Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:37
Tabular Output Report in Format: HTML
Building: RetailStripmall
Environment: RUNPERIOD 1 ** Tampa-MacDill AFB FL USA TMY3 WMO#=747880
Simulation Timestamp: 2023-10-16 08:37:30
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:30
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1089.74 | 521.33 | 521.33 |
Net Site Energy | 1089.74 | 521.33 | 521.33 |
Total Source Energy | 3411.06 | 1631.84 | 1631.84 |
Net Source Energy | 3411.06 | 1631.84 | 1631.84 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 2090.32 |
Net Conditioned Building Area | 2090.32 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 19.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 352.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 366.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 60.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 128.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 102.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 59.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1070.47 | 19.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 19.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 352.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 366.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 60.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 128.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 102.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 59.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 19.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 352.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 366.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 60.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 128.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 102.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 59.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 204.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 246.67 | 9.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Other | 61.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 512.11 | 9.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 204.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 246.67 | 9.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Other | 61.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 512.11 | 9.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1070.467 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1070.467 | 100.00 |
Total On-Site and Utility Electric Sources | 1070.467 | 100.00 |
Total Electricity End Uses | 1070.467 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 87.30 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 87.30 | 100.00 |
Total Water End Uses | 87.30 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 0.17 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 2026.67 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTRIPMALL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 2A
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_FL_TAMPA
| Environment |ZoneCoolingSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ZoneHeatingSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ZoneElectricSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |SpaceGainsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |PeakSpaceGainsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |SpaceGainComponentsAtCoolingPeakMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ComfortReportSimple55Monthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |OccupantComfortDataSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |DXReportMonthly
| PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL | PSZ-AC_3:3 COOLING COIL | PSZ-AC_4:4 COOLING COIL | PSZ-AC_5:5 COOLING COIL | PSZ-AC_6:6 COOLING COIL | PSZ-AC_7:7 COOLING COIL | PSZ-AC_8:8 COOLING COIL | PSZ-AC_9:9 COOLING COIL | PSZ-AC_10:10 COOLING COIL |WindowReportMonthly
| LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR |WindowEnergyReportMonthly
| LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR |WindowZoneSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |WindowEnergyZoneSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| GAS TANK1 | GAS TANK2 | GAS TANK3 | GAS TANK4 | GAS TANK5 | GAS TANK6 | GAS TANK7 |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC_1:1 HEATING COIL | PSZ-AC_2:2 HEATING COIL | PSZ-AC_3:3 HEATING COIL | PSZ-AC_4:4 HEATING COIL | PSZ-AC_5:5 HEATING COIL | PSZ-AC_6:6 HEATING COIL | PSZ-AC_7:7 HEATING COIL | PSZ-AC_8:8 HEATING COIL | PSZ-AC_9:9 HEATING COIL | PSZ-AC_10:10 HEATING COIL | PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL | PSZ-AC_3:3 COOLING COIL | PSZ-AC_4:4 COOLING COIL | PSZ-AC_5:5 COOLING COIL | PSZ-AC_6:6 COOLING COIL | PSZ-AC_7:7 COOLING COIL | PSZ-AC_8:8 COOLING COIL | PSZ-AC_9:9 COOLING COIL | PSZ-AC_10:10 COOLING COIL |FanReportMonthly
| PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN |ZoneTemperatureOscillationReportMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |MechanicalVentilationLoadsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:30
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:37 |
RunPeriod | RUNPERIOD 1 |
Weather File | Tampa-MacDill AFB FL USA TMY3 WMO#=747880 |
Latitude [deg] | 27.85 |
Longitude [deg] | -82.5 |
Elevation [m] | 8.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Above Ground Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Window Opening Area [m2] | 124.40 | 0.00 | 0.00 | 124.40 | 0.00 |
Gross Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Above Ground Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Above Ground Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Window Opening Area [m2] | 124.40 | 0.00 | 0.00 | 124.40 | 0.00 |
Gross Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Above Ground Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Total | |
Gross Roof Area [m2] | 2090.32 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
LGSTORE1 | 348.39 | Yes | Yes | 1805.20 | 1.00 | 276.30 | 0.00 | 20.77 | 20.77 | 15.3022 | 6.19 | 4.3000 |
SMSTORE1 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.38 | 10.38 | 18.2890 | 6.19 | 4.3000 |
SMSTORE2 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 16.6533 | 6.19 | 4.3000 |
SMSTORE3 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 16.6533 | 6.19 | 4.3000 |
SMSTORE4 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 16.6533 | 6.19 | 4.3000 |
LGSTORE2 | 348.39 | Yes | Yes | 1805.20 | 1.00 | 157.89 | 0.00 | 20.72 | 20.72 | 9.5842 | 6.19 | 4.3000 |
SMSTORE5 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 9.6995 | 6.19 | 4.3000 |
SMSTORE6 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 9.6995 | 6.19 | 4.3000 |
SMSTORE7 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 9.6995 | 6.19 | 4.3000 |
SMSTORE8 | 174.19 | Yes | Yes | 902.60 | 1.00 | 197.36 | 0.00 | 10.36 | 10.36 | 9.6995 | 6.19 | 4.3000 |
Total | 2090.32 | 10831.20 | 1184.15 | 0.00 | 124.40 | 124.40 | 13.0683 | 6.19 | 4.3000 | |||
Conditioned Total | 2090.32 | 10831.20 | 1184.15 | 0.00 | 124.40 | 124.40 | 13.0683 | 6.19 | 4.3000 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
LGSTORE1 | 348.39 | Yes | Yes | 1.00 | LGSTORE1 | GENERAL | LGSTORE1 | 15.3022 | 6.19 | 4.3000 | |
SMSTORE1 | 174.19 | Yes | Yes | 1.00 | SMSTORE1 | GENERAL | SMSTORE1 | 18.2890 | 6.19 | 4.3000 | |
SMSTORE2 | 174.19 | Yes | Yes | 1.00 | SMSTORE2 | GENERAL | SMSTORE2 | 16.6533 | 6.19 | 4.3000 | |
SMSTORE3 | 174.19 | Yes | Yes | 1.00 | SMSTORE3 | GENERAL | SMSTORE3 | 16.6533 | 6.19 | 4.3000 | |
SMSTORE4 | 174.19 | Yes | Yes | 1.00 | SMSTORE4 | GENERAL | SMSTORE4 | 16.6533 | 6.19 | 4.3000 | |
LGSTORE2 | 348.39 | Yes | Yes | 1.00 | LGSTORE2 | GENERAL | LGSTORE2 | 9.5842 | 6.19 | 4.3000 | |
SMSTORE5 | 174.19 | Yes | Yes | 1.00 | SMSTORE5 | GENERAL | SMSTORE5 | 9.6995 | 6.19 | 4.3000 | |
SMSTORE6 | 174.19 | Yes | Yes | 1.00 | SMSTORE6 | GENERAL | SMSTORE6 | 9.6995 | 6.19 | 4.3000 | |
SMSTORE7 | 174.19 | Yes | Yes | 1.00 | SMSTORE7 | GENERAL | SMSTORE7 | 9.6995 | 6.19 | 4.3000 | |
SMSTORE8 | 174.19 | Yes | Yes | 1.00 | SMSTORE8 | GENERAL | SMSTORE8 | 9.6995 | 6.19 | 4.3000 | |
Total | 2090.32 | 13.0683 | 3.10 | 4.3000 | |||||||
Conditioned Total | 2090.32 | 13.0683 | 3.10 | 4.3000 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 2090.32 | 2090.32 | 0.00 | 0.00 | 13.0683 | 6.19 | 4.3000 |
Total | 2090.32 | 2090.32 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:30
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 10-SEP-13:30 | 05-FEB-09:09 | - | - | - | - | - | - | - | - | - | - | 06-JAN-13:09 |
Heating | 0.00 | 99899.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 71628.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 23459.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 8059.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 11264.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 5105.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 119517.11 | 99899.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 99899.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 71628.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 23459.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 8059.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 11264.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 5105.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:30
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 20.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1117.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1161.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 190.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 405.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 325.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 189.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 3390.17 | 20.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 9.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 534.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 555.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 90.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 194.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 155.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 90.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1621.84 | 9.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 9.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 534.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 555.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 90.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 194.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 155.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 90.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1621.84 | 9.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:30
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
LGSTORE1 DIRECT AIR | 2.16 |
SMSTORE1 DIRECT AIR | 1.14 |
SMSTORE2 DIRECT AIR | 1.14 |
SMSTORE3 DIRECT AIR | 1.15 |
SMSTORE4 DIRECT AIR | 1.14 |
LGSTORE2 DIRECT AIR | 1.99 |
SMSTORE5 DIRECT AIR | 1.04 |
SMSTORE6 DIRECT AIR | 1.04 |
SMSTORE7 DIRECT AIR | 1.04 |
SMSTORE8 DIRECT AIR | 1.20 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC_1:1 | 2.16 | 2.16 | 2.16 | 2.16 | 2.16 | 2.16 | 1.00 | 1.00 | 2.16 |
PSZ-AC_2:2 | 1.14 | 1.14 | 1.14 | 1.14 | 1.14 | 1.14 | 1.00 | 1.00 | 1.14 |
PSZ-AC_3:3 | 1.14 | 1.14 | 1.14 | 1.14 | 1.14 | 1.14 | 1.00 | 1.00 | 1.14 |
PSZ-AC_4:4 | 1.15 | 1.15 | 1.15 | 1.15 | 1.15 | 1.15 | 1.00 | 1.00 | 1.15 |
PSZ-AC_5:5 | 1.14 | 1.14 | 1.14 | 1.14 | 1.14 | 1.14 | 1.00 | 1.00 | 1.14 |
PSZ-AC_6:6 | 1.99 | 1.99 | 1.99 | 1.99 | 1.99 | 1.99 | 1.00 | 1.000000 | 1.99 |
PSZ-AC_7:7 | 1.04 | 1.04 | 1.04 | 1.04 | 1.04 | 1.04 | 1.00 | 1.000000 | 1.04 |
PSZ-AC_8:8 | 1.04 | 1.04 | 1.04 | 1.04 | 1.04 | 1.04 | 1.00 | 1.00 | 1.04 |
PSZ-AC_9:9 | 1.04 | 1.04 | 1.04 | 1.04 | 1.04 | 1.04 | 1.00 | 1.00 | 1.04 |
PSZ-AC_10:10 | 1.20 | 1.20 | 1.20 | 1.20 | 1.20 | 1.20 | 1.00 | 1.000000 | 1.20 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC_1:1_OA_CONTROLLER | 2.16 | 0.411479 |
PSZ-AC_2:2_OA_CONTROLLER | 1.14 | 0.205739 |
PSZ-AC_3:3_OA_CONTROLLER | 1.14 | 0.205739 |
PSZ-AC_4:4_OA_CONTROLLER | 1.15 | 0.205739 |
PSZ-AC_5:5_OA_CONTROLLER | 1.14 | 0.205739 |
PSZ-AC_6:6_OA_CONTROLLER | 1.99 | 0.411479 |
PSZ-AC_7:7_OA_CONTROLLER | 1.04 | 0.205739 |
PSZ-AC_8:8_OA_CONTROLLER | 1.04 | 0.205739 |
PSZ-AC_9:9_OA_CONTROLLER | 1.04 | 0.205739 |
PSZ-AC_10:10_OA_CONTROLLER | 1.20 | 0.205739 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | 2.16 | 2311.27 |
PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | 1.14 | 1262.21 |
PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | 1.14 | 1265.00 |
PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | 1.15 | 1268.62 |
PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | 1.14 | 1257.69 |
PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | 1.99 | 2129.41 |
PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | 1.04 | 1156.31 |
PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | 1.04 | 1151.44 |
PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | 1.04 | 1155.03 |
PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | 1.20 | 1330.97 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC_1:1_UNITARY_PACKAGE_DX | 2.16 | 2.16 | 2.16 | 1.43 | 53637.21 | 57547.23 | 40.00 | 1.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_DX | 1.14 | 1.14 | 1.14 | 0.752427 | 28309.95 | 30145.39 | 40.00 | 1.00 |
PSZ-AC_3:3_UNITARY_PACKAGE_DX | 1.14 | 1.14 | 1.14 | 0.754095 | 28372.68 | 30203.09 | 40.00 | 1.00 |
PSZ-AC_4:4_UNITARY_PACKAGE_DX | 1.15 | 1.15 | 1.15 | 0.756249 | 28453.74 | 30277.65 | 40.00 | 1.00 |
PSZ-AC_5:5_UNITARY_PACKAGE_DX | 1.14 | 1.14 | 1.14 | 0.749732 | 28208.53 | 30052.10 | 40.00 | 1.00 |
PSZ-AC_6:6_UNITARY_PACKAGE_DX | 1.99 | 1.99 | 1.99 | 1.31 | 49416.79 | 53665.15 | 40.00 | 1.00 |
PSZ-AC_7:7_UNITARY_PACKAGE_DX | 1.04 | 1.04 | 1.04 | 0.689303 | 25934.88 | 27960.84 | 40.00 | 1.00 |
PSZ-AC_8:8_UNITARY_PACKAGE_DX | 1.04 | 1.04 | 1.04 | 0.686398 | 25825.61 | 27860.33 | 40.00 | 1.00 |
PSZ-AC_9:9_UNITARY_PACKAGE_DX | 1.04 | 1.04 | 1.04 | 0.688536 | 25906.06 | 27934.32 | 40.00 | 1.00 |
PSZ-AC_10:10_UNITARY_PACKAGE_DX | 1.20 | 1.20 | 1.20 | 0.793421 | 29725.08 | 31564.30 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-AC_1:1 COOLING COIL | 2.16 | 1.08 | 1.44 | 53637.21 | 26818.60 | 0.701080 | 0.701080 |
PSZ-AC_2:2 COOLING COIL | 1.14 | 0.570021 | 0.760027 | 28309.95 | 14154.98 | 0.701080 | 0.701080 |
PSZ-AC_3:3 COOLING COIL | 1.14 | 0.571284 | 0.761713 | 28372.68 | 14186.34 | 0.701080 | 0.701080 |
PSZ-AC_4:4 COOLING COIL | 1.15 | 0.572916 | 0.763887 | 28453.74 | 14226.87 | 0.701080 | 0.701080 |
PSZ-AC_5:5 COOLING COIL | 1.14 | 0.567979 | 0.757307 | 28208.53 | 14104.26 | 0.701080 | 0.701080 |
PSZ-AC_6:6 COOLING COIL | 1.99 | 0.995007 | 1.33 | 49416.79 | 24708.40 | 0.701080 | 0.701080 |
PSZ-AC_7:7 COOLING COIL | 1.04 | 0.522199 | 0.696267 | 25934.88 | 12967.44 | 0.701080 | 0.701080 |
PSZ-AC_8:8 COOLING COIL | 1.04 | 0.519999 | 0.693333 | 25825.61 | 12912.81 | 0.701080 | 0.701080 |
PSZ-AC_9:9 COOLING COIL | 1.04 | 0.521619 | 0.695493 | 25906.06 | 12953.03 | 0.701080 | 0.701080 |
PSZ-AC_10:10 COOLING COIL | 1.20 | 0.601077 | 0.801433 | 29725.08 | 14862.54 | 0.703130 | 0.703130 |
Design Size Nominal Capacity [W] | |
PSZ-AC_1:1 HEATING COIL | 57547.23 |
PSZ-AC_2:2 HEATING COIL | 30145.39 |
PSZ-AC_3:3 HEATING COIL | 30203.09 |
PSZ-AC_4:4 HEATING COIL | 30277.65 |
PSZ-AC_5:5 HEATING COIL | 30052.10 |
PSZ-AC_6:6 HEATING COIL | 53665.15 |
PSZ-AC_7:7 HEATING COIL | 27960.84 |
PSZ-AC_8:8 HEATING COIL | 27860.33 |
PSZ-AC_9:9 HEATING COIL | 27934.32 |
PSZ-AC_10:10 HEATING COIL | 31564.30 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:30
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
LGSTORE1_WALL_3 | LGSTORE1_WALL_3_DOOR_1 | LGSTORE1_WALL_3_DOOR_2 | |
LGSTORE1_WALL_1 | LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | |
SMSTORE1_WALL_1 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | |
SMSTORE1_WALL_3 | SMSTORE1_WALL_3_DOOR | |
SMSTORE2_WALL_1 | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | |
SMSTORE2_WALL_3 | SMSTORE2_WALL_3_DOOR | |
SMSTORE3_WALL_1 | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | |
SMSTORE3_WALL_3 | SMSTORE3_WALL_3_DOOR | |
SMSTORE4_WALL_1 | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | |
SMSTORE4_WALL_3 | SMSTORE4_WALL_3_DOOR | |
LGSTORE2_WALL_3 | LGSTORE2_WALL_3_DOOR_1 | LGSTORE2_WALL_3_DOOR_2 | |
LGSTORE2_WALL_1 | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | |
SMSTORE5_WALL_1 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | |
SMSTORE5_WALL_3 | SMSTORE5_WALL_3_DOOR | |
SMSTORE6_WALL_1 | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | |
SMSTORE6_WALL_3 | SMSTORE6_WALL_3_DOOR | |
SMSTORE7_WALL_1 | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | |
SMSTORE7_WALL_3 | SMSTORE7_WALL_3_DOOR | |
SMSTORE8_WALL_1 | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR | |
SMSTORE8_WALL_3 | SMSTORE8_WALL_3_DOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:30
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:30
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 24.20 | 18.90 | 15.70 | 13.60 | 15.50 | 17.10 | 21.20 | 26.90 | 27.60 | 27.90 | 27.40 | 26.20 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Tampa-MacDill AFB FL USA TMY3 WMO#=747880 | 27.85 | -82.52 | -5.00 | 8.00 | 101229 | 1.2032 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 21.85 | 14.30 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RetailStripmall | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 10 | 118 | 48 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | LGSTORE1 | 0.0 | 0.00 | 0.00 | 0.00 | 7.62 | 11.43 | 2.59 | 1 | 1 | 1 | 0.00 | 15.24 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 1805.20 | TARP | TARP | 348.39 | 276.30 | 247.74 | 20.77 | 6 | 8 | 0 | Yes |
2 | SMSTORE1 | 0.0 | 0.00 | 0.00 | 0.00 | 19.05 | 11.43 | 2.59 | 1 | 1 | 1 | 15.24 | 22.86 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.66 | 10.38 | 6 | 4 | 0 | Yes |
3 | SMSTORE2 | 0.0 | 0.00 | 0.00 | 0.00 | 26.67 | 11.43 | 2.59 | 1 | 1 | 1 | 22.86 | 30.48 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
4 | SMSTORE3 | 0.0 | 0.00 | 0.00 | 0.00 | 34.29 | 11.43 | 2.59 | 1 | 1 | 1 | 30.48 | 38.10 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
5 | SMSTORE4 | 0.0 | 0.00 | 0.00 | 0.00 | 41.91 | 11.43 | 2.59 | 1 | 1 | 1 | 38.10 | 45.72 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
6 | LGSTORE2 | 0.0 | 0.00 | 0.00 | 0.00 | 53.34 | 11.43 | 2.59 | 1 | 1 | 1 | 45.72 | 60.96 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 1805.20 | TARP | TARP | 348.39 | 157.89 | 129.41 | 20.72 | 6 | 8 | 0 | Yes |
7 | SMSTORE5 | 0.0 | 0.00 | 0.00 | 0.00 | 64.77 | 11.43 | 2.59 | 1 | 1 | 1 | 60.96 | 68.58 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
8 | SMSTORE6 | 0.0 | 0.00 | 0.00 | 0.00 | 72.39 | 11.43 | 2.59 | 1 | 1 | 1 | 68.58 | 76.20 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
9 | SMSTORE7 | 0.0 | 0.00 | 0.00 | 0.00 | 80.01 | 11.43 | 2.59 | 1 | 1 | 1 | 76.20 | 83.82 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
10 | SMSTORE8 | 0.0 | 0.00 | 0.00 | 0.00 | 87.63 | 11.43 | 2.59 | 1 | 1 | 1 | 83.82 | 91.44 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 197.36 | 183.12 | 10.36 | 6 | 4 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | LGSTORE1 | 348.39 | 56.3 | 6.193 | 0.161 | 15.302 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 19.602 | No |
2 | SMSTORE1 | 174.19 | 28.1 | 6.194 | 0.161 | 18.289 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 22.589 | No |
3 | SMSTORE2 | 174.19 | 28.1 | 6.194 | 0.161 | 16.653 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 20.953 | No |
4 | SMSTORE3 | 174.19 | 28.1 | 6.194 | 0.161 | 16.653 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 20.953 | No |
5 | SMSTORE4 | 174.19 | 28.1 | 6.194 | 0.161 | 16.653 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 20.953 | No |
6 | LGSTORE2 | 348.39 | 56.3 | 6.193 | 0.161 | 9.584 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 13.884 | No |
7 | SMSTORE5 | 174.19 | 28.1 | 6.194 | 0.161 | 9.699 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 13.999 | No |
8 | SMSTORE6 | 174.19 | 28.1 | 6.194 | 0.161 | 9.699 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 13.999 | No |
9 | SMSTORE7 | 174.19 | 28.1 | 6.194 | 0.161 | 9.699 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 13.999 | No |
10 | SMSTORE8 | 174.19 | 28.1 | 6.194 | 0.161 | 9.699 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 13.999 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | LGSTORE1 | TYPE1_OCC_SCH | LGSTORE1 | 348.39 | 56.3 | 56.3 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 56 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | SMSTORE1 | TYPE1_OCC_SCH | SMSTORE1 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | SMSTORE2 | TYPE2_OCC_SCH | SMSTORE2 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | SMSTORE3 | TYPE2_OCC_SCH | SMSTORE3 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | SMSTORE4 | TYPE2_OCC_SCH | SMSTORE4 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | LGSTORE2 | TYPE3_OCC_SCH | LGSTORE2 | 348.39 | 56.3 | 56.3 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 56 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | SMSTORE5 | TYPE3_OCC_SCH | SMSTORE5 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | SMSTORE6 | TYPE3_OCC_SCH | SMSTORE6 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | SMSTORE7 | TYPE3_OCC_SCH | SMSTORE7 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | SMSTORE8 | TYPE3_OCC_SCH | SMSTORE8 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | LGSTORE1_LIGHTS | LTG_SCH_BASE_LPD1 | LGSTORE1 | 348.39 | 56.3 | 3346.345 | 9.605 | 59.490 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3346.345 |
2 | LGSTORE1_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | LGSTORE1 | 348.39 | 56.3 | 1984.726 | 5.697 | 35.284 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1984.726 |
3 | SMSTORE1_LIGHTS | LTG_SCH_BASE_SMALL_LPD1 | SMSTORE1 | 174.19 | 28.1 | 1693.257 | 9.721 | 60.206 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1693.257 |
4 | SMSTORE1_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | SMSTORE1 | 174.19 | 28.1 | 1492.567 | 8.568 | 53.070 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1492.567 |
5 | SMSTORE2_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE2 | 174.19 | 28.1 | 1689.582 | 9.699 | 60.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1689.582 |
6 | SMSTORE2_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE2 | 174.19 | 28.1 | 1211.319 | 6.954 | 43.070 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1211.319 |
7 | SMSTORE3_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE3 | 174.19 | 28.1 | 1689.582 | 9.699 | 60.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1689.582 |
8 | SMSTORE3_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE3 | 174.19 | 28.1 | 1211.319 | 6.954 | 43.070 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1211.319 |
9 | SMSTORE4_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE4 | 174.19 | 28.1 | 1689.582 | 9.699 | 60.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1689.582 |
10 | SMSTORE4_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE4 | 174.19 | 28.1 | 1211.319 | 6.954 | 43.070 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1211.319 |
11 | LGSTORE2_LIGHTS | LTG_SCH_BASE_LPD2 | LGSTORE2 | 348.39 | 56.3 | 3338.998 | 9.584 | 59.359 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3338.998 |
12 | LGSTORE2_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | LGSTORE2 | 348.39 | 56.3 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
13 | SMSTORE5_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE5 | 174.19 | 28.1 | 1689.582 | 9.699 | 60.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1689.582 |
14 | SMSTORE5_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE5 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
15 | SMSTORE6_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE6 | 174.19 | 28.1 | 1689.582 | 9.699 | 60.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1689.582 |
16 | SMSTORE6_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE6 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
17 | SMSTORE7_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE7 | 174.19 | 28.1 | 1689.582 | 9.699 | 60.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1689.582 |
18 | SMSTORE7_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE7 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
19 | SMSTORE8_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE8 | 174.19 | 28.1 | 1689.582 | 9.699 | 60.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1689.582 |
20 | SMSTORE8_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE8 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LGSTORE1_MISCPLUG_EQUIP | TYPE1_EQUIP_SCH | LGSTORE1 | 348.39 | 56.3 | 1498.062 | 4.300 | 26.632 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1498.062 |
2 | SMSTORE1_MISCPLUG_EQUIP | TYPE1_EQUIP_SCH | SMSTORE1 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
3 | SMSTORE2_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE2 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
4 | SMSTORE3_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE3 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
5 | SMSTORE4_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE4 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
6 | LGSTORE2_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | LGSTORE2 | 348.39 | 56.3 | 1498.062 | 4.300 | 26.632 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1498.062 |
7 | SMSTORE5_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE5 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
8 | SMSTORE6_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE6 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
9 | SMSTORE7_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE7 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
10 | SMSTORE8_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE8 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.2284 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
5 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 0.7374 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
6 | LGSTORE1_FLOOR_FFACTOR | 36 | 2 | 7 | 0.167 | 0.1995 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
7 | SMSTORE1_FLOOR_FFACTOR | 37 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
8 | SMSTORE2_FLOOR_FFACTOR | 38 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | SMSTORE3_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
10 | SMSTORE4_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
11 | LGSTORE2_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | SMSTORE5_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | SMSTORE6_FLOOR_FFACTOR | 43 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | SMSTORE7_FLOOR_FFACTOR | 44 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | SMSTORE8_FLOOR_FFACTOR | 45 | 2 | 7 | 0.167 | 0.2888 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
6 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
7 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
8 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
10 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.122 |
11 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
12 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.937 |
13 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
14 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
15 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
16 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
17 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
18 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
19 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
20 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
21 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
22 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
23 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
24 | ~FC_Insulation_7 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_8 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_9 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_10 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.386 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
14 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
15 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
16 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
17 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
18 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
19 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
20 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
21 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
22 | 7 | -0.30765797E-12 | 0.12488460E-14 | -0.98016509E-13 | 0.16213517E-15 |
23 | 6 | 0.29136061E-07 | 0.20843390E-09 | 0.66705746E-08 | -0.13769473E-12 |
24 | 5 | -0.19246395E-03 | 0.17782628E-05 | -0.98963596E-04 | 0.65927994E-08 |
25 | 4 | 0.29490032 | 0.86304157E-03 | 0.10067388 | -0.33959898E-04 |
26 | 3 | -7.3208521 | 0.26669396E-01 | -2.3550924 | 0.29276239E-01 |
27 | 2 | 41.050957 | 0.94592451E-01 | 15.331444 | -0.33534308 |
28 | 1 | -80.683573 | 0.42595651E-01 | -29.201163 | 1.0815555 |
29 | 0 | 46.824338 | 0.85510937E-03 | 16.289814 | |
30 | 7 | -0.21163652E-08 | -0.68723841E-15 | 0.43910983E-14 | -0.57684426E-16 |
31 | 6 | 0.56109385E-05 | 0.38186281E-08 | 0.31898696E-02 | -0.26759299E-04 |
32 | 5 | -0.40164657E-03 | 0.22608617E-05 | -0.22372456 | 0.19561502E-02 |
33 | 4 | 0.92272104E-02 | 0.10289840E-03 | 4.8295456 | -0.45264980E-01 |
34 | 3 | -0.80993241E-01 | 0.81813938E-03 | -38.021416 | 0.39865375 |
35 | 2 | 0.28754352 | 0.13608947E-02 | 116.48395 | -1.4179393 |
36 | 1 | -0.41499682 | 0.41453381E-03 | -143.90731 | 2.0490399 |
37 | 0 | 0.20232414 | 0.10048102E-04 | 60.838472 | |
38 | 7 | -0.37862368E-08 | -0.38757603E-14 | 0.11479940E-14 | -0.41635801E-16 |
39 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
40 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
41 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
42 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
43 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
44 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
45 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
46 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479937E-14 | -0.41635796E-16 |
47 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
48 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
49 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
50 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
51 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
52 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
53 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
54 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479940E-14 | -0.41635801E-16 |
55 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
56 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
57 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
58 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
59 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
60 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
61 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
62 | 7 | -0.37862368E-08 | -0.38757603E-14 | 0.11479940E-14 | -0.41635801E-16 |
63 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
64 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
65 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
66 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
67 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
68 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
69 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
70 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479937E-14 | -0.41635796E-16 |
71 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
72 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
73 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
74 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
75 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
76 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
77 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
78 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479937E-14 | -0.41635796E-16 |
79 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
80 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
81 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
82 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
83 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
84 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
85 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
86 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479940E-14 | -0.41635801E-16 |
87 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
88 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
89 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
90 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
91 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
92 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
93 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
94 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479936E-14 | -0.41635794E-16 |
95 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
96 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
97 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
98 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
99 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
100 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
101 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
102 | 7 | -0.14484255E-08 | -0.22640907E-15 | 0.11860658E-13 | -0.17473455E-15 |
103 | 6 | 0.80640390E-05 | 0.55493782E-08 | 0.31828288E-02 | -0.26700235E-04 |
104 | 5 | -0.58275339E-03 | 0.32892043E-05 | -0.22332434 | 0.19526176E-02 |
105 | 4 | 0.13421983E-01 | 0.14977251E-03 | 4.8228790 | -0.45200897E-01 |
106 | 3 | -0.11791368 | 0.11914425E-02 | -37.983753 | 0.39823745 |
107 | 2 | 0.41875064 | 0.19825898E-02 | 116.41064 | -1.4169588 |
108 | 1 | -0.60444169 | 0.60433957E-03 | -143.86415 | 2.0483306 |
109 | 0 | 0.29470347 | 0.14596444E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.453_SHGC_0.25 | 35 | 1 | VerySmooth | 2.574 | 2.574 | 1.000 | 0.251 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 2.62916E-002 | 0.16139 | 0.61691 | 0.61691 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 0.12096 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | GAS TANK1 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
2 | WaterHeater:Mixed | GAS TANK2 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
3 | WaterHeater:Mixed | GAS TANK3 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
4 | WaterHeater:Mixed | GAS TANK4 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
5 | WaterHeater:Mixed | GAS TANK5 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
6 | WaterHeater:Mixed | GAS TANK6 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
7 | WaterHeater:Mixed | GAS TANK7 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | LGSTORE1_WALL_2 | 0 | 118.41 | 56.08 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
2 | LGSTORE1_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
3 | LGSTORE1_WALL_3_DOOR_1 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
4 | LGSTORE1_WALL_3_DOOR_2 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
5 | LGSTORE1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
6 | LGSTORE1_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
7 | LGSTORE1_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
8 | LGSTORE1_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
9 | LGSTORE1_WALL_1_WINDOW_3 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
10 | LGSTORE1_WALL_1_WINDOW_4 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
11 | LGSTORE1_WALL_1_DOOR_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 1 | No | No |
12 | LGSTORE1_WALL_1_DOOR_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 1 | No | No |
13 | LGSTORE1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
14 | LGSTORE1_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
15 | LGSTORE1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
16 | SMSTORE1_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
17 | SMSTORE1_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
18 | SMSTORE1_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
19 | SMSTORE1_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
20 | SMSTORE1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
21 | SMSTORE1_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
22 | SMSTORE1_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
23 | SMSTORE1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
24 | SMSTORE1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
25 | SMSTORE1_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
26 | SMSTORE1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
27 | SMSTORE2_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
28 | SMSTORE2_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
29 | SMSTORE2_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
30 | SMSTORE2_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
31 | SMSTORE2_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
32 | SMSTORE2_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
33 | SMSTORE2_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
34 | SMSTORE2_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
35 | SMSTORE2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
36 | SMSTORE2_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
37 | SMSTORE2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
38 | SMSTORE3_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
39 | SMSTORE3_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
40 | SMSTORE3_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
41 | SMSTORE3_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
42 | SMSTORE3_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
43 | SMSTORE3_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
44 | SMSTORE3_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
45 | SMSTORE3_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
46 | SMSTORE3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
47 | SMSTORE3_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
48 | SMSTORE3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
49 | SMSTORE4_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
50 | SMSTORE4_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
51 | SMSTORE4_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
52 | SMSTORE4_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
53 | SMSTORE4_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
54 | SMSTORE4_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 3 | No | No |
55 | SMSTORE4_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
56 | SMSTORE4_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
57 | SMSTORE4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
58 | SMSTORE4_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
59 | SMSTORE4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
60 | LGSTORE2_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
61 | LGSTORE2_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 4 | No | No |
62 | LGSTORE2_WALL_3_DOOR_1 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
63 | LGSTORE2_WALL_3_DOOR_2 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
64 | LGSTORE2_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
65 | LGSTORE2_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 4 | No | No |
66 | LGSTORE2_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
67 | LGSTORE2_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
68 | LGSTORE2_WALL_1_WINDOW_3 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
69 | LGSTORE2_WALL_1_WINDOW_4 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
70 | LGSTORE2_WALL_1_DOOR_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
71 | LGSTORE2_WALL_1_DOOR_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
72 | LGSTORE2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
73 | LGSTORE2_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
74 | LGSTORE2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
75 | SMSTORE5_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
76 | SMSTORE5_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
77 | SMSTORE5_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
78 | SMSTORE5_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
79 | SMSTORE5_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
80 | SMSTORE5_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
81 | SMSTORE5_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
82 | SMSTORE5_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
83 | SMSTORE5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
84 | SMSTORE5_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
85 | SMSTORE5_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
86 | SMSTORE6_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
87 | SMSTORE6_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
88 | SMSTORE6_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
89 | SMSTORE6_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
90 | SMSTORE6_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
91 | SMSTORE6_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
92 | SMSTORE6_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
93 | SMSTORE6_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
94 | SMSTORE6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
95 | SMSTORE6_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
96 | SMSTORE6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
97 | SMSTORE7_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
98 | SMSTORE7_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
99 | SMSTORE7_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
100 | SMSTORE7_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
101 | SMSTORE7_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
102 | SMSTORE7_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 3 | No | No |
103 | SMSTORE7_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
104 | SMSTORE7_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
105 | SMSTORE7_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
106 | SMSTORE7_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
107 | SMSTORE7_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
108 | SMSTORE8_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 4 | No | No |
109 | SMSTORE8_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 2 | No | No |
110 | SMSTORE8_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 2 | No | No |
111 | SMSTORE8_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 1 | No | No |
112 | SMSTORE8_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
113 | SMSTORE8_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 3 | No | No |
114 | SMSTORE8_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
115 | SMSTORE8_WALL_4 | 0 | 118.41 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 3 | No | No |
116 | SMSTORE8_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
117 | SMSTORE8_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
118 | SMSTORE8_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | LGSTORE1_INFILTRATION | TYPE1_INFIL_SCH | LGSTORE1 | 348.39 | 56.3 | 0.157 | 4.517E-004 | 2.488E-004 | 0.314 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | LGSTORE1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LGSTORE1 | 348.39 | 56.3 | 0.389 | 1.116E-003 | 6.149E-004 | 0.776 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | SMSTORE1_INFILTRATION | TYPE1_INFIL_SCH | SMSTORE1 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | SMSTORE1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE1 | 174.19 | 28.1 | 0.222 | 1.276E-003 | 8.648E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | SMSTORE2_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE2 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | SMSTORE2_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE2 | 174.19 | 28.1 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | SMSTORE3_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE3 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | SMSTORE3_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE3 | 174.19 | 28.1 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | SMSTORE4_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE4 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | SMSTORE4_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE4 | 174.19 | 28.1 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | LGSTORE2_INFILTRATION | TYPE3_INFIL_SCH | LGSTORE2 | 348.39 | 56.3 | 8.993E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | LGSTORE2_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LGSTORE2 | 348.39 | 56.3 | 0.389 | 1.116E-003 | 7.565E-004 | 0.776 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | SMSTORE5_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE5 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | SMSTORE5_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE5 | 174.19 | 28.1 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | SMSTORE6_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE6 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | SMSTORE6_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE6 | 174.19 | 28.1 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | SMSTORE7_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE7 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
18 | SMSTORE7_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE7 | 174.19 | 28.1 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | SMSTORE8_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE8 | 174.19 | 28.1 | 0.112 | 6.453E-004 | 2.994E-004 | 0.448 | 0.000 | 0.000 | 0.224 | 0.000 |
20 | SMSTORE8_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE8 | 174.19 | 28.1 | 0.222 | 1.276E-003 | 5.921E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | LGSTORE1 | Mixing/Well-Stirred |
2 | SMSTORE1 | Mixing/Well-Stirred |
3 | SMSTORE2 | Mixing/Well-Stirred |
4 | SMSTORE3 | Mixing/Well-Stirred |
5 | SMSTORE4 | Mixing/Well-Stirred |
6 | LGSTORE2 | Mixing/Well-Stirred |
7 | SMSTORE5 | Mixing/Well-Stirred |
8 | SMSTORE6 | Mixing/Well-Stirred |
9 | SMSTORE7 | Mixing/Well-Stirred |
10 | SMSTORE8 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone LGSTORE1 | 1.2000 |
3 | Zone SMSTORE1 | 1.2000 |
4 | Zone SMSTORE2 | 1.2000 |
5 | Zone SMSTORE3 | 1.2000 |
6 | Zone SMSTORE4 | 1.2000 |
7 | Zone LGSTORE2 | 1.2000 |
8 | Zone SMSTORE5 | 1.2000 |
9 | Zone SMSTORE6 | 1.2000 |
10 | Zone SMSTORE7 | 1.2000 |
11 | Zone SMSTORE8 | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone LGSTORE1 | 1.2000 |
3 | Zone SMSTORE1 | 1.2000 |
4 | Zone SMSTORE2 | 1.2000 |
5 | Zone SMSTORE3 | 1.2000 |
6 | Zone SMSTORE4 | 1.2000 |
7 | Zone LGSTORE2 | 1.2000 |
8 | Zone SMSTORE5 | 1.2000 |
9 | Zone SMSTORE6 | 1.2000 |
10 | Zone SMSTORE7 | 1.2000 |
11 | Zone SMSTORE8 | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | LGSTORE1 | Cooling | 24495.91461 | 29395.09753 | 1.79998 | 2.15997 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 33.90000 | 1.65364E-002 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
2 | LGSTORE1 | Heating | 15959.44532 | 19151.33438 | 0.68856 | 0.82627 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 4.60000 | 5.25715E-003 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
3 | SMSTORE1 | Cooling | 12928.86426 | 15514.63712 | 0.95003 | 1.14004 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 33.90000 | 1.65364E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
4 | SMSTORE1 | Heating | 7900.63668 | 9480.76401 | 0.34087 | 0.40904 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 4.60000 | 5.25715E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
5 | SMSTORE2 | Cooling | 12957.56478 | 15549.07774 | 0.95214 | 1.14257 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 33.83417 | 1.65363E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
6 | SMSTORE2 | Heating | 7962.98903 | 9555.58683 | 0.34356 | 0.41227 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 4.60000 | 5.25715E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
7 | SMSTORE3 | Cooling | 12994.58043 | 15593.49651 | 0.95486 | 1.14583 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 33.83417 | 1.65363E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
8 | SMSTORE3 | Heating | 8028.92617 | 9634.71140 | 0.34640 | 0.41568 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 4.60000 | 5.25715E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
9 | SMSTORE4 | Cooling | 12882.60340 | 15459.12408 | 0.94663 | 1.13596 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 33.83417 | 1.65363E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
10 | SMSTORE4 | Heating | 8172.01705 | 9806.42046 | 0.35257 | 0.42309 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 4.60000 | 5.25715E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
11 | LGSTORE2 | Cooling | 22569.04715 | 27082.85658 | 1.65834 | 1.99001 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 33.83417 | 1.65363E-002 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
12 | LGSTORE2 | Heating | 15376.62956 | 18451.95547 | 0.66342 | 0.79610 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 4.60000 | 5.25715E-003 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
13 | SMSTORE5 | Cooling | 11844.30901 | 14213.17081 | 0.87033 | 1.04440 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 33.83417 | 1.65363E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
14 | SMSTORE5 | Heating | 8367.35165 | 10040.82198 | 0.36100 | 0.43320 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 4.60000 | 5.25715E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
15 | SMSTORE6 | Cooling | 11794.40592 | 14153.28711 | 0.86666 | 1.04000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 33.83417 | 1.65363E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
16 | SMSTORE6 | Heating | 8373.14131 | 10047.76957 | 0.36125 | 0.43350 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 4.60000 | 5.25715E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
17 | SMSTORE7 | Cooling | 11831.15103 | 14197.38123 | 0.86936 | 1.04324 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 33.83417 | 1.65363E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
18 | SMSTORE7 | Heating | 8619.15634 | 10342.98761 | 0.37187 | 0.44624 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 4.60000 | 5.25715E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
19 | SMSTORE8 | Cooling | 13635.77237 | 16362.92685 | 1.00179 | 1.20215 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | 33.50500 | 1.65356E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
20 | SMSTORE8 | Heating | 10154.70856 | 12185.65028 | 0.43811 | 0.52573 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 4.60000 | 5.25715E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC_1:1 | Cooling | Sensible | 33924.21 | 2.15997 | 2.15997 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
2 | PSZ-AC_1:1 | Heating | Sensible | 27084.92 | 0.82627 | 0.82627 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
3 | PSZ-AC_2:2 | Cooling | Sensible | 17766.60 | 1.14004 | 1.14004 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
4 | PSZ-AC_2:2 | Heating | Sensible | 13448.93 | 0.40904 | 0.40904 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
5 | PSZ-AC_3:3 | Cooling | Sensible | 17798.31 | 1.14257 | 1.14257 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
6 | PSZ-AC_3:3 | Heating | Sensible | 13522.66 | 0.41227 | 0.41227 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
7 | PSZ-AC_4:4 | Cooling | Sensible | 17841.29 | 1.14583 | 1.14583 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
8 | PSZ-AC_4:4 | Heating | Sensible | 13600.63 | 0.41568 | 0.41568 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
9 | PSZ-AC_5:5 | Cooling | Sensible | 17709.30 | 1.13596 | 1.13596 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
10 | PSZ-AC_5:5 | Heating | Sensible | 13769.84 | 0.42309 | 0.42309 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
11 | PSZ-AC_6:6 | Cooling | Sensible | 31642.81 | 1.99001 | 1.99001 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
12 | PSZ-AC_6:6 | Heating | Sensible | 26395.78 | 0.79610 | 0.79610 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
13 | PSZ-AC_7:7 | Cooling | Sensible | 16481.89 | 1.04440 | 1.04440 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
14 | PSZ-AC_7:7 | Heating | Sensible | 14000.83 | 0.43320 | 0.43320 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
15 | PSZ-AC_8:8 | Cooling | Sensible | 16422.85 | 1.04000 | 1.04000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
16 | PSZ-AC_8:8 | Heating | Sensible | 14007.67 | 0.43350 | 0.43350 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
17 | PSZ-AC_9:9 | Cooling | Sensible | 16464.94 | 1.04324 | 1.04324 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
18 | PSZ-AC_9:9 | Heating | Sensible | 14298.59 | 0.44624 | 0.44624 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
19 | PSZ-AC_10:10 | Cooling | Sensible | 18503.00 | 1.20215 | 1.20215 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
20 | PSZ-AC_10:10 | Heating | Sensible | 16114.36 | 0.52573 | 0.52573 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | LGSTORE1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.15997 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.14004 |
3 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.14257 |
4 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.14583 |
5 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE4 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.13596 |
6 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | LGSTORE2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.99001 |
7 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE5 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.04440 |
8 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.04000 |
9 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE7 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.04324 |
10 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE8 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.20215 |
11 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.15997 |
12 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.15997 |
13 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.15997 |
14 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 2.15997 |
15 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.15997 |
16 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Main Design Air Flow Rate [m3/s] | 2.15997 |
17 | AirLoopHVAC | PSZ-AC_1:1 | User Heating Air Flow Ratio [] | 1.00000 |
18 | AirLoopHVAC | PSZ-AC_1:1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
19 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.14004 |
20 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.14004 |
21 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.14004 |
22 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.14004 |
23 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.14004 |
24 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Main Design Air Flow Rate [m3/s] | 1.14004 |
25 | AirLoopHVAC | PSZ-AC_2:2 | User Heating Air Flow Ratio [] | 1.00000 |
26 | AirLoopHVAC | PSZ-AC_2:2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
27 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.14257 |
28 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.14257 |
29 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.14257 |
30 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.14257 |
31 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.14257 |
32 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Main Design Air Flow Rate [m3/s] | 1.14257 |
33 | AirLoopHVAC | PSZ-AC_3:3 | User Heating Air Flow Ratio [] | 1.00000 |
34 | AirLoopHVAC | PSZ-AC_3:3 | Calculated Heating Air Flow Ratio [] | 1.00000 |
35 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.14583 |
36 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.14583 |
37 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.14583 |
38 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.14583 |
39 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.14583 |
40 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Main Design Air Flow Rate [m3/s] | 1.14583 |
41 | AirLoopHVAC | PSZ-AC_4:4 | User Heating Air Flow Ratio [] | 1.00000 |
42 | AirLoopHVAC | PSZ-AC_4:4 | Calculated Heating Air Flow Ratio [] | 1.00000 |
43 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.13596 |
44 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.13596 |
45 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.13596 |
46 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.13596 |
47 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.13596 |
48 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Main Design Air Flow Rate [m3/s] | 1.13596 |
49 | AirLoopHVAC | PSZ-AC_5:5 | User Heating Air Flow Ratio [] | 1.00000 |
50 | AirLoopHVAC | PSZ-AC_5:5 | Calculated Heating Air Flow Ratio [] | 1.00000 |
51 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.99001 |
52 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.99001 |
53 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.99001 |
54 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.99001 |
55 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.99001 |
56 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Main Design Air Flow Rate [m3/s] | 1.99001 |
57 | AirLoopHVAC | PSZ-AC_6:6 | User Heating Air Flow Ratio [] | 1.00000 |
58 | AirLoopHVAC | PSZ-AC_6:6 | Calculated Heating Air Flow Ratio [] | 1.00000 |
59 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.04440 |
60 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.04440 |
61 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.04440 |
62 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.04440 |
63 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.04440 |
64 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Main Design Air Flow Rate [m3/s] | 1.04440 |
65 | AirLoopHVAC | PSZ-AC_7:7 | User Heating Air Flow Ratio [] | 1.00000 |
66 | AirLoopHVAC | PSZ-AC_7:7 | Calculated Heating Air Flow Ratio [] | 1.00000 |
67 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.04000 |
68 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.04000 |
69 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.04000 |
70 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.04000 |
71 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.04000 |
72 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Main Design Air Flow Rate [m3/s] | 1.04000 |
73 | AirLoopHVAC | PSZ-AC_8:8 | User Heating Air Flow Ratio [] | 1.00000 |
74 | AirLoopHVAC | PSZ-AC_8:8 | Calculated Heating Air Flow Ratio [] | 1.00000 |
75 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.04324 |
76 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.04324 |
77 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.04324 |
78 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.04324 |
79 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.04324 |
80 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Main Design Air Flow Rate [m3/s] | 1.04324 |
81 | AirLoopHVAC | PSZ-AC_9:9 | User Heating Air Flow Ratio [] | 1.00000 |
82 | AirLoopHVAC | PSZ-AC_9:9 | Calculated Heating Air Flow Ratio [] | 1.00000 |
83 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.20215 |
84 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.20215 |
85 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.20215 |
86 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.20215 |
87 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.20215 |
88 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Main Design Air Flow Rate [m3/s] | 1.20215 |
89 | AirLoopHVAC | PSZ-AC_10:10 | User Heating Air Flow Ratio [] | 1.00000 |
90 | AirLoopHVAC | PSZ-AC_10:10 | Calculated Heating Air Flow Ratio [] | 1.00000 |
91 | AirLoopHVAC | PSZ-AC_1:1 | Design Supply Air Flow Rate [m3/s] | 2.15997 |
92 | AirLoopHVAC | PSZ-AC_2:2 | Design Supply Air Flow Rate [m3/s] | 1.14004 |
93 | AirLoopHVAC | PSZ-AC_3:3 | Design Supply Air Flow Rate [m3/s] | 1.14257 |
94 | AirLoopHVAC | PSZ-AC_4:4 | Design Supply Air Flow Rate [m3/s] | 1.14583 |
95 | AirLoopHVAC | PSZ-AC_5:5 | Design Supply Air Flow Rate [m3/s] | 1.13596 |
96 | AirLoopHVAC | PSZ-AC_6:6 | Design Supply Air Flow Rate [m3/s] | 1.99001 |
97 | AirLoopHVAC | PSZ-AC_7:7 | Design Supply Air Flow Rate [m3/s] | 1.04440 |
98 | AirLoopHVAC | PSZ-AC_8:8 | Design Supply Air Flow Rate [m3/s] | 1.04000 |
99 | AirLoopHVAC | PSZ-AC_9:9 | Design Supply Air Flow Rate [m3/s] | 1.04324 |
100 | AirLoopHVAC | PSZ-AC_10:10 | Design Supply Air Flow Rate [m3/s] | 1.20215 |
101 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.15997 |
102 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41148 |
103 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.15997 |
104 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 2311.27060 |
105 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.15997 |
106 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.15997 |
107 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.15997 |
108 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.42558 |
109 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.15997 |
110 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.07999 |
111 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.43998 |
112 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 53637.21000 |
113 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 26818.60500 |
114 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
115 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
116 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 53637.21000 |
117 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 57547.23218 |
118 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
119 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
120 | Coil:Heating:Fuel | PSZ-AC_1:1 HEATING COIL | Design Size Nominal Capacity [W] | 57547.23218 |
121 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.14004 |
122 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
123 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.14004 |
124 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1262.20701 |
125 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.14004 |
126 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.14004 |
127 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.14004 |
128 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.75243 |
129 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.14004 |
130 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.57002 |
131 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.76003 |
132 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 28309.95000 |
133 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 14154.97500 |
134 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
135 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
136 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 28309.95000 |
137 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 30145.38556 |
138 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
139 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
140 | Coil:Heating:Fuel | PSZ-AC_2:2 HEATING COIL | Design Size Nominal Capacity [W] | 30145.38556 |
141 | Controller:OutdoorAir | PSZ-AC_3:3_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.14257 |
142 | Controller:OutdoorAir | PSZ-AC_3:3_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
143 | Fan:SystemModel | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.14257 |
144 | Fan:SystemModel | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1265.00416 |
145 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.14257 |
146 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.14257 |
147 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.14257 |
148 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.75409 |
149 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.14257 |
150 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.57128 |
151 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.76171 |
152 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 28372.68000 |
153 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 14186.34000 |
154 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
155 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
156 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 28372.68000 |
157 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 30203.09395 |
158 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
159 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
160 | Coil:Heating:Fuel | PSZ-AC_3:3 HEATING COIL | Design Size Nominal Capacity [W] | 30203.09395 |
161 | Controller:OutdoorAir | PSZ-AC_4:4_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.14583 |
162 | Controller:OutdoorAir | PSZ-AC_4:4_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
163 | Fan:SystemModel | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.14583 |
164 | Fan:SystemModel | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1268.61799 |
165 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.14583 |
166 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.14583 |
167 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.14583 |
168 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.75625 |
169 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.14583 |
170 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.57292 |
171 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.76389 |
172 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 28453.74000 |
173 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 14226.87000 |
174 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
175 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
176 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 28453.74000 |
177 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 30277.64605 |
178 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
179 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
180 | Coil:Heating:Fuel | PSZ-AC_4:4 HEATING COIL | Design Size Nominal Capacity [W] | 30277.64605 |
181 | Controller:OutdoorAir | PSZ-AC_5:5_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.13596 |
182 | Controller:OutdoorAir | PSZ-AC_5:5_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
183 | Fan:SystemModel | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.13596 |
184 | Fan:SystemModel | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1257.68516 |
185 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.13596 |
186 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.13596 |
187 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.13596 |
188 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.74973 |
189 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.13596 |
190 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.56798 |
191 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.75731 |
192 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 28208.53000 |
193 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 14104.26500 |
194 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
195 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
196 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 28208.53000 |
197 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 30052.09601 |
198 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
199 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
200 | Coil:Heating:Fuel | PSZ-AC_5:5 HEATING COIL | Design Size Nominal Capacity [W] | 30052.09601 |
201 | Controller:OutdoorAir | PSZ-AC_6:6_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.99001 |
202 | Controller:OutdoorAir | PSZ-AC_6:6_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41148 |
203 | Fan:SystemModel | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.99001 |
204 | Fan:SystemModel | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 2129.40904 |
205 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.99001 |
206 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.99001 |
207 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.99001 |
208 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.31341 |
209 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.99001 |
210 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.99501 |
211 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.32667 |
212 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 49416.79000 |
213 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 24708.39500 |
214 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
215 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
216 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 49416.79000 |
217 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 53665.14708 |
218 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
219 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
220 | Coil:Heating:Fuel | PSZ-AC_6:6 HEATING COIL | Design Size Nominal Capacity [W] | 53665.14708 |
221 | Controller:OutdoorAir | PSZ-AC_7:7_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.04440 |
