.56 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 0.00 | 0.00 | 0.00 | 23082.98 | 0.00 | -91.67 | 0.00 | -9.07 | 0.00 |
SMSTORE4 | 06-JUN-06:02 | 0.00 | 0.00 | 0.00 | -22542.51 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 0.00 | 0.00 | 0.00 | 22485.09 | 0.00 | -11.54 | 0.00 | -5.35 | 0.00 |
LGSTORE2 | 02-OCT-07:02 | 0.00 | 0.00 | 0.00 | -37749.13 | 0.00 | 0.00 | 0.00 | 75.00 | 73.64 | 0.00 | 0.00 | 0.00 | 37787.94 | 0.00 | -86.69 | 0.00 | -100.76 | 0.00 |
SMSTORE5 | 02-OCT-07:02 | 0.00 | 0.00 | 0.00 | -19499.75 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 0.00 | 0.00 | 0.00 | 19522.46 | 0.00 | -42.74 | 0.00 | -54.29 | 0.00 |
SMSTORE6 | 02-OCT-07:02 | 0.00 | 0.00 | 0.00 | -19368.08 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 0.00 | 0.00 | 0.00 | 19389.89 | 0.00 | -42.24 | 0.00 | -53.89 | 0.00 |
SMSTORE7 | 02-OCT-07:02 | 0.00 | 0.00 | 0.00 | -19340.90 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 0.00 | 0.00 | 0.00 | 19361.33 | 0.00 | -41.88 | 0.00 | -52.87 | 0.00 |
SMSTORE8 | 02-OCT-07:02 | 0.00 | 0.00 | 0.00 | -21169.25 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 0.00 | 0.00 | 0.00 | 21198.03 | 0.00 | -43.34 | 0.00 | -59.75 | 0.00 |
Total Facility | 03-JUL-07:01 | 0.00 | 0.00 | 0.00 | -186495.16 | 0.00 | 0.00 | 539.40 | 450.00 | 1452.23 | 2136.89 | 0.00 | 712.93 | 181203.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
LGSTORE1 | 19-DEC-08:61 | 0.00 | 0.00 | 58967.67 | 0.00 | 0.00 | 0.00 | 250.91 | 75.00 | 74.62 | 229.86 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -821.31 | -58776.75 |
SMSTORE1 | 02-MAR-08:61 | 0.00 | 0.00 | 30535.33 | 0.00 | 0.00 | 0.00 | 122.86 | 37.50 | 37.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -212.56 | 0.00 | -485.23 | -30035.22 |
SMSTORE2 | 31-DEC-08:61 | 0.00 | 0.00 | 30660.67 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 37.31 | 399.41 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -499.07 | -30635.83 |
SMSTORE3 | 31-DEC-08:61 | 0.00 | 0.00 | 30530.89 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 37.31 | 404.25 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -493.70 | -30516.26 |
SMSTORE4 | 31-DEC-08:61 | 0.00 | 0.00 | 30503.78 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 37.31 | 408.59 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -488.46 | -30498.72 |
LGSTORE2 | 19-DEC-08:61 | 0.00 | 0.00 | 55162.68 | 0.00 | 0.00 | 0.00 | 0.00 | 75.00 | 73.64 | 237.36 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -811.21 | -54737.46 |
SMSTORE5 | 19-DEC-08:61 | 0.00 | 0.00 | 28481.35 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 120.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -452.06 | -28223.62 |
SMSTORE6 | 19-DEC-08:61 | 0.00 | 0.00 | 28378.76 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 121.85 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -450.25 | -28124.67 |
SMSTORE7 | 19-DEC-08:61 | 0.00 | 0.00 | 28415.26 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 128.73 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -443.03 | -28175.28 |
SMSTORE8 | 19-DEC-08:61 | 0.00 | 0.00 | 31423.34 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 156.17 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -416.82 | -31237.01 |
Total Facility | 27-DEC-08:61 | 0.00 | 0.00 | 268484.59 | 0.00 | 0.00 | 0.00 | 730.42 | 450.00 | 1452.23 | 2321.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -6021.74 | -267416.75 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:11
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 2.3936 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 2.3936 | 0.1719 | 1.0000 | Not calculated | 0.4115 | 0.1719 | ||
PSZ-AC_2:2 | 1.2500 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.2500 | 0.1646 | 1.0000 | Not calculated | 0.2057 | 0.1646 | ||
PSZ-AC_3:3 | 1.2849 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.2849 | 0.1601 | 1.0000 | Not calculated | 0.2057 | 0.1601 | ||
PSZ-AC_4:4 | 1.2778 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.2778 | 0.1610 | 1.0000 | Not calculated | 0.2057 | 0.1610 | ||
PSZ-AC_5:5 | 1.2763 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.2763 | 0.1612 | 1.0000 | Not calculated | 0.2057 | 0.1612 | ||
PSZ-AC_6:6 | 2.1950 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 2.1950 | 0.1875 | 1.0000 | Not calculated | 0.4115 | 0.1875 | ||
PSZ-AC_7:7 | 1.1420 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.1420 | 0.1802 | 1.0000 | Not calculated | 0.2057 | 0.1802 | ||
PSZ-AC_8:8 | 1.1368 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.1368 | 0.1810 | 1.0000 | Not calculated | 0.2057 | 0.1810 | ||
PSZ-AC_9:9 | 1.1384 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.1384 | 0.1807 | 1.0000 | Not calculated | 0.2057 | 0.1807 | ||
PSZ-AC_10:10 | 1.2951 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.2951 | 0.1589 | 1.0000 | Not calculated | 0.2057 | 0.1589 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 2.3936 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 2.3936 | 1.0000 | 1.0000 | Not calculated | 0.4115 | 0.1719 | ||
PSZ-AC_2:2 | 1.2500 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.2500 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1646 | ||
PSZ-AC_3:3 | 1.2849 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.2849 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1601 | ||
PSZ-AC_4:4 | 1.2778 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.2778 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1610 | ||
PSZ-AC_5:5 | 1.2763 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.2763 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1612 | ||
PSZ-AC_6:6 | 2.1950 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 2.1950 | 1.0000 | 1.0000 | Not calculated | 0.4115 | 0.1875 | ||
PSZ-AC_7:7 | 1.1420 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.1420 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1802 | ||
PSZ-AC_8:8 | 1.1368 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.1368 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1810 | ||
PSZ-AC_9:9 | 1.1384 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.1384 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1807 | ||
PSZ-AC_10:10 | 1.2951 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.2951 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1589 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
LGSTORE1 | PSZ-AC_1:1 | 0.000000 | 56.2505 | 0.001181 | 348.39 | 0.4115 | 1.0000 | 0.4115 | 1.000 | 0.4115 |
SMSTORE1 | PSZ-AC_2:2 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE2 | PSZ-AC_3:3 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE3 | PSZ-AC_4:4 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE4 | PSZ-AC_5:5 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
LGSTORE2 | PSZ-AC_6:6 | 0.000000 | 56.2505 | 0.001181 | 348.39 | 0.4115 | 1.0000 | 0.4115 | 1.000 | 0.4115 |
SMSTORE5 | PSZ-AC_7:7 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE6 | PSZ-AC_8:8 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE7 | PSZ-AC_9:9 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE8 | PSZ-AC_10:10 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC_1:1 | 0.000000 | 56.25 | 0.001181 | 348.3864 | 0.4115 | 0.4115 | 0.4115 |
PSZ-AC_2:2 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_3:3 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_4:4 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_5:5 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_6:6 | 0.000000 | 56.25 | 0.001181 | 348.3864 | 0.4115 | 0.4115 | 0.4115 |
PSZ-AC_7:7 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_8:8 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_9:9 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_10:10 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LGSTORE1 | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.3936 | 2.3936 | 2.3936 | No | 0.4115 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE1 | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2500 | 1.2500 | 1.2500 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE2 | PSZ-AC_3:3 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2849 | 1.2849 | 1.2849 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE3 | PSZ-AC_4:4 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2778 | 1.2778 | 1.2778 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE4 | PSZ-AC_5:5 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2763 | 1.2763 | 1.2763 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LGSTORE2 | PSZ-AC_6:6 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.1950 | 2.1950 | 2.1950 | No | 0.4115 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE5 | PSZ-AC_7:7 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1420 | 1.1420 | 1.1420 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE6 | PSZ-AC_8:8 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1368 | 1.1368 | 1.1368 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE7 | PSZ-AC_9:9 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1384 | 1.1384 | 1.1384 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE8 | PSZ-AC_10:10 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2951 | 1.2951 | 1.2951 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 2.3936 | 2.3936 | 2.3936 | 2.3936 | 0.4115 | 1.0000 |
PSZ-AC_2:2 | 1.2500 | 1.2500 | 1.2500 | 1.2500 | 0.2057 | 1.0000 |
PSZ-AC_3:3 | 1.2849 | 1.2849 | 1.2849 | 1.2849 | 0.2057 | 1.0000 |
PSZ-AC_4:4 | 1.2778 | 1.2778 | 1.2778 | 1.2778 | 0.2057 | 1.0000 |
PSZ-AC_5:5 | 1.2763 | 1.2763 | 1.2763 | 1.2763 | 0.2057 | 1.0000 |
PSZ-AC_6:6 | 2.1950 | 2.1950 | 2.1950 | 2.1950 | 0.4115 | 1.0000 |
PSZ-AC_7:7 | 1.1420 | 1.1420 | 1.1420 | 1.1420 | 0.2057 | 1.0000 |
PSZ-AC_8:8 | 1.1368 | 1.1368 | 1.1368 | 1.1368 | 0.2057 | 1.0000 |
PSZ-AC_9:9 | 1.1384 | 1.1384 | 1.1384 | 1.1384 | 0.2057 | 1.0000 |
PSZ-AC_10:10 | 1.2951 | 1.2951 | 1.2951 | 1.2951 | 0.2057 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LGSTORE1 | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.3936 | 2.3936 | 2.3936 | No | 0.4115 | 0.3724 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE1 | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2500 | 1.2500 | 1.2500 | No | 0.2057 | 0.3963 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE2 | PSZ-AC_3:3 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2849 | 1.2849 | 1.2849 | No | 0.2057 | 0.3909 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE3 | PSZ-AC_4:4 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2778 | 1.2778 | 1.2778 | No | 0.2057 | 0.3865 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE4 | PSZ-AC_5:5 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2763 | 1.2763 | 1.2763 | No | 0.2057 | 0.3789 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LGSTORE2 | PSZ-AC_6:6 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.1950 | 2.1950 | 2.1950 | No | 0.4115 | 0.3891 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE5 | PSZ-AC_7:7 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1420 | 1.1420 | 1.1420 | No | 0.2057 | 0.3663 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE6 | PSZ-AC_8:8 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1368 | 1.1368 | 1.1368 | No | 0.2057 | 0.3665 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE7 | PSZ-AC_9:9 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1384 | 1.1384 | 1.1384 | No | 0.2057 | 0.3563 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE8 | PSZ-AC_10:10 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2951 | 1.2951 | 1.2951 | No | 0.2057 | 0.2953 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 2.3936 | 2.3936 | 2.3936 | 2.3936 | 0.4115 | 1.0000 |
PSZ-AC_2:2 | 1.2500 | 1.2500 | 1.2500 | 1.2500 | 0.2057 | 1.0000 |
PSZ-AC_3:3 | 1.2849 | 1.2849 | 1.2849 | 1.2849 | 0.2057 | 1.0000 |
PSZ-AC_4:4 | 1.2778 | 1.2778 | 1.2778 | 1.2778 | 0.2057 | 1.0000 |
PSZ-AC_5:5 | 1.2763 | 1.2763 | 1.2763 | 1.2763 | 0.2057 | 1.0000 |
PSZ-AC_6:6 | 2.1950 | 2.1950 | 2.1950 | 2.1950 | 0.4115 | 1.0000 |
PSZ-AC_7:7 | 1.1420 | 1.1420 | 1.1420 | 1.1420 | 0.2057 | 1.0000 |
PSZ-AC_8:8 | 1.1368 | 1.1368 | 1.1368 | 1.1368 | 0.2057 | 1.0000 |
PSZ-AC_9:9 | 1.1384 | 1.1384 | 1.1384 | 1.1384 | 0.2057 | 1.0000 |
PSZ-AC_10:10 | 1.2951 | 1.2951 | 1.2951 | 1.2951 | 0.2057 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:11
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** El Paso International Ap Ut TX USA TMY3 WMO#=722700 |
Total gross floor area [m2] | 2090.32 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
LGSTORE1 | 348.39 | 348.39 | 0.00 | 112.00 |
SMSTORE1 | 174.19 | 174.19 | 0.00 | 112.00 |
SMSTORE2 | 174.19 | 174.19 | 0.00 | 84.29 |
SMSTORE3 | 174.19 | 174.19 | 0.00 | 84.29 |
SMSTORE4 | 174.19 | 174.19 | 0.00 | 84.29 |
LGSTORE2 | 348.39 | 348.39 | 0.00 | 77.29 |
SMSTORE5 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE6 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE7 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE8 | 174.19 | 174.19 | 0.00 | 77.29 |
Totals | 2090.32 | 2090.32 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 0.00 |
Number of hours not met | 0.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 60.23 | 115995.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 177.71 | 42459.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 366.68 | 23459.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 60.06 | 5507.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 128.15 | 8059.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 110.71 | 8786.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 61.44 | 11810.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 128.15 | 904.75 |
Natural Gas | 0.00 | 60.23 |
Additional | 0.00 | 0.00 |
Total | 128.15 | 964.99 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 175.42 |
Space Heating | 0.00 |
Space Cooling | 85.02 |
Fans (All) | 52.96 |
Service Water Heating | 29.39 |
Receptacle Equipment | 61.31 |
Miscellaneous (All) | 432.83 |
Subtotal | 432.83 |
Natural Gas [MJ/m2] | |
Space Heating | 28.82 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 28.82 |
Subtotal | 28.82 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 38.00 |
Space Heating | 6.24 |
Space Cooling | 18.42 |
Fans (All) | 11.47 |
Service Water Heating | 6.37 |
Receptacle Equipment | 13.28 |
Miscellaneous | 6.22 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
TYPE1_OCC_SCH | 1630. | 5840. |
TYPE2_OCC_SCH | 995. | 4429. |
TYPE3_OCC_SCH | 1709. | 4064. |
LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 3767. | 8760. |
LTG_SCH_BASE_LPD2 | 3238. | 8760. |
LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 3296. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | 5084. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | 5084. | 8760. |
LTG_SCH_BASE_SMALL_LPD1 | 4453. | 8760. |
LTG_SCH_BASE_LPD1 | 4376. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | 3767. | 8760. |
LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 3584. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 4096. | 8760. |
TYPE1_EQUIP_SCH | 4868. | 8760. |
TYPE2_EQUIP_SCH | 3893. | 8760. |
TYPE3_EQUIP_SCH | 3584. | 8760. |
TYPE1_INFIL_SCH | 4302. | 8760. |
TYPE2_INFIL_SCH | 5164. | 8760. |
TYPE3_INFIL_SCH | 5438. | 8760. |
INFIL_DOOR_OPENING_SCH | 2477. | 4380. |
TYPE1_MINOA_MOTORIZEDDAMPER_SCH | 5579. | 5579. |
TYPE2_MINOA_MOTORIZEDDAMPER_SCH | 4429. | 4429. |
TYPE3_MINOA_MOTORIZEDDAMPER_SCH | 4064. | 4064. |
TYPE1_SWH_SCH | 2063. | 6048. |
TYPE2_SWH_SCH | 1831. | 4429. |
TYPE3_SWH_SCH | 1733. | 4064. |
AVERAGE_SWH_SCH | 1863. | 6152. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 7118. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 5839. | 5839. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 7300. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6570. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
TYPE1_HTGSETP_SCH_NO_OPTIMUM | LGSTORE1 DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
TYPE1_CLGSETP_SCH_NO_OPTIMUM | LGSTORE1 DUAL SP CONTROL | July | 23.89 | 365 | 23.89 | 365 |
TYPE2_HTGSETP_SCH_NO_OPTIMUM | SMSTORE2 DUAL SP CONTROL | January | 21.11 | 365 | 15.56 | 365 |
TYPE2_CLGSETP_SCH_NO_OPTIMUM | SMSTORE2 DUAL SP CONTROL | July | 23.89 | 365 | 29.44 | 365 |
TYPE3_HTGSETP_SCH_NO_OPTIMUM | LGSTORE2 DUAL SP CONTROL | January | 21.11 | 365 | 15.56 | 365 |
TYPE3_CLGSETP_SCH_NO_OPTIMUM | LGSTORE2 DUAL SP CONTROL | July | 23.89 | 365 | 29.44 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:11
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
LGSTORE1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 8670.83 | 89.17 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 8658.17 | 101.83 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 8678.67 | 81.33 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 8709.83 | 50.17 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 8719.83 | 40.17 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 8721.00 | 39.00 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 8721.17 | 38.83 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 8676.67 | 83.33 | 0.00 | 0.00 | 0.00 |
Min | 8658.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 101.83 | 0.00 | 0.00 | 0.00 |
Average | 8707.62 | 52.38 | 0.00 | 0.00 | 0.00 |
Sum | 87076.17 | 523.83 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
LGSTORE1 | 89041.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 43777.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 25442.50 | 32.50 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 25442.33 | 32.67 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 25445.33 | 29.67 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 93114.00 | 97.00 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 45865.50 | 46.50 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 45866.00 | 46.00 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 45866.00 | 46.00 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 45856.00 | 56.00 | 0.00 | 0.00 | 0.00 |
Min | 25442.33 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 93114.00 | 97.00 | 0.00 | 0.00 | 0.00 |
Average | 48571.57 | 38.63 | 0.00 | 0.00 | 0.00 |
Sum | 485715.67 | 386.33 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
LGSTORE1 | 8549.50 | 210.50 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 8733.67 | 26.33 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 8406.33 | 353.67 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 8386.17 | 373.83 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 8430.00 | 330.00 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 8494.17 | 265.83 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 8502.00 | 258.00 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 8504.17 | 255.83 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 8509.50 | 250.50 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 8465.00 | 295.00 | 0.00 | 0.00 | 0.00 |
Min | 8386.17 | 26.33 | 0.00 | 0.00 | 0.00 |
Max | 8733.67 | 373.83 | 0.00 | 0.00 | 0.00 |
Average | 8498.05 | 261.95 | 0.00 | 0.00 | 0.00 |
Sum | 84980.50 | 2619.50 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
LGSTORE1 | 88909.17 | 131.83 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 43742.17 | 34.83 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 25410.17 | 64.83 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 25411.00 | 64.00 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 25408.67 | 66.33 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 92942.67 | 268.33 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 45775.50 | 136.50 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 45773.50 | 138.50 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 45770.50 | 141.50 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 45777.67 | 134.33 | 0.00 | 0.00 | 0.00 |
Min | 25408.67 | 34.83 | 0.00 | 0.00 | 0.00 |
Max | 92942.67 | 268.33 | 0.00 | 0.00 | 0.00 |
Average | 48492.10 | 118.10 | 0.00 | 0.00 | 0.00 |
Sum | 484921.00 | 1181.00 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:11
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:11
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
For: Environment
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTRIPMALL
For: Environment
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3B
For: Environment
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_TX_ELPASO
For: Environment
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: ZoneCoolingSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.464752E+10 | 7720.11 | 28-JAN-00:12 | -0.4 | -4.2 | 0.115018E+10 | 1641.89 | 13-JAN-13:00 | -0.4 | -4.2 |
February | 0.427113E+10 | 7569.40 | 03-FEB-00:03 | 0.00 | -4.1 | 0.111200E+10 | 1685.85 | 19-FEB-18:30 | 20.00 | 7.15 |
March | 0.510093E+10 | 6508.74 | 16-MAR-17:10 | 20.92 | 7.82 | 0.130941E+10 | 1685.85 | 26-MAR-16:19 | 22.40 | 8.95 |
April | 0.879553E+10 | 11876.36 | 30-APR-16:04 | 30.50 | 12.87 | 0.135355E+10 | 1685.86 | 29-APR-12:00 | 30.50 | 12.87 |
May | 0.129344E+11 | 27077.75 | 31-MAY-07:03 | 25.37 | 12.75 | 0.140125E+10 | 1685.95 | 21-MAY-17:00 | 25.37 | 12.75 |
June | 0.162926E+11 | 38504.07 | 06-JUN-07:02 | 24.78 | 13.82 | 0.135457E+10 | 1685.95 | 23-JUN-12:09 | 27.57 | 16.83 |
July | 0.174975E+11 | 39464.08 | 03-JUL-07:01 | 27.98 | 16.41 | 0.141288E+10 | 1686.00 | 08-JUL-12:09 | 28.68 | 20.13 |
August | 0.171724E+11 | 38258.13 | 07-AUG-07:01 | 26.47 | 16.94 | 0.139412E+10 | 1685.98 | 18-AUG-12:30 | 26.95 | 18.05 |
September | 0.158085E+11 | 32996.71 | 13-SEP-07:02 | 22.88 | 17.65 | 0.136517E+10 | 1686.01 | 08-SEP-12:09 | 22.88 | 17.65 |
October | 0.118648E+11 | 40228.53 | 02-OCT-07:02 | 22.02 | 15.21 | 0.140755E+10 | 1686.01 | 08-OCT-17:00 | 23.90 | 16.81 |
November | 0.682343E+10 | 9233.45 | 09-NOV-15:00 | 23.30 | 12.64 | 0.127781E+10 | 1685.92 | 03-NOV-12:00 | 23.30 | 12.64 |
December | 0.454457E+10 | 7609.05 | 30-DEC-00:12 | 0.00 | -2.4 | 0.113613E+10 | 1676.81 | 10-DEC-13:00 | 0.00 | -2.4 |
Annual Sum or Average | 0.125753E+12 | 0.156746E+11 | ||||||||
Minimum of Months | 0.427113E+10 | 6508.74 | -0.4 | -4.2 | 0.111200E+10 | 1641.89 | -0.4 | -4.2 | ||
Maximum of Months | 0.174975E+11 | 40228.53 | 30.50 | 17.65 | 0.141288E+10 | 1686.01 | 30.50 | 20.13 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.224873E+10 | 3554.96 | 01-JAN-18:10 | 12.52 | 7.66 | 0.624738E+09 | 842.90 | 01-JAN-18:00 | 11.10 | 7.09 |
February | 0.235410E+10 | 16385.04 | 19-FEB-18:35 | 19.63 | 6.99 | 0.589068E+09 | 842.91 | 19-FEB-18:00 | 18.90 | 6.67 |
March | 0.302260E+10 | 16647.57 | 19-MAR-17:08 | 19.17 | 7.66 | 0.676776E+09 | 842.90 | 19-MAR-16:10 | 19.17 | 7.66 |
April | 0.535366E+10 | 17031.69 | 05-APR-21:22 | 18.60 | 9.05 | 0.675755E+09 | 842.98 | 30-APR-17:49 | 30.00 | 12.82 |
May | 0.729117E+10 | 16730.81 | 06-MAY-22:05 | 19.13 | 7.66 | 0.698464E+09 | 843.06 | 29-MAY-17:30 | 31.95 | 15.92 |
June | 0.873181E+10 | 20158.22 | 06-JUN-07:02 | 24.78 | 13.82 | 0.676761E+09 | 842.98 | 18-JUN-17:00 | 36.70 | 16.94 |
July | 0.922774E+10 | 20503.26 | 03-JUL-07:01 | 27.98 | 16.41 | 0.706288E+09 | 842.97 | 02-JUL-16:10 | 27.98 | 16.41 |
August | 0.906339E+10 | 20451.18 | 27-AUG-07:02 | 24.37 | 13.02 | 0.696501E+09 | 842.98 | 18-AUG-12:09 | 24.37 | 13.02 |
September | 0.838169E+10 | 17465.71 | 30-SEP-20:05 | 17.80 | 9.17 | 0.679920E+09 | 843.35 | 17-SEP-17:49 | 17.80 | 9.17 |
October | 0.662604E+10 | 20802.86 | 02-OCT-07:02 | 22.02 | 15.21 | 0.701125E+09 | 842.98 | 08-OCT-17:10 | 24.32 | 17.29 |
November | 0.374693E+10 | 16437.38 | 09-NOV-22:10 | 18.53 | 10.92 | 0.657868E+09 | 842.94 | 03-NOV-12:39 | 18.53 | 10.92 |
December | 0.213378E+10 | 3759.07 | 26-DEC-09:23 | -0.3 | -2.8 | 0.616557E+09 | 843.03 | 25-DEC-18:00 | -0.3 | -2.8 |
Annual Sum or Average | 0.681816E+11 | 0.799982E+10 | ||||||||
Minimum of Months | 0.213378E+10 | 3554.96 | -0.3 | -2.8 | 0.589068E+09 | 842.90 | -0.3 | -2.8 | ||
Maximum of Months | 0.922774E+10 | 20802.86 | 27.98 | 16.41 | 0.706288E+09 | 843.35 | 36.70 | 17.29 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.187524E+10 | 3919.26 | 05-JAN-08:61 | 0.28 | -4.7 | 0.351071E+09 | 716.23 | 07-JAN-13:00 | 13.90 | 6.19 |
February | 0.182991E+10 | 3630.88 | 09-FEB-08:61 | 1.78 | -1.8 | 0.338258E+09 | 842.88 | 11-FEB-13:00 | 18.90 | 6.65 |
March | 0.222517E+10 | 3574.46 | 18-MAR-07:01 | 2.15 | -2.3 | 0.408312E+09 | 842.88 | 25-MAR-12:39 | 19.23 | 8.73 |
April | 0.363339E+10 | 5975.38 | 21-APR-14:00 | 32.20 | 15.21 | 0.408531E+09 | 842.91 | 29-APR-12:09 | 27.30 | 15.21 |
May | 0.528242E+10 | 21084.66 | 31-MAY-06:02 | 23.58 | 11.53 | 0.426230E+09 | 842.90 | 27-MAY-12:09 | 23.58 | 11.53 |
June | 0.667802E+10 | 22728.14 | 06-JUN-06:02 | 22.57 | 13.18 | 0.417663E+09 | 842.92 | 03-JUN-12:09 | 22.57 | 13.18 |
July | 0.691191E+10 | 20974.13 | 03-JUL-06:01 | 26.88 | 16.13 | 0.420730E+09 | 842.97 | 08-JUL-12:09 | 28.68 | 20.13 |
August | 0.690826E+10 | 22513.27 | 23-AUG-06:02 | 20.28 | 12.08 | 0.432166E+09 | 842.95 | 12-AUG-12:09 | 20.28 | 12.08 |
September | 0.622825E+10 | 21846.53 | 18-SEP-06:02 | 18.68 | 14.33 | 0.411052E+09 | 842.95 | 09-SEP-12:09 | 18.68 | 14.33 |
October | 0.472364E+10 | 22072.29 | 02-OCT-06:02 | 22.70 | 15.09 | 0.419418E+09 | 842.94 | 28-OCT-12:30 | 21.40 | 13.50 |
November | 0.277601E+10 | 4852.37 | 09-NOV-14:00 | 23.30 | 12.45 | 0.384303E+09 | 842.90 | 18-NOV-13:00 | 19.40 | 6.83 |
December | 0.177426E+10 | 3689.77 | 12-DEC-08:61 | 1.28 | -2.3 | 0.344370E+09 | 842.89 | 09-DEC-13:00 | 1.28 | -2.3 |
Annual Sum or Average | 0.508465E+11 | 0.476210E+10 | ||||||||
Minimum of Months | 0.177426E+10 | 3574.46 | 0.28 | -4.7 | 0.338258E+09 | 716.23 | 1.28 | -2.3 | ||
Maximum of Months | 0.691191E+10 | 22728.14 | 32.20 | 16.13 | 0.432166E+09 | 842.97 | 28.68 | 20.13 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.172412E+10 | 3876.33 | 05-JAN-08:61 | 0.28 | -4.7 | 0.347301E+09 | 708.52 | 07-JAN-13:00 | 13.90 | 6.19 |
February | 0.170769E+10 | 3599.16 | 09-FEB-08:61 | 1.78 | -1.8 | 0.335466E+09 | 842.87 | 11-FEB-13:00 | 18.90 | 6.65 |
March | 0.208944E+10 | 3544.71 | 18-MAR-07:01 | 2.15 | -2.3 | 0.406474E+09 | 842.88 | 25-MAR-12:50 | 19.32 | 8.70 |
April | 0.357856E+10 | 5958.14 | 21-APR-14:00 | 32.20 | 15.21 | 0.408397E+09 | 842.91 | 29-APR-12:09 | 27.30 | 15.21 |
May | 0.529401E+10 | 21245.53 | 31-MAY-06:02 | 23.58 | 11.53 | 0.426226E+09 | 842.90 | 27-MAY-12:09 | 23.58 | 11.53 |
June | 0.672364E+10 | 22659.37 | 06-JUN-06:02 | 22.57 | 13.18 | 0.417665E+09 | 842.92 | 03-JUN-12:09 | 22.57 | 13.18 |
July | 0.695841E+10 | 20886.16 | 03-JUL-06:01 | 26.88 | 16.13 | 0.420732E+09 | 842.97 | 08-JUL-12:09 | 28.68 | 20.13 |
August | 0.695445E+10 | 23054.25 | 23-AUG-06:02 | 20.28 | 12.08 | 0.432168E+09 | 842.95 | 12-AUG-12:09 | 20.28 | 12.08 |
September | 0.625920E+10 | 22024.68 | 20-SEP-06:02 | 18.03 | 13.59 | 0.411051E+09 | 842.94 | 09-SEP-12:09 | 18.03 | 13.59 |
October | 0.469595E+10 | 22012.89 | 02-OCT-06:02 | 22.70 | 15.09 | 0.419365E+09 | 842.94 | 28-OCT-12:30 | 21.40 | 13.50 |
November | 0.265681E+10 | 4770.20 | 09-NOV-14:00 | 23.30 | 12.45 | 0.383127E+09 | 842.90 | 18-NOV-13:00 | 19.40 | 6.83 |
December | 0.163859E+10 | 3641.27 | 12-DEC-08:61 | 1.28 | -2.3 | 0.341023E+09 | 842.89 | 09-DEC-13:00 | 1.28 | -2.3 |
Annual Sum or Average | 0.502809E+11 | 0.474900E+10 | ||||||||
Minimum of Months | 0.163859E+10 | 3544.71 | 0.28 | -4.7 | 0.335466E+09 | 708.52 | 1.28 | -2.3 | ||
Maximum of Months | 0.695841E+10 | 23054.25 | 32.20 | 16.13 | 0.432168E+09 | 842.97 | 28.68 | 20.13 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.151894E+10 | 3724.37 | 27-JAN-09:23 | -0.3 | -5.1 | 0.342447E+09 | 702.41 | 03-JAN-17:10 | -0.3 | -5.1 |
February | 0.150825E+10 | 3546.64 | 09-FEB-08:61 | 1.78 | -1.8 | 0.331551E+09 | 842.60 | 11-FEB-13:00 | 18.90 | 6.65 |
March | 0.184839E+10 | 3487.38 | 18-MAR-07:01 | 2.15 | -2.3 | 0.403062E+09 | 842.88 | 25-MAR-12:00 | 19.40 | 8.67 |
April | 0.335162E+10 | 5781.37 | 21-APR-14:00 | 32.20 | 15.21 | 0.407912E+09 | 842.91 | 29-APR-12:09 | 27.30 | 15.21 |
May | 0.508393E+10 | 19815.83 | 31-MAY-06:02 | 23.58 | 11.53 | 0.426160E+09 | 842.90 | 27-MAY-12:09 | 23.58 | 11.53 |
June | 0.653750E+10 | 22540.04 | 06-JUN-06:02 | 22.57 | 13.18 | 0.417627E+09 | 842.92 | 03-JUN-12:09 | 22.57 | 13.18 |
July | 0.678494E+10 | 20867.03 | 03-JUL-06:01 | 26.88 | 16.13 | 0.420696E+09 | 842.97 | 08-JUL-12:09 | 28.68 | 20.13 |
August | 0.677491E+10 | 21920.08 | 28-AUG-06:02 | 20.37 | 14.83 | 0.432131E+09 | 842.95 | 12-AUG-12:09 | 20.37 | 14.83 |
September | 0.607867E+10 | 21804.03 | 18-SEP-06:02 | 18.68 | 14.33 | 0.411011E+09 | 842.95 | 09-SEP-12:09 | 18.68 | 14.33 |
October | 0.449442E+10 | 21896.29 | 02-OCT-06:02 | 22.70 | 15.09 | 0.419125E+09 | 842.94 | 28-OCT-12:30 | 21.40 | 13.50 |
November | 0.244738E+10 | 4559.50 | 09-NOV-14:00 | 23.30 | 12.45 | 0.380821E+09 | 842.90 | 18-NOV-13:00 | 19.40 | 6.83 |
December | 0.144183E+10 | 2859.92 | 08-DEC-08:61 | 4.13 | 0.72 | 0.336517E+09 | 842.72 | 09-DEC-13:00 | 17.20 | 7.07 |
Annual Sum or Average | 0.478708E+11 | 0.472906E+10 | ||||||||
Minimum of Months | 0.144183E+10 | 2859.92 | -0.3 | -5.1 | 0.331551E+09 | 702.41 | -0.3 | -5.1 | ||
Maximum of Months | 0.678494E+10 | 22540.04 | 32.20 | 16.13 | 0.432131E+09 | 842.97 | 28.68 | 20.13 |
Report: ZoneCoolingSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.225405E+10 | 4645.18 | 04-JAN-19:30 | 8.05 | 1.06 | 0.114806E+10 | 1994.90 | 03-JAN-17:00 | 8.05 | 1.06 |
February | 0.223421E+10 | 5512.21 | 24-FEB-09:03 | 5.87 | 1.59 | 0.112120E+10 | 2247.76 | 18-FEB-15:00 | 5.87 | 1.59 |
March | 0.277616E+10 | 5609.07 | 17-MAR-08:63 | 5.87 | -0.5 | 0.136445E+10 | 2247.80 | 25-MAR-14:00 | 21.10 | 8.87 |
April | 0.531996E+10 | 10404.27 | 21-APR-14:30 | 32.20 | 15.35 | 0.139879E+10 | 2247.80 | 29-APR-14:09 | 30.10 | 15.60 |
May | 0.846435E+10 | 28546.87 | 30-MAY-07:03 | 25.78 | 12.49 | 0.145799E+10 | 2247.80 | 27-MAY-14:09 | 25.78 | 12.49 |
June | 0.111397E+11 | 36347.26 | 06-JUN-07:02 | 24.78 | 13.82 | 0.143061E+10 | 2247.94 | 03-JUN-14:20 | 24.78 | 13.82 |
July | 0.115706E+11 | 37009.13 | 03-JUL-07:01 | 27.98 | 16.41 | 0.143922E+10 | 2248.07 | 01-JUL-14:20 | 27.98 | 16.41 |
August | 0.115808E+11 | 37082.16 | 28-AUG-07:02 | 22.38 | 15.17 | 0.148103E+10 | 2247.84 | 12-AUG-14:09 | 22.38 | 15.17 |
September | 0.103516E+11 | 32113.81 | 18-SEP-07:03 | 21.05 | 15.73 | 0.141031E+10 | 2247.91 | 23-SEP-14:00 | 28.30 | 18.50 |
October | 0.737016E+10 | 37743.51 | 02-OCT-07:02 | 22.02 | 15.21 | 0.143062E+10 | 2247.86 | 28-OCT-14:09 | 22.98 | 13.61 |
November | 0.380214E+10 | 7898.37 | 09-NOV-14:00 | 23.30 | 12.45 | 0.128420E+10 | 2247.71 | 18-NOV-15:09 | 19.40 | 6.83 |
December | 0.208759E+10 | 3941.47 | 18-DEC-12:00 | 8.90 | 0.02 | 0.113705E+10 | 2167.13 | 09-DEC-15:30 | 8.90 | 0.02 |
Annual Sum or Average | 0.789513E+11 | 0.161035E+11 | ||||||||
Minimum of Months | 0.208759E+10 | 3941.47 | 5.87 | -0.5 | 0.112120E+10 | 1994.90 | 5.87 | 0.02 | ||
Maximum of Months | 0.115808E+11 | 37743.51 | 32.20 | 16.41 | 0.148103E+10 | 2248.07 | 30.10 | 18.50 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.104974E+10 | 2819.88 | 26-JAN-13:03 | 4.68 | -2.3 | 0.572048E+09 | 997.43 | 03-JAN-17:10 | 4.68 | -2.3 |
February | 0.104535E+10 | 2730.66 | 08-FEB-18:30 | 6.10 | 0.64 | 0.558643E+09 | 1123.85 | 11-FEB-15:00 | 20.00 | 6.94 |
March | 0.130251E+10 | 2782.16 | 16-MAR-15:00 | 22.80 | 8.72 | 0.679581E+09 | 1123.86 | 25-MAR-14:00 | 21.10 | 8.87 |
April | 0.267638E+10 | 5406.23 | 21-APR-14:40 | 32.20 | 15.40 | 0.698982E+09 | 1123.87 | 29-APR-14:09 | 30.10 | 15.60 |
May | 0.435207E+10 | 14187.25 | 30-MAY-07:03 | 25.78 | 12.49 | 0.728942E+09 | 1123.87 | 27-MAY-14:09 | 25.78 | 12.49 |
June | 0.576380E+10 | 18642.93 | 06-JUN-07:02 | 24.78 | 13.82 | 0.715249E+09 | 1123.93 | 03-JUN-14:20 | 24.78 | 13.82 |
July | 0.599278E+10 | 19052.32 | 03-JUL-07:01 | 27.98 | 16.41 | 0.719553E+09 | 1124.01 | 01-JUL-14:20 | 27.98 | 16.41 |
August | 0.598803E+10 | 19152.54 | 28-AUG-07:02 | 22.38 | 15.17 | 0.740458E+09 | 1123.89 | 12-AUG-14:09 | 22.38 | 15.17 |
September | 0.534264E+10 | 15847.58 | 18-SEP-07:03 | 21.05 | 15.73 | 0.705112E+09 | 1123.92 | 23-SEP-14:00 | 28.30 | 18.50 |
October | 0.375562E+10 | 19496.60 | 02-OCT-07:02 | 22.02 | 15.21 | 0.715207E+09 | 1123.90 | 28-OCT-14:09 | 22.98 | 13.61 |
November | 0.185094E+10 | 4031.78 | 09-NOV-14:00 | 23.30 | 12.45 | 0.641005E+09 | 1123.83 | 18-NOV-15:09 | 19.40 | 6.83 |
December | 0.978201E+09 | 2563.71 | 18-DEC-17:55 | 5.60 | -2.3 | 0.566941E+09 | 1072.29 | 09-DEC-15:30 | 5.60 | -2.3 |
Annual Sum or Average | 0.400981E+11 | 0.804172E+10 | ||||||||
Minimum of Months | 0.978201E+09 | 2563.71 | 4.68 | -2.3 | 0.558643E+09 | 997.43 | 4.68 | -2.3 | ||
Maximum of Months | 0.599278E+10 | 19496.60 | 32.20 | 16.41 | 0.740458E+09 | 1124.01 | 30.10 | 18.50 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.995638E+09 | 3006.56 | 26-JAN-20:43 | 3.72 | -2.9 | 0.569948E+09 | 997.43 | 03-JAN-17:10 | 3.72 | -2.9 |
February | 0.990217E+09 | 2686.58 | 24-FEB-09:03 | 5.87 | 1.59 | 0.556655E+09 | 1123.85 | 11-FEB-15:00 | 5.87 | 1.59 |
March | 0.123646E+10 | 2736.57 | 17-MAR-08:63 | 5.87 | -0.5 | 0.676949E+09 | 1123.85 | 25-MAR-14:09 | 20.18 | 8.75 |
April | 0.260675E+10 | 5346.86 | 21-APR-14:40 | 32.20 | 15.40 | 0.698417E+09 | 1123.87 | 29-APR-14:09 | 30.10 | 15.60 |
May | 0.429441E+10 | 13773.15 | 30-MAY-07:03 | 25.78 | 12.49 | 0.728916E+09 | 1123.87 | 27-MAY-14:09 | 25.78 | 12.49 |
June | 0.571519E+10 | 18552.72 | 06-JUN-07:02 | 24.78 | 13.82 | 0.715243E+09 | 1123.93 | 03-JUN-14:20 | 24.78 | 13.82 |
July | 0.594738E+10 | 18976.11 | 03-JUL-07:01 | 27.98 | 16.41 | 0.719546E+09 | 1124.01 | 01-JUL-14:20 | 27.98 | 16.41 |
August | 0.594380E+10 | 19035.76 | 28-AUG-07:02 | 22.38 | 15.17 | 0.740453E+09 | 1123.89 | 12-AUG-14:09 | 22.38 | 15.17 |
September | 0.529860E+10 | 15714.73 | 13-SEP-07:02 | 22.88 | 17.65 | 0.705105E+09 | 1123.92 | 23-SEP-14:00 | 28.30 | 18.50 |
October | 0.369800E+10 | 19365.00 | 02-OCT-07:02 | 22.02 | 15.21 | 0.714964E+09 | 1123.90 | 28-OCT-14:09 | 22.98 | 13.61 |
November | 0.179372E+10 | 3951.76 | 09-NOV-14:00 | 23.30 | 12.45 | 0.639062E+09 | 1123.83 | 18-NOV-15:09 | 19.40 | 6.83 |
December | 0.932173E+09 | 2726.51 | 02-DEC-18:33 | 5.20 | 0.50 | 0.565374E+09 | 1065.71 | 09-DEC-15:30 | 16.95 | 6.83 |
Annual Sum or Average | 0.394523E+11 | 0.803063E+10 | ||||||||
Minimum of Months | 0.932173E+09 | 2686.58 | 3.72 | -2.9 | 0.556655E+09 | 997.43 | 3.72 | -2.9 | ||
Maximum of Months | 0.594738E+10 | 19365.00 | 32.20 | 17.65 | 0.740453E+09 | 1124.01 | 30.10 | 18.50 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.840531E+09 | 3155.11 | 26-JAN-20:03 | 2.98 | -2.9 | 0.565223E+09 | 995.71 | 03-JAN-17:30 | 2.98 | -2.9 |
February | 0.833225E+09 | 3055.67 | 01-FEB-20:33 | 3.50 | -1.8 | 0.551437E+09 | 1119.02 | 11-FEB-15:00 | 20.00 | 6.94 |
March | 0.106677E+10 | 2665.62 | 17-MAR-08:63 | 5.87 | -0.5 | 0.670054E+09 | 1123.85 | 25-MAR-14:20 | 20.37 | 8.78 |
April | 0.243880E+10 | 5232.64 | 21-APR-14:40 | 32.20 | 15.40 | 0.696723E+09 | 1123.87 | 29-APR-14:09 | 30.10 | 15.60 |
May | 0.417943E+10 | 12209.28 | 30-MAY-07:03 | 25.78 | 12.49 | 0.728824E+09 | 1123.87 | 27-MAY-14:09 | 25.78 | 12.49 |
June | 0.567833E+10 | 18545.01 | 18-JUN-08:62 | 26.47 | 16.53 | 0.715239E+09 | 1123.93 | 03-JUN-14:20 | 26.47 | 16.53 |
July | 0.593704E+10 | 18990.05 | 03-JUL-07:01 | 27.98 | 16.41 | 0.719543E+09 | 1124.01 | 01-JUL-14:20 | 27.98 | 16.41 |
August | 0.594050E+10 | 19031.17 | 28-AUG-07:02 | 22.38 | 15.17 | 0.740454E+09 | 1123.89 | 12-AUG-14:09 | 22.38 | 15.17 |
September | 0.527827E+10 | 15682.71 | 13-SEP-07:02 | 22.88 | 17.65 | 0.705098E+09 | 1123.92 | 23-SEP-14:00 | 28.30 | 18.50 |
October | 0.358190E+10 | 19337.82 | 02-OCT-07:02 | 22.02 | 15.21 | 0.714120E+09 | 1123.90 | 28-OCT-14:09 | 22.98 | 13.61 |
November | 0.165554E+10 | 3805.58 | 09-NOV-14:00 | 23.30 | 12.45 | 0.634260E+09 | 1123.84 | 18-NOV-15:09 | 19.40 | 6.83 |
December | 0.793598E+09 | 3039.38 | 29-DEC-20:23 | 3.60 | -0.4 | 0.561789E+09 | 1051.70 | 09-DEC-15:30 | 3.60 | -0.4 |
Annual Sum or Average | 0.382239E+11 | 0.800276E+10 | ||||||||
Minimum of Months | 0.793598E+09 | 2665.62 | 2.98 | -2.9 | 0.551437E+09 | 995.71 | 2.98 | -2.9 | ||
Maximum of Months | 0.594050E+10 | 19337.82 | 32.20 | 17.65 | 0.740454E+09 | 1124.01 | 30.10 | 18.50 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.547198E+09 | 2464.76 | 26-JAN-18:15 | 5.57 | -1.7 | 0.560131E+09 | 972.21 | 03-JAN-17:19 | 5.57 | -1.7 |
February | 0.529648E+09 | 2391.35 | 01-FEB-18:45 | 5.97 | -0.6 | 0.544500E+09 | 1087.45 | 18-FEB-15:00 | 20.00 | 8.60 |
March | 0.800762E+09 | 2246.98 | 16-MAR-14:40 | 22.80 | 8.93 | 0.661887E+09 | 1123.86 | 25-MAR-14:39 | 20.73 | 8.83 |
April | 0.249802E+10 | 5654.02 | 21-APR-14:20 | 32.20 | 15.31 | 0.695229E+09 | 1123.87 | 29-APR-14:09 | 30.10 | 15.60 |
May | 0.465546E+10 | 9602.26 | 30-MAY-07:03 | 25.78 | 12.49 | 0.728790E+09 | 1123.87 | 27-MAY-14:09 | 25.78 | 12.49 |
June | 0.661130E+10 | 20402.71 | 18-JUN-08:62 | 26.47 | 16.53 | 0.715325E+09 | 1123.94 | 03-JUN-14:20 | 26.47 | 16.53 |
July | 0.701150E+10 | 20825.89 | 03-JUL-07:01 | 27.98 | 16.41 | 0.719679E+09 | 1124.04 | 01-JUL-14:20 | 27.98 | 16.41 |
August | 0.704834E+10 | 20677.75 | 28-AUG-07:02 | 22.38 | 15.17 | 0.740577E+09 | 1123.93 | 05-AUG-14:20 | 22.38 | 15.17 |
September | 0.625257E+10 | 16991.98 | 13-SEP-07:02 | 22.88 | 17.65 | 0.705222E+09 | 1123.92 | 23-SEP-14:00 | 28.30 | 18.50 |
October | 0.384344E+10 | 21166.56 | 02-OCT-07:02 | 22.02 | 15.21 | 0.712069E+09 | 1123.89 | 28-OCT-14:09 | 22.98 | 13.61 |
November | 0.149130E+10 | 4033.71 | 09-NOV-14:00 | 23.30 | 12.45 | 0.629226E+09 | 1123.84 | 18-NOV-15:00 | 19.40 | 6.83 |
December | 0.532162E+09 | 2328.19 | 28-DEC-18:35 | 6.33 | 1.64 | 0.558825E+09 | 1042.82 | 09-DEC-15:20 | 6.33 | 1.64 |
Annual Sum or Average | 0.418217E+11 | 0.797146E+10 | ||||||||
Minimum of Months | 0.529648E+09 | 2246.98 | 5.57 | -1.7 | 0.544500E+09 | 972.21 | 5.57 | -1.7 | ||
Maximum of Months | 0.704834E+10 | 21166.56 | 32.20 | 17.65 | 0.740577E+09 | 1124.04 | 30.10 | 18.50 |
Report: ZoneHeatingSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.457266E+09 | 58945.72 | 06-JAN-08:61 | -0.6 |
February | 0.337609E+09 | 58962.47 | 03-FEB-08:61 | -2.0 |
March | 0.224830E+09 | 58954.13 | 02-MAR-08:61 | -0.9 |
April | 78470133.43 | 991.97 | 12-APR-07:13 | 8.00 |
May | 31515754.88 | 1958.57 | 31-MAY-07:05 | 25.37 |
June | 35242001.91 | 2160.36 | 17-JUN-07:04 | 24.78 |
July | 27546735.61 | 2150.70 | 01-JUL-07:04 | 27.38 |
August | 31587434.16 | 2068.33 | 28-AUG-07:04 | 22.38 |
September | 29352216.87 | 1978.33 | 14-SEP-07:05 | 19.60 |
October | 39192867.04 | 2005.58 | 05-OCT-07:05 | 20.97 |
November | 0.127740E+09 | 58924.19 | 28-NOV-08:61 | 2.48 |
December | 0.588493E+09 | 58967.61 | 19-DEC-08:61 | -2.3 |
Annual Sum or Average | 0.200884E+10 | |||
Minimum of Months | 27546735.61 | 991.97 | -2.3 | |
Maximum of Months | 0.588493E+09 | 58967.61 | 27.38 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 84174693.87 | 30526.74 | 27-JAN-08:61 | -3.5 |
February | 71403102.41 | 30534.67 | 03-FEB-08:61 | -2.0 |
March | 65063572.47 | 30535.33 | 02-MAR-08:61 | -0.9 |
April | 27266381.51 | 657.75 | 20-APR-07:10 | 20.60 |
May | 12381720.14 | 1127.77 | 31-MAY-07:05 | 25.37 |
June | 17723198.97 | 1192.23 | 10-JUN-07:04 | 24.50 |
July | 12085194.07 | 1145.43 | 01-JUL-07:04 | 27.38 |
August | 15162740.43 | 1146.46 | 28-AUG-07:04 | 22.38 |
September | 15752463.67 | 1089.43 | 21-SEP-07:05 | 20.97 |
October | 9109768.59 | 1102.70 | 05-OCT-07:05 | 20.97 |
November | 42157653.90 | 20705.94 | 28-NOV-08:61 | 2.48 |
December | 0.110156E+09 | 30526.66 | 29-DEC-08:61 | -0.1 |
Annual Sum or Average | 0.482437E+09 | |||
Minimum of Months | 9109768.59 | 657.75 | -3.5 | |
Maximum of Months | 0.110156E+09 | 30535.33 | 27.38 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.127955E+09 | 30363.62 | 28-JAN-07:02 | -2.9 |
February | 89457266.65 | 30128.64 | 03-FEB-07:02 | -5.1 |
March | 70343870.66 | 27717.88 | 02-MAR-07:02 | -1.6 |
April | 62962675.26 | 1650.53 | 30-APR-16:02 | 30.50 |
May | 0.100981E+09 | 2255.59 | 21-MAY-16:02 | 33.57 |
June | 0.171274E+09 | 3073.34 | 18-JUN-16:01 | 37.20 |
July | 0.144103E+09 | 3285.09 | 02-JUL-16:01 | 38.22 |
August | 0.123992E+09 | 2844.19 | 06-AUG-16:01 | 36.10 |
September | 59901508.48 | 2090.21 | 17-SEP-16:02 | 32.62 |
October | 20784761.17 | 1839.22 | 01-OCT-16:02 | 31.60 |
November | 53163085.14 | 17849.93 | 28-NOV-07:02 | 0.87 |
December | 0.188428E+09 | 30660.68 | 31-DEC-08:61 | -1.7 |
Annual Sum or Average | 0.121335E+10 | |||
Minimum of Months | 20784761.17 | 1650.53 | -5.1 | |
Maximum of Months | 0.188428E+09 | 30660.68 | 38.22 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.163681E+09 | 30241.64 | 27-JAN-07:02 | -4.3 |
February | 0.105118E+09 | 30244.22 | 03-FEB-07:02 | -5.1 |
March | 75728478.47 | 30259.40 | 02-MAR-07:02 | -1.6 |
April | 65065868.30 | 1650.05 | 30-APR-16:02 | 30.50 |
May | 0.100920E+09 | 2254.71 | 21-MAY-16:02 | 33.57 |
June | 0.170349E+09 | 3071.39 | 18-JUN-16:01 | 37.20 |
July | 0.143286E+09 | 3283.66 | 02-JUL-16:01 | 38.22 |
August | 0.122795E+09 | 2842.14 | 06-AUG-16:01 | 36.10 |
September | 59326130.97 | 2088.68 | 17-SEP-16:02 | 32.62 |
October | 21974957.81 | 1839.11 | 01-OCT-16:02 | 31.60 |
November | 58961981.00 | 20755.98 | 28-NOV-07:02 | 0.87 |
December | 0.232034E+09 | 30530.89 | 31-DEC-08:61 | -1.7 |
Annual Sum or Average | 0.131924E+10 | |||
Minimum of Months | 21974957.81 | 1650.05 | -5.1 | |
Maximum of Months | 0.232034E+09 | 30530.89 | 38.22 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.227977E+09 | 30215.65 | 27-JAN-07:02 | -4.3 |
February | 0.134126E+09 | 30228.87 | 02-FEB-07:02 | -4.0 |
March | 89462663.49 | 30233.41 | 02-MAR-07:02 | -1.6 |
April | 73495182.11 | 1657.33 | 30-APR-16:02 | 30.50 |
May | 0.104085E+09 | 2261.30 | 21-MAY-16:02 | 33.57 |
June | 0.172494E+09 | 3075.55 | 18-JUN-16:01 | 37.20 |
July | 0.145327E+09 | 3287.98 | 02-JUL-16:01 | 38.22 |
August | 0.124696E+09 | 2846.05 | 06-AUG-16:01 | 36.10 |
September | 60686442.96 | 2093.64 | 17-SEP-16:02 | 32.62 |
October | 26900782.55 | 1845.67 | 01-OCT-16:02 | 31.60 |
November | 67927559.38 | 23744.20 | 28-NOV-07:02 | 0.87 |
December | 0.301094E+09 | 30503.78 | 31-DEC-08:61 | -1.7 |
Annual Sum or Average | 0.152827E+10 | |||
Minimum of Months | 26900782.55 | 1657.33 | -4.3 | |
Maximum of Months | 0.301094E+09 | 30503.78 | 38.22 |
Report: ZoneHeatingSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.522763E+09 | 55141.39 | 06-JAN-08:61 | -0.6 |
February | 0.314837E+09 | 55153.94 | 02-FEB-08:61 | -1.7 |
March | 0.210362E+09 | 55155.67 | 02-MAR-08:61 | -0.9 |
April | 0.121558E+09 | 3294.96 | 30-APR-16:02 | 30.50 |
May | 0.117192E+09 | 4526.09 | 21-MAY-16:02 | 33.57 |
June | 0.124916E+09 | 6129.13 | 18-JUN-16:01 | 37.20 |
July | 0.136236E+09 | 6561.45 | 02-JUL-16:01 | 38.22 |
August | 0.124483E+09 | 5669.10 | 06-AUG-16:01 | 36.10 |
September | 74232582.13 | 4166.57 | 17-SEP-16:02 | 32.62 |
October | 60014926.02 | 3688.66 | 01-OCT-16:02 | 31.60 |
November | 0.141934E+09 | 55131.63 | 28-NOV-08:61 | 2.48 |
December | 0.668741E+09 | 55162.68 | 19-DEC-08:61 | -2.3 |
Annual Sum or Average | 0.261727E+10 | |||
Minimum of Months | 60014926.02 | 3294.96 | -2.3 | |
Maximum of Months | 0.668741E+09 | 55162.68 | 38.22 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.312991E+09 | 28470.75 | 06-JAN-08:61 | -0.6 |
February | 0.187254E+09 | 28477.28 | 02-FEB-08:61 | -1.7 |
March | 0.124443E+09 | 28478.19 | 02-MAR-08:61 | -0.9 |
April | 66485918.66 | 1664.79 | 30-APR-16:02 | 30.50 |
May | 61040015.75 | 2275.88 | 21-MAY-16:02 | 33.57 |
June | 64338596.93 | 3078.18 | 18-JUN-16:01 | 37.20 |
July | 69540545.90 | 3293.01 | 02-JUL-16:01 | 38.22 |
August | 63654161.62 | 2848.23 | 06-AUG-16:01 | 36.10 |
September | 38860664.84 | 2098.05 | 17-SEP-16:02 | 32.62 |
October | 33583582.39 | 1857.79 | 01-OCT-16:02 | 31.60 |
November | 82623812.93 | 28465.15 | 28-NOV-08:61 | 2.48 |
December | 0.400105E+09 | 28481.35 | 19-DEC-08:61 | -2.3 |
Annual Sum or Average | 0.150492E+10 | |||
Minimum of Months | 33583582.39 | 1664.79 | -2.3 | |
Maximum of Months | 0.400105E+09 | 28481.35 | 38.22 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.343511E+09 | 28369.23 | 06-JAN-08:61 | -0.6 |
February | 0.204964E+09 | 28375.56 | 02-FEB-08:61 | -1.7 |
March | 0.137641E+09 | 28376.46 | 02-MAR-08:61 | -0.9 |
April | 67362309.19 | 1666.08 | 30-APR-16:02 | 30.50 |
May | 61398419.23 | 2276.94 | 21-MAY-16:02 | 33.57 |
June | 64345823.70 | 3078.67 | 18-JUN-16:01 | 37.20 |
July | 69739322.18 | 3293.49 | 02-JUL-16:01 | 38.22 |
August | 63577494.02 | 2848.54 | 06-AUG-16:01 | 36.10 |
September | 38898984.04 | 2098.45 | 17-SEP-16:02 | 32.62 |
October | 34878903.60 | 1858.78 | 01-OCT-16:02 | 31.60 |
November | 88376338.45 | 28363.66 | 28-NOV-08:61 | 2.48 |
December | 0.430936E+09 | 28378.76 | 19-DEC-08:61 | -2.3 |
Annual Sum or Average | 0.160563E+10 | |||
Minimum of Months | 34878903.60 | 1666.08 | -2.3 | |
Maximum of Months | 0.430936E+09 | 28378.76 | 38.22 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.465019E+09 | 28403.78 | 06-JAN-08:61 | -0.6 |
February | 0.282840E+09 | 28410.81 | 02-FEB-08:61 | -1.7 |
March | 0.201991E+09 | 28412.03 | 02-MAR-08:61 | -0.9 |
April | 72267531.24 | 3583.90 | 01-APR-07:03 | 11.02 |
May | 62978080.60 | 2279.46 | 21-MAY-16:02 | 33.57 |
June | 64364996.40 | 3078.91 | 18-JUN-16:01 | 37.20 |
July | 69344109.83 | 3293.28 | 02-JUL-16:01 | 38.22 |
August | 63479521.39 | 2847.46 | 06-AUG-16:01 | 36.10 |
September | 39258279.06 | 2098.22 | 17-SEP-16:02 | 32.62 |
October | 39463239.69 | 1860.74 | 01-OCT-16:02 | 31.60 |
November | 0.110824E+09 | 28397.87 | 28-NOV-08:61 | 2.48 |
December | 0.550159E+09 | 28415.26 | 19-DEC-08:61 | -2.3 |
Annual Sum or Average | 0.202199E+10 | |||
Minimum of Months | 39258279.06 | 1860.74 | -2.3 | |
Maximum of Months | 0.550159E+09 | 28415.26 | 38.22 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.992775E+09 | 31403.46 | 06-JAN-08:61 | -0.6 |
February | 0.640805E+09 | 31415.68 | 03-FEB-08:61 | -2.0 |
March | 0.513156E+09 | 31413.42 | 02-MAR-08:61 | -0.9 |
April | 99564922.12 | 23519.97 | 12-APR-07:02 | 7.35 |
May | 66826896.66 | 2272.61 | 21-MAY-16:02 | 33.57 |
June | 61186583.03 | 3072.14 | 18-JUN-16:01 | 37.20 |
July | 66662996.04 | 3275.22 | 02-JUL-16:01 | 38.22 |
August | 61037256.41 | 2829.11 | 06-AUG-16:01 | 36.10 |
September | 41064221.41 | 2083.75 | 17-SEP-16:02 | 32.62 |
October | 48985289.82 | 1849.30 | 01-OCT-16:02 | 31.60 |
November | 0.240716E+09 | 31390.64 | 28-NOV-08:61 | 2.48 |
December | 0.103261E+10 | 31423.34 | 19-DEC-08:61 | -2.3 |
Annual Sum or Average | 0.386539E+10 | |||
Minimum of Months | 41064221.41 | 1849.30 | -2.3 | |
Maximum of Months | 0.103261E+10 | 31423.34 | 38.22 |
Report: ZoneElectricSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.739462E+10 | 4621.63 | 01-JAN-10:09 | 0.222596E+10 | 1343.25 | 01-JAN-10:09 |
February | 0.668410E+10 | 4621.63 | 01-FEB-10:09 | 0.201408E+10 | 1343.25 | 01-FEB-10:09 |
March | 0.740180E+10 | 4621.63 | 01-MAR-10:09 | 0.223295E+10 | 1343.25 | 01-MAR-10:09 |
April | 0.716384E+10 | 4621.63 | 01-APR-09:09 | 0.215748E+10 | 1343.25 | 01-APR-09:09 |
May | 0.739462E+10 | 4621.63 | 01-MAY-09:09 | 0.222596E+10 | 1343.25 | 01-MAY-09:09 |
June | 0.716485E+10 | 4621.63 | 01-JUN-09:09 | 0.216232E+10 | 1343.25 | 01-JUN-09:09 |
July | 0.740069E+10 | 4621.63 | 01-JUL-09:09 | 0.222811E+10 | 1343.25 | 01-JUL-09:09 |
August | 0.739513E+10 | 4621.63 | 01-AUG-09:09 | 0.222838E+10 | 1343.25 | 01-AUG-09:09 |
September | 0.717041E+10 | 4621.63 | 01-SEP-09:09 | 0.216205E+10 | 1343.25 | 01-SEP-09:09 |
October | 0.739462E+10 | 4621.63 | 01-OCT-09:09 | 0.222596E+10 | 1343.25 | 01-OCT-09:09 |
November | 0.714323E+10 | 4621.63 | 01-NOV-09:09 | 0.215077E+10 | 1343.25 | 01-NOV-09:09 |
December | 0.740776E+10 | 4621.63 | 01-DEC-10:09 | 0.223509E+10 | 1343.25 | 01-DEC-10:09 |
Annual Sum or Average | 0.871157E+11 | 0.262491E+11 | ||||
Minimum of Months | 0.668410E+10 | 4621.63 | 0.201408E+10 | 1343.25 | ||
Maximum of Months | 0.740776E+10 | 4621.63 | 0.223509E+10 | 1343.25 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.451584E+10 | 2827.07 | 01-JAN-10:09 | 0.111298E+10 | 671.63 | 01-JAN-10:09 |
February | 0.408193E+10 | 2827.07 | 01-FEB-10:09 | 0.100704E+10 | 671.63 | 01-FEB-10:09 |
March | 0.452026E+10 | 2827.07 | 01-MAR-10:09 | 0.111647E+10 | 671.63 | 01-MAR-10:09 |
April | 0.437489E+10 | 2827.07 | 01-APR-09:09 | 0.107874E+10 | 671.63 | 01-APR-09:09 |
May | 0.451584E+10 | 2827.07 | 01-MAY-09:09 | 0.111298E+10 | 671.63 | 01-MAY-09:09 |
June | 0.437556E+10 | 2827.07 | 01-JUN-09:09 | 0.108116E+10 | 671.63 | 01-JUN-09:09 |
July | 0.451952E+10 | 2827.07 | 01-JUL-09:09 | 0.111405E+10 | 671.63 | 01-JUL-09:09 |
August | 0.451617E+10 | 2827.07 | 01-AUG-09:09 | 0.111419E+10 | 671.63 | 01-AUG-09:09 |
