Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:37
Tabular Output Report in Format: HTML
Building: RetailStripmall
Environment: RUNPERIOD 1 ** Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930
Simulation Timestamp: 2023-10-16 08:37:31
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:31
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1124.18 | 537.80 | 537.80 |
Net Site Energy | 1124.18 | 537.80 | 537.80 |
Total Source Energy | 2930.75 | 1402.06 | 1402.06 |
Net Source Energy | 2930.75 | 1402.06 | 1402.06 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 2090.32 |
Net Conditioned Building Area | 2090.32 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 302.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 27.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 366.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 60.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 128.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 174.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 64.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 821.96 | 302.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 302.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 27.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 366.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 60.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 128.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 174.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 64.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 302.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 27.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 366.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 60.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 128.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 174.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 64.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 204.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 127.60 | 144.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Other | 61.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 393.22 | 144.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 204.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 127.60 | 144.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Other | 61.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 393.22 | 144.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 821.961 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 821.961 | 100.00 |
Total On-Site and Utility Electric Sources | 821.961 | 100.00 |
Total Electricity End Uses | 821.961 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 87.30 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 87.30 | 100.00 |
Total Water End Uses | 87.30 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 0.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 1368.67 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTRIPMALL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4C
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_SEATTLE
| Environment |ZoneCoolingSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ZoneHeatingSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ZoneElectricSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |SpaceGainsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |PeakSpaceGainsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |SpaceGainComponentsAtCoolingPeakMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ComfortReportSimple55Monthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |OccupantComfortDataSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |DXReportMonthly
| PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL | PSZ-AC_3:3 COOLING COIL | PSZ-AC_4:4 COOLING COIL | PSZ-AC_5:5 COOLING COIL | PSZ-AC_6:6 COOLING COIL | PSZ-AC_7:7 COOLING COIL | PSZ-AC_8:8 COOLING COIL | PSZ-AC_9:9 COOLING COIL | PSZ-AC_10:10 COOLING COIL |WindowReportMonthly
| LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR |WindowEnergyReportMonthly
| LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR |WindowZoneSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |WindowEnergyZoneSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| GAS TANK1 | GAS TANK2 | GAS TANK3 | GAS TANK4 | GAS TANK5 | GAS TANK6 | GAS TANK7 |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC_1:1 HEATING COIL | PSZ-AC_2:2 HEATING COIL | PSZ-AC_3:3 HEATING COIL | PSZ-AC_4:4 HEATING COIL | PSZ-AC_5:5 HEATING COIL | PSZ-AC_6:6 HEATING COIL | PSZ-AC_7:7 HEATING COIL | PSZ-AC_8:8 HEATING COIL | PSZ-AC_9:9 HEATING COIL | PSZ-AC_10:10 HEATING COIL | PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL | PSZ-AC_3:3 COOLING COIL | PSZ-AC_4:4 COOLING COIL | PSZ-AC_5:5 COOLING COIL | PSZ-AC_6:6 COOLING COIL | PSZ-AC_7:7 COOLING COIL | PSZ-AC_8:8 COOLING COIL | PSZ-AC_9:9 COOLING COIL | PSZ-AC_10:10 COOLING COIL |FanReportMonthly
| PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN |ZoneTemperatureOscillationReportMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |MechanicalVentilationLoadsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:31
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:37 |
RunPeriod | RUNPERIOD 1 |
Weather File | Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 |
Latitude [deg] | 47.47 |
Longitude [deg] | -122.3 |
Elevation [m] | 122.00 |
Time Zone | -8.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Above Ground Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Window Opening Area [m2] | 124.40 | 0.00 | 0.00 | 124.40 | 0.00 |
Gross Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Above Ground Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Above Ground Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Window Opening Area [m2] | 124.40 | 0.00 | 0.00 | 124.40 | 0.00 |
Gross Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Above Ground Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Total | |
Gross Roof Area [m2] | 2090.32 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
LGSTORE1 | 348.39 | Yes | Yes | 1805.20 | 1.00 | 276.30 | 0.00 | 20.77 | 20.77 | 15.3022 | 6.19 | 4.3000 |
SMSTORE1 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.38 | 10.38 | 18.2890 | 6.19 | 4.3000 |
SMSTORE2 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 16.6533 | 6.19 | 4.3000 |
SMSTORE3 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 16.6533 | 6.19 | 4.3000 |
SMSTORE4 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 16.6533 | 6.19 | 4.3000 |
LGSTORE2 | 348.39 | Yes | Yes | 1805.20 | 1.00 | 157.89 | 0.00 | 20.72 | 20.72 | 9.5842 | 6.19 | 4.3000 |
SMSTORE5 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 9.6995 | 6.19 | 4.3000 |
SMSTORE6 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 9.6995 | 6.19 | 4.3000 |
SMSTORE7 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 9.6995 | 6.19 | 4.3000 |
SMSTORE8 | 174.19 | Yes | Yes | 902.60 | 1.00 | 197.36 | 0.00 | 10.36 | 10.36 | 9.6995 | 6.19 | 4.3000 |
Total | 2090.32 | 10831.20 | 1184.15 | 0.00 | 124.40 | 124.40 | 13.0683 | 6.19 | 4.3000 | |||
Conditioned Total | 2090.32 | 10831.20 | 1184.15 | 0.00 | 124.40 | 124.40 | 13.0683 | 6.19 | 4.3000 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
LGSTORE1 | 348.39 | Yes | Yes | 1.00 | LGSTORE1 | GENERAL | LGSTORE1 | 15.3022 | 6.19 | 4.3000 | |
SMSTORE1 | 174.19 | Yes | Yes | 1.00 | SMSTORE1 | GENERAL | SMSTORE1 | 18.2890 | 6.19 | 4.3000 | |
SMSTORE2 | 174.19 | Yes | Yes | 1.00 | SMSTORE2 | GENERAL | SMSTORE2 | 16.6533 | 6.19 | 4.3000 | |
SMSTORE3 | 174.19 | Yes | Yes | 1.00 | SMSTORE3 | GENERAL | SMSTORE3 | 16.6533 | 6.19 | 4.3000 | |
SMSTORE4 | 174.19 | Yes | Yes | 1.00 | SMSTORE4 | GENERAL | SMSTORE4 | 16.6533 | 6.19 | 4.3000 | |
LGSTORE2 | 348.39 | Yes | Yes | 1.00 | LGSTORE2 | GENERAL | LGSTORE2 | 9.5842 | 6.19 | 4.3000 | |
SMSTORE5 | 174.19 | Yes | Yes | 1.00 | SMSTORE5 | GENERAL | SMSTORE5 | 9.6995 | 6.19 | 4.3000 | |
SMSTORE6 | 174.19 | Yes | Yes | 1.00 | SMSTORE6 | GENERAL | SMSTORE6 | 9.6995 | 6.19 | 4.3000 | |
SMSTORE7 | 174.19 | Yes | Yes | 1.00 | SMSTORE7 | GENERAL | SMSTORE7 | 9.6995 | 6.19 | 4.3000 | |
SMSTORE8 | 174.19 | Yes | Yes | 1.00 | SMSTORE8 | GENERAL | SMSTORE8 | 9.6995 | 6.19 | 4.3000 | |
Total | 2090.32 | 13.0683 | 3.10 | 4.3000 | |||||||
Conditioned Total | 2090.32 | 13.0683 | 3.10 | 4.3000 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 2090.32 | 2090.32 | 0.00 | 0.00 | 13.0683 | 6.19 | 4.3000 |
Total | 2090.32 | 2090.32 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:31
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 29-AUG-13:50 | 16-JAN-09:09 | - | - | - | - | - | - | - | - | - | - | 06-JAN-13:09 |
Heating | 0.00 | 144700.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 25008.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 23459.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 8059.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 10380.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 7575.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 74483.43 | 144700.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 144700.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 25008.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 23459.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 8059.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 10380.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 7575.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:31
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 327.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 88.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1161.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 191.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 405.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 553.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 203.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2603.15 | 327.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 156.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 42.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 555.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 91.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 194.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 264.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 97.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1245.34 | 156.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 156.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 42.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 555.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 91.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 194.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 264.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 97.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1245.34 | 156.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:31
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
LGSTORE1 DIRECT AIR | 1.87 |
SMSTORE1 DIRECT AIR | 0.988342 |
SMSTORE2 DIRECT AIR | 1.02 |
SMSTORE3 DIRECT AIR | 1.03 |
SMSTORE4 DIRECT AIR | 1.02 |
LGSTORE2 DIRECT AIR | 1.78 |
SMSTORE5 DIRECT AIR | 0.908037 |
SMSTORE6 DIRECT AIR | 0.901406 |
SMSTORE7 DIRECT AIR | 0.890585 |
SMSTORE8 DIRECT AIR | 0.942539 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC_1:1 | 1.87 | 1.87 | 1.87 | 1.87 | 1.87 | 1.87 | 1.00 | 1.000000 | 1.87 |
PSZ-AC_2:2 | 0.988342 | 0.988342 | 0.988342 | 0.988342 | 1.02 | 1.02 | 1.00 | 0.972362 | 1.02 |
PSZ-AC_3:3 | 1.02 | 1.02 | 1.02 | 1.02 | 1.02 | 1.02 | 1.00 | 1.00 | 1.02 |
PSZ-AC_4:4 | 1.03 | 1.03 | 1.03 | 1.03 | 1.03 | 1.03 | 1.00 | 1.00 | 1.03 |
PSZ-AC_5:5 | 1.02 | 1.02 | 1.02 | 1.02 | 1.02 | 1.02 | 1.00 | 1.00 | 1.02 |
PSZ-AC_6:6 | 1.78 | 1.78 | 1.78 | 1.78 | 1.78 | 1.78 | 1.00 | 1.00 | 1.78 |
PSZ-AC_7:7 | 0.908037 | 0.908037 | 0.908037 | 0.908037 | 0.919547 | 0.919547 | 1.00 | 0.987483 | 0.919547 |
PSZ-AC_8:8 | 0.901406 | 0.901406 | 0.901406 | 0.901406 | 0.913028 | 0.913028 | 1.00 | 0.987271 | 0.913028 |
PSZ-AC_9:9 | 0.890585 | 0.890585 | 0.890585 | 0.890585 | 0.906856 | 0.906856 | 1.00 | 0.982058 | 0.906856 |
PSZ-AC_10:10 | 0.942539 | 0.942539 | 0.942539 | 0.942539 | 0.964728 | 0.964728 | 1.00 | 0.977000 | 0.964728 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC_1:1_OA_CONTROLLER | 1.87 | 0.411479 |
PSZ-AC_2:2_OA_CONTROLLER | 1.02 | 0.205739 |
PSZ-AC_3:3_OA_CONTROLLER | 1.02 | 0.205739 |
PSZ-AC_4:4_OA_CONTROLLER | 1.03 | 0.205739 |
PSZ-AC_5:5_OA_CONTROLLER | 1.02 | 0.205739 |
PSZ-AC_6:6_OA_CONTROLLER | 1.78 | 0.411479 |
PSZ-AC_7:7_OA_CONTROLLER | 0.919547 | 0.205739 |
PSZ-AC_8:8_OA_CONTROLLER | 0.913028 | 0.205739 |
PSZ-AC_9:9_OA_CONTROLLER | 0.906856 | 0.205739 |
PSZ-AC_10:10_OA_CONTROLLER | 0.964728 | 0.205739 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | 1.87 | 2002.42 |
PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | 1.02 | 1125.35 |
PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | 1.02 | 1131.57 |
PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | 1.03 | 1135.37 |
PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | 1.02 | 1124.20 |
PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | 1.78 | 1907.87 |
PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | 0.919547 | 1018.08 |
PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | 0.913028 | 1010.87 |
PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | 0.906856 | 1004.03 |
PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | 0.964728 | 1068.11 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC_1:1_UNITARY_PACKAGE_DX | 1.87 | 1.87 | 1.87 | 1.24 | 32747.32 | 54590.70 | 40.00 | 1.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_DX | 1.02 | 1.02 | 1.02 | 1.02 | 17617.94 | 28482.14 | 40.00 | 1.00 |
PSZ-AC_3:3_UNITARY_PACKAGE_DX | 1.02 | 1.02 | 1.02 | 1.02 | 17704.74 | 29241.71 | 40.00 | 1.00 |
PSZ-AC_4:4_UNITARY_PACKAGE_DX | 1.03 | 1.03 | 1.03 | 1.03 | 17757.61 | 29318.96 | 40.00 | 1.00 |
PSZ-AC_5:5_UNITARY_PACKAGE_DX | 1.02 | 1.02 | 1.02 | 1.02 | 17602.36 | 29091.75 | 40.00 | 1.00 |
PSZ-AC_6:6_UNITARY_PACKAGE_DX | 1.78 | 1.78 | 1.78 | 1.18 | 31389.77 | 52598.82 | 40.00 | 1.00 |
PSZ-AC_7:7_UNITARY_PACKAGE_DX | 0.919547 | 0.919547 | 0.919547 | 0.919547 | 16122.53 | 26672.48 | 40.00 | 1.00 |
PSZ-AC_8:8_UNITARY_PACKAGE_DX | 0.913028 | 0.913028 | 0.913028 | 0.913028 | 16021.69 | 26523.05 | 40.00 | 1.00 |
PSZ-AC_9:9_UNITARY_PACKAGE_DX | 0.906856 | 0.906856 | 0.906856 | 0.906856 | 15925.99 | 26279.22 | 40.00 | 1.00 |
PSZ-AC_10:10_UNITARY_PACKAGE_DX | 0.964728 | 0.964728 | 0.964728 | 0.964728 | 16684.32 | 27450.62 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-AC_1:1 COOLING COIL | 1.87 | 0.935667 | 1.25 | 32747.32 | 16373.66 | 0.800780 | 0.800780 |
PSZ-AC_2:2 COOLING COIL | 1.02 | 0.508217 | 0.677620 | 17617.94 | 8808.97 | 0.800120 | 0.800120 |
PSZ-AC_3:3 COOLING COIL | 1.02 | 0.511025 | 0.681367 | 17704.74 | 8852.37 | 0.800330 | 0.800330 |
PSZ-AC_4:4 COOLING COIL | 1.03 | 0.512739 | 0.683653 | 17757.61 | 8878.81 | 0.800460 | 0.800460 |
PSZ-AC_5:5 COOLING COIL | 1.02 | 0.507698 | 0.676933 | 17602.36 | 8801.18 | 0.800070 | 0.800070 |
PSZ-AC_6:6 COOLING COIL | 1.78 | 0.891486 | 1.19 | 31389.77 | 15694.89 | 0.800690 | 0.800690 |
PSZ-AC_7:7 COOLING COIL | 0.919550 | 0.459773 | 0.613033 | 16122.53 | 8061.27 | 0.800110 | 0.800110 |
PSZ-AC_8:8 COOLING COIL | 0.913030 | 0.456514 | 0.608687 | 16021.69 | 8010.85 | 0.800820 | 0.800820 |
PSZ-AC_9:9 COOLING COIL | 0.906860 | 0.453428 | 0.604573 | 15925.99 | 7962.99 | 0.800550 | 0.800550 |
PSZ-AC_10:10 COOLING COIL | 0.964730 | 0.482364 | 0.643153 | 16684.32 | 8342.16 | 0.800910 | 0.800910 |
Design Size Nominal Capacity [W] | |
PSZ-AC_1:1 HEATING COIL | 54590.70 |
PSZ-AC_2:2 HEATING COIL | 28482.14 |
PSZ-AC_3:3 HEATING COIL | 29241.71 |
PSZ-AC_4:4 HEATING COIL | 29318.96 |
PSZ-AC_5:5 HEATING COIL | 29091.75 |
PSZ-AC_6:6 HEATING COIL | 52598.82 |
PSZ-AC_7:7 HEATING COIL | 26672.48 |
PSZ-AC_8:8 HEATING COIL | 26523.05 |
PSZ-AC_9:9 HEATING COIL | 26279.22 |
PSZ-AC_10:10 HEATING COIL | 27450.62 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:31
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
LGSTORE1_WALL_3 | LGSTORE1_WALL_3_DOOR_1 | LGSTORE1_WALL_3_DOOR_2 | |
LGSTORE1_WALL_1 | LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | |
SMSTORE1_WALL_1 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | |
SMSTORE1_WALL_3 | SMSTORE1_WALL_3_DOOR | |
SMSTORE2_WALL_1 | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | |
SMSTORE2_WALL_3 | SMSTORE2_WALL_3_DOOR | |
SMSTORE3_WALL_1 | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | |
SMSTORE3_WALL_3 | SMSTORE3_WALL_3_DOOR | |
SMSTORE4_WALL_1 | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | |
SMSTORE4_WALL_3 | SMSTORE4_WALL_3_DOOR | |
LGSTORE2_WALL_3 | LGSTORE2_WALL_3_DOOR_1 | LGSTORE2_WALL_3_DOOR_2 | |
LGSTORE2_WALL_1 | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | |
SMSTORE5_WALL_1 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | |
SMSTORE5_WALL_3 | SMSTORE5_WALL_3_DOOR | |
SMSTORE6_WALL_1 | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | |
SMSTORE6_WALL_3 | SMSTORE6_WALL_3_DOOR | |
SMSTORE7_WALL_1 | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | |
SMSTORE7_WALL_3 | SMSTORE7_WALL_3_DOOR | |
SMSTORE8_WALL_1 | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR | |
SMSTORE8_WALL_3 | SMSTORE8_WALL_3_DOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:31
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:31
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 11.40 | 8.10 | 5.40 | 4.50 | 5.80 | 8.30 | 10.90 | 13.00 | 15.60 | 17.70 | 18.80 | 15.10 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 | 47.47 | -122.32 | -8.00 | 122.00 | 99868 | 1.1870 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 11.22 | 14.30 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RetailStripmall | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 10 | 118 | 48 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | LGSTORE1 | 0.0 | 0.00 | 0.00 | 0.00 | 7.62 | 11.43 | 2.59 | 1 | 1 | 1 | 0.00 | 15.24 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 1805.20 | TARP | TARP | 348.39 | 276.30 | 247.74 | 20.77 | 6 | 8 | 0 | Yes |
2 | SMSTORE1 | 0.0 | 0.00 | 0.00 | 0.00 | 19.05 | 11.43 | 2.59 | 1 | 1 | 1 | 15.24 | 22.86 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.66 | 10.38 | 6 | 4 | 0 | Yes |
3 | SMSTORE2 | 0.0 | 0.00 | 0.00 | 0.00 | 26.67 | 11.43 | 2.59 | 1 | 1 | 1 | 22.86 | 30.48 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
4 | SMSTORE3 | 0.0 | 0.00 | 0.00 | 0.00 | 34.29 | 11.43 | 2.59 | 1 | 1 | 1 | 30.48 | 38.10 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
5 | SMSTORE4 | 0.0 | 0.00 | 0.00 | 0.00 | 41.91 | 11.43 | 2.59 | 1 | 1 | 1 | 38.10 | 45.72 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
6 | LGSTORE2 | 0.0 | 0.00 | 0.00 | 0.00 | 53.34 | 11.43 | 2.59 | 1 | 1 | 1 | 45.72 | 60.96 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 1805.20 | TARP | TARP | 348.39 | 157.89 | 129.41 | 20.72 | 6 | 8 | 0 | Yes |
7 | SMSTORE5 | 0.0 | 0.00 | 0.00 | 0.00 | 64.77 | 11.43 | 2.59 | 1 | 1 | 1 | 60.96 | 68.58 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
8 | SMSTORE6 | 0.0 | 0.00 | 0.00 | 0.00 | 72.39 | 11.43 | 2.59 | 1 | 1 | 1 | 68.58 | 76.20 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
9 | SMSTORE7 | 0.0 | 0.00 | 0.00 | 0.00 | 80.01 | 11.43 | 2.59 | 1 | 1 | 1 | 76.20 | 83.82 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
10 | SMSTORE8 | 0.0 | 0.00 | 0.00 | 0.00 | 87.63 | 11.43 | 2.59 | 1 | 1 | 1 | 83.82 | 91.44 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 197.36 | 183.12 | 10.36 | 6 | 4 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | LGSTORE1 | 348.39 | 56.3 | 6.193 | 0.161 | 15.302 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 19.602 | No |
2 | SMSTORE1 | 174.19 | 28.1 | 6.194 | 0.161 | 18.289 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 22.589 | No |
3 | SMSTORE2 | 174.19 | 28.1 | 6.194 | 0.161 | 16.653 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 20.953 | No |
4 | SMSTORE3 | 174.19 | 28.1 | 6.194 | 0.161 | 16.653 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 20.953 | No |
5 | SMSTORE4 | 174.19 | 28.1 | 6.194 | 0.161 | 16.653 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 20.953 | No |
6 | LGSTORE2 | 348.39 | 56.3 | 6.193 | 0.161 | 9.584 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 13.884 | No |
7 | SMSTORE5 | 174.19 | 28.1 | 6.194 | 0.161 | 9.699 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 13.999 | No |
8 | SMSTORE6 | 174.19 | 28.1 | 6.194 | 0.161 | 9.699 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 13.999 | No |
9 | SMSTORE7 | 174.19 | 28.1 | 6.194 | 0.161 | 9.699 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 13.999 | No |
10 | SMSTORE8 | 174.19 | 28.1 | 6.194 | 0.161 | 9.699 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 13.999 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | LGSTORE1 | TYPE1_OCC_SCH | LGSTORE1 | 348.39 | 56.3 | 56.3 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 56 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | SMSTORE1 | TYPE1_OCC_SCH | SMSTORE1 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | SMSTORE2 | TYPE2_OCC_SCH | SMSTORE2 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | SMSTORE3 | TYPE2_OCC_SCH | SMSTORE3 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | SMSTORE4 | TYPE2_OCC_SCH | SMSTORE4 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | LGSTORE2 | TYPE3_OCC_SCH | LGSTORE2 | 348.39 | 56.3 | 56.3 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 56 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | SMSTORE5 | TYPE3_OCC_SCH | SMSTORE5 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | SMSTORE6 | TYPE3_OCC_SCH | SMSTORE6 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | SMSTORE7 | TYPE3_OCC_SCH | SMSTORE7 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | SMSTORE8 | TYPE3_OCC_SCH | SMSTORE8 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | LGSTORE1_LIGHTS | LTG_SCH_BASE_LPD1 | LGSTORE1 | 348.39 | 56.3 | 3346.345 | 9.605 | 59.490 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3346.345 |
2 | LGSTORE1_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | LGSTORE1 | 348.39 | 56.3 | 1984.726 | 5.697 | 35.284 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1984.726 |
3 | SMSTORE1_LIGHTS | LTG_SCH_BASE_SMALL_LPD1 | SMSTORE1 | 174.19 | 28.1 | 1693.257 | 9.721 | 60.206 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1693.257 |
4 | SMSTORE1_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | SMSTORE1 | 174.19 | 28.1 | 1492.567 | 8.568 | 53.070 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1492.567 |
5 | SMSTORE2_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE2 | 174.19 | 28.1 | 1689.582 | 9.699 | 60.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1689.582 |
6 | SMSTORE2_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE2 | 174.19 | 28.1 | 1211.319 | 6.954 | 43.070 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1211.319 |
7 | SMSTORE3_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE3 | 174.19 | 28.1 | 1689.582 | 9.699 | 60.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1689.582 |
8 | SMSTORE3_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE3 | 174.19 | 28.1 | 1211.319 | 6.954 | 43.070 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1211.319 |
9 | SMSTORE4_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE4 | 174.19 | 28.1 | 1689.582 | 9.699 | 60.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1689.582 |
10 | SMSTORE4_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE4 | 174.19 | 28.1 | 1211.319 | 6.954 | 43.070 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1211.319 |
11 | LGSTORE2_LIGHTS | LTG_SCH_BASE_LPD2 | LGSTORE2 | 348.39 | 56.3 | 3338.998 | 9.584 | 59.359 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3338.998 |
12 | LGSTORE2_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | LGSTORE2 | 348.39 | 56.3 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
13 | SMSTORE5_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE5 | 174.19 | 28.1 | 1689.582 | 9.699 | 60.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1689.582 |
14 | SMSTORE5_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE5 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
15 | SMSTORE6_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE6 | 174.19 | 28.1 | 1689.582 | 9.699 | 60.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1689.582 |
16 | SMSTORE6_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE6 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
17 | SMSTORE7_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE7 | 174.19 | 28.1 | 1689.582 | 9.699 | 60.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1689.582 |
18 | SMSTORE7_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE7 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
19 | SMSTORE8_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE8 | 174.19 | 28.1 | 1689.582 | 9.699 | 60.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1689.582 |
20 | SMSTORE8_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE8 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LGSTORE1_MISCPLUG_EQUIP | TYPE1_EQUIP_SCH | LGSTORE1 | 348.39 | 56.3 | 1498.062 | 4.300 | 26.632 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1498.062 |
2 | SMSTORE1_MISCPLUG_EQUIP | TYPE1_EQUIP_SCH | SMSTORE1 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
3 | SMSTORE2_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE2 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
4 | SMSTORE3_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE3 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
5 | SMSTORE4_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE4 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
6 | LGSTORE2_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | LGSTORE2 | 348.39 | 56.3 | 1498.062 | 4.300 | 26.632 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1498.062 |
7 | SMSTORE5_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE5 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
8 | SMSTORE6_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE6 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
9 | SMSTORE7_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE7 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
10 | SMSTORE8_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE8 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.770 | 0.700 | Rough |
5 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 0.6000 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
6 | LGSTORE1_FLOOR_FFACTOR | 36 | 2 | 7 | 0.167 | 0.1408 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
7 | SMSTORE1_FLOOR_FFACTOR | 37 | 2 | 7 | 0.167 | 0.7972E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
8 | SMSTORE2_FLOOR_FFACTOR | 38 | 2 | 7 | 0.167 | 0.7972E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | SMSTORE3_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.7972E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
10 | SMSTORE4_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.7972E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
11 | LGSTORE2_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.7972E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | SMSTORE5_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.7972E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | SMSTORE6_FLOOR_FFACTOR | 43 | 2 | 7 | 0.167 | 0.7972E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | SMSTORE7_FLOOR_FFACTOR | 44 | 2 | 7 | 0.167 | 0.7972E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | SMSTORE8_FLOOR_FFACTOR | 45 | 2 | 7 | 0.167 | 0.2031 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
6 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
7 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
8 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
10 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.433 |
11 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
12 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 7.024 |
13 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
14 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.47 |
15 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
16 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.47 |
17 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
18 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.47 |
19 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
20 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.47 |
21 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
22 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.47 |
23 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
24 | ~FC_Insulation_7 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.47 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_8 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.47 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_9 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.47 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_10 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.847 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
14 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
15 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
16 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
17 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
18 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
19 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
20 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
21 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
22 | 7 | -0.34128934E-12 | 0.10473450E-14 | -0.10397207E-12 | 0.10371484E-15 |
23 | 6 | 0.30755064E-07 | 0.17217129E-09 | 0.70279215E-08 | -0.14642558E-12 |
24 | 5 | -0.20062951E-03 | 0.14545406E-05 | -0.10304618E-03 | 0.69406843E-08 |
25 | 4 | 0.30437449 | 0.69977658E-03 | 0.10408506 | -0.35305012E-04 |
26 | 3 | -7.5082928 | 0.21456968E-01 | -2.4107259 | 0.30195353E-01 |
27 | 2 | 41.668927 | 0.75582488E-01 | 15.559173 | -0.34222686 |
28 | 1 | -81.156896 | 0.33830739E-01 | -29.405205 | 1.0916426 |
29 | 0 | 46.824335 | 0.67514285E-03 | 16.285023 | |
30 | 7 | -0.30155247E-08 | -0.19705740E-14 | 0.18469307E-14 | -0.46079768E-16 |
31 | 6 | 0.40551627E-05 | 0.26926011E-08 | 0.31944497E-02 | -0.26797721E-04 |
32 | 5 | -0.28496186E-03 | 0.15923452E-05 | -0.22398486 | 0.19584477E-02 |
33 | 4 | 0.65115693E-02 | 0.72427529E-04 | 4.8338806 | -0.45306652E-01 |
34 | 3 | -0.57046066E-01 | 0.57554694E-03 | -38.045903 | 0.39892442 |
35 | 2 | 0.20237164 | 0.95689144E-03 | 116.53161 | -1.4185768 |
36 | 1 | -0.29197338 | 0.29127682E-03 | -143.93536 | 2.0495010 |
37 | 0 | 0.14232195 | 0.70641069E-05 | 60.838472 | |
38 | 7 | -0.53597813E-08 | -0.10943972E-13 | 0.15521545E-14 | -0.37274179E-16 |
39 | 6 | 0.25551035E-05 | 0.15319154E-08 | 0.31991935E-02 | -0.26837516E-04 |
40 | 5 | -0.16700335E-03 | 0.90227195E-06 | -0.22425438 | 0.19608267E-02 |
41 | 4 | 0.37302439E-02 | 0.40957222E-04 | 4.8383675 | -0.45349785E-01 |
42 | 3 | -0.32401395E-01 | 0.32489936E-03 | -38.071239 | 0.39920448 |
43 | 2 | 0.11454695 | 0.53930964E-03 | 116.58090 | -1.4192362 |
44 | 1 | -0.16500402 | 0.16380141E-03 | -143.96437 | 2.0499779 |
45 | 0 | 0.80366526E-01 | 0.39747064E-05 | 60.838472 | |
46 | 7 | -0.53597813E-08 | -0.10943972E-13 | 0.15521547E-14 | -0.37274182E-16 |
47 | 6 | 0.25551035E-05 | 0.15319154E-08 | 0.31991935E-02 | -0.26837516E-04 |
48 | 5 | -0.16700335E-03 | 0.90227195E-06 | -0.22425438 | 0.19608267E-02 |
49 | 4 | 0.37302439E-02 | 0.40957222E-04 | 4.8383675 | -0.45349785E-01 |
50 | 3 | -0.32401395E-01 | 0.32489936E-03 | -38.071239 | 0.39920448 |
51 | 2 | 0.11454695 | 0.53930964E-03 | 116.58090 | -1.4192362 |
52 | 1 | -0.16500402 | 0.16380141E-03 | -143.96437 | 2.0499779 |
53 | 0 | 0.80366526E-01 | 0.39747064E-05 | 60.838472 | |
54 | 7 | -0.53597813E-08 | -0.10943972E-13 | 0.15521549E-14 | -0.37274185E-16 |
55 | 6 | 0.25551035E-05 | 0.15319154E-08 | 0.31991935E-02 | -0.26837516E-04 |
56 | 5 | -0.16700335E-03 | 0.90227195E-06 | -0.22425438 | 0.19608267E-02 |
57 | 4 | 0.37302439E-02 | 0.40957222E-04 | 4.8383675 | -0.45349785E-01 |
58 | 3 | -0.32401395E-01 | 0.32489936E-03 | -38.071239 | 0.39920448 |
59 | 2 | 0.11454695 | 0.53930964E-03 | 116.58090 | -1.4192362 |
60 | 1 | -0.16500402 | 0.16380141E-03 | -143.96437 | 2.0499779 |
61 | 0 | 0.80366526E-01 | 0.39747064E-05 | 60.838472 | |
62 | 7 | -0.53597813E-08 | -0.10943972E-13 | 0.15521548E-14 | -0.37274183E-16 |
63 | 6 | 0.25551035E-05 | 0.15319154E-08 | 0.31991935E-02 | -0.26837516E-04 |
64 | 5 | -0.16700335E-03 | 0.90227195E-06 | -0.22425438 | 0.19608267E-02 |
65 | 4 | 0.37302439E-02 | 0.40957222E-04 | 4.8383675 | -0.45349785E-01 |
66 | 3 | -0.32401395E-01 | 0.32489936E-03 | -38.071239 | 0.39920448 |
67 | 2 | 0.11454695 | 0.53930964E-03 | 116.58090 | -1.4192362 |
68 | 1 | -0.16500402 | 0.16380141E-03 | -143.96437 | 2.0499779 |
69 | 0 | 0.80366526E-01 | 0.39747064E-05 | 60.838472 | |
70 | 7 | -0.53597813E-08 | -0.10943972E-13 | 0.15521547E-14 | -0.37274182E-16 |
71 | 6 | 0.25551035E-05 | 0.15319154E-08 | 0.31991935E-02 | -0.26837516E-04 |
72 | 5 | -0.16700335E-03 | 0.90227195E-06 | -0.22425438 | 0.19608267E-02 |
73 | 4 | 0.37302439E-02 | 0.40957222E-04 | 4.8383675 | -0.45349785E-01 |
74 | 3 | -0.32401395E-01 | 0.32489936E-03 | -38.071239 | 0.39920448 |
75 | 2 | 0.11454695 | 0.53930964E-03 | 116.58090 | -1.4192362 |
76 | 1 | -0.16500402 | 0.16380141E-03 | -143.96437 | 2.0499779 |
77 | 0 | 0.80366526E-01 | 0.39747064E-05 | 60.838472 | |
78 | 7 | -0.53597813E-08 | -0.10943972E-13 | 0.15521547E-14 | -0.37274181E-16 |
79 | 6 | 0.25551035E-05 | 0.15319154E-08 | 0.31991935E-02 | -0.26837516E-04 |
80 | 5 | -0.16700335E-03 | 0.90227195E-06 | -0.22425438 | 0.19608267E-02 |
81 | 4 | 0.37302439E-02 | 0.40957222E-04 | 4.8383675 | -0.45349785E-01 |
82 | 3 | -0.32401395E-01 | 0.32489936E-03 | -38.071239 | 0.39920448 |
83 | 2 | 0.11454695 | 0.53930964E-03 | 116.58090 | -1.4192362 |
84 | 1 | -0.16500402 | 0.16380141E-03 | -143.96437 | 2.0499779 |
85 | 0 | 0.80366526E-01 | 0.39747064E-05 | 60.838472 | |
86 | 7 | -0.53597813E-08 | -0.10943972E-13 | 0.15521545E-14 | -0.37274179E-16 |
87 | 6 | 0.25551035E-05 | 0.15319154E-08 | 0.31991935E-02 | -0.26837516E-04 |
88 | 5 | -0.16700335E-03 | 0.90227195E-06 | -0.22425438 | 0.19608267E-02 |
89 | 4 | 0.37302439E-02 | 0.40957222E-04 | 4.8383675 | -0.45349785E-01 |
90 | 3 | -0.32401395E-01 | 0.32489936E-03 | -38.071239 | 0.39920448 |
91 | 2 | 0.11454695 | 0.53930964E-03 | 116.58090 | -1.4192362 |
92 | 1 | -0.16500402 | 0.16380141E-03 | -143.96437 | 2.0499779 |
93 | 0 | 0.80366526E-01 | 0.39747064E-05 | 60.838472 | |
94 | 7 | -0.53597813E-08 | -0.10943972E-13 | 0.15521547E-14 | -0.37274182E-16 |
95 | 6 | 0.25551035E-05 | 0.15319154E-08 | 0.31991935E-02 | -0.26837516E-04 |
96 | 5 | -0.16700335E-03 | 0.90227195E-06 | -0.22425438 | 0.19608267E-02 |
97 | 4 | 0.37302439E-02 | 0.40957222E-04 | 4.8383675 | -0.45349785E-01 |
98 | 3 | -0.32401395E-01 | 0.32489936E-03 | -38.071239 | 0.39920448 |
99 | 2 | 0.11454695 | 0.53930964E-03 | 116.58090 | -1.4192362 |
100 | 1 | -0.16500402 | 0.16380141E-03 | -143.96437 | 2.0499779 |
101 | 0 | 0.80366526E-01 | 0.39747064E-05 | 60.838472 | |
102 | 7 | -0.20778300E-08 | -0.65167512E-15 | 0.79548166E-14 | -0.12010680E-15 |
103 | 6 | 0.57088823E-05 | 0.38884884E-08 | 0.31895855E-02 | -0.26756916E-04 |
104 | 5 | -0.40892418E-03 | 0.23023551E-05 | -0.22370841 | 0.19560076E-02 |
105 | 4 | 0.93961169E-02 | 0.10478953E-03 | 4.8292766 | -0.45262394E-01 |
106 | 3 | -0.82481111E-01 | 0.83319714E-03 | -38.019897 | 0.39863696 |
107 | 2 | 0.29283299 | 0.13859693E-02 | 116.48099 | -1.4178998 |
108 | 1 | -0.42263540 | 0.42218679E-03 | -143.90557 | 2.0490113 |
109 | 0 | 0.20604930 | 0.10232106E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.362_SHGC_0.359 | 35 | 1 | VerySmooth | 2.057 | 2.057 | 1.000 | 0.360 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 3.63679E-002 | 0.27216 | 0.52074 | 0.52074 | 0.39490 | 0.13813 | 0.18098 | 0.00000 | 0.84000 | 0.84000 | 0.11599 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | GAS TANK1 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
2 | WaterHeater:Mixed | GAS TANK2 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
3 | WaterHeater:Mixed | GAS TANK3 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
4 | WaterHeater:Mixed | GAS TANK4 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
5 | WaterHeater:Mixed | GAS TANK5 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
6 | WaterHeater:Mixed | GAS TANK6 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
7 | WaterHeater:Mixed | GAS TANK7 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | LGSTORE1_WALL_2 | 0 | 118.41 | 56.08 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
2 | LGSTORE1_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
3 | LGSTORE1_WALL_3_DOOR_1 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
4 | LGSTORE1_WALL_3_DOOR_2 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
5 | LGSTORE1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
6 | LGSTORE1_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
7 | LGSTORE1_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
8 | LGSTORE1_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
9 | LGSTORE1_WALL_1_WINDOW_3 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
10 | LGSTORE1_WALL_1_WINDOW_4 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
11 | LGSTORE1_WALL_1_DOOR_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 1 | No | No |
12 | LGSTORE1_WALL_1_DOOR_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 1 | No | No |
13 | LGSTORE1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
14 | LGSTORE1_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
15 | LGSTORE1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
16 | SMSTORE1_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
17 | SMSTORE1_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
18 | SMSTORE1_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
19 | SMSTORE1_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
20 | SMSTORE1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
21 | SMSTORE1_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
22 | SMSTORE1_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
23 | SMSTORE1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
24 | SMSTORE1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
25 | SMSTORE1_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
26 | SMSTORE1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
27 | SMSTORE2_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
28 | SMSTORE2_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
29 | SMSTORE2_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
30 | SMSTORE2_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
31 | SMSTORE2_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
32 | SMSTORE2_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
33 | SMSTORE2_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
34 | SMSTORE2_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
35 | SMSTORE2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
36 | SMSTORE2_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
37 | SMSTORE2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
38 | SMSTORE3_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
39 | SMSTORE3_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
40 | SMSTORE3_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
41 | SMSTORE3_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
42 | SMSTORE3_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
43 | SMSTORE3_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
44 | SMSTORE3_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
45 | SMSTORE3_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
46 | SMSTORE3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
47 | SMSTORE3_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
48 | SMSTORE3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
49 | SMSTORE4_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
50 | SMSTORE4_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
51 | SMSTORE4_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
52 | SMSTORE4_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
53 | SMSTORE4_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
54 | SMSTORE4_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 3 | No | No |
55 | SMSTORE4_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
56 | SMSTORE4_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
57 | SMSTORE4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
58 | SMSTORE4_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
59 | SMSTORE4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
60 | LGSTORE2_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
61 | LGSTORE2_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 4 | No | No |
62 | LGSTORE2_WALL_3_DOOR_1 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
63 | LGSTORE2_WALL_3_DOOR_2 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
64 | LGSTORE2_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
65 | LGSTORE2_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 4 | No | No |
66 | LGSTORE2_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
67 | LGSTORE2_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
68 | LGSTORE2_WALL_1_WINDOW_3 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
69 | LGSTORE2_WALL_1_WINDOW_4 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
70 | LGSTORE2_WALL_1_DOOR_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
71 | LGSTORE2_WALL_1_DOOR_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
72 | LGSTORE2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
73 | LGSTORE2_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
74 | LGSTORE2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
75 | SMSTORE5_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
76 | SMSTORE5_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
77 | SMSTORE5_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
78 | SMSTORE5_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
79 | SMSTORE5_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
80 | SMSTORE5_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
81 | SMSTORE5_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
82 | SMSTORE5_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
83 | SMSTORE5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
84 | SMSTORE5_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
85 | SMSTORE5_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
86 | SMSTORE6_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
87 | SMSTORE6_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
88 | SMSTORE6_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
89 | SMSTORE6_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
90 | SMSTORE6_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
91 | SMSTORE6_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
92 | SMSTORE6_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
93 | SMSTORE6_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
94 | SMSTORE6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
95 | SMSTORE6_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
96 | SMSTORE6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
97 | SMSTORE7_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
98 | SMSTORE7_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
99 | SMSTORE7_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
100 | SMSTORE7_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
101 | SMSTORE7_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
102 | SMSTORE7_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 3 | No | No |
103 | SMSTORE7_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
104 | SMSTORE7_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
105 | SMSTORE7_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
106 | SMSTORE7_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
107 | SMSTORE7_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
108 | SMSTORE8_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 4 | No | No |
109 | SMSTORE8_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 2 | No | No |
110 | SMSTORE8_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 2 | No | No |
111 | SMSTORE8_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 1 | No | No |
112 | SMSTORE8_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
113 | SMSTORE8_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 3 | No | No |
114 | SMSTORE8_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
115 | SMSTORE8_WALL_4 | 0 | 118.41 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 3 | No | No |
116 | SMSTORE8_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
117 | SMSTORE8_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
118 | SMSTORE8_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | LGSTORE1_INFILTRATION | TYPE1_INFIL_SCH | LGSTORE1 | 348.39 | 56.3 | 0.157 | 4.517E-004 | 2.488E-004 | 0.314 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | LGSTORE1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LGSTORE1 | 348.39 | 56.3 | 0.241 | 6.922E-004 | 3.813E-004 | 0.481 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | SMSTORE1_INFILTRATION | TYPE1_INFIL_SCH | SMSTORE1 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | SMSTORE1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE1 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | SMSTORE2_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE2 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | SMSTORE2_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE2 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | SMSTORE3_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE3 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | SMSTORE3_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE3 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | SMSTORE4_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE4 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | SMSTORE4_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE4 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | LGSTORE2_INFILTRATION | TYPE3_INFIL_SCH | LGSTORE2 | 348.39 | 56.3 | 8.993E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | LGSTORE2_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LGSTORE2 | 348.39 | 56.3 | 0.241 | 6.922E-004 | 4.692E-004 | 0.481 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | SMSTORE5_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE5 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | SMSTORE5_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE5 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | SMSTORE6_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE6 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | SMSTORE6_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE6 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | SMSTORE7_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE7 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
18 | SMSTORE7_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE7 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | SMSTORE8_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE8 | 174.19 | 28.1 | 0.112 | 6.453E-004 | 2.994E-004 | 0.448 | 0.000 | 0.000 | 0.224 | 0.000 |
20 | SMSTORE8_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE8 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 3.583E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | LGSTORE1 | Mixing/Well-Stirred |
2 | SMSTORE1 | Mixing/Well-Stirred |
3 | SMSTORE2 | Mixing/Well-Stirred |
4 | SMSTORE3 | Mixing/Well-Stirred |
5 | SMSTORE4 | Mixing/Well-Stirred |
6 | LGSTORE2 | Mixing/Well-Stirred |
7 | SMSTORE5 | Mixing/Well-Stirred |
8 | SMSTORE6 | Mixing/Well-Stirred |
9 | SMSTORE7 | Mixing/Well-Stirred |
10 | SMSTORE8 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone LGSTORE1 | 1.2000 |
3 | Zone SMSTORE1 | 1.2000 |
4 | Zone SMSTORE2 | 1.2000 |
5 | Zone SMSTORE3 | 1.2000 |
6 | Zone SMSTORE4 | 1.2000 |
7 | Zone LGSTORE2 | 1.2000 |
8 | Zone SMSTORE5 | 1.2000 |
9 | Zone SMSTORE6 | 1.2000 |
10 | Zone SMSTORE7 | 1.2000 |
11 | Zone SMSTORE8 | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone LGSTORE1 | 1.2000 |
3 | Zone SMSTORE1 | 1.2000 |
4 | Zone SMSTORE2 | 1.2000 |
5 | Zone SMSTORE3 | 1.2000 |
6 | Zone SMSTORE4 | 1.2000 |
7 | Zone LGSTORE2 | 1.2000 |
8 | Zone SMSTORE5 | 1.2000 |
9 | Zone SMSTORE6 | 1.2000 |
10 | Zone SMSTORE7 | 1.2000 |
11 | Zone SMSTORE8 | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | LGSTORE1 | Cooling | 20947.97307 | 25137.56768 | 1.55945 | 1.87133 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | 29.40000 | 8.82150E-003 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
2 | LGSTORE1 | Heating | 19254.70931 | 23105.65117 | 0.84200 | 1.01040 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -4.20000 | 2.69032E-003 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
3 | SMSTORE1 | Cooling | 11395.10329 | 13674.12395 | 0.82362 | 0.98834 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 25.44800 | 8.81519E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
4 | SMSTORE1 | Heating | 8922.57146 | 10707.08575 | 0.39018 | 0.46822 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -4.20000 | 2.69032E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
5 | SMSTORE2 | Cooling | 11441.03215 | 13729.23858 | 0.85171 | 1.02205 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 29.31333 | 8.82136E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
6 | SMSTORE2 | Heating | 9029.08703 | 10834.90443 | 0.39484 | 0.47381 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -4.20000 | 2.69032E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
7 | SMSTORE3 | Cooling | 11479.40605 | 13775.28726 | 0.85456 | 1.02548 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 29.31333 | 8.82136E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
8 | SMSTORE3 | Heating | 9126.46121 | 10951.75345 | 0.39910 | 0.47892 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -4.20000 | 2.69032E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
9 | SMSTORE4 | Cooling | 11366.54776 | 13639.85731 | 0.84616 | 1.01540 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 29.31333 | 8.82136E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
10 | SMSTORE4 | Heating | 9300.79904 | 11160.95885 | 0.40672 | 0.48807 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -4.20000 | 2.69032E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
11 | LGSTORE2 | Cooling | 19958.81527 | 23950.57833 | 1.48581 | 1.78297 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 29.31333 | 8.82136E-003 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
12 | LGSTORE2 | Heating | 18046.60661 | 21655.92793 | 0.78918 | 0.94702 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -4.20000 | 2.69032E-003 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
13 | SMSTORE5 | Cooling | 10493.68654 | 12592.42385 | 0.75670 | 0.90804 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 25.44800 | 8.81519E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
14 | SMSTORE5 | Heating | 9601.99433 | 11522.39319 | 0.41990 | 0.50387 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -4.20000 | 2.69032E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
15 | SMSTORE6 | Cooling | 10419.52541 | 12503.43050 | 0.75117 | 0.90141 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 25.44800 | 8.81519E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
16 | SMSTORE6 | Heating | 9604.32544 | 11525.19053 | 0.42000 | 0.50400 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -4.20000 | 2.69032E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
17 | SMSTORE7 | Cooling | 10298.57771 | 12358.29326 | 0.74215 | 0.89059 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 25.44800 | 8.81519E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
18 | SMSTORE7 | Heating | 9888.13705 | 11865.76446 | 0.43241 | 0.51889 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -4.20000 | 2.69032E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
19 | SMSTORE8 | Cooling | 10879.85394 | 13055.82473 | 0.78545 | 0.94254 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 25.44800 | 8.81519E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
20 | SMSTORE8 | Heating | 12221.13513 | 14665.36216 | 0.53441 | 0.64129 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -4.20000 | 2.69032E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC_1:1 | Cooling | Sensible | 27454.14 | 1.87133 | 1.87133 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
2 | PSZ-AC_1:1 | Heating | Sensible | 35189.62 | 1.01040 | 1.01040 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
3 | PSZ-AC_2:2 | Cooling | Sensible | 14795.30 | 1.01643 | 1.01643 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
4 | PSZ-AC_2:2 | Heating | Sensible | 16761.45 | 0.46822 | 0.46822 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
5 | PSZ-AC_3:3 | Cooling | Sensible | 14867.30 | 1.02205 | 1.02205 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
6 | PSZ-AC_3:3 | Heating | Sensible | 16887.41 | 0.47381 | 0.47381 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
7 | PSZ-AC_4:4 | Cooling | Sensible | 14911.90 | 1.02548 | 1.02548 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
8 | PSZ-AC_4:4 | Heating | Sensible | 17002.56 | 0.47892 | 0.47892 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
9 | PSZ-AC_5:5 | Cooling | Sensible | 14778.85 | 1.01540 | 1.01540 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
10 | PSZ-AC_5:5 | Heating | Sensible | 17208.72 | 0.48807 | 0.48807 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
11 | PSZ-AC_6:6 | Cooling | Sensible | 26275.78 | 1.78297 | 1.78297 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
12 | PSZ-AC_6:6 | Heating | Sensible | 33761.22 | 0.94702 | 0.94702 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
13 | PSZ-AC_7:7 | Cooling | Sensible | 13510.86 | 0.91955 | 0.91955 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
14 | PSZ-AC_7:7 | Heating | Sensible | 17564.89 | 0.50387 | 0.50387 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
15 | PSZ-AC_8:8 | Cooling | Sensible | 13423.89 | 0.91303 | 0.91303 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
16 | PSZ-AC_8:8 | Heating | Sensible | 17567.65 | 0.50400 | 0.50400 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
17 | PSZ-AC_9:9 | Cooling | Sensible | 13342.80 | 0.90686 | 0.90686 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
18 | PSZ-AC_9:9 | Heating | Sensible | 17903.26 | 0.51889 | 0.51889 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
19 | PSZ-AC_10:10 | Cooling | Sensible | 13987.42 | 0.96473 | 0.96473 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
20 | PSZ-AC_10:10 | Heating | Sensible | 20661.90 | 0.64129 | 0.64129 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | LGSTORE1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.87133 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.98834 |
3 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.02205 |
4 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.02548 |
5 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE4 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.01540 |
6 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | LGSTORE2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.78297 |
7 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE5 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.90804 |
8 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.90141 |
9 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE7 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.89059 |
10 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE8 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.94254 |
11 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.87133 |
12 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.87133 |
13 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.87133 |
14 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.87133 |
15 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.87133 |
16 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Main Design Air Flow Rate [m3/s] | 1.87133 |
17 | AirLoopHVAC | PSZ-AC_1:1 | User Heating Air Flow Ratio [] | 1.00000 |
18 | AirLoopHVAC | PSZ-AC_1:1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
19 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.98834 |
20 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.98834 |
21 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.98834 |
22 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.98834 |
23 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.01643 |
24 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Main Design Air Flow Rate [m3/s] | 1.01643 |
25 | AirLoopHVAC | PSZ-AC_2:2 | User Heating Air Flow Ratio [] | 1.00000 |
26 | AirLoopHVAC | PSZ-AC_2:2 | Calculated Heating Air Flow Ratio [] | 0.97236 |
27 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.02205 |
28 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.02205 |
29 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.02205 |
30 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.02205 |
31 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.02205 |
32 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Main Design Air Flow Rate [m3/s] | 1.02205 |
33 | AirLoopHVAC | PSZ-AC_3:3 | User Heating Air Flow Ratio [] | 1.00000 |
34 | AirLoopHVAC | PSZ-AC_3:3 | Calculated Heating Air Flow Ratio [] | 1.00000 |
35 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.02548 |
36 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.02548 |
37 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.02548 |
38 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.02548 |
39 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.02548 |
40 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Main Design Air Flow Rate [m3/s] | 1.02548 |
41 | AirLoopHVAC | PSZ-AC_4:4 | User Heating Air Flow Ratio [] | 1.00000 |
42 | AirLoopHVAC | PSZ-AC_4:4 | Calculated Heating Air Flow Ratio [] | 1.00000 |
43 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.01540 |
44 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.01540 |
45 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.01540 |
46 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.01540 |
47 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.01540 |
48 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Main Design Air Flow Rate [m3/s] | 1.01540 |
49 | AirLoopHVAC | PSZ-AC_5:5 | User Heating Air Flow Ratio [] | 1.00000 |
50 | AirLoopHVAC | PSZ-AC_5:5 | Calculated Heating Air Flow Ratio [] | 1.00000 |
51 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.78297 |
52 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.78297 |
53 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.78297 |
54 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.78297 |
55 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.78297 |
56 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Main Design Air Flow Rate [m3/s] | 1.78297 |
57 | AirLoopHVAC | PSZ-AC_6:6 | User Heating Air Flow Ratio [] | 1.00000 |
58 | AirLoopHVAC | PSZ-AC_6:6 | Calculated Heating Air Flow Ratio [] | 1.00000 |
59 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.90804 |
60 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.90804 |
61 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.90804 |
62 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.90804 |
63 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.91955 |
64 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Main Design Air Flow Rate [m3/s] | 0.91955 |
65 | AirLoopHVAC | PSZ-AC_7:7 | User Heating Air Flow Ratio [] | 1.00000 |
66 | AirLoopHVAC | PSZ-AC_7:7 | Calculated Heating Air Flow Ratio [] | 0.98748 |
67 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.90141 |
68 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.90141 |
69 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.90141 |
70 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.90141 |
71 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.91303 |
72 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Main Design Air Flow Rate [m3/s] | 0.91303 |
73 | AirLoopHVAC | PSZ-AC_8:8 | User Heating Air Flow Ratio [] | 1.00000 |
74 | AirLoopHVAC | PSZ-AC_8:8 | Calculated Heating Air Flow Ratio [] | 0.98727 |
75 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.89059 |
76 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.89059 |
77 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.89059 |
78 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.89059 |
79 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.90686 |
80 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Main Design Air Flow Rate [m3/s] | 0.90686 |
81 | AirLoopHVAC | PSZ-AC_9:9 | User Heating Air Flow Ratio [] | 1.00000 |
82 | AirLoopHVAC | PSZ-AC_9:9 | Calculated Heating Air Flow Ratio [] | 0.98206 |
83 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.94254 |
84 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.94254 |
85 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.94254 |
86 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.94254 |
87 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.96473 |
88 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Main Design Air Flow Rate [m3/s] | 0.96473 |
89 | AirLoopHVAC | PSZ-AC_10:10 | User Heating Air Flow Ratio [] | 1.00000 |
90 | AirLoopHVAC | PSZ-AC_10:10 | Calculated Heating Air Flow Ratio [] | 0.97700 |
91 | AirLoopHVAC | PSZ-AC_1:1 | Design Supply Air Flow Rate [m3/s] | 1.87133 |
92 | AirLoopHVAC | PSZ-AC_2:2 | Design Supply Air Flow Rate [m3/s] | 1.01643 |
93 | AirLoopHVAC | PSZ-AC_3:3 | Design Supply Air Flow Rate [m3/s] | 1.02205 |
94 | AirLoopHVAC | PSZ-AC_4:4 | Design Supply Air Flow Rate [m3/s] | 1.02548 |
95 | AirLoopHVAC | PSZ-AC_5:5 | Design Supply Air Flow Rate [m3/s] | 1.01540 |
96 | AirLoopHVAC | PSZ-AC_6:6 | Design Supply Air Flow Rate [m3/s] | 1.78297 |
97 | AirLoopHVAC | PSZ-AC_7:7 | Design Supply Air Flow Rate [m3/s] | 0.91955 |
98 | AirLoopHVAC | PSZ-AC_8:8 | Design Supply Air Flow Rate [m3/s] | 0.91303 |
99 | AirLoopHVAC | PSZ-AC_9:9 | Design Supply Air Flow Rate [m3/s] | 0.90686 |
100 | AirLoopHVAC | PSZ-AC_10:10 | Design Supply Air Flow Rate [m3/s] | 0.96473 |
101 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.87133 |
102 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41148 |
103 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.87133 |
104 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 2002.41611 |
105 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.87133 |
106 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.87133 |
107 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.87133 |
108 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.23508 |
109 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.87133 |
110 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.93567 |
111 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.24755 |
112 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 32747.32000 |
113 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 16373.66000 |
114 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80078 |
115 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80078 |
116 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 32747.32000 |
117 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 54590.69844 |
118 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
119 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
120 | Coil:Heating:Fuel | PSZ-AC_1:1 HEATING COIL | Design Size Nominal Capacity [W] | 54590.69844 |
121 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.01643 |
122 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
123 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.01643 |
124 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1125.35374 |
125 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.01643 |
126 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.01643 |
127 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.01643 |
128 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.01643 |
129 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.01643 |
130 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.50822 |
131 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.67762 |
132 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 17617.94000 |
133 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 8808.97000 |
134 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80012 |
135 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80012 |
136 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 17617.94000 |
137 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 28482.13642 |
138 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
139 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
140 | Coil:Heating:Fuel | PSZ-AC_2:2 HEATING COIL | Design Size Nominal Capacity [W] | 28482.13642 |
141 | Controller:OutdoorAir | PSZ-AC_3:3_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.02205 |
142 | Controller:OutdoorAir | PSZ-AC_3:3_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
143 | Fan:SystemModel | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.02205 |
144 | Fan:SystemModel | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1131.57104 |
145 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.02205 |
146 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.02205 |
147 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.02205 |
148 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.02205 |
149 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.02205 |
150 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.51102 |
151 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.68137 |
152 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 17704.74000 |
153 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 8852.37000 |
154 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80033 |
155 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80033 |
156 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 17704.74000 |
157 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 29241.70830 |
158 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
159 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
160 | Coil:Heating:Fuel | PSZ-AC_3:3 HEATING COIL | Design Size Nominal Capacity [W] | 29241.70830 |
161 | Controller:OutdoorAir | PSZ-AC_4:4_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.02548 |
162 | Controller:OutdoorAir | PSZ-AC_4:4_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
163 | Fan:SystemModel | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.02548 |
164 | Fan:SystemModel | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1135.36638 |
165 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.02548 |
166 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.02548 |
167 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.02548 |
168 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.02548 |
169 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.02548 |
170 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.51274 |
171 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.68365 |
172 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 17757.61000 |
173 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 8878.80500 |
174 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80046 |
175 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80046 |
176 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 17757.61000 |
177 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 29318.95527 |
178 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
179 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
180 | Coil:Heating:Fuel | PSZ-AC_4:4 HEATING COIL | Design Size Nominal Capacity [W] | 29318.95527 |
181 | Controller:OutdoorAir | PSZ-AC_5:5_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.01540 |
182 | Controller:OutdoorAir | PSZ-AC_5:5_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
183 | Fan:SystemModel | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.01540 |
184 | Fan:SystemModel | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1124.20409 |
185 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.01540 |
186 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.01540 |
187 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.01540 |
188 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.01540 |
