Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:37
Tabular Output Report in Format: HTML
Building: RetailStripmall
Environment: RUNPERIOD 1 ** Dubai Intl AP - ARE IWEC2 WMO#=411940
Simulation Timestamp: 2023-10-16 08:37:02
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:02
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1391.36 | 665.62 | 665.62 |
Net Site Energy | 1391.36 | 665.62 | 665.62 |
Total Source Energy | 4406.43 | 2108.02 | 2108.02 |
Net Source Energy | 4406.43 | 2108.02 | 2108.02 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 2090.32 |
Net Conditioned Building Area | 2090.32 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 642.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 366.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 60.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 128.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 136.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 57.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1391.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 642.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 366.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 60.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 128.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 136.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 57.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 642.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 366.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 60.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 128.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 136.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 57.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 204.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 400.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Other | 61.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 665.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 204.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 400.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Other | 61.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 665.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1391.356 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1391.356 | 100.00 |
Total On-Site and Utility Electric Sources | 1391.356 | 100.00 |
Total Electricity End Uses | 1391.356 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 87.30 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 87.30 | 100.00 |
Total Water End Uses | 87.30 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 4.67 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 1088.33 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTRIPMALL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 0B
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY ARE_DUBAI_DUBAIINTL
| Environment |ZoneCoolingSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ZoneHeatingSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ZoneElectricSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |SpaceGainsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |PeakSpaceGainsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |SpaceGainComponentsAtCoolingPeakMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ComfortReportSimple55Monthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |OccupantComfortDataSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |DXReportMonthly
| PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL | PSZ-AC_3:3 COOLING COIL | PSZ-AC_4:4 COOLING COIL | PSZ-AC_5:5 COOLING COIL | PSZ-AC_6:6 COOLING COIL | PSZ-AC_7:7 COOLING COIL | PSZ-AC_8:8 COOLING COIL | PSZ-AC_9:9 COOLING COIL | PSZ-AC_10:10 COOLING COIL |WindowReportMonthly
| LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR |WindowEnergyReportMonthly
| LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR |WindowZoneSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |WindowEnergyZoneSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| GAS TANK1 | GAS TANK2 | GAS TANK3 | GAS TANK4 | GAS TANK5 | GAS TANK6 | GAS TANK7 |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC_1:1 HEATING COIL | PSZ-AC_2:2 HEATING COIL | PSZ-AC_3:3 HEATING COIL | PSZ-AC_4:4 HEATING COIL | PSZ-AC_5:5 HEATING COIL | PSZ-AC_6:6 HEATING COIL | PSZ-AC_7:7 HEATING COIL | PSZ-AC_8:8 HEATING COIL | PSZ-AC_9:9 HEATING COIL | PSZ-AC_10:10 HEATING COIL | PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL | PSZ-AC_3:3 COOLING COIL | PSZ-AC_4:4 COOLING COIL | PSZ-AC_5:5 COOLING COIL | PSZ-AC_6:6 COOLING COIL | PSZ-AC_7:7 COOLING COIL | PSZ-AC_8:8 COOLING COIL | PSZ-AC_9:9 COOLING COIL | PSZ-AC_10:10 COOLING COIL |FanReportMonthly
| PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN |ZoneTemperatureOscillationReportMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |MechanicalVentilationLoadsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:02
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:37 |
RunPeriod | RUNPERIOD 1 |
Weather File | Dubai Intl AP - ARE IWEC2 WMO#=411940 |
Latitude [deg] | 25.25 |
Longitude [deg] | 55.33 |
Elevation [m] | 5.00 |
Time Zone | 4.00 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Above Ground Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Window Opening Area [m2] | 124.40 | 0.00 | 0.00 | 124.40 | 0.00 |
Gross Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Above Ground Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Above Ground Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Window Opening Area [m2] | 124.40 | 0.00 | 0.00 | 124.40 | 0.00 |
Gross Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Above Ground Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Total | |
Gross Roof Area [m2] | 2090.32 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
LGSTORE1 | 348.39 | Yes | Yes | 1805.20 | 1.00 | 276.30 | 0.00 | 20.77 | 20.77 | 15.3022 | 6.19 | 4.3000 |
SMSTORE1 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.38 | 10.38 | 18.2890 | 6.19 | 4.3000 |
SMSTORE2 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 16.6533 | 6.19 | 4.3000 |
SMSTORE3 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 16.6533 | 6.19 | 4.3000 |
SMSTORE4 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 16.6533 | 6.19 | 4.3000 |
LGSTORE2 | 348.39 | Yes | Yes | 1805.20 | 1.00 | 157.89 | 0.00 | 20.72 | 20.72 | 9.5842 | 6.19 | 4.3000 |
SMSTORE5 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 9.6995 | 6.19 | 4.3000 |
SMSTORE6 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 9.6995 | 6.19 | 4.3000 |
SMSTORE7 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 9.6995 | 6.19 | 4.3000 |
SMSTORE8 | 174.19 | Yes | Yes | 902.60 | 1.00 | 197.36 | 0.00 | 10.36 | 10.36 | 9.6995 | 6.19 | 4.3000 |
Total | 2090.32 | 10831.20 | 1184.15 | 0.00 | 124.40 | 124.40 | 13.0683 | 6.19 | 4.3000 | |||
Conditioned Total | 2090.32 | 10831.20 | 1184.15 | 0.00 | 124.40 | 124.40 | 13.0683 | 6.19 | 4.3000 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
LGSTORE1 | 348.39 | Yes | Yes | 1.00 | LGSTORE1 | GENERAL | LGSTORE1 | 15.3022 | 6.19 | 4.3000 | |
SMSTORE1 | 174.19 | Yes | Yes | 1.00 | SMSTORE1 | GENERAL | SMSTORE1 | 18.2890 | 6.19 | 4.3000 | |
SMSTORE2 | 174.19 | Yes | Yes | 1.00 | SMSTORE2 | GENERAL | SMSTORE2 | 16.6533 | 6.19 | 4.3000 | |
SMSTORE3 | 174.19 | Yes | Yes | 1.00 | SMSTORE3 | GENERAL | SMSTORE3 | 16.6533 | 6.19 | 4.3000 | |
SMSTORE4 | 174.19 | Yes | Yes | 1.00 | SMSTORE4 | GENERAL | SMSTORE4 | 16.6533 | 6.19 | 4.3000 | |
LGSTORE2 | 348.39 | Yes | Yes | 1.00 | LGSTORE2 | GENERAL | LGSTORE2 | 9.5842 | 6.19 | 4.3000 | |
SMSTORE5 | 174.19 | Yes | Yes | 1.00 | SMSTORE5 | GENERAL | SMSTORE5 | 9.6995 | 6.19 | 4.3000 | |
SMSTORE6 | 174.19 | Yes | Yes | 1.00 | SMSTORE6 | GENERAL | SMSTORE6 | 9.6995 | 6.19 | 4.3000 | |
SMSTORE7 | 174.19 | Yes | Yes | 1.00 | SMSTORE7 | GENERAL | SMSTORE7 | 9.6995 | 6.19 | 4.3000 | |
SMSTORE8 | 174.19 | Yes | Yes | 1.00 | SMSTORE8 | GENERAL | SMSTORE8 | 9.6995 | 6.19 | 4.3000 | |
Total | 2090.32 | 13.0683 | 3.10 | 4.3000 | |||||||
Conditioned Total | 2090.32 | 13.0683 | 3.10 | 4.3000 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 2090.32 | 2090.32 | 0.00 | 0.00 | 13.0683 | 6.19 | 4.3000 |
Total | 2090.32 | 2090.32 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:02
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 10-AUG-16:10 | 02-JAN-08:30 | - | - | - | - | - | - | - | - | - | - | 06-JAN-13:09 |
Heating | 0.00 | 84.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 105570.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 23459.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 8059.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 14964.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 2867.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 154921.40 | 84.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 84.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 105570.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 23459.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 8059.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 14964.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 2867.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:02
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 2033.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1161.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 190.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 405.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 432.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 182.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 4406.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 973.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 555.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 91.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 194.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 207.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 87.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2108.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 973.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 555.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 91.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 194.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 207.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 87.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2108.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:02
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
LGSTORE1 DIRECT AIR | 2.91 |
SMSTORE1 DIRECT AIR | 1.47 |
SMSTORE2 DIRECT AIR | 1.46 |
SMSTORE3 DIRECT AIR | 1.47 |
SMSTORE4 DIRECT AIR | 1.46 |
LGSTORE2 DIRECT AIR | 2.59 |
SMSTORE5 DIRECT AIR | 1.37 |
SMSTORE6 DIRECT AIR | 1.37 |
SMSTORE7 DIRECT AIR | 1.38 |
SMSTORE8 DIRECT AIR | 1.65 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC_1:1 | 2.91 | 2.91 | 2.91 | 2.91 | 2.91 | 2.91 | 1.00 | 1.00 | 2.91 |
PSZ-AC_2:2 | 1.47 | 1.47 | 1.47 | 1.47 | 1.47 | 1.47 | 1.00 | 1.000000 | 1.47 |
PSZ-AC_3:3 | 1.46 | 1.46 | 1.46 | 1.46 | 1.46 | 1.46 | 1.00 | 1.00 | 1.46 |
PSZ-AC_4:4 | 1.47 | 1.47 | 1.47 | 1.47 | 1.47 | 1.47 | 1.00 | 1.00 | 1.47 |
PSZ-AC_5:5 | 1.46 | 1.46 | 1.46 | 1.46 | 1.46 | 1.46 | 1.00 | 1.00 | 1.46 |
PSZ-AC_6:6 | 2.59 | 2.59 | 2.59 | 2.59 | 2.59 | 2.59 | 1.00 | 1.00 | 2.59 |
PSZ-AC_7:7 | 1.37 | 1.37 | 1.37 | 1.37 | 1.37 | 1.37 | 1.00 | 1.00 | 1.37 |
PSZ-AC_8:8 | 1.37 | 1.37 | 1.37 | 1.37 | 1.37 | 1.37 | 1.00 | 1.00 | 1.37 |
PSZ-AC_9:9 | 1.38 | 1.38 | 1.38 | 1.38 | 1.38 | 1.38 | 1.00 | 1.00 | 1.38 |
PSZ-AC_10:10 | 1.65 | 1.65 | 1.65 | 1.65 | 1.65 | 1.65 | 1.00 | 1.00 | 1.65 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC_1:1_OA_CONTROLLER | 2.91 | 0.411479 |
PSZ-AC_2:2_OA_CONTROLLER | 1.47 | 0.205739 |
PSZ-AC_3:3_OA_CONTROLLER | 1.46 | 0.205739 |
PSZ-AC_4:4_OA_CONTROLLER | 1.47 | 0.205739 |
PSZ-AC_5:5_OA_CONTROLLER | 1.46 | 0.205739 |
PSZ-AC_6:6_OA_CONTROLLER | 2.59 | 0.411479 |
PSZ-AC_7:7_OA_CONTROLLER | 1.37 | 0.205739 |
PSZ-AC_8:8_OA_CONTROLLER | 1.37 | 0.205739 |
PSZ-AC_9:9_OA_CONTROLLER | 1.38 | 0.205739 |
PSZ-AC_10:10_OA_CONTROLLER | 1.65 | 0.205739 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | 2.91 | 3114.91 |
PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | 1.47 | 1568.08 |
PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | 1.46 | 1567.48 |
PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | 1.47 | 1570.87 |
PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | 1.46 | 1561.99 |
PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | 2.59 | 2775.27 |
PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | 1.37 | 1518.92 |
PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | 1.37 | 1514.18 |
PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | 1.38 | 1524.45 |
PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | 1.65 | 1762.39 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC_1:1_UNITARY_PACKAGE_DX | 2.91 | 2.91 | 2.91 | 1.92 | 72287.21 | 71890.17 | 40.00 | 1.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_DX | 1.47 | 1.47 | 1.47 | 0.967181 | 36390.02 | 35571.45 | 40.00 | 1.00 |
PSZ-AC_3:3_UNITARY_PACKAGE_DX | 1.46 | 1.46 | 1.46 | 0.966814 | 36376.21 | 35558.72 | 40.00 | 1.00 |
PSZ-AC_4:4_UNITARY_PACKAGE_DX | 1.47 | 1.47 | 1.47 | 0.968905 | 36454.89 | 35631.11 | 40.00 | 1.00 |
PSZ-AC_5:5_UNITARY_PACKAGE_DX | 1.46 | 1.46 | 1.46 | 0.963427 | 36248.77 | 35441.48 | 40.00 | 1.00 |
PSZ-AC_6:6_UNITARY_PACKAGE_DX | 2.59 | 2.59 | 2.59 | 1.71 | 64405.04 | 64479.44 | 40.00 | 1.00 |
PSZ-AC_7:7_UNITARY_PACKAGE_DX | 1.37 | 1.37 | 1.37 | 0.905461 | 34067.80 | 33981.03 | 40.00 | 1.00 |
PSZ-AC_8:8_UNITARY_PACKAGE_DX | 1.37 | 1.37 | 1.37 | 0.902636 | 33961.51 | 33883.25 | 40.00 | 1.00 |
PSZ-AC_9:9_UNITARY_PACKAGE_DX | 1.38 | 1.38 | 1.38 | 0.908758 | 34191.87 | 34129.66 | 40.00 | 1.00 |
PSZ-AC_10:10_UNITARY_PACKAGE_DX | 1.65 | 1.65 | 1.65 | 1.09 | 39705.60 | 40268.02 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-AC_1:1 COOLING COIL | 2.91 | 1.46 | 1.94 | 72287.21 | 36143.61 | 0.701080 | 0.701080 |
PSZ-AC_2:2 COOLING COIL | 1.47 | 0.732713 | 0.976953 | 36390.02 | 18195.01 | 0.701080 | 0.701080 |
PSZ-AC_3:3 COOLING COIL | 1.46 | 0.732435 | 0.976580 | 36376.21 | 18188.10 | 0.701080 | 0.701080 |
PSZ-AC_4:4 COOLING COIL | 1.47 | 0.734019 | 0.978693 | 36454.89 | 18227.44 | 0.701080 | 0.701080 |
PSZ-AC_5:5 COOLING COIL | 1.46 | 0.729869 | 0.973160 | 36248.77 | 18124.38 | 0.701080 | 0.701080 |
PSZ-AC_6:6 COOLING COIL | 2.59 | 1.30 | 1.73 | 64405.04 | 32202.52 | 0.701080 | 0.701080 |
PSZ-AC_7:7 COOLING COIL | 1.37 | 0.685955 | 0.914607 | 34067.80 | 17033.90 | 0.701080 | 0.701080 |
PSZ-AC_8:8 COOLING COIL | 1.37 | 0.683815 | 0.911753 | 33961.51 | 16980.76 | 0.701080 | 0.701080 |
PSZ-AC_9:9 COOLING COIL | 1.38 | 0.688453 | 0.917940 | 34191.87 | 17095.94 | 0.701080 | 0.701080 |
PSZ-AC_10:10 COOLING COIL | 1.65 | 0.823512 | 1.10 | 39705.60 | 19852.80 | 0.710450 | 0.710450 |
Design Size Nominal Capacity [W] | |
PSZ-AC_1:1 HEATING COIL | 71890.17 |
PSZ-AC_2:2 HEATING COIL | 35571.45 |
PSZ-AC_3:3 HEATING COIL | 35558.72 |
PSZ-AC_4:4 HEATING COIL | 35631.11 |
PSZ-AC_5:5 HEATING COIL | 35441.48 |
PSZ-AC_6:6 HEATING COIL | 64479.44 |
PSZ-AC_7:7 HEATING COIL | 33981.03 |
PSZ-AC_8:8 HEATING COIL | 33883.25 |
PSZ-AC_9:9 HEATING COIL | 34129.66 |
PSZ-AC_10:10 HEATING COIL | 40268.02 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:02
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
LGSTORE1_WALL_3 | LGSTORE1_WALL_3_DOOR_1 | LGSTORE1_WALL_3_DOOR_2 | |
LGSTORE1_WALL_1 | LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | |
SMSTORE1_WALL_1 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | |
SMSTORE1_WALL_3 | SMSTORE1_WALL_3_DOOR | |
SMSTORE2_WALL_1 | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | |
SMSTORE2_WALL_3 | SMSTORE2_WALL_3_DOOR | |
SMSTORE3_WALL_1 | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | |
SMSTORE3_WALL_3 | SMSTORE3_WALL_3_DOOR | |
SMSTORE4_WALL_1 | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | |
SMSTORE4_WALL_3 | SMSTORE4_WALL_3_DOOR | |
LGSTORE2_WALL_3 | LGSTORE2_WALL_3_DOOR_1 | LGSTORE2_WALL_3_DOOR_2 | |
LGSTORE2_WALL_1 | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | |
SMSTORE5_WALL_1 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | |
SMSTORE5_WALL_3 | SMSTORE5_WALL_3_DOOR | |
SMSTORE6_WALL_1 | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | |
SMSTORE6_WALL_3 | SMSTORE6_WALL_3_DOOR | |
SMSTORE7_WALL_1 | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | |
SMSTORE7_WALL_3 | SMSTORE7_WALL_3_DOOR | |
SMSTORE8_WALL_1 | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR | |
SMSTORE8_WALL_3 | SMSTORE8_WALL_3_DOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:02
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:02
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 29.50 | 25.50 | 21.10 | 19.20 | 20.80 | 23.10 | 26.50 | 31.40 | 33.00 | 35.10 | 35.30 | 32.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Dubai Intl AP - ARE IWEC2 WMO#=411940 | 25.25 | 55.33 | 4.00 | 5.00 | 101265 | 1.2036 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 27.75 | 16.10 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RetailStripmall | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 10 | 118 | 48 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | LGSTORE1 | 0.0 | 0.00 | 0.00 | 0.00 | 7.62 | 11.43 | 2.59 | 1 | 1 | 1 | 0.00 | 15.24 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 1805.20 | TARP | TARP | 348.39 | 276.30 | 247.74 | 20.77 | 6 | 8 | 0 | Yes |
2 | SMSTORE1 | 0.0 | 0.00 | 0.00 | 0.00 | 19.05 | 11.43 | 2.59 | 1 | 1 | 1 | 15.24 | 22.86 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.66 | 10.38 | 6 | 4 | 0 | Yes |
3 | SMSTORE2 | 0.0 | 0.00 | 0.00 | 0.00 | 26.67 | 11.43 | 2.59 | 1 | 1 | 1 | 22.86 | 30.48 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
4 | SMSTORE3 | 0.0 | 0.00 | 0.00 | 0.00 | 34.29 | 11.43 | 2.59 | 1 | 1 | 1 | 30.48 | 38.10 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
5 | SMSTORE4 | 0.0 | 0.00 | 0.00 | 0.00 | 41.91 | 11.43 | 2.59 | 1 | 1 | 1 | 38.10 | 45.72 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
6 | LGSTORE2 | 0.0 | 0.00 | 0.00 | 0.00 | 53.34 | 11.43 | 2.59 | 1 | 1 | 1 | 45.72 | 60.96 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 1805.20 | TARP | TARP | 348.39 | 157.89 | 129.41 | 20.72 | 6 | 8 | 0 | Yes |
7 | SMSTORE5 | 0.0 | 0.00 | 0.00 | 0.00 | 64.77 | 11.43 | 2.59 | 1 | 1 | 1 | 60.96 | 68.58 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
8 | SMSTORE6 | 0.0 | 0.00 | 0.00 | 0.00 | 72.39 | 11.43 | 2.59 | 1 | 1 | 1 | 68.58 | 76.20 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
9 | SMSTORE7 | 0.0 | 0.00 | 0.00 | 0.00 | 80.01 | 11.43 | 2.59 | 1 | 1 | 1 | 76.20 | 83.82 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
10 | SMSTORE8 | 0.0 | 0.00 | 0.00 | 0.00 | 87.63 | 11.43 | 2.59 | 1 | 1 | 1 | 83.82 | 91.44 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 197.36 | 183.12 | 10.36 | 6 | 4 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | LGSTORE1 | 348.39 | 56.3 | 6.193 | 0.161 | 15.302 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 19.602 | No |
2 | SMSTORE1 | 174.19 | 28.1 | 6.194 | 0.161 | 18.289 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 22.589 | No |
3 | SMSTORE2 | 174.19 | 28.1 | 6.194 | 0.161 | 16.653 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 20.953 | No |
4 | SMSTORE3 | 174.19 | 28.1 | 6.194 | 0.161 | 16.653 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 20.953 | No |
5 | SMSTORE4 | 174.19 | 28.1 | 6.194 | 0.161 | 16.653 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 20.953 | No |
6 | LGSTORE2 | 348.39 | 56.3 | 6.193 | 0.161 | 9.584 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 13.884 | No |
7 | SMSTORE5 | 174.19 | 28.1 | 6.194 | 0.161 | 9.699 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 13.999 | No |
8 | SMSTORE6 | 174.19 | 28.1 | 6.194 | 0.161 | 9.699 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 13.999 | No |
9 | SMSTORE7 | 174.19 | 28.1 | 6.194 | 0.161 | 9.699 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 13.999 | No |
10 | SMSTORE8 | 174.19 | 28.1 | 6.194 | 0.161 | 9.699 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 13.999 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | LGSTORE1 | TYPE1_OCC_SCH | LGSTORE1 | 348.39 | 56.3 | 56.3 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 56 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | SMSTORE1 | TYPE1_OCC_SCH | SMSTORE1 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | SMSTORE2 | TYPE2_OCC_SCH | SMSTORE2 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | SMSTORE3 | TYPE2_OCC_SCH | SMSTORE3 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | SMSTORE4 | TYPE2_OCC_SCH | SMSTORE4 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | LGSTORE2 | TYPE3_OCC_SCH | LGSTORE2 | 348.39 | 56.3 | 56.3 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 56 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | SMSTORE5 | TYPE3_OCC_SCH | SMSTORE5 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | SMSTORE6 | TYPE3_OCC_SCH | SMSTORE6 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | SMSTORE7 | TYPE3_OCC_SCH | SMSTORE7 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | SMSTORE8 | TYPE3_OCC_SCH | SMSTORE8 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | LGSTORE1_LIGHTS | LTG_SCH_BASE_LPD1 | LGSTORE1 | 348.39 | 56.3 | 3346.345 | 9.605 | 59.490 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3346.345 |
2 | LGSTORE1_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | LGSTORE1 | 348.39 | 56.3 | 1984.726 | 5.697 | 35.284 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1984.726 |
3 | SMSTORE1_LIGHTS | LTG_SCH_BASE_SMALL_LPD1 | SMSTORE1 | 174.19 | 28.1 | 1693.257 | 9.721 | 60.206 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1693.257 |
4 | SMSTORE1_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | SMSTORE1 | 174.19 | 28.1 | 1492.567 | 8.568 | 53.070 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1492.567 |
5 | SMSTORE2_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE2 | 174.19 | 28.1 | 1689.582 | 9.699 | 60.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1689.582 |
6 | SMSTORE2_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE2 | 174.19 | 28.1 | 1211.319 | 6.954 | 43.070 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1211.319 |
7 | SMSTORE3_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE3 | 174.19 | 28.1 | 1689.582 | 9.699 | 60.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1689.582 |
8 | SMSTORE3_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE3 | 174.19 | 28.1 | 1211.319 | 6.954 | 43.070 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1211.319 |
9 | SMSTORE4_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE4 | 174.19 | 28.1 | 1689.582 | 9.699 | 60.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1689.582 |
10 | SMSTORE4_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE4 | 174.19 | 28.1 | 1211.319 | 6.954 | 43.070 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1211.319 |
11 | LGSTORE2_LIGHTS | LTG_SCH_BASE_LPD2 | LGSTORE2 | 348.39 | 56.3 | 3338.998 | 9.584 | 59.359 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3338.998 |
12 | LGSTORE2_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | LGSTORE2 | 348.39 | 56.3 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
13 | SMSTORE5_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE5 | 174.19 | 28.1 | 1689.582 | 9.699 | 60.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1689.582 |
14 | SMSTORE5_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE5 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
15 | SMSTORE6_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE6 | 174.19 | 28.1 | 1689.582 | 9.699 | 60.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1689.582 |
16 | SMSTORE6_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE6 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
17 | SMSTORE7_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE7 | 174.19 | 28.1 | 1689.582 | 9.699 | 60.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1689.582 |
18 | SMSTORE7_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE7 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
19 | SMSTORE8_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE8 | 174.19 | 28.1 | 1689.582 | 9.699 | 60.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1689.582 |
20 | SMSTORE8_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE8 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LGSTORE1_MISCPLUG_EQUIP | TYPE1_EQUIP_SCH | LGSTORE1 | 348.39 | 56.3 | 1498.062 | 4.300 | 26.632 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1498.062 |
2 | SMSTORE1_MISCPLUG_EQUIP | TYPE1_EQUIP_SCH | SMSTORE1 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
3 | SMSTORE2_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE2 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
4 | SMSTORE3_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE3 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
5 | SMSTORE4_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE4 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
6 | LGSTORE2_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | LGSTORE2 | 348.39 | 56.3 | 1498.062 | 4.300 | 26.632 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1498.062 |
7 | SMSTORE5_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE5 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
8 | SMSTORE6_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE6 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
9 | SMSTORE7_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE7 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
10 | SMSTORE8_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE8 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.2284 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
5 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 1.028 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
6 | LGSTORE1_FLOOR_FFACTOR | 36 | 2 | 7 | 0.167 | 0.1995 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
7 | SMSTORE1_FLOOR_FFACTOR | 37 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
8 | SMSTORE2_FLOOR_FFACTOR | 38 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | SMSTORE3_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
10 | SMSTORE4_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
11 | LGSTORE2_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | SMSTORE5_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | SMSTORE6_FLOOR_FFACTOR | 43 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | SMSTORE7_FLOOR_FFACTOR | 44 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | SMSTORE8_FLOOR_FFACTOR | 45 | 2 | 7 | 0.167 | 0.2888 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
6 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
7 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
8 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
10 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7383 |
11 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
12 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.937 |
13 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
14 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
15 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
16 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
17 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
18 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
19 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
20 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
21 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
22 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
23 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
24 | ~FC_Insulation_7 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_8 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_9 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_10 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.386 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
14 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
15 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
16 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
17 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
18 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
19 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
20 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
21 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
22 | 7 | -0.27626373E-12 | 0.13670118E-14 | -0.80430638E-13 | 0.78416590E-16 |
23 | 6 | 0.25658824E-07 | 0.27941242E-09 | 0.59030768E-08 | -0.11909973E-12 |
24 | 5 | -0.17468948E-03 | 0.24402707E-05 | -0.90039107E-04 | 0.58437388E-08 |
25 | 4 | 0.27392503 | 0.12091412E-02 | 0.93138911E-01 | -0.31018751E-04 |
26 | 3 | -6.9050330 | 0.38055846E-01 | -2.2317352 | 0.27239655E-01 |
27 | 2 | 39.679098 | 0.13717309 | 14.824430 | -0.32006664 |
28 | 1 | -79.631803 | 0.62641324E-01 | -28.746304 | 1.0591428 |
29 | 0 | 46.824345 | 0.12749544E-02 | 16.300917 | |
30 | 7 | -0.21163652E-08 | -0.68723841E-15 | 0.43910983E-14 | -0.57684426E-16 |
31 | 6 | 0.56109385E-05 | 0.38186281E-08 | 0.31898696E-02 | -0.26759299E-04 |
32 | 5 | -0.40164657E-03 | 0.22608617E-05 | -0.22372456 | 0.19561502E-02 |
33 | 4 | 0.92272104E-02 | 0.10289840E-03 | 4.8295456 | -0.45264980E-01 |
34 | 3 | -0.80993241E-01 | 0.81813938E-03 | -38.021416 | 0.39865375 |
35 | 2 | 0.28754352 | 0.13608947E-02 | 116.48395 | -1.4179393 |
36 | 1 | -0.41499682 | 0.41453381E-03 | -143.90731 | 2.0490399 |
37 | 0 | 0.20232414 | 0.10048102E-04 | 60.838472 | |
38 | 7 | -0.37862368E-08 | -0.38757603E-14 | 0.11479940E-14 | -0.41635801E-16 |
39 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
40 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
41 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
42 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
43 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
44 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
45 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
46 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479937E-14 | -0.41635796E-16 |
47 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
48 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
49 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
50 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
51 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
52 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
53 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
54 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479940E-14 | -0.41635801E-16 |
55 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
56 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
57 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
58 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
59 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
60 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
61 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
62 | 7 | -0.37862368E-08 | -0.38757603E-14 | 0.11479940E-14 | -0.41635801E-16 |
63 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
64 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
65 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
66 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
67 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
68 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
69 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
70 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479937E-14 | -0.41635796E-16 |
71 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
72 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
73 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
74 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
75 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
76 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
77 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
78 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479937E-14 | -0.41635796E-16 |
79 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
80 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
81 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
82 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
83 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
84 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
85 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
86 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479940E-14 | -0.41635801E-16 |
87 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
88 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
89 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
90 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
91 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
92 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
93 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
94 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479936E-14 | -0.41635794E-16 |
95 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
96 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
97 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
98 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
99 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
100 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
101 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
102 | 7 | -0.14484255E-08 | -0.22640907E-15 | 0.11860658E-13 | -0.17473455E-15 |
103 | 6 | 0.80640390E-05 | 0.55493782E-08 | 0.31828288E-02 | -0.26700235E-04 |
104 | 5 | -0.58275339E-03 | 0.32892043E-05 | -0.22332434 | 0.19526176E-02 |
105 | 4 | 0.13421983E-01 | 0.14977251E-03 | 4.8228790 | -0.45200897E-01 |
106 | 3 | -0.11791368 | 0.11914425E-02 | -37.983753 | 0.39823745 |
107 | 2 | 0.41875064 | 0.19825898E-02 | 116.41064 | -1.4169588 |
108 | 1 | -0.60444169 | 0.60433957E-03 | -143.86415 | 2.0483306 |
109 | 0 | 0.29470347 | 0.14596444E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.503_SHGC_0.22 | 35 | 1 | VerySmooth | 2.860 | 2.860 | 1.000 | 0.221 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 1.93472E-002 | 0.13126 | 0.64057 | 0.64057 | 0.24200 | 0.16318 | 0.24318 | 0.00000 | 0.84000 | 0.84000 | 0.10783 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | GAS TANK1 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
2 | WaterHeater:Mixed | GAS TANK2 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
3 | WaterHeater:Mixed | GAS TANK3 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
4 | WaterHeater:Mixed | GAS TANK4 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
5 | WaterHeater:Mixed | GAS TANK5 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
6 | WaterHeater:Mixed | GAS TANK6 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
7 | WaterHeater:Mixed | GAS TANK7 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | LGSTORE1_WALL_2 | 0 | 118.41 | 56.08 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
2 | LGSTORE1_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
3 | LGSTORE1_WALL_3_DOOR_1 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
4 | LGSTORE1_WALL_3_DOOR_2 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
5 | LGSTORE1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
6 | LGSTORE1_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
7 | LGSTORE1_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
8 | LGSTORE1_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
9 | LGSTORE1_WALL_1_WINDOW_3 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
10 | LGSTORE1_WALL_1_WINDOW_4 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
11 | LGSTORE1_WALL_1_DOOR_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 1 | No | No |
12 | LGSTORE1_WALL_1_DOOR_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 1 | No | No |
13 | LGSTORE1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
14 | LGSTORE1_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
15 | LGSTORE1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
16 | SMSTORE1_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
17 | SMSTORE1_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
18 | SMSTORE1_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
19 | SMSTORE1_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
20 | SMSTORE1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
21 | SMSTORE1_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
22 | SMSTORE1_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
23 | SMSTORE1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
24 | SMSTORE1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
25 | SMSTORE1_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
26 | SMSTORE1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
27 | SMSTORE2_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
28 | SMSTORE2_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
29 | SMSTORE2_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
30 | SMSTORE2_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
31 | SMSTORE2_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
32 | SMSTORE2_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
33 | SMSTORE2_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
34 | SMSTORE2_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
35 | SMSTORE2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
36 | SMSTORE2_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
37 | SMSTORE2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
38 | SMSTORE3_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
39 | SMSTORE3_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
40 | SMSTORE3_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
41 | SMSTORE3_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
42 | SMSTORE3_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
43 | SMSTORE3_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
44 | SMSTORE3_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
45 | SMSTORE3_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
46 | SMSTORE3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
47 | SMSTORE3_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
48 | SMSTORE3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
49 | SMSTORE4_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
50 | SMSTORE4_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
51 | SMSTORE4_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
52 | SMSTORE4_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
53 | SMSTORE4_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
54 | SMSTORE4_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 3 | No | No |
55 | SMSTORE4_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
56 | SMSTORE4_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
57 | SMSTORE4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
58 | SMSTORE4_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
59 | SMSTORE4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
60 | LGSTORE2_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
61 | LGSTORE2_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 4 | No | No |
62 | LGSTORE2_WALL_3_DOOR_1 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
63 | LGSTORE2_WALL_3_DOOR_2 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
64 | LGSTORE2_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
65 | LGSTORE2_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 4 | No | No |
66 | LGSTORE2_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
67 | LGSTORE2_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
68 | LGSTORE2_WALL_1_WINDOW_3 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
69 | LGSTORE2_WALL_1_WINDOW_4 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
70 | LGSTORE2_WALL_1_DOOR_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
71 | LGSTORE2_WALL_1_DOOR_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
72 | LGSTORE2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
73 | LGSTORE2_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
74 | LGSTORE2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
75 | SMSTORE5_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
76 | SMSTORE5_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
77 | SMSTORE5_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
78 | SMSTORE5_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
79 | SMSTORE5_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
80 | SMSTORE5_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
81 | SMSTORE5_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
82 | SMSTORE5_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
83 | SMSTORE5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
84 | SMSTORE5_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
85 | SMSTORE5_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
86 | SMSTORE6_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
87 | SMSTORE6_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
88 | SMSTORE6_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
89 | SMSTORE6_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
90 | SMSTORE6_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
91 | SMSTORE6_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
92 | SMSTORE6_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
93 | SMSTORE6_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
94 | SMSTORE6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
95 | SMSTORE6_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
96 | SMSTORE6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
97 | SMSTORE7_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
98 | SMSTORE7_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
99 | SMSTORE7_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
100 | SMSTORE7_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
101 | SMSTORE7_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
102 | SMSTORE7_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 3 | No | No |
103 | SMSTORE7_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
104 | SMSTORE7_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
105 | SMSTORE7_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
106 | SMSTORE7_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
107 | SMSTORE7_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
108 | SMSTORE8_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 4 | No | No |
109 | SMSTORE8_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 2 | No | No |
110 | SMSTORE8_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 2 | No | No |
111 | SMSTORE8_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 1 | No | No |
112 | SMSTORE8_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
113 | SMSTORE8_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 3 | No | No |
114 | SMSTORE8_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
115 | SMSTORE8_WALL_4 | 0 | 118.41 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 3 | No | No |
116 | SMSTORE8_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
117 | SMSTORE8_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
118 | SMSTORE8_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | LGSTORE1_INFILTRATION | TYPE1_INFIL_SCH | LGSTORE1 | 348.39 | 56.3 | 0.157 | 4.517E-004 | 2.488E-004 | 0.314 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | LGSTORE1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LGSTORE1 | 348.39 | 56.3 | 0.389 | 1.116E-003 | 6.149E-004 | 0.776 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | SMSTORE1_INFILTRATION | TYPE1_INFIL_SCH | SMSTORE1 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | SMSTORE1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE1 | 174.19 | 28.1 | 0.222 | 1.276E-003 | 8.648E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | SMSTORE2_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE2 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | SMSTORE2_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE2 | 174.19 | 28.1 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | SMSTORE3_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE3 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | SMSTORE3_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE3 | 174.19 | 28.1 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | SMSTORE4_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE4 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | SMSTORE4_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE4 | 174.19 | 28.1 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | LGSTORE2_INFILTRATION | TYPE3_INFIL_SCH | LGSTORE2 | 348.39 | 56.3 | 8.993E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | LGSTORE2_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LGSTORE2 | 348.39 | 56.3 | 0.389 | 1.116E-003 | 7.565E-004 | 0.776 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | SMSTORE5_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE5 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | SMSTORE5_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE5 | 174.19 | 28.1 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | SMSTORE6_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE6 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | SMSTORE6_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE6 | 174.19 | 28.1 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | SMSTORE7_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE7 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
18 | SMSTORE7_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE7 | 174.19 | 28.1 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | SMSTORE8_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE8 | 174.19 | 28.1 | 0.112 | 6.453E-004 | 2.994E-004 | 0.448 | 0.000 | 0.000 | 0.224 | 0.000 |
20 | SMSTORE8_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE8 | 174.19 | 28.1 | 0.222 | 1.276E-003 | 5.921E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | LGSTORE1 | Mixing/Well-Stirred |
2 | SMSTORE1 | Mixing/Well-Stirred |
3 | SMSTORE2 | Mixing/Well-Stirred |
4 | SMSTORE3 | Mixing/Well-Stirred |
5 | SMSTORE4 | Mixing/Well-Stirred |
6 | LGSTORE2 | Mixing/Well-Stirred |
7 | SMSTORE5 | Mixing/Well-Stirred |
8 | SMSTORE6 | Mixing/Well-Stirred |
9 | SMSTORE7 | Mixing/Well-Stirred |
10 | SMSTORE8 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone LGSTORE1 | 1.2000 |
3 | Zone SMSTORE1 | 1.2000 |
4 | Zone SMSTORE2 | 1.2000 |
5 | Zone SMSTORE3 | 1.2000 |
6 | Zone SMSTORE4 | 1.2000 |
7 | Zone LGSTORE2 | 1.2000 |
8 | Zone SMSTORE5 | 1.2000 |
9 | Zone SMSTORE6 | 1.2000 |
10 | Zone SMSTORE7 | 1.2000 |
11 | Zone SMSTORE8 | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone LGSTORE1 | 1.2000 |
3 | Zone SMSTORE1 | 1.2000 |
4 | Zone SMSTORE2 | 1.2000 |
5 | Zone SMSTORE3 | 1.2000 |
6 | Zone SMSTORE4 | 1.2000 |
7 | Zone LGSTORE2 | 1.2000 |
8 | Zone SMSTORE5 | 1.2000 |
9 | Zone SMSTORE6 | 1.2000 |
10 | Zone SMSTORE7 | 1.2000 |
11 | Zone SMSTORE8 | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | LGSTORE1 | Cooling | 32943.68153 | 39532.41784 | 2.42584 | 2.91101 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 42.70300 | 1.07816E-002 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
2 | LGSTORE1 | Heating | 9161.86196 | 10994.23435 | 0.37921 | 0.45506 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 | 12.70000 | 9.15345E-003 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
3 | SMSTORE1 | Cooling | 16584.14215 | 19900.97058 | 1.22119 | 1.46543 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 42.80000 | 1.07818E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
4 | SMSTORE1 | Heating | 4219.68458 | 5063.62150 | 0.18201 | 0.21842 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 12.70000 | 9.15345E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
5 | SMSTORE2 | Cooling | 16577.85126 | 19893.42151 | 1.22072 | 1.46487 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 42.80000 | 1.07818E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
6 | SMSTORE2 | Heating | 4235.01355 | 5082.01626 | 0.18267 | 0.21921 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 12.70000 | 9.15345E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
7 | SMSTORE3 | Cooling | 16613.71114 | 19936.45337 | 1.22337 | 1.46804 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 42.80000 | 1.07818E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
8 | SMSTORE3 | Heating | 4273.59243 | 5128.31091 | 0.18434 | 0.22121 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 12.70000 | 9.15345E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
9 | SMSTORE4 | Cooling | 16519.77719 | 19823.73263 | 1.21645 | 1.45974 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 42.80000 | 1.07818E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
10 | SMSTORE4 | Heating | 4392.45699 | 5270.94839 | 0.18947 | 0.22736 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 12.70000 | 9.15345E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
11 | LGSTORE2 | Cooling | 29351.87033 | 35222.24440 | 2.16133 | 2.59359 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 42.71917 | 1.07817E-002 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
12 | LGSTORE2 | Heating | 8945.36390 | 10734.43668 | 0.36980 | 0.44376 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 | 12.70000 | 9.15345E-003 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
13 | SMSTORE5 | Cooling | 15525.84668 | 18631.01602 | 1.14326 | 1.37191 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 42.71917 | 1.07817E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
14 | SMSTORE5 | Heating | 4689.90481 | 5627.88577 | 0.19474 | 0.23368 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 | 12.70000 | 9.15345E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
15 | SMSTORE6 | Cooling | 15477.40757 | 18572.88909 | 1.13969 | 1.36763 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 42.71917 | 1.07817E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
16 | SMSTORE6 | Heating | 4714.09379 | 5656.91255 | 0.19573 | 0.23487 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 | 12.70000 | 9.15345E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
17 | SMSTORE7 | Cooling | 15582.39310 | 18698.87172 | 1.14742 | 1.37691 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 42.71917 | 1.07817E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
18 | SMSTORE7 | Heating | 5032.75386 | 6039.30463 | 0.20871 | 0.25045 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 | 12.70000 | 9.15345E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
19 | SMSTORE8 | Cooling | 18640.43190 | 22368.51828 | 1.37252 | 1.64702 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | 42.31500 | 1.07810E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
20 | SMSTORE8 | Heating | 5994.69626 | 7193.63551 | 0.25020 | 0.30024 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 | 12.70000 | 9.15345E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC_1:1 | Cooling | Sensible | 48433.92 | 2.91101 | 2.91101 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
2 | PSZ-AC_1:1 | Heating | Sensible | 14602.60 | 0.45506 | 0.45506 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 |
3 | PSZ-AC_2:2 | Cooling | Sensible | 24353.47 | 1.46543 | 1.46543 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
4 | PSZ-AC_2:2 | Heating | Sensible | 7082.67 | 0.21842 | 0.21842 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
5 | PSZ-AC_3:3 | Cooling | Sensible | 24346.02 | 1.46487 | 1.46487 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
6 | PSZ-AC_3:3 | Heating | Sensible | 7100.80 | 0.21921 | 0.21921 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
7 | PSZ-AC_4:4 | Cooling | Sensible | 24388.50 | 1.46804 | 1.46804 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
8 | PSZ-AC_4:4 | Heating | Sensible | 7146.42 | 0.22121 | 0.22121 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
9 | PSZ-AC_5:5 | Cooling | Sensible | 24277.22 | 1.45974 | 1.45974 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
10 | PSZ-AC_5:5 | Heating | Sensible | 7286.98 | 0.22736 | 0.22736 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
11 | PSZ-AC_6:6 | Cooling | Sensible | 44184.80 | 2.59359 | 2.59359 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
12 | PSZ-AC_6:6 | Heating | Sensible | 14338.99 | 0.44376 | 0.44376 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 |
13 | PSZ-AC_7:7 | Cooling | Sensible | 23098.63 | 1.37191 | 1.37191 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
14 | PSZ-AC_7:7 | Heating | Sensible | 7444.57 | 0.23368 | 0.23368 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 |
15 | PSZ-AC_8:8 | Cooling | Sensible | 23041.14 | 1.36763 | 1.36763 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
16 | PSZ-AC_8:8 | Heating | Sensible | 7472.33 | 0.23487 | 0.23487 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 |
17 | PSZ-AC_9:9 | Cooling | Sensible | 23164.07 | 1.37691 | 1.37691 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
18 | PSZ-AC_9:9 | Heating | Sensible | 7836.67 | 0.25045 | 0.25045 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 |
19 | PSZ-AC_10:10 | Cooling | Sensible | 26668.66 | 1.64702 | 1.64702 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
20 | PSZ-AC_10:10 | Heating | Sensible | 8987.95 | 0.30024 | 0.30024 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | LGSTORE1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.91101 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.46543 |
3 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.46487 |
4 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.46804 |
5 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE4 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.45974 |
6 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | LGSTORE2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.59359 |
7 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE5 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.37191 |
8 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.36763 |
9 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE7 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.37691 |
10 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE8 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.64702 |
11 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.91101 |
12 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.91101 |
13 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.91101 |
14 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 2.91101 |
15 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.91101 |
16 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Main Design Air Flow Rate [m3/s] | 2.91101 |
17 | AirLoopHVAC | PSZ-AC_1:1 | User Heating Air Flow Ratio [] | 1.00000 |
18 | AirLoopHVAC | PSZ-AC_1:1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
19 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.46543 |
20 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.46543 |
21 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.46543 |
22 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.46543 |
23 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.46543 |
24 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Main Design Air Flow Rate [m3/s] | 1.46543 |
25 | AirLoopHVAC | PSZ-AC_2:2 | User Heating Air Flow Ratio [] | 1.00000 |
26 | AirLoopHVAC | PSZ-AC_2:2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
27 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.46487 |
28 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.46487 |
29 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.46487 |
30 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.46487 |
31 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.46487 |
32 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Main Design Air Flow Rate [m3/s] | 1.46487 |
33 | AirLoopHVAC | PSZ-AC_3:3 | User Heating Air Flow Ratio [] | 1.00000 |
34 | AirLoopHVAC | PSZ-AC_3:3 | Calculated Heating Air Flow Ratio [] | 1.00000 |
35 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.46804 |
36 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.46804 |
37 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.46804 |
38 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.46804 |
39 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.46804 |
40 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Main Design Air Flow Rate [m3/s] | 1.46804 |
41 | AirLoopHVAC | PSZ-AC_4:4 | User Heating Air Flow Ratio [] | 1.00000 |
42 | AirLoopHVAC | PSZ-AC_4:4 | Calculated Heating Air Flow Ratio [] | 1.00000 |
43 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.45974 |
44 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.45974 |
45 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.45974 |
46 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.45974 |
47 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.45974 |
48 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Main Design Air Flow Rate [m3/s] | 1.45974 |
49 | AirLoopHVAC | PSZ-AC_5:5 | User Heating Air Flow Ratio [] | 1.00000 |
50 | AirLoopHVAC | PSZ-AC_5:5 | Calculated Heating Air Flow Ratio [] | 1.00000 |
51 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.59359 |
52 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.59359 |
53 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.59359 |
54 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Heating Design Air Flow Rate [m3/s] | 2.59359 |
55 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.59359 |
56 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Main Design Air Flow Rate [m3/s] | 2.59359 |
57 | AirLoopHVAC | PSZ-AC_6:6 | User Heating Air Flow Ratio [] | 1.00000 |
58 | AirLoopHVAC | PSZ-AC_6:6 | Calculated Heating Air Flow Ratio [] | 1.00000 |
59 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.37191 |
60 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.37191 |
61 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.37191 |
62 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.37191 |
63 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.37191 |
64 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Main Design Air Flow Rate [m3/s] | 1.37191 |
65 | AirLoopHVAC | PSZ-AC_7:7 | User Heating Air Flow Ratio [] | 1.00000 |
66 | AirLoopHVAC | PSZ-AC_7:7 | Calculated Heating Air Flow Ratio [] | 1.00000 |
67 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.36763 |
68 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.36763 |
69 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.36763 |
70 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.36763 |
71 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.36763 |
72 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Main Design Air Flow Rate [m3/s] | 1.36763 |
73 | AirLoopHVAC | PSZ-AC_8:8 | User Heating Air Flow Ratio [] | 1.00000 |
74 | AirLoopHVAC | PSZ-AC_8:8 | Calculated Heating Air Flow Ratio [] | 1.00000 |
75 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.37691 |
76 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.37691 |
77 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.37691 |
78 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.37691 |
79 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.37691 |
80 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Main Design Air Flow Rate [m3/s] | 1.37691 |
81 | AirLoopHVAC | PSZ-AC_9:9 | User Heating Air Flow Ratio [] | 1.00000 |
82 | AirLoopHVAC | PSZ-AC_9:9 | Calculated Heating Air Flow Ratio [] | 1.00000 |
83 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.64702 |
84 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.64702 |
85 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.64702 |
86 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.64702 |
87 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.64702 |
88 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Main Design Air Flow Rate [m3/s] | 1.64702 |
89 | AirLoopHVAC | PSZ-AC_10:10 | User Heating Air Flow Ratio [] | 1.00000 |
90 | AirLoopHVAC | PSZ-AC_10:10 | Calculated Heating Air Flow Ratio [] | 1.00000 |
91 | AirLoopHVAC | PSZ-AC_1:1 | Design Supply Air Flow Rate [m3/s] | 2.91101 |
92 | AirLoopHVAC | PSZ-AC_2:2 | Design Supply Air Flow Rate [m3/s] | 1.46543 |
93 | AirLoopHVAC | PSZ-AC_3:3 | Design Supply Air Flow Rate [m3/s] | 1.46487 |
94 | AirLoopHVAC | PSZ-AC_4:4 | Design Supply Air Flow Rate [m3/s] | 1.46804 |
95 | AirLoopHVAC | PSZ-AC_5:5 | Design Supply Air Flow Rate [m3/s] | 1.45974 |
96 | AirLoopHVAC | PSZ-AC_6:6 | Design Supply Air Flow Rate [m3/s] | 2.59359 |
97 | AirLoopHVAC | PSZ-AC_7:7 | Design Supply Air Flow Rate [m3/s] | 1.37191 |
98 | AirLoopHVAC | PSZ-AC_8:8 | Design Supply Air Flow Rate [m3/s] | 1.36763 |
99 | AirLoopHVAC | PSZ-AC_9:9 | Design Supply Air Flow Rate [m3/s] | 1.37691 |
100 | AirLoopHVAC | PSZ-AC_10:10 | Design Supply Air Flow Rate [m3/s] | 1.64702 |
101 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.91101 |
102 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41148 |
103 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.91101 |
104 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 3114.91390 |
105 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.91101 |
106 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.91101 |
107 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.91101 |
108 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.92126 |
109 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.91101 |
110 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.45550 |
111 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.94067 |
112 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 72287.21000 |
113 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 36143.60500 |
114 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
115 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
116 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 72287.21000 |
117 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 71890.16892 |
118 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
119 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
120 | Coil:Heating:Fuel | PSZ-AC_1:1 HEATING COIL | Design Size Nominal Capacity [W] | 71890.16892 |
121 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.46543 |
122 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
123 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.46543 |
124 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1568.07522 |
125 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.46543 |
126 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.46543 |
127 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.46543 |
128 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.96718 |
129 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.46543 |
130 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.73271 |
131 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.97695 |
132 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 36390.02000 |
133 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 18195.01000 |
134 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
135 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
136 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 36390.02000 |
137 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 35571.44950 |
138 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
139 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
140 | Coil:Heating:Fuel | PSZ-AC_2:2 HEATING COIL | Design Size Nominal Capacity [W] | 35571.44950 |
141 | Controller:OutdoorAir | PSZ-AC_3:3_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.46487 |
142 | Controller:OutdoorAir | PSZ-AC_3:3_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
143 | Fan:SystemModel | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.46487 |
144 | Fan:SystemModel | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1567.47999 |
145 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.46487 |
146 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.46487 |
147 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.46487 |
148 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.96681 |
149 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.46487 |
150 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.73243 |
151 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.97658 |
152 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 36376.21000 |
153 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 18188.10500 |
154 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
155 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
156 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 36376.21000 |
157 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 35558.71801 |
158 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
159 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
160 | Coil:Heating:Fuel | PSZ-AC_3:3 HEATING COIL | Design Size Nominal Capacity [W] | 35558.71801 |
161 | Controller:OutdoorAir | PSZ-AC_4:4_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.46804 |
162 | Controller:OutdoorAir | PSZ-AC_4:4_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
163 | Fan:SystemModel | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.46804 |
164 | Fan:SystemModel | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1570.87058 |
165 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.46804 |
166 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.46804 |
167 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.46804 |
168 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.96891 |
169 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.46804 |
170 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.73402 |
171 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.97869 |
172 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 36454.89000 |
173 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 18227.44500 |
174 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
175 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
176 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 36454.89000 |
177 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 35631.10632 |
178 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
179 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
180 | Coil:Heating:Fuel | PSZ-AC_4:4 HEATING COIL | Design Size Nominal Capacity [W] | 35631.10632 |
181 | Controller:OutdoorAir | PSZ-AC_5:5_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.45974 |
182 | Controller:OutdoorAir | PSZ-AC_5:5_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
183 | Fan:SystemModel | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.45974 |
184 | Fan:SystemModel | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1561.98865 |
185 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.45974 |
186 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.45974 |
187 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.45974 |
188 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.96343 |
189 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.45974 |
190 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.72987 |
191 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.97316 |
192 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 36248.77000 |
193 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 18124.38500 |
194 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
195 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
196 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 36248.77000 |
197 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 35441.47883 |
198 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
199 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
200 | Coil:Heating:Fuel | PSZ-AC_5:5 HEATING COIL | Design Size Nominal Capacity [W] | 35441.47883 |
201 | Controller:OutdoorAir | PSZ-AC_6:6_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.59359 |
202 | Controller:OutdoorAir | PSZ-AC_6:6_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41148 |
203 | Fan:SystemModel | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.59359 |
204 | Fan:SystemModel | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 2775.26507 |
205 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.59359 |
206 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.59359 |
207 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.59359 |
208 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.71177 |
209 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.59359 |
210 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.29680 |
211 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.72906 |