September | 0.437891E+10 | 2827.07 | 01-SEP-09:09 | 0.108102E+10 | 671.63 | 01-SEP-09:09 |
October | 0.451584E+10 | 2827.07 | 01-OCT-09:09 | 0.111298E+10 | 671.63 | 01-OCT-09:09 |
November | 0.436230E+10 | 2827.07 | 01-NOV-09:09 | 0.107538E+10 | 671.63 | 01-NOV-09:09 |
December | 0.452388E+10 | 2827.07 | 01-DEC-10:09 | 0.111755E+10 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.532009E+11 | 0.131245E+11 | ||||
Minimum of Months | 0.408193E+10 | 2827.07 | 0.100704E+10 | 671.63 | ||
Maximum of Months | 0.452388E+10 | 2827.07 | 0.111755E+10 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.317044E+10 | 2555.22 | 01-JAN-10:09 | 0.879849E+09 | 671.63 | 01-JAN-10:09 |
February | 0.287181E+10 | 2555.22 | 01-FEB-09:09 | 0.796766E+09 | 671.63 | 01-FEB-09:09 |
March | 0.324295E+10 | 2555.22 | 01-MAR-09:09 | 0.898128E+09 | 671.63 | 01-MAR-09:09 |
April | 0.307694E+10 | 2555.22 | 01-APR-08:09 | 0.853677E+09 | 671.63 | 01-APR-08:09 |
May | 0.320669E+10 | 2555.22 | 01-MAY-08:09 | 0.888989E+09 | 671.63 | 01-MAY-08:09 |
June | 0.313132E+10 | 2555.22 | 01-JUN-08:09 | 0.867387E+09 | 671.63 | 01-JUN-08:09 |
July | 0.315231E+10 | 2555.22 | 01-JUL-08:09 | 0.875279E+09 | 671.63 | 01-JUL-08:09 |
August | 0.324295E+10 | 2555.22 | 01-AUG-08:09 | 0.898128E+09 | 671.63 | 01-AUG-08:09 |
September | 0.307694E+10 | 2555.22 | 01-SEP-08:09 | 0.853677E+09 | 671.63 | 01-SEP-08:09 |
October | 0.317044E+10 | 2555.22 | 01-OCT-09:09 | 0.879849E+09 | 671.63 | 01-OCT-09:09 |
November | 0.307694E+10 | 2555.22 | 01-NOV-08:09 | 0.853679E+09 | 671.63 | 01-NOV-08:09 |
December | 0.315231E+10 | 2555.22 | 01-DEC-09:09 | 0.875279E+09 | 671.63 | 01-DEC-09:09 |
Annual Sum or Average | 0.375720E+11 | 0.104207E+11 | ||||
Minimum of Months | 0.287181E+10 | 2555.22 | 0.796766E+09 | 671.63 | ||
Maximum of Months | 0.324295E+10 | 2555.22 | 0.898128E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.317044E+10 | 2555.22 | 01-JAN-10:09 | 0.879849E+09 | 671.63 | 01-JAN-10:09 |
February | 0.287181E+10 | 2555.22 | 01-FEB-09:09 | 0.796766E+09 | 671.63 | 01-FEB-09:09 |
March | 0.324295E+10 | 2555.22 | 01-MAR-09:09 | 0.898128E+09 | 671.63 | 01-MAR-09:09 |
April | 0.307694E+10 | 2555.22 | 01-APR-08:09 | 0.853677E+09 | 671.63 | 01-APR-08:09 |
May | 0.320669E+10 | 2555.22 | 01-MAY-08:09 | 0.888989E+09 | 671.63 | 01-MAY-08:09 |
June | 0.313132E+10 | 2555.22 | 01-JUN-08:09 | 0.867387E+09 | 671.63 | 01-JUN-08:09 |
July | 0.315231E+10 | 2555.22 | 01-JUL-08:09 | 0.875279E+09 | 671.63 | 01-JUL-08:09 |
August | 0.324295E+10 | 2555.22 | 01-AUG-08:09 | 0.898128E+09 | 671.63 | 01-AUG-08:09 |
September | 0.307694E+10 | 2555.22 | 01-SEP-08:09 | 0.853677E+09 | 671.63 | 01-SEP-08:09 |
October | 0.317044E+10 | 2555.22 | 01-OCT-09:09 | 0.879849E+09 | 671.63 | 01-OCT-09:09 |
November | 0.307694E+10 | 2555.22 | 01-NOV-08:09 | 0.853679E+09 | 671.63 | 01-NOV-08:09 |
December | 0.315231E+10 | 2555.22 | 01-DEC-09:09 | 0.875279E+09 | 671.63 | 01-DEC-09:09 |
Annual Sum or Average | 0.375720E+11 | 0.104207E+11 | ||||
Minimum of Months | 0.287181E+10 | 2555.22 | 0.796766E+09 | 671.63 | ||
Maximum of Months | 0.324295E+10 | 2555.22 | 0.898128E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.317044E+10 | 2555.22 | 01-JAN-10:09 | 0.879849E+09 | 671.63 | 01-JAN-10:09 |
February | 0.287181E+10 | 2555.22 | 01-FEB-09:09 | 0.796766E+09 | 671.63 | 01-FEB-09:09 |
March | 0.324295E+10 | 2555.22 | 01-MAR-09:09 | 0.898128E+09 | 671.63 | 01-MAR-09:09 |
April | 0.307694E+10 | 2555.22 | 01-APR-08:09 | 0.853677E+09 | 671.63 | 01-APR-08:09 |
May | 0.320669E+10 | 2555.22 | 01-MAY-08:09 | 0.888989E+09 | 671.63 | 01-MAY-08:09 |
June | 0.313132E+10 | 2555.22 | 01-JUN-08:09 | 0.867387E+09 | 671.63 | 01-JUN-08:09 |
July | 0.315231E+10 | 2555.22 | 01-JUL-08:09 | 0.875279E+09 | 671.63 | 01-JUL-08:09 |
August | 0.324295E+10 | 2555.22 | 01-AUG-08:09 | 0.898128E+09 | 671.63 | 01-AUG-08:09 |
September | 0.307694E+10 | 2555.22 | 01-SEP-08:09 | 0.853677E+09 | 671.63 | 01-SEP-08:09 |
October | 0.317044E+10 | 2555.22 | 01-OCT-09:09 | 0.879849E+09 | 671.63 | 01-OCT-09:09 |
November | 0.307694E+10 | 2555.22 | 01-NOV-08:09 | 0.853679E+09 | 671.63 | 01-NOV-08:09 |
December | 0.315231E+10 | 2555.22 | 01-DEC-09:09 | 0.875279E+09 | 671.63 | 01-DEC-09:09 |
Annual Sum or Average | 0.375720E+11 | 0.104207E+11 | ||||
Minimum of Months | 0.287181E+10 | 2555.22 | 0.796766E+09 | 671.63 | ||
Maximum of Months | 0.324295E+10 | 2555.22 | 0.898128E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.313454E+10 | 2726.96 | 01-JAN-11:09 | 0.161799E+10 | 1343.25 | 01-JAN-11:09 |
February | 0.283982E+10 | 2726.96 | 01-FEB-10:09 | 0.146554E+10 | 1343.25 | 01-FEB-10:09 |
March | 0.321092E+10 | 2726.96 | 01-MAR-10:09 | 0.165455E+10 | 1343.25 | 01-MAR-10:09 |
April | 0.304266E+10 | 2726.96 | 01-APR-09:09 | 0.157022E+10 | 1343.25 | 01-APR-09:09 |
May | 0.317273E+10 | 2726.96 | 01-MAY-09:09 | 0.163627E+10 | 1343.25 | 01-MAY-09:09 |
June | 0.309995E+10 | 2726.96 | 01-JUN-09:09 | 0.159764E+10 | 1343.25 | 01-JUN-09:09 |
July | 0.311545E+10 | 2726.96 | 01-JUL-09:09 | 0.160885E+10 | 1343.25 | 01-JUL-09:09 |
August | 0.321092E+10 | 2726.96 | 01-AUG-09:09 | 0.165455E+10 | 1343.25 | 01-AUG-09:09 |
September | 0.304266E+10 | 2726.96 | 01-SEP-09:09 | 0.157022E+10 | 1343.25 | 01-SEP-09:09 |
October | 0.313454E+10 | 2726.96 | 01-OCT-10:09 | 0.161799E+10 | 1343.25 | 01-OCT-10:09 |
November | 0.304266E+10 | 2726.96 | 01-NOV-09:09 | 0.157022E+10 | 1343.25 | 01-NOV-09:09 |
December | 0.311545E+10 | 2726.96 | 01-DEC-10:09 | 0.160885E+10 | 1343.25 | 01-DEC-10:09 |
Annual Sum or Average | 0.371623E+11 | 0.191729E+11 | ||||
Minimum of Months | 0.283982E+10 | 2726.96 | 0.146554E+10 | 1343.25 | ||
Maximum of Months | 0.321092E+10 | 2726.96 | 0.165455E+10 | 1343.25 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.161274E+10 | 1404.46 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.146111E+10 | 1404.46 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.165211E+10 | 1404.46 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.156548E+10 | 1404.46 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.163243E+10 | 1404.46 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.159501E+10 | 1404.46 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.160290E+10 | 1404.46 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.165211E+10 | 1404.46 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.156548E+10 | 1404.46 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.161274E+10 | 1404.46 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.156548E+10 | 1404.46 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.160290E+10 | 1404.46 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.191205E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.146111E+10 | 1404.46 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.165211E+10 | 1404.46 | 0.827277E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.161274E+10 | 1404.46 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.146111E+10 | 1404.46 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.165211E+10 | 1404.46 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.156548E+10 | 1404.46 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.163243E+10 | 1404.46 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.159501E+10 | 1404.46 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.160290E+10 | 1404.46 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.165211E+10 | 1404.46 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.156548E+10 | 1404.46 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.161274E+10 | 1404.46 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.156548E+10 | 1404.46 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.160290E+10 | 1404.46 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.191205E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.146111E+10 | 1404.46 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.165211E+10 | 1404.46 | 0.827277E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.161274E+10 | 1404.46 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.146111E+10 | 1404.46 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.165211E+10 | 1404.46 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.156548E+10 | 1404.46 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.163243E+10 | 1404.46 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.159501E+10 | 1404.46 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.160290E+10 | 1404.46 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.165211E+10 | 1404.46 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.156548E+10 | 1404.46 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.161274E+10 | 1404.46 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.156548E+10 | 1404.46 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.160290E+10 | 1404.46 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.191205E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.146111E+10 | 1404.46 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.165211E+10 | 1404.46 | 0.827277E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.161274E+10 | 1404.46 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.146111E+10 | 1404.46 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.165211E+10 | 1404.46 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.156548E+10 | 1404.46 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.163243E+10 | 1404.46 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.159501E+10 | 1404.46 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.160290E+10 | 1404.46 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.165211E+10 | 1404.46 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.156548E+10 | 1404.46 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.161274E+10 | 1404.46 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.156548E+10 | 1404.46 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.160290E+10 | 1404.46 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.191205E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.146111E+10 | 1404.46 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.165211E+10 | 1404.46 | 0.827277E+09 | 671.63 |
Report: SpaceGainsMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.338624E+10 | 0.739462E+10 | 0.222596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.256291E+10 |
February | 0.305697E+10 | 0.668410E+10 | 0.201408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187436E+10 |
March | 0.335708E+10 | 0.740180E+10 | 0.223295E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4486640.23 | 0.166265E+10 |
April | 0.327081E+10 | 0.716384E+10 | 0.215748E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.420069E+09 | 0.705260E+09 |
May | 0.336680E+10 | 0.739462E+10 | 0.222596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100255E+10 | 0.254091E+09 |
June | 0.325380E+10 | 0.716485E+10 | 0.216232E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168916E+10 | 80952564.22 |
July | 0.339353E+10 | 0.740069E+10 | 0.222811E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153843E+10 | 55147999.68 |
August | 0.334857E+10 | 0.739513E+10 | 0.222838E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130007E+10 | 0.113199E+09 |
September | 0.327932E+10 | 0.717041E+10 | 0.216205E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.934382E+09 | 0.133742E+09 |
October | 0.338624E+10 | 0.739462E+10 | 0.222596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.225912E+09 | 0.784204E+09 |
November | 0.327446E+10 | 0.714323E+10 | 0.215077E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 925.13 | 0.199178E+10 |
December | 0.340325E+10 | 0.740776E+10 | 0.223509E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.266294E+10 |
Annual Sum or Average | 0.397770E+11 | 0.871157E+11 | 0.262491E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.711505E+10 | 0.128812E+11 |
Minimum of Months | 0.305697E+10 | 0.668410E+10 | 0.201408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55147999.68 |
Maximum of Months | 0.340325E+10 | 0.740776E+10 | 0.223509E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168916E+10 | 0.266294E+10 |
Report: SpaceGainsMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.169307E+10 | 0.451584E+10 | 0.111298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130717E+10 |
February | 0.152844E+10 | 0.408193E+10 | 0.100704E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.933556E+09 |
March | 0.167849E+10 | 0.452026E+10 | 0.111647E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2423419.44 | 0.805227E+09 |
April | 0.163536E+10 | 0.437489E+10 | 0.107874E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.225053E+09 | 0.307613E+09 |
May | 0.168335E+10 | 0.451584E+10 | 0.111298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.534566E+09 | 91003774.95 |
June | 0.162685E+10 | 0.437556E+10 | 0.108116E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.901798E+09 | 26344013.40 |
July | 0.169671E+10 | 0.451952E+10 | 0.111405E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.826924E+09 | 17780603.05 |
August | 0.167424E+10 | 0.451617E+10 | 0.111419E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.701313E+09 | 40891121.37 |
September | 0.163961E+10 | 0.437891E+10 | 0.108102E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.512544E+09 | 47867564.47 |
October | 0.169307E+10 | 0.451584E+10 | 0.111298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123255E+09 | 0.351940E+09 |
November | 0.163718E+10 | 0.436230E+10 | 0.107538E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 503.07 | 0.981920E+09 |
December | 0.170157E+10 | 0.452388E+10 | 0.111755E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137852E+10 |
Annual Sum or Average | 0.198880E+11 | 0.532009E+11 | 0.131245E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.382788E+10 | 0.628983E+10 |
Minimum of Months | 0.152844E+10 | 0.408193E+10 | 0.100704E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17780603.05 |
Maximum of Months | 0.170157E+10 | 0.452388E+10 | 0.111755E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.901798E+09 | 0.137852E+10 |
Report: SpaceGainsMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.317044E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130855E+10 |
February | 0.914877E+09 | 0.287181E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.947046E+09 |
March | 0.103395E+10 | 0.324295E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2423143.20 | 0.832793E+09 |
April | 0.984131E+09 | 0.307694E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.218090E+09 | 0.326524E+09 |
May | 0.102058E+10 | 0.320669E+10 | 0.888989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.524406E+09 | 0.101182E+09 |
June | 0.998711E+09 | 0.313132E+10 | 0.867387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.894784E+09 | 30227482.29 |
July | 0.100600E+10 | 0.315231E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.815344E+09 | 23927210.91 |
August | 0.103395E+10 | 0.324295E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.692240E+09 | 45199856.37 |
September | 0.984131E+09 | 0.307694E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.503534E+09 | 57815064.88 |
October | 0.100722E+10 | 0.317044E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119339E+09 | 0.374436E+09 |
November | 0.973196E+09 | 0.307694E+10 | 0.853679E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 503.07 | 0.100599E+10 |
December | 0.100600E+10 | 0.315231E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137673E+10 |
Annual Sum or Average | 0.119700E+11 | 0.375720E+11 | 0.104207E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.377016E+10 | 0.643041E+10 |
Minimum of Months | 0.914877E+09 | 0.287181E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23927210.91 |
Maximum of Months | 0.103395E+10 | 0.324295E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.894784E+09 | 0.137673E+10 |
Report: SpaceGainsMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.317044E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129294E+10 |
February | 0.914877E+09 | 0.287181E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.935468E+09 |
March | 0.103395E+10 | 0.324295E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2423143.20 | 0.824469E+09 |
April | 0.984131E+09 | 0.307694E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.218135E+09 | 0.325397E+09 |
May | 0.102058E+10 | 0.320669E+10 | 0.888989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.524248E+09 | 0.101349E+09 |
June | 0.998711E+09 | 0.313132E+10 | 0.867387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.894313E+09 | 30703357.27 |
July | 0.100600E+10 | 0.315231E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.814839E+09 | 24424873.26 |
August | 0.103395E+10 | 0.324295E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.691869E+09 | 45663827.16 |
September | 0.984131E+09 | 0.307694E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.503472E+09 | 58097530.41 |
October | 0.100722E+10 | 0.317044E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119305E+09 | 0.374100E+09 |
November | 0.973196E+09 | 0.307694E+10 | 0.853679E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 503.07 | 0.100083E+10 |
December | 0.100600E+10 | 0.315231E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136255E+10 |
Annual Sum or Average | 0.119700E+11 | 0.375720E+11 | 0.104207E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.376860E+10 | 0.637599E+10 |
Minimum of Months | 0.914877E+09 | 0.287181E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24424873.26 |
Maximum of Months | 0.103395E+10 | 0.324295E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.894313E+09 | 0.136255E+10 |
Report: SpaceGainsMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.317044E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127423E+10 |
February | 0.914877E+09 | 0.287181E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.920522E+09 |
March | 0.103395E+10 | 0.324295E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2423143.20 | 0.811039E+09 |
April | 0.984131E+09 | 0.307694E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.218441E+09 | 0.321623E+09 |
May | 0.102058E+10 | 0.320669E+10 | 0.888989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.524906E+09 | 99394186.10 |
June | 0.998711E+09 | 0.313132E+10 | 0.867387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.895231E+09 | 29562422.35 |
July | 0.100600E+10 | 0.315231E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.815649E+09 | 23348520.05 |
August | 0.103395E+10 | 0.324295E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.692460E+09 | 44630590.41 |
September | 0.984131E+09 | 0.307694E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.503627E+09 | 57180726.00 |
October | 0.100722E+10 | 0.317044E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119405E+09 | 0.371957E+09 |
November | 0.973196E+09 | 0.307694E+10 | 0.853679E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 503.07 | 0.992084E+09 |
December | 0.100600E+10 | 0.315231E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134473E+10 |
Annual Sum or Average | 0.119700E+11 | 0.375720E+11 | 0.104207E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.377214E+10 | 0.629031E+10 |
Minimum of Months | 0.914877E+09 | 0.287181E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23348520.05 |
Maximum of Months | 0.103395E+10 | 0.324295E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.895231E+09 | 0.134473E+10 |
Report: SpaceGainsMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.344359E+10 | 0.313454E+10 | 0.161799E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230574E+10 |
February | 0.313522E+10 | 0.283982E+10 | 0.146554E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166806E+10 |
March | 0.355148E+10 | 0.321092E+10 | 0.165455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4361872.63 | 0.147190E+10 |
April | 0.338259E+10 | 0.304266E+10 | 0.157022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.396065E+09 | 0.599373E+09 |
May | 0.349753E+10 | 0.317273E+10 | 0.163627E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.952134E+09 | 0.193217E+09 |
June | 0.343071E+10 | 0.309995E+10 | 0.159764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162316E+10 | 57039652.26 |
July | 0.344942E+10 | 0.311545E+10 | 0.160885E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147631E+10 | 45483422.89 |
August | 0.355148E+10 | 0.321092E+10 | 0.165455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125185E+10 | 86907582.58 |
September | 0.338259E+10 | 0.304266E+10 | 0.157022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.906107E+09 | 0.112048E+09 |
October | 0.344359E+10 | 0.313454E+10 | 0.161799E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.215224E+09 | 0.696127E+09 |
November | 0.331698E+10 | 0.304266E+10 | 0.157022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 895.50 | 0.180897E+10 |
December | 0.344942E+10 | 0.311545E+10 | 0.160885E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.243038E+10 |
Annual Sum or Average | 0.410346E+11 | 0.371623E+11 | 0.191729E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.682522E+10 | 0.114752E+11 |
Minimum of Months | 0.313522E+10 | 0.283982E+10 | 0.146554E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45483422.89 |
Maximum of Months | 0.355148E+10 | 0.321092E+10 | 0.165455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162316E+10 | 0.243038E+10 |
Report: SpaceGainsMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.161274E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125454E+10 |
February | 0.156756E+10 | 0.146111E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.902071E+09 |
March | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2423143.20 | 0.790703E+09 |
April | 0.169125E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219964E+09 | 0.318887E+09 |
May | 0.174872E+10 | 0.163243E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.528317E+09 | 99393604.65 |
June | 0.171530E+10 | 0.159501E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.900438E+09 | 28438140.13 |
July | 0.172466E+10 | 0.160290E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.819800E+09 | 22510127.39 |
August | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.695519E+09 | 44624143.64 |
September | 0.169125E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.504575E+09 | 57753830.46 |
October | 0.172174E+10 | 0.161274E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119769E+09 | 0.373995E+09 |
November | 0.165844E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 500.17 | 0.982767E+09 |
December | 0.172466E+10 | 0.160290E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132786E+10 |
Annual Sum or Average | 0.205167E+11 | 0.191205E+11 | 0.958644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.379081E+10 | 0.620355E+10 |
Minimum of Months | 0.156756E+10 | 0.146111E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22510127.39 |
Maximum of Months | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.900438E+09 | 0.132786E+10 |
Report: SpaceGainsMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.161274E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124936E+10 |
February | 0.156756E+10 | 0.146111E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.897138E+09 |
March | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2423143.20 | 0.784564E+09 |
April | 0.169125E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.220111E+09 | 0.317083E+09 |
May | 0.174872E+10 | 0.163243E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.528494E+09 | 98879395.86 |
June | 0.171530E+10 | 0.159501E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.900634E+09 | 28218173.24 |
July | 0.172466E+10 | 0.160290E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.819980E+09 | 22316156.82 |
August | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.695639E+09 | 44446538.35 |
September | 0.169125E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.504621E+09 | 57573596.75 |
October | 0.172174E+10 | 0.161274E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119798E+09 | 0.373084E+09 |
November | 0.165844E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 499.53 | 0.978294E+09 |
December | 0.172466E+10 | 0.160290E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132393E+10 |
Annual Sum or Average | 0.205167E+11 | 0.191205E+11 | 0.958644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.379170E+10 | 0.617488E+10 |
Minimum of Months | 0.156756E+10 | 0.146111E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22316156.82 |
Maximum of Months | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.900634E+09 | 0.132393E+10 |
Report: SpaceGainsMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.161274E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123640E+10 |
February | 0.156756E+10 | 0.146111E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.883335E+09 |
March | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2423143.42 | 0.767741E+09 |
April | 0.169125E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.220472E+09 | 0.311245E+09 |
May | 0.174872E+10 | 0.163243E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.528898E+09 | 96987293.10 |
June | 0.171530E+10 | 0.159501E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.900872E+09 | 27601800.00 |
July | 0.172466E+10 | 0.160290E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.820101E+09 | 21866518.36 |
August | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.695659E+09 | 44087924.58 |
September | 0.169125E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.504629E+09 | 57230501.86 |
October | 0.172174E+10 | 0.161274E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119841E+09 | 0.370124E+09 |
November | 0.165844E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 499.59 | 0.966624E+09 |
December | 0.172466E+10 | 0.160290E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131390E+10 |
Annual Sum or Average | 0.205167E+11 | 0.191205E+11 | 0.958644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.379290E+10 | 0.609714E+10 |
Minimum of Months | 0.156756E+10 | 0.146111E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21866518.36 |
Maximum of Months | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.900872E+09 | 0.131390E+10 |
Report: SpaceGainsMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.161274E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153008E+10 |
February | 0.156756E+10 | 0.146111E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113404E+10 |
March | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2547920.51 | 0.101805E+10 |
April | 0.169125E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.236458E+09 | 0.458871E+09 |
May | 0.174872E+10 | 0.163243E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.571759E+09 | 0.179215E+09 |
June | 0.171530E+10 | 0.159501E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.972947E+09 | 58943521.90 |
July | 0.172466E+10 | 0.160290E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.873390E+09 | 48990567.45 |
August | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.735662E+09 | 85030248.56 |
September | 0.169125E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.516810E+09 | 0.110701E+09 |
October | 0.172174E+10 | 0.161274E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123992E+09 | 0.526007E+09 |
November | 0.165844E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 523.07 | 0.122407E+10 |
December | 0.172466E+10 | 0.160290E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158484E+10 |
Annual Sum or Average | 0.205167E+11 | 0.191205E+11 | 0.958644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.403357E+10 | 0.795884E+10 |
Minimum of Months | 0.156756E+10 | 0.146111E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48990567.45 |
Maximum of Months | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.972947E+09 | 0.158484E+10 |
Report: PeakSpaceGainsMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 4050.04 | 01-JAN-13:09 | 4621.63 | 01-JAN-10:09 | 1343.25 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 4759.78 | 26-JAN-12:10 |
February | 4050.04 | 03-FEB-13:09 | 4621.63 | 01-FEB-10:09 | 1343.25 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 4422.53 | 08-FEB-18:00 |
March | 4050.04 | 03-MAR-13:09 | 4621.63 | 01-MAR-10:09 | 1343.25 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 295.61 | 22-MAR-13:00 | 4306.07 | 01-MAR-18:00 |
April | 4050.04 | 01-APR-12:09 | 4621.63 | 01-APR-09:09 | 1343.25 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2329.01 | 21-APR-15:00 | 2876.29 | 06-APR-12:00 |
May | 4050.04 | 05-MAY-12:09 | 4621.63 | 01-MAY-09:09 | 1343.25 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2978.24 | 19-MAY-14:00 | 1256.28 | 01-MAY-12:00 |
June | 4050.04 | 02-JUN-12:09 | 4621.63 | 01-JUN-09:09 | 1343.25 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3756.85 | 02-JUN-16:00 | 767.04 | 28-JUN-02:00 |
July | 4050.04 | 01-JUL-12:09 | 4621.63 | 01-JUL-09:09 | 1343.25 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3667.72 | 03-JUL-17:00 | 605.29 | 08-JUL-15:00 |
August | 4050.04 | 04-AUG-12:09 | 4621.63 | 01-AUG-09:09 | 1343.25 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3392.41 | 07-AUG-16:00 | 810.91 | 14-AUG-11:10 |
September | 4050.04 | 01-SEP-12:09 | 4621.63 | 01-SEP-09:09 | 1343.25 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2506.35 | 19-SEP-14:00 | 1642.21 | 23-SEP-17:00 |
October | 4050.04 | 01-OCT-12:09 | 4621.63 | 01-OCT-09:09 | 1343.25 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2302.69 | 01-OCT-15:00 | 2750.72 | 24-OCT-11:10 |
November | 4050.04 | 03-NOV-12:09 | 4621.63 | 01-NOV-09:09 | 1343.25 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.77 | 03-NOV-16:00 | 4314.21 | 26-NOV-18:00 |
December | 4050.04 | 01-DEC-13:09 | 4621.63 | 01-DEC-10:09 | 1343.25 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 5586.00 | 26-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 4050.04 | 4621.63 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 605.29 | |||||
Maximum of Months | 4050.04 | 4621.63 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 3756.85 | 5586.00 |
Report: PeakSpaceGainsMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 01-JAN-13:09 | 2827.07 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2613.89 | 26-JAN-12:10 |
February | 2024.96 | 03-FEB-13:09 | 2827.07 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2376.75 | 08-FEB-18:00 |
March | 2024.96 | 03-MAR-13:09 | 2827.07 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 158.50 | 22-MAR-13:00 | 2330.08 | 01-MAR-18:00 |
April | 2024.96 | 01-APR-12:09 | 2827.07 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1213.30 | 21-APR-15:00 | 1597.21 | 11-APR-11:10 |
May | 2024.96 | 05-MAY-12:09 | 2827.07 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1582.04 | 19-MAY-14:00 | 668.82 | 01-MAY-12:00 |
June | 2024.96 | 02-JUN-12:09 | 2827.07 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2048.26 | 02-JUN-16:00 | 228.89 | 28-JUN-02:00 |
July | 2024.96 | 01-JUL-12:09 | 2827.07 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1980.08 | 03-JUL-17:00 | 325.28 | 08-JUL-15:00 |
August | 2024.96 | 04-AUG-12:09 | 2827.07 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1840.00 | 07-AUG-16:00 | 448.44 | 14-AUG-11:10 |
September | 2024.96 | 01-SEP-12:09 | 2827.07 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1376.39 | 19-SEP-14:00 | 892.80 | 23-SEP-17:00 |
October | 2024.96 | 01-OCT-12:09 | 2827.07 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1248.93 | 01-OCT-15:00 | 1583.57 | 24-OCT-11:10 |
November | 2024.96 | 03-NOV-12:09 | 2827.07 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.42 | 03-NOV-16:00 | 2329.09 | 26-NOV-18:00 |
December | 2024.96 | 01-DEC-13:09 | 2827.07 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3072.62 | 26-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 2827.07 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 228.89 | |||||
Maximum of Months | 2024.96 | 2827.07 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 2048.26 | 3072.62 |
Report: PeakSpaceGainsMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 2555.22 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2613.89 | 26-JAN-12:10 |
February | 2024.96 | 04-FEB-13:09 | 2555.22 | 01-FEB-09:09 | 671.63 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2349.84 | 08-FEB-18:00 |
March | 2024.96 | 04-MAR-13:09 | 2555.22 | 01-MAR-09:09 | 671.63 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 158.50 | 22-MAR-13:00 | 2330.08 | 01-MAR-18:00 |
April | 2024.96 | 01-APR-12:09 | 2555.22 | 01-APR-08:09 | 671.63 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1213.30 | 21-APR-15:00 | 1588.06 | 11-APR-11:10 |
May | 2024.96 | 06-MAY-12:09 | 2555.22 | 01-MAY-08:09 | 671.63 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1582.04 | 19-MAY-14:00 | 668.82 | 01-MAY-12:00 |
June | 2024.96 | 03-JUN-12:09 | 2555.22 | 01-JUN-08:09 | 671.63 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2048.28 | 02-JUN-16:00 | 235.06 | 28-JUN-02:00 |
July | 2024.96 | 01-JUL-12:09 | 2555.22 | 01-JUL-08:09 | 671.63 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1980.09 | 03-JUL-17:00 | 325.28 | 08-JUL-15:00 |
August | 2024.96 | 05-AUG-12:09 | 2555.22 | 01-AUG-08:09 | 671.63 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1840.02 | 07-AUG-16:00 | 448.44 | 14-AUG-11:10 |
September | 2024.96 | 02-SEP-12:09 | 2555.22 | 01-SEP-08:09 | 671.63 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1376.39 | 19-SEP-14:00 | 892.73 | 23-SEP-17:00 |
October | 2024.96 | 07-OCT-12:09 | 2555.22 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1248.93 | 01-OCT-15:00 | 1582.09 | 24-OCT-11:10 |
November | 2024.96 | 04-NOV-12:09 | 2555.22 | 01-NOV-08:09 | 671.63 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.42 | 03-NOV-16:00 | 2329.09 | 26-NOV-18:00 |
December | 2024.96 | 02-DEC-13:09 | 2555.22 | 01-DEC-09:09 | 671.63 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3072.62 | 26-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 2555.22 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 235.06 | |||||
Maximum of Months | 2024.96 | 2555.22 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 2048.28 | 3072.62 |
Report: PeakSpaceGainsMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 2555.22 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2613.89 | 26-JAN-12:10 |
February | 2024.96 | 04-FEB-13:09 | 2555.22 | 01-FEB-09:09 | 671.63 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2327.89 | 08-FEB-18:00 |
March | 2024.96 | 04-MAR-13:09 | 2555.22 | 01-MAR-09:09 | 671.63 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 158.50 | 22-MAR-13:00 | 2330.08 | 01-MAR-18:00 |
April | 2024.96 | 01-APR-12:09 | 2555.22 | 01-APR-08:09 | 671.63 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1213.30 | 21-APR-15:00 | 1578.94 | 11-APR-11:10 |
May | 2024.96 | 06-MAY-12:09 | 2555.22 | 01-MAY-08:09 | 671.63 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1582.04 | 19-MAY-14:00 | 668.82 | 01-MAY-12:00 |
June | 2024.96 | 03-JUN-12:09 | 2555.22 | 01-JUN-08:09 | 671.63 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2048.27 | 02-JUN-16:00 | 236.30 | 28-JUN-02:00 |
July | 2024.96 | 01-JUL-12:09 | 2555.22 | 01-JUL-08:09 | 671.63 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1980.08 | 03-JUL-17:00 | 325.28 | 08-JUL-15:00 |
August | 2024.96 | 05-AUG-12:09 | 2555.22 | 01-AUG-08:09 | 671.63 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1840.01 | 07-AUG-16:00 | 448.44 | 14-AUG-11:10 |
September | 2024.96 | 02-SEP-12:09 | 2555.22 | 01-SEP-08:09 | 671.63 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1376.39 | 19-SEP-14:00 | 892.73 | 23-SEP-17:00 |
October | 2024.96 | 07-OCT-12:09 | 2555.22 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1248.93 | 01-OCT-15:00 | 1578.28 | 24-OCT-11:10 |
November | 2024.96 | 04-NOV-12:09 | 2555.22 | 01-NOV-08:09 | 671.63 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.42 | 03-NOV-16:00 | 2329.09 | 26-NOV-18:00 |
December | 2024.96 | 02-DEC-13:09 | 2555.22 | 01-DEC-09:09 | 671.63 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3072.62 | 26-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 2555.22 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 236.30 | |||||
Maximum of Months | 2024.96 | 2555.22 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 2048.27 | 3072.62 |
Report: PeakSpaceGainsMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 2555.22 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2613.89 | 26-JAN-12:10 |
February | 2024.96 | 04-FEB-13:09 | 2555.22 | 01-FEB-09:09 | 671.63 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2290.28 | 08-FEB-18:00 |
March | 2024.96 | 04-MAR-13:09 | 2555.22 | 01-MAR-09:09 | 671.63 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 158.50 | 22-MAR-13:00 | 2330.08 | 01-MAR-18:00 |
April | 2024.96 | 01-APR-12:09 | 2555.22 | 01-APR-08:09 | 671.63 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1213.30 | 21-APR-15:00 | 1555.04 | 11-APR-11:10 |
May | 2024.96 | 06-MAY-12:09 | 2555.22 | 01-MAY-08:09 | 671.63 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1582.04 | 19-MAY-14:00 | 668.82 | 01-MAY-12:00 |
June | 2024.96 | 03-JUN-12:09 | 2555.22 | 01-JUN-08:09 | 671.63 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2048.29 | 02-JUN-16:00 | 232.64 | 28-JUN-02:00 |
July | 2024.96 | 01-JUL-12:09 | 2555.22 | 01-JUL-08:09 | 671.63 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1980.09 | 03-JUL-17:00 | 325.28 | 08-JUL-15:00 |
August | 2024.96 | 05-AUG-12:09 | 2555.22 | 01-AUG-08:09 | 671.63 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1840.01 | 07-AUG-16:00 | 448.44 | 14-AUG-11:10 |
September | 2024.96 | 02-SEP-12:09 | 2555.22 | 01-SEP-08:09 | 671.63 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1376.39 | 19-SEP-14:00 | 892.72 | 23-SEP-17:00 |
October | 2024.96 | 07-OCT-12:09 | 2555.22 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1248.93 | 01-OCT-15:00 | 1560.64 | 24-OCT-11:10 |
November | 2024.96 | 04-NOV-12:09 | 2555.22 | 01-NOV-08:09 | 671.63 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.42 | 03-NOV-16:00 | 2329.09 | 26-NOV-18:00 |
December | 2024.96 | 02-DEC-13:09 | 2555.22 | 01-DEC-09:09 | 671.63 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3072.62 | 26-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 2555.22 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 232.64 | |||||
Maximum of Months | 2024.96 | 2555.22 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 2048.29 | 3072.62 |
Report: PeakSpaceGainsMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 5400.05 | 07-JAN-15:09 | 2726.96 | 01-JAN-11:09 | 1343.25 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 4695.52 | 26-JAN-12:10 |
February | 5400.05 | 04-FEB-15:09 | 2726.96 | 01-FEB-10:09 | 1343.25 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 4040.79 | 08-FEB-18:00 |
March | 5400.05 | 04-MAR-15:09 | 2726.96 | 01-MAR-10:09 | 1343.25 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 285.58 | 22-MAR-13:00 | 4193.35 | 01-MAR-18:00 |
April | 5400.05 | 01-APR-14:09 | 2726.96 | 01-APR-09:09 | 1343.25 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2194.06 | 21-APR-15:00 | 2722.34 | 11-APR-11:10 |
May | 5400.05 | 06-MAY-14:09 | 2726.96 | 01-MAY-09:09 | 1343.25 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2853.75 | 19-MAY-14:00 | 1206.11 | 01-MAY-12:00 |
June | 5400.05 | 03-JUN-14:09 | 2726.96 | 01-JUN-09:09 | 1343.25 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3682.73 | 02-JUN-16:00 | 445.47 | 28-JUN-02:00 |
July | 5400.05 | 01-JUL-14:09 | 2726.96 | 01-JUL-09:09 | 1343.25 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3564.48 | 03-JUL-17:00 | 585.90 | 08-JUL-15:00 |
August | 5400.05 | 05-AUG-14:09 | 2726.96 | 01-AUG-09:09 | 1343.25 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3310.36 | 07-AUG-16:00 | 804.87 | 14-AUG-11:10 |
September | 5400.05 | 02-SEP-14:09 | 2726.96 | 01-SEP-09:09 | 1343.25 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2472.51 | 19-SEP-14:00 | 1605.63 | 23-SEP-17:00 |
October | 5400.05 | 07-OCT-14:09 | 2726.96 | 01-OCT-10:09 | 1343.25 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2247.00 | 01-OCT-15:00 | 2738.05 | 24-OCT-11:10 |
November | 5400.05 | 04-NOV-14:09 | 2726.96 | 01-NOV-09:09 | 1343.25 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.75 | 08-NOV-15:00 | 4192.77 | 26-NOV-18:00 |
December | 5400.05 | 02-DEC-15:09 | 2726.96 | 01-DEC-10:09 | 1343.25 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 5518.47 | 26-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 5400.05 | 2726.96 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 445.47 | |||||
Maximum of Months | 5400.05 | 2726.96 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 3682.73 | 5518.47 |
Report: PeakSpaceGainsMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1404.46 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2613.89 | 26-JAN-12:10 |
February | 2699.95 | 04-FEB-15:09 | 1404.46 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2231.45 | 08-FEB-18:00 |
March | 2699.95 | 04-MAR-15:09 | 1404.46 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 158.50 | 22-MAR-13:00 | 2330.08 | 01-MAR-18:00 |
April | 2699.95 | 01-APR-14:09 | 1404.46 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1213.30 | 21-APR-15:00 | 1506.11 | 11-APR-11:10 |
May | 2699.95 | 06-MAY-14:09 | 1404.46 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1582.04 | 19-MAY-14:00 | 668.82 | 01-MAY-12:00 |
June | 2699.95 | 03-JUN-14:09 | 1404.46 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2048.26 | 02-JUN-16:00 | 221.18 | 28-JUN-02:00 |
July | 2699.95 | 01-JUL-14:09 | 1404.46 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1980.06 | 03-JUL-17:00 | 325.28 | 08-JUL-15:00 |
August | 2699.95 | 05-AUG-14:09 | 1404.46 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1839.97 | 07-AUG-16:00 | 448.44 | 14-AUG-11:10 |
September | 2699.95 | 02-SEP-14:09 | 1404.46 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1376.39 | 19-SEP-14:00 | 892.71 | 23-SEP-17:00 |
October | 2699.95 | 07-OCT-14:09 | 1404.46 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1248.93 | 01-OCT-15:00 | 1521.50 | 24-OCT-11:10 |
November | 2699.95 | 04-NOV-14:09 | 1404.46 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.42 | 08-NOV-15:00 | 2329.09 | 26-NOV-18:00 |
December | 2699.95 | 02-DEC-15:09 | 1404.46 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3072.62 | 26-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 221.18 | |||||
Maximum of Months | 2699.95 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 2048.26 | 3072.62 |
Report: PeakSpaceGainsMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1404.46 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2613.89 | 26-JAN-12:10 |
February | 2699.95 | 04-FEB-15:09 | 1404.46 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2231.40 | 08-FEB-18:00 |
March | 2699.95 | 04-MAR-15:09 | 1404.46 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 158.50 | 22-MAR-13:00 | 2330.08 | 01-MAR-18:00 |
April | 2699.95 | 01-APR-14:09 | 1404.46 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1213.30 | 21-APR-15:00 | 1496.14 | 11-APR-11:10 |
May | 2699.95 | 06-MAY-14:09 | 1404.46 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1582.04 | 19-MAY-14:00 | 668.82 | 01-MAY-12:00 |
June | 2699.95 | 03-JUN-14:09 | 1404.46 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2048.26 | 02-JUN-16:00 | 220.39 | 28-JUN-02:00 |
July | 2699.95 | 01-JUL-14:09 | 1404.46 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1980.06 | 03-JUL-17:00 | 325.28 | 08-JUL-15:00 |
August | 2699.95 | 05-AUG-14:09 | 1404.46 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1839.97 | 07-AUG-16:00 | 448.44 | 14-AUG-11:10 |
September | 2699.95 | 02-SEP-14:09 | 1404.46 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1376.39 | 19-SEP-14:00 | 892.71 | 23-SEP-17:00 |
October | 2699.95 | 07-OCT-14:09 | 1404.46 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1248.93 | 01-OCT-15:00 | 1514.97 | 24-OCT-11:10 |
November | 2699.95 | 04-NOV-14:09 | 1404.46 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.42 | 08-NOV-15:00 | 2329.09 | 26-NOV-18:00 |
December | 2699.95 | 02-DEC-15:09 | 1404.46 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3072.62 | 26-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 220.39 | |||||
Maximum of Months | 2699.95 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 2048.26 | 3072.62 |
Report: PeakSpaceGainsMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1404.46 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2613.89 | 26-JAN-12:10 |
February | 2699.95 | 04-FEB-15:09 | 1404.46 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2231.40 | 08-FEB-18:00 |
March | 2699.95 | 04-MAR-15:09 | 1404.46 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 158.50 | 22-MAR-13:00 | 2330.08 | 01-MAR-18:00 |
April | 2699.95 | 01-APR-14:09 | 1404.46 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1213.30 | 21-APR-15:00 | 1467.80 | 11-APR-11:10 |
May | 2699.95 | 06-MAY-14:09 | 1404.46 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1582.04 | 19-MAY-14:00 | 668.81 | 01-MAY-12:00 |
June | 2699.95 | 03-JUN-14:09 | 1404.46 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2048.26 | 02-JUN-16:00 | 218.68 | 28-JUN-02:00 |
July | 2699.95 | 01-JUL-14:09 | 1404.46 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1980.06 | 03-JUL-17:00 | 325.28 | 08-JUL-15:00 |
August | 2699.95 | 05-AUG-14:09 | 1404.46 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1839.96 | 07-AUG-16:00 | 448.44 | 14-AUG-11:10 |
September | 2699.95 | 02-SEP-14:09 | 1404.46 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1376.39 | 19-SEP-14:00 | 892.71 | 23-SEP-17:00 |
October | 2699.95 | 07-OCT-14:09 | 1404.46 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1248.93 | 01-OCT-15:00 | 1492.52 | 24-OCT-11:10 |
November | 2699.95 | 04-NOV-14:09 | 1404.46 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.42 | 08-NOV-15:00 | 2329.09 | 26-NOV-18:00 |
December | 2699.95 | 02-DEC-15:09 | 1404.46 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3072.62 | 26-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 218.68 | |||||
Maximum of Months | 2699.95 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 2048.26 | 3072.62 |
Report: PeakSpaceGainsMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1404.46 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2678.15 | 26-JAN-12:10 |
February | 2699.95 | 04-FEB-15:09 | 1404.46 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2519.17 | 08-FEB-18:00 |
March | 2699.95 | 04-MAR-15:09 | 1404.46 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 168.54 | 22-MAR-13:00 | 2442.80 | 01-MAR-18:00 |
April | 2699.95 | 01-APR-14:09 | 1404.46 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1348.25 | 21-APR-15:00 | 1628.92 | 06-APR-12:00 |
May | 2699.95 | 06-MAY-14:09 | 1404.46 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1706.53 | 19-MAY-14:00 | 719.02 | 01-MAY-12:00 |
June | 2699.95 | 03-JUN-14:09 | 1404.46 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2122.39 | 02-JUN-16:00 | 513.61 | 28-JUN-02:00 |
July | 2699.95 | 01-JUL-14:09 | 1404.46 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2083.28 | 03-JUL-17:00 | 344.67 | 08-JUL-15:00 |
August | 2699.95 | 05-AUG-14:09 | 1404.46 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1921.93 | 07-AUG-16:00 | 470.34 | 14-AUG-01:00 |
September | 2699.95 | 02-SEP-14:09 | 1404.46 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1410.22 | 19-SEP-14:00 | 929.11 | 23-SEP-17:00 |
October | 2699.95 | 07-OCT-14:09 | 1404.46 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1304.62 | 01-OCT-15:00 | 1456.60 | 24-OCT-11:10 |
November | 2699.95 | 04-NOV-14:09 | 1404.46 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.44 | 03-NOV-16:00 | 2450.53 | 26-NOV-18:00 |
December | 2699.95 | 02-DEC-15:09 | 1404.46 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3140.15 | 26-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 344.67 | |||||
Maximum of Months | 2699.95 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 2122.39 | 3140.15 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7720.11 | 28-JAN-00:12 | 1350.01 | 9729.72 | 2985.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.28 |
February | 7569.40 | 03-FEB-00:03 | 1350.01 | 972.92 | 2985.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.53 |
March | 6508.74 | 16-MAR-17:10 | 3375.03 | 4621.63 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 156.09 |