189 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.01540 |
190 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.50770 |
191 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.67693 |
192 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 17602.36000 |
193 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 8801.18000 |
194 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80007 |
195 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80007 |
196 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 17602.36000 |
197 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 29091.75475 |
198 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
199 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
200 | Coil:Heating:Fuel | PSZ-AC_5:5 HEATING COIL | Design Size Nominal Capacity [W] | 29091.75475 |
201 | Controller:OutdoorAir | PSZ-AC_6:6_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.78297 |
202 | Controller:OutdoorAir | PSZ-AC_6:6_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41148 |
203 | Fan:SystemModel | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.78297 |
204 | Fan:SystemModel | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1907.86524 |
205 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.78297 |
206 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.78297 |
207 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.78297 |
208 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.17676 |
209 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.78297 |
210 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.89149 |
211 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.18865 |
212 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 31389.77000 |
213 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 15694.88500 |
214 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80069 |
215 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80069 |
216 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 31389.77000 |
217 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 52598.82248 |
218 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
219 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
220 | Coil:Heating:Fuel | PSZ-AC_6:6 HEATING COIL | Design Size Nominal Capacity [W] | 52598.82248 |
221 | Controller:OutdoorAir | PSZ-AC_7:7_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.91955 |
222 | Controller:OutdoorAir | PSZ-AC_7:7_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
223 | Fan:SystemModel | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.91955 |
224 | Fan:SystemModel | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1018.08411 |
225 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.91955 |
226 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.91955 |
227 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.91955 |
228 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.91955 |
229 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.91955 |
230 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.45977 |
231 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.61303 |
232 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 16122.53000 |
233 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 8061.26500 |
234 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80011 |
235 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80011 |
236 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 16122.53000 |
237 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 26672.47838 |
238 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
239 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
240 | Coil:Heating:Fuel | PSZ-AC_7:7 HEATING COIL | Design Size Nominal Capacity [W] | 26672.47838 |
241 | Controller:OutdoorAir | PSZ-AC_8:8_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.91303 |
242 | Controller:OutdoorAir | PSZ-AC_8:8_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
243 | Fan:SystemModel | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.91303 |
244 | Fan:SystemModel | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1010.86644 |
245 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.91303 |
246 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.91303 |
247 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.91303 |
248 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.91303 |
249 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.91303 |
250 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.45651 |
251 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.60869 |
252 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 16021.69000 |
253 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 8010.84500 |
254 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80082 |
255 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80082 |
256 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 16021.69000 |
257 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 26523.05046 |
258 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
259 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
260 | Coil:Heating:Fuel | PSZ-AC_8:8 HEATING COIL | Design Size Nominal Capacity [W] | 26523.05046 |
261 | Controller:OutdoorAir | PSZ-AC_9:9_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.90686 |
262 | Controller:OutdoorAir | PSZ-AC_9:9_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
263 | Fan:SystemModel | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.90686 |
264 | Fan:SystemModel | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1004.03362 |
265 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.90686 |
266 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.90686 |
267 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.90686 |
268 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.90686 |
269 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.90686 |
270 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.45343 |
271 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.60457 |
272 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 15925.99000 |
273 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 7962.99500 |
274 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80055 |
275 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80055 |
276 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 15925.99000 |
277 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 26279.21799 |
278 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
279 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
280 | Coil:Heating:Fuel | PSZ-AC_9:9 HEATING COIL | Design Size Nominal Capacity [W] | 26279.21799 |
281 | Controller:OutdoorAir | PSZ-AC_10:10_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.96473 |
282 | Controller:OutdoorAir | PSZ-AC_10:10_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
283 | Fan:SystemModel | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.96473 |
284 | Fan:SystemModel | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1068.10692 |
285 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.96473 |
286 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.96473 |
287 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.96473 |
288 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.96473 |
289 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.96473 |
290 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.48236 |
291 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.64315 |
292 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 16684.32000 |
293 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 8342.16000 |
294 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80091 |
295 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80091 |
296 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 16684.32000 |
297 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 27450.62228 |
298 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
299 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
300 | Coil:Heating:Fuel | PSZ-AC_10:10 HEATING COIL | Design Size Nominal Capacity [W] | 27450.62228 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | 31279.6 | 11.24 | 11.24 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | 16820.9 | 11.96 | 11.96 | |||
3 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | 16903.3 | 11.95 | 11.95 | |||
4 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | 16953.4 | 11.95 | 11.95 | |||
5 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | 16806.1 | 11.96 | 11.96 | |||
6 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | 29991.3 | 11.25 | 11.25 | |||
7 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | 15401.3 | 11.99 | 11.99 | |||
8 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | 15305.6 | 11.99 | 11.99 | |||
9 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | 15214.7 | 11.99 | 11.99 | |||
10 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | 15927.8 | 11.95 | 11.95 |
Zone Name | # Surfaces | |
1 | LGSTORE1 | 15 |
2 | SMSTORE1 | 11 |
3 | SMSTORE2 | 11 |
4 | SMSTORE3 | 11 |
5 | SMSTORE4 | 11 |
6 | LGSTORE2 | 15 |
7 | SMSTORE5 | 11 |
8 | SMSTORE6 | 11 |
9 | SMSTORE7 | 11 |
10 | SMSTORE8 | 11 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | LGSTORE1_WALL_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.600 | 0.551 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | LGSTORE1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.600 | 0.551 | 71.15 | 78.94 | 71.15 | 0.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | LGSTORE1_WALL_3_DOOR_1 | Door | LGSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
4 | LGSTORE1_WALL_3_DOOR_2 | Door | LGSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
5 | LGSTORE1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
6 | LGSTORE1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.600 | 0.551 | 58.18 | 78.94 | 58.18 | 180.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
7 | LGSTORE1_WALL_1_WINDOW_1 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.362_SHGC_0.359 | N/A | 2.057 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
8 | LGSTORE1_WALL_1_WINDOW_2 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.362_SHGC_0.359 | N/A | 2.057 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
9 | LGSTORE1_WALL_1_WINDOW_3 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.362_SHGC_0.359 | N/A | 2.057 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
10 | LGSTORE1_WALL_1_WINDOW_4 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.362_SHGC_0.359 | N/A | 2.057 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
11 | LGSTORE1_WALL_1_DOOR_1 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.362_SHGC_0.359 | N/A | 2.057 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
12 | LGSTORE1_WALL_1_DOOR_2 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.362_SHGC_0.359 | N/A | 2.057 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
13 | LGSTORE1_FLOOR | Floor | CTF - ConductionTransferFunction | LGSTORE1_FLOOR_FFACTOR | 0.141 | 0.136 | 348.39 | 348.39 | 348.39 | 270.00 | 180.00 | 22.86 | 15.24 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | LGSTORE1_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 348.39 | 348.39 | 348.39 | 270.00 | 0.00 | 22.86 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
15 | LGSTORE1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 696.77 | 696.77 | 696.77 | 0.00 | 90.00 | 696.77 | 1.00 | 0.00 | LGSTORE1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
16 | SMSTORE1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.600 | 0.551 | 29.09 | 39.47 | 29.09 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
17 | SMSTORE1_WALL_1_WINDOW_1 | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.362_SHGC_0.359 | N/A | 2.057 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
18 | SMSTORE1_WALL_1_WINDOW_2 | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.362_SHGC_0.359 | N/A | 2.057 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
19 | SMSTORE1_WALL_1_DOOR | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.362_SHGC_0.359 | N/A | 2.057 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
20 | SMSTORE1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | SMSTORE1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.600 | 0.551 | 35.57 | 39.47 | 35.57 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | SMSTORE1_WALL_3_DOOR | Door | SMSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
23 | SMSTORE1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE2_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | SMSTORE1_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE1_FLOOR_FFACTOR | 7.972E-002 | 7.821E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | SMSTORE1_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
26 | SMSTORE1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
27 | SMSTORE2_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.600 | 0.551 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | SMSTORE2_WALL_1_WINDOW_1 | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.362_SHGC_0.359 | N/A | 2.057 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
29 | SMSTORE2_WALL_1_WINDOW_2 | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.362_SHGC_0.359 | N/A | 2.057 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
30 | SMSTORE2_WALL_1_DOOR | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.362_SHGC_0.359 | N/A | 2.057 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
31 | SMSTORE2_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | SMSTORE2_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.600 | 0.551 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | SMSTORE2_WALL_3_DOOR | Door | SMSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
34 | SMSTORE2_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE3_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | SMSTORE2_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE2_FLOOR_FFACTOR | 7.972E-002 | 7.821E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | SMSTORE2_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | SMSTORE2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | SMSTORE3_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.600 | 0.551 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | SMSTORE3_WALL_1_WINDOW_1 | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.362_SHGC_0.359 | N/A | 2.057 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
40 | SMSTORE3_WALL_1_WINDOW_2 | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.362_SHGC_0.359 | N/A | 2.057 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
41 | SMSTORE3_WALL_1_DOOR | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.362_SHGC_0.359 | N/A | 2.057 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
42 | SMSTORE3_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE2_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | SMSTORE3_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.600 | 0.551 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | SMSTORE3_WALL_3_DOOR | Door | SMSTORE3_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
45 | SMSTORE3_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE4_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | SMSTORE3_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE3_FLOOR_FFACTOR | 7.972E-002 | 7.821E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
47 | SMSTORE3_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
48 | SMSTORE3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
49 | SMSTORE4_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.600 | 0.551 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | SMSTORE4_WALL_1_WINDOW_1 | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.362_SHGC_0.359 | N/A | 2.057 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
51 | SMSTORE4_WALL_1_WINDOW_2 | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.362_SHGC_0.359 | N/A | 2.057 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
52 | SMSTORE4_WALL_1_DOOR | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.362_SHGC_0.359 | N/A | 2.057 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | SMSTORE4_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE3_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | SMSTORE4_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.600 | 0.551 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | SMSTORE4_WALL_3_DOOR | Door | SMSTORE4_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | SMSTORE4_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE2_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | SMSTORE4_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE4_FLOOR_FFACTOR | 7.972E-002 | 7.821E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | SMSTORE4_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | SMSTORE4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | LGSTORE2_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE4_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | LGSTORE2_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.600 | 0.551 | 71.19 | 78.94 | 71.19 | 0.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
62 | LGSTORE2_WALL_3_DOOR_1 | Door | LGSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
63 | LGSTORE2_WALL_3_DOOR_2 | Door | LGSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
64 | LGSTORE2_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE5_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LGSTORE2_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.600 | 0.551 | 58.22 | 78.94 | 58.22 | 180.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
66 | LGSTORE2_WALL_1_WINDOW_1 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.362_SHGC_0.359 | N/A | 2.057 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | LGSTORE2_WALL_1_WINDOW_2 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.362_SHGC_0.359 | N/A | 2.057 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | LGSTORE2_WALL_1_WINDOW_3 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.362_SHGC_0.359 | N/A | 2.057 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | LGSTORE2_WALL_1_WINDOW_4 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.362_SHGC_0.359 | N/A | 2.057 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LGSTORE2_WALL_1_DOOR_1 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.362_SHGC_0.359 | N/A | 2.057 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
71 | LGSTORE2_WALL_1_DOOR_2 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.362_SHGC_0.359 | N/A | 2.057 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
72 | LGSTORE2_FLOOR | Floor | CTF - ConductionTransferFunction | LGSTORE2_FLOOR_FFACTOR | 7.972E-002 | 7.821E-002 | 348.39 | 348.39 | 348.39 | 270.00 | 180.00 | 22.86 | 15.24 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
73 | LGSTORE2_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 348.39 | 348.39 | 348.39 | 270.00 | 0.00 | 22.86 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
74 | LGSTORE2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 696.77 | 696.77 | 696.77 | 0.00 | 90.00 | 696.77 | 1.00 | 0.00 | LGSTORE2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
75 | SMSTORE5_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.600 | 0.551 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | SMSTORE5_WALL_1_WINDOW_1 | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.362_SHGC_0.359 | N/A | 2.057 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
77 | SMSTORE5_WALL_1_WINDOW_2 | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.362_SHGC_0.359 | N/A | 2.057 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | SMSTORE5_WALL_1_DOOR | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.362_SHGC_0.359 | N/A | 2.057 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
79 | SMSTORE5_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE2_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | SMSTORE5_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.600 | 0.551 | 35.59 | 39.47 | 35.59 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | SMSTORE5_WALL_3_DOOR | Door | SMSTORE5_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
82 | SMSTORE5_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE6_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
83 | SMSTORE5_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE5_FLOOR_FFACTOR | 7.972E-002 | 7.821E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
84 | SMSTORE5_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
85 | SMSTORE5_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE5_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | SMSTORE6_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.600 | 0.551 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | SMSTORE6_WALL_1_WINDOW_1 | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.362_SHGC_0.359 | N/A | 2.057 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | SMSTORE6_WALL_1_WINDOW_2 | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.362_SHGC_0.359 | N/A | 2.057 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
89 | SMSTORE6_WALL_1_DOOR | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.362_SHGC_0.359 | N/A | 2.057 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | SMSTORE6_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE5_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | SMSTORE6_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.600 | 0.551 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | SMSTORE6_WALL_3_DOOR | Door | SMSTORE6_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
93 | SMSTORE6_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE7_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | SMSTORE6_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE6_FLOOR_FFACTOR | 7.972E-002 | 7.821E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
95 | SMSTORE6_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
96 | SMSTORE6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
97 | SMSTORE7_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.600 | 0.551 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | SMSTORE7_WALL_1_WINDOW_1 | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.362_SHGC_0.359 | N/A | 2.057 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | SMSTORE7_WALL_1_WINDOW_2 | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.362_SHGC_0.359 | N/A | 2.057 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
100 | SMSTORE7_WALL_1_DOOR | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.362_SHGC_0.359 | N/A | 2.057 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
101 | SMSTORE7_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE6_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
102 | SMSTORE7_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.600 | 0.551 | 35.59 | 39.47 | 35.59 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | SMSTORE7_WALL_3_DOOR | Door | SMSTORE7_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
104 | SMSTORE7_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE8_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | SMSTORE7_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE7_FLOOR_FFACTOR | 7.972E-002 | 7.821E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
106 | SMSTORE7_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
107 | SMSTORE7_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE7_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
108 | SMSTORE8_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.600 | 0.551 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | SMSTORE8_WALL_1_WINDOW_1 | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.362_SHGC_0.359 | N/A | 2.057 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
110 | SMSTORE8_WALL_1_WINDOW_2 | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.362_SHGC_0.359 | N/A | 2.057 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
111 | SMSTORE8_WALL_1_DOOR | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.362_SHGC_0.359 | N/A | 2.057 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
112 | SMSTORE8_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE7_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | SMSTORE8_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.600 | 0.551 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | SMSTORE8_WALL_3_DOOR | Door | SMSTORE8_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
115 | SMSTORE8_WALL_4 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.600 | 0.551 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | SMSTORE8_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE8_FLOOR_FFACTOR | 0.203 | 0.194 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | SMSTORE8_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | SMSTORE8_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE8_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | LGSTORE1 | RunPeriod: RUNPERIOD 1 | 3.2711389994E-002 | 0.1941760918 | Pass | Pass | 0.2309297889 | 0.9868126789 | Pass | Pass |
2 | SMSTORE1 | RunPeriod: RUNPERIOD 1 | 4.8122156360E-002 | 0.1480437674 | Pass | Pass | 8.1107026987E-002 | 0.2307653073 | Pass | Pass |
3 | SMSTORE2 | RunPeriod: RUNPERIOD 1 | 3.2516023749E-002 | 0.1813841070 | Pass | Pass | 8.9387634669E-002 | 0.3212422658 | Pass | Pass |
4 | SMSTORE3 | RunPeriod: RUNPERIOD 1 | 3.8218459213E-002 | 0.2258117982 | Pass | Pass | 8.5256036886E-002 | 0.2641705967 | Pass | Pass |
5 | SMSTORE4 | RunPeriod: RUNPERIOD 1 | 4.2488788676E-002 | 0.2437015999 | Pass | Pass | 7.8030363071E-002 | 0.3979265160 | Pass | Pass |
6 | LGSTORE2 | RunPeriod: RUNPERIOD 1 | 5.0683570299E-002 | 0.2731387345 | Pass | Pass | 3.0514201824E-002 | 9.2448265508E-002 | Pass | Pass |
7 | SMSTORE5 | RunPeriod: RUNPERIOD 1 | 5.0406185936E-002 | 0.2735826119 | Pass | Pass | 2.9004996434E-002 | 8.6412726142E-002 | Pass | Pass |
8 | SMSTORE6 | RunPeriod: RUNPERIOD 1 | 5.1500091512E-002 | 0.2761285466 | Pass | Pass | 2.8969302847E-002 | 8.7536440845E-002 | Pass | Pass |
9 | SMSTORE7 | RunPeriod: RUNPERIOD 1 | 5.6710960790E-002 | 0.2956731068 | Pass | Pass | 2.8152294197E-002 | 9.1037603112E-002 | Pass | Pass |
10 | SMSTORE8 | RunPeriod: RUNPERIOD 1 | 7.4748549440E-002 | 0.3813139627 | Pass | Pass | 2.2940132652E-002 | 7.9463942527E-002 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:31
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 3425.08 | 207.34 | 0.00 | 572.87 | 210.69 | 4415.98 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:31
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | -4.20 | 0.00 | -4.20 | Wetbulb [C] | 4.30 | 20.00 |
SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 29.40 | 10.40 | 18.30 | Wetbulb [C] | 4.20 | 350.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 22.00 | 23 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 16.00 | 20 | |||
Jul | 0.00 | 0 | |||
Aug | 24.00 | 18 | |||
Sep | 12.00 | 15 | |||
Oct | 61.00 | 41 | |||
Nov | 0.00 | 0 | |||
Dec | 45.00 | 41 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:31
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_2 | NONRES_EXT_WALL_GRD | 0.30 | 0.551 | 0.600 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE1_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.551 | 0.600 | 78.94 | 71.15 | 0.00 | 90.00 | N |
LGSTORE1_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.551 | 0.600 | 78.94 | 58.18 | 180.00 | 90.00 | S |
LGSTORE1_FLOOR | LGSTORE1_FLOOR_FFACTOR | 1.00 | 0.138 | 0.141 | 348.39 | 348.39 | 270.00 | 180.00 | |
LGSTORE1_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 348.39 | 348.39 | 270.00 | 0.00 | |
SMSTORE1_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.551 | 0.600 | 39.47 | 29.09 | 180.00 | 90.00 | S |
SMSTORE1_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.551 | 0.600 | 39.47 | 35.57 | 0.00 | 90.00 | N |
SMSTORE1_FLOOR | SMSTORE1_FLOOR_FFACTOR | 1.00 | 0.079 | 0.080 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE1_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE2_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.551 | 0.600 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE2_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.551 | 0.600 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE2_FLOOR | SMSTORE2_FLOOR_FFACTOR | 1.00 | 0.079 | 0.080 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE2_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE3_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.551 | 0.600 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE3_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.551 | 0.600 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE3_FLOOR | SMSTORE3_FLOOR_FFACTOR | 1.00 | 0.079 | 0.080 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE3_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE4_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.551 | 0.600 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE4_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.551 | 0.600 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE4_FLOOR | SMSTORE4_FLOOR_FFACTOR | 1.00 | 0.079 | 0.080 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE4_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
LGSTORE2_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.551 | 0.600 | 78.94 | 71.19 | 0.00 | 90.00 | N |
LGSTORE2_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.551 | 0.600 | 78.94 | 58.22 | 180.00 | 90.00 | S |
LGSTORE2_FLOOR | LGSTORE2_FLOOR_FFACTOR | 1.00 | 0.079 | 0.080 | 348.39 | 348.39 | 270.00 | 180.00 | |
LGSTORE2_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 348.39 | 348.39 | 270.00 | 0.00 | |
SMSTORE5_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.551 | 0.600 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE5_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.551 | 0.600 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE5_FLOOR | SMSTORE5_FLOOR_FFACTOR | 1.00 | 0.079 | 0.080 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE5_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE6_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.551 | 0.600 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE6_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.551 | 0.600 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE6_FLOOR | SMSTORE6_FLOOR_FFACTOR | 1.00 | 0.079 | 0.080 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE6_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE7_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.551 | 0.600 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE7_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.551 | 0.600 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE7_FLOOR | SMSTORE7_FLOOR_FFACTOR | 1.00 | 0.079 | 0.080 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE7_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE8_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.551 | 0.600 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE8_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.551 | 0.600 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE8_WALL_4 | NONRES_EXT_WALL_GRD | 0.30 | 0.551 | 0.600 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE8_FLOOR | SMSTORE8_FLOOR_FFACTOR | 1.00 | 0.197 | 0.203 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE8_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE1_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE2_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE2_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE3_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE3_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE4_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE4_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
LGSTORE2_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE2_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE5_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE5_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE6_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE6_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE7_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE7_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE8_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 696.77 | 0.00 | 90.00 | N | ||
SMSTORE1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
LGSTORE2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 696.77 | 0.00 | 90.00 | N | ||
SMSTORE5_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE7_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE8_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.362_SHGC_0.359 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.057 | 0.360 | 0.396 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.362_SHGC_0.359 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.057 | 0.360 | 0.396 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_3 | NONRESWINDOW_U_0.362_SHGC_0.359 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.057 | 0.360 | 0.396 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_4 | NONRESWINDOW_U_0.362_SHGC_0.359 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.057 | 0.360 | 0.396 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_DOOR_1 | NONRESWINDOW_U_0.362_SHGC_0.359 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.057 | 0.360 | 0.396 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_DOOR_2 | NONRESWINDOW_U_0.362_SHGC_0.359 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.057 | 0.360 | 0.396 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.362_SHGC_0.359 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.057 | 0.360 | 0.396 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.362_SHGC_0.359 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.057 | 0.360 | 0.396 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_DOOR | NONRESWINDOW_U_0.362_SHGC_0.359 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.057 | 0.360 | 0.396 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.362_SHGC_0.359 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.057 | 0.360 | 0.396 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.362_SHGC_0.359 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.057 | 0.360 | 0.396 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_DOOR | NONRESWINDOW_U_0.362_SHGC_0.359 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.057 | 0.360 | 0.396 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.362_SHGC_0.359 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.057 | 0.360 | 0.396 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.362_SHGC_0.359 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.057 | 0.360 | 0.396 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_DOOR | NONRESWINDOW_U_0.362_SHGC_0.359 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.057 | 0.360 | 0.396 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.362_SHGC_0.359 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.057 | 0.360 | 0.396 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.362_SHGC_0.359 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.057 | 0.360 | 0.396 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_DOOR | NONRESWINDOW_U_0.362_SHGC_0.359 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.057 | 0.360 | 0.396 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.362_SHGC_0.359 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.057 | 0.360 | 0.396 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.362_SHGC_0.359 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.057 | 0.360 | 0.396 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_3 | NONRESWINDOW_U_0.362_SHGC_0.359 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.057 | 0.360 | 0.396 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_4 | NONRESWINDOW_U_0.362_SHGC_0.359 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.057 | 0.360 | 0.396 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_DOOR_1 | NONRESWINDOW_U_0.362_SHGC_0.359 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.057 | 0.360 | 0.396 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_DOOR_2 | NONRESWINDOW_U_0.362_SHGC_0.359 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.057 | 0.360 | 0.396 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.362_SHGC_0.359 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.057 | 0.360 | 0.396 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.362_SHGC_0.359 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.057 | 0.360 | 0.396 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_DOOR | NONRESWINDOW_U_0.362_SHGC_0.359 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.057 | 0.360 | 0.396 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.362_SHGC_0.359 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.057 | 0.360 | 0.396 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.362_SHGC_0.359 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.057 | 0.360 | 0.396 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_DOOR | NONRESWINDOW_U_0.362_SHGC_0.359 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.057 | 0.360 | 0.396 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.362_SHGC_0.359 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.057 | 0.360 | 0.396 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.362_SHGC_0.359 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.057 | 0.360 | 0.396 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_DOOR | NONRESWINDOW_U_0.362_SHGC_0.359 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.057 | 0.360 | 0.396 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.362_SHGC_0.359 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.057 | 0.360 | 0.396 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.362_SHGC_0.359 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.057 | 0.360 | 0.396 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_DOOR | NONRESWINDOW_U_0.362_SHGC_0.359 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.057 | 0.360 | 0.396 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
Total or Average | 124.40 | 2.057 | 0.360 | 0.396 | |||||||||||||||||
North Total or Average | 0.00 | - | - | - | |||||||||||||||||
Non-North Total or Average | 124.40 | 2.057 | 0.360 | 0.396 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
LGSTORE1_WALL_3_DOOR_1 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.90 | LGSTORE1_WALL_3 |
LGSTORE1_WALL_3_DOOR_2 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.90 | LGSTORE1_WALL_3 |
SMSTORE1_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.90 | SMSTORE1_WALL_3 |
SMSTORE2_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE2_WALL_3 |
SMSTORE3_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE3_WALL_3 |
SMSTORE4_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE4_WALL_3 |
LGSTORE2_WALL_3_DOOR_1 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | LGSTORE2_WALL_3 |
LGSTORE2_WALL_3_DOOR_2 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | LGSTORE2_WALL_3 |
SMSTORE5_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE5_WALL_3 |
SMSTORE6_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE6_WALL_3 |
SMSTORE7_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE7_WALL_3 |
SMSTORE8_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE8_WALL_3 |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:31
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
LGSTORE1_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_DOOR_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_DOOR_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_DOOR_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_DOOR_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:31
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
LGSTORE1_LIGHTS | LGSTORE1 | LGSTORE1 | GENERAL | 9.6053 | 348.39 | 3346.35 | LightsWired | LTG_SCH_BASE_LPD1 | 83.91 | 168.00 | 82.62 | 0.0000 | Y | 51.90 |
LGSTORE1_LIGHTS_ALLOWANCE | LGSTORE1 | LGSTORE1 | GENERAL | 5.6969 | 348.39 | 1984.73 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | 97.50 | 112.00 | 94.53 | 0.0000 | Y | 35.22 |
SMSTORE1_LIGHTS | SMSTORE1 | SMSTORE1 | GENERAL | 9.7206 | 174.19 | 1693.26 | LightsWired | LTG_SCH_BASE_SMALL_LPD1 | 85.41 | 168.00 | 84.05 | 0.0000 | Y | 26.72 |
SMSTORE1_LIGHTS_ALLOWANCE | SMSTORE1 | SMSTORE1 | GENERAL | 8.5685 | 174.19 | 1492.57 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | 97.50 | 112.00 | 94.53 | 0.0000 | Y | 26.49 |
SMSTORE2_LIGHTS | SMSTORE2 | SMSTORE2 | GENERAL | 9.6995 | 174.19 | 1689.58 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 68.73 | 168.00 | 65.95 | 0.0000 | Y | 20.92 |
SMSTORE2_LIGHTS_ALLOWANCE | SMSTORE2 | SMSTORE2 | GENERAL | 6.9539 | 174.19 | 1211.32 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 84.29 | 73.25 | 0.0000 | Y | 16.66 |
SMSTORE3_LIGHTS | SMSTORE3 | SMSTORE3 | GENERAL | 9.6995 | 174.19 | 1689.58 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 68.73 | 168.00 | 65.95 | 0.0000 | Y | 20.92 |
SMSTORE3_LIGHTS_ALLOWANCE | SMSTORE3 | SMSTORE3 | GENERAL | 6.9539 | 174.19 | 1211.32 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 84.29 | 73.25 | 0.0000 | Y | 16.66 |
SMSTORE4_LIGHTS | SMSTORE4 | SMSTORE4 | GENERAL | 9.6995 | 174.19 | 1689.58 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 68.73 | 168.00 | 65.95 | 0.0000 | Y | 20.92 |
SMSTORE4_LIGHTS_ALLOWANCE | SMSTORE4 | SMSTORE4 | GENERAL | 6.9539 | 174.19 | 1211.32 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 84.29 | 73.25 | 0.0000 | Y | 16.66 |
LGSTORE2_LIGHTS | LGSTORE2 | LGSTORE2 | GENERAL | 9.5842 | 348.39 | 3339.00 | LightsWired | LTG_SCH_BASE_LPD2 | 62.11 | 168.00 | 59.29 | 0.0000 | Y | 37.16 |
LGSTORE2_LIGHTS_ALLOWANCE | LGSTORE2 | LGSTORE2 | GENERAL | 0.0000 | 348.39 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE5_LIGHTS | SMSTORE5 | SMSTORE5 | GENERAL | 9.6995 | 174.19 | 1689.58 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 60.29 | 0.0000 | Y | 19.12 |
SMSTORE5_LIGHTS_ALLOWANCE | SMSTORE5 | SMSTORE5 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE6_LIGHTS | SMSTORE6 | SMSTORE6 | GENERAL | 9.6995 | 174.19 | 1689.58 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 60.29 | 0.0000 | Y | 19.12 |
SMSTORE6_LIGHTS_ALLOWANCE | SMSTORE6 | SMSTORE6 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE7_LIGHTS | SMSTORE7 | SMSTORE7 | GENERAL | 9.6995 | 174.19 | 1689.58 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 60.29 | 0.0000 | Y | 19.12 |
SMSTORE7_LIGHTS_ALLOWANCE | SMSTORE7 | SMSTORE7 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE8_LIGHTS | SMSTORE8 | SMSTORE8 | GENERAL | 9.6995 | 174.19 | 1689.58 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 60.29 | 0.0000 | Y | 19.12 |
SMSTORE8_LIGHTS_ALLOWANCE | SMSTORE8 | SMSTORE8 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
Interior Lighting Total | 6.5342 | 4180.64 | 27316.92 | 366.68 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 455.59 | AstronomicalClock | - | 42.59 | 42.59 | 3.64 | |
EXTERIOR_LIGHTS_B | 2744.24 | AstronomicalClock | - | 83.55 | 63.07 | 32.49 | |
EXTERIOR_LIGHTS_C | 2307.23 | AstronomicalClock | - | 83.55 | 56.07 | 24.28 | |
Exterior Lighting Total | 5507.06 | 60.41 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:31
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 32747.32 | 26223.40 | 6523.92 | 0.80 | 3.80 | |||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 17617.94 | 14096.47 | 3521.47 | 0.80 | 4.12 | |||
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 17704.74 | 14169.63 | 3535.11 | 0.80 | 4.12 | |||
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 17757.61 | 14214.26 | 3543.35 | 0.80 | 4.12 | |||
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 17602.36 | 14083.12 | 3519.24 | 0.80 | 4.12 | |||
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 31389.77 | 25133.47 | 6256.30 | 0.80 | 3.80 | |||
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 16122.53 | 12899.80 | 3222.73 | 0.80 | 4.12 | |||
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 16021.69 | 12830.49 | 3191.20 | 0.80 | 4.12 | |||
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 15925.99 | 12749.55 | 3176.44 | 0.80 | 4.12 | |||
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 16684.32 | 13362.64 | 3321.68 | 0.80 | 4.12 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC_1:1 COOLING COIL | 31279.6 | 11.24 | 11.24 | ||||
PSZ-AC_2:2 COOLING COIL | 16820.9 | 11.96 | 11.96 | ||||
PSZ-AC_3:3 COOLING COIL | 16903.3 | 11.95 | 11.95 | ||||
PSZ-AC_4:4 COOLING COIL | 16953.4 | 11.95 | 11.95 | ||||
PSZ-AC_5:5 COOLING COIL | 16806.1 | 11.96 | 11.96 | ||||
PSZ-AC_6:6 COOLING COIL | 29991.3 | 11.25 | 11.25 | ||||
PSZ-AC_7:7 COOLING COIL | 15401.3 | 11.99 | 11.99 | ||||
PSZ-AC_8:8 COOLING COIL | 15305.6 | 11.99 | 11.99 | ||||
PSZ-AC_9:9 COOLING COIL | 15214.7 | 11.99 | 11.99 | ||||
PSZ-AC_10:10 COOLING COIL | 15927.8 | 11.95 | 11.95 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | 54590.70 | 0.80 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | 28482.14 | 0.80 | |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | 29241.71 | 0.80 | |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | 29318.96 | 0.80 | |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | 29091.75 | 0.80 | |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | 52598.82 | 0.80 | |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | 26672.48 | 0.80 | |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | 26523.05 | 0.80 | |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | 26279.22 | 0.80 | |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | 27450.62 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 1.87 | 2002.42 | 1070.05 | 1.00 | 1.32 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 |
PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.02 | 1125.35 | 1107.16 | 1.00 | 1.40 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 |
PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.02 | 1131.57 | 1107.16 | 1.00 | 1.40 | General | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.03 | 1135.37 | 1107.16 | 1.00 | 1.40 | General | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.02 | 1124.20 | 1107.16 | 1.00 | 1.40 | General | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 1.78 | 1907.87 | 1070.05 | 1.00 | 1.33 | General | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.92 | 1018.08 | 1107.16 | 1.00 | 1.42 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 |
PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.91 | 1010.87 | 1107.16 | 1.00 | 1.43 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 |
PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.91 | 1004.03 | 1107.16 | 1.00 | 1.43 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 |
PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.96 | 1068.11 | 1107.16 | 1.00 | 1.41 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
GAS TANK1 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK2 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK3 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK4 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK5 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK6 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK7 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:31
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
LGSTORE1 | 20947.97 | 25137.57 | 72.15 | 1.559 | 1.871 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | 23.89 | 23.89 | 0.00906 | 29.40 | 0.00882 | 0.411 | 0.00 |
SMSTORE1 | 11395.10 | 13674.12 | 78.50 | 0.824 | 0.988 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 23.89 | 23.89 | 0.00927 | 25.45 | 0.00882 | 0.206 | 0.00 |
SMSTORE2 | 11441.03 | 13729.24 | 78.82 | 0.852 | 1.022 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 23.89 | 23.89 | 0.00901 | 29.31 | 0.00882 | 0.206 | 0.00 |
SMSTORE3 | 11479.41 | 13775.29 | 79.08 | 0.855 | 1.025 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 23.89 | 23.89 | 0.00901 | 29.31 | 0.00882 | 0.206 | 0.00 |
SMSTORE4 | 11366.55 | 13639.86 | 78.30 | 0.846 | 1.015 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 23.89 | 23.89 | 0.00902 | 29.31 | 0.00882 | 0.206 | 0.00 |
LGSTORE2 | 19958.82 | 23950.58 | 68.75 | 1.486 | 1.783 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 23.89 | 23.89 | 0.00908 | 29.31 | 0.00882 | 0.411 | 0.00 |
SMSTORE5 | 10493.69 | 12592.42 | 72.29 | 0.757 | 0.908 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 23.89 | 23.89 | 0.00949 | 25.45 | 0.00882 | 0.206 | 0.00 |
SMSTORE6 | 10419.53 | 12503.43 | 71.78 | 0.751 | 0.901 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 23.89 | 23.89 | 0.00950 | 25.45 | 0.00882 | 0.206 | 0.00 |
SMSTORE7 | 10298.58 | 12358.29 | 70.95 | 0.742 | 0.891 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 23.89 | 23.89 | 0.00952 | 25.45 | 0.00882 | 0.206 | 0.00 |
SMSTORE8 | 10879.85 | 13055.82 | 74.95 | 0.785 | 0.943 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 23.89 | 23.89 | 0.00941 | 25.45 | 0.00882 | 0.206 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
LGSTORE1 | 19254.71 | 23105.65 | 66.32 | 0.842 | 1.010 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.11 | 0.00670 | -4.20 | 0.00269 | 0.411 | 0.00 |
SMSTORE1 | 8922.57 | 10707.09 | 61.47 | 0.390 | 0.468 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.11 | 0.00661 | -4.20 | 0.00269 | 0.206 | 0.00 |
SMSTORE2 | 9029.09 | 10834.90 | 62.20 | 0.395 | 0.474 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.11 | 0.00663 | -4.20 | 0.00269 | 0.206 | 0.00 |
SMSTORE3 | 9126.46 | 10951.75 | 62.87 | 0.399 | 0.479 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.11 | 0.00664 | -4.20 | 0.00269 | 0.206 | 0.00 |
SMSTORE4 | 9300.80 | 11160.96 | 64.07 | 0.407 | 0.488 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.11 | 0.00665 | -4.20 | 0.00269 | 0.206 | 0.00 |
LGSTORE2 | 18046.61 | 21655.93 | 62.16 | 0.789 | 0.947 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.11 | 0.00673 | -4.20 | 0.00269 | 0.411 | 0.00 |
SMSTORE5 | 9601.99 | 11522.39 | 66.15 | 0.420 | 0.504 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.11 | 0.00668 | -4.20 | 0.00269 | 0.206 | 0.00 |
SMSTORE6 | 9604.33 | 11525.19 | 66.16 | 0.420 | 0.504 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.11 | 0.00668 | -4.20 | 0.00269 | 0.206 | 0.00 |
SMSTORE7 | 9888.14 | 11865.76 | 68.12 | 0.432 | 0.519 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.11 | 0.00670 | -4.20 | 0.00269 | 0.206 | 0.00 |
SMSTORE8 | 12221.14 | 14665.36 | 84.19 | 0.534 | 0.641 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.11 | 0.00673 | -4.20 | 0.00269 | 0.206 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC_1:1 | 1.87 | 1.87 | 1.01 | 1.01 | 1.8713 | 1.8713 | 1.8713 | 1.0000 | 1.0000 |
PSZ-AC_2:2 | 1.02 | 1.02 | 0.47 | 0.47 | 1.0164 | 0.9883 | 1.0164 | 0.9724 | 1.0000 |
PSZ-AC_3:3 | 1.02 | 1.02 | 0.47 | 0.47 | 1.0220 | 1.0220 | 1.0220 | 1.0000 | 1.0000 |
PSZ-AC_4:4 | 1.03 | 1.03 | 0.48 | 0.48 | 1.0255 | 1.0255 | 1.0255 | 1.0000 | 1.0000 |
PSZ-AC_5:5 | 1.02 | 1.02 | 0.49 | 0.49 | 1.0154 | 1.0154 | 1.0154 | 1.0000 | 1.0000 |
PSZ-AC_6:6 | 1.78 | 1.78 | 0.95 | 0.95 | 1.7830 | 1.7830 | 1.7830 | 1.0000 | 1.0000 |
PSZ-AC_7:7 | 0.92 | 0.92 | 0.50 | 0.50 | 0.9195 | 0.9080 | 0.9195 | 0.9875 | 1.0000 |
PSZ-AC_8:8 | 0.91 | 0.91 | 0.50 | 0.50 | 0.9130 | 0.9014 | 0.9130 | 0.9873 | 1.0000 |
PSZ-AC_9:9 | 0.91 | 0.91 | 0.52 | 0.52 | 0.9069 | 0.8906 | 0.9069 | 0.9821 | 1.0000 |
PSZ-AC_10:10 | 0.96 | 0.96 | 0.64 | 0.64 | 0.9647 | 0.9425 | 0.9647 | 0.9770 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 32747.320 | 26223.399 | 1.871330 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | 16373.66 | 15073.89 | 1.247553 | 25.98 | 17.35 | 0.00900406 | 12.80 | 11.97 | 0.00850000 | 29.40 | 0.00882150 | 18.34 | 32.9829 | 23.89 | 0.00905552 | 48.3334 | 20947.97 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_1:1 | 54590.698 | 54590.698 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 54590.70 | 54590.70 | 1.871334 | 15.54 | 10.37 | 0.00581490 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 21.9885 | 21.11 | 0.00669560 | 42.4790 | 19254.71 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 17617.940 | 14096.466 | 1.016430 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 8808.97 | 8141.60 | 0.677620 | 25.92 | 17.31 | 0.00897705 | 12.80 | 11.97 | 0.00850000 | 29.40 | 0.00882150 | 18.34 | 30.3621 | 23.89 | 0.00901652 | 48.1280 | 11378.17 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_2:2 | 28482.136 | 28482.136 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 28482.14 | 28482.14 | 1.016434 | 15.98 | 10.57 | 0.00582055 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 20.2413 | 21.11 | 0.00661494 | 41.9723 | 8922.57 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_3:3 | 17704.740 | 14169.635 | 1.022050 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 8852.37 | 8183.65 | 0.681367 | 25.91 | 17.30 | 0.00897537 | 12.80 | 11.97 | 0.00850000 | 29.40 | 0.00882150 | 18.34 | 30.1951 | 23.89 | 0.00901416 | 48.1156 | 11439.12 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_3:3 | 29241.708 | 29241.708 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 29241.71 | 29241.71 | 1.022050 | 16.01 | 10.59 | 0.00583447 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 20.1301 | 21.11 | 0.00662691 | 42.0474 | 9029.09 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_4:4 | 17757.610 | 14214.257 | 1.025480 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 8878.81 | 8209.28 | 0.683653 | 25.91 | 17.30 | 0.00897434 | 12.80 | 11.97 | 0.00850000 | 29.40 | 0.00882150 | 18.34 | 30.0941 | 23.89 | 0.00901271 | 48.1079 | 11476.87 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_4:4 | 29318.955 | 29318.955 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 29318.96 | 29318.96 | 1.025478 | 16.03 | 10.61 | 0.00584444 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 20.0628 | 21.11 | 0.00663607 | 42.1050 | 9126.46 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_5:5 | 17602.360 | 14083.120 | 1.015400 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 8801.18 | 8133.96 | 0.676933 | 25.92 | 17.31 | 0.00897744 | 12.80 | 11.97 | 0.00850000 | 29.40 | 0.00882150 | 18.34 | 30.3929 | 23.89 | 0.00901707 | 48.1309 | 11364.25 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_5:5 | 29091.755 | 29091.755 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 29091.75 | 29091.75 | 1.015396 | 15.98 | 10.59 | 0.00584997 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 20.2620 | 21.11 | 0.00665287 | 42.2104 | 9300.80 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_6:6 | 31389.770 | 25133.475 | 1.782970 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 15694.89 | 14414.03 | 1.188647 | 26.04 | 17.39 | 0.00902160 | 12.80 | 11.97 | 0.00850000 | 29.40 | 0.00882150 | 18.34 | 34.6174 | 23.89 | 0.00908167 | 48.4709 | 19950.58 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_6:6 | 52598.822 | 52598.822 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 52598.82 | 52598.82 | 1.782973 | 15.27 | 10.23 | 0.00579897 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 23.0782 | 21.11 | 0.00673164 | 42.7042 | 18046.61 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_7:7 | 16122.530 | 12899.797 | 0.919550 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 8061.27 | 7417.98 | 0.613033 | 26.03 | 17.37 | 0.00900874 | 12.80 | 11.97 | 0.00850000 | 29.40 | 0.00882150 | 18.34 | 33.5609 | 23.89 | 0.00906272 | 48.3710 | 10290.99 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_7:7 | 26672.478 | 26672.478 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 26672.48 | 26672.48 | 0.919547 | 15.44 | 10.30 | 0.00578615 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 22.3740 | 21.11 | 0.00667846 | 42.3711 | 9601.99 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_8:8 | 16021.690 | 12830.490 | 0.913030 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | 8010.85 | 7369.32 | 0.608687 | 26.04 | 17.38 | 0.00901101 | 12.80 | 11.97 | 0.00850000 | 29.40 | 0.00882150 | 18.34 | 33.8005 | 23.89 | 0.00906615 | 48.3891 | 10217.39 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_8:8 | 26523.050 | 26523.050 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 26523.05 | 26523.05 | 0.913028 | 15.40 | 10.27 | 0.00578002 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 22.5338 | 21.11 | 0.00667876 | 42.3730 | 9604.33 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_9:9 | 15925.990 | 12749.551 | 0.906860 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 7962.99 | 7323.19 | 0.604573 | 26.05 | 17.38 | 0.00901314 | 12.80 | 11.97 | 0.00850000 | 29.40 | 0.00882150 | 18.34 | 34.0305 | 23.89 | 0.00906939 | 48.4061 | 10148.75 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_9:9 | 26279.218 | 26279.218 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 26279.22 | 26279.22 | 0.906856 | 15.37 | 10.27 | 0.00579280 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 22.6871 | 21.11 | 0.00670320 | 42.5265 | 9888.14 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_10:10 | 16684.320 | 13362.639 | 0.964730 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:10:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | 8342.16 | 7691.43 | 0.643153 | 25.89 | 17.31 | 0.00899134 | 12.80 | 11.97 | 0.00850000 | 28.97 | 0.00882080 | 18.20 | 31.9892 | 23.89 | 0.00903765 | 48.2391 | 10784.37 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_10:10 | 27450.622 | 27450.622 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 27450.62 | 27450.62 | 0.964728 | 15.71 | 10.50 | 0.00587120 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 21.3262 | 21.11 | 0.00673344 | 42.7184 | 12221.14 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:37:31
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 32747.320 | 26223.399 | 1.871330 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.5781 | 1004.8586 | 1.1870 | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.871334 | 2.22125651 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | Sensible | 16373.66 | 15073.89 | 1.0000 | 1.48083431 | 1.247553 | 25.98 | 17.35 | 0.00900406 | 49061.7 | 12.80 | 11.97 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 16373.66 | 29.40 | 0.00882150 | 18.34 | 0.41147883 | 32.9829 | 23.89 | 0.00905552 | 23.89 | 0.00905552 | 48.3334 | 20947.97 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 54590.698 | 54590.698 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.871334 | 2.22125651 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | Sensible | 54590.70 | 54590.70 | 1.0000 | 2.22125651 | 1.871334 | 15.54 | 10.37 | 0.00581490 | 30328.3 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 54590.70 | -4.20 | 0.00269032 | -4.20 | 0.41147883 | 21.9885 | 21.11 | 0.00669560 | 21.11 | 0.00669560 | 42.4790 | 19254.71 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 17617.940 | 14096.466 | 1.016430 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.5279 | 1004.8586 | 1.1870 | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.016434 | 1.20649774 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | Sensible | 8808.97 | 8141.60 | 1.0000 | 0.80432869 | 0.677620 | 25.92 | 17.31 | 0.00897705 | 48925.8 | 12.80 | 11.97 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8808.97 | 29.40 | 0.00882150 | 18.34 | 0.20573941 | 30.3621 | 23.89 | 0.00901652 | 23.89 | 0.00901652 | 48.1280 | 11378.17 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 28482.136 | 28482.136 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.016434 | 1.20649774 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | Sensible | 28482.14 | 28482.14 | 1.0000 | 1.20649774 | 1.016434 | 15.98 | 10.57 | 0.00582055 | 30791.9 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28482.14 | -4.20 | 0.00269032 | -4.20 | 0.20573941 | 20.2413 | 21.11 | 0.00661494 | 21.11 | 0.00661494 | 41.9723 | 8922.57 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 17704.740 | 14169.635 | 1.022050 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.5248 | 1004.8586 | 1.1870 | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.022050 | 1.21316334 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | Sensible | 8852.37 | 8183.65 | 1.0000 | 0.80877595 | 0.681367 | 25.91 | 17.30 | 0.00897537 | 48915.5 | 12.80 | 11.97 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8852.37 | 29.40 | 0.00882150 | 18.34 | 0.20573941 | 30.1951 | 23.89 | 0.00901416 | 23.89 | 0.00901416 | 48.1156 | 11439.12 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 29241.708 | 29241.708 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.022050 | 1.21316334 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | Sensible | 29241.71 | 29241.71 | 1.0000 | 1.21316334 | 1.022050 | 16.01 | 10.59 | 0.00583447 | 30855.7 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 29241.71 | -4.20 | 0.00269032 | -4.20 | 0.20573941 | 20.1301 | 21.11 | 0.00662691 | 21.11 | 0.00662691 | 42.0474 | 9029.09 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 17757.610 | 14214.257 | 1.025480 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.5228 | 1004.8586 | 1.1870 | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.025478 | 1.21723234 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | Sensible | 8878.81 | 8209.28 | 1.0000 | 0.81149021 | 0.683653 | 25.91 | 17.30 | 0.00897434 | 48909.1 | 12.80 | 11.97 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8878.81 | 29.40 | 0.00882150 | 18.34 | 0.20573941 | 30.0941 | 23.89 | 0.00901271 | 23.89 | 0.00901271 | 48.1079 | 11476.87 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 29318.955 | 29318.955 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.025478 | 1.21723234 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | Sensible | 29318.96 | 29318.96 | 1.0000 | 1.21723234 | 1.025478 | 16.03 | 10.61 | 0.00584444 | 30898.2 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 29318.96 | -4.20 | 0.00269032 | -4.20 | 0.20573941 | 20.0628 | 21.11 | 0.00663607 | 21.11 | 0.00663607 | 42.1050 | 9126.46 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 17602.360 | 14083.120 | 1.015400 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.5286 | 1004.8586 | 1.1870 | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.015396 | 1.20526520 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | Sensible | 8801.18 | 8133.96 | 1.0000 | 0.80351363 | 0.676933 | 25.92 | 17.31 | 0.00897744 | 48928.2 | 12.80 | 11.97 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8801.18 | 29.40 | 0.00882150 | 18.34 | 0.20573941 | 30.3929 | 23.89 | 0.00901707 | 23.89 | 0.00901707 | 48.1309 | 11364.25 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 29091.755 | 29091.755 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.015396 | 1.20526520 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | Sensible | 29091.75 | 29091.75 | 1.0000 | 1.20526520 | 1.015396 | 15.98 | 10.59 | 0.00584997 | 30861.0 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 29091.75 | -4.20 | 0.00269032 | -4.20 | 0.20573941 | 20.2620 | 21.11 | 0.00665287 | 21.11 | 0.00665287 | 42.2104 | 9300.80 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 31389.770 | 25133.475 | 1.782970 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.6107 | 1004.8586 | 1.1870 | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.782973 | 2.11637235 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | Sensible | 15694.89 | 14414.03 | 1.0000 | 1.41091264 | 1.188647 | 26.04 | 17.39 | 0.00902160 | 49168.3 | 12.80 | 11.97 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 15694.89 | 29.40 | 0.00882150 | 18.34 | 0.41147883 | 34.6174 | 23.89 | 0.00908167 | 23.89 | 0.00908167 | 48.4709 | 19950.58 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 52598.822 | 52598.822 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.782973 | 2.11637235 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | Sensible | 52598.82 | 52598.82 | 1.0000 | 2.11637235 | 1.782973 | 15.27 | 10.23 | 0.00579897 | 30008.2 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 52598.82 | -4.20 | 0.00269032 | -4.20 | 0.41147883 | 23.0782 | 21.11 | 0.00673164 | 21.11 | 0.00673164 | 42.7042 | 18046.61 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 16122.530 | 12899.797 | 0.919550 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.5868 | 1004.8586 | 1.1870 | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.919547 | 1.09149341 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | Sensible | 8061.27 | 7417.98 | 1.0000 | 0.72766492 | 0.613033 | 26.03 | 17.37 | 0.00900874 | 49126.9 | 12.80 | 11.97 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8061.27 | 29.40 | 0.00882150 | 18.34 | 0.20573941 | 33.5609 | 23.89 | 0.00906272 | 23.89 | 0.00906272 | 48.3710 | 10290.99 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 26672.478 | 26672.478 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.919547 | 1.09149341 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | Sensible | 26672.48 | 26672.48 | 1.0000 | 1.09149341 | 0.919547 | 15.44 | 10.30 | 0.00578615 | 30156.7 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 26672.48 | -4.20 | 0.00269032 | -4.20 | 0.20573941 | 22.3740 | 21.11 | 0.00667846 | 21.11 | 0.00667846 | 42.3711 | 9601.99 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 16021.690 | 12830.490 | 0.913030 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.5910 | 1004.8586 | 1.1870 | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.913028 | 1.08375530 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | Sensible | 8010.85 | 7369.32 | 1.0000 | 0.72250546 | 0.608687 | 26.04 | 17.38 | 0.00901101 | 49141.8 | 12.80 | 11.97 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8010.85 | 29.40 | 0.00882150 | 18.34 | 0.20573941 | 33.8005 | 23.89 | 0.00906615 | 23.89 | 0.00906615 | 48.3891 | 10217.39 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 26523.050 | 26523.050 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.913028 | 1.08375530 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | Sensible | 26523.05 | 26523.05 | 1.0000 | 1.08375530 | 0.913028 | 15.40 | 10.27 | 0.00578002 | 30100.1 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 26523.05 | -4.20 | 0.00269032 | -4.20 | 0.20573941 | 22.5338 | 21.11 | 0.00667876 | 21.11 | 0.00667876 | 42.3730 | 9604.33 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 15925.990 | 12749.551 | 0.906860 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.5950 | 1004.8586 | 1.1870 | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.906856 | 1.07642980 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | Sensible | 7962.99 | 7323.19 | 1.0000 | 0.71762297 | 0.604573 | 26.05 | 17.38 | 0.00901314 | 49155.8 | 12.80 | 11.97 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7962.99 | 29.40 | 0.00882150 | 18.34 | 0.20573941 | 34.0305 | 23.89 | 0.00906939 | 23.89 | 0.00906939 | 48.4061 | 10148.75 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 26279.218 | 26279.218 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.906856 | 1.07642980 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | Sensible | 26279.22 | 26279.22 | 1.0000 | 1.07642980 | 0.906856 | 15.37 | 10.27 | 0.00579280 | 30093.0 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 26279.22 | -4.20 | 0.00269032 | -4.20 | 0.20573941 | 22.6871 | 21.11 | 0.00670320 | 21.11 | 0.00670320 | 42.5265 | 9888.14 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 16684.320 | 13362.639 | 0.964730 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.5545 | 1004.8586 | 1.1870 | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.964728 | 1.14512312 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:10:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:10:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | Sensible | 8342.16 | 7691.43 | 1.0000 | 0.76341708 | 0.643153 | 25.89 | 17.31 | 0.00899134 | 48930.4 | 12.80 | 11.97 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8342.16 | 28.97 | 0.00882080 | 18.20 | 0.20573941 | 31.9892 | 23.89 | 0.00903765 | 23.89 | 0.00903765 | 48.2391 | 10784.37 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 27450.622 | 27450.622 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.964728 | 1.14512312 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | Sensible | 27450.62 | 27450.62 | 1.0000 | 1.14512312 | 0.964728 | 15.71 | 10.50 | 0.00587120 | 30640.6 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 27450.62 | -4.20 | 0.00269032 | -4.20 | 0.20573941 | 21.3262 | 21.11 | 0.00673344 | 21.11 | 0.00673344 | 42.7184 | 12221.14 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:31
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-AC_1:1_OA_CONTROLLER | DifferentialDryBulb | 0.41 | 1.87 | - | |||
