Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:37
Tabular Output Report in Format: HTML
Building: RetailStripmall
Environment: RUNPERIOD 1 ** Ho Chi Minh City-Tan Son Nhat Intl AP - VNM IWEC2 WMO#=489000
Simulation Timestamp: 2023-10-16 08:37:06
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:06
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1415.97 | 677.39 | 677.39 |
Net Site Energy | 1415.97 | 677.39 | 677.39 |
Total Source Energy | 4484.37 | 2145.30 | 2145.30 |
Net Source Energy | 4484.37 | 2145.30 | 2145.30 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 2090.32 |
Net Conditioned Building Area | 2090.32 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 685.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 366.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 60.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 128.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 117.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 57.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1415.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 685.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 366.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 60.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 128.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 117.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 57.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 685.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 366.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 60.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 128.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 117.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 57.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 204.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 411.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Other | 61.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 677.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 204.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 411.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Other | 61.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 677.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1415.967 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1415.967 | 100.00 |
Total On-Site and Utility Electric Sources | 1415.967 | 100.00 |
Total Electricity End Uses | 1415.967 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 87.30 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 87.30 | 100.00 |
Total Water End Uses | 87.30 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 1.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 3892.00 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTRIPMALL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 0A
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY VNM_HOCHIMINH_TANSONHOA
| Environment |ZoneCoolingSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ZoneHeatingSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ZoneElectricSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |SpaceGainsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |PeakSpaceGainsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |SpaceGainComponentsAtCoolingPeakMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ComfortReportSimple55Monthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |OccupantComfortDataSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |DXReportMonthly
| PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL | PSZ-AC_3:3 COOLING COIL | PSZ-AC_4:4 COOLING COIL | PSZ-AC_5:5 COOLING COIL | PSZ-AC_6:6 COOLING COIL | PSZ-AC_7:7 COOLING COIL | PSZ-AC_8:8 COOLING COIL | PSZ-AC_9:9 COOLING COIL | PSZ-AC_10:10 COOLING COIL |WindowReportMonthly
| LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR |WindowEnergyReportMonthly
| LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR |WindowZoneSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |WindowEnergyZoneSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| GAS TANK1 | GAS TANK2 | GAS TANK3 | GAS TANK4 | GAS TANK5 | GAS TANK6 | GAS TANK7 |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC_1:1 HEATING COIL | PSZ-AC_2:2 HEATING COIL | PSZ-AC_3:3 HEATING COIL | PSZ-AC_4:4 HEATING COIL | PSZ-AC_5:5 HEATING COIL | PSZ-AC_6:6 HEATING COIL | PSZ-AC_7:7 HEATING COIL | PSZ-AC_8:8 HEATING COIL | PSZ-AC_9:9 HEATING COIL | PSZ-AC_10:10 HEATING COIL | PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL | PSZ-AC_3:3 COOLING COIL | PSZ-AC_4:4 COOLING COIL | PSZ-AC_5:5 COOLING COIL | PSZ-AC_6:6 COOLING COIL | PSZ-AC_7:7 COOLING COIL | PSZ-AC_8:8 COOLING COIL | PSZ-AC_9:9 COOLING COIL | PSZ-AC_10:10 COOLING COIL |FanReportMonthly
| PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN |ZoneTemperatureOscillationReportMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |MechanicalVentilationLoadsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:06
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:37 |
RunPeriod | RUNPERIOD 1 |
Weather File | Ho Chi Minh City-Tan Son Nhat Intl AP - VNM IWEC2 WMO#=489000 |
Latitude [deg] | 10.82 |
Longitude [deg] | 106.67 |
Elevation [m] | 5.00 |
Time Zone | 7.00 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Above Ground Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Window Opening Area [m2] | 124.40 | 0.00 | 0.00 | 124.40 | 0.00 |
Gross Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Above Ground Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Above Ground Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Window Opening Area [m2] | 124.40 | 0.00 | 0.00 | 124.40 | 0.00 |
Gross Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Above Ground Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Total | |
Gross Roof Area [m2] | 2090.32 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
LGSTORE1 | 348.39 | Yes | Yes | 1805.20 | 1.00 | 276.30 | 0.00 | 20.77 | 20.77 | 15.3022 | 6.19 | 4.3000 |
SMSTORE1 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.38 | 10.38 | 18.2890 | 6.19 | 4.3000 |
SMSTORE2 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 16.6533 | 6.19 | 4.3000 |
SMSTORE3 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 16.6533 | 6.19 | 4.3000 |
SMSTORE4 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 16.6533 | 6.19 | 4.3000 |
LGSTORE2 | 348.39 | Yes | Yes | 1805.20 | 1.00 | 157.89 | 0.00 | 20.72 | 20.72 | 9.5842 | 6.19 | 4.3000 |
SMSTORE5 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 9.6995 | 6.19 | 4.3000 |
SMSTORE6 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 9.6995 | 6.19 | 4.3000 |
SMSTORE7 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 9.6995 | 6.19 | 4.3000 |
SMSTORE8 | 174.19 | Yes | Yes | 902.60 | 1.00 | 197.36 | 0.00 | 10.36 | 10.36 | 9.6995 | 6.19 | 4.3000 |
Total | 2090.32 | 10831.20 | 1184.15 | 0.00 | 124.40 | 124.40 | 13.0683 | 6.19 | 4.3000 | |||
Conditioned Total | 2090.32 | 10831.20 | 1184.15 | 0.00 | 124.40 | 124.40 | 13.0683 | 6.19 | 4.3000 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
LGSTORE1 | 348.39 | Yes | Yes | 1.00 | LGSTORE1 | GENERAL | LGSTORE1 | 15.3022 | 6.19 | 4.3000 | |
SMSTORE1 | 174.19 | Yes | Yes | 1.00 | SMSTORE1 | GENERAL | SMSTORE1 | 18.2890 | 6.19 | 4.3000 | |
SMSTORE2 | 174.19 | Yes | Yes | 1.00 | SMSTORE2 | GENERAL | SMSTORE2 | 16.6533 | 6.19 | 4.3000 | |
SMSTORE3 | 174.19 | Yes | Yes | 1.00 | SMSTORE3 | GENERAL | SMSTORE3 | 16.6533 | 6.19 | 4.3000 | |
SMSTORE4 | 174.19 | Yes | Yes | 1.00 | SMSTORE4 | GENERAL | SMSTORE4 | 16.6533 | 6.19 | 4.3000 | |
LGSTORE2 | 348.39 | Yes | Yes | 1.00 | LGSTORE2 | GENERAL | LGSTORE2 | 9.5842 | 6.19 | 4.3000 | |
SMSTORE5 | 174.19 | Yes | Yes | 1.00 | SMSTORE5 | GENERAL | SMSTORE5 | 9.6995 | 6.19 | 4.3000 | |
SMSTORE6 | 174.19 | Yes | Yes | 1.00 | SMSTORE6 | GENERAL | SMSTORE6 | 9.6995 | 6.19 | 4.3000 | |
SMSTORE7 | 174.19 | Yes | Yes | 1.00 | SMSTORE7 | GENERAL | SMSTORE7 | 9.6995 | 6.19 | 4.3000 | |
SMSTORE8 | 174.19 | Yes | Yes | 1.00 | SMSTORE8 | GENERAL | SMSTORE8 | 9.6995 | 6.19 | 4.3000 | |
Total | 2090.32 | 13.0683 | 3.10 | 4.3000 | |||||||
Conditioned Total | 2090.32 | 13.0683 | 3.10 | 4.3000 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 2090.32 | 2090.32 | 0.00 | 0.00 | 13.0683 | 6.19 | 4.3000 |
Total | 2090.32 | 2090.32 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:06
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 16-JUN-12:39 | - | - | - | - | - | - | - | - | - | - | - | 06-JAN-13:09 |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 75895.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 23459.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 8059.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 11970.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 7542.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 126926.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 75895.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 23459.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 8059.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 11970.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 7542.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:06
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 2172.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1161.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 190.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 405.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 372.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 182.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 4484.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1039.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 555.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 91.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 194.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 178.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 87.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2145.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1039.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 555.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 91.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 194.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 178.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 87.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2145.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:06
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
LGSTORE1 DIRECT AIR | 2.28 |
SMSTORE1 DIRECT AIR | 1.16 |
SMSTORE2 DIRECT AIR | 1.16 |
SMSTORE3 DIRECT AIR | 1.17 |
SMSTORE4 DIRECT AIR | 1.16 |
LGSTORE2 DIRECT AIR | 2.03 |
SMSTORE5 DIRECT AIR | 1.07 |
SMSTORE6 DIRECT AIR | 1.06 |
SMSTORE7 DIRECT AIR | 1.07 |
SMSTORE8 DIRECT AIR | 1.25 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC_1:1 | 2.28 | 2.28 | 2.28 | 2.28 | 2.28 | 2.28 | 1.00 | 1.00 | 2.28 |
PSZ-AC_2:2 | 1.16 | 1.16 | 1.16 | 1.16 | 1.16 | 1.16 | 1.00 | 1.00 | 1.16 |
PSZ-AC_3:3 | 1.16 | 1.16 | 1.16 | 1.16 | 1.16 | 1.16 | 1.00 | 0.999998 | 1.16 |
PSZ-AC_4:4 | 1.17 | 1.17 | 1.17 | 1.17 | 1.17 | 1.17 | 1.00 | 1.00 | 1.17 |
PSZ-AC_5:5 | 1.16 | 1.16 | 1.16 | 1.16 | 1.16 | 1.16 | 1.00 | 1.00 | 1.16 |
PSZ-AC_6:6 | 2.03 | 2.03 | 2.03 | 2.03 | 2.03 | 2.03 | 1.00 | 1.00 | 2.03 |
PSZ-AC_7:7 | 1.07 | 1.07 | 1.07 | 1.07 | 1.07 | 1.07 | 1.00 | 0.999958 | 1.07 |
PSZ-AC_8:8 | 1.06 | 1.06 | 1.06 | 1.06 | 1.06 | 1.06 | 1.00 | 0.999969 | 1.06 |
PSZ-AC_9:9 | 1.07 | 1.07 | 1.07 | 1.07 | 1.07 | 1.07 | 1.00 | 1.00 | 1.07 |
PSZ-AC_10:10 | 1.25 | 1.25 | 1.25 | 1.25 | 1.25 | 1.25 | 1.00 | 1.00 | 1.25 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC_1:1_OA_CONTROLLER | 2.28 | 0.411479 |
PSZ-AC_2:2_OA_CONTROLLER | 1.16 | 0.205739 |
PSZ-AC_3:3_OA_CONTROLLER | 1.16 | 0.205739 |
PSZ-AC_4:4_OA_CONTROLLER | 1.17 | 0.205739 |
PSZ-AC_5:5_OA_CONTROLLER | 1.16 | 0.205739 |
PSZ-AC_6:6_OA_CONTROLLER | 2.03 | 0.411479 |
PSZ-AC_7:7_OA_CONTROLLER | 1.07 | 0.205739 |
PSZ-AC_8:8_OA_CONTROLLER | 1.06 | 0.205739 |
PSZ-AC_9:9_OA_CONTROLLER | 1.07 | 0.205739 |
PSZ-AC_10:10_OA_CONTROLLER | 1.25 | 0.205739 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | 2.28 | 2444.19 |
PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | 1.16 | 1287.13 |
PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | 1.16 | 1288.73 |
PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | 1.17 | 1292.27 |
PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | 1.16 | 1281.49 |
PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | 2.03 | 2171.67 |
PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | 1.07 | 1181.87 |
PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | 1.06 | 1177.23 |
PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | 1.07 | 1182.62 |
PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | 1.25 | 1385.04 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC_1:1_UNITARY_PACKAGE_DX | 2.28 | 2.28 | 2.28 | 1.51 | 56721.74 | 52685.94 | 40.00 | 1.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_DX | 1.16 | 1.16 | 1.16 | 0.767283 | 28868.90 | 26810.42 | 40.00 | 1.00 |
PSZ-AC_3:3_UNITARY_PACKAGE_DX | 1.16 | 1.16 | 1.16 | 0.768237 | 28904.79 | 26843.18 | 40.00 | 1.00 |
PSZ-AC_4:4_UNITARY_PACKAGE_DX | 1.17 | 1.17 | 1.17 | 0.770351 | 28984.33 | 26916.39 | 40.00 | 1.00 |
PSZ-AC_5:5_UNITARY_PACKAGE_DX | 1.16 | 1.16 | 1.16 | 0.763923 | 28742.45 | 26693.75 | 40.00 | 1.00 |
PSZ-AC_6:6_UNITARY_PACKAGE_DX | 2.03 | 2.03 | 2.03 | 1.34 | 50397.45 | 46867.29 | 40.00 | 1.00 |
PSZ-AC_7:7_UNITARY_PACKAGE_DX | 1.07 | 1.07 | 1.07 | 0.704535 | 26507.99 | 24637.14 | 40.00 | 1.00 |
PSZ-AC_8:8_UNITARY_PACKAGE_DX | 1.06 | 1.06 | 1.06 | 0.701773 | 26404.07 | 24541.47 | 40.00 | 1.00 |
PSZ-AC_9:9_UNITARY_PACKAGE_DX | 1.07 | 1.07 | 1.07 | 0.704985 | 26524.94 | 24653.67 | 40.00 | 1.00 |
PSZ-AC_10:10_UNITARY_PACKAGE_DX | 1.25 | 1.25 | 1.25 | 0.825648 | 31064.88 | 29331.79 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-AC_1:1 COOLING COIL | 2.28 | 1.14 | 1.52 | 56721.74 | 28360.87 | 0.701080 | 0.701080 |
PSZ-AC_2:2 COOLING COIL | 1.16 | 0.581275 | 0.775033 | 28868.90 | 14434.45 | 0.701080 | 0.701080 |
PSZ-AC_3:3 COOLING COIL | 1.16 | 0.581998 | 0.776000 | 28904.79 | 14452.40 | 0.701080 | 0.701080 |
PSZ-AC_4:4 COOLING COIL | 1.17 | 0.583600 | 0.778133 | 28984.33 | 14492.17 | 0.701080 | 0.701080 |
PSZ-AC_5:5 COOLING COIL | 1.16 | 0.578729 | 0.771640 | 28742.45 | 14371.23 | 0.701080 | 0.701080 |
PSZ-AC_6:6 COOLING COIL | 2.03 | 1.01 | 1.35 | 50397.45 | 25198.72 | 0.701080 | 0.701080 |
PSZ-AC_7:7 COOLING COIL | 1.07 | 0.533738 | 0.711653 | 26507.99 | 13254.00 | 0.701080 | 0.701080 |
PSZ-AC_8:8 COOLING COIL | 1.06 | 0.531646 | 0.708860 | 26404.07 | 13202.03 | 0.701080 | 0.701080 |
PSZ-AC_9:9 COOLING COIL | 1.07 | 0.534080 | 0.712107 | 26524.94 | 13262.47 | 0.701080 | 0.701080 |
PSZ-AC_10:10 COOLING COIL | 1.25 | 0.625491 | 0.833987 | 31064.88 | 15532.44 | 0.701080 | 0.701080 |
Design Size Nominal Capacity [W] | |
PSZ-AC_1:1 HEATING COIL | 52685.94 |
PSZ-AC_2:2 HEATING COIL | 26810.42 |
PSZ-AC_3:3 HEATING COIL | 26843.18 |
PSZ-AC_4:4 HEATING COIL | 26916.39 |
PSZ-AC_5:5 HEATING COIL | 26693.75 |
PSZ-AC_6:6 HEATING COIL | 46867.29 |
PSZ-AC_7:7 HEATING COIL | 24637.14 |
PSZ-AC_8:8 HEATING COIL | 24541.47 |
PSZ-AC_9:9 HEATING COIL | 24653.67 |
PSZ-AC_10:10 HEATING COIL | 29331.79 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:06
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
LGSTORE1_WALL_3 | LGSTORE1_WALL_3_DOOR_1 | LGSTORE1_WALL_3_DOOR_2 | |
LGSTORE1_WALL_1 | LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | |
SMSTORE1_WALL_1 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | |
SMSTORE1_WALL_3 | SMSTORE1_WALL_3_DOOR | |
SMSTORE2_WALL_1 | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | |
SMSTORE2_WALL_3 | SMSTORE2_WALL_3_DOOR | |
SMSTORE3_WALL_1 | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | |
SMSTORE3_WALL_3 | SMSTORE3_WALL_3_DOOR | |
SMSTORE4_WALL_1 | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | |
SMSTORE4_WALL_3 | SMSTORE4_WALL_3_DOOR | |
LGSTORE2_WALL_3 | LGSTORE2_WALL_3_DOOR_1 | LGSTORE2_WALL_3_DOOR_2 | |
LGSTORE2_WALL_1 | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | |
SMSTORE5_WALL_1 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | |
SMSTORE5_WALL_3 | SMSTORE5_WALL_3_DOOR | |
SMSTORE6_WALL_1 | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | |
SMSTORE6_WALL_3 | SMSTORE6_WALL_3_DOOR | |
SMSTORE7_WALL_1 | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | |
SMSTORE7_WALL_3 | SMSTORE7_WALL_3_DOOR | |
SMSTORE8_WALL_1 | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR | |
SMSTORE8_WALL_3 | SMSTORE8_WALL_3_DOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:06
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:06
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 26.90 | 26.70 | 26.00 | 26.40 | 27.50 | 28.30 | 29.20 | 29.00 | 28.90 | 27.20 | 27.50 | 27.60 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Ho Chi Minh City-Tan Son Nhat Intl AP - VNM IWEC2 WMO#=489000 | 10.82 | 106.67 | 7.00 | 5.00 | 101265 | 1.2036 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 27.60 | 3.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RetailStripmall | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 10 | 118 | 48 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | LGSTORE1 | 0.0 | 0.00 | 0.00 | 0.00 | 7.62 | 11.43 | 2.59 | 1 | 1 | 1 | 0.00 | 15.24 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 1805.20 | TARP | TARP | 348.39 | 276.30 | 247.74 | 20.77 | 6 | 8 | 0 | Yes |
2 | SMSTORE1 | 0.0 | 0.00 | 0.00 | 0.00 | 19.05 | 11.43 | 2.59 | 1 | 1 | 1 | 15.24 | 22.86 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.66 | 10.38 | 6 | 4 | 0 | Yes |
3 | SMSTORE2 | 0.0 | 0.00 | 0.00 | 0.00 | 26.67 | 11.43 | 2.59 | 1 | 1 | 1 | 22.86 | 30.48 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
4 | SMSTORE3 | 0.0 | 0.00 | 0.00 | 0.00 | 34.29 | 11.43 | 2.59 | 1 | 1 | 1 | 30.48 | 38.10 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
5 | SMSTORE4 | 0.0 | 0.00 | 0.00 | 0.00 | 41.91 | 11.43 | 2.59 | 1 | 1 | 1 | 38.10 | 45.72 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
6 | LGSTORE2 | 0.0 | 0.00 | 0.00 | 0.00 | 53.34 | 11.43 | 2.59 | 1 | 1 | 1 | 45.72 | 60.96 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 1805.20 | TARP | TARP | 348.39 | 157.89 | 129.41 | 20.72 | 6 | 8 | 0 | Yes |
7 | SMSTORE5 | 0.0 | 0.00 | 0.00 | 0.00 | 64.77 | 11.43 | 2.59 | 1 | 1 | 1 | 60.96 | 68.58 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
8 | SMSTORE6 | 0.0 | 0.00 | 0.00 | 0.00 | 72.39 | 11.43 | 2.59 | 1 | 1 | 1 | 68.58 | 76.20 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
9 | SMSTORE7 | 0.0 | 0.00 | 0.00 | 0.00 | 80.01 | 11.43 | 2.59 | 1 | 1 | 1 | 76.20 | 83.82 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
10 | SMSTORE8 | 0.0 | 0.00 | 0.00 | 0.00 | 87.63 | 11.43 | 2.59 | 1 | 1 | 1 | 83.82 | 91.44 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 197.36 | 183.12 | 10.36 | 6 | 4 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | LGSTORE1 | 348.39 | 56.3 | 6.193 | 0.161 | 15.302 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 19.602 | No |
2 | SMSTORE1 | 174.19 | 28.1 | 6.194 | 0.161 | 18.289 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 22.589 | No |
3 | SMSTORE2 | 174.19 | 28.1 | 6.194 | 0.161 | 16.653 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 20.953 | No |
4 | SMSTORE3 | 174.19 | 28.1 | 6.194 | 0.161 | 16.653 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 20.953 | No |
5 | SMSTORE4 | 174.19 | 28.1 | 6.194 | 0.161 | 16.653 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 20.953 | No |
6 | LGSTORE2 | 348.39 | 56.3 | 6.193 | 0.161 | 9.584 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 13.884 | No |
7 | SMSTORE5 | 174.19 | 28.1 | 6.194 | 0.161 | 9.699 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 13.999 | No |
8 | SMSTORE6 | 174.19 | 28.1 | 6.194 | 0.161 | 9.699 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 13.999 | No |
9 | SMSTORE7 | 174.19 | 28.1 | 6.194 | 0.161 | 9.699 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 13.999 | No |
10 | SMSTORE8 | 174.19 | 28.1 | 6.194 | 0.161 | 9.699 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 13.999 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | LGSTORE1 | TYPE1_OCC_SCH | LGSTORE1 | 348.39 | 56.3 | 56.3 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 56 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | SMSTORE1 | TYPE1_OCC_SCH | SMSTORE1 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | SMSTORE2 | TYPE2_OCC_SCH | SMSTORE2 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | SMSTORE3 | TYPE2_OCC_SCH | SMSTORE3 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | SMSTORE4 | TYPE2_OCC_SCH | SMSTORE4 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | LGSTORE2 | TYPE3_OCC_SCH | LGSTORE2 | 348.39 | 56.3 | 56.3 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 56 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | SMSTORE5 | TYPE3_OCC_SCH | SMSTORE5 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | SMSTORE6 | TYPE3_OCC_SCH | SMSTORE6 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | SMSTORE7 | TYPE3_OCC_SCH | SMSTORE7 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | SMSTORE8 | TYPE3_OCC_SCH | SMSTORE8 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | LGSTORE1_LIGHTS | LTG_SCH_BASE_LPD1 | LGSTORE1 | 348.39 | 56.3 | 3346.345 | 9.605 | 59.490 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3346.345 |
2 | LGSTORE1_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | LGSTORE1 | 348.39 | 56.3 | 1984.726 | 5.697 | 35.284 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1984.726 |
3 | SMSTORE1_LIGHTS | LTG_SCH_BASE_SMALL_LPD1 | SMSTORE1 | 174.19 | 28.1 | 1693.257 | 9.721 | 60.206 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1693.257 |