212 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 64405.04000 |
213 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 32202.52000 |
214 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
215 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
216 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 64405.04000 |
217 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 64479.44165 |
218 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
219 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
220 | Coil:Heating:Fuel | PSZ-AC_6:6 HEATING COIL | Design Size Nominal Capacity [W] | 64479.44165 |
221 | Controller:OutdoorAir | PSZ-AC_7:7_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.37191 |
222 | Controller:OutdoorAir | PSZ-AC_7:7_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
223 | Fan:SystemModel | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.37191 |
224 | Fan:SystemModel | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1518.92241 |
225 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.37191 |
226 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.37191 |
227 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.37191 |
228 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.90546 |
229 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.37191 |
230 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.68596 |
231 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.91461 |
232 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 34067.80000 |
233 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 17033.90000 |
234 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
235 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
236 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 34067.80000 |
237 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 33981.02581 |
238 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
239 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
240 | Coil:Heating:Fuel | PSZ-AC_7:7 HEATING COIL | Design Size Nominal Capacity [W] | 33981.02581 |
241 | Controller:OutdoorAir | PSZ-AC_8:8_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.36763 |
242 | Controller:OutdoorAir | PSZ-AC_8:8_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
243 | Fan:SystemModel | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.36763 |
244 | Fan:SystemModel | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1514.18354 |
245 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.36763 |
246 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.36763 |
247 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.36763 |
248 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.90264 |
249 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.36763 |
250 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.68382 |
251 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.91175 |
252 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 33961.51000 |
253 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 16980.75500 |
254 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
255 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
256 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 33961.51000 |
257 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 33883.24964 |
258 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
259 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
260 | Coil:Heating:Fuel | PSZ-AC_8:8 HEATING COIL | Design Size Nominal Capacity [W] | 33883.24964 |
261 | Controller:OutdoorAir | PSZ-AC_9:9_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.37691 |
262 | Controller:OutdoorAir | PSZ-AC_9:9_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
263 | Fan:SystemModel | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.37691 |
264 | Fan:SystemModel | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1524.45403 |
265 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.37691 |
266 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.37691 |
267 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.37691 |
268 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.90876 |
269 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.37691 |
270 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.68845 |
271 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.91794 |
272 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 34191.87000 |
273 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 17095.93500 |
274 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
275 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
276 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 34191.87000 |
277 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 34129.65751 |
278 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
279 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
280 | Coil:Heating:Fuel | PSZ-AC_9:9 HEATING COIL | Design Size Nominal Capacity [W] | 34129.65751 |
281 | Controller:OutdoorAir | PSZ-AC_10:10_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.64702 |
282 | Controller:OutdoorAir | PSZ-AC_10:10_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
283 | Fan:SystemModel | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.64702 |
284 | Fan:SystemModel | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1762.39396 |
285 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.64702 |
286 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.64702 |
287 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.64702 |
288 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.08704 |
289 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.64702 |
290 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.82351 |
291 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.09801 |
292 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 39705.60000 |
293 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 19852.80000 |
294 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.71045 |
295 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.71045 |
296 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 39705.60000 |
297 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 40268.01972 |
298 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
299 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
300 | Coil:Heating:Fuel | PSZ-AC_10:10 HEATING COIL | Design Size Nominal Capacity [W] | 40268.01972 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | 69990.7 | 10.86 | 10.86 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | 35233.9 | 11.95 | 11.95 | |||
3 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | 35220.6 | 11.95 | 11.95 | |||
4 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | 35296.7 | 11.95 | 11.95 | |||
5 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | 35097.2 | 11.95 | 11.95 | |||
6 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | 62358.9 | 11.77 | 11.77 | |||
7 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | 32985.5 | 11.95 | 11.95 | |||
8 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | 32882.6 | 11.95 | 11.95 | |||
9 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | 33105.6 | 11.95 | 11.95 | |||
10 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | 38407.0 | 11.72 | 11.72 |
Zone Name | # Surfaces | |
1 | LGSTORE1 | 15 |
2 | SMSTORE1 | 11 |
3 | SMSTORE2 | 11 |
4 | SMSTORE3 | 11 |
5 | SMSTORE4 | 11 |
6 | LGSTORE2 | 15 |
7 | SMSTORE5 | 11 |
8 | SMSTORE6 | 11 |
9 | SMSTORE7 | 11 |
10 | SMSTORE8 | 11 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | LGSTORE1_WALL_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | LGSTORE1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 71.15 | 78.94 | 71.15 | 0.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | LGSTORE1_WALL_3_DOOR_1 | Door | LGSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
4 | LGSTORE1_WALL_3_DOOR_2 | Door | LGSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
5 | LGSTORE1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
6 | LGSTORE1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 58.18 | 78.94 | 58.18 | 180.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
7 | LGSTORE1_WALL_1_WINDOW_1 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.22 | N/A | 2.860 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
8 | LGSTORE1_WALL_1_WINDOW_2 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.22 | N/A | 2.860 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
9 | LGSTORE1_WALL_1_WINDOW_3 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.22 | N/A | 2.860 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
10 | LGSTORE1_WALL_1_WINDOW_4 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.22 | N/A | 2.860 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
11 | LGSTORE1_WALL_1_DOOR_1 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.22 | N/A | 2.860 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
12 | LGSTORE1_WALL_1_DOOR_2 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.22 | N/A | 2.860 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
13 | LGSTORE1_FLOOR | Floor | CTF - ConductionTransferFunction | LGSTORE1_FLOOR_FFACTOR | 0.199 | 0.190 | 348.39 | 348.39 | 348.39 | 270.00 | 180.00 | 22.86 | 15.24 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | LGSTORE1_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 348.39 | 348.39 | 348.39 | 270.00 | 0.00 | 22.86 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
15 | LGSTORE1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 696.77 | 696.77 | 696.77 | 0.00 | 90.00 | 696.77 | 1.00 | 0.00 | LGSTORE1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
16 | SMSTORE1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 29.09 | 39.47 | 29.09 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
17 | SMSTORE1_WALL_1_WINDOW_1 | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.22 | N/A | 2.860 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
18 | SMSTORE1_WALL_1_WINDOW_2 | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.22 | N/A | 2.860 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
19 | SMSTORE1_WALL_1_DOOR | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.22 | N/A | 2.860 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
20 | SMSTORE1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | SMSTORE1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 35.57 | 39.47 | 35.57 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | SMSTORE1_WALL_3_DOOR | Door | SMSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
23 | SMSTORE1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE2_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | SMSTORE1_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE1_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | SMSTORE1_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
26 | SMSTORE1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
27 | SMSTORE2_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | SMSTORE2_WALL_1_WINDOW_1 | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.22 | N/A | 2.860 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
29 | SMSTORE2_WALL_1_WINDOW_2 | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.22 | N/A | 2.860 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
30 | SMSTORE2_WALL_1_DOOR | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.22 | N/A | 2.860 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
31 | SMSTORE2_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | SMSTORE2_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | SMSTORE2_WALL_3_DOOR | Door | SMSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
34 | SMSTORE2_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE3_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | SMSTORE2_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE2_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | SMSTORE2_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | SMSTORE2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | SMSTORE3_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | SMSTORE3_WALL_1_WINDOW_1 | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.22 | N/A | 2.860 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
40 | SMSTORE3_WALL_1_WINDOW_2 | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.22 | N/A | 2.860 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
41 | SMSTORE3_WALL_1_DOOR | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.22 | N/A | 2.860 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
42 | SMSTORE3_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE2_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | SMSTORE3_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | SMSTORE3_WALL_3_DOOR | Door | SMSTORE3_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
45 | SMSTORE3_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE4_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | SMSTORE3_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE3_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
47 | SMSTORE3_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
48 | SMSTORE3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
49 | SMSTORE4_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | SMSTORE4_WALL_1_WINDOW_1 | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.22 | N/A | 2.860 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
51 | SMSTORE4_WALL_1_WINDOW_2 | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.22 | N/A | 2.860 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
52 | SMSTORE4_WALL_1_DOOR | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.22 | N/A | 2.860 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | SMSTORE4_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE3_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | SMSTORE4_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | SMSTORE4_WALL_3_DOOR | Door | SMSTORE4_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | SMSTORE4_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE2_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | SMSTORE4_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE4_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | SMSTORE4_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | SMSTORE4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | LGSTORE2_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE4_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | LGSTORE2_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 71.19 | 78.94 | 71.19 | 0.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
62 | LGSTORE2_WALL_3_DOOR_1 | Door | LGSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
63 | LGSTORE2_WALL_3_DOOR_2 | Door | LGSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
64 | LGSTORE2_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE5_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LGSTORE2_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 58.22 | 78.94 | 58.22 | 180.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
66 | LGSTORE2_WALL_1_WINDOW_1 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.22 | N/A | 2.860 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | LGSTORE2_WALL_1_WINDOW_2 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.22 | N/A | 2.860 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | LGSTORE2_WALL_1_WINDOW_3 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.22 | N/A | 2.860 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | LGSTORE2_WALL_1_WINDOW_4 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.22 | N/A | 2.860 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LGSTORE2_WALL_1_DOOR_1 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.22 | N/A | 2.860 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
71 | LGSTORE2_WALL_1_DOOR_2 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.22 | N/A | 2.860 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
72 | LGSTORE2_FLOOR | Floor | CTF - ConductionTransferFunction | LGSTORE2_FLOOR_FFACTOR | 0.112 | 0.109 | 348.39 | 348.39 | 348.39 | 270.00 | 180.00 | 22.86 | 15.24 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
73 | LGSTORE2_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 348.39 | 348.39 | 348.39 | 270.00 | 0.00 | 22.86 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
74 | LGSTORE2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 696.77 | 696.77 | 696.77 | 0.00 | 90.00 | 696.77 | 1.00 | 0.00 | LGSTORE2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
75 | SMSTORE5_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | SMSTORE5_WALL_1_WINDOW_1 | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.22 | N/A | 2.860 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
77 | SMSTORE5_WALL_1_WINDOW_2 | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.22 | N/A | 2.860 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | SMSTORE5_WALL_1_DOOR | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.22 | N/A | 2.860 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
79 | SMSTORE5_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE2_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | SMSTORE5_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 35.59 | 39.47 | 35.59 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | SMSTORE5_WALL_3_DOOR | Door | SMSTORE5_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
82 | SMSTORE5_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE6_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
83 | SMSTORE5_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE5_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
84 | SMSTORE5_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
85 | SMSTORE5_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE5_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | SMSTORE6_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | SMSTORE6_WALL_1_WINDOW_1 | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.22 | N/A | 2.860 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | SMSTORE6_WALL_1_WINDOW_2 | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.22 | N/A | 2.860 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
89 | SMSTORE6_WALL_1_DOOR | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.22 | N/A | 2.860 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | SMSTORE6_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE5_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | SMSTORE6_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | SMSTORE6_WALL_3_DOOR | Door | SMSTORE6_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
93 | SMSTORE6_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE7_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | SMSTORE6_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE6_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
95 | SMSTORE6_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
96 | SMSTORE6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
97 | SMSTORE7_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | SMSTORE7_WALL_1_WINDOW_1 | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.22 | N/A | 2.860 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | SMSTORE7_WALL_1_WINDOW_2 | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.22 | N/A | 2.860 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
100 | SMSTORE7_WALL_1_DOOR | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.22 | N/A | 2.860 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
101 | SMSTORE7_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE6_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
102 | SMSTORE7_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 35.59 | 39.47 | 35.59 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | SMSTORE7_WALL_3_DOOR | Door | SMSTORE7_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
104 | SMSTORE7_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE8_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | SMSTORE7_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE7_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
106 | SMSTORE7_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
107 | SMSTORE7_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE7_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
108 | SMSTORE8_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | SMSTORE8_WALL_1_WINDOW_1 | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.22 | N/A | 2.860 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
110 | SMSTORE8_WALL_1_WINDOW_2 | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.22 | N/A | 2.860 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
111 | SMSTORE8_WALL_1_DOOR | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.22 | N/A | 2.860 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
112 | SMSTORE8_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE7_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | SMSTORE8_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | SMSTORE8_WALL_3_DOOR | Door | SMSTORE8_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
115 | SMSTORE8_WALL_4 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | SMSTORE8_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE8_FLOOR_FFACTOR | 0.289 | 0.270 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | SMSTORE8_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | SMSTORE8_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE8_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | LGSTORE1 | RunPeriod: RUNPERIOD 1 | 3.2575425977E-002 | 6.4682724424E-002 | Pass | Pass | 3.4795031901E-002 | 9.7289964067E-002 | Pass | Pass |
2 | SMSTORE1 | RunPeriod: RUNPERIOD 1 | 2.8067781509E-002 | 6.8429487306E-002 | Pass | Pass | 3.3832038833E-002 | 9.5269560514E-002 | Pass | Pass |
3 | SMSTORE2 | RunPeriod: RUNPERIOD 1 | 3.8683150737E-002 | 7.4749709584E-002 | Pass | Pass | 0.1381519648 | 1.1980965863 | Pass | Pass |
4 | SMSTORE3 | RunPeriod: RUNPERIOD 1 | 3.9216122710E-002 | 7.2970979676E-002 | Pass | Pass | 0.1505144603 | 1.3113284906 | Pass | Pass |
5 | SMSTORE4 | RunPeriod: RUNPERIOD 1 | 3.9664728407E-002 | 7.0238963050E-002 | Pass | Pass | 0.1739406876 | 1.5201892696 | Pass | Pass |
6 | LGSTORE2 | RunPeriod: RUNPERIOD 1 | 3.4243318465E-002 | 4.8137113430E-002 | Pass | Pass | 0.1592499325 | 1.3859415795 | Pass | Pass |
7 | SMSTORE5 | RunPeriod: RUNPERIOD 1 | 3.3810443647E-002 | 4.6087785258E-002 | Pass | Pass | 0.4242843778 | 3.5731342575 | Pass | Pass |
8 | SMSTORE6 | RunPeriod: RUNPERIOD 1 | 3.4179235925E-002 | 4.6043472515E-002 | Pass | Pass | 0.4256396932 | 4.1789083575 | Pass | Pass |
9 | SMSTORE7 | RunPeriod: RUNPERIOD 1 | 3.5729880780E-002 | 4.6178101663E-002 | Pass | Pass | 2.6150787455 | 30.4633810540 | Pass | Pass |
10 | SMSTORE8 | RunPeriod: RUNPERIOD 1 | 4.2838988300E-002 | 4.8996905180E-002 | Pass | Pass | 0.2003169709 | 1.6465799535 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:02
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 2257.57 | -413.8 | 0.00 | -978.3 | 2957.98 | 3823.56 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:02
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 12.70 | 0.00 | 12.70 | Wetbulb [C] | 2.00 | 170.00 |
DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 42.80 | 9.70 | 23.80 | Wetbulb [C] | 5.00 | 80.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 2.40 | 26 | |||
Feb | 9.60 | 38 | |||
Mar | 3.60 | 37 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 0.00 | 0 | |||
Jul | 1.20 | 13 | |||
Aug | 0.00 | 0 | |||
Sep | 0.00 | 0 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 18.00 | 37 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:02
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_2 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE1_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 78.94 | 71.15 | 0.00 | 90.00 | N |
LGSTORE1_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 78.94 | 58.18 | 180.00 | 90.00 | S |
LGSTORE1_FLOOR | LGSTORE1_FLOOR_FFACTOR | 1.00 | 0.193 | 0.199 | 348.39 | 348.39 | 270.00 | 180.00 | |
LGSTORE1_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 348.39 | 348.39 | 270.00 | 0.00 | |
SMSTORE1_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 39.47 | 29.09 | 180.00 | 90.00 | S |
SMSTORE1_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 39.47 | 35.57 | 0.00 | 90.00 | N |
SMSTORE1_FLOOR | SMSTORE1_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE1_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE2_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE2_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE2_FLOOR | SMSTORE2_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE2_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE3_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE3_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE3_FLOOR | SMSTORE3_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE3_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE4_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE4_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE4_FLOOR | SMSTORE4_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE4_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 | |
LGSTORE2_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 78.94 | 71.19 | 0.00 | 90.00 | N |
LGSTORE2_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 78.94 | 58.22 | 180.00 | 90.00 | S |
LGSTORE2_FLOOR | LGSTORE2_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 348.39 | 348.39 | 270.00 | 180.00 | |
LGSTORE2_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 348.39 | 348.39 | 270.00 | 0.00 | |
SMSTORE5_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE5_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE5_FLOOR | SMSTORE5_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE5_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE6_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE6_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE6_FLOOR | SMSTORE6_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE6_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE7_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE7_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE7_FLOOR | SMSTORE7_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE7_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE8_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE8_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE8_WALL_4 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE8_FLOOR | SMSTORE8_FLOOR_FFACTOR | 1.00 | 0.276 | 0.289 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE8_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE1_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE2_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE2_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE3_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE3_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE4_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE4_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
LGSTORE2_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE2_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE5_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE5_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE6_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE6_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE7_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE7_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE8_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 696.77 | 0.00 | 90.00 | N | ||
SMSTORE1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
LGSTORE2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 696.77 | 0.00 | 90.00 | N | ||
SMSTORE5_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE7_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE8_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.503_SHGC_0.22 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.860 | 0.221 | 0.243 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.503_SHGC_0.22 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.860 | 0.221 | 0.243 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_3 | NONRESWINDOW_U_0.503_SHGC_0.22 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.860 | 0.221 | 0.243 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_4 | NONRESWINDOW_U_0.503_SHGC_0.22 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.860 | 0.221 | 0.243 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_DOOR_1 | NONRESWINDOW_U_0.503_SHGC_0.22 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.860 | 0.221 | 0.243 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_DOOR_2 | NONRESWINDOW_U_0.503_SHGC_0.22 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.860 | 0.221 | 0.243 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.503_SHGC_0.22 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.860 | 0.221 | 0.243 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.503_SHGC_0.22 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.860 | 0.221 | 0.243 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_DOOR | NONRESWINDOW_U_0.503_SHGC_0.22 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.860 | 0.221 | 0.243 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.503_SHGC_0.22 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.860 | 0.221 | 0.243 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.503_SHGC_0.22 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.860 | 0.221 | 0.243 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_DOOR | NONRESWINDOW_U_0.503_SHGC_0.22 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.860 | 0.221 | 0.243 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.503_SHGC_0.22 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.860 | 0.221 | 0.243 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.503_SHGC_0.22 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.860 | 0.221 | 0.243 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_DOOR | NONRESWINDOW_U_0.503_SHGC_0.22 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.860 | 0.221 | 0.243 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.503_SHGC_0.22 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.860 | 0.221 | 0.243 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.503_SHGC_0.22 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.860 | 0.221 | 0.243 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_DOOR | NONRESWINDOW_U_0.503_SHGC_0.22 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.860 | 0.221 | 0.243 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.503_SHGC_0.22 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.860 | 0.221 | 0.243 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.503_SHGC_0.22 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.860 | 0.221 | 0.243 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_3 | NONRESWINDOW_U_0.503_SHGC_0.22 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.860 | 0.221 | 0.243 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_4 | NONRESWINDOW_U_0.503_SHGC_0.22 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.860 | 0.221 | 0.243 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_DOOR_1 | NONRESWINDOW_U_0.503_SHGC_0.22 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.860 | 0.221 | 0.243 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_DOOR_2 | NONRESWINDOW_U_0.503_SHGC_0.22 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.860 | 0.221 | 0.243 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.503_SHGC_0.22 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.860 | 0.221 | 0.243 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.503_SHGC_0.22 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.860 | 0.221 | 0.243 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_DOOR | NONRESWINDOW_U_0.503_SHGC_0.22 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.860 | 0.221 | 0.243 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.503_SHGC_0.22 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.860 | 0.221 | 0.243 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.503_SHGC_0.22 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.860 | 0.221 | 0.243 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_DOOR | NONRESWINDOW_U_0.503_SHGC_0.22 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.860 | 0.221 | 0.243 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.503_SHGC_0.22 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.860 | 0.221 | 0.243 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.503_SHGC_0.22 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.860 | 0.221 | 0.243 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_DOOR | NONRESWINDOW_U_0.503_SHGC_0.22 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.860 | 0.221 | 0.243 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.503_SHGC_0.22 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.860 | 0.221 | 0.243 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.503_SHGC_0.22 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.860 | 0.221 | 0.243 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_DOOR | NONRESWINDOW_U_0.503_SHGC_0.22 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.860 | 0.221 | 0.243 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
Total or Average | 124.40 | 2.860 | 0.221 | 0.243 | |||||||||||||||||
North Total or Average | 0.00 | - | - | - | |||||||||||||||||
Non-North Total or Average | 124.40 | 2.860 | 0.221 | 0.243 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
LGSTORE1_WALL_3_DOOR_1 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.90 | LGSTORE1_WALL_3 |
LGSTORE1_WALL_3_DOOR_2 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.90 | LGSTORE1_WALL_3 |
SMSTORE1_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.90 | SMSTORE1_WALL_3 |
SMSTORE2_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE2_WALL_3 |
SMSTORE3_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE3_WALL_3 |
SMSTORE4_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE4_WALL_3 |
LGSTORE2_WALL_3_DOOR_1 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | LGSTORE2_WALL_3 |
LGSTORE2_WALL_3_DOOR_2 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | LGSTORE2_WALL_3 |
SMSTORE5_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE5_WALL_3 |
SMSTORE6_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE6_WALL_3 |
SMSTORE7_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE7_WALL_3 |
SMSTORE8_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE8_WALL_3 |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:02
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
LGSTORE1_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_4 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_DOOR_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_DOOR_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_4 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_DOOR_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_DOOR_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:02
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
LGSTORE1_LIGHTS | LGSTORE1 | LGSTORE1 | GENERAL | 9.6053 | 348.39 | 3346.35 | LightsWired | LTG_SCH_BASE_LPD1 | 83.91 | 168.00 | 82.62 | 0.0000 | Y | 51.90 |
LGSTORE1_LIGHTS_ALLOWANCE | LGSTORE1 | LGSTORE1 | GENERAL | 5.6969 | 348.39 | 1984.73 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | 97.50 | 112.00 | 94.53 | 0.0000 | Y | 35.22 |
SMSTORE1_LIGHTS | SMSTORE1 | SMSTORE1 | GENERAL | 9.7206 | 174.19 | 1693.26 | LightsWired | LTG_SCH_BASE_SMALL_LPD1 | 85.41 | 168.00 | 84.05 | 0.0000 | Y | 26.72 |
SMSTORE1_LIGHTS_ALLOWANCE | SMSTORE1 | SMSTORE1 | GENERAL | 8.5685 | 174.19 | 1492.57 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | 97.50 | 112.00 | 94.53 | 0.0000 | Y | 26.49 |
SMSTORE2_LIGHTS | SMSTORE2 | SMSTORE2 | GENERAL | 9.6995 | 174.19 | 1689.58 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 68.73 | 168.00 | 65.95 | 0.0000 | Y | 20.92 |
SMSTORE2_LIGHTS_ALLOWANCE | SMSTORE2 | SMSTORE2 | GENERAL | 6.9539 | 174.19 | 1211.32 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 84.29 | 73.25 | 0.0000 | Y | 16.66 |
SMSTORE3_LIGHTS | SMSTORE3 | SMSTORE3 | GENERAL | 9.6995 | 174.19 | 1689.58 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 68.73 | 168.00 | 65.95 | 0.0000 | Y | 20.92 |
SMSTORE3_LIGHTS_ALLOWANCE | SMSTORE3 | SMSTORE3 | GENERAL | 6.9539 | 174.19 | 1211.32 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 84.29 | 73.25 | 0.0000 | Y | 16.66 |
SMSTORE4_LIGHTS | SMSTORE4 | SMSTORE4 | GENERAL | 9.6995 | 174.19 | 1689.58 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 68.73 | 168.00 | 65.95 | 0.0000 | Y | 20.92 |
SMSTORE4_LIGHTS_ALLOWANCE | SMSTORE4 | SMSTORE4 | GENERAL | 6.9539 | 174.19 | 1211.32 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 84.29 | 73.25 | 0.0000 | Y | 16.66 |
LGSTORE2_LIGHTS | LGSTORE2 | LGSTORE2 | GENERAL | 9.5842 | 348.39 | 3339.00 | LightsWired | LTG_SCH_BASE_LPD2 | 62.11 | 168.00 | 59.29 | 0.0000 | Y | 37.16 |
LGSTORE2_LIGHTS_ALLOWANCE | LGSTORE2 | LGSTORE2 | GENERAL | 0.0000 | 348.39 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE5_LIGHTS | SMSTORE5 | SMSTORE5 | GENERAL | 9.6995 | 174.19 | 1689.58 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 60.29 | 0.0000 | Y | 19.12 |
SMSTORE5_LIGHTS_ALLOWANCE | SMSTORE5 | SMSTORE5 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE6_LIGHTS | SMSTORE6 | SMSTORE6 | GENERAL | 9.6995 | 174.19 | 1689.58 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 60.29 | 0.0000 | Y | 19.12 |
SMSTORE6_LIGHTS_ALLOWANCE | SMSTORE6 | SMSTORE6 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE7_LIGHTS | SMSTORE7 | SMSTORE7 | GENERAL | 9.6995 | 174.19 | 1689.58 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 60.29 | 0.0000 | Y | 19.12 |
SMSTORE7_LIGHTS_ALLOWANCE | SMSTORE7 | SMSTORE7 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE8_LIGHTS | SMSTORE8 | SMSTORE8 | GENERAL | 9.6995 | 174.19 | 1689.58 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 60.29 | 0.0000 | Y | 19.12 |
SMSTORE8_LIGHTS_ALLOWANCE | SMSTORE8 | SMSTORE8 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
Interior Lighting Total | 6.5342 | 4180.64 | 27316.92 | 366.68 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 455.59 | AstronomicalClock | - | 41.85 | 41.85 | 3.58 | |
EXTERIOR_LIGHTS_B | 2744.24 | AstronomicalClock | - | 83.85 | 62.85 | 32.38 | |
EXTERIOR_LIGHTS_C | 2307.23 | AstronomicalClock | - | 83.85 | 55.85 | 24.19 | |
Exterior Lighting Total | 5507.06 | 60.14 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:02
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 72287.21 | 50679.12 | 21608.09 | 0.70 | 3.40 | |||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 36390.02 | 25512.32 | 10877.70 | 0.70 | 3.80 | |||
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 36376.21 | 25502.63 | 10873.58 | 0.70 | 3.80 | |||
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 36454.89 | 25557.79 | 10897.10 | 0.70 | 3.80 | |||
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 36248.77 | 25413.29 | 10835.48 | 0.70 | 3.80 | |||
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 64405.04 | 45153.09 | 19251.95 | 0.70 | 3.73 | |||
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 34067.80 | 23884.25 | 10183.55 | 0.70 | 3.80 | |||
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 33961.51 | 23809.74 | 10151.77 | 0.70 | 3.80 | |||
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 34191.87 | 23971.24 | 10220.63 | 0.70 | 3.80 | |||
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 39705.60 | 28208.84 | 11496.76 | 0.71 | 3.73 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC_1:1 COOLING COIL | 69990.7 | 10.86 | 10.86 | ||||
PSZ-AC_2:2 COOLING COIL | 35233.9 | 11.95 | 11.95 | ||||
PSZ-AC_3:3 COOLING COIL | 35220.6 | 11.95 | 11.95 | ||||
PSZ-AC_4:4 COOLING COIL | 35296.7 | 11.95 | 11.95 | ||||
PSZ-AC_5:5 COOLING COIL | 35097.2 | 11.95 | 11.95 | ||||
PSZ-AC_6:6 COOLING COIL | 62358.9 | 11.77 | 11.77 | ||||
PSZ-AC_7:7 COOLING COIL | 32985.5 | 11.95 | 11.95 | ||||
PSZ-AC_8:8 COOLING COIL | 32882.6 | 11.95 | 11.95 | ||||
PSZ-AC_9:9 COOLING COIL | 33105.6 | 11.95 | 11.95 | ||||
PSZ-AC_10:10 COOLING COIL | 38407.0 | 11.72 | 11.72 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | 71890.17 | 0.80 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | 35571.45 | 0.80 | |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | 35558.72 | 0.80 | |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | 35631.11 | 0.80 | |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | 35441.48 | 0.80 | |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | 64479.44 | 0.80 | |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | 33981.03 | 0.80 | |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | 33883.25 | 0.80 | |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | 34129.66 | 0.80 | |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | 40268.02 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 2.91 | 3114.91 | 1070.05 | 1.00 | 1.27 | General | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 |
PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 1.47 | 1568.08 | 1070.05 | 1.00 | 1.37 | General | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 |
PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 1.46 | 1567.48 | 1070.05 | 1.00 | 1.37 | General | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 1.47 | 1570.87 | 1070.05 | 1.00 | 1.37 | General | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 1.46 | 1561.99 | 1070.05 | 1.00 | 1.37 | General | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 2.59 | 2775.27 | 1070.05 | 1.00 | 1.28 | General | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 |
PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.37 | 1518.92 | 1107.16 | 1.00 | 1.33 | General | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 |
PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.37 | 1514.18 | 1107.16 | 1.00 | 1.33 | General | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 |
PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.38 | 1524.45 | 1107.16 | 1.00 | 1.33 | General | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 |
PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 1.65 | 1762.39 | 1070.05 | 1.00 | 1.35 | General | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
GAS TANK1 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK2 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK3 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK4 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK5 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK6 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK7 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:02
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
LGSTORE1 | 32943.68 | 39532.42 | 113.47 | 2.426 | 2.911 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 23.89 | 23.89 | 0.00786 | 42.70 | 0.01078 | 0.411 | 0.00 |
SMSTORE1 | 16584.14 | 19900.97 | 114.25 | 1.221 | 1.465 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 23.89 | 23.89 | 0.00789 | 42.80 | 0.01078 | 0.206 | 0.00 |
SMSTORE2 | 16577.85 | 19893.42 | 114.20 | 1.221 | 1.465 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 23.89 | 23.89 | 0.00789 | 42.80 | 0.01078 | 0.206 | 0.00 |
SMSTORE3 | 16613.71 | 19936.45 | 114.45 | 1.223 | 1.468 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 23.89 | 23.89 | 0.00789 | 42.80 | 0.01078 | 0.206 | 0.00 |
SMSTORE4 | 16519.78 | 19823.73 | 113.80 | 1.216 | 1.460 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 23.89 | 23.89 | 0.00789 | 42.80 | 0.01078 | 0.206 | 0.00 |
LGSTORE2 | 29351.87 | 35222.24 | 101.10 | 2.161 | 2.594 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 23.89 | 23.89 | 0.00793 | 42.72 | 0.01078 | 0.411 | 0.00 |
SMSTORE5 | 15525.85 | 18631.02 | 106.96 | 1.143 | 1.372 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 23.89 | 23.89 | 0.00794 | 42.72 | 0.01078 | 0.206 | 0.00 |
SMSTORE6 | 15477.41 | 18572.89 | 106.62 | 1.140 | 1.368 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 23.89 | 23.89 | 0.00794 | 42.72 | 0.01078 | 0.206 | 0.00 |
SMSTORE7 | 15582.39 | 18698.87 | 107.35 | 1.147 | 1.377 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 23.89 | 23.89 | 0.00794 | 42.72 | 0.01078 | 0.206 | 0.00 |
SMSTORE8 | 18640.43 | 22368.52 | 128.41 | 1.373 | 1.647 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | 23.89 | 23.89 | 0.00784 | 42.31 | 0.01078 | 0.206 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
LGSTORE1 | 9161.86 | 10994.23 | 31.56 | 0.379 | 0.455 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 | 21.11 | 21.11 | 0.00836 | 12.70 | 0.00915 | 0.411 | 0.00 |
SMSTORE1 | 4219.68 | 5063.62 | 29.07 | 0.182 | 0.218 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00855 | 12.70 | 0.00915 | 0.206 | 0.00 |
SMSTORE2 | 4235.01 | 5082.02 | 29.17 | 0.183 | 0.219 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00856 | 12.70 | 0.00915 | 0.206 | 0.00 |
SMSTORE3 | 4273.59 | 5128.31 | 29.44 | 0.184 | 0.221 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00855 | 12.70 | 0.00915 | 0.206 | 0.00 |
SMSTORE4 | 4392.46 | 5270.95 | 30.26 | 0.189 | 0.227 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00855 | 12.70 | 0.00915 | 0.206 | 0.00 |
LGSTORE2 | 8945.36 | 10734.44 | 30.81 | 0.370 | 0.444 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 | 21.11 | 21.11 | 0.00841 | 12.70 | 0.00915 | 0.411 | 0.00 |
SMSTORE5 | 4689.90 | 5627.89 | 32.31 | 0.195 | 0.234 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 | 21.11 | 21.11 | 0.00841 | 12.70 | 0.00915 | 0.206 | 0.00 |
SMSTORE6 | 4714.09 | 5656.91 | 32.47 | 0.196 | 0.235 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 | 21.11 | 21.11 | 0.00841 | 12.70 | 0.00915 | 0.206 | 0.00 |
SMSTORE7 | 5032.75 | 6039.30 | 34.67 | 0.209 | 0.250 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 | 21.11 | 21.11 | 0.00839 | 12.70 | 0.00915 | 0.206 | 0.00 |
SMSTORE8 | 5994.70 | 7193.64 | 41.30 | 0.250 | 0.300 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 | 21.11 | 21.11 | 0.00842 | 12.70 | 0.00915 | 0.206 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC_1:1 | 2.91 | 2.91 | 0.46 | 0.46 | 2.9110 | 2.9110 | 2.9110 | 1.0000 | 1.0000 |
PSZ-AC_2:2 | 1.47 | 1.47 | 0.22 | 0.22 | 1.4654 | 1.4654 | 1.4654 | 1.0000 | 1.0000 |
PSZ-AC_3:3 | 1.46 | 1.46 | 0.22 | 0.22 | 1.4649 | 1.4649 | 1.4649 | 1.0000 | 1.0000 |
PSZ-AC_4:4 | 1.47 | 1.47 | 0.22 | 0.22 | 1.4680 | 1.4680 | 1.4680 | 1.0000 | 1.0000 |
PSZ-AC_5:5 | 1.46 | 1.46 | 0.23 | 0.23 | 1.4597 | 1.4597 | 1.4597 | 1.0000 | 1.0000 |
PSZ-AC_6:6 | 2.59 | 2.59 | 0.44 | 0.44 | 2.5936 | 2.5936 | 2.5936 | 1.0000 | 1.0000 |
PSZ-AC_7:7 | 1.37 | 1.37 | 0.23 | 0.23 | 1.3719 | 1.3719 | 1.3719 | 1.0000 | 1.0000 |
PSZ-AC_8:8 | 1.37 | 1.37 | 0.23 | 0.23 | 1.3676 | 1.3676 | 1.3676 | 1.0000 | 1.0000 |
PSZ-AC_9:9 | 1.38 | 1.38 | 0.25 | 0.25 | 1.3769 | 1.3769 | 1.3769 | 1.0000 | 1.0000 |
PSZ-AC_10:10 | 1.65 | 1.65 | 0.30 | 0.30 | 1.6470 | 1.6470 | 1.6470 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 72287.210 | 50679.117 | 2.911010 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 36143.61 | 30873.63 | 1.940673 | 27.43 | 17.39 | 0.00827351 | 12.80 | 10.55 | 0.00700000 | 42.80 | 0.01078182 | 23.86 | 21.2029 | 23.89 | 0.00786050 | 42.6296 | 32937.82 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_1:1 | 71890.169 | 71890.169 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 | 71890.17 | 71890.17 | 2.911006 | 19.58 | 14.74 | 0.00847367 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 14.1353 | 21.11 | 0.00836176 | 53.6342 | 9161.86 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 36390.020 | 25512.315 | 1.465430 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 18195.01 | 15504.14 | 0.976953 | 27.41 | 17.40 | 0.00829360 | 12.80 | 10.55 | 0.00700000 | 42.80 | 0.01078182 | 23.86 | 21.0593 | 23.89 | 0.00788722 | 42.7727 | 16584.14 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_2:2 | 35571.449 | 35571.449 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 35571.45 | 35571.45 | 1.465426 | 19.93 | 15.02 | 0.00863730 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 14.0396 | 21.11 | 0.00855300 | 54.8430 | 4219.68 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_3:3 | 36376.210 | 25502.633 | 1.464870 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 18188.10 | 15497.55 | 0.976580 | 27.41 | 17.40 | 0.00829407 | 12.80 | 10.55 | 0.00700000 | 42.80 | 0.01078182 | 23.86 | 21.0673 | 23.89 | 0.00788758 | 42.7746 | 16577.85 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_3:3 | 35558.718 | 35558.718 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 35558.72 | 35558.72 | 1.464870 | 19.93 | 15.03 | 0.00863993 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 14.0449 | 21.11 | 0.00855602 | 54.8621 | 4235.01 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_4:4 | 36454.890 | 25557.794 | 1.468040 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 18227.44 | 15534.40 | 0.978693 | 27.41 | 17.39 | 0.00829181 | 12.80 | 10.55 | 0.00700000 | 42.80 | 0.01078182 | 23.86 | 21.0218 | 23.89 | 0.00788596 | 42.7660 | 16613.71 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_4:4 | 35631.106 | 35631.106 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 35631.11 | 35631.11 | 1.468038 | 19.93 | 15.02 | 0.00863776 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 14.0146 | 21.11 | 0.00855371 | 54.8475 | 4273.59 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_5:5 | 36248.770 | 25413.288 | 1.459740 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 18124.38 | 15437.83 | 0.973160 | 27.42 | 17.40 | 0.00829779 | 12.80 | 10.55 | 0.00700000 | 42.80 | 0.01078182 | 23.86 | 21.1414 | 23.89 | 0.00789024 | 42.7888 | 16519.78 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_5:5 | 35441.479 | 35441.479 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 35441.48 | 35441.48 | 1.459738 | 19.93 | 15.02 | 0.00863110 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 14.0943 | 21.11 | 0.00854540 | 54.7949 | 4392.46 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_6:6 | 64405.040 | 45153.085 | 2.593590 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 32202.52 | 27246.70 | 1.729060 | 27.76 | 17.59 | 0.00838039 | 12.80 | 10.55 | 0.00700000 | 42.80 | 0.01078182 | 23.86 | 23.7978 | 23.89 | 0.00792754 | 42.9883 | 29351.15 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_6:6 | 64479.442 | 64479.442 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 | 64479.44 | 64479.44 | 2.593591 | 19.44 | 14.74 | 0.00852849 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 15.8652 | 21.11 | 0.00841065 | 53.9434 | 8945.36 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_7:7 | 34067.800 | 23884.253 | 1.371910 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 17033.90 | 14422.34 | 0.914607 | 27.62 | 17.53 | 0.00836470 | 12.80 | 10.55 | 0.00700000 | 42.80 | 0.01078182 | 23.86 | 22.4949 | 23.89 | 0.00793823 | 43.0458 | 15524.92 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_7:7 | 33981.026 | 33981.026 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 | 33981.03 | 33981.03 | 1.371910 | 19.52 | 14.77 | 0.00852261 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 14.9966 | 21.11 | 0.00841131 | 53.9475 | 4689.90 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_8:8 | 33961.510 | 23809.735 | 1.367630 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 16980.76 | 14372.81 | 0.911753 | 27.63 | 17.53 | 0.00836814 | 12.80 | 10.55 | 0.00700000 | 42.80 | 0.01078182 | 23.86 | 22.5652 | 23.89 | 0.00794071 | 43.0591 | 15476.39 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_8:8 | 33883.250 | 33883.250 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 | 33883.25 | 33883.25 | 1.367630 | 19.52 | 14.76 | 0.00852213 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 15.0435 | 21.11 | 0.00841034 | 53.9413 | 4714.09 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_9:9 | 34191.870 | 23971.236 | 1.376910 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 17095.94 | 14479.99 | 0.917940 | 27.61 | 17.52 | 0.00836083 | 12.80 | 10.55 | 0.00700000 | 42.80 | 0.01078182 | 23.86 | 22.4132 | 23.89 | 0.00793546 | 43.0310 | 15580.16 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_9:9 | 34129.658 | 34129.658 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 | 34129.66 | 34129.66 | 1.376906 | 19.51 | 14.74 | 0.00850386 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 14.9421 | 21.11 | 0.00838974 | 53.8110 | 5032.75 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_10:10 | 39705.600 | 28208.844 | 1.647020 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | 19852.80 | 17038.04 | 1.098013 | 27.06 | 17.21 | 0.00820841 | 12.80 | 10.55 | 0.00700000 | 42.31 | 0.01078097 | 23.73 | 18.7374 | 23.89 | 0.00784118 | 42.5266 | 18640.43 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_10:10 | 40268.020 | 40268.020 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 | 40268.02 | 40268.02 | 1.647024 | 19.78 | 14.86 | 0.00851349 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 12.4916 | 21.11 | 0.00842214 | 54.0153 | 5994.70 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:37:02
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 72287.210 | 50679.117 | 2.911010 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.2200 | 1004.8586 | 1.2036 | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.911006 | 3.50367208 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | Sensible | 36143.61 | 30873.63 | 1.0000 | 2.33578468 | 1.940673 | 27.43 | 17.39 | 0.00827351 | 48677.0 | 12.80 | 10.55 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 36143.61 | 42.80 | 0.01078182 | 23.86 | 0.41147883 | 21.2029 | 23.89 | 0.00786050 | 23.89 | 0.00786050 | 42.6296 | 32937.82 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 71890.169 | 71890.169 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.911006 | 3.50367208 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 | Sensible | 71890.17 | 71890.17 | 1.0000 | 3.50367208 | 2.911006 | 19.58 | 14.74 | 0.00847367 | 41176.0 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 71890.17 | 12.70 | 0.00915345 | 12.70 | 0.41147883 | 14.1353 | 20.71 | 0.00836176 | 21.11 | 0.00836176 | 53.6342 | 9161.86 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 36390.020 | 25512.315 | 1.465430 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.2574 | 1004.8586 | 1.2036 | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.465426 | 1.76377952 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | Sensible | 18195.01 | 15504.14 | 1.0000 | 1.17585613 | 0.976953 | 27.41 | 17.40 | 0.00829360 | 48709.3 | 12.80 | 10.55 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 18195.01 | 42.80 | 0.01078182 | 23.86 | 0.20573941 | 21.0593 | 23.89 | 0.00788722 | 23.89 | 0.00788722 | 42.7727 | 16584.14 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 35571.449 | 35571.449 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.465426 | 1.76377952 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 35571.45 | 35571.45 | 1.0000 | 1.76377952 | 1.465426 | 19.93 | 15.02 | 0.00863730 | 41947.6 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 35571.45 | 12.70 | 0.00915345 | 12.70 | 0.20573941 | 14.0396 | 21.11 | 0.00855300 | 21.11 | 0.00855300 | 54.8430 | 4219.68 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 36376.210 | 25502.633 | 1.464870 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.2583 | 1004.8586 | 1.2036 | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.464870 | 1.76311001 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | Sensible | 18188.10 | 15497.55 | 1.0000 | 1.17540679 | 0.976580 | 27.41 | 17.40 | 0.00829407 | 48711.5 | 12.80 | 10.55 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 18188.10 | 42.80 | 0.01078182 | 23.86 | 0.20573941 | 21.0673 | 23.89 | 0.00788758 | 23.89 | 0.00788758 | 42.7746 | 16577.85 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 35558.718 | 35558.718 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.464870 | 1.76311001 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 35558.72 | 35558.72 | 1.0000 | 1.76311001 | 1.464870 | 19.93 | 15.03 | 0.00863993 | 41953.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 35558.72 | 12.70 | 0.00915345 | 12.70 | 0.20573941 | 14.0449 | 21.11 | 0.00855602 | 21.11 | 0.00855602 | 54.8621 | 4235.01 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 36454.890 | 25557.794 | 1.468040 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.2541 | 1004.8586 | 1.2036 | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.468038 | 1.76692376 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | Sensible | 18227.44 | 15534.40 | 1.0000 | 1.17795038 | 0.978693 | 27.41 | 17.39 | 0.00829181 | 48699.9 | 12.80 | 10.55 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 18227.44 | 42.80 | 0.01078182 | 23.86 | 0.20573941 | 21.0218 | 23.89 | 0.00788596 | 23.89 | 0.00788596 | 42.7660 | 16613.71 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 35631.106 | 35631.106 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.468038 | 1.76692376 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 35631.11 | 35631.11 | 1.0000 | 1.76692376 | 1.468038 | 19.93 | 15.02 | 0.00863776 | 41950.9 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 35631.11 | 12.70 | 0.00915345 | 12.70 | 0.20573941 | 14.0146 | 21.11 | 0.00855371 | 21.11 | 0.00855371 | 54.8475 | 4273.59 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 36248.770 | 25413.288 | 1.459740 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.2652 | 1004.8586 | 1.2036 | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.459738 | 1.75693331 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | Sensible | 18124.38 | 15437.83 | 1.0000 | 1.17129049 | 0.973160 | 27.42 | 17.40 | 0.00829779 | 48730.5 | 12.80 | 10.55 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 18124.38 | 42.80 | 0.01078182 | 23.86 | 0.20573941 | 21.1414 | 23.89 | 0.00789024 | 23.89 | 0.00789024 | 42.7888 | 16519.78 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 35441.479 | 35441.479 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.459738 | 1.75693331 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 35441.48 | 35441.48 | 1.0000 | 1.75693331 | 1.459738 | 19.93 | 15.02 | 0.00863110 | 41927.2 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 35441.48 | 12.70 | 0.00915345 | 12.70 | 0.20573941 | 14.0943 | 21.11 | 0.00854540 | 21.11 | 0.00854540 | 54.7949 | 4392.46 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 64405.040 | 45153.085 | 2.593590 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.4187 | 1004.8586 | 1.2036 | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.593591 | 3.12163322 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | Sensible | 32202.52 | 27246.70 | 1.0000 | 2.08108794 | 1.729060 | 27.76 | 17.59 | 0.00838039 | 49283.2 | 12.80 | 10.55 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 32202.52 | 42.80 | 0.01078182 | 23.86 | 0.41147883 | 23.7978 | 23.89 | 0.00792754 | 23.89 | 0.00792754 | 42.9883 | 29351.15 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 64479.442 | 64479.442 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.593591 | 3.12163322 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 | Sensible | 64479.44 | 64479.44 | 1.0000 | 3.12163322 | 2.593591 | 19.44 | 14.74 | 0.00852849 | 41175.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 64479.44 | 12.70 | 0.00915345 | 12.70 | 0.41147883 | 15.8652 | 20.72 | 0.00841065 | 21.11 | 0.00841065 | 53.9434 | 8945.36 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 34067.800 | 23884.253 | 1.371910 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.3896 | 1004.8586 | 1.2036 | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.371910 | 1.65122428 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | Sensible | 17033.90 | 14422.34 | 1.0000 | 1.10081599 | 0.914607 | 27.62 | 17.53 | 0.00836470 | 49106.3 | 12.80 | 10.55 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 17033.90 | 42.80 | 0.01078182 | 23.86 | 0.20573941 | 22.4949 | 23.89 | 0.00793823 | 23.89 | 0.00793823 | 43.0458 | 15524.92 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 33981.026 | 33981.026 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.371910 | 1.65122428 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 | Sensible | 33981.03 | 33981.03 | 1.0000 | 1.65122428 | 1.371910 | 19.52 | 14.77 | 0.00852261 | 41238.5 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 33981.03 | 12.70 | 0.00915345 | 12.70 | 0.20573941 | 14.9966 | 20.72 | 0.00841131 | 21.11 | 0.00841131 | 53.9475 | 4689.90 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 33961.510 | 23809.735 | 1.367630 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.3959 | 1004.8586 | 1.2036 | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.367630 | 1.64607264 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | Sensible | 16980.76 | 14372.81 | 1.0000 | 1.09738174 | 0.911753 | 27.63 | 17.53 | 0.00836814 | 49124.2 | 12.80 | 10.55 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 16980.76 | 42.80 | 0.01078182 | 23.86 | 0.20573941 | 22.5652 | 23.89 | 0.00794071 | 23.89 | 0.00794071 | 43.0591 | 15476.39 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 33883.250 | 33883.250 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.367630 | 1.64607264 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 | Sensible | 33883.25 | 33883.25 | 1.0000 | 1.64607264 | 1.367630 | 19.52 | 14.76 | 0.00852213 | 41232.2 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 33883.25 | 12.70 | 0.00915345 | 12.70 | 0.20573941 | 15.0435 | 20.72 | 0.00841034 | 21.11 | 0.00841034 | 53.9413 | 4714.09 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 34191.870 | 23971.236 | 1.376910 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.3824 | 1004.8586 | 1.2036 | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.376906 | 1.65723772 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | Sensible | 17095.94 | 14479.99 | 1.0000 | 1.10482798 | 0.917940 | 27.61 | 17.52 | 0.00836083 | 49086.2 | 12.80 | 10.55 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 17095.94 | 42.80 | 0.01078182 | 23.86 | 0.20573941 | 22.4132 | 23.89 | 0.00793546 | 23.89 | 0.00793546 | 43.0310 | 15580.16 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 34129.658 | 34129.658 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.376906 | 1.65723772 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 | Sensible | 34129.66 | 34129.66 | 1.0000 | 1.65723772 | 1.376906 | 19.51 | 14.74 | 0.00850386 | 41175.7 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 34129.66 | 12.70 | 0.00915345 | 12.70 | 0.20573941 | 14.9421 | 20.70 | 0.00838974 | 21.11 | 0.00838974 | 53.8110 | 5032.75 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 39705.600 | 28208.844 | 1.647020 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.0990 | 1004.8586 | 1.2036 | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.647024 | 1.98235030 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | Sensible | 19852.80 | 17038.04 | 1.0000 | 1.32156334 | 1.098013 | 27.06 | 17.21 | 0.00820841 | 48132.1 | 12.80 | 10.55 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 19852.80 | 42.31 | 0.01078097 | 23.73 | 0.20573941 | 18.7374 | 23.89 | 0.00784118 | 23.89 | 0.00784118 | 42.5266 | 18640.43 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 40268.020 | 40268.020 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.647024 | 1.98235030 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 | Sensible | 40268.02 | 40268.02 | 1.0000 | 1.98235030 | 1.647024 | 19.78 | 14.86 | 0.00851349 | 41485.6 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 40268.02 | 12.70 | 0.00915345 | 12.70 | 0.20573941 | 12.4916 | 20.80 | 0.00842214 | 21.11 | 0.00842214 | 54.0153 | 5994.70 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:02
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
LGSTORE1 | 5206.83 | 835.50 | 740.00 |
SMSTORE1 | 4981.00 | 628.50 | 556.17 |
SMSTORE2 | 3959.67 | 747.33 | 692.50 |
SMSTORE3 | 3950.17 | 740.67 | 681.50 |
SMSTORE4 | 3909.33 | 772.33 | 702.50 |
LGSTORE2 | 3494.17 | 755.33 | 701.83 |
SMSTORE5 | 3383.33 | 766.00 | 703.83 |
SMSTORE6 | 3367.17 | 776.67 | 709.50 |
SMSTORE7 | 3364.33 | 772.67 | 694.17 |
SMSTORE8 | 3508.33 | 632.33 | 540.83 |
Facility | 5354.67 | 1258.33 | 1088.33 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
LGSTORE1 | 0.00 | 5.67 | 0.00 | 4.67 |
SMSTORE1 | 0.00 | 0.17 | 0.00 | 0.17 |
SMSTORE2 | 0.00 | 11.33 | 0.00 | 0.00 |
SMSTORE3 | 0.00 | 12.50 | 0.00 | 0.00 |
SMSTORE4 | 0.00 | 11.67 | 0.00 | 0.00 |
LGSTORE2 | 0.00 | 9.67 | 0.00 | 0.00 |
SMSTORE5 | 0.00 | 7.83 | 0.00 | 0.00 |
SMSTORE6 | 0.00 | 7.83 | 0.00 | 0.00 |
SMSTORE7 | 0.00 | 8.50 | 0.00 | 0.00 |
SMSTORE8 | 0.00 | 14.00 | 0.00 | 0.00 |
Facility | 0.00 | 26.83 | 0.00 | 4.67 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:02
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
LGSTORE1 | 16.92 | 56.25 | 1805.20 | 0.848 | 0.341 | 0.000 | 0.000 |
SMSTORE1 | 8.46 | 28.12 | 902.60 | 0.687 | 0.378 | 0.000 | 0.000 |
SMSTORE2 | 7.10 | 28.12 | 902.60 | 0.849 | 0.497 | 0.000 | 0.000 |
SMSTORE3 | 7.10 | 28.12 | 902.60 | 0.849 | 0.497 | 0.000 | 0.000 |
SMSTORE4 | 7.10 | 28.12 | 902.60 | 0.849 | 0.497 | 0.000 | 0.000 |
LGSTORE2 | 24.82 | 56.25 | 1805.20 | 0.849 | 0.465 | 0.000 | 0.000 |
SMSTORE5 | 12.41 | 28.12 | 902.60 | 0.849 | 0.530 | 0.000 | 0.000 |
SMSTORE6 | 12.41 | 28.12 | 902.60 | 0.849 | 0.530 | 0.000 | 0.000 |
SMSTORE7 | 12.41 | 28.12 | 902.60 | 0.849 | 0.530 | 0.000 | 0.000 |
SMSTORE8 | 12.41 | 28.12 | 902.60 | 0.848 | 0.549 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
LGSTORE1 | 16.92 | 56.25 | 1805.20 | 0.825 | 0.000 | 0.000 | 0.000 |
SMSTORE1 | 8.46 | 28.12 | 902.60 | 0.038 | 0.000 | 0.000 | 0.000 |
SMSTORE2 | 7.10 | 28.12 | 902.60 | 0.825 | 0.000 | 0.000 | 0.000 |
SMSTORE3 | 7.10 | 28.12 | 902.60 | 0.824 | 0.000 | 0.000 | 0.000 |
SMSTORE4 | 7.10 | 28.12 | 902.60 | 0.824 | 0.000 | 0.000 | 0.000 |
LGSTORE2 | 24.82 | 56.25 | 1805.20 | 0.828 | 0.000 | 0.000 | 0.000 |
SMSTORE5 | 12.41 | 28.12 | 902.60 | 0.828 | 0.000 | 0.000 | 0.000 |
SMSTORE6 | 12.41 | 28.12 | 902.60 | 0.828 | 0.000 | 0.000 | 0.000 |
SMSTORE7 | 12.41 | 28.12 | 902.60 | 0.828 | 0.000 | 0.000 | 0.000 |
SMSTORE8 | 12.41 | 28.12 | 902.60 | 0.827 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:37:02
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
LGSTORE1 | PSZ-AC_1:1 | 16.92 | 56.25 | 1805.20 | 348.39 | 0.4115 | 0.411 |
SMSTORE1 | PSZ-AC_2:2 | 8.46 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE2 | PSZ-AC_3:3 | 7.10 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE3 | PSZ-AC_4:4 | 7.10 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE4 | PSZ-AC_5:5 | 7.10 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
LGSTORE2 | PSZ-AC_6:6 | 24.82 | 56.25 | 1805.20 | 348.39 | 0.4115 | 0.411 |
SMSTORE5 | PSZ-AC_7:7 | 12.41 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE6 | PSZ-AC_8:8 | 12.41 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE7 | PSZ-AC_9:9 | 12.41 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE8 | PSZ-AC_10:10 | 12.41 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
Total Facility | 121.13 | 337.50 | 10831.20 | 2090.32 | 2.4689 | 2.469 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
LGSTORE1 | 8803569.00 | 0.00 | 8803569.00 | 3720417.12 | 12523986.12 | 12976396.34 | 2817.00 | 5943.00 | 0.00 | 103.00 |
SMSTORE1 | 3583437.70 | 0.00 | 3583437.70 | 2005460.50 | 5588898.20 | 6488198.17 | 4303.00 | 4457.00 | 0.00 | 103.00 |
SMSTORE2 | 3525578.09 | 0.00 | 3525578.09 | 2030324.42 | 5555902.51 | 6488198.17 | 4000.00 | 4760.00 | 0.00 | 365.00 |
SMSTORE3 | 3525577.67 | 0.00 | 3525577.67 | 2030324.42 | 5555902.10 | 6488198.17 | 4000.00 | 4760.00 | 0.00 | 365.00 |
SMSTORE4 | 3525578.51 | 0.00 | 3525578.51 | 2030324.42 | 5555902.94 | 6488198.17 | 4000.00 | 4760.00 | 0.00 | 365.00 |
LGSTORE2 | 6510488.67 | 0.00 | 6510488.67 | 3601646.44 | 10112135.11 | 12976396.34 | 4365.00 | 4395.00 | 0.00 | 365.00 |
SMSTORE5 | 3255238.18 | 0.00 | 3255238.18 | 2036872.93 | 5292111.10 | 6488198.17 | 4365.00 | 4395.00 | 0.00 | 365.00 |
SMSTORE6 | 3255237.95 | 0.00 | 3255237.95 | 2036872.93 | 5292110.88 | 6488198.17 | 4365.00 | 4395.00 | 0.00 | 365.00 |
SMSTORE7 | 3255237.02 | 0.00 | 3255237.02 | 2036872.93 | 5292109.94 | 6488198.17 | 4365.00 | 4395.00 | 0.00 | 365.00 |
SMSTORE8 | 3255304.22 | 0.00 | 3255304.22 | 2265587.09 | 5520891.30 | 6488198.17 | 4365.00 | 4395.00 | 0.00 | 366.19 |
Total Facility | 42495247.01 | 0.00 | 42495247.01 | 23794703.20 | 66289950.21 | 77858378.04 | 4365.00 | 6246.00 | 0.00 | 731.19 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