April | 11876.36 | 30-APR-16:04 | 20250.19 | 23108.15 | 6716.25 | 0.00 | 0.00 | 0.00 | 0.00 | 1709.19 | 0.00 |
May | 27077.75 | 31-MAY-07:03 | 1350.01 | 300.00 | 298.50 | 0.00 | 0.00 | 0.00 | 0.00 | 52.52 | 0.00 |
June | 38504.07 | 06-JUN-07:02 | 1687.52 | 375.00 | 373.12 | 0.00 | 0.00 | 0.00 | 0.00 | 34.83 | 0.00 |
July | 39464.08 | 03-JUL-07:01 | 3037.53 | 675.00 | 671.62 | 0.00 | 0.00 | 0.00 | 0.00 | 113.53 | 0.00 |
August | 38258.13 | 07-AUG-07:01 | 2700.03 | 600.00 | 597.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.16 | 0.00 |
September | 32996.71 | 13-SEP-07:02 | 1687.52 | 375.00 | 373.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.65 |
October | 40228.53 | 02-OCT-07:02 | 2025.02 | 450.00 | 447.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.02 |
November | 9233.45 | 09-NOV-15:00 | 2700.03 | 4621.63 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 157.88 |
December | 7609.05 | 30-DEC-00:12 | 1350.01 | 9729.72 | 2985.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.86 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 6508.74 | 1350.01 | 300.00 | 298.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 40228.53 | 20250.19 | 23108.15 | 6716.25 | 0.00 | 0.00 | 0.00 | 0.00 | 1709.19 | 157.88 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3554.96 | 01-JAN-18:10 | 4049.92 | 5654.14 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 243.99 |
February | 16385.04 | 19-FEB-18:35 | 16199.69 | 22616.54 | 5373.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.58 |
March | 16647.57 | 19-MAR-17:08 | 16199.69 | 22616.54 | 5373.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 119.53 |
April | 17031.69 | 05-APR-21:22 | 8099.84 | 22616.54 | 5373.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.16 |
May | 16730.81 | 06-MAY-22:05 | 5399.90 | 22616.54 | 5373.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.34 |
June | 20158.22 | 06-JUN-07:02 | 843.73 | 187.50 | 186.56 | 0.00 | 0.00 | 0.00 | 0.00 | 13.25 | 0.00 |
July | 20503.26 | 03-JUL-07:01 | 1518.72 | 337.50 | 335.81 | 0.00 | 0.00 | 0.00 | 0.00 | 53.84 | 0.00 |
August | 20451.18 | 27-AUG-07:02 | 843.73 | 187.50 | 186.56 | 0.00 | 0.00 | 0.00 | 0.00 | 6.10 | 0.00 |
September | 17465.71 | 30-SEP-20:05 | 6074.88 | 16962.41 | 4029.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 20802.86 | 02-OCT-07:02 | 1012.48 | 225.00 | 223.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.07 |
November | 16437.38 | 09-NOV-22:10 | 7087.36 | 19789.47 | 4701.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.62 |
December | 3759.07 | 26-DEC-09:23 | 506.24 | 4463.79 | 1119.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 474.38 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3554.96 | 506.24 | 187.50 | 186.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 20802.86 | 16199.69 | 22616.54 | 5373.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.84 | 474.38 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3919.26 | 05-JAN-08:61 | 1687.47 | 375.00 | 3731.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 489.60 |
February | 3630.88 | 09-FEB-08:61 | 1518.72 | 337.50 | 3358.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 399.37 |
March | 3574.46 | 18-MAR-07:01 | 1349.97 | 300.00 | 2985.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 430.18 |
April | 5975.38 | 21-APR-14:00 | 1012.48 | 2555.22 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1208.54 | 0.00 |
May | 21084.66 | 31-MAY-06:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 |
June | 22728.14 | 06-JUN-06:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.55 |
July | 20974.13 | 03-JUL-06:01 | 0.00 | 300.00 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 3.56 | 0.00 |
August | 22513.27 | 23-AUG-06:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.05 |
September | 21846.53 | 18-SEP-06:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.64 |
October | 22072.29 | 02-OCT-06:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.15 |
November | 4852.37 | 09-NOV-14:00 | 1349.97 | 2555.22 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.73 |
December | 3689.77 | 12-DEC-08:61 | 1518.72 | 337.50 | 3358.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 440.49 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3574.46 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22728.14 | 1687.47 | 2555.22 | 3731.25 | 0.00 | 0.00 | 0.00 | 0.00 | 1208.54 | 489.60 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3876.33 | 05-JAN-08:61 | 1687.47 | 375.00 | 3731.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 484.46 |
February | 3599.16 | 09-FEB-08:61 | 1518.72 | 337.50 | 3358.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 395.96 |
March | 3544.71 | 18-MAR-07:01 | 1349.97 | 300.00 | 2985.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 426.66 |
April | 5958.14 | 21-APR-14:00 | 1012.48 | 2555.22 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1208.54 | 0.00 |
May | 21245.53 | 31-MAY-06:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.69 |
June | 22659.37 | 06-JUN-06:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.76 |
July | 20886.16 | 03-JUL-06:01 | 0.00 | 300.00 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 3.11 | 0.00 |
August | 23054.25 | 23-AUG-06:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.07 |
September | 22024.68 | 20-SEP-06:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 22012.89 | 02-OCT-06:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.31 |
November | 4770.20 | 09-NOV-14:00 | 1349.97 | 2555.22 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.73 |
December | 3641.27 | 12-DEC-08:61 | 1518.72 | 337.50 | 3358.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 435.05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3544.71 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 23054.25 | 1687.47 | 2555.22 | 3731.25 | 0.00 | 0.00 | 0.00 | 0.00 | 1208.54 | 484.46 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3724.37 | 27-JAN-09:23 | 1012.48 | 7665.65 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 487.71 |
February | 3546.64 | 09-FEB-08:61 | 1518.72 | 337.50 | 3358.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 390.89 |
March | 3487.38 | 18-MAR-07:01 | 1349.97 | 300.00 | 2985.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 420.62 |
April | 5781.37 | 21-APR-14:00 | 1012.48 | 2555.22 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1208.54 | 0.00 |
May | 19815.83 | 31-MAY-06:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.64 |
June | 22540.04 | 06-JUN-06:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.35 |
July | 20867.03 | 03-JUL-06:01 | 0.00 | 300.00 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 3.46 | 0.00 |
August | 21920.08 | 28-AUG-06:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.33 |
September | 21804.03 | 18-SEP-06:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.64 |
October | 21896.29 | 02-OCT-06:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.97 |
November | 4559.50 | 09-NOV-14:00 | 1349.97 | 2555.22 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.73 |
December | 2859.92 | 08-DEC-08:61 | 1349.97 | 300.00 | 2985.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 381.93 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2859.92 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22540.04 | 1518.72 | 7665.65 | 3358.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1208.54 | 487.71 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4645.18 | 04-JAN-19:30 | 1755.02 | 2726.96 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 502.99 |
February | 5512.21 | 24-FEB-09:03 | 2227.52 | 225.00 | 2238.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 792.12 |
March | 5609.07 | 17-MAR-08:63 | 2227.52 | 225.00 | 2238.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 715.08 |
April | 10404.27 | 21-APR-14:30 | 4657.54 | 2726.96 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 2189.18 | 0.00 |
May | 28546.87 | 30-MAY-07:03 | 0.00 | 300.00 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 74.01 | 0.00 |
June | 36347.26 | 06-JUN-07:02 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 22.09 | 0.00 |
July | 37009.13 | 03-JUL-07:01 | 0.00 | 675.00 | 662.75 | 0.00 | 0.00 | 0.00 | 0.00 | 80.90 | 0.00 |
August | 37082.16 | 28-AUG-07:02 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.40 |
September | 32113.81 | 18-SEP-07:03 | 0.00 | 300.00 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 110.74 |
October | 37743.51 | 02-OCT-07:02 | 0.00 | 450.00 | 441.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.76 |
November | 7898.37 | 09-NOV-14:00 | 4792.55 | 2726.96 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 156.17 |
December | 3941.47 | 18-DEC-12:00 | 2902.53 | 2726.96 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 588.54 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3941.47 | 0.00 | 225.00 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 37743.51 | 4792.55 | 2726.96 | 2238.75 | 0.00 | 0.00 | 0.00 | 0.00 | 2189.18 | 792.12 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2819.88 | 26-JAN-13:03 | 7188.61 | 4213.39 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2451.16 |
February | 2730.66 | 08-FEB-18:30 | 1147.48 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 468.43 |
March | 2782.16 | 16-MAR-15:00 | 2328.71 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 161.71 |
April | 5406.23 | 21-APR-14:40 | 2328.71 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1211.72 | 0.00 |
May | 14187.25 | 30-MAY-07:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 40.36 | 0.00 |
June | 18642.93 | 06-JUN-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.03 | 0.00 |
July | 19052.32 | 03-JUL-07:01 | 0.00 | 337.50 | 331.38 | 0.00 | 0.00 | 0.00 | 0.00 | 44.94 | 0.00 |
August | 19152.54 | 28-AUG-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.82 |
September | 15847.58 | 18-SEP-07:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.04 |
October | 19496.60 | 02-OCT-07:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.29 |
November | 4031.78 | 09-NOV-14:00 | 2396.20 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.73 |
December | 2563.71 | 18-DEC-17:55 | 4792.41 | 2808.93 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2331.58 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2563.71 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19496.60 | 7188.61 | 4213.39 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 1211.72 | 2451.16 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3006.56 | 26-JAN-20:43 | 1113.73 | 2217.58 | 1119.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.09 |
February | 2686.58 | 24-FEB-09:03 | 1113.73 | 112.50 | 1119.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 423.38 |
March | 2736.57 | 17-MAR-08:63 | 1113.73 | 112.50 | 1119.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 386.54 |
April | 5346.86 | 21-APR-14:40 | 2328.71 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1211.72 | 0.00 |
May | 13773.15 | 30-MAY-07:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 40.47 | 0.00 |
June | 18552.72 | 06-JUN-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.40 | 0.00 |
July | 18976.11 | 03-JUL-07:01 | 0.00 | 337.50 | 331.38 | 0.00 | 0.00 | 0.00 | 0.00 | 45.09 | 0.00 |
August | 19035.76 | 28-AUG-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.68 |
September | 15714.73 | 13-SEP-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.47 |
October | 19365.00 | 02-OCT-07:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.89 |
November | 3951.76 | 09-NOV-14:00 | 2396.20 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.73 |
December | 2726.51 | 02-DEC-18:33 | 1113.73 | 2217.58 | 1119.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 375.32 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2686.58 | 0.00 | 112.50 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19365.00 | 2396.20 | 2217.58 | 1119.38 | 0.00 | 0.00 | 0.00 | 0.00 | 1211.72 | 423.38 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3155.11 | 26-JAN-20:03 | 1113.73 | 2217.58 | 1119.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.83 |
February | 3055.67 | 01-FEB-20:33 | 1113.73 | 2217.58 | 1119.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.52 |
March | 2665.62 | 17-MAR-08:63 | 1113.73 | 112.50 | 1119.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 377.90 |
April | 5232.64 | 21-APR-14:40 | 2328.71 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1211.72 | 0.00 |
May | 12209.28 | 30-MAY-07:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 40.89 | 0.00 |
June | 18545.01 | 18-JUN-08:62 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 36.72 | 0.00 |
July | 18990.05 | 03-JUL-07:01 | 0.00 | 337.50 | 331.38 | 0.00 | 0.00 | 0.00 | 0.00 | 45.54 | 0.00 |
August | 19031.17 | 28-AUG-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.10 |
September | 15682.71 | 13-SEP-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.44 |
October | 19337.82 | 02-OCT-07:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.87 |
November | 3805.58 | 09-NOV-14:00 | 2396.20 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.73 |
December | 3039.38 | 29-DEC-20:23 | 1113.73 | 2217.58 | 1119.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.23 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2665.62 | 0.00 | 112.50 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19337.82 | 2396.20 | 2217.58 | 1119.38 | 0.00 | 0.00 | 0.00 | 0.00 | 1211.72 | 377.90 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2464.76 | 26-JAN-18:15 | 2294.96 | 2808.93 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 360.91 |
February | 2391.35 | 01-FEB-18:45 | 2294.96 | 2808.93 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 433.60 |
March | 2246.98 | 16-MAR-14:40 | 2328.71 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 176.13 |
April | 5654.02 | 21-APR-14:20 | 2328.71 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1339.13 | 0.00 |
May | 9602.26 | 30-MAY-07:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 53.40 | 0.00 |
June | 20402.71 | 18-JUN-08:62 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 41.70 | 0.00 |
July | 20825.89 | 03-JUL-07:01 | 0.00 | 337.50 | 331.38 | 0.00 | 0.00 | 0.00 | 0.00 | 52.27 | 0.00 |
August | 20677.75 | 28-AUG-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.87 |
September | 16991.98 | 13-SEP-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.18 |
October | 21166.56 | 02-OCT-07:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.75 |
November | 4033.71 | 09-NOV-14:00 | 2396.20 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.57 |
December | 2328.19 | 28-DEC-18:35 | 2294.96 | 2808.93 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 331.98 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2246.98 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21166.56 | 2396.20 | 2808.93 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 1339.13 | 433.60 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.630444E+11 | 53033.54 | 24-JAN-18:40 | 0.177311E+11 | 106337.82 | 27-JAN-08:09 |
February | 0.569628E+11 | 51486.55 | 21-FEB-15:00 | 0.959249E+10 | 108713.28 | 03-FEB-08:09 |
March | 0.638946E+11 | 55630.03 | 21-MAR-16:30 | 0.512294E+10 | 105390.61 | 02-MAR-08:09 |
April | 0.700342E+11 | 69309.92 | 29-APR-15:09 | 97233251.18 | 14346.58 | 11-APR-08:30 |
May | 0.830419E+11 | 75147.52 | 30-MAY-15:50 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 0.919763E+11 | 88548.95 | 02-JUN-16:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 0.965902E+11 | 84906.14 | 03-JUL-16:30 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.937636E+11 | 86748.91 | 07-AUG-16:40 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.865045E+11 | 77336.97 | 16-SEP-11:00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 0.742248E+11 | 76379.92 | 03-OCT-14:20 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 0.616245E+11 | 58851.35 | 09-NOV-14:00 | 0.433568E+10 | 72766.43 | 28-NOV-08:09 |
December | 0.630904E+11 | 55170.94 | 12-DEC-18:49 | 0.233543E+11 | 115995.83 | 27-DEC-08:09 |
Annual Sum or Average | 0.904752E+12 | 0.602338E+11 | ||||
Minimum of Months | 0.569628E+11 | 51486.55 | 0.00 | 0.00 | ||
Maximum of Months | 0.965902E+11 | 88548.95 | 0.233543E+11 | 115995.83 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.310073E+11 | 0.625132E+10 | 0.108325E+11 | 0.00 | 0.951349E+10 | 0.00 | 0.00 | 4138831.65 | 0.00 | 0.00 | 0.00 | 0.543570E+10 | 0.00 |
February | 0.280657E+11 | 0.524025E+10 | 0.980803E+10 | 0.00 | 0.853136E+10 | 0.00 | 0.00 | 0.406819E+09 | 0.00 | 0.00 | 0.00 | 0.491061E+10 | 0.00 |
March | 0.314703E+11 | 0.522370E+10 | 0.110075E+11 | 0.00 | 0.951153E+10 | 0.00 | 0.00 | 0.127303E+10 | 0.00 | 0.00 | 0.00 | 0.540859E+10 | 0.00 |
April | 0.300741E+11 | 0.447365E+10 | 0.105079E+11 | 0.00 | 0.896994E+10 | 0.00 | 0.00 | 0.109190E+11 | 0.00 | 0.00 | 0.00 | 0.508958E+10 | 0.00 |
May | 0.312330E+11 | 0.412339E+10 | 0.109147E+11 | 0.00 | 0.929824E+10 | 0.00 | 0.00 | 0.223167E+11 | 0.00 | 0.00 | 0.00 | 0.515591E+10 | 0.00 |
June | 0.304143E+11 | 0.374011E+10 | 0.106386E+11 | 0.00 | 0.917782E+10 | 0.00 | 0.00 | 0.330969E+11 | 0.00 | 0.00 | 0.00 | 0.490857E+10 | 0.00 |
July | 0.309042E+11 | 0.397470E+10 | 0.107945E+11 | 0.00 | 0.931303E+10 | 0.00 | 0.00 | 0.366169E+11 | 0.00 | 0.00 | 0.00 | 0.498693E+10 | 0.00 |
August | 0.314595E+11 | 0.440095E+10 | 0.110006E+11 | 0.00 | 0.944453E+10 | 0.00 | 0.00 | 0.324377E+11 | 0.00 | 0.00 | 0.00 | 0.502036E+10 | 0.00 |
September | 0.300847E+11 | 0.479747E+10 | 0.105148E+11 | 0.00 | 0.898335E+10 | 0.00 | 0.00 | 0.272311E+11 | 0.00 | 0.00 | 0.00 | 0.489311E+10 | 0.00 |
October | 0.310073E+11 | 0.556404E+10 | 0.108325E+11 | 0.00 | 0.929463E+10 | 0.00 | 0.00 | 0.123846E+11 | 0.00 | 0.00 | 0.00 | 0.514182E+10 | 0.00 |
November | 0.300409E+11 | 0.589117E+10 | 0.104978E+11 | 0.00 | 0.907022E+10 | 0.00 | 0.00 | 0.102213E+10 | 0.00 | 0.00 | 0.00 | 0.510217E+10 | 0.00 |
December | 0.309156E+11 | 0.637688E+10 | 0.108050E+11 | 0.00 | 0.960233E+10 | 0.00 | 0.00 | 1273634.47 | 0.00 | 0.00 | 0.00 | 0.538934E+10 | 0.00 |
Annual Sum or Average | 0.366677E+12 | 0.600576E+11 | 0.128154E+12 | 0.00 | 0.110710E+12 | 0.00 | 0.00 | 0.177710E+12 | 0.00 | 0.00 | 0.00 | 0.614427E+11 | 0.00 |
Minimum of Months | 0.280657E+11 | 0.374011E+10 | 0.980803E+10 | 0.00 | 0.853136E+10 | 0.00 | 0.00 | 1273634.47 | 0.00 | 0.00 | 0.00 | 0.489311E+10 | 0.00 |
Maximum of Months | 0.314703E+11 | 0.637688E+10 | 0.110075E+11 | 0.00 | 0.960233E+10 | 0.00 | 0.00 | 0.366169E+11 | 0.00 | 0.00 | 0.00 | 0.543570E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.177311E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.959249E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.512294E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 97233251.18 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.433568E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.233543E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.602338E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.233543E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 23459.17 | 01-JAN-11:09 | 5507.06 | 01-JAN-06:10 | 8059.50 | 01-JAN-11:09 | 0.00 | 8580.71 | 27-JAN-08:09 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 23459.17 | 01-FEB-10:09 | 5507.06 | 01-FEB-06:10 | 8059.50 | 01-FEB-10:09 | 0.00 | 8631.07 | 03-FEB-08:09 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 23459.17 | 01-MAR-10:09 | 5507.06 | 01-MAR-06:10 | 8059.50 | 01-MAR-10:09 | 0.00 | 8560.06 | 02-MAR-08:09 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 23459.17 | 01-APR-09:09 | 5507.06 | 01-APR-05:10 | 8059.50 | 01-APR-09:09 | 0.00 | 6608.84 | 11-APR-08:30 | 0.00 | 0.00 | 01-APR-00:10 |
May | 23459.17 | 01-MAY-09:09 | 5507.06 | 01-MAY-05:10 | 8059.50 | 01-MAY-09:09 | 0.00 | 7081.62 | 31-MAY-07:10 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 23459.17 | 01-JUN-09:09 | 5507.06 | 01-JUN-19:10 | 8059.50 | 01-JUN-09:09 | 0.00 | 7853.89 | 15-JUN-14:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 23459.17 | 01-JUL-09:09 | 5507.06 | 01-JUL-19:19 | 8059.50 | 01-JUL-09:09 | 0.00 | 7941.26 | 03-JUL-07:10 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 23459.17 | 01-AUG-09:09 | 5507.06 | 01-AUG-05:10 | 8059.50 | 01-AUG-09:09 | 0.00 | 8031.32 | 07-AUG-07:10 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 23459.17 | 01-SEP-09:09 | 5507.06 | 01-SEP-05:10 | 8059.50 | 01-SEP-09:09 | 0.00 | 7685.99 | 22-SEP-07:10 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 23459.17 | 01-OCT-10:09 | 5507.06 | 01-OCT-05:10 | 8059.50 | 01-OCT-10:09 | 0.00 | 7455.76 | 02-OCT-07:10 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 23459.17 | 01-NOV-09:09 | 5507.06 | 01-NOV-05:10 | 8059.50 | 01-NOV-09:09 | 0.00 | 7863.41 | 28-NOV-08:09 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 23459.17 | 01-DEC-10:09 | 5507.06 | 01-DEC-06:10 | 8059.50 | 01-DEC-10:09 | 0.00 | 8786.70 | 27-DEC-08:09 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||||
Minimum of Months | 23459.17 | 5507.06 | 8059.50 | 0.00 | 6608.84 | 0.00 | 0.00 | |||||
Maximum of Months | 23459.17 | 5507.06 | 8059.50 | 0.00 | 8786.70 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 492.04 | 03-JAN-14:00 | 0.00 | 0.00 | 0.00 | 11810.58 | 05-JAN-12:39 | 0.00 |
February | 8197.72 | 20-FEB-15:30 | 0.00 | 0.00 | 0.00 | 9677.72 | 07-FEB-12:09 | 0.00 |
March | 11667.52 | 22-MAR-12:00 | 0.00 | 0.00 | 0.00 | 11030.34 | 10-MAR-13:30 | 0.00 |
April | 26895.72 | 21-APR-14:30 | 0.00 | 0.00 | 0.00 | 8369.05 | 27-APR-18:00 | 0.00 |
May | 32307.74 | 19-MAY-16:10 | 0.00 | 0.00 | 0.00 | 10085.59 | 13-MAY-15:30 | 0.00 |
June | 42459.82 | 02-JUN-16:19 | 0.00 | 0.00 | 0.00 | 8304.66 | 02-JUN-13:09 | 0.00 |
July | 42179.90 | 03-JUL-16:10 | 0.00 | 0.00 | 0.00 | 9363.41 | 25-JUL-11:09 | 0.00 |
August | 41090.18 | 07-AUG-16:10 | 0.00 | 0.00 | 0.00 | 9665.84 | 30-AUG-13:00 | 0.00 |
September | 33674.63 | 15-SEP-12:00 | 0.00 | 0.00 | 0.00 | 9591.49 | 05-SEP-17:19 | 0.00 |
October | 33869.06 | 03-OCT-13:00 | 0.00 | 0.00 | 0.00 | 9684.00 | 27-OCT-13:00 | 0.00 |
November | 13908.77 | 09-NOV-13:00 | 0.00 | 0.00 | 0.00 | 9996.07 | 07-NOV-14:00 | 0.00 |
December | 309.02 | 10-DEC-22:49 | 0.00 | 0.00 | 0.00 | 11575.39 | 12-DEC-18:49 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 309.02 | 0.00 | 0.00 | 0.00 | 8304.66 | 0.00 | ||
Maximum of Months | 42459.82 | 0.00 | 0.00 | 0.00 | 11810.58 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 53033.54 | 24-JAN-18:40 | 23459.17 | 8059.50 | 5507.06 | 0.00 | 6445.08 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 51486.55 | 21-FEB-15:00 | 23459.17 | 8059.50 | 0.00 | 0.00 | 6304.64 | 0.00 | 0.00 | 6726.05 | 0.00 |
March | 55630.03 | 21-MAR-16:30 | 23459.17 | 8059.50 | 0.00 | 0.00 | 6304.64 | 0.00 | 0.00 | 10833.66 | 0.00 |
April | 69309.92 | 29-APR-15:09 | 23459.17 | 8059.50 | 0.00 | 0.00 | 6304.64 | 0.00 | 0.00 | 24597.09 | 0.00 |
May | 75147.52 | 30-MAY-15:50 | 23459.17 | 8059.50 | 0.00 | 0.00 | 6304.64 | 0.00 | 0.00 | 30710.78 | 0.00 |
June | 88548.95 | 02-JUN-16:00 | 23459.17 | 8059.50 | 0.00 | 0.00 | 7642.74 | 0.00 | 0.00 | 42114.89 | 0.00 |
July | 84906.14 | 03-JUL-16:30 | 23459.17 | 8059.50 | 0.00 | 0.00 | 7608.92 | 0.00 | 0.00 | 41917.88 | 0.00 |
August | 86748.91 | 07-AUG-16:40 | 23459.17 | 8059.50 | 0.00 | 0.00 | 7415.64 | 0.00 | 0.00 | 40282.81 | 0.00 |
September | 77336.97 | 16-SEP-11:00 | 23459.17 | 8059.50 | 0.00 | 0.00 | 6304.64 | 0.00 | 0.00 | 30094.55 | 0.00 |
October | 76379.92 | 03-OCT-14:20 | 23459.17 | 8059.50 | 0.00 | 0.00 | 6304.64 | 0.00 | 0.00 | 33388.97 | 0.00 |
November | 58851.35 | 09-NOV-14:00 | 23459.17 | 8059.50 | 0.00 | 0.00 | 6304.64 | 0.00 | 0.00 | 13458.60 | 0.00 |
December | 55170.94 | 12-DEC-18:49 | 23459.17 | 8059.50 | 5507.06 | 0.00 | 6569.82 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 51486.55 | 23459.17 | 8059.50 | 0.00 | 0.00 | 6304.64 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 88548.95 | 23459.17 | 8059.50 | 5507.06 | 0.00 | 7642.74 | 0.00 | 0.00 | 42114.89 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 106337.82 | 27-JAN-08:09 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 108713.28 | 03-FEB-08:09 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 105390.61 | 02-MAR-08:09 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 14346.58 | 11-APR-08:30 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 72766.43 | 28-NOV-08:09 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 115995.83 | 27-DEC-08:09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 115995.83 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.83 | 20.47 | 0.00 | 20.47 | 0.00 | 20.47 | 0.00 | 20.47 |
Annual Sum or Average | 0.83 | 20.47 | 0.00 | 20.47 | 0.00 | 20.47 | 0.00 | 20.47 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.83 | 20.47 | 0.00 | 20.47 | 0.00 | 20.47 | 0.00 | 20.47 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.33 | 20.52 | 0.00 | 20.52 | 0.00 | 20.52 | 0.00 | 20.52 |
February | 0.33 | 20.48 | 0.00 | 20.48 | 0.00 | 20.48 | 0.00 | 20.48 |
March | 0.17 | 20.39 | 0.00 | 20.39 | 0.00 | 20.39 | 0.00 | 20.39 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.17 | 20.42 | 0.00 | 20.42 | 0.00 | 20.42 | 0.00 | 20.42 |
Annual Sum or Average | 1.00 | 20.47 | 0.00 | 20.47 | 0.00 | 20.47 | 0.00 | 20.47 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.33 | 20.52 | 0.00 | 20.52 | 0.00 | 20.52 | 0.00 | 20.52 |
Report: ComfortReportSimple55Monthly
For: LGSTORE1
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 496.00 | 21.63 | 51.00 | 21.56 | 51.00 | 21.51 |
February | 448.00 | 22.19 | 39.67 | 22.08 | 39.67 | 21.99 |
March | 497.00 | 22.81 | 23.17 | 22.73 | 23.17 | 22.66 |
April | 272.50 | 23.59 | 11.83 | 23.60 | 0.00 | 23.60 |
May | 80.83 | 23.83 | 177.17 | 23.87 | 0.00 | 23.87 |
June | 11.17 | 23.87 | 328.00 | 23.89 | 0.00 | 23.89 |
July | 70.83 | 23.89 | 495.00 | 23.89 | 70.83 | 23.89 |
August | 33.67 | 23.89 | 482.50 | 23.89 | 33.67 | 23.89 |
September | 46.33 | 23.88 | 407.00 | 23.89 | 39.33 | 23.89 |
October | 69.67 | 23.59 | 240.00 | 23.82 | 14.50 | 23.82 |
November | 381.00 | 22.75 | 24.83 | 22.78 | 5.17 | 22.76 |
December | 496.00 | 21.50 | 62.00 | 21.44 | 62.00 | 21.39 |
Annual Sum or Average | 2903.00 | 22.46 | 2342.17 | 23.00 | 339.33 | 22.96 |
Minimum of Months | 11.17 | 21.50 | 11.83 | 21.44 | 0.00 | 21.39 |
Maximum of Months | 497.00 | 23.89 | 495.00 | 23.89 | 70.83 | 23.89 |
Report: ComfortReportSimple55Monthly
For: SMSTORE1
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 485.50 | 22.47 | 5.17 | 22.46 | 5.17 | 22.45 |
February | 444.67 | 22.90 | 3.50 | 22.89 | 3.50 | 22.88 |
March | 483.50 | 23.33 | 2.33 | 23.32 | 2.33 | 23.31 |
April | 232.33 | 23.66 | 14.50 | 23.67 | 0.00 | 23.67 |
May | 71.33 | 23.69 | 159.17 | 23.82 | 0.00 | 23.82 |
June | 7.17 | 23.68 | 309.33 | 23.88 | 0.00 | 23.88 |
July | 44.00 | 23.89 | 494.33 | 23.89 | 44.00 | 23.89 |
August | 20.67 | 23.80 | 475.83 | 23.88 | 19.67 | 23.88 |
September | 32.33 | 23.67 | 388.83 | 23.85 | 21.33 | 23.85 |
October | 53.50 | 23.65 | 230.67 | 23.83 | 8.83 | 23.83 |
November | 333.33 | 23.24 | 22.17 | 23.28 | 0.00 | 23.28 |
December | 496.00 | 22.34 | 6.67 | 22.32 | 6.67 | 22.31 |
Annual Sum or Average | 2704.33 | 22.97 | 2112.50 | 23.36 | 111.50 | 23.36 |
Minimum of Months | 7.17 | 22.34 | 2.33 | 22.32 | 0.00 | 22.31 |
Maximum of Months | 496.00 | 23.89 | 494.33 | 23.89 | 44.00 | 23.89 |
Report: ComfortReportSimple55Monthly
For: SMSTORE2
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 370.33 | 21.88 | 17.00 | 21.84 | 17.00 | 21.81 |
February | 334.33 | 22.43 | 11.00 | 22.39 | 11.00 | 22.35 |
March | 375.00 | 23.05 | 4.83 | 23.03 | 4.83 | 23.00 |
April | 157.00 | 23.59 | 25.17 | 23.78 | 0.00 | 23.78 |
May | 40.17 | 23.91 | 142.00 | 24.24 | 0.83 | 24.26 |
June | 7.00 | 25.21 | 256.50 | 24.25 | 2.00 | 24.28 |
July | 66.17 | 24.54 | 368.17 | 24.19 | 66.17 | 24.23 |
August | 25.33 | 24.71 | 372.67 | 24.14 | 25.33 | 24.18 |
September | 27.00 | 24.18 | 319.17 | 24.10 | 23.67 | 24.11 |
October | 40.33 | 23.47 | 189.50 | 23.96 | 7.00 | 23.96 |
November | 258.67 | 22.89 | 19.33 | 22.95 | 1.83 | 22.94 |
December | 369.00 | 21.73 | 21.00 | 21.70 | 21.00 | 21.67 |
Annual Sum or Average | 2070.33 | 22.64 | 1746.33 | 23.29 | 180.67 | 23.30 |
Minimum of Months | 7.00 | 21.73 | 4.83 | 21.70 | 0.00 | 21.67 |
Maximum of Months | 375.00 | 25.21 | 372.67 | 24.25 | 66.17 | 24.28 |
Report: ComfortReportSimple55Monthly
For: SMSTORE3
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 371.00 | 21.79 | 21.17 | 21.75 | 21.17 | 21.72 |
February | 335.50 | 22.35 | 13.50 | 22.31 | 13.50 | 22.26 |
March | 376.83 | 23.00 | 6.00 | 22.97 | 6.00 | 22.94 |
April | 162.17 | 23.58 | 24.33 | 23.77 | 0.00 | 23.77 |
May | 40.00 | 23.91 | 142.50 | 24.24 | 0.83 | 24.26 |
June | 6.17 | 25.52 | 259.17 | 24.25 | 2.17 | 24.28 |
July | 65.50 | 24.57 | 368.17 | 24.19 | 65.50 | 24.24 |
August | 24.67 | 24.74 | 372.83 | 24.14 | 24.67 | 24.18 |
September | 26.67 | 24.19 | 319.67 | 24.10 | 23.33 | 24.11 |
October | 40.83 | 23.45 | 188.50 | 23.95 | 7.00 | 23.95 |
November | 266.00 | 22.86 | 18.50 | 22.91 | 2.33 | 22.89 |
December | 369.00 | 21.65 | 27.33 | 21.61 | 27.33 | 21.58 |
Annual Sum or Average | 2084.33 | 22.59 | 1761.67 | 23.25 | 193.83 | 23.25 |
Minimum of Months | 6.17 | 21.65 | 6.00 | 21.61 | 0.00 | 21.58 |
Maximum of Months | 376.83 | 25.52 | 372.83 | 24.25 | 65.50 | 24.28 |
Report: ComfortReportSimple55Monthly
For: SMSTORE4
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 371.00 | 21.67 | 28.00 | 21.63 | 28.00 | 21.59 |
February | 336.00 | 22.24 | 18.67 | 22.18 | 18.67 | 22.13 |
March | 379.00 | 22.90 | 10.67 | 22.85 | 10.67 | 22.81 |
April | 181.83 | 23.57 | 18.17 | 23.71 | 0.00 | 23.71 |
May | 44.83 | 23.88 | 138.17 | 24.22 | 0.67 | 24.23 |
June | 6.83 | 25.03 | 253.33 | 24.24 | 1.67 | 24.27 |
July | 66.67 | 24.45 | 368.00 | 24.17 | 66.67 | 24.21 |
August | 25.17 | 24.66 | 372.50 | 24.13 | 25.17 | 24.17 |
September | 27.67 | 24.16 | 316.67 | 24.09 | 23.83 | 24.10 |
October | 47.33 | 23.43 | 182.33 | 23.92 | 7.83 | 23.93 |
November | 278.67 | 22.80 | 15.50 | 22.83 | 3.17 | 22.81 |
December | 369.00 | 21.54 | 35.83 | 21.50 | 35.83 | 21.47 |
Annual Sum or Average | 2134.00 | 22.52 | 1757.83 | 23.18 | 222.17 | 23.17 |
Minimum of Months | 6.83 | 21.54 | 10.67 | 21.50 | 0.00 | 21.47 |
Maximum of Months | 379.00 | 25.03 | 372.50 | 24.24 | 66.67 | 24.27 |
Report: ComfortReportSimple55Monthly
For: LGSTORE2
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.51 | 40.17 | 21.47 | 40.17 | 21.43 |
February | 308.00 | 22.11 | 28.33 | 22.02 | 28.33 | 21.95 |
March | 348.00 | 22.79 | 15.50 | 22.71 | 15.50 | 22.65 |
April | 207.00 | 23.62 | 9.00 | 23.67 | 0.00 | 23.67 |
May | 55.00 | 23.88 | 111.50 | 24.03 | 0.50 | 24.04 |
June | 5.33 | 25.16 | 216.00 | 24.03 | 1.50 | 24.06 |
July | 74.67 | 24.16 | 336.00 | 24.02 | 74.67 | 24.04 |
August | 21.50 | 24.43 | 338.17 | 24.00 | 21.50 | 24.02 |
September | 17.33 | 24.24 | 282.50 | 23.99 | 14.83 | 24.00 |
October | 56.33 | 23.54 | 158.33 | 23.86 | 9.33 | 23.86 |
November | 283.17 | 22.76 | 8.33 | 22.74 | 5.17 | 22.71 |
December | 338.00 | 21.40 | 59.67 | 21.36 | 59.67 | 21.33 |
Annual Sum or Average | 2054.33 | 22.46 | 1603.50 | 23.02 | 271.17 | 22.98 |
Minimum of Months | 5.33 | 21.40 | 8.33 | 21.36 | 0.00 | 21.33 |
Maximum of Months | 348.00 | 25.16 | 338.17 | 24.03 | 74.67 | 24.06 |
Report: ComfortReportSimple55Monthly
For: SMSTORE5
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.49 | 45.33 | 21.44 | 45.33 | 21.41 |
February | 308.00 | 22.08 | 33.17 | 21.99 | 33.17 | 21.91 |
March | 348.00 | 22.76 | 18.67 | 22.67 | 18.67 | 22.60 |
April | 227.83 | 23.64 | 6.83 | 23.68 | 0.00 | 23.68 |
May | 70.67 | 23.86 | 98.83 | 24.01 | 0.17 | 24.02 |
June | 8.33 | 24.52 | 192.83 | 24.04 | 1.17 | 24.06 |
July | 74.00 | 24.11 | 335.17 | 24.01 | 74.00 | 24.02 |
August | 21.17 | 24.27 | 334.33 | 23.99 | 21.17 | 24.00 |
September | 17.67 | 24.05 | 269.33 | 23.98 | 14.33 | 23.98 |
October | 65.00 | 23.59 | 149.50 | 23.86 | 9.17 | 23.86 |
November | 287.33 | 22.76 | 5.67 | 22.73 | 5.67 | 22.70 |
December | 338.00 | 21.39 | 65.83 | 21.34 | 65.83 | 21.31 |
Annual Sum or Average | 2106.00 | 22.47 | 1555.50 | 22.99 | 288.67 | 22.94 |
Minimum of Months | 8.33 | 21.39 | 5.67 | 21.34 | 0.00 | 21.31 |
Maximum of Months | 348.00 | 24.52 | 335.17 | 24.04 | 74.00 | 24.06 |
Report: ComfortReportSimple55Monthly
For: SMSTORE6
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.46 | 48.67 | 21.41 | 48.67 | 21.38 |
February | 308.00 | 22.05 | 37.00 | 21.95 | 37.00 | 21.87 |
March | 348.00 | 22.71 | 21.17 | 22.62 | 21.17 | 22.54 |
April | 230.50 | 23.62 | 6.83 | 23.66 | 0.00 | 23.66 |
May | 73.17 | 23.85 | 97.00 | 24.01 | 0.00 | 24.01 |
June | 8.67 | 24.49 | 190.83 | 24.04 | 1.17 | 24.06 |
July | 73.83 | 24.10 | 335.17 | 24.01 | 73.83 | 24.02 |
August | 21.17 | 24.27 | 334.00 | 23.99 | 21.17 | 24.00 |
September | 18.33 | 24.04 | 268.67 | 23.98 | 14.33 | 23.98 |
October | 69.50 | 23.58 | 147.83 | 23.85 | 9.50 | 23.85 |
November | 289.00 | 22.73 | 6.00 | 22.69 | 6.00 | 22.66 |
December | 338.00 | 21.37 | 71.17 | 21.32 | 71.17 | 21.29 |
Annual Sum or Average | 2118.17 | 22.45 | 1564.33 | 22.96 | 304.00 | 22.91 |
Minimum of Months | 8.67 | 21.37 | 6.00 | 21.32 | 0.00 | 21.29 |
Maximum of Months | 348.00 | 24.49 | 335.17 | 24.04 | 73.83 | 24.06 |
Report: ComfortReportSimple55Monthly
For: SMSTORE7
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.40 | 62.00 | 21.35 | 62.00 | 21.32 |
February | 308.00 | 21.96 | 48.50 | 21.85 | 48.50 | 21.76 |
March | 348.00 | 22.60 | 31.33 | 22.48 | 31.33 | 22.38 |
April | 238.67 | 23.57 | 6.67 | 23.61 | 0.33 | 23.60 |
May | 77.00 | 23.83 | 96.17 | 24.00 | 0.00 | 24.00 |
June | 8.67 | 24.49 | 192.33 | 24.04 | 1.17 | 24.06 |
July | 74.50 | 24.10 | 335.17 | 24.01 | 74.50 | 24.02 |
August | 21.67 | 24.26 | 334.50 | 23.98 | 21.67 | 24.00 |
September | 19.17 | 24.03 | 268.83 | 23.98 | 14.83 | 23.98 |
October | 77.83 | 23.53 | 144.00 | 23.82 | 9.67 | 23.82 |
November | 292.83 | 22.64 | 7.50 | 22.60 | 7.50 | 22.56 |
December | 338.00 | 21.32 | 85.33 | 21.28 | 85.33 | 21.25 |
Annual Sum or Average | 2144.33 | 22.40 | 1612.33 | 22.90 | 356.83 | 22.84 |
Minimum of Months | 8.67 | 21.32 | 6.67 | 21.28 | 0.00 | 21.25 |
Maximum of Months | 348.00 | 24.49 | 335.17 | 24.04 | 85.33 | 24.06 |
Report: ComfortReportSimple55Monthly
For: SMSTORE8
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.33 | 117.33 | 21.27 | 117.33 | 21.24 |
February | 308.00 | 21.86 | 93.17 | 21.68 | 93.17 | 21.57 |
March | 348.00 | 22.47 | 57.67 | 22.28 | 57.67 | 22.13 |
April | 245.00 | 23.52 | 10.33 | 23.53 | 3.00 | 23.50 |
May | 70.17 | 23.85 | 111.67 | 24.00 | 0.67 | 24.02 |
June | 4.83 | 25.61 | 233.17 | 24.03 | 2.17 | 24.07 |
July | 65.17 | 24.27 | 336.50 | 24.04 | 65.17 | 24.07 |
August | 24.33 | 24.54 | 343.00 | 24.01 | 24.33 | 24.04 |
September | 19.00 | 24.40 | 290.00 | 24.00 | 15.67 | 24.03 |
October | 82.83 | 23.37 | 144.33 | 23.76 | 10.17 | 23.76 |
November | 295.83 | 22.54 | 19.50 | 22.45 | 19.50 | 22.37 |
December | 338.00 | 21.28 | 139.17 | 21.23 | 139.17 | 21.21 |
Annual Sum or Average | 2141.17 | 22.33 | 1895.83 | 22.80 | 548.00 | 22.69 |
Minimum of Months | 4.83 | 21.28 | 10.33 | 21.23 | 0.67 | 21.21 |
Maximum of Months | 348.00 | 25.61 | 343.00 | 24.04 | 139.17 | 24.07 |
Report: OccupantComfortDataSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 496.00000 | 21.62714 | 22.89499 | -0.3386 | 8.26766 |
February | 448.00000 | 22.18932 | 18.88303 | -0.2382 | 7.58533 |
March | 497.00000 | 22.80953 | 17.59588 | -0.0959 | 6.56745 |
April | 479.00000 | 23.71630 | 20.02352 | 0.19320 | 6.31118 |
May | 496.00000 | 23.88098 | 29.53464 | -0.5298 | 11.23295 |
June | 481.00000 | 23.88775 | 34.10201 | -0.4292 | 9.01036 |
July | 495.00000 | 23.89036 | 49.65125 | -0.3035 | 6.99080 |
August | 497.00000 | 23.88872 | 45.08369 | -0.3388 | 7.50415 |
September | 479.00000 | 23.88861 | 43.03429 | -0.3651 | 8.01007 |
October | 496.00000 | 23.83961 | 36.51227 | 0.38468 | 8.37401 |
November | 480.00000 | 22.98394 | 23.06701 | 0.02656 | 6.48538 |
December | 496.00000 | 21.49991 | 19.84986 | -0.3896 | 8.77442 |
Annual Sum or Average | 5840.00000 | 23.17826 | 30.10777 | -0.2024 | 7.93442 |
Minimum of Months | 448.00000 | 21.49991 | 17.59588 | -0.5298 | 6.31118 |
Maximum of Months | 497.00000 | 23.89036 | 49.65125 | 0.38468 | 11.23295 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 496.00000 | 22.49831 | 24.13950 | -0.1297 | 6.39862 |
February | 448.00000 | 22.91006 | 19.11171 | -0.0605 | 6.09171 |
March | 497.00000 | 23.34876 | 17.52870 | 0.04395 | 5.89674 |
April | 479.00000 | 23.77156 | 20.54453 | 0.22409 | 6.32726 |
May | 496.00000 | 23.84317 | 30.28876 | -0.5334 | 11.23091 |
June | 481.00000 | 23.87402 | 34.37215 | -0.4451 | 9.26525 |
July | 495.00000 | 23.88528 | 48.40455 | -0.3334 | 7.38387 |
August | 497.00000 | 23.86921 | 44.61837 | -0.3674 | 7.92075 |
September | 479.00000 | 23.84065 | 42.28039 | -0.4030 | 8.64087 |
October | 496.00000 | 23.82933 | 36.24264 | 0.38097 | 8.24115 |
November | 480.00000 | 23.42984 | 23.09937 | 0.13276 | 6.27380 |
December | 496.00000 | 22.33994 | 21.33462 | -0.1878 | 6.63868 |
Annual Sum or Average | 5840.00000 | 23.45472 | 30.25308 | -0.1408 | 7.53661 |
Minimum of Months | 448.00000 | 22.33994 | 17.52870 | -0.5334 | 5.89674 |
Maximum of Months | 497.00000 | 23.88528 | 48.40455 | 0.38097 | 11.23091 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 21.88068 | 21.32435 | -0.2656 | 7.41226 |
February | 336.00000 | 22.43907 | 17.87455 | -0.1606 | 6.78348 |
March | 379.00000 | 23.06486 | 16.53492 | -0.0211 | 6.22615 |
April | 360.00000 | 23.86749 | 20.02440 | 0.23522 | 6.67805 |
May | 375.00000 | 24.06243 | 28.88457 | -0.4859 | 10.57345 |
June | 366.00000 | 24.12324 | 33.15901 | -0.3861 | 8.78233 |
July | 369.00000 | 24.12499 | 48.99364 | -0.2637 | 7.04537 |
August | 379.00000 | 24.09905 | 44.81999 | -0.3029 | 7.41423 |
September | 360.00000 | 24.06850 | 42.48898 | -0.3351 | 7.80030 |
October | 371.00000 | 23.94149 | 35.44150 | 0.39904 | 8.67755 |
November | 360.00000 | 23.17238 | 22.37046 | 0.08041 | 6.47550 |
December | 369.00000 | 21.73350 | 18.70296 | -0.3188 | 7.83144 |
Annual Sum or Average | 4395.00000 | 23.38748 | 29.31186 | -0.1531 | 7.65201 |
Minimum of Months | 336.00000 | 21.73350 | 16.53492 | -0.4859 | 6.22615 |
Maximum of Months | 379.00000 | 24.12499 | 48.99364 | 0.39904 | 10.57345 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 21.78624 | 21.43589 | -0.2955 | 7.68643 |
February | 336.00000 | 22.35590 | 17.98566 | -0.1868 | 6.97571 |
March | 379.00000 | 23.00580 | 16.61812 | -0.0412 | 6.29363 |
April | 360.00000 | 23.85842 | 20.03931 | 0.23079 | 6.65595 |
May | 375.00000 | 24.06210 | 28.88401 | -0.4855 | 10.56622 |
June | 366.00000 | 24.12363 | 33.15165 | -0.3840 | 8.75006 |
July | 369.00000 | 24.12540 | 48.96770 | -0.2618 | 7.02668 |
August | 379.00000 | 24.09935 | 44.80070 | -0.3010 | 7.39296 |
September | 360.00000 | 24.06848 | 42.47074 | -0.3338 | 7.78377 |
October | 371.00000 | 23.93749 | 35.45632 | 0.39718 | 8.65144 |
November | 360.00000 | 23.12776 | 22.44738 | 0.06506 | 6.48700 |
December | 369.00000 | 21.65057 | 18.78915 | -0.3455 | 8.13418 |
Annual Sum or Average | 4395.00000 | 23.35643 | 29.34696 | -0.1627 | 7.70995 |
Minimum of Months | 336.00000 | 21.65057 | 16.61812 | -0.4855 | 6.29363 |
Maximum of Months | 379.00000 | 24.12540 | 48.96770 | 0.39718 | 10.56622 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 21.66751 | 21.57255 | -0.3320 | 8.06207 |
February | 336.00000 | 22.24229 | 18.13335 | -0.2220 | 7.26589 |
March | 379.00000 | 22.90155 | 16.76574 | -0.0744 | 6.41864 |
April | 360.00000 | 23.82687 | 20.08576 | 0.21629 | 6.56816 |
May | 375.00000 | 24.05505 | 28.91858 | -0.4950 | 10.75894 |
June | 366.00000 | 24.11920 | 33.19283 | -0.3911 | 8.84404 |
July | 369.00000 | 24.12117 | 49.12985 | -0.2673 | 7.06500 |
August | 379.00000 | 24.09513 | 44.91184 | -0.3070 | 7.45009 |
September | 360.00000 | 24.06342 | 42.57125 | -0.3406 | 7.86923 |
October | 371.00000 | 23.92074 | 35.54191 | 0.38876 | 8.52654 |
November | 360.00000 | 23.04642 | 22.58808 | 0.03965 | 6.49198 |
December | 369.00000 | 21.54154 | 18.89898 | -0.3796 | 8.54843 |
Annual Sum or Average | 4395.00000 | 23.30681 | 29.45210 | -0.1811 | 7.83149 |
Minimum of Months | 336.00000 | 21.54154 | 16.76574 | -0.4950 | 6.41864 |
Maximum of Months | 379.00000 | 24.12117 | 49.12985 | 0.38876 | 10.75894 |
Report: OccupantComfortDataSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.50883 | 23.11895 | -0.3903 | 8.77714 |
February | 308.00000 | 22.10909 | 19.54339 | -0.2766 | 7.74079 |
March | 348.00000 | 22.78635 | 18.14929 | -0.1242 | 6.52311 |
April | 330.00000 | 23.76758 | 21.57836 | 0.19056 | 6.28359 |
May | 344.00000 | 23.95190 | 30.59597 | -0.5327 | 11.40597 |
June | 336.00000 | 23.96450 | 34.60268 | -0.4358 | 9.31620 |
July | 338.00000 | 23.98772 | 50.23012 | -0.3076 | 7.30466 |
August | 348.00000 | 23.96572 | 45.97573 | -0.3465 | 7.79765 |
September | 330.00000 | 23.96037 | 43.48129 | -0.3740 | 8.24834 |
October | 340.00000 | 23.86278 | 36.63673 | 0.36922 | 8.16191 |
November | 330.00000 | 22.91732 | 24.15141 | -0.0044 | 6.46308 |
December | 338.00000 | 21.40342 | 20.49118 | -0.4345 | 9.34408 |
Annual Sum or Average | 4030.00000 | 23.18917 | 30.80565 | -0.2230 | 8.12322 |
Minimum of Months | 308.00000 | 21.40342 | 18.14929 | -0.5327 | 6.28359 |
Maximum of Months | 348.00000 | 23.98772 | 50.23012 | 0.36922 | 11.40597 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.48625 | 23.04797 | -0.4031 | 8.95261 |
February | 308.00000 | 22.08441 | 19.48684 | -0.2901 | 7.88342 |
March | 348.00000 | 22.75602 | 18.11741 | -0.1402 | 6.60734 |
April | 330.00000 | 23.76129 | 21.49163 | 0.17699 | 6.17883 |
May | 344.00000 | 23.95011 | 30.51740 | -0.5531 | 11.85413 |
June | 336.00000 | 23.96271 | 34.54236 | -0.4605 | 9.76756 |
July | 338.00000 | 23.98575 | 50.23597 | -0.3324 | 7.62125 |
August | 348.00000 | 23.96397 | 45.96879 | -0.3708 | 8.14474 |
September | 330.00000 | 23.95896 | 43.46670 | -0.3976 | 8.61311 |
October | 340.00000 | 23.86329 | 36.58281 | 0.35617 | 7.95140 |
November | 330.00000 | 22.90732 | 24.08515 | -0.0170 | 6.45062 |
December | 338.00000 | 21.38611 | 20.40410 | -0.4450 | 9.50566 |
Annual Sum or Average | 4030.00000 | 23.17928 | 30.75517 | -0.2405 | 8.30468 |
Minimum of Months | 308.00000 | 21.38611 | 18.11741 | -0.5531 | 6.17883 |
Maximum of Months | 348.00000 | 23.98575 | 50.23597 | 0.35617 | 11.85413 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.45776 | 23.08282 | -0.4141 | 9.11157 |
February | 308.00000 | 22.05063 | 19.53166 | -0.3023 | 8.02030 |
March | 348.00000 | 22.71404 | 18.18608 | -0.1545 | 6.70003 |
April | 330.00000 | 23.74711 | 21.51706 | 0.16987 | 6.15280 |
May | 344.00000 | 23.94879 | 30.51885 | -0.5568 | 11.94583 |
June | 336.00000 | 23.96239 | 34.53654 | -0.4632 | 9.81784 |
July | 338.00000 | 23.98536 | 50.23226 | -0.3349 | 7.65364 |
August | 348.00000 | 23.96369 | 45.95696 | -0.3732 | 8.18016 |
September | 330.00000 | 23.95853 | 43.45786 | -0.4002 | 8.65500 |
October | 340.00000 | 23.85704 | 36.60688 | 0.35237 | 7.90195 |
November | 330.00000 | 22.86916 | 24.15428 | -0.0293 | 6.48100 |
December | 338.00000 | 21.36594 | 20.42119 | -0.4537 | 9.64798 |
Annual Sum or Average | 4030.00000 | 23.16393 | 30.77625 | -0.2474 | 8.36590 |
Minimum of Months | 308.00000 | 21.36594 | 18.18608 | -0.5568 | 6.15280 |
Maximum of Months | 348.00000 | 23.98536 | 50.23226 | 0.35237 | 11.94583 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.39511 | 23.15661 | -0.4394 | 9.51179 |
February | 308.00000 | 21.96377 | 19.63598 | -0.3327 | 8.39564 |
March | 348.00000 | 22.60499 | 18.35129 | -0.1891 | 6.97350 |
April | 330.00000 | 23.70288 | 21.58903 | 0.15279 | 6.12549 |
May | 344.00000 | 23.94427 | 30.53875 | -0.5616 | 12.08420 |
June | 336.00000 | 23.96219 | 34.54385 | -0.4618 | 9.79144 |
July | 338.00000 | 23.98519 | 50.26512 | -0.3321 | 7.61478 |
August | 348.00000 | 23.96374 | 45.96822 | -0.3702 | 8.13724 |
September | 330.00000 | 23.95815 | 43.46467 | -0.3982 | 8.62834 |
October | 340.00000 | 23.83559 | 36.68947 | 0.34495 | 7.82871 |
November | 330.00000 | 22.77561 | 24.31442 | -0.0571 | 6.58808 |
December | 338.00000 | 21.32086 | 20.45753 | -0.4739 | 10.00873 |
Annual Sum or Average | 4030.00000 | 23.12528 | 30.84033 | -0.2605 | 8.48303 |
Minimum of Months | 308.00000 | 21.32086 | 18.35129 | -0.5616 | 6.12549 |
Maximum of Months | 348.00000 | 23.98519 | 50.26512 | 0.34495 | 12.08420 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.32845 | 23.05798 | -0.4906 | 10.49564 |
February | 308.00000 | 21.85525 | 19.69222 | -0.3901 | 9.31153 |
March | 348.00000 | 22.46969 | 18.41408 | -0.2465 | 7.61478 |
April | 330.00000 | 23.65544 | 21.54612 | 0.13589 | 6.18817 |
May | 344.00000 | 23.94335 | 30.32284 | -0.5427 | 11.74317 |
June | 336.00000 | 23.96687 | 34.42152 | -0.4158 | 8.96549 |
July | 338.00000 | 23.99239 | 49.80528 | -0.2813 | 7.01053 |
August | 348.00000 | 23.97011 | 45.63919 | -0.3180 | 7.45603 |
September | 330.00000 | 23.96547 | 43.06312 | -0.3476 | 7.91331 |
October | 340.00000 | 23.79128 | 36.67025 | 0.34347 | 7.96602 |
November | 330.00000 | 22.67829 | 24.31127 | -0.0949 | 6.88489 |
December | 338.00000 | 21.28448 | 20.32482 | -0.5145 | 10.87791 |
Annual Sum or Average | 4030.00000 | 23.08310 | 30.69672 | -0.2638 | 8.53931 |
Minimum of Months | 308.00000 | 21.28448 | 18.41408 | -0.5427 | 6.18817 |
Maximum of Months | 348.00000 | 23.99239 | 49.80528 | 0.34347 | 11.74317 |
Report: DXReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 222235.51 | 63714.81 | 0.33 | 222235.51 | -0.0 | 0.00 | 0.02 | 03-JAN-15:00 | 0.00 | 01-JAN-00:05 | 271.66 | 03-JAN-15:00 | 271.66 | 03-JAN-15:00 | 0.00 | 01-JAN-00:05 | 77.83 | 03-JAN-15:00 | 0.00 | 01-JAN-00:05 |
February | 0.322098E+09 | 89593958.04 | 34.17 | 0.322098E+09 | -0.0 | 0.00 | 0.36 | 20-FEB-16:00 | 0.00 | 01-FEB-00:10 | 6159.11 | 20-FEB-16:00 | 6159.11 | 20-FEB-16:00 | 0.00 | 22-FEB-15:20 | 1680.81 | 20-FEB-16:00 | 0.00 | 01-FEB-00:10 |
March | 0.896546E+09 | 0.249304E+09 | 82.75 | 0.896546E+09 | -0.0 | 0.00 | 0.43 | 14-MAR-16:30 | 0.00 | 01-MAR-00:10 | 7517.58 | 14-MAR-16:30 | 7517.58 | 14-MAR-16:30 | 0.00 | 22-MAR-13:20 | 2059.70 | 21-MAR-16:10 | 0.00 | 01-MAR-00:10 |
April | 0.821102E+10 | 0.228530E+10 | 310.92 | 0.818741E+10 | 23606564.92 | 0.00 | 0.82 | 30-APR-16:02 | 0.00 | 01-APR-00:10 | 15769.46 | 30-APR-16:04 | 15769.46 | 30-APR-16:04 | 687.73 | 18-APR-18:00 | 4555.93 | 21-APR-14:00 | 0.00 | 01-APR-00:10 |
May | 0.164774E+11 | 0.460091E+10 | 455.89 | 0.160105E+11 | 0.466881E+09 | 0.00 | 1.00 | 30-MAY-07:03 | 0.00 | 01-MAY-00:10 | 31141.15 | 31-MAY-07:03 | 31141.15 | 31-MAY-07:03 | 3433.43 | 24-MAY-13:00 | 7284.42 | 31-MAY-07:03 | 0.00 | 01-MAY-00:10 |
June | 0.236303E+11 | 0.679300E+10 | 481.11 | 0.228076E+11 | 0.822638E+09 | 0.00 | 1.00 | 01-JUN-14:40 | 0.00 | 01-JUN-00:10 | 45766.02 | 19-JUN-07:02 | 43388.40 | 06-JUN-07:02 | 8854.58 | 22-JUN-07:02 | 10430.72 | 08-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.285184E+11 | 0.764630E+10 | 498.01 | 0.236251E+11 | 0.489338E+10 | 0.00 | 1.00 | 01-JUL-07:02 | 0.00 | 01-JUL-00:05 | 49210.05 | 20-JUL-07:03 | 43939.28 | 03-JUL-07:01 | 29331.71 | 19-JUL-07:03 | 10717.95 | 03-JUL-07:01 | 0.00 | 01-JUL-00:05 |
August | 0.247931E+11 | 0.671101E+10 | 490.76 | 0.219692E+11 | 0.282389E+10 | 0.00 | 1.00 | 01-AUG-07:02 | 0.00 | 01-AUG-00:10 | 48903.80 | 02-AUG-07:02 | 42883.54 | 07-AUG-07:01 | 21658.59 | 02-AUG-07:02 | 10644.97 | 03-AUG-07:02 | 0.00 | 01-AUG-00:10 |
September | 0.208017E+11 | 0.549112E+10 | 462.96 | 0.180888E+11 | 0.271280E+10 | 0.00 | 1.00 | 01-SEP-07:03 | 0.00 | 01-SEP-00:05 | 48146.11 | 23-SEP-07:02 | 33226.70 | 13-SEP-07:02 | 23376.26 | 14-SEP-07:03 | 10383.30 | 23-SEP-07:02 | 0.00 | 01-SEP-00:05 |
October | 0.950952E+10 | 0.249748E+10 | 325.18 | 0.852163E+10 | 0.987886E+09 | 0.00 | 1.00 | 02-OCT-07:02 | 0.00 | 01-OCT-00:10 | 44756.14 | 02-OCT-07:02 | 38709.70 | 02-OCT-07:02 | 13305.03 | 05-OCT-07:03 | 9831.69 | 02-OCT-07:02 | 0.00 | 01-OCT-00:10 |
November | 0.743345E+09 | 0.200618E+09 | 61.42 | 0.735353E+09 | 7992121.69 | 0.00 | 0.52 | 09-NOV-15:00 | 0.00 | 01-NOV-00:10 | 9513.80 | 09-NOV-15:00 | 9513.80 | 09-NOV-15:00 | 630.42 | 03-NOV-12:50 | 2480.83 | 09-NOV-15:00 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.133904E+12 | 0.365647E+11 | 3203.48 | 0.121165E+12 | 0.127391E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.285184E+11 | 0.764630E+10 | 498.01 | 0.236251E+11 | 0.489338E+10 | 0.00 | 1.00 | 0.00 | 49210.05 | 43939.28 | 29331.71 | 10717.95 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 13806934.15 | 3801856.68 | 8.42 | 13771502.21 | 35431.95 | 0.00 | 0.36 | 01-JAN-18:10 | 0.00 | 01-JAN-00:05 | 3231.50 | 01-JAN-18:10 | 3231.50 | 01-JAN-18:10 | 21.33 | 14-JAN-20:50 | 832.16 | 01-JAN-18:10 | 0.00 | 01-JAN-00:05 |