PSZ-AC_2:2_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.02 | - | |||
PSZ-AC_3:3_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.02 | - | |||
PSZ-AC_4:4_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.03 | - | |||
PSZ-AC_5:5_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.02 | - | |||
PSZ-AC_6:6_OA_CONTROLLER | DifferentialDryBulb | 0.41 | 1.78 | - | |||
PSZ-AC_7:7_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 0.92 | - | |||
PSZ-AC_8:8_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 0.91 | - | |||
PSZ-AC_9:9_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 0.91 | - | |||
PSZ-AC_10:10_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 0.96 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
LGSTORE1 | 1485.83 | 4040.33 | 517.17 |
SMSTORE1 | 1132.00 | 3453.50 | 48.83 |
SMSTORE2 | 1088.00 | 2694.17 | 151.50 |
SMSTORE3 | 1108.67 | 2732.83 | 191.50 |
SMSTORE4 | 1102.33 | 2851.33 | 253.00 |
LGSTORE2 | 1077.33 | 2872.50 | 459.17 |
SMSTORE5 | 1036.17 | 2818.33 | 464.67 |
SMSTORE6 | 1044.00 | 2839.50 | 489.67 |
SMSTORE7 | 1112.00 | 2921.50 | 600.67 |
SMSTORE8 | 1551.83 | 3067.33 | 1103.00 |
Facility | 2574.17 | 4467.67 | 1368.67 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
LGSTORE1 | 4.50 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 0.00 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 0.33 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 0.33 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 0.50 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 1.83 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 12.50 | 0.00 | 0.00 | 0.00 |
Facility | 17.00 | 0.00 | 0.00 | 0.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:31
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
LGSTORE1 | 16.93 | 56.25 | 1805.20 | 0.984 | 0.230 | 0.000 | 0.000 |
SMSTORE1 | 8.46 | 28.12 | 902.60 | 1.109 | 0.245 | 0.000 | 0.000 |
SMSTORE2 | 7.08 | 28.12 | 902.60 | 1.246 | 0.320 | 0.000 | 0.000 |
SMSTORE3 | 7.08 | 28.12 | 902.60 | 1.240 | 0.320 | 0.000 | 0.000 |
SMSTORE4 | 7.08 | 28.12 | 902.60 | 1.212 | 0.320 | 0.000 | 0.000 |
LGSTORE2 | 24.78 | 56.25 | 1805.20 | 0.993 | 0.307 | 0.000 | 0.000 |
SMSTORE5 | 12.39 | 28.12 | 902.60 | 1.158 | 0.341 | 0.000 | 0.000 |
SMSTORE6 | 12.39 | 28.12 | 902.60 | 1.151 | 0.341 | 0.000 | 0.000 |
SMSTORE7 | 12.39 | 28.12 | 902.60 | 1.129 | 0.341 | 0.000 | 0.000 |
SMSTORE8 | 12.39 | 28.12 | 902.60 | 1.127 | 0.359 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
LGSTORE1 | 16.93 | 56.25 | 1805.20 | 0.000 | 0.000 | 0.000 | 0.000 |
SMSTORE1 | 8.46 | 28.12 | 902.60 | 0.000 | 0.000 | 0.000 | 0.000 |
SMSTORE2 | 7.08 | 28.12 | 902.60 | 0.808 | 0.000 | 0.000 | 0.000 |
SMSTORE3 | 7.08 | 28.12 | 902.60 | 0.808 | 0.000 | 0.000 | 0.000 |
SMSTORE4 | 7.08 | 28.12 | 902.60 | 0.808 | 0.000 | 0.000 | 0.000 |
LGSTORE2 | 24.78 | 56.25 | 1805.20 | 0.810 | 0.000 | 0.000 | 0.000 |
SMSTORE5 | 12.39 | 28.12 | 902.60 | 0.810 | 0.000 | 0.000 | 0.000 |
SMSTORE6 | 12.39 | 28.12 | 902.60 | 0.810 | 0.000 | 0.000 | 0.000 |
SMSTORE7 | 12.39 | 28.12 | 902.60 | 0.810 | 0.000 | 0.000 | 0.000 |
SMSTORE8 | 12.39 | 28.12 | 902.60 | 0.810 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:37:31
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
LGSTORE1 | PSZ-AC_1:1 | 16.93 | 56.25 | 1805.20 | 348.39 | 0.4115 | 0.411 |
SMSTORE1 | PSZ-AC_2:2 | 8.46 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE2 | PSZ-AC_3:3 | 7.08 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE3 | PSZ-AC_4:4 | 7.08 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE4 | PSZ-AC_5:5 | 7.08 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
LGSTORE2 | PSZ-AC_6:6 | 24.78 | 56.25 | 1805.20 | 348.39 | 0.4115 | 0.411 |
SMSTORE5 | PSZ-AC_7:7 | 12.39 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE6 | PSZ-AC_8:8 | 12.39 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE7 | PSZ-AC_9:9 | 12.39 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE8 | PSZ-AC_10:10 | 12.39 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
Total Facility | 120.98 | 337.50 | 10831.20 | 2090.32 | 2.4689 | 2.469 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
LGSTORE1 | 10210359.17 | 0.00 | 10210359.17 | 2751432.93 | 12961792.11 | 12976396.34 | 3176.44 | 4202.92 | 1380.64 | 18.11 |
SMSTORE1 | 5750236.73 | 0.00 | 5750236.73 | 1379627.48 | 7129864.21 | 6488198.17 | 4133.36 | 2708.69 | 1917.95 | 39.36 |
SMSTORE2 | 4913613.77 | 0.00 | 4913613.77 | 1417008.46 | 6330622.24 | 6488198.17 | 4348.21 | 3135.83 | 1275.96 | 132.11 |
SMSTORE3 | 4890460.87 | 0.00 | 4890460.87 | 1417008.46 | 6307469.33 | 6488198.17 | 4348.04 | 3169.25 | 1242.71 | 127.69 |
SMSTORE4 | 4773125.29 | 0.00 | 4773125.29 | 1417008.46 | 6190133.75 | 6488198.17 | 4350.29 | 3261.42 | 1148.29 | 116.89 |
LGSTORE2 | 7141367.70 | 0.00 | 7141367.70 | 2601582.32 | 9742950.01 | 12976396.34 | 4723.78 | 3205.83 | 830.39 | 65.22 |
SMSTORE5 | 4179373.97 | 0.00 | 4179373.97 | 1426750.59 | 5606124.57 | 6488198.17 | 4719.53 | 3044.00 | 996.47 | 94.89 |
SMSTORE6 | 4148902.52 | 0.00 | 4148902.52 | 1426750.59 | 5575653.12 | 6488198.17 | 4720.28 | 3060.42 | 979.31 | 91.22 |
SMSTORE7 | 4063670.62 | 0.00 | 4063670.62 | 1426750.59 | 5490421.22 | 6488198.17 | 4720.97 | 3129.33 | 909.69 | 72.83 |
SMSTORE8 | 4046874.27 | 0.00 | 4046874.27 | 1741532.12 | 5788406.39 | 6488198.17 | 4721.11 | 3218.17 | 820.72 | 29.25 |
Total Facility | 54117984.91 | 0.00 | 54117984.91 | 17005452.03 | 71123436.94 | 77858378.04 | 4725.22 | 4714.69 | 2054.29 | 238.72 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
LGSTORE1 | 0.4853 | 0.0000 | 0.4853 | 0.1134 | 0.5987 | 0.4115 | 257.22 | 4202.75 | 1380.03 |
SMSTORE1 | 0.2726 | 0.0000 | 0.2726 | 0.0605 | 0.3331 | 0.2057 | 1218.06 | 2708.36 | 1913.59 |
SMSTORE2 | 0.3067 | 0.0000 | 0.3067 | 0.0789 | 0.3856 | 0.2057 | 0.00 | 3135.33 | 1259.67 |
SMSTORE3 | 0.3054 | 0.0000 | 0.3054 | 0.0789 | 0.3842 | 0.2057 | 0.00 | 3168.75 | 1226.25 |
SMSTORE4 | 0.2984 | 0.0000 | 0.2984 | 0.0789 | 0.3773 | 0.2057 | 0.00 | 3260.92 | 1134.08 |
LGSTORE2 | 0.4896 | 0.0000 | 0.4896 | 0.1515 | 0.6411 | 0.4115 | 0.00 | 3205.83 | 824.17 |
SMSTORE5 | 0.2852 | 0.0000 | 0.2852 | 0.0841 | 0.3694 | 0.2057 | 0.00 | 3043.67 | 986.33 |
SMSTORE6 | 0.2833 | 0.0000 | 0.2833 | 0.0841 | 0.3675 | 0.2057 | 0.00 | 3060.17 | 969.83 |
SMSTORE7 | 0.2781 | 0.0000 | 0.2781 | 0.0841 | 0.3622 | 0.2057 | 0.00 | 3129.08 | 900.92 |
SMSTORE8 | 0.2778 | 0.0000 | 0.2778 | 0.0886 | 0.3664 | 0.2057 | 0.00 | 3217.67 | 812.33 |
Total Facility | 3.2824 | 0.0000 | 3.2824 | 0.9031 | 4.1855 | 2.4689 | 1332.53 | 4712.36 | 2040.56 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-AC_1:1 | 14386310.33 | 0.00 | 14386310.33 | 12976396.34 | 3173.78 | 0.00 | 5586.22 | 18.11 |
PSZ-AC_2:2 | 8101779.48 | 0.00 | 8101779.48 | 6488198.17 | 4094.58 | 4.40 | 4661.01 | 39.36 |
PSZ-AC_3:3 | 6923021.97 | 0.00 | 6923021.97 | 6488198.17 | 4328.54 | 1.83 | 4429.62 | 131.94 |
PSZ-AC_4:4 | 6890400.76 | 0.00 | 6890400.76 | 6488198.17 | 4329.71 | 1.50 | 4428.79 | 127.53 |
PSZ-AC_5:5 | 6725081.12 | 0.00 | 6725081.12 | 6488198.17 | 4335.87 | 1.33 | 4422.79 | 116.89 |
PSZ-AC_6:6 | 10062135.67 | 0.00 | 10062135.67 | 12976396.34 | 4720.53 | 0.00 | 4039.47 | 65.06 |
PSZ-AC_7:7 | 5888516.92 | 0.00 | 5888516.92 | 6488198.17 | 4711.44 | 0.58 | 4047.97 | 94.56 |
PSZ-AC_8:8 | 5845584.26 | 0.00 | 5845584.26 | 6488198.17 | 4712.97 | 0.67 | 4046.36 | 91.06 |
PSZ-AC_9:9 | 5725497.02 | 0.00 | 5725497.02 | 6488198.17 | 4717.58 | 0.67 | 4041.75 | 72.67 |
PSZ-AC_10:10 | 5701831.84 | 0.00 | 5701831.84 | 6488198.17 | 4719.11 | 0.00 | 4040.89 | 29.08 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-AC_1:1 | 0.6838 | 0.0000 | 0.6838 | 0.4115 | 254.64 | 0.00 | 5585.36 |
PSZ-AC_2:2 | 0.3841 | 0.0000 | 0.3841 | 0.2057 | 1186.61 | 4.07 | 4649.32 |
PSZ-AC_3:3 | 0.4321 | 0.0000 | 0.4321 | 0.2057 | 0.00 | 0.00 | 4395.00 |
PSZ-AC_4:4 | 0.4302 | 0.0000 | 0.4302 | 0.2057 | 0.00 | 0.00 | 4395.00 |
PSZ-AC_5:5 | 0.4205 | 0.0000 | 0.4205 | 0.2057 | 0.00 | 0.00 | 4395.00 |
PSZ-AC_6:6 | 0.6898 | 0.0000 | 0.6898 | 0.4115 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_7:7 | 0.4019 | 0.0000 | 0.4019 | 0.2057 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_8:8 | 0.3992 | 0.0000 | 0.3992 | 0.2057 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_9:9 | 0.3918 | 0.0000 | 0.3918 | 0.2057 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_10:10 | 0.3913 | 0.0000 | 0.3913 | 0.2057 | 0.00 | 0.00 | 4030.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-AC_1:1 | 0.00 | 4948.72 | 695.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_2:2 | 0.00 | 3391.82 | 1685.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_3:3 | 0.00 | 3627.24 | 899.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_4:4 | 0.00 | 3654.40 | 868.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_5:5 | 0.00 | 3719.62 | 792.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_6:6 | 0.00 | 3731.81 | 363.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_7:7 | 0.00 | 3484.28 | 640.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_8:8 | 0.00 | 3494.61 | 626.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_9:9 | 0.00 | 3544.31 | 558.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_10:10 | 0.00 | 3602.17 | 456.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-AC_1:1 | 0.0000 | 0.6901 | 0.8554 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_2:2 | 0.0000 | 0.4247 | 0.4881 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_3:3 | 0.0000 | 0.3976 | 0.5954 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_4:4 | 0.0000 | 0.3960 | 0.5997 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_5:5 | 0.0000 | 0.3869 | 0.6060 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_6:6 | 0.0000 | 0.6735 | 0.8952 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_7:7 | 0.0000 | 0.3761 | 0.5674 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_8:8 | 0.0000 | 0.3738 | 0.5655 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_9:9 | 0.0000 | 0.3682 | 0.5649 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_10:10 | 0.0000 | 0.3678 | 0.5901 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:31
Surfaces by ClassTotal | Outdoors | |
Wall | 40 | 22 |
Floor | 10 | 10 |
Roof | 10 | 10 |
Internal Mass | 10 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 36 | 36 |
Door | 12 | 12 |
Glass Door | 12 | 12 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 10 |
Conditioned Zones | 10 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 830 |
Defaulted Fields | 823 |
Fields with Defaults | 2682 |
Autosized Fields | 184 |
Autosizable Fields | 458 |
Autocalculated Fields | 128 |
Autocalculatable Fields | 256 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:37:31
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 821.96 | 2102.83 | 15-JAN-08:00 | 74483.43 | 29-AUG-13:50 |
Electricity:Building | 494.83 | 891.83 | 01-JAN-00:20 | 31518.67 | 01-JAN-11:10 |
Electricity:Zone:LGSTORE1 | 113.36 | 148.64 | 01-JAN-00:20 | 5964.88 | 01-JAN-10:10 |
Electricity:SpaceType:GENERAL | 494.83 | 891.83 | 01-JAN-00:20 | 31518.67 | 01-JAN-11:10 |
InteriorLights:Electricity | 366.68 | 450.00 | 01-JAN-00:20 | 23459.17 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:LGSTORE1 | 87.12 | 75.00 | 01-JAN-00:20 | 4621.63 | 01-JAN-10:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 366.68 | 450.00 | 01-JAN-00:20 | 23459.17 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity | 366.68 | 450.00 | 01-JAN-00:20 | 23459.17 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:LGSTORE1 | 87.12 | 75.00 | 01-JAN-00:20 | 4621.63 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 366.68 | 450.00 | 01-JAN-00:20 | 23459.17 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE1 | 66.33 | 74.32 | 01-JAN-00:20 | 3498.69 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE1 | 53.20 | 37.50 | 01-JAN-00:20 | 2827.07 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE1 | 53.20 | 37.50 | 01-JAN-00:20 | 2827.07 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE2 | 47.99 | 74.32 | 01-JAN-00:10 | 3226.84 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE2 | 37.57 | 37.50 | 01-JAN-00:10 | 2555.22 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE2 | 37.57 | 37.50 | 01-JAN-00:10 | 2555.22 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE3 | 47.99 | 74.32 | 01-JAN-00:10 | 3226.84 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE3 | 37.57 | 37.50 | 01-JAN-00:10 | 2555.22 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE3 | 37.57 | 37.50 | 01-JAN-00:10 | 2555.22 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE4 | 47.99 | 74.32 | 01-JAN-00:10 | 3226.84 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE4 | 37.57 | 37.50 | 01-JAN-00:10 | 2555.22 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE4 | 37.57 | 37.50 | 01-JAN-00:10 | 2555.22 | 01-JAN-10:10 |
Electricity:Zone:LGSTORE2 | 56.34 | 148.64 | 01-JAN-00:10 | 4070.21 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:LGSTORE2 | 37.16 | 75.00 | 01-JAN-00:10 | 2726.96 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:LGSTORE2 | 37.16 | 75.00 | 01-JAN-00:10 | 2726.96 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE5 | 28.71 | 74.32 | 01-JAN-00:10 | 2076.09 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE5 | 19.12 | 37.50 | 01-JAN-00:10 | 1404.46 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE5 | 19.12 | 37.50 | 01-JAN-00:10 | 1404.46 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE6 | 28.71 | 74.32 | 01-JAN-00:10 | 2076.09 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE6 | 19.12 | 37.50 | 01-JAN-00:10 | 1404.46 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE6 | 19.12 | 37.50 | 01-JAN-00:10 | 1404.46 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE7 | 28.71 | 74.32 | 01-JAN-00:10 | 2076.09 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE7 | 19.12 | 37.50 | 01-JAN-00:10 | 1404.46 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE7 | 19.12 | 37.50 | 01-JAN-00:10 | 1404.46 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE8 | 28.71 | 74.32 | 01-JAN-00:10 | 2076.09 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE8 | 19.12 | 37.50 | 01-JAN-00:10 | 1404.46 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE8 | 19.12 | 37.50 | 01-JAN-00:10 | 1404.46 | 01-JAN-11:10 |
InteriorEquipment:Electricity | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:LGSTORE1 | 26.25 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-10:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LGSTORE1 | 26.25 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE1 | 13.12 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE1 | 13.12 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE2 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE2 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE3 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE3 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE4 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE4 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:LGSTORE2 | 19.17 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LGSTORE2 | 19.17 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE5 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE5 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE6 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE6 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE7 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE7 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE8 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE8 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
ElectricityPurchased:Facility | 821.96 | 2102.83 | 15-JAN-08:00 | 74483.43 | 29-AUG-13:50 |
ElectricityPurchased:Plant | 821.96 | 2102.83 | 15-JAN-08:00 | 74483.43 | 29-AUG-13:50 |
Cogeneration:ElectricityPurchased | 821.96 | 2102.83 | 15-JAN-08:00 | 74483.43 | 29-AUG-13:50 |
General:Cogeneration:ElectricityPurchased | 821.96 | 2102.83 | 15-JAN-08:00 | 74483.43 | 29-AUG-13:50 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 821.96 | 2102.83 | 15-JAN-08:00 | 74483.43 | 29-AUG-13:50 |
ElectricityNet:Plant | 821.96 | 2102.83 | 15-JAN-08:00 | 74483.43 | 29-AUG-13:50 |
Cogeneration:ElectricityNet | 821.96 | 2102.83 | 15-JAN-08:00 | 74483.43 | 29-AUG-13:50 |
General:Cogeneration:ElectricityNet | 821.96 | 2102.83 | 15-JAN-08:00 | 74483.43 | 29-AUG-13:50 |
Electricity:HVAC | 202.51 | 0.00 | 01-JAN-00:10 | 37347.59 | 29-AUG-15:00 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 27.88 | 0.00 | 01-JAN-00:10 | 26821.93 | 29-AUG-15:00 |
General:Cooling:Electricity | 27.88 | 0.00 | 01-JAN-00:10 | 26821.93 | 29-AUG-15:00 |
Fans:Electricity | 174.63 | 0.00 | 01-JAN-00:10 | 10992.51 | 16-JAN-09:10 |
General:Fans:Electricity | 174.63 | 0.00 | 01-JAN-00:10 | 10992.51 | 16-JAN-09:10 |
ExteriorLights:Electricity | 60.41 | 0.00 | 01-JAN-08:10 | 5507.06 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 60.41 | 0.00 | 01-JAN-08:10 | 5507.06 | 01-JAN-06:10 |
Electricity:Plant | 64.21 | 1211.00 | 11-JAN-08:10 | 13988.60 | 20-JAN-14:00 |
WaterSystems:Electricity | 64.21 | 1211.00 | 11-JAN-08:10 | 13988.60 | 20-JAN-14:00 |
Water Heater:WaterSystems:Electricity | 64.21 | 1211.00 | 11-JAN-08:10 | 13988.60 | 20-JAN-14:00 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 302.22 | 0.00 | 01-JAN-00:10 | 144700.38 | 16-JAN-09:10 |
NaturalGas:HVAC | 302.22 | 0.00 | 01-JAN-00:10 | 144700.38 | 16-JAN-09:10 |
Heating:NaturalGas | 302.22 | 0.00 | 01-JAN-00:10 | 144700.38 | 16-JAN-09:10 |
General:Heating:NaturalGas | 302.22 | 0.00 | 01-JAN-00:10 | 144700.38 | 16-JAN-09:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water:Plant | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
WaterSystems:Water | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water Heater:WaterSystems:Water | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
MainsWater:Facility | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
MainsWater:Plant | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
WaterSystems:MainsWater | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water Heater:WaterSystems:MainsWater | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 724.59 | 0.00 | 01-JAN-00:10 | 212316.99 | 26-DEC-08:10 |
EnergyTransfer:Building | 360.45 | 0.00 | 01-JAN-00:10 | 101682.43 | 26-DEC-08:10 |
EnergyTransfer:Zone:LGSTORE1 | 77.93 | 0.00 | 01-JAN-00:10 | 21803.48 | 19-FEB-08:10 |
Heating:EnergyTransfer | 75.71 | 0.00 | 01-JAN-00:10 | 101682.43 | 26-DEC-08:10 |
Heating:EnergyTransfer:Zone:LGSTORE1 | 9.90 | 0.00 | 01-JAN-00:10 | 21803.48 | 19-FEB-08:10 |
General:Heating:EnergyTransfer | 75.71 | 0.00 | 01-JAN-00:10 | 101682.43 | 26-DEC-08:10 |
General:Heating:EnergyTransfer:Zone:LGSTORE1 | 9.90 | 0.00 | 01-JAN-00:10 | 21803.48 | 19-FEB-08:10 |
Cooling:EnergyTransfer | 284.74 | 0.00 | 01-JAN-00:10 | 79209.55 | 10-AUG-16:10 |
Cooling:EnergyTransfer:Zone:LGSTORE1 | 68.03 | 0.00 | 01-JAN-00:10 | 13736.66 | 10-AUG-16:30 |
General:Cooling:EnergyTransfer | 284.74 | 0.00 | 01-JAN-00:10 | 79209.55 | 10-AUG-16:10 |
General:Cooling:EnergyTransfer:Zone:LGSTORE1 | 68.03 | 0.00 | 01-JAN-00:10 | 13736.66 | 10-AUG-16:30 |
EnergyTransfer:Zone:SMSTORE1 | 39.96 | 0.00 | 01-JAN-00:10 | 11090.82 | 08-AUG-22:00 |
Heating:EnergyTransfer:Zone:SMSTORE1 | 2.44 | 0.00 | 01-JAN-00:10 | 6985.38 | 19-FEB-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE1 | 2.44 | 0.00 | 01-JAN-00:10 | 6985.38 | 19-FEB-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE1 | 37.52 | 0.00 | 01-JAN-00:10 | 11090.82 | 08-AUG-22:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE1 | 37.52 | 0.00 | 01-JAN-00:10 | 11090.82 | 08-AUG-22:00 |
EnergyTransfer:Zone:SMSTORE2 | 30.68 | 0.00 | 01-JAN-00:10 | 8477.77 | 19-FEB-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE2 | 3.70 | 0.00 | 01-JAN-00:10 | 8477.77 | 19-FEB-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE2 | 3.70 | 0.00 | 01-JAN-00:10 | 8477.77 | 19-FEB-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE2 | 26.98 | 0.00 | 01-JAN-00:10 | 7045.38 | 10-AUG-16:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE2 | 26.98 | 0.00 | 01-JAN-00:10 | 7045.38 | 10-AUG-16:10 |
EnergyTransfer:Zone:SMSTORE3 | 30.21 | 0.00 | 01-JAN-00:10 | 9184.55 | 19-FEB-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE3 | 4.28 | 0.00 | 01-JAN-00:10 | 9184.55 | 19-FEB-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE3 | 4.28 | 0.00 | 01-JAN-00:10 | 9184.55 | 19-FEB-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE3 | 25.93 | 0.00 | 01-JAN-00:10 | 7049.52 | 10-AUG-16:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE3 | 25.93 | 0.00 | 01-JAN-00:10 | 7049.52 | 10-AUG-16:10 |
EnergyTransfer:Zone:SMSTORE4 | 28.81 | 0.00 | 01-JAN-00:10 | 9965.05 | 19-FEB-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE4 | 5.27 | 0.00 | 01-JAN-00:10 | 9965.05 | 19-FEB-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE4 | 5.27 | 0.00 | 01-JAN-00:10 | 9965.05 | 19-FEB-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE4 | 23.54 | 0.00 | 01-JAN-00:10 | 6911.96 | 10-AUG-16:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE4 | 23.54 | 0.00 | 01-JAN-00:10 | 6911.96 | 10-AUG-16:10 |
EnergyTransfer:Zone:LGSTORE2 | 50.06 | 0.00 | 01-JAN-00:10 | 21985.08 | 16-JAN-09:10 |
Heating:EnergyTransfer:Zone:LGSTORE2 | 11.17 | 0.00 | 01-JAN-00:10 | 21985.08 | 16-JAN-09:10 |
General:Heating:EnergyTransfer:Zone:LGSTORE2 | 11.17 | 0.00 | 01-JAN-00:10 | 21985.08 | 16-JAN-09:10 |
Cooling:EnergyTransfer:Zone:LGSTORE2 | 38.89 | 0.00 | 01-JAN-00:10 | 12292.34 | 10-AUG-15:00 |
General:Cooling:EnergyTransfer:Zone:LGSTORE2 | 38.89 | 0.00 | 01-JAN-00:10 | 12292.34 | 10-AUG-15:00 |
EnergyTransfer:Zone:SMSTORE5 | 24.56 | 0.00 | 01-JAN-00:10 | 11471.63 | 16-JAN-09:10 |
Heating:EnergyTransfer:Zone:SMSTORE5 | 6.84 | 0.00 | 01-JAN-00:10 | 11471.63 | 16-JAN-09:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE5 | 6.84 | 0.00 | 01-JAN-00:10 | 11471.63 | 16-JAN-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE5 | 17.73 | 0.00 | 01-JAN-00:10 | 6399.22 | 10-AUG-15:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE5 | 17.73 | 0.00 | 01-JAN-00:10 | 6399.22 | 10-AUG-15:00 |
EnergyTransfer:Zone:SMSTORE6 | 24.45 | 0.00 | 01-JAN-00:10 | 11724.83 | 16-JAN-09:10 |
Heating:EnergyTransfer:Zone:SMSTORE6 | 7.17 | 0.00 | 01-JAN-00:10 | 11724.83 | 16-JAN-09:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE6 | 7.17 | 0.00 | 01-JAN-00:10 | 11724.83 | 16-JAN-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE6 | 17.27 | 0.00 | 01-JAN-00:10 | 6349.98 | 10-AUG-15:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE6 | 17.27 | 0.00 | 01-JAN-00:10 | 6349.98 | 10-AUG-15:00 |
EnergyTransfer:Zone:SMSTORE7 | 24.39 | 0.00 | 01-JAN-00:10 | 12727.68 | 16-JAN-09:10 |
Heating:EnergyTransfer:Zone:SMSTORE7 | 8.76 | 0.00 | 01-JAN-00:10 | 12727.68 | 16-JAN-09:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE7 | 8.76 | 0.00 | 01-JAN-00:10 | 12727.68 | 16-JAN-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE7 | 15.63 | 0.00 | 01-JAN-00:10 | 6288.80 | 10-AUG-15:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE7 | 15.63 | 0.00 | 01-JAN-00:10 | 6288.80 | 10-AUG-15:00 |
EnergyTransfer:Zone:SMSTORE8 | 29.41 | 0.00 | 01-JAN-00:10 | 16891.33 | 15-JAN-09:10 |
Heating:EnergyTransfer:Zone:SMSTORE8 | 16.19 | 0.00 | 01-JAN-00:10 | 16891.33 | 15-JAN-09:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE8 | 16.19 | 0.00 | 01-JAN-00:10 | 16891.33 | 15-JAN-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE8 | 13.22 | 0.00 | 01-JAN-00:10 | 6679.49 | 10-AUG-14:50 |
General:Cooling:EnergyTransfer:Zone:SMSTORE8 | 13.22 | 0.00 | 01-JAN-00:10 | 6679.49 | 10-AUG-14:50 |
EnergyTransfer:HVAC | 364.14 | 0.00 | 01-JAN-00:10 | 118577.76 | 29-AUG-14:50 |
HeatingCoils:EnergyTransfer | 241.77 | 0.00 | 01-JAN-00:10 | 115760.30 | 16-JAN-09:10 |
CoolingCoils:EnergyTransfer | 122.37 | 0.00 | 01-JAN-00:10 | 118577.76 | 29-AUG-14:50 |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:31
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
LGSTORE1 | 0.000 | 0.000 | 9.902 | -68.031 | 0.000 | 0.000 | 25.456 | 87.116 | 26.249 | 18.892 | 0.000 | 0.453 | 0.001 | 0.000 | -8.881 | 0.000 | -31.262 | -59.895 |
SMSTORE1 | 0.000 | 0.000 | 2.439 | -37.518 | 0.000 | 0.000 | 12.375 | 53.201 | 13.125 | 9.320 | 0.000 | 0.246 | 0.001 | 0.000 | -4.753 | 0.000 | -15.914 | -32.521 |
SMSTORE2 | 0.000 | 0.000 | 3.695 | -26.982 | 0.000 | 0.000 | 7.552 | 37.572 | 10.421 | 9.311 | 0.000 | 0.241 | 0.000 | 0.000 | -4.691 | 0.000 | -16.316 | -20.802 |
SMSTORE3 | 0.000 | 0.000 | 4.279 | -25.929 | 0.000 | 0.000 | 7.567 | 37.572 | 10.421 | 9.327 | 0.000 | 0.241 | 0.001 | 0.000 | -4.631 | 0.000 | -16.226 | -22.619 |
SMSTORE4 | 0.000 | 0.000 | 5.272 | -23.541 | 0.000 | 0.000 | 7.596 | 37.572 | 10.421 | 9.357 | 0.000 | 0.241 | 0.001 | 0.000 | -4.556 | 0.000 | -16.080 | -26.283 |
LGSTORE2 | 0.000 | 0.000 | 11.171 | -38.886 | 0.000 | 0.000 | 26.370 | 37.162 | 19.173 | 18.863 | 0.000 | 0.434 | 0.002 | 0.000 | -8.735 | 0.000 | -28.931 | -36.620 |
SMSTORE5 | 0.000 | 0.000 | 6.835 | -17.728 | 0.000 | 0.000 | 13.113 | 19.120 | 9.586 | 9.401 | 0.000 | 0.241 | 0.000 | 0.000 | -4.384 | 0.000 | -15.947 | -20.238 |
SMSTORE6 | 0.000 | 0.000 | 7.174 | -17.274 | 0.000 | 0.000 | 13.122 | 19.120 | 9.586 | 9.410 | 0.000 | 0.241 | 0.003 | 0.000 | -4.364 | 0.000 | -15.917 | -21.099 |
SMSTORE7 | 0.000 | 0.000 | 8.756 | -15.630 | 0.000 | 0.000 | 13.159 | 19.120 | 9.586 | 9.441 | 0.000 | 0.241 | 0.001 | 0.000 | -4.283 | 0.000 | -15.789 | -24.602 |
SMSTORE8 | 0.000 | 0.000 | 16.190 | -13.218 | 0.000 | 0.000 | 13.220 | 19.120 | 9.586 | 9.524 | 0.000 | 0.251 | 0.004 | 0.000 | -3.990 | 0.000 | -19.346 | -31.338 |
Total Facility | 0.000 | 0.000 | 75.712 | -284.736 | 0.000 | 0.000 | 139.531 | 366.677 | 128.154 | 112.844 | 0.000 | 2.830 | 0.014 | 0.000 | -53.268 | 0.000 | -191.727 | -296.017 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
LGSTORE1 | 10-AUG-07:03 | 0.00 | 0.00 | 0.00 | -15049.61 | 0.00 | 0.00 | 186.75 | 75.00 | 74.62 | 142.08 | 0.00 | 0.00 | 14752.35 | 0.00 | -0.00 | 0.00 | -181.20 | 0.00 |
SMSTORE1 | 24-JUN-18:07 | 0.00 | 0.00 | 0.00 | -19702.47 | 0.00 | 0.00 | 985.05 | 2827.07 | 671.63 | 75.36 | 0.00 | 0.00 | 15268.09 | 0.00 | -0.00 | 0.00 | -124.73 | 0.00 |
SMSTORE2 | 10-AUG-06:03 | 0.00 | 0.00 | 0.00 | -14598.80 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 0.00 | 0.00 | 0.00 | 14613.68 | 0.00 | -74.84 | 0.00 | -14.36 | 0.00 |
SMSTORE3 | 10-AUG-06:03 | 0.00 | 0.00 | 0.00 | -14934.83 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 0.00 | 0.00 | 0.00 | 14950.20 | 0.00 | -75.32 | 0.00 | -14.36 | 0.00 |
SMSTORE4 | 10-AUG-06:03 | 0.00 | 0.00 | 0.00 | -13233.39 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 0.00 | 0.00 | 0.00 | 13246.76 | 0.00 | -73.36 | 0.00 | -14.33 | 0.00 |
LGSTORE2 | 24-JUL-07:03 | 0.00 | 0.00 | 0.00 | -18085.88 | 0.00 | 0.00 | 0.00 | 75.00 | 73.64 | 211.12 | 0.00 | 0.00 | 17903.81 | 0.00 | -0.00 | 0.00 | -177.69 | 0.00 |
SMSTORE5 | 14-AUG-07:03 | 0.00 | 0.00 | 0.00 | -8492.14 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 71.85 | 0.00 | 0.00 | 8512.95 | 0.00 | -0.00 | 0.00 | -166.98 | 0.00 |
SMSTORE6 | 14-AUG-07:03 | 0.00 | 0.00 | 0.00 | -8087.81 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 72.65 | 0.00 | 0.00 | 8107.71 | 0.00 | -0.00 | 0.00 | -166.87 | 0.00 |
SMSTORE7 | 14-AUG-07:03 | 0.00 | 0.00 | 0.00 | -6621.69 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 75.06 | 0.00 | 0.00 | 6638.81 | 0.00 | -0.00 | 0.00 | -166.50 | 0.00 |
SMSTORE8 | 10-AUG-14:50 | 0.00 | 0.00 | 0.00 | -6679.14 | 0.00 | 0.00 | 1359.36 | 1404.46 | 671.63 | 1483.75 | 0.00 | 991.10 | 768.84 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 10-AUG-16:10 | 0.00 | 0.00 | 0.00 | -79207.46 | 0.00 | 0.00 | 14302.70 | 23459.17 | 8059.50 | 8332.18 | 0.00 | 13366.93 | 11686.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
LGSTORE1 | 06-JAN-08:61 | 0.00 | 0.00 | 54834.04 | 0.00 | 0.00 | 0.00 | 0.00 | 75.00 | 73.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -375.43 | 0.00 | -897.08 | -53710.17 |
SMSTORE1 | 07-JAN-08:61 | 0.00 | 0.00 | 28607.49 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -338.28 | 0.00 | -609.33 | -27734.20 |
SMSTORE2 | 19-FEB-08:61 | 0.00 | 0.00 | 29327.81 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 37.31 | 391.52 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -661.04 | -29133.10 |
SMSTORE3 | 19-FEB-08:61 | 0.00 | 0.00 | 29403.23 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 37.31 | 396.11 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -654.15 | -29220.00 |
SMSTORE4 | 19-FEB-08:61 | 0.00 | 0.00 | 29183.81 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 37.31 | 400.56 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -646.63 | -29012.56 |
LGSTORE2 | 17-JAN-08:61 | 0.00 | 0.00 | 52892.46 | 0.00 | 0.00 | 0.00 | 0.00 | 75.00 | 73.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -468.29 | 0.00 | -742.48 | -51830.33 |
SMSTORE5 | 17-JAN-08:61 | 0.00 | 0.00 | 26848.03 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -234.75 | 0.00 | -410.55 | -26277.05 |
SMSTORE6 | 17-JAN-08:61 | 0.00 | 0.00 | 26700.99 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -232.97 | 0.00 | -408.20 | -26134.15 |
SMSTORE7 | 17-JAN-08:61 | 0.00 | 0.00 | 26467.17 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -225.02 | 0.00 | -396.82 | -25919.65 |
SMSTORE8 | 17-JAN-08:12 | 0.00 | 0.00 | 27831.70 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -227.21 | 0.00 | -528.43 | -27150.38 |
Total Facility | 26-DEC-08:61 | 0.00 | 0.00 | 253885.11 | 0.00 | 0.00 | 0.00 | 732.44 | 450.00 | 1452.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4133.28 | 0.00 | -6236.61 | -246149.88 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:31
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 1.8713 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 1.8713 | 0.2199 | 1.0000 | Not calculated | 0.4115 | 0.2199 | ||
PSZ-AC_2:2 | 0.9883 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0164 | 0.2024 | 1.0000 | Not calculated | 0.2057 | 0.2024 | ||
PSZ-AC_3:3 | 1.0220 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0220 | 0.2013 | 1.0000 | Not calculated | 0.2057 | 0.2013 | ||
PSZ-AC_4:4 | 1.0255 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0255 | 0.2006 | 1.0000 | Not calculated | 0.2057 | 0.2006 | ||
PSZ-AC_5:5 | 1.0154 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0154 | 0.2026 | 1.0000 | Not calculated | 0.2057 | 0.2026 | ||
PSZ-AC_6:6 | 1.7830 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 1.7830 | 0.2308 | 1.0000 | Not calculated | 0.4115 | 0.2308 | ||
PSZ-AC_7:7 | 0.9080 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9195 | 0.2237 | 1.0000 | Not calculated | 0.2057 | 0.2237 | ||
PSZ-AC_8:8 | 0.9014 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9130 | 0.2253 | 1.0000 | Not calculated | 0.2057 | 0.2253 | ||
PSZ-AC_9:9 | 0.8906 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9069 | 0.2269 | 1.0000 | Not calculated | 0.2057 | 0.2269 | ||
PSZ-AC_10:10 | 0.9425 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9647 | 0.2133 | 1.0000 | Not calculated | 0.2057 | 0.2133 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 1.8713 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 1.8713 | 1.0000 | 1.0000 | Not calculated | 0.4115 | 0.2199 | ||
PSZ-AC_2:2 | 0.9883 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9883 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.2082 | ||
PSZ-AC_3:3 | 1.0220 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0220 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.2013 | ||
PSZ-AC_4:4 | 1.0255 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0255 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.2006 | ||
PSZ-AC_5:5 | 1.0154 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0154 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.2026 | ||
PSZ-AC_6:6 | 1.7830 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 1.7830 | 1.0000 | 1.0000 | Not calculated | 0.4115 | 0.2308 | ||
PSZ-AC_7:7 | 0.9080 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9080 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.2266 | ||
PSZ-AC_8:8 | 0.9014 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9014 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.2282 | ||
PSZ-AC_9:9 | 0.8906 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.8906 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.2310 | ||
PSZ-AC_10:10 | 0.9425 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9425 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.2183 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
LGSTORE1 | PSZ-AC_1:1 | 0.000000 | 56.2505 | 0.001181 | 348.39 | 0.4115 | 1.0000 | 0.4115 | 1.000 | 0.4115 |
SMSTORE1 | PSZ-AC_2:2 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE2 | PSZ-AC_3:3 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE3 | PSZ-AC_4:4 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE4 | PSZ-AC_5:5 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
LGSTORE2 | PSZ-AC_6:6 | 0.000000 | 56.2505 | 0.001181 | 348.39 | 0.4115 | 1.0000 | 0.4115 | 1.000 | 0.4115 |
SMSTORE5 | PSZ-AC_7:7 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE6 | PSZ-AC_8:8 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE7 | PSZ-AC_9:9 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE8 | PSZ-AC_10:10 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC_1:1 | 0.000000 | 56.25 | 0.001181 | 348.3864 | 0.4115 | 0.4115 | 0.4115 |
PSZ-AC_2:2 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_3:3 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_4:4 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_5:5 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_6:6 | 0.000000 | 56.25 | 0.001181 | 348.3864 | 0.4115 | 0.4115 | 0.4115 |
PSZ-AC_7:7 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_8:8 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_9:9 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_10:10 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LGSTORE1 | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.8713 | 1.8713 | 1.8713 | No | 0.4115 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE1 | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9883 | 0.9883 | 0.9883 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE2 | PSZ-AC_3:3 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0220 | 1.0220 | 1.0220 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE3 | PSZ-AC_4:4 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0255 | 1.0255 | 1.0255 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE4 | PSZ-AC_5:5 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0154 | 1.0154 | 1.0154 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LGSTORE2 | PSZ-AC_6:6 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.7830 | 1.7830 | 1.7830 | No | 0.4115 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE5 | PSZ-AC_7:7 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9080 | 0.9080 | 0.9080 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE6 | PSZ-AC_8:8 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9014 | 0.9014 | 0.9014 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE7 | PSZ-AC_9:9 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8906 | 0.8906 | 0.8906 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE8 | PSZ-AC_10:10 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9425 | 0.9425 | 0.9425 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 1.8713 | 1.8713 | 1.8713 | 1.8713 | 0.4115 | 1.0000 |
PSZ-AC_2:2 | 0.9883 | 1.0164 | 0.9883 | 0.9883 | 0.2057 | 1.0000 |
PSZ-AC_3:3 | 1.0220 | 1.0220 | 1.0220 | 1.0220 | 0.2057 | 1.0000 |
PSZ-AC_4:4 | 1.0255 | 1.0255 | 1.0255 | 1.0255 | 0.2057 | 1.0000 |
PSZ-AC_5:5 | 1.0154 | 1.0154 | 1.0154 | 1.0154 | 0.2057 | 1.0000 |
PSZ-AC_6:6 | 1.7830 | 1.7830 | 1.7830 | 1.7830 | 0.4115 | 1.0000 |
PSZ-AC_7:7 | 0.9080 | 0.9195 | 0.9080 | 0.9080 | 0.2057 | 1.0000 |
PSZ-AC_8:8 | 0.9014 | 0.9130 | 0.9014 | 0.9014 | 0.2057 | 1.0000 |
PSZ-AC_9:9 | 0.8906 | 0.9069 | 0.8906 | 0.8906 | 0.2057 | 1.0000 |
PSZ-AC_10:10 | 0.9425 | 0.9647 | 0.9425 | 0.9425 | 0.2057 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LGSTORE1 | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.8713 | 1.8713 | 1.8713 | No | 0.4115 | 0.4072 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE1 | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9883 | 0.9883 | 0.9883 | No | 0.2057 | 0.4394 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE2 | PSZ-AC_3:3 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0220 | 1.0220 | 1.0220 | No | 0.2057 | 0.4342 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE3 | PSZ-AC_4:4 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0255 | 1.0255 | 1.0255 | No | 0.2057 | 0.4296 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE4 | PSZ-AC_5:5 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0154 | 1.0154 | 1.0154 | No | 0.2057 | 0.4215 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LGSTORE2 | PSZ-AC_6:6 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.7830 | 1.7830 | 1.7830 | No | 0.4115 | 0.4345 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE5 | PSZ-AC_7:7 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9080 | 0.9080 | 0.9080 | No | 0.2057 | 0.4083 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE6 | PSZ-AC_8:8 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9014 | 0.9014 | 0.9014 | No | 0.2057 | 0.4082 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE7 | PSZ-AC_9:9 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8906 | 0.8906 | 0.8906 | No | 0.2057 | 0.3965 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE8 | PSZ-AC_10:10 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9425 | 0.9425 | 0.9425 | No | 0.2057 | 0.3208 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 1.8713 | 1.8713 | 1.8713 | 1.8713 | 0.4115 | 1.0000 |
PSZ-AC_2:2 | 0.9883 | 0.9883 | 0.9883 | 0.9883 | 0.2057 | 1.0000 |
PSZ-AC_3:3 | 1.0220 | 1.0220 | 1.0220 | 1.0220 | 0.2057 | 1.0000 |
PSZ-AC_4:4 | 1.0255 | 1.0255 | 1.0255 | 1.0255 | 0.2057 | 1.0000 |
PSZ-AC_5:5 | 1.0154 | 1.0154 | 1.0154 | 1.0154 | 0.2057 | 1.0000 |
PSZ-AC_6:6 | 1.7830 | 1.7830 | 1.7830 | 1.7830 | 0.4115 | 1.0000 |
PSZ-AC_7:7 | 0.9080 | 0.9080 | 0.9080 | 0.9080 | 0.2057 | 1.0000 |
PSZ-AC_8:8 | 0.9014 | 0.9014 | 0.9014 | 0.9014 | 0.2057 | 1.0000 |
PSZ-AC_9:9 | 0.8906 | 0.8906 | 0.8906 | 0.8906 | 0.2057 | 1.0000 |
PSZ-AC_10:10 | 0.9425 | 0.9425 | 0.9425 | 0.9425 | 0.2057 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:31
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 |
Total gross floor area [m2] | 2090.32 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
LGSTORE1 | 348.39 | 348.39 | 0.00 | 112.00 |
SMSTORE1 | 174.19 | 174.19 | 0.00 | 112.00 |
SMSTORE2 | 174.19 | 174.19 | 0.00 | 84.29 |
SMSTORE3 | 174.19 | 174.19 | 0.00 | 84.29 |
SMSTORE4 | 174.19 | 174.19 | 0.00 | 84.29 |
LGSTORE2 | 348.39 | 348.39 | 0.00 | 77.29 |
SMSTORE5 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE6 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE7 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE8 | 174.19 | 174.19 | 0.00 | 77.29 |
Totals | 2090.32 | 2090.32 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 0.00 |
Number of hours not met | 0.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 302.22 | 144700.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 27.88 | 26821.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 366.68 | 23459.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 60.41 | 5507.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 128.15 | 8059.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 174.63 | 10992.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 64.21 | 13988.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 128.15 | 821.96 |
Natural Gas | 0.00 | 302.22 |
Additional | 0.00 | 0.00 |
Total | 128.15 | 1124.18 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 175.42 |
Space Heating | 0.00 |
Space Cooling | 13.34 |
Fans (All) | 83.54 |
Service Water Heating | 30.72 |
Receptacle Equipment | 61.31 |
Miscellaneous (All) | 393.22 |
Subtotal | 393.22 |
Natural Gas [MJ/m2] | |
Space Heating | 144.58 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 144.58 |
Subtotal | 144.58 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 32.62 |
Space Heating | 26.88 |
Space Cooling | 2.48 |
Fans (All) | 15.53 |
Service Water Heating | 5.71 |
Receptacle Equipment | 11.40 |
Miscellaneous | 5.37 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
TYPE1_OCC_SCH | 1630. | 5840. |
TYPE2_OCC_SCH | 995. | 4429. |
TYPE3_OCC_SCH | 1709. | 4064. |
LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 3767. | 8760. |
LTG_SCH_BASE_LPD2 | 3238. | 8760. |
LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 3296. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | 5084. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | 5084. | 8760. |
LTG_SCH_BASE_SMALL_LPD1 | 4453. | 8760. |
LTG_SCH_BASE_LPD1 | 4376. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | 3767. | 8760. |
LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 3584. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 4096. | 8760. |
TYPE1_EQUIP_SCH | 4868. | 8760. |
TYPE2_EQUIP_SCH | 3893. | 8760. |
TYPE3_EQUIP_SCH | 3584. | 8760. |
TYPE1_INFIL_SCH | 4302. | 8760. |
TYPE2_INFIL_SCH | 5164. | 8760. |
TYPE3_INFIL_SCH | 5438. | 8760. |
INFIL_DOOR_OPENING_SCH | 2477. | 4380. |
TYPE1_MINOA_MOTORIZEDDAMPER_SCH | 5579. | 5579. |
TYPE2_MINOA_MOTORIZEDDAMPER_SCH | 4429. | 4429. |
TYPE3_MINOA_MOTORIZEDDAMPER_SCH | 4064. | 4064. |
TYPE1_SWH_SCH | 2063. | 6048. |
TYPE2_SWH_SCH | 1831. | 4429. |
TYPE3_SWH_SCH | 1733. | 4064. |
AVERAGE_SWH_SCH | 1863. | 6152. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 7118. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 5839. | 5839. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 7300. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6570. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
TYPE1_HTGSETP_SCH_NO_OPTIMUM | LGSTORE1 DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
TYPE1_CLGSETP_SCH_NO_OPTIMUM | LGSTORE1 DUAL SP CONTROL | July | 23.89 | 365 | 23.89 | 365 |
TYPE2_HTGSETP_SCH_NO_OPTIMUM | SMSTORE2 DUAL SP CONTROL | January | 21.11 | 365 | 15.56 | 365 |
TYPE2_CLGSETP_SCH_NO_OPTIMUM | SMSTORE2 DUAL SP CONTROL | July | 23.89 | 365 | 29.44 | 365 |
TYPE3_HTGSETP_SCH_NO_OPTIMUM | LGSTORE2 DUAL SP CONTROL | January | 21.11 | 365 | 15.56 | 365 |
TYPE3_CLGSETP_SCH_NO_OPTIMUM | LGSTORE2 DUAL SP CONTROL | July | 23.89 | 365 | 29.44 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:31
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
LGSTORE1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 8756.33 | 3.67 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 8756.00 | 4.00 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 8757.00 | 3.00 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 8758.83 | 1.17 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 8758.67 | 1.33 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 8758.67 | 1.33 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 8758.67 | 1.33 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 8758.67 | 1.33 | 0.00 | 0.00 | 0.00 |
Min | 8756.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 4.00 | 0.00 | 0.00 | 0.00 |
Average | 8758.28 | 1.72 | 0.00 | 0.00 | 0.00 |
Sum | 87582.83 | 17.17 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
LGSTORE1 | 89041.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 43777.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 25473.50 | 1.50 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 25473.50 | 1.50 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 25473.67 | 1.33 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 93207.00 | 4.00 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 45909.50 | 2.50 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 45909.50 | 2.50 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 45909.50 | 2.50 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 45909.50 | 2.50 | 0.00 | 0.00 | 0.00 |
Min | 25473.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 93207.00 | 4.00 | 0.00 | 0.00 | 0.00 |
Average | 48608.37 | 1.83 | 0.00 | 0.00 | 0.00 |
Sum | 486083.67 | 18.33 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
LGSTORE1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 8735.33 | 24.67 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 8734.83 | 25.17 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 8739.50 | 20.50 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 8750.17 | 9.83 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 8749.00 | 11.00 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 8749.50 | 10.50 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 8751.67 | 8.33 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 8754.00 | 6.00 | 0.00 | 0.00 | 0.00 |
Min | 8734.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 25.17 | 0.00 | 0.00 | 0.00 |
Average | 8748.40 | 11.60 | 0.00 | 0.00 | 0.00 |
Sum | 87484.00 | 116.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
LGSTORE1 | 89041.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 43777.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 25469.33 | 5.67 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 25469.50 | 5.50 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 25470.17 | 4.83 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 93203.00 | 8.00 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 45905.50 | 6.50 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 45905.50 | 6.50 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 45906.00 | 6.00 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 45906.00 | 6.00 | 0.00 | 0.00 | 0.00 |
Min | 25469.33 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 93203.00 | 8.00 | 0.00 | 0.00 | 0.00 |
Average | 48605.30 | 4.90 | 0.00 | 0.00 | 0.00 |
Sum | 486053.00 | 49.00 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:31
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:31
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
For: Environment
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTRIPMALL
For: Environment
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4C
For: Environment
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_SEATTLE
For: Environment
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: ZoneCoolingSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.116514E+10 | 9667.85 | 07-JAN-00:03 | -1.2 | -1.2 | 0.106541E+10 | 1275.40 | 08-JAN-18:00 | 3.30 | -0.3 |
February | 0.190318E+10 | 9428.20 | 18-FEB-00:03 | -0.8 | -1.8 | 0.970970E+09 | 1377.46 | 27-FEB-17:19 | 18.33 | 12.12 |
March | 0.379278E+10 | 7252.57 | 24-MAR-23:03 | 3.80 | -1.4 | 0.107812E+10 | 1503.26 | 18-MAR-12:00 | 3.80 | -1.4 |
April | 0.541321E+10 | 9038.34 | 27-APR-16:10 | 27.02 | 16.89 | 0.114214E+10 | 1685.89 | 29-APR-12:00 | 20.00 | 14.70 |
May | 0.721401E+10 | 8938.38 | 15-MAY-16:20 | 24.07 | 12.90 | 0.128637E+10 | 1685.95 | 07-MAY-12:00 | 24.07 | 12.90 |
June | 0.806013E+10 | 10425.19 | 28-JUN-17:00 | 26.70 | 16.74 | 0.132885E+10 | 1685.93 | 11-JUN-12:20 | 26.70 | 16.74 |
July | 0.105721E+11 | 14681.85 | 24-JUL-07:03 | 19.37 | 15.37 | 0.140931E+10 | 1685.97 | 15-JUL-12:00 | 19.37 | 15.37 |
August | 0.111277E+11 | 15050.96 | 10-AUG-07:03 | 19.83 | 15.97 | 0.139149E+10 | 1685.95 | 26-AUG-12:00 | 22.20 | 17.01 |
September | 0.830231E+10 | 10652.31 | 14-SEP-16:10 | 24.50 | 16.99 | 0.132287E+10 | 1685.97 | 23-SEP-12:39 | 21.47 | 16.94 |
October | 0.603161E+10 | 7981.78 | 04-OCT-17:10 | 20.13 | 11.18 | 0.120040E+10 | 1685.86 | 08-OCT-16:10 | 19.72 | 12.98 |
November | 0.282970E+10 | 6997.18 | 17-NOV-00:03 | 4.40 | 4.09 | 0.105383E+10 | 1685.80 | 04-NOV-12:00 | 4.40 | 4.09 |
December | 0.161913E+10 | 8897.01 | 22-DEC-00:03 | 0.40 | -0.8 | 0.107082E+10 | 1275.84 | 03-DEC-13:00 | 0.40 | -0.8 |
Annual Sum or Average | 0.680310E+11 | 0.143206E+11 | ||||||||
Minimum of Months | 0.116514E+10 | 6997.18 | -1.2 | -1.8 | 0.970970E+09 | 1275.40 | 0.40 | -1.4 | ||
Maximum of Months | 0.111277E+11 | 15050.96 | 27.02 | 16.99 | 0.140931E+10 | 1685.97 | 26.70 | 17.01 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.620406E+09 | 3056.05 | 14-JAN-10:03 | 2.80 | 1.41 | 0.552858E+09 | 776.10 | 29-JAN-18:00 | 9.40 | 5.55 |
February | 0.101361E+10 | 2901.32 | 05-FEB-09:01 | 4.50 | 3.53 | 0.515424E+09 | 842.90 | 26-FEB-18:00 | 10.00 | 7.75 |
March | 0.189231E+10 | 3165.62 | 05-MAR-09:01 | 3.40 | 2.59 | 0.594904E+09 | 842.90 | 19-MAR-17:30 | 10.30 | 6.58 |
April | 0.262137E+10 | 17738.23 | 27-APR-20:09 | 19.03 | 13.28 | 0.629669E+09 | 842.92 | 29-APR-12:00 | 20.00 | 14.70 |
May | 0.377580E+10 | 19301.30 | 14-MAY-19:30 | 18.05 | 10.80 | 0.687042E+09 | 842.94 | 07-MAY-12:00 | 18.05 | 10.80 |
June | 0.481143E+10 | 19702.15 | 24-JUN-18:07 | 18.72 | 11.75 | 0.674348E+09 | 842.93 | 11-JUN-12:20 | 18.72 | 11.75 |
July | 0.621918E+10 | 19163.90 | 07-JUL-21:35 | 18.53 | 11.87 | 0.703602E+09 | 842.94 | 15-JUL-12:00 | 20.60 | 16.71 |
August | 0.654747E+10 | 17998.35 | 14-AUG-21:37 | 18.83 | 12.89 | 0.693466E+09 | 842.95 | 26-AUG-12:20 | 22.20 | 17.39 |
September | 0.473564E+10 | 17810.67 | 10-SEP-19:10 | 19.22 | 13.40 | 0.677611E+09 | 842.95 | 23-SEP-12:39 | 21.47 | 16.94 |
October | 0.295009E+10 | 19319.33 | 04-OCT-20:01 | 16.65 | 10.41 | 0.659704E+09 | 842.90 | 08-OCT-16:19 | 19.43 | 12.92 |
November | 0.146352E+10 | 3789.24 | 11-NOV-09:01 | 0.78 | 0.55 | 0.563898E+09 | 842.91 | 04-NOV-12:00 | 0.78 | 0.55 |
December | 0.867034E+09 | 3683.80 | 25-DEC-10:13 | -0.0 | -0.1 | 0.560247E+09 | 818.59 | 03-DEC-18:00 | -0.0 | -0.1 |
Annual Sum or Average | 0.375179E+11 | 0.751277E+10 | ||||||||
Minimum of Months | 0.620406E+09 | 2901.32 | -0.0 | -0.1 | 0.515424E+09 | 776.10 | -0.0 | -0.1 | ||
Maximum of Months | 0.654747E+10 | 19702.15 | 19.22 | 13.40 | 0.703602E+09 | 842.95 | 22.20 | 17.39 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.357735E+09 | 3019.10 | 21-JAN-18:33 | 2.93 | 1.77 | 0.317535E+09 | 637.68 | 07-JAN-13:00 | 2.93 | 1.77 |
February | 0.707718E+09 | 3389.24 | 18-FEB-10:03 | 1.20 | 0.11 | 0.295434E+09 | 734.26 | 25-FEB-13:50 | 14.50 | 11.67 |
March | 0.158248E+10 | 3600.91 | 02-MAR-08:61 | 2.15 | 1.10 | 0.346153E+09 | 834.58 | 18-MAR-12:00 | 17.20 | 10.94 |
April | 0.204533E+10 | 5068.30 | 27-APR-16:10 | 27.02 | 16.89 | 0.362547E+09 | 842.91 | 29-APR-12:00 | 20.00 | 14.70 |
May | 0.273106E+10 | 4785.28 | 06-MAY-13:00 | 23.90 | 17.58 | 0.411988E+09 | 842.93 | 06-MAY-12:09 | 23.90 | 17.58 |
June | 0.334284E+10 | 5357.77 | 28-JUN-16:10 | 26.20 | 16.37 | 0.414444E+09 | 842.91 | 10-JUN-12:09 | 26.20 | 16.37 |
July | 0.428713E+10 | 10227.67 | 24-JUL-06:03 | 17.48 | 14.11 | 0.419454E+09 | 842.94 | 15-JUL-12:00 | 17.48 | 14.11 |
August | 0.474191E+10 | 14601.79 | 10-AUG-06:03 | 17.43 | 14.93 | 0.431119E+09 | 842.95 | 26-AUG-12:20 | 22.20 | 17.39 |
September | 0.327959E+10 | 5556.70 | 14-SEP-14:00 | 23.90 | 17.12 | 0.406000E+09 | 842.95 | 23-SEP-12:39 | 21.47 | 16.94 |
October | 0.228057E+10 | 4496.95 | 04-OCT-14:00 | 21.10 | 11.41 | 0.377480E+09 | 842.89 | 07-OCT-12:09 | 16.28 | 11.84 |
November | 0.106656E+10 | 2822.22 | 16-NOV-08:61 | 4.68 | 2.83 | 0.318516E+09 | 842.91 | 04-NOV-12:00 | 4.68 | 2.83 |
December | 0.558721E+09 | 3083.86 | 04-DEC-08:61 | 3.58 | 3.15 | 0.317623E+09 | 692.71 | 02-DEC-13:00 | 3.58 | 3.15 |
Annual Sum or Average | 0.269816E+11 | 0.441829E+10 | ||||||||
Minimum of Months | 0.357735E+09 | 2822.22 | 1.20 | 0.11 | 0.295434E+09 | 637.68 | 2.93 | 1.77 | ||
Maximum of Months | 0.474191E+10 | 14601.79 | 27.02 | 17.58 | 0.431119E+09 | 842.95 | 26.20 | 17.58 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.294453E+09 | 2929.71 | 18-JAN-20:53 | 3.30 | 1.92 | 0.317453E+09 | 637.68 | 21-JAN-13:39 | 2.43 | 2.18 |
February | 0.613384E+09 | 3275.76 | 17-FEB-11:23 | 1.70 | 0.58 | 0.294544E+09 | 724.41 | 25-FEB-13:50 | 14.50 | 11.67 |
March | 0.142394E+10 | 3541.22 | 02-MAR-08:61 | 2.15 | 1.10 | 0.343471E+09 | 826.53 | 18-MAR-12:00 | 17.20 | 10.94 |
April | 0.191425E+10 | 4931.31 | 27-APR-16:10 | 27.02 | 16.89 | 0.359085E+09 | 842.91 | 29-APR-12:00 | 20.00 | 14.70 |
May | 0.262922E+10 | 4742.00 | 06-MAY-13:00 | 23.90 | 17.58 | 0.410182E+09 | 842.93 | 06-MAY-12:09 | 23.90 | 17.58 |
June | 0.327565E+10 | 5325.52 | 28-JUN-16:10 | 26.20 | 16.37 | 0.414185E+09 | 842.91 | 10-JUN-12:09 | 26.20 | 16.37 |
July | 0.425348E+10 | 10481.30 | 24-JUL-06:03 | 17.48 | 14.11 | 0.419427E+09 | 842.94 | 15-JUL-12:00 | 17.48 | 14.11 |
August | 0.472934E+10 | 14938.01 | 10-AUG-06:03 | 17.43 | 14.93 | 0.431104E+09 | 842.95 | 26-AUG-12:20 | 22.20 | 17.39 |
September | 0.321263E+10 | 5540.40 | 14-SEP-14:00 | 23.90 | 17.12 | 0.405432E+09 | 842.95 | 23-SEP-12:39 | 21.47 | 16.94 |
October | 0.216007E+10 | 4401.14 | 04-OCT-14:00 | 21.10 | 11.41 | 0.373761E+09 | 842.89 | 07-OCT-12:09 | 16.28 | 11.84 |
November | 0.949716E+09 | 2715.19 | 10-NOV-08:61 | 5.18 | 4.64 | 0.316939E+09 | 842.90 | 04-NOV-12:00 | 5.18 | 4.64 |
December | 0.473175E+09 | 2511.66 | 08-DEC-09:25 | 4.70 | 4.07 | 0.317402E+09 | 686.66 | 02-DEC-13:00 | 4.70 | 4.07 |
Annual Sum or Average | 0.259293E+11 | 0.440298E+10 | ||||||||
Minimum of Months | 0.294453E+09 | 2511.66 | 1.70 | 0.58 | 0.294544E+09 | 637.68 | 2.43 | 2.18 | ||
Maximum of Months | 0.472934E+10 | 14938.01 | 27.02 | 17.58 | 0.431104E+09 | 842.95 | 26.20 | 17.58 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.209260E+09 | 2545.41 | 23-JAN-20:45 | 4.50 | 3.07 | 0.317355E+09 | 637.68 | 07-JAN-13:00 | 4.50 | 3.07 |
February | 0.486807E+09 | 2873.13 | 14-FEB-11:03 | 3.58 | 1.62 | 0.293300E+09 | 707.30 | 25-FEB-13:50 | 14.50 | 11.67 |
March | 0.119764E+10 | 3468.78 | 02-MAR-08:61 | 2.15 | 1.10 | 0.339404E+09 | 810.74 | 18-MAR-12:00 | 17.20 | 10.94 |
April | 0.169359E+10 | 4609.62 | 27-APR-16:10 | 27.02 | 16.89 | 0.353176E+09 | 842.91 | 29-APR-12:00 | 20.00 | 14.70 |
May | 0.237886E+10 | 4525.51 | 06-MAY-13:00 | 23.90 | 17.58 | 0.404698E+09 | 842.93 | 06-MAY-12:09 | 23.90 | 17.58 |
June | 0.301092E+10 | 5171.70 | 28-JUN-16:10 | 26.20 | 16.37 | 0.413050E+09 | 842.91 | 10-JUN-12:09 | 26.20 | 16.37 |
July | 0.401912E+10 | 9341.17 | 24-JUL-06:03 | 17.48 | 14.11 | 0.419267E+09 | 842.94 | 15-JUL-12:00 | 17.48 | 14.11 |
August | 0.449827E+10 | 13235.65 | 10-AUG-06:03 | 17.43 | 14.93 | 0.430982E+09 | 842.95 | 26-AUG-12:20 | 22.20 | 17.39 |
September | 0.297899E+10 | 5385.16 | 14-SEP-14:00 | 23.90 | 17.12 | 0.403141E+09 | 842.95 | 23-SEP-12:50 | 21.83 | 17.05 |
October | 0.193014E+10 | 4135.70 | 04-OCT-14:00 | 21.10 | 11.41 | 0.367427E+09 | 842.89 | 07-OCT-12:09 | 16.28 | 11.84 |
November | 0.779979E+09 | 2652.13 | 30-NOV-10:35 | 4.07 | 3.50 | 0.314683E+09 | 842.90 | 04-NOV-12:09 | 4.07 | 3.50 |
December | 0.357003E+09 | 2650.28 | 11-DEC-10:25 | 4.15 | 4.15 | 0.317127E+09 | 674.27 | 02-DEC-13:00 | 4.15 | 4.15 |
Annual Sum or Average | 0.235406E+11 | 0.437361E+10 | ||||||||
Minimum of Months | 0.209260E+09 | 2545.41 | 2.15 | 1.10 | 0.293300E+09 | 637.68 | 4.07 | 3.07 | ||
Maximum of Months | 0.449827E+10 | 13235.65 | 27.02 | 17.58 | 0.430982E+09 | 842.95 | 26.20 | 17.58 |
Report: ZoneCoolingSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.115591E+09 | 7921.59 | 19-JAN-18:23 | 2.50 | 1.27 | 0.108442E+10 | 1700.53 | 07-JAN-15:20 | 2.50 | 1.27 |
February | 0.590253E+09 | 7454.16 | 14-FEB-18:43 | 3.48 | 2.13 | 0.994933E+09 | 1906.37 | 27-FEB-15:50 | 19.50 | 12.39 |
March | 0.182514E+10 | 5654.74 | 30-MAR-09:03 | 7.38 | 4.78 | 0.113381E+10 | 2247.75 | 18-MAR-14:00 | 7.38 | 4.78 |
April | 0.298526E+10 | 7758.72 | 27-APR-15:00 | 27.20 | 17.29 | 0.115765E+10 | 2247.88 | 29-APR-14:30 | 21.65 | 15.01 |
May | 0.442871E+10 | 7702.60 | 06-MAY-13:40 | 23.90 | 16.96 | 0.131289E+10 | 2247.91 | 06-MAY-14:00 | 23.90 | 17.27 |
June | 0.505556E+10 | 9235.23 | 28-JUN-15:00 | 26.10 | 15.54 | 0.139048E+10 | 2247.84 | 03-JUN-14:09 | 26.10 | 15.54 |
July | 0.663550E+10 | 18085.04 | 24-JUL-07:03 | 19.37 | 15.37 | 0.143078E+10 | 2247.96 | 15-JUL-14:09 | 19.37 | 15.37 |
August | 0.744764E+10 | 17975.75 | 14-AUG-07:03 | 16.98 | 14.61 | 0.147517E+10 | 2247.94 | 26-AUG-14:50 | 20.25 | 16.60 |
September | 0.519868E+10 | 9785.92 | 14-SEP-14:30 | 23.90 | 17.04 | 0.134349E+10 | 2247.92 | 23-SEP-14:09 | 23.30 | 17.84 |
October | 0.330798E+10 | 7102.83 | 04-OCT-14:50 | 21.60 | 11.48 | 0.119652E+10 | 2247.70 | 07-OCT-14:09 | 17.38 | 12.04 |
November | 0.100520E+10 | 7670.60 | 11-NOV-10:43 | 3.03 | 2.40 | 0.105828E+10 | 2247.86 | 04-NOV-14:50 | 3.03 | 2.40 |
December | 0.290620E+09 | 8323.50 | 21-DEC-19:03 | 1.87 | 0.19 | 0.108625E+10 | 1700.53 | 16-DEC-15:50 | 1.87 | 0.19 |
Annual Sum or Average | 0.388861E+11 | 0.146647E+11 | ||||||||
Minimum of Months | 0.115591E+09 | 5654.74 | 1.87 | 0.19 | 0.994933E+09 | 1700.53 | 1.87 | 0.19 | ||
Maximum of Months | 0.744764E+10 | 18085.04 | 27.20 | 17.29 | 0.147517E+10 | 2247.96 | 26.10 | 17.84 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 50771634.74 | 3677.93 | 06-JAN-18:53 | 0.60 | 0.60 | 0.542195E+09 | 850.24 | 21-JAN-15:09 | 3.30 | 2.80 |
February | 0.234386E+09 | 2157.32 | 08-FEB-16:15 | 7.03 | 3.66 | 0.499395E+09 | 975.26 | 27-FEB-17:10 | 18.62 | 12.15 |
March | 0.762516E+09 | 2445.53 | 04-MAR-18:55 | 5.60 | 3.13 | 0.572002E+09 | 1123.86 | 18-MAR-14:00 | 20.00 | 10.34 |
April | 0.121844E+10 | 4072.20 | 27-APR-15:00 | 27.20 | 17.29 | 0.589606E+09 | 1123.89 | 29-APR-14:30 | 21.65 | 15.01 |
May | 0.182261E+10 | 3949.36 | 06-MAY-13:50 | 23.90 | 16.80 | 0.673489E+09 | 1123.90 | 06-MAY-14:00 | 23.90 | 17.27 |
June | 0.233408E+10 | 4769.91 | 28-JUN-15:00 | 26.10 | 15.54 | 0.703195E+09 | 1123.87 | 03-JUN-14:09 | 26.10 | 15.54 |
July | 0.328725E+10 | 8433.43 | 24-JUL-07:03 | 19.37 | 15.37 | 0.717274E+09 | 1123.93 | 15-JUL-14:09 | 19.37 | 15.37 |
August | 0.373973E+10 | 8493.29 | 14-AUG-07:03 | 16.98 | 14.61 | 0.738855E+09 | 1123.91 | 26-AUG-14:09 | 20.45 | 16.60 |
September | 0.236629E+10 | 5050.67 | 14-SEP-14:30 | 23.90 | 17.04 | 0.682652E+09 | 1123.91 | 23-SEP-14:09 | 23.30 | 17.84 |
October | 0.136686E+10 | 3759.70 | 04-OCT-15:00 | 21.70 | 11.49 | 0.610348E+09 | 1123.84 | 07-OCT-14:09 | 17.38 | 12.04 |
November | 0.418463E+09 | 2583.83 | 24-NOV-20:25 | 5.00 | 3.73 | 0.531056E+09 | 1123.88 | 04-NOV-14:00 | 5.00 | 3.73 |
December | 0.126830E+09 | 3750.69 | 06-DEC-20:53 | 0.20 | 0.14 | 0.543160E+09 | 851.07 | 02-DEC-15:09 | 0.20 | 0.14 |
Annual Sum or Average | 0.177282E+11 | 0.740323E+10 | ||||||||
Minimum of Months | 50771634.74 | 2157.32 | 0.20 | 0.14 | 0.499395E+09 | 850.24 | 0.20 | 0.14 | ||
Maximum of Months | 0.373973E+10 | 8493.29 | 27.20 | 17.29 | 0.738855E+09 | 1123.93 | 26.10 | 17.84 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 47702313.19 | 3611.73 | 06-JAN-18:13 | 0.93 | 0.93 | 0.542190E+09 | 850.24 | 07-JAN-15:50 | 2.88 | 1.32 |
February | 0.219025E+09 | 3186.85 | 16-FEB-11:53 | 2.80 | 1.22 | 0.499149E+09 | 970.85 | 27-FEB-17:10 | 18.62 | 12.15 |
March | 0.718334E+09 | 2169.28 | 01-MAR-12:00 | 8.30 | 4.65 | 0.571149E+09 | 1123.86 | 18-MAR-14:00 | 20.00 | 10.34 |
April | 0.117444E+10 | 3998.62 | 27-APR-15:00 | 27.20 | 17.29 | 0.588044E+09 | 1123.89 | 29-APR-14:39 | 21.83 | 15.09 |
May | 0.178116E+10 | 3876.77 | 06-MAY-13:50 | 23.90 | 16.80 | 0.671121E+09 | 1123.90 | 06-MAY-14:00 | 23.90 | 17.27 |
June | 0.228092E+10 | 4711.35 | 28-JUN-15:00 | 26.10 | 15.54 | 0.702445E+09 | 1123.87 | 03-JUN-14:09 | 26.10 | 15.54 |
July | 0.322175E+10 | 8008.10 | 24-JUL-07:03 | 19.37 | 15.37 | 0.717118E+09 | 1123.93 | 15-JUL-14:09 | 19.37 | 15.37 |
August | 0.367599E+10 | 8088.81 | 14-AUG-07:03 | 16.98 | 14.61 | 0.738779E+09 | 1123.91 | 26-AUG-14:09 | 20.45 | 16.60 |
September | 0.232521E+10 | 4996.96 | 14-SEP-14:30 | 23.90 | 17.04 | 0.681697E+09 | 1123.91 | 23-SEP-14:09 | 23.30 | 17.84 |
October | 0.132610E+10 | 3682.93 | 04-OCT-15:00 | 21.70 | 11.49 | 0.608854E+09 | 1123.84 | 07-OCT-14:09 | 17.38 | 12.04 |
November | 0.391429E+09 | 2829.68 | 29-NOV-19:23 | 4.40 | 3.29 | 0.530739E+09 | 1123.88 | 04-NOV-14:00 | 4.40 | 3.29 |
December | 0.111648E+09 | 2744.22 | 22-DEC-18:55 | 4.30 | 1.78 | 0.543150E+09 | 850.29 | 02-DEC-15:09 | 4.30 | 1.78 |
Annual Sum or Average | 0.172737E+11 | 0.739443E+10 | ||||||||
Minimum of Months | 47702313.19 | 2169.28 | 0.93 | 0.93 | 0.499149E+09 | 850.24 | 2.88 | 1.32 | ||
Maximum of Months | 0.367599E+10 | 8088.81 | 27.20 | 17.29 | 0.738779E+09 | 1123.93 | 26.10 | 17.84 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 19367999.96 | 3199.03 | 20-JAN-18:53 | 2.80 | 1.45 | 0.542192E+09 | 850.24 | 14-JAN-15:30 | 2.80 | 1.45 |
February | 0.152189E+09 | 2264.31 | 08-FEB-13:45 | 6.60 | 3.81 | 0.498217E+09 | 963.69 | 27-FEB-15:50 | 19.50 | 12.39 |
March | 0.558135E+09 | 1902.44 | 01-MAR-12:00 | 8.30 | 4.65 | 0.568612E+09 | 1123.86 | 18-MAR-14:00 | 20.00 | 10.34 |
April | 0.100543E+10 | 3799.25 | 27-APR-15:00 | 27.20 | 17.29 | 0.582610E+09 | 1123.89 | 29-APR-14:39 | 21.83 | 15.09 |
May | 0.160643E+10 | 3677.01 | 06-MAY-13:50 | 23.90 | 16.80 | 0.661125E+09 | 1123.90 | 06-MAY-14:00 | 23.90 | 17.27 |
June | 0.209466E+10 | 4571.39 | 28-JUN-15:00 | 26.10 | 15.54 | 0.698359E+09 | 1123.87 | 03-JUN-14:09 | 26.10 | 15.54 |
July | 0.302560E+10 | 6297.18 | 24-JUL-07:03 | 19.37 | 15.37 | 0.716373E+09 | 1123.93 | 15-JUL-14:20 | 19.37 | 15.37 |
August | 0.349810E+10 | 6622.21 | 14-AUG-07:03 | 16.98 | 14.61 | 0.738369E+09 | 1123.91 | 26-AUG-14:09 | 20.45 | 16.60 |
September | 0.216131E+10 | 4894.11 | 14-SEP-14:30 | 23.90 | 17.04 | 0.676402E+09 | 1123.92 | 23-SEP-14:09 | 23.30 | 17.84 |
October | 0.115069E+10 | 3403.43 | 04-OCT-15:00 | 21.70 | 11.49 | 0.602707E+09 | 1123.84 | 07-OCT-14:09 | 17.38 | 12.04 |
November | 0.292251E+09 | 2479.25 | 16-NOV-20:25 | 5.55 | 3.84 | 0.529825E+09 | 1123.88 | 04-NOV-14:50 | 5.55 | 3.84 |
December | 65932299.82 | 2440.96 | 13-DEC-18:35 | 5.73 | 2.62 | 0.543117E+09 | 850.24 | 02-DEC-15:09 | 5.73 | 2.62 |
Annual Sum or Average | 0.156301E+11 | 0.735791E+10 | ||||||||
Minimum of Months | 19367999.96 | 1902.44 | 2.80 | 1.45 | 0.498217E+09 | 850.24 | 2.80 | 1.45 | ||
Maximum of Months | 0.349810E+10 | 6622.21 | 27.20 | 17.29 | 0.738369E+09 | 1123.93 | 26.10 | 17.84 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 722386.77 | 843.59 | 11-JAN-18:30 | 12.50 | 9.44 | 0.542188E+09 | 850.24 | 28-JAN-15:39 | 6.70 | 5.64 |
February | 45568390.90 | 1585.14 | 28-FEB-20:25 | 9.40 | 7.97 | 0.496707E+09 | 931.90 | 27-FEB-15:50 | 9.40 | 7.97 |
March | 0.220098E+09 | 2023.52 | 24-MAR-18:45 | 7.30 | 1.76 | 0.565442E+09 | 1119.15 | 18-MAR-14:00 | 7.30 | 1.76 |
April | 0.676407E+09 | 3784.61 | 27-APR-15:00 | 27.20 | 17.29 | 0.575204E+09 | 1123.89 | 29-APR-14:00 | 22.20 | 15.23 |
May | 0.125520E+10 | 3640.88 | 06-MAY-13:40 | 23.90 | 16.96 | 0.645839E+09 | 1123.91 | 06-MAY-14:00 | 23.90 | 17.27 |
June | 0.188679E+10 | 4582.63 | 28-JUN-15:00 | 26.10 | 15.54 | 0.690154E+09 | 1123.87 | 03-JUN-14:09 | 26.10 | 15.54 |
July | 0.287180E+10 | 6359.45 | 24-JUL-15:00 | 30.60 | 18.78 | 0.713812E+09 | 1123.93 | 15-JUL-14:50 | 30.60 | 18.78 |
August | 0.342779E+10 | 6679.49 | 10-AUG-14:50 | 30.07 | 18.95 | 0.736854E+09 | 1123.90 | 26-AUG-14:09 | 20.45 | 16.60 |
September | 0.194961E+10 | 4998.96 | 14-SEP-14:20 | 23.90 | 17.07 | 0.664705E+09 | 1123.92 | 23-SEP-14:09 | 23.30 | 17.84 |
October | 0.765508E+09 | 3016.90 | 04-OCT-15:00 | 21.70 | 11.49 | 0.594010E+09 | 1123.85 | 07-OCT-14:09 | 17.38 | 12.04 |
November | 0.109296E+09 | 1546.38 | 15-NOV-13:15 | 9.60 | 6.62 | 0.528836E+09 | 1123.87 | 04-NOV-14:00 | 9.60 | 6.62 |
December | 8887902.59 | 910.09 | 02-DEC-12:00 | 12.20 | 6.13 | 0.543112E+09 | 850.24 | 09-DEC-15:00 | 5.60 | 4.08 |
Annual Sum or Average | 0.132177E+11 | 0.729686E+10 | ||||||||
Minimum of Months | 722386.77 | 843.59 | 7.30 | 1.76 | 0.496707E+09 | 850.24 | 5.60 | 1.76 | ||
Maximum of Months | 0.342779E+10 | 6679.49 | 30.60 | 18.95 | 0.736854E+09 | 1123.93 | 30.60 | 18.78 |
Report: ZoneHeatingSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.313857E+10 | 54834.08 | 06-JAN-08:61 | -2.7 |
February | 0.184173E+10 | 54807.26 | 08-FEB-08:61 | -0.4 |
March | 0.750207E+09 | 54812.08 | 25-MAR-07:01 | 2.15 |
April | 0.278084E+09 | 54802.20 | 19-APR-07:01 | 4.18 |
May | 84132182.58 | 18822.55 | 18-MAY-07:02 | 6.10 |
June | 57016179.31 | 798.09 | 14-JUN-07:25 | 10.85 |
July | 23366594.03 | 1249.04 | 24-JUL-07:07 | 19.37 |
August | 33069726.02 | 1252.01 | 10-AUG-07:07 | 19.83 |
September | 54709480.01 | 894.68 | 14-SEP-07:10 | 14.18 |
October | 0.149009E+09 | 54353.64 | 28-OCT-07:01 | 7.80 |
November | 0.105946E+10 | 54825.88 | 24-NOV-08:61 | 1.97 |
December | 0.243265E+10 | 54828.19 | 11-DEC-08:61 | 2.88 |
Annual Sum or Average | 0.990200E+10 | |||
Minimum of Months | 23366594.03 | 798.09 | -2.7 | |
Maximum of Months | 0.313857E+10 | 54834.08 | 19.83 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.746622E+09 | 28607.56 | 07-JAN-08:61 | -3.8 |
February | 0.428334E+09 | 28595.18 | 08-FEB-08:61 | -0.4 |
March | 0.142373E+09 | 28600.34 | 25-MAR-07:01 | 2.15 |
April | 0.103015E+09 | 16988.92 | 19-APR-07:01 | 4.18 |
May | 73959615.80 | 1113.46 | 12-MAY-07:25 | 10.00 |
June | 17602372.73 | 1113.80 | 15-JUN-07:25 | 11.15 |
July | 10652194.93 | 1556.66 | 24-JUL-07:07 | 19.37 |
August | 14149943.84 | 1561.87 | 10-AUG-07:07 | 19.83 |
September | 25350056.42 | 1243.40 | 14-SEP-07:10 | 14.18 |
October | 87107883.71 | 1117.84 | 11-OCT-07:25 | 8.05 |
November | 0.220906E+09 | 28601.92 | 24-NOV-08:61 | 1.97 |
December | 0.569011E+09 | 28604.39 | 22-DEC-08:61 | 0.10 |
Annual Sum or Average | 0.243908E+10 | |||
Minimum of Months | 10652194.93 | 1113.46 | -3.8 | |
Maximum of Months | 0.746622E+09 | 28607.56 | 19.83 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.117690E+10 | 29250.95 | 15-JAN-08:61 | -3.7 |
February | 0.645867E+09 | 29327.83 | 19-FEB-08:61 | -4.7 |
March | 0.197254E+09 | 27172.69 | 06-MAR-07:02 | 6.70 |
April | 0.109811E+09 | 11388.98 | 19-APR-06:03 | 2.48 |
May | 69381163.29 | 1046.60 | 28-MAY-08:00 | 8.30 |
June | 19307326.24 | 1040.89 | 11-JUN-07:10 | 12.98 |
July | 26745925.54 | 1624.42 | 23-JUL-16:12 | 27.43 |
August | 40985364.29 | 1953.44 | 10-AUG-19:03 | 29.18 |
September | 23342504.01 | 1271.35 | 14-SEP-06:10 | 12.07 |
October | 84562192.56 | 1078.30 | 22-OCT-08:00 | 7.80 |
November | 0.400089E+09 | 28706.88 | 24-NOV-07:02 | 1.20 |
December | 0.900797E+09 | 29089.98 | 26-DEC-07:01 | -1.6 |
Annual Sum or Average | 0.369504E+10 | |||
Minimum of Months | 19307326.24 | 1040.89 | -4.7 | |
Maximum of Months | 0.117690E+10 | 29327.83 | 29.18 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.135906E+10 | 29325.76 | 15-JAN-08:61 | -3.7 |
February | 0.742585E+09 | 29403.25 | 19-FEB-08:61 | -4.7 |
March | 0.237911E+09 | 28749.67 | 06-MAR-07:02 | 6.70 |
April | 0.120630E+09 | 14181.41 | 19-APR-06:03 | 2.48 |
May | 75278120.87 | 1050.84 | 28-MAY-08:00 | 8.30 |
June | 24177268.64 | 967.97 | 11-JUN-07:10 | 12.98 |
July | 27278816.85 | 1629.15 | 23-JUL-16:12 | 27.43 |
August | 41546535.02 | 1955.98 | 10-AUG-19:03 | 29.18 |
September | 27839313.04 | 1272.69 | 14-SEP-06:10 | 12.07 |
October | 92125842.84 | 2242.33 | 30-OCT-06:05 | 7.20 |
November | 0.488611E+09 | 28778.98 | 24-NOV-07:02 | 1.20 |
December | 0.104166E+10 | 29164.94 | 26-DEC-07:01 | -1.6 |
Annual Sum or Average | 0.427871E+10 | |||
Minimum of Months | 24177268.64 | 967.97 | -4.7 | |
Maximum of Months | 0.135906E+10 | 29403.25 | 29.18 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.164744E+10 | 29107.74 | 15-JAN-08:61 | -3.7 |
February | 0.916944E+09 | 29183.83 | 19-FEB-08:61 | -4.7 |
March | 0.320697E+09 | 28545.49 | 05-MAR-08:62 | 2.38 |
April | 0.144457E+09 | 17526.12 | 19-APR-06:03 | 2.48 |
May | 83077296.97 | 1043.30 | 28-MAY-08:00 | 8.30 |
June | 37295418.52 | 1018.37 | 14-JUN-07:00 | 10.60 |
July | 28372365.91 | 1626.57 | 23-JUL-16:12 | 27.43 |
August | 41508110.70 | 1960.54 | 10-AUG-19:03 | 29.18 |
September | 39726682.00 | 1168.48 | 14-SEP-06:10 | 12.07 |
October | 0.109128E+09 | 5379.81 | 29-OCT-07:03 | 6.70 |
November | 0.623505E+09 | 28570.63 | 24-NOV-07:02 | 1.20 |
December | 0.128006E+10 | 28950.09 | 26-DEC-07:01 | -1.6 |
Annual Sum or Average | 0.527221E+10 | |||
Minimum of Months | 28372365.91 | 1018.37 | -4.7 | |
Maximum of Months | 0.164744E+10 | 29183.83 | 29.18 |
Report: ZoneHeatingSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.354265E+10 | 52892.45 | 17-JAN-08:61 | 1.70 |
February | 0.197243E+10 | 52873.55 | 06-FEB-08:61 | 3.90 |
March | 0.784681E+09 | 52875.71 | 25-MAR-07:01 | 2.15 |
April | 0.292890E+09 | 52868.16 | 19-APR-07:01 | 4.18 |
May | 79478337.47 | 20987.33 | 29-MAY-08:61 | 10.60 |
June | 53206537.09 | 758.98 | 14-JUN-07:25 | 10.85 |
July | 37542388.09 | 2156.80 | 23-JUL-16:03 | 27.62 |
August | 39510996.86 | 2340.49 | 13-AUG-16:03 | 28.08 |
September | 52750348.38 | 893.27 | 14-SEP-07:10 | 14.18 |
October | 0.202124E+09 | 52466.62 | 30-OCT-07:01 | 7.20 |
November | 0.134621E+10 | 52884.88 | 24-NOV-08:61 | 1.97 |
December | 0.276701E+10 | 52888.14 | 26-DEC-08:61 | -1.1 |
Annual Sum or Average | 0.111705E+11 | |||
Minimum of Months | 37542388.09 | 758.98 | -1.1 | |