LGSTORE1 | 0.4115 | 0.0000 | 0.4115 | 0.1654 | 0.5768 | 0.4115 | 0.00 | 5840.00 | 0.00 |
SMSTORE1 | 0.1668 | 0.0000 | 0.1668 | 0.0918 | 0.2586 | 0.2057 | 1486.00 | 4354.00 | 0.00 |
SMSTORE2 | 0.2057 | 0.0000 | 0.2057 | 0.1205 | 0.3262 | 0.2057 | 0.00 | 4395.00 | 0.00 |
SMSTORE3 | 0.2057 | 0.0000 | 0.2057 | 0.1205 | 0.3262 | 0.2057 | 0.00 | 4395.00 | 0.00 |
SMSTORE4 | 0.2057 | 0.0000 | 0.2057 | 0.1205 | 0.3262 | 0.2057 | 0.00 | 4395.00 | 0.00 |
LGSTORE2 | 0.4115 | 0.0000 | 0.4115 | 0.2254 | 0.6369 | 0.4115 | 0.00 | 4030.00 | 0.00 |
SMSTORE5 | 0.2057 | 0.0000 | 0.2057 | 0.1284 | 0.3342 | 0.2057 | 0.00 | 4030.00 | 0.00 |
SMSTORE6 | 0.2057 | 0.0000 | 0.2057 | 0.1284 | 0.3342 | 0.2057 | 0.00 | 4030.00 | 0.00 |
SMSTORE7 | 0.2057 | 0.0000 | 0.2057 | 0.1284 | 0.3342 | 0.2057 | 0.00 | 4030.00 | 0.00 |
SMSTORE8 | 0.2057 | 0.0000 | 0.2057 | 0.1330 | 0.3388 | 0.2057 | 0.00 | 4030.00 | 0.00 |
Total Facility | 2.4300 | 0.0000 | 2.4300 | 1.3622 | 3.7922 | 2.4689 | 1486.00 | 5943.00 | 0.00 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-AC_1:1 | 12753120.48 | 0.00 | 12753120.48 | 12976396.34 | 2817.00 | 0.00 | 5943.00 | 103.00 |
PSZ-AC_2:2 | 5191076.36 | 0.00 | 5191076.36 | 6488198.17 | 4302.75 | 0.08 | 4457.17 | 103.00 |
PSZ-AC_3:3 | 5107256.73 | 0.00 | 5107256.73 | 6488198.17 | 4000.00 | 0.00 | 4760.00 | 365.00 |
PSZ-AC_4:4 | 5107256.73 | 0.00 | 5107256.73 | 6488198.17 | 4000.00 | 0.00 | 4760.00 | 365.00 |
PSZ-AC_5:5 | 5107256.73 | 0.00 | 5107256.73 | 6488198.17 | 4000.00 | 0.00 | 4760.00 | 365.00 |
PSZ-AC_6:6 | 9431257.70 | 0.00 | 9431257.70 | 12976396.34 | 4365.00 | 0.00 | 4395.00 | 365.00 |
PSZ-AC_7:7 | 4715628.85 | 0.00 | 4715628.85 | 6488198.17 | 4365.00 | 0.00 | 4395.00 | 365.00 |
PSZ-AC_8:8 | 4715628.85 | 0.00 | 4715628.85 | 6488198.17 | 4365.00 | 0.00 | 4395.00 | 365.00 |
PSZ-AC_9:9 | 4715628.85 | 0.00 | 4715628.85 | 6488198.17 | 4365.00 | 0.00 | 4395.00 | 365.00 |
PSZ-AC_10:10 | 4715744.39 | 0.00 | 4715744.39 | 6488198.17 | 4365.00 | 0.00 | 4395.00 | 366.19 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-AC_1:1 | 0.5961 | 0.0000 | 0.5961 | 0.4115 | 0.00 | 0.00 | 5840.00 |
PSZ-AC_2:2 | 0.2417 | 0.0000 | 0.2417 | 0.2057 | 1485.75 | 0.08 | 4354.17 |
PSZ-AC_3:3 | 0.2980 | 0.0000 | 0.2980 | 0.2057 | 0.00 | 0.00 | 4395.00 |
PSZ-AC_4:4 | 0.2980 | 0.0000 | 0.2980 | 0.2057 | 0.00 | 0.00 | 4395.00 |
PSZ-AC_5:5 | 0.2980 | 0.0000 | 0.2980 | 0.2057 | 0.00 | 0.00 | 4395.00 |
PSZ-AC_6:6 | 0.5961 | 0.0000 | 0.5961 | 0.4115 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_7:7 | 0.2980 | 0.0000 | 0.2980 | 0.2057 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_8:8 | 0.2980 | 0.0000 | 0.2980 | 0.2057 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_9:9 | 0.2980 | 0.0000 | 0.2980 | 0.2057 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_10:10 | 0.2980 | 0.0000 | 0.2980 | 0.2057 | 0.00 | 0.00 | 4030.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-AC_1:1 | 0.00 | 5943.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_2:2 | 0.00 | 5943.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_3:3 | 0.00 | 4760.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_4:4 | 0.00 | 4760.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_5:5 | 0.00 | 4760.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_6:6 | 0.00 | 4395.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_7:7 | 0.00 | 4395.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_8:8 | 0.00 | 4395.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_9:9 | 0.00 | 4395.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_10:10 | 0.00 | 4396.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-AC_1:1 | 0.0000 | 0.5961 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_2:2 | 0.0000 | 0.2417 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_3:3 | 0.0000 | 0.2981 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_4:4 | 0.0000 | 0.2981 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_5:5 | 0.0000 | 0.2981 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_6:6 | 0.0000 | 0.5962 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_7:7 | 0.0000 | 0.2981 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_8:8 | 0.0000 | 0.2981 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_9:9 | 0.0000 | 0.2981 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_10:10 | 0.0000 | 0.2981 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:02
Surfaces by ClassTotal | Outdoors | |
Wall | 40 | 22 |
Floor | 10 | 10 |
Roof | 10 | 10 |
Internal Mass | 10 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 36 | 36 |
Door | 12 | 12 |
Glass Door | 12 | 12 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 10 |
Conditioned Zones | 10 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 830 |
Defaulted Fields | 823 |
Fields with Defaults | 2682 |
Autosized Fields | 184 |
Autosizable Fields | 458 |
Autocalculated Fields | 128 |
Autocalculatable Fields | 256 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:37:02
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1391.36 | 2102.83 | 01-JAN-07:10 | 154921.40 | 10-AUG-16:10 |
Electricity:Building | 494.83 | 891.83 | 01-JAN-00:20 | 31518.67 | 01-JAN-11:10 |
Electricity:Zone:LGSTORE1 | 113.36 | 148.64 | 01-JAN-00:20 | 5964.88 | 01-JAN-10:10 |
Electricity:SpaceType:GENERAL | 494.83 | 891.83 | 01-JAN-00:20 | 31518.67 | 01-JAN-11:10 |
InteriorLights:Electricity | 366.68 | 450.00 | 01-JAN-00:20 | 23459.17 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:LGSTORE1 | 87.12 | 75.00 | 01-JAN-00:20 | 4621.63 | 01-JAN-10:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 366.68 | 450.00 | 01-JAN-00:20 | 23459.17 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity | 366.68 | 450.00 | 01-JAN-00:20 | 23459.17 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:LGSTORE1 | 87.12 | 75.00 | 01-JAN-00:20 | 4621.63 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 366.68 | 450.00 | 01-JAN-00:20 | 23459.17 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE1 | 66.33 | 74.32 | 01-JAN-00:20 | 3498.69 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE1 | 53.20 | 37.50 | 01-JAN-00:20 | 2827.07 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE1 | 53.20 | 37.50 | 01-JAN-00:20 | 2827.07 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE2 | 47.99 | 74.32 | 01-JAN-00:10 | 3226.84 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE2 | 37.57 | 37.50 | 01-JAN-00:10 | 2555.22 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE2 | 37.57 | 37.50 | 01-JAN-00:10 | 2555.22 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE3 | 47.99 | 74.32 | 01-JAN-00:10 | 3226.84 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE3 | 37.57 | 37.50 | 01-JAN-00:10 | 2555.22 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE3 | 37.57 | 37.50 | 01-JAN-00:10 | 2555.22 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE4 | 47.99 | 74.32 | 01-JAN-00:10 | 3226.84 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE4 | 37.57 | 37.50 | 01-JAN-00:10 | 2555.22 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE4 | 37.57 | 37.50 | 01-JAN-00:10 | 2555.22 | 01-JAN-10:10 |
Electricity:Zone:LGSTORE2 | 56.34 | 148.64 | 01-JAN-00:10 | 4070.21 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:LGSTORE2 | 37.16 | 75.00 | 01-JAN-00:10 | 2726.96 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:LGSTORE2 | 37.16 | 75.00 | 01-JAN-00:10 | 2726.96 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE5 | 28.71 | 74.32 | 01-JAN-00:10 | 2076.09 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE5 | 19.12 | 37.50 | 01-JAN-00:10 | 1404.46 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE5 | 19.12 | 37.50 | 01-JAN-00:10 | 1404.46 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE6 | 28.71 | 74.32 | 01-JAN-00:10 | 2076.09 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE6 | 19.12 | 37.50 | 01-JAN-00:10 | 1404.46 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE6 | 19.12 | 37.50 | 01-JAN-00:10 | 1404.46 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE7 | 28.71 | 74.32 | 01-JAN-00:10 | 2076.09 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE7 | 19.12 | 37.50 | 01-JAN-00:10 | 1404.46 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE7 | 19.12 | 37.50 | 01-JAN-00:10 | 1404.46 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE8 | 28.71 | 74.32 | 01-JAN-00:10 | 2076.09 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE8 | 19.12 | 37.50 | 01-JAN-00:10 | 1404.46 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE8 | 19.12 | 37.50 | 01-JAN-00:10 | 1404.46 | 01-JAN-11:10 |
InteriorEquipment:Electricity | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:LGSTORE1 | 26.25 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-10:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LGSTORE1 | 26.25 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE1 | 13.12 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE1 | 13.12 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE2 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE2 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE3 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE3 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE4 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE4 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:LGSTORE2 | 19.17 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LGSTORE2 | 19.17 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE5 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE5 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE6 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE6 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE7 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE7 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE8 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE8 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
ElectricityPurchased:Facility | 1391.36 | 2102.83 | 01-JAN-07:10 | 154921.40 | 10-AUG-16:10 |
ElectricityPurchased:Plant | 1391.36 | 2102.83 | 01-JAN-07:10 | 154921.40 | 10-AUG-16:10 |
Cogeneration:ElectricityPurchased | 1391.36 | 2102.83 | 01-JAN-07:10 | 154921.40 | 10-AUG-16:10 |
General:Cogeneration:ElectricityPurchased | 1391.36 | 2102.83 | 01-JAN-07:10 | 154921.40 | 10-AUG-16:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1391.36 | 2102.83 | 01-JAN-07:10 | 154921.40 | 10-AUG-16:10 |
ElectricityNet:Plant | 1391.36 | 2102.83 | 01-JAN-07:10 | 154921.40 | 10-AUG-16:10 |
Cogeneration:ElectricityNet | 1391.36 | 2102.83 | 01-JAN-07:10 | 154921.40 | 10-AUG-16:10 |
General:Cogeneration:ElectricityNet | 1391.36 | 2102.83 | 01-JAN-07:10 | 154921.40 | 10-AUG-16:10 |
Electricity:HVAC | 778.90 | 0.00 | 01-JAN-00:10 | 120535.22 | 10-AUG-16:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 642.23 | 0.00 | 01-JAN-00:10 | 105570.71 | 10-AUG-16:10 |
General:Cooling:Electricity | 642.23 | 0.00 | 01-JAN-00:10 | 105570.71 | 10-AUG-16:10 |
Fans:Electricity | 136.66 | 0.00 | 01-JAN-00:10 | 14964.51 | 10-AUG-16:10 |
General:Fans:Electricity | 136.66 | 0.00 | 01-JAN-00:10 | 14964.51 | 10-AUG-16:10 |
ExteriorLights:Electricity | 60.14 | 0.00 | 01-JAN-07:10 | 5507.06 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 60.14 | 0.00 | 01-JAN-07:10 | 5507.06 | 01-JAN-06:10 |
Electricity:Plant | 57.49 | 1211.00 | 08-MAY-06:10 | 11787.90 | 06-JAN-14:10 |
WaterSystems:Electricity | 57.49 | 1211.00 | 08-MAY-06:10 | 11787.90 | 06-JAN-14:10 |
Water Heater:WaterSystems:Electricity | 57.49 | 1211.00 | 08-MAY-06:10 | 11787.90 | 06-JAN-14:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 84.49 | 02-JAN-08:30 |
NaturalGas:HVAC | 0.00 | 0.00 | 01-JAN-00:10 | 84.49 | 02-JAN-08:30 |
Heating:NaturalGas | 0.00 | 0.00 | 01-JAN-00:10 | 84.49 | 02-JAN-08:30 |
General:Heating:NaturalGas | 0.00 | 0.00 | 01-JAN-00:10 | 84.49 | 02-JAN-08:30 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water:Plant | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
WaterSystems:Water | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water Heater:WaterSystems:Water | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
MainsWater:Facility | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
MainsWater:Plant | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
WaterSystems:MainsWater | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water Heater:WaterSystems:MainsWater | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 3479.07 | 0.00 | 01-JAN-00:10 | 506423.56 | 10-AUG-16:10 |
EnergyTransfer:Building | 1163.32 | 0.00 | 01-JAN-00:10 | 156595.64 | 16-AUG-12:10 |
EnergyTransfer:Zone:LGSTORE1 | 236.08 | 0.00 | 01-JAN-00:10 | 25882.47 | 04-AUG-13:00 |
Heating:EnergyTransfer | 8.78 | 0.00 | 01-JAN-00:10 | 35315.33 | 05-AUG-17:10 |
Heating:EnergyTransfer:Zone:LGSTORE1 | 0.29 | 0.00 | 01-JAN-00:10 | 3724.27 | 29-APR-07:20 |
General:Heating:EnergyTransfer | 8.78 | 0.00 | 01-JAN-00:10 | 35315.33 | 05-AUG-17:10 |
General:Heating:EnergyTransfer:Zone:LGSTORE1 | 0.29 | 0.00 | 01-JAN-00:10 | 3724.27 | 29-APR-07:20 |
Cooling:EnergyTransfer | 1154.54 | 0.00 | 01-JAN-00:10 | 156595.64 | 16-AUG-12:10 |
Cooling:EnergyTransfer:Zone:LGSTORE1 | 235.79 | 0.00 | 01-JAN-00:10 | 25882.47 | 04-AUG-13:00 |
General:Cooling:EnergyTransfer | 1154.54 | 0.00 | 01-JAN-00:10 | 156595.64 | 16-AUG-12:10 |
General:Cooling:EnergyTransfer:Zone:LGSTORE1 | 235.79 | 0.00 | 01-JAN-00:10 | 25882.47 | 04-AUG-13:00 |
EnergyTransfer:Zone:SMSTORE1 | 121.72 | 0.00 | 01-JAN-00:10 | 13109.43 | 04-AUG-13:00 |
Heating:EnergyTransfer:Zone:SMSTORE1 | 0.13 | 0.00 | 01-JAN-00:10 | 1875.86 | 04-MAY-07:20 |
General:Heating:EnergyTransfer:Zone:SMSTORE1 | 0.13 | 0.00 | 01-JAN-00:10 | 1875.86 | 04-MAY-07:20 |
Cooling:EnergyTransfer:Zone:SMSTORE1 | 121.58 | 0.00 | 01-JAN-00:10 | 13109.43 | 04-AUG-13:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE1 | 121.58 | 0.00 | 01-JAN-00:10 | 13109.43 | 04-AUG-13:00 |
EnergyTransfer:Zone:SMSTORE2 | 96.43 | 0.00 | 01-JAN-00:10 | 13192.56 | 16-AUG-12:10 |
Heating:EnergyTransfer:Zone:SMSTORE2 | 1.61 | 0.00 | 01-JAN-00:10 | 4162.90 | 31-MAY-19:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE2 | 1.61 | 0.00 | 01-JAN-00:10 | 4162.90 | 31-MAY-19:10 |
Cooling:EnergyTransfer:Zone:SMSTORE2 | 94.83 | 0.00 | 01-JAN-00:10 | 13192.56 | 16-AUG-12:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE2 | 94.83 | 0.00 | 01-JAN-00:10 | 13192.56 | 16-AUG-12:10 |
EnergyTransfer:Zone:SMSTORE3 | 96.92 | 0.00 | 01-JAN-00:10 | 13261.33 | 16-AUG-12:10 |
Heating:EnergyTransfer:Zone:SMSTORE3 | 1.60 | 0.00 | 01-JAN-00:10 | 4160.79 | 31-MAY-19:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE3 | 1.60 | 0.00 | 01-JAN-00:10 | 4160.79 | 31-MAY-19:10 |
Cooling:EnergyTransfer:Zone:SMSTORE3 | 95.32 | 0.00 | 01-JAN-00:10 | 13261.33 | 16-AUG-12:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE3 | 95.32 | 0.00 | 01-JAN-00:10 | 13261.33 | 16-AUG-12:10 |
EnergyTransfer:Zone:SMSTORE4 | 94.91 | 0.00 | 01-JAN-00:10 | 13145.08 | 16-AUG-12:10 |
Heating:EnergyTransfer:Zone:SMSTORE4 | 1.62 | 0.00 | 01-JAN-00:10 | 4169.67 | 31-MAY-19:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE4 | 1.62 | 0.00 | 01-JAN-00:10 | 4169.67 | 31-MAY-19:10 |
Cooling:EnergyTransfer:Zone:SMSTORE4 | 93.30 | 0.00 | 01-JAN-00:10 | 13145.08 | 16-AUG-12:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE4 | 93.30 | 0.00 | 01-JAN-00:10 | 13145.08 | 16-AUG-12:10 |
EnergyTransfer:Zone:LGSTORE2 | 161.53 | 0.00 | 01-JAN-00:10 | 23807.36 | 16-AUG-12:10 |
Heating:EnergyTransfer:Zone:LGSTORE2 | 1.20 | 0.00 | 01-JAN-00:10 | 7889.56 | 05-AUG-17:10 |
General:Heating:EnergyTransfer:Zone:LGSTORE2 | 1.20 | 0.00 | 01-JAN-00:10 | 7889.56 | 05-AUG-17:10 |
Cooling:EnergyTransfer:Zone:LGSTORE2 | 160.33 | 0.00 | 01-JAN-00:10 | 23807.36 | 16-AUG-12:10 |
General:Cooling:EnergyTransfer:Zone:LGSTORE2 | 160.33 | 0.00 | 01-JAN-00:10 | 23807.36 | 16-AUG-12:10 |
EnergyTransfer:Zone:SMSTORE5 | 84.55 | 0.00 | 01-JAN-00:10 | 12728.77 | 16-AUG-12:10 |
Heating:EnergyTransfer:Zone:SMSTORE5 | 0.61 | 0.00 | 01-JAN-00:10 | 3976.50 | 05-AUG-17:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE5 | 0.61 | 0.00 | 01-JAN-00:10 | 3976.50 | 05-AUG-17:10 |
Cooling:EnergyTransfer:Zone:SMSTORE5 | 83.94 | 0.00 | 01-JAN-00:10 | 12728.77 | 16-AUG-12:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE5 | 83.94 | 0.00 | 01-JAN-00:10 | 12728.77 | 16-AUG-12:10 |
EnergyTransfer:Zone:SMSTORE6 | 84.10 | 0.00 | 01-JAN-00:10 | 12705.22 | 16-AUG-12:10 |
Heating:EnergyTransfer:Zone:SMSTORE6 | 0.61 | 0.00 | 01-JAN-00:10 | 3978.13 | 05-AUG-17:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE6 | 0.61 | 0.00 | 01-JAN-00:10 | 3978.13 | 05-AUG-17:10 |
Cooling:EnergyTransfer:Zone:SMSTORE6 | 83.49 | 0.00 | 01-JAN-00:10 | 12705.22 | 16-AUG-12:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE6 | 83.49 | 0.00 | 01-JAN-00:10 | 12705.22 | 16-AUG-12:10 |
EnergyTransfer:Zone:SMSTORE7 | 84.54 | 0.00 | 01-JAN-00:10 | 12883.46 | 16-AUG-12:10 |
Heating:EnergyTransfer:Zone:SMSTORE7 | 0.60 | 0.00 | 01-JAN-00:10 | 3968.97 | 05-AUG-17:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE7 | 0.60 | 0.00 | 01-JAN-00:10 | 3968.97 | 05-AUG-17:10 |
Cooling:EnergyTransfer:Zone:SMSTORE7 | 83.94 | 0.00 | 01-JAN-00:10 | 12883.46 | 16-AUG-12:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE7 | 83.94 | 0.00 | 01-JAN-00:10 | 12883.46 | 16-AUG-12:10 |
EnergyTransfer:Zone:SMSTORE8 | 102.55 | 0.00 | 01-JAN-00:10 | 16047.43 | 16-AUG-12:10 |
Heating:EnergyTransfer:Zone:SMSTORE8 | 0.52 | 0.00 | 01-JAN-00:10 | 3775.71 | 05-AUG-17:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE8 | 0.52 | 0.00 | 01-JAN-00:10 | 3775.71 | 05-AUG-17:10 |
Cooling:EnergyTransfer:Zone:SMSTORE8 | 102.03 | 0.00 | 01-JAN-00:10 | 16047.43 | 16-AUG-12:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE8 | 102.03 | 0.00 | 01-JAN-00:10 | 16047.43 | 16-AUG-12:10 |
EnergyTransfer:HVAC | 2315.75 | 0.00 | 01-JAN-00:10 | 370050.38 | 20-JUL-13:00 |
HeatingCoils:EnergyTransfer | 0.00 | 0.00 | 01-JAN-00:10 | 67.59 | 02-JAN-08:30 |
CoolingCoils:EnergyTransfer | 2315.75 | 0.00 | 01-JAN-00:10 | 370050.38 | 20-JUL-13:00 |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:02
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
LGSTORE1 | 0.000 | 0.000 | 0.286 | -235.794 | 0.000 | 0.000 | 23.220 | 87.116 | 26.249 | 18.781 | 0.000 | 32.851 | 52.229 | 0.000 | -2.645 | 0.000 | -2.292 | -0.000 |
SMSTORE1 | 0.000 | 0.000 | 0.132 | -121.582 | 0.000 | 0.000 | 11.609 | 53.201 | 13.125 | 9.473 | 0.000 | 18.154 | 18.318 | 0.000 | -1.336 | 0.000 | -1.094 | -0.000 |
SMSTORE2 | 0.000 | 0.000 | 1.607 | -94.826 | 0.000 | 0.000 | 6.968 | 37.572 | 10.421 | 9.254 | 0.000 | 17.954 | 13.656 | 0.000 | -1.426 | 0.000 | -1.179 | -0.000 |
SMSTORE3 | 0.000 | 0.000 | 1.598 | -95.317 | 0.000 | 0.000 | 6.968 | 37.572 | 10.421 | 9.236 | 0.000 | 17.944 | 14.187 | 0.000 | -1.430 | 0.000 | -1.178 | -0.001 |
SMSTORE4 | 0.000 | 0.000 | 1.616 | -93.296 | 0.000 | 0.000 | 6.968 | 37.572 | 10.421 | 9.255 | 0.000 | 17.952 | 12.083 | 0.000 | -1.406 | 0.000 | -1.166 | -0.001 |
LGSTORE2 | 0.000 | 0.000 | 1.200 | -160.325 | 0.000 | 0.000 | 23.926 | 37.162 | 19.173 | 18.555 | 0.000 | 31.636 | 33.462 | 0.000 | -2.685 | 0.000 | -2.103 | -0.001 |
SMSTORE5 | 0.000 | 0.000 | 0.610 | -83.939 | 0.000 | 0.000 | 11.963 | 19.120 | 9.586 | 9.322 | 0.000 | 17.992 | 17.826 | 0.000 | -1.322 | 0.000 | -1.158 | -0.000 |
SMSTORE6 | 0.000 | 0.000 | 0.610 | -83.486 | 0.000 | 0.000 | 11.963 | 19.120 | 9.586 | 9.328 | 0.000 | 17.993 | 17.356 | 0.000 | -1.317 | 0.000 | -1.155 | -0.000 |
SMSTORE7 | 0.000 | 0.000 | 0.604 | -83.941 | 0.000 | 0.000 | 11.964 | 19.120 | 9.586 | 9.309 | 0.000 | 17.988 | 17.827 | 0.000 | -1.311 | 0.000 | -1.146 | -0.000 |
SMSTORE8 | 0.000 | 0.000 | 0.521 | -102.026 | 0.000 | 0.000 | 11.963 | 19.120 | 9.586 | 9.121 | 0.000 | 18.935 | 35.627 | 0.000 | -1.312 | 0.000 | -1.536 | -0.001 |
Total Facility | 0.000 | 0.000 | 8.785 | -1154.531 | 0.000 | 0.000 | 127.510 | 366.677 | 128.154 | 111.635 | 0.000 | 209.398 | 232.570 | 0.000 | -16.190 | 0.000 | -14.007 | -0.004 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
LGSTORE1 | 11-MAY-07:01 | 0.00 | 0.00 | 0.00 | -57688.73 | 0.00 | 0.00 | 162.77 | 75.00 | 74.62 | 379.27 | 0.00 | 345.20 | 56651.86 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 11-MAY-07:01 | 0.00 | 0.00 | 0.00 | -29696.84 | 0.00 | 0.00 | 81.78 | 37.50 | 37.31 | 192.03 | 0.00 | 198.53 | 29149.68 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 05-MAY-06:02 | 0.00 | 0.00 | 0.00 | -29057.02 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 0.00 | 0.00 | 1.58 | 29002.79 | 0.00 | -21.68 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 05-MAY-06:02 | 0.00 | 0.00 | 0.00 | -29181.14 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 0.00 | 0.00 | 1.52 | 29128.36 | 0.00 | -23.06 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 05-MAY-06:02 | 0.00 | 0.00 | 0.00 | -28869.40 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 0.00 | 0.00 | 1.67 | 28813.84 | 0.00 | -20.42 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 04-JUL-08:61 | 0.00 | 0.00 | 0.00 | -51377.24 | 0.00 | 0.00 | 0.00 | 75.00 | 73.64 | 672.76 | 0.00 | 419.97 | 50135.87 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 04-JUL-08:61 | 0.00 | 0.00 | 0.00 | -27086.52 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 339.21 | 0.00 | 242.98 | 26430.00 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 04-JUL-08:61 | 0.00 | 0.00 | 0.00 | -26996.10 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 339.33 | 0.00 | 243.08 | 26339.37 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 04-JUL-08:61 | 0.00 | 0.00 | 0.00 | -27255.07 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 336.94 | 0.00 | 240.90 | 26602.91 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 04-JUL-08:61 | 0.00 | 0.00 | 0.00 | -32468.37 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 322.60 | 0.00 | 238.68 | 31832.77 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 11-MAY-07:01 | 0.00 | 0.00 | 0.00 | -261664.86 | 0.00 | 0.00 | 540.06 | 450.00 | 1452.23 | 2374.83 | 0.00 | 2419.24 | 254428.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
LGSTORE1 | 05-AUG-07:05 | 0.00 | 0.00 | 7487.60 | 0.00 | 0.00 | 0.00 | 0.00 | 75.00 | 73.64 | 564.56 | 0.00 | 841.42 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -9042.23 |
SMSTORE1 | 05-AUG-07:04 | 0.00 | 0.00 | 3974.96 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 292.89 | 0.00 | 457.36 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -4799.53 |
SMSTORE2 | 31-MAY-19:02 | 0.00 | 0.00 | 4607.08 | 0.00 | 0.00 | 0.00 | 98.50 | 1344.85 | 373.13 | 348.66 | 0.00 | 63.49 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -6835.71 |
SMSTORE3 | 31-MAY-19:02 | 0.00 | 0.00 | 4605.87 | 0.00 | 0.00 | 0.00 | 98.50 | 1344.85 | 373.13 | 348.45 | 0.00 | 63.49 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -6834.29 |
SMSTORE4 | 31-MAY-19:02 | 0.00 | 0.00 | 4610.82 | 0.00 | 0.00 | 0.00 | 98.50 | 1344.85 | 373.13 | 348.88 | 0.00 | 63.50 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -6839.68 |
LGSTORE2 | 05-AUG-17:01 | 0.00 | 0.00 | 8871.07 | 0.00 | 0.00 | 0.00 | 433.43 | 1435.23 | 746.25 | 1003.29 | 0.00 | 1167.58 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -13656.86 |
SMSTORE5 | 05-AUG-17:01 | 0.00 | 0.00 | 4455.01 | 0.00 | 0.00 | 0.00 | 216.71 | 739.19 | 373.13 | 506.22 | 0.00 | 657.41 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -6947.67 |
SMSTORE6 | 05-AUG-17:01 | 0.00 | 0.00 | 4455.71 | 0.00 | 0.00 | 0.00 | 216.71 | 739.19 | 373.13 | 506.41 | 0.00 | 657.44 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -6948.60 |
SMSTORE7 | 05-AUG-17:01 | 0.00 | 0.00 | 4450.65 | 0.00 | 0.00 | 0.00 | 216.71 | 739.19 | 373.13 | 505.16 | 0.00 | 657.23 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -6942.07 |
SMSTORE8 | 05-AUG-17:01 | 0.00 | 0.00 | 4336.14 | 0.00 | 0.00 | 0.00 | 216.71 | 739.19 | 373.13 | 491.40 | 0.00 | 755.14 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -6911.70 |
Total Facility | 05-AUG-17:01 | -25700.27 | 25700.27 | 39800.62 | -25700.27 | 0.00 | 0.00 | 4550.99 | 15875.25 | 5373.00 | 6038.97 | 0.00 | 7840.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -53779.45 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:02
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 2.9110 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 2.9110 | 0.1414 | 1.0000 | Not calculated | 0.4115 | 0.1414 | ||
PSZ-AC_2:2 | 1.4654 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.4654 | 0.1404 | 1.0000 | Not calculated | 0.2057 | 0.1404 | ||
PSZ-AC_3:3 | 1.4649 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.4649 | 0.1404 | 1.0000 | Not calculated | 0.2057 | 0.1404 | ||
PSZ-AC_4:4 | 1.4680 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.4680 | 0.1401 | 1.0000 | Not calculated | 0.2057 | 0.1401 | ||
PSZ-AC_5:5 | 1.4597 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.4597 | 0.1409 | 1.0000 | Not calculated | 0.2057 | 0.1409 | ||
PSZ-AC_6:6 | 2.5936 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 2.5936 | 0.1587 | 1.0000 | Not calculated | 0.4115 | 0.1587 | ||
PSZ-AC_7:7 | 1.3719 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.3719 | 0.1500 | 1.0000 | Not calculated | 0.2057 | 0.1500 | ||
PSZ-AC_8:8 | 1.3676 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.3676 | 0.1504 | 1.0000 | Not calculated | 0.2057 | 0.1504 | ||
PSZ-AC_9:9 | 1.3769 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.3769 | 0.1494 | 1.0000 | Not calculated | 0.2057 | 0.1494 | ||
PSZ-AC_10:10 | 1.6470 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.6470 | 0.1249 | 1.0000 | Not calculated | 0.2057 | 0.1249 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 2.9110 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 2.9110 | 1.0000 | 1.0000 | Not calculated | 0.4115 | 0.1414 | ||
PSZ-AC_2:2 | 1.4654 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.4654 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1404 | ||
PSZ-AC_3:3 | 1.4649 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.4649 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1404 | ||
PSZ-AC_4:4 | 1.4680 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.4680 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1401 | ||
PSZ-AC_5:5 | 1.4597 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.4597 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1409 | ||
PSZ-AC_6:6 | 2.5936 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 2.5936 | 1.0000 | 1.0000 | Not calculated | 0.4115 | 0.1587 | ||
PSZ-AC_7:7 | 1.3719 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.3719 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1500 | ||
PSZ-AC_8:8 | 1.3676 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.3676 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1504 | ||
PSZ-AC_9:9 | 1.3769 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.3769 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1494 | ||
PSZ-AC_10:10 | 1.6470 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.6470 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1249 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
LGSTORE1 | PSZ-AC_1:1 | 0.000000 | 56.2505 | 0.001181 | 348.39 | 0.4115 | 1.0000 | 0.4115 | 1.000 | 0.4115 |
SMSTORE1 | PSZ-AC_2:2 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE2 | PSZ-AC_3:3 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE3 | PSZ-AC_4:4 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE4 | PSZ-AC_5:5 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
LGSTORE2 | PSZ-AC_6:6 | 0.000000 | 56.2505 | 0.001181 | 348.39 | 0.4115 | 1.0000 | 0.4115 | 1.000 | 0.4115 |
SMSTORE5 | PSZ-AC_7:7 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE6 | PSZ-AC_8:8 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE7 | PSZ-AC_9:9 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE8 | PSZ-AC_10:10 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC_1:1 | 0.000000 | 56.25 | 0.001181 | 348.3864 | 0.4115 | 0.4115 | 0.4115 |
PSZ-AC_2:2 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_3:3 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_4:4 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_5:5 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_6:6 | 0.000000 | 56.25 | 0.001181 | 348.3864 | 0.4115 | 0.4115 | 0.4115 |
PSZ-AC_7:7 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_8:8 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_9:9 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_10:10 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LGSTORE1 | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.9110 | 2.9110 | 2.9110 | No | 0.4115 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE1 | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.4654 | 1.4654 | 1.4654 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE2 | PSZ-AC_3:3 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.4649 | 1.4649 | 1.4649 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE3 | PSZ-AC_4:4 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.4680 | 1.4680 | 1.4680 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE4 | PSZ-AC_5:5 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.4597 | 1.4597 | 1.4597 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LGSTORE2 | PSZ-AC_6:6 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.5936 | 2.5936 | 2.5936 | No | 0.4115 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE5 | PSZ-AC_7:7 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.3719 | 1.3719 | 1.3719 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE6 | PSZ-AC_8:8 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.3676 | 1.3676 | 1.3676 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE7 | PSZ-AC_9:9 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.3769 | 1.3769 | 1.3769 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE8 | PSZ-AC_10:10 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.6470 | 1.6470 | 1.6470 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 2.9110 | 2.9110 | 2.9110 | 2.9110 | 0.4115 | 1.0000 |
PSZ-AC_2:2 | 1.4654 | 1.4654 | 1.4654 | 1.4654 | 0.2057 | 1.0000 |
PSZ-AC_3:3 | 1.4649 | 1.4649 | 1.4649 | 1.4649 | 0.2057 | 1.0000 |
PSZ-AC_4:4 | 1.4680 | 1.4680 | 1.4680 | 1.4680 | 0.2057 | 1.0000 |
PSZ-AC_5:5 | 1.4597 | 1.4597 | 1.4597 | 1.4597 | 0.2057 | 1.0000 |
PSZ-AC_6:6 | 2.5936 | 2.5936 | 2.5936 | 2.5936 | 0.4115 | 1.0000 |
PSZ-AC_7:7 | 1.3719 | 1.3719 | 1.3719 | 1.3719 | 0.2057 | 1.0000 |
PSZ-AC_8:8 | 1.3676 | 1.3676 | 1.3676 | 1.3676 | 0.2057 | 1.0000 |
PSZ-AC_9:9 | 1.3769 | 1.3769 | 1.3769 | 1.3769 | 0.2057 | 1.0000 |
PSZ-AC_10:10 | 1.6470 | 1.6470 | 1.6470 | 1.6470 | 0.2057 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LGSTORE1 | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.9110 | 2.9110 | 2.9110 | No | 0.4115 | 0.9042 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE1 | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.4654 | 1.4654 | 1.4654 | No | 0.2057 | 0.9420 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE2 | PSZ-AC_3:3 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.4649 | 1.4649 | 1.4649 | No | 0.2057 | 0.9386 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE3 | PSZ-AC_4:4 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.4680 | 1.4680 | 1.4680 | No | 0.2057 | 0.9301 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE4 | PSZ-AC_5:5 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.4597 | 1.4597 | 1.4597 | No | 0.2057 | 0.9049 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LGSTORE2 | PSZ-AC_6:6 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.5936 | 2.5936 | 2.5936 | No | 0.4115 | 0.9273 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE5 | PSZ-AC_7:7 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.3719 | 1.3719 | 1.3719 | No | 0.2057 | 0.8804 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE6 | PSZ-AC_8:8 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.3676 | 1.3676 | 1.3676 | No | 0.2057 | 0.8760 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE7 | PSZ-AC_9:9 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.3769 | 1.3769 | 1.3769 | No | 0.2057 | 0.8215 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE8 | PSZ-AC_10:10 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.6470 | 1.6470 | 1.6470 | No | 0.2057 | 0.6852 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 2.9110 | 2.9110 | 2.9110 | 2.9110 | 0.4115 | 1.0000 |
PSZ-AC_2:2 | 1.4654 | 1.4654 | 1.4654 | 1.4654 | 0.2057 | 1.0000 |
PSZ-AC_3:3 | 1.4649 | 1.4649 | 1.4649 | 1.4649 | 0.2057 | 1.0000 |
PSZ-AC_4:4 | 1.4680 | 1.4680 | 1.4680 | 1.4680 | 0.2057 | 1.0000 |
PSZ-AC_5:5 | 1.4597 | 1.4597 | 1.4597 | 1.4597 | 0.2057 | 1.0000 |
PSZ-AC_6:6 | 2.5936 | 2.5936 | 2.5936 | 2.5936 | 0.4115 | 1.0000 |
PSZ-AC_7:7 | 1.3719 | 1.3719 | 1.3719 | 1.3719 | 0.2057 | 1.0000 |
PSZ-AC_8:8 | 1.3676 | 1.3676 | 1.3676 | 1.3676 | 0.2057 | 1.0000 |
PSZ-AC_9:9 | 1.3769 | 1.3769 | 1.3769 | 1.3769 | 0.2057 | 1.0000 |
PSZ-AC_10:10 | 1.6470 | 1.6470 | 1.6470 | 1.6470 | 0.2057 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:02
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Dubai Intl AP - ARE IWEC2 WMO#=411940 |
Total gross floor area [m2] | 2090.32 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
LGSTORE1 | 348.39 | 348.39 | 0.00 | 112.00 |
SMSTORE1 | 174.19 | 174.19 | 0.00 | 112.00 |
SMSTORE2 | 174.19 | 174.19 | 0.00 | 84.29 |
SMSTORE3 | 174.19 | 174.19 | 0.00 | 84.29 |
SMSTORE4 | 174.19 | 174.19 | 0.00 | 84.29 |
LGSTORE2 | 348.39 | 348.39 | 0.00 | 77.29 |
SMSTORE5 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE6 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE7 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE8 | 174.19 | 174.19 | 0.00 | 77.29 |
Totals | 2090.32 | 2090.32 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 4.67 |
Number of hours not met | 4.67 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 84.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 642.23 | 105570.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 366.68 | 23459.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 60.14 | 5507.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 128.15 | 8059.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 136.66 | 14964.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 57.49 | 11787.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 128.15 | 1391.36 |
Natural Gas | 0.00 | 0.00 |
Additional | 0.00 | 0.00 |
Total | 128.15 | 1391.36 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 175.42 |
Space Heating | 0.00 |
Space Cooling | 307.24 |
Fans (All) | 65.38 |
Service Water Heating | 27.50 |
Receptacle Equipment | 61.31 |
Miscellaneous (All) | 665.62 |
Subtotal | 665.62 |
Natural Gas [MJ/m2] | |
Space Heating | 0.00 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 0.00 |
Subtotal | 0.00 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 26.35 |
Space Heating | 0.00 |
Space Cooling | 46.16 |
Fans (All) | 9.82 |
Service Water Heating | 4.13 |
Receptacle Equipment | 9.21 |
Miscellaneous | 4.32 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
TYPE1_OCC_SCH | 1630. | 5840. |
TYPE2_OCC_SCH | 995. | 4429. |
TYPE3_OCC_SCH | 1709. | 4064. |
LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 3767. | 8760. |
LTG_SCH_BASE_LPD2 | 3238. | 8760. |
LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 3296. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | 5084. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | 5084. | 8760. |
LTG_SCH_BASE_SMALL_LPD1 | 4453. | 8760. |
LTG_SCH_BASE_LPD1 | 4376. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | 3767. | 8760. |
LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 3584. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 4096. | 8760. |
TYPE1_EQUIP_SCH | 4868. | 8760. |
TYPE2_EQUIP_SCH | 3893. | 8760. |
TYPE3_EQUIP_SCH | 3584. | 8760. |
TYPE1_INFIL_SCH | 4302. | 8760. |
TYPE2_INFIL_SCH | 5164. | 8760. |
TYPE3_INFIL_SCH | 5438. | 8760. |
INFIL_DOOR_OPENING_SCH | 2505. | 4380. |
TYPE1_MINOA_MOTORIZEDDAMPER_SCH | 5579. | 5579. |
TYPE2_MINOA_MOTORIZEDDAMPER_SCH | 4429. | 4429. |
TYPE3_MINOA_MOTORIZEDDAMPER_SCH | 4064. | 4064. |
TYPE1_SWH_SCH | 2063. | 6048. |
TYPE2_SWH_SCH | 1831. | 4429. |
TYPE3_SWH_SCH | 1733. | 4064. |
AVERAGE_SWH_SCH | 1863. | 6152. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 7118. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 5839. | 5839. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 7300. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6570. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
TYPE1_HTGSETP_SCH_NO_OPTIMUM | LGSTORE1 DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
TYPE1_CLGSETP_SCH_NO_OPTIMUM | LGSTORE1 DUAL SP CONTROL | July | 23.89 | 365 | 23.89 | 365 |
TYPE2_HTGSETP_SCH_NO_OPTIMUM | SMSTORE2 DUAL SP CONTROL | January | 21.11 | 365 | 15.56 | 365 |
TYPE2_CLGSETP_SCH_NO_OPTIMUM | SMSTORE2 DUAL SP CONTROL | July | 23.89 | 365 | 29.44 | 365 |
TYPE3_HTGSETP_SCH_NO_OPTIMUM | LGSTORE2 DUAL SP CONTROL | January | 21.11 | 365 | 15.56 | 365 |
TYPE3_CLGSETP_SCH_NO_OPTIMUM | LGSTORE2 DUAL SP CONTROL | July | 23.89 | 365 | 29.44 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:02
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
LGSTORE1 | 8019.33 | 740.67 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 8323.50 | 436.50 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 6813.00 | 1911.33 | 35.67 | 0.00 | 0.00 |
SMSTORE3 | 6744.50 | 1969.50 | 46.00 | 0.00 | 0.00 |
SMSTORE4 | 6842.00 | 1873.17 | 44.83 | 0.00 | 0.00 |
LGSTORE2 | 7308.50 | 1404.17 | 47.33 | 0.00 | 0.00 |
SMSTORE5 | 7403.17 | 1309.17 | 47.67 | 0.00 | 0.00 |
SMSTORE6 | 7412.33 | 1300.00 | 47.67 | 0.00 | 0.00 |
SMSTORE7 | 7394.00 | 1317.83 | 48.17 | 0.00 | 0.00 |
SMSTORE8 | 6937.00 | 1656.83 | 166.17 | 0.00 | 0.00 |
Min | 6744.50 | 436.50 | 0.00 | 0.00 | 0.00 |
Max | 8323.50 | 1969.50 | 166.17 | 0.00 | 0.00 |
Average | 7319.73 | 1391.92 | 48.35 | 0.00 | 0.00 |
Sum | 73197.33 | 13919.17 | 483.50 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
LGSTORE1 | 89041.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 43777.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 25323.67 | 148.50 | 2.83 | 0.00 | 0.00 |
SMSTORE3 | 25323.33 | 148.67 | 3.00 | 0.00 | 0.00 |
SMSTORE4 | 25327.17 | 145.00 | 2.83 | 0.00 | 0.00 |
LGSTORE2 | 92893.00 | 302.00 | 16.00 | 0.00 | 0.00 |
SMSTORE5 | 45752.50 | 150.50 | 9.00 | 0.00 | 0.00 |
SMSTORE6 | 45753.00 | 150.00 | 9.00 | 0.00 | 0.00 |
SMSTORE7 | 45752.50 | 150.00 | 9.50 | 0.00 | 0.00 |
SMSTORE8 | 45737.00 | 165.50 | 9.50 | 0.00 | 0.00 |
Min | 25323.33 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 92893.00 | 302.00 | 16.00 | 0.00 | 0.00 |
Average | 48468.02 | 136.02 | 6.17 | 0.00 | 0.00 |
Sum | 484680.17 | 1360.17 | 61.67 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
LGSTORE1 | 6441.67 | 2318.33 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 7393.67 | 1366.33 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 5047.50 | 3681.33 | 31.17 | 0.00 | 0.00 |
SMSTORE3 | 5056.00 | 3665.33 | 38.67 | 0.00 | 0.00 |
SMSTORE4 | 5075.50 | 3646.00 | 38.50 | 0.00 | 0.00 |
LGSTORE2 | 5240.00 | 3482.17 | 37.83 | 0.00 | 0.00 |
SMSTORE5 | 5284.00 | 3434.00 | 42.00 | 0.00 | 0.00 |
SMSTORE6 | 5283.50 | 3434.50 | 42.00 | 0.00 | 0.00 |
SMSTORE7 | 5325.17 | 3392.33 | 42.50 | 0.00 | 0.00 |
SMSTORE8 | 5334.67 | 3321.83 | 103.50 | 0.00 | 0.00 |
Min | 5047.50 | 1366.33 | 0.00 | 0.00 | 0.00 |
Max | 7393.67 | 3681.33 | 103.50 | 0.00 | 0.00 |
Average | 5548.17 | 3174.22 | 37.62 | 0.00 | 0.00 |
Sum | 55481.67 | 31742.17 | 376.17 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
LGSTORE1 | 79610.67 | 9430.33 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 39324.50 | 4452.50 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 22013.67 | 3460.67 | 0.67 | 0.00 | 0.00 |
SMSTORE3 | 22039.67 | 3434.67 | 0.67 | 0.00 | 0.00 |
SMSTORE4 | 21946.83 | 3527.50 | 0.67 | 0.00 | 0.00 |
LGSTORE2 | 78235.67 | 14971.33 | 4.00 | 0.00 | 0.00 |
SMSTORE5 | 38395.50 | 7514.00 | 2.50 | 0.00 | 0.00 |
SMSTORE6 | 38327.00 | 7582.50 | 2.50 | 0.00 | 0.00 |
SMSTORE7 | 38496.67 | 7412.83 | 2.50 | 0.00 | 0.00 |
SMSTORE8 | 40312.00 | 5598.00 | 2.00 | 0.00 | 0.00 |
Min | 21946.83 | 3434.67 | 0.00 | 0.00 | 0.00 |
Max | 79610.67 | 14971.33 | 4.00 | 0.00 | 0.00 |
Average | 41870.22 | 6738.43 | 1.55 | 0.00 | 0.00 |
Sum | 418702.17 | 67384.33 | 15.50 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:02
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:02
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
For: Environment
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTRIPMALL
For: Environment
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 0B
For: Environment
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY ARE_DUBAI_DUBAIINTL
For: Environment
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: ZoneCoolingSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.102038E+11 | 15904.03 | 30-JAN-08:63 | 20.33 | 17.75 | 0.140762E+10 | 1685.99 | 22-JAN-13:00 | 20.33 | 17.75 |
February | 0.105204E+11 | 29614.39 | 09-FEB-08:62 | 22.17 | 19.26 | 0.127169E+10 | 1686.05 | 05-FEB-13:09 | 22.17 | 19.26 |
March | 0.137242E+11 | 54620.02 | 02-MAR-08:62 | 27.00 | 17.55 | 0.139701E+10 | 1686.02 | 26-MAR-17:00 | 31.00 | 18.89 |
April | 0.167747E+11 | 52301.79 | 29-APR-07:02 | 27.25 | 16.62 | 0.136159E+10 | 1686.04 | 15-APR-12:20 | 27.25 | 16.62 |
May | 0.230796E+11 | 57693.54 | 11-MAY-07:01 | 30.33 | 16.47 | 0.140186E+10 | 1686.05 | 14-MAY-17:00 | 33.00 | 21.47 |
June | 0.245729E+11 | 50362.31 | 01-JUN-07:01 | 30.17 | 21.35 | 0.135491E+10 | 1686.10 | 02-JUN-12:00 | 38.60 | 24.59 |
July | 0.280826E+11 | 56391.36 | 04-JUL-07:01 | 31.33 | 17.56 | 0.141321E+10 | 1686.16 | 04-JUL-12:20 | 39.90 | 23.87 |
August | 0.292659E+11 | 50672.10 | 06-AUG-07:01 | 35.08 | 22.69 | 0.139458E+10 | 1686.11 | 06-AUG-17:30 | 39.50 | 26.07 |
September | 0.256618E+11 | 47344.17 | 02-SEP-07:01 | 32.25 | 23.03 | 0.136555E+10 | 1686.12 | 15-SEP-12:09 | 37.12 | 24.73 |
October | 0.233447E+11 | 54033.58 | 20-OCT-07:02 | 23.25 | 15.43 | 0.141001E+10 | 1686.12 | 01-OCT-12:09 | 23.25 | 15.43 |
November | 0.178506E+11 | 54552.65 | 05-NOV-07:02 | 21.17 | 15.81 | 0.136321E+10 | 1686.07 | 04-NOV-12:09 | 21.17 | 15.81 |
December | 0.127122E+11 | 45590.35 | 12-DEC-08:62 | 23.17 | 17.37 | 0.141625E+10 | 1686.05 | 01-DEC-13:50 | 23.17 | 17.37 |
Annual Sum or Average | 0.235793E+12 | 0.165575E+11 | ||||||||
Minimum of Months | 0.102038E+11 | 15904.03 | 20.33 | 15.43 | 0.127169E+10 | 1685.99 | 20.33 | 15.43 | ||
Maximum of Months | 0.292659E+11 | 57693.54 | 35.08 | 23.03 | 0.141625E+10 | 1686.16 | 39.90 | 26.07 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.580570E+10 | 10010.88 | 30-JAN-08:63 | 20.33 | 17.75 | 0.704216E+09 | 842.97 | 22-JAN-13:00 | 20.33 | 17.75 |
February | 0.589157E+10 | 17240.37 | 09-FEB-08:62 | 22.17 | 19.26 | 0.636047E+09 | 842.99 | 05-FEB-13:09 | 22.17 | 19.26 |
March | 0.750350E+10 | 28060.27 | 02-MAR-08:62 | 27.00 | 17.55 | 0.698627E+09 | 843.00 | 25-MAR-12:00 | 30.00 | 19.03 |
April | 0.891283E+10 | 27393.50 | 29-APR-07:02 | 27.25 | 16.62 | 0.680787E+09 | 843.01 | 22-APR-12:00 | 27.25 | 16.62 |
May | 0.117916E+11 | 29698.05 | 11-MAY-07:01 | 30.33 | 16.47 | 0.700912E+09 | 843.01 | 29-MAY-12:00 | 33.40 | 29.11 |
June | 0.123717E+11 | 27802.21 | 02-JUN-07:01 | 29.67 | 18.04 | 0.677429E+09 | 843.04 | 02-JUN-12:00 | 38.60 | 24.59 |
July | 0.139914E+11 | 29370.73 | 04-JUL-07:01 | 31.33 | 17.56 | 0.706563E+09 | 843.06 | 02-JUL-12:30 | 31.33 | 17.56 |
August | 0.144189E+11 | 26867.61 | 06-AUG-07:01 | 35.08 | 22.69 | 0.697236E+09 | 843.02 | 13-AUG-17:30 | 37.50 | 25.83 |
September | 0.128016E+11 | 26724.90 | 26-SEP-07:01 | 27.00 | 17.98 | 0.682742E+09 | 843.03 | 24-SEP-12:50 | 27.00 | 17.98 |
October | 0.118289E+11 | 28959.13 | 20-OCT-07:02 | 23.25 | 15.43 | 0.704980E+09 | 843.01 | 06-OCT-12:00 | 23.25 | 15.43 |
November | 0.927965E+10 | 29227.31 | 05-NOV-07:02 | 21.17 | 15.81 | 0.681587E+09 | 843.01 | 17-NOV-13:00 | 29.00 | 19.29 |
December | 0.698541E+10 | 25121.78 | 12-DEC-08:62 | 23.17 | 17.37 | 0.708216E+09 | 843.00 | 03-DEC-13:39 | 23.17 | 17.37 |
Annual Sum or Average | 0.121583E+12 | 0.827934E+10 | ||||||||
Minimum of Months | 0.580570E+10 | 10010.88 | 20.33 | 15.43 | 0.636047E+09 | 842.97 | 20.33 | 15.43 | ||
Maximum of Months | 0.144189E+11 | 29698.05 | 35.08 | 22.69 | 0.708216E+09 | 843.06 | 38.60 | 29.11 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.404340E+10 | 10187.67 | 30-JAN-07:03 | 20.17 | 17.39 | 0.419077E+09 | 842.92 | 21-JAN-13:00 | 20.17 | 17.39 |
February | 0.423888E+10 | 18146.92 | 09-FEB-07:03 | 22.42 | 19.25 | 0.381230E+09 | 842.91 | 04-FEB-13:00 | 22.42 | 19.25 |
March | 0.561351E+10 | 28581.95 | 28-MAR-06:02 | 24.00 | 14.40 | 0.431333E+09 | 843.00 | 25-MAR-12:00 | 24.00 | 14.40 |
April | 0.676450E+10 | 28481.56 | 29-APR-06:02 | 25.25 | 16.39 | 0.411204E+09 | 843.01 | 08-APR-12:30 | 25.25 | 16.39 |
May | 0.938250E+10 | 29060.34 | 05-MAY-06:02 | 25.92 | 15.74 | 0.427134E+09 | 842.93 | 27-MAY-12:00 | 34.50 | 22.36 |
June | 0.100007E+11 | 27380.95 | 01-JUN-06:01 | 27.43 | 20.95 | 0.418114E+09 | 843.01 | 03-JUN-12:00 | 39.80 | 23.10 |
July | 0.112073E+11 | 28691.66 | 04-JUL-07:01 | 31.33 | 17.56 | 0.421576E+09 | 843.05 | 29-JUL-12:09 | 39.77 | 23.68 |
August | 0.118290E+11 | 23664.61 | 16-AUG-06:01 | 33.90 | 25.20 | 0.433196E+09 | 842.90 | 26-AUG-12:20 | 37.10 | 27.26 |
September | 0.102618E+11 | 22157.31 | 05-SEP-06:01 | 30.92 | 23.71 | 0.412043E+09 | 843.03 | 30-SEP-12:00 | 36.20 | 24.62 |
October | 0.933497E+10 | 27900.27 | 20-OCT-06:02 | 23.82 | 15.96 | 0.421452E+09 | 842.94 | 28-OCT-12:00 | 33.40 | 20.86 |
November | 0.713016E+10 | 27499.61 | 05-NOV-07:02 | 21.17 | 15.81 | 0.406568E+09 | 842.99 | 04-NOV-12:09 | 21.17 | 15.81 |
December | 0.502020E+10 | 23471.48 | 12-DEC-07:02 | 23.17 | 17.81 | 0.419490E+09 | 842.96 | 30-DEC-13:50 | 25.08 | 14.90 |
Annual Sum or Average | 0.948269E+11 | 0.500242E+10 | ||||||||
Minimum of Months | 0.404340E+10 | 10187.67 | 20.17 | 14.40 | 0.381230E+09 | 842.90 | 20.17 | 14.40 | ||
Maximum of Months | 0.118290E+11 | 29060.34 | 33.90 | 25.20 | 0.433196E+09 | 843.05 | 39.80 | 27.26 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.397269E+10 | 9908.47 | 30-JAN-07:03 | 20.17 | 17.39 | 0.418988E+09 | 842.92 | 21-JAN-13:00 | 20.17 | 17.39 |
February | 0.419656E+10 | 18162.94 | 09-FEB-07:03 | 22.42 | 19.25 | 0.381195E+09 | 842.91 | 04-FEB-13:00 | 22.42 | 19.25 |
March | 0.559083E+10 | 29180.06 | 28-MAR-06:02 | 24.00 | 14.40 | 0.431315E+09 | 843.00 | 25-MAR-12:00 | 24.00 | 14.40 |
April | 0.678162E+10 | 28600.66 | 29-APR-06:02 | 25.25 | 16.39 | 0.411203E+09 | 843.01 | 22-APR-12:00 | 25.25 | 16.39 |
May | 0.946269E+10 | 29184.44 | 05-MAY-06:02 | 25.92 | 15.74 | 0.427141E+09 | 842.93 | 27-MAY-12:00 | 34.50 | 22.36 |
June | 0.100943E+11 | 27559.67 | 01-JUN-06:01 | 27.43 | 20.95 | 0.418122E+09 | 843.01 | 03-JUN-12:00 | 39.80 | 23.10 |
July | 0.113354E+11 | 28892.27 | 04-JUL-07:01 | 31.33 | 17.56 | 0.421586E+09 | 843.02 | 29-JUL-12:09 | 39.77 | 23.68 |
August | 0.119554E+11 | 23846.62 | 16-AUG-06:01 | 33.90 | 25.20 | 0.433206E+09 | 842.90 | 26-AUG-12:09 | 37.05 | 27.29 |
September | 0.103650E+11 | 22509.19 | 05-SEP-06:01 | 30.92 | 23.71 | 0.412052E+09 | 843.03 | 30-SEP-12:00 | 36.20 | 24.62 |
October | 0.941860E+10 | 28016.78 | 20-OCT-06:02 | 23.82 | 15.96 | 0.421459E+09 | 842.94 | 28-OCT-12:00 | 33.40 | 20.86 |
November | 0.715490E+10 | 27619.74 | 05-NOV-07:02 | 21.17 | 15.81 | 0.406568E+09 | 842.99 | 04-NOV-12:09 | 21.17 | 15.81 |
December | 0.499039E+10 | 23519.96 | 12-DEC-07:02 | 23.17 | 17.81 | 0.419468E+09 | 842.96 | 30-DEC-13:50 | 25.08 | 14.90 |
Annual Sum or Average | 0.953183E+11 | 0.500230E+10 | ||||||||
Minimum of Months | 0.397269E+10 | 9908.47 | 20.17 | 14.40 | 0.381195E+09 | 842.90 | 20.17 | 14.40 | ||
Maximum of Months | 0.119554E+11 | 29184.44 | 33.90 | 25.20 | 0.433206E+09 | 843.03 | 39.80 | 27.29 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.375447E+10 | 8692.35 | 30-JAN-07:03 | 20.17 | 17.39 | 0.418774E+09 | 842.92 | 21-JAN-13:00 | 20.17 | 17.39 |
February | 0.400766E+10 | 16734.98 | 09-FEB-07:03 | 22.42 | 19.25 | 0.381092E+09 | 842.91 | 04-FEB-13:00 | 22.42 | 19.25 |
March | 0.538171E+10 | 27359.34 | 28-MAR-06:02 | 24.00 | 14.40 | 0.431236E+09 | 843.00 | 25-MAR-12:00 | 24.00 | 14.40 |
April | 0.659709E+10 | 28288.75 | 29-APR-06:02 | 25.25 | 16.39 | 0.411167E+09 | 843.01 | 22-APR-12:00 | 25.25 | 16.39 |
May | 0.930419E+10 | 28872.77 | 05-MAY-06:02 | 25.92 | 15.74 | 0.427109E+09 | 842.94 | 27-MAY-12:00 | 34.50 | 22.36 |
June | 0.994410E+10 | 27218.42 | 01-JUN-06:01 | 27.43 | 20.95 | 0.418092E+09 | 843.00 | 03-JUN-12:00 | 39.80 | 23.10 |
July | 0.112079E+11 | 28586.99 | 04-JUL-07:01 | 31.33 | 17.56 | 0.421559E+09 | 843.04 | 29-JUL-12:09 | 39.77 | 23.68 |
August | 0.118228E+11 | 23561.82 | 16-AUG-06:01 | 33.90 | 25.20 | 0.433177E+09 | 842.90 | 26-AUG-12:20 | 37.10 | 27.26 |
September | 0.102303E+11 | 22346.84 | 05-SEP-06:01 | 30.92 | 23.71 | 0.412023E+09 | 843.03 | 30-SEP-12:00 | 36.20 | 24.62 |
October | 0.927139E+10 | 27746.45 | 20-OCT-06:02 | 23.82 | 15.96 | 0.421428E+09 | 842.94 | 28-OCT-12:00 | 33.40 | 20.86 |
November | 0.698574E+10 | 27369.70 | 05-NOV-07:02 | 21.17 | 15.81 | 0.406536E+09 | 842.99 | 04-NOV-12:09 | 21.17 | 15.81 |
December | 0.478960E+10 | 23254.05 | 12-DEC-07:02 | 23.17 | 17.81 | 0.419390E+09 | 842.96 | 30-DEC-13:50 | 25.08 | 14.90 |
Annual Sum or Average | 0.932969E+11 | 0.500158E+10 | ||||||||
Minimum of Months | 0.375447E+10 | 8692.35 | 20.17 | 14.40 | 0.381092E+09 | 842.90 | 20.17 | 14.40 | ||
Maximum of Months | 0.118228E+11 | 28872.77 | 33.90 | 25.20 | 0.433177E+09 | 843.04 | 39.80 | 27.26 |
Report: ZoneCoolingSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.597767E+10 | 13956.80 | 30-JAN-08:63 | 20.33 | 17.75 | 0.143140E+10 | 2247.99 | 28-JAN-15:09 | 20.33 | 17.75 |
February | 0.655347E+10 | 28281.96 | 06-FEB-08:62 | 21.17 | 17.80 | 0.130491E+10 | 2247.97 | 04-FEB-15:00 | 21.17 | 17.80 |
March | 0.900493E+10 | 46316.77 | 02-MAR-08:62 | 27.00 | 17.55 | 0.147904E+10 | 2247.80 | 11-MAR-15:00 | 24.60 | 18.51 |
April | 0.112287E+11 | 49409.34 | 29-APR-07:02 | 27.25 | 16.62 | 0.141068E+10 | 2247.91 | 29-APR-14:00 | 34.00 | 22.91 |
May | 0.161366E+11 | 51067.54 | 11-MAY-07:01 | 30.33 | 16.47 | 0.145944E+10 | 2247.88 | 27-MAY-14:00 | 35.00 | 21.99 |
June | 0.173121E+11 | 47300.70 | 01-JUN-07:01 | 30.17 | 21.35 | 0.143147E+10 | 2247.81 | 24-JUN-14:09 | 36.00 | 27.04 |
July | 0.195914E+11 | 51379.40 | 04-JUL-08:61 | 32.82 | 19.26 | 0.144089E+10 | 2247.81 | 08-JUL-14:00 | 35.00 | 26.74 |
August | 0.207496E+11 | 41897.77 | 16-AUG-07:01 | 33.67 | 25.11 | 0.148203E+10 | 2247.81 | 26-AUG-14:00 | 36.00 | 27.58 |
September | 0.178438E+11 | 41068.54 | 26-SEP-07:01 | 27.00 | 17.98 | 0.141212E+10 | 2247.87 | 16-SEP-14:09 | 27.00 | 17.98 |
October | 0.160856E+11 | 49484.75 | 20-OCT-07:02 | 23.25 | 15.43 | 0.143704E+10 | 2247.96 | 28-OCT-14:00 | 32.00 | 20.74 |
November | 0.119550E+11 | 48093.79 | 19-NOV-09:02 | 25.40 | 16.09 | 0.138289E+10 | 2247.98 | 04-NOV-14:09 | 25.40 | 16.09 |
December | 0.788681E+10 | 42320.76 | 12-DEC-08:62 | 23.17 | 17.37 | 0.143670E+10 | 2247.93 | 30-DEC-15:09 | 24.83 | 13.98 |
Annual Sum or Average | 0.160326E+12 | 0.171086E+11 | ||||||||
Minimum of Months | 0.597767E+10 | 13956.80 | 20.33 | 15.43 | 0.130491E+10 | 2247.80 | 20.33 | 13.98 | ||
Maximum of Months | 0.207496E+11 | 51379.40 | 33.67 | 25.11 | 0.148203E+10 | 2247.99 | 36.00 | 27.58 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.301384E+10 | 6745.66 | 30-JAN-08:63 | 20.33 | 17.75 | 0.715704E+09 | 1123.96 | 28-JAN-15:09 | 20.33 | 17.75 |
February | 0.334551E+10 | 13982.64 | 06-FEB-08:62 | 21.17 | 17.80 | 0.652437E+09 | 1123.95 | 04-FEB-15:00 | 21.17 | 17.80 |
March | 0.465087E+10 | 24338.95 | 02-MAR-08:62 | 27.00 | 17.55 | 0.739509E+09 | 1123.87 | 11-MAR-15:00 | 24.60 | 18.51 |
April | 0.587572E+10 | 24672.12 | 29-APR-07:02 | 27.25 | 16.62 | 0.705304E+09 | 1123.93 | 29-APR-14:00 | 34.00 | 22.91 |
May | 0.850369E+10 | 26853.03 | 11-MAY-07:01 | 30.33 | 16.47 | 0.729677E+09 | 1123.91 | 27-MAY-14:00 | 35.00 | 21.99 |
June | 0.912678E+10 | 24957.62 | 01-JUN-07:01 | 30.17 | 21.35 | 0.715686E+09 | 1123.87 | 24-JUN-14:09 | 36.00 | 27.04 |
July | 0.103478E+11 | 27087.71 | 04-JUL-08:61 | 32.82 | 19.26 | 0.720397E+09 | 1123.87 | 08-JUL-14:00 | 35.00 | 26.74 |
August | 0.109385E+11 | 22093.62 | 16-AUG-07:01 | 33.67 | 25.11 | 0.740971E+09 | 1123.87 | 26-AUG-14:00 | 36.00 | 27.58 |
September | 0.939916E+10 | 21576.81 | 26-SEP-07:01 | 27.00 | 17.98 | 0.706014E+09 | 1124.05 | 16-SEP-14:09 | 27.00 | 17.98 |
October | 0.845139E+10 | 25954.27 | 20-OCT-07:02 | 23.25 | 15.43 | 0.718489E+09 | 1123.95 | 28-OCT-14:00 | 32.00 | 20.74 |
November | 0.623919E+10 | 25232.91 | 19-NOV-09:02 | 25.40 | 16.09 | 0.691416E+09 | 1123.96 | 04-NOV-14:09 | 25.40 | 16.09 |
December | 0.404662E+10 | 20774.58 | 12-DEC-08:62 | 23.17 | 17.37 | 0.718341E+09 | 1123.93 | 30-DEC-15:09 | 24.83 | 13.98 |
Annual Sum or Average | 0.839391E+11 | 0.855394E+10 | ||||||||
Minimum of Months | 0.301384E+10 | 6745.66 | 20.33 | 15.43 | 0.652437E+09 | 1123.87 | 20.33 | 13.98 | ||
Maximum of Months | 0.109385E+11 | 27087.71 | 33.67 | 25.11 | 0.740971E+09 | 1124.05 | 36.00 | 27.58 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.296132E+10 | 6454.89 | 30-JAN-08:63 | 20.33 | 17.75 | 0.715625E+09 | 1123.96 | 28-JAN-15:09 | 20.33 | 17.75 |
February | 0.329811E+10 | 13643.89 | 06-FEB-08:62 | 21.17 | 17.80 | 0.652390E+09 | 1123.95 | 04-FEB-15:00 | 21.17 | 17.80 |
March | 0.459981E+10 | 24234.89 | 02-MAR-08:62 | 27.00 | 17.55 | 0.739486E+09 | 1123.87 | 11-MAR-15:00 | 24.60 | 18.51 |
April | 0.583430E+10 | 24453.18 | 29-APR-07:02 | 27.25 | 16.62 | 0.705299E+09 | 1123.93 | 29-APR-14:00 | 34.00 | 22.91 |
May | 0.846932E+10 | 26752.57 | 11-MAY-07:01 | 30.33 | 16.47 | 0.729673E+09 | 1123.91 | 27-MAY-14:00 | 35.00 | 21.99 |
June | 0.909492E+10 | 24861.43 | 01-JUN-07:01 | 30.17 | 21.35 | 0.715682E+09 | 1123.87 | 24-JUN-14:09 | 36.00 | 27.04 |
July | 0.103212E+11 | 26997.28 | 04-JUL-08:61 | 32.82 | 19.26 | 0.720393E+09 | 1123.87 | 08-JUL-14:00 | 35.00 | 26.74 |
August | 0.109115E+11 | 22011.23 | 16-AUG-07:01 | 33.67 | 25.11 | 0.740968E+09 | 1123.87 | 26-AUG-14:00 | 36.00 | 27.58 |
September | 0.937177E+10 | 21496.56 | 26-SEP-07:01 | 27.00 | 17.98 | 0.706010E+09 | 1124.05 | 16-SEP-14:09 | 27.00 | 17.98 |
October | 0.842029E+10 | 25859.61 | 20-OCT-07:02 | 23.25 | 15.43 | 0.718482E+09 | 1123.95 | 28-OCT-14:00 | 32.00 | 20.74 |
November | 0.620202E+10 | 24975.36 | 19-NOV-09:02 | 25.40 | 16.09 | 0.691411E+09 | 1123.96 | 04-NOV-14:09 | 25.40 | 16.09 |
December | 0.400103E+10 | 20450.57 | 12-DEC-08:62 | 23.17 | 17.37 | 0.718318E+09 | 1123.93 | 30-DEC-15:09 | 24.83 | 13.98 |
Annual Sum or Average | 0.834857E+11 | 0.855374E+10 | ||||||||
Minimum of Months | 0.296132E+10 | 6454.89 | 20.33 | 15.43 | 0.652390E+09 | 1123.87 | 20.33 | 13.98 | ||
Maximum of Months | 0.109115E+11 | 26997.28 | 33.67 | 25.11 | 0.740968E+09 | 1124.05 | 36.00 | 27.58 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.284213E+10 | 5518.18 | 30-JAN-08:63 | 20.33 | 17.75 | 0.715346E+09 | 1123.96 | 28-JAN-15:09 | 20.33 | 17.75 |
February | 0.319667E+10 | 12546.07 | 06-FEB-08:62 | 21.17 | 17.80 | 0.652209E+09 | 1123.95 | 04-FEB-15:00 | 21.17 | 17.80 |
March | 0.450925E+10 | 24315.62 | 02-MAR-08:62 | 27.00 | 17.55 | 0.739408E+09 | 1123.87 | 11-MAR-15:00 | 24.60 | 18.51 |
April | 0.581108E+10 | 24097.76 | 29-APR-07:02 | 27.25 | 16.62 | 0.705296E+09 | 1123.93 | 29-APR-14:00 | 34.00 | 22.91 |
May | 0.855211E+10 | 26922.78 | 11-MAY-07:01 | 30.33 | 16.47 | 0.729682E+09 | 1123.91 | 27-MAY-14:00 | 35.00 | 21.99 |
June | 0.921345E+10 | 25052.11 | 01-JUN-07:01 | 30.17 | 21.35 | 0.715693E+09 | 1123.87 | 24-JUN-14:00 | 36.00 | 27.58 |
July | 0.104962E+11 | 27256.24 | 04-JUL-08:61 | 32.82 | 19.26 | 0.720407E+09 | 1123.87 | 08-JUL-14:00 | 35.00 | 26.74 |
August | 0.111222E+11 | 22296.25 | 16-AUG-07:01 | 33.67 | 25.11 | 0.740979E+09 | 1123.87 | 26-AUG-14:00 | 36.00 | 27.58 |
September | 0.952337E+10 | 21699.12 | 26-SEP-07:01 | 27.00 | 17.98 | 0.706023E+09 | 1124.06 | 16-SEP-14:09 | 27.00 | 17.98 |
October | 0.852719E+10 | 26039.02 | 20-OCT-07:02 | 23.25 | 15.43 | 0.718493E+09 | 1123.95 | 28-OCT-14:00 | 32.00 | 20.74 |
November | 0.622434E+10 | 24653.63 | 05-NOV-08:62 | 24.50 | 17.35 | 0.691413E+09 | 1123.96 | 04-NOV-14:09 | 24.50 | 17.35 |
December | 0.392317E+10 | 19670.86 | 12-DEC-08:62 | 23.17 | 17.37 | 0.718247E+09 | 1123.93 | 30-DEC-15:09 | 24.83 | 13.98 |
Annual Sum or Average | 0.839412E+11 | 0.855320E+10 | ||||||||
Minimum of Months | 0.284213E+10 | 5518.18 | 20.33 | 15.43 | 0.652209E+09 | 1123.87 | 20.33 | 13.98 | ||
Maximum of Months | 0.111222E+11 | 27256.24 | 33.67 | 25.11 | 0.740979E+09 | 1124.06 | 36.00 | 27.58 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.307364E+10 | 5910.35 | 28-JAN-14:00 | 28.00 | 13.07 | 0.714987E+09 | 1123.95 | 28-JAN-15:09 | 25.75 | 18.22 |
February | 0.349586E+10 | 9756.06 | 06-FEB-08:62 | 21.17 | 17.80 | 0.651936E+09 | 1123.96 | 04-FEB-15:00 | 21.17 | 17.80 |
March | 0.506112E+10 | 29977.91 | 02-MAR-08:62 | 27.00 | 17.55 | 0.739248E+09 | 1123.87 | 11-MAR-15:00 | 24.60 | 18.51 |
April | 0.686964E+10 | 24949.35 | 29-APR-07:02 | 27.25 | 16.62 | 0.705437E+09 | 1123.94 | 29-APR-14:00 | 34.00 | 22.91 |
May | 0.105388E+11 | 31767.59 | 11-MAY-07:01 | 30.33 | 16.47 | 0.729862E+09 | 1123.93 | 27-MAY-14:00 | 35.00 | 21.99 |
June | 0.114543E+11 | 28601.54 | 01-JUN-07:01 | 30.17 | 21.35 | 0.715865E+09 | 1123.87 | 03-JUN-14:09 | 38.67 | 24.77 |
July | 0.131272E+11 | 32469.64 | 04-JUL-08:61 | 32.82 | 19.26 | 0.720599E+09 | 1123.87 | 08-JUL-14:00 | 35.00 | 26.74 |
August | 0.141024E+11 | 26864.32 | 06-AUG-08:61 | 36.17 | 23.08 | 0.741122E+09 | 1123.87 | 26-AUG-14:00 | 36.00 | 27.58 |
September | 0.119245E+11 | 25386.95 | 26-SEP-07:01 | 27.00 | 17.98 | 0.706248E+09 | 1124.08 | 23-SEP-14:09 | 27.00 | 17.98 |
October | 0.105227E+11 | 29620.47 | 20-OCT-07:02 | 23.25 | 15.43 | 0.718704E+09 | 1123.96 | 28-OCT-14:00 | 32.00 | 20.74 |
November | 0.747713E+10 | 28453.54 | 12-NOV-09:02 | 24.47 | 16.77 | 0.691541E+09 | 1123.97 | 04-NOV-14:09 | 24.47 | 16.77 |
December | 0.438063E+10 | 19552.30 | 12-DEC-08:62 | 23.17 | 17.37 | 0.718217E+09 | 1123.93 | 30-DEC-15:09 | 24.83 | 13.98 |
Annual Sum or Average | 0.102028E+12 | 0.855377E+10 | ||||||||
Minimum of Months | 0.307364E+10 | 5910.35 | 21.17 | 13.07 | 0.651936E+09 | 1123.87 | 21.17 | 13.98 | ||
Maximum of Months | 0.141024E+11 | 32469.64 | 36.17 | 23.08 | 0.741122E+09 | 1124.08 | 38.67 | 27.58 |
Report: ZoneHeatingSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 663802.00 | 1012.98 | 29-JAN-08:07 | 22.17 |
February | 2751544.18 | 1555.08 | 09-FEB-08:05 | 22.17 |
March | 13032712.54 | 3422.40 | 27-MAR-07:05 | 26.50 |
April | 31049941.25 | 4615.08 | 29-APR-07:04 | 27.25 |
May | 53524249.53 | 5260.10 | 11-MAY-07:04 | 30.33 |
June | 35424307.26 | 5807.64 | 11-JUN-07:04 | 31.92 |
July | 23384461.58 | 6749.63 | 19-JUL-07:06 | 33.75 |
August | 23896207.86 | 7488.27 | 05-AUG-07:05 | 35.67 |
September | 29545200.42 | 6166.78 | 02-SEP-07:04 | 32.25 |
October | 38959718.83 | 4072.27 | 06-OCT-07:04 | 27.43 |
November | 29786700.61 | 3411.02 | 25-NOV-08:04 | 25.33 |
December | 3581956.10 | 2388.93 | 12-DEC-08:04 | 23.17 |
Annual Sum or Average | 0.285601E+09 | |||
Minimum of Months | 663802.00 | 1012.98 | 22.17 | |
Maximum of Months | 53524249.53 | 7488.27 | 35.67 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 391226.36 | 651.87 | 29-JAN-08:07 | 22.17 |
February | 1395415.89 | 898.27 | 09-FEB-08:05 | 22.17 |
March | 6908689.42 | 2066.54 | 02-MAR-08:03 | 27.00 |
April | 16349406.04 | 2383.51 | 29-APR-07:04 | 27.25 |
May | 23566425.83 | 2557.94 | 11-MAY-07:04 | 30.33 |
June | 14175260.71 | 3552.57 | 05-JUN-07:04 | 34.50 |
July | 11780236.65 | 3469.34 | 19-JUL-07:04 | 33.75 |
August | 11109877.20 | 3975.02 | 05-AUG-07:04 | 35.67 |
September | 11621806.07 | 2910.94 | 04-SEP-07:04 | 31.55 |
October | 17172410.45 | 2059.50 | 06-OCT-07:04 | 27.43 |
November | 16066262.24 | 1817.63 | 25-NOV-08:04 | 25.33 |
December | 1947637.25 | 1312.70 | 12-DEC-08:04 | 23.17 |
Annual Sum or Average | 0.132485E+09 | |||
Minimum of Months | 391226.36 | 651.87 | 22.17 | |
Maximum of Months | 23566425.83 | 3975.02 | 35.67 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 1294865.73 | 633.16 | 29-JAN-08:07 | 22.17 |
February | 9975195.78 | 1928.06 | 05-FEB-17:12 | 31.00 |
March | 34223392.79 | 2188.27 | 27-MAR-19:12 | 31.67 |
April | 0.101190E+09 | 2598.94 | 29-APR-17:02 | 33.67 |
May | 0.222600E+09 | 4607.08 | 31-MAY-19:02 | 41.85 |
June | 0.234005E+09 | 3793.00 | 09-JUN-19:02 | 38.25 |
July | 0.263717E+09 | 4395.03 | 21-JUL-19:02 | 41.00 |
August | 0.272112E+09 | 4412.22 | 10-AUG-19:02 | 40.92 |
September | 0.207546E+09 | 4293.87 | 04-SEP-16:01 | 40.58 |
October | 0.173732E+09 | 3315.72 | 09-OCT-16:01 | 36.67 |
November | 76046160.72 | 2016.59 | 05-NOV-16:02 | 31.33 |
December | 10242696.79 | 1225.67 | 12-DEC-07:04 | 23.17 |
Annual Sum or Average | 0.160668E+10 | |||
Minimum of Months | 1294865.73 | 633.16 | 22.17 | |
Maximum of Months | 0.272112E+09 | 4607.08 | 41.85 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 1322883.67 | 615.58 | 29-JAN-08:07 | 22.17 |
February | 10057177.49 | 1930.08 | 05-FEB-17:12 | 31.00 |
March | 34355354.46 | 2189.09 | 27-MAR-19:12 | 31.67 |
April | 0.101064E+09 | 2598.50 | 29-APR-17:02 | 33.67 |
May | 0.220396E+09 | 4605.87 | 31-MAY-19:02 | 41.85 |
June | 0.232057E+09 | 3792.67 | 09-JUN-19:02 | 38.25 |
July | 0.262722E+09 | 4393.76 | 21-JUL-19:02 | 41.00 |
August | 0.270162E+09 | 4411.52 | 10-AUG-19:02 | 40.92 |
September | 0.206120E+09 | 4290.42 | 04-SEP-16:01 | 40.58 |
October | 0.173103E+09 | 3313.11 | 09-OCT-16:01 | 36.67 |
November | 75924399.59 | 2015.74 | 05-NOV-16:02 | 31.33 |
December | 10324617.74 | 1229.17 | 12-DEC-07:04 | 23.17 |
Annual Sum or Average | 0.159761E+10 | |||
Minimum of Months | 1322883.67 | 615.58 | 22.17 | |
Maximum of Months | 0.270162E+09 | 4605.87 | 41.85 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 1370490.61 | 541.24 | 29-JAN-08:07 | 22.17 |
February | 10466777.39 | 1933.57 | 05-FEB-17:12 | 31.00 |
March | 35177079.18 | 2192.77 | 27-MAR-19:12 | 31.67 |
April | 0.102613E+09 | 2605.35 | 29-APR-17:02 | 33.67 |
May | 0.222947E+09 | 4610.82 | 31-MAY-19:02 | 41.85 |
June | 0.234701E+09 | 3798.21 | 09-JUN-19:02 | 38.25 |
July | 0.264879E+09 | 4399.27 | 21-JUL-19:02 | 41.00 |
August | 0.273597E+09 | 4417.02 | 10-AUG-19:02 | 40.92 |
September | 0.207977E+09 | 4292.16 | 04-SEP-16:01 | 40.58 |
October | 0.174045E+09 | 3315.57 | 09-OCT-16:01 | 36.67 |
November | 77500273.45 | 2020.56 | 05-NOV-16:02 | 31.33 |
December | 10744901.91 | 1224.20 | 12-DEC-07:04 | 23.17 |
Annual Sum or Average | 0.161602E+10 | |||
Minimum of Months | 1370490.61 | 541.24 | 22.17 | |
Maximum of Months | 0.273597E+09 | 4610.82 | 41.85 |
Report: ZoneHeatingSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 2816003.04 | 1141.00 | 29-JAN-09:10 | 23.22 |
February | 16578573.68 | 3916.69 | 05-FEB-17:02 | 31.00 |
March | 32609445.77 | 4171.88 | 26-MAR-16:02 | 31.70 |
April | 0.115448E+09 | 5267.33 | 29-APR-17:02 | 33.67 |
May | 0.173413E+09 | 7125.35 | 21-MAY-16:01 | 37.42 |
June | 0.157761E+09 | 6930.57 | 04-JUN-16:01 | 36.83 |
July | 0.181413E+09 | 8458.67 | 29-JUL-17:01 | 40.00 |
August | 0.130792E+09 | 8870.03 | 05-AUG-17:01 | 40.83 |
September | 0.150947E+09 | 8640.73 | 04-SEP-16:01 | 40.58 |
October | 0.144479E+09 | 6680.23 | 09-OCT-16:01 | 36.67 |
November | 78328676.72 | 4094.48 | 05-NOV-16:02 | 31.33 |
December | 15336587.97 | 2065.54 | 12-DEC-08:04 | 23.17 |
Annual Sum or Average | 0.119992E+10 | |||
Minimum of Months | 2816003.04 | 1141.00 | 23.17 | |
Maximum of Months | 0.181413E+09 | 8870.03 | 40.83 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 1707294.80 | 605.94 | 29-JAN-09:10 | 23.22 |
February | 8947803.52 | 1969.92 | 05-FEB-17:02 | 31.00 |
March | 17435913.90 | 2093.38 | 26-MAR-16:02 | 31.70 |
April | 60111181.73 | 2655.06 | 29-APR-17:02 | 33.67 |
May | 85028743.41 | 3570.26 | 21-MAY-16:01 | 37.42 |
June | 77009971.29 | 3473.77 | 04-JUN-16:01 | 36.83 |
July | 93756247.19 | 4250.37 | 29-JUL-17:01 | 40.00 |
August | 66193486.78 | 4454.48 | 05-AUG-17:01 | 40.83 |
September | 75945589.92 | 4322.56 | 04-SEP-16:01 | 40.58 |
October | 72800116.79 | 3346.57 | 09-OCT-16:01 | 36.67 |
November | 41827250.21 | 2059.06 | 05-NOV-16:02 | 31.33 |
December | 8716369.86 | 1112.71 | 12-DEC-08:04 | 23.17 |
Annual Sum or Average | 0.609480E+09 | |||
Minimum of Months | 1707294.80 | 605.94 | 23.17 | |
Maximum of Months | 93756247.19 | 4454.48 | 40.83 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 1723684.00 | 592.17 | 29-JAN-09:10 | 23.22 |
February | 8947165.08 | 1971.60 | 05-FEB-17:02 | 31.00 |
March | 17425101.39 | 2094.79 | 26-MAR-16:02 | 31.70 |
April | 60064904.80 | 2656.27 | 29-APR-17:02 | 33.67 |
May | 85186743.93 | 3570.84 | 21-MAY-16:01 | 37.42 |
June | 77202485.44 | 3474.28 | 04-JUN-16:01 | 36.83 |
July | 94101652.90 | 4251.03 | 29-JUL-17:01 | 40.00 |
August | 66343753.27 | 4455.18 | 05-AUG-17:01 | 40.83 |
September | 76096342.96 | 4322.85 | 04-SEP-16:01 | 40.58 |
October | 72612551.34 | 3346.95 | 09-OCT-16:01 | 36.67 |
November | 41914496.97 | 2059.90 | 05-NOV-16:02 | 31.33 |
December | 8743101.20 | 1099.05 | 12-DEC-08:04 | 23.17 |
Annual Sum or Average | 0.610362E+09 | |||
Minimum of Months | 1723684.00 | 592.17 | 23.17 | |
Maximum of Months | 94101652.90 | 4455.18 | 40.83 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 1766928.49 | 547.44 | 29-JAN-09:10 | 23.22 |
February | 8972859.35 | 1975.13 | 05-FEB-17:02 | 31.00 |
March | 17447021.29 | 2096.00 | 26-MAR-16:02 | 31.70 |
April | 59604564.44 | 2654.70 | 29-APR-17:02 | 33.67 |
May | 85040150.34 | 3568.40 | 21-MAY-16:01 | 37.42 |
June | 76666448.15 | 3471.47 | 04-JUN-16:01 | 36.83 |
July | 91859927.36 | 4247.79 | 29-JUL-17:01 | 40.00 |
August | 65279369.65 | 4450.12 | 05-AUG-17:01 | 40.83 |
September | 74990993.45 | 4317.96 | 04-SEP-16:01 | 40.58 |
October | 71456931.44 | 3343.45 | 09-OCT-16:01 | 36.67 |
November | 41713052.55 | 2058.35 | 05-NOV-16:02 | 31.33 |
December | 8873294.23 | 1062.86 | 12-DEC-08:04 | 23.17 |
Annual Sum or Average | 0.603672E+09 | |||
Minimum of Months | 1766928.49 | 547.44 | 23.17 | |
Maximum of Months | 91859927.36 | 4450.12 | 40.83 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 2021175.08 | 522.15 | 29-JAN-17:25 | 24.50 |
February | 9593765.44 | 1982.59 | 05-FEB-17:12 | 31.00 |
March | 18529437.99 | 2399.42 | 02-MAR-08:03 | 27.00 |
April | 56957767.58 | 2577.85 | 29-APR-17:02 | 33.67 |
May | 73789412.42 | 3493.83 | 21-MAY-16:01 | 37.42 |
June | 64714990.33 | 3514.20 | 05-JUN-07:07 | 34.50 |
July | 72965606.16 | 4156.82 | 29-JUL-17:01 | 40.00 |
August | 48742776.86 | 4335.59 | 05-AUG-17:01 | 40.83 |
September | 62473093.63 | 4216.94 | 04-SEP-16:01 | 40.58 |
October | 61259180.06 | 3258.72 | 09-OCT-16:01 | 36.67 |
November | 41000369.05 | 2026.76 | 19-NOV-09:04 | 25.40 |
December | 9212923.74 | 1243.71 | 12-DEC-08:04 | 23.17 |
Annual Sum or Average | 0.521260E+09 | |||
Minimum of Months | 2021175.08 | 522.15 | 23.17 | |
Maximum of Months | 73789412.42 | 4335.59 | 40.83 |
Report: ZoneElectricSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.739462E+10 | 4621.63 | 01-JAN-10:09 | 0.222596E+10 | 1343.25 | 01-JAN-10:09 |
February | 0.668410E+10 | 4621.63 | 01-FEB-10:09 | 0.201408E+10 | 1343.25 | 01-FEB-10:09 |
March | 0.740180E+10 | 4621.63 | 01-MAR-10:09 | 0.223295E+10 | 1343.25 | 01-MAR-10:09 |
April | 0.716384E+10 | 4621.63 | 01-APR-09:09 | 0.215748E+10 | 1343.25 | 01-APR-09:09 |
May | 0.739462E+10 | 4621.63 | 01-MAY-09:09 | 0.222596E+10 | 1343.25 | 01-MAY-09:09 |
June | 0.716485E+10 | 4621.63 | 01-JUN-09:09 | 0.216232E+10 | 1343.25 | 01-JUN-09:09 |
July | 0.740069E+10 | 4621.63 | 01-JUL-09:09 | 0.222811E+10 | 1343.25 | 01-JUL-09:09 |
August | 0.739513E+10 | 4621.63 | 01-AUG-09:09 | 0.222838E+10 | 1343.25 | 01-AUG-09:09 |
September | 0.717041E+10 | 4621.63 | 01-SEP-09:09 | 0.216205E+10 | 1343.25 | 01-SEP-09:09 |
October | 0.739462E+10 | 4621.63 | 01-OCT-09:09 | 0.222596E+10 | 1343.25 | 01-OCT-09:09 |
November | 0.714323E+10 | 4621.63 | 01-NOV-09:09 | 0.215077E+10 | 1343.25 | 01-NOV-09:09 |
December | 0.740776E+10 | 4621.63 | 01-DEC-10:09 | 0.223509E+10 | 1343.25 | 01-DEC-10:09 |
Annual Sum or Average | 0.871157E+11 | 0.262491E+11 | ||||
Minimum of Months | 0.668410E+10 | 4621.63 | 0.201408E+10 | 1343.25 | ||
Maximum of Months | 0.740776E+10 | 4621.63 | 0.223509E+10 | 1343.25 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.451584E+10 | 2827.07 | 01-JAN-10:09 | 0.111298E+10 | 671.63 | 01-JAN-10:09 |
February | 0.408193E+10 | 2827.07 | 01-FEB-10:09 | 0.100704E+10 | 671.63 | 01-FEB-10:09 |
March | 0.452026E+10 | 2827.07 | 01-MAR-10:09 | 0.111647E+10 | 671.63 | 01-MAR-10:09 |
April | 0.437489E+10 | 2827.07 | 01-APR-09:09 | 0.107874E+10 | 671.63 | 01-APR-09:09 |
May | 0.451584E+10 | 2827.07 | 01-MAY-09:09 | 0.111298E+10 | 671.63 | 01-MAY-09:09 |
June | 0.437556E+10 | 2827.07 | 01-JUN-09:09 | 0.108116E+10 | 671.63 | 01-JUN-09:09 |