222 | Controller:OutdoorAir | PSZ-AC_7:7_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
223 | Fan:SystemModel | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.04440 |
224 | Fan:SystemModel | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1156.31414 |
225 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.04440 |
226 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.04440 |
227 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.04440 |
228 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.68930 |
229 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.04440 |
230 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.52220 |
231 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.69627 |
232 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 25934.88000 |
233 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 12967.44000 |
234 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
235 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
236 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 25934.88000 |
237 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 27960.83881 |
238 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
239 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
240 | Coil:Heating:Fuel | PSZ-AC_7:7 HEATING COIL | Design Size Nominal Capacity [W] | 27960.83881 |
241 | Controller:OutdoorAir | PSZ-AC_8:8_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.04000 |
242 | Controller:OutdoorAir | PSZ-AC_8:8_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
243 | Fan:SystemModel | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.04000 |
244 | Fan:SystemModel | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1151.44203 |
245 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.04000 |
246 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.04000 |
247 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.04000 |
248 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.68640 |
249 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.04000 |
250 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.52000 |
251 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.69333 |
252 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 25825.61000 |
253 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 12912.80500 |
254 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
255 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
256 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 25825.61000 |
257 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 27860.32660 |
258 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
259 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
260 | Coil:Heating:Fuel | PSZ-AC_8:8 HEATING COIL | Design Size Nominal Capacity [W] | 27860.32660 |
261 | Controller:OutdoorAir | PSZ-AC_9:9_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.04324 |
262 | Controller:OutdoorAir | PSZ-AC_9:9_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
263 | Fan:SystemModel | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.04324 |
264 | Fan:SystemModel | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1155.02896 |
265 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.04324 |
266 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.04324 |
267 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.04324 |
268 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.68854 |
269 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.04324 |
270 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.52162 |
271 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.69549 |
272 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 25906.06000 |
273 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 12953.03000 |
274 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
275 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
276 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 25906.06000 |
277 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 27934.31680 |
278 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
279 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
280 | Coil:Heating:Fuel | PSZ-AC_9:9 HEATING COIL | Design Size Nominal Capacity [W] | 27934.31680 |
281 | Controller:OutdoorAir | PSZ-AC_10:10_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.20215 |
282 | Controller:OutdoorAir | PSZ-AC_10:10_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
283 | Fan:SystemModel | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.20215 |
284 | Fan:SystemModel | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1330.97455 |
285 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.20215 |
286 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.20215 |
287 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.20215 |
288 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.79342 |
289 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.20215 |
290 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.60108 |
291 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.80143 |
292 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 29725.08000 |
293 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 14862.54000 |
294 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70313 |
295 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70313 |
296 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 29725.08000 |
297 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 31564.30184 |
298 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
299 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
300 | Coil:Heating:Fuel | PSZ-AC_10:10 HEATING COIL | Design Size Nominal Capacity [W] | 31564.30184 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | 51933.2 | 11.77 | 11.77 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | 27410.6 | 11.95 | 11.95 | |||
3 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | 27471.3 | 11.95 | 11.95 | |||
4 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | 27549.8 | 11.95 | 11.95 | |||
5 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | 27312.4 | 11.95 | 11.95 | |||
6 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | 47846.8 | 11.77 | 11.77 | |||
7 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | 25110.9 | 11.95 | 11.95 | |||
8 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | 25005.1 | 11.95 | 11.95 | |||
9 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | 25083.0 | 11.95 | 11.95 | |||
10 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | 28776.8 | 11.94 | 11.94 |
Zone Name | # Surfaces | |
1 | LGSTORE1 | 15 |
2 | SMSTORE1 | 11 |
3 | SMSTORE2 | 11 |
4 | SMSTORE3 | 11 |
5 | SMSTORE4 | 11 |
6 | LGSTORE2 | 15 |
7 | SMSTORE5 | 11 |
8 | SMSTORE6 | 11 |
9 | SMSTORE7 | 11 |
10 | SMSTORE8 | 11 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | LGSTORE1_WALL_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.737 | 0.664 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | LGSTORE1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.737 | 0.664 | 71.15 | 78.94 | 71.15 | 0.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | LGSTORE1_WALL_3_DOOR_1 | Door | LGSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
4 | LGSTORE1_WALL_3_DOOR_2 | Door | LGSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
5 | LGSTORE1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
6 | LGSTORE1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.737 | 0.664 | 58.18 | 78.94 | 58.18 | 180.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
7 | LGSTORE1_WALL_1_WINDOW_1 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.453_SHGC_0.25 | N/A | 2.574 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
8 | LGSTORE1_WALL_1_WINDOW_2 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.453_SHGC_0.25 | N/A | 2.574 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
9 | LGSTORE1_WALL_1_WINDOW_3 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.453_SHGC_0.25 | N/A | 2.574 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
10 | LGSTORE1_WALL_1_WINDOW_4 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.453_SHGC_0.25 | N/A | 2.574 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
11 | LGSTORE1_WALL_1_DOOR_1 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.453_SHGC_0.25 | N/A | 2.574 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
12 | LGSTORE1_WALL_1_DOOR_2 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.453_SHGC_0.25 | N/A | 2.574 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
13 | LGSTORE1_FLOOR | Floor | CTF - ConductionTransferFunction | LGSTORE1_FLOOR_FFACTOR | 0.199 | 0.190 | 348.39 | 348.39 | 348.39 | 270.00 | 180.00 | 22.86 | 15.24 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | LGSTORE1_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 348.39 | 348.39 | 348.39 | 270.00 | 0.00 | 22.86 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
15 | LGSTORE1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 696.77 | 696.77 | 696.77 | 0.00 | 90.00 | 696.77 | 1.00 | 0.00 | LGSTORE1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
16 | SMSTORE1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.737 | 0.664 | 29.09 | 39.47 | 29.09 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
17 | SMSTORE1_WALL_1_WINDOW_1 | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.453_SHGC_0.25 | N/A | 2.574 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
18 | SMSTORE1_WALL_1_WINDOW_2 | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.453_SHGC_0.25 | N/A | 2.574 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
19 | SMSTORE1_WALL_1_DOOR | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.453_SHGC_0.25 | N/A | 2.574 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
20 | SMSTORE1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | SMSTORE1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.737 | 0.664 | 35.57 | 39.47 | 35.57 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | SMSTORE1_WALL_3_DOOR | Door | SMSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
23 | SMSTORE1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE2_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | SMSTORE1_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE1_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | SMSTORE1_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
26 | SMSTORE1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
27 | SMSTORE2_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.737 | 0.664 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | SMSTORE2_WALL_1_WINDOW_1 | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.453_SHGC_0.25 | N/A | 2.574 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
29 | SMSTORE2_WALL_1_WINDOW_2 | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.453_SHGC_0.25 | N/A | 2.574 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
30 | SMSTORE2_WALL_1_DOOR | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.453_SHGC_0.25 | N/A | 2.574 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
31 | SMSTORE2_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | SMSTORE2_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.737 | 0.664 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | SMSTORE2_WALL_3_DOOR | Door | SMSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
34 | SMSTORE2_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE3_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | SMSTORE2_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE2_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | SMSTORE2_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | SMSTORE2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | SMSTORE3_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.737 | 0.664 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | SMSTORE3_WALL_1_WINDOW_1 | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.453_SHGC_0.25 | N/A | 2.574 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
40 | SMSTORE3_WALL_1_WINDOW_2 | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.453_SHGC_0.25 | N/A | 2.574 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
41 | SMSTORE3_WALL_1_DOOR | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.453_SHGC_0.25 | N/A | 2.574 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
42 | SMSTORE3_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE2_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | SMSTORE3_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.737 | 0.664 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | SMSTORE3_WALL_3_DOOR | Door | SMSTORE3_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
45 | SMSTORE3_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE4_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | SMSTORE3_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE3_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
47 | SMSTORE3_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
48 | SMSTORE3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
49 | SMSTORE4_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.737 | 0.664 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | SMSTORE4_WALL_1_WINDOW_1 | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.453_SHGC_0.25 | N/A | 2.574 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
51 | SMSTORE4_WALL_1_WINDOW_2 | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.453_SHGC_0.25 | N/A | 2.574 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
52 | SMSTORE4_WALL_1_DOOR | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.453_SHGC_0.25 | N/A | 2.574 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | SMSTORE4_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE3_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | SMSTORE4_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.737 | 0.664 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | SMSTORE4_WALL_3_DOOR | Door | SMSTORE4_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | SMSTORE4_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE2_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | SMSTORE4_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE4_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | SMSTORE4_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | SMSTORE4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | LGSTORE2_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE4_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | LGSTORE2_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.737 | 0.664 | 71.19 | 78.94 | 71.19 | 0.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
62 | LGSTORE2_WALL_3_DOOR_1 | Door | LGSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
63 | LGSTORE2_WALL_3_DOOR_2 | Door | LGSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
64 | LGSTORE2_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE5_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LGSTORE2_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.737 | 0.664 | 58.22 | 78.94 | 58.22 | 180.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
66 | LGSTORE2_WALL_1_WINDOW_1 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.453_SHGC_0.25 | N/A | 2.574 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | LGSTORE2_WALL_1_WINDOW_2 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.453_SHGC_0.25 | N/A | 2.574 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | LGSTORE2_WALL_1_WINDOW_3 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.453_SHGC_0.25 | N/A | 2.574 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | LGSTORE2_WALL_1_WINDOW_4 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.453_SHGC_0.25 | N/A | 2.574 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LGSTORE2_WALL_1_DOOR_1 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.453_SHGC_0.25 | N/A | 2.574 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
71 | LGSTORE2_WALL_1_DOOR_2 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.453_SHGC_0.25 | N/A | 2.574 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
72 | LGSTORE2_FLOOR | Floor | CTF - ConductionTransferFunction | LGSTORE2_FLOOR_FFACTOR | 0.112 | 0.109 | 348.39 | 348.39 | 348.39 | 270.00 | 180.00 | 22.86 | 15.24 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
73 | LGSTORE2_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 348.39 | 348.39 | 348.39 | 270.00 | 0.00 | 22.86 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
74 | LGSTORE2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 696.77 | 696.77 | 696.77 | 0.00 | 90.00 | 696.77 | 1.00 | 0.00 | LGSTORE2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
75 | SMSTORE5_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.737 | 0.664 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | SMSTORE5_WALL_1_WINDOW_1 | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.453_SHGC_0.25 | N/A | 2.574 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
77 | SMSTORE5_WALL_1_WINDOW_2 | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.453_SHGC_0.25 | N/A | 2.574 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | SMSTORE5_WALL_1_DOOR | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.453_SHGC_0.25 | N/A | 2.574 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
79 | SMSTORE5_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE2_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | SMSTORE5_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.737 | 0.664 | 35.59 | 39.47 | 35.59 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | SMSTORE5_WALL_3_DOOR | Door | SMSTORE5_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
82 | SMSTORE5_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE6_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
83 | SMSTORE5_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE5_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
84 | SMSTORE5_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
85 | SMSTORE5_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE5_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | SMSTORE6_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.737 | 0.664 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | SMSTORE6_WALL_1_WINDOW_1 | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.453_SHGC_0.25 | N/A | 2.574 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | SMSTORE6_WALL_1_WINDOW_2 | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.453_SHGC_0.25 | N/A | 2.574 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
89 | SMSTORE6_WALL_1_DOOR | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.453_SHGC_0.25 | N/A | 2.574 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | SMSTORE6_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE5_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | SMSTORE6_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.737 | 0.664 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | SMSTORE6_WALL_3_DOOR | Door | SMSTORE6_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
93 | SMSTORE6_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE7_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | SMSTORE6_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE6_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
95 | SMSTORE6_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
96 | SMSTORE6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
97 | SMSTORE7_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.737 | 0.664 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | SMSTORE7_WALL_1_WINDOW_1 | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.453_SHGC_0.25 | N/A | 2.574 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | SMSTORE7_WALL_1_WINDOW_2 | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.453_SHGC_0.25 | N/A | 2.574 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
100 | SMSTORE7_WALL_1_DOOR | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.453_SHGC_0.25 | N/A | 2.574 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
101 | SMSTORE7_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE6_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
102 | SMSTORE7_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.737 | 0.664 | 35.59 | 39.47 | 35.59 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | SMSTORE7_WALL_3_DOOR | Door | SMSTORE7_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
104 | SMSTORE7_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE8_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | SMSTORE7_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE7_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
106 | SMSTORE7_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
107 | SMSTORE7_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE7_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
108 | SMSTORE8_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.737 | 0.664 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | SMSTORE8_WALL_1_WINDOW_1 | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.453_SHGC_0.25 | N/A | 2.574 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
110 | SMSTORE8_WALL_1_WINDOW_2 | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.453_SHGC_0.25 | N/A | 2.574 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
111 | SMSTORE8_WALL_1_DOOR | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.453_SHGC_0.25 | N/A | 2.574 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
112 | SMSTORE8_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE7_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | SMSTORE8_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.737 | 0.664 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | SMSTORE8_WALL_3_DOOR | Door | SMSTORE8_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
115 | SMSTORE8_WALL_4 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.737 | 0.664 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | SMSTORE8_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE8_FLOOR_FFACTOR | 0.289 | 0.270 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | SMSTORE8_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | SMSTORE8_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE8_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | LGSTORE1 | RunPeriod: RUNPERIOD 1 | 1.6907118091E-002 | 6.8557174220E-002 | Pass | Pass | 3.3946914623E-002 | 8.9500281498E-002 | Pass | Pass |
2 | SMSTORE1 | RunPeriod: RUNPERIOD 1 | 2.3462355722E-002 | 0.1046860765 | Pass | Pass | 3.6179927277E-002 | 9.6117557542E-002 | Pass | Pass |
3 | SMSTORE2 | RunPeriod: RUNPERIOD 1 | 3.8440003079E-002 | 0.1289573173 | Pass | Pass | 0.1629798155 | 1.5172584536 | Pass | Pass |
4 | SMSTORE3 | RunPeriod: RUNPERIOD 1 | 3.8073577058E-002 | 0.1272060209 | Pass | Pass | 0.1648429123 | 1.5374910145 | Pass | Pass |
5 | SMSTORE4 | RunPeriod: RUNPERIOD 1 | 3.6255779910E-002 | 0.1174520321 | Pass | Pass | 0.1670247968 | 1.5637418049 | Pass | Pass |
6 | LGSTORE2 | RunPeriod: RUNPERIOD 1 | 3.3137080698E-002 | 9.8871093694E-002 | Pass | Pass | 0.1447537834 | 1.2244343889 | Pass | Pass |
7 | SMSTORE5 | RunPeriod: RUNPERIOD 1 | 3.2650116751E-002 | 9.5242803940E-002 | Pass | Pass | 0.1929926192 | 1.5883738717 | Pass | Pass |
8 | SMSTORE6 | RunPeriod: RUNPERIOD 1 | 3.2171921900E-002 | 9.2198350669E-002 | Pass | Pass | 0.2009104687 | 1.6142373885 | Pass | Pass |
9 | SMSTORE7 | RunPeriod: RUNPERIOD 1 | 3.0946938245E-002 | 8.4148844387E-002 | Pass | Pass | 0.3351386651 | 2.5102465582 | Pass | Pass |
10 | SMSTORE8 | RunPeriod: RUNPERIOD 1 | 3.1989065092E-002 | 8.0486541296E-002 | Pass | Pass | 0.2137199273 | 2.0699720028 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:30
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 3145.10 | -207.7 | 0.00 | -312.2 | 1805.16 | 4430.30 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:30
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 4.60 | 0.00 | 4.60 | Wetbulb [C] | 2.50 | 10.00 |
TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 33.90 | 7.90 | 25.10 | Wetbulb [C] | 3.10 | 270.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 66.00 | 12 | |||
Feb | 66.00 | 22 | |||
Mar | 126.00 | 32 | |||
Apr | 206.00 | 19 | |||
May | 144.00 | 46 | |||
Jun | 99.00 | 30 | |||
Jul | 192.00 | 52 | |||
Aug | 240.00 | 34 | |||
Sep | 310.00 | 44 | |||
Oct | 34.00 | 10 | |||
Nov | 63.00 | 12 | |||
Dec | 35.00 | 24 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:30
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_2 | NONRES_EXT_WALL_GRD | 0.30 | 0.664 | 0.737 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE1_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.664 | 0.737 | 78.94 | 71.15 | 0.00 | 90.00 | N |
LGSTORE1_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.664 | 0.737 | 78.94 | 58.18 | 180.00 | 90.00 | S |
LGSTORE1_FLOOR | LGSTORE1_FLOOR_FFACTOR | 1.00 | 0.193 | 0.199 | 348.39 | 348.39 | 270.00 | 180.00 | |
LGSTORE1_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 348.39 | 348.39 | 270.00 | 0.00 | |
SMSTORE1_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.664 | 0.737 | 39.47 | 29.09 | 180.00 | 90.00 | S |
SMSTORE1_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.664 | 0.737 | 39.47 | 35.57 | 0.00 | 90.00 | N |
SMSTORE1_FLOOR | SMSTORE1_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE1_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE2_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.664 | 0.737 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE2_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.664 | 0.737 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE2_FLOOR | SMSTORE2_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE2_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE3_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.664 | 0.737 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE3_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.664 | 0.737 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE3_FLOOR | SMSTORE3_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE3_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE4_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.664 | 0.737 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE4_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.664 | 0.737 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE4_FLOOR | SMSTORE4_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE4_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 | |
LGSTORE2_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.664 | 0.737 | 78.94 | 71.19 | 0.00 | 90.00 | N |
LGSTORE2_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.664 | 0.737 | 78.94 | 58.22 | 180.00 | 90.00 | S |
LGSTORE2_FLOOR | LGSTORE2_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 348.39 | 348.39 | 270.00 | 180.00 | |
LGSTORE2_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 348.39 | 348.39 | 270.00 | 0.00 | |
SMSTORE5_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.664 | 0.737 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE5_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.664 | 0.737 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE5_FLOOR | SMSTORE5_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE5_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE6_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.664 | 0.737 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE6_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.664 | 0.737 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE6_FLOOR | SMSTORE6_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE6_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE7_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.664 | 0.737 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE7_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.664 | 0.737 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE7_FLOOR | SMSTORE7_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE7_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE8_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.664 | 0.737 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE8_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.664 | 0.737 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE8_WALL_4 | NONRES_EXT_WALL_GRD | 0.30 | 0.664 | 0.737 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE8_FLOOR | SMSTORE8_FLOOR_FFACTOR | 1.00 | 0.276 | 0.289 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE8_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE1_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE2_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE2_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE3_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE3_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE4_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE4_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
LGSTORE2_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE2_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE5_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE5_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE6_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE6_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE7_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE7_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE8_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 696.77 | 0.00 | 90.00 | N | ||
SMSTORE1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
LGSTORE2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 696.77 | 0.00 | 90.00 | N | ||
SMSTORE5_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE7_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE8_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.453_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.574 | 0.251 | 0.276 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.453_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.574 | 0.251 | 0.276 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_3 | NONRESWINDOW_U_0.453_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.574 | 0.251 | 0.276 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_4 | NONRESWINDOW_U_0.453_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.574 | 0.251 | 0.276 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_DOOR_1 | NONRESWINDOW_U_0.453_SHGC_0.25 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.574 | 0.251 | 0.276 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_DOOR_2 | NONRESWINDOW_U_0.453_SHGC_0.25 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.574 | 0.251 | 0.276 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.453_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.574 | 0.251 | 0.276 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.453_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.574 | 0.251 | 0.276 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_DOOR | NONRESWINDOW_U_0.453_SHGC_0.25 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.574 | 0.251 | 0.276 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.453_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.574 | 0.251 | 0.276 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.453_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.574 | 0.251 | 0.276 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_DOOR | NONRESWINDOW_U_0.453_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.574 | 0.251 | 0.276 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.453_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.574 | 0.251 | 0.276 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.453_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.574 | 0.251 | 0.276 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_DOOR | NONRESWINDOW_U_0.453_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.574 | 0.251 | 0.276 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.453_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.574 | 0.251 | 0.276 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.453_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.574 | 0.251 | 0.276 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_DOOR | NONRESWINDOW_U_0.453_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.574 | 0.251 | 0.276 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.453_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.574 | 0.251 | 0.276 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.453_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.574 | 0.251 | 0.276 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_3 | NONRESWINDOW_U_0.453_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.574 | 0.251 | 0.276 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_4 | NONRESWINDOW_U_0.453_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.574 | 0.251 | 0.276 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_DOOR_1 | NONRESWINDOW_U_0.453_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.574 | 0.251 | 0.276 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_DOOR_2 | NONRESWINDOW_U_0.453_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.574 | 0.251 | 0.276 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.453_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.574 | 0.251 | 0.276 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.453_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.574 | 0.251 | 0.276 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_DOOR | NONRESWINDOW_U_0.453_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.574 | 0.251 | 0.276 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.453_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.574 | 0.251 | 0.276 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.453_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.574 | 0.251 | 0.276 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_DOOR | NONRESWINDOW_U_0.453_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.574 | 0.251 | 0.276 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.453_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.574 | 0.251 | 0.276 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.453_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.574 | 0.251 | 0.276 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_DOOR | NONRESWINDOW_U_0.453_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.574 | 0.251 | 0.276 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.453_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.574 | 0.251 | 0.276 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.453_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.574 | 0.251 | 0.276 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_DOOR | NONRESWINDOW_U_0.453_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.574 | 0.251 | 0.276 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
Total or Average | 124.40 | 2.574 | 0.251 | 0.276 | |||||||||||||||||
North Total or Average | 0.00 | - | - | - | |||||||||||||||||
Non-North Total or Average | 124.40 | 2.574 | 0.251 | 0.276 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
LGSTORE1_WALL_3_DOOR_1 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.90 | LGSTORE1_WALL_3 |
LGSTORE1_WALL_3_DOOR_2 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.90 | LGSTORE1_WALL_3 |
SMSTORE1_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.90 | SMSTORE1_WALL_3 |
SMSTORE2_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE2_WALL_3 |
SMSTORE3_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE3_WALL_3 |
SMSTORE4_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE4_WALL_3 |
LGSTORE2_WALL_3_DOOR_1 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | LGSTORE2_WALL_3 |
LGSTORE2_WALL_3_DOOR_2 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | LGSTORE2_WALL_3 |
SMSTORE5_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE5_WALL_3 |
SMSTORE6_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE6_WALL_3 |
SMSTORE7_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE7_WALL_3 |
SMSTORE8_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE8_WALL_3 |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:30
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
LGSTORE1_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_4 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_DOOR_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_DOOR_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_4 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_DOOR_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_DOOR_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:30
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
LGSTORE1_LIGHTS | LGSTORE1 | LGSTORE1 | GENERAL | 9.6053 | 348.39 | 3346.35 | LightsWired | LTG_SCH_BASE_LPD1 | 83.91 | 168.00 | 82.62 | 0.0000 | Y | 51.90 |
LGSTORE1_LIGHTS_ALLOWANCE | LGSTORE1 | LGSTORE1 | GENERAL | 5.6969 | 348.39 | 1984.73 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | 97.50 | 112.00 | 94.53 | 0.0000 | Y | 35.22 |
SMSTORE1_LIGHTS | SMSTORE1 | SMSTORE1 | GENERAL | 9.7206 | 174.19 | 1693.26 | LightsWired | LTG_SCH_BASE_SMALL_LPD1 | 85.41 | 168.00 | 84.05 | 0.0000 | Y | 26.72 |
SMSTORE1_LIGHTS_ALLOWANCE | SMSTORE1 | SMSTORE1 | GENERAL | 8.5685 | 174.19 | 1492.57 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | 97.50 | 112.00 | 94.53 | 0.0000 | Y | 26.49 |
SMSTORE2_LIGHTS | SMSTORE2 | SMSTORE2 | GENERAL | 9.6995 | 174.19 | 1689.58 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 68.73 | 168.00 | 65.95 | 0.0000 | Y | 20.92 |
SMSTORE2_LIGHTS_ALLOWANCE | SMSTORE2 | SMSTORE2 | GENERAL | 6.9539 | 174.19 | 1211.32 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 84.29 | 73.25 | 0.0000 | Y | 16.66 |
SMSTORE3_LIGHTS | SMSTORE3 | SMSTORE3 | GENERAL | 9.6995 | 174.19 | 1689.58 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 68.73 | 168.00 | 65.95 | 0.0000 | Y | 20.92 |
SMSTORE3_LIGHTS_ALLOWANCE | SMSTORE3 | SMSTORE3 | GENERAL | 6.9539 | 174.19 | 1211.32 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 84.29 | 73.25 | 0.0000 | Y | 16.66 |
SMSTORE4_LIGHTS | SMSTORE4 | SMSTORE4 | GENERAL | 9.6995 | 174.19 | 1689.58 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 68.73 | 168.00 | 65.95 | 0.0000 | Y | 20.92 |
SMSTORE4_LIGHTS_ALLOWANCE | SMSTORE4 | SMSTORE4 | GENERAL | 6.9539 | 174.19 | 1211.32 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 84.29 | 73.25 | 0.0000 | Y | 16.66 |
LGSTORE2_LIGHTS | LGSTORE2 | LGSTORE2 | GENERAL | 9.5842 | 348.39 | 3339.00 | LightsWired | LTG_SCH_BASE_LPD2 | 62.11 | 168.00 | 59.29 | 0.0000 | Y | 37.16 |
LGSTORE2_LIGHTS_ALLOWANCE | LGSTORE2 | LGSTORE2 | GENERAL | 0.0000 | 348.39 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE5_LIGHTS | SMSTORE5 | SMSTORE5 | GENERAL | 9.6995 | 174.19 | 1689.58 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 60.29 | 0.0000 | Y | 19.12 |
SMSTORE5_LIGHTS_ALLOWANCE | SMSTORE5 | SMSTORE5 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE6_LIGHTS | SMSTORE6 | SMSTORE6 | GENERAL | 9.6995 | 174.19 | 1689.58 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 60.29 | 0.0000 | Y | 19.12 |
SMSTORE6_LIGHTS_ALLOWANCE | SMSTORE6 | SMSTORE6 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE7_LIGHTS | SMSTORE7 | SMSTORE7 | GENERAL | 9.6995 | 174.19 | 1689.58 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 60.29 | 0.0000 | Y | 19.12 |
SMSTORE7_LIGHTS_ALLOWANCE | SMSTORE7 | SMSTORE7 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE8_LIGHTS | SMSTORE8 | SMSTORE8 | GENERAL | 9.6995 | 174.19 | 1689.58 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 60.29 | 0.0000 | Y | 19.12 |
SMSTORE8_LIGHTS_ALLOWANCE | SMSTORE8 | SMSTORE8 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
Interior Lighting Total | 6.5342 | 4180.64 | 27316.92 | 366.68 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 455.59 | AstronomicalClock | - | 41.73 | 41.73 | 3.57 | |
EXTERIOR_LIGHTS_B | 2744.24 | AstronomicalClock | - | 83.73 | 62.73 | 32.31 | |
EXTERIOR_LIGHTS_C | 2307.23 | AstronomicalClock | - | 83.73 | 55.73 | 24.13 | |
Exterior Lighting Total | 5507.06 | 60.01 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:30
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 53637.21 | 37603.98 | 16033.23 | 0.70 | 3.73 | |||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 28309.95 | 19847.54 | 8462.41 | 0.70 | 3.80 | |||
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 28372.68 | 19891.52 | 8481.16 | 0.70 | 3.80 | |||
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 28453.74 | 19948.35 | 8505.39 | 0.70 | 3.80 | |||
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 28208.53 | 19776.44 | 8432.09 | 0.70 | 3.80 | |||
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 49416.79 | 34645.12 | 14771.67 | 0.70 | 3.73 | |||
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 25934.88 | 18182.43 | 7752.45 | 0.70 | 3.80 | |||
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 25825.61 | 18105.82 | 7719.79 | 0.70 | 3.80 | |||
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 25906.06 | 18162.22 | 7743.84 | 0.70 | 3.80 | |||
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 29725.08 | 20900.60 | 8824.48 | 0.70 | 3.80 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC_1:1 COOLING COIL | 51933.2 | 11.77 | 11.77 | ||||
PSZ-AC_2:2 COOLING COIL | 27410.6 | 11.95 | 11.95 | ||||
PSZ-AC_3:3 COOLING COIL | 27471.3 | 11.95 | 11.95 | ||||
PSZ-AC_4:4 COOLING COIL | 27549.8 | 11.95 | 11.95 | ||||
PSZ-AC_5:5 COOLING COIL | 27312.4 | 11.95 | 11.95 | ||||
PSZ-AC_6:6 COOLING COIL | 47846.8 | 11.77 | 11.77 | ||||
PSZ-AC_7:7 COOLING COIL | 25110.9 | 11.95 | 11.95 | ||||
PSZ-AC_8:8 COOLING COIL | 25005.1 | 11.95 | 11.95 | ||||
PSZ-AC_9:9 COOLING COIL | 25083.0 | 11.95 | 11.95 | ||||
PSZ-AC_10:10 COOLING COIL | 28776.8 | 11.94 | 11.94 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | 57547.23 | 0.80 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | 30145.39 | 0.80 | |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | 30203.09 | 0.80 | |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | 30277.65 | 0.80 | |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | 30052.10 | 0.80 | |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | 53665.15 | 0.80 | |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | 27960.84 | 0.80 | |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | 27860.33 | 0.80 | |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | 27934.32 | 0.80 | |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | 31564.30 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 2.16 | 2311.27 | 1070.05 | 1.00 | 1.30 | General | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.14 | 1262.21 | 1107.16 | 1.00 | 1.37 | General | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.14 | 1265.00 | 1107.16 | 1.00 | 1.37 | General | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.15 | 1268.62 | 1107.16 | 1.00 | 1.37 | General | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.14 | 1257.69 | 1107.16 | 1.00 | 1.37 | General | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 1.99 | 2129.41 | 1070.05 | 1.00 | 1.32 | General | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 |
PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.04 | 1156.31 | 1107.16 | 1.00 | 1.39 | General | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 |
PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.04 | 1151.44 | 1107.16 | 1.00 | 1.39 | General | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.04 | 1155.03 | 1107.16 | 1.00 | 1.39 | General | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.20 | 1330.97 | 1107.16 | 1.00 | 1.36 | General | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
GAS TANK1 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK2 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK3 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK4 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK5 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK6 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK7 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:30
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
LGSTORE1 | 24495.91 | 29395.10 | 84.37 | 1.800 | 2.160 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 23.89 | 23.88 | 0.01035 | 33.90 | 0.01654 | 0.411 | 0.00 |
SMSTORE1 | 12928.86 | 15514.64 | 89.07 | 0.950 | 1.140 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 23.89 | 23.88 | 0.01038 | 33.90 | 0.01654 | 0.206 | 0.00 |
SMSTORE2 | 12957.56 | 15549.08 | 89.26 | 0.952 | 1.143 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 23.89 | 23.88 | 0.01037 | 33.83 | 0.01654 | 0.206 | 0.00 |
SMSTORE3 | 12994.58 | 15593.50 | 89.52 | 0.955 | 1.146 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 23.89 | 23.88 | 0.01037 | 33.83 | 0.01654 | 0.206 | 0.00 |
SMSTORE4 | 12882.60 | 15459.12 | 88.75 | 0.947 | 1.136 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 23.89 | 23.88 | 0.01038 | 33.83 | 0.01654 | 0.206 | 0.00 |
LGSTORE2 | 22569.05 | 27082.86 | 77.74 | 1.658 | 1.990 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 23.89 | 23.88 | 0.01044 | 33.83 | 0.01654 | 0.411 | 0.00 |
SMSTORE5 | 11844.31 | 14213.17 | 81.59 | 0.870 | 1.044 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 23.89 | 23.88 | 0.01051 | 33.83 | 0.01654 | 0.206 | 0.00 |
SMSTORE6 | 11794.41 | 14153.29 | 81.25 | 0.867 | 1.040 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 23.89 | 23.88 | 0.01052 | 33.83 | 0.01654 | 0.206 | 0.00 |
SMSTORE7 | 11831.15 | 14197.38 | 81.50 | 0.869 | 1.043 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 23.89 | 23.88 | 0.01052 | 33.83 | 0.01654 | 0.206 | 0.00 |
SMSTORE8 | 13635.77 | 16362.93 | 93.94 | 1.002 | 1.202 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | 23.89 | 23.88 | 0.01036 | 33.50 | 0.01654 | 0.206 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
LGSTORE1 | 15959.45 | 19151.33 | 54.97 | 0.689 | 0.826 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00704 | 4.60 | 0.00526 | 0.411 | 0.00 |
SMSTORE1 | 7900.64 | 9480.76 | 54.43 | 0.341 | 0.409 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00696 | 4.60 | 0.00526 | 0.206 | 0.00 |
SMSTORE2 | 7962.99 | 9555.59 | 54.86 | 0.344 | 0.412 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00697 | 4.60 | 0.00526 | 0.206 | 0.00 |
SMSTORE3 | 8028.93 | 9634.71 | 55.31 | 0.346 | 0.416 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00697 | 4.60 | 0.00526 | 0.206 | 0.00 |
SMSTORE4 | 8172.02 | 9806.42 | 56.30 | 0.353 | 0.423 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00698 | 4.60 | 0.00526 | 0.206 | 0.00 |
LGSTORE2 | 15376.63 | 18451.96 | 52.96 | 0.663 | 0.796 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00704 | 4.60 | 0.00526 | 0.411 | 0.00 |
SMSTORE5 | 8367.35 | 10040.82 | 57.64 | 0.361 | 0.433 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00700 | 4.60 | 0.00526 | 0.206 | 0.00 |
SMSTORE6 | 8373.14 | 10047.77 | 57.68 | 0.361 | 0.434 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00700 | 4.60 | 0.00526 | 0.206 | 0.00 |
SMSTORE7 | 8619.16 | 10342.99 | 59.38 | 0.372 | 0.446 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00701 | 4.60 | 0.00526 | 0.206 | 0.00 |
SMSTORE8 | 10154.71 | 12185.65 | 69.95 | 0.438 | 0.526 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00706 | 4.60 | 0.00526 | 0.206 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC_1:1 | 2.16 | 2.16 | 0.83 | 0.83 | 2.1600 | 2.1600 | 2.1600 | 1.0000 | 1.0000 |
PSZ-AC_2:2 | 1.14 | 1.14 | 0.41 | 0.41 | 1.1400 | 1.1400 | 1.1400 | 1.0000 | 1.0000 |
PSZ-AC_3:3 | 1.14 | 1.14 | 0.41 | 0.41 | 1.1426 | 1.1426 | 1.1426 | 1.0000 | 1.0000 |
PSZ-AC_4:4 | 1.15 | 1.15 | 0.42 | 0.42 | 1.1458 | 1.1458 | 1.1458 | 1.0000 | 1.0000 |
PSZ-AC_5:5 | 1.14 | 1.14 | 0.42 | 0.42 | 1.1360 | 1.1360 | 1.1360 | 1.0000 | 1.0000 |
PSZ-AC_6:6 | 1.99 | 1.99 | 0.80 | 0.80 | 1.9900 | 1.9900 | 1.9900 | 1.0000 | 1.0000 |
PSZ-AC_7:7 | 1.04 | 1.04 | 0.43 | 0.43 | 1.0444 | 1.0444 | 1.0444 | 1.0000 | 1.0000 |
PSZ-AC_8:8 | 1.04 | 1.04 | 0.43 | 0.43 | 1.0400 | 1.0400 | 1.0400 | 1.0000 | 1.0000 |
PSZ-AC_9:9 | 1.04 | 1.04 | 0.45 | 0.45 | 1.0432 | 1.0432 | 1.0432 | 1.0000 | 1.0000 |
PSZ-AC_10:10 | 1.20 | 1.20 | 0.53 | 0.53 | 1.2022 | 1.2022 | 1.2022 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 53637.210 | 37603.975 | 2.159970 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 26818.60 | 17849.99 | 1.439980 | 26.66 | 19.71 | 0.01153032 | 12.80 | 12.09 | 0.00850000 | 33.90 | 0.01653638 | 25.13 | 28.5753 | 23.88 | 0.01035222 | 55.9117 | 24495.91 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_1:1 | 57547.232 | 57547.232 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 57547.23 | 57547.23 | 2.159971 | 17.96 | 12.41 | 0.00669832 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 19.0502 | 21.11 | 0.00703748 | 45.2273 | 15959.45 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 28309.950 | 19847.540 | 1.140040 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 14154.98 | 9450.46 | 0.760027 | 26.59 | 19.65 | 0.01148846 | 12.80 | 12.09 | 0.00850000 | 33.90 | 0.01653638 | 25.13 | 27.0700 | 23.88 | 0.01037687 | 56.0433 | 12928.86 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_2:2 | 30145.386 | 30145.386 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 30145.39 | 30145.39 | 1.140042 | 18.13 | 12.44 | 0.00665604 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 18.0467 | 21.11 | 0.00696409 | 44.7612 | 7900.64 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_3:3 | 28372.680 | 19891.518 | 1.142570 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 14186.34 | 9475.71 | 0.761713 | 26.58 | 19.65 | 0.01148364 | 12.80 | 12.09 | 0.00850000 | 33.90 | 0.01653638 | 25.13 | 27.0101 | 23.88 | 0.01037380 | 56.0270 | 12955.71 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_3:3 | 30203.094 | 30203.094 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 30203.09 | 30203.09 | 1.142568 | 18.14 | 12.45 | 0.00666014 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 18.0068 | 21.11 | 0.00696826 | 44.7877 | 7962.99 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_4:4 | 28453.740 | 19948.348 | 1.145830 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 14226.87 | 9508.72 | 0.763887 | 26.58 | 19.64 | 0.01147704 | 12.80 | 12.09 | 0.00850000 | 33.90 | 0.01653638 | 25.13 | 26.9332 | 23.88 | 0.01036955 | 56.0044 | 12992.09 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_4:4 | 30277.646 | 30277.646 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 30277.65 | 30277.65 | 1.145832 | 18.14 | 12.45 | 0.00666486 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 17.9555 | 21.11 | 0.00697294 | 44.8175 | 8028.93 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_5:5 | 28208.530 | 19776.436 | 1.135960 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 14104.26 | 9408.62 | 0.757307 | 26.59 | 19.66 | 0.01149744 | 12.80 | 12.09 | 0.00850000 | 33.90 | 0.01653638 | 25.13 | 27.1673 | 23.88 | 0.01038273 | 56.0744 | 12880.37 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_5:5 | 30052.096 | 30052.096 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 30052.10 | 30052.10 | 1.135957 | 18.12 | 12.45 | 0.00667087 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 18.1115 | 21.11 | 0.00698355 | 44.8849 | 8172.02 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_6:6 | 49416.790 | 34645.123 | 1.990010 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 24708.40 | 16197.45 | 1.326673 | 26.82 | 19.89 | 0.01170302 | 12.80 | 12.09 | 0.00850000 | 33.90 | 0.01653638 | 25.13 | 31.0158 | 23.88 | 0.01044282 | 56.3923 | 22564.99 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_6:6 | 53665.147 | 53665.147 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 53665.15 | 53665.15 | 1.990014 | 17.69 | 12.28 | 0.00667314 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 20.6772 | 21.11 | 0.00704224 | 45.2573 | 15376.63 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_7:7 | 25934.880 | 18182.426 | 1.044400 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 12967.44 | 8489.25 | 0.696267 | 26.75 | 19.87 | 0.01170139 | 12.80 | 12.09 | 0.00850000 | 33.90 | 0.01653638 | 25.13 | 29.5489 | 23.88 | 0.01051492 | 56.7763 | 11841.47 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_7:7 | 27960.839 | 27960.839 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 27960.84 | 27960.84 | 1.044398 | 17.86 | 12.33 | 0.00665311 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 19.6993 | 21.11 | 0.00699556 | 44.9613 | 8367.35 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_8:8 | 25825.610 | 18105.819 | 1.040000 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 12912.81 | 8445.50 | 0.693333 | 26.76 | 19.88 | 0.01171189 | 12.80 | 12.09 | 0.00850000 | 33.90 | 0.01653638 | 25.13 | 29.6740 | 23.88 | 0.01052175 | 56.8126 | 11791.50 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_8:8 | 27860.327 | 27860.327 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 27860.33 | 27860.33 | 1.039997 | 17.84 | 12.32 | 0.00665206 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 19.7827 | 21.11 | 0.00699606 | 44.9645 | 8373.14 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_9:9 | 25906.060 | 18162.221 | 1.043240 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 12953.03 | 8477.50 | 0.695493 | 26.75 | 19.87 | 0.01170442 | 12.80 | 12.09 | 0.00850000 | 33.90 | 0.01653638 | 25.13 | 29.5818 | 23.88 | 0.01051690 | 56.7868 | 11827.13 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_9:9 | 27934.317 | 27934.317 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 27934.32 | 27934.32 | 1.043237 | 17.85 | 12.34 | 0.00666644 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 19.7213 | 21.11 | 0.00701265 | 45.0700 | 8619.16 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_10:10 | 29725.080 | 20900.596 | 1.202150 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | 14862.54 | 9971.04 | 0.801433 | 26.43 | 19.55 | 0.01141410 | 12.80 | 12.09 | 0.00850000 | 33.50 | 0.01653563 | 25.03 | 25.6714 | 23.88 | 0.01035661 | 55.9358 | 13635.77 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_10:10 | 31564.302 | 31564.302 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 31564.30 | 31564.30 | 1.202153 | 18.28 | 12.60 | 0.00675225 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 17.1142 | 21.11 | 0.00706096 | 45.3777 | 10154.71 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:37:30
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 53637.210 | 37603.975 | 2.159970 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1026.2743 | 1004.8586 | 1.2032 | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.159971 | 2.59880507 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | Sensible | 26818.60 | 17849.99 | 1.0000 | 1.73253627 | 1.439980 | 26.66 | 19.71 | 0.01153032 | 56194.3 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 26818.60 | 33.90 | 0.01653638 | 25.13 | 0.41147883 | 28.5753 | 23.88 | 0.01035222 | 23.88 | 0.01035222 | 55.9117 | 24495.91 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 57547.232 | 57547.232 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.159971 | 2.59880507 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 57547.23 | 57547.23 | 1.0000 | 2.59880507 | 2.159971 | 17.96 | 12.41 | 0.00669832 | 35026.1 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 57547.23 | 4.60 | 0.00525715 | 4.60 | 0.41147883 | 19.0502 | 21.11 | 0.00703748 | 21.11 | 0.00703748 | 45.2273 | 15959.45 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 28309.950 | 19847.540 | 1.140040 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1026.1965 | 1004.8586 | 1.2032 | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.140042 | 1.37166030 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | Sensible | 14154.98 | 9450.46 | 1.0000 | 0.91443893 | 0.760027 | 26.59 | 19.65 | 0.01148846 | 56015.1 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 14154.98 | 33.90 | 0.01653638 | 25.13 | 0.20573941 | 27.0700 | 23.88 | 0.01037687 | 23.88 | 0.01037687 | 56.0433 | 12928.86 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 30145.386 | 30145.386 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.140042 | 1.37166030 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 30145.39 | 30145.39 | 1.0000 | 1.37166030 | 1.140042 | 18.13 | 12.44 | 0.00665604 | 35087.4 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 30145.39 | 4.60 | 0.00525715 | 4.60 | 0.20573941 | 18.0467 | 21.11 | 0.00696409 | 21.11 | 0.00696409 | 44.7612 | 7900.64 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 28372.680 | 19891.518 | 1.142570 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1026.1875 | 1004.8586 | 1.2032 | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.142568 | 1.37470002 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | Sensible | 14186.34 | 9475.71 | 1.0000 | 0.91646827 | 0.761713 | 26.58 | 19.65 | 0.01148364 | 55999.0 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 14186.34 | 33.90 | 0.01653638 | 25.13 | 0.20573941 | 27.0101 | 23.88 | 0.01037380 | 23.88 | 0.01037380 | 56.0270 | 12955.71 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 30203.094 | 30203.094 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.142568 | 1.37470002 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 30203.09 | 30203.09 | 1.0000 | 1.37470002 | 1.142568 | 18.14 | 12.45 | 0.00666014 | 35104.5 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 30203.09 | 4.60 | 0.00525715 | 4.60 | 0.20573941 | 18.0068 | 21.11 | 0.00696826 | 21.11 | 0.00696826 | 44.7877 | 7962.99 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 28453.740 | 19948.348 | 1.145830 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1026.1752 | 1004.8586 | 1.2032 | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.145832 | 1.37862722 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | Sensible | 14226.87 | 9508.72 | 1.0000 | 0.91908315 | 0.763887 | 26.58 | 19.64 | 0.01147704 | 55977.0 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 14226.87 | 33.90 | 0.01653638 | 25.13 | 0.20573941 | 26.9332 | 23.88 | 0.01036955 | 23.88 | 0.01036955 | 56.0044 | 12992.09 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 30277.646 | 30277.646 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.145832 | 1.37862722 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 30277.65 | 30277.65 | 1.0000 | 1.37862722 | 1.145832 | 18.14 | 12.45 | 0.00666486 | 35125.1 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 30277.65 | 4.60 | 0.00525715 | 4.60 | 0.20573941 | 17.9555 | 21.11 | 0.00697294 | 21.11 | 0.00697294 | 44.8175 | 8028.93 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 28208.530 | 19776.436 | 1.135960 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1026.2132 | 1004.8586 | 1.2032 | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.135957 | 1.36674634 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | Sensible | 14104.26 | 9408.62 | 1.0000 | 0.91116631 | 0.757307 | 26.59 | 19.66 | 0.01149744 | 56045.0 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 14104.26 | 33.90 | 0.01653638 | 25.13 | 0.20573941 | 27.1673 | 23.88 | 0.01038273 | 23.88 | 0.01038273 | 56.0744 | 12880.37 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 30052.096 | 30052.096 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.135957 | 1.36674634 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 30052.10 | 30052.10 | 1.0000 | 1.36674634 | 1.135957 | 18.12 | 12.45 | 0.00667087 | 35114.1 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 30052.10 | 4.60 | 0.00525715 | 4.60 | 0.20573941 | 18.1115 | 21.11 | 0.00698355 | 21.11 | 0.00698355 | 44.8849 | 8172.02 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 49416.790 | 34645.123 | 1.990010 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1026.5953 | 1004.8586 | 1.2032 | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.990014 | 2.39431896 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | Sensible | 24708.40 | 16197.45 | 1.0000 | 1.59620944 | 1.326673 | 26.82 | 19.89 | 0.01170302 | 56802.4 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 24708.40 | 33.90 | 0.01653638 | 25.13 | 0.41147883 | 31.0158 | 23.88 | 0.01044282 | 23.88 | 0.01044282 | 56.3923 | 22564.99 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 53665.147 | 53665.147 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.990014 | 2.39431896 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 53665.15 | 53665.15 | 1.0000 | 2.39431896 | 1.990014 | 17.69 | 12.28 | 0.00667314 | 34689.1 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 53665.15 | 4.60 | 0.00525715 | 4.60 | 0.41147883 | 20.6772 | 21.11 | 0.00704224 | 21.11 | 0.00704224 | 45.2573 | 15376.63 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 25934.880 | 18182.426 | 1.044400 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1026.5923 | 1004.8586 | 1.2032 | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.044398 | 1.25658484 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | Sensible | 12967.44 | 8489.25 | 1.0000 | 0.83772500 | 0.696267 | 26.75 | 19.87 | 0.01170139 | 56728.3 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 12967.44 | 33.90 | 0.01653638 | 25.13 | 0.20573941 | 29.5489 | 23.88 | 0.01051492 | 23.88 | 0.01051492 | 56.7763 | 11841.47 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 27960.839 | 27960.839 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.044398 | 1.25658484 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 27960.84 | 27960.84 | 1.0000 | 1.25658484 | 1.044398 | 17.86 | 12.33 | 0.00665311 | 34802.4 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 27960.84 | 4.60 | 0.00525715 | 4.60 | 0.20573941 | 19.6993 | 21.11 | 0.00699556 | 21.11 | 0.00699556 | 44.9613 | 8367.35 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 25825.610 | 18105.819 | 1.040000 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1026.6118 | 1004.8586 | 1.2032 | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.039997 | 1.25129025 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | Sensible | 12912.81 | 8445.50 | 1.0000 | 0.83419571 | 0.693333 | 26.76 | 19.88 | 0.01171189 | 56763.7 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 12912.81 | 33.90 | 0.01653638 | 25.13 | 0.20573941 | 29.6740 | 23.88 | 0.01052175 | 23.88 | 0.01052175 | 56.8126 | 11791.50 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 27860.327 | 27860.327 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.039997 | 1.25129025 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 27860.33 | 27860.33 | 1.0000 | 1.25129025 | 1.039997 | 17.84 | 12.32 | 0.00665206 | 34785.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 27860.33 | 4.60 | 0.00525715 | 4.60 | 0.20573941 | 19.7827 | 21.11 | 0.00699606 | 21.11 | 0.00699606 | 44.9645 | 8373.14 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 25906.060 | 18162.221 | 1.043240 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1026.5979 | 1004.8586 | 1.2032 | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.043237 | 1.25518823 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | Sensible | 12953.03 | 8477.50 | 1.0000 | 0.83679456 | 0.695493 | 26.75 | 19.87 | 0.01170442 | 56738.5 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 12953.03 | 33.90 | 0.01653638 | 25.13 | 0.20573941 | 29.5818 | 23.88 | 0.01051690 | 23.88 | 0.01051690 | 56.7868 | 11827.13 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 27934.317 | 27934.317 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.043237 | 1.25518823 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 27934.32 | 27934.32 | 1.0000 | 1.25518823 | 1.043237 | 17.85 | 12.34 | 0.00666644 | 34832.5 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 27934.32 | 4.60 | 0.00525715 | 4.60 | 0.20573941 | 19.7213 | 21.11 | 0.00701265 | 21.11 | 0.00701265 | 45.0700 | 8619.16 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 29725.080 | 20900.596 | 1.202150 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1026.0582 | 1004.8586 | 1.2032 | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.202153 | 1.44639108 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | Sensible | 14862.54 | 9971.04 | 1.0000 | 0.96425806 | 0.801433 | 26.43 | 19.55 | 0.01141410 | 55662.1 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 14862.54 | 33.50 | 0.01653563 | 25.03 | 0.20573941 | 25.6714 | 23.88 | 0.01035661 | 23.88 | 0.01035661 | 55.9358 | 13635.77 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 31564.302 | 31564.302 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.202153 | 1.44639108 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 31564.30 | 31564.30 | 1.0000 | 1.44639108 | 1.202153 | 18.28 | 12.60 | 0.00675225 | 35487.7 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 31564.30 | 4.60 | 0.00525715 | 4.60 | 0.20573941 | 17.1142 | 21.11 | 0.00706096 | 21.11 | 0.00706096 | 45.3777 | 10154.71 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:30
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-AC_1:1_OA_CONTROLLER | DifferentialEnthalpy | 0.41 | 2.16 | - | |||
PSZ-AC_2:2_OA_CONTROLLER | DifferentialEnthalpy | 0.21 | 1.14 | - | |||
PSZ-AC_3:3_OA_CONTROLLER | DifferentialEnthalpy | 0.21 | 1.14 | - | |||
PSZ-AC_4:4_OA_CONTROLLER | DifferentialEnthalpy | 0.21 | 1.15 | - | |||
PSZ-AC_5:5_OA_CONTROLLER | DifferentialEnthalpy | 0.21 | 1.14 | - | |||
PSZ-AC_6:6_OA_CONTROLLER | DifferentialEnthalpy | 0.41 | 1.99 | - | |||
PSZ-AC_7:7_OA_CONTROLLER | DifferentialEnthalpy | 0.21 | 1.04 | - | |||
PSZ-AC_8:8_OA_CONTROLLER | DifferentialEnthalpy | 0.21 | 1.04 | - | |||
PSZ-AC_9:9_OA_CONTROLLER | DifferentialEnthalpy | 0.21 | 1.04 | - | |||
PSZ-AC_10:10_OA_CONTROLLER | DifferentialEnthalpy | 0.21 | 1.20 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
LGSTORE1 | 4379.67 | 2303.67 | 1295.67 |
SMSTORE1 | 4279.50 | 1608.00 | 776.50 |
SMSTORE2 | 3306.67 | 1880.00 | 1171.83 |
SMSTORE3 | 3288.33 | 1903.67 | 1164.83 |
SMSTORE4 | 3256.83 | 2044.33 | 1251.83 |
LGSTORE2 | 2938.00 | 2267.83 | 1459.17 |
SMSTORE5 | 2905.67 | 2318.33 | 1479.00 |
SMSTORE6 | 2897.83 | 2355.17 | 1499.50 |
SMSTORE7 | 2884.17 | 2407.00 | 1524.00 |
SMSTORE8 | 2918.67 | 2181.00 | 1307.50 |
Facility | 4557.50 | 3296.33 | 2026.67 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
LGSTORE1 | 0.00 | 0.17 | 0.00 | 0.17 |
SMSTORE1 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 0.00 | 0.17 | 0.00 | 0.00 |
SMSTORE3 | 0.00 | 0.50 | 0.00 | 0.00 |
SMSTORE4 | 0.00 | 0.17 | 0.00 | 0.00 |
LGSTORE2 | 0.00 | 0.50 | 0.00 | 0.00 |
SMSTORE5 | 0.00 | 0.50 | 0.00 | 0.00 |
SMSTORE6 | 0.00 | 0.50 | 0.00 | 0.00 |
SMSTORE7 | 0.00 | 0.33 | 0.00 | 0.00 |
SMSTORE8 | 0.17 | 0.50 | 0.00 | 0.00 |
Facility | 0.17 | 1.00 | 0.00 | 0.17 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:30
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
LGSTORE1 | 16.92 | 56.25 | 1805.20 | 0.941 | 0.345 | 0.000 | 0.000 |
SMSTORE1 | 8.46 | 28.12 | 902.60 | 0.824 | 0.384 | 0.000 | 0.000 |
SMSTORE2 | 7.09 | 28.12 | 902.60 | 0.987 | 0.504 | 0.000 | 0.000 |
SMSTORE3 | 7.09 | 28.12 | 902.60 | 0.984 | 0.504 | 0.000 | 0.000 |
SMSTORE4 | 7.09 | 28.12 | 902.60 | 0.976 | 0.504 | 0.000 | 0.000 |
LGSTORE2 | 24.81 | 56.25 | 1805.20 | 0.954 | 0.472 | 0.000 | 0.000 |
SMSTORE5 | 12.41 | 28.12 | 902.60 | 0.960 | 0.538 | 0.000 | 0.000 |
SMSTORE6 | 12.41 | 28.12 | 902.60 | 0.956 | 0.538 | 0.000 | 0.000 |
SMSTORE7 | 12.41 | 28.12 | 902.60 | 0.952 | 0.538 | 0.000 | 0.000 |
SMSTORE8 | 12.41 | 28.12 | 902.60 | 0.972 | 0.553 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
LGSTORE1 | 16.92 | 56.25 | 1805.20 | 0.000 | 0.000 | 0.000 | 0.000 |
SMSTORE1 | 8.46 | 28.12 | 902.60 | 0.000 | 0.000 | 0.000 | 0.000 |
SMSTORE2 | 7.09 | 28.12 | 902.60 | 0.804 | 0.000 | 0.000 | 0.000 |
SMSTORE3 | 7.09 | 28.12 | 902.60 | 0.804 | 0.000 | 0.000 | 0.000 |
SMSTORE4 | 7.09 | 28.12 | 902.60 | 0.804 | 0.000 | 0.000 | 0.000 |
LGSTORE2 | 24.81 | 56.25 | 1805.20 | 0.805 | 0.000 | 0.000 | 0.000 |
SMSTORE5 | 12.41 | 28.12 | 902.60 | 0.805 | 0.000 | 0.000 | 0.000 |
SMSTORE6 | 12.41 | 28.12 | 902.60 | 0.804 | 0.000 | 0.000 | 0.000 |
SMSTORE7 | 12.41 | 28.12 | 902.60 | 0.805 | 0.000 | 0.000 | 0.000 |
SMSTORE8 | 12.41 | 28.12 | 902.60 | 0.805 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:37:30
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
LGSTORE1 | PSZ-AC_1:1 | 16.92 | 56.25 | 1805.20 | 348.39 | 0.4115 | 0.411 |
SMSTORE1 | PSZ-AC_2:2 | 8.46 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE2 | PSZ-AC_3:3 | 7.09 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE3 | PSZ-AC_4:4 | 7.09 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE4 | PSZ-AC_5:5 | 7.09 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
LGSTORE2 | PSZ-AC_6:6 | 24.81 | 56.25 | 1805.20 | 348.39 | 0.4115 | 0.411 |
SMSTORE5 | PSZ-AC_7:7 | 12.41 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE6 | PSZ-AC_8:8 | 12.41 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE7 | PSZ-AC_9:9 | 12.41 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE8 | PSZ-AC_10:10 | 12.41 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
Total Facility | 121.09 | 337.50 | 10831.20 | 2090.32 | 2.4689 | 2.469 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
LGSTORE1 | 9711006.23 | 0.00 | 9711006.23 | 3838649.30 | 13549655.54 | 12976396.34 | 3170.97 | 4721.64 | 867.39 | 12.76 |
SMSTORE1 | 4255133.89 | 0.00 | 4255133.89 | 2068521.06 | 6323654.95 | 6488198.17 | 4416.53 | 3460.25 | 883.22 | 16.28 |
SMSTORE2 | 3871406.75 | 0.00 | 3871406.75 | 2094113.03 | 5965519.78 | 6488198.17 | 4346.67 | 3803.50 | 609.83 | 70.64 |
SMSTORE3 | 3858070.52 | 0.00 | 3858070.52 | 2094113.03 | 5952183.55 | 6488198.17 | 4348.00 | 3819.75 | 592.25 | 67.82 |
SMSTORE4 | 3824127.08 | 0.00 | 3824127.08 | 2094113.03 | 5918240.11 | 6488198.17 | 4348.65 | 3851.33 | 560.02 | 66.33 |
LGSTORE2 | 6832788.60 | 0.00 | 6832788.60 | 3717029.21 | 10549817.81 | 12976396.34 | 4719.07 | 3527.00 | 513.93 | 46.07 |