4 | SMSTORE1_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | SMSTORE1 | 174.19 | 28.1 | 1492.567 | 8.568 | 53.070 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1492.567 |
5 | SMSTORE2_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE2 | 174.19 | 28.1 | 1689.582 | 9.699 | 60.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1689.582 |
6 | SMSTORE2_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE2 | 174.19 | 28.1 | 1211.319 | 6.954 | 43.070 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1211.319 |
7 | SMSTORE3_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE3 | 174.19 | 28.1 | 1689.582 | 9.699 | 60.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1689.582 |
8 | SMSTORE3_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE3 | 174.19 | 28.1 | 1211.319 | 6.954 | 43.070 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1211.319 |
9 | SMSTORE4_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE4 | 174.19 | 28.1 | 1689.582 | 9.699 | 60.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1689.582 |
10 | SMSTORE4_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE4 | 174.19 | 28.1 | 1211.319 | 6.954 | 43.070 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1211.319 |
11 | LGSTORE2_LIGHTS | LTG_SCH_BASE_LPD2 | LGSTORE2 | 348.39 | 56.3 | 3338.998 | 9.584 | 59.359 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3338.998 |
12 | LGSTORE2_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | LGSTORE2 | 348.39 | 56.3 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
13 | SMSTORE5_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE5 | 174.19 | 28.1 | 1689.582 | 9.699 | 60.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1689.582 |
14 | SMSTORE5_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE5 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
15 | SMSTORE6_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE6 | 174.19 | 28.1 | 1689.582 | 9.699 | 60.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1689.582 |
16 | SMSTORE6_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE6 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
17 | SMSTORE7_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE7 | 174.19 | 28.1 | 1689.582 | 9.699 | 60.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1689.582 |
18 | SMSTORE7_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE7 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
19 | SMSTORE8_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE8 | 174.19 | 28.1 | 1689.582 | 9.699 | 60.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1689.582 |
20 | SMSTORE8_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE8 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LGSTORE1_MISCPLUG_EQUIP | TYPE1_EQUIP_SCH | LGSTORE1 | 348.39 | 56.3 | 1498.062 | 4.300 | 26.632 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1498.062 |
2 | SMSTORE1_MISCPLUG_EQUIP | TYPE1_EQUIP_SCH | SMSTORE1 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
3 | SMSTORE2_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE2 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
4 | SMSTORE3_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE3 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
5 | SMSTORE4_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE4 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
6 | LGSTORE2_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | LGSTORE2 | 348.39 | 56.3 | 1498.062 | 4.300 | 26.632 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1498.062 |
7 | SMSTORE5_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE5 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
8 | SMSTORE6_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE6 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
9 | SMSTORE7_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE7 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
10 | SMSTORE8_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE8 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.2284 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
5 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 1.028 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
6 | LGSTORE1_FLOOR_FFACTOR | 36 | 2 | 7 | 0.167 | 0.1995 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
7 | SMSTORE1_FLOOR_FFACTOR | 37 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
8 | SMSTORE2_FLOOR_FFACTOR | 38 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | SMSTORE3_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
10 | SMSTORE4_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
11 | LGSTORE2_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | SMSTORE5_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | SMSTORE6_FLOOR_FFACTOR | 43 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | SMSTORE7_FLOOR_FFACTOR | 44 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | SMSTORE8_FLOOR_FFACTOR | 45 | 2 | 7 | 0.167 | 0.2888 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
6 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
7 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
8 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
10 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7383 |
11 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
12 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.937 |
13 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
14 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
15 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
16 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
17 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
18 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
19 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
20 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
21 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
22 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
23 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
24 | ~FC_Insulation_7 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_8 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_9 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_10 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.386 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
14 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
15 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
16 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
17 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
18 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
19 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
20 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
21 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
22 | 7 | -0.27626373E-12 | 0.13670118E-14 | -0.80430638E-13 | 0.78416590E-16 |
23 | 6 | 0.25658824E-07 | 0.27941242E-09 | 0.59030768E-08 | -0.11909973E-12 |
24 | 5 | -0.17468948E-03 | 0.24402707E-05 | -0.90039107E-04 | 0.58437388E-08 |
25 | 4 | 0.27392503 | 0.12091412E-02 | 0.93138911E-01 | -0.31018751E-04 |
26 | 3 | -6.9050330 | 0.38055846E-01 | -2.2317352 | 0.27239655E-01 |
27 | 2 | 39.679098 | 0.13717309 | 14.824430 | -0.32006664 |
28 | 1 | -79.631803 | 0.62641324E-01 | -28.746304 | 1.0591428 |
29 | 0 | 46.824345 | 0.12749544E-02 | 16.300917 | |
30 | 7 | -0.21163652E-08 | -0.68723841E-15 | 0.43910983E-14 | -0.57684426E-16 |
31 | 6 | 0.56109385E-05 | 0.38186281E-08 | 0.31898696E-02 | -0.26759299E-04 |
32 | 5 | -0.40164657E-03 | 0.22608617E-05 | -0.22372456 | 0.19561502E-02 |
33 | 4 | 0.92272104E-02 | 0.10289840E-03 | 4.8295456 | -0.45264980E-01 |
34 | 3 | -0.80993241E-01 | 0.81813938E-03 | -38.021416 | 0.39865375 |
35 | 2 | 0.28754352 | 0.13608947E-02 | 116.48395 | -1.4179393 |
36 | 1 | -0.41499682 | 0.41453381E-03 | -143.90731 | 2.0490399 |
37 | 0 | 0.20232414 | 0.10048102E-04 | 60.838472 | |
38 | 7 | -0.37862368E-08 | -0.38757603E-14 | 0.11479940E-14 | -0.41635801E-16 |
39 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
40 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
41 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
42 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
43 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
44 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
45 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
46 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479937E-14 | -0.41635796E-16 |
47 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
48 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
49 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
50 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
51 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
52 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
53 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
54 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479940E-14 | -0.41635801E-16 |
55 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
56 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
57 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
58 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
59 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
60 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
61 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
62 | 7 | -0.37862368E-08 | -0.38757603E-14 | 0.11479940E-14 | -0.41635801E-16 |
63 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
64 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
65 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
66 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
67 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
68 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
69 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
70 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479937E-14 | -0.41635796E-16 |
71 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
72 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
73 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
74 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
75 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
76 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
77 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
78 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479937E-14 | -0.41635796E-16 |
79 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
80 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
81 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
82 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
83 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
84 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
85 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
86 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479940E-14 | -0.41635801E-16 |
87 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
88 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
89 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
90 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
91 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
92 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
93 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
94 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479936E-14 | -0.41635794E-16 |
95 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
96 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
97 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
98 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
99 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
100 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
101 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
102 | 7 | -0.14484255E-08 | -0.22640907E-15 | 0.11860658E-13 | -0.17473455E-15 |
103 | 6 | 0.80640390E-05 | 0.55493782E-08 | 0.31828288E-02 | -0.26700235E-04 |
104 | 5 | -0.58275339E-03 | 0.32892043E-05 | -0.22332434 | 0.19526176E-02 |
105 | 4 | 0.13421983E-01 | 0.14977251E-03 | 4.8228790 | -0.45200897E-01 |
106 | 3 | -0.11791368 | 0.11914425E-02 | -37.983753 | 0.39823745 |
107 | 2 | 0.41875064 | 0.19825898E-02 | 116.41064 | -1.4169588 |
108 | 1 | -0.60444169 | 0.60433957E-03 | -143.86415 | 2.0483306 |
109 | 0 | 0.29470347 | 0.14596444E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.503_SHGC_0.22 | 35 | 1 | VerySmooth | 2.860 | 2.860 | 1.000 | 0.221 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 1.93472E-002 | 0.13126 | 0.64057 | 0.64057 | 0.24200 | 0.16318 | 0.24318 | 0.00000 | 0.84000 | 0.84000 | 0.10783 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | GAS TANK1 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
2 | WaterHeater:Mixed | GAS TANK2 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
3 | WaterHeater:Mixed | GAS TANK3 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
4 | WaterHeater:Mixed | GAS TANK4 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
5 | WaterHeater:Mixed | GAS TANK5 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
6 | WaterHeater:Mixed | GAS TANK6 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
7 | WaterHeater:Mixed | GAS TANK7 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | LGSTORE1_WALL_2 | 0 | 118.41 | 56.08 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
2 | LGSTORE1_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
3 | LGSTORE1_WALL_3_DOOR_1 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
4 | LGSTORE1_WALL_3_DOOR_2 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
5 | LGSTORE1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
6 | LGSTORE1_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
7 | LGSTORE1_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
8 | LGSTORE1_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
9 | LGSTORE1_WALL_1_WINDOW_3 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
10 | LGSTORE1_WALL_1_WINDOW_4 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
11 | LGSTORE1_WALL_1_DOOR_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 1 | No | No |
12 | LGSTORE1_WALL_1_DOOR_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 1 | No | No |
13 | LGSTORE1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
14 | LGSTORE1_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
15 | LGSTORE1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
16 | SMSTORE1_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
17 | SMSTORE1_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
18 | SMSTORE1_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
19 | SMSTORE1_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
20 | SMSTORE1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
21 | SMSTORE1_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
22 | SMSTORE1_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
23 | SMSTORE1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
24 | SMSTORE1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
25 | SMSTORE1_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
26 | SMSTORE1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
27 | SMSTORE2_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
28 | SMSTORE2_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
29 | SMSTORE2_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
30 | SMSTORE2_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
31 | SMSTORE2_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
32 | SMSTORE2_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
33 | SMSTORE2_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
34 | SMSTORE2_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
35 | SMSTORE2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
36 | SMSTORE2_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
37 | SMSTORE2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
38 | SMSTORE3_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
39 | SMSTORE3_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
40 | SMSTORE3_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
41 | SMSTORE3_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
42 | SMSTORE3_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
43 | SMSTORE3_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
44 | SMSTORE3_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
45 | SMSTORE3_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
46 | SMSTORE3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
47 | SMSTORE3_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
48 | SMSTORE3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
49 | SMSTORE4_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
50 | SMSTORE4_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
51 | SMSTORE4_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
52 | SMSTORE4_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
53 | SMSTORE4_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
54 | SMSTORE4_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 3 | No | No |
55 | SMSTORE4_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
56 | SMSTORE4_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
57 | SMSTORE4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
58 | SMSTORE4_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
59 | SMSTORE4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
60 | LGSTORE2_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
61 | LGSTORE2_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 4 | No | No |
62 | LGSTORE2_WALL_3_DOOR_1 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
63 | LGSTORE2_WALL_3_DOOR_2 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
64 | LGSTORE2_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
65 | LGSTORE2_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 4 | No | No |
66 | LGSTORE2_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
67 | LGSTORE2_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
68 | LGSTORE2_WALL_1_WINDOW_3 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
69 | LGSTORE2_WALL_1_WINDOW_4 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
70 | LGSTORE2_WALL_1_DOOR_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
71 | LGSTORE2_WALL_1_DOOR_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
72 | LGSTORE2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
73 | LGSTORE2_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
74 | LGSTORE2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
75 | SMSTORE5_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
76 | SMSTORE5_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
77 | SMSTORE5_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
78 | SMSTORE5_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
79 | SMSTORE5_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
80 | SMSTORE5_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
81 | SMSTORE5_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
82 | SMSTORE5_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
83 | SMSTORE5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
84 | SMSTORE5_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
85 | SMSTORE5_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
86 | SMSTORE6_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
87 | SMSTORE6_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
88 | SMSTORE6_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
89 | SMSTORE6_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
90 | SMSTORE6_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
91 | SMSTORE6_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
92 | SMSTORE6_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
93 | SMSTORE6_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
94 | SMSTORE6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
95 | SMSTORE6_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
96 | SMSTORE6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
97 | SMSTORE7_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
98 | SMSTORE7_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
99 | SMSTORE7_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
100 | SMSTORE7_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
101 | SMSTORE7_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
102 | SMSTORE7_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 3 | No | No |
103 | SMSTORE7_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
104 | SMSTORE7_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
105 | SMSTORE7_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
106 | SMSTORE7_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
107 | SMSTORE7_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
108 | SMSTORE8_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 4 | No | No |
109 | SMSTORE8_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 2 | No | No |
110 | SMSTORE8_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 2 | No | No |
111 | SMSTORE8_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 1 | No | No |
112 | SMSTORE8_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
113 | SMSTORE8_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 3 | No | No |
114 | SMSTORE8_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
115 | SMSTORE8_WALL_4 | 0 | 118.41 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 3 | No | No |
116 | SMSTORE8_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
117 | SMSTORE8_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