July | 0.451952E+10 | 2827.07 | 01-JUL-09:09 | 0.111405E+10 | 671.63 | 01-JUL-09:09 |
August | 0.451617E+10 | 2827.07 | 01-AUG-09:09 | 0.111419E+10 | 671.63 | 01-AUG-09:09 |
September | 0.437891E+10 | 2827.07 | 01-SEP-09:09 | 0.108102E+10 | 671.63 | 01-SEP-09:09 |
October | 0.451584E+10 | 2827.07 | 01-OCT-09:09 | 0.111298E+10 | 671.63 | 01-OCT-09:09 |
November | 0.436230E+10 | 2827.07 | 01-NOV-09:09 | 0.107538E+10 | 671.63 | 01-NOV-09:09 |
December | 0.452388E+10 | 2827.07 | 01-DEC-10:09 | 0.111755E+10 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.532009E+11 | 0.131245E+11 | ||||
Minimum of Months | 0.408193E+10 | 2827.07 | 0.100704E+10 | 671.63 | ||
Maximum of Months | 0.452388E+10 | 2827.07 | 0.111755E+10 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.317044E+10 | 2555.22 | 01-JAN-10:09 | 0.879849E+09 | 671.63 | 01-JAN-10:09 |
February | 0.287181E+10 | 2555.22 | 01-FEB-09:09 | 0.796766E+09 | 671.63 | 01-FEB-09:09 |
March | 0.324295E+10 | 2555.22 | 01-MAR-09:09 | 0.898128E+09 | 671.63 | 01-MAR-09:09 |
April | 0.307694E+10 | 2555.22 | 01-APR-08:09 | 0.853677E+09 | 671.63 | 01-APR-08:09 |
May | 0.320669E+10 | 2555.22 | 01-MAY-08:09 | 0.888989E+09 | 671.63 | 01-MAY-08:09 |
June | 0.313132E+10 | 2555.22 | 01-JUN-08:09 | 0.867387E+09 | 671.63 | 01-JUN-08:09 |
July | 0.315231E+10 | 2555.22 | 01-JUL-08:09 | 0.875279E+09 | 671.63 | 01-JUL-08:09 |
August | 0.324295E+10 | 2555.22 | 01-AUG-08:09 | 0.898128E+09 | 671.63 | 01-AUG-08:09 |
September | 0.307694E+10 | 2555.22 | 01-SEP-08:09 | 0.853677E+09 | 671.63 | 01-SEP-08:09 |
October | 0.317044E+10 | 2555.22 | 01-OCT-09:09 | 0.879849E+09 | 671.63 | 01-OCT-09:09 |
November | 0.307694E+10 | 2555.22 | 01-NOV-08:09 | 0.853679E+09 | 671.63 | 01-NOV-08:09 |
December | 0.315231E+10 | 2555.22 | 01-DEC-09:09 | 0.875279E+09 | 671.63 | 01-DEC-09:09 |
Annual Sum or Average | 0.375720E+11 | 0.104207E+11 | ||||
Minimum of Months | 0.287181E+10 | 2555.22 | 0.796766E+09 | 671.63 | ||
Maximum of Months | 0.324295E+10 | 2555.22 | 0.898128E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.317044E+10 | 2555.22 | 01-JAN-10:09 | 0.879849E+09 | 671.63 | 01-JAN-10:09 |
February | 0.287181E+10 | 2555.22 | 01-FEB-09:09 | 0.796766E+09 | 671.63 | 01-FEB-09:09 |
March | 0.324295E+10 | 2555.22 | 01-MAR-09:09 | 0.898128E+09 | 671.63 | 01-MAR-09:09 |
April | 0.307694E+10 | 2555.22 | 01-APR-08:09 | 0.853677E+09 | 671.63 | 01-APR-08:09 |
May | 0.320669E+10 | 2555.22 | 01-MAY-08:09 | 0.888989E+09 | 671.63 | 01-MAY-08:09 |
June | 0.313132E+10 | 2555.22 | 01-JUN-08:09 | 0.867387E+09 | 671.63 | 01-JUN-08:09 |
July | 0.315231E+10 | 2555.22 | 01-JUL-08:09 | 0.875279E+09 | 671.63 | 01-JUL-08:09 |
August | 0.324295E+10 | 2555.22 | 01-AUG-08:09 | 0.898128E+09 | 671.63 | 01-AUG-08:09 |
September | 0.307694E+10 | 2555.22 | 01-SEP-08:09 | 0.853677E+09 | 671.63 | 01-SEP-08:09 |
October | 0.317044E+10 | 2555.22 | 01-OCT-09:09 | 0.879849E+09 | 671.63 | 01-OCT-09:09 |
November | 0.307694E+10 | 2555.22 | 01-NOV-08:09 | 0.853679E+09 | 671.63 | 01-NOV-08:09 |
December | 0.315231E+10 | 2555.22 | 01-DEC-09:09 | 0.875279E+09 | 671.63 | 01-DEC-09:09 |
Annual Sum or Average | 0.375720E+11 | 0.104207E+11 | ||||
Minimum of Months | 0.287181E+10 | 2555.22 | 0.796766E+09 | 671.63 | ||
Maximum of Months | 0.324295E+10 | 2555.22 | 0.898128E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.317044E+10 | 2555.22 | 01-JAN-10:09 | 0.879849E+09 | 671.63 | 01-JAN-10:09 |
February | 0.287181E+10 | 2555.22 | 01-FEB-09:09 | 0.796766E+09 | 671.63 | 01-FEB-09:09 |
March | 0.324295E+10 | 2555.22 | 01-MAR-09:09 | 0.898128E+09 | 671.63 | 01-MAR-09:09 |
April | 0.307694E+10 | 2555.22 | 01-APR-08:09 | 0.853677E+09 | 671.63 | 01-APR-08:09 |
May | 0.320669E+10 | 2555.22 | 01-MAY-08:09 | 0.888989E+09 | 671.63 | 01-MAY-08:09 |
June | 0.313132E+10 | 2555.22 | 01-JUN-08:09 | 0.867387E+09 | 671.63 | 01-JUN-08:09 |
July | 0.315231E+10 | 2555.22 | 01-JUL-08:09 | 0.875279E+09 | 671.63 | 01-JUL-08:09 |
August | 0.324295E+10 | 2555.22 | 01-AUG-08:09 | 0.898128E+09 | 671.63 | 01-AUG-08:09 |
September | 0.307694E+10 | 2555.22 | 01-SEP-08:09 | 0.853677E+09 | 671.63 | 01-SEP-08:09 |
October | 0.317044E+10 | 2555.22 | 01-OCT-09:09 | 0.879849E+09 | 671.63 | 01-OCT-09:09 |
November | 0.307694E+10 | 2555.22 | 01-NOV-08:09 | 0.853679E+09 | 671.63 | 01-NOV-08:09 |
December | 0.315231E+10 | 2555.22 | 01-DEC-09:09 | 0.875279E+09 | 671.63 | 01-DEC-09:09 |
Annual Sum or Average | 0.375720E+11 | 0.104207E+11 | ||||
Minimum of Months | 0.287181E+10 | 2555.22 | 0.796766E+09 | 671.63 | ||
Maximum of Months | 0.324295E+10 | 2555.22 | 0.898128E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.313454E+10 | 2726.96 | 01-JAN-11:09 | 0.161799E+10 | 1343.25 | 01-JAN-11:09 |
February | 0.283982E+10 | 2726.96 | 01-FEB-10:09 | 0.146554E+10 | 1343.25 | 01-FEB-10:09 |
March | 0.321092E+10 | 2726.96 | 01-MAR-10:09 | 0.165455E+10 | 1343.25 | 01-MAR-10:09 |
April | 0.304266E+10 | 2726.96 | 01-APR-09:09 | 0.157022E+10 | 1343.25 | 01-APR-09:09 |
May | 0.317273E+10 | 2726.96 | 01-MAY-09:09 | 0.163627E+10 | 1343.25 | 01-MAY-09:09 |
June | 0.309995E+10 | 2726.96 | 01-JUN-09:09 | 0.159764E+10 | 1343.25 | 01-JUN-09:09 |
July | 0.311545E+10 | 2726.96 | 01-JUL-09:09 | 0.160885E+10 | 1343.25 | 01-JUL-09:09 |
August | 0.321092E+10 | 2726.96 | 01-AUG-09:09 | 0.165455E+10 | 1343.25 | 01-AUG-09:09 |
September | 0.304266E+10 | 2726.96 | 01-SEP-09:09 | 0.157022E+10 | 1343.25 | 01-SEP-09:09 |
October | 0.313454E+10 | 2726.96 | 01-OCT-10:09 | 0.161799E+10 | 1343.25 | 01-OCT-10:09 |
November | 0.304266E+10 | 2726.96 | 01-NOV-09:09 | 0.157022E+10 | 1343.25 | 01-NOV-09:09 |
December | 0.311545E+10 | 2726.96 | 01-DEC-10:09 | 0.160885E+10 | 1343.25 | 01-DEC-10:09 |
Annual Sum or Average | 0.371623E+11 | 0.191729E+11 | ||||
Minimum of Months | 0.283982E+10 | 2726.96 | 0.146554E+10 | 1343.25 | ||
Maximum of Months | 0.321092E+10 | 2726.96 | 0.165455E+10 | 1343.25 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.161274E+10 | 1404.46 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.146111E+10 | 1404.46 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.165211E+10 | 1404.46 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.156548E+10 | 1404.46 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.163243E+10 | 1404.46 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.159501E+10 | 1404.46 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.160290E+10 | 1404.46 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.165211E+10 | 1404.46 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.156548E+10 | 1404.46 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.161274E+10 | 1404.46 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.156548E+10 | 1404.46 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.160290E+10 | 1404.46 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.191205E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.146111E+10 | 1404.46 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.165211E+10 | 1404.46 | 0.827277E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.161274E+10 | 1404.46 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.146111E+10 | 1404.46 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.165211E+10 | 1404.46 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.156548E+10 | 1404.46 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.163243E+10 | 1404.46 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.159501E+10 | 1404.46 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.160290E+10 | 1404.46 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.165211E+10 | 1404.46 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.156548E+10 | 1404.46 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.161274E+10 | 1404.46 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.156548E+10 | 1404.46 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.160290E+10 | 1404.46 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.191205E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.146111E+10 | 1404.46 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.165211E+10 | 1404.46 | 0.827277E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.161274E+10 | 1404.46 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.146111E+10 | 1404.46 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.165211E+10 | 1404.46 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.156548E+10 | 1404.46 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.163243E+10 | 1404.46 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.159501E+10 | 1404.46 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.160290E+10 | 1404.46 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.165211E+10 | 1404.46 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.156548E+10 | 1404.46 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.161274E+10 | 1404.46 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.156548E+10 | 1404.46 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.160290E+10 | 1404.46 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.191205E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.146111E+10 | 1404.46 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.165211E+10 | 1404.46 | 0.827277E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.161274E+10 | 1404.46 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.146111E+10 | 1404.46 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.165211E+10 | 1404.46 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.156548E+10 | 1404.46 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.163243E+10 | 1404.46 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.159501E+10 | 1404.46 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.160290E+10 | 1404.46 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.165211E+10 | 1404.46 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.156548E+10 | 1404.46 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.161274E+10 | 1404.46 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.156548E+10 | 1404.46 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.160290E+10 | 1404.46 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.191205E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.146111E+10 | 1404.46 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.165211E+10 | 1404.46 | 0.827277E+09 | 671.63 |
Report: SpaceGainsMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.338624E+10 | 0.739462E+10 | 0.222596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 75449070.49 | 0.827533E+09 |
February | 0.305697E+10 | 0.668410E+10 | 0.201408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.402045E+09 | 0.594184E+09 |
March | 0.335708E+10 | 0.740180E+10 | 0.223295E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104759E+10 | 0.255981E+09 |
April | 0.327081E+10 | 0.716384E+10 | 0.215748E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.231288E+10 | 71561727.65 |
May | 0.336680E+10 | 0.739462E+10 | 0.222596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.410640E+10 | 8037964.21 |
June | 0.325380E+10 | 0.716485E+10 | 0.216232E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.451390E+10 | 1732887.56 |
July | 0.339353E+10 | 0.740069E+10 | 0.222811E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.525387E+10 | 0.00 |
August | 0.334857E+10 | 0.739513E+10 | 0.222838E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.529256E+10 | 0.00 |
September | 0.327932E+10 | 0.717041E+10 | 0.216205E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.431226E+10 | 1760380.93 |
October | 0.338624E+10 | 0.739462E+10 | 0.222596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.336310E+10 | 15784037.74 |
November | 0.327446E+10 | 0.714323E+10 | 0.215077E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.177453E+10 | 75130251.35 |
December | 0.340325E+10 | 0.740776E+10 | 0.223509E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.396522E+09 | 0.440701E+09 |
Annual Sum or Average | 0.397770E+11 | 0.871157E+11 | 0.262491E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.328511E+11 | 0.229241E+10 |
Minimum of Months | 0.305697E+10 | 0.668410E+10 | 0.201408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 75449070.49 | 0.00 |
Maximum of Months | 0.340325E+10 | 0.740776E+10 | 0.223509E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.529256E+10 | 0.827533E+09 |
Report: SpaceGainsMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.169307E+10 | 0.451584E+10 | 0.111298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42463337.85 | 0.419071E+09 |
February | 0.152844E+10 | 0.408193E+10 | 0.100704E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.225294E+09 | 0.289174E+09 |
March | 0.167849E+10 | 0.452026E+10 | 0.111647E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.583290E+09 | 0.118443E+09 |
April | 0.163536E+10 | 0.437489E+10 | 0.107874E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129003E+10 | 25134245.14 |
May | 0.168335E+10 | 0.451584E+10 | 0.111298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.227691E+10 | 2612462.40 |
June | 0.162685E+10 | 0.437556E+10 | 0.108116E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.248429E+10 | 571248.86 |
July | 0.169671E+10 | 0.451952E+10 | 0.111405E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.287984E+10 | 0.00 |
August | 0.167424E+10 | 0.451617E+10 | 0.111419E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.290001E+10 | 0.00 |
September | 0.163961E+10 | 0.437891E+10 | 0.108102E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.238172E+10 | 461932.67 |
October | 0.169307E+10 | 0.451584E+10 | 0.111298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187390E+10 | 4568357.51 |
November | 0.163718E+10 | 0.436230E+10 | 0.107538E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.992752E+09 | 24308065.57 |
December | 0.170157E+10 | 0.452388E+10 | 0.111755E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.223074E+09 | 0.209427E+09 |
Annual Sum or Average | 0.198880E+11 | 0.532009E+11 | 0.131245E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181536E+11 | 0.109377E+10 |
Minimum of Months | 0.152844E+10 | 0.408193E+10 | 0.100704E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42463337.85 | 0.00 |
Maximum of Months | 0.170157E+10 | 0.452388E+10 | 0.111755E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.290001E+10 | 0.419071E+09 |
Report: SpaceGainsMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.317044E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 41992715.99 | 0.441372E+09 |
February | 0.914877E+09 | 0.287181E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.221185E+09 | 0.310492E+09 |
March | 0.103395E+10 | 0.324295E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.576175E+09 | 0.131069E+09 |
April | 0.984131E+09 | 0.307694E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126677E+10 | 27726825.18 |
May | 0.102058E+10 | 0.320669E+10 | 0.888989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.225397E+10 | 2800274.27 |
June | 0.998711E+09 | 0.313132E+10 | 0.867387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.246556E+10 | 603777.67 |
July | 0.100600E+10 | 0.315231E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.285450E+10 | 0.00 |
August | 0.103395E+10 | 0.324295E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.288392E+10 | 0.00 |
September | 0.984131E+09 | 0.307694E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235647E+10 | 567414.31 |
October | 0.100722E+10 | 0.317044E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.184354E+10 | 4896850.22 |
November | 0.973196E+09 | 0.307694E+10 | 0.853679E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.970862E+09 | 29137862.00 |
December | 0.100600E+10 | 0.315231E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.218610E+09 | 0.230370E+09 |
Annual Sum or Average | 0.119700E+11 | 0.375720E+11 | 0.104207E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179536E+11 | 0.117904E+10 |
Minimum of Months | 0.914877E+09 | 0.287181E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 41992715.99 | 0.00 |
Maximum of Months | 0.103395E+10 | 0.324295E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.288392E+10 | 0.441372E+09 |
Report: SpaceGainsMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.317044E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 41993704.51 | 0.440201E+09 |
February | 0.914877E+09 | 0.287181E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.221180E+09 | 0.309863E+09 |
March | 0.103395E+10 | 0.324295E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.576136E+09 | 0.130819E+09 |
April | 0.984131E+09 | 0.307694E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126654E+10 | 27899140.23 |
May | 0.102058E+10 | 0.320669E+10 | 0.888989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.225293E+10 | 2960360.67 |
June | 0.998711E+09 | 0.313132E+10 | 0.867387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.246404E+10 | 655473.46 |
July | 0.100600E+10 | 0.315231E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.285227E+10 | 0.00 |
August | 0.103395E+10 | 0.324295E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.288201E+10 | 0.00 |
September | 0.984131E+09 | 0.307694E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235486E+10 | 627592.06 |
October | 0.100722E+10 | 0.317044E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.184258E+10 | 5219240.22 |
November | 0.973196E+09 | 0.307694E+10 | 0.853679E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.970689E+09 | 29445222.14 |
December | 0.100600E+10 | 0.315231E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.218615E+09 | 0.230004E+09 |
Annual Sum or Average | 0.119700E+11 | 0.375720E+11 | 0.104207E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179438E+11 | 0.117769E+10 |
Minimum of Months | 0.914877E+09 | 0.287181E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 41993704.51 | 0.00 |
Maximum of Months | 0.103395E+10 | 0.324295E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.288201E+10 | 0.440201E+09 |
Report: SpaceGainsMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.317044E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 41995766.67 | 0.437456E+09 |
February | 0.914877E+09 | 0.287181E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.221254E+09 | 0.307593E+09 |
March | 0.103395E+10 | 0.324295E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.576409E+09 | 0.129110E+09 |
April | 0.984131E+09 | 0.307694E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126713E+10 | 26959398.34 |
May | 0.102058E+10 | 0.320669E+10 | 0.888989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.225389E+10 | 2731349.58 |
June | 0.998711E+09 | 0.313132E+10 | 0.867387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.246538E+10 | 573976.61 |
July | 0.100600E+10 | 0.315231E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.285365E+10 | 0.00 |
August | 0.103395E+10 | 0.324295E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.288330E+10 | 0.00 |
September | 0.984131E+09 | 0.307694E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235605E+10 | 558300.22 |
October | 0.100722E+10 | 0.317044E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.184354E+10 | 4831857.13 |
November | 0.973196E+09 | 0.307694E+10 | 0.853679E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.971159E+09 | 28404056.21 |
December | 0.100600E+10 | 0.315231E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.218645E+09 | 0.228030E+09 |
Annual Sum or Average | 0.119700E+11 | 0.375720E+11 | 0.104207E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179524E+11 | 0.116625E+10 |
Minimum of Months | 0.914877E+09 | 0.287181E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 41995766.67 | 0.00 |
Maximum of Months | 0.103395E+10 | 0.324295E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.288330E+10 | 0.437456E+09 |
Report: SpaceGainsMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.344359E+10 | 0.313454E+10 | 0.161799E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 73653791.48 | 0.778581E+09 |
February | 0.313522E+10 | 0.283982E+10 | 0.146554E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.388617E+09 | 0.551738E+09 |
March | 0.355148E+10 | 0.321092E+10 | 0.165455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101434E+10 | 0.232573E+09 |
April | 0.338259E+10 | 0.304266E+10 | 0.157022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222938E+10 | 52593607.71 |
May | 0.349753E+10 | 0.317273E+10 | 0.163627E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.396732E+10 | 5401073.38 |
June | 0.343071E+10 | 0.309995E+10 | 0.159764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.434934E+10 | 1336194.65 |
July | 0.344942E+10 | 0.311545E+10 | 0.160885E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.503684E+10 | 0.00 |
August | 0.355148E+10 | 0.321092E+10 | 0.165455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.509132E+10 | 0.00 |
September | 0.338259E+10 | 0.304266E+10 | 0.157022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.415053E+10 | 1231666.68 |
October | 0.344359E+10 | 0.313454E+10 | 0.161799E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.324243E+10 | 11190937.87 |
November | 0.331698E+10 | 0.304266E+10 | 0.157022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.170812E+10 | 56875565.61 |
December | 0.344942E+10 | 0.311545E+10 | 0.160885E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.383646E+09 | 0.411784E+09 |
Annual Sum or Average | 0.410346E+11 | 0.371623E+11 | 0.191729E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.316356E+11 | 0.210330E+10 |
Minimum of Months | 0.313522E+10 | 0.283982E+10 | 0.146554E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 73653791.48 | 0.00 |
Maximum of Months | 0.355148E+10 | 0.321092E+10 | 0.165455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.509132E+10 | 0.778581E+09 |
Report: SpaceGainsMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.161274E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 42004877.27 | 0.434324E+09 |
February | 0.156756E+10 | 0.146111E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.221541E+09 | 0.304737E+09 |
March | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.577693E+09 | 0.126996E+09 |
April | 0.169125E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127019E+10 | 26949535.01 |
May | 0.174872E+10 | 0.163243E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.225741E+10 | 2650577.19 |
June | 0.171530E+10 | 0.159501E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.247197E+10 | 653357.75 |
July | 0.172466E+10 | 0.160290E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.286019E+10 | 0.00 |
August | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.289111E+10 | 0.00 |
September | 0.169125E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.236035E+10 | 575091.06 |
October | 0.172174E+10 | 0.161274E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.184674E+10 | 5428152.59 |
November | 0.165844E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.973634E+09 | 28735455.25 |
December | 0.172466E+10 | 0.160290E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.218798E+09 | 0.226705E+09 |
Annual Sum or Average | 0.205167E+11 | 0.191205E+11 | 0.958644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179916E+11 | 0.115775E+10 |
Minimum of Months | 0.156756E+10 | 0.146111E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 42004877.27 | 0.00 |
Maximum of Months | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.289111E+10 | 0.434324E+09 |
Report: SpaceGainsMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.161274E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 42005696.31 | 0.433481E+09 |
February | 0.156756E+10 | 0.146111E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.221562E+09 | 0.304015E+09 |
March | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.577750E+09 | 0.126541E+09 |
April | 0.169125E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127032E+10 | 26778285.00 |
May | 0.174872E+10 | 0.163243E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.225757E+10 | 2626451.14 |
June | 0.171530E+10 | 0.159501E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.247216E+10 | 646118.79 |
July | 0.172466E+10 | 0.160290E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.286035E+10 | 0.00 |
August | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.289124E+10 | 0.00 |
September | 0.169125E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.236049E+10 | 568740.03 |
October | 0.172174E+10 | 0.161274E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.184692E+10 | 5382781.00 |
November | 0.165844E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.973745E+09 | 28572194.63 |
December | 0.172466E+10 | 0.160290E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.218807E+09 | 0.226208E+09 |
Annual Sum or Average | 0.205167E+11 | 0.191205E+11 | 0.958644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179929E+11 | 0.115482E+10 |
Minimum of Months | 0.156756E+10 | 0.146111E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 42005696.31 | 0.00 |
Maximum of Months | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.289124E+10 | 0.433481E+09 |
Report: SpaceGainsMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.161274E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 42006835.24 | 0.430703E+09 |
February | 0.156756E+10 | 0.146111E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.221586E+09 | 0.301553E+09 |
March | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.577841E+09 | 0.125034E+09 |
April | 0.169125E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127033E+10 | 26319984.60 |
May | 0.174872E+10 | 0.163243E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.225719E+10 | 2601201.57 |
June | 0.171530E+10 | 0.159501E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.247152E+10 | 648550.04 |
July | 0.172466E+10 | 0.160290E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.285902E+10 | 0.00 |
August | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.288994E+10 | 0.00 |
September | 0.169125E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235954E+10 | 593121.40 |
October | 0.172174E+10 | 0.161274E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.184643E+10 | 5457663.19 |
November | 0.165844E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.973707E+09 | 28359903.55 |
December | 0.172466E+10 | 0.160290E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.218816E+09 | 0.224758E+09 |
Annual Sum or Average | 0.205167E+11 | 0.191205E+11 | 0.958644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179879E+11 | 0.114603E+10 |
Minimum of Months | 0.156756E+10 | 0.146111E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 42006835.24 | 0.00 |
Maximum of Months | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.288994E+10 | 0.430703E+09 |
Report: SpaceGainsMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.161274E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 42985322.20 | 0.527039E+09 |
February | 0.156756E+10 | 0.146111E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.227844E+09 | 0.391978E+09 |
March | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.600893E+09 | 0.172866E+09 |
April | 0.169125E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131552E+10 | 51571077.18 |
May | 0.174872E+10 | 0.163243E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.236614E+10 | 6435116.03 |
June | 0.171530E+10 | 0.159501E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.261956E+10 | 1619080.08 |
July | 0.172466E+10 | 0.160290E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.305067E+10 | 0.00 |
August | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.308519E+10 | 0.00 |
September | 0.169125E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.248360E+10 | 2082309.08 |
October | 0.172174E+10 | 0.161274E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.191553E+10 | 15835058.96 |
November | 0.165844E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100338E+10 | 63441274.67 |
December | 0.172466E+10 | 0.160290E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.223787E+09 | 0.303495E+09 |
Annual Sum or Average | 0.205167E+11 | 0.191205E+11 | 0.958644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189351E+11 | 0.153636E+10 |
Minimum of Months | 0.156756E+10 | 0.146111E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 42985322.20 | 0.00 |
Maximum of Months | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.308519E+10 | 0.527039E+09 |
Report: PeakSpaceGainsMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 4050.04 | 01-JAN-13:09 | 4621.63 | 01-JAN-10:09 | 1343.25 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1938.27 | 23-JAN-14:00 | 2423.02 | 18-JAN-17:00 |
February | 4050.04 | 03-FEB-13:09 | 4621.63 | 01-FEB-10:09 | 1343.25 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4040.61 | 06-FEB-15:00 | 2980.52 | 20-FEB-16:00 |
March | 4050.04 | 03-MAR-13:09 | 4621.63 | 01-MAR-10:09 | 1343.25 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6493.18 | 27-MAR-11:10 | 2863.31 | 05-MAR-18:00 |
April | 4050.04 | 01-APR-12:09 | 4621.63 | 01-APR-09:09 | 1343.25 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8034.01 | 28-APR-12:00 | 458.74 | 01-APR-07:05 |
May | 4050.04 | 05-MAY-12:09 | 4621.63 | 01-MAY-09:09 | 1343.25 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7779.74 | 09-MAY-13:00 | 217.28 | 01-MAY-07:02 |
June | 4050.04 | 02-JUN-12:09 | 4621.63 | 01-JUN-09:09 | 1343.25 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8427.20 | 12-JUN-12:00 | 206.26 | 22-JUN-08:00 |
July | 4050.04 | 01-JUL-12:09 | 4621.63 | 01-JUL-09:09 | 1343.25 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 9608.28 | 21-JUL-12:00 | 0.00 | 01-JUL-00:03 |
August | 4050.04 | 04-AUG-12:09 | 4621.63 | 01-AUG-09:09 | 1343.25 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 9880.30 | 16-AUG-12:00 | 0.00 | 01-AUG-00:10 |
September | 4050.04 | 01-SEP-12:09 | 4621.63 | 01-SEP-09:09 | 1343.25 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7772.87 | 26-SEP-13:00 | 78.95 | 25-SEP-05:00 |
October | 4050.04 | 01-OCT-12:09 | 4621.63 | 01-OCT-09:09 | 1343.25 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6298.26 | 09-OCT-12:00 | 236.98 | 29-OCT-07:02 |
November | 4050.04 | 03-NOV-12:09 | 4621.63 | 01-NOV-09:09 | 1343.25 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4618.19 | 05-NOV-12:00 | 432.99 | 22-NOV-08:63 |
December | 4050.04 | 01-DEC-13:09 | 4621.63 | 01-DEC-10:09 | 1343.25 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2845.57 | 10-DEC-12:10 | 2919.28 | 15-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 4050.04 | 4621.63 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 1938.27 | 0.00 | |||||
Maximum of Months | 4050.04 | 4621.63 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 9880.30 | 2980.52 |
Report: PeakSpaceGainsMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 01-JAN-13:09 | 2827.07 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1091.83 | 23-JAN-14:00 | 1358.14 | 18-JAN-17:00 |
February | 2024.96 | 03-FEB-13:09 | 2827.07 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2264.83 | 06-FEB-15:00 | 1684.17 | 20-FEB-16:00 |
March | 2024.96 | 03-MAR-13:09 | 2827.07 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3623.86 | 27-MAR-11:10 | 1615.40 | 05-MAR-18:00 |
April | 2024.96 | 01-APR-12:09 | 2827.07 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4553.99 | 28-APR-12:00 | 255.89 | 01-APR-07:05 |
May | 2024.96 | 05-MAY-12:09 | 2827.07 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4367.33 | 09-MAY-13:00 | 117.47 | 01-MAY-07:02 |
June | 2024.96 | 02-JUN-12:09 | 2827.07 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4761.86 | 12-JUN-12:00 | 114.16 | 22-JUN-08:00 |
July | 2024.96 | 01-JUL-12:09 | 2827.07 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5429.23 | 21-JUL-12:00 | 0.00 | 01-JUL-00:03 |
August | 2024.96 | 04-AUG-12:09 | 2827.07 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5521.19 | 16-AUG-12:00 | 0.00 | 01-AUG-00:10 |
September | 2024.96 | 01-SEP-12:09 | 2827.07 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4385.19 | 26-SEP-13:00 | 22.70 | 25-SEP-05:00 |
October | 2024.96 | 01-OCT-12:09 | 2827.07 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3582.70 | 09-OCT-12:00 | 128.50 | 29-OCT-07:02 |
November | 2024.96 | 03-NOV-12:09 | 2827.07 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2621.98 | 05-NOV-12:00 | 235.62 | 22-NOV-08:63 |
December | 2024.96 | 01-DEC-13:09 | 2827.07 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1605.14 | 10-DEC-12:10 | 1622.74 | 15-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 2827.07 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1091.83 | 0.00 | |||||
Maximum of Months | 2024.96 | 2827.07 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 5521.19 | 1684.17 |
Report: PeakSpaceGainsMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 2555.22 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1091.83 | 23-JAN-14:00 | 1358.13 | 18-JAN-17:00 |
February | 2024.96 | 04-FEB-13:09 | 2555.22 | 01-FEB-09:09 | 671.63 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2264.84 | 06-FEB-15:00 | 1684.17 | 20-FEB-16:00 |
March | 2024.96 | 04-MAR-13:09 | 2555.22 | 01-MAR-09:09 | 671.63 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3623.86 | 27-MAR-11:10 | 1613.59 | 05-MAR-18:00 |
April | 2024.96 | 01-APR-12:09 | 2555.22 | 01-APR-08:09 | 671.63 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4553.98 | 28-APR-12:00 | 249.17 | 01-APR-07:10 |
May | 2024.96 | 06-MAY-12:09 | 2555.22 | 01-MAY-08:09 | 671.63 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4367.33 | 09-MAY-13:00 | 111.48 | 01-MAY-07:08 |
June | 2024.96 | 03-JUN-12:09 | 2555.22 | 01-JUN-08:09 | 671.63 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4761.86 | 12-JUN-12:00 | 114.16 | 22-JUN-08:00 |
July | 2024.96 | 01-JUL-12:09 | 2555.22 | 01-JUL-08:09 | 671.63 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5429.23 | 21-JUL-12:00 | 0.00 | 01-JUL-00:03 |
August | 2024.96 | 05-AUG-12:09 | 2555.22 | 01-AUG-08:09 | 671.63 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5521.19 | 16-AUG-12:00 | 0.00 | 01-AUG-00:10 |
September | 2024.96 | 02-SEP-12:09 | 2555.22 | 01-SEP-08:09 | 671.63 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4385.17 | 26-SEP-13:00 | 33.25 | 24-SEP-07:01 |
October | 2024.96 | 07-OCT-12:09 | 2555.22 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3582.71 | 09-OCT-12:00 | 146.12 | 29-OCT-07:02 |
November | 2024.96 | 04-NOV-12:09 | 2555.22 | 01-NOV-08:09 | 671.63 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2621.98 | 05-NOV-12:00 | 231.34 | 22-NOV-08:10 |
December | 2024.96 | 02-DEC-13:09 | 2555.22 | 01-DEC-09:09 | 671.63 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1605.14 | 10-DEC-12:10 | 1622.74 | 15-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 2555.22 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1091.83 | 0.00 | |||||
Maximum of Months | 2024.96 | 2555.22 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 5521.19 | 1684.17 |
Report: PeakSpaceGainsMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 2555.22 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1091.82 | 23-JAN-14:00 | 1358.13 | 18-JAN-17:00 |
February | 2024.96 | 04-FEB-13:09 | 2555.22 | 01-FEB-09:09 | 671.63 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2264.84 | 06-FEB-15:00 | 1684.17 | 20-FEB-16:00 |
March | 2024.96 | 04-MAR-13:09 | 2555.22 | 01-MAR-09:09 | 671.63 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3623.86 | 27-MAR-11:10 | 1605.62 | 05-MAR-18:00 |
April | 2024.96 | 01-APR-12:09 | 2555.22 | 01-APR-08:09 | 671.63 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4553.98 | 28-APR-12:00 | 248.94 | 01-APR-07:10 |
May | 2024.96 | 06-MAY-12:09 | 2555.22 | 01-MAY-08:09 | 671.63 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4367.32 | 09-MAY-13:00 | 111.48 | 01-MAY-07:08 |
June | 2024.96 | 03-JUN-12:09 | 2555.22 | 01-JUN-08:09 | 671.63 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4761.86 | 12-JUN-12:00 | 114.16 | 22-JUN-08:00 |
July | 2024.96 | 01-JUL-12:09 | 2555.22 | 01-JUL-08:09 | 671.63 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5429.22 | 21-JUL-12:00 | 0.00 | 01-JUL-00:03 |
August | 2024.96 | 05-AUG-12:09 | 2555.22 | 01-AUG-08:09 | 671.63 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5521.19 | 16-AUG-12:00 | 0.00 | 01-AUG-00:10 |
September | 2024.96 | 02-SEP-12:09 | 2555.22 | 01-SEP-08:09 | 671.63 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4385.16 | 26-SEP-13:00 | 36.54 | 24-SEP-07:01 |
October | 2024.96 | 07-OCT-12:09 | 2555.22 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3582.71 | 09-OCT-12:00 | 148.34 | 29-OCT-07:02 |
November | 2024.96 | 04-NOV-12:09 | 2555.22 | 01-NOV-08:09 | 671.63 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2621.98 | 05-NOV-12:00 | 231.34 | 22-NOV-08:10 |
December | 2024.96 | 02-DEC-13:09 | 2555.22 | 01-DEC-09:09 | 671.63 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1605.14 | 10-DEC-12:10 | 1622.74 | 15-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 2555.22 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1091.82 | 0.00 | |||||
Maximum of Months | 2024.96 | 2555.22 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 5521.19 | 1684.17 |
Report: PeakSpaceGainsMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 2555.22 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1091.82 | 23-JAN-14:00 | 1358.13 | 18-JAN-17:00 |
February | 2024.96 | 04-FEB-13:09 | 2555.22 | 01-FEB-09:09 | 671.63 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2264.84 | 06-FEB-15:00 | 1684.17 | 20-FEB-16:00 |
March | 2024.96 | 04-MAR-13:09 | 2555.22 | 01-MAR-09:09 | 671.63 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3623.86 | 27-MAR-11:10 | 1586.60 | 05-MAR-18:00 |
April | 2024.96 | 01-APR-12:09 | 2555.22 | 01-APR-08:09 | 671.63 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4553.99 | 28-APR-12:00 | 246.13 | 01-APR-07:05 |
May | 2024.96 | 06-MAY-12:09 | 2555.22 | 01-MAY-08:09 | 671.63 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4367.33 | 09-MAY-13:00 | 111.48 | 01-MAY-07:08 |
June | 2024.96 | 03-JUN-12:09 | 2555.22 | 01-JUN-08:09 | 671.63 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4761.86 | 12-JUN-12:00 | 114.16 | 22-JUN-08:00 |
July | 2024.96 | 01-JUL-12:09 | 2555.22 | 01-JUL-08:09 | 671.63 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5429.23 | 21-JUL-12:00 | 0.00 | 01-JUL-00:03 |
August | 2024.96 | 05-AUG-12:09 | 2555.22 | 01-AUG-08:09 | 671.63 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5521.19 | 16-AUG-12:00 | 0.00 | 01-AUG-00:10 |
September | 2024.96 | 02-SEP-12:09 | 2555.22 | 01-SEP-08:09 | 671.63 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4385.17 | 26-SEP-13:00 | 33.21 | 24-SEP-07:01 |
October | 2024.96 | 07-OCT-12:09 | 2555.22 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3582.71 | 09-OCT-12:00 | 145.03 | 29-OCT-07:02 |
November | 2024.96 | 04-NOV-12:09 | 2555.22 | 01-NOV-08:09 | 671.63 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2621.98 | 05-NOV-12:00 | 231.34 | 22-NOV-08:63 |
December | 2024.96 | 02-DEC-13:09 | 2555.22 | 01-DEC-09:09 | 671.63 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1605.14 | 10-DEC-12:10 | 1622.74 | 15-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 2555.22 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1091.82 | 0.00 | |||||
Maximum of Months | 2024.96 | 2555.22 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 5521.19 | 1684.17 |
Report: PeakSpaceGainsMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 5400.05 | 07-JAN-15:09 | 2726.96 | 01-JAN-11:09 | 1343.25 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1914.12 | 23-JAN-14:00 | 2382.76 | 18-JAN-17:00 |
February | 5400.05 | 04-FEB-15:09 | 2726.96 | 01-FEB-10:09 | 1343.25 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3973.46 | 06-FEB-15:00 | 2951.28 | 20-FEB-16:00 |
March | 5400.05 | 04-MAR-15:09 | 2726.96 | 01-MAR-10:09 | 1343.25 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6361.78 | 27-MAR-11:10 | 2660.11 | 05-MAR-18:00 |
April | 5400.05 | 01-APR-14:09 | 2726.96 | 01-APR-09:09 | 1343.25 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7976.58 | 28-APR-12:00 | 446.49 | 01-APR-07:05 |
May | 5400.05 | 06-MAY-14:09 | 2726.96 | 01-MAY-09:09 | 1343.25 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7660.33 | 09-MAY-13:00 | 265.95 | 01-MAY-07:02 |
June | 5400.05 | 03-JUN-14:09 | 2726.96 | 01-JUN-09:09 | 1343.25 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8344.54 | 12-JUN-12:00 | 200.65 | 22-JUN-08:00 |
July | 5400.05 | 01-JUL-14:09 | 2726.96 | 01-JUL-09:09 | 1343.25 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 9514.02 | 21-JUL-12:00 | 0.00 | 01-JUL-00:03 |
August | 5400.05 | 05-AUG-14:09 | 2726.96 | 01-AUG-09:09 | 1343.25 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 9690.80 | 16-AUG-12:00 | 0.00 | 01-AUG-00:10 |
September | 5400.05 | 02-SEP-14:09 | 2726.96 | 01-SEP-09:09 | 1343.25 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7686.88 | 26-SEP-13:00 | 103.59 | 24-SEP-07:01 |
October | 5400.05 | 07-OCT-14:09 | 2726.96 | 01-OCT-10:09 | 1343.25 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6272.21 | 09-OCT-12:00 | 346.87 | 29-OCT-07:02 |
November | 5400.05 | 04-NOV-14:09 | 2726.96 | 01-NOV-09:09 | 1343.25 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4591.53 | 05-NOV-12:00 | 465.57 | 26-NOV-08:62 |
December | 5400.05 | 02-DEC-15:09 | 2726.96 | 01-DEC-10:09 | 1343.25 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2813.51 | 10-DEC-12:10 | 2850.51 | 15-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 5400.05 | 2726.96 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 1914.12 | 0.00 | |||||
Maximum of Months | 5400.05 | 2726.96 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 9690.80 | 2951.28 |
Report: PeakSpaceGainsMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1404.46 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1091.81 | 23-JAN-14:00 | 1358.14 | 18-JAN-17:00 |
February | 2699.95 | 04-FEB-15:09 | 1404.46 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2264.83 | 06-FEB-15:00 | 1684.17 | 20-FEB-16:00 |
March | 2699.95 | 04-MAR-15:09 | 1404.46 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3623.86 | 27-MAR-11:10 | 1513.56 | 05-MAR-18:00 |
April | 2699.95 | 01-APR-14:09 | 1404.46 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4553.96 | 28-APR-12:00 | 253.89 | 01-APR-07:05 |
May | 2699.95 | 06-MAY-14:09 | 1404.46 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4367.27 | 09-MAY-13:00 | 148.65 | 01-MAY-07:02 |
June | 2699.95 | 03-JUN-14:09 | 1404.46 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4761.86 | 12-JUN-12:00 | 114.16 | 22-JUN-08:00 |
July | 2699.95 | 01-JUL-14:09 | 1404.46 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5429.22 | 21-JUL-12:00 | 0.00 | 01-JUL-00:03 |
August | 2699.95 | 05-AUG-14:09 | 1404.46 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5521.19 | 16-AUG-12:00 | 0.00 | 01-AUG-00:10 |
September | 2699.95 | 02-SEP-14:09 | 1404.46 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4385.57 | 26-SEP-13:00 | 56.79 | 24-SEP-07:01 |
October | 2699.95 | 07-OCT-14:09 | 1404.46 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3582.72 | 09-OCT-12:00 | 193.90 | 29-OCT-07:02 |
November | 2699.95 | 04-NOV-14:09 | 1404.46 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2621.98 | 05-NOV-12:00 | 258.17 | 26-NOV-08:62 |
December | 2699.95 | 02-DEC-15:09 | 1404.46 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1605.14 | 10-DEC-12:10 | 1622.76 | 15-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1091.81 | 0.00 | |||||
Maximum of Months | 2699.95 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 5521.19 | 1684.17 |
Report: PeakSpaceGainsMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1404.46 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1091.81 | 23-JAN-14:00 | 1358.14 | 18-JAN-17:00 |
February | 2699.95 | 04-FEB-15:09 | 1404.46 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2264.83 | 06-FEB-15:00 | 1684.17 | 20-FEB-16:00 |
March | 2699.95 | 04-MAR-15:09 | 1404.46 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3623.86 | 27-MAR-11:10 | 1508.17 | 05-MAR-18:00 |
April | 2699.95 | 01-APR-14:09 | 1404.46 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4553.96 | 28-APR-12:00 | 253.72 | 01-APR-07:05 |
May | 2699.95 | 06-MAY-14:09 | 1404.46 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4367.27 | 09-MAY-13:00 | 148.26 | 01-MAY-07:02 |
June | 2699.95 | 03-JUN-14:09 | 1404.46 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4761.86 | 12-JUN-12:00 | 114.16 | 22-JUN-08:00 |
July | 2699.95 | 01-JUL-14:09 | 1404.46 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5429.22 | 21-JUL-12:00 | 0.00 | 01-JUL-00:03 |
August | 2699.95 | 05-AUG-14:09 | 1404.46 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5521.19 | 16-AUG-12:00 | 0.00 | 01-AUG-00:10 |
September | 2699.95 | 02-SEP-14:09 | 1404.46 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4385.57 | 26-SEP-13:00 | 56.51 | 24-SEP-07:01 |
October | 2699.95 | 07-OCT-14:09 | 1404.46 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3582.72 | 09-OCT-12:00 | 193.36 | 29-OCT-07:02 |
November | 2699.95 | 04-NOV-14:09 | 1404.46 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2621.98 | 05-NOV-12:00 | 257.30 | 26-NOV-08:62 |
December | 2699.95 | 02-DEC-15:09 | 1404.46 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1605.14 | 10-DEC-12:10 | 1622.75 | 15-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1091.81 | 0.00 | |||||
Maximum of Months | 2699.95 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 5521.19 | 1684.17 |
Report: PeakSpaceGainsMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1404.46 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1091.80 | 23-JAN-14:00 | 1358.14 | 18-JAN-17:00 |
February | 2699.95 | 04-FEB-15:09 | 1404.46 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2264.82 | 06-FEB-15:00 | 1684.22 | 20-FEB-16:00 |
March | 2699.95 | 04-MAR-15:09 | 1404.46 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3623.86 | 27-MAR-11:10 | 1495.97 | 05-MAR-18:00 |
April | 2699.95 | 01-APR-14:09 | 1404.46 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4553.96 | 28-APR-12:00 | 253.15 | 01-APR-07:05 |
May | 2699.95 | 06-MAY-14:09 | 1404.46 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4367.27 | 09-MAY-13:00 | 147.20 | 01-MAY-07:02 |
June | 2699.95 | 03-JUN-14:09 | 1404.46 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4761.86 | 12-JUN-12:00 | 114.16 | 22-JUN-08:00 |
July | 2699.95 | 01-JUL-14:09 | 1404.46 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5429.21 | 21-JUL-12:00 | 0.00 | 01-JUL-00:03 |
August | 2699.95 | 05-AUG-14:09 | 1404.46 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5521.19 | 16-AUG-12:00 | 0.00 | 01-AUG-00:10 |
September | 2699.95 | 02-SEP-14:09 | 1404.46 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4385.57 | 26-SEP-13:00 | 58.00 | 24-SEP-07:01 |
October | 2699.95 | 07-OCT-14:09 | 1404.46 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3582.72 | 09-OCT-12:00 | 193.52 | 29-OCT-07:02 |
November | 2699.95 | 04-NOV-14:09 | 1404.46 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2621.98 | 05-NOV-12:00 | 254.38 | 26-NOV-08:62 |
December | 2699.95 | 02-DEC-15:09 | 1404.46 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1605.14 | 10-DEC-12:10 | 1622.32 | 15-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1091.80 | 0.00 | |||||
Maximum of Months | 2699.95 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 5521.19 | 1684.22 |
Report: PeakSpaceGainsMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1404.46 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1115.93 | 23-JAN-14:00 | 1398.40 | 18-JAN-17:00 |
February | 2699.95 | 04-FEB-15:09 | 1404.46 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2331.98 | 06-FEB-15:00 | 1713.45 | 20-FEB-16:00 |
March | 2699.95 | 04-MAR-15:09 | 1404.46 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3755.26 | 27-MAR-11:10 | 1524.29 | 05-MAR-18:00 |
April | 2699.95 | 01-APR-14:09 | 1404.46 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4611.22 | 28-APR-12:00 | 247.71 | 01-APR-07:05 |
May | 2699.95 | 06-MAY-14:09 | 1404.46 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4486.49 | 09-MAY-13:00 | 149.26 | 01-MAY-07:02 |
June | 2699.95 | 03-JUN-14:09 | 1404.46 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4844.53 | 12-JUN-12:00 | 119.77 | 22-JUN-08:00 |
July | 2699.95 | 01-JUL-14:09 | 1404.46 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5523.42 | 21-JUL-12:00 | 0.00 | 01-JUL-00:03 |
August | 2699.95 | 05-AUG-14:09 | 1404.46 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5710.69 | 16-AUG-12:00 | 0.00 | 01-AUG-00:10 |
September | 2699.95 | 02-SEP-14:09 | 1404.46 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4472.02 | 26-SEP-13:00 | 75.04 | 24-SEP-07:01 |
October | 2699.95 | 07-OCT-14:09 | 1404.46 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3608.81 | 09-OCT-12:00 | 223.86 | 29-OCT-07:02 |
November | 2699.95 | 04-NOV-14:09 | 1404.46 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2648.66 | 05-NOV-12:00 | 311.14 | 23-NOV-08:62 |
December | 2699.95 | 02-DEC-15:09 | 1404.46 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1637.21 | 10-DEC-12:10 | 1690.29 | 15-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1115.93 | 0.00 | |||||
Maximum of Months | 2699.95 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 5710.69 | 1713.45 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 15904.03 | 30-JAN-08:63 | 1012.51 | 225.00 | 223.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 267.05 |
February | 29614.39 | 09-FEB-08:62 | 1350.01 | 300.00 | 298.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 149.78 |
March | 54620.02 | 02-MAR-08:62 | 2025.02 | 450.00 | 447.75 | 0.00 | 0.00 | 0.00 | 0.00 | 198.41 | 0.00 |
April | 52301.79 | 29-APR-07:02 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 220.22 | 0.00 |
May | 57693.54 | 11-MAY-07:01 | 2362.52 | 525.00 | 522.37 | 0.00 | 0.00 | 0.00 | 0.00 | 345.20 | 0.00 |
June | 50362.31 | 01-JUN-07:01 | 2700.03 | 600.00 | 597.00 | 0.00 | 0.00 | 0.00 | 0.00 | 302.18 | 0.00 |
July | 56391.36 | 04-JUL-07:01 | 3037.53 | 675.00 | 671.62 | 0.00 | 0.00 | 0.00 | 0.00 | 371.01 | 0.00 |
August | 50672.10 | 06-AUG-07:01 | 3375.03 | 750.00 | 746.25 | 0.00 | 0.00 | 0.00 | 0.00 | 524.39 | 0.00 |
September | 47344.17 | 02-SEP-07:01 | 0.00 | 675.00 | 662.75 | 0.00 | 0.00 | 0.00 | 0.00 | 438.49 | 0.00 |
October | 54033.58 | 20-OCT-07:02 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.19 |
November | 54552.65 | 05-NOV-07:02 | 2025.02 | 450.00 | 447.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 202.52 |
December | 45590.35 | 12-DEC-08:62 | 1687.52 | 375.00 | 373.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.29 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 15904.03 | 0.00 | 225.00 | 223.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 57693.54 | 3375.03 | 750.00 | 746.25 | 0.00 | 0.00 | 0.00 | 0.00 | 524.39 | 267.05 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 10010.88 | 30-JAN-08:63 | 506.24 | 112.50 | 111.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 148.19 |
February | 17240.37 | 09-FEB-08:62 | 674.99 | 150.00 | 149.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.27 |
March | 28060.27 | 02-MAR-08:62 | 1012.48 | 225.00 | 223.88 | 0.00 | 0.00 | 0.00 | 0.00 | 104.17 | 0.00 |
April | 27393.50 | 29-APR-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 122.73 | 0.00 |
May | 29698.05 | 11-MAY-07:01 | 1181.23 | 262.50 | 261.19 | 0.00 | 0.00 | 0.00 | 0.00 | 198.53 | 0.00 |
June | 27802.21 | 02-JUN-07:01 | 0.00 | 262.50 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 176.99 | 0.00 |
July | 29370.73 | 04-JUL-07:01 | 1518.72 | 337.50 | 335.81 | 0.00 | 0.00 | 0.00 | 0.00 | 211.32 | 0.00 |
August | 26867.61 | 06-AUG-07:01 | 1687.47 | 375.00 | 373.13 | 0.00 | 0.00 | 0.00 | 0.00 | 307.68 | 0.00 |
September | 26724.90 | 26-SEP-07:01 | 1181.23 | 262.50 | 261.19 | 0.00 | 0.00 | 0.00 | 0.00 | 74.01 | 0.00 |
October | 28959.13 | 20-OCT-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.35 |
November | 29227.31 | 05-NOV-07:02 | 1012.48 | 225.00 | 223.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 115.37 |
December | 25121.78 | 12-DEC-08:62 | 843.73 | 187.50 | 186.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.22 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 10010.88 | 0.00 | 112.50 | 111.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 29698.05 | 1687.47 | 375.00 | 373.13 | 0.00 | 0.00 | 0.00 | 0.00 | 307.68 | 148.19 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 10187.67 | 30-JAN-07:03 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.06 |
February | 18146.92 | 09-FEB-07:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 |
March | 28581.95 | 28-MAR-06:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.07 |
April | 28481.56 | 29-APR-06:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 | 0.00 |
May | 29060.34 | 05-MAY-06:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 1.58 | 0.00 |
June | 27380.95 | 01-JUN-06:01 | 0.00 | 300.00 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.69 | 0.00 |
July | 28691.66 | 04-JUL-07:01 | 0.00 | 337.50 | 335.81 | 0.00 | 0.00 | 0.00 | 0.00 | 196.42 | 0.00 |
August | 23664.61 | 16-AUG-06:01 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 27.74 | 0.00 |
September | 22157.31 | 05-SEP-06:01 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 6.66 | 0.00 |
October | 27900.27 | 20-OCT-06:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.19 |
November | 27499.61 | 05-NOV-07:02 | 0.00 | 225.00 | 223.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 129.00 |
December | 23471.48 | 12-DEC-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 10187.67 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 29060.34 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 196.42 | 129.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 9908.47 | 30-JAN-07:03 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.05 |
February | 18162.94 | 09-FEB-07:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 |
March | 29180.06 | 28-MAR-06:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.08 |
April | 28600.66 | 29-APR-06:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 0.00 |
May | 29184.44 | 05-MAY-06:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 1.52 | 0.00 |
June | 27559.67 | 01-JUN-06:01 | 0.00 | 300.00 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.65 | 0.00 |
July | 28892.27 | 04-JUL-07:01 | 0.00 | 337.50 | 335.81 | 0.00 | 0.00 | 0.00 | 0.00 | 192.11 | 0.00 |
August | 23846.62 | 16-AUG-06:01 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 27.35 | 0.00 |
September | 22509.19 | 05-SEP-06:01 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 6.26 | 0.00 |
October | 28016.78 | 20-OCT-06:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.32 |
November | 27619.74 | 05-NOV-07:02 | 0.00 | 225.00 | 223.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 131.16 |
December | 23519.96 | 12-DEC-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 9908.47 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 29184.44 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 192.11 | 131.16 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 8692.35 | 30-JAN-07:03 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.03 |
February | 16734.98 | 09-FEB-07:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.07 |
March | 27359.34 | 28-MAR-06:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.06 |
April | 28288.75 | 29-APR-06:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.39 | 0.00 |
May | 28872.77 | 05-MAY-06:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 0.00 |
June | 27218.42 | 01-JUN-06:01 | 0.00 | 300.00 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.71 | 0.00 |
July | 28586.99 | 04-JUL-07:01 | 0.00 | 337.50 | 335.81 | 0.00 | 0.00 | 0.00 | 0.00 | 196.48 | 0.00 |
August | 23561.82 | 16-AUG-06:01 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 27.78 | 0.00 |
September | 22346.84 | 05-SEP-06:01 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 6.30 | 0.00 |
October | 27746.45 | 20-OCT-06:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.07 |
November | 27369.70 | 05-NOV-07:02 | 0.00 | 225.00 | 223.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 127.91 |
December | 23254.05 | 12-DEC-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.87 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 8692.35 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 28872.77 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 196.48 | 127.91 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 13956.80 | 30-JAN-08:63 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 257.84 |
February | 28281.96 | 06-FEB-08:62 | 0.00 | 300.00 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 206.52 |
March | 46316.77 | 02-MAR-08:62 | 0.00 | 450.00 | 441.83 | 0.00 | 0.00 | 0.00 | 0.00 | 190.56 | 0.00 |
April | 49409.34 | 29-APR-07:02 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 212.47 | 0.00 |
May | 51067.54 | 11-MAY-07:01 | 0.00 | 525.00 | 515.47 | 0.00 | 0.00 | 0.00 | 0.00 | 343.67 | 0.00 |
June | 47300.70 | 01-JUN-07:01 | 0.00 | 600.00 | 589.11 | 0.00 | 0.00 | 0.00 | 0.00 | 299.20 | 0.00 |
July | 51379.40 | 04-JUL-08:61 | 0.00 | 750.00 | 736.39 | 0.00 | 0.00 | 0.00 | 0.00 | 419.97 | 0.00 |
August | 41897.77 | 16-AUG-07:01 | 0.00 | 750.00 | 736.39 | 0.00 | 0.00 | 0.00 | 0.00 | 505.51 | 0.00 |
September | 41068.54 | 26-SEP-07:01 | 0.00 | 525.00 | 515.47 | 0.00 | 0.00 | 0.00 | 0.00 | 106.95 | 0.00 |
October | 49484.75 | 20-OCT-07:02 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.25 |
November | 48093.79 | 19-NOV-09:02 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 91.33 | 0.00 |
December | 42320.76 | 12-DEC-08:62 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.34 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 13956.80 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 51379.40 | 0.00 | 750.00 | 736.39 | 0.00 | 0.00 | 0.00 | 0.00 | 505.51 | 257.84 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6745.66 | 30-JAN-08:63 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 146.67 |
February | 13982.64 | 06-FEB-08:62 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 116.99 |
March | 24338.95 | 02-MAR-08:62 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 112.00 | 0.00 |
April | 24672.12 | 29-APR-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 123.73 | 0.00 |
May | 26853.03 | 11-MAY-07:01 | 0.00 | 262.50 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 201.05 | 0.00 |
June | 24957.62 | 01-JUN-07:01 | 0.00 | 300.00 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 175.44 | 0.00 |
July | 27087.71 | 04-JUL-08:61 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 242.98 | 0.00 |
August | 22093.62 | 16-AUG-07:01 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 289.67 | 0.00 |
September | 21576.81 | 26-SEP-07:01 | 0.00 | 262.50 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 64.90 | 0.00 |
October | 25954.27 | 20-OCT-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.19 |
November | 25232.91 | 19-NOV-09:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.51 | 0.00 |
December | 20774.58 | 12-DEC-08:62 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.68 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 6745.66 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 27087.71 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 289.67 | 146.67 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6454.89 | 30-JAN-08:63 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 146.55 |
February | 13643.89 | 06-FEB-08:62 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 116.84 |
March | 24234.89 | 02-MAR-08:62 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 112.92 | 0.00 |
April | 24453.18 | 29-APR-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 123.82 | 0.00 |
May | 26752.57 | 11-MAY-07:01 | 0.00 | 262.50 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 201.55 | 0.00 |
June | 24861.43 | 01-JUN-07:01 | 0.00 | 300.00 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 175.84 | 0.00 |
July | 26997.28 | 04-JUL-08:61 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 243.08 | 0.00 |
August | 22011.23 | 16-AUG-07:01 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 289.86 | 0.00 |
September | 21496.56 | 26-SEP-07:01 | 0.00 | 262.50 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 65.11 | 0.00 |
October | 25859.61 | 20-OCT-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.69 |
November | 24975.36 | 19-NOV-09:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.63 | 0.00 |
December | 20450.57 | 12-DEC-08:62 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.56 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 6454.89 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 26997.28 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 289.86 | 146.55 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5518.18 | 30-JAN-08:63 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 146.17 |
February | 12546.07 | 06-FEB-08:62 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 116.42 |
March | 24315.62 | 02-MAR-08:62 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 115.69 | 0.00 |
April | 24097.76 | 29-APR-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 124.00 | 0.00 |
May | 26922.78 | 11-MAY-07:01 | 0.00 | 262.50 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 202.01 | 0.00 |
June | 25052.11 | 01-JUN-07:01 | 0.00 | 300.00 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 175.55 | 0.00 |
July | 27256.24 | 04-JUL-08:61 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 240.90 | 0.00 |
August | 22296.25 | 16-AUG-07:01 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 285.95 | 0.00 |
September | 21699.12 | 26-SEP-07:01 | 0.00 | 262.50 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 64.48 | 0.00 |
October | 26039.02 | 20-OCT-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.72 |
November | 24653.63 | 05-NOV-08:62 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.31 | 0.00 |
December | 19670.86 | 12-DEC-08:62 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.22 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5518.18 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 27256.24 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 285.95 | 146.17 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5910.35 | 28-JAN-14:00 | 2497.45 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1096.62 | 0.00 |
February | 9756.06 | 06-FEB-08:62 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.98 |
March | 29977.91 | 02-MAR-08:62 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 142.63 | 0.00 |
April | 24949.35 | 29-APR-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 127.34 | 0.00 |
May | 31767.59 | 11-MAY-07:01 | 0.00 | 262.50 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 201.84 | 0.00 |
June | 28601.54 | 01-JUN-07:01 | 0.00 | 300.00 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 170.77 | 0.00 |
July | 32469.64 | 04-JUL-08:61 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 238.68 | 0.00 |
August | 26864.32 | 06-AUG-08:61 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 290.73 | 0.00 |
September | 25386.95 | 26-SEP-07:01 | 0.00 | 262.50 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 58.10 | 0.00 |
October | 29620.47 | 20-OCT-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.87 |
November | 28453.54 | 12-NOV-09:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.28 |
December | 19552.30 | 12-DEC-08:62 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.19 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5910.35 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 32469.64 | 2497.45 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1096.62 | 126.98 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.796354E+11 | 73563.43 | 23-JAN-13:00 | 50694.50 | 84.49 | 02-JAN-08:30 |
February | 0.768223E+11 | 85186.74 | 07-FEB-14:20 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 0.924026E+11 | 92176.54 | 27-MAR-12:50 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 0.101511E+12 | 103596.62 | 28-APR-11:00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 0.126110E+12 | 122479.95 | 31-MAY-12:20 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 0.137284E+12 | 133980.33 | 09-JUN-13:20 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 0.155539E+12 | 147888.36 | 20-JUL-12:50 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.163680E+12 | 154921.40 | 10-AUG-16:10 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.141094E+12 | 140943.29 | 07-SEP-13:30 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 0.124988E+12 | 128230.32 | 07-OCT-13:20 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 0.104037E+12 | 105093.07 | 01-NOV-12:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 0.882524E+11 | 81217.87 | 04-DEC-15:09 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.139136E+13 | 50694.50 | ||||
Minimum of Months | 0.768223E+11 | 73563.43 | 0.00 | 0.00 | ||
Maximum of Months | 0.163680E+12 | 154921.40 | 50694.50 | 84.49 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.310073E+11 | 0.595724E+10 | 0.108325E+11 | 0.00 | 0.107656E+11 | 0.00 | 0.00 | 0.159950E+11 | 0.00 | 0.00 | 0.00 | 0.507781E+10 | 0.00 |
February | 0.280657E+11 | 0.508826E+10 | 0.980803E+10 | 0.00 | 0.975463E+10 | 0.00 | 0.00 | 0.195404E+11 | 0.00 | 0.00 | 0.00 | 0.456532E+10 | 0.00 |
March | 0.314703E+11 | 0.520718E+10 | 0.110075E+11 | 0.00 | 0.109617E+11 | 0.00 | 0.00 | 0.287530E+11 | 0.00 | 0.00 | 0.00 | 0.500299E+10 | 0.00 |
April | 0.300741E+11 | 0.458600E+10 | 0.105079E+11 | 0.00 | 0.104870E+11 | 0.00 | 0.00 | 0.411328E+11 | 0.00 | 0.00 | 0.00 | 0.472340E+10 | 0.00 |
May | 0.312330E+11 | 0.437452E+10 | 0.109147E+11 | 0.00 | 0.111292E+11 | 0.00 | 0.00 | 0.636795E+11 | 0.00 | 0.00 | 0.00 | 0.477868E+10 | 0.00 |
June | 0.304143E+11 | 0.406393E+10 | 0.106386E+11 | 0.00 | 0.117282E+11 | 0.00 | 0.00 | 0.758712E+11 | 0.00 | 0.00 | 0.00 | 0.456763E+10 | 0.00 |
July | 0.309042E+11 | 0.426217E+10 | 0.107945E+11 | 0.00 | 0.133195E+11 | 0.00 | 0.00 | 0.915916E+11 | 0.00 | 0.00 | 0.00 | 0.466680E+10 | 0.00 |
August | 0.314595E+11 | 0.457607E+10 | 0.110006E+11 | 0.00 | 0.140670E+11 | 0.00 | 0.00 | 0.978556E+11 | 0.00 | 0.00 | 0.00 | 0.472145E+10 | 0.00 |
September | 0.300847E+11 | 0.484042E+10 | 0.105148E+11 | 0.00 | 0.120937E+11 | 0.00 | 0.00 | 0.789314E+11 | 0.00 | 0.00 | 0.00 | 0.462897E+10 | 0.00 |
October | 0.310073E+11 | 0.545170E+10 | 0.108325E+11 | 0.00 | 0.110956E+11 | 0.00 | 0.00 | 0.617193E+11 | 0.00 | 0.00 | 0.00 | 0.488209E+10 | 0.00 |
November | 0.300409E+11 | 0.566318E+10 | 0.104978E+11 | 0.00 | 0.105096E+11 | 0.00 | 0.00 | 0.425080E+11 | 0.00 | 0.00 | 0.00 | 0.481784E+10 | 0.00 |
December | 0.309156E+11 | 0.607289E+10 | 0.108050E+11 | 0.00 | 0.107489E+11 | 0.00 | 0.00 | 0.246567E+11 | 0.00 | 0.00 | 0.00 | 0.505328E+10 | 0.00 |
Annual Sum or Average | 0.366677E+12 | 0.601436E+11 | 0.128154E+12 | 0.00 | 0.136661E+12 | 0.00 | 0.00 | 0.642234E+12 | 0.00 | 0.00 | 0.00 | 0.574863E+11 | 0.00 |
Minimum of Months | 0.280657E+11 | 0.406393E+10 | 0.980803E+10 | 0.00 | 0.975463E+10 | 0.00 | 0.00 | 0.159950E+11 | 0.00 | 0.00 | 0.00 | 0.456532E+10 | 0.00 |
Maximum of Months | 0.314703E+11 | 0.607289E+10 | 0.110075E+11 | 0.00 | 0.140670E+11 | 0.00 | 0.00 | 0.978556E+11 | 0.00 | 0.00 | 0.00 | 0.507781E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 50694.50 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 50694.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 50694.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 23459.17 | 01-JAN-11:09 | 5507.06 | 01-JAN-06:10 | 8059.50 | 01-JAN-11:09 | 0.00 | 7393.19 | 02-JAN-08:30 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 23459.17 | 01-FEB-10:09 | 5507.06 | 01-FEB-06:10 | 8059.50 | 01-FEB-10:09 | 0.00 | 8076.61 | 09-FEB-08:09 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 23459.17 | 01-MAR-10:09 | 5507.06 | 01-MAR-06:10 | 8059.50 | 01-MAR-10:09 | 0.00 | 8769.24 | 02-MAR-08:09 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 23459.17 | 01-APR-09:09 | 5507.06 | 01-APR-05:10 | 8059.50 | 01-APR-09:09 | 0.00 | 8967.78 | 18-APR-07:10 | 0.00 | 0.00 | 01-APR-00:10 |