SMSTORE5 | 3438741.46 | 0.00 | 3438741.46 | 2101897.61 | 5540639.07 | 6488198.17 | 4718.04 | 3536.42 | 505.55 | 45.55 |
SMSTORE6 | 3425920.91 | 0.00 | 3425920.91 | 2101897.61 | 5527818.52 | 6488198.17 | 4719.76 | 3544.50 | 495.74 | 43.99 |
SMSTORE7 | 3405937.95 | 0.00 | 3405937.95 | 2101897.61 | 5507835.56 | 6488198.17 | 4720.99 | 3565.25 | 473.76 | 35.53 |
SMSTORE8 | 3473502.47 | 0.00 | 3473502.47 | 2340335.64 | 5813838.11 | 6488198.17 | 4721.90 | 3577.83 | 460.27 | 19.03 |
Total Facility | 46096635.88 | 0.00 | 46096635.88 | 24552567.14 | 70649203.01 | 77858378.04 | 4725.03 | 5254.81 | 1146.35 | 138.27 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
LGSTORE1 | 0.4615 | 0.0000 | 0.4615 | 0.1689 | 0.6304 | 0.4115 | 252.23 | 4721.47 | 866.30 |
SMSTORE1 | 0.2021 | 0.0000 | 0.2021 | 0.0942 | 0.2963 | 0.2057 | 1498.48 | 3460.25 | 881.27 |
SMSTORE2 | 0.2419 | 0.0000 | 0.2419 | 0.1236 | 0.3655 | 0.2057 | 0.00 | 3802.67 | 592.33 |
SMSTORE3 | 0.2412 | 0.0000 | 0.2412 | 0.1236 | 0.3648 | 0.2057 | 0.00 | 3819.00 | 576.00 |
SMSTORE4 | 0.2393 | 0.0000 | 0.2393 | 0.1236 | 0.3629 | 0.2057 | 0.00 | 3851.00 | 544.00 |
LGSTORE2 | 0.4676 | 0.0000 | 0.4676 | 0.2310 | 0.6986 | 0.4115 | 0.00 | 3526.92 | 503.08 |
SMSTORE5 | 0.2353 | 0.0000 | 0.2353 | 0.1317 | 0.3670 | 0.2057 | 0.00 | 3536.42 | 493.58 |
SMSTORE6 | 0.2345 | 0.0000 | 0.2345 | 0.1317 | 0.3662 | 0.2057 | 0.00 | 3544.33 | 485.67 |
SMSTORE7 | 0.2334 | 0.0000 | 0.2334 | 0.1317 | 0.3651 | 0.2057 | 0.00 | 3565.25 | 464.75 |
SMSTORE8 | 0.2384 | 0.0000 | 0.2384 | 0.1354 | 0.3738 | 0.2057 | 0.00 | 3577.83 | 452.17 |
Total Facility | 2.7950 | 0.0000 | 2.7950 | 1.3954 | 4.1904 | 2.4689 | 1604.28 | 5252.72 | 1129.91 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-AC_1:1 | 14057708.91 | 0.00 | 14057708.91 | 12976396.34 | 3164.60 | 0.08 | 5595.32 | 12.76 |
PSZ-AC_2:2 | 6159752.63 | 0.00 | 6159752.63 | 6488198.17 | 4346.34 | 2.25 | 4411.41 | 16.28 |
PSZ-AC_3:3 | 5604267.71 | 0.00 | 5604267.71 | 6488198.17 | 4335.22 | 0.33 | 4424.45 | 70.30 |
PSZ-AC_4:4 | 5584963.12 | 0.00 | 5584963.12 | 6488198.17 | 4336.72 | 1.17 | 4422.11 | 67.82 |
PSZ-AC_5:5 | 5535825.70 | 0.00 | 5535825.70 | 6488198.17 | 4339.62 | 0.58 | 4419.80 | 66.16 |
PSZ-AC_6:6 | 9891162.30 | 0.00 | 9891162.30 | 12976396.34 | 4714.40 | 0.00 | 4045.60 | 46.07 |
PSZ-AC_7:7 | 4977935.66 | 0.00 | 4977935.66 | 6488198.17 | 4713.79 | 0.17 | 4046.05 | 45.38 |
PSZ-AC_8:8 | 4959374.64 | 0.00 | 4959374.64 | 6488198.17 | 4714.95 | 0.33 | 4044.71 | 43.99 |
PSZ-AC_9:9 | 4930441.00 | 0.00 | 4930441.00 | 6488198.17 | 4717.91 | 0.25 | 4041.84 | 35.53 |
PSZ-AC_10:10 | 5028246.99 | 0.00 | 5028246.99 | 6488198.17 | 4720.62 | 0.00 | 4039.38 | 19.03 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-AC_1:1 | 0.6681 | 0.0000 | 0.6681 | 0.4115 | 246.78 | 0.08 | 5593.13 |
PSZ-AC_2:2 | 0.2926 | 0.0000 | 0.2926 | 0.2057 | 1429.20 | 2.25 | 4408.55 |
PSZ-AC_3:3 | 0.3502 | 0.0000 | 0.3502 | 0.2057 | 0.00 | 0.00 | 4395.00 |
PSZ-AC_4:4 | 0.3492 | 0.0000 | 0.3492 | 0.2057 | 0.00 | 0.00 | 4395.00 |
PSZ-AC_5:5 | 0.3464 | 0.0000 | 0.3464 | 0.2057 | 0.00 | 0.00 | 4395.00 |
PSZ-AC_6:6 | 0.6768 | 0.0000 | 0.6768 | 0.4115 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_7:7 | 0.3405 | 0.0000 | 0.3405 | 0.2057 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_8:8 | 0.3394 | 0.0000 | 0.3394 | 0.2057 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_9:9 | 0.3378 | 0.0000 | 0.3378 | 0.2057 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_10:10 | 0.3450 | 0.0000 | 0.3450 | 0.2057 | 0.00 | 0.00 | 4030.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-AC_1:1 | 0.00 | 5097.53 | 536.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_2:2 | 0.00 | 4799.59 | 749.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_3:3 | 0.00 | 4124.31 | 341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_4:4 | 0.00 | 4134.64 | 328.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_5:5 | 0.00 | 4152.26 | 308.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_6:6 | 0.00 | 3826.99 | 249.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_7:7 | 0.00 | 3823.77 | 251.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_8:8 | 0.00 | 3827.99 | 246.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_9:9 | 0.00 | 3838.28 | 227.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_10:10 | 0.00 | 3825.91 | 223.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-AC_1:1 | 0.0000 | 0.6662 | 0.9674 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_2:2 | 0.0000 | 0.2925 | 0.4159 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_3:3 | 0.0000 | 0.3381 | 0.5329 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_4:4 | 0.0000 | 0.3373 | 0.5355 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_5:5 | 0.0000 | 0.3349 | 0.5402 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_6:6 | 0.0000 | 0.6603 | 0.9852 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_7:7 | 0.0000 | 0.3315 | 0.5069 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_8:8 | 0.0000 | 0.3308 | 0.5005 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_9:9 | 0.0000 | 0.3296 | 0.5010 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_10:10 | 0.0000 | 0.3343 | 0.5469 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:30
Surfaces by ClassTotal | Outdoors | |
Wall | 40 | 22 |
Floor | 10 | 10 |
Roof | 10 | 10 |
Internal Mass | 10 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 36 | 36 |
Door | 12 | 12 |
Glass Door | 12 | 12 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 10 |
Conditioned Zones | 10 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 830 |
Defaulted Fields | 823 |
Fields with Defaults | 2682 |
Autosized Fields | 184 |
Autosizable Fields | 458 |
Autocalculated Fields | 128 |
Autocalculatable Fields | 256 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:37:30
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1070.47 | 2102.83 | 01-JAN-07:30 | 119517.11 | 10-SEP-13:30 |
Electricity:Building | 494.83 | 891.83 | 01-JAN-00:20 | 31518.67 | 01-JAN-11:10 |
Electricity:Zone:LGSTORE1 | 113.36 | 148.64 | 01-JAN-00:20 | 5964.88 | 01-JAN-10:10 |
Electricity:SpaceType:GENERAL | 494.83 | 891.83 | 01-JAN-00:20 | 31518.67 | 01-JAN-11:10 |
InteriorLights:Electricity | 366.68 | 450.00 | 01-JAN-00:20 | 23459.17 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:LGSTORE1 | 87.12 | 75.00 | 01-JAN-00:20 | 4621.63 | 01-JAN-10:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 366.68 | 450.00 | 01-JAN-00:20 | 23459.17 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity | 366.68 | 450.00 | 01-JAN-00:20 | 23459.17 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:LGSTORE1 | 87.12 | 75.00 | 01-JAN-00:20 | 4621.63 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 366.68 | 450.00 | 01-JAN-00:20 | 23459.17 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE1 | 66.33 | 74.32 | 01-JAN-00:20 | 3498.69 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE1 | 53.20 | 37.50 | 01-JAN-00:20 | 2827.07 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE1 | 53.20 | 37.50 | 01-JAN-00:20 | 2827.07 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE2 | 47.99 | 74.32 | 01-JAN-00:10 | 3226.84 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE2 | 37.57 | 37.50 | 01-JAN-00:10 | 2555.22 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE2 | 37.57 | 37.50 | 01-JAN-00:10 | 2555.22 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE3 | 47.99 | 74.32 | 01-JAN-00:10 | 3226.84 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE3 | 37.57 | 37.50 | 01-JAN-00:10 | 2555.22 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE3 | 37.57 | 37.50 | 01-JAN-00:10 | 2555.22 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE4 | 47.99 | 74.32 | 01-JAN-00:10 | 3226.84 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE4 | 37.57 | 37.50 | 01-JAN-00:10 | 2555.22 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE4 | 37.57 | 37.50 | 01-JAN-00:10 | 2555.22 | 01-JAN-10:10 |
Electricity:Zone:LGSTORE2 | 56.34 | 148.64 | 01-JAN-00:10 | 4070.21 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:LGSTORE2 | 37.16 | 75.00 | 01-JAN-00:10 | 2726.96 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:LGSTORE2 | 37.16 | 75.00 | 01-JAN-00:10 | 2726.96 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE5 | 28.71 | 74.32 | 01-JAN-00:10 | 2076.09 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE5 | 19.12 | 37.50 | 01-JAN-00:10 | 1404.46 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE5 | 19.12 | 37.50 | 01-JAN-00:10 | 1404.46 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE6 | 28.71 | 74.32 | 01-JAN-00:10 | 2076.09 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE6 | 19.12 | 37.50 | 01-JAN-00:10 | 1404.46 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE6 | 19.12 | 37.50 | 01-JAN-00:10 | 1404.46 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE7 | 28.71 | 74.32 | 01-JAN-00:10 | 2076.09 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE7 | 19.12 | 37.50 | 01-JAN-00:10 | 1404.46 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE7 | 19.12 | 37.50 | 01-JAN-00:10 | 1404.46 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE8 | 28.71 | 74.32 | 01-JAN-00:10 | 2076.09 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE8 | 19.12 | 37.50 | 01-JAN-00:10 | 1404.46 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE8 | 19.12 | 37.50 | 01-JAN-00:10 | 1404.46 | 01-JAN-11:10 |
InteriorEquipment:Electricity | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:LGSTORE1 | 26.25 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-10:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LGSTORE1 | 26.25 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE1 | 13.12 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE1 | 13.12 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE2 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE2 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE3 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE3 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE4 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE4 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:LGSTORE2 | 19.17 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LGSTORE2 | 19.17 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE5 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE5 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE6 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE6 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE7 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE7 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE8 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE8 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
ElectricityPurchased:Facility | 1070.47 | 2102.83 | 01-JAN-07:30 | 119517.11 | 10-SEP-13:30 |
ElectricityPurchased:Plant | 1070.47 | 2102.83 | 01-JAN-07:30 | 119517.11 | 10-SEP-13:30 |
Cogeneration:ElectricityPurchased | 1070.47 | 2102.83 | 01-JAN-07:30 | 119517.11 | 10-SEP-13:30 |
General:Cogeneration:ElectricityPurchased | 1070.47 | 2102.83 | 01-JAN-07:30 | 119517.11 | 10-SEP-13:30 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1070.47 | 2102.83 | 01-JAN-07:30 | 119517.11 | 10-SEP-13:30 |
ElectricityNet:Plant | 1070.47 | 2102.83 | 01-JAN-07:30 | 119517.11 | 10-SEP-13:30 |
Cogeneration:ElectricityNet | 1070.47 | 2102.83 | 01-JAN-07:30 | 119517.11 | 10-SEP-13:30 |
General:Cogeneration:ElectricityNet | 1070.47 | 2102.83 | 01-JAN-07:30 | 119517.11 | 10-SEP-13:30 |
Electricity:HVAC | 455.79 | 0.00 | 01-JAN-00:10 | 82893.02 | 10-SEP-13:30 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 352.95 | 0.00 | 01-JAN-00:10 | 71673.28 | 10-SEP-14:10 |
General:Cooling:Electricity | 352.95 | 0.00 | 01-JAN-00:10 | 71673.28 | 10-SEP-14:10 |
Fans:Electricity | 102.84 | 0.00 | 01-JAN-00:10 | 11327.58 | 10-SEP-13:00 |
General:Fans:Electricity | 102.84 | 0.00 | 01-JAN-00:10 | 11327.58 | 10-SEP-13:00 |
ExteriorLights:Electricity | 60.01 | 0.00 | 01-JAN-07:30 | 5507.06 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 60.01 | 0.00 | 01-JAN-07:30 | 5507.06 | 01-JAN-06:10 |
Electricity:Plant | 59.83 | 1211.00 | 05-JAN-08:10 | 11639.69 | 01-JAN-08:30 |
WaterSystems:Electricity | 59.83 | 1211.00 | 05-JAN-08:10 | 11639.69 | 01-JAN-08:30 |
Water Heater:WaterSystems:Electricity | 59.83 | 1211.00 | 05-JAN-08:10 | 11639.69 | 01-JAN-08:30 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 19.27 | 0.00 | 01-JAN-00:10 | 99899.40 | 05-FEB-09:10 |
NaturalGas:HVAC | 19.27 | 0.00 | 01-JAN-00:10 | 99899.40 | 05-FEB-09:10 |
Heating:NaturalGas | 19.27 | 0.00 | 01-JAN-00:10 | 99899.40 | 05-FEB-09:10 |
General:Heating:NaturalGas | 19.27 | 0.00 | 01-JAN-00:10 | 99899.40 | 05-FEB-09:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water:Plant | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
WaterSystems:Water | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water Heater:WaterSystems:Water | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
MainsWater:Facility | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
MainsWater:Plant | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
WaterSystems:MainsWater | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water Heater:WaterSystems:MainsWater | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 2230.89 | 0.00 | 01-JAN-00:10 | 402708.57 | 10-SEP-13:00 |
EnergyTransfer:Building | 767.11 | 0.00 | 01-JAN-00:10 | 118409.26 | 10-SEP-14:10 |
EnergyTransfer:Zone:LGSTORE1 | 160.07 | 0.00 | 01-JAN-00:10 | 19546.23 | 10-SEP-15:00 |
Heating:EnergyTransfer | 8.57 | 0.00 | 01-JAN-00:10 | 55709.61 | 06-FEB-08:10 |
Heating:EnergyTransfer:Zone:LGSTORE1 | 0.86 | 0.00 | 01-JAN-00:10 | 13970.66 | 05-FEB-08:10 |
General:Heating:EnergyTransfer | 8.57 | 0.00 | 01-JAN-00:10 | 55709.61 | 06-FEB-08:10 |
General:Heating:EnergyTransfer:Zone:LGSTORE1 | 0.86 | 0.00 | 01-JAN-00:10 | 13970.66 | 05-FEB-08:10 |
Cooling:EnergyTransfer | 758.53 | 0.00 | 01-JAN-00:10 | 118409.26 | 10-SEP-14:10 |
Cooling:EnergyTransfer:Zone:LGSTORE1 | 159.21 | 0.00 | 01-JAN-00:10 | 19546.23 | 10-SEP-15:00 |
General:Cooling:EnergyTransfer | 758.53 | 0.00 | 01-JAN-00:10 | 118409.26 | 10-SEP-14:10 |
General:Cooling:EnergyTransfer:Zone:LGSTORE1 | 159.21 | 0.00 | 01-JAN-00:10 | 19546.23 | 10-SEP-15:00 |
EnergyTransfer:Zone:SMSTORE1 | 86.12 | 0.00 | 01-JAN-00:10 | 10175.58 | 10-SEP-13:00 |
Heating:EnergyTransfer:Zone:SMSTORE1 | 0.30 | 0.00 | 01-JAN-00:10 | 2851.15 | 05-FEB-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE1 | 0.30 | 0.00 | 01-JAN-00:10 | 2851.15 | 05-FEB-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE1 | 85.82 | 0.00 | 01-JAN-00:10 | 10175.58 | 10-SEP-13:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE1 | 85.82 | 0.00 | 01-JAN-00:10 | 10175.58 | 10-SEP-13:00 |
EnergyTransfer:Zone:SMSTORE2 | 65.60 | 0.00 | 01-JAN-00:10 | 10033.07 | 10-SEP-14:00 |
Heating:EnergyTransfer:Zone:SMSTORE2 | 0.77 | 0.00 | 01-JAN-00:10 | 4394.76 | 05-FEB-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE2 | 0.77 | 0.00 | 01-JAN-00:10 | 4394.76 | 05-FEB-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE2 | 64.83 | 0.00 | 01-JAN-00:10 | 10033.07 | 10-SEP-14:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE2 | 64.83 | 0.00 | 01-JAN-00:10 | 10033.07 | 10-SEP-14:00 |
EnergyTransfer:Zone:SMSTORE3 | 65.29 | 0.00 | 01-JAN-00:10 | 10076.49 | 10-SEP-14:00 |
Heating:EnergyTransfer:Zone:SMSTORE3 | 0.79 | 0.00 | 01-JAN-00:10 | 5004.80 | 05-FEB-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE3 | 0.79 | 0.00 | 01-JAN-00:10 | 5004.80 | 05-FEB-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE3 | 64.50 | 0.00 | 01-JAN-00:10 | 10076.49 | 10-SEP-14:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE3 | 64.50 | 0.00 | 01-JAN-00:10 | 10076.49 | 10-SEP-14:00 |
EnergyTransfer:Zone:SMSTORE4 | 63.12 | 0.00 | 01-JAN-00:10 | 9971.54 | 10-SEP-14:00 |
Heating:EnergyTransfer:Zone:SMSTORE4 | 0.85 | 0.00 | 01-JAN-00:10 | 5372.50 | 05-FEB-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE4 | 0.85 | 0.00 | 01-JAN-00:10 | 5372.50 | 05-FEB-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE4 | 62.27 | 0.00 | 01-JAN-00:10 | 9971.54 | 10-SEP-14:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE4 | 62.27 | 0.00 | 01-JAN-00:10 | 9971.54 | 10-SEP-14:00 |
EnergyTransfer:Zone:LGSTORE2 | 105.68 | 0.00 | 01-JAN-00:10 | 18388.08 | 10-SEP-14:10 |
Heating:EnergyTransfer:Zone:LGSTORE2 | 1.25 | 0.00 | 01-JAN-00:10 | 12159.43 | 05-FEB-09:10 |
General:Heating:EnergyTransfer:Zone:LGSTORE2 | 1.25 | 0.00 | 01-JAN-00:10 | 12159.43 | 05-FEB-09:10 |
Cooling:EnergyTransfer:Zone:LGSTORE2 | 104.43 | 0.00 | 01-JAN-00:10 | 18388.08 | 10-SEP-14:10 |
General:Cooling:EnergyTransfer:Zone:LGSTORE2 | 104.43 | 0.00 | 01-JAN-00:10 | 18388.08 | 10-SEP-14:10 |
EnergyTransfer:Zone:SMSTORE5 | 54.56 | 0.00 | 01-JAN-00:10 | 9773.08 | 10-SEP-14:10 |
Heating:EnergyTransfer:Zone:SMSTORE5 | 0.72 | 0.00 | 01-JAN-00:10 | 6538.71 | 05-FEB-09:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE5 | 0.72 | 0.00 | 01-JAN-00:10 | 6538.71 | 05-FEB-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE5 | 53.84 | 0.00 | 01-JAN-00:10 | 9773.08 | 10-SEP-14:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE5 | 53.84 | 0.00 | 01-JAN-00:10 | 9773.08 | 10-SEP-14:10 |
EnergyTransfer:Zone:SMSTORE6 | 53.98 | 0.00 | 01-JAN-00:10 | 9743.68 | 10-SEP-14:10 |
Heating:EnergyTransfer:Zone:SMSTORE6 | 0.75 | 0.00 | 01-JAN-00:10 | 6720.27 | 05-FEB-09:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE6 | 0.75 | 0.00 | 01-JAN-00:10 | 6720.27 | 05-FEB-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE6 | 53.24 | 0.00 | 01-JAN-00:10 | 9743.68 | 10-SEP-14:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE6 | 53.24 | 0.00 | 01-JAN-00:10 | 9743.68 | 10-SEP-14:10 |
EnergyTransfer:Zone:SMSTORE7 | 53.23 | 0.00 | 01-JAN-00:10 | 9830.03 | 10-SEP-14:10 |
Heating:EnergyTransfer:Zone:SMSTORE7 | 0.87 | 0.00 | 01-JAN-00:10 | 7633.64 | 05-FEB-09:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE7 | 0.87 | 0.00 | 01-JAN-00:10 | 7633.64 | 05-FEB-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE7 | 52.35 | 0.00 | 01-JAN-00:10 | 9830.03 | 10-SEP-14:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE7 | 52.35 | 0.00 | 01-JAN-00:10 | 9830.03 | 10-SEP-14:10 |
EnergyTransfer:Zone:SMSTORE8 | 59.47 | 0.00 | 01-JAN-00:10 | 12464.22 | 05-FEB-09:10 |
Heating:EnergyTransfer:Zone:SMSTORE8 | 1.42 | 0.00 | 01-JAN-00:10 | 12464.22 | 05-FEB-09:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE8 | 1.42 | 0.00 | 01-JAN-00:10 | 12464.22 | 05-FEB-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE8 | 58.05 | 0.00 | 01-JAN-00:10 | 11475.79 | 10-SEP-14:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE8 | 58.05 | 0.00 | 01-JAN-00:10 | 11475.79 | 10-SEP-14:10 |
EnergyTransfer:HVAC | 1463.78 | 0.00 | 01-JAN-00:10 | 286885.27 | 10-SEP-13:00 |
HeatingCoils:EnergyTransfer | 15.42 | 0.00 | 01-JAN-00:10 | 79919.52 | 05-FEB-09:10 |
CoolingCoils:EnergyTransfer | 1448.36 | 0.00 | 01-JAN-00:10 | 286885.27 | 10-SEP-13:00 |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:30
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
LGSTORE1 | 0.000 | 0.000 | 0.856 | -159.209 | 0.000 | 0.000 | 23.583 | 87.116 | 26.249 | 19.401 | 0.000 | 14.167 | 3.093 | 0.000 | -4.684 | 0.000 | -10.572 | -0.001 |
SMSTORE1 | 0.000 | 0.000 | 0.299 | -85.820 | 0.000 | 0.000 | 11.722 | 53.201 | 13.125 | 9.674 | 0.000 | 7.951 | 0.001 | 0.000 | -2.431 | 0.000 | -5.514 | -2.206 |
SMSTORE2 | 0.000 | 0.000 | 0.768 | -64.828 | 0.000 | 0.000 | 7.077 | 37.572 | 10.421 | 9.622 | 0.000 | 7.806 | 0.002 | 0.000 | -2.508 | 0.000 | -5.623 | -0.306 |
SMSTORE3 | 0.000 | 0.000 | 0.794 | -64.493 | 0.000 | 0.000 | 7.082 | 37.572 | 10.421 | 9.628 | 0.000 | 7.804 | 0.000 | 0.000 | -2.493 | 0.000 | -5.587 | -0.728 |
SMSTORE4 | 0.000 | 0.000 | 0.851 | -62.265 | 0.000 | 0.000 | 7.091 | 37.572 | 10.421 | 9.647 | 0.000 | 7.808 | 0.000 | 0.000 | -2.450 | 0.000 | -5.516 | -3.159 |
LGSTORE2 | 0.000 | 0.000 | 1.250 | -104.425 | 0.000 | 0.000 | 24.373 | 37.162 | 19.173 | 19.341 | 0.000 | 13.709 | 3.859 | 0.000 | -4.688 | 0.000 | -9.755 | -0.001 |
SMSTORE5 | 0.000 | 0.000 | 0.715 | -53.842 | 0.000 | 0.000 | 12.194 | 19.120 | 9.586 | 9.675 | 0.000 | 7.819 | 2.463 | 0.000 | -2.318 | 0.000 | -5.413 | -0.000 |
SMSTORE6 | 0.000 | 0.000 | 0.747 | -53.234 | 0.000 | 0.000 | 12.199 | 19.120 | 9.586 | 9.683 | 0.000 | 7.820 | 1.770 | 0.000 | -2.304 | 0.000 | -5.389 | -0.001 |
SMSTORE7 | 0.000 | 0.000 | 0.875 | -52.352 | 0.000 | 0.000 | 12.212 | 19.120 | 9.586 | 9.695 | 0.000 | 7.822 | 0.645 | 0.000 | -2.275 | 0.000 | -5.328 | -0.001 |
SMSTORE8 | 0.000 | 0.000 | 1.418 | -58.050 | 0.000 | 0.000 | 12.222 | 19.120 | 9.586 | 9.673 | 0.000 | 8.023 | 6.646 | 0.000 | -2.192 | 0.000 | -6.447 | -0.001 |
Total Facility | 0.000 | 0.000 | 8.573 | -758.519 | 0.000 | 0.000 | 129.756 | 366.677 | 128.154 | 116.040 | 0.000 | 90.730 | 18.480 | 0.000 | -28.343 | 0.000 | -65.145 | -6.405 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
LGSTORE1 | 26-OCT-07:02 | 0.00 | 0.00 | 0.00 | -47286.28 | 0.00 | 0.00 | 174.46 | 75.00 | 74.62 | 0.00 | 0.00 | 0.00 | 47235.76 | 0.00 | -83.14 | 0.00 | -190.43 | 0.00 |
SMSTORE1 | 26-OCT-07:02 | 0.00 | 0.00 | 0.00 | -25461.07 | 0.00 | 0.00 | 86.46 | 37.50 | 37.31 | 0.00 | 0.00 | 0.00 | 25442.42 | 0.00 | -42.70 | 0.00 | -99.92 | 0.00 |
SMSTORE2 | 26-OCT-06:02 | 0.00 | 0.00 | 0.00 | -24452.70 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 0.00 | 0.00 | 0.00 | 24507.13 | 0.00 | -113.23 | 0.00 | -15.51 | 0.00 |
SMSTORE3 | 26-OCT-06:02 | 0.00 | 0.00 | 0.00 | -24538.11 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 0.00 | 0.00 | 0.00 | 24592.99 | 0.00 | -113.61 | 0.00 | -15.59 | 0.00 |
SMSTORE4 | 26-OCT-06:02 | 0.00 | 0.00 | 0.00 | -24186.52 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 0.00 | 0.00 | 0.00 | 24238.76 | 0.00 | -111.59 | 0.00 | -14.97 | 0.00 |
LGSTORE2 | 26-OCT-07:02 | 0.00 | 0.00 | 0.00 | -43193.70 | 0.00 | 0.00 | 0.00 | 75.00 | 73.64 | 0.00 | 0.00 | 0.00 | 43300.81 | 0.00 | -77.80 | 0.00 | -177.95 | 0.00 |
SMSTORE5 | 26-OCT-07:02 | 0.00 | 0.00 | 0.00 | -22526.21 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 0.00 | 0.00 | 0.00 | 22585.31 | 0.00 | -37.56 | 0.00 | -95.86 | 0.00 |
SMSTORE6 | 26-OCT-07:02 | 0.00 | 0.00 | 0.00 | -22409.11 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 0.00 | 0.00 | 0.00 | 22467.01 | 0.00 | -37.06 | 0.00 | -95.16 | 0.00 |
SMSTORE7 | 26-OCT-07:02 | 0.00 | 0.00 | 0.00 | -22430.97 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 0.00 | 0.00 | 0.00 | 22486.85 | 0.00 | -36.80 | 0.00 | -93.40 | 0.00 |
SMSTORE8 | 26-OCT-07:02 | 0.00 | 0.00 | 0.00 | -22514.76 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 0.00 | 0.00 | 0.00 | 22581.81 | 0.00 | -37.03 | 0.00 | -104.34 | 0.00 |
Total Facility | 26-OCT-07:02 | 0.00 | 0.00 | 0.00 | -212782.25 | 0.00 | 0.00 | 556.43 | 450.00 | 1452.23 | 0.00 | 0.00 | 0.00 | 211883.90 | 0.00 | -439.58 | 0.00 | -1120.74 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
LGSTORE1 | 06-FEB-08:61 | 0.00 | 0.00 | 57725.07 | 0.00 | 0.00 | 0.00 | 247.88 | 75.00 | 74.62 | 198.01 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -1253.89 | -57066.69 |
SMSTORE1 | 05-FEB-08:61 | 0.00 | 0.00 | 16962.78 | 0.00 | 0.00 | 0.00 | 119.46 | 37.50 | 37.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4.82 | 0.00 | -1152.57 | -15999.65 |
SMSTORE2 | 05-FEB-08:61 | 0.00 | 0.00 | 26806.13 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 37.31 | 3.76 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -1151.41 | -25733.30 |
SMSTORE3 | 05-FEB-08:61 | 0.00 | 0.00 | 29930.22 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 37.31 | 7.86 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -1148.69 | -28864.20 |
SMSTORE4 | 05-FEB-08:61 | 0.00 | 0.00 | 29720.09 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 37.31 | 11.43 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -1139.80 | -28666.52 |
LGSTORE2 | 06-FEB-08:61 | 0.00 | 0.00 | 53964.72 | 0.00 | 0.00 | 0.00 | 0.00 | 75.00 | 73.64 | 206.05 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -1184.93 | -53134.49 |
SMSTORE5 | 06-FEB-08:61 | 0.00 | 0.00 | 28120.46 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 102.91 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -672.44 | -27625.24 |
SMSTORE6 | 06-FEB-08:61 | 0.00 | 0.00 | 28021.94 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 104.94 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -668.40 | -27532.81 |
SMSTORE7 | 06-FEB-08:61 | 0.00 | 0.00 | 28097.38 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 112.98 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -651.44 | -27633.23 |
SMSTORE8 | 06-FEB-08:61 | 0.00 | 0.00 | 31610.69 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 142.73 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -635.93 | -31191.81 |
Total Facility | 21-DEC-08:61 | 0.00 | 0.00 | 246775.18 | 0.00 | 0.00 | 0.00 | 714.10 | 450.00 | 1452.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3136.14 | 0.00 | -8796.84 | -237458.53 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:30
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 2.1600 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 2.1600 | 0.1905 | 1.0000 | Not calculated | 0.4115 | 0.1905 | ||
PSZ-AC_2:2 | 1.1400 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.1400 | 0.1805 | 1.0000 | Not calculated | 0.2057 | 0.1805 | ||
PSZ-AC_3:3 | 1.1426 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.1426 | 0.1801 | 1.0000 | Not calculated | 0.2057 | 0.1801 | ||
PSZ-AC_4:4 | 1.1458 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.1458 | 0.1796 | 1.0000 | Not calculated | 0.2057 | 0.1796 | ||
PSZ-AC_5:5 | 1.1360 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.1360 | 0.1811 | 1.0000 | Not calculated | 0.2057 | 0.1811 | ||
PSZ-AC_6:6 | 1.9900 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 1.9900 | 0.2068 | 1.0000 | Not calculated | 0.4115 | 0.2068 | ||
PSZ-AC_7:7 | 1.0444 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0444 | 0.1970 | 1.0000 | Not calculated | 0.2057 | 0.1970 | ||
PSZ-AC_8:8 | 1.0400 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0400 | 0.1978 | 1.0000 | Not calculated | 0.2057 | 0.1978 | ||
PSZ-AC_9:9 | 1.0432 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0432 | 0.1972 | 1.0000 | Not calculated | 0.2057 | 0.1972 | ||
PSZ-AC_10:10 | 1.2022 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.2022 | 0.1711 | 1.0000 | Not calculated | 0.2057 | 0.1711 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 2.1600 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 2.1600 | 1.0000 | 1.0000 | Not calculated | 0.4115 | 0.1905 | ||
PSZ-AC_2:2 | 1.1400 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.1400 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1805 | ||
PSZ-AC_3:3 | 1.1426 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.1426 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1801 | ||
PSZ-AC_4:4 | 1.1458 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.1458 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1796 | ||
PSZ-AC_5:5 | 1.1360 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.1360 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1811 | ||
PSZ-AC_6:6 | 1.9900 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 1.9900 | 1.0000 | 1.0000 | Not calculated | 0.4115 | 0.2068 | ||
PSZ-AC_7:7 | 1.0444 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0444 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1970 | ||
PSZ-AC_8:8 | 1.0400 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0400 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1978 | ||
PSZ-AC_9:9 | 1.0432 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0432 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1972 | ||
PSZ-AC_10:10 | 1.2022 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.2022 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1711 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
LGSTORE1 | PSZ-AC_1:1 | 0.000000 | 56.2505 | 0.001181 | 348.39 | 0.4115 | 1.0000 | 0.4115 | 1.000 | 0.4115 |
SMSTORE1 | PSZ-AC_2:2 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE2 | PSZ-AC_3:3 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE3 | PSZ-AC_4:4 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE4 | PSZ-AC_5:5 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
LGSTORE2 | PSZ-AC_6:6 | 0.000000 | 56.2505 | 0.001181 | 348.39 | 0.4115 | 1.0000 | 0.4115 | 1.000 | 0.4115 |
SMSTORE5 | PSZ-AC_7:7 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE6 | PSZ-AC_8:8 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE7 | PSZ-AC_9:9 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE8 | PSZ-AC_10:10 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC_1:1 | 0.000000 | 56.25 | 0.001181 | 348.3864 | 0.4115 | 0.4115 | 0.4115 |
PSZ-AC_2:2 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_3:3 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_4:4 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_5:5 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_6:6 | 0.000000 | 56.25 | 0.001181 | 348.3864 | 0.4115 | 0.4115 | 0.4115 |
PSZ-AC_7:7 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_8:8 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_9:9 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_10:10 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LGSTORE1 | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.1600 | 2.1600 | 2.1600 | No | 0.4115 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE1 | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1400 | 1.1400 | 1.1400 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE2 | PSZ-AC_3:3 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1426 | 1.1426 | 1.1426 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE3 | PSZ-AC_4:4 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1458 | 1.1458 | 1.1458 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE4 | PSZ-AC_5:5 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1360 | 1.1360 | 1.1360 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LGSTORE2 | PSZ-AC_6:6 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.9900 | 1.9900 | 1.9900 | No | 0.4115 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE5 | PSZ-AC_7:7 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0444 | 1.0444 | 1.0444 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE6 | PSZ-AC_8:8 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0400 | 1.0400 | 1.0400 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE7 | PSZ-AC_9:9 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0432 | 1.0432 | 1.0432 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE8 | PSZ-AC_10:10 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2022 | 1.2022 | 1.2022 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 2.1600 | 2.1600 | 2.1600 | 2.1600 | 0.4115 | 1.0000 |
PSZ-AC_2:2 | 1.1400 | 1.1400 | 1.1400 | 1.1400 | 0.2057 | 1.0000 |
PSZ-AC_3:3 | 1.1426 | 1.1426 | 1.1426 | 1.1426 | 0.2057 | 1.0000 |
PSZ-AC_4:4 | 1.1458 | 1.1458 | 1.1458 | 1.1458 | 0.2057 | 1.0000 |
PSZ-AC_5:5 | 1.1360 | 1.1360 | 1.1360 | 1.1360 | 0.2057 | 1.0000 |
PSZ-AC_6:6 | 1.9900 | 1.9900 | 1.9900 | 1.9900 | 0.4115 | 1.0000 |
PSZ-AC_7:7 | 1.0444 | 1.0444 | 1.0444 | 1.0444 | 0.2057 | 1.0000 |
PSZ-AC_8:8 | 1.0400 | 1.0400 | 1.0400 | 1.0400 | 0.2057 | 1.0000 |
PSZ-AC_9:9 | 1.0432 | 1.0432 | 1.0432 | 1.0432 | 0.2057 | 1.0000 |
PSZ-AC_10:10 | 1.2022 | 1.2022 | 1.2022 | 1.2022 | 0.2057 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LGSTORE1 | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.1600 | 2.1600 | 2.1600 | No | 0.4115 | 0.4980 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE1 | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1400 | 1.1400 | 1.1400 | No | 0.2057 | 0.5030 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE2 | PSZ-AC_3:3 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1426 | 1.1426 | 1.1426 | No | 0.2057 | 0.4990 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE3 | PSZ-AC_4:4 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1458 | 1.1458 | 1.1458 | No | 0.2057 | 0.4949 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE4 | PSZ-AC_5:5 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1360 | 1.1360 | 1.1360 | No | 0.2057 | 0.4863 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LGSTORE2 | PSZ-AC_6:6 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.9900 | 1.9900 | 1.9900 | No | 0.4115 | 0.5169 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE5 | PSZ-AC_7:7 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0444 | 1.0444 | 1.0444 | No | 0.2057 | 0.4749 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE6 | PSZ-AC_8:8 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0400 | 1.0400 | 1.0400 | No | 0.2057 | 0.4746 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE7 | PSZ-AC_9:9 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0432 | 1.0432 | 1.0432 | No | 0.2057 | 0.4611 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE8 | PSZ-AC_10:10 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2022 | 1.2022 | 1.2022 | No | 0.2057 | 0.3913 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 2.1600 | 2.1600 | 2.1600 | 2.1600 | 0.4115 | 1.0000 |
PSZ-AC_2:2 | 1.1400 | 1.1400 | 1.1400 | 1.1400 | 0.2057 | 1.0000 |
PSZ-AC_3:3 | 1.1426 | 1.1426 | 1.1426 | 1.1426 | 0.2057 | 1.0000 |
PSZ-AC_4:4 | 1.1458 | 1.1458 | 1.1458 | 1.1458 | 0.2057 | 1.0000 |
PSZ-AC_5:5 | 1.1360 | 1.1360 | 1.1360 | 1.1360 | 0.2057 | 1.0000 |
PSZ-AC_6:6 | 1.9900 | 1.9900 | 1.9900 | 1.9900 | 0.4115 | 1.0000 |
PSZ-AC_7:7 | 1.0444 | 1.0444 | 1.0444 | 1.0444 | 0.2057 | 1.0000 |
PSZ-AC_8:8 | 1.0400 | 1.0400 | 1.0400 | 1.0400 | 0.2057 | 1.0000 |
PSZ-AC_9:9 | 1.0432 | 1.0432 | 1.0432 | 1.0432 | 0.2057 | 1.0000 |
PSZ-AC_10:10 | 1.2022 | 1.2022 | 1.2022 | 1.2022 | 0.2057 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:30
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Tampa-MacDill AFB FL USA TMY3 WMO#=747880 |
Total gross floor area [m2] | 2090.32 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
LGSTORE1 | 348.39 | 348.39 | 0.00 | 112.00 |
SMSTORE1 | 174.19 | 174.19 | 0.00 | 112.00 |
SMSTORE2 | 174.19 | 174.19 | 0.00 | 84.29 |
SMSTORE3 | 174.19 | 174.19 | 0.00 | 84.29 |
SMSTORE4 | 174.19 | 174.19 | 0.00 | 84.29 |
LGSTORE2 | 348.39 | 348.39 | 0.00 | 77.29 |
SMSTORE5 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE6 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE7 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE8 | 174.19 | 174.19 | 0.00 | 77.29 |
Totals | 2090.32 | 2090.32 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 0.17 |
Number of hours not met | 0.17 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 19.27 | 99899.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 352.95 | 71673.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 366.68 | 23459.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 60.01 | 5507.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 128.15 | 8059.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 102.84 | 11327.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 59.83 | 11639.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 128.15 | 1070.47 |
Natural Gas | 0.00 | 19.27 |
Additional | 0.00 | 0.00 |
Total | 128.15 | 1089.74 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 175.42 |
Space Heating | 0.00 |
Space Cooling | 168.85 |
Fans (All) | 49.20 |
Service Water Heating | 28.62 |
Receptacle Equipment | 61.31 |
Miscellaneous (All) | 512.11 |
Subtotal | 512.11 |
Natural Gas [MJ/m2] | |
Space Heating | 9.22 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 9.22 |
Subtotal | 9.22 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 33.65 |
Space Heating | 1.77 |
Space Cooling | 32.39 |
Fans (All) | 9.44 |
Service Water Heating | 5.49 |
Receptacle Equipment | 11.76 |
Miscellaneous | 5.51 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
TYPE1_OCC_SCH | 1630. | 5840. |
TYPE2_OCC_SCH | 995. | 4429. |
TYPE3_OCC_SCH | 1709. | 4064. |
LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 3767. | 8760. |
LTG_SCH_BASE_LPD2 | 3238. | 8760. |
LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 3296. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | 5084. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | 5084. | 8760. |
LTG_SCH_BASE_SMALL_LPD1 | 4453. | 8760. |
LTG_SCH_BASE_LPD1 | 4376. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | 3767. | 8760. |
LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 3584. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 4096. | 8760. |
TYPE1_EQUIP_SCH | 4868. | 8760. |
TYPE2_EQUIP_SCH | 3893. | 8760. |
TYPE3_EQUIP_SCH | 3584. | 8760. |
TYPE1_INFIL_SCH | 4302. | 8760. |
TYPE2_INFIL_SCH | 5164. | 8760. |
TYPE3_INFIL_SCH | 5438. | 8760. |
INFIL_DOOR_OPENING_SCH | 2505. | 4380. |
TYPE1_MINOA_MOTORIZEDDAMPER_SCH | 5579. | 5579. |
TYPE2_MINOA_MOTORIZEDDAMPER_SCH | 4429. | 4429. |
TYPE3_MINOA_MOTORIZEDDAMPER_SCH | 4064. | 4064. |
TYPE1_SWH_SCH | 2063. | 6048. |
TYPE2_SWH_SCH | 1831. | 4429. |
TYPE3_SWH_SCH | 1733. | 4064. |
AVERAGE_SWH_SCH | 1863. | 6152. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 7118. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 5839. | 5839. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 7300. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6570. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
TYPE1_HTGSETP_SCH_NO_OPTIMUM | LGSTORE1 DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
TYPE1_CLGSETP_SCH_NO_OPTIMUM | LGSTORE1 DUAL SP CONTROL | July | 23.89 | 365 | 23.89 | 365 |
TYPE2_HTGSETP_SCH_NO_OPTIMUM | SMSTORE2 DUAL SP CONTROL | January | 21.11 | 365 | 15.56 | 365 |
TYPE2_CLGSETP_SCH_NO_OPTIMUM | SMSTORE2 DUAL SP CONTROL | July | 23.89 | 365 | 29.44 | 365 |
TYPE3_HTGSETP_SCH_NO_OPTIMUM | LGSTORE2 DUAL SP CONTROL | January | 21.11 | 365 | 15.56 | 365 |
TYPE3_CLGSETP_SCH_NO_OPTIMUM | LGSTORE2 DUAL SP CONTROL | July | 23.89 | 365 | 29.44 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:30
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
LGSTORE1 | 8753.17 | 6.83 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 8755.50 | 4.50 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 8070.00 | 689.67 | 0.33 | 0.00 | 0.00 |
SMSTORE3 | 7980.50 | 779.17 | 0.33 | 0.00 | 0.00 |
SMSTORE4 | 8156.00 | 603.67 | 0.33 | 0.00 | 0.00 |
LGSTORE2 | 8375.17 | 384.50 | 0.33 | 0.00 | 0.00 |
SMSTORE5 | 8397.33 | 362.50 | 0.17 | 0.00 | 0.00 |
SMSTORE6 | 8406.17 | 353.67 | 0.17 | 0.00 | 0.00 |
SMSTORE7 | 8418.50 | 341.17 | 0.33 | 0.00 | 0.00 |
SMSTORE8 | 8335.67 | 424.00 | 0.33 | 0.00 | 0.00 |
Min | 7980.50 | 4.50 | 0.00 | 0.00 | 0.00 |
Max | 8755.50 | 779.17 | 0.33 | 0.00 | 0.00 |
Average | 8364.80 | 394.97 | 0.23 | 0.00 | 0.00 |
Sum | 83648.00 | 3949.67 | 2.33 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
LGSTORE1 | 89041.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 43777.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 25403.50 | 71.33 | 0.17 | 0.00 | 0.00 |
SMSTORE3 | 25403.50 | 71.33 | 0.17 | 0.00 | 0.00 |
SMSTORE4 | 25407.50 | 67.33 | 0.17 | 0.00 | 0.00 |
LGSTORE2 | 93017.00 | 193.00 | 1.00 | 0.00 | 0.00 |
SMSTORE5 | 45815.50 | 96.50 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 45817.50 | 94.50 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 45818.00 | 93.50 | 0.50 | 0.00 | 0.00 |
SMSTORE8 | 45805.50 | 106.00 | 0.50 | 0.00 | 0.00 |
Min | 25403.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 93017.00 | 193.00 | 1.00 | 0.00 | 0.00 |
Average | 48530.60 | 79.35 | 0.25 | 0.00 | 0.00 |
Sum | 485306.00 | 793.50 | 2.50 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
LGSTORE1 | 5471.83 | 3288.17 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 7327.33 | 1432.67 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 4572.00 | 4188.00 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 4595.50 | 4164.50 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 4529.17 | 4230.83 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 4282.67 | 4477.33 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 4299.17 | 4460.83 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 4290.67 | 4469.33 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 4290.17 | 4469.83 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 4550.00 | 4210.00 | 0.00 | 0.00 | 0.00 |
Min | 4282.67 | 1432.67 | 0.00 | 0.00 | 0.00 |
Max | 7327.33 | 4477.33 | 0.00 | 0.00 | 0.00 |
Average | 4820.85 | 3939.15 | 0.00 | 0.00 | 0.00 |
Sum | 48208.50 | 39391.50 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
LGSTORE1 | 69738.50 | 19302.50 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 35715.50 | 8061.50 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 18504.33 | 6970.67 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 18524.67 | 6950.33 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 18088.00 | 7387.00 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 57628.67 | 35582.33 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 28169.33 | 17742.67 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 27969.33 | 17942.67 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 27843.00 | 18069.00 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 30798.33 | 15113.67 | 0.00 | 0.00 | 0.00 |
Min | 18088.00 | 6950.33 | 0.00 | 0.00 | 0.00 |
Max | 69738.50 | 35582.33 | 0.00 | 0.00 | 0.00 |
Average | 33297.97 | 15312.23 | 0.00 | 0.00 | 0.00 |
Sum | 332979.67 | 153122.33 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:30
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:30
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
For: Environment
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTRIPMALL
For: Environment
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 2A
For: Environment
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_FL_TAMPA
For: Environment
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: ZoneCoolingSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.748247E+10 | 12172.46 | 01-JAN-14:00 | 26.00 | 17.88 | 0.127230E+10 | 1685.95 | 16-JAN-18:49 | 18.33 | 16.84 |
February | 0.707088E+10 | 13901.15 | 28-FEB-08:63 | 19.50 | 18.32 | 0.119483E+10 | 1685.90 | 20-FEB-18:49 | 19.50 | 18.32 |
March | 0.816951E+10 | 12815.60 | 07-MAR-08:63 | 21.47 | 19.93 | 0.133158E+10 | 1686.01 | 26-MAR-12:00 | 29.40 | 20.20 |
April | 0.109001E+11 | 26815.49 | 29-APR-07:03 | 24.08 | 22.45 | 0.136017E+10 | 1686.03 | 22-APR-12:39 | 24.08 | 22.45 |
May | 0.165480E+11 | 33998.98 | 07-MAY-07:02 | 24.60 | 22.15 | 0.140169E+10 | 1686.07 | 28-MAY-12:00 | 32.20 | 23.64 |
June | 0.173147E+11 | 34668.27 | 11-JUN-07:02 | 23.58 | 20.40 | 0.135468E+10 | 1686.04 | 18-JUN-12:00 | 30.60 | 26.05 |
July | 0.183512E+11 | 34064.52 | 09-JUL-07:01 | 28.48 | 25.79 | 0.141292E+10 | 1686.05 | 01-JUL-12:00 | 28.48 | 25.79 |
August | 0.192100E+11 | 36929.45 | 31-AUG-07:02 | 25.45 | 23.81 | 0.139423E+10 | 1686.05 | 25-AUG-12:30 | 25.45 | 23.81 |
September | 0.172234E+11 | 33196.98 | 22-SEP-07:02 | 21.97 | 19.93 | 0.136535E+10 | 1686.04 | 23-SEP-12:20 | 30.70 | 24.24 |
October | 0.170593E+11 | 47318.59 | 26-OCT-07:02 | 21.83 | 13.09 | 0.140938E+10 | 1686.06 | 13-OCT-12:20 | 21.83 | 13.09 |
November | 0.109462E+11 | 31708.09 | 07-NOV-08:62 | 22.47 | 20.72 | 0.135589E+10 | 1686.05 | 03-NOV-12:00 | 22.47 | 20.72 |
December | 0.893548E+10 | 29880.14 | 17-DEC-08:62 | 19.83 | 15.88 | 0.134065E+10 | 1686.03 | 10-DEC-13:30 | 19.83 | 15.88 |
Annual Sum or Average | 0.159211E+12 | 0.161937E+11 | ||||||||
Minimum of Months | 0.707088E+10 | 12172.46 | 19.50 | 13.09 | 0.119483E+10 | 1685.90 | 18.33 | 13.09 | ||
Maximum of Months | 0.192100E+11 | 47318.59 | 28.48 | 25.79 | 0.141292E+10 | 1686.07 | 32.20 | 26.05 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.380118E+10 | 14900.50 | 29-JAN-19:09 | 19.00 | 15.30 | 0.663744E+09 | 842.98 | 01-JAN-13:00 | 19.00 | 15.30 |
February | 0.388040E+10 | 12506.89 | 20-FEB-18:28 | 19.65 | 17.65 | 0.612483E+09 | 842.99 | 24-FEB-13:39 | 27.37 | 21.42 |
March | 0.459034E+10 | 16495.66 | 04-MAR-19:08 | 21.42 | 13.84 | 0.678391E+09 | 842.99 | 26-MAR-12:39 | 29.03 | 20.30 |
April | 0.622684E+10 | 16698.10 | 02-APR-17:56 | 17.20 | 13.09 | 0.679579E+09 | 842.99 | 22-APR-12:39 | 29.03 | 19.99 |
May | 0.903434E+10 | 21048.70 | 30-MAY-07:02 | 26.28 | 23.33 | 0.700838E+09 | 843.01 | 19-MAY-12:30 | 26.28 | 23.33 |
June | 0.929990E+10 | 21801.59 | 26-JUN-07:02 | 25.68 | 23.94 | 0.677340E+09 | 843.00 | 18-JUN-12:39 | 25.68 | 23.94 |
July | 0.979229E+10 | 21104.19 | 09-JUL-07:01 | 28.48 | 25.79 | 0.706454E+09 | 843.01 | 08-JUL-12:09 | 28.48 | 25.79 |
August | 0.100546E+11 | 21879.37 | 31-AUG-07:02 | 25.45 | 23.81 | 0.697105E+09 | 843.01 | 12-AUG-12:50 | 25.45 | 23.81 |
September | 0.910729E+10 | 21062.44 | 02-SEP-07:02 | 25.97 | 24.31 | 0.682661E+09 | 842.99 | 22-SEP-12:09 | 28.38 | 21.44 |
October | 0.907857E+10 | 25474.13 | 26-OCT-07:02 | 21.83 | 13.09 | 0.704388E+09 | 843.00 | 20-OCT-12:30 | 21.83 | 13.09 |
November | 0.610744E+10 | 19590.80 | 02-NOV-07:02 | 22.98 | 22.50 | 0.679476E+09 | 843.00 | 03-NOV-12:50 | 29.22 | 24.44 |
December | 0.484869E+10 | 18026.09 | 17-DEC-08:62 | 19.83 | 15.88 | 0.683015E+09 | 842.99 | 10-DEC-13:09 | 19.83 | 15.88 |
Annual Sum or Average | 0.858219E+11 | 0.816548E+10 | ||||||||
Minimum of Months | 0.380118E+10 | 12506.89 | 17.20 | 13.09 | 0.612483E+09 | 842.98 | 19.00 | 13.09 | ||
Maximum of Months | 0.100546E+11 | 25474.13 | 28.48 | 25.79 | 0.706454E+09 | 843.01 | 29.22 | 25.79 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.288403E+10 | 10040.66 | 02-JAN-07:03 | 15.83 | 15.23 | 0.382631E+09 | 842.94 | 28-JAN-13:00 | 22.00 | 13.62 |
February | 0.284389E+10 | 9522.48 | 28-FEB-07:03 | 18.90 | 18.08 | 0.360818E+09 | 842.90 | 25-FEB-13:09 | 18.90 | 18.08 |
March | 0.337016E+10 | 9408.57 | 30-MAR-06:03 | 20.50 | 19.29 | 0.412088E+09 | 842.93 | 04-MAR-13:09 | 20.50 | 19.29 |
April | 0.447583E+10 | 16150.25 | 28-APR-06:03 | 23.22 | 22.07 | 0.409945E+09 | 842.99 | 22-APR-12:39 | 23.22 | 22.07 |
May | 0.691184E+10 | 17947.46 | 12-MAY-06:02 | 23.40 | 20.68 | 0.426338E+09 | 842.99 | 27-MAY-12:20 | 30.37 | 24.49 |
June | 0.721938E+10 | 18619.51 | 14-JUN-06:02 | 25.28 | 22.79 | 0.417307E+09 | 842.98 | 17-JUN-12:50 | 27.80 | 24.92 |
July | 0.747259E+10 | 16792.84 | 19-JUL-06:01 | 26.88 | 24.44 | 0.420467E+09 | 843.00 | 01-JUL-12:50 | 26.88 | 24.44 |
August | 0.786811E+10 | 18559.54 | 31-AUG-06:02 | 24.00 | 23.17 | 0.432011E+09 | 843.01 | 12-AUG-12:50 | 24.00 | 23.17 |
September | 0.691093E+10 | 17481.83 | 23-SEP-06:02 | 22.28 | 20.36 | 0.411078E+09 | 842.98 | 09-SEP-12:09 | 22.28 | 20.36 |
October | 0.687559E+10 | 24471.92 | 26-OCT-06:02 | 22.00 | 13.53 | 0.420433E+09 | 842.98 | 14-OCT-12:09 | 22.00 | 13.53 |
November | 0.444930E+10 | 17796.19 | 08-NOV-07:02 | 19.50 | 18.38 | 0.403931E+09 | 842.95 | 25-NOV-13:39 | 20.17 | 14.26 |
December | 0.354851E+10 | 18656.68 | 17-DEC-08:62 | 19.83 | 15.88 | 0.396160E+09 | 842.95 | 16-DEC-13:09 | 19.83 | 15.88 |
Annual Sum or Average | 0.648302E+11 | 0.489321E+10 | ||||||||
Minimum of Months | 0.284389E+10 | 9408.57 | 15.83 | 13.53 | 0.360818E+09 | 842.90 | 18.90 | 13.53 | ||
Maximum of Months | 0.786811E+10 | 24471.92 | 26.88 | 24.44 | 0.432011E+09 | 843.01 | 30.37 | 24.92 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.276127E+10 | 9872.65 | 02-JAN-07:03 | 15.83 | 15.23 | 0.380506E+09 | 842.93 | 28-JAN-13:00 | 22.00 | 13.62 |
February | 0.274252E+10 | 9170.32 | 28-FEB-07:03 | 18.90 | 18.08 | 0.359639E+09 | 842.90 | 25-FEB-13:09 | 18.90 | 18.08 |
March | 0.327879E+10 | 9174.17 | 30-MAR-06:03 | 20.50 | 19.29 | 0.411263E+09 | 842.93 | 04-MAR-13:00 | 20.50 | 19.29 |
April | 0.443101E+10 | 16214.65 | 28-APR-06:03 | 23.22 | 22.07 | 0.409889E+09 | 842.99 | 22-APR-12:39 | 23.22 | 22.07 |
May | 0.692879E+10 | 18026.51 | 12-MAY-06:02 | 23.40 | 20.68 | 0.426337E+09 | 843.00 | 27-MAY-12:09 | 31.28 | 24.76 |
June | 0.724794E+10 | 18711.20 | 14-JUN-06:02 | 25.28 | 22.79 | 0.417308E+09 | 842.98 | 17-JUN-12:50 | 27.80 | 24.92 |
July | 0.751662E+10 | 16878.50 | 19-JUL-06:01 | 26.88 | 24.44 | 0.420470E+09 | 843.00 | 01-JUL-12:50 | 26.88 | 24.44 |
August | 0.790396E+10 | 18649.56 | 31-AUG-06:02 | 24.00 | 23.17 | 0.432012E+09 | 843.01 | 12-AUG-12:50 | 24.00 | 23.17 |
September | 0.694194E+10 | 17548.15 | 23-SEP-06:02 | 22.28 | 20.36 | 0.411078E+09 | 842.98 | 09-SEP-12:09 | 22.28 | 20.36 |
October | 0.689375E+10 | 24557.45 | 26-OCT-06:02 | 22.00 | 13.53 | 0.420428E+09 | 842.98 | 14-OCT-12:09 | 22.00 | 13.53 |
November | 0.439232E+10 | 17853.47 | 08-NOV-07:02 | 19.50 | 18.38 | 0.403787E+09 | 842.95 | 25-NOV-13:39 | 20.17 | 14.26 |
December | 0.345614E+10 | 18584.60 | 17-DEC-08:62 | 19.83 | 15.88 | 0.395192E+09 | 842.96 | 16-DEC-13:09 | 19.83 | 15.88 |
Annual Sum or Average | 0.644951E+11 | 0.488791E+10 | ||||||||
Minimum of Months | 0.274252E+10 | 9170.32 | 15.83 | 13.53 | 0.359639E+09 | 842.90 | 18.90 | 13.53 | ||
Maximum of Months | 0.790396E+10 | 24557.45 | 26.88 | 24.44 | 0.432012E+09 | 843.01 | 31.28 | 24.92 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.256492E+10 | 8807.51 | 02-JAN-07:03 | 15.83 | 15.23 | 0.377383E+09 | 842.93 | 28-JAN-13:00 | 22.00 | 13.62 |
February | 0.255190E+10 | 7878.22 | 28-FEB-07:03 | 18.90 | 18.08 | 0.357583E+09 | 842.90 | 25-FEB-13:09 | 18.90 | 18.08 |
March | 0.306893E+10 | 7826.33 | 30-MAR-06:03 | 20.50 | 19.29 | 0.409543E+09 | 842.93 | 04-MAR-13:00 | 20.50 | 19.29 |
April | 0.422061E+10 | 14997.18 | 30-APR-07:03 | 21.50 | 20.38 | 0.409722E+09 | 842.99 | 22-APR-12:39 | 21.50 | 20.38 |
May | 0.674656E+10 | 17751.80 | 12-MAY-06:02 | 23.40 | 20.68 | 0.426303E+09 | 843.00 | 27-MAY-12:09 | 31.28 | 24.76 |
June | 0.707419E+10 | 18408.05 | 14-JUN-06:02 | 25.28 | 22.79 | 0.417275E+09 | 842.97 | 17-JUN-12:50 | 27.80 | 24.92 |
July | 0.735105E+10 | 16566.51 | 19-JUL-06:01 | 26.88 | 24.44 | 0.420437E+09 | 843.00 | 01-JUL-12:00 | 26.88 | 24.44 |
August | 0.773244E+10 | 18359.08 | 31-AUG-06:02 | 24.00 | 23.17 | 0.431979E+09 | 843.00 | 12-AUG-12:50 | 24.00 | 23.17 |
September | 0.678265E+10 | 17286.01 | 23-SEP-06:02 | 22.28 | 20.36 | 0.411047E+09 | 842.97 | 09-SEP-12:09 | 22.28 | 20.36 |
October | 0.672264E+10 | 24205.51 | 26-OCT-06:02 | 22.00 | 13.53 | 0.420365E+09 | 842.98 | 14-OCT-12:09 | 22.00 | 13.53 |
November | 0.419431E+10 | 17561.00 | 08-NOV-07:02 | 19.50 | 18.38 | 0.403401E+09 | 842.95 | 25-NOV-13:39 | 20.17 | 14.26 |
December | 0.325668E+10 | 17237.45 | 17-DEC-08:62 | 19.83 | 15.88 | 0.393579E+09 | 842.96 | 16-DEC-13:09 | 19.83 | 15.88 |
Annual Sum or Average | 0.622669E+11 | 0.487862E+10 | ||||||||
Minimum of Months | 0.255190E+10 | 7826.33 | 15.83 | 13.53 | 0.357583E+09 | 842.90 | 18.90 | 13.53 | ||
Maximum of Months | 0.773244E+10 | 24205.51 | 26.88 | 24.44 | 0.431979E+09 | 843.00 | 31.28 | 24.92 |
Report: ZoneCoolingSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.411466E+10 | 12226.36 | 02-JAN-08:63 | 15.50 | 14.72 | 0.127816E+10 | 2247.89 | 28-JAN-15:39 | 23.00 | 14.05 |
February | 0.408495E+10 | 11651.35 | 28-FEB-08:63 | 19.50 | 18.32 | 0.121394E+10 | 2247.80 | 11-FEB-15:00 | 19.50 | 18.32 |
March | 0.490298E+10 | 10560.27 | 26-MAR-14:10 | 28.97 | 20.05 | 0.139527E+10 | 2247.88 | 04-MAR-15:00 | 28.97 | 20.05 |
April | 0.688385E+10 | 25986.78 | 29-APR-07:03 | 24.08 | 22.45 | 0.140693E+10 | 2247.99 | 15-APR-14:09 | 24.08 | 22.45 |
May | 0.114430E+11 | 31461.21 | 12-MAY-07:03 | 23.98 | 20.89 | 0.145820E+10 | 2248.06 | 06-MAY-14:30 | 23.98 | 20.89 |
June | 0.120816E+11 | 33251.50 | 14-JUN-07:02 | 26.88 | 23.48 | 0.143028E+10 | 2248.06 | 03-JUN-14:09 | 26.88 | 23.48 |
July | 0.125223E+11 | 31056.54 | 19-JUL-07:02 | 28.07 | 25.39 | 0.143890E+10 | 2248.03 | 29-JUL-14:09 | 27.20 | 24.88 |
August | 0.132521E+11 | 34192.11 | 31-AUG-07:02 | 25.45 | 23.81 | 0.148043E+10 | 2248.05 | 26-AUG-14:30 | 25.45 | 23.81 |
September | 0.115522E+11 | 31037.46 | 23-SEP-07:02 | 23.08 | 21.03 | 0.141077E+10 | 2248.02 | 23-SEP-14:00 | 28.80 | 24.09 |
October | 0.114629E+11 | 43225.04 | 26-OCT-07:02 | 21.83 | 13.09 | 0.143492E+10 | 2248.01 | 21-OCT-14:09 | 21.83 | 13.09 |
November | 0.683354E+10 | 30773.41 | 07-NOV-08:62 | 22.47 | 20.72 | 0.137304E+10 | 2248.03 | 04-NOV-14:30 | 22.47 | 20.72 |
December | 0.529231E+10 | 29503.18 | 17-DEC-09:02 | 19.00 | 14.29 | 0.134071E+10 | 2248.03 | 09-DEC-15:20 | 19.00 | 14.29 |
Annual Sum or Average | 0.104426E+12 | 0.166615E+11 | ||||||||
Minimum of Months | 0.408495E+10 | 10560.27 | 15.50 | 13.09 | 0.121394E+10 | 2247.80 | 19.00 | 13.09 | ||
Maximum of Months | 0.132521E+11 | 43225.04 | 28.97 | 25.39 | 0.148043E+10 | 2248.06 | 28.97 | 24.88 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.199707E+10 | 5762.70 | 02-JAN-08:63 | 15.50 | 14.72 | 0.636527E+09 | 1123.91 | 28-JAN-15:39 | 23.00 | 14.05 |
February | 0.201079E+10 | 5330.71 | 24-FEB-14:00 | 27.20 | 21.39 | 0.605120E+09 | 1123.87 | 11-FEB-15:00 | 27.20 | 21.39 |
March | 0.243767E+10 | 5518.42 | 26-MAR-14:10 | 28.97 | 20.05 | 0.696034E+09 | 1123.91 | 04-MAR-15:00 | 28.97 | 20.05 |
April | 0.352421E+10 | 12367.12 | 29-APR-07:03 | 24.08 | 22.45 | 0.703360E+09 | 1123.97 | 15-APR-14:09 | 24.08 | 22.45 |
May | 0.598765E+10 | 16147.73 | 31-MAY-07:02 | 24.87 | 22.53 | 0.729065E+09 | 1124.00 | 06-MAY-14:30 | 24.87 | 22.53 |
June | 0.632687E+10 | 17371.67 | 14-JUN-07:02 | 26.88 | 23.48 | 0.715101E+09 | 1124.00 | 03-JUN-14:09 | 26.88 | 23.48 |
July | 0.655655E+10 | 16226.03 | 19-JUL-07:02 | 28.07 | 25.39 | 0.719410E+09 | 1123.99 | 29-JUL-14:20 | 27.20 | 25.03 |
August | 0.693017E+10 | 17859.49 | 31-AUG-07:02 | 25.45 | 23.81 | 0.740179E+09 | 1123.99 | 26-AUG-14:30 | 25.45 | 23.81 |
September | 0.602305E+10 | 16198.02 | 23-SEP-07:02 | 23.08 | 21.03 | 0.705348E+09 | 1123.97 | 23-SEP-14:00 | 28.80 | 24.09 |
October | 0.595282E+10 | 22543.29 | 26-OCT-07:02 | 21.83 | 13.09 | 0.717430E+09 | 1123.97 | 21-OCT-14:09 | 21.83 | 13.09 |
November | 0.346941E+10 | 14965.16 | 07-NOV-08:62 | 22.47 | 20.72 | 0.686222E+09 | 1123.92 | 25-NOV-15:09 | 19.80 | 14.72 |
December | 0.262715E+10 | 14184.79 | 17-DEC-09:02 | 19.00 | 14.29 | 0.669073E+09 | 1123.97 | 16-DEC-15:00 | 19.00 | 14.29 |
Annual Sum or Average | 0.538434E+11 | 0.832287E+10 | ||||||||
Minimum of Months | 0.199707E+10 | 5330.71 | 15.50 | 13.09 | 0.605120E+09 | 1123.87 | 19.00 | 13.09 | ||
Maximum of Months | 0.693017E+10 | 22543.29 | 28.97 | 25.39 | 0.740179E+09 | 1124.00 | 28.97 | 25.03 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.194023E+10 | 5455.09 | 01-JAN-15:10 | 25.00 | 18.55 | 0.634981E+09 | 1123.91 | 28-JAN-15:39 | 23.00 | 14.05 |
February | 0.195819E+10 | 5271.46 | 02-FEB-13:40 | 27.90 | 20.68 | 0.603872E+09 | 1123.87 | 11-FEB-15:00 | 22.20 | 18.16 |
March | 0.237985E+10 | 5454.59 | 26-MAR-14:10 | 28.97 | 20.05 | 0.694955E+09 | 1123.91 | 04-MAR-15:00 | 28.97 | 20.05 |
April | 0.346546E+10 | 11981.81 | 29-APR-07:03 | 24.08 | 22.45 | 0.703228E+09 | 1123.97 | 15-APR-14:09 | 24.08 | 22.45 |
May | 0.593816E+10 | 16046.22 | 31-MAY-07:02 | 24.87 | 22.53 | 0.729059E+09 | 1124.00 | 06-MAY-14:30 | 24.87 | 22.53 |
June | 0.628047E+10 | 17275.42 | 14-JUN-07:02 | 26.88 | 23.48 | 0.715096E+09 | 1124.00 | 03-JUN-14:09 | 26.88 | 23.48 |
July | 0.651436E+10 | 16128.52 | 19-JUL-07:02 | 28.07 | 25.39 | 0.719404E+09 | 1123.99 | 29-JUL-14:20 | 27.20 | 25.03 |
August | 0.688811E+10 | 17758.54 | 31-AUG-07:02 | 25.45 | 23.81 | 0.740175E+09 | 1123.99 | 26-AUG-14:30 | 25.45 | 23.81 |
September | 0.598256E+10 | 16108.47 | 23-SEP-07:02 | 23.08 | 21.03 | 0.705343E+09 | 1123.97 | 23-SEP-14:00 | 28.80 | 24.09 |
October | 0.590452E+10 | 22426.08 | 26-OCT-07:02 | 21.83 | 13.09 | 0.717399E+09 | 1123.97 | 21-OCT-14:09 | 21.83 | 13.09 |
November | 0.341344E+10 | 14643.45 | 03-NOV-07:03 | 21.47 | 21.47 | 0.685942E+09 | 1123.91 | 25-NOV-15:09 | 19.80 | 14.72 |
December | 0.256982E+10 | 13746.25 | 17-DEC-09:02 | 19.00 | 14.29 | 0.667971E+09 | 1123.97 | 16-DEC-15:00 | 19.00 | 14.29 |
Annual Sum or Average | 0.532352E+11 | 0.831742E+10 | ||||||||
Minimum of Months | 0.194023E+10 | 5271.46 | 19.00 | 13.09 | 0.603872E+09 | 1123.87 | 19.00 | 13.09 | ||
Maximum of Months | 0.688811E+10 | 22426.08 | 28.97 | 25.39 | 0.740175E+09 | 1124.00 | 28.97 | 25.03 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.180696E+10 | 5358.34 | 01-JAN-15:10 | 25.00 | 18.55 | 0.631660E+09 | 1123.91 | 28-JAN-15:39 | 23.00 | 14.05 |
February | 0.183442E+10 | 5152.94 | 24-FEB-14:00 | 27.20 | 21.39 | 0.601020E+09 | 1123.87 | 11-FEB-15:00 | 27.20 | 21.39 |
March | 0.224171E+10 | 5340.89 | 26-MAR-14:10 | 28.97 | 20.05 | 0.692342E+09 | 1123.91 | 04-MAR-15:00 | 28.97 | 20.05 |
April | 0.332928E+10 | 10538.51 | 29-APR-07:03 | 24.08 | 22.45 | 0.702749E+09 | 1124.00 | 29-APR-14:09 | 30.00 | 24.56 |
May | 0.588242E+10 | 15997.88 | 31-MAY-07:02 | 24.87 | 22.53 | 0.729053E+09 | 1123.99 | 06-MAY-14:30 | 24.87 | 22.53 |
June | 0.625091E+10 | 17258.19 | 14-JUN-07:02 | 26.88 | 23.48 | 0.715093E+09 | 1124.01 | 03-JUN-14:39 | 26.88 | 23.48 |
July | 0.651294E+10 | 16143.41 | 19-JUL-07:02 | 28.07 | 25.39 | 0.719403E+09 | 1123.98 | 29-JUL-14:20 | 27.20 | 25.03 |
August | 0.690366E+10 | 17794.44 | 31-AUG-07:02 | 25.45 | 23.81 | 0.740176E+09 | 1123.99 | 26-AUG-14:30 | 25.45 | 23.81 |
September | 0.597790E+10 | 16120.26 | 23-SEP-07:02 | 23.08 | 21.03 | 0.705344E+09 | 1123.97 | 23-SEP-14:00 | 28.80 | 24.09 |
October | 0.586989E+10 | 22448.01 | 26-OCT-07:02 | 21.83 | 13.09 | 0.717306E+09 | 1123.96 | 21-OCT-14:09 | 21.83 | 13.09 |
November | 0.330125E+10 | 14433.39 | 02-NOV-07:02 | 22.98 | 22.50 | 0.685222E+09 | 1123.90 | 25-NOV-15:09 | 19.80 | 14.72 |
December | 0.244182E+10 | 12482.26 | 17-DEC-09:02 | 19.00 | 14.29 | 0.665324E+09 | 1123.98 | 16-DEC-15:00 | 19.00 | 14.29 |
Annual Sum or Average | 0.523532E+11 | 0.830469E+10 | ||||||||
Minimum of Months | 0.180696E+10 | 5152.94 | 19.00 | 13.09 | 0.601020E+09 | 1123.87 | 19.00 | 13.09 | ||
Maximum of Months | 0.690366E+10 | 22448.01 | 28.97 | 25.39 | 0.740176E+09 | 1124.01 | 30.00 | 25.03 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.166727E+10 | 5663.10 | 01-JAN-15:10 | 25.00 | 18.55 | 0.630377E+09 | 1123.91 | 28-JAN-15:39 | 23.00 | 14.05 |
February | 0.175289E+10 | 5607.36 | 24-FEB-13:50 | 27.28 | 21.41 | 0.598082E+09 | 1123.87 | 11-FEB-15:50 | 27.28 | 21.41 |
March | 0.224210E+10 | 5902.13 | 26-MAR-14:10 | 28.97 | 20.05 | 0.689715E+09 | 1123.91 | 04-MAR-15:00 | 28.97 | 20.05 |
April | 0.351795E+10 | 7898.08 | 28-APR-15:00 | 33.30 | 23.06 | 0.702138E+09 | 1123.96 | 22-APR-14:09 | 33.30 | 23.06 |
May | 0.661239E+10 | 17479.08 | 31-MAY-07:02 | 24.87 | 22.53 | 0.729124E+09 | 1123.99 | 27-MAY-14:00 | 24.87 | 22.53 |
June | 0.716950E+10 | 18064.67 | 14-JUN-07:02 | 26.88 | 23.48 | 0.715184E+09 | 1123.96 | 24-JUN-14:00 | 27.20 | 23.27 |
July | 0.757836E+10 | 17653.42 | 19-JUL-07:02 | 28.07 | 25.39 | 0.719548E+09 | 1124.00 | 08-JUL-14:09 | 28.07 | 25.39 |
August | 0.809054E+10 | 20672.85 | 31-AUG-07:02 | 25.45 | 23.81 | 0.740301E+09 | 1124.01 | 26-AUG-14:00 | 25.45 | 23.81 |
September | 0.690239E+10 | 18247.27 | 01-SEP-07:02 | 25.97 | 23.81 | 0.705491E+09 | 1124.02 | 23-SEP-14:09 | 30.22 | 24.09 |
October | 0.667335E+10 | 22529.80 | 26-OCT-07:02 | 21.83 | 13.09 | 0.717236E+09 | 1123.96 | 21-OCT-14:50 | 21.83 | 13.09 |
November | 0.348115E+10 | 15332.44 | 02-NOV-07:02 | 22.98 | 22.50 | 0.684688E+09 | 1123.88 | 25-NOV-15:09 | 19.80 | 14.72 |
December | 0.236356E+10 | 8785.38 | 17-DEC-09:02 | 19.00 | 14.29 | 0.662749E+09 | 1123.99 | 16-DEC-15:20 | 19.00 | 14.29 |
Annual Sum or Average | 0.580514E+11 | 0.829463E+10 | ||||||||
Minimum of Months | 0.166727E+10 | 5607.36 | 19.00 | 13.09 | 0.598082E+09 | 1123.87 | 19.00 | 13.09 | ||
Maximum of Months | 0.809054E+10 | 22529.80 | 33.30 | 25.39 | 0.740301E+09 | 1124.02 | 33.30 | 25.39 |
Report: ZoneHeatingSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.124454E+09 | 57225.49 | 10-JAN-08:61 | 4.17 |
February | 0.152151E+09 | 57725.08 | 06-FEB-08:61 | 4.87 |
March | 0.201353E+09 | 57191.20 | 11-MAR-08:61 | 7.52 |
April | 43171848.60 | 1769.84 | 29-APR-07:05 | 24.08 |
May | 31234179.86 | 1929.75 | 16-MAY-07:05 | 26.38 |
June | 28472893.31 | 1924.20 | 09-JUN-07:05 | 24.50 |
July | 25812112.04 | 1816.70 | 19-JUL-07:05 | 28.07 |
August | 25639396.70 | 1820.79 | 03-AUG-07:05 | 26.88 |
September | 24554336.81 | 1804.87 | 22-SEP-07:04 | 21.97 |
October | 30127865.63 | 2173.43 | 26-OCT-07:04 | 21.83 |
November | 47929154.68 | 1916.68 | 01-NOV-07:05 | 23.38 |
December | 0.120805E+09 | 57495.62 | 21-DEC-08:61 | 3.50 |
Annual Sum or Average | 0.855705E+09 | |||
Minimum of Months | 24554336.81 | 1769.84 | 3.50 | |
Maximum of Months | 0.201353E+09 | 57725.08 | 28.07 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 41136263.94 | 4149.59 | 05-JAN-08:61 | 1.00 |
February | 40672860.25 | 16962.84 | 05-FEB-08:61 | -2.9 |
March | 54049885.18 | 6129.39 | 12-MAR-07:02 | 6.97 |
April | 19644737.61 | 1058.31 | 29-APR-07:05 | 24.08 |
May | 17220468.74 | 1128.64 | 12-MAY-07:05 | 23.98 |
June | 14846320.80 | 1132.83 | 02-JUN-07:05 | 25.97 |
July | 12201106.34 | 1106.03 | 15-JUL-07:05 | 26.38 |
August | 13141434.13 | 1087.38 | 19-AUG-07:04 | 24.58 |
September | 13822148.74 | 1100.78 | 22-SEP-07:04 | 21.97 |
October | 15668337.97 | 1220.73 | 26-OCT-07:04 | 21.83 |
November | 17697447.88 | 1125.16 | 03-NOV-07:05 | 21.47 |
December | 38730804.27 | 16473.67 | 21-DEC-08:61 | 3.50 |
Annual Sum or Average | 0.298832E+09 | |||
Minimum of Months | 12201106.34 | 1058.31 | -2.9 | |
Maximum of Months | 54049885.18 | 16962.84 | 26.38 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 46398071.49 | 5134.60 | 10-JAN-07:03 | 3.17 |
February | 56643450.60 | 26806.16 | 05-FEB-08:61 | -2.9 |
March | 64871850.26 | 15328.20 | 12-MAR-07:02 | 6.97 |
April | 29476232.32 | 1720.73 | 22-APR-17:03 | 30.13 |
May | 86957589.56 | 2534.36 | 28-MAY-16:02 | 33.43 |
June | 0.104140E+09 | 2354.67 | 25-JUN-16:02 | 32.70 |
July | 0.106597E+09 | 2845.44 | 22-JUL-17:02 | 34.63 |
August | 90970657.87 | 2573.74 | 27-AUG-16:02 | 33.67 |
September | 64708364.08 | 3281.70 | 09-SEP-17:02 | 36.18 |
October | 53089243.42 | 1856.57 | 08-OCT-16:02 | 30.67 |
November | 22141945.24 | 1054.13 | 01-NOV-06:05 | 22.80 |
December | 41897477.17 | 7368.96 | 21-DEC-07:03 | 0.50 |
Annual Sum or Average | 0.767892E+09 | |||
Minimum of Months | 22141945.24 | 1054.13 | -2.9 | |
Maximum of Months | 0.106597E+09 | 26806.16 | 36.18 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 51300716.93 | 7534.45 | 10-JAN-07:03 | 3.17 |
February | 64558963.50 | 29930.26 | 05-FEB-08:61 | -2.9 |
March | 73556989.90 | 19186.02 | 12-MAR-07:02 | 6.97 |
April | 30359266.74 | 1722.25 | 22-APR-17:03 | 30.13 |
May | 86895838.98 | 2535.27 | 28-MAY-16:02 | 33.43 |
June | 0.104137E+09 | 2354.98 | 25-JUN-16:02 | 32.70 |
July | 0.106067E+09 | 2845.72 | 22-JUL-17:02 | 34.63 |
August | 90449735.50 | 2573.45 | 27-AUG-16:02 | 33.67 |
September | 64389220.59 | 3282.48 | 09-SEP-17:02 | 36.18 |
October | 53021184.16 | 1856.18 | 08-OCT-16:02 | 30.67 |
November | 23551573.87 | 1058.16 | 01-NOV-06:05 | 22.80 |
December | 46046636.72 | 8705.17 | 21-DEC-07:03 | 0.50 |
Annual Sum or Average | 0.794334E+09 | |||
Minimum of Months | 23551573.87 | 1058.16 | -2.9 | |
Maximum of Months | 0.106067E+09 | 29930.26 | 36.18 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 61011683.27 | 9898.79 | 10-JAN-07:03 | 3.17 |
February | 77159147.57 | 29720.12 | 05-FEB-08:61 | -2.9 |
March | 87726350.66 | 22814.28 | 12-MAR-07:02 | 6.97 |
April | 31424465.08 | 1728.84 | 22-APR-17:03 | 30.13 |
May | 88484670.44 | 2539.29 | 28-MAY-16:02 | 33.43 |
June | 0.105473E+09 | 2358.77 | 25-JUN-16:02 | 32.70 |
July | 0.107746E+09 | 2850.59 | 22-JUL-17:02 | 34.63 |
August | 91767571.46 | 2577.01 | 27-AUG-16:02 | 33.67 |
September | 65446882.15 | 3286.08 | 09-SEP-17:02 | 36.18 |
October | 55018031.95 | 1859.18 | 08-OCT-16:02 | 30.67 |
November | 25947886.74 | 1024.67 | 01-NOV-06:05 | 22.80 |
December | 53812052.53 | 10447.38 | 21-DEC-07:03 | 0.50 |
Annual Sum or Average | 0.851018E+09 | |||
Minimum of Months | 25947886.74 | 1024.67 | -2.9 | |
Maximum of Months | 0.107746E+09 | 29720.12 | 36.18 |
Report: ZoneHeatingSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.140843E+09 | 53531.51 | 10-JAN-08:61 | 4.17 |
February | 0.163717E+09 | 53964.75 | 06-FEB-08:61 | 4.87 |
March | 0.177381E+09 | 53902.69 | 12-MAR-08:61 | 9.18 |
April | 63473167.80 | 3469.36 | 22-APR-17:03 | 30.13 |
May | 89464714.41 | 5090.26 | 28-MAY-16:02 | 33.43 |
June | 93888500.20 | 4727.42 | 25-JUN-16:02 | 32.70 |
July | 0.114156E+09 | 5710.12 | 22-JUL-17:02 | 34.63 |
August | 75450213.88 | 5169.91 | 27-AUG-16:02 | 33.67 |
September | 94237918.78 | 6562.48 | 09-SEP-17:02 | 36.18 |
October | 65865654.26 | 3718.94 | 08-OCT-16:02 | 30.67 |
November | 50038895.51 | 1874.40 | 05-NOV-16:03 | 27.02 |
December | 0.121383E+09 | 53765.75 | 21-DEC-08:61 | 3.50 |
Annual Sum or Average | 0.124990E+10 | |||
Minimum of Months | 50038895.51 | 1874.40 | 3.50 | |
Maximum of Months | 0.177381E+09 | 53964.75 | 36.18 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 87976178.04 | 27886.08 | 10-JAN-08:61 | 4.17 |
February | 0.107081E+09 | 28120.47 | 06-FEB-08:61 | 4.87 |
March | 0.108371E+09 | 28086.35 | 12-MAR-08:61 | 9.18 |
April | 34855963.27 | 1751.55 | 22-APR-17:03 | 30.13 |
May | 46047926.62 | 2551.85 | 28-MAY-16:02 | 33.43 |
June | 47458444.51 | 2371.21 | 25-JUN-16:02 | 32.70 |
July | 58479679.12 | 2869.96 | 22-JUL-17:02 | 34.63 |
August | 39048730.60 | 2590.26 | 27-AUG-16:02 | 33.67 |
September | 48937089.80 | 3297.94 | 09-SEP-17:02 | 36.18 |
October | 34486926.59 | 1869.15 | 08-OCT-16:02 | 30.67 |
November | 27935355.59 | 948.37 | 05-NOV-16:03 | 27.02 |
December | 74589703.12 | 28013.11 | 21-DEC-08:61 | 3.50 |
Annual Sum or Average | 0.715268E+09 | |||
Minimum of Months | 27935355.59 | 948.37 | 3.50 | |
Maximum of Months | 0.108371E+09 | 28120.47 | 36.18 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 95673114.53 | 27789.83 | 10-JAN-08:61 | 4.17 |
February | 0.117915E+09 | 28021.96 | 06-FEB-08:61 | 4.87 |
March | 0.115052E+09 | 27988.98 | 12-MAR-08:61 | 9.18 |
April | 35683184.01 | 1752.95 | 22-APR-17:03 | 30.13 |
May | 46131270.73 | 2552.77 | 28-MAY-16:02 | 33.43 |
June | 47492376.04 | 2371.96 | 25-JUN-16:02 | 32.70 |
July | 58575853.05 | 2870.97 | 22-JUL-17:02 | 34.63 |
August | 39056820.89 | 2591.05 | 27-AUG-16:02 | 33.67 |
September | 48883185.30 | 3298.50 | 09-SEP-17:02 | 36.18 |
October | 34709729.00 | 1869.94 | 08-OCT-16:02 | 30.67 |
November | 28522211.32 | 949.82 | 05-NOV-16:03 | 27.02 |
December | 79127707.35 | 27915.98 | 21-DEC-08:61 | 3.50 |
Annual Sum or Average | 0.746823E+09 | |||
Minimum of Months | 28522211.32 | 949.82 | 3.50 | |
Maximum of Months | 0.117915E+09 | 28021.96 | 36.18 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.128838E+09 | 27863.09 | 10-JAN-08:61 | 4.17 |
February | 0.153404E+09 | 28097.40 | 06-FEB-08:61 | 4.87 |
March | 0.145190E+09 | 28059.81 | 12-MAR-08:61 | 9.18 |
April | 39233015.36 | 1756.06 | 22-APR-17:03 | 30.13 |
May | 46922828.54 | 2554.08 | 28-MAY-16:02 | 33.43 |
June | 47700953.03 | 2372.73 | 25-JUN-16:02 | 32.70 |
July | 58712316.87 | 2870.49 | 22-JUL-17:02 | 34.63 |
August | 38951629.91 | 2590.37 | 27-AUG-16:02 | 33.67 |
September | 48894710.82 | 3298.56 | 09-SEP-17:02 | 36.18 |
October | 35300512.39 | 1869.55 | 08-OCT-16:02 | 30.67 |
November | 30146362.72 | 952.85 | 05-NOV-16:03 | 27.02 |
December | 0.101669E+09 | 27989.50 | 21-DEC-08:61 | 3.50 |
Annual Sum or Average | 0.874963E+09 | |||
Minimum of Months | 30146362.72 | 952.85 | 3.50 | |
Maximum of Months | 0.153404E+09 | 28097.40 | 36.18 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.280376E+09 | 31310.89 | 10-JAN-08:61 | 4.17 |
February | 0.282752E+09 | 31610.71 | 06-FEB-08:61 | 4.87 |
March | 0.281852E+09 | 31566.47 | 12-MAR-08:61 | 9.18 |
April | 47224074.19 | 1755.04 | 22-APR-17:03 | 30.13 |
May | 49034044.07 | 2543.21 | 28-MAY-16:02 | 33.43 |
June | 48502308.14 | 2358.29 | 25-JUN-16:02 | 32.70 |
July | 57361125.32 | 2838.06 | 22-JUL-17:02 | 34.63 |
August | 37186195.14 | 2561.41 | 27-AUG-16:02 | 33.67 |
September | 47606833.57 | 3277.07 | 09-SEP-17:02 | 36.18 |
October | 38460235.77 | 1848.84 | 08-OCT-16:02 | 30.67 |
November | 37574182.46 | 1716.05 | 16-NOV-08:65 | 11.88 |
December | 0.209919E+09 | 31472.11 | 21-DEC-08:61 | 3.50 |
Annual Sum or Average | 0.141785E+10 | |||
Minimum of Months | 37186195.14 | 1716.05 | 3.50 | |
Maximum of Months | 0.282752E+09 | 31610.71 | 36.18 |
Report: ZoneElectricSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.739462E+10 | 4621.63 | 01-JAN-10:09 | 0.222596E+10 | 1343.25 | 01-JAN-10:09 |
February | 0.668410E+10 | 4621.63 | 01-FEB-10:09 | 0.201408E+10 | 1343.25 | 01-FEB-10:09 |
March | 0.740180E+10 | 4621.63 | 01-MAR-10:09 | 0.223295E+10 | 1343.25 | 01-MAR-10:09 |
April | 0.716384E+10 | 4621.63 | 01-APR-09:09 | 0.215748E+10 | 1343.25 | 01-APR-09:09 |
May | 0.739462E+10 | 4621.63 | 01-MAY-09:09 | 0.222596E+10 | 1343.25 | 01-MAY-09:09 |
June | 0.716485E+10 | 4621.63 | 01-JUN-09:09 | 0.216232E+10 | 1343.25 | 01-JUN-09:09 |
July | 0.740069E+10 | 4621.63 | 01-JUL-09:09 | 0.222811E+10 | 1343.25 | 01-JUL-09:09 |
August | 0.739513E+10 | 4621.63 | 01-AUG-09:09 | 0.222838E+10 | 1343.25 | 01-AUG-09:09 |
September | 0.717041E+10 | 4621.63 | 01-SEP-09:09 | 0.216205E+10 | 1343.25 | 01-SEP-09:09 |
October | 0.739462E+10 | 4621.63 | 01-OCT-09:09 | 0.222596E+10 | 1343.25 | 01-OCT-09:09 |
November | 0.714323E+10 | 4621.63 | 01-NOV-09:09 | 0.215077E+10 | 1343.25 | 01-NOV-09:09 |
December | 0.740776E+10 | 4621.63 | 01-DEC-10:09 | 0.223509E+10 | 1343.25 | 01-DEC-10:09 |
Annual Sum or Average | 0.871157E+11 | 0.262491E+11 | ||||
Minimum of Months | 0.668410E+10 | 4621.63 | 0.201408E+10 | 1343.25 | ||
Maximum of Months | 0.740776E+10 | 4621.63 | 0.223509E+10 | 1343.25 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.451584E+10 | 2827.07 | 01-JAN-10:09 | 0.111298E+10 | 671.63 | 01-JAN-10:09 |
February | 0.408193E+10 | 2827.07 | 01-FEB-10:09 | 0.100704E+10 | 671.63 | 01-FEB-10:09 |
March | 0.452026E+10 | 2827.07 | 01-MAR-10:09 | 0.111647E+10 | 671.63 | 01-MAR-10:09 |
April | 0.437489E+10 | 2827.07 | 01-APR-09:09 | 0.107874E+10 | 671.63 | 01-APR-09:09 |
May | 0.451584E+10 | 2827.07 | 01-MAY-09:09 | 0.111298E+10 | 671.63 | 01-MAY-09:09 |