February | 0.304688E+09 | 79733810.86 | 47.01 | 0.304641E+09 | 46892.62 | 0.00 | 1.00 | 12-FEB-18:01 | 0.00 | 01-FEB-00:10 | 22100.90 | 12-FEB-18:30 | 22100.90 | 19-FEB-18:20 | 141.42 | 13-FEB-21:30 | 4679.14 | 12-FEB-18:20 | 0.00 | 01-FEB-00:10 |
March | 0.755374E+09 | 0.199404E+09 | 108.02 | 0.755265E+09 | 109558.88 | 0.00 | 1.00 | 12-MAR-17:01 | 0.00 | 01-MAR-00:10 | 22100.90 | 12-MAR-17:20 | 22100.90 | 12-MAR-17:30 | 182.42 | 10-MAR-23:20 | 4769.10 | 26-MAR-17:01 | 0.00 | 01-MAR-00:10 |
April | 0.532561E+10 | 0.139365E+10 | 305.72 | 0.530550E+10 | 20103970.08 | 0.00 | 1.00 | 01-APR-21:01 | 0.00 | 01-APR-00:10 | 22859.65 | 18-APR-20:56 | 22349.65 | 29-APR-20:17 | 2547.21 | 18-APR-21:25 | 4964.69 | 29-APR-20:17 | 0.00 | 01-APR-00:10 |
May | 0.932330E+10 | 0.250504E+10 | 445.10 | 0.901762E+10 | 0.305680E+09 | 0.00 | 1.00 | 02-MAY-20:01 | 0.00 | 01-MAY-00:10 | 23916.85 | 27-MAY-21:00 | 22306.36 | 18-MAY-23:21 | 8042.51 | 24-MAY-22:10 | 5260.73 | 27-MAY-20:40 | 0.00 | 01-MAY-00:10 |
June | 0.122092E+11 | 0.343937E+10 | 475.07 | 0.117620E+11 | 0.447200E+09 | 0.00 | 1.00 | 01-JUN-07:03 | 0.00 | 01-JUN-00:10 | 23899.00 | 29-JUN-22:38 | 22980.84 | 05-JUN-07:02 | 6357.40 | 23-JUN-20:02 | 5338.34 | 08-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.145265E+11 | 0.383427E+10 | 496.05 | 0.121044E+11 | 0.242209E+10 | 0.00 | 1.00 | 01-JUL-07:02 | 0.00 | 01-JUL-00:05 | 25425.22 | 19-JUL-07:03 | 22921.71 | 03-JUL-07:01 | 14623.79 | 19-JUL-07:03 | 5475.81 | 03-JUL-07:01 | 0.00 | 01-JUL-00:05 |
August | 0.129207E+11 | 0.341996E+10 | 482.07 | 0.113938E+11 | 0.152698E+10 | 0.00 | 1.00 | 01-AUG-07:02 | 0.00 | 01-AUG-00:10 | 25172.06 | 03-AUG-07:02 | 22688.69 | 07-AUG-07:01 | 11881.61 | 16-AUG-20:10 | 5414.66 | 03-AUG-07:02 | 0.00 | 01-AUG-00:10 |
September | 0.115023E+11 | 0.293304E+10 | 434.59 | 0.100026E+11 | 0.149967E+10 | 0.00 | 1.00 | 01-SEP-07:03 | 0.00 | 01-SEP-00:05 | 24767.34 | 23-SEP-07:02 | 22302.06 | 28-SEP-21:30 | 12297.63 | 03-SEP-21:47 | 5334.99 | 09-SEP-20:00 | 0.00 | 01-SEP-00:05 |
October | 0.583630E+10 | 0.145847E+10 | 308.95 | 0.520131E+10 | 0.634989E+09 | 0.00 | 1.00 | 02-OCT-07:02 | 0.00 | 01-OCT-00:10 | 24765.97 | 03-OCT-20:03 | 22100.90 | 09-OCT-17:35 | 11144.40 | 03-OCT-22:10 | 5322.96 | 03-OCT-20:03 | 0.00 | 01-OCT-00:10 |
November | 0.542673E+09 | 0.141926E+09 | 80.45 | 0.537065E+09 | 5607974.05 | 0.00 | 1.00 | 08-NOV-21:01 | 0.00 | 01-NOV-00:10 | 22100.90 | 09-NOV-22:03 | 22091.75 | 09-NOV-21:01 | 977.95 | 09-NOV-22:10 | 4679.14 | 09-NOV-21:01 | 0.00 | 01-NOV-00:10 |
December | 4639622.01 | 1273634.47 | 3.36 | 4638228.70 | 1393.31 | 0.00 | 0.24 | 09-DEC-19:10 | 0.00 | 01-DEC-00:10 | 2083.00 | 09-DEC-19:10 | 2083.00 | 09-DEC-19:10 | 2.16 | 25-DEC-22:10 | 553.92 | 09-DEC-19:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.732651E+11 | 0.194099E+11 | 3194.81 | 0.664026E+11 | 0.686251E+10 | 0.00 | ||||||||||||||
Minimum of Months | 4639622.01 | 1273634.47 | 3.36 | 4638228.70 | 1393.31 | 0.00 | 0.24 | 0.00 | 2083.00 | 2083.00 | 2.16 | 553.92 | 0.00 | |||||||
Maximum of Months | 0.145265E+11 | 0.383427E+10 | 496.05 | 0.121044E+11 | 0.242209E+10 | 0.00 | 1.00 | 0.00 | 25425.22 | 22980.84 | 14623.79 | 5475.81 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_3:3 COOLING COIL
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 859508.05 | 241011.24 | 1.67 | 859508.05 | 0.00 | 0.00 | 0.05 | 03-JAN-15:00 | 0.00 | 01-JAN-00:05 | 393.77 | 03-JAN-15:00 | 393.77 | 03-JAN-15:00 | 0.00 | 03-JAN-14:50 | 110.03 | 03-JAN-15:00 | 0.00 | 01-JAN-00:05 |
February | 0.170975E+09 | 46729564.90 | 34.67 | 0.170975E+09 | -0.0 | 0.00 | 0.33 | 20-FEB-15:00 | 0.00 | 01-FEB-00:10 | 3059.35 | 20-FEB-15:00 | 3059.35 | 20-FEB-15:00 | 0.00 | 20-FEB-14:30 | 825.26 | 20-FEB-15:00 | 0.00 | 01-FEB-00:10 |
March | 0.521828E+09 | 0.141941E+09 | 83.42 | 0.521828E+09 | 40.66 | 0.00 | 0.45 | 22-MAR-13:00 | 0.00 | 01-MAR-00:10 | 4245.99 | 22-MAR-13:00 | 4245.99 | 22-MAR-13:00 | 0.02 | 10-MAR-19:00 | 1146.37 | 22-MAR-13:00 | 0.00 | 01-MAR-00:10 |
April | 0.337830E+10 | 0.923636E+09 | 230.00 | 0.336833E+10 | 9963911.08 | 0.00 | 0.81 | 21-APR-14:00 | 0.00 | 01-APR-00:10 | 8357.02 | 21-APR-14:00 | 8357.02 | 21-APR-14:00 | 347.09 | 18-APR-18:00 | 2376.99 | 21-APR-14:00 | 0.00 | 01-APR-00:10 |
May | 0.663396E+10 | 0.182410E+10 | 341.38 | 0.646085E+10 | 0.173105E+09 | 0.00 | 1.00 | 14-MAY-07:03 | 0.00 | 01-MAY-00:10 | 22486.03 | 31-MAY-06:02 | 22486.03 | 31-MAY-06:02 | 3156.90 | 23-MAY-06:03 | 4983.53 | 31-MAY-06:02 | 0.00 | 01-MAY-00:10 |
June | 0.945919E+10 | 0.267847E+10 | 357.64 | 0.913072E+10 | 0.328471E+09 | 0.00 | 1.00 | 01-JUN-06:03 | 0.00 | 01-JUN-00:10 | 24103.62 | 19-JUN-06:02 | 23434.34 | 03-JUN-06:02 | 6284.54 | 28-JUN-06:03 | 5380.53 | 08-JUN-06:02 | 0.00 | 01-JUN-00:10 |
July | 0.112281E+11 | 0.296526E+10 | 363.92 | 0.928060E+10 | 0.194749E+10 | 0.00 | 1.00 | 01-JUL-06:02 | 0.00 | 01-JUL-00:05 | 26117.15 | 19-JUL-06:03 | 23628.36 | 03-JUL-06:01 | 14703.77 | 17-JUL-06:02 | 5590.15 | 16-JUL-07:01 | 0.00 | 01-JUL-00:05 |
August | 0.983553E+10 | 0.261469E+10 | 368.80 | 0.864345E+10 | 0.119209E+10 | 0.00 | 1.00 | 01-AUG-06:02 | 0.00 | 01-AUG-00:10 | 26046.92 | 03-AUG-06:02 | 23095.28 | 27-AUG-07:02 | 12215.71 | 03-AUG-06:02 | 5532.59 | 06-AUG-07:01 | 0.00 | 01-AUG-00:10 |
September | 0.844658E+10 | 0.220781E+10 | 342.96 | 0.740139E+10 | 0.104518E+10 | 0.00 | 1.00 | 01-SEP-06:03 | 0.00 | 01-SEP-00:05 | 25531.38 | 23-SEP-06:02 | 18317.15 | 18-SEP-06:02 | 12392.30 | 14-SEP-06:02 | 5378.98 | 23-SEP-06:02 | 0.00 | 01-SEP-00:05 |
October | 0.400879E+10 | 0.103786E+10 | 256.59 | 0.362975E+10 | 0.379044E+09 | 0.00 | 1.00 | 02-OCT-06:02 | 0.00 | 01-OCT-00:10 | 24406.59 | 05-OCT-06:02 | 21817.07 | 02-OCT-06:02 | 8334.07 | 04-OCT-06:03 | 5191.69 | 05-OCT-06:02 | 0.00 | 01-OCT-00:10 |
November | 0.404262E+09 | 0.107284E+09 | 65.50 | 0.399921E+09 | 4340901.47 | 0.00 | 0.52 | 09-NOV-14:00 | 0.00 | 01-NOV-00:10 | 5022.35 | 09-NOV-14:00 | 5022.35 | 09-NOV-14:00 | 339.65 | 03-NOV-12:50 | 1287.55 | 09-NOV-14:00 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.540884E+11 | 0.145480E+11 | 2446.54 | 0.490087E+11 | 0.507968E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.112281E+11 | 0.296526E+10 | 368.80 | 0.928060E+10 | 0.194749E+10 | 0.00 | 1.00 | 0.00 | 26117.15 | 23628.36 | 14703.77 | 5590.15 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_4:4 COOLING COIL
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 114443.84 | 32248.09 | 0.33 | 114443.84 | -0.0 | 0.00 | 0.02 | 03-JAN-15:00 | 0.00 | 01-JAN-00:05 | 128.11 | 03-JAN-15:00 | 128.11 | 03-JAN-15:00 | 0.00 | 01-JAN-00:05 | 36.08 | 03-JAN-15:00 | 0.00 | 01-JAN-00:05 |
February | 0.147783E+09 | 40570207.02 | 32.58 | 0.147783E+09 | -0.0 | 0.00 | 0.31 | 20-FEB-15:00 | 0.00 | 01-FEB-00:10 | 2833.89 | 20-FEB-15:00 | 2833.89 | 20-FEB-15:00 | 0.00 | 20-FEB-16:20 | 768.80 | 20-FEB-15:00 | 0.00 | 01-FEB-00:10 |
March | 0.479799E+09 | 0.130876E+09 | 79.08 | 0.479799E+09 | 29.42 | 0.00 | 0.44 | 22-MAR-13:00 | 0.00 | 01-MAR-00:10 | 4100.88 | 22-MAR-13:00 | 4100.88 | 22-MAR-13:00 | 0.02 | 10-MAR-19:00 | 1110.76 | 22-MAR-13:00 | 0.00 | 01-MAR-00:10 |
April | 0.333591E+10 | 0.912586E+09 | 228.00 | 0.332607E+10 | 9830493.87 | 0.00 | 0.82 | 21-APR-14:00 | 0.00 | 01-APR-00:10 | 8336.63 | 21-APR-14:00 | 8336.63 | 21-APR-14:00 | 342.29 | 18-APR-18:00 | 2369.47 | 21-APR-14:00 | 0.00 | 01-APR-00:10 |
May | 0.664207E+10 | 0.182434E+10 | 341.46 | 0.646839E+10 | 0.173679E+09 | 0.00 | 1.00 | 14-MAY-07:03 | 0.00 | 01-MAY-00:10 | 22646.33 | 31-MAY-06:02 | 22646.33 | 31-MAY-06:02 | 3212.22 | 23-MAY-06:03 | 5018.96 | 31-MAY-06:02 | 0.00 | 01-MAY-00:10 |
June | 0.950353E+10 | 0.268635E+10 | 357.93 | 0.917322E+10 | 0.330314E+09 | 0.00 | 1.00 | 01-JUN-06:03 | 0.00 | 01-JUN-00:10 | 23964.34 | 19-JUN-06:02 | 23305.09 | 03-JUN-06:02 | 6462.89 | 28-JUN-06:03 | 5349.10 | 08-JUN-06:02 | 0.00 | 01-JUN-00:10 |
July | 0.112764E+11 | 0.297247E+10 | 363.86 | 0.932347E+10 | 0.195294E+10 | 0.00 | 1.00 | 01-JUL-06:02 | 0.00 | 01-JUL-00:05 | 25965.03 | 19-JUL-06:03 | 23519.75 | 03-JUL-06:01 | 14599.63 | 17-JUL-06:02 | 5557.10 | 16-JUL-07:01 | 0.00 | 01-JUL-00:05 |
August | 0.988357E+10 | 0.262259E+10 | 368.93 | 0.868588E+10 | 0.119769E+10 | 0.00 | 1.00 | 01-AUG-06:02 | 0.00 | 01-AUG-00:10 | 25892.62 | 03-AUG-06:02 | 22961.27 | 27-AUG-07:02 | 12135.87 | 03-AUG-06:02 | 5500.00 | 06-AUG-07:01 | 0.00 | 01-AUG-00:10 |
September | 0.847785E+10 | 0.221242E+10 | 343.13 | 0.742787E+10 | 0.104997E+10 | 0.00 | 1.00 | 01-SEP-06:03 | 0.00 | 01-SEP-00:05 | 25380.51 | 23-SEP-06:02 | 18293.72 | 18-SEP-06:02 | 12314.52 | 14-SEP-06:02 | 5347.07 | 23-SEP-06:02 | 0.00 | 01-SEP-00:05 |
October | 0.398853E+10 | 0.103217E+10 | 255.09 | 0.361181E+10 | 0.376718E+09 | 0.00 | 1.00 | 02-OCT-06:02 | 0.00 | 01-OCT-00:10 | 24262.01 | 05-OCT-06:02 | 21702.66 | 02-OCT-06:02 | 8500.11 | 04-OCT-06:03 | 5160.91 | 05-OCT-06:02 | 0.00 | 01-OCT-00:10 |
November | 0.380445E+09 | 0.101065E+09 | 62.83 | 0.376287E+09 | 4158131.65 | 0.00 | 0.51 | 09-NOV-14:00 | 0.00 | 01-NOV-00:10 | 4939.24 | 09-NOV-14:00 | 4939.24 | 09-NOV-14:00 | 327.16 | 03-NOV-12:50 | 1267.99 | 09-NOV-14:00 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.541160E+11 | 0.145355E+11 | 2433.22 | 0.490207E+11 | 0.509531E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.112764E+11 | 0.297247E+10 | 368.93 | 0.932347E+10 | 0.195294E+10 | 0.00 | 1.00 | 0.00 | 25965.03 | 23519.75 | 14599.63 | 5557.10 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_5:5 COOLING COIL
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 0.116587E+09 | 32226295.89 | 28.17 | 0.116587E+09 | 0.00 | 0.00 | 0.28 | 20-FEB-15:00 | 0.00 | 01-FEB-00:10 | 2523.98 | 20-FEB-15:00 | 2523.98 | 20-FEB-15:00 | 0.00 | 21-FEB-15:20 | 690.63 | 20-FEB-15:00 | 0.00 | 01-FEB-00:10 |
March | 0.406420E+09 | 0.111536E+09 | 72.25 | 0.406420E+09 | 0.00 | 0.00 | 0.42 | 22-MAR-13:00 | 0.00 | 01-MAR-00:10 | 3834.17 | 22-MAR-13:00 | 3834.17 | 22-MAR-13:00 | 0.00 | 14-MAR-16:10 | 1046.02 | 22-MAR-13:00 | 0.00 | 01-MAR-00:10 |
April | 0.317006E+10 | 0.871969E+09 | 221.92 | 0.316115E+10 | 8907896.49 | 0.00 | 0.80 | 21-APR-14:00 | 0.00 | 01-APR-00:10 | 8159.15 | 21-APR-14:00 | 8159.15 | 21-APR-14:00 | 326.06 | 18-APR-18:00 | 2329.24 | 21-APR-14:00 | 0.00 | 01-APR-00:10 |
May | 0.644788E+10 | 0.177844E+10 | 337.88 | 0.628072E+10 | 0.167161E+09 | 0.00 | 1.00 | 20-MAY-06:03 | 0.00 | 01-MAY-00:10 | 21099.36 | 31-MAY-06:02 | 21099.36 | 31-MAY-06:02 | 2906.58 | 23-MAY-06:03 | 4676.57 | 31-MAY-06:02 | 0.00 | 01-MAY-00:10 |
June | 0.930682E+10 | 0.263987E+10 | 357.63 | 0.898825E+10 | 0.318571E+09 | 0.00 | 1.00 | 01-JUN-16:10 | 0.00 | 01-JUN-00:10 | 23962.65 | 19-JUN-06:02 | 23300.57 | 03-JUN-06:02 | 5797.54 | 28-JUN-06:03 | 5346.08 | 18-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.110653E+11 | 0.292673E+10 | 364.07 | 0.914935E+10 | 0.191591E+10 | 0.00 | 1.00 | 01-JUL-06:02 | 0.00 | 01-JUL-00:05 | 25960.70 | 17-JUL-06:02 | 23499.20 | 03-JUL-06:01 | 14618.96 | 17-JUL-06:02 | 5556.95 | 16-JUL-07:01 | 0.00 | 01-JUL-00:05 |
August | 0.967842E+10 | 0.257717E+10 | 368.68 | 0.851233E+10 | 0.116609E+10 | 0.00 | 1.00 | 01-AUG-06:02 | 0.00 | 01-AUG-00:10 | 25891.96 | 03-AUG-06:02 | 22958.60 | 27-AUG-07:02 | 12162.98 | 03-AUG-06:02 | 5499.90 | 06-AUG-07:01 | 0.00 | 01-AUG-00:10 |
September | 0.828393E+10 | 0.216965E+10 | 341.45 | 0.726208E+10 | 0.102185E+10 | 0.00 | 1.00 | 01-SEP-06:03 | 0.00 | 01-SEP-00:05 | 25379.10 | 23-SEP-06:02 | 18291.22 | 18-SEP-06:02 | 12342.75 | 14-SEP-06:02 | 5347.05 | 23-SEP-06:02 | 0.00 | 01-SEP-00:05 |
October | 0.383613E+10 | 0.996526E+09 | 246.26 | 0.347599E+10 | 0.360145E+09 | 0.00 | 1.00 | 02-OCT-06:02 | 0.00 | 01-OCT-00:10 | 24260.60 | 05-OCT-06:02 | 21698.85 | 02-OCT-06:02 | 7817.75 | 05-OCT-06:02 | 5160.68 | 05-OCT-06:02 | 0.00 | 01-OCT-00:10 |
November | 0.331354E+09 | 88335863.95 | 56.25 | 0.327810E+09 | 3543962.51 | 0.00 | 0.49 | 09-NOV-14:00 | 0.00 | 01-NOV-00:10 | 4728.39 | 09-NOV-14:00 | 4728.39 | 09-NOV-14:00 | 294.48 | 03-NOV-12:50 | 1220.53 | 09-NOV-14:00 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.526429E+11 | 0.141925E+11 | 2394.56 | 0.476807E+11 | 0.496218E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.110653E+11 | 0.292673E+10 | 368.68 | 0.914935E+10 | 0.191591E+10 | 0.00 | 1.00 | 0.00 | 25960.70 | 23499.20 | 14618.96 | 5556.95 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_6:6 COOLING COIL
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 0.173091E+09 | 48872361.01 | 24.50 | 0.173091E+09 | 0.00 | 0.00 | 0.27 | 20-FEB-15:30 | 0.00 | 01-FEB-00:10 | 4333.90 | 20-FEB-15:30 | 4333.90 | 20-FEB-15:30 | 0.00 | 21-FEB-15:30 | 1208.87 | 20-FEB-15:30 | 0.00 | 01-FEB-00:10 |
March | 0.606515E+09 | 0.170296E+09 | 64.67 | 0.606515E+09 | -0.0 | 0.00 | 0.40 | 22-MAR-13:00 | 0.00 | 01-MAR-00:10 | 6541.36 | 22-MAR-13:00 | 6541.36 | 22-MAR-13:00 | 0.00 | 22-MAR-13:20 | 1821.71 | 22-MAR-13:00 | 0.00 | 01-MAR-00:10 |
April | 0.542990E+10 | 0.152661E+10 | 219.08 | 0.541108E+10 | 18817497.88 | 0.00 | 0.82 | 21-APR-14:20 | 0.00 | 01-APR-00:10 | 14967.44 | 21-APR-14:30 | 14967.44 | 21-APR-14:30 | 681.01 | 18-APR-17:00 | 4298.82 | 21-APR-14:30 | 0.00 | 01-APR-00:10 |
May | 0.114598E+11 | 0.321875E+10 | 334.15 | 0.111321E+11 | 0.327706E+09 | 0.00 | 1.00 | 30-MAY-07:03 | 0.00 | 01-MAY-00:10 | 32832.28 | 30-MAY-07:03 | 32832.28 | 30-MAY-07:03 | 4802.80 | 28-MAY-08:63 | 7728.46 | 30-MAY-07:03 | 0.00 | 01-MAY-00:10 |
June | 0.167586E+11 | 0.483966E+10 | 349.02 | 0.161664E+11 | 0.592157E+09 | 0.00 | 1.00 | 01-JUN-07:03 | 0.00 | 01-JUN-00:10 | 42363.82 | 19-JUN-07:02 | 41054.11 | 05-JUN-07:02 | 9139.76 | 04-JUN-08:62 | 9709.78 | 18-JUN-08:62 | 0.00 | 01-JUN-00:10 |
July | 0.197051E+11 | 0.528256E+10 | 351.45 | 0.162313E+11 | 0.347383E+10 | 0.00 | 1.00 | 01-JUL-07:02 | 0.00 | 01-JUL-00:05 | 45623.35 | 19-JUL-07:03 | 41015.37 | 03-JUL-07:01 | 26633.88 | 19-JUL-07:03 | 10106.11 | 02-JUL-08:62 | 0.00 | 01-JUL-00:05 |
August | 0.173961E+11 | 0.469721E+10 | 359.30 | 0.152273E+11 | 0.216879E+10 | 0.00 | 1.00 | 01-AUG-07:02 | 0.00 | 01-AUG-00:10 | 45373.65 | 03-AUG-07:02 | 40409.03 | 06-AUG-08:61 | 19945.92 | 14-AUG-07:02 | 9919.40 | 07-AUG-07:01 | 0.00 | 01-AUG-00:10 |
September | 0.149322E+11 | 0.396237E+10 | 334.58 | 0.130046E+11 | 0.192758E+10 | 0.00 | 1.00 | 01-SEP-07:03 | 0.00 | 01-SEP-00:05 | 44501.34 | 23-SEP-07:02 | 31066.18 | 13-SEP-07:02 | 19940.78 | 14-SEP-07:03 | 9732.30 | 10-SEP-08:62 | 0.00 | 01-SEP-00:05 |
October | 0.672450E+10 | 0.177408E+10 | 238.56 | 0.601835E+10 | 0.706147E+09 | 0.00 | 1.00 | 02-OCT-07:02 | 0.00 | 01-OCT-00:10 | 41549.35 | 02-OCT-07:02 | 36071.28 | 02-OCT-07:02 | 12165.12 | 05-OCT-07:03 | 9128.15 | 02-OCT-07:02 | 0.00 | 01-OCT-00:10 |
November | 0.509912E+09 | 0.138585E+09 | 49.00 | 0.503039E+09 | 6873072.03 | 0.00 | 0.48 | 09-NOV-14:00 | 0.00 | 01-NOV-00:10 | 8153.44 | 09-NOV-14:00 | 8153.44 | 09-NOV-14:00 | 566.62 | 03-NOV-13:00 | 2146.84 | 09-NOV-14:00 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.936957E+11 | 0.256590E+11 | 2324.30 | 0.844738E+11 | 0.922190E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.197051E+11 | 0.528256E+10 | 359.30 | 0.162313E+11 | 0.347383E+10 | 0.00 | 1.00 | 0.00 | 45623.35 | 41054.11 | 26633.88 | 10106.11 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_7:7 COOLING COIL
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 79989954.70 | 22243067.90 | 23.00 | 79989954.70 | 0.00 | 0.00 | 0.27 | 20-FEB-15:40 | 0.00 | 01-FEB-00:10 | 2154.41 | 20-FEB-15:40 | 2154.41 | 20-FEB-15:40 | 0.00 | 20-FEB-16:00 | 591.94 | 20-FEB-15:40 | 0.00 | 01-FEB-00:10 |
March | 0.288438E+09 | 79735979.33 | 61.50 | 0.288438E+09 | 0.00 | 0.00 | 0.39 | 22-MAR-13:00 | 0.00 | 01-MAR-00:10 | 3262.87 | 22-MAR-13:00 | 3262.87 | 22-MAR-13:00 | 0.00 | 22-MAR-14:20 | 895.88 | 22-MAR-13:00 | 0.00 | 01-MAR-00:10 |
April | 0.277151E+10 | 0.766284E+09 | 215.67 | 0.276281E+10 | 8702067.17 | 0.00 | 0.82 | 21-APR-14:20 | 0.00 | 01-APR-00:10 | 7723.98 | 21-APR-14:40 | 7723.98 | 21-APR-14:40 | 331.32 | 18-APR-17:00 | 2180.36 | 21-APR-14:30 | 0.00 | 01-APR-00:10 |
May | 0.588970E+10 | 0.162641E+10 | 333.15 | 0.572654E+10 | 0.163160E+09 | 0.00 | 1.00 | 30-MAY-07:03 | 0.00 | 01-MAY-00:10 | 16367.78 | 30-MAY-07:03 | 16367.78 | 30-MAY-07:03 | 2199.77 | 28-MAY-08:63 | 3785.78 | 30-MAY-07:03 | 0.00 | 01-MAY-00:10 |
June | 0.861649E+10 | 0.244734E+10 | 349.70 | 0.832129E+10 | 0.295197E+09 | 0.00 | 1.00 | 01-JUN-07:03 | 0.00 | 01-JUN-00:10 | 21890.62 | 19-JUN-07:02 | 21225.24 | 05-JUN-07:02 | 4348.70 | 04-JUN-08:62 | 4930.04 | 18-JUN-08:62 | 0.00 | 01-JUN-00:10 |
July | 0.101309E+11 | 0.267167E+10 | 352.70 | 0.836950E+10 | 0.176143E+10 | 0.00 | 1.00 | 01-JUL-07:02 | 0.00 | 01-JUL-00:05 | 23470.65 | 18-JUL-07:02 | 21199.76 | 03-JUL-07:01 | 13391.44 | 19-JUL-07:03 | 5129.53 | 02-JUL-08:62 | 0.00 | 01-JUL-00:05 |
August | 0.894351E+10 | 0.237497E+10 | 359.55 | 0.784986E+10 | 0.109365E+10 | 0.00 | 1.00 | 01-AUG-07:02 | 0.00 | 01-AUG-00:10 | 23443.62 | 03-AUG-07:02 | 20972.13 | 06-AUG-08:61 | 10259.99 | 14-AUG-07:02 | 5035.37 | 07-AUG-07:01 | 0.00 | 01-AUG-00:10 |
September | 0.767761E+10 | 0.200334E+10 | 334.63 | 0.670610E+10 | 0.971503E+09 | 0.00 | 1.00 | 01-SEP-07:03 | 0.00 | 01-SEP-00:05 | 22993.37 | 23-SEP-07:02 | 16121.90 | 13-SEP-07:02 | 9422.50 | 23-SEP-07:02 | 4940.42 | 10-SEP-08:62 | 0.00 | 01-SEP-00:05 |
October | 0.344997E+10 | 0.894705E+09 | 236.81 | 0.309660E+10 | 0.353379E+09 | 0.00 | 1.00 | 02-OCT-07:02 | 0.00 | 01-OCT-00:10 | 21468.72 | 02-OCT-07:02 | 18737.73 | 02-OCT-07:02 | 5757.96 | 05-OCT-07:03 | 4633.85 | 02-OCT-07:02 | 0.00 | 01-OCT-00:10 |
November | 0.252833E+09 | 67537901.10 | 48.17 | 0.249792E+09 | 3040917.07 | 0.00 | 0.48 | 09-NOV-14:00 | 0.00 | 01-NOV-00:10 | 4181.58 | 09-NOV-14:00 | 4181.58 | 09-NOV-14:00 | 268.17 | 03-NOV-13:00 | 1082.78 | 09-NOV-14:00 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.481010E+11 | 0.129542E+11 | 2314.87 | 0.434509E+11 | 0.465007E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.101309E+11 | 0.267167E+10 | 359.55 | 0.836950E+10 | 0.176143E+10 | 0.00 | 1.00 | 0.00 | 23470.65 | 21225.24 | 13391.44 | 5129.53 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_8:8 COOLING COIL
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 73029395.06 | 20351022.12 | 22.33 | 73029395.06 | 0.00 | 0.00 | 0.26 | 20-FEB-15:40 | 0.00 | 01-FEB-00:10 | 2067.52 | 20-FEB-15:40 | 2067.52 | 20-FEB-15:40 | 0.00 | 20-FEB-14:50 | 569.45 | 20-FEB-15:40 | 0.00 | 01-FEB-00:10 |
March | 0.268579E+09 | 74407109.29 | 58.50 | 0.268579E+09 | 0.00 | 0.00 | 0.38 | 22-MAR-13:00 | 0.00 | 01-MAR-00:10 | 3162.19 | 22-MAR-13:00 | 3162.19 | 22-MAR-13:00 | 0.00 | 22-MAR-14:20 | 870.55 | 22-MAR-13:00 | 0.00 | 01-MAR-00:10 |
April | 0.271724E+10 | 0.752425E+09 | 213.08 | 0.270856E+10 | 8678820.64 | 0.00 | 0.82 | 21-APR-14:20 | 0.00 | 01-APR-00:10 | 7662.28 | 21-APR-14:40 | 7662.28 | 21-APR-14:40 | 330.96 | 18-APR-17:00 | 2164.61 | 21-APR-14:30 | 0.00 | 01-APR-00:10 |
May | 0.583450E+10 | 0.161217E+10 | 331.82 | 0.567117E+10 | 0.163332E+09 | 0.00 | 1.00 | 30-MAY-07:03 | 0.00 | 01-MAY-00:10 | 15856.87 | 30-MAY-07:03 | 15856.87 | 30-MAY-07:03 | 2085.95 | 28-MAY-08:63 | 3667.99 | 30-MAY-07:03 | 0.00 | 01-MAY-00:10 |
June | 0.856619E+10 | 0.243370E+10 | 349.67 | 0.827040E+10 | 0.295786E+09 | 0.00 | 1.00 | 01-JUN-07:03 | 0.00 | 01-JUN-00:10 | 21804.43 | 19-JUN-07:02 | 21128.69 | 05-JUN-07:02 | 4303.23 | 04-JUN-08:62 | 4908.76 | 18-JUN-08:62 | 0.00 | 01-JUN-00:10 |
July | 0.100830E+11 | 0.265929E+10 | 352.70 | 0.832106E+10 | 0.176195E+10 | 0.00 | 1.00 | 01-JUL-07:02 | 0.00 | 01-JUL-00:05 | 23378.44 | 18-JUL-07:02 | 21109.98 | 03-JUL-07:01 | 12978.29 | 19-JUL-07:03 | 5109.00 | 02-JUL-08:62 | 0.00 | 01-JUL-00:05 |
August | 0.889976E+10 | 0.236359E+10 | 359.71 | 0.780497E+10 | 0.109479E+10 | 0.00 | 1.00 | 01-AUG-07:02 | 0.00 | 01-AUG-00:10 | 23351.61 | 03-AUG-07:02 | 20835.39 | 06-AUG-08:61 | 10235.06 | 14-AUG-07:02 | 5015.66 | 07-AUG-07:01 | 0.00 | 01-AUG-00:10 |
September | 0.763402E+10 | 0.199226E+10 | 334.13 | 0.666209E+10 | 0.971935E+09 | 0.00 | 1.00 | 01-SEP-07:03 | 0.00 | 01-SEP-00:05 | 22902.76 | 23-SEP-07:02 | 16028.66 | 13-SEP-07:02 | 9408.59 | 23-SEP-07:02 | 4921.05 | 10-SEP-08:62 | 0.00 | 01-SEP-00:05 |
October | 0.340709E+10 | 0.884127E+09 | 235.31 | 0.305579E+10 | 0.351305E+09 | 0.00 | 1.00 | 02-OCT-07:02 | 0.00 | 01-OCT-00:10 | 21384.01 | 02-OCT-07:02 | 18624.58 | 02-OCT-07:02 | 5643.57 | 05-OCT-07:03 | 4615.57 | 02-OCT-07:02 | 0.00 | 01-OCT-00:10 |
November | 0.239310E+09 | 64001668.58 | 45.58 | 0.236322E+09 | 2987946.08 | 0.00 | 0.47 | 09-NOV-14:00 | 0.00 | 01-NOV-00:10 | 4100.89 | 09-NOV-14:00 | 4100.89 | 09-NOV-14:00 | 261.12 | 03-NOV-13:00 | 1063.84 | 09-NOV-14:00 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.477227E+11 | 0.128563E+11 | 2302.83 | 0.430720E+11 | 0.465076E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.100830E+11 | 0.265929E+10 | 359.71 | 0.832106E+10 | 0.176195E+10 | 0.00 | 1.00 | 0.00 | 23378.44 | 21128.69 | 12978.29 | 5109.00 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_9:9 COOLING COIL
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 2.96 | 0.84 | 0.17 | 2.96 | 0.00 | 0.00 | 0.00 | 03-JAN-15:00 | 0.00 | 01-JAN-00:05 | 0.00 | 03-JAN-15:00 | 0.00 | 03-JAN-15:00 | 0.00 | 01-JAN-00:05 | 0.00 | 03-JAN-15:00 | 0.00 | 01-JAN-00:05 |
February | 56189531.07 | 15741933.54 | 21.17 | 56189531.07 | 0.00 | 0.00 | 0.23 | 20-FEB-15:30 | 0.00 | 01-FEB-00:10 | 1874.81 | 20-FEB-15:30 | 1874.81 | 20-FEB-15:30 | 0.00 | 20-FEB-14:40 | 519.51 | 20-FEB-15:30 | 0.00 | 01-FEB-00:10 |
March | 0.223384E+09 | 62244406.58 | 50.00 | 0.223384E+09 | 0.00 | 0.00 | 0.36 | 22-MAR-13:00 | 0.00 | 01-MAR-00:10 | 2924.25 | 22-MAR-13:00 | 2924.25 | 22-MAR-13:00 | 0.00 | 22-MAR-12:30 | 810.96 | 22-MAR-13:00 | 0.00 | 01-MAR-00:10 |
April | 0.259390E+10 | 0.721590E+09 | 207.50 | 0.258592E+10 | 7973524.69 | 0.00 | 0.81 | 21-APR-14:20 | 0.00 | 01-APR-00:10 | 7548.82 | 21-APR-14:40 | 7548.82 | 21-APR-14:40 | 315.34 | 18-APR-17:00 | 2139.46 | 21-APR-14:30 | 0.00 | 01-APR-00:10 |
May | 0.572954E+10 | 0.158697E+10 | 326.18 | 0.556989E+10 | 0.159649E+09 | 0.00 | 1.00 | 30-MAY-07:03 | 0.00 | 01-MAY-00:10 | 13941.32 | 30-MAY-07:03 | 13941.32 | 30-MAY-07:03 | 1853.26 | 24-MAY-13:00 | 3226.39 | 30-MAY-07:03 | 0.00 | 01-MAY-00:10 |
June | 0.852725E+10 | 0.242487E+10 | 349.44 | 0.823576E+10 | 0.291485E+09 | 0.00 | 1.00 | 01-JUN-14:10 | 0.00 | 01-JUN-00:10 | 21828.81 | 19-JUN-07:02 | 21151.37 | 05-JUN-07:02 | 4047.34 | 04-JUN-08:62 | 4911.32 | 18-JUN-08:62 | 0.00 | 01-JUN-00:10 |
July | 0.100683E+11 | 0.265674E+10 | 352.64 | 0.831197E+10 | 0.175629E+10 | 0.00 | 1.00 | 01-JUL-07:02 | 0.00 | 01-JUL-00:05 | 23404.98 | 18-JUL-07:02 | 21133.20 | 03-JUL-07:01 | 11735.26 | 19-JUL-07:03 | 5114.08 | 02-JUL-08:62 | 0.00 | 01-JUL-00:05 |
August | 0.889641E+10 | 0.236312E+10 | 359.55 | 0.780668E+10 | 0.108973E+10 | 0.00 | 1.00 | 01-AUG-07:02 | 0.00 | 01-AUG-00:10 | 23378.70 | 03-AUG-07:02 | 20831.55 | 06-AUG-08:61 | 10256.40 | 14-AUG-07:02 | 5021.82 | 07-AUG-07:01 | 0.00 | 01-AUG-00:10 |
September | 0.761640E+10 | 0.198829E+10 | 333.73 | 0.664801E+10 | 0.968390E+09 | 0.00 | 1.00 | 01-SEP-07:03 | 0.00 | 01-SEP-00:05 | 22929.50 | 23-SEP-07:02 | 16038.12 | 13-SEP-07:02 | 9430.33 | 23-SEP-07:02 | 4888.26 | 03-SEP-08:62 | 0.00 | 01-SEP-00:05 |
October | 0.332513E+10 | 0.864510E+09 | 230.47 | 0.298302E+10 | 0.342112E+09 | 0.00 | 1.00 | 02-OCT-07:02 | 0.00 | 01-OCT-00:10 | 21408.49 | 02-OCT-07:02 | 18638.16 | 02-OCT-07:02 | 5320.49 | 05-OCT-07:03 | 4620.88 | 02-OCT-07:02 | 0.00 | 01-OCT-00:10 |
November | 0.212165E+09 | 56910645.24 | 40.67 | 0.209528E+09 | 2636585.99 | 0.00 | 0.46 | 09-NOV-14:00 | 0.00 | 01-NOV-00:10 | 3955.02 | 09-NOV-14:00 | 3955.02 | 09-NOV-14:00 | 236.16 | 03-NOV-13:00 | 1030.49 | 09-NOV-14:00 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.472486E+11 | 0.127410E+11 | 2271.51 | 0.426304E+11 | 0.461827E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.100683E+11 | 0.265674E+10 | 359.55 | 0.831197E+10 | 0.175629E+10 | 0.00 | 1.00 | 0.00 | 23404.98 | 21151.37 | 11735.26 | 5114.08 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_10:10 COOLING COIL
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 38131157.32 | 10757217.10 | 15.67 | 38131157.32 | -0.0 | 0.00 | 0.20 | 20-FEB-15:30 | 0.00 | 01-FEB-00:10 | 1726.20 | 20-FEB-15:30 | 1726.20 | 20-FEB-15:30 | 0.00 | 20-FEB-15:20 | 482.91 | 20-FEB-15:30 | 0.00 | 01-FEB-00:10 |
March | 0.189500E+09 | 53282441.72 | 42.00 | 0.189500E+09 | -0.0 | 0.00 | 0.33 | 22-MAR-13:00 | 0.00 | 01-MAR-00:10 | 2945.08 | 22-MAR-13:00 | 2945.08 | 22-MAR-13:00 | 0.00 | 14-MAR-17:00 | 822.88 | 22-MAR-13:00 | 0.00 | 01-MAR-00:10 |
April | 0.273865E+10 | 0.764918E+09 | 203.00 | 0.273145E+10 | 7203424.59 | 0.00 | 0.79 | 21-APR-14:10 | 0.00 | 01-APR-00:10 | 8039.55 | 21-APR-14:20 | 8039.55 | 21-APR-14:20 | 284.07 | 18-APR-17:00 | 2295.12 | 21-APR-14:10 | 0.00 | 01-APR-00:10 |
May | 0.627523E+10 | 0.173958E+10 | 327.89 | 0.610635E+10 | 0.168882E+09 | 0.00 | 0.98 | 30-MAY-07:03 | 0.00 | 01-MAY-00:10 | 10891.93 | 30-MAY-07:03 | 10891.93 | 30-MAY-07:03 | 1931.83 | 24-MAY-13:00 | 2813.08 | 30-MAY-14:10 | 0.00 | 01-MAY-00:10 |
June | 0.957518E+10 | 0.271423E+10 | 347.93 | 0.925909E+10 | 0.316093E+09 | 0.00 | 1.00 | 01-JUN-14:10 | 0.00 | 01-JUN-00:10 | 24110.47 | 19-JUN-07:02 | 23404.26 | 18-JUN-08:62 | 4116.24 | 04-JUN-08:62 | 5432.21 | 18-JUN-08:62 | 0.00 | 01-JUN-00:10 |
July | 0.114072E+11 | 0.300157E+10 | 353.18 | 0.948003E+10 | 0.192713E+10 | 0.00 | 1.00 | 01-JUL-07:02 | 0.00 | 01-JUL-00:05 | 25794.52 | 18-JUL-07:02 | 23355.51 | 03-JUL-07:01 | 11581.42 | 18-JUL-07:02 | 5654.87 | 02-JUL-08:62 | 0.00 | 01-JUL-00:05 |
August | 0.102015E+11 | 0.269338E+10 | 357.72 | 0.899840E+10 | 0.120306E+10 | 0.00 | 1.00 | 01-AUG-07:02 | 0.00 | 01-AUG-00:10 | 25757.82 | 03-AUG-07:02 | 22905.03 | 27-AUG-08:62 | 11513.12 | 14-AUG-07:02 | 5565.56 | 06-AUG-08:61 | 0.00 | 01-AUG-00:10 |
September | 0.876169E+10 | 0.227077E+10 | 332.56 | 0.768303E+10 | 0.107867E+10 | 0.00 | 1.00 | 01-SEP-07:03 | 0.00 | 01-SEP-00:05 | 25274.59 | 23-SEP-07:02 | 17477.65 | 13-SEP-07:02 | 10627.30 | 23-SEP-07:02 | 5381.69 | 03-SEP-08:62 | 0.00 | 01-SEP-00:05 |
October | 0.363485E+10 | 0.944643E+09 | 225.14 | 0.327524E+10 | 0.359615E+09 | 0.00 | 1.00 | 02-OCT-07:02 | 0.00 | 01-OCT-00:10 | 23584.30 | 02-OCT-07:02 | 20440.21 | 02-OCT-07:02 | 4795.50 | 05-OCT-07:03 | 5089.94 | 02-OCT-07:02 | 0.00 | 01-OCT-00:10 |
November | 0.207890E+09 | 55862539.13 | 33.33 | 0.205581E+09 | 2309381.65 | 0.00 | 0.44 | 09-NOV-14:00 | 0.00 | 01-NOV-00:10 | 4204.08 | 09-NOV-14:00 | 4204.08 | 09-NOV-14:00 | 225.32 | 03-NOV-13:00 | 1099.61 | 09-NOV-14:00 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.530297E+11 | 0.142490E+11 | 2238.41 | 0.479668E+11 | 0.506295E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.114072E+11 | 0.300157E+10 | 357.72 | 0.948003E+10 | 0.192713E+10 | 0.00 | 1.00 | 0.00 | 25794.52 | 23404.26 | 11581.42 | 5654.87 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 98.39 | 74.54 | 23.85 | 138.90 | 63.52 | 0.00 | 0.00 | 0.00 |
February | 91.26 | 64.34 | 26.92 | 131.28 | 56.96 | 0.00 | 0.00 | 0.00 |
March | 74.17 | 42.77 | 31.40 | 110.15 | 51.16 | 0.00 | 0.00 | 0.00 |
April | 50.29 | 18.76 | 31.52 | 83.10 | 32.47 | 0.00 | 0.00 | 0.00 |
May | 35.54 | 4.97 | 30.56 | 64.69 | 19.29 | 0.00 | 0.00 | 0.00 |
June | 30.66 | 1.95 | 28.71 | 67.97 | 9.62 | 0.00 | 0.00 | 0.00 |
July | 31.25 | 2.90 | 28.36 | 68.97 | 7.84 | 0.00 | 0.00 | 0.00 |
August | 39.84 | 10.55 | 29.29 | 82.33 | 11.50 | 0.00 | 0.00 | 0.00 |
September | 62.19 | 32.31 | 29.88 | 116.73 | 22.64 | 0.00 | 0.00 | 0.00 |
October | 84.49 | 57.12 | 27.37 | 136.30 | 36.58 | 0.00 | 0.00 | 0.00 |
November | 101.68 | 77.52 | 24.16 | 147.28 | 57.76 | 0.00 | 0.00 | 0.00 |
December | 100.77 | 75.64 | 25.13 | 139.48 | 69.04 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.57 | 38.47 | 28.10 | 107.11 | 36.43 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.66 | 1.95 | 23.85 | 64.69 | 7.84 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 101.68 | 77.52 | 31.52 | 147.28 | 69.04 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 98.39 | 74.54 | 23.85 | 138.90 | 63.52 | 0.00 | 0.00 | 0.00 |
February | 91.26 | 64.34 | 26.92 | 131.28 | 56.96 | 0.00 | 0.00 | 0.00 |
March | 74.17 | 42.77 | 31.40 | 110.15 | 51.16 | 0.00 | 0.00 | 0.00 |
April | 50.29 | 18.76 | 31.52 | 83.10 | 32.47 | 0.00 | 0.00 | 0.00 |
May | 35.54 | 4.97 | 30.56 | 64.69 | 19.29 | 0.00 | 0.00 | 0.00 |
June | 30.66 | 1.95 | 28.71 | 67.97 | 9.62 | 0.00 | 0.00 | 0.00 |
July | 31.25 | 2.90 | 28.36 | 68.97 | 7.84 | 0.00 | 0.00 | 0.00 |
August | 39.84 | 10.55 | 29.29 | 82.33 | 11.50 | 0.00 | 0.00 | 0.00 |
September | 62.19 | 32.31 | 29.88 | 116.73 | 22.64 | 0.00 | 0.00 | 0.00 |
October | 84.49 | 57.12 | 27.37 | 136.30 | 36.58 | 0.00 | 0.00 | 0.00 |
November | 101.68 | 77.52 | 24.16 | 147.28 | 57.76 | 0.00 | 0.00 | 0.00 |
December | 100.77 | 75.64 | 25.13 | 139.48 | 69.04 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.57 | 38.47 | 28.10 | 107.11 | 36.43 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.66 | 1.95 | 23.85 | 64.69 | 7.84 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 101.68 | 77.52 | 31.52 | 147.28 | 69.04 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 98.39 | 74.54 | 23.85 | 138.90 | 63.52 | 0.00 | 0.00 | 0.00 |
February | 91.26 | 64.34 | 26.92 | 131.28 | 56.96 | 0.00 | 0.00 | 0.00 |
March | 74.17 | 42.77 | 31.40 | 110.15 | 51.16 | 0.00 | 0.00 | 0.00 |
April | 50.29 | 18.76 | 31.52 | 83.10 | 32.47 | 0.00 | 0.00 | 0.00 |
May | 35.54 | 4.97 | 30.56 | 64.69 | 19.29 | 0.00 | 0.00 | 0.00 |
June | 30.66 | 1.95 | 28.71 | 67.97 | 9.62 | 0.00 | 0.00 | 0.00 |
July | 31.25 | 2.90 | 28.36 | 68.97 | 7.84 | 0.00 | 0.00 | 0.00 |
August | 39.84 | 10.55 | 29.29 | 82.33 | 11.50 | 0.00 | 0.00 | 0.00 |
September | 62.19 | 32.31 | 29.88 | 116.73 | 22.64 | 0.00 | 0.00 | 0.00 |
October | 84.49 | 57.12 | 27.37 | 136.30 | 36.58 | 0.00 | 0.00 | 0.00 |
November | 101.68 | 77.52 | 24.16 | 147.28 | 57.76 | 0.00 | 0.00 | 0.00 |
December | 100.77 | 75.64 | 25.13 | 139.48 | 69.04 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.57 | 38.47 | 28.10 | 107.11 | 36.43 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.66 | 1.95 | 23.85 | 64.69 | 7.84 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 101.68 | 77.52 | 31.52 | 147.28 | 69.04 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 98.39 | 74.54 | 23.85 | 138.90 | 63.52 | 0.00 | 0.00 | 0.00 |
February | 91.26 | 64.34 | 26.92 | 131.28 | 56.96 | 0.00 | 0.00 | 0.00 |
March | 74.17 | 42.77 | 31.40 | 110.15 | 51.16 | 0.00 | 0.00 | 0.00 |
April | 50.29 | 18.76 | 31.52 | 83.10 | 32.47 | 0.00 | 0.00 | 0.00 |
May | 35.54 | 4.97 | 30.56 | 64.69 | 19.29 | 0.00 | 0.00 | 0.00 |
June | 30.66 | 1.95 | 28.71 | 67.97 | 9.62 | 0.00 | 0.00 | 0.00 |
July | 31.25 | 2.90 | 28.36 | 68.97 | 7.84 | 0.00 | 0.00 | 0.00 |
August | 39.84 | 10.55 | 29.29 | 82.33 | 11.50 | 0.00 | 0.00 | 0.00 |
September | 62.19 | 32.31 | 29.88 | 116.73 | 22.64 | 0.00 | 0.00 | 0.00 |
October | 84.49 | 57.12 | 27.37 | 136.30 | 36.58 | 0.00 | 0.00 | 0.00 |
November | 101.68 | 77.52 | 24.16 | 147.28 | 57.76 | 0.00 | 0.00 | 0.00 |
December | 100.77 | 75.64 | 25.13 | 139.48 | 69.04 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.57 | 38.47 | 28.10 | 107.11 | 36.43 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.66 | 1.95 | 23.85 | 64.69 | 7.84 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 101.68 | 77.52 | 31.52 | 147.28 | 69.04 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 118.27 | 89.61 | 28.67 | 167.27 | 75.61 | 0.00 | 0.00 | 0.00 |
February | 109.71 | 77.35 | 32.37 | 158.09 | 67.82 | 0.00 | 0.00 | 0.00 |
March | 89.16 | 51.41 | 37.75 | 132.72 | 60.98 | 0.00 | 0.00 | 0.00 |
April | 60.45 | 22.56 | 37.90 | 99.90 | 38.84 | 0.00 | 0.00 | 0.00 |
May | 42.72 | 5.98 | 36.74 | 77.47 | 23.20 | 0.00 | 0.00 | 0.00 |
June | 36.86 | 2.34 | 34.52 | 81.07 | 11.61 | 0.00 | 0.00 | 0.00 |
July | 37.57 | 3.48 | 34.09 | 82.41 | 9.44 | 0.00 | 0.00 | 0.00 |
August | 47.89 | 12.68 | 35.22 | 98.56 | 13.81 | 0.00 | 0.00 | 0.00 |
September | 74.76 | 38.84 | 35.92 | 140.07 | 27.12 | 0.00 | 0.00 | 0.00 |
October | 101.57 | 68.67 | 32.90 | 163.85 | 43.67 | 0.00 | 0.00 | 0.00 |
November | 122.24 | 93.19 | 29.05 | 177.24 | 68.85 | 0.00 | 0.00 | 0.00 |
December | 121.14 | 90.93 | 30.21 | 167.90 | 82.23 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 80.03 | 46.24 | 33.78 | 128.69 | 43.47 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 36.86 | 2.34 | 28.67 | 77.47 | 9.44 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 122.24 | 93.19 | 37.90 | 177.24 | 82.23 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 118.27 | 89.61 | 28.67 | 167.27 | 75.61 | 0.00 | 0.00 | 0.00 |
February | 109.71 | 77.35 | 32.37 | 158.09 | 67.82 | 0.00 | 0.00 | 0.00 |
March | 89.16 | 51.41 | 37.75 | 132.72 | 60.98 | 0.00 | 0.00 | 0.00 |
April | 60.45 | 22.56 | 37.90 | 99.90 | 38.84 | 0.00 | 0.00 | 0.00 |
May | 42.72 | 5.98 | 36.74 | 77.47 | 23.20 | 0.00 | 0.00 | 0.00 |
June | 36.86 | 2.34 | 34.52 | 81.07 | 11.61 | 0.00 | 0.00 | 0.00 |
July | 37.57 | 3.48 | 34.09 | 82.41 | 9.44 | 0.00 | 0.00 | 0.00 |
August | 47.89 | 12.68 | 35.22 | 98.56 | 13.81 | 0.00 | 0.00 | 0.00 |
September | 74.76 | 38.84 | 35.92 | 140.07 | 27.12 | 0.00 | 0.00 | 0.00 |
October | 101.57 | 68.67 | 32.90 | 163.85 | 43.67 | 0.00 | 0.00 | 0.00 |
November | 122.24 | 93.19 | 29.05 | 177.24 | 68.85 | 0.00 | 0.00 | 0.00 |
December | 121.14 | 90.93 | 30.21 | 167.90 | 82.23 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 80.03 | 46.24 | 33.78 | 128.69 | 43.47 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 36.86 | 2.34 | 28.67 | 77.47 | 9.44 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 122.24 | 93.19 | 37.90 | 177.24 | 82.23 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 98.39 | 74.54 | 23.85 | 137.05 | 68.14 | 0.00 | 0.00 | 0.00 |
February | 91.26 | 64.34 | 26.92 | 129.30 | 61.06 | 0.00 | 0.00 | 0.00 |
March | 74.17 | 42.77 | 31.40 | 108.22 | 54.48 | 0.00 | 0.00 | 0.00 |
April | 50.29 | 18.76 | 31.52 | 82.35 | 33.53 | 0.00 | 0.00 | 0.00 |
May | 35.54 | 4.97 | 30.56 | 64.65 | 19.58 | 0.00 | 0.00 | 0.00 |
June | 30.66 | 1.95 | 28.71 | 68.38 | 9.76 | 0.00 | 0.00 | 0.00 |
July | 31.25 | 2.90 | 28.36 | 69.45 | 7.90 | 0.00 | 0.00 | 0.00 |
August | 39.84 | 10.55 | 29.29 | 82.75 | 11.49 | 0.00 | 0.00 | 0.00 |
September | 62.19 | 32.31 | 29.88 | 116.90 | 22.45 | 0.00 | 0.00 | 0.00 |
October | 84.49 | 57.12 | 27.37 | 135.96 | 36.91 | 0.00 | 0.00 | 0.00 |
November | 101.68 | 77.52 | 24.16 | 145.90 | 60.20 | 0.00 | 0.00 | 0.00 |
December | 100.77 | 75.64 | 25.13 | 137.69 | 73.37 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.57 | 38.47 | 28.10 | 106.40 | 38.13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.66 | 1.95 | 23.85 | 64.65 | 7.90 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 101.68 | 77.52 | 31.52 | 145.90 | 73.37 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 98.39 | 74.54 | 23.85 | 137.05 | 68.14 | 0.00 | 0.00 | 0.00 |
February | 91.26 | 64.34 | 26.92 | 129.30 | 61.06 | 0.00 | 0.00 | 0.00 |
March | 74.17 | 42.77 | 31.40 | 108.22 | 54.48 | 0.00 | 0.00 | 0.00 |
April | 50.29 | 18.76 | 31.52 | 82.35 | 33.53 | 0.00 | 0.00 | 0.00 |
May | 35.54 | 4.97 | 30.56 | 64.65 | 19.58 | 0.00 | 0.00 | 0.00 |
June | 30.66 | 1.95 | 28.71 | 68.38 | 9.76 | 0.00 | 0.00 | 0.00 |
July | 31.25 | 2.90 | 28.36 | 69.45 | 7.90 | 0.00 | 0.00 | 0.00 |
August | 39.84 | 10.55 | 29.29 | 82.75 | 11.49 | 0.00 | 0.00 | 0.00 |
September | 62.19 | 32.31 | 29.88 | 116.90 | 22.45 | 0.00 | 0.00 | 0.00 |
October | 84.49 | 57.12 | 27.37 | 135.96 | 36.91 | 0.00 | 0.00 | 0.00 |
November | 101.68 | 77.52 | 24.16 | 145.90 | 60.20 | 0.00 | 0.00 | 0.00 |
December | 100.77 | 75.64 | 25.13 | 137.69 | 73.37 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.57 | 38.47 | 28.10 | 106.40 | 38.13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.66 | 1.95 | 23.85 | 64.65 | 7.90 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 101.68 | 77.52 | 31.52 | 145.90 | 73.37 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 118.27 | 89.61 | 28.67 | 165.11 | 81.03 | 0.00 | 0.00 | 0.00 |
February | 109.71 | 77.35 | 32.37 | 155.77 | 72.65 | 0.00 | 0.00 | 0.00 |
March | 89.16 | 51.41 | 37.75 | 130.46 | 64.89 | 0.00 | 0.00 | 0.00 |
April | 60.45 | 22.56 | 37.90 | 99.03 | 40.09 | 0.00 | 0.00 | 0.00 |
May | 42.72 | 5.98 | 36.74 | 77.42 | 23.55 | 0.00 | 0.00 | 0.00 |
June | 36.86 | 2.34 | 34.52 | 81.53 | 11.78 | 0.00 | 0.00 | 0.00 |
July | 37.57 | 3.48 | 34.09 | 82.97 | 9.51 | 0.00 | 0.00 | 0.00 |
August | 47.89 | 12.68 | 35.22 | 99.06 | 13.81 | 0.00 | 0.00 | 0.00 |
September | 74.76 | 38.84 | 35.92 | 140.31 | 26.90 | 0.00 | 0.00 | 0.00 |
October | 101.57 | 68.67 | 32.90 | 163.49 | 44.06 | 0.00 | 0.00 | 0.00 |
November | 122.24 | 93.19 | 29.05 | 175.63 | 71.71 | 0.00 | 0.00 | 0.00 |
December | 121.14 | 90.93 | 30.21 | 165.80 | 87.33 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 80.03 | 46.24 | 33.78 | 127.86 | 45.47 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 36.86 | 2.34 | 28.67 | 77.42 | 9.51 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 122.24 | 93.19 | 37.90 | 175.63 | 87.33 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 98.39 | 74.54 | 23.85 | 137.59 | 66.03 | 0.00 | 0.00 | 0.00 |
February | 91.26 | 64.34 | 26.92 | 129.73 | 59.60 | 0.00 | 0.00 | 0.00 |
March | 74.17 | 42.77 | 31.40 | 108.52 | 53.71 | 0.00 | 0.00 | 0.00 |
April | 50.29 | 18.76 | 31.52 | 82.16 | 34.43 | 0.00 | 0.00 | 0.00 |
May | 35.54 | 4.97 | 30.56 | 64.05 | 21.06 | 0.00 | 0.00 | 0.00 |
June | 30.66 | 1.95 | 28.71 | 66.89 | 11.00 | 0.00 | 0.00 | 0.00 |
July | 31.25 | 2.90 | 28.36 | 67.95 | 9.22 | 0.00 | 0.00 | 0.00 |
August | 39.84 | 10.55 | 29.29 | 81.61 | 12.95 | 0.00 | 0.00 | 0.00 |
September | 62.19 | 32.31 | 29.88 | 116.56 | 24.47 | 0.00 | 0.00 | 0.00 |
October | 84.49 | 57.12 | 27.37 | 135.79 | 38.12 | 0.00 | 0.00 | 0.00 |
November | 101.68 | 77.52 | 24.16 | 146.24 | 59.70 | 0.00 | 0.00 | 0.00 |
December | 100.77 | 75.64 | 25.13 | 138.21 | 71.37 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.57 | 38.47 | 28.10 | 106.12 | 38.36 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.66 | 1.95 | 23.85 | 64.05 | 9.22 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 101.68 | 77.52 | 31.52 | 146.24 | 71.37 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 98.39 | 74.54 | 23.85 | 137.59 | 66.03 | 0.00 | 0.00 | 0.00 |
February | 91.26 | 64.34 | 26.92 | 129.73 | 59.60 | 0.00 | 0.00 | 0.00 |
March | 74.17 | 42.77 | 31.40 | 108.52 | 53.71 | 0.00 | 0.00 | 0.00 |
April | 50.29 | 18.76 | 31.52 | 82.16 | 34.43 | 0.00 | 0.00 | 0.00 |
May | 35.54 | 4.97 | 30.56 | 64.05 | 21.06 | 0.00 | 0.00 | 0.00 |
June | 30.66 | 1.95 | 28.71 | 66.89 | 11.00 | 0.00 | 0.00 | 0.00 |
July | 31.25 | 2.90 | 28.36 | 67.95 | 9.22 | 0.00 | 0.00 | 0.00 |
August | 39.84 | 10.55 | 29.29 | 81.61 | 12.95 | 0.00 | 0.00 | 0.00 |
September | 62.19 | 32.31 | 29.88 | 116.56 | 24.47 | 0.00 | 0.00 | 0.00 |
October | 84.49 | 57.12 | 27.37 | 135.79 | 38.12 | 0.00 | 0.00 | 0.00 |
November | 101.68 | 77.52 | 24.16 | 146.24 | 59.70 | 0.00 | 0.00 | 0.00 |
December | 100.77 | 75.64 | 25.13 | 138.21 | 71.37 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.57 | 38.47 | 28.10 | 106.12 | 38.36 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.66 | 1.95 | 23.85 | 64.05 | 9.22 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 101.68 | 77.52 | 31.52 | 146.24 | 71.37 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.63 | 89.12 | 28.51 | 164.86 | 78.12 | 0.00 | 0.00 | 0.00 |
February | 109.11 | 76.92 | 32.19 | 155.43 | 70.54 | 0.00 | 0.00 | 0.00 |
March | 88.68 | 51.13 | 37.55 | 130.11 | 63.63 | 0.00 | 0.00 | 0.00 |
April | 60.12 | 22.43 | 37.69 | 98.27 | 40.92 | 0.00 | 0.00 | 0.00 |
May | 42.49 | 5.95 | 36.54 | 76.31 | 25.16 | 0.00 | 0.00 | 0.00 |
June | 36.66 | 2.33 | 34.33 | 79.38 | 13.19 | 0.00 | 0.00 | 0.00 |
July | 37.37 | 3.46 | 33.90 | 80.80 | 11.02 | 0.00 | 0.00 | 0.00 |
August | 47.63 | 12.61 | 35.02 | 97.21 | 15.45 | 0.00 | 0.00 | 0.00 |
September | 74.35 | 38.63 | 35.72 | 139.14 | 29.11 | 0.00 | 0.00 | 0.00 |
October | 101.02 | 68.30 | 32.72 | 162.40 | 45.23 | 0.00 | 0.00 | 0.00 |
November | 121.57 | 92.68 | 28.89 | 175.07 | 70.72 | 0.00 | 0.00 | 0.00 |
December | 120.48 | 90.44 | 30.04 | 165.51 | 84.51 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 79.59 | 45.99 | 33.60 | 126.85 | 45.51 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 36.66 | 2.33 | 28.51 | 76.31 | 11.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 121.57 | 92.68 | 37.69 | 175.07 | 84.51 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 98.39 | 74.54 | 23.85 | 137.96 | 64.92 | 0.00 | 0.00 | 0.00 |
February | 91.26 | 64.34 | 26.92 | 130.07 | 58.65 | 0.00 | 0.00 | 0.00 |
March | 74.17 | 42.77 | 31.40 | 108.82 | 52.98 | 0.00 | 0.00 | 0.00 |
April | 50.29 | 18.76 | 31.52 | 82.23 | 34.24 | 0.00 | 0.00 | 0.00 |
May | 35.54 | 4.97 | 30.56 | 64.03 | 21.11 | 0.00 | 0.00 | 0.00 |
June | 30.66 | 1.95 | 28.71 | 66.82 | 11.14 | 0.00 | 0.00 | 0.00 |
July | 31.25 | 2.90 | 28.36 | 67.87 | 9.36 | 0.00 | 0.00 | 0.00 |
August | 39.84 | 10.55 | 29.29 | 81.54 | 13.10 | 0.00 | 0.00 | 0.00 |
September | 62.19 | 32.31 | 29.88 | 116.53 | 24.59 | 0.00 | 0.00 | 0.00 |
October | 84.49 | 57.12 | 27.37 | 135.82 | 38.05 | 0.00 | 0.00 | 0.00 |
November | 101.68 | 77.52 | 24.16 | 146.47 | 59.12 | 0.00 | 0.00 | 0.00 |
December | 100.77 | 75.64 | 25.13 | 138.54 | 70.35 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.57 | 38.47 | 28.10 | 106.24 | 38.03 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.66 | 1.95 | 23.85 | 64.03 | 9.36 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 101.68 | 77.52 | 31.52 | 146.47 | 70.35 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 98.39 | 74.54 | 23.85 | 137.96 | 64.92 | 0.00 | 0.00 | 0.00 |
February | 91.26 | 64.34 | 26.92 | 130.07 | 58.65 | 0.00 | 0.00 | 0.00 |
March | 74.17 | 42.77 | 31.40 | 108.82 | 52.98 | 0.00 | 0.00 | 0.00 |
April | 50.29 | 18.76 | 31.52 | 82.23 | 34.24 | 0.00 | 0.00 | 0.00 |
May | 35.54 | 4.97 | 30.56 | 64.03 | 21.11 | 0.00 | 0.00 | 0.00 |
June | 30.66 | 1.95 | 28.71 | 66.82 | 11.14 | 0.00 | 0.00 | 0.00 |
July | 31.25 | 2.90 | 28.36 | 67.87 | 9.36 | 0.00 | 0.00 | 0.00 |
August | 39.84 | 10.55 | 29.29 | 81.54 | 13.10 | 0.00 | 0.00 | 0.00 |
September | 62.19 | 32.31 | 29.88 | 116.53 | 24.59 | 0.00 | 0.00 | 0.00 |
October | 84.49 | 57.12 | 27.37 | 135.82 | 38.05 | 0.00 | 0.00 | 0.00 |
November | 101.68 | 77.52 | 24.16 | 146.47 | 59.12 | 0.00 | 0.00 | 0.00 |
December | 100.77 | 75.64 | 25.13 | 138.54 | 70.35 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.57 | 38.47 | 28.10 | 106.24 | 38.03 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.66 | 1.95 | 23.85 | 64.03 | 9.36 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 101.68 | 77.52 | 31.52 | 146.47 | 70.35 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.63 | 89.12 | 28.51 | 165.30 | 76.80 | 0.00 | 0.00 | 0.00 |
February | 109.11 | 76.92 | 32.19 | 155.84 | 69.43 | 0.00 | 0.00 | 0.00 |
March | 88.68 | 51.13 | 37.55 | 130.47 | 62.77 | 0.00 | 0.00 | 0.00 |
April | 60.12 | 22.43 | 37.69 | 98.35 | 40.70 | 0.00 | 0.00 | 0.00 |
May | 42.49 | 5.95 | 36.54 | 76.29 | 25.23 | 0.00 | 0.00 | 0.00 |
June | 36.66 | 2.33 | 34.33 | 79.29 | 13.36 | 0.00 | 0.00 | 0.00 |
July | 37.37 | 3.46 | 33.90 | 80.70 | 11.20 | 0.00 | 0.00 | 0.00 |
August | 47.63 | 12.61 | 35.02 | 97.13 | 15.64 | 0.00 | 0.00 | 0.00 |
September | 74.35 | 38.63 | 35.72 | 139.11 | 29.26 | 0.00 | 0.00 | 0.00 |
October | 101.02 | 68.30 | 32.72 | 162.43 | 45.14 | 0.00 | 0.00 | 0.00 |
November | 121.57 | 92.68 | 28.89 | 175.35 | 70.04 | 0.00 | 0.00 | 0.00 |
December | 120.48 | 90.44 | 30.04 | 165.91 | 83.30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 79.59 | 45.99 | 33.60 | 126.99 | 45.12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 36.66 | 2.33 | 28.51 | 76.29 | 11.20 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 121.57 | 92.68 | 37.69 | 175.35 | 83.30 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 98.39 | 74.54 | 23.85 | 138.39 | 63.89 | 0.00 | 0.00 | 0.00 |
February | 91.26 | 64.34 | 26.92 | 130.51 | 57.68 | 0.00 | 0.00 | 0.00 |
March | 74.17 | 42.77 | 31.40 | 109.30 | 52.08 | 0.00 | 0.00 | 0.00 |
April | 50.29 | 18.76 | 31.52 | 82.47 | 33.73 | 0.00 | 0.00 | 0.00 |
May | 35.54 | 4.97 | 30.56 | 64.19 | 20.79 | 0.00 | 0.00 | 0.00 |
June | 30.66 | 1.95 | 28.71 | 66.99 | 10.90 | 0.00 | 0.00 | 0.00 |
July | 31.25 | 2.90 | 28.36 | 68.02 | 9.13 | 0.00 | 0.00 | 0.00 |
August | 39.84 | 10.55 | 29.29 | 81.66 | 12.85 | 0.00 | 0.00 | 0.00 |
September | 62.19 | 32.31 | 29.88 | 116.63 | 24.30 | 0.00 | 0.00 | 0.00 |
October | 84.49 | 57.12 | 27.37 | 135.96 | 37.69 | 0.00 | 0.00 | 0.00 |
November | 101.68 | 77.52 | 24.16 | 146.83 | 58.43 | 0.00 | 0.00 | 0.00 |
December | 100.77 | 75.64 | 25.13 | 138.96 | 69.39 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.57 | 38.47 | 28.10 | 106.50 | 37.47 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.66 | 1.95 | 23.85 | 64.19 | 9.13 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 101.68 | 77.52 | 31.52 | 146.83 | 69.39 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 98.39 | 74.54 | 23.85 | 138.39 | 63.89 | 0.00 | 0.00 | 0.00 |
February | 91.26 | 64.34 | 26.92 | 130.51 | 57.68 | 0.00 | 0.00 | 0.00 |
March | 74.17 | 42.77 | 31.40 | 109.30 | 52.08 | 0.00 | 0.00 | 0.00 |
April | 50.29 | 18.76 | 31.52 | 82.47 | 33.73 | 0.00 | 0.00 | 0.00 |
May | 35.54 | 4.97 | 30.56 | 64.19 | 20.79 | 0.00 | 0.00 | 0.00 |
June | 30.66 | 1.95 | 28.71 | 66.99 | 10.90 | 0.00 | 0.00 | 0.00 |
July | 31.25 | 2.90 | 28.36 | 68.02 | 9.13 | 0.00 | 0.00 | 0.00 |
August | 39.84 | 10.55 | 29.29 | 81.66 | 12.85 | 0.00 | 0.00 | 0.00 |
September | 62.19 | 32.31 | 29.88 | 116.63 | 24.30 | 0.00 | 0.00 | 0.00 |
October | 84.49 | 57.12 | 27.37 | 135.96 | 37.69 | 0.00 | 0.00 | 0.00 |
November | 101.68 | 77.52 | 24.16 | 146.83 | 58.43 | 0.00 | 0.00 | 0.00 |
December | 100.77 | 75.64 | 25.13 | 138.96 | 69.39 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.57 | 38.47 | 28.10 | 106.50 | 37.47 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.66 | 1.95 | 23.85 | 64.19 | 9.13 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 101.68 | 77.52 | 31.52 | 146.83 | 69.39 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.63 | 89.12 | 28.51 | 165.81 | 75.59 | 0.00 | 0.00 | 0.00 |
February | 109.11 | 76.92 | 32.19 | 156.37 | 68.28 | 0.00 | 0.00 | 0.00 |
March | 88.68 | 51.13 | 37.55 | 131.04 | 61.71 | 0.00 | 0.00 | 0.00 |
April | 60.12 | 22.43 | 37.69 | 98.65 | 40.10 | 0.00 | 0.00 | 0.00 |
May | 42.49 | 5.95 | 36.54 | 76.47 | 24.84 | 0.00 | 0.00 | 0.00 |
June | 36.66 | 2.33 | 34.33 | 79.49 | 13.07 | 0.00 | 0.00 | 0.00 |
July | 37.37 | 3.46 | 33.90 | 80.87 | 10.92 | 0.00 | 0.00 | 0.00 |
August | 47.63 | 12.61 | 35.02 | 97.27 | 15.34 | 0.00 | 0.00 | 0.00 |
September | 74.35 | 38.63 | 35.72 | 139.23 | 28.92 | 0.00 | 0.00 | 0.00 |
October | 101.02 | 68.30 | 32.72 | 162.60 | 44.72 | 0.00 | 0.00 | 0.00 |
November | 121.57 | 92.68 | 28.89 | 175.78 | 69.23 | 0.00 | 0.00 | 0.00 |
December | 120.48 | 90.44 | 30.04 | 166.40 | 82.17 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 79.59 | 45.99 | 33.60 | 127.31 | 44.45 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 36.66 | 2.33 | 28.51 | 76.47 | 10.92 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 121.57 | 92.68 | 37.69 | 175.78 | 82.17 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 98.39 | 74.54 | 23.85 | 139.42 | 61.73 | 0.00 | 0.00 | 0.00 |
February | 91.26 | 64.34 | 26.92 | 131.59 | 55.61 | 0.00 | 0.00 | 0.00 |
March | 74.17 | 42.77 | 31.40 | 110.40 | 50.08 | 0.00 | 0.00 | 0.00 |
April | 50.29 | 18.76 | 31.52 | 83.01 | 32.39 | 0.00 | 0.00 | 0.00 |
May | 35.54 | 4.97 | 30.56 | 64.30 | 19.80 | 0.00 | 0.00 | 0.00 |
June | 30.66 | 1.95 | 28.71 | 67.13 | 10.20 | 0.00 | 0.00 | 0.00 |
July | 31.25 | 2.90 | 28.36 | 68.01 | 8.47 | 0.00 | 0.00 | 0.00 |
August | 39.84 | 10.55 | 29.29 | 81.64 | 12.08 | 0.00 | 0.00 | 0.00 |
September | 62.19 | 32.31 | 29.88 | 116.61 | 23.39 | 0.00 | 0.00 | 0.00 |
October | 84.49 | 57.12 | 27.37 | 136.26 | 36.71 | 0.00 | 0.00 | 0.00 |
November | 101.68 | 77.52 | 24.16 | 147.64 | 56.85 | 0.00 | 0.00 | 0.00 |
December | 100.77 | 75.64 | 25.13 | 139.97 | 67.37 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.57 | 38.47 | 28.10 | 107.00 | 36.12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.66 | 1.95 | 23.85 | 64.30 | 8.47 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 101.68 | 77.52 | 31.52 | 147.64 | 67.37 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 98.39 | 74.54 | 23.85 | 139.42 | 61.73 | 0.00 | 0.00 | 0.00 |