118 | SMSTORE8_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | LGSTORE1_INFILTRATION | TYPE1_INFIL_SCH | LGSTORE1 | 348.39 | 56.3 | 0.157 | 4.517E-004 | 2.488E-004 | 0.314 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | LGSTORE1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LGSTORE1 | 348.39 | 56.3 | 0.389 | 1.116E-003 | 6.149E-004 | 0.776 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | SMSTORE1_INFILTRATION | TYPE1_INFIL_SCH | SMSTORE1 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | SMSTORE1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE1 | 174.19 | 28.1 | 0.222 | 1.276E-003 | 8.648E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | SMSTORE2_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE2 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | SMSTORE2_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE2 | 174.19 | 28.1 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | SMSTORE3_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE3 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | SMSTORE3_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE3 | 174.19 | 28.1 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | SMSTORE4_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE4 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | SMSTORE4_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE4 | 174.19 | 28.1 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | LGSTORE2_INFILTRATION | TYPE3_INFIL_SCH | LGSTORE2 | 348.39 | 56.3 | 8.993E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | LGSTORE2_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LGSTORE2 | 348.39 | 56.3 | 0.389 | 1.116E-003 | 7.565E-004 | 0.776 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | SMSTORE5_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE5 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | SMSTORE5_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE5 | 174.19 | 28.1 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | SMSTORE6_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE6 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | SMSTORE6_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE6 | 174.19 | 28.1 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | SMSTORE7_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE7 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
18 | SMSTORE7_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE7 | 174.19 | 28.1 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | SMSTORE8_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE8 | 174.19 | 28.1 | 0.112 | 6.453E-004 | 2.994E-004 | 0.448 | 0.000 | 0.000 | 0.224 | 0.000 |
20 | SMSTORE8_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE8 | 174.19 | 28.1 | 0.222 | 1.276E-003 | 5.921E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | LGSTORE1 | Mixing/Well-Stirred |
2 | SMSTORE1 | Mixing/Well-Stirred |
3 | SMSTORE2 | Mixing/Well-Stirred |
4 | SMSTORE3 | Mixing/Well-Stirred |
5 | SMSTORE4 | Mixing/Well-Stirred |
6 | LGSTORE2 | Mixing/Well-Stirred |
7 | SMSTORE5 | Mixing/Well-Stirred |
8 | SMSTORE6 | Mixing/Well-Stirred |
9 | SMSTORE7 | Mixing/Well-Stirred |
10 | SMSTORE8 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone LGSTORE1 | 1.2000 |
3 | Zone SMSTORE1 | 1.2000 |
4 | Zone SMSTORE2 | 1.2000 |
5 | Zone SMSTORE3 | 1.2000 |
6 | Zone SMSTORE4 | 1.2000 |
7 | Zone LGSTORE2 | 1.2000 |
8 | Zone SMSTORE5 | 1.2000 |
9 | Zone SMSTORE6 | 1.2000 |
10 | Zone SMSTORE7 | 1.2000 |
11 | Zone SMSTORE8 | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone LGSTORE1 | 1.2000 |
3 | Zone SMSTORE1 | 1.2000 |
4 | Zone SMSTORE2 | 1.2000 |
5 | Zone SMSTORE3 | 1.2000 |
6 | Zone SMSTORE4 | 1.2000 |
7 | Zone LGSTORE2 | 1.2000 |
8 | Zone SMSTORE5 | 1.2000 |
9 | Zone SMSTORE6 | 1.2000 |
10 | Zone SMSTORE7 | 1.2000 |
11 | Zone SMSTORE8 | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | LGSTORE1 | Cooling | 25912.39713 | 31094.87655 | 1.90349 | 2.28418 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:40:00 | 34.86000 | 1.71575E-002 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
2 | LGSTORE1 | Heating | 1894.31454 | 2273.17745 | 7.99666E-002 | 0.41148 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 10:00:00 | 20.10000 | 1.47983E-002 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
3 | SMSTORE1 | Cooling | 13188.21521 | 15825.85825 | 0.96879 | 1.16255 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:50:00 | 35.12917 | 1.71580E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
4 | SMSTORE1 | Heating | 867.21246 | 1040.65495 | 3.67443E-002 | 0.20574 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 10:00:00 | 20.10000 | 1.47983E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
5 | SMSTORE2 | Cooling | 13205.09379 | 15846.11255 | 0.96999 | 1.16399 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:30:00 | 34.98750 | 1.71577E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
6 | SMSTORE2 | Heating | 955.08705 | 1146.10446 | 4.04718E-002 | 0.20574 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 20.10000 | 1.47983E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
7 | SMSTORE3 | Cooling | 13241.45542 | 15889.74650 | 0.97267 | 1.16720 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:30:00 | 34.98750 | 1.71577E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
8 | SMSTORE3 | Heating | 986.86985 | 1184.24382 | 4.17880E-002 | 0.20574 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 20.10000 | 1.47983E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
9 | SMSTORE4 | Cooling | 13130.96354 | 15757.15624 | 0.96455 | 1.15746 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:30:00 | 34.98750 | 1.71577E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
10 | SMSTORE4 | Heating | 1129.58451 | 1355.50141 | 4.77128E-002 | 0.20574 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 20.10000 | 1.47983E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
11 | LGSTORE2 | Cooling | 23024.92742 | 27629.91290 | 1.69125 | 2.02951 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:30:00 | 34.98750 | 1.71577E-002 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
12 | LGSTORE2 | Heating | 2068.97540 | 2482.77048 | 8.70711E-002 | 0.41148 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 10:00:00 | 20.10000 | 1.47983E-002 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
13 | SMSTORE5 | Cooling | 12110.28854 | 14532.34624 | 0.88953 | 1.06743 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:20:00 | 34.91667 | 1.71576E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
14 | SMSTORE5 | Heating | 1038.98838 | 1246.78606 | 4.39305E-002 | 0.20574 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 10:00:00 | 20.10000 | 1.47983E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
15 | SMSTORE6 | Cooling | 12062.94220 | 14475.53064 | 0.88605 | 1.06326 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:20:00 | 34.91667 | 1.71576E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
16 | SMSTORE6 | Heating | 1036.11770 | 1243.34124 | 4.38120E-002 | 0.20574 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 10:00:00 | 20.10000 | 1.47983E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
17 | SMSTORE7 | Cooling | 12118.54806 | 14542.25768 | 0.89013 | 1.06816 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:20:00 | 34.91667 | 1.71576E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
18 | SMSTORE7 | Heating | 1159.56169 | 1391.47403 | 4.89106E-002 | 0.20574 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 10:00:00 | 20.10000 | 1.47983E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
19 | SMSTORE8 | Cooling | 14194.04326 | 17032.85192 | 1.04249 | 1.25098 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:00:00 | 34.77500 | 1.71573E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
20 | SMSTORE8 | Heating | 1283.44983 | 1540.13980 | 5.41517E-002 | 0.20574 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 10:00:00 | 20.10000 | 1.47983E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC_1:1 | Cooling | Sensible | 36154.65 | 2.28418 | 2.28418 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 05:00:00 |
2 | PSZ-AC_1:1 | Heating | Sensible | 9903.44 | 0.41148 | 0.41148 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
3 | PSZ-AC_2:2 | Cooling | Sensible | 18394.57 | 1.16255 | 1.16255 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 05:00:00 |
4 | PSZ-AC_2:2 | Heating | Sensible | 4951.72 | 0.20574 | 0.20574 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
5 | PSZ-AC_3:3 | Cooling | Sensible | 18406.30 | 1.16400 | 1.16400 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 05:00:00 |
6 | PSZ-AC_3:3 | Heating | Sensible | 4951.72 | 0.20574 | 0.20574 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
7 | PSZ-AC_4:4 | Cooling | Sensible | 18447.15 | 1.16720 | 1.16720 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 05:00:00 |
8 | PSZ-AC_4:4 | Heating | Sensible | 4951.72 | 0.20574 | 0.20574 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
9 | PSZ-AC_5:5 | Cooling | Sensible | 18317.27 | 1.15746 | 1.15746 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 05:00:00 |
10 | PSZ-AC_5:5 | Heating | Sensible | 4951.72 | 0.20574 | 0.20574 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
11 | PSZ-AC_6:6 | Cooling | Sensible | 32810.51 | 2.02951 | 2.02951 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 05:00:00 |
12 | PSZ-AC_6:6 | Heating | Sensible | 9903.44 | 0.41148 | 0.41148 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
13 | PSZ-AC_7:7 | Cooling | Sensible | 17108.13 | 1.06748 | 1.06748 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 05:00:00 |
14 | PSZ-AC_7:7 | Heating | Sensible | 4951.72 | 0.20574 | 0.20574 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
15 | PSZ-AC_8:8 | Cooling | Sensible | 17051.71 | 1.06329 | 1.06329 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 05:00:00 |
16 | PSZ-AC_8:8 | Heating | Sensible | 4951.72 | 0.20574 | 0.20574 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 10:50:00 |
17 | PSZ-AC_9:9 | Cooling | Sensible | 17109.90 | 1.06816 | 1.06816 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 05:00:00 |
18 | PSZ-AC_9:9 | Heating | Sensible | 4951.72 | 0.20574 | 0.20574 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
19 | PSZ-AC_10:10 | Cooling | Sensible | 19479.55 | 1.25098 | 1.25098 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 05:00:00 |
20 | PSZ-AC_10:10 | Heating | Sensible | 4951.72 | 0.20574 | 0.20574 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 10:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | LGSTORE1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.28418 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.16255 |
3 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.16399 |
4 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.16720 |
5 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE4 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.15746 |
6 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | LGSTORE2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.02951 |
7 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE5 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.06743 |
8 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.06326 |
9 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE7 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.06816 |
10 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE8 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.25098 |
11 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.28418 |
12 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.28418 |
13 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.28418 |
14 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 2.28418 |
15 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.28418 |
16 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Main Design Air Flow Rate [m3/s] | 2.28418 |
17 | AirLoopHVAC | PSZ-AC_1:1 | User Heating Air Flow Ratio [] | 1.00000 |
18 | AirLoopHVAC | PSZ-AC_1:1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
19 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.16255 |
20 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.16255 |
21 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.16255 |
22 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.16255 |
23 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.16255 |
24 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Main Design Air Flow Rate [m3/s] | 1.16255 |
25 | AirLoopHVAC | PSZ-AC_2:2 | User Heating Air Flow Ratio [] | 1.00000 |
26 | AirLoopHVAC | PSZ-AC_2:2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
27 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.16399 |
28 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.16399 |
29 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.16399 |
30 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.16399 |
31 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.16400 |
32 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Main Design Air Flow Rate [m3/s] | 1.16400 |
33 | AirLoopHVAC | PSZ-AC_3:3 | User Heating Air Flow Ratio [] | 1.00000 |
34 | AirLoopHVAC | PSZ-AC_3:3 | Calculated Heating Air Flow Ratio [] | 1.00000 |
35 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.16720 |
36 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.16720 |
37 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.16720 |
38 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.16720 |
39 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.16720 |
40 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Main Design Air Flow Rate [m3/s] | 1.16720 |
41 | AirLoopHVAC | PSZ-AC_4:4 | User Heating Air Flow Ratio [] | 1.00000 |
42 | AirLoopHVAC | PSZ-AC_4:4 | Calculated Heating Air Flow Ratio [] | 1.00000 |
43 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.15746 |
44 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.15746 |
45 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.15746 |
46 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.15746 |
47 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.15746 |
48 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Main Design Air Flow Rate [m3/s] | 1.15746 |
49 | AirLoopHVAC | PSZ-AC_5:5 | User Heating Air Flow Ratio [] | 1.00000 |
50 | AirLoopHVAC | PSZ-AC_5:5 | Calculated Heating Air Flow Ratio [] | 1.00000 |
51 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.02951 |
52 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.02951 |
53 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.02951 |
54 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Heating Design Air Flow Rate [m3/s] | 2.02951 |
55 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.02951 |
56 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Main Design Air Flow Rate [m3/s] | 2.02951 |
57 | AirLoopHVAC | PSZ-AC_6:6 | User Heating Air Flow Ratio [] | 1.00000 |
58 | AirLoopHVAC | PSZ-AC_6:6 | Calculated Heating Air Flow Ratio [] | 1.00000 |
59 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.06743 |
60 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.06743 |
61 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.06743 |
62 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.06743 |
63 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.06748 |
64 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Main Design Air Flow Rate [m3/s] | 1.06748 |
65 | AirLoopHVAC | PSZ-AC_7:7 | User Heating Air Flow Ratio [] | 1.00000 |
66 | AirLoopHVAC | PSZ-AC_7:7 | Calculated Heating Air Flow Ratio [] | 0.99996 |
67 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.06326 |
68 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.06326 |
69 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.06326 |
70 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.06326 |
71 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.06329 |
72 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Main Design Air Flow Rate [m3/s] | 1.06329 |
73 | AirLoopHVAC | PSZ-AC_8:8 | User Heating Air Flow Ratio [] | 1.00000 |
74 | AirLoopHVAC | PSZ-AC_8:8 | Calculated Heating Air Flow Ratio [] | 0.99997 |
75 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.06816 |
76 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.06816 |
77 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.06816 |
78 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.06816 |
79 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.06816 |
80 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Main Design Air Flow Rate [m3/s] | 1.06816 |
81 | AirLoopHVAC | PSZ-AC_9:9 | User Heating Air Flow Ratio [] | 1.00000 |
82 | AirLoopHVAC | PSZ-AC_9:9 | Calculated Heating Air Flow Ratio [] | 1.00000 |
83 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.25098 |
84 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.25098 |
85 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.25098 |
86 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.25098 |
87 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.25098 |
88 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Main Design Air Flow Rate [m3/s] | 1.25098 |
89 | AirLoopHVAC | PSZ-AC_10:10 | User Heating Air Flow Ratio [] | 1.00000 |
90 | AirLoopHVAC | PSZ-AC_10:10 | Calculated Heating Air Flow Ratio [] | 1.00000 |
91 | AirLoopHVAC | PSZ-AC_1:1 | Design Supply Air Flow Rate [m3/s] | 2.28418 |
92 | AirLoopHVAC | PSZ-AC_2:2 | Design Supply Air Flow Rate [m3/s] | 1.16255 |
93 | AirLoopHVAC | PSZ-AC_3:3 | Design Supply Air Flow Rate [m3/s] | 1.16400 |
94 | AirLoopHVAC | PSZ-AC_4:4 | Design Supply Air Flow Rate [m3/s] | 1.16720 |
95 | AirLoopHVAC | PSZ-AC_5:5 | Design Supply Air Flow Rate [m3/s] | 1.15746 |
96 | AirLoopHVAC | PSZ-AC_6:6 | Design Supply Air Flow Rate [m3/s] | 2.02951 |
97 | AirLoopHVAC | PSZ-AC_7:7 | Design Supply Air Flow Rate [m3/s] | 1.06748 |
98 | AirLoopHVAC | PSZ-AC_8:8 | Design Supply Air Flow Rate [m3/s] | 1.06329 |
99 | AirLoopHVAC | PSZ-AC_9:9 | Design Supply Air Flow Rate [m3/s] | 1.06816 |
100 | AirLoopHVAC | PSZ-AC_10:10 | Design Supply Air Flow Rate [m3/s] | 1.25098 |
101 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.28418 |
102 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41148 |
103 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.28418 |
104 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 2444.18542 |
105 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.28418 |
106 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.28418 |
107 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.28418 |
108 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.50756 |
109 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.28418 |
110 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.14209 |
111 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.52279 |
112 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 56721.74000 |
113 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 28360.87000 |
114 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
115 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
116 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 56721.74000 |
117 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 52685.93633 |
118 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
119 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
120 | Coil:Heating:Fuel | PSZ-AC_1:1 HEATING COIL | Design Size Nominal Capacity [W] | 52685.93633 |
121 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.16255 |
122 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
123 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.16255 |
124 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1287.12798 |
125 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.16255 |
126 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.16255 |
127 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.16255 |
128 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.76728 |
129 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.16255 |
130 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.58128 |
131 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.77503 |
132 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 28868.90000 |
133 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 14434.45000 |
134 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
135 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
136 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 28868.90000 |
137 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 26810.42285 |
138 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
139 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
140 | Coil:Heating:Fuel | PSZ-AC_2:2 HEATING COIL | Design Size Nominal Capacity [W] | 26810.42285 |
141 | Controller:OutdoorAir | PSZ-AC_3:3_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.16400 |
142 | Controller:OutdoorAir | PSZ-AC_3:3_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
143 | Fan:SystemModel | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.16400 |
144 | Fan:SystemModel | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1288.72824 |
145 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.16400 |
146 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.16400 |
147 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.16400 |
148 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.76824 |
149 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.16400 |
150 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.58200 |
151 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.77600 |
152 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 28904.79000 |
153 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 14452.39500 |
154 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
155 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
156 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 28904.79000 |
157 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 26843.17894 |