June | 0.437556E+10 | 2827.07 | 01-JUN-09:09 | 0.108116E+10 | 671.63 | 01-JUN-09:09 |
July | 0.451952E+10 | 2827.07 | 01-JUL-09:09 | 0.111405E+10 | 671.63 | 01-JUL-09:09 |
August | 0.451617E+10 | 2827.07 | 01-AUG-09:09 | 0.111419E+10 | 671.63 | 01-AUG-09:09 |
September | 0.437891E+10 | 2827.07 | 01-SEP-09:09 | 0.108102E+10 | 671.63 | 01-SEP-09:09 |
October | 0.451584E+10 | 2827.07 | 01-OCT-09:09 | 0.111298E+10 | 671.63 | 01-OCT-09:09 |
November | 0.436230E+10 | 2827.07 | 01-NOV-09:09 | 0.107538E+10 | 671.63 | 01-NOV-09:09 |
December | 0.452388E+10 | 2827.07 | 01-DEC-10:09 | 0.111755E+10 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.532009E+11 | 0.131245E+11 | ||||
Minimum of Months | 0.408193E+10 | 2827.07 | 0.100704E+10 | 671.63 | ||
Maximum of Months | 0.452388E+10 | 2827.07 | 0.111755E+10 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.317044E+10 | 2555.22 | 01-JAN-10:09 | 0.879849E+09 | 671.63 | 01-JAN-10:09 |
February | 0.287181E+10 | 2555.22 | 01-FEB-09:09 | 0.796766E+09 | 671.63 | 01-FEB-09:09 |
March | 0.324295E+10 | 2555.22 | 01-MAR-09:09 | 0.898128E+09 | 671.63 | 01-MAR-09:09 |
April | 0.307694E+10 | 2555.22 | 01-APR-08:09 | 0.853677E+09 | 671.63 | 01-APR-08:09 |
May | 0.320669E+10 | 2555.22 | 01-MAY-08:09 | 0.888989E+09 | 671.63 | 01-MAY-08:09 |
June | 0.313132E+10 | 2555.22 | 01-JUN-08:09 | 0.867387E+09 | 671.63 | 01-JUN-08:09 |
July | 0.315231E+10 | 2555.22 | 01-JUL-08:09 | 0.875279E+09 | 671.63 | 01-JUL-08:09 |
August | 0.324295E+10 | 2555.22 | 01-AUG-08:09 | 0.898128E+09 | 671.63 | 01-AUG-08:09 |
September | 0.307694E+10 | 2555.22 | 01-SEP-08:09 | 0.853677E+09 | 671.63 | 01-SEP-08:09 |
October | 0.317044E+10 | 2555.22 | 01-OCT-09:09 | 0.879849E+09 | 671.63 | 01-OCT-09:09 |
November | 0.307694E+10 | 2555.22 | 01-NOV-08:09 | 0.853679E+09 | 671.63 | 01-NOV-08:09 |
December | 0.315231E+10 | 2555.22 | 01-DEC-09:09 | 0.875279E+09 | 671.63 | 01-DEC-09:09 |
Annual Sum or Average | 0.375720E+11 | 0.104207E+11 | ||||
Minimum of Months | 0.287181E+10 | 2555.22 | 0.796766E+09 | 671.63 | ||
Maximum of Months | 0.324295E+10 | 2555.22 | 0.898128E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.317044E+10 | 2555.22 | 01-JAN-10:09 | 0.879849E+09 | 671.63 | 01-JAN-10:09 |
February | 0.287181E+10 | 2555.22 | 01-FEB-09:09 | 0.796766E+09 | 671.63 | 01-FEB-09:09 |
March | 0.324295E+10 | 2555.22 | 01-MAR-09:09 | 0.898128E+09 | 671.63 | 01-MAR-09:09 |
April | 0.307694E+10 | 2555.22 | 01-APR-08:09 | 0.853677E+09 | 671.63 | 01-APR-08:09 |
May | 0.320669E+10 | 2555.22 | 01-MAY-08:09 | 0.888989E+09 | 671.63 | 01-MAY-08:09 |
June | 0.313132E+10 | 2555.22 | 01-JUN-08:09 | 0.867387E+09 | 671.63 | 01-JUN-08:09 |
July | 0.315231E+10 | 2555.22 | 01-JUL-08:09 | 0.875279E+09 | 671.63 | 01-JUL-08:09 |
August | 0.324295E+10 | 2555.22 | 01-AUG-08:09 | 0.898128E+09 | 671.63 | 01-AUG-08:09 |
September | 0.307694E+10 | 2555.22 | 01-SEP-08:09 | 0.853677E+09 | 671.63 | 01-SEP-08:09 |
October | 0.317044E+10 | 2555.22 | 01-OCT-09:09 | 0.879849E+09 | 671.63 | 01-OCT-09:09 |
November | 0.307694E+10 | 2555.22 | 01-NOV-08:09 | 0.853679E+09 | 671.63 | 01-NOV-08:09 |
December | 0.315231E+10 | 2555.22 | 01-DEC-09:09 | 0.875279E+09 | 671.63 | 01-DEC-09:09 |
Annual Sum or Average | 0.375720E+11 | 0.104207E+11 | ||||
Minimum of Months | 0.287181E+10 | 2555.22 | 0.796766E+09 | 671.63 | ||
Maximum of Months | 0.324295E+10 | 2555.22 | 0.898128E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.317044E+10 | 2555.22 | 01-JAN-10:09 | 0.879849E+09 | 671.63 | 01-JAN-10:09 |
February | 0.287181E+10 | 2555.22 | 01-FEB-09:09 | 0.796766E+09 | 671.63 | 01-FEB-09:09 |
March | 0.324295E+10 | 2555.22 | 01-MAR-09:09 | 0.898128E+09 | 671.63 | 01-MAR-09:09 |
April | 0.307694E+10 | 2555.22 | 01-APR-08:09 | 0.853677E+09 | 671.63 | 01-APR-08:09 |
May | 0.320669E+10 | 2555.22 | 01-MAY-08:09 | 0.888989E+09 | 671.63 | 01-MAY-08:09 |
June | 0.313132E+10 | 2555.22 | 01-JUN-08:09 | 0.867387E+09 | 671.63 | 01-JUN-08:09 |
July | 0.315231E+10 | 2555.22 | 01-JUL-08:09 | 0.875279E+09 | 671.63 | 01-JUL-08:09 |
August | 0.324295E+10 | 2555.22 | 01-AUG-08:09 | 0.898128E+09 | 671.63 | 01-AUG-08:09 |
September | 0.307694E+10 | 2555.22 | 01-SEP-08:09 | 0.853677E+09 | 671.63 | 01-SEP-08:09 |
October | 0.317044E+10 | 2555.22 | 01-OCT-09:09 | 0.879849E+09 | 671.63 | 01-OCT-09:09 |
November | 0.307694E+10 | 2555.22 | 01-NOV-08:09 | 0.853679E+09 | 671.63 | 01-NOV-08:09 |
December | 0.315231E+10 | 2555.22 | 01-DEC-09:09 | 0.875279E+09 | 671.63 | 01-DEC-09:09 |
Annual Sum or Average | 0.375720E+11 | 0.104207E+11 | ||||
Minimum of Months | 0.287181E+10 | 2555.22 | 0.796766E+09 | 671.63 | ||
Maximum of Months | 0.324295E+10 | 2555.22 | 0.898128E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.313454E+10 | 2726.96 | 01-JAN-11:09 | 0.161799E+10 | 1343.25 | 01-JAN-11:09 |
February | 0.283982E+10 | 2726.96 | 01-FEB-10:09 | 0.146554E+10 | 1343.25 | 01-FEB-10:09 |
March | 0.321092E+10 | 2726.96 | 01-MAR-10:09 | 0.165455E+10 | 1343.25 | 01-MAR-10:09 |
April | 0.304266E+10 | 2726.96 | 01-APR-09:09 | 0.157022E+10 | 1343.25 | 01-APR-09:09 |
May | 0.317273E+10 | 2726.96 | 01-MAY-09:09 | 0.163627E+10 | 1343.25 | 01-MAY-09:09 |
June | 0.309995E+10 | 2726.96 | 01-JUN-09:09 | 0.159764E+10 | 1343.25 | 01-JUN-09:09 |
July | 0.311545E+10 | 2726.96 | 01-JUL-09:09 | 0.160885E+10 | 1343.25 | 01-JUL-09:09 |
August | 0.321092E+10 | 2726.96 | 01-AUG-09:09 | 0.165455E+10 | 1343.25 | 01-AUG-09:09 |
September | 0.304266E+10 | 2726.96 | 01-SEP-09:09 | 0.157022E+10 | 1343.25 | 01-SEP-09:09 |
October | 0.313454E+10 | 2726.96 | 01-OCT-10:09 | 0.161799E+10 | 1343.25 | 01-OCT-10:09 |
November | 0.304266E+10 | 2726.96 | 01-NOV-09:09 | 0.157022E+10 | 1343.25 | 01-NOV-09:09 |
December | 0.311545E+10 | 2726.96 | 01-DEC-10:09 | 0.160885E+10 | 1343.25 | 01-DEC-10:09 |
Annual Sum or Average | 0.371623E+11 | 0.191729E+11 | ||||
Minimum of Months | 0.283982E+10 | 2726.96 | 0.146554E+10 | 1343.25 | ||
Maximum of Months | 0.321092E+10 | 2726.96 | 0.165455E+10 | 1343.25 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.161274E+10 | 1404.46 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.146111E+10 | 1404.46 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.165211E+10 | 1404.46 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.156548E+10 | 1404.46 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.163243E+10 | 1404.46 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.159501E+10 | 1404.46 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.160290E+10 | 1404.46 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.165211E+10 | 1404.46 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.156548E+10 | 1404.46 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.161274E+10 | 1404.46 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.156548E+10 | 1404.46 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.160290E+10 | 1404.46 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.191205E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.146111E+10 | 1404.46 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.165211E+10 | 1404.46 | 0.827277E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.161274E+10 | 1404.46 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.146111E+10 | 1404.46 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.165211E+10 | 1404.46 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.156548E+10 | 1404.46 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.163243E+10 | 1404.46 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.159501E+10 | 1404.46 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.160290E+10 | 1404.46 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.165211E+10 | 1404.46 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.156548E+10 | 1404.46 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.161274E+10 | 1404.46 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.156548E+10 | 1404.46 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.160290E+10 | 1404.46 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.191205E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.146111E+10 | 1404.46 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.165211E+10 | 1404.46 | 0.827277E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.161274E+10 | 1404.46 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.146111E+10 | 1404.46 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.165211E+10 | 1404.46 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.156548E+10 | 1404.46 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.163243E+10 | 1404.46 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.159501E+10 | 1404.46 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.160290E+10 | 1404.46 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.165211E+10 | 1404.46 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.156548E+10 | 1404.46 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.161274E+10 | 1404.46 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.156548E+10 | 1404.46 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.160290E+10 | 1404.46 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.191205E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.146111E+10 | 1404.46 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.165211E+10 | 1404.46 | 0.827277E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.161274E+10 | 1404.46 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.146111E+10 | 1404.46 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.165211E+10 | 1404.46 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.156548E+10 | 1404.46 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.163243E+10 | 1404.46 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.159501E+10 | 1404.46 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.160290E+10 | 1404.46 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.165211E+10 | 1404.46 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.156548E+10 | 1404.46 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.161274E+10 | 1404.46 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.156548E+10 | 1404.46 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.160290E+10 | 1404.46 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.191205E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.146111E+10 | 1404.46 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.165211E+10 | 1404.46 | 0.827277E+09 | 671.63 |
Report: SpaceGainsMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.338624E+10 | 0.739462E+10 | 0.222596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 70559410.72 | 0.256398E+10 |
February | 0.305697E+10 | 0.668410E+10 | 0.201408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122072E+09 | 0.186926E+10 |
March | 0.335708E+10 | 0.740180E+10 | 0.223295E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.266935E+09 | 0.164106E+10 |
April | 0.327081E+10 | 0.716384E+10 | 0.215748E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.755986E+09 | 0.583041E+09 |
May | 0.336680E+10 | 0.739462E+10 | 0.222596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.217091E+10 | 25022052.82 |
June | 0.325380E+10 | 0.716485E+10 | 0.216232E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.234830E+10 | 20737065.29 |
July | 0.339353E+10 | 0.740069E+10 | 0.222811E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.228215E+10 | 13750194.47 |
August | 0.334857E+10 | 0.739513E+10 | 0.222838E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.233773E+10 | 33372202.93 |
September | 0.327932E+10 | 0.717041E+10 | 0.216205E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166185E+10 | 67194643.31 |
October | 0.338624E+10 | 0.739462E+10 | 0.222596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153538E+10 | 0.365335E+09 |
November | 0.327446E+10 | 0.714323E+10 | 0.215077E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.373077E+09 | 0.117287E+10 |
December | 0.340325E+10 | 0.740776E+10 | 0.223509E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.242261E+09 | 0.221620E+10 |
Annual Sum or Average | 0.397770E+11 | 0.871157E+11 | 0.262491E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141672E+11 | 0.105718E+11 |
Minimum of Months | 0.305697E+10 | 0.668410E+10 | 0.201408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 70559410.72 | 13750194.47 |
Maximum of Months | 0.340325E+10 | 0.740776E+10 | 0.223509E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.234830E+10 | 0.256398E+10 |
Report: SpaceGainsMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.169307E+10 | 0.451584E+10 | 0.111298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39886720.80 | 0.138197E+10 |
February | 0.152844E+10 | 0.408193E+10 | 0.100704E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 68878477.47 | 0.100090E+10 |
March | 0.167849E+10 | 0.452026E+10 | 0.111647E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150067E+09 | 0.859623E+09 |
April | 0.163536E+10 | 0.437489E+10 | 0.107874E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.426545E+09 | 0.290714E+09 |
May | 0.168335E+10 | 0.451584E+10 | 0.111298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121924E+10 | 8725658.56 |
June | 0.162685E+10 | 0.437556E+10 | 0.108116E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132142E+10 | 6701974.77 |
July | 0.169671E+10 | 0.451952E+10 | 0.111405E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127919E+10 | 6075168.62 |
August | 0.167424E+10 | 0.451617E+10 | 0.111419E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131012E+10 | 10941066.12 |
September | 0.163961E+10 | 0.437891E+10 | 0.108102E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.929161E+09 | 26421000.09 |
October | 0.169307E+10 | 0.451584E+10 | 0.111298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.858986E+09 | 0.160298E+09 |
November | 0.163718E+10 | 0.436230E+10 | 0.107538E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.210865E+09 | 0.598627E+09 |
December | 0.170157E+10 | 0.452388E+10 | 0.111755E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137010E+09 | 0.116324E+10 |
Annual Sum or Average | 0.198880E+11 | 0.532009E+11 | 0.131245E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.795137E+10 | 0.551423E+10 |
Minimum of Months | 0.152844E+10 | 0.408193E+10 | 0.100704E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39886720.80 | 6075168.62 |
Maximum of Months | 0.170157E+10 | 0.452388E+10 | 0.111755E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132142E+10 | 0.138197E+10 |
Report: SpaceGainsMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.317044E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 39887466.31 | 0.138065E+10 |
February | 0.914877E+09 | 0.287181E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 68805970.55 | 0.100934E+10 |
March | 0.103395E+10 | 0.324295E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147779E+09 | 0.874284E+09 |
April | 0.984131E+09 | 0.307694E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.421380E+09 | 0.306177E+09 |
May | 0.102058E+10 | 0.320669E+10 | 0.888989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119600E+10 | 12782100.17 |
June | 0.998711E+09 | 0.313132E+10 | 0.867387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130174E+10 | 9936566.60 |
July | 0.100600E+10 | 0.315231E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125072E+10 | 7658997.19 |
August | 0.103395E+10 | 0.324295E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129192E+10 | 18649083.45 |
September | 0.984131E+09 | 0.307694E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.905231E+09 | 36351297.67 |
October | 0.100722E+10 | 0.317044E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.838071E+09 | 0.176435E+09 |
November | 0.973196E+09 | 0.307694E+10 | 0.853679E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.207896E+09 | 0.614239E+09 |
December | 0.100600E+10 | 0.315231E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136539E+09 | 0.117693E+10 |
Annual Sum or Average | 0.119700E+11 | 0.375720E+11 | 0.104207E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.780596E+10 | 0.562343E+10 |
Minimum of Months | 0.914877E+09 | 0.287181E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 39887466.31 | 7658997.19 |
Maximum of Months | 0.103395E+10 | 0.324295E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130174E+10 | 0.138065E+10 |
Report: SpaceGainsMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.317044E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 39887461.79 | 0.136613E+10 |
February | 0.914877E+09 | 0.287181E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 68805964.90 | 0.100082E+10 |
March | 0.103395E+10 | 0.324295E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147788E+09 | 0.867805E+09 |
April | 0.984131E+09 | 0.307694E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.421377E+09 | 0.305504E+09 |
May | 0.102058E+10 | 0.320669E+10 | 0.888989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119579E+10 | 13076681.45 |
June | 0.998711E+09 | 0.313132E+10 | 0.867387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130150E+10 | 10230808.21 |
July | 0.100600E+10 | 0.315231E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125021E+10 | 7966472.73 |
August | 0.103395E+10 | 0.324295E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129159E+10 | 19117677.49 |
September | 0.984131E+09 | 0.307694E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.904862E+09 | 36870774.65 |
October | 0.100722E+10 | 0.317044E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.837981E+09 | 0.177020E+09 |
November | 0.973196E+09 | 0.307694E+10 | 0.853679E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.207899E+09 | 0.612862E+09 |
December | 0.100600E+10 | 0.315231E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136541E+09 | 0.116981E+10 |
Annual Sum or Average | 0.119700E+11 | 0.375720E+11 | 0.104207E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.780422E+10 | 0.558720E+10 |
Minimum of Months | 0.914877E+09 | 0.287181E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 39887461.79 | 7966472.73 |
Maximum of Months | 0.103395E+10 | 0.324295E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130150E+10 | 0.136613E+10 |
Report: SpaceGainsMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.317044E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 39887456.24 | 0.134604E+10 |
February | 0.914877E+09 | 0.287181E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 68805957.46 | 0.987184E+09 |
March | 0.103395E+10 | 0.324295E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147814E+09 | 0.855282E+09 |
April | 0.984131E+09 | 0.307694E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.421472E+09 | 0.303262E+09 |
May | 0.102058E+10 | 0.320669E+10 | 0.888989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119644E+10 | 11805650.89 |
June | 0.998711E+09 | 0.313132E+10 | 0.867387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130204E+10 | 9349360.45 |
July | 0.100600E+10 | 0.315231E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125112E+10 | 7296862.66 |
August | 0.103395E+10 | 0.324295E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129217E+10 | 17835914.25 |
September | 0.984131E+09 | 0.307694E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.905366E+09 | 35491182.97 |
October | 0.100722E+10 | 0.317044E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.838291E+09 | 0.174896E+09 |
November | 0.973196E+09 | 0.307694E+10 | 0.853679E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.207918E+09 | 0.609183E+09 |
December | 0.100600E+10 | 0.315231E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136544E+09 | 0.115868E+10 |
Annual Sum or Average | 0.119700E+11 | 0.375720E+11 | 0.104207E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.780787E+10 | 0.551631E+10 |
Minimum of Months | 0.914877E+09 | 0.287181E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 39887456.24 | 7296862.66 |
Maximum of Months | 0.103395E+10 | 0.324295E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130204E+10 | 0.134604E+10 |
Report: SpaceGainsMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.344359E+10 | 0.313454E+10 | 0.161799E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 69893202.60 | 0.236495E+10 |
February | 0.313522E+10 | 0.283982E+10 | 0.146554E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120602E+09 | 0.173314E+10 |
March | 0.355148E+10 | 0.321092E+10 | 0.165455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.259398E+09 | 0.150894E+10 |
April | 0.338259E+10 | 0.304266E+10 | 0.157022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.739184E+09 | 0.543625E+09 |
May | 0.349753E+10 | 0.317273E+10 | 0.163627E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.210082E+10 | 20231081.69 |
June | 0.343071E+10 | 0.309995E+10 | 0.159764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.228571E+10 | 16622099.37 |
July | 0.344942E+10 | 0.311545E+10 | 0.160885E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219701E+10 | 12191568.68 |
August | 0.355148E+10 | 0.321092E+10 | 0.165455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.226976E+10 | 31175802.00 |
September | 0.338259E+10 | 0.304266E+10 | 0.157022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158968E+10 | 64264913.90 |
October | 0.344359E+10 | 0.313454E+10 | 0.161799E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147345E+10 | 0.325430E+09 |
November | 0.331698E+10 | 0.304266E+10 | 0.157022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.364566E+09 | 0.108723E+10 |
December | 0.344942E+10 | 0.311545E+10 | 0.160885E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.239261E+09 | 0.204771E+10 |
Annual Sum or Average | 0.410346E+11 | 0.371623E+11 | 0.191729E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137093E+11 | 0.975550E+10 |
Minimum of Months | 0.313522E+10 | 0.283982E+10 | 0.146554E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 69893202.60 | 12191568.68 |
Maximum of Months | 0.355148E+10 | 0.321092E+10 | 0.165455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.228571E+10 | 0.236495E+10 |
Report: SpaceGainsMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.161274E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 39887454.00 | 0.131609E+10 |
February | 0.156756E+10 | 0.146111E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 68807774.26 | 0.965189E+09 |
March | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147915E+09 | 0.835312E+09 |
April | 0.169125E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.421871E+09 | 0.301285E+09 |
May | 0.174872E+10 | 0.163243E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119839E+10 | 9726155.19 |
June | 0.171530E+10 | 0.159501E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130410E+10 | 7978672.98 |
July | 0.172466E+10 | 0.160290E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125314E+10 | 6301507.63 |
August | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129422E+10 | 15276355.54 |
September | 0.169125E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.906249E+09 | 33107477.96 |
October | 0.172174E+10 | 0.161274E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.840132E+09 | 0.175562E+09 |
November | 0.165844E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.208048E+09 | 0.605589E+09 |
December | 0.172466E+10 | 0.160290E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136552E+09 | 0.114168E+10 |
Annual Sum or Average | 0.205167E+11 | 0.191205E+11 | 0.958644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.781931E+10 | 0.541310E+10 |
Minimum of Months | 0.156756E+10 | 0.146111E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 39887454.00 | 6301507.63 |
Maximum of Months | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130410E+10 | 0.131609E+10 |
Report: SpaceGainsMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.161274E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 39887452.27 | 0.130980E+10 |
February | 0.156756E+10 | 0.146111E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 68808012.64 | 0.960123E+09 |
March | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147925E+09 | 0.830871E+09 |
April | 0.169125E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.421901E+09 | 0.300291E+09 |
May | 0.174872E+10 | 0.163243E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119861E+10 | 9497453.91 |
June | 0.171530E+10 | 0.159501E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130428E+10 | 7840610.78 |
July | 0.172466E+10 | 0.160290E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125340E+10 | 6218664.51 |
August | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129436E+10 | 15085080.94 |
September | 0.169125E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.906386E+09 | 32876457.53 |
October | 0.172174E+10 | 0.161274E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.840230E+09 | 0.175013E+09 |
November | 0.165844E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.208056E+09 | 0.603984E+09 |
December | 0.172466E+10 | 0.160290E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136553E+09 | 0.113708E+10 |
Annual Sum or Average | 0.205167E+11 | 0.191205E+11 | 0.958644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.782039E+10 | 0.538868E+10 |
Minimum of Months | 0.156756E+10 | 0.146111E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 39887452.27 | 6218664.51 |
Maximum of Months | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130428E+10 | 0.130980E+10 |
Report: SpaceGainsMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.161274E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 39887446.80 | 0.129551E+10 |
February | 0.156756E+10 | 0.146111E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 68808497.07 | 0.947931E+09 |
March | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147948E+09 | 0.819423E+09 |
April | 0.169125E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.421948E+09 | 0.296753E+09 |
May | 0.174872E+10 | 0.163243E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119908E+10 | 8767351.62 |
June | 0.171530E+10 | 0.159501E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130455E+10 | 7465590.82 |
July | 0.172466E+10 | 0.160290E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125365E+10 | 6016619.30 |
August | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129442E+10 | 14782970.55 |
September | 0.169125E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.906351E+09 | 32399995.60 |
October | 0.172174E+10 | 0.161274E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.840285E+09 | 0.173653E+09 |
November | 0.165844E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.208067E+09 | 0.599659E+09 |
December | 0.172466E+10 | 0.160290E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136554E+09 | 0.112552E+10 |
Annual Sum or Average | 0.205167E+11 | 0.191205E+11 | 0.958644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.782155E+10 | 0.532788E+10 |
Minimum of Months | 0.156756E+10 | 0.146111E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 39887446.80 | 6016619.30 |
Maximum of Months | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130455E+10 | 0.129551E+10 |
Report: SpaceGainsMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.161274E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 40553943.45 | 0.152558E+10 |
February | 0.156756E+10 | 0.146111E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 70151710.53 | 0.110007E+10 |
March | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151598E+09 | 0.992106E+09 |
April | 0.169125E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.429513E+09 | 0.366558E+09 |
May | 0.174872E+10 | 0.163243E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123069E+10 | 18034023.11 |
June | 0.171530E+10 | 0.159501E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133450E+10 | 17211496.12 |
July | 0.172466E+10 | 0.160290E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128754E+10 | 10200863.73 |
August | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133021E+10 | 34590577.82 |
September | 0.169125E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.933626E+09 | 61701693.25 |
October | 0.172174E+10 | 0.161274E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.864388E+09 | 0.263626E+09 |
November | 0.165844E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.211486E+09 | 0.727833E+09 |
December | 0.172466E+10 | 0.160290E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138744E+09 | 0.132960E+10 |
Annual Sum or Average | 0.205167E+11 | 0.191205E+11 | 0.958644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.802300E+10 | 0.644711E+10 |
Minimum of Months | 0.156756E+10 | 0.146111E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 40553943.45 | 10200863.73 |
Maximum of Months | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133450E+10 | 0.152558E+10 |
Report: PeakSpaceGainsMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 4050.04 | 01-JAN-13:09 | 4621.63 | 01-JAN-10:09 | 1343.25 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1459.20 | 16-JAN-15:00 | 7668.65 | 04-JAN-18:00 |
February | 4050.04 | 03-FEB-13:09 | 4621.63 | 01-FEB-10:09 | 1343.25 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2107.21 | 02-FEB-13:00 | 8462.73 | 04-FEB-18:00 |
March | 4050.04 | 03-MAR-13:09 | 4621.63 | 01-MAR-10:09 | 1343.25 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2854.25 | 26-MAR-14:00 | 7632.19 | 11-MAR-12:10 |
April | 4050.04 | 01-APR-12:09 | 4621.63 | 01-APR-09:09 | 1343.25 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4371.43 | 28-APR-15:00 | 3404.57 | 02-APR-11:10 |
May | 4050.04 | 05-MAY-12:09 | 4621.63 | 01-MAY-09:09 | 1343.25 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4660.72 | 07-MAY-14:00 | 524.52 | 31-MAY-13:00 |
June | 4050.04 | 02-JUN-12:09 | 4621.63 | 01-JUN-09:09 | 1343.25 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5074.35 | 14-JUN-14:00 | 534.24 | 01-JUN-13:00 |
July | 4050.04 | 01-JUL-12:09 | 4621.63 | 01-JUL-09:09 | 1343.25 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5552.73 | 22-JUL-16:00 | 529.81 | 12-JUL-15:00 |
August | 4050.04 | 04-AUG-12:09 | 4621.63 | 01-AUG-09:09 | 1343.25 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5648.88 | 30-AUG-16:00 | 1008.29 | 16-AUG-17:00 |
September | 4050.04 | 01-SEP-12:09 | 4621.63 | 01-SEP-09:09 | 1343.25 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5771.84 | 09-SEP-17:00 | 1979.94 | 07-SEP-17:00 |
October | 4050.04 | 01-OCT-12:09 | 4621.63 | 01-OCT-09:09 | 1343.25 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4643.30 | 05-OCT-15:00 | 3395.49 | 27-OCT-16:00 |
November | 4050.04 | 03-NOV-12:09 | 4621.63 | 01-NOV-09:09 | 1343.25 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2838.21 | 01-NOV-14:00 | 6028.84 | 15-NOV-18:00 |
December | 4050.04 | 01-DEC-13:09 | 4621.63 | 01-DEC-10:09 | 1343.25 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2866.44 | 13-DEC-15:00 | 8685.40 | 20-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 4050.04 | 4621.63 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 1459.20 | 524.52 | |||||
Maximum of Months | 4050.04 | 4621.63 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 5771.84 | 8685.40 |
Report: PeakSpaceGainsMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 01-JAN-13:09 | 2827.07 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 827.14 | 16-JAN-15:00 | 4346.94 | 04-JAN-18:00 |
February | 2024.96 | 03-FEB-13:09 | 2827.07 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1179.68 | 02-FEB-13:00 | 4744.68 | 04-FEB-18:00 |
March | 2024.96 | 03-MAR-13:09 | 2827.07 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1615.89 | 26-MAR-14:00 | 4292.50 | 11-MAR-12:10 |
April | 2024.96 | 01-APR-12:09 | 2827.07 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2466.24 | 28-APR-15:00 | 1961.01 | 02-APR-11:10 |
May | 2024.96 | 05-MAY-12:09 | 2827.07 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2629.46 | 07-MAY-14:00 | 296.85 | 31-MAY-13:00 |
June | 2024.96 | 02-JUN-12:09 | 2827.07 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2880.95 | 14-JUN-14:00 | 299.45 | 01-JUN-13:00 |
July | 2024.96 | 01-JUL-12:09 | 2827.07 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3158.61 | 22-JUL-16:00 | 298.90 | 12-JUL-15:00 |
August | 2024.96 | 04-AUG-12:09 | 2827.07 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3204.08 | 30-AUG-16:00 | 570.82 | 16-AUG-17:00 |
September | 2024.96 | 01-SEP-12:09 | 2827.07 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3253.27 | 09-SEP-17:00 | 1121.25 | 07-SEP-17:00 |
October | 2024.96 | 01-OCT-12:09 | 2827.07 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2632.03 | 05-OCT-15:00 | 1915.64 | 27-OCT-16:00 |
November | 2024.96 | 03-NOV-12:09 | 2827.07 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1611.87 | 01-NOV-14:00 | 3482.07 | 15-NOV-18:00 |
December | 2024.96 | 01-DEC-13:09 | 2827.07 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1622.26 | 13-DEC-15:00 | 4940.59 | 20-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 2827.07 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 827.14 | 296.85 | |||||
Maximum of Months | 2024.96 | 2827.07 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 3253.27 | 4940.59 |
Report: PeakSpaceGainsMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 2555.22 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 827.14 | 16-JAN-15:00 | 4346.94 | 04-JAN-18:00 |
February | 2024.96 | 04-FEB-13:09 | 2555.22 | 01-FEB-09:09 | 671.63 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1179.68 | 02-FEB-13:00 | 4744.95 | 04-FEB-18:00 |
March | 2024.96 | 04-MAR-13:09 | 2555.22 | 01-MAR-09:09 | 671.63 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1615.86 | 26-MAR-14:00 | 4292.50 | 11-MAR-12:10 |
April | 2024.96 | 01-APR-12:09 | 2555.22 | 01-APR-08:09 | 671.63 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2466.32 | 28-APR-15:00 | 1950.12 | 02-APR-11:10 |
May | 2024.96 | 06-MAY-12:09 | 2555.22 | 01-MAY-08:09 | 671.63 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2629.41 | 07-MAY-14:00 | 296.85 | 31-MAY-13:00 |
June | 2024.96 | 03-JUN-12:09 | 2555.22 | 01-JUN-08:09 | 671.63 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2880.95 | 14-JUN-14:00 | 299.45 | 01-JUN-13:00 |
July | 2024.96 | 01-JUL-12:09 | 2555.22 | 01-JUL-08:09 | 671.63 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3158.61 | 22-JUL-16:00 | 298.90 | 12-JUL-15:00 |
August | 2024.96 | 05-AUG-12:09 | 2555.22 | 01-AUG-08:09 | 671.63 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3204.08 | 30-AUG-16:00 | 570.82 | 16-AUG-17:00 |
September | 2024.96 | 02-SEP-12:09 | 2555.22 | 01-SEP-08:09 | 671.63 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3253.27 | 09-SEP-17:00 | 1121.25 | 07-SEP-17:00 |
October | 2024.96 | 07-OCT-12:09 | 2555.22 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2632.03 | 05-OCT-15:00 | 1915.65 | 27-OCT-16:00 |
November | 2024.96 | 04-NOV-12:09 | 2555.22 | 01-NOV-08:09 | 671.63 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1612.02 | 01-NOV-14:00 | 3443.83 | 15-NOV-18:00 |
December | 2024.96 | 02-DEC-13:09 | 2555.22 | 01-DEC-09:09 | 671.63 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1622.22 | 13-DEC-15:00 | 4940.59 | 20-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 2555.22 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 827.14 | 296.85 | |||||
Maximum of Months | 2024.96 | 2555.22 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 3253.27 | 4940.59 |
Report: PeakSpaceGainsMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 2555.22 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 827.14 | 16-JAN-15:00 | 4346.94 | 04-JAN-18:00 |
February | 2024.96 | 04-FEB-13:09 | 2555.22 | 01-FEB-09:09 | 671.63 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1179.68 | 02-FEB-13:00 | 4744.95 | 04-FEB-18:00 |
March | 2024.96 | 04-MAR-13:09 | 2555.22 | 01-MAR-09:09 | 671.63 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1615.85 | 26-MAR-14:00 | 4292.50 | 11-MAR-12:10 |
April | 2024.96 | 01-APR-12:09 | 2555.22 | 01-APR-08:09 | 671.63 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2466.33 | 28-APR-15:00 | 1945.28 | 02-APR-11:10 |
May | 2024.96 | 06-MAY-12:09 | 2555.22 | 01-MAY-08:09 | 671.63 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2629.08 | 07-MAY-14:00 | 296.85 | 31-MAY-13:00 |
June | 2024.96 | 03-JUN-12:09 | 2555.22 | 01-JUN-08:09 | 671.63 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2880.95 | 14-JUN-14:00 | 299.45 | 01-JUN-13:00 |
July | 2024.96 | 01-JUL-12:09 | 2555.22 | 01-JUL-08:09 | 671.63 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3158.61 | 22-JUL-16:00 | 298.90 | 12-JUL-15:00 |
August | 2024.96 | 05-AUG-12:09 | 2555.22 | 01-AUG-08:09 | 671.63 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3204.08 | 30-AUG-16:00 | 570.82 | 16-AUG-17:00 |
September | 2024.96 | 02-SEP-12:09 | 2555.22 | 01-SEP-08:09 | 671.63 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3253.27 | 09-SEP-17:00 | 1121.25 | 07-SEP-17:00 |
October | 2024.96 | 07-OCT-12:09 | 2555.22 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2632.03 | 05-OCT-15:00 | 1915.65 | 27-OCT-16:00 |
November | 2024.96 | 04-NOV-12:09 | 2555.22 | 01-NOV-08:09 | 671.63 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1612.04 | 01-NOV-14:00 | 3427.21 | 15-NOV-18:00 |
December | 2024.96 | 02-DEC-13:09 | 2555.22 | 01-DEC-09:09 | 671.63 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1622.21 | 13-DEC-15:00 | 4940.59 | 20-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 2555.22 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 827.14 | 296.85 | |||||
Maximum of Months | 2024.96 | 2555.22 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 3253.27 | 4940.59 |
Report: PeakSpaceGainsMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 2555.22 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 827.14 | 16-JAN-15:00 | 4346.94 | 04-JAN-18:00 |
February | 2024.96 | 04-FEB-13:09 | 2555.22 | 01-FEB-09:09 | 671.63 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1179.68 | 02-FEB-13:00 | 4744.95 | 04-FEB-18:00 |
March | 2024.96 | 04-MAR-13:09 | 2555.22 | 01-MAR-09:09 | 671.63 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1615.84 | 26-MAR-14:00 | 4292.50 | 11-MAR-12:10 |
April | 2024.96 | 01-APR-12:09 | 2555.22 | 01-APR-08:09 | 671.63 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2466.35 | 28-APR-15:00 | 1932.51 | 02-APR-11:10 |
May | 2024.96 | 06-MAY-12:09 | 2555.22 | 01-MAY-08:09 | 671.63 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2629.09 | 07-MAY-14:00 | 296.85 | 31-MAY-13:00 |
June | 2024.96 | 03-JUN-12:09 | 2555.22 | 01-JUN-08:09 | 671.63 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2880.95 | 14-JUN-14:00 | 299.45 | 01-JUN-13:00 |
July | 2024.96 | 01-JUL-12:09 | 2555.22 | 01-JUL-08:09 | 671.63 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3158.61 | 22-JUL-16:00 | 298.90 | 12-JUL-15:00 |
August | 2024.96 | 05-AUG-12:09 | 2555.22 | 01-AUG-08:09 | 671.63 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3204.08 | 30-AUG-16:00 | 570.82 | 16-AUG-17:00 |
September | 2024.96 | 02-SEP-12:09 | 2555.22 | 01-SEP-08:09 | 671.63 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3253.27 | 09-SEP-17:00 | 1121.25 | 07-SEP-17:00 |
October | 2024.96 | 07-OCT-12:09 | 2555.22 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2632.03 | 05-OCT-15:00 | 1915.65 | 27-OCT-16:00 |
November | 2024.96 | 04-NOV-12:09 | 2555.22 | 01-NOV-08:09 | 671.63 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1612.07 | 01-NOV-14:00 | 3391.35 | 15-NOV-18:00 |
December | 2024.96 | 02-DEC-13:09 | 2555.22 | 01-DEC-09:09 | 671.63 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1622.20 | 13-DEC-15:00 | 4940.59 | 20-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 2555.22 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 827.14 | 296.85 | |||||
Maximum of Months | 2024.96 | 2555.22 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 3253.27 | 4940.59 |
Report: PeakSpaceGainsMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 5400.05 | 07-JAN-15:09 | 2726.96 | 01-JAN-11:09 | 1343.25 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1448.80 | 16-JAN-15:00 | 7613.97 | 04-JAN-18:00 |
February | 5400.05 | 04-FEB-15:09 | 2726.96 | 01-FEB-10:09 | 1343.25 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2070.02 | 02-FEB-13:00 | 8324.27 | 04-FEB-18:00 |
March | 5400.05 | 04-MAR-15:09 | 2726.96 | 01-MAR-10:09 | 1343.25 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2830.81 | 26-MAR-14:00 | 7527.14 | 11-MAR-12:10 |
April | 5400.05 | 01-APR-14:09 | 2726.96 | 01-APR-09:09 | 1343.25 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4322.47 | 28-APR-15:00 | 3272.85 | 01-APR-17:00 |
May | 5400.05 | 06-MAY-14:09 | 2726.96 | 01-MAY-09:09 | 1343.25 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4608.83 | 07-MAY-14:00 | 520.08 | 31-MAY-13:00 |
June | 5400.05 | 03-JUN-14:09 | 2726.96 | 01-JUN-09:09 | 1343.25 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5045.04 | 14-JUN-14:00 | 525.36 | 01-JUN-13:00 |
July | 5400.05 | 01-JUL-14:09 | 2726.96 | 01-JUL-09:09 | 1343.25 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5529.73 | 22-JUL-16:00 | 523.91 | 12-JUL-15:00 |
August | 5400.05 | 05-AUG-14:09 | 2726.96 | 01-AUG-09:09 | 1343.25 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5611.65 | 30-AUG-16:00 | 1000.01 | 16-AUG-17:00 |
September | 5400.05 | 02-SEP-14:09 | 2726.96 | 01-SEP-09:09 | 1343.25 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5702.99 | 09-SEP-17:00 | 1964.22 | 07-SEP-17:00 |
October | 5400.05 | 07-OCT-14:09 | 2726.96 | 01-OCT-10:09 | 1343.25 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4610.19 | 05-OCT-15:00 | 3357.64 | 27-OCT-16:00 |
November | 5400.05 | 04-NOV-14:09 | 2726.96 | 01-NOV-09:09 | 1343.25 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2822.71 | 01-NOV-14:00 | 5788.04 | 15-NOV-18:00 |
December | 5400.05 | 02-DEC-15:09 | 2726.96 | 01-DEC-10:09 | 1343.25 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2842.11 | 13-DEC-15:00 | 8649.42 | 20-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 5400.05 | 2726.96 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 1448.80 | 520.08 | |||||
Maximum of Months | 5400.05 | 2726.96 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 5702.99 | 8649.42 |
Report: PeakSpaceGainsMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1404.46 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 827.14 | 16-JAN-15:00 | 4346.94 | 04-JAN-18:00 |
February | 2699.95 | 04-FEB-15:09 | 1404.46 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1179.68 | 02-FEB-13:00 | 4744.95 | 04-FEB-18:00 |
March | 2699.95 | 04-MAR-15:09 | 1404.46 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1615.85 | 26-MAR-14:00 | 4292.50 | 11-MAR-12:10 |
April | 2699.95 | 01-APR-14:09 | 1404.46 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2466.39 | 28-APR-15:00 | 1860.07 | 01-APR-17:00 |
May | 2699.95 | 06-MAY-14:09 | 1404.46 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2629.46 | 07-MAY-14:00 | 296.85 | 31-MAY-13:00 |
June | 2699.95 | 03-JUN-14:09 | 1404.46 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2880.95 | 14-JUN-14:00 | 299.45 | 01-JUN-13:00 |
July | 2699.95 | 01-JUL-14:09 | 1404.46 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3158.61 | 22-JUL-16:00 | 298.90 | 12-JUL-15:00 |
August | 2699.95 | 05-AUG-14:09 | 1404.46 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3204.08 | 30-AUG-16:00 | 570.82 | 16-AUG-17:00 |
September | 2699.95 | 02-SEP-14:09 | 1404.46 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3253.27 | 09-SEP-17:00 | 1121.25 | 07-SEP-17:00 |
October | 2699.95 | 07-OCT-14:09 | 1404.46 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2632.03 | 05-OCT-15:00 | 1915.64 | 27-OCT-16:00 |
November | 2699.95 | 04-NOV-14:09 | 1404.46 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1611.97 | 01-NOV-14:00 | 3287.09 | 15-NOV-18:00 |
December | 2699.95 | 02-DEC-15:09 | 1404.46 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1622.24 | 13-DEC-15:00 | 4940.59 | 20-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 827.14 | 296.85 | |||||
Maximum of Months | 2699.95 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 3253.27 | 4940.59 |
Report: PeakSpaceGainsMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1404.46 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 827.14 | 16-JAN-15:00 | 4346.94 | 04-JAN-18:00 |
February | 2699.95 | 04-FEB-15:09 | 1404.46 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1179.68 | 02-FEB-13:00 | 4744.95 | 04-FEB-18:00 |
March | 2699.95 | 04-MAR-15:09 | 1404.46 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1615.85 | 26-MAR-14:00 | 4292.50 | 11-MAR-12:10 |
April | 2699.95 | 01-APR-14:09 | 1404.46 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2466.39 | 28-APR-15:00 | 1856.08 | 01-APR-17:00 |
May | 2699.95 | 06-MAY-14:09 | 1404.46 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2629.46 | 07-MAY-14:00 | 296.85 | 31-MAY-13:00 |
June | 2699.95 | 03-JUN-14:09 | 1404.46 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2880.95 | 14-JUN-14:00 | 299.45 | 01-JUN-13:00 |
July | 2699.95 | 01-JUL-14:09 | 1404.46 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3158.61 | 22-JUL-16:00 | 298.90 | 12-JUL-15:00 |
August | 2699.95 | 05-AUG-14:09 | 1404.46 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3204.08 | 30-AUG-16:00 | 570.82 | 16-AUG-17:00 |
September | 2699.95 | 02-SEP-14:09 | 1404.46 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3253.27 | 09-SEP-17:00 | 1121.25 | 07-SEP-17:00 |
October | 2699.95 | 07-OCT-14:09 | 1404.46 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2632.03 | 05-OCT-15:00 | 1915.64 | 27-OCT-16:00 |
November | 2699.95 | 04-NOV-14:09 | 1404.46 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1611.97 | 01-NOV-14:00 | 3271.81 | 15-NOV-18:00 |
December | 2699.95 | 02-DEC-15:09 | 1404.46 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1622.23 | 13-DEC-15:00 | 4940.59 | 20-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 827.14 | 296.85 | |||||
Maximum of Months | 2699.95 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 3253.27 | 4940.59 |
Report: PeakSpaceGainsMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1404.46 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 827.14 | 16-JAN-15:00 | 4346.94 | 04-JAN-18:00 |
February | 2699.95 | 04-FEB-15:09 | 1404.46 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1179.68 | 02-FEB-13:00 | 4744.95 | 04-FEB-18:00 |
March | 2699.95 | 04-MAR-15:09 | 1404.46 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1616.11 | 26-MAR-14:00 | 4292.50 | 11-MAR-12:10 |
April | 2699.95 | 01-APR-14:09 | 1404.46 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2466.09 | 28-APR-15:00 | 1846.15 | 01-APR-17:00 |
May | 2699.95 | 06-MAY-14:09 | 1404.46 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2629.46 | 07-MAY-14:00 | 296.85 | 31-MAY-13:00 |
June | 2699.95 | 03-JUN-14:09 | 1404.46 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2880.95 | 14-JUN-14:00 | 299.45 | 01-JUN-13:00 |
July | 2699.95 | 01-JUL-14:09 | 1404.46 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3158.61 | 22-JUL-16:00 | 298.90 | 12-JUL-15:00 |
August | 2699.95 | 05-AUG-14:09 | 1404.46 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3204.08 | 30-AUG-16:00 | 570.82 | 16-AUG-17:00 |
September | 2699.95 | 02-SEP-14:09 | 1404.46 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3253.27 | 09-SEP-17:00 | 1121.25 | 07-SEP-17:00 |
October | 2699.95 | 07-OCT-14:09 | 1404.46 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2632.03 | 05-OCT-15:00 | 1915.64 | 27-OCT-16:00 |
November | 2699.95 | 04-NOV-14:09 | 1404.46 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1612.01 | 01-NOV-14:00 | 3239.52 | 15-NOV-18:00 |
December | 2699.95 | 02-DEC-15:09 | 1404.46 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1622.22 | 13-DEC-15:00 | 4940.59 | 20-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 827.14 | 296.85 | |||||
Maximum of Months | 2699.95 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 3253.27 | 4940.59 |
Report: PeakSpaceGainsMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1404.46 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 837.55 | 16-JAN-15:00 | 4401.62 | 04-JAN-18:00 |
February | 2699.95 | 04-FEB-15:09 | 1404.46 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1216.86 | 02-FEB-13:00 | 4883.41 | 04-FEB-18:00 |
March | 2699.95 | 04-MAR-15:09 | 1404.46 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1639.54 | 26-MAR-14:00 | 4397.55 | 11-MAR-12:10 |
April | 2699.95 | 01-APR-14:09 | 1404.46 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2515.01 | 28-APR-15:00 | 1900.06 | 01-APR-17:00 |
May | 2699.95 | 06-MAY-14:09 | 1404.46 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2681.02 | 07-MAY-14:00 | 301.30 | 31-MAY-13:00 |
June | 2699.95 | 03-JUN-14:09 | 1404.46 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2910.27 | 14-JUN-14:00 | 308.33 | 01-JUN-13:00 |
July | 2699.95 | 01-JUL-14:09 | 1404.46 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3181.61 | 22-JUL-16:00 | 304.80 | 12-JUL-15:00 |
August | 2699.95 | 05-AUG-14:09 | 1404.46 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3241.30 | 30-AUG-16:00 | 579.09 | 16-AUG-17:00 |
September | 2699.95 | 02-SEP-14:09 | 1404.46 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3322.12 | 09-SEP-17:00 | 1136.97 | 07-SEP-17:00 |
October | 2699.95 | 07-OCT-14:09 | 1404.46 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2665.14 | 05-OCT-15:00 | 1953.46 | 27-OCT-16:00 |
November | 2699.95 | 04-NOV-14:09 | 1404.46 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1627.69 | 01-NOV-14:00 | 3208.84 | 15-NOV-18:00 |
December | 2699.95 | 02-DEC-15:09 | 1404.46 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1646.38 | 13-DEC-15:00 | 4976.57 | 20-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 837.55 | 301.30 | |||||
Maximum of Months | 2699.95 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 3322.12 | 4976.57 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 12172.46 | 01-JAN-14:00 | 4050.04 | 4621.63 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 987.55 | 0.00 |
February | 13901.15 | 28-FEB-08:63 | 1012.51 | 225.00 | 223.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 317.69 |
March | 12815.60 | 07-MAR-08:63 | 1012.51 | 225.00 | 223.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 186.13 |
April | 26815.49 | 29-APR-07:03 | 0.00 | 300.00 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 7.26 | 0.00 |
May | 33998.98 | 07-MAY-07:02 | 1687.52 | 375.00 | 373.12 | 0.00 | 0.00 | 0.00 | 0.00 | 41.07 | 0.00 |
June | 34668.27 | 11-JUN-07:02 | 1687.52 | 375.00 | 373.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.66 |
July | 34064.52 | 09-JUL-07:01 | 2362.52 | 525.00 | 522.37 | 0.00 | 0.00 | 0.00 | 0.00 | 225.29 | 0.00 |
August | 36929.45 | 31-AUG-07:02 | 2025.02 | 450.00 | 447.75 | 0.00 | 0.00 | 0.00 | 0.00 | 34.41 | 0.00 |
September | 33196.98 | 22-SEP-07:02 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 175.89 |
October | 47318.59 | 26-OCT-07:02 | 1687.52 | 375.00 | 373.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 190.43 |
November | 31708.09 | 07-NOV-08:62 | 1350.01 | 300.00 | 298.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 119.59 |
December | 29880.14 | 17-DEC-08:62 | 1350.01 | 300.00 | 298.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 364.57 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 12172.46 | 0.00 | 225.00 | 223.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 47318.59 | 4050.04 | 4621.63 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 987.55 | 364.57 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 14900.50 | 29-JAN-19:09 | 9449.82 | 19789.47 | 4701.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 190.68 |
February | 12506.89 | 20-FEB-18:28 | 12149.77 | 16962.41 | 4029.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 155.24 |
March | 16495.66 | 04-MAR-19:08 | 13499.74 | 22616.54 | 5373.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.53 |
April | 16698.10 | 02-APR-17:56 | 10124.81 | 14135.34 | 3358.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 264.86 |
May | 21048.70 | 30-MAY-07:02 | 1012.48 | 225.00 | 223.88 | 0.00 | 0.00 | 0.00 | 0.00 | 63.74 | 0.00 |
June | 21801.59 | 26-JUN-07:02 | 1012.48 | 225.00 | 223.88 | 0.00 | 0.00 | 0.00 | 0.00 | 38.31 | 0.00 |
July | 21104.19 | 09-JUL-07:01 | 1181.23 | 262.50 | 261.19 | 0.00 | 0.00 | 0.00 | 0.00 | 129.44 | 0.00 |
August | 21879.37 | 31-AUG-07:02 | 1012.48 | 225.00 | 223.88 | 0.00 | 0.00 | 0.00 | 0.00 | 25.93 | 0.00 |
September | 21062.44 | 02-SEP-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 59.11 | 0.00 |
October | 25474.13 | 26-OCT-07:02 | 843.73 | 187.50 | 186.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.92 |
November | 19590.80 | 02-NOV-07:02 | 843.73 | 187.50 | 186.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.77 |
December | 18026.09 | 17-DEC-08:62 | 674.99 | 150.00 | 149.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 186.65 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 12506.89 | 0.00 | 150.00 | 149.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 25474.13 | 13499.74 | 22616.54 | 5373.00 | 0.00 | 0.00 | 0.00 | 0.00 | 129.44 | 264.86 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 10040.66 | 02-JAN-07:03 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.59 |
February | 9522.48 | 28-FEB-07:03 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.48 |
March | 9408.57 | 30-MAR-06:03 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.02 |
April | 16150.25 | 28-APR-06:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.46 |
May | 17947.46 | 12-MAY-06:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.99 |
June | 18619.51 | 14-JUN-06:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 | 0.00 |
July | 16792.84 | 19-JUL-06:01 | 0.00 | 262.50 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 1.53 | 0.00 |
August | 18559.54 | 31-AUG-06:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17481.83 | 23-SEP-06:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.78 |
October | 24471.92 | 26-OCT-06:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.51 |
November | 17796.19 | 08-NOV-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.93 |
December | 18656.68 | 17-DEC-08:62 | 0.00 | 150.00 | 149.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 187.17 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 9408.57 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 24471.92 | 0.00 | 262.50 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 1.53 | 187.17 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 9872.65 | 02-JAN-07:03 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.59 |
February | 9170.32 | 28-FEB-07:03 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.48 |
March | 9174.17 | 30-MAR-06:03 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.02 |
April | 16214.65 | 28-APR-06:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.47 |
May | 18026.51 | 12-MAY-06:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.06 |
June | 18711.20 | 14-JUN-06:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 | 0.00 |
July | 16878.50 | 19-JUL-06:01 | 0.00 | 262.50 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 1.49 | 0.00 |
August | 18649.56 | 31-AUG-06:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17548.15 | 23-SEP-06:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.82 |
October | 24557.45 | 26-OCT-06:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.59 |
November | 17853.47 | 08-NOV-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.95 |
December | 18584.60 | 17-DEC-08:62 | 0.00 | 150.00 | 149.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 187.14 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 9170.32 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 24557.45 | 0.00 | 262.50 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 1.49 | 187.14 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 8807.51 | 02-JAN-07:03 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.57 |
February | 7878.22 | 28-FEB-07:03 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.47 |
March | 7826.33 | 30-MAR-06:03 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.01 |
April | 14997.18 | 30-APR-07:03 | 0.00 | 150.00 | 149.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 116.60 |
May | 17751.80 | 12-MAY-06:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 |
June | 18408.05 | 14-JUN-06:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.08 | 0.00 |
July | 16566.51 | 19-JUL-06:01 | 0.00 | 262.50 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 1.65 | 0.00 |
August | 18359.08 | 31-AUG-06:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17286.01 | 23-SEP-06:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.64 |
October | 24205.51 | 26-OCT-06:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.97 |
November | 17561.00 | 08-NOV-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.65 |
December | 17237.45 | 17-DEC-08:62 | 0.00 | 150.00 | 149.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 186.46 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 7826.33 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 24205.51 | 0.00 | 262.50 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 1.65 | 186.46 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 12226.36 | 02-JAN-08:63 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 635.07 |
February | 11651.35 | 28-FEB-08:63 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 311.04 |
March | 10560.27 | 26-MAR-14:10 | 4657.54 | 2726.96 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 2362.11 | 0.00 |
April | 25986.78 | 29-APR-07:03 | 0.00 | 300.00 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 7.47 | 0.00 |
May | 31461.21 | 12-MAY-07:03 | 0.00 | 300.00 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.43 |
June | 33251.50 | 14-JUN-07:02 | 0.00 | 450.00 | 441.83 | 0.00 | 0.00 | 0.00 | 0.00 | 140.00 | 0.00 |
July | 31056.54 | 19-JUL-07:02 | 0.00 | 450.00 | 441.83 | 0.00 | 0.00 | 0.00 | 0.00 | 208.90 | 0.00 |
August | 34192.11 | 31-AUG-07:02 | 0.00 | 450.00 | 441.83 | 0.00 | 0.00 | 0.00 | 0.00 | 40.18 | 0.00 |
September | 31037.46 | 23-SEP-07:02 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.12 |
October | 43225.04 | 26-OCT-07:02 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 177.95 |
November | 30773.41 | 07-NOV-08:62 | 0.00 | 300.00 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 113.50 |
December | 29503.18 | 17-DEC-09:02 | 0.00 | 300.00 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 400.08 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 10560.27 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 43225.04 | 4657.54 | 2726.96 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 2362.11 | 635.07 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5762.70 | 02-JAN-08:63 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 359.52 |
February | 5330.71 | 24-FEB-14:00 | 2396.20 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 882.60 | 0.00 |
March | 5518.42 | 26-MAR-14:10 | 2328.71 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1348.15 | 0.00 |
April | 12367.12 | 29-APR-07:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 4.43 | 0.00 |
May | 16147.73 | 31-MAY-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.02 | 0.00 |
June | 17371.67 | 14-JUN-07:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 83.49 | 0.00 |
July | 16226.03 | 19-JUL-07:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 122.43 | 0.00 |
August | 17859.49 | 31-AUG-07:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 27.33 | 0.00 |
September | 16198.02 | 23-SEP-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.53 |
October | 22543.29 | 26-OCT-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.86 |
November | 14965.16 | 07-NOV-08:62 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.46 |
December | 14184.79 | 17-DEC-09:02 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 224.30 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5330.71 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22543.29 | 2396.20 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1348.15 | 359.52 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5455.09 | 01-JAN-15:10 | 2328.71 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 296.61 | 0.00 |
February | 5271.46 | 02-FEB-13:40 | 2396.20 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1072.53 | 0.00 |
March | 5454.59 | 26-MAR-14:10 | 2328.71 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1348.40 | 0.00 |
April | 11981.81 | 29-APR-07:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 4.59 | 0.00 |
May | 16046.22 | 31-MAY-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.91 | 0.00 |
June | 17275.42 | 14-JUN-07:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 84.28 | 0.00 |
July | 16128.52 | 19-JUL-07:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 123.23 | 0.00 |
August | 17758.54 | 31-AUG-07:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 28.02 | 0.00 |
September | 16108.47 | 23-SEP-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.80 |
October | 22426.08 | 26-OCT-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.16 |
November | 14643.45 | 03-NOV-07:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.37 |
December | 13746.25 | 17-DEC-09:02 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 224.14 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5271.46 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22426.08 | 2396.20 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1348.40 | 224.14 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5358.34 | 01-JAN-15:10 | 2328.71 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 296.61 | 0.00 |
February | 5152.94 | 24-FEB-14:00 | 2396.20 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 882.60 | 0.00 |
March | 5340.89 | 26-MAR-14:10 | 2328.71 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1348.43 | 0.00 |
April | 10538.51 | 29-APR-07:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 5.24 | 0.00 |
May | 15997.88 | 31-MAY-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.01 | 0.00 |
June | 17258.19 | 14-JUN-07:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 87.68 | 0.00 |
July | 16143.41 | 19-JUL-07:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 125.21 | 0.00 |
August | 17794.44 | 31-AUG-07:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 29.41 | 0.00 |
September | 16120.26 | 23-SEP-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.75 |
October | 22448.01 | 26-OCT-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.40 |
November | 14433.39 | 02-NOV-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.93 |
December | 12482.26 | 17-DEC-09:02 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 223.68 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5152.94 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22448.01 | 2396.20 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1348.43 | 223.68 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5663.10 | 01-JAN-15:10 | 2328.71 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 299.48 | 0.00 |
February | 5607.36 | 24-FEB-13:50 | 2396.20 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 919.21 | 0.00 |
March | 5902.13 | 26-MAR-14:10 | 2328.71 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1369.70 | 0.00 |
April | 7898.08 | 28-APR-15:00 | 2328.71 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 2515.01 | 0.00 |
May | 17479.08 | 31-MAY-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.99 | 0.00 |
June | 18064.67 | 14-JUN-07:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 96.02 | 0.00 |
July | 17653.42 | 19-JUL-07:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 133.05 | 0.00 |
August | 20672.85 | 31-AUG-07:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 30.61 | 0.00 |
September | 18247.27 | 01-SEP-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.81 | 0.00 |
October | 22529.80 | 26-OCT-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.34 |
November | 15332.44 | 02-NOV-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.01 |
December | 8785.38 | 17-DEC-09:02 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 266.45 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5607.36 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22529.80 | 2396.20 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 2515.01 | 266.45 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.670183E+11 | 71519.50 | 19-JAN-15:39 | 0.532930E+10 | 65224.50 | 10-JAN-08:09 |
February | 0.629768E+11 | 74707.28 | 24-FEB-13:09 | 0.539509E+10 | 99899.40 | 05-FEB-09:09 |
March | 0.724585E+11 | 76228.48 | 30-MAR-12:20 | 0.388686E+10 | 86951.77 | 11-MAR-12:09 |
April | 0.786038E+11 | 92376.43 | 28-APR-16:00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 0.104800E+12 | 93225.29 | 24-MAY-12:00 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 0.106262E+12 | 102290.24 | 28-JUN-13:50 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 0.112552E+12 | 109731.23 | 22-JUL-15:30 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.114147E+12 | 101264.40 | 28-AUG-13:09 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.104261E+12 | 119517.11 | 10-SEP-13:30 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 0.100464E+12 | 109601.57 | 07-OCT-13:20 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 0.752330E+11 | 89947.19 | 02-NOV-12:39 | 1766112.23 | 846.24 | 16-NOV-08:09 |
December | 0.716896E+11 | 82724.97 | 15-DEC-13:30 | 0.465663E+10 | 78751.16 | 20-DEC-17:00 |
Annual Sum or Average | 0.107047E+13 | 0.192696E+11 | ||||
Minimum of Months | 0.629768E+11 | 71519.50 | 0.00 | 0.00 | ||
Maximum of Months | 0.114147E+12 | 119517.11 | 0.539509E+10 | 99899.40 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.310073E+11 | 0.605968E+10 | 0.108325E+11 | 0.00 | 0.844120E+10 | 0.00 | 0.00 | 0.543094E+10 | 0.00 | 0.00 | 0.00 | 0.524672E+10 | 0.00 |
February | 0.280657E+11 | 0.514443E+10 | 0.980803E+10 | 0.00 | 0.768714E+10 | 0.00 | 0.00 | 0.754195E+10 | 0.00 | 0.00 | 0.00 | 0.472948E+10 | 0.00 |
March | 0.314703E+11 | 0.520057E+10 | 0.110075E+11 | 0.00 | 0.858145E+10 | 0.00 | 0.00 | 0.109842E+11 | 0.00 | 0.00 | 0.00 | 0.521455E+10 | 0.00 |
April | 0.300741E+11 | 0.455295E+10 | 0.105079E+11 | 0.00 | 0.814072E+10 | 0.00 | 0.00 | 0.203913E+11 | 0.00 | 0.00 | 0.00 | 0.493679E+10 | 0.00 |
May | 0.312330E+11 | 0.427208E+10 | 0.109147E+11 | 0.00 | 0.861016E+10 | 0.00 | 0.00 | 0.447499E+11 | 0.00 | 0.00 | 0.00 | 0.502016E+10 | 0.00 |
June | 0.304143E+11 | 0.389871E+10 | 0.106386E+11 | 0.00 | 0.865280E+10 | 0.00 | 0.00 | 0.478480E+11 | 0.00 | 0.00 | 0.00 | 0.481003E+10 | 0.00 |
July | 0.309042E+11 | 0.415313E+10 | 0.107945E+11 | 0.00 | 0.924161E+10 | 0.00 | 0.00 | 0.525525E+11 | 0.00 | 0.00 | 0.00 | 0.490634E+10 | 0.00 |
August | 0.314595E+11 | 0.450338E+10 | 0.110006E+11 | 0.00 | 0.935614E+10 | 0.00 | 0.00 | 0.528789E+11 | 0.00 | 0.00 | 0.00 | 0.494841E+10 | 0.00 |
September | 0.300847E+11 | 0.483051E+10 | 0.105148E+11 | 0.00 | 0.867236E+10 | 0.00 | 0.00 | 0.453449E+11 | 0.00 | 0.00 | 0.00 | 0.481414E+10 | 0.00 |
October | 0.310073E+11 | 0.549465E+10 | 0.108325E+11 | 0.00 | 0.882134E+10 | 0.00 | 0.00 | 0.392676E+11 | 0.00 | 0.00 | 0.00 | 0.504071E+10 | 0.00 |
November | 0.300409E+11 | 0.573587E+10 | 0.104978E+11 | 0.00 | 0.818056E+10 | 0.00 | 0.00 | 0.158142E+11 | 0.00 | 0.00 | 0.00 | 0.496360E+10 | 0.00 |
December | 0.309156E+11 | 0.616872E+10 | 0.108050E+11 | 0.00 | 0.845551E+10 | 0.00 | 0.00 | 0.101414E+11 | 0.00 | 0.00 | 0.00 | 0.520332E+10 | 0.00 |
Annual Sum or Average | 0.366677E+12 | 0.600147E+11 | 0.128154E+12 | 0.00 | 0.102841E+12 | 0.00 | 0.00 | 0.352946E+12 | 0.00 | 0.00 | 0.00 | 0.598343E+11 | 0.00 |
Minimum of Months | 0.280657E+11 | 0.389871E+10 | 0.980803E+10 | 0.00 | 0.768714E+10 | 0.00 | 0.00 | 0.543094E+10 | 0.00 | 0.00 | 0.00 | 0.472948E+10 | 0.00 |
Maximum of Months | 0.314703E+11 | 0.616872E+10 | 0.110075E+11 | 0.00 | 0.935614E+10 | 0.00 | 0.00 | 0.528789E+11 | 0.00 | 0.00 | 0.00 | 0.524672E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.532930E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.539509E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.388686E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 1766112.23 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.465663E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.192696E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.539509E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 23459.17 | 01-JAN-11:09 | 5507.06 | 01-JAN-06:10 | 8059.50 | 01-JAN-11:09 | 0.00 | 7005.53 | 10-JAN-08:09 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 23459.17 | 01-FEB-10:09 | 5507.06 | 01-FEB-06:10 | 8059.50 | 01-FEB-10:09 | 0.00 | 7690.44 | 05-FEB-09:09 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 23459.17 | 01-MAR-10:09 | 5507.06 | 01-MAR-06:10 | 8059.50 | 01-MAR-10:09 | 0.00 | 7431.71 | 11-MAR-12:09 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 23459.17 | 01-APR-09:09 | 5507.06 | 01-APR-05:10 | 8059.50 | 01-APR-09:09 | 0.00 | 7034.33 | 28-APR-16:10 | 0.00 | 0.00 | 01-APR-00:10 |
May | 23459.17 | 01-MAY-09:09 | 5507.06 | 01-MAY-05:10 | 8059.50 | 01-MAY-09:09 | 0.00 | 7661.15 | 22-MAY-07:10 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 23459.17 | 01-JUN-09:09 | 5507.06 | 01-JUN-05:10 | 8059.50 | 01-JUN-09:09 | 0.00 | 8667.70 | 28-JUN-13:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 23459.17 | 01-JUL-09:09 | 5507.06 | 01-JUL-05:10 | 8059.50 | 01-JUL-09:09 | 0.00 | 9855.38 | 22-JUL-15:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 23459.17 | 01-AUG-09:09 | 5507.06 | 01-AUG-05:10 | 8059.50 | 01-AUG-09:09 | 0.00 | 8680.40 | 07-AUG-12:00 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 23459.17 | 01-SEP-09:09 | 5507.06 | 01-SEP-05:10 | 8059.50 | 01-SEP-09:09 | 0.00 | 11327.58 | 10-SEP-12:00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 23459.17 | 01-OCT-10:09 | 5507.06 | 01-OCT-05:10 | 8059.50 | 01-OCT-10:09 | 0.00 | 10082.48 | 07-OCT-12:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 23459.17 | 01-NOV-09:09 | 5507.06 | 01-NOV-05:10 | 8059.50 | 01-NOV-09:09 | 0.00 | 7128.08 | 03-NOV-07:10 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 23459.17 | 01-DEC-10:09 | 5507.06 | 01-DEC-06:10 | 8059.50 | 01-DEC-10:09 | 0.00 | 7270.42 | 20-DEC-17:00 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||||