February | 91.26 | 64.34 | 26.92 | 131.59 | 55.61 | 0.00 | 0.00 | 0.00 |
March | 74.17 | 42.77 | 31.40 | 110.40 | 50.08 | 0.00 | 0.00 | 0.00 |
April | 50.29 | 18.76 | 31.52 | 83.01 | 32.39 | 0.00 | 0.00 | 0.00 |
May | 35.54 | 4.97 | 30.56 | 64.30 | 19.80 | 0.00 | 0.00 | 0.00 |
June | 30.66 | 1.95 | 28.71 | 67.13 | 10.20 | 0.00 | 0.00 | 0.00 |
July | 31.25 | 2.90 | 28.36 | 68.01 | 8.47 | 0.00 | 0.00 | 0.00 |
August | 39.84 | 10.55 | 29.29 | 81.64 | 12.08 | 0.00 | 0.00 | 0.00 |
September | 62.19 | 32.31 | 29.88 | 116.61 | 23.39 | 0.00 | 0.00 | 0.00 |
October | 84.49 | 57.12 | 27.37 | 136.26 | 36.71 | 0.00 | 0.00 | 0.00 |
November | 101.68 | 77.52 | 24.16 | 147.64 | 56.85 | 0.00 | 0.00 | 0.00 |
December | 100.77 | 75.64 | 25.13 | 139.97 | 67.37 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.57 | 38.47 | 28.10 | 107.00 | 36.12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.66 | 1.95 | 23.85 | 64.30 | 8.47 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 101.68 | 77.52 | 31.52 | 147.64 | 67.37 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 98.39 | 74.54 | 23.85 | 139.42 | 61.73 | 0.00 | 0.00 | 0.00 |
February | 91.26 | 64.34 | 26.92 | 131.59 | 55.61 | 0.00 | 0.00 | 0.00 |
March | 74.17 | 42.77 | 31.40 | 110.40 | 50.08 | 0.00 | 0.00 | 0.00 |
April | 50.29 | 18.76 | 31.52 | 83.01 | 32.39 | 0.00 | 0.00 | 0.00 |
May | 35.54 | 4.97 | 30.56 | 64.30 | 19.80 | 0.00 | 0.00 | 0.00 |
June | 30.66 | 1.95 | 28.71 | 67.13 | 10.20 | 0.00 | 0.00 | 0.00 |
July | 31.25 | 2.90 | 28.36 | 68.01 | 8.47 | 0.00 | 0.00 | 0.00 |
August | 39.84 | 10.55 | 29.29 | 81.64 | 12.08 | 0.00 | 0.00 | 0.00 |
September | 62.19 | 32.31 | 29.88 | 116.61 | 23.39 | 0.00 | 0.00 | 0.00 |
October | 84.49 | 57.12 | 27.37 | 136.26 | 36.71 | 0.00 | 0.00 | 0.00 |
November | 101.68 | 77.52 | 24.16 | 147.64 | 56.85 | 0.00 | 0.00 | 0.00 |
December | 100.77 | 75.64 | 25.13 | 139.97 | 67.37 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.57 | 38.47 | 28.10 | 107.00 | 36.12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.66 | 1.95 | 23.85 | 64.30 | 8.47 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 101.68 | 77.52 | 31.52 | 147.64 | 67.37 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 98.39 | 74.54 | 23.85 | 139.42 | 61.73 | 0.00 | 0.00 | 0.00 |
February | 91.26 | 64.34 | 26.92 | 131.59 | 55.61 | 0.00 | 0.00 | 0.00 |
March | 74.17 | 42.77 | 31.40 | 110.40 | 50.08 | 0.00 | 0.00 | 0.00 |
April | 50.29 | 18.76 | 31.52 | 83.01 | 32.39 | 0.00 | 0.00 | 0.00 |
May | 35.54 | 4.97 | 30.56 | 64.30 | 19.80 | 0.00 | 0.00 | 0.00 |
June | 30.66 | 1.95 | 28.71 | 67.13 | 10.20 | 0.00 | 0.00 | 0.00 |
July | 31.25 | 2.90 | 28.36 | 68.01 | 8.47 | 0.00 | 0.00 | 0.00 |
August | 39.84 | 10.55 | 29.29 | 81.64 | 12.08 | 0.00 | 0.00 | 0.00 |
September | 62.19 | 32.31 | 29.88 | 116.61 | 23.39 | 0.00 | 0.00 | 0.00 |
October | 84.49 | 57.12 | 27.37 | 136.26 | 36.71 | 0.00 | 0.00 | 0.00 |
November | 101.68 | 77.52 | 24.16 | 147.64 | 56.85 | 0.00 | 0.00 | 0.00 |
December | 100.77 | 75.64 | 25.13 | 139.97 | 67.37 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.57 | 38.47 | 28.10 | 107.00 | 36.12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.66 | 1.95 | 23.85 | 64.30 | 8.47 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 101.68 | 77.52 | 31.52 | 147.64 | 67.37 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.63 | 89.12 | 28.51 | 166.98 | 73.07 | 0.00 | 0.00 | 0.00 |
February | 109.11 | 76.92 | 32.19 | 157.61 | 65.85 | 0.00 | 0.00 | 0.00 |
March | 88.68 | 51.13 | 37.55 | 132.30 | 59.36 | 0.00 | 0.00 | 0.00 |
April | 60.12 | 22.43 | 37.69 | 99.27 | 38.52 | 0.00 | 0.00 | 0.00 |
May | 42.49 | 5.95 | 36.54 | 76.61 | 23.66 | 0.00 | 0.00 | 0.00 |
June | 36.66 | 2.33 | 34.33 | 79.67 | 12.23 | 0.00 | 0.00 | 0.00 |
July | 37.37 | 3.46 | 33.90 | 80.88 | 10.13 | 0.00 | 0.00 | 0.00 |
August | 47.63 | 12.61 | 35.02 | 97.25 | 14.42 | 0.00 | 0.00 | 0.00 |
September | 74.35 | 38.63 | 35.72 | 139.19 | 27.83 | 0.00 | 0.00 | 0.00 |
October | 101.02 | 68.30 | 32.72 | 162.93 | 43.57 | 0.00 | 0.00 | 0.00 |
November | 121.57 | 92.68 | 28.89 | 176.70 | 67.38 | 0.00 | 0.00 | 0.00 |
December | 120.48 | 90.44 | 30.04 | 167.57 | 79.80 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 79.59 | 45.99 | 33.60 | 127.89 | 42.87 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 36.66 | 2.33 | 28.51 | 76.61 | 10.13 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 121.57 | 92.68 | 37.69 | 176.70 | 79.80 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.63 | 89.12 | 28.51 | 166.98 | 73.07 | 0.00 | 0.00 | 0.00 |
February | 109.11 | 76.92 | 32.19 | 157.61 | 65.85 | 0.00 | 0.00 | 0.00 |
March | 88.68 | 51.13 | 37.55 | 132.30 | 59.36 | 0.00 | 0.00 | 0.00 |
April | 60.12 | 22.43 | 37.69 | 99.27 | 38.52 | 0.00 | 0.00 | 0.00 |
May | 42.49 | 5.95 | 36.54 | 76.61 | 23.66 | 0.00 | 0.00 | 0.00 |
June | 36.66 | 2.33 | 34.33 | 79.67 | 12.23 | 0.00 | 0.00 | 0.00 |
July | 37.37 | 3.46 | 33.90 | 80.88 | 10.13 | 0.00 | 0.00 | 0.00 |
August | 47.63 | 12.61 | 35.02 | 97.25 | 14.42 | 0.00 | 0.00 | 0.00 |
September | 74.35 | 38.63 | 35.72 | 139.19 | 27.83 | 0.00 | 0.00 | 0.00 |
October | 101.02 | 68.30 | 32.72 | 162.93 | 43.57 | 0.00 | 0.00 | 0.00 |
November | 121.57 | 92.68 | 28.89 | 176.70 | 67.38 | 0.00 | 0.00 | 0.00 |
December | 120.48 | 90.44 | 30.04 | 167.57 | 79.80 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 79.59 | 45.99 | 33.60 | 127.89 | 42.87 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 36.66 | 2.33 | 28.51 | 76.61 | 10.13 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 121.57 | 92.68 | 37.69 | 176.70 | 79.80 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 98.39 | 74.54 | 23.85 | 139.16 | 61.66 | 0.00 | 0.00 | 0.00 |
February | 91.26 | 64.34 | 26.92 | 131.38 | 55.53 | 0.00 | 0.00 | 0.00 |
March | 74.17 | 42.77 | 31.40 | 110.22 | 49.93 | 0.00 | 0.00 | 0.00 |
April | 50.29 | 18.76 | 31.52 | 82.97 | 32.18 | 0.00 | 0.00 | 0.00 |
May | 35.54 | 4.97 | 30.56 | 64.46 | 19.53 | 0.00 | 0.00 | 0.00 |
June | 30.66 | 1.95 | 28.71 | 67.55 | 9.93 | 0.00 | 0.00 | 0.00 |
July | 31.25 | 2.90 | 28.36 | 68.35 | 8.21 | 0.00 | 0.00 | 0.00 |
August | 39.84 | 10.55 | 29.29 | 81.87 | 11.80 | 0.00 | 0.00 | 0.00 |
September | 62.19 | 32.31 | 29.88 | 116.63 | 23.08 | 0.00 | 0.00 | 0.00 |
October | 84.49 | 57.12 | 27.37 | 136.11 | 36.53 | 0.00 | 0.00 | 0.00 |
November | 101.68 | 77.52 | 24.16 | 147.46 | 56.75 | 0.00 | 0.00 | 0.00 |
December | 100.77 | 75.64 | 25.13 | 139.74 | 67.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.57 | 38.47 | 28.10 | 107.00 | 35.94 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.66 | 1.95 | 23.85 | 64.46 | 8.21 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 101.68 | 77.52 | 31.52 | 147.46 | 67.34 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 98.39 | 74.54 | 23.85 | 139.16 | 61.66 | 0.00 | 0.00 | 0.00 |
February | 91.26 | 64.34 | 26.92 | 131.38 | 55.53 | 0.00 | 0.00 | 0.00 |
March | 74.17 | 42.77 | 31.40 | 110.22 | 49.93 | 0.00 | 0.00 | 0.00 |
April | 50.29 | 18.76 | 31.52 | 82.97 | 32.18 | 0.00 | 0.00 | 0.00 |
May | 35.54 | 4.97 | 30.56 | 64.46 | 19.53 | 0.00 | 0.00 | 0.00 |
June | 30.66 | 1.95 | 28.71 | 67.55 | 9.93 | 0.00 | 0.00 | 0.00 |
July | 31.25 | 2.90 | 28.36 | 68.35 | 8.21 | 0.00 | 0.00 | 0.00 |
August | 39.84 | 10.55 | 29.29 | 81.87 | 11.80 | 0.00 | 0.00 | 0.00 |
September | 62.19 | 32.31 | 29.88 | 116.63 | 23.08 | 0.00 | 0.00 | 0.00 |
October | 84.49 | 57.12 | 27.37 | 136.11 | 36.53 | 0.00 | 0.00 | 0.00 |
November | 101.68 | 77.52 | 24.16 | 147.46 | 56.75 | 0.00 | 0.00 | 0.00 |
December | 100.77 | 75.64 | 25.13 | 139.74 | 67.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.57 | 38.47 | 28.10 | 107.00 | 35.94 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.66 | 1.95 | 23.85 | 64.46 | 8.21 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 101.68 | 77.52 | 31.52 | 147.46 | 67.34 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.63 | 89.12 | 28.51 | 166.74 | 72.96 | 0.00 | 0.00 | 0.00 |
February | 109.11 | 76.92 | 32.19 | 157.40 | 65.74 | 0.00 | 0.00 | 0.00 |
March | 88.68 | 51.13 | 37.55 | 132.14 | 59.18 | 0.00 | 0.00 | 0.00 |
April | 60.12 | 22.43 | 37.69 | 99.24 | 38.26 | 0.00 | 0.00 | 0.00 |
May | 42.49 | 5.95 | 36.54 | 76.80 | 23.36 | 0.00 | 0.00 | 0.00 |
June | 36.66 | 2.33 | 34.33 | 80.15 | 11.92 | 0.00 | 0.00 | 0.00 |
July | 37.37 | 3.46 | 33.90 | 81.26 | 9.82 | 0.00 | 0.00 | 0.00 |
August | 47.63 | 12.61 | 35.02 | 97.52 | 14.09 | 0.00 | 0.00 | 0.00 |
September | 74.35 | 38.63 | 35.72 | 139.24 | 27.47 | 0.00 | 0.00 | 0.00 |
October | 101.02 | 68.30 | 32.72 | 162.80 | 43.35 | 0.00 | 0.00 | 0.00 |
November | 121.57 | 92.68 | 28.89 | 176.53 | 67.24 | 0.00 | 0.00 | 0.00 |
December | 120.48 | 90.44 | 30.04 | 167.35 | 79.75 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 79.59 | 45.99 | 33.60 | 127.90 | 42.64 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 36.66 | 2.33 | 28.51 | 76.80 | 9.82 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 121.57 | 92.68 | 37.69 | 176.53 | 79.75 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 98.39 | 74.54 | 23.85 | 139.31 | 61.31 | 0.00 | 0.00 | 0.00 |
February | 91.26 | 64.34 | 26.92 | 131.55 | 55.17 | 0.00 | 0.00 | 0.00 |
March | 74.17 | 42.77 | 31.40 | 110.44 | 49.55 | 0.00 | 0.00 | 0.00 |
April | 50.29 | 18.76 | 31.52 | 83.10 | 31.96 | 0.00 | 0.00 | 0.00 |
May | 35.54 | 4.97 | 30.56 | 64.53 | 19.43 | 0.00 | 0.00 | 0.00 |
June | 30.66 | 1.95 | 28.71 | 67.61 | 9.87 | 0.00 | 0.00 | 0.00 |
July | 31.25 | 2.90 | 28.36 | 68.40 | 8.15 | 0.00 | 0.00 | 0.00 |
August | 39.84 | 10.55 | 29.29 | 81.92 | 11.74 | 0.00 | 0.00 | 0.00 |
September | 62.19 | 32.31 | 29.88 | 116.67 | 23.01 | 0.00 | 0.00 | 0.00 |
October | 84.49 | 57.12 | 27.37 | 136.19 | 36.40 | 0.00 | 0.00 | 0.00 |
November | 101.68 | 77.52 | 24.16 | 147.64 | 56.44 | 0.00 | 0.00 | 0.00 |
December | 100.77 | 75.64 | 25.13 | 139.87 | 67.06 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.57 | 38.47 | 28.10 | 107.11 | 35.74 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.66 | 1.95 | 23.85 | 64.53 | 8.15 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 101.68 | 77.52 | 31.52 | 147.64 | 67.06 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 98.39 | 74.54 | 23.85 | 139.31 | 61.31 | 0.00 | 0.00 | 0.00 |
February | 91.26 | 64.34 | 26.92 | 131.55 | 55.17 | 0.00 | 0.00 | 0.00 |
March | 74.17 | 42.77 | 31.40 | 110.44 | 49.55 | 0.00 | 0.00 | 0.00 |
April | 50.29 | 18.76 | 31.52 | 83.10 | 31.96 | 0.00 | 0.00 | 0.00 |
May | 35.54 | 4.97 | 30.56 | 64.53 | 19.43 | 0.00 | 0.00 | 0.00 |
June | 30.66 | 1.95 | 28.71 | 67.61 | 9.87 | 0.00 | 0.00 | 0.00 |
July | 31.25 | 2.90 | 28.36 | 68.40 | 8.15 | 0.00 | 0.00 | 0.00 |
August | 39.84 | 10.55 | 29.29 | 81.92 | 11.74 | 0.00 | 0.00 | 0.00 |
September | 62.19 | 32.31 | 29.88 | 116.67 | 23.01 | 0.00 | 0.00 | 0.00 |
October | 84.49 | 57.12 | 27.37 | 136.19 | 36.40 | 0.00 | 0.00 | 0.00 |
November | 101.68 | 77.52 | 24.16 | 147.64 | 56.44 | 0.00 | 0.00 | 0.00 |
December | 100.77 | 75.64 | 25.13 | 139.87 | 67.06 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.57 | 38.47 | 28.10 | 107.11 | 35.74 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.66 | 1.95 | 23.85 | 64.53 | 8.15 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 101.68 | 77.52 | 31.52 | 147.64 | 67.06 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.63 | 89.12 | 28.51 | 166.92 | 72.54 | 0.00 | 0.00 | 0.00 |
February | 109.11 | 76.92 | 32.19 | 157.61 | 65.32 | 0.00 | 0.00 | 0.00 |
March | 88.68 | 51.13 | 37.55 | 132.40 | 58.72 | 0.00 | 0.00 | 0.00 |
April | 60.12 | 22.43 | 37.69 | 99.40 | 38.01 | 0.00 | 0.00 | 0.00 |
May | 42.49 | 5.95 | 36.54 | 76.88 | 23.24 | 0.00 | 0.00 | 0.00 |
June | 36.66 | 2.33 | 34.33 | 80.23 | 11.85 | 0.00 | 0.00 | 0.00 |
July | 37.37 | 3.46 | 33.90 | 81.33 | 9.76 | 0.00 | 0.00 | 0.00 |
August | 47.63 | 12.61 | 35.02 | 97.57 | 14.02 | 0.00 | 0.00 | 0.00 |
September | 74.35 | 38.63 | 35.72 | 139.29 | 27.39 | 0.00 | 0.00 | 0.00 |
October | 101.02 | 68.30 | 32.72 | 162.88 | 43.19 | 0.00 | 0.00 | 0.00 |
November | 121.57 | 92.68 | 28.89 | 176.76 | 66.87 | 0.00 | 0.00 | 0.00 |
December | 120.48 | 90.44 | 30.04 | 167.50 | 79.42 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 79.59 | 45.99 | 33.60 | 128.04 | 42.41 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 36.66 | 2.33 | 28.51 | 76.88 | 9.76 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 121.57 | 92.68 | 37.69 | 176.76 | 79.42 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 98.39 | 74.54 | 23.85 | 139.69 | 60.30 | 0.00 | 0.00 | 0.00 |
February | 91.26 | 64.34 | 26.92 | 132.02 | 54.11 | 0.00 | 0.00 | 0.00 |
March | 74.17 | 42.77 | 31.40 | 110.97 | 48.45 | 0.00 | 0.00 | 0.00 |
April | 50.29 | 18.76 | 31.52 | 83.42 | 31.33 | 0.00 | 0.00 | 0.00 |
May | 35.54 | 4.97 | 30.56 | 64.64 | 19.19 | 0.00 | 0.00 | 0.00 |
June | 30.66 | 1.95 | 28.71 | 67.61 | 9.80 | 0.00 | 0.00 | 0.00 |
July | 31.25 | 2.90 | 28.36 | 68.37 | 8.13 | 0.00 | 0.00 | 0.00 |
August | 39.84 | 10.55 | 29.29 | 81.87 | 11.73 | 0.00 | 0.00 | 0.00 |
September | 62.19 | 32.31 | 29.88 | 116.65 | 22.97 | 0.00 | 0.00 | 0.00 |
October | 84.49 | 57.12 | 27.37 | 136.33 | 36.08 | 0.00 | 0.00 | 0.00 |
November | 101.68 | 77.52 | 24.16 | 148.09 | 55.62 | 0.00 | 0.00 | 0.00 |
December | 100.77 | 75.64 | 25.13 | 140.22 | 66.22 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.57 | 38.47 | 28.10 | 107.33 | 35.23 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.66 | 1.95 | 23.85 | 64.64 | 8.13 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 101.68 | 77.52 | 31.52 | 148.09 | 66.22 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 98.39 | 74.54 | 23.85 | 139.69 | 60.30 | 0.00 | 0.00 | 0.00 |
February | 91.26 | 64.34 | 26.92 | 132.02 | 54.11 | 0.00 | 0.00 | 0.00 |
March | 74.17 | 42.77 | 31.40 | 110.97 | 48.45 | 0.00 | 0.00 | 0.00 |
April | 50.29 | 18.76 | 31.52 | 83.42 | 31.33 | 0.00 | 0.00 | 0.00 |
May | 35.54 | 4.97 | 30.56 | 64.64 | 19.19 | 0.00 | 0.00 | 0.00 |
June | 30.66 | 1.95 | 28.71 | 67.61 | 9.80 | 0.00 | 0.00 | 0.00 |
July | 31.25 | 2.90 | 28.36 | 68.37 | 8.13 | 0.00 | 0.00 | 0.00 |
August | 39.84 | 10.55 | 29.29 | 81.87 | 11.73 | 0.00 | 0.00 | 0.00 |
September | 62.19 | 32.31 | 29.88 | 116.65 | 22.97 | 0.00 | 0.00 | 0.00 |
October | 84.49 | 57.12 | 27.37 | 136.33 | 36.08 | 0.00 | 0.00 | 0.00 |
November | 101.68 | 77.52 | 24.16 | 148.09 | 55.62 | 0.00 | 0.00 | 0.00 |
December | 100.77 | 75.64 | 25.13 | 140.22 | 66.22 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.57 | 38.47 | 28.10 | 107.33 | 35.23 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.66 | 1.95 | 23.85 | 64.64 | 8.13 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 101.68 | 77.52 | 31.52 | 148.09 | 66.22 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.63 | 89.12 | 28.51 | 167.36 | 71.35 | 0.00 | 0.00 | 0.00 |
February | 109.11 | 76.92 | 32.19 | 158.17 | 64.07 | 0.00 | 0.00 | 0.00 |
March | 88.68 | 51.13 | 37.55 | 133.03 | 57.43 | 0.00 | 0.00 | 0.00 |
April | 60.12 | 22.43 | 37.69 | 99.78 | 37.27 | 0.00 | 0.00 | 0.00 |
May | 42.49 | 5.95 | 36.54 | 77.02 | 22.95 | 0.00 | 0.00 | 0.00 |
June | 36.66 | 2.33 | 34.33 | 80.23 | 11.77 | 0.00 | 0.00 | 0.00 |
July | 37.37 | 3.46 | 33.90 | 81.29 | 9.73 | 0.00 | 0.00 | 0.00 |
August | 47.63 | 12.61 | 35.02 | 97.52 | 14.01 | 0.00 | 0.00 | 0.00 |
September | 74.35 | 38.63 | 35.72 | 139.26 | 27.34 | 0.00 | 0.00 | 0.00 |
October | 101.02 | 68.30 | 32.72 | 163.05 | 42.82 | 0.00 | 0.00 | 0.00 |
November | 121.57 | 92.68 | 28.89 | 177.29 | 65.90 | 0.00 | 0.00 | 0.00 |
December | 120.48 | 90.44 | 30.04 | 167.91 | 78.42 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 79.59 | 45.99 | 33.60 | 128.30 | 41.81 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 36.66 | 2.33 | 28.51 | 77.02 | 9.73 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 121.57 | 92.68 | 37.69 | 177.29 | 78.42 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 98.39 | 74.54 | 23.85 | 140.57 | 56.82 | 0.00 | 0.00 | 0.00 |
February | 91.26 | 64.34 | 26.92 | 133.08 | 50.50 | 0.00 | 0.00 | 0.00 |
March | 74.17 | 42.77 | 31.40 | 111.94 | 44.84 | 0.00 | 0.00 | 0.00 |
April | 50.29 | 18.76 | 31.52 | 83.78 | 29.12 | 0.00 | 0.00 | 0.00 |
May | 35.54 | 4.97 | 30.56 | 64.49 | 18.21 | 0.00 | 0.00 | 0.00 |
June | 30.66 | 1.95 | 28.71 | 66.89 | 9.58 | 0.00 | 0.00 | 0.00 |
July | 31.25 | 2.90 | 28.36 | 67.44 | 8.19 | 0.00 | 0.00 | 0.00 |
August | 39.84 | 10.55 | 29.29 | 80.96 | 11.88 | 0.00 | 0.00 | 0.00 |
September | 62.19 | 32.31 | 29.88 | 115.97 | 23.03 | 0.00 | 0.00 | 0.00 |
October | 84.49 | 57.12 | 27.37 | 136.39 | 35.01 | 0.00 | 0.00 | 0.00 |
November | 101.68 | 77.52 | 24.16 | 148.85 | 53.07 | 0.00 | 0.00 | 0.00 |
December | 100.77 | 75.64 | 25.13 | 141.07 | 63.17 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.57 | 38.47 | 28.10 | 107.45 | 33.53 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.66 | 1.95 | 23.85 | 64.49 | 8.19 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 101.68 | 77.52 | 31.52 | 148.85 | 63.17 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 98.39 | 74.54 | 23.85 | 140.57 | 56.82 | 0.00 | 0.00 | 0.00 |
February | 91.26 | 64.34 | 26.92 | 133.08 | 50.50 | 0.00 | 0.00 | 0.00 |
March | 74.17 | 42.77 | 31.40 | 111.94 | 44.84 | 0.00 | 0.00 | 0.00 |
April | 50.29 | 18.76 | 31.52 | 83.78 | 29.12 | 0.00 | 0.00 | 0.00 |
May | 35.54 | 4.97 | 30.56 | 64.49 | 18.21 | 0.00 | 0.00 | 0.00 |
June | 30.66 | 1.95 | 28.71 | 66.89 | 9.58 | 0.00 | 0.00 | 0.00 |
July | 31.25 | 2.90 | 28.36 | 67.44 | 8.19 | 0.00 | 0.00 | 0.00 |
August | 39.84 | 10.55 | 29.29 | 80.96 | 11.88 | 0.00 | 0.00 | 0.00 |
September | 62.19 | 32.31 | 29.88 | 115.97 | 23.03 | 0.00 | 0.00 | 0.00 |
October | 84.49 | 57.12 | 27.37 | 136.39 | 35.01 | 0.00 | 0.00 | 0.00 |
November | 101.68 | 77.52 | 24.16 | 148.85 | 53.07 | 0.00 | 0.00 | 0.00 |
December | 100.77 | 75.64 | 25.13 | 141.07 | 63.17 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.57 | 38.47 | 28.10 | 107.45 | 33.53 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.66 | 1.95 | 23.85 | 64.49 | 8.19 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 101.68 | 77.52 | 31.52 | 148.85 | 63.17 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.63 | 89.12 | 28.51 | 168.43 | 67.25 | 0.00 | 0.00 | 0.00 |
February | 109.11 | 76.92 | 32.19 | 159.44 | 59.81 | 0.00 | 0.00 | 0.00 |
March | 88.68 | 51.13 | 37.55 | 134.19 | 53.18 | 0.00 | 0.00 | 0.00 |
April | 60.12 | 22.43 | 37.69 | 100.21 | 34.66 | 0.00 | 0.00 | 0.00 |
May | 42.49 | 5.95 | 36.54 | 76.83 | 21.80 | 0.00 | 0.00 | 0.00 |
June | 36.66 | 2.33 | 34.33 | 79.37 | 11.51 | 0.00 | 0.00 | 0.00 |
July | 37.37 | 3.46 | 33.90 | 80.18 | 9.81 | 0.00 | 0.00 | 0.00 |
August | 47.63 | 12.61 | 35.02 | 96.43 | 14.19 | 0.00 | 0.00 | 0.00 |
September | 74.35 | 38.63 | 35.72 | 138.45 | 27.42 | 0.00 | 0.00 | 0.00 |
October | 101.02 | 68.30 | 32.72 | 163.13 | 41.56 | 0.00 | 0.00 | 0.00 |
November | 121.57 | 92.68 | 28.89 | 178.19 | 62.90 | 0.00 | 0.00 | 0.00 |
December | 120.48 | 90.44 | 30.04 | 168.94 | 74.81 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 79.59 | 45.99 | 33.60 | 128.45 | 39.81 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 36.66 | 2.33 | 28.51 | 76.83 | 9.81 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 121.57 | 92.68 | 37.69 | 178.19 | 74.81 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.263516E+09 | 0.199641E+09 | 63875169.97 | 0.372024E+09 | 0.170130E+09 |
February | 0.220785E+09 | 0.155650E+09 | 65135039.89 | 0.317589E+09 | 0.137790E+09 |
March | 0.198659E+09 | 0.114546E+09 | 84112693.66 | 0.295027E+09 | 0.137025E+09 |
April | 0.130345E+09 | 48635019.57 | 81710029.33 | 0.215384E+09 | 84163042.25 |
May | 95183853.57 | 13322620.49 | 81861233.08 | 0.173260E+09 | 51661248.46 |
June | 79470675.37 | 5042437.65 | 74428237.72 | 0.176190E+09 | 24937186.90 |
July | 83711989.83 | 7760244.97 | 75951744.86 | 0.184741E+09 | 21003385.52 |
August | 0.106710E+09 | 28246702.05 | 78463003.44 | 0.220522E+09 | 30798233.56 |
September | 0.161189E+09 | 83743175.85 | 77445616.35 | 0.302552E+09 | 58673860.20 |
October | 0.226308E+09 | 0.153000E+09 | 73308827.12 | 0.365056E+09 | 97964369.05 |
November | 0.263556E+09 | 0.200929E+09 | 62626973.79 | 0.381755E+09 | 0.149713E+09 |
December | 0.269901E+09 | 0.202600E+09 | 67301001.16 | 0.373583E+09 | 0.184906E+09 |
Annual Sum or Average | 0.209934E+10 | 0.121312E+10 | 0.886220E+09 | 0.337768E+10 | 0.114877E+10 |
Minimum of Months | 79470675.37 | 5042437.65 | 62626973.79 | 0.173260E+09 | 21003385.52 |
Maximum of Months | 0.269901E+09 | 0.202600E+09 | 84112693.66 | 0.381755E+09 | 0.184906E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.263516E+09 | 0.199641E+09 | 63875169.97 | 0.372024E+09 | 0.170130E+09 |
February | 0.220785E+09 | 0.155650E+09 | 65135039.89 | 0.317589E+09 | 0.137790E+09 |
March | 0.198659E+09 | 0.114546E+09 | 84112693.66 | 0.295027E+09 | 0.137025E+09 |
April | 0.130345E+09 | 48635019.57 | 81710029.33 | 0.215384E+09 | 84163042.25 |
May | 95183853.57 | 13322620.49 | 81861233.08 | 0.173260E+09 | 51661248.46 |
June | 79470675.37 | 5042437.65 | 74428237.72 | 0.176190E+09 | 24937186.90 |
July | 83711989.83 | 7760244.97 | 75951744.86 | 0.184741E+09 | 21003385.52 |
August | 0.106710E+09 | 28246702.05 | 78463003.44 | 0.220522E+09 | 30798233.56 |
September | 0.161189E+09 | 83743175.85 | 77445616.35 | 0.302552E+09 | 58673860.20 |
October | 0.226308E+09 | 0.153000E+09 | 73308827.12 | 0.365056E+09 | 97964369.05 |
November | 0.263556E+09 | 0.200929E+09 | 62626973.79 | 0.381755E+09 | 0.149713E+09 |
December | 0.269901E+09 | 0.202600E+09 | 67301001.16 | 0.373583E+09 | 0.184906E+09 |
Annual Sum or Average | 0.209934E+10 | 0.121312E+10 | 0.886220E+09 | 0.337768E+10 | 0.114877E+10 |
Minimum of Months | 79470675.37 | 5042437.65 | 62626973.79 | 0.173260E+09 | 21003385.52 |
Maximum of Months | 0.269901E+09 | 0.202600E+09 | 84112693.66 | 0.381755E+09 | 0.184906E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.263516E+09 | 0.199641E+09 | 63875169.97 | 0.372024E+09 | 0.170130E+09 |
February | 0.220785E+09 | 0.155650E+09 | 65135039.89 | 0.317589E+09 | 0.137790E+09 |
March | 0.198659E+09 | 0.114546E+09 | 84112693.66 | 0.295027E+09 | 0.137025E+09 |
April | 0.130345E+09 | 48635019.57 | 81710029.33 | 0.215384E+09 | 84163042.25 |
May | 95183853.57 | 13322620.49 | 81861233.08 | 0.173260E+09 | 51661248.46 |
June | 79470675.37 | 5042437.65 | 74428237.72 | 0.176190E+09 | 24937186.90 |
July | 83711989.83 | 7760244.97 | 75951744.86 | 0.184741E+09 | 21003385.52 |
August | 0.106710E+09 | 28246702.05 | 78463003.44 | 0.220522E+09 | 30798233.56 |
September | 0.161189E+09 | 83743175.85 | 77445616.35 | 0.302552E+09 | 58673860.20 |
October | 0.226308E+09 | 0.153000E+09 | 73308827.12 | 0.365056E+09 | 97964369.05 |
November | 0.263556E+09 | 0.200929E+09 | 62626973.79 | 0.381755E+09 | 0.149713E+09 |
December | 0.269901E+09 | 0.202600E+09 | 67301001.16 | 0.373583E+09 | 0.184906E+09 |
Annual Sum or Average | 0.209934E+10 | 0.121312E+10 | 0.886220E+09 | 0.337768E+10 | 0.114877E+10 |
Minimum of Months | 79470675.37 | 5042437.65 | 62626973.79 | 0.173260E+09 | 21003385.52 |
Maximum of Months | 0.269901E+09 | 0.202600E+09 | 84112693.66 | 0.381755E+09 | 0.184906E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.263516E+09 | 0.199641E+09 | 63875169.97 | 0.372024E+09 | 0.170130E+09 |
February | 0.220785E+09 | 0.155650E+09 | 65135039.89 | 0.317589E+09 | 0.137790E+09 |
March | 0.198659E+09 | 0.114546E+09 | 84112693.66 | 0.295027E+09 | 0.137025E+09 |
April | 0.130345E+09 | 48635019.57 | 81710029.33 | 0.215384E+09 | 84163042.25 |
May | 95183853.57 | 13322620.49 | 81861233.08 | 0.173260E+09 | 51661248.46 |
June | 79470675.37 | 5042437.65 | 74428237.72 | 0.176190E+09 | 24937186.90 |
July | 83711989.83 | 7760244.97 | 75951744.86 | 0.184741E+09 | 21003385.52 |
August | 0.106710E+09 | 28246702.05 | 78463003.44 | 0.220522E+09 | 30798233.56 |
September | 0.161189E+09 | 83743175.85 | 77445616.35 | 0.302552E+09 | 58673860.20 |
October | 0.226308E+09 | 0.153000E+09 | 73308827.12 | 0.365056E+09 | 97964369.05 |
November | 0.263556E+09 | 0.200929E+09 | 62626973.79 | 0.381755E+09 | 0.149713E+09 |
December | 0.269901E+09 | 0.202600E+09 | 67301001.16 | 0.373583E+09 | 0.184906E+09 |
Annual Sum or Average | 0.209934E+10 | 0.121312E+10 | 0.886220E+09 | 0.337768E+10 | 0.114877E+10 |
Minimum of Months | 79470675.37 | 5042437.65 | 62626973.79 | 0.173260E+09 | 21003385.52 |
Maximum of Months | 0.269901E+09 | 0.202600E+09 | 84112693.66 | 0.381755E+09 | 0.184906E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.316787E+09 | 0.239999E+09 | 76787787.94 | 0.448025E+09 | 0.202501E+09 |
February | 0.265418E+09 | 0.187115E+09 | 78302345.55 | 0.382456E+09 | 0.164074E+09 |
March | 0.238818E+09 | 0.137702E+09 | 0.101116E+09 | 0.355490E+09 | 0.163321E+09 |
April | 0.156695E+09 | 58466780.93 | 98228034.59 | 0.258951E+09 | 0.100664E+09 |
May | 0.114426E+09 | 16015840.86 | 98409804.77 | 0.207493E+09 | 62133304.03 |
June | 95535986.37 | 6061786.34 | 89474200.03 | 0.210125E+09 | 30080603.16 |
July | 0.100635E+09 | 9329009.15 | 91305690.16 | 0.220735E+09 | 25292144.59 |
August | 0.128281E+09 | 33956884.46 | 94324609.58 | 0.263980E+09 | 36994030.37 |
September | 0.193774E+09 | 0.100672E+09 | 93101553.68 | 0.363073E+09 | 70293692.30 |
October | 0.272058E+09 | 0.183929E+09 | 88128496.15 | 0.438856E+09 | 0.116965E+09 |
November | 0.316835E+09 | 0.241548E+09 | 75287263.97 | 0.459395E+09 | 0.178446E+09 |
December | 0.324462E+09 | 0.243556E+09 | 80906164.45 | 0.449694E+09 | 0.220258E+09 |
Annual Sum or Average | 0.252372E+10 | 0.145835E+10 | 0.106537E+10 | 0.405827E+10 | 0.137102E+10 |
Minimum of Months | 95535986.37 | 6061786.34 | 75287263.97 | 0.207493E+09 | 25292144.59 |
Maximum of Months | 0.324462E+09 | 0.243556E+09 | 0.101116E+09 | 0.459395E+09 | 0.220258E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.316787E+09 | 0.239999E+09 | 76787787.94 | 0.448025E+09 | 0.202501E+09 |
February | 0.265418E+09 | 0.187115E+09 | 78302345.55 | 0.382456E+09 | 0.164074E+09 |
March | 0.238818E+09 | 0.137702E+09 | 0.101116E+09 | 0.355490E+09 | 0.163321E+09 |
April | 0.156695E+09 | 58466780.93 | 98228034.59 | 0.258951E+09 | 0.100664E+09 |
May | 0.114426E+09 | 16015840.86 | 98409804.77 | 0.207493E+09 | 62133304.03 |
June | 95535986.37 | 6061786.34 | 89474200.03 | 0.210125E+09 | 30080603.16 |
July | 0.100635E+09 | 9329009.15 | 91305690.16 | 0.220735E+09 | 25292144.59 |
August | 0.128281E+09 | 33956884.46 | 94324609.58 | 0.263980E+09 | 36994030.37 |
September | 0.193774E+09 | 0.100672E+09 | 93101553.68 | 0.363073E+09 | 70293692.30 |
October | 0.272058E+09 | 0.183929E+09 | 88128496.15 | 0.438856E+09 | 0.116965E+09 |
November | 0.316835E+09 | 0.241548E+09 | 75287263.97 | 0.459395E+09 | 0.178446E+09 |
December | 0.324462E+09 | 0.243556E+09 | 80906164.45 | 0.449694E+09 | 0.220258E+09 |
Annual Sum or Average | 0.252372E+10 | 0.145835E+10 | 0.106537E+10 | 0.405827E+10 | 0.137102E+10 |
Minimum of Months | 95535986.37 | 6061786.34 | 75287263.97 | 0.207493E+09 | 25292144.59 |
Maximum of Months | 0.324462E+09 | 0.243556E+09 | 0.101116E+09 | 0.459395E+09 | 0.220258E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.263516E+09 | 0.199641E+09 | 63875169.97 | 0.367062E+09 | 0.182500E+09 |
February | 0.220785E+09 | 0.155650E+09 | 65135039.89 | 0.312799E+09 | 0.147721E+09 |
March | 0.198659E+09 | 0.114546E+09 | 84112693.66 | 0.289850E+09 | 0.145908E+09 |
April | 0.130345E+09 | 48635019.57 | 81710029.33 | 0.213441E+09 | 86901049.56 |
May | 95183853.57 | 13322620.49 | 81861233.08 | 0.173155E+09 | 52438610.84 |
June | 79470675.37 | 5042437.65 | 74428237.72 | 0.177247E+09 | 25310201.97 |
July | 83711989.83 | 7760244.97 | 75951744.86 | 0.186007E+09 | 21153135.35 |
August | 0.106710E+09 | 28246702.05 | 78463003.44 | 0.221646E+09 | 30783195.97 |
September | 0.161189E+09 | 83743175.85 | 77445616.35 | 0.303013E+09 | 58188914.67 |
October | 0.226308E+09 | 0.153000E+09 | 73308827.12 | 0.364167E+09 | 98860317.34 |
November | 0.263556E+09 | 0.200929E+09 | 62626973.79 | 0.378165E+09 | 0.156039E+09 |
December | 0.269901E+09 | 0.202600E+09 | 67301001.16 | 0.368789E+09 | 0.196516E+09 |
Annual Sum or Average | 0.209934E+10 | 0.121312E+10 | 0.886220E+09 | 0.335534E+10 | 0.120232E+10 |
Minimum of Months | 79470675.37 | 5042437.65 | 62626973.79 | 0.173155E+09 | 21153135.35 |
Maximum of Months | 0.269901E+09 | 0.202600E+09 | 84112693.66 | 0.378165E+09 | 0.196516E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.263516E+09 | 0.199641E+09 | 63875169.97 | 0.367062E+09 | 0.182500E+09 |
February | 0.220785E+09 | 0.155650E+09 | 65135039.89 | 0.312799E+09 | 0.147721E+09 |
March | 0.198659E+09 | 0.114546E+09 | 84112693.66 | 0.289850E+09 | 0.145908E+09 |
April | 0.130345E+09 | 48635019.57 | 81710029.33 | 0.213441E+09 | 86901049.56 |
May | 95183853.57 | 13322620.49 | 81861233.08 | 0.173155E+09 | 52438610.84 |
June | 79470675.37 | 5042437.65 | 74428237.72 | 0.177247E+09 | 25310201.97 |
July | 83711989.83 | 7760244.97 | 75951744.86 | 0.186007E+09 | 21153135.35 |
August | 0.106710E+09 | 28246702.05 | 78463003.44 | 0.221646E+09 | 30783195.97 |
September | 0.161189E+09 | 83743175.85 | 77445616.35 | 0.303013E+09 | 58188914.67 |
October | 0.226308E+09 | 0.153000E+09 | 73308827.12 | 0.364167E+09 | 98860317.34 |
November | 0.263556E+09 | 0.200929E+09 | 62626973.79 | 0.378165E+09 | 0.156039E+09 |
December | 0.269901E+09 | 0.202600E+09 | 67301001.16 | 0.368789E+09 | 0.196516E+09 |
Annual Sum or Average | 0.209934E+10 | 0.121312E+10 | 0.886220E+09 | 0.335534E+10 | 0.120232E+10 |
Minimum of Months | 79470675.37 | 5042437.65 | 62626973.79 | 0.173155E+09 | 21153135.35 |
Maximum of Months | 0.269901E+09 | 0.202600E+09 | 84112693.66 | 0.378165E+09 | 0.196516E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.316787E+09 | 0.239999E+09 | 76787787.94 | 0.442223E+09 | 0.217038E+09 |
February | 0.265418E+09 | 0.187115E+09 | 78302345.55 | 0.376840E+09 | 0.175761E+09 |
March | 0.238818E+09 | 0.137702E+09 | 0.101116E+09 | 0.349422E+09 | 0.173790E+09 |
April | 0.156695E+09 | 58466780.93 | 98228034.59 | 0.256674E+09 | 0.103913E+09 |
May | 0.114426E+09 | 16015840.86 | 98409804.77 | 0.207348E+09 | 63074524.83 |
June | 95535986.37 | 6061786.34 | 89474200.03 | 0.211328E+09 | 30537778.37 |
July | 0.100635E+09 | 9329009.15 | 91305690.16 | 0.222222E+09 | 25475686.04 |
August | 0.128281E+09 | 33956884.46 | 94324609.58 | 0.265327E+09 | 36979407.31 |
September | 0.193774E+09 | 0.100672E+09 | 93101553.68 | 0.363680E+09 | 69712117.22 |
October | 0.272058E+09 | 0.183929E+09 | 88128496.15 | 0.437896E+09 | 0.118007E+09 |
November | 0.316835E+09 | 0.241548E+09 | 75287263.97 | 0.455228E+09 | 0.185881E+09 |
December | 0.324462E+09 | 0.243556E+09 | 80906164.45 | 0.444075E+09 | 0.233918E+09 |
Annual Sum or Average | 0.252372E+10 | 0.145835E+10 | 0.106537E+10 | 0.403226E+10 | 0.143409E+10 |
Minimum of Months | 95535986.37 | 6061786.34 | 75287263.97 | 0.207348E+09 | 25475686.04 |
Maximum of Months | 0.324462E+09 | 0.243556E+09 | 0.101116E+09 | 0.455228E+09 | 0.233918E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.263516E+09 | 0.199641E+09 | 63875169.97 | 0.368533E+09 | 0.176859E+09 |
February | 0.220785E+09 | 0.155650E+09 | 65135039.89 | 0.313846E+09 | 0.144178E+09 |
March | 0.198659E+09 | 0.114546E+09 | 84112693.66 | 0.290662E+09 | 0.143847E+09 |
April | 0.130345E+09 | 48635019.57 | 81710029.33 | 0.212947E+09 | 89241654.96 |
May | 95183853.57 | 13322620.49 | 81861233.08 | 0.171556E+09 | 56409391.63 |
June | 79470675.37 | 5042437.65 | 74428237.72 | 0.173391E+09 | 28505179.25 |
July | 83711989.83 | 7760244.97 | 75951744.86 | 0.182010E+09 | 24685265.34 |
August | 0.106710E+09 | 28246702.05 | 78463003.44 | 0.218578E+09 | 34685160.79 |
September | 0.161189E+09 | 83743175.85 | 77445616.35 | 0.302126E+09 | 63428738.31 |
October | 0.226308E+09 | 0.153000E+09 | 73308827.12 | 0.363710E+09 | 0.102112E+09 |
November | 0.263556E+09 | 0.200929E+09 | 62626973.79 | 0.379053E+09 | 0.154736E+09 |
December | 0.269901E+09 | 0.202600E+09 | 67301001.16 | 0.370173E+09 | 0.191161E+09 |
Annual Sum or Average | 0.209934E+10 | 0.121312E+10 | 0.886220E+09 | 0.334658E+10 | 0.120985E+10 |
Minimum of Months | 79470675.37 | 5042437.65 | 62626973.79 | 0.171556E+09 | 24685265.34 |
Maximum of Months | 0.269901E+09 | 0.202600E+09 | 84112693.66 | 0.379053E+09 | 0.191161E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.263516E+09 | 0.199641E+09 | 63875169.97 | 0.368533E+09 | 0.176859E+09 |
February | 0.220785E+09 | 0.155650E+09 | 65135039.89 | 0.313846E+09 | 0.144178E+09 |
March | 0.198659E+09 | 0.114546E+09 | 84112693.66 | 0.290662E+09 | 0.143847E+09 |
April | 0.130345E+09 | 48635019.57 | 81710029.33 | 0.212947E+09 | 89241654.96 |
May | 95183853.57 | 13322620.49 | 81861233.08 | 0.171556E+09 | 56409391.63 |
June | 79470675.37 | 5042437.65 | 74428237.72 | 0.173391E+09 | 28505179.25 |
July | 83711989.83 | 7760244.97 | 75951744.86 | 0.182010E+09 | 24685265.34 |
August | 0.106710E+09 | 28246702.05 | 78463003.44 | 0.218578E+09 | 34685160.79 |
September | 0.161189E+09 | 83743175.85 | 77445616.35 | 0.302126E+09 | 63428738.31 |
October | 0.226308E+09 | 0.153000E+09 | 73308827.12 | 0.363710E+09 | 0.102112E+09 |
November | 0.263556E+09 | 0.200929E+09 | 62626973.79 | 0.379053E+09 | 0.154736E+09 |
December | 0.269901E+09 | 0.202600E+09 | 67301001.16 | 0.370173E+09 | 0.191161E+09 |
Annual Sum or Average | 0.209934E+10 | 0.121312E+10 | 0.886220E+09 | 0.334658E+10 | 0.120985E+10 |
Minimum of Months | 79470675.37 | 5042437.65 | 62626973.79 | 0.171556E+09 | 24685265.34 |
Maximum of Months | 0.269901E+09 | 0.202600E+09 | 84112693.66 | 0.379053E+09 | 0.191161E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.315056E+09 | 0.238688E+09 | 76368182.54 | 0.441554E+09 | 0.209248E+09 |
February | 0.263967E+09 | 0.186093E+09 | 77874463.88 | 0.376025E+09 | 0.170656E+09 |
March | 0.237513E+09 | 0.136950E+09 | 0.100564E+09 | 0.348478E+09 | 0.170422E+09 |
April | 0.155839E+09 | 58147290.33 | 97691269.37 | 0.254705E+09 | 0.106074E+09 |
May | 0.113800E+09 | 15928322.61 | 97872046.28 | 0.204388E+09 | 67396206.88 |
June | 95013931.80 | 6028661.83 | 88985269.98 | 0.205756E+09 | 34179537.66 |
July | 0.100085E+09 | 9278030.96 | 90806751.97 | 0.216411E+09 | 29520506.93 |
August | 0.127581E+09 | 33771327.72 | 93809174.56 | 0.260354E+09 | 41394591.10 |
September | 0.192715E+09 | 0.100122E+09 | 92592802.02 | 0.360662E+09 | 75459368.61 |
October | 0.270571E+09 | 0.182924E+09 | 87646919.67 | 0.434972E+09 | 0.121144E+09 |
November | 0.315104E+09 | 0.240228E+09 | 74875858.16 | 0.453793E+09 | 0.183319E+09 |
December | 0.322689E+09 | 0.242225E+09 | 80464054.26 | 0.443294E+09 | 0.226360E+09 |
Annual Sum or Average | 0.250993E+10 | 0.145038E+10 | 0.105955E+10 | 0.400039E+10 | 0.143517E+10 |
Minimum of Months | 95013931.80 | 6028661.83 | 74875858.16 | 0.204388E+09 | 29520506.93 |
Maximum of Months | 0.322689E+09 | 0.242225E+09 | 0.100564E+09 | 0.453793E+09 | 0.226360E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.263516E+09 | 0.199641E+09 | 63875169.97 | 0.369515E+09 | 0.173870E+09 |
February | 0.220785E+09 | 0.155650E+09 | 65135039.89 | 0.314662E+09 | 0.141895E+09 |
March | 0.198659E+09 | 0.114546E+09 | 84112693.66 | 0.291476E+09 | 0.141901E+09 |
April | 0.130345E+09 | 48635019.57 | 81710029.33 | 0.213138E+09 | 88754667.23 |
May | 95183853.57 | 13322620.49 | 81861233.08 | 0.171509E+09 | 56551274.38 |
June | 79470675.37 | 5042437.65 | 74428237.72 | 0.173193E+09 | 28879820.68 |
July | 83711989.83 | 7760244.97 | 75951744.86 | 0.181789E+09 | 25081114.16 |
August | 0.106710E+09 | 28246702.05 | 78463003.44 | 0.218409E+09 | 35095854.48 |
September | 0.161189E+09 | 83743175.85 | 77445616.35 | 0.302058E+09 | 63748254.36 |
October | 0.226308E+09 | 0.153000E+09 | 73308827.12 | 0.363773E+09 | 0.101910E+09 |
November | 0.263556E+09 | 0.200929E+09 | 62626973.79 | 0.379661E+09 | 0.153245E+09 |
December | 0.269901E+09 | 0.202600E+09 | 67301001.16 | 0.371077E+09 | 0.188412E+09 |
Annual Sum or Average | 0.209934E+10 | 0.121312E+10 | 0.886220E+09 | 0.335026E+10 | 0.119934E+10 |
Minimum of Months | 79470675.37 | 5042437.65 | 62626973.79 | 0.171509E+09 | 25081114.16 |
Maximum of Months | 0.269901E+09 | 0.202600E+09 | 84112693.66 | 0.379661E+09 | 0.188412E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.263516E+09 | 0.199641E+09 | 63875169.97 | 0.369515E+09 | 0.173870E+09 |
February | 0.220785E+09 | 0.155650E+09 | 65135039.89 | 0.314662E+09 | 0.141895E+09 |
March | 0.198659E+09 | 0.114546E+09 | 84112693.66 | 0.291476E+09 | 0.141901E+09 |
April | 0.130345E+09 | 48635019.57 | 81710029.33 | 0.213138E+09 | 88754667.23 |
May | 95183853.57 | 13322620.49 | 81861233.08 | 0.171509E+09 | 56551274.38 |
June | 79470675.37 | 5042437.65 | 74428237.72 | 0.173193E+09 | 28879820.68 |
July | 83711989.83 | 7760244.97 | 75951744.86 | 0.181789E+09 | 25081114.16 |
August | 0.106710E+09 | 28246702.05 | 78463003.44 | 0.218409E+09 | 35095854.48 |
September | 0.161189E+09 | 83743175.85 | 77445616.35 | 0.302058E+09 | 63748254.36 |
October | 0.226308E+09 | 0.153000E+09 | 73308827.12 | 0.363773E+09 | 0.101910E+09 |
November | 0.263556E+09 | 0.200929E+09 | 62626973.79 | 0.379661E+09 | 0.153245E+09 |
December | 0.269901E+09 | 0.202600E+09 | 67301001.16 | 0.371077E+09 | 0.188412E+09 |
Annual Sum or Average | 0.209934E+10 | 0.121312E+10 | 0.886220E+09 | 0.335026E+10 | 0.119934E+10 |
Minimum of Months | 79470675.37 | 5042437.65 | 62626973.79 | 0.171509E+09 | 25081114.16 |
Maximum of Months | 0.269901E+09 | 0.202600E+09 | 84112693.66 | 0.379661E+09 | 0.188412E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.315056E+09 | 0.238688E+09 | 76368182.54 | 0.442726E+09 | 0.205714E+09 |
February | 0.263967E+09 | 0.186093E+09 | 77874463.88 | 0.376999E+09 | 0.167962E+09 |
March | 0.237513E+09 | 0.136950E+09 | 0.100564E+09 | 0.349447E+09 | 0.168125E+09 |
April | 0.155839E+09 | 58147290.33 | 97691269.37 | 0.254935E+09 | 0.105499E+09 |
May | 0.113800E+09 | 15928322.61 | 97872046.28 | 0.204333E+09 | 67564858.56 |
June | 95013931.80 | 6028661.83 | 88985269.98 | 0.205523E+09 | 34625380.76 |
July | 0.100085E+09 | 9278030.96 | 90806751.97 | 0.216150E+09 | 29990203.05 |
August | 0.127581E+09 | 33771327.72 | 93809174.56 | 0.260153E+09 | 41881824.49 |
September | 0.192715E+09 | 0.100122E+09 | 92592802.02 | 0.360580E+09 | 75837257.86 |
October | 0.270571E+09 | 0.182924E+09 | 87646919.67 | 0.435049E+09 | 0.120905E+09 |
November | 0.315104E+09 | 0.240228E+09 | 74875858.16 | 0.454519E+09 | 0.181556E+09 |
December | 0.322689E+09 | 0.242225E+09 | 80464054.26 | 0.444372E+09 | 0.223108E+09 |
Annual Sum or Average | 0.250993E+10 | 0.145038E+10 | 0.105955E+10 | 0.400479E+10 | 0.142277E+10 |
Minimum of Months | 95013931.80 | 6028661.83 | 74875858.16 | 0.204333E+09 | 29990203.05 |
Maximum of Months | 0.322689E+09 | 0.242225E+09 | 0.100564E+09 | 0.454519E+09 | 0.223108E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.263516E+09 | 0.199641E+09 | 63875169.97 | 0.370666E+09 | 0.171110E+09 |
February | 0.220785E+09 | 0.155650E+09 | 65135039.89 | 0.315742E+09 | 0.139529E+09 |
March | 0.198659E+09 | 0.114546E+09 | 84112693.66 | 0.292752E+09 | 0.139494E+09 |
April | 0.130345E+09 | 48635019.57 | 81710029.33 | 0.213772E+09 | 87421269.70 |
May | 95183853.57 | 13322620.49 | 81861233.08 | 0.171913E+09 | 55680094.48 |
June | 79470675.37 | 5042437.65 | 74428237.72 | 0.173637E+09 | 28243843.23 |
July | 83711989.83 | 7760244.97 | 75951744.86 | 0.182178E+09 | 24460850.60 |
August | 0.106710E+09 | 28246702.05 | 78463003.44 | 0.218731E+09 | 34421011.59 |
September | 0.161189E+09 | 83743175.85 | 77445616.35 | 0.302307E+09 | 62997869.59 |
October | 0.226308E+09 | 0.153000E+09 | 73308827.12 | 0.364151E+09 | 0.100947E+09 |
November | 0.263556E+09 | 0.200929E+09 | 62626973.79 | 0.380589E+09 | 0.151446E+09 |
December | 0.269901E+09 | 0.202600E+09 | 67301001.16 | 0.372189E+09 | 0.185845E+09 |
Annual Sum or Average | 0.209934E+10 | 0.121312E+10 | 0.886220E+09 | 0.335863E+10 | 0.118160E+10 |
Minimum of Months | 79470675.37 | 5042437.65 | 62626973.79 | 0.171913E+09 | 24460850.60 |
Maximum of Months | 0.269901E+09 | 0.202600E+09 | 84112693.66 | 0.380589E+09 | 0.185845E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.263516E+09 | 0.199641E+09 | 63875169.97 | 0.370666E+09 | 0.171110E+09 |
February | 0.220785E+09 | 0.155650E+09 | 65135039.89 | 0.315742E+09 | 0.139529E+09 |
March | 0.198659E+09 | 0.114546E+09 | 84112693.66 | 0.292752E+09 | 0.139494E+09 |
April | 0.130345E+09 | 48635019.57 | 81710029.33 | 0.213772E+09 | 87421269.70 |
May | 95183853.57 | 13322620.49 | 81861233.08 | 0.171913E+09 | 55680094.48 |
June | 79470675.37 | 5042437.65 | 74428237.72 | 0.173637E+09 | 28243843.23 |
July | 83711989.83 | 7760244.97 | 75951744.86 | 0.182178E+09 | 24460850.60 |
August | 0.106710E+09 | 28246702.05 | 78463003.44 | 0.218731E+09 | 34421011.59 |
September | 0.161189E+09 | 83743175.85 | 77445616.35 | 0.302307E+09 | 62997869.59 |
October | 0.226308E+09 | 0.153000E+09 | 73308827.12 | 0.364151E+09 | 0.100947E+09 |
November | 0.263556E+09 | 0.200929E+09 | 62626973.79 | 0.380589E+09 | 0.151446E+09 |
December | 0.269901E+09 | 0.202600E+09 | 67301001.16 | 0.372189E+09 | 0.185845E+09 |
Annual Sum or Average | 0.209934E+10 | 0.121312E+10 | 0.886220E+09 | 0.335863E+10 | 0.118160E+10 |
Minimum of Months | 79470675.37 | 5042437.65 | 62626973.79 | 0.171913E+09 | 24460850.60 |
Maximum of Months | 0.269901E+09 | 0.202600E+09 | 84112693.66 | 0.380589E+09 | 0.185845E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.315056E+09 | 0.238688E+09 | 76368182.54 | 0.444097E+09 | 0.202456E+09 |
February | 0.263967E+09 | 0.186093E+09 | 77874463.88 | 0.378286E+09 | 0.165174E+09 |
March | 0.237513E+09 | 0.136950E+09 | 0.100564E+09 | 0.350968E+09 | 0.165288E+09 |
April | 0.155839E+09 | 58147290.33 | 97691269.37 | 0.255691E+09 | 0.103928E+09 |
May | 0.113800E+09 | 15928322.61 | 97872046.28 | 0.204815E+09 | 66538094.40 |
June | 95013931.80 | 6028661.83 | 88985269.98 | 0.206048E+09 | 33872304.25 |
July | 0.100085E+09 | 9278030.96 | 90806751.97 | 0.216611E+09 | 29259032.67 |
August | 0.127581E+09 | 33771327.72 | 93809174.56 | 0.260538E+09 | 41085441.70 |
September | 0.192715E+09 | 0.100122E+09 | 92592802.02 | 0.360879E+09 | 74955605.71 |
October | 0.270571E+09 | 0.182924E+09 | 87646919.67 | 0.435503E+09 | 0.119771E+09 |
November | 0.315104E+09 | 0.240228E+09 | 74875858.16 | 0.455626E+09 | 0.179434E+09 |
December | 0.322689E+09 | 0.242225E+09 | 80464054.26 | 0.445698E+09 | 0.220076E+09 |
Annual Sum or Average | 0.250993E+10 | 0.145038E+10 | 0.105955E+10 | 0.401476E+10 | 0.140184E+10 |
Minimum of Months | 95013931.80 | 6028661.83 | 74875858.16 | 0.204815E+09 | 29259032.67 |
Maximum of Months | 0.322689E+09 | 0.242225E+09 | 0.100564E+09 | 0.455626E+09 | 0.220076E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.263516E+09 | 0.199641E+09 | 63875169.97 | 0.373413E+09 | 0.165339E+09 |
February | 0.220785E+09 | 0.155650E+09 | 65135039.89 | 0.318346E+09 | 0.134526E+09 |
March | 0.198659E+09 | 0.114546E+09 | 84112693.66 | 0.295693E+09 | 0.134132E+09 |
April | 0.130345E+09 | 48635019.57 | 81710029.33 | 0.215157E+09 | 83955393.20 |
May | 95183853.57 | 13322620.49 | 81861233.08 | 0.172223E+09 | 53035537.03 |
June | 79470675.37 | 5042437.65 | 74428237.72 | 0.173989E+09 | 26437246.82 |
July | 83711989.83 | 7760244.97 | 75951744.86 | 0.182164E+09 | 22679892.13 |
August | 0.106710E+09 | 28246702.05 | 78463003.44 | 0.218675E+09 | 32363413.92 |
September | 0.161189E+09 | 83743175.85 | 77445616.35 | 0.302253E+09 | 60616271.93 |
October | 0.226308E+09 | 0.153000E+09 | 73308827.12 | 0.364965E+09 | 98336125.20 |
November | 0.263556E+09 | 0.200929E+09 | 62626973.79 | 0.382690E+09 | 0.147361E+09 |
December | 0.269901E+09 | 0.202600E+09 | 67301001.16 | 0.374892E+09 | 0.180446E+09 |
Annual Sum or Average | 0.209934E+10 | 0.121312E+10 | 0.886220E+09 | 0.337446E+10 | 0.113923E+10 |
Minimum of Months | 79470675.37 | 5042437.65 | 62626973.79 | 0.172223E+09 | 22679892.13 |
Maximum of Months | 0.269901E+09 | 0.202600E+09 | 84112693.66 | 0.382690E+09 | 0.180446E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.263516E+09 | 0.199641E+09 | 63875169.97 | 0.373413E+09 | 0.165339E+09 |
February | 0.220785E+09 | 0.155650E+09 | 65135039.89 | 0.318346E+09 | 0.134526E+09 |
March | 0.198659E+09 | 0.114546E+09 | 84112693.66 | 0.295693E+09 | 0.134132E+09 |
April | 0.130345E+09 | 48635019.57 | 81710029.33 | 0.215157E+09 | 83955393.20 |
May | 95183853.57 | 13322620.49 | 81861233.08 | 0.172223E+09 | 53035537.03 |
June | 79470675.37 | 5042437.65 | 74428237.72 | 0.173989E+09 | 26437246.82 |
July | 83711989.83 | 7760244.97 | 75951744.86 | 0.182164E+09 | 22679892.13 |
August | 0.106710E+09 | 28246702.05 | 78463003.44 | 0.218675E+09 | 32363413.92 |
September | 0.161189E+09 | 83743175.85 | 77445616.35 | 0.302253E+09 | 60616271.93 |
October | 0.226308E+09 | 0.153000E+09 | 73308827.12 | 0.364965E+09 | 98336125.20 |
November | 0.263556E+09 | 0.200929E+09 | 62626973.79 | 0.382690E+09 | 0.147361E+09 |
December | 0.269901E+09 | 0.202600E+09 | 67301001.16 | 0.374892E+09 | 0.180446E+09 |
Annual Sum or Average | 0.209934E+10 | 0.121312E+10 | 0.886220E+09 | 0.337446E+10 | 0.113923E+10 |
Minimum of Months | 79470675.37 | 5042437.65 | 62626973.79 | 0.172223E+09 | 22679892.13 |
Maximum of Months | 0.269901E+09 | 0.202600E+09 | 84112693.66 | 0.382690E+09 | 0.180446E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.263516E+09 | 0.199641E+09 | 63875169.97 | 0.373413E+09 | 0.165339E+09 |
February | 0.220785E+09 | 0.155650E+09 | 65135039.89 | 0.318346E+09 | 0.134526E+09 |
March | 0.198659E+09 | 0.114546E+09 | 84112693.66 | 0.295693E+09 | 0.134132E+09 |
April | 0.130345E+09 | 48635019.57 | 81710029.33 | 0.215157E+09 | 83955393.20 |
May | 95183853.57 | 13322620.49 | 81861233.08 | 0.172223E+09 | 53035537.03 |
June | 79470675.37 | 5042437.65 | 74428237.72 | 0.173989E+09 | 26437246.82 |
July | 83711989.83 | 7760244.97 | 75951744.86 | 0.182164E+09 | 22679892.13 |
August | 0.106710E+09 | 28246702.05 | 78463003.44 | 0.218675E+09 | 32363413.92 |
September | 0.161189E+09 | 83743175.85 | 77445616.35 | 0.302253E+09 | 60616271.93 |
October | 0.226308E+09 | 0.153000E+09 | 73308827.12 | 0.364965E+09 | 98336125.20 |
November | 0.263556E+09 | 0.200929E+09 | 62626973.79 | 0.382690E+09 | 0.147361E+09 |
December | 0.269901E+09 | 0.202600E+09 | 67301001.16 | 0.374892E+09 | 0.180446E+09 |
Annual Sum or Average | 0.209934E+10 | 0.121312E+10 | 0.886220E+09 | 0.337446E+10 | 0.113923E+10 |
Minimum of Months | 79470675.37 | 5042437.65 | 62626973.79 | 0.172223E+09 | 22679892.13 |
Maximum of Months | 0.269901E+09 | 0.202600E+09 | 84112693.66 | 0.382690E+09 | 0.180446E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.263516E+09 | 0.199641E+09 | 63875169.97 | 0.373413E+09 | 0.165339E+09 |
February | 0.220785E+09 | 0.155650E+09 | 65135039.89 | 0.318346E+09 | 0.134526E+09 |
March | 0.198659E+09 | 0.114546E+09 | 84112693.66 | 0.295693E+09 | 0.134132E+09 |
April | 0.130345E+09 | 48635019.57 | 81710029.33 | 0.215157E+09 | 83955393.20 |
May | 95183853.57 | 13322620.49 | 81861233.08 | 0.172223E+09 | 53035537.03 |
June | 79470675.37 | 5042437.65 | 74428237.72 | 0.173989E+09 | 26437246.82 |
July | 83711989.83 | 7760244.97 | 75951744.86 | 0.182164E+09 | 22679892.13 |
August | 0.106710E+09 | 28246702.05 | 78463003.44 | 0.218675E+09 | 32363413.92 |
September | 0.161189E+09 | 83743175.85 | 77445616.35 | 0.302253E+09 | 60616271.93 |
October | 0.226308E+09 | 0.153000E+09 | 73308827.12 | 0.364965E+09 | 98336125.20 |
November | 0.263556E+09 | 0.200929E+09 | 62626973.79 | 0.382690E+09 | 0.147361E+09 |
December | 0.269901E+09 | 0.202600E+09 | 67301001.16 | 0.374892E+09 | 0.180446E+09 |
Annual Sum or Average | 0.209934E+10 | 0.121312E+10 | 0.886220E+09 | 0.337446E+10 | 0.113923E+10 |
Minimum of Months | 79470675.37 | 5042437.65 | 62626973.79 | 0.172223E+09 | 22679892.13 |
Maximum of Months | 0.269901E+09 | 0.202600E+09 | 84112693.66 | 0.382690E+09 | 0.180446E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.315056E+09 | 0.238688E+09 | 76368182.54 | 0.447247E+09 | 0.195702E+09 |
February | 0.263967E+09 | 0.186093E+09 | 77874463.88 | 0.381286E+09 | 0.159313E+09 |
March | 0.237513E+09 | 0.136950E+09 | 0.100564E+09 | 0.354354E+09 | 0.158995E+09 |
April | 0.155839E+09 | 58147290.33 | 97691269.37 | 0.257298E+09 | 99831286.16 |
May | 0.113800E+09 | 15928322.61 | 97872046.28 | 0.205196E+09 | 63383809.63 |
June | 95013931.80 | 6028661.83 | 88985269.98 | 0.206508E+09 | 31694989.56 |
July | 0.100085E+09 | 9278030.96 | 90806751.97 | 0.216618E+09 | 27123538.80 |
August | 0.127581E+09 | 33771327.72 | 93809174.56 | 0.260471E+09 | 38623522.99 |
September | 0.192715E+09 | 0.100122E+09 | 92592802.02 | 0.360785E+09 | 72134017.05 |
October | 0.270571E+09 | 0.182924E+09 | 87646919.67 | 0.436392E+09 | 0.116701E+09 |
November | 0.315104E+09 | 0.240228E+09 | 74875858.16 | 0.458017E+09 | 0.174645E+09 |