158 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
159 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
160 | Coil:Heating:Fuel | PSZ-AC_3:3 HEATING COIL | Design Size Nominal Capacity [W] | 26843.17894 |
161 | Controller:OutdoorAir | PSZ-AC_4:4_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.16720 |
162 | Controller:OutdoorAir | PSZ-AC_4:4_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
163 | Fan:SystemModel | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.16720 |
164 | Fan:SystemModel | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1292.27471 |
165 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.16720 |
166 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.16720 |
167 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.16720 |
168 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.77035 |
169 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.16720 |
170 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.58360 |
171 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.77813 |
172 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 28984.33000 |
173 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 14492.16500 |
174 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
175 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
176 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 28984.33000 |
177 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 26916.38748 |
178 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
179 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
180 | Coil:Heating:Fuel | PSZ-AC_4:4 HEATING COIL | Design Size Nominal Capacity [W] | 26916.38748 |
181 | Controller:OutdoorAir | PSZ-AC_5:5_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.15746 |
182 | Controller:OutdoorAir | PSZ-AC_5:5_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
183 | Fan:SystemModel | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.15746 |
184 | Fan:SystemModel | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1281.49042 |
185 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.15746 |
186 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.15746 |
187 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.15746 |
188 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.76392 |
189 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.15746 |
190 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.57873 |
191 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.77164 |
192 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 28742.45000 |
193 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 14371.22500 |
194 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
195 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
196 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 28742.45000 |
197 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 26693.74942 |
198 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
199 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
200 | Coil:Heating:Fuel | PSZ-AC_5:5 HEATING COIL | Design Size Nominal Capacity [W] | 26693.74942 |
201 | Controller:OutdoorAir | PSZ-AC_6:6_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.02951 |
202 | Controller:OutdoorAir | PSZ-AC_6:6_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41148 |
203 | Fan:SystemModel | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.02951 |
204 | Fan:SystemModel | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 2171.66659 |
205 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.02951 |
206 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.02951 |
207 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.02951 |
208 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.33947 |
209 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.02951 |
210 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.01475 |
211 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.35301 |
212 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 50397.45000 |
213 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 25198.72500 |
214 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
215 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
216 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 50397.45000 |
217 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 46867.28890 |
218 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
219 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
220 | Coil:Heating:Fuel | PSZ-AC_6:6 HEATING COIL | Design Size Nominal Capacity [W] | 46867.28890 |
221 | Controller:OutdoorAir | PSZ-AC_7:7_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.06748 |
222 | Controller:OutdoorAir | PSZ-AC_7:7_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
223 | Fan:SystemModel | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.06748 |
224 | Fan:SystemModel | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1181.86612 |
225 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.06748 |
226 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.06748 |
227 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.06748 |
228 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.70453 |
229 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.06748 |
230 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.53374 |
231 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.71165 |
232 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 26507.99000 |
233 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 13253.99500 |
234 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
235 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
236 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 26507.99000 |
237 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 24637.14441 |
238 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
239 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
240 | Coil:Heating:Fuel | PSZ-AC_7:7 HEATING COIL | Design Size Nominal Capacity [W] | 24637.14441 |
241 | Controller:OutdoorAir | PSZ-AC_8:8_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.06329 |
242 | Controller:OutdoorAir | PSZ-AC_8:8_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
243 | Fan:SystemModel | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.06329 |
244 | Fan:SystemModel | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1177.23292 |
245 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.06329 |
246 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.06329 |
247 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.06329 |
248 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.70177 |
249 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.06329 |
250 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.53165 |
251 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.70886 |
252 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 26404.07000 |
253 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 13202.03500 |
254 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
255 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
256 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 26404.07000 |
257 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 24541.46545 |
258 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
259 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
260 | Coil:Heating:Fuel | PSZ-AC_8:8 HEATING COIL | Design Size Nominal Capacity [W] | 24541.46545 |
261 | Controller:OutdoorAir | PSZ-AC_9:9_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.06816 |
262 | Controller:OutdoorAir | PSZ-AC_9:9_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
263 | Fan:SystemModel | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.06816 |
264 | Fan:SystemModel | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1182.62207 |
265 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.06816 |
266 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.06816 |
267 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.06816 |
268 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.70499 |
269 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.06816 |
270 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.53408 |
271 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.71211 |
272 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 26524.94000 |
273 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 13262.47000 |
274 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
275 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
276 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 26524.94000 |
277 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 24653.67393 |
278 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
279 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
280 | Coil:Heating:Fuel | PSZ-AC_9:9 HEATING COIL | Design Size Nominal Capacity [W] | 24653.67393 |
281 | Controller:OutdoorAir | PSZ-AC_10:10_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.25098 |
282 | Controller:OutdoorAir | PSZ-AC_10:10_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
283 | Fan:SystemModel | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.25098 |
284 | Fan:SystemModel | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1385.03628 |
285 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.25098 |
286 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.25098 |
287 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.25098 |
288 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.82565 |
289 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.25098 |
290 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.62549 |
291 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.83399 |
292 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 31064.88000 |
293 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 15532.44000 |
294 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
295 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
296 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 31064.88000 |
297 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 29331.79290 |
298 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
299 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
300 | Coil:Heating:Fuel | PSZ-AC_10:10 HEATING COIL | Design Size Nominal Capacity [W] | 29331.79290 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | 54919.7 | 11.77 | 11.77 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | 27951.7 | 11.95 | 11.95 | |||
3 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | 27986.5 | 11.95 | 11.95 | |||
4 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | 28063.5 | 11.95 | 11.95 | |||
5 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | 27829.3 | 11.95 | 11.95 | |||
6 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | 48796.3 | 11.77 | 11.77 | |||
7 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | 25665.8 | 11.95 | 11.95 | |||
8 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | 25565.2 | 11.95 | 11.95 | |||
9 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | 25682.3 | 11.95 | 11.95 | |||
10 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | 30078.0 | 11.95 | 11.95 |
Zone Name | # Surfaces | |
1 | LGSTORE1 | 15 |
2 | SMSTORE1 | 11 |
3 | SMSTORE2 | 11 |
4 | SMSTORE3 | 11 |
5 | SMSTORE4 | 11 |
6 | LGSTORE2 | 15 |
7 | SMSTORE5 | 11 |
8 | SMSTORE6 | 11 |
9 | SMSTORE7 | 11 |
10 | SMSTORE8 | 11 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | LGSTORE1_WALL_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | LGSTORE1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 71.15 | 78.94 | 71.15 | 0.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | LGSTORE1_WALL_3_DOOR_1 | Door | LGSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
4 | LGSTORE1_WALL_3_DOOR_2 | Door | LGSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
5 | LGSTORE1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
6 | LGSTORE1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 58.18 | 78.94 | 58.18 | 180.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
7 | LGSTORE1_WALL_1_WINDOW_1 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.22 | N/A | 2.860 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
8 | LGSTORE1_WALL_1_WINDOW_2 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.22 | N/A | 2.860 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
9 | LGSTORE1_WALL_1_WINDOW_3 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.22 | N/A | 2.860 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
10 | LGSTORE1_WALL_1_WINDOW_4 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.22 | N/A | 2.860 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
11 | LGSTORE1_WALL_1_DOOR_1 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.22 | N/A | 2.860 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
12 | LGSTORE1_WALL_1_DOOR_2 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.22 | N/A | 2.860 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
13 | LGSTORE1_FLOOR | Floor | CTF - ConductionTransferFunction | LGSTORE1_FLOOR_FFACTOR | 0.199 | 0.190 | 348.39 | 348.39 | 348.39 | 270.00 | 180.00 | 22.86 | 15.24 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | LGSTORE1_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 348.39 | 348.39 | 348.39 | 270.00 | 0.00 | 22.86 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
15 | LGSTORE1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 696.77 | 696.77 | 696.77 | 0.00 | 90.00 | 696.77 | 1.00 | 0.00 | LGSTORE1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
16 | SMSTORE1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 29.09 | 39.47 | 29.09 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
17 | SMSTORE1_WALL_1_WINDOW_1 | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.22 | N/A | 2.860 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
18 | SMSTORE1_WALL_1_WINDOW_2 | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.22 | N/A | 2.860 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
19 | SMSTORE1_WALL_1_DOOR | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.22 | N/A | 2.860 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
20 | SMSTORE1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | SMSTORE1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 35.57 | 39.47 | 35.57 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | SMSTORE1_WALL_3_DOOR | Door | SMSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
23 | SMSTORE1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE2_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | SMSTORE1_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE1_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | SMSTORE1_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
26 | SMSTORE1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
27 | SMSTORE2_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | SMSTORE2_WALL_1_WINDOW_1 | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.22 | N/A | 2.860 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
29 | SMSTORE2_WALL_1_WINDOW_2 | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.22 | N/A | 2.860 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
30 | SMSTORE2_WALL_1_DOOR | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.22 | N/A | 2.860 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
31 | SMSTORE2_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | SMSTORE2_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | SMSTORE2_WALL_3_DOOR | Door | SMSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
34 | SMSTORE2_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE3_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | SMSTORE2_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE2_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | SMSTORE2_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | SMSTORE2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | SMSTORE3_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | SMSTORE3_WALL_1_WINDOW_1 | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.22 | N/A | 2.860 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
40 | SMSTORE3_WALL_1_WINDOW_2 | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.22 | N/A | 2.860 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
41 | SMSTORE3_WALL_1_DOOR | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.22 | N/A | 2.860 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
42 | SMSTORE3_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE2_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | SMSTORE3_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | SMSTORE3_WALL_3_DOOR | Door | SMSTORE3_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
45 | SMSTORE3_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE4_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | SMSTORE3_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE3_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
47 | SMSTORE3_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
48 | SMSTORE3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
49 | SMSTORE4_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | SMSTORE4_WALL_1_WINDOW_1 | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.22 | N/A | 2.860 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
51 | SMSTORE4_WALL_1_WINDOW_2 | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.22 | N/A | 2.860 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
52 | SMSTORE4_WALL_1_DOOR | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.22 | N/A | 2.860 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | SMSTORE4_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE3_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | SMSTORE4_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | SMSTORE4_WALL_3_DOOR | Door | SMSTORE4_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | SMSTORE4_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE2_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | SMSTORE4_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE4_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | SMSTORE4_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | SMSTORE4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | LGSTORE2_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE4_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | LGSTORE2_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 71.19 | 78.94 | 71.19 | 0.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
62 | LGSTORE2_WALL_3_DOOR_1 | Door | LGSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
63 | LGSTORE2_WALL_3_DOOR_2 | Door | LGSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
64 | LGSTORE2_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE5_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LGSTORE2_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 58.22 | 78.94 | 58.22 | 180.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
66 | LGSTORE2_WALL_1_WINDOW_1 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.22 | N/A | 2.860 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | LGSTORE2_WALL_1_WINDOW_2 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.22 | N/A | 2.860 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | LGSTORE2_WALL_1_WINDOW_3 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.22 | N/A | 2.860 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | LGSTORE2_WALL_1_WINDOW_4 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.22 | N/A | 2.860 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LGSTORE2_WALL_1_DOOR_1 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.22 | N/A | 2.860 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
71 | LGSTORE2_WALL_1_DOOR_2 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.22 | N/A | 2.860 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
72 | LGSTORE2_FLOOR | Floor | CTF - ConductionTransferFunction | LGSTORE2_FLOOR_FFACTOR | 0.112 | 0.109 | 348.39 | 348.39 | 348.39 | 270.00 | 180.00 | 22.86 | 15.24 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
73 | LGSTORE2_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 348.39 | 348.39 | 348.39 | 270.00 | 0.00 | 22.86 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
74 | LGSTORE2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 696.77 | 696.77 | 696.77 | 0.00 | 90.00 | 696.77 | 1.00 | 0.00 | LGSTORE2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
75 | SMSTORE5_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | SMSTORE5_WALL_1_WINDOW_1 | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.22 | N/A | 2.860 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
77 | SMSTORE5_WALL_1_WINDOW_2 | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.22 | N/A | 2.860 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | SMSTORE5_WALL_1_DOOR | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.22 | N/A | 2.860 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
79 | SMSTORE5_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE2_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | SMSTORE5_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 35.59 | 39.47 | 35.59 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | SMSTORE5_WALL_3_DOOR | Door | SMSTORE5_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
82 | SMSTORE5_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE6_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
83 | SMSTORE5_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE5_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
84 | SMSTORE5_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