Minimum of Months | 23459.17 | 5507.06 | 8059.50 | 0.00 | 7005.53 | 0.00 | 0.00 | |||||
Maximum of Months | 23459.17 | 5507.06 | 8059.50 | 0.00 | 11327.58 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 29778.33 | 19-JAN-13:00 | 0.00 | 0.00 | 0.00 | 11639.69 | 01-JAN-08:30 | 0.00 |
February | 32021.79 | 24-FEB-13:09 | 0.00 | 0.00 | 0.00 | 8449.34 | 10-FEB-15:39 | 0.00 |
March | 35341.14 | 30-MAR-12:00 | 0.00 | 0.00 | 0.00 | 7567.90 | 06-MAR-13:09 | 0.00 |
April | 47981.33 | 28-APR-16:10 | 0.00 | 0.00 | 0.00 | 9618.33 | 28-APR-19:10 | 0.00 |
May | 51106.45 | 24-MAY-12:00 | 0.00 | 0.00 | 0.00 | 7556.23 | 03-MAY-12:50 | 0.00 |
June | 57305.14 | 28-JUN-13:00 | 0.00 | 0.00 | 0.00 | 7546.81 | 26-JUN-12:00 | 0.00 |
July | 65093.36 | 22-JUL-15:00 | 0.00 | 0.00 | 0.00 | 8898.64 | 05-JUL-13:39 | 0.00 |
August | 57683.01 | 03-AUG-16:10 | 0.00 | 0.00 | 0.00 | 7547.35 | 26-AUG-12:09 | 0.00 |
September | 71673.28 | 10-SEP-14:09 | 0.00 | 0.00 | 0.00 | 7551.52 | 15-SEP-12:09 | 0.00 |
October | 63588.55 | 07-OCT-12:00 | 0.00 | 0.00 | 0.00 | 7466.86 | 08-OCT-02:20 | 0.00 |
November | 45698.83 | 02-NOV-12:00 | 0.00 | 0.00 | 0.00 | 9679.76 | 18-NOV-13:39 | 0.00 |
December | 38420.98 | 15-DEC-13:00 | 0.00 | 0.00 | 0.00 | 9671.35 | 21-DEC-12:20 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 29778.33 | 0.00 | 0.00 | 0.00 | 7466.86 | 0.00 | ||
Maximum of Months | 71673.28 | 0.00 | 0.00 | 0.00 | 11639.69 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 71519.50 | 19-JAN-15:39 | 23459.17 | 8059.50 | 0.00 | 0.00 | 5715.18 | 0.00 | 0.00 | 28847.94 | 0.00 |
February | 74707.28 | 24-FEB-13:09 | 23459.17 | 8059.50 | 0.00 | 0.00 | 5715.18 | 0.00 | 0.00 | 32021.79 | 0.00 |
March | 76228.48 | 30-MAR-12:20 | 23459.17 | 8059.50 | 0.00 | 0.00 | 5715.18 | 0.00 | 0.00 | 33548.60 | 0.00 |
April | 92376.43 | 28-APR-16:00 | 23459.17 | 8059.50 | 0.00 | 0.00 | 6533.96 | 0.00 | 0.00 | 45026.88 | 0.00 |
May | 93225.29 | 24-MAY-12:00 | 23459.17 | 8059.50 | 0.00 | 0.00 | 7571.94 | 0.00 | 0.00 | 51106.45 | 0.00 |
June | 102290.24 | 28-JUN-13:50 | 23459.17 | 8059.50 | 0.00 | 0.00 | 8584.59 | 0.00 | 0.00 | 56753.60 | 0.00 |
July | 109731.23 | 22-JUL-15:30 | 23459.17 | 8059.50 | 0.00 | 0.00 | 9445.05 | 0.00 | 0.00 | 62528.35 | 0.00 |
August | 101264.40 | 28-AUG-13:09 | 23459.17 | 8059.50 | 0.00 | 0.00 | 8308.16 | 0.00 | 0.00 | 56003.53 | 0.00 |
September | 119517.11 | 10-SEP-13:30 | 23459.17 | 8059.50 | 0.00 | 0.00 | 11264.22 | 0.00 | 0.00 | 71628.80 | 0.00 |
October | 109601.57 | 07-OCT-13:20 | 23459.17 | 8059.50 | 0.00 | 0.00 | 9908.87 | 0.00 | 0.00 | 62735.95 | 0.00 |
November | 89947.19 | 02-NOV-12:39 | 23459.17 | 8059.50 | 0.00 | 0.00 | 6649.09 | 0.00 | 0.00 | 44809.20 | 0.00 |
December | 82724.97 | 15-DEC-13:30 | 23459.17 | 8059.50 | 0.00 | 0.00 | 5715.18 | 0.00 | 0.00 | 37921.04 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 71519.50 | 23459.17 | 8059.50 | 0.00 | 0.00 | 5715.18 | 0.00 | 0.00 | 28847.94 | 0.00 | |
Maximum of Months | 119517.11 | 23459.17 | 8059.50 | 0.00 | 0.00 | 11264.22 | 0.00 | 0.00 | 71628.80 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 65224.50 | 10-JAN-08:09 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 99899.40 | 05-FEB-09:09 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 86951.77 | 11-MAR-12:09 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 846.24 | 16-NOV-08:09 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 78751.16 | 20-DEC-17:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 99899.40 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.46 | 0.17 | 24.46 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.17 | 24.46 | 0.17 | 24.46 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.46 | 0.17 | 24.46 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.59 | 0.00 | 24.59 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.17 | 24.59 | 0.00 | 24.59 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.59 | 0.00 | 24.59 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.47 | 0.00 | 24.47 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.54 | 0.00 | 24.54 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.50 | 24.52 | 0.00 | 24.52 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.54 | 0.00 | 24.54 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.58 | 0.00 | 24.58 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.17 | 24.58 | 0.00 | 24.58 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.58 | 0.00 | 24.58 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.47 | 0.00 | 24.47 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.67 | 0.00 | 24.67 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.50 | 24.61 | 0.00 | 24.61 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.67 | 0.00 | 24.67 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.46 | 0.00 | 24.46 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.62 | 0.00 | 24.62 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.50 | 24.57 | 0.00 | 24.57 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.62 | 0.00 | 24.62 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.46 | 0.00 | 24.46 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.62 | 0.00 | 24.62 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.50 | 24.57 | 0.00 | 24.57 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.62 | 0.00 | 24.62 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.63 | 0.00 | 24.63 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.33 | 24.63 | 0.00 | 24.63 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.63 | 0.00 | 24.63 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.17 | 20.50 | 0.00 | 20.50 | 0.00 | 20.50 | 0.00 | 20.50 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.47 | 0.00 | 24.47 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.76 | 0.00 | 24.76 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.17 | 20.50 | 0.00 | 20.50 | 0.50 | 23.62 | 0.00 | 23.62 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 20.50 | 0.00 | 20.50 | 0.33 | 24.76 | 0.00 | 24.76 |
Report: ComfortReportSimple55Monthly
For: LGSTORE1
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 345.00 | 22.11 | 154.50 | 22.62 | 44.00 | 22.69 |
February | 275.50 | 22.62 | 223.33 | 23.13 | 81.17 | 23.19 |
March | 255.17 | 22.63 | 217.67 | 23.17 | 57.50 | 23.22 |
April | 96.67 | 23.70 | 360.50 | 23.85 | 59.83 | 23.85 |
May | 125.33 | 23.89 | 496.00 | 23.89 | 125.33 | 23.89 |
June | 128.67 | 23.89 | 481.00 | 23.89 | 128.67 | 23.89 |
July | 257.83 | 23.89 | 495.00 | 23.89 | 257.83 | 23.89 |
August | 158.83 | 23.89 | 497.00 | 23.89 | 158.83 | 23.89 |
September | 183.17 | 23.89 | 479.00 | 23.89 | 183.17 | 23.89 |
October | 123.50 | 23.85 | 445.67 | 23.88 | 113.50 | 23.88 |
November | 111.00 | 23.47 | 312.67 | 23.78 | 45.00 | 23.79 |
December | 243.00 | 22.42 | 217.33 | 23.10 | 40.83 | 23.15 |
Annual Sum or Average | 2303.67 | 23.15 | 4379.67 | 23.62 | 1295.67 | 23.66 |
Minimum of Months | 96.67 | 22.11 | 154.50 | 22.62 | 40.83 | 22.69 |
Maximum of Months | 345.00 | 23.89 | 497.00 | 23.89 | 257.83 | 23.89 |
Report: ComfortReportSimple55Monthly
For: SMSTORE1
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 292.17 | 22.72 | 150.83 | 23.11 | 24.83 | 23.14 |
February | 204.83 | 22.94 | 210.83 | 23.42 | 44.17 | 23.46 |
March | 182.50 | 22.89 | 205.33 | 23.42 | 16.17 | 23.44 |
April | 38.50 | 23.72 | 331.17 | 23.87 | 16.17 | 23.87 |
May | 68.83 | 23.89 | 487.00 | 23.89 | 68.83 | 23.89 |
June | 74.00 | 23.89 | 477.00 | 23.89 | 74.00 | 23.89 |
July | 171.50 | 23.89 | 494.67 | 23.89 | 171.50 | 23.89 |
August | 101.50 | 23.89 | 496.00 | 23.89 | 101.50 | 23.89 |
September | 126.00 | 23.89 | 476.33 | 23.89 | 126.00 | 23.89 |
October | 90.33 | 23.85 | 429.17 | 23.88 | 82.17 | 23.88 |
November | 68.83 | 23.67 | 304.17 | 23.85 | 27.67 | 23.85 |
December | 189.00 | 22.77 | 217.00 | 23.37 | 23.50 | 23.40 |
Annual Sum or Average | 1608.00 | 23.30 | 4279.50 | 23.73 | 776.50 | 23.74 |
Minimum of Months | 38.50 | 22.72 | 150.83 | 23.11 | 16.17 | 23.14 |
Maximum of Months | 292.17 | 23.89 | 496.00 | 23.89 | 171.50 | 23.89 |
Report: ComfortReportSimple55Monthly
For: SMSTORE2
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 247.00 | 22.25 | 117.17 | 22.78 | 27.00 | 22.84 |
February | 174.83 | 22.63 | 166.33 | 23.24 | 39.50 | 23.29 |
March | 175.33 | 22.70 | 162.00 | 23.32 | 32.50 | 23.38 |
April | 71.83 | 23.89 | 274.17 | 23.99 | 50.17 | 24.01 |
May | 111.00 | 24.30 | 375.00 | 24.13 | 111.00 | 24.16 |
June | 132.50 | 24.30 | 366.00 | 24.14 | 132.50 | 24.18 |
July | 235.33 | 24.19 | 369.00 | 24.13 | 235.33 | 24.15 |
August | 159.17 | 24.25 | 379.00 | 24.13 | 159.17 | 24.16 |
September | 192.17 | 24.18 | 360.00 | 24.11 | 192.17 | 24.13 |
October | 113.33 | 24.15 | 332.83 | 24.09 | 106.33 | 24.12 |
November | 84.50 | 23.70 | 241.50 | 23.91 | 46.67 | 23.94 |
December | 183.00 | 22.55 | 163.67 | 23.21 | 39.50 | 23.28 |
Annual Sum or Average | 1880.00 | 23.47 | 3306.67 | 23.84 | 1171.83 | 23.90 |
Minimum of Months | 71.83 | 22.25 | 117.17 | 22.78 | 27.00 | 22.84 |
Maximum of Months | 247.00 | 24.30 | 379.00 | 24.14 | 235.33 | 24.18 |
Report: ComfortReportSimple55Monthly
For: SMSTORE3
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 254.67 | 22.22 | 116.50 | 22.73 | 30.17 | 22.80 |
February | 182.50 | 22.60 | 164.33 | 23.20 | 40.67 | 23.25 |
March | 184.67 | 22.71 | 158.50 | 23.30 | 33.17 | 23.36 |
April | 74.33 | 23.88 | 271.67 | 23.99 | 51.17 | 24.00 |
May | 110.50 | 24.30 | 375.00 | 24.13 | 110.50 | 24.16 |
June | 130.50 | 24.31 | 366.00 | 24.14 | 130.50 | 24.18 |
July | 231.00 | 24.20 | 369.00 | 24.14 | 231.00 | 24.15 |
August | 156.50 | 24.25 | 379.00 | 24.13 | 156.50 | 24.16 |
September | 189.17 | 24.19 | 360.00 | 24.11 | 189.17 | 24.13 |
October | 112.00 | 24.15 | 332.50 | 24.09 | 105.17 | 24.12 |
November | 87.00 | 23.68 | 235.50 | 23.90 | 47.00 | 23.93 |
December | 190.83 | 22.54 | 160.33 | 23.18 | 39.83 | 23.26 |
Annual Sum or Average | 1903.67 | 23.45 | 3288.33 | 23.82 | 1164.83 | 23.89 |
Minimum of Months | 74.33 | 22.22 | 116.50 | 22.73 | 30.17 | 22.80 |
Maximum of Months | 254.67 | 24.31 | 379.00 | 24.14 | 231.00 | 24.18 |
Report: ComfortReportSimple55Monthly
For: SMSTORE4
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 268.50 | 22.18 | 114.67 | 22.67 | 36.33 | 22.75 |
February | 193.67 | 22.54 | 162.33 | 23.14 | 43.17 | 23.18 |
March | 201.67 | 22.70 | 151.33 | 23.24 | 36.67 | 23.30 |
April | 84.83 | 23.84 | 268.83 | 23.97 | 55.33 | 23.98 |
May | 114.33 | 24.29 | 375.00 | 24.12 | 114.33 | 24.15 |
June | 139.50 | 24.27 | 366.00 | 24.13 | 139.50 | 24.16 |
July | 244.50 | 24.18 | 369.00 | 24.13 | 244.50 | 24.14 |
August | 170.17 | 24.21 | 379.00 | 24.12 | 170.17 | 24.14 |
September | 205.17 | 24.16 | 360.00 | 24.10 | 205.17 | 24.12 |
October | 118.50 | 24.13 | 331.33 | 24.08 | 110.67 | 24.10 |
November | 97.50 | 23.64 | 222.17 | 23.88 | 51.50 | 23.91 |
December | 206.00 | 22.54 | 157.17 | 23.14 | 44.50 | 23.23 |
Annual Sum or Average | 2044.33 | 23.42 | 3256.83 | 23.80 | 1251.83 | 23.86 |
Minimum of Months | 84.83 | 22.18 | 114.67 | 22.67 | 36.33 | 22.75 |
Maximum of Months | 268.50 | 24.29 | 379.00 | 24.13 | 244.50 | 24.16 |
Report: ComfortReportSimple55Monthly
For: LGSTORE2
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 270.00 | 22.18 | 95.00 | 22.59 | 45.50 | 22.69 |
February | 201.83 | 22.54 | 147.67 | 23.06 | 52.50 | 23.11 |
March | 223.83 | 22.76 | 130.50 | 23.18 | 52.17 | 23.27 |
April | 102.33 | 23.81 | 238.00 | 23.89 | 63.33 | 23.91 |
May | 127.83 | 24.05 | 344.00 | 23.98 | 127.83 | 24.00 |
June | 166.50 | 24.01 | 336.00 | 23.97 | 166.50 | 23.98 |
July | 264.00 | 24.01 | 338.00 | 23.99 | 264.00 | 24.00 |
August | 213.00 | 23.97 | 348.00 | 23.96 | 213.00 | 23.96 |
September | 243.33 | 24.00 | 330.00 | 23.99 | 243.33 | 23.99 |
October | 123.67 | 23.99 | 301.83 | 23.97 | 115.33 | 23.99 |
November | 119.50 | 23.61 | 191.50 | 23.80 | 64.50 | 23.82 |
December | 212.00 | 22.54 | 137.50 | 23.06 | 51.17 | 23.15 |
Annual Sum or Average | 2267.83 | 23.37 | 2938.00 | 23.69 | 1459.17 | 23.75 |
Minimum of Months | 102.33 | 22.18 | 95.00 | 22.59 | 45.50 | 22.69 |
Maximum of Months | 270.00 | 24.05 | 348.00 | 23.99 | 264.00 | 24.00 |
Report: ComfortReportSimple55Monthly
For: SMSTORE5
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 277.17 | 22.19 | 92.33 | 22.57 | 47.83 | 22.68 |
February | 205.33 | 22.53 | 147.83 | 23.03 | 55.67 | 23.08 |
March | 229.67 | 22.76 | 129.17 | 23.17 | 54.33 | 23.25 |
April | 106.67 | 23.81 | 235.17 | 23.89 | 64.33 | 23.91 |
May | 128.00 | 24.05 | 344.00 | 23.98 | 128.00 | 24.00 |
June | 168.83 | 24.00 | 336.00 | 23.97 | 168.83 | 23.98 |
July | 264.17 | 24.00 | 338.00 | 23.99 | 264.17 | 23.99 |
August | 216.17 | 23.97 | 348.00 | 23.96 | 216.17 | 23.96 |
September | 247.00 | 24.00 | 330.00 | 23.98 | 247.00 | 23.99 |
October | 127.00 | 23.98 | 297.83 | 23.97 | 115.33 | 23.98 |
November | 126.67 | 23.61 | 176.50 | 23.79 | 64.50 | 23.82 |
December | 221.67 | 22.57 | 130.83 | 23.05 | 52.83 | 23.14 |
Annual Sum or Average | 2318.33 | 23.36 | 2905.67 | 23.68 | 1479.00 | 23.74 |
Minimum of Months | 106.67 | 22.19 | 92.33 | 22.57 | 47.83 | 22.68 |
Maximum of Months | 277.17 | 24.05 | 348.00 | 23.99 | 264.17 | 24.00 |
Report: ComfortReportSimple55Monthly
For: SMSTORE6
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 279.67 | 22.18 | 91.67 | 22.55 | 48.83 | 22.67 |
February | 208.17 | 22.51 | 147.67 | 23.01 | 57.83 | 23.06 |
March | 233.50 | 22.75 | 128.33 | 23.15 | 55.67 | 23.24 |
April | 110.17 | 23.80 | 234.33 | 23.89 | 65.83 | 23.90 |
May | 130.50 | 24.05 | 344.00 | 23.98 | 130.50 | 24.00 |
June | 171.17 | 24.00 | 336.00 | 23.97 | 171.17 | 23.98 |
July | 265.83 | 24.00 | 338.00 | 23.99 | 265.83 | 23.99 |
August | 219.83 | 23.97 | 348.00 | 23.96 | 219.83 | 23.96 |
September | 249.17 | 24.00 | 330.00 | 23.98 | 249.17 | 23.99 |
October | 128.67 | 23.98 | 297.50 | 23.97 | 116.00 | 23.98 |
November | 130.67 | 23.60 | 173.33 | 23.79 | 65.33 | 23.81 |
December | 227.83 | 22.57 | 129.00 | 23.04 | 53.50 | 23.13 |
Annual Sum or Average | 2355.17 | 23.36 | 2897.83 | 23.67 | 1499.50 | 23.73 |
Minimum of Months | 110.17 | 22.18 | 91.67 | 22.55 | 48.83 | 22.67 |
Maximum of Months | 279.67 | 24.05 | 348.00 | 23.99 | 265.83 | 24.00 |
Report: ComfortReportSimple55Monthly
For: SMSTORE7
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 286.50 | 22.15 | 91.33 | 22.52 | 51.00 | 22.64 |
February | 215.33 | 22.47 | 148.00 | 22.96 | 64.50 | 23.01 |
March | 242.83 | 22.72 | 127.00 | 23.11 | 59.83 | 23.20 |
April | 118.50 | 23.76 | 231.50 | 23.87 | 70.00 | 23.89 |
May | 132.50 | 24.04 | 344.00 | 23.98 | 132.50 | 23.99 |
June | 173.33 | 24.00 | 336.00 | 23.97 | 173.33 | 23.98 |
July | 266.50 | 24.00 | 338.00 | 23.99 | 266.50 | 23.99 |
August | 218.50 | 23.97 | 348.00 | 23.96 | 218.50 | 23.96 |
September | 249.83 | 24.00 | 330.00 | 23.98 | 249.83 | 23.99 |
October | 130.33 | 23.97 | 296.67 | 23.96 | 116.50 | 23.98 |
November | 135.50 | 23.56 | 168.50 | 23.76 | 65.83 | 23.79 |
December | 237.33 | 22.55 | 125.17 | 22.99 | 55.67 | 23.09 |
Annual Sum or Average | 2407.00 | 23.33 | 2884.17 | 23.65 | 1524.00 | 23.72 |
Minimum of Months | 118.50 | 22.15 | 91.33 | 22.52 | 51.00 | 22.64 |
Maximum of Months | 286.50 | 24.04 | 348.00 | 23.99 | 266.50 | 23.99 |
Report: ComfortReportSimple55Monthly
For: SMSTORE8
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 283.00 | 22.09 | 96.67 | 22.46 | 52.83 | 22.55 |
February | 218.83 | 22.39 | 153.83 | 22.86 | 70.83 | 22.89 |
March | 236.83 | 22.60 | 137.83 | 23.00 | 62.50 | 23.06 |
April | 123.00 | 23.68 | 226.50 | 23.84 | 70.83 | 23.86 |
May | 119.00 | 24.07 | 344.00 | 23.99 | 119.00 | 24.00 |
June | 133.67 | 24.05 | 336.00 | 23.98 | 133.67 | 24.00 |
July | 217.50 | 24.04 | 338.00 | 24.01 | 217.50 | 24.02 |
August | 155.33 | 24.02 | 348.00 | 23.98 | 155.33 | 23.99 |
September | 202.00 | 24.04 | 330.00 | 24.00 | 202.00 | 24.01 |
October | 122.17 | 23.97 | 299.17 | 23.97 | 107.50 | 23.99 |
November | 130.83 | 23.50 | 175.00 | 23.74 | 58.00 | 23.77 |
December | 238.83 | 22.47 | 133.67 | 22.93 | 57.50 | 23.00 |
Annual Sum or Average | 2181.00 | 23.24 | 2918.67 | 23.62 | 1307.50 | 23.67 |
Minimum of Months | 119.00 | 22.09 | 96.67 | 22.46 | 52.83 | 22.55 |
Maximum of Months | 283.00 | 24.07 | 348.00 | 24.01 | 217.50 | 24.02 |
Report: OccupantComfortDataSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 496.00000 | 22.64711 | 44.22983 | 0.10194 | 7.92369 |
February | 448.00000 | 23.10213 | 48.08256 | 0.23838 | 8.97026 |
March | 497.00000 | 23.23260 | 46.60564 | 0.25613 | 8.74634 |
April | 479.00000 | 23.84934 | 53.42946 | 0.48665 | 10.29326 |
May | 496.00000 | 23.88846 | 61.62675 | -0.2546 | 6.41665 |
June | 481.00000 | 23.88940 | 61.47897 | -0.2336 | 6.22391 |
July | 495.00000 | 23.89030 | 65.17972 | -0.1958 | 5.87140 |
August | 497.00000 | 23.89059 | 63.08594 | -0.1957 | 5.88396 |
September | 479.00000 | 23.89064 | 63.90045 | -0.2063 | 5.99248 |
October | 496.00000 | 23.87753 | 56.36369 | 0.58470 | 12.47537 |
November | 480.00000 | 23.78680 | 48.26322 | 0.44855 | 9.79760 |
December | 496.00000 | 23.16149 | 46.09481 | 0.25609 | 8.76243 |
Annual Sum or Average | 5840.00000 | 23.59325 | 54.89464 | 0.10589 | 8.10624 |
Minimum of Months | 448.00000 | 22.64711 | 44.22983 | -0.2546 | 5.87140 |
Maximum of Months | 497.00000 | 23.89064 | 65.17972 | 0.58470 | 12.47537 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 496.00000 | 23.19326 | 42.96449 | 0.21843 | 7.68258 |
February | 448.00000 | 23.44375 | 46.59483 | 0.31186 | 8.76549 |
March | 497.00000 | 23.51318 | 44.52372 | 0.31427 | 8.44158 |
April | 479.00000 | 23.86692 | 50.20143 | 0.47363 | 9.93054 |
May | 496.00000 | 23.88810 | 57.71388 | -0.2908 | 6.88112 |
June | 481.00000 | 23.88983 | 57.89393 | -0.2740 | 6.70222 |
July | 495.00000 | 23.89049 | 61.50480 | -0.2395 | 6.32489 |
August | 497.00000 | 23.89035 | 59.89534 | -0.2433 | 6.37258 |
September | 479.00000 | 23.89046 | 60.32718 | -0.2513 | 6.47799 |
October | 496.00000 | 23.87929 | 53.46986 | 0.55317 | 11.68880 |
November | 480.00000 | 23.84530 | 46.48482 | 0.45128 | 9.61193 |
December | 496.00000 | 23.45708 | 44.68989 | 0.31586 | 8.60164 |
Annual Sum or Average | 5840.00000 | 23.72121 | 52.21614 | 0.11008 | 8.11733 |
Minimum of Months | 448.00000 | 23.19326 | 42.96449 | -0.2908 | 6.32489 |
Maximum of Months | 497.00000 | 23.89049 | 61.50480 | 0.55317 | 11.68880 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 22.80691 | 42.21626 | 0.13780 | 7.82033 |
February | 336.00000 | 23.23960 | 46.83803 | 0.27513 | 9.03626 |
March | 379.00000 | 23.35705 | 45.25221 | 0.28689 | 8.82912 |
April | 360.00000 | 23.95158 | 52.64515 | 0.50619 | 10.78387 |
May | 375.00000 | 24.07430 | 61.33263 | -0.2145 | 6.39951 |
June | 366.00000 | 24.08586 | 61.59711 | -0.1929 | 6.29373 |
July | 369.00000 | 24.09895 | 65.67550 | -0.1514 | 6.05644 |
August | 379.00000 | 24.08401 | 63.80528 | -0.1611 | 6.03370 |
September | 360.00000 | 24.07061 | 64.54658 | -0.1708 | 6.10621 |
October | 371.00000 | 24.04317 | 56.19148 | 0.60810 | 13.27838 |
November | 360.00000 | 23.87762 | 47.59665 | 0.46793 | 10.17704 |
December | 369.00000 | 23.23647 | 45.25424 | 0.27738 | 8.92146 |
Annual Sum or Average | 4395.00000 | 23.74608 | 54.46662 | 0.13686 | 8.29833 |
Minimum of Months | 336.00000 | 22.80691 | 42.21626 | -0.2145 | 6.03370 |
Maximum of Months | 379.00000 | 24.09895 | 65.67550 | 0.60810 | 13.27838 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 22.74621 | 42.45403 | 0.11907 | 7.81132 |
February | 336.00000 | 23.19811 | 47.00493 | 0.26099 | 8.96475 |
March | 379.00000 | 23.32893 | 45.35983 | 0.27662 | 8.79499 |
April | 360.00000 | 23.94720 | 52.69690 | 0.50377 | 10.74601 |
May | 375.00000 | 24.07426 | 61.30178 | -0.2140 | 6.39575 |
June | 366.00000 | 24.08603 | 61.54618 | -0.1920 | 6.28806 |
July | 369.00000 | 24.09932 | 65.59338 | -0.1501 | 6.05187 |
August | 379.00000 | 24.08424 | 63.74181 | -0.1600 | 6.02900 |
September | 360.00000 | 24.07076 | 64.48583 | -0.1699 | 6.10291 |
October | 371.00000 | 24.04275 | 56.15889 | 0.60826 | 13.28637 |
November | 360.00000 | 23.86989 | 47.65348 | 0.46432 | 10.12950 |
December | 369.00000 | 23.20246 | 45.36062 | 0.26587 | 8.88278 |
Annual Sum or Average | 4395.00000 | 23.73155 | 54.49959 | 0.13226 | 8.27773 |
Minimum of Months | 336.00000 | 22.74621 | 42.45403 | -0.2140 | 6.02900 |
Maximum of Months | 379.00000 | 24.09932 | 65.59338 | 0.60826 | 13.28637 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 22.65791 | 42.80429 | 0.09332 | 7.79509 |
February | 336.00000 | 23.12617 | 47.37228 | 0.23885 | 8.84440 |
March | 379.00000 | 23.27133 | 45.65699 | 0.25783 | 8.70742 |
April | 360.00000 | 23.93350 | 53.05359 | 0.49714 | 10.63116 |
May | 375.00000 | 24.07011 | 61.62726 | -0.2188 | 6.41994 |
June | 366.00000 | 24.08199 | 61.85033 | -0.1966 | 6.30410 |
July | 369.00000 | 24.09538 | 65.90980 | -0.1540 | 6.05409 |
August | 379.00000 | 24.08029 | 64.04770 | -0.1640 | 6.03495 |
September | 360.00000 | 24.06688 | 64.87780 | -0.1733 | 6.10932 |
October | 371.00000 | 24.03652 | 56.40838 | 0.60484 | 13.20200 |
November | 360.00000 | 23.84958 | 47.89605 | 0.45590 | 10.01138 |
December | 369.00000 | 23.14596 | 45.63039 | 0.24798 | 8.80791 |
Annual Sum or Average | 4395.00000 | 23.70390 | 54.81382 | 0.12201 | 8.23174 |
Minimum of Months | 336.00000 | 22.65791 | 42.80429 | -0.2188 | 6.03495 |
Maximum of Months | 379.00000 | 24.09538 | 65.90980 | 0.60484 | 13.20200 |
Report: OccupantComfortDataSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 22.53137 | 44.46394 | 0.05273 | 7.74802 |
February | 308.00000 | 23.01100 | 49.04639 | 0.20088 | 8.55748 |
March | 348.00000 | 23.17321 | 47.25583 | 0.22287 | 8.45257 |
April | 330.00000 | 23.87421 | 54.27760 | 0.47505 | 10.14565 |
May | 344.00000 | 23.95785 | 63.25194 | -0.2547 | 6.59073 |
June | 336.00000 | 23.95579 | 63.40087 | -0.2342 | 6.40967 |
July | 338.00000 | 23.98013 | 67.55667 | -0.1864 | 6.07924 |
August | 348.00000 | 23.95100 | 65.62051 | -0.1992 | 6.07127 |
September | 330.00000 | 23.97298 | 66.56589 | -0.1999 | 6.21133 |
October | 340.00000 | 23.94015 | 57.90666 | 0.58754 | 12.68337 |
November | 330.00000 | 23.79285 | 49.23959 | 0.43598 | 9.62430 |
December | 338.00000 | 23.04154 | 47.15161 | 0.21462 | 8.58792 |
Annual Sum or Average | 4030.00000 | 23.60102 | 56.36562 | 0.09075 | 8.08656 |
Minimum of Months | 308.00000 | 22.53137 | 44.46394 | -0.2547 | 6.07127 |
Maximum of Months | 348.00000 | 23.98013 | 67.55667 | 0.58754 | 12.68337 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 22.50156 | 44.48059 | 0.03584 | 7.73345 |
February | 308.00000 | 22.98513 | 49.09517 | 0.18447 | 8.46286 |
March | 348.00000 | 23.15477 | 47.29207 | 0.20827 | 8.34002 |
April | 330.00000 | 23.87222 | 54.30859 | 0.46268 | 9.89863 |
May | 344.00000 | 23.95707 | 63.31207 | -0.2762 | 6.82502 |
June | 336.00000 | 23.95485 | 63.47800 | -0.2573 | 6.64009 |
July | 338.00000 | 23.97909 | 67.70268 | -0.2096 | 6.26244 |
August | 348.00000 | 23.95009 | 65.75020 | -0.2233 | 6.27688 |
September | 330.00000 | 23.97194 | 66.73060 | -0.2224 | 6.39839 |
October | 340.00000 | 23.93978 | 57.99931 | 0.57145 | 12.27831 |
November | 330.00000 | 23.78965 | 49.27184 | 0.42321 | 9.39546 |
December | 338.00000 | 23.02611 | 47.14703 | 0.19996 | 8.46401 |
Annual Sum or Average | 4030.00000 | 23.59279 | 56.43498 | 0.07252 | 8.07250 |
Minimum of Months | 308.00000 | 22.50156 | 44.48059 | -0.2762 | 6.26244 |
Maximum of Months | 348.00000 | 23.97909 | 67.70268 | 0.57145 | 12.27831 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 22.47785 | 44.56345 | 0.02725 | 7.74522 |
February | 308.00000 | 22.96020 | 49.22152 | 0.17561 | 8.44228 |
March | 348.00000 | 23.13561 | 47.39666 | 0.20095 | 8.31750 |
April | 330.00000 | 23.86749 | 54.40698 | 0.45943 | 9.84958 |
May | 344.00000 | 23.95675 | 63.40931 | -0.2782 | 6.84591 |
June | 336.00000 | 23.95457 | 63.56743 | -0.2592 | 6.65853 |
July | 338.00000 | 23.97875 | 67.79225 | -0.2113 | 6.27425 |
August | 348.00000 | 23.94985 | 65.83133 | -0.2249 | 6.28995 |
September | 330.00000 | 23.97163 | 66.81966 | -0.2241 | 6.41117 |
October | 340.00000 | 23.93849 | 58.07906 | 0.56992 | 12.24483 |
November | 330.00000 | 23.78209 | 49.35440 | 0.41945 | 9.35166 |
December | 338.00000 | 23.00458 | 47.24885 | 0.19240 | 8.44241 |
Annual Sum or Average | 4030.00000 | 23.58418 | 56.52832 | 0.06841 | 8.06422 |
Minimum of Months | 308.00000 | 22.47785 | 44.56345 | -0.2782 | 6.27425 |
Maximum of Months | 348.00000 | 23.97875 | 67.79225 | 0.56992 | 12.24483 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 22.42612 | 44.76822 | 0.01059 | 7.80554 |
February | 308.00000 | 22.90073 | 49.54358 | 0.15700 | 8.44249 |
March | 348.00000 | 23.08726 | 47.64580 | 0.18508 | 8.30861 |
April | 330.00000 | 23.85035 | 54.64001 | 0.45258 | 9.77065 |
May | 344.00000 | 23.95639 | 63.53569 | -0.2769 | 6.82969 |
June | 336.00000 | 23.95442 | 63.63498 | -0.2570 | 6.63479 |
July | 338.00000 | 23.97872 | 67.81041 | -0.2080 | 6.24712 |
August | 348.00000 | 23.94991 | 65.81304 | -0.2212 | 6.25746 |
September | 330.00000 | 23.97169 | 66.84707 | -0.2210 | 6.38739 |
October | 340.00000 | 23.93507 | 58.13199 | 0.57027 | 12.27211 |
November | 330.00000 | 23.76122 | 49.52044 | 0.41271 | 9.30241 |
December | 338.00000 | 22.95162 | 47.47512 | 0.17638 | 8.44073 |
Annual Sum or Average | 4030.00000 | 23.56322 | 56.66645 | 0.06293 | 8.04983 |
Minimum of Months | 308.00000 | 22.42612 | 44.76822 | -0.2769 | 6.24712 |
Maximum of Months | 348.00000 | 23.97872 | 67.81041 | 0.57027 | 12.27211 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 22.39684 | 44.68150 | -0.0071 | 8.04601 |
February | 308.00000 | 22.83082 | 49.59003 | 0.12983 | 8.59564 |
March | 348.00000 | 23.02738 | 47.53878 | 0.16265 | 8.50680 |
April | 330.00000 | 23.82050 | 54.57527 | 0.44871 | 9.83474 |
May | 344.00000 | 23.96031 | 62.81901 | -0.2443 | 6.50505 |
June | 336.00000 | 23.95926 | 62.51971 | -0.2167 | 6.27963 |
July | 338.00000 | 23.98669 | 66.36611 | -0.1632 | 5.97873 |
August | 348.00000 | 23.95657 | 64.36717 | -0.1730 | 5.92506 |
September | 330.00000 | 23.97981 | 65.62305 | -0.1801 | 6.13954 |
October | 340.00000 | 23.93269 | 57.27418 | 0.59189 | 12.91682 |
November | 330.00000 | 23.74052 | 49.21997 | 0.41234 | 9.45355 |
December | 338.00000 | 22.89420 | 47.51087 | 0.15515 | 8.65701 |
Annual Sum or Average | 4030.00000 | 23.54373 | 56.05378 | 0.07452 | 8.06026 |
Minimum of Months | 308.00000 | 22.39684 | 44.68150 | -0.2443 | 5.92506 |
Maximum of Months | 348.00000 | 23.98669 | 66.36611 | 0.59189 | 12.91682 |
Report: DXReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.439586E+10 | 0.112190E+10 | 125.34 | 0.275181E+10 | 0.164405E+10 | 0.00 | 0.80 | 19-JAN-15:00 | 0.00 | 01-JAN-00:05 | 21609.48 | 19-JAN-15:00 | 14140.80 | 01-JAN-14:00 | 9151.87 | 19-JAN-15:00 | 5123.90 | 19-JAN-15:00 | 0.00 | 01-JAN-00:05 |
February | 0.571307E+10 | 0.145096E+10 | 158.76 | 0.357160E+10 | 0.214147E+10 | 0.00 | 0.84 | 24-FEB-14:00 | 0.00 | 01-FEB-00:05 | 22473.74 | 24-FEB-14:00 | 14212.60 | 24-FEB-14:00 | 10268.68 | 28-FEB-08:63 | 5467.76 | 24-FEB-14:00 | 0.00 | 01-FEB-00:05 |
March | 0.841796E+10 | 0.215851E+10 | 230.31 | 0.543074E+10 | 0.298722E+10 | 0.00 | 0.87 | 30-MAR-13:00 | 0.00 | 01-MAR-00:05 | 23610.87 | 30-MAR-13:00 | 16368.16 | 26-MAR-14:00 | 12373.08 | 07-MAR-08:63 | 5835.57 | 30-MAR-13:00 | 0.00 | 01-MAR-00:05 |
April | 0.160068E+11 | 0.409567E+10 | 369.39 | 0.104391E+11 | 0.556762E+10 | 0.00 | 1.00 | 23-APR-07:03 | 0.00 | 01-APR-00:05 | 57860.64 | 29-APR-07:03 | 31393.91 | 29-APR-07:03 | 28464.68 | 30-APR-07:03 | 12477.48 | 29-APR-07:03 | 0.00 | 01-APR-00:05 |
May | 0.363427E+11 | 0.906932E+10 | 496.00 | 0.220124E+11 | 0.143304E+11 | 0.00 | 1.00 | 01-MAY-07:03 | 0.00 | 01-MAY-00:10 | 59932.44 | 24-MAY-07:02 | 38731.51 | 07-MAY-07:02 | 29789.42 | 24-MAY-07:02 | 13052.35 | 27-MAY-07:02 | 0.00 | 01-MAY-00:10 |
June | 0.388334E+11 | 0.962670E+10 | 482.65 | 0.233175E+11 | 0.155159E+11 | 0.00 | 1.00 | 01-JUN-07:03 | 0.00 | 01-JUN-00:10 | 59247.03 | 19-JUN-07:02 | 39468.97 | 11-JUN-07:02 | 27741.61 | 19-JUN-07:02 | 13352.23 | 17-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.442299E+11 | 0.107597E+11 | 497.49 | 0.246327E+11 | 0.195972E+11 | 0.00 | 1.00 | 01-JUL-07:02 | 0.00 | 01-JUL-00:05 | 60210.24 | 02-JUL-07:02 | 38101.37 | 09-JUL-07:01 | 30219.09 | 02-JUL-07:03 | 13293.22 | 09-JUL-07:01 | 0.00 | 01-JUL-00:05 |
August | 0.436775E+11 | 0.106489E+11 | 498.46 | 0.252055E+11 | 0.184720E+11 | 0.00 | 1.00 | 01-AUG-07:02 | 0.00 | 01-AUG-00:10 | 59979.08 | 10-AUG-07:02 | 41474.04 | 31-AUG-07:02 | 28826.68 | 10-AUG-07:03 | 13099.30 | 22-AUG-07:01 | 0.00 | 01-AUG-00:10 |
September | 0.386950E+11 | 0.935564E+10 | 482.69 | 0.216741E+11 | 0.170210E+11 | 0.00 | 1.00 | 01-SEP-07:02 | 0.00 | 01-SEP-00:05 | 60743.82 | 05-SEP-07:02 | 37890.91 | 22-SEP-07:02 | 31920.28 | 05-SEP-07:03 | 13869.29 | 10-SEP-07:13 | 0.00 | 01-SEP-00:05 |
October | 0.328516E+11 | 0.801325E+10 | 456.31 | 0.198010E+11 | 0.130506E+11 | 0.00 | 1.00 | 01-OCT-07:03 | 0.00 | 01-OCT-00:10 | 60133.62 | 25-OCT-07:02 | 45473.87 | 26-OCT-07:02 | 29831.77 | 15-OCT-07:02 | 13138.09 | 14-OCT-07:02 | 0.00 | 01-OCT-00:10 |
November | 0.126808E+11 | 0.315755E+10 | 294.31 | 0.791691E+10 | 0.476385E+10 | 0.00 | 1.00 | 01-NOV-07:03 | 0.00 | 01-NOV-00:10 | 58476.88 | 02-NOV-07:02 | 36805.51 | 07-NOV-08:62 | 28630.42 | 04-NOV-07:03 | 12569.23 | 01-NOV-07:03 | 0.00 | 01-NOV-00:10 |
December | 0.818360E+10 | 0.204570E+10 | 188.70 | 0.507758E+10 | 0.310602E+10 | 0.00 | 1.00 | 11-DEC-08:62 | 0.00 | 01-DEC-00:10 | 56788.36 | 15-DEC-08:62 | 33107.75 | 11-DEC-08:62 | 25242.42 | 13-DEC-08:62 | 12072.05 | 15-DEC-08:62 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.290028E+12 | 0.715038E+11 | 4280.42 | 0.171831E+12 | 0.118197E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.439586E+10 | 0.112190E+10 | 125.34 | 0.275181E+10 | 0.164405E+10 | 0.00 | 0.80 | 0.00 | 21609.48 | 14140.80 | 9151.87 | 5123.90 | 0.00 | |||||||
Maximum of Months | 0.442299E+11 | 0.107597E+11 | 498.46 | 0.252055E+11 | 0.195972E+11 | 0.00 | 1.00 | 0.00 | 60743.82 | 45473.87 | 31920.28 | 13869.29 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.269158E+10 | 0.671651E+09 | 139.65 | 0.173798E+10 | 0.953597E+09 | 0.00 | 1.00 | 01-JAN-18:02 | 0.00 | 01-JAN-00:05 | 29602.43 | 01-JAN-18:02 | 19010.00 | 29-JAN-18:07 | 13862.10 | 01-JAN-18:02 | 6255.18 | 01-JAN-18:02 | 0.00 | 01-JAN-00:05 |
February | 0.355103E+10 | 0.884296E+09 | 178.46 | 0.227498E+10 | 0.127605E+10 | 0.00 | 1.00 | 20-FEB-18:02 | 0.00 | 01-FEB-00:05 | 29993.13 | 28-FEB-21:50 | 15959.10 | 20-FEB-18:08 | 16538.12 | 28-FEB-21:50 | 6309.92 | 28-FEB-21:50 | 0.00 | 01-FEB-00:05 |
March | 0.512244E+10 | 0.128493E+10 | 245.33 | 0.342112E+10 | 0.170132E+10 | 0.00 | 1.00 | 04-MAR-19:01 | 0.00 | 01-MAR-00:05 | 28261.19 | 24-MAR-20:30 | 23716.89 | 04-MAR-19:01 | 9537.65 | 24-MAR-20:30 | 6017.40 | 24-MAR-20:30 | 0.00 | 01-MAR-00:05 |
April | 0.910047E+10 | 0.228537E+10 | 392.09 | 0.614873E+10 | 0.295174E+10 | 0.00 | 1.00 | 02-APR-17:02 | 0.00 | 01-APR-00:05 | 29516.15 | 15-APR-18:10 | 24597.61 | 17-APR-20:01 | 15781.87 | 15-APR-18:10 | 6242.16 | 15-APR-18:10 | 0.00 | 01-APR-00:05 |
May | 0.183901E+11 | 0.455081E+10 | 496.59 | 0.115696E+11 | 0.682045E+10 | 0.00 | 1.00 | 01-MAY-07:03 | 0.00 | 01-MAY-00:10 | 30433.23 | 22-MAY-07:02 | 23853.38 | 07-MAY-07:02 | 10818.03 | 22-MAY-07:02 | 6719.75 | 22-MAY-07:02 | 0.00 | 01-MAY-00:10 |
June | 0.194155E+11 | 0.478365E+10 | 483.81 | 0.120754E+11 | 0.734010E+10 | 0.00 | 1.00 | 01-JUN-07:03 | 0.00 | 01-JUN-00:10 | 29801.88 | 05-JUN-07:02 | 24506.35 | 26-JUN-07:02 | 9687.77 | 29-JUN-17:00 | 6814.53 | 17-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.218570E+11 | 0.529973E+10 | 498.46 | 0.126568E+11 | 0.920020E+10 | 0.00 | 1.00 | 01-JUL-07:02 | 0.00 | 01-JUL-00:05 | 30453.09 | 03-JUL-07:02 | 23546.15 | 09-JUL-07:01 | 10666.59 | 02-JUL-07:02 | 6804.77 | 04-JUL-07:01 | 0.00 | 01-JUL-00:05 |
August | 0.215406E+11 | 0.522803E+10 | 498.90 | 0.128492E+11 | 0.869134E+10 | 0.00 | 1.00 | 01-AUG-07:02 | 0.00 | 01-AUG-00:10 | 30647.12 | 16-AUG-07:02 | 24585.59 | 31-AUG-07:02 | 11398.57 | 16-AUG-07:02 | 6719.91 | 10-AUG-07:02 | 0.00 | 01-AUG-00:10 |
September | 0.192287E+11 | 0.462031E+10 | 483.03 | 0.111841E+11 | 0.804457E+10 | 0.00 | 1.00 | 01-SEP-07:02 | 0.00 | 01-SEP-00:05 | 30929.68 | 05-SEP-07:02 | 23977.31 | 02-SEP-07:02 | 12056.79 | 05-SEP-07:02 | 7175.51 | 10-SEP-07:01 | 0.00 | 01-SEP-00:05 |
October | 0.166555E+11 | 0.403131E+10 | 461.23 | 0.104192E+11 | 0.623630E+10 | 0.00 | 1.00 | 01-OCT-07:03 | 0.00 | 01-OCT-00:10 | 30550.03 | 08-OCT-07:01 | 24646.27 | 26-OCT-07:02 | 10896.67 | 24-OCT-13:30 | 6755.35 | 14-OCT-07:02 | 0.00 | 01-OCT-00:10 |
November | 0.704262E+10 | 0.172425E+10 | 307.36 | 0.455151E+10 | 0.249111E+10 | 0.00 | 1.00 | 01-NOV-07:03 | 0.00 | 01-NOV-00:10 | 29911.38 | 29-NOV-21:02 | 22366.99 | 02-NOV-07:02 | 15670.67 | 29-NOV-21:02 | 6387.46 | 02-NOV-07:02 | 0.00 | 01-NOV-00:10 |
December | 0.449626E+10 | 0.110685E+10 | 201.73 | 0.290348E+10 | 0.159277E+10 | 0.00 | 1.00 | 08-DEC-21:22 | 0.00 | 01-DEC-00:10 | 29323.51 | 08-DEC-22:44 | 19377.69 | 11-DEC-08:62 | 13657.54 | 08-DEC-22:44 | 6211.92 | 08-DEC-22:44 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.149092E+12 | 0.364712E+11 | 4386.64 | 0.917922E+11 | 0.572995E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.269158E+10 | 0.671651E+09 | 139.65 | 0.173798E+10 | 0.953597E+09 | 0.00 | 1.00 | 0.00 | 28261.19 | 15959.10 | 9537.65 | 6017.40 | 0.00 | |||||||
Maximum of Months | 0.218570E+11 | 0.529973E+10 | 498.90 | 0.128492E+11 | 0.920020E+10 | 0.00 | 1.00 | 0.00 | 30929.68 | 24646.27 | 16538.12 | 7175.51 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_3:3 COOLING COIL
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.200232E+10 | 0.503591E+09 | 105.08 | 0.127987E+10 | 0.722451E+09 | 0.00 | 0.87 | 20-JAN-07:03 | 0.00 | 01-JAN-00:05 | 12417.18 | 20-JAN-07:03 | 7318.28 | 01-JAN-14:00 | 6936.63 | 20-JAN-07:03 | 2737.83 | 20-JAN-07:03 | 0.00 | 01-JAN-00:05 |
February | 0.275951E+10 | 0.689844E+09 | 141.53 | 0.174614E+10 | 0.101337E+10 | 0.00 | 0.95 | 28-FEB-07:03 | 0.00 | 01-FEB-00:05 | 13910.97 | 28-FEB-07:03 | 7555.80 | 02-FEB-13:30 | 7249.03 | 28-FEB-07:03 | 2986.73 | 28-FEB-07:03 | 0.00 | 01-FEB-00:05 |
March | 0.387016E+10 | 0.974710E+09 | 190.00 | 0.253134E+10 | 0.133882E+10 | 0.00 | 1.00 | 07-MAR-07:03 | 0.00 | 01-MAR-00:05 | 18185.93 | 07-MAR-07:03 | 10099.68 | 07-MAR-07:03 | 8321.56 | 30-MAR-06:03 | 3774.96 | 07-MAR-07:03 | 0.00 | 01-MAR-00:05 |
April | 0.689545E+10 | 0.173669E+10 | 296.85 | 0.459164E+10 | 0.230382E+10 | 0.00 | 1.00 | 22-APR-06:03 | 0.00 | 01-APR-00:05 | 31390.12 | 29-APR-06:03 | 18909.29 | 28-APR-06:03 | 17347.14 | 30-APR-07:03 | 6550.38 | 29-APR-06:03 | 0.00 | 01-APR-00:05 |
May | 0.150759E+11 | 0.369355E+10 | 368.45 | 0.921194E+10 | 0.586394E+10 | 0.00 | 1.00 | 01-MAY-06:03 | 0.00 | 01-MAY-00:10 | 32186.06 | 21-MAY-07:02 | 20581.82 | 12-MAY-06:02 | 17142.19 | 21-MAY-07:02 | 6777.77 | 28-MAY-07:02 | 0.00 | 01-MAY-00:10 |
June | 0.161525E+11 | 0.393171E+10 | 359.14 | 0.973434E+10 | 0.641813E+10 | 0.00 | 1.00 | 01-JUN-06:03 | 0.00 | 01-JUN-00:10 | 32683.85 | 19-JUN-06:02 | 21079.53 | 14-JUN-06:02 | 18943.50 | 19-JUN-06:02 | 6903.57 | 18-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.179543E+11 | 0.428958E+10 | 364.25 | 0.999774E+10 | 0.795661E+10 | 0.00 | 1.00 | 01-JUL-06:02 | 0.00 | 01-JUL-00:05 | 32715.06 | 03-JUL-06:01 | 18944.99 | 19-JUL-06:01 | 18700.20 | 31-JUL-06:02 | 6943.14 | 09-JUL-07:01 | 0.00 | 01-JUL-00:05 |
August | 0.180661E+11 | 0.432804E+10 | 373.59 | 0.103930E+11 | 0.767310E+10 | 0.00 | 1.00 | 01-AUG-06:02 | 0.00 | 01-AUG-00:10 | 32704.70 | 14-AUG-06:01 | 21005.41 | 31-AUG-06:02 | 19152.78 | 14-AUG-06:03 | 6766.82 | 06-AUG-07:03 | 0.00 | 01-AUG-00:10 |
September | 0.156732E+11 | 0.371205E+10 | 354.86 | 0.873272E+10 | 0.694046E+10 | 0.00 | 1.00 | 01-SEP-06:02 | 0.00 | 01-SEP-00:05 | 32751.26 | 05-SEP-06:02 | 20078.22 | 23-SEP-06:02 | 18595.55 | 05-SEP-06:02 | 7204.61 | 10-SEP-07:13 | 0.00 | 01-SEP-00:05 |
October | 0.133715E+11 | 0.320267E+10 | 338.91 | 0.808264E+10 | 0.528883E+10 | 0.00 | 1.00 | 01-OCT-07:03 | 0.00 | 01-OCT-00:10 | 32637.14 | 08-OCT-07:01 | 23099.21 | 26-OCT-06:02 | 17884.19 | 08-OCT-07:03 | 6801.87 | 07-OCT-06:03 | 0.00 | 01-OCT-00:10 |
November | 0.554157E+10 | 0.135927E+10 | 253.46 | 0.352074E+10 | 0.202083E+10 | 0.00 | 1.00 | 01-NOV-06:03 | 0.00 | 01-NOV-00:10 | 31321.69 | 02-NOV-06:02 | 20185.22 | 07-NOV-07:03 | 17083.92 | 04-NOV-06:02 | 6566.92 | 02-NOV-06:02 | 0.00 | 01-NOV-00:10 |
December | 0.357472E+10 | 0.878438E+09 | 159.50 | 0.224676E+10 | 0.132796E+10 | 0.00 | 1.00 | 11-DEC-07:03 | 0.00 | 01-DEC-00:10 | 31150.20 | 15-DEC-07:03 | 17871.28 | 12-DEC-07:03 | 17860.27 | 16-DEC-07:03 | 6441.09 | 15-DEC-07:03 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.120937E+12 | 0.293001E+11 | 3305.61 | 0.720689E+11 | 0.488683E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.200232E+10 | 0.503591E+09 | 105.08 | 0.127987E+10 | 0.722451E+09 | 0.00 | 0.87 | 0.00 | 12417.18 | 7318.28 | 6936.63 | 2737.83 | 0.00 | |||||||
Maximum of Months | 0.180661E+11 | 0.432804E+10 | 373.59 | 0.103930E+11 | 0.795661E+10 | 0.00 | 1.00 | 0.00 | 32751.26 | 23099.21 | 19152.78 | 7204.61 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_4:4 COOLING COIL
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.192531E+10 | 0.485347E+09 | 101.50 | 0.122658E+10 | 0.698725E+09 | 0.00 | 0.84 | 20-JAN-07:03 | 0.00 | 01-JAN-00:05 | 11761.85 | 20-JAN-07:03 | 7285.41 | 01-JAN-14:00 | 6574.40 | 20-JAN-07:03 | 2625.18 | 20-JAN-07:03 | 0.00 | 01-JAN-00:05 |
February | 0.269303E+10 | 0.674475E+09 | 140.19 | 0.170042E+10 | 0.992609E+09 | 0.00 | 0.91 | 28-FEB-07:03 | 0.00 | 01-FEB-00:05 | 13163.55 | 28-FEB-07:03 | 7505.18 | 02-FEB-13:30 | 6864.16 | 28-FEB-07:03 | 2864.60 | 28-FEB-07:03 | 0.00 | 01-FEB-00:05 |
March | 0.380490E+10 | 0.959641E+09 | 186.67 | 0.248244E+10 | 0.132246E+10 | 0.00 | 1.00 | 07-MAR-07:03 | 0.00 | 01-MAR-00:05 | 17262.15 | 07-MAR-07:03 | 9534.34 | 07-MAR-07:03 | 8099.41 | 30-MAR-06:03 | 3584.18 | 07-MAR-07:03 | 0.00 | 01-MAR-00:05 |
April | 0.685023E+10 | 0.172675E+10 | 295.01 | 0.455745E+10 | 0.229278E+10 | 0.00 | 1.00 | 22-APR-06:03 | 0.00 | 01-APR-00:05 | 31482.16 | 29-APR-06:03 | 18990.63 | 28-APR-06:03 | 17394.24 | 30-APR-07:03 | 6569.21 | 29-APR-06:03 | 0.00 | 01-APR-00:05 |
May | 0.151013E+11 | 0.370073E+10 | 368.41 | 0.923069E+10 | 0.587056E+10 | 0.00 | 1.00 | 01-MAY-06:03 | 0.00 | 01-MAY-00:10 | 32279.47 | 21-MAY-07:02 | 20676.46 | 12-MAY-06:02 | 17184.43 | 21-MAY-07:02 | 6797.14 | 28-MAY-07:02 | 0.00 | 01-MAY-00:10 |
June | 0.161935E+11 | 0.394225E+10 | 359.00 | 0.976462E+10 | 0.642888E+10 | 0.00 | 1.00 | 01-JUN-06:03 | 0.00 | 01-JUN-00:10 | 32784.09 | 19-JUN-06:02 | 21184.50 | 14-JUN-06:02 | 18955.01 | 19-JUN-06:02 | 6923.30 | 18-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.180196E+11 | 0.430543E+10 | 364.52 | 0.100445E+11 | 0.797515E+10 | 0.00 | 1.00 | 01-JUL-06:02 | 0.00 | 01-JUL-00:05 | 32808.55 | 03-JUL-06:01 | 19041.88 | 19-JUL-06:01 | 18703.65 | 31-JUL-06:02 | 6962.96 | 09-JUL-07:01 | 0.00 | 01-JUL-00:05 |
August | 0.181187E+11 | 0.434102E+10 | 373.72 | 0.104313E+11 | 0.768744E+10 | 0.00 | 1.00 | 01-AUG-06:02 | 0.00 | 01-AUG-00:10 | 32798.16 | 14-AUG-06:01 | 21108.76 | 31-AUG-06:02 | 19136.86 | 14-AUG-06:03 | 6785.89 | 06-AUG-07:03 | 0.00 | 01-AUG-00:10 |
September | 0.157199E+11 | 0.372358E+10 | 355.02 | 0.876610E+10 | 0.695383E+10 | 0.00 | 1.00 | 01-SEP-06:02 | 0.00 | 01-SEP-00:05 | 32844.86 | 05-SEP-06:02 | 20160.17 | 23-SEP-06:02 | 18564.22 | 05-SEP-06:02 | 7225.20 | 10-SEP-07:13 | 0.00 | 01-SEP-00:05 |
October | 0.133982E+11 | 0.320956E+10 | 338.19 | 0.810214E+10 | 0.529607E+10 | 0.00 | 1.00 | 01-OCT-07:03 | 0.00 | 01-OCT-00:10 | 32739.08 | 08-OCT-07:01 | 23168.24 | 26-OCT-06:02 | 17889.25 | 08-OCT-07:03 | 6821.17 | 07-OCT-06:03 | 0.00 | 01-OCT-00:10 |
November | 0.548976E+10 | 0.134715E+10 | 249.55 | 0.348188E+10 | 0.200788E+10 | 0.00 | 1.00 | 01-NOV-06:03 | 0.00 | 01-NOV-00:10 | 31415.42 | 03-NOV-06:02 | 20249.17 | 07-NOV-07:03 | 17131.54 | 04-NOV-06:02 | 6585.79 | 02-NOV-06:02 | 0.00 | 01-NOV-00:10 |
December | 0.353073E+10 | 0.868081E+09 | 156.67 | 0.221441E+10 | 0.131632E+10 | 0.00 | 1.00 | 11-DEC-07:03 | 0.00 | 01-DEC-00:10 | 31241.33 | 15-DEC-07:03 | 17912.27 | 15-DEC-07:03 | 17913.98 | 16-DEC-07:03 | 6459.66 | 15-DEC-07:03 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.120845E+12 | 0.292840E+11 | 3288.45 | 0.720025E+11 | 0.488427E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.192531E+10 | 0.485347E+09 | 101.50 | 0.122658E+10 | 0.698725E+09 | 0.00 | 0.84 | 0.00 | 11761.85 | 7285.41 | 6574.40 | 2625.18 | 0.00 | |||||||
Maximum of Months | 0.181187E+11 | 0.434102E+10 | 373.72 | 0.104313E+11 | 0.797515E+10 | 0.00 | 1.00 | 0.00 | 32844.86 | 23168.24 | 19136.86 | 7225.20 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_5:5 COOLING COIL
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.180236E+10 | 0.455820E+09 | 97.50 | 0.114267E+10 | 0.659683E+09 | 0.00 | 0.77 | 19-JAN-14:00 | 0.00 | 01-JAN-00:05 | 10791.97 | 19-JAN-14:00 | 7138.05 | 01-JAN-14:00 | 4871.36 | 20-JAN-07:03 | 2539.08 | 19-JAN-14:00 | 0.00 | 01-JAN-00:05 |
February | 0.253990E+10 | 0.637898E+09 | 133.61 | 0.159537E+10 | 0.944539E+09 | 0.00 | 0.81 | 24-FEB-13:50 | 0.00 | 01-FEB-00:05 | 11221.64 | 24-FEB-13:50 | 7320.48 | 02-FEB-13:30 | 5502.17 | 28-FEB-07:03 | 2723.32 | 24-FEB-13:10 | 0.00 | 01-FEB-00:05 |
March | 0.362376E+10 | 0.916363E+09 | 182.58 | 0.235048E+10 | 0.127328E+10 | 0.00 | 0.95 | 07-MAR-07:03 | 0.00 | 01-MAR-00:05 | 14383.64 | 07-MAR-07:03 | 8189.69 | 26-MAR-14:00 | 6688.00 | 30-MAR-06:03 | 3036.37 | 07-MAR-07:03 | 0.00 | 01-MAR-00:05 |
April | 0.659031E+10 | 0.166386E+10 | 287.10 | 0.437144E+10 | 0.221887E+10 | 0.00 | 1.00 | 23-APR-07:03 | 0.00 | 01-APR-00:05 | 31203.17 | 29-APR-06:03 | 16963.58 | 28-APR-06:03 | 17269.89 | 30-APR-07:03 | 6512.23 | 29-APR-06:03 | 0.00 | 01-APR-00:05 |
May | 0.148388E+11 | 0.363915E+10 | 368.65 | 0.904149E+10 | 0.579734E+10 | 0.00 | 1.00 | 01-MAY-06:03 | 0.00 | 01-MAY-00:10 | 31981.74 | 21-MAY-07:02 | 20348.70 | 12-MAY-06:02 | 17169.49 | 21-MAY-07:02 | 6738.56 | 28-MAY-07:02 | 0.00 | 01-MAY-00:10 |
June | 0.159456E+11 | 0.388307E+10 | 359.13 | 0.958363E+10 | 0.636200E+10 | 0.00 | 1.00 | 01-JUN-06:03 | 0.00 | 01-JUN-00:10 | 32488.10 | 19-JUN-06:02 | 20835.16 | 14-JUN-06:02 | 18908.23 | 19-JUN-06:02 | 6863.61 | 18-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.177727E+11 | 0.424671E+10 | 364.21 | 0.987086E+10 | 0.790182E+10 | 0.00 | 1.00 | 01-JUL-06:02 | 0.00 | 01-JUL-00:05 | 32525.79 | 03-JUL-06:01 | 18697.59 | 19-JUL-06:01 | 18640.05 | 31-JUL-06:02 | 6902.97 | 09-JUL-07:01 | 0.00 | 01-JUL-00:05 |
August | 0.178685E+11 | 0.428138E+10 | 374.37 | 0.102518E+11 | 0.761667E+10 | 0.00 | 1.00 | 01-AUG-06:02 | 0.00 | 01-AUG-00:10 | 32515.48 | 14-AUG-06:01 | 20770.65 | 31-AUG-06:02 | 19081.52 | 14-AUG-06:03 | 6727.81 | 06-AUG-07:03 | 0.00 | 01-AUG-00:10 |
September | 0.154640E+11 | 0.366431E+10 | 354.82 | 0.858619E+10 | 0.687784E+10 | 0.00 | 1.00 | 01-SEP-06:02 | 0.00 | 01-SEP-00:05 | 32561.78 | 05-SEP-06:02 | 19846.06 | 23-SEP-06:02 | 18480.47 | 05-SEP-06:02 | 7162.75 | 10-SEP-07:13 | 0.00 | 01-SEP-00:05 |
October | 0.131801E+11 | 0.315816E+10 | 336.27 | 0.794199E+10 | 0.523808E+10 | 0.00 | 1.00 | 01-OCT-07:03 | 0.00 | 01-OCT-00:10 | 32444.82 | 08-OCT-07:01 | 22931.81 | 26-OCT-06:02 | 17821.86 | 08-OCT-07:03 | 6762.53 | 07-OCT-06:03 | 0.00 | 01-OCT-00:10 |
November | 0.529466E+10 | 0.130010E+10 | 241.16 | 0.333892E+10 | 0.195575E+10 | 0.00 | 1.00 | 01-NOV-06:03 | 0.00 | 01-NOV-00:10 | 31142.55 | 03-NOV-06:02 | 18827.30 | 07-NOV-07:03 | 17027.34 | 04-NOV-06:02 | 6528.64 | 02-NOV-06:02 | 0.00 | 01-NOV-00:10 |
December | 0.339648E+10 | 0.836064E+09 | 150.75 | 0.211763E+10 | 0.127885E+10 | 0.00 | 1.00 | 11-DEC-07:03 | 0.00 | 01-DEC-00:10 | 30964.25 | 15-DEC-07:03 | 17590.47 | 15-DEC-07:03 | 17287.38 | 11-DEC-07:03 | 6403.38 | 15-DEC-07:03 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.118317E+12 | 0.286829E+11 | 3250.14 | 0.701925E+11 | 0.481247E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.180236E+10 | 0.455820E+09 | 97.50 | 0.114267E+10 | 0.659683E+09 | 0.00 | 0.77 | 0.00 | 10791.97 | 7138.05 | 4871.36 | 2539.08 | 0.00 | |||||||
Maximum of Months | 0.178685E+11 | 0.428138E+10 | 374.37 | 0.102518E+11 | 0.790182E+10 | 0.00 | 1.00 | 0.00 | 32561.78 | 22931.81 | 19081.52 | 7162.75 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_6:6 COOLING COIL
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.288849E+10 | 0.741542E+09 | 90.53 | 0.179312E+10 | 0.109537E+10 | 0.00 | 0.80 | 19-JAN-14:00 | 0.00 | 01-JAN-00:05 | 19784.24 | 19-JAN-14:00 | 12257.20 | 01-JAN-14:10 | 8739.09 | 19-JAN-14:00 | 4684.11 | 19-JAN-14:00 | 0.00 | 01-JAN-00:05 |
February | 0.425662E+10 | 0.108406E+10 | 123.31 | 0.261238E+10 | 0.164424E+10 | 0.00 | 0.83 | 24-FEB-13:50 | 0.00 | 01-FEB-00:05 | 20579.76 | 24-FEB-13:40 | 13140.63 | 02-FEB-13:30 | 7900.24 | 28-FEB-08:63 | 5019.45 | 24-FEB-13:10 | 0.00 | 01-FEB-00:05 |
March | 0.612139E+10 | 0.156902E+10 | 175.08 | 0.388092E+10 | 0.224047E+10 | 0.00 | 0.90 | 30-MAR-13:00 | 0.00 | 01-MAR-00:05 | 22897.53 | 30-MAR-13:00 | 14348.93 | 26-MAR-14:00 | 9364.59 | 07-MAR-13:40 | 5576.36 | 30-MAR-13:00 | 0.00 | 01-MAR-00:05 |
April | 0.114975E+11 | 0.294080E+10 | 277.75 | 0.749560E+10 | 0.400195E+10 | 0.00 | 1.00 | 23-APR-08:63 | 0.00 | 01-APR-00:05 | 53394.92 | 29-APR-07:03 | 30185.43 | 29-APR-07:03 | 23209.49 | 29-APR-07:03 | 11576.00 | 29-APR-07:03 | 0.00 | 01-APR-00:05 |
May | 0.263224E+11 | 0.652024E+10 | 358.27 | 0.158070E+11 | 0.105154E+11 | 0.00 | 1.00 | 01-MAY-07:03 | 0.00 | 01-MAY-00:10 | 56106.21 | 21-MAY-08:62 | 36225.88 | 12-MAY-07:03 | 30544.95 | 21-MAY-08:62 | 12165.67 | 28-MAY-08:62 | 0.00 | 01-MAY-00:10 |
June | 0.284936E+11 | 0.701272E+10 | 350.76 | 0.168907E+11 | 0.116029E+11 | 0.00 | 1.00 | 01-JUN-07:03 | 0.00 | 01-JUN-00:10 | 56824.25 | 19-JUN-07:02 | 37225.26 | 14-JUN-07:02 | 33315.33 | 19-JUN-07:02 | 12289.30 | 17-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.316004E+11 | 0.763049E+10 | 351.38 | 0.172704E+11 | 0.143300E+11 | 0.00 | 1.00 | 01-JUL-07:02 | 0.00 | 01-JUL-00:05 | 57025.28 | 03-JUL-07:02 | 34869.28 | 19-JUL-07:02 | 33477.91 | 02-JUL-08:03 | 12471.66 | 09-JUL-08:04 | 0.00 | 01-JUL-00:05 |
August | 0.319647E+11 | 0.774929E+10 | 364.16 | 0.180817E+11 | 0.138831E+11 | 0.00 | 1.00 | 01-AUG-07:02 | 0.00 | 01-AUG-00:10 | 56943.02 | 14-AUG-07:02 | 38228.25 | 31-AUG-07:02 | 33578.82 | 14-AUG-07:03 | 12235.00 | 06-AUG-08:05 | 0.00 | 01-AUG-00:10 |
September | 0.273697E+11 | 0.654668E+10 | 343.81 | 0.148999E+11 | 0.124697E+11 | 0.00 | 1.00 | 01-SEP-07:02 | 0.00 | 01-SEP-00:05 | 57029.75 | 05-SEP-07:02 | 35219.61 | 23-SEP-07:02 | 32567.03 | 05-SEP-07:02 | 12947.70 | 10-SEP-08:13 | 0.00 | 01-SEP-00:05 |
October | 0.235917E+11 | 0.571737E+10 | 327.54 | 0.139926E+11 | 0.959904E+10 | 0.00 | 1.00 | 01-OCT-08:63 | 0.00 | 01-OCT-00:10 | 56828.91 | 08-OCT-08:62 | 41396.39 | 26-OCT-07:02 | 31634.65 | 08-OCT-08:62 | 12092.20 | 14-OCT-07:02 | 0.00 | 01-OCT-00:10 |
November | 0.924491E+10 | 0.229357E+10 | 223.39 | 0.570021E+10 | 0.354469E+10 | 0.00 | 1.00 | 01-NOV-07:03 | 0.00 | 01-NOV-00:10 | 53809.00 | 02-NOV-07:02 | 35444.33 | 07-NOV-08:62 | 27467.47 | 04-NOV-07:03 | 11570.47 | 02-NOV-07:02 | 0.00 | 01-NOV-00:10 |
December | 0.588801E+10 | 0.146351E+10 | 137.47 | 0.359490E+10 | 0.229311E+10 | 0.00 | 1.00 | 11-DEC-08:62 | 0.00 | 01-DEC-00:10 | 52439.36 | 11-DEC-08:62 | 29441.63 | 15-DEC-08:62 | 29700.45 | 11-DEC-08:62 | 11101.13 | 11-DEC-08:62 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.209239E+12 | 0.512693E+11 | 3123.46 | 0.122019E+12 | 0.872200E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.288849E+10 | 0.741542E+09 | 90.53 | 0.179312E+10 | 0.109537E+10 | 0.00 | 0.80 | 0.00 | 19784.24 | 12257.20 | 7900.24 | 4684.11 | 0.00 | |||||||
Maximum of Months | 0.319647E+11 | 0.774929E+10 | 364.16 | 0.180817E+11 | 0.143300E+11 | 0.00 | 1.00 | 0.00 | 57029.75 | 41396.39 | 33578.82 | 12947.70 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_7:7 COOLING COIL
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.146789E+10 | 0.370873E+09 | 89.19 | 0.911697E+09 | 0.556197E+09 | 0.00 | 0.79 | 19-JAN-14:00 | 0.00 | 01-JAN-00:05 | 10210.93 | 19-JAN-14:00 | 6373.24 | 01-JAN-14:10 | 4513.11 | 19-JAN-14:00 | 2382.90 | 19-JAN-14:00 | 0.00 | 01-JAN-00:05 |
February | 0.216931E+10 | 0.543790E+09 | 119.56 | 0.133144E+10 | 0.837870E+09 | 0.00 | 0.82 | 24-FEB-13:50 | 0.00 | 01-FEB-00:05 | 10667.87 | 24-FEB-13:50 | 6818.10 | 02-FEB-13:30 | 4101.71 | 24-FEB-13:10 | 2564.13 | 24-FEB-13:10 | 0.00 | 01-FEB-00:05 |
March | 0.312864E+10 | 0.789262E+09 | 172.75 | 0.198094E+10 | 0.114770E+10 | 0.00 | 0.90 | 30-MAR-13:00 | 0.00 | 01-MAR-00:05 | 11967.49 | 30-MAR-13:00 | 7479.25 | 26-MAR-14:00 | 4846.49 | 07-MAR-13:40 | 2867.33 | 30-MAR-13:00 | 0.00 | 01-MAR-00:05 |
April | 0.592755E+10 | 0.149219E+10 | 274.42 | 0.386721E+10 | 0.206034E+10 | 0.00 | 1.00 | 24-APR-07:03 | 0.00 | 01-APR-00:05 | 25444.43 | 29-APR-07:03 | 14367.17 | 29-APR-07:03 | 11077.26 | 29-APR-07:03 | 5423.61 | 29-APR-07:03 | 0.00 | 01-APR-00:05 |
May | 0.136708E+11 | 0.333546E+10 | 358.67 | 0.821845E+10 | 0.545236E+10 | 0.00 | 1.00 | 01-MAY-07:03 | 0.00 | 01-MAY-00:10 | 29452.61 | 21-MAY-08:62 | 18436.13 | 31-MAY-07:02 | 16075.81 | 21-MAY-08:62 | 6272.50 | 28-MAY-08:62 | 0.00 | 01-MAY-00:10 |
June | 0.147997E+11 | 0.358851E+10 | 352.16 | 0.878131E+10 | 0.601839E+10 | 0.00 | 1.00 | 01-JUN-07:03 | 0.00 | 01-JUN-00:10 | 29838.03 | 19-JUN-07:02 | 19536.40 | 14-JUN-07:02 | 17571.84 | 19-JUN-07:02 | 6335.85 | 17-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.164154E+11 | 0.390599E+10 | 351.96 | 0.898284E+10 | 0.743254E+10 | 0.00 | 1.00 | 01-JUL-07:02 | 0.00 | 01-JUL-00:05 | 29927.94 | 03-JUL-07:02 | 18303.87 | 19-JUL-07:02 | 17691.36 | 02-JUL-08:03 | 6430.70 | 09-JUL-08:04 | 0.00 | 01-JUL-00:05 |
August | 0.165950E+11 | 0.396396E+10 | 364.38 | 0.939789E+10 | 0.719707E+10 | 0.00 | 1.00 | 01-AUG-07:02 | 0.00 | 01-AUG-00:10 | 29884.76 | 14-AUG-07:02 | 20063.49 | 31-AUG-07:02 | 17742.29 | 14-AUG-07:03 | 6292.70 | 06-AUG-08:03 | 0.00 | 01-AUG-00:10 |
September | 0.142031E+11 | 0.334585E+10 | 343.88 | 0.774330E+10 | 0.645984E+10 | 0.00 | 1.00 | 01-SEP-07:02 | 0.00 | 01-SEP-00:05 | 29939.29 | 05-SEP-07:02 | 18481.23 | 23-SEP-07:02 | 17145.94 | 05-SEP-07:02 | 6676.07 | 10-SEP-08:13 | 0.00 | 01-SEP-00:05 |
October | 0.122322E+11 | 0.291879E+10 | 327.28 | 0.726120E+10 | 0.497100E+10 | 0.00 | 1.00 | 02-OCT-07:03 | 0.00 | 01-OCT-00:10 | 29832.23 | 08-OCT-08:62 | 21743.61 | 26-OCT-07:02 | 16666.33 | 08-OCT-08:62 | 6234.63 | 14-OCT-07:02 | 0.00 | 01-OCT-00:10 |
November | 0.474904E+10 | 0.115905E+10 | 220.77 | 0.292598E+10 | 0.182305E+10 | 0.00 | 1.00 | 01-NOV-07:03 | 0.00 | 01-NOV-00:10 | 28225.27 | 02-NOV-07:02 | 17340.11 | 03-NOV-07:03 | 12948.62 | 04-NOV-07:03 | 5964.90 | 02-NOV-07:02 | 0.00 | 01-NOV-00:10 |
December | 0.302982E+10 | 0.740937E+09 | 134.39 | 0.184958E+10 | 0.118025E+10 | 0.00 | 1.00 | 11-DEC-08:62 | 0.00 | 01-DEC-00:10 | 25101.35 | 11-DEC-08:62 | 13955.65 | 15-DEC-08:62 | 14246.76 | 11-DEC-08:62 | 5221.39 | 11-DEC-08:62 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.108388E+12 | 0.261547E+11 | 3109.42 | 0.632518E+11 | 0.451366E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.146789E+10 | 0.370873E+09 | 89.19 | 0.911697E+09 | 0.556197E+09 | 0.00 | 0.79 | 0.00 | 10210.93 | 6373.24 | 4101.71 | 2382.90 | 0.00 | |||||||
Maximum of Months | 0.165950E+11 | 0.396396E+10 | 364.38 | 0.939789E+10 | 0.743254E+10 | 0.00 | 1.00 | 0.00 | 29939.29 | 21743.61 | 17742.29 | 6676.07 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_8:8 COOLING COIL
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.143678E+10 | 0.363346E+09 | 88.06 | 0.891569E+09 | 0.545209E+09 | 0.00 | 0.78 | 19-JAN-14:00 | 0.00 | 01-JAN-00:05 | 10119.22 | 19-JAN-14:00 | 6313.34 | 01-JAN-14:10 | 4481.50 | 19-JAN-14:00 | 2363.39 | 19-JAN-14:00 | 0.00 | 01-JAN-00:05 |
February | 0.212560E+10 | 0.533275E+09 | 117.81 | 0.130291E+10 | 0.822687E+09 | 0.00 | 0.82 | 24-FEB-14:00 | 0.00 | 01-FEB-00:05 | 10576.18 | 24-FEB-13:50 | 6758.12 | 02-FEB-13:30 | 4076.56 | 24-FEB-13:10 | 2543.97 | 24-FEB-13:10 | 0.00 | 01-FEB-00:05 |
March | 0.307363E+10 | 0.775868E+09 | 170.33 | 0.194146E+10 | 0.113217E+10 | 0.00 | 0.90 | 30-MAR-13:00 | 0.00 | 01-MAR-00:05 | 11901.28 | 30-MAR-13:00 | 7408.42 | 26-MAR-14:00 | 4810.06 | 07-MAR-13:40 | 2851.81 | 30-MAR-13:00 | 0.00 | 01-MAR-00:05 |
April | 0.585608E+10 | 0.147468E+10 | 273.08 | 0.381638E+10 | 0.203970E+10 | 0.00 | 1.00 | 24-APR-07:03 | 0.00 | 01-APR-00:05 | 24707.82 | 29-APR-07:03 | 13895.47 | 29-APR-07:03 | 10812.35 | 29-APR-07:03 | 5266.64 | 29-APR-07:03 | 0.00 | 01-APR-00:05 |
May | 0.135963E+11 | 0.331707E+10 | 358.89 | 0.816625E+10 | 0.543010E+10 | 0.00 | 1.00 | 01-MAY-07:03 | 0.00 | 01-MAY-00:10 | 29324.46 | 21-MAY-08:62 | 18316.92 | 31-MAY-07:02 | 16037.00 | 21-MAY-08:62 | 6246.13 | 28-MAY-08:62 | 0.00 | 01-MAY-00:10 |
June | 0.147310E+11 | 0.357123E+10 | 352.11 | 0.873231E+10 | 0.599869E+10 | 0.00 | 1.00 | 01-JUN-07:03 | 0.00 | 01-JUN-00:10 | 29712.31 | 19-JUN-07:02 | 19424.21 | 14-JUN-07:02 | 17528.43 | 19-JUN-07:02 | 6309.25 | 17-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.163502E+11 | 0.388963E+10 | 351.76 | 0.893807E+10 | 0.741216E+10 | 0.00 | 1.00 | 01-JUL-07:02 | 0.00 | 01-JUL-00:05 | 29801.84 | 03-JUL-07:02 | 18191.02 | 19-JUL-07:02 | 17640.78 | 02-JUL-08:03 | 6403.61 | 09-JUL-08:04 | 0.00 | 01-JUL-00:05 |
August | 0.165314E+11 | 0.394792E+10 | 364.36 | 0.935332E+10 | 0.717804E+10 | 0.00 | 1.00 | 01-AUG-07:02 | 0.00 | 01-AUG-00:10 | 29758.85 | 14-AUG-07:03 | 19945.69 | 31-AUG-07:02 | 17684.64 | 14-AUG-07:03 | 6266.22 | 06-AUG-08:03 | 0.00 | 01-AUG-00:10 |
September | 0.141403E+11 | 0.333052E+10 | 343.68 | 0.770066E+10 | 0.643967E+10 | 0.00 | 1.00 | 01-SEP-07:02 | 0.00 | 01-SEP-00:05 | 29813.14 | 05-SEP-07:02 | 18375.79 | 23-SEP-07:02 | 17087.70 | 05-SEP-07:02 | 6647.85 | 10-SEP-08:13 | 0.00 | 01-SEP-00:05 |
October | 0.121673E+11 | 0.290291E+10 | 327.17 | 0.721434E+10 | 0.495301E+10 | 0.00 | 1.00 | 02-OCT-07:03 | 0.00 | 01-OCT-00:10 | 29704.71 | 08-OCT-08:62 | 21643.16 | 26-OCT-07:02 | 16614.53 | 08-OCT-08:62 | 6208.37 | 14-OCT-07:02 | 0.00 | 01-OCT-00:10 |
November | 0.469214E+10 | 0.114511E+10 | 219.08 | 0.288472E+10 | 0.180742E+10 | 0.00 | 1.00 | 01-NOV-07:03 | 0.00 | 01-NOV-00:10 | 28109.81 | 02-NOV-07:02 | 17035.79 | 03-NOV-07:03 | 12605.31 | 04-NOV-07:03 | 5940.02 | 02-NOV-07:02 | 0.00 | 01-NOV-00:10 |
December | 0.299045E+10 | 0.731491E+09 | 133.64 | 0.182166E+10 | 0.116880E+10 | 0.00 | 1.00 | 11-DEC-08:62 | 0.00 | 01-DEC-00:10 | 23979.77 | 11-DEC-08:62 | 13486.96 | 15-DEC-08:62 | 13631.84 | 11-DEC-08:62 | 4988.83 | 11-DEC-08:62 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.107691E+12 | 0.259831E+11 | 3099.96 | 0.627637E+11 | 0.449276E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.143678E+10 | 0.363346E+09 | 88.06 | 0.891569E+09 | 0.545209E+09 | 0.00 | 0.78 | 0.00 | 10119.22 | 6313.34 | 4076.56 | 2363.39 | 0.00 | |||||||
Maximum of Months | 0.165314E+11 | 0.394792E+10 | 364.36 | 0.935332E+10 | 0.741216E+10 | 0.00 | 1.00 | 0.00 | 29813.14 | 21643.16 | 17684.64 | 6647.85 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_9:9 COOLING COIL
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.137337E+10 | 0.348182E+09 | 86.17 | 0.850379E+09 | 0.522993E+09 | 0.00 | 0.77 | 19-JAN-14:00 | 0.00 | 01-JAN-00:05 | 9997.62 | 19-JAN-14:00 | 6216.11 | 01-JAN-14:10 | 4438.54 | 19-JAN-14:00 | 2341.53 | 19-JAN-14:00 | 0.00 | 01-JAN-00:05 |
February | 0.202311E+10 | 0.509037E+09 | 113.39 | 0.123702E+10 | 0.786094E+09 | 0.00 | 0.81 | 24-FEB-14:00 | 0.00 | 01-FEB-00:05 | 10417.85 | 24-FEB-13:50 | 6639.23 | 02-FEB-13:30 | 4032.76 | 24-FEB-13:10 | 2513.64 | 24-FEB-13:10 | 0.00 | 01-FEB-00:05 |
March | 0.295895E+10 | 0.748787E+09 | 165.33 | 0.186013E+10 | 0.109882E+10 | 0.00 | 0.89 | 30-MAR-13:00 | 0.00 | 01-MAR-00:05 | 11789.04 | 30-MAR-13:00 | 7299.04 | 26-MAR-14:00 | 4750.76 | 07-MAR-13:40 | 2832.43 | 30-MAR-13:00 | 0.00 | 01-MAR-00:05 |
April | 0.570089E+10 | 0.143864E+10 | 266.72 | 0.370750E+10 | 0.199339E+10 | 0.00 | 1.00 | 28-APR-07:03 | 0.00 | 01-APR-00:05 | 21836.74 | 29-APR-07:03 | 12127.79 | 29-APR-07:03 | 9708.95 | 29-APR-07:03 | 4657.87 | 29-APR-07:03 | 0.00 | 01-APR-00:05 |
May | 0.135136E+11 | 0.330000E+10 | 358.82 | 0.811024E+10 | 0.540334E+10 | 0.00 | 1.00 | 01-MAY-07:03 | 0.00 | 01-MAY-00:10 | 29399.17 | 21-MAY-08:62 | 18275.38 | 31-MAY-07:02 | 16179.40 | 21-MAY-08:62 | 6265.85 | 28-MAY-08:62 | 0.00 | 01-MAY-00:10 |
June | 0.146893E+11 | 0.356313E+10 | 352.72 | 0.870302E+10 | 0.598632E+10 | 0.00 | 1.00 | 01-JUN-07:03 | 0.00 | 01-JUN-00:10 | 29799.51 | 19-JUN-07:02 | 19421.92 | 14-JUN-07:02 | 17682.73 | 19-JUN-07:02 | 6328.29 | 17-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.163465E+11 | 0.389043E+10 | 352.42 | 0.893725E+10 | 0.740921E+10 | 0.00 | 1.00 | 01-JUL-07:02 | 0.00 | 01-JUL-00:05 | 29894.68 | 03-JUL-07:02 | 18221.23 | 19-JUL-07:02 | 17738.44 | 02-JUL-08:03 | 6423.53 | 09-JUL-08:04 | 0.00 | 01-JUL-00:05 |
August | 0.165548E+11 | 0.395464E+10 | 365.04 | 0.937041E+10 | 0.718434E+10 | 0.00 | 1.00 | 01-AUG-07:02 | 0.00 | 01-AUG-00:10 | 29851.55 | 14-AUG-07:02 | 19990.03 | 31-AUG-07:02 | 17772.55 | 14-AUG-07:03 | 6286.21 | 06-AUG-08:03 | 0.00 | 01-AUG-00:10 |
September | 0.141335E+11 | 0.333048E+10 | 344.14 | 0.769740E+10 | 0.643609E+10 | 0.00 | 1.00 | 01-SEP-07:02 | 0.00 | 01-SEP-00:05 | 29906.01 | 05-SEP-07:02 | 18388.71 | 23-SEP-07:02 | 17160.92 | 05-SEP-07:02 | 6668.52 | 10-SEP-08:13 | 0.00 | 01-SEP-00:05 |
October | 0.121326E+11 | 0.289602E+10 | 325.49 | 0.718974E+10 | 0.494286E+10 | 0.00 | 1.00 | 02-OCT-07:03 | 0.00 | 01-OCT-00:10 | 29791.87 | 08-OCT-08:62 | 21701.18 | 26-OCT-07:02 | 16686.99 | 08-OCT-08:62 | 6227.45 | 14-OCT-07:02 | 0.00 | 01-OCT-00:10 |
November | 0.458974E+10 | 0.112094E+10 | 214.05 | 0.281015E+10 | 0.177959E+10 | 0.00 | 1.00 | 01-NOV-07:03 | 0.00 | 01-NOV-00:10 | 28194.22 | 02-NOV-07:02 | 16560.53 | 02-NOV-07:02 | 11663.72 | 04-NOV-07:03 | 5958.29 | 02-NOV-07:02 | 0.00 | 01-NOV-00:10 |
December | 0.291528E+10 | 0.714446E+09 | 130.72 | 0.176962E+10 | 0.114567E+10 | 0.00 | 1.00 | 11-DEC-08:62 | 0.00 | 01-DEC-00:10 | 21549.62 | 11-DEC-08:62 | 12615.41 | 11-DEC-08:62 | 9047.49 | 16-DEC-08:62 | 4484.43 | 11-DEC-08:62 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.106932E+12 | 0.258147E+11 | 3075.02 | 0.622429E+11 | 0.446887E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.137337E+10 | 0.348182E+09 | 86.17 | 0.850379E+09 | 0.522993E+09 | 0.00 | 0.77 | 0.00 | 9997.62 | 6216.11 | 4032.76 | 2341.53 | 0.00 | |||||||
Maximum of Months | 0.165548E+11 | 0.395464E+10 | 365.04 | 0.937041E+10 | 0.740921E+10 | 0.00 | 1.00 | 0.00 | 29906.01 | 21701.18 | 17772.55 | 6668.52 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_10:10 COOLING COIL
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.144123E+10 | 0.368689E+09 | 83.08 | 0.902209E+09 | 0.539025E+09 | 0.00 | 0.75 | 19-JAN-14:00 | 0.00 | 01-JAN-00:05 | 10933.32 | 19-JAN-14:00 | 6675.56 | 01-JAN-14:00 | 4712.03 | 19-JAN-14:00 | 2589.38 | 19-JAN-14:00 | 0.00 | 01-JAN-00:05 |
February | 0.209904E+10 | 0.534308E+09 | 108.92 | 0.129702E+10 | 0.802013E+09 | 0.00 | 0.77 | 24-FEB-13:10 | 0.00 | 01-FEB-00:05 | 11290.61 | 24-FEB-13:10 | 7093.50 | 02-FEB-13:10 | 4274.20 | 24-FEB-13:10 | 2763.60 | 24-FEB-13:10 | 0.00 | 01-FEB-00:05 |
March | 0.315904E+10 | 0.807125E+09 | 160.75 | 0.200688E+10 | 0.115216E+10 | 0.00 | 0.85 | 30-MAR-13:00 | 0.00 | 01-MAR-00:05 | 12671.80 | 30-MAR-13:00 | 7949.96 | 26-MAR-14:00 | 5068.92 | 07-MAR-13:20 | 3097.78 | 30-MAR-13:00 | 0.00 | 01-MAR-00:05 |
April | 0.602264E+10 | 0.153665E+10 | 258.79 | 0.396252E+10 | 0.206012E+10 | 0.00 | 1.00 | 28-APR-14:20 | 0.00 | 01-APR-00:05 | 16971.50 | 28-APR-16:10 | 10817.53 | 28-APR-15:00 | 7259.31 | 29-APR-07:03 | 4066.63 | 28-APR-16:10 | 0.00 | 01-APR-00:05 |
May | 0.146736E+11 | 0.362358E+10 | 358.57 | 0.892105E+10 | 0.575260E+10 | 0.00 | 1.00 | 01-MAY-14:30 | 0.00 | 01-MAY-00:10 | 33839.60 | 21-MAY-08:62 | 20224.28 | 31-MAY-07:02 | 19160.24 | 21-MAY-08:62 | 7180.02 | 28-MAY-08:62 | 0.00 | 01-MAY-00:10 |
June | 0.161057E+11 | 0.394502E+10 | 353.26 | 0.970067E+10 | 0.640504E+10 | 0.00 | 1.00 | 02-JUN-07:03 | 0.00 | 01-JUN-00:10 | 34198.68 | 19-JUN-07:02 | 20599.79 | 14-JUN-07:02 | 20736.24 | 19-JUN-07:02 | 7274.63 | 17-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.180377E+11 | 0.433482E+10 | 353.23 | 0.100890E+11 | 0.794864E+10 | 0.00 | 1.00 | 01-JUL-07:02 | 0.00 | 01-JUL-00:05 | 34301.73 | 03-JUL-07:02 | 20152.36 | 19-JUL-07:02 | 21205.80 | 02-JUL-08:03 | 7365.65 | 09-JUL-08:03 | 0.00 | 01-JUL-00:05 |
August | 0.184220E+11 | 0.443568E+10 | 366.85 | 0.106473E+11 | 0.777470E+10 | 0.00 | 1.00 | 01-AUG-07:02 | 0.00 | 01-AUG-00:10 | 34253.73 | 07-AUG-07:02 | 23406.77 | 31-AUG-07:02 | 20588.95 | 14-AUG-07:03 | 7211.46 | 06-AUG-08:62 | 0.00 | 01-AUG-00:10 |
September | 0.156262E+11 | 0.371545E+10 | 345.47 | 0.870396E+10 | 0.692221E+10 | 0.00 | 1.00 | 01-SEP-07:02 | 0.00 | 01-SEP-00:05 | 34314.74 | 05-SEP-07:02 | 21029.03 | 01-SEP-07:02 | 20054.02 | 05-SEP-07:03 | 7632.03 | 10-SEP-08:13 | 0.00 | 01-SEP-00:05 |
October | 0.133749E+11 | 0.321751E+10 | 323.45 | 0.806108E+10 | 0.531379E+10 | 0.00 | 1.00 | 03-OCT-07:03 | 0.00 | 01-OCT-00:10 | 34270.63 | 08-OCT-08:62 | 21723.35 | 26-OCT-07:02 | 19850.16 | 22-OCT-08:62 | 7152.49 | 14-OCT-07:02 | 0.00 | 01-OCT-00:10 |
November | 0.489315E+10 | 0.120717E+10 | 205.26 | 0.303273E+10 | 0.186042E+10 | 0.00 | 1.00 | 01-NOV-07:03 | 0.00 | 01-NOV-00:10 | 32726.16 | 02-NOV-07:02 | 17848.95 | 02-NOV-07:02 | 14877.21 | 02-NOV-07:02 | 6860.59 | 02-NOV-07:02 | 0.00 | 01-NOV-00:10 |
December | 0.303936E+10 | 0.755900E+09 | 128.46 | 0.186125E+10 | 0.117810E+10 | 0.00 | 0.95 | 15-DEC-08:62 | 0.00 | 01-DEC-00:10 | 15216.20 | 15-DEC-08:62 | 8631.74 | 13-DEC-15:10 | 7598.80 | 11-DEC-08:62 | 3296.04 | 15-DEC-14:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.116895E+12 | 0.284819E+11 | 3046.08 | 0.691857E+11 | 0.477088E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.144123E+10 | 0.368689E+09 | 83.08 | 0.902209E+09 | 0.539025E+09 | 0.00 | 0.75 | 0.00 | 10933.32 | 6675.56 | 4274.20 | 2589.38 | 0.00 | |||||||
Maximum of Months | 0.184220E+11 | 0.443568E+10 | 366.85 | 0.106473E+11 | 0.794864E+10 | 0.00 | 1.00 | 0.00 | 34314.74 | 23406.77 | 21205.80 | 7632.03 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.87 | 64.09 | 25.78 | 134.64 | 49.52 | 0.00 | 0.00 | 0.00 |
February | 81.51 | 52.76 | 28.75 | 124.10 | 43.16 | 0.00 | 0.00 | 0.00 |
March | 52.04 | 23.48 | 28.55 | 81.69 | 38.01 | 0.00 | 0.00 | 0.00 |
April | 38.57 | 9.04 | 29.53 | 66.27 | 25.10 | 0.00 | 0.00 | 0.00 |
May | 29.47 | 1.25 | 28.22 | 62.34 | 6.20 | 0.00 | 0.00 | 0.00 |
June | 29.11 | 0.27 | 28.84 | 62.98 | 5.40 | 0.00 | 0.00 | 0.00 |
July | 30.47 | 0.56 | 29.91 | 66.02 | 3.50 | 0.00 | 0.00 | 0.00 |
August | 35.85 | 4.30 | 31.55 | 77.28 | 5.85 | 0.00 | 0.00 | 0.00 |
September | 43.01 | 11.34 | 31.68 | 86.12 | 8.38 | 0.00 | 0.00 | 0.00 |
October | 66.74 | 34.76 | 31.97 | 122.87 | 15.79 | 0.00 | 0.00 | 0.00 |
November | 84.93 | 58.47 | 26.45 | 135.45 | 34.58 | 0.00 | 0.00 | 0.00 |
December | 87.81 | 63.06 | 24.75 | 135.10 | 44.85 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 55.65 | 26.82 | 28.83 | 96.10 | 23.25 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 29.11 | 0.27 | 24.75 | 62.34 | 3.50 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 89.87 | 64.09 | 31.97 | 135.45 | 49.52 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.87 | 64.09 | 25.78 | 134.64 | 49.52 | 0.00 | 0.00 | 0.00 |
February | 81.51 | 52.76 | 28.75 | 124.10 | 43.16 | 0.00 | 0.00 | 0.00 |
March | 52.04 | 23.48 | 28.55 | 81.69 | 38.01 | 0.00 | 0.00 | 0.00 |
April | 38.57 | 9.04 | 29.53 | 66.27 | 25.10 | 0.00 | 0.00 | 0.00 |
May | 29.47 | 1.25 | 28.22 | 62.34 | 6.20 | 0.00 | 0.00 | 0.00 |
June | 29.11 | 0.27 | 28.84 | 62.98 | 5.40 | 0.00 | 0.00 | 0.00 |
July | 30.47 | 0.56 | 29.91 | 66.02 | 3.50 | 0.00 | 0.00 | 0.00 |
August | 35.85 | 4.30 | 31.55 | 77.28 | 5.85 | 0.00 | 0.00 | 0.00 |
September | 43.01 | 11.34 | 31.68 | 86.12 | 8.38 | 0.00 | 0.00 | 0.00 |
October | 66.74 | 34.76 | 31.97 | 122.87 | 15.79 | 0.00 | 0.00 | 0.00 |
November | 84.93 | 58.47 | 26.45 | 135.45 | 34.58 | 0.00 | 0.00 | 0.00 |
December | 87.81 | 63.06 | 24.75 | 135.10 | 44.85 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 55.65 | 26.82 | 28.83 | 96.10 | 23.25 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 29.11 | 0.27 | 24.75 | 62.34 | 3.50 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 89.87 | 64.09 | 31.97 | 135.45 | 49.52 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.87 | 64.09 | 25.78 | 134.64 | 49.52 | 0.00 | 0.00 | 0.00 |
February | 81.51 | 52.76 | 28.75 | 124.10 | 43.16 | 0.00 | 0.00 | 0.00 |
March | 52.04 | 23.48 | 28.55 | 81.69 | 38.01 | 0.00 | 0.00 | 0.00 |
April | 38.57 | 9.04 | 29.53 | 66.27 | 25.10 | 0.00 | 0.00 | 0.00 |
May | 29.47 | 1.25 | 28.22 | 62.34 | 6.20 | 0.00 | 0.00 | 0.00 |
June | 29.11 | 0.27 | 28.84 | 62.98 | 5.40 | 0.00 | 0.00 | 0.00 |
July | 30.47 | 0.56 | 29.91 | 66.02 | 3.50 | 0.00 | 0.00 | 0.00 |
August | 35.85 | 4.30 | 31.55 | 77.28 | 5.85 | 0.00 | 0.00 | 0.00 |
September | 43.01 | 11.34 | 31.68 | 86.12 | 8.38 | 0.00 | 0.00 | 0.00 |
October | 66.74 | 34.76 | 31.97 | 122.87 | 15.79 | 0.00 | 0.00 | 0.00 |
November | 84.93 | 58.47 | 26.45 | 135.45 | 34.58 | 0.00 | 0.00 | 0.00 |
December | 87.81 | 63.06 | 24.75 | 135.10 | 44.85 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 55.65 | 26.82 | 28.83 | 96.10 | 23.25 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 29.11 | 0.27 | 24.75 | 62.34 | 3.50 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 89.87 | 64.09 | 31.97 | 135.45 | 49.52 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.87 | 64.09 | 25.78 | 134.64 | 49.52 | 0.00 | 0.00 | 0.00 |
February | 81.51 | 52.76 | 28.75 | 124.10 | 43.16 | 0.00 | 0.00 | 0.00 |
March | 52.04 | 23.48 | 28.55 | 81.69 | 38.01 | 0.00 | 0.00 | 0.00 |
April | 38.57 | 9.04 | 29.53 | 66.27 | 25.10 | 0.00 | 0.00 | 0.00 |
May | 29.47 | 1.25 | 28.22 | 62.34 | 6.20 | 0.00 | 0.00 | 0.00 |
June | 29.11 | 0.27 | 28.84 | 62.98 | 5.40 | 0.00 | 0.00 | 0.00 |
July | 30.47 | 0.56 | 29.91 | 66.02 | 3.50 | 0.00 | 0.00 | 0.00 |
August | 35.85 | 4.30 | 31.55 | 77.28 | 5.85 | 0.00 | 0.00 | 0.00 |
September | 43.01 | 11.34 | 31.68 | 86.12 | 8.38 | 0.00 | 0.00 | 0.00 |
October | 66.74 | 34.76 | 31.97 | 122.87 | 15.79 | 0.00 | 0.00 | 0.00 |
November | 84.93 | 58.47 | 26.45 | 135.45 | 34.58 | 0.00 | 0.00 | 0.00 |
December | 87.81 | 63.06 | 24.75 | 135.10 | 44.85 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 55.65 | 26.82 | 28.83 | 96.10 | 23.25 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 29.11 | 0.27 | 24.75 | 62.34 | 3.50 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 89.87 | 64.09 | 31.97 | 135.45 | 49.52 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 108.04 | 77.05 | 30.99 | 162.05 | 58.94 | 0.00 | 0.00 | 0.00 |
February | 97.98 | 63.42 | 34.56 | 149.35 | 51.42 | 0.00 | 0.00 | 0.00 |
March | 62.56 | 28.23 | 34.32 | 98.32 | 45.27 | 0.00 | 0.00 | 0.00 |
April | 46.36 | 10.86 | 35.50 | 79.61 | 29.98 | 0.00 | 0.00 | 0.00 |
May | 35.43 | 1.51 | 33.92 | 74.60 | 7.47 | 0.00 | 0.00 | 0.00 |
June | 35.00 | 0.33 | 34.67 | 75.30 | 6.51 | 0.00 | 0.00 | 0.00 |
July | 36.63 | 0.67 | 35.96 | 78.92 | 4.25 | 0.00 | 0.00 | 0.00 |
August | 43.10 | 5.17 | 37.93 | 92.51 | 7.05 | 0.00 | 0.00 | 0.00 |
September | 51.71 | 13.63 | 38.08 | 103.24 | 10.09 | 0.00 | 0.00 | 0.00 |
October | 80.23 | 41.79 | 38.44 | 147.49 | 18.90 | 0.00 | 0.00 | 0.00 |
November | 102.10 | 70.29 | 31.80 | 162.79 | 41.27 | 0.00 | 0.00 | 0.00 |
December | 105.57 | 75.81 | 29.75 | 162.49 | 53.43 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.89 | 32.24 | 34.66 | 115.39 | 27.75 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 35.00 | 0.33 | 29.75 | 74.60 | 4.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 108.04 | 77.05 | 38.44 | 162.79 | 58.94 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 108.04 | 77.05 | 30.99 | 162.05 | 58.94 | 0.00 | 0.00 | 0.00 |
February | 97.98 | 63.42 | 34.56 | 149.35 | 51.42 | 0.00 | 0.00 | 0.00 |
March | 62.56 | 28.23 | 34.32 | 98.32 | 45.27 | 0.00 | 0.00 | 0.00 |
April | 46.36 | 10.86 | 35.50 | 79.61 | 29.98 | 0.00 | 0.00 | 0.00 |
May | 35.43 | 1.51 | 33.92 | 74.60 | 7.47 | 0.00 | 0.00 | 0.00 |
June | 35.00 | 0.33 | 34.67 | 75.30 | 6.51 | 0.00 | 0.00 | 0.00 |
July | 36.63 | 0.67 | 35.96 | 78.92 | 4.25 | 0.00 | 0.00 | 0.00 |
August | 43.10 | 5.17 | 37.93 | 92.51 | 7.05 | 0.00 | 0.00 | 0.00 |
September | 51.71 | 13.63 | 38.08 | 103.24 | 10.09 | 0.00 | 0.00 | 0.00 |
October | 80.23 | 41.79 | 38.44 | 147.49 | 18.90 | 0.00 | 0.00 | 0.00 |
November | 102.10 | 70.29 | 31.80 | 162.79 | 41.27 | 0.00 | 0.00 | 0.00 |
December | 105.57 | 75.81 | 29.75 | 162.49 | 53.43 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.89 | 32.24 | 34.66 | 115.39 | 27.75 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 35.00 | 0.33 | 29.75 | 74.60 | 4.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 108.04 | 77.05 | 38.44 | 162.79 | 58.94 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.87 | 64.09 | 25.78 | 133.21 | 52.48 | 0.00 | 0.00 | 0.00 |
February | 81.51 | 52.76 | 28.75 | 122.94 | 45.35 | 0.00 | 0.00 | 0.00 |
March | 52.04 | 23.48 | 28.55 | 80.80 | 40.10 | 0.00 | 0.00 | 0.00 |
April | 38.57 | 9.04 | 29.53 | 65.97 | 25.77 | 0.00 | 0.00 | 0.00 |
May | 29.47 | 1.25 | 28.22 | 62.50 | 6.38 | 0.00 | 0.00 | 0.00 |
June | 29.11 | 0.27 | 28.84 | 63.30 | 5.52 | 0.00 | 0.00 | 0.00 |
July | 30.47 | 0.56 | 29.91 | 66.44 | 3.54 | 0.00 | 0.00 | 0.00 |
August | 35.85 | 4.30 | 31.55 | 77.78 | 5.76 | 0.00 | 0.00 | 0.00 |