May | 23459.17 | 01-MAY-09:09 | 5507.06 | 01-MAY-05:10 | 8059.50 | 01-MAY-09:09 | 0.00 | 10484.19 | 30-MAY-12:00 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 23459.17 | 01-JUN-09:09 | 5507.06 | 01-JUN-05:10 | 8059.50 | 01-JUN-09:09 | 0.00 | 11882.29 | 09-JUN-12:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 23459.17 | 01-JUL-09:09 | 5507.06 | 01-JUL-05:10 | 8059.50 | 01-JUL-09:09 | 0.00 | 14541.57 | 20-JUL-12:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 23459.17 | 01-AUG-09:09 | 5507.06 | 01-AUG-05:10 | 8059.50 | 01-AUG-09:09 | 0.00 | 14964.51 | 10-AUG-16:10 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 23459.17 | 01-SEP-09:09 | 5507.06 | 01-SEP-05:10 | 8059.50 | 01-SEP-09:09 | 0.00 | 13258.88 | 07-SEP-13:39 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 23459.17 | 01-OCT-10:09 | 5507.06 | 01-OCT-05:10 | 8059.50 | 01-OCT-10:09 | 0.00 | 11481.12 | 07-OCT-12:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 23459.17 | 01-NOV-09:09 | 5507.06 | 01-NOV-05:10 | 8059.50 | 01-NOV-09:09 | 0.00 | 9044.80 | 01-NOV-07:10 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 23459.17 | 01-DEC-10:09 | 5507.06 | 01-DEC-06:10 | 8059.50 | 01-DEC-10:09 | 0.00 | 8845.72 | 12-DEC-08:09 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||||
Minimum of Months | 23459.17 | 5507.06 | 8059.50 | 0.00 | 7393.19 | 0.00 | 0.00 | |||||
Maximum of Months | 23459.17 | 5507.06 | 8059.50 | 0.00 | 14964.51 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 29452.59 | 29-JAN-15:00 | 0.00 | 0.00 | 0.00 | 11787.90 | 06-JAN-14:09 | 0.00 |
February | 40815.44 | 07-FEB-13:39 | 0.00 | 0.00 | 0.00 | 10544.43 | 01-FEB-13:30 | 0.00 |
March | 49005.39 | 27-MAR-12:09 | 0.00 | 0.00 | 0.00 | 7323.68 | 20-MAR-18:00 | 0.00 |
April | 63071.99 | 28-APR-11:00 | 0.00 | 0.00 | 0.00 | 7536.69 | 28-APR-13:09 | 0.00 |
May | 77282.83 | 31-MAY-12:09 | 0.00 | 0.00 | 0.00 | 7537.36 | 05-MAY-12:30 | 0.00 |
June | 86924.22 | 09-JUN-12:00 | 0.00 | 0.00 | 0.00 | 7517.86 | 13-JUN-11:00 | 0.00 |
July | 99878.20 | 20-JUL-12:00 | 0.00 | 0.00 | 0.00 | 7525.98 | 26-JUL-12:39 | 0.00 |
August | 105570.71 | 10-AUG-16:10 | 0.00 | 0.00 | 0.00 | 7529.93 | 25-AUG-12:30 | 0.00 |
September | 90763.01 | 07-SEP-13:30 | 0.00 | 0.00 | 0.00 | 9337.44 | 10-SEP-13:50 | 0.00 |
October | 78682.68 | 07-OCT-12:00 | 0.00 | 0.00 | 0.00 | 7542.37 | 21-OCT-12:09 | 0.00 |
November | 61017.38 | 01-NOV-13:00 | 0.00 | 0.00 | 0.00 | 7303.09 | 11-NOV-17:30 | 0.00 |
December | 36779.36 | 05-DEC-15:39 | 0.00 | 0.00 | 0.00 | 7557.95 | 19-DEC-13:00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 29452.59 | 0.00 | 0.00 | 0.00 | 7303.09 | 0.00 | ||
Maximum of Months | 105570.71 | 0.00 | 0.00 | 0.00 | 11787.90 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 73563.43 | 23-JAN-13:00 | 23459.17 | 8059.50 | 0.00 | 0.00 | 7391.42 | 0.00 | 0.00 | 27409.35 | 0.00 |
February | 85186.74 | 07-FEB-14:20 | 23459.17 | 8059.50 | 0.00 | 0.00 | 7391.42 | 0.00 | 0.00 | 38720.59 | 0.00 |
March | 92176.54 | 27-MAR-12:50 | 23459.17 | 8059.50 | 0.00 | 0.00 | 7391.42 | 0.00 | 0.00 | 48632.74 | 0.00 |
April | 103596.62 | 28-APR-11:00 | 23459.17 | 8059.50 | 0.00 | 0.00 | 7794.96 | 0.00 | 0.00 | 63071.99 | 0.00 |
May | 122479.95 | 31-MAY-12:20 | 23459.17 | 8059.50 | 0.00 | 0.00 | 10389.58 | 0.00 | 0.00 | 77254.38 | 0.00 |
June | 133980.33 | 09-JUN-13:20 | 23459.17 | 8059.50 | 0.00 | 0.00 | 11583.48 | 0.00 | 0.00 | 85456.48 | 0.00 |
July | 147888.36 | 20-JUL-12:50 | 23459.17 | 8059.50 | 0.00 | 0.00 | 14401.03 | 0.00 | 0.00 | 98652.74 | 0.00 |
August | 154921.40 | 10-AUG-16:10 | 23459.17 | 8059.50 | 0.00 | 0.00 | 14964.51 | 0.00 | 0.00 | 105570.71 | 0.00 |
September | 140943.29 | 07-SEP-13:30 | 23459.17 | 8059.50 | 0.00 | 0.00 | 13237.11 | 0.00 | 0.00 | 90763.01 | 0.00 |
October | 128230.32 | 07-OCT-13:20 | 23459.17 | 8059.50 | 0.00 | 0.00 | 11312.49 | 0.00 | 0.00 | 77860.80 | 0.00 |
November | 105093.07 | 01-NOV-12:00 | 23459.17 | 8059.50 | 0.00 | 0.00 | 8231.31 | 0.00 | 0.00 | 59907.50 | 0.00 |
December | 81217.87 | 04-DEC-15:09 | 23459.17 | 8059.50 | 0.00 | 0.00 | 7391.42 | 0.00 | 0.00 | 34929.88 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 73563.43 | 23459.17 | 8059.50 | 0.00 | 0.00 | 7391.42 | 0.00 | 0.00 | 27409.35 | 0.00 | |
Maximum of Months | 154921.40 | 23459.17 | 8059.50 | 0.00 | 0.00 | 14964.51 | 0.00 | 0.00 | 105570.71 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 84.49 | 02-JAN-08:30 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 84.49 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.52 | 0.17 | 24.50 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 24.56 | 1.67 | 24.55 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 24.57 | 2.50 | 24.57 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.45 | 0.33 | 24.45 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 5.67 | 24.56 | 4.67 | 24.55 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 24.57 | 2.50 | 24.57 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.47 | 0.17 | 24.47 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.17 | 24.47 | 0.17 | 24.47 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.47 | 0.17 | 24.47 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.52 | 0.00 | 24.52 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 24.65 | 0.00 | 24.65 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 24.62 | 0.00 | 24.62 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 24.58 | 0.00 | 24.58 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.48 | 0.00 | 24.48 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 11.33 | 24.61 | 0.00 | 24.61 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 24.65 | 0.00 | 24.65 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 24.54 | 0.00 | 24.54 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 24.68 | 0.00 | 24.68 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 24.66 | 0.00 | 24.66 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 24.57 | 0.00 | 24.57 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.49 | 0.00 | 24.49 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 12.50 | 24.63 | 0.00 | 24.63 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 24.68 | 0.00 | 24.68 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 24.53 | 0.00 | 24.53 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 24.66 | 0.00 | 24.66 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 24.63 | 0.00 | 24.63 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 24.60 | 0.00 | 24.60 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.48 | 0.00 | 24.48 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 11.67 | 24.62 | 0.00 | 24.62 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 24.66 | 0.00 | 24.66 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 24.64 | 0.00 | 24.64 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 24.79 | 0.00 | 24.79 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 24.70 | 0.00 | 24.70 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 24.71 | 0.00 | 24.71 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.58 | 0.00 | 24.58 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 9.67 | 24.71 | 0.00 | 24.71 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 24.79 | 0.00 | 24.79 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 24.63 | 0.00 | 24.63 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 24.74 | 0.00 | 24.74 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 24.73 | 0.00 | 24.73 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 24.70 | 0.00 | 24.70 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.55 | 0.00 | 24.55 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 7.83 | 24.71 | 0.00 | 24.71 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 24.74 | 0.00 | 24.74 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 24.64 | 0.00 | 24.64 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 24.74 | 0.00 | 24.74 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 24.74 | 0.00 | 24.74 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 24.70 | 0.00 | 24.70 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.55 | 0.00 | 24.55 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 7.83 | 24.71 | 0.00 | 24.71 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 24.74 | 0.00 | 24.74 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 24.64 | 0.00 | 24.64 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 24.77 | 0.00 | 24.77 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 24.71 | 0.00 | 24.71 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 24.73 | 0.00 | 24.73 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.55 | 0.00 | 24.55 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 8.50 | 24.71 | 0.00 | 24.71 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 24.77 | 0.00 | 24.77 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.47 | 0.00 | 24.47 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 24.63 | 0.00 | 24.63 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 24.85 | 0.00 | 24.85 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 25.20 | 0.00 | 25.20 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 25.19 | 0.00 | 25.19 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 24.65 | 0.00 | 24.65 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 14.00 | 24.98 | 0.00 | 24.98 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 25.20 | 0.00 | 25.20 |
Report: ComfortReportSimple55Monthly
For: LGSTORE1
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 45.00 | 23.12 | 267.33 | 23.78 | 1.33 | 23.78 |
February | 20.00 | 23.18 | 342.17 | 23.85 | 0.00 | 23.85 |
March | 22.67 | 23.51 | 363.50 | 23.87 | 3.50 | 23.87 |
April | 5.17 | 23.87 | 429.83 | 23.89 | 5.17 | 23.89 |
May | 22.33 | 23.89 | 492.00 | 23.89 | 22.33 | 23.89 |
June | 117.83 | 23.90 | 481.00 | 23.89 | 117.83 | 23.89 |
July | 194.67 | 23.90 | 495.00 | 23.90 | 194.67 | 23.90 |
August | 187.17 | 23.90 | 497.00 | 23.90 | 187.17 | 23.90 |
September | 125.67 | 23.90 | 479.00 | 23.89 | 125.67 | 23.90 |
October | 64.00 | 23.90 | 491.50 | 23.89 | 64.00 | 23.89 |
November | 10.17 | 23.89 | 470.17 | 23.89 | 10.17 | 23.89 |
December | 20.83 | 23.59 | 398.33 | 23.87 | 8.17 | 23.87 |
Annual Sum or Average | 835.50 | 23.82 | 5206.83 | 23.88 | 740.00 | 23.88 |
Minimum of Months | 5.17 | 23.12 | 267.33 | 23.78 | 0.00 | 23.78 |
Maximum of Months | 194.67 | 23.90 | 497.00 | 23.90 | 194.67 | 23.90 |
Report: ComfortReportSimple55Monthly
For: SMSTORE1
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 33.83 | 23.29 | 236.83 | 23.82 | 1.17 | 23.82 |
February | 15.00 | 23.40 | 305.50 | 23.87 | 0.00 | 23.87 |
March | 14.50 | 23.61 | 326.67 | 23.88 | 0.00 | 23.88 |
April | 2.50 | 23.84 | 391.33 | 23.89 | 2.17 | 23.89 |
May | 13.83 | 23.89 | 478.50 | 23.89 | 13.83 | 23.89 |
June | 85.17 | 23.89 | 480.83 | 23.89 | 85.17 | 23.89 |
July | 145.83 | 23.89 | 495.00 | 23.89 | 145.83 | 23.89 |
August | 159.83 | 23.89 | 497.00 | 23.89 | 159.83 | 23.89 |
September | 96.00 | 23.89 | 479.00 | 23.89 | 96.00 | 23.89 |
October | 41.50 | 23.89 | 485.00 | 23.89 | 41.50 | 23.89 |
November | 7.17 | 23.88 | 441.33 | 23.89 | 7.00 | 23.89 |
December | 13.33 | 23.63 | 364.00 | 23.88 | 3.67 | 23.88 |
Annual Sum or Average | 628.50 | 23.84 | 4981.00 | 23.88 | 556.17 | 23.89 |
Minimum of Months | 2.50 | 23.29 | 236.83 | 23.82 | 0.00 | 23.82 |
Maximum of Months | 159.83 | 23.89 | 497.00 | 23.89 | 159.83 | 23.89 |
Report: ComfortReportSimple55Monthly
For: SMSTORE2
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 31.67 | 23.19 | 212.83 | 23.92 | 1.50 | 23.92 |
February | 11.33 | 23.28 | 270.50 | 23.98 | 0.17 | 23.99 |
March | 10.33 | 23.99 | 284.50 | 24.06 | 2.67 | 24.08 |
April | 9.17 | 26.08 | 311.67 | 24.17 | 9.17 | 24.23 |
May | 34.33 | 25.81 | 372.17 | 24.30 | 34.33 | 24.41 |
June | 101.33 | 24.74 | 366.00 | 24.29 | 101.33 | 24.37 |
July | 161.33 | 24.58 | 369.00 | 24.32 | 161.33 | 24.38 |
August | 176.50 | 24.53 | 379.00 | 24.31 | 176.50 | 24.36 |
September | 117.67 | 24.73 | 360.00 | 24.31 | 117.67 | 24.40 |
October | 60.17 | 24.94 | 362.50 | 24.27 | 60.17 | 24.35 |
November | 15.83 | 25.00 | 355.00 | 24.12 | 15.83 | 24.15 |
December | 17.67 | 24.11 | 316.50 | 24.03 | 11.83 | 24.04 |
Annual Sum or Average | 747.33 | 24.63 | 3959.67 | 24.20 | 692.50 | 24.27 |
Minimum of Months | 9.17 | 23.19 | 212.83 | 23.92 | 0.17 | 23.92 |
Maximum of Months | 176.50 | 26.08 | 379.00 | 24.32 | 176.50 | 24.41 |
Report: ComfortReportSimple55Monthly
For: SMSTORE3
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 33.67 | 23.16 | 208.83 | 23.90 | 1.50 | 23.90 |
February | 12.33 | 23.26 | 267.00 | 23.98 | 0.17 | 23.98 |
March | 11.00 | 23.95 | 283.50 | 24.06 | 2.67 | 24.07 |
April | 9.17 | 26.13 | 312.50 | 24.17 | 9.17 | 24.23 |
May | 34.00 | 25.83 | 372.17 | 24.30 | 34.00 | 24.42 |
June | 99.50 | 24.76 | 366.00 | 24.30 | 99.50 | 24.38 |
July | 157.67 | 24.60 | 369.00 | 24.33 | 157.67 | 24.39 |
August | 175.00 | 24.54 | 379.00 | 24.31 | 175.00 | 24.37 |
September | 114.83 | 24.75 | 360.00 | 24.32 | 114.83 | 24.40 |
October | 59.17 | 24.99 | 362.67 | 24.27 | 59.17 | 24.36 |
November | 15.67 | 25.01 | 355.00 | 24.12 | 15.67 | 24.16 |
December | 18.67 | 24.07 | 314.50 | 24.02 | 12.17 | 24.04 |
Annual Sum or Average | 740.67 | 24.64 | 3950.17 | 24.21 | 681.50 | 24.28 |
Minimum of Months | 9.17 | 23.16 | 208.83 | 23.90 | 0.17 | 23.90 |
Maximum of Months | 175.00 | 26.13 | 379.00 | 24.33 | 175.00 | 24.42 |
Report: ComfortReportSimple55Monthly
For: SMSTORE4
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 37.50 | 23.12 | 202.50 | 23.87 | 1.67 | 23.87 |
February | 15.33 | 23.29 | 259.33 | 23.97 | 0.50 | 23.97 |
March | 14.50 | 23.84 | 270.50 | 24.06 | 3.67 | 24.07 |
April | 9.83 | 25.86 | 308.00 | 24.17 | 9.83 | 24.22 |
May | 34.33 | 25.73 | 370.50 | 24.29 | 34.33 | 24.40 |
June | 102.83 | 24.72 | 366.00 | 24.29 | 102.83 | 24.37 |
July | 161.00 | 24.58 | 369.00 | 24.32 | 161.00 | 24.38 |
August | 176.50 | 24.52 | 379.00 | 24.30 | 176.50 | 24.36 |
September | 118.00 | 24.72 | 360.00 | 24.31 | 118.00 | 24.39 |
October | 61.00 | 24.90 | 362.33 | 24.26 | 61.00 | 24.34 |
November | 17.17 | 24.89 | 354.67 | 24.11 | 17.17 | 24.15 |
December | 24.33 | 23.99 | 307.50 | 24.02 | 16.00 | 24.03 |
Annual Sum or Average | 772.33 | 24.58 | 3909.33 | 24.20 | 702.50 | 24.26 |
Minimum of Months | 9.83 | 23.12 | 202.50 | 23.87 | 0.50 | 23.87 |
Maximum of Months | 176.50 | 25.86 | 379.00 | 24.32 | 176.50 | 24.40 |
Report: ComfortReportSimple55Monthly
For: LGSTORE2
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 34.00 | 23.29 | 168.67 | 23.82 | 3.00 | 23.82 |
February | 10.67 | 23.31 | 218.33 | 23.90 | 0.67 | 23.90 |
March | 11.83 | 23.77 | 220.83 | 23.94 | 4.17 | 23.94 |
April | 6.83 | 25.92 | 277.67 | 24.03 | 6.83 | 24.08 |
May | 25.67 | 24.95 | 338.50 | 24.06 | 25.67 | 24.12 |
June | 102.17 | 24.19 | 336.00 | 24.03 | 102.17 | 24.06 |
July | 166.33 | 24.17 | 338.00 | 24.08 | 166.33 | 24.10 |
August | 179.50 | 24.08 | 348.00 | 24.02 | 179.50 | 24.04 |
September | 120.00 | 24.21 | 330.00 | 24.06 | 120.00 | 24.09 |
October | 54.33 | 24.39 | 331.83 | 24.05 | 54.33 | 24.09 |
November | 16.50 | 24.09 | 323.83 | 23.96 | 16.50 | 23.97 |
December | 27.50 | 24.01 | 262.50 | 23.95 | 22.67 | 23.96 |
Annual Sum or Average | 755.33 | 24.15 | 3494.17 | 24.01 | 701.83 | 24.04 |
Minimum of Months | 6.83 | 23.29 | 168.67 | 23.82 | 0.67 | 23.82 |
Maximum of Months | 179.50 | 25.92 | 348.00 | 24.08 | 179.50 | 24.12 |
Report: ComfortReportSimple55Monthly
For: SMSTORE5
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 39.17 | 23.36 | 148.17 | 23.81 | 3.00 | 23.81 |
February | 12.00 | 23.37 | 195.83 | 23.90 | 0.83 | 23.90 |
March | 13.50 | 23.79 | 197.67 | 23.94 | 4.17 | 23.94 |
April | 7.33 | 25.59 | 266.50 | 24.03 | 7.33 | 24.07 |
May | 26.67 | 24.86 | 330.00 | 24.06 | 26.67 | 24.11 |
June | 103.67 | 24.18 | 336.00 | 24.03 | 103.67 | 24.06 |
July | 164.67 | 24.17 | 338.00 | 24.07 | 164.67 | 24.10 |
August | 179.17 | 24.07 | 348.00 | 24.02 | 179.17 | 24.03 |
September | 120.83 | 24.21 | 330.00 | 24.06 | 120.83 | 24.09 |
October | 54.33 | 24.38 | 328.00 | 24.05 | 54.33 | 24.09 |
November | 16.50 | 24.01 | 318.17 | 23.96 | 16.50 | 23.96 |
December | 28.17 | 24.02 | 247.00 | 23.95 | 22.67 | 23.97 |
Annual Sum or Average | 766.00 | 24.14 | 3383.33 | 24.01 | 703.83 | 24.04 |
Minimum of Months | 7.33 | 23.36 | 148.17 | 23.81 | 0.83 | 23.81 |
Maximum of Months | 179.17 | 25.59 | 348.00 | 24.07 | 179.17 | 24.11 |
Report: ComfortReportSimple55Monthly
For: SMSTORE6
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 41.83 | 23.37 | 145.33 | 23.80 | 3.17 | 23.81 |
February | 13.17 | 23.38 | 190.67 | 23.90 | 1.00 | 23.90 |
March | 15.00 | 23.77 | 194.33 | 23.94 | 4.33 | 23.94 |
April | 7.83 | 25.53 | 265.00 | 24.03 | 7.83 | 24.07 |
May | 26.83 | 24.83 | 329.50 | 24.05 | 26.83 | 24.11 |
June | 104.17 | 24.18 | 336.00 | 24.03 | 104.17 | 24.06 |
July | 165.17 | 24.16 | 338.00 | 24.07 | 165.17 | 24.10 |
August | 180.17 | 24.07 | 348.00 | 24.02 | 180.17 | 24.03 |
September | 121.67 | 24.20 | 330.00 | 24.06 | 121.67 | 24.09 |
October | 54.33 | 24.37 | 327.83 | 24.05 | 54.33 | 24.09 |
November | 16.83 | 24.01 | 318.00 | 23.96 | 16.83 | 23.96 |
December | 29.67 | 24.03 | 244.50 | 23.95 | 24.00 | 23.97 |
Annual Sum or Average | 776.67 | 24.13 | 3367.17 | 24.01 | 709.50 | 24.04 |
Minimum of Months | 7.83 | 23.37 | 145.33 | 23.80 | 1.00 | 23.81 |
Maximum of Months | 180.17 | 25.53 | 348.00 | 24.07 | 180.17 | 24.11 |
Report: ComfortReportSimple55Monthly
For: SMSTORE7
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 46.83 | 23.34 | 142.83 | 23.78 | 3.17 | 23.78 |
February | 16.33 | 23.36 | 187.17 | 23.89 | 1.33 | 23.89 |
March | 17.33 | 23.73 | 193.50 | 23.93 | 4.67 | 23.94 |
April | 7.83 | 25.53 | 265.67 | 24.03 | 7.83 | 24.07 |
May | 25.67 | 24.90 | 332.33 | 24.06 | 25.67 | 24.11 |
June | 100.83 | 24.19 | 336.00 | 24.03 | 100.83 | 24.06 |
July | 161.83 | 24.17 | 338.00 | 24.07 | 161.83 | 24.10 |
August | 174.83 | 24.08 | 348.00 | 24.02 | 174.83 | 24.04 |
September | 118.50 | 24.21 | 330.00 | 24.06 | 118.50 | 24.09 |
October | 53.17 | 24.40 | 328.83 | 24.05 | 53.17 | 24.09 |
November | 16.83 | 24.01 | 318.67 | 23.96 | 16.83 | 23.96 |
December | 32.67 | 23.99 | 243.33 | 23.95 | 25.50 | 23.96 |
Annual Sum or Average | 772.67 | 24.12 | 3364.33 | 24.01 | 694.17 | 24.04 |
Minimum of Months | 7.83 | 23.34 | 142.83 | 23.78 | 1.33 | 23.78 |
Maximum of Months | 174.83 | 25.53 | 348.00 | 24.07 | 174.83 | 24.11 |
Report: ComfortReportSimple55Monthly
For: SMSTORE8
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 50.00 | 23.24 | 159.83 | 23.77 | 3.50 | 23.77 |
February | 20.17 | 23.27 | 207.67 | 23.88 | 1.50 | 23.88 |
March | 24.00 | 23.68 | 226.83 | 23.92 | 6.67 | 23.93 |
April | 11.17 | 25.60 | 293.67 | 24.05 | 10.67 | 24.10 |
May | 22.33 | 25.35 | 342.83 | 24.08 | 22.33 | 24.15 |
June | 75.17 | 24.34 | 336.00 | 24.06 | 75.17 | 24.10 |
July | 126.50 | 24.28 | 338.00 | 24.10 | 126.50 | 24.14 |
August | 133.33 | 24.17 | 348.00 | 24.04 | 133.33 | 24.07 |
September | 84.83 | 24.39 | 330.00 | 24.09 | 84.83 | 24.15 |
October | 38.83 | 24.76 | 338.17 | 24.08 | 38.83 | 24.14 |
November | 13.17 | 24.40 | 327.33 | 23.98 | 13.17 | 24.00 |
December | 32.83 | 23.93 | 260.00 | 23.94 | 24.33 | 23.96 |
Annual Sum or Average | 632.33 | 24.22 | 3508.33 | 24.02 | 540.83 | 24.06 |
Minimum of Months | 11.17 | 23.24 | 159.83 | 23.77 | 1.50 | 23.77 |
Maximum of Months | 133.33 | 25.60 | 348.00 | 24.10 | 133.33 | 24.15 |
Report: OccupantComfortDataSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 496.00000 | 23.81663 | 45.65045 | 0.42090 | 8.93094 |
February | 448.00000 | 23.85362 | 48.71730 | 0.46568 | 9.67167 |
March | 497.00000 | 23.87011 | 46.39737 | 0.47181 | 9.80279 |
April | 479.00000 | 23.88625 | 49.56122 | 0.53083 | 11.01239 |
May | 496.00000 | 23.89031 | 51.16872 | -0.2373 | 6.31904 |
June | 481.00000 | 23.89237 | 58.26353 | -0.1568 | 5.62357 |
July | 495.00000 | 23.89448 | 60.38277 | -0.1035 | 5.34743 |
August | 497.00000 | 23.89531 | 61.70216 | -0.0759 | 5.22779 |
September | 479.00000 | 23.89290 | 60.67028 | -0.1180 | 5.40501 |
October | 496.00000 | 23.89124 | 54.20586 | 0.63095 | 13.46415 |
November | 480.00000 | 23.88578 | 51.28522 | 0.56398 | 11.76058 |
December | 496.00000 | 23.87120 | 49.93425 | 0.49190 | 10.19878 |
Annual Sum or Average | 5840.00000 | 23.87843 | 53.17785 | 0.23891 | 8.55562 |
Minimum of Months | 448.00000 | 23.81663 | 45.65045 | -0.2373 | 5.22779 |
Maximum of Months | 497.00000 | 23.89531 | 61.70216 | 0.63095 | 13.46415 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 496.00000 | 23.84648 | 43.73392 | 0.41896 | 8.82948 |
February | 448.00000 | 23.87052 | 46.22126 | 0.45366 | 9.40716 |
March | 497.00000 | 23.87947 | 44.34922 | 0.45610 | 9.46232 |
April | 479.00000 | 23.88546 | 46.95228 | 0.50032 | 10.34783 |
May | 496.00000 | 23.88990 | 49.09738 | -0.2903 | 6.88707 |
June | 481.00000 | 23.89173 | 55.87288 | -0.2212 | 6.14064 |
July | 495.00000 | 23.89317 | 58.48899 | -0.1734 | 5.75269 |
August | 497.00000 | 23.89368 | 60.02156 | -0.1510 | 5.58868 |
September | 479.00000 | 23.89205 | 58.32108 | -0.1877 | 5.85977 |
October | 496.00000 | 23.89087 | 51.87368 | 0.58516 | 12.29715 |
November | 480.00000 | 23.88469 | 49.15996 | 0.53085 | 11.00600 |
December | 496.00000 | 23.87862 | 47.41511 | 0.47357 | 9.80849 |
Annual Sum or Average | 5840.00000 | 23.88310 | 50.97955 | 0.19798 | 8.44214 |
Minimum of Months | 448.00000 | 23.84648 | 43.73392 | -0.2903 | 5.58868 |
Maximum of Months | 497.00000 | 23.89368 | 60.02156 | 0.58516 | 12.29715 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 23.90850 | 44.84500 | 0.43498 | 9.19815 |
February | 336.00000 | 23.96326 | 47.72990 | 0.48100 | 10.00910 |
March | 379.00000 | 24.01348 | 45.34671 | 0.48835 | 10.22247 |
April | 360.00000 | 24.08556 | 47.96093 | 0.54645 | 11.61608 |
May | 375.00000 | 24.15462 | 49.67802 | -0.2111 | 6.88514 |
June | 366.00000 | 24.16843 | 56.88518 | -0.1333 | 6.46029 |
July | 369.00000 | 24.21090 | 60.09820 | -0.0690 | 6.41955 |
August | 379.00000 | 24.20313 | 61.69157 | -0.0480 | 6.30719 |
September | 360.00000 | 24.17371 | 60.01479 | -0.0912 | 6.30436 |
October | 371.00000 | 24.14691 | 53.14992 | 0.64982 | 14.36370 |
November | 360.00000 | 24.07710 | 51.25414 | 0.58709 | 12.48948 |
December | 369.00000 | 23.99270 | 49.34881 | 0.50926 | 10.61888 |
Annual Sum or Average | 4395.00000 | 24.09241 | 52.35923 | 0.25956 | 9.22648 |
Minimum of Months | 336.00000 | 23.90850 | 44.84500 | -0.2111 | 6.30436 |
Maximum of Months | 379.00000 | 24.21090 | 61.69157 | 0.64982 | 14.36370 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 23.90089 | 44.92140 | 0.43107 | 9.14028 |
February | 336.00000 | 23.95958 | 47.78635 | 0.47883 | 9.96947 |
March | 379.00000 | 24.01176 | 45.36535 | 0.48728 | 10.20260 |
April | 360.00000 | 24.08554 | 47.94618 | 0.54689 | 11.62587 |
May | 375.00000 | 24.15539 | 49.61039 | -0.2081 | 6.86666 |
June | 366.00000 | 24.16944 | 56.78587 | -0.1300 | 6.45242 |
July | 369.00000 | 24.21221 | 59.96890 | -0.0648 | 6.42130 |
August | 379.00000 | 24.20435 | 61.56257 | -0.0440 | 6.31278 |
September | 360.00000 | 24.17479 | 59.89436 | -0.0877 | 6.30237 |
October | 371.00000 | 24.14782 | 53.05618 | 0.65169 | 14.41847 |
November | 360.00000 | 24.07717 | 51.22595 | 0.58766 | 12.50413 |
December | 369.00000 | 23.99052 | 49.38510 | 0.50795 | 10.59278 |
Annual Sum or Average | 4395.00000 | 24.09169 | 52.31733 | 0.26061 | 9.21952 |
Minimum of Months | 336.00000 | 23.90089 | 44.92140 | -0.2081 | 6.30237 |
Maximum of Months | 379.00000 | 24.21221 | 61.56257 | 0.65169 | 14.41847 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 23.88282 | 45.16919 | 0.42236 | 9.00541 |
February | 336.00000 | 23.94860 | 48.04445 | 0.47251 | 9.84861 |
March | 379.00000 | 24.00367 | 45.56519 | 0.48163 | 10.08788 |
April | 360.00000 | 24.08123 | 48.13092 | 0.54273 | 11.52198 |
May | 375.00000 | 24.15188 | 49.73286 | -0.2127 | 6.88463 |
June | 366.00000 | 24.16597 | 56.93972 | -0.1339 | 6.44690 |
July | 369.00000 | 24.20910 | 60.10090 | -0.0676 | 6.39903 |
August | 379.00000 | 24.20118 | 61.70421 | -0.0469 | 6.28561 |
September | 360.00000 | 24.17151 | 60.05854 | -0.0908 | 6.28695 |
October | 371.00000 | 24.14425 | 53.21186 | 0.64920 | 14.33967 |
November | 360.00000 | 24.07316 | 51.42529 | 0.58435 | 12.41345 |
December | 369.00000 | 23.98219 | 49.64917 | 0.50284 | 10.48552 |
Annual Sum or Average | 4395.00000 | 24.08556 | 52.50199 | 0.25619 | 9.15301 |
Minimum of Months | 336.00000 | 23.88282 | 45.16919 | -0.2127 | 6.28561 |
Maximum of Months | 379.00000 | 24.20910 | 61.70421 | 0.64920 | 14.33967 |
Report: OccupantComfortDataSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 23.85015 | 46.85217 | 0.40780 | 8.69353 |
February | 308.00000 | 23.89571 | 49.60416 | 0.45615 | 9.46465 |
March | 348.00000 | 23.91703 | 47.14399 | 0.46148 | 9.60179 |
April | 330.00000 | 23.97085 | 49.60081 | 0.52128 | 10.92740 |
May | 344.00000 | 23.98830 | 51.33529 | -0.2506 | 6.83971 |
June | 336.00000 | 23.98548 | 58.52452 | -0.1745 | 6.22445 |
July | 338.00000 | 24.02919 | 61.68482 | -0.1029 | 5.98425 |
August | 348.00000 | 23.99064 | 63.38928 | -0.0886 | 5.72745 |
September | 330.00000 | 24.00836 | 61.55944 | -0.1240 | 5.96707 |
October | 340.00000 | 23.99234 | 54.39968 | 0.62582 | 13.52951 |
November | 330.00000 | 23.95719 | 52.87860 | 0.56310 | 11.78411 |
December | 338.00000 | 23.92345 | 51.32312 | 0.48724 | 10.10676 |
Annual Sum or Average | 4030.00000 | 23.95938 | 54.05022 | 0.22919 | 8.72270 |
Minimum of Months | 308.00000 | 23.85015 | 46.85217 | -0.2506 | 5.72745 |
Maximum of Months | 348.00000 | 24.02919 | 63.38928 | 0.62582 | 13.52951 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 23.85124 | 46.79912 | 0.39698 | 8.50734 |
February | 308.00000 | 23.89584 | 49.56847 | 0.44400 | 9.23206 |
March | 348.00000 | 23.91715 | 47.09855 | 0.44789 | 9.33722 |
April | 330.00000 | 23.96984 | 49.55716 | 0.50515 | 10.57539 |
May | 344.00000 | 23.98733 | 51.24460 | -0.2791 | 7.14471 |
June | 336.00000 | 23.98425 | 58.46855 | -0.2049 | 6.45732 |
July | 338.00000 | 24.02812 | 61.64448 | -0.1357 | 6.14353 |
August | 348.00000 | 23.98970 | 63.37784 | -0.1225 | 5.87034 |
September | 330.00000 | 24.00721 | 61.56706 | -0.1554 | 6.14169 |
October | 340.00000 | 23.99173 | 54.34204 | 0.60522 | 12.99441 |
November | 330.00000 | 23.95656 | 52.85634 | 0.54613 | 11.38469 |
December | 338.00000 | 23.92374 | 51.30176 | 0.47491 | 9.85525 |
Annual Sum or Average | 4030.00000 | 23.95888 | 54.01088 | 0.20749 | 8.62405 |
Minimum of Months | 308.00000 | 23.85124 | 46.79912 | -0.2791 | 5.87034 |
Maximum of Months | 348.00000 | 24.02812 | 63.37784 | 0.60522 | 12.99441 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 23.84743 | 46.86712 | 0.39413 | 8.46706 |
February | 308.00000 | 23.89357 | 49.64075 | 0.44172 | 9.19222 |
March | 348.00000 | 23.91610 | 47.15133 | 0.44596 | 9.30259 |
April | 330.00000 | 23.96952 | 49.60287 | 0.50381 | 10.54625 |
May | 344.00000 | 23.98712 | 51.27579 | -0.2806 | 7.16154 |
June | 336.00000 | 23.98407 | 58.50614 | -0.2063 | 6.46776 |
July | 338.00000 | 24.02794 | 61.67811 | -0.1368 | 6.14825 |
August | 348.00000 | 23.98958 | 63.41216 | -0.1236 | 5.87457 |
September | 330.00000 | 24.00701 | 61.60517 | -0.1566 | 6.14761 |
October | 340.00000 | 23.99142 | 54.37695 | 0.60430 | 12.97006 |
November | 330.00000 | 23.95629 | 52.90323 | 0.54502 | 11.35867 |
December | 338.00000 | 23.92265 | 51.36873 | 0.47325 | 9.82320 |
Annual Sum or Average | 4030.00000 | 23.95805 | 54.05755 | 0.20596 | 8.60891 |
Minimum of Months | 308.00000 | 23.84743 | 46.86712 | -0.2806 | 5.87457 |
Maximum of Months | 348.00000 | 24.02794 | 63.41216 | 0.60430 | 12.97006 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 23.83429 | 47.02418 | 0.38897 | 8.41100 |
February | 308.00000 | 23.88533 | 49.80181 | 0.43833 | 9.14285 |
March | 348.00000 | 23.91255 | 47.24753 | 0.44434 | 9.28178 |
April | 330.00000 | 23.96941 | 49.63855 | 0.50544 | 10.58333 |
May | 344.00000 | 23.98759 | 51.20626 | -0.2740 | 7.09171 |
June | 336.00000 | 23.98463 | 58.37296 | -0.1986 | 6.40919 |
July | 338.00000 | 24.02868 | 61.48361 | -0.1275 | 6.10493 |
August | 348.00000 | 23.99014 | 63.17601 | -0.1136 | 5.83206 |
September | 330.00000 | 24.00771 | 61.41407 | -0.1480 | 6.10216 |
October | 340.00000 | 23.99198 | 54.26068 | 0.60912 | 13.09613 |
November | 330.00000 | 23.95638 | 52.87932 | 0.54785 | 11.42523 |
December | 338.00000 | 23.91933 | 51.48633 | 0.47237 | 9.81222 |
Annual Sum or Average | 4030.00000 | 23.95603 | 54.02304 | 0.20937 | 8.59494 |
Minimum of Months | 308.00000 | 23.83429 | 47.02418 | -0.2740 | 5.83206 |
Maximum of Months | 348.00000 | 24.02868 | 63.17601 | 0.60912 | 13.09613 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 23.81853 | 46.88598 | 0.39416 | 8.58056 |
February | 308.00000 | 23.87328 | 49.72088 | 0.44781 | 9.37528 |
March | 348.00000 | 23.90616 | 47.12987 | 0.46143 | 9.67068 |
April | 330.00000 | 23.97779 | 49.27559 | 0.54355 | 11.46324 |
May | 344.00000 | 23.99659 | 50.37664 | -0.1887 | 6.34821 |
June | 336.00000 | 23.99338 | 56.96557 | -0.1073 | 5.90951 |
July | 338.00000 | 24.03893 | 59.73530 | -0.0258 | 5.87637 |
August | 348.00000 | 23.99741 | 61.09500 | -0.0059 | 5.64929 |
September | 330.00000 | 24.01892 | 59.58406 | -0.0514 | 5.82019 |
October | 340.00000 | 24.00285 | 53.05352 | 0.66632 | 14.67291 |
November | 330.00000 | 23.96375 | 52.06545 | 0.58826 | 12.42214 |
December | 338.00000 | 23.91931 | 51.17779 | 0.48839 | 10.16932 |
Annual Sum or Average | 4030.00000 | 23.95933 | 53.10660 | 0.26524 | 8.81409 |
Minimum of Months | 308.00000 | 23.81853 | 46.88598 | -0.1887 | 5.64929 |
Maximum of Months | 348.00000 | 24.03893 | 61.09500 | 0.66632 | 14.67291 |
Report: DXReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.127288E+11 | 0.378352E+10 | 443.81 | 0.968759E+10 | 0.304122E+10 | 0.00 | 0.74 | 30-JAN-08:63 | 0.00 | 01-JAN-00:10 | 25934.59 | 30-JAN-08:63 | 16640.52 | 30-JAN-08:63 | 9294.07 | 30-JAN-08:63 | 6647.21 | 30-JAN-08:63 | 0.00 | 01-JAN-00:10 |
February | 0.150103E+11 | 0.447405E+10 | 421.25 | 0.112234E+11 | 0.378685E+10 | 0.00 | 1.00 | 06-FEB-08:62 | 0.00 | 01-FEB-00:05 | 54944.77 | 09-FEB-08:62 | 33037.94 | 09-FEB-08:62 | 21906.83 | 09-FEB-08:62 | 12968.63 | 09-FEB-08:62 | 0.00 | 01-FEB-00:05 |
March | 0.212470E+11 | 0.643679E+10 | 478.53 | 0.166189E+11 | 0.462810E+10 | 0.00 | 1.00 | 01-MAR-08:62 | 0.00 | 01-MAR-00:05 | 72925.44 | 02-MAR-08:62 | 62949.18 | 02-MAR-08:62 | 19354.19 | 29-MAR-07:03 | 18878.61 | 02-MAR-08:62 | 0.00 | 01-MAR-00:05 |
April | 0.303205E+11 | 0.926231E+10 | 477.30 | 0.229567E+11 | 0.736385E+10 | 0.00 | 1.00 | 03-APR-07:03 | 0.00 | 01-APR-00:05 | 78893.11 | 30-APR-07:02 | 61239.94 | 29-APR-07:02 | 34718.37 | 30-APR-07:02 | 18416.45 | 18-APR-07:02 | 0.00 | 01-APR-00:05 |
May | 0.453074E+11 | 0.141165E+11 | 500.66 | 0.340652E+11 | 0.112422E+11 | 0.00 | 1.00 | 01-MAY-07:02 | 0.00 | 01-MAY-00:10 | 81124.24 | 30-MAY-07:01 | 67638.95 | 10-MAY-07:02 | 39265.19 | 30-MAY-07:02 | 20117.01 | 23-MAY-07:01 | 0.00 | 01-MAY-00:10 |
June | 0.552188E+11 | 0.167154E+11 | 488.85 | 0.366644E+11 | 0.185544E+11 | 0.00 | 1.00 | 01-JUN-07:01 | 0.00 | 01-JUN-00:10 | 82723.02 | 19-JUN-07:01 | 58551.45 | 02-JUN-07:01 | 44288.72 | 19-JUN-07:04 | 21316.33 | 05-JUN-07:03 | 0.00 | 01-JUN-00:10 |
July | 0.663490E+11 | 0.202121E+11 | 503.51 | 0.425285E+11 | 0.238205E+11 | 0.00 | 1.00 | 01-JUL-07:01 | 0.00 | 01-JUL-00:03 | 82629.37 | 26-JUL-07:01 | 65035.13 | 04-JUL-07:01 | 45511.57 | 18-JUL-07:04 | 21140.14 | 15-JUL-07:12 | 0.00 | 01-JUL-00:03 |
August | 0.701817E+11 | 0.212396E+11 | 504.51 | 0.439110E+11 | 0.262707E+11 | 0.00 | 1.00 | 01-AUG-07:01 | 0.00 | 01-AUG-00:10 | 82629.37 | 08-AUG-07:04 | 59982.62 | 06-AUG-07:01 | 50868.42 | 08-AUG-07:06 | 21641.73 | 05-AUG-07:01 | 0.00 | 01-AUG-00:10 |
September | 0.596102E+11 | 0.175247E+11 | 487.84 | 0.372679E+11 | 0.223423E+11 | 0.00 | 1.00 | 01-SEP-07:01 | 0.00 | 01-SEP-00:03 | 82514.83 | 11-SEP-07:01 | 55774.97 | 02-SEP-07:01 | 43684.08 | 11-SEP-07:12 | 20661.35 | 02-SEP-07:01 | 0.00 | 01-SEP-00:03 |
October | 0.467071E+11 | 0.138015E+11 | 499.91 | 0.323674E+11 | 0.143398E+11 | 0.00 | 1.00 | 01-OCT-07:01 | 0.00 | 01-OCT-00:10 | 82395.69 | 08-OCT-07:01 | 61333.35 | 20-OCT-07:02 | 43144.25 | 08-OCT-07:02 | 19529.42 | 06-OCT-07:01 | 0.00 | 01-OCT-00:10 |
November | 0.321231E+11 | 0.945002E+10 | 478.28 | 0.230333E+11 | 0.908982E+10 | 0.00 | 1.00 | 01-NOV-07:02 | 0.00 | 01-NOV-00:10 | 78890.41 | 03-NOV-07:02 | 60083.50 | 05-NOV-07:02 | 31744.18 | 03-NOV-07:02 | 19005.43 | 20-NOV-08:62 | 0.00 | 01-NOV-00:10 |
December | 0.193056E+11 | 0.566240E+10 | 477.84 | 0.138208E+11 | 0.548473E+10 | 0.00 | 1.00 | 05-DEC-08:62 | 0.00 | 01-DEC-01:05 | 76792.45 | 12-DEC-08:62 | 52046.54 | 12-DEC-08:62 | 24745.91 | 12-DEC-08:62 | 18428.28 | 12-DEC-08:62 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.474109E+12 | 0.142679E+12 | 5762.30 | 0.324145E+12 | 0.149964E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.127288E+11 | 0.378352E+10 | 421.25 | 0.968759E+10 | 0.304122E+10 | 0.00 | 0.74 | 0.00 | 25934.59 | 16640.52 | 9294.07 | 6647.21 | 0.00 | |||||||
Maximum of Months | 0.701817E+11 | 0.212396E+11 | 504.51 | 0.439110E+11 | 0.262707E+11 | 0.00 | 1.00 | 0.00 | 82723.02 | 67638.95 | 50868.42 | 21641.73 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.744723E+10 | 0.196839E+10 | 460.06 | 0.579198E+10 | 0.165525E+10 | 0.00 | 0.81 | 29-JAN-08:63 | 0.00 | 01-JAN-00:10 | 14192.97 | 29-JAN-08:63 | 10909.86 | 29-JAN-08:63 | 3435.25 | 29-JAN-14:00 | 3250.18 | 29-JAN-08:63 | 0.00 | 01-JAN-00:10 |
February | 0.834118E+10 | 0.221361E+10 | 430.08 | 0.637448E+10 | 0.196671E+10 | 0.00 | 1.00 | 06-FEB-08:62 | 0.00 | 01-FEB-00:05 | 27575.73 | 09-FEB-08:62 | 19253.27 | 09-FEB-08:62 | 8322.45 | 09-FEB-08:62 | 5889.44 | 09-FEB-08:62 | 0.00 | 01-FEB-00:05 |
March | 0.111793E+11 | 0.302224E+10 | 484.17 | 0.889352E+10 | 0.228577E+10 | 0.00 | 1.00 | 01-MAR-08:62 | 0.00 | 01-MAR-00:05 | 36434.11 | 02-MAR-08:62 | 32327.90 | 02-MAR-08:62 | 7331.14 | 29-MAR-07:03 | 8467.69 | 02-MAR-08:62 | 0.00 | 01-MAR-00:05 |
April | 0.150205E+11 | 0.411984E+10 | 478.02 | 0.116385E+11 | 0.338202E+10 | 0.00 | 1.00 | 03-APR-07:03 | 0.00 | 01-APR-00:05 | 37929.36 | 30-APR-07:02 | 32053.09 | 29-APR-07:02 | 11015.93 | 30-APR-07:02 | 8178.76 | 18-APR-07:02 | 0.00 | 01-APR-00:05 |
May | 0.215810E+11 | 0.608171E+10 | 500.52 | 0.165688E+11 | 0.501228E+10 | 0.00 | 1.00 | 01-MAY-07:02 | 0.00 | 01-MAY-00:10 | 39018.96 | 30-MAY-07:01 | 34562.95 | 10-MAY-07:02 | 13427.43 | 30-MAY-07:02 | 8992.65 | 23-MAY-07:01 | 0.00 | 01-MAY-00:10 |
June | 0.259437E+11 | 0.714442E+10 | 488.79 | 0.176916E+11 | 0.825205E+10 | 0.00 | 1.00 | 01-JUN-07:01 | 0.00 | 01-JUN-00:10 | 39956.61 | 19-JUN-07:01 | 32331.97 | 02-JUN-07:01 | 16506.51 | 19-JUN-07:02 | 9600.64 | 05-JUN-07:01 | 0.00 | 01-JUN-00:10 |
July | 0.310794E+11 | 0.862068E+10 | 503.26 | 0.203180E+11 | 0.107614E+11 | 0.00 | 1.00 | 01-JUL-07:01 | 0.00 | 01-JUL-00:03 | 40243.33 | 18-JUL-07:01 | 33836.01 | 04-JUL-07:01 | 17672.02 | 18-JUL-07:03 | 9510.58 | 15-JUL-07:03 | 0.00 | 01-JUL-00:03 |
August | 0.328684E+11 | 0.905049E+10 | 504.38 | 0.209146E+11 | 0.119538E+11 | 0.00 | 1.00 | 01-AUG-07:01 | 0.00 | 01-AUG-00:10 | 41133.42 | 08-AUG-07:01 | 31750.46 | 06-AUG-07:01 | 20924.61 | 08-AUG-07:12 | 9694.27 | 05-AUG-07:01 | 0.00 | 01-AUG-00:10 |
September | 0.278752E+11 | 0.745829E+10 | 487.80 | 0.178967E+11 | 0.997857E+10 | 0.00 | 1.00 | 01-SEP-07:01 | 0.00 | 01-SEP-00:03 | 39802.01 | 10-SEP-07:01 | 30484.43 | 02-SEP-07:01 | 15716.54 | 28-SEP-07:03 | 9241.27 | 02-SEP-07:01 | 0.00 | 01-SEP-00:03 |
October | 0.221677E+11 | 0.592845E+10 | 500.75 | 0.157505E+11 | 0.641717E+10 | 0.00 | 1.00 | 01-OCT-07:01 | 0.00 | 01-OCT-00:10 | 39851.94 | 08-OCT-07:01 | 32895.72 | 20-OCT-07:02 | 16027.95 | 08-OCT-07:02 | 8762.08 | 02-OCT-07:01 | 0.00 | 01-OCT-00:10 |
November | 0.158614E+11 | 0.418636E+10 | 478.16 | 0.115894E+11 | 0.427200E+10 | 0.00 | 1.00 | 01-NOV-07:02 | 0.00 | 01-NOV-00:10 | 38430.19 | 02-NOV-07:02 | 32203.51 | 05-NOV-07:02 | 10947.22 | 02-NOV-07:02 | 8466.60 | 20-NOV-08:62 | 0.00 | 01-NOV-00:10 |
December | 0.104062E+11 | 0.272320E+10 | 484.17 | 0.765463E+10 | 0.275158E+10 | 0.00 | 1.00 | 05-DEC-08:62 | 0.00 | 01-DEC-01:05 | 36792.13 | 12-DEC-08:62 | 28565.27 | 12-DEC-08:62 | 8226.86 | 12-DEC-08:62 | 7991.99 | 12-DEC-08:62 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.229771E+12 | 0.625177E+11 | 5800.16 | 0.161083E+12 | 0.686886E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.744723E+10 | 0.196839E+10 | 430.08 | 0.579198E+10 | 0.165525E+10 | 0.00 | 0.81 | 0.00 | 14192.97 | 10909.86 | 3435.25 | 3250.18 | 0.00 | |||||||
Maximum of Months | 0.328684E+11 | 0.905049E+10 | 504.38 | 0.209146E+11 | 0.119538E+11 | 0.00 | 1.00 | 0.00 | 41133.42 | 34562.95 | 20924.61 | 9694.27 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_3:3 COOLING COIL
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.499072E+10 | 0.132480E+10 | 310.56 | 0.384994E+10 | 0.114078E+10 | 0.00 | 0.94 | 30-JAN-07:03 | 0.00 | 01-JAN-00:10 | 17748.53 | 30-JAN-07:03 | 10687.55 | 30-JAN-07:03 | 7060.97 | 30-JAN-07:03 | 3809.18 | 30-JAN-07:03 | 0.00 | 01-JAN-00:10 |
February | 0.599433E+10 | 0.159717E+10 | 299.17 | 0.456487E+10 | 0.142947E+10 | 0.00 | 1.00 | 06-FEB-07:03 | 0.00 | 01-FEB-00:05 | 34836.86 | 09-FEB-07:03 | 20807.62 | 09-FEB-07:03 | 14029.24 | 09-FEB-07:03 | 7342.47 | 09-FEB-07:03 | 0.00 | 01-FEB-00:05 |
March | 0.851489E+10 | 0.231197E+10 | 348.82 | 0.679114E+10 | 0.172375E+10 | 0.00 | 1.00 | 01-MAR-07:03 | 0.00 | 01-MAR-00:05 | 37106.66 | 02-MAR-07:02 | 32487.66 | 28-MAR-06:02 | 15190.23 | 29-MAR-06:03 | 8635.38 | 02-MAR-07:02 | 0.00 | 01-MAR-00:05 |
April | 0.117665E+11 | 0.322899E+10 | 348.61 | 0.915175E+10 | 0.261471E+10 | 0.00 | 1.00 | 02-APR-07:03 | 0.00 | 01-APR-00:05 | 39837.97 | 30-APR-07:02 | 32352.38 | 29-APR-06:02 | 17225.41 | 30-APR-07:02 | 8411.79 | 17-APR-06:02 | 0.00 | 01-APR-00:05 |
May | 0.177148E+11 | 0.494475E+10 | 372.97 | 0.135764E+11 | 0.413839E+10 | 0.00 | 1.00 | 01-MAY-06:02 | 0.00 | 01-MAY-00:10 | 41394.46 | 01-MAY-06:02 | 33159.83 | 05-MAY-06:02 | 23677.52 | 01-MAY-06:02 | 9055.08 | 23-MAY-06:01 | 0.00 | 01-MAY-00:10 |
June | 0.216359E+11 | 0.589254E+10 | 366.04 | 0.146695E+11 | 0.696647E+10 | 0.00 | 1.00 | 01-JUN-06:01 | 0.00 | 01-JUN-00:10 | 41956.57 | 25-JUN-07:01 | 30924.19 | 01-JUN-06:01 | 25194.80 | 19-JUN-06:04 | 9416.96 | 29-JUN-06:03 | 0.00 | 01-JUN-00:10 |
July | 0.260128E+11 | 0.709482E+10 | 372.06 | 0.166682E+11 | 0.934458E+10 | 0.00 | 1.00 | 01-JUL-06:01 | 0.00 | 01-JUL-00:03 | 41678.87 | 06-JUL-06:01 | 33003.63 | 04-JUL-07:01 | 26977.27 | 31-JUL-06:04 | 9459.48 | 23-JUL-07:13 | 0.00 | 01-JUL-00:03 |
August | 0.280604E+11 | 0.760566E+10 | 381.56 | 0.175033E+11 | 0.105572E+11 | 0.00 | 1.00 | 01-AUG-06:01 | 0.00 | 01-AUG-00:10 | 41675.20 | 31-AUG-06:01 | 28038.45 | 16-AUG-06:01 | 25874.07 | 27-AUG-07:05 | 9680.26 | 06-AUG-07:13 | 0.00 | 01-AUG-00:10 |
September | 0.231143E+11 | 0.610053E+10 | 360.97 | 0.146669E+11 | 0.844747E+10 | 0.00 | 1.00 | 01-SEP-06:01 | 0.00 | 01-SEP-00:03 | 41993.81 | 25-SEP-06:01 | 25612.80 | 05-SEP-06:01 | 28739.99 | 11-SEP-06:01 | 9281.48 | 04-SEP-07:13 | 0.00 | 01-SEP-00:03 |
October | 0.181810E+11 | 0.479317E+10 | 367.86 | 0.127199E+11 | 0.546107E+10 | 0.00 | 1.00 | 01-OCT-07:01 | 0.00 | 01-OCT-00:10 | 41922.58 | 01-OCT-07:01 | 31269.93 | 20-OCT-06:02 | 26230.43 | 08-OCT-07:04 | 8747.53 | 05-OCT-06:01 | 0.00 | 01-OCT-00:10 |
November | 0.127672E+11 | 0.334593E+10 | 351.74 | 0.914922E+10 | 0.361797E+10 | 0.00 | 1.00 | 01-NOV-06:02 | 0.00 | 01-NOV-00:10 | 40478.88 | 03-NOV-06:02 | 30224.20 | 05-NOV-07:02 | 18616.93 | 03-NOV-06:02 | 8482.18 | 25-NOV-07:02 | 0.00 | 01-NOV-00:10 |
December | 0.757859E+10 | 0.198630E+10 | 338.48 | 0.550450E+10 | 0.207409E+10 | 0.00 | 1.00 | 05-DEC-07:03 | 0.00 | 01-DEC-00:10 | 38496.96 | 12-DEC-07:02 | 26785.45 | 12-DEC-07:02 | 13502.28 | 11-DEC-07:03 | 8282.34 | 12-DEC-07:02 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.186331E+12 | 0.502266E+11 | 4218.83 | 0.128816E+12 | 0.575159E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.499072E+10 | 0.132480E+10 | 299.17 | 0.384994E+10 | 0.114078E+10 | 0.00 | 0.94 | 0.00 | 17748.53 | 10687.55 | 7060.97 | 3809.18 | 0.00 | |||||||
Maximum of Months | 0.280604E+11 | 0.760566E+10 | 381.56 | 0.175033E+11 | 0.105572E+11 | 0.00 | 1.00 | 0.00 | 41993.81 | 33159.83 | 28739.99 | 9680.26 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_4:4 COOLING COIL
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.491079E+10 | 0.130507E+10 | 307.61 | 0.378448E+10 | 0.112631E+10 | 0.00 | 0.92 | 30-JAN-07:03 | 0.00 | 01-JAN-00:10 | 17275.03 | 30-JAN-07:03 | 10391.73 | 30-JAN-07:03 | 6883.30 | 30-JAN-07:03 | 3732.78 | 30-JAN-07:03 | 0.00 | 01-JAN-00:10 |
February | 0.594459E+10 | 0.158524E+10 | 297.92 | 0.452569E+10 | 0.141890E+10 | 0.00 | 1.00 | 06-FEB-07:03 | 0.00 | 01-FEB-00:05 | 34875.78 | 09-FEB-07:03 | 20827.14 | 09-FEB-07:03 | 14048.64 | 09-FEB-07:03 | 7350.58 | 09-FEB-07:03 | 0.00 | 01-FEB-00:05 |
March | 0.849090E+10 | 0.230674E+10 | 348.65 | 0.677106E+10 | 0.171984E+10 | 0.00 | 1.00 | 01-MAR-07:03 | 0.00 | 01-MAR-00:05 | 37187.44 | 02-MAR-07:02 | 33216.32 | 28-MAR-06:02 | 15367.18 | 29-MAR-06:03 | 8654.11 | 02-MAR-07:02 | 0.00 | 01-MAR-00:05 |
April | 0.117889E+11 | 0.323573E+10 | 348.68 | 0.917091E+10 | 0.261803E+10 | 0.00 | 1.00 | 02-APR-07:03 | 0.00 | 01-APR-00:05 | 39935.29 | 30-APR-07:02 | 32479.89 | 29-APR-06:02 | 17201.79 | 30-APR-07:02 | 8430.62 | 17-APR-06:02 | 0.00 | 01-APR-00:05 |
May | 0.178164E+11 | 0.497133E+10 | 373.19 | 0.136611E+11 | 0.415532E+10 | 0.00 | 1.00 | 01-MAY-06:02 | 0.00 | 01-MAY-00:10 | 41498.90 | 01-MAY-06:02 | 33289.40 | 05-MAY-06:02 | 23638.59 | 01-MAY-06:02 | 9074.89 | 23-MAY-06:01 | 0.00 | 01-MAY-00:10 |
June | 0.217600E+11 | 0.592486E+10 | 366.14 | 0.147680E+11 | 0.699202E+10 | 0.00 | 1.00 | 01-JUN-06:01 | 0.00 | 01-JUN-00:10 | 42047.31 | 25-JUN-07:01 | 31096.85 | 01-JUN-06:01 | 25136.15 | 19-JUN-06:05 | 9437.21 | 29-JUN-06:03 | 0.00 | 01-JUN-00:10 |
July | 0.261804E+11 | 0.713896E+10 | 372.12 | 0.168017E+11 | 0.937872E+10 | 0.00 | 1.00 | 01-JUL-06:01 | 0.00 | 01-JUL-00:03 | 41769.01 | 06-JUL-06:02 | 33194.87 | 04-JUL-07:01 | 26825.49 | 31-JUL-06:04 | 9480.03 | 23-JUL-07:13 | 0.00 | 01-JUL-00:03 |
August | 0.282278E+11 | 0.764977E+10 | 381.75 | 0.176359E+11 | 0.105919E+11 | 0.00 | 1.00 | 01-AUG-06:01 | 0.00 | 01-AUG-00:10 | 41765.33 | 31-AUG-06:01 | 28211.17 | 16-AUG-06:01 | 25833.25 | 27-AUG-07:05 | 9701.25 | 06-AUG-07:13 | 0.00 | 01-AUG-00:10 |
September | 0.232525E+11 | 0.613587E+10 | 361.15 | 0.147750E+11 | 0.847749E+10 | 0.00 | 1.00 | 01-SEP-06:01 | 0.00 | 01-SEP-00:03 | 42084.63 | 25-SEP-06:01 | 25929.38 | 05-SEP-06:01 | 28575.59 | 11-SEP-06:03 | 9301.57 | 04-SEP-07:13 | 0.00 | 01-SEP-00:03 |
October | 0.182897E+11 | 0.481956E+10 | 367.94 | 0.128063E+11 | 0.548335E+10 | 0.00 | 1.00 | 01-OCT-07:01 | 0.00 | 01-OCT-00:10 | 42013.25 | 01-OCT-07:02 | 31398.82 | 20-OCT-06:02 | 26289.93 | 08-OCT-07:05 | 8766.40 | 05-OCT-06:01 | 0.00 | 01-OCT-00:10 |
November | 0.127998E+11 | 0.335464E+10 | 351.82 | 0.917590E+10 | 0.362387E+10 | 0.00 | 1.00 | 01-NOV-06:02 | 0.00 | 01-NOV-00:10 | 40576.98 | 03-NOV-06:02 | 30353.95 | 05-NOV-07:02 | 18601.20 | 03-NOV-06:02 | 8500.90 | 25-NOV-07:02 | 0.00 | 01-NOV-00:10 |
December | 0.754376E+10 | 0.197837E+10 | 337.48 | 0.547747E+10 | 0.206629E+10 | 0.00 | 1.00 | 05-DEC-07:03 | 0.00 | 01-DEC-00:10 | 38581.85 | 12-DEC-07:02 | 26845.94 | 12-DEC-07:02 | 13555.09 | 11-DEC-07:03 | 8300.43 | 12-DEC-07:02 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.187006E+12 | 0.504061E+11 | 4214.44 | 0.129354E+12 | 0.576520E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.491079E+10 | 0.130507E+10 | 297.92 | 0.378448E+10 | 0.112631E+10 | 0.00 | 0.92 | 0.00 | 17275.03 | 10391.73 | 6883.30 | 3732.78 | 0.00 | |||||||
Maximum of Months | 0.282278E+11 | 0.764977E+10 | 381.75 | 0.176359E+11 | 0.105919E+11 | 0.00 | 1.00 | 0.00 | 42084.63 | 33289.40 | 28575.59 | 9701.25 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_5:5 COOLING COIL
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.464581E+10 | 0.123821E+10 | 303.47 | 0.356943E+10 | 0.107638E+10 | 0.00 | 0.83 | 30-JAN-07:03 | 0.00 | 01-JAN-00:10 | 15154.86 | 30-JAN-07:03 | 9069.60 | 30-JAN-07:03 | 6085.26 | 30-JAN-07:03 | 3365.81 | 30-JAN-07:03 | 0.00 | 01-JAN-00:10 |
February | 0.570493E+10 | 0.152522E+10 | 294.50 | 0.433633E+10 | 0.136860E+10 | 0.00 | 1.00 | 06-FEB-07:03 | 0.00 | 01-FEB-00:05 | 32180.40 | 09-FEB-07:03 | 19032.37 | 09-FEB-07:03 | 13148.03 | 09-FEB-07:03 | 6786.10 | 09-FEB-07:03 | 0.00 | 01-FEB-00:05 |
March | 0.823361E+10 | 0.224224E+10 | 346.23 | 0.655936E+10 | 0.167425E+10 | 0.00 | 1.00 | 01-MAR-07:03 | 0.00 | 01-MAR-00:05 | 36949.17 | 02-MAR-07:02 | 30996.62 | 28-MAR-06:02 | 14402.75 | 29-MAR-06:03 | 8602.12 | 02-MAR-07:02 | 0.00 | 01-MAR-00:05 |
April | 0.115574E+11 | 0.317762E+10 | 347.80 | 0.898125E+10 | 0.257612E+10 | 0.00 | 1.00 | 03-APR-06:02 | 0.00 | 01-APR-00:05 | 39694.80 | 30-APR-07:02 | 32141.06 | 29-APR-06:02 | 17215.35 | 30-APR-07:02 | 8381.16 | 17-APR-06:02 | 0.00 | 01-APR-00:05 |
May | 0.176222E+11 | 0.491998E+10 | 373.20 | 0.134961E+11 | 0.412618E+10 | 0.00 | 1.00 | 01-MAY-06:02 | 0.00 | 01-MAY-00:10 | 41252.32 | 01-MAY-06:02 | 32951.50 | 05-MAY-06:02 | 23597.36 | 01-MAY-06:02 | 9023.38 | 23-MAY-06:01 | 0.00 | 01-MAY-00:10 |
June | 0.215613E+11 | 0.587108E+10 | 365.77 | 0.146098E+11 | 0.695145E+10 | 0.00 | 1.00 | 01-JUN-06:01 | 0.00 | 01-JUN-00:10 | 41809.57 | 25-JUN-07:01 | 30754.29 | 01-JUN-06:01 | 25041.56 | 19-JUN-06:04 | 9383.98 | 29-JUN-06:03 | 0.00 | 01-JUN-00:10 |
July | 0.260082E+11 | 0.708951E+10 | 371.97 | 0.166663E+11 | 0.934186E+10 | 0.00 | 1.00 | 01-JUL-06:01 | 0.00 | 01-JUL-00:03 | 41532.84 | 06-JUL-06:01 | 32888.13 | 04-JUL-07:01 | 26745.51 | 31-JUL-06:04 | 9426.17 | 23-JUL-07:13 | 0.00 | 01-JUL-00:03 |
August | 0.280460E+11 | 0.759746E+10 | 381.44 | 0.174941E+11 | 0.105519E+11 | 0.00 | 1.00 | 01-AUG-06:01 | 0.00 | 01-AUG-00:10 | 41529.18 | 31-AUG-06:01 | 27924.25 | 16-AUG-06:01 | 25783.89 | 27-AUG-07:05 | 9646.89 | 06-AUG-07:13 | 0.00 | 01-AUG-00:10 |
September | 0.230691E+11 | 0.608661E+10 | 360.99 | 0.146329E+11 | 0.843613E+10 | 0.00 | 1.00 | 01-SEP-06:01 | 0.00 | 01-SEP-00:03 | 41846.68 | 25-SEP-06:03 | 25752.33 | 05-SEP-06:01 | 28497.57 | 11-SEP-06:03 | 9248.93 | 04-SEP-07:13 | 0.00 | 01-SEP-00:03 |
October | 0.181012E+11 | 0.477208E+10 | 368.14 | 0.126539E+11 | 0.544735E+10 | 0.00 | 1.00 | 01-OCT-07:01 | 0.00 | 01-OCT-00:10 | 41775.70 | 01-OCT-07:01 | 31099.32 | 20-OCT-06:02 | 26161.08 | 08-OCT-07:04 | 8716.90 | 05-OCT-06:01 | 0.00 | 01-OCT-00:10 |
November | 0.125814E+11 | 0.330159E+10 | 351.39 | 0.900175E+10 | 0.357967E+10 | 0.00 | 1.00 | 01-NOV-06:02 | 0.00 | 01-NOV-00:10 | 40334.77 | 03-NOV-06:02 | 30076.55 | 05-NOV-07:02 | 18655.33 | 03-NOV-06:02 | 8451.54 | 25-NOV-07:02 | 0.00 | 01-NOV-00:10 |
December | 0.728288E+10 | 0.191420E+10 | 334.64 | 0.527479E+10 | 0.200809E+10 | 0.00 | 1.00 | 05-DEC-07:03 | 0.00 | 01-DEC-00:10 | 38344.31 | 12-DEC-07:02 | 26550.81 | 12-DEC-07:02 | 12763.58 | 11-DEC-07:03 | 8251.35 | 12-DEC-07:02 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.184414E+12 | 0.497358E+11 | 4199.55 | 0.127276E+12 | 0.571380E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.464581E+10 | 0.123821E+10 | 294.50 | 0.356943E+10 | 0.107638E+10 | 0.00 | 0.83 | 0.00 | 15154.86 | 9069.60 | 6085.26 | 3365.81 | 0.00 | |||||||
Maximum of Months | 0.280460E+11 | 0.759746E+10 | 381.44 | 0.174941E+11 | 0.105519E+11 | 0.00 | 1.00 | 0.00 | 41846.68 | 32951.50 | 28497.57 | 9646.89 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_6:6 COOLING COIL
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.772933E+10 | 0.210099E+10 | 302.58 | 0.580407E+10 | 0.192526E+10 | 0.00 | 0.76 | 30-JAN-08:63 | 0.00 | 01-JAN-00:10 | 24272.51 | 30-JAN-08:63 | 14243.36 | 30-JAN-08:63 | 10029.15 | 30-JAN-08:63 | 5600.86 | 30-JAN-08:63 | 0.00 | 01-JAN-00:10 |
February | 0.979585E+10 | 0.266582E+10 | 290.36 | 0.730795E+10 | 0.248790E+10 | 0.00 | 1.00 | 06-FEB-08:62 | 0.00 | 01-FEB-00:05 | 50941.05 | 09-FEB-08:62 | 30507.52 | 06-FEB-08:62 | 20681.08 | 09-FEB-08:62 | 10945.12 | 09-FEB-08:62 | 0.00 | 01-FEB-00:05 |
March | 0.145777E+11 | 0.403446E+10 | 342.77 | 0.114268E+11 | 0.315090E+10 | 0.00 | 1.00 | 01-MAR-08:62 | 0.00 | 01-MAR-00:05 | 65726.87 | 02-MAR-08:62 | 53267.00 | 02-MAR-08:62 | 21006.07 | 29-MAR-07:03 | 15412.50 | 02-MAR-08:62 | 0.00 | 01-MAR-00:05 |
April | 0.208424E+11 | 0.580452E+10 | 339.80 | 0.159979E+11 | 0.484456E+10 | 0.00 | 1.00 | 03-APR-07:03 | 0.00 | 01-APR-00:05 | 70776.83 | 30-APR-08:62 | 57589.86 | 29-APR-07:02 | 31613.40 | 30-APR-08:62 | 15383.51 | 28-APR-07:02 | 0.00 | 01-APR-00:05 |
May | 0.322595E+11 | 0.910238E+10 | 363.91 | 0.244871E+11 | 0.777239E+10 | 0.00 | 1.00 | 01-MAY-07:02 | 0.00 | 01-MAY-00:10 | 73298.83 | 01-MAY-07:02 | 59314.93 | 11-MAY-07:01 | 42355.83 | 01-MAY-07:02 | 16939.05 | 28-MAY-08:61 | 0.00 | 01-MAY-00:10 |
June | 0.395592E+11 | 0.109014E+11 | 357.84 | 0.265772E+11 | 0.129820E+11 | 0.00 | 1.00 | 01-JUN-07:01 | 0.00 | 01-JUN-00:10 | 74183.37 | 25-JUN-08:61 | 54697.31 | 01-JUN-07:01 | 44085.69 | 19-JUN-07:05 | 17337.42 | 11-JUN-08:13 | 0.00 | 01-JUN-00:10 |
July | 0.475888E+11 | 0.131385E+11 | 360.62 | 0.303104E+11 | 0.172784E+11 | 0.00 | 1.00 | 01-JUL-07:01 | 0.00 | 01-JUL-00:03 | 73562.72 | 18-JUL-07:01 | 59377.29 | 04-JUL-08:61 | 46185.93 | 31-JUL-07:04 | 17646.74 | 23-JUL-08:12 | 0.00 | 01-JUL-00:03 |
August | 0.516378E+11 | 0.141633E+11 | 373.14 | 0.319616E+11 | 0.196762E+11 | 0.00 | 1.00 | 01-AUG-07:01 | 0.00 | 01-AUG-00:10 | 73619.52 | 08-AUG-07:03 | 49710.28 | 16-AUG-07:01 | 45501.21 | 27-AUG-08:08 | 17705.76 | 06-AUG-08:12 | 0.00 | 01-AUG-00:10 |
September | 0.423158E+11 | 0.113009E+11 | 350.90 | 0.265519E+11 | 0.157639E+11 | 0.00 | 1.00 | 01-SEP-07:01 | 0.00 | 01-SEP-00:03 | 74335.79 | 25-SEP-07:01 | 47073.87 | 02-SEP-07:01 | 50626.68 | 11-SEP-07:02 | 17219.65 | 04-SEP-08:13 | 0.00 | 01-SEP-00:03 |
October | 0.328527E+11 | 0.876395E+10 | 357.54 | 0.228265E+11 | 0.100262E+11 | 0.00 | 1.00 | 01-OCT-08:61 | 0.00 | 01-OCT-00:10 | 74115.13 | 02-OCT-07:01 | 55478.63 | 20-OCT-07:02 | 46216.47 | 08-OCT-08:05 | 16048.24 | 08-OCT-08:13 | 0.00 | 01-OCT-00:10 |
November | 0.226728E+11 | 0.602466E+10 | 342.84 | 0.159826E+11 | 0.669020E+10 | 0.00 | 1.00 | 01-NOV-07:02 | 0.00 | 01-NOV-00:10 | 70550.83 | 03-NOV-07:02 | 55132.23 | 19-NOV-09:02 | 29632.25 | 03-NOV-07:02 | 15427.63 | 20-NOV-08:62 | 0.00 | 01-NOV-00:10 |
December | 0.126289E+11 | 0.337383E+10 | 328.35 | 0.895853E+10 | 0.367040E+10 | 0.00 | 1.00 | 05-DEC-08:62 | 0.00 | 01-DEC-00:10 | 67750.65 | 12-DEC-08:62 | 47776.15 | 12-DEC-08:62 | 20975.17 | 11-DEC-08:62 | 14878.13 | 12-DEC-08:62 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.334461E+12 | 0.913748E+11 | 4110.67 | 0.228193E+12 | 0.106268E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.772933E+10 | 0.210099E+10 | 290.36 | 0.580407E+10 | 0.192526E+10 | 0.00 | 0.76 | 0.00 | 24272.51 | 14243.36 | 10029.15 | 5600.86 | 0.00 | |||||||
Maximum of Months | 0.516378E+11 | 0.141633E+11 | 373.14 | 0.319616E+11 | 0.196762E+11 | 0.00 | 1.00 | 0.00 | 74335.79 | 59377.29 | 50626.68 | 17705.76 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_7:7 COOLING COIL
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.398297E+10 | 0.106574E+10 | 303.17 | 0.299477E+10 | 0.988202E+09 | 0.00 | 0.72 | 30-JAN-08:63 | 0.00 | 01-JAN-00:10 | 11865.42 | 30-JAN-08:63 | 7038.16 | 28-JAN-14:00 | 4899.58 | 30-JAN-08:63 | 2729.08 | 30-JAN-08:63 | 0.00 | 01-JAN-00:10 |
February | 0.506478E+10 | 0.135718E+10 | 290.28 | 0.378437E+10 | 0.128041E+10 | 0.00 | 1.00 | 06-FEB-08:62 | 0.00 | 01-FEB-00:05 | 24499.33 | 09-FEB-08:62 | 15115.06 | 06-FEB-08:62 | 9976.31 | 09-FEB-08:62 | 5174.18 | 09-FEB-08:62 | 0.00 | 01-FEB-00:05 |
March | 0.755722E+10 | 0.206017E+10 | 343.41 | 0.593128E+10 | 0.162594E+10 | 0.00 | 1.00 | 01-MAR-08:62 | 0.00 | 01-MAR-00:05 | 34753.64 | 02-MAR-08:62 | 28151.30 | 02-MAR-08:62 | 10076.10 | 29-MAR-07:03 | 8008.18 | 02-MAR-08:62 | 0.00 | 01-MAR-00:05 |
April | 0.108435E+11 | 0.297532E+10 | 339.98 | 0.832523E+10 | 0.251823E+10 | 0.00 | 1.00 | 03-APR-07:03 | 0.00 | 01-APR-00:05 | 37459.75 | 30-APR-08:62 | 28871.87 | 29-APR-07:02 | 16798.90 | 30-APR-08:62 | 7886.10 | 30-APR-08:62 | 0.00 | 01-APR-00:05 |
May | 0.168082E+11 | 0.467542E+10 | 364.04 | 0.127517E+11 | 0.405655E+10 | 0.00 | 1.00 | 01-MAY-07:02 | 0.00 | 01-MAY-00:10 | 38817.66 | 01-MAY-07:02 | 31311.78 | 11-MAY-07:01 | 22504.93 | 01-MAY-07:02 | 8802.74 | 28-MAY-08:61 | 0.00 | 01-MAY-00:10 |
June | 0.205957E+11 | 0.559811E+10 | 357.77 | 0.138348E+11 | 0.676089E+10 | 0.00 | 1.00 | 01-JUN-07:01 | 0.00 | 01-JUN-00:10 | 39240.16 | 25-JUN-08:02 | 28963.34 | 01-JUN-07:01 | 23526.83 | 26-JUN-07:04 | 9010.51 | 11-JUN-08:13 | 0.00 | 01-JUN-00:10 |
July | 0.247874E+11 | 0.675076E+10 | 360.48 | 0.157865E+11 | 0.900091E+10 | 0.00 | 1.00 | 01-JUL-07:01 | 0.00 | 01-JUL-00:03 | 38911.86 | 18-JUL-07:01 | 31372.54 | 04-JUL-08:61 | 24716.35 | 31-JUL-07:02 | 9171.24 | 23-JUL-08:12 | 0.00 | 01-JUL-00:03 |
August | 0.268699E+11 | 0.727097E+10 | 373.13 | 0.166292E+11 | 0.102407E+11 | 0.00 | 1.00 | 01-AUG-07:01 | 0.00 | 01-AUG-00:10 | 38941.91 | 08-AUG-07:01 | 26266.08 | 16-AUG-07:01 | 24143.10 | 27-AUG-08:06 | 9200.25 | 06-AUG-08:12 | 0.00 | 01-AUG-00:10 |
September | 0.220273E+11 | 0.580174E+10 | 350.67 | 0.138273E+11 | 0.819998E+10 | 0.00 | 1.00 | 01-SEP-07:01 | 0.00 | 01-SEP-00:03 | 39320.78 | 25-SEP-07:01 | 24841.29 | 02-SEP-07:01 | 27047.57 | 11-SEP-07:01 | 8948.87 | 04-SEP-08:13 | 0.00 | 01-SEP-00:03 |
October | 0.170996E+11 | 0.449765E+10 | 358.69 | 0.118916E+11 | 0.520800E+10 | 0.00 | 1.00 | 01-OCT-08:61 | 0.00 | 01-OCT-00:10 | 39204.06 | 02-OCT-07:02 | 29349.97 | 20-OCT-07:02 | 24532.04 | 08-OCT-08:05 | 8340.10 | 08-OCT-08:13 | 0.00 | 01-OCT-00:10 |
November | 0.117883E+11 | 0.308663E+10 | 343.03 | 0.831807E+10 | 0.347018E+10 | 0.00 | 1.00 | 01-NOV-07:02 | 0.00 | 01-NOV-00:10 | 37292.80 | 03-NOV-07:02 | 29142.99 | 19-NOV-09:02 | 15585.46 | 03-NOV-07:02 | 8017.41 | 20-NOV-08:62 | 0.00 | 01-NOV-00:10 |
December | 0.654570E+10 | 0.172189E+10 | 328.94 | 0.464982E+10 | 0.189588E+10 | 0.00 | 1.00 | 05-DEC-08:62 | 0.00 | 01-DEC-00:10 | 33344.49 | 12-DEC-08:62 | 23504.02 | 12-DEC-08:62 | 10434.52 | 11-DEC-08:62 | 7196.38 | 12-DEC-08:62 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.173971E+12 | 0.468616E+11 | 4113.59 | 0.118725E+12 | 0.552459E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.398297E+10 | 0.106574E+10 | 290.28 | 0.299477E+10 | 0.988202E+09 | 0.00 | 0.72 | 0.00 | 11865.42 | 7038.16 | 4899.58 | 2729.08 | 0.00 | |||||||
Maximum of Months | 0.268699E+11 | 0.727097E+10 | 373.13 | 0.166292E+11 | 0.102407E+11 | 0.00 | 1.00 | 0.00 | 39320.78 | 31372.54 | 27047.57 | 9200.25 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_8:8 COOLING COIL
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.391573E+10 | 0.104844E+10 | 302.08 | 0.294140E+10 | 0.974326E+09 | 0.00 | 0.69 | 30-JAN-08:63 | 0.00 | 01-JAN-00:10 | 11342.89 | 30-JAN-08:63 | 6988.76 | 28-JAN-14:00 | 4692.41 | 30-JAN-08:63 | 2628.30 | 30-JAN-08:63 | 0.00 | 01-JAN-00:10 |
February | 0.500186E+10 | 0.134107E+10 | 288.61 | 0.373558E+10 | 0.126629E+10 | 0.00 | 1.00 | 06-FEB-08:62 | 0.00 | 01-FEB-00:05 | 23869.73 | 09-FEB-08:62 | 14707.11 | 06-FEB-08:62 | 9760.57 | 09-FEB-08:62 | 5041.73 | 09-FEB-08:62 | 0.00 | 01-FEB-00:05 |
March | 0.749170E+10 | 0.204322E+10 | 342.83 | 0.587816E+10 | 0.161354E+10 | 0.00 | 1.00 | 01-MAR-08:62 | 0.00 | 01-MAR-00:05 | 34642.18 | 02-MAR-08:62 | 28033.70 | 02-MAR-08:62 | 9886.86 | 29-MAR-07:03 | 7982.84 | 02-MAR-08:62 | 0.00 | 01-MAR-00:05 |
April | 0.107891E+11 | 0.296084E+10 | 340.02 | 0.828142E+10 | 0.250765E+10 | 0.00 | 1.00 | 03-APR-07:03 | 0.00 | 01-APR-00:05 | 37341.41 | 30-APR-08:62 | 28604.46 | 29-APR-07:02 | 16766.77 | 30-APR-08:62 | 7861.42 | 30-APR-08:62 | 0.00 | 01-APR-00:05 |
May | 0.167635E+11 | 0.466217E+10 | 363.99 | 0.127148E+11 | 0.404873E+10 | 0.00 | 1.00 | 01-MAY-07:02 | 0.00 | 01-MAY-00:10 | 38694.98 | 01-MAY-07:02 | 31197.46 | 11-MAY-07:01 | 22450.50 | 01-MAY-07:02 | 8775.29 | 28-MAY-08:61 | 0.00 | 01-MAY-00:10 |
June | 0.205520E+11 | 0.558493E+10 | 357.77 | 0.138007E+11 | 0.675135E+10 | 0.00 | 1.00 | 01-JUN-07:01 | 0.00 | 01-JUN-00:10 | 39117.73 | 25-JUN-08:02 | 28854.80 | 01-JUN-07:01 | 23455.06 | 26-JUN-07:04 | 8982.35 | 11-JUN-08:13 | 0.00 | 01-JUN-00:10 |
July | 0.247499E+11 | 0.673855E+10 | 360.44 | 0.157577E+11 | 0.899217E+10 | 0.00 | 1.00 | 01-JUL-07:01 | 0.00 | 01-JUL-00:03 | 38790.46 | 18-JUL-07:01 | 31269.78 | 04-JUL-08:61 | 24631.85 | 31-JUL-07:02 | 9142.58 | 23-JUL-08:12 | 0.00 | 01-JUL-00:03 |
August | 0.268319E+11 | 0.725841E+10 | 373.12 | 0.166002E+11 | 0.102316E+11 | 0.00 | 1.00 | 01-AUG-07:01 | 0.00 | 01-AUG-00:10 | 38820.41 | 08-AUG-07:01 | 26173.20 | 16-AUG-07:01 | 24070.04 | 27-AUG-08:06 | 9171.72 | 06-AUG-08:12 | 0.00 | 01-AUG-00:10 |
September | 0.219886E+11 | 0.579007E+10 | 350.56 | 0.137979E+11 | 0.819065E+10 | 0.00 | 1.00 | 01-SEP-07:01 | 0.00 | 01-SEP-00:03 | 39198.10 | 25-SEP-07:01 | 24745.37 | 02-SEP-07:01 | 26961.81 | 11-SEP-07:01 | 8920.96 | 04-SEP-08:13 | 0.00 | 01-SEP-00:03 |
October | 0.170577E+11 | 0.448564E+10 | 358.76 | 0.118583E+11 | 0.519937E+10 | 0.00 | 1.00 | 01-OCT-08:61 | 0.00 | 01-OCT-00:10 | 39081.75 | 02-OCT-07:01 | 29240.25 | 20-OCT-07:02 | 24464.00 | 08-OCT-08:05 | 8314.08 | 08-OCT-08:13 | 0.00 | 01-OCT-00:10 |
November | 0.117377E+11 | 0.307350E+10 | 342.95 | 0.827840E+10 | 0.345934E+10 | 0.00 | 1.00 | 01-NOV-07:02 | 0.00 | 01-NOV-00:10 | 37178.32 | 03-NOV-07:02 | 28827.06 | 19-NOV-09:02 | 15571.51 | 03-NOV-07:02 | 7992.22 | 20-NOV-08:62 | 0.00 | 01-NOV-00:10 |
December | 0.648332E+10 | 0.170614E+10 | 328.44 | 0.460223E+10 | 0.188109E+10 | 0.00 | 1.00 | 05-DEC-08:62 | 0.00 | 01-DEC-00:10 | 32831.92 | 12-DEC-08:62 | 23110.82 | 12-DEC-08:62 | 10270.80 | 11-DEC-08:62 | 7086.25 | 12-DEC-08:62 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.173363E+12 | 0.466930E+11 | 4109.55 | 0.118247E+12 | 0.551161E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.391573E+10 | 0.104844E+10 | 288.61 | 0.294140E+10 | 0.974326E+09 | 0.00 | 0.69 | 0.00 | 11342.89 | 6988.76 | 4692.41 | 2628.30 | 0.00 | |||||||
Maximum of Months | 0.268319E+11 | 0.725841E+10 | 373.12 | 0.166002E+11 | 0.102316E+11 | 0.00 | 1.00 | 0.00 | 39198.10 | 31269.78 | 26961.81 | 9171.72 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_9:9 COOLING COIL
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.377883E+10 | 0.101387E+10 | 298.25 | 0.283304E+10 | 0.945785E+09 | 0.00 | 0.60 | 30-JAN-08:63 | 0.00 | 01-JAN-00:10 | 9670.96 | 30-JAN-08:63 | 6908.00 | 28-JAN-14:00 | 4019.46 | 30-JAN-08:63 | 2306.71 | 29-JAN-16:00 | 0.00 | 01-JAN-00:10 |
February | 0.488020E+10 | 0.131118E+10 | 284.53 | 0.364199E+10 | 0.123821E+10 | 0.00 | 1.00 | 06-FEB-08:62 | 0.00 | 01-FEB-00:05 | 21935.37 | 09-FEB-08:62 | 13391.78 | 06-FEB-08:62 | 9078.59 | 09-FEB-08:62 | 4635.62 | 09-FEB-08:62 | 0.00 | 01-FEB-00:05 |
March | 0.738805E+10 | 0.201871E+10 | 340.66 | 0.579471E+10 | 0.159334E+10 | 0.00 | 1.00 | 02-MAR-08:62 | 0.00 | 01-MAR-00:05 | 34867.18 | 02-MAR-08:62 | 28164.67 | 02-MAR-08:62 | 9304.57 | 29-MAR-07:03 | 8035.83 | 02-MAR-08:62 | 0.00 | 01-MAR-00:05 |
April | 0.107644E+11 | 0.295784E+10 | 339.32 | 0.826353E+10 | 0.250091E+10 | 0.00 | 1.00 | 03-APR-07:03 | 0.00 | 01-APR-00:05 | 37586.45 | 30-APR-08:62 | 28166.69 | 29-APR-07:02 | 16891.01 | 30-APR-08:62 | 7914.30 | 30-APR-08:62 | 0.00 | 01-APR-00:05 |
May | 0.168690E+11 | 0.469311E+10 | 363.95 | 0.128032E+11 | 0.406582E+10 | 0.00 | 1.00 | 01-MAY-07:02 | 0.00 | 01-MAY-00:10 | 38953.41 | 01-MAY-07:02 | 31411.84 | 11-MAY-07:01 | 22612.96 | 01-MAY-07:02 | 8834.76 | 28-MAY-08:61 | 0.00 | 01-MAY-00:10 |
June | 0.207094E+11 | 0.562981E+10 | 357.72 | 0.139261E+11 | 0.678336E+10 | 0.00 | 1.00 | 01-JUN-07:01 | 0.00 | 01-JUN-00:10 | 39383.04 | 25-JUN-08:02 | 29080.86 | 01-JUN-07:01 | 23572.75 | 26-JUN-07:04 | 9043.33 | 11-JUN-08:13 | 0.00 | 01-JUN-00:10 |
July | 0.249847E+11 | 0.680555E+10 | 360.49 | 0.159439E+11 | 0.904078E+10 | 0.00 | 1.00 | 01-JUL-07:01 | 0.00 | 01-JUL-00:03 | 39053.55 | 18-JUL-07:01 | 31548.15 | 04-JUL-08:61 | 24680.38 | 31-JUL-07:04 | 9204.62 | 23-JUL-08:12 | 0.00 | 01-JUL-00:03 |
August | 0.271141E+11 | 0.733776E+10 | 373.08 | 0.168224E+11 | 0.102917E+11 | 0.00 | 1.00 | 01-AUG-07:01 | 0.00 | 01-AUG-00:10 | 39083.71 | 08-AUG-07:01 | 26466.98 | 16-AUG-07:01 | 24191.95 | 27-AUG-08:06 | 9234.05 | 06-AUG-08:12 | 0.00 | 01-AUG-00:10 |
September | 0.221944E+11 | 0.584633E+10 | 350.68 | 0.139582E+11 | 0.823617E+10 | 0.00 | 1.00 | 01-SEP-07:01 | 0.00 | 01-SEP-00:03 | 39463.96 | 25-SEP-07:01 | 25008.79 | 02-SEP-07:01 | 27011.36 | 11-SEP-07:01 | 8981.47 | 04-SEP-08:13 | 0.00 | 01-SEP-00:03 |
October | 0.172000E+11 | 0.452353E+10 | 359.13 | 0.119720E+11 | 0.522798E+10 | 0.00 | 1.00 | 01-OCT-08:61 | 0.00 | 01-OCT-00:10 | 39346.82 | 02-OCT-07:01 | 29447.65 | 20-OCT-07:02 | 24602.22 | 08-OCT-08:05 | 8370.47 | 08-OCT-08:13 | 0.00 | 01-OCT-00:10 |
November | 0.117717E+11 | 0.308440E+10 | 342.98 | 0.830594E+10 | 0.346579E+10 | 0.00 | 1.00 | 01-NOV-07:02 | 0.00 | 01-NOV-00:10 | 37422.82 | 03-NOV-07:02 | 28275.62 | 19-NOV-09:02 | 15644.67 | 03-NOV-07:02 | 8045.88 | 20-NOV-08:62 | 0.00 | 01-NOV-00:10 |
December | 0.638855E+10 | 0.168381E+10 | 326.10 | 0.453112E+10 | 0.185743E+10 | 0.00 | 1.00 | 11-DEC-08:62 | 0.00 | 01-DEC-00:10 | 31589.41 | 12-DEC-08:62 | 22160.02 | 12-DEC-08:62 | 9825.65 | 11-DEC-08:62 | 6820.04 | 12-DEC-08:62 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.174043E+12 | 0.469059E+11 | 4096.89 | 0.118796E+12 | 0.552472E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.377883E+10 | 0.101387E+10 | 284.53 | 0.283304E+10 | 0.945785E+09 | 0.00 | 0.60 | 0.00 | 9670.96 | 6908.00 | 4019.46 | 2306.71 | 0.00 | |||||||
Maximum of Months | 0.271141E+11 | 0.733776E+10 | 373.08 | 0.168224E+11 | 0.102917E+11 | 0.00 | 1.00 | 0.00 | 39463.96 | 31548.15 | 27011.36 | 9234.05 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_10:10 COOLING COIL
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.418304E+10 | 0.114600E+10 | 297.22 | 0.319213E+10 | 0.990913E+09 | 0.00 | 0.55 | 29-JAN-16:00 | 0.00 | 01-JAN-00:10 | 9893.94 | 29-JAN-16:00 | 7641.24 | 28-JAN-14:00 | 3285.07 | 29-JAN-16:00 | 2605.88 | 29-JAN-16:00 | 0.00 | 01-JAN-00:10 |
February | 0.534326E+10 | 0.146983E+10 | 281.33 | 0.405586E+10 | 0.128739E+10 | 0.00 | 0.87 | 09-FEB-08:62 | 0.00 | 01-FEB-00:05 | 17846.40 | 09-FEB-08:62 | 11090.18 | 06-FEB-15:10 | 7805.82 | 09-FEB-08:62 | 3996.86 | 09-FEB-08:62 | 0.00 | 01-FEB-00:05 |
March | 0.813206E+10 | 0.227645E+10 | 336.14 | 0.647481E+10 | 0.165725E+10 | 0.00 | 1.00 | 02-MAR-08:62 | 0.00 | 01-MAR-00:05 | 39856.50 | 02-MAR-08:62 | 35005.35 | 02-MAR-08:62 | 7263.11 | 29-MAR-07:03 | 9418.06 | 02-MAR-08:62 | 0.00 | 01-MAR-00:05 |
April | 0.121040E+11 | 0.340977E+10 | 339.42 | 0.944157E+10 | 0.266247E+10 | 0.00 | 1.00 | 03-APR-07:03 | 0.00 | 01-APR-00:05 | 44177.13 | 30-APR-08:62 | 29327.24 | 29-APR-07:02 | 21540.35 | 30-APR-08:62 | 9378.41 | 30-APR-08:62 | 0.00 | 01-APR-00:05 |
May | 0.193248E+11 | 0.551222E+10 | 365.44 | 0.149259E+11 | 0.439890E+10 | 0.00 | 1.00 | 01-MAY-07:02 | 0.00 | 01-MAY-00:10 | 45642.69 | 30-MAY-07:01 | 37228.51 | 11-MAY-07:01 | 25767.23 | 01-MAY-07:02 | 10447.54 | 28-MAY-08:61 | 0.00 | 01-MAY-00:10 |
June | 0.236890E+11 | 0.660859E+10 | 359.11 | 0.163057E+11 | 0.738335E+10 | 0.00 | 1.00 | 01-JUN-07:01 | 0.00 | 01-JUN-00:10 | 45733.94 | 25-JUN-08:02 | 33337.69 | 01-JUN-07:01 | 28155.33 | 19-JUN-07:05 | 10689.56 | 11-JUN-08:13 | 0.00 | 01-JUN-00:10 |
July | 0.285763E+11 | 0.800207E+10 | 362.15 | 0.187406E+11 | 0.983568E+10 | 0.00 | 1.00 | 01-JUL-07:01 | 0.00 | 01-JUL-00:03 | 45386.34 | 26-JUL-07:01 | 37454.12 | 04-JUL-08:61 | 29822.42 | 05-JUL-07:05 | 10871.56 | 23-JUL-08:12 | 0.00 | 01-JUL-00:03 |
August | 0.311951E+11 | 0.868224E+10 | 375.31 | 0.199846E+11 | 0.112105E+11 | 0.00 | 1.00 | 01-AUG-07:01 | 0.00 | 01-AUG-00:10 | 45386.34 | 08-AUG-07:07 | 31827.41 | 06-AUG-08:61 | 29324.41 | 21-AUG-07:06 | 10910.65 | 06-AUG-08:12 | 0.00 | 01-AUG-00:10 |
September | 0.254533E+11 | 0.688631E+10 | 352.43 | 0.165047E+11 | 0.894853E+10 | 0.00 | 1.00 | 01-SEP-07:01 | 0.00 | 01-SEP-00:03 | 45827.91 | 25-SEP-07:01 | 29289.11 | 26-SEP-07:01 | 31323.26 | 11-SEP-07:02 | 10615.87 | 04-SEP-08:13 | 0.00 | 01-SEP-00:03 |
October | 0.197971E+11 | 0.533379E+10 | 360.29 | 0.141012E+11 | 0.569588E+10 | 0.00 | 1.00 | 01-OCT-08:61 | 0.00 | 01-OCT-00:10 | 45691.87 | 02-OCT-07:02 | 34104.89 | 20-OCT-07:02 | 29230.30 | 08-OCT-08:05 | 9893.72 | 08-OCT-08:13 | 0.00 | 01-OCT-00:10 |
November | 0.134158E+11 | 0.360030E+10 | 344.00 | 0.967890E+10 | 0.373685E+10 | 0.00 | 1.00 | 01-NOV-07:02 | 0.00 | 01-NOV-00:10 | 43989.89 | 03-NOV-07:02 | 33007.36 | 05-NOV-08:62 | 19602.37 | 03-NOV-07:02 | 9541.15 | 20-NOV-08:62 | 0.00 | 01-NOV-00:10 |
December | 0.706445E+10 | 0.190655E+10 | 324.69 | 0.511125E+10 | 0.195320E+10 | 0.00 | 1.00 | 11-DEC-08:62 | 0.00 | 01-DEC-00:10 | 32899.93 | 12-DEC-08:62 | 22207.26 | 12-DEC-08:62 | 10692.67 | 12-DEC-08:62 | 7201.67 | 12-DEC-08:62 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.198278E+12 | 0.548341E+11 | 4097.53 | 0.138517E+12 | 0.597609E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.418304E+10 | 0.114600E+10 | 281.33 | 0.319213E+10 | 0.990913E+09 | 0.00 | 0.55 | 0.00 | 9893.94 | 7641.24 | 3285.07 | 2605.88 | 0.00 | |||||||
Maximum of Months | 0.311951E+11 | 0.868224E+10 | 375.31 | 0.199846E+11 | 0.112105E+11 | 0.00 | 1.00 | 0.00 | 45827.91 | 37454.12 | 31323.26 | 10910.65 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 51.06 | 24.00 | 27.05 | 83.36 | 35.26 | 0.00 | 0.00 | 0.00 |
February | 47.95 | 19.61 | 28.33 | 83.22 | 29.70 | 0.00 | 0.00 | 0.00 |
March | 39.46 | 10.71 | 28.75 | 76.57 | 22.66 | 0.00 | 0.00 | 0.00 |
April | 31.02 | 3.29 | 27.73 | 71.79 | 13.64 | 0.00 | 0.00 | 0.00 |
May | 26.28 | 0.40 | 25.87 | 81.20 | 3.34 | 0.00 | 0.00 | 0.00 |
June | 24.75 | 0.03 | 24.72 | 85.17 | 0.86 | 0.00 | 0.00 | 0.00 |
July | 24.75 | 0.21 | 24.54 | 100.21 | 0.02 | 0.00 | 0.00 | 0.00 |
August | 28.70 | 2.03 | 26.67 | 110.79 | 0.01 | 0.00 | 0.00 | 0.00 |
September | 37.84 | 8.67 | 29.17 | 111.97 | 1.58 | 0.00 | 0.00 | 0.00 |
October | 49.55 | 19.70 | 29.85 | 117.06 | 5.96 | 0.00 | 0.00 | 0.00 |
November | 54.66 | 26.35 | 28.31 | 108.44 | 15.97 | 0.00 | 0.00 | 0.00 |
December | 50.74 | 25.06 | 25.68 | 87.91 | 29.30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.84 | 11.63 | 27.21 | 93.21 | 13.11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 24.75 | 0.03 | 24.54 | 71.79 | 0.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 54.66 | 26.35 | 29.85 | 117.06 | 35.26 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 51.06 | 24.00 | 27.05 | 83.36 | 35.26 | 0.00 | 0.00 | 0.00 |
February | 47.95 | 19.61 | 28.33 | 83.22 | 29.70 | 0.00 | 0.00 | 0.00 |
March | 39.46 | 10.71 | 28.75 | 76.57 | 22.66 | 0.00 | 0.00 | 0.00 |
April | 31.02 | 3.29 | 27.73 | 71.79 | 13.64 | 0.00 | 0.00 | 0.00 |
May | 26.28 | 0.40 | 25.87 | 81.20 | 3.34 | 0.00 | 0.00 | 0.00 |
June | 24.75 | 0.03 | 24.72 | 85.17 | 0.86 | 0.00 | 0.00 | 0.00 |
July | 24.75 | 0.21 | 24.54 | 100.21 | 0.02 | 0.00 | 0.00 | 0.00 |
August | 28.70 | 2.03 | 26.67 | 110.79 | 0.01 | 0.00 | 0.00 | 0.00 |
September | 37.84 | 8.67 | 29.17 | 111.97 | 1.58 | 0.00 | 0.00 | 0.00 |
October | 49.55 | 19.70 | 29.85 | 117.06 | 5.96 | 0.00 | 0.00 | 0.00 |
November | 54.66 | 26.35 | 28.31 | 108.44 | 15.97 | 0.00 | 0.00 | 0.00 |
December | 50.74 | 25.06 | 25.68 | 87.91 | 29.30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.84 | 11.63 | 27.21 | 93.21 | 13.11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 24.75 | 0.03 | 24.54 | 71.79 | 0.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 54.66 | 26.35 | 29.85 | 117.06 | 35.26 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 51.06 | 24.00 | 27.05 | 83.36 | 35.26 | 0.00 | 0.00 | 0.00 |
February | 47.95 | 19.61 | 28.33 | 83.22 | 29.70 | 0.00 | 0.00 | 0.00 |
March | 39.46 | 10.71 | 28.75 | 76.57 | 22.66 | 0.00 | 0.00 | 0.00 |
April | 31.02 | 3.29 | 27.73 | 71.79 | 13.64 | 0.00 | 0.00 | 0.00 |
May | 26.28 | 0.40 | 25.87 | 81.20 | 3.34 | 0.00 | 0.00 | 0.00 |
June | 24.75 | 0.03 | 24.72 | 85.17 | 0.86 | 0.00 | 0.00 | 0.00 |
July | 24.75 | 0.21 | 24.54 | 100.21 | 0.02 | 0.00 | 0.00 | 0.00 |
August | 28.70 | 2.03 | 26.67 | 110.79 | 0.01 | 0.00 | 0.00 | 0.00 |
September | 37.84 | 8.67 | 29.17 | 111.97 | 1.58 | 0.00 | 0.00 | 0.00 |
October | 49.55 | 19.70 | 29.85 | 117.06 | 5.96 | 0.00 | 0.00 | 0.00 |
November | 54.66 | 26.35 | 28.31 | 108.44 | 15.97 | 0.00 | 0.00 | 0.00 |
December | 50.74 | 25.06 | 25.68 | 87.91 | 29.30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.84 | 11.63 | 27.21 | 93.21 | 13.11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 24.75 | 0.03 | 24.54 | 71.79 | 0.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 54.66 | 26.35 | 29.85 | 117.06 | 35.26 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 51.06 | 24.00 | 27.05 | 83.36 | 35.26 | 0.00 | 0.00 | 0.00 |
February | 47.95 | 19.61 | 28.33 | 83.22 | 29.70 | 0.00 | 0.00 | 0.00 |
March | 39.46 | 10.71 | 28.75 | 76.57 | 22.66 | 0.00 | 0.00 | 0.00 |
April | 31.02 | 3.29 | 27.73 | 71.79 | 13.64 | 0.00 | 0.00 | 0.00 |
May | 26.28 | 0.40 | 25.87 | 81.20 | 3.34 | 0.00 | 0.00 | 0.00 |
June | 24.75 | 0.03 | 24.72 | 85.17 | 0.86 | 0.00 | 0.00 | 0.00 |
July | 24.75 | 0.21 | 24.54 | 100.21 | 0.02 | 0.00 | 0.00 | 0.00 |
August | 28.70 | 2.03 | 26.67 | 110.79 | 0.01 | 0.00 | 0.00 | 0.00 |
September | 37.84 | 8.67 | 29.17 | 111.97 | 1.58 | 0.00 | 0.00 | 0.00 |
October | 49.55 | 19.70 | 29.85 | 117.06 | 5.96 | 0.00 | 0.00 | 0.00 |