85 | SMSTORE5_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE5_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | SMSTORE6_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | SMSTORE6_WALL_1_WINDOW_1 | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.22 | N/A | 2.860 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | SMSTORE6_WALL_1_WINDOW_2 | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.22 | N/A | 2.860 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
89 | SMSTORE6_WALL_1_DOOR | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.22 | N/A | 2.860 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | SMSTORE6_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE5_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | SMSTORE6_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | SMSTORE6_WALL_3_DOOR | Door | SMSTORE6_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
93 | SMSTORE6_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE7_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | SMSTORE6_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE6_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
95 | SMSTORE6_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
96 | SMSTORE6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
97 | SMSTORE7_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | SMSTORE7_WALL_1_WINDOW_1 | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.22 | N/A | 2.860 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | SMSTORE7_WALL_1_WINDOW_2 | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.22 | N/A | 2.860 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
100 | SMSTORE7_WALL_1_DOOR | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.22 | N/A | 2.860 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
101 | SMSTORE7_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE6_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
102 | SMSTORE7_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 35.59 | 39.47 | 35.59 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | SMSTORE7_WALL_3_DOOR | Door | SMSTORE7_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
104 | SMSTORE7_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE8_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | SMSTORE7_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE7_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
106 | SMSTORE7_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
107 | SMSTORE7_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE7_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
108 | SMSTORE8_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | SMSTORE8_WALL_1_WINDOW_1 | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.22 | N/A | 2.860 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
110 | SMSTORE8_WALL_1_WINDOW_2 | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.22 | N/A | 2.860 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
111 | SMSTORE8_WALL_1_DOOR | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.22 | N/A | 2.860 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
112 | SMSTORE8_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE7_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | SMSTORE8_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | SMSTORE8_WALL_3_DOOR | Door | SMSTORE8_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
115 | SMSTORE8_WALL_4 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | SMSTORE8_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE8_FLOOR_FFACTOR | 0.289 | 0.270 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | SMSTORE8_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | SMSTORE8_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE8_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | LGSTORE1 | RunPeriod: RUNPERIOD 1 | 2.7158862066E-002 | 0.1673937341 | Pass | Pass | 3.6393093516E-002 | 0.1624413465 | Pass | Pass |
2 | SMSTORE1 | RunPeriod: RUNPERIOD 1 | 2.8359038050E-002 | 0.1757051525 | Pass | Pass | 4.9779547887E-002 | 0.3041785402 | Pass | Pass |
3 | SMSTORE2 | RunPeriod: RUNPERIOD 1 | 4.0855916706E-002 | 0.2002480220 | Pass | Pass | 0.1170478468 | 0.8254348730 | Pass | Pass |
4 | SMSTORE3 | RunPeriod: RUNPERIOD 1 | 4.0946641108E-002 | 0.2025395437 | Pass | Pass | 0.1215199961 | 0.8377841965 | Pass | Pass |
5 | SMSTORE4 | RunPeriod: RUNPERIOD 1 | 4.0159495354E-002 | 0.1954697323 | Pass | Pass | 0.1122220586 | 0.7934685328 | Pass | Pass |
6 | LGSTORE2 | RunPeriod: RUNPERIOD 1 | 3.9602627820E-002 | 0.1900174644 | Pass | Pass | 0.1213865397 | 0.7855505981 | Pass | Pass |
7 | SMSTORE5 | RunPeriod: RUNPERIOD 1 | 3.8721935507E-002 | 0.1886514575 | Pass | Pass | 0.1268951710 | 0.8249330696 | Pass | Pass |
8 | SMSTORE6 | RunPeriod: RUNPERIOD 1 | 3.8571462731E-002 | 0.1875723897 | Pass | Pass | 0.1247966191 | 0.8117358127 | Pass | Pass |
9 | SMSTORE7 | RunPeriod: RUNPERIOD 1 | 3.8545353175E-002 | 0.1841806383 | Pass | Pass | 0.1252809923 | 0.8149747940 | Pass | Pass |
10 | SMSTORE8 | RunPeriod: RUNPERIOD 1 | 4.3101151324E-002 | 0.1986194869 | Pass | Pass | 0.2443990461 | 1.8715147747 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:06
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 3409.02 | -599.2 | 0.00 | -1509.9 | 3563.87 | 4863.78 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:06
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 20.10 | 0.00 | 20.10 | Wetbulb [C] | 1.80 | 0.00 |
HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 35.20 | 8.50 | 25.80 | Wetbulb [C] | 4.10 | 160.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 57.00 | 12 | |||
Feb | 0.00 | 0 | |||
Mar | 153.60 | 31 | |||
Apr | 87.00 | 59 | |||
May | 227.22 | 128 | |||
Jun | 144.58 | 109 | |||
Jul | 42.40 | 24 | |||
Aug | 164.90 | 163 | |||
Sep | 119.60 | 50 | |||
Oct | 365.70 | 188 | |||
Nov | 70.90 | 67 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:06
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_2 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE1_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 78.94 | 71.15 | 0.00 | 90.00 | N |
LGSTORE1_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 78.94 | 58.18 | 180.00 | 90.00 | S |
LGSTORE1_FLOOR | LGSTORE1_FLOOR_FFACTOR | 1.00 | 0.193 | 0.199 | 348.39 | 348.39 | 270.00 | 180.00 | |
LGSTORE1_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 348.39 | 348.39 | 270.00 | 0.00 | |
SMSTORE1_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 39.47 | 29.09 | 180.00 | 90.00 | S |
SMSTORE1_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 39.47 | 35.57 | 0.00 | 90.00 | N |
SMSTORE1_FLOOR | SMSTORE1_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE1_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE2_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE2_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE2_FLOOR | SMSTORE2_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE2_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE3_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE3_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE3_FLOOR | SMSTORE3_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE3_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE4_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE4_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE4_FLOOR | SMSTORE4_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE4_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 | |
LGSTORE2_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 78.94 | 71.19 | 0.00 | 90.00 | N |
LGSTORE2_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 78.94 | 58.22 | 180.00 | 90.00 | S |
LGSTORE2_FLOOR | LGSTORE2_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 348.39 | 348.39 | 270.00 | 180.00 | |
LGSTORE2_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 348.39 | 348.39 | 270.00 | 0.00 | |
SMSTORE5_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE5_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE5_FLOOR | SMSTORE5_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE5_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE6_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE6_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE6_FLOOR | SMSTORE6_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE6_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE7_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE7_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE7_FLOOR | SMSTORE7_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE7_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE8_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE8_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE8_WALL_4 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE8_FLOOR | SMSTORE8_FLOOR_FFACTOR | 1.00 | 0.276 | 0.289 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE8_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE1_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE2_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE2_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE3_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE3_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE4_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE4_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
LGSTORE2_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE2_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE5_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE5_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE6_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE6_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE7_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE7_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE8_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 696.77 | 0.00 | 90.00 | N | ||
SMSTORE1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
LGSTORE2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 696.77 | 0.00 | 90.00 | N | ||
SMSTORE5_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE7_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE8_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.503_SHGC_0.22 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.860 | 0.221 | 0.243 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.503_SHGC_0.22 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.860 | 0.221 | 0.243 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_3 | NONRESWINDOW_U_0.503_SHGC_0.22 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.860 | 0.221 | 0.243 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_4 | NONRESWINDOW_U_0.503_SHGC_0.22 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.860 | 0.221 | 0.243 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_DOOR_1 | NONRESWINDOW_U_0.503_SHGC_0.22 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.860 | 0.221 | 0.243 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_DOOR_2 | NONRESWINDOW_U_0.503_SHGC_0.22 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.860 | 0.221 | 0.243 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.503_SHGC_0.22 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.860 | 0.221 | 0.243 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.503_SHGC_0.22 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.860 | 0.221 | 0.243 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_DOOR | NONRESWINDOW_U_0.503_SHGC_0.22 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.860 | 0.221 | 0.243 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.503_SHGC_0.22 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.860 | 0.221 | 0.243 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.503_SHGC_0.22 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.860 | 0.221 | 0.243 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_DOOR | NONRESWINDOW_U_0.503_SHGC_0.22 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.860 | 0.221 | 0.243 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.503_SHGC_0.22 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.860 | 0.221 | 0.243 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.503_SHGC_0.22 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.860 | 0.221 | 0.243 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_DOOR | NONRESWINDOW_U_0.503_SHGC_0.22 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.860 | 0.221 | 0.243 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.503_SHGC_0.22 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.860 | 0.221 | 0.243 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.503_SHGC_0.22 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.860 | 0.221 | 0.243 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_DOOR | NONRESWINDOW_U_0.503_SHGC_0.22 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.860 | 0.221 | 0.243 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.503_SHGC_0.22 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.860 | 0.221 | 0.243 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.503_SHGC_0.22 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.860 | 0.221 | 0.243 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_3 | NONRESWINDOW_U_0.503_SHGC_0.22 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.860 | 0.221 | 0.243 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_4 | NONRESWINDOW_U_0.503_SHGC_0.22 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.860 | 0.221 | 0.243 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_DOOR_1 | NONRESWINDOW_U_0.503_SHGC_0.22 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.860 | 0.221 | 0.243 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_DOOR_2 | NONRESWINDOW_U_0.503_SHGC_0.22 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.860 | 0.221 | 0.243 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.503_SHGC_0.22 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.860 | 0.221 | 0.243 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.503_SHGC_0.22 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.860 | 0.221 | 0.243 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_DOOR | NONRESWINDOW_U_0.503_SHGC_0.22 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.860 | 0.221 | 0.243 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.503_SHGC_0.22 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.860 | 0.221 | 0.243 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.503_SHGC_0.22 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.860 | 0.221 | 0.243 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_DOOR | NONRESWINDOW_U_0.503_SHGC_0.22 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.860 | 0.221 | 0.243 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.503_SHGC_0.22 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.860 | 0.221 | 0.243 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.503_SHGC_0.22 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.860 | 0.221 | 0.243 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_DOOR | NONRESWINDOW_U_0.503_SHGC_0.22 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.860 | 0.221 | 0.243 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.503_SHGC_0.22 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.860 | 0.221 | 0.243 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.503_SHGC_0.22 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.860 | 0.221 | 0.243 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_DOOR | NONRESWINDOW_U_0.503_SHGC_0.22 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.860 | 0.221 | 0.243 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
Total or Average | 124.40 | 2.860 | 0.221 | 0.243 | |||||||||||||||||
North Total or Average | 0.00 | - | - | - | |||||||||||||||||
Non-North Total or Average | 124.40 | 2.860 | 0.221 | 0.243 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
LGSTORE1_WALL_3_DOOR_1 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.90 | LGSTORE1_WALL_3 |
LGSTORE1_WALL_3_DOOR_2 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.90 | LGSTORE1_WALL_3 |
SMSTORE1_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.90 | SMSTORE1_WALL_3 |
SMSTORE2_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE2_WALL_3 |
SMSTORE3_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE3_WALL_3 |
SMSTORE4_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE4_WALL_3 |
LGSTORE2_WALL_3_DOOR_1 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | LGSTORE2_WALL_3 |
LGSTORE2_WALL_3_DOOR_2 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | LGSTORE2_WALL_3 |
SMSTORE5_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE5_WALL_3 |
SMSTORE6_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE6_WALL_3 |
SMSTORE7_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE7_WALL_3 |
SMSTORE8_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE8_WALL_3 |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:06
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
LGSTORE1_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_3 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_4 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_DOOR_1 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_DOOR_2 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_3 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_4 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_DOOR_1 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_DOOR_2 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:06
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
LGSTORE1_LIGHTS | LGSTORE1 | LGSTORE1 | GENERAL | 9.6053 | 348.39 | 3346.35 | LightsWired | LTG_SCH_BASE_LPD1 | 83.91 | 168.00 | 82.62 | 0.0000 | Y | 51.90 |
LGSTORE1_LIGHTS_ALLOWANCE | LGSTORE1 | LGSTORE1 | GENERAL | 5.6969 | 348.39 | 1984.73 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | 97.50 | 112.00 | 94.53 | 0.0000 | Y | 35.22 |
SMSTORE1_LIGHTS | SMSTORE1 | SMSTORE1 | GENERAL | 9.7206 | 174.19 | 1693.26 | LightsWired | LTG_SCH_BASE_SMALL_LPD1 | 85.41 | 168.00 | 84.05 | 0.0000 | Y | 26.72 |
SMSTORE1_LIGHTS_ALLOWANCE | SMSTORE1 | SMSTORE1 | GENERAL | 8.5685 | 174.19 | 1492.57 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | 97.50 | 112.00 | 94.53 | 0.0000 | Y | 26.49 |
SMSTORE2_LIGHTS | SMSTORE2 | SMSTORE2 | GENERAL | 9.6995 | 174.19 | 1689.58 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 68.73 | 168.00 | 65.95 | 0.0000 | Y | 20.92 |
SMSTORE2_LIGHTS_ALLOWANCE | SMSTORE2 | SMSTORE2 | GENERAL | 6.9539 | 174.19 | 1211.32 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 84.29 | 73.25 | 0.0000 | Y | 16.66 |
SMSTORE3_LIGHTS | SMSTORE3 | SMSTORE3 | GENERAL | 9.6995 | 174.19 | 1689.58 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 68.73 | 168.00 | 65.95 | 0.0000 | Y | 20.92 |
SMSTORE3_LIGHTS_ALLOWANCE | SMSTORE3 | SMSTORE3 | GENERAL | 6.9539 | 174.19 | 1211.32 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 84.29 | 73.25 | 0.0000 | Y | 16.66 |
SMSTORE4_LIGHTS | SMSTORE4 | SMSTORE4 | GENERAL | 9.6995 | 174.19 | 1689.58 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 68.73 | 168.00 | 65.95 | 0.0000 | Y | 20.92 |
SMSTORE4_LIGHTS_ALLOWANCE | SMSTORE4 | SMSTORE4 | GENERAL | 6.9539 | 174.19 | 1211.32 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 84.29 | 73.25 | 0.0000 | Y | 16.66 |
LGSTORE2_LIGHTS | LGSTORE2 | LGSTORE2 | GENERAL | 9.5842 | 348.39 | 3339.00 | LightsWired | LTG_SCH_BASE_LPD2 | 62.11 | 168.00 | 59.29 | 0.0000 | Y | 37.16 |
LGSTORE2_LIGHTS_ALLOWANCE | LGSTORE2 | LGSTORE2 | GENERAL | 0.0000 | 348.39 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE5_LIGHTS | SMSTORE5 | SMSTORE5 | GENERAL | 9.6995 | 174.19 | 1689.58 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 60.29 | 0.0000 | Y | 19.12 |
SMSTORE5_LIGHTS_ALLOWANCE | SMSTORE5 | SMSTORE5 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE6_LIGHTS | SMSTORE6 | SMSTORE6 | GENERAL | 9.6995 | 174.19 | 1689.58 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 60.29 | 0.0000 | Y | 19.12 |
SMSTORE6_LIGHTS_ALLOWANCE | SMSTORE6 | SMSTORE6 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE7_LIGHTS | SMSTORE7 | SMSTORE7 | GENERAL | 9.6995 | 174.19 | 1689.58 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 60.29 | 0.0000 | Y | 19.12 |
SMSTORE7_LIGHTS_ALLOWANCE | SMSTORE7 | SMSTORE7 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE8_LIGHTS | SMSTORE8 | SMSTORE8 | GENERAL | 9.6995 | 174.19 | 1689.58 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 60.29 | 0.0000 | Y | 19.12 |
SMSTORE8_LIGHTS_ALLOWANCE | SMSTORE8 | SMSTORE8 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
Interior Lighting Total | 6.5342 | 4180.64 | 27316.92 | 366.68 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 455.59 | AstronomicalClock | - | 41.93 | 41.93 | 3.59 | |
EXTERIOR_LIGHTS_B | 2744.24 | AstronomicalClock | - | 83.83 | 62.88 | 32.39 | |
EXTERIOR_LIGHTS_C | 2307.23 | AstronomicalClock | - | 83.83 | 55.88 | 24.20 | |
Exterior Lighting Total | 5507.06 | 60.18 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:06
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 56721.74 | 39766.48 | 16955.26 | 0.70 | 3.73 | |||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 28868.90 | 20239.41 | 8629.49 | 0.70 | 3.80 | |||
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 28904.79 | 20264.57 | 8640.22 | 0.70 | 3.80 | |||
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 28984.33 | 20320.33 | 8664.00 | 0.70 | 3.80 | |||
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 28742.45 | 20150.76 | 8591.69 | 0.70 | 3.80 | |||
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 50397.45 | 35332.64 | 15064.81 | 0.70 | 3.73 | |||
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 26507.99 | 18584.22 | 7923.77 | 0.70 | 3.80 | |||
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 26404.07 | 18511.37 | 7892.70 | 0.70 | 3.80 | |||