September | 43.01 | 11.34 | 31.68 | 86.44 | 8.32 | 0.00 | 0.00 | 0.00 |
October | 66.74 | 34.76 | 31.97 | 122.98 | 15.86 | 0.00 | 0.00 | 0.00 |
November | 84.93 | 58.47 | 26.45 | 134.97 | 35.23 | 0.00 | 0.00 | 0.00 |
December | 87.81 | 63.06 | 24.75 | 134.23 | 46.77 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 55.65 | 26.82 | 28.83 | 95.83 | 24.14 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 29.11 | 0.27 | 24.75 | 62.50 | 3.54 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 89.87 | 64.09 | 31.97 | 134.97 | 52.48 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.87 | 64.09 | 25.78 | 133.21 | 52.48 | 0.00 | 0.00 | 0.00 |
February | 81.51 | 52.76 | 28.75 | 122.94 | 45.35 | 0.00 | 0.00 | 0.00 |
March | 52.04 | 23.48 | 28.55 | 80.80 | 40.10 | 0.00 | 0.00 | 0.00 |
April | 38.57 | 9.04 | 29.53 | 65.97 | 25.77 | 0.00 | 0.00 | 0.00 |
May | 29.47 | 1.25 | 28.22 | 62.50 | 6.38 | 0.00 | 0.00 | 0.00 |
June | 29.11 | 0.27 | 28.84 | 63.30 | 5.52 | 0.00 | 0.00 | 0.00 |
July | 30.47 | 0.56 | 29.91 | 66.44 | 3.54 | 0.00 | 0.00 | 0.00 |
August | 35.85 | 4.30 | 31.55 | 77.78 | 5.76 | 0.00 | 0.00 | 0.00 |
September | 43.01 | 11.34 | 31.68 | 86.44 | 8.32 | 0.00 | 0.00 | 0.00 |
October | 66.74 | 34.76 | 31.97 | 122.98 | 15.86 | 0.00 | 0.00 | 0.00 |
November | 84.93 | 58.47 | 26.45 | 134.97 | 35.23 | 0.00 | 0.00 | 0.00 |
December | 87.81 | 63.06 | 24.75 | 134.23 | 46.77 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 55.65 | 26.82 | 28.83 | 95.83 | 24.14 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 29.11 | 0.27 | 24.75 | 62.50 | 3.54 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 89.87 | 64.09 | 31.97 | 134.97 | 52.48 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 108.04 | 77.05 | 30.99 | 160.39 | 62.42 | 0.00 | 0.00 | 0.00 |
February | 97.98 | 63.42 | 34.56 | 148.00 | 53.99 | 0.00 | 0.00 | 0.00 |
March | 62.56 | 28.23 | 34.32 | 97.28 | 47.72 | 0.00 | 0.00 | 0.00 |
April | 46.36 | 10.86 | 35.50 | 79.26 | 30.78 | 0.00 | 0.00 | 0.00 |
May | 35.43 | 1.51 | 33.92 | 74.79 | 7.69 | 0.00 | 0.00 | 0.00 |
June | 35.00 | 0.33 | 34.67 | 75.69 | 6.65 | 0.00 | 0.00 | 0.00 |
July | 36.63 | 0.67 | 35.96 | 79.43 | 4.30 | 0.00 | 0.00 | 0.00 |
August | 43.10 | 5.17 | 37.93 | 93.11 | 6.94 | 0.00 | 0.00 | 0.00 |
September | 51.71 | 13.63 | 38.08 | 103.63 | 10.02 | 0.00 | 0.00 | 0.00 |
October | 80.23 | 41.79 | 38.44 | 147.65 | 18.98 | 0.00 | 0.00 | 0.00 |
November | 102.10 | 70.29 | 31.80 | 162.26 | 42.04 | 0.00 | 0.00 | 0.00 |
December | 105.57 | 75.81 | 29.75 | 161.49 | 55.67 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.89 | 32.24 | 34.66 | 115.09 | 28.80 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 35.00 | 0.33 | 29.75 | 74.79 | 4.30 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 108.04 | 77.05 | 38.44 | 162.26 | 62.42 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.87 | 64.09 | 25.78 | 133.66 | 51.57 | 0.00 | 0.00 | 0.00 |
February | 81.51 | 52.76 | 28.75 | 123.25 | 44.91 | 0.00 | 0.00 | 0.00 |
March | 52.04 | 23.48 | 28.55 | 80.94 | 39.99 | 0.00 | 0.00 | 0.00 |
April | 38.57 | 9.04 | 29.53 | 65.84 | 26.74 | 0.00 | 0.00 | 0.00 |
May | 29.47 | 1.25 | 28.22 | 61.82 | 7.89 | 0.00 | 0.00 | 0.00 |
June | 29.11 | 0.27 | 28.84 | 62.56 | 7.16 | 0.00 | 0.00 | 0.00 |
July | 30.47 | 0.56 | 29.91 | 65.01 | 4.85 | 0.00 | 0.00 | 0.00 |
August | 35.85 | 4.30 | 31.55 | 76.80 | 7.26 | 0.00 | 0.00 | 0.00 |
September | 43.01 | 11.34 | 31.68 | 85.78 | 10.08 | 0.00 | 0.00 | 0.00 |
October | 66.74 | 34.76 | 31.97 | 122.56 | 17.64 | 0.00 | 0.00 | 0.00 |
November | 84.93 | 58.47 | 26.45 | 135.04 | 36.10 | 0.00 | 0.00 | 0.00 |
December | 87.81 | 63.06 | 24.75 | 134.50 | 46.64 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 55.65 | 26.82 | 28.83 | 95.51 | 24.96 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 29.11 | 0.27 | 24.75 | 61.82 | 4.85 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 89.87 | 64.09 | 31.97 | 135.04 | 51.57 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.87 | 64.09 | 25.78 | 133.66 | 51.57 | 0.00 | 0.00 | 0.00 |
February | 81.51 | 52.76 | 28.75 | 123.25 | 44.91 | 0.00 | 0.00 | 0.00 |
March | 52.04 | 23.48 | 28.55 | 80.94 | 39.99 | 0.00 | 0.00 | 0.00 |
April | 38.57 | 9.04 | 29.53 | 65.84 | 26.74 | 0.00 | 0.00 | 0.00 |
May | 29.47 | 1.25 | 28.22 | 61.82 | 7.89 | 0.00 | 0.00 | 0.00 |
June | 29.11 | 0.27 | 28.84 | 62.56 | 7.16 | 0.00 | 0.00 | 0.00 |
July | 30.47 | 0.56 | 29.91 | 65.01 | 4.85 | 0.00 | 0.00 | 0.00 |
August | 35.85 | 4.30 | 31.55 | 76.80 | 7.26 | 0.00 | 0.00 | 0.00 |
September | 43.01 | 11.34 | 31.68 | 85.78 | 10.08 | 0.00 | 0.00 | 0.00 |
October | 66.74 | 34.76 | 31.97 | 122.56 | 17.64 | 0.00 | 0.00 | 0.00 |
November | 84.93 | 58.47 | 26.45 | 135.04 | 36.10 | 0.00 | 0.00 | 0.00 |
December | 87.81 | 63.06 | 24.75 | 134.50 | 46.64 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 55.65 | 26.82 | 28.83 | 95.51 | 24.96 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 29.11 | 0.27 | 24.75 | 61.82 | 4.85 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 89.87 | 64.09 | 31.97 | 135.04 | 51.57 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 107.45 | 76.63 | 30.82 | 160.05 | 61.00 | 0.00 | 0.00 | 0.00 |
February | 97.45 | 63.08 | 34.37 | 147.57 | 53.17 | 0.00 | 0.00 | 0.00 |
March | 62.21 | 28.08 | 34.14 | 96.92 | 47.32 | 0.00 | 0.00 | 0.00 |
April | 46.11 | 10.81 | 35.31 | 78.68 | 31.73 | 0.00 | 0.00 | 0.00 |
May | 35.23 | 1.50 | 33.74 | 73.60 | 9.42 | 0.00 | 0.00 | 0.00 |
June | 34.80 | 0.32 | 34.48 | 74.43 | 8.54 | 0.00 | 0.00 | 0.00 |
July | 36.43 | 0.67 | 35.76 | 77.34 | 5.82 | 0.00 | 0.00 | 0.00 |
August | 42.86 | 5.14 | 37.72 | 91.48 | 8.67 | 0.00 | 0.00 | 0.00 |
September | 51.43 | 13.55 | 37.87 | 102.31 | 12.03 | 0.00 | 0.00 | 0.00 |
October | 79.79 | 41.56 | 38.23 | 146.37 | 20.96 | 0.00 | 0.00 | 0.00 |
November | 101.54 | 69.91 | 31.63 | 161.45 | 42.81 | 0.00 | 0.00 | 0.00 |
December | 104.99 | 75.40 | 29.59 | 160.92 | 55.21 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.53 | 32.06 | 34.47 | 114.10 | 29.60 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 34.80 | 0.32 | 29.59 | 73.60 | 5.82 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 107.45 | 76.63 | 38.23 | 161.45 | 61.00 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.87 | 64.09 | 25.78 | 133.94 | 50.84 | 0.00 | 0.00 | 0.00 |
February | 81.51 | 52.76 | 28.75 | 123.49 | 44.33 | 0.00 | 0.00 | 0.00 |
March | 52.04 | 23.48 | 28.55 | 81.09 | 39.54 | 0.00 | 0.00 | 0.00 |
April | 38.57 | 9.04 | 29.53 | 65.88 | 26.60 | 0.00 | 0.00 | 0.00 |
May | 29.47 | 1.25 | 28.22 | 61.80 | 7.98 | 0.00 | 0.00 | 0.00 |
June | 29.11 | 0.27 | 28.84 | 62.53 | 7.29 | 0.00 | 0.00 | 0.00 |
July | 30.47 | 0.56 | 29.91 | 64.93 | 5.00 | 0.00 | 0.00 | 0.00 |
August | 35.85 | 4.30 | 31.55 | 76.76 | 7.41 | 0.00 | 0.00 | 0.00 |
September | 43.01 | 11.34 | 31.68 | 85.74 | 10.22 | 0.00 | 0.00 | 0.00 |
October | 66.74 | 34.76 | 31.97 | 122.55 | 17.74 | 0.00 | 0.00 | 0.00 |
November | 84.93 | 58.47 | 26.45 | 135.10 | 35.91 | 0.00 | 0.00 | 0.00 |
December | 87.81 | 63.06 | 24.75 | 134.66 | 46.16 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 55.65 | 26.82 | 28.83 | 95.57 | 24.81 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 29.11 | 0.27 | 24.75 | 61.80 | 5.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 89.87 | 64.09 | 31.97 | 135.10 | 50.84 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.87 | 64.09 | 25.78 | 133.94 | 50.84 | 0.00 | 0.00 | 0.00 |
February | 81.51 | 52.76 | 28.75 | 123.49 | 44.33 | 0.00 | 0.00 | 0.00 |
March | 52.04 | 23.48 | 28.55 | 81.09 | 39.54 | 0.00 | 0.00 | 0.00 |
April | 38.57 | 9.04 | 29.53 | 65.88 | 26.60 | 0.00 | 0.00 | 0.00 |
May | 29.47 | 1.25 | 28.22 | 61.80 | 7.98 | 0.00 | 0.00 | 0.00 |
June | 29.11 | 0.27 | 28.84 | 62.53 | 7.29 | 0.00 | 0.00 | 0.00 |
July | 30.47 | 0.56 | 29.91 | 64.93 | 5.00 | 0.00 | 0.00 | 0.00 |
August | 35.85 | 4.30 | 31.55 | 76.76 | 7.41 | 0.00 | 0.00 | 0.00 |
September | 43.01 | 11.34 | 31.68 | 85.74 | 10.22 | 0.00 | 0.00 | 0.00 |
October | 66.74 | 34.76 | 31.97 | 122.55 | 17.74 | 0.00 | 0.00 | 0.00 |
November | 84.93 | 58.47 | 26.45 | 135.10 | 35.91 | 0.00 | 0.00 | 0.00 |
December | 87.81 | 63.06 | 24.75 | 134.66 | 46.16 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 55.65 | 26.82 | 28.83 | 95.57 | 24.81 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 29.11 | 0.27 | 24.75 | 61.80 | 5.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 89.87 | 64.09 | 31.97 | 135.10 | 50.84 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 107.45 | 76.63 | 30.82 | 160.39 | 60.14 | 0.00 | 0.00 | 0.00 |
February | 97.45 | 63.08 | 34.37 | 147.84 | 52.48 | 0.00 | 0.00 | 0.00 |
March | 62.21 | 28.08 | 34.14 | 97.10 | 46.79 | 0.00 | 0.00 | 0.00 |
April | 46.11 | 10.81 | 35.31 | 78.73 | 31.56 | 0.00 | 0.00 | 0.00 |
May | 35.23 | 1.50 | 33.74 | 73.57 | 9.53 | 0.00 | 0.00 | 0.00 |
June | 34.80 | 0.32 | 34.48 | 74.38 | 8.70 | 0.00 | 0.00 | 0.00 |
July | 36.43 | 0.67 | 35.76 | 77.26 | 6.00 | 0.00 | 0.00 | 0.00 |
August | 42.86 | 5.14 | 37.72 | 91.43 | 8.85 | 0.00 | 0.00 | 0.00 |
September | 51.43 | 13.55 | 37.87 | 102.26 | 12.19 | 0.00 | 0.00 | 0.00 |
October | 79.79 | 41.56 | 38.23 | 146.35 | 21.08 | 0.00 | 0.00 | 0.00 |
November | 101.54 | 69.91 | 31.63 | 161.53 | 42.59 | 0.00 | 0.00 | 0.00 |
December | 104.99 | 75.40 | 29.59 | 161.12 | 54.64 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.53 | 32.06 | 34.47 | 114.17 | 29.42 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 34.80 | 0.32 | 29.59 | 73.57 | 6.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 107.45 | 76.63 | 38.23 | 161.53 | 60.14 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.87 | 64.09 | 25.78 | 134.31 | 50.06 | 0.00 | 0.00 | 0.00 |
February | 81.51 | 52.76 | 28.75 | 123.84 | 43.63 | 0.00 | 0.00 | 0.00 |
March | 52.04 | 23.48 | 28.55 | 81.37 | 38.89 | 0.00 | 0.00 | 0.00 |
April | 38.57 | 9.04 | 29.53 | 66.04 | 26.20 | 0.00 | 0.00 | 0.00 |
May | 29.47 | 1.25 | 28.22 | 61.92 | 7.70 | 0.00 | 0.00 | 0.00 |
June | 29.11 | 0.27 | 28.84 | 62.65 | 7.02 | 0.00 | 0.00 | 0.00 |
July | 30.47 | 0.56 | 29.91 | 65.07 | 4.77 | 0.00 | 0.00 | 0.00 |
August | 35.85 | 4.30 | 31.55 | 76.87 | 7.15 | 0.00 | 0.00 | 0.00 |
September | 43.01 | 11.34 | 31.68 | 85.83 | 9.95 | 0.00 | 0.00 | 0.00 |
October | 66.74 | 34.76 | 31.97 | 122.64 | 17.45 | 0.00 | 0.00 | 0.00 |
November | 84.93 | 58.47 | 26.45 | 135.27 | 35.51 | 0.00 | 0.00 | 0.00 |
December | 87.81 | 63.06 | 24.75 | 134.91 | 45.53 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 55.65 | 26.82 | 28.83 | 95.76 | 24.38 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 29.11 | 0.27 | 24.75 | 61.92 | 4.77 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 89.87 | 64.09 | 31.97 | 135.27 | 50.06 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.87 | 64.09 | 25.78 | 134.31 | 50.06 | 0.00 | 0.00 | 0.00 |
February | 81.51 | 52.76 | 28.75 | 123.84 | 43.63 | 0.00 | 0.00 | 0.00 |
March | 52.04 | 23.48 | 28.55 | 81.37 | 38.89 | 0.00 | 0.00 | 0.00 |
April | 38.57 | 9.04 | 29.53 | 66.04 | 26.20 | 0.00 | 0.00 | 0.00 |
May | 29.47 | 1.25 | 28.22 | 61.92 | 7.70 | 0.00 | 0.00 | 0.00 |
June | 29.11 | 0.27 | 28.84 | 62.65 | 7.02 | 0.00 | 0.00 | 0.00 |
July | 30.47 | 0.56 | 29.91 | 65.07 | 4.77 | 0.00 | 0.00 | 0.00 |
August | 35.85 | 4.30 | 31.55 | 76.87 | 7.15 | 0.00 | 0.00 | 0.00 |
September | 43.01 | 11.34 | 31.68 | 85.83 | 9.95 | 0.00 | 0.00 | 0.00 |
October | 66.74 | 34.76 | 31.97 | 122.64 | 17.45 | 0.00 | 0.00 | 0.00 |
November | 84.93 | 58.47 | 26.45 | 135.27 | 35.51 | 0.00 | 0.00 | 0.00 |
December | 87.81 | 63.06 | 24.75 | 134.91 | 45.53 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 55.65 | 26.82 | 28.83 | 95.76 | 24.38 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 29.11 | 0.27 | 24.75 | 61.92 | 4.77 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 89.87 | 64.09 | 31.97 | 135.27 | 50.06 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 107.45 | 76.63 | 30.82 | 160.83 | 59.23 | 1.00 | 0.00 | 0.00 |
February | 97.45 | 63.08 | 34.37 | 148.26 | 51.67 | 0.00 | 0.00 | 0.00 |
March | 62.21 | 28.08 | 34.14 | 97.43 | 46.03 | 0.00 | 0.00 | 0.00 |
April | 46.11 | 10.81 | 35.31 | 78.92 | 31.09 | 0.00 | 0.00 | 0.00 |
May | 35.23 | 1.50 | 33.74 | 73.72 | 9.20 | 0.00 | 0.00 | 0.00 |
June | 34.80 | 0.32 | 34.48 | 74.53 | 8.38 | 0.00 | 0.00 | 0.00 |
July | 36.43 | 0.67 | 35.76 | 77.41 | 5.73 | 0.00 | 0.00 | 0.00 |
August | 42.86 | 5.14 | 37.72 | 91.56 | 8.55 | 0.00 | 0.00 | 0.00 |
September | 51.43 | 13.55 | 37.87 | 102.37 | 11.88 | 0.00 | 0.00 | 0.00 |
October | 79.79 | 41.56 | 38.23 | 146.46 | 20.74 | 0.00 | 0.00 | 0.00 |
November | 101.54 | 69.91 | 31.63 | 161.73 | 42.12 | 0.00 | 0.00 | 0.00 |
December | 104.99 | 75.40 | 29.59 | 161.42 | 53.90 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.53 | 32.06 | 34.47 | 114.39 | 28.92 | 1.00 | 0.00 | 0.00 |
Minimum of Months | 34.80 | 0.32 | 29.59 | 73.72 | 5.73 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 107.45 | 76.63 | 38.23 | 161.73 | 59.23 | 1.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.87 | 64.09 | 25.78 | 135.12 | 48.46 | 1.33 | 0.00 | 0.00 |
February | 81.51 | 52.76 | 28.75 | 124.64 | 42.12 | 0.00 | 0.00 | 0.00 |
March | 52.04 | 23.48 | 28.55 | 81.99 | 37.37 | 0.00 | 0.00 | 0.00 |
April | 38.57 | 9.04 | 29.53 | 66.31 | 25.13 | 0.00 | 0.00 | 0.00 |
May | 29.47 | 1.25 | 28.22 | 61.88 | 6.88 | 0.00 | 0.00 | 0.00 |
June | 29.11 | 0.27 | 28.84 | 62.51 | 6.17 | 0.00 | 0.00 | 0.00 |
July | 30.47 | 0.56 | 29.91 | 64.99 | 4.14 | 0.00 | 0.00 | 0.00 |
August | 35.85 | 4.30 | 31.55 | 76.78 | 6.39 | 0.00 | 0.00 | 0.00 |
September | 43.01 | 11.34 | 31.68 | 85.68 | 9.20 | 0.00 | 0.00 | 0.00 |
October | 66.74 | 34.76 | 31.97 | 122.68 | 16.65 | 0.00 | 0.00 | 0.00 |
November | 84.93 | 58.47 | 26.45 | 135.60 | 34.51 | 0.00 | 0.00 | 0.00 |
December | 87.81 | 63.06 | 24.75 | 135.45 | 44.13 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 55.65 | 26.82 | 28.83 | 96.00 | 23.33 | 1.33 | 0.00 | 0.00 |
Minimum of Months | 29.11 | 0.27 | 24.75 | 61.88 | 4.14 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 89.87 | 64.09 | 31.97 | 135.60 | 48.46 | 1.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.87 | 64.09 | 25.78 | 135.12 | 48.46 | 1.33 | 0.00 | 0.00 |
February | 81.51 | 52.76 | 28.75 | 124.64 | 42.12 | 0.00 | 0.00 | 0.00 |
March | 52.04 | 23.48 | 28.55 | 81.99 | 37.37 | 0.00 | 0.00 | 0.00 |
April | 38.57 | 9.04 | 29.53 | 66.31 | 25.13 | 0.00 | 0.00 | 0.00 |
May | 29.47 | 1.25 | 28.22 | 61.88 | 6.88 | 0.00 | 0.00 | 0.00 |
June | 29.11 | 0.27 | 28.84 | 62.51 | 6.17 | 0.00 | 0.00 | 0.00 |
July | 30.47 | 0.56 | 29.91 | 64.99 | 4.14 | 0.00 | 0.00 | 0.00 |
August | 35.85 | 4.30 | 31.55 | 76.78 | 6.39 | 0.00 | 0.00 | 0.00 |
September | 43.01 | 11.34 | 31.68 | 85.68 | 9.20 | 0.00 | 0.00 | 0.00 |
October | 66.74 | 34.76 | 31.97 | 122.68 | 16.65 | 0.00 | 0.00 | 0.00 |
November | 84.93 | 58.47 | 26.45 | 135.60 | 34.51 | 0.00 | 0.00 | 0.00 |
December | 87.81 | 63.06 | 24.75 | 135.45 | 44.13 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 55.65 | 26.82 | 28.83 | 96.00 | 23.33 | 1.33 | 0.00 | 0.00 |
Minimum of Months | 29.11 | 0.27 | 24.75 | 61.88 | 4.14 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 89.87 | 64.09 | 31.97 | 135.60 | 48.46 | 1.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.87 | 64.09 | 25.78 | 135.12 | 48.46 | 1.33 | 0.00 | 0.00 |
February | 81.51 | 52.76 | 28.75 | 124.64 | 42.12 | 0.00 | 0.00 | 0.00 |
March | 52.04 | 23.48 | 28.55 | 81.99 | 37.37 | 0.00 | 0.00 | 0.00 |
April | 38.57 | 9.04 | 29.53 | 66.31 | 25.13 | 0.00 | 0.00 | 0.00 |
May | 29.47 | 1.25 | 28.22 | 61.88 | 6.88 | 0.00 | 0.00 | 0.00 |
June | 29.11 | 0.27 | 28.84 | 62.51 | 6.17 | 0.00 | 0.00 | 0.00 |
July | 30.47 | 0.56 | 29.91 | 64.99 | 4.14 | 0.00 | 0.00 | 0.00 |
August | 35.85 | 4.30 | 31.55 | 76.78 | 6.39 | 0.00 | 0.00 | 0.00 |
September | 43.01 | 11.34 | 31.68 | 85.68 | 9.20 | 0.00 | 0.00 | 0.00 |
October | 66.74 | 34.76 | 31.97 | 122.68 | 16.65 | 0.00 | 0.00 | 0.00 |
November | 84.93 | 58.47 | 26.45 | 135.60 | 34.51 | 0.00 | 0.00 | 0.00 |
December | 87.81 | 63.06 | 24.75 | 135.45 | 44.13 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 55.65 | 26.82 | 28.83 | 96.00 | 23.33 | 1.33 | 0.00 | 0.00 |
Minimum of Months | 29.11 | 0.27 | 24.75 | 61.88 | 4.14 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 89.87 | 64.09 | 31.97 | 135.60 | 48.46 | 1.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.87 | 64.09 | 25.78 | 135.12 | 48.46 | 1.33 | 0.00 | 0.00 |
February | 81.51 | 52.76 | 28.75 | 124.64 | 42.12 | 0.00 | 0.00 | 0.00 |
March | 52.04 | 23.48 | 28.55 | 81.99 | 37.37 | 0.00 | 0.00 | 0.00 |
April | 38.57 | 9.04 | 29.53 | 66.31 | 25.13 | 0.00 | 0.00 | 0.00 |
May | 29.47 | 1.25 | 28.22 | 61.88 | 6.88 | 0.00 | 0.00 | 0.00 |
June | 29.11 | 0.27 | 28.84 | 62.51 | 6.17 | 0.00 | 0.00 | 0.00 |
July | 30.47 | 0.56 | 29.91 | 64.99 | 4.14 | 0.00 | 0.00 | 0.00 |
August | 35.85 | 4.30 | 31.55 | 76.78 | 6.39 | 0.00 | 0.00 | 0.00 |
September | 43.01 | 11.34 | 31.68 | 85.68 | 9.20 | 0.00 | 0.00 | 0.00 |
October | 66.74 | 34.76 | 31.97 | 122.68 | 16.65 | 0.00 | 0.00 | 0.00 |
November | 84.93 | 58.47 | 26.45 | 135.60 | 34.51 | 0.00 | 0.00 | 0.00 |
December | 87.81 | 63.06 | 24.75 | 135.45 | 44.13 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 55.65 | 26.82 | 28.83 | 96.00 | 23.33 | 1.33 | 0.00 | 0.00 |
Minimum of Months | 29.11 | 0.27 | 24.75 | 61.88 | 4.14 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 89.87 | 64.09 | 31.97 | 135.60 | 48.46 | 1.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 107.45 | 76.63 | 30.82 | 161.75 | 57.36 | 1.33 | 0.00 | 0.00 |
February | 97.45 | 63.08 | 34.37 | 149.17 | 49.89 | 0.00 | 0.00 | 0.00 |
March | 62.21 | 28.08 | 34.14 | 98.14 | 44.24 | 0.00 | 0.00 | 0.00 |
April | 46.11 | 10.81 | 35.31 | 79.24 | 29.83 | 0.00 | 0.00 | 0.00 |
May | 35.23 | 1.50 | 33.74 | 73.67 | 8.22 | 0.00 | 0.00 | 0.00 |
June | 34.80 | 0.32 | 34.48 | 74.38 | 7.36 | 0.00 | 0.00 | 0.00 |
July | 36.43 | 0.67 | 35.76 | 77.33 | 4.97 | 0.00 | 0.00 | 0.00 |
August | 42.86 | 5.14 | 37.72 | 91.46 | 7.64 | 0.00 | 0.00 | 0.00 |
September | 51.43 | 13.55 | 37.87 | 102.19 | 10.99 | 0.00 | 0.00 | 0.00 |
October | 79.79 | 41.56 | 38.23 | 146.49 | 19.79 | 0.00 | 0.00 | 0.00 |
November | 101.54 | 69.91 | 31.63 | 162.09 | 40.94 | 0.00 | 0.00 | 0.00 |
December | 104.99 | 75.40 | 29.59 | 162.03 | 52.26 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.53 | 32.06 | 34.47 | 114.66 | 27.67 | 1.33 | 0.00 | 0.00 |
Minimum of Months | 34.80 | 0.32 | 29.59 | 73.67 | 4.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 107.45 | 76.63 | 38.23 | 162.09 | 57.36 | 1.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 107.45 | 76.63 | 30.82 | 161.75 | 57.36 | 1.33 | 0.00 | 0.00 |
February | 97.45 | 63.08 | 34.37 | 149.17 | 49.89 | 0.00 | 0.00 | 0.00 |
March | 62.21 | 28.08 | 34.14 | 98.14 | 44.24 | 0.00 | 0.00 | 0.00 |
April | 46.11 | 10.81 | 35.31 | 79.24 | 29.83 | 0.00 | 0.00 | 0.00 |
May | 35.23 | 1.50 | 33.74 | 73.67 | 8.22 | 0.00 | 0.00 | 0.00 |
June | 34.80 | 0.32 | 34.48 | 74.38 | 7.36 | 0.00 | 0.00 | 0.00 |
July | 36.43 | 0.67 | 35.76 | 77.33 | 4.97 | 0.00 | 0.00 | 0.00 |
August | 42.86 | 5.14 | 37.72 | 91.46 | 7.64 | 0.00 | 0.00 | 0.00 |
September | 51.43 | 13.55 | 37.87 | 102.19 | 10.99 | 0.00 | 0.00 | 0.00 |
October | 79.79 | 41.56 | 38.23 | 146.49 | 19.79 | 0.00 | 0.00 | 0.00 |
November | 101.54 | 69.91 | 31.63 | 162.09 | 40.94 | 0.00 | 0.00 | 0.00 |
December | 104.99 | 75.40 | 29.59 | 162.03 | 52.26 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.53 | 32.06 | 34.47 | 114.66 | 27.67 | 1.33 | 0.00 | 0.00 |
Minimum of Months | 34.80 | 0.32 | 29.59 | 73.67 | 4.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 107.45 | 76.63 | 38.23 | 162.09 | 57.36 | 1.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.87 | 64.09 | 25.78 | 134.95 | 48.28 | 1.33 | 0.00 | 0.00 |
February | 81.51 | 52.76 | 28.75 | 124.50 | 41.91 | 0.00 | 0.00 | 0.00 |
March | 52.04 | 23.48 | 28.55 | 81.90 | 37.18 | 0.00 | 0.00 | 0.00 |
April | 38.57 | 9.04 | 29.53 | 66.31 | 24.91 | 0.00 | 0.00 | 0.00 |
May | 29.47 | 1.25 | 28.22 | 62.08 | 6.59 | 0.00 | 0.00 | 0.00 |
June | 29.11 | 0.27 | 28.84 | 62.77 | 5.87 | 0.00 | 0.00 | 0.00 |
July | 30.47 | 0.56 | 29.91 | 65.31 | 3.87 | 0.00 | 0.00 | 0.00 |
August | 35.85 | 4.30 | 31.55 | 77.01 | 6.07 | 0.00 | 0.00 | 0.00 |
September | 43.01 | 11.34 | 31.68 | 85.80 | 8.86 | 0.00 | 0.00 | 0.00 |
October | 66.74 | 34.76 | 31.97 | 122.68 | 16.34 | 0.00 | 0.00 | 0.00 |
November | 84.93 | 58.47 | 26.45 | 135.47 | 34.30 | 0.00 | 0.00 | 0.00 |
December | 87.81 | 63.06 | 24.75 | 135.30 | 43.94 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 55.65 | 26.82 | 28.83 | 96.03 | 23.07 | 1.33 | 0.00 | 0.00 |
Minimum of Months | 29.11 | 0.27 | 24.75 | 62.08 | 3.87 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 89.87 | 64.09 | 31.97 | 135.47 | 48.28 | 1.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.87 | 64.09 | 25.78 | 134.95 | 48.28 | 1.33 | 0.00 | 0.00 |
February | 81.51 | 52.76 | 28.75 | 124.50 | 41.91 | 0.00 | 0.00 | 0.00 |
March | 52.04 | 23.48 | 28.55 | 81.90 | 37.18 | 0.00 | 0.00 | 0.00 |
April | 38.57 | 9.04 | 29.53 | 66.31 | 24.91 | 0.00 | 0.00 | 0.00 |
May | 29.47 | 1.25 | 28.22 | 62.08 | 6.59 | 0.00 | 0.00 | 0.00 |
June | 29.11 | 0.27 | 28.84 | 62.77 | 5.87 | 0.00 | 0.00 | 0.00 |
July | 30.47 | 0.56 | 29.91 | 65.31 | 3.87 | 0.00 | 0.00 | 0.00 |
August | 35.85 | 4.30 | 31.55 | 77.01 | 6.07 | 0.00 | 0.00 | 0.00 |
September | 43.01 | 11.34 | 31.68 | 85.80 | 8.86 | 0.00 | 0.00 | 0.00 |
October | 66.74 | 34.76 | 31.97 | 122.68 | 16.34 | 0.00 | 0.00 | 0.00 |
November | 84.93 | 58.47 | 26.45 | 135.47 | 34.30 | 0.00 | 0.00 | 0.00 |
December | 87.81 | 63.06 | 24.75 | 135.30 | 43.94 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 55.65 | 26.82 | 28.83 | 96.03 | 23.07 | 1.33 | 0.00 | 0.00 |
Minimum of Months | 29.11 | 0.27 | 24.75 | 62.08 | 3.87 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 89.87 | 64.09 | 31.97 | 135.47 | 48.28 | 1.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 107.45 | 76.63 | 30.82 | 161.60 | 57.12 | 1.33 | 0.00 | 0.00 |
February | 97.45 | 63.08 | 34.37 | 149.06 | 49.63 | 0.00 | 0.00 | 0.00 |
March | 62.21 | 28.08 | 34.14 | 98.07 | 44.00 | 0.00 | 0.00 | 0.00 |
April | 46.11 | 10.81 | 35.31 | 79.25 | 29.57 | 0.00 | 0.00 | 0.00 |
May | 35.23 | 1.50 | 33.74 | 73.92 | 7.88 | 0.00 | 0.00 | 0.00 |
June | 34.80 | 0.32 | 34.48 | 74.68 | 7.02 | 0.00 | 0.00 | 0.00 |
July | 36.43 | 0.67 | 35.76 | 77.71 | 4.66 | 0.00 | 0.00 | 0.00 |
August | 42.86 | 5.14 | 37.72 | 91.73 | 7.27 | 0.00 | 0.00 | 0.00 |
September | 51.43 | 13.55 | 37.87 | 102.34 | 10.59 | 0.00 | 0.00 | 0.00 |
October | 79.79 | 41.56 | 38.23 | 146.52 | 19.43 | 0.00 | 0.00 | 0.00 |
November | 101.54 | 69.91 | 31.63 | 161.99 | 40.69 | 0.00 | 0.00 | 0.00 |
December | 104.99 | 75.40 | 29.59 | 161.89 | 52.01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.53 | 32.06 | 34.47 | 114.73 | 27.37 | 1.33 | 0.00 | 0.00 |
Minimum of Months | 34.80 | 0.32 | 29.59 | 73.92 | 4.66 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 107.45 | 76.63 | 38.23 | 161.99 | 57.12 | 1.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.87 | 64.09 | 25.78 | 135.09 | 48.02 | 1.33 | 0.00 | 0.00 |
February | 81.51 | 52.76 | 28.75 | 124.65 | 41.64 | 0.00 | 0.00 | 0.00 |
March | 52.04 | 23.48 | 28.55 | 82.02 | 36.93 | 0.00 | 0.00 | 0.00 |
April | 38.57 | 9.04 | 29.53 | 66.38 | 24.77 | 0.00 | 0.00 | 0.00 |
May | 29.47 | 1.25 | 28.22 | 62.14 | 6.52 | 0.00 | 0.00 | 0.00 |
June | 29.11 | 0.27 | 28.84 | 62.82 | 5.81 | 0.00 | 0.00 | 0.00 |
July | 30.47 | 0.56 | 29.91 | 65.37 | 3.82 | 0.00 | 0.00 | 0.00 |
August | 35.85 | 4.30 | 31.55 | 77.05 | 6.02 | 0.00 | 0.00 | 0.00 |
September | 43.01 | 11.34 | 31.68 | 85.84 | 8.80 | 0.00 | 0.00 | 0.00 |
October | 66.74 | 34.76 | 31.97 | 122.72 | 16.26 | 0.00 | 0.00 | 0.00 |
November | 84.93 | 58.47 | 26.45 | 135.56 | 34.16 | 0.00 | 0.00 | 0.00 |
December | 87.81 | 63.06 | 24.75 | 135.41 | 43.70 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 55.65 | 26.82 | 28.83 | 96.12 | 22.93 | 1.33 | 0.00 | 0.00 |
Minimum of Months | 29.11 | 0.27 | 24.75 | 62.14 | 3.82 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 89.87 | 64.09 | 31.97 | 135.56 | 48.02 | 1.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.87 | 64.09 | 25.78 | 135.09 | 48.02 | 1.33 | 0.00 | 0.00 |
February | 81.51 | 52.76 | 28.75 | 124.65 | 41.64 | 0.00 | 0.00 | 0.00 |
March | 52.04 | 23.48 | 28.55 | 82.02 | 36.93 | 0.00 | 0.00 | 0.00 |
April | 38.57 | 9.04 | 29.53 | 66.38 | 24.77 | 0.00 | 0.00 | 0.00 |
May | 29.47 | 1.25 | 28.22 | 62.14 | 6.52 | 0.00 | 0.00 | 0.00 |
June | 29.11 | 0.27 | 28.84 | 62.82 | 5.81 | 0.00 | 0.00 | 0.00 |
July | 30.47 | 0.56 | 29.91 | 65.37 | 3.82 | 0.00 | 0.00 | 0.00 |
August | 35.85 | 4.30 | 31.55 | 77.05 | 6.02 | 0.00 | 0.00 | 0.00 |
September | 43.01 | 11.34 | 31.68 | 85.84 | 8.80 | 0.00 | 0.00 | 0.00 |
October | 66.74 | 34.76 | 31.97 | 122.72 | 16.26 | 0.00 | 0.00 | 0.00 |
November | 84.93 | 58.47 | 26.45 | 135.56 | 34.16 | 0.00 | 0.00 | 0.00 |
December | 87.81 | 63.06 | 24.75 | 135.41 | 43.70 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 55.65 | 26.82 | 28.83 | 96.12 | 22.93 | 1.33 | 0.00 | 0.00 |
Minimum of Months | 29.11 | 0.27 | 24.75 | 62.14 | 3.82 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 89.87 | 64.09 | 31.97 | 135.56 | 48.02 | 1.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 107.45 | 76.63 | 30.82 | 161.76 | 56.81 | 1.33 | 0.00 | 0.00 |
February | 97.45 | 63.08 | 34.37 | 149.25 | 49.32 | 0.00 | 0.00 | 0.00 |
March | 62.21 | 28.08 | 34.14 | 98.22 | 43.71 | 0.00 | 0.00 | 0.00 |
April | 46.11 | 10.81 | 35.31 | 79.35 | 29.40 | 0.00 | 0.00 | 0.00 |
May | 35.23 | 1.50 | 33.74 | 73.99 | 7.80 | 0.00 | 0.00 | 0.00 |
June | 34.80 | 0.32 | 34.48 | 74.75 | 6.94 | 0.00 | 0.00 | 0.00 |
July | 36.43 | 0.67 | 35.76 | 77.78 | 4.60 | 0.00 | 0.00 | 0.00 |
August | 42.86 | 5.14 | 37.72 | 91.79 | 7.20 | 0.00 | 0.00 | 0.00 |
September | 51.43 | 13.55 | 37.87 | 102.39 | 10.51 | 0.00 | 0.00 | 0.00 |
October | 79.79 | 41.56 | 38.23 | 146.57 | 19.32 | 0.00 | 0.00 | 0.00 |
November | 101.54 | 69.91 | 31.63 | 162.09 | 40.52 | 0.00 | 0.00 | 0.00 |
December | 104.99 | 75.40 | 29.59 | 162.03 | 51.73 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.53 | 32.06 | 34.47 | 114.83 | 27.20 | 1.33 | 0.00 | 0.00 |
Minimum of Months | 34.80 | 0.32 | 29.59 | 73.99 | 4.60 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 107.45 | 76.63 | 38.23 | 162.09 | 56.81 | 1.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.87 | 64.09 | 25.78 | 135.39 | 47.38 | 1.50 | 0.00 | 0.00 |
February | 81.51 | 52.76 | 28.75 | 125.01 | 40.96 | 0.00 | 0.00 | 0.00 |
March | 52.04 | 23.48 | 28.55 | 82.29 | 36.27 | 0.00 | 0.00 | 0.00 |
April | 38.57 | 9.04 | 29.53 | 66.55 | 24.36 | 0.00 | 0.00 | 0.00 |
May | 29.47 | 1.25 | 28.22 | 62.17 | 6.43 | 0.00 | 0.00 | 0.00 |
June | 29.11 | 0.27 | 28.84 | 62.82 | 5.76 | 0.00 | 0.00 | 0.00 |
July | 30.47 | 0.56 | 29.91 | 65.31 | 3.82 | 0.00 | 0.00 | 0.00 |
August | 35.85 | 4.30 | 31.55 | 76.98 | 6.05 | 0.00 | 0.00 | 0.00 |
September | 43.01 | 11.34 | 31.68 | 85.79 | 8.80 | 0.00 | 0.00 | 0.00 |
October | 66.74 | 34.76 | 31.97 | 122.73 | 16.18 | 0.00 | 0.00 | 0.00 |
November | 84.93 | 58.47 | 26.45 | 135.73 | 33.82 | 0.00 | 0.00 | 0.00 |
December | 87.81 | 63.06 | 24.75 | 135.67 | 43.10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 55.65 | 26.82 | 28.83 | 96.23 | 22.64 | 1.50 | 0.00 | 0.00 |
Minimum of Months | 29.11 | 0.27 | 24.75 | 62.17 | 3.82 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 89.87 | 64.09 | 31.97 | 135.73 | 47.38 | 1.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.87 | 64.09 | 25.78 | 135.39 | 47.38 | 1.50 | 0.00 | 0.00 |
February | 81.51 | 52.76 | 28.75 | 125.01 | 40.96 | 0.00 | 0.00 | 0.00 |
March | 52.04 | 23.48 | 28.55 | 82.29 | 36.27 | 0.00 | 0.00 | 0.00 |
April | 38.57 | 9.04 | 29.53 | 66.55 | 24.36 | 0.00 | 0.00 | 0.00 |
May | 29.47 | 1.25 | 28.22 | 62.17 | 6.43 | 0.00 | 0.00 | 0.00 |
June | 29.11 | 0.27 | 28.84 | 62.82 | 5.76 | 0.00 | 0.00 | 0.00 |
July | 30.47 | 0.56 | 29.91 | 65.31 | 3.82 | 0.00 | 0.00 | 0.00 |
August | 35.85 | 4.30 | 31.55 | 76.98 | 6.05 | 0.00 | 0.00 | 0.00 |
September | 43.01 | 11.34 | 31.68 | 85.79 | 8.80 | 0.00 | 0.00 | 0.00 |
October | 66.74 | 34.76 | 31.97 | 122.73 | 16.18 | 0.00 | 0.00 | 0.00 |
November | 84.93 | 58.47 | 26.45 | 135.73 | 33.82 | 0.00 | 0.00 | 0.00 |
December | 87.81 | 63.06 | 24.75 | 135.67 | 43.10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 55.65 | 26.82 | 28.83 | 96.23 | 22.64 | 1.50 | 0.00 | 0.00 |
Minimum of Months | 29.11 | 0.27 | 24.75 | 62.17 | 3.82 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 89.87 | 64.09 | 31.97 | 135.73 | 47.38 | 1.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 107.45 | 76.63 | 30.82 | 162.12 | 56.06 | 1.50 | 0.00 | 0.00 |
February | 97.45 | 63.08 | 34.37 | 149.67 | 48.51 | 0.00 | 0.00 | 0.00 |
March | 62.21 | 28.08 | 34.14 | 98.53 | 42.93 | 0.00 | 0.00 | 0.00 |
April | 46.11 | 10.81 | 35.31 | 79.54 | 28.92 | 0.00 | 0.00 | 0.00 |
May | 35.23 | 1.50 | 33.74 | 74.02 | 7.69 | 0.00 | 0.00 | 0.00 |
June | 34.80 | 0.32 | 34.48 | 74.74 | 6.88 | 0.00 | 0.00 | 0.00 |
July | 36.43 | 0.67 | 35.76 | 77.71 | 4.61 | 0.00 | 0.00 | 0.00 |
August | 42.86 | 5.14 | 37.72 | 91.70 | 7.24 | 0.00 | 0.00 | 0.00 |
September | 51.43 | 13.55 | 37.87 | 102.33 | 10.52 | 0.00 | 0.00 | 0.00 |
October | 79.79 | 41.56 | 38.23 | 146.57 | 19.24 | 0.00 | 0.00 | 0.00 |
November | 101.54 | 69.91 | 31.63 | 162.29 | 40.12 | 0.00 | 0.00 | 0.00 |
December | 104.99 | 75.40 | 29.59 | 162.33 | 51.03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.53 | 32.06 | 34.47 | 114.96 | 26.86 | 1.50 | 0.00 | 0.00 |
Minimum of Months | 34.80 | 0.32 | 29.59 | 74.02 | 4.61 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 107.45 | 76.63 | 38.23 | 162.33 | 56.06 | 1.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.87 | 64.09 | 25.78 | 135.84 | 45.26 | 0.00 | 0.00 | 0.00 |
February | 81.51 | 52.76 | 28.75 | 125.62 | 38.67 | 0.00 | 0.00 | 0.00 |
March | 52.04 | 23.48 | 28.55 | 82.61 | 33.99 | 0.00 | 0.00 | 0.00 |
April | 38.57 | 9.04 | 29.53 | 66.68 | 22.91 | 0.00 | 0.00 | 0.00 |
May | 29.47 | 1.25 | 28.22 | 61.68 | 6.26 | 0.00 | 0.00 | 0.00 |
June | 29.11 | 0.27 | 28.84 | 62.11 | 5.79 | 0.00 | 0.00 | 0.00 |
July | 30.47 | 0.56 | 29.91 | 64.32 | 4.09 | 0.00 | 0.00 | 0.00 |
August | 35.85 | 4.30 | 31.55 | 75.98 | 6.56 | 0.00 | 0.00 | 0.00 |
September | 43.01 | 11.34 | 31.68 | 84.99 | 9.18 | 0.00 | 0.00 | 0.00 |
October | 66.74 | 34.76 | 31.97 | 122.19 | 16.18 | 0.00 | 0.00 | 0.00 |
November | 84.93 | 58.47 | 26.45 | 135.86 | 32.78 | 0.00 | 0.00 | 0.00 |
December | 87.81 | 63.06 | 24.75 | 136.09 | 41.19 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 55.65 | 26.82 | 28.83 | 96.02 | 21.81 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 29.11 | 0.27 | 24.75 | 61.68 | 4.09 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 89.87 | 64.09 | 31.97 | 136.09 | 45.26 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.87 | 64.09 | 25.78 | 135.84 | 45.26 | 0.00 | 0.00 | 0.00 |
February | 81.51 | 52.76 | 28.75 | 125.62 | 38.67 | 0.00 | 0.00 | 0.00 |
March | 52.04 | 23.48 | 28.55 | 82.61 | 33.99 | 0.00 | 0.00 | 0.00 |
April | 38.57 | 9.04 | 29.53 | 66.68 | 22.91 | 0.00 | 0.00 | 0.00 |
May | 29.47 | 1.25 | 28.22 | 61.68 | 6.26 | 0.00 | 0.00 | 0.00 |
June | 29.11 | 0.27 | 28.84 | 62.11 | 5.79 | 0.00 | 0.00 | 0.00 |
July | 30.47 | 0.56 | 29.91 | 64.32 | 4.09 | 0.00 | 0.00 | 0.00 |
August | 35.85 | 4.30 | 31.55 | 75.98 | 6.56 | 0.00 | 0.00 | 0.00 |
September | 43.01 | 11.34 | 31.68 | 84.99 | 9.18 | 0.00 | 0.00 | 0.00 |
October | 66.74 | 34.76 | 31.97 | 122.19 | 16.18 | 0.00 | 0.00 | 0.00 |
November | 84.93 | 58.47 | 26.45 | 135.86 | 32.78 | 0.00 | 0.00 | 0.00 |
December | 87.81 | 63.06 | 24.75 | 136.09 | 41.19 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 55.65 | 26.82 | 28.83 | 96.02 | 21.81 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 29.11 | 0.27 | 24.75 | 61.68 | 4.09 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 89.87 | 64.09 | 31.97 | 136.09 | 45.26 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 107.45 | 76.63 | 30.82 | 162.66 | 53.56 | 0.00 | 0.00 | 0.00 |
February | 97.45 | 63.08 | 34.37 | 150.40 | 45.82 | 0.00 | 0.00 | 0.00 |
March | 62.21 | 28.08 | 34.14 | 98.93 | 40.25 | 0.00 | 0.00 | 0.00 |
April | 46.11 | 10.81 | 35.31 | 79.70 | 27.21 | 0.00 | 0.00 | 0.00 |
May | 35.23 | 1.50 | 33.74 | 73.43 | 7.50 | 0.00 | 0.00 | 0.00 |
June | 34.80 | 0.32 | 34.48 | 73.89 | 6.92 | 0.00 | 0.00 | 0.00 |
July | 36.43 | 0.67 | 35.76 | 76.53 | 4.93 | 0.00 | 0.00 | 0.00 |
August | 42.86 | 5.14 | 37.72 | 90.50 | 7.85 | 0.00 | 0.00 | 0.00 |
September | 51.43 | 13.55 | 37.87 | 101.38 | 10.97 | 0.00 | 0.00 | 0.00 |
October | 79.79 | 41.56 | 38.23 | 145.93 | 19.24 | 0.00 | 0.00 | 0.00 |
November | 101.54 | 69.91 | 31.63 | 162.44 | 38.90 | 0.00 | 0.00 | 0.00 |
December | 104.99 | 75.40 | 29.59 | 162.83 | 48.78 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.53 | 32.06 | 34.47 | 114.71 | 25.88 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 34.80 | 0.32 | 29.59 | 73.43 | 4.93 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 107.45 | 76.63 | 38.23 | 162.83 | 53.56 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.240708E+09 | 0.171666E+09 | 69041282.45 | 0.360617E+09 | 0.132628E+09 |
February | 0.197182E+09 | 0.127632E+09 | 69549272.56 | 0.300226E+09 | 0.104414E+09 |
March | 0.139373E+09 | 62899027.69 | 76473585.23 | 0.218804E+09 | 0.101813E+09 |
April | 99968954.93 | 23425199.97 | 76543754.96 | 0.171765E+09 | 65052187.87 |
May | 78929612.44 | 3354397.83 | 75575214.61 | 0.166982E+09 | 16596076.69 |
June | 75453823.09 | 703302.40 | 74750520.70 | 0.163236E+09 | 14007566.02 |
July | 81620854.48 | 1500182.56 | 80120671.91 | 0.176824E+09 | 9387212.55 |
August | 96022619.41 | 11525606.25 | 84497013.16 | 0.206984E+09 | 15665573.74 |
September | 0.111495E+09 | 29383542.52 | 82111012.86 | 0.223229E+09 | 21720786.68 |
October | 0.178751E+09 | 93112331.70 | 85638602.58 | 0.329096E+09 | 42286446.32 |
November | 0.220134E+09 | 0.151565E+09 | 68569497.40 | 0.351074E+09 | 89627933.05 |
December | 0.235201E+09 | 0.168908E+09 | 66292070.89 | 0.361865E+09 | 0.120138E+09 |
Annual Sum or Average | 0.175484E+10 | 0.845675E+09 | 0.909162E+09 | 0.303070E+10 | 0.733336E+09 |
Minimum of Months | 75453823.09 | 703302.40 | 66292070.89 | 0.163236E+09 | 9387212.55 |
Maximum of Months | 0.240708E+09 | 0.171666E+09 | 85638602.58 | 0.361865E+09 | 0.132628E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.240708E+09 | 0.171666E+09 | 69041282.45 | 0.360617E+09 | 0.132628E+09 |
February | 0.197182E+09 | 0.127632E+09 | 69549272.56 | 0.300226E+09 | 0.104414E+09 |
March | 0.139373E+09 | 62899027.69 | 76473585.23 | 0.218804E+09 | 0.101813E+09 |
April | 99968954.93 | 23425199.97 | 76543754.96 | 0.171765E+09 | 65052187.87 |
May | 78929612.44 | 3354397.83 | 75575214.61 | 0.166982E+09 | 16596076.69 |
June | 75453823.09 | 703302.40 | 74750520.70 | 0.163236E+09 | 14007566.02 |
July | 81620854.48 | 1500182.56 | 80120671.91 | 0.176824E+09 | 9387212.55 |
August | 96022619.41 | 11525606.25 | 84497013.16 | 0.206984E+09 | 15665573.74 |
September | 0.111495E+09 | 29383542.52 | 82111012.86 | 0.223229E+09 | 21720786.68 |
October | 0.178751E+09 | 93112331.70 | 85638602.58 | 0.329096E+09 | 42286446.32 |
November | 0.220134E+09 | 0.151565E+09 | 68569497.40 | 0.351074E+09 | 89627933.05 |
December | 0.235201E+09 | 0.168908E+09 | 66292070.89 | 0.361865E+09 | 0.120138E+09 |
Annual Sum or Average | 0.175484E+10 | 0.845675E+09 | 0.909162E+09 | 0.303070E+10 | 0.733336E+09 |
Minimum of Months | 75453823.09 | 703302.40 | 66292070.89 | 0.163236E+09 | 9387212.55 |
Maximum of Months | 0.240708E+09 | 0.171666E+09 | 85638602.58 | 0.361865E+09 | 0.132628E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.240708E+09 | 0.171666E+09 | 69041282.45 | 0.360617E+09 | 0.132628E+09 |
February | 0.197182E+09 | 0.127632E+09 | 69549272.56 | 0.300226E+09 | 0.104414E+09 |
March | 0.139373E+09 | 62899027.69 | 76473585.23 | 0.218804E+09 | 0.101813E+09 |
April | 99968954.93 | 23425199.97 | 76543754.96 | 0.171765E+09 | 65052187.87 |
May | 78929612.44 | 3354397.83 | 75575214.61 | 0.166982E+09 | 16596076.69 |
June | 75453823.09 | 703302.40 | 74750520.70 | 0.163236E+09 | 14007566.02 |
July | 81620854.48 | 1500182.56 | 80120671.91 | 0.176824E+09 | 9387212.55 |
August | 96022619.41 | 11525606.25 | 84497013.16 | 0.206984E+09 | 15665573.74 |
September | 0.111495E+09 | 29383542.52 | 82111012.86 | 0.223229E+09 | 21720786.68 |
October | 0.178751E+09 | 93112331.70 | 85638602.58 | 0.329096E+09 | 42286446.32 |
November | 0.220134E+09 | 0.151565E+09 | 68569497.40 | 0.351074E+09 | 89627933.05 |
December | 0.235201E+09 | 0.168908E+09 | 66292070.89 | 0.361865E+09 | 0.120138E+09 |
Annual Sum or Average | 0.175484E+10 | 0.845675E+09 | 0.909162E+09 | 0.303070E+10 | 0.733336E+09 |
Minimum of Months | 75453823.09 | 703302.40 | 66292070.89 | 0.163236E+09 | 9387212.55 |
Maximum of Months | 0.240708E+09 | 0.171666E+09 | 85638602.58 | 0.361865E+09 | 0.132628E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.240708E+09 | 0.171666E+09 | 69041282.45 | 0.360617E+09 | 0.132628E+09 |
February | 0.197182E+09 | 0.127632E+09 | 69549272.56 | 0.300226E+09 | 0.104414E+09 |
March | 0.139373E+09 | 62899027.69 | 76473585.23 | 0.218804E+09 | 0.101813E+09 |
April | 99968954.93 | 23425199.97 | 76543754.96 | 0.171765E+09 | 65052187.87 |
May | 78929612.44 | 3354397.83 | 75575214.61 | 0.166982E+09 | 16596076.69 |
June | 75453823.09 | 703302.40 | 74750520.70 | 0.163236E+09 | 14007566.02 |
July | 81620854.48 | 1500182.56 | 80120671.91 | 0.176824E+09 | 9387212.55 |
August | 96022619.41 | 11525606.25 | 84497013.16 | 0.206984E+09 | 15665573.74 |
September | 0.111495E+09 | 29383542.52 | 82111012.86 | 0.223229E+09 | 21720786.68 |
October | 0.178751E+09 | 93112331.70 | 85638602.58 | 0.329096E+09 | 42286446.32 |
November | 0.220134E+09 | 0.151565E+09 | 68569497.40 | 0.351074E+09 | 89627933.05 |
December | 0.235201E+09 | 0.168908E+09 | 66292070.89 | 0.361865E+09 | 0.120138E+09 |
Annual Sum or Average | 0.175484E+10 | 0.845675E+09 | 0.909162E+09 | 0.303070E+10 | 0.733336E+09 |
Minimum of Months | 75453823.09 | 703302.40 | 66292070.89 | 0.163236E+09 | 9387212.55 |
Maximum of Months | 0.240708E+09 | 0.171666E+09 | 85638602.58 | 0.361865E+09 | 0.132628E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.289368E+09 | 0.206369E+09 | 82998250.47 | 0.434031E+09 | 0.157876E+09 |
February | 0.237043E+09 | 0.153434E+09 | 83608932.79 | 0.361297E+09 | 0.124393E+09 |
March | 0.167547E+09 | 75614314.65 | 91933022.62 | 0.263333E+09 | 0.121248E+09 |
April | 0.120178E+09 | 28160696.70 | 92017377.45 | 0.206340E+09 | 77705452.41 |
May | 94885545.44 | 4032502.60 | 90853042.84 | 0.199812E+09 | 19997921.15 |
June | 90707111.54 | 845477.76 | 89861633.79 | 0.195186E+09 | 16882497.17 |
July | 98120832.69 | 1803450.40 | 96317382.29 | 0.211390E+09 | 11379921.10 |
August | 0.115434E+09 | 13855553.09 | 0.101578E+09 | 0.247771E+09 | 18878056.52 |
September | 0.134034E+09 | 35323541.73 | 98710078.52 | 0.267591E+09 | 26161932.97 |
October | 0.214886E+09 | 0.111935E+09 | 0.102951E+09 | 0.395040E+09 | 50627829.66 |
November | 0.264635E+09 | 0.182204E+09 | 82431092.21 | 0.421945E+09 | 0.106984E+09 |
December | 0.282747E+09 | 0.203054E+09 | 79693274.94 | 0.435209E+09 | 0.143103E+09 |
Annual Sum or Average | 0.210959E+10 | 0.101663E+10 | 0.109295E+10 | 0.363895E+10 | 0.875237E+09 |
Minimum of Months | 90707111.54 | 845477.76 | 79693274.94 | 0.195186E+09 | 11379921.10 |
Maximum of Months | 0.289368E+09 | 0.206369E+09 | 0.102951E+09 | 0.435209E+09 | 0.157876E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.289368E+09 | 0.206369E+09 | 82998250.47 | 0.434031E+09 | 0.157876E+09 |
February | 0.237043E+09 | 0.153434E+09 | 83608932.79 | 0.361297E+09 | 0.124393E+09 |
March | 0.167547E+09 | 75614314.65 | 91933022.62 | 0.263333E+09 | 0.121248E+09 |
April | 0.120178E+09 | 28160696.70 | 92017377.45 | 0.206340E+09 | 77705452.41 |
May | 94885545.44 | 4032502.60 | 90853042.84 | 0.199812E+09 | 19997921.15 |
June | 90707111.54 | 845477.76 | 89861633.79 | 0.195186E+09 | 16882497.17 |
July | 98120832.69 | 1803450.40 | 96317382.29 | 0.211390E+09 | 11379921.10 |
August | 0.115434E+09 | 13855553.09 | 0.101578E+09 | 0.247771E+09 | 18878056.52 |
September | 0.134034E+09 | 35323541.73 | 98710078.52 | 0.267591E+09 | 26161932.97 |
October | 0.214886E+09 | 0.111935E+09 | 0.102951E+09 | 0.395040E+09 | 50627829.66 |
November | 0.264635E+09 | 0.182204E+09 | 82431092.21 | 0.421945E+09 | 0.106984E+09 |
December | 0.282747E+09 | 0.203054E+09 | 79693274.94 | 0.435209E+09 | 0.143103E+09 |
Annual Sum or Average | 0.210959E+10 | 0.101663E+10 | 0.109295E+10 | 0.363895E+10 | 0.875237E+09 |
Minimum of Months | 90707111.54 | 845477.76 | 79693274.94 | 0.195186E+09 | 11379921.10 |
Maximum of Months | 0.289368E+09 | 0.206369E+09 | 0.102951E+09 | 0.435209E+09 | 0.157876E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.240708E+09 | 0.171666E+09 | 69041282.45 | 0.356779E+09 | 0.140562E+09 |
February | 0.197182E+09 | 0.127632E+09 | 69549272.56 | 0.297409E+09 | 0.109704E+09 |
March | 0.139373E+09 | 62899027.69 | 76473585.23 | 0.216418E+09 | 0.107391E+09 |
April | 99968954.93 | 23425199.97 | 76543754.96 | 0.170990E+09 | 66804903.25 |
May | 78929612.44 | 3354397.83 | 75575214.61 | 0.167410E+09 | 17090975.74 |
June | 75453823.09 | 703302.40 | 74750520.70 | 0.164084E+09 | 14302606.14 |
July | 81620854.48 | 1500182.56 | 80120671.91 | 0.177962E+09 | 9485913.16 |
August | 96022619.41 | 11525606.25 | 84497013.16 | 0.208314E+09 | 15421992.74 |
September | 0.111495E+09 | 29383542.52 | 82111012.86 | 0.224057E+09 | 21556647.89 |
October | 0.178751E+09 | 93112331.70 | 85638602.58 | 0.329391E+09 | 42481599.47 |
November | 0.220134E+09 | 0.151565E+09 | 68569497.40 | 0.349841E+09 | 91323041.07 |
December | 0.235201E+09 | 0.168908E+09 | 66292070.89 | 0.359515E+09 | 0.125267E+09 |
Annual Sum or Average | 0.175484E+10 | 0.845675E+09 | 0.909162E+09 | 0.302217E+10 | 0.761392E+09 |
Minimum of Months | 75453823.09 | 703302.40 | 66292070.89 | 0.164084E+09 | 9485913.16 |
Maximum of Months | 0.240708E+09 | 0.171666E+09 | 85638602.58 | 0.359515E+09 | 0.140562E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.240708E+09 | 0.171666E+09 | 69041282.45 | 0.356779E+09 | 0.140562E+09 |
February | 0.197182E+09 | 0.127632E+09 | 69549272.56 | 0.297409E+09 | 0.109704E+09 |
March | 0.139373E+09 | 62899027.69 | 76473585.23 | 0.216418E+09 | 0.107391E+09 |
April | 99968954.93 | 23425199.97 | 76543754.96 | 0.170990E+09 | 66804903.25 |
May | 78929612.44 | 3354397.83 | 75575214.61 | 0.167410E+09 | 17090975.74 |
June | 75453823.09 | 703302.40 | 74750520.70 | 0.164084E+09 | 14302606.14 |
July | 81620854.48 | 1500182.56 | 80120671.91 | 0.177962E+09 | 9485913.16 |
August | 96022619.41 | 11525606.25 | 84497013.16 | 0.208314E+09 | 15421992.74 |
September | 0.111495E+09 | 29383542.52 | 82111012.86 | 0.224057E+09 | 21556647.89 |
October | 0.178751E+09 | 93112331.70 | 85638602.58 | 0.329391E+09 | 42481599.47 |
November | 0.220134E+09 | 0.151565E+09 | 68569497.40 | 0.349841E+09 | 91323041.07 |
December | 0.235201E+09 | 0.168908E+09 | 66292070.89 | 0.359515E+09 | 0.125267E+09 |
Annual Sum or Average | 0.175484E+10 | 0.845675E+09 | 0.909162E+09 | 0.302217E+10 | 0.761392E+09 |
Minimum of Months | 75453823.09 | 703302.40 | 66292070.89 | 0.164084E+09 | 9485913.16 |
Maximum of Months | 0.240708E+09 | 0.171666E+09 | 85638602.58 | 0.359515E+09 | 0.140562E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.289368E+09 | 0.206369E+09 | 82998250.47 | 0.429586E+09 | 0.167178E+09 |
February | 0.237043E+09 | 0.153434E+09 | 83608932.79 | 0.358035E+09 | 0.130603E+09 |
March | 0.167547E+09 | 75614314.65 | 91933022.62 | 0.260563E+09 | 0.127811E+09 |
April | 0.120178E+09 | 28160696.70 | 92017377.45 | 0.205451E+09 | 79774717.21 |
May | 94885545.44 | 4032502.60 | 90853042.84 | 0.200329E+09 | 20596596.77 |
June | 90707111.54 | 845477.76 | 89861633.79 | 0.196190E+09 | 17237436.71 |
July | 98120832.69 | 1803450.40 | 96317382.29 | 0.212744E+09 | 11506688.70 |
August | 0.115434E+09 | 13855553.09 | 0.101578E+09 | 0.249384E+09 | 18590430.11 |
September | 0.134034E+09 | 35323541.73 | 98710078.52 | 0.268620E+09 | 25967259.23 |
October | 0.214886E+09 | 0.111935E+09 | 0.102951E+09 | 0.395477E+09 | 50846166.14 |
November | 0.264635E+09 | 0.182204E+09 | 82431092.21 | 0.420574E+09 | 0.108972E+09 |
December | 0.282747E+09 | 0.203054E+09 | 79693274.94 | 0.432524E+09 | 0.149115E+09 |
Annual Sum or Average | 0.210959E+10 | 0.101663E+10 | 0.109295E+10 | 0.362947E+10 | 0.908198E+09 |
Minimum of Months | 90707111.54 | 845477.76 | 79693274.94 | 0.196190E+09 | 11506688.70 |
Maximum of Months | 0.289368E+09 | 0.206369E+09 | 0.102951E+09 | 0.432524E+09 | 0.167178E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.240708E+09 | 0.171666E+09 | 69041282.45 | 0.357987E+09 | 0.138119E+09 |
February | 0.197182E+09 | 0.127632E+09 | 69549272.56 | 0.298175E+09 | 0.108647E+09 |
March | 0.139373E+09 | 62899027.69 | 76473585.23 | 0.216785E+09 | 0.107107E+09 |
April | 99968954.93 | 23425199.97 | 76543754.96 | 0.170650E+09 | 69307348.49 |
May | 78929612.44 | 3354397.83 | 75575214.61 | 0.165588E+09 | 21129063.09 |
June | 75453823.09 | 703302.40 | 74750520.70 | 0.162168E+09 | 18551949.36 |
July | 81620854.48 | 1500182.56 | 80120671.91 | 0.174117E+09 | 12988457.77 |
August | 96022619.41 | 11525606.25 | 84497013.16 | 0.205707E+09 | 19439846.76 |
September | 0.111495E+09 | 29383542.52 | 82111012.86 | 0.222351E+09 | 26128323.12 |
October | 0.178751E+09 | 93112331.70 | 85638602.58 | 0.328278E+09 | 47238985.91 |
November | 0.220134E+09 | 0.151565E+09 | 68569497.40 | 0.350018E+09 | 93566487.13 |
December | 0.235201E+09 | 0.168908E+09 | 66292070.89 | 0.360240E+09 | 0.124933E+09 |
Annual Sum or Average | 0.175484E+10 | 0.845675E+09 | 0.909162E+09 | 0.301206E+10 | 0.787157E+09 |
Minimum of Months | 75453823.09 | 703302.40 | 66292070.89 | 0.162168E+09 | 12988457.77 |
Maximum of Months | 0.240708E+09 | 0.171666E+09 | 85638602.58 | 0.360240E+09 | 0.138119E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.240708E+09 | 0.171666E+09 | 69041282.45 | 0.357987E+09 | 0.138119E+09 |
February | 0.197182E+09 | 0.127632E+09 | 69549272.56 | 0.298175E+09 | 0.108647E+09 |
March | 0.139373E+09 | 62899027.69 | 76473585.23 | 0.216785E+09 | 0.107107E+09 |
April | 99968954.93 | 23425199.97 | 76543754.96 | 0.170650E+09 | 69307348.49 |
May | 78929612.44 | 3354397.83 | 75575214.61 | 0.165588E+09 | 21129063.09 |
June | 75453823.09 | 703302.40 | 74750520.70 | 0.162168E+09 | 18551949.36 |
July | 81620854.48 | 1500182.56 | 80120671.91 | 0.174117E+09 | 12988457.77 |
August | 96022619.41 | 11525606.25 | 84497013.16 | 0.205707E+09 | 19439846.76 |
September | 0.111495E+09 | 29383542.52 | 82111012.86 | 0.222351E+09 | 26128323.12 |
October | 0.178751E+09 | 93112331.70 | 85638602.58 | 0.328278E+09 | 47238985.91 |
November | 0.220134E+09 | 0.151565E+09 | 68569497.40 | 0.350018E+09 | 93566487.13 |
December | 0.235201E+09 | 0.168908E+09 | 66292070.89 | 0.360240E+09 | 0.124933E+09 |
Annual Sum or Average | 0.175484E+10 | 0.845675E+09 | 0.909162E+09 | 0.301206E+10 | 0.787157E+09 |
Minimum of Months | 75453823.09 | 703302.40 | 66292070.89 | 0.162168E+09 | 12988457.77 |
Maximum of Months | 0.240708E+09 | 0.171666E+09 | 85638602.58 | 0.360240E+09 | 0.138119E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.287786E+09 | 0.205242E+09 | 82544708.12 | 0.428673E+09 | 0.163384E+09 |
February | 0.235747E+09 | 0.152595E+09 | 83152053.37 | 0.356991E+09 | 0.128630E+09 |
March | 0.166632E+09 | 75201121.67 | 91430656.38 | 0.259578E+09 | 0.126750E+09 |
April | 0.119521E+09 | 28006813.11 | 91514550.25 | 0.203938E+09 | 82237435.00 |
May | 94367045.19 | 4010467.07 | 90356578.12 | 0.197134E+09 | 25221975.57 |
June | 90211444.27 | 840857.66 | 89370586.61 | 0.192913E+09 | 22138716.86 |
July | 97584653.27 | 1793595.48 | 95791057.80 | 0.207157E+09 | 15594258.12 |
August | 0.114803E+09 | 13779839.69 | 0.101023E+09 | 0.245024E+09 | 23225526.70 |
September | 0.133301E+09 | 35130516.91 | 98170679.18 | 0.265186E+09 | 31182475.06 |
October | 0.213712E+09 | 0.111324E+09 | 0.102388E+09 | 0.392038E+09 | 56136871.31 |
November | 0.263189E+09 | 0.181208E+09 | 81980649.09 | 0.418485E+09 | 0.110968E+09 |
December | 0.281202E+09 | 0.201944E+09 | 79257792.56 | 0.431019E+09 | 0.147878E+09 |
Annual Sum or Average | 0.209806E+10 | 0.101108E+10 | 0.108698E+10 | 0.359814E+10 | 0.933347E+09 |
Minimum of Months | 90211444.27 | 840857.66 | 79257792.56 | 0.192913E+09 | 15594258.12 |
Maximum of Months | 0.287786E+09 | 0.205242E+09 | 0.102388E+09 | 0.431019E+09 | 0.163384E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.240708E+09 | 0.171666E+09 | 69041282.45 | 0.358751E+09 | 0.136171E+09 |
February | 0.197182E+09 | 0.127632E+09 | 69549272.56 | 0.298737E+09 | 0.107242E+09 |
March | 0.139373E+09 | 62899027.69 | 76473585.23 | 0.217196E+09 | 0.105896E+09 |
April | 99968954.93 | 23425199.97 | 76543754.96 | 0.170762E+09 | 68946387.63 |
May | 78929612.44 | 3354397.83 | 75575214.61 | 0.165526E+09 | 21385818.21 |
June | 75453823.09 | 703302.40 | 74750520.70 | 0.162072E+09 | 18895350.91 |
July | 81620854.48 | 1500182.56 | 80120671.91 | 0.173911E+09 | 13394515.50 |
August | 96022619.41 | 11525606.25 | 84497013.16 | 0.205585E+09 | 19846379.35 |
September | 0.111495E+09 | 29383542.52 | 82111012.86 | 0.222238E+09 | 26480112.81 |
October | 0.178751E+09 | 93112331.70 | 85638602.58 | 0.328236E+09 | 47507916.62 |
November | 0.220134E+09 | 0.151565E+09 | 68569497.40 | 0.350192E+09 | 93088483.92 |
December | 0.235201E+09 | 0.168908E+09 | 66292070.89 | 0.360682E+09 | 0.123628E+09 |
Annual Sum or Average | 0.175484E+10 | 0.845675E+09 | 0.909162E+09 | 0.301389E+10 | 0.782481E+09 |
Minimum of Months | 75453823.09 | 703302.40 | 66292070.89 | 0.162072E+09 | 13394515.50 |
Maximum of Months | 0.240708E+09 | 0.171666E+09 | 85638602.58 | 0.360682E+09 | 0.136171E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.240708E+09 | 0.171666E+09 | 69041282.45 | 0.358751E+09 | 0.136171E+09 |
February | 0.197182E+09 | 0.127632E+09 | 69549272.56 | 0.298737E+09 | 0.107242E+09 |
March | 0.139373E+09 | 62899027.69 | 76473585.23 | 0.217196E+09 | 0.105896E+09 |
April | 99968954.93 | 23425199.97 | 76543754.96 | 0.170762E+09 | 68946387.63 |
May | 78929612.44 | 3354397.83 | 75575214.61 | 0.165526E+09 | 21385818.21 |
June | 75453823.09 | 703302.40 | 74750520.70 | 0.162072E+09 | 18895350.91 |
July | 81620854.48 | 1500182.56 | 80120671.91 | 0.173911E+09 | 13394515.50 |
August | 96022619.41 | 11525606.25 | 84497013.16 | 0.205585E+09 | 19846379.35 |
September | 0.111495E+09 | 29383542.52 | 82111012.86 | 0.222238E+09 | 26480112.81 |
October | 0.178751E+09 | 93112331.70 | 85638602.58 | 0.328236E+09 | 47507916.62 |
November | 0.220134E+09 | 0.151565E+09 | 68569497.40 | 0.350192E+09 | 93088483.92 |
December | 0.235201E+09 | 0.168908E+09 | 66292070.89 | 0.360682E+09 | 0.123628E+09 |
Annual Sum or Average | 0.175484E+10 | 0.845675E+09 | 0.909162E+09 | 0.301389E+10 | 0.782481E+09 |
Minimum of Months | 75453823.09 | 703302.40 | 66292070.89 | 0.162072E+09 | 13394515.50 |
Maximum of Months | 0.240708E+09 | 0.171666E+09 | 85638602.58 | 0.360682E+09 | 0.136171E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.287786E+09 | 0.205242E+09 | 82544708.12 | 0.429585E+09 | 0.161083E+09 |
February | 0.235747E+09 | 0.152595E+09 | 83152053.37 | 0.357663E+09 | 0.126971E+09 |
March | 0.166632E+09 | 75201121.67 | 91430656.38 | 0.260068E+09 | 0.125318E+09 |
April | 0.119521E+09 | 28006813.11 | 91514550.25 | 0.204074E+09 | 81811054.63 |
May | 94367045.19 | 4010467.07 | 90356578.12 | 0.197060E+09 | 25525050.74 |
June | 90211444.27 | 840857.66 | 89370586.61 | 0.192798E+09 | 22545734.42 |
July | 97584653.27 | 1793595.48 | 95791057.80 | 0.206920E+09 | 16081712.51 |
August | 0.114803E+09 | 13779839.69 | 0.101023E+09 | 0.244881E+09 | 23708049.92 |
September | 0.133301E+09 | 35130516.91 | 98170679.18 | 0.265052E+09 | 31599560.03 |
October | 0.213712E+09 | 0.111324E+09 | 0.102388E+09 | 0.391987E+09 | 56453749.99 |
November | 0.263189E+09 | 0.181208E+09 | 81980649.09 | 0.418693E+09 | 0.110404E+09 |
December | 0.281202E+09 | 0.201944E+09 | 79257792.56 | 0.431548E+09 | 0.146336E+09 |
Annual Sum or Average | 0.209806E+10 | 0.101108E+10 | 0.108698E+10 | 0.360033E+10 | 0.927837E+09 |
Minimum of Months | 90211444.27 | 840857.66 | 79257792.56 | 0.192798E+09 | 16081712.51 |
Maximum of Months | 0.287786E+09 | 0.205242E+09 | 0.102388E+09 | 0.431548E+09 | 0.161083E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.240708E+09 | 0.171666E+09 | 69041282.45 | 0.359744E+09 | 0.134093E+09 |
February | 0.197182E+09 | 0.127632E+09 | 69549272.56 | 0.299585E+09 | 0.105558E+09 |
March | 0.139373E+09 | 62899027.69 | 76473585.23 | 0.217944E+09 | 0.104170E+09 |
April | 99968954.93 | 23425199.97 | 76543754.96 | 0.171168E+09 | 67901114.62 |
May | 78929612.44 | 3354397.83 | 75575214.61 | 0.165860E+09 | 20624324.83 |
June | 75453823.09 | 703302.40 | 74750520.70 | 0.162382E+09 | 18184100.36 |
July | 81620854.48 | 1500182.56 | 80120671.91 | 0.174275E+09 | 12783227.22 |
August | 96022619.41 | 11525606.25 | 84497013.16 | 0.205884E+09 | 19150172.38 |
September | 0.111495E+09 | 29383542.52 | 82111012.86 | 0.222477E+09 | 25801780.87 |
October | 0.178751E+09 | 93112331.70 | 85638602.58 | 0.328485E+09 | 46730196.84 |
November | 0.220134E+09 | 0.151565E+09 | 68569497.40 | 0.350626E+09 | 92046993.33 |
December | 0.235201E+09 | 0.168908E+09 | 66292070.89 | 0.361354E+09 | 0.121960E+09 |
Annual Sum or Average | 0.175484E+10 | 0.845675E+09 | 0.909162E+09 | 0.301978E+10 | 0.769003E+09 |
Minimum of Months | 75453823.09 | 703302.40 | 66292070.89 | 0.162382E+09 | 12783227.22 |
Maximum of Months | 0.240708E+09 | 0.171666E+09 | 85638602.58 | 0.361354E+09 | 0.134093E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.240708E+09 | 0.171666E+09 | 69041282.45 | 0.359744E+09 | 0.134093E+09 |
February | 0.197182E+09 | 0.127632E+09 | 69549272.56 | 0.299585E+09 | 0.105558E+09 |
March | 0.139373E+09 | 62899027.69 | 76473585.23 | 0.217944E+09 | 0.104170E+09 |
April | 99968954.93 | 23425199.97 | 76543754.96 | 0.171168E+09 | 67901114.62 |
May | 78929612.44 | 3354397.83 | 75575214.61 | 0.165860E+09 | 20624324.83 |
June | 75453823.09 | 703302.40 | 74750520.70 | 0.162382E+09 | 18184100.36 |
July | 81620854.48 | 1500182.56 | 80120671.91 | 0.174275E+09 | 12783227.22 |
August | 96022619.41 | 11525606.25 | 84497013.16 | 0.205884E+09 | 19150172.38 |
September | 0.111495E+09 | 29383542.52 | 82111012.86 | 0.222477E+09 | 25801780.87 |
October | 0.178751E+09 | 93112331.70 | 85638602.58 | 0.328485E+09 | 46730196.84 |
November | 0.220134E+09 | 0.151565E+09 | 68569497.40 | 0.350626E+09 | 92046993.33 |
December | 0.235201E+09 | 0.168908E+09 | 66292070.89 | 0.361354E+09 | 0.121960E+09 |
Annual Sum or Average | 0.175484E+10 | 0.845675E+09 | 0.909162E+09 | 0.301978E+10 | 0.769003E+09 |
Minimum of Months | 75453823.09 | 703302.40 | 66292070.89 | 0.162382E+09 | 12783227.22 |
Maximum of Months | 0.240708E+09 | 0.171666E+09 | 85638602.58 | 0.361354E+09 | 0.134093E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.287786E+09 | 0.205242E+09 | 82544708.12 | 0.430768E+09 | 0.158636E+09 |
February | 0.235747E+09 | 0.152595E+09 | 83152053.37 | 0.358675E+09 | 0.124989E+09 |
March | 0.166632E+09 | 75201121.67 | 91430656.38 | 0.260963E+09 | 0.123286E+09 |
April | 0.119521E+09 | 28006813.11 | 91514550.25 | 0.204561E+09 | 80580876.31 |
May | 94367045.19 | 4010467.07 | 90356578.12 | 0.197459E+09 | 24631572.33 |
June | 90211444.27 | 840857.66 | 89370586.61 | 0.193171E+09 | 21709348.15 |
July | 97584653.27 | 1793595.48 | 95791057.80 | 0.207347E+09 | 15358552.42 |
August | 0.114803E+09 | 13779839.69 | 0.101023E+09 | 0.245237E+09 | 22889296.63 |
September | 0.133301E+09 | 35130516.91 | 98170679.18 | 0.265339E+09 | 30802990.53 |
October | 0.213712E+09 | 0.111324E+09 | 0.102388E+09 | 0.392288E+09 | 55542086.04 |
November | 0.263189E+09 | 0.181208E+09 | 81980649.09 | 0.419215E+09 | 0.109176E+09 |
December | 0.281202E+09 | 0.201944E+09 | 79257792.56 | 0.432350E+09 | 0.144371E+09 |
Annual Sum or Average | 0.209806E+10 | 0.101108E+10 | 0.108698E+10 | 0.360737E+10 | 0.911973E+09 |
Minimum of Months | 90211444.27 | 840857.66 | 79257792.56 | 0.193171E+09 | 15358552.42 |
Maximum of Months | 0.287786E+09 | 0.205242E+09 | 0.102388E+09 | 0.432350E+09 | 0.158636E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.240708E+09 | 0.171666E+09 | 69041282.45 | 0.361910E+09 | 0.129802E+09 |
February | 0.197182E+09 | 0.127632E+09 | 69549272.56 | 0.301519E+09 | 0.101898E+09 |
March | 0.139373E+09 | 62899027.69 | 76473585.23 | 0.219591E+09 | 0.100089E+09 |
April | 99968954.93 | 23425199.97 | 76543754.96 | 0.171887E+09 | 65145648.62 |
May | 78929612.44 | 3354397.83 | 75575214.61 | 0.165729E+09 | 18421416.88 |
June | 75453823.09 | 703302.40 | 74750520.70 | 0.162036E+09 | 15982675.86 |
July | 81620854.48 | 1500182.56 | 80120671.91 | 0.174073E+09 | 11075607.91 |
August | 96022619.41 | 11525606.25 | 84497013.16 | 0.205648E+09 | 17114172.54 |
September | 0.111495E+09 | 29383542.52 | 82111012.86 | 0.222094E+09 | 23855816.80 |
October | 0.178751E+09 | 93112331.70 | 85638602.58 | 0.328588E+09 | 44601058.63 |
November | 0.220134E+09 | 0.151565E+09 | 68569497.40 | 0.351468E+09 | 89445383.72 |
December | 0.235201E+09 | 0.168908E+09 | 66292070.89 | 0.362799E+09 | 0.118200E+09 |
Annual Sum or Average | 0.175484E+10 | 0.845675E+09 | 0.909162E+09 | 0.302734E+10 | 0.735631E+09 |
Minimum of Months | 75453823.09 | 703302.40 | 66292070.89 | 0.162036E+09 | 11075607.91 |
Maximum of Months | 0.240708E+09 | 0.171666E+09 | 85638602.58 | 0.362799E+09 | 0.129802E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.240708E+09 | 0.171666E+09 | 69041282.45 | 0.361910E+09 | 0.129802E+09 |
February | 0.197182E+09 | 0.127632E+09 | 69549272.56 | 0.301519E+09 | 0.101898E+09 |
March | 0.139373E+09 | 62899027.69 | 76473585.23 | 0.219591E+09 | 0.100089E+09 |
April | 99968954.93 | 23425199.97 | 76543754.96 | 0.171887E+09 | 65145648.62 |
May | 78929612.44 | 3354397.83 | 75575214.61 | 0.165729E+09 | 18421416.88 |
June | 75453823.09 | 703302.40 | 74750520.70 | 0.162036E+09 | 15982675.86 |
July | 81620854.48 | 1500182.56 | 80120671.91 | 0.174073E+09 | 11075607.91 |
August | 96022619.41 | 11525606.25 | 84497013.16 | 0.205648E+09 | 17114172.54 |
September | 0.111495E+09 | 29383542.52 | 82111012.86 | 0.222094E+09 | 23855816.80 |
October | 0.178751E+09 | 93112331.70 | 85638602.58 | 0.328588E+09 | 44601058.63 |
November | 0.220134E+09 | 0.151565E+09 | 68569497.40 | 0.351468E+09 | 89445383.72 |
December | 0.235201E+09 | 0.168908E+09 | 66292070.89 | 0.362799E+09 | 0.118200E+09 |
Annual Sum or Average | 0.175484E+10 | 0.845675E+09 | 0.909162E+09 | 0.302734E+10 | 0.735631E+09 |
Minimum of Months | 75453823.09 | 703302.40 | 66292070.89 | 0.162036E+09 | 11075607.91 |
Maximum of Months | 0.240708E+09 | 0.171666E+09 | 85638602.58 | 0.362799E+09 | 0.129802E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.240708E+09 | 0.171666E+09 | 69041282.45 | 0.361910E+09 | 0.129802E+09 |
February | 0.197182E+09 | 0.127632E+09 | 69549272.56 | 0.301519E+09 | 0.101898E+09 |
March | 0.139373E+09 | 62899027.69 | 76473585.23 | 0.219591E+09 | 0.100089E+09 |
April | 99968954.93 | 23425199.97 | 76543754.96 | 0.171887E+09 | 65145648.62 |
May | 78929612.44 | 3354397.83 | 75575214.61 | 0.165729E+09 | 18421416.88 |
June | 75453823.09 | 703302.40 | 74750520.70 | 0.162036E+09 | 15982675.86 |
July | 81620854.48 | 1500182.56 | 80120671.91 | 0.174073E+09 | 11075607.91 |
August | 96022619.41 | 11525606.25 | 84497013.16 | 0.205648E+09 | 17114172.54 |
September | 0.111495E+09 | 29383542.52 | 82111012.86 | 0.222094E+09 | 23855816.80 |
October | 0.178751E+09 | 93112331.70 | 85638602.58 | 0.328588E+09 | 44601058.63 |
November | 0.220134E+09 | 0.151565E+09 | 68569497.40 | 0.351468E+09 | 89445383.72 |
December | 0.235201E+09 | 0.168908E+09 | 66292070.89 | 0.362799E+09 | 0.118200E+09 |
Annual Sum or Average | 0.175484E+10 | 0.845675E+09 | 0.909162E+09 | 0.302734E+10 | 0.735631E+09 |
Minimum of Months | 75453823.09 | 703302.40 | 66292070.89 | 0.162036E+09 | 11075607.91 |
Maximum of Months | 0.240708E+09 | 0.171666E+09 | 85638602.58 | 0.362799E+09 | 0.129802E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.240708E+09 | 0.171666E+09 | 69041282.45 | 0.361910E+09 | 0.129802E+09 |
February | 0.197182E+09 | 0.127632E+09 | 69549272.56 | 0.301519E+09 | 0.101898E+09 |
March | 0.139373E+09 | 62899027.69 | 76473585.23 | 0.219591E+09 | 0.100089E+09 |
April | 99968954.93 | 23425199.97 | 76543754.96 | 0.171887E+09 | 65145648.62 |
May | 78929612.44 | 3354397.83 | 75575214.61 | 0.165729E+09 | 18421416.88 |
June | 75453823.09 | 703302.40 | 74750520.70 | 0.162036E+09 | 15982675.86 |
July | 81620854.48 | 1500182.56 | 80120671.91 | 0.174073E+09 | 11075607.91 |
August | 96022619.41 | 11525606.25 | 84497013.16 | 0.205648E+09 | 17114172.54 |
September | 0.111495E+09 | 29383542.52 | 82111012.86 | 0.222094E+09 | 23855816.80 |
October | 0.178751E+09 | 93112331.70 | 85638602.58 | 0.328588E+09 | 44601058.63 |
November | 0.220134E+09 | 0.151565E+09 | 68569497.40 | 0.351468E+09 | 89445383.72 |
December | 0.235201E+09 | 0.168908E+09 | 66292070.89 | 0.362799E+09 | 0.118200E+09 |
Annual Sum or Average | 0.175484E+10 | 0.845675E+09 | 0.909162E+09 | 0.302734E+10 | 0.735631E+09 |
Minimum of Months | 75453823.09 | 703302.40 | 66292070.89 | 0.162036E+09 | 11075607.91 |
Maximum of Months | 0.240708E+09 | 0.171666E+09 | 85638602.58 | 0.362799E+09 | 0.129802E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.287786E+09 | 0.205242E+09 | 82544708.12 | 0.433224E+09 | 0.153622E+09 |
February | 0.235747E+09 | 0.152595E+09 | 83152053.37 | 0.360883E+09 | 0.120699E+09 |
March | 0.166632E+09 | 75201121.67 | 91430656.38 | 0.262855E+09 | 0.118496E+09 |
April | 0.119521E+09 | 28006813.11 | 91514550.25 | 0.205392E+09 | 77330457.97 |
May | 94367045.19 | 4010467.07 | 90356578.12 | 0.197327E+09 | 22007847.91 |
June | 90211444.27 | 840857.66 | 89370586.61 | 0.192795E+09 | 19085314.26 |
July | 97584653.27 | 1793595.48 | 95791057.80 | 0.207133E+09 | 13308278.20 |
August | 0.114803E+09 | 13779839.69 | 0.101023E+09 | 0.244959E+09 | 20458139.79 |
September | 0.133301E+09 | 35130516.91 | 98170679.18 | 0.264873E+09 | 28484062.07 |
October | 0.213712E+09 | 0.111324E+09 | 0.102388E+09 | 0.392346E+09 | 53014919.29 |
November | 0.263189E+09 | 0.181208E+09 | 81980649.09 | 0.420141E+09 | 0.106111E+09 |
December | 0.281202E+09 | 0.201944E+09 | 79257792.56 | 0.433970E+09 | 0.139965E+09 |
Annual Sum or Average | 0.209806E+10 | 0.101108E+10 | 0.108698E+10 | 0.361590E+10 | 0.872582E+09 |
Minimum of Months | 90211444.27 | 840857.66 | 79257792.56 | 0.192795E+09 | 13308278.20 |
Maximum of Months | 0.287786E+09 | 0.205242E+09 | 0.102388E+09 | 0.433970E+09 | 0.153622E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.287786E+09 | 0.205242E+09 | 82544708.12 | 0.433224E+09 | 0.153622E+09 |
February | 0.235747E+09 | 0.152595E+09 | 83152053.37 | 0.360883E+09 | 0.120699E+09 |
March | 0.166632E+09 | 75201121.67 | 91430656.38 | 0.262855E+09 | 0.118496E+09 |
April | 0.119521E+09 | 28006813.11 | 91514550.25 | 0.205392E+09 | 77330457.97 |
May | 94367045.19 | 4010467.07 | 90356578.12 | 0.197327E+09 | 22007847.91 |
June | 90211444.27 | 840857.66 | 89370586.61 | 0.192795E+09 | 19085314.26 |
July | 97584653.27 | 1793595.48 | 95791057.80 | 0.207133E+09 | 13308278.20 |
August | 0.114803E+09 | 13779839.69 | 0.101023E+09 | 0.244959E+09 | 20458139.79 |
September | 0.133301E+09 | 35130516.91 | 98170679.18 | 0.264873E+09 | 28484062.07 |
October | 0.213712E+09 | 0.111324E+09 | 0.102388E+09 | 0.392346E+09 | 53014919.29 |
November | 0.263189E+09 | 0.181208E+09 | 81980649.09 | 0.420141E+09 | 0.106111E+09 |
December | 0.281202E+09 | 0.201944E+09 | 79257792.56 | 0.433970E+09 | 0.139965E+09 |
Annual Sum or Average | 0.209806E+10 | 0.101108E+10 | 0.108698E+10 | 0.361590E+10 | 0.872582E+09 |
Minimum of Months | 90211444.27 | 840857.66 | 79257792.56 | 0.192795E+09 | 13308278.20 |
Maximum of Months | 0.287786E+09 | 0.205242E+09 | 0.102388E+09 | 0.433970E+09 | 0.153622E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.240708E+09 | 0.171666E+09 | 69041282.45 | 0.361446E+09 | 0.129303E+09 |
February | 0.197182E+09 | 0.127632E+09 | 69549272.56 | 0.301185E+09 | 0.101389E+09 |
March | 0.139373E+09 | 62899027.69 | 76473585.23 | 0.219365E+09 | 99575350.42 |
April | 99968954.93 | 23425199.97 | 76543754.96 | 0.171866E+09 | 64572651.61 |
May | 78929612.44 | 3354397.83 | 75575214.61 | 0.166281E+09 | 17659161.30 |
June | 75453823.09 | 703302.40 | 74750520.70 | 0.162697E+09 | 15224040.21 |
July | 81620854.48 | 1500182.56 | 80120671.91 | 0.174923E+09 | 10366514.94 |
August | 96022619.41 | 11525606.25 | 84497013.16 | 0.206257E+09 | 16264845.83 |
September | 0.111495E+09 | 29383542.52 | 82111012.86 | 0.222385E+09 | 22973472.97 |
October | 0.178751E+09 | 93112331.70 | 85638602.58 | 0.328580E+09 | 43765901.64 |
November | 0.220134E+09 | 0.151565E+09 | 68569497.40 | 0.351150E+09 | 88908336.13 |
December | 0.235201E+09 | 0.168908E+09 | 66292070.89 | 0.362378E+09 | 0.117682E+09 |
Annual Sum or Average | 0.175484E+10 | 0.845675E+09 | 0.909162E+09 | 0.302851E+10 | 0.727684E+09 |
Minimum of Months | 75453823.09 | 703302.40 | 66292070.89 | 0.162697E+09 | 10366514.94 |
Maximum of Months | 0.240708E+09 | 0.171666E+09 | 85638602.58 | 0.362378E+09 | 0.129303E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.240708E+09 | 0.171666E+09 | 69041282.45 | 0.361446E+09 | 0.129303E+09 |
February | 0.197182E+09 | 0.127632E+09 | 69549272.56 | 0.301185E+09 | 0.101389E+09 |
March | 0.139373E+09 | 62899027.69 | 76473585.23 | 0.219365E+09 | 99575350.42 |
April | 99968954.93 | 23425199.97 | 76543754.96 | 0.171866E+09 | 64572651.61 |
May | 78929612.44 | 3354397.83 | 75575214.61 | 0.166281E+09 | 17659161.30 |
June | 75453823.09 | 703302.40 | 74750520.70 | 0.162697E+09 | 15224040.21 |
July | 81620854.48 | 1500182.56 | 80120671.91 | 0.174923E+09 | 10366514.94 |
August | 96022619.41 | 11525606.25 | 84497013.16 | 0.206257E+09 | 16264845.83 |
September | 0.111495E+09 | 29383542.52 | 82111012.86 | 0.222385E+09 | 22973472.97 |
October | 0.178751E+09 | 93112331.70 | 85638602.58 | 0.328580E+09 | 43765901.64 |
November | 0.220134E+09 | 0.151565E+09 | 68569497.40 | 0.351150E+09 | 88908336.13 |
December | 0.235201E+09 | 0.168908E+09 | 66292070.89 | 0.362378E+09 | 0.117682E+09 |
Annual Sum or Average | 0.175484E+10 | 0.845675E+09 | 0.909162E+09 | 0.302851E+10 | 0.727684E+09 |
Minimum of Months | 75453823.09 | 703302.40 | 66292070.89 | 0.162697E+09 | 10366514.94 |
Maximum of Months | 0.240708E+09 | 0.171666E+09 | 85638602.58 | 0.362378E+09 | 0.129303E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.287786E+09 | 0.205242E+09 | 82544708.12 | 0.432818E+09 | 0.152979E+09 |
February | 0.235747E+09 | 0.152595E+09 | 83152053.37 | 0.360605E+09 | 0.120065E+09 |
March | 0.166632E+09 | 75201121.67 | 91430656.38 | 0.262680E+09 | 0.117852E+09 |
April | 0.119521E+09 | 28006813.11 | 91514550.25 | 0.205422E+09 | 76645404.04 |
May | 94367045.19 | 4010467.07 | 90356578.12 | 0.197988E+09 | 21116303.71 |
June | 90211444.27 | 840857.66 | 89370586.61 | 0.193578E+09 | 18197448.25 |
July | 97584653.27 | 1793595.48 | 95791057.80 | 0.208134E+09 | 12476978.00 |
August | 0.114803E+09 | 13779839.69 | 0.101023E+09 | 0.245702E+09 | 19463365.92 |
September | 0.133301E+09 | 35130516.91 | 98170679.18 | 0.265264E+09 | 27451294.73 |
October | 0.213712E+09 | 0.111324E+09 | 0.102388E+09 | 0.392428E+09 | 52028223.73 |
November | 0.263189E+09 | 0.181208E+09 | 81980649.09 | 0.419874E+09 | 0.105457E+09 |
December | 0.281202E+09 | 0.201944E+09 | 79257792.56 | 0.433599E+09 | 0.139309E+09 |
Annual Sum or Average | 0.209806E+10 | 0.101108E+10 | 0.108698E+10 | 0.361809E+10 | 0.863042E+09 |
Minimum of Months | 90211444.27 | 840857.66 | 79257792.56 | 0.193578E+09 | 12476978.00 |
Maximum of Months | 0.287786E+09 | 0.205242E+09 | 0.102388E+09 | 0.433599E+09 | 0.152979E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.240708E+09 | 0.171666E+09 | 69041282.45 | 0.361824E+09 | 0.128614E+09 |
February | 0.197182E+09 | 0.127632E+09 | 69549272.56 | 0.301562E+09 | 0.100748E+09 |
March | 0.139373E+09 | 62899027.69 | 76473585.23 | 0.219691E+09 | 98919123.95 |
April | 99968954.93 | 23425199.97 | 76543754.96 | 0.172067E+09 | 64192098.28 |
May | 78929612.44 | 3354397.83 | 75575214.61 | 0.166439E+09 | 17464904.72 |
June | 75453823.09 | 703302.40 | 74750520.70 | 0.162842E+09 | 15052919.29 |
July | 81620854.48 | 1500182.56 | 80120671.91 | 0.175081E+09 | 10232662.82 |
August | 96022619.41 | 11525606.25 | 84497013.16 | 0.206381E+09 | 16118001.86 |
September | 0.111495E+09 | 29383542.52 | 82111012.86 | 0.222489E+09 | 22806088.93 |
October | 0.178751E+09 | 93112331.70 | 85638602.58 | 0.328704E+09 | 43537572.40 |
November | 0.220134E+09 | 0.151565E+09 | 68569497.40 | 0.351364E+09 | 88534160.95 |
December | 0.235201E+09 | 0.168908E+09 | 66292070.89 | 0.362686E+09 | 0.117044E+09 |
Annual Sum or Average | 0.175484E+10 | 0.845675E+09 | 0.909162E+09 | 0.303113E+10 | 0.723263E+09 |
Minimum of Months | 75453823.09 | 703302.40 | 66292070.89 | 0.162842E+09 | 10232662.82 |
Maximum of Months | 0.240708E+09 | 0.171666E+09 | 85638602.58 | 0.362686E+09 | 0.128614E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.240708E+09 | 0.171666E+09 | 69041282.45 | 0.361824E+09 | 0.128614E+09 |
February | 0.197182E+09 | 0.127632E+09 | 69549272.56 | 0.301562E+09 | 0.100748E+09 |
March | 0.139373E+09 | 62899027.69 | 76473585.23 | 0.219691E+09 | 98919123.95 |
April | 99968954.93 | 23425199.97 | 76543754.96 | 0.172067E+09 | 64192098.28 |
May | 78929612.44 | 3354397.83 | 75575214.61 | 0.166439E+09 | 17464904.72 |
June | 75453823.09 | 703302.40 | 74750520.70 | 0.162842E+09 | 15052919.29 |
July | 81620854.48 | 1500182.56 | 80120671.91 | 0.175081E+09 | 10232662.82 |
August | 96022619.41 | 11525606.25 | 84497013.16 | 0.206381E+09 | 16118001.86 |
September | 0.111495E+09 | 29383542.52 | 82111012.86 | 0.222489E+09 | 22806088.93 |
October | 0.178751E+09 | 93112331.70 | 85638602.58 | 0.328704E+09 | 43537572.40 |
November | 0.220134E+09 | 0.151565E+09 | 68569497.40 | 0.351364E+09 | 88534160.95 |