December | 0.322689E+09 | 0.242225E+09 | 80464054.26 | 0.448812E+09 | 0.213744E+09 |
Annual Sum or Average | 0.250993E+10 | 0.145038E+10 | 0.105955E+10 | 0.403298E+10 | 0.135189E+10 |
Minimum of Months | 95013931.80 | 6028661.83 | 74875858.16 | 0.205196E+09 | 27123538.80 |
Maximum of Months | 0.322689E+09 | 0.242225E+09 | 0.100564E+09 | 0.458017E+09 | 0.213744E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.315056E+09 | 0.238688E+09 | 76368182.54 | 0.447247E+09 | 0.195702E+09 |
February | 0.263967E+09 | 0.186093E+09 | 77874463.88 | 0.381286E+09 | 0.159313E+09 |
March | 0.237513E+09 | 0.136950E+09 | 0.100564E+09 | 0.354354E+09 | 0.158995E+09 |
April | 0.155839E+09 | 58147290.33 | 97691269.37 | 0.257298E+09 | 99831286.16 |
May | 0.113800E+09 | 15928322.61 | 97872046.28 | 0.205196E+09 | 63383809.63 |
June | 95013931.80 | 6028661.83 | 88985269.98 | 0.206508E+09 | 31694989.56 |
July | 0.100085E+09 | 9278030.96 | 90806751.97 | 0.216618E+09 | 27123538.80 |
August | 0.127581E+09 | 33771327.72 | 93809174.56 | 0.260471E+09 | 38623522.99 |
September | 0.192715E+09 | 0.100122E+09 | 92592802.02 | 0.360785E+09 | 72134017.05 |
October | 0.270571E+09 | 0.182924E+09 | 87646919.67 | 0.436392E+09 | 0.116701E+09 |
November | 0.315104E+09 | 0.240228E+09 | 74875858.16 | 0.458017E+09 | 0.174645E+09 |
December | 0.322689E+09 | 0.242225E+09 | 80464054.26 | 0.448812E+09 | 0.213744E+09 |
Annual Sum or Average | 0.250993E+10 | 0.145038E+10 | 0.105955E+10 | 0.403298E+10 | 0.135189E+10 |
Minimum of Months | 95013931.80 | 6028661.83 | 74875858.16 | 0.205196E+09 | 27123538.80 |
Maximum of Months | 0.322689E+09 | 0.242225E+09 | 0.100564E+09 | 0.458017E+09 | 0.213744E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.263516E+09 | 0.199641E+09 | 63875169.97 | 0.372739E+09 | 0.165145E+09 |
February | 0.220785E+09 | 0.155650E+09 | 65135039.89 | 0.317823E+09 | 0.134331E+09 |
March | 0.198659E+09 | 0.114546E+09 | 84112693.66 | 0.295225E+09 | 0.133737E+09 |
April | 0.130345E+09 | 48635019.57 | 81710029.33 | 0.215053E+09 | 83405001.89 |
May | 95183853.57 | 13322620.49 | 81861233.08 | 0.172655E+09 | 52318458.49 |
June | 79470675.37 | 5042437.65 | 74428237.72 | 0.175078E+09 | 25750371.66 |
July | 83711989.83 | 7760244.97 | 75951744.86 | 0.183059E+09 | 21985452.87 |
August | 0.106710E+09 | 28246702.05 | 78463003.44 | 0.219279E+09 | 31600780.42 |
September | 0.161189E+09 | 83743175.85 | 77445616.35 | 0.302303E+09 | 59832236.62 |
October | 0.226308E+09 | 0.153000E+09 | 73308827.12 | 0.364568E+09 | 97848533.21 |
November | 0.263556E+09 | 0.200929E+09 | 62626973.79 | 0.382206E+09 | 0.147093E+09 |
December | 0.269901E+09 | 0.202600E+09 | 67301001.16 | 0.374289E+09 | 0.180369E+09 |
Annual Sum or Average | 0.209934E+10 | 0.121312E+10 | 0.886220E+09 | 0.337427E+10 | 0.113342E+10 |
Minimum of Months | 79470675.37 | 5042437.65 | 62626973.79 | 0.172655E+09 | 21985452.87 |
Maximum of Months | 0.269901E+09 | 0.202600E+09 | 84112693.66 | 0.382206E+09 | 0.180369E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.263516E+09 | 0.199641E+09 | 63875169.97 | 0.372739E+09 | 0.165145E+09 |
February | 0.220785E+09 | 0.155650E+09 | 65135039.89 | 0.317823E+09 | 0.134331E+09 |
March | 0.198659E+09 | 0.114546E+09 | 84112693.66 | 0.295225E+09 | 0.133737E+09 |
April | 0.130345E+09 | 48635019.57 | 81710029.33 | 0.215053E+09 | 83405001.89 |
May | 95183853.57 | 13322620.49 | 81861233.08 | 0.172655E+09 | 52318458.49 |
June | 79470675.37 | 5042437.65 | 74428237.72 | 0.175078E+09 | 25750371.66 |
July | 83711989.83 | 7760244.97 | 75951744.86 | 0.183059E+09 | 21985452.87 |
August | 0.106710E+09 | 28246702.05 | 78463003.44 | 0.219279E+09 | 31600780.42 |
September | 0.161189E+09 | 83743175.85 | 77445616.35 | 0.302303E+09 | 59832236.62 |
October | 0.226308E+09 | 0.153000E+09 | 73308827.12 | 0.364568E+09 | 97848533.21 |
November | 0.263556E+09 | 0.200929E+09 | 62626973.79 | 0.382206E+09 | 0.147093E+09 |
December | 0.269901E+09 | 0.202600E+09 | 67301001.16 | 0.374289E+09 | 0.180369E+09 |
Annual Sum or Average | 0.209934E+10 | 0.121312E+10 | 0.886220E+09 | 0.337427E+10 | 0.113342E+10 |
Minimum of Months | 79470675.37 | 5042437.65 | 62626973.79 | 0.172655E+09 | 21985452.87 |
Maximum of Months | 0.269901E+09 | 0.202600E+09 | 84112693.66 | 0.382206E+09 | 0.180369E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.315056E+09 | 0.238688E+09 | 76368182.54 | 0.446588E+09 | 0.195408E+09 |
February | 0.263967E+09 | 0.186093E+09 | 77874463.88 | 0.380782E+09 | 0.159039E+09 |
March | 0.237513E+09 | 0.136950E+09 | 0.100564E+09 | 0.353926E+09 | 0.158495E+09 |
April | 0.155839E+09 | 58147290.33 | 97691269.37 | 0.257231E+09 | 99181164.50 |
May | 0.113800E+09 | 15928322.61 | 97872046.28 | 0.205704E+09 | 62557387.10 |
June | 95013931.80 | 6028661.83 | 88985269.98 | 0.207744E+09 | 30896582.51 |
July | 0.100085E+09 | 9278030.96 | 90806751.97 | 0.217656E+09 | 26311565.29 |
August | 0.127581E+09 | 33771327.72 | 93809174.56 | 0.261193E+09 | 37730339.57 |
September | 0.192715E+09 | 0.100122E+09 | 92592802.02 | 0.360907E+09 | 71211585.18 |
October | 0.270571E+09 | 0.182924E+09 | 87646919.67 | 0.436031E+09 | 0.116106E+09 |
November | 0.315104E+09 | 0.240228E+09 | 74875858.16 | 0.457573E+09 | 0.174282E+09 |
December | 0.322689E+09 | 0.242225E+09 | 80464054.26 | 0.448221E+09 | 0.213596E+09 |
Annual Sum or Average | 0.250993E+10 | 0.145038E+10 | 0.105955E+10 | 0.403356E+10 | 0.134482E+10 |
Minimum of Months | 95013931.80 | 6028661.83 | 74875858.16 | 0.205704E+09 | 26311565.29 |
Maximum of Months | 0.322689E+09 | 0.242225E+09 | 0.100564E+09 | 0.457573E+09 | 0.213596E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.263516E+09 | 0.199641E+09 | 63875169.97 | 0.373141E+09 | 0.164205E+09 |
February | 0.220785E+09 | 0.155650E+09 | 65135039.89 | 0.318253E+09 | 0.133466E+09 |
March | 0.198659E+09 | 0.114546E+09 | 84112693.66 | 0.295804E+09 | 0.132706E+09 |
April | 0.130345E+09 | 48635019.57 | 81710029.33 | 0.215399E+09 | 82843271.27 |
May | 95183853.57 | 13322620.49 | 81861233.08 | 0.172843E+09 | 52054250.38 |
June | 79470675.37 | 5042437.65 | 74428237.72 | 0.175246E+09 | 25595135.99 |
July | 83711989.83 | 7760244.97 | 75951744.86 | 0.183214E+09 | 21837544.49 |
August | 0.106710E+09 | 28246702.05 | 78463003.44 | 0.219404E+09 | 31448328.70 |
September | 0.161189E+09 | 83743175.85 | 77445616.35 | 0.302403E+09 | 59644508.75 |
October | 0.226308E+09 | 0.153000E+09 | 73308827.12 | 0.364758E+09 | 97497656.38 |
November | 0.263556E+09 | 0.200929E+09 | 62626973.79 | 0.382690E+09 | 0.146290E+09 |
December | 0.269901E+09 | 0.202600E+09 | 67301001.16 | 0.374635E+09 | 0.179625E+09 |
Annual Sum or Average | 0.209934E+10 | 0.121312E+10 | 0.886220E+09 | 0.337779E+10 | 0.112721E+10 |
Minimum of Months | 79470675.37 | 5042437.65 | 62626973.79 | 0.172843E+09 | 21837544.49 |
Maximum of Months | 0.269901E+09 | 0.202600E+09 | 84112693.66 | 0.382690E+09 | 0.179625E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.263516E+09 | 0.199641E+09 | 63875169.97 | 0.373141E+09 | 0.164205E+09 |
February | 0.220785E+09 | 0.155650E+09 | 65135039.89 | 0.318253E+09 | 0.133466E+09 |
March | 0.198659E+09 | 0.114546E+09 | 84112693.66 | 0.295804E+09 | 0.132706E+09 |
April | 0.130345E+09 | 48635019.57 | 81710029.33 | 0.215399E+09 | 82843271.27 |
May | 95183853.57 | 13322620.49 | 81861233.08 | 0.172843E+09 | 52054250.38 |
June | 79470675.37 | 5042437.65 | 74428237.72 | 0.175246E+09 | 25595135.99 |
July | 83711989.83 | 7760244.97 | 75951744.86 | 0.183214E+09 | 21837544.49 |
August | 0.106710E+09 | 28246702.05 | 78463003.44 | 0.219404E+09 | 31448328.70 |
September | 0.161189E+09 | 83743175.85 | 77445616.35 | 0.302403E+09 | 59644508.75 |
October | 0.226308E+09 | 0.153000E+09 | 73308827.12 | 0.364758E+09 | 97497656.38 |
November | 0.263556E+09 | 0.200929E+09 | 62626973.79 | 0.382690E+09 | 0.146290E+09 |
December | 0.269901E+09 | 0.202600E+09 | 67301001.16 | 0.374635E+09 | 0.179625E+09 |
Annual Sum or Average | 0.209934E+10 | 0.121312E+10 | 0.886220E+09 | 0.337779E+10 | 0.112721E+10 |
Minimum of Months | 79470675.37 | 5042437.65 | 62626973.79 | 0.172843E+09 | 21837544.49 |
Maximum of Months | 0.269901E+09 | 0.202600E+09 | 84112693.66 | 0.382690E+09 | 0.179625E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.315056E+09 | 0.238688E+09 | 76368182.54 | 0.447068E+09 | 0.194296E+09 |
February | 0.263967E+09 | 0.186093E+09 | 77874463.88 | 0.381296E+09 | 0.158018E+09 |
March | 0.237513E+09 | 0.136950E+09 | 0.100564E+09 | 0.354615E+09 | 0.157278E+09 |
April | 0.155839E+09 | 58147290.33 | 97691269.37 | 0.257645E+09 | 98518228.29 |
May | 0.113800E+09 | 15928322.61 | 97872046.28 | 0.205928E+09 | 62244497.39 |
June | 95013931.80 | 6028661.83 | 88985269.98 | 0.207945E+09 | 30711972.34 |
July | 0.100085E+09 | 9278030.96 | 90806751.97 | 0.217842E+09 | 26136286.10 |
August | 0.127581E+09 | 33771327.72 | 93809174.56 | 0.261344E+09 | 37549689.45 |
September | 0.192715E+09 | 0.100122E+09 | 92592802.02 | 0.361028E+09 | 70989440.88 |
October | 0.270571E+09 | 0.182924E+09 | 87646919.67 | 0.436260E+09 | 0.115691E+09 |
November | 0.315104E+09 | 0.240228E+09 | 74875858.16 | 0.458151E+09 | 0.173333E+09 |
December | 0.322689E+09 | 0.242225E+09 | 80464054.26 | 0.448634E+09 | 0.212714E+09 |
Annual Sum or Average | 0.250993E+10 | 0.145038E+10 | 0.105955E+10 | 0.403776E+10 | 0.133748E+10 |
Minimum of Months | 95013931.80 | 6028661.83 | 74875858.16 | 0.205928E+09 | 26136286.10 |
Maximum of Months | 0.322689E+09 | 0.242225E+09 | 0.100564E+09 | 0.458151E+09 | 0.212714E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.263516E+09 | 0.199641E+09 | 63875169.97 | 0.374142E+09 | 0.161506E+09 |
February | 0.220785E+09 | 0.155650E+09 | 65135039.89 | 0.319393E+09 | 0.130906E+09 |
March | 0.198659E+09 | 0.114546E+09 | 84112693.66 | 0.297214E+09 | 0.129780E+09 |
April | 0.130345E+09 | 48635019.57 | 81710029.33 | 0.216224E+09 | 81208714.30 |
May | 95183853.57 | 13322620.49 | 81861233.08 | 0.173141E+09 | 51387916.10 |
June | 79470675.37 | 5042437.65 | 74428237.72 | 0.175250E+09 | 25413954.77 |
July | 83711989.83 | 7760244.97 | 75951744.86 | 0.183114E+09 | 21764154.70 |
August | 0.106710E+09 | 28246702.05 | 78463003.44 | 0.219272E+09 | 31415569.24 |
September | 0.161189E+09 | 83743175.85 | 77445616.35 | 0.302359E+09 | 59530888.02 |
October | 0.226308E+09 | 0.153000E+09 | 73308827.12 | 0.365143E+09 | 96636081.16 |
November | 0.263556E+09 | 0.200929E+09 | 62626973.79 | 0.383848E+09 | 0.144163E+09 |
December | 0.269901E+09 | 0.202600E+09 | 67301001.16 | 0.375554E+09 | 0.177361E+09 |
Annual Sum or Average | 0.209934E+10 | 0.121312E+10 | 0.886220E+09 | 0.338465E+10 | 0.111107E+10 |
Minimum of Months | 79470675.37 | 5042437.65 | 62626973.79 | 0.173141E+09 | 21764154.70 |
Maximum of Months | 0.269901E+09 | 0.202600E+09 | 84112693.66 | 0.383848E+09 | 0.177361E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.263516E+09 | 0.199641E+09 | 63875169.97 | 0.374142E+09 | 0.161506E+09 |
February | 0.220785E+09 | 0.155650E+09 | 65135039.89 | 0.319393E+09 | 0.130906E+09 |
March | 0.198659E+09 | 0.114546E+09 | 84112693.66 | 0.297214E+09 | 0.129780E+09 |
April | 0.130345E+09 | 48635019.57 | 81710029.33 | 0.216224E+09 | 81208714.30 |
May | 95183853.57 | 13322620.49 | 81861233.08 | 0.173141E+09 | 51387916.10 |
June | 79470675.37 | 5042437.65 | 74428237.72 | 0.175250E+09 | 25413954.77 |
July | 83711989.83 | 7760244.97 | 75951744.86 | 0.183114E+09 | 21764154.70 |
August | 0.106710E+09 | 28246702.05 | 78463003.44 | 0.219272E+09 | 31415569.24 |
September | 0.161189E+09 | 83743175.85 | 77445616.35 | 0.302359E+09 | 59530888.02 |
October | 0.226308E+09 | 0.153000E+09 | 73308827.12 | 0.365143E+09 | 96636081.16 |
November | 0.263556E+09 | 0.200929E+09 | 62626973.79 | 0.383848E+09 | 0.144163E+09 |
December | 0.269901E+09 | 0.202600E+09 | 67301001.16 | 0.375554E+09 | 0.177361E+09 |
Annual Sum or Average | 0.209934E+10 | 0.121312E+10 | 0.886220E+09 | 0.338465E+10 | 0.111107E+10 |
Minimum of Months | 79470675.37 | 5042437.65 | 62626973.79 | 0.173141E+09 | 21764154.70 |
Maximum of Months | 0.269901E+09 | 0.202600E+09 | 84112693.66 | 0.383848E+09 | 0.177361E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.315056E+09 | 0.238688E+09 | 76368182.54 | 0.448265E+09 | 0.191108E+09 |
February | 0.263967E+09 | 0.186093E+09 | 77874463.88 | 0.382657E+09 | 0.155000E+09 |
March | 0.237513E+09 | 0.136950E+09 | 0.100564E+09 | 0.356297E+09 | 0.153829E+09 |
April | 0.155839E+09 | 58147290.33 | 97691269.37 | 0.258628E+09 | 96593595.51 |
May | 0.113800E+09 | 15928322.61 | 97872046.28 | 0.206283E+09 | 61461975.77 |
June | 95013931.80 | 6028661.83 | 88985269.98 | 0.207947E+09 | 30502079.24 |
July | 0.100085E+09 | 9278030.96 | 90806751.97 | 0.217721E+09 | 26054884.40 |
August | 0.127581E+09 | 33771327.72 | 93809174.56 | 0.261185E+09 | 37516330.45 |
September | 0.192715E+09 | 0.100122E+09 | 92592802.02 | 0.360974E+09 | 70861361.07 |
October | 0.270571E+09 | 0.182924E+09 | 87646919.67 | 0.436717E+09 | 0.114677E+09 |
November | 0.315104E+09 | 0.240228E+09 | 74875858.16 | 0.459527E+09 | 0.170824E+09 |
December | 0.322689E+09 | 0.242225E+09 | 80464054.26 | 0.449737E+09 | 0.210040E+09 |
Annual Sum or Average | 0.250993E+10 | 0.145038E+10 | 0.105955E+10 | 0.404594E+10 | 0.131847E+10 |
Minimum of Months | 95013931.80 | 6028661.83 | 74875858.16 | 0.206283E+09 | 26054884.40 |
Maximum of Months | 0.322689E+09 | 0.242225E+09 | 0.100564E+09 | 0.459527E+09 | 0.210040E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.263516E+09 | 0.199641E+09 | 63875169.97 | 0.376515E+09 | 0.152197E+09 |
February | 0.220785E+09 | 0.155650E+09 | 65135039.89 | 0.321938E+09 | 0.122163E+09 |
March | 0.198659E+09 | 0.114546E+09 | 84112693.66 | 0.299821E+09 | 0.120102E+09 |
April | 0.130345E+09 | 48635019.57 | 81710029.33 | 0.217169E+09 | 75479287.45 |
May | 95183853.57 | 13322620.49 | 81861233.08 | 0.172722E+09 | 48780066.62 |
June | 79470675.37 | 5042437.65 | 74428237.72 | 0.173388E+09 | 24841108.32 |
July | 83711989.83 | 7760244.97 | 75951744.86 | 0.180641E+09 | 21936349.58 |
August | 0.106710E+09 | 28246702.05 | 78463003.44 | 0.216848E+09 | 31819303.53 |
September | 0.161189E+09 | 83743175.85 | 77445616.35 | 0.300604E+09 | 59702471.93 |
October | 0.226308E+09 | 0.153000E+09 | 73308827.12 | 0.365319E+09 | 93771559.50 |
November | 0.263556E+09 | 0.200929E+09 | 62626973.79 | 0.385817E+09 | 0.137556E+09 |
December | 0.269901E+09 | 0.202600E+09 | 67301001.16 | 0.377833E+09 | 0.169183E+09 |
Annual Sum or Average | 0.209934E+10 | 0.121312E+10 | 0.886220E+09 | 0.338861E+10 | 0.105753E+10 |
Minimum of Months | 79470675.37 | 5042437.65 | 62626973.79 | 0.172722E+09 | 21936349.58 |
Maximum of Months | 0.269901E+09 | 0.202600E+09 | 84112693.66 | 0.385817E+09 | 0.169183E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.263516E+09 | 0.199641E+09 | 63875169.97 | 0.376515E+09 | 0.152197E+09 |
February | 0.220785E+09 | 0.155650E+09 | 65135039.89 | 0.321938E+09 | 0.122163E+09 |
March | 0.198659E+09 | 0.114546E+09 | 84112693.66 | 0.299821E+09 | 0.120102E+09 |
April | 0.130345E+09 | 48635019.57 | 81710029.33 | 0.217169E+09 | 75479287.45 |
May | 95183853.57 | 13322620.49 | 81861233.08 | 0.172722E+09 | 48780066.62 |
June | 79470675.37 | 5042437.65 | 74428237.72 | 0.173388E+09 | 24841108.32 |
July | 83711989.83 | 7760244.97 | 75951744.86 | 0.180641E+09 | 21936349.58 |
August | 0.106710E+09 | 28246702.05 | 78463003.44 | 0.216848E+09 | 31819303.53 |
September | 0.161189E+09 | 83743175.85 | 77445616.35 | 0.300604E+09 | 59702471.93 |
October | 0.226308E+09 | 0.153000E+09 | 73308827.12 | 0.365319E+09 | 93771559.50 |
November | 0.263556E+09 | 0.200929E+09 | 62626973.79 | 0.385817E+09 | 0.137556E+09 |
December | 0.269901E+09 | 0.202600E+09 | 67301001.16 | 0.377833E+09 | 0.169183E+09 |
Annual Sum or Average | 0.209934E+10 | 0.121312E+10 | 0.886220E+09 | 0.338861E+10 | 0.105753E+10 |
Minimum of Months | 79470675.37 | 5042437.65 | 62626973.79 | 0.172722E+09 | 21936349.58 |
Maximum of Months | 0.269901E+09 | 0.202600E+09 | 84112693.66 | 0.385817E+09 | 0.169183E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.315056E+09 | 0.238688E+09 | 76368182.54 | 0.451119E+09 | 0.180119E+09 |
February | 0.263967E+09 | 0.186093E+09 | 77874463.88 | 0.385707E+09 | 0.144697E+09 |
March | 0.237513E+09 | 0.136950E+09 | 0.100564E+09 | 0.359425E+09 | 0.142433E+09 |
April | 0.155839E+09 | 58147290.33 | 97691269.37 | 0.259755E+09 | 89846009.67 |
May | 0.113800E+09 | 15928322.61 | 97872046.28 | 0.205774E+09 | 58391838.32 |
June | 95013931.80 | 6028661.83 | 88985269.98 | 0.205718E+09 | 29835396.77 |
July | 0.100085E+09 | 9278030.96 | 90806751.97 | 0.214762E+09 | 26272841.47 |
August | 0.127581E+09 | 33771327.72 | 93809174.56 | 0.258282E+09 | 38011222.30 |
September | 0.192715E+09 | 0.100122E+09 | 92592802.02 | 0.358858E+09 | 71072462.91 |
October | 0.270571E+09 | 0.182924E+09 | 87646919.67 | 0.436916E+09 | 0.111308E+09 |
November | 0.315104E+09 | 0.240228E+09 | 74875858.16 | 0.461874E+09 | 0.163029E+09 |
December | 0.322689E+09 | 0.242225E+09 | 80464054.26 | 0.452478E+09 | 0.200381E+09 |
Annual Sum or Average | 0.250993E+10 | 0.145038E+10 | 0.105955E+10 | 0.405067E+10 | 0.125540E+10 |
Minimum of Months | 95013931.80 | 6028661.83 | 74875858.16 | 0.205718E+09 | 26272841.47 |
Maximum of Months | 0.322689E+09 | 0.242225E+09 | 0.100564E+09 | 0.461874E+09 | 0.200381E+09 |
Report: WindowZoneSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 890.14 | 405.29 | 630.09 | 477.36 | 152.73 | 0.00 | 0.00 |
February | 841.30 | 363.47 | 584.48 | 412.05 | 172.43 | 0.00 | 0.00 |
March | 706.05 | 326.59 | 475.01 | 273.89 | 201.12 | 0.00 | 0.00 |
April | 532.19 | 207.55 | 322.06 | 120.17 | 201.89 | 0.00 | 0.00 |
May | 413.69 | 123.55 | 227.59 | 31.86 | 195.74 | 0.00 | 0.00 |
June | 434.03 | 61.69 | 196.36 | 12.46 | 183.90 | 0.00 | 0.00 |
July | 440.72 | 50.25 | 200.16 | 18.56 | 181.61 | 0.00 | 0.00 |
August | 526.45 | 73.62 | 255.15 | 67.54 | 187.61 | 0.00 | 0.00 |
September | 747.05 | 144.78 | 398.26 | 206.91 | 191.35 | 0.00 | 0.00 |
October | 872.88 | 233.64 | 541.12 | 365.84 | 175.29 | 0.00 | 0.00 |
November | 943.60 | 368.73 | 651.19 | 496.46 | 154.74 | 0.00 | 0.00 |
December | 893.71 | 440.61 | 645.36 | 484.44 | 160.92 | 0.00 | 0.00 |
Annual Sum or Average | 685.80 | 232.66 | 426.33 | 246.36 | 179.97 | 0.00 | 0.00 |
Minimum of Months | 413.69 | 50.25 | 196.36 | 12.46 | 152.73 | 0.00 | 0.00 |
Maximum of Months | 943.60 | 440.61 | 651.19 | 496.46 | 201.89 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 439.20 | 217.31 | 315.05 | 238.68 | 76.37 | 0.00 | 0.00 |
February | 414.37 | 194.78 | 292.24 | 206.02 | 86.22 | 0.00 | 0.00 |
March | 346.89 | 173.84 | 237.51 | 136.95 | 100.56 | 0.00 | 0.00 |
April | 263.72 | 107.14 | 161.03 | 60.08 | 100.94 | 0.00 | 0.00 |
May | 206.71 | 62.71 | 113.80 | 15.93 | 97.87 | 0.00 | 0.00 |
June | 218.29 | 31.31 | 98.18 | 6.23 | 91.95 | 0.00 | 0.00 |
July | 221.86 | 25.31 | 100.08 | 9.28 | 90.80 | 0.00 | 0.00 |
August | 264.57 | 36.79 | 127.58 | 33.77 | 93.81 | 0.00 | 0.00 |
September | 374.11 | 71.79 | 199.13 | 103.46 | 95.68 | 0.00 | 0.00 |
October | 435.42 | 117.88 | 270.56 | 182.92 | 87.64 | 0.00 | 0.00 |
November | 467.42 | 192.11 | 325.60 | 248.23 | 77.37 | 0.00 | 0.00 |
December | 441.18 | 234.08 | 322.68 | 242.22 | 80.46 | 0.00 | 0.00 |
Annual Sum or Average | 340.66 | 121.72 | 213.17 | 123.18 | 89.99 | 0.00 | 0.00 |
Minimum of Months | 206.71 | 25.31 | 98.18 | 6.23 | 76.37 | 0.00 | 0.00 |
Maximum of Months | 467.42 | 234.08 | 325.60 | 248.23 | 100.94 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 440.05 | 210.19 | 314.40 | 238.19 | 76.21 | 0.00 | 0.00 |
February | 414.90 | 189.74 | 291.64 | 205.60 | 86.04 | 0.00 | 0.00 |
March | 347.15 | 171.04 | 237.02 | 136.66 | 100.35 | 0.00 | 0.00 |
April | 262.58 | 109.78 | 160.70 | 59.96 | 100.74 | 0.00 | 0.00 |
May | 204.41 | 67.28 | 113.56 | 15.90 | 97.67 | 0.00 | 0.00 |
June | 213.17 | 35.18 | 97.98 | 6.22 | 91.76 | 0.00 | 0.00 |
July | 216.71 | 29.45 | 99.88 | 9.26 | 90.62 | 0.00 | 0.00 |
August | 260.42 | 41.35 | 127.31 | 33.70 | 93.61 | 0.00 | 0.00 |
September | 372.27 | 78.05 | 198.72 | 103.24 | 95.48 | 0.00 | 0.00 |
October | 433.99 | 121.48 | 270.01 | 182.54 | 87.46 | 0.00 | 0.00 |
November | 467.55 | 190.12 | 324.93 | 247.72 | 77.21 | 0.00 | 0.00 |
December | 441.92 | 227.26 | 322.02 | 241.72 | 80.30 | 0.00 | 0.00 |
Annual Sum or Average | 339.09 | 122.24 | 212.73 | 122.93 | 89.80 | 0.00 | 0.00 |
Minimum of Months | 204.41 | 29.45 | 97.98 | 6.22 | 76.21 | 0.00 | 0.00 |
Maximum of Months | 467.55 | 227.26 | 324.93 | 247.72 | 100.74 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 441.22 | 206.64 | 314.40 | 238.19 | 76.21 | 0.00 | 0.00 |
February | 415.97 | 186.74 | 291.64 | 205.60 | 86.04 | 0.00 | 0.00 |
March | 348.12 | 168.73 | 237.02 | 136.66 | 100.35 | 0.00 | 0.00 |
April | 262.81 | 109.19 | 160.70 | 59.96 | 100.74 | 0.00 | 0.00 |
May | 204.36 | 67.45 | 113.56 | 15.90 | 97.67 | 0.00 | 0.00 |
June | 212.93 | 35.64 | 97.98 | 6.22 | 91.76 | 0.00 | 0.00 |
July | 216.45 | 29.93 | 99.88 | 9.26 | 90.62 | 0.00 | 0.00 |
August | 260.22 | 41.84 | 127.31 | 33.70 | 93.61 | 0.00 | 0.00 |
September | 372.18 | 78.45 | 198.72 | 103.24 | 95.48 | 0.00 | 0.00 |
October | 434.06 | 121.24 | 270.01 | 182.54 | 87.46 | 0.00 | 0.00 |
November | 468.30 | 188.29 | 324.93 | 247.72 | 77.21 | 0.00 | 0.00 |
December | 443.00 | 223.99 | 322.02 | 241.72 | 80.30 | 0.00 | 0.00 |
Annual Sum or Average | 339.46 | 121.18 | 212.73 | 122.93 | 89.80 | 0.00 | 0.00 |
Minimum of Months | 204.36 | 29.93 | 97.98 | 6.22 | 76.21 | 0.00 | 0.00 |
Maximum of Months | 468.30 | 223.99 | 324.93 | 247.72 | 100.74 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 442.59 | 203.36 | 314.40 | 238.19 | 76.21 | 0.00 | 0.00 |
February | 417.40 | 183.63 | 291.64 | 205.60 | 86.04 | 0.00 | 0.00 |
March | 349.64 | 165.87 | 237.02 | 136.66 | 100.35 | 0.00 | 0.00 |
April | 263.59 | 107.55 | 160.70 | 59.96 | 100.74 | 0.00 | 0.00 |
May | 204.84 | 66.42 | 113.56 | 15.90 | 97.67 | 0.00 | 0.00 |
June | 213.47 | 34.86 | 97.98 | 6.22 | 91.76 | 0.00 | 0.00 |
July | 216.91 | 29.19 | 99.88 | 9.26 | 90.62 | 0.00 | 0.00 |
August | 260.60 | 41.04 | 127.31 | 33.70 | 93.61 | 0.00 | 0.00 |
September | 372.49 | 77.53 | 198.72 | 103.24 | 95.48 | 0.00 | 0.00 |
October | 434.51 | 120.10 | 270.01 | 182.54 | 87.46 | 0.00 | 0.00 |
November | 469.45 | 186.08 | 324.93 | 247.72 | 77.21 | 0.00 | 0.00 |
December | 444.32 | 220.94 | 322.02 | 241.72 | 80.30 | 0.00 | 0.00 |
Annual Sum or Average | 340.31 | 119.39 | 212.73 | 122.93 | 89.80 | 0.00 | 0.00 |
Minimum of Months | 204.84 | 29.19 | 97.98 | 6.22 | 76.21 | 0.00 | 0.00 |
Maximum of Months | 469.45 | 220.94 | 324.93 | 247.72 | 100.74 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 891.63 | 393.06 | 628.80 | 476.38 | 152.42 | 0.00 | 0.00 |
February | 841.58 | 354.14 | 583.28 | 411.20 | 172.08 | 0.00 | 0.00 |
March | 706.20 | 319.04 | 474.04 | 273.33 | 200.71 | 0.00 | 0.00 |
April | 530.56 | 206.59 | 321.40 | 119.92 | 201.47 | 0.00 | 0.00 |
May | 410.42 | 126.53 | 227.13 | 31.79 | 195.34 | 0.00 | 0.00 |
June | 427.84 | 65.25 | 195.95 | 12.43 | 183.52 | 0.00 | 0.00 |
July | 433.80 | 54.12 | 199.75 | 18.52 | 181.24 | 0.00 | 0.00 |
August | 521.07 | 77.17 | 254.63 | 67.40 | 187.23 | 0.00 | 0.00 |
September | 744.82 | 149.20 | 397.45 | 206.49 | 190.96 | 0.00 | 0.00 |
October | 870.91 | 234.00 | 540.01 | 365.09 | 174.93 | 0.00 | 0.00 |
November | 943.98 | 362.16 | 649.86 | 495.44 | 154.42 | 0.00 | 0.00 |
December | 895.01 | 429.09 | 644.03 | 483.44 | 160.59 | 0.00 | 0.00 |
Annual Sum or Average | 683.78 | 230.23 | 425.46 | 245.85 | 179.60 | 0.00 | 0.00 |
Minimum of Months | 410.42 | 54.12 | 195.95 | 12.43 | 152.42 | 0.00 | 0.00 |
Maximum of Months | 943.98 | 429.09 | 649.86 | 495.44 | 201.47 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 445.07 | 196.27 | 314.40 | 238.19 | 76.21 | 0.00 | 0.00 |
February | 420.15 | 176.79 | 291.64 | 205.60 | 86.04 | 0.00 | 0.00 |
March | 352.59 | 159.04 | 237.02 | 136.66 | 100.35 | 0.00 | 0.00 |
April | 265.18 | 102.62 | 160.70 | 59.96 | 100.74 | 0.00 | 0.00 |
May | 205.72 | 62.42 | 113.56 | 15.90 | 97.67 | 0.00 | 0.00 |
June | 215.24 | 31.79 | 97.98 | 6.22 | 91.76 | 0.00 | 0.00 |
July | 217.96 | 26.24 | 99.88 | 9.26 | 90.62 | 0.00 | 0.00 |
August | 261.26 | 37.68 | 127.31 | 33.70 | 93.61 | 0.00 | 0.00 |
September | 372.50 | 73.64 | 198.72 | 103.24 | 95.48 | 0.00 | 0.00 |
October | 435.02 | 116.41 | 270.01 | 182.54 | 87.46 | 0.00 | 0.00 |
November | 471.44 | 180.74 | 324.93 | 247.72 | 77.21 | 0.00 | 0.00 |
December | 446.83 | 214.43 | 322.02 | 241.72 | 80.30 | 0.00 | 0.00 |
Annual Sum or Average | 341.90 | 114.52 | 212.73 | 122.93 | 89.80 | 0.00 | 0.00 |
Minimum of Months | 205.72 | 26.24 | 97.98 | 6.22 | 76.21 | 0.00 | 0.00 |
Maximum of Months | 471.44 | 214.43 | 324.93 | 247.72 | 100.74 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 445.55 | 195.16 | 314.40 | 238.19 | 76.21 | 0.00 | 0.00 |
February | 420.72 | 175.66 | 291.64 | 205.60 | 86.04 | 0.00 | 0.00 |
March | 353.28 | 157.81 | 237.02 | 136.66 | 100.35 | 0.00 | 0.00 |
April | 265.60 | 101.93 | 160.70 | 59.96 | 100.74 | 0.00 | 0.00 |
May | 205.95 | 62.11 | 113.56 | 15.90 | 97.67 | 0.00 | 0.00 |
June | 215.45 | 31.60 | 97.98 | 6.22 | 91.76 | 0.00 | 0.00 |
July | 218.14 | 26.06 | 99.88 | 9.26 | 90.62 | 0.00 | 0.00 |
August | 261.41 | 37.50 | 127.31 | 33.70 | 93.61 | 0.00 | 0.00 |
September | 372.62 | 73.41 | 198.72 | 103.24 | 95.48 | 0.00 | 0.00 |
October | 435.25 | 116.00 | 270.01 | 182.54 | 87.46 | 0.00 | 0.00 |
November | 472.04 | 179.75 | 324.93 | 247.72 | 77.21 | 0.00 | 0.00 |
December | 447.25 | 213.55 | 322.02 | 241.72 | 80.30 | 0.00 | 0.00 |
Annual Sum or Average | 342.25 | 113.90 | 212.73 | 122.93 | 89.80 | 0.00 | 0.00 |
Minimum of Months | 205.95 | 26.06 | 97.98 | 6.22 | 76.21 | 0.00 | 0.00 |
Maximum of Months | 472.04 | 213.55 | 324.93 | 247.72 | 100.74 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 446.74 | 191.95 | 314.40 | 238.19 | 76.21 | 0.00 | 0.00 |
February | 422.22 | 172.29 | 291.64 | 205.60 | 86.04 | 0.00 | 0.00 |
March | 354.96 | 154.34 | 237.02 | 136.66 | 100.35 | 0.00 | 0.00 |
April | 266.62 | 99.93 | 160.70 | 59.96 | 100.74 | 0.00 | 0.00 |
May | 206.30 | 61.32 | 113.56 | 15.90 | 97.67 | 0.00 | 0.00 |
June | 215.45 | 31.38 | 97.98 | 6.22 | 91.76 | 0.00 | 0.00 |
July | 218.02 | 25.98 | 99.88 | 9.26 | 90.62 | 0.00 | 0.00 |
August | 261.25 | 37.47 | 127.31 | 33.70 | 93.61 | 0.00 | 0.00 |
September | 372.57 | 73.27 | 198.72 | 103.24 | 95.48 | 0.00 | 0.00 |
October | 435.71 | 114.98 | 270.01 | 182.54 | 87.46 | 0.00 | 0.00 |
November | 473.47 | 177.14 | 324.93 | 247.72 | 77.21 | 0.00 | 0.00 |
December | 448.34 | 210.86 | 322.02 | 241.72 | 80.30 | 0.00 | 0.00 |
Annual Sum or Average | 342.95 | 112.27 | 212.73 | 122.93 | 89.80 | 0.00 | 0.00 |
Minimum of Months | 206.30 | 25.98 | 97.98 | 6.22 | 76.21 | 0.00 | 0.00 |
Maximum of Months | 473.47 | 210.86 | 324.93 | 247.72 | 100.74 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 449.58 | 180.90 | 314.40 | 238.19 | 76.21 | 0.00 | 0.00 |
February | 425.59 | 160.81 | 291.64 | 205.60 | 86.04 | 0.00 | 0.00 |
March | 358.07 | 142.86 | 237.02 | 136.66 | 100.35 | 0.00 | 0.00 |
April | 267.78 | 92.90 | 160.70 | 59.96 | 100.74 | 0.00 | 0.00 |
May | 205.80 | 58.23 | 113.56 | 15.90 | 97.67 | 0.00 | 0.00 |
June | 213.15 | 30.68 | 97.98 | 6.22 | 91.76 | 0.00 | 0.00 |
July | 215.07 | 26.19 | 99.88 | 9.26 | 90.62 | 0.00 | 0.00 |
August | 258.35 | 37.95 | 127.31 | 33.70 | 93.61 | 0.00 | 0.00 |
September | 370.40 | 73.49 | 198.72 | 103.24 | 95.48 | 0.00 | 0.00 |
October | 435.91 | 111.58 | 270.01 | 182.54 | 87.46 | 0.00 | 0.00 |
November | 475.89 | 169.04 | 324.93 | 247.72 | 77.21 | 0.00 | 0.00 |
December | 451.07 | 201.15 | 322.02 | 241.72 | 80.30 | 0.00 | 0.00 |
Annual Sum or Average | 343.35 | 106.88 | 212.73 | 122.93 | 89.80 | 0.00 | 0.00 |
Minimum of Months | 205.80 | 26.19 | 97.98 | 6.22 | 76.21 | 0.00 | 0.00 |
Maximum of Months | 475.89 | 201.15 | 324.93 | 247.72 | 100.74 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.238414E+10 | 0.108552E+10 | 0.168764E+10 | 0.127856E+10 | 0.409076E+09 | 0.00 | 0.00 |
February | 0.203526E+10 | 0.879305E+09 | 0.141398E+10 | 0.996831E+09 | 0.417145E+09 | 0.00 | 0.00 |
March | 0.189109E+10 | 0.874742E+09 | 0.127227E+10 | 0.733588E+09 | 0.538684E+09 | 0.00 | 0.00 |
April | 0.137944E+10 | 0.537980E+09 | 0.834770E+09 | 0.311474E+09 | 0.523296E+09 | 0.00 | 0.00 |
May | 0.110802E+10 | 0.330908E+09 | 0.609587E+09 | 85322163.70 | 0.524265E+09 | 0.00 | 0.00 |
June | 0.112501E+10 | 0.159906E+09 | 0.508955E+09 | 32293323.27 | 0.476661E+09 | 0.00 | 0.00 |
July | 0.118043E+10 | 0.134595E+09 | 0.536117E+09 | 49698998.17 | 0.486418E+09 | 0.00 | 0.00 |
August | 0.141005E+10 | 0.197179E+09 | 0.683402E+09 | 0.180901E+09 | 0.502501E+09 | 0.00 | 0.00 |
September | 0.193635E+10 | 0.375281E+09 | 0.103230E+10 | 0.536317E+09 | 0.495986E+09 | 0.00 | 0.00 |
October | 0.233793E+10 | 0.625786E+09 | 0.144935E+10 | 0.979857E+09 | 0.469492E+09 | 0.00 | 0.00 |
November | 0.244581E+10 | 0.955744E+09 | 0.168790E+10 | 0.128681E+10 | 0.401082E+09 | 0.00 | 0.00 |
December | 0.239372E+10 | 0.118014E+10 | 0.172853E+10 | 0.129751E+10 | 0.431016E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.216273E+11 | 0.733709E+10 | 0.134448E+11 | 0.776917E+10 | 0.567562E+10 | 0.00 | 0.00 |
Minimum of Months | 0.110802E+10 | 0.134595E+09 | 0.508955E+09 | 32293323.27 | 0.401082E+09 | 0.00 | 0.00 |
Maximum of Months | 0.244581E+10 | 0.118014E+10 | 0.172853E+10 | 0.129751E+10 | 0.538684E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.117635E+10 | 0.582037E+09 | 0.843820E+09 | 0.639281E+09 | 0.204538E+09 | 0.00 | 0.00 |
February | 0.100244E+10 | 0.471202E+09 | 0.706988E+09 | 0.498416E+09 | 0.208572E+09 | 0.00 | 0.00 |
March | 0.929121E+09 | 0.465605E+09 | 0.636136E+09 | 0.366794E+09 | 0.269342E+09 | 0.00 | 0.00 |
April | 0.683555E+09 | 0.277714E+09 | 0.417385E+09 | 0.155737E+09 | 0.261648E+09 | 0.00 | 0.00 |
May | 0.553657E+09 | 0.167950E+09 | 0.304793E+09 | 42661081.85 | 0.262132E+09 | 0.00 | 0.00 |
June | 0.565819E+09 | 81155824.38 | 0.254477E+09 | 16146661.64 | 0.238331E+09 | 0.00 | 0.00 |
July | 0.594234E+09 | 67780571.11 | 0.268059E+09 | 24849499.09 | 0.243209E+09 | 0.00 | 0.00 |
August | 0.708616E+09 | 98544223.48 | 0.341701E+09 | 90450288.55 | 0.251251E+09 | 0.00 | 0.00 |
September | 0.969706E+09 | 0.186089E+09 | 0.516151E+09 | 0.268159E+09 | 0.247993E+09 | 0.00 | 0.00 |
October | 0.116623E+10 | 0.315727E+09 | 0.724674E+09 | 0.489928E+09 | 0.234746E+09 | 0.00 | 0.00 |
November | 0.121156E+10 | 0.497958E+09 | 0.843948E+09 | 0.643407E+09 | 0.200541E+09 | 0.00 | 0.00 |
December | 0.118165E+10 | 0.626949E+09 | 0.864264E+09 | 0.648756E+09 | 0.215508E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.107429E+11 | 0.383871E+10 | 0.672240E+10 | 0.388458E+10 | 0.283781E+10 | 0.00 | 0.00 |
Minimum of Months | 0.553657E+09 | 67780571.11 | 0.254477E+09 | 16146661.64 | 0.200541E+09 | 0.00 | 0.00 |
Maximum of Months | 0.121156E+10 | 0.626949E+09 | 0.864264E+09 | 0.648756E+09 | 0.269342E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.117862E+10 | 0.562965E+09 | 0.842088E+09 | 0.637970E+09 | 0.204119E+09 | 0.00 | 0.00 |
February | 0.100372E+10 | 0.459011E+09 | 0.705538E+09 | 0.497393E+09 | 0.208145E+09 | 0.00 | 0.00 |
March | 0.929802E+09 | 0.458116E+09 | 0.634831E+09 | 0.366042E+09 | 0.268789E+09 | 0.00 | 0.00 |
April | 0.680598E+09 | 0.284557E+09 | 0.416529E+09 | 0.155417E+09 | 0.261111E+09 | 0.00 | 0.00 |
May | 0.547499E+09 | 0.180213E+09 | 0.304168E+09 | 42573563.60 | 0.261595E+09 | 0.00 | 0.00 |
June | 0.552536E+09 | 91188040.20 | 0.253955E+09 | 16113537.12 | 0.237842E+09 | 0.00 | 0.00 |
July | 0.580431E+09 | 78890135.20 | 0.267509E+09 | 24798520.89 | 0.242710E+09 | 0.00 | 0.00 |
August | 0.697509E+09 | 0.110764E+09 | 0.341000E+09 | 90264731.81 | 0.250735E+09 | 0.00 | 0.00 |
September | 0.964913E+09 | 0.202317E+09 | 0.515092E+09 | 0.267608E+09 | 0.247484E+09 | 0.00 | 0.00 |
October | 0.116239E+10 | 0.325368E+09 | 0.723188E+09 | 0.488923E+09 | 0.234265E+09 | 0.00 | 0.00 |
November | 0.121190E+10 | 0.492790E+09 | 0.842216E+09 | 0.642087E+09 | 0.200130E+09 | 0.00 | 0.00 |
December | 0.118364E+10 | 0.608681E+09 | 0.862491E+09 | 0.647425E+09 | 0.215066E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.106936E+11 | 0.385486E+10 | 0.670861E+10 | 0.387662E+10 | 0.283199E+10 | 0.00 | 0.00 |
Minimum of Months | 0.547499E+09 | 78890135.20 | 0.253955E+09 | 16113537.12 | 0.200130E+09 | 0.00 | 0.00 |
Maximum of Months | 0.121190E+10 | 0.608681E+09 | 0.862491E+09 | 0.647425E+09 | 0.268789E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.118176E+10 | 0.553453E+09 | 0.842088E+09 | 0.637970E+09 | 0.204119E+09 | 0.00 | 0.00 |
February | 0.100632E+10 | 0.451752E+09 | 0.705538E+09 | 0.497393E+09 | 0.208145E+09 | 0.00 | 0.00 |
March | 0.932398E+09 | 0.451926E+09 | 0.634831E+09 | 0.366042E+09 | 0.268789E+09 | 0.00 | 0.00 |
April | 0.681211E+09 | 0.283008E+09 | 0.416529E+09 | 0.155417E+09 | 0.261111E+09 | 0.00 | 0.00 |
May | 0.547349E+09 | 0.180666E+09 | 0.304168E+09 | 42573563.60 | 0.261595E+09 | 0.00 | 0.00 |
June | 0.551907E+09 | 92383342.69 | 0.253955E+09 | 16113537.12 | 0.237842E+09 | 0.00 | 0.00 |
July | 0.579727E+09 | 80151564.39 | 0.267509E+09 | 24798520.89 | 0.242710E+09 | 0.00 | 0.00 |
August | 0.696970E+09 | 0.112072E+09 | 0.341000E+09 | 90264731.81 | 0.250735E+09 | 0.00 | 0.00 |
September | 0.964695E+09 | 0.203334E+09 | 0.515092E+09 | 0.267608E+09 | 0.247484E+09 | 0.00 | 0.00 |
October | 0.116260E+10 | 0.324724E+09 | 0.723188E+09 | 0.488923E+09 | 0.234265E+09 | 0.00 | 0.00 |
November | 0.121384E+10 | 0.488044E+09 | 0.842216E+09 | 0.642087E+09 | 0.200130E+09 | 0.00 | 0.00 |
December | 0.118653E+10 | 0.599933E+09 | 0.862491E+09 | 0.647425E+09 | 0.215066E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.107053E+11 | 0.382145E+10 | 0.670861E+10 | 0.387662E+10 | 0.283199E+10 | 0.00 | 0.00 |
Minimum of Months | 0.547349E+09 | 80151564.39 | 0.253955E+09 | 16113537.12 | 0.200130E+09 | 0.00 | 0.00 |
Maximum of Months | 0.121384E+10 | 0.599933E+09 | 0.862491E+09 | 0.647425E+09 | 0.268789E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.118543E+10 | 0.544676E+09 | 0.842088E+09 | 0.637970E+09 | 0.204119E+09 | 0.00 | 0.00 |
February | 0.100977E+10 | 0.444232E+09 | 0.705538E+09 | 0.497393E+09 | 0.208145E+09 | 0.00 | 0.00 |
March | 0.936470E+09 | 0.444275E+09 | 0.634831E+09 | 0.366042E+09 | 0.268789E+09 | 0.00 | 0.00 |
April | 0.683235E+09 | 0.278770E+09 | 0.416529E+09 | 0.155417E+09 | 0.261111E+09 | 0.00 | 0.00 |
May | 0.548640E+09 | 0.177896E+09 | 0.304168E+09 | 42573563.60 | 0.261595E+09 | 0.00 | 0.00 |
June | 0.553320E+09 | 90358226.24 | 0.253955E+09 | 16113537.12 | 0.237842E+09 | 0.00 | 0.00 |
July | 0.580965E+09 | 78180146.31 | 0.267509E+09 | 24798520.89 | 0.242710E+09 | 0.00 | 0.00 |
August | 0.697999E+09 | 0.109927E+09 | 0.341000E+09 | 90264731.81 | 0.250735E+09 | 0.00 | 0.00 |
September | 0.965492E+09 | 0.200951E+09 | 0.515092E+09 | 0.267608E+09 | 0.247484E+09 | 0.00 | 0.00 |
October | 0.116380E+10 | 0.321664E+09 | 0.723188E+09 | 0.488923E+09 | 0.234265E+09 | 0.00 | 0.00 |
November | 0.121680E+10 | 0.482326E+09 | 0.842216E+09 | 0.642087E+09 | 0.200130E+09 | 0.00 | 0.00 |
December | 0.119007E+10 | 0.591766E+09 | 0.862491E+09 | 0.647425E+09 | 0.215066E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.107320E+11 | 0.376502E+10 | 0.670861E+10 | 0.387662E+10 | 0.283199E+10 | 0.00 | 0.00 |
Minimum of Months | 0.548640E+09 | 78180146.31 | 0.253955E+09 | 16113537.12 | 0.200130E+09 | 0.00 | 0.00 |
Maximum of Months | 0.121680E+10 | 0.591766E+09 | 0.862491E+09 | 0.647425E+09 | 0.268789E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.238815E+10 | 0.105276E+10 | 0.168418E+10 | 0.127594E+10 | 0.408237E+09 | 0.00 | 0.00 |
February | 0.203596E+10 | 0.856729E+09 | 0.141108E+10 | 0.994786E+09 | 0.416289E+09 | 0.00 | 0.00 |
March | 0.189148E+10 | 0.854517E+09 | 0.126966E+10 | 0.732083E+09 | 0.537578E+09 | 0.00 | 0.00 |
April | 0.137522E+10 | 0.535483E+09 | 0.833057E+09 | 0.310835E+09 | 0.522223E+09 | 0.00 | 0.00 |
May | 0.109928E+10 | 0.338907E+09 | 0.608336E+09 | 85147127.19 | 0.523189E+09 | 0.00 | 0.00 |
June | 0.110897E+10 | 0.169137E+09 | 0.507911E+09 | 32227074.24 | 0.475683E+09 | 0.00 | 0.00 |
July | 0.116189E+10 | 0.144965E+09 | 0.535018E+09 | 49597041.79 | 0.485420E+09 | 0.00 | 0.00 |
August | 0.139564E+10 | 0.206699E+09 | 0.682000E+09 | 0.180529E+09 | 0.501470E+09 | 0.00 | 0.00 |
September | 0.193058E+10 | 0.386732E+09 | 0.103018E+10 | 0.535217E+09 | 0.494968E+09 | 0.00 | 0.00 |
October | 0.233265E+10 | 0.626746E+09 | 0.144638E+10 | 0.977846E+09 | 0.468529E+09 | 0.00 | 0.00 |
November | 0.244679E+10 | 0.938731E+09 | 0.168443E+10 | 0.128417E+10 | 0.400260E+09 | 0.00 | 0.00 |
December | 0.239719E+10 | 0.114927E+10 | 0.172498E+10 | 0.129485E+10 | 0.430132E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.215638E+11 | 0.726068E+10 | 0.134172E+11 | 0.775323E+10 | 0.566398E+10 | 0.00 | 0.00 |
Minimum of Months | 0.109928E+10 | 0.144965E+09 | 0.507911E+09 | 32227074.24 | 0.400260E+09 | 0.00 | 0.00 |
Maximum of Months | 0.244679E+10 | 0.114927E+10 | 0.172498E+10 | 0.129485E+10 | 0.537578E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.119207E+10 | 0.525697E+09 | 0.842088E+09 | 0.637970E+09 | 0.204119E+09 | 0.00 | 0.00 |
February | 0.101643E+10 | 0.427701E+09 | 0.705538E+09 | 0.497393E+09 | 0.208145E+09 | 0.00 | 0.00 |
March | 0.944376E+09 | 0.425969E+09 | 0.634831E+09 | 0.366042E+09 | 0.268789E+09 | 0.00 | 0.00 |
April | 0.687336E+09 | 0.265991E+09 | 0.416529E+09 | 0.155417E+09 | 0.261111E+09 | 0.00 | 0.00 |
May | 0.551011E+09 | 0.167193E+09 | 0.304168E+09 | 42573563.60 | 0.261595E+09 | 0.00 | 0.00 |
June | 0.557898E+09 | 82396058.58 | 0.253955E+09 | 16113537.12 | 0.237842E+09 | 0.00 | 0.00 |
July | 0.583773E+09 | 70281594.59 | 0.267509E+09 | 24798520.89 | 0.242710E+09 | 0.00 | 0.00 |
August | 0.699750E+09 | 0.100931E+09 | 0.341000E+09 | 90264731.81 | 0.250735E+09 | 0.00 | 0.00 |
September | 0.965512E+09 | 0.190876E+09 | 0.515092E+09 | 0.267608E+09 | 0.247484E+09 | 0.00 | 0.00 |
October | 0.116517E+10 | 0.311803E+09 | 0.723188E+09 | 0.488923E+09 | 0.234265E+09 | 0.00 | 0.00 |
November | 0.122198E+10 | 0.468468E+09 | 0.842216E+09 | 0.642087E+09 | 0.200130E+09 | 0.00 | 0.00 |
December | 0.119680E+10 | 0.574334E+09 | 0.862491E+09 | 0.647425E+09 | 0.215066E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.107821E+11 | 0.361164E+10 | 0.670861E+10 | 0.387662E+10 | 0.283199E+10 | 0.00 | 0.00 |
Minimum of Months | 0.551011E+09 | 70281594.59 | 0.253955E+09 | 16113537.12 | 0.200130E+09 | 0.00 | 0.00 |
Maximum of Months | 0.122198E+10 | 0.574334E+09 | 0.862491E+09 | 0.647425E+09 | 0.268789E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.119335E+10 | 0.522705E+09 | 0.842088E+09 | 0.637970E+09 | 0.204119E+09 | 0.00 | 0.00 |
February | 0.101780E+10 | 0.424949E+09 | 0.705538E+09 | 0.497393E+09 | 0.208145E+09 | 0.00 | 0.00 |
March | 0.946223E+09 | 0.422690E+09 | 0.634831E+09 | 0.366042E+09 | 0.268789E+09 | 0.00 | 0.00 |
April | 0.688442E+09 | 0.264204E+09 | 0.416529E+09 | 0.155417E+09 | 0.261111E+09 | 0.00 | 0.00 |
May | 0.551612E+09 | 0.166351E+09 | 0.304168E+09 | 42573563.60 | 0.261595E+09 | 0.00 | 0.00 |
June | 0.558437E+09 | 81900941.62 | 0.253955E+09 | 16113537.12 | 0.237842E+09 | 0.00 | 0.00 |
July | 0.584269E+09 | 69810073.42 | 0.267509E+09 | 24798520.89 | 0.242710E+09 | 0.00 | 0.00 |
August | 0.700152E+09 | 0.100446E+09 | 0.341000E+09 | 90264731.81 | 0.250735E+09 | 0.00 | 0.00 |
September | 0.965834E+09 | 0.190278E+09 | 0.515092E+09 | 0.267608E+09 | 0.247484E+09 | 0.00 | 0.00 |
October | 0.116578E+10 | 0.310686E+09 | 0.723188E+09 | 0.488923E+09 | 0.234265E+09 | 0.00 | 0.00 |
November | 0.122353E+10 | 0.465913E+09 | 0.842216E+09 | 0.642087E+09 | 0.200130E+09 | 0.00 | 0.00 |
December | 0.119790E+10 | 0.571963E+09 | 0.862491E+09 | 0.647425E+09 | 0.215066E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.107933E+11 | 0.359190E+10 | 0.670861E+10 | 0.387662E+10 | 0.283199E+10 | 0.00 | 0.00 |
Minimum of Months | 0.551612E+09 | 69810073.42 | 0.253955E+09 | 16113537.12 | 0.200130E+09 | 0.00 | 0.00 |
Maximum of Months | 0.122353E+10 | 0.571963E+09 | 0.862491E+09 | 0.647425E+09 | 0.268789E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.119655E+10 | 0.514118E+09 | 0.842088E+09 | 0.637970E+09 | 0.204119E+09 | 0.00 | 0.00 |
February | 0.102144E+10 | 0.416811E+09 | 0.705538E+09 | 0.497393E+09 | 0.208145E+09 | 0.00 | 0.00 |
March | 0.950725E+09 | 0.413388E+09 | 0.634831E+09 | 0.366042E+09 | 0.268789E+09 | 0.00 | 0.00 |
April | 0.691075E+09 | 0.259011E+09 | 0.416529E+09 | 0.155417E+09 | 0.261111E+09 | 0.00 | 0.00 |
May | 0.552564E+09 | 0.164236E+09 | 0.304168E+09 | 42573563.60 | 0.261595E+09 | 0.00 | 0.00 |
June | 0.558445E+09 | 81328540.67 | 0.253955E+09 | 16113537.12 | 0.237842E+09 | 0.00 | 0.00 |
July | 0.583948E+09 | 69582142.91 | 0.267509E+09 | 24798520.89 | 0.242710E+09 | 0.00 | 0.00 |
August | 0.699729E+09 | 0.100347E+09 | 0.341000E+09 | 90264731.81 | 0.250735E+09 | 0.00 | 0.00 |
September | 0.965691E+09 | 0.189923E+09 | 0.515092E+09 | 0.267608E+09 | 0.247484E+09 | 0.00 | 0.00 |
October | 0.116700E+10 | 0.307950E+09 | 0.723188E+09 | 0.488923E+09 | 0.234265E+09 | 0.00 | 0.00 |
November | 0.122722E+10 | 0.459151E+09 | 0.842216E+09 | 0.642087E+09 | 0.200130E+09 | 0.00 | 0.00 |
December | 0.120084E+10 | 0.564761E+09 | 0.862491E+09 | 0.647425E+09 | 0.215066E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.108152E+11 | 0.354061E+10 | 0.670861E+10 | 0.387662E+10 | 0.283199E+10 | 0.00 | 0.00 |
Minimum of Months | 0.552564E+09 | 69582142.91 | 0.253955E+09 | 16113537.12 | 0.200130E+09 | 0.00 | 0.00 |
Maximum of Months | 0.122722E+10 | 0.564761E+09 | 0.862491E+09 | 0.647425E+09 | 0.268789E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.120415E+10 | 0.484512E+09 | 0.842088E+09 | 0.637970E+09 | 0.204119E+09 | 0.00 | 0.00 |
February | 0.102958E+10 | 0.389021E+09 | 0.705538E+09 | 0.497393E+09 | 0.208145E+09 | 0.00 | 0.00 |
March | 0.959066E+09 | 0.382637E+09 | 0.634831E+09 | 0.366042E+09 | 0.268789E+09 | 0.00 | 0.00 |
April | 0.694093E+09 | 0.240804E+09 | 0.416529E+09 | 0.155417E+09 | 0.261111E+09 | 0.00 | 0.00 |
May | 0.551216E+09 | 0.155950E+09 | 0.304168E+09 | 42573563.60 | 0.261595E+09 | 0.00 | 0.00 |
June | 0.552493E+09 | 79516360.74 | 0.253955E+09 | 16113537.12 | 0.237842E+09 | 0.00 | 0.00 |
July | 0.576043E+09 | 70144318.02 | 0.267509E+09 | 24798520.89 | 0.242710E+09 | 0.00 | 0.00 |
August | 0.691976E+09 | 0.101648E+09 | 0.341000E+09 | 90264731.81 | 0.250735E+09 | 0.00 | 0.00 |
September | 0.960066E+09 | 0.190477E+09 | 0.515092E+09 | 0.267608E+09 | 0.247484E+09 | 0.00 | 0.00 |
October | 0.116755E+10 | 0.298851E+09 | 0.723188E+09 | 0.488923E+09 | 0.234265E+09 | 0.00 | 0.00 |
November | 0.123351E+10 | 0.438140E+09 | 0.842216E+09 | 0.642087E+09 | 0.200130E+09 | 0.00 | 0.00 |
December | 0.120814E+10 | 0.538748E+09 | 0.862491E+09 | 0.647425E+09 | 0.215066E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.108279E+11 | 0.337045E+10 | 0.670861E+10 | 0.387662E+10 | 0.283199E+10 | 0.00 | 0.00 |
Minimum of Months | 0.551216E+09 | 70144318.02 | 0.253955E+09 | 16113537.12 | 0.200130E+09 | 0.00 | 0.00 |
Maximum of Months | 0.123351E+10 | 0.538748E+09 | 0.862491E+09 | 0.647425E+09 | 0.268789E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 8.14 | 3.28 | -3.0 | 3.49 | -5.4 | 41.12 | 223.64 | 0.00 |
February | 10.27 | 3.71 | -4.6 | 3.82 | -5.0 | 51.61 | 245.22 | 0.00 |
March | 12.55 | 4.68 | -5.5 | 4.62 | -3.1 | 72.41 | 273.25 | 0.00 |
April | 19.23 | 8.50 | -2.7 | 4.72 | 3.38 | 79.21 | 314.56 | 0.00 |
May | 23.84 | 12.23 | 2.64 | 5.25 | 8.38 | 86.83 | 326.20 | 0.00 |
June | 27.86 | 15.03 | 5.88 | 4.15 | 14.09 | 80.19 | 344.14 | 0.01 |
July | 27.54 | 18.92 | 14.64 | 3.53 | 17.44 | 86.25 | 283.04 | 0.01 |
August | 26.28 | 17.11 | 12.00 | 3.28 | 15.48 | 80.55 | 269.68 | 0.02 |
September | 23.38 | 15.82 | 11.20 | 2.23 | 11.29 | 66.71 | 294.09 | 0.00 |
October | 18.30 | 12.02 | 7.27 | 3.24 | 6.21 | 54.59 | 257.93 | 0.01 |
November | 11.18 | 5.22 | -1.5 | 3.40 | -3.3 | 40.23 | 258.80 | 0.00 |
December | 6.79 | 1.84 | -4.8 | 2.82 | -8.9 | 42.65 | 217.21 | 0.00 |
Annual Sum or Average | 17.98 | 9.90 | 2.67 | 3.71 | 4.26 | 65.29 | 275.60 | 0.00 |
Minimum of Months | 6.79 | 1.84 | -5.5 | 2.23 | -8.9 | 40.23 | 217.21 | 0.00 |
Maximum of Months | 27.86 | 18.92 | 14.64 | 5.25 | 17.44 | 86.83 | 344.14 | 0.02 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 20.60 | 03-JAN-14:00 | 8.39 | -5.0 | 9.80 | 2.22 | 118.50 | 530.50 |
February | 23.30 | 20-FEB-14:00 | 8.88 | -7.8 | 4.10 | 4.10 | 55.00 | 955.00 |
March | 25.00 | 21-MAR-15:00 | 9.53 | -8.3 | 6.20 | 5.54 | 50.00 | 873.00 |
April | 32.20 | 21-APR-13:00 | 15.21 | 2.80 | 13.90 | 18.28 | 265.50 | 638.50 |
May | 35.00 | 19-MAY-13:00 | 17.23 | 6.10 | 10.30 | 21.78 | 145.00 | 874.50 |
June | 38.90 | 02-JUN-15:00 | 16.22 | -1.1 | 4.60 | 20.40 | 234.50 | 284.00 |
July | 38.30 | 01-JUL-16:00 | 19.19 | 8.90 | 3.60 | 26.81 | 165.50 | 256.50 |
August | 37.20 | 07-AUG-15:00 | 17.89 | 6.70 | 5.70 | 24.66 | 143.50 | 615.00 |
September | 33.90 | 19-SEP-13:00 | 16.85 | 6.70 | 3.10 | 17.75 | 113.00 | 912.00 |
October | 32.80 | 01-OCT-14:00 | 15.90 | 4.40 | 5.70 | 16.12 | 127.50 | 736.50 |
November | 23.90 | 03-NOV-15:00 | 13.45 | 6.10 | 5.70 | 12.22 | 48.50 | 648.50 |
December | 18.30 | 10-DEC-14:00 | 7.97 | -2.8 | 7.20 | 4.10 | 123.00 | 52.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 18.30 | 7.97 | -8.3 | 3.10 | 2.22 | 48.50 | 52.50 | |
Maximum of Months | 38.90 | 19.19 | 8.90 | 13.90 | 26.81 | 265.50 | 955.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -4.4 | 27-JAN-06:00 | -7.5 | -15.0 | 3.60 | -23.6 | 0.00 | 0.00 |
February | -5.6 | 03-FEB-06:00 | -7.5 | -11.7 | 1.50 | -23.9 | 0.00 | 0.00 |
March | -3.9 | 02-MAR-04:00 | -6.5 | -12.8 | 1.50 | -21.3 | 0.00 | 0.00 |
April | 3.30 | 12-APR-05:00 | -1.8 | -9.4 | 2.10 | -14.9 | 37.00 | 217.50 |
May | 9.40 | 02-MAY-05:00 | 3.98 | -2.2 | 3.60 | -7.6 | 51.00 | 277.50 |
June | 15.00 | 13-JUN-04:00 | 4.43 | -10.6 | 2.10 | -4.3 | 0.00 | 0.00 |
July | 17.80 | 05-JUL-05:00 | 15.98 | 15.00 | 4.10 | 4.31 | 39.00 | 249.00 |
August | 16.70 | 31-AUG-05:00 | 13.89 | 12.20 | 4.10 | 2.64 | 36.00 | 126.50 |
September | 8.30 | 30-SEP-05:00 | 5.77 | 3.30 | 1.50 | -7.3 | 0.00 | 0.00 |
October | 6.70 | 11-OCT-05:00 | 5.82 | 5.00 | 1.50 | -5.5 | 0.00 | 0.00 |
November | -0.6 | 17-NOV-03:00 | -3.1 | -6.7 | 1.50 | -18.1 | 0.00 | 0.00 |
December | -4.4 | 27-DEC-06:00 | -5.1 | -6.1 | 2.10 | -18.6 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -5.6 | -7.5 | -15.0 | 1.50 | -23.9 | 0.00 | 0.00 | |
Maximum of Months | 17.80 | 15.98 | 15.00 | 4.10 | 4.31 | 51.00 | 277.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.18 | 12-JAN-15:00 | 18.90 | 2.80 | 3.60 | 6.15 | 70.50 | 491.50 |
February | 11.42 | 13-FEB-16:00 | 12.80 | 10.60 | 4.10 | 6.55 | 34.00 | 18.50 |
March | 10.75 | 10-MAR-18:00 | 13.30 | 8.90 | 1.50 | 8.54 | 0.00 | 0.00 |
April | 15.74 | 29-APR-13:00 | 30.00 | 6.70 | 4.10 | 18.28 | 336.50 | 432.50 |
May | 19.12 | 24-MAY-12:00 | 27.80 | 15.00 | 5.20 | 17.57 | 188.50 | 862.00 |
June | 20.21 | 03-JUN-14:00 | 33.90 | 13.90 | 8.80 | 23.66 | 264.50 | 316.00 |
July | 22.88 | 20-JUL-15:39 | 25.53 | 21.87 | 2.93 | 18.99 | 184.00 | 15.83 |
August | 21.18 | 02-AUG-11:00 | 30.60 | 17.20 | 3.60 | 20.75 | 154.50 | 850.00 |
September | 20.65 | 14-SEP-09:00 | 25.00 | 18.90 | 2.10 | 14.47 | 126.50 | 835.50 |
October | 19.64 | 03-OCT-13:00 | 32.80 | 13.30 | 2.60 | 21.44 | 224.50 | 577.50 |
November | 13.57 | 03-NOV-14:00 | 23.30 | 7.20 | 0.00 | 10.88 | 72.50 | 802.00 |
December | 8.30 | 10-DEC-12:00 | 17.20 | -0.6 | 5.70 | 1.58 | 198.50 | 507.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 8.30 | 12.80 | -0.6 | 0.00 | 1.58 | 0.00 | 0.00 | |
Maximum of Months | 22.88 | 33.90 | 21.87 | 8.80 | 23.66 | 336.50 | 862.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 9.00 | 16-JAN-01:00 | 9.00 | 9.00 | 2.10 | 4.51 | 0.00 | 0.00 |
February | 10.60 | 13-FEB-13:09 | 12.20 | 11.24 | 5.53 | 5.71 | 147.33 | 0.00 |
March | 10.00 | 11-MAR-00:00 | 10.60 | 10.24 | 2.10 | 6.15 | 0.00 | 0.00 |
April | 10.60 | 17-APR-01:00 | 17.80 | 13.38 | 7.20 | 3.48 | 0.00 | 0.00 |
May | 15.00 | 24-MAY-10:00 | 25.60 | 18.41 | 7.20 | 15.39 | 171.00 | 872.50 |
June | 17.20 | 19-JUN-17:00 | 23.90 | 19.20 | 3.60 | 15.39 | 86.00 | 324.00 |
July | 22.20 | 20-JUL-14:00 | 24.40 | 22.82 | 4.60 | 17.93 | 283.00 | 59.50 |
August | 18.90 | 01-AUG-20:00 | 22.20 | 19.91 | 4.60 | 17.75 | 0.00 | 0.00 |
September | 19.40 | 22-SEP-01:00 | 20.60 | 19.76 | 1.50 | 16.30 | 0.00 | 0.00 |
October | 17.20 | 03-OCT-19:00 | 23.30 | 19.11 | 4.60 | 18.46 | 0.00 | 0.00 |
November | 10.00 | 01-NOV-09:00 | 13.30 | 11.28 | 3.10 | 8.94 | 123.50 | 0.00 |
December | 6.10 | 13-DEC-00:00 | 8.30 | 7.10 | 7.70 | 3.06 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.10 | 8.30 | 7.10 | 1.50 | 3.06 | 0.00 | 0.00 | |