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 26524.94 | 18596.10 | 7928.84 | 0.70 | 3.80 | |||
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 31064.88 | 21778.97 | 9285.91 | 0.70 | 3.80 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC_1:1 COOLING COIL | 54919.7 | 11.77 | 11.77 | ||||
PSZ-AC_2:2 COOLING COIL | 27951.7 | 11.95 | 11.95 | ||||
PSZ-AC_3:3 COOLING COIL | 27986.5 | 11.95 | 11.95 | ||||
PSZ-AC_4:4 COOLING COIL | 28063.5 | 11.95 | 11.95 | ||||
PSZ-AC_5:5 COOLING COIL | 27829.3 | 11.95 | 11.95 | ||||
PSZ-AC_6:6 COOLING COIL | 48796.3 | 11.77 | 11.77 | ||||
PSZ-AC_7:7 COOLING COIL | 25665.8 | 11.95 | 11.95 | ||||
PSZ-AC_8:8 COOLING COIL | 25565.2 | 11.95 | 11.95 | ||||
PSZ-AC_9:9 COOLING COIL | 25682.3 | 11.95 | 11.95 | ||||
PSZ-AC_10:10 COOLING COIL | 30078.0 | 11.95 | 11.95 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | 52685.94 | 0.80 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | 26810.42 | 0.80 | |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | 26843.18 | 0.80 | |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | 26916.39 | 0.80 | |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | 26693.75 | 0.80 | |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | 46867.29 | 0.80 | |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | 24637.14 | 0.80 | |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | 24541.47 | 0.80 | |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | 24653.67 | 0.80 | |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | 29331.79 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 2.28 | 2444.19 | 1070.05 | 1.00 | 1.30 | General | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.16 | 1287.13 | 1107.16 | 1.00 | 1.37 | General | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.16 | 1288.73 | 1107.16 | 1.00 | 1.37 | General | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:40:00 |
PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.17 | 1292.27 | 1107.16 | 1.00 | 1.37 | General | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:10:00 |
PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.16 | 1281.49 | 1107.16 | 1.00 | 1.37 | General | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 2.03 | 2171.67 | 1070.05 | 1.00 | 1.31 | General | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 09:40:00 |
PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.07 | 1181.87 | 1107.16 | 1.00 | 1.39 | General | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:30:00 |
PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.06 | 1177.23 | 1107.16 | 1.00 | 1.39 | General | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:30:00 |
PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.07 | 1182.62 | 1107.16 | 1.00 | 1.39 | General | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.25 | 1385.04 | 1107.16 | 1.00 | 1.35 | General | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 10:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
GAS TANK1 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK2 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK3 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK4 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK5 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK6 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK7 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:06
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
LGSTORE1 | 25912.40 | 31094.88 | 89.25 | 1.903 | 2.284 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:40:00 | 23.89 | 23.88 | 0.01040 | 34.86 | 0.01716 | 0.411 | 0.00 |
SMSTORE1 | 13188.22 | 15825.86 | 90.85 | 0.969 | 1.163 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:50:00 | 23.89 | 23.88 | 0.01047 | 35.13 | 0.01716 | 0.206 | 0.00 |
SMSTORE2 | 13205.09 | 15846.11 | 90.97 | 0.970 | 1.164 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:30:00 | 23.89 | 23.88 | 0.01046 | 34.99 | 0.01716 | 0.206 | 0.00 |
SMSTORE3 | 13241.46 | 15889.75 | 91.22 | 0.973 | 1.167 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:30:00 | 23.89 | 23.88 | 0.01046 | 34.99 | 0.01716 | 0.206 | 0.00 |
SMSTORE4 | 13130.96 | 15757.16 | 90.46 | 0.965 | 1.157 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:30:00 | 23.89 | 23.88 | 0.01047 | 34.99 | 0.01716 | 0.206 | 0.00 |
LGSTORE2 | 23024.93 | 27629.91 | 79.31 | 1.691 | 2.030 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:30:00 | 23.89 | 23.88 | 0.01053 | 34.99 | 0.01716 | 0.411 | 0.00 |
SMSTORE5 | 12110.29 | 14532.35 | 83.43 | 0.890 | 1.067 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:20:00 | 23.89 | 23.88 | 0.01060 | 34.92 | 0.01716 | 0.206 | 0.00 |
SMSTORE6 | 12062.94 | 14475.53 | 83.10 | 0.886 | 1.063 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:20:00 | 23.89 | 23.88 | 0.01061 | 34.92 | 0.01716 | 0.206 | 0.00 |
SMSTORE7 | 12118.55 | 14542.26 | 83.48 | 0.890 | 1.068 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:20:00 | 23.89 | 23.88 | 0.01060 | 34.92 | 0.01716 | 0.206 | 0.00 |
SMSTORE8 | 14194.04 | 17032.85 | 97.78 | 1.042 | 1.251 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:00:00 | 23.89 | 23.88 | 0.01044 | 34.78 | 0.01716 | 0.206 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
LGSTORE1 | 1894.31 | 2273.18 | 6.52 | 0.080 | 0.411 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 10:00:00 | 21.11 | 21.11 | 0.01217 | 20.10 | 0.01480 | 0.411 | 0.00 |
SMSTORE1 | 867.21 | 1040.65 | 5.97 | 0.037 | 0.206 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 10:00:00 | 21.11 | 21.11 | 0.01208 | 20.10 | 0.01480 | 0.206 | 0.00 |
SMSTORE2 | 955.09 | 1146.10 | 6.58 | 0.040 | 0.206 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 21.11 | 21.11 | 0.01281 | 20.10 | 0.01480 | 0.206 | 0.00 |
SMSTORE3 | 986.87 | 1184.24 | 6.80 | 0.042 | 0.206 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 21.11 | 21.11 | 0.01277 | 20.10 | 0.01480 | 0.206 | 0.00 |
SMSTORE4 | 1129.58 | 1355.50 | 7.78 | 0.048 | 0.206 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 21.11 | 21.11 | 0.01257 | 20.10 | 0.01480 | 0.206 | 0.00 |
LGSTORE2 | 2068.98 | 2482.77 | 7.13 | 0.087 | 0.411 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 10:00:00 | 21.11 | 21.11 | 0.01266 | 20.10 | 0.01480 | 0.411 | 0.00 |
SMSTORE5 | 1038.99 | 1246.79 | 7.16 | 0.044 | 0.206 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 10:00:00 | 21.11 | 21.11 | 0.01278 | 20.10 | 0.01480 | 0.206 | 0.00 |
SMSTORE6 | 1036.12 | 1243.34 | 7.14 | 0.044 | 0.206 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 10:00:00 | 21.11 | 21.11 | 0.01278 | 20.10 | 0.01480 | 0.206 | 0.00 |
SMSTORE7 | 1159.56 | 1391.47 | 7.99 | 0.049 | 0.206 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 10:00:00 | 21.11 | 21.11 | 0.01261 | 20.10 | 0.01480 | 0.206 | 0.00 |
SMSTORE8 | 1283.45 | 1540.14 | 8.84 | 0.054 | 0.206 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 10:00:00 | 21.11 | 21.11 | 0.01293 | 20.10 | 0.01480 | 0.206 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC_1:1 | 2.28 | 2.28 | 0.41 | 0.41 | 2.2842 | 2.2842 | 2.2842 | 1.0000 | 1.0000 |
PSZ-AC_2:2 | 1.16 | 1.16 | 0.21 | 0.21 | 1.1626 | 1.1626 | 1.1626 | 1.0000 | 1.0000 |
PSZ-AC_3:3 | 1.16 | 1.16 | 0.21 | 0.21 | 1.1640 | 1.1640 | 1.1640 | 1.0000 | 1.0000 |
PSZ-AC_4:4 | 1.17 | 1.17 | 0.21 | 0.21 | 1.1672 | 1.1672 | 1.1672 | 1.0000 | 1.0000 |
PSZ-AC_5:5 | 1.16 | 1.16 | 0.21 | 0.21 | 1.1575 | 1.1575 | 1.1575 | 1.0000 | 1.0000 |
PSZ-AC_6:6 | 2.03 | 2.03 | 0.41 | 0.41 | 2.0295 | 2.0295 | 2.0295 | 1.0000 | 1.0000 |
PSZ-AC_7:7 | 1.07 | 1.07 | 0.21 | 0.21 | 1.0675 | 1.0674 | 1.0675 | 1.0000 | 1.0000 |
PSZ-AC_8:8 | 1.06 | 1.06 | 0.21 | 0.21 | 1.0633 | 1.0633 | 1.0633 | 1.0000 | 1.0000 |
PSZ-AC_9:9 | 1.07 | 1.07 | 0.21 | 0.21 | 1.0682 | 1.0682 | 1.0682 | 1.0000 | 1.0000 |
PSZ-AC_10:10 | 1.25 | 1.25 | 0.21 | 0.21 | 1.2510 | 1.2510 | 1.2510 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 56721.740 | 39766.477 | 2.284180 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:10:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:40:00 | 28360.87 | 18743.73 | 1.522787 | 26.77 | 19.81 | 0.01161724 | 12.80 | 12.09 | 0.00850000 | 35.12 | 0.01715799 | 25.81 | 27.0214 | 23.88 | 0.01039739 | 56.1738 | 25870.25 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_1:1 | 52685.936 | 52685.936 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 52685.94 | 52685.94 | 2.284185 | 20.93 | 18.50 | 0.01234207 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 18.0143 | 21.11 | 0.01180238 | 75.2901 | 1061.98 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 28868.900 | 20239.408 | 1.162550 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:50:00 | 14434.45 | 9503.85 | 0.775033 | 26.78 | 19.84 | 0.01165328 | 12.80 | 12.09 | 0.00850000 | 35.20 | 0.01715815 | 25.83 | 26.5459 | 23.88 | 0.01046932 | 56.5564 | 13185.73 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_2:2 | 26810.423 | 26810.423 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 26810.42 | 26810.42 | 1.162551 | 20.93 | 18.58 | 0.01245131 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 17.6972 | 21.11 | 0.01194665 | 76.1934 | 481.63 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_3:3 | 28904.790 | 20264.570 | 1.164000 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:40:00 | 14452.40 | 9517.19 | 0.776000 | 26.78 | 19.84 | 0.01165149 | 12.80 | 12.09 | 0.00850000 | 35.20 | 0.01715815 | 25.83 | 26.5128 | 23.88 | 0.01046823 | 56.5505 | 13195.65 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_3:3 | 26843.179 | 26843.179 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 09:30:00 | 26843.18 | 26843.18 | 1.163996 | 20.93 | 19.23 | 0.01328498 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 17.6753 | 20.50 | 0.01296007 | 85.7055 | 0.00 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_4:4 | 28984.330 | 20320.334 | 1.167200 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:30:00 | 14492.17 | 9549.03 | 0.778133 | 26.77 | 19.83 | 0.01164496 | 12.80 | 12.09 | 0.00850000 | 35.20 | 0.01715815 | 25.83 | 26.4401 | 23.88 | 0.01046405 | 56.5283 | 13230.23 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_4:4 | 26916.387 | 26916.387 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:10:00 | 26916.39 | 26916.39 | 1.167199 | 20.93 | 19.21 | 0.01325941 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 17.6268 | 20.47 | 0.01293011 | 85.6500 | 0.00 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_5:5 | 28742.450 | 20150.757 | 1.157460 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:30:00 | 14371.23 | 9451.43 | 0.771640 | 26.79 | 19.85 | 0.01166587 | 12.80 | 12.09 | 0.00850000 | 35.20 | 0.01715815 | 25.83 | 26.6626 | 23.88 | 0.01047746 | 56.5995 | 13120.30 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_5:5 | 26693.749 | 26693.749 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 26693.75 | 26693.75 | 1.157459 | 20.93 | 19.10 | 0.01311544 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 17.7751 | 20.37 | 0.01275164 | 84.9905 | 0.00 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_6:6 | 50397.450 | 35332.644 | 2.029510 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:30:00 | 25198.72 | 16289.72 | 1.353007 | 27.04 | 20.09 | 0.01188110 | 12.80 | 12.09 | 0.00850000 | 35.20 | 0.01715815 | 25.83 | 30.4122 | 23.88 | 0.01053764 | 56.9179 | 23004.04 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_6:6 | 46867.289 | 46867.289 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 09:40:00 | 46867.29 | 46867.29 | 2.029505 | 20.91 | 19.11 | 0.01314177 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 20.2748 | 20.34 | 0.01272049 | 84.9450 | 0.00 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_7:7 | 26507.990 | 18584.222 | 1.067480 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:30:00 | 13254.00 | 8557.54 | 0.711653 | 26.96 | 20.06 | 0.01187476 | 12.80 | 12.09 | 0.00850000 | 35.20 | 0.01715815 | 25.83 | 28.9101 | 23.88 | 0.01061170 | 57.3124 | 12096.87 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_7:7 | 24637.144 | 24637.144 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 24637.14 | 24637.14 | 1.067477 | 20.92 | 19.17 | 0.01321398 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 19.2734 | 20.43 | 0.01283573 | 85.2228 | 0.00 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_8:8 | 26404.070 | 18511.365 | 1.063290 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:30:00 | 13202.03 | 8516.36 | 0.708860 | 26.97 | 20.07 | 0.01188518 | 12.80 | 12.09 | 0.00850000 | 35.20 | 0.01715815 | 25.83 | 29.0240 | 23.88 | 0.01061841 | 57.3480 | 12049.11 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_8:8 | 24541.465 | 24541.465 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 10:50:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 10:50:00 | 24541.47 | 24541.47 | 1.063292 | 20.92 | 18.98 | 0.01297495 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 19.3493 | 21.11 | 0.01253751 | 79.8846 | 730.81 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_9:9 | 26524.940 | 18596.105 | 1.068160 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:20:00 | 13262.47 | 8563.22 | 0.712107 | 26.96 | 20.06 | 0.01187448 | 12.80 | 12.09 | 0.00850000 | 35.20 | 0.01715815 | 25.83 | 28.8917 | 23.88 | 0.01061154 | 57.3115 | 12098.37 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_9:9 | 24653.674 | 24653.674 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 24653.67 | 24653.67 | 1.068159 | 20.92 | 19.07 | 0.01308417 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 19.2611 | 20.34 | 0.01267524 | 84.6491 | 0.00 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_10:10 | 31064.880 | 21778.966 | 1.250980 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:00:00 | 15532.44 | 10298.45 | 0.833987 | 26.57 | 19.70 | 0.01154680 | 12.80 | 12.09 | 0.00850000 | 34.78 | 0.01715734 | 25.72 | 24.6694 | 23.88 | 0.01044246 | 56.4142 | 14194.04 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_10:10 | 29331.793 | 29331.793 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 10:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 10:00:00 | 29331.79 | 29331.79 | 1.250983 | 20.61 | 19.09 | 0.01324053 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 16.4462 | 21.11 | 0.01293391 | 82.3567 | 1283.45 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:37:06
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 56721.740 | 39766.477 | 2.284180 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1026.4359 | 1004.8586 | 1.2036 | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.284185 | 2.74923304 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:10:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:10:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:40:00 | Sensible | 28360.87 | 18743.73 | 1.0000 | 1.83281839 | 1.522787 | 26.77 | 19.81 | 0.01161724 | 56536.5 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28360.87 | 35.12 | 0.01715799 | 25.81 | 0.41147883 | 27.0214 | 23.88 | 0.01039739 | 23.88 | 0.01039739 | 56.1738 | 25870.25 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 52685.936 | 52685.936 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.284185 | 2.74923304 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 52685.94 | 52685.94 | 1.0000 | 2.74923304 | 2.284185 | 20.93 | 18.50 | 0.01234207 | 52377.0 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 52685.94 | 20.10 | 0.01479830 | 20.10 | 0.41147883 | 18.0143 | 21.11 | 0.01180238 | 21.11 | 0.01180238 | 75.2901 | 1061.98 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 28868.900 | 20239.408 | 1.162550 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1026.5029 | 1004.8586 | 1.2036 | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.162551 | 1.39923999 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:50:00 | Sensible | 14434.45 | 9503.85 | 1.0000 | 0.93282623 | 0.775033 | 26.78 | 19.84 | 0.01165328 | 56635.0 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 14434.45 | 35.20 | 0.01715815 | 25.83 | 0.20573941 | 26.5459 | 23.88 | 0.01046932 | 23.88 | 0.01046932 | 56.5564 | 13185.73 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 26810.423 | 26810.423 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.162551 | 1.39923999 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 26810.42 | 26810.42 | 1.0000 | 1.39923999 | 1.162551 | 20.93 | 18.58 | 0.01245131 | 52657.7 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 26810.42 | 20.10 | 0.01479830 | 20.10 | 0.20573941 | 17.6972 | 21.11 | 0.01194665 | 21.11 | 0.01194665 | 76.1934 | 481.63 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 28904.790 | 20264.570 | 1.164000 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1026.4995 | 1004.8586 | 1.2036 | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.163996 | 1.40097963 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:40:00 | Sensible | 14452.40 | 9517.19 | 1.0000 | 0.93398971 | 0.776000 | 26.78 | 19.84 | 0.01165149 | 56628.9 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 14452.40 | 35.20 | 0.01715815 | 25.83 | 0.20573941 | 26.5128 | 23.88 | 0.01046823 | 23.88 | 0.01046823 | 56.5505 | 13195.65 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 26843.179 | 26843.179 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.163996 | 1.40097963 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 09:30:00 | Sensible | 26843.18 | 26843.18 | 1.0000 | 1.40097963 | 1.163996 | 20.93 | 19.23 | 0.01328498 | 54775.5 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 26843.18 | 20.10 | 0.01479830 | 20.10 | 0.20573941 | 17.6753 | 21.11 | 0.01296007 | 20.50 | 0.01296007 | 85.7055 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 28984.330 | 20320.334 | 1.167200 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1026.4874 | 1004.8586 | 1.2036 | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.167199 | 1.40483501 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:30:00 | Sensible | 14492.17 | 9549.03 | 1.0000 | 0.93655738 | 0.778133 | 26.77 | 19.83 | 0.01164496 | 56606.9 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 14492.17 | 35.20 | 0.01715815 | 25.83 | 0.20573941 | 26.4401 | 23.88 | 0.01046405 | 23.88 | 0.01046405 | 56.5283 | 13230.23 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 26916.387 | 26916.387 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.167199 | 1.40483501 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:10:00 | Sensible | 26916.39 | 26916.39 | 1.0000 | 1.40483501 | 1.167199 | 20.93 | 19.21 | 0.01325941 | 54711.1 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 26916.39 | 20.10 | 0.01479830 | 20.10 | 0.20573941 | 17.6268 | 21.11 | 0.01293011 | 20.47 | 0.01293011 | 85.6500 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 28742.450 | 20150.757 | 1.157460 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1026.5263 | 1004.8586 | 1.2036 | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.157459 | 1.39311138 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:30:00 | Sensible | 14371.23 | 9451.43 | 1.0000 | 0.92874203 | 0.771640 | 26.79 | 19.85 | 0.01166587 | 56677.4 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 14371.23 | 35.20 | 0.01715815 | 25.83 | 0.20573941 | 26.6626 | 23.88 | 0.01047746 | 23.88 | 0.01047746 | 56.5995 | 13120.30 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 26693.749 | 26693.749 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.157459 | 1.39311138 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 26693.75 | 26693.75 | 1.0000 | 1.39311138 | 1.157459 | 20.93 | 19.10 | 0.01311544 | 54344.0 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 26693.75 | 20.10 | 0.01479830 | 20.10 | 0.20573941 | 17.7751 | 21.11 | 0.01275164 | 20.37 | 0.01275164 | 84.9905 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 50397.450 | 35332.644 | 2.029510 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1026.9264 | 1004.8586 | 1.2036 | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.029505 | 2.44270237 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:30:00 | Sensible | 25198.72 | 16289.72 | 1.0000 | 1.62847203 | 1.353007 | 27.04 | 20.09 | 0.01188110 | 57486.5 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 25198.72 | 35.20 | 0.01715815 | 25.83 | 0.41147883 | 30.4122 | 23.88 | 0.01053764 | 23.88 | 0.01053764 | 56.9179 | 23004.04 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 46867.289 | 46867.289 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.029505 | 2.44270237 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 09:40:00 | Sensible | 46867.29 | 46867.29 | 1.0000 | 2.44270237 | 2.029505 | 20.91 | 19.11 | 0.01314177 | 54384.