December | 0.235201E+09 | 0.168908E+09 | 66292070.89 | 0.362686E+09 | 0.117044E+09 |
Annual Sum or Average | 0.175484E+10 | 0.845675E+09 | 0.909162E+09 | 0.303113E+10 | 0.723263E+09 |
Minimum of Months | 75453823.09 | 703302.40 | 66292070.89 | 0.162842E+09 | 10232662.82 |
Maximum of Months | 0.240708E+09 | 0.171666E+09 | 85638602.58 | 0.362686E+09 | 0.128614E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.287786E+09 | 0.205242E+09 | 82544708.12 | 0.433270E+09 | 0.152165E+09 |
February | 0.235747E+09 | 0.152595E+09 | 83152053.37 | 0.361056E+09 | 0.119308E+09 |
March | 0.166632E+09 | 75201121.67 | 91430656.38 | 0.263070E+09 | 0.117077E+09 |
April | 0.119521E+09 | 28006813.11 | 91514550.25 | 0.205664E+09 | 76195679.07 |
May | 94367045.19 | 4010467.07 | 90356578.12 | 0.198178E+09 | 20886100.85 |
June | 90211444.27 | 840857.66 | 89370586.61 | 0.193752E+09 | 17994351.75 |
July | 97584653.27 | 1793595.48 | 95791057.80 | 0.208323E+09 | 12318031.60 |
August | 0.114803E+09 | 13779839.69 | 0.101023E+09 | 0.245851E+09 | 19289272.80 |
September | 0.133301E+09 | 35130516.91 | 98170679.18 | 0.265389E+09 | 27253065.96 |
October | 0.213712E+09 | 0.111324E+09 | 0.102388E+09 | 0.392577E+09 | 51758757.73 |
November | 0.263189E+09 | 0.181208E+09 | 81980649.09 | 0.420131E+09 | 0.105016E+09 |
December | 0.281202E+09 | 0.201944E+09 | 79257792.56 | 0.433968E+09 | 0.138555E+09 |
Annual Sum or Average | 0.209806E+10 | 0.101108E+10 | 0.108698E+10 | 0.362123E+10 | 0.857815E+09 |
Minimum of Months | 90211444.27 | 840857.66 | 79257792.56 | 0.193752E+09 | 12318031.60 |
Maximum of Months | 0.287786E+09 | 0.205242E+09 | 0.102388E+09 | 0.433968E+09 | 0.152165E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.240708E+09 | 0.171666E+09 | 69041282.45 | 0.362631E+09 | 0.126912E+09 |
February | 0.197182E+09 | 0.127632E+09 | 69549272.56 | 0.302415E+09 | 99081343.50 |
March | 0.139373E+09 | 62899027.69 | 76473585.23 | 0.220393E+09 | 97141618.24 |
April | 99968954.93 | 23425199.97 | 76543754.96 | 0.172497E+09 | 63133502.92 |
May | 78929612.44 | 3354397.83 | 75575214.61 | 0.166509E+09 | 17209608.29 |
June | 75453823.09 | 703302.40 | 74750520.70 | 0.162817E+09 | 14917848.37 |
July | 81620854.48 | 1500182.56 | 80120671.91 | 0.174931E+09 | 10240982.47 |
August | 96022619.41 | 11525606.25 | 84497013.16 | 0.206190E+09 | 16209276.90 |
September | 0.111495E+09 | 29383542.52 | 82111012.86 | 0.222364E+09 | 22814181.61 |
October | 0.178751E+09 | 93112331.70 | 85638602.58 | 0.328708E+09 | 43328313.35 |
November | 0.220134E+09 | 0.151565E+09 | 68569497.40 | 0.351805E+09 | 87664482.06 |
December | 0.235201E+09 | 0.168908E+09 | 66292070.89 | 0.363376E+09 | 0.115447E+09 |
Annual Sum or Average | 0.175484E+10 | 0.845675E+09 | 0.909162E+09 | 0.303464E+10 | 0.714100E+09 |
Minimum of Months | 75453823.09 | 703302.40 | 66292070.89 | 0.162817E+09 | 10240982.47 |
Maximum of Months | 0.240708E+09 | 0.171666E+09 | 85638602.58 | 0.363376E+09 | 0.126912E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.240708E+09 | 0.171666E+09 | 69041282.45 | 0.362631E+09 | 0.126912E+09 |
February | 0.197182E+09 | 0.127632E+09 | 69549272.56 | 0.302415E+09 | 99081343.50 |
March | 0.139373E+09 | 62899027.69 | 76473585.23 | 0.220393E+09 | 97141618.24 |
April | 99968954.93 | 23425199.97 | 76543754.96 | 0.172497E+09 | 63133502.92 |
May | 78929612.44 | 3354397.83 | 75575214.61 | 0.166509E+09 | 17209608.29 |
June | 75453823.09 | 703302.40 | 74750520.70 | 0.162817E+09 | 14917848.37 |
July | 81620854.48 | 1500182.56 | 80120671.91 | 0.174931E+09 | 10240982.47 |
August | 96022619.41 | 11525606.25 | 84497013.16 | 0.206190E+09 | 16209276.90 |
September | 0.111495E+09 | 29383542.52 | 82111012.86 | 0.222364E+09 | 22814181.61 |
October | 0.178751E+09 | 93112331.70 | 85638602.58 | 0.328708E+09 | 43328313.35 |
November | 0.220134E+09 | 0.151565E+09 | 68569497.40 | 0.351805E+09 | 87664482.06 |
December | 0.235201E+09 | 0.168908E+09 | 66292070.89 | 0.363376E+09 | 0.115447E+09 |
Annual Sum or Average | 0.175484E+10 | 0.845675E+09 | 0.909162E+09 | 0.303464E+10 | 0.714100E+09 |
Minimum of Months | 75453823.09 | 703302.40 | 66292070.89 | 0.162817E+09 | 10240982.47 |
Maximum of Months | 0.240708E+09 | 0.171666E+09 | 85638602.58 | 0.363376E+09 | 0.126912E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.287786E+09 | 0.205242E+09 | 82544708.12 | 0.434231E+09 | 0.150158E+09 |
February | 0.235747E+09 | 0.152595E+09 | 83152053.37 | 0.362073E+09 | 0.117346E+09 |
March | 0.166632E+09 | 75201121.67 | 91430656.38 | 0.263911E+09 | 0.114986E+09 |
April | 0.119521E+09 | 28006813.11 | 91514550.25 | 0.206178E+09 | 74951924.41 |
May | 94367045.19 | 4010467.07 | 90356578.12 | 0.198259E+09 | 20591290.53 |
June | 90211444.27 | 840857.66 | 89370586.61 | 0.193721E+09 | 17840662.20 |
July | 97584653.27 | 1793595.48 | 95791057.80 | 0.208141E+09 | 12334299.39 |
August | 0.114803E+09 | 13779839.69 | 0.101023E+09 | 0.245620E+09 | 19404336.32 |
September | 0.133301E+09 | 35130516.91 | 98170679.18 | 0.265239E+09 | 27269687.79 |
October | 0.213712E+09 | 0.111324E+09 | 0.102388E+09 | 0.392580E+09 | 51519622.21 |
November | 0.263189E+09 | 0.181208E+09 | 81980649.09 | 0.420657E+09 | 0.103996E+09 |
December | 0.281202E+09 | 0.201944E+09 | 79257792.56 | 0.434790E+09 | 0.136674E+09 |
Annual Sum or Average | 0.209806E+10 | 0.101108E+10 | 0.108698E+10 | 0.362540E+10 | 0.847073E+09 |
Minimum of Months | 90211444.27 | 840857.66 | 79257792.56 | 0.193721E+09 | 12334299.39 |
Maximum of Months | 0.287786E+09 | 0.205242E+09 | 0.102388E+09 | 0.434790E+09 | 0.150158E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.240708E+09 | 0.171666E+09 | 69041282.45 | 0.363833E+09 | 0.121216E+09 |
February | 0.197182E+09 | 0.127632E+09 | 69549272.56 | 0.303890E+09 | 93559367.34 |
March | 0.139373E+09 | 62899027.69 | 76473585.23 | 0.221274E+09 | 91039429.53 |
April | 99968954.93 | 23425199.97 | 76543754.96 | 0.172842E+09 | 59371454.16 |
May | 78929612.44 | 3354397.83 | 75575214.61 | 0.165191E+09 | 16771320.10 |
June | 75453823.09 | 703302.40 | 74750520.70 | 0.160987E+09 | 14996518.11 |
July | 81620854.48 | 1500182.56 | 80120671.91 | 0.172280E+09 | 10956921.26 |
August | 96022619.41 | 11525606.25 | 84497013.16 | 0.203493E+09 | 17571948.60 |
September | 0.111495E+09 | 29383542.52 | 82111012.86 | 0.220306E+09 | 23796709.78 |
October | 0.178751E+09 | 93112331.70 | 85638602.58 | 0.327274E+09 | 43323858.02 |
November | 0.220134E+09 | 0.151565E+09 | 68569497.40 | 0.352136E+09 | 84975438.74 |
December | 0.235201E+09 | 0.168908E+09 | 66292070.89 | 0.364500E+09 | 0.110328E+09 |
Annual Sum or Average | 0.175484E+10 | 0.845675E+09 | 0.909162E+09 | 0.302801E+10 | 0.687907E+09 |
Minimum of Months | 75453823.09 | 703302.40 | 66292070.89 | 0.160987E+09 | 10956921.26 |
Maximum of Months | 0.240708E+09 | 0.171666E+09 | 85638602.58 | 0.364500E+09 | 0.121216E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.240708E+09 | 0.171666E+09 | 69041282.45 | 0.363833E+09 | 0.121216E+09 |
February | 0.197182E+09 | 0.127632E+09 | 69549272.56 | 0.303890E+09 | 93559367.34 |
March | 0.139373E+09 | 62899027.69 | 76473585.23 | 0.221274E+09 | 91039429.53 |
April | 99968954.93 | 23425199.97 | 76543754.96 | 0.172842E+09 | 59371454.16 |
May | 78929612.44 | 3354397.83 | 75575214.61 | 0.165191E+09 | 16771320.10 |
June | 75453823.09 | 703302.40 | 74750520.70 | 0.160987E+09 | 14996518.11 |
July | 81620854.48 | 1500182.56 | 80120671.91 | 0.172280E+09 | 10956921.26 |
August | 96022619.41 | 11525606.25 | 84497013.16 | 0.203493E+09 | 17571948.60 |
September | 0.111495E+09 | 29383542.52 | 82111012.86 | 0.220306E+09 | 23796709.78 |
October | 0.178751E+09 | 93112331.70 | 85638602.58 | 0.327274E+09 | 43323858.02 |
November | 0.220134E+09 | 0.151565E+09 | 68569497.40 | 0.352136E+09 | 84975438.74 |
December | 0.235201E+09 | 0.168908E+09 | 66292070.89 | 0.364500E+09 | 0.110328E+09 |
Annual Sum or Average | 0.175484E+10 | 0.845675E+09 | 0.909162E+09 | 0.302801E+10 | 0.687907E+09 |
Minimum of Months | 75453823.09 | 703302.40 | 66292070.89 | 0.160987E+09 | 10956921.26 |
Maximum of Months | 0.240708E+09 | 0.171666E+09 | 85638602.58 | 0.364500E+09 | 0.121216E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.287786E+09 | 0.205242E+09 | 82544708.12 | 0.435675E+09 | 0.143451E+09 |
February | 0.235747E+09 | 0.152595E+09 | 83152053.37 | 0.363836E+09 | 0.110841E+09 |
March | 0.166632E+09 | 75201121.67 | 91430656.38 | 0.264968E+09 | 0.107798E+09 |
April | 0.119521E+09 | 28006813.11 | 91514550.25 | 0.206586E+09 | 70522191.79 |
May | 94367045.19 | 4010467.07 | 90356578.12 | 0.196668E+09 | 20076415.22 |
June | 90211444.27 | 840857.66 | 89370586.61 | 0.191516E+09 | 17937470.56 |
July | 97584653.27 | 1793595.48 | 95791057.80 | 0.204975E+09 | 13197721.07 |
August | 0.114803E+09 | 13779839.69 | 0.101023E+09 | 0.242384E+09 | 21025867.95 |
September | 0.133301E+09 | 35130516.91 | 98170679.18 | 0.262768E+09 | 28441057.19 |
October | 0.213712E+09 | 0.111324E+09 | 0.102388E+09 | 0.390850E+09 | 51525660.40 |
November | 0.263189E+09 | 0.181208E+09 | 81980649.09 | 0.421041E+09 | 0.100828E+09 |
December | 0.281202E+09 | 0.201944E+09 | 79257792.56 | 0.436132E+09 | 0.130644E+09 |
Annual Sum or Average | 0.209806E+10 | 0.101108E+10 | 0.108698E+10 | 0.361740E+10 | 0.816289E+09 |
Minimum of Months | 90211444.27 | 840857.66 | 79257792.56 | 0.191516E+09 | 13197721.07 |
Maximum of Months | 0.287786E+09 | 0.205242E+09 | 0.102388E+09 | 0.436132E+09 | 0.143451E+09 |
Report: WindowZoneSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 862.65 | 315.96 | 575.55 | 410.47 | 165.08 | 0.00 | 0.00 |
February | 795.10 | 275.48 | 522.00 | 337.88 | 184.12 | 0.00 | 0.00 |
March | 523.40 | 242.59 | 333.25 | 150.40 | 182.86 | 0.00 | 0.00 |
April | 424.28 | 160.35 | 247.00 | 57.88 | 189.12 | 0.00 | 0.00 |
May | 398.58 | 39.72 | 188.73 | 8.02 | 180.71 | 0.00 | 0.00 |
June | 402.51 | 34.64 | 186.43 | 1.74 | 184.69 | 0.00 | 0.00 |
July | 421.92 | 22.52 | 195.16 | 3.59 | 191.58 | 0.00 | 0.00 |
August | 494.13 | 37.49 | 229.60 | 27.56 | 202.04 | 0.00 | 0.00 |
September | 550.96 | 53.71 | 275.48 | 72.60 | 202.88 | 0.00 | 0.00 |
October | 786.46 | 100.96 | 427.41 | 222.64 | 204.77 | 0.00 | 0.00 |
November | 867.36 | 220.86 | 543.91 | 374.49 | 169.42 | 0.00 | 0.00 |
December | 865.40 | 286.27 | 562.39 | 403.88 | 158.51 | 0.00 | 0.00 |
Annual Sum or Average | 615.19 | 148.52 | 356.37 | 171.74 | 184.63 | 0.00 | 0.00 |
Minimum of Months | 398.58 | 22.52 | 186.43 | 1.74 | 158.51 | 0.00 | 0.00 |
Maximum of Months | 867.36 | 315.96 | 575.55 | 410.47 | 204.77 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 426.80 | 167.38 | 287.78 | 205.24 | 82.54 | 0.00 | 0.00 |
February | 393.87 | 144.68 | 261.00 | 168.94 | 92.06 | 0.00 | 0.00 |
March | 258.89 | 127.91 | 166.63 | 75.20 | 91.43 | 0.00 | 0.00 |
April | 211.20 | 82.32 | 123.50 | 28.94 | 94.56 | 0.00 | 0.00 |
May | 199.80 | 20.45 | 94.36 | 4.01 | 90.35 | 0.00 | 0.00 |
June | 202.30 | 17.69 | 93.22 | 0.87 | 92.35 | 0.00 | 0.00 |
July | 212.32 | 11.38 | 97.58 | 1.79 | 95.79 | 0.00 | 0.00 |
August | 248.66 | 18.46 | 114.80 | 13.78 | 101.02 | 0.00 | 0.00 |
September | 276.52 | 26.65 | 137.74 | 36.30 | 101.44 | 0.00 | 0.00 |
October | 393.61 | 50.71 | 213.71 | 111.32 | 102.39 | 0.00 | 0.00 |
November | 432.20 | 112.51 | 271.95 | 187.24 | 84.71 | 0.00 | 0.00 |
December | 429.94 | 149.21 | 281.19 | 201.94 | 79.26 | 0.00 | 0.00 |
Annual Sum or Average | 306.75 | 77.09 | 178.19 | 85.87 | 92.32 | 0.00 | 0.00 |
Minimum of Months | 199.80 | 11.38 | 93.22 | 0.87 | 79.26 | 0.00 | 0.00 |
Maximum of Months | 432.20 | 167.38 | 287.78 | 205.24 | 102.39 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 427.36 | 164.14 | 287.19 | 204.81 | 82.37 | 0.00 | 0.00 |
February | 394.07 | 142.99 | 260.46 | 168.59 | 91.87 | 0.00 | 0.00 |
March | 258.79 | 127.30 | 166.28 | 75.04 | 91.24 | 0.00 | 0.00 |
April | 210.35 | 85.21 | 123.25 | 28.88 | 94.37 | 0.00 | 0.00 |
May | 197.25 | 25.19 | 94.17 | 4.00 | 90.17 | 0.00 | 0.00 |
June | 199.56 | 22.86 | 93.02 | 0.87 | 92.16 | 0.00 | 0.00 |
July | 207.36 | 15.52 | 97.38 | 1.79 | 95.59 | 0.00 | 0.00 |
August | 245.09 | 23.19 | 114.56 | 13.75 | 100.81 | 0.00 | 0.00 |
September | 273.88 | 32.19 | 137.46 | 36.23 | 101.23 | 0.00 | 0.00 |
October | 391.50 | 56.23 | 213.27 | 111.09 | 102.17 | 0.00 | 0.00 |
November | 431.53 | 115.01 | 271.40 | 186.86 | 84.54 | 0.00 | 0.00 |
December | 429.92 | 148.50 | 280.62 | 201.52 | 79.09 | 0.00 | 0.00 |
Annual Sum or Average | 305.12 | 79.52 | 177.82 | 85.69 | 92.13 | 0.00 | 0.00 |
Minimum of Months | 197.25 | 15.52 | 93.02 | 0.87 | 79.09 | 0.00 | 0.00 |
Maximum of Months | 431.53 | 164.14 | 287.19 | 204.81 | 102.17 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 428.27 | 161.82 | 287.19 | 204.81 | 82.37 | 0.00 | 0.00 |
February | 394.82 | 141.14 | 260.46 | 168.59 | 91.87 | 0.00 | 0.00 |
March | 259.28 | 125.86 | 166.28 | 75.04 | 91.24 | 0.00 | 0.00 |
April | 210.49 | 84.76 | 123.25 | 28.88 | 94.37 | 0.00 | 0.00 |
May | 197.17 | 25.50 | 94.17 | 4.00 | 90.17 | 0.00 | 0.00 |
June | 199.44 | 23.28 | 93.02 | 0.87 | 92.16 | 0.00 | 0.00 |
July | 207.12 | 16.01 | 97.38 | 1.79 | 95.59 | 0.00 | 0.00 |
August | 244.94 | 23.67 | 114.56 | 13.75 | 100.81 | 0.00 | 0.00 |
September | 273.74 | 32.62 | 137.46 | 36.23 | 101.23 | 0.00 | 0.00 |
October | 391.45 | 56.55 | 213.27 | 111.09 | 102.17 | 0.00 | 0.00 |
November | 431.74 | 114.42 | 271.40 | 186.86 | 84.54 | 0.00 | 0.00 |
December | 430.45 | 146.95 | 280.62 | 201.52 | 79.09 | 0.00 | 0.00 |
Annual Sum or Average | 305.31 | 79.05 | 177.82 | 85.69 | 92.13 | 0.00 | 0.00 |
Minimum of Months | 197.17 | 16.01 | 93.02 | 0.87 | 79.09 | 0.00 | 0.00 |
Maximum of Months | 431.74 | 161.82 | 287.19 | 204.81 | 102.17 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 429.46 | 159.36 | 287.19 | 204.81 | 82.37 | 0.00 | 0.00 |
February | 395.93 | 138.93 | 260.46 | 168.59 | 91.87 | 0.00 | 0.00 |
March | 260.17 | 123.81 | 166.28 | 75.04 | 91.24 | 0.00 | 0.00 |
April | 210.99 | 83.48 | 123.25 | 28.88 | 94.37 | 0.00 | 0.00 |
May | 197.57 | 24.60 | 94.17 | 4.00 | 90.17 | 0.00 | 0.00 |
June | 199.82 | 22.41 | 93.02 | 0.87 | 92.16 | 0.00 | 0.00 |
July | 207.55 | 15.28 | 97.38 | 1.79 | 95.59 | 0.00 | 0.00 |
August | 245.30 | 22.85 | 114.56 | 13.75 | 100.81 | 0.00 | 0.00 |
September | 274.03 | 31.79 | 137.46 | 36.23 | 101.23 | 0.00 | 0.00 |
October | 391.75 | 55.63 | 213.27 | 111.09 | 102.17 | 0.00 | 0.00 |
November | 432.28 | 113.14 | 271.40 | 186.86 | 84.54 | 0.00 | 0.00 |
December | 431.25 | 144.97 | 280.62 | 201.52 | 79.09 | 0.00 | 0.00 |
Annual Sum or Average | 305.90 | 77.69 | 177.82 | 85.69 | 92.13 | 0.00 | 0.00 |
Minimum of Months | 197.57 | 15.28 | 93.02 | 0.87 | 79.09 | 0.00 | 0.00 |
Maximum of Months | 432.28 | 159.36 | 287.19 | 204.81 | 102.17 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 863.98 | 308.56 | 574.37 | 409.63 | 164.75 | 0.00 | 0.00 |
February | 796.89 | 268.27 | 520.92 | 337.19 | 183.74 | 0.00 | 0.00 |
March | 524.22 | 237.96 | 332.57 | 150.09 | 182.48 | 0.00 | 0.00 |
April | 423.74 | 160.20 | 246.50 | 57.76 | 188.74 | 0.00 | 0.00 |
May | 394.85 | 43.94 | 188.34 | 8.00 | 180.34 | 0.00 | 0.00 |
June | 398.82 | 39.39 | 186.05 | 1.73 | 184.31 | 0.00 | 0.00 |
July | 414.63 | 26.48 | 194.76 | 3.58 | 191.18 | 0.00 | 0.00 |
August | 490.04 | 40.83 | 229.13 | 27.50 | 201.63 | 0.00 | 0.00 |
September | 547.11 | 58.79 | 274.92 | 72.45 | 202.46 | 0.00 | 0.00 |
October | 783.69 | 106.20 | 426.53 | 222.18 | 204.35 | 0.00 | 0.00 |
November | 866.57 | 219.91 | 542.79 | 373.72 | 169.07 | 0.00 | 0.00 |
December | 865.87 | 281.04 | 561.23 | 403.05 | 158.19 | 0.00 | 0.00 |
Annual Sum or Average | 613.30 | 148.65 | 355.64 | 171.39 | 184.25 | 0.00 | 0.00 |
Minimum of Months | 394.85 | 26.48 | 186.05 | 1.73 | 158.19 | 0.00 | 0.00 |
Maximum of Months | 866.57 | 308.56 | 574.37 | 409.63 | 204.35 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 431.49 | 153.67 | 287.19 | 204.81 | 82.37 | 0.00 | 0.00 |
February | 398.05 | 133.45 | 260.46 | 168.59 | 91.87 | 0.00 | 0.00 |
March | 261.88 | 118.36 | 166.28 | 75.04 | 91.24 | 0.00 | 0.00 |
April | 211.86 | 79.39 | 123.25 | 28.88 | 94.37 | 0.00 | 0.00 |
May | 198.08 | 21.07 | 94.17 | 4.00 | 90.17 | 0.00 | 0.00 |
June | 200.22 | 18.77 | 93.02 | 0.87 | 92.16 | 0.00 | 0.00 |
July | 208.33 | 12.40 | 97.38 | 1.79 | 95.59 | 0.00 | 0.00 |
August | 245.75 | 19.41 | 114.56 | 13.75 | 100.81 | 0.00 | 0.00 |
September | 273.93 | 28.32 | 137.46 | 36.23 | 101.23 | 0.00 | 0.00 |
October | 391.87 | 52.11 | 213.27 | 111.09 | 102.17 | 0.00 | 0.00 |
November | 432.94 | 109.29 | 271.40 | 186.86 | 84.54 | 0.00 | 0.00 |
December | 432.48 | 139.89 | 280.62 | 201.52 | 79.09 | 0.00 | 0.00 |
Annual Sum or Average | 306.80 | 73.52 | 177.82 | 85.69 | 92.13 | 0.00 | 0.00 |
Minimum of Months | 198.08 | 12.40 | 93.02 | 0.87 | 79.09 | 0.00 | 0.00 |
Maximum of Months | 432.94 | 153.67 | 287.19 | 204.81 | 102.17 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 431.94 | 152.85 | 287.19 | 204.81 | 82.37 | 0.00 | 0.00 |
February | 398.55 | 132.61 | 260.46 | 168.59 | 91.87 | 0.00 | 0.00 |
March | 262.26 | 117.58 | 166.28 | 75.04 | 91.24 | 0.00 | 0.00 |
April | 212.11 | 78.93 | 123.25 | 28.88 | 94.37 | 0.00 | 0.00 |
May | 198.27 | 20.84 | 94.17 | 4.00 | 90.17 | 0.00 | 0.00 |
June | 200.40 | 18.56 | 93.02 | 0.87 | 92.16 | 0.00 | 0.00 |
July | 208.51 | 12.24 | 97.38 | 1.79 | 95.59 | 0.00 | 0.00 |
August | 245.90 | 19.24 | 114.56 | 13.75 | 100.81 | 0.00 | 0.00 |
September | 274.06 | 28.11 | 137.46 | 36.23 | 101.23 | 0.00 | 0.00 |
October | 392.02 | 51.83 | 213.27 | 111.09 | 102.17 | 0.00 | 0.00 |
November | 433.20 | 108.83 | 271.40 | 186.86 | 84.54 | 0.00 | 0.00 |
December | 432.85 | 139.13 | 280.62 | 201.52 | 79.09 | 0.00 | 0.00 |
Annual Sum or Average | 307.06 | 73.07 | 177.82 | 85.69 | 92.13 | 0.00 | 0.00 |
Minimum of Months | 198.27 | 12.24 | 93.02 | 0.87 | 79.09 | 0.00 | 0.00 |
Maximum of Months | 433.20 | 152.85 | 287.19 | 204.81 | 102.17 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 432.91 | 150.83 | 287.19 | 204.81 | 82.37 | 0.00 | 0.00 |
February | 399.68 | 130.42 | 260.46 | 168.59 | 91.87 | 0.00 | 0.00 |
March | 263.10 | 115.47 | 166.28 | 75.04 | 91.24 | 0.00 | 0.00 |
April | 212.64 | 77.63 | 123.25 | 28.88 | 94.37 | 0.00 | 0.00 |
May | 198.36 | 20.54 | 94.17 | 4.00 | 90.17 | 0.00 | 0.00 |
June | 200.37 | 18.39 | 93.02 | 0.87 | 92.16 | 0.00 | 0.00 |
July | 208.33 | 12.25 | 97.38 | 1.79 | 95.59 | 0.00 | 0.00 |
August | 245.67 | 19.35 | 114.56 | 13.75 | 100.81 | 0.00 | 0.00 |
September | 273.91 | 28.12 | 137.46 | 36.23 | 101.23 | 0.00 | 0.00 |
October | 392.02 | 51.59 | 213.27 | 111.09 | 102.17 | 0.00 | 0.00 |
November | 433.74 | 107.76 | 271.40 | 186.86 | 84.54 | 0.00 | 0.00 |
December | 433.67 | 137.23 | 280.62 | 201.52 | 79.09 | 0.00 | 0.00 |
Annual Sum or Average | 307.42 | 72.15 | 177.82 | 85.69 | 92.13 | 0.00 | 0.00 |
Minimum of Months | 198.36 | 12.25 | 93.02 | 0.87 | 79.09 | 0.00 | 0.00 |
Maximum of Months | 433.74 | 150.83 | 287.19 | 204.81 | 102.17 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 434.34 | 144.07 | 287.19 | 204.81 | 82.37 | 0.00 | 0.00 |
February | 401.63 | 123.16 | 260.46 | 168.59 | 91.87 | 0.00 | 0.00 |
March | 264.16 | 108.23 | 166.28 | 75.04 | 91.24 | 0.00 | 0.00 |
April | 213.07 | 73.02 | 123.25 | 28.88 | 94.37 | 0.00 | 0.00 |
May | 196.78 | 20.02 | 94.17 | 4.00 | 90.17 | 0.00 | 0.00 |
June | 198.11 | 18.49 | 93.02 | 0.87 | 92.16 | 0.00 | 0.00 |
July | 205.17 | 13.11 | 97.38 | 1.79 | 95.59 | 0.00 | 0.00 |
August | 242.45 | 20.97 | 114.56 | 13.75 | 100.81 | 0.00 | 0.00 |
September | 271.37 | 29.33 | 137.46 | 36.23 | 101.23 | 0.00 | 0.00 |
October | 390.31 | 51.59 | 213.27 | 111.09 | 102.17 | 0.00 | 0.00 |
November | 434.15 | 104.47 | 271.40 | 186.86 | 84.54 | 0.00 | 0.00 |
December | 435.01 | 131.16 | 280.62 | 201.52 | 79.09 | 0.00 | 0.00 |
Annual Sum or Average | 306.74 | 69.51 | 177.82 | 85.69 | 92.13 | 0.00 | 0.00 |
Minimum of Months | 196.78 | 13.11 | 93.02 | 0.87 | 79.09 | 0.00 | 0.00 |
Maximum of Months | 435.01 | 144.07 | 287.19 | 204.81 | 102.17 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.231053E+10 | 0.846263E+09 | 0.154157E+10 | 0.109940E+10 | 0.442162E+09 | 0.00 | 0.00 |
February | 0.192350E+10 | 0.666439E+09 | 0.126281E+10 | 0.817396E+09 | 0.445415E+09 | 0.00 | 0.00 |
March | 0.140188E+10 | 0.649746E+09 | 0.892585E+09 | 0.402825E+09 | 0.489760E+09 | 0.00 | 0.00 |
April | 0.109974E+10 | 0.415619E+09 | 0.640232E+09 | 0.150022E+09 | 0.490210E+09 | 0.00 | 0.00 |
May | 0.106755E+10 | 0.106379E+09 | 0.505490E+09 | 21482596.50 | 0.484007E+09 | 0.00 | 0.00 |
June | 0.104331E+10 | 89792566.40 | 0.483230E+09 | 4504165.10 | 0.478725E+09 | 0.00 | 0.00 |
July | 0.113008E+10 | 60306610.22 | 0.522725E+09 | 9607631.05 | 0.513117E+09 | 0.00 | 0.00 |
August | 0.132348E+10 | 0.100417E+09 | 0.614958E+09 | 73813531.21 | 0.541145E+09 | 0.00 | 0.00 |
September | 0.142810E+10 | 0.139206E+09 | 0.714045E+09 | 0.188181E+09 | 0.525864E+09 | 0.00 | 0.00 |
October | 0.210646E+10 | 0.270400E+09 | 0.114478E+10 | 0.596320E+09 | 0.548456E+09 | 0.00 | 0.00 |
November | 0.224819E+10 | 0.572479E+09 | 0.140981E+10 | 0.970667E+09 | 0.439140E+09 | 0.00 | 0.00 |
December | 0.231788E+10 | 0.766758E+09 | 0.150630E+10 | 0.108174E+10 | 0.424555E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.194007E+11 | 0.468381E+10 | 0.112385E+11 | 0.541597E+10 | 0.582256E+10 | 0.00 | 0.00 |
Minimum of Months | 0.104331E+10 | 60306610.22 | 0.483230E+09 | 4504165.10 | 0.424555E+09 | 0.00 | 0.00 |
Maximum of Months | 0.231788E+10 | 0.846263E+09 | 0.154157E+10 | 0.109940E+10 | 0.548456E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.114314E+10 | 0.448301E+09 | 0.770783E+09 | 0.549702E+09 | 0.221081E+09 | 0.00 | 0.00 |
February | 0.952852E+09 | 0.350011E+09 | 0.631406E+09 | 0.408698E+09 | 0.222707E+09 | 0.00 | 0.00 |
March | 0.693399E+09 | 0.342593E+09 | 0.446293E+09 | 0.201412E+09 | 0.244880E+09 | 0.00 | 0.00 |
April | 0.547430E+09 | 0.213384E+09 | 0.320116E+09 | 75011096.64 | 0.245105E+09 | 0.00 | 0.00 |
May | 0.535149E+09 | 54777696.51 | 0.252745E+09 | 10741298.25 | 0.242003E+09 | 0.00 | 0.00 |
June | 0.524356E+09 | 45840974.89 | 0.241615E+09 | 2252082.55 | 0.239363E+09 | 0.00 | 0.00 |
July | 0.568666E+09 | 30477030.67 | 0.261363E+09 | 4803815.53 | 0.256559E+09 | 0.00 | 0.00 |
August | 0.666012E+09 | 49433889.77 | 0.307479E+09 | 36906765.60 | 0.270572E+09 | 0.00 | 0.00 |
September | 0.716732E+09 | 69079831.01 | 0.357023E+09 | 94090626.76 | 0.262932E+09 | 0.00 | 0.00 |
October | 0.105426E+10 | 0.135809E+09 | 0.572388E+09 | 0.298160E+09 | 0.274228E+09 | 0.00 | 0.00 |
November | 0.112026E+10 | 0.291618E+09 | 0.704904E+09 | 0.485334E+09 | 0.219570E+09 | 0.00 | 0.00 |
December | 0.115155E+10 | 0.399648E+09 | 0.753148E+09 | 0.540871E+09 | 0.212277E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.967381E+10 | 0.243097E+10 | 0.561926E+10 | 0.270798E+10 | 0.291128E+10 | 0.00 | 0.00 |
Minimum of Months | 0.524356E+09 | 30477030.67 | 0.241615E+09 | 2252082.55 | 0.212277E+09 | 0.00 | 0.00 |
Maximum of Months | 0.115155E+10 | 0.448301E+09 | 0.770783E+09 | 0.549702E+09 | 0.274228E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.114465E+10 | 0.439621E+09 | 0.769201E+09 | 0.548574E+09 | 0.220627E+09 | 0.00 | 0.00 |
February | 0.953340E+09 | 0.345925E+09 | 0.630110E+09 | 0.407860E+09 | 0.222251E+09 | 0.00 | 0.00 |
March | 0.693148E+09 | 0.340964E+09 | 0.445377E+09 | 0.200999E+09 | 0.244378E+09 | 0.00 | 0.00 |
April | 0.545237E+09 | 0.220852E+09 | 0.319459E+09 | 74857213.05 | 0.244602E+09 | 0.00 | 0.00 |
May | 0.528311E+09 | 67480025.28 | 0.252226E+09 | 10719262.72 | 0.241507E+09 | 0.00 | 0.00 |
June | 0.517249E+09 | 59242520.76 | 0.241119E+09 | 2247462.45 | 0.238872E+09 | 0.00 | 0.00 |
July | 0.555389E+09 | 41569717.69 | 0.260826E+09 | 4793960.61 | 0.256032E+09 | 0.00 | 0.00 |
August | 0.656438E+09 | 62105044.61 | 0.306848E+09 | 36831052.20 | 0.270017E+09 | 0.00 | 0.00 |
September | 0.709887E+09 | 83438746.86 | 0.356290E+09 | 93897601.94 | 0.262393E+09 | 0.00 | 0.00 |
October | 0.104859E+10 | 0.150614E+09 | 0.571214E+09 | 0.297548E+09 | 0.273665E+09 | 0.00 | 0.00 |
November | 0.111852E+10 | 0.298101E+09 | 0.703458E+09 | 0.484338E+09 | 0.219120E+09 | 0.00 | 0.00 |
December | 0.115150E+10 | 0.397745E+09 | 0.751603E+09 | 0.539761E+09 | 0.211842E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.962226E+10 | 0.250766E+10 | 0.560773E+10 | 0.270243E+10 | 0.290531E+10 | 0.00 | 0.00 |
Minimum of Months | 0.517249E+09 | 41569717.69 | 0.241119E+09 | 2247462.45 | 0.211842E+09 | 0.00 | 0.00 |
Maximum of Months | 0.115150E+10 | 0.439621E+09 | 0.769201E+09 | 0.548574E+09 | 0.273665E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.114709E+10 | 0.433425E+09 | 0.769201E+09 | 0.548574E+09 | 0.220627E+09 | 0.00 | 0.00 |
February | 0.955137E+09 | 0.341455E+09 | 0.630110E+09 | 0.407860E+09 | 0.222251E+09 | 0.00 | 0.00 |
March | 0.694460E+09 | 0.337109E+09 | 0.445377E+09 | 0.200999E+09 | 0.244378E+09 | 0.00 | 0.00 |
April | 0.545599E+09 | 0.219704E+09 | 0.319459E+09 | 74857213.05 | 0.244602E+09 | 0.00 | 0.00 |
May | 0.528111E+09 | 68296679.78 | 0.252226E+09 | 10719262.72 | 0.241507E+09 | 0.00 | 0.00 |
June | 0.516941E+09 | 60336351.58 | 0.241119E+09 | 2247462.45 | 0.238872E+09 | 0.00 | 0.00 |
July | 0.554741E+09 | 42869414.60 | 0.260826E+09 | 4793960.61 | 0.256032E+09 | 0.00 | 0.00 |
August | 0.656052E+09 | 63400648.95 | 0.306848E+09 | 36831052.20 | 0.270017E+09 | 0.00 | 0.00 |
September | 0.709528E+09 | 84559404.57 | 0.356290E+09 | 93897601.94 | 0.262393E+09 | 0.00 | 0.00 |
October | 0.104846E+10 | 0.151469E+09 | 0.571214E+09 | 0.297548E+09 | 0.273665E+09 | 0.00 | 0.00 |
November | 0.111908E+10 | 0.296581E+09 | 0.703458E+09 | 0.484338E+09 | 0.219120E+09 | 0.00 | 0.00 |
December | 0.115291E+10 | 0.393591E+09 | 0.751603E+09 | 0.539761E+09 | 0.211842E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.962810E+10 | 0.249280E+10 | 0.560773E+10 | 0.270243E+10 | 0.290531E+10 | 0.00 | 0.00 |
Minimum of Months | 0.516941E+09 | 42869414.60 | 0.241119E+09 | 2247462.45 | 0.211842E+09 | 0.00 | 0.00 |
Maximum of Months | 0.115291E+10 | 0.433425E+09 | 0.769201E+09 | 0.548574E+09 | 0.273665E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.115026E+10 | 0.426821E+09 | 0.769201E+09 | 0.548574E+09 | 0.220627E+09 | 0.00 | 0.00 |
February | 0.957844E+09 | 0.336106E+09 | 0.630110E+09 | 0.407860E+09 | 0.222251E+09 | 0.00 | 0.00 |
March | 0.696851E+09 | 0.331626E+09 | 0.445377E+09 | 0.200999E+09 | 0.244378E+09 | 0.00 | 0.00 |
April | 0.546897E+09 | 0.216383E+09 | 0.319459E+09 | 74857213.05 | 0.244602E+09 | 0.00 | 0.00 |
May | 0.529178E+09 | 65880214.27 | 0.252226E+09 | 10719262.72 | 0.241507E+09 | 0.00 | 0.00 |
June | 0.517935E+09 | 58077214.53 | 0.241119E+09 | 2247462.45 | 0.238872E+09 | 0.00 | 0.00 |
July | 0.555895E+09 | 40923288.85 | 0.260826E+09 | 4793960.61 | 0.256032E+09 | 0.00 | 0.00 |
August | 0.657004E+09 | 61189417.84 | 0.306848E+09 | 36831052.20 | 0.270017E+09 | 0.00 | 0.00 |
September | 0.710292E+09 | 82406161.61 | 0.356290E+09 | 93897601.94 | 0.262393E+09 | 0.00 | 0.00 |
October | 0.104926E+10 | 0.149002E+09 | 0.571214E+09 | 0.297548E+09 | 0.273665E+09 | 0.00 | 0.00 |
November | 0.112047E+10 | 0.293270E+09 | 0.703458E+09 | 0.484338E+09 | 0.219120E+09 | 0.00 | 0.00 |
December | 0.115506E+10 | 0.388290E+09 | 0.751603E+09 | 0.539761E+09 | 0.211842E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.964693E+10 | 0.244997E+10 | 0.560773E+10 | 0.270243E+10 | 0.290531E+10 | 0.00 | 0.00 |
Minimum of Months | 0.517935E+09 | 40923288.85 | 0.241119E+09 | 2247462.45 | 0.211842E+09 | 0.00 | 0.00 |
Maximum of Months | 0.115506E+10 | 0.426821E+09 | 0.769201E+09 | 0.548574E+09 | 0.273665E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.231409E+10 | 0.826449E+09 | 0.153840E+10 | 0.109715E+10 | 0.441255E+09 | 0.00 | 0.00 |
February | 0.192784E+10 | 0.648991E+09 | 0.126022E+10 | 0.815720E+09 | 0.444501E+09 | 0.00 | 0.00 |
March | 0.140407E+10 | 0.637348E+09 | 0.890754E+09 | 0.401998E+09 | 0.488756E+09 | 0.00 | 0.00 |
April | 0.109833E+10 | 0.415243E+09 | 0.638919E+09 | 0.149714E+09 | 0.489204E+09 | 0.00 | 0.00 |
May | 0.105757E+10 | 0.117701E+09 | 0.504453E+09 | 21438525.43 | 0.483014E+09 | 0.00 | 0.00 |
June | 0.103373E+10 | 0.102101E+09 | 0.482238E+09 | 4494924.91 | 0.477743E+09 | 0.00 | 0.00 |
July | 0.111055E+10 | 70917186.57 | 0.521653E+09 | 9587921.21 | 0.512065E+09 | 0.00 | 0.00 |
August | 0.131251E+10 | 0.109372E+09 | 0.613697E+09 | 73662104.40 | 0.540035E+09 | 0.00 | 0.00 |
September | 0.141812E+10 | 0.152390E+09 | 0.712581E+09 | 0.187795E+09 | 0.524785E+09 | 0.00 | 0.00 |
October | 0.209904E+10 | 0.284433E+09 | 0.114243E+10 | 0.595097E+09 | 0.547331E+09 | 0.00 | 0.00 |
November | 0.224615E+10 | 0.570003E+09 | 0.140692E+10 | 0.968676E+09 | 0.438239E+09 | 0.00 | 0.00 |
December | 0.231914E+10 | 0.752729E+09 | 0.150321E+10 | 0.107952E+10 | 0.423684E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.193412E+11 | 0.468768E+10 | 0.112155E+11 | 0.540485E+10 | 0.581061E+10 | 0.00 | 0.00 |
Minimum of Months | 0.103373E+10 | 70917186.57 | 0.482238E+09 | 4494924.91 | 0.423684E+09 | 0.00 | 0.00 |
Maximum of Months | 0.231914E+10 | 0.826449E+09 | 0.153840E+10 | 0.109715E+10 | 0.547331E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.115571E+10 | 0.411586E+09 | 0.769201E+09 | 0.548574E+09 | 0.220627E+09 | 0.00 | 0.00 |
February | 0.962974E+09 | 0.322842E+09 | 0.630110E+09 | 0.407860E+09 | 0.222251E+09 | 0.00 | 0.00 |
March | 0.701410E+09 | 0.317003E+09 | 0.445377E+09 | 0.200999E+09 | 0.244378E+09 | 0.00 | 0.00 |
April | 0.549153E+09 | 0.205791E+09 | 0.319459E+09 | 74857213.05 | 0.244602E+09 | 0.00 | 0.00 |
May | 0.530549E+09 | 56434440.23 | 0.252226E+09 | 10719262.72 | 0.241507E+09 | 0.00 | 0.00 |
June | 0.518973E+09 | 48645367.96 | 0.241119E+09 | 2247462.45 | 0.238872E+09 | 0.00 | 0.00 |
July | 0.557980E+09 | 33209539.15 | 0.260826E+09 | 4793960.61 | 0.256032E+09 | 0.00 | 0.00 |
August | 0.658214E+09 | 51992655.07 | 0.306848E+09 | 36831052.20 | 0.270017E+09 | 0.00 | 0.00 |
September | 0.710034E+09 | 73397740.62 | 0.356290E+09 | 93897601.94 | 0.262393E+09 | 0.00 | 0.00 |
October | 0.104959E+10 | 0.139560E+09 | 0.571214E+09 | 0.297548E+09 | 0.273665E+09 | 0.00 | 0.00 |
November | 0.112217E+10 | 0.283274E+09 | 0.703458E+09 | 0.484338E+09 | 0.219120E+09 | 0.00 | 0.00 |
December | 0.115836E+10 | 0.374673E+09 | 0.751603E+09 | 0.539761E+09 | 0.211842E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.967511E+10 | 0.231841E+10 | 0.560773E+10 | 0.270243E+10 | 0.290531E+10 | 0.00 | 0.00 |
Minimum of Months | 0.518973E+09 | 33209539.15 | 0.241119E+09 | 2247462.45 | 0.211842E+09 | 0.00 | 0.00 |
Maximum of Months | 0.115836E+10 | 0.411586E+09 | 0.769201E+09 | 0.548574E+09 | 0.273665E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.115692E+10 | 0.409393E+09 | 0.769201E+09 | 0.548574E+09 | 0.220627E+09 | 0.00 | 0.00 |
February | 0.964179E+09 | 0.320803E+09 | 0.630110E+09 | 0.407860E+09 | 0.222251E+09 | 0.00 | 0.00 |
March | 0.702451E+09 | 0.314915E+09 | 0.445377E+09 | 0.200999E+09 | 0.244378E+09 | 0.00 | 0.00 |
April | 0.549799E+09 | 0.204580E+09 | 0.319459E+09 | 74857213.05 | 0.244602E+09 | 0.00 | 0.00 |
May | 0.531056E+09 | 55815822.29 | 0.252226E+09 | 10719262.72 | 0.241507E+09 | 0.00 | 0.00 |
June | 0.519437E+09 | 48100007.77 | 0.241119E+09 | 2247462.45 | 0.238872E+09 | 0.00 | 0.00 |
July | 0.558484E+09 | 32783024.39 | 0.260826E+09 | 4793960.61 | 0.256032E+09 | 0.00 | 0.00 |
August | 0.658613E+09 | 51524957.07 | 0.306848E+09 | 36831052.20 | 0.270017E+09 | 0.00 | 0.00 |
September | 0.710366E+09 | 72864602.51 | 0.356290E+09 | 93897601.94 | 0.262393E+09 | 0.00 | 0.00 |
October | 0.104999E+10 | 0.138834E+09 | 0.571214E+09 | 0.297548E+09 | 0.273665E+09 | 0.00 | 0.00 |
November | 0.112286E+10 | 0.282084E+09 | 0.703458E+09 | 0.484338E+09 | 0.219120E+09 | 0.00 | 0.00 |
December | 0.115934E+10 | 0.372642E+09 | 0.751603E+09 | 0.539761E+09 | 0.211842E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.968349E+10 | 0.230434E+10 | 0.560773E+10 | 0.270243E+10 | 0.290531E+10 | 0.00 | 0.00 |
Minimum of Months | 0.519437E+09 | 32783024.39 | 0.241119E+09 | 2247462.45 | 0.211842E+09 | 0.00 | 0.00 |
Maximum of Months | 0.115934E+10 | 0.409393E+09 | 0.769201E+09 | 0.548574E+09 | 0.273665E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.115949E+10 | 0.403981E+09 | 0.769201E+09 | 0.548574E+09 | 0.220627E+09 | 0.00 | 0.00 |
February | 0.966903E+09 | 0.315508E+09 | 0.630110E+09 | 0.407860E+09 | 0.222251E+09 | 0.00 | 0.00 |
March | 0.704695E+09 | 0.309268E+09 | 0.445377E+09 | 0.200999E+09 | 0.244378E+09 | 0.00 | 0.00 |
April | 0.551171E+09 | 0.201219E+09 | 0.319459E+09 | 74857213.05 | 0.244602E+09 | 0.00 | 0.00 |
May | 0.531277E+09 | 55010412.46 | 0.252226E+09 | 10719262.72 | 0.241507E+09 | 0.00 | 0.00 |
June | 0.519356E+09 | 47676190.00 | 0.241119E+09 | 2247462.45 | 0.238872E+09 | 0.00 | 0.00 |
July | 0.558002E+09 | 32815301.60 | 0.260826E+09 | 4793960.61 | 0.256032E+09 | 0.00 | 0.00 |
August | 0.658000E+09 | 51822675.00 | 0.306848E+09 | 36831052.20 | 0.270017E+09 | 0.00 | 0.00 |
September | 0.709968E+09 | 72897634.42 | 0.356290E+09 | 93897601.94 | 0.262393E+09 | 0.00 | 0.00 |
October | 0.105000E+10 | 0.138176E+09 | 0.571214E+09 | 0.297548E+09 | 0.273665E+09 | 0.00 | 0.00 |
November | 0.112427E+10 | 0.279325E+09 | 0.703458E+09 | 0.484338E+09 | 0.219120E+09 | 0.00 | 0.00 |
December | 0.116154E+10 | 0.367568E+09 | 0.751603E+09 | 0.539761E+09 | 0.211842E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.969467E+10 | 0.227527E+10 | 0.560773E+10 | 0.270243E+10 | 0.290531E+10 | 0.00 | 0.00 |
Minimum of Months | 0.519356E+09 | 32815301.60 | 0.241119E+09 | 2247462.45 | 0.211842E+09 | 0.00 | 0.00 |
Maximum of Months | 0.116154E+10 | 0.403981E+09 | 0.769201E+09 | 0.548574E+09 | 0.273665E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.116334E+10 | 0.385882E+09 | 0.769201E+09 | 0.548574E+09 | 0.220627E+09 | 0.00 | 0.00 |
February | 0.971617E+09 | 0.297960E+09 | 0.630110E+09 | 0.407860E+09 | 0.222251E+09 | 0.00 | 0.00 |
March | 0.707514E+09 | 0.289876E+09 | 0.445377E+09 | 0.200999E+09 | 0.244378E+09 | 0.00 | 0.00 |
April | 0.552269E+09 | 0.189265E+09 | 0.319459E+09 | 74857213.05 | 0.244602E+09 | 0.00 | 0.00 |
May | 0.527049E+09 | 53618891.95 | 0.252226E+09 | 10719262.72 | 0.241507E+09 | 0.00 | 0.00 |
June | 0.513490E+09 | 47930115.22 | 0.241119E+09 | 2247462.45 | 0.238872E+09 | 0.00 | 0.00 |
July | 0.549532E+09 | 35108669.14 | 0.260826E+09 | 4793960.61 | 0.256032E+09 | 0.00 | 0.00 |
August | 0.649370E+09 | 56169554.13 | 0.306848E+09 | 36831052.20 | 0.270017E+09 | 0.00 | 0.00 |
September | 0.703379E+09 | 76033987.24 | 0.356290E+09 | 93897601.94 | 0.262393E+09 | 0.00 | 0.00 |
October | 0.104540E+10 | 0.138173E+09 | 0.571214E+09 | 0.297548E+09 | 0.273665E+09 | 0.00 | 0.00 |
November | 0.112531E+10 | 0.270779E+09 | 0.703458E+09 | 0.484338E+09 | 0.219120E+09 | 0.00 | 0.00 |
December | 0.116513E+10 | 0.351300E+09 | 0.751603E+09 | 0.539761E+09 | 0.211842E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.967340E+10 | 0.219210E+10 | 0.560773E+10 | 0.270243E+10 | 0.290531E+10 | 0.00 | 0.00 |
Minimum of Months | 0.513490E+09 | 35108669.14 | 0.241119E+09 | 2247462.45 | 0.211842E+09 | 0.00 | 0.00 |
Maximum of Months | 0.116513E+10 | 0.385882E+09 | 0.769201E+09 | 0.548574E+09 | 0.273665E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 13.57 | 11.02 | 8.64 | 3.24 | 3.13 | 48.31 | 209.17 | 0.01 |
February | 15.49 | 12.82 | 10.40 | 2.82 | 4.36 | 58.07 | 218.23 | 0.02 |
March | 17.07 | 13.58 | 10.72 | 3.68 | 7.24 | 76.61 | 186.08 | 0.03 |
April | 21.23 | 17.54 | 15.23 | 2.65 | 11.47 | 90.28 | 216.86 | 0.02 |
May | 26.90 | 22.82 | 21.10 | 3.11 | 19.64 | 106.10 | 173.47 | 0.04 |
June | 27.61 | 23.37 | 21.62 | 2.44 | 19.77 | 115.40 | 187.69 | 0.03 |
July | 27.94 | 24.58 | 23.34 | 2.53 | 20.70 | 123.49 | 154.05 | 0.05 |
August | 27.43 | 23.90 | 22.52 | 3.20 | 20.40 | 118.51 | 145.78 | 0.03 |
September | 26.23 | 23.37 | 22.24 | 3.39 | 19.02 | 101.73 | 135.58 | 0.05 |
October | 24.23 | 20.47 | 18.40 | 4.11 | 16.60 | 78.24 | 178.15 | 0.01 |
November | 18.91 | 15.31 | 12.62 | 2.63 | 7.99 | 49.56 | 205.43 | 0.01 |
December | 15.68 | 12.88 | 10.53 | 3.17 | 6.01 | 45.08 | 191.18 | 0.02 |
Annual Sum or Average | 21.89 | 18.50 | 16.48 | 3.09 | 13.08 | 84.44 | 183.16 | 0.03 |
Minimum of Months | 13.57 | 11.02 | 8.64 | 2.44 | 3.13 | 45.08 | 135.58 | 0.01 |
Maximum of Months | 27.94 | 24.58 | 23.34 | 4.11 | 20.70 | 123.49 | 218.23 | 0.05 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 27.00 | 02-JAN-14:00 | 18.67 | 14.00 | 1.50 | 17.75 | 146.50 | 0.00 |
February | 28.30 | 02-FEB-12:00 | 20.78 | 17.20 | 6.60 | 17.93 | 127.50 | 748.50 |
March | 30.00 | 26-MAR-13:00 | 19.88 | 14.40 | 3.00 | 19.52 | 288.50 | 548.00 |
April | 33.30 | 28-APR-14:00 | 23.06 | 18.80 | 4.10 | 23.15 | 150.50 | 762.50 |
May | 33.90 | 07-MAY-13:00 | 23.76 | 19.40 | 4.10 | 23.15 | 287.50 | 507.50 |
June | 35.00 | 14-JUN-13:00 | 23.95 | 19.40 | 2.10 | 24.16 | 194.50 | 712.50 |
July | 36.10 | 21-JUL-15:00 | 25.96 | 22.20 | 1.50 | 26.65 | 216.00 | 245.00 |
August | 36.30 | 30-AUG-15:00 | 23.74 | 18.50 | 2.40 | 25.33 | 116.00 | 698.50 |
September | 36.40 | 09-SEP-16:00 | 26.65 | 23.40 | 4.40 | 26.48 | 114.00 | 401.50 |
October | 34.00 | 05-OCT-14:00 | 24.05 | 20.00 | 2.60 | 29.55 | 169.50 | 606.00 |
November | 30.00 | 01-NOV-13:00 | 25.01 | 23.30 | 2.00 | 26.48 | 216.50 | 118.00 |
December | 30.00 | 13-DEC-14:00 | 21.84 | 18.00 | 3.10 | 20.92 | 101.50 | 682.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 27.00 | 18.67 | 14.00 | 1.50 | 17.75 | 101.50 | 0.00 | |
Maximum of Months | 36.40 | 26.65 | 23.40 | 6.60 | 29.55 | 288.50 | 762.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 0.00 | 05-JAN-05:00 | -0.0 | -0.0 | 2.10 | -16.0 | 0.00 | 0.00 |
February | -3.4 | 05-FEB-07:10 | -5.4 | -9.4 | 4.68 | -21.3 | 0.00 | 0.00 |
March | 1.10 | 09-MAR-05:00 | -2.1 | -7.3 | 3.60 | -14.4 | 0.00 | 0.00 |
April | 8.30 | 11-APR-05:00 | 6.95 | 5.50 | 0.00 | -6.9 | 0.00 | 0.00 |
May | 21.10 | 07-MAY-00:00 | 19.58 | 18.90 | 0.00 | 11.46 | 0.00 | 0.00 |
June | 20.60 | 07-JUN-01:00 | 18.00 | 16.70 | 3.60 | 10.50 | 0.00 | 0.00 |
July | 22.20 | 11-JUL-19:00 | 21.37 | 21.10 | 2.10 | 20.22 | 0.00 | 0.00 |
August | 20.20 | 25-AUG-23:00 | 20.20 | 20.20 | 5.30 | 11.84 | 0.00 | 0.00 |
September | 19.20 | 07-SEP-17:00 | 19.20 | 19.20 | 2.50 | 16.85 | 35.00 | 7.00 |
October | 10.00 | 28-OCT-04:00 | 5.56 | 0.00 | 3.60 | -0.1 | 0.00 | 0.00 |
November | 7.20 | 12-NOV-07:49 | 4.12 | 0.18 | 4.60 | -9.0 | 36.00 | 517.00 |
December | 0.00 | 21-DEC-04:00 | -0.9 | -2.0 | 2.10 | -16.2 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -3.4 | -5.4 | -9.4 | 0.00 | -21.3 | 0.00 | 0.00 | |
Maximum of Months | 22.20 | 21.37 | 21.10 | 5.30 | 20.22 | 36.00 | 517.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 22.11 | 31-JAN-12:00 | 25.00 | 21.00 | 5.70 | 20.92 | 336.50 | 96.00 |
February | 21.49 | 24-FEB-12:00 | 27.70 | 18.80 | 4.10 | 17.75 | 165.00 | 746.50 |
March | 22.77 | 30-MAR-12:00 | 29.40 | 20.00 | 2.50 | 27.14 | 340.00 | 0.00 |
April | 25.55 | 28-APR-15:00 | 32.20 | 23.30 | 3.60 | 22.47 | 156.00 | 575.50 |
May | 25.84 | 27-MAY-13:00 | 31.70 | 23.90 | 3.10 | 22.13 | 168.50 | 735.50 |
June | 26.52 | 29-JUN-16:00 | 29.40 | 25.60 | 1.50 | 26.32 | 164.00 | 36.00 |
July | 27.17 | 22-JUL-10:00 | 32.20 | 25.60 | 2.10 | 21.96 | 191.00 | 719.50 |
August | 27.24 | 07-AUG-12:00 | 31.00 | 26.00 | 3.10 | 27.95 | 473.00 | 200.00 |
September | 27.79 | 10-SEP-12:00 | 35.00 | 25.50 | 2.90 | 24.66 | 239.50 | 662.00 |
October | 28.18 | 07-OCT-07:00 | 29.00 | 28.00 | 2.60 | 21.09 | 95.00 | 500.50 |
November | 25.01 | 01-NOV-13:00 | 30.00 | 23.30 | 2.00 | 26.48 | 216.50 | 118.00 |
December | 24.12 | 12-DEC-13:00 | 27.00 | 23.00 | 2.10 | 19.17 | 160.50 | 599.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 21.49 | 25.00 | 18.80 | 1.50 | 17.75 | 95.00 | 0.00 | |
Maximum of Months | 28.18 | 35.00 | 28.00 | 5.70 | 27.95 | 473.00 | 746.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 21.00 | 31-JAN-12:00 | 25.00 | 22.11 | 5.70 | 20.92 | 336.50 | 96.00 |
February | 20.20 | 02-FEB-22:00 | 21.50 | 20.56 | 4.80 | 14.65 | 0.00 | 0.00 |
March | 21.10 | 07-MAR-08:00 | 23.30 | 21.69 | 2.00 | 13.91 | 126.00 | 566.50 |
April | 23.30 | 28-APR-15:00 | 32.20 | 25.55 | 3.60 | 22.47 | 156.00 | 575.50 |
May | 24.40 | 26-MAY-08:20 | 27.07 | 25.09 | 3.10 | 23.71 | 252.67 | 47.33 |
June | 25.60 | 29-JUN-14:00 | 27.20 | 26.00 | 5.10 | 24.16 | 335.00 | 238.00 |
July | 25.60 | 02-JUL-05:00 | 26.10 | 25.71 | 2.60 | 19.52 | 30.50 | 8.50 |
August | 26.60 | 09-AUG-18:00 | 26.60 | 26.60 | 1.90 | 19.52 | 26.00 | 23.00 |
September | 25.50 | 10-SEP-12:00 | 35.00 | 27.79 | 2.90 | 24.66 | 239.50 | 662.00 |
October | 28.00 | 07-OCT-07:00 | 29.00 | 28.18 | 2.60 | 21.09 | 95.00 | 500.50 |
November | 23.80 | 01-NOV-10:00 | 26.10 | 24.39 | 2.00 | 22.64 | 228.50 | 113.00 |
December | 23.00 | 12-DEC-13:00 | 27.00 | 24.12 | 2.10 | 19.17 | 160.50 | 599.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 20.20 | 21.50 | 20.56 | 1.90 | 13.91 | 0.00 | 0.00 | |
Maximum of Months | 28.00 | 35.00 | 28.18 | 5.70 | 24.66 | 336.50 | 662.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 20.46 | 29.60 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 20.78 | 36.65 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 22.23 | 38.94 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 24.49 | 49.11 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 26.95 | 46.95 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 28.93 | 51.71 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 29.89 | 48.43 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 29.58 | 45.50 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 28.08 | 39.22 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 25.80 | 37.51 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 23.35 | 31.26 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 21.40 | 27.18 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 25.18 | 40.17 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 20.46 | 27.18 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 29.89 | 51.71 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK1
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.306880E+09 | -189184259.5 | 0.00 | 0.00 | 744.00 | 0.00 | -117695282.7 | 58.99 | 0.00 | 0.00 |
February | 0.275287E+09 | -170375696.0 | 0.00 | 0.00 | 672.00 | 0.00 | -104910958.3 | 58.99 | 0.00 | 0.00 |
March | 0.300055E+09 | -184428432.2 | 0.00 | 0.00 | 744.00 | 0.00 | -115626662.2 | 58.99 | 0.00 | 0.00 |
April | 0.274762E+09 | -165336011.8 | 0.00 | 0.00 | 720.00 | 0.00 | -109426485.9 | 58.99 | 0.00 | 0.00 |
May | 0.270949E+09 | -159011648.9 | 0.00 | 0.00 | 744.00 | 0.00 | -111937074.4 | 58.99 | 0.00 | 0.00 |
June | 0.254006E+09 | -145799423.4 | 0.00 | 0.00 | 720.00 | 0.00 | -108206758.1 | 58.99 | 0.00 | 0.00 |
July | 0.254394E+09 | -142822018.6 | 0.00 | 0.00 | 744.00 | 0.00 | -111571875.7 | 58.99 | 0.00 | 0.00 |
August | 0.258922E+09 | -147439410.8 | 0.00 | 0.00 | 744.00 | 0.00 | -111482728.4 | 58.99 | 0.00 | 0.00 |
September | 0.256332E+09 | -148330440.0 | 0.00 | 0.00 | 720.00 | 0.00 | -108001595.1 | 58.99 | 0.00 | 0.00 |
October | 0.274976E+09 | -163003721.3 | 0.00 | 0.00 | 744.00 | 0.00 | -111972274.0 | 58.99 | 0.00 | 0.00 |
November | 0.278432E+09 | -168877109.9 | 0.00 | 0.00 | 720.00 | 0.00 | -109554790.0 | 58.99 | 0.00 | 0.00 |
December | 0.300476E+09 | -184816760.7 | 0.00 | 0.00 | 744.00 | 0.00 | -115659204.9 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.330547E+10 | -0.196942E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.133605E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.254006E+09 | -189184259.5 | 0.00 | 0.00 | 672.00 | 0.00 | -117695282.7 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.306880E+09 | -142822018.6 | 0.00 | 0.00 | 744.00 | 0.00 | -104910958.3 | 58.99 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK2
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.304812E+09 | -189192703.3 | 0.00 | 0.00 | 744.00 | 0.00 | -115619114.3 | 58.99 | 0.00 | 0.00 |
February | 0.273966E+09 | -170373650.7 | 0.00 | 0.00 | 672.00 | 0.00 | -103592254.4 | 58.99 | 0.00 | 0.00 |
March | 0.298762E+09 | -184429824.7 | 0.00 | 0.00 | 744.00 | 0.00 | -114332058.5 | 58.99 | 0.00 | 0.00 |
April | 0.274385E+09 | -165339573.9 | 0.00 | 0.00 | 720.00 | 0.00 | -109045436.1 | 58.99 | 0.00 | 0.00 |
May | 0.270782E+09 | -159007295.1 | 0.00 | 0.00 | 744.00 | 0.00 | -111774247.5 | 58.99 | 0.00 | 0.00 |
June | 0.253871E+09 | -145794410.3 | 0.00 | 0.00 | 720.00 | 0.00 | -108077058.3 | 58.99 | 0.00 | 0.00 |
July | 0.254317E+09 | -142848215.6 | 0.00 | 0.00 | 744.00 | 0.00 | -111468875.9 | 58.99 | 0.00 | 0.00 |
August | 0.258901E+09 | -147450222.2 | 0.00 | 0.00 | 744.00 | 0.00 | -111450703.6 | 58.99 | 0.00 | 0.00 |
September | 0.256263E+09 | -148310015.7 | 0.00 | 0.00 | 720.00 | 0.00 | -107953368.1 | 58.99 | 0.00 | 0.00 |
October | 0.274837E+09 | -163023663.8 | 0.00 | 0.00 | 744.00 | 0.00 | -111813807.5 | 58.99 | 0.00 | 0.00 |
November | 0.277984E+09 | -168878339.7 | 0.00 | 0.00 | 720.00 | 0.00 | -109105678.3 | 58.99 | 0.00 | 0.00 |
December | 0.299208E+09 | -184813735.7 | 0.00 | 0.00 | 744.00 | 0.00 | -114393769.8 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.329809E+10 | -0.196946E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.132863E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.253871E+09 | -189192703.3 | 0.00 | 0.00 | 672.00 | 0.00 | -115619114.3 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.304812E+09 | -142848215.6 | 0.00 | 0.00 | 744.00 | 0.00 | -103592254.4 | 58.99 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK3
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.282828E+09 | -166347601.6 | 0.00 | 0.00 | 744.00 | 0.00 | -116480386.7 | 59.00 | 0.00 | 0.00 |
February | 0.253933E+09 | -149953458.7 | 0.00 | 0.00 | 672.00 | 0.00 | -103979224.0 | 58.99 | 0.00 | 0.00 |
March | 0.279041E+09 | -164611932.1 | 0.00 | 0.00 | 744.00 | 0.00 | -114428605.3 | 58.99 | 0.00 | 0.00 |
April | 0.253649E+09 | -145420512.1 | 0.00 | 0.00 | 720.00 | 0.00 | -108228936.0 | 58.99 | 0.00 | 0.00 |
May | 0.251166E+09 | -141050278.1 | 0.00 | 0.00 | 744.00 | 0.00 | -110115241.9 | 58.99 | 0.00 | 0.00 |
June | 0.236195E+09 | -129853241.2 | 0.00 | 0.00 | 720.00 | 0.00 | -106341924.4 | 58.99 | 0.00 | 0.00 |
July | 0.234343E+09 | -124881825.2 | 0.00 | 0.00 | 744.00 | 0.00 | -109460988.6 | 58.99 | 0.00 | 0.00 |
August | 0.241305E+09 | -131696979.3 | 0.00 | 0.00 | 744.00 | 0.00 | -109607973.5 | 58.99 | 0.00 | 0.00 |
September | 0.236605E+09 | -130374120.6 | 0.00 | 0.00 | 720.00 | 0.00 | -106231287.4 | 58.99 | 0.00 | 0.00 |
October | 0.253592E+09 | -143398601.8 | 0.00 | 0.00 | 744.00 | 0.00 | -110193540.4 | 58.98 | 0.00 | 0.00 |
November | 0.257617E+09 | -149109483.0 | 0.00 | 0.00 | 720.00 | 0.00 | -108507399.8 | 58.99 | 0.00 | 0.00 |
December | 0.275928E+09 | -161329372.7 | 0.00 | 0.00 | 744.00 | 0.00 | -114599004.3 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.305620E+10 | -0.173803E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.131817E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.234343E+09 | -166347601.6 | 0.00 | 0.00 | 672.00 | 0.00 | -116480386.7 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.282828E+09 | -124881825.2 | 0.00 | 0.00 | 744.00 | 0.00 | -103979224.0 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK4
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.283237E+09 | -166353048.4 | 0.00 | 0.00 | 744.00 | 0.00 | -116883460.3 | 59.00 | 0.00 | 0.00 |
February | 0.254214E+09 | -149956022.3 | 0.00 | 0.00 | 672.00 | 0.00 | -104258290.3 | 58.99 | 0.00 | 0.00 |
March | 0.279265E+09 | -164587574.1 | 0.00 | 0.00 | 744.00 | 0.00 | -114677283.6 | 58.99 | 0.00 | 0.00 |
April | 0.253708E+09 | -145412147.4 | 0.00 | 0.00 | 720.00 | 0.00 | -108296020.6 | 58.99 | 0.00 | 0.00 |
May | 0.251118E+09 | -141041760.6 | 0.00 | 0.00 | 744.00 | 0.00 | -110076458.8 | 58.99 | 0.00 | 0.00 |
June | 0.236134E+09 | -129848476.0 | 0.00 | 0.00 | 720.00 | 0.00 | -106285611.9 | 58.99 | 0.00 | 0.00 |
July | 0.234243E+09 | -124874238.2 | 0.00 | 0.00 | 744.00 | 0.00 | -109368793.2 | 58.99 | 0.00 | 0.00 |
August | 0.241212E+09 | -131676892.6 | 0.00 | 0.00 | 744.00 | 0.00 | -109535120.0 | 58.99 | 0.00 | 0.00 |
September | 0.236532E+09 | -130372118.4 | 0.00 | 0.00 | 720.00 | 0.00 | -106159990.8 | 58.99 | 0.00 | 0.00 |
October | 0.253540E+09 | -143338911.0 | 0.00 | 0.00 | 744.00 | 0.00 | -110201096.5 | 59.00 | 0.00 | 0.00 |
November | 0.257714E+09 | -149111242.9 | 0.00 | 0.00 | 720.00 | 0.00 | -108602707.7 | 58.99 | 0.00 | 0.00 |
December | 0.276175E+09 | -161324308.7 | 0.00 | 0.00 | 744.00 | 0.00 | -114850384.0 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.305709E+10 | -0.173790E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.131920E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.234243E+09 | -166353048.4 | 0.00 | 0.00 | 672.00 | 0.00 | -116883460.3 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.283237E+09 | -124874238.2 | 0.00 | 0.00 | 744.00 | 0.00 | -104258290.3 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK5
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.275481E+09 | -157241877.4 | 0.00 | 0.00 | 744.00 | 0.00 | -118238712.2 | 58.99 | 0.00 | 0.00 |
February | 0.247248E+09 | -141797242.1 | 0.00 | 0.00 | 672.00 | 0.00 | -105451234.0 | 58.99 | 0.00 | 0.00 |
March | 0.271620E+09 | -155756087.1 | 0.00 | 0.00 | 744.00 | 0.00 | -115863860.7 | 58.99 | 0.00 | 0.00 |
April | 0.246675E+09 | -137594870.9 | 0.00 | 0.00 | 720.00 | 0.00 | -109080084.7 | 58.99 | 0.00 | 0.00 |
May | 0.244103E+09 | -133388778.3 | 0.00 | 0.00 | 744.00 | 0.00 | -110714278.0 | 58.99 | 0.00 | 0.00 |
June | 0.229791E+09 | -122854269.5 | 0.00 | 0.00 | 720.00 | 0.00 | -106936428.5 | 58.99 | 0.00 | 0.00 |
July | 0.228034E+09 | -118083317.7 | 0.00 | 0.00 | 744.00 | 0.00 | -109950751.8 | 58.99 | 0.00 | 0.00 |
August | 0.234773E+09 | -124599236.6 | 0.00 | 0.00 | 744.00 | 0.00 | -110173816.4 | 58.99 | 0.00 | 0.00 |
September | 0.230000E+09 | -123383400.1 | 0.00 | 0.00 | 720.00 | 0.00 | -106616856.3 | 58.99 | 0.00 | 0.00 |
October | 0.246264E+09 | -135518124.3 | 0.00 | 0.00 | 744.00 | 0.00 | -110746286.2 | 58.99 | 0.00 | 0.00 |
November | 0.250158E+09 | -140820062.8 | 0.00 | 0.00 | 720.00 | 0.00 | -109337578.2 | 58.99 | 0.00 | 0.00 |
December | 0.268516E+09 | -152577739.7 | 0.00 | 0.00 | 744.00 | 0.00 | -115938688.6 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.297266E+10 | -0.164362E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.132905E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.228034E+09 | -157241877.4 | 0.00 | 0.00 | 672.00 | 0.00 | -118238712.2 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.275481E+09 | -118083317.7 | 0.00 | 0.00 | 744.00 | 0.00 | -105451234.0 | 58.99 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK6
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.275624E+09 | -157236411.8 | 0.00 | 0.00 | 744.00 | 0.00 | -118387405.9 | 58.99 | 0.00 | 0.00 |
February | 0.247372E+09 | -141809490.6 | 0.00 | 0.00 | 672.00 | 0.00 | -105562172.7 | 58.99 | 0.00 | 0.00 |
March | 0.271722E+09 | -155744249.2 | 0.00 | 0.00 | 744.00 | 0.00 | -115978222.3 | 58.99 | 0.00 | 0.00 |
April | 0.246741E+09 | -137629200.2 | 0.00 | 0.00 | 720.00 | 0.00 | -109112109.0 | 58.98 | 0.00 | 0.00 |
May | 0.244204E+09 | -133370075.8 | 0.00 | 0.00 | 744.00 | 0.00 | -110833989.8 | 58.99 | 0.00 | 0.00 |
June | 0.229915E+09 | -122873538.8 | 0.00 | 0.00 | 720.00 | 0.00 | -107041698.2 | 58.99 | 0.00 | 0.00 |
July | 0.228165E+09 | -118110380.5 | 0.00 | 0.00 | 744.00 | 0.00 | -110054746.7 | 58.99 | 0.00 | 0.00 |
August | 0.234889E+09 | -124610854.4 | 0.00 | 0.00 | 744.00 | 0.00 | -110277805.7 | 58.99 | 0.00 | 0.00 |
September | 0.230124E+09 | -123387403.5 | 0.00 | 0.00 | 720.00 | 0.00 | -106736307.5 | 58.99 | 0.00 | 0.00 |
October | 0.246370E+09 | -135523753.4 | 0.00 | 0.00 | 744.00 | 0.00 | -110846154.5 | 58.99 | 0.00 | 0.00 |
November | 0.250241E+09 | -140833377.8 | 0.00 | 0.00 | 720.00 | 0.00 | -109407892.8 | 58.99 | 0.00 | 0.00 |
December | 0.268628E+09 | -152579263.5 | 0.00 | 0.00 | 744.00 | 0.00 | -116048840.7 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.297400E+10 | -0.164371E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.133029E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.228165E+09 | -157236411.8 | 0.00 | 0.00 | 672.00 | 0.00 | -118387405.9 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.275624E+09 | -118110380.5 | 0.00 | 0.00 | 744.00 | 0.00 | -105562172.7 | 58.99 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK7
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.275769E+09 | -157234631.2 | 0.00 | 0.00 | 744.00 | 0.00 | -118534532.2 | 59.00 | 0.00 | 0.00 |
February | 0.247512E+09 | -141811650.0 | 0.00 | 0.00 | 672.00 | 0.00 | -105700506.7 | 58.99 | 0.00 | 0.00 |
March | 0.271847E+09 | -155731308.1 | 0.00 | 0.00 | 744.00 | 0.00 | -116115464.9 | 58.99 | 0.00 | 0.00 |
April | 0.246820E+09 | -137581415.1 | 0.00 | 0.00 | 720.00 | 0.00 | -109238330.2 | 59.00 | 0.00 | 0.00 |
May | 0.244244E+09 | -133383323.8 | 0.00 | 0.00 | 744.00 | 0.00 | -110860730.8 | 58.99 | 0.00 | 0.00 |
June | 0.229942E+09 | -122857019.9 | 0.00 | 0.00 | 720.00 | 0.00 | -107084809.5 | 58.99 | 0.00 | 0.00 |
July | 0.228194E+09 | -118079888.2 | 0.00 | 0.00 | 744.00 | 0.00 | -110114015.0 | 58.99 | 0.00 | 0.00 |
August | 0.234933E+09 | -124607434.2 | 0.00 | 0.00 | 744.00 | 0.00 | -110325329.3 | 58.99 | 0.00 | 0.00 |
September | 0.230147E+09 | -123368959.1 | 0.00 | 0.00 | 720.00 | 0.00 | -106777974.7 | 58.99 | 0.00 | 0.00 |
October | 0.246413E+09 | -135507101.7 | 0.00 | 0.00 | 744.00 | 0.00 | -110906050.2 | 58.99 | 0.00 | 0.00 |
November | 0.250309E+09 | -140835101.4 | 0.00 | 0.00 | 720.00 | 0.00 | -109473821.4 | 58.99 | 0.00 | 0.00 |
December | 0.268757E+09 | -152567369.5 | 0.00 | 0.00 | 744.00 | 0.00 | -116189326.9 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.297489E+10 | -0.164357E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.133132E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.228194E+09 | -157234631.2 | 0.00 | 0.00 | 672.00 | 0.00 | -118534532.2 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.275769E+09 | -118079888.2 | 0.00 | 0.00 | 744.00 | 0.00 | -105700506.7 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 307.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 295.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 296.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 347.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 353.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 394.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 390.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 380.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 342.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 330.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 308.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 282.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4027.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 282.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 394.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 HEATING COIL
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.639066E+09 | 57547.23 | 05-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.792186E+09 | 57547.23 | 05-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.528734E+09 | 57547.23 | 11-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.588550E+09 | 57547.23 | 21-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.254854E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.792186E+09 | 57547.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 HEATING COIL
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 54835205.81 | 3691.88 | 05-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.145653E+09 | 16806.37 | 05-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.121460E+09 | 5807.42 | 12-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.119655E+09 | 16156.04 | 21-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.441603E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.145653E+09 | 16806.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3 HEATING COIL
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.190331E+09 | 7364.94 | 05-JAN-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.246592E+09 | 27009.60 | 05-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.179084E+09 | 15403.39 | 12-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.199125E+09 | 7363.81 | 21-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.815133E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.246592E+09 | 27009.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4 HEATING COIL
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.233460E+09 | 7542.65 | 10-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.275663E+09 | 30277.65 | 05-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.197819E+09 | 19477.60 | 12-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.221988E+09 | 8804.32 | 21-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.928931E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.275663E+09 | 30277.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5 HEATING COIL
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.304407E+09 | 10091.86 | 10-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.323400E+09 | 30052.10 | 05-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.231748E+09 | 23326.95 | 12-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.267932E+09 | 10685.79 | 21-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.112749E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.323400E+09 | 30052.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6 HEATING COIL
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.723020E+09 | 53665.15 | 10-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.676976E+09 | 53665.15 | 05-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.474572E+09 | 53665.15 | 11-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.613749E+09 | 53665.15 | 21-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.248832E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.723020E+09 | 53665.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7 HEATING COIL
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.396262E+09 | 27960.84 | 10-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.372882E+09 | 27960.84 | 05-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.260428E+09 | 27960.84 | 11-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.337310E+09 | 27960.84 | 21-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.136688E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.396262E+09 | 27960.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8 HEATING COIL
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.427480E+09 | 27860.33 | 10-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.393766E+09 | 27860.33 | 05-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.274782E+09 | 27860.33 | 11-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.356803E+09 | 27860.33 | 21-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.145283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.427480E+09 | 27860.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9 HEATING COIL
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.521751E+09 | 27934.32 | 05-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.455122E+09 | 27934.32 | 05-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.329295E+09 | 27934.32 | 11-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.416229E+09 | 27934.32 | 21-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.172240E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.521751E+09 | 27934.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10 HEATING COIL
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.772827E+09 | 31564.30 | 05-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.633829E+09 | 31564.30 | 05-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511567E+09 | 31564.30 | 09-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1412889.78 | 1353.99 | 16-NOV-08:65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.603961E+09 | 31564.30 | 20-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.252360E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.772827E+09 | 31564.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.439586E+10 | 0.275181E+10 | 21609.48 | 19-JAN-15:00 | 12457.61 | 0.00 |
February | 0.00 | 0.00 | 0.571307E+10 | 0.357160E+10 | 22473.74 | 24-FEB-14:00 | 14212.60 | 0.00 |
March | 0.00 | 0.00 | 0.841796E+10 | 0.543074E+10 | 23610.87 | 30-MAR-13:00 | 14516.99 | 0.00 |
April | 0.00 | 0.00 | 0.160068E+11 | 0.104391E+11 | 57860.64 | 29-APR-07:03 | 31393.91 | 0.00 |
May | 0.00 | 0.00 | 0.363427E+11 | 0.220124E+11 | 59932.44 | 24-MAY-07:02 | 30143.02 | 0.00 |
June | 0.00 | 0.00 | 0.388334E+11 | 0.233175E+11 | 59247.03 | 19-JUN-07:02 | 31505.42 | 0.00 |
July | 0.00 | 0.00 | 0.442299E+11 | 0.246327E+11 | 60210.24 | 02-JUL-07:02 | 30134.96 | 0.00 |
August | 0.00 | 0.00 | 0.436775E+11 | 0.252055E+11 | 59979.08 | 10-AUG-07:02 | 31356.06 | 0.00 |
September | 0.00 | 0.00 | 0.386950E+11 | 0.216741E+11 | 60743.82 | 05-SEP-07:02 | 28893.99 | 0.00 |
October | 0.00 | 0.00 | 0.328516E+11 | 0.198010E+11 | 60133.62 | 25-OCT-07:02 | 31411.60 | 0.00 |
November | 0.00 | 0.00 | 0.126808E+11 | 0.791691E+10 | 58476.88 | 02-NOV-07:02 | 34932.81 | 0.00 |
December | 0.00 | 0.00 | 0.818360E+10 | 0.507758E+10 | 56788.36 | 15-DEC-08:62 | 32748.13 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.290028E+12 | 0.171831E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.439586E+10 | 0.275181E+10 | 21609.48 | 12457.61 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.442299E+11 | 0.252055E+11 | 60743.82 | 34932.81 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.269158E+10 | 0.173798E+10 | 29602.43 | 01-JAN-18:02 | 15740.34 | 0.00 |
February | 0.00 | 0.00 | 0.355103E+10 | 0.227498E+10 | 29993.13 | 28-FEB-21:50 | 13455.01 | 0.00 |
March | 0.00 | 0.00 | 0.512244E+10 | 0.342112E+10 | 28261.19 | 24-MAR-20:30 | 18723.55 | 0.00 |
April | 0.00 | 0.00 | 0.910047E+10 | 0.614873E+10 | 29516.15 | 15-APR-18:10 | 13734.28 | 0.00 |
May | 0.00 | 0.00 | 0.183901E+11 | 0.115696E+11 | 30433.23 | 22-MAY-07:02 | 19615.20 | 0.00 |
June | 0.00 | 0.00 | 0.194155E+11 | 0.120754E+11 | 29801.88 | 05-JUN-07:02 | 21466.38 | 0.00 |
July | 0.00 | 0.00 | 0.218570E+11 | 0.126568E+11 | 30453.09 | 03-JUL-07:02 | 20216.36 | 0.00 |
August | 0.00 | 0.00 | 0.215406E+11 | 0.128492E+11 | 30647.12 | 16-AUG-07:02 | 19248.55 | 0.00 |
September | 0.00 | 0.00 | 0.192287E+11 | 0.111841E+11 | 30929.68 | 05-SEP-07:02 | 18872.89 | 0.00 |
October | 0.00 | 0.00 | 0.166555E+11 | 0.104192E+11 | 30550.03 | 08-OCT-07:01 | 20305.53 | 0.00 |
November | 0.00 | 0.00 | 0.704262E+10 | 0.455151E+10 | 29911.38 | 29-NOV-21:02 | 14240.70 | 0.00 |
December | 0.00 | 0.00 | 0.449626E+10 | 0.290348E+10 | 29323.51 | 08-DEC-22:44 | 15665.97 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.149092E+12 | 0.917922E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.269158E+10 | 0.173798E+10 | 28261.19 | 13455.01 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.218570E+11 | 0.128492E+11 | 30929.68 | 21466.38 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3 COOLING COIL
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.200232E+10 | 0.127987E+10 | 12417.18 | 20-JAN-07:03 | 5480.55 | 0.00 |
February | 0.00 | 0.00 | 0.275951E+10 | 0.174614E+10 | 13910.97 | 28-FEB-07:03 | 6661.95 | 0.00 |
March | 0.00 | 0.00 | 0.387016E+10 | 0.253134E+10 | 18185.93 | 07-MAR-07:03 | 10099.68 | 0.00 |
April | 0.00 | 0.00 | 0.689545E+10 | 0.459164E+10 | 31390.12 | 29-APR-06:03 | 17144.52 | 0.00 |
May | 0.00 | 0.00 | 0.150759E+11 | 0.921194E+10 | 32186.06 | 21-MAY-07:02 | 15043.87 | 0.00 |
June | 0.00 | 0.00 | 0.161525E+11 | 0.973434E+10 | 32683.85 | 19-JUN-06:02 | 13740.36 | 0.00 |
July | 0.00 | 0.00 | 0.179543E+11 | 0.999774E+10 | 32715.06 | 03-JUL-06:01 | 14105.66 | 0.00 |
August | 0.00 | 0.00 | 0.180661E+11 | 0.103930E+11 | 32704.70 | 14-AUG-06:01 | 13649.50 | 0.00 |
September | 0.00 | 0.00 | 0.156732E+11 | 0.873272E+10 | 32751.26 | 05-SEP-06:02 | 14155.72 | 0.00 |
October | 0.00 | 0.00 | 0.133715E+11 | 0.808264E+10 | 32637.14 | 08-OCT-07:01 | 14772.87 | 0.00 |
November | 0.00 | 0.00 | 0.554157E+10 | 0.352074E+10 | 31321.69 | 02-NOV-06:02 | 17669.08 | 0.00 |
December | 0.00 | 0.00 | 0.357472E+10 | 0.224676E+10 | 31150.20 | 15-DEC-07:03 | 17871.23 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.120937E+12 | 0.720689E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.200232E+10 | 0.127987E+10 | 12417.18 | 5480.55 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.180661E+11 | 0.103930E+11 | 32751.26 | 17871.23 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4 COOLING COIL
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.192531E+10 | 0.122658E+10 | 11761.85 | 20-JAN-07:03 | 5187.45 | 0.00 |
February | 0.00 | 0.00 | 0.269303E+10 | 0.170042E+10 | 13163.55 | 28-FEB-07:03 | 6299.39 | 0.00 |
March | 0.00 | 0.00 | 0.380490E+10 | 0.248244E+10 | 17262.15 | 07-MAR-07:03 | 9534.34 | 0.00 |
April | 0.00 | 0.00 | 0.685023E+10 | 0.455745E+10 | 31482.16 | 29-APR-06:03 | 17190.72 | 0.00 |
May | 0.00 | 0.00 | 0.151013E+11 | 0.923069E+10 | 32279.47 | 21-MAY-07:02 | 15095.04 | 0.00 |
June | 0.00 | 0.00 | 0.161935E+11 | 0.976462E+10 | 32784.09 | 19-JUN-06:02 | 13829.08 | 0.00 |
July | 0.00 | 0.00 | 0.180196E+11 | 0.100445E+11 | 32808.55 | 03-JUL-06:01 | 14221.33 | 0.00 |
August | 0.00 | 0.00 | 0.181187E+11 | 0.104313E+11 | 32798.16 | 14-AUG-06:01 | 13765.16 | 0.00 |
September | 0.00 | 0.00 | 0.157199E+11 | 0.876610E+10 | 32844.86 | 05-SEP-06:02 | 14280.64 | 0.00 |
October | 0.00 | 0.00 | 0.133982E+11 | 0.810214E+10 | 32739.08 | 08-OCT-07:01 | 14874.59 | 0.00 |
November | 0.00 | 0.00 | 0.548976E+10 | 0.348188E+10 | 31415.42 | 03-NOV-06:02 | 17796.52 | 0.00 |
December | 0.00 | 0.00 | 0.353073E+10 | 0.221441E+10 | 31241.33 | 15-DEC-07:03 | 17912.27 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.120845E+12 | 0.720025E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.192531E+10 | 0.122658E+10 | 11761.85 | 5187.45 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.181187E+11 | 0.104313E+11 | 32844.86 | 17912.27 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5 COOLING COIL
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.180236E+10 | 0.114267E+10 | 10791.97 | 19-JAN-14:00 | 6200.66 | 0.00 |
February | 0.00 | 0.00 | 0.253990E+10 | 0.159537E+10 | 11221.64 | 24-FEB-13:50 | 7131.07 | 0.00 |
March | 0.00 | 0.00 | 0.362376E+10 | 0.235048E+10 | 14383.64 | 07-MAR-07:03 | 7825.89 | 0.00 |
April | 0.00 | 0.00 | 0.659031E+10 | 0.437144E+10 | 31203.17 | 29-APR-06:03 | 16866.05 | 0.00 |
May | 0.00 | 0.00 | 0.148388E+11 | 0.904149E+10 | 31981.74 | 21-MAY-07:02 | 14812.25 | 0.00 |
June | 0.00 | 0.00 | 0.159456E+11 | 0.958363E+10 | 32488.10 | 19-JUN-06:02 | 13579.87 | 0.00 |
July | 0.00 | 0.00 | 0.177727E+11 | 0.987086E+10 | 32525.79 | 03-JUL-06:01 | 13987.89 | 0.00 |
August | 0.00 | 0.00 | 0.178685E+11 | 0.102518E+11 | 32515.48 | 14-AUG-06:01 | 13527.76 | 0.00 |
September | 0.00 | 0.00 | 0.154640E+11 | 0.858619E+10 | 32561.78 | 05-SEP-06:02 | 14081.31 | 0.00 |
October | 0.00 | 0.00 | 0.131801E+11 | 0.794199E+10 | 32444.82 | 08-OCT-07:01 | 14639.37 | 0.00 |
November | 0.00 | 0.00 | 0.529466E+10 | 0.333892E+10 | 31142.55 | 03-NOV-06:02 | 17457.91 | 0.00 |
December | 0.00 | 0.00 | 0.339648E+10 | 0.211763E+10 | 30964.25 | 15-DEC-07:03 | 17590.47 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.118317E+12 | 0.701925E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.180236E+10 | 0.114267E+10 | 10791.97 | 6200.66 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.178685E+11 | 0.102518E+11 | 32561.78 | 17590.47 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6 COOLING COIL
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.288849E+10 | 0.179312E+10 | 19784.24 | 19-JAN-14:00 | 11045.15 | 0.00 |
February | 0.00 | 0.00 | 0.425662E+10 | 0.261238E+10 | 20579.76 | 24-FEB-13:40 | 12772.54 | 0.00 |
March | 0.00 | 0.00 | 0.612139E+10 | 0.388092E+10 | 22897.53 | 30-MAR-13:00 | 13818.19 | 0.00 |
April | 0.00 | 0.00 | 0.114975E+11 | 0.749560E+10 | 53394.92 | 29-APR-07:03 | 30185.43 | 0.00 |
May | 0.00 | 0.00 | 0.263224E+11 | 0.158070E+11 | 56106.21 | 21-MAY-08:62 | 25561.26 | 0.00 |
June | 0.00 | 0.00 | 0.284936E+11 | 0.168907E+11 | 56824.25 | 19-JUN-07:02 | 23508.92 | 0.00 |
July | 0.00 | 0.00 | 0.316004E+11 | 0.172704E+11 | 57025.28 | 03-JUL-07:02 | 24243.41 | 0.00 |
August | 0.00 | 0.00 | 0.319647E+11 | 0.180817E+11 | 56943.02 | 14-AUG-07:02 | 23529.78 | 0.00 |
September | 0.00 | 0.00 | 0.273697E+11 | 0.148999E+11 | 57029.75 | 05-SEP-07:02 | 24462.72 | 0.00 |
October | 0.00 | 0.00 | 0.235917E+11 | 0.139926E+11 | 56828.91 | 08-OCT-08:62 | 25194.25 | 0.00 |
November | 0.00 | 0.00 | 0.924491E+10 | 0.570021E+10 | 53809.00 | 02-NOV-07:02 | 31835.11 | 0.00 |
December | 0.00 | 0.00 | 0.588801E+10 | 0.359490E+10 | 52439.36 | 11-DEC-08:62 | 22738.91 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.209239E+12 | 0.122019E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.288849E+10 | 0.179312E+10 | 19784.24 | 11045.15 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.319647E+11 | 0.180817E+11 | 57029.75 | 31835.11 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7 COOLING COIL
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.146789E+10 | 0.911697E+09 | 10210.93 | 19-JAN-14:00 | 5697.83 | 0.00 |
February | 0.00 | 0.00 | 0.216931E+10 | 0.133144E+10 | 10667.87 | 24-FEB-13:50 | 6621.41 | 0.00 |
March | 0.00 | 0.00 | 0.312864E+10 | 0.198094E+10 | 11967.49 | 30-MAR-13:00 | 7213.43 | 0.00 |
April | 0.00 | 0.00 | 0.592755E+10 | 0.386721E+10 | 25444.43 | 29-APR-07:03 | 14367.17 | 0.00 |
May | 0.00 | 0.00 | 0.136708E+11 | 0.821845E+10 | 29452.61 | 21-MAY-08:62 | 13376.80 | 0.00 |
June | 0.00 | 0.00 | 0.147997E+11 | 0.878131E+10 | 29838.03 | 19-JUN-07:02 | 12266.19 | 0.00 |
July | 0.00 | 0.00 | 0.164154E+11 | 0.898284E+10 | 29927.94 | 03-JUL-07:02 | 12653.56 | 0.00 |
August | 0.00 | 0.00 | 0.165950E+11 | 0.939789E+10 | 29884.76 | 14-AUG-07:02 | 12223.31 | 0.00 |