Maximum of Months | 0.354265E+10 | 52892.45 | 28.08 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.206740E+10 | 26848.02 | 17-JAN-08:61 | 1.70 |
February | 0.117786E+10 | 26838.43 | 06-FEB-08:61 | 3.90 |
March | 0.495542E+09 | 26840.22 | 25-MAR-07:01 | 2.15 |
April | 0.207317E+09 | 26835.74 | 19-APR-07:01 | 4.18 |
May | 96484129.48 | 11586.80 | 29-MAY-08:61 | 10.60 |
June | 57246154.66 | 1009.43 | 15-JUN-07:25 | 11.15 |
July | 30524037.40 | 1560.06 | 23-JUL-16:12 | 27.43 |
August | 31370003.32 | 1663.84 | 13-AUG-16:12 | 27.97 |
September | 58660522.51 | 986.86 | 27-SEP-07:13 | 8.90 |
October | 0.155224E+09 | 26626.56 | 30-OCT-07:01 | 7.20 |
November | 0.831054E+09 | 26844.50 | 24-NOV-08:61 | 1.97 |
December | 0.162633E+10 | 26846.46 | 26-DEC-08:61 | -1.1 |
Annual Sum or Average | 0.683501E+10 | |||
Minimum of Months | 30524037.40 | 986.86 | -1.1 | |
Maximum of Months | 0.206740E+10 | 26848.02 | 27.97 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.214901E+10 | 26700.99 | 17-JAN-08:61 | 1.70 |
February | 0.124124E+10 | 26692.15 | 08-FEB-08:61 | -0.4 |
March | 0.534037E+09 | 26694.22 | 25-MAR-07:01 | 2.15 |
April | 0.222215E+09 | 26689.54 | 19-APR-07:01 | 4.18 |
May | 99134675.27 | 14064.98 | 29-MAY-08:61 | 10.60 |
June | 61057623.14 | 1003.53 | 15-JUN-07:25 | 11.15 |
July | 33878275.32 | 1556.85 | 23-JUL-16:12 | 27.43 |
August | 32902963.16 | 1659.98 | 13-AUG-16:12 | 27.97 |
September | 60942875.16 | 980.81 | 27-SEP-07:13 | 8.90 |
October | 0.167027E+09 | 26482.79 | 30-OCT-07:01 | 7.20 |
November | 0.876383E+09 | 26698.29 | 24-NOV-08:61 | 1.97 |
December | 0.169575E+10 | 26700.22 | 26-DEC-08:61 | -1.1 |
Annual Sum or Average | 0.717358E+10 | |||
Minimum of Months | 32902963.16 | 980.81 | -1.1 | |
Maximum of Months | 0.214901E+10 | 26700.99 | 27.97 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.253080E+10 | 26467.17 | 17-JAN-08:61 | 1.70 |
February | 0.152324E+10 | 26457.39 | 06-FEB-08:61 | 3.90 |
March | 0.724443E+09 | 26458.20 | 25-MAR-07:01 | 2.15 |
April | 0.300957E+09 | 26454.64 | 19-APR-07:01 | 4.18 |
May | 0.112727E+09 | 23661.60 | 29-MAY-08:61 | 10.60 |
June | 76243881.80 | 996.54 | 15-JUN-07:25 | 11.15 |
July | 53177406.35 | 1555.03 | 23-JUL-16:12 | 27.43 |
August | 42700313.09 | 1657.53 | 13-AUG-16:12 | 27.97 |
September | 70518452.75 | 3147.80 | 28-SEP-07:03 | 9.08 |
October | 0.217931E+09 | 26251.57 | 30-OCT-07:01 | 7.20 |
November | 0.107887E+10 | 26462.70 | 24-NOV-08:61 | 1.97 |
December | 0.202406E+10 | 26464.79 | 26-DEC-08:61 | -1.1 |
Annual Sum or Average | 0.875566E+10 | |||
Minimum of Months | 42700313.09 | 996.54 | -1.1 | |
Maximum of Months | 0.253080E+10 | 26467.17 | 27.97 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.432172E+10 | 27831.69 | 17-JAN-08:12 | 1.70 |
February | 0.284252E+10 | 27814.49 | 20-FEB-09:12 | 1.83 |
March | 0.163566E+10 | 27599.35 | 07-MAR-08:61 | 7.15 |
April | 0.710956E+09 | 27595.97 | 19-APR-07:01 | 4.18 |
May | 0.236486E+09 | 27205.08 | 29-MAY-08:61 | 10.60 |
June | 99628519.80 | 9404.91 | 15-JUN-07:03 | 10.78 |
July | 89391649.31 | 1601.46 | 23-JUL-16:12 | 27.43 |
August | 67353577.50 | 1697.39 | 13-AUG-16:12 | 27.97 |
September | 0.103935E+09 | 18944.49 | 28-SEP-07:03 | 9.08 |
October | 0.512624E+09 | 27376.21 | 30-OCT-07:01 | 7.20 |
November | 0.201935E+10 | 27612.17 | 13-NOV-08:61 | 0.78 |
December | 0.354990E+10 | 27682.01 | 26-DEC-08:13 | -1.1 |
Annual Sum or Average | 0.161895E+11 | |||
Minimum of Months | 67353577.50 | 1601.46 | -1.1 | |
Maximum of Months | 0.432172E+10 | 27831.69 | 27.97 |
Report: ZoneElectricSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.739462E+10 | 4621.63 | 01-JAN-10:09 | 0.222596E+10 | 1343.25 | 01-JAN-10:09 |
February | 0.668410E+10 | 4621.63 | 01-FEB-10:09 | 0.201408E+10 | 1343.25 | 01-FEB-10:09 |
March | 0.740180E+10 | 4621.63 | 01-MAR-10:09 | 0.223295E+10 | 1343.25 | 01-MAR-10:09 |
April | 0.716384E+10 | 4621.63 | 01-APR-09:09 | 0.215748E+10 | 1343.25 | 01-APR-09:09 |
May | 0.739462E+10 | 4621.63 | 01-MAY-09:09 | 0.222596E+10 | 1343.25 | 01-MAY-09:09 |
June | 0.716485E+10 | 4621.63 | 01-JUN-09:09 | 0.216232E+10 | 1343.25 | 01-JUN-09:09 |
July | 0.740069E+10 | 4621.63 | 01-JUL-09:09 | 0.222811E+10 | 1343.25 | 01-JUL-09:09 |
August | 0.739513E+10 | 4621.63 | 01-AUG-09:09 | 0.222838E+10 | 1343.25 | 01-AUG-09:09 |
September | 0.717041E+10 | 4621.63 | 01-SEP-09:09 | 0.216205E+10 | 1343.25 | 01-SEP-09:09 |
October | 0.739462E+10 | 4621.63 | 01-OCT-09:09 | 0.222596E+10 | 1343.25 | 01-OCT-09:09 |
November | 0.714323E+10 | 4621.63 | 01-NOV-09:09 | 0.215077E+10 | 1343.25 | 01-NOV-09:09 |
December | 0.740776E+10 | 4621.63 | 01-DEC-10:09 | 0.223509E+10 | 1343.25 | 01-DEC-10:09 |
Annual Sum or Average | 0.871157E+11 | 0.262491E+11 | ||||
Minimum of Months | 0.668410E+10 | 4621.63 | 0.201408E+10 | 1343.25 | ||
Maximum of Months | 0.740776E+10 | 4621.63 | 0.223509E+10 | 1343.25 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.451584E+10 | 2827.07 | 01-JAN-10:09 | 0.111298E+10 | 671.63 | 01-JAN-10:09 |
February | 0.408193E+10 | 2827.07 | 01-FEB-10:09 | 0.100704E+10 | 671.63 | 01-FEB-10:09 |
March | 0.452026E+10 | 2827.07 | 01-MAR-10:09 | 0.111647E+10 | 671.63 | 01-MAR-10:09 |
April | 0.437489E+10 | 2827.07 | 01-APR-09:09 | 0.107874E+10 | 671.63 | 01-APR-09:09 |
May | 0.451584E+10 | 2827.07 | 01-MAY-09:09 | 0.111298E+10 | 671.63 | 01-MAY-09:09 |
June | 0.437556E+10 | 2827.07 | 01-JUN-09:09 | 0.108116E+10 | 671.63 | 01-JUN-09:09 |
July | 0.451952E+10 | 2827.07 | 01-JUL-09:09 | 0.111405E+10 | 671.63 | 01-JUL-09:09 |
August | 0.451617E+10 | 2827.07 | 01-AUG-09:09 | 0.111419E+10 | 671.63 | 01-AUG-09:09 |
September | 0.437891E+10 | 2827.07 | 01-SEP-09:09 | 0.108102E+10 | 671.63 | 01-SEP-09:09 |
October | 0.451584E+10 | 2827.07 | 01-OCT-09:09 | 0.111298E+10 | 671.63 | 01-OCT-09:09 |
November | 0.436230E+10 | 2827.07 | 01-NOV-09:09 | 0.107538E+10 | 671.63 | 01-NOV-09:09 |
December | 0.452388E+10 | 2827.07 | 01-DEC-10:09 | 0.111755E+10 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.532009E+11 | 0.131245E+11 | ||||
Minimum of Months | 0.408193E+10 | 2827.07 | 0.100704E+10 | 671.63 | ||
Maximum of Months | 0.452388E+10 | 2827.07 | 0.111755E+10 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.317044E+10 | 2555.22 | 01-JAN-10:09 | 0.879849E+09 | 671.63 | 01-JAN-10:09 |
February | 0.287181E+10 | 2555.22 | 01-FEB-09:09 | 0.796766E+09 | 671.63 | 01-FEB-09:09 |
March | 0.324295E+10 | 2555.22 | 01-MAR-09:09 | 0.898128E+09 | 671.63 | 01-MAR-09:09 |
April | 0.307694E+10 | 2555.22 | 01-APR-08:09 | 0.853677E+09 | 671.63 | 01-APR-08:09 |
May | 0.320669E+10 | 2555.22 | 01-MAY-08:09 | 0.888989E+09 | 671.63 | 01-MAY-08:09 |
June | 0.313132E+10 | 2555.22 | 01-JUN-08:09 | 0.867387E+09 | 671.63 | 01-JUN-08:09 |
July | 0.315231E+10 | 2555.22 | 01-JUL-08:09 | 0.875279E+09 | 671.63 | 01-JUL-08:09 |
August | 0.324295E+10 | 2555.22 | 01-AUG-08:09 | 0.898128E+09 | 671.63 | 01-AUG-08:09 |
September | 0.307694E+10 | 2555.22 | 01-SEP-08:09 | 0.853677E+09 | 671.63 | 01-SEP-08:09 |
October | 0.317044E+10 | 2555.22 | 01-OCT-09:09 | 0.879849E+09 | 671.63 | 01-OCT-09:09 |
November | 0.307694E+10 | 2555.22 | 01-NOV-08:09 | 0.853679E+09 | 671.63 | 01-NOV-08:09 |
December | 0.315231E+10 | 2555.22 | 01-DEC-09:09 | 0.875279E+09 | 671.63 | 01-DEC-09:09 |
Annual Sum or Average | 0.375720E+11 | 0.104207E+11 | ||||
Minimum of Months | 0.287181E+10 | 2555.22 | 0.796766E+09 | 671.63 | ||
Maximum of Months | 0.324295E+10 | 2555.22 | 0.898128E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.317044E+10 | 2555.22 | 01-JAN-10:09 | 0.879849E+09 | 671.63 | 01-JAN-10:09 |
February | 0.287181E+10 | 2555.22 | 01-FEB-09:09 | 0.796766E+09 | 671.63 | 01-FEB-09:09 |
March | 0.324295E+10 | 2555.22 | 01-MAR-09:09 | 0.898128E+09 | 671.63 | 01-MAR-09:09 |
April | 0.307694E+10 | 2555.22 | 01-APR-08:09 | 0.853677E+09 | 671.63 | 01-APR-08:09 |
May | 0.320669E+10 | 2555.22 | 01-MAY-08:09 | 0.888989E+09 | 671.63 | 01-MAY-08:09 |
June | 0.313132E+10 | 2555.22 | 01-JUN-08:09 | 0.867387E+09 | 671.63 | 01-JUN-08:09 |
July | 0.315231E+10 | 2555.22 | 01-JUL-08:09 | 0.875279E+09 | 671.63 | 01-JUL-08:09 |
August | 0.324295E+10 | 2555.22 | 01-AUG-08:09 | 0.898128E+09 | 671.63 | 01-AUG-08:09 |
September | 0.307694E+10 | 2555.22 | 01-SEP-08:09 | 0.853677E+09 | 671.63 | 01-SEP-08:09 |
October | 0.317044E+10 | 2555.22 | 01-OCT-09:09 | 0.879849E+09 | 671.63 | 01-OCT-09:09 |
November | 0.307694E+10 | 2555.22 | 01-NOV-08:09 | 0.853679E+09 | 671.63 | 01-NOV-08:09 |
December | 0.315231E+10 | 2555.22 | 01-DEC-09:09 | 0.875279E+09 | 671.63 | 01-DEC-09:09 |
Annual Sum or Average | 0.375720E+11 | 0.104207E+11 | ||||
Minimum of Months | 0.287181E+10 | 2555.22 | 0.796766E+09 | 671.63 | ||
Maximum of Months | 0.324295E+10 | 2555.22 | 0.898128E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.317044E+10 | 2555.22 | 01-JAN-10:09 | 0.879849E+09 | 671.63 | 01-JAN-10:09 |
February | 0.287181E+10 | 2555.22 | 01-FEB-09:09 | 0.796766E+09 | 671.63 | 01-FEB-09:09 |
March | 0.324295E+10 | 2555.22 | 01-MAR-09:09 | 0.898128E+09 | 671.63 | 01-MAR-09:09 |
April | 0.307694E+10 | 2555.22 | 01-APR-08:09 | 0.853677E+09 | 671.63 | 01-APR-08:09 |
May | 0.320669E+10 | 2555.22 | 01-MAY-08:09 | 0.888989E+09 | 671.63 | 01-MAY-08:09 |
June | 0.313132E+10 | 2555.22 | 01-JUN-08:09 | 0.867387E+09 | 671.63 | 01-JUN-08:09 |
July | 0.315231E+10 | 2555.22 | 01-JUL-08:09 | 0.875279E+09 | 671.63 | 01-JUL-08:09 |
August | 0.324295E+10 | 2555.22 | 01-AUG-08:09 | 0.898128E+09 | 671.63 | 01-AUG-08:09 |
September | 0.307694E+10 | 2555.22 | 01-SEP-08:09 | 0.853677E+09 | 671.63 | 01-SEP-08:09 |
October | 0.317044E+10 | 2555.22 | 01-OCT-09:09 | 0.879849E+09 | 671.63 | 01-OCT-09:09 |
November | 0.307694E+10 | 2555.22 | 01-NOV-08:09 | 0.853679E+09 | 671.63 | 01-NOV-08:09 |
December | 0.315231E+10 | 2555.22 | 01-DEC-09:09 | 0.875279E+09 | 671.63 | 01-DEC-09:09 |
Annual Sum or Average | 0.375720E+11 | 0.104207E+11 | ||||
Minimum of Months | 0.287181E+10 | 2555.22 | 0.796766E+09 | 671.63 | ||
Maximum of Months | 0.324295E+10 | 2555.22 | 0.898128E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.313454E+10 | 2726.96 | 01-JAN-11:09 | 0.161799E+10 | 1343.25 | 01-JAN-11:09 |
February | 0.283982E+10 | 2726.96 | 01-FEB-10:09 | 0.146554E+10 | 1343.25 | 01-FEB-10:09 |
March | 0.321092E+10 | 2726.96 | 01-MAR-10:09 | 0.165455E+10 | 1343.25 | 01-MAR-10:09 |
April | 0.304266E+10 | 2726.96 | 01-APR-09:09 | 0.157022E+10 | 1343.25 | 01-APR-09:09 |
May | 0.317273E+10 | 2726.96 | 01-MAY-09:09 | 0.163627E+10 | 1343.25 | 01-MAY-09:09 |
June | 0.309995E+10 | 2726.96 | 01-JUN-09:09 | 0.159764E+10 | 1343.25 | 01-JUN-09:09 |
July | 0.311545E+10 | 2726.96 | 01-JUL-09:09 | 0.160885E+10 | 1343.25 | 01-JUL-09:09 |
August | 0.321092E+10 | 2726.96 | 01-AUG-09:09 | 0.165455E+10 | 1343.25 | 01-AUG-09:09 |
September | 0.304266E+10 | 2726.96 | 01-SEP-09:09 | 0.157022E+10 | 1343.25 | 01-SEP-09:09 |
October | 0.313454E+10 | 2726.96 | 01-OCT-10:09 | 0.161799E+10 | 1343.25 | 01-OCT-10:09 |
November | 0.304266E+10 | 2726.96 | 01-NOV-09:09 | 0.157022E+10 | 1343.25 | 01-NOV-09:09 |
December | 0.311545E+10 | 2726.96 | 01-DEC-10:09 | 0.160885E+10 | 1343.25 | 01-DEC-10:09 |
Annual Sum or Average | 0.371623E+11 | 0.191729E+11 | ||||
Minimum of Months | 0.283982E+10 | 2726.96 | 0.146554E+10 | 1343.25 | ||
Maximum of Months | 0.321092E+10 | 2726.96 | 0.165455E+10 | 1343.25 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.161274E+10 | 1404.46 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.146111E+10 | 1404.46 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.165211E+10 | 1404.46 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.156548E+10 | 1404.46 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.163243E+10 | 1404.46 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.159501E+10 | 1404.46 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.160290E+10 | 1404.46 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.165211E+10 | 1404.46 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.156548E+10 | 1404.46 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.161274E+10 | 1404.46 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.156548E+10 | 1404.46 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.160290E+10 | 1404.46 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.191205E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.146111E+10 | 1404.46 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.165211E+10 | 1404.46 | 0.827277E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.161274E+10 | 1404.46 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.146111E+10 | 1404.46 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.165211E+10 | 1404.46 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.156548E+10 | 1404.46 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.163243E+10 | 1404.46 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.159501E+10 | 1404.46 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.160290E+10 | 1404.46 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.165211E+10 | 1404.46 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.156548E+10 | 1404.46 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.161274E+10 | 1404.46 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.156548E+10 | 1404.46 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.160290E+10 | 1404.46 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.191205E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.146111E+10 | 1404.46 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.165211E+10 | 1404.46 | 0.827277E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.161274E+10 | 1404.46 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.146111E+10 | 1404.46 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.165211E+10 | 1404.46 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.156548E+10 | 1404.46 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.163243E+10 | 1404.46 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.159501E+10 | 1404.46 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.160290E+10 | 1404.46 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.165211E+10 | 1404.46 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.156548E+10 | 1404.46 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.161274E+10 | 1404.46 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.156548E+10 | 1404.46 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.160290E+10 | 1404.46 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.191205E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.146111E+10 | 1404.46 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.165211E+10 | 1404.46 | 0.827277E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.161274E+10 | 1404.46 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.146111E+10 | 1404.46 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.165211E+10 | 1404.46 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.156548E+10 | 1404.46 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.163243E+10 | 1404.46 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.159501E+10 | 1404.46 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.160290E+10 | 1404.46 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.165211E+10 | 1404.46 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.156548E+10 | 1404.46 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.161274E+10 | 1404.46 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.156548E+10 | 1404.46 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.160290E+10 | 1404.46 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.191205E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.146111E+10 | 1404.46 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.165211E+10 | 1404.46 | 0.827277E+09 | 671.63 |
Report: SpaceGainsMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.338624E+10 | 0.739462E+10 | 0.222596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.449069E+10 |
February | 0.305697E+10 | 0.668410E+10 | 0.201408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.357775E+10 |
March | 0.335708E+10 | 0.740180E+10 | 0.223295E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.320878E+10 |
April | 0.327081E+10 | 0.716384E+10 | 0.215748E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24394611.69 | 0.249709E+10 |
May | 0.336680E+10 | 0.739462E+10 | 0.222596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2651636.23 | 0.212432E+10 |
June | 0.325380E+10 | 0.716485E+10 | 0.216232E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13745761.41 | 0.162315E+10 |
July | 0.339353E+10 | 0.740069E+10 | 0.222811E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130178E+09 | 0.113020E+10 |
August | 0.334857E+10 | 0.739513E+10 | 0.222838E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.278912E+09 | 0.934477E+09 |
September | 0.327932E+10 | 0.717041E+10 | 0.216205E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3240716.28 | 0.152216E+10 |
October | 0.338624E+10 | 0.739462E+10 | 0.222596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.256531E+10 |
November | 0.327446E+10 | 0.714323E+10 | 0.215077E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.348621E+10 |
December | 0.340325E+10 | 0.740776E+10 | 0.223509E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.410164E+10 |
Annual Sum or Average | 0.397770E+11 | 0.871157E+11 | 0.262491E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.453123E+09 | 0.312618E+11 |
Minimum of Months | 0.305697E+10 | 0.668410E+10 | 0.201408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.934477E+09 |
Maximum of Months | 0.340325E+10 | 0.740776E+10 | 0.223509E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.278912E+09 | 0.449069E+10 |
Report: SpaceGainsMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.169307E+10 | 0.451584E+10 | 0.111298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.226150E+10 |
February | 0.152844E+10 | 0.408193E+10 | 0.100704E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180759E+10 |
March | 0.167849E+10 | 0.452026E+10 | 0.111647E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165088E+10 |
April | 0.163536E+10 | 0.437489E+10 | 0.107874E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13270501.49 | 0.130308E+10 |
May | 0.168335E+10 | 0.451584E+10 | 0.111298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1458570.18 | 0.111895E+10 |
June | 0.162685E+10 | 0.437556E+10 | 0.108116E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7466555.64 | 0.789080E+09 |
July | 0.169671E+10 | 0.451952E+10 | 0.111405E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 70590002.67 | 0.520094E+09 |
August | 0.167424E+10 | 0.451617E+10 | 0.111419E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151705E+09 | 0.418711E+09 |
September | 0.163961E+10 | 0.437891E+10 | 0.108102E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1785789.31 | 0.811625E+09 |
October | 0.169307E+10 | 0.451584E+10 | 0.111298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135871E+10 |
November | 0.163718E+10 | 0.436230E+10 | 0.107538E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178065E+10 |
December | 0.170157E+10 | 0.452388E+10 | 0.111755E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.209349E+10 |
Annual Sum or Average | 0.198880E+11 | 0.532009E+11 | 0.131245E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.246276E+09 | 0.159143E+11 |
Minimum of Months | 0.152844E+10 | 0.408193E+10 | 0.100704E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.418711E+09 |
Maximum of Months | 0.170157E+10 | 0.452388E+10 | 0.111755E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151705E+09 | 0.226150E+10 |
Report: SpaceGainsMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.317044E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.231817E+10 |
February | 0.914877E+09 | 0.287181E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.184947E+10 |
March | 0.103395E+10 | 0.324295E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.167410E+10 |
April | 0.984131E+09 | 0.307694E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13095573.66 | 0.132956E+10 |
May | 0.102058E+10 | 0.320669E+10 | 0.888989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1456085.42 | 0.115565E+10 |
June | 0.998711E+09 | 0.313132E+10 | 0.867387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7466423.94 | 0.824539E+09 |
July | 0.100600E+10 | 0.315231E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 67090700.48 | 0.557189E+09 |
August | 0.103395E+10 | 0.324295E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149651E+09 | 0.450172E+09 |
September | 0.984131E+09 | 0.307694E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1785748.49 | 0.835206E+09 |
October | 0.100722E+10 | 0.317044E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137576E+10 |
November | 0.973196E+09 | 0.307694E+10 | 0.853679E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180496E+10 |
December | 0.100600E+10 | 0.315231E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.214111E+10 |
Annual Sum or Average | 0.119700E+11 | 0.375720E+11 | 0.104207E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.240546E+09 | 0.163159E+11 |
Minimum of Months | 0.914877E+09 | 0.287181E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.450172E+09 |
Maximum of Months | 0.103395E+10 | 0.324295E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149651E+09 | 0.231817E+10 |
Report: SpaceGainsMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.317044E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.231285E+10 |
February | 0.914877E+09 | 0.287181E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.184235E+10 |
March | 0.103395E+10 | 0.324295E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166053E+10 |
April | 0.984131E+09 | 0.307694E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13099844.78 | 0.131280E+10 |
May | 0.102058E+10 | 0.320669E+10 | 0.888989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1456075.36 | 0.114665E+10 |
June | 0.998711E+09 | 0.313132E+10 | 0.867387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7466423.75 | 0.822568E+09 |
July | 0.100600E+10 | 0.315231E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 67091442.88 | 0.556676E+09 |
August | 0.103395E+10 | 0.324295E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149650E+09 | 0.449987E+09 |
September | 0.984131E+09 | 0.307694E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1785733.99 | 0.832444E+09 |
October | 0.100722E+10 | 0.317044E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135817E+10 |
November | 0.973196E+09 | 0.307694E+10 | 0.853679E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179497E+10 |
December | 0.100600E+10 | 0.315231E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.213647E+10 |
Annual Sum or Average | 0.119700E+11 | 0.375720E+11 | 0.104207E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.240549E+09 | 0.162265E+11 |
Minimum of Months | 0.914877E+09 | 0.287181E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.449987E+09 |
Maximum of Months | 0.103395E+10 | 0.324295E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149650E+09 | 0.231285E+10 |
Report: SpaceGainsMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.317044E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230815E+10 |
February | 0.914877E+09 | 0.287181E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183459E+10 |
March | 0.103395E+10 | 0.324295E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.164273E+10 |
April | 0.984131E+09 | 0.307694E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13112416.65 | 0.128649E+10 |
May | 0.102058E+10 | 0.320669E+10 | 0.888989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1456053.84 | 0.112262E+10 |
June | 0.998711E+09 | 0.313132E+10 | 0.867387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7466422.28 | 0.815483E+09 |
July | 0.100600E+10 | 0.315231E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 67129288.07 | 0.553752E+09 |
August | 0.103395E+10 | 0.324295E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149673E+09 | 0.447439E+09 |
September | 0.984131E+09 | 0.307694E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1785703.25 | 0.822834E+09 |
October | 0.100722E+10 | 0.317044E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133076E+10 |
November | 0.973196E+09 | 0.307694E+10 | 0.853679E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178278E+10 |
December | 0.100600E+10 | 0.315231E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.213198E+10 |
Annual Sum or Average | 0.119700E+11 | 0.375720E+11 | 0.104207E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.240623E+09 | 0.160796E+11 |
Minimum of Months | 0.914877E+09 | 0.287181E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.447439E+09 |
Maximum of Months | 0.103395E+10 | 0.324295E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149673E+09 | 0.230815E+10 |
Report: SpaceGainsMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.344359E+10 | 0.313454E+10 | 0.161799E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.421681E+10 |
February | 0.313522E+10 | 0.283982E+10 | 0.146554E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.334124E+10 |
March | 0.355148E+10 | 0.321092E+10 | 0.165455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.296349E+10 |
April | 0.338259E+10 | 0.304266E+10 | 0.157022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23751317.41 | 0.226833E+10 |
May | 0.349753E+10 | 0.317273E+10 | 0.163627E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2614426.25 | 0.193257E+10 |
June | 0.343071E+10 | 0.309995E+10 | 0.159764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13429723.35 | 0.146561E+10 |
July | 0.344942E+10 | 0.311545E+10 | 0.160885E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121440E+09 | 0.101973E+10 |
August | 0.355148E+10 | 0.321092E+10 | 0.165455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.269727E+09 | 0.830502E+09 |
September | 0.338259E+10 | 0.304266E+10 | 0.157022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3205321.62 | 0.143048E+10 |
October | 0.344359E+10 | 0.313454E+10 | 0.161799E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.234316E+10 |
November | 0.331698E+10 | 0.304266E+10 | 0.157022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.323369E+10 |
December | 0.344942E+10 | 0.311545E+10 | 0.160885E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.388534E+10 |
Annual Sum or Average | 0.410346E+11 | 0.371623E+11 | 0.191729E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.434168E+09 | 0.289310E+11 |
Minimum of Months | 0.313522E+10 | 0.283982E+10 | 0.146554E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.830502E+09 |
Maximum of Months | 0.355148E+10 | 0.321092E+10 | 0.165455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.269727E+09 | 0.421681E+10 |
Report: SpaceGainsMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.161274E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.231232E+10 |
February | 0.156756E+10 | 0.146111E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183329E+10 |
March | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162913E+10 |
April | 0.169125E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13175436.11 | 0.125611E+10 |
May | 0.174872E+10 | 0.163243E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1455962.78 | 0.108513E+10 |
June | 0.171530E+10 | 0.159501E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7466498.42 | 0.809611E+09 |
July | 0.172466E+10 | 0.160290E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 67321549.89 | 0.553671E+09 |
August | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149861E+09 | 0.448411E+09 |
September | 0.169125E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1785638.72 | 0.806254E+09 |
October | 0.172174E+10 | 0.161274E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130306E+10 |
November | 0.165844E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.177611E+10 |
December | 0.172466E+10 | 0.160290E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.213405E+10 |
Annual Sum or Average | 0.205167E+11 | 0.191205E+11 | 0.958644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.241066E+09 | 0.159471E+11 |
Minimum of Months | 0.156756E+10 | 0.146111E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.448411E+09 |
Maximum of Months | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149861E+09 | 0.231232E+10 |
Report: SpaceGainsMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.161274E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.231113E+10 |
February | 0.156756E+10 | 0.146111E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183169E+10 |
March | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162602E+10 |
April | 0.169125E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13181974.44 | 0.125152E+10 |
May | 0.174872E+10 | 0.163243E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1455963.12 | 0.107924E+10 |
June | 0.171530E+10 | 0.159501E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7466504.14 | 0.807249E+09 |
July | 0.172466E+10 | 0.160290E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 67340278.65 | 0.552566E+09 |
August | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149874E+09 | 0.447627E+09 |
September | 0.169125E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1785637.99 | 0.803919E+09 |
October | 0.172174E+10 | 0.161274E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129891E+10 |
November | 0.165844E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.177425E+10 |
December | 0.172466E+10 | 0.160290E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.213299E+10 |
Annual Sum or Average | 0.205167E+11 | 0.191205E+11 | 0.958644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.241104E+09 | 0.159171E+11 |
Minimum of Months | 0.156756E+10 | 0.146111E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.447627E+09 |
Maximum of Months | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149874E+09 | 0.231113E+10 |
Report: SpaceGainsMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.161274E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230530E+10 |
February | 0.156756E+10 | 0.146111E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182474E+10 |
March | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161507E+10 |
April | 0.169125E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13205845.67 | 0.123428E+10 |
May | 0.174872E+10 | 0.163243E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1455936.58 | 0.105390E+10 |
June | 0.171530E+10 | 0.159501E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7466501.77 | 0.795192E+09 |
July | 0.172466E+10 | 0.160290E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 67391621.97 | 0.547911E+09 |
August | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149901E+09 | 0.444357E+09 |
September | 0.169125E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1785607.26 | 0.791170E+09 |
October | 0.172174E+10 | 0.161274E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128140E+10 |
November | 0.165844E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.176718E+10 |
December | 0.172466E+10 | 0.160290E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.212816E+10 |
Annual Sum or Average | 0.205167E+11 | 0.191205E+11 | 0.958644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.241206E+09 | 0.157887E+11 |
Minimum of Months | 0.156756E+10 | 0.146111E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.444357E+09 |
Maximum of Months | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149901E+09 | 0.230530E+10 |
Report: SpaceGainsMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.161274E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.275643E+10 |
February | 0.156756E+10 | 0.146111E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.220558E+10 |
March | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.198336E+10 |
April | 0.169125E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13840373.04 | 0.156306E+10 |
May | 0.174872E+10 | 0.163243E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1492826.55 | 0.131152E+10 |
June | 0.171530E+10 | 0.159501E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7782012.59 | 0.103342E+10 |
July | 0.172466E+10 | 0.160290E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 70276310.50 | 0.751082E+09 |
August | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155863E+09 | 0.631370E+09 |
September | 0.169125E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1820492.15 | 0.911540E+09 |
October | 0.172174E+10 | 0.161274E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157596E+10 |
November | 0.165844E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.211670E+10 |
December | 0.172466E+10 | 0.160290E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.250550E+10 |
Annual Sum or Average | 0.205167E+11 | 0.191205E+11 | 0.958644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.251075E+09 | 0.193455E+11 |
Minimum of Months | 0.156756E+10 | 0.146111E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.631370E+09 |
Maximum of Months | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155863E+09 | 0.275643E+10 |
Report: PeakSpaceGainsMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 4050.04 | 01-JAN-13:09 | 4621.63 | 01-JAN-10:09 | 1343.25 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 6851.57 | 07-JAN-12:10 |
February | 4050.04 | 03-FEB-13:09 | 4621.63 | 01-FEB-10:09 | 1343.25 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 7078.81 | 18-FEB-18:00 |
March | 4050.04 | 03-MAR-13:09 | 4621.63 | 01-MAR-10:09 | 1343.25 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 5122.21 | 22-MAR-11:10 |
April | 4050.04 | 01-APR-12:09 | 4621.63 | 01-APR-09:09 | 1343.25 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 996.74 | 01-APR-16:00 | 4438.64 | 18-APR-17:00 |
May | 4050.04 | 05-MAY-12:09 | 4621.63 | 01-MAY-09:09 | 1343.25 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 321.47 | 05-MAY-16:00 | 4018.37 | 23-MAY-17:00 |
June | 4050.04 | 02-JUN-12:09 | 4621.63 | 01-JUN-09:09 | 1343.25 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 818.14 | 28-JUN-17:00 | 3534.35 | 13-JUN-14:00 |
July | 4050.04 | 01-JUL-12:09 | 4621.63 | 01-JUL-09:09 | 1343.25 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1924.02 | 24-JUL-15:00 | 3042.12 | 09-JUL-13:00 |
August | 4050.04 | 04-AUG-12:09 | 4621.63 | 01-AUG-09:09 | 1343.25 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2236.67 | 10-AUG-17:00 | 3021.30 | 01-AUG-11:10 |
September | 4050.04 | 01-SEP-12:09 | 4621.63 | 01-SEP-09:09 | 1343.25 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 323.76 | 14-SEP-17:00 | 3306.64 | 16-SEP-11:10 |
October | 4050.04 | 01-OCT-12:09 | 4621.63 | 01-OCT-09:09 | 1343.25 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 3842.84 | 31-OCT-17:00 |
November | 4050.04 | 03-NOV-12:09 | 4621.63 | 01-NOV-09:09 | 1343.25 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 5652.45 | 12-NOV-17:00 |
December | 4050.04 | 01-DEC-13:09 | 4621.63 | 01-DEC-10:09 | 1343.25 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 6746.90 | 26-DEC-13:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 4050.04 | 4621.63 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3021.30 | |||||
Maximum of Months | 4050.04 | 4621.63 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 2236.67 | 7078.81 |
Report: PeakSpaceGainsMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 01-JAN-13:09 | 2827.07 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 3788.98 | 07-JAN-12:10 |
February | 2024.96 | 03-FEB-13:09 | 2827.07 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3839.40 | 18-FEB-18:00 |
March | 2024.96 | 03-MAR-13:09 | 2827.07 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2779.27 | 22-MAR-11:10 |
April | 2024.96 | 01-APR-12:09 | 2827.07 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 536.87 | 01-APR-16:00 | 2413.10 | 18-APR-17:00 |
May | 2024.96 | 05-MAY-12:09 | 2827.07 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 177.00 | 05-MAY-16:00 | 2418.96 | 23-MAY-17:00 |
June | 2024.96 | 02-JUN-12:09 | 2827.07 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 449.30 | 28-JUN-17:00 | 2084.43 | 13-JUN-14:00 |
July | 2024.96 | 01-JUL-12:09 | 2827.07 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1056.67 | 24-JUL-15:00 | 1677.41 | 09-JUL-13:00 |
August | 2024.96 | 04-AUG-12:09 | 2827.07 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1231.30 | 10-AUG-17:00 | 1734.56 | 01-AUG-11:10 |
September | 2024.96 | 01-SEP-12:09 | 2827.07 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 177.81 | 14-SEP-17:00 | 1992.49 | 16-SEP-11:10 |
October | 2024.96 | 01-OCT-12:09 | 2827.07 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2059.22 | 29-OCT-11:10 |
November | 2024.96 | 03-NOV-12:09 | 2827.07 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3111.71 | 12-NOV-17:00 |
December | 2024.96 | 01-DEC-13:09 | 2827.07 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 3697.75 | 26-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 2827.07 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1677.41 | |||||
Maximum of Months | 2024.96 | 2827.07 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1231.30 | 3839.40 |
Report: PeakSpaceGainsMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 2555.22 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 3788.98 | 07-JAN-12:10 |
February | 2024.96 | 04-FEB-13:09 | 2555.22 | 01-FEB-09:09 | 671.63 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3839.40 | 18-FEB-18:00 |
March | 2024.96 | 04-MAR-13:09 | 2555.22 | 01-MAR-09:09 | 671.63 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2779.27 | 22-MAR-11:10 |
April | 2024.96 | 01-APR-12:09 | 2555.22 | 01-APR-08:09 | 671.63 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 536.87 | 01-APR-16:00 | 2413.10 | 18-APR-17:00 |
May | 2024.96 | 06-MAY-12:09 | 2555.22 | 01-MAY-08:09 | 671.63 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 177.00 | 05-MAY-16:00 | 2409.75 | 23-MAY-17:00 |
June | 2024.96 | 03-JUN-12:09 | 2555.22 | 01-JUN-08:09 | 671.63 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 449.30 | 28-JUN-17:00 | 2072.66 | 13-JUN-14:00 |
July | 2024.96 | 01-JUL-12:09 | 2555.22 | 01-JUL-08:09 | 671.63 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1056.67 | 24-JUL-15:00 | 1677.43 | 09-JUL-13:00 |
August | 2024.96 | 05-AUG-12:09 | 2555.22 | 01-AUG-08:09 | 671.63 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1231.30 | 10-AUG-17:00 | 1738.98 | 01-AUG-11:10 |
September | 2024.96 | 02-SEP-12:09 | 2555.22 | 01-SEP-08:09 | 671.63 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 177.80 | 14-SEP-17:00 | 2013.26 | 16-SEP-11:10 |
October | 2024.96 | 07-OCT-12:09 | 2555.22 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2041.32 | 31-OCT-17:00 |
November | 2024.96 | 04-NOV-12:09 | 2555.22 | 01-NOV-08:09 | 671.63 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3111.71 | 12-NOV-17:00 |
December | 2024.96 | 02-DEC-13:09 | 2555.22 | 01-DEC-09:09 | 671.63 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 3697.90 | 26-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 2555.22 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1677.43 | |||||
Maximum of Months | 2024.96 | 2555.22 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1231.30 | 3839.40 |
Report: PeakSpaceGainsMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 2555.22 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 3788.98 | 07-JAN-12:10 |
February | 2024.96 | 04-FEB-13:09 | 2555.22 | 01-FEB-09:09 | 671.63 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3839.40 | 18-FEB-18:00 |
March | 2024.96 | 04-MAR-13:09 | 2555.22 | 01-MAR-09:09 | 671.63 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2779.27 | 22-MAR-11:10 |
April | 2024.96 | 01-APR-12:09 | 2555.22 | 01-APR-08:09 | 671.63 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 536.87 | 01-APR-16:00 | 2413.10 | 18-APR-17:00 |
May | 2024.96 | 06-MAY-12:09 | 2555.22 | 01-MAY-08:09 | 671.63 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 177.00 | 05-MAY-16:00 | 2389.78 | 23-MAY-17:00 |
June | 2024.96 | 03-JUN-12:09 | 2555.22 | 01-JUN-08:09 | 671.63 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 449.30 | 28-JUN-17:00 | 2067.05 | 13-JUN-14:00 |
July | 2024.96 | 01-JUL-12:09 | 2555.22 | 01-JUL-08:09 | 671.63 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1056.67 | 24-JUL-15:00 | 1677.43 | 09-JUL-13:00 |
August | 2024.96 | 05-AUG-12:09 | 2555.22 | 01-AUG-08:09 | 671.63 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1231.30 | 10-AUG-17:00 | 1739.76 | 01-AUG-11:10 |
September | 2024.96 | 02-SEP-12:09 | 2555.22 | 01-SEP-08:09 | 671.63 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 177.80 | 14-SEP-17:00 | 2013.22 | 16-SEP-11:10 |
October | 2024.96 | 07-OCT-12:09 | 2555.22 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2041.32 | 31-OCT-17:00 |
November | 2024.96 | 04-NOV-12:09 | 2555.22 | 01-NOV-08:09 | 671.63 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3111.71 | 12-NOV-17:00 |
December | 2024.96 | 02-DEC-13:09 | 2555.22 | 01-DEC-09:09 | 671.63 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 3697.90 | 26-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 2555.22 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1677.43 | |||||
Maximum of Months | 2024.96 | 2555.22 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1231.30 | 3839.40 |
Report: PeakSpaceGainsMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 2555.22 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 3788.98 | 07-JAN-12:10 |
February | 2024.96 | 04-FEB-13:09 | 2555.22 | 01-FEB-09:09 | 671.63 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3839.40 | 18-FEB-18:00 |
March | 2024.96 | 04-MAR-13:09 | 2555.22 | 01-MAR-09:09 | 671.63 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2779.27 | 22-MAR-11:10 |
April | 2024.96 | 01-APR-12:09 | 2555.22 | 01-APR-08:09 | 671.63 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 536.87 | 01-APR-16:00 | 2413.10 | 18-APR-17:00 |
May | 2024.96 | 06-MAY-12:09 | 2555.22 | 01-MAY-08:09 | 671.63 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 177.00 | 05-MAY-16:00 | 2335.57 | 23-MAY-17:00 |
June | 2024.96 | 03-JUN-12:09 | 2555.22 | 01-JUN-08:09 | 671.63 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 449.30 | 28-JUN-17:00 | 2038.43 | 13-JUN-14:00 |
July | 2024.96 | 01-JUL-12:09 | 2555.22 | 01-JUL-08:09 | 671.63 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1056.67 | 24-JUL-15:00 | 1677.43 | 09-JUL-13:00 |
August | 2024.96 | 05-AUG-12:09 | 2555.22 | 01-AUG-08:09 | 671.63 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1231.30 | 10-AUG-17:00 | 1733.79 | 01-AUG-11:10 |
September | 2024.96 | 02-SEP-12:09 | 2555.22 | 01-SEP-08:09 | 671.63 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 177.80 | 14-SEP-17:00 | 1998.30 | 16-SEP-11:10 |
October | 2024.96 | 07-OCT-12:09 | 2555.22 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2041.32 | 31-OCT-17:00 |
November | 2024.96 | 04-NOV-12:09 | 2555.22 | 01-NOV-08:09 | 671.63 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3111.71 | 12-NOV-17:00 |
December | 2024.96 | 02-DEC-13:09 | 2555.22 | 01-DEC-09:09 | 671.63 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 3697.90 | 26-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 2555.22 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1677.43 | |||||
Maximum of Months | 2024.96 | 2555.22 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1231.30 | 3839.40 |
Report: PeakSpaceGainsMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 5400.05 | 07-JAN-15:09 | 2726.96 | 01-JAN-11:09 | 1343.25 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 6800.61 | 07-JAN-12:10 |
February | 5400.05 | 04-FEB-15:09 | 2726.96 | 01-FEB-10:09 | 1343.25 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 6907.61 | 18-FEB-18:00 |
March | 5400.05 | 04-MAR-15:09 | 2726.96 | 01-MAR-10:09 | 1343.25 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 5000.04 | 22-MAR-11:10 |
April | 5400.05 | 01-APR-14:09 | 2726.96 | 01-APR-09:09 | 1343.25 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 966.74 | 01-APR-16:00 | 4340.23 | 18-APR-17:00 |
May | 5400.05 | 06-MAY-14:09 | 2726.96 | 01-MAY-09:09 | 1343.25 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 317.80 | 05-MAY-16:00 | 3925.97 | 23-MAY-17:00 |
June | 5400.05 | 03-JUN-14:09 | 2726.96 | 01-JUN-09:09 | 1343.25 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 807.08 | 28-JUN-17:00 | 3412.18 | 13-JUN-14:00 |
July | 5400.05 | 01-JUL-14:09 | 2726.96 | 01-JUL-09:09 | 1343.25 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1897.93 | 24-JUL-15:00 | 2873.82 | 09-JUL-13:00 |
August | 5400.05 | 05-AUG-14:09 | 2726.96 | 01-AUG-09:09 | 1343.25 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2210.93 | 10-AUG-17:00 | 2999.04 | 01-AUG-11:10 |
September | 5400.05 | 02-SEP-14:09 | 2726.96 | 01-SEP-09:09 | 1343.25 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 319.37 | 14-SEP-17:00 | 3369.62 | 16-SEP-11:10 |
October | 5400.05 | 07-OCT-14:09 | 2726.96 | 01-OCT-10:09 | 1343.25 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 3682.21 | 31-OCT-17:00 |
November | 5400.05 | 04-NOV-14:09 | 2726.96 | 01-NOV-09:09 | 1343.25 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 5588.12 | 12-NOV-17:00 |
December | 5400.05 | 02-DEC-15:09 | 2726.96 | 01-DEC-10:09 | 1343.25 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 6644.20 | 26-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 5400.05 | 2726.96 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2873.82 | |||||
Maximum of Months | 5400.05 | 2726.96 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 2210.93 | 6907.61 |
Report: PeakSpaceGainsMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1404.46 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 3788.98 | 07-JAN-12:10 |
February | 2699.95 | 04-FEB-15:09 | 1404.46 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3839.40 | 18-FEB-18:00 |
March | 2699.95 | 04-MAR-15:09 | 1404.46 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2779.27 | 22-MAR-11:10 |
April | 2699.95 | 01-APR-14:09 | 1404.46 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 536.87 | 01-APR-16:00 | 2413.10 | 18-APR-17:00 |
May | 2699.95 | 06-MAY-14:09 | 1404.46 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 176.99 | 05-MAY-16:00 | 2222.97 | 23-MAY-17:00 |
June | 2699.95 | 03-JUN-14:09 | 1404.46 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 449.30 | 28-JUN-17:00 | 1962.27 | 13-JUN-14:00 |
July | 2699.95 | 01-JUL-14:09 | 1404.46 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1056.66 | 24-JUL-15:00 | 1656.15 | 09-JUL-13:00 |
August | 2699.95 | 05-AUG-14:09 | 1404.46 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1231.30 | 10-AUG-17:00 | 1714.48 | 01-AUG-11:10 |
September | 2699.95 | 02-SEP-14:09 | 1404.46 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 177.80 | 14-SEP-17:00 | 1941.53 | 16-SEP-11:10 |
October | 2699.95 | 07-OCT-14:09 | 1404.46 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2041.32 | 31-OCT-17:00 |
November | 2699.95 | 04-NOV-14:09 | 1404.46 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3111.71 | 12-NOV-17:00 |
December | 2699.95 | 02-DEC-15:09 | 1404.46 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 3697.90 | 26-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1656.15 | |||||
Maximum of Months | 2699.95 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1231.30 | 3839.40 |
Report: PeakSpaceGainsMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1404.46 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 3788.98 | 07-JAN-12:10 |
February | 2699.95 | 04-FEB-15:09 | 1404.46 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3839.40 | 18-FEB-18:00 |
March | 2699.95 | 04-MAR-15:09 | 1404.46 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2779.27 | 22-MAR-11:10 |
April | 2699.95 | 01-APR-14:09 | 1404.46 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 536.87 | 01-APR-16:00 | 2413.05 | 18-APR-17:00 |
May | 2699.95 | 06-MAY-14:09 | 1404.46 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 176.99 | 05-MAY-16:00 | 2212.73 | 23-MAY-17:00 |
June | 2699.95 | 03-JUN-14:09 | 1404.46 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 449.30 | 28-JUN-17:00 | 1955.60 | 13-JUN-14:00 |
July | 2699.95 | 01-JUL-14:09 | 1404.46 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1056.66 | 24-JUL-15:00 | 1650.16 | 09-JUL-13:00 |
August | 2699.95 | 05-AUG-14:09 | 1404.46 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1231.30 | 10-AUG-17:00 | 1712.95 | 01-AUG-11:10 |
September | 2699.95 | 02-SEP-14:09 | 1404.46 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 177.80 | 14-SEP-17:00 | 1936.22 | 16-SEP-11:10 |
October | 2699.95 | 07-OCT-14:09 | 1404.46 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2041.32 | 31-OCT-17:00 |
November | 2699.95 | 04-NOV-14:09 | 1404.46 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3111.71 | 12-NOV-17:00 |
December | 2699.95 | 02-DEC-15:09 | 1404.46 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 3697.90 | 26-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1650.16 | |||||
Maximum of Months | 2699.95 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1231.30 | 3839.40 |
Report: PeakSpaceGainsMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1404.46 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 3788.98 | 07-JAN-12:10 |
February | 2699.95 | 04-FEB-15:09 | 1404.46 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3839.40 | 18-FEB-18:00 |
March | 2699.95 | 04-MAR-15:09 | 1404.46 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2779.27 | 22-MAR-11:10 |
April | 2699.95 | 01-APR-14:09 | 1404.46 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 536.87 | 01-APR-16:00 | 2413.10 | 18-APR-17:00 |
May | 2699.95 | 06-MAY-14:09 | 1404.46 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 176.99 | 05-MAY-16:00 | 2184.86 | 23-MAY-17:00 |
June | 2699.95 | 03-JUN-14:09 | 1404.46 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 449.30 | 28-JUN-17:00 | 1920.78 | 13-JUN-14:00 |
July | 2699.95 | 01-JUL-14:09 | 1404.46 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1056.66 | 24-JUL-15:00 | 1625.45 | 09-JUL-13:00 |
August | 2699.95 | 05-AUG-14:09 | 1404.46 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1231.30 | 10-AUG-17:00 | 1706.96 | 01-AUG-11:10 |
September | 2699.95 | 02-SEP-14:09 | 1404.46 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 177.80 | 14-SEP-17:00 | 1912.03 | 16-SEP-11:10 |
October | 2699.95 | 07-OCT-14:09 | 1404.46 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2041.32 | 31-OCT-17:00 |
November | 2699.95 | 04-NOV-14:09 | 1404.46 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3111.71 | 12-NOV-17:00 |
December | 2699.95 | 02-DEC-15:09 | 1404.46 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 3697.90 | 26-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1625.45 | |||||
Maximum of Months | 2699.95 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1231.30 | 3839.40 |
Report: PeakSpaceGainsMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1404.46 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 3839.94 | 07-JAN-12:10 |
February | 2699.95 | 04-FEB-15:09 | 1404.46 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 4010.60 | 18-FEB-18:00 |
March | 2699.95 | 04-MAR-15:09 | 1404.46 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2901.44 | 22-MAR-11:10 |
April | 2699.95 | 01-APR-14:09 | 1404.46 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 566.87 | 01-APR-16:00 | 2511.52 | 18-APR-17:00 |
May | 2699.95 | 06-MAY-14:09 | 1404.46 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 180.65 | 05-MAY-16:00 | 2254.79 | 23-MAY-17:00 |
June | 2699.95 | 03-JUN-14:09 | 1404.46 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 460.34 | 28-JUN-17:00 | 1921.89 | 13-JUN-14:00 |
July | 2699.95 | 01-JUL-14:09 | 1404.46 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1082.64 | 24-JUL-15:00 | 1604.19 | 09-JUL-13:00 |
August | 2699.95 | 05-AUG-14:09 | 1404.46 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1256.75 | 10-AUG-17:00 | 1742.54 | 01-AUG-11:10 |
September | 2699.95 | 02-SEP-14:09 | 1404.46 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 182.17 | 14-SEP-17:00 | 1874.57 | 16-SEP-11:10 |
October | 2699.95 | 07-OCT-14:09 | 1404.46 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2201.94 | 31-OCT-17:00 |
November | 2699.95 | 04-NOV-14:09 | 1404.46 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3176.04 | 12-NOV-17:00 |
December | 2699.95 | 02-DEC-15:09 | 1404.46 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 3817.59 | 26-DEC-13:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1604.19 | |||||
Maximum of Months | 2699.95 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1256.75 | 4010.60 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 9667.85 | 07-JAN-00:03 | 1350.01 | 9729.72 | 2985.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 174.46 |
February | 9428.20 | 18-FEB-00:03 | 1350.01 | 9729.72 | 2985.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 144.54 |
March | 7252.57 | 24-MAR-23:03 | 1012.51 | 7297.29 | 2238.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 321.76 |
April | 9038.34 | 27-APR-16:10 | 3375.03 | 4621.63 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 911.82 | 0.00 |
May | 8938.38 | 15-MAY-16:20 | 3375.03 | 4621.63 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 49.62 | 0.00 |
June | 10425.19 | 28-JUN-17:00 | 3375.03 | 4621.63 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 818.14 | 0.00 |
July | 14681.85 | 24-JUL-07:03 | 1012.51 | 225.00 | 223.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 179.61 |
August | 15050.96 | 10-AUG-07:03 | 1012.51 | 225.00 | 223.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 181.20 |
September | 10652.31 | 14-SEP-16:10 | 3375.03 | 4621.63 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 176.23 | 0.00 |
October | 7981.78 | 04-OCT-17:10 | 3375.03 | 4621.63 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 178.19 |
November | 6997.18 | 17-NOV-00:03 | 1012.51 | 729.69 | 2238.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 303.66 |
December | 8897.01 | 22-DEC-00:03 | 1350.01 | 972.92 | 2985.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 234.87 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 6997.18 | 1012.51 | 225.00 | 223.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15050.96 | 3375.03 | 9729.72 | 2985.00 | 0.00 | 0.00 | 0.00 | 0.00 | 911.82 | 321.76 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3056.05 | 14-JAN-10:03 | 1012.48 | 8481.20 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 496.28 |
February | 2901.32 | 05-FEB-09:01 | 1687.47 | 14879.30 | 3731.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 433.86 |
March | 3165.62 | 05-MAR-09:01 | 1687.47 | 14879.30 | 3731.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 460.15 |
April | 17738.23 | 27-APR-20:09 | 9112.33 | 25443.61 | 6044.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.87 |
May | 19301.30 | 14-MAY-19:30 | 4049.92 | 8481.20 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.61 |
June | 19702.15 | 24-JUN-18:07 | 15187.21 | 25443.61 | 6044.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 124.73 |
July | 19163.90 | 07-JUL-21:35 | 8099.84 | 22616.54 | 5373.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.71 |
August | 17998.35 | 14-AUG-21:37 | 7087.36 | 19789.47 | 4701.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.07 |
September | 17810.67 | 10-SEP-19:10 | 9449.82 | 19789.47 | 4701.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.26 |
October | 19319.33 | 04-OCT-20:01 | 10124.81 | 28270.68 | 6716.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.14 |
November | 3789.24 | 11-NOV-09:01 | 1687.47 | 14879.30 | 3731.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 500.98 |
December | 3683.80 | 25-DEC-10:13 | 1012.48 | 8481.20 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 528.65 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2901.32 | 1012.48 | 8481.20 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.87 | |
Maximum of Months | 19702.15 | 15187.21 | 28270.68 | 6716.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 528.65 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3019.10 | 21-JAN-18:33 | 506.24 | 4034.55 | 1119.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 445.56 |
February | 3389.24 | 18-FEB-10:03 | 1012.48 | 7665.65 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 523.01 |
March | 3600.91 | 02-MAR-08:61 | 1687.47 | 375.00 | 3731.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 490.17 |
April | 5068.30 | 27-APR-16:10 | 1687.47 | 2555.22 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 498.94 | 0.00 |
May | 4785.28 | 06-MAY-13:00 | 2024.96 | 2555.22 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.42 | 0.00 |
June | 5357.77 | 28-JUN-16:10 | 1687.47 | 2555.22 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 372.19 | 0.00 |
July | 10227.67 | 24-JUL-06:03 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.34 |
August | 14601.79 | 10-AUG-06:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.36 |
September | 5556.70 | 14-SEP-14:00 | 1012.48 | 2555.22 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.43 | 0.00 |
October | 4496.95 | 04-OCT-14:00 | 1012.48 | 2555.22 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 455.74 |
November | 2822.22 | 16-NOV-08:61 | 1518.72 | 337.50 | 3358.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 416.19 |
December | 3083.86 | 04-DEC-08:61 | 1687.47 | 375.00 | 3731.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 392.34 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2822.22 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14601.79 | 2024.96 | 7665.65 | 3731.25 | 0.00 | 0.00 | 0.00 | 0.00 | 498.94 | 523.01 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2929.71 | 18-JAN-20:53 | 506.24 | 4034.55 | 1119.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.59 |
February | 3275.76 | 17-FEB-11:23 | 1012.48 | 7665.65 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 454.00 |
March | 3541.22 | 02-MAR-08:61 | 1687.47 | 375.00 | 3731.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 484.44 |
April | 4931.31 | 27-APR-16:10 | 1687.47 | 2555.22 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 498.94 | 0.00 |
May | 4742.00 | 06-MAY-13:00 | 2024.96 | 2555.22 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.42 | 0.00 |
June | 5325.52 | 28-JUN-16:10 | 1687.47 | 2555.22 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 372.19 | 0.00 |
July | 10481.30 | 24-JUL-06:03 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.35 |
August | 14938.01 | 10-AUG-06:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.36 |
September | 5540.40 | 14-SEP-14:00 | 1012.48 | 2555.22 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.43 | 0.00 |
October | 4401.14 | 04-OCT-14:00 | 1012.48 | 2555.22 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 455.74 |
November | 2715.19 | 10-NOV-08:61 | 1349.97 | 300.00 | 2985.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 365.30 |
December | 2511.66 | 08-DEC-09:25 | 674.99 | 5110.43 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 408.81 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2511.66 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14938.01 | 2024.96 | 7665.65 | 3731.25 | 0.00 | 0.00 | 0.00 | 0.00 | 498.94 | 484.44 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2545.41 | 23-JAN-20:45 | 337.49 | 2689.70 | 746.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.24 |
February | 2873.13 | 14-FEB-11:03 | 1012.48 | 7665.65 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 430.15 |
March | 3468.78 | 02-MAR-08:61 | 1687.47 | 375.00 | 3731.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 475.67 |
April | 4609.62 | 27-APR-16:10 | 1687.47 | 2555.22 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 498.94 | 0.00 |
May | 4525.51 | 06-MAY-13:00 | 2024.96 | 2555.22 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.42 | 0.00 |
June | 5171.70 | 28-JUN-16:10 | 1687.47 | 2555.22 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 372.19 | 0.00 |
July | 9341.17 | 24-JUL-06:03 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.32 |
August | 13235.65 | 10-AUG-06:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.33 |
September | 5385.16 | 14-SEP-14:00 | 1012.48 | 2555.22 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.43 | 0.00 |
October | 4135.70 | 04-OCT-14:00 | 1012.48 | 2555.22 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 455.74 |
November | 2652.13 | 30-NOV-10:35 | 674.99 | 5110.43 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 462.66 |
December | 2650.28 | 11-DEC-10:25 | 674.99 | 5110.43 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 404.66 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2545.41 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13235.65 | 2024.96 | 7665.65 | 3731.25 | 0.00 | 0.00 | 0.00 | 0.00 | 498.94 | 475.67 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7921.59 | 19-JAN-18:23 | 6885.06 | 8180.88 | 4029.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 815.17 |
February | 7454.16 | 14-FEB-18:43 | 6885.06 | 8180.88 | 4029.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 772.39 |
March | 5654.74 | 30-MAR-09:03 | 2227.52 | 8180.88 | 4029.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 697.43 |
April | 7758.72 | 27-APR-15:00 | 4657.54 | 2726.96 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 950.38 | 0.00 |
May | 7702.60 | 06-MAY-13:40 | 5197.55 | 2726.96 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.71 | 0.00 |
June | 9235.23 | 28-JUN-15:00 | 4657.54 | 2726.96 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 641.05 | 0.00 |
July | 18085.04 | 24-JUL-07:03 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 177.69 |
August | 17975.75 | 14-AUG-07:03 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 301.99 |
September | 9785.92 | 14-SEP-14:30 | 4657.54 | 2726.96 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.76 | 0.00 |
October | 7102.83 | 04-OCT-14:50 | 4657.54 | 2726.96 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 675.18 |
November | 7670.60 | 11-NOV-10:43 | 2227.52 | 4305.70 | 2238.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 781.96 |
December | 8323.50 | 21-DEC-19:03 | 7020.07 | 10907.84 | 5373.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 866.09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5654.74 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18085.04 | 7020.07 | 10907.84 | 5373.00 | 0.00 | 0.00 | 0.00 | 0.00 | 950.38 | 866.09 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3677.93 | 06-JAN-18:53 | 3442.43 | 4213.39 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 487.05 |
February | 2157.32 | 08-FEB-16:15 | 3644.93 | 2808.93 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2370.88 |
March | 2445.53 | 04-MAR-18:55 | 742.49 | 1478.38 | 746.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 413.44 |
April | 4072.20 | 27-APR-15:00 | 2328.71 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 528.76 | 0.00 |
May | 3949.36 | 06-MAY-13:50 | 2598.70 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.42 | 0.00 |
June | 4769.91 | 28-JUN-15:00 | 2328.71 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 356.54 | 0.00 |
July | 8433.43 | 24-JUL-07:03 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.36 |
August | 8493.29 | 14-AUG-07:03 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 166.98 |
September | 5050.67 | 14-SEP-14:30 | 2328.71 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.44 | 0.00 |
October | 3759.70 | 04-OCT-15:00 | 2328.71 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 359.31 |
November | 2583.83 | 24-NOV-20:25 | 742.49 | 1478.38 | 746.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.54 |
December | 3750.69 | 06-DEC-20:53 | 1113.73 | 2217.58 | 1119.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2157.32 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8493.29 | 3644.93 | 4213.39 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 528.76 | 2370.88 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3611.73 | 06-JAN-18:13 | 3442.43 | 4213.39 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 491.79 |
February | 3186.85 | 16-FEB-11:53 | 4353.67 | 4213.39 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 519.46 |
March | 2169.28 | 01-MAR-12:00 | 1451.22 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 321.52 |
April | 3998.62 | 27-APR-15:00 | 2328.71 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 528.76 | 0.00 |
May | 3876.77 | 06-MAY-13:50 | 2598.70 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.42 | 0.00 |
June | 4711.35 | 28-JUN-15:00 | 2328.71 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 356.54 | 0.00 |
July | 8008.10 | 24-JUL-07:03 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.25 |
August | 8088.81 | 14-AUG-07:03 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 166.87 |
September | 4996.96 | 14-SEP-14:30 | 2328.71 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.44 | 0.00 |
October | 3682.93 | 04-OCT-15:00 | 2328.71 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 359.31 |
November | 2829.68 | 29-NOV-19:23 | 2632.45 | 4213.39 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 491.45 |
December | 2744.22 | 22-DEC-18:55 | 2294.96 | 2808.93 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 414.43 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2169.28 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8088.81 | 4353.67 | 4213.39 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 528.76 | 519.46 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3199.03 | 20-JAN-18:53 | 3442.43 | 4213.39 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 475.82 |
February | 2264.31 | 08-FEB-13:45 | 4792.41 | 2808.93 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2431.10 |
March | 1902.44 | 01-MAR-12:00 | 1451.22 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 321.09 |
April | 3799.25 | 27-APR-15:00 | 2328.71 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 528.76 | 0.00 |
May | 3677.01 | 06-MAY-13:50 | 2598.70 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.42 | 0.00 |
June | 4571.39 | 28-JUN-15:00 | 2328.71 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 356.54 | 0.00 |
July | 6297.18 | 24-JUL-07:03 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.83 |
August | 6622.21 | 14-AUG-07:03 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 166.50 |
September | 4894.11 | 14-SEP-14:30 | 2328.71 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.43 | 0.00 |
October | 3403.43 | 04-OCT-15:00 | 2328.71 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 359.31 |
November | 2479.25 | 16-NOV-20:25 | 742.49 | 1478.38 | 746.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.95 |
December | 2440.96 | 13-DEC-18:35 | 2294.96 | 2808.93 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 369.79 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1902.44 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 6622.21 | 4792.41 | 4213.39 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 528.76 | 2431.10 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 843.59 | 11-JAN-18:30 | 1147.48 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 283.48 |
February | 1585.14 | 28-FEB-20:25 | 742.49 | 1478.38 | 746.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.37 |
March | 2023.52 | 24-MAR-18:45 | 1754.97 | 2808.93 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 407.27 |
April | 3784.61 | 27-APR-15:00 | 2328.71 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 545.86 | 0.00 |
May | 3640.88 | 06-MAY-13:40 | 2598.70 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.43 | 0.00 |
June | 4582.63 | 28-JUN-15:00 | 2328.71 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 369.44 | 0.00 |
July | 6359.45 | 24-JUL-15:00 | 2328.71 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1082.64 | 0.00 |
August | 6679.49 | 10-AUG-14:50 | 2328.71 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 991.10 | 0.00 |
September | 4998.96 | 14-SEP-14:20 | 2328.71 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.44 | 0.00 |
October | 3016.90 | 04-OCT-15:00 | 2328.71 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 373.96 |
November | 1546.38 | 15-NOV-13:15 | 4792.41 | 2808.93 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1981.87 |
December | 910.09 | 02-DEC-12:00 | 1957.46 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 294.69 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 843.59 | 742.49 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 6679.49 | 4792.41 | 2808.93 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 1082.64 | 1981.87 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.694863E+11 | 59265.75 | 25-JAN-17:49 | 0.839721E+11 | 144700.38 | 16-JAN-09:09 |