November | 54.66 | 26.35 | 28.31 | 108.44 | 15.97 | 0.00 | 0.00 | 0.00 |
December | 50.74 | 25.06 | 25.68 | 87.91 | 29.30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.84 | 11.63 | 27.21 | 93.21 | 13.11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 24.75 | 0.03 | 24.54 | 71.79 | 0.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 54.66 | 26.35 | 29.85 | 117.06 | 35.26 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 61.38 | 28.86 | 32.52 | 100.31 | 42.06 | 0.00 | 0.00 | 0.00 |
February | 57.64 | 23.58 | 34.06 | 100.07 | 35.45 | 0.00 | 0.00 | 0.00 |
March | 47.44 | 12.88 | 34.56 | 91.89 | 27.12 | 0.00 | 0.00 | 0.00 |
April | 37.29 | 3.95 | 33.34 | 85.86 | 16.40 | 0.00 | 0.00 | 0.00 |
May | 31.59 | 0.48 | 31.10 | 96.56 | 4.06 | 0.00 | 0.00 | 0.00 |
June | 29.75 | 0.04 | 29.71 | 101.04 | 1.08 | 0.00 | 0.00 | 0.00 |
July | 29.75 | 0.25 | 29.49 | 118.94 | 0.03 | 0.00 | 0.00 | 0.00 |
August | 34.50 | 2.44 | 32.06 | 131.63 | 0.02 | 0.00 | 0.00 | 0.00 |
September | 45.50 | 10.43 | 35.07 | 133.44 | 1.94 | 0.00 | 0.00 | 0.00 |
October | 59.56 | 23.68 | 35.88 | 139.95 | 7.23 | 0.00 | 0.00 | 0.00 |
November | 65.71 | 31.68 | 34.03 | 130.03 | 19.22 | 0.00 | 0.00 | 0.00 |
December | 61.00 | 30.13 | 30.87 | 105.65 | 35.01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 46.69 | 13.98 | 32.71 | 111.36 | 15.71 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 29.75 | 0.04 | 29.49 | 85.86 | 0.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 65.71 | 31.68 | 35.88 | 139.95 | 42.06 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 61.38 | 28.86 | 32.52 | 100.31 | 42.06 | 0.00 | 0.00 | 0.00 |
February | 57.64 | 23.58 | 34.06 | 100.07 | 35.45 | 0.00 | 0.00 | 0.00 |
March | 47.44 | 12.88 | 34.56 | 91.89 | 27.12 | 0.00 | 0.00 | 0.00 |
April | 37.29 | 3.95 | 33.34 | 85.86 | 16.40 | 0.00 | 0.00 | 0.00 |
May | 31.59 | 0.48 | 31.10 | 96.56 | 4.06 | 0.00 | 0.00 | 0.00 |
June | 29.75 | 0.04 | 29.71 | 101.04 | 1.08 | 0.00 | 0.00 | 0.00 |
July | 29.75 | 0.25 | 29.49 | 118.94 | 0.03 | 0.00 | 0.00 | 0.00 |
August | 34.50 | 2.44 | 32.06 | 131.63 | 0.02 | 0.00 | 0.00 | 0.00 |
September | 45.50 | 10.43 | 35.07 | 133.44 | 1.94 | 0.00 | 0.00 | 0.00 |
October | 59.56 | 23.68 | 35.88 | 139.95 | 7.23 | 0.00 | 0.00 | 0.00 |
November | 65.71 | 31.68 | 34.03 | 130.03 | 19.22 | 0.00 | 0.00 | 0.00 |
December | 61.00 | 30.13 | 30.87 | 105.65 | 35.01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 46.69 | 13.98 | 32.71 | 111.36 | 15.71 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 29.75 | 0.04 | 29.49 | 85.86 | 0.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 65.71 | 31.68 | 35.88 | 139.95 | 42.06 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 51.06 | 24.00 | 27.05 | 82.88 | 35.97 | 0.00 | 0.00 | 0.00 |
February | 47.95 | 19.61 | 28.33 | 82.90 | 30.32 | 0.00 | 0.00 | 0.00 |
March | 39.46 | 10.71 | 28.75 | 76.52 | 23.09 | 0.00 | 0.00 | 0.00 |
April | 31.02 | 3.29 | 27.73 | 72.15 | 13.85 | 0.00 | 0.00 | 0.00 |
May | 26.28 | 0.40 | 25.87 | 82.38 | 3.30 | 0.00 | 0.00 | 0.00 |
June | 24.75 | 0.03 | 24.72 | 86.85 | 0.77 | 0.00 | 0.00 | 0.00 |
July | 24.75 | 0.21 | 24.54 | 102.37 | 0.01 | 0.00 | 0.00 | 0.00 |
August | 28.70 | 2.03 | 26.67 | 113.24 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 37.84 | 8.67 | 29.17 | 113.66 | 1.44 | 0.00 | 0.00 | 0.00 |
October | 49.55 | 19.70 | 29.85 | 118.07 | 5.70 | 0.00 | 0.00 | 0.00 |
November | 54.66 | 26.35 | 28.31 | 108.77 | 15.83 | 0.00 | 0.00 | 0.00 |
December | 50.74 | 25.06 | 25.68 | 87.70 | 29.64 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.84 | 11.63 | 27.21 | 94.03 | 13.25 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 24.75 | 0.03 | 24.54 | 72.15 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 54.66 | 26.35 | 29.85 | 118.07 | 35.97 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 51.06 | 24.00 | 27.05 | 82.88 | 35.97 | 0.00 | 0.00 | 0.00 |
February | 47.95 | 19.61 | 28.33 | 82.90 | 30.32 | 0.00 | 0.00 | 0.00 |
March | 39.46 | 10.71 | 28.75 | 76.52 | 23.09 | 0.00 | 0.00 | 0.00 |
April | 31.02 | 3.29 | 27.73 | 72.15 | 13.85 | 0.00 | 0.00 | 0.00 |
May | 26.28 | 0.40 | 25.87 | 82.38 | 3.30 | 0.00 | 0.00 | 0.00 |
June | 24.75 | 0.03 | 24.72 | 86.85 | 0.77 | 0.00 | 0.00 | 0.00 |
July | 24.75 | 0.21 | 24.54 | 102.37 | 0.01 | 0.00 | 0.00 | 0.00 |
August | 28.70 | 2.03 | 26.67 | 113.24 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 37.84 | 8.67 | 29.17 | 113.66 | 1.44 | 0.00 | 0.00 | 0.00 |
October | 49.55 | 19.70 | 29.85 | 118.07 | 5.70 | 0.00 | 0.00 | 0.00 |
November | 54.66 | 26.35 | 28.31 | 108.77 | 15.83 | 0.00 | 0.00 | 0.00 |
December | 50.74 | 25.06 | 25.68 | 87.70 | 29.64 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.84 | 11.63 | 27.21 | 94.03 | 13.25 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 24.75 | 0.03 | 24.54 | 72.15 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 54.66 | 26.35 | 29.85 | 118.07 | 35.97 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 61.38 | 28.86 | 32.52 | 99.77 | 42.88 | 0.00 | 0.00 | 0.00 |
February | 57.64 | 23.58 | 34.06 | 99.71 | 36.17 | 0.00 | 0.00 | 0.00 |
March | 47.44 | 12.88 | 34.56 | 91.84 | 27.64 | 0.00 | 0.00 | 0.00 |
April | 37.29 | 3.95 | 33.34 | 86.28 | 16.65 | 0.00 | 0.00 | 0.00 |
May | 31.59 | 0.48 | 31.10 | 97.95 | 4.02 | 0.00 | 0.00 | 0.00 |
June | 29.75 | 0.04 | 29.71 | 102.99 | 0.97 | 0.00 | 0.00 | 0.00 |
July | 29.75 | 0.25 | 29.49 | 121.48 | 0.02 | 0.00 | 0.00 | 0.00 |
August | 34.50 | 2.44 | 32.06 | 134.50 | 0.01 | 0.00 | 0.00 | 0.00 |
September | 45.50 | 10.43 | 35.07 | 135.45 | 1.77 | 0.00 | 0.00 | 0.00 |
October | 59.56 | 23.68 | 35.88 | 141.16 | 6.93 | 0.00 | 0.00 | 0.00 |
November | 65.71 | 31.68 | 34.03 | 130.45 | 19.04 | 0.00 | 0.00 | 0.00 |
December | 61.00 | 30.13 | 30.87 | 105.43 | 35.41 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 46.69 | 13.98 | 32.71 | 112.34 | 15.86 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 29.75 | 0.04 | 29.49 | 86.28 | 0.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 65.71 | 31.68 | 35.88 | 141.16 | 42.88 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 51.06 | 24.00 | 27.05 | 82.97 | 36.80 | 0.00 | 0.00 | 0.00 |
February | 47.95 | 19.61 | 28.33 | 82.90 | 31.39 | 0.00 | 0.00 | 0.00 |
March | 39.46 | 10.71 | 28.75 | 76.33 | 24.40 | 0.00 | 0.00 | 0.00 |
April | 31.02 | 3.29 | 27.73 | 71.32 | 15.44 | 0.00 | 0.00 | 0.00 |
May | 26.28 | 0.40 | 25.87 | 79.36 | 4.05 | 0.00 | 0.00 | 0.00 |
June | 24.75 | 0.03 | 24.72 | 83.08 | 1.10 | 0.00 | 0.00 | 0.00 |
July | 24.75 | 0.21 | 24.54 | 97.44 | 0.04 | 0.00 | 0.00 | 0.00 |
August | 28.70 | 2.03 | 26.67 | 108.51 | 0.02 | 0.00 | 0.00 | 0.00 |
September | 37.84 | 8.67 | 29.17 | 109.73 | 1.82 | 0.00 | 0.00 | 0.00 |
October | 49.55 | 19.70 | 29.85 | 115.81 | 7.13 | 0.00 | 0.00 | 0.00 |
November | 54.66 | 26.35 | 28.31 | 108.42 | 17.88 | 0.00 | 0.00 | 0.00 |
December | 50.74 | 25.06 | 25.68 | 87.73 | 31.06 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.84 | 11.63 | 27.21 | 92.03 | 14.18 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 24.75 | 0.03 | 24.54 | 71.32 | 0.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 54.66 | 26.35 | 29.85 | 115.81 | 36.80 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 51.06 | 24.00 | 27.05 | 82.97 | 36.80 | 0.00 | 0.00 | 0.00 |
February | 47.95 | 19.61 | 28.33 | 82.90 | 31.39 | 0.00 | 0.00 | 0.00 |
March | 39.46 | 10.71 | 28.75 | 76.33 | 24.40 | 0.00 | 0.00 | 0.00 |
April | 31.02 | 3.29 | 27.73 | 71.32 | 15.44 | 0.00 | 0.00 | 0.00 |
May | 26.28 | 0.40 | 25.87 | 79.36 | 4.05 | 0.00 | 0.00 | 0.00 |
June | 24.75 | 0.03 | 24.72 | 83.08 | 1.10 | 0.00 | 0.00 | 0.00 |
July | 24.75 | 0.21 | 24.54 | 97.44 | 0.04 | 0.00 | 0.00 | 0.00 |
August | 28.70 | 2.03 | 26.67 | 108.51 | 0.02 | 0.00 | 0.00 | 0.00 |
September | 37.84 | 8.67 | 29.17 | 109.73 | 1.82 | 0.00 | 0.00 | 0.00 |
October | 49.55 | 19.70 | 29.85 | 115.81 | 7.13 | 0.00 | 0.00 | 0.00 |
November | 54.66 | 26.35 | 28.31 | 108.42 | 17.88 | 0.00 | 0.00 | 0.00 |
December | 50.74 | 25.06 | 25.68 | 87.73 | 31.06 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.84 | 11.63 | 27.21 | 92.03 | 14.18 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 24.75 | 0.03 | 24.54 | 71.32 | 0.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 54.66 | 26.35 | 29.85 | 115.81 | 36.80 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 61.04 | 28.70 | 32.34 | 99.34 | 43.60 | 0.00 | 0.00 | 0.00 |
February | 57.32 | 23.45 | 33.88 | 99.17 | 37.21 | 0.00 | 0.00 | 0.00 |
March | 47.18 | 12.81 | 34.37 | 91.12 | 29.01 | 0.00 | 0.00 | 0.00 |
April | 37.09 | 3.93 | 33.15 | 84.87 | 18.43 | 0.00 | 0.00 | 0.00 |
May | 31.42 | 0.48 | 30.93 | 93.92 | 4.89 | 0.00 | 0.00 | 0.00 |
June | 29.59 | 0.04 | 29.55 | 98.07 | 1.37 | 0.00 | 0.00 | 0.00 |
July | 29.59 | 0.25 | 29.33 | 115.07 | 0.06 | 0.00 | 0.00 | 0.00 |
August | 34.32 | 2.43 | 31.88 | 128.27 | 0.02 | 0.00 | 0.00 | 0.00 |
September | 45.25 | 10.37 | 34.88 | 130.15 | 2.23 | 0.00 | 0.00 | 0.00 |
October | 59.24 | 23.55 | 35.69 | 137.80 | 8.61 | 0.00 | 0.00 | 0.00 |
November | 65.35 | 31.50 | 33.85 | 129.34 | 21.35 | 0.00 | 0.00 | 0.00 |
December | 60.66 | 29.97 | 30.70 | 104.89 | 36.85 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 46.44 | 13.91 | 32.53 | 109.40 | 16.87 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 29.59 | 0.04 | 29.33 | 84.87 | 0.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 65.35 | 31.50 | 35.69 | 137.80 | 43.60 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 51.06 | 24.00 | 27.05 | 83.06 | 36.56 | 0.00 | 0.00 | 0.00 |
February | 47.95 | 19.61 | 28.33 | 82.95 | 31.24 | 0.00 | 0.00 | 0.00 |
March | 39.46 | 10.71 | 28.75 | 76.35 | 24.35 | 0.00 | 0.00 | 0.00 |
April | 31.02 | 3.29 | 27.73 | 71.29 | 15.54 | 0.00 | 0.00 | 0.00 |
May | 26.28 | 0.40 | 25.87 | 79.13 | 4.22 | 0.00 | 0.00 | 0.00 |
June | 24.75 | 0.03 | 24.72 | 82.71 | 1.21 | 0.00 | 0.00 | 0.00 |
July | 24.75 | 0.21 | 24.54 | 96.83 | 0.06 | 0.00 | 0.00 | 0.00 |
August | 28.70 | 2.03 | 26.67 | 107.91 | 0.02 | 0.00 | 0.00 | 0.00 |
September | 37.84 | 8.67 | 29.17 | 109.34 | 1.95 | 0.00 | 0.00 | 0.00 |
October | 49.55 | 19.70 | 29.85 | 115.67 | 7.41 | 0.00 | 0.00 | 0.00 |
November | 54.66 | 26.35 | 28.31 | 108.39 | 18.01 | 0.00 | 0.00 | 0.00 |
December | 50.74 | 25.06 | 25.68 | 87.75 | 30.98 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.84 | 11.63 | 27.21 | 91.84 | 14.21 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 24.75 | 0.03 | 24.54 | 71.29 | 0.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 54.66 | 26.35 | 29.85 | 115.67 | 36.56 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 51.06 | 24.00 | 27.05 | 83.06 | 36.56 | 0.00 | 0.00 | 0.00 |
February | 47.95 | 19.61 | 28.33 | 82.95 | 31.24 | 0.00 | 0.00 | 0.00 |
March | 39.46 | 10.71 | 28.75 | 76.35 | 24.35 | 0.00 | 0.00 | 0.00 |
April | 31.02 | 3.29 | 27.73 | 71.29 | 15.54 | 0.00 | 0.00 | 0.00 |
May | 26.28 | 0.40 | 25.87 | 79.13 | 4.22 | 0.00 | 0.00 | 0.00 |
June | 24.75 | 0.03 | 24.72 | 82.71 | 1.21 | 0.00 | 0.00 | 0.00 |
July | 24.75 | 0.21 | 24.54 | 96.83 | 0.06 | 0.00 | 0.00 | 0.00 |
August | 28.70 | 2.03 | 26.67 | 107.91 | 0.02 | 0.00 | 0.00 | 0.00 |
September | 37.84 | 8.67 | 29.17 | 109.34 | 1.95 | 0.00 | 0.00 | 0.00 |
October | 49.55 | 19.70 | 29.85 | 115.67 | 7.41 | 0.00 | 0.00 | 0.00 |
November | 54.66 | 26.35 | 28.31 | 108.39 | 18.01 | 0.00 | 0.00 | 0.00 |
December | 50.74 | 25.06 | 25.68 | 87.75 | 30.98 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.84 | 11.63 | 27.21 | 91.84 | 14.21 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 24.75 | 0.03 | 24.54 | 71.29 | 0.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 54.66 | 26.35 | 29.85 | 115.67 | 36.56 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 61.04 | 28.70 | 32.34 | 99.44 | 43.32 | 0.00 | 0.00 | 0.00 |
February | 57.32 | 23.45 | 33.88 | 99.23 | 37.04 | 0.00 | 0.00 | 0.00 |
March | 47.18 | 12.81 | 34.37 | 91.14 | 28.96 | 0.00 | 0.00 | 0.00 |
April | 37.09 | 3.93 | 33.15 | 84.84 | 18.56 | 0.00 | 0.00 | 0.00 |
May | 31.42 | 0.48 | 30.93 | 93.65 | 5.10 | 0.00 | 0.00 | 0.00 |
June | 29.59 | 0.04 | 29.55 | 97.64 | 1.51 | 0.00 | 0.00 | 0.00 |
July | 29.59 | 0.25 | 29.33 | 114.36 | 0.08 | 0.00 | 0.00 | 0.00 |
August | 34.32 | 2.43 | 31.88 | 127.56 | 0.03 | 0.00 | 0.00 | 0.00 |
September | 45.25 | 10.37 | 34.88 | 129.69 | 2.38 | 0.00 | 0.00 | 0.00 |
October | 59.24 | 23.55 | 35.69 | 137.64 | 8.94 | 0.00 | 0.00 | 0.00 |
November | 65.35 | 31.50 | 33.85 | 129.30 | 21.51 | 0.00 | 0.00 | 0.00 |
December | 60.66 | 29.97 | 30.70 | 104.92 | 36.76 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 46.44 | 13.91 | 32.53 | 109.19 | 16.92 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 29.59 | 0.04 | 29.33 | 84.84 | 0.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 65.35 | 31.50 | 35.69 | 137.64 | 43.32 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 51.06 | 24.00 | 27.05 | 83.26 | 36.10 | 0.00 | 0.00 | 0.00 |
February | 47.95 | 19.61 | 28.33 | 83.10 | 30.83 | 0.00 | 0.00 | 0.00 |
March | 39.46 | 10.71 | 28.75 | 76.49 | 23.96 | 0.00 | 0.00 | 0.00 |
April | 31.02 | 3.29 | 27.73 | 71.42 | 15.21 | 0.00 | 0.00 | 0.00 |
May | 26.28 | 0.40 | 25.87 | 79.35 | 4.06 | 0.00 | 0.00 | 0.00 |
June | 24.75 | 0.03 | 24.72 | 82.99 | 1.13 | 0.00 | 0.00 | 0.00 |
July | 24.75 | 0.21 | 24.54 | 97.12 | 0.05 | 0.00 | 0.00 | 0.00 |
August | 28.70 | 2.03 | 26.67 | 108.23 | 0.02 | 0.00 | 0.00 | 0.00 |
September | 37.84 | 8.67 | 29.17 | 109.56 | 1.85 | 0.00 | 0.00 | 0.00 |
October | 49.55 | 19.70 | 29.85 | 115.80 | 7.19 | 0.00 | 0.00 | 0.00 |
November | 54.66 | 26.35 | 28.31 | 108.50 | 17.70 | 0.00 | 0.00 | 0.00 |
December | 50.74 | 25.06 | 25.68 | 87.89 | 30.60 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.84 | 11.63 | 27.21 | 92.04 | 13.98 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 24.75 | 0.03 | 24.54 | 71.42 | 0.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 54.66 | 26.35 | 29.85 | 115.80 | 36.10 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 51.06 | 24.00 | 27.05 | 83.26 | 36.10 | 0.00 | 0.00 | 0.00 |
February | 47.95 | 19.61 | 28.33 | 83.10 | 30.83 | 0.00 | 0.00 | 0.00 |
March | 39.46 | 10.71 | 28.75 | 76.49 | 23.96 | 0.00 | 0.00 | 0.00 |
April | 31.02 | 3.29 | 27.73 | 71.42 | 15.21 | 0.00 | 0.00 | 0.00 |
May | 26.28 | 0.40 | 25.87 | 79.35 | 4.06 | 0.00 | 0.00 | 0.00 |
June | 24.75 | 0.03 | 24.72 | 82.99 | 1.13 | 0.00 | 0.00 | 0.00 |
July | 24.75 | 0.21 | 24.54 | 97.12 | 0.05 | 0.00 | 0.00 | 0.00 |
August | 28.70 | 2.03 | 26.67 | 108.23 | 0.02 | 0.00 | 0.00 | 0.00 |
September | 37.84 | 8.67 | 29.17 | 109.56 | 1.85 | 0.00 | 0.00 | 0.00 |
October | 49.55 | 19.70 | 29.85 | 115.80 | 7.19 | 0.00 | 0.00 | 0.00 |
November | 54.66 | 26.35 | 28.31 | 108.50 | 17.70 | 0.00 | 0.00 | 0.00 |
December | 50.74 | 25.06 | 25.68 | 87.89 | 30.60 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.84 | 11.63 | 27.21 | 92.04 | 13.98 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 24.75 | 0.03 | 24.54 | 71.42 | 0.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 54.66 | 26.35 | 29.85 | 115.80 | 36.10 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 61.04 | 28.70 | 32.34 | 99.68 | 42.78 | 0.00 | 0.00 | 0.00 |
February | 57.32 | 23.45 | 33.88 | 99.42 | 36.55 | 0.00 | 0.00 | 0.00 |
March | 47.18 | 12.81 | 34.37 | 91.31 | 28.50 | 0.00 | 0.00 | 0.00 |
April | 37.09 | 3.93 | 33.15 | 84.99 | 18.17 | 0.00 | 0.00 | 0.00 |
May | 31.42 | 0.48 | 30.93 | 93.90 | 4.91 | 0.00 | 0.00 | 0.00 |
June | 29.59 | 0.04 | 29.55 | 97.97 | 1.41 | 0.00 | 0.00 | 0.00 |
July | 29.59 | 0.25 | 29.33 | 114.71 | 0.07 | 0.00 | 0.00 | 0.00 |
August | 34.32 | 2.43 | 31.88 | 127.93 | 0.02 | 0.00 | 0.00 | 0.00 |
September | 45.25 | 10.37 | 34.88 | 129.96 | 2.27 | 0.00 | 0.00 | 0.00 |
October | 59.24 | 23.55 | 35.69 | 137.79 | 8.68 | 0.00 | 0.00 | 0.00 |
November | 65.35 | 31.50 | 33.85 | 129.43 | 21.14 | 0.00 | 0.00 | 0.00 |
December | 60.66 | 29.97 | 30.70 | 105.08 | 36.31 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 46.44 | 13.91 | 32.53 | 109.42 | 16.64 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 29.59 | 0.04 | 29.33 | 84.99 | 0.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 65.35 | 31.50 | 35.69 | 137.79 | 42.78 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 51.06 | 24.00 | 27.05 | 83.72 | 34.93 | 0.00 | 0.00 | 0.00 |
February | 47.95 | 19.61 | 28.33 | 83.45 | 29.72 | 0.00 | 0.00 | 0.00 |
March | 39.46 | 10.71 | 28.75 | 76.74 | 22.88 | 0.00 | 0.00 | 0.00 |
April | 31.02 | 3.29 | 27.73 | 71.53 | 14.29 | 0.00 | 0.00 | 0.00 |
May | 26.28 | 0.40 | 25.87 | 79.57 | 3.67 | 0.00 | 0.00 | 0.00 |
June | 24.75 | 0.03 | 24.72 | 83.26 | 0.93 | 0.00 | 0.00 | 0.00 |
July | 24.75 | 0.21 | 24.54 | 97.27 | 0.04 | 0.00 | 0.00 | 0.00 |
August | 28.70 | 2.03 | 26.67 | 108.50 | 0.01 | 0.00 | 0.00 | 0.00 |
September | 37.84 | 8.67 | 29.17 | 109.74 | 1.66 | 0.00 | 0.00 | 0.00 |
October | 49.55 | 19.70 | 29.85 | 115.88 | 6.64 | 0.00 | 0.00 | 0.00 |
November | 54.66 | 26.35 | 28.31 | 108.49 | 16.76 | 0.00 | 0.00 | 0.00 |
December | 50.74 | 25.06 | 25.68 | 88.13 | 29.53 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.84 | 11.63 | 27.21 | 92.25 | 13.34 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 24.75 | 0.03 | 24.54 | 71.53 | 0.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 54.66 | 26.35 | 29.85 | 115.88 | 34.93 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 51.06 | 24.00 | 27.05 | 83.72 | 34.93 | 0.00 | 0.00 | 0.00 |
February | 47.95 | 19.61 | 28.33 | 83.45 | 29.72 | 0.00 | 0.00 | 0.00 |
March | 39.46 | 10.71 | 28.75 | 76.74 | 22.88 | 0.00 | 0.00 | 0.00 |
April | 31.02 | 3.29 | 27.73 | 71.53 | 14.29 | 0.00 | 0.00 | 0.00 |
May | 26.28 | 0.40 | 25.87 | 79.57 | 3.67 | 0.00 | 0.00 | 0.00 |
June | 24.75 | 0.03 | 24.72 | 83.26 | 0.93 | 0.00 | 0.00 | 0.00 |
July | 24.75 | 0.21 | 24.54 | 97.27 | 0.04 | 0.00 | 0.00 | 0.00 |
August | 28.70 | 2.03 | 26.67 | 108.50 | 0.01 | 0.00 | 0.00 | 0.00 |
September | 37.84 | 8.67 | 29.17 | 109.74 | 1.66 | 0.00 | 0.00 | 0.00 |
October | 49.55 | 19.70 | 29.85 | 115.88 | 6.64 | 0.00 | 0.00 | 0.00 |
November | 54.66 | 26.35 | 28.31 | 108.49 | 16.76 | 0.00 | 0.00 | 0.00 |
December | 50.74 | 25.06 | 25.68 | 88.13 | 29.53 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.84 | 11.63 | 27.21 | 92.25 | 13.34 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 24.75 | 0.03 | 24.54 | 71.53 | 0.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 54.66 | 26.35 | 29.85 | 115.88 | 34.93 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 51.06 | 24.00 | 27.05 | 83.72 | 34.93 | 0.00 | 0.00 | 0.00 |
February | 47.95 | 19.61 | 28.33 | 83.45 | 29.72 | 0.00 | 0.00 | 0.00 |
March | 39.46 | 10.71 | 28.75 | 76.74 | 22.88 | 0.00 | 0.00 | 0.00 |
April | 31.02 | 3.29 | 27.73 | 71.53 | 14.29 | 0.00 | 0.00 | 0.00 |
May | 26.28 | 0.40 | 25.87 | 79.57 | 3.67 | 0.00 | 0.00 | 0.00 |
June | 24.75 | 0.03 | 24.72 | 83.26 | 0.93 | 0.00 | 0.00 | 0.00 |
July | 24.75 | 0.21 | 24.54 | 97.27 | 0.04 | 0.00 | 0.00 | 0.00 |
August | 28.70 | 2.03 | 26.67 | 108.50 | 0.01 | 0.00 | 0.00 | 0.00 |
September | 37.84 | 8.67 | 29.17 | 109.74 | 1.66 | 0.00 | 0.00 | 0.00 |
October | 49.55 | 19.70 | 29.85 | 115.88 | 6.64 | 0.00 | 0.00 | 0.00 |
November | 54.66 | 26.35 | 28.31 | 108.49 | 16.76 | 0.00 | 0.00 | 0.00 |
December | 50.74 | 25.06 | 25.68 | 88.13 | 29.53 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.84 | 11.63 | 27.21 | 92.25 | 13.34 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 24.75 | 0.03 | 24.54 | 71.53 | 0.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 54.66 | 26.35 | 29.85 | 115.88 | 34.93 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 51.06 | 24.00 | 27.05 | 83.72 | 34.93 | 0.00 | 0.00 | 0.00 |
February | 47.95 | 19.61 | 28.33 | 83.45 | 29.72 | 0.00 | 0.00 | 0.00 |
March | 39.46 | 10.71 | 28.75 | 76.74 | 22.88 | 0.00 | 0.00 | 0.00 |
April | 31.02 | 3.29 | 27.73 | 71.53 | 14.29 | 0.00 | 0.00 | 0.00 |
May | 26.28 | 0.40 | 25.87 | 79.57 | 3.67 | 0.00 | 0.00 | 0.00 |
June | 24.75 | 0.03 | 24.72 | 83.26 | 0.93 | 0.00 | 0.00 | 0.00 |
July | 24.75 | 0.21 | 24.54 | 97.27 | 0.04 | 0.00 | 0.00 | 0.00 |
August | 28.70 | 2.03 | 26.67 | 108.50 | 0.01 | 0.00 | 0.00 | 0.00 |
September | 37.84 | 8.67 | 29.17 | 109.74 | 1.66 | 0.00 | 0.00 | 0.00 |
October | 49.55 | 19.70 | 29.85 | 115.88 | 6.64 | 0.00 | 0.00 | 0.00 |
November | 54.66 | 26.35 | 28.31 | 108.49 | 16.76 | 0.00 | 0.00 | 0.00 |
December | 50.74 | 25.06 | 25.68 | 88.13 | 29.53 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.84 | 11.63 | 27.21 | 92.25 | 13.34 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 24.75 | 0.03 | 24.54 | 71.53 | 0.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 54.66 | 26.35 | 29.85 | 115.88 | 34.93 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 61.04 | 28.70 | 32.34 | 100.20 | 41.41 | 0.00 | 0.00 | 0.00 |
February | 57.32 | 23.45 | 33.88 | 99.81 | 35.25 | 0.00 | 0.00 | 0.00 |
March | 47.18 | 12.81 | 34.37 | 91.60 | 27.22 | 0.00 | 0.00 | 0.00 |
April | 37.09 | 3.93 | 33.15 | 85.12 | 17.06 | 0.00 | 0.00 | 0.00 |
May | 31.42 | 0.48 | 30.93 | 94.20 | 4.43 | 0.00 | 0.00 | 0.00 |
June | 29.59 | 0.04 | 29.55 | 98.33 | 1.16 | 0.00 | 0.00 | 0.00 |
July | 29.59 | 0.25 | 29.33 | 114.94 | 0.06 | 0.00 | 0.00 | 0.00 |
August | 34.32 | 2.43 | 31.88 | 128.31 | 0.01 | 0.00 | 0.00 | 0.00 |
September | 45.25 | 10.37 | 34.88 | 130.20 | 2.03 | 0.00 | 0.00 | 0.00 |
October | 59.24 | 23.55 | 35.69 | 137.88 | 8.01 | 0.00 | 0.00 | 0.00 |
November | 65.35 | 31.50 | 33.85 | 129.42 | 20.02 | 0.00 | 0.00 | 0.00 |
December | 60.66 | 29.97 | 30.70 | 105.35 | 35.06 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 46.44 | 13.91 | 32.53 | 109.68 | 15.88 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 29.59 | 0.04 | 29.33 | 85.12 | 0.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 65.35 | 31.50 | 35.69 | 137.88 | 41.41 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 61.04 | 28.70 | 32.34 | 100.20 | 41.41 | 0.00 | 0.00 | 0.00 |
February | 57.32 | 23.45 | 33.88 | 99.81 | 35.25 | 0.00 | 0.00 | 0.00 |
March | 47.18 | 12.81 | 34.37 | 91.60 | 27.22 | 0.00 | 0.00 | 0.00 |
April | 37.09 | 3.93 | 33.15 | 85.12 | 17.06 | 0.00 | 0.00 | 0.00 |
May | 31.42 | 0.48 | 30.93 | 94.20 | 4.43 | 0.00 | 0.00 | 0.00 |
June | 29.59 | 0.04 | 29.55 | 98.33 | 1.16 | 0.00 | 0.00 | 0.00 |
July | 29.59 | 0.25 | 29.33 | 114.94 | 0.06 | 0.00 | 0.00 | 0.00 |
August | 34.32 | 2.43 | 31.88 | 128.31 | 0.01 | 0.00 | 0.00 | 0.00 |
September | 45.25 | 10.37 | 34.88 | 130.20 | 2.03 | 0.00 | 0.00 | 0.00 |
October | 59.24 | 23.55 | 35.69 | 137.88 | 8.01 | 0.00 | 0.00 | 0.00 |
November | 65.35 | 31.50 | 33.85 | 129.42 | 20.02 | 0.00 | 0.00 | 0.00 |
December | 60.66 | 29.97 | 30.70 | 105.35 | 35.06 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 46.44 | 13.91 | 32.53 | 109.68 | 15.88 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 29.59 | 0.04 | 29.33 | 85.12 | 0.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 65.35 | 31.50 | 35.69 | 137.88 | 41.41 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 51.06 | 24.00 | 27.05 | 83.58 | 34.78 | 0.00 | 0.00 | 0.00 |
February | 47.95 | 19.61 | 28.33 | 83.35 | 29.50 | 0.00 | 0.00 | 0.00 |
March | 39.46 | 10.71 | 28.75 | 76.76 | 22.59 | 0.00 | 0.00 | 0.00 |
April | 31.02 | 3.29 | 27.73 | 71.74 | 13.95 | 0.00 | 0.00 | 0.00 |
May | 26.28 | 0.40 | 25.87 | 80.29 | 3.47 | 0.00 | 0.00 | 0.00 |
June | 24.75 | 0.03 | 24.72 | 84.27 | 0.80 | 0.00 | 0.00 | 0.00 |
July | 24.75 | 0.21 | 24.54 | 98.44 | 0.04 | 0.00 | 0.00 | 0.00 |
August | 28.70 | 2.03 | 26.67 | 109.73 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 37.84 | 8.67 | 29.17 | 110.57 | 1.53 | 0.00 | 0.00 | 0.00 |
October | 49.55 | 19.70 | 29.85 | 116.27 | 6.30 | 0.00 | 0.00 | 0.00 |
November | 54.66 | 26.35 | 28.31 | 108.58 | 16.38 | 0.00 | 0.00 | 0.00 |
December | 50.74 | 25.06 | 25.68 | 88.05 | 29.29 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.84 | 11.63 | 27.21 | 92.70 | 13.14 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 24.75 | 0.03 | 24.54 | 71.74 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 54.66 | 26.35 | 29.85 | 116.27 | 34.78 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 51.06 | 24.00 | 27.05 | 83.58 | 34.78 | 0.00 | 0.00 | 0.00 |
February | 47.95 | 19.61 | 28.33 | 83.35 | 29.50 | 0.00 | 0.00 | 0.00 |
March | 39.46 | 10.71 | 28.75 | 76.76 | 22.59 | 0.00 | 0.00 | 0.00 |
April | 31.02 | 3.29 | 27.73 | 71.74 | 13.95 | 0.00 | 0.00 | 0.00 |
May | 26.28 | 0.40 | 25.87 | 80.29 | 3.47 | 0.00 | 0.00 | 0.00 |
June | 24.75 | 0.03 | 24.72 | 84.27 | 0.80 | 0.00 | 0.00 | 0.00 |
July | 24.75 | 0.21 | 24.54 | 98.44 | 0.04 | 0.00 | 0.00 | 0.00 |
August | 28.70 | 2.03 | 26.67 | 109.73 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 37.84 | 8.67 | 29.17 | 110.57 | 1.53 | 0.00 | 0.00 | 0.00 |
October | 49.55 | 19.70 | 29.85 | 116.27 | 6.30 | 0.00 | 0.00 | 0.00 |
November | 54.66 | 26.35 | 28.31 | 108.58 | 16.38 | 0.00 | 0.00 | 0.00 |
December | 50.74 | 25.06 | 25.68 | 88.05 | 29.29 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.84 | 11.63 | 27.21 | 92.70 | 13.14 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 24.75 | 0.03 | 24.54 | 71.74 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 54.66 | 26.35 | 29.85 | 116.27 | 34.78 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 61.04 | 28.70 | 32.34 | 100.07 | 41.22 | 0.00 | 0.00 | 0.00 |
February | 57.32 | 23.45 | 33.88 | 99.72 | 34.99 | 0.00 | 0.00 | 0.00 |
March | 47.18 | 12.81 | 34.37 | 91.64 | 26.88 | 0.00 | 0.00 | 0.00 |
April | 37.09 | 3.93 | 33.15 | 85.37 | 16.67 | 0.00 | 0.00 | 0.00 |
May | 31.42 | 0.48 | 30.93 | 95.02 | 4.20 | 0.00 | 0.00 | 0.00 |
June | 29.59 | 0.04 | 29.55 | 99.47 | 1.01 | 0.00 | 0.00 | 0.00 |
July | 29.59 | 0.25 | 29.33 | 116.27 | 0.05 | 0.00 | 0.00 | 0.00 |
August | 34.32 | 2.43 | 31.88 | 129.71 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 45.25 | 10.37 | 34.88 | 131.14 | 1.87 | 0.00 | 0.00 | 0.00 |
October | 59.24 | 23.55 | 35.69 | 138.34 | 7.61 | 0.00 | 0.00 | 0.00 |
November | 65.35 | 31.50 | 33.85 | 129.54 | 19.58 | 0.00 | 0.00 | 0.00 |
December | 60.66 | 29.97 | 30.70 | 105.28 | 34.77 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 46.44 | 13.91 | 32.53 | 110.20 | 15.64 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 29.59 | 0.04 | 29.33 | 85.37 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 65.35 | 31.50 | 35.69 | 138.34 | 41.22 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 51.06 | 24.00 | 27.05 | 83.66 | 34.65 | 0.00 | 0.00 | 0.00 |
February | 47.95 | 19.61 | 28.33 | 83.41 | 29.38 | 0.00 | 0.00 | 0.00 |
March | 39.46 | 10.71 | 28.75 | 76.82 | 22.49 | 0.00 | 0.00 | 0.00 |
April | 31.02 | 3.29 | 27.73 | 71.79 | 13.88 | 0.00 | 0.00 | 0.00 |
May | 26.28 | 0.40 | 25.87 | 80.35 | 3.44 | 0.00 | 0.00 | 0.00 |
June | 24.75 | 0.03 | 24.72 | 84.33 | 0.79 | 0.00 | 0.00 | 0.00 |
July | 24.75 | 0.21 | 24.54 | 98.50 | 0.04 | 0.00 | 0.00 | 0.00 |
August | 28.70 | 2.03 | 26.67 | 109.78 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 37.84 | 8.67 | 29.17 | 110.62 | 1.52 | 0.00 | 0.00 | 0.00 |
October | 49.55 | 19.70 | 29.85 | 116.31 | 6.27 | 0.00 | 0.00 | 0.00 |
November | 54.66 | 26.35 | 28.31 | 108.62 | 16.32 | 0.00 | 0.00 | 0.00 |
December | 50.74 | 25.06 | 25.68 | 88.10 | 29.20 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.84 | 11.63 | 27.21 | 92.75 | 13.09 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 24.75 | 0.03 | 24.54 | 71.79 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 54.66 | 26.35 | 29.85 | 116.31 | 34.65 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 51.06 | 24.00 | 27.05 | 83.66 | 34.65 | 0.00 | 0.00 | 0.00 |
February | 47.95 | 19.61 | 28.33 | 83.41 | 29.38 | 0.00 | 0.00 | 0.00 |
March | 39.46 | 10.71 | 28.75 | 76.82 | 22.49 | 0.00 | 0.00 | 0.00 |
April | 31.02 | 3.29 | 27.73 | 71.79 | 13.88 | 0.00 | 0.00 | 0.00 |
May | 26.28 | 0.40 | 25.87 | 80.35 | 3.44 | 0.00 | 0.00 | 0.00 |
June | 24.75 | 0.03 | 24.72 | 84.33 | 0.79 | 0.00 | 0.00 | 0.00 |
July | 24.75 | 0.21 | 24.54 | 98.50 | 0.04 | 0.00 | 0.00 | 0.00 |
August | 28.70 | 2.03 | 26.67 | 109.78 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 37.84 | 8.67 | 29.17 | 110.62 | 1.52 | 0.00 | 0.00 | 0.00 |
October | 49.55 | 19.70 | 29.85 | 116.31 | 6.27 | 0.00 | 0.00 | 0.00 |
November | 54.66 | 26.35 | 28.31 | 108.62 | 16.32 | 0.00 | 0.00 | 0.00 |
December | 50.74 | 25.06 | 25.68 | 88.10 | 29.20 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.84 | 11.63 | 27.21 | 92.75 | 13.09 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 24.75 | 0.03 | 24.54 | 71.79 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 54.66 | 26.35 | 29.85 | 116.31 | 34.65 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 61.04 | 28.70 | 32.34 | 100.16 | 41.07 | 0.00 | 0.00 | 0.00 |
February | 57.32 | 23.45 | 33.88 | 99.80 | 34.85 | 0.00 | 0.00 | 0.00 |
March | 47.18 | 12.81 | 34.37 | 91.71 | 26.75 | 0.00 | 0.00 | 0.00 |
April | 37.09 | 3.93 | 33.15 | 85.43 | 16.59 | 0.00 | 0.00 | 0.00 |
May | 31.42 | 0.48 | 30.93 | 95.09 | 4.17 | 0.00 | 0.00 | 0.00 |
June | 29.59 | 0.04 | 29.55 | 99.55 | 1.00 | 0.00 | 0.00 | 0.00 |
July | 29.59 | 0.25 | 29.33 | 116.34 | 0.05 | 0.00 | 0.00 | 0.00 |
August | 34.32 | 2.43 | 31.88 | 129.77 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 45.25 | 10.37 | 34.88 | 131.20 | 1.85 | 0.00 | 0.00 | 0.00 |
October | 59.24 | 23.55 | 35.69 | 138.39 | 7.57 | 0.00 | 0.00 | 0.00 |
November | 65.35 | 31.50 | 33.85 | 129.59 | 19.50 | 0.00 | 0.00 | 0.00 |
December | 60.66 | 29.97 | 30.70 | 105.34 | 34.66 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 46.44 | 13.91 | 32.53 | 110.27 | 15.58 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 29.59 | 0.04 | 29.33 | 85.43 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 65.35 | 31.50 | 35.69 | 138.39 | 41.07 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 51.06 | 24.00 | 27.05 | 83.82 | 34.31 | 0.00 | 0.00 | 0.00 |
February | 47.95 | 19.61 | 28.33 | 83.54 | 29.08 | 0.00 | 0.00 | 0.00 |
March | 39.46 | 10.71 | 28.75 | 76.89 | 22.27 | 0.00 | 0.00 | 0.00 |
April | 31.02 | 3.29 | 27.73 | 71.76 | 13.82 | 0.00 | 0.00 | 0.00 |
May | 26.28 | 0.40 | 25.87 | 80.11 | 3.50 | 0.00 | 0.00 | 0.00 |
June | 24.75 | 0.03 | 24.72 | 83.97 | 0.85 | 0.00 | 0.00 | 0.00 |
July | 24.75 | 0.21 | 24.54 | 97.91 | 0.04 | 0.00 | 0.00 | 0.00 |
August | 28.70 | 2.03 | 26.67 | 109.13 | 0.01 | 0.00 | 0.00 | 0.00 |
September | 37.84 | 8.67 | 29.17 | 110.18 | 1.60 | 0.00 | 0.00 | 0.00 |
October | 49.55 | 19.70 | 29.85 | 116.10 | 6.44 | 0.00 | 0.00 | 0.00 |
November | 54.66 | 26.35 | 28.31 | 108.56 | 16.37 | 0.00 | 0.00 | 0.00 |
December | 50.74 | 25.06 | 25.68 | 88.17 | 29.02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.84 | 11.63 | 27.21 | 92.57 | 13.03 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 24.75 | 0.03 | 24.54 | 71.76 | 0.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 54.66 | 26.35 | 29.85 | 116.10 | 34.31 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 51.06 | 24.00 | 27.05 | 83.82 | 34.31 | 0.00 | 0.00 | 0.00 |
February | 47.95 | 19.61 | 28.33 | 83.54 | 29.08 | 0.00 | 0.00 | 0.00 |
March | 39.46 | 10.71 | 28.75 | 76.89 | 22.27 | 0.00 | 0.00 | 0.00 |
April | 31.02 | 3.29 | 27.73 | 71.76 | 13.82 | 0.00 | 0.00 | 0.00 |
May | 26.28 | 0.40 | 25.87 | 80.11 | 3.50 | 0.00 | 0.00 | 0.00 |
June | 24.75 | 0.03 | 24.72 | 83.97 | 0.85 | 0.00 | 0.00 | 0.00 |
July | 24.75 | 0.21 | 24.54 | 97.91 | 0.04 | 0.00 | 0.00 | 0.00 |
August | 28.70 | 2.03 | 26.67 | 109.13 | 0.01 | 0.00 | 0.00 | 0.00 |
September | 37.84 | 8.67 | 29.17 | 110.18 | 1.60 | 0.00 | 0.00 | 0.00 |
October | 49.55 | 19.70 | 29.85 | 116.10 | 6.44 | 0.00 | 0.00 | 0.00 |
November | 54.66 | 26.35 | 28.31 | 108.56 | 16.37 | 0.00 | 0.00 | 0.00 |
December | 50.74 | 25.06 | 25.68 | 88.17 | 29.02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.84 | 11.63 | 27.21 | 92.57 | 13.03 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 24.75 | 0.03 | 24.54 | 71.76 | 0.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 54.66 | 26.35 | 29.85 | 116.10 | 34.31 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 61.04 | 28.70 | 32.34 | 100.37 | 40.67 | 0.00 | 0.00 | 0.00 |
February | 57.32 | 23.45 | 33.88 | 99.95 | 34.50 | 0.00 | 0.00 | 0.00 |
March | 47.18 | 12.81 | 34.37 | 91.80 | 26.49 | 0.00 | 0.00 | 0.00 |
April | 37.09 | 3.93 | 33.15 | 85.39 | 16.52 | 0.00 | 0.00 | 0.00 |
May | 31.42 | 0.48 | 30.93 | 94.80 | 4.24 | 0.00 | 0.00 | 0.00 |
June | 29.59 | 0.04 | 29.55 | 99.11 | 1.07 | 0.00 | 0.00 | 0.00 |
July | 29.59 | 0.25 | 29.33 | 115.64 | 0.06 | 0.00 | 0.00 | 0.00 |
August | 34.32 | 2.43 | 31.88 | 128.99 | 0.01 | 0.00 | 0.00 | 0.00 |
September | 45.25 | 10.37 | 34.88 | 130.68 | 1.96 | 0.00 | 0.00 | 0.00 |
October | 59.24 | 23.55 | 35.69 | 138.14 | 7.78 | 0.00 | 0.00 | 0.00 |
November | 65.35 | 31.50 | 33.85 | 129.51 | 19.57 | 0.00 | 0.00 | 0.00 |
December | 60.66 | 29.97 | 30.70 | 105.43 | 34.46 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 46.44 | 13.91 | 32.53 | 110.05 | 15.52 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 29.59 | 0.04 | 29.33 | 85.39 | 0.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 65.35 | 31.50 | 35.69 | 138.14 | 40.67 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 51.06 | 24.00 | 27.05 | 83.89 | 33.24 | 0.00 | 0.00 | 0.00 |
February | 47.95 | 19.61 | 28.33 | 83.50 | 28.04 | 0.00 | 0.00 | 0.00 |
March | 39.46 | 10.71 | 28.75 | 76.59 | 21.54 | 0.00 | 0.00 | 0.00 |
April | 31.02 | 3.29 | 27.73 | 70.87 | 13.80 | 0.00 | 0.00 | 0.00 |
May | 26.28 | 0.40 | 25.87 | 77.77 | 3.92 | 0.00 | 0.00 | 0.00 |
June | 24.75 | 0.03 | 24.72 | 80.85 | 1.20 | 0.00 | 0.00 | 0.00 |
July | 24.75 | 0.21 | 24.54 | 93.53 | 0.11 | 0.00 | 0.00 | 0.00 |
August | 28.70 | 2.03 | 26.67 | 104.31 | 0.05 | 0.00 | 0.00 | 0.00 |
September | 37.84 | 8.67 | 29.17 | 106.81 | 2.19 | 0.00 | 0.00 | 0.00 |
October | 49.55 | 19.70 | 29.85 | 114.14 | 7.57 | 0.00 | 0.00 | 0.00 |
November | 54.66 | 26.35 | 28.31 | 107.57 | 17.03 | 0.00 | 0.00 | 0.00 |
December | 50.74 | 25.06 | 25.68 | 87.97 | 28.60 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.84 | 11.63 | 27.21 | 90.70 | 13.03 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 24.75 | 0.03 | 24.54 | 70.87 | 0.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 54.66 | 26.35 | 29.85 | 114.14 | 33.24 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 51.06 | 24.00 | 27.05 | 83.89 | 33.24 | 0.00 | 0.00 | 0.00 |
February | 47.95 | 19.61 | 28.33 | 83.50 | 28.04 | 0.00 | 0.00 | 0.00 |
March | 39.46 | 10.71 | 28.75 | 76.59 | 21.54 | 0.00 | 0.00 | 0.00 |
April | 31.02 | 3.29 | 27.73 | 70.87 | 13.80 | 0.00 | 0.00 | 0.00 |
May | 26.28 | 0.40 | 25.87 | 77.77 | 3.92 | 0.00 | 0.00 | 0.00 |
June | 24.75 | 0.03 | 24.72 | 80.85 | 1.20 | 0.00 | 0.00 | 0.00 |
July | 24.75 | 0.21 | 24.54 | 93.53 | 0.11 | 0.00 | 0.00 | 0.00 |
August | 28.70 | 2.03 | 26.67 | 104.31 | 0.05 | 0.00 | 0.00 | 0.00 |
September | 37.84 | 8.67 | 29.17 | 106.81 | 2.19 | 0.00 | 0.00 | 0.00 |
October | 49.55 | 19.70 | 29.85 | 114.14 | 7.57 | 0.00 | 0.00 | 0.00 |
November | 54.66 | 26.35 | 28.31 | 107.57 | 17.03 | 0.00 | 0.00 | 0.00 |
December | 50.74 | 25.06 | 25.68 | 87.97 | 28.60 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.84 | 11.63 | 27.21 | 90.70 | 13.03 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 24.75 | 0.03 | 24.54 | 70.87 | 0.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 54.66 | 26.35 | 29.85 | 114.14 | 33.24 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 61.04 | 28.70 | 32.34 | 100.44 | 39.42 | 0.00 | 0.00 | 0.00 |
February | 57.32 | 23.45 | 33.88 | 99.90 | 33.28 | 0.00 | 0.00 | 0.00 |
March | 47.18 | 12.81 | 34.37 | 91.43 | 25.65 | 0.00 | 0.00 | 0.00 |
April | 37.09 | 3.93 | 33.15 | 84.33 | 16.51 | 0.00 | 0.00 | 0.00 |
May | 31.42 | 0.48 | 30.93 | 92.02 | 4.74 | 0.00 | 0.00 | 0.00 |
June | 29.59 | 0.04 | 29.55 | 95.41 | 1.50 | 0.00 | 0.00 | 0.00 |
July | 29.59 | 0.25 | 29.33 | 110.43 | 0.14 | 0.00 | 0.00 | 0.00 |
August | 34.32 | 2.43 | 31.88 | 123.26 | 0.06 | 0.00 | 0.00 | 0.00 |
September | 45.25 | 10.37 | 34.88 | 126.68 | 2.68 | 0.00 | 0.00 | 0.00 |
October | 59.24 | 23.55 | 35.69 | 135.80 | 9.13 | 0.00 | 0.00 | 0.00 |
November | 65.35 | 31.50 | 33.85 | 128.33 | 20.35 | 0.00 | 0.00 | 0.00 |
December | 60.66 | 29.97 | 30.70 | 105.19 | 33.96 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 46.44 | 13.91 | 32.53 | 107.82 | 15.53 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 29.59 | 0.04 | 29.33 | 84.33 | 0.06 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 65.35 | 31.50 | 35.69 | 135.80 | 39.42 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.136752E+09 | 64293395.40 | 72458816.16 | 0.223269E+09 | 94451505.21 |
February | 0.115989E+09 | 47444481.46 | 68544281.97 | 0.201331E+09 | 71844534.30 |
March | 0.105692E+09 | 28694877.00 | 76997385.59 | 0.205089E+09 | 60681684.09 |
April | 80401979.59 | 8524131.67 | 71877847.93 | 0.186087E+09 | 35341944.66 |
May | 70377678.63 | 1077764.15 | 69299914.48 | 0.217474E+09 | 8941405.84 |
June | 64141529.09 | 79377.56 | 64062151.53 | 0.220757E+09 | 2226676.85 |
July | 66277787.06 | 563159.07 | 65714628.00 | 0.268400E+09 | 52740.37 |
August | 76876963.45 | 5447043.90 | 71429919.55 | 0.296748E+09 | 33849.49 |
September | 98093415.27 | 22480968.51 | 75612446.76 | 0.290216E+09 | 4103714.79 |
October | 0.132704E+09 | 52757419.02 | 79946835.82 | 0.313540E+09 | 15955446.21 |
November | 0.141677E+09 | 68298945.76 | 73378249.49 | 0.281067E+09 | 41406467.41 |
December | 0.135903E+09 | 67132131.21 | 68771213.22 | 0.235457E+09 | 78488775.67 |
Annual Sum or Average | 0.122489E+10 | 0.366794E+09 | 0.858094E+09 | 0.293944E+10 | 0.413529E+09 |
Minimum of Months | 64141529.09 | 79377.56 | 64062151.53 | 0.186087E+09 | 33849.49 |
Maximum of Months | 0.141677E+09 | 68298945.76 | 79946835.82 | 0.313540E+09 | 94451505.21 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.136752E+09 | 64293395.40 | 72458816.16 | 0.223269E+09 | 94451505.21 |
February | 0.115989E+09 | 47444481.46 | 68544281.97 | 0.201331E+09 | 71844534.30 |
March | 0.105692E+09 | 28694877.00 | 76997385.59 | 0.205089E+09 | 60681684.09 |
April | 80401979.59 | 8524131.67 | 71877847.93 | 0.186087E+09 | 35341944.66 |
May | 70377678.63 | 1077764.15 | 69299914.48 | 0.217474E+09 | 8941405.84 |
June | 64141529.09 | 79377.56 | 64062151.53 | 0.220757E+09 | 2226676.85 |
July | 66277787.06 | 563159.07 | 65714628.00 | 0.268400E+09 | 52740.37 |
August | 76876963.45 | 5447043.90 | 71429919.55 | 0.296748E+09 | 33849.49 |
September | 98093415.27 | 22480968.51 | 75612446.76 | 0.290216E+09 | 4103714.79 |
October | 0.132704E+09 | 52757419.02 | 79946835.82 | 0.313540E+09 | 15955446.21 |
November | 0.141677E+09 | 68298945.76 | 73378249.49 | 0.281067E+09 | 41406467.41 |
December | 0.135903E+09 | 67132131.21 | 68771213.22 | 0.235457E+09 | 78488775.67 |
Annual Sum or Average | 0.122489E+10 | 0.366794E+09 | 0.858094E+09 | 0.293944E+10 | 0.413529E+09 |
Minimum of Months | 64141529.09 | 79377.56 | 64062151.53 | 0.186087E+09 | 33849.49 |
Maximum of Months | 0.141677E+09 | 68298945.76 | 79946835.82 | 0.313540E+09 | 94451505.21 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.136752E+09 | 64293395.40 | 72458816.16 | 0.223269E+09 | 94451505.21 |
February | 0.115989E+09 | 47444481.46 | 68544281.97 | 0.201331E+09 | 71844534.30 |
March | 0.105692E+09 | 28694877.00 | 76997385.59 | 0.205089E+09 | 60681684.09 |
April | 80401979.59 | 8524131.67 | 71877847.93 | 0.186087E+09 | 35341944.66 |
May | 70377678.63 | 1077764.15 | 69299914.48 | 0.217474E+09 | 8941405.84 |
June | 64141529.09 | 79377.56 | 64062151.53 | 0.220757E+09 | 2226676.85 |
July | 66277787.06 | 563159.07 | 65714628.00 | 0.268400E+09 | 52740.37 |
August | 76876963.45 | 5447043.90 | 71429919.55 | 0.296748E+09 | 33849.49 |
September | 98093415.27 | 22480968.51 | 75612446.76 | 0.290216E+09 | 4103714.79 |
October | 0.132704E+09 | 52757419.02 | 79946835.82 | 0.313540E+09 | 15955446.21 |
November | 0.141677E+09 | 68298945.76 | 73378249.49 | 0.281067E+09 | 41406467.41 |
December | 0.135903E+09 | 67132131.21 | 68771213.22 | 0.235457E+09 | 78488775.67 |
Annual Sum or Average | 0.122489E+10 | 0.366794E+09 | 0.858094E+09 | 0.293944E+10 | 0.413529E+09 |
Minimum of Months | 64141529.09 | 79377.56 | 64062151.53 | 0.186087E+09 | 33849.49 |
Maximum of Months | 0.141677E+09 | 68298945.76 | 79946835.82 | 0.313540E+09 | 94451505.21 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.136752E+09 | 64293395.40 | 72458816.16 | 0.223269E+09 | 94451505.21 |
February | 0.115989E+09 | 47444481.46 | 68544281.97 | 0.201331E+09 | 71844534.30 |
March | 0.105692E+09 | 28694877.00 | 76997385.59 | 0.205089E+09 | 60681684.09 |
April | 80401979.59 | 8524131.67 | 71877847.93 | 0.186087E+09 | 35341944.66 |
May | 70377678.63 | 1077764.15 | 69299914.48 | 0.217474E+09 | 8941405.84 |
June | 64141529.09 | 79377.56 | 64062151.53 | 0.220757E+09 | 2226676.85 |
July | 66277787.06 | 563159.07 | 65714628.00 | 0.268400E+09 | 52740.37 |
August | 76876963.45 | 5447043.90 | 71429919.55 | 0.296748E+09 | 33849.49 |
September | 98093415.27 | 22480968.51 | 75612446.76 | 0.290216E+09 | 4103714.79 |
October | 0.132704E+09 | 52757419.02 | 79946835.82 | 0.313540E+09 | 15955446.21 |
November | 0.141677E+09 | 68298945.76 | 73378249.49 | 0.281067E+09 | 41406467.41 |
December | 0.135903E+09 | 67132131.21 | 68771213.22 | 0.235457E+09 | 78488775.67 |
Annual Sum or Average | 0.122489E+10 | 0.366794E+09 | 0.858094E+09 | 0.293944E+10 | 0.413529E+09 |
Minimum of Months | 64141529.09 | 79377.56 | 64062151.53 | 0.186087E+09 | 33849.49 |
Maximum of Months | 0.141677E+09 | 68298945.76 | 79946835.82 | 0.313540E+09 | 94451505.21 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.164397E+09 | 77290559.30 | 87106652.12 | 0.268663E+09 | 0.112640E+09 |
February | 0.139436E+09 | 57035570.84 | 82400779.38 | 0.242095E+09 | 85750128.82 |
March | 0.127058E+09 | 34495659.75 | 92562711.29 | 0.246107E+09 | 72650723.14 |
April | 96655557.43 | 10247318.56 | 86408238.87 | 0.222549E+09 | 42503684.01 |
May | 84604804.42 | 1295638.43 | 83309165.99 | 0.258619E+09 | 10867528.52 |
June | 77107992.61 | 95424.05 | 77012568.56 | 0.261883E+09 | 2793923.59 |
July | 79676103.58 | 677003.89 | 78999099.68 | 0.318579E+09 | 73135.75 |
August | 92417945.34 | 6548185.35 | 85869760.00 | 0.352547E+09 | 46701.52 |
September | 0.117923E+09 | 27025585.12 | 90897801.61 | 0.345885E+09 | 5028366.77 |
October | 0.159531E+09 | 63422539.71 | 96108404.54 | 0.374830E+09 | 19354426.54 |
November | 0.170318E+09 | 82105847.49 | 88211952.54 | 0.337029E+09 | 49821697.52 |
December | 0.163377E+09 | 80703156.76 | 82673585.68 | 0.282974E+09 | 93782600.35 |
Annual Sum or Average | 0.147250E+10 | 0.440942E+09 | 0.103156E+10 | 0.351176E+10 | 0.495313E+09 |
Minimum of Months | 77107992.61 | 95424.05 | 77012568.56 | 0.222549E+09 | 46701.52 |
Maximum of Months | 0.170318E+09 | 82105847.49 | 96108404.54 | 0.374830E+09 | 0.112640E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.164397E+09 | 77290559.30 | 87106652.12 | 0.268663E+09 | 0.112640E+09 |
February | 0.139436E+09 | 57035570.84 | 82400779.38 | 0.242095E+09 | 85750128.82 |
March | 0.127058E+09 | 34495659.75 | 92562711.29 | 0.246107E+09 | 72650723.14 |
April | 96655557.43 | 10247318.56 | 86408238.87 | 0.222549E+09 | 42503684.01 |
May | 84604804.42 | 1295638.43 | 83309165.99 | 0.258619E+09 | 10867528.52 |
June | 77107992.61 | 95424.05 | 77012568.56 | 0.261883E+09 | 2793923.59 |
July | 79676103.58 | 677003.89 | 78999099.68 | 0.318579E+09 | 73135.75 |
August | 92417945.34 | 6548185.35 | 85869760.00 | 0.352547E+09 | 46701.52 |
September | 0.117923E+09 | 27025585.12 | 90897801.61 | 0.345885E+09 | 5028366.77 |
October | 0.159531E+09 | 63422539.71 | 96108404.54 | 0.374830E+09 | 19354426.54 |
November | 0.170318E+09 | 82105847.49 | 88211952.54 | 0.337029E+09 | 49821697.52 |
December | 0.163377E+09 | 80703156.76 | 82673585.68 | 0.282974E+09 | 93782600.35 |
Annual Sum or Average | 0.147250E+10 | 0.440942E+09 | 0.103156E+10 | 0.351176E+10 | 0.495313E+09 |
Minimum of Months | 77107992.61 | 95424.05 | 77012568.56 | 0.222549E+09 | 46701.52 |
Maximum of Months | 0.170318E+09 | 82105847.49 | 96108404.54 | 0.374830E+09 | 0.112640E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.136752E+09 | 64293395.40 | 72458816.16 | 0.221973E+09 | 96349743.41 |
February | 0.115989E+09 | 47444481.46 | 68544281.97 | 0.200543E+09 | 73352595.58 |
March | 0.105692E+09 | 28694877.00 | 76997385.59 | 0.204941E+09 | 61846461.41 |
April | 80401979.59 | 8524131.67 | 71877847.93 | 0.187010E+09 | 35890238.59 |
May | 70377678.63 | 1077764.15 | 69299914.48 | 0.220659E+09 | 8841914.49 |
June | 64141529.09 | 79377.56 | 64062151.53 | 0.225102E+09 | 1993296.53 |
July | 66277787.06 | 563159.07 | 65714628.00 | 0.274198E+09 | 38561.68 |
August | 76876963.45 | 5447043.90 | 71429919.55 | 0.303294E+09 | 12458.92 |
September | 98093415.27 | 22480968.51 | 75612446.76 | 0.294616E+09 | 3732376.64 |
October | 0.132704E+09 | 52757419.02 | 79946835.82 | 0.316248E+09 | 15279685.75 |
November | 0.141677E+09 | 68298945.76 | 73378249.49 | 0.281938E+09 | 41021506.59 |
December | 0.135903E+09 | 67132131.21 | 68771213.22 | 0.234899E+09 | 79392726.68 |
Annual Sum or Average | 0.122489E+10 | 0.366794E+09 | 0.858094E+09 | 0.296542E+10 | 0.417752E+09 |
Minimum of Months | 64141529.09 | 79377.56 | 64062151.53 | 0.187010E+09 | 12458.92 |
Maximum of Months | 0.141677E+09 | 68298945.76 | 79946835.82 | 0.316248E+09 | 96349743.41 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.136752E+09 | 64293395.40 | 72458816.16 | 0.221973E+09 | 96349743.41 |
February | 0.115989E+09 | 47444481.46 | 68544281.97 | 0.200543E+09 | 73352595.58 |
March | 0.105692E+09 | 28694877.00 | 76997385.59 | 0.204941E+09 | 61846461.41 |
April | 80401979.59 | 8524131.67 | 71877847.93 | 0.187010E+09 | 35890238.59 |
May | 70377678.63 | 1077764.15 | 69299914.48 | 0.220659E+09 | 8841914.49 |
June | 64141529.09 | 79377.56 | 64062151.53 | 0.225102E+09 | 1993296.53 |
July | 66277787.06 | 563159.07 | 65714628.00 | 0.274198E+09 | 38561.68 |
August | 76876963.45 | 5447043.90 | 71429919.55 | 0.303294E+09 | 12458.92 |
September | 98093415.27 | 22480968.51 | 75612446.76 | 0.294616E+09 | 3732376.64 |
October | 0.132704E+09 | 52757419.02 | 79946835.82 | 0.316248E+09 | 15279685.75 |
November | 0.141677E+09 | 68298945.76 | 73378249.49 | 0.281938E+09 | 41021506.59 |
December | 0.135903E+09 | 67132131.21 | 68771213.22 | 0.234899E+09 | 79392726.68 |
Annual Sum or Average | 0.122489E+10 | 0.366794E+09 | 0.858094E+09 | 0.296542E+10 | 0.417752E+09 |
Minimum of Months | 64141529.09 | 79377.56 | 64062151.53 | 0.187010E+09 | 12458.92 |
Maximum of Months | 0.141677E+09 | 68298945.76 | 79946835.82 | 0.316248E+09 | 96349743.41 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.164397E+09 | 77290559.30 | 87106652.12 | 0.267213E+09 | 0.114863E+09 |
February | 0.139436E+09 | 57035570.84 | 82400779.38 | 0.241230E+09 | 87514556.14 |
March | 0.127058E+09 | 34495659.75 | 92562711.29 | 0.245980E+09 | 74029021.89 |
April | 96655557.43 | 10247318.56 | 86408238.87 | 0.223650E+09 | 43164064.92 |
May | 84604804.42 | 1295638.43 | 83309165.99 | 0.262342E+09 | 10759420.16 |
June | 77107992.61 | 95424.05 | 77012568.56 | 0.266946E+09 | 2517719.86 |
July | 79676103.58 | 677003.89 | 78999099.68 | 0.325372E+09 | 52596.16 |
August | 92417945.34 | 6548185.35 | 85869760.00 | 0.360245E+09 | 20472.23 |
September | 0.117923E+09 | 27025585.12 | 90897801.61 | 0.351084E+09 | 4579751.50 |
October | 0.159531E+09 | 63422539.71 | 96108404.54 | 0.378081E+09 | 18564117.05 |
November | 0.170318E+09 | 82105847.49 | 88211952.54 | 0.338120E+09 | 49359894.77 |
December | 0.163377E+09 | 80703156.76 | 82673585.68 | 0.282395E+09 | 94836792.81 |
Annual Sum or Average | 0.147250E+10 | 0.440942E+09 | 0.103156E+10 | 0.354266E+10 | 0.500261E+09 |
Minimum of Months | 77107992.61 | 95424.05 | 77012568.56 | 0.223650E+09 | 20472.23 |
Maximum of Months | 0.170318E+09 | 82105847.49 | 96108404.54 | 0.378081E+09 | 0.114863E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.136752E+09 | 64293395.40 | 72458816.16 | 0.222231E+09 | 98557264.43 |
February | 0.115989E+09 | 47444481.46 | 68544281.97 | 0.200547E+09 | 75931240.30 |
March | 0.105692E+09 | 28694877.00 | 76997385.59 | 0.204433E+09 | 65355887.96 |
April | 80401979.59 | 8524131.67 | 71877847.93 | 0.184861E+09 | 40011027.65 |
May | 70377678.63 | 1077764.15 | 69299914.48 | 0.212567E+09 | 10841289.58 |
June | 64141529.09 | 79377.56 | 64062151.53 | 0.215330E+09 | 2849997.85 |
July | 66277787.06 | 563159.07 | 65714628.00 | 0.260972E+09 | 117955.06 |
August | 76876963.45 | 5447043.90 | 71429919.55 | 0.290646E+09 | 45061.35 |
September | 98093415.27 | 22480968.51 | 75612446.76 | 0.284414E+09 | 4717185.34 |
October | 0.132704E+09 | 52757419.02 | 79946835.82 | 0.310177E+09 | 19097029.93 |
November | 0.141677E+09 | 68298945.76 | 73378249.49 | 0.281021E+09 | 46350575.09 |
December | 0.135903E+09 | 67132131.21 | 68771213.22 | 0.234966E+09 | 83187044.46 |
Annual Sum or Average | 0.122489E+10 | 0.366794E+09 | 0.858094E+09 | 0.290217E+10 | 0.447062E+09 |
Minimum of Months | 64141529.09 | 79377.56 | 64062151.53 | 0.184861E+09 | 45061.35 |
Maximum of Months | 0.141677E+09 | 68298945.76 | 79946835.82 | 0.310177E+09 | 98557264.43 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.136752E+09 | 64293395.40 | 72458816.16 | 0.222231E+09 | 98557264.43 |
February | 0.115989E+09 | 47444481.46 | 68544281.97 | 0.200547E+09 | 75931240.30 |
March | 0.105692E+09 | 28694877.00 | 76997385.59 | 0.204433E+09 | 65355887.96 |
April | 80401979.59 | 8524131.67 | 71877847.93 | 0.184861E+09 | 40011027.65 |
May | 70377678.63 | 1077764.15 | 69299914.48 | 0.212567E+09 | 10841289.58 |
June | 64141529.09 | 79377.56 | 64062151.53 | 0.215330E+09 | 2849997.85 |
July | 66277787.06 | 563159.07 | 65714628.00 | 0.260972E+09 | 117955.06 |
August | 76876963.45 | 5447043.90 | 71429919.55 | 0.290646E+09 | 45061.35 |
September | 98093415.27 | 22480968.51 | 75612446.76 | 0.284414E+09 | 4717185.34 |
October | 0.132704E+09 | 52757419.02 | 79946835.82 | 0.310177E+09 | 19097029.93 |
November | 0.141677E+09 | 68298945.76 | 73378249.49 | 0.281021E+09 | 46350575.09 |
December | 0.135903E+09 | 67132131.21 | 68771213.22 | 0.234966E+09 | 83187044.46 |
Annual Sum or Average | 0.122489E+10 | 0.366794E+09 | 0.858094E+09 | 0.290217E+10 | 0.447062E+09 |
Minimum of Months | 64141529.09 | 79377.56 | 64062151.53 | 0.184861E+09 | 45061.35 |
Maximum of Months | 0.141677E+09 | 68298945.76 | 79946835.82 | 0.310177E+09 | 98557264.43 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.163499E+09 | 76868206.52 | 86630659.49 | 0.266063E+09 | 0.116774E+09 |
February | 0.138674E+09 | 56723901.05 | 81950501.90 | 0.239924E+09 | 90020273.96 |
March | 0.126364E+09 | 34307158.88 | 92056904.13 | 0.244053E+09 | 77702776.17 |
April | 96127384.99 | 10191322.28 | 85936062.70 | 0.219974E+09 | 47773155.93 |
May | 84142483.08 | 1288558.44 | 82853924.64 | 0.251565E+09 | 13104340.59 |
June | 76686637.46 | 94902.61 | 76591734.85 | 0.254188E+09 | 3563625.77 |
July | 79240715.03 | 673304.42 | 78567410.61 | 0.308217E+09 | 157874.94 |
August | 91912929.25 | 6512402.91 | 85400526.34 | 0.343555E+09 | 61255.73 |
September | 0.117279E+09 | 26877904.32 | 90401092.31 | 0.337357E+09 | 5772507.02 |
October | 0.158659E+09 | 63075968.46 | 95583222.00 | 0.369089E+09 | 23058107.35 |
November | 0.169387E+09 | 81657181.66 | 87729920.01 | 0.335245E+09 | 55337835.55 |
December | 0.162484E+09 | 80262155.91 | 82221817.45 | 0.280927E+09 | 98708828.41 |
Annual Sum or Average | 0.146446E+10 | 0.438533E+09 | 0.102592E+10 | 0.345016E+10 | 0.532035E+09 |
Minimum of Months | 76686637.46 | 94902.61 | 76591734.85 | 0.219974E+09 | 61255.73 |
Maximum of Months | 0.169387E+09 | 81657181.66 | 95583222.00 | 0.369089E+09 | 0.116774E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.136752E+09 | 64293395.40 | 72458816.16 | 0.222468E+09 | 97927638.27 |
February | 0.115989E+09 | 47444481.46 | 68544281.97 | 0.200665E+09 | 75582387.85 |
March | 0.105692E+09 | 28694877.00 | 76997385.59 | 0.204485E+09 | 65231162.07 |
April | 80401979.59 | 8524131.67 | 71877847.93 | 0.184795E+09 | 40289411.63 |
May | 70377678.63 | 1077764.15 | 69299914.48 | 0.211932E+09 | 11296863.63 |
June | 64141529.09 | 79377.56 | 64062151.53 | 0.214381E+09 | 3135981.27 |
July | 66277787.06 | 563159.07 | 65714628.00 | 0.259346E+09 | 158999.76 |
August | 76876963.45 | 5447043.90 | 71429919.55 | 0.289035E+09 | 57284.71 |
September | 98093415.27 | 22480968.51 | 75612446.76 | 0.283401E+09 | 5043513.23 |
October | 0.132704E+09 | 52757419.02 | 79946835.82 | 0.309812E+09 | 19850304.23 |
November | 0.141677E+09 | 68298945.76 | 73378249.49 | 0.280945E+09 | 46694506.91 |
December | 0.135903E+09 | 67132131.21 | 68771213.22 | 0.235043E+09 | 82973255.27 |
Annual Sum or Average | 0.122489E+10 | 0.366794E+09 | 0.858094E+09 | 0.289631E+10 | 0.448241E+09 |
Minimum of Months | 64141529.09 | 79377.56 | 64062151.53 | 0.184795E+09 | 57284.71 |
Maximum of Months | 0.141677E+09 | 68298945.76 | 79946835.82 | 0.309812E+09 | 97927638.27 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.136752E+09 | 64293395.40 | 72458816.16 | 0.222468E+09 | 97927638.27 |
February | 0.115989E+09 | 47444481.46 | 68544281.97 | 0.200665E+09 | 75582387.85 |
March | 0.105692E+09 | 28694877.00 | 76997385.59 | 0.204485E+09 | 65231162.07 |
April | 80401979.59 | 8524131.67 | 71877847.93 | 0.184795E+09 | 40289411.63 |
May | 70377678.63 | 1077764.15 | 69299914.48 | 0.211932E+09 | 11296863.63 |
June | 64141529.09 | 79377.56 | 64062151.53 | 0.214381E+09 | 3135981.27 |
July | 66277787.06 | 563159.07 | 65714628.00 | 0.259346E+09 | 158999.76 |
August | 76876963.45 | 5447043.90 | 71429919.55 | 0.289035E+09 | 57284.71 |
September | 98093415.27 | 22480968.51 | 75612446.76 | 0.283401E+09 | 5043513.23 |
October | 0.132704E+09 | 52757419.02 | 79946835.82 | 0.309812E+09 | 19850304.23 |
November | 0.141677E+09 | 68298945.76 | 73378249.49 | 0.280945E+09 | 46694506.91 |
December | 0.135903E+09 | 67132131.21 | 68771213.22 | 0.235043E+09 | 82973255.27 |
Annual Sum or Average | 0.122489E+10 | 0.366794E+09 | 0.858094E+09 | 0.289631E+10 | 0.448241E+09 |
Minimum of Months | 64141529.09 | 79377.56 | 64062151.53 | 0.184795E+09 | 57284.71 |
Maximum of Months | 0.141677E+09 | 68298945.76 | 79946835.82 | 0.309812E+09 | 97927638.27 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.163499E+09 | 76868206.52 | 86630659.49 | 0.266346E+09 | 0.116030E+09 |
February | 0.138674E+09 | 56723901.05 | 81950501.90 | 0.240065E+09 | 89609055.08 |
March | 0.126364E+09 | 34307158.88 | 92056904.13 | 0.244115E+09 | 77555500.90 |
April | 96127384.99 | 10191322.28 | 85936062.70 | 0.219896E+09 | 48102965.01 |
May | 84142483.08 | 1288558.44 | 82853924.64 | 0.250819E+09 | 13649774.63 |
June | 76686637.46 | 94902.61 | 76591734.85 | 0.253079E+09 | 3914425.73 |
July | 79240715.03 | 673304.42 | 78567410.61 | 0.306296E+09 | 209606.88 |
August | 91912929.25 | 6512402.91 | 85400526.34 | 0.341652E+09 | 78118.68 |
September | 0.117279E+09 | 26877904.32 | 90401092.31 | 0.336168E+09 | 6171834.69 |
October | 0.158659E+09 | 63075968.46 | 95583222.00 | 0.368659E+09 | 23952227.84 |
November | 0.169387E+09 | 81657181.66 | 87729920.01 | 0.335155E+09 | 55745154.17 |
December | 0.162484E+09 | 80262155.91 | 82221817.45 | 0.281019E+09 | 98456303.95 |
Annual Sum or Average | 0.146446E+10 | 0.438533E+09 | 0.102592E+10 | 0.344327E+10 | 0.533475E+09 |
Minimum of Months | 76686637.46 | 94902.61 | 76591734.85 | 0.219896E+09 | 78118.68 |
Maximum of Months | 0.169387E+09 | 81657181.66 | 95583222.00 | 0.368659E+09 | 0.116030E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.136752E+09 | 64293395.40 | 72458816.16 | 0.223001E+09 | 96684248.32 |
February | 0.115989E+09 | 47444481.46 | 68544281.97 | 0.201038E+09 | 74576252.94 |
March | 0.105692E+09 | 28694877.00 | 76997385.59 | 0.204862E+09 | 64181885.63 |
April | 80401979.59 | 8524131.67 | 71877847.93 | 0.185132E+09 | 39422534.12 |
May | 70377678.63 | 1077764.15 | 69299914.48 | 0.212521E+09 | 10877534.30 |
June | 64141529.09 | 79377.56 | 64062151.53 | 0.215108E+09 | 2918818.81 |
July | 66277787.06 | 563159.07 | 65714628.00 | 0.260139E+09 | 142484.49 |
August | 76876963.45 | 5447043.90 | 71429919.55 | 0.289884E+09 | 46405.84 |
September | 98093415.27 | 22480968.51 | 75612446.76 | 0.283985E+09 | 4807820.98 |
October | 0.132704E+09 | 52757419.02 | 79946835.82 | 0.310149E+09 | 19246076.74 |
November | 0.141677E+09 | 68298945.76 | 73378249.49 | 0.281230E+09 | 45887776.12 |
December | 0.135903E+09 | 67132131.21 | 68771213.22 | 0.235403E+09 | 81954537.14 |
Annual Sum or Average | 0.122489E+10 | 0.366794E+09 | 0.858094E+09 | 0.290245E+10 | 0.440746E+09 |
Minimum of Months | 64141529.09 | 79377.56 | 64062151.53 | 0.185132E+09 | 46405.84 |
Maximum of Months | 0.141677E+09 | 68298945.76 | 79946835.82 | 0.310149E+09 | 96684248.32 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.136752E+09 | 64293395.40 | 72458816.16 | 0.223001E+09 | 96684248.32 |
February | 0.115989E+09 | 47444481.46 | 68544281.97 | 0.201038E+09 | 74576252.94 |
March | 0.105692E+09 | 28694877.00 | 76997385.59 | 0.204862E+09 | 64181885.63 |
April | 80401979.59 | 8524131.67 | 71877847.93 | 0.185132E+09 | 39422534.12 |
May | 70377678.63 | 1077764.15 | 69299914.48 | 0.212521E+09 | 10877534.30 |
June | 64141529.09 | 79377.56 | 64062151.53 | 0.215108E+09 | 2918818.81 |
July | 66277787.06 | 563159.07 | 65714628.00 | 0.260139E+09 | 142484.49 |
August | 76876963.45 | 5447043.90 | 71429919.55 | 0.289884E+09 | 46405.84 |
September | 98093415.27 | 22480968.51 | 75612446.76 | 0.283985E+09 | 4807820.98 |
October | 0.132704E+09 | 52757419.02 | 79946835.82 | 0.310149E+09 | 19246076.74 |
November | 0.141677E+09 | 68298945.76 | 73378249.49 | 0.281230E+09 | 45887776.12 |
December | 0.135903E+09 | 67132131.21 | 68771213.22 | 0.235403E+09 | 81954537.14 |
Annual Sum or Average | 0.122489E+10 | 0.366794E+09 | 0.858094E+09 | 0.290245E+10 | 0.440746E+09 |
Minimum of Months | 64141529.09 | 79377.56 | 64062151.53 | 0.185132E+09 | 46405.84 |
Maximum of Months | 0.141677E+09 | 68298945.76 | 79946835.82 | 0.310149E+09 | 96684248.32 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.163499E+09 | 76868206.52 | 86630659.49 | 0.266986E+09 | 0.114572E+09 |
February | 0.138674E+09 | 56723901.05 | 81950501.90 | 0.240515E+09 | 88429552.49 |
March | 0.126364E+09 | 34307158.88 | 92056904.13 | 0.244567E+09 | 76322701.81 |
April | 96127384.99 | 10191322.28 | 85936062.70 | 0.220299E+09 | 47084246.36 |
May | 84142483.08 | 1288558.44 | 82853924.64 | 0.251513E+09 | 13152720.63 |
June | 76686637.46 | 94902.61 | 76591734.85 | 0.253927E+09 | 3650943.36 |
July | 79240715.03 | 673304.42 | 78567410.61 | 0.307228E+09 | 188864.96 |
August | 91912929.25 | 6512402.91 | 85400526.34 | 0.342649E+09 | 64159.99 |
September | 0.117279E+09 | 26877904.32 | 90401092.31 | 0.336851E+09 | 5887551.59 |
October | 0.158659E+09 | 63075968.46 | 95583222.00 | 0.369056E+09 | 23240248.02 |
November | 0.169387E+09 | 81657181.66 | 87729920.01 | 0.335495E+09 | 54798015.69 |
December | 0.162484E+09 | 80262155.91 | 82221817.45 | 0.281453E+09 | 97260762.34 |
Annual Sum or Average | 0.146446E+10 | 0.438533E+09 | 0.102592E+10 | 0.345054E+10 | 0.524651E+09 |
Minimum of Months | 76686637.46 | 94902.61 | 76591734.85 | 0.220299E+09 | 64159.99 |
Maximum of Months | 0.169387E+09 | 81657181.66 | 95583222.00 | 0.369056E+09 | 0.114572E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.136752E+09 | 64293395.40 | 72458816.16 | 0.224241E+09 | 93569369.38 |
February | 0.115989E+09 | 47444481.46 | 68544281.97 | 0.201885E+09 | 71889742.98 |
March | 0.105692E+09 | 28694877.00 | 76997385.59 | 0.205543E+09 | 61294702.88 |
April | 80401979.59 | 8524131.67 | 71877847.93 | 0.185410E+09 | 37035573.85 |
May | 70377678.63 | 1077764.15 | 69299914.48 | 0.213114E+09 | 9832199.58 |
June | 64141529.09 | 79377.56 | 64062151.53 | 0.215802E+09 | 2402075.05 |
July | 66277787.06 | 563159.07 | 65714628.00 | 0.260523E+09 | 116936.18 |
August | 76876963.45 | 5447043.90 | 71429919.55 | 0.290612E+09 | 21559.29 |
September | 98093415.27 | 22480968.51 | 75612446.76 | 0.284458E+09 | 4308272.63 |
October | 0.132704E+09 | 52757419.02 | 79946835.82 | 0.310369E+09 | 17788990.28 |
November | 0.141677E+09 | 68298945.76 | 73378249.49 | 0.281217E+09 | 43441561.98 |
December | 0.135903E+09 | 67132131.21 | 68771213.22 | 0.236043E+09 | 79100982.99 |
Annual Sum or Average | 0.122489E+10 | 0.366794E+09 | 0.858094E+09 | 0.290922E+10 | 0.420802E+09 |
Minimum of Months | 64141529.09 | 79377.56 | 64062151.53 | 0.185410E+09 | 21559.29 |
Maximum of Months | 0.141677E+09 | 68298945.76 | 79946835.82 | 0.310369E+09 | 93569369.38 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.136752E+09 | 64293395.40 | 72458816.16 | 0.224241E+09 | 93569369.38 |
February | 0.115989E+09 | 47444481.46 | 68544281.97 | 0.201885E+09 | 71889742.98 |
March | 0.105692E+09 | 28694877.00 | 76997385.59 | 0.205543E+09 | 61294702.88 |
April | 80401979.59 | 8524131.67 | 71877847.93 | 0.185410E+09 | 37035573.85 |
May | 70377678.63 | 1077764.15 | 69299914.48 | 0.213114E+09 | 9832199.58 |
June | 64141529.09 | 79377.56 | 64062151.53 | 0.215802E+09 | 2402075.05 |
July | 66277787.06 | 563159.07 | 65714628.00 | 0.260523E+09 | 116936.18 |
August | 76876963.45 | 5447043.90 | 71429919.55 | 0.290612E+09 | 21559.29 |
September | 98093415.27 | 22480968.51 | 75612446.76 | 0.284458E+09 | 4308272.63 |
October | 0.132704E+09 | 52757419.02 | 79946835.82 | 0.310369E+09 | 17788990.28 |
November | 0.141677E+09 | 68298945.76 | 73378249.49 | 0.281217E+09 | 43441561.98 |
December | 0.135903E+09 | 67132131.21 | 68771213.22 | 0.236043E+09 | 79100982.99 |
Annual Sum or Average | 0.122489E+10 | 0.366794E+09 | 0.858094E+09 | 0.290922E+10 | 0.420802E+09 |
Minimum of Months | 64141529.09 | 79377.56 | 64062151.53 | 0.185410E+09 | 21559.29 |
Maximum of Months | 0.141677E+09 | 68298945.76 | 79946835.82 | 0.310369E+09 | 93569369.38 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.136752E+09 | 64293395.40 | 72458816.16 | 0.224241E+09 | 93569369.38 |
February | 0.115989E+09 | 47444481.46 | 68544281.97 | 0.201885E+09 | 71889742.98 |
March | 0.105692E+09 | 28694877.00 | 76997385.59 | 0.205543E+09 | 61294702.88 |
April | 80401979.59 | 8524131.67 | 71877847.93 | 0.185410E+09 | 37035573.85 |
May | 70377678.63 | 1077764.15 | 69299914.48 | 0.213114E+09 | 9832199.58 |
June | 64141529.09 | 79377.56 | 64062151.53 | 0.215802E+09 | 2402075.05 |
July | 66277787.06 | 563159.07 | 65714628.00 | 0.260523E+09 | 116936.18 |
August | 76876963.45 | 5447043.90 | 71429919.55 | 0.290612E+09 | 21559.29 |
September | 98093415.27 | 22480968.51 | 75612446.76 | 0.284458E+09 | 4308272.63 |
October | 0.132704E+09 | 52757419.02 | 79946835.82 | 0.310369E+09 | 17788990.28 |
November | 0.141677E+09 | 68298945.76 | 73378249.49 | 0.281217E+09 | 43441561.98 |
December | 0.135903E+09 | 67132131.21 | 68771213.22 | 0.236043E+09 | 79100982.99 |
Annual Sum or Average | 0.122489E+10 | 0.366794E+09 | 0.858094E+09 | 0.290922E+10 | 0.420802E+09 |
Minimum of Months | 64141529.09 | 79377.56 | 64062151.53 | 0.185410E+09 | 21559.29 |
Maximum of Months | 0.141677E+09 | 68298945.76 | 79946835.82 | 0.310369E+09 | 93569369.38 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.136752E+09 | 64293395.40 | 72458816.16 | 0.224241E+09 | 93569369.38 |
February | 0.115989E+09 | 47444481.46 | 68544281.97 | 0.201885E+09 | 71889742.98 |
March | 0.105692E+09 | 28694877.00 | 76997385.59 | 0.205543E+09 | 61294702.88 |
April | 80401979.59 | 8524131.67 | 71877847.93 | 0.185410E+09 | 37035573.85 |
May | 70377678.63 | 1077764.15 | 69299914.48 | 0.213114E+09 | 9832199.58 |
June | 64141529.09 | 79377.56 | 64062151.53 | 0.215802E+09 | 2402075.05 |
July | 66277787.06 | 563159.07 | 65714628.00 | 0.260523E+09 | 116936.18 |
August | 76876963.45 | 5447043.90 | 71429919.55 | 0.290612E+09 | 21559.29 |
September | 98093415.27 | 22480968.51 | 75612446.76 | 0.284458E+09 | 4308272.63 |
October | 0.132704E+09 | 52757419.02 | 79946835.82 | 0.310369E+09 | 17788990.28 |
November | 0.141677E+09 | 68298945.76 | 73378249.49 | 0.281217E+09 | 43441561.98 |
December | 0.135903E+09 | 67132131.21 | 68771213.22 | 0.236043E+09 | 79100982.99 |
Annual Sum or Average | 0.122489E+10 | 0.366794E+09 | 0.858094E+09 | 0.290922E+10 | 0.420802E+09 |
Minimum of Months | 64141529.09 | 79377.56 | 64062151.53 | 0.185410E+09 | 21559.29 |
Maximum of Months | 0.141677E+09 | 68298945.76 | 79946835.82 | 0.310369E+09 | 93569369.38 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.163499E+09 | 76868206.52 | 86630659.49 | 0.268383E+09 | 0.110915E+09 |
February | 0.138674E+09 | 56723901.05 | 81950501.90 | 0.241461E+09 | 85270365.58 |
March | 0.126364E+09 | 34307158.88 | 92056904.13 | 0.245344E+09 | 72902359.20 |
April | 96127384.99 | 10191322.28 | 85936062.70 | 0.220635E+09 | 44228399.56 |
May | 84142483.08 | 1288558.44 | 82853924.64 | 0.252303E+09 | 11874266.85 |
June | 76686637.46 | 94902.61 | 76591734.85 | 0.254870E+09 | 3001852.61 |
July | 79240715.03 | 673304.42 | 78567410.61 | 0.307848E+09 | 152345.02 |
August | 91912929.25 | 6512402.91 | 85400526.34 | 0.343671E+09 | 31851.87 |
September | 0.117279E+09 | 26877904.32 | 90401092.31 | 0.337466E+09 | 5255544.28 |
October | 0.158659E+09 | 63075968.46 | 95583222.00 | 0.369294E+09 | 21449444.57 |
November | 0.169387E+09 | 81657181.66 | 87729920.01 | 0.335446E+09 | 51879591.35 |
December | 0.162484E+09 | 80262155.91 | 82221817.45 | 0.282160E+09 | 93901685.11 |
Annual Sum or Average | 0.146446E+10 | 0.438533E+09 | 0.102592E+10 | 0.345888E+10 | 0.500863E+09 |
Minimum of Months | 76686637.46 | 94902.61 | 76591734.85 | 0.220635E+09 | 31851.87 |
Maximum of Months | 0.169387E+09 | 81657181.66 | 95583222.00 | 0.369294E+09 | 0.110915E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.163499E+09 | 76868206.52 | 86630659.49 | 0.268383E+09 | 0.110915E+09 |
February | 0.138674E+09 | 56723901.05 | 81950501.90 | 0.241461E+09 | 85270365.58 |
March | 0.126364E+09 | 34307158.88 | 92056904.13 | 0.245344E+09 | 72902359.20 |
April | 96127384.99 | 10191322.28 | 85936062.70 | 0.220635E+09 | 44228399.56 |
May | 84142483.08 | 1288558.44 | 82853924.64 | 0.252303E+09 | 11874266.85 |
June | 76686637.46 | 94902.61 | 76591734.85 | 0.254870E+09 | 3001852.61 |
July | 79240715.03 | 673304.42 | 78567410.61 | 0.307848E+09 | 152345.02 |
August | 91912929.25 | 6512402.91 | 85400526.34 | 0.343671E+09 | 31851.87 |
September | 0.117279E+09 | 26877904.32 | 90401092.31 | 0.337466E+09 | 5255544.28 |
October | 0.158659E+09 | 63075968.46 | 95583222.00 | 0.369294E+09 | 21449444.57 |
November | 0.169387E+09 | 81657181.66 | 87729920.01 | 0.335446E+09 | 51879591.35 |
December | 0.162484E+09 | 80262155.91 | 82221817.45 | 0.282160E+09 | 93901685.11 |
Annual Sum or Average | 0.146446E+10 | 0.438533E+09 | 0.102592E+10 | 0.345888E+10 | 0.500863E+09 |
Minimum of Months | 76686637.46 | 94902.61 | 76591734.85 | 0.220635E+09 | 31851.87 |
Maximum of Months | 0.169387E+09 | 81657181.66 | 95583222.00 | 0.369294E+09 | 0.110915E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.136752E+09 | 64293395.40 | 72458816.16 | 0.223856E+09 | 93154066.25 |
February | 0.115989E+09 | 47444481.46 | 68544281.97 | 0.201638E+09 | 71378401.36 |
March | 0.105692E+09 | 28694877.00 | 76997385.59 | 0.205593E+09 | 60517492.73 |
April | 80401979.59 | 8524131.67 | 71877847.93 | 0.185951E+09 | 36163371.12 |
May | 70377678.63 | 1077764.15 | 69299914.48 | 0.215045E+09 | 9281536.12 |
June | 64141529.09 | 79377.56 | 64062151.53 | 0.218422E+09 | 2078961.44 |
July | 66277787.06 | 563159.07 | 65714628.00 | 0.263670E+09 | 96838.19 |
August | 76876963.45 | 5447043.90 | 71429919.55 | 0.293899E+09 | 6412.99 |
September | 98093415.27 | 22480968.51 | 75612446.76 | 0.286592E+09 | 3956594.45 |
October | 0.132704E+09 | 52757419.02 | 79946835.82 | 0.311411E+09 | 16870642.96 |
November | 0.141677E+09 | 68298945.76 | 73378249.49 | 0.281439E+09 | 42460240.34 |
December | 0.135903E+09 | 67132131.21 | 68771213.22 | 0.235823E+09 | 78456397.24 |
Annual Sum or Average | 0.122489E+10 | 0.366794E+09 | 0.858094E+09 | 0.292334E+10 | 0.414421E+09 |
Minimum of Months | 64141529.09 | 79377.56 | 64062151.53 | 0.185951E+09 | 6412.99 |
Maximum of Months | 0.141677E+09 | 68298945.76 | 79946835.82 | 0.311411E+09 | 93154066.25 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.136752E+09 | 64293395.40 | 72458816.16 | 0.223856E+09 | 93154066.25 |
February | 0.115989E+09 | 47444481.46 | 68544281.97 | 0.201638E+09 | 71378401.36 |
March | 0.105692E+09 | 28694877.00 | 76997385.59 | 0.205593E+09 | 60517492.73 |
April | 80401979.59 | 8524131.67 | 71877847.93 | 0.185951E+09 | 36163371.12 |
May | 70377678.63 | 1077764.15 | 69299914.48 | 0.215045E+09 | 9281536.12 |
June | 64141529.09 | 79377.56 | 64062151.53 | 0.218422E+09 | 2078961.44 |
July | 66277787.06 | 563159.07 | 65714628.00 | 0.263670E+09 | 96838.19 |
August | 76876963.45 | 5447043.90 | 71429919.55 | 0.293899E+09 | 6412.99 |
September | 98093415.27 | 22480968.51 | 75612446.76 | 0.286592E+09 | 3956594.45 |
October | 0.132704E+09 | 52757419.02 | 79946835.82 | 0.311411E+09 | 16870642.96 |
November | 0.141677E+09 | 68298945.76 | 73378249.49 | 0.281439E+09 | 42460240.34 |
December | 0.135903E+09 | 67132131.21 | 68771213.22 | 0.235823E+09 | 78456397.24 |
Annual Sum or Average | 0.122489E+10 | 0.366794E+09 | 0.858094E+09 | 0.292334E+10 | 0.414421E+09 |
Minimum of Months | 64141529.09 | 79377.56 | 64062151.53 | 0.185951E+09 | 6412.99 |