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 46867.29 | 20.10 | 0.01479830 | 20.10 | 0.41147883 | 20.2748 | 21.11 | 0.01272049 | 20.34 | 0.01272049 | 84.9450 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 26507.990 | 18584.222 | 1.067480 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1026.9146 | 1004.8586 | 1.2036 | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.067477 | 1.28480957 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:30:00 | Sensible | 13254.00 | 8557.54 | 1.0000 | 0.85654238 | 0.711653 | 26.96 | 20.06 | 0.01187476 | 57384.8 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 13254.00 | 35.20 | 0.01715815 | 25.83 | 0.20573941 | 28.9101 | 23.88 | 0.01061170 | 23.88 | 0.01061170 | 57.3124 | 12096.87 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 24637.144 | 24637.144 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.067477 | 1.28480957 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 24637.14 | 24637.14 | 1.0000 | 1.28480957 | 1.067477 | 20.92 | 19.17 | 0.01321398 | 54578.6 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 24637.14 | 20.10 | 0.01479830 | 20.10 | 0.20573941 | 19.2734 | 21.11 | 0.01283573 | 20.43 | 0.01283573 | 85.2228 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 26404.070 | 18511.365 | 1.063290 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1026.9340 | 1004.8586 | 1.2036 | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.063292 | 1.27977279 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:30:00 | Sensible | 13202.03 | 8516.36 | 1.0000 | 0.85318034 | 0.708860 | 26.97 | 20.07 | 0.01188518 | 57420.3 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 13202.03 | 35.20 | 0.01715815 | 25.83 | 0.20573941 | 29.0240 | 23.88 | 0.01061841 | 23.88 | 0.01061841 | 57.3480 | 12049.11 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 24541.465 | 24541.465 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.063292 | 1.27977279 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 10:50:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 10:50:00 | Sensible | 24541.47 | 24541.47 | 1.0000 | 1.27977279 | 1.063292 | 20.92 | 18.98 | 0.01297495 | 53971.0 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 24541.47 | 20.10 | 0.01479830 | 20.10 | 0.20573941 | 19.3493 | 21.11 | 0.01253751 | 21.11 | 0.01253751 | 79.8846 | 730.81 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 26524.940 | 18596.105 | 1.068160 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1026.9141 | 1004.8586 | 1.2036 | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.068159 | 1.28563135 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:20:00 | Sensible | 13262.47 | 8563.22 | 1.0000 | 0.85708801 | 0.712107 | 26.96 | 20.06 | 0.01187448 | 57383.9 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 13262.47 | 35.20 | 0.01715815 | 25.83 | 0.20573941 | 28.8917 | 23.88 | 0.01061154 | 23.88 | 0.01061154 | 57.3115 | 12098.37 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 24653.674 | 24653.674 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.068159 | 1.28563135 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 24653.67 | 24653.67 | 1.0000 | 1.28563135 | 1.068159 | 20.92 | 19.07 | 0.01308417 | 54249.1 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 24653.67 | 20.10 | 0.01479830 | 20.10 | 0.20573941 | 19.2611 | 21.11 | 0.01267524 | 20.34 | 0.01267524 | 84.6491 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 31064.880 | 21778.966 | 1.250980 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1026.3049 | 1004.8586 | 1.2036 | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.250983 | 1.50567634 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:00:00 | Sensible | 15532.44 | 10298.45 | 1.0000 | 1.00378217 | 0.833987 | 26.57 | 19.70 | 0.01154680 | 56148.0 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 15532.44 | 34.78 | 0.01715734 | 25.72 | 0.20573941 | 24.6694 | 23.88 | 0.01044246 | 23.88 | 0.01044246 | 56.4142 | 14194.04 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 29331.793 | 29331.793 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.250983 | 1.50567634 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 10:00:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 10:00:00 | Sensible | 29331.79 | 29331.79 | 1.0000 | 1.50567634 | 1.250983 | 20.61 | 19.09 | 0.01324053 | 54334.3 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 29331.79 | 20.10 | 0.01479830 | 20.10 | 0.20573941 | 16.4462 | 20.71 | 0.01293391 | 21.11 | 0.01293391 | 82.3567 | 1283.45 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:06
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
LGSTORE1 | 5840.00 | 3015.17 | 3015.17 |
SMSTORE1 | 5832.33 | 2391.83 | 2391.83 |
SMSTORE2 | 4395.00 | 2739.83 | 2739.83 |
SMSTORE3 | 4395.00 | 2720.33 | 2720.33 |
SMSTORE4 | 4395.00 | 2793.83 | 2793.83 |
LGSTORE2 | 4030.00 | 2873.50 | 2873.50 |
SMSTORE5 | 4030.00 | 2899.67 | 2899.67 |
SMSTORE6 | 4030.00 | 2917.50 | 2917.50 |
SMSTORE7 | 4030.00 | 2895.17 | 2895.17 |
SMSTORE8 | 4030.00 | 2252.83 | 2252.83 |
Facility | 5943.00 | 3892.00 | 3892.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
LGSTORE1 | 0.00 | 1.50 | 0.00 | 1.00 |
SMSTORE1 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 0.00 | 5.50 | 0.00 | 0.00 |
SMSTORE3 | 0.00 | 6.50 | 0.00 | 0.00 |
SMSTORE4 | 0.00 | 4.50 | 0.00 | 0.00 |
LGSTORE2 | 0.00 | 7.00 | 0.00 | 0.00 |
SMSTORE5 | 0.00 | 5.17 | 0.00 | 0.00 |
SMSTORE6 | 0.00 | 5.00 | 0.00 | 0.00 |
SMSTORE7 | 0.00 | 4.50 | 0.00 | 0.00 |
SMSTORE8 | 0.00 | 9.50 | 0.00 | 0.00 |
Facility | 0.00 | 16.83 | 0.00 | 1.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:06
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
LGSTORE1 | 16.92 | 56.25 | 1805.20 | 0.850 | 0.335 | 0.000 | 0.000 |
SMSTORE1 | 8.46 | 28.12 | 902.60 | 0.710 | 0.375 | 0.000 | 0.000 |
SMSTORE2 | 7.09 | 28.12 | 902.60 | 0.851 | 0.492 | 0.000 | 0.000 |
SMSTORE3 | 7.09 | 28.12 | 902.60 | 0.851 | 0.492 | 0.000 | 0.000 |
SMSTORE4 | 7.09 | 28.12 | 902.60 | 0.851 | 0.492 | 0.000 | 0.000 |
LGSTORE2 | 24.80 | 56.25 | 1805.20 | 0.852 | 0.460 | 0.000 | 0.000 |
SMSTORE5 | 12.40 | 28.12 | 902.60 | 0.852 | 0.525 | 0.000 | 0.000 |
SMSTORE6 | 12.40 | 28.12 | 902.60 | 0.852 | 0.525 | 0.000 | 0.000 |
SMSTORE7 | 12.40 | 28.12 | 902.60 | 0.852 | 0.525 | 0.000 | 0.000 |
SMSTORE8 | 12.40 | 28.12 | 902.60 | 0.851 | 0.538 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
LGSTORE1 | 16.92 | 56.25 | 1805.20 | 0.832 | 0.000 | 0.000 | 0.000 |
SMSTORE1 | 8.46 | 28.12 | 902.60 | 0.121 | 0.000 | 0.000 | 0.000 |
SMSTORE2 | 7.09 | 28.12 | 902.60 | 0.831 | 0.000 | 0.000 | 0.000 |
SMSTORE3 | 7.09 | 28.12 | 902.60 | 0.831 | 0.000 | 0.000 | 0.000 |
SMSTORE4 | 7.09 | 28.12 | 902.60 | 0.831 | 0.000 | 0.000 | 0.000 |
LGSTORE2 | 24.80 | 56.25 | 1805.20 | 0.833 | 0.000 | 0.000 | 0.000 |
SMSTORE5 | 12.40 | 28.12 | 902.60 | 0.833 | 0.000 | 0.000 | 0.000 |
SMSTORE6 | 12.40 | 28.12 | 902.60 | 0.833 | 0.000 | 0.000 | 0.000 |
SMSTORE7 | 12.40 | 28.12 | 902.60 | 0.833 | 0.000 | 0.000 | 0.000 |
SMSTORE8 | 12.40 | 28.12 | 902.60 | 0.833 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:37:06
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
LGSTORE1 | PSZ-AC_1:1 | 16.92 | 56.25 | 1805.20 | 348.39 | 0.4115 | 0.411 |
SMSTORE1 | PSZ-AC_2:2 | 8.46 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE2 | PSZ-AC_3:3 | 7.09 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE3 | PSZ-AC_4:4 | 7.09 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE4 | PSZ-AC_5:5 | 7.09 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
LGSTORE2 | PSZ-AC_6:6 | 24.80 | 56.25 | 1805.20 | 348.39 | 0.4115 | 0.411 |
SMSTORE5 | PSZ-AC_7:7 | 12.40 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE6 | PSZ-AC_8:8 | 12.40 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE7 | PSZ-AC_9:9 | 12.40 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE8 | PSZ-AC_10:10 | 12.40 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
Total Facility | 121.06 | 337.50 | 10831.20 | 2090.32 | 2.4689 | 2.469 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
LGSTORE1 | 8803677.56 | 0.00 | 8803677.56 | 3601967.37 | 12405644.94 | 12976396.34 | 2817.00 | 5943.00 | 0.00 | 103.00 |
SMSTORE1 | 3687552.20 | 0.00 | 3687552.20 | 1965043.96 | 5652596.15 | 6488198.17 | 4303.00 | 4457.00 | 0.00 | 103.00 |
SMSTORE2 | 3525627.36 | 0.00 | 3525627.36 | 1989485.12 | 5515112.49 | 6488198.17 | 4000.00 | 4760.00 | 0.00 | 365.00 |
SMSTORE3 | 3525626.81 | 0.00 | 3525626.81 | 1989485.12 | 5515111.93 | 6488198.17 | 4000.00 | 4760.00 | 0.00 | 365.00 |
SMSTORE4 | 3525629.16 | 0.00 | 3525629.16 | 1989485.12 | 5515114.28 | 6488198.17 | 4000.00 | 4760.00 | 0.00 | 365.00 |
LGSTORE2 | 6510618.54 | 0.00 | 6510618.54 | 3520231.44 | 10030849.98 | 12976396.34 | 4365.00 | 4395.00 | 0.00 | 365.00 |
SMSTORE5 | 3255288.77 | 0.00 | 3255288.77 | 1994519.00 | 5249807.77 | 6488198.17 | 4365.00 | 4395.00 | 0.00 | 365.00 |
SMSTORE6 | 3255290.41 | 0.00 | 3255290.41 | 1994519.00 | 5249809.41 | 6488198.17 | 4365.00 | 4395.00 | 0.00 | 365.00 |
SMSTORE7 | 3255289.24 | 0.00 | 3255289.24 | 1994519.00 | 5249808.23 | 6488198.17 | 4365.00 | 4395.00 | 0.00 | 365.00 |
SMSTORE8 | 3255258.88 | 0.00 | 3255258.88 | 2179417.57 | 5434676.45 | 6488198.17 | 4365.00 | 4395.00 | 0.00 | 365.00 |
Total Facility | 42599858.93 | 0.00 | 42599858.93 | 23218672.70 | 65818531.63 | 77858378.04 | 4365.00 | 6246.00 | 0.00 | 730.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
LGSTORE1 | 0.4115 | 0.0000 | 0.4115 | 0.1619 | 0.5734 | 0.4115 | 0.00 | 5840.00 | 0.00 |
SMSTORE1 | 0.1718 | 0.0000 | 0.1718 | 0.0905 | 0.2623 | 0.2057 | 1486.00 | 4354.00 | 0.00 |
SMSTORE2 | 0.2057 | 0.0000 | 0.2057 | 0.1188 | 0.3245 | 0.2057 | 0.00 | 4395.00 | 0.00 |
SMSTORE3 | 0.2057 | 0.0000 | 0.2057 | 0.1188 | 0.3245 | 0.2057 | 0.00 | 4395.00 | 0.00 |
SMSTORE4 | 0.2057 | 0.0000 | 0.2057 | 0.1188 | 0.3245 | 0.2057 | 0.00 | 4395.00 | 0.00 |
LGSTORE2 | 0.4115 | 0.0000 | 0.4115 | 0.2221 | 0.6336 | 0.4115 | 0.00 | 4030.00 | 0.00 |
SMSTORE5 | 0.2057 | 0.0000 | 0.2057 | 0.1267 | 0.3324 | 0.2057 | 0.00 | 4030.00 | 0.00 |
SMSTORE6 | 0.2057 | 0.0000 | 0.2057 | 0.1267 | 0.3324 | 0.2057 | 0.00 | 4030.00 | 0.00 |
SMSTORE7 | 0.2057 | 0.0000 | 0.2057 | 0.1267 | 0.3324 | 0.2057 | 0.00 | 4030.00 | 0.00 |
SMSTORE8 | 0.2057 | 0.0000 | 0.2057 | 0.1299 | 0.3357 | 0.2057 | 0.00 | 4030.00 | 0.00 |
Total Facility | 2.4350 | 0.0000 | 2.4350 | 1.3408 | 3.7758 | 2.4689 | 1486.00 | 5943.00 | 0.00 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-AC_1:1 | 12753120.48 | 0.00 | 12753120.48 | 12976396.34 | 2817.00 | 0.00 | 5943.00 | 103.00 |
PSZ-AC_2:2 | 5341829.35 | 0.00 | 5341829.35 | 6488198.17 | 4301.42 | 1.17 | 4457.42 | 103.00 |
PSZ-AC_3:3 | 5107256.73 | 0.00 | 5107256.73 | 6488198.17 | 4000.00 | 0.00 | 4760.00 | 365.00 |
PSZ-AC_4:4 | 5107256.73 | 0.00 | 5107256.73 | 6488198.17 | 4000.00 | 0.00 | 4760.00 | 365.00 |
PSZ-AC_5:5 | 5107256.73 | 0.00 | 5107256.73 | 6488198.17 | 4000.00 | 0.00 | 4760.00 | 365.00 |
PSZ-AC_6:6 | 9431257.70 | 0.00 | 9431257.70 | 12976396.34 | 4365.00 | 0.00 | 4395.00 | 365.00 |
PSZ-AC_7:7 | 4715628.85 | 0.00 | 4715628.85 | 6488198.17 | 4365.00 | 0.00 | 4395.00 | 365.00 |
PSZ-AC_8:8 | 4715628.85 | 0.00 | 4715628.85 | 6488198.17 | 4365.00 | 0.00 | 4395.00 | 365.00 |
PSZ-AC_9:9 | 4715628.85 | 0.00 | 4715628.85 | 6488198.17 | 4365.00 | 0.00 | 4395.00 | 365.00 |
PSZ-AC_10:10 | 4715628.85 | 0.00 | 4715628.85 | 6488198.17 | 4365.00 | 0.00 | 4395.00 | 365.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-AC_1:1 | 0.5961 | 0.0000 | 0.5961 | 0.4115 | 0.00 | 0.00 | 5840.00 |
PSZ-AC_2:2 | 0.2488 | 0.0000 | 0.2488 | 0.2057 | 1484.42 | 1.17 | 4354.42 |
PSZ-AC_3:3 | 0.2980 | 0.0000 | 0.2980 | 0.2057 | 0.00 | 0.00 | 4395.00 |
PSZ-AC_4:4 | 0.2980 | 0.0000 | 0.2980 | 0.2057 | 0.00 | 0.00 | 4395.00 |
PSZ-AC_5:5 | 0.2980 | 0.0000 | 0.2980 | 0.2057 | 0.00 | 0.00 | 4395.00 |
PSZ-AC_6:6 | 0.5961 | 0.0000 | 0.5961 | 0.4115 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_7:7 | 0.2980 | 0.0000 | 0.2980 | 0.2057 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_8:8 | 0.2980 | 0.0000 | 0.2980 | 0.2057 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_9:9 | 0.2980 | 0.0000 | 0.2980 | 0.2057 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_10:10 | 0.2980 | 0.0000 | 0.2980 | 0.2057 | 0.00 | 0.00 | 4030.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-AC_1:1 | 0.00 | 5943.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_2:2 | 0.00 | 5943.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_3:3 | 0.00 | 4760.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_4:4 | 0.00 | 4760.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_5:5 | 0.00 | 4760.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_6:6 | 0.00 | 4395.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_7:7 | 0.00 | 4395.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_8:8 | 0.00 | 4395.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_9:9 | 0.00 | 4395.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_10:10 | 0.00 | 4395.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-AC_1:1 | 0.0000 | 0.5961 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_2:2 | 0.0000 | 0.2488 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_3:3 | 0.0000 | 0.2981 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_4:4 | 0.0000 | 0.2981 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_5:5 | 0.0000 | 0.2981 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_6:6 | 0.0000 | 0.5962 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_7:7 | 0.0000 | 0.2981 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_8:8 | 0.0000 | 0.2981 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_9:9 | 0.0000 | 0.2981 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_10:10 | 0.0000 | 0.2981 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:06
Surfaces by ClassTotal | Outdoors | |
Wall | 40 | 22 |
Floor | 10 | 10 |
Roof | 10 | 10 |
Internal Mass | 10 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 36 | 36 |
Door | 12 | 12 |
Glass Door | 12 | 12 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 10 |
Conditioned Zones | 10 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 830 |
Defaulted Fields | 823 |
Fields with Defaults | 2682 |
Autosized Fields | 184 |
Autosizable Fields | 458 |
Autocalculated Fields | 128 |
Autocalculatable Fields | 256 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:37:06
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1415.97 | 2102.83 | 01-JAN-06:20 | 126926.96 | 16-JUN-12:40 |
Electricity:Building | 494.83 | 891.83 | 01-JAN-00:20 | 31518.67 | 01-JAN-11:10 |
Electricity:Zone:LGSTORE1 | 113.36 | 148.64 | 01-JAN-00:20 | 5964.88 | 01-JAN-10:10 |
Electricity:SpaceType:GENERAL | 494.83 | 891.83 | 01-JAN-00:20 | 31518.67 | 01-JAN-11:10 |
InteriorLights:Electricity | 366.68 | 450.00 | 01-JAN-00:20 | 23459.17 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:LGSTORE1 | 87.12 | 75.00 | 01-JAN-00:20 | 4621.63 | 01-JAN-10:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 366.68 | 450.00 | 01-JAN-00:20 | 23459.17 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity | 366.68 | 450.00 | 01-JAN-00:20 | 23459.17 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:LGSTORE1 | 87.12 | 75.00 | 01-JAN-00:20 | 4621.63 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 366.68 | 450.00 | 01-JAN-00:20 | 23459.17 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE1 | 66.33 | 74.32 | 01-JAN-00:20 | 3498.69 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE1 | 53.20 | 37.50 | 01-JAN-00:20 | 2827.07 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE1 | 53.20 | 37.50 | 01-JAN-00:20 | 2827.07 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE2 | 47.99 | 74.32 | 01-JAN-00:10 | 3226.84 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE2 | 37.57 | 37.50 | 01-JAN-00:10 | 2555.22 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE2 | 37.57 | 37.50 | 01-JAN-00:10 | 2555.22 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE3 | 47.99 | 74.32 | 01-JAN-00:10 | 3226.84 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE3 | 37.57 | 37.50 | 01-JAN-00:10 | 2555.22 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE3 | 37.57 | 37.50 | 01-JAN-00:10 | 2555.22 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE4 | 47.99 | 74.32 | 01-JAN-00:10 | 3226.84 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE4 | 37.57 | 37.50 | 01-JAN-00:10 | 2555.22 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE4 | 37.57 | 37.50 | 01-JAN-00:10 | 2555.22 | 01-JAN-10:10 |
Electricity:Zone:LGSTORE2 | 56.34 | 148.64 | 01-JAN-00:10 | 4070.21 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:LGSTORE2 | 37.16 | 75.00 | 01-JAN-00:10 | 2726.96 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:LGSTORE2 | 37.16 | 75.00 | 01-JAN-00:10 | 2726.96 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE5 | 28.71 | 74.32 | 01-JAN-00:10 | 2076.09 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE5 | 19.12 | 37.50 | 01-JAN-00:10 | 1404.46 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE5 | 19.12 | 37.50 | 01-JAN-00:10 | 1404.46 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE6 | 28.71 | 74.32 | 01-JAN-00:10 | 2076.09 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE6 | 19.12 | 37.50 | 01-JAN-00:10 | 1404.46 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE6 | 19.12 | 37.50 | 01-JAN-00:10 | 1404.46 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE7 | 28.71 | 74.32 | 01-JAN-00:10 | 2076.09 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE7 | 19.12 | 37.50 | 01-JAN-00:10 | 1404.46 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE7 | 19.12 | 37.50 | 01-JAN-00:10 | 1404.46 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE8 | 28.71 | 74.32 | 01-JAN-00:10 | 2076.09 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE8 | 19.12 | 37.50 | 01-JAN-00:10 | 1404.46 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE8 | 19.12 | 37.50 | 01-JAN-00:10 | 1404.46 | 01-JAN-11:10 |
InteriorEquipment:Electricity | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:LGSTORE1 | 26.25 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-10:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LGSTORE1 | 26.25 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE1 | 13.12 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE1 | 13.12 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE2 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE2 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE3 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE3 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE4 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE4 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:LGSTORE2 | 19.17 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LGSTORE2 | 19.17 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE5 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE5 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE6 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE6 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE7 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE7 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE8 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE8 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
ElectricityPurchased:Facility | 1415.97 | 2102.83 | 01-JAN-06:20 | 126926.96 | 16-JUN-12:40 |
ElectricityPurchased:Plant | 1415.97 | 2102.83 | 01-JAN-06:20 | 126926.96 | 16-JUN-12:40 |
Cogeneration:ElectricityPurchased | 1415.97 | 2102.83 | 01-JAN-06:20 | 126926.96 | 16-JUN-12:40 |
General:Cogeneration:ElectricityPurchased | 1415.97 | 2102.83 | 01-JAN-06:20 | 126926.96 | 16-JUN-12:40 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1415.97 | 2102.83 | 01-JAN-06:20 | 126926.96 | 16-JUN-12:40 |
ElectricityNet:Plant | 1415.97 | 2102.83 | 01-JAN-06:20 | 126926.96 | 16-JUN-12:40 |
Cogeneration:ElectricityNet | 1415.97 | 2102.83 | 01-JAN-06:20 | 126926.96 | 16-JUN-12:40 |
General:Cogeneration:ElectricityNet | 1415.97 | 2102.83 | 01-JAN-06:20 | 126926.96 | 16-JUN-12:40 |
Electricity:HVAC | 803.43 | 0.00 | 01-JAN-00:10 | 89906.47 | 16-JUN-13:00 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 685.93 | 0.00 | 01-JAN-00:10 | 77657.47 | 16-JUN-13:00 |
General:Cooling:Electricity | 685.93 | 0.00 | 01-JAN-00:10 | 77657.47 | 16-JUN-13:00 |
Fans:Electricity | 117.50 | 0.00 | 01-JAN-00:10 | 12249.01 | 16-JUN-13:00 |
General:Fans:Electricity | 117.50 | 0.00 | 01-JAN-00:10 | 12249.01 | 16-JUN-13:00 |
ExteriorLights:Electricity | 60.18 | 0.00 | 01-JAN-06:20 | 5507.06 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 60.18 | 0.00 | 01-JAN-06:20 | 5507.06 | 01-JAN-06:10 |
Electricity:Plant | 57.53 | 1211.00 | 16-JAN-09:10 | 11748.27 | 02-JAN-15:10 |
WaterSystems:Electricity | 57.53 | 1211.00 | 16-JAN-09:10 | 11748.27 | 02-JAN-15:10 |
Water Heater:WaterSystems:Electricity | 57.53 | 1211.00 | 16-JAN-09:10 | 11748.27 | 02-JAN-15:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
NaturalGas:HVAC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:NaturalGas | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:NaturalGas | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water:Plant | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
WaterSystems:Water | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water Heater:WaterSystems:Water | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
MainsWater:Facility | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
MainsWater:Plant | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
WaterSystems:MainsWater | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water Heater:WaterSystems:MainsWater | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 4055.90 | 0.00 | 01-JAN-00:10 | 423905.89 | 16-JUN-13:00 |
EnergyTransfer:Building | 1177.96 | 0.00 | 01-JAN-00:10 | 123348.40 | 06-MAY-13:00 |
EnergyTransfer:Zone:LGSTORE1 | 240.55 | 0.00 | 01-JAN-00:10 | 20664.19 | 06-MAY-13:00 |
Heating:EnergyTransfer | 6.61 | 0.00 | 01-JAN-00:10 | 21379.49 | 29-MAY-16:10 |
Heating:EnergyTransfer:Zone:LGSTORE1 | 0.35 | 0.00 | 01-JAN-00:10 | 2121.74 | 05-JAN-08:20 |
General:Heating:EnergyTransfer | 6.61 | 0.00 | 01-JAN-00:10 | 21379.49 | 29-MAY-16:10 |
General:Heating:EnergyTransfer:Zone:LGSTORE1 | 0.35 | 0.00 | 01-JAN-00:10 | 2121.74 | 05-JAN-08:20 |
Cooling:EnergyTransfer | 1171.35 | 0.00 | 01-JAN-00:10 | 123348.40 | 06-MAY-13:00 |
Cooling:EnergyTransfer:Zone:LGSTORE1 | 240.20 | 0.00 | 01-JAN-00:10 | 20664.19 | 06-MAY-13:00 |
General:Cooling:EnergyTransfer | 1171.35 | 0.00 | 01-JAN-00:10 | 123348.40 | 06-MAY-13:00 |
General:Cooling:EnergyTransfer:Zone:LGSTORE1 | 240.20 | 0.00 | 01-JAN-00:10 | 20664.19 | 06-MAY-13:00 |
EnergyTransfer:Zone:SMSTORE1 | 123.13 | 0.00 | 01-JAN-00:10 | 10582.80 | 06-MAY-13:00 |
Heating:EnergyTransfer:Zone:SMSTORE1 | 0.16 | 0.00 | 01-JAN-00:10 | 809.90 | 08-JUL-07:20 |
General:Heating:EnergyTransfer:Zone:SMSTORE1 | 0.16 | 0.00 | 01-JAN-00:10 | 809.90 | 08-JUL-07:20 |