February | 0.620364E+11 | 57116.52 | 21-FEB-17:00 | 0.556277E+11 | 142363.22 | 19-FEB-09:09 |
March | 0.682767E+11 | 54949.71 | 27-MAR-18:49 | 0.291703E+11 | 89166.13 | 25-MAR-07:10 |
April | 0.650574E+11 | 64618.67 | 27-APR-16:00 | 0.105398E+11 | 70487.40 | 18-APR-07:10 |
May | 0.675622E+11 | 62662.58 | 06-MAY-13:39 | 0.131790E+10 | 30267.03 | 18-MAY-08:20 |
June | 0.669585E+11 | 64389.30 | 28-JUN-16:19 | 14349206.89 | 3892.89 | 15-JUN-07:10 |
July | 0.728751E+11 | 71233.75 | 24-JUL-14:39 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.776390E+11 | 74483.43 | 29-AUG-13:50 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.679593E+11 | 65143.24 | 14-SEP-14:09 | 90674643.67 | 10913.32 | 28-SEP-08:20 |
October | 0.678977E+11 | 56918.59 | 17-OCT-17:40 | 0.724276E+10 | 43670.94 | 30-OCT-07:10 |
November | 0.667798E+11 | 56985.27 | 07-NOV-17:30 | 0.429953E+11 | 97395.26 | 24-NOV-08:09 |
December | 0.694330E+11 | 57573.15 | 31-DEC-16:40 | 0.712445E+11 | 138293.21 | 26-DEC-08:09 |
Annual Sum or Average | 0.821961E+12 | 0.302215E+12 | ||||
Minimum of Months | 0.620364E+11 | 54949.71 | 0.00 | 0.00 | ||
Maximum of Months | 0.776390E+11 | 74483.43 | 0.839721E+11 | 144700.38 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.310073E+11 | 0.713686E+10 | 0.108325E+11 | 0.00 | 0.149399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.556987E+10 | 0.00 |
February | 0.280657E+11 | 0.570615E+10 | 0.980803E+10 | 0.00 | 0.134090E+11 | 0.00 | 0.00 | 291010.46 | 0.00 | 0.00 | 0.00 | 0.504720E+10 | 0.00 |
March | 0.314703E+11 | 0.530301E+10 | 0.110075E+11 | 0.00 | 0.148955E+11 | 0.00 | 0.00 | 1166598.29 | 0.00 | 0.00 | 0.00 | 0.559932E+10 | 0.00 |
April | 0.300741E+11 | 0.411349E+10 | 0.105079E+11 | 0.00 | 0.141671E+11 | 0.00 | 0.00 | 0.862770E+09 | 0.00 | 0.00 | 0.00 | 0.533205E+10 | 0.00 |
May | 0.312330E+11 | 0.348367E+10 | 0.109147E+11 | 0.00 | 0.148143E+11 | 0.00 | 0.00 | 0.167734E+10 | 0.00 | 0.00 | 0.00 | 0.543921E+10 | 0.00 |
June | 0.304143E+11 | 0.299473E+10 | 0.106386E+11 | 0.00 | 0.145352E+11 | 0.00 | 0.00 | 0.316263E+10 | 0.00 | 0.00 | 0.00 | 0.521304E+10 | 0.00 |
July | 0.309042E+11 | 0.322606E+10 | 0.107945E+11 | 0.00 | 0.147550E+11 | 0.00 | 0.00 | 0.789915E+10 | 0.00 | 0.00 | 0.00 | 0.529623E+10 | 0.00 |
August | 0.314595E+11 | 0.385505E+10 | 0.110006E+11 | 0.00 | 0.150210E+11 | 0.00 | 0.00 | 0.109670E+11 | 0.00 | 0.00 | 0.00 | 0.533571E+10 | 0.00 |
September | 0.300847E+11 | 0.468843E+10 | 0.105148E+11 | 0.00 | 0.143663E+11 | 0.00 | 0.00 | 0.314720E+10 | 0.00 | 0.00 | 0.00 | 0.515786E+10 | 0.00 |
October | 0.310073E+11 | 0.589777E+10 | 0.108325E+11 | 0.00 | 0.146294E+11 | 0.00 | 0.00 | 0.138721E+09 | 0.00 | 0.00 | 0.00 | 0.539210E+10 | 0.00 |
November | 0.300409E+11 | 0.663132E+10 | 0.104978E+11 | 0.00 | 0.142935E+11 | 0.00 | 0.00 | 20031474.15 | 0.00 | 0.00 | 0.00 | 0.529619E+10 | 0.00 |
December | 0.309156E+11 | 0.737807E+10 | 0.108050E+11 | 0.00 | 0.148035E+11 | 0.00 | 0.00 | 4975.97 | 0.00 | 0.00 | 0.00 | 0.553080E+10 | 0.00 |
Annual Sum or Average | 0.366677E+12 | 0.604146E+11 | 0.128154E+12 | 0.00 | 0.174630E+12 | 0.00 | 0.00 | 0.278763E+11 | 0.00 | 0.00 | 0.00 | 0.642096E+11 | 0.00 |
Minimum of Months | 0.280657E+11 | 0.299473E+10 | 0.980803E+10 | 0.00 | 0.134090E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.504720E+10 | 0.00 |
Maximum of Months | 0.314703E+11 | 0.737807E+10 | 0.110075E+11 | 0.00 | 0.150210E+11 | 0.00 | 0.00 | 0.109670E+11 | 0.00 | 0.00 | 0.00 | 0.559932E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.839721E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.556277E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.291703E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.105398E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.131790E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 14349206.89 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 90674643.67 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.724276E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.429953E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.712445E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.302215E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.839721E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 23459.17 | 01-JAN-11:09 | 5507.06 | 01-JAN-06:10 | 8059.50 | 01-JAN-11:09 | 0.00 | 10992.51 | 16-JAN-09:09 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 23459.17 | 01-FEB-10:09 | 5507.06 | 01-FEB-06:10 | 8059.50 | 01-FEB-10:09 | 0.00 | 10991.57 | 19-FEB-09:09 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 23459.17 | 01-MAR-10:09 | 5507.06 | 01-MAR-06:10 | 8059.50 | 01-MAR-10:09 | 0.00 | 10717.21 | 25-MAR-07:10 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 23459.17 | 01-APR-09:09 | 5507.06 | 01-APR-05:10 | 8059.50 | 01-APR-09:09 | 0.00 | 10597.65 | 18-APR-08:09 | 0.00 | 0.00 | 01-APR-00:10 |
May | 23459.17 | 01-MAY-09:09 | 5507.06 | 01-MAY-19:19 | 8059.50 | 01-MAY-09:09 | 0.00 | 10445.77 | 18-MAY-08:09 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 23459.17 | 01-JUN-09:09 | 5507.06 | 01-JUN-19:00 | 8059.50 | 01-JUN-09:09 | 0.00 | 10181.70 | 09-JUN-18:49 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 23459.17 | 01-JUL-09:09 | 5507.06 | 01-JUL-20:10 | 8059.50 | 01-JUL-09:09 | 0.00 | 10327.51 | 24-JUL-14:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 23459.17 | 01-AUG-09:09 | 5507.06 | 01-AUG-19:40 | 8059.50 | 01-AUG-09:09 | 0.00 | 10532.61 | 10-AUG-16:10 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 23459.17 | 01-SEP-09:09 | 5507.06 | 01-SEP-05:10 | 8059.50 | 01-SEP-09:09 | 0.00 | 10297.60 | 28-SEP-08:20 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 23459.17 | 01-OCT-10:09 | 5507.06 | 01-OCT-05:10 | 8059.50 | 01-OCT-10:09 | 0.00 | 10489.18 | 30-OCT-08:09 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 23459.17 | 01-NOV-09:09 | 5507.06 | 01-NOV-05:10 | 8059.50 | 01-NOV-09:09 | 0.00 | 10737.72 | 24-NOV-08:09 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 23459.17 | 01-DEC-10:09 | 5507.06 | 01-DEC-06:10 | 8059.50 | 01-DEC-10:09 | 0.00 | 10965.13 | 26-DEC-08:09 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||||
Minimum of Months | 23459.17 | 5507.06 | 8059.50 | 0.00 | 10181.70 | 0.00 | 0.00 | |||||
Maximum of Months | 23459.17 | 5507.06 | 8059.50 | 0.00 | 10992.51 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 13988.60 | 20-JAN-13:00 | 0.00 |
February | 204.62 | 27-FEB-21:10 | 0.00 | 0.00 | 0.00 | 9602.62 | 07-FEB-09:09 | 0.00 |
March | 289.57 | 18-MAR-20:00 | 0.00 | 0.00 | 0.00 | 9721.31 | 27-MAR-13:00 | 0.00 |
April | 17086.97 | 27-APR-14:00 | 0.00 | 0.00 | 0.00 | 9651.77 | 20-APR-10:20 | 0.00 |
May | 15568.62 | 06-MAY-12:00 | 0.00 | 0.00 | 0.00 | 9709.11 | 18-MAY-13:30 | 0.00 |
June | 17658.47 | 28-JUN-16:00 | 0.00 | 0.00 | 0.00 | 8467.11 | 12-JUN-13:00 | 0.00 |
July | 24505.37 | 24-JUL-14:00 | 0.00 | 0.00 | 0.00 | 8797.45 | 27-JUL-16:30 | 0.00 |
August | 26821.93 | 29-AUG-14:00 | 0.00 | 0.00 | 0.00 | 9639.71 | 02-AUG-10:30 | 0.00 |
September | 17997.93 | 14-SEP-14:09 | 0.00 | 0.00 | 0.00 | 7580.41 | 08-SEP-12:09 | 0.00 |
October | 8376.87 | 04-OCT-14:00 | 0.00 | 0.00 | 0.00 | 9709.43 | 17-OCT-12:50 | 0.00 |
November | 2685.51 | 04-NOV-14:39 | 0.00 | 0.00 | 0.00 | 9710.46 | 07-NOV-14:20 | 0.00 |
December | 8.29 | 03-DEC-20:00 | 0.00 | 0.00 | 0.00 | 10698.93 | 30-DEC-15:00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 7580.41 | 0.00 | ||
Maximum of Months | 26821.93 | 0.00 | 0.00 | 0.00 | 13988.60 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 59265.75 | 25-JAN-17:49 | 23459.17 | 8059.50 | 5507.06 | 0.00 | 10496.75 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 57116.52 | 21-FEB-17:00 | 23459.17 | 8059.50 | 5507.06 | 0.00 | 10661.10 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 54949.71 | 27-MAR-18:49 | 23459.17 | 8059.50 | 5507.06 | 0.00 | 10311.60 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 64618.67 | 27-APR-16:00 | 23459.17 | 8059.50 | 0.00 | 0.00 | 10181.70 | 0.00 | 0.00 | 15489.09 | 0.00 |
May | 62662.58 | 06-MAY-13:39 | 23459.17 | 8059.50 | 0.00 | 0.00 | 10181.70 | 0.00 | 0.00 | 15502.42 | 0.00 |
June | 64389.30 | 28-JUN-16:19 | 23459.17 | 8059.50 | 0.00 | 0.00 | 10181.70 | 0.00 | 0.00 | 17246.52 | 0.00 |
July | 71233.75 | 24-JUL-14:39 | 23459.17 | 8059.50 | 0.00 | 0.00 | 10282.39 | 0.00 | 0.00 | 23990.57 | 0.00 |
August | 74483.43 | 29-AUG-13:50 | 23459.17 | 8059.50 | 0.00 | 0.00 | 10380.26 | 0.00 | 0.00 | 25008.94 | 0.00 |
September | 65143.24 | 14-SEP-14:09 | 23459.17 | 8059.50 | 0.00 | 0.00 | 10181.70 | 0.00 | 0.00 | 17997.93 | 0.00 |
October | 56918.59 | 17-OCT-17:40 | 23459.17 | 8059.50 | 5507.06 | 0.00 | 10221.80 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 56985.27 | 07-NOV-17:30 | 23459.17 | 8059.50 | 5507.06 | 0.00 | 10284.25 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 57573.15 | 31-DEC-16:40 | 23459.17 | 8059.50 | 5507.06 | 0.00 | 10570.30 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 54949.71 | 23459.17 | 8059.50 | 0.00 | 0.00 | 10181.70 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 74483.43 | 23459.17 | 8059.50 | 5507.06 | 0.00 | 10661.10 | 0.00 | 0.00 | 25008.94 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 144700.38 | 16-JAN-09:09 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 142363.22 | 19-FEB-09:09 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 89166.13 | 25-MAR-07:10 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 70487.40 | 18-APR-07:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 30267.03 | 18-MAY-08:20 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 3892.89 | 15-JUN-07:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 10913.32 | 28-SEP-08:20 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 43670.94 | 30-OCT-07:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 97395.26 | 24-NOV-08:09 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 138293.21 | 26-DEC-08:09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 144700.38 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.67 | 20.46 | 0.00 | 20.46 | 0.00 | 20.46 | 0.00 | 20.46 |
February | 0.67 | 20.49 | 0.00 | 20.49 | 0.00 | 20.49 | 0.00 | 20.49 |
March | 0.67 | 20.50 | 0.00 | 20.50 | 0.00 | 20.50 | 0.00 | 20.50 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.17 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 |
December | 1.33 | 20.49 | 0.00 | 20.49 | 0.00 | 20.49 | 0.00 | 20.49 |
Annual Sum or Average | 4.50 | 20.48 | 0.00 | 20.48 | 0.00 | 20.48 | 0.00 | 20.48 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.67 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 20.50 | 0.00 | 20.50 | 0.00 | 20.50 | 0.00 | 20.50 |
February | 0.17 | 20.54 | 0.00 | 20.54 | 0.00 | 20.54 | 0.00 | 20.54 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.33 | 20.52 | 0.00 | 20.52 | 0.00 | 20.52 | 0.00 | 20.52 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 20.54 | 0.00 | 20.54 | 0.00 | 20.54 | 0.00 | 20.54 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 20.50 | 0.00 | 20.50 | 0.00 | 20.50 | 0.00 | 20.50 |
February | 0.17 | 20.54 | 0.00 | 20.54 | 0.00 | 20.54 | 0.00 | 20.54 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.33 | 20.52 | 0.00 | 20.52 | 0.00 | 20.52 | 0.00 | 20.52 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 20.54 | 0.00 | 20.54 | 0.00 | 20.54 | 0.00 | 20.54 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 20.47 | 0.00 | 20.47 | 0.00 | 20.47 | 0.00 | 20.47 |
February | 0.33 | 20.53 | 0.00 | 20.53 | 0.00 | 20.53 | 0.00 | 20.53 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.50 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.33 | 20.53 | 0.00 | 20.53 | 0.00 | 20.53 | 0.00 | 20.53 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.00 | 20.48 | 0.00 | 20.48 | 0.00 | 20.48 | 0.00 | 20.48 |
February | 0.50 | 20.46 | 0.00 | 20.46 | 0.00 | 20.46 | 0.00 | 20.46 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.33 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 |
Annual Sum or Average | 1.83 | 20.48 | 0.00 | 20.48 | 0.00 | 20.48 | 0.00 | 20.48 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.00 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 4.50 | 20.27 | 0.00 | 20.27 | 0.00 | 20.27 | 0.00 | 20.27 |
February | 3.33 | 19.75 | 0.00 | 19.75 | 0.00 | 19.75 | 0.00 | 19.75 |
March | 1.00 | 20.47 | 0.00 | 20.47 | 0.00 | 20.47 | 0.00 | 20.47 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.83 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 |
December | 2.83 | 20.41 | 0.00 | 20.41 | 0.00 | 20.41 | 0.00 | 20.41 |
Annual Sum or Average | 12.50 | 20.20 | 0.00 | 20.20 | 0.00 | 20.20 | 0.00 | 20.20 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4.50 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 |
Report: ComfortReportSimple55Monthly
For: LGSTORE1
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 496.00 | 21.07 | 184.33 | 21.06 | 184.33 | 21.05 |
February | 448.00 | 21.14 | 133.00 | 21.12 | 133.00 | 21.10 |
March | 497.00 | 21.22 | 42.33 | 21.19 | 42.33 | 21.17 |
April | 434.50 | 21.67 | 23.00 | 21.72 | 9.00 | 21.71 |
May | 355.67 | 22.31 | 49.50 | 22.50 | 0.00 | 22.50 |
June | 162.83 | 22.92 | 98.00 | 23.28 | 0.00 | 23.28 |
July | 57.17 | 23.36 | 286.83 | 23.80 | 0.00 | 23.80 |
August | 38.33 | 23.25 | 337.83 | 23.82 | 0.00 | 23.82 |
September | 177.00 | 22.70 | 174.00 | 23.29 | 0.00 | 23.29 |
October | 407.67 | 21.68 | 8.17 | 21.72 | 0.33 | 21.72 |
November | 470.17 | 21.21 | 34.83 | 21.19 | 34.17 | 21.17 |
December | 496.00 | 21.07 | 114.00 | 21.05 | 114.00 | 21.03 |
Annual Sum or Average | 4040.33 | 21.55 | 1485.83 | 21.90 | 517.17 | 21.83 |
Minimum of Months | 38.33 | 21.07 | 8.17 | 21.05 | 0.00 | 21.03 |
Maximum of Months | 497.00 | 23.36 | 337.83 | 23.82 | 184.33 | 23.82 |
Report: ComfortReportSimple55Monthly
For: SMSTORE1
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 496.00 | 21.47 | 25.17 | 21.46 | 25.17 | 21.44 |
February | 444.83 | 21.73 | 16.50 | 21.71 | 16.50 | 21.69 |
March | 497.00 | 22.18 | 0.50 | 22.18 | 0.50 | 22.18 |
April | 389.17 | 22.74 | 22.00 | 22.80 | 0.00 | 22.80 |
May | 195.50 | 23.25 | 62.33 | 23.41 | 0.00 | 23.41 |
June | 54.67 | 23.54 | 121.00 | 23.78 | 0.00 | 23.78 |
July | 15.67 | 23.64 | 288.83 | 23.87 | 0.00 | 23.87 |
August | 10.50 | 23.39 | 347.00 | 23.86 | 0.00 | 23.86 |
September | 65.33 | 23.37 | 219.00 | 23.76 | 0.00 | 23.76 |
October | 339.50 | 22.78 | 14.67 | 22.83 | 0.00 | 22.83 |
November | 449.33 | 21.84 | 8.33 | 21.88 | 0.00 | 21.88 |
December | 496.00 | 21.55 | 6.67 | 21.55 | 6.67 | 21.54 |
Annual Sum or Average | 3453.50 | 22.12 | 1132.00 | 22.53 | 48.83 | 22.51 |
Minimum of Months | 10.50 | 21.47 | 0.50 | 21.46 | 0.00 | 21.44 |
Maximum of Months | 497.00 | 23.64 | 347.00 | 23.87 | 25.17 | 23.87 |
Report: ComfortReportSimple55Monthly
For: SMSTORE2
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 371.00 | 21.12 | 65.00 | 21.12 | 65.00 | 21.12 |
February | 336.00 | 21.30 | 36.83 | 21.28 | 36.83 | 21.26 |
March | 379.00 | 21.56 | 6.83 | 21.56 | 6.83 | 21.55 |
April | 307.00 | 22.19 | 18.33 | 22.30 | 0.00 | 22.30 |
May | 166.83 | 22.91 | 57.17 | 23.21 | 0.00 | 23.21 |
June | 50.50 | 23.32 | 109.83 | 23.85 | 0.00 | 23.85 |
July | 13.50 | 23.63 | 248.00 | 24.02 | 0.00 | 24.02 |
August | 10.83 | 23.53 | 311.33 | 24.01 | 0.17 | 24.01 |
September | 69.33 | 23.14 | 175.33 | 23.76 | 0.00 | 23.76 |
October | 272.67 | 22.22 | 11.67 | 22.29 | 0.00 | 22.29 |
November | 348.50 | 21.36 | 11.83 | 21.39 | 6.83 | 21.39 |
December | 369.00 | 21.12 | 35.83 | 21.12 | 35.83 | 21.12 |
Annual Sum or Average | 2694.17 | 21.70 | 1088.00 | 22.25 | 151.50 | 22.21 |
Minimum of Months | 10.83 | 21.12 | 6.83 | 21.12 | 0.00 | 21.12 |
Maximum of Months | 379.00 | 23.63 | 311.33 | 24.02 | 65.00 | 24.02 |
Report: ComfortReportSimple55Monthly
For: SMSTORE3
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 371.00 | 21.12 | 77.50 | 21.12 | 77.50 | 21.11 |
February | 336.00 | 21.27 | 44.50 | 21.25 | 44.50 | 21.24 |
March | 379.00 | 21.50 | 10.17 | 21.49 | 10.17 | 21.48 |
April | 310.83 | 22.10 | 18.17 | 22.20 | 0.50 | 22.20 |
May | 183.17 | 22.87 | 53.17 | 23.14 | 0.00 | 23.14 |
June | 54.33 | 23.31 | 106.67 | 23.83 | 0.00 | 23.83 |
July | 14.50 | 23.61 | 246.67 | 24.02 | 0.00 | 24.02 |
August | 11.50 | 23.52 | 310.00 | 24.01 | 0.17 | 24.01 |
September | 74.33 | 23.10 | 169.33 | 23.72 | 0.00 | 23.72 |
October | 279.17 | 22.12 | 9.83 | 22.18 | 0.00 | 22.18 |
November | 350.00 | 21.32 | 15.83 | 21.34 | 11.83 | 21.34 |
December | 369.00 | 21.12 | 46.83 | 21.12 | 46.83 | 21.12 |
Annual Sum or Average | 2732.83 | 21.67 | 1108.67 | 22.21 | 191.50 | 22.15 |
Minimum of Months | 11.50 | 21.12 | 9.83 | 21.12 | 0.00 | 21.11 |
Maximum of Months | 379.00 | 23.61 | 310.00 | 24.02 | 77.50 | 24.02 |
Report: ComfortReportSimple55Monthly
For: SMSTORE4
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 371.00 | 21.11 | 99.17 | 21.11 | 99.17 | 21.11 |
February | 336.00 | 21.23 | 58.00 | 21.22 | 58.00 | 21.20 |
March | 379.00 | 21.40 | 16.17 | 21.39 | 16.17 | 21.38 |
April | 320.33 | 21.97 | 18.33 | 22.06 | 2.50 | 22.05 |
May | 230.33 | 22.80 | 44.00 | 23.00 | 0.00 | 23.00 |
June | 75.00 | 23.25 | 94.83 | 23.72 | 0.00 | 23.72 |
July | 20.33 | 23.57 | 236.50 | 24.00 | 0.00 | 24.00 |
August | 14.00 | 23.45 | 298.33 | 24.00 | 0.17 | 24.00 |
September | 93.00 | 22.99 | 150.67 | 23.61 | 0.00 | 23.61 |
October | 291.33 | 21.97 | 6.33 | 22.01 | 0.00 | 22.01 |
November | 352.00 | 21.27 | 19.83 | 21.28 | 16.83 | 21.27 |
December | 369.00 | 21.11 | 60.17 | 21.11 | 60.17 | 21.11 |
Annual Sum or Average | 2851.33 | 21.65 | 1102.33 | 22.13 | 253.00 | 22.07 |
Minimum of Months | 14.00 | 21.11 | 6.33 | 21.11 | 0.00 | 21.11 |
Maximum of Months | 379.00 | 23.57 | 298.33 | 24.00 | 99.17 | 24.00 |
Report: ComfortReportSimple55Monthly
For: LGSTORE2
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.11 | 169.17 | 21.11 | 169.17 | 21.11 |
February | 308.00 | 21.16 | 114.00 | 21.15 | 114.00 | 21.14 |
March | 348.00 | 21.20 | 29.17 | 21.19 | 29.17 | 21.19 |
April | 304.83 | 21.59 | 12.33 | 21.65 | 3.83 | 21.64 |
May | 260.83 | 22.22 | 27.83 | 22.39 | 0.00 | 22.39 |
June | 137.00 | 22.93 | 54.00 | 23.21 | 0.00 | 23.21 |
July | 40.50 | 23.24 | 188.83 | 23.81 | 0.00 | 23.81 |
August | 24.00 | 23.07 | 231.83 | 23.84 | 0.00 | 23.84 |
September | 145.67 | 22.54 | 107.17 | 23.13 | 0.00 | 23.13 |
October | 300.00 | 21.66 | 0.00 | 21.66 | 0.00 | 21.66 |
November | 325.67 | 21.16 | 28.50 | 21.15 | 28.50 | 21.15 |
December | 338.00 | 21.11 | 114.50 | 21.11 | 114.50 | 21.11 |
Annual Sum or Average | 2872.50 | 21.55 | 1077.33 | 21.87 | 459.17 | 21.79 |
Minimum of Months | 24.00 | 21.11 | 0.00 | 21.11 | 0.00 | 21.11 |
Maximum of Months | 348.00 | 23.24 | 231.83 | 23.84 | 169.17 | 23.84 |
Report: ComfortReportSimple55Monthly
For: SMSTORE5
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.11 | 169.00 | 21.11 | 169.00 | 21.11 |
February | 308.00 | 21.19 | 115.33 | 21.17 | 115.33 | 21.16 |
March | 348.00 | 21.27 | 31.33 | 21.25 | 31.33 | 21.24 |
April | 304.67 | 21.78 | 11.00 | 21.81 | 4.67 | 21.80 |
May | 256.67 | 22.58 | 24.50 | 22.70 | 0.00 | 22.70 |
June | 131.00 | 23.30 | 44.17 | 23.47 | 0.00 | 23.47 |
July | 32.17 | 23.54 | 173.50 | 23.89 | 0.00 | 23.89 |
August | 17.50 | 23.36 | 219.17 | 23.89 | 0.00 | 23.89 |
September | 129.33 | 22.88 | 103.33 | 23.35 | 0.00 | 23.35 |
October | 287.50 | 21.81 | 0.67 | 21.81 | 0.17 | 21.81 |
November | 325.50 | 21.19 | 29.83 | 21.19 | 29.83 | 21.18 |
December | 338.00 | 21.11 | 114.33 | 21.11 | 114.33 | 21.11 |
Annual Sum or Average | 2818.33 | 21.65 | 1036.17 | 21.92 | 464.67 | 21.84 |
Minimum of Months | 17.50 | 21.11 | 0.67 | 21.11 | 0.00 | 21.11 |
Maximum of Months | 348.00 | 23.54 | 219.17 | 23.89 | 169.00 | 23.89 |
Report: ComfortReportSimple55Monthly
For: SMSTORE6
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.11 | 176.33 | 21.11 | 176.33 | 21.11 |
February | 308.00 | 21.19 | 119.67 | 21.17 | 119.67 | 21.15 |
March | 348.00 | 21.26 | 35.00 | 21.24 | 35.00 | 21.23 |
April | 305.83 | 21.76 | 10.17 | 21.78 | 5.17 | 21.77 |
May | 260.17 | 22.55 | 23.50 | 22.66 | 0.00 | 22.66 |
June | 136.33 | 23.28 | 41.83 | 23.45 | 0.00 | 23.45 |
July | 35.17 | 23.53 | 167.17 | 23.88 | 0.00 | 23.88 |
August | 19.17 | 23.36 | 215.33 | 23.89 | 0.00 | 23.89 |
September | 132.50 | 22.86 | 101.50 | 23.33 | 0.00 | 23.33 |
October | 290.50 | 21.80 | 0.33 | 21.80 | 0.33 | 21.80 |
November | 325.83 | 21.19 | 33.17 | 21.18 | 33.17 | 21.18 |
December | 338.00 | 21.11 | 120.00 | 21.11 | 120.00 | 21.11 |
Annual Sum or Average | 2839.50 | 21.65 | 1044.00 | 21.91 | 489.67 | 21.82 |
Minimum of Months | 19.17 | 21.11 | 0.33 | 21.11 | 0.00 | 21.11 |
Maximum of Months | 348.00 | 23.53 | 215.33 | 23.89 | 176.33 | 23.89 |
Report: ComfortReportSimple55Monthly
For: SMSTORE7
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.11 | 205.50 | 21.11 | 205.50 | 21.11 |
February | 308.00 | 21.17 | 134.67 | 21.15 | 134.67 | 21.14 |
March | 348.00 | 21.22 | 48.50 | 21.21 | 48.50 | 21.20 |
April | 308.50 | 21.68 | 11.00 | 21.68 | 9.67 | 21.66 |
May | 273.67 | 22.41 | 19.67 | 22.51 | 0.00 | 22.51 |
June | 155.00 | 23.18 | 35.00 | 23.32 | 0.00 | 23.32 |
July | 45.67 | 23.46 | 155.83 | 23.84 | 0.00 | 23.84 |
August | 25.17 | 23.31 | 207.33 | 23.86 | 0.00 | 23.86 |
September | 147.17 | 22.74 | 92.17 | 23.20 | 0.00 | 23.20 |
October | 306.00 | 21.79 | 0.83 | 21.79 | 0.83 | 21.79 |
November | 326.33 | 21.18 | 47.50 | 21.17 | 47.50 | 21.16 |
December | 338.00 | 21.11 | 154.00 | 21.11 | 154.00 | 21.11 |
Annual Sum or Average | 2921.50 | 21.64 | 1112.00 | 21.85 | 600.67 | 21.76 |
Minimum of Months | 25.17 | 21.11 | 0.83 | 21.11 | 0.00 | 21.11 |
Maximum of Months | 348.00 | 23.46 | 207.33 | 23.86 | 205.50 | 23.86 |
Report: ComfortReportSimple55Monthly
For: SMSTORE8
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.11 | 321.33 | 21.11 | 321.33 | 21.11 |
February | 308.00 | 21.15 | 192.17 | 21.14 | 192.17 | 21.13 |
March | 348.00 | 21.18 | 125.00 | 21.16 | 125.00 | 21.15 |
April | 313.50 | 21.59 | 35.33 | 21.54 | 35.33 | 21.50 |
May | 294.00 | 22.21 | 14.50 | 22.28 | 1.67 | 22.27 |
June | 179.17 | 22.96 | 25.17 | 23.09 | 0.00 | 23.09 |
July | 72.33 | 23.28 | 140.00 | 23.73 | 0.00 | 23.73 |
August | 44.67 | 23.20 | 190.67 | 23.79 | 0.00 | 23.79 |
September | 177.67 | 22.53 | 80.17 | 22.97 | 0.00 | 22.97 |
October | 324.67 | 21.75 | 10.17 | 21.73 | 10.17 | 21.71 |
November | 327.33 | 21.17 | 146.83 | 21.15 | 146.83 | 21.14 |
December | 338.00 | 21.11 | 270.50 | 21.11 | 270.50 | 21.11 |
Annual Sum or Average | 3067.33 | 21.62 | 1551.83 | 21.73 | 1103.00 | 21.61 |
Minimum of Months | 44.67 | 21.11 | 10.17 | 21.11 | 0.00 | 21.11 |
Maximum of Months | 348.00 | 23.28 | 321.33 | 23.79 | 321.33 | 23.79 |
Report: OccupantComfortDataSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 496.00000 | 21.07313 | 30.41109 | -0.5200 | 10.82540 |
February | 448.00000 | 21.14431 | 32.24102 | -0.4570 | 9.84532 |
March | 497.00000 | 21.21664 | 33.57402 | -0.3838 | 8.44800 |
April | 479.00000 | 21.87318 | 37.03337 | -0.1710 | 7.06523 |
May | 496.00000 | 22.75110 | 40.38548 | -0.9167 | 25.01793 |
June | 481.00000 | 23.54844 | 40.98135 | -0.6214 | 14.05227 |
July | 495.00000 | 23.81766 | 44.48931 | -0.4658 | 9.91727 |
August | 497.00000 | 23.82758 | 47.62170 | -0.4376 | 9.34541 |
September | 479.00000 | 23.42564 | 46.95049 | -0.6186 | 14.47499 |
October | 496.00000 | 22.06803 | 41.20632 | -0.0870 | 6.68055 |
November | 480.00000 | 21.25838 | 39.26188 | -0.3564 | 8.39033 |
December | 496.00000 | 21.07218 | 32.66306 | -0.4879 | 10.11931 |
Annual Sum or Average | 5840.00000 | 22.26245 | 38.93164 | -0.4605 | 11.19493 |
Minimum of Months | 448.00000 | 21.07218 | 30.41109 | -0.9167 | 6.68055 |
Maximum of Months | 497.00000 | 23.82758 | 47.62170 | -0.0870 | 25.01793 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 496.00000 | 21.47495 | 32.69667 | -0.3704 | 8.21889 |
February | 448.00000 | 21.74891 | 33.71421 | -0.2790 | 7.60122 |
March | 497.00000 | 22.17849 | 33.94639 | -0.1485 | 6.33187 |
April | 479.00000 | 22.94322 | 36.02891 | 0.07220 | 6.22097 |
May | 496.00000 | 23.62464 | 38.55675 | -0.6402 | 14.35360 |
June | 481.00000 | 23.83204 | 39.97605 | -0.5177 | 10.81319 |
July | 495.00000 | 23.85407 | 44.29534 | -0.4439 | 9.31134 |
August | 497.00000 | 23.83679 | 47.49841 | -0.4231 | 8.93439 |
September | 479.00000 | 23.79435 | 45.74316 | -0.4948 | 10.49481 |
October | 496.00000 | 23.13012 | 39.62387 | 0.14934 | 6.33312 |
November | 480.00000 | 21.97416 | 40.19827 | -0.1674 | 6.85375 |
December | 496.00000 | 21.55252 | 34.86434 | -0.3292 | 7.70094 |
Annual Sum or Average | 5840.00000 | 22.83407 | 38.95352 | -0.2998 | 8.60556 |
Minimum of Months | 448.00000 | 21.47495 | 32.69667 | -0.6402 | 6.22097 |
Maximum of Months | 497.00000 | 23.85407 | 47.49841 | 0.14934 | 14.35360 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 21.11842 | 30.28400 | -0.4665 | 9.65947 |
February | 336.00000 | 21.29745 | 31.56307 | -0.3857 | 8.73873 |
March | 379.00000 | 21.56411 | 32.20539 | -0.2779 | 7.23796 |
April | 360.00000 | 22.44847 | 35.14100 | -0.0305 | 6.46559 |
May | 375.00000 | 23.47330 | 38.27870 | -0.6779 | 15.91045 |
June | 366.00000 | 23.87300 | 39.24408 | -0.5101 | 10.83877 |
July | 369.00000 | 23.98681 | 44.04023 | -0.4076 | 8.82313 |
August | 379.00000 | 23.98899 | 47.41250 | -0.3784 | 8.32590 |
September | 360.00000 | 23.78567 | 45.31998 | -0.4980 | 10.86823 |
October | 371.00000 | 22.67028 | 38.77297 | 0.05489 | 6.31477 |
November | 360.00000 | 21.44061 | 38.25346 | -0.2903 | 7.68312 |
December | 369.00000 | 21.12465 | 32.11173 | -0.4386 | 9.11276 |
Annual Sum or Average | 4395.00000 | 22.57457 | 37.76010 | -0.3593 | 9.17388 |
Minimum of Months | 336.00000 | 21.11842 | 30.28400 | -0.6779 | 6.31477 |
Maximum of Months | 379.00000 | 23.98899 | 47.41250 | 0.05489 | 15.91045 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 21.11666 | 30.28800 | -0.4789 | 9.90693 |
February | 336.00000 | 21.27034 | 31.63228 | -0.4018 | 8.94414 |
March | 379.00000 | 21.49928 | 32.33061 | -0.3014 | 7.46713 |
April | 360.00000 | 22.35084 | 35.34213 | -0.0595 | 6.56676 |
May | 375.00000 | 23.41535 | 38.42512 | -0.7031 | 16.77328 |
June | 366.00000 | 23.86192 | 39.27926 | -0.5174 | 11.02125 |
July | 369.00000 | 23.98431 | 44.05033 | -0.4101 | 8.87296 |
August | 379.00000 | 23.98758 | 47.41691 | -0.3795 | 8.34743 |
September | 360.00000 | 23.76447 | 45.39030 | -0.5086 | 11.16351 |
October | 371.00000 | 22.56411 | 39.02933 | 0.02507 | 6.38528 |
November | 360.00000 | 21.39365 | 38.38182 | -0.3106 | 7.85312 |
December | 369.00000 | 21.12037 | 32.11742 | -0.4502 | 9.33002 |
Annual Sum or Average | 4395.00000 | 22.53765 | 37.84804 | -0.3750 | 9.39569 |
Minimum of Months | 336.00000 | 21.11666 | 30.28800 | -0.7031 | 6.38528 |
Maximum of Months | 379.00000 | 23.98758 | 47.41691 | 0.02507 | 16.77328 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 21.11378 | 30.29525 | -0.4946 | 10.22903 |
February | 336.00000 | 21.23379 | 31.72692 | -0.4228 | 9.23304 |
March | 379.00000 | 21.40385 | 32.52053 | -0.3342 | 7.80832 |
April | 360.00000 | 22.18569 | 35.68985 | -0.1062 | 6.73066 |
May | 375.00000 | 23.24531 | 38.84345 | -0.7707 | 19.16860 |
June | 366.00000 | 23.81346 | 39.43609 | -0.5446 | 11.73246 |
July | 369.00000 | 23.97063 | 44.11997 | -0.4229 | 9.11638 |
August | 379.00000 | 23.97650 | 47.48671 | -0.3909 | 8.54398 |
September | 360.00000 | 23.68483 | 45.64958 | -0.5445 | 12.18566 |
October | 371.00000 | 22.38350 | 39.46895 | -0.0245 | 6.48274 |
November | 360.00000 | 21.32522 | 38.57369 | -0.3381 | 8.09147 |
December | 369.00000 | 21.11486 | 32.12544 | -0.4654 | 9.62244 |
Annual Sum or Average | 4395.00000 | 22.46437 | 38.03611 | -0.4054 | 9.92483 |
Minimum of Months | 336.00000 | 21.11378 | 30.29525 | -0.7707 | 6.48274 |
Maximum of Months | 379.00000 | 23.97650 | 47.48671 | -0.0245 | 19.16860 |
Report: OccupantComfortDataSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.10994 | 31.82839 | -0.5374 | 11.13775 |
February | 308.00000 | 21.16167 | 33.40590 | -0.4730 | 10.01360 |
March | 348.00000 | 21.20027 | 34.42789 | -0.4025 | 8.65098 |
April | 330.00000 | 21.76458 | 37.97368 | -0.2092 | 7.23940 |
May | 344.00000 | 22.62799 | 41.69054 | -0.9671 | 26.88425 |
June | 336.00000 | 23.50231 | 41.42750 | -0.6533 | 14.94607 |
July | 338.00000 | 23.82329 | 45.46809 | -0.4786 | 10.20549 |
August | 348.00000 | 23.84057 | 48.55724 | -0.4451 | 9.48985 |
September | 330.00000 | 23.28370 | 48.00791 | -0.6761 | 16.42707 |
October | 340.00000 | 21.92022 | 41.99965 | -0.1368 | 6.78263 |
November | 330.00000 | 21.19181 | 40.45181 | -0.3997 | 8.81257 |
December | 338.00000 | 21.10956 | 33.65144 | -0.5069 | 10.45727 |
Annual Sum or Average | 4030.00000 | 22.22074 | 39.94937 | -0.4911 | 11.77724 |
Minimum of Months | 308.00000 | 21.10956 | 31.82839 | -0.9671 | 6.78263 |
Maximum of Months | 348.00000 | 23.84057 | 48.55724 | -0.1368 | 26.88425 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.10972 | 31.71484 | -0.5365 | 11.11526 |
February | 308.00000 | 21.19040 | 33.22070 | -0.4709 | 10.02352 |
March | 348.00000 | 21.26761 | 34.17823 | -0.3982 | 8.64263 |
April | 330.00000 | 21.94126 | 37.45691 | -0.1892 | 7.14767 |
May | 344.00000 | 22.92201 | 40.82349 | -0.9106 | 24.41153 |
June | 336.00000 | 23.67411 | 40.71550 | -0.6274 | 13.89392 |
July | 338.00000 | 23.88592 | 45.29353 | -0.4816 | 10.15974 |
August | 348.00000 | 23.88555 | 48.57434 | -0.4513 | 9.52109 |
September | 330.00000 | 23.50076 | 47.27918 | -0.6367 | 14.84564 |
October | 340.00000 | 22.12521 | 41.34385 | -0.1096 | 6.75978 |
November | 330.00000 | 21.22961 | 40.21436 | -0.3975 | 8.83181 |
December | 338.00000 | 21.11023 | 33.53271 | -0.5071 | 10.45881 |
Annual Sum or Average | 4030.00000 | 22.32998 | 39.57083 | -0.4770 | 11.33822 |
Minimum of Months | 308.00000 | 21.10972 | 31.71484 | -0.9106 | 6.75978 |
Maximum of Months | 348.00000 | 23.88592 | 48.57434 | -0.1096 | 24.41153 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.10942 | 31.71586 | -0.5405 | 11.20614 |
February | 308.00000 | 21.18660 | 33.23014 | -0.4761 | 10.12149 |
March | 348.00000 | 21.25674 | 34.20072 | -0.4051 | 8.75155 |
April | 330.00000 | 21.91695 | 37.50953 | -0.1981 | 7.21577 |
May | 344.00000 | 22.88253 | 40.92267 | -0.9269 | 25.07847 |
June | 336.00000 | 23.65798 | 40.77300 | -0.6364 | 14.16744 |
July | 338.00000 | 23.88064 | 45.33572 | -0.4871 | 10.28284 |
August | 348.00000 | 23.88256 | 48.61389 | -0.4557 | 9.61163 |
September | 330.00000 | 23.48265 | 47.34852 | -0.6453 | 15.12609 |
October | 340.00000 | 22.10087 | 41.40761 | -0.1179 | 6.79875 |
November | 330.00000 | 21.22381 | 40.23249 | -0.4030 | 8.91660 |
December | 338.00000 | 21.10992 | 33.53348 | -0.5113 | 10.54805 |
Annual Sum or Average | 4030.00000 | 22.31728 | 39.61071 | -0.4843 | 11.50691 |
Minimum of Months | 308.00000 | 21.10942 | 31.71586 | -0.9269 | 6.79875 |
Maximum of Months | 348.00000 | 23.88256 | 48.61389 | -0.1179 | 25.07847 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.10985 | 31.71546 | -0.5555 | 11.55491 |
February | 308.00000 | 21.17337 | 33.26239 | -0.4945 | 10.47336 |
March | 348.00000 | 21.22408 | 34.27101 | -0.4274 | 9.11238 |
April | 330.00000 | 21.83037 | 37.69840 | -0.2287 | 7.46351 |
May | 344.00000 | 22.71652 | 41.32723 | -0.9920 | 27.86849 |
June | 336.00000 | 23.57476 | 41.02482 | -0.6737 | 15.43049 |
July | 338.00000 | 23.85759 | 45.45988 | -0.5034 | 10.69151 |
August | 348.00000 | 23.86834 | 48.69890 | -0.4673 | 9.88717 |
September | 330.00000 | 23.38423 | 47.67932 | -0.6859 | 16.57569 |
October | 340.00000 | 21.99884 | 41.66901 | -0.1507 | 6.93101 |
November | 330.00000 | 21.20657 | 40.28597 | -0.4204 | 9.19311 |
December | 338.00000 | 21.10957 | 33.53416 | -0.5260 | 10.87075 |
Annual Sum or Average | 4030.00000 | 22.26402 | 39.76153 | -0.5111 | 12.19577 |
Minimum of Months | 308.00000 | 21.10957 | 31.71546 | -0.9920 | 6.93101 |
Maximum of Months | 348.00000 | 23.86834 | 48.69890 | -0.1507 | 27.86849 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.10988 | 31.55225 | -0.6198 | 13.17612 |
February | 308.00000 | 21.15233 | 33.14565 | -0.5608 | 11.95372 |
March | 348.00000 | 21.18368 | 34.23345 | -0.4922 | 10.35523 |
April | 330.00000 | 21.70796 | 37.85129 | -0.2931 | 8.20733 |
May | 344.00000 | 22.46231 | 41.78092 | -1.1117 | 33.35404 |
June | 336.00000 | 23.40785 | 41.39468 | -0.7493 | 18.34129 |
July | 338.00000 | 23.78664 | 45.57982 | -0.5416 | 11.86957 |
August | 348.00000 | 23.82255 | 48.76262 | -0.4906 | 10.63105 |
September | 330.00000 | 23.16565 | 48.24365 | -0.7777 | 20.28581 |
October | 340.00000 | 21.84272 | 41.90510 | -0.2210 | 7.44348 |
November | 330.00000 | 21.18749 | 40.14410 | -0.4759 | 10.25802 |
December | 338.00000 | 21.11000 | 33.37107 | -0.5866 | 12.31138 |
Annual Sum or Average | 4030.00000 | 22.17079 | 39.87408 | -0.5773 | 14.04296 |
Minimum of Months | 308.00000 | 21.10988 | 31.55225 | -1.1117 | 7.44348 |
Maximum of Months | 348.00000 | 23.82255 | 48.76262 | -0.2210 | 33.35404 |
Report: DXReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 0.635086E+09 | 0.166266E+09 | 34.00 | 0.608582E+09 | 26504486.59 | 0.00 | 0.79 | 27-APR-16:10 | 0.00 | 01-APR-00:10 | 11887.25 | 27-APR-16:10 | 11393.09 | 27-APR-16:10 | 779.13 | 27-APR-17:00 | 2976.44 | 27-APR-16:10 | 0.00 | 01-APR-00:10 |
May | 0.142042E+10 | 0.361301E+09 | 82.00 | 0.125662E+10 | 0.163805E+09 | 0.00 | 0.72 | 06-MAY-13:00 | 0.00 | 01-MAY-00:10 | 11098.91 | 06-MAY-13:00 | 9937.46 | 15-MAY-17:00 | 2262.67 | 06-MAY-12:50 | 2670.78 | 06-MAY-13:00 | 0.00 | 01-MAY-00:10 |
June | 0.264656E+10 | 0.672976E+09 | 157.83 | 0.247773E+10 | 0.168832E+09 | 0.00 | 0.85 | 28-JUN-17:00 | 0.00 | 01-JUN-00:10 | 13072.21 | 28-JUN-17:00 | 12622.08 | 28-JUN-17:00 | 1320.55 | 21-JUN-17:00 | 3194.48 | 28-JUN-17:00 | 0.00 | 01-JUN-00:10 |
July | 0.689074E+10 | 0.170413E+10 | 289.36 | 0.593336E+10 | 0.957379E+09 | 0.00 | 1.00 | 24-JUL-13:40 | 0.00 | 01-JUL-00:10 | 17748.61 | 31-JUL-16:10 | 16186.58 | 24-JUL-15:00 | 3694.81 | 24-JUL-07:03 | 4225.95 | 31-JUL-16:10 | 0.00 | 01-JUL-00:10 |
August | 0.919229E+10 | 0.226026E+10 | 326.94 | 0.794710E+10 | 0.124518E+10 | 0.00 | 1.00 | 08-AUG-13:20 | 0.00 | 01-AUG-00:10 | 19015.02 | 10-AUG-16:40 | 18673.04 | 10-AUG-17:00 | 4778.70 | 10-AUG-07:03 | 4820.57 | 10-AUG-17:00 | 0.00 | 01-AUG-00:10 |
September | 0.273099E+10 | 0.672419E+09 | 134.17 | 0.222449E+10 | 0.506502E+09 | 0.00 | 0.86 | 14-SEP-16:20 | 0.00 | 01-SEP-00:10 | 13541.06 | 14-SEP-16:10 | 11813.87 | 14-SEP-16:30 | 3471.74 | 14-SEP-13:00 | 3170.09 | 14-SEP-16:30 | 0.00 | 01-SEP-00:10 |
October | 0.121139E+09 | 31461251.82 | 13.28 | 0.119549E+09 | 1590320.53 | 0.00 | 0.46 | 04-OCT-15:00 | 0.00 | 01-OCT-00:10 | 6020.28 | 04-OCT-15:00 | 6020.28 | 04-OCT-15:00 | 355.04 | 08-OCT-14:00 | 1521.48 | 04-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 12652571.98 | 3492276.94 | 3.00 | 9457444.00 | 3195127.98 | 0.00 | 0.15 | 04-NOV-14:00 | 0.00 | 01-NOV-00:10 | 1914.24 | 04-NOV-14:00 | 1440.26 | 04-NOV-14:00 | 473.97 | 04-NOV-14:00 | 523.39 | 04-NOV-14:00 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.236499E+11 | 0.587231E+10 | 1040.59 | 0.205769E+11 | 0.307299E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.919229E+10 | 0.226026E+10 | 326.94 | 0.794710E+10 | 0.124518E+10 | 0.00 | 1.00 | 0.00 | 19015.02 | 18673.04 | 4778.70 | 4820.57 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 1197475.39 | 291006.90 | 1.33 | 1122956.01 | 74519.39 | 0.00 | 0.12 | 27-FEB-21:10 | 0.00 | 01-FEB-00:10 | 850.38 | 27-FEB-21:10 | 802.75 | 27-FEB-21:10 | 47.63 | 27-FEB-21:10 | 204.62 | 27-FEB-21:10 | 0.00 | 01-FEB-00:10 |
March | 4867764.27 | 1165196.90 | 3.64 | 4642496.67 | 225267.60 | 0.00 | 0.23 | 10-MAR-21:20 | 0.00 | 01-MAR-00:10 | 1731.63 | 10-MAR-21:20 | 1569.76 | 19-MAR-17:20 | 279.75 | 10-MAR-21:20 | 404.86 | 10-MAR-21:20 | 0.00 | 01-MAR-00:10 |
April | 0.467189E+09 | 0.104422E+09 | 38.76 | 0.457187E+09 | 10002408.55 | 0.00 | 1.00 | 01-APR-18:31 | 0.00 | 01-APR-00:10 | 17080.97 | 27-APR-20:01 | 16740.48 | 01-APR-18:39 | 2157.90 | 27-APR-20:01 | 3433.30 | 01-APR-18:39 | 0.00 | 01-APR-00:10 |
May | 0.955701E+09 | 0.208142E+09 | 90.70 | 0.875554E+09 | 80147453.57 | 0.00 | 1.00 | 04-MAY-20:01 | 0.00 | 01-MAY-00:10 | 17883.62 | 07-MAY-17:02 | 16788.43 | 14-MAY-18:00 | 5697.25 | 06-MAY-18:43 | 3530.49 | 07-MAY-17:02 | 0.00 | 01-MAY-00:10 |
June | 0.170183E+10 | 0.370707E+09 | 154.93 | 0.163583E+10 | 66007289.19 | 0.00 | 1.00 | 02-JUN-20:04 | 0.00 | 01-JUN-00:10 | 17630.75 | 11-JUN-18:00 | 17018.64 | 25-JUN-17:30 | 4061.37 | 28-JUN-20:40 | 3508.07 | 10-JUN-18:07 | 0.00 | 01-JUN-00:10 |
July | 0.408664E+10 | 0.871926E+09 | 260.54 | 0.364561E+10 | 0.441030E+09 | 0.00 | 1.00 | 07-JUL-20:01 | 0.00 | 01-JUL-00:10 | 18333.70 | 15-JUL-18:02 | 16823.86 | 23-JUL-19:17 | 6298.48 | 15-JUL-20:13 | 3641.94 | 15-JUL-18:02 | 0.00 | 01-JUL-00:10 |
August | 0.558544E+10 | 0.118495E+10 | 292.12 | 0.498995E+10 | 0.595488E+09 | 0.00 | 1.00 | 05-AUG-18:01 | 0.00 | 01-AUG-00:10 | 18199.80 | 26-AUG-18:02 | 17231.89 | 08-AUG-22:00 | 6881.56 | 26-AUG-18:55 | 3674.19 | 24-AUG-20:52 | 0.00 | 01-AUG-00:10 |
September | 0.158487E+10 | 0.336678E+09 | 125.28 | 0.135103E+10 | 0.233838E+09 | 0.00 | 1.00 | 02-SEP-18:01 | 0.00 | 01-SEP-00:10 | 18057.17 | 23-SEP-18:02 | 16777.48 | 10-SEP-17:01 | 5587.34 | 23-SEP-18:15 | 3537.31 | 23-SEP-18:02 | 0.00 | 01-SEP-00:10 |
October | 85064931.34 | 19323799.78 | 19.42 | 83630279.44 | 1434651.91 | 0.00 | 1.00 | 04-OCT-20:01 | 0.00 | 01-OCT-00:10 | 16579.60 | 04-OCT-20:01 | 16579.60 | 04-OCT-20:01 | 183.06 | 01-OCT-22:10 | 3238.81 | 04-OCT-20:01 | 0.00 | 01-OCT-00:10 |
November | 20215185.19 | 4751950.54 | 5.67 | 16066183.59 | 4149001.60 | 0.00 | 0.27 | 05-NOV-20:00 | 0.00 | 01-NOV-00:10 | 2057.08 | 04-NOV-14:00 | 1759.49 | 05-NOV-20:00 | 423.69 | 04-NOV-14:00 | 475.74 | 04-NOV-14:00 | 0.00 | 01-NOV-00:10 |
December | 20214.76 | 4975.97 | 0.17 | 20214.76 | -0.0 | 0.00 | 0.00 | 03-DEC-21:00 | 0.00 | 01-DEC-00:03 | 33.69 | 03-DEC-21:00 | 33.69 | 03-DEC-21:00 | 0.00 | 01-DEC-00:03 | 8.29 | 03-DEC-21:00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.144930E+11 | 0.310236E+10 | 992.56 | 0.130606E+11 | 0.143240E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.558544E+10 | 0.118495E+10 | 292.12 | 0.498995E+10 | 0.595488E+09 | 0.00 | 1.00 | 0.00 | 18333.70 | 17231.89 | 6881.56 | 3674.19 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_3:3 COOLING COIL
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 14.38 | 3.56 | 0.33 | 14.38 | -0.0 | 0.00 | 0.00 | 27-FEB-17:00 | 0.00 | 01-FEB-00:10 | 0.02 | 27-FEB-17:00 | 0.02 | 27-FEB-17:00 | 0.00 | 01-FEB-00:10 | 0.00 | 27-FEB-17:00 | 0.00 | 01-FEB-00:10 |
March | 0.67 | 0.17 | 0.17 | 0.67 | -0.0 | 0.00 | 0.00 | 18-MAR-13:30 | 0.00 | 01-MAR-00:10 | 0.00 | 18-MAR-13:30 | 0.00 | 18-MAR-13:30 | 0.00 | 01-MAR-00:10 | 0.00 | 18-MAR-13:30 | 0.00 | 01-MAR-00:10 |
April | 0.368836E+09 | 82861604.95 | 29.08 | 0.361895E+09 | 6941689.46 | 0.00 | 0.79 | 27-APR-16:10 | 0.00 | 01-APR-00:10 | 7062.78 | 27-APR-16:10 | 6977.61 | 27-APR-16:10 | 312.43 | 29-APR-13:50 | 1540.66 | 27-APR-15:00 | 0.00 | 01-APR-00:10 |
May | 0.726193E+09 | 0.160408E+09 | 74.58 | 0.668757E+09 | 57435666.32 | 0.00 | 0.76 | 06-MAY-13:00 | 0.00 | 01-MAY-00:10 | 7007.22 | 06-MAY-13:00 | 5916.30 | 06-MAY-13:00 | 1155.33 | 06-MAY-12:50 | 1451.63 | 06-MAY-13:00 | 0.00 | 01-MAY-00:10 |
June | 0.125463E+10 | 0.277992E+09 | 130.67 | 0.122116E+10 | 33461805.19 | 0.00 | 0.80 | 28-JUN-17:00 | 0.00 | 01-JUN-00:10 | 7143.08 | 28-JUN-17:00 | 7143.08 | 28-JUN-17:00 | 501.74 | 11-JUN-12:00 | 1546.70 | 28-JUN-17:00 | 0.00 | 01-JUN-00:10 |
July | 0.301415E+10 | 0.652785E+09 | 221.08 | 0.272689E+10 | 0.287259E+09 | 0.00 | 0.99 | 31-JUL-16:10 | 0.00 | 01-JUL-00:10 | 9637.61 | 31-JUL-16:10 | 9181.86 | 24-JUL-15:00 | 2272.08 | 31-JUL-06:03 | 2036.26 | 24-JUL-15:00 | 0.00 | 01-JUL-00:10 |
August | 0.418481E+10 | 0.898951E+09 | 252.32 | 0.378113E+10 | 0.403676E+09 | 0.00 | 1.00 | 10-AUG-06:03 | 0.00 | 01-AUG-00:10 | 14723.57 | 10-AUG-06:03 | 10023.73 | 10-AUG-16:20 | 4782.06 | 10-AUG-06:03 | 2854.10 | 10-AUG-06:03 | 0.00 | 01-AUG-00:10 |
September | 0.125978E+10 | 0.270538E+09 | 113.83 | 0.108092E+10 | 0.178855E+09 | 0.00 | 0.84 | 14-SEP-14:00 | 0.00 | 01-SEP-00:10 | 7874.16 | 14-SEP-14:00 | 6816.97 | 14-SEP-16:10 | 1811.05 | 23-SEP-14:00 | 1593.91 | 14-SEP-14:00 | 0.00 | 01-SEP-00:10 |
October | 58395424.45 | 13206720.79 | 11.50 | 58189233.59 | 206190.86 | 0.00 | 0.45 | 04-OCT-15:00 | 0.00 | 01-OCT-00:10 | 3497.80 | 04-OCT-15:00 | 3497.80 | 04-OCT-15:00 | 115.51 | 08-OCT-14:00 | 772.96 | 04-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 13197031.65 | 3123304.38 | 3.33 | 10358929.58 | 2838102.06 | 0.00 | 0.22 | 04-NOV-14:00 | 0.00 | 01-NOV-00:10 | 1693.43 | 04-NOV-14:00 | 1343.92 | 04-NOV-14:00 | 349.51 | 04-NOV-14:00 | 396.35 | 04-NOV-14:00 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.108800E+11 | 0.235987E+10 | 836.90 | 0.990931E+10 | 0.970673E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.418481E+10 | 0.898951E+09 | 252.32 | 0.378113E+10 | 0.403676E+09 | 0.00 | 1.00 | 0.00 | 14723.57 | 10023.73 | 4782.06 | 2854.10 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_4:4 COOLING COIL
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 84.34 | 20.85 | 0.67 | 84.34 | 0.00 | 0.00 | 0.00 | 18-MAR-13:20 | 0.00 | 01-MAR-00:10 | 0.05 | 18-MAR-13:20 | 0.05 | 18-MAR-13:20 | 0.00 | 18-MAR-13:30 | 0.01 | 18-MAR-13:20 | 0.00 | 01-MAR-00:10 |
April | 0.354426E+09 | 79971186.83 | 29.42 | 0.347747E+09 | 6678883.11 | 0.00 | 0.77 | 27-APR-16:10 | 0.00 | 01-APR-00:10 | 6928.55 | 27-APR-16:10 | 6844.45 | 27-APR-16:10 | 301.75 | 29-APR-15:10 | 1517.11 | 27-APR-16:10 | 0.00 | 01-APR-00:10 |
May | 0.700856E+09 | 0.155118E+09 | 72.92 | 0.645589E+09 | 55266770.04 | 0.00 | 0.76 | 06-MAY-13:00 | 0.00 | 01-MAY-00:10 | 6961.41 | 06-MAY-13:00 | 5876.86 | 06-MAY-13:00 | 1147.14 | 06-MAY-12:50 | 1444.74 | 06-MAY-13:00 | 0.00 | 01-MAY-00:10 |
June | 0.123014E+10 | 0.272859E+09 | 128.42 | 0.119744E+10 | 32697134.78 | 0.00 | 0.79 | 28-JUN-17:00 | 0.00 | 01-JUN-00:10 | 7117.29 | 28-JUN-17:00 | 7117.29 | 28-JUN-17:00 | 493.47 | 11-JUN-12:00 | 1543.14 | 28-JUN-17:00 | 0.00 | 01-JUN-00:10 |
July | 0.299589E+10 | 0.649241E+09 | 219.25 | 0.271018E+10 | 0.285716E+09 | 0.00 | 0.99 | 31-JUL-16:10 | 0.00 | 01-JUL-00:10 | 9654.85 | 31-JUL-16:10 | 9191.51 | 24-JUL-15:00 | 2415.90 | 31-JUL-06:03 | 2039.44 | 24-JUL-15:00 | 0.00 | 01-JUL-00:10 |
August | 0.417711E+10 | 0.897654E+09 | 250.57 | 0.377379E+10 | 0.403325E+09 | 0.00 | 1.00 | 10-AUG-06:03 | 0.00 | 01-AUG-00:10 | 15210.73 | 10-AUG-06:03 | 10265.65 | 10-AUG-06:03 | 4945.08 | 10-AUG-06:03 | 2955.28 | 10-AUG-06:03 | 0.00 | 01-AUG-00:10 |
September | 0.124073E+10 | 0.266647E+09 | 110.75 | 0.106449E+10 | 0.176237E+09 | 0.00 | 0.83 | 14-SEP-14:00 | 0.00 | 01-SEP-00:10 | 7859.80 | 14-SEP-14:00 | 6800.51 | 14-SEP-16:10 | 1793.84 | 23-SEP-14:00 | 1592.60 | 14-SEP-14:00 | 0.00 | 01-SEP-00:10 |
October | 54930216.93 | 12443973.95 | 9.83 | 54780891.29 | 149325.64 | 0.00 | 0.44 | 04-OCT-15:00 | 0.00 | 01-OCT-00:10 | 3404.30 | 04-OCT-15:00 | 3404.30 | 04-OCT-15:00 | 100.07 | 08-OCT-14:00 | 754.82 | 04-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 10213488.17 | 2435626.70 | 3.17 | 8029999.99 | 2183488.19 | 0.00 | 0.18 | 04-NOV-14:00 | 0.00 | 01-NOV-00:10 | 1423.71 | 04-NOV-14:00 | 1129.37 | 04-NOV-14:00 | 294.35 | 04-NOV-14:00 | 336.18 | 04-NOV-14:00 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.107643E+11 | 0.233637E+10 | 824.99 | 0.980204E+10 | 0.962253E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.417711E+10 | 0.897654E+09 | 250.57 | 0.377379E+10 | 0.403325E+09 | 0.00 | 1.00 | 0.00 | 15210.73 | 10265.65 | 4945.08 | 2955.28 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_5:5 COOLING COIL
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 379.17 | 93.65 | 0.67 | 379.17 | -0.0 | 0.00 | 0.00 | 18-MAR-13:40 | 0.00 | 01-MAR-00:10 | 0.24 | 18-MAR-13:40 | 0.24 | 18-MAR-13:40 | 0.00 | 18-MAR-13:50 | 0.06 | 18-MAR-13:40 | 0.00 | 01-MAR-00:10 |
April | 0.323894E+09 | 73664023.66 | 24.83 | 0.317916E+09 | 5977318.81 | 0.00 | 0.75 | 27-APR-16:10 | 0.00 | 01-APR-00:10 | 6593.32 | 27-APR-16:10 | 6511.64 | 27-APR-16:10 | 278.94 | 29-APR-15:10 | 1454.95 | 27-APR-16:10 | 0.00 | 01-APR-00:10 |
May | 0.631404E+09 | 0.140362E+09 | 67.83 | 0.581586E+09 | 49817994.00 | 0.00 | 0.74 | 06-MAY-13:00 | 0.00 | 01-MAY-00:10 | 6700.49 | 06-MAY-13:00 | 5649.37 | 06-MAY-13:00 | 1104.60 | 06-MAY-12:50 | 1398.21 | 06-MAY-13:00 | 0.00 | 01-MAY-00:10 |
June | 0.114677E+10 | 0.255112E+09 | 116.08 | 0.111669E+10 | 30079343.24 | 0.00 | 0.78 | 28-JUN-17:00 | 0.00 | 01-JUN-00:10 | 6952.55 | 28-JUN-17:00 | 6952.55 | 28-JUN-17:00 | 461.15 | 11-JUN-12:00 | 1511.77 | 28-JUN-17:00 | 0.00 | 01-JUN-00:10 |
July | 0.286893E+10 | 0.623344E+09 | 212.11 | 0.259591E+10 | 0.273012E+09 | 0.00 | 0.99 | 31-JUL-16:10 | 0.00 | 01-JUL-00:10 | 9505.82 | 31-JUL-16:10 | 9047.55 | 24-JUL-15:00 | 1990.41 | 31-JUL-06:03 | 2010.96 | 24-JUL-15:00 | 0.00 | 01-JUL-00:10 |
August | 0.402620E+10 | 0.867049E+09 | 242.85 | 0.363952E+10 | 0.386681E+09 | 0.00 | 1.00 | 10-AUG-06:03 | 0.00 | 01-AUG-00:10 | 12684.43 | 10-AUG-06:03 | 9883.13 | 10-AUG-16:20 | 4094.44 | 10-AUG-06:03 | 2429.06 | 10-AUG-06:03 | 0.00 | 01-AUG-00:10 |
September | 0.116893E+10 | 0.251761E+09 | 101.00 | 0.100286E+10 | 0.166071E+09 | 0.00 | 0.82 | 14-SEP-14:00 | 0.00 | 01-SEP-00:10 | 7672.03 | 14-SEP-14:00 | 6646.92 | 14-SEP-16:10 | 1739.93 | 14-SEP-13:00 | 1559.48 | 14-SEP-14:00 | 0.00 | 01-SEP-00:10 |
October | 48037988.18 | 10933995.87 | 8.17 | 47966253.32 | 71734.86 | 0.00 | 0.41 | 04-OCT-15:00 | 0.00 | 01-OCT-00:10 | 3161.17 | 04-OCT-15:00 | 3161.17 | 04-OCT-15:00 | 68.75 | 08-OCT-14:00 | 705.80 | 04-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 5570497.97 | 1344213.45 | 2.67 | 4396222.06 | 1174275.90 | 0.00 | 0.13 | 04-NOV-14:00 | 0.00 | 01-NOV-00:10 | 953.76 | 04-NOV-14:00 | 755.64 | 04-NOV-14:00 | 198.12 | 04-NOV-14:00 | 228.62 | 04-NOV-14:00 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.102197E+11 | 0.222357E+10 | 776.21 | 0.930685E+10 | 0.912885E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.402620E+10 | 0.867049E+09 | 242.85 | 0.363952E+10 | 0.386681E+09 | 0.00 | 1.00 | 0.00 | 12684.43 | 9883.13 | 4094.44 | 2429.06 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_6:6 COOLING COIL
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 0.471364E+09 | 0.124447E+09 | 24.50 | 0.447874E+09 | 23490742.01 | 0.00 | 0.76 | 27-APR-15:00 | 0.00 | 01-APR-00:10 | 10947.95 | 27-APR-15:00 | 10166.56 | 27-APR-15:00 | 842.03 | 29-APR-15:00 | 2765.96 | 27-APR-15:00 | 0.00 | 01-APR-00:10 |
May | 0.949634E+09 | 0.243986E+09 | 60.75 | 0.840182E+09 | 0.109453E+09 | 0.00 | 0.72 | 06-MAY-13:30 | 0.00 | 01-MAY-00:10 | 10511.79 | 06-MAY-13:30 | 8459.56 | 06-MAY-13:40 | 2125.03 | 06-MAY-13:10 | 2535.01 | 06-MAY-13:30 | 0.00 | 01-MAY-00:10 |
June | 0.191474E+10 | 0.491773E+09 | 118.58 | 0.179555E+10 | 0.119192E+09 | 0.00 | 0.79 | 28-JUN-17:00 | 0.00 | 01-JUN-00:10 | 11487.73 | 28-JUN-17:00 | 11089.27 | 28-JUN-15:00 | 1157.56 | 21-JUN-17:00 | 2855.96 | 28-JUN-17:00 | 0.00 | 01-JUN-00:10 |
July | 0.501211E+10 | 0.124861E+10 | 218.36 | 0.430710E+10 | 0.705016E+09 | 0.00 | 1.00 | 24-JUL-07:03 | 0.00 | 01-JUL-00:10 | 18490.49 | 24-JUL-07:03 | 15991.94 | 24-JUL-15:00 | 5183.17 | 31-JUL-07:03 | 4180.62 | 24-JUL-15:00 | 0.00 | 01-JUL-00:10 |
August | 0.699056E+10 | 0.172541E+10 | 252.28 | 0.601895E+10 | 0.971616E+09 | 0.00 | 1.00 | 08-AUG-12:50 | 0.00 | 01-AUG-00:10 | 18398.94 | 29-AUG-14:50 | 16695.50 | 10-AUG-16:10 | 6032.01 | 14-AUG-07:03 | 4517.04 | 29-AUG-15:00 | 0.00 | 01-AUG-00:10 |
September | 0.208538E+10 | 0.514265E+09 | 101.25 | 0.168882E+10 | 0.396563E+09 | 0.00 | 0.85 | 14-SEP-14:10 | 0.00 | 01-SEP-00:10 | 12972.84 | 14-SEP-14:10 | 10642.80 | 12-SEP-14:30 | 3501.55 | 14-SEP-13:00 | 3003.31 | 14-SEP-14:10 | 0.00 | 01-SEP-00:10 |
October | 84869806.60 | 22142200.36 | 8.83 | 84241632.95 | 628173.64 | 0.00 | 0.44 | 04-OCT-15:00 | 0.00 | 01-OCT-00:10 | 5534.55 | 04-OCT-15:00 | 5534.55 | 04-OCT-15:00 | 235.27 | 08-OCT-14:10 | 1405.48 | 04-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 11162460.64 | 3075188.42 | 2.50 | 8297801.57 | 2864659.07 | 0.00 | 0.14 | 04-NOV-14:40 | 0.00 | 01-NOV-00:10 | 1789.53 | 04-NOV-14:40 | 1341.32 | 04-NOV-14:40 | 448.21 | 04-NOV-14:40 | 489.72 | 04-NOV-14:40 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.175198E+11 | 0.437371E+10 | 787.06 | 0.151910E+11 | 0.232882E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.699056E+10 | 0.172541E+10 | 252.28 | 0.601895E+10 | 0.971616E+09 | 0.00 | 1.00 | 0.00 | 18490.49 | 16695.50 | 6032.01 | 4517.04 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_7:7 COOLING COIL
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 351.66 | 86.87 | 0.33 | 351.66 | -0.0 | 0.00 | 0.00 | 18-MAR-13:50 | 0.00 | 01-MAR-00:10 | 0.30 | 18-MAR-13:50 | 0.30 | 18-MAR-13:50 | 0.00 | 01-MAR-00:10 | 0.07 | 18-MAR-13:50 | 0.00 | 01-MAR-00:10 |
April | 0.268388E+09 | 61559990.20 | 23.58 | 0.261965E+09 | 6422844.87 | 0.00 | 0.76 | 27-APR-15:00 | 0.00 | 01-APR-00:10 | 6163.14 | 27-APR-15:00 | 5913.62 | 27-APR-15:00 | 276.52 | 27-APR-17:00 | 1356.52 | 27-APR-15:00 | 0.00 | 01-APR-00:10 |
May | 0.496542E+09 | 0.110918E+09 | 54.75 | 0.455558E+09 | 40984189.05 | 0.00 | 0.71 | 06-MAY-13:30 | 0.00 | 01-MAY-00:10 | 5894.92 | 06-MAY-13:30 | 4965.92 | 06-MAY-13:50 | 956.50 | 06-MAY-13:20 | 1238.87 | 06-MAY-13:30 | 0.00 | 01-MAY-00:10 |
June | 0.971672E+09 | 0.217460E+09 | 104.50 | 0.945784E+09 | 25888461.70 | 0.00 | 0.78 | 28-JUN-15:00 | 0.00 | 01-JUN-00:10 | 6347.53 | 28-JUN-17:00 | 6334.62 | 28-JUN-15:00 | 412.43 | 21-JUN-17:00 | 1379.69 | 28-JUN-17:00 | 0.00 | 01-JUN-00:10 |
July | 0.255140E+10 | 0.555416E+09 | 198.61 | 0.229329E+10 | 0.258109E+09 | 0.00 | 1.00 | 24-JUL-14:10 | 0.00 | 01-JUL-00:10 | 9228.74 | 24-JUL-15:00 | 8849.40 | 24-JUL-15:00 | 1842.88 | 31-JUL-07:03 | 2002.42 | 24-JUL-15:00 | 0.00 | 01-JUL-00:10 |
August | 0.369075E+10 | 0.795822E+09 | 228.92 | 0.330952E+10 | 0.381226E+09 | 0.00 | 1.00 | 08-AUG-14:10 | 0.00 | 01-AUG-00:10 | 10036.65 | 29-AUG-14:50 | 9173.51 | 10-AUG-16:10 | 1843.08 | 14-AUG-07:03 | 2183.24 | 29-AUG-15:00 | 0.00 | 01-AUG-00:10 |
September | 0.100758E+10 | 0.217128E+09 | 88.42 | 0.861523E+09 | 0.146053E+09 | 0.00 | 0.83 | 14-SEP-14:10 | 0.00 | 01-SEP-00:10 | 7134.16 | 14-SEP-14:10 | 6125.04 | 12-SEP-14:30 | 1600.02 | 14-SEP-13:00 | 1445.52 | 14-SEP-14:10 | 0.00 | 01-SEP-00:10 |
October | 37714183.97 | 8620686.59 | 7.00 | 37688986.91 | 25197.06 | 0.00 | 0.42 | 04-OCT-15:00 | 0.00 | 01-OCT-00:10 | 2959.27 | 04-OCT-15:00 | 2959.27 | 04-OCT-15:00 | 24.46 | 08-OCT-14:10 | 659.28 | 04-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 3121447.24 | 756867.01 | 2.00 | 2462445.43 | 659001.81 | 0.00 | 0.10 | 04-NOV-14:50 | 0.00 | 01-NOV-00:10 | 659.03 | 04-NOV-14:50 | 521.81 | 04-NOV-14:50 | 137.21 | 04-NOV-14:50 | 159.20 | 04-NOV-14:50 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.902716E+10 | 0.196768E+10 | 708.11 | 0.816779E+10 | 0.859368E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.369075E+10 | 0.795822E+09 | 228.92 | 0.330952E+10 | 0.381226E+09 | 0.00 | 1.00 | 0.00 | 10036.65 | 9173.51 | 1843.08 | 2183.24 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_8:8 COOLING COIL
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 453.08 | 111.91 | 0.33 | 453.08 | 0.00 | 0.00 | 0.00 | 18-MAR-14:00 | 0.00 | 01-MAR-00:10 | 0.50 | 18-MAR-14:00 | 0.50 | 18-MAR-14:00 | 0.00 | 18-MAR-14:00 | 0.12 | 18-MAR-14:00 | 0.00 | 01-MAR-00:10 |
April | 0.261885E+09 | 60162674.45 | 23.58 | 0.255773E+09 | 6112437.01 | 0.00 | 0.75 | 27-APR-15:00 | 0.00 | 01-APR-00:10 | 6073.23 | 27-APR-15:00 | 5832.86 | 27-APR-15:00 | 267.98 | 27-APR-17:00 | 1338.81 | 27-APR-15:00 | 0.00 | 01-APR-00:10 |
May | 0.481211E+09 | 0.107646E+09 | 53.33 | 0.441740E+09 | 39470595.57 | 0.00 | 0.71 | 06-MAY-13:30 | 0.00 | 01-MAY-00:10 | 5796.91 | 06-MAY-13:30 | 4886.19 | 06-MAY-13:50 | 938.44 | 06-MAY-13:20 | 1220.51 | 06-MAY-13:30 | 0.00 | 01-MAY-00:10 |
June | 0.949170E+09 | 0.212638E+09 | 102.33 | 0.924539E+09 | 24630746.83 | 0.00 | 0.78 | 28-JUN-15:00 | 0.00 | 01-JUN-00:10 | 6277.97 | 28-JUN-17:00 | 6268.85 | 28-JUN-15:00 | 402.03 | 21-JUN-17:00 | 1365.81 | 28-JUN-17:00 | 0.00 | 01-JUN-00:10 |
July | 0.250848E+10 | 0.546482E+09 | 196.69 | 0.225678E+10 | 0.251706E+09 | 0.00 | 1.00 | 24-JUL-14:10 | 0.00 | 01-JUL-00:10 | 9155.97 | 24-JUL-15:00 | 8788.71 | 24-JUL-15:00 | 1684.73 | 31-JUL-07:03 | 1985.91 | 24-JUL-15:00 | 0.00 | 01-JUL-00:10 |
August | 0.364072E+10 | 0.785465E+09 | 225.50 | 0.326765E+10 | 0.373071E+09 | 0.00 | 1.00 | 08-AUG-14:10 | 0.00 | 01-AUG-00:10 | 9960.62 | 29-AUG-15:00 | 9119.28 | 10-AUG-16:10 | 1780.53 | 30-AUG-13:00 | 2165.97 | 29-AUG-15:00 | 0.00 | 01-AUG-00:10 |
September | 0.988787E+09 | 0.213238E+09 | 87.17 | 0.846139E+09 | 0.142648E+09 | 0.00 | 0.83 | 14-SEP-14:10 | 0.00 | 01-SEP-00:10 | 7058.11 | 14-SEP-14:10 | 6060.80 | 12-SEP-14:30 | 1576.47 | 14-SEP-13:00 | 1431.41 | 14-SEP-14:10 | 0.00 | 01-SEP-00:10 |
October | 36083685.00 | 8260740.80 | 6.50 | 36070794.39 | 12890.61 | 0.00 | 0.41 | 04-OCT-15:00 | 0.00 | 01-OCT-00:10 | 2888.18 | 04-OCT-15:00 | 2888.18 | 04-OCT-15:00 | 17.42 | 08-OCT-14:10 | 644.66 | 04-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 2720052.95 | 660544.44 | 1.67 | 2148676.85 | 571376.09 | 0.00 | 0.09 | 04-NOV-14:40 | 0.00 | 01-NOV-00:10 | 597.34 | 04-NOV-14:40 | 473.29 | 04-NOV-14:50 | 124.14 | 04-NOV-14:40 | 144.60 | 04-NOV-14:40 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.886907E+10 | 0.193455E+10 | 697.11 | 0.803084E+10 | 0.838224E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.364072E+10 | 0.785465E+09 | 225.50 | 0.326765E+10 | 0.373071E+09 | 0.00 | 1.00 | 0.00 | 9960.62 | 9119.28 | 1780.53 | 2165.97 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_9:9 COOLING COIL
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 254.38 | 62.79 | 0.33 | 254.38 | -0.0 | 0.00 | 0.00 | 18-MAR-14:10 | 0.00 | 01-MAR-00:10 | 0.38 | 18-MAR-14:10 | 0.38 | 18-MAR-14:10 | 0.00 | 01-MAR-00:10 | 0.09 | 18-MAR-14:10 | 0.00 | 01-MAR-00:10 |
April | 0.242404E+09 | 56017810.83 | 23.50 | 0.236895E+09 | 5508537.45 | 0.00 | 0.73 | 27-APR-15:00 | 0.00 | 01-APR-00:10 | 5860.21 | 27-APR-15:00 | 5626.73 | 27-APR-15:00 | 259.32 | 27-APR-17:00 | 1298.97 | 27-APR-15:00 | 0.00 | 01-APR-00:10 |
May | 0.435932E+09 | 98044376.43 | 49.25 | 0.400015E+09 | 35916849.42 | 0.00 | 0.69 | 06-MAY-13:30 | 0.00 | 01-MAY-00:10 | 5557.22 | 06-MAY-13:30 | 4679.78 | 06-MAY-13:50 | 905.84 | 06-MAY-13:20 | 1177.40 | 06-MAY-13:30 | 0.00 | 01-MAY-00:10 |
June | 0.883708E+09 | 0.198663E+09 | 99.25 | 0.861367E+09 | 22340421.56 | 0.00 | 0.77 | 28-JUN-15:00 | 0.00 | 01-JUN-00:10 | 6138.28 | 28-JUN-17:00 | 6122.11 | 28-JUN-15:00 | 389.01 | 21-JUN-17:00 | 1339.67 | 28-JUN-17:00 | 0.00 | 01-JUN-00:10 |
July | 0.240135E+10 | 0.524434E+09 | 184.94 | 0.216143E+10 | 0.239921E+09 | 0.00 | 1.00 | 24-JUL-14:10 | 0.00 | 01-JUL-00:10 | 9048.39 | 24-JUL-15:00 | 8687.73 | 24-JUL-15:00 | 1276.01 | 27-JUL-17:00 | 1961.01 | 24-JUL-15:00 | 0.00 | 01-JUL-00:10 |
August | 0.353314E+10 | 0.763381E+09 | 220.03 | 0.317179E+10 | 0.361347E+09 | 0.00 | 1.00 | 08-AUG-14:10 | 0.00 | 01-AUG-00:10 | 9836.28 | 29-AUG-15:00 | 9049.94 | 10-AUG-16:10 | 1736.41 | 30-AUG-13:00 | 2136.94 | 29-AUG-15:00 | 0.00 | 01-AUG-00:10 |
September | 0.939172E+09 | 0.203109E+09 | 82.25 | 0.803837E+09 | 0.135335E+09 | 0.00 | 0.82 | 14-SEP-14:10 | 0.00 | 01-SEP-00:10 | 6933.95 | 14-SEP-14:10 | 5925.79 | 12-SEP-14:30 | 1545.05 | 14-SEP-13:00 | 1409.63 | 14-SEP-14:10 | 0.00 | 01-SEP-00:10 |
October | 30431061.97 | 7023337.51 | 6.17 | 30429550.58 | 1511.39 | 0.00 | 0.38 | 04-OCT-15:00 | 0.00 | 01-OCT-00:10 | 2614.21 | 04-OCT-15:00 | 2614.21 | 04-OCT-15:00 | 2.51 | 09-OCT-15:30 | 588.97 | 04-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 1490265.61 | 364169.97 | 1.50 | 1178157.37 | 312108.25 | 0.00 | 0.06 | 04-NOV-14:40 | 0.00 | 01-NOV-00:10 | 385.22 | 04-NOV-14:40 | 304.95 | 04-NOV-14:40 | 80.28 | 04-NOV-14:40 | 93.98 | 04-NOV-14:40 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.846763E+10 | 0.185104E+10 | 667.22 | 0.766694E+10 | 0.800682E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.353314E+10 | 0.763381E+09 | 220.03 | 0.317179E+10 | 0.361347E+09 | 0.00 | 1.00 | 0.00 | 9836.28 | 9049.94 | 1736.41 | 2136.94 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_10:10 COOLING COIL
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 4153.82 | 1025.16 | 0.50 | 4153.82 | -0.0 | 0.00 | 0.00 | 18-MAR-15:10 | 0.00 | 01-MAR-00:10 | 6.63 | 18-MAR-15:10 | 6.63 | 18-MAR-15:10 | 0.00 | 01-MAR-00:10 | 1.64 | 18-MAR-15:10 | 0.00 | 01-MAR-00:10 |
April | 0.229623E+09 | 53397942.17 | 21.83 | 0.224676E+09 | 4946805.64 | 0.00 | 0.71 | 27-APR-15:00 | 0.00 | 01-APR-00:10 | 5924.17 | 27-APR-15:00 | 5676.22 | 27-APR-15:00 | 267.30 | 27-APR-17:00 | 1321.83 | 27-APR-15:00 | 0.00 | 01-APR-00:10 |
May | 0.403814E+09 | 91415611.37 | 46.17 | 0.371138E+09 | 32676433.05 | 0.00 | 0.67 | 06-MAY-13:30 | 0.00 | 01-MAY-00:10 | 5614.61 | 06-MAY-13:30 | 4708.02 | 06-MAY-13:40 | 921.99 | 06-MAY-13:20 | 1196.89 | 06-MAY-13:30 | 0.00 | 01-MAY-00:10 |
June | 0.852482E+09 | 0.192447E+09 | 95.33 | 0.830722E+09 | 21760218.14 | 0.00 | 0.75 | 28-JUN-15:00 | 0.00 | 01-JUN-00:10 | 6197.59 | 28-JUN-15:00 | 6197.59 | 28-JUN-15:00 | 387.22 | 21-JUN-17:00 | 1354.95 | 28-JUN-17:00 | 0.00 | 01-JUN-00:10 |
July | 0.238972E+10 | 0.522774E+09 | 178.39 | 0.215409E+10 | 0.235627E+09 | 0.00 | 1.00 | 24-JUL-14:10 | 0.00 | 01-JUL-00:10 | 9498.13 | 24-JUL-15:00 | 9098.12 | 24-JUL-15:00 | 1302.66 | 31-JUL-10:10 | 2060.89 | 24-JUL-15:00 | 0.00 | 01-JUL-00:10 |
August | 0.365374E+10 | 0.788103E+09 | 204.83 | 0.327878E+10 | 0.374962E+09 | 0.00 | 1.00 | 08-AUG-12:50 | 0.00 | 01-AUG-00:10 | 10229.56 | 29-AUG-14:50 | 9425.68 | 10-AUG-16:10 | 1723.71 | 30-AUG-13:00 | 2221.19 | 29-AUG-15:00 | 0.00 | 01-AUG-00:10 |
September | 0.926729E+09 | 0.201414E+09 | 80.25 | 0.791113E+09 | 0.135616E+09 | 0.00 | 0.81 | 14-SEP-14:10 | 0.00 | 01-SEP-00:10 | 7156.04 | 14-SEP-14:10 | 6065.09 | 14-SEP-14:20 | 1640.69 | 14-SEP-13:00 | 1459.30 | 14-SEP-14:10 | 0.00 | 01-SEP-00:10 |
October | 22612186.29 | 5304422.00 | 6.17 | 22610603.10 | 1583.19 | 0.00 | 0.31 | 04-OCT-15:00 | 0.00 | 01-OCT-00:10 | 2177.79 | 04-OCT-15:00 | 2177.79 | 04-OCT-15:00 | 1.32 | 06-OCT-13:20 | 500.42 | 04-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 110611.85 | 27332.29 | 1.17 | 87442.26 | 23169.59 | 0.00 | 0.01 | 04-NOV-14:50 | 0.00 | 01-NOV-00:10 | 51.47 | 04-NOV-14:50 | 40.70 | 04-NOV-14:50 | 10.77 | 04-NOV-14:50 | 12.72 | 04-NOV-14:50 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.847883E+10 | 0.185489E+10 | 634.64 | 0.767322E+10 | 0.805613E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.365374E+10 | 0.788103E+09 | 204.83 | 0.327878E+10 | 0.374962E+09 | 0.00 | 1.00 | 0.00 | 10229.56 | 9425.68 | 1723.71 | 2221.19 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 52.73 | 31.31 | 21.42 | 49.18 | 66.22 | 0.00 | 0.00 | 0.00 |
February | 81.09 | 50.20 | 30.90 | 86.82 | 57.74 | 0.00 | 0.00 | 0.00 |
March | 87.23 | 46.52 | 40.71 | 98.58 | 48.46 | 0.00 | 0.00 | 0.00 |
April | 92.10 | 39.99 | 52.11 | 110.37 | 40.62 | 0.00 | 0.00 | 0.00 |
May | 84.22 | 25.09 | 59.13 | 101.22 | 35.22 | 0.00 | 0.00 | 0.00 |
June | 77.05 | 20.69 | 56.36 | 93.42 | 28.77 | 0.00 | 0.00 | 0.00 |
July | 84.03 | 30.77 | 53.25 | 111.30 | 26.33 | 0.00 | 0.00 | 0.00 |
August | 90.28 | 42.10 | 48.18 | 123.04 | 25.66 | 0.00 | 0.00 | 0.00 |
September | 100.02 | 55.24 | 44.79 | 128.23 | 35.61 | 0.00 | 0.00 | 0.00 |
October | 90.60 | 55.94 | 34.66 | 107.70 | 44.71 | 0.00 | 0.00 | 0.00 |
November | 53.57 | 30.70 | 22.87 | 54.06 | 54.04 | 0.00 | 0.00 | 0.00 |
December | 56.05 | 36.27 | 19.78 | 57.54 | 67.17 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 79.05 | 38.66 | 40.38 | 93.48 | 44.15 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 52.73 | 20.69 | 19.78 | 49.18 | 25.66 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 100.02 | 55.94 | 59.13 | 128.23 | 67.17 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 52.73 | 31.31 | 21.42 | 49.18 | 66.22 | 0.00 | 0.00 | 0.00 |
February | 81.09 | 50.20 | 30.90 | 86.82 | 57.74 | 0.00 | 0.00 | 0.00 |
March | 87.23 | 46.52 | 40.71 | 98.58 | 48.46 | 0.00 | 0.00 | 0.00 |
April | 92.10 | 39.99 | 52.11 | 110.37 | 40.62 | 0.00 | 0.00 | 0.00 |
May | 84.22 | 25.09 | 59.13 | 101.22 | 35.22 | 0.00 | 0.00 | 0.00 |
June | 77.05 | 20.69 | 56.36 | 93.42 | 28.77 | 0.00 | 0.00 | 0.00 |
July | 84.03 | 30.77 | 53.25 | 111.30 | 26.33 | 0.00 | 0.00 | 0.00 |
August | 90.28 | 42.10 | 48.18 | 123.04 | 25.66 | 0.00 | 0.00 | 0.00 |
September | 100.02 | 55.24 | 44.79 | 128.23 | 35.61 | 0.00 | 0.00 | 0.00 |
October | 90.60 | 55.94 | 34.66 | 107.70 | 44.71 | 0.00 | 0.00 | 0.00 |
November | 53.57 | 30.70 | 22.87 | 54.06 | 54.04 | 0.00 | 0.00 | 0.00 |
December | 56.05 | 36.27 | 19.78 | 57.54 | 67.17 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 79.05 | 38.66 | 40.38 | 93.48 | 44.15 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 52.73 | 20.69 | 19.78 | 49.18 | 25.66 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 100.02 | 55.94 | 59.13 | 128.23 | 67.17 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 52.73 | 31.31 | 21.42 | 49.18 | 66.22 | 0.00 | 0.00 | 0.00 |
February | 81.09 | 50.20 | 30.90 | 86.82 | 57.74 | 0.00 | 0.00 | 0.00 |
March | 87.23 | 46.52 | 40.71 | 98.58 | 48.46 | 0.00 | 0.00 | 0.00 |
April | 92.10 | 39.99 | 52.11 | 110.37 | 40.62 | 0.00 | 0.00 | 0.00 |
May | 84.22 | 25.09 | 59.13 | 101.22 | 35.22 | 0.00 | 0.00 | 0.00 |
June | 77.05 | 20.69 | 56.36 | 93.42 | 28.77 | 0.00 | 0.00 | 0.00 |
July | 84.03 | 30.77 | 53.25 | 111.30 | 26.33 | 0.00 | 0.00 | 0.00 |
August | 90.28 | 42.10 | 48.18 | 123.04 | 25.66 | 0.00 | 0.00 | 0.00 |
September | 100.02 | 55.24 | 44.79 | 128.23 | 35.61 | 0.00 | 0.00 | 0.00 |
October | 90.60 | 55.94 | 34.66 | 107.70 | 44.71 | 0.00 | 0.00 | 0.00 |
November | 53.57 | 30.70 | 22.87 | 54.06 | 54.04 | 0.00 | 0.00 | 0.00 |
December | 56.05 | 36.27 | 19.78 | 57.54 | 67.17 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 79.05 | 38.66 | 40.38 | 93.48 | 44.15 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 52.73 | 20.69 | 19.78 | 49.18 | 25.66 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 100.02 | 55.94 | 59.13 | 128.23 | 67.17 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 52.73 | 31.31 | 21.42 | 49.18 | 66.22 | 0.00 | 0.00 | 0.00 |
February | 81.09 | 50.20 | 30.90 | 86.82 | 57.74 | 0.00 | 0.00 | 0.00 |
March | 87.23 | 46.52 | 40.71 | 98.58 | 48.46 | 0.00 | 0.00 | 0.00 |
April | 92.10 | 39.99 | 52.11 | 110.37 | 40.62 | 0.00 | 0.00 | 0.00 |
May | 84.22 | 25.09 | 59.13 | 101.22 | 35.22 | 0.00 | 0.00 | 0.00 |
June | 77.05 | 20.69 | 56.36 | 93.42 | 28.77 | 0.00 | 0.00 | 0.00 |
July | 84.03 | 30.77 | 53.25 | 111.30 | 26.33 | 0.00 | 0.00 | 0.00 |
August | 90.28 | 42.10 | 48.18 | 123.04 | 25.66 | 0.00 | 0.00 | 0.00 |
September | 100.02 | 55.24 | 44.79 | 128.23 | 35.61 | 0.00 | 0.00 | 0.00 |
October | 90.60 | 55.94 | 34.66 | 107.70 | 44.71 | 0.00 | 0.00 | 0.00 |
November | 53.57 | 30.70 | 22.87 | 54.06 | 54.04 | 0.00 | 0.00 | 0.00 |
December | 56.05 | 36.27 | 19.78 | 57.54 | 67.17 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 79.05 | 38.66 | 40.38 | 93.48 | 44.15 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 52.73 | 20.69 | 19.78 | 49.18 | 25.66 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 100.02 | 55.94 | 59.13 | 128.23 | 67.17 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 63.39 | 37.64 | 25.75 | 59.41 | 78.58 | 0.00 | 0.00 | 0.00 |
February | 97.49 | 60.35 | 37.14 | 104.70 | 68.61 | 0.00 | 0.00 | 0.00 |
March | 104.87 | 55.93 | 48.94 | 118.79 | 57.60 | 0.00 | 0.00 | 0.00 |
April | 110.72 | 48.07 | 62.65 | 132.98 | 48.29 | 0.00 | 0.00 | 0.00 |
May | 101.24 | 30.16 | 71.08 | 121.96 | 41.91 | 0.00 | 0.00 | 0.00 |
June | 92.63 | 24.87 | 67.76 | 112.53 | 34.26 | 0.00 | 0.00 | 0.00 |
July | 101.01 | 37.00 | 64.02 | 133.91 | 31.39 | 0.00 | 0.00 | 0.00 |
August | 108.53 | 50.61 | 57.92 | 147.96 | 30.62 | 0.00 | 0.00 | 0.00 |
September | 120.24 | 66.40 | 53.84 | 154.20 | 42.49 | 0.00 | 0.00 | 0.00 |
October | 108.92 | 67.25 | 41.67 | 129.71 | 53.22 | 0.00 | 0.00 | 0.00 |
November | 64.40 | 36.90 | 27.49 | 65.20 | 64.20 | 0.00 | 0.00 | 0.00 |
December | 67.38 | 43.60 | 23.77 | 69.37 | 79.80 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 95.03 | 46.48 | 48.55 | 112.58 | 52.51 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 63.39 | 24.87 | 23.77 | 59.41 | 30.62 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 120.24 | 67.25 | 71.08 | 154.20 | 79.80 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 63.39 | 37.64 | 25.75 | 59.41 | 78.58 | 0.00 | 0.00 | 0.00 |
February | 97.49 | 60.35 | 37.14 | 104.70 | 68.61 | 0.00 | 0.00 | 0.00 |
March | 104.87 | 55.93 | 48.94 | 118.79 | 57.60 | 0.00 | 0.00 | 0.00 |
April | 110.72 | 48.07 | 62.65 | 132.98 | 48.29 | 0.00 | 0.00 | 0.00 |
May | 101.24 | 30.16 | 71.08 | 121.96 | 41.91 | 0.00 | 0.00 | 0.00 |
June | 92.63 | 24.87 | 67.76 | 112.53 | 34.26 | 0.00 | 0.00 | 0.00 |
July | 101.01 | 37.00 | 64.02 | 133.91 | 31.39 | 0.00 | 0.00 | 0.00 |
August | 108.53 | 50.61 | 57.92 | 147.96 | 30.62 | 0.00 | 0.00 | 0.00 |
September | 120.24 | 66.40 | 53.84 | 154.20 | 42.49 | 0.00 | 0.00 | 0.00 |
October | 108.92 | 67.25 | 41.67 | 129.71 | 53.22 | 0.00 | 0.00 | 0.00 |
November | 64.40 | 36.90 | 27.49 | 65.20 | 64.20 | 0.00 | 0.00 | 0.00 |
December | 67.38 | 43.60 | 23.77 | 69.37 | 79.80 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 95.03 | 46.48 | 48.55 | 112.58 | 52.51 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 63.39 | 24.87 | 23.77 | 59.41 | 30.62 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 120.24 | 67.25 | 71.08 | 154.20 | 79.80 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 52.73 | 31.31 | 21.42 | 48.38 | 70.35 | 0.00 | 0.00 | 0.00 |
February | 81.09 | 50.20 | 30.90 | 85.58 | 61.79 | 0.00 | 0.00 | 0.00 |
March | 87.23 | 46.52 | 40.71 | 96.96 | 53.31 | 0.00 | 0.00 | 0.00 |
April | 92.10 | 39.99 | 52.11 | 108.12 | 44.93 | 0.00 | 0.00 | 0.00 |
May | 84.22 | 25.09 | 59.13 | 98.92 | 38.43 | 0.00 | 0.00 | 0.00 |
June | 77.05 | 20.69 | 56.36 | 92.16 | 30.28 | 0.00 | 0.00 | 0.00 |
July | 84.03 | 30.77 | 53.25 | 110.75 | 26.99 | 0.00 | 0.00 | 0.00 |
August | 90.28 | 42.10 | 48.18 | 122.60 | 26.21 | 0.00 | 0.00 | 0.00 |
September | 100.02 | 55.24 | 44.79 | 127.15 | 37.20 | 0.00 | 0.00 | 0.00 |
October | 90.60 | 55.94 | 34.66 | 105.90 | 49.09 | 0.00 | 0.00 | 0.00 |
November | 53.57 | 30.70 | 22.87 | 53.04 | 58.19 | 0.00 | 0.00 | 0.00 |
December | 56.05 | 36.27 | 19.78 | 56.81 | 71.32 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 79.05 | 38.66 | 40.38 | 92.22 | 47.27 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 52.73 | 20.69 | 19.78 | 48.38 | 26.21 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 100.02 | 55.94 | 59.13 | 127.15 | 71.32 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 52.73 | 31.31 | 21.42 | 48.38 | 70.35 | 0.00 | 0.00 | 0.00 |
February | 81.09 | 50.20 | 30.90 | 85.58 | 61.79 | 0.00 | 0.00 | 0.00 |
March | 87.23 | 46.52 | 40.71 | 96.96 | 53.31 | 0.00 | 0.00 | 0.00 |
April | 92.10 | 39.99 | 52.11 | 108.12 | 44.93 | 0.00 | 0.00 | 0.00 |
May | 84.22 | 25.09 | 59.13 | 98.92 | 38.43 | 0.00 | 0.00 | 0.00 |
June | 77.05 | 20.69 | 56.36 | 92.16 | 30.28 | 0.00 | 0.00 | 0.00 |
July | 84.03 | 30.77 | 53.25 | 110.75 | 26.99 | 0.00 | 0.00 | 0.00 |
August | 90.28 | 42.10 | 48.18 | 122.60 | 26.21 | 0.00 | 0.00 | 0.00 |
September | 100.02 | 55.24 | 44.79 | 127.15 | 37.20 | 0.00 | 0.00 | 0.00 |
October | 90.60 | 55.94 | 34.66 | 105.90 | 49.09 | 0.00 | 0.00 | 0.00 |
November | 53.57 | 30.70 | 22.87 | 53.04 | 58.19 | 0.00 | 0.00 | 0.00 |
December | 56.05 | 36.27 | 19.78 | 56.81 | 71.32 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 79.05 | 38.66 | 40.38 | 92.22 | 47.27 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 52.73 | 20.69 | 19.78 | 48.38 | 26.21 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 100.02 | 55.94 | 59.13 | 127.15 | 71.32 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 63.39 | 37.64 | 25.75 | 58.45 | 83.45 | 0.00 | 0.00 | 0.00 |
February | 97.49 | 60.35 | 37.14 | 103.22 | 73.38 | 0.00 | 0.00 | 0.00 |
March | 104.87 | 55.93 | 48.94 | 116.87 | 63.30 | 0.00 | 0.00 | 0.00 |
April | 110.72 | 48.07 | 62.65 | 130.33 | 53.35 | 0.00 | 0.00 | 0.00 |
May | 101.24 | 30.16 | 71.08 | 119.25 | 45.68 | 0.00 | 0.00 | 0.00 |
June | 92.63 | 24.87 | 67.76 | 111.05 | 36.03 | 0.00 | 0.00 | 0.00 |
July | 101.01 | 37.00 | 64.02 | 133.28 | 32.16 | 0.00 | 0.00 | 0.00 |
August | 108.53 | 50.61 | 57.92 | 147.45 | 31.27 | 0.00 | 0.00 | 0.00 |
September | 120.24 | 66.40 | 53.84 | 152.93 | 44.38 | 0.00 | 0.00 | 0.00 |
October | 108.92 | 67.25 | 41.67 | 127.59 | 58.38 | 0.00 | 0.00 | 0.00 |
November | 64.40 | 36.90 | 27.49 | 64.00 | 69.07 | 0.00 | 0.00 | 0.00 |
December | 67.38 | 43.60 | 23.77 | 68.51 | 84.69 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 95.03 | 46.48 | 48.55 | 111.10 | 56.18 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 63.39 | 24.87 | 23.77 | 58.45 | 31.27 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 120.24 | 67.25 | 71.08 | 152.93 | 84.69 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 52.73 | 31.31 | 21.42 | 48.55 | 68.34 | 0.00 | 0.00 | 0.00 |