September | 0.00 | 0.00 | 0.142031E+11 | 0.774330E+10 | 29939.29 | 05-SEP-07:02 | 12793.34 | 0.00 |
October | 0.00 | 0.00 | 0.122322E+11 | 0.726120E+10 | 29832.23 | 08-OCT-08:62 | 13165.90 | 0.00 |
November | 0.00 | 0.00 | 0.474904E+10 | 0.292598E+10 | 28225.27 | 02-NOV-07:02 | 16728.79 | 0.00 |
December | 0.00 | 0.00 | 0.302982E+10 | 0.184958E+10 | 25101.35 | 11-DEC-08:62 | 10854.59 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.108388E+12 | 0.632518E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.146789E+10 | 0.911697E+09 | 10210.93 | 5697.83 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.165950E+11 | 0.939789E+10 | 29939.29 | 16728.79 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8 COOLING COIL
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.143678E+10 | 0.891569E+09 | 10119.22 | 19-JAN-14:00 | 5637.72 | 0.00 |
February | 0.00 | 0.00 | 0.212560E+10 | 0.130291E+10 | 10576.18 | 24-FEB-13:50 | 6555.82 | 0.00 |
March | 0.00 | 0.00 | 0.307363E+10 | 0.194146E+10 | 11901.28 | 30-MAR-13:00 | 7166.78 | 0.00 |
April | 0.00 | 0.00 | 0.585608E+10 | 0.381638E+10 | 24707.82 | 29-APR-07:03 | 13895.47 | 0.00 |
May | 0.00 | 0.00 | 0.135963E+11 | 0.816625E+10 | 29324.46 | 21-MAY-08:62 | 13287.46 | 0.00 |
June | 0.00 | 0.00 | 0.147310E+11 | 0.873231E+10 | 29712.31 | 19-JUN-07:02 | 12183.88 | 0.00 |
July | 0.00 | 0.00 | 0.163502E+11 | 0.893807E+10 | 29801.84 | 03-JUL-07:02 | 12580.53 | 0.00 |
August | 0.00 | 0.00 | 0.165314E+11 | 0.935332E+10 | 29758.85 | 14-AUG-07:03 | 12074.20 | 0.00 |
September | 0.00 | 0.00 | 0.141403E+11 | 0.770066E+10 | 29813.14 | 05-SEP-07:02 | 12725.44 | 0.00 |
October | 0.00 | 0.00 | 0.121673E+11 | 0.721434E+10 | 29704.71 | 08-OCT-08:62 | 13090.18 | 0.00 |
November | 0.00 | 0.00 | 0.469214E+10 | 0.288472E+10 | 28109.81 | 02-NOV-07:02 | 16613.36 | 0.00 |
December | 0.00 | 0.00 | 0.299045E+10 | 0.182166E+10 | 23979.77 | 11-DEC-08:62 | 10347.92 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.107691E+12 | 0.627637E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.143678E+10 | 0.891569E+09 | 10119.22 | 5637.72 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.165314E+11 | 0.935332E+10 | 29813.14 | 16613.36 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9 COOLING COIL
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.137337E+10 | 0.850379E+09 | 9997.62 | 19-JAN-14:00 | 5559.08 | 0.00 |
February | 0.00 | 0.00 | 0.202311E+10 | 0.123702E+10 | 10417.85 | 24-FEB-13:50 | 6442.58 | 0.00 |
March | 0.00 | 0.00 | 0.295895E+10 | 0.186013E+10 | 11789.04 | 30-MAR-13:00 | 7087.33 | 0.00 |
April | 0.00 | 0.00 | 0.570089E+10 | 0.370750E+10 | 21836.74 | 29-APR-07:03 | 12127.79 | 0.00 |
May | 0.00 | 0.00 | 0.135136E+11 | 0.811024E+10 | 29399.17 | 21-MAY-08:62 | 13219.77 | 0.00 |
June | 0.00 | 0.00 | 0.146893E+11 | 0.870302E+10 | 29799.51 | 19-JUN-07:02 | 12116.78 | 0.00 |
July | 0.00 | 0.00 | 0.163465E+11 | 0.893725E+10 | 29894.68 | 03-JUL-07:02 | 12575.45 | 0.00 |
August | 0.00 | 0.00 | 0.165548E+11 | 0.937041E+10 | 29851.55 | 14-AUG-07:02 | 12158.45 | 0.00 |
September | 0.00 | 0.00 | 0.141335E+11 | 0.769740E+10 | 29906.01 | 05-SEP-07:02 | 12745.09 | 0.00 |
October | 0.00 | 0.00 | 0.121326E+11 | 0.718974E+10 | 29791.87 | 08-OCT-08:62 | 13104.89 | 0.00 |
November | 0.00 | 0.00 | 0.458974E+10 | 0.281015E+10 | 28194.22 | 02-NOV-07:02 | 16560.53 | 0.00 |
December | 0.00 | 0.00 | 0.291528E+10 | 0.176962E+10 | 21549.62 | 11-DEC-08:62 | 12615.41 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.106932E+12 | 0.622429E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.137337E+10 | 0.850379E+09 | 9997.62 | 5559.08 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.165548E+11 | 0.937041E+10 | 29906.01 | 16560.53 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10 COOLING COIL
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.144123E+10 | 0.902209E+09 | 10933.32 | 19-JAN-14:00 | 6221.29 | 0.00 |
February | 0.00 | 0.00 | 0.209904E+10 | 0.129702E+10 | 11290.61 | 24-FEB-13:10 | 7016.42 | 0.00 |
March | 0.00 | 0.00 | 0.315904E+10 | 0.200688E+10 | 12671.80 | 30-MAR-13:00 | 7717.11 | 0.00 |
April | 0.00 | 0.00 | 0.602264E+10 | 0.396252E+10 | 16971.50 | 28-APR-16:10 | 10004.35 | 0.00 |
May | 0.00 | 0.00 | 0.146736E+11 | 0.892105E+10 | 33839.60 | 21-MAY-08:62 | 14679.36 | 0.00 |
June | 0.00 | 0.00 | 0.161057E+11 | 0.970067E+10 | 34198.68 | 19-JUN-07:02 | 13462.44 | 0.00 |
July | 0.00 | 0.00 | 0.180377E+11 | 0.100890E+11 | 34301.73 | 03-JUL-07:02 | 13854.28 | 0.00 |
August | 0.00 | 0.00 | 0.184220E+11 | 0.106473E+11 | 34253.73 | 07-AUG-07:02 | 14649.68 | 0.00 |
September | 0.00 | 0.00 | 0.156262E+11 | 0.870396E+10 | 34314.74 | 05-SEP-07:02 | 14272.73 | 0.00 |
October | 0.00 | 0.00 | 0.133749E+11 | 0.806108E+10 | 34270.63 | 08-OCT-08:62 | 14916.56 | 0.00 |
November | 0.00 | 0.00 | 0.489315E+10 | 0.303273E+10 | 32726.16 | 02-NOV-07:02 | 17848.95 | 0.00 |
December | 0.00 | 0.00 | 0.303936E+10 | 0.186125E+10 | 15216.20 | 15-DEC-08:62 | 7952.94 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.116895E+12 | 0.691857E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.144123E+10 | 0.902209E+09 | 10933.32 | 6221.29 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.184220E+11 | 0.106473E+11 | 34314.74 | 17848.95 | 0.00 |
Report: FanReportMonthly
For: PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.169283E+10 | 0.36 | 2311.27 | 05-JAN-08:61 | 0.88 |
February | 0.153676E+10 | 0.36 | 2311.27 | 05-FEB-08:61 | 0.88 |
March | 0.169683E+10 | 0.36 | 2311.27 | 11-MAR-08:61 | 0.88 |
April | 0.162663E+10 | 0.36 | 2255.55 | 29-APR-07:03 | 0.85 |
May | 0.170535E+10 | 0.36 | 2311.27 | 03-MAY-07:03 | 0.87 |
June | 0.169638E+10 | 0.37 | 2311.27 | 02-JUN-07:03 | 0.86 |
July | 0.181859E+10 | 0.37 | 2311.27 | 01-JUL-07:02 | 0.86 |
August | 0.181847E+10 | 0.37 | 2311.27 | 01-AUG-07:02 | 0.86 |
September | 0.172024E+10 | 0.37 | 2311.27 | 01-SEP-07:02 | 0.86 |
October | 0.175040E+10 | 0.36 | 2311.27 | 03-OCT-07:03 | 0.87 |
November | 0.162560E+10 | 0.36 | 2311.27 | 01-NOV-07:03 | 0.87 |
December | 0.169915E+10 | 0.36 | 2311.27 | 21-DEC-08:61 | 0.88 |
Annual Sum or Average | 0.203872E+11 | 0.36 | |||
Minimum of Months | 0.153676E+10 | 0.36 | 2255.55 | 0.85 | |
Maximum of Months | 0.181859E+10 | 0.37 | 2311.27 | 0.88 |
Report: FanReportMonthly
For: PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.766590E+09 | 0.35 | 597.63 | 05-JAN-08:61 | 0.61 |
February | 0.729710E+09 | 0.36 | 927.10 | 05-FEB-08:61 | 0.79 |
March | 0.806818E+09 | 0.36 | 650.78 | 12-MAR-07:02 | 0.64 |
April | 0.783182E+09 | 0.37 | 1165.57 | 30-APR-07:03 | 0.87 |
May | 0.807354E+09 | 0.37 | 1262.21 | 04-MAY-07:02 | 0.90 |
June | 0.810598E+09 | 0.38 | 1262.21 | 03-JUN-07:02 | 0.90 |
July | 0.878511E+09 | 0.38 | 1262.21 | 01-JUL-07:02 | 0.90 |
August | 0.876314E+09 | 0.38 | 1262.21 | 01-AUG-07:02 | 0.90 |
September | 0.819364E+09 | 0.38 | 1262.21 | 01-SEP-07:02 | 0.90 |
October | 0.836891E+09 | 0.38 | 1262.21 | 04-OCT-07:02 | 0.90 |
November | 0.816673E+09 | 0.37 | 1262.21 | 02-NOV-07:02 | 0.90 |
December | 0.815546E+09 | 0.36 | 1023.35 | 11-DEC-08:62 | 0.82 |
Annual Sum or Average | 0.974755E+10 | 0.37 | |||
Minimum of Months | 0.729710E+09 | 0.35 | 597.63 | 0.61 | |
Maximum of Months | 0.878511E+09 | 0.38 | 1262.21 | 0.90 |
Report: FanReportMonthly
For: PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.737069E+09 | 0.30 | 691.08 | 05-JAN-08:03 | 0.67 |
February | 0.669261E+09 | 0.30 | 1184.75 | 05-FEB-08:61 | 0.89 |
March | 0.751394E+09 | 0.30 | 893.09 | 12-MAR-07:02 | 0.77 |
April | 0.711732E+09 | 0.30 | 1265.00 | 29-APR-06:03 | 0.89 |
May | 0.751655E+09 | 0.30 | 1265.00 | 01-MAY-06:03 | 0.89 |
June | 0.752956E+09 | 0.31 | 1265.00 | 01-JUN-06:03 | 0.90 |
July | 0.795849E+09 | 0.31 | 1265.00 | 01-JUL-06:02 | 0.89 |
August | 0.809243E+09 | 0.31 | 1265.00 | 01-AUG-06:02 | 0.89 |
September | 0.750173E+09 | 0.30 | 1265.00 | 01-SEP-06:02 | 0.89 |
October | 0.764927E+09 | 0.30 | 1265.00 | 03-OCT-06:02 | 0.90 |
November | 0.712416E+09 | 0.30 | 1265.00 | 01-NOV-06:03 | 0.89 |
December | 0.734327E+09 | 0.30 | 1265.00 | 11-DEC-07:03 | 0.89 |
Annual Sum or Average | 0.894100E+10 | 0.30 | |||
Minimum of Months | 0.669261E+09 | 0.30 | 691.08 | 0.67 | |
Maximum of Months | 0.809243E+09 | 0.31 | 1265.00 | 0.90 |
Report: FanReportMonthly
For: PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.740247E+09 | 0.30 | 697.07 | 10-JAN-07:03 | 0.67 |
February | 0.671889E+09 | 0.30 | 1268.62 | 05-FEB-08:61 | 0.91 |
March | 0.753986E+09 | 0.30 | 997.11 | 12-MAR-07:02 | 0.81 |
April | 0.713688E+09 | 0.30 | 1268.62 | 29-APR-06:03 | 0.89 |
May | 0.753360E+09 | 0.30 | 1268.62 | 01-MAY-06:03 | 0.89 |
June | 0.754695E+09 | 0.31 | 1268.62 | 01-JUN-06:03 | 0.90 |
July | 0.798034E+09 | 0.31 | 1268.62 | 01-JUL-06:02 | 0.89 |
August | 0.811152E+09 | 0.31 | 1268.62 | 01-AUG-06:02 | 0.89 |
September | 0.752201E+09 | 0.30 | 1268.62 | 01-SEP-06:02 | 0.89 |
October | 0.766846E+09 | 0.30 | 1268.62 | 03-OCT-06:02 | 0.90 |
November | 0.714349E+09 | 0.30 | 1268.62 | 01-NOV-06:03 | 0.89 |
December | 0.736977E+09 | 0.30 | 1268.62 | 11-DEC-07:03 | 0.89 |
Annual Sum or Average | 0.896742E+10 | 0.30 | |||
Minimum of Months | 0.671889E+09 | 0.30 | 697.07 | 0.67 | |
Maximum of Months | 0.811152E+09 | 0.31 | 1268.62 | 0.91 |
Report: FanReportMonthly
For: PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.735692E+09 | 0.30 | 756.48 | 10-JAN-07:03 | 0.71 |
February | 0.667349E+09 | 0.30 | 1257.69 | 05-FEB-08:61 | 0.91 |
March | 0.748357E+09 | 0.30 | 1088.82 | 12-MAR-07:02 | 0.85 |
April | 0.707345E+09 | 0.30 | 1257.69 | 29-APR-06:03 | 0.89 |
May | 0.746112E+09 | 0.30 | 1257.69 | 02-MAY-06:03 | 0.89 |
June | 0.746987E+09 | 0.31 | 1257.69 | 02-JUN-06:02 | 0.89 |
July | 0.790127E+09 | 0.31 | 1257.69 | 01-JUL-06:02 | 0.89 |
August | 0.802773E+09 | 0.31 | 1257.69 | 01-AUG-06:02 | 0.89 |
September | 0.745002E+09 | 0.30 | 1257.69 | 01-SEP-06:02 | 0.89 |
October | 0.759467E+09 | 0.30 | 1257.69 | 03-OCT-06:02 | 0.90 |
November | 0.708007E+09 | 0.30 | 1257.69 | 01-NOV-06:03 | 0.89 |
December | 0.731735E+09 | 0.30 | 1257.69 | 15-DEC-07:03 | 0.89 |
Annual Sum or Average | 0.888895E+10 | 0.30 | |||
Minimum of Months | 0.667349E+09 | 0.30 | 756.48 | 0.71 | |
Maximum of Months | 0.802773E+09 | 0.31 | 1257.69 | 0.91 |
Report: FanReportMonthly
For: PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.115483E+10 | 0.27 | 2129.41 | 10-JAN-08:61 | 0.88 |
February | 0.104641E+10 | 0.27 | 2129.41 | 05-FEB-09:01 | 0.88 |
March | 0.117344E+10 | 0.27 | 2129.41 | 11-MAR-08:61 | 0.88 |
April | 0.110751E+10 | 0.26 | 2099.67 | 29-APR-07:03 | 0.86 |
May | 0.118770E+10 | 0.27 | 2129.41 | 01-MAY-07:03 | 0.86 |
June | 0.120319E+10 | 0.28 | 2129.41 | 02-JUN-07:03 | 0.86 |
July | 0.128604E+10 | 0.28 | 2129.41 | 01-JUL-07:02 | 0.86 |
August | 0.130976E+10 | 0.29 | 2129.41 | 01-AUG-07:02 | 0.86 |
September | 0.119965E+10 | 0.27 | 2129.41 | 01-SEP-07:02 | 0.87 |
October | 0.121837E+10 | 0.27 | 2129.41 | 03-OCT-07:03 | 0.87 |
November | 0.110946E+10 | 0.26 | 2129.41 | 02-NOV-07:02 | 0.86 |
December | 0.114690E+10 | 0.26 | 2129.41 | 21-DEC-08:61 | 0.88 |
Annual Sum or Average | 0.141433E+11 | 0.27 | |||
Minimum of Months | 0.104641E+10 | 0.26 | 2099.67 | 0.86 | |
Maximum of Months | 0.130976E+10 | 0.29 | 2129.41 | 0.88 |
Report: FanReportMonthly
For: PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.627582E+09 | 0.28 | 1156.31 | 10-JAN-08:61 | 0.91 |
February | 0.568723E+09 | 0.28 | 1156.31 | 05-FEB-09:01 | 0.91 |
March | 0.637532E+09 | 0.28 | 1156.31 | 11-MAR-08:61 | 0.91 |
April | 0.601283E+09 | 0.27 | 1015.25 | 29-APR-07:03 | 0.84 |
May | 0.644812E+09 | 0.28 | 1156.31 | 04-MAY-07:02 | 0.90 |
June | 0.652762E+09 | 0.29 | 1156.31 | 02-JUN-07:03 | 0.89 |
July | 0.697527E+09 | 0.29 | 1156.31 | 01-JUL-07:02 | 0.89 |
August | 0.710186E+09 | 0.30 | 1156.31 | 01-AUG-07:02 | 0.89 |
September | 0.650353E+09 | 0.28 | 1156.31 | 01-SEP-07:02 | 0.90 |
October | 0.660211E+09 | 0.28 | 1156.31 | 04-OCT-07:02 | 0.90 |
November | 0.602187E+09 | 0.27 | 1156.31 | 02-NOV-07:02 | 0.89 |
December | 0.623126E+09 | 0.27 | 1156.31 | 21-DEC-08:61 | 0.91 |
Annual Sum or Average | 0.767628E+10 | 0.28 | |||
Minimum of Months | 0.568723E+09 | 0.27 | 1015.25 | 0.84 | |
Maximum of Months | 0.710186E+09 | 0.30 | 1156.31 | 0.91 |
Report: FanReportMonthly
For: PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.625747E+09 | 0.28 | 1151.44 | 10-JAN-08:61 | 0.91 |
February | 0.566878E+09 | 0.28 | 1151.44 | 05-FEB-09:01 | 0.91 |
March | 0.635225E+09 | 0.28 | 1151.44 | 11-MAR-08:61 | 0.91 |
April | 0.598725E+09 | 0.27 | 980.16 | 29-APR-07:03 | 0.83 |
May | 0.642098E+09 | 0.28 | 1151.44 | 04-MAY-07:02 | 0.90 |
June | 0.650144E+09 | 0.29 | 1151.44 | 02-JUN-07:03 | 0.89 |
July | 0.694962E+09 | 0.29 | 1151.44 | 01-JUL-07:02 | 0.89 |
August | 0.707625E+09 | 0.30 | 1151.44 | 01-AUG-07:02 | 0.89 |
September | 0.647880E+09 | 0.28 | 1151.44 | 01-SEP-07:02 | 0.90 |
October | 0.657545E+09 | 0.28 | 1151.44 | 04-OCT-07:02 | 0.90 |
November | 0.599603E+09 | 0.27 | 1151.44 | 02-NOV-07:02 | 0.89 |
December | 0.620982E+09 | 0.27 | 1151.44 | 21-DEC-08:61 | 0.91 |
Annual Sum or Average | 0.764741E+10 | 0.28 | |||
Minimum of Months | 0.566878E+09 | 0.27 | 980.16 | 0.83 | |
Maximum of Months | 0.707625E+09 | 0.30 | 1151.44 | 0.91 |
Report: FanReportMonthly
For: PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.630007E+09 | 0.28 | 1155.03 | 05-JAN-08:61 | 0.91 |
February | 0.570140E+09 | 0.28 | 1155.03 | 05-FEB-09:01 | 0.91 |
March | 0.638538E+09 | 0.28 | 1155.03 | 11-MAR-08:61 | 0.91 |
April | 0.600349E+09 | 0.27 | 839.84 | 29-APR-07:03 | 0.77 |
May | 0.642798E+09 | 0.28 | 1155.03 | 04-MAY-07:02 | 0.90 |
June | 0.650949E+09 | 0.29 | 1155.03 | 03-JUN-07:02 | 0.89 |
July | 0.696369E+09 | 0.29 | 1155.03 | 01-JUL-07:02 | 0.89 |
August | 0.709479E+09 | 0.30 | 1155.03 | 01-AUG-07:02 | 0.89 |
September | 0.649587E+09 | 0.28 | 1155.03 | 01-SEP-07:02 | 0.90 |
October | 0.658977E+09 | 0.28 | 1155.03 | 04-OCT-07:02 | 0.90 |
November | 0.601145E+09 | 0.27 | 1155.03 | 02-NOV-07:02 | 0.89 |
December | 0.624254E+09 | 0.27 | 1155.03 | 21-DEC-08:61 | 0.91 |
Annual Sum or Average | 0.767259E+10 | 0.28 | |||
Minimum of Months | 0.570140E+09 | 0.27 | 839.84 | 0.77 | |
Maximum of Months | 0.709479E+09 | 0.30 | 1155.03 | 0.91 |
Report: FanReportMonthly
For: PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.730613E+09 | 0.28 | 1330.97 | 05-JAN-08:61 | 0.91 |
February | 0.660015E+09 | 0.28 | 1330.97 | 05-FEB-09:01 | 0.91 |
March | 0.739335E+09 | 0.28 | 1330.97 | 09-MAR-08:62 | 0.91 |
April | 0.690266E+09 | 0.27 | 589.82 | 28-APR-16:10 | 0.58 |
May | 0.728924E+09 | 0.28 | 1330.97 | 06-MAY-07:02 | 0.89 |
June | 0.734146E+09 | 0.28 | 1330.97 | 03-JUN-07:02 | 0.89 |
July | 0.785603E+09 | 0.29 | 1330.97 | 01-JUL-07:02 | 0.89 |
August | 0.801147E+09 | 0.29 | 1330.97 | 01-AUG-07:02 | 0.89 |
September | 0.737903E+09 | 0.28 | 1330.97 | 01-SEP-07:02 | 0.90 |
October | 0.747702E+09 | 0.28 | 1330.97 | 04-OCT-07:02 | 0.89 |
November | 0.691122E+09 | 0.27 | 1330.97 | 02-NOV-07:02 | 0.89 |
December | 0.722507E+09 | 0.27 | 1330.97 | 20-DEC-08:61 | 0.91 |
Annual Sum or Average | 0.876928E+10 | 0.28 | |||
Minimum of Months | 0.660015E+09 | 0.27 | 589.82 | 0.58 | |
Maximum of Months | 0.801147E+09 | 0.29 | 1330.97 | 0.91 |
Report: ZoneTemperatureOscillationReportMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.281473E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.298772E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.385534E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.572230E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.107747E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.113231E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.125783E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.124674E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.110759E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.976366E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.478315E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.374485E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.918911E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.281473E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.125783E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.143824E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.161401E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.209175E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.306856E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.535817E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.559425E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.617825E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.610434E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.543968E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.486820E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.254092E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.192239E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.462187E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.143824E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.617825E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_3:3
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.124066E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.135911E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.172610E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.244842E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.444520E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.468466E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.508543E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.513728E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.446223E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.396759E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.207168E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.161277E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.382411E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.124066E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.513728E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_4:4
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.122559E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.134636E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.171363E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.244043E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.445409E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.469695E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.510346E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.515217E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.447578E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.397640E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.206150E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.160506E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.382514E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.122559E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.515217E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_5:5
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.119151E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.130525E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.166472E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.237121E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.438527E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.463005E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.503684E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.508415E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.440931E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.391763E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.200811E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.156780E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.375718E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.119151E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.508415E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_6:6
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.189637E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.213047E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.274247E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.404831E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.770794E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.821591E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.891653E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.905905E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.774634E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.693574E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.340304E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.261042E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.654126E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.189637E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.905905E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_7:7
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.998455E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.111251E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.142679E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.209348E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.398027E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.424127E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.460351E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.467414E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.399621E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.357900E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.176124E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.136406E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.338309E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.998455E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.467414E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_8:8
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.989093E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.110015E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.141109E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.207340E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.395917E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.422137E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.458460E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.465555E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.397840E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.356046E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.174471E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.135247E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.336305E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.989093E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.465555E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_9:9
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.978188E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.107918E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.138732E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.203899E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.394280E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.421408E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.458680E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.466412E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.398007E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.355500E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.172209E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.133870E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.334873E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.978188E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.466412E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_10:10
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.109930E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.119432E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.154646E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.222692E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.435250E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.467916E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.512043E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.523683E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.445335E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.396521E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.189829E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.147841E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.372512E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.109930E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.523683E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.169283E+10 | 0.439586E+10 | 0.639066E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.153676E+10 | 0.571307E+10 | 0.792186E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.169683E+10 | 0.841796E+10 | 0.528734E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.162663E+10 | 0.160068E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.170535E+10 | 0.363427E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.169638E+10 | 0.388334E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.181859E+10 | 0.442299E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.181847E+10 | 0.436775E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.172024E+10 | 0.386950E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.175040E+10 | 0.328516E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.162560E+10 | 0.126808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.169915E+10 | 0.818360E+10 | 0.588550E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.203872E+11 | 0.290028E+12 | 0.254854E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.153676E+10 | 0.439586E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.181859E+10 | 0.442299E+11 | 0.792186E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.766590E+09 | 0.268340E+10 | 54835205.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.729710E+09 | 0.354282E+10 | 0.145653E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.806818E+09 | 0.510442E+10 | 0.121460E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.783182E+09 | 0.904293E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.807354E+09 | 0.183901E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.810598E+09 | 0.194155E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.878511E+09 | 0.218570E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.876314E+09 | 0.215406E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.819364E+09 | 0.192287E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.836891E+09 | 0.166293E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.816673E+09 | 0.699238E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.815546E+09 | 0.449506E+10 | 0.119655E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.974755E+10 | 0.148922E+12 | 0.441603E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.729710E+09 | 0.268340E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.878511E+09 | 0.218570E+11 | 0.145653E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_3:3
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.737069E+09 | 0.200232E+10 | 0.190331E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.669261E+09 | 0.275951E+10 | 0.246592E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.751394E+09 | 0.387016E+10 | 0.179084E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.711732E+09 | 0.689545E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.751655E+09 | 0.150759E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.752956E+09 | 0.161525E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.795849E+09 | 0.179543E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.809243E+09 | 0.180661E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.750173E+09 | 0.156732E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.764927E+09 | 0.133715E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.712416E+09 | 0.554157E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.734327E+09 | 0.357472E+10 | 0.199125E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.894100E+10 | 0.120937E+12 | 0.815133E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.669261E+09 | 0.200232E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.809243E+09 | 0.180661E+11 | 0.246592E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_4:4
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.740247E+09 | 0.192531E+10 | 0.233460E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.671889E+09 | 0.269303E+10 | 0.275663E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.753986E+09 | 0.380490E+10 | 0.197819E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.713688E+09 | 0.685023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.753360E+09 | 0.151013E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.754695E+09 | 0.161935E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.798034E+09 | 0.180196E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.811152E+09 | 0.181187E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.752201E+09 | 0.157199E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.766846E+09 | 0.133982E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.714349E+09 | 0.548976E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.736977E+09 | 0.353073E+10 | 0.221988E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.896742E+10 | 0.120845E+12 | 0.928931E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.671889E+09 | 0.192531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.811152E+09 | 0.181187E+11 | 0.275663E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_5:5
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.735692E+09 | 0.180236E+10 | 0.304407E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.667349E+09 | 0.253990E+10 | 0.323400E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.748357E+09 | 0.362376E+10 | 0.231748E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.707345E+09 | 0.659031E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.746112E+09 | 0.148388E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.746987E+09 | 0.159456E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.790127E+09 | 0.177727E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.802773E+09 | 0.178685E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.745002E+09 | 0.154640E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.759467E+09 | 0.131801E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.708007E+09 | 0.529466E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.731735E+09 | 0.339648E+10 | 0.267932E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.888895E+10 | 0.118317E+12 | 0.112749E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.667349E+09 | 0.180236E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.802773E+09 | 0.178685E+11 | 0.323400E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_6:6
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.115483E+10 | 0.288849E+10 | 0.723020E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.104641E+10 | 0.425662E+10 | 0.676976E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.117344E+10 | 0.612139E+10 | 0.474572E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.110751E+10 | 0.114975E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.118770E+10 | 0.263224E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.120319E+10 | 0.284936E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.128604E+10 | 0.316004E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130976E+10 | 0.319647E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.119965E+10 | 0.273697E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.121837E+10 | 0.235917E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.110946E+10 | 0.924491E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.114690E+10 | 0.588801E+10 | 0.613749E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.141433E+11 | 0.209239E+12 | 0.248832E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.104641E+10 | 0.288849E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130976E+10 | 0.319647E+11 | 0.723020E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_7:7
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.627582E+09 | 0.146789E+10 | 0.396262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.568723E+09 | 0.216931E+10 | 0.372882E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.637532E+09 | 0.312864E+10 | 0.260428E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.601283E+09 | 0.592755E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.644812E+09 | 0.136708E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.652762E+09 | 0.147997E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.697527E+09 | 0.164154E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.710186E+09 | 0.165950E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.650353E+09 | 0.142031E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.660211E+09 | 0.122322E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.602187E+09 | 0.474904E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.623126E+09 | 0.302982E+10 | 0.337310E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.767628E+10 | 0.108388E+12 | 0.136688E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.568723E+09 | 0.146789E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.710186E+09 | 0.165950E+11 | 0.396262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_8:8
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.625747E+09 | 0.143678E+10 | 0.427480E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.566878E+09 | 0.212560E+10 | 0.393766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.635225E+09 | 0.307363E+10 | 0.274782E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.598725E+09 | 0.585608E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.642098E+09 | 0.135963E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.650144E+09 | 0.147310E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.694962E+09 | 0.163502E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.707625E+09 | 0.165314E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.647880E+09 | 0.141403E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.657545E+09 | 0.121673E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.599603E+09 | 0.469214E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.620982E+09 | 0.299045E+10 | 0.356803E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.764741E+10 | 0.107691E+12 | 0.145283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.566878E+09 | 0.143678E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.707625E+09 | 0.165314E+11 | 0.427480E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_9:9
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.630007E+09 | 0.137337E+10 | 0.521751E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.570140E+09 | 0.202311E+10 | 0.455122E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.638538E+09 | 0.295895E+10 | 0.329295E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.600349E+09 | 0.570089E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.642798E+09 | 0.135136E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.650949E+09 | 0.146893E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.696369E+09 | 0.163465E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.709479E+09 | 0.165548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.649587E+09 | 0.141335E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.658977E+09 | 0.121326E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.601145E+09 | 0.458974E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.624254E+09 | 0.291528E+10 | 0.416229E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.767259E+10 | 0.106932E+12 | 0.172240E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.570140E+09 | 0.137337E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.709479E+09 | 0.165548E+11 | 0.521751E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_10:10
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.730613E+09 | 0.144123E+10 | 0.772827E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.660015E+09 | 0.209904E+10 | 0.633829E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.739335E+09 | 0.315904E+10 | 0.511567E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.690266E+09 | 0.602264E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.728924E+09 | 0.146736E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.734146E+09 | 0.161057E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.785603E+09 | 0.180377E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.801147E+09 | 0.184220E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.737903E+09 | 0.156262E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.747702E+09 | 0.133749E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.691122E+09 | 0.489315E+10 | 1412889.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.722507E+09 | 0.303936E+10 | 0.603961E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.876928E+10 | 0.116895E+12 | 0.252360E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.660015E+09 | 0.144123E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.801147E+09 | 0.184220E+11 | 0.772827E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.169283E+10 | 0.00 | 0.00 | 0.00 | 0.112190E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.153676E+10 | 0.00 | 0.00 | 0.00 | 0.145096E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.169683E+10 | 0.00 | 0.00 | 0.00 | 0.215851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.162663E+10 | 0.00 | 0.00 | 0.00 | 0.409567E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.170535E+10 | 0.00 | 0.00 | 0.00 | 0.906932E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.169638E+10 | 0.00 | 0.00 | 0.00 | 0.962670E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.181859E+10 | 0.00 | 0.00 | 0.00 | 0.107597E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.181847E+10 | 0.00 | 0.00 | 0.00 | 0.106489E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.172024E+10 | 0.00 | 0.00 | 0.00 | 0.935564E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.175040E+10 | 0.00 | 0.00 | 0.00 | 0.801325E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.162560E+10 | 0.00 | 0.00 | 0.00 | 0.315755E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.169915E+10 | 0.00 | 0.00 | 0.00 | 0.204570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.203872E+11 | 0.00 | 0.00 | 0.00 | 0.715038E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.153676E+10 | 0.00 | 0.00 | 0.00 | 0.112190E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.181859E+10 | 0.00 | 0.00 | 0.00 | 0.107597E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.766590E+09 | 0.00 | 0.00 | 0.00 | 0.671651E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.729710E+09 | 0.00 | 0.00 | 0.00 | 0.884296E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.806818E+09 | 0.00 | 0.00 | 0.00 | 0.128493E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.783182E+09 | 0.00 | 0.00 | 0.00 | 0.228537E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.807354E+09 | 0.00 | 0.00 | 0.00 | 0.455081E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.810598E+09 | 0.00 | 0.00 | 0.00 | 0.478365E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.878511E+09 | 0.00 | 0.00 | 0.00 | 0.529973E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.876314E+09 | 0.00 | 0.00 | 0.00 | 0.522803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.819364E+09 | 0.00 | 0.00 | 0.00 | 0.462031E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.836891E+09 | 0.00 | 0.00 | 0.00 | 0.403131E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.816673E+09 | 0.00 | 0.00 | 0.00 | 0.172425E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.815546E+09 | 0.00 | 0.00 | 0.00 | 0.110685E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.974755E+10 | 0.00 | 0.00 | 0.00 | 0.364712E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.729710E+09 | 0.00 | 0.00 | 0.00 | 0.671651E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.878511E+09 | 0.00 | 0.00 | 0.00 | 0.529973E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_3:3
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.737069E+09 | 0.00 | 0.00 | 0.00 | 0.503591E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.669261E+09 | 0.00 | 0.00 | 0.00 | 0.689844E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.751394E+09 | 0.00 | 0.00 | 0.00 | 0.974710E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.711732E+09 | 0.00 | 0.00 | 0.00 | 0.173669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.751655E+09 | 0.00 | 0.00 | 0.00 | 0.369355E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.752956E+09 | 0.00 | 0.00 | 0.00 | 0.393171E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.795849E+09 | 0.00 | 0.00 | 0.00 | 0.428958E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.809243E+09 | 0.00 | 0.00 | 0.00 | 0.432804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.750173E+09 | 0.00 | 0.00 | 0.00 | 0.371205E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.764927E+09 | 0.00 | 0.00 | 0.00 | 0.320267E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.712416E+09 | 0.00 | 0.00 | 0.00 | 0.135927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.734327E+09 | 0.00 | 0.00 | 0.00 | 0.878438E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.894100E+10 | 0.00 | 0.00 | 0.00 | 0.293001E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.669261E+09 | 0.00 | 0.00 | 0.00 | 0.503591E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.809243E+09 | 0.00 | 0.00 | 0.00 | 0.432804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_4:4
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.740247E+09 | 0.00 | 0.00 | 0.00 | 0.485347E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.671889E+09 | 0.00 | 0.00 | 0.00 | 0.674475E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.753986E+09 | 0.00 | 0.00 | 0.00 | 0.959641E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.713688E+09 | 0.00 | 0.00 | 0.00 | 0.172675E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.753360E+09 | 0.00 | 0.00 | 0.00 | 0.370073E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.754695E+09 | 0.00 | 0.00 | 0.00 | 0.394225E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.798034E+09 | 0.00 | 0.00 | 0.00 | 0.430543E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.811152E+09 | 0.00 | 0.00 | 0.00 | 0.434102E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.752201E+09 | 0.00 | 0.00 | 0.00 | 0.372358E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.766846E+09 | 0.00 | 0.00 | 0.00 | 0.320956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.714349E+09 | 0.00 | 0.00 | 0.00 | 0.134715E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.736977E+09 | 0.00 | 0.00 | 0.00 | 0.868081E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.896742E+10 | 0.00 | 0.00 | 0.00 | 0.292840E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.671889E+09 | 0.00 | 0.00 | 0.00 | 0.485347E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.811152E+09 | 0.00 | 0.00 | 0.00 | 0.434102E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_5:5
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.735692E+09 | 0.00 | 0.00 | 0.00 | 0.455820E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.667349E+09 | 0.00 | 0.00 | 0.00 | 0.637898E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.748357E+09 | 0.00 | 0.00 | 0.00 | 0.916363E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.707345E+09 | 0.00 | 0.00 | 0.00 | 0.166386E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.746112E+09 | 0.00 | 0.00 | 0.00 | 0.363915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.746987E+09 | 0.00 | 0.00 | 0.00 | 0.388307E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.790127E+09 | 0.00 | 0.00 | 0.00 | 0.424671E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.802773E+09 | 0.00 | 0.00 | 0.00 | 0.428138E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.745002E+09 | 0.00 | 0.00 | 0.00 | 0.366431E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.759467E+09 | 0.00 | 0.00 | 0.00 | 0.315816E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.708007E+09 | 0.00 | 0.00 | 0.00 | 0.130010E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.731735E+09 | 0.00 | 0.00 | 0.00 | 0.836064E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.888895E+10 | 0.00 | 0.00 | 0.00 | 0.286829E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.667349E+09 | 0.00 | 0.00 | 0.00 | 0.455820E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.802773E+09 | 0.00 | 0.00 | 0.00 | 0.428138E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_6:6
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.115483E+10 | 0.00 | 0.00 | 0.00 | 0.741542E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.104641E+10 | 0.00 | 0.00 | 0.00 | 0.108406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.156902E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.110751E+10 | 0.00 | 0.00 | 0.00 | 0.294080E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.118770E+10 | 0.00 | 0.00 | 0.00 | 0.652024E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.120319E+10 | 0.00 | 0.00 | 0.00 | 0.701272E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.128604E+10 | 0.00 | 0.00 | 0.00 | 0.763049E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130976E+10 | 0.00 | 0.00 | 0.00 | 0.774929E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.119965E+10 | 0.00 | 0.00 | 0.00 | 0.654668E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.121837E+10 | 0.00 | 0.00 | 0.00 | 0.571737E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.110946E+10 | 0.00 | 0.00 | 0.00 | 0.229357E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.114690E+10 | 0.00 | 0.00 | 0.00 | 0.146351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.141433E+11 | 0.00 | 0.00 | 0.00 | 0.512693E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.104641E+10 | 0.00 | 0.00 | 0.00 | 0.741542E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130976E+10 | 0.00 | 0.00 | 0.00 | 0.774929E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_7:7
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.627582E+09 | 0.00 | 0.00 | 0.00 | 0.370873E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.568723E+09 | 0.00 | 0.00 | 0.00 | 0.543790E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.637532E+09 | 0.00 | 0.00 | 0.00 | 0.789262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.601283E+09 | 0.00 | 0.00 | 0.00 | 0.149219E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.644812E+09 | 0.00 | 0.00 | 0.00 | 0.333546E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.652762E+09 | 0.00 | 0.00 | 0.00 | 0.358851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.697527E+09 | 0.00 | 0.00 | 0.00 | 0.390599E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.710186E+09 | 0.00 | 0.00 | 0.00 | 0.396396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.650353E+09 | 0.00 | 0.00 | 0.00 | 0.334585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.660211E+09 | 0.00 | 0.00 | 0.00 | 0.291879E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.602187E+09 | 0.00 | 0.00 | 0.00 | 0.115905E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.623126E+09 | 0.00 | 0.00 | 0.00 | 0.740937E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.767628E+10 | 0.00 | 0.00 | 0.00 | 0.261547E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.568723E+09 | 0.00 | 0.00 | 0.00 | 0.370873E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.710186E+09 | 0.00 | 0.00 | 0.00 | 0.396396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_8:8
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.625747E+09 | 0.00 | 0.00 | 0.00 | 0.363346E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.566878E+09 | 0.00 | 0.00 | 0.00 | 0.533275E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.635225E+09 | 0.00 | 0.00 | 0.00 | 0.775868E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.598725E+09 | 0.00 | 0.00 | 0.00 | 0.147468E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.642098E+09 | 0.00 | 0.00 | 0.00 | 0.331707E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.650144E+09 | 0.00 | 0.00 | 0.00 | 0.357123E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.694962E+09 | 0.00 | 0.00 | 0.00 | 0.388963E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.707625E+09 | 0.00 | 0.00 | 0.00 | 0.394792E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.647880E+09 | 0.00 | 0.00 | 0.00 | 0.333052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.657545E+09 | 0.00 | 0.00 | 0.00 | 0.290291E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.599603E+09 | 0.00 | 0.00 | 0.00 | 0.114511E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.620982E+09 | 0.00 | 0.00 | 0.00 | 0.731491E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.764741E+10 | 0.00 | 0.00 | 0.00 | 0.259831E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.566878E+09 | 0.00 | 0.00 | 0.00 | 0.363346E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.707625E+09 | 0.00 | 0.00 | 0.00 | 0.394792E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_9:9
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.630007E+09 | 0.00 | 0.00 | 0.00 | 0.348182E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.570140E+09 | 0.00 | 0.00 | 0.00 | 0.509037E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.638538E+09 | 0.00 | 0.00 | 0.00 | 0.748787E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.600349E+09 | 0.00 | 0.00 | 0.00 | 0.143864E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.642798E+09 | 0.00 | 0.00 | 0.00 | 0.330000E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.650949E+09 | 0.00 | 0.00 | 0.00 | 0.356313E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.696369E+09 | 0.00 | 0.00 | 0.00 | 0.389043E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.709479E+09 | 0.00 | 0.00 | 0.00 | 0.395464E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.649587E+09 | 0.00 | 0.00 | 0.00 | 0.333048E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.658977E+09 | 0.00 | 0.00 | 0.00 | 0.289602E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.601145E+09 | 0.00 | 0.00 | 0.00 | 0.112094E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.624254E+09 | 0.00 | 0.00 | 0.00 | 0.714446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.767259E+10 | 0.00 | 0.00 | 0.00 | 0.258147E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.570140E+09 | 0.00 | 0.00 | 0.00 | 0.348182E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.709479E+09 | 0.00 | 0.00 | 0.00 | 0.395464E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_10:10
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.730613E+09 | 0.00 | 0.00 | 0.00 | 0.368689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.660015E+09 | 0.00 | 0.00 | 0.00 | 0.534308E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.739335E+09 | 0.00 | 0.00 | 0.00 | 0.807125E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.690266E+09 | 0.00 | 0.00 | 0.00 | 0.153665E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.728924E+09 | 0.00 | 0.00 | 0.00 | 0.362358E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.734146E+09 | 0.00 | 0.00 | 0.00 | 0.394502E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.785603E+09 | 0.00 | 0.00 | 0.00 | 0.433482E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.801147E+09 | 0.00 | 0.00 | 0.00 | 0.443568E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.737903E+09 | 0.00 | 0.00 | 0.00 | 0.371545E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.747702E+09 | 0.00 | 0.00 | 0.00 | 0.321751E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.691122E+09 | 0.00 | 0.00 | 0.00 | 0.120717E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.722507E+09 | 0.00 | 0.00 | 0.00 | 0.755900E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.876928E+10 | 0.00 | 0.00 | 0.00 | 0.284819E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.660015E+09 | 0.00 | 0.00 | 0.00 | 0.368689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.801147E+09 | 0.00 | 0.00 | 0.00 | 0.443568E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.580426E+10 | 0.652469E+09 | 0.00 | 2937175.83 | 3142647.26 | 66796063.95 | 0.148883E+10 | 0.00 | 0.63 |
February | 0.350850E+10 | 0.849157E+09 | 0.00 | 3817807.94 | 0.00 | 0.251891E+09 | 0.219164E+10 | 0.00 | 0.69 |
March | 0.263703E+10 | 0.159246E+10 | 0.00 | 4293853.40 | 718645.03 | 0.266366E+09 | 0.234037E+10 | 0.00 | 0.69 |
April | 0.251399E+09 | 0.383935E+10 | 0.00 | 5775472.97 | 2999179.75 | 0.00 | 0.269327E+10 | 0.00 | 0.74 |
May | 0.00 | 0.129794E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.54 |
June | 0.00 | 0.145160E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.54 |
July | 0.00 | 0.174127E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.54 |
August | 0.00 | 0.162293E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.54 |
September | 0.00 | 0.136240E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.54 |
October | 91195941.72 | 0.104223E+11 | 0.00 | 3442458.70 | 0.00 | 0.00 | 0.123724E+10 | 0.00 | 0.63 |
November | 0.820858E+09 | 0.302554E+10 | 0.00 | 8144078.93 | 2839447.88 | 0.00 | 0.452116E+10 | 0.00 | 0.81 |
December | 0.342294E+10 | 0.180812E+10 | 0.00 | 4092059.21 | 6850825.41 | 0.147926E+09 | 0.311069E+10 | 0.00 | 0.66 |
Annual Sum or Average | 0.165362E+11 | 0.969508E+11 | 0.00 | 32502906.97 | 16550745.33 | 0.732979E+09 | 0.175832E+11 | 0.00 | 0.63 |
Minimum of Months | 0.00 | 0.652469E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.54 |
Maximum of Months | 0.580426E+10 | 0.174127E+11 | 0.00 | 8144078.93 | 6850825.41 | 0.266366E+09 | 0.452116E+10 | 0.00 | 0.81 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.191514E+10 | 0.353485E+09 | 0.00 | 1949113.40 | 135558.26 | 0.00 | 0.109769E+10 | 0.00 | 0.55 |
February | 0.104530E+10 | 0.484237E+09 | 0.00 | 2379580.78 | 0.00 | 33909505.88 | 0.144363E+10 | 0.00 | 0.63 |
March | 0.852180E+09 | 0.877200E+09 | 0.00 | 2477484.57 | 0.00 | 59594567.79 | 0.138287E+10 | 0.00 | 0.61 |
April | 59962008.64 | 0.187856E+10 | 0.00 | 2693426.62 | 452247.05 | 0.00 | 0.124649E+10 | 0.00 | 0.65 |
May | 0.00 | 0.573841E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.44 |
June | 0.00 | 0.639021E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.44 |
July | 0.00 | 0.755149E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.44 |
August | 0.00 | 0.711427E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.44 |
September | 0.00 | 0.597559E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.44 |
October | 27886215.26 | 0.460781E+10 | 0.00 | 1535068.26 | 0.00 | 0.00 | 0.562167E+09 | 0.00 | 0.53 |
November | 0.204687E+09 | 0.142557E+10 | 0.00 | 4571541.14 | 254339.87 | 0.00 | 0.247340E+10 | 0.00 | 0.79 |
December | 0.108581E+10 | 0.887673E+09 | 0.00 | 3037051.72 | 134227.43 | 17687230.83 | 0.207783E+10 | 0.00 | 0.64 |
Annual Sum or Average | 0.519097E+10 | 0.432845E+11 | 0.00 | 18643266.49 | 976372.61 | 0.111191E+09 | 0.102841E+11 | 0.00 | 0.55 |
Minimum of Months | 0.00 | 0.353485E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.44 |
Maximum of Months | 0.191514E+10 | 0.755149E+10 | 0.00 | 4571541.14 | 452247.05 | 59594567.79 | 0.247340E+10 | 0.00 | 0.79 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.210146E+10 | 0.288674E+09 | 0.00 | 735863.64 | 9429018.91 | 42122152.24 | 0.422036E+09 | 0.00 | 0.49 |
February | 0.126948E+10 | 0.401451E+09 | 0.00 | 1100338.29 | 6148965.63 | 90221400.68 | 0.610089E+09 | 0.00 | 0.54 |
March | 0.106276E+10 | 0.727681E+09 | 0.00 | 1252158.32 | 14558737.12 | 0.104125E+09 | 0.699865E+09 | 0.00 | 0.55 |
April | 0.171145E+09 | 0.150046E+10 | 0.00 | 1624771.99 | 73894057.29 | 0.00 | 0.768974E+09 | 0.00 | 0.60 |
May | 0.00 | 0.486583E+10 | 0.00 | 19934.81 | 0.300982E+09 | 0.00 | 223374.61 | 0.00 | 0.43 |
June | 0.00 | 0.546557E+10 | 0.00 | 37957.01 | 0.351560E+09 | 0.00 | 742860.16 | 0.00 | 0.43 |
July | 0.00 | 0.629778E+10 | 0.00 | 0.00 | 0.398836E+09 | 0.00 | 0.00 | 0.00 | 0.42 |
August | 0.00 | 0.610606E+10 | 0.00 | 0.00 | 0.346732E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
September | 743098.54 | 0.498856E+10 | 0.00 | 53615.42 | 0.280827E+09 | 0.00 | 140896.49 | 0.00 | 0.42 |
October | 72231951.47 | 0.389462E+10 | 0.00 | 1418390.33 | 0.215832E+09 | 0.00 | 0.481250E+09 | 0.00 | 0.51 |
November | 0.426826E+09 | 0.119890E+10 | 0.00 | 2690413.72 | 61701167.76 | 0.00 | 0.143931E+10 | 0.00 | 0.67 |
December | 0.137677E+10 | 0.755221E+09 | 0.00 | 1505088.60 | 28924535.89 | 58718091.15 | 0.942882E+09 | 0.00 | 0.54 |
Annual Sum or Average | 0.648143E+10 | 0.364908E+11 | 0.00 | 10438532.13 | 0.208942E+10 | 0.295186E+09 | 0.536552E+10 | 0.00 | 0.50 |
Minimum of Months | 0.00 | 0.288674E+09 | 0.00 | 0.00 | 6148965.63 | 0.00 | 0.00 | 0.00 | 0.42 |
Maximum of Months | 0.210146E+10 | 0.629778E+10 | 0.00 | 2690413.72 | 0.398836E+09 | 0.104125E+09 | 0.143931E+10 | 0.00 | 0.67 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.208978E+10 | 0.281021E+09 | 0.00 | 698565.48 | 9774465.81 | 55588913.29 | 0.398690E+09 | 0.00 | 0.49 |
February | 0.127880E+10 | 0.395373E+09 | 0.00 | 1012277.54 | 6065861.65 | 0.102109E+09 | 0.563971E+09 | 0.00 | 0.53 |
March | 0.107144E+10 | 0.722759E+09 | 0.00 | 1149756.58 | 14365717.00 | 0.107979E+09 | 0.663007E+09 | 0.00 | 0.55 |
April | 0.172720E+09 | 0.149572E+10 | 0.00 | 1585812.76 | 74893065.58 | 0.00 | 0.761678E+09 | 0.00 | 0.59 |
May | 0.00 | 0.487104E+10 | 0.00 | 20026.81 | 0.300901E+09 | 0.00 | 227323.43 | 0.00 | 0.43 |
June | 0.00 | 0.547366E+10 | 0.00 | 38343.67 | 0.351561E+09 | 0.00 | 751844.40 | 0.00 | 0.43 |
July | 0.00 | 0.631077E+10 | 0.00 | 0.00 | 0.398952E+09 | 0.00 | 0.00 | 0.00 | 0.42 |
August | 0.00 | 0.611646E+10 | 0.00 | 0.00 | 0.346763E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
September | 743477.20 | 0.499808E+10 | 0.00 | 57251.19 | 0.280850E+09 | 0.00 | 145130.69 | 0.00 | 0.42 |
October | 72502757.87 | 0.390014E+10 | 0.00 | 1432494.90 | 0.215795E+09 | 0.00 | 0.481350E+09 | 0.00 | 0.51 |
November | 0.443383E+09 | 0.119599E+10 | 0.00 | 2619349.08 | 61671957.42 | 0.00 | 0.141087E+10 | 0.00 | 0.66 |
December | 0.138624E+10 | 0.752433E+09 | 0.00 | 1387805.75 | 29293097.73 | 67632367.36 | 0.890233E+09 | 0.00 | 0.53 |
Annual Sum or Average | 0.651561E+10 | 0.365135E+11 | 0.00 | 10001683.76 | 0.209089E+10 | 0.333309E+09 | 0.517092E+10 | 0.00 | 0.50 |
Minimum of Months | 0.00 | 0.281021E+09 | 0.00 | 0.00 | 6065861.65 | 0.00 | 0.00 | 0.00 | 0.42 |
Maximum of Months | 0.208978E+10 | 0.631077E+10 | 0.00 | 2619349.08 | 0.398952E+09 | 0.107979E+09 | 0.141087E+10 | 0.00 | 0.66 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.206626E+10 | 0.265590E+09 | 0.00 | 591527.04 | 10165835.44 | 86290997.89 | 0.344750E+09 | 0.00 | 0.48 |
February | 0.128174E+10 | 0.378781E+09 | 0.00 | 875669.56 | 5794260.85 | 0.130284E+09 | 0.491042E+09 | 0.00 | 0.53 |
March | 0.113714E+10 | 0.703154E+09 | 0.00 | 953226.44 | 13768656.39 | 0.115743E+09 | 0.538552E+09 | 0.00 | 0.54 |
April | 0.190425E+09 | 0.145822E+10 | 0.00 | 1466918.99 | 74350552.64 | 0.00 | 0.725933E+09 | 0.00 | 0.59 |
May | 0.00 | 0.482321E+10 | 0.00 | 18233.50 | 0.299045E+09 | 0.00 | 221089.68 | 0.00 | 0.43 |
June | 0.00 | 0.543015E+10 | 0.00 | 34969.22 | 0.349854E+09 | 0.00 | 700830.74 | 0.00 | 0.43 |
July | 0.00 | 0.626520E+10 | 0.00 | 0.00 | 0.397047E+09 | 0.00 | 0.00 | 0.00 | 0.42 |
August | 0.00 | 0.607121E+10 | 0.00 | 0.00 | 0.344987E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
September | 3756215.73 | 0.494879E+10 | 0.00 | 96615.51 | 0.278188E+09 | 0.00 | 8060252.18 | 0.00 | 0.43 |
October | 82842841.18 | 0.386727E+10 | 0.00 | 1355438.95 | 0.214497E+09 | 0.00 | 0.456718E+09 | 0.00 | 0.50 |
November | 0.483595E+09 | 0.117543E+10 | 0.00 | 2412526.50 | 61193811.36 | 0.00 | 0.132225E+10 | 0.00 | 0.65 |
December | 0.140878E+10 | 0.735472E+09 | 0.00 | 1171943.31 | 29340613.69 | 96637926.43 | 0.776379E+09 | 0.00 | 0.52 |
Annual Sum or Average | 0.665455E+10 | 0.361225E+11 | 0.00 | 8977069.01 | 0.207823E+10 | 0.428956E+09 | 0.466460E+10 | 0.00 | 0.49 |
Minimum of Months | 0.00 | 0.265590E+09 | 0.00 | 0.00 | 5794260.85 | 0.00 | 0.00 | 0.00 | 0.42 |
Maximum of Months | 0.206626E+10 | 0.626520E+10 | 0.00 | 2412526.50 | 0.397047E+09 | 0.130284E+09 | 0.132225E+10 | 0.00 | 0.65 |
Report: MechanicalVentilationLoadsMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.380784E+10 | 0.416872E+09 | 0.00 | 1056584.00 | 22962602.34 | 0.127834E+09 | 0.634031E+09 | 0.00 | 0.44 |
February | 0.239212E+10 | 0.620391E+09 | 0.00 | 1361524.17 | 10715780.36 | 0.240889E+09 | 0.753291E+09 | 0.00 | 0.47 |
March | 0.208389E+10 | 0.120146E+10 | 0.00 | 1372660.83 | 15315503.78 | 0.250298E+09 | 0.810984E+09 | 0.00 | 0.47 |
April | 0.281534E+09 | 0.264128E+10 | 0.00 | 2261351.54 | 58820858.14 | 0.00 | 0.118190E+10 | 0.00 | 0.51 |
May | 0.00 | 0.898857E+10 | 0.00 | 0.00 | 0.155802E+09 | 0.00 | 0.00 | 0.00 | 0.39 |
June | 0.00 | 0.102495E+11 | 0.00 | 0.00 | 0.164420E+09 | 0.00 | 0.00 | 0.00 | 0.39 |
July | 0.00 | 0.116737E+11 | 0.00 | 0.00 | 0.278557E+09 | 0.00 | 0.00 | 0.00 | 0.38 |
August | 0.00 | 0.114369E+11 | 0.00 | 0.00 | 0.155635E+09 | 0.00 | 0.00 | 0.00 | 0.39 |
September | 0.00 | 0.912386E+10 | 0.00 | 126695.67 | 0.216226E+09 | 0.00 | 44206065.47 | 0.00 | 0.39 |
October | 84079664.31 | 0.727319E+10 | 0.00 | 2267912.16 | 0.120704E+09 | 0.00 | 0.743557E+09 | 0.00 | 0.45 |
November | 0.722262E+09 | 0.216828E+10 | 0.00 | 3917049.95 | 31101624.18 | 0.00 | 0.229912E+10 | 0.00 | 0.56 |
December | 0.269327E+10 | 0.129769E+10 | 0.00 | 1606451.48 | 30613032.86 | 0.174173E+09 | 0.115649E+10 | 0.00 | 0.45 |
Annual Sum or Average | 0.120650E+11 | 0.670918E+11 | 0.00 | 13970229.80 | 0.126087E+10 | 0.793194E+09 | 0.762358E+10 | 0.00 | 0.44 |
Minimum of Months | 0.00 | 0.416872E+09 | 0.00 | 0.00 | 10715780.36 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.380784E+10 | 0.116737E+11 | 0.00 | 3917049.95 | 0.278557E+09 | 0.250298E+09 | 0.229912E+10 | 0.00 | 0.56 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.187408E+10 | 0.204387E+09 | 0.00 | 495836.49 | 12088816.35 | 94973642.04 | 0.295791E+09 | 0.00 | 0.45 |
February | 0.113547E+10 | 0.304312E+09 | 0.00 | 658967.47 | 5667948.24 | 0.172934E+09 | 0.374657E+09 | 0.00 | 0.47 |
March | 0.105258E+10 | 0.592088E+09 | 0.00 | 637756.56 | 7517848.94 | 0.127020E+09 | 0.379485E+09 | 0.00 | 0.48 |
April | 0.148377E+09 | 0.131664E+10 | 0.00 | 1100808.80 | 29070852.18 | 0.00 | 0.589244E+09 | 0.00 | 0.52 |
May | 0.00 | 0.448699E+10 | 0.00 | 0.00 | 76891924.87 | 0.00 | 0.00 | 0.00 | 0.39 |
June | 0.00 | 0.511524E+10 | 0.00 | 0.00 | 81326351.15 | 0.00 | 0.00 | 0.00 | 0.39 |
July | 0.00 | 0.581911E+10 | 0.00 | 0.00 | 0.136970E+09 | 0.00 | 0.00 | 0.00 | 0.38 |
August | 0.00 | 0.570134E+10 | 0.00 | 0.00 | 76529710.35 | 0.00 | 0.00 | 0.00 | 0.39 |
September | 0.00 | 0.454202E+10 | 0.00 | 64546.93 | 0.106250E+09 | 0.00 | 24424231.95 | 0.00 | 0.39 |
October | 44187415.01 | 0.362401E+10 | 0.00 | 1124240.07 | 59060896.91 | 0.00 | 0.374088E+09 | 0.00 | 0.45 |
November | 0.367759E+09 | 0.107724E+10 | 0.00 | 1965505.47 | 15425374.12 | 0.00 | 0.115960E+10 | 0.00 | 0.57 |
December | 0.133425E+10 | 0.645044E+09 | 0.00 | 756710.93 | 15297560.53 | 0.120509E+09 | 0.542017E+09 | 0.00 | 0.45 |
Annual Sum or Average | 0.595671E+10 | 0.334284E+11 | 0.00 | 6804372.72 | 0.622097E+09 | 0.515437E+09 | 0.373931E+10 | 0.00 | 0.44 |
Minimum of Months | 0.00 | 0.204387E+09 | 0.00 | 0.00 | 5667948.24 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.187408E+10 | 0.581911E+10 | 0.00 | 1965505.47 | 0.136970E+09 | 0.172934E+09 | 0.115960E+10 | 0.00 | 0.57 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.186096E+10 | 0.202191E+09 | 0.00 | 464057.50 | 12976825.43 | 0.109058E+09 | 0.283557E+09 | 0.00 | 0.44 |
February | 0.112467E+10 | 0.299984E+09 | 0.00 | 626411.06 | 5805159.70 | 0.184287E+09 | 0.363219E+09 | 0.00 | 0.47 |
March | 0.105676E+10 | 0.584477E+09 | 0.00 | 600744.82 | 7772156.10 | 0.133619E+09 | 0.357049E+09 | 0.00 | 0.47 |
April | 0.156887E+09 | 0.130686E+10 | 0.00 | 1058511.04 | 29109110.67 | 0.00 | 0.572791E+09 | 0.00 | 0.51 |
May | 0.00 | 0.447283E+10 | 0.00 | 0.00 | 76779654.85 | 0.00 | 0.00 | 0.00 | 0.39 |
June | 0.00 | 0.510250E+10 | 0.00 | 0.00 | 81226412.22 | 0.00 | 0.00 | 0.00 | 0.39 |
July | 0.00 | 0.580643E+10 | 0.00 | 0.00 | 0.136801E+09 | 0.00 | 0.00 | 0.00 | 0.38 |
August | 0.00 | 0.568944E+10 | 0.00 | 0.00 | 76431451.12 | 0.00 | 0.00 | 0.00 | 0.39 |
September | 0.00 | 0.452979E+10 | 0.00 | 63924.37 | 0.106105E+09 | 0.00 | 24559762.07 | 0.00 | 0.39 |
October | 48121264.70 | 0.361360E+10 | 0.00 | 1105655.47 | 58953321.13 | 0.00 | 0.366703E+09 | 0.00 | 0.45 |
November | 0.379950E+09 | 0.107105E+10 | 0.00 | 1917320.16 | 15444062.54 | 0.00 | 0.113258E+10 | 0.00 | 0.57 |
December | 0.133443E+10 | 0.639270E+09 | 0.00 | 708639.24 | 15591450.16 | 0.131649E+09 | 0.514725E+09 | 0.00 | 0.45 |
Annual Sum or Average | 0.596177E+10 | 0.333184E+11 | 0.00 | 6545263.64 | 0.622995E+09 | 0.558613E+09 | 0.361519E+10 | 0.00 | 0.44 |
Minimum of Months | 0.00 | 0.202191E+09 | 0.00 | 0.00 | 5805159.70 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.186096E+10 | 0.580643E+10 | 0.00 | 1917320.16 | 0.136801E+09 | 0.184287E+09 | 0.113258E+10 | 0.00 | 0.57 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.181047E+10 | 0.194474E+09 | 0.00 | 413874.61 | 15082133.19 | 0.160555E+09 | 0.261077E+09 | 0.00 | 0.44 |
February | 0.107540E+10 | 0.289353E+09 | 0.00 | 582757.36 | 6682252.38 | 0.233822E+09 | 0.344529E+09 | 0.00 | 0.46 |
March | 0.104660E+10 | 0.567672E+09 | 0.00 | 529375.94 | 8425689.97 | 0.156111E+09 | 0.318317E+09 | 0.00 | 0.47 |
April | 0.174584E+09 | 0.128503E+10 | 0.00 | 945347.38 | 31699112.68 | 0.00 | 0.536829E+09 | 0.00 | 0.51 |
May | 0.00 | 0.445375E+10 | 0.00 | 0.00 | 76700821.42 | 0.00 | 0.00 | 0.00 | 0.39 |
June | 0.00 | 0.509222E+10 | 0.00 | 0.00 | 81223706.24 | 0.00 | 0.00 | 0.00 | 0.39 |
July | 0.00 | 0.580322E+10 | 0.00 | 0.00 | 0.136892E+09 | 0.00 | 0.00 | 0.00 | 0.38 |
August | 0.00 | 0.569174E+10 | 0.00 | 0.00 | 76511893.04 | 0.00 | 0.00 | 0.00 | 0.39 |
September | 0.00 | 0.452551E+10 | 0.00 | 63783.94 | 0.106214E+09 | 0.00 | 24712003.15 | 0.00 | 0.39 |
October | 51835907.36 | 0.360795E+10 | 0.00 | 1058493.63 | 58996497.21 | 0.00 | 0.355887E+09 | 0.00 | 0.45 |
November | 0.406917E+09 | 0.106054E+10 | 0.00 | 1792281.90 | 15873609.58 | 0.00 | 0.107436E+10 | 0.00 | 0.56 |
December | 0.131268E+10 | 0.627419E+09 | 0.00 | 620152.98 | 16972914.21 | 0.181008E+09 | 0.452921E+09 | 0.00 | 0.44 |
Annual Sum or Average | 0.587849E+10 | 0.331989E+11 | 0.00 | 6006067.77 | 0.631275E+09 | 0.731496E+09 | 0.336863E+10 | 0.00 | 0.44 |
Minimum of Months | 0.00 | 0.194474E+09 | 0.00 | 0.00 | 6682252.38 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.181047E+10 | 0.580322E+10 | 0.00 | 1792281.90 | 0.136892E+09 | 0.233822E+09 | 0.107436E+10 | 0.00 | 0.56 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.165132E+10 | 0.200619E+09 | 0.00 | 412394.46 | 13644178.15 | 0.291240E+09 | 0.274001E+09 | 0.00 | 0.45 |
February | 0.921343E+09 | 0.295828E+09 | 0.00 | 565589.66 | 8642621.59 | 0.363476E+09 | 0.348742E+09 | 0.00 | 0.48 |
March | 0.898013E+09 | 0.578175E+09 | 0.00 | 538778.03 | 10893160.22 | 0.260209E+09 | 0.334668E+09 | 0.00 | 0.48 |
April | 0.181680E+09 | 0.130090E+10 | 0.00 | 906027.22 | 32972917.12 | 0.00 | 0.548044E+09 | 0.00 | 0.52 |
May | 0.00 | 0.454711E+10 | 0.00 | 0.00 | 77106316.01 | 0.00 | 0.00 | 0.00 | 0.39 |
June | 0.00 | 0.524048E+10 | 0.00 | 9147.64 | 82335796.79 | 0.00 | 64088.01 | 0.00 | 0.39 |
July | 0.00 | 0.599596E+10 | 0.00 | 0.00 | 0.139794E+09 | 0.00 | 0.00 | 0.00 | 0.38 |
August | 0.00 | 0.589086E+10 | 0.00 | 0.00 | 78414118.80 | 0.00 | 0.00 | 0.00 | 0.39 |
September | 0.00 | 0.468211E+10 | 0.00 | 67413.02 | 0.109161E+09 | 0.00 | 26025072.29 | 0.00 | 0.39 |
October | 66401458.24 | 0.371868E+10 | 0.00 | 1003987.64 | 60334436.19 | 0.00 | 0.344104E+09 | 0.00 | 0.46 |
November | 0.404524E+09 | 0.108890E+10 | 0.00 | 1757798.77 | 15677089.29 | 0.00 | 0.109537E+10 | 0.00 | 0.59 |
December | 0.110572E+10 | 0.621527E+09 | 0.00 | 611555.99 | 14664770.11 | 0.382130E+09 | 0.440258E+09 | 0.00 | 0.46 |
Annual Sum or Average | 0.522901E+10 | 0.341611E+11 | 0.00 | 5872692.42 | 0.643640E+09 | 0.129706E+10 | 0.341128E+10 | 0.00 | 0.45 |
Minimum of Months | 0.00 | 0.200619E+09 | 0.00 | 0.00 | 8642621.59 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.165132E+10 | 0.599596E+10 | 0.00 | 1757798.77 | 0.139794E+09 | 0.382130E+09 | 0.109537E+10 | 0.00 | 0.59 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:37:30
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.204968E+12 | 0.148835E+11 | 0.00 | 0.287398E+11 | 0.279220E+11 |
February | 0.229000E+12 | 0.867500E+10 | 0.00 | 0.202693E+11 | 0.385512E+11 |
March | 0.262086E+12 | 0.517415E+10 | 0.00 | 0.143102E+11 | 0.550425E+11 |
April | 0.308016E+12 | -0.872446E+10 | 0.00 | -0.698336E+10 | 0.100839E+12 |
May | 0.314640E+12 | -0.363630E+11 | 0.00 | -0.615906E+11 | 0.226275E+12 |
June | 0.317020E+12 | -0.395513E+11 | 0.00 | -0.696168E+11 | 0.243208E+12 |
July | 0.325988E+12 | -0.463554E+11 | 0.00 | -0.809603E+11 | 0.271136E+12 |
August | 0.301813E+12 | -0.453944E+11 | 0.00 | -0.775496E+11 | 0.272218E+12 |
September | 0.253512E+12 | -0.385830E+11 | 0.00 | -0.632640E+11 | 0.235599E+12 |
October | 0.255324E+12 | -0.287034E+11 | 0.00 | -0.434634E+11 | 0.202223E+12 |
November | 0.187210E+12 | -0.154178E+10 | 0.00 | 0.786390E+10 | 0.800329E+11 |
December | 0.185519E+12 | 0.875116E+10 | 0.00 | 0.199963E+11 | 0.521174E+11 |
Annual Sum or Average | 0.314510E+13 | -0.207733E+12 | 0.00 | -0.312248E+12 | 0.180516E+13 |
Minimum of Months | 0.185519E+12 | -0.463554E+11 | 0.00 | -0.809603E+11 | 0.279220E+11 |
Maximum of Months | 0.325988E+12 | 0.148835E+11 | 0.00 | 0.287398E+11 | 0.272218E+12 |