Maximum of Months | 0.141677E+09 | 68298945.76 | 79946835.82 | 0.311411E+09 | 93154066.25 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.163499E+09 | 76868206.52 | 86630659.49 | 0.268034E+09 | 0.110405E+09 |
February | 0.138674E+09 | 56723901.05 | 81950501.90 | 0.241252E+09 | 84655865.77 |
March | 0.126364E+09 | 34307158.88 | 92056904.13 | 0.245461E+09 | 71990823.16 |
April | 96127384.99 | 10191322.28 | 85936062.70 | 0.221281E+09 | 43220646.25 |
May | 84142483.08 | 1288558.44 | 82853924.64 | 0.254495E+09 | 11236288.32 |
June | 76686637.46 | 94902.61 | 76591734.85 | 0.257827E+09 | 2622796.97 |
July | 79240715.03 | 673304.42 | 78567410.61 | 0.311424E+09 | 127339.37 |
August | 91912929.25 | 6512402.91 | 85400526.34 | 0.347418E+09 | 13018.07 |
September | 0.117279E+09 | 26877904.32 | 90401092.31 | 0.339917E+09 | 4836516.68 |
October | 0.158659E+09 | 63075968.46 | 95583222.00 | 0.370532E+09 | 20382860.36 |
November | 0.169387E+09 | 81657181.66 | 87729920.01 | 0.335769E+09 | 50740458.73 |
December | 0.162484E+09 | 80262155.91 | 82221817.45 | 0.281991E+09 | 93135055.92 |
Annual Sum or Average | 0.146446E+10 | 0.438533E+09 | 0.102592E+10 | 0.347540E+10 | 0.493367E+09 |
Minimum of Months | 76686637.46 | 94902.61 | 76591734.85 | 0.221281E+09 | 13018.07 |
Maximum of Months | 0.169387E+09 | 81657181.66 | 95583222.00 | 0.370532E+09 | 0.110405E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.136752E+09 | 64293395.40 | 72458816.16 | 0.224062E+09 | 92802394.40 |
February | 0.115989E+09 | 47444481.46 | 68544281.97 | 0.201795E+09 | 71083826.01 |
March | 0.105692E+09 | 28694877.00 | 76997385.59 | 0.205744E+09 | 60233339.83 |
April | 80401979.59 | 8524131.67 | 71877847.93 | 0.186072E+09 | 35972117.03 |
May | 70377678.63 | 1077764.15 | 69299914.48 | 0.215199E+09 | 9215275.15 |
June | 64141529.09 | 79377.56 | 64062151.53 | 0.218590E+09 | 2052279.94 |
July | 66277787.06 | 563159.07 | 65714628.00 | 0.263816E+09 | 97256.74 |
August | 76876963.45 | 5447043.90 | 71429919.55 | 0.294041E+09 | 5737.61 |
September | 98093415.27 | 22480968.51 | 75612446.76 | 0.286721E+09 | 3931996.90 |
October | 0.132704E+09 | 52757419.02 | 79946835.82 | 0.311518E+09 | 16786968.86 |
November | 0.141677E+09 | 68298945.76 | 73378249.49 | 0.281541E+09 | 42304740.49 |
December | 0.135903E+09 | 67132131.21 | 68771213.22 | 0.235960E+09 | 78197031.30 |
Annual Sum or Average | 0.122489E+10 | 0.366794E+09 | 0.858094E+09 | 0.292506E+10 | 0.412683E+09 |
Minimum of Months | 64141529.09 | 79377.56 | 64062151.53 | 0.186072E+09 | 5737.61 |
Maximum of Months | 0.141677E+09 | 68298945.76 | 79946835.82 | 0.311518E+09 | 92802394.40 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.136752E+09 | 64293395.40 | 72458816.16 | 0.224062E+09 | 92802394.40 |
February | 0.115989E+09 | 47444481.46 | 68544281.97 | 0.201795E+09 | 71083826.01 |
March | 0.105692E+09 | 28694877.00 | 76997385.59 | 0.205744E+09 | 60233339.83 |
April | 80401979.59 | 8524131.67 | 71877847.93 | 0.186072E+09 | 35972117.03 |
May | 70377678.63 | 1077764.15 | 69299914.48 | 0.215199E+09 | 9215275.15 |
June | 64141529.09 | 79377.56 | 64062151.53 | 0.218590E+09 | 2052279.94 |
July | 66277787.06 | 563159.07 | 65714628.00 | 0.263816E+09 | 97256.74 |
August | 76876963.45 | 5447043.90 | 71429919.55 | 0.294041E+09 | 5737.61 |
September | 98093415.27 | 22480968.51 | 75612446.76 | 0.286721E+09 | 3931996.90 |
October | 0.132704E+09 | 52757419.02 | 79946835.82 | 0.311518E+09 | 16786968.86 |
November | 0.141677E+09 | 68298945.76 | 73378249.49 | 0.281541E+09 | 42304740.49 |
December | 0.135903E+09 | 67132131.21 | 68771213.22 | 0.235960E+09 | 78197031.30 |
Annual Sum or Average | 0.122489E+10 | 0.366794E+09 | 0.858094E+09 | 0.292506E+10 | 0.412683E+09 |
Minimum of Months | 64141529.09 | 79377.56 | 64062151.53 | 0.186072E+09 | 5737.61 |
Maximum of Months | 0.141677E+09 | 68298945.76 | 79946835.82 | 0.311518E+09 | 92802394.40 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.163499E+09 | 76868206.52 | 86630659.49 | 0.268280E+09 | 0.109990E+09 |
February | 0.138674E+09 | 56723901.05 | 81950501.90 | 0.241441E+09 | 84308377.68 |
March | 0.126364E+09 | 34307158.88 | 92056904.13 | 0.245641E+09 | 71654773.17 |
April | 96127384.99 | 10191322.28 | 85936062.70 | 0.221426E+09 | 42994126.83 |
May | 84142483.08 | 1288558.44 | 82853924.64 | 0.254679E+09 | 11157443.10 |
June | 76686637.46 | 94902.61 | 76591734.85 | 0.258026E+09 | 2590420.91 |
July | 79240715.03 | 673304.42 | 78567410.61 | 0.311598E+09 | 127690.93 |
August | 91912929.25 | 6512402.91 | 85400526.34 | 0.347586E+09 | 11790.01 |
September | 0.117279E+09 | 26877904.32 | 90401092.31 | 0.340069E+09 | 4806545.57 |
October | 0.158659E+09 | 63075968.46 | 95583222.00 | 0.370657E+09 | 20282274.48 |
November | 0.169387E+09 | 81657181.66 | 87729920.01 | 0.335892E+09 | 50555843.95 |
December | 0.162484E+09 | 80262155.91 | 82221817.45 | 0.282155E+09 | 92828977.99 |
Annual Sum or Average | 0.146446E+10 | 0.438533E+09 | 0.102592E+10 | 0.347745E+10 | 0.491308E+09 |
Minimum of Months | 76686637.46 | 94902.61 | 76591734.85 | 0.221426E+09 | 11790.01 |
Maximum of Months | 0.169387E+09 | 81657181.66 | 95583222.00 | 0.370657E+09 | 0.109990E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.136752E+09 | 64293395.40 | 72458816.16 | 0.224514E+09 | 91901353.69 |
February | 0.115989E+09 | 47444481.46 | 68544281.97 | 0.202104E+09 | 70353625.79 |
March | 0.105692E+09 | 28694877.00 | 76997385.59 | 0.205934E+09 | 59639177.40 |
April | 80401979.59 | 8524131.67 | 71877847.93 | 0.186003E+09 | 35820152.42 |
May | 70377678.63 | 1077764.15 | 69299914.48 | 0.214560E+09 | 9387511.53 |
June | 64141529.09 | 79377.56 | 64062151.53 | 0.217638E+09 | 2202344.23 |
July | 66277787.06 | 563159.07 | 65714628.00 | 0.262239E+09 | 118354.61 |
August | 76876963.45 | 5447043.90 | 71429919.55 | 0.292289E+09 | 14617.10 |
September | 98093415.27 | 22480968.51 | 75612446.76 | 0.285582E+09 | 4148419.46 |
October | 0.132704E+09 | 52757419.02 | 79946835.82 | 0.310959E+09 | 17241389.86 |
November | 0.141677E+09 | 68298945.76 | 73378249.49 | 0.281378E+09 | 42432615.25 |
December | 0.135903E+09 | 67132131.21 | 68771213.22 | 0.236148E+09 | 77730328.20 |
Annual Sum or Average | 0.122489E+10 | 0.366794E+09 | 0.858094E+09 | 0.291935E+10 | 0.410990E+09 |
Minimum of Months | 64141529.09 | 79377.56 | 64062151.53 | 0.186003E+09 | 14617.10 |
Maximum of Months | 0.141677E+09 | 68298945.76 | 79946835.82 | 0.310959E+09 | 91901353.69 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.136752E+09 | 64293395.40 | 72458816.16 | 0.224514E+09 | 91901353.69 |
February | 0.115989E+09 | 47444481.46 | 68544281.97 | 0.202104E+09 | 70353625.79 |
March | 0.105692E+09 | 28694877.00 | 76997385.59 | 0.205934E+09 | 59639177.40 |
April | 80401979.59 | 8524131.67 | 71877847.93 | 0.186003E+09 | 35820152.42 |
May | 70377678.63 | 1077764.15 | 69299914.48 | 0.214560E+09 | 9387511.53 |
June | 64141529.09 | 79377.56 | 64062151.53 | 0.217638E+09 | 2202344.23 |
July | 66277787.06 | 563159.07 | 65714628.00 | 0.262239E+09 | 118354.61 |
August | 76876963.45 | 5447043.90 | 71429919.55 | 0.292289E+09 | 14617.10 |
September | 98093415.27 | 22480968.51 | 75612446.76 | 0.285582E+09 | 4148419.46 |
October | 0.132704E+09 | 52757419.02 | 79946835.82 | 0.310959E+09 | 17241389.86 |
November | 0.141677E+09 | 68298945.76 | 73378249.49 | 0.281378E+09 | 42432615.25 |
December | 0.135903E+09 | 67132131.21 | 68771213.22 | 0.236148E+09 | 77730328.20 |
Annual Sum or Average | 0.122489E+10 | 0.366794E+09 | 0.858094E+09 | 0.291935E+10 | 0.410990E+09 |
Minimum of Months | 64141529.09 | 79377.56 | 64062151.53 | 0.186003E+09 | 14617.10 |
Maximum of Months | 0.141677E+09 | 68298945.76 | 79946835.82 | 0.310959E+09 | 91901353.69 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.163499E+09 | 76868206.52 | 86630659.49 | 0.268819E+09 | 0.108935E+09 |
February | 0.138674E+09 | 56723901.05 | 81950501.90 | 0.241810E+09 | 83454762.08 |
March | 0.126364E+09 | 34307158.88 | 92056904.13 | 0.245867E+09 | 70961714.59 |
April | 96127384.99 | 10191322.28 | 85936062.70 | 0.221343E+09 | 42822718.12 |
May | 84142483.08 | 1288558.44 | 82853924.64 | 0.253915E+09 | 11368021.65 |
June | 76686637.46 | 94902.61 | 76591734.85 | 0.256894E+09 | 2776594.10 |
July | 79240715.03 | 673304.42 | 78567410.61 | 0.309718E+09 | 155172.90 |
August | 91912929.25 | 6512402.91 | 85400526.34 | 0.345499E+09 | 24859.41 |
September | 0.117279E+09 | 26877904.32 | 90401092.31 | 0.338717E+09 | 5073684.94 |
October | 0.158659E+09 | 63075968.46 | 95583222.00 | 0.369994E+09 | 20831418.74 |
November | 0.169387E+09 | 81657181.66 | 87729920.01 | 0.335696E+09 | 50715742.54 |
December | 0.162484E+09 | 80262155.91 | 82221817.45 | 0.282380E+09 | 92287428.04 |
Annual Sum or Average | 0.146446E+10 | 0.438533E+09 | 0.102592E+10 | 0.347065E+10 | 0.489407E+09 |
Minimum of Months | 76686637.46 | 94902.61 | 76591734.85 | 0.221343E+09 | 24859.41 |
Maximum of Months | 0.169387E+09 | 81657181.66 | 95583222.00 | 0.369994E+09 | 0.108935E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.136752E+09 | 64293395.40 | 72458816.16 | 0.224685E+09 | 89032765.65 |
February | 0.115989E+09 | 47444481.46 | 68544281.97 | 0.202004E+09 | 67837193.48 |
March | 0.105692E+09 | 28694877.00 | 76997385.59 | 0.205126E+09 | 57705791.93 |
April | 80401979.59 | 8524131.67 | 71877847.93 | 0.183692E+09 | 35781784.68 |
May | 70377678.63 | 1077764.15 | 69299914.48 | 0.208312E+09 | 10489026.71 |
June | 64141529.09 | 79377.56 | 64062151.53 | 0.209559E+09 | 3101584.59 |
July | 66277787.06 | 563159.07 | 65714628.00 | 0.250510E+09 | 285626.93 |
August | 76876963.45 | 5447043.90 | 71429919.55 | 0.279379E+09 | 123649.71 |
September | 98093415.27 | 22480968.51 | 75612446.76 | 0.276839E+09 | 5679245.92 |
October | 0.132704E+09 | 52757419.02 | 79946835.82 | 0.305715E+09 | 20287394.93 |
November | 0.141677E+09 | 68298945.76 | 73378249.49 | 0.278829E+09 | 44131996.27 |
December | 0.135903E+09 | 67132131.21 | 68771213.22 | 0.235631E+09 | 76597252.73 |
Annual Sum or Average | 0.122489E+10 | 0.366794E+09 | 0.858094E+09 | 0.286028E+10 | 0.411053E+09 |
Minimum of Months | 64141529.09 | 79377.56 | 64062151.53 | 0.183692E+09 | 123649.71 |
Maximum of Months | 0.141677E+09 | 68298945.76 | 79946835.82 | 0.305715E+09 | 89032765.65 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.136752E+09 | 64293395.40 | 72458816.16 | 0.224685E+09 | 89032765.65 |
February | 0.115989E+09 | 47444481.46 | 68544281.97 | 0.202004E+09 | 67837193.48 |
March | 0.105692E+09 | 28694877.00 | 76997385.59 | 0.205126E+09 | 57705791.93 |
April | 80401979.59 | 8524131.67 | 71877847.93 | 0.183692E+09 | 35781784.68 |
May | 70377678.63 | 1077764.15 | 69299914.48 | 0.208312E+09 | 10489026.71 |
June | 64141529.09 | 79377.56 | 64062151.53 | 0.209559E+09 | 3101584.59 |
July | 66277787.06 | 563159.07 | 65714628.00 | 0.250510E+09 | 285626.93 |
August | 76876963.45 | 5447043.90 | 71429919.55 | 0.279379E+09 | 123649.71 |
September | 98093415.27 | 22480968.51 | 75612446.76 | 0.276839E+09 | 5679245.92 |
October | 0.132704E+09 | 52757419.02 | 79946835.82 | 0.305715E+09 | 20287394.93 |
November | 0.141677E+09 | 68298945.76 | 73378249.49 | 0.278829E+09 | 44131996.27 |
December | 0.135903E+09 | 67132131.21 | 68771213.22 | 0.235631E+09 | 76597252.73 |
Annual Sum or Average | 0.122489E+10 | 0.366794E+09 | 0.858094E+09 | 0.286028E+10 | 0.411053E+09 |
Minimum of Months | 64141529.09 | 79377.56 | 64062151.53 | 0.183692E+09 | 123649.71 |
Maximum of Months | 0.141677E+09 | 68298945.76 | 79946835.82 | 0.305715E+09 | 89032765.65 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.163499E+09 | 76868206.52 | 86630659.49 | 0.269008E+09 | 0.105569E+09 |
February | 0.138674E+09 | 56723901.05 | 81950501.90 | 0.241680E+09 | 80508765.35 |
March | 0.126364E+09 | 34307158.88 | 92056904.13 | 0.244890E+09 | 68693461.72 |
April | 96127384.99 | 10191322.28 | 85936062.70 | 0.218572E+09 | 42791773.45 |
May | 84142483.08 | 1288558.44 | 82853924.64 | 0.246465E+09 | 12693610.15 |
June | 76686637.46 | 94902.61 | 76591734.85 | 0.247297E+09 | 3879024.90 |
July | 79240715.03 | 673304.42 | 78567410.61 | 0.295768E+09 | 369281.33 |
August | 91912929.25 | 6512402.91 | 85400526.34 | 0.330141E+09 | 167918.63 |
September | 0.117279E+09 | 26877904.32 | 90401092.31 | 0.328349E+09 | 6951737.95 |
October | 0.158659E+09 | 63075968.46 | 95583222.00 | 0.363726E+09 | 24460301.18 |
November | 0.169387E+09 | 81657181.66 | 87729920.01 | 0.332642E+09 | 52748758.51 |
December | 0.162484E+09 | 80262155.91 | 82221817.45 | 0.281747E+09 | 90964074.88 |
Annual Sum or Average | 0.146446E+10 | 0.438533E+09 | 0.102592E+10 | 0.340029E+10 | 0.489798E+09 |
Minimum of Months | 76686637.46 | 94902.61 | 76591734.85 | 0.218572E+09 | 167918.63 |
Maximum of Months | 0.169387E+09 | 81657181.66 | 95583222.00 | 0.363726E+09 | 0.105569E+09 |
Report: WindowZoneSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 534.05 | 225.17 | 326.99 | 153.73 | 173.26 | 0.00 | 0.00 |
February | 533.03 | 189.68 | 307.06 | 125.60 | 181.46 | 0.00 | 0.00 |
March | 490.06 | 144.87 | 252.72 | 68.61 | 184.11 | 0.00 | 0.00 |
April | 458.89 | 87.34 | 198.66 | 21.06 | 177.60 | 0.00 | 0.00 |
May | 517.90 | 21.47 | 168.28 | 2.58 | 165.70 | 0.00 | 0.00 |
June | 542.74 | 5.59 | 158.48 | 0.20 | 158.28 | 0.00 | 0.00 |
July | 638.72 | 0.13 | 158.48 | 1.35 | 157.13 | 0.00 | 0.00 |
August | 706.42 | 0.09 | 183.82 | 13.02 | 170.80 | 0.00 | 0.00 |
September | 714.75 | 10.21 | 242.37 | 55.55 | 186.82 | 0.00 | 0.00 |
October | 748.14 | 38.28 | 317.31 | 126.15 | 191.16 | 0.00 | 0.00 |
November | 693.79 | 102.34 | 350.06 | 168.75 | 181.30 | 0.00 | 0.00 |
December | 562.94 | 187.25 | 324.96 | 160.52 | 164.44 | 0.00 | 0.00 |
Annual Sum or Average | 595.55 | 83.86 | 248.75 | 74.49 | 174.26 | 0.00 | 0.00 |
Minimum of Months | 458.89 | 0.09 | 158.48 | 0.20 | 157.13 | 0.00 | 0.00 |
Maximum of Months | 748.14 | 225.17 | 350.06 | 168.75 | 191.16 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 265.52 | 114.83 | 163.49 | 76.87 | 86.63 | 0.00 | 0.00 |
February | 265.51 | 96.82 | 153.53 | 62.80 | 90.73 | 0.00 | 0.00 |
March | 244.87 | 73.82 | 126.36 | 34.31 | 92.05 | 0.00 | 0.00 |
April | 230.58 | 44.35 | 99.33 | 10.53 | 88.80 | 0.00 | 0.00 |
May | 262.72 | 10.62 | 84.14 | 1.29 | 82.85 | 0.00 | 0.00 |
June | 276.68 | 2.51 | 79.24 | 0.10 | 79.14 | 0.00 | 0.00 |
July | 326.23 | 0.05 | 79.24 | 0.67 | 78.56 | 0.00 | 0.00 |
August | 360.97 | 0.02 | 91.91 | 6.51 | 85.40 | 0.00 | 0.00 |
September | 362.78 | 4.65 | 121.18 | 27.77 | 93.41 | 0.00 | 0.00 |
October | 377.31 | 18.34 | 158.65 | 63.07 | 95.58 | 0.00 | 0.00 |
November | 347.99 | 50.70 | 175.03 | 84.38 | 90.65 | 0.00 | 0.00 |
December | 280.84 | 94.69 | 162.48 | 80.26 | 82.22 | 0.00 | 0.00 |
Annual Sum or Average | 300.40 | 42.36 | 124.37 | 37.24 | 87.13 | 0.00 | 0.00 |
Minimum of Months | 230.58 | 0.02 | 79.24 | 0.10 | 78.56 | 0.00 | 0.00 |
Maximum of Months | 377.31 | 114.83 | 175.03 | 84.38 | 95.58 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 265.28 | 117.19 | 163.16 | 76.71 | 86.45 | 0.00 | 0.00 |
February | 264.97 | 99.98 | 153.21 | 62.67 | 90.54 | 0.00 | 0.00 |
March | 243.77 | 77.81 | 126.10 | 34.24 | 91.87 | 0.00 | 0.00 |
April | 227.51 | 49.30 | 99.12 | 10.51 | 88.62 | 0.00 | 0.00 |
May | 252.65 | 12.99 | 83.97 | 1.29 | 82.68 | 0.00 | 0.00 |
June | 264.22 | 3.57 | 79.08 | 0.10 | 78.98 | 0.00 | 0.00 |
July | 309.95 | 0.15 | 79.08 | 0.67 | 78.40 | 0.00 | 0.00 |
August | 345.30 | 0.06 | 91.72 | 6.50 | 85.22 | 0.00 | 0.00 |
September | 349.61 | 5.87 | 120.94 | 27.72 | 93.22 | 0.00 | 0.00 |
October | 369.42 | 22.87 | 158.33 | 62.94 | 95.38 | 0.00 | 0.00 |
November | 346.18 | 57.11 | 174.67 | 84.20 | 90.47 | 0.00 | 0.00 |
December | 280.34 | 98.97 | 162.15 | 80.09 | 82.05 | 0.00 | 0.00 |
Annual Sum or Average | 293.46 | 45.22 | 124.12 | 37.17 | 86.95 | 0.00 | 0.00 |
Minimum of Months | 227.51 | 0.06 | 79.08 | 0.10 | 78.40 | 0.00 | 0.00 |
Maximum of Months | 369.42 | 117.19 | 174.67 | 84.20 | 95.38 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 265.56 | 116.44 | 163.16 | 76.71 | 86.45 | 0.00 | 0.00 |
February | 265.13 | 99.53 | 153.21 | 62.67 | 90.54 | 0.00 | 0.00 |
March | 243.83 | 77.66 | 126.10 | 34.24 | 91.87 | 0.00 | 0.00 |
April | 227.43 | 49.65 | 99.12 | 10.51 | 88.62 | 0.00 | 0.00 |
May | 251.90 | 13.53 | 83.97 | 1.29 | 82.68 | 0.00 | 0.00 |
June | 263.05 | 3.93 | 79.08 | 0.10 | 78.98 | 0.00 | 0.00 |
July | 308.01 | 0.20 | 79.08 | 0.67 | 78.40 | 0.00 | 0.00 |
August | 343.38 | 0.07 | 91.72 | 6.50 | 85.22 | 0.00 | 0.00 |
September | 348.37 | 6.27 | 120.94 | 27.72 | 93.22 | 0.00 | 0.00 |
October | 368.98 | 23.76 | 158.33 | 62.94 | 95.38 | 0.00 | 0.00 |
November | 346.08 | 57.54 | 174.67 | 84.20 | 90.47 | 0.00 | 0.00 |
December | 280.43 | 98.72 | 162.15 | 80.09 | 82.05 | 0.00 | 0.00 |
Annual Sum or Average | 292.87 | 45.34 | 124.12 | 37.17 | 86.95 | 0.00 | 0.00 |
Minimum of Months | 227.43 | 0.07 | 79.08 | 0.10 | 78.40 | 0.00 | 0.00 |
Maximum of Months | 368.98 | 116.44 | 174.67 | 84.20 | 95.38 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 266.20 | 114.97 | 163.16 | 76.71 | 86.45 | 0.00 | 0.00 |
February | 265.62 | 98.21 | 153.21 | 62.67 | 90.54 | 0.00 | 0.00 |
March | 244.28 | 76.42 | 126.10 | 34.24 | 91.87 | 0.00 | 0.00 |
April | 227.84 | 48.58 | 99.12 | 10.51 | 88.62 | 0.00 | 0.00 |
May | 252.60 | 13.03 | 83.97 | 1.29 | 82.68 | 0.00 | 0.00 |
June | 263.94 | 3.66 | 79.08 | 0.10 | 78.98 | 0.00 | 0.00 |
July | 308.96 | 0.18 | 79.08 | 0.67 | 78.40 | 0.00 | 0.00 |
August | 344.39 | 0.06 | 91.72 | 6.50 | 85.22 | 0.00 | 0.00 |
September | 349.08 | 5.98 | 120.94 | 27.72 | 93.22 | 0.00 | 0.00 |
October | 369.38 | 23.05 | 158.33 | 62.94 | 95.38 | 0.00 | 0.00 |
November | 346.43 | 56.55 | 174.67 | 84.20 | 90.47 | 0.00 | 0.00 |
December | 280.86 | 97.51 | 162.15 | 80.09 | 82.05 | 0.00 | 0.00 |
Annual Sum or Average | 293.49 | 44.59 | 124.12 | 37.17 | 86.95 | 0.00 | 0.00 |
Minimum of Months | 227.84 | 0.06 | 79.08 | 0.10 | 78.40 | 0.00 | 0.00 |
Maximum of Months | 369.38 | 114.97 | 174.67 | 84.20 | 95.38 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 535.29 | 222.56 | 326.32 | 153.42 | 172.90 | 0.00 | 0.00 |
February | 533.43 | 189.36 | 306.43 | 125.34 | 181.08 | 0.00 | 0.00 |
March | 490.17 | 145.98 | 252.20 | 68.47 | 183.73 | 0.00 | 0.00 |
April | 456.37 | 91.28 | 198.25 | 21.02 | 177.23 | 0.00 | 0.00 |
May | 506.67 | 23.55 | 167.93 | 2.57 | 165.36 | 0.00 | 0.00 |
June | 529.69 | 6.02 | 158.16 | 0.20 | 157.96 | 0.00 | 0.00 |
July | 618.95 | 0.29 | 158.15 | 1.34 | 156.81 | 0.00 | 0.00 |
August | 690.63 | 0.06 | 183.44 | 13.00 | 170.45 | 0.00 | 0.00 |
September | 699.37 | 10.70 | 241.87 | 55.43 | 186.44 | 0.00 | 0.00 |
October | 739.27 | 42.58 | 316.66 | 125.89 | 190.77 | 0.00 | 0.00 |
November | 692.81 | 107.07 | 349.34 | 168.41 | 180.93 | 0.00 | 0.00 |
December | 563.21 | 188.25 | 324.29 | 160.19 | 164.10 | 0.00 | 0.00 |
Annual Sum or Average | 588.36 | 85.14 | 248.24 | 74.34 | 173.90 | 0.00 | 0.00 |
Minimum of Months | 456.37 | 0.06 | 158.15 | 0.20 | 156.81 | 0.00 | 0.00 |
Maximum of Months | 739.27 | 222.56 | 349.34 | 168.41 | 190.77 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 267.23 | 110.78 | 163.16 | 76.71 | 86.45 | 0.00 | 0.00 |
February | 266.42 | 94.00 | 153.21 | 62.67 | 90.54 | 0.00 | 0.00 |
March | 245.16 | 72.07 | 126.10 | 34.24 | 91.87 | 0.00 | 0.00 |
April | 228.85 | 44.58 | 99.12 | 10.51 | 88.62 | 0.00 | 0.00 |
May | 255.59 | 11.13 | 83.97 | 1.29 | 82.68 | 0.00 | 0.00 |
June | 268.01 | 2.62 | 79.08 | 0.10 | 78.98 | 0.00 | 0.00 |
July | 313.16 | 0.12 | 79.08 | 0.67 | 78.40 | 0.00 | 0.00 |
August | 349.17 | 0.01 | 91.72 | 6.50 | 85.22 | 0.00 | 0.00 |
September | 352.28 | 4.92 | 120.94 | 27.72 | 93.22 | 0.00 | 0.00 |
October | 370.87 | 20.21 | 158.33 | 62.94 | 95.38 | 0.00 | 0.00 |
November | 346.70 | 52.34 | 174.67 | 84.20 | 90.47 | 0.00 | 0.00 |
December | 281.38 | 93.36 | 162.15 | 80.09 | 82.05 | 0.00 | 0.00 |
Annual Sum or Average | 295.60 | 41.93 | 124.12 | 37.17 | 86.95 | 0.00 | 0.00 |
Minimum of Months | 228.85 | 0.01 | 79.08 | 0.10 | 78.40 | 0.00 | 0.00 |
Maximum of Months | 370.87 | 110.78 | 174.67 | 84.20 | 95.38 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 267.47 | 110.36 | 163.16 | 76.71 | 86.45 | 0.00 | 0.00 |
February | 266.63 | 93.62 | 153.21 | 62.67 | 90.54 | 0.00 | 0.00 |
March | 245.34 | 71.73 | 126.10 | 34.24 | 91.87 | 0.00 | 0.00 |
April | 229.00 | 44.34 | 99.12 | 10.51 | 88.62 | 0.00 | 0.00 |
May | 255.78 | 11.05 | 83.97 | 1.29 | 82.68 | 0.00 | 0.00 |
June | 268.21 | 2.58 | 79.08 | 0.10 | 78.98 | 0.00 | 0.00 |
July | 313.33 | 0.12 | 79.08 | 0.67 | 78.40 | 0.00 | 0.00 |
August | 349.34 | 0.01 | 91.72 | 6.50 | 85.22 | 0.00 | 0.00 |
September | 352.43 | 4.89 | 120.94 | 27.72 | 93.22 | 0.00 | 0.00 |
October | 371.00 | 20.11 | 158.33 | 62.94 | 95.38 | 0.00 | 0.00 |
November | 346.83 | 52.15 | 174.67 | 84.20 | 90.47 | 0.00 | 0.00 |
December | 281.54 | 93.05 | 162.15 | 80.09 | 82.05 | 0.00 | 0.00 |
Annual Sum or Average | 295.77 | 41.75 | 124.12 | 37.17 | 86.95 | 0.00 | 0.00 |
Minimum of Months | 229.00 | 0.01 | 79.08 | 0.10 | 78.40 | 0.00 | 0.00 |
Maximum of Months | 371.00 | 110.36 | 174.67 | 84.20 | 95.38 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 268.01 | 109.30 | 163.16 | 76.71 | 86.45 | 0.00 | 0.00 |
February | 267.04 | 92.66 | 153.21 | 62.67 | 90.54 | 0.00 | 0.00 |
March | 245.57 | 71.03 | 126.10 | 34.24 | 91.87 | 0.00 | 0.00 |
April | 228.91 | 44.16 | 99.12 | 10.51 | 88.62 | 0.00 | 0.00 |
May | 255.02 | 11.25 | 83.97 | 1.29 | 82.68 | 0.00 | 0.00 |
June | 267.04 | 2.77 | 79.08 | 0.10 | 78.98 | 0.00 | 0.00 |
July | 311.45 | 0.15 | 79.08 | 0.67 | 78.40 | 0.00 | 0.00 |
August | 347.25 | 0.02 | 91.72 | 6.50 | 85.22 | 0.00 | 0.00 |
September | 351.03 | 5.16 | 120.94 | 27.72 | 93.22 | 0.00 | 0.00 |
October | 370.34 | 20.65 | 158.33 | 62.94 | 95.38 | 0.00 | 0.00 |
November | 346.62 | 52.31 | 174.67 | 84.20 | 90.47 | 0.00 | 0.00 |
December | 281.76 | 92.50 | 162.15 | 80.09 | 82.05 | 0.00 | 0.00 |
Annual Sum or Average | 295.20 | 41.58 | 124.12 | 37.17 | 86.95 | 0.00 | 0.00 |
Minimum of Months | 228.91 | 0.02 | 79.08 | 0.10 | 78.40 | 0.00 | 0.00 |
Maximum of Months | 370.34 | 109.30 | 174.67 | 84.20 | 95.38 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 268.21 | 105.90 | 163.16 | 76.71 | 86.45 | 0.00 | 0.00 |
February | 266.90 | 89.36 | 153.21 | 62.67 | 90.54 | 0.00 | 0.00 |
March | 244.60 | 68.74 | 126.10 | 34.24 | 91.87 | 0.00 | 0.00 |
April | 226.06 | 44.12 | 99.12 | 10.51 | 88.62 | 0.00 | 0.00 |
May | 247.57 | 12.57 | 83.97 | 1.29 | 82.68 | 0.00 | 0.00 |
June | 257.10 | 3.89 | 79.08 | 0.10 | 78.98 | 0.00 | 0.00 |
July | 297.49 | 0.35 | 79.08 | 0.67 | 78.40 | 0.00 | 0.00 |
August | 331.88 | 0.15 | 91.72 | 6.50 | 85.22 | 0.00 | 0.00 |
September | 340.29 | 7.06 | 120.94 | 27.72 | 93.22 | 0.00 | 0.00 |
October | 364.08 | 24.28 | 158.33 | 62.94 | 95.38 | 0.00 | 0.00 |
November | 343.48 | 54.40 | 174.67 | 84.20 | 90.47 | 0.00 | 0.00 |
December | 281.14 | 91.16 | 162.15 | 80.09 | 82.05 | 0.00 | 0.00 |
Annual Sum or Average | 289.22 | 41.60 | 124.12 | 37.17 | 86.95 | 0.00 | 0.00 |
Minimum of Months | 226.06 | 0.15 | 79.08 | 0.10 | 78.40 | 0.00 | 0.00 |
Maximum of Months | 364.08 | 105.90 | 174.67 | 84.20 | 95.38 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.143040E+10 | 0.603086E+09 | 0.875803E+09 | 0.411755E+09 | 0.464049E+09 | 0.00 | 0.00 |
February | 0.128951E+10 | 0.458878E+09 | 0.742828E+09 | 0.303849E+09 | 0.438979E+09 | 0.00 | 0.00 |
March | 0.131257E+10 | 0.388028E+09 | 0.676886E+09 | 0.183771E+09 | 0.493115E+09 | 0.00 | 0.00 |
April | 0.118944E+10 | 0.226374E+09 | 0.514919E+09 | 54591163.78 | 0.460328E+09 | 0.00 | 0.00 |
May | 0.138713E+10 | 57498728.86 | 0.450720E+09 | 6902333.46 | 0.443818E+09 | 0.00 | 0.00 |
June | 0.140679E+10 | 14490326.49 | 0.410782E+09 | 508358.34 | 0.410274E+09 | 0.00 | 0.00 |
July | 0.171076E+10 | 356727.27 | 0.424463E+09 | 3606644.05 | 0.420857E+09 | 0.00 | 0.00 |
August | 0.189209E+10 | 228800.99 | 0.492344E+09 | 34884546.30 | 0.457459E+09 | 0.00 | 0.00 |
September | 0.185263E+10 | 26469826.96 | 0.628220E+09 | 0.143975E+09 | 0.484245E+09 | 0.00 | 0.00 |
October | 0.200382E+10 | 0.102527E+09 | 0.849879E+09 | 0.337875E+09 | 0.512004E+09 | 0.00 | 0.00 |
November | 0.179832E+10 | 0.265261E+09 | 0.907344E+09 | 0.437407E+09 | 0.469937E+09 | 0.00 | 0.00 |
December | 0.150777E+10 | 0.501519E+09 | 0.870367E+09 | 0.429935E+09 | 0.440432E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.187812E+11 | 0.264472E+10 | 0.784456E+10 | 0.234906E+10 | 0.549550E+10 | 0.00 | 0.00 |
Minimum of Months | 0.118944E+10 | 228800.99 | 0.410782E+09 | 508358.34 | 0.410274E+09 | 0.00 | 0.00 |
Maximum of Months | 0.200382E+10 | 0.603086E+09 | 0.907344E+09 | 0.437407E+09 | 0.512004E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.711158E+09 | 0.307562E+09 | 0.437902E+09 | 0.205877E+09 | 0.232024E+09 | 0.00 | 0.00 |
February | 0.642314E+09 | 0.234219E+09 | 0.371414E+09 | 0.151925E+09 | 0.219489E+09 | 0.00 | 0.00 |
March | 0.655861E+09 | 0.197722E+09 | 0.338443E+09 | 91885413.74 | 0.246557E+09 | 0.00 | 0.00 |
April | 0.597669E+09 | 0.114943E+09 | 0.257460E+09 | 27295581.89 | 0.230164E+09 | 0.00 | 0.00 |
May | 0.703659E+09 | 28441748.20 | 0.225360E+09 | 3451166.73 | 0.221909E+09 | 0.00 | 0.00 |
June | 0.717149E+09 | 6503030.82 | 0.205391E+09 | 254179.17 | 0.205137E+09 | 0.00 | 0.00 |
July | 0.873768E+09 | 129719.52 | 0.212232E+09 | 1803322.02 | 0.210428E+09 | 0.00 | 0.00 |
August | 0.966833E+09 | 45276.91 | 0.246172E+09 | 17442273.15 | 0.228730E+09 | 0.00 | 0.00 |
September | 0.940314E+09 | 12043268.60 | 0.314110E+09 | 71987522.14 | 0.242123E+09 | 0.00 | 0.00 |
October | 0.101057E+10 | 49121358.53 | 0.424939E+09 | 0.168937E+09 | 0.256002E+09 | 0.00 | 0.00 |
November | 0.901995E+09 | 0.131402E+09 | 0.453672E+09 | 0.218704E+09 | 0.234968E+09 | 0.00 | 0.00 |
December | 0.752193E+09 | 0.253622E+09 | 0.435183E+09 | 0.214967E+09 | 0.220216E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.947349E+10 | 0.133575E+10 | 0.392228E+10 | 0.117453E+10 | 0.274775E+10 | 0.00 | 0.00 |
Minimum of Months | 0.597669E+09 | 45276.91 | 0.205391E+09 | 254179.17 | 0.205137E+09 | 0.00 | 0.00 |
Maximum of Months | 0.101057E+10 | 0.307562E+09 | 0.453672E+09 | 0.218704E+09 | 0.256002E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.710525E+09 | 0.313889E+09 | 0.437003E+09 | 0.205455E+09 | 0.231548E+09 | 0.00 | 0.00 |
February | 0.641018E+09 | 0.241882E+09 | 0.370652E+09 | 0.151613E+09 | 0.219039E+09 | 0.00 | 0.00 |
March | 0.652918E+09 | 0.208413E+09 | 0.337749E+09 | 91696912.87 | 0.246052E+09 | 0.00 | 0.00 |
April | 0.589695E+09 | 0.127795E+09 | 0.256931E+09 | 27239585.61 | 0.229692E+09 | 0.00 | 0.00 |
May | 0.676697E+09 | 34785738.44 | 0.224898E+09 | 3444086.74 | 0.221454E+09 | 0.00 | 0.00 |
June | 0.684846E+09 | 9260451.25 | 0.204970E+09 | 253657.73 | 0.204716E+09 | 0.00 | 0.00 |
July | 0.830160E+09 | 393384.82 | 0.211796E+09 | 1799622.55 | 0.209997E+09 | 0.00 | 0.00 |
August | 0.924847E+09 | 151200.93 | 0.245667E+09 | 17406490.71 | 0.228260E+09 | 0.00 | 0.00 |
September | 0.906182E+09 | 15204972.74 | 0.313466E+09 | 71839841.35 | 0.241626E+09 | 0.00 | 0.00 |
October | 0.989443E+09 | 61251825.13 | 0.424068E+09 | 0.168591E+09 | 0.255477E+09 | 0.00 | 0.00 |
November | 0.897286E+09 | 0.148038E+09 | 0.452741E+09 | 0.218255E+09 | 0.234486E+09 | 0.00 | 0.00 |
December | 0.750858E+09 | 0.265083E+09 | 0.434291E+09 | 0.214526E+09 | 0.219764E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.925448E+10 | 0.142615E+10 | 0.391423E+10 | 0.117212E+10 | 0.274211E+10 | 0.00 | 0.00 |
Minimum of Months | 0.589695E+09 | 151200.93 | 0.204970E+09 | 253657.73 | 0.204716E+09 | 0.00 | 0.00 |
Maximum of Months | 0.989443E+09 | 0.313889E+09 | 0.452741E+09 | 0.218255E+09 | 0.255477E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.711282E+09 | 0.311885E+09 | 0.437003E+09 | 0.205455E+09 | 0.231548E+09 | 0.00 | 0.00 |
February | 0.641394E+09 | 0.240773E+09 | 0.370652E+09 | 0.151613E+09 | 0.219039E+09 | 0.00 | 0.00 |
March | 0.653085E+09 | 0.208017E+09 | 0.337749E+09 | 91696912.87 | 0.246052E+09 | 0.00 | 0.00 |
April | 0.589486E+09 | 0.128681E+09 | 0.256931E+09 | 27239585.61 | 0.229692E+09 | 0.00 | 0.00 |
May | 0.674682E+09 | 36241932.95 | 0.224898E+09 | 3444086.74 | 0.221454E+09 | 0.00 | 0.00 |
June | 0.681838E+09 | 10183114.35 | 0.204970E+09 | 253657.73 | 0.204716E+09 | 0.00 | 0.00 |
July | 0.824987E+09 | 527505.24 | 0.211796E+09 | 1799622.55 | 0.209997E+09 | 0.00 | 0.00 |
August | 0.919721E+09 | 192081.60 | 0.245667E+09 | 17406490.71 | 0.228260E+09 | 0.00 | 0.00 |
September | 0.902968E+09 | 16257143.06 | 0.313466E+09 | 71839841.35 | 0.241626E+09 | 0.00 | 0.00 |
October | 0.988282E+09 | 63651447.12 | 0.424068E+09 | 0.168591E+09 | 0.255477E+09 | 0.00 | 0.00 |
November | 0.897044E+09 | 0.149134E+09 | 0.452741E+09 | 0.218255E+09 | 0.234486E+09 | 0.00 | 0.00 |
December | 0.751105E+09 | 0.264402E+09 | 0.434291E+09 | 0.214526E+09 | 0.219764E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.923587E+10 | 0.142995E+10 | 0.391423E+10 | 0.117212E+10 | 0.274211E+10 | 0.00 | 0.00 |
Minimum of Months | 0.589486E+09 | 192081.60 | 0.204970E+09 | 253657.73 | 0.204716E+09 | 0.00 | 0.00 |
Maximum of Months | 0.988282E+09 | 0.311885E+09 | 0.452741E+09 | 0.218255E+09 | 0.255477E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.712987E+09 | 0.307940E+09 | 0.437003E+09 | 0.205455E+09 | 0.231548E+09 | 0.00 | 0.00 |
February | 0.642591E+09 | 0.237582E+09 | 0.370652E+09 | 0.151613E+09 | 0.219039E+09 | 0.00 | 0.00 |
March | 0.654291E+09 | 0.204686E+09 | 0.337749E+09 | 91696912.87 | 0.246052E+09 | 0.00 | 0.00 |
April | 0.590562E+09 | 0.125929E+09 | 0.256931E+09 | 27239585.61 | 0.229692E+09 | 0.00 | 0.00 |
May | 0.676554E+09 | 34906724.91 | 0.224898E+09 | 3444086.74 | 0.221454E+09 | 0.00 | 0.00 |
June | 0.684139E+09 | 9484917.73 | 0.204970E+09 | 253657.73 | 0.204716E+09 | 0.00 | 0.00 |
July | 0.827507E+09 | 473332.54 | 0.211796E+09 | 1799622.55 | 0.209997E+09 | 0.00 | 0.00 |
August | 0.922416E+09 | 156516.26 | 0.245667E+09 | 17406490.71 | 0.228260E+09 | 0.00 | 0.00 |
September | 0.904819E+09 | 15500553.55 | 0.313466E+09 | 71839841.35 | 0.241626E+09 | 0.00 | 0.00 |
October | 0.989352E+09 | 61731385.16 | 0.424068E+09 | 0.168591E+09 | 0.255477E+09 | 0.00 | 0.00 |
November | 0.897954E+09 | 0.146572E+09 | 0.452741E+09 | 0.218255E+09 | 0.234486E+09 | 0.00 | 0.00 |
December | 0.752259E+09 | 0.261170E+09 | 0.434291E+09 | 0.214526E+09 | 0.219764E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.925543E+10 | 0.140613E+10 | 0.391423E+10 | 0.117212E+10 | 0.274211E+10 | 0.00 | 0.00 |
Minimum of Months | 0.590562E+09 | 156516.26 | 0.204970E+09 | 253657.73 | 0.204716E+09 | 0.00 | 0.00 |
Maximum of Months | 0.989352E+09 | 0.307940E+09 | 0.452741E+09 | 0.218255E+09 | 0.255477E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.143373E+10 | 0.596107E+09 | 0.874007E+09 | 0.410910E+09 | 0.463097E+09 | 0.00 | 0.00 |
February | 0.129046E+10 | 0.458098E+09 | 0.741304E+09 | 0.303226E+09 | 0.438078E+09 | 0.00 | 0.00 |
March | 0.131286E+10 | 0.390983E+09 | 0.675497E+09 | 0.183394E+09 | 0.492103E+09 | 0.00 | 0.00 |
April | 0.118291E+10 | 0.236598E+09 | 0.513863E+09 | 54479171.23 | 0.459384E+09 | 0.00 | 0.00 |
May | 0.135706E+10 | 63074863.03 | 0.449796E+09 | 6888173.48 | 0.442908E+09 | 0.00 | 0.00 |
June | 0.137295E+10 | 15609752.33 | 0.409939E+09 | 507315.46 | 0.409432E+09 | 0.00 | 0.00 |
July | 0.165779E+10 | 772355.74 | 0.423593E+09 | 3599245.10 | 0.419993E+09 | 0.00 | 0.00 |
August | 0.184979E+10 | 149940.91 | 0.491334E+09 | 34812981.43 | 0.456521E+09 | 0.00 | 0.00 |
September | 0.181276E+10 | 27740236.43 | 0.626932E+09 | 0.143680E+09 | 0.483252E+09 | 0.00 | 0.00 |
October | 0.198006E+10 | 0.114052E+09 | 0.848135E+09 | 0.337182E+09 | 0.510954E+09 | 0.00 | 0.00 |
November | 0.179576E+10 | 0.277523E+09 | 0.905483E+09 | 0.436510E+09 | 0.468973E+09 | 0.00 | 0.00 |
December | 0.150849E+10 | 0.504207E+09 | 0.868581E+09 | 0.429053E+09 | 0.439528E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.185546E+11 | 0.268491E+10 | 0.782846E+10 | 0.234424E+10 | 0.548422E+10 | 0.00 | 0.00 |
Minimum of Months | 0.118291E+10 | 149940.91 | 0.409939E+09 | 507315.46 | 0.409432E+09 | 0.00 | 0.00 |
Maximum of Months | 0.198006E+10 | 0.596107E+09 | 0.905483E+09 | 0.436510E+09 | 0.510954E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.715746E+09 | 0.296713E+09 | 0.437003E+09 | 0.205455E+09 | 0.231548E+09 | 0.00 | 0.00 |
February | 0.644528E+09 | 0.227412E+09 | 0.370652E+09 | 0.151613E+09 | 0.219039E+09 | 0.00 | 0.00 |
March | 0.656647E+09 | 0.193026E+09 | 0.337749E+09 | 91696912.87 | 0.246052E+09 | 0.00 | 0.00 |
April | 0.593184E+09 | 0.115547E+09 | 0.256931E+09 | 27239585.61 | 0.229692E+09 | 0.00 | 0.00 |
May | 0.684584E+09 | 29798525.60 | 0.224898E+09 | 3444086.74 | 0.221454E+09 | 0.00 | 0.00 |
June | 0.694669E+09 | 6778731.50 | 0.204970E+09 | 253657.73 | 0.204716E+09 | 0.00 | 0.00 |
July | 0.838763E+09 | 320674.49 | 0.211796E+09 | 1799622.55 | 0.209997E+09 | 0.00 | 0.00 |
August | 0.935216E+09 | 24965.52 | 0.245667E+09 | 17406490.71 | 0.228260E+09 | 0.00 | 0.00 |
September | 0.913100E+09 | 12747953.98 | 0.313466E+09 | 71839841.35 | 0.241626E+09 | 0.00 | 0.00 |
October | 0.993351E+09 | 54120438.85 | 0.424068E+09 | 0.168591E+09 | 0.255477E+09 | 0.00 | 0.00 |
November | 0.898645E+09 | 0.135659E+09 | 0.452741E+09 | 0.218255E+09 | 0.234486E+09 | 0.00 | 0.00 |
December | 0.753636E+09 | 0.250047E+09 | 0.434291E+09 | 0.214526E+09 | 0.219764E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.932207E+10 | 0.132220E+10 | 0.391423E+10 | 0.117212E+10 | 0.274211E+10 | 0.00 | 0.00 |
Minimum of Months | 0.593184E+09 | 24965.52 | 0.204970E+09 | 253657.73 | 0.204716E+09 | 0.00 | 0.00 |
Maximum of Months | 0.993351E+09 | 0.296713E+09 | 0.452741E+09 | 0.218255E+09 | 0.255477E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.716404E+09 | 0.295594E+09 | 0.437003E+09 | 0.205455E+09 | 0.231548E+09 | 0.00 | 0.00 |
February | 0.645030E+09 | 0.226475E+09 | 0.370652E+09 | 0.151613E+09 | 0.219039E+09 | 0.00 | 0.00 |
March | 0.657130E+09 | 0.192121E+09 | 0.337749E+09 | 91696912.87 | 0.246052E+09 | 0.00 | 0.00 |
April | 0.593570E+09 | 0.114938E+09 | 0.256931E+09 | 27239585.61 | 0.229692E+09 | 0.00 | 0.00 |
May | 0.685076E+09 | 29586924.28 | 0.224898E+09 | 3444086.74 | 0.221454E+09 | 0.00 | 0.00 |
June | 0.695206E+09 | 6693196.40 | 0.204970E+09 | 253657.73 | 0.204716E+09 | 0.00 | 0.00 |
July | 0.839230E+09 | 321837.75 | 0.211796E+09 | 1799622.55 | 0.209997E+09 | 0.00 | 0.00 |
August | 0.935667E+09 | 22400.17 | 0.245667E+09 | 17406490.71 | 0.228260E+09 | 0.00 | 0.00 |
September | 0.913510E+09 | 12668664.04 | 0.313466E+09 | 71839841.35 | 0.241626E+09 | 0.00 | 0.00 |
October | 0.993690E+09 | 53853259.93 | 0.424068E+09 | 0.168591E+09 | 0.255477E+09 | 0.00 | 0.00 |
November | 0.898973E+09 | 0.135164E+09 | 0.452741E+09 | 0.218255E+09 | 0.234486E+09 | 0.00 | 0.00 |
December | 0.754073E+09 | 0.249223E+09 | 0.434291E+09 | 0.214526E+09 | 0.219764E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.932756E+10 | 0.131666E+10 | 0.391423E+10 | 0.117212E+10 | 0.274211E+10 | 0.00 | 0.00 |
Minimum of Months | 0.593570E+09 | 22400.17 | 0.204970E+09 | 253657.73 | 0.204716E+09 | 0.00 | 0.00 |
Maximum of Months | 0.993690E+09 | 0.295594E+09 | 0.452741E+09 | 0.218255E+09 | 0.255477E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.717846E+09 | 0.292737E+09 | 0.437003E+09 | 0.205455E+09 | 0.231548E+09 | 0.00 | 0.00 |
February | 0.646017E+09 | 0.224162E+09 | 0.370652E+09 | 0.151613E+09 | 0.219039E+09 | 0.00 | 0.00 |
March | 0.657734E+09 | 0.190240E+09 | 0.337749E+09 | 91696912.87 | 0.246052E+09 | 0.00 | 0.00 |
April | 0.593347E+09 | 0.114463E+09 | 0.256931E+09 | 27239585.61 | 0.229692E+09 | 0.00 | 0.00 |
May | 0.683034E+09 | 30141968.96 | 0.224898E+09 | 3444086.74 | 0.221454E+09 | 0.00 | 0.00 |
June | 0.692168E+09 | 7179343.07 | 0.204970E+09 | 253657.73 | 0.204716E+09 | 0.00 | 0.00 |
July | 0.834195E+09 | 391505.34 | 0.211796E+09 | 1799622.55 | 0.209997E+09 | 0.00 | 0.00 |
August | 0.930077E+09 | 53548.04 | 0.245667E+09 | 17406490.71 | 0.228260E+09 | 0.00 | 0.00 |
September | 0.909880E+09 | 13368363.90 | 0.313466E+09 | 71839841.35 | 0.241626E+09 | 0.00 | 0.00 |
October | 0.991911E+09 | 55312530.40 | 0.424068E+09 | 0.168591E+09 | 0.255477E+09 | 0.00 | 0.00 |
November | 0.898449E+09 | 0.135579E+09 | 0.452741E+09 | 0.218255E+09 | 0.234486E+09 | 0.00 | 0.00 |
December | 0.754675E+09 | 0.247747E+09 | 0.434291E+09 | 0.214526E+09 | 0.219764E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.930933E+10 | 0.131137E+10 | 0.391423E+10 | 0.117212E+10 | 0.274211E+10 | 0.00 | 0.00 |
Minimum of Months | 0.593347E+09 | 53548.04 | 0.204970E+09 | 253657.73 | 0.204716E+09 | 0.00 | 0.00 |
Maximum of Months | 0.991911E+09 | 0.292737E+09 | 0.452741E+09 | 0.218255E+09 | 0.255477E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.718377E+09 | 0.283634E+09 | 0.437003E+09 | 0.205455E+09 | 0.231548E+09 | 0.00 | 0.00 |
February | 0.645686E+09 | 0.216182E+09 | 0.370652E+09 | 0.151613E+09 | 0.219039E+09 | 0.00 | 0.00 |
March | 0.655141E+09 | 0.184105E+09 | 0.337749E+09 | 91696912.87 | 0.246052E+09 | 0.00 | 0.00 |
April | 0.585955E+09 | 0.114355E+09 | 0.256931E+09 | 27239585.61 | 0.229692E+09 | 0.00 | 0.00 |
May | 0.663088E+09 | 33670453.70 | 0.224898E+09 | 3444086.74 | 0.221454E+09 | 0.00 | 0.00 |
June | 0.666414E+09 | 10080497.36 | 0.204970E+09 | 253657.73 | 0.204716E+09 | 0.00 | 0.00 |
July | 0.796788E+09 | 939684.39 | 0.211796E+09 | 1799622.55 | 0.209997E+09 | 0.00 | 0.00 |
August | 0.888898E+09 | 415041.77 | 0.245667E+09 | 17406490.71 | 0.228260E+09 | 0.00 | 0.00 |
September | 0.882026E+09 | 18308393.82 | 0.313466E+09 | 71839841.35 | 0.241626E+09 | 0.00 | 0.00 |
October | 0.975156E+09 | 65033841.32 | 0.424068E+09 | 0.168591E+09 | 0.255477E+09 | 0.00 | 0.00 |
November | 0.890297E+09 | 0.141010E+09 | 0.452741E+09 | 0.218255E+09 | 0.234486E+09 | 0.00 | 0.00 |
December | 0.753009E+09 | 0.244159E+09 | 0.434291E+09 | 0.214526E+09 | 0.219764E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.912084E+10 | 0.131189E+10 | 0.391423E+10 | 0.117212E+10 | 0.274211E+10 | 0.00 | 0.00 |
Minimum of Months | 0.585955E+09 | 415041.77 | 0.204970E+09 | 253657.73 | 0.204716E+09 | 0.00 | 0.00 |
Maximum of Months | 0.975156E+09 | 0.283634E+09 | 0.452741E+09 | 0.218255E+09 | 0.255477E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 19.24 | 14.74 | 11.63 | 2.95 | 7.91 | 83.00 | 101.34 | 0.00 |
February | 20.75 | 16.26 | 13.46 | 3.66 | 9.80 | 96.50 | 106.33 | 0.00 |
March | 23.12 | 16.75 | 12.67 | 3.48 | 11.63 | 114.51 | 110.36 | 0.00 |
April | 26.49 | 19.17 | 14.91 | 3.36 | 14.65 | 129.52 | 127.73 | 0.00 |
May | 31.37 | 21.91 | 17.14 | 3.30 | 19.37 | 135.62 | 152.47 | 0.00 |
June | 32.97 | 24.78 | 21.39 | 3.95 | 20.59 | 135.23 | 162.31 | 0.00 |
July | 35.08 | 26.48 | 23.16 | 3.85 | 24.14 | 131.49 | 150.69 | 0.00 |
August | 35.31 | 27.02 | 24.10 | 3.89 | 24.33 | 129.32 | 147.63 | 0.00 |
September | 32.49 | 25.68 | 23.13 | 3.64 | 20.59 | 118.70 | 140.92 | 0.00 |
October | 29.53 | 22.66 | 19.34 | 3.16 | 16.84 | 101.82 | 135.23 | 0.00 |
November | 25.53 | 19.62 | 16.50 | 2.98 | 12.88 | 85.82 | 121.41 | 0.00 |
December | 21.13 | 16.84 | 14.23 | 2.84 | 10.14 | 76.46 | 98.30 | 0.00 |
Annual Sum or Average | 27.79 | 21.02 | 17.66 | 3.42 | 16.11 | 111.56 | 129.66 | 0.00 |
Minimum of Months | 19.24 | 14.74 | 11.63 | 2.84 | 7.91 | 76.46 | 98.30 | 0.00 |
Maximum of Months | 35.31 | 27.02 | 24.10 | 3.95 | 24.33 | 135.62 | 162.31 | 0.00 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 28.00 | 23-JAN-13:00 | 16.55 | 9.00 | 4.60 | 16.85 | 268.00 | 249.50 |
February | 32.50 | 06-FEB-14:00 | 17.28 | 6.50 | 6.20 | 21.27 | 242.00 | 327.50 |
March | 38.00 | 27-MAR-10:00 | 18.84 | 6.00 | 7.70 | 21.44 | 329.50 | 440.00 |
April | 42.00 | 28-APR-11:00 | 19.18 | 2.00 | 2.60 | 24.16 | 371.50 | 432.50 |
May | 42.10 | 31-MAY-18:00 | 20.76 | 8.00 | 5.10 | 30.18 | 0.00 | 0.00 |
June | 43.00 | 12-JUN-11:00 | 24.56 | 17.00 | 3.60 | 28.91 | 372.00 | 427.00 |
July | 46.00 | 21-JUL-11:00 | 22.01 | 9.00 | 3.60 | 32.99 | 306.00 | 562.50 |
August | 46.00 | 16-AUG-11:00 | 25.38 | 17.00 | 7.20 | 31.75 | 273.00 | 629.50 |
September | 41.20 | 26-SEP-12:00 | 22.43 | 13.00 | 4.10 | 26.15 | 325.00 | 455.00 |
October | 38.00 | 04-OCT-11:00 | 19.81 | 9.00 | 1.00 | 22.13 | 338.00 | 421.50 |
November | 34.00 | 05-NOV-11:00 | 17.15 | 5.00 | 2.10 | 17.39 | 294.00 | 427.50 |
December | 30.00 | 10-DEC-11:00 | 19.04 | 13.00 | 4.10 | 21.27 | 305.00 | 214.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 28.00 | 16.55 | 2.00 | 1.00 | 16.85 | 0.00 | 0.00 | |
Maximum of Months | 46.00 | 25.38 | 17.00 | 7.70 | 32.99 | 372.00 | 629.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 12.00 | 09-JAN-07:00 | 12.00 | 12.00 | 1.00 | -1.9 | 54.50 | 10.00 |
February | 13.00 | 01-FEB-04:00 | 12.45 | 12.00 | 1.00 | -0.8 | 0.00 | 0.00 |
March | 14.00 | 07-MAR-05:00 | 11.74 | 10.00 | 0.50 | 2.64 | 0.00 | 0.00 |
April | 17.00 | 01-APR-05:00 | 15.74 | 15.00 | 0.50 | 3.69 | 0.00 | 0.00 |
May | 20.40 | 01-MAY-05:00 | 20.40 | 20.40 | 2.10 | 9.33 | 28.50 | 50.50 |
June | 21.00 | 22-JUN-07:00 | 19.59 | 19.00 | 1.50 | 8.35 | 206.50 | 266.00 |
July | 28.00 | 03-JUL-05:00 | 16.06 | 8.00 | 1.00 | 12.41 | 32.50 | 30.50 |
August | 28.80 | 31-AUG-03:00 | 25.95 | 25.00 | 1.50 | 17.03 | 0.00 | 0.00 |
September | 23.00 | 25-SEP-04:00 | 22.27 | 22.00 | 2.10 | 10.88 | 0.00 | 0.00 |
October | 20.60 | 29-OCT-06:00 | 17.24 | 15.40 | 0.50 | 7.15 | 49.50 | 123.00 |
November | 16.90 | 22-NOV-06:00 | 14.44 | 12.90 | 3.10 | 3.06 | 31.00 | 106.50 |
December | 13.00 | 18-DEC-04:00 | 10.82 | 9.00 | 1.80 | -1.4 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 12.00 | 10.82 | 8.00 | 0.50 | -1.9 | 0.00 | 0.00 | |
Maximum of Months | 28.80 | 25.95 | 25.00 | 3.10 | 17.03 | 206.50 | 266.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 20.89 | 30-JAN-13:00 | 23.00 | 20.00 | 3.60 | 18.82 | 266.50 | 27.50 |
February | 23.21 | 07-FEB-15:00 | 28.00 | 21.30 | 6.20 | 18.64 | 178.50 | 219.50 |
March | 23.05 | 28-MAR-10:00 | 28.00 | 21.00 | 7.20 | 23.82 | 374.50 | 58.00 |
April | 26.40 | 30-APR-14:00 | 31.00 | 25.00 | 8.70 | 22.98 | 350.50 | 184.00 |
May | 29.11 | 29-MAY-12:00 | 33.40 | 27.90 | 7.70 | 22.13 | 421.00 | 303.50 |
June | 29.09 | 04-JUN-18:00 | 33.20 | 28.00 | 4.10 | 21.96 | 16.50 | 15.50 |
July | 30.86 | 18-JUL-20:00 | 34.00 | 30.00 | 3.60 | 26.32 | 0.00 | 0.00 |
August | 31.14 | 22-AUG-16:00 | 36.00 | 30.00 | 9.30 | 25.16 | 159.00 | 168.50 |
September | 30.39 | 09-SEP-13:00 | 36.00 | 29.00 | 5.70 | 28.11 | 339.50 | 377.00 |
October | 30.18 | 07-OCT-09:00 | 30.60 | 30.10 | 4.60 | 19.87 | 295.50 | 353.00 |
November | 26.24 | 01-NOV-13:00 | 33.00 | 24.00 | 6.20 | 20.92 | 269.00 | 349.50 |
December | 23.18 | 05-DEC-14:00 | 26.00 | 22.00 | 4.60 | 16.85 | 185.00 | 295.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 20.89 | 23.00 | 20.00 | 3.60 | 16.85 | 0.00 | 0.00 | |
Maximum of Months | 31.14 | 36.00 | 30.10 | 9.30 | 28.11 | 421.00 | 377.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 20.00 | 30-JAN-13:00 | 23.00 | 20.89 | 3.60 | 18.82 | 266.50 | 27.50 |
February | 21.30 | 07-FEB-15:00 | 28.00 | 23.21 | 6.20 | 18.64 | 178.50 | 219.50 |
March | 22.00 | 31-MAR-09:00 | 23.00 | 22.27 | 0.50 | 10.88 | 323.50 | 305.50 |
April | 25.00 | 30-APR-14:00 | 31.00 | 26.40 | 8.70 | 22.98 | 350.50 | 184.00 |
May | 27.90 | 29-MAY-12:00 | 33.40 | 29.11 | 7.70 | 22.13 | 421.00 | 303.50 |
June | 28.00 | 04-JUN-18:00 | 33.20 | 29.09 | 4.10 | 21.96 | 16.50 | 15.50 |
July | 30.00 | 19-JUL-23:19 | 34.00 | 30.86 | 0.83 | 25.33 | 0.00 | 0.00 |
August | 30.00 | 07-AUG-23:19 | 33.00 | 30.56 | 3.43 | 22.30 | 0.00 | 0.00 |
September | 29.00 | 08-SEP-07:00 | 31.00 | 29.41 | 1.50 | 24.33 | 179.00 | 151.00 |
October | 30.10 | 07-OCT-09:00 | 30.60 | 30.18 | 4.60 | 19.87 | 295.50 | 353.00 |
November | 24.00 | 01-NOV-10:00 | 32.00 | 26.10 | 3.10 | 20.05 | 300.50 | 377.00 |
December | 23.00 | 25-DEC-10:00 | 23.00 | 23.00 | 0.80 | 14.10 | 245.00 | 376.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 20.00 | 23.00 | 20.89 | 0.50 | 10.88 | 0.00 | 0.00 | |
Maximum of Months | 30.10 | 34.00 | 30.86 | 8.70 | 25.33 | 421.00 | 377.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 24.90 | 26.90 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 25.87 | 32.18 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 28.18 | 38.22 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 31.32 | 44.91 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 34.39 | 50.41 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 36.58 | 52.39 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 37.28 | 50.68 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 36.29 | 48.56 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 33.90 | 43.99 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 30.75 | 37.43 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 27.69 | 30.34 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 25.55 | 25.09 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 31.09 | 40.13 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 24.90 | 25.09 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 37.28 | 52.39 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK1
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.280697E+09 | -167384171.8 | 0.00 | 0.00 | 744.00 | 0.00 | -113312444.0 | 58.99 | 0.00 | 0.00 |
February | 0.249750E+09 | -147685806.5 | 0.00 | 0.00 | 672.00 | 0.00 | -102064585.0 | 58.99 | 0.00 | 0.00 |
March | 0.267205E+09 | -154572246.9 | 0.00 | 0.00 | 744.00 | 0.00 | -112632979.5 | 58.99 | 0.00 | 0.00 |
April | 0.241174E+09 | -132631302.7 | 0.00 | 0.00 | 720.00 | 0.00 | -108542770.4 | 58.99 | 0.00 | 0.00 |
May | 0.233350E+09 | -122096396.0 | 0.00 | 0.00 | 744.00 | 0.00 | -111253934.7 | 58.99 | 0.00 | 0.00 |
June | 0.215948E+09 | -108685855.5 | 0.00 | 0.00 | 720.00 | 0.00 | -107262104.4 | 58.99 | 0.00 | 0.00 |
July | 0.216840E+09 | -106564799.4 | 0.00 | 0.00 | 744.00 | 0.00 | -110275423.2 | 58.99 | 0.00 | 0.00 |
August | 0.223873E+09 | -113792601.9 | 0.00 | 0.00 | 744.00 | 0.00 | -110080803.3 | 58.99 | 0.00 | 0.00 |
September | 0.227474E+09 | -120424138.8 | 0.00 | 0.00 | 720.00 | 0.00 | -107049493.4 | 58.99 | 0.00 | 0.00 |
October | 0.249797E+09 | -138694364.9 | 0.00 | 0.00 | 744.00 | 0.00 | -111103060.5 | 58.99 | 0.00 | 0.00 |
November | 0.256494E+09 | -148301928.6 | 0.00 | 0.00 | 720.00 | 0.00 | -108192207.0 | 58.99 | 0.00 | 0.00 |
December | 0.277075E+09 | -164403236.2 | 0.00 | 0.00 | 744.00 | 0.00 | -112671749.0 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.293968E+10 | -0.162524E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.131444E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.215948E+09 | -167384171.8 | 0.00 | 0.00 | 672.00 | 0.00 | -113312444.0 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.280697E+09 | -106564799.4 | 0.00 | 0.00 | 744.00 | 0.00 | -102064585.0 | 58.99 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK2
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.280285E+09 | -167381408.6 | 0.00 | 0.00 | 744.00 | 0.00 | -112903921.2 | 58.99 | 0.00 | 0.00 |
February | 0.249426E+09 | -147678888.7 | 0.00 | 0.00 | 672.00 | 0.00 | -101746991.6 | 58.99 | 0.00 | 0.00 |
March | 0.266924E+09 | -154571366.5 | 0.00 | 0.00 | 744.00 | 0.00 | -112352353.0 | 58.99 | 0.00 | 0.00 |
April | 0.241014E+09 | -132638854.3 | 0.00 | 0.00 | 720.00 | 0.00 | -108375228.8 | 58.99 | 0.00 | 0.00 |
May | 0.233344E+09 | -122090917.6 | 0.00 | 0.00 | 744.00 | 0.00 | -111253018.8 | 58.99 | 0.00 | 0.00 |
June | 0.216048E+09 | -108685674.6 | 0.00 | 0.00 | 720.00 | 0.00 | -107362625.7 | 58.99 | 0.00 | 0.00 |
July | 0.217069E+09 | -106571339.2 | 0.00 | 0.00 | 744.00 | 0.00 | -110497377.0 | 58.99 | 0.00 | 0.00 |
August | 0.224147E+09 | -113797720.8 | 0.00 | 0.00 | 744.00 | 0.00 | -110349603.3 | 58.99 | 0.00 | 0.00 |
September | 0.227635E+09 | -120425918.2 | 0.00 | 0.00 | 720.00 | 0.00 | -107209225.7 | 58.99 | 0.00 | 0.00 |
October | 0.249856E+09 | -138702866.6 | 0.00 | 0.00 | 744.00 | 0.00 | -111152726.0 | 58.99 | 0.00 | 0.00 |
November | 0.256446E+09 | -148301978.1 | 0.00 | 0.00 | 720.00 | 0.00 | -108144175.3 | 58.99 | 0.00 | 0.00 |
December | 0.276822E+09 | -164399218.9 | 0.00 | 0.00 | 744.00 | 0.00 | -112422897.6 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.293902E+10 | -0.162525E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.131377E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.216048E+09 | -167381408.6 | 0.00 | 0.00 | 672.00 | 0.00 | -112903921.2 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.280285E+09 | -106571339.2 | 0.00 | 0.00 | 744.00 | 0.00 | -101746991.6 | 58.99 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK3
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.259489E+09 | -147197089.5 | 0.00 | 0.00 | 744.00 | 0.00 | -112292391.9 | 58.99 | 0.00 | 0.00 |
February | 0.230991E+09 | -130025794.4 | 0.00 | 0.00 | 672.00 | 0.00 | -100965284.3 | 58.98 | 0.00 | 0.00 |
March | 0.249181E+09 | -137936673.2 | 0.00 | 0.00 | 744.00 | 0.00 | -111243889.1 | 58.99 | 0.00 | 0.00 |
April | 0.223329E+09 | -116660528.2 | 0.00 | 0.00 | 720.00 | 0.00 | -106668193.2 | 58.99 | 0.00 | 0.00 |
May | 0.217131E+09 | -108328540.0 | 0.00 | 0.00 | 744.00 | 0.00 | -108802442.9 | 58.99 | 0.00 | 0.00 |
June | 0.201637E+09 | -96807137.3 | 0.00 | 0.00 | 720.00 | 0.00 | -104830274.4 | 58.98 | 0.00 | 0.00 |
July | 0.200614E+09 | -93181490.5 | 0.00 | 0.00 | 744.00 | 0.00 | -107433004.2 | 58.99 | 0.00 | 0.00 |
August | 0.209084E+09 | -101667218.7 | 0.00 | 0.00 | 744.00 | 0.00 | -107417094.0 | 58.98 | 0.00 | 0.00 |
September | 0.210430E+09 | -105881424.2 | 0.00 | 0.00 | 720.00 | 0.00 | -104548620.6 | 58.99 | 0.00 | 0.00 |
October | 0.230706E+09 | -122007199.3 | 0.00 | 0.00 | 744.00 | 0.00 | -108698469.0 | 58.99 | 0.00 | 0.00 |
November | 0.237395E+09 | -130926627.8 | 0.00 | 0.00 | 720.00 | 0.00 | -106468048.7 | 58.99 | 0.00 | 0.00 |
December | 0.254914E+09 | -143544974.1 | 0.00 | 0.00 | 744.00 | 0.00 | -111369279.3 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.272490E+10 | -0.143416E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.129074E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.200614E+09 | -147197089.5 | 0.00 | 0.00 | 672.00 | 0.00 | -112292391.9 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.259489E+09 | -93181490.5 | 0.00 | 0.00 | 744.00 | 0.00 | -100965284.3 | 58.99 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK4
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.259596E+09 | -147195360.5 | 0.00 | 0.00 | 744.00 | 0.00 | -112400504.7 | 58.99 | 0.00 | 0.00 |
February | 0.231053E+09 | -129987227.2 | 0.00 | 0.00 | 672.00 | 0.00 | -101065538.8 | 58.99 | 0.00 | 0.00 |
March | 0.249189E+09 | -137940378.9 | 0.00 | 0.00 | 744.00 | 0.00 | -111248132.4 | 58.99 | 0.00 | 0.00 |
April | 0.223285E+09 | -116659262.7 | 0.00 | 0.00 | 720.00 | 0.00 | -106626078.6 | 58.99 | 0.00 | 0.00 |
May | 0.216967E+09 | -108299824.8 | 0.00 | 0.00 | 744.00 | 0.00 | -108667316.4 | 58.99 | 0.00 | 0.00 |
June | 0.201458E+09 | -96804412.9 | 0.00 | 0.00 | 720.00 | 0.00 | -104653183.3 | 58.98 | 0.00 | 0.00 |
July | 0.200398E+09 | -93202979.5 | 0.00 | 0.00 | 744.00 | 0.00 | -107194782.7 | 58.98 | 0.00 | 0.00 |
August | 0.208845E+09 | -101609793.0 | 0.00 | 0.00 | 744.00 | 0.00 | -107235699.4 | 59.00 | 0.00 | 0.00 |
September | 0.210226E+09 | -105847439.5 | 0.00 | 0.00 | 720.00 | 0.00 | -104378772.0 | 59.00 | 0.00 | 0.00 |
October | 0.230543E+09 | -122003330.6 | 0.00 | 0.00 | 744.00 | 0.00 | -108539361.8 | 58.99 | 0.00 | 0.00 |
November | 0.237341E+09 | -130906587.7 | 0.00 | 0.00 | 720.00 | 0.00 | -106434278.9 | 59.00 | 0.00 | 0.00 |
December | 0.254948E+09 | -143522927.2 | 0.00 | 0.00 | 744.00 | 0.00 | -111425445.9 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.272385E+10 | -0.143398E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.128987E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.200398E+09 | -147195360.5 | 0.00 | 0.00 | 672.00 | 0.00 | -112400504.7 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.259596E+09 | -93202979.5 | 0.00 | 0.00 | 744.00 | 0.00 | -101065538.8 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK5
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.252313E+09 | -139109491.9 | 0.00 | 0.00 | 744.00 | 0.00 | -113203142.2 | 58.99 | 0.00 | 0.00 |
February | 0.224657E+09 | -122937535.6 | 0.00 | 0.00 | 672.00 | 0.00 | -101719934.2 | 58.99 | 0.00 | 0.00 |
March | 0.242543E+09 | -130509194.7 | 0.00 | 0.00 | 744.00 | 0.00 | -112033722.9 | 58.99 | 0.00 | 0.00 |
April | 0.217727E+09 | -110415187.3 | 0.00 | 0.00 | 720.00 | 0.00 | -107312011.4 | 58.98 | 0.00 | 0.00 |
May | 0.211791E+09 | -102430656.5 | 0.00 | 0.00 | 744.00 | 0.00 | -109360028.4 | 58.99 | 0.00 | 0.00 |
June | 0.196918E+09 | -91577784.4 | 0.00 | 0.00 | 720.00 | 0.00 | -105340535.2 | 58.99 | 0.00 | 0.00 |
July | 0.195839E+09 | -88118991.6 | 0.00 | 0.00 | 744.00 | 0.00 | -107719991.2 | 58.99 | 0.00 | 0.00 |
August | 0.203995E+09 | -96186880.5 | 0.00 | 0.00 | 744.00 | 0.00 | -107808566.9 | 58.98 | 0.00 | 0.00 |
September | 0.205067E+09 | -100117736.3 | 0.00 | 0.00 | 720.00 | 0.00 | -104949166.1 | 59.01 | 0.00 | 0.00 |
October | 0.224478E+09 | -115332808.6 | 0.00 | 0.00 | 744.00 | 0.00 | -109144906.8 | 58.98 | 0.00 | 0.00 |
November | 0.230700E+09 | -123662715.6 | 0.00 | 0.00 | 720.00 | 0.00 | -107037711.5 | 58.99 | 0.00 | 0.00 |
December | 0.247823E+09 | -135730170.1 | 0.00 | 0.00 | 744.00 | 0.00 | -112093178.5 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.265385E+10 | -0.135613E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.129772E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.195839E+09 | -139109491.9 | 0.00 | 0.00 | 672.00 | 0.00 | -113203142.2 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.252313E+09 | -88118991.6 | 0.00 | 0.00 | 744.00 | 0.00 | -101719934.2 | 59.01 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK6
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.252356E+09 | -139110045.6 | 0.00 | 0.00 | 744.00 | 0.00 | -113246087.0 | 58.99 | 0.00 | 0.00 |
February | 0.224709E+09 | -122936560.9 | 0.00 | 0.00 | 672.00 | 0.00 | -101771947.4 | 58.99 | 0.00 | 0.00 |
March | 0.242612E+09 | -130508837.4 | 0.00 | 0.00 | 744.00 | 0.00 | -112102664.5 | 58.99 | 0.00 | 0.00 |
April | 0.217815E+09 | -110390863.3 | 0.00 | 0.00 | 720.00 | 0.00 | -107424092.2 | 58.99 | 0.00 | 0.00 |
May | 0.211948E+09 | -102439609.5 | 0.00 | 0.00 | 744.00 | 0.00 | -109508069.9 | 58.99 | 0.00 | 0.00 |
June | 0.197081E+09 | -91573546.0 | 0.00 | 0.00 | 720.00 | 0.00 | -105507064.4 | 58.99 | 0.00 | 0.00 |
July | 0.196039E+09 | -88128916.7 | 0.00 | 0.00 | 744.00 | 0.00 | -107909858.8 | 58.99 | 0.00 | 0.00 |
August | 0.204218E+09 | -96180233.0 | 0.00 | 0.00 | 744.00 | 0.00 | -108037417.2 | 58.99 | 0.00 | 0.00 |
September | 0.205242E+09 | -100147945.1 | 0.00 | 0.00 | 720.00 | 0.00 | -105094381.2 | 59.00 | 0.00 | 0.00 |
October | 0.224623E+09 | -115328003.6 | 0.00 | 0.00 | 744.00 | 0.00 | -109295167.9 | 58.99 | 0.00 | 0.00 |
November | 0.230808E+09 | -123652592.0 | 0.00 | 0.00 | 720.00 | 0.00 | -107155116.6 | 58.99 | 0.00 | 0.00 |
December | 0.247884E+09 | -135735996.8 | 0.00 | 0.00 | 744.00 | 0.00 | -112148186.1 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.265533E+10 | -0.135613E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.129920E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.196039E+09 | -139110045.6 | 0.00 | 0.00 | 672.00 | 0.00 | -113246087.0 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.252356E+09 | -88128916.7 | 0.00 | 0.00 | 744.00 | 0.00 | -101771947.4 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK7
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.252421E+09 | -139113749.0 | 0.00 | 0.00 | 744.00 | 0.00 | -113307483.3 | 58.99 | 0.00 | 0.00 |
February | 0.224757E+09 | -122937339.8 | 0.00 | 0.00 | 672.00 | 0.00 | -101819865.9 | 58.99 | 0.00 | 0.00 |
March | 0.242655E+09 | -130514870.6 | 0.00 | 0.00 | 744.00 | 0.00 | -112140345.8 | 58.99 | 0.00 | 0.00 |
April | 0.217848E+09 | -110375572.0 | 0.00 | 0.00 | 720.00 | 0.00 | -107472611.8 | 58.99 | 0.00 | 0.00 |
May | 0.211968E+09 | -102433955.5 | 0.00 | 0.00 | 744.00 | 0.00 | -109533759.8 | 58.99 | 0.00 | 0.00 |
June | 0.197105E+09 | -91583728.8 | 0.00 | 0.00 | 720.00 | 0.00 | -105521435.7 | 58.99 | 0.00 | 0.00 |
July | 0.196050E+09 | -88118310.9 | 0.00 | 0.00 | 744.00 | 0.00 | -107931203.6 | 58.99 | 0.00 | 0.00 |
August | 0.204228E+09 | -96191602.8 | 0.00 | 0.00 | 744.00 | 0.00 | -108036189.8 | 58.98 | 0.00 | 0.00 |
September | 0.205254E+09 | -100128205.0 | 0.00 | 0.00 | 720.00 | 0.00 | -105125465.0 | 59.01 | 0.00 | 0.00 |
October | 0.224645E+09 | -115309777.0 | 0.00 | 0.00 | 744.00 | 0.00 | -109335656.1 | 58.99 | 0.00 | 0.00 |
November | 0.230832E+09 | -123660766.7 | 0.00 | 0.00 | 720.00 | 0.00 | -107171155.3 | 58.99 | 0.00 | 0.00 |
December | 0.247932E+09 | -135715528.1 | 0.00 | 0.00 | 744.00 | 0.00 | -112216928.8 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.265570E+10 | -0.135608E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.129961E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.196050E+09 | -139113749.0 | 0.00 | 0.00 | 672.00 | 0.00 | -113307483.3 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.252421E+09 | -88118310.9 | 0.00 | 0.00 | 744.00 | 0.00 | -101819865.9 | 59.01 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 325.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 308.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 357.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 375.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 405.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 403.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 405.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 395.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 358.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 351.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 318.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 319.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4323.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 308.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 405.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 HEATING COIL
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 HEATING COIL
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3 HEATING COIL
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4 HEATING COIL
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5 HEATING COIL
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6 HEATING COIL
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7 HEATING COIL
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8 HEATING COIL
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9 HEATING COIL
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10 HEATING COIL
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 40555.60 | 67.59 | 02-JAN-08:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 40555.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 40555.60 | 67.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.127288E+11 | 0.968759E+10 | 25934.59 | 30-JAN-08:63 | 16640.52 | 0.00 |
February | 0.00 | 0.00 | 0.150103E+11 | 0.112234E+11 | 54944.77 | 09-FEB-08:62 | 33037.94 | 0.00 |
March | 0.00 | 0.00 | 0.212470E+11 | 0.166189E+11 | 72925.44 | 02-MAR-08:62 | 62949.18 | 0.00 |
April | 0.00 | 0.00 | 0.303205E+11 | 0.229567E+11 | 78893.11 | 30-APR-07:02 | 44174.74 | 0.00 |
May | 0.00 | 0.00 | 0.453074E+11 | 0.340652E+11 | 81124.24 | 30-MAY-07:01 | 42272.59 | 0.00 |
June | 0.00 | 0.00 | 0.552188E+11 | 0.366644E+11 | 82723.02 | 19-JUN-07:01 | 38740.01 | 0.00 |
July | 0.00 | 0.00 | 0.663490E+11 | 0.425285E+11 | 82629.37 | 26-JUL-07:01 | 39613.75 | 0.00 |
August | 0.00 | 0.00 | 0.701817E+11 | 0.439110E+11 | 82629.37 | 08-AUG-07:04 | 32084.22 | 0.00 |
September | 0.00 | 0.00 | 0.596102E+11 | 0.372679E+11 | 82514.83 | 11-SEP-07:01 | 40737.39 | 0.00 |
October | 0.00 | 0.00 | 0.467071E+11 | 0.323674E+11 | 82395.69 | 08-OCT-07:01 | 39590.13 | 0.00 |
November | 0.00 | 0.00 | 0.321231E+11 | 0.230333E+11 | 78890.41 | 03-NOV-07:02 | 47146.23 | 0.00 |
December | 0.00 | 0.00 | 0.193056E+11 | 0.138208E+11 | 76792.45 | 12-DEC-08:62 | 52046.54 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.474109E+12 | 0.324145E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.127288E+11 | 0.968759E+10 | 25934.59 | 16640.52 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.701817E+11 | 0.439110E+11 | 82723.02 | 62949.18 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.744723E+10 | 0.579198E+10 | 14192.97 | 29-JAN-08:63 | 10909.86 | 0.00 |
February | 0.00 | 0.00 | 0.834118E+10 | 0.637448E+10 | 27575.73 | 09-FEB-08:62 | 19253.27 | 0.00 |
March | 0.00 | 0.00 | 0.111793E+11 | 0.889352E+10 | 36434.11 | 02-MAR-08:62 | 32327.90 | 0.00 |
April | 0.00 | 0.00 | 0.150205E+11 | 0.116385E+11 | 37929.36 | 30-APR-07:02 | 26913.43 | 0.00 |
May | 0.00 | 0.00 | 0.215810E+11 | 0.165688E+11 | 39018.96 | 30-MAY-07:01 | 26106.20 | 0.00 |
June | 0.00 | 0.00 | 0.259437E+11 | 0.176916E+11 | 39956.61 | 19-JUN-07:01 | 23795.22 | 0.00 |
July | 0.00 | 0.00 | 0.310794E+11 | 0.203180E+11 | 40243.33 | 18-JUL-07:01 | 23455.08 | 0.00 |
August | 0.00 | 0.00 | 0.328684E+11 | 0.209146E+11 | 41133.42 | 08-AUG-07:01 | 21494.68 | 0.00 |
September | 0.00 | 0.00 | 0.278752E+11 | 0.178967E+11 | 39802.01 | 10-SEP-07:01 | 24617.38 | 0.00 |
October | 0.00 | 0.00 | 0.221677E+11 | 0.157505E+11 | 39851.94 | 08-OCT-07:01 | 24269.33 | 0.00 |
November | 0.00 | 0.00 | 0.158614E+11 | 0.115894E+11 | 38430.19 | 02-NOV-07:02 | 27482.97 | 0.00 |
December | 0.00 | 0.00 | 0.104062E+11 | 0.765463E+10 | 36792.13 | 12-DEC-08:62 | 28565.27 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.229771E+12 | 0.161083E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.744723E+10 | 0.579198E+10 | 14192.97 | 10909.86 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.328684E+11 | 0.209146E+11 | 41133.42 | 32327.90 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3 COOLING COIL
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.499072E+10 | 0.384994E+10 | 17748.53 | 30-JAN-07:03 | 10687.55 | 0.00 |
February | 0.00 | 0.00 | 0.599433E+10 | 0.456487E+10 | 34836.86 | 09-FEB-07:03 | 20807.62 | 0.00 |
March | 0.00 | 0.00 | 0.851489E+10 | 0.679114E+10 | 37106.66 | 02-MAR-07:02 | 30498.20 | 0.00 |
April | 0.00 | 0.00 | 0.117665E+11 | 0.915175E+10 | 39837.97 | 30-APR-07:02 | 22612.56 | 0.00 |
May | 0.00 | 0.00 | 0.177148E+11 | 0.135764E+11 | 41394.46 | 01-MAY-06:02 | 17716.94 | 0.00 |
June | 0.00 | 0.00 | 0.216359E+11 | 0.146695E+11 | 41956.57 | 25-JUN-07:01 | 18293.23 | 0.00 |
July | 0.00 | 0.00 | 0.260128E+11 | 0.166682E+11 | 41678.87 | 06-JUL-06:01 | 17359.79 | 0.00 |
August | 0.00 | 0.00 | 0.280604E+11 | 0.175033E+11 | 41675.20 | 31-AUG-06:01 | 18945.98 | 0.00 |
September | 0.00 | 0.00 | 0.231143E+11 | 0.146669E+11 | 41993.81 | 25-SEP-06:01 | 16723.01 | 0.00 |
October | 0.00 | 0.00 | 0.181810E+11 | 0.127199E+11 | 41922.58 | 01-OCT-07:01 | 17135.62 | 0.00 |
November | 0.00 | 0.00 | 0.127672E+11 | 0.914922E+10 | 40478.88 | 03-NOV-06:02 | 21861.95 | 0.00 |
December | 0.00 | 0.00 | 0.757859E+10 | 0.550450E+10 | 38496.96 | 12-DEC-07:02 | 26785.45 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.186331E+12 | 0.128816E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.499072E+10 | 0.384994E+10 | 17748.53 | 10687.55 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.280604E+11 | 0.175033E+11 | 41993.81 | 30498.20 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4 COOLING COIL
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.491079E+10 | 0.378448E+10 | 17275.03 | 30-JAN-07:03 | 10391.73 | 0.00 |
February | 0.00 | 0.00 | 0.594459E+10 | 0.452569E+10 | 34875.78 | 09-FEB-07:03 | 20827.14 | 0.00 |
March | 0.00 | 0.00 | 0.849090E+10 | 0.677106E+10 | 37187.44 | 02-MAR-07:02 | 30552.24 | 0.00 |
April | 0.00 | 0.00 | 0.117889E+11 | 0.917091E+10 | 39935.29 | 30-APR-07:02 | 22733.49 | 0.00 |
May | 0.00 | 0.00 | 0.178164E+11 | 0.136611E+11 | 41498.90 | 01-MAY-06:02 | 17860.31 | 0.00 |
June | 0.00 | 0.00 | 0.217600E+11 | 0.147680E+11 | 42047.31 | 25-JUN-07:01 | 18444.74 | 0.00 |
July | 0.00 | 0.00 | 0.261804E+11 | 0.168017E+11 | 41769.01 | 06-JUL-06:02 | 17332.39 | 0.00 |
August | 0.00 | 0.00 | 0.282278E+11 | 0.176359E+11 | 41765.33 | 31-AUG-06:01 | 19082.27 | 0.00 |
September | 0.00 | 0.00 | 0.232525E+11 | 0.147750E+11 | 42084.63 | 25-SEP-06:01 | 16909.45 | 0.00 |
October | 0.00 | 0.00 | 0.182897E+11 | 0.128063E+11 | 42013.25 | 01-OCT-07:02 | 17111.44 | 0.00 |
November | 0.00 | 0.00 | 0.127998E+11 | 0.917590E+10 | 40576.98 | 03-NOV-06:02 | 21975.78 | 0.00 |
December | 0.00 | 0.00 | 0.754376E+10 | 0.547747E+10 | 38581.85 | 12-DEC-07:02 | 26845.94 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.187006E+12 | 0.129354E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.491079E+10 | 0.378448E+10 | 17275.03 | 10391.73 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.282278E+11 | 0.176359E+11 | 42084.63 | 30552.24 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5 COOLING COIL
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.464581E+10 | 0.356943E+10 | 15154.86 | 30-JAN-07:03 | 9069.60 | 0.00 |
February | 0.00 | 0.00 | 0.570493E+10 | 0.433633E+10 | 32180.40 | 09-FEB-07:03 | 19032.37 | 0.00 |
March | 0.00 | 0.00 | 0.823361E+10 | 0.655936E+10 | 36949.17 | 02-MAR-07:02 | 30229.67 | 0.00 |
April | 0.00 | 0.00 | 0.115574E+11 | 0.898125E+10 | 39694.80 | 30-APR-07:02 | 22479.45 | 0.00 |
May | 0.00 | 0.00 | 0.176222E+11 | 0.134961E+11 | 41252.32 | 01-MAY-06:02 | 17654.96 | 0.00 |
June | 0.00 | 0.00 | 0.215613E+11 | 0.146098E+11 | 41809.57 | 25-JUN-07:01 | 18198.79 | 0.00 |
July | 0.00 | 0.00 | 0.260082E+11 | 0.166663E+11 | 41532.84 | 06-JUL-06:01 | 17290.61 | 0.00 |
August | 0.00 | 0.00 | 0.280460E+11 | 0.174941E+11 | 41529.18 | 31-AUG-06:01 | 18794.78 | 0.00 |
September | 0.00 | 0.00 | 0.230691E+11 | 0.146329E+11 | 41846.68 | 25-SEP-06:03 | 16624.56 | 0.00 |
October | 0.00 | 0.00 | 0.181012E+11 | 0.126539E+11 | 41775.70 | 01-OCT-07:01 | 17047.22 | 0.00 |
November | 0.00 | 0.00 | 0.125814E+11 | 0.900175E+10 | 40334.77 | 03-NOV-06:02 | 21679.44 | 0.00 |
December | 0.00 | 0.00 | 0.728288E+10 | 0.527479E+10 | 38344.31 | 12-DEC-07:02 | 26550.81 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.184414E+12 | 0.127276E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.464581E+10 | 0.356943E+10 | 15154.86 | 9069.60 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.280460E+11 | 0.174941E+11 | 41846.68 | 30229.67 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6 COOLING COIL
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.772933E+10 | 0.580407E+10 | 24272.51 | 30-JAN-08:63 | 14243.36 | 0.00 |
February | 0.00 | 0.00 | 0.979585E+10 | 0.730795E+10 | 50941.05 | 09-FEB-08:62 | 30259.97 | 0.00 |
March | 0.00 | 0.00 | 0.145777E+11 | 0.114268E+11 | 65726.87 | 02-MAR-08:62 | 53267.00 | 0.00 |
April | 0.00 | 0.00 | 0.208424E+11 | 0.159979E+11 | 70776.83 | 30-APR-08:62 | 39163.43 | 0.00 |
May | 0.00 | 0.00 | 0.322595E+11 | 0.244871E+11 | 73298.83 | 01-MAY-07:02 | 30942.99 | 0.00 |
June | 0.00 | 0.00 | 0.395592E+11 | 0.265772E+11 | 74183.37 | 25-JUN-08:61 | 30907.79 | 0.00 |
July | 0.00 | 0.00 | 0.475888E+11 | 0.303104E+11 | 73562.72 | 18-JUL-07:01 | 36204.69 | 0.00 |
August | 0.00 | 0.00 | 0.516378E+11 | 0.319616E+11 | 73619.52 | 08-AUG-07:03 | 33261.55 | 0.00 |
September | 0.00 | 0.00 | 0.423158E+11 | 0.265519E+11 | 74335.79 | 25-SEP-07:01 | 29859.54 | 0.00 |
October | 0.00 | 0.00 | 0.328527E+11 | 0.228265E+11 | 74115.13 | 02-OCT-07:01 | 30597.64 | 0.00 |
November | 0.00 | 0.00 | 0.226728E+11 | 0.159826E+11 | 70550.83 | 03-NOV-07:02 | 40918.58 | 0.00 |
December | 0.00 | 0.00 | 0.126289E+11 | 0.895853E+10 | 67750.65 | 12-DEC-08:62 | 47776.15 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.334461E+12 | 0.228193E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.772933E+10 | 0.580407E+10 | 24272.51 | 14243.36 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.516378E+11 | 0.319616E+11 | 74335.79 | 53267.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7 COOLING COIL
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.398297E+10 | 0.299477E+10 | 11865.42 | 30-JAN-08:63 | 6965.84 | 0.00 |
February | 0.00 | 0.00 | 0.506478E+10 | 0.378437E+10 | 24499.33 | 09-FEB-08:62 | 14523.02 | 0.00 |
March | 0.00 | 0.00 | 0.755722E+10 | 0.593128E+10 | 34753.64 | 02-MAR-08:62 | 28151.30 | 0.00 |
April | 0.00 | 0.00 | 0.108435E+11 | 0.832523E+10 | 37459.75 | 30-APR-08:62 | 20660.85 | 0.00 |
May | 0.00 | 0.00 | 0.168082E+11 | 0.127517E+11 | 38817.66 | 01-MAY-07:02 | 16312.73 | 0.00 |
June | 0.00 | 0.00 | 0.205957E+11 | 0.138348E+11 | 39240.16 | 25-JUN-08:02 | 16102.26 | 0.00 |
July | 0.00 | 0.00 | 0.247874E+11 | 0.157865E+11 | 38911.86 | 18-JUL-07:01 | 19193.03 | 0.00 |
August | 0.00 | 0.00 | 0.268699E+11 | 0.166292E+11 | 38941.91 | 08-AUG-07:01 | 18327.11 | 0.00 |
September | 0.00 | 0.00 | 0.220273E+11 | 0.138273E+11 | 39320.78 | 25-SEP-07:01 | 15631.17 | 0.00 |
October | 0.00 | 0.00 | 0.170996E+11 | 0.118916E+11 | 39204.06 | 02-OCT-07:02 | 15903.30 | 0.00 |
November | 0.00 | 0.00 | 0.117883E+11 | 0.831807E+10 | 37292.80 | 03-NOV-07:02 | 21707.34 | 0.00 |