February | 81.09 | 50.20 | 30.90 | 85.86 | 60.02 | 0.00 | 0.00 | 0.00 |
March | 87.23 | 46.52 | 40.71 | 97.27 | 51.68 | 0.00 | 0.00 | 0.00 |
April | 92.10 | 39.99 | 52.11 | 108.43 | 44.00 | 0.00 | 0.00 | 0.00 |
May | 84.22 | 25.09 | 59.13 | 98.94 | 38.64 | 0.00 | 0.00 | 0.00 |
June | 77.05 | 20.69 | 56.36 | 92.02 | 31.09 | 0.00 | 0.00 | 0.00 |
July | 84.03 | 30.77 | 53.25 | 110.52 | 28.17 | 0.00 | 0.00 | 0.00 |
August | 90.28 | 42.10 | 48.18 | 122.40 | 27.54 | 0.00 | 0.00 | 0.00 |
September | 100.02 | 55.24 | 44.79 | 127.09 | 37.97 | 0.00 | 0.00 | 0.00 |
October | 90.60 | 55.94 | 34.66 | 106.14 | 48.32 | 0.00 | 0.00 | 0.00 |
November | 53.57 | 30.70 | 22.87 | 53.30 | 56.50 | 0.00 | 0.00 | 0.00 |
December | 56.05 | 36.27 | 19.78 | 57.00 | 69.44 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 79.05 | 38.66 | 40.38 | 92.31 | 46.75 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 52.73 | 20.69 | 19.78 | 48.55 | 27.54 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 100.02 | 55.94 | 59.13 | 127.09 | 69.44 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 52.73 | 31.31 | 21.42 | 48.55 | 68.34 | 0.00 | 0.00 | 0.00 |
February | 81.09 | 50.20 | 30.90 | 85.86 | 60.02 | 0.00 | 0.00 | 0.00 |
March | 87.23 | 46.52 | 40.71 | 97.27 | 51.68 | 0.00 | 0.00 | 0.00 |
April | 92.10 | 39.99 | 52.11 | 108.43 | 44.00 | 0.00 | 0.00 | 0.00 |
May | 84.22 | 25.09 | 59.13 | 98.94 | 38.64 | 0.00 | 0.00 | 0.00 |
June | 77.05 | 20.69 | 56.36 | 92.02 | 31.09 | 0.00 | 0.00 | 0.00 |
July | 84.03 | 30.77 | 53.25 | 110.52 | 28.17 | 0.00 | 0.00 | 0.00 |
August | 90.28 | 42.10 | 48.18 | 122.40 | 27.54 | 0.00 | 0.00 | 0.00 |
September | 100.02 | 55.24 | 44.79 | 127.09 | 37.97 | 0.00 | 0.00 | 0.00 |
October | 90.60 | 55.94 | 34.66 | 106.14 | 48.32 | 0.00 | 0.00 | 0.00 |
November | 53.57 | 30.70 | 22.87 | 53.30 | 56.50 | 0.00 | 0.00 | 0.00 |
December | 56.05 | 36.27 | 19.78 | 57.00 | 69.44 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 79.05 | 38.66 | 40.38 | 92.31 | 46.75 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 52.73 | 20.69 | 19.78 | 48.55 | 27.54 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 100.02 | 55.94 | 59.13 | 127.09 | 69.44 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 63.05 | 37.44 | 25.61 | 58.33 | 80.64 | 0.00 | 0.00 | 0.00 |
February | 96.96 | 60.02 | 36.94 | 103.00 | 70.90 | 0.00 | 0.00 | 0.00 |
March | 104.30 | 55.62 | 48.68 | 116.60 | 61.05 | 0.00 | 0.00 | 0.00 |
April | 110.12 | 47.81 | 62.30 | 129.99 | 51.98 | 0.00 | 0.00 | 0.00 |
May | 100.69 | 30.00 | 70.69 | 118.61 | 45.67 | 0.00 | 0.00 | 0.00 |
June | 92.12 | 24.73 | 67.39 | 110.28 | 36.77 | 0.00 | 0.00 | 0.00 |
July | 100.46 | 36.79 | 63.67 | 132.29 | 33.37 | 0.00 | 0.00 | 0.00 |
August | 107.93 | 50.33 | 57.60 | 146.40 | 32.65 | 0.00 | 0.00 | 0.00 |
September | 119.58 | 66.04 | 53.55 | 152.03 | 45.03 | 0.00 | 0.00 | 0.00 |
October | 108.32 | 66.88 | 41.44 | 127.18 | 57.16 | 0.00 | 0.00 | 0.00 |
November | 64.04 | 36.70 | 27.34 | 63.96 | 66.71 | 0.00 | 0.00 | 0.00 |
December | 67.01 | 43.36 | 23.64 | 68.36 | 82.03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 94.51 | 46.23 | 48.28 | 110.61 | 55.26 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 63.05 | 24.73 | 23.64 | 58.33 | 32.65 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 119.58 | 66.88 | 70.69 | 152.03 | 82.03 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 52.73 | 31.31 | 21.42 | 48.66 | 67.41 | 0.00 | 0.00 | 0.00 |
February | 81.09 | 50.20 | 30.90 | 86.05 | 59.18 | 0.00 | 0.00 | 0.00 |
March | 87.23 | 46.52 | 40.71 | 97.51 | 50.77 | 0.00 | 0.00 | 0.00 |
April | 92.10 | 39.99 | 52.11 | 108.77 | 43.17 | 0.00 | 0.00 | 0.00 |
May | 84.22 | 25.09 | 59.13 | 99.18 | 38.15 | 0.00 | 0.00 | 0.00 |
June | 77.05 | 20.69 | 56.36 | 92.10 | 30.89 | 0.00 | 0.00 | 0.00 |
July | 84.03 | 30.77 | 53.25 | 110.55 | 28.10 | 0.00 | 0.00 | 0.00 |
August | 90.28 | 42.10 | 48.18 | 122.41 | 27.51 | 0.00 | 0.00 | 0.00 |
September | 100.02 | 55.24 | 44.79 | 127.18 | 37.72 | 0.00 | 0.00 | 0.00 |
October | 90.60 | 55.94 | 34.66 | 106.41 | 47.45 | 0.00 | 0.00 | 0.00 |
November | 53.57 | 30.70 | 22.87 | 53.49 | 55.58 | 0.00 | 0.00 | 0.00 |
December | 56.05 | 36.27 | 19.78 | 57.11 | 68.59 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 79.05 | 38.66 | 40.38 | 92.47 | 46.15 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 52.73 | 20.69 | 19.78 | 48.66 | 27.51 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 100.02 | 55.94 | 59.13 | 127.18 | 68.59 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 52.73 | 31.31 | 21.42 | 48.66 | 67.41 | 0.00 | 0.00 | 0.00 |
February | 81.09 | 50.20 | 30.90 | 86.05 | 59.18 | 0.00 | 0.00 | 0.00 |
March | 87.23 | 46.52 | 40.71 | 97.51 | 50.77 | 0.00 | 0.00 | 0.00 |
April | 92.10 | 39.99 | 52.11 | 108.77 | 43.17 | 0.00 | 0.00 | 0.00 |
May | 84.22 | 25.09 | 59.13 | 99.18 | 38.15 | 0.00 | 0.00 | 0.00 |
June | 77.05 | 20.69 | 56.36 | 92.10 | 30.89 | 0.00 | 0.00 | 0.00 |
July | 84.03 | 30.77 | 53.25 | 110.55 | 28.10 | 0.00 | 0.00 | 0.00 |
August | 90.28 | 42.10 | 48.18 | 122.41 | 27.51 | 0.00 | 0.00 | 0.00 |
September | 100.02 | 55.24 | 44.79 | 127.18 | 37.72 | 0.00 | 0.00 | 0.00 |
October | 90.60 | 55.94 | 34.66 | 106.41 | 47.45 | 0.00 | 0.00 | 0.00 |
November | 53.57 | 30.70 | 22.87 | 53.49 | 55.58 | 0.00 | 0.00 | 0.00 |
December | 56.05 | 36.27 | 19.78 | 57.11 | 68.59 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 79.05 | 38.66 | 40.38 | 92.47 | 46.15 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 52.73 | 20.69 | 19.78 | 48.66 | 27.51 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 100.02 | 55.94 | 59.13 | 127.18 | 68.59 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 63.05 | 37.44 | 25.61 | 58.47 | 79.53 | 0.00 | 0.00 | 0.00 |
February | 96.96 | 60.02 | 36.94 | 103.24 | 69.91 | 0.00 | 0.00 | 0.00 |
March | 104.30 | 55.62 | 48.68 | 116.90 | 59.98 | 0.00 | 0.00 | 0.00 |
April | 110.12 | 47.81 | 62.30 | 130.39 | 51.00 | 0.00 | 0.00 | 0.00 |
May | 100.69 | 30.00 | 70.69 | 118.91 | 45.10 | 0.00 | 0.00 | 0.00 |
June | 92.12 | 24.73 | 67.39 | 110.38 | 36.54 | 0.00 | 0.00 | 0.00 |
July | 100.46 | 36.79 | 63.67 | 132.32 | 33.28 | 0.00 | 0.00 | 0.00 |
August | 107.93 | 50.33 | 57.60 | 146.42 | 32.62 | 0.00 | 0.00 | 0.00 |
September | 119.58 | 66.04 | 53.55 | 152.14 | 44.74 | 0.00 | 0.00 | 0.00 |
October | 108.32 | 66.88 | 41.44 | 127.50 | 56.13 | 0.00 | 0.00 | 0.00 |
November | 64.04 | 36.70 | 27.34 | 64.18 | 65.63 | 0.00 | 0.00 | 0.00 |
December | 67.01 | 43.36 | 23.64 | 68.49 | 81.01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 94.51 | 46.23 | 48.28 | 110.80 | 54.55 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 63.05 | 24.73 | 23.64 | 58.47 | 32.62 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 119.58 | 66.88 | 70.69 | 152.14 | 81.01 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 52.73 | 31.31 | 21.42 | 48.81 | 66.59 | 0.00 | 0.00 | 0.00 |
February | 81.09 | 50.20 | 30.90 | 86.30 | 58.42 | 0.00 | 0.00 | 0.00 |
March | 87.23 | 46.52 | 40.71 | 97.84 | 49.83 | 0.00 | 0.00 | 0.00 |
April | 92.10 | 39.99 | 52.11 | 109.30 | 42.16 | 0.00 | 0.00 | 0.00 |
May | 84.22 | 25.09 | 59.13 | 99.79 | 37.23 | 0.00 | 0.00 | 0.00 |
June | 77.05 | 20.69 | 56.36 | 92.40 | 30.38 | 0.00 | 0.00 | 0.00 |
July | 84.03 | 30.77 | 53.25 | 110.71 | 27.76 | 0.00 | 0.00 | 0.00 |
August | 90.28 | 42.10 | 48.18 | 122.54 | 27.18 | 0.00 | 0.00 | 0.00 |
September | 100.02 | 55.24 | 44.79 | 127.47 | 37.12 | 0.00 | 0.00 | 0.00 |
October | 90.60 | 55.94 | 34.66 | 106.86 | 46.30 | 0.00 | 0.00 | 0.00 |
November | 53.57 | 30.70 | 22.87 | 53.73 | 54.69 | 0.00 | 0.00 | 0.00 |
December | 56.05 | 36.27 | 19.78 | 57.24 | 67.81 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 79.05 | 38.66 | 40.38 | 92.77 | 45.40 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 52.73 | 20.69 | 19.78 | 48.81 | 27.18 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 100.02 | 55.94 | 59.13 | 127.47 | 67.81 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 52.73 | 31.31 | 21.42 | 48.81 | 66.59 | 0.00 | 0.00 | 0.00 |
February | 81.09 | 50.20 | 30.90 | 86.30 | 58.42 | 0.00 | 0.00 | 0.00 |
March | 87.23 | 46.52 | 40.71 | 97.84 | 49.83 | 0.00 | 0.00 | 0.00 |
April | 92.10 | 39.99 | 52.11 | 109.30 | 42.16 | 0.00 | 0.00 | 0.00 |
May | 84.22 | 25.09 | 59.13 | 99.79 | 37.23 | 0.00 | 0.00 | 0.00 |
June | 77.05 | 20.69 | 56.36 | 92.40 | 30.38 | 0.00 | 0.00 | 0.00 |
July | 84.03 | 30.77 | 53.25 | 110.71 | 27.76 | 0.00 | 0.00 | 0.00 |
August | 90.28 | 42.10 | 48.18 | 122.54 | 27.18 | 0.00 | 0.00 | 0.00 |
September | 100.02 | 55.24 | 44.79 | 127.47 | 37.12 | 0.00 | 0.00 | 0.00 |
October | 90.60 | 55.94 | 34.66 | 106.86 | 46.30 | 0.00 | 0.00 | 0.00 |
November | 53.57 | 30.70 | 22.87 | 53.73 | 54.69 | 0.00 | 0.00 | 0.00 |
December | 56.05 | 36.27 | 19.78 | 57.24 | 67.81 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 79.05 | 38.66 | 40.38 | 92.77 | 45.40 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 52.73 | 20.69 | 19.78 | 48.81 | 27.18 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 100.02 | 55.94 | 59.13 | 127.47 | 67.81 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 63.05 | 37.44 | 25.61 | 58.65 | 78.57 | 0.00 | 0.00 | 0.00 |
February | 96.96 | 60.02 | 36.94 | 103.53 | 69.01 | 0.00 | 0.00 | 0.00 |
March | 104.30 | 55.62 | 48.68 | 117.29 | 58.87 | 0.00 | 0.00 | 0.00 |
April | 110.12 | 47.81 | 62.30 | 131.03 | 49.81 | 0.00 | 0.00 | 0.00 |
May | 100.69 | 30.00 | 70.69 | 119.63 | 44.02 | 0.00 | 0.00 | 0.00 |
June | 92.12 | 24.73 | 67.39 | 110.74 | 35.94 | 0.00 | 0.00 | 0.00 |
July | 100.46 | 36.79 | 63.67 | 132.51 | 32.88 | 0.00 | 0.00 | 0.00 |
August | 107.93 | 50.33 | 57.60 | 146.58 | 32.24 | 0.00 | 0.00 | 0.00 |
September | 119.58 | 66.04 | 53.55 | 152.48 | 44.03 | 0.00 | 0.00 | 0.00 |
October | 108.32 | 66.88 | 41.44 | 128.04 | 54.78 | 0.00 | 0.00 | 0.00 |
November | 64.04 | 36.70 | 27.34 | 64.47 | 64.58 | 0.00 | 0.00 | 0.00 |
December | 67.01 | 43.36 | 23.64 | 68.65 | 80.09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 94.51 | 46.23 | 48.28 | 111.16 | 53.66 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 63.05 | 24.73 | 23.64 | 58.65 | 32.24 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 119.58 | 66.88 | 70.69 | 152.48 | 80.09 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 52.73 | 31.31 | 21.42 | 49.29 | 64.28 | 0.00 | 0.00 | 0.00 |
February | 81.09 | 50.20 | 30.90 | 87.02 | 56.41 | 0.00 | 0.00 | 0.00 |
March | 87.23 | 46.52 | 40.71 | 98.63 | 47.77 | 0.00 | 0.00 | 0.00 |
April | 92.10 | 39.99 | 52.11 | 110.50 | 39.99 | 0.00 | 0.00 | 0.00 |
May | 84.22 | 25.09 | 59.13 | 101.31 | 35.01 | 0.00 | 0.00 | 0.00 |
June | 77.05 | 20.69 | 56.36 | 93.27 | 28.92 | 0.00 | 0.00 | 0.00 |
July | 84.03 | 30.77 | 53.25 | 111.07 | 26.72 | 0.00 | 0.00 | 0.00 |
August | 90.28 | 42.10 | 48.18 | 122.81 | 26.14 | 0.00 | 0.00 | 0.00 |
September | 100.02 | 55.24 | 44.79 | 128.24 | 35.52 | 0.00 | 0.00 | 0.00 |
October | 90.60 | 55.94 | 34.66 | 107.90 | 43.94 | 0.00 | 0.00 | 0.00 |
November | 53.57 | 30.70 | 22.87 | 54.30 | 52.57 | 0.00 | 0.00 | 0.00 |
December | 56.05 | 36.27 | 19.78 | 57.66 | 65.63 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 79.05 | 38.66 | 40.38 | 93.52 | 43.52 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 52.73 | 20.69 | 19.78 | 49.29 | 26.14 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 100.02 | 55.94 | 59.13 | 128.24 | 65.63 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 52.73 | 31.31 | 21.42 | 49.29 | 64.28 | 0.00 | 0.00 | 0.00 |
February | 81.09 | 50.20 | 30.90 | 87.02 | 56.41 | 0.00 | 0.00 | 0.00 |
March | 87.23 | 46.52 | 40.71 | 98.63 | 47.77 | 0.00 | 0.00 | 0.00 |
April | 92.10 | 39.99 | 52.11 | 110.50 | 39.99 | 0.00 | 0.00 | 0.00 |
May | 84.22 | 25.09 | 59.13 | 101.31 | 35.01 | 0.00 | 0.00 | 0.00 |
June | 77.05 | 20.69 | 56.36 | 93.27 | 28.92 | 0.00 | 0.00 | 0.00 |
July | 84.03 | 30.77 | 53.25 | 111.07 | 26.72 | 0.00 | 0.00 | 0.00 |
August | 90.28 | 42.10 | 48.18 | 122.81 | 26.14 | 0.00 | 0.00 | 0.00 |
September | 100.02 | 55.24 | 44.79 | 128.24 | 35.52 | 0.00 | 0.00 | 0.00 |
October | 90.60 | 55.94 | 34.66 | 107.90 | 43.94 | 0.00 | 0.00 | 0.00 |
November | 53.57 | 30.70 | 22.87 | 54.30 | 52.57 | 0.00 | 0.00 | 0.00 |
December | 56.05 | 36.27 | 19.78 | 57.66 | 65.63 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 79.05 | 38.66 | 40.38 | 93.52 | 43.52 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 52.73 | 20.69 | 19.78 | 49.29 | 26.14 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 100.02 | 55.94 | 59.13 | 128.24 | 65.63 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 52.73 | 31.31 | 21.42 | 49.29 | 64.28 | 0.00 | 0.00 | 0.00 |
February | 81.09 | 50.20 | 30.90 | 87.02 | 56.41 | 0.00 | 0.00 | 0.00 |
March | 87.23 | 46.52 | 40.71 | 98.63 | 47.77 | 0.00 | 0.00 | 0.00 |
April | 92.10 | 39.99 | 52.11 | 110.50 | 39.99 | 0.00 | 0.00 | 0.00 |
May | 84.22 | 25.09 | 59.13 | 101.31 | 35.01 | 0.00 | 0.00 | 0.00 |
June | 77.05 | 20.69 | 56.36 | 93.27 | 28.92 | 0.00 | 0.00 | 0.00 |
July | 84.03 | 30.77 | 53.25 | 111.07 | 26.72 | 0.00 | 0.00 | 0.00 |
August | 90.28 | 42.10 | 48.18 | 122.81 | 26.14 | 0.00 | 0.00 | 0.00 |
September | 100.02 | 55.24 | 44.79 | 128.24 | 35.52 | 0.00 | 0.00 | 0.00 |
October | 90.60 | 55.94 | 34.66 | 107.90 | 43.94 | 0.00 | 0.00 | 0.00 |
November | 53.57 | 30.70 | 22.87 | 54.30 | 52.57 | 0.00 | 0.00 | 0.00 |
December | 56.05 | 36.27 | 19.78 | 57.66 | 65.63 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 79.05 | 38.66 | 40.38 | 93.52 | 43.52 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 52.73 | 20.69 | 19.78 | 49.29 | 26.14 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 100.02 | 55.94 | 59.13 | 128.24 | 65.63 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 52.73 | 31.31 | 21.42 | 49.29 | 64.28 | 0.00 | 0.00 | 0.00 |
February | 81.09 | 50.20 | 30.90 | 87.02 | 56.41 | 0.00 | 0.00 | 0.00 |
March | 87.23 | 46.52 | 40.71 | 98.63 | 47.77 | 0.00 | 0.00 | 0.00 |
April | 92.10 | 39.99 | 52.11 | 110.50 | 39.99 | 0.00 | 0.00 | 0.00 |
May | 84.22 | 25.09 | 59.13 | 101.31 | 35.01 | 0.00 | 0.00 | 0.00 |
June | 77.05 | 20.69 | 56.36 | 93.27 | 28.92 | 0.00 | 0.00 | 0.00 |
July | 84.03 | 30.77 | 53.25 | 111.07 | 26.72 | 0.00 | 0.00 | 0.00 |
August | 90.28 | 42.10 | 48.18 | 122.81 | 26.14 | 0.00 | 0.00 | 0.00 |
September | 100.02 | 55.24 | 44.79 | 128.24 | 35.52 | 0.00 | 0.00 | 0.00 |
October | 90.60 | 55.94 | 34.66 | 107.90 | 43.94 | 0.00 | 0.00 | 0.00 |
November | 53.57 | 30.70 | 22.87 | 54.30 | 52.57 | 0.00 | 0.00 | 0.00 |
December | 56.05 | 36.27 | 19.78 | 57.66 | 65.63 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 79.05 | 38.66 | 40.38 | 93.52 | 43.52 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 52.73 | 20.69 | 19.78 | 49.29 | 26.14 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 100.02 | 55.94 | 59.13 | 128.24 | 65.63 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 63.05 | 37.44 | 25.61 | 59.21 | 75.87 | 0.00 | 0.00 | 0.00 |
February | 96.96 | 60.02 | 36.94 | 104.37 | 66.66 | 0.00 | 0.00 | 0.00 |
March | 104.30 | 55.62 | 48.68 | 118.21 | 56.47 | 0.00 | 0.00 | 0.00 |
April | 110.12 | 47.81 | 62.30 | 132.41 | 47.27 | 0.00 | 0.00 | 0.00 |
May | 100.69 | 30.00 | 70.69 | 121.40 | 41.41 | 0.00 | 0.00 | 0.00 |
June | 92.12 | 24.73 | 67.39 | 111.75 | 34.23 | 0.00 | 0.00 | 0.00 |
July | 100.46 | 36.79 | 63.67 | 132.92 | 31.66 | 0.00 | 0.00 | 0.00 |
August | 107.93 | 50.33 | 57.60 | 146.88 | 31.01 | 0.00 | 0.00 | 0.00 |
September | 119.58 | 66.04 | 53.55 | 153.38 | 42.14 | 0.00 | 0.00 | 0.00 |
October | 108.32 | 66.88 | 41.44 | 129.24 | 52.01 | 0.00 | 0.00 | 0.00 |
November | 64.04 | 36.70 | 27.34 | 65.14 | 62.09 | 0.00 | 0.00 | 0.00 |
December | 67.01 | 43.36 | 23.64 | 69.14 | 77.54 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 94.51 | 46.23 | 48.28 | 112.03 | 51.46 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 63.05 | 24.73 | 23.64 | 59.21 | 31.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 119.58 | 66.88 | 70.69 | 153.38 | 77.54 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 63.05 | 37.44 | 25.61 | 59.21 | 75.87 | 0.00 | 0.00 | 0.00 |
February | 96.96 | 60.02 | 36.94 | 104.37 | 66.66 | 0.00 | 0.00 | 0.00 |
March | 104.30 | 55.62 | 48.68 | 118.21 | 56.47 | 0.00 | 0.00 | 0.00 |
April | 110.12 | 47.81 | 62.30 | 132.41 | 47.27 | 0.00 | 0.00 | 0.00 |
May | 100.69 | 30.00 | 70.69 | 121.40 | 41.41 | 0.00 | 0.00 | 0.00 |
June | 92.12 | 24.73 | 67.39 | 111.75 | 34.23 | 0.00 | 0.00 | 0.00 |
July | 100.46 | 36.79 | 63.67 | 132.92 | 31.66 | 0.00 | 0.00 | 0.00 |
August | 107.93 | 50.33 | 57.60 | 146.88 | 31.01 | 0.00 | 0.00 | 0.00 |
September | 119.58 | 66.04 | 53.55 | 153.38 | 42.14 | 0.00 | 0.00 | 0.00 |
October | 108.32 | 66.88 | 41.44 | 129.24 | 52.01 | 0.00 | 0.00 | 0.00 |
November | 64.04 | 36.70 | 27.34 | 65.14 | 62.09 | 0.00 | 0.00 | 0.00 |
December | 67.01 | 43.36 | 23.64 | 69.14 | 77.54 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 94.51 | 46.23 | 48.28 | 112.03 | 51.46 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 63.05 | 24.73 | 23.64 | 59.21 | 31.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 119.58 | 66.88 | 70.69 | 153.38 | 77.54 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 52.73 | 31.31 | 21.42 | 49.08 | 64.64 | 0.00 | 0.00 | 0.00 |
February | 81.09 | 50.20 | 30.90 | 86.74 | 56.63 | 0.00 | 0.00 | 0.00 |
March | 87.23 | 46.52 | 40.71 | 98.35 | 47.91 | 0.00 | 0.00 | 0.00 |
April | 92.10 | 39.99 | 52.11 | 110.07 | 40.16 | 0.00 | 0.00 | 0.00 |
May | 84.22 | 25.09 | 59.13 | 100.73 | 35.31 | 0.00 | 0.00 | 0.00 |
June | 77.05 | 20.69 | 56.36 | 92.86 | 29.03 | 0.00 | 0.00 | 0.00 |
July | 84.03 | 30.77 | 53.25 | 110.87 | 26.64 | 0.00 | 0.00 | 0.00 |
August | 90.28 | 42.10 | 48.18 | 122.64 | 26.02 | 0.00 | 0.00 | 0.00 |
September | 100.02 | 55.24 | 44.79 | 127.85 | 35.71 | 0.00 | 0.00 | 0.00 |
October | 90.60 | 55.94 | 34.66 | 107.46 | 44.22 | 0.00 | 0.00 | 0.00 |
November | 53.57 | 30.70 | 22.87 | 54.11 | 52.77 | 0.00 | 0.00 | 0.00 |
December | 56.05 | 36.27 | 19.78 | 57.50 | 65.93 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 79.05 | 38.66 | 40.38 | 93.21 | 43.69 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 52.73 | 20.69 | 19.78 | 49.08 | 26.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 100.02 | 55.94 | 59.13 | 127.85 | 65.93 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 52.73 | 31.31 | 21.42 | 49.08 | 64.64 | 0.00 | 0.00 | 0.00 |
February | 81.09 | 50.20 | 30.90 | 86.74 | 56.63 | 0.00 | 0.00 | 0.00 |
March | 87.23 | 46.52 | 40.71 | 98.35 | 47.91 | 0.00 | 0.00 | 0.00 |
April | 92.10 | 39.99 | 52.11 | 110.07 | 40.16 | 0.00 | 0.00 | 0.00 |
May | 84.22 | 25.09 | 59.13 | 100.73 | 35.31 | 0.00 | 0.00 | 0.00 |
June | 77.05 | 20.69 | 56.36 | 92.86 | 29.03 | 0.00 | 0.00 | 0.00 |
July | 84.03 | 30.77 | 53.25 | 110.87 | 26.64 | 0.00 | 0.00 | 0.00 |
August | 90.28 | 42.10 | 48.18 | 122.64 | 26.02 | 0.00 | 0.00 | 0.00 |
September | 100.02 | 55.24 | 44.79 | 127.85 | 35.71 | 0.00 | 0.00 | 0.00 |
October | 90.60 | 55.94 | 34.66 | 107.46 | 44.22 | 0.00 | 0.00 | 0.00 |
November | 53.57 | 30.70 | 22.87 | 54.11 | 52.77 | 0.00 | 0.00 | 0.00 |
December | 56.05 | 36.27 | 19.78 | 57.50 | 65.93 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 79.05 | 38.66 | 40.38 | 93.21 | 43.69 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 52.73 | 20.69 | 19.78 | 49.08 | 26.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 100.02 | 55.94 | 59.13 | 127.85 | 65.93 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 63.05 | 37.44 | 25.61 | 58.98 | 76.26 | 0.00 | 0.00 | 0.00 |
February | 96.96 | 60.02 | 36.94 | 104.07 | 66.89 | 0.00 | 0.00 | 0.00 |
March | 104.30 | 55.62 | 48.68 | 117.91 | 56.60 | 0.00 | 0.00 | 0.00 |
April | 110.12 | 47.81 | 62.30 | 131.95 | 47.46 | 0.00 | 0.00 | 0.00 |
May | 100.69 | 30.00 | 70.69 | 120.76 | 41.74 | 0.00 | 0.00 | 0.00 |
June | 92.12 | 24.73 | 67.39 | 111.30 | 34.35 | 0.00 | 0.00 | 0.00 |
July | 100.46 | 36.79 | 63.67 | 132.71 | 31.56 | 0.00 | 0.00 | 0.00 |
August | 107.93 | 50.33 | 57.60 | 146.71 | 30.86 | 0.00 | 0.00 | 0.00 |
September | 119.58 | 66.04 | 53.55 | 152.95 | 42.35 | 0.00 | 0.00 | 0.00 |
October | 108.32 | 66.88 | 41.44 | 128.76 | 52.32 | 0.00 | 0.00 | 0.00 |
November | 64.04 | 36.70 | 27.34 | 64.94 | 62.30 | 0.00 | 0.00 | 0.00 |
December | 67.01 | 43.36 | 23.64 | 68.97 | 77.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 94.51 | 46.23 | 48.28 | 111.69 | 51.64 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 63.05 | 24.73 | 23.64 | 58.98 | 30.86 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 119.58 | 66.88 | 70.69 | 152.95 | 77.86 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 52.73 | 31.31 | 21.42 | 49.12 | 64.42 | 0.00 | 0.00 | 0.00 |
February | 81.09 | 50.20 | 30.90 | 86.82 | 56.39 | 0.00 | 0.00 | 0.00 |
March | 87.23 | 46.52 | 40.71 | 98.44 | 47.65 | 0.00 | 0.00 | 0.00 |
April | 92.10 | 39.99 | 52.11 | 110.19 | 39.93 | 0.00 | 0.00 | 0.00 |
May | 84.22 | 25.09 | 59.13 | 100.90 | 35.08 | 0.00 | 0.00 | 0.00 |
June | 77.05 | 20.69 | 56.36 | 92.98 | 28.88 | 0.00 | 0.00 | 0.00 |
July | 84.03 | 30.77 | 53.25 | 110.95 | 26.51 | 0.00 | 0.00 | 0.00 |
August | 90.28 | 42.10 | 48.18 | 122.71 | 25.90 | 0.00 | 0.00 | 0.00 |
September | 100.02 | 55.24 | 44.79 | 127.93 | 35.56 | 0.00 | 0.00 | 0.00 |
October | 90.60 | 55.94 | 34.66 | 107.55 | 43.99 | 0.00 | 0.00 | 0.00 |
November | 53.57 | 30.70 | 22.87 | 54.17 | 52.53 | 0.00 | 0.00 | 0.00 |
December | 56.05 | 36.27 | 19.78 | 57.55 | 65.70 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 79.05 | 38.66 | 40.38 | 93.29 | 43.49 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 52.73 | 20.69 | 19.78 | 49.12 | 25.90 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 100.02 | 55.94 | 59.13 | 127.93 | 65.70 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 52.73 | 31.31 | 21.42 | 49.12 | 64.42 | 0.00 | 0.00 | 0.00 |
February | 81.09 | 50.20 | 30.90 | 86.82 | 56.39 | 0.00 | 0.00 | 0.00 |
March | 87.23 | 46.52 | 40.71 | 98.44 | 47.65 | 0.00 | 0.00 | 0.00 |
April | 92.10 | 39.99 | 52.11 | 110.19 | 39.93 | 0.00 | 0.00 | 0.00 |
May | 84.22 | 25.09 | 59.13 | 100.90 | 35.08 | 0.00 | 0.00 | 0.00 |
June | 77.05 | 20.69 | 56.36 | 92.98 | 28.88 | 0.00 | 0.00 | 0.00 |
July | 84.03 | 30.77 | 53.25 | 110.95 | 26.51 | 0.00 | 0.00 | 0.00 |
August | 90.28 | 42.10 | 48.18 | 122.71 | 25.90 | 0.00 | 0.00 | 0.00 |
September | 100.02 | 55.24 | 44.79 | 127.93 | 35.56 | 0.00 | 0.00 | 0.00 |
October | 90.60 | 55.94 | 34.66 | 107.55 | 43.99 | 0.00 | 0.00 | 0.00 |
November | 53.57 | 30.70 | 22.87 | 54.17 | 52.53 | 0.00 | 0.00 | 0.00 |
December | 56.05 | 36.27 | 19.78 | 57.55 | 65.70 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 79.05 | 38.66 | 40.38 | 93.29 | 43.49 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 52.73 | 20.69 | 19.78 | 49.12 | 25.90 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 100.02 | 55.94 | 59.13 | 127.93 | 65.70 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 63.05 | 37.44 | 25.61 | 59.03 | 75.99 | 0.00 | 0.00 | 0.00 |
February | 96.96 | 60.02 | 36.94 | 104.16 | 66.61 | 0.00 | 0.00 | 0.00 |
March | 104.30 | 55.62 | 48.68 | 118.01 | 56.29 | 0.00 | 0.00 | 0.00 |
April | 110.12 | 47.81 | 62.30 | 132.09 | 47.18 | 0.00 | 0.00 | 0.00 |
May | 100.69 | 30.00 | 70.69 | 120.95 | 41.48 | 0.00 | 0.00 | 0.00 |
June | 92.12 | 24.73 | 67.39 | 111.43 | 34.17 | 0.00 | 0.00 | 0.00 |
July | 100.46 | 36.79 | 63.67 | 132.81 | 31.41 | 0.00 | 0.00 | 0.00 |
August | 107.93 | 50.33 | 57.60 | 146.79 | 30.72 | 0.00 | 0.00 | 0.00 |
September | 119.58 | 66.04 | 53.55 | 153.04 | 42.17 | 0.00 | 0.00 | 0.00 |
October | 108.32 | 66.88 | 41.44 | 128.88 | 52.05 | 0.00 | 0.00 | 0.00 |
November | 64.04 | 36.70 | 27.34 | 65.01 | 62.02 | 0.00 | 0.00 | 0.00 |
December | 67.01 | 43.36 | 23.64 | 69.02 | 77.59 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 94.51 | 46.23 | 48.28 | 111.79 | 51.41 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 63.05 | 24.73 | 23.64 | 59.03 | 30.72 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 119.58 | 66.88 | 70.69 | 153.04 | 77.59 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 52.73 | 31.31 | 21.42 | 49.28 | 63.41 | 0.00 | 0.00 | 0.00 |
February | 81.09 | 50.20 | 30.90 | 87.09 | 55.42 | 0.00 | 0.00 | 0.00 |
March | 87.23 | 46.52 | 40.71 | 98.74 | 46.67 | 0.00 | 0.00 | 0.00 |
April | 92.10 | 39.99 | 52.11 | 110.61 | 39.01 | 0.00 | 0.00 | 0.00 |
May | 84.22 | 25.09 | 59.13 | 101.53 | 34.12 | 0.00 | 0.00 | 0.00 |
June | 77.05 | 20.69 | 56.36 | 93.42 | 28.25 | 0.00 | 0.00 | 0.00 |
July | 84.03 | 30.77 | 53.25 | 111.19 | 26.08 | 0.00 | 0.00 | 0.00 |
August | 90.28 | 42.10 | 48.18 | 122.88 | 25.55 | 0.00 | 0.00 | 0.00 |
September | 100.02 | 55.24 | 44.79 | 128.28 | 34.87 | 0.00 | 0.00 | 0.00 |
October | 90.60 | 55.94 | 34.66 | 107.93 | 43.04 | 0.00 | 0.00 | 0.00 |
November | 53.57 | 30.70 | 22.87 | 54.38 | 51.65 | 0.00 | 0.00 | 0.00 |
December | 56.05 | 36.27 | 19.78 | 57.70 | 64.75 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 79.05 | 38.66 | 40.38 | 93.60 | 42.68 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 52.73 | 20.69 | 19.78 | 49.28 | 25.55 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 100.02 | 55.94 | 59.13 | 128.28 | 64.75 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 52.73 | 31.31 | 21.42 | 49.28 | 63.41 | 0.00 | 0.00 | 0.00 |
February | 81.09 | 50.20 | 30.90 | 87.09 | 55.42 | 0.00 | 0.00 | 0.00 |
March | 87.23 | 46.52 | 40.71 | 98.74 | 46.67 | 0.00 | 0.00 | 0.00 |
April | 92.10 | 39.99 | 52.11 | 110.61 | 39.01 | 0.00 | 0.00 | 0.00 |
May | 84.22 | 25.09 | 59.13 | 101.53 | 34.12 | 0.00 | 0.00 | 0.00 |
June | 77.05 | 20.69 | 56.36 | 93.42 | 28.25 | 0.00 | 0.00 | 0.00 |
July | 84.03 | 30.77 | 53.25 | 111.19 | 26.08 | 0.00 | 0.00 | 0.00 |
August | 90.28 | 42.10 | 48.18 | 122.88 | 25.55 | 0.00 | 0.00 | 0.00 |
September | 100.02 | 55.24 | 44.79 | 128.28 | 34.87 | 0.00 | 0.00 | 0.00 |
October | 90.60 | 55.94 | 34.66 | 107.93 | 43.04 | 0.00 | 0.00 | 0.00 |
November | 53.57 | 30.70 | 22.87 | 54.38 | 51.65 | 0.00 | 0.00 | 0.00 |
December | 56.05 | 36.27 | 19.78 | 57.70 | 64.75 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 79.05 | 38.66 | 40.38 | 93.60 | 42.68 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 52.73 | 20.69 | 19.78 | 49.28 | 25.55 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 100.02 | 55.94 | 59.13 | 128.28 | 64.75 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 63.05 | 37.44 | 25.61 | 59.23 | 74.80 | 0.00 | 0.00 | 0.00 |
February | 96.96 | 60.02 | 36.94 | 104.49 | 65.47 | 0.00 | 0.00 | 0.00 |
March | 104.30 | 55.62 | 48.68 | 118.37 | 55.13 | 0.00 | 0.00 | 0.00 |
April | 110.12 | 47.81 | 62.30 | 132.60 | 46.10 | 0.00 | 0.00 | 0.00 |
May | 100.69 | 30.00 | 70.69 | 121.70 | 40.35 | 0.00 | 0.00 | 0.00 |
June | 92.12 | 24.73 | 67.39 | 111.96 | 33.43 | 0.00 | 0.00 | 0.00 |
July | 100.46 | 36.79 | 63.67 | 133.10 | 30.90 | 0.00 | 0.00 | 0.00 |
August | 107.93 | 50.33 | 57.60 | 146.99 | 30.30 | 0.00 | 0.00 | 0.00 |
September | 119.58 | 66.04 | 53.55 | 153.46 | 41.36 | 0.00 | 0.00 | 0.00 |
October | 108.32 | 66.88 | 41.44 | 129.32 | 50.93 | 0.00 | 0.00 | 0.00 |
November | 64.04 | 36.70 | 27.34 | 65.26 | 60.97 | 0.00 | 0.00 | 0.00 |
December | 67.01 | 43.36 | 23.64 | 69.21 | 76.46 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 94.51 | 46.23 | 48.28 | 112.16 | 50.45 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 63.05 | 24.73 | 23.64 | 59.23 | 30.30 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 119.58 | 66.88 | 70.69 | 153.46 | 76.46 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 52.73 | 31.31 | 21.42 | 49.94 | 59.27 | 0.00 | 0.00 | 0.00 |
February | 81.09 | 50.20 | 30.90 | 88.04 | 51.58 | 0.00 | 0.00 | 0.00 |
March | 87.23 | 46.52 | 40.71 | 99.67 | 43.02 | 0.00 | 0.00 | 0.00 |
April | 92.10 | 39.99 | 52.11 | 111.63 | 35.87 | 0.00 | 0.00 | 0.00 |
May | 84.22 | 25.09 | 59.13 | 102.86 | 31.23 | 0.00 | 0.00 | 0.00 |
June | 77.05 | 20.69 | 56.36 | 94.42 | 26.10 | 0.00 | 0.00 | 0.00 |
July | 84.03 | 30.77 | 53.25 | 111.81 | 24.42 | 0.00 | 0.00 | 0.00 |
August | 90.28 | 42.10 | 48.18 | 123.26 | 24.13 | 0.00 | 0.00 | 0.00 |
September | 100.02 | 55.24 | 44.79 | 129.11 | 32.67 | 0.00 | 0.00 | 0.00 |
October | 90.60 | 55.94 | 34.66 | 108.82 | 40.08 | 0.00 | 0.00 | 0.00 |
November | 53.57 | 30.70 | 22.87 | 55.00 | 48.44 | 0.00 | 0.00 | 0.00 |
December | 56.05 | 36.27 | 19.78 | 58.29 | 60.89 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 79.05 | 38.66 | 40.38 | 94.42 | 39.76 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 52.73 | 20.69 | 19.78 | 49.94 | 24.13 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 100.02 | 55.94 | 59.13 | 129.11 | 60.89 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 52.73 | 31.31 | 21.42 | 49.94 | 59.27 | 0.00 | 0.00 | 0.00 |
February | 81.09 | 50.20 | 30.90 | 88.04 | 51.58 | 0.00 | 0.00 | 0.00 |
March | 87.23 | 46.52 | 40.71 | 99.67 | 43.02 | 0.00 | 0.00 | 0.00 |
April | 92.10 | 39.99 | 52.11 | 111.63 | 35.87 | 0.00 | 0.00 | 0.00 |
May | 84.22 | 25.09 | 59.13 | 102.86 | 31.23 | 0.00 | 0.00 | 0.00 |
June | 77.05 | 20.69 | 56.36 | 94.42 | 26.10 | 0.00 | 0.00 | 0.00 |
July | 84.03 | 30.77 | 53.25 | 111.81 | 24.42 | 0.00 | 0.00 | 0.00 |
August | 90.28 | 42.10 | 48.18 | 123.26 | 24.13 | 0.00 | 0.00 | 0.00 |
September | 100.02 | 55.24 | 44.79 | 129.11 | 32.67 | 0.00 | 0.00 | 0.00 |
October | 90.60 | 55.94 | 34.66 | 108.82 | 40.08 | 0.00 | 0.00 | 0.00 |
November | 53.57 | 30.70 | 22.87 | 55.00 | 48.44 | 0.00 | 0.00 | 0.00 |
December | 56.05 | 36.27 | 19.78 | 58.29 | 60.89 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 79.05 | 38.66 | 40.38 | 94.42 | 39.76 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 52.73 | 20.69 | 19.78 | 49.94 | 24.13 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 100.02 | 55.94 | 59.13 | 129.11 | 60.89 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 63.05 | 37.44 | 25.61 | 60.03 | 69.91 | 0.00 | 0.00 | 0.00 |
February | 96.96 | 60.02 | 36.94 | 105.64 | 60.92 | 0.00 | 0.00 | 0.00 |
March | 104.30 | 55.62 | 48.68 | 119.50 | 50.83 | 0.00 | 0.00 | 0.00 |
April | 110.12 | 47.81 | 62.30 | 133.83 | 42.40 | 0.00 | 0.00 | 0.00 |
May | 100.69 | 30.00 | 70.69 | 123.29 | 36.95 | 0.00 | 0.00 | 0.00 |
June | 92.12 | 24.73 | 67.39 | 113.16 | 30.91 | 0.00 | 0.00 | 0.00 |
July | 100.46 | 36.79 | 63.67 | 133.83 | 28.95 | 0.00 | 0.00 | 0.00 |
August | 107.93 | 50.33 | 57.60 | 147.45 | 28.63 | 0.00 | 0.00 | 0.00 |
September | 119.58 | 66.04 | 53.55 | 154.45 | 38.77 | 0.00 | 0.00 | 0.00 |
October | 108.32 | 66.88 | 41.44 | 130.40 | 47.44 | 0.00 | 0.00 | 0.00 |
November | 64.04 | 36.70 | 27.34 | 66.01 | 57.19 | 0.00 | 0.00 | 0.00 |
December | 67.01 | 43.36 | 23.64 | 69.92 | 71.89 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 94.51 | 46.23 | 48.28 | 113.15 | 47.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 63.05 | 24.73 | 23.64 | 60.03 | 28.63 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 119.58 | 66.88 | 70.69 | 154.45 | 71.89 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.141239E+09 | 83868378.55 | 57370671.88 | 0.131731E+09 | 0.177351E+09 |
February | 0.196184E+09 | 0.121441E+09 | 74743521.61 | 0.210044E+09 | 0.139684E+09 |
March | 0.233649E+09 | 0.124602E+09 | 0.109046E+09 | 0.264042E+09 | 0.129789E+09 |
April | 0.238731E+09 | 0.103656E+09 | 0.135075E+09 | 0.286066E+09 | 0.105284E+09 |
May | 0.225565E+09 | 67198142.68 | 0.158367E+09 | 0.271116E+09 | 94343918.72 |
June | 0.199713E+09 | 53620423.71 | 0.146093E+09 | 0.242135E+09 | 74578354.39 |
July | 0.225056E+09 | 82427341.00 | 0.142628E+09 | 0.298093E+09 | 70512139.45 |
August | 0.241794E+09 | 0.112753E+09 | 0.129041E+09 | 0.329564E+09 | 68716812.86 |
September | 0.259256E+09 | 0.143170E+09 | 0.116086E+09 | 0.332368E+09 | 92290203.48 |
October | 0.242670E+09 | 0.149831E+09 | 92839157.57 | 0.288463E+09 | 0.119749E+09 |
November | 0.138846E+09 | 79570640.96 | 59275692.84 | 0.140119E+09 | 0.140081E+09 |
December | 0.150115E+09 | 97145650.36 | 52969808.28 | 0.154112E+09 | 0.179910E+09 |
Annual Sum or Average | 0.249282E+10 | 0.121928E+10 | 0.127354E+10 | 0.294785E+10 | 0.139229E+10 |
Minimum of Months | 0.138846E+09 | 53620423.71 | 52969808.28 | 0.131731E+09 | 68716812.86 |
Maximum of Months | 0.259256E+09 | 0.149831E+09 | 0.158367E+09 | 0.332368E+09 | 0.179910E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.141239E+09 | 83868378.55 | 57370671.88 | 0.131731E+09 | 0.177351E+09 |
February | 0.196184E+09 | 0.121441E+09 | 74743521.61 | 0.210044E+09 | 0.139684E+09 |
March | 0.233649E+09 | 0.124602E+09 | 0.109046E+09 | 0.264042E+09 | 0.129789E+09 |
April | 0.238731E+09 | 0.103656E+09 | 0.135075E+09 | 0.286066E+09 | 0.105284E+09 |
May | 0.225565E+09 | 67198142.68 | 0.158367E+09 | 0.271116E+09 | 94343918.72 |
June | 0.199713E+09 | 53620423.71 | 0.146093E+09 | 0.242135E+09 | 74578354.39 |
July | 0.225056E+09 | 82427341.00 | 0.142628E+09 | 0.298093E+09 | 70512139.45 |
August | 0.241794E+09 | 0.112753E+09 | 0.129041E+09 | 0.329564E+09 | 68716812.86 |
September | 0.259256E+09 | 0.143170E+09 | 0.116086E+09 | 0.332368E+09 | 92290203.48 |
October | 0.242670E+09 | 0.149831E+09 | 92839157.57 | 0.288463E+09 | 0.119749E+09 |
November | 0.138846E+09 | 79570640.96 | 59275692.84 | 0.140119E+09 | 0.140081E+09 |
December | 0.150115E+09 | 97145650.36 | 52969808.28 | 0.154112E+09 | 0.179910E+09 |
Annual Sum or Average | 0.249282E+10 | 0.121928E+10 | 0.127354E+10 | 0.294785E+10 | 0.139229E+10 |
Minimum of Months | 0.138846E+09 | 53620423.71 | 52969808.28 | 0.131731E+09 | 68716812.86 |
Maximum of Months | 0.259256E+09 | 0.149831E+09 | 0.158367E+09 | 0.332368E+09 | 0.179910E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.141239E+09 | 83868378.55 | 57370671.88 | 0.131731E+09 | 0.177351E+09 |
February | 0.196184E+09 | 0.121441E+09 | 74743521.61 | 0.210044E+09 | 0.139684E+09 |
March | 0.233649E+09 | 0.124602E+09 | 0.109046E+09 | 0.264042E+09 | 0.129789E+09 |
April | 0.238731E+09 | 0.103656E+09 | 0.135075E+09 | 0.286066E+09 | 0.105284E+09 |
May | 0.225565E+09 | 67198142.68 | 0.158367E+09 | 0.271116E+09 | 94343918.72 |
June | 0.199713E+09 | 53620423.71 | 0.146093E+09 | 0.242135E+09 | 74578354.39 |
July | 0.225056E+09 | 82427341.00 | 0.142628E+09 | 0.298093E+09 | 70512139.45 |
August | 0.241794E+09 | 0.112753E+09 | 0.129041E+09 | 0.329564E+09 | 68716812.86 |
September | 0.259256E+09 | 0.143170E+09 | 0.116086E+09 | 0.332368E+09 | 92290203.48 |
October | 0.242670E+09 | 0.149831E+09 | 92839157.57 | 0.288463E+09 | 0.119749E+09 |
November | 0.138846E+09 | 79570640.96 | 59275692.84 | 0.140119E+09 | 0.140081E+09 |
December | 0.150115E+09 | 97145650.36 | 52969808.28 | 0.154112E+09 | 0.179910E+09 |
Annual Sum or Average | 0.249282E+10 | 0.121928E+10 | 0.127354E+10 | 0.294785E+10 | 0.139229E+10 |
Minimum of Months | 0.138846E+09 | 53620423.71 | 52969808.28 | 0.131731E+09 | 68716812.86 |
Maximum of Months | 0.259256E+09 | 0.149831E+09 | 0.158367E+09 | 0.332368E+09 | 0.179910E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.141239E+09 | 83868378.55 | 57370671.88 | 0.131731E+09 | 0.177351E+09 |
February | 0.196184E+09 | 0.121441E+09 | 74743521.61 | 0.210044E+09 | 0.139684E+09 |
March | 0.233649E+09 | 0.124602E+09 | 0.109046E+09 | 0.264042E+09 | 0.129789E+09 |
April | 0.238731E+09 | 0.103656E+09 | 0.135075E+09 | 0.286066E+09 | 0.105284E+09 |
May | 0.225565E+09 | 67198142.68 | 0.158367E+09 | 0.271116E+09 | 94343918.72 |
June | 0.199713E+09 | 53620423.71 | 0.146093E+09 | 0.242135E+09 | 74578354.39 |
July | 0.225056E+09 | 82427341.00 | 0.142628E+09 | 0.298093E+09 | 70512139.45 |
August | 0.241794E+09 | 0.112753E+09 | 0.129041E+09 | 0.329564E+09 | 68716812.86 |
September | 0.259256E+09 | 0.143170E+09 | 0.116086E+09 | 0.332368E+09 | 92290203.48 |
October | 0.242670E+09 | 0.149831E+09 | 92839157.57 | 0.288463E+09 | 0.119749E+09 |
November | 0.138846E+09 | 79570640.96 | 59275692.84 | 0.140119E+09 | 0.140081E+09 |
December | 0.150115E+09 | 97145650.36 | 52969808.28 | 0.154112E+09 | 0.179910E+09 |
Annual Sum or Average | 0.249282E+10 | 0.121928E+10 | 0.127354E+10 | 0.294785E+10 | 0.139229E+10 |
Minimum of Months | 0.138846E+09 | 53620423.71 | 52969808.28 | 0.131731E+09 | 68716812.86 |
Maximum of Months | 0.259256E+09 | 0.149831E+09 | 0.158367E+09 | 0.332368E+09 | 0.179910E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.169791E+09 | 0.100823E+09 | 68968379.87 | 0.159113E+09 | 0.210472E+09 |
February | 0.235844E+09 | 0.145990E+09 | 89853219.81 | 0.253294E+09 | 0.165977E+09 |
March | 0.280882E+09 | 0.149791E+09 | 0.131091E+09 | 0.318167E+09 | 0.154263E+09 |
April | 0.286991E+09 | 0.124610E+09 | 0.162381E+09 | 0.344681E+09 | 0.125170E+09 |
May | 0.271164E+09 | 80782512.71 | 0.190382E+09 | 0.326649E+09 | 0.112251E+09 |
June | 0.240086E+09 | 64460004.21 | 0.175626E+09 | 0.291668E+09 | 88799814.40 |
July | 0.270551E+09 | 99090353.65 | 0.171461E+09 | 0.358655E+09 | 84068376.34 |
August | 0.290673E+09 | 0.135546E+09 | 0.155128E+09 | 0.396295E+09 | 82019763.28 |
September | 0.311665E+09 | 0.172112E+09 | 0.139553E+09 | 0.399682E+09 | 0.110141E+09 |
October | 0.291727E+09 | 0.180120E+09 | 0.111607E+09 | 0.347425E+09 | 0.142548E+09 |
November | 0.166915E+09 | 95656160.40 | 71258508.34 | 0.169004E+09 | 0.166395E+09 |
December | 0.180462E+09 | 0.116784E+09 | 63677864.30 | 0.185798E+09 | 0.213733E+09 |
Annual Sum or Average | 0.299675E+10 | 0.146576E+10 | 0.153099E+10 | 0.355043E+10 | 0.165584E+10 |
Minimum of Months | 0.166915E+09 | 64460004.21 | 63677864.30 | 0.159113E+09 | 82019763.28 |
Maximum of Months | 0.311665E+09 | 0.180120E+09 | 0.190382E+09 | 0.399682E+09 | 0.213733E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.169791E+09 | 0.100823E+09 | 68968379.87 | 0.159113E+09 | 0.210472E+09 |
February | 0.235844E+09 | 0.145990E+09 | 89853219.81 | 0.253294E+09 | 0.165977E+09 |
March | 0.280882E+09 | 0.149791E+09 | 0.131091E+09 | 0.318167E+09 | 0.154263E+09 |
April | 0.286991E+09 | 0.124610E+09 | 0.162381E+09 | 0.344681E+09 | 0.125170E+09 |
May | 0.271164E+09 | 80782512.71 | 0.190382E+09 | 0.326649E+09 | 0.112251E+09 |
June | 0.240086E+09 | 64460004.21 | 0.175626E+09 | 0.291668E+09 | 88799814.40 |
July | 0.270551E+09 | 99090353.65 | 0.171461E+09 | 0.358655E+09 | 84068376.34 |
August | 0.290673E+09 | 0.135546E+09 | 0.155128E+09 | 0.396295E+09 | 82019763.28 |
September | 0.311665E+09 | 0.172112E+09 | 0.139553E+09 | 0.399682E+09 | 0.110141E+09 |
October | 0.291727E+09 | 0.180120E+09 | 0.111607E+09 | 0.347425E+09 | 0.142548E+09 |
November | 0.166915E+09 | 95656160.40 | 71258508.34 | 0.169004E+09 | 0.166395E+09 |
December | 0.180462E+09 | 0.116784E+09 | 63677864.30 | 0.185798E+09 | 0.213733E+09 |
Annual Sum or Average | 0.299675E+10 | 0.146576E+10 | 0.153099E+10 | 0.355043E+10 | 0.165584E+10 |
Minimum of Months | 0.166915E+09 | 64460004.21 | 63677864.30 | 0.159113E+09 | 82019763.28 |
Maximum of Months | 0.311665E+09 | 0.180120E+09 | 0.190382E+09 | 0.399682E+09 | 0.213733E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.141239E+09 | 83868378.55 | 57370671.88 | 0.129587E+09 | 0.188422E+09 |
February | 0.196184E+09 | 0.121441E+09 | 74743521.61 | 0.207024E+09 | 0.149491E+09 |
March | 0.233649E+09 | 0.124602E+09 | 0.109046E+09 | 0.259706E+09 | 0.142787E+09 |
April | 0.238731E+09 | 0.103656E+09 | 0.135075E+09 | 0.280247E+09 | 0.116454E+09 |
May | 0.225565E+09 | 67198142.68 | 0.158367E+09 | 0.264955E+09 | 0.102921E+09 |
June | 0.199713E+09 | 53620423.71 | 0.146093E+09 | 0.238875E+09 | 78486735.77 |
July | 0.225056E+09 | 82427341.00 | 0.142628E+09 | 0.296627E+09 | 72286964.94 |
August | 0.241794E+09 | 0.112753E+09 | 0.129041E+09 | 0.328361E+09 | 70198375.92 |
September | 0.259256E+09 | 0.143170E+09 | 0.116086E+09 | 0.329572E+09 | 96434227.55 |
October | 0.242670E+09 | 0.149831E+09 | 92839157.57 | 0.283634E+09 | 0.131492E+09 |
November | 0.138846E+09 | 79570640.96 | 59275692.84 | 0.137481E+09 | 0.150838E+09 |
December | 0.150115E+09 | 97145650.36 | 52969808.28 | 0.152163E+09 | 0.191016E+09 |
Annual Sum or Average | 0.249282E+10 | 0.121928E+10 | 0.127354E+10 | 0.290823E+10 | 0.149083E+10 |
Minimum of Months | 0.138846E+09 | 53620423.71 | 52969808.28 | 0.129587E+09 | 70198375.92 |
Maximum of Months | 0.259256E+09 | 0.149831E+09 | 0.158367E+09 | 0.329572E+09 | 0.191016E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.141239E+09 | 83868378.55 | 57370671.88 | 0.129587E+09 | 0.188422E+09 |
February | 0.196184E+09 | 0.121441E+09 | 74743521.61 | 0.207024E+09 | 0.149491E+09 |
March | 0.233649E+09 | 0.124602E+09 | 0.109046E+09 | 0.259706E+09 | 0.142787E+09 |
April | 0.238731E+09 | 0.103656E+09 | 0.135075E+09 | 0.280247E+09 | 0.116454E+09 |
May | 0.225565E+09 | 67198142.68 | 0.158367E+09 | 0.264955E+09 | 0.102921E+09 |
June | 0.199713E+09 | 53620423.71 | 0.146093E+09 | 0.238875E+09 | 78486735.77 |
July | 0.225056E+09 | 82427341.00 | 0.142628E+09 | 0.296627E+09 | 72286964.94 |
August | 0.241794E+09 | 0.112753E+09 | 0.129041E+09 | 0.328361E+09 | 70198375.92 |
September | 0.259256E+09 | 0.143170E+09 | 0.116086E+09 | 0.329572E+09 | 96434227.55 |
October | 0.242670E+09 | 0.149831E+09 | 92839157.57 | 0.283634E+09 | 0.131492E+09 |
November | 0.138846E+09 | 79570640.96 | 59275692.84 | 0.137481E+09 | 0.150838E+09 |
December | 0.150115E+09 | 97145650.36 | 52969808.28 | 0.152163E+09 | 0.191016E+09 |
Annual Sum or Average | 0.249282E+10 | 0.121928E+10 | 0.127354E+10 | 0.290823E+10 | 0.149083E+10 |
Minimum of Months | 0.138846E+09 | 53620423.71 | 52969808.28 | 0.129587E+09 | 70198375.92 |
Maximum of Months | 0.259256E+09 | 0.149831E+09 | 0.158367E+09 | 0.329572E+09 | 0.191016E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.169791E+09 | 0.100823E+09 | 68968379.87 | 0.156556E+09 | 0.223506E+09 |
February | 0.235844E+09 | 0.145990E+09 | 89853219.81 | 0.249715E+09 | 0.177510E+09 |
March | 0.280882E+09 | 0.149791E+09 | 0.131091E+09 | 0.313037E+09 | 0.169544E+09 |
April | 0.286991E+09 | 0.124610E+09 | 0.162381E+09 | 0.337821E+09 | 0.138286E+09 |
May | 0.271164E+09 | 80782512.71 | 0.190382E+09 | 0.319392E+09 | 0.122337E+09 |
June | 0.240086E+09 | 64460004.21 | 0.175626E+09 | 0.287847E+09 | 93388307.44 |
July | 0.270551E+09 | 99090353.65 | 0.171461E+09 | 0.356971E+09 | 86144159.35 |
August | 0.290673E+09 | 0.135546E+09 | 0.155128E+09 | 0.394920E+09 | 83759520.23 |
September | 0.311665E+09 | 0.172112E+09 | 0.139553E+09 | 0.396404E+09 | 0.115037E+09 |
October | 0.291727E+09 | 0.180120E+09 | 0.111607E+09 | 0.341749E+09 | 0.156367E+09 |
November | 0.166915E+09 | 95656160.40 | 71258508.34 | 0.165875E+09 | 0.179030E+09 |
December | 0.180462E+09 | 0.116784E+09 | 63677864.30 | 0.183484E+09 | 0.226830E+09 |
Annual Sum or Average | 0.299675E+10 | 0.146576E+10 | 0.153099E+10 | 0.350377E+10 | 0.177174E+10 |
Minimum of Months | 0.166915E+09 | 64460004.21 | 63677864.30 | 0.156556E+09 | 83759520.23 |
Maximum of Months | 0.311665E+09 | 0.180120E+09 | 0.190382E+09 | 0.396404E+09 | 0.226830E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.141239E+09 | 83868378.55 | 57370671.88 | 0.130029E+09 | 0.183038E+09 |
February | 0.196184E+09 | 0.121441E+09 | 74743521.61 | 0.207709E+09 | 0.145197E+09 |
March | 0.233649E+09 | 0.124602E+09 | 0.109046E+09 | 0.260529E+09 | 0.138420E+09 |
April | 0.238731E+09 | 0.103656E+09 | 0.135075E+09 | 0.281063E+09 | 0.114050E+09 |
May | 0.225565E+09 | 67198142.68 | 0.158367E+09 | 0.264998E+09 | 0.103486E+09 |
June | 0.199713E+09 | 53620423.71 | 0.146093E+09 | 0.238509E+09 | 80578194.91 |
July | 0.225056E+09 | 82427341.00 | 0.142628E+09 | 0.296029E+09 | 75463711.61 |
August | 0.241794E+09 | 0.112753E+09 | 0.129041E+09 | 0.327825E+09 | 73759630.71 |
September | 0.259256E+09 | 0.143170E+09 | 0.116086E+09 | 0.329422E+09 | 98424136.06 |
October | 0.242670E+09 | 0.149831E+09 | 92839157.57 | 0.284275E+09 | 0.129415E+09 |
November | 0.138846E+09 | 79570640.96 | 59275692.84 | 0.138153E+09 | 0.146437E+09 |
December | 0.150115E+09 | 97145650.36 | 52969808.28 | 0.152662E+09 | 0.185996E+09 |
Annual Sum or Average | 0.249282E+10 | 0.121928E+10 | 0.127354E+10 | 0.291120E+10 | 0.147426E+10 |
Minimum of Months | 0.138846E+09 | 53620423.71 | 52969808.28 | 0.130029E+09 | 73759630.71 |
Maximum of Months | 0.259256E+09 | 0.149831E+09 | 0.158367E+09 | 0.329422E+09 | 0.185996E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.141239E+09 | 83868378.55 | 57370671.88 | 0.130029E+09 | 0.183038E+09 |
February | 0.196184E+09 | 0.121441E+09 | 74743521.61 | 0.207709E+09 | 0.145197E+09 |
March | 0.233649E+09 | 0.124602E+09 | 0.109046E+09 | 0.260529E+09 | 0.138420E+09 |
April | 0.238731E+09 | 0.103656E+09 | 0.135075E+09 | 0.281063E+09 | 0.114050E+09 |
May | 0.225565E+09 | 67198142.68 | 0.158367E+09 | 0.264998E+09 | 0.103486E+09 |
June | 0.199713E+09 | 53620423.71 | 0.146093E+09 | 0.238509E+09 | 80578194.91 |
July | 0.225056E+09 | 82427341.00 | 0.142628E+09 | 0.296029E+09 | 75463711.61 |
August | 0.241794E+09 | 0.112753E+09 | 0.129041E+09 | 0.327825E+09 | 73759630.71 |
September | 0.259256E+09 | 0.143170E+09 | 0.116086E+09 | 0.329422E+09 | 98424136.06 |
October | 0.242670E+09 | 0.149831E+09 | 92839157.57 | 0.284275E+09 | 0.129415E+09 |
November | 0.138846E+09 | 79570640.96 | 59275692.84 | 0.138153E+09 | 0.146437E+09 |
December | 0.150115E+09 | 97145650.36 | 52969808.28 | 0.152662E+09 | 0.185996E+09 |
Annual Sum or Average | 0.249282E+10 | 0.121928E+10 | 0.127354E+10 | 0.291120E+10 | 0.147426E+10 |
Minimum of Months | 0.138846E+09 | 53620423.71 | 52969808.28 | 0.130029E+09 | 73759630.71 |
Maximum of Months | 0.259256E+09 | 0.149831E+09 | 0.158367E+09 | 0.329422E+09 | 0.185996E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.168863E+09 | 0.100272E+09 | 68591503.48 | 0.156239E+09 | 0.215978E+09 |
February | 0.234555E+09 | 0.145193E+09 | 89362218.61 | 0.249178E+09 | 0.171519E+09 |
March | 0.279347E+09 | 0.148973E+09 | 0.130374E+09 | 0.312310E+09 | 0.163525E+09 |
April | 0.285423E+09 | 0.123929E+09 | 0.161494E+09 | 0.336940E+09 | 0.134729E+09 |
May | 0.269682E+09 | 80341078.22 | 0.189341E+09 | 0.317695E+09 | 0.122323E+09 |
June | 0.238774E+09 | 64107763.75 | 0.174666E+09 | 0.285841E+09 | 95308293.83 |
July | 0.269073E+09 | 98548876.30 | 0.170524E+09 | 0.354314E+09 | 89371121.59 |
August | 0.289085E+09 | 0.134805E+09 | 0.154280E+09 | 0.392128E+09 | 87454581.00 |
September | 0.309962E+09 | 0.171171E+09 | 0.138791E+09 | 0.394061E+09 | 0.116722E+09 |
October | 0.290132E+09 | 0.179135E+09 | 0.110997E+09 | 0.340639E+09 | 0.153085E+09 |
November | 0.166003E+09 | 95133449.14 | 70869117.58 | 0.165776E+09 | 0.172907E+09 |
December | 0.179476E+09 | 0.116146E+09 | 63329897.83 | 0.183083E+09 | 0.219707E+09 |
Annual Sum or Average | 0.298038E+10 | 0.145776E+10 | 0.152262E+10 | 0.348820E+10 | 0.174263E+10 |
Minimum of Months | 0.166003E+09 | 64107763.75 | 63329897.83 | 0.156239E+09 | 87454581.00 |
Maximum of Months | 0.309962E+09 | 0.179135E+09 | 0.189341E+09 | 0.394061E+09 | 0.219707E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.141239E+09 | 83868378.55 | 57370671.88 | 0.130338E+09 | 0.180545E+09 |
February | 0.196184E+09 | 0.121441E+09 | 74743521.61 | 0.208182E+09 | 0.143165E+09 |
March | 0.233649E+09 | 0.124602E+09 | 0.109046E+09 | 0.261183E+09 | 0.135978E+09 |
April | 0.238731E+09 | 0.103656E+09 | 0.135075E+09 | 0.281936E+09 | 0.111902E+09 |
May | 0.225565E+09 | 67198142.68 | 0.158367E+09 | 0.265653E+09 | 0.102194E+09 |
June | 0.199713E+09 | 53620423.71 | 0.146093E+09 | 0.238727E+09 | 80070640.61 |
July | 0.225056E+09 | 82427341.00 | 0.142628E+09 | 0.296106E+09 | 75269850.98 |
August | 0.241794E+09 | 0.112753E+09 | 0.129041E+09 | 0.327852E+09 | 73694052.40 |
September | 0.259256E+09 | 0.143170E+09 | 0.116086E+09 | 0.329650E+09 | 97777006.27 |
October | 0.242670E+09 | 0.149831E+09 | 92839157.57 | 0.285003E+09 | 0.127091E+09 |
November | 0.138846E+09 | 79570640.96 | 59275692.84 | 0.138636E+09 | 0.144074E+09 |
December | 0.150115E+09 | 97145650.36 | 52969808.28 | 0.152953E+09 | 0.183704E+09 |
Annual Sum or Average | 0.249282E+10 | 0.121928E+10 | 0.127354E+10 | 0.291622E+10 | 0.145546E+10 |
Minimum of Months | 0.138846E+09 | 53620423.71 | 52969808.28 | 0.130338E+09 | 73694052.40 |
Maximum of Months | 0.259256E+09 | 0.149831E+09 | 0.158367E+09 | 0.329650E+09 | 0.183704E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.141239E+09 | 83868378.55 | 57370671.88 | 0.130338E+09 | 0.180545E+09 |
February | 0.196184E+09 | 0.121441E+09 | 74743521.61 | 0.208182E+09 | 0.143165E+09 |
March | 0.233649E+09 | 0.124602E+09 | 0.109046E+09 | 0.261183E+09 | 0.135978E+09 |
April | 0.238731E+09 | 0.103656E+09 | 0.135075E+09 | 0.281936E+09 | 0.111902E+09 |
May | 0.225565E+09 | 67198142.68 | 0.158367E+09 | 0.265653E+09 | 0.102194E+09 |
June | 0.199713E+09 | 53620423.71 | 0.146093E+09 | 0.238727E+09 | 80070640.61 |
July | 0.225056E+09 | 82427341.00 | 0.142628E+09 | 0.296106E+09 | 75269850.98 |
August | 0.241794E+09 | 0.112753E+09 | 0.129041E+09 | 0.327852E+09 | 73694052.40 |
September | 0.259256E+09 | 0.143170E+09 | 0.116086E+09 | 0.329650E+09 | 97777006.27 |
October | 0.242670E+09 | 0.149831E+09 | 92839157.57 | 0.285003E+09 | 0.127091E+09 |
November | 0.138846E+09 | 79570640.96 | 59275692.84 | 0.138636E+09 | 0.144074E+09 |
December | 0.150115E+09 | 97145650.36 | 52969808.28 | 0.152953E+09 | 0.183704E+09 |
Annual Sum or Average | 0.249282E+10 | 0.121928E+10 | 0.127354E+10 | 0.291622E+10 | 0.145546E+10 |
Minimum of Months | 0.138846E+09 | 53620423.71 | 52969808.28 | 0.130338E+09 | 73694052.40 |
Maximum of Months | 0.259256E+09 | 0.149831E+09 | 0.158367E+09 | 0.329650E+09 | 0.183704E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.168863E+09 | 0.100272E+09 | 68591503.48 | 0.156614E+09 | 0.213026E+09 |
February | 0.234555E+09 | 0.145193E+09 | 89362218.61 | 0.249748E+09 | 0.169115E+09 |
March | 0.279347E+09 | 0.148973E+09 | 0.130374E+09 | 0.313097E+09 | 0.160642E+09 |
April | 0.285423E+09 | 0.123929E+09 | 0.161494E+09 | 0.337982E+09 | 0.132196E+09 |
May | 0.269682E+09 | 80341078.22 | 0.189341E+09 | 0.318478E+09 | 0.120798E+09 |
June | 0.238774E+09 | 64107763.75 | 0.174666E+09 | 0.286102E+09 | 94708912.25 |
July | 0.269073E+09 | 98548876.30 | 0.170524E+09 | 0.354407E+09 | 89142916.77 |
August | 0.289085E+09 | 0.134805E+09 | 0.154280E+09 | 0.392161E+09 | 87377612.64 |
September | 0.309962E+09 | 0.171171E+09 | 0.138791E+09 | 0.394336E+09 | 0.115956E+09 |
October | 0.290132E+09 | 0.179135E+09 | 0.110997E+09 | 0.341507E+09 | 0.150341E+09 |
November | 0.166003E+09 | 95133449.14 | 70869117.58 | 0.166359E+09 | 0.170116E+09 |
December | 0.179476E+09 | 0.116146E+09 | 63329897.83 | 0.183434E+09 | 0.216987E+09 |
Annual Sum or Average | 0.298038E+10 | 0.145776E+10 | 0.152262E+10 | 0.349422E+10 | 0.172041E+10 |
Minimum of Months | 0.166003E+09 | 64107763.75 | 63329897.83 | 0.156614E+09 | 87377612.64 |
Maximum of Months | 0.309962E+09 | 0.179135E+09 | 0.189341E+09 | 0.394336E+09 | 0.216987E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.141239E+09 | 83868378.55 | 57370671.88 | 0.130735E+09 | 0.178353E+09 |
February | 0.196184E+09 | 0.121441E+09 | 74743521.61 | 0.208771E+09 | 0.141331E+09 |
March | 0.233649E+09 | 0.124602E+09 | 0.109046E+09 | 0.262062E+09 | 0.133477E+09 |
April | 0.238731E+09 | 0.103656E+09 | 0.135075E+09 | 0.283308E+09 | 0.109284E+09 |
May | 0.225565E+09 | 67198142.68 | 0.158367E+09 | 0.267272E+09 | 99729313.97 |
June | 0.199713E+09 | 53620423.71 | 0.146093E+09 | 0.239500E+09 | 78753854.35 |
July | 0.225056E+09 | 82427341.00 | 0.142628E+09 | 0.296528E+09 | 74348745.66 |
August | 0.241794E+09 | 0.112753E+09 | 0.129041E+09 | 0.328217E+09 | 72810807.63 |
September | 0.259256E+09 | 0.143170E+09 | 0.116086E+09 | 0.330398E+09 | 96220000.67 |
October | 0.242670E+09 | 0.149831E+09 | 92839157.57 | 0.286212E+09 | 0.124012E+09 |
November | 0.138846E+09 | 79570640.96 | 59275692.84 | 0.139268E+09 | 0.141756E+09 |
December | 0.150115E+09 | 97145650.36 | 52969808.28 | 0.153316E+09 | 0.181620E+09 |
Annual Sum or Average | 0.249282E+10 | 0.121928E+10 | 0.127354E+10 | 0.292559E+10 | 0.143169E+10 |
Minimum of Months | 0.138846E+09 | 53620423.71 | 52969808.28 | 0.130735E+09 | 72810807.63 |
Maximum of Months | 0.259256E+09 | 0.149831E+09 | 0.158367E+09 | 0.330398E+09 | 0.181620E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.141239E+09 | 83868378.55 | 57370671.88 | 0.130735E+09 | 0.178353E+09 |
February | 0.196184E+09 | 0.121441E+09 | 74743521.61 | 0.208771E+09 | 0.141331E+09 |
March | 0.233649E+09 | 0.124602E+09 | 0.109046E+09 | 0.262062E+09 | 0.133477E+09 |
April | 0.238731E+09 | 0.103656E+09 | 0.135075E+09 | 0.283308E+09 | 0.109284E+09 |
May | 0.225565E+09 | 67198142.68 | 0.158367E+09 | 0.267272E+09 | 99729313.97 |
June | 0.199713E+09 | 53620423.71 | 0.146093E+09 | 0.239500E+09 | 78753854.35 |
July | 0.225056E+09 | 82427341.00 | 0.142628E+09 | 0.296528E+09 | 74348745.66 |
August | 0.241794E+09 | 0.112753E+09 | 0.129041E+09 | 0.328217E+09 | 72810807.63 |
September | 0.259256E+09 | 0.143170E+09 | 0.116086E+09 | 0.330398E+09 | 96220000.67 |
October | 0.242670E+09 | 0.149831E+09 | 92839157.57 | 0.286212E+09 | 0.124012E+09 |
November | 0.138846E+09 | 79570640.96 | 59275692.84 | 0.139268E+09 | 0.141756E+09 |
December | 0.150115E+09 | 97145650.36 | 52969808.28 | 0.153316E+09 | 0.181620E+09 |
Annual Sum or Average | 0.249282E+10 | 0.121928E+10 | 0.127354E+10 | 0.292559E+10 | 0.143169E+10 |
Minimum of Months | 0.138846E+09 | 53620423.71 | 52969808.28 | 0.130735E+09 | 72810807.63 |
Maximum of Months | 0.259256E+09 | 0.149831E+09 | 0.158367E+09 | 0.330398E+09 | 0.181620E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.168863E+09 | 0.100272E+09 | 68591503.48 | 0.157098E+09 | 0.210431E+09 |
February | 0.234555E+09 | 0.145193E+09 | 89362218.61 | 0.250457E+09 | 0.166947E+09 |
March | 0.279347E+09 | 0.148973E+09 | 0.130374E+09 | 0.314151E+09 | 0.157690E+09 |
April | 0.285423E+09 | 0.123929E+09 | 0.161494E+09 | 0.339619E+09 | 0.129114E+09 |
May | 0.269682E+09 | 80341078.22 | 0.189341E+09 | 0.320407E+09 | 0.117895E+09 |
June | 0.238774E+09 | 64107763.75 | 0.174666E+09 | 0.287031E+09 | 93160827.93 |
July | 0.269073E+09 | 98548876.30 | 0.170524E+09 | 0.354917E+09 | 88061664.31 |
August | 0.289085E+09 | 0.134805E+09 | 0.154280E+09 | 0.392601E+09 | 86339288.30 |
September | 0.309962E+09 | 0.171171E+09 | 0.138791E+09 | 0.395232E+09 | 0.114116E+09 |
October | 0.290132E+09 | 0.179135E+09 | 0.110997E+09 | 0.342947E+09 | 0.146711E+09 |
November | 0.166003E+09 | 95133449.14 | 70869117.58 | 0.167117E+09 | 0.167379E+09 |
December | 0.179476E+09 | 0.116146E+09 | 63329897.83 | 0.183873E+09 | 0.214514E+09 |
Annual Sum or Average | 0.298038E+10 | 0.145776E+10 | 0.152262E+10 | 0.350545E+10 | 0.169236E+10 |
Minimum of Months | 0.166003E+09 | 64107763.75 | 63329897.83 | 0.157098E+09 | 86339288.30 |
Maximum of Months | 0.309962E+09 | 0.179135E+09 | 0.189341E+09 | 0.395232E+09 | 0.214514E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.141239E+09 | 83868378.55 | 57370671.88 | 0.132008E+09 | 0.172172E+09 |
February | 0.196184E+09 | 0.121441E+09 | 74743521.61 | 0.210511E+09 | 0.136471E+09 |
March | 0.233649E+09 | 0.124602E+09 | 0.109046E+09 | 0.264182E+09 | 0.127959E+09 |
April | 0.238731E+09 | 0.103656E+09 | 0.135075E+09 | 0.286406E+09 | 0.103648E+09 |
May | 0.225565E+09 | 67198142.68 | 0.158367E+09 | 0.271346E+09 | 93760964.56 |
June | 0.199713E+09 | 53620423.71 | 0.146093E+09 | 0.241768E+09 | 74965256.41 |
July | 0.225056E+09 | 82427341.00 | 0.142628E+09 | 0.297494E+09 | 71569259.11 |
August | 0.241794E+09 | 0.112753E+09 | 0.129041E+09 | 0.328927E+09 | 70015815.12 |
September | 0.259256E+09 | 0.143170E+09 | 0.116086E+09 | 0.332407E+09 | 92075634.06 |
October | 0.242670E+09 | 0.149831E+09 | 92839157.57 | 0.288987E+09 | 0.117686E+09 |
November | 0.138846E+09 | 79570640.96 | 59275692.84 | 0.140735E+09 | 0.136249E+09 |
December | 0.150115E+09 | 97145650.36 | 52969808.28 | 0.154444E+09 | 0.175786E+09 |
Annual Sum or Average | 0.249282E+10 | 0.121928E+10 | 0.127354E+10 | 0.294921E+10 | 0.137236E+10 |
Minimum of Months | 0.138846E+09 | 53620423.71 | 52969808.28 | 0.132008E+09 | 70015815.12 |
Maximum of Months | 0.259256E+09 | 0.149831E+09 | 0.158367E+09 | 0.332407E+09 | 0.175786E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.141239E+09 | 83868378.55 | 57370671.88 | 0.132008E+09 | 0.172172E+09 |
February | 0.196184E+09 | 0.121441E+09 | 74743521.61 | 0.210511E+09 | 0.136471E+09 |
March | 0.233649E+09 | 0.124602E+09 | 0.109046E+09 | 0.264182E+09 | 0.127959E+09 |
April | 0.238731E+09 | 0.103656E+09 | 0.135075E+09 | 0.286406E+09 | 0.103648E+09 |
May | 0.225565E+09 | 67198142.68 | 0.158367E+09 | 0.271346E+09 | 93760964.56 |
June | 0.199713E+09 | 53620423.71 | 0.146093E+09 | 0.241768E+09 | 74965256.41 |
July | 0.225056E+09 | 82427341.00 | 0.142628E+09 | 0.297494E+09 | 71569259.11 |
August | 0.241794E+09 | 0.112753E+09 | 0.129041E+09 | 0.328927E+09 | 70015815.12 |
September | 0.259256E+09 | 0.143170E+09 | 0.116086E+09 | 0.332407E+09 | 92075634.06 |
October | 0.242670E+09 | 0.149831E+09 | 92839157.57 | 0.288987E+09 | 0.117686E+09 |
November | 0.138846E+09 | 79570640.96 | 59275692.84 | 0.140735E+09 | 0.136249E+09 |
December | 0.150115E+09 | 97145650.36 | 52969808.28 | 0.154444E+09 | 0.175786E+09 |
Annual Sum or Average | 0.249282E+10 | 0.121928E+10 | 0.127354E+10 | 0.294921E+10 | 0.137236E+10 |
Minimum of Months | 0.138846E+09 | 53620423.71 | 52969808.28 | 0.132008E+09 | 70015815.12 |
Maximum of Months | 0.259256E+09 | 0.149831E+09 | 0.158367E+09 | 0.332407E+09 | 0.175786E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.141239E+09 | 83868378.55 | 57370671.88 | 0.132008E+09 | 0.172172E+09 |
February | 0.196184E+09 | 0.121441E+09 | 74743521.61 | 0.210511E+09 | 0.136471E+09 |
March | 0.233649E+09 | 0.124602E+09 | 0.109046E+09 | 0.264182E+09 | 0.127959E+09 |
April | 0.238731E+09 | 0.103656E+09 | 0.135075E+09 | 0.286406E+09 | 0.103648E+09 |
May | 0.225565E+09 | 67198142.68 | 0.158367E+09 | 0.271346E+09 | 93760964.56 |
June | 0.199713E+09 | 53620423.71 | 0.146093E+09 | 0.241768E+09 | 74965256.41 |
July | 0.225056E+09 | 82427341.00 | 0.142628E+09 | 0.297494E+09 | 71569259.11 |
August | 0.241794E+09 | 0.112753E+09 | 0.129041E+09 | 0.328927E+09 | 70015815.12 |
September | 0.259256E+09 | 0.143170E+09 | 0.116086E+09 | 0.332407E+09 | 92075634.06 |
October | 0.242670E+09 | 0.149831E+09 | 92839157.57 | 0.288987E+09 | 0.117686E+09 |
November | 0.138846E+09 | 79570640.96 | 59275692.84 | 0.140735E+09 | 0.136249E+09 |
December | 0.150115E+09 | 97145650.36 | 52969808.28 | 0.154444E+09 | 0.175786E+09 |
Annual Sum or Average | 0.249282E+10 | 0.121928E+10 | 0.127354E+10 | 0.294921E+10 | 0.137236E+10 |
Minimum of Months | 0.138846E+09 | 53620423.71 | 52969808.28 | 0.132008E+09 | 70015815.12 |
Maximum of Months | 0.259256E+09 | 0.149831E+09 | 0.158367E+09 | 0.332407E+09 | 0.175786E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.141239E+09 | 83868378.55 | 57370671.88 | 0.132008E+09 | 0.172172E+09 |
February | 0.196184E+09 | 0.121441E+09 | 74743521.61 | 0.210511E+09 | 0.136471E+09 |
March | 0.233649E+09 | 0.124602E+09 | 0.109046E+09 | 0.264182E+09 | 0.127959E+09 |
April | 0.238731E+09 | 0.103656E+09 | 0.135075E+09 | 0.286406E+09 | 0.103648E+09 |
May | 0.225565E+09 | 67198142.68 | 0.158367E+09 | 0.271346E+09 | 93760964.56 |
June | 0.199713E+09 | 53620423.71 | 0.146093E+09 | 0.241768E+09 | 74965256.41 |
July | 0.225056E+09 | 82427341.00 | 0.142628E+09 | 0.297494E+09 | 71569259.11 |
August | 0.241794E+09 | 0.112753E+09 | 0.129041E+09 | 0.328927E+09 | 70015815.12 |
September | 0.259256E+09 | 0.143170E+09 | 0.116086E+09 | 0.332407E+09 | 92075634.06 |
October | 0.242670E+09 | 0.149831E+09 | 92839157.57 | 0.288987E+09 | 0.117686E+09 |
November | 0.138846E+09 | 79570640.96 | 59275692.84 | 0.140735E+09 | 0.136249E+09 |
December | 0.150115E+09 | 97145650.36 | 52969808.28 | 0.154444E+09 | 0.175786E+09 |
Annual Sum or Average | 0.249282E+10 | 0.121928E+10 | 0.127354E+10 | 0.294921E+10 | 0.137236E+10 |
Minimum of Months | 0.138846E+09 | 53620423.71 | 52969808.28 | 0.132008E+09 | 70015815.12 |
Maximum of Months | 0.259256E+09 | 0.149831E+09 | 0.158367E+09 | 0.332407E+09 | 0.175786E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.168863E+09 | 0.100272E+09 | 68591503.48 | 0.158592E+09 | 0.203219E+09 |
February | 0.234555E+09 | 0.145193E+09 | 89362218.61 | 0.252482E+09 | 0.161275E+09 |
March | 0.279347E+09 | 0.148973E+09 | 0.130374E+09 | 0.316611E+09 | 0.151239E+09 |
April | 0.285423E+09 | 0.123929E+09 | 0.161494E+09 | 0.343216E+09 | 0.122529E+09 |
May | 0.269682E+09 | 80341078.22 | 0.189341E+09 | 0.325153E+09 | 0.110916E+09 |
June | 0.238774E+09 | 64107763.75 | 0.174666E+09 | 0.289656E+09 | 88731272.50 |
July | 0.269073E+09 | 98548876.30 | 0.170524E+09 | 0.356009E+09 | 84805589.33 |
August | 0.289085E+09 | 0.134805E+09 | 0.154280E+09 | 0.393395E+09 | 83054770.18 |
September | 0.309962E+09 | 0.171171E+09 | 0.138791E+09 | 0.397565E+09 | 0.109237E+09 |
October | 0.290132E+09 | 0.179135E+09 | 0.110997E+09 | 0.346167E+09 | 0.139298E+09 |
November | 0.166003E+09 | 95133449.14 | 70869117.58 | 0.168834E+09 | 0.160938E+09 |
December | 0.179476E+09 | 0.116146E+09 | 63329897.83 | 0.185191E+09 | 0.207681E+09 |
Annual Sum or Average | 0.298038E+10 | 0.145776E+10 | 0.152262E+10 | 0.353287E+10 | 0.162292E+10 |
Minimum of Months | 0.166003E+09 | 64107763.75 | 63329897.83 | 0.158592E+09 | 83054770.18 |
Maximum of Months | 0.309962E+09 | 0.179135E+09 | 0.189341E+09 | 0.397565E+09 | 0.207681E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.168863E+09 | 0.100272E+09 | 68591503.48 | 0.158592E+09 | 0.203219E+09 |
February | 0.234555E+09 | 0.145193E+09 | 89362218.61 | 0.252482E+09 | 0.161275E+09 |
March | 0.279347E+09 | 0.148973E+09 | 0.130374E+09 | 0.316611E+09 | 0.151239E+09 |
April | 0.285423E+09 | 0.123929E+09 | 0.161494E+09 | 0.343216E+09 | 0.122529E+09 |
May | 0.269682E+09 | 80341078.22 | 0.189341E+09 | 0.325153E+09 | 0.110916E+09 |
June | 0.238774E+09 | 64107763.75 | 0.174666E+09 | 0.289656E+09 | 88731272.50 |
July | 0.269073E+09 | 98548876.30 | 0.170524E+09 | 0.356009E+09 | 84805589.33 |
August | 0.289085E+09 | 0.134805E+09 | 0.154280E+09 | 0.393395E+09 | 83054770.18 |
September | 0.309962E+09 | 0.171171E+09 | 0.138791E+09 | 0.397565E+09 | 0.109237E+09 |
October | 0.290132E+09 | 0.179135E+09 | 0.110997E+09 | 0.346167E+09 | 0.139298E+09 |
November | 0.166003E+09 | 95133449.14 | 70869117.58 | 0.168834E+09 | 0.160938E+09 |
December | 0.179476E+09 | 0.116146E+09 | 63329897.83 | 0.185191E+09 | 0.207681E+09 |
Annual Sum or Average | 0.298038E+10 | 0.145776E+10 | 0.152262E+10 | 0.353287E+10 | 0.162292E+10 |
Minimum of Months | 0.166003E+09 | 64107763.75 | 63329897.83 | 0.158592E+09 | 83054770.18 |
Maximum of Months | 0.309962E+09 | 0.179135E+09 | 0.189341E+09 | 0.397565E+09 | 0.207681E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.141239E+09 | 83868378.55 | 57370671.88 | 0.131444E+09 | 0.173132E+09 |
February | 0.196184E+09 | 0.121441E+09 | 74743521.61 | 0.209850E+09 | 0.136998E+09 |
March | 0.233649E+09 | 0.124602E+09 | 0.109046E+09 | 0.263421E+09 | 0.128312E+09 |
April | 0.238731E+09 | 0.103656E+09 | 0.135075E+09 | 0.285292E+09 | 0.104104E+09 |
May | 0.225565E+09 | 67198142.68 | 0.158367E+09 | 0.269805E+09 | 94561215.14 |
June | 0.199713E+09 | 53620423.71 | 0.146093E+09 | 0.240703E+09 | 75251036.91 |
July | 0.225056E+09 | 82427341.00 | 0.142628E+09 | 0.296959E+09 | 71352707.66 |
August | 0.241794E+09 | 0.112753E+09 | 0.129041E+09 | 0.328489E+09 | 69683348.57 |
September | 0.259256E+09 | 0.143170E+09 | 0.116086E+09 | 0.331387E+09 | 92548686.61 |
October | 0.242670E+09 | 0.149831E+09 | 92839157.57 | 0.287809E+09 | 0.118433E+09 |
November | 0.138846E+09 | 79570640.96 | 59275692.84 | 0.140258E+09 | 0.136781E+09 |
December | 0.150115E+09 | 97145650.36 | 52969808.28 | 0.154015E+09 | 0.176590E+09 |
Annual Sum or Average | 0.249282E+10 | 0.121928E+10 | 0.127354E+10 | 0.293943E+10 | 0.137775E+10 |
Minimum of Months | 0.138846E+09 | 53620423.71 | 52969808.28 | 0.131444E+09 | 69683348.57 |
Maximum of Months | 0.259256E+09 | 0.149831E+09 | 0.158367E+09 | 0.331387E+09 | 0.176590E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.141239E+09 | 83868378.55 | 57370671.88 | 0.131444E+09 | 0.173132E+09 |
February | 0.196184E+09 | 0.121441E+09 | 74743521.61 | 0.209850E+09 | 0.136998E+09 |
March | 0.233649E+09 | 0.124602E+09 | 0.109046E+09 | 0.263421E+09 | 0.128312E+09 |
April | 0.238731E+09 | 0.103656E+09 | 0.135075E+09 | 0.285292E+09 | 0.104104E+09 |
May | 0.225565E+09 | 67198142.68 | 0.158367E+09 | 0.269805E+09 | 94561215.14 |
June | 0.199713E+09 | 53620423.71 | 0.146093E+09 | 0.240703E+09 | 75251036.91 |
July | 0.225056E+09 | 82427341.00 | 0.142628E+09 | 0.296959E+09 | 71352707.66 |
August | 0.241794E+09 | 0.112753E+09 | 0.129041E+09 | 0.328489E+09 | 69683348.57 |
September | 0.259256E+09 | 0.143170E+09 | 0.116086E+09 | 0.331387E+09 | 92548686.61 |
October | 0.242670E+09 | 0.149831E+09 | 92839157.57 | 0.287809E+09 | 0.118433E+09 |
November | 0.138846E+09 | 79570640.96 | 59275692.84 | 0.140258E+09 | 0.136781E+09 |
December | 0.150115E+09 | 97145650.36 | 52969808.28 | 0.154015E+09 | 0.176590E+09 |
Annual Sum or Average | 0.249282E+10 | 0.121928E+10 | 0.127354E+10 | 0.293943E+10 | 0.137775E+10 |
Minimum of Months | 0.138846E+09 | 53620423.71 | 52969808.28 | 0.131444E+09 | 69683348.57 |
Maximum of Months | 0.259256E+09 | 0.149831E+09 | 0.158367E+09 | 0.331387E+09 | 0.176590E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.168863E+09 | 0.100272E+09 | 68591503.48 | 0.157977E+09 | 0.204252E+09 |
February | 0.234555E+09 | 0.145193E+09 | 89362218.61 | 0.251773E+09 | 0.161823E+09 |
March | 0.279347E+09 | 0.148973E+09 | 0.130374E+09 | 0.315800E+09 | 0.151586E+09 |
April | 0.285423E+09 | 0.123929E+09 | 0.161494E+09 | 0.342003E+09 | 0.123007E+09 |
May | 0.269682E+09 | 80341078.22 | 0.189341E+09 | 0.323444E+09 | 0.111806E+09 |
June | 0.238774E+09 | 64107763.75 | 0.174666E+09 | 0.288491E+09 | 89032724.38 |
July | 0.269073E+09 | 98548876.30 | 0.170524E+09 | 0.355463E+09 | 84525866.85 |
August | 0.289085E+09 | 0.134805E+09 | 0.154280E+09 | 0.392958E+09 | 82645359.23 |
September | 0.309962E+09 | 0.171171E+09 | 0.138791E+09 | 0.396439E+09 | 0.109764E+09 |
October | 0.290132E+09 | 0.179135E+09 | 0.110997E+09 | 0.344869E+09 | 0.140122E+09 |
November | 0.166003E+09 | 95133449.14 | 70869117.58 | 0.168321E+09 | 0.161491E+09 |
December | 0.179476E+09 | 0.116146E+09 | 63329897.83 | 0.184731E+09 | 0.208543E+09 |
Annual Sum or Average | 0.298038E+10 | 0.145776E+10 | 0.152262E+10 | 0.352227E+10 | 0.162860E+10 |
Minimum of Months | 0.166003E+09 | 64107763.75 | 63329897.83 | 0.157977E+09 | 82645359.23 |
Maximum of Months | 0.309962E+09 | 0.179135E+09 | 0.189341E+09 | 0.396439E+09 | 0.208543E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.141239E+09 | 83868378.55 | 57370671.88 | 0.131554E+09 | 0.172532E+09 |
February | 0.196184E+09 | 0.121441E+09 | 74743521.61 | 0.210031E+09 | 0.136429E+09 |
March | 0.233649E+09 | 0.124602E+09 | 0.109046E+09 | 0.263663E+09 | 0.127619E+09 |
April | 0.238731E+09 | 0.103656E+09 | 0.135075E+09 | 0.285614E+09 | 0.103496E+09 |
May | 0.225565E+09 | 67198142.68 | 0.158367E+09 | 0.270240E+09 | 93960498.97 |
June | 0.199713E+09 | 53620423.71 | 0.146093E+09 | 0.240994E+09 | 74860388.05 |
July | 0.225056E+09 | 82427341.00 | 0.142628E+09 | 0.297171E+09 | 71015806.70 |
August | 0.241794E+09 | 0.112753E+09 | 0.129041E+09 | 0.328657E+09 | 69382924.06 |
September | 0.259256E+09 | 0.143170E+09 | 0.116086E+09 | 0.331594E+09 | 92161388.37 |
October | 0.242670E+09 | 0.149831E+09 | 92839157.57 | 0.288069E+09 | 0.117821E+09 |
November | 0.138846E+09 | 79570640.96 | 59275692.84 | 0.140418E+09 | 0.136163E+09 |
December | 0.150115E+09 | 97145650.36 | 52969808.28 | 0.154131E+09 | 0.175983E+09 |
Annual Sum or Average | 0.249282E+10 | 0.121928E+10 | 0.127354E+10 | 0.294214E+10 | 0.137142E+10 |
Minimum of Months | 0.138846E+09 | 53620423.71 | 52969808.28 | 0.131554E+09 | 69382924.06 |
Maximum of Months | 0.259256E+09 | 0.149831E+09 | 0.158367E+09 | 0.331594E+09 | 0.175983E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.141239E+09 | 83868378.55 | 57370671.88 | 0.131554E+09 | 0.172532E+09 |
February | 0.196184E+09 | 0.121441E+09 | 74743521.61 | 0.210031E+09 | 0.136429E+09 |
March | 0.233649E+09 | 0.124602E+09 | 0.109046E+09 | 0.263663E+09 | 0.127619E+09 |
April | 0.238731E+09 | 0.103656E+09 | 0.135075E+09 | 0.285614E+09 | 0.103496E+09 |
May | 0.225565E+09 | 67198142.68 | 0.158367E+09 | 0.270240E+09 | 93960498.97 |
June | 0.199713E+09 | 53620423.71 | 0.146093E+09 | 0.240994E+09 | 74860388.05 |
July | 0.225056E+09 | 82427341.00 | 0.142628E+09 | 0.297171E+09 | 71015806.70 |
August | 0.241794E+09 | 0.112753E+09 | 0.129041E+09 | 0.328657E+09 | 69382924.06 |
September | 0.259256E+09 | 0.143170E+09 | 0.116086E+09 | 0.331594E+09 | 92161388.37 |
October | 0.242670E+09 | 0.149831E+09 | 92839157.57 | 0.288069E+09 | 0.117821E+09 |
November | 0.138846E+09 | 79570640.96 | 59275692.84 | 0.140418E+09 | 0.136163E+09 |
December | 0.150115E+09 | 97145650.36 | 52969808.28 | 0.154131E+09 | 0.175983E+09 |
Annual Sum or Average | 0.249282E+10 | 0.121928E+10 | 0.127354E+10 | 0.294214E+10 | 0.137142E+10 |
Minimum of Months | 0.138846E+09 | 53620423.71 | 52969808.28 | 0.131554E+09 | 69382924.06 |
Maximum of Months | 0.259256E+09 | 0.149831E+09 | 0.158367E+09 | 0.331594E+09 | 0.175983E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.168863E+09 | 0.100272E+09 | 68591503.48 | 0.158111E+09 | 0.203541E+09 |