Maximum of Months | 22.20 | 25.60 | 22.82 | 7.70 | 18.46 | 283.00 | 872.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 15.16 | 28.38 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 15.21 | 35.58 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 16.80 | 47.71 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 19.62 | 58.45 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 22.88 | 63.58 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 25.71 | 66.73 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 27.35 | 58.19 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 27.33 | 54.44 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 25.68 | 50.89 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 22.83 | 39.37 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 19.57 | 32.11 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 16.77 | 26.90 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 21.28 | 46.90 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 15.16 | 26.90 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 27.35 | 66.73 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK1
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.337062E+09 | -215187556.7 | 0.00 | 0.00 | 744.00 | 0.00 | -121874593.9 | 58.99 | 0.00 | 0.00 |
February | 0.303848E+09 | -195216022.5 | 0.00 | 0.00 | 672.00 | 0.00 | -108631698.9 | 58.99 | 0.00 | 0.00 |
March | 0.329892E+09 | -211647540.5 | 0.00 | 0.00 | 744.00 | 0.00 | -118243982.7 | 58.99 | 0.00 | 0.00 |
April | 0.299342E+09 | -188702721.2 | 0.00 | 0.00 | 720.00 | 0.00 | -110639516.3 | 58.99 | 0.00 | 0.00 |
May | 0.292100E+09 | -179190960.7 | 0.00 | 0.00 | 744.00 | 0.00 | -112908586.8 | 58.99 | 0.00 | 0.00 |
June | 0.269862E+09 | -161375693.7 | 0.00 | 0.00 | 720.00 | 0.00 | -108486529.2 | 58.99 | 0.00 | 0.00 |
July | 0.267113E+09 | -155321838.6 | 0.00 | 0.00 | 744.00 | 0.00 | -111791062.5 | 58.99 | 0.00 | 0.00 |
August | 0.270572E+09 | -158713357.2 | 0.00 | 0.00 | 744.00 | 0.00 | -111858286.9 | 58.99 | 0.00 | 0.00 |
September | 0.268441E+09 | -159851492.5 | 0.00 | 0.00 | 720.00 | 0.00 | -108589467.3 | 58.99 | 0.00 | 0.00 |
October | 0.290655E+09 | -177592252.3 | 0.00 | 0.00 | 744.00 | 0.00 | -113063185.1 | 58.99 | 0.00 | 0.00 |
November | 0.299952E+09 | -186789830.4 | 0.00 | 0.00 | 720.00 | 0.00 | -113161875.9 | 58.99 | 0.00 | 0.00 |
December | 0.329907E+09 | -207551252.1 | 0.00 | 0.00 | 744.00 | 0.00 | -122355873.0 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.355875E+10 | -0.219714E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.136160E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.267113E+09 | -215187556.7 | 0.00 | 0.00 | 672.00 | 0.00 | -122355873.0 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.337062E+09 | -155321838.6 | 0.00 | 0.00 | 744.00 | 0.00 | -108486529.2 | 58.99 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK2
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.333878E+09 | -215187978.9 | 0.00 | 0.00 | 744.00 | 0.00 | -118689538.3 | 58.99 | 0.00 | 0.00 |
February | 0.301296E+09 | -195216345.3 | 0.00 | 0.00 | 672.00 | 0.00 | -106079505.5 | 58.99 | 0.00 | 0.00 |
March | 0.327555E+09 | -211650759.5 | 0.00 | 0.00 | 744.00 | 0.00 | -115904365.6 | 58.99 | 0.00 | 0.00 |
April | 0.298643E+09 | -188704542.8 | 0.00 | 0.00 | 720.00 | 0.00 | -109938717.5 | 58.99 | 0.00 | 0.00 |
May | 0.291879E+09 | -179189167.6 | 0.00 | 0.00 | 744.00 | 0.00 | -112689498.6 | 58.99 | 0.00 | 0.00 |
June | 0.269716E+09 | -161374370.3 | 0.00 | 0.00 | 720.00 | 0.00 | -108341936.0 | 58.99 | 0.00 | 0.00 |
July | 0.267022E+09 | -155318480.6 | 0.00 | 0.00 | 744.00 | 0.00 | -111703901.0 | 58.99 | 0.00 | 0.00 |
August | 0.270543E+09 | -158699143.7 | 0.00 | 0.00 | 744.00 | 0.00 | -111844304.1 | 58.99 | 0.00 | 0.00 |
September | 0.268480E+09 | -159851470.7 | 0.00 | 0.00 | 720.00 | 0.00 | -108629014.5 | 58.99 | 0.00 | 0.00 |
October | 0.290394E+09 | -177587077.5 | 0.00 | 0.00 | 744.00 | 0.00 | -112807366.6 | 58.99 | 0.00 | 0.00 |
November | 0.298181E+09 | -186793724.0 | 0.00 | 0.00 | 720.00 | 0.00 | -111387203.3 | 58.99 | 0.00 | 0.00 |
December | 0.326867E+09 | -207561125.6 | 0.00 | 0.00 | 744.00 | 0.00 | -119305889.8 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.354446E+10 | -0.219713E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.134732E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.267022E+09 | -215187978.9 | 0.00 | 0.00 | 672.00 | 0.00 | -119305889.8 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.333878E+09 | -155318480.6 | 0.00 | 0.00 | 744.00 | 0.00 | -106079505.5 | 58.99 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK3
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.309804E+09 | -189232296.2 | 0.00 | 0.00 | 744.00 | 0.00 | -120571375.5 | 58.99 | 0.00 | 0.00 |
February | 0.279140E+09 | -171817829.4 | 0.00 | 0.00 | 672.00 | 0.00 | -107322449.9 | 58.99 | 0.00 | 0.00 |
March | 0.305595E+09 | -188882281.4 | 0.00 | 0.00 | 744.00 | 0.00 | -116712614.9 | 58.99 | 0.00 | 0.00 |
April | 0.275109E+09 | -165972681.9 | 0.00 | 0.00 | 720.00 | 0.00 | -109135961.7 | 58.99 | 0.00 | 0.00 |
May | 0.270075E+09 | -158962391.6 | 0.00 | 0.00 | 744.00 | 0.00 | -111112296.5 | 58.99 | 0.00 | 0.00 |
June | 0.250099E+09 | -143714572.8 | 0.00 | 0.00 | 720.00 | 0.00 | -106384031.1 | 58.99 | 0.00 | 0.00 |
July | 0.245376E+09 | -135784023.2 | 0.00 | 0.00 | 744.00 | 0.00 | -109591593.8 | 58.99 | 0.00 | 0.00 |
August | 0.251629E+09 | -141766862.2 | 0.00 | 0.00 | 744.00 | 0.00 | -109862102.5 | 58.99 | 0.00 | 0.00 |
September | 0.247415E+09 | -140473480.3 | 0.00 | 0.00 | 720.00 | 0.00 | -106941783.9 | 59.01 | 0.00 | 0.00 |
October | 0.268008E+09 | -156187915.2 | 0.00 | 0.00 | 744.00 | 0.00 | -111819862.2 | 58.99 | 0.00 | 0.00 |
November | 0.276918E+09 | -164927463.0 | 0.00 | 0.00 | 720.00 | 0.00 | -111990596.0 | 58.99 | 0.00 | 0.00 |
December | 0.302297E+09 | -181174861.7 | 0.00 | 0.00 | 744.00 | 0.00 | -121121896.3 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.328146E+10 | -0.193890E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.134257E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.245376E+09 | -189232296.2 | 0.00 | 0.00 | 672.00 | 0.00 | -121121896.3 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.309804E+09 | -135784023.2 | 0.00 | 0.00 | 744.00 | 0.00 | -106384031.1 | 59.01 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK4
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.310428E+09 | -189231258.6 | 0.00 | 0.00 | 744.00 | 0.00 | -121196552.9 | 58.99 | 0.00 | 0.00 |
February | 0.279623E+09 | -171803164.1 | 0.00 | 0.00 | 672.00 | 0.00 | -107819676.7 | 59.00 | 0.00 | 0.00 |
March | 0.306021E+09 | -188880263.2 | 0.00 | 0.00 | 744.00 | 0.00 | -117140554.3 | 58.99 | 0.00 | 0.00 |
April | 0.275203E+09 | -166004700.2 | 0.00 | 0.00 | 720.00 | 0.00 | -109198329.3 | 58.98 | 0.00 | 0.00 |
May | 0.270042E+09 | -158973868.5 | 0.00 | 0.00 | 744.00 | 0.00 | -111067895.1 | 58.99 | 0.00 | 0.00 |
June | 0.250007E+09 | -143695312.0 | 0.00 | 0.00 | 720.00 | 0.00 | -106311309.7 | 58.99 | 0.00 | 0.00 |
July | 0.245280E+09 | -135784891.0 | 0.00 | 0.00 | 744.00 | 0.00 | -109495131.3 | 58.99 | 0.00 | 0.00 |
August | 0.251538E+09 | -141767700.3 | 0.00 | 0.00 | 744.00 | 0.00 | -109770720.4 | 58.99 | 0.00 | 0.00 |
September | 0.247353E+09 | -140480485.4 | 0.00 | 0.00 | 720.00 | 0.00 | -106872945.6 | 59.00 | 0.00 | 0.00 |
October | 0.268046E+09 | -156182507.6 | 0.00 | 0.00 | 744.00 | 0.00 | -111863483.5 | 59.00 | 0.00 | 0.00 |
November | 0.277242E+09 | -164927387.7 | 0.00 | 0.00 | 720.00 | 0.00 | -112314169.6 | 58.99 | 0.00 | 0.00 |
December | 0.302868E+09 | -181170256.1 | 0.00 | 0.00 | 744.00 | 0.00 | -121697805.9 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.328365E+10 | -0.193890E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.134475E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.245280E+09 | -189231258.6 | 0.00 | 0.00 | 672.00 | 0.00 | -121697805.9 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.310428E+09 | -135784891.0 | 0.00 | 0.00 | 744.00 | 0.00 | -106311309.7 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK5
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.301919E+09 | -178852667.7 | 0.00 | 0.00 | 744.00 | 0.00 | -123066426.9 | 58.99 | 0.00 | 0.00 |
February | 0.271964E+09 | -162485073.0 | 0.00 | 0.00 | 672.00 | 0.00 | -109478859.4 | 58.99 | 0.00 | 0.00 |
March | 0.297708E+09 | -178711045.7 | 0.00 | 0.00 | 744.00 | 0.00 | -118997373.6 | 59.00 | 0.00 | 0.00 |
April | 0.267426E+09 | -157064040.8 | 0.00 | 0.00 | 720.00 | 0.00 | -110361659.2 | 58.99 | 0.00 | 0.00 |
May | 0.262292E+09 | -150351370.5 | 0.00 | 0.00 | 744.00 | 0.00 | -111940934.1 | 58.98 | 0.00 | 0.00 |
June | 0.243125E+09 | -135982217.5 | 0.00 | 0.00 | 720.00 | 0.00 | -107142942.0 | 58.99 | 0.00 | 0.00 |
July | 0.238604E+09 | -128424208.2 | 0.00 | 0.00 | 744.00 | 0.00 | -110179790.5 | 58.99 | 0.00 | 0.00 |
August | 0.244628E+09 | -134132931.6 | 0.00 | 0.00 | 744.00 | 0.00 | -110495088.9 | 58.99 | 0.00 | 0.00 |
September | 0.240487E+09 | -132987937.6 | 0.00 | 0.00 | 720.00 | 0.00 | -107498647.4 | 58.99 | 0.00 | 0.00 |
October | 0.260236E+09 | -147621850.1 | 0.00 | 0.00 | 744.00 | 0.00 | -112614038.2 | 58.99 | 0.00 | 0.00 |
November | 0.269494E+09 | -155761883.3 | 0.00 | 0.00 | 720.00 | 0.00 | -113732455.6 | 58.99 | 0.00 | 0.00 |
December | 0.294825E+09 | -171333395.6 | 0.00 | 0.00 | 744.00 | 0.00 | -123491676.7 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.319271E+10 | -0.183371E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.135900E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.238604E+09 | -178852667.7 | 0.00 | 0.00 | 672.00 | 0.00 | -123491676.7 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.301919E+09 | -128424208.2 | 0.00 | 0.00 | 744.00 | 0.00 | -107142942.0 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK6
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.302019E+09 | -178854840.0 | 0.00 | 0.00 | 744.00 | 0.00 | -123164108.7 | 58.99 | 0.00 | 0.00 |
February | 0.272047E+09 | -162480715.3 | 0.00 | 0.00 | 672.00 | 0.00 | -109566120.0 | 58.99 | 0.00 | 0.00 |
March | 0.297822E+09 | -178741387.8 | 0.00 | 0.00 | 744.00 | 0.00 | -119080629.9 | 58.99 | 0.00 | 0.00 |
April | 0.267502E+09 | -157046869.3 | 0.00 | 0.00 | 720.00 | 0.00 | -110455462.1 | 58.99 | 0.00 | 0.00 |
May | 0.262365E+09 | -150314335.3 | 0.00 | 0.00 | 744.00 | 0.00 | -112050440.0 | 59.00 | 0.00 | 0.00 |
June | 0.243233E+09 | -135985550.1 | 0.00 | 0.00 | 720.00 | 0.00 | -107247550.2 | 58.99 | 0.00 | 0.00 |
July | 0.238738E+09 | -128412373.4 | 0.00 | 0.00 | 744.00 | 0.00 | -110325592.9 | 58.99 | 0.00 | 0.00 |
August | 0.244742E+09 | -134143753.7 | 0.00 | 0.00 | 744.00 | 0.00 | -110598118.1 | 58.99 | 0.00 | 0.00 |
September | 0.240597E+09 | -132952950.2 | 0.00 | 0.00 | 720.00 | 0.00 | -107644381.0 | 59.00 | 0.00 | 0.00 |
October | 0.260297E+09 | -147625234.6 | 0.00 | 0.00 | 744.00 | 0.00 | -112671746.3 | 58.99 | 0.00 | 0.00 |
November | 0.269585E+09 | -155760325.9 | 0.00 | 0.00 | 720.00 | 0.00 | -113824325.4 | 58.99 | 0.00 | 0.00 |
December | 0.294899E+09 | -171314436.6 | 0.00 | 0.00 | 744.00 | 0.00 | -123584715.3 | 59.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.319385E+10 | -0.183363E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.136021E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.238738E+09 | -178854840.0 | 0.00 | 0.00 | 672.00 | 0.00 | -123584715.3 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.302019E+09 | -128412373.4 | 0.00 | 0.00 | 744.00 | 0.00 | -107247550.2 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK7
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.302202E+09 | -178859899.2 | 0.00 | 0.00 | 744.00 | 0.00 | -123341862.9 | 58.99 | 0.00 | 0.00 |
February | 0.272244E+09 | -162471207.2 | 0.00 | 0.00 | 672.00 | 0.00 | -109772417.4 | 59.00 | 0.00 | 0.00 |
March | 0.298047E+09 | -178729850.3 | 0.00 | 0.00 | 744.00 | 0.00 | -119317153.5 | 58.99 | 0.00 | 0.00 |
April | 0.267623E+09 | -157066577.7 | 0.00 | 0.00 | 720.00 | 0.00 | -110556144.1 | 58.99 | 0.00 | 0.00 |
May | 0.262421E+09 | -150355781.3 | 0.00 | 0.00 | 744.00 | 0.00 | -112064874.7 | 58.98 | 0.00 | 0.00 |
June | 0.243276E+09 | -135988440.5 | 0.00 | 0.00 | 720.00 | 0.00 | -107287638.1 | 58.99 | 0.00 | 0.00 |
July | 0.238778E+09 | -128423217.5 | 0.00 | 0.00 | 744.00 | 0.00 | -110354920.6 | 58.99 | 0.00 | 0.00 |
August | 0.244779E+09 | -134140758.1 | 0.00 | 0.00 | 744.00 | 0.00 | -110638084.4 | 58.99 | 0.00 | 0.00 |
September | 0.240628E+09 | -132976688.5 | 0.00 | 0.00 | 720.00 | 0.00 | -107651635.2 | 58.99 | 0.00 | 0.00 |
October | 0.260371E+09 | -147639043.4 | 0.00 | 0.00 | 744.00 | 0.00 | -112731479.2 | 58.99 | 0.00 | 0.00 |
November | 0.269778E+09 | -155761003.1 | 0.00 | 0.00 | 720.00 | 0.00 | -114016996.2 | 58.99 | 0.00 | 0.00 |
December | 0.295045E+09 | -171327322.7 | 0.00 | 0.00 | 744.00 | 0.00 | -123717628.3 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.319519E+10 | -0.183374E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.136145E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.238778E+09 | -178859899.2 | 0.00 | 0.00 | 672.00 | 0.00 | -123717628.3 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.302202E+09 | -128423217.5 | 0.00 | 0.00 | 744.00 | 0.00 | -107287638.1 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 276.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 268.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 351.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 373.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 408.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 398.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 400.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 377.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 365.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 318.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 295.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 289.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4125.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 268.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 408.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 HEATING COIL
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.234380E+10 | 58814.13 | 05-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.134759E+10 | 58814.13 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.674417E+09 | 58814.13 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 9153973.74 | 3483.87 | 11-APR-08:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.581040E+09 | 58814.13 | 28-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.332670E+10 | 58814.13 | 04-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.828271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.332670E+10 | 58814.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 HEATING COIL
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.307497E+09 | 30461.80 | 27-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.139842E+09 | 30461.80 | 02-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 74587900.73 | 30461.80 | 02-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 80745960.24 | 20394.93 | 28-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.555342E+09 | 30461.80 | 27-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.115801E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.555342E+09 | 30461.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3 HEATING COIL
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.699585E+09 | 31154.76 | 28-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.326650E+09 | 30895.29 | 03-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.172380E+09 | 28310.33 | 02-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 345257.39 | 524.06 | 11-APR-07:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.180495E+09 | 18118.31 | 28-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.104457E+10 | 31154.76 | 27-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.242403E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.104457E+10 | 31154.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4 HEATING COIL
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.843025E+09 | 31013.52 | 27-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.394022E+09 | 31013.52 | 03-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.209693E+09 | 31013.52 | 02-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 697725.58 | 795.31 | 11-APR-07:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.209376E+09 | 21210.89 | 28-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.119613E+10 | 31013.52 | 04-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.285295E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.119613E+10 | 31013.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5 HEATING COIL
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.105499E+10 | 30982.65 | 27-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.517860E+09 | 30982.65 | 02-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.280671E+09 | 30982.65 | 02-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 2241779.51 | 1365.27 | 11-APR-07:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.251793E+09 | 24408.42 | 28-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.142325E+10 | 30982.65 | 04-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.353081E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.142325E+10 | 30982.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6 HEATING COIL
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.241272E+10 | 54877.46 | 02-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.125658E+10 | 54877.46 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.626744E+09 | 54877.46 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6412948.73 | 3522.25 | 11-APR-08:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.587354E+09 | 54877.46 | 28-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.316941E+10 | 54877.46 | 03-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.805921E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.316941E+10 | 54877.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7 HEATING COIL
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.127514E+10 | 28321.81 | 02-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.666384E+09 | 28321.81 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.336630E+09 | 28321.81 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 2866442.51 | 1742.49 | 11-APR-08:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.306334E+09 | 28321.81 | 28-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.166032E+10 | 28321.81 | 03-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.424767E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.166032E+10 | 28321.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8 HEATING COIL
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.135120E+10 | 28217.14 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.717366E+09 | 28217.14 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.369093E+09 | 28217.14 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 3747965.07 | 2043.58 | 11-APR-08:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.321927E+09 | 28217.14 | 27-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.173315E+10 | 28217.14 | 03-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.449648E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.173315E+10 | 28217.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9 HEATING COIL
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.160085E+10 | 28249.86 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.893254E+09 | 28249.86 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.487094E+09 | 28249.86 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 9093637.99 | 3275.20 | 11-APR-08:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.379961E+09 | 28249.86 | 27-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.197272E+10 | 28249.86 | 02-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.534298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.197272E+10 | 28249.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10 HEATING COIL
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.229611E+10 | 31356.71 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.141445E+10 | 31356.71 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.867040E+09 | 31356.71 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 43226870.44 | 24167.44 | 12-APR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.569518E+09 | 31356.71 | 27-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.260185E+10 | 31356.71 | 01-DEC-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.779220E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.260185E+10 | 31356.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 222235.51 | 222235.51 | 271.66 | 03-JAN-15:00 | 271.66 | 0.00 |
February | 0.00 | 0.00 | 0.322098E+09 | 0.322098E+09 | 6159.11 | 20-FEB-16:00 | 6159.11 | 0.00 |
March | 0.00 | 0.00 | 0.896546E+09 | 0.896546E+09 | 7517.58 | 14-MAR-16:30 | 7517.58 | 0.00 |
April | 0.00 | 0.00 | 0.821102E+10 | 0.818741E+10 | 15769.46 | 30-APR-16:04 | 15769.46 | 0.00 |
May | 0.00 | 0.00 | 0.164774E+11 | 0.160105E+11 | 31141.15 | 31-MAY-07:03 | 31141.15 | 0.00 |
June | 0.00 | 0.00 | 0.236303E+11 | 0.228076E+11 | 45766.02 | 19-JUN-07:02 | 38808.12 | 0.00 |
July | 0.00 | 0.00 | 0.285184E+11 | 0.236251E+11 | 49210.05 | 20-JUL-07:03 | 29763.94 | 0.00 |
August | 0.00 | 0.00 | 0.247931E+11 | 0.219692E+11 | 48903.80 | 02-AUG-07:02 | 27245.20 | 0.00 |
September | 0.00 | 0.00 | 0.208017E+11 | 0.180888E+11 | 48146.11 | 23-SEP-07:02 | 27314.75 | 0.00 |
October | 0.00 | 0.00 | 0.950952E+10 | 0.852163E+10 | 44756.14 | 02-OCT-07:02 | 38709.70 | 0.00 |
November | 0.00 | 0.00 | 0.743345E+09 | 0.735353E+09 | 9513.80 | 09-NOV-15:00 | 9513.80 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.133904E+12 | 0.121165E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.285184E+11 | 0.236251E+11 | 49210.05 | 38808.12 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 13806934.15 | 13771502.21 | 3231.50 | 01-JAN-18:10 | 3231.50 | 0.00 |
February | 0.00 | 0.00 | 0.304688E+09 | 0.304641E+09 | 22100.90 | 12-FEB-18:30 | 22100.90 | 0.00 |
March | 0.00 | 0.00 | 0.755374E+09 | 0.755265E+09 | 22100.90 | 12-MAR-17:20 | 22100.90 | 0.00 |
April | 0.00 | 0.00 | 0.532561E+10 | 0.530550E+10 | 22859.65 | 18-APR-20:56 | 20323.29 | 0.00 |
May | 0.00 | 0.00 | 0.932330E+10 | 0.901762E+10 | 23916.85 | 27-MAY-21:00 | 17744.02 | 0.00 |
June | 0.00 | 0.00 | 0.122092E+11 | 0.117620E+11 | 23899.00 | 29-JUN-22:38 | 18232.99 | 0.00 |
July | 0.00 | 0.00 | 0.145265E+11 | 0.121044E+11 | 25425.22 | 19-JUL-07:03 | 10801.43 | 0.00 |
August | 0.00 | 0.00 | 0.129207E+11 | 0.113938E+11 | 25172.06 | 03-AUG-07:02 | 15231.41 | 0.00 |
September | 0.00 | 0.00 | 0.115023E+11 | 0.100026E+11 | 24767.34 | 23-SEP-07:02 | 14959.99 | 0.00 |
October | 0.00 | 0.00 | 0.583630E+10 | 0.520131E+10 | 24765.97 | 03-OCT-20:03 | 14694.30 | 0.00 |
November | 0.00 | 0.00 | 0.542673E+09 | 0.537065E+09 | 22100.90 | 09-NOV-22:03 | 21136.02 | 0.00 |
December | 0.00 | 0.00 | 4639622.01 | 4638228.70 | 2083.00 | 09-DEC-19:10 | 2083.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.732651E+11 | 0.664026E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4639622.01 | 4638228.70 | 2083.00 | 2083.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.145265E+11 | 0.121044E+11 | 25425.22 | 22100.90 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3 COOLING COIL
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 859508.05 | 859508.05 | 393.77 | 03-JAN-15:00 | 393.77 | 0.00 |
February | 0.00 | 0.00 | 0.170975E+09 | 0.170975E+09 | 3059.35 | 20-FEB-15:00 | 3059.35 | 0.00 |
March | 0.00 | 0.00 | 0.521828E+09 | 0.521828E+09 | 4245.99 | 22-MAR-13:00 | 4245.99 | 0.00 |
April | 0.00 | 0.00 | 0.337830E+10 | 0.336833E+10 | 8357.02 | 21-APR-14:00 | 8357.02 | 0.00 |
May | 0.00 | 0.00 | 0.663396E+10 | 0.646085E+10 | 22486.03 | 31-MAY-06:02 | 22486.03 | 0.00 |
June | 0.00 | 0.00 | 0.945919E+10 | 0.913072E+10 | 24103.62 | 19-JUN-06:02 | 20819.61 | 0.00 |
July | 0.00 | 0.00 | 0.112281E+11 | 0.928060E+10 | 26117.15 | 19-JUL-06:03 | 16646.57 | 0.00 |
August | 0.00 | 0.00 | 0.983553E+10 | 0.864345E+10 | 26046.92 | 03-AUG-06:02 | 13831.21 | 0.00 |
September | 0.00 | 0.00 | 0.844658E+10 | 0.740139E+10 | 25531.38 | 23-SEP-06:02 | 14455.42 | 0.00 |
October | 0.00 | 0.00 | 0.400879E+10 | 0.362975E+10 | 24406.59 | 05-OCT-06:02 | 16555.57 | 0.00 |
November | 0.00 | 0.00 | 0.404262E+09 | 0.399921E+09 | 5022.35 | 09-NOV-14:00 | 5022.35 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.540884E+11 | 0.490087E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.112281E+11 | 0.928060E+10 | 26117.15 | 22486.03 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4 COOLING COIL
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 114443.84 | 114443.84 | 128.11 | 03-JAN-15:00 | 128.11 | 0.00 |
February | 0.00 | 0.00 | 0.147783E+09 | 0.147783E+09 | 2833.89 | 20-FEB-15:00 | 2833.89 | 0.00 |
March | 0.00 | 0.00 | 0.479799E+09 | 0.479799E+09 | 4100.88 | 22-MAR-13:00 | 4100.88 | 0.00 |
April | 0.00 | 0.00 | 0.333591E+10 | 0.332607E+10 | 8336.63 | 21-APR-14:00 | 8336.63 | 0.00 |
May | 0.00 | 0.00 | 0.664207E+10 | 0.646839E+10 | 22646.33 | 31-MAY-06:02 | 22646.33 | 0.00 |
June | 0.00 | 0.00 | 0.950353E+10 | 0.917322E+10 | 23964.34 | 19-JUN-06:02 | 20723.52 | 0.00 |
July | 0.00 | 0.00 | 0.112764E+11 | 0.932347E+10 | 25965.03 | 19-JUL-06:03 | 16573.00 | 0.00 |
August | 0.00 | 0.00 | 0.988357E+10 | 0.868588E+10 | 25892.62 | 03-AUG-06:02 | 13756.75 | 0.00 |
September | 0.00 | 0.00 | 0.847785E+10 | 0.742787E+10 | 25380.51 | 23-SEP-06:02 | 14379.36 | 0.00 |
October | 0.00 | 0.00 | 0.398853E+10 | 0.361181E+10 | 24262.01 | 05-OCT-06:02 | 16463.66 | 0.00 |
November | 0.00 | 0.00 | 0.380445E+09 | 0.376287E+09 | 4939.24 | 09-NOV-14:00 | 4939.24 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.541160E+11 | 0.490207E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.112764E+11 | 0.932347E+10 | 25965.03 | 22646.33 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5 COOLING COIL
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.116587E+09 | 0.116587E+09 | 2523.98 | 20-FEB-15:00 | 2523.98 | 0.00 |
March | 0.00 | 0.00 | 0.406420E+09 | 0.406420E+09 | 3834.17 | 22-MAR-13:00 | 3834.17 | 0.00 |
April | 0.00 | 0.00 | 0.317006E+10 | 0.316115E+10 | 8159.15 | 21-APR-14:00 | 8159.15 | 0.00 |
May | 0.00 | 0.00 | 0.644788E+10 | 0.628072E+10 | 21099.36 | 31-MAY-06:02 | 21099.36 | 0.00 |
June | 0.00 | 0.00 | 0.930682E+10 | 0.898825E+10 | 23962.65 | 19-JUN-06:02 | 20725.48 | 0.00 |
July | 0.00 | 0.00 | 0.110653E+11 | 0.914935E+10 | 25960.70 | 17-JUL-06:02 | 11341.74 | 0.00 |
August | 0.00 | 0.00 | 0.967842E+10 | 0.851233E+10 | 25891.96 | 03-AUG-06:02 | 13728.98 | 0.00 |
September | 0.00 | 0.00 | 0.828393E+10 | 0.726208E+10 | 25379.10 | 23-SEP-06:02 | 14355.42 | 0.00 |
October | 0.00 | 0.00 | 0.383613E+10 | 0.347599E+10 | 24260.60 | 05-OCT-06:02 | 16442.85 | 0.00 |
November | 0.00 | 0.00 | 0.331354E+09 | 0.327810E+09 | 4728.39 | 09-NOV-14:00 | 4728.39 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.526429E+11 | 0.476807E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.110653E+11 | 0.914935E+10 | 25960.70 | 21099.36 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6 COOLING COIL
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.173091E+09 | 0.173091E+09 | 4333.90 | 20-FEB-15:30 | 4333.90 | 0.00 |
March | 0.00 | 0.00 | 0.606515E+09 | 0.606515E+09 | 6541.36 | 22-MAR-13:00 | 6541.36 | 0.00 |
April | 0.00 | 0.00 | 0.542990E+10 | 0.541108E+10 | 14967.44 | 21-APR-14:30 | 14967.44 | 0.00 |
May | 0.00 | 0.00 | 0.114598E+11 | 0.111321E+11 | 32832.28 | 30-MAY-07:03 | 32832.28 | 0.00 |
June | 0.00 | 0.00 | 0.167586E+11 | 0.161664E+11 | 42363.82 | 19-JUN-07:02 | 36807.02 | 0.00 |
July | 0.00 | 0.00 | 0.197051E+11 | 0.162313E+11 | 45623.35 | 19-JUL-07:03 | 18989.47 | 0.00 |
August | 0.00 | 0.00 | 0.173961E+11 | 0.152273E+11 | 45373.65 | 03-AUG-07:02 | 26145.94 | 0.00 |
September | 0.00 | 0.00 | 0.149322E+11 | 0.130046E+11 | 44501.34 | 23-SEP-07:02 | 26161.39 | 0.00 |
October | 0.00 | 0.00 | 0.672450E+10 | 0.601835E+10 | 41549.35 | 02-OCT-07:02 | 36071.28 | 0.00 |
November | 0.00 | 0.00 | 0.509912E+09 | 0.503039E+09 | 8153.44 | 09-NOV-14:00 | 8153.44 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.936957E+11 | 0.844738E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.197051E+11 | 0.162313E+11 | 45623.35 | 36807.02 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7 COOLING COIL
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 79989954.70 | 79989954.70 | 2154.41 | 20-FEB-15:40 | 2154.41 | 0.00 |
March | 0.00 | 0.00 | 0.288438E+09 | 0.288438E+09 | 3262.87 | 22-MAR-13:00 | 3262.87 | 0.00 |
April | 0.00 | 0.00 | 0.277151E+10 | 0.276281E+10 | 7723.98 | 21-APR-14:40 | 7723.98 | 0.00 |
May | 0.00 | 0.00 | 0.588970E+10 | 0.572654E+10 | 16367.78 | 30-MAY-07:03 | 16367.78 | 0.00 |
June | 0.00 | 0.00 | 0.861649E+10 | 0.832129E+10 | 21890.62 | 19-JUN-07:02 | 19121.38 | 0.00 |
July | 0.00 | 0.00 | 0.101309E+11 | 0.836950E+10 | 23470.65 | 18-JUL-07:02 | 13214.68 | 0.00 |
August | 0.00 | 0.00 | 0.894351E+10 | 0.784986E+10 | 23443.62 | 03-AUG-07:02 | 13566.94 | 0.00 |
September | 0.00 | 0.00 | 0.767761E+10 | 0.670610E+10 | 22993.37 | 23-SEP-07:02 | 13570.87 | 0.00 |
October | 0.00 | 0.00 | 0.344997E+10 | 0.309660E+10 | 21468.72 | 02-OCT-07:02 | 18737.73 | 0.00 |
November | 0.00 | 0.00 | 0.252833E+09 | 0.249792E+09 | 4181.58 | 09-NOV-14:00 | 4181.58 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.481010E+11 | 0.434509E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.101309E+11 | 0.836950E+10 | 23470.65 | 19121.38 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8 COOLING COIL
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 73029395.06 | 73029395.06 | 2067.52 | 20-FEB-15:40 | 2067.52 | 0.00 |
March | 0.00 | 0.00 | 0.268579E+09 | 0.268579E+09 | 3162.19 | 22-MAR-13:00 | 3162.19 | 0.00 |
April | 0.00 | 0.00 | 0.271724E+10 | 0.270856E+10 | 7662.28 | 21-APR-14:40 | 7662.28 | 0.00 |
May | 0.00 | 0.00 | 0.583450E+10 | 0.567117E+10 | 15856.87 | 30-MAY-07:03 | 15856.87 | 0.00 |
June | 0.00 | 0.00 | 0.856619E+10 | 0.827040E+10 | 21804.43 | 19-JUN-07:02 | 19004.99 | 0.00 |
July | 0.00 | 0.00 | 0.100830E+11 | 0.832106E+10 | 23378.44 | 18-JUL-07:02 | 13138.81 | 0.00 |
August | 0.00 | 0.00 | 0.889976E+10 | 0.780497E+10 | 23351.61 | 03-AUG-07:02 | 13488.47 | 0.00 |
September | 0.00 | 0.00 | 0.763402E+10 | 0.666209E+10 | 22902.76 | 23-SEP-07:02 | 13494.18 | 0.00 |
October | 0.00 | 0.00 | 0.340709E+10 | 0.305579E+10 | 21384.01 | 02-OCT-07:02 | 18624.58 | 0.00 |
November | 0.00 | 0.00 | 0.239310E+09 | 0.236322E+09 | 4100.89 | 09-NOV-14:00 | 4100.89 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.477227E+11 | 0.430720E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.100830E+11 | 0.832106E+10 | 23378.44 | 19004.99 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9 COOLING COIL
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 2.96 | 2.96 | 0.00 | 03-JAN-15:00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 56189531.07 | 56189531.07 | 1874.81 | 20-FEB-15:30 | 1874.81 | 0.00 |
March | 0.00 | 0.00 | 0.223384E+09 | 0.223384E+09 | 2924.25 | 22-MAR-13:00 | 2924.25 | 0.00 |
April | 0.00 | 0.00 | 0.259390E+10 | 0.258592E+10 | 7548.82 | 21-APR-14:40 | 7548.82 | 0.00 |
May | 0.00 | 0.00 | 0.572954E+10 | 0.556989E+10 | 13941.32 | 30-MAY-07:03 | 13941.32 | 0.00 |
June | 0.00 | 0.00 | 0.852725E+10 | 0.823576E+10 | 21828.81 | 19-JUN-07:02 | 19015.46 | 0.00 |
July | 0.00 | 0.00 | 0.100683E+11 | 0.831197E+10 | 23404.98 | 18-JUL-07:02 | 13135.07 | 0.00 |
August | 0.00 | 0.00 | 0.889641E+10 | 0.780668E+10 | 23378.70 | 03-AUG-07:02 | 13492.15 | 0.00 |
September | 0.00 | 0.00 | 0.761640E+10 | 0.664801E+10 | 22929.50 | 23-SEP-07:02 | 13499.17 | 0.00 |
October | 0.00 | 0.00 | 0.332513E+10 | 0.298302E+10 | 21408.49 | 02-OCT-07:02 | 18638.16 | 0.00 |
November | 0.00 | 0.00 | 0.212165E+09 | 0.209528E+09 | 3955.02 | 09-NOV-14:00 | 3955.02 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.472486E+11 | 0.426304E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.100683E+11 | 0.831197E+10 | 23404.98 | 19015.46 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10 COOLING COIL
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 38131157.32 | 38131157.32 | 1726.20 | 20-FEB-15:30 | 1726.20 | 0.00 |
March | 0.00 | 0.00 | 0.189500E+09 | 0.189500E+09 | 2945.08 | 22-MAR-13:00 | 2945.08 | 0.00 |
April | 0.00 | 0.00 | 0.273865E+10 | 0.273145E+10 | 8039.55 | 21-APR-14:20 | 8039.55 | 0.00 |
May | 0.00 | 0.00 | 0.627523E+10 | 0.610635E+10 | 10891.93 | 30-MAY-07:03 | 10891.93 | 0.00 |
June | 0.00 | 0.00 | 0.957518E+10 | 0.925909E+10 | 24110.47 | 19-JUN-07:02 | 20594.30 | 0.00 |
July | 0.00 | 0.00 | 0.114072E+11 | 0.948003E+10 | 25794.52 | 18-JUL-07:02 | 14213.10 | 0.00 |
August | 0.00 | 0.00 | 0.102015E+11 | 0.899840E+10 | 25757.82 | 03-AUG-07:02 | 14713.31 | 0.00 |
September | 0.00 | 0.00 | 0.876169E+10 | 0.768303E+10 | 25274.59 | 23-SEP-07:02 | 14647.29 | 0.00 |
October | 0.00 | 0.00 | 0.363485E+10 | 0.327524E+10 | 23584.30 | 02-OCT-07:02 | 20440.21 | 0.00 |
November | 0.00 | 0.00 | 0.207890E+09 | 0.205581E+09 | 4204.08 | 09-NOV-14:00 | 4204.08 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.530297E+11 | 0.479668E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.114072E+11 | 0.948003E+10 | 25794.52 | 20594.30 | 0.00 |
Report: FanReportMonthly
For: PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.192020E+10 | 0.42 | 2561.22 | 05-JAN-08:61 | 1.02 |
February | 0.171711E+10 | 0.42 | 2561.22 | 01-FEB-08:61 | 1.01 |
March | 0.188391E+10 | 0.42 | 2561.22 | 01-MAR-08:61 | 1.01 |
April | 0.180006E+10 | 0.42 | 1115.52 | 11-APR-08:13 | 0.65 |
May | 0.185899E+10 | 0.41 | 1722.62 | 31-MAY-07:03 | 0.83 |
June | 0.182638E+10 | 0.42 | 2561.22 | 07-JUN-07:02 | 1.01 |
July | 0.187408E+10 | 0.41 | 2561.22 | 01-JUL-07:02 | 1.00 |
August | 0.187097E+10 | 0.41 | 2561.22 | 01-AUG-07:02 | 1.00 |
September | 0.180574E+10 | 0.41 | 2561.22 | 03-SEP-07:02 | 1.00 |
October | 0.185921E+10 | 0.41 | 2561.22 | 02-OCT-07:02 | 1.00 |
November | 0.181132E+10 | 0.42 | 2561.22 | 28-NOV-08:61 | 1.01 |
December | 0.195340E+10 | 0.43 | 2561.22 | 04-DEC-08:61 | 1.01 |
Annual Sum or Average | 0.221814E+11 | 0.42 | |||
Minimum of Months | 0.171711E+10 | 0.41 | 1115.52 | 0.65 | |
Maximum of Months | 0.195340E+10 | 0.43 | 2561.22 | 1.02 |
Report: FanReportMonthly
For: PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.781497E+09 | 0.38 | 1383.93 | 27-JAN-08:61 | 1.05 |
February | 0.759664E+09 | 0.40 | 1383.93 | 02-FEB-08:61 | 1.05 |
March | 0.898970E+09 | 0.42 | 1383.93 | 02-MAR-08:61 | 1.05 |
April | 0.858751E+09 | 0.41 | 553.57 | 02-APR-10:40 | 0.64 |
May | 0.867424E+09 | 0.42 | 1094.98 | 31-MAY-07:03 | 0.94 |
June | 0.867444E+09 | 0.44 | 1383.93 | 03-JUN-07:02 | 1.04 |
July | 0.902077E+09 | 0.44 | 1383.93 | 01-JUL-07:02 | 1.04 |
August | 0.896136E+09 | 0.43 | 1383.93 | 01-AUG-07:02 | 1.03 |
September | 0.856273E+09 | 0.41 | 1383.93 | 03-SEP-07:02 | 1.03 |
October | 0.930969E+09 | 0.41 | 1383.93 | 02-OCT-07:02 | 1.04 |
November | 0.874375E+09 | 0.42 | 1109.52 | 28-NOV-08:61 | 0.94 |
December | 0.783661E+09 | 0.37 | 1383.93 | 27-DEC-08:61 | 1.05 |
Annual Sum or Average | 0.102772E+11 | 0.41 | |||
Minimum of Months | 0.759664E+09 | 0.37 | 553.57 | 0.64 | |
Maximum of Months | 0.930969E+09 | 0.44 | 1383.93 | 1.05 |
Report: FanReportMonthly
For: PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.842698E+09 | 0.35 | 1422.63 | 28-JAN-07:02 | 1.05 |
February | 0.754634E+09 | 0.35 | 1415.52 | 03-FEB-07:02 | 1.05 |
March | 0.844642E+09 | 0.35 | 1344.70 | 02-MAR-07:02 | 1.03 |
April | 0.798957E+09 | 0.34 | 583.41 | 11-APR-07:30 | 0.65 |
May | 0.831946E+09 | 0.35 | 1400.82 | 31-MAY-06:02 | 1.04 |
June | 0.817304E+09 | 0.35 | 1422.63 | 03-JUN-06:02 | 1.04 |
July | 0.824271E+09 | 0.34 | 1422.63 | 01-JUL-06:02 | 1.04 |
August | 0.842908E+09 | 0.35 | 1422.63 | 01-AUG-06:02 | 1.03 |
September | 0.800632E+09 | 0.34 | 1422.63 | 02-SEP-06:02 | 1.03 |
October | 0.823848E+09 | 0.34 | 1422.63 | 02-OCT-06:02 | 1.04 |
November | 0.803893E+09 | 0.34 | 1065.46 | 28-NOV-07:02 | 0.91 |
December | 0.848053E+09 | 0.35 | 1422.63 | 27-DEC-07:01 | 1.05 |
Annual Sum or Average | 0.983379E+10 | 0.35 | |||
Minimum of Months | 0.754634E+09 | 0.34 | 583.41 | 0.65 | |
Maximum of Months | 0.848053E+09 | 0.35 | 1422.63 | 1.05 |
Report: FanReportMonthly
For: PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.842039E+09 | 0.35 | 1414.74 | 27-JAN-07:02 | 1.05 |
February | 0.752335E+09 | 0.35 | 1414.74 | 03-FEB-07:02 | 1.05 |
March | 0.841002E+09 | 0.35 | 1414.74 | 02-MAR-07:02 | 1.05 |
April | 0.794537E+09 | 0.34 | 587.66 | 11-APR-07:30 | 0.65 |
May | 0.827357E+09 | 0.35 | 1414.74 | 31-MAY-06:02 | 1.05 |
June | 0.813538E+09 | 0.35 | 1414.74 | 03-JUN-06:02 | 1.04 |
July | 0.820213E+09 | 0.34 | 1414.74 | 01-JUL-06:02 | 1.04 |
August | 0.838393E+09 | 0.35 | 1414.74 | 01-AUG-06:02 | 1.03 |
September | 0.796286E+09 | 0.34 | 1414.74 | 02-SEP-06:02 | 1.03 |
October | 0.819292E+09 | 0.34 | 1414.74 | 02-OCT-06:02 | 1.04 |
November | 0.800249E+09 | 0.35 | 1146.44 | 28-NOV-07:02 | 0.95 |
December | 0.847629E+09 | 0.35 | 1414.74 | 04-DEC-07:02 | 1.05 |
Annual Sum or Average | 0.979287E+10 | 0.35 | |||
Minimum of Months | 0.752335E+09 | 0.34 | 587.66 | 0.65 | |
Maximum of Months | 0.847629E+09 | 0.35 | 1414.74 | 1.05 |
Report: FanReportMonthly
For: PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.846836E+09 | 0.35 | 1413.02 | 27-JAN-07:02 | 1.05 |
February | 0.754818E+09 | 0.35 | 1413.02 | 02-FEB-07:02 | 1.05 |
March | 0.841925E+09 | 0.35 | 1413.02 | 02-MAR-07:02 | 1.05 |
April | 0.793611E+09 | 0.34 | 602.57 | 11-APR-07:30 | 0.66 |
May | 0.826274E+09 | 0.35 | 1298.56 | 31-MAY-06:02 | 1.01 |
June | 0.811165E+09 | 0.35 | 1413.02 | 03-JUN-06:02 | 1.04 |
July | 0.818558E+09 | 0.34 | 1413.02 | 01-JUL-06:02 | 1.04 |
August | 0.837105E+09 | 0.35 | 1413.02 | 01-AUG-06:02 | 1.03 |
September | 0.795116E+09 | 0.34 | 1413.02 | 02-SEP-06:02 | 1.03 |
October | 0.818259E+09 | 0.34 | 1413.02 | 02-OCT-06:02 | 1.04 |
November | 0.800440E+09 | 0.35 | 1233.12 | 28-NOV-07:02 | 0.98 |
December | 0.852844E+09 | 0.35 | 1413.02 | 04-DEC-07:02 | 1.05 |
Annual Sum or Average | 0.979695E+10 | 0.35 | |||
Minimum of Months | 0.754818E+09 | 0.34 | 602.57 | 0.66 | |
Maximum of Months | 0.852844E+09 | 0.35 | 1413.02 | 1.05 |
Report: FanReportMonthly
For: PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.131677E+10 | 0.32 | 2348.77 | 02-JAN-08:61 | 1.01 |
February | 0.116870E+10 | 0.31 | 2348.77 | 01-FEB-08:61 | 1.01 |
March | 0.129796E+10 | 0.32 | 2348.77 | 01-MAR-08:61 | 1.01 |
April | 0.121777E+10 | 0.31 | 1029.96 | 11-APR-08:13 | 0.65 |
May | 0.126860E+10 | 0.31 | 1830.42 | 30-MAY-07:03 | 0.90 |
June | 0.125471E+10 | 0.31 | 2348.77 | 03-JUN-07:02 | 1.00 |
July | 0.126367E+10 | 0.30 | 2348.77 | 01-JUL-07:02 | 1.01 |
August | 0.129020E+10 | 0.31 | 2348.77 | 01-AUG-07:02 | 1.00 |
September | 0.122013E+10 | 0.30 | 2348.77 | 03-SEP-08:62 | 1.00 |
October | 0.125518E+10 | 0.30 | 2348.77 | 02-OCT-07:02 | 1.00 |
November | 0.123269E+10 | 0.31 | 2348.77 | 28-NOV-08:61 | 1.01 |
December | 0.132944E+10 | 0.32 | 2348.77 | 03-DEC-09:01 | 1.01 |
Annual Sum or Average | 0.151158E+11 | 0.31 | |||
Minimum of Months | 0.116870E+10 | 0.30 | 1029.96 | 0.65 | |
Maximum of Months | 0.132944E+10 | 0.32 | 2348.77 | 1.01 |
Report: FanReportMonthly
For: PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.709663E+09 | 0.33 | 1264.42 | 02-JAN-08:61 | 1.04 |
February | 0.629629E+09 | 0.32 | 1264.42 | 01-FEB-08:61 | 1.05 |
March | 0.699089E+09 | 0.33 | 1264.42 | 01-MAR-08:61 | 1.05 |
April | 0.655554E+09 | 0.32 | 552.45 | 11-APR-08:13 | 0.67 |
May | 0.682914E+09 | 0.32 | 941.73 | 30-MAY-07:03 | 0.91 |
June | 0.675594E+09 | 0.32 | 1264.42 | 05-JUN-07:02 | 1.04 |
July | 0.680267E+09 | 0.31 | 1264.42 | 02-JUL-08:62 | 1.03 |
August | 0.694437E+09 | 0.32 | 1264.42 | 01-AUG-07:02 | 1.03 |
September | 0.656680E+09 | 0.31 | 1264.42 | 03-SEP-08:62 | 1.03 |
October | 0.675677E+09 | 0.31 | 1264.42 | 02-OCT-07:02 | 1.04 |
November | 0.663683E+09 | 0.32 | 1264.42 | 28-NOV-08:61 | 1.05 |
December | 0.716339E+09 | 0.33 | 1264.42 | 03-DEC-09:01 | 1.05 |
Annual Sum or Average | 0.813953E+10 | 0.32 | |||
Minimum of Months | 0.629629E+09 | 0.31 | 552.45 | 0.67 | |
Maximum of Months | 0.716339E+09 | 0.33 | 1264.42 | 1.05 |
Report: FanReportMonthly
For: PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.708544E+09 | 0.33 | 1258.58 | 01-JAN-09:01 | 1.05 |
February | 0.628149E+09 | 0.32 | 1258.58 | 01-FEB-08:61 | 1.05 |
March | 0.696760E+09 | 0.33 | 1258.58 | 01-MAR-08:61 | 1.05 |
April | 0.652548E+09 | 0.32 | 558.12 | 11-APR-08:13 | 0.68 |
May | 0.679748E+09 | 0.32 | 906.07 | 30-MAY-07:03 | 0.89 |
June | 0.672433E+09 | 0.32 | 1258.58 | 05-JUN-07:02 | 1.04 |
July | 0.677182E+09 | 0.31 | 1258.58 | 02-JUL-08:62 | 1.03 |
August | 0.691266E+09 | 0.32 | 1258.58 | 01-AUG-07:02 | 1.03 |
September | 0.653614E+09 | 0.31 | 1258.58 | 03-SEP-08:62 | 1.03 |
October | 0.672547E+09 | 0.31 | 1258.58 | 02-OCT-07:02 | 1.04 |
November | 0.661063E+09 | 0.32 | 1258.58 | 27-NOV-08:61 | 1.05 |
December | 0.715141E+09 | 0.33 | 1258.58 | 03-DEC-09:01 | 1.05 |
Annual Sum or Average | 0.810899E+10 | 0.32 | |||
Minimum of Months | 0.628149E+09 | 0.31 | 558.12 | 0.68 | |
Maximum of Months | 0.715141E+09 | 0.33 | 1258.58 | 1.05 |
Report: FanReportMonthly
For: PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.716214E+09 | 0.33 | 1260.41 | 01-JAN-09:01 | 1.05 |
February | 0.633747E+09 | 0.33 | 1260.41 | 01-FEB-08:61 | 1.05 |
March | 0.700919E+09 | 0.33 | 1260.41 | 01-MAR-08:61 | 1.05 |
April | 0.653638E+09 | 0.32 | 591.84 | 11-APR-08:10 | 0.70 |
May | 0.680697E+09 | 0.32 | 769.37 | 30-MAY-07:03 | 0.82 |
June | 0.673091E+09 | 0.32 | 1260.41 | 05-JUN-07:02 | 1.04 |
July | 0.678115E+09 | 0.31 | 1260.41 | 02-JUL-08:62 | 1.03 |
August | 0.692342E+09 | 0.32 | 1260.41 | 01-AUG-07:02 | 1.03 |
September | 0.654456E+09 | 0.31 | 1260.41 | 03-SEP-08:62 | 1.03 |
October | 0.673500E+09 | 0.31 | 1260.41 | 02-OCT-07:02 | 1.04 |
November | 0.663566E+09 | 0.32 | 1260.41 | 27-NOV-08:61 | 1.05 |
December | 0.722539E+09 | 0.33 | 1260.41 | 02-DEC-08:61 | 1.05 |
Annual Sum or Average | 0.814282E+10 | 0.32 | |||
Minimum of Months | 0.633747E+09 | 0.31 | 591.84 | 0.70 | |
Maximum of Months | 0.722539E+09 | 0.33 | 1260.41 | 1.05 |
Report: FanReportMonthly
For: PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.829034E+09 | 0.33 | 1433.88 | 01-JAN-09:01 | 1.05 |
February | 0.732576E+09 | 0.33 | 1433.88 | 01-FEB-08:61 | 1.05 |
March | 0.806343E+09 | 0.33 | 1433.88 | 01-MAR-08:61 | 1.05 |
April | 0.744509E+09 | 0.32 | 1236.63 | 12-APR-07:02 | 0.98 |
May | 0.774295E+09 | 0.32 | 573.55 | 03-MAY-10:40 | 0.63 |
June | 0.766156E+09 | 0.32 | 1433.88 | 08-JUN-07:02 | 1.04 |
July | 0.774597E+09 | 0.31 | 1433.88 | 02-JUL-08:62 | 1.03 |
August | 0.790770E+09 | 0.32 | 1433.88 | 01-AUG-07:02 | 1.03 |
September | 0.744427E+09 | 0.31 | 1433.88 | 03-SEP-08:62 | 1.03 |
October | 0.766145E+09 | 0.31 | 1433.88 | 02-OCT-07:02 | 1.04 |
November | 0.758949E+09 | 0.32 | 1433.88 | 27-NOV-08:61 | 1.05 |
December | 0.833293E+09 | 0.33 | 1433.88 | 01-DEC-08:62 | 1.05 |
Annual Sum or Average | 0.932109E+10 | 0.32 | |||
Minimum of Months | 0.732576E+09 | 0.31 | 573.55 | 0.63 | |
Maximum of Months | 0.833293E+09 | 0.33 | 1433.88 | 1.05 |
Report: ZoneTemperatureOscillationReportMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.192026E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.180670E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.213322E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.408536E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.645990E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.861938E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.952038E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.858198E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.729685E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.435669E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.201193E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.195340E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.587461E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.180670E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.952038E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.785299E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.839397E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.109837E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.225240E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.337246E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.430681E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.473634E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.431610E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.378932E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.238944E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.101630E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.784935E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.296872E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.784935E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.473634E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_3:3
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.842939E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.801364E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.986584E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.172259E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.265605E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.349578E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.378954E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.345760E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.300845E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.186171E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.911177E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.848053E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.243818E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.801364E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.378954E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_4:4
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.842071E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.792905E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.971878E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.170712E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.265170E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.349989E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.379268E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.346098E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.300871E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.185146E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.901314E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.847629E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.243283E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.792905E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.379268E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_5:5
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.846836E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.787044E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.953461E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.166558E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.260472E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.345103E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.374529E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.341427E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.296477E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.181478E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.888776E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.852844E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.239894E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.787044E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.374529E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_6:6