December | 0.00 | 0.00 | 0.654570E+10 | 0.464982E+10 | 33344.49 | 12-DEC-08:62 | 23504.02 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.173971E+12 | 0.118725E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.398297E+10 | 0.299477E+10 | 11865.42 | 6965.84 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.268699E+11 | 0.166292E+11 | 39320.78 | 28151.30 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8 COOLING COIL
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.391573E+10 | 0.294140E+10 | 11342.89 | 30-JAN-08:63 | 6650.48 | 0.00 |
February | 0.00 | 0.00 | 0.500186E+10 | 0.373558E+10 | 23869.73 | 09-FEB-08:62 | 14109.17 | 0.00 |
March | 0.00 | 0.00 | 0.749170E+10 | 0.587816E+10 | 34642.18 | 02-MAR-08:62 | 28033.70 | 0.00 |
April | 0.00 | 0.00 | 0.107891E+11 | 0.828142E+10 | 37341.41 | 30-APR-08:62 | 20574.65 | 0.00 |
May | 0.00 | 0.00 | 0.167635E+11 | 0.127148E+11 | 38694.98 | 01-MAY-07:02 | 16244.48 | 0.00 |
June | 0.00 | 0.00 | 0.205520E+11 | 0.138007E+11 | 39117.73 | 25-JUN-08:02 | 16039.78 | 0.00 |
July | 0.00 | 0.00 | 0.247499E+11 | 0.157577E+11 | 38790.46 | 18-JUL-07:01 | 19117.08 | 0.00 |
August | 0.00 | 0.00 | 0.268319E+11 | 0.166002E+11 | 38820.41 | 08-AUG-07:01 | 18261.17 | 0.00 |
September | 0.00 | 0.00 | 0.219886E+11 | 0.137979E+11 | 39198.10 | 25-SEP-07:01 | 15579.68 | 0.00 |
October | 0.00 | 0.00 | 0.170577E+11 | 0.118583E+11 | 39081.75 | 02-OCT-07:01 | 15947.40 | 0.00 |
November | 0.00 | 0.00 | 0.117377E+11 | 0.827840E+10 | 37178.32 | 03-NOV-07:02 | 21606.81 | 0.00 |
December | 0.00 | 0.00 | 0.648332E+10 | 0.460223E+10 | 32831.92 | 12-DEC-08:62 | 23110.82 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.173363E+12 | 0.118247E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.391573E+10 | 0.294140E+10 | 11342.89 | 6650.48 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.268319E+11 | 0.166002E+11 | 39198.10 | 28033.70 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9 COOLING COIL
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.377883E+10 | 0.283304E+10 | 9670.96 | 30-JAN-08:63 | 5651.51 | 0.00 |
February | 0.00 | 0.00 | 0.488020E+10 | 0.364199E+10 | 21935.37 | 09-FEB-08:62 | 12856.78 | 0.00 |
March | 0.00 | 0.00 | 0.738805E+10 | 0.579471E+10 | 34867.18 | 02-MAR-08:62 | 28164.67 | 0.00 |
April | 0.00 | 0.00 | 0.107644E+11 | 0.826353E+10 | 37586.45 | 30-APR-08:62 | 20695.44 | 0.00 |
May | 0.00 | 0.00 | 0.168690E+11 | 0.128032E+11 | 38953.41 | 01-MAY-07:02 | 16340.45 | 0.00 |
June | 0.00 | 0.00 | 0.207094E+11 | 0.139261E+11 | 39383.04 | 25-JUN-08:02 | 16176.71 | 0.00 |
July | 0.00 | 0.00 | 0.249847E+11 | 0.159439E+11 | 39053.55 | 18-JUL-07:01 | 19363.86 | 0.00 |
August | 0.00 | 0.00 | 0.271141E+11 | 0.168224E+11 | 39083.71 | 08-AUG-07:01 | 18516.80 | 0.00 |
September | 0.00 | 0.00 | 0.221944E+11 | 0.139582E+11 | 39463.96 | 25-SEP-07:01 | 15745.95 | 0.00 |
October | 0.00 | 0.00 | 0.172000E+11 | 0.119720E+11 | 39346.82 | 02-OCT-07:01 | 16125.30 | 0.00 |
November | 0.00 | 0.00 | 0.117717E+11 | 0.830594E+10 | 37422.82 | 03-NOV-07:02 | 21778.15 | 0.00 |
December | 0.00 | 0.00 | 0.638855E+10 | 0.453112E+10 | 31589.41 | 12-DEC-08:62 | 22160.02 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.174043E+12 | 0.118796E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.377883E+10 | 0.283304E+10 | 9670.96 | 5651.51 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.271141E+11 | 0.168224E+11 | 39463.96 | 28164.67 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10 COOLING COIL
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.418304E+10 | 0.319213E+10 | 9893.94 | 29-JAN-16:00 | 6608.86 | 0.00 |
February | 0.00 | 0.00 | 0.534326E+10 | 0.405586E+10 | 17846.40 | 09-FEB-08:62 | 10040.58 | 0.00 |
March | 0.00 | 0.00 | 0.813206E+10 | 0.647481E+10 | 39856.50 | 02-MAR-08:62 | 35005.35 | 0.00 |
April | 0.00 | 0.00 | 0.121040E+11 | 0.944157E+10 | 44177.13 | 30-APR-08:62 | 22636.78 | 0.00 |
May | 0.00 | 0.00 | 0.193248E+11 | 0.149259E+11 | 45642.69 | 30-MAY-07:01 | 21741.01 | 0.00 |
June | 0.00 | 0.00 | 0.236890E+11 | 0.163057E+11 | 45733.94 | 25-JUN-08:02 | 17853.31 | 0.00 |
July | 0.00 | 0.00 | 0.285763E+11 | 0.187406E+11 | 45386.34 | 26-JUL-07:01 | 19803.20 | 0.00 |
August | 0.00 | 0.00 | 0.311951E+11 | 0.199846E+11 | 45386.34 | 08-AUG-07:07 | 16326.43 | 0.00 |
September | 0.00 | 0.00 | 0.254533E+11 | 0.165047E+11 | 45827.91 | 25-SEP-07:01 | 18342.29 | 0.00 |
October | 0.00 | 0.00 | 0.197971E+11 | 0.141012E+11 | 45691.87 | 02-OCT-07:02 | 18248.87 | 0.00 |
November | 0.00 | 0.00 | 0.134158E+11 | 0.967890E+10 | 43989.89 | 03-NOV-07:02 | 24387.53 | 0.00 |
December | 0.00 | 0.00 | 0.706445E+10 | 0.511125E+10 | 32899.93 | 12-DEC-08:62 | 22207.26 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.198278E+12 | 0.138517E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.418304E+10 | 0.319213E+10 | 9893.94 | 6608.86 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.311951E+11 | 0.199846E+11 | 45827.91 | 35005.35 | 0.00 |
Report: FanReportMonthly
For: PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.226068E+10 | 0.36 | 1245.97 | 08-JAN-10:20 | 0.53 |
February | 0.204564E+10 | 0.36 | 2020.00 | 09-FEB-08:62 | 0.70 |
March | 0.227013E+10 | 0.36 | 3114.91 | 02-MAR-08:62 | 0.87 |
April | 0.219037E+10 | 0.36 | 3114.91 | 18-APR-07:02 | 0.87 |
May | 0.228700E+10 | 0.36 | 3114.91 | 01-MAY-07:02 | 0.86 |
June | 0.234966E+10 | 0.37 | 3114.91 | 01-JUN-07:01 | 0.87 |
July | 0.264271E+10 | 0.39 | 3114.91 | 01-JUL-07:01 | 0.86 |
August | 0.274234E+10 | 0.40 | 3114.91 | 01-AUG-07:01 | 0.86 |
September | 0.242601E+10 | 0.38 | 3114.91 | 01-SEP-07:01 | 0.86 |
October | 0.229630E+10 | 0.36 | 3114.91 | 01-OCT-07:01 | 0.86 |
November | 0.219008E+10 | 0.36 | 3114.91 | 01-NOV-07:02 | 0.87 |
December | 0.227008E+10 | 0.36 | 3114.91 | 12-DEC-08:62 | 0.87 |
Annual Sum or Average | 0.279710E+11 | 0.37 | |||
Minimum of Months | 0.204564E+10 | 0.36 | 1245.97 | 0.53 | |
Maximum of Months | 0.274234E+10 | 0.40 | 3114.91 | 0.87 |
Report: FanReportMonthly
For: PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.924935E+09 | 0.38 | 627.23 | 03-JAN-11:40 | 0.53 |
February | 0.843006E+09 | 0.38 | 1045.52 | 09-FEB-08:62 | 0.71 |
March | 0.949635E+09 | 0.38 | 1568.08 | 02-MAR-08:62 | 0.87 |
April | 0.931025E+09 | 0.38 | 1568.08 | 18-APR-07:02 | 0.87 |
May | 0.100991E+10 | 0.37 | 1568.08 | 06-MAY-07:02 | 0.87 |
June | 0.107011E+10 | 0.38 | 1568.08 | 01-JUN-07:01 | 0.87 |
July | 0.122566E+10 | 0.40 | 1568.08 | 01-JUL-07:01 | 0.87 |
August | 0.127888E+10 | 0.40 | 1568.08 | 01-AUG-07:01 | 0.86 |
September | 0.110941E+10 | 0.39 | 1568.08 | 01-SEP-07:01 | 0.87 |
October | 0.101348E+10 | 0.37 | 1568.08 | 01-OCT-07:01 | 0.86 |
November | 0.934771E+09 | 0.37 | 1568.08 | 01-NOV-07:02 | 0.87 |
December | 0.936362E+09 | 0.38 | 1525.41 | 12-DEC-08:62 | 0.86 |
Annual Sum or Average | 0.122272E+11 | 0.38 | |||
Minimum of Months | 0.843006E+09 | 0.37 | 627.23 | 0.53 | |
Maximum of Months | 0.127888E+10 | 0.40 | 1568.08 | 0.87 |
Report: FanReportMonthly
For: PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.907383E+09 | 0.29 | 626.99 | 18-JAN-12:30 | 0.53 |
February | 0.821949E+09 | 0.29 | 1349.13 | 09-FEB-07:03 | 0.81 |
March | 0.926033E+09 | 0.29 | 1567.48 | 02-MAR-07:02 | 0.87 |
April | 0.882250E+09 | 0.29 | 1567.48 | 03-APR-06:02 | 0.87 |
May | 0.931349E+09 | 0.29 | 1567.48 | 01-MAY-06:02 | 0.86 |
June | 0.972921E+09 | 0.30 | 1567.48 | 01-JUN-06:01 | 0.87 |
July | 0.109279E+10 | 0.31 | 1567.48 | 01-JUL-06:01 | 0.86 |
August | 0.115837E+10 | 0.33 | 1567.48 | 01-AUG-06:01 | 0.86 |
September | 0.995524E+09 | 0.30 | 1567.48 | 01-SEP-06:01 | 0.86 |
October | 0.926228E+09 | 0.29 | 1567.48 | 01-OCT-07:01 | 0.86 |
November | 0.883647E+09 | 0.29 | 1567.48 | 01-NOV-06:02 | 0.87 |
December | 0.903277E+09 | 0.28 | 1567.48 | 12-DEC-07:02 | 0.87 |
Annual Sum or Average | 0.114017E+11 | 0.30 | |||
Minimum of Months | 0.821949E+09 | 0.28 | 626.99 | 0.53 | |
Maximum of Months | 0.115837E+10 | 0.33 | 1567.48 | 0.87 |
Report: FanReportMonthly
For: PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.909346E+09 | 0.29 | 628.35 | 07-JAN-10:00 | 0.53 |
February | 0.823729E+09 | 0.29 | 1350.28 | 09-FEB-07:03 | 0.81 |
March | 0.928041E+09 | 0.29 | 1570.87 | 02-MAR-07:02 | 0.87 |
April | 0.884199E+09 | 0.29 | 1570.87 | 03-APR-06:02 | 0.87 |
May | 0.933932E+09 | 0.29 | 1570.87 | 01-MAY-06:02 | 0.86 |
June | 0.976264E+09 | 0.30 | 1570.87 | 01-JUN-06:01 | 0.87 |
July | 0.109763E+10 | 0.31 | 1570.87 | 01-JUL-06:01 | 0.86 |
August | 0.116315E+10 | 0.33 | 1570.87 | 01-AUG-06:01 | 0.86 |
September | 0.999376E+09 | 0.31 | 1570.87 | 01-SEP-06:01 | 0.86 |
October | 0.928685E+09 | 0.29 | 1570.87 | 01-OCT-07:01 | 0.86 |
November | 0.885575E+09 | 0.29 | 1570.87 | 01-NOV-06:02 | 0.87 |
December | 0.905230E+09 | 0.28 | 1570.87 | 12-DEC-07:02 | 0.87 |
Annual Sum or Average | 0.114352E+11 | 0.30 | |||
Minimum of Months | 0.823729E+09 | 0.28 | 628.35 | 0.53 | |
Maximum of Months | 0.116315E+10 | 0.33 | 1570.87 | 0.87 |
Report: FanReportMonthly
For: PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.904204E+09 | 0.29 | 624.80 | 20-JAN-16:10 | 0.53 |
February | 0.819003E+09 | 0.29 | 1224.76 | 09-FEB-07:03 | 0.77 |
March | 0.922681E+09 | 0.29 | 1561.99 | 02-MAR-07:02 | 0.87 |
April | 0.878927E+09 | 0.29 | 1561.99 | 03-APR-06:02 | 0.87 |
May | 0.928350E+09 | 0.29 | 1561.99 | 01-MAY-06:02 | 0.86 |
June | 0.969490E+09 | 0.30 | 1561.99 | 01-JUN-06:01 | 0.87 |
July | 0.109068E+10 | 0.31 | 1561.99 | 01-JUL-06:01 | 0.86 |
August | 0.115592E+10 | 0.33 | 1561.99 | 01-AUG-06:01 | 0.86 |
September | 0.992555E+09 | 0.31 | 1561.99 | 01-SEP-06:01 | 0.86 |
October | 0.922868E+09 | 0.29 | 1561.99 | 01-OCT-07:01 | 0.86 |
November | 0.880346E+09 | 0.29 | 1561.99 | 01-NOV-06:02 | 0.87 |
December | 0.900043E+09 | 0.28 | 1561.99 | 12-DEC-07:02 | 0.87 |
Annual Sum or Average | 0.113651E+11 | 0.30 | |||
Minimum of Months | 0.819003E+09 | 0.28 | 624.80 | 0.53 | |
Maximum of Months | 0.115592E+10 | 0.33 | 1561.99 | 0.87 |
Report: FanReportMonthly
For: PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.148266E+10 | 0.26 | 1110.11 | 03-JAN-18:40 | 0.53 |
February | 0.134314E+10 | 0.26 | 1892.95 | 09-FEB-08:62 | 0.72 |
March | 0.151519E+10 | 0.27 | 2775.27 | 02-MAR-08:62 | 0.87 |
April | 0.144080E+10 | 0.26 | 2775.27 | 18-APR-07:02 | 0.87 |
May | 0.154011E+10 | 0.27 | 2775.27 | 01-MAY-07:02 | 0.86 |
June | 0.165207E+10 | 0.29 | 2775.27 | 01-JUN-07:01 | 0.87 |
July | 0.189175E+10 | 0.30 | 2775.27 | 01-JUL-07:01 | 0.86 |
August | 0.201321E+10 | 0.31 | 2775.27 | 01-AUG-07:01 | 0.86 |
September | 0.170775E+10 | 0.29 | 2775.27 | 01-SEP-07:01 | 0.86 |
October | 0.153099E+10 | 0.27 | 2775.27 | 01-OCT-08:61 | 0.85 |
November | 0.144558E+10 | 0.26 | 2775.27 | 01-NOV-07:02 | 0.87 |
December | 0.147515E+10 | 0.26 | 2775.27 | 12-DEC-08:62 | 0.87 |
Annual Sum or Average | 0.190384E+11 | 0.28 | |||
Minimum of Months | 0.134314E+10 | 0.26 | 1110.11 | 0.53 | |
Maximum of Months | 0.201321E+10 | 0.31 | 2775.27 | 0.87 |
Report: FanReportMonthly
For: PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.811469E+09 | 0.27 | 607.57 | 01-JAN-14:30 | 0.55 |
February | 0.735051E+09 | 0.27 | 915.42 | 09-FEB-08:62 | 0.70 |
March | 0.829209E+09 | 0.28 | 1518.92 | 02-MAR-08:62 | 0.90 |
April | 0.788341E+09 | 0.27 | 1518.92 | 18-APR-07:02 | 0.90 |
May | 0.841656E+09 | 0.28 | 1518.92 | 01-MAY-07:02 | 0.89 |
June | 0.900614E+09 | 0.30 | 1518.92 | 01-JUN-07:01 | 0.90 |
July | 0.102957E+10 | 0.31 | 1518.92 | 01-JUL-07:01 | 0.89 |
August | 0.109388E+10 | 0.32 | 1518.92 | 01-AUG-07:01 | 0.89 |
September | 0.929523E+09 | 0.30 | 1518.92 | 01-SEP-07:01 | 0.89 |
October | 0.836269E+09 | 0.28 | 1518.92 | 01-OCT-08:61 | 0.88 |
November | 0.790875E+09 | 0.27 | 1518.92 | 01-NOV-07:02 | 0.90 |
December | 0.807284E+09 | 0.27 | 1393.18 | 12-DEC-08:62 | 0.86 |
Annual Sum or Average | 0.103937E+11 | 0.28 | |||
Minimum of Months | 0.735051E+09 | 0.27 | 607.57 | 0.55 | |
Maximum of Months | 0.109388E+10 | 0.32 | 1518.92 | 0.90 |
Report: FanReportMonthly
For: PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.808937E+09 | 0.27 | 605.67 | 26-JAN-14:20 | 0.55 |
February | 0.732742E+09 | 0.27 | 885.25 | 09-FEB-08:62 | 0.68 |
March | 0.826610E+09 | 0.28 | 1514.18 | 02-MAR-08:62 | 0.90 |
April | 0.785852E+09 | 0.27 | 1514.18 | 18-APR-07:02 | 0.90 |
May | 0.839234E+09 | 0.28 | 1514.18 | 01-MAY-07:02 | 0.89 |
June | 0.898480E+09 | 0.30 | 1514.18 | 01-JUN-07:01 | 0.90 |
July | 0.102769E+10 | 0.31 | 1514.18 | 01-JUL-07:01 | 0.89 |
August | 0.109195E+10 | 0.32 | 1514.18 | 01-AUG-07:01 | 0.89 |
September | 0.927600E+09 | 0.30 | 1514.18 | 01-SEP-07:01 | 0.89 |
October | 0.833862E+09 | 0.28 | 1514.18 | 01-OCT-08:61 | 0.88 |
November | 0.788399E+09 | 0.27 | 1514.18 | 01-NOV-07:02 | 0.90 |
December | 0.804752E+09 | 0.27 | 1368.29 | 12-DEC-08:62 | 0.86 |
Annual Sum or Average | 0.103661E+11 | 0.29 | |||
Minimum of Months | 0.732742E+09 | 0.27 | 605.67 | 0.55 | |
Maximum of Months | 0.109195E+10 | 0.32 | 1514.18 | 0.90 |
Report: FanReportMonthly
For: PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.814424E+09 | 0.27 | 609.78 | 10-JAN-18:10 | 0.54 |
February | 0.737651E+09 | 0.27 | 787.93 | 09-FEB-08:62 | 0.64 |
March | 0.832178E+09 | 0.28 | 1524.45 | 02-MAR-08:62 | 0.90 |
April | 0.791060E+09 | 0.27 | 1524.45 | 30-APR-08:62 | 0.89 |
May | 0.844952E+09 | 0.28 | 1524.45 | 01-MAY-07:02 | 0.89 |
June | 0.905061E+09 | 0.30 | 1524.45 | 01-JUN-07:01 | 0.90 |
July | 0.103685E+10 | 0.31 | 1524.45 | 01-JUL-07:01 | 0.89 |
August | 0.110258E+10 | 0.32 | 1524.45 | 01-AUG-07:01 | 0.89 |
September | 0.935493E+09 | 0.30 | 1524.45 | 01-SEP-07:01 | 0.89 |
October | 0.839742E+09 | 0.28 | 1524.45 | 01-OCT-08:61 | 0.88 |
November | 0.793647E+09 | 0.27 | 1524.45 | 01-NOV-07:02 | 0.90 |
December | 0.810171E+09 | 0.27 | 1303.95 | 12-DEC-08:62 | 0.84 |
Annual Sum or Average | 0.104438E+11 | 0.29 | |||
Minimum of Months | 0.737651E+09 | 0.27 | 609.78 | 0.54 | |
Maximum of Months | 0.110258E+10 | 0.32 | 1524.45 | 0.90 |
Report: FanReportMonthly
For: PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.941542E+09 | 0.26 | 706.73 | 02-JAN-08:30 | 0.53 |
February | 0.852717E+09 | 0.26 | 704.96 | 11-FEB-13:20 | 0.53 |
March | 0.961977E+09 | 0.27 | 1762.39 | 02-MAR-08:62 | 0.87 |
April | 0.914190E+09 | 0.26 | 1762.39 | 30-APR-08:62 | 0.86 |
May | 0.972737E+09 | 0.27 | 1762.39 | 01-MAY-07:02 | 0.86 |
June | 0.103355E+10 | 0.28 | 1762.39 | 01-JUN-07:01 | 0.87 |
July | 0.118421E+10 | 0.30 | 1762.39 | 01-JUL-07:01 | 0.86 |
August | 0.126674E+10 | 0.31 | 1762.39 | 01-AUG-07:01 | 0.86 |
September | 0.107048E+10 | 0.29 | 1762.39 | 01-SEP-07:01 | 0.86 |
October | 0.967214E+09 | 0.27 | 1762.39 | 01-OCT-08:61 | 0.85 |
November | 0.916680E+09 | 0.26 | 1762.39 | 01-NOV-07:02 | 0.86 |
December | 0.936556E+09 | 0.26 | 1301.75 | 12-DEC-08:62 | 0.75 |
Annual Sum or Average | 0.120186E+11 | 0.28 | |||
Minimum of Months | 0.852717E+09 | 0.26 | 704.96 | 0.53 | |
Maximum of Months | 0.126674E+10 | 0.31 | 1762.39 | 0.87 |
Report: ZoneTemperatureOscillationReportMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.604420E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.651968E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.870692E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.114527E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.164034E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.190650E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.228548E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.239819E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.199507E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.160978E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.116401E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.793248E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.170650E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.604420E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.239819E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.289333E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.305662E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.397187E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.505087E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.709162E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.821453E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.984635E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.103294E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.856770E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.694193E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.512113E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.365956E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.747449E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.289333E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.103294E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_3:3
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.223218E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.241912E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.323801E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.411124E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.587610E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.686546E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.818761E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.876403E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.709605E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.571939E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.422957E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.288958E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.616284E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.223218E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.876403E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_4:4
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.221441E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.240897E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.323478E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.411993E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.590526E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.690112E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.823659E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.881291E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.713524E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.574824E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.424021E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.288360E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.618413E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.221441E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.881291E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_5:5
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.214242E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.234422E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.316492E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.405655E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.584833E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.684057E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.818018E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.875338E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.707916E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.569494E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.418193E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.281425E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.611009E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.214242E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.875338E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_6:6
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.358365E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.400897E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.554965E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.724532E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.106425E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.125535E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.150303E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.161765E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.130087E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.102949E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.747024E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.484897E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.110413E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.358365E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.161765E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_7:7
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.187721E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.209223E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.288938E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.376366E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.551708E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.649872E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.778033E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.836484E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.673126E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.533392E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.387750E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.252918E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.572553E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.187721E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.836484E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_8:8
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.185738E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.207381E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.286983E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.374670E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.550140E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.648341E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.776624E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.835037E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.671767E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.531950E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.386190E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.251089E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.570591E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.185738E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.835037E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_9:9
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.182830E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.204883E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.285089E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.374890E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.553806E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.653487E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.784240E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.844035E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.678183E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.536327E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.387804E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.249398E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.573497E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.182830E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.844035E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_10:10
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.208754E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.232255E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.323843E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.432396E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.648496E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.764213E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.918627E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.994898E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.795679E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.630100E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.451698E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.284311E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.668527E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.208754E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.994898E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.226068E+10 | 0.127288E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.204564E+10 | 0.150103E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.227013E+10 | 0.212470E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.219037E+10 | 0.303205E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.228700E+10 | 0.453074E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.234966E+10 | 0.552188E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.264271E+10 | 0.663490E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.274234E+10 | 0.701817E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.242601E+10 | 0.596102E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.229630E+10 | 0.467071E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.219008E+10 | 0.321231E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.227008E+10 | 0.193056E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.279710E+11 | 0.474109E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.204564E+10 | 0.127288E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.274234E+10 | 0.701817E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.924935E+09 | 0.744723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.843006E+09 | 0.834118E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.949635E+09 | 0.111793E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.931025E+09 | 0.150205E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.100991E+10 | 0.215810E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.107011E+10 | 0.259437E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.122566E+10 | 0.310794E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.127888E+10 | 0.328684E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.110941E+10 | 0.278752E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.101348E+10 | 0.221677E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.934771E+09 | 0.158614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.936362E+09 | 0.104062E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.122272E+11 | 0.229771E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.843006E+09 | 0.744723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.127888E+10 | 0.328684E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_3:3
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.907383E+09 | 0.499072E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.821949E+09 | 0.599433E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.926033E+09 | 0.851489E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.882250E+09 | 0.117665E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.931349E+09 | 0.177148E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.972921E+09 | 0.216359E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.109279E+10 | 0.260128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.115837E+10 | 0.280604E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.995524E+09 | 0.231143E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.926228E+09 | 0.181810E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.883647E+09 | 0.127672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.903277E+09 | 0.757859E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.114017E+11 | 0.186331E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.821949E+09 | 0.499072E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.115837E+10 | 0.280604E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_4:4
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.909346E+09 | 0.491079E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.823729E+09 | 0.594459E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.928041E+09 | 0.849090E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.884199E+09 | 0.117889E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.933932E+09 | 0.178164E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.976264E+09 | 0.217600E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.109763E+10 | 0.261804E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.116315E+10 | 0.282278E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.999376E+09 | 0.232525E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.928685E+09 | 0.182897E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.885575E+09 | 0.127998E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.905230E+09 | 0.754376E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.114352E+11 | 0.187006E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.823729E+09 | 0.491079E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.116315E+10 | 0.282278E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_5:5
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.904204E+09 | 0.464581E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.819003E+09 | 0.570493E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.922681E+09 | 0.823361E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.878927E+09 | 0.115574E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.928350E+09 | 0.176222E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.969490E+09 | 0.215613E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.109068E+10 | 0.260082E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.115592E+10 | 0.280460E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.992555E+09 | 0.230691E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.922868E+09 | 0.181012E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.880346E+09 | 0.125814E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.900043E+09 | 0.728288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.113651E+11 | 0.184414E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.819003E+09 | 0.464581E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.115592E+10 | 0.280460E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_6:6
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.148266E+10 | 0.772933E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.134314E+10 | 0.979585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.151519E+10 | 0.145777E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.144080E+10 | 0.208424E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.154011E+10 | 0.322595E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.165207E+10 | 0.395592E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.189175E+10 | 0.475888E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.201321E+10 | 0.516378E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.170775E+10 | 0.423158E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.153099E+10 | 0.328527E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.144558E+10 | 0.226728E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.147515E+10 | 0.126289E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.190384E+11 | 0.334461E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.134314E+10 | 0.772933E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.201321E+10 | 0.516378E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_7:7
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.811469E+09 | 0.398297E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.735051E+09 | 0.506478E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.829209E+09 | 0.755722E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.788341E+09 | 0.108435E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.841656E+09 | 0.168082E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.900614E+09 | 0.205957E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.102957E+10 | 0.247874E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.109388E+10 | 0.268699E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.929523E+09 | 0.220273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.836269E+09 | 0.170996E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.790875E+09 | 0.117883E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.807284E+09 | 0.654570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.103937E+11 | 0.173971E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.735051E+09 | 0.398297E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.109388E+10 | 0.268699E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_8:8
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.808937E+09 | 0.391573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.732742E+09 | 0.500186E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.826610E+09 | 0.749170E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.785852E+09 | 0.107891E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.839234E+09 | 0.167635E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.898480E+09 | 0.205520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.102769E+10 | 0.247499E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.109195E+10 | 0.268319E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.927600E+09 | 0.219886E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.833862E+09 | 0.170577E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.788399E+09 | 0.117377E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.804752E+09 | 0.648332E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.103661E+11 | 0.173363E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.732742E+09 | 0.391573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.109195E+10 | 0.268319E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_9:9
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.814424E+09 | 0.377883E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.737651E+09 | 0.488020E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.832178E+09 | 0.738805E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.791060E+09 | 0.107644E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.844952E+09 | 0.168690E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.905061E+09 | 0.207094E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.103685E+10 | 0.249847E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.110258E+10 | 0.271141E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.935493E+09 | 0.221944E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.839742E+09 | 0.172000E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.793647E+09 | 0.117717E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.810171E+09 | 0.638855E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.104438E+11 | 0.174043E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.737651E+09 | 0.377883E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.110258E+10 | 0.271141E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_10:10
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.941542E+09 | 0.418304E+10 | 40555.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.852717E+09 | 0.534326E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.961977E+09 | 0.813206E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.914190E+09 | 0.121040E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.972737E+09 | 0.193248E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.103355E+10 | 0.236890E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.118421E+10 | 0.285763E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.126674E+10 | 0.311951E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.107048E+10 | 0.254533E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.967214E+09 | 0.197971E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.916680E+09 | 0.134158E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.936556E+09 | 0.706445E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.120186E+11 | 0.198278E+12 | 40555.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.852717E+09 | 0.418304E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.126674E+10 | 0.311951E+11 | 40555.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.226068E+10 | 0.00 | 0.00 | 0.00 | 0.378352E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.204564E+10 | 0.00 | 0.00 | 0.00 | 0.447405E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.227013E+10 | 0.00 | 0.00 | 0.00 | 0.643679E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.219037E+10 | 0.00 | 0.00 | 0.00 | 0.926231E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.228700E+10 | 0.00 | 0.00 | 0.00 | 0.141165E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.234966E+10 | 0.00 | 0.00 | 0.00 | 0.167154E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.264271E+10 | 0.00 | 0.00 | 0.00 | 0.202121E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.274234E+10 | 0.00 | 0.00 | 0.00 | 0.212396E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.242601E+10 | 0.00 | 0.00 | 0.00 | 0.175247E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.229630E+10 | 0.00 | 0.00 | 0.00 | 0.138015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.219008E+10 | 0.00 | 0.00 | 0.00 | 0.945002E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.227008E+10 | 0.00 | 0.00 | 0.00 | 0.566240E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.279710E+11 | 0.00 | 0.00 | 0.00 | 0.142679E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.204564E+10 | 0.00 | 0.00 | 0.00 | 0.378352E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.274234E+10 | 0.00 | 0.00 | 0.00 | 0.212396E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.924935E+09 | 0.00 | 0.00 | 0.00 | 0.196839E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.843006E+09 | 0.00 | 0.00 | 0.00 | 0.221361E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.949635E+09 | 0.00 | 0.00 | 0.00 | 0.302224E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.931025E+09 | 0.00 | 0.00 | 0.00 | 0.411984E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.100991E+10 | 0.00 | 0.00 | 0.00 | 0.608171E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.107011E+10 | 0.00 | 0.00 | 0.00 | 0.714442E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.122566E+10 | 0.00 | 0.00 | 0.00 | 0.862068E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.127888E+10 | 0.00 | 0.00 | 0.00 | 0.905049E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.110941E+10 | 0.00 | 0.00 | 0.00 | 0.745829E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.101348E+10 | 0.00 | 0.00 | 0.00 | 0.592845E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.934771E+09 | 0.00 | 0.00 | 0.00 | 0.418636E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.936362E+09 | 0.00 | 0.00 | 0.00 | 0.272320E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.122272E+11 | 0.00 | 0.00 | 0.00 | 0.625177E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.843006E+09 | 0.00 | 0.00 | 0.00 | 0.196839E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.127888E+10 | 0.00 | 0.00 | 0.00 | 0.905049E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_3:3
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.907383E+09 | 0.00 | 0.00 | 0.00 | 0.132480E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.821949E+09 | 0.00 | 0.00 | 0.00 | 0.159717E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.926033E+09 | 0.00 | 0.00 | 0.00 | 0.231197E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.882250E+09 | 0.00 | 0.00 | 0.00 | 0.322899E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.931349E+09 | 0.00 | 0.00 | 0.00 | 0.494475E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.972921E+09 | 0.00 | 0.00 | 0.00 | 0.589254E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.109279E+10 | 0.00 | 0.00 | 0.00 | 0.709482E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.115837E+10 | 0.00 | 0.00 | 0.00 | 0.760566E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.995524E+09 | 0.00 | 0.00 | 0.00 | 0.610053E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.926228E+09 | 0.00 | 0.00 | 0.00 | 0.479317E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.883647E+09 | 0.00 | 0.00 | 0.00 | 0.334593E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.903277E+09 | 0.00 | 0.00 | 0.00 | 0.198630E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.114017E+11 | 0.00 | 0.00 | 0.00 | 0.502266E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.821949E+09 | 0.00 | 0.00 | 0.00 | 0.132480E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.115837E+10 | 0.00 | 0.00 | 0.00 | 0.760566E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_4:4
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.909346E+09 | 0.00 | 0.00 | 0.00 | 0.130507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.823729E+09 | 0.00 | 0.00 | 0.00 | 0.158524E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.928041E+09 | 0.00 | 0.00 | 0.00 | 0.230674E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.884199E+09 | 0.00 | 0.00 | 0.00 | 0.323573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.933932E+09 | 0.00 | 0.00 | 0.00 | 0.497133E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.976264E+09 | 0.00 | 0.00 | 0.00 | 0.592486E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.109763E+10 | 0.00 | 0.00 | 0.00 | 0.713896E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.116315E+10 | 0.00 | 0.00 | 0.00 | 0.764977E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.999376E+09 | 0.00 | 0.00 | 0.00 | 0.613587E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.928685E+09 | 0.00 | 0.00 | 0.00 | 0.481956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.885575E+09 | 0.00 | 0.00 | 0.00 | 0.335464E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.905230E+09 | 0.00 | 0.00 | 0.00 | 0.197837E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.114352E+11 | 0.00 | 0.00 | 0.00 | 0.504061E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.823729E+09 | 0.00 | 0.00 | 0.00 | 0.130507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.116315E+10 | 0.00 | 0.00 | 0.00 | 0.764977E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_5:5
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.904204E+09 | 0.00 | 0.00 | 0.00 | 0.123821E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.819003E+09 | 0.00 | 0.00 | 0.00 | 0.152522E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.922681E+09 | 0.00 | 0.00 | 0.00 | 0.224224E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.878927E+09 | 0.00 | 0.00 | 0.00 | 0.317762E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.928350E+09 | 0.00 | 0.00 | 0.00 | 0.491998E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.969490E+09 | 0.00 | 0.00 | 0.00 | 0.587108E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.109068E+10 | 0.00 | 0.00 | 0.00 | 0.708951E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.115592E+10 | 0.00 | 0.00 | 0.00 | 0.759746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.992555E+09 | 0.00 | 0.00 | 0.00 | 0.608661E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.922868E+09 | 0.00 | 0.00 | 0.00 | 0.477208E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.880346E+09 | 0.00 | 0.00 | 0.00 | 0.330159E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.900043E+09 | 0.00 | 0.00 | 0.00 | 0.191420E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.113651E+11 | 0.00 | 0.00 | 0.00 | 0.497358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.819003E+09 | 0.00 | 0.00 | 0.00 | 0.123821E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.115592E+10 | 0.00 | 0.00 | 0.00 | 0.759746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_6:6
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.148266E+10 | 0.00 | 0.00 | 0.00 | 0.210099E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.134314E+10 | 0.00 | 0.00 | 0.00 | 0.266582E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.151519E+10 | 0.00 | 0.00 | 0.00 | 0.403446E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.144080E+10 | 0.00 | 0.00 | 0.00 | 0.580452E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.154011E+10 | 0.00 | 0.00 | 0.00 | 0.910238E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.165207E+10 | 0.00 | 0.00 | 0.00 | 0.109014E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.189175E+10 | 0.00 | 0.00 | 0.00 | 0.131385E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.201321E+10 | 0.00 | 0.00 | 0.00 | 0.141633E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.170775E+10 | 0.00 | 0.00 | 0.00 | 0.113009E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.153099E+10 | 0.00 | 0.00 | 0.00 | 0.876395E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.144558E+10 | 0.00 | 0.00 | 0.00 | 0.602466E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.147515E+10 | 0.00 | 0.00 | 0.00 | 0.337383E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.190384E+11 | 0.00 | 0.00 | 0.00 | 0.913748E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.134314E+10 | 0.00 | 0.00 | 0.00 | 0.210099E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.201321E+10 | 0.00 | 0.00 | 0.00 | 0.141633E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_7:7
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.811469E+09 | 0.00 | 0.00 | 0.00 | 0.106574E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.735051E+09 | 0.00 | 0.00 | 0.00 | 0.135718E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.829209E+09 | 0.00 | 0.00 | 0.00 | 0.206017E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.788341E+09 | 0.00 | 0.00 | 0.00 | 0.297532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.841656E+09 | 0.00 | 0.00 | 0.00 | 0.467542E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.900614E+09 | 0.00 | 0.00 | 0.00 | 0.559811E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.102957E+10 | 0.00 | 0.00 | 0.00 | 0.675076E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.109388E+10 | 0.00 | 0.00 | 0.00 | 0.727097E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.929523E+09 | 0.00 | 0.00 | 0.00 | 0.580174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.836269E+09 | 0.00 | 0.00 | 0.00 | 0.449765E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.790875E+09 | 0.00 | 0.00 | 0.00 | 0.308663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.807284E+09 | 0.00 | 0.00 | 0.00 | 0.172189E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.103937E+11 | 0.00 | 0.00 | 0.00 | 0.468616E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.735051E+09 | 0.00 | 0.00 | 0.00 | 0.106574E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.109388E+10 | 0.00 | 0.00 | 0.00 | 0.727097E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_8:8
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.808937E+09 | 0.00 | 0.00 | 0.00 | 0.104844E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.732742E+09 | 0.00 | 0.00 | 0.00 | 0.134107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.826610E+09 | 0.00 | 0.00 | 0.00 | 0.204322E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.785852E+09 | 0.00 | 0.00 | 0.00 | 0.296084E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.839234E+09 | 0.00 | 0.00 | 0.00 | 0.466217E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.898480E+09 | 0.00 | 0.00 | 0.00 | 0.558493E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.102769E+10 | 0.00 | 0.00 | 0.00 | 0.673855E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.109195E+10 | 0.00 | 0.00 | 0.00 | 0.725841E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.927600E+09 | 0.00 | 0.00 | 0.00 | 0.579007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.833862E+09 | 0.00 | 0.00 | 0.00 | 0.448564E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.788399E+09 | 0.00 | 0.00 | 0.00 | 0.307350E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.804752E+09 | 0.00 | 0.00 | 0.00 | 0.170614E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.103661E+11 | 0.00 | 0.00 | 0.00 | 0.466930E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.732742E+09 | 0.00 | 0.00 | 0.00 | 0.104844E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.109195E+10 | 0.00 | 0.00 | 0.00 | 0.725841E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_9:9
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.814424E+09 | 0.00 | 0.00 | 0.00 | 0.101387E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.737651E+09 | 0.00 | 0.00 | 0.00 | 0.131118E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.832178E+09 | 0.00 | 0.00 | 0.00 | 0.201871E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.791060E+09 | 0.00 | 0.00 | 0.00 | 0.295784E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.844952E+09 | 0.00 | 0.00 | 0.00 | 0.469311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.905061E+09 | 0.00 | 0.00 | 0.00 | 0.562981E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.103685E+10 | 0.00 | 0.00 | 0.00 | 0.680555E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.110258E+10 | 0.00 | 0.00 | 0.00 | 0.733776E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.935493E+09 | 0.00 | 0.00 | 0.00 | 0.584633E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.839742E+09 | 0.00 | 0.00 | 0.00 | 0.452353E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.793647E+09 | 0.00 | 0.00 | 0.00 | 0.308440E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.810171E+09 | 0.00 | 0.00 | 0.00 | 0.168381E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.104438E+11 | 0.00 | 0.00 | 0.00 | 0.469059E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.737651E+09 | 0.00 | 0.00 | 0.00 | 0.101387E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.110258E+10 | 0.00 | 0.00 | 0.00 | 0.733776E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_10:10
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.941542E+09 | 0.00 | 0.00 | 0.00 | 0.114600E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.852717E+09 | 0.00 | 0.00 | 0.00 | 0.146983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.961977E+09 | 0.00 | 0.00 | 0.00 | 0.227645E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.914190E+09 | 0.00 | 0.00 | 0.00 | 0.340977E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.972737E+09 | 0.00 | 0.00 | 0.00 | 0.551222E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.103355E+10 | 0.00 | 0.00 | 0.00 | 0.660859E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.118421E+10 | 0.00 | 0.00 | 0.00 | 0.800207E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.126674E+10 | 0.00 | 0.00 | 0.00 | 0.868224E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.107048E+10 | 0.00 | 0.00 | 0.00 | 0.688631E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.967214E+09 | 0.00 | 0.00 | 0.00 | 0.533379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.916680E+09 | 0.00 | 0.00 | 0.00 | 0.360030E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.936556E+09 | 0.00 | 0.00 | 0.00 | 0.190655E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.120186E+11 | 0.00 | 0.00 | 0.00 | 0.548341E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.852717E+09 | 0.00 | 0.00 | 0.00 | 0.114600E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.126674E+10 | 0.00 | 0.00 | 0.00 | 0.868224E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.591440E+09 | 0.657056E+09 | 0.00 | 9921932.12 | 2582762.19 | 0.00 | 0.164026E+10 | 0.00 | 0.57 |
February | 0.284234E+09 | 0.170790E+10 | 0.00 | 6452032.10 | 4884381.17 | 0.00 | 0.934158E+09 | 0.00 | 0.57 |
March | 0.209907E+09 | 0.364128E+10 | 0.00 | 3735659.64 | 7007118.28 | 0.00 | 0.432670E+09 | 0.00 | 0.57 |
April | 58547118.39 | 0.849041E+10 | 0.00 | 710512.47 | 32639717.54 | 0.00 | 94803400.50 | 0.00 | 0.57 |
May | 2879117.25 | 0.158693E+11 | 0.00 | 875716.32 | 74537663.77 | 0.00 | 3058322.41 | 0.00 | 0.58 |
June | 1314769.67 | 0.222614E+11 | 0.00 | 329886.46 | 94975195.76 | 0.00 | 1495270.00 | 0.00 | 0.58 |
July | 0.00 | 0.277764E+11 | 0.00 | 238793.74 | 80007940.65 | 0.00 | 21820.58 | 0.00 | 0.58 |
August | 0.00 | 0.296498E+11 | 0.00 | 0.00 | 74034164.43 | 0.00 | 0.00 | 0.00 | 0.58 |
September | 496578.02 | 0.244067E+11 | 0.00 | 168761.22 | 96306080.86 | 0.00 | 489026.57 | 0.00 | 0.58 |
October | 3907566.89 | 0.162585E+11 | 0.00 | 660703.75 | 0.118846E+09 | 0.00 | 13325634.82 | 0.00 | 0.57 |
November | 5099805.04 | 0.851653E+10 | 0.00 | 724168.72 | 63961204.28 | 0.00 | 13342686.85 | 0.00 | 0.57 |
December | 0.196025E+09 | 0.271834E+10 | 0.00 | 6136288.69 | 7090921.02 | 0.00 | 0.773290E+09 | 0.00 | 0.57 |
Annual Sum or Average | 0.135385E+10 | 0.161954E+12 | 0.00 | 29954455.23 | 0.656873E+09 | 0.00 | 0.390692E+10 | 0.00 | 0.58 |
Minimum of Months | 0.00 | 0.657056E+09 | 0.00 | 0.00 | 2582762.19 | 0.00 | 0.00 | 0.00 | 0.57 |
Maximum of Months | 0.591440E+09 | 0.296498E+11 | 0.00 | 9921932.12 | 0.118846E+09 | 0.00 | 0.164026E+10 | 0.00 | 0.58 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.185504E+09 | 0.350757E+09 | 0.00 | 5146746.24 | 4925543.04 | 0.00 | 0.448857E+09 | 0.00 | 0.44 |
February | 57683858.66 | 0.817769E+09 | 0.00 | 2918267.07 | 10301642.91 | 0.00 | 0.218278E+09 | 0.00 | 0.45 |
March | 41550816.91 | 0.164385E+10 | 0.00 | 1747171.40 | 13052051.91 | 0.00 | 92198007.57 | 0.00 | 0.46 |
April | 5937627.13 | 0.358048E+10 | 0.00 | 304253.17 | 37354429.58 | 0.00 | 12153262.30 | 0.00 | 0.46 |
May | 0.00 | 0.659483E+10 | 0.00 | 67161.69 | 61041597.94 | 0.00 | 0.00 | 0.00 | 0.47 |
June | 0.00 | 0.929948E+10 | 0.00 | 24813.53 | 65131349.14 | 0.00 | 0.00 | 0.00 | 0.49 |
July | 0.00 | 0.117632E+11 | 0.00 | 0.00 | 56925790.83 | 0.00 | 0.00 | 0.00 | 0.49 |
August | 0.00 | 0.127144E+11 | 0.00 | 0.00 | 55836214.52 | 0.00 | 0.00 | 0.00 | 0.50 |
September | 0.00 | 0.102169E+11 | 0.00 | 0.00 | 69089147.45 | 0.00 | 0.00 | 0.00 | 0.48 |
October | 0.00 | 0.677899E+10 | 0.00 | 94558.38 | 81899629.49 | 0.00 | 887522.82 | 0.00 | 0.47 |
November | 72048.46 | 0.373152E+10 | 0.00 | 65875.46 | 67980902.64 | 0.00 | 565136.44 | 0.00 | 0.46 |
December | 42508451.41 | 0.129391E+10 | 0.00 | 2894567.25 | 18189250.20 | 0.00 | 0.156526E+09 | 0.00 | 0.45 |
Annual Sum or Average | 0.333257E+09 | 0.687861E+11 | 0.00 | 13263414.18 | 0.541728E+09 | 0.00 | 0.929464E+09 | 0.00 | 0.47 |
Minimum of Months | 0.00 | 0.350757E+09 | 0.00 | 0.00 | 4925543.04 | 0.00 | 0.00 | 0.00 | 0.44 |
Maximum of Months | 0.185504E+09 | 0.127144E+11 | 0.00 | 5146746.24 | 81899629.49 | 0.00 | 0.448857E+09 | 0.00 | 0.50 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.478030E+09 | 0.295630E+09 | 0.00 | 3155952.05 | 6523675.47 | 0.00 | 0.471773E+09 | 0.00 | 0.45 |
February | 0.258588E+09 | 0.673699E+09 | 0.00 | 2042569.49 | 33503899.04 | 0.00 | 0.273711E+09 | 0.00 | 0.46 |
March | 0.168794E+09 | 0.139209E+10 | 0.00 | 1454198.62 | 78534847.03 | 0.00 | 0.190070E+09 | 0.00 | 0.47 |
April | 31779135.21 | 0.291058E+10 | 0.00 | 900352.22 | 0.208079E+09 | 0.00 | 0.111705E+09 | 0.00 | 0.46 |
May | 7277007.79 | 0.544939E+10 | 0.00 | 1066308.93 | 0.407557E+09 | 0.00 | 12562579.97 | 0.00 | 0.46 |
June | 1580905.51 | 0.762369E+10 | 0.00 | 677541.17 | 0.617325E+09 | 0.00 | 2399704.18 | 0.00 | 0.47 |
July | 547207.55 | 0.977083E+10 | 0.00 | 368715.11 | 0.667610E+09 | 0.00 | 2062398.32 | 0.00 | 0.46 |
August | 0.00 | 0.106896E+11 | 0.00 | 205238.59 | 0.737825E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
September | 945630.75 | 0.822858E+10 | 0.00 | 686472.14 | 0.650855E+09 | 0.00 | 4126654.28 | 0.00 | 0.46 |
October | 2645157.14 | 0.559739E+10 | 0.00 | 534586.98 | 0.441184E+09 | 0.00 | 13295071.51 | 0.00 | 0.46 |
November | 8688916.14 | 0.316930E+10 | 0.00 | 722771.99 | 0.190287E+09 | 0.00 | 25357738.44 | 0.00 | 0.46 |
December | 0.194226E+09 | 0.101903E+10 | 0.00 | 2106478.22 | 58443446.48 | 0.00 | 0.256049E+09 | 0.00 | 0.45 |
Annual Sum or Average | 0.115310E+10 | 0.568198E+11 | 0.00 | 13921185.51 | 0.409773E+10 | 0.00 | 0.136311E+10 | 0.00 | 0.46 |
Minimum of Months | 0.00 | 0.295630E+09 | 0.00 | 205238.59 | 6523675.47 | 0.00 | 0.00 | 0.00 | 0.45 |
Maximum of Months | 0.478030E+09 | 0.106896E+11 | 0.00 | 3155952.05 | 0.737825E+09 | 0.00 | 0.471773E+09 | 0.00 | 0.47 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.484940E+09 | 0.291930E+09 | 0.00 | 3088061.22 | 6455078.82 | 0.00 | 0.466546E+09 | 0.00 | 0.45 |
February | 0.266147E+09 | 0.670755E+09 | 0.00 | 2029151.91 | 33377135.27 | 0.00 | 0.268306E+09 | 0.00 | 0.46 |
March | 0.173575E+09 | 0.139107E+10 | 0.00 | 1448633.12 | 78463187.00 | 0.00 | 0.185822E+09 | 0.00 | 0.47 |
April | 31711191.00 | 0.291317E+10 | 0.00 | 907072.44 | 0.207899E+09 | 0.00 | 0.111585E+09 | 0.00 | 0.46 |
May | 7132593.54 | 0.546255E+10 | 0.00 | 1118326.49 | 0.406728E+09 | 0.00 | 12388273.08 | 0.00 | 0.46 |
June | 1571069.17 | 0.764511E+10 | 0.00 | 707685.13 | 0.614222E+09 | 0.00 | 2336302.44 | 0.00 | 0.47 |
July | 193459.73 | 0.979936E+10 | 0.00 | 399032.78 | 0.663107E+09 | 0.00 | 2336275.49 | 0.00 | 0.46 |
August | 0.00 | 0.107187E+11 | 0.00 | 212012.96 | 0.733306E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
September | 883656.93 | 0.825257E+10 | 0.00 | 741474.86 | 0.648704E+09 | 0.00 | 4074327.23 | 0.00 | 0.46 |
October | 2625441.71 | 0.561375E+10 | 0.00 | 553402.15 | 0.441664E+09 | 0.00 | 13066238.99 | 0.00 | 0.46 |
November | 8694616.88 | 0.317384E+10 | 0.00 | 738719.35 | 0.190498E+09 | 0.00 | 25338287.06 | 0.00 | 0.46 |
December | 0.198059E+09 | 0.101650E+10 | 0.00 | 2083100.28 | 58296675.04 | 0.00 | 0.253682E+09 | 0.00 | 0.45 |
Annual Sum or Average | 0.117553E+10 | 0.569493E+11 | 0.00 | 14026672.69 | 0.408272E+10 | 0.00 | 0.134548E+10 | 0.00 | 0.46 |
Minimum of Months | 0.00 | 0.291930E+09 | 0.00 | 212012.96 | 6455078.82 | 0.00 | 0.00 | 0.00 | 0.45 |
Maximum of Months | 0.484940E+09 | 0.107187E+11 | 0.00 | 3088061.22 | 0.733306E+09 | 0.00 | 0.466546E+09 | 0.00 | 0.47 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.513051E+09 | 0.277892E+09 | 0.00 | 2915487.56 | 6230254.98 | 0.00 | 0.447776E+09 | 0.00 | 0.45 |
February | 0.278730E+09 | 0.652505E+09 | 0.00 | 1960173.22 | 32631813.07 | 0.00 | 0.265923E+09 | 0.00 | 0.46 |
March | 0.188717E+09 | 0.137010E+10 | 0.00 | 1355349.42 | 77762322.09 | 0.00 | 0.176930E+09 | 0.00 | 0.47 |
April | 38377536.37 | 0.288949E+10 | 0.00 | 846441.03 | 0.207455E+09 | 0.00 | 0.109533E+09 | 0.00 | 0.46 |
May | 7222491.56 | 0.544381E+10 | 0.00 | 1049104.08 | 0.406088E+09 | 0.00 | 12671715.71 | 0.00 | 0.46 |
June | 1556288.82 | 0.761869E+10 | 0.00 | 677986.09 | 0.615070E+09 | 0.00 | 2433553.88 | 0.00 | 0.47 |
July | 197480.29 | 0.977628E+10 | 0.00 | 375890.05 | 0.664109E+09 | 0.00 | 2386937.91 | 0.00 | 0.46 |
August | 0.00 | 0.106901E+11 | 0.00 | 206164.32 | 0.737676E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
September | 890374.65 | 0.822454E+10 | 0.00 | 711907.33 | 0.649812E+09 | 0.00 | 4184020.62 | 0.00 | 0.46 |
October | 2788909.35 | 0.559191E+10 | 0.00 | 528539.43 | 0.438844E+09 | 0.00 | 13331077.94 | 0.00 | 0.46 |
November | 9211325.00 | 0.314595E+10 | 0.00 | 683380.54 | 0.189442E+09 | 0.00 | 26234227.22 | 0.00 | 0.46 |
December | 0.210478E+09 | 0.992228E+09 | 0.00 | 1989311.61 | 57305887.40 | 0.00 | 0.253352E+09 | 0.00 | 0.45 |
Annual Sum or Average | 0.125122E+10 | 0.566735E+11 | 0.00 | 13299734.67 | 0.408243E+10 | 0.00 | 0.131476E+10 | 0.00 | 0.46 |
Minimum of Months | 0.00 | 0.277892E+09 | 0.00 | 206164.32 | 6230254.98 | 0.00 | 0.00 | 0.00 | 0.45 |
Maximum of Months | 0.513051E+09 | 0.106901E+11 | 0.00 | 2915487.56 | 0.737676E+09 | 0.00 | 0.447776E+09 | 0.00 | 0.47 |
Report: MechanicalVentilationLoadsMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.634772E+09 | 0.370367E+09 | 0.00 | 5910768.99 | 9722042.87 | 0.00 | 0.104720E+10 | 0.00 | 0.42 |
February | 0.348905E+09 | 0.110036E+10 | 0.00 | 4185471.01 | 24958704.33 | 0.00 | 0.571172E+09 | 0.00 | 0.42 |
March | 0.218043E+09 | 0.250657E+10 | 0.00 | 2353325.60 | 39739616.50 | 0.00 | 0.267669E+09 | 0.00 | 0.43 |
April | 59616467.38 | 0.562427E+10 | 0.00 | 713323.09 | 0.156020E+09 | 0.00 | 75761424.98 | 0.00 | 0.42 |
May | 6461446.88 | 0.107671E+11 | 0.00 | 1158445.94 | 0.256631E+09 | 0.00 | 7244050.21 | 0.00 | 0.43 |
June | 986702.19 | 0.150017E+11 | 0.00 | 643881.10 | 0.381985E+09 | 0.00 | 1154826.33 | 0.00 | 0.44 |
July | 320121.46 | 0.188691E+11 | 0.00 | 540902.37 | 0.430138E+09 | 0.00 | 741598.10 | 0.00 | 0.43 |
August | 0.00 | 0.209214E+11 | 0.00 | 21204.84 | 0.338906E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
September | 939657.68 | 0.162215E+11 | 0.00 | 1222863.37 | 0.416188E+09 | 0.00 | 1130687.52 | 0.00 | 0.43 |
October | 6377449.58 | 0.108155E+11 | 0.00 | 905247.06 | 0.338872E+09 | 0.00 | 17986971.51 | 0.00 | 0.42 |
November | 5878739.97 | 0.607792E+10 | 0.00 | 528902.99 | 0.129282E+09 | 0.00 | 10095216.68 | 0.00 | 0.42 |
December | 0.228242E+09 | 0.171468E+10 | 0.00 | 3812241.73 | 46878751.34 | 0.00 | 0.483371E+09 | 0.00 | 0.42 |
Annual Sum or Average | 0.151054E+10 | 0.109990E+12 | 0.00 | 21996578.08 | 0.256932E+10 | 0.00 | 0.248353E+10 | 0.00 | 0.43 |
Minimum of Months | 0.00 | 0.370367E+09 | 0.00 | 21204.84 | 9722042.87 | 0.00 | 0.00 | 0.00 | 0.42 |
Maximum of Months | 0.634772E+09 | 0.209214E+11 | 0.00 | 5910768.99 | 0.430138E+09 | 0.00 | 0.104720E+10 | 0.00 | 0.44 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.319226E+09 | 0.184041E+09 | 0.00 | 2970353.28 | 4681621.58 | 0.00 | 0.514037E+09 | 0.00 | 0.42 |
February | 0.174847E+09 | 0.551938E+09 | 0.00 | 2077039.79 | 12416514.83 | 0.00 | 0.282333E+09 | 0.00 | 0.42 |
March | 0.109677E+09 | 0.125808E+10 | 0.00 | 1195155.55 | 19720467.86 | 0.00 | 0.131345E+09 | 0.00 | 0.43 |
April | 28768117.66 | 0.281923E+10 | 0.00 | 342858.15 | 77612392.81 | 0.00 | 38772000.52 | 0.00 | 0.42 |
May | 3236076.44 | 0.539752E+10 | 0.00 | 547092.52 | 0.130817E+09 | 0.00 | 3674120.73 | 0.00 | 0.43 |
June | 476142.69 | 0.751495E+10 | 0.00 | 323641.26 | 0.190109E+09 | 0.00 | 548257.99 | 0.00 | 0.44 |
July | 91812.57 | 0.943119E+10 | 0.00 | 290361.88 | 0.230994E+09 | 0.00 | 440518.25 | 0.00 | 0.43 |
August | 0.00 | 0.104682E+11 | 0.00 | 13919.36 | 0.170956E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
September | 440965.66 | 0.811266E+10 | 0.00 | 609961.21 | 0.210767E+09 | 0.00 | 559450.69 | 0.00 | 0.43 |
October | 2683225.01 | 0.541845E+10 | 0.00 | 443264.88 | 0.169342E+09 | 0.00 | 9180894.20 | 0.00 | 0.42 |
November | 2749869.51 | 0.304287E+10 | 0.00 | 254983.97 | 65235933.15 | 0.00 | 5157230.12 | 0.00 | 0.42 |
December | 0.114073E+09 | 0.857281E+09 | 0.00 | 1916869.45 | 22785207.00 | 0.00 | 0.238404E+09 | 0.00 | 0.42 |
Annual Sum or Average | 0.756270E+09 | 0.550565E+11 | 0.00 | 10985501.30 | 0.130544E+10 | 0.00 | 0.122445E+10 | 0.00 | 0.43 |
Minimum of Months | 0.00 | 0.184041E+09 | 0.00 | 13919.36 | 4681621.58 | 0.00 | 0.00 | 0.00 | 0.42 |
Maximum of Months | 0.319226E+09 | 0.104682E+11 | 0.00 | 2970353.28 | 0.230994E+09 | 0.00 | 0.514037E+09 | 0.00 | 0.44 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.320317E+09 | 0.181331E+09 | 0.00 | 2921434.92 | 4670584.17 | 0.00 | 0.516787E+09 | 0.00 | 0.42 |
February | 0.177724E+09 | 0.547664E+09 | 0.00 | 2058926.32 | 12362618.51 | 0.00 | 0.282979E+09 | 0.00 | 0.42 |
March | 0.111571E+09 | 0.125243E+10 | 0.00 | 1170922.04 | 19631054.96 | 0.00 | 0.130929E+09 | 0.00 | 0.43 |
April | 29905301.26 | 0.281291E+10 | 0.00 | 335410.64 | 77478564.54 | 0.00 | 38293486.00 | 0.00 | 0.42 |
May | 3257154.85 | 0.539204E+10 | 0.00 | 543928.82 | 0.131371E+09 | 0.00 | 3688044.28 | 0.00 | 0.43 |
June | 481142.79 | 0.750921E+10 | 0.00 | 323575.54 | 0.189974E+09 | 0.00 | 554926.51 | 0.00 | 0.44 |
July | 92649.16 | 0.942567E+10 | 0.00 | 293211.08 | 0.231308E+09 | 0.00 | 441507.43 | 0.00 | 0.43 |
August | 0.00 | 0.104629E+11 | 0.00 | 14221.12 | 0.170876E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
September | 445262.69 | 0.810708E+10 | 0.00 | 613270.27 | 0.210614E+09 | 0.00 | 564167.16 | 0.00 | 0.43 |
October | 2691882.70 | 0.541031E+10 | 0.00 | 440852.51 | 0.172165E+09 | 0.00 | 9228817.06 | 0.00 | 0.42 |
November | 2791168.29 | 0.303603E+10 | 0.00 | 252579.80 | 65100075.41 | 0.00 | 5222030.39 | 0.00 | 0.42 |
December | 0.116954E+09 | 0.851345E+09 | 0.00 | 1892457.49 | 22677647.09 | 0.00 | 0.238609E+09 | 0.00 | 0.42 |
Annual Sum or Average | 0.766231E+09 | 0.549889E+11 | 0.00 | 10860790.53 | 0.130823E+10 | 0.00 | 0.122730E+10 | 0.00 | 0.43 |
Minimum of Months | 0.00 | 0.181331E+09 | 0.00 | 14221.12 | 4670584.17 | 0.00 | 0.00 | 0.00 | 0.42 |
Maximum of Months | 0.320317E+09 | 0.104629E+11 | 0.00 | 2921434.92 | 0.231308E+09 | 0.00 | 0.516787E+09 | 0.00 | 0.44 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.327639E+09 | 0.176234E+09 | 0.00 | 2800157.99 | 4733535.58 | 0.00 | 0.515142E+09 | 0.00 | 0.42 |
February | 0.187714E+09 | 0.539653E+09 | 0.00 | 1977034.25 | 12227877.69 | 0.00 | 0.279190E+09 | 0.00 | 0.42 |
March | 0.118293E+09 | 0.124384E+10 | 0.00 | 1107711.62 | 19546435.35 | 0.00 | 0.126820E+09 | 0.00 | 0.43 |
April | 31949292.14 | 0.280694E+10 | 0.00 | 319352.07 | 78217167.93 | 0.00 | 37899618.41 | 0.00 | 0.42 |
May | 3317228.16 | 0.540381E+10 | 0.00 | 530232.32 | 0.129686E+09 | 0.00 | 3641464.52 | 0.00 | 0.43 |
June | 482864.93 | 0.753020E+10 | 0.00 | 317903.79 | 0.189543E+09 | 0.00 | 552749.73 | 0.00 | 0.44 |
July | 92518.30 | 0.946755E+10 | 0.00 | 297215.93 | 0.221223E+09 | 0.00 | 436969.76 | 0.00 | 0.43 |
August | 0.00 | 0.105034E+11 | 0.00 | 15393.91 | 0.170343E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
September | 425477.38 | 0.814051E+10 | 0.00 | 625214.54 | 0.207366E+09 | 0.00 | 536773.39 | 0.00 | 0.43 |
October | 2683446.22 | 0.543159E+10 | 0.00 | 446266.84 | 0.169535E+09 | 0.00 | 9141676.09 | 0.00 | 0.42 |
November | 2969616.89 | 0.303960E+10 | 0.00 | 242136.28 | 64751310.14 | 0.00 | 5207566.72 | 0.00 | 0.42 |
December | 0.126244E+09 | 0.842742E+09 | 0.00 | 1852038.22 | 22576077.52 | 0.00 | 0.235146E+09 | 0.00 | 0.42 |
Annual Sum or Average | 0.801811E+09 | 0.551261E+11 | 0.00 | 10530657.76 | 0.128975E+10 | 0.00 | 0.121371E+10 | 0.00 | 0.43 |
Minimum of Months | 0.00 | 0.176234E+09 | 0.00 | 15393.91 | 4733535.58 | 0.00 | 0.00 | 0.00 | 0.42 |
Maximum of Months | 0.327639E+09 | 0.105034E+11 | 0.00 | 2800157.99 | 0.221223E+09 | 0.00 | 0.515142E+09 | 0.00 | 0.44 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.311804E+09 | 0.190910E+09 | 0.00 | 2902180.67 | 4497977.62 | 0.00 | 0.499059E+09 | 0.00 | 0.42 |
February | 0.202811E+09 | 0.549678E+09 | 0.00 | 2032250.35 | 10592327.91 | 0.00 | 0.250060E+09 | 0.00 | 0.42 |
March | 0.126914E+09 | 0.126673E+10 | 0.00 | 1051892.60 | 17976615.27 | 0.00 | 0.115862E+09 | 0.00 | 0.43 |
April | 40906231.76 | 0.284339E+10 | 0.00 | 295160.66 | 73387549.60 | 0.00 | 37535627.96 | 0.00 | 0.42 |
May | 2745416.36 | 0.551639E+10 | 0.00 | 756093.01 | 0.109269E+09 | 0.00 | 4762968.59 | 0.00 | 0.43 |
June | 773738.84 | 0.772543E+10 | 0.00 | 396885.58 | 0.153158E+09 | 0.00 | 1047097.77 | 0.00 | 0.44 |
July | 71277.67 | 0.971631E+10 | 0.00 | 596914.55 | 0.174186E+09 | 0.00 | 145277.33 | 0.00 | 0.43 |
August | 0.00 | 0.108045E+11 | 0.00 | 175034.83 | 0.133609E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
September | 428438.52 | 0.839329E+10 | 0.00 | 928859.31 | 0.173792E+09 | 0.00 | 569525.12 | 0.00 | 0.43 |
October | 2263736.98 | 0.559338E+10 | 0.00 | 583035.08 | 0.144202E+09 | 0.00 | 11295965.25 | 0.00 | 0.42 |
November | 3778280.76 | 0.313871E+10 | 0.00 | 296423.89 | 57466979.81 | 0.00 | 6928510.26 | 0.00 | 0.42 |
December | 0.129497E+09 | 0.881220E+09 | 0.00 | 1881956.29 | 23109214.92 | 0.00 | 0.223567E+09 | 0.00 | 0.42 |
Annual Sum or Average | 0.821992E+09 | 0.566199E+11 | 0.00 | 11896686.82 | 0.107524E+10 | 0.00 | 0.115083E+10 | 0.00 | 0.43 |
Minimum of Months | 0.00 | 0.190910E+09 | 0.00 | 175034.83 | 4497977.62 | 0.00 | 0.00 | 0.00 | 0.42 |
Maximum of Months | 0.311804E+09 | 0.108045E+11 | 0.00 | 2902180.67 | 0.174186E+09 | 0.00 | 0.499059E+09 | 0.00 | 0.44 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:37:02
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.133394E+12 | 0.220568E+10 | 0.00 | 0.358109E+11 | 0.743083E+11 |
February | 0.156028E+12 | -0.284688E+10 | 0.00 | 0.157168E+11 | 0.906216E+11 |
March | 0.202387E+12 | -0.100799E+11 | 0.00 | -0.227578E+10 | 0.131565E+12 |
April | 0.223512E+12 | -0.241361E+11 | 0.00 | -0.410061E+11 | 0.186930E+12 |
May | 0.244583E+12 | -0.422045E+11 | 0.00 | -0.104348E+12 | 0.285747E+12 |
June | 0.238673E+12 | -0.564659E+11 | 0.00 | -0.153106E+12 | 0.347096E+12 |
July | 0.241343E+12 | -0.710450E+11 | 0.00 | -0.201857E+12 | 0.417908E+12 |
August | 0.230958E+12 | -0.761498E+11 | 0.00 | -0.215854E+12 | 0.448889E+12 |
September | 0.195110E+12 | -0.614039E+11 | 0.00 | -0.164023E+12 | 0.369832E+12 |
October | 0.157910E+12 | -0.409389E+11 | 0.00 | -0.111884E+12 | 0.289173E+12 |
November | 0.118904E+12 | -0.240755E+11 | 0.00 | -0.466529E+11 | 0.200027E+12 |
December | 0.114768E+12 | -0.662239E+10 | 0.00 | 0.112059E+11 | 0.115885E+12 |
Annual Sum or Average | 0.225757E+13 | -0.413763E+12 | 0.00 | -0.978274E+12 | 0.295798E+13 |
Minimum of Months | 0.114768E+12 | -0.761498E+11 | 0.00 | -0.215854E+12 | 0.743083E+11 |
Maximum of Months | 0.244583E+12 | 0.220568E+10 | 0.00 | 0.358109E+11 | 0.448889E+12 |