February | 0.234555E+09 | 0.145193E+09 | 89362218.61 | 0.251991E+09 | 0.161149E+09 |
March | 0.279347E+09 | 0.148973E+09 | 0.130374E+09 | 0.316091E+09 | 0.150766E+09 |
April | 0.285423E+09 | 0.123929E+09 | 0.161494E+09 | 0.342390E+09 | 0.122291E+09 |
May | 0.269682E+09 | 80341078.22 | 0.189341E+09 | 0.323963E+09 | 0.111097E+09 |
June | 0.238774E+09 | 64107763.75 | 0.174666E+09 | 0.288839E+09 | 88572047.78 |
July | 0.269073E+09 | 98548876.30 | 0.170524E+09 | 0.355718E+09 | 84128481.64 |
August | 0.289085E+09 | 0.134805E+09 | 0.154280E+09 | 0.393162E+09 | 82290966.52 |
September | 0.309962E+09 | 0.171171E+09 | 0.138791E+09 | 0.396687E+09 | 0.109306E+09 |
October | 0.290132E+09 | 0.179135E+09 | 0.110997E+09 | 0.345179E+09 | 0.139400E+09 |
November | 0.166003E+09 | 95133449.14 | 70869117.58 | 0.168515E+09 | 0.160757E+09 |
December | 0.179476E+09 | 0.116146E+09 | 63329897.83 | 0.184871E+09 | 0.207822E+09 |
Annual Sum or Average | 0.298038E+10 | 0.145776E+10 | 0.152262E+10 | 0.352552E+10 | 0.162112E+10 |
Minimum of Months | 0.166003E+09 | 64107763.75 | 63329897.83 | 0.158111E+09 | 82290966.52 |
Maximum of Months | 0.309962E+09 | 0.179135E+09 | 0.189341E+09 | 0.396687E+09 | 0.207822E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.141239E+09 | 83868378.55 | 57370671.88 | 0.131988E+09 | 0.169838E+09 |
February | 0.196184E+09 | 0.121441E+09 | 74743521.61 | 0.210681E+09 | 0.134083E+09 |
March | 0.233649E+09 | 0.124602E+09 | 0.109046E+09 | 0.264459E+09 | 0.124994E+09 |
April | 0.238731E+09 | 0.103656E+09 | 0.135075E+09 | 0.286710E+09 | 0.101125E+09 |
May | 0.225565E+09 | 67198142.68 | 0.158367E+09 | 0.271926E+09 | 91391987.09 |
June | 0.199713E+09 | 53620423.71 | 0.146093E+09 | 0.242134E+09 | 73224003.43 |
July | 0.225056E+09 | 82427341.00 | 0.142628E+09 | 0.297814E+09 | 69859314.10 |
August | 0.241794E+09 | 0.112753E+09 | 0.129041E+09 | 0.329113E+09 | 68420020.64 |
September | 0.259256E+09 | 0.143170E+09 | 0.116086E+09 | 0.332497E+09 | 90375627.94 |
October | 0.242670E+09 | 0.149831E+09 | 92839157.57 | 0.289074E+09 | 0.115280E+09 |
November | 0.138846E+09 | 79570640.96 | 59275692.84 | 0.140941E+09 | 0.133865E+09 |
December | 0.150115E+09 | 97145650.36 | 52969808.28 | 0.154552E+09 | 0.173420E+09 |
Annual Sum or Average | 0.249282E+10 | 0.121928E+10 | 0.127354E+10 | 0.295189E+10 | 0.134588E+10 |
Minimum of Months | 0.138846E+09 | 53620423.71 | 52969808.28 | 0.131988E+09 | 68420020.64 |
Maximum of Months | 0.259256E+09 | 0.149831E+09 | 0.158367E+09 | 0.332497E+09 | 0.173420E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.141239E+09 | 83868378.55 | 57370671.88 | 0.131988E+09 | 0.169838E+09 |
February | 0.196184E+09 | 0.121441E+09 | 74743521.61 | 0.210681E+09 | 0.134083E+09 |
March | 0.233649E+09 | 0.124602E+09 | 0.109046E+09 | 0.264459E+09 | 0.124994E+09 |
April | 0.238731E+09 | 0.103656E+09 | 0.135075E+09 | 0.286710E+09 | 0.101125E+09 |
May | 0.225565E+09 | 67198142.68 | 0.158367E+09 | 0.271926E+09 | 91391987.09 |
June | 0.199713E+09 | 53620423.71 | 0.146093E+09 | 0.242134E+09 | 73224003.43 |
July | 0.225056E+09 | 82427341.00 | 0.142628E+09 | 0.297814E+09 | 69859314.10 |
August | 0.241794E+09 | 0.112753E+09 | 0.129041E+09 | 0.329113E+09 | 68420020.64 |
September | 0.259256E+09 | 0.143170E+09 | 0.116086E+09 | 0.332497E+09 | 90375627.94 |
October | 0.242670E+09 | 0.149831E+09 | 92839157.57 | 0.289074E+09 | 0.115280E+09 |
November | 0.138846E+09 | 79570640.96 | 59275692.84 | 0.140941E+09 | 0.133865E+09 |
December | 0.150115E+09 | 97145650.36 | 52969808.28 | 0.154552E+09 | 0.173420E+09 |
Annual Sum or Average | 0.249282E+10 | 0.121928E+10 | 0.127354E+10 | 0.295189E+10 | 0.134588E+10 |
Minimum of Months | 0.138846E+09 | 53620423.71 | 52969808.28 | 0.131988E+09 | 68420020.64 |
Maximum of Months | 0.259256E+09 | 0.149831E+09 | 0.158367E+09 | 0.332497E+09 | 0.173420E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.168863E+09 | 0.100272E+09 | 68591503.48 | 0.158638E+09 | 0.200355E+09 |
February | 0.234555E+09 | 0.145193E+09 | 89362218.61 | 0.252779E+09 | 0.158378E+09 |
March | 0.279347E+09 | 0.148973E+09 | 0.130374E+09 | 0.317052E+09 | 0.147667E+09 |
April | 0.285423E+09 | 0.123929E+09 | 0.161494E+09 | 0.343703E+09 | 0.119501E+09 |
May | 0.269682E+09 | 80341078.22 | 0.189341E+09 | 0.325971E+09 | 0.108073E+09 |
June | 0.238774E+09 | 64107763.75 | 0.174666E+09 | 0.290199E+09 | 86647646.28 |
July | 0.269073E+09 | 98548876.30 | 0.170524E+09 | 0.356490E+09 | 82767664.43 |
August | 0.289085E+09 | 0.134805E+09 | 0.154280E+09 | 0.393710E+09 | 81159527.43 |
September | 0.309962E+09 | 0.171171E+09 | 0.138791E+09 | 0.397765E+09 | 0.107197E+09 |
October | 0.290132E+09 | 0.179135E+09 | 0.110997E+09 | 0.346381E+09 | 0.136405E+09 |
November | 0.166003E+09 | 95133449.14 | 70869117.58 | 0.169145E+09 | 0.158042E+09 |
December | 0.179476E+09 | 0.116146E+09 | 63329897.83 | 0.185378E+09 | 0.204785E+09 |
Annual Sum or Average | 0.298038E+10 | 0.145776E+10 | 0.152262E+10 | 0.353721E+10 | 0.159098E+10 |
Minimum of Months | 0.166003E+09 | 64107763.75 | 63329897.83 | 0.158638E+09 | 81159527.43 |
Maximum of Months | 0.309962E+09 | 0.179135E+09 | 0.189341E+09 | 0.397765E+09 | 0.204785E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.141239E+09 | 83868378.55 | 57370671.88 | 0.133753E+09 | 0.158741E+09 |
February | 0.196184E+09 | 0.121441E+09 | 74743521.61 | 0.212993E+09 | 0.124773E+09 |
March | 0.233649E+09 | 0.124602E+09 | 0.109046E+09 | 0.266952E+09 | 0.115222E+09 |
April | 0.238731E+09 | 0.103656E+09 | 0.135075E+09 | 0.289348E+09 | 92963804.16 |
May | 0.225565E+09 | 67198142.68 | 0.158367E+09 | 0.275490E+09 | 83653744.12 |
June | 0.199713E+09 | 53620423.71 | 0.146093E+09 | 0.244736E+09 | 67663145.72 |
July | 0.225056E+09 | 82427341.00 | 0.142628E+09 | 0.299463E+09 | 65417801.50 |
August | 0.241794E+09 | 0.112753E+09 | 0.129041E+09 | 0.330142E+09 | 64624687.28 |
September | 0.259256E+09 | 0.143170E+09 | 0.116086E+09 | 0.334645E+09 | 84688245.75 |
October | 0.242670E+09 | 0.149831E+09 | 92839157.57 | 0.291476E+09 | 0.107360E+09 |
November | 0.138846E+09 | 79570640.96 | 59275692.84 | 0.142559E+09 | 0.125566E+09 |
December | 0.150115E+09 | 97145650.36 | 52969808.28 | 0.156114E+09 | 0.163081E+09 |
Annual Sum or Average | 0.249282E+10 | 0.121928E+10 | 0.127354E+10 | 0.297767E+10 | 0.125375E+10 |
Minimum of Months | 0.138846E+09 | 53620423.71 | 52969808.28 | 0.133753E+09 | 64624687.28 |
Maximum of Months | 0.259256E+09 | 0.149831E+09 | 0.158367E+09 | 0.334645E+09 | 0.163081E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.141239E+09 | 83868378.55 | 57370671.88 | 0.133753E+09 | 0.158741E+09 |
February | 0.196184E+09 | 0.121441E+09 | 74743521.61 | 0.212993E+09 | 0.124773E+09 |
March | 0.233649E+09 | 0.124602E+09 | 0.109046E+09 | 0.266952E+09 | 0.115222E+09 |
April | 0.238731E+09 | 0.103656E+09 | 0.135075E+09 | 0.289348E+09 | 92963804.16 |
May | 0.225565E+09 | 67198142.68 | 0.158367E+09 | 0.275490E+09 | 83653744.12 |
June | 0.199713E+09 | 53620423.71 | 0.146093E+09 | 0.244736E+09 | 67663145.72 |
July | 0.225056E+09 | 82427341.00 | 0.142628E+09 | 0.299463E+09 | 65417801.50 |
August | 0.241794E+09 | 0.112753E+09 | 0.129041E+09 | 0.330142E+09 | 64624687.28 |
September | 0.259256E+09 | 0.143170E+09 | 0.116086E+09 | 0.334645E+09 | 84688245.75 |
October | 0.242670E+09 | 0.149831E+09 | 92839157.57 | 0.291476E+09 | 0.107360E+09 |
November | 0.138846E+09 | 79570640.96 | 59275692.84 | 0.142559E+09 | 0.125566E+09 |
December | 0.150115E+09 | 97145650.36 | 52969808.28 | 0.156114E+09 | 0.163081E+09 |
Annual Sum or Average | 0.249282E+10 | 0.121928E+10 | 0.127354E+10 | 0.297767E+10 | 0.125375E+10 |
Minimum of Months | 0.138846E+09 | 53620423.71 | 52969808.28 | 0.133753E+09 | 64624687.28 |
Maximum of Months | 0.259256E+09 | 0.149831E+09 | 0.158367E+09 | 0.334645E+09 | 0.163081E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.168863E+09 | 0.100272E+09 | 68591503.48 | 0.160788E+09 | 0.187246E+09 |
February | 0.234555E+09 | 0.145193E+09 | 89362218.61 | 0.255574E+09 | 0.147381E+09 |
March | 0.279347E+09 | 0.148973E+09 | 0.130374E+09 | 0.320078E+09 | 0.136147E+09 |
April | 0.285423E+09 | 0.123929E+09 | 0.161494E+09 | 0.346875E+09 | 0.109899E+09 |
May | 0.269682E+09 | 80341078.22 | 0.189341E+09 | 0.330232E+09 | 98970410.27 |
June | 0.238774E+09 | 64107763.75 | 0.174666E+09 | 0.293302E+09 | 80114495.28 |
July | 0.269073E+09 | 98548876.30 | 0.170524E+09 | 0.358462E+09 | 77546609.89 |
August | 0.289085E+09 | 0.134805E+09 | 0.154280E+09 | 0.394939E+09 | 76693564.46 |
September | 0.309962E+09 | 0.171171E+09 | 0.138791E+09 | 0.400329E+09 | 0.100480E+09 |
October | 0.290132E+09 | 0.179135E+09 | 0.110997E+09 | 0.349262E+09 | 0.127070E+09 |
November | 0.166003E+09 | 95133449.14 | 70869117.58 | 0.171103E+09 | 0.148240E+09 |
December | 0.179476E+09 | 0.116146E+09 | 63329897.83 | 0.187273E+09 | 0.192546E+09 |
Annual Sum or Average | 0.298038E+10 | 0.145776E+10 | 0.152262E+10 | 0.356822E+10 | 0.148233E+10 |
Minimum of Months | 0.166003E+09 | 64107763.75 | 63329897.83 | 0.160788E+09 | 76693564.46 |
Maximum of Months | 0.309962E+09 | 0.179135E+09 | 0.189341E+09 | 0.400329E+09 | 0.192546E+09 |
Report: WindowZoneSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 315.54 | 422.02 | 337.72 | 200.54 | 137.18 | 0.00 | 0.00 |
February | 556.70 | 368.18 | 519.36 | 321.49 | 197.87 | 0.00 | 0.00 |
March | 631.91 | 309.02 | 558.68 | 297.94 | 260.74 | 0.00 | 0.00 |
April | 707.42 | 259.06 | 589.86 | 256.11 | 333.74 | 0.00 | 0.00 |
May | 648.81 | 224.71 | 539.35 | 160.68 | 378.67 | 0.00 | 0.00 |
June | 598.72 | 183.61 | 493.45 | 132.49 | 360.97 | 0.00 | 0.00 |
July | 712.99 | 168.08 | 538.13 | 197.09 | 341.04 | 0.00 | 0.00 |
August | 788.10 | 163.87 | 578.15 | 269.60 | 308.55 | 0.00 | 0.00 |
September | 821.31 | 227.41 | 640.57 | 353.74 | 286.83 | 0.00 | 0.00 |
October | 690.23 | 285.28 | 580.25 | 358.26 | 221.99 | 0.00 | 0.00 |
November | 346.64 | 344.56 | 343.06 | 196.60 | 146.46 | 0.00 | 0.00 |
December | 368.89 | 428.28 | 358.94 | 232.28 | 126.66 | 0.00 | 0.00 |
Annual Sum or Average | 599.07 | 281.61 | 506.24 | 247.61 | 258.63 | 0.00 | 0.00 |
Minimum of Months | 315.54 | 163.87 | 337.72 | 132.49 | 126.66 | 0.00 | 0.00 |
Maximum of Months | 821.31 | 428.28 | 640.57 | 358.26 | 378.67 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 155.21 | 224.14 | 168.86 | 100.27 | 68.59 | 0.00 | 0.00 |
February | 274.37 | 196.96 | 259.68 | 160.74 | 98.93 | 0.00 | 0.00 |
March | 310.80 | 169.92 | 279.34 | 148.97 | 130.37 | 0.00 | 0.00 |
April | 346.57 | 143.21 | 294.93 | 128.06 | 166.87 | 0.00 | 0.00 |
May | 317.09 | 122.53 | 269.67 | 80.34 | 189.34 | 0.00 | 0.00 |
June | 295.37 | 96.59 | 246.73 | 66.24 | 180.48 | 0.00 | 0.00 |
July | 354.77 | 86.14 | 269.06 | 98.55 | 170.52 | 0.00 | 0.00 |
August | 392.64 | 83.69 | 289.08 | 134.80 | 154.28 | 0.00 | 0.00 |
September | 407.23 | 118.79 | 320.28 | 176.87 | 143.41 | 0.00 | 0.00 |
October | 339.39 | 156.57 | 290.12 | 179.13 | 110.99 | 0.00 | 0.00 |
November | 170.08 | 185.46 | 171.53 | 98.30 | 73.23 | 0.00 | 0.00 |
December | 182.13 | 227.32 | 179.47 | 116.14 | 63.33 | 0.00 | 0.00 |
Annual Sum or Average | 295.54 | 150.73 | 253.12 | 123.81 | 129.31 | 0.00 | 0.00 |
Minimum of Months | 155.21 | 83.69 | 168.86 | 66.24 | 63.33 | 0.00 | 0.00 |
Maximum of Months | 407.23 | 227.32 | 320.28 | 179.13 | 189.34 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 155.43 | 217.31 | 168.51 | 100.06 | 68.45 | 0.00 | 0.00 |
February | 274.72 | 190.94 | 259.14 | 160.41 | 98.73 | 0.00 | 0.00 |
March | 311.14 | 164.41 | 278.76 | 148.66 | 130.10 | 0.00 | 0.00 |
April | 346.86 | 139.98 | 294.32 | 127.79 | 166.53 | 0.00 | 0.00 |
May | 316.49 | 122.94 | 269.12 | 80.17 | 188.95 | 0.00 | 0.00 |
June | 294.31 | 98.94 | 246.22 | 66.11 | 180.11 | 0.00 | 0.00 |
July | 353.33 | 89.72 | 268.51 | 98.34 | 170.17 | 0.00 | 0.00 |
August | 391.20 | 87.73 | 288.48 | 134.52 | 153.96 | 0.00 | 0.00 |
September | 406.21 | 120.98 | 319.63 | 176.51 | 143.12 | 0.00 | 0.00 |
October | 339.45 | 153.79 | 289.53 | 178.76 | 110.77 | 0.00 | 0.00 |
November | 170.56 | 179.70 | 171.18 | 98.10 | 73.08 | 0.00 | 0.00 |
December | 182.35 | 220.91 | 179.10 | 115.90 | 63.20 | 0.00 | 0.00 |
Annual Sum or Average | 295.24 | 148.76 | 252.60 | 123.55 | 129.05 | 0.00 | 0.00 |
Minimum of Months | 155.43 | 87.73 | 168.51 | 66.11 | 63.20 | 0.00 | 0.00 |
Maximum of Months | 406.21 | 220.91 | 319.63 | 178.76 | 188.95 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 155.80 | 214.35 | 168.51 | 100.06 | 68.45 | 0.00 | 0.00 |
February | 275.34 | 188.26 | 259.14 | 160.41 | 98.73 | 0.00 | 0.00 |
March | 311.93 | 161.51 | 278.76 | 148.66 | 130.10 | 0.00 | 0.00 |
April | 347.94 | 137.34 | 294.32 | 127.79 | 166.53 | 0.00 | 0.00 |
May | 317.27 | 121.41 | 269.12 | 80.17 | 188.95 | 0.00 | 0.00 |
June | 294.58 | 98.32 | 246.22 | 66.11 | 180.11 | 0.00 | 0.00 |
July | 353.43 | 89.49 | 268.51 | 98.34 | 170.17 | 0.00 | 0.00 |
August | 391.23 | 87.65 | 288.48 | 134.52 | 153.96 | 0.00 | 0.00 |
September | 406.49 | 120.18 | 319.63 | 176.51 | 143.12 | 0.00 | 0.00 |
October | 340.32 | 151.03 | 289.53 | 178.76 | 110.77 | 0.00 | 0.00 |
November | 171.15 | 176.80 | 171.18 | 98.10 | 73.08 | 0.00 | 0.00 |
December | 182.70 | 218.19 | 179.10 | 115.90 | 63.20 | 0.00 | 0.00 |
Annual Sum or Average | 295.75 | 146.86 | 252.60 | 123.55 | 129.05 | 0.00 | 0.00 |
Minimum of Months | 155.80 | 87.65 | 168.51 | 66.11 | 63.20 | 0.00 | 0.00 |
Maximum of Months | 406.49 | 218.19 | 319.63 | 178.76 | 188.95 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 156.27 | 211.74 | 168.51 | 100.06 | 68.45 | 0.00 | 0.00 |
February | 276.12 | 185.85 | 259.14 | 160.41 | 98.73 | 0.00 | 0.00 |
March | 312.98 | 158.54 | 278.76 | 148.66 | 130.10 | 0.00 | 0.00 |
April | 349.63 | 134.14 | 294.32 | 127.79 | 166.53 | 0.00 | 0.00 |
May | 319.20 | 118.49 | 269.12 | 80.17 | 188.95 | 0.00 | 0.00 |
June | 295.54 | 96.71 | 246.22 | 66.11 | 180.11 | 0.00 | 0.00 |
July | 353.93 | 88.40 | 268.51 | 98.34 | 170.17 | 0.00 | 0.00 |
August | 391.66 | 86.60 | 288.48 | 134.52 | 153.96 | 0.00 | 0.00 |
September | 407.42 | 118.27 | 319.63 | 176.51 | 143.12 | 0.00 | 0.00 |
October | 341.76 | 147.38 | 289.53 | 178.76 | 110.77 | 0.00 | 0.00 |
November | 171.93 | 173.95 | 171.18 | 98.10 | 73.08 | 0.00 | 0.00 |
December | 183.13 | 215.71 | 179.10 | 115.90 | 63.20 | 0.00 | 0.00 |
Annual Sum or Average | 296.70 | 144.46 | 252.60 | 123.55 | 129.05 | 0.00 | 0.00 |
Minimum of Months | 156.27 | 86.60 | 168.51 | 66.11 | 63.20 | 0.00 | 0.00 |
Maximum of Months | 407.42 | 215.71 | 319.63 | 178.76 | 188.95 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 315.57 | 408.87 | 337.02 | 200.13 | 136.90 | 0.00 | 0.00 |
February | 556.80 | 358.97 | 518.29 | 320.83 | 197.46 | 0.00 | 0.00 |
March | 630.95 | 304.03 | 557.53 | 297.32 | 260.21 | 0.00 | 0.00 |
April | 706.81 | 254.49 | 588.65 | 255.59 | 333.06 | 0.00 | 0.00 |
May | 648.03 | 222.85 | 538.24 | 160.35 | 377.89 | 0.00 | 0.00 |
June | 596.60 | 184.15 | 492.44 | 132.21 | 360.22 | 0.00 | 0.00 |
July | 710.12 | 170.21 | 537.03 | 196.69 | 340.34 | 0.00 | 0.00 |
August | 784.98 | 166.58 | 576.97 | 269.05 | 307.92 | 0.00 | 0.00 |
September | 819.74 | 226.38 | 639.25 | 353.02 | 286.24 | 0.00 | 0.00 |
October | 690.07 | 279.77 | 579.06 | 357.52 | 221.53 | 0.00 | 0.00 |
November | 347.46 | 334.44 | 342.36 | 196.20 | 146.16 | 0.00 | 0.00 |
December | 368.93 | 417.60 | 358.20 | 231.81 | 126.40 | 0.00 | 0.00 |
Annual Sum or Average | 598.13 | 276.99 | 505.20 | 247.10 | 258.10 | 0.00 | 0.00 |
Minimum of Months | 315.57 | 166.58 | 337.02 | 132.21 | 126.40 | 0.00 | 0.00 |
Maximum of Months | 819.74 | 417.60 | 639.25 | 357.52 | 377.89 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 157.13 | 205.54 | 168.51 | 100.06 | 68.45 | 0.00 | 0.00 |
February | 277.56 | 180.15 | 259.14 | 160.41 | 98.73 | 0.00 | 0.00 |
March | 314.61 | 152.41 | 278.76 | 148.66 | 130.10 | 0.00 | 0.00 |
April | 352.08 | 127.78 | 294.32 | 127.79 | 166.53 | 0.00 | 0.00 |
May | 322.23 | 112.35 | 269.12 | 80.17 | 188.95 | 0.00 | 0.00 |
June | 297.03 | 92.41 | 246.22 | 66.11 | 180.11 | 0.00 | 0.00 |
July | 354.46 | 84.84 | 268.51 | 98.34 | 170.17 | 0.00 | 0.00 |
August | 392.00 | 82.89 | 288.48 | 134.52 | 153.96 | 0.00 | 0.00 |
September | 408.65 | 113.76 | 319.63 | 176.51 | 143.12 | 0.00 | 0.00 |
October | 343.67 | 140.75 | 289.53 | 178.76 | 110.77 | 0.00 | 0.00 |
November | 173.16 | 167.84 | 171.18 | 98.10 | 73.08 | 0.00 | 0.00 |
December | 183.98 | 209.72 | 179.10 | 115.90 | 63.20 | 0.00 | 0.00 |
Annual Sum or Average | 298.11 | 139.02 | 252.60 | 123.55 | 129.05 | 0.00 | 0.00 |
Minimum of Months | 157.13 | 82.89 | 168.51 | 66.11 | 63.20 | 0.00 | 0.00 |
Maximum of Months | 408.65 | 209.72 | 319.63 | 178.76 | 188.95 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 157.26 | 204.82 | 168.51 | 100.06 | 68.45 | 0.00 | 0.00 |
February | 277.80 | 179.40 | 259.14 | 160.41 | 98.73 | 0.00 | 0.00 |
March | 314.90 | 151.58 | 278.76 | 148.66 | 130.10 | 0.00 | 0.00 |
April | 352.48 | 127.04 | 294.32 | 127.79 | 166.53 | 0.00 | 0.00 |
May | 322.75 | 111.64 | 269.12 | 80.17 | 188.95 | 0.00 | 0.00 |
June | 297.39 | 91.93 | 246.22 | 66.11 | 180.11 | 0.00 | 0.00 |
July | 354.71 | 84.44 | 268.51 | 98.34 | 170.17 | 0.00 | 0.00 |
August | 392.20 | 82.53 | 288.48 | 134.52 | 153.96 | 0.00 | 0.00 |
September | 408.90 | 113.28 | 319.63 | 176.51 | 143.12 | 0.00 | 0.00 |
October | 343.98 | 140.02 | 289.53 | 178.76 | 110.77 | 0.00 | 0.00 |
November | 173.36 | 167.08 | 171.18 | 98.10 | 73.08 | 0.00 | 0.00 |
December | 184.11 | 209.00 | 179.10 | 115.90 | 63.20 | 0.00 | 0.00 |
Annual Sum or Average | 298.38 | 138.38 | 252.60 | 123.55 | 129.05 | 0.00 | 0.00 |
Minimum of Months | 157.26 | 82.53 | 168.51 | 66.11 | 63.20 | 0.00 | 0.00 |
Maximum of Months | 408.90 | 209.00 | 319.63 | 178.76 | 188.95 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 157.79 | 201.62 | 168.51 | 100.06 | 68.45 | 0.00 | 0.00 |
February | 278.66 | 176.31 | 259.14 | 160.41 | 98.73 | 0.00 | 0.00 |
March | 315.85 | 148.47 | 278.76 | 148.66 | 130.10 | 0.00 | 0.00 |
April | 353.83 | 124.13 | 294.32 | 127.79 | 166.53 | 0.00 | 0.00 |
May | 324.75 | 108.59 | 269.12 | 80.17 | 188.95 | 0.00 | 0.00 |
June | 298.79 | 89.93 | 246.22 | 66.11 | 180.11 | 0.00 | 0.00 |
July | 355.48 | 83.07 | 268.51 | 98.34 | 170.17 | 0.00 | 0.00 |
August | 392.75 | 81.39 | 288.48 | 134.52 | 153.96 | 0.00 | 0.00 |
September | 410.01 | 111.09 | 319.63 | 176.51 | 143.12 | 0.00 | 0.00 |
October | 345.18 | 137.01 | 289.53 | 178.76 | 110.77 | 0.00 | 0.00 |
November | 174.01 | 164.26 | 171.18 | 98.10 | 73.08 | 0.00 | 0.00 |
December | 184.62 | 205.95 | 179.10 | 115.90 | 63.20 | 0.00 | 0.00 |
Annual Sum or Average | 299.37 | 135.80 | 252.60 | 123.55 | 129.05 | 0.00 | 0.00 |
Minimum of Months | 157.79 | 81.39 | 168.51 | 66.11 | 63.20 | 0.00 | 0.00 |
Maximum of Months | 410.01 | 205.95 | 319.63 | 178.76 | 188.95 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 159.91 | 188.44 | 168.51 | 100.06 | 68.45 | 0.00 | 0.00 |
February | 281.73 | 164.07 | 259.14 | 160.41 | 98.73 | 0.00 | 0.00 |
March | 318.84 | 136.87 | 278.76 | 148.66 | 130.10 | 0.00 | 0.00 |
April | 357.09 | 114.13 | 294.32 | 127.79 | 166.53 | 0.00 | 0.00 |
May | 329.01 | 99.42 | 269.12 | 80.17 | 188.95 | 0.00 | 0.00 |
June | 302.00 | 83.12 | 246.22 | 66.11 | 180.11 | 0.00 | 0.00 |
July | 357.45 | 77.80 | 268.51 | 98.34 | 170.17 | 0.00 | 0.00 |
August | 393.97 | 76.89 | 288.48 | 134.52 | 153.96 | 0.00 | 0.00 |
September | 412.66 | 104.11 | 319.63 | 176.51 | 143.12 | 0.00 | 0.00 |
October | 348.05 | 127.61 | 289.53 | 178.76 | 110.77 | 0.00 | 0.00 |
November | 176.01 | 154.08 | 171.18 | 98.10 | 73.08 | 0.00 | 0.00 |
December | 186.49 | 193.66 | 179.10 | 115.90 | 63.20 | 0.00 | 0.00 |
Annual Sum or Average | 301.99 | 126.52 | 252.60 | 123.55 | 129.05 | 0.00 | 0.00 |
Minimum of Months | 159.91 | 76.89 | 168.51 | 66.11 | 63.20 | 0.00 | 0.00 |
Maximum of Months | 412.66 | 193.66 | 319.63 | 178.76 | 188.95 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.845148E+09 | 0.113035E+10 | 0.904538E+09 | 0.537119E+09 | 0.367419E+09 | 0.00 | 0.00 |
February | 0.134676E+10 | 0.890690E+09 | 0.125642E+10 | 0.777744E+09 | 0.478681E+09 | 0.00 | 0.00 |
March | 0.169250E+10 | 0.827679E+09 | 0.149636E+10 | 0.797991E+09 | 0.698367E+09 | 0.00 | 0.00 |
April | 0.183363E+10 | 0.671477E+09 | 0.152891E+10 | 0.663843E+09 | 0.865064E+09 | 0.00 | 0.00 |
May | 0.173776E+10 | 0.601875E+09 | 0.144459E+10 | 0.430358E+09 | 0.101423E+10 | 0.00 | 0.00 |
June | 0.155187E+10 | 0.475911E+09 | 0.127902E+10 | 0.343402E+09 | 0.935622E+09 | 0.00 | 0.00 |
July | 0.190968E+10 | 0.450185E+09 | 0.144133E+10 | 0.527890E+09 | 0.913435E+09 | 0.00 | 0.00 |
August | 0.211084E+10 | 0.438905E+09 | 0.154852E+10 | 0.722102E+09 | 0.826421E+09 | 0.00 | 0.00 |
September | 0.212883E+10 | 0.589442E+09 | 0.166035E+10 | 0.916902E+09 | 0.743452E+09 | 0.00 | 0.00 |
October | 0.184870E+10 | 0.764091E+09 | 0.155413E+10 | 0.959562E+09 | 0.594571E+09 | 0.00 | 0.00 |
November | 0.898479E+09 | 0.893110E+09 | 0.889215E+09 | 0.509595E+09 | 0.379620E+09 | 0.00 | 0.00 |
December | 0.988043E+09 | 0.114711E+10 | 0.961386E+09 | 0.622151E+09 | 0.339235E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.188923E+11 | 0.888082E+10 | 0.159648E+11 | 0.780866E+10 | 0.815612E+10 | 0.00 | 0.00 |
Minimum of Months | 0.845148E+09 | 0.438905E+09 | 0.889215E+09 | 0.343402E+09 | 0.339235E+09 | 0.00 | 0.00 |
Maximum of Months | 0.212883E+10 | 0.114711E+10 | 0.166035E+10 | 0.959562E+09 | 0.101423E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.415727E+09 | 0.600348E+09 | 0.452269E+09 | 0.268559E+09 | 0.183710E+09 | 0.00 | 0.00 |
February | 0.663760E+09 | 0.476490E+09 | 0.628212E+09 | 0.388872E+09 | 0.239340E+09 | 0.00 | 0.00 |
March | 0.832447E+09 | 0.455118E+09 | 0.748179E+09 | 0.398996E+09 | 0.349183E+09 | 0.00 | 0.00 |
April | 0.898313E+09 | 0.371194E+09 | 0.764453E+09 | 0.331921E+09 | 0.432532E+09 | 0.00 | 0.00 |
May | 0.849301E+09 | 0.328179E+09 | 0.722294E+09 | 0.215179E+09 | 0.507116E+09 | 0.00 | 0.00 |
June | 0.765595E+09 | 0.250361E+09 | 0.639512E+09 | 0.171701E+09 | 0.467811E+09 | 0.00 | 0.00 |
July | 0.950224E+09 | 0.230717E+09 | 0.720663E+09 | 0.263945E+09 | 0.456718E+09 | 0.00 | 0.00 |
August | 0.105164E+10 | 0.224156E+09 | 0.774261E+09 | 0.361051E+09 | 0.413210E+09 | 0.00 | 0.00 |
September | 0.105555E+10 | 0.307905E+09 | 0.830177E+09 | 0.458451E+09 | 0.371726E+09 | 0.00 | 0.00 |
October | 0.909018E+09 | 0.419350E+09 | 0.777067E+09 | 0.479781E+09 | 0.297285E+09 | 0.00 | 0.00 |
November | 0.440836E+09 | 0.480704E+09 | 0.444607E+09 | 0.254797E+09 | 0.189810E+09 | 0.00 | 0.00 |
December | 0.487809E+09 | 0.608861E+09 | 0.480693E+09 | 0.311075E+09 | 0.169617E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.932022E+10 | 0.475338E+10 | 0.798239E+10 | 0.390433E+10 | 0.407806E+10 | 0.00 | 0.00 |
Minimum of Months | 0.415727E+09 | 0.224156E+09 | 0.444607E+09 | 0.171701E+09 | 0.169617E+09 | 0.00 | 0.00 |
Maximum of Months | 0.105555E+10 | 0.608861E+09 | 0.830177E+09 | 0.479781E+09 | 0.507116E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.416295E+09 | 0.582051E+09 | 0.451341E+09 | 0.268009E+09 | 0.183333E+09 | 0.00 | 0.00 |
February | 0.664595E+09 | 0.461911E+09 | 0.626923E+09 | 0.388074E+09 | 0.238849E+09 | 0.00 | 0.00 |
March | 0.833365E+09 | 0.440363E+09 | 0.746644E+09 | 0.398177E+09 | 0.348467E+09 | 0.00 | 0.00 |
April | 0.899065E+09 | 0.362829E+09 | 0.762885E+09 | 0.331240E+09 | 0.431645E+09 | 0.00 | 0.00 |
May | 0.847691E+09 | 0.329295E+09 | 0.720813E+09 | 0.214737E+09 | 0.506075E+09 | 0.00 | 0.00 |
June | 0.762859E+09 | 0.256464E+09 | 0.638200E+09 | 0.171349E+09 | 0.466851E+09 | 0.00 | 0.00 |
July | 0.946370E+09 | 0.240298E+09 | 0.719184E+09 | 0.263404E+09 | 0.455781E+09 | 0.00 | 0.00 |
August | 0.104778E+10 | 0.234973E+09 | 0.772673E+09 | 0.360310E+09 | 0.412363E+09 | 0.00 | 0.00 |
September | 0.105291E+10 | 0.313570E+09 | 0.828474E+09 | 0.457511E+09 | 0.370963E+09 | 0.00 | 0.00 |
October | 0.909188E+09 | 0.411914E+09 | 0.775472E+09 | 0.478797E+09 | 0.296675E+09 | 0.00 | 0.00 |
November | 0.442080E+09 | 0.465779E+09 | 0.443695E+09 | 0.254275E+09 | 0.189421E+09 | 0.00 | 0.00 |
December | 0.488406E+09 | 0.591698E+09 | 0.479707E+09 | 0.310437E+09 | 0.169270E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.931060E+10 | 0.469114E+10 | 0.796601E+10 | 0.389632E+10 | 0.406969E+10 | 0.00 | 0.00 |
Minimum of Months | 0.416295E+09 | 0.234973E+09 | 0.443695E+09 | 0.171349E+09 | 0.169270E+09 | 0.00 | 0.00 |
Maximum of Months | 0.105291E+10 | 0.591698E+09 | 0.828474E+09 | 0.478797E+09 | 0.506075E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.417287E+09 | 0.574113E+09 | 0.451341E+09 | 0.268009E+09 | 0.183333E+09 | 0.00 | 0.00 |
February | 0.666110E+09 | 0.455443E+09 | 0.626923E+09 | 0.388074E+09 | 0.238849E+09 | 0.00 | 0.00 |
March | 0.835462E+09 | 0.432597E+09 | 0.746644E+09 | 0.398177E+09 | 0.348467E+09 | 0.00 | 0.00 |
April | 0.901851E+09 | 0.355997E+09 | 0.762885E+09 | 0.331240E+09 | 0.431645E+09 | 0.00 | 0.00 |
May | 0.849783E+09 | 0.325184E+09 | 0.720813E+09 | 0.214737E+09 | 0.506075E+09 | 0.00 | 0.00 |
June | 0.763555E+09 | 0.254849E+09 | 0.638200E+09 | 0.171349E+09 | 0.466851E+09 | 0.00 | 0.00 |
July | 0.946617E+09 | 0.239682E+09 | 0.719184E+09 | 0.263404E+09 | 0.455781E+09 | 0.00 | 0.00 |
August | 0.104786E+10 | 0.234765E+09 | 0.772673E+09 | 0.360310E+09 | 0.412363E+09 | 0.00 | 0.00 |
September | 0.105363E+10 | 0.311509E+09 | 0.828474E+09 | 0.457511E+09 | 0.370963E+09 | 0.00 | 0.00 |
October | 0.911511E+09 | 0.404522E+09 | 0.775472E+09 | 0.478797E+09 | 0.296675E+09 | 0.00 | 0.00 |
November | 0.443629E+09 | 0.458263E+09 | 0.443695E+09 | 0.254275E+09 | 0.189421E+09 | 0.00 | 0.00 |
December | 0.489339E+09 | 0.584395E+09 | 0.479707E+09 | 0.310437E+09 | 0.169270E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.932664E+10 | 0.463132E+10 | 0.796601E+10 | 0.389632E+10 | 0.406969E+10 | 0.00 | 0.00 |
Minimum of Months | 0.417287E+09 | 0.234765E+09 | 0.443695E+09 | 0.171349E+09 | 0.169270E+09 | 0.00 | 0.00 |
Maximum of Months | 0.105363E+10 | 0.584395E+09 | 0.828474E+09 | 0.478797E+09 | 0.506075E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.418566E+09 | 0.567136E+09 | 0.451341E+09 | 0.268009E+09 | 0.183333E+09 | 0.00 | 0.00 |
February | 0.667997E+09 | 0.449607E+09 | 0.626923E+09 | 0.388074E+09 | 0.238849E+09 | 0.00 | 0.00 |
March | 0.838273E+09 | 0.424642E+09 | 0.746644E+09 | 0.398177E+09 | 0.348467E+09 | 0.00 | 0.00 |
April | 0.906234E+09 | 0.347681E+09 | 0.762885E+09 | 0.331240E+09 | 0.431645E+09 | 0.00 | 0.00 |
May | 0.854952E+09 | 0.317353E+09 | 0.720813E+09 | 0.214737E+09 | 0.506075E+09 | 0.00 | 0.00 |
June | 0.766031E+09 | 0.250668E+09 | 0.638200E+09 | 0.171349E+09 | 0.466851E+09 | 0.00 | 0.00 |
July | 0.947971E+09 | 0.236758E+09 | 0.719184E+09 | 0.263404E+09 | 0.455781E+09 | 0.00 | 0.00 |
August | 0.104903E+10 | 0.231960E+09 | 0.772673E+09 | 0.360310E+09 | 0.412363E+09 | 0.00 | 0.00 |
September | 0.105603E+10 | 0.306555E+09 | 0.828474E+09 | 0.457511E+09 | 0.370963E+09 | 0.00 | 0.00 |
October | 0.915371E+09 | 0.394735E+09 | 0.775472E+09 | 0.478797E+09 | 0.296675E+09 | 0.00 | 0.00 |
November | 0.445652E+09 | 0.450890E+09 | 0.443695E+09 | 0.254275E+09 | 0.189421E+09 | 0.00 | 0.00 |
December | 0.490505E+09 | 0.577754E+09 | 0.479707E+09 | 0.310437E+09 | 0.169270E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.935661E+10 | 0.455574E+10 | 0.796601E+10 | 0.389632E+10 | 0.406969E+10 | 0.00 | 0.00 |
Minimum of Months | 0.418566E+09 | 0.231960E+09 | 0.443695E+09 | 0.171349E+09 | 0.169270E+09 | 0.00 | 0.00 |
Maximum of Months | 0.105603E+10 | 0.577754E+09 | 0.828474E+09 | 0.478797E+09 | 0.506075E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.845212E+09 | 0.109512E+10 | 0.902683E+09 | 0.536017E+09 | 0.366666E+09 | 0.00 | 0.00 |
February | 0.134701E+10 | 0.868432E+09 | 0.125385E+10 | 0.776148E+09 | 0.477699E+09 | 0.00 | 0.00 |
March | 0.168995E+10 | 0.814310E+09 | 0.149329E+10 | 0.796354E+09 | 0.696934E+09 | 0.00 | 0.00 |
April | 0.183205E+10 | 0.659646E+09 | 0.152577E+10 | 0.662481E+09 | 0.863289E+09 | 0.00 | 0.00 |
May | 0.173569E+10 | 0.596875E+09 | 0.144163E+10 | 0.429475E+09 | 0.101215E+10 | 0.00 | 0.00 |
June | 0.154638E+10 | 0.477323E+09 | 0.127640E+10 | 0.342697E+09 | 0.933702E+09 | 0.00 | 0.00 |
July | 0.190199E+10 | 0.455887E+09 | 0.143837E+10 | 0.526807E+09 | 0.911561E+09 | 0.00 | 0.00 |
August | 0.210250E+10 | 0.446172E+09 | 0.154535E+10 | 0.720620E+09 | 0.824725E+09 | 0.00 | 0.00 |
September | 0.212476E+10 | 0.586776E+09 | 0.165695E+10 | 0.915021E+09 | 0.741926E+09 | 0.00 | 0.00 |
October | 0.184828E+10 | 0.749336E+09 | 0.155094E+10 | 0.957594E+09 | 0.593351E+09 | 0.00 | 0.00 |
November | 0.900608E+09 | 0.866870E+09 | 0.887390E+09 | 0.508549E+09 | 0.378841E+09 | 0.00 | 0.00 |
December | 0.988155E+09 | 0.111851E+10 | 0.959413E+09 | 0.620874E+09 | 0.338539E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.188626E+11 | 0.873526E+10 | 0.159320E+11 | 0.779264E+10 | 0.813938E+10 | 0.00 | 0.00 |
Minimum of Months | 0.845212E+09 | 0.446172E+09 | 0.887390E+09 | 0.342697E+09 | 0.338539E+09 | 0.00 | 0.00 |
Maximum of Months | 0.212476E+10 | 0.111851E+10 | 0.165695E+10 | 0.957594E+09 | 0.101215E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.420861E+09 | 0.550513E+09 | 0.451341E+09 | 0.268009E+09 | 0.183333E+09 | 0.00 | 0.00 |
February | 0.671472E+09 | 0.435819E+09 | 0.626923E+09 | 0.388074E+09 | 0.238849E+09 | 0.00 | 0.00 |
March | 0.842641E+09 | 0.408209E+09 | 0.746644E+09 | 0.398177E+09 | 0.348467E+09 | 0.00 | 0.00 |
April | 0.912586E+09 | 0.331212E+09 | 0.762885E+09 | 0.331240E+09 | 0.431645E+09 | 0.00 | 0.00 |
May | 0.863053E+09 | 0.300927E+09 | 0.720813E+09 | 0.214737E+09 | 0.506075E+09 | 0.00 | 0.00 |
June | 0.769895E+09 | 0.239534E+09 | 0.638200E+09 | 0.171349E+09 | 0.466851E+09 | 0.00 | 0.00 |
July | 0.949379E+09 | 0.227230E+09 | 0.719184E+09 | 0.263404E+09 | 0.455781E+09 | 0.00 | 0.00 |
August | 0.104994E+10 | 0.222012E+09 | 0.772673E+09 | 0.360310E+09 | 0.412363E+09 | 0.00 | 0.00 |
September | 0.105921E+10 | 0.294861E+09 | 0.828474E+09 | 0.457511E+09 | 0.370963E+09 | 0.00 | 0.00 |
October | 0.920486E+09 | 0.376987E+09 | 0.775472E+09 | 0.478797E+09 | 0.296675E+09 | 0.00 | 0.00 |
November | 0.448835E+09 | 0.435052E+09 | 0.443695E+09 | 0.254275E+09 | 0.189421E+09 | 0.00 | 0.00 |
December | 0.492761E+09 | 0.561722E+09 | 0.479707E+09 | 0.310437E+09 | 0.169270E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.940112E+10 | 0.438408E+10 | 0.796601E+10 | 0.389632E+10 | 0.406969E+10 | 0.00 | 0.00 |
Minimum of Months | 0.420861E+09 | 0.222012E+09 | 0.443695E+09 | 0.171349E+09 | 0.169270E+09 | 0.00 | 0.00 |
Maximum of Months | 0.105921E+10 | 0.561722E+09 | 0.828474E+09 | 0.478797E+09 | 0.506075E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.421215E+09 | 0.548601E+09 | 0.451341E+09 | 0.268009E+09 | 0.183333E+09 | 0.00 | 0.00 |
February | 0.672052E+09 | 0.434007E+09 | 0.626923E+09 | 0.388074E+09 | 0.238849E+09 | 0.00 | 0.00 |
March | 0.843417E+09 | 0.406003E+09 | 0.746644E+09 | 0.398177E+09 | 0.348467E+09 | 0.00 | 0.00 |
April | 0.913615E+09 | 0.329281E+09 | 0.762885E+09 | 0.331240E+09 | 0.431645E+09 | 0.00 | 0.00 |
May | 0.864441E+09 | 0.299017E+09 | 0.720813E+09 | 0.214737E+09 | 0.506075E+09 | 0.00 | 0.00 |
June | 0.770826E+09 | 0.238292E+09 | 0.638200E+09 | 0.171349E+09 | 0.466851E+09 | 0.00 | 0.00 |
July | 0.950059E+09 | 0.226159E+09 | 0.719184E+09 | 0.263404E+09 | 0.455781E+09 | 0.00 | 0.00 |
August | 0.105047E+10 | 0.221055E+09 | 0.772673E+09 | 0.360310E+09 | 0.412363E+09 | 0.00 | 0.00 |
September | 0.105987E+10 | 0.293628E+09 | 0.828474E+09 | 0.457511E+09 | 0.370963E+09 | 0.00 | 0.00 |
October | 0.921317E+09 | 0.375041E+09 | 0.775472E+09 | 0.478797E+09 | 0.296675E+09 | 0.00 | 0.00 |
November | 0.449351E+09 | 0.433082E+09 | 0.443695E+09 | 0.254275E+09 | 0.189421E+09 | 0.00 | 0.00 |
December | 0.493133E+09 | 0.559787E+09 | 0.479707E+09 | 0.310437E+09 | 0.169270E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.940977E+10 | 0.436395E+10 | 0.796601E+10 | 0.389632E+10 | 0.406969E+10 | 0.00 | 0.00 |
Minimum of Months | 0.421215E+09 | 0.221055E+09 | 0.443695E+09 | 0.171349E+09 | 0.169270E+09 | 0.00 | 0.00 |
Maximum of Months | 0.105987E+10 | 0.559787E+09 | 0.828474E+09 | 0.478797E+09 | 0.506075E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.422613E+09 | 0.540029E+09 | 0.451341E+09 | 0.268009E+09 | 0.183333E+09 | 0.00 | 0.00 |
February | 0.674139E+09 | 0.426540E+09 | 0.626923E+09 | 0.388074E+09 | 0.238849E+09 | 0.00 | 0.00 |
March | 0.845967E+09 | 0.397653E+09 | 0.746644E+09 | 0.398177E+09 | 0.348467E+09 | 0.00 | 0.00 |
April | 0.917122E+09 | 0.321750E+09 | 0.762885E+09 | 0.331240E+09 | 0.431645E+09 | 0.00 | 0.00 |
May | 0.869823E+09 | 0.290857E+09 | 0.720813E+09 | 0.214737E+09 | 0.506075E+09 | 0.00 | 0.00 |
June | 0.774467E+09 | 0.233095E+09 | 0.638200E+09 | 0.171349E+09 | 0.466851E+09 | 0.00 | 0.00 |
July | 0.952119E+09 | 0.222486E+09 | 0.719184E+09 | 0.263404E+09 | 0.455781E+09 | 0.00 | 0.00 |
August | 0.105194E+10 | 0.217999E+09 | 0.772673E+09 | 0.360310E+09 | 0.412363E+09 | 0.00 | 0.00 |
September | 0.106276E+10 | 0.287948E+09 | 0.828474E+09 | 0.457511E+09 | 0.370963E+09 | 0.00 | 0.00 |
October | 0.924528E+09 | 0.366962E+09 | 0.775472E+09 | 0.478797E+09 | 0.296675E+09 | 0.00 | 0.00 |
November | 0.451026E+09 | 0.425771E+09 | 0.443695E+09 | 0.254275E+09 | 0.189421E+09 | 0.00 | 0.00 |
December | 0.494481E+09 | 0.551624E+09 | 0.479707E+09 | 0.310437E+09 | 0.169270E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.944098E+10 | 0.428272E+10 | 0.796601E+10 | 0.389632E+10 | 0.406969E+10 | 0.00 | 0.00 |
Minimum of Months | 0.422613E+09 | 0.217999E+09 | 0.443695E+09 | 0.171349E+09 | 0.169270E+09 | 0.00 | 0.00 |
Maximum of Months | 0.106276E+10 | 0.551624E+09 | 0.828474E+09 | 0.478797E+09 | 0.506075E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.428290E+09 | 0.504725E+09 | 0.451341E+09 | 0.268009E+09 | 0.183333E+09 | 0.00 | 0.00 |
February | 0.681559E+09 | 0.396927E+09 | 0.626923E+09 | 0.388074E+09 | 0.238849E+09 | 0.00 | 0.00 |
March | 0.853980E+09 | 0.366590E+09 | 0.746644E+09 | 0.398177E+09 | 0.348467E+09 | 0.00 | 0.00 |
April | 0.925569E+09 | 0.295825E+09 | 0.762885E+09 | 0.331240E+09 | 0.431645E+09 | 0.00 | 0.00 |
May | 0.881210E+09 | 0.266277E+09 | 0.720813E+09 | 0.214737E+09 | 0.506075E+09 | 0.00 | 0.00 |
June | 0.782774E+09 | 0.215440E+09 | 0.638200E+09 | 0.171349E+09 | 0.466851E+09 | 0.00 | 0.00 |
July | 0.957389E+09 | 0.208382E+09 | 0.719184E+09 | 0.263404E+09 | 0.455781E+09 | 0.00 | 0.00 |
August | 0.105522E+10 | 0.205942E+09 | 0.772673E+09 | 0.360310E+09 | 0.412363E+09 | 0.00 | 0.00 |
September | 0.106962E+10 | 0.269856E+09 | 0.828474E+09 | 0.457511E+09 | 0.370963E+09 | 0.00 | 0.00 |
October | 0.932212E+09 | 0.341788E+09 | 0.775472E+09 | 0.478797E+09 | 0.296675E+09 | 0.00 | 0.00 |
November | 0.456218E+09 | 0.399369E+09 | 0.443695E+09 | 0.254275E+09 | 0.189421E+09 | 0.00 | 0.00 |
December | 0.499501E+09 | 0.518706E+09 | 0.479707E+09 | 0.310437E+09 | 0.169270E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.952354E+10 | 0.398983E+10 | 0.796601E+10 | 0.389632E+10 | 0.406969E+10 | 0.00 | 0.00 |
Minimum of Months | 0.428290E+09 | 0.205942E+09 | 0.443695E+09 | 0.171349E+09 | 0.169270E+09 | 0.00 | 0.00 |
Maximum of Months | 0.106962E+10 | 0.518706E+09 | 0.828474E+09 | 0.478797E+09 | 0.506075E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 4.50 | 3.10 | 1.22 | 3.91 | -4.2 | 29.50 | 44.23 | 0.00 |
February | 5.82 | 4.07 | 1.77 | 3.94 | -3.8 | 43.80 | 82.64 | 0.00 |
March | 8.33 | 5.86 | 2.94 | 3.85 | -1.4 | 65.55 | 100.60 | 0.02 |
April | 10.85 | 8.04 | 5.25 | 4.23 | 1.22 | 89.73 | 150.02 | 0.00 |
May | 12.97 | 10.02 | 7.49 | 3.85 | 3.75 | 114.98 | 168.60 | 0.00 |
June | 15.59 | 11.80 | 8.88 | 4.02 | 5.93 | 107.53 | 199.74 | 0.01 |
July | 17.66 | 13.41 | 10.38 | 3.76 | 8.02 | 92.25 | 247.81 | 0.00 |
August | 18.80 | 14.57 | 11.86 | 3.84 | 8.90 | 79.20 | 215.47 | 0.01 |
September | 15.09 | 12.55 | 10.74 | 2.23 | 5.47 | 68.06 | 162.11 | 0.01 |
October | 11.43 | 9.19 | 7.19 | 4.02 | 2.10 | 48.18 | 106.36 | 0.04 |
November | 8.07 | 6.72 | 5.29 | 3.86 | 0.13 | 33.26 | 46.10 | 0.00 |
December | 5.42 | 4.09 | 2.46 | 3.51 | -3.8 | 24.03 | 50.49 | 0.04 |
Annual Sum or Average | 11.24 | 8.64 | 6.31 | 3.75 | 1.89 | 66.43 | 131.49 | 0.01 |
Minimum of Months | 4.50 | 3.10 | 1.22 | 2.23 | -4.2 | 24.03 | 44.23 | 0.00 |
Maximum of Months | 18.80 | 14.57 | 11.86 | 4.23 | 8.90 | 114.98 | 247.81 | 0.04 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 14.40 | 11-JAN-14:20 | 10.49 | 7.20 | 8.40 | 3.89 | 99.17 | 130.33 |
February | 20.00 | 27-FEB-14:00 | 12.17 | 5.60 | 2.60 | 5.54 | 87.00 | 691.00 |
March | 20.60 | 18-MAR-15:00 | 10.43 | 0.00 | 6.20 | 6.55 | 111.50 | 465.50 |
April | 27.20 | 27-APR-15:09 | 17.22 | 11.02 | 4.10 | 12.63 | 151.33 | 598.33 |
May | 25.00 | 05-MAY-15:00 | 17.36 | 12.80 | 2.60 | 18.99 | 208.50 | 29.50 |
June | 26.70 | 28-JUN-16:00 | 16.74 | 10.60 | 3.10 | 11.84 | 131.50 | 527.00 |
July | 30.60 | 24-JUL-14:00 | 18.78 | 12.20 | 3.10 | 20.75 | 267.00 | 383.50 |
August | 31.80 | 10-AUG-16:00 | 18.70 | 11.10 | 2.60 | 16.85 | 50.50 | 750.50 |
September | 25.00 | 14-SEP-16:00 | 16.69 | 11.70 | 3.10 | 13.54 | 100.50 | 235.00 |
October | 21.70 | 04-OCT-14:00 | 11.49 | 1.70 | 5.20 | 4.92 | 56.50 | 783.50 |
November | 21.10 | 04-NOV-13:00 | 15.94 | 12.80 | 0.00 | 6.95 | 52.50 | 729.00 |
December | 13.30 | 14-DEC-11:00 | 8.44 | 3.60 | 13.90 | 5.33 | 127.50 | 85.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 13.30 | 8.44 | 0.00 | 0.00 | 3.89 | 50.50 | 29.50 | |
Maximum of Months | 31.80 | 18.78 | 12.80 | 13.90 | 20.75 | 267.00 | 783.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -3.9 | 07-JAN-07:00 | -3.9 | -3.9 | 2.10 | -14.4 | 0.00 | 0.00 |
February | -5.6 | 19-FEB-05:10 | -6.1 | -7.3 | 3.77 | -22.8 | 0.00 | 0.00 |
March | -0.6 | 01-MAR-06:00 | -2.0 | -3.9 | 1.50 | -17.3 | 16.50 | 102.00 |
April | 1.70 | 19-APR-04:00 | 1.21 | 0.60 | 3.10 | -11.9 | 0.00 | 0.00 |
May | 4.40 | 11-MAY-02:00 | 3.92 | 3.30 | 3.10 | -10.9 | 0.00 | 0.00 |
June | 8.30 | 15-JUN-02:00 | 7.50 | 6.70 | 3.10 | -3.2 | 0.00 | 0.00 |
July | 11.10 | 03-JUL-03:00 | 8.19 | 5.00 | 2.60 | 5.54 | 0.00 | 0.00 |
August | 11.00 | 06-AUG-04:00 | 10.57 | 10.20 | 2.60 | -3.2 | 11.00 | 135.50 |
September | 7.20 | 27-SEP-04:49 | 6.72 | 6.20 | 0.25 | -4.0 | 0.00 | 0.00 |
October | 5.60 | 13-OCT-04:00 | 4.51 | 3.30 | 2.10 | -8.5 | 0.00 | 0.00 |
November | 0.00 | 11-NOV-06:00 | -0.2 | -0.6 | 2.10 | -16.0 | 0.00 | 0.00 |
December | -1.7 | 26-DEC-06:00 | -1.7 | -1.7 | 2.10 | -15.7 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -5.6 | -6.1 | -7.3 | 0.25 | -22.8 | 0.00 | 0.00 | |
Maximum of Months | 11.10 | 10.57 | 10.20 | 3.77 | 5.54 | 16.50 | 135.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.49 | 11-JAN-13:00 | 14.40 | 7.20 | 8.20 | 2.85 | 105.50 | 249.00 |
February | 12.42 | 27-FEB-15:00 | 19.40 | 6.70 | 2.60 | 6.35 | 88.00 | 342.50 |
March | 12.45 | 09-MAR-11:00 | 17.20 | 8.90 | 2.10 | 12.41 | 178.00 | 40.00 |
April | 17.29 | 27-APR-14:00 | 27.20 | 11.10 | 4.10 | 12.41 | 147.50 | 646.00 |
May | 17.58 | 06-MAY-12:00 | 23.90 | 13.90 | 5.20 | 15.57 | 365.50 | 282.50 |
June | 16.74 | 28-JUN-16:00 | 26.70 | 10.60 | 3.10 | 11.84 | 131.50 | 527.00 |
July | 19.18 | 31-JUL-15:00 | 28.90 | 13.90 | 4.10 | 14.65 | 45.00 | 848.50 |
August | 20.13 | 29-AUG-12:00 | 28.90 | 15.70 | 2.60 | 17.39 | 136.50 | 655.00 |
September | 17.97 | 23-SEP-13:00 | 23.30 | 15.00 | 2.10 | 9.72 | 148.00 | 670.50 |
October | 15.15 | 01-OCT-11:00 | 17.20 | 13.90 | 4.60 | 13.73 | 236.50 | 63.50 |
November | 16.05 | 04-NOV-12:00 | 20.60 | 13.30 | 0.00 | 7.95 | 62.00 | 746.50 |
December | 10.71 | 16-DEC-11:00 | 11.70 | 10.00 | 6.70 | 7.35 | 89.50 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.49 | 11.70 | 6.70 | 0.00 | 2.85 | 45.00 | 0.00 | |
Maximum of Months | 20.13 | 28.90 | 15.70 | 8.20 | 17.39 | 365.50 | 848.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.00 | 11-JAN-21:00 | 11.10 | 10.49 | 4.60 | 6.75 | 0.00 | 0.00 |
February | 11.70 | 24-FEB-00:00 | 12.80 | 12.15 | 4.10 | 8.74 | 0.00 | 0.00 |
March | 11.70 | 09-MAR-16:00 | 12.80 | 12.15 | 2.10 | 8.74 | 37.50 | 0.00 |
April | 12.80 | 28-APR-12:00 | 16.70 | 14.35 | 4.10 | 8.35 | 265.50 | 596.00 |
May | 13.90 | 05-MAY-16:00 | 22.80 | 17.10 | 2.60 | 19.17 | 111.50 | 27.50 |
June | 13.90 | 12-JUN-12:00 | 16.70 | 15.00 | 3.60 | 13.16 | 263.50 | 0.00 |
July | 15.00 | 11-JUL-09:20 | 16.13 | 15.49 | 4.60 | 12.91 | 204.17 | 28.17 |
August | 16.40 | 30-AUG-07:00 | 17.40 | 16.77 | 5.20 | 12.41 | 168.50 | 34.50 |
September | 15.00 | 14-SEP-11:20 | 20.37 | 16.93 | 2.10 | 6.89 | 152.83 | 748.17 |
October | 13.90 | 01-OCT-10:00 | 16.70 | 15.01 | 4.10 | 13.16 | 184.50 | 0.00 |
November | 13.90 | 03-NOV-19:00 | 15.00 | 14.31 | 4.60 | 11.46 | 0.00 | 0.00 |
December | 10.00 | 16-DEC-10:00 | 11.10 | 10.48 | 7.70 | 6.75 | 81.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.00 | 11.10 | 10.48 | 2.10 | 6.75 | 0.00 | 0.00 | |
Maximum of Months | 16.40 | 22.80 | 17.10 | 7.70 | 19.17 | 265.50 | 748.17 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 11.48 | 8.35 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 11.14 | 14.81 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 11.69 | 23.26 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 12.99 | 36.00 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 14.72 | 45.46 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 16.40 | 49.26 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 17.58 | 51.50 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 17.95 | 42.11 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 17.39 | 30.76 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 16.06 | 18.91 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 14.32 | 9.65 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 12.65 | 7.39 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 14.55 | 28.19 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 11.14 | 7.39 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 17.95 | 51.50 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK1
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.357545E+09 | -233291212.4 | 0.00 | 0.00 | 744.00 | 0.00 | -124253423.2 | 59.00 | 0.00 | 0.00 |
February | 0.325116E+09 | -213318778.2 | 0.00 | 0.00 | 672.00 | 0.00 | -111797226.1 | 58.99 | 0.00 | 0.00 |
March | 0.360320E+09 | -237334969.5 | 0.00 | 0.00 | 744.00 | 0.00 | -122985329.7 | 58.99 | 0.00 | 0.00 |
April | 0.337280E+09 | -220462108.1 | 0.00 | 0.00 | 720.00 | 0.00 | -116818029.6 | 58.99 | 0.00 | 0.00 |
May | 0.337115E+09 | -219627113.1 | 0.00 | 0.00 | 744.00 | 0.00 | -117488135.3 | 58.99 | 0.00 | 0.00 |
June | 0.317509E+09 | -206541429.2 | 0.00 | 0.00 | 720.00 | 0.00 | -110967790.5 | 58.99 | 0.00 | 0.00 |
July | 0.316641E+09 | -203275738.2 | 0.00 | 0.00 | 744.00 | 0.00 | -113365699.2 | 58.99 | 0.00 | 0.00 |
August | 0.318962E+09 | -205764620.6 | 0.00 | 0.00 | 744.00 | 0.00 | -113197714.6 | 58.99 | 0.00 | 0.00 |
September | 0.310583E+09 | -199579025.0 | 0.00 | 0.00 | 720.00 | 0.00 | -111004464.9 | 58.99 | 0.00 | 0.00 |
October | 0.330319E+09 | -210818276.9 | 0.00 | 0.00 | 744.00 | 0.00 | -119500818.8 | 58.99 | 0.00 | 0.00 |
November | 0.330410E+09 | -211659069.9 | 0.00 | 0.00 | 720.00 | 0.00 | -118751207.1 | 58.99 | 0.00 | 0.00 |
December | 0.351760E+09 | -227817858.0 | 0.00 | 0.00 | 744.00 | 0.00 | -123941653.1 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.399356E+10 | -0.258949E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.140407E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.310583E+09 | -237334969.5 | 0.00 | 0.00 | 672.00 | 0.00 | -124253423.2 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.360320E+09 | -199579025.0 | 0.00 | 0.00 | 744.00 | 0.00 | -110967790.5 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK2
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.355515E+09 | -233294649.9 | 0.00 | 0.00 | 744.00 | 0.00 | -122220526.8 | 58.99 | 0.00 | 0.00 |
February | 0.322841E+09 | -213321509.6 | 0.00 | 0.00 | 672.00 | 0.00 | -109519005.6 | 58.99 | 0.00 | 0.00 |
March | 0.356803E+09 | -237339172.0 | 0.00 | 0.00 | 744.00 | 0.00 | -119463909.6 | 58.99 | 0.00 | 0.00 |
April | 0.333653E+09 | -220464279.2 | 0.00 | 0.00 | 720.00 | 0.00 | -113188314.5 | 58.99 | 0.00 | 0.00 |
May | 0.333988E+09 | -219629908.7 | 0.00 | 0.00 | 744.00 | 0.00 | -114357592.2 | 58.99 | 0.00 | 0.00 |
June | 0.316166E+09 | -206550357.3 | 0.00 | 0.00 | 720.00 | 0.00 | -109615725.9 | 58.99 | 0.00 | 0.00 |
July | 0.316104E+09 | -203266899.6 | 0.00 | 0.00 | 744.00 | 0.00 | -112836938.8 | 58.99 | 0.00 | 0.00 |
August | 0.318542E+09 | -205768410.9 | 0.00 | 0.00 | 744.00 | 0.00 | -112773472.4 | 58.99 | 0.00 | 0.00 |
September | 0.309178E+09 | -199581456.9 | 0.00 | 0.00 | 720.00 | 0.00 | -109596376.5 | 58.99 | 0.00 | 0.00 |
October | 0.326724E+09 | -210824184.1 | 0.00 | 0.00 | 744.00 | 0.00 | -115900001.4 | 58.99 | 0.00 | 0.00 |
November | 0.327778E+09 | -211653392.1 | 0.00 | 0.00 | 720.00 | 0.00 | -116124367.3 | 58.99 | 0.00 | 0.00 |
December | 0.349600E+09 | -227817854.7 | 0.00 | 0.00 | 744.00 | 0.00 | -121781911.1 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.396689E+10 | -0.258951E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.137738E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.309178E+09 | -237339172.0 | 0.00 | 0.00 | 672.00 | 0.00 | -122220526.8 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.356803E+09 | -199581456.9 | 0.00 | 0.00 | 744.00 | 0.00 | -109519005.6 | 58.99 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK3
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.329079E+09 | -205142064.0 | 0.00 | 0.00 | 744.00 | 0.00 | -123936790.8 | 59.00 | 0.00 | 0.00 |
February | 0.298820E+09 | -187771761.2 | 0.00 | 0.00 | 672.00 | 0.00 | -111048512.8 | 58.98 | 0.00 | 0.00 |
March | 0.333018E+09 | -211851461.1 | 0.00 | 0.00 | 744.00 | 0.00 | -121167003.7 | 58.98 | 0.00 | 0.00 |
April | 0.308244E+09 | -193887050.6 | 0.00 | 0.00 | 720.00 | 0.00 | -114357254.9 | 59.00 | 0.00 | 0.00 |
May | 0.309231E+09 | -194788713.2 | 0.00 | 0.00 | 744.00 | 0.00 | -114442449.7 | 58.99 | 0.00 | 0.00 |
June | 0.293005E+09 | -183942570.8 | 0.00 | 0.00 | 720.00 | 0.00 | -109061987.8 | 59.00 | 0.00 | 0.00 |
July | 0.289507E+09 | -177712712.4 | 0.00 | 0.00 | 744.00 | 0.00 | -111794360.3 | 58.99 | 0.00 | 0.00 |
August | 0.295447E+09 | -183785600.3 | 0.00 | 0.00 | 744.00 | 0.00 | -111661872.4 | 58.99 | 0.00 | 0.00 |
September | 0.284545E+09 | -175400829.0 | 0.00 | 0.00 | 720.00 | 0.00 | -109144282.3 | 58.99 | 0.00 | 0.00 |
October | 0.302339E+09 | -185405865.0 | 0.00 | 0.00 | 744.00 | 0.00 | -116933158.3 | 58.99 | 0.00 | 0.00 |
November | 0.304610E+09 | -186872396.0 | 0.00 | 0.00 | 720.00 | 0.00 | -117737361.4 | 59.00 | 0.00 | 0.00 |
December | 0.322357E+09 | -198834173.4 | 0.00 | 0.00 | 744.00 | 0.00 | -123523218.8 | 59.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.367020E+10 | -0.228540E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.138481E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.284545E+09 | -211851461.1 | 0.00 | 0.00 | 672.00 | 0.00 | -123936790.8 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.333018E+09 | -175400829.0 | 0.00 | 0.00 | 744.00 | 0.00 | -109061987.8 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK4
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.329492E+09 | -205158246.9 | 0.00 | 0.00 | 744.00 | 0.00 | -124333556.9 | 58.99 | 0.00 | 0.00 |
February | 0.299239E+09 | -187701154.3 | 0.00 | 0.00 | 672.00 | 0.00 | -111537909.2 | 59.01 | 0.00 | 0.00 |
March | 0.333530E+09 | -211882044.5 | 0.00 | 0.00 | 744.00 | 0.00 | -121647489.8 | 58.97 | 0.00 | 0.00 |
April | 0.308782E+09 | -193882155.6 | 0.00 | 0.00 | 720.00 | 0.00 | -114899530.2 | 59.00 | 0.00 | 0.00 |
May | 0.309594E+09 | -194782799.9 | 0.00 | 0.00 | 744.00 | 0.00 | -114811003.8 | 58.99 | 0.00 | 0.00 |
June | 0.293115E+09 | -183956565.2 | 0.00 | 0.00 | 720.00 | 0.00 | -109158865.7 | 58.99 | 0.00 | 0.00 |
July | 0.289548E+09 | -177719429.0 | 0.00 | 0.00 | 744.00 | 0.00 | -111828470.4 | 58.99 | 0.00 | 0.00 |
August | 0.295458E+09 | -183781548.9 | 0.00 | 0.00 | 744.00 | 0.00 | -111676316.4 | 59.00 | 0.00 | 0.00 |
September | 0.284701E+09 | -175369675.0 | 0.00 | 0.00 | 720.00 | 0.00 | -109331458.0 | 59.01 | 0.00 | 0.00 |
October | 0.302897E+09 | -185413977.7 | 0.00 | 0.00 | 744.00 | 0.00 | -117483337.0 | 58.99 | 0.00 | 0.00 |
November | 0.305069E+09 | -186887639.2 | 0.00 | 0.00 | 720.00 | 0.00 | -118181216.8 | 58.99 | 0.00 | 0.00 |
December | 0.322736E+09 | -198856403.7 | 0.00 | 0.00 | 744.00 | 0.00 | -123879728.4 | 59.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.367416E+10 | -0.228539E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.138877E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.284701E+09 | -211882044.5 | 0.00 | 0.00 | 672.00 | 0.00 | -124333556.9 | 58.97 | 0.00 | 0.00 |
Maximum of Months | 0.333530E+09 | -175369675.0 | 0.00 | 0.00 | 744.00 | 0.00 | -109158865.7 | 59.01 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK5
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.319701E+09 | -193897273.0 | 0.00 | 0.00 | 744.00 | 0.00 | -125803317.4 | 59.00 | 0.00 | 0.00 |
February | 0.290431E+09 | -177538145.1 | 0.00 | 0.00 | 672.00 | 0.00 | -112893109.9 | 58.99 | 0.00 | 0.00 |
March | 0.324044E+09 | -200431707.5 | 0.00 | 0.00 | 744.00 | 0.00 | -123612083.4 | 58.99 | 0.00 | 0.00 |
April | 0.300834E+09 | -183482076.5 | 0.00 | 0.00 | 720.00 | 0.00 | -117352304.8 | 58.99 | 0.00 | 0.00 |
May | 0.301960E+09 | -184208019.4 | 0.00 | 0.00 | 744.00 | 0.00 | -117751629.0 | 58.99 | 0.00 | 0.00 |
June | 0.284841E+09 | -174076120.8 | 0.00 | 0.00 | 720.00 | 0.00 | -110764828.3 | 58.99 | 0.00 | 0.00 |
July | 0.280922E+09 | -168093319.3 | 0.00 | 0.00 | 744.00 | 0.00 | -112828598.9 | 58.98 | 0.00 | 0.00 |
August | 0.286564E+09 | -173893902.2 | 0.00 | 0.00 | 744.00 | 0.00 | -112670030.5 | 59.00 | 0.00 | 0.00 |
September | 0.277092E+09 | -165968096.4 | 0.00 | 0.00 | 720.00 | 0.00 | -111123452.1 | 59.00 | 0.00 | 0.00 |
October | 0.295338E+09 | -175249613.1 | 0.00 | 0.00 | 744.00 | 0.00 | -120088701.7 | 58.99 | 0.00 | 0.00 |
November | 0.296315E+09 | -176506368.6 | 0.00 | 0.00 | 720.00 | 0.00 | -119808199.5 | 58.99 | 0.00 | 0.00 |
December | 0.313316E+09 | -188072132.3 | 0.00 | 0.00 | 744.00 | 0.00 | -125244080.5 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.357136E+10 | -0.216142E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.140994E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.277092E+09 | -200431707.5 | 0.00 | 0.00 | 672.00 | 0.00 | -125803317.4 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.324044E+09 | -165968096.4 | 0.00 | 0.00 | 744.00 | 0.00 | -110764828.3 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK6
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.319652E+09 | -193896328.9 | 0.00 | 0.00 | 744.00 | 0.00 | -125755939.3 | 59.00 | 0.00 | 0.00 |
February | 0.290374E+09 | -177537558.2 | 0.00 | 0.00 | 672.00 | 0.00 | -112836766.6 | 58.99 | 0.00 | 0.00 |
March | 0.323936E+09 | -200430218.8 | 0.00 | 0.00 | 744.00 | 0.00 | -123505969.1 | 58.99 | 0.00 | 0.00 |
April | 0.300521E+09 | -183484165.7 | 0.00 | 0.00 | 720.00 | 0.00 | -117037250.6 | 58.99 | 0.00 | 0.00 |
May | 0.301384E+09 | -184193094.6 | 0.00 | 0.00 | 744.00 | 0.00 | -117190674.4 | 59.00 | 0.00 | 0.00 |
June | 0.284518E+09 | -174070645.9 | 0.00 | 0.00 | 720.00 | 0.00 | -110447241.0 | 58.99 | 0.00 | 0.00 |
July | 0.280865E+09 | -168074095.8 | 0.00 | 0.00 | 744.00 | 0.00 | -112790987.0 | 58.99 | 0.00 | 0.00 |
August | 0.286529E+09 | -173891646.7 | 0.00 | 0.00 | 744.00 | 0.00 | -112636890.6 | 59.00 | 0.00 | 0.00 |
September | 0.276687E+09 | -165992710.6 | 0.00 | 0.00 | 720.00 | 0.00 | -110693969.1 | 58.99 | 0.00 | 0.00 |
October | 0.294937E+09 | -175208935.8 | 0.00 | 0.00 | 744.00 | 0.00 | -119728332.2 | 59.00 | 0.00 | 0.00 |
November | 0.296246E+09 | -176495156.1 | 0.00 | 0.00 | 720.00 | 0.00 | -119750413.5 | 58.99 | 0.00 | 0.00 |
December | 0.313290E+09 | -188065251.2 | 0.00 | 0.00 | 744.00 | 0.00 | -125224569.4 | 59.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.356894E+10 | -0.216134E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.140760E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.276687E+09 | -200430218.8 | 0.00 | 0.00 | 672.00 | 0.00 | -125755939.3 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.323936E+09 | -165992710.6 | 0.00 | 0.00 | 744.00 | 0.00 | -110447241.0 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK7
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.319747E+09 | -193897612.4 | 0.00 | 0.00 | 744.00 | 0.00 | -125849164.4 | 59.00 | 0.00 | 0.00 |
February | 0.290474E+09 | -177536305.5 | 0.00 | 0.00 | 672.00 | 0.00 | -112937281.4 | 58.99 | 0.00 | 0.00 |
March | 0.324066E+09 | -200436163.8 | 0.00 | 0.00 | 744.00 | 0.00 | -123630174.0 | 58.99 | 0.00 | 0.00 |
April | 0.300680E+09 | -183484574.9 | 0.00 | 0.00 | 720.00 | 0.00 | -117195484.5 | 58.99 | 0.00 | 0.00 |
May | 0.301553E+09 | -184213459.5 | 0.00 | 0.00 | 744.00 | 0.00 | -117339196.4 | 58.99 | 0.00 | 0.00 |
June | 0.284632E+09 | -174052976.7 | 0.00 | 0.00 | 720.00 | 0.00 | -110578952.4 | 59.00 | 0.00 | 0.00 |
July | 0.280959E+09 | -168036616.6 | 0.00 | 0.00 | 744.00 | 0.00 | -112922546.3 | 59.00 | 0.00 | 0.00 |
August | 0.286587E+09 | -173906558.0 | 0.00 | 0.00 | 744.00 | 0.00 | -112680033.0 | 58.99 | 0.00 | 0.00 |
September | 0.276784E+09 | -166022015.0 | 0.00 | 0.00 | 720.00 | 0.00 | -110761668.6 | 58.98 | 0.00 | 0.00 |
October | 0.295081E+09 | -175210699.4 | 0.00 | 0.00 | 744.00 | 0.00 | -119870303.0 | 59.00 | 0.00 | 0.00 |
November | 0.296355E+09 | -176493322.1 | 0.00 | 0.00 | 720.00 | 0.00 | -119862149.4 | 58.99 | 0.00 | 0.00 |
December | 0.313383E+09 | -188066981.2 | 0.00 | 0.00 | 744.00 | 0.00 | -125315934.3 | 59.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.357030E+10 | -0.216136E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.140894E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.276784E+09 | -200436163.8 | 0.00 | 0.00 | 672.00 | 0.00 | -125849164.4 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.324066E+09 | -166022015.0 | 0.00 | 0.00 | 744.00 | 0.00 | -110578952.4 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 237.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 259.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 247.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 379.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 427.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 375.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 471.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 366.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 301.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 245.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 242.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 160.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3714.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 160.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 471.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 HEATING COIL
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.136765E+11 | 54590.70 | 01-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.943335E+10 | 54590.70 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.524100E+10 | 54590.70 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.195211E+10 | 54590.70 | 01-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.223856E+09 | 18409.64 | 18-MAY-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 9830957.00 | 4122.25 | 28-SEP-08:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.125262E+10 | 54590.70 | 28-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.712484E+10 | 54590.70 | 10-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.118193E+11 | 54590.70 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.507334E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.136765E+11 | 54590.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 HEATING COIL
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.342821E+10 | 28482.14 | 01-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.202300E+10 | 28482.14 | 08-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.517136E+09 | 28482.14 | 24-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 68693498.63 | 16464.51 | 19-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 903015.94 | 712.27 | 18-MAY-08:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 7081322.78 | 1298.21 | 28-OCT-08:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.131184E+10 | 28482.14 | 24-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.269447E+10 | 28482.14 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.100513E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.342821E+10 | 28482.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3 HEATING COIL
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.439698E+10 | 29241.71 | 01-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.271634E+10 | 29241.71 | 12-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.954175E+09 | 27649.01 | 06-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.195128E+09 | 11240.17 | 19-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 1856001.18 | 1340.57 | 18-MAY-07:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 49900273.97 | 3472.09 | 16-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.190975E+10 | 29241.71 | 24-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.358737E+10 | 29241.71 | 18-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.138115E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.439698E+10 | 29241.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4 HEATING COIL
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.463772E+10 | 29318.96 | 01-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.288924E+10 | 29318.96 | 05-FEB-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.112105E+10 | 29318.96 | 06-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.264629E+09 | 14270.35 | 19-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2803584.17 | 1341.43 | 18-MAY-07:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 95094313.09 | 4026.08 | 29-OCT-08:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.208846E+10 | 29318.96 | 13-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.380769E+10 | 29318.96 | 17-DEC-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.149067E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.463772E+10 | 29318.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5 HEATING COIL
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.502816E+10 | 29091.75 | 01-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.318854E+10 | 29091.75 | 05-FEB-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.140745E+10 | 29091.75 | 05-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.397101E+09 | 17895.27 | 19-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 10279184.55 | 1616.47 | 18-MAY-07:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.194983E+09 | 4830.87 | 29-OCT-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.237697E+10 | 29091.75 | 13-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.417810E+10 | 29091.75 | 09-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.167816E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.502816E+10 | 29091.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6 HEATING COIL
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.116126E+11 | 52598.82 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.787615E+10 | 52598.82 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.470979E+10 | 52598.82 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.189608E+10 | 52598.82 | 01-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.235832E+09 | 20529.50 | 29-MAY-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17490810.32 | 3765.93 | 27-SEP-08:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.149859E+10 | 52598.82 | 16-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.655262E+10 | 52598.82 | 10-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.100835E+11 | 52598.82 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.444826E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.116126E+11 | 52598.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7 HEATING COIL
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.538562E+10 | 26672.48 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.351506E+10 | 26672.48 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.181833E+10 | 26672.48 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.627139E+09 | 26672.48 | 01-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 47022904.52 | 11106.64 | 29-MAY-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 654695.25 | 735.69 | 28-SEP-08:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.441298E+09 | 26672.48 | 16-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.278789E+10 | 26672.48 | 10-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.456713E+10 | 26672.48 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.191901E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.538562E+10 | 26672.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8 HEATING COIL
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.548013E+10 | 26523.05 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.360141E+10 | 26523.05 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.190670E+10 | 26523.05 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.676915E+09 | 26523.05 | 01-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 56833116.09 | 13702.00 | 29-MAY-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 1223125.13 | 911.87 | 28-SEP-08:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.480802E+09 | 26523.05 | 16-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.286686E+10 | 26523.05 | 02-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.466151E+10 | 26523.05 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.197324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.548013E+10 | 26523.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9 HEATING COIL
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.590072E+10 | 26279.22 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.395550E+10 | 26279.22 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.225474E+10 | 26279.22 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.875026E+09 | 26279.22 | 01-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.106912E+09 | 23735.34 | 29-MAY-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6202032.21 | 2373.58 | 28-SEP-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.634686E+09 | 26279.22 | 16-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.317014E+10 | 26279.22 | 01-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.504619E+10 | 26279.22 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.219501E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.590072E+10 | 26279.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10 HEATING COIL
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.763103E+10 | 27450.62 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.530355E+10 | 27450.62 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.340590E+10 | 27450.62 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.147900E+10 | 27450.62 | 01-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.368019E+09 | 27450.62 | 18-MAY-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 11479365.51 | 9342.93 | 15-JUN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 37138095.04 | 19407.84 | 28-SEP-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.113916E+10 | 27450.62 | 14-OCT-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.420687E+10 | 27450.62 | 01-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.655037E+10 | 27450.62 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.301325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.763103E+10 | 27450.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.635086E+09 | 0.608582E+09 | 11887.25 | 27-APR-16:10 | 11393.09 | 0.00 |
May | 0.00 | 0.00 | 0.142042E+10 | 0.125662E+10 | 11098.91 | 06-MAY-13:00 | 8900.97 | 0.00 |
June | 0.00 | 0.00 | 0.264656E+10 | 0.247773E+10 | 13072.21 | 28-JUN-17:00 | 12622.08 | 0.00 |
July | 0.00 | 0.00 | 0.689074E+10 | 0.593336E+10 | 17748.61 | 31-JUL-16:10 | 15628.78 | 0.00 |
August | 0.00 | 0.00 | 0.919229E+10 | 0.794710E+10 | 19015.02 | 10-AUG-16:40 | 18589.54 | 0.00 |
September | 0.00 | 0.00 | 0.273099E+10 | 0.222449E+10 | 13541.06 | 14-SEP-16:10 | 11749.55 | 0.00 |
October | 0.00 | 0.00 | 0.121139E+09 | 0.119549E+09 | 6020.28 | 04-OCT-15:00 | 6020.28 | 0.00 |
November | 0.00 | 0.00 | 12652571.98 | 9457444.00 | 1914.24 | 04-NOV-14:00 | 1440.26 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.236499E+11 | 0.205769E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.919229E+10 | 0.794710E+10 | 19015.02 | 18589.54 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 1197475.39 | 1122956.01 | 850.38 | 27-FEB-21:10 | 802.75 | 0.00 |
March | 0.00 | 0.00 | 4867764.27 | 4642496.67 | 1731.63 | 10-MAR-21:20 | 1451.88 | 0.00 |
April | 0.00 | 0.00 | 0.467189E+09 | 0.457187E+09 | 17080.97 | 27-APR-20:01 | 14923.07 | 0.00 |
May | 0.00 | 0.00 | 0.955701E+09 | 0.875554E+09 | 17883.62 | 07-MAY-17:02 | 14109.64 | 0.00 |
June | 0.00 | 0.00 | 0.170183E+10 | 0.163583E+10 | 17630.75 | 11-JUN-18:00 | 14667.76 | 0.00 |
July | 0.00 | 0.00 | 0.408664E+10 | 0.364561E+10 | 18333.70 | 15-JUL-18:02 | 13162.45 | 0.00 |
August | 0.00 | 0.00 | 0.558544E+10 | 0.498995E+10 | 18199.80 | 26-AUG-18:02 | 11927.89 | 0.00 |
September | 0.00 | 0.00 | 0.158487E+10 | 0.135103E+10 | 18057.17 | 23-SEP-18:02 | 12482.89 | 0.00 |
October | 0.00 | 0.00 | 85064931.34 | 83630279.44 | 16579.60 | 04-OCT-20:01 | 16579.60 | 0.00 |
November | 0.00 | 0.00 | 20215185.19 | 16066183.59 | 2057.08 | 04-NOV-14:00 | 1633.39 | 0.00 |
December | 0.00 | 0.00 | 20214.76 | 20214.76 | 33.69 | 03-DEC-21:00 | 33.69 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.144930E+11 | 0.130606E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.558544E+10 | 0.498995E+10 | 18333.70 | 16579.60 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3 COOLING COIL
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 14.38 | 14.38 | 0.02 | 27-FEB-17:00 | 0.02 | 0.00 |
March | 0.00 | 0.00 | 0.67 | 0.67 | 0.00 | 18-MAR-13:30 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.368836E+09 | 0.361895E+09 | 7062.78 | 27-APR-16:10 | 6977.61 | 0.00 |
May | 0.00 | 0.00 | 0.726193E+09 | 0.668757E+09 | 7007.22 | 06-MAY-13:00 | 5916.30 | 0.00 |
June | 0.00 | 0.00 | 0.125463E+10 | 0.122116E+10 | 7143.08 | 28-JUN-17:00 | 7143.08 | 0.00 |
July | 0.00 | 0.00 | 0.301415E+10 | 0.272689E+10 | 9637.61 | 31-JUL-16:10 | 8740.29 | 0.00 |
August | 0.00 | 0.00 | 0.418481E+10 | 0.378113E+10 | 14723.57 | 10-AUG-06:03 | 9941.51 | 0.00 |
September | 0.00 | 0.00 | 0.125978E+10 | 0.108092E+10 | 7874.16 | 14-SEP-14:00 | 6685.70 | 0.00 |
October | 0.00 | 0.00 | 58395424.45 | 58189233.59 | 3497.80 | 04-OCT-15:00 | 3497.80 | 0.00 |
November | 0.00 | 0.00 | 13197031.65 | 10358929.58 | 1693.43 | 04-NOV-14:00 | 1343.92 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.108800E+11 | 0.990931E+10 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.418481E+10 | 0.378113E+10 | 14723.57 | 9941.51 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4 COOLING COIL
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 84.34 | 84.34 | 0.05 | 18-MAR-13:20 | 0.05 | 0.00 |
April | 0.00 | 0.00 | 0.354426E+09 | 0.347747E+09 | 6928.55 | 27-APR-16:10 | 6844.45 | 0.00 |
May | 0.00 | 0.00 | 0.700856E+09 | 0.645589E+09 | 6961.41 | 06-MAY-13:00 | 5876.86 | 0.00 |
June | 0.00 | 0.00 | 0.123014E+10 | 0.119744E+10 | 7117.29 | 28-JUN-17:00 | 7117.29 | 0.00 |
July | 0.00 | 0.00 | 0.299589E+10 | 0.271018E+10 | 9654.85 | 31-JUL-16:10 | 8756.60 | 0.00 |
August | 0.00 | 0.00 | 0.417711E+10 | 0.377379E+10 | 15210.73 | 10-AUG-06:03 | 10265.65 | 0.00 |
September | 0.00 | 0.00 | 0.124073E+10 | 0.106449E+10 | 7859.80 | 14-SEP-14:00 | 6673.23 | 0.00 |
October | 0.00 | 0.00 | 54930216.93 | 54780891.29 | 3404.30 | 04-OCT-15:00 | 3404.30 | 0.00 |
November | 0.00 | 0.00 | 10213488.17 | 8029999.99 | 1423.71 | 04-NOV-14:00 | 1129.37 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.107643E+11 | 0.980204E+10 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.417711E+10 | 0.377379E+10 | 15210.73 | 10265.65 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5 COOLING COIL
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 379.17 | 379.17 | 0.24 | 18-MAR-13:40 | 0.24 | 0.00 |
April | 0.00 | 0.00 | 0.323894E+09 | 0.317916E+09 | 6593.32 | 27-APR-16:10 | 6511.64 | 0.00 |
May | 0.00 | 0.00 | 0.631404E+09 | 0.581586E+09 | 6700.49 | 06-MAY-13:00 | 5649.37 | 0.00 |
June | 0.00 | 0.00 | 0.114677E+10 | 0.111669E+10 | 6952.55 | 28-JUN-17:00 | 6952.55 | 0.00 |
July | 0.00 | 0.00 | 0.286893E+10 | 0.259591E+10 | 9505.82 | 31-JUL-16:10 | 8616.24 | 0.00 |
August | 0.00 | 0.00 | 0.402620E+10 | 0.363952E+10 | 12684.43 | 10-AUG-06:03 | 8589.98 | 0.00 |