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.131677E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.121757E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.146826E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.274438E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.448735E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.609438E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.654623E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.598741E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.518250E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.302926E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.137127E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.132944E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.407748E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.121757E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.654623E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_7:7
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.709663E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.651872E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.778825E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.142184E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.230932E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.312293E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.335194E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.306941E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.266002E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.157038E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.731221E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.716339E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.210938E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.651872E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.335194E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_8:8
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.708544E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.648500E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.771167E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.140497E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.229192E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.310613E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.333647E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.305486E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.264587E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.155667E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.725064E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.715141E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.209653E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.648500E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.333647E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_9:9
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.716214E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.649489E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.763163E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.137523E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.226767E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.309796E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.333486E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.305546E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.264275E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.153801E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.720477E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.722539E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.208838E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.649489E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.333486E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_10:10
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.829034E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.743333E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.859625E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.150943E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.251387E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.348038E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.377617E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.348415E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.301520E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.171079E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.814811E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.833293E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.235701E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.743333E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.377617E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.192020E+10 | 222235.51 | 0.234380E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.171711E+10 | 0.322098E+09 | 0.134759E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.188391E+10 | 0.896546E+09 | 0.674417E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.180006E+10 | 0.821102E+10 | 9153973.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.185899E+10 | 0.164774E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.182638E+10 | 0.236303E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.187408E+10 | 0.285184E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.187097E+10 | 0.247931E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.180574E+10 | 0.208017E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.185921E+10 | 0.950952E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.181132E+10 | 0.743345E+09 | 0.581040E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.195340E+10 | 0.00 | 0.332670E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.221814E+11 | 0.133904E+12 | 0.828271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.171711E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.195340E+10 | 0.285184E+11 | 0.332670E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.781497E+09 | 13806934.15 | 0.307497E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.759664E+09 | 0.292352E+09 | 0.139842E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.898970E+09 | 0.736187E+09 | 74587900.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.858751E+09 | 0.501389E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.867424E+09 | 0.904045E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.867444E+09 | 0.121098E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.902077E+09 | 0.144374E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.896136E+09 | 0.127199E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.856273E+09 | 0.110763E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.930969E+09 | 0.552702E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.874375E+09 | 0.538129E+09 | 80745960.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.783661E+09 | 4639622.01 | 0.555342E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.102772E+11 | 0.715099E+11 | 0.115801E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.759664E+09 | 4639622.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.930969E+09 | 0.144374E+11 | 0.555342E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_3:3
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.842698E+09 | 859508.05 | 0.699585E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.754634E+09 | 0.170975E+09 | 0.326650E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.844642E+09 | 0.521828E+09 | 0.172380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.798957E+09 | 0.337830E+10 | 345257.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.831946E+09 | 0.663396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.817304E+09 | 0.945919E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.824271E+09 | 0.112281E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.842908E+09 | 0.983553E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.800632E+09 | 0.844658E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.823848E+09 | 0.400879E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.803893E+09 | 0.404262E+09 | 0.180495E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.848053E+09 | 0.00 | 0.104457E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.983379E+10 | 0.540884E+11 | 0.242403E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.754634E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.848053E+09 | 0.112281E+11 | 0.104457E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_4:4
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.842039E+09 | 114443.84 | 0.843025E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.752335E+09 | 0.147783E+09 | 0.394022E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.841002E+09 | 0.479799E+09 | 0.209693E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.794537E+09 | 0.333591E+10 | 697725.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.827357E+09 | 0.664207E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.813538E+09 | 0.950353E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.820213E+09 | 0.112764E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.838393E+09 | 0.988357E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.796286E+09 | 0.847785E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.819292E+09 | 0.398853E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.800249E+09 | 0.380445E+09 | 0.209376E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.847629E+09 | 0.00 | 0.119613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.979287E+10 | 0.541160E+11 | 0.285295E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.752335E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.847629E+09 | 0.112764E+11 | 0.119613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_5:5
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.846836E+09 | 0.00 | 0.105499E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.754818E+09 | 0.116587E+09 | 0.517860E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.841925E+09 | 0.406420E+09 | 0.280671E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.793611E+09 | 0.317006E+10 | 2241779.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.826274E+09 | 0.644788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.811165E+09 | 0.930682E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.818558E+09 | 0.110653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.837105E+09 | 0.967842E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.795116E+09 | 0.828393E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.818259E+09 | 0.383613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.800440E+09 | 0.331354E+09 | 0.251793E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.852844E+09 | 0.00 | 0.142325E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.979695E+10 | 0.526429E+11 | 0.353081E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.754818E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.852844E+09 | 0.110653E+11 | 0.142325E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_6:6
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.131677E+10 | 0.00 | 0.241272E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.116870E+10 | 0.173091E+09 | 0.125658E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.129796E+10 | 0.606515E+09 | 0.626744E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.121777E+10 | 0.542990E+10 | 6412948.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.126860E+10 | 0.114598E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.125471E+10 | 0.167586E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.126367E+10 | 0.197051E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.129020E+10 | 0.173961E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.122013E+10 | 0.149322E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.125518E+10 | 0.672450E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.123269E+10 | 0.509912E+09 | 0.587354E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.132944E+10 | 0.00 | 0.316941E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.151158E+11 | 0.936957E+11 | 0.805921E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.116870E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.132944E+10 | 0.197051E+11 | 0.316941E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_7:7
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.709663E+09 | 0.00 | 0.127514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.629629E+09 | 79989954.70 | 0.666384E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.699089E+09 | 0.288438E+09 | 0.336630E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.655554E+09 | 0.277151E+10 | 2866442.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.682914E+09 | 0.588970E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.675594E+09 | 0.861649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.680267E+09 | 0.101309E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.694437E+09 | 0.894351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.656680E+09 | 0.767761E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.675677E+09 | 0.344997E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.663683E+09 | 0.252833E+09 | 0.306334E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.716339E+09 | 0.00 | 0.166032E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.813953E+10 | 0.481010E+11 | 0.424767E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.629629E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.716339E+09 | 0.101309E+11 | 0.166032E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_8:8
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.708544E+09 | 0.00 | 0.135120E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.628149E+09 | 73029395.06 | 0.717366E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.696760E+09 | 0.268579E+09 | 0.369093E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.652548E+09 | 0.271724E+10 | 3747965.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.679748E+09 | 0.583450E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.672433E+09 | 0.856619E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.677182E+09 | 0.100830E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.691266E+09 | 0.889976E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.653614E+09 | 0.763402E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.672547E+09 | 0.340709E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.661063E+09 | 0.239310E+09 | 0.321927E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.715141E+09 | 0.00 | 0.173315E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.810899E+10 | 0.477227E+11 | 0.449648E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.628149E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.715141E+09 | 0.100830E+11 | 0.173315E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_9:9
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.716214E+09 | 2.96 | 0.160085E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.633747E+09 | 56189531.07 | 0.893254E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.700919E+09 | 0.223384E+09 | 0.487094E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.653638E+09 | 0.259390E+10 | 9093637.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.680697E+09 | 0.572954E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.673091E+09 | 0.852725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.678115E+09 | 0.100683E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.692342E+09 | 0.889641E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.654456E+09 | 0.761640E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.673500E+09 | 0.332513E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.663566E+09 | 0.212165E+09 | 0.379961E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.722539E+09 | 0.00 | 0.197272E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.814282E+10 | 0.472486E+11 | 0.534298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.633747E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.722539E+09 | 0.100683E+11 | 0.197272E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_10:10
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.829034E+09 | 0.00 | 0.229611E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.732576E+09 | 38131157.32 | 0.141445E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.806343E+09 | 0.189500E+09 | 0.867040E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.744509E+09 | 0.273865E+10 | 43226870.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.774295E+09 | 0.627523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.766156E+09 | 0.957518E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.774597E+09 | 0.114072E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.790770E+09 | 0.102015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.744427E+09 | 0.876169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.766145E+09 | 0.363485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.758949E+09 | 0.207890E+09 | 0.569518E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.833293E+09 | 0.00 | 0.260185E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.932109E+10 | 0.530297E+11 | 0.779220E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.732576E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.833293E+09 | 0.114072E+11 | 0.260185E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.192020E+10 | 0.00 | 0.00 | 0.00 | 63714.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.171711E+10 | 0.00 | 0.00 | 0.00 | 89593958.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.188391E+10 | 0.00 | 0.00 | 0.00 | 0.249304E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.180006E+10 | 0.00 | 0.00 | 0.00 | 0.228530E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.185899E+10 | 0.00 | 0.00 | 0.00 | 0.460091E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.182638E+10 | 0.00 | 0.00 | 0.00 | 0.679300E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.187408E+10 | 0.00 | 0.00 | 0.00 | 0.764630E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.187097E+10 | 0.00 | 0.00 | 0.00 | 0.671101E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.180574E+10 | 0.00 | 0.00 | 0.00 | 0.549112E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.185921E+10 | 0.00 | 0.00 | 0.00 | 0.249748E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.181132E+10 | 0.00 | 0.00 | 0.00 | 0.200618E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.195340E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.221814E+11 | 0.00 | 0.00 | 0.00 | 0.365647E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.171711E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.195340E+10 | 0.00 | 0.00 | 0.00 | 0.764630E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.781497E+09 | 0.00 | 0.00 | 0.00 | 3801856.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.759664E+09 | 0.00 | 0.00 | 0.00 | 79733810.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.898970E+09 | 0.00 | 0.00 | 0.00 | 0.199404E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.858751E+09 | 0.00 | 0.00 | 0.00 | 0.139365E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.867424E+09 | 0.00 | 0.00 | 0.00 | 0.250504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.867444E+09 | 0.00 | 0.00 | 0.00 | 0.343937E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.902077E+09 | 0.00 | 0.00 | 0.00 | 0.383427E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.896136E+09 | 0.00 | 0.00 | 0.00 | 0.341996E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.856273E+09 | 0.00 | 0.00 | 0.00 | 0.293304E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.930969E+09 | 0.00 | 0.00 | 0.00 | 0.145847E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.874375E+09 | 0.00 | 0.00 | 0.00 | 0.141926E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.783661E+09 | 0.00 | 0.00 | 0.00 | 1273634.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.102772E+11 | 0.00 | 0.00 | 0.00 | 0.194099E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.759664E+09 | 0.00 | 0.00 | 0.00 | 1273634.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.930969E+09 | 0.00 | 0.00 | 0.00 | 0.383427E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_3:3
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.842698E+09 | 0.00 | 0.00 | 0.00 | 241011.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.754634E+09 | 0.00 | 0.00 | 0.00 | 46729564.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.844642E+09 | 0.00 | 0.00 | 0.00 | 0.141941E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.798957E+09 | 0.00 | 0.00 | 0.00 | 0.923636E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.831946E+09 | 0.00 | 0.00 | 0.00 | 0.182410E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.817304E+09 | 0.00 | 0.00 | 0.00 | 0.267847E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.824271E+09 | 0.00 | 0.00 | 0.00 | 0.296526E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.842908E+09 | 0.00 | 0.00 | 0.00 | 0.261469E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.800632E+09 | 0.00 | 0.00 | 0.00 | 0.220781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.823848E+09 | 0.00 | 0.00 | 0.00 | 0.103786E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.803893E+09 | 0.00 | 0.00 | 0.00 | 0.107284E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.848053E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.983379E+10 | 0.00 | 0.00 | 0.00 | 0.145480E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.754634E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.848053E+09 | 0.00 | 0.00 | 0.00 | 0.296526E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_4:4
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.842039E+09 | 0.00 | 0.00 | 0.00 | 32248.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.752335E+09 | 0.00 | 0.00 | 0.00 | 40570207.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.841002E+09 | 0.00 | 0.00 | 0.00 | 0.130876E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.794537E+09 | 0.00 | 0.00 | 0.00 | 0.912586E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.827357E+09 | 0.00 | 0.00 | 0.00 | 0.182434E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.813538E+09 | 0.00 | 0.00 | 0.00 | 0.268635E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.820213E+09 | 0.00 | 0.00 | 0.00 | 0.297247E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.838393E+09 | 0.00 | 0.00 | 0.00 | 0.262259E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.796286E+09 | 0.00 | 0.00 | 0.00 | 0.221242E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.819292E+09 | 0.00 | 0.00 | 0.00 | 0.103217E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.800249E+09 | 0.00 | 0.00 | 0.00 | 0.101065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.847629E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.979287E+10 | 0.00 | 0.00 | 0.00 | 0.145355E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.752335E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.847629E+09 | 0.00 | 0.00 | 0.00 | 0.297247E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_5:5
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.846836E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.754818E+09 | 0.00 | 0.00 | 0.00 | 32226295.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.841925E+09 | 0.00 | 0.00 | 0.00 | 0.111536E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.793611E+09 | 0.00 | 0.00 | 0.00 | 0.871969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.826274E+09 | 0.00 | 0.00 | 0.00 | 0.177844E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.811165E+09 | 0.00 | 0.00 | 0.00 | 0.263987E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.818558E+09 | 0.00 | 0.00 | 0.00 | 0.292673E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.837105E+09 | 0.00 | 0.00 | 0.00 | 0.257717E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.795116E+09 | 0.00 | 0.00 | 0.00 | 0.216965E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.818259E+09 | 0.00 | 0.00 | 0.00 | 0.996526E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.800440E+09 | 0.00 | 0.00 | 0.00 | 88335863.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.852844E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.979695E+10 | 0.00 | 0.00 | 0.00 | 0.141925E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.754818E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.852844E+09 | 0.00 | 0.00 | 0.00 | 0.292673E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_6:6
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.131677E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.116870E+10 | 0.00 | 0.00 | 0.00 | 48872361.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.129796E+10 | 0.00 | 0.00 | 0.00 | 0.170296E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.121777E+10 | 0.00 | 0.00 | 0.00 | 0.152661E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.126860E+10 | 0.00 | 0.00 | 0.00 | 0.321875E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.125471E+10 | 0.00 | 0.00 | 0.00 | 0.483966E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.126367E+10 | 0.00 | 0.00 | 0.00 | 0.528256E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.129020E+10 | 0.00 | 0.00 | 0.00 | 0.469721E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.122013E+10 | 0.00 | 0.00 | 0.00 | 0.396237E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.125518E+10 | 0.00 | 0.00 | 0.00 | 0.177408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.123269E+10 | 0.00 | 0.00 | 0.00 | 0.138585E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.132944E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.151158E+11 | 0.00 | 0.00 | 0.00 | 0.256590E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.116870E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.132944E+10 | 0.00 | 0.00 | 0.00 | 0.528256E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_7:7
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.709663E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.629629E+09 | 0.00 | 0.00 | 0.00 | 22243067.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.699089E+09 | 0.00 | 0.00 | 0.00 | 79735979.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.655554E+09 | 0.00 | 0.00 | 0.00 | 0.766284E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.682914E+09 | 0.00 | 0.00 | 0.00 | 0.162641E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.675594E+09 | 0.00 | 0.00 | 0.00 | 0.244734E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.680267E+09 | 0.00 | 0.00 | 0.00 | 0.267167E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.694437E+09 | 0.00 | 0.00 | 0.00 | 0.237497E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.656680E+09 | 0.00 | 0.00 | 0.00 | 0.200334E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.675677E+09 | 0.00 | 0.00 | 0.00 | 0.894705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.663683E+09 | 0.00 | 0.00 | 0.00 | 67537901.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.716339E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.813953E+10 | 0.00 | 0.00 | 0.00 | 0.129542E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.629629E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.716339E+09 | 0.00 | 0.00 | 0.00 | 0.267167E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_8:8
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.708544E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.628149E+09 | 0.00 | 0.00 | 0.00 | 20351022.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.696760E+09 | 0.00 | 0.00 | 0.00 | 74407109.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.652548E+09 | 0.00 | 0.00 | 0.00 | 0.752425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.679748E+09 | 0.00 | 0.00 | 0.00 | 0.161217E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.672433E+09 | 0.00 | 0.00 | 0.00 | 0.243370E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.677182E+09 | 0.00 | 0.00 | 0.00 | 0.265929E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.691266E+09 | 0.00 | 0.00 | 0.00 | 0.236359E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.653614E+09 | 0.00 | 0.00 | 0.00 | 0.199226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.672547E+09 | 0.00 | 0.00 | 0.00 | 0.884127E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.661063E+09 | 0.00 | 0.00 | 0.00 | 64001668.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.715141E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.810899E+10 | 0.00 | 0.00 | 0.00 | 0.128563E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.628149E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.715141E+09 | 0.00 | 0.00 | 0.00 | 0.265929E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_9:9
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.716214E+09 | 0.00 | 0.00 | 0.00 | 0.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.633747E+09 | 0.00 | 0.00 | 0.00 | 15741933.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.700919E+09 | 0.00 | 0.00 | 0.00 | 62244406.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.653638E+09 | 0.00 | 0.00 | 0.00 | 0.721590E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.680697E+09 | 0.00 | 0.00 | 0.00 | 0.158697E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.673091E+09 | 0.00 | 0.00 | 0.00 | 0.242487E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.678115E+09 | 0.00 | 0.00 | 0.00 | 0.265674E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.692342E+09 | 0.00 | 0.00 | 0.00 | 0.236312E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.654456E+09 | 0.00 | 0.00 | 0.00 | 0.198829E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.673500E+09 | 0.00 | 0.00 | 0.00 | 0.864510E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.663566E+09 | 0.00 | 0.00 | 0.00 | 56910645.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.722539E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.814282E+10 | 0.00 | 0.00 | 0.00 | 0.127410E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.633747E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.722539E+09 | 0.00 | 0.00 | 0.00 | 0.265674E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_10:10
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.829034E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.732576E+09 | 0.00 | 0.00 | 0.00 | 10757217.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.806343E+09 | 0.00 | 0.00 | 0.00 | 53282441.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.744509E+09 | 0.00 | 0.00 | 0.00 | 0.764918E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.774295E+09 | 0.00 | 0.00 | 0.00 | 0.173958E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.766156E+09 | 0.00 | 0.00 | 0.00 | 0.271423E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.774597E+09 | 0.00 | 0.00 | 0.00 | 0.300157E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.790770E+09 | 0.00 | 0.00 | 0.00 | 0.269338E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.744427E+09 | 0.00 | 0.00 | 0.00 | 0.227077E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.766145E+09 | 0.00 | 0.00 | 0.00 | 0.944643E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.758949E+09 | 0.00 | 0.00 | 0.00 | 55862539.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.833293E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.932109E+10 | 0.00 | 0.00 | 0.00 | 0.142490E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.732576E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.833293E+09 | 0.00 | 0.00 | 0.00 | 0.300157E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.837617E+10 | 0.00 | 0.00 | 284200.45 | 0.00 | 0.576285E+09 | 0.389487E+09 | 0.00 | 0.54 |
February | 0.575532E+10 | 0.00 | 0.00 | 2052580.56 | 0.00 | 0.303377E+09 | 0.148782E+10 | 0.00 | 0.65 |
March | 0.439262E+10 | 257606.23 | 0.00 | 4318148.87 | 0.00 | 0.185610E+09 | 0.301494E+10 | 0.00 | 0.75 |
April | 0.794088E+09 | 0.492813E+09 | 0.00 | 12014708.07 | 775378.70 | 0.00 | 0.312782E+10 | 0.00 | 0.86 |
May | 69124796.59 | 0.201582E+10 | 0.00 | 9464099.92 | 380893.64 | 0.00 | 0.145139E+10 | 0.00 | 0.78 |
June | 466777.63 | 0.447744E+10 | 0.00 | 2038573.20 | 0.00 | 0.00 | 0.163668E+09 | 0.00 | 0.63 |
July | 0.00 | 0.710635E+10 | 0.00 | 511584.19 | 18964495.72 | 0.00 | 26628591.04 | 0.00 | 0.60 |
August | 119380.94 | 0.461272E+10 | 0.00 | 2599702.98 | 4895016.77 | 0.00 | 0.434899E+09 | 0.00 | 0.73 |
September | 3862102.11 | 0.316035E+10 | 0.00 | 9813250.68 | 735756.83 | 0.00 | 0.142871E+10 | 0.00 | 0.86 |
October | 0.408506E+09 | 0.732897E+09 | 0.00 | 18699333.54 | 0.00 | 0.00 | 0.578928E+10 | 0.00 | 1.06 |
November | 0.462289E+10 | 0.00 | 0.00 | 6283426.26 | 0.00 | 93990512.67 | 0.465715E+10 | 0.00 | 0.76 |
December | 0.914505E+10 | 0.00 | 0.00 | 15040.25 | 0.00 | 0.937573E+09 | 38350690.13 | 0.00 | 0.53 |
Annual Sum or Average | 0.335682E+11 | 0.225986E+11 | 0.00 | 68094648.96 | 25751541.66 | 0.209684E+10 | 0.220101E+11 | 0.00 | 0.73 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 15040.25 | 0.00 | 0.00 | 26628591.04 | 0.00 | 0.53 |
Maximum of Months | 0.914505E+10 | 0.710635E+10 | 0.00 | 18699333.54 | 18964495.72 | 0.937573E+09 | 0.578928E+10 | 0.00 | 1.06 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.303508E+10 | 0.00 | 0.00 | 666590.08 | 0.00 | 46196358.61 | 0.611359E+09 | 0.00 | 0.43 |
February | 0.196926E+10 | 0.00 | 0.00 | 1833754.70 | 0.00 | 26050113.48 | 0.133238E+10 | 0.00 | 0.61 |
March | 0.119348E+10 | 149904.20 | 0.00 | 3758061.95 | 0.00 | 21560594.36 | 0.251016E+10 | 0.00 | 0.78 |
April | 0.185981E+09 | 0.235873E+09 | 0.00 | 5624299.57 | 0.00 | 0.00 | 0.179624E+10 | 0.00 | 0.77 |
May | 9075610.68 | 0.948738E+09 | 0.00 | 4033070.82 | 184977.62 | 0.00 | 0.654201E+09 | 0.00 | 0.64 |
June | 0.00 | 0.198394E+10 | 0.00 | 776354.06 | 0.00 | 0.00 | 65181710.05 | 0.00 | 0.51 |
July | 0.00 | 0.322064E+10 | 0.00 | 0.00 | 23294272.37 | 0.00 | 0.00 | 0.00 | 0.49 |
August | 0.00 | 0.210482E+10 | 0.00 | 1016530.18 | 6812486.52 | 0.00 | 0.165781E+09 | 0.00 | 0.61 |
September | 506452.06 | 0.158436E+10 | 0.00 | 3220876.35 | 2440222.36 | 0.00 | 0.530623E+09 | 0.00 | 0.69 |
October | 89452788.69 | 0.370826E+09 | 0.00 | 8489300.75 | 209197.61 | 0.00 | 0.298856E+10 | 0.00 | 1.01 |
November | 0.112764E+10 | 0.00 | 0.00 | 4947824.85 | 0.00 | 4282048.83 | 0.350380E+10 | 0.00 | 0.79 |
December | 0.328585E+10 | 0.00 | 0.00 | 338090.10 | 0.00 | 0.164296E+09 | 0.358201E+09 | 0.00 | 0.40 |
Annual Sum or Average | 0.108963E+11 | 0.104493E+11 | 0.00 | 34704753.40 | 32941156.49 | 0.262385E+09 | 0.145165E+11 | 0.00 | 0.64 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.40 |
Maximum of Months | 0.328585E+10 | 0.322064E+10 | 0.00 | 8489300.75 | 23294272.37 | 0.164296E+09 | 0.350380E+10 | 0.00 | 1.01 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.306911E+10 | 0.00 | 0.00 | 213592.14 | 0.00 | 0.209590E+09 | 0.246601E+09 | 0.00 | 0.43 |
February | 0.216536E+10 | 0.00 | 0.00 | 823731.40 | 0.00 | 99764572.64 | 0.613168E+09 | 0.00 | 0.54 |
March | 0.163271E+10 | 302774.02 | 0.00 | 1911359.60 | 0.00 | 41513491.13 | 0.126617E+10 | 0.00 | 0.67 |
April | 0.405513E+09 | 0.230333E+09 | 0.00 | 2399547.61 | 7761970.53 | 0.00 | 0.109495E+10 | 0.00 | 0.66 |
May | 58772898.79 | 0.879391E+09 | 0.00 | 1630028.01 | 38830112.73 | 0.00 | 0.530854E+09 | 0.00 | 0.62 |
June | 1187101.46 | 0.179552E+10 | 0.00 | 862437.55 | 0.107590E+09 | 0.00 | 0.123048E+09 | 0.00 | 0.53 |
July | 0.00 | 0.273542E+10 | 0.00 | 246174.11 | 0.189492E+09 | 0.00 | 9051463.72 | 0.00 | 0.49 |
August | 5648154.00 | 0.181657E+10 | 0.00 | 1149427.28 | 0.101124E+09 | 0.00 | 0.234909E+09 | 0.00 | 0.62 |
September | 32194843.33 | 0.131185E+10 | 0.00 | 1444553.41 | 38602146.56 | 0.00 | 0.326169E+09 | 0.00 | 0.62 |
October | 0.299808E+09 | 0.306512E+09 | 0.00 | 4894553.96 | 13516903.83 | 0.00 | 0.192890E+10 | 0.00 | 0.82 |
November | 0.158903E+10 | 0.00 | 0.00 | 2806806.46 | 0.00 | 35547516.66 | 0.194756E+10 | 0.00 | 0.67 |
December | 0.326196E+10 | 0.00 | 0.00 | 47268.88 | 0.00 | 0.376600E+09 | 75234315.84 | 0.00 | 0.41 |
Annual Sum or Average | 0.125213E+11 | 0.907590E+10 | 0.00 | 18429480.41 | 0.496917E+09 | 0.763015E+09 | 0.839661E+10 | 0.00 | 0.59 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 47268.88 | 0.00 | 0.00 | 9051463.72 | 0.00 | 0.41 |
Maximum of Months | 0.326196E+10 | 0.273542E+10 | 0.00 | 4894553.96 | 0.189492E+09 | 0.376600E+09 | 0.194756E+10 | 0.00 | 0.82 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.302396E+10 | 0.00 | 0.00 | 154108.10 | 0.00 | 0.270658E+09 | 0.184466E+09 | 0.00 | 0.43 |
February | 0.214795E+10 | 0.00 | 0.00 | 717855.19 | 0.00 | 0.128711E+09 | 0.549149E+09 | 0.00 | 0.53 |
March | 0.163911E+10 | 300725.31 | 0.00 | 1718592.94 | 0.00 | 61689115.71 | 0.117094E+10 | 0.00 | 0.65 |
April | 0.408199E+09 | 0.230273E+09 | 0.00 | 2342365.60 | 7846019.00 | 0.00 | 0.107292E+10 | 0.00 | 0.66 |
May | 59496725.35 | 0.879739E+09 | 0.00 | 1639362.93 | 38824627.71 | 0.00 | 0.529453E+09 | 0.00 | 0.62 |
June | 1294421.23 | 0.179672E+10 | 0.00 | 882591.02 | 0.107538E+09 | 0.00 | 0.122301E+09 | 0.00 | 0.53 |
July | 1927.88 | 0.273849E+10 | 0.00 | 254874.63 | 0.190922E+09 | 0.00 | 9212703.50 | 0.00 | 0.49 |
August | 5658266.09 | 0.181918E+10 | 0.00 | 1172510.00 | 0.100981E+09 | 0.00 | 0.232611E+09 | 0.00 | 0.62 |
September | 32120353.18 | 0.131503E+10 | 0.00 | 1466174.10 | 38482595.21 | 0.00 | 0.325242E+09 | 0.00 | 0.62 |
October | 0.305347E+09 | 0.306302E+09 | 0.00 | 4845003.11 | 13469995.61 | 0.00 | 0.190892E+10 | 0.00 | 0.82 |
November | 0.161397E+10 | 0.00 | 0.00 | 2615807.38 | 0.00 | 57263855.02 | 0.182237E+10 | 0.00 | 0.65 |
December | 0.320924E+10 | 0.00 | 0.00 | 26814.17 | 0.00 | 0.429184E+09 | 44893923.61 | 0.00 | 0.41 |
Annual Sum or Average | 0.124463E+11 | 0.908603E+10 | 0.00 | 17836059.16 | 0.498064E+09 | 0.947506E+09 | 0.797247E+10 | 0.00 | 0.59 |
Minimum of Months | 1927.88 | 0.00 | 0.00 | 26814.17 | 0.00 | 0.00 | 9212703.50 | 0.00 | 0.41 |
Maximum of Months | 0.320924E+10 | 0.273849E+10 | 0.00 | 4845003.11 | 0.190922E+09 | 0.429184E+09 | 0.190892E+10 | 0.00 | 0.82 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.292605E+10 | 0.00 | 0.00 | 88794.32 | 0.00 | 0.381039E+09 | 0.115745E+09 | 0.00 | 0.42 |
February | 0.212065E+10 | 0.00 | 0.00 | 574602.80 | 0.00 | 0.163290E+09 | 0.467231E+09 | 0.00 | 0.52 |
March | 0.168431E+10 | 299469.14 | 0.00 | 1391949.86 | 0.00 | 93333483.97 | 0.979638E+09 | 0.00 | 0.63 |
April | 0.434131E+09 | 0.230069E+09 | 0.00 | 2082630.54 | 8110716.44 | 0.00 | 0.975242E+09 | 0.00 | 0.64 |
May | 70356035.45 | 0.876078E+09 | 0.00 | 1501477.02 | 39266914.73 | 0.00 | 0.494287E+09 | 0.00 | 0.61 |
June | 1172912.60 | 0.179076E+10 | 0.00 | 814266.82 | 0.108241E+09 | 0.00 | 0.122176E+09 | 0.00 | 0.53 |
July | 246861.79 | 0.271530E+10 | 0.00 | 239165.06 | 0.187713E+09 | 0.00 | 8668186.06 | 0.00 | 0.49 |
August | 5700983.32 | 0.180133E+10 | 0.00 | 1107766.15 | 0.101442E+09 | 0.00 | 0.233970E+09 | 0.00 | 0.62 |
September | 35759634.51 | 0.129895E+10 | 0.00 | 1378034.72 | 38749731.68 | 0.00 | 0.313800E+09 | 0.00 | 0.62 |
October | 0.344674E+09 | 0.300007E+09 | 0.00 | 4555310.17 | 13675837.50 | 0.00 | 0.180472E+10 | 0.00 | 0.81 |
November | 0.166136E+10 | 0.00 | 0.00 | 2248572.70 | 0.00 | 69312632.97 | 0.163193E+10 | 0.00 | 0.63 |
December | 0.306890E+10 | 0.00 | 0.00 | 6019.30 | 0.00 | 0.563611E+09 | 14419971.69 | 0.00 | 0.41 |
Annual Sum or Average | 0.123533E+11 | 0.901279E+10 | 0.00 | 15988589.46 | 0.497200E+09 | 0.127059E+10 | 0.716183E+10 | 0.00 | 0.58 |
Minimum of Months | 246861.79 | 0.00 | 0.00 | 6019.30 | 0.00 | 0.00 | 8668186.06 | 0.00 | 0.41 |
Maximum of Months | 0.306890E+10 | 0.271530E+10 | 0.00 | 4555310.17 | 0.187713E+09 | 0.563611E+09 | 0.180472E+10 | 0.00 | 0.81 |
Report: MechanicalVentilationLoadsMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.538167E+10 | 0.00 | 0.00 | 73908.65 | 0.00 | 0.720809E+09 | 0.130475E+09 | 0.00 | 0.38 |
February | 0.395859E+10 | 0.00 | 0.00 | 735508.24 | 0.00 | 0.261886E+09 | 0.738165E+09 | 0.00 | 0.45 |
March | 0.310515E+10 | 0.00 | 0.00 | 1911197.34 | 0.00 | 0.156441E+09 | 0.161057E+10 | 0.00 | 0.53 |
April | 0.657880E+09 | 0.275476E+09 | 0.00 | 4066454.32 | 8275340.07 | 0.00 | 0.159810E+10 | 0.00 | 0.54 |
May | 59058159.39 | 0.146513E+10 | 0.00 | 2376659.80 | 50371097.83 | 0.00 | 0.673181E+09 | 0.00 | 0.51 |
June | 0.00 | 0.333482E+10 | 0.00 | 623980.19 | 61071345.65 | 0.00 | 89221841.26 | 0.00 | 0.44 |
July | 0.00 | 0.500712E+10 | 0.00 | 200563.71 | 0.116698E+09 | 0.00 | 2033627.75 | 0.00 | 0.41 |
August | 20394.71 | 0.332860E+10 | 0.00 | 1229906.49 | 62430624.23 | 0.00 | 0.303405E+09 | 0.00 | 0.51 |
September | 23589753.70 | 0.238446E+10 | 0.00 | 2436135.61 | 31143736.50 | 0.00 | 0.409524E+09 | 0.00 | 0.52 |
October | 0.406828E+09 | 0.534566E+09 | 0.00 | 7559998.00 | 8190919.07 | 0.00 | 0.321655E+10 | 0.00 | 0.68 |
November | 0.321797E+10 | 0.00 | 0.00 | 3089118.75 | 0.00 | 0.161039E+09 | 0.250541E+10 | 0.00 | 0.53 |
December | 0.549961E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118824E+10 | 0.00 | 0.00 | 0.37 |
Annual Sum or Average | 0.223104E+11 | 0.163302E+11 | 0.00 | 24303431.10 | 0.338181E+09 | 0.248842E+10 | 0.112766E+11 | 0.00 | 0.49 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.37 |
Maximum of Months | 0.549961E+10 | 0.500712E+10 | 0.00 | 7559998.00 | 0.116698E+09 | 0.118824E+10 | 0.321655E+10 | 0.00 | 0.68 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.260265E+10 | 0.00 | 0.00 | 25029.38 | 0.00 | 0.441680E+09 | 48387326.38 | 0.00 | 0.38 |
February | 0.194774E+10 | 0.00 | 0.00 | 327068.48 | 0.00 | 0.165967E+09 | 0.339342E+09 | 0.00 | 0.45 |
March | 0.157117E+10 | 0.00 | 0.00 | 868057.87 | 0.00 | 95730822.13 | 0.735593E+09 | 0.00 | 0.53 |
April | 0.340081E+09 | 0.143844E+09 | 0.00 | 1960345.25 | 4550085.40 | 0.00 | 0.779678E+09 | 0.00 | 0.54 |
May | 31090977.90 | 0.742015E+09 | 0.00 | 1182585.27 | 25987763.15 | 0.00 | 0.339349E+09 | 0.00 | 0.52 |
June | 0.00 | 0.167721E+10 | 0.00 | 308982.66 | 31334436.62 | 0.00 | 47142732.87 | 0.00 | 0.44 |
July | 0.00 | 0.250174E+10 | 0.00 | 94759.92 | 62236071.66 | 0.00 | 1040552.04 | 0.00 | 0.41 |
August | 13906.53 | 0.166724E+10 | 0.00 | 622092.78 | 34111788.30 | 0.00 | 0.160487E+09 | 0.00 | 0.51 |
September | 12158620.03 | 0.119604E+10 | 0.00 | 1221007.93 | 15366457.18 | 0.00 | 0.209574E+09 | 0.00 | 0.53 |
October | 0.206341E+09 | 0.267287E+09 | 0.00 | 3839892.47 | 4364941.71 | 0.00 | 0.162628E+10 | 0.00 | 0.69 |
November | 0.158600E+10 | 0.00 | 0.00 | 1493831.28 | 0.00 | 0.116293E+09 | 0.122652E+10 | 0.00 | 0.53 |
December | 0.262789E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.698149E+09 | 0.00 | 0.00 | 0.37 |
Annual Sum or Average | 0.109251E+11 | 0.819537E+10 | 0.00 | 11943653.29 | 0.177952E+09 | 0.151782E+10 | 0.551340E+10 | 0.00 | 0.49 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.37 |
Maximum of Months | 0.262789E+10 | 0.250174E+10 | 0.00 | 3839892.47 | 62236071.66 | 0.698149E+09 | 0.162628E+10 | 0.00 | 0.69 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.254896E+10 | 0.00 | 0.00 | 18862.67 | 0.00 | 0.491206E+09 | 40794841.54 | 0.00 | 0.38 |
February | 0.193870E+10 | 0.00 | 0.00 | 294074.95 | 0.00 | 0.186154E+09 | 0.309482E+09 | 0.00 | 0.44 |
March | 0.157687E+10 | 0.00 | 0.00 | 790208.38 | 0.00 | 0.111916E+09 | 0.681187E+09 | 0.00 | 0.52 |
April | 0.361326E+09 | 0.143915E+09 | 0.00 | 1872194.93 | 4622925.71 | 0.00 | 0.738621E+09 | 0.00 | 0.54 |
May | 36565122.95 | 0.742202E+09 | 0.00 | 1144054.47 | 26133733.35 | 0.00 | 0.328135E+09 | 0.00 | 0.51 |
June | 0.00 | 0.167795E+10 | 0.00 | 298697.21 | 31427940.97 | 0.00 | 46871491.83 | 0.00 | 0.44 |
July | 0.00 | 0.250120E+10 | 0.00 | 91255.93 | 62900008.09 | 0.00 | 1024514.48 | 0.00 | 0.41 |
August | 10149.41 | 0.166834E+10 | 0.00 | 611850.12 | 34599422.15 | 0.00 | 0.159515E+09 | 0.00 | 0.51 |
September | 12341070.19 | 0.119657E+10 | 0.00 | 1198356.55 | 15357198.86 | 0.00 | 0.206953E+09 | 0.00 | 0.52 |
October | 0.224420E+09 | 0.266976E+09 | 0.00 | 3748798.73 | 4392340.81 | 0.00 | 0.158769E+10 | 0.00 | 0.69 |
November | 0.158901E+10 | 0.00 | 0.00 | 1391179.75 | 0.00 | 0.142261E+09 | 0.115773E+10 | 0.00 | 0.52 |
December | 0.256060E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.759089E+09 | 0.00 | 0.00 | 0.37 |
Annual Sum or Average | 0.108488E+11 | 0.819716E+10 | 0.00 | 11459533.69 | 0.179434E+09 | 0.169063E+10 | 0.525800E+10 | 0.00 | 0.49 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.37 |
Maximum of Months | 0.256060E+10 | 0.250120E+10 | 0.00 | 3748798.73 | 62900008.09 | 0.759089E+09 | 0.158769E+10 | 0.00 | 0.69 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.233212E+10 | 0.00 | 0.00 | 6857.55 | 0.00 | 0.701573E+09 | 23035997.30 | 0.00 | 0.38 |
February | 0.186414E+10 | 0.00 | 0.00 | 220136.70 | 0.00 | 0.278935E+09 | 0.248903E+09 | 0.00 | 0.44 |
March | 0.152873E+10 | 0.00 | 0.00 | 618917.36 | 0.00 | 0.202601E+09 | 0.563568E+09 | 0.00 | 0.50 |
April | 0.405285E+09 | 0.143768E+09 | 0.00 | 1663114.49 | 5107223.88 | 1237015.01 | 0.645227E+09 | 0.00 | 0.52 |
May | 45761449.52 | 0.740620E+09 | 0.00 | 1051481.54 | 26318564.76 | 0.00 | 0.304933E+09 | 0.00 | 0.51 |
June | 5627.09 | 0.167561E+10 | 0.00 | 279987.19 | 31477909.17 | 0.00 | 46840623.75 | 0.00 | 0.44 |
July | 0.00 | 0.249493E+10 | 0.00 | 80687.61 | 64012379.71 | 0.00 | 982215.88 | 0.00 | 0.41 |
August | 186796.84 | 0.166666E+10 | 0.00 | 593567.02 | 34694723.37 | 0.00 | 0.158718E+09 | 0.00 | 0.51 |
September | 13624565.33 | 0.119427E+10 | 0.00 | 1167536.73 | 15261890.58 | 0.00 | 0.201145E+09 | 0.00 | 0.52 |
October | 0.274489E+09 | 0.264283E+09 | 0.00 | 3554142.68 | 4471409.65 | 0.00 | 0.149330E+10 | 0.00 | 0.68 |
November | 0.158087E+10 | 0.00 | 0.00 | 1179670.65 | 0.00 | 0.216899E+09 | 0.101052E+10 | 0.00 | 0.51 |
December | 0.235231E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.953102E+09 | 0.00 | 0.00 | 0.37 |
Annual Sum or Average | 0.103975E+11 | 0.818013E+10 | 0.00 | 10416099.52 | 0.181344E+09 | 0.235435E+10 | 0.469718E+10 | 0.00 | 0.48 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.37 |
Maximum of Months | 0.235231E+10 | 0.249493E+10 | 0.00 | 3554142.68 | 64012379.71 | 0.953102E+09 | 0.149330E+10 | 0.00 | 0.68 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.165170E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136142E+10 | 0.00 | 0.00 | 0.38 |
February | 0.142161E+10 | 0.00 | 0.00 | 160370.98 | 0.00 | 0.724510E+09 | 0.208682E+09 | 0.00 | 0.44 |
March | 0.131568E+10 | 0.00 | 0.00 | 451885.16 | 0.00 | 0.438397E+09 | 0.452372E+09 | 0.00 | 0.50 |
April | 0.421206E+09 | 0.147613E+09 | 0.00 | 1601860.06 | 5213948.83 | 8241562.52 | 0.608375E+09 | 0.00 | 0.54 |
May | 37184330.27 | 0.756951E+09 | 0.00 | 1068337.61 | 27454615.04 | 0.00 | 0.311180E+09 | 0.00 | 0.53 |
June | 3239053.81 | 0.168889E+10 | 0.00 | 237474.95 | 31228145.09 | 0.00 | 51649491.88 | 0.00 | 0.45 |
July | 49432.88 | 0.254860E+10 | 0.00 | 129793.46 | 58968122.28 | 0.00 | 3270198.49 | 0.00 | 0.42 |
August | 2082203.12 | 0.170740E+10 | 0.00 | 689817.86 | 32798431.75 | 0.00 | 0.176387E+09 | 0.00 | 0.53 |
September | 13695064.93 | 0.122929E+10 | 0.00 | 1295629.37 | 15306458.88 | 0.00 | 0.222236E+09 | 0.00 | 0.55 |
October | 0.340351E+09 | 0.273801E+09 | 0.00 | 3699163.18 | 4324570.90 | 0.00 | 0.147245E+10 | 0.00 | 0.72 |
November | 0.146481E+10 | 0.00 | 0.00 | 1099750.52 | 0.00 | 0.373701E+09 | 0.935156E+09 | 0.00 | 0.52 |
December | 0.171746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155608E+10 | 0.00 | 0.00 | 0.37 |
Annual Sum or Average | 0.838906E+10 | 0.835254E+10 | 0.00 | 10434083.14 | 0.175294E+09 | 0.446235E+10 | 0.444175E+10 | 0.00 | 0.50 |
Minimum of Months | 49432.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.37 |
Maximum of Months | 0.171746E+10 | 0.254860E+10 | 0.00 | 3699163.18 | 58968122.28 | 0.155608E+10 | 0.147245E+10 | 0.00 | 0.72 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:37:11
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.177012E+12 | 0.172865E+11 | 0.00 | 0.429460E+11 | 0.356537E+10 |
February | 0.188654E+12 | 0.126890E+11 | 0.00 | 0.345373E+11 | 0.380788E+10 |
March | 0.293023E+12 | 0.114921E+11 | 0.00 | 0.342736E+11 | 0.693400E+10 |
April | 0.320792E+12 | 0.336680E+10 | 0.00 | 0.146516E+11 | 0.506105E+11 |
May | 0.347845E+12 | -0.313348E+10 | 0.00 | -0.414768E+10 | 0.103030E+12 |
June | 0.348150E+12 | -0.894303E+10 | 0.00 | -0.215228E+11 | 0.149250E+12 |
July | 0.344013E+12 | -0.130030E+11 | 0.00 | -0.345041E+11 | 0.174626E+12 |
August | 0.313451E+12 | -0.853783E+10 | 0.00 | -0.204533E+11 | 0.153886E+12 |
September | 0.283260E+12 | -0.580719E+10 | 0.00 | -0.117269E+11 | 0.131365E+12 |
October | 0.245651E+12 | 0.388704E+10 | 0.00 | 0.231284E+11 | 0.601054E+11 |
November | 0.183439E+12 | 0.135708E+11 | 0.00 | 0.419904E+11 | 0.571345E+10 |
December | 0.143658E+12 | 0.180128E+11 | 0.00 | 0.463499E+11 | 0.467678E+10 |
Annual Sum or Average | 0.318895E+13 | 0.408804E+11 | 0.00 | 0.145523E+12 | 0.847571E+12 |
Minimum of Months | 0.143658E+12 | -0.130030E+11 | 0.00 | -0.345041E+11 | 0.356537E+10 |