September | 0.00 | 0.00 | 0.116893E+10 | 0.100286E+10 | 7672.03 | 14-SEP-14:00 | 6506.96 | 0.00 |
October | 0.00 | 0.00 | 48037988.18 | 47966253.32 | 3161.17 | 04-OCT-15:00 | 3161.17 | 0.00 |
November | 0.00 | 0.00 | 5570497.97 | 4396222.06 | 953.76 | 04-NOV-14:00 | 755.64 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.102197E+11 | 0.930685E+10 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.402620E+10 | 0.363952E+10 | 12684.43 | 8616.24 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6 COOLING COIL
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.471364E+09 | 0.447874E+09 | 10947.95 | 27-APR-15:00 | 10166.56 | 0.00 |
May | 0.00 | 0.00 | 0.949634E+09 | 0.840182E+09 | 10511.79 | 06-MAY-13:30 | 8431.98 | 0.00 |
June | 0.00 | 0.00 | 0.191474E+10 | 0.179555E+10 | 11487.73 | 28-JUN-17:00 | 10938.19 | 0.00 |
July | 0.00 | 0.00 | 0.501211E+10 | 0.430710E+10 | 18490.49 | 24-JUL-07:03 | 14040.09 | 0.00 |
August | 0.00 | 0.00 | 0.699056E+10 | 0.601895E+10 | 18398.94 | 29-AUG-14:50 | 15993.22 | 0.00 |
September | 0.00 | 0.00 | 0.208538E+10 | 0.168882E+10 | 12972.84 | 14-SEP-14:10 | 10511.95 | 0.00 |
October | 0.00 | 0.00 | 84869806.60 | 84241632.95 | 5534.55 | 04-OCT-15:00 | 5534.55 | 0.00 |
November | 0.00 | 0.00 | 11162460.64 | 8297801.57 | 1789.53 | 04-NOV-14:40 | 1341.32 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.175198E+11 | 0.151910E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.699056E+10 | 0.601895E+10 | 18490.49 | 15993.22 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7 COOLING COIL
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 351.66 | 351.66 | 0.30 | 18-MAR-13:50 | 0.30 | 0.00 |
April | 0.00 | 0.00 | 0.268388E+09 | 0.261965E+09 | 6163.14 | 27-APR-15:00 | 5913.62 | 0.00 |
May | 0.00 | 0.00 | 0.496542E+09 | 0.455558E+09 | 5894.92 | 06-MAY-13:30 | 4948.76 | 0.00 |
June | 0.00 | 0.00 | 0.971672E+09 | 0.945784E+09 | 6347.53 | 28-JUN-17:00 | 6250.42 | 0.00 |
July | 0.00 | 0.00 | 0.255140E+10 | 0.229329E+10 | 9228.74 | 24-JUL-15:00 | 8849.40 | 0.00 |
August | 0.00 | 0.00 | 0.369075E+10 | 0.330952E+10 | 10036.65 | 29-AUG-14:50 | 8818.29 | 0.00 |
September | 0.00 | 0.00 | 0.100758E+10 | 0.861523E+09 | 7134.16 | 14-SEP-14:10 | 6047.56 | 0.00 |
October | 0.00 | 0.00 | 37714183.97 | 37688986.91 | 2959.27 | 04-OCT-15:00 | 2959.27 | 0.00 |
November | 0.00 | 0.00 | 3121447.24 | 2462445.43 | 659.03 | 04-NOV-14:50 | 521.81 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.902716E+10 | 0.816779E+10 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.369075E+10 | 0.330952E+10 | 10036.65 | 8849.40 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8 COOLING COIL
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 453.08 | 453.08 | 0.50 | 18-MAR-14:00 | 0.50 | 0.00 |
April | 0.00 | 0.00 | 0.261885E+09 | 0.255773E+09 | 6073.23 | 27-APR-15:00 | 5832.86 | 0.00 |
May | 0.00 | 0.00 | 0.481211E+09 | 0.441740E+09 | 5796.91 | 06-MAY-13:30 | 4868.17 | 0.00 |
June | 0.00 | 0.00 | 0.949170E+09 | 0.924539E+09 | 6277.97 | 28-JUN-17:00 | 6188.98 | 0.00 |
July | 0.00 | 0.00 | 0.250848E+10 | 0.225678E+10 | 9155.97 | 24-JUL-15:00 | 8788.71 | 0.00 |
August | 0.00 | 0.00 | 0.364072E+10 | 0.326765E+10 | 9960.62 | 29-AUG-15:00 | 8836.91 | 0.00 |
September | 0.00 | 0.00 | 0.988787E+09 | 0.846139E+09 | 7058.11 | 14-SEP-14:10 | 5986.25 | 0.00 |
October | 0.00 | 0.00 | 36083685.00 | 36070794.39 | 2888.18 | 04-OCT-15:00 | 2888.18 | 0.00 |
November | 0.00 | 0.00 | 2720052.95 | 2148676.85 | 597.34 | 04-NOV-14:40 | 473.19 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.886907E+10 | 0.803084E+10 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.364072E+10 | 0.326765E+10 | 9960.62 | 8836.91 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9 COOLING COIL
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 254.38 | 254.38 | 0.38 | 18-MAR-14:10 | 0.38 | 0.00 |
April | 0.00 | 0.00 | 0.242404E+09 | 0.236895E+09 | 5860.21 | 27-APR-15:00 | 5626.73 | 0.00 |
May | 0.00 | 0.00 | 0.435932E+09 | 0.400015E+09 | 5557.22 | 06-MAY-13:30 | 4659.38 | 0.00 |
June | 0.00 | 0.00 | 0.883708E+09 | 0.861367E+09 | 6138.28 | 28-JUN-17:00 | 6050.91 | 0.00 |
July | 0.00 | 0.00 | 0.240135E+10 | 0.216143E+10 | 9048.39 | 24-JUL-15:00 | 8687.73 | 0.00 |
August | 0.00 | 0.00 | 0.353314E+10 | 0.317179E+10 | 9836.28 | 29-AUG-15:00 | 8724.42 | 0.00 |
September | 0.00 | 0.00 | 0.939172E+09 | 0.803837E+09 | 6933.95 | 14-SEP-14:10 | 5876.14 | 0.00 |
October | 0.00 | 0.00 | 30431061.97 | 30429550.58 | 2614.21 | 04-OCT-15:00 | 2614.21 | 0.00 |
November | 0.00 | 0.00 | 1490265.61 | 1178157.37 | 385.22 | 04-NOV-14:40 | 304.95 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.846763E+10 | 0.766694E+10 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.353314E+10 | 0.317179E+10 | 9836.28 | 8724.42 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10 COOLING COIL
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 4153.82 | 4153.82 | 6.63 | 18-MAR-15:10 | 6.63 | 0.00 |
April | 0.00 | 0.00 | 0.229623E+09 | 0.224676E+09 | 5924.17 | 27-APR-15:00 | 5676.22 | 0.00 |
May | 0.00 | 0.00 | 0.403814E+09 | 0.371138E+09 | 5614.61 | 06-MAY-13:30 | 4703.09 | 0.00 |
June | 0.00 | 0.00 | 0.852482E+09 | 0.830722E+09 | 6197.59 | 28-JUN-15:00 | 6197.59 | 0.00 |
July | 0.00 | 0.00 | 0.238972E+10 | 0.215409E+10 | 9498.13 | 24-JUL-15:00 | 9098.12 | 0.00 |
August | 0.00 | 0.00 | 0.365374E+10 | 0.327878E+10 | 10229.56 | 29-AUG-14:50 | 8984.45 | 0.00 |
September | 0.00 | 0.00 | 0.926729E+09 | 0.791113E+09 | 7156.04 | 14-SEP-14:10 | 6064.32 | 0.00 |
October | 0.00 | 0.00 | 22612186.29 | 22610603.10 | 2177.79 | 04-OCT-15:00 | 2177.79 | 0.00 |
November | 0.00 | 0.00 | 110611.85 | 87442.26 | 51.47 | 04-NOV-14:50 | 40.70 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.847883E+10 | 0.767322E+10 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.365374E+10 | 0.327878E+10 | 10229.56 | 9098.12 | 0.00 |
Report: FanReportMonthly
For: PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.175532E+10 | 0.42 | 2002.42 | 01-JAN-08:61 | 0.89 |
February | 0.152329E+10 | 0.40 | 2002.42 | 01-FEB-08:61 | 0.89 |
March | 0.157465E+10 | 0.39 | 2002.42 | 01-MAR-08:61 | 0.89 |
April | 0.145021E+10 | 0.37 | 2002.42 | 01-APR-07:01 | 0.89 |
May | 0.145820E+10 | 0.36 | 1206.13 | 18-MAY-07:02 | 0.69 |
June | 0.141290E+10 | 0.37 | 800.97 | 02-JUN-13:00 | 0.54 |
July | 0.145379E+10 | 0.36 | 889.39 | 31-JUL-16:10 | 0.57 |
August | 0.146332E+10 | 0.36 | 1020.16 | 10-AUG-17:00 | 0.62 |
September | 0.141024E+10 | 0.36 | 891.69 | 28-SEP-08:15 | 0.58 |
October | 0.148084E+10 | 0.37 | 2002.42 | 28-OCT-07:01 | 0.89 |
November | 0.156136E+10 | 0.39 | 2002.42 | 10-NOV-08:61 | 0.89 |
December | 0.171994E+10 | 0.41 | 2002.42 | 01-DEC-08:61 | 0.89 |
Annual Sum or Average | 0.182641E+11 | 0.38 | |||
Minimum of Months | 0.141024E+10 | 0.36 | 800.97 | 0.54 | |
Maximum of Months | 0.175532E+10 | 0.42 | 2002.42 | 0.89 |
Report: FanReportMonthly
For: PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.152733E+10 | 0.47 | 1125.35 | 05-JAN-15:40 | 0.92 |
February | 0.138634E+10 | 0.49 | 1125.35 | 04-FEB-17:30 | 0.92 |
March | 0.157627E+10 | 0.53 | 1125.35 | 03-MAR-15:30 | 0.92 |
April | 0.161038E+10 | 0.59 | 1125.35 | 11-APR-10:10 | 0.92 |
May | 0.182778E+10 | 0.62 | 1125.35 | 15-MAY-10:20 | 0.92 |
June | 0.187877E+10 | 0.62 | 1125.35 | 02-JUN-12:20 | 0.92 |
July | 0.195552E+10 | 0.60 | 1125.35 | 01-JUL-13:30 | 0.92 |
August | 0.191076E+10 | 0.60 | 1125.35 | 09-AUG-15:30 | 0.91 |
September | 0.189050E+10 | 0.62 | 1125.35 | 10-SEP-08:20 | 0.91 |
October | 0.171156E+10 | 0.60 | 1125.35 | 01-OCT-09:15 | 0.91 |
November | 0.152430E+10 | 0.50 | 1125.35 | 13-NOV-12:00 | 0.92 |
December | 0.151923E+10 | 0.46 | 1125.35 | 14-DEC-20:00 | 0.92 |
Annual Sum or Average | 0.203187E+11 | 0.56 | |||
Minimum of Months | 0.138634E+10 | 0.46 | 1125.35 | 0.91 | |
Maximum of Months | 0.195552E+10 | 0.62 | 1125.35 | 0.92 |
Report: FanReportMonthly
For: PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.163761E+10 | 0.50 | 1131.57 | 01-JAN-09:40 | 0.92 |
February | 0.148281E+10 | 0.50 | 1131.57 | 01-FEB-08:08 | 0.92 |
March | 0.167020E+10 | 0.51 | 1131.57 | 01-MAR-08:20 | 0.92 |
April | 0.158873E+10 | 0.50 | 1131.57 | 01-APR-07:03 | 0.92 |
May | 0.165390E+10 | 0.50 | 1131.57 | 03-MAY-10:15 | 0.92 |
June | 0.161317E+10 | 0.50 | 1131.57 | 01-JUN-16:10 | 0.92 |
July | 0.162946E+10 | 0.49 | 1131.57 | 01-JUL-12:40 | 0.92 |
August | 0.167020E+10 | 0.50 | 1131.57 | 01-AUG-16:40 | 0.92 |
September | 0.158873E+10 | 0.50 | 1131.57 | 01-SEP-10:40 | 0.91 |
October | 0.163761E+10 | 0.50 | 1131.57 | 04-OCT-06:10 | 0.92 |
November | 0.158873E+10 | 0.50 | 1131.57 | 02-NOV-07:20 | 0.92 |
December | 0.162946E+10 | 0.49 | 1131.57 | 01-DEC-09:30 | 0.92 |
Annual Sum or Average | 0.193906E+11 | 0.50 | |||
Minimum of Months | 0.148281E+10 | 0.49 | 1131.57 | 0.91 | |
Maximum of Months | 0.167020E+10 | 0.51 | 1131.57 | 0.92 |
Report: FanReportMonthly
For: PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.164310E+10 | 0.50 | 1135.37 | 30-JAN-18:30 | 0.92 |
February | 0.148778E+10 | 0.50 | 1135.37 | 01-FEB-07:05 | 0.92 |
March | 0.167580E+10 | 0.51 | 1135.37 | 01-MAR-07:10 | 0.92 |
April | 0.159405E+10 | 0.50 | 1135.37 | 01-APR-06:07 | 0.92 |
May | 0.165945E+10 | 0.50 | 1135.37 | 01-MAY-06:10 | 0.92 |
June | 0.161858E+10 | 0.50 | 1135.37 | 01-JUN-06:10 | 0.91 |
July | 0.163493E+10 | 0.49 | 1135.37 | 01-JUL-06:20 | 0.91 |
August | 0.167580E+10 | 0.50 | 1135.37 | 01-AUG-06:03 | 0.91 |
September | 0.159405E+10 | 0.50 | 1135.37 | 01-SEP-06:05 | 0.91 |
October | 0.164310E+10 | 0.50 | 1135.37 | 01-OCT-07:10 | 0.91 |
November | 0.159405E+10 | 0.50 | 1135.37 | 01-NOV-06:10 | 0.92 |
December | 0.163493E+10 | 0.49 | 1135.37 | 04-DEC-19:00 | 0.92 |
Annual Sum or Average | 0.194556E+11 | 0.50 | |||
Minimum of Months | 0.148778E+10 | 0.49 | 1135.37 | 0.91 | |
Maximum of Months | 0.167580E+10 | 0.51 | 1135.37 | 0.92 |
Report: FanReportMonthly
For: PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.162695E+10 | 0.50 | 1124.20 | 01-JAN-13:00 | 0.92 |
February | 0.147316E+10 | 0.50 | 1124.20 | 01-FEB-07:30 | 0.92 |
March | 0.165933E+10 | 0.51 | 1124.20 | 01-MAR-08:04 | 0.92 |
April | 0.157838E+10 | 0.50 | 1124.20 | 01-APR-07:01 | 0.92 |
May | 0.164314E+10 | 0.50 | 1124.20 | 03-MAY-13:00 | 0.92 |
June | 0.160267E+10 | 0.50 | 1124.20 | 02-JUN-11:10 | 0.92 |
July | 0.161885E+10 | 0.49 | 1124.20 | 01-JUL-06:20 | 0.91 |
August | 0.165933E+10 | 0.50 | 1124.20 | 01-AUG-17:30 | 0.91 |
September | 0.157838E+10 | 0.50 | 1124.20 | 02-SEP-06:10 | 0.91 |
October | 0.162695E+10 | 0.50 | 1124.20 | 04-OCT-11:50 | 0.92 |
November | 0.157838E+10 | 0.50 | 1124.20 | 01-NOV-07:07 | 0.92 |
December | 0.161885E+10 | 0.49 | 1124.20 | 01-DEC-10:40 | 0.92 |
Annual Sum or Average | 0.192644E+11 | 0.50 | |||
Minimum of Months | 0.147316E+10 | 0.49 | 1124.20 | 0.91 | |
Maximum of Months | 0.165933E+10 | 0.51 | 1124.20 | 0.92 |
Report: FanReportMonthly
For: PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.127199E+10 | 0.31 | 1907.87 | 01-JAN-09:01 | 0.89 |
February | 0.109451E+10 | 0.30 | 1907.87 | 01-FEB-08:61 | 0.89 |
March | 0.114374E+10 | 0.29 | 1907.87 | 01-MAR-08:61 | 0.89 |
April | 0.103030E+10 | 0.28 | 1907.87 | 01-APR-07:01 | 0.89 |
May | 0.103538E+10 | 0.27 | 1209.93 | 29-MAY-08:61 | 0.71 |
June | 0.100552E+10 | 0.27 | 763.15 | 20-JUN-09:50 | 0.54 |
July | 0.101452E+10 | 0.27 | 972.87 | 24-JUL-07:03 | 0.62 |
August | 0.104608E+10 | 0.27 | 944.54 | 29-AUG-15:00 | 0.61 |
September | 0.989418E+09 | 0.27 | 845.10 | 27-SEP-08:20 | 0.57 |
October | 0.105187E+10 | 0.27 | 1907.87 | 16-OCT-07:01 | 0.89 |
November | 0.113164E+10 | 0.29 | 1907.87 | 10-NOV-08:61 | 0.89 |
December | 0.123321E+10 | 0.30 | 1907.87 | 01-DEC-08:61 | 0.89 |
Annual Sum or Average | 0.130482E+11 | 0.28 | |||
Minimum of Months | 0.989418E+09 | 0.27 | 763.15 | 0.54 | |
Maximum of Months | 0.127199E+10 | 0.31 | 1907.87 | 0.89 |
Report: FanReportMonthly
For: PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.135975E+10 | 0.46 | 1018.08 | 02-JAN-19:00 | 0.92 |
February | 0.123147E+10 | 0.46 | 1018.08 | 01-FEB-08:40 | 0.92 |
March | 0.138907E+10 | 0.47 | 1018.08 | 19-MAR-10:40 | 0.92 |
April | 0.131944E+10 | 0.46 | 1018.08 | 12-APR-09:10 | 0.92 |
May | 0.137441E+10 | 0.46 | 1018.08 | 04-MAY-17:50 | 0.92 |
June | 0.134143E+10 | 0.47 | 1018.08 | 08-JUN-19:50 | 0.92 |
July | 0.135242E+10 | 0.45 | 1018.08 | 30-JUL-08:50 | 0.91 |
August | 0.138907E+10 | 0.47 | 1018.08 | 11-AUG-15:30 | 0.91 |
September | 0.131944E+10 | 0.46 | 1018.08 | 09-SEP-11:00 | 0.92 |
October | 0.135975E+10 | 0.46 | 1018.08 | 18-OCT-10:00 | 0.92 |
November | 0.131944E+10 | 0.46 | 1018.08 | 07-NOV-09:40 | 0.91 |
December | 0.135242E+10 | 0.46 | 1018.08 | 01-DEC-15:30 | 0.92 |
Annual Sum or Average | 0.161081E+11 | 0.46 | |||
Minimum of Months | 0.123147E+10 | 0.45 | 1018.08 | 0.91 | |
Maximum of Months | 0.138907E+10 | 0.47 | 1018.08 | 0.92 |
Report: FanReportMonthly
For: PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.135011E+10 | 0.46 | 1010.87 | 01-JAN-13:00 | 0.92 |
February | 0.122274E+10 | 0.46 | 1010.87 | 01-FEB-14:10 | 0.92 |
March | 0.137923E+10 | 0.47 | 1010.87 | 01-MAR-11:30 | 0.92 |
April | 0.131008E+10 | 0.46 | 1010.87 | 01-APR-08:40 | 0.92 |
May | 0.136467E+10 | 0.46 | 1010.87 | 23-MAY-09:00 | 0.92 |
June | 0.133192E+10 | 0.47 | 1010.87 | 17-JUN-14:40 | 0.92 |
July | 0.134283E+10 | 0.45 | 1010.87 | 08-JUL-09:30 | 0.91 |
August | 0.137923E+10 | 0.47 | 1010.87 | 12-AUG-09:50 | 0.91 |
September | 0.131008E+10 | 0.46 | 1010.87 | 02-SEP-15:30 | 0.91 |
October | 0.135011E+10 | 0.46 | 1010.87 | 04-OCT-17:10 | 0.92 |
November | 0.131008E+10 | 0.46 | 1010.87 | 01-NOV-11:40 | 0.91 |
December | 0.134283E+10 | 0.46 | 1010.87 | 04-DEC-08:40 | 0.92 |
Annual Sum or Average | 0.159939E+11 | 0.46 | |||
Minimum of Months | 0.122274E+10 | 0.45 | 1010.87 | 0.91 | |
Maximum of Months | 0.137923E+10 | 0.47 | 1010.87 | 0.92 |
Report: FanReportMonthly
For: PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.134099E+10 | 0.46 | 1004.03 | 01-JAN-12:30 | 0.92 |
February | 0.121448E+10 | 0.46 | 1004.03 | 01-FEB-08:08 | 0.92 |
March | 0.136990E+10 | 0.47 | 1004.03 | 01-MAR-08:30 | 0.92 |
April | 0.130123E+10 | 0.46 | 1004.03 | 01-APR-09:40 | 0.92 |
May | 0.135545E+10 | 0.46 | 1004.03 | 04-MAY-12:50 | 0.91 |
June | 0.132291E+10 | 0.47 | 1004.03 | 03-JUN-16:00 | 0.92 |
July | 0.133376E+10 | 0.45 | 1004.03 | 03-JUL-15:40 | 0.92 |
August | 0.136990E+10 | 0.47 | 1004.03 | 04-AUG-13:00 | 0.91 |
September | 0.130123E+10 | 0.46 | 1004.03 | 02-SEP-16:50 | 0.92 |
October | 0.134099E+10 | 0.46 | 1004.03 | 13-OCT-08:13 | 0.92 |
November | 0.130123E+10 | 0.46 | 1004.03 | 01-NOV-11:40 | 0.91 |
December | 0.133376E+10 | 0.46 | 1004.03 | 01-DEC-17:30 | 0.92 |
Annual Sum or Average | 0.158858E+11 | 0.46 | |||
Minimum of Months | 0.121448E+10 | 0.45 | 1004.03 | 0.91 | |
Maximum of Months | 0.136990E+10 | 0.47 | 1004.03 | 0.92 |
Report: FanReportMonthly
For: PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.142673E+10 | 0.46 | 1068.11 | 11-JAN-14:20 | 0.92 |
February | 0.129244E+10 | 0.46 | 1068.11 | 01-FEB-08:07 | 0.92 |
March | 0.145733E+10 | 0.47 | 1068.11 | 01-MAR-11:40 | 0.92 |
April | 0.138427E+10 | 0.46 | 1068.11 | 01-APR-07:07 | 0.92 |
May | 0.144194E+10 | 0.46 | 1068.11 | 20-MAY-09:30 | 0.92 |
June | 0.140734E+10 | 0.47 | 1068.11 | 16-JUN-08:40 | 0.92 |
July | 0.141887E+10 | 0.45 | 1068.11 | 01-JUL-13:20 | 0.92 |
August | 0.145733E+10 | 0.47 | 1068.11 | 10-AUG-13:20 | 0.91 |
September | 0.138427E+10 | 0.46 | 1068.11 | 23-SEP-10:10 | 0.91 |
October | 0.142656E+10 | 0.46 | 1068.11 | 13-OCT-19:10 | 0.92 |
November | 0.138427E+10 | 0.46 | 1068.11 | 03-NOV-14:10 | 0.91 |
December | 0.141887E+10 | 0.46 | 1068.11 | 01-DEC-08:06 | 0.92 |
Annual Sum or Average | 0.169002E+11 | 0.46 | |||
Minimum of Months | 0.129244E+10 | 0.45 | 1068.11 | 0.91 | |
Maximum of Months | 0.145733E+10 | 0.47 | 1068.11 | 0.92 |
Report: ZoneTemperatureOscillationReportMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.175532E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.152329E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.157465E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.161647E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.181950E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.208588E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.315792E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.372358E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.208266E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.151230E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.156485E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.171994E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.241364E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.151230E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.372358E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.152733E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.138663E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.157744E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.171480E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.203593E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.224948E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.282745E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.309572E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.222718E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.173089E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.152905E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.151924E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.234211E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.138663E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.309572E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_3:3
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.163761E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.148281E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.167020E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.167159E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.181431E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.189116E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.228225E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.256915E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.185926E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.165082E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.159185E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.162946E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.217505E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.148281E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.256915E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_4:4
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.164310E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.148778E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.167580E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.167403E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.181457E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.189144E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.228417E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.257345E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.186070E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.165555E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.159649E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.163493E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.217920E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.148778E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.257345E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_5:5
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.162695E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.147316E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.165933E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.165205E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.178350E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.185778E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.224220E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.252637E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.183014E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.163788E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.157973E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.161885E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.214879E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.147316E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.252637E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_6:6
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.127199E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.109451E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.114374E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.115475E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.127937E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.149729E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.226314E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.277149E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.150368E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.107401E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.113472E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.123321E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.174219E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.107401E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.277149E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_7:7
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.135975E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.123147E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.138907E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.138100E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.148533E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.155889E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.190784E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.218490E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.153656E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.136837E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.132019E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.135242E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.180758E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.123147E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.218490E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_8:8
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.135011E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.122274E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.137923E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.137025E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.147232E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.154456E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.188932E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.216469E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.152332E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.135837E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.131074E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.134283E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.179285E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.122274E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.216469E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_9:9
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.134099E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.121448E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.136990E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.135725E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.145349E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.152158E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.185819E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.213328E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.150434E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.134801E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.130159E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.133376E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.177369E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.121448E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.213328E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_10:10
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.142673E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.129244E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.145733E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.143766E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.153336E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.159978E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.194165E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.224543E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.158568E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.143187E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.138429E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.141887E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.187551E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.129244E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.224543E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.175532E+10 | 0.00 | 0.136765E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.152329E+10 | 0.00 | 0.943335E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.157465E+10 | 0.00 | 0.524100E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.145021E+10 | 0.635086E+09 | 0.195211E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.145820E+10 | 0.142042E+10 | 0.223856E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.141290E+10 | 0.264656E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.145379E+10 | 0.689074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.146332E+10 | 0.919229E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.141024E+10 | 0.273099E+10 | 9830957.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.148084E+10 | 0.121139E+09 | 0.125262E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.156136E+10 | 12652571.98 | 0.712484E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.171994E+10 | 0.00 | 0.118193E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.182641E+11 | 0.236499E+11 | 0.507334E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.141024E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.175532E+10 | 0.919229E+10 | 0.136765E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.152733E+10 | 0.00 | 0.342821E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.138634E+10 | 1197475.39 | 0.202300E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.157627E+10 | 4867764.27 | 0.517136E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.161038E+10 | 0.467189E+09 | 68693498.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.182778E+10 | 0.955701E+09 | 903015.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.187877E+10 | 0.170183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.195552E+10 | 0.408664E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.191076E+10 | 0.558544E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.189050E+10 | 0.158487E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.171156E+10 | 85064931.34 | 7081322.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.152430E+10 | 20215185.19 | 0.131184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.151923E+10 | 20214.76 | 0.269447E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.203187E+11 | 0.144930E+11 | 0.100513E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.138634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.195552E+10 | 0.558544E+10 | 0.342821E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_3:3
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.163761E+10 | 0.00 | 0.439698E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.148281E+10 | 14.38 | 0.271634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.167020E+10 | 0.67 | 0.954175E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.158873E+10 | 0.368836E+09 | 0.195128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.165390E+10 | 0.726193E+09 | 1856001.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.161317E+10 | 0.125463E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.162946E+10 | 0.301415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.167020E+10 | 0.418481E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.158873E+10 | 0.125978E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.163761E+10 | 58395424.45 | 49900273.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.158873E+10 | 13197031.65 | 0.190975E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.162946E+10 | 0.00 | 0.358737E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.193906E+11 | 0.108800E+11 | 0.138115E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.148281E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.167020E+10 | 0.418481E+10 | 0.439698E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_4:4
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.164310E+10 | 0.00 | 0.463772E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.148778E+10 | 0.00 | 0.288924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.167580E+10 | 84.34 | 0.112105E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.159405E+10 | 0.354426E+09 | 0.264629E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.165945E+10 | 0.700856E+09 | 2803584.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.161858E+10 | 0.123014E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.163493E+10 | 0.299589E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.167580E+10 | 0.417711E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.159405E+10 | 0.124073E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.164310E+10 | 54930216.93 | 95094313.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.159405E+10 | 10213488.17 | 0.208846E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.163493E+10 | 0.00 | 0.380769E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.194556E+11 | 0.107643E+11 | 0.149067E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.148778E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.167580E+10 | 0.417711E+10 | 0.463772E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_5:5
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.162695E+10 | 0.00 | 0.502816E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.147316E+10 | 0.00 | 0.318854E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.165933E+10 | 379.17 | 0.140745E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.157838E+10 | 0.323894E+09 | 0.397101E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.164314E+10 | 0.631404E+09 | 10279184.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.160267E+10 | 0.114677E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.161885E+10 | 0.286893E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.165933E+10 | 0.402620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.157838E+10 | 0.116893E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.162695E+10 | 48037988.18 | 0.194983E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.157838E+10 | 5570497.97 | 0.237697E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.161885E+10 | 0.00 | 0.417810E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.192644E+11 | 0.102197E+11 | 0.167816E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.147316E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.165933E+10 | 0.402620E+10 | 0.502816E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_6:6
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.127199E+10 | 0.00 | 0.116126E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109451E+10 | 0.00 | 0.787615E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.114374E+10 | 0.00 | 0.470979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.103030E+10 | 0.471364E+09 | 0.189608E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.103538E+10 | 0.949634E+09 | 0.235832E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.100552E+10 | 0.191474E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.101452E+10 | 0.501211E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.104608E+10 | 0.699056E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.989418E+09 | 0.208538E+10 | 17490810.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.105187E+10 | 84869806.60 | 0.149859E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.113164E+10 | 11162460.64 | 0.655262E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.123321E+10 | 0.00 | 0.100835E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.130482E+11 | 0.175198E+11 | 0.444826E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.989418E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.127199E+10 | 0.699056E+10 | 0.116126E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_7:7
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.135975E+10 | 0.00 | 0.538562E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.123147E+10 | 0.00 | 0.351506E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.138907E+10 | 351.66 | 0.181833E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.131944E+10 | 0.268388E+09 | 0.627139E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.137441E+10 | 0.496542E+09 | 47022904.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.134143E+10 | 0.971672E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.135242E+10 | 0.255140E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.138907E+10 | 0.369075E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.131944E+10 | 0.100758E+10 | 654695.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.135975E+10 | 37714183.97 | 0.441298E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.131944E+10 | 3121447.24 | 0.278789E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.135242E+10 | 0.00 | 0.456713E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.161081E+11 | 0.902716E+10 | 0.191901E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.123147E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.138907E+10 | 0.369075E+10 | 0.538562E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_8:8
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.135011E+10 | 0.00 | 0.548013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.122274E+10 | 0.00 | 0.360141E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.137923E+10 | 453.08 | 0.190670E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.131008E+10 | 0.261885E+09 | 0.676915E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.136467E+10 | 0.481211E+09 | 56833116.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.133192E+10 | 0.949170E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.134283E+10 | 0.250848E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.137923E+10 | 0.364072E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.131008E+10 | 0.988787E+09 | 1223125.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.135011E+10 | 36083685.00 | 0.480802E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.131008E+10 | 2720052.95 | 0.286686E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.134283E+10 | 0.00 | 0.466151E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.159939E+11 | 0.886907E+10 | 0.197324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.122274E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.137923E+10 | 0.364072E+10 | 0.548013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_9:9
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.134099E+10 | 0.00 | 0.590072E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121448E+10 | 0.00 | 0.395550E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.136990E+10 | 254.38 | 0.225474E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.130123E+10 | 0.242404E+09 | 0.875026E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.135545E+10 | 0.435932E+09 | 0.106912E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.132291E+10 | 0.883708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.133376E+10 | 0.240135E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.136990E+10 | 0.353314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.130123E+10 | 0.939172E+09 | 6202032.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.134099E+10 | 30431061.97 | 0.634686E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.130123E+10 | 1490265.61 | 0.317014E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.133376E+10 | 0.00 | 0.504619E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.158858E+11 | 0.846763E+10 | 0.219501E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.121448E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.136990E+10 | 0.353314E+10 | 0.590072E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_10:10
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.142673E+10 | 0.00 | 0.763103E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.129244E+10 | 0.00 | 0.530355E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145733E+10 | 4153.82 | 0.340590E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.138427E+10 | 0.229623E+09 | 0.147900E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.144194E+10 | 0.403814E+09 | 0.368019E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.140734E+10 | 0.852482E+09 | 11479365.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.141887E+10 | 0.238972E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.145733E+10 | 0.365374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.138427E+10 | 0.926729E+09 | 37138095.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.142656E+10 | 22612186.29 | 0.113916E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.138427E+10 | 110611.85 | 0.420687E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.141887E+10 | 0.00 | 0.655037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.169002E+11 | 0.847883E+10 | 0.301325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.129244E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145733E+10 | 0.365374E+10 | 0.763103E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.175532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.152329E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.157465E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.145021E+10 | 0.00 | 0.00 | 0.00 | 0.166266E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.145820E+10 | 0.00 | 0.00 | 0.00 | 0.361301E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.141290E+10 | 0.00 | 0.00 | 0.00 | 0.672976E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.145379E+10 | 0.00 | 0.00 | 0.00 | 0.170413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.146332E+10 | 0.00 | 0.00 | 0.00 | 0.226026E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.141024E+10 | 0.00 | 0.00 | 0.00 | 0.672419E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.148084E+10 | 0.00 | 0.00 | 0.00 | 31461251.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.156136E+10 | 0.00 | 0.00 | 0.00 | 3492276.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.171994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.182641E+11 | 0.00 | 0.00 | 0.00 | 0.587231E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.141024E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.175532E+10 | 0.00 | 0.00 | 0.00 | 0.226026E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.152733E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.138634E+10 | 0.00 | 0.00 | 0.00 | 291006.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.157627E+10 | 0.00 | 0.00 | 0.00 | 1165196.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.161038E+10 | 0.00 | 0.00 | 0.00 | 0.104422E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.182778E+10 | 0.00 | 0.00 | 0.00 | 0.208142E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.187877E+10 | 0.00 | 0.00 | 0.00 | 0.370707E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.195552E+10 | 0.00 | 0.00 | 0.00 | 0.871926E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.191076E+10 | 0.00 | 0.00 | 0.00 | 0.118495E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.189050E+10 | 0.00 | 0.00 | 0.00 | 0.336678E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.171156E+10 | 0.00 | 0.00 | 0.00 | 19323799.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.152430E+10 | 0.00 | 0.00 | 0.00 | 4751950.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.151923E+10 | 0.00 | 0.00 | 0.00 | 4975.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.203187E+11 | 0.00 | 0.00 | 0.00 | 0.310236E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.138634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.195552E+10 | 0.00 | 0.00 | 0.00 | 0.118495E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_3:3
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.163761E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.148281E+10 | 0.00 | 0.00 | 0.00 | 3.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.167020E+10 | 0.00 | 0.00 | 0.00 | 0.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.158873E+10 | 0.00 | 0.00 | 0.00 | 82861604.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.165390E+10 | 0.00 | 0.00 | 0.00 | 0.160408E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.161317E+10 | 0.00 | 0.00 | 0.00 | 0.277992E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.162946E+10 | 0.00 | 0.00 | 0.00 | 0.652785E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.167020E+10 | 0.00 | 0.00 | 0.00 | 0.898951E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.158873E+10 | 0.00 | 0.00 | 0.00 | 0.270538E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.163761E+10 | 0.00 | 0.00 | 0.00 | 13206720.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.158873E+10 | 0.00 | 0.00 | 0.00 | 3123304.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.162946E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.193906E+11 | 0.00 | 0.00 | 0.00 | 0.235987E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.148281E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.167020E+10 | 0.00 | 0.00 | 0.00 | 0.898951E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_4:4
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.164310E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.148778E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.167580E+10 | 0.00 | 0.00 | 0.00 | 20.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.159405E+10 | 0.00 | 0.00 | 0.00 | 79971186.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.165945E+10 | 0.00 | 0.00 | 0.00 | 0.155118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.161858E+10 | 0.00 | 0.00 | 0.00 | 0.272859E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.163493E+10 | 0.00 | 0.00 | 0.00 | 0.649241E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.167580E+10 | 0.00 | 0.00 | 0.00 | 0.897654E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.159405E+10 | 0.00 | 0.00 | 0.00 | 0.266647E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.164310E+10 | 0.00 | 0.00 | 0.00 | 12443973.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.159405E+10 | 0.00 | 0.00 | 0.00 | 2435626.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.163493E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.194556E+11 | 0.00 | 0.00 | 0.00 | 0.233637E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.148778E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.167580E+10 | 0.00 | 0.00 | 0.00 | 0.897654E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_5:5
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.162695E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.147316E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.165933E+10 | 0.00 | 0.00 | 0.00 | 93.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.157838E+10 | 0.00 | 0.00 | 0.00 | 73664023.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.164314E+10 | 0.00 | 0.00 | 0.00 | 0.140362E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.160267E+10 | 0.00 | 0.00 | 0.00 | 0.255112E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.161885E+10 | 0.00 | 0.00 | 0.00 | 0.623344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.165933E+10 | 0.00 | 0.00 | 0.00 | 0.867049E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.157838E+10 | 0.00 | 0.00 | 0.00 | 0.251761E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.162695E+10 | 0.00 | 0.00 | 0.00 | 10933995.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.157838E+10 | 0.00 | 0.00 | 0.00 | 1344213.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.161885E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.192644E+11 | 0.00 | 0.00 | 0.00 | 0.222357E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.147316E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.165933E+10 | 0.00 | 0.00 | 0.00 | 0.867049E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_6:6
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.127199E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109451E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.114374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.103030E+10 | 0.00 | 0.00 | 0.00 | 0.124447E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.103538E+10 | 0.00 | 0.00 | 0.00 | 0.243986E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.100552E+10 | 0.00 | 0.00 | 0.00 | 0.491773E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.101452E+10 | 0.00 | 0.00 | 0.00 | 0.124861E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.104608E+10 | 0.00 | 0.00 | 0.00 | 0.172541E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.989418E+09 | 0.00 | 0.00 | 0.00 | 0.514265E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.105187E+10 | 0.00 | 0.00 | 0.00 | 22142200.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.113164E+10 | 0.00 | 0.00 | 0.00 | 3075188.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.123321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.130482E+11 | 0.00 | 0.00 | 0.00 | 0.437371E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.989418E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.127199E+10 | 0.00 | 0.00 | 0.00 | 0.172541E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_7:7
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.135975E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.123147E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.138907E+10 | 0.00 | 0.00 | 0.00 | 86.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.131944E+10 | 0.00 | 0.00 | 0.00 | 61559990.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.137441E+10 | 0.00 | 0.00 | 0.00 | 0.110918E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.134143E+10 | 0.00 | 0.00 | 0.00 | 0.217460E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.135242E+10 | 0.00 | 0.00 | 0.00 | 0.555416E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.138907E+10 | 0.00 | 0.00 | 0.00 | 0.795822E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.131944E+10 | 0.00 | 0.00 | 0.00 | 0.217128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.135975E+10 | 0.00 | 0.00 | 0.00 | 8620686.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.131944E+10 | 0.00 | 0.00 | 0.00 | 756867.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.135242E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.161081E+11 | 0.00 | 0.00 | 0.00 | 0.196768E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.123147E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.138907E+10 | 0.00 | 0.00 | 0.00 | 0.795822E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_8:8
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.135011E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.122274E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.137923E+10 | 0.00 | 0.00 | 0.00 | 111.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.131008E+10 | 0.00 | 0.00 | 0.00 | 60162674.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.136467E+10 | 0.00 | 0.00 | 0.00 | 0.107646E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.133192E+10 | 0.00 | 0.00 | 0.00 | 0.212638E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.134283E+10 | 0.00 | 0.00 | 0.00 | 0.546482E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.137923E+10 | 0.00 | 0.00 | 0.00 | 0.785465E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.131008E+10 | 0.00 | 0.00 | 0.00 | 0.213238E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.135011E+10 | 0.00 | 0.00 | 0.00 | 8260740.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.131008E+10 | 0.00 | 0.00 | 0.00 | 660544.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.134283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.159939E+11 | 0.00 | 0.00 | 0.00 | 0.193455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.122274E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.137923E+10 | 0.00 | 0.00 | 0.00 | 0.785465E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_9:9
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.134099E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121448E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.136990E+10 | 0.00 | 0.00 | 0.00 | 62.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.130123E+10 | 0.00 | 0.00 | 0.00 | 56017810.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.135545E+10 | 0.00 | 0.00 | 0.00 | 98044376.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.132291E+10 | 0.00 | 0.00 | 0.00 | 0.198663E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.133376E+10 | 0.00 | 0.00 | 0.00 | 0.524434E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.136990E+10 | 0.00 | 0.00 | 0.00 | 0.763381E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.130123E+10 | 0.00 | 0.00 | 0.00 | 0.203109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.134099E+10 | 0.00 | 0.00 | 0.00 | 7023337.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.130123E+10 | 0.00 | 0.00 | 0.00 | 364169.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.133376E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.158858E+11 | 0.00 | 0.00 | 0.00 | 0.185104E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.121448E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.136990E+10 | 0.00 | 0.00 | 0.00 | 0.763381E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_10:10
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.142673E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.129244E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145733E+10 | 0.00 | 0.00 | 0.00 | 1025.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.138427E+10 | 0.00 | 0.00 | 0.00 | 53397942.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.144194E+10 | 0.00 | 0.00 | 0.00 | 91415611.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.140734E+10 | 0.00 | 0.00 | 0.00 | 0.192447E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.141887E+10 | 0.00 | 0.00 | 0.00 | 0.522774E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.145733E+10 | 0.00 | 0.00 | 0.00 | 0.788103E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.138427E+10 | 0.00 | 0.00 | 0.00 | 0.201414E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.142656E+10 | 0.00 | 0.00 | 0.00 | 5304422.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.138427E+10 | 0.00 | 0.00 | 0.00 | 27332.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.141887E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.169002E+11 | 0.00 | 0.00 | 0.00 | 0.185489E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.129244E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145733E+10 | 0.00 | 0.00 | 0.00 | 0.788103E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.632856E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.795993E+10 | 0.00 | 0.00 | 0.53 |
February | 0.699665E+10 | 0.00 | 0.00 | 15542.89 | 0.00 | 0.473115E+10 | 26468313.42 | 0.00 | 0.53 |
March | 0.870020E+10 | 0.00 | 0.00 | 61062.17 | 0.00 | 0.190291E+10 | 86350421.82 | 0.00 | 0.53 |
April | 0.751059E+10 | 26375575.02 | 0.00 | 1660583.65 | 0.00 | 0.351455E+09 | 0.941603E+09 | 0.00 | 0.57 |
May | 0.572885E+10 | 14130494.37 | 0.00 | 5433860.44 | 0.00 | 11800779.72 | 0.269906E+10 | 0.00 | 0.66 |
June | 0.234601E+10 | 22608208.39 | 0.00 | 12204773.17 | 0.00 | 0.00 | 0.551910E+10 | 0.00 | 0.81 |
July | 0.638732E+09 | 0.342758E+09 | 0.00 | 16572738.29 | 0.00 | 0.00 | 0.611766E+10 | 0.00 | 0.93 |
August | 0.519205E+09 | 0.772314E+09 | 0.00 | 16176141.91 | 0.00 | 0.00 | 0.499444E+10 | 0.00 | 0.90 |
September | 0.290759E+10 | 33895704.35 | 0.00 | 10693147.87 | 0.00 | 0.00 | 0.521359E+10 | 0.00 | 0.79 |
October | 0.730769E+10 | 0.00 | 0.00 | 2323267.37 | 0.00 | 0.125492E+09 | 0.200043E+10 | 0.00 | 0.57 |
November | 0.756054E+10 | 0.00 | 0.00 | 158920.77 | 0.00 | 0.353181E+10 | 0.170845E+09 | 0.00 | 0.53 |
December | 0.717747E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.637812E+10 | 0.00 | 0.00 | 0.53 |
Annual Sum or Average | 0.637221E+11 | 0.121208E+10 | 0.00 | 65300038.55 | 0.00 | 0.249927E+11 | 0.277696E+11 | 0.00 | 0.66 |
Minimum of Months | 0.519205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.53 |
Maximum of Months | 0.870020E+10 | 0.772314E+09 | 0.00 | 16572738.29 | 0.00 | 0.795993E+10 | 0.611766E+10 | 0.00 | 0.93 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.246362E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.276701E+10 | 0.00 | 0.00 | 0.39 |
February | 0.298942E+10 | 0.00 | 0.00 | 119088.46 | 0.00 | 0.124776E+10 | 0.122833E+09 | 0.00 | 0.40 |
March | 0.384928E+10 | 0.00 | 0.00 | 254630.79 | 0.00 | 0.146589E+09 | 0.269946E+09 | 0.00 | 0.42 |
April | 0.265182E+10 | 12565776.26 | 0.00 | 1841093.50 | 0.00 | 13234683.25 | 0.152278E+10 | 0.00 | 0.56 |
May | 0.127774E+10 | 6779645.52 | 0.00 | 5120697.41 | 0.00 | 0.00 | 0.384631E+10 | 0.00 | 0.84 |
June | 0.322116E+09 | 11012239.20 | 0.00 | 8075365.08 | 0.00 | 0.00 | 0.523420E+10 | 0.00 | 1.19 |
July | 40197048.56 | 0.151333E+09 | 0.00 | 9032349.38 | 0.00 | 0.00 | 0.487700E+10 | 0.00 | 1.33 |
August | 55293353.27 | 0.357583E+09 | 0.00 | 8055417.46 | 0.00 | 0.00 | 0.389760E+10 | 0.00 | 1.21 |
September | 0.566720E+09 | 12228228.56 | 0.00 | 7436921.17 | 0.00 | 0.00 | 0.506097E+10 | 0.00 | 1.12 |
October | 0.243992E+10 | 0.00 | 0.00 | 2791187.39 | 0.00 | 0.00 | 0.254703E+10 | 0.00 | 0.61 |
November | 0.335508E+10 | 0.00 | 0.00 | 347885.28 | 0.00 | 0.770924E+09 | 0.346169E+09 | 0.00 | 0.43 |
December | 0.280370E+10 | 0.00 | 0.00 | 43.99 | 0.00 | 0.212148E+10 | 13171.82 | 0.00 | 0.38 |
Annual Sum or Average | 0.228149E+11 | 0.551503E+09 | 0.00 | 43074679.90 | 0.00 | 0.706700E+10 | 0.277248E+11 | 0.00 | 0.74 |
Minimum of Months | 40197048.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.384928E+10 | 0.357583E+09 | 0.00 | 9032349.38 | 0.00 | 0.276701E+10 | 0.523420E+10 | 0.00 | 1.33 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.197635E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.344524E+10 | 0.00 | 0.00 | 0.41 |
February | 0.260230E+10 | 0.00 | 0.00 | 38466.70 | 0.00 | 0.178611E+10 | 55208104.21 | 0.00 | 0.42 |
March | 0.382263E+10 | 0.00 | 0.00 | 52918.67 | 0.00 | 0.335043E+09 | 83490867.95 | 0.00 | 0.43 |
April | 0.292159E+10 | 13108335.82 | 0.00 | 714187.09 | 0.00 | 53549922.53 | 0.598879E+09 | 0.00 | 0.49 |
May | 0.178085E+10 | 6851892.65 | 0.00 | 2665923.32 | 0.00 | 0.00 | 0.209977E+10 | 0.00 | 0.68 |
June | 0.655202E+09 | 12135962.16 | 0.00 | 4734139.53 | 13493.79 | 0.00 | 0.335869E+10 | 0.00 | 0.93 |
July | 0.232160E+09 | 0.145443E+09 | 0.00 | 5280623.92 | 2730336.06 | 0.00 | 0.314919E+10 | 0.00 | 1.03 |
August | 0.230179E+09 | 0.342950E+09 | 0.00 | 4473868.19 | 5272889.97 | 0.00 | 0.271548E+10 | 0.00 | 0.97 |
September | 0.929419E+09 | 12972666.95 | 0.00 | 4213176.21 | 0.00 | 0.00 | 0.299118E+10 | 0.00 | 0.86 |
October | 0.276648E+10 | 0.00 | 0.00 | 1364820.36 | 0.00 | 1840196.59 | 0.131741E+10 | 0.00 | 0.52 |
November | 0.297367E+10 | 0.00 | 0.00 | 96252.87 | 0.00 | 0.129103E+10 | 94940067.73 | 0.00 | 0.43 |
December | 0.241173E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.266984E+10 | 0.00 | 0.00 | 0.41 |
Annual Sum or Average | 0.233026E+11 | 0.533461E+09 | 0.00 | 23634376.85 | 8016719.83 | 0.958266E+10 | 0.164642E+11 | 0.00 | 0.63 |
Minimum of Months | 0.230179E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.382263E+10 | 0.342950E+09 | 0.00 | 5280623.92 | 5272889.97 | 0.344524E+10 | 0.335869E+10 | 0.00 | 1.03 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.179563E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.362533E+10 | 0.00 | 0.00 | 0.41 |
February | 0.240636E+10 | 0.00 | 0.00 | 26072.06 | 0.00 | 0.197863E+10 | 44406402.48 | 0.00 | 0.42 |
March | 0.363797E+10 | 0.00 | 0.00 | 41970.13 | 0.00 | 0.499488E+09 | 75776724.77 | 0.00 | 0.43 |
April | 0.291142E+10 | 13103719.22 | 0.00 | 637845.20 | 0.00 | 80126717.17 | 0.526270E+09 | 0.00 | 0.48 |
May | 0.186099E+10 | 6783049.39 | 0.00 | 2452940.03 | 0.00 | 0.00 | 0.193920E+10 | 0.00 | 0.67 |
June | 0.691549E+09 | 12149013.23 | 0.00 | 4595241.08 | 13398.73 | 0.00 | 0.327829E+10 | 0.00 | 0.92 |
July | 0.243155E+09 | 0.145497E+09 | 0.00 | 5223246.64 | 2731447.35 | 0.00 | 0.312697E+10 | 0.00 | 1.03 |
August | 0.234918E+09 | 0.342984E+09 | 0.00 | 4458275.73 | 5271431.74 | 0.00 | 0.271026E+10 | 0.00 | 0.97 |
September | 0.986810E+09 | 12791064.96 | 0.00 | 4078138.05 | 0.00 | 0.00 | 0.288419E+10 | 0.00 | 0.85 |
October | 0.276151E+10 | 0.00 | 0.00 | 1261736.29 | 0.00 | 9149037.83 | 0.123664E+10 | 0.00 | 0.52 |
November | 0.273436E+10 | 0.00 | 0.00 | 81130.20 | 0.00 | 0.152072E+10 | 84288997.74 | 0.00 | 0.43 |
December | 0.224243E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.283760E+10 | 0.00 | 0.00 | 0.41 |
Annual Sum or Average | 0.225071E+11 | 0.533308E+09 | 0.00 | 22856595.42 | 8016277.81 | 0.105511E+11 | 0.159063E+11 | 0.00 | 0.63 |
Minimum of Months | 0.234918E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.363797E+10 | 0.342984E+09 | 0.00 | 5223246.64 | 5271431.74 | 0.362533E+10 | 0.327829E+10 | 0.00 | 1.03 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.147177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.394824E+10 | 0.00 | 0.00 | 0.41 |
February | 0.202584E+10 | 0.00 | 0.00 | 13078.45 | 0.00 | 0.235631E+10 | 29553319.28 | 0.00 | 0.42 |
March | 0.331861E+10 | 0.00 | 0.00 | 27006.36 | 0.00 | 0.800335E+09 | 52900651.29 | 0.00 | 0.43 |
April | 0.289391E+10 | 13061246.01 | 0.00 | 495163.24 | 0.00 | 0.136634E+09 | 0.386211E+09 | 0.00 | 0.47 |
May | 0.211268E+10 | 6451480.15 | 0.00 | 1928194.70 | 0.00 | 0.00 | 0.148048E+10 | 0.00 | 0.64 |
June | 0.830781E+09 | 12082108.31 | 0.00 | 4062184.91 | 14665.82 | 0.00 | 0.292244E+10 | 0.00 | 0.88 |
July | 0.303359E+09 | 0.143972E+09 | 0.00 | 4827449.20 | 2755249.37 | 0.00 | 0.293807E+10 | 0.00 | 1.00 |
August | 0.266262E+09 | 0.339798E+09 | 0.00 | 4131227.57 | 5299753.73 | 0.00 | 0.257722E+10 | 0.00 | 0.95 |
September | 0.115261E+10 | 12092388.53 | 0.00 | 3600248.85 | 0.00 | 0.00 | 0.252175E+10 | 0.00 | 0.82 |
October | 0.277411E+10 | 0.00 | 0.00 | 1005313.28 | 0.00 | 37655717.86 | 0.103274E+10 | 0.00 | 0.50 |
November | 0.247534E+10 | 0.00 | 0.00 | 59044.85 | 0.00 | 0.176880E+10 | 65895837.32 | 0.00 | 0.43 |
December | 0.191480E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.316331E+10 | 0.00 | 0.00 | 0.41 |
Annual Sum or Average | 0.215401E+11 | 0.527457E+09 | 0.00 | 20148911.41 | 8069668.93 | 0.122113E+11 | 0.140073E+11 | 0.00 | 0.61 |
Minimum of Months | 0.266262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.331861E+10 | 0.339798E+09 | 0.00 | 4827449.20 | 5299753.73 | 0.394824E+10 | 0.293807E+10 | 0.00 | 1.00 |
Report: MechanicalVentilationLoadsMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.134132E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.881816E+10 | 0.00 | 0.00 | 0.38 |
February | 0.286746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.535829E+10 | 0.00 | 0.00 | 0.38 |
March | 0.556875E+10 | 0.00 | 0.00 | 28926.63 | 0.00 | 0.204137E+10 | 51913414.54 | 0.00 | 0.39 |
April | 0.513081E+10 | 15591602.63 | 0.00 | 672938.18 | 0.00 | 0.415029E+09 | 0.378024E+09 | 0.00 | 0.40 |
May | 0.435959E+10 | 4487660.69 | 0.00 | 2200767.63 | 0.00 | 23811634.15 | 0.121822E+10 | 0.00 | 0.46 |
June | 0.202170E+10 | 12145215.19 | 0.00 | 5623303.97 | 11793.40 | 0.00 | 0.313006E+10 | 0.00 | 0.56 |
July | 0.687401E+09 | 0.252715E+09 | 0.00 | 7448518.75 | 3691651.37 | 0.00 | 0.337801E+10 | 0.00 | 0.63 |
August | 0.459989E+09 | 0.616863E+09 | 0.00 | 6305442.09 | 3814445.08 | 0.00 | 0.297289E+10 | 0.00 | 0.61 |
September | 0.254688E+10 | 9453423.73 | 0.00 | 5061675.59 | 0.00 | 0.00 | 0.257555E+10 | 0.00 | 0.53 |
October | 0.522426E+10 | 0.00 | 0.00 | 960667.54 | 0.00 | 0.250835E+09 | 0.923138E+09 | 0.00 | 0.40 |
November | 0.377926E+10 | 0.00 | 0.00 | 76057.05 | 0.00 | 0.417550E+10 | 77072626.08 | 0.00 | 0.38 |
December | 0.224908E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.730116E+10 | 0.00 | 0.00 | 0.38 |
Annual Sum or Average | 0.362365E+11 | 0.911256E+09 | 0.00 | 28378297.43 | 7517889.86 | 0.283841E+11 | 0.147049E+11 | 0.00 | 0.46 |
Minimum of Months | 0.459989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.556875E+10 | 0.616863E+09 | 0.00 | 7448518.75 | 3814445.08 | 0.881816E+10 | 0.337801E+10 | 0.00 | 0.63 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.570989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.449490E+10 | 0.00 | 0.00 | 0.38 |
February | 0.124295E+10 | 0.00 | 0.00 | 1740.99 | 0.00 | 0.286017E+10 | 6914714.54 | 0.00 | 0.38 |
March | 0.258266E+10 | 0.00 | 0.00 | 14016.63 | 0.00 | 0.123143E+10 | 35953764.48 | 0.00 | 0.39 |
April | 0.255303E+10 | 7505754.61 | 0.00 | 359714.33 | 0.00 | 0.238284E+09 | 0.276647E+09 | 0.00 | 0.42 |
May | 0.213284E+10 | 1871658.93 | 0.00 | 1258356.04 | 0.00 | 10020731.41 | 0.968311E+09 | 0.00 | 0.55 |
June | 0.888142E+09 | 5573704.73 | 0.00 | 3066618.80 | 0.00 | 0.00 | 0.229217E+10 | 0.00 | 0.75 |
July | 0.274153E+09 | 0.111358E+09 | 0.00 | 4019641.37 | 1418611.21 | 0.00 | 0.248819E+10 | 0.00 | 0.87 |
August | 0.190365E+09 | 0.281825E+09 | 0.00 | 3447825.66 | 1512208.38 | 0.00 | 0.216249E+10 | 0.00 | 0.82 |
September | 0.116969E+10 | 2786938.54 | 0.00 | 2868171.82 | 0.00 | 0.00 | 0.197131E+10 | 0.00 | 0.69 |
October | 0.247278E+10 | 0.00 | 0.00 | 629257.15 | 0.00 | 0.193459E+09 | 0.720057E+09 | 0.00 | 0.43 |
November | 0.178703E+10 | 0.00 | 0.00 | 39788.72 | 0.00 | 0.218727E+10 | 55304816.47 | 0.00 | 0.39 |
December | 0.104430E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.371686E+10 | 0.00 | 0.00 | 0.38 |
Annual Sum or Average | 0.169089E+11 | 0.410920E+09 | 0.00 | 15705131.51 | 2930819.58 | 0.149324E+11 | 0.109774E+11 | 0.00 | 0.54 |
Minimum of Months | 0.190365E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.258266E+10 | 0.281825E+09 | 0.00 | 4019641.37 | 1512208.38 | 0.449490E+10 | 0.248819E+10 | 0.00 | 0.87 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.518043E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.454779E+10 | 0.00 | 0.00 | 0.38 |
February | 0.118242E+10 | 0.00 | 0.00 | 1267.01 | 0.00 | 0.292126E+10 | 4839247.87 | 0.00 | 0.38 |
March | 0.251598E+10 | 0.00 | 0.00 | 12587.24 | 0.00 | 0.129429E+10 | 34699712.82 | 0.00 | 0.39 |
April | 0.251047E+10 | 7441921.49 | 0.00 | 343465.80 | 0.00 | 0.277173E+09 | 0.266898E+09 | 0.00 | 0.42 |
May | 0.213893E+10 | 1765648.75 | 0.00 | 1198929.69 | 0.00 | 13033859.12 | 0.927308E+09 | 0.00 | 0.54 |
June | 0.912364E+09 | 5511013.01 | 0.00 | 2962674.21 | 0.00 | 0.00 | 0.222092E+10 | 0.00 | 0.74 |
July | 0.296461E+09 | 0.110056E+09 | 0.00 | 3909780.39 | 1413165.51 | 0.00 | 0.242629E+10 | 0.00 | 0.86 |
August | 0.199738E+09 | 0.279172E+09 | 0.00 | 3372246.15 | 1504772.26 | 0.00 | 0.212235E+10 | 0.00 | 0.81 |
September | 0.118168E+10 | 2621664.72 | 0.00 | 2788002.50 | 0.00 | 0.00 | 0.192310E+10 | 0.00 | 0.68 |
October | 0.243118E+10 | 0.00 | 0.00 | 595369.19 | 0.00 | 0.234840E+09 | 0.697199E+09 | 0.00 | 0.43 |
November | 0.171475E+10 | 0.00 | 0.00 | 37769.82 | 0.00 | 0.225864E+10 | 53300626.74 | 0.00 | 0.39 |
December | 0.937022E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.382411E+10 | 0.00 | 0.00 | 0.38 |
Annual Sum or Average | 0.165390E+11 | 0.406569E+09 | 0.00 | 15222091.99 | 2917937.77 | 0.153711E+11 | 0.106769E+11 | 0.00 | 0.53 |
Minimum of Months | 0.199738E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.251598E+10 | 0.279172E+09 | 0.00 | 3909780.39 | 1504772.26 | 0.454779E+10 | 0.242629E+10 | 0.00 | 0.86 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.262671E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.480337E+10 | 0.00 | 0.00 | 0.38 |
February | 0.919488E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.318419E+10 | 0.00 | 0.00 | 0.38 |
March | 0.223235E+10 | 0.00 | 0.00 | 7557.65 | 0.00 | 0.156910E+10 | 27819076.53 | 0.00 | 0.39 |
April | 0.231525E+10 | 7400762.87 | 0.00 | 288877.33 | 0.00 | 0.461611E+09 | 0.232910E+09 | 0.00 | 0.42 |
May | 0.216641E+10 | 1568618.94 | 0.00 | 996639.83 | 0.00 | 21877571.55 | 0.776980E+09 | 0.00 | 0.53 |
June | 0.101423E+10 | 5476920.79 | 0.00 | 2604903.30 | 0.00 | 0.00 | 0.196238E+10 | 0.00 | 0.71 |
July | 0.367297E+09 | 0.108661E+09 | 0.00 | 3567417.53 | 1435226.59 | 0.00 | 0.222861E+10 | 0.00 | 0.83 |
August | 0.236038E+09 | 0.276921E+09 | 0.00 | 3095577.54 | 1515767.36 | 0.00 | 0.198739E+10 | 0.00 | 0.79 |
September | 0.125077E+10 | 2358756.20 | 0.00 | 2491607.17 | 0.00 | 817038.17 | 0.171429E+10 | 0.00 | 0.66 |
October | 0.236601E+10 | 0.00 | 0.00 | 449695.59 | 0.00 | 0.359596E+09 | 0.553316E+09 | 0.00 | 0.42 |
November | 0.144391E+10 | 0.00 | 0.00 | 31916.30 | 0.00 | 0.252485E+10 | 49626233.89 | 0.00 | 0.39 |
December | 0.592314E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.416875E+10 | 0.00 | 0.00 | 0.38 |
Annual Sum or Average | 0.151667E+11 | 0.402387E+09 | 0.00 | 13534192.23 | 2950993.95 | 0.170942E+11 | 0.953333E+10 | 0.00 | 0.52 |
Minimum of Months | 0.236038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.236601E+10 | 0.276921E+09 | 0.00 | 3567417.53 | 1515767.36 | 0.480337E+10 | 0.222861E+10 | 0.00 | 0.83 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 6105737.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.503892E+10 | 0.00 | 0.00 | 0.38 |
February | 0.278502E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.379899E+10 | 0.00 | 0.00 | 0.38 |
March | 0.115816E+10 | 0.00 | 0.00 | 52.72 | 0.00 | 0.263053E+10 | 2589283.45 | 0.00 | 0.39 |
April | 0.171707E+10 | 7648792.80 | 0.00 | 221621.97 | 0.00 | 0.102659E+10 | 0.197913E+09 | 0.00 | 0.42 |
May | 0.200327E+10 | 1586701.66 | 0.00 | 826065.83 | 0.00 | 0.210809E+09 | 0.615134E+09 | 0.00 | 0.53 |
June | 0.104665E+10 | 5816101.71 | 0.00 | 2317579.52 | 0.00 | 1447675.07 | 0.179075E+10 | 0.00 | 0.70 |
July | 0.417617E+09 | 0.112496E+09 | 0.00 | 3207063.16 | 1447599.07 | 0.00 | 0.205021E+10 | 0.00 | 0.83 |
August | 0.303479E+09 | 0.288632E+09 | 0.00 | 2692321.19 | 1517476.58 | 0.00 | 0.178797E+10 | 0.00 | 0.78 |
September | 0.131124E+10 | 2459675.18 | 0.00 | 2238874.03 | 0.00 | 17655792.91 | 0.148196E+10 | 0.00 | 0.66 |
October | 0.184922E+10 | 0.00 | 0.00 | 291845.62 | 0.00 | 0.915818E+09 | 0.396317E+09 | 0.00 | 0.41 |
November | 0.480433E+09 | 0.00 | 0.00 | 25810.18 | 0.00 | 0.345745E+10 | 47173892.13 | 0.00 | 0.39 |
December | 76871189.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.466357E+10 | 0.00 | 0.00 | 0.38 |
Annual Sum or Average | 0.106486E+11 | 0.418639E+09 | 0.00 | 11821234.21 | 2965075.65 | 0.217618E+11 | 0.837001E+10 | 0.00 | 0.52 |
Minimum of Months | 6105737.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.200327E+10 | 0.288632E+09 | 0.00 | 3207063.16 | 1517476.58 | 0.503892E+10 | 0.205021E+10 | 0.00 | 0.83 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:37:31
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.431967E+11 | 0.294334E+11 | 0.00 | 0.687282E+11 | 0.167944E+11 |
February | 0.118890E+12 | 0.236816E+11 | 0.00 | 0.560058E+11 | 0.111270E+11 |
March | 0.234250E+12 | 0.214624E+11 | 0.00 | 0.519318E+11 | 0.584011E+10 |
April | 0.389248E+12 | 0.170615E+11 | 0.00 | 0.418561E+11 | 0.659382E+10 |
May | 0.527562E+12 | 0.148538E+11 | 0.00 | 0.424350E+11 | 0.914263E+10 |
June | 0.538098E+12 | 0.111542E+11 | 0.00 | 0.424088E+11 | 0.167172E+11 |
July | 0.572953E+12 | 0.672349E+10 | 0.00 | 0.347305E+11 | 0.426186E+11 |
August | 0.442498E+12 | 0.417633E+10 | 0.00 | 0.267826E+11 | 0.596418E+11 |
September | 0.301759E+12 | 0.107775E+11 | 0.00 | 0.423181E+11 | 0.170983E+11 |
October | 0.173225E+12 | 0.176797E+11 | 0.00 | 0.462619E+11 | 0.216655E+10 |
November | 0.585717E+11 | 0.231068E+11 | 0.00 | 0.545837E+11 | 0.869954E+10 |
December | 0.248268E+11 | 0.272257E+11 | 0.00 | 0.648289E+11 | 0.142489E+11 |
Annual Sum or Average | 0.342508E+13 | 0.207337E+12 | 0.00 | 0.572872E+12 | 0.210689E+12 |
Minimum of Months | 0.248268E+11 | 0.417633E+10 | 0.00 | 0.267826E+11 | 0.216655E+10 |
Maximum of Months | 0.572953E+12 | 0.294334E+11 | 0.00 | 0.687282E+11 | 0.596418E+11 |