Cooling:EnergyTransfer:Zone:SMSTORE1 | 122.97 | 0.00 | 01-JAN-00:10 | 10582.80 | 06-MAY-13:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE1 | 122.97 | 0.00 | 01-JAN-00:10 | 10582.80 | 06-MAY-13:00 |
EnergyTransfer:Zone:SMSTORE2 | 96.89 | 0.00 | 01-JAN-00:10 | 10627.51 | 06-MAY-13:00 |
Heating:EnergyTransfer:Zone:SMSTORE2 | 1.02 | 0.00 | 01-JAN-00:10 | 2368.83 | 29-MAY-16:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE2 | 1.02 | 0.00 | 01-JAN-00:10 | 2368.83 | 29-MAY-16:10 |
Cooling:EnergyTransfer:Zone:SMSTORE2 | 95.87 | 0.00 | 01-JAN-00:10 | 10627.51 | 06-MAY-13:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE2 | 95.87 | 0.00 | 01-JAN-00:10 | 10627.51 | 06-MAY-13:00 |
EnergyTransfer:Zone:SMSTORE3 | 97.31 | 0.00 | 01-JAN-00:10 | 10662.51 | 06-MAY-13:00 |
Heating:EnergyTransfer:Zone:SMSTORE3 | 1.02 | 0.00 | 01-JAN-00:10 | 2367.44 | 29-MAY-16:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE3 | 1.02 | 0.00 | 01-JAN-00:10 | 2367.44 | 29-MAY-16:10 |
Cooling:EnergyTransfer:Zone:SMSTORE3 | 96.30 | 0.00 | 01-JAN-00:10 | 10662.51 | 06-MAY-13:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE3 | 96.30 | 0.00 | 01-JAN-00:10 | 10662.51 | 06-MAY-13:00 |
EnergyTransfer:Zone:SMSTORE4 | 95.44 | 0.00 | 01-JAN-00:10 | 10535.59 | 06-MAY-13:00 |
Heating:EnergyTransfer:Zone:SMSTORE4 | 1.04 | 0.00 | 01-JAN-00:10 | 2373.14 | 29-MAY-16:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE4 | 1.04 | 0.00 | 01-JAN-00:10 | 2373.14 | 29-MAY-16:10 |
Cooling:EnergyTransfer:Zone:SMSTORE4 | 94.40 | 0.00 | 01-JAN-00:10 | 10535.59 | 06-MAY-13:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE4 | 94.40 | 0.00 | 01-JAN-00:10 | 10535.59 | 06-MAY-13:00 |
EnergyTransfer:Zone:LGSTORE2 | 163.64 | 0.00 | 01-JAN-00:10 | 18636.17 | 06-MAY-13:10 |
Heating:EnergyTransfer:Zone:LGSTORE2 | 1.03 | 0.00 | 01-JAN-00:10 | 4782.07 | 29-MAY-16:10 |
General:Heating:EnergyTransfer:Zone:LGSTORE2 | 1.03 | 0.00 | 01-JAN-00:10 | 4782.07 | 29-MAY-16:10 |
Cooling:EnergyTransfer:Zone:LGSTORE2 | 162.61 | 0.00 | 01-JAN-00:10 | 18636.17 | 06-MAY-13:10 |
General:Cooling:EnergyTransfer:Zone:LGSTORE2 | 162.61 | 0.00 | 01-JAN-00:10 | 18636.17 | 06-MAY-13:10 |
EnergyTransfer:Zone:SMSTORE5 | 85.59 | 0.00 | 01-JAN-00:10 | 9888.79 | 06-MAY-13:10 |
Heating:EnergyTransfer:Zone:SMSTORE5 | 0.51 | 0.00 | 01-JAN-00:10 | 2397.03 | 29-MAY-16:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE5 | 0.51 | 0.00 | 01-JAN-00:10 | 2397.03 | 29-MAY-16:10 |
Cooling:EnergyTransfer:Zone:SMSTORE5 | 85.08 | 0.00 | 01-JAN-00:10 | 9888.79 | 06-MAY-13:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE5 | 85.08 | 0.00 | 01-JAN-00:10 | 9888.79 | 06-MAY-13:10 |
EnergyTransfer:Zone:SMSTORE6 | 85.14 | 0.00 | 01-JAN-00:10 | 9857.64 | 06-MAY-13:10 |
Heating:EnergyTransfer:Zone:SMSTORE6 | 0.51 | 0.00 | 01-JAN-00:10 | 2398.27 | 29-MAY-16:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE6 | 0.51 | 0.00 | 01-JAN-00:10 | 2398.27 | 29-MAY-16:10 |
Cooling:EnergyTransfer:Zone:SMSTORE6 | 84.63 | 0.00 | 01-JAN-00:10 | 9857.64 | 06-MAY-13:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE6 | 84.63 | 0.00 | 01-JAN-00:10 | 9857.64 | 06-MAY-13:10 |
EnergyTransfer:Zone:SMSTORE7 | 85.70 | 0.00 | 01-JAN-00:10 | 9969.63 | 06-MAY-13:10 |
Heating:EnergyTransfer:Zone:SMSTORE7 | 0.52 | 0.00 | 01-JAN-00:10 | 2394.03 | 29-MAY-16:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE7 | 0.52 | 0.00 | 01-JAN-00:10 | 2394.03 | 29-MAY-16:10 |
Cooling:EnergyTransfer:Zone:SMSTORE7 | 85.18 | 0.00 | 01-JAN-00:10 | 9969.63 | 06-MAY-13:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE7 | 85.18 | 0.00 | 01-JAN-00:10 | 9969.63 | 06-MAY-13:10 |
EnergyTransfer:Zone:SMSTORE8 | 104.57 | 0.00 | 01-JAN-00:10 | 12117.32 | 06-MAY-12:30 |
Heating:EnergyTransfer:Zone:SMSTORE8 | 0.46 | 0.00 | 01-JAN-00:10 | 2298.68 | 29-MAY-16:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE8 | 0.46 | 0.00 | 01-JAN-00:10 | 2298.68 | 29-MAY-16:10 |
Cooling:EnergyTransfer:Zone:SMSTORE8 | 104.12 | 0.00 | 01-JAN-00:10 | 12117.32 | 06-MAY-12:30 |
General:Cooling:EnergyTransfer:Zone:SMSTORE8 | 104.12 | 0.00 | 01-JAN-00:10 | 12117.32 | 06-MAY-12:30 |
EnergyTransfer:HVAC | 2877.94 | 0.00 | 01-JAN-00:10 | 307433.90 | 16-JUN-13:00 |
HeatingCoils:EnergyTransfer | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
CoolingCoils:EnergyTransfer | 2877.94 | 0.00 | 01-JAN-00:10 | 307433.90 | 16-JUN-13:00 |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:06
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
LGSTORE1 | 0.000 | 0.000 | 0.352 | -240.194 | 0.000 | 0.000 | 23.215 | 87.116 | 26.249 | 15.753 | 0.000 | 28.356 | 60.453 | 0.000 | -1.092 | 0.000 | -0.208 | -0.000 |
SMSTORE1 | 0.000 | 0.000 | 0.159 | -122.964 | 0.000 | 0.000 | 11.607 | 53.201 | 13.125 | 7.953 | 0.000 | 15.891 | 21.627 | 0.000 | -0.533 | 0.000 | -0.066 | -0.002 |
SMSTORE2 | 0.000 | 0.000 | 1.022 | -95.868 | 0.000 | 0.000 | 6.968 | 37.572 | 10.421 | 7.840 | 0.000 | 15.616 | 17.237 | 0.000 | -0.697 | 0.000 | -0.110 | -0.000 |
SMSTORE3 | 0.000 | 0.000 | 1.017 | -96.293 | 0.000 | 0.000 | 6.968 | 37.572 | 10.421 | 7.834 | 0.000 | 15.611 | 17.696 | 0.000 | -0.712 | 0.000 | -0.114 | -0.000 |
SMSTORE4 | 0.000 | 0.000 | 1.037 | -94.397 | 0.000 | 0.000 | 6.969 | 37.572 | 10.421 | 7.846 | 0.000 | 15.619 | 15.726 | 0.000 | -0.687 | 0.000 | -0.105 | -0.000 |
LGSTORE2 | 0.000 | 0.000 | 1.029 | -162.608 | 0.000 | 0.000 | 23.924 | 37.162 | 19.173 | 15.666 | 0.000 | 27.434 | 39.640 | 0.000 | -1.227 | 0.000 | -0.192 | -0.000 |
SMSTORE5 | 0.000 | 0.000 | 0.511 | -85.082 | 0.000 | 0.000 | 11.962 | 19.120 | 9.586 | 7.866 | 0.000 | 15.644 | 21.067 | 0.000 | -0.581 | 0.000 | -0.094 | -0.000 |
SMSTORE6 | 0.000 | 0.000 | 0.512 | -84.626 | 0.000 | 0.000 | 11.962 | 19.120 | 9.586 | 7.871 | 0.000 | 15.646 | 20.598 | 0.000 | -0.576 | 0.000 | -0.093 | -0.000 |
SMSTORE7 | 0.000 | 0.000 | 0.518 | -85.178 | 0.000 | 0.000 | 11.962 | 19.120 | 9.586 | 7.859 | 0.000 | 15.646 | 21.160 | 0.000 | -0.582 | 0.000 | -0.091 | -0.000 |
SMSTORE8 | 0.000 | 0.000 | 0.457 | -104.112 | 0.000 | 0.000 | 11.960 | 19.120 | 9.586 | 7.710 | 0.000 | 16.062 | 40.079 | 0.000 | -0.643 | 0.000 | -0.219 | -0.001 |
Total Facility | 0.000 | 0.000 | 6.613 | -1171.322 | 0.000 | 0.000 | 127.495 | 366.677 | 128.154 | 94.197 | 0.000 | 181.525 | 275.283 | 0.000 | -7.332 | 0.000 | -1.292 | -0.003 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
LGSTORE1 | 21-FEB-08:61 | 0.00 | 0.00 | 0.00 | -38287.12 | 0.00 | 0.00 | 167.08 | 75.00 | 74.62 | 1058.50 | 0.00 | 68.79 | 36843.13 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 21-FEB-08:61 | 0.00 | 0.00 | 0.00 | -21891.26 | 0.00 | 0.00 | 83.06 | 37.50 | 37.31 | 528.46 | 0.00 | 39.65 | 21165.27 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 25-FEB-07:02 | 0.00 | 0.00 | 0.00 | -18881.40 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 158.52 | 0.00 | 0.00 | 18649.23 | 0.00 | -0.00 | 0.00 | -0.67 | 0.00 |
SMSTORE3 | 25-FEB-07:02 | 0.00 | 0.00 | 0.00 | -18970.78 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 157.58 | 0.00 | 0.00 | 18739.56 | 0.00 | -0.00 | 0.00 | -0.68 | 0.00 |
SMSTORE4 | 25-FEB-07:02 | 0.00 | 0.00 | 0.00 | -18682.69 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 159.71 | 0.00 | 0.00 | 18449.30 | 0.00 | -0.00 | 0.00 | -0.65 | 0.00 |
LGSTORE2 | 25-FEB-08:62 | 0.00 | 0.00 | 0.00 | -33341.78 | 0.00 | 0.00 | 0.00 | 75.00 | 73.64 | 862.32 | 0.00 | 119.80 | 32211.02 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 25-FEB-08:62 | 0.00 | 0.00 | 0.00 | -17452.85 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 432.94 | 0.00 | 72.17 | 16873.42 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 25-FEB-08:62 | 0.00 | 0.00 | 0.00 | -17359.59 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 433.49 | 0.00 | 72.88 | 16778.89 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 25-FEB-08:62 | 0.00 | 0.00 | 0.00 | -17389.45 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 433.63 | 0.00 | 75.33 | 16806.17 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 23-FEB-08:62 | 0.00 | 0.00 | 0.00 | -20307.94 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 442.14 | 0.00 | 0.00 | 19858.69 | 0.00 | -0.00 | 0.00 | -67.21 | 0.00 |
Total Facility | 23-FEB-08:62 | 0.00 | 0.00 | 0.00 | -173070.37 | 0.00 | 0.00 | 549.66 | 450.00 | 1452.23 | 5405.84 | 0.00 | 0.00 | 165838.74 | 0.00 | 0.00 | 0.00 | -626.11 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
LGSTORE1 | 06-MAY-07:06 | 0.00 | 0.00 | 4718.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.00 | 73.64 | 493.59 | 0.00 | 571.09 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -5931.32 |
SMSTORE1 | 28-MAY-07:06 | 0.00 | 0.00 | 2797.10 | 0.00 | 0.00 | 0.00 | 81.44 | 37.50 | 37.31 | 285.06 | 0.00 | 324.67 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -3563.08 |
SMSTORE2 | 29-MAY-16:01 | 0.00 | 0.00 | 2825.25 | 0.00 | 0.00 | 0.00 | 98.50 | 1344.85 | 373.13 | 395.19 | 0.00 | 2606.47 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -7643.39 |
SMSTORE3 | 29-MAY-16:01 | 0.00 | 0.00 | 2824.64 | 0.00 | 0.00 | 0.00 | 98.50 | 1344.85 | 373.13 | 394.98 | 0.00 | 2606.23 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -7642.33 |
SMSTORE4 | 29-MAY-16:01 | 0.00 | 0.00 | 2827.04 | 0.00 | 0.00 | 0.00 | 98.50 | 1344.85 | 373.13 | 395.32 | 0.00 | 2607.11 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -7645.94 |
LGSTORE2 | 29-MAY-16:01 | 0.00 | 0.00 | 5657.12 | 0.00 | 0.00 | 0.00 | 433.43 | 1435.23 | 746.25 | 788.05 | 0.00 | 4579.74 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -13639.83 |
SMSTORE5 | 29-MAY-16:01 | 0.00 | 0.00 | 2834.75 | 0.00 | 0.00 | 0.00 | 216.71 | 739.19 | 373.13 | 397.05 | 0.00 | 2611.81 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -7172.63 |
SMSTORE6 | 29-MAY-16:01 | 0.00 | 0.00 | 2835.11 | 0.00 | 0.00 | 0.00 | 216.71 | 739.19 | 373.13 | 397.22 | 0.00 | 2612.05 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -7173.41 |
SMSTORE7 | 29-MAY-16:01 | 0.00 | 0.00 | 2832.98 | 0.00 | 0.00 | 0.00 | 216.71 | 739.19 | 373.13 | 396.36 | 0.00 | 2611.28 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -7169.64 |
SMSTORE8 | 29-MAY-16:01 | 0.00 | 0.00 | 2790.60 | 0.00 | 0.00 | 0.00 | 216.71 | 739.19 | 373.13 | 385.99 | 0.00 | 2610.53 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -7116.14 |
Total Facility | 29-MAY-16:01 | -28698.36 | 28698.36 | 25427.48 | -28698.36 | 0.00 | 0.00 | 5142.03 | 15875.25 | 5373.00 | 4749.25 | 0.00 | 30339.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -58208.22 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:06
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 2.2842 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 2.2842 | 0.1801 | 1.0000 | Not calculated | 0.4115 | 0.1801 | ||
PSZ-AC_2:2 | 1.1626 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.1626 | 0.1770 | 1.0000 | Not calculated | 0.2057 | 0.1770 | ||
PSZ-AC_3:3 | 1.1640 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.1640 | 0.1768 | 1.0000 | Not calculated | 0.2057 | 0.1768 | ||
PSZ-AC_4:4 | 1.1672 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.1672 | 0.1763 | 1.0000 | Not calculated | 0.2057 | 0.1763 | ||
PSZ-AC_5:5 | 1.1575 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.1575 | 0.1778 | 1.0000 | Not calculated | 0.2057 | 0.1778 | ||
PSZ-AC_6:6 | 2.0295 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 2.0295 | 0.2027 | 1.0000 | Not calculated | 0.4115 | 0.2027 | ||
PSZ-AC_7:7 | 1.0674 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0675 | 0.1927 | 1.0000 | Not calculated | 0.2057 | 0.1927 | ||
PSZ-AC_8:8 | 1.0633 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0633 | 0.1935 | 1.0000 | Not calculated | 0.2057 | 0.1935 | ||
PSZ-AC_9:9 | 1.0682 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0682 | 0.1926 | 1.0000 | Not calculated | 0.2057 | 0.1926 | ||
PSZ-AC_10:10 | 1.2510 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.2510 | 0.1645 | 1.0000 | Not calculated | 0.2057 | 0.1645 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 2.2842 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 2.2842 | 1.0000 | 1.0000 | Not calculated | 0.4115 | 0.1801 | ||
PSZ-AC_2:2 | 1.1626 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.1626 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1770 | ||
PSZ-AC_3:3 | 1.1640 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.1640 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1768 | ||
PSZ-AC_4:4 | 1.1672 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.1672 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1763 | ||
PSZ-AC_5:5 | 1.1575 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.1575 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1778 | ||
PSZ-AC_6:6 | 2.0295 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 2.0295 | 1.0000 | 1.0000 | Not calculated | 0.4115 | 0.2027 | ||
PSZ-AC_7:7 | 1.0674 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0674 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1927 | ||
PSZ-AC_8:8 | 1.0633 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0633 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1935 | ||
PSZ-AC_9:9 | 1.0682 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0682 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1926 | ||
PSZ-AC_10:10 | 1.2510 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.2510 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1645 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
LGSTORE1 | PSZ-AC_1:1 | 0.000000 | 56.2505 | 0.001181 | 348.39 | 0.4115 | 1.0000 | 0.4115 | 1.000 | 0.4115 |
SMSTORE1 | PSZ-AC_2:2 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE2 | PSZ-AC_3:3 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE3 | PSZ-AC_4:4 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE4 | PSZ-AC_5:5 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
LGSTORE2 | PSZ-AC_6:6 | 0.000000 | 56.2505 | 0.001181 | 348.39 | 0.4115 | 1.0000 | 0.4115 | 1.000 | 0.4115 |
SMSTORE5 | PSZ-AC_7:7 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE6 | PSZ-AC_8:8 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE7 | PSZ-AC_9:9 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE8 | PSZ-AC_10:10 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC_1:1 | 0.000000 | 56.25 | 0.001181 | 348.3864 | 0.4115 | 0.4115 | 0.4115 |
PSZ-AC_2:2 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_3:3 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_4:4 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_5:5 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_6:6 | 0.000000 | 56.25 | 0.001181 | 348.3864 | 0.4115 | 0.4115 | 0.4115 |
PSZ-AC_7:7 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_8:8 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_9:9 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_10:10 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LGSTORE1 | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.2842 | 2.2842 | 2.2842 | No | 0.4115 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE1 | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1626 | 1.1626 | 1.1626 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE2 | PSZ-AC_3:3 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1640 | 1.1640 | 1.1640 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE3 | PSZ-AC_4:4 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1672 | 1.1672 | 1.1672 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE4 | PSZ-AC_5:5 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1575 | 1.1575 | 1.1575 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LGSTORE2 | PSZ-AC_6:6 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.0295 | 2.0295 | 2.0295 | No | 0.4115 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE5 | PSZ-AC_7:7 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0674 | 1.0674 | 1.0674 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE6 | PSZ-AC_8:8 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0633 | 1.0633 | 1.0633 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE7 | PSZ-AC_9:9 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0682 | 1.0682 | 1.0682 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE8 | PSZ-AC_10:10 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2510 | 1.2510 | 1.2510 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 2.2842 | 2.2842 | 2.2842 | 2.2842 | 0.4115 | 1.0000 |
PSZ-AC_2:2 | 1.1626 | 1.1626 | 1.1626 | 1.1626 | 0.2057 | 1.0000 |
PSZ-AC_3:3 | 1.1640 | 1.1640 | 1.1640 | 1.1640 | 0.2057 | 1.0000 |
PSZ-AC_4:4 | 1.1672 | 1.1672 | 1.1672 | 1.1672 | 0.2057 | 1.0000 |
PSZ-AC_5:5 | 1.1575 | 1.1575 | 1.1575 | 1.1575 | 0.2057 | 1.0000 |
PSZ-AC_6:6 | 2.0295 | 2.0295 | 2.0295 | 2.0295 | 0.4115 | 1.0000 |
PSZ-AC_7:7 | 1.0674 | 1.0675 | 1.0674 | 1.0674 | 0.2057 | 1.0000 |
PSZ-AC_8:8 | 1.0633 | 1.0633 | 1.0633 | 1.0633 | 0.2057 | 1.0000 |
PSZ-AC_9:9 | 1.0682 | 1.0682 | 1.0682 | 1.0682 | 0.2057 | 1.0000 |
PSZ-AC_10:10 | 1.2510 | 1.2510 | 1.2510 | 1.2510 | 0.2057 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LGSTORE1 | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.2842 | 2.2842 | 2.2842 | No | 0.4115 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE1 | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1626 | 1.1626 | 1.1626 | No | 0.2057 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE2 | PSZ-AC_3:3 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1640 | 1.1640 | 1.1640 | No | 0.2057 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE3 | PSZ-AC_4:4 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1672 | 1.1672 | 1.1672 | No | 0.2057 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE4 | PSZ-AC_5:5 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1575 | 1.1575 | 1.1575 | No | 0.2057 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LGSTORE2 | PSZ-AC_6:6 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.0295 | 2.0295 | 2.0295 | No | 0.4115 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE5 | PSZ-AC_7:7 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0674 | 1.0674 | 1.0674 | No | 0.2057 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE6 | PSZ-AC_8:8 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0633 | 1.0633 | 1.0633 | No | 0.2057 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE7 | PSZ-AC_9:9 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0682 | 1.0682 | 1.0682 | No | 0.2057 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE8 | PSZ-AC_10:10 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2510 | 1.2510 | 1.2510 | No | 0.2057 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 2.2842 | 2.2842 | 2.2842 | 2.2842 | 0.4115 | 1.0000 |
PSZ-AC_2:2 | 1.1626 | 1.1626 | 1.1626 | 1.1626 | 0.2057 | 1.0000 |
PSZ-AC_3:3 | 1.1640 | 1.1640 | 1.1640 | 1.1640 | 0.2057 | 1.0000 |
PSZ-AC_4:4 | 1.1672 | 1.1672 | 1.1672 | 1.1672 | 0.2057 | 1.0000 |
PSZ-AC_5:5 | 1.1575 | 1.1575 | 1.1575 | 1.1575 | 0.2057 | 1.0000 |
PSZ-AC_6:6 | 2.0295 | 2.0295 | 2.0295 | 2.0295 | 0.4115 | 1.0000 |
PSZ-AC_7:7 | 1.0674 | 1.0674 | 1.0674 | 1.0674 | 0.2057 | 1.0000 |
PSZ-AC_8:8 | 1.0633 | 1.0633 | 1.0633 | 1.0633 | 0.2057 | 1.0000 |
PSZ-AC_9:9 | 1.0682 | 1.0682 | 1.0682 | 1.0682 | 0.2057 | 1.0000 |
PSZ-AC_10:10 | 1.2510 | 1.2510 | 1.2510 | 1.2510 | 0.2057 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:06
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Ho Chi Minh City-Tan Son Nhat Intl AP - VNM IWEC2 WMO#=489000 |
Total gross floor area [m2] | 2090.32 |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
LGSTORE1 | 348.39 | 348.39 | 0.00 | 112.00 |
SMSTORE1 | 174.19 | 174.19 | 0.00 | 112.00 |
SMSTORE2 | 174.19 | 174.19 | 0.00 | 84.29 |
SMSTORE3 | 174.19 | 174.19 | 0.00 | 84.29 |
SMSTORE4 | 174.19 | 174.19 | 0.00 | 84.29 |
LGSTORE2 | 348.39 | 348.39 | 0.00 | 77.29 |
SMSTORE5 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE6 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE7 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE8 | 174.19 | 174.19 | 0.00 | 77.29 |
Totals | 2090.32 | 2090.32 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 1.00 |
Number of hours not met | 1.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 685.93 | 77657.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 366.68 | 23459.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 60.18 | 5507.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 128.15 | 8059.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 117.50 | 12249.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 57.53 | 11748.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 128.15 | 1415.97 |
Natural Gas | 0.00 | 0.00 |
Additional | 0.00 | 0.00 |
Total | 128.15 | 1415.97 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 175.42 |
Space Heating | 0.00 |
Space Cooling | 328.15 |
Fans (All) | 56.21 |
Service Water Heating | 27.52 |
Receptacle Equipment | 61.31 |
Miscellaneous (All) | 677.39 |
Subtotal | 677.39 |
Natural Gas [MJ/m2] | |
Space Heating | 0.00 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 0.00 |
Subtotal | 0.00 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 25.90 |
Space Heating | 0.00 |
Space Cooling | 48.44 |
Fans (All) | 8.30 |
Service Water Heating | 4.06 |
Receptacle Equipment | 9.05 |
Miscellaneous | 4.25 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
TYPE1_OCC_SCH | 1630. | 5840. |
TYPE2_OCC_SCH | 995. | 4429. |
TYPE3_OCC_SCH | 1709. | 4064. |
LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 3767. | 8760. |
LTG_SCH_BASE_LPD2 | 3238. | 8760. |
LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 3296. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | 5084. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | 5084. | 8760. |
LTG_SCH_BASE_SMALL_LPD1 | 4453. | 8760. |
LTG_SCH_BASE_LPD1 | 4376. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | 3767. | 8760. |
LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 3584. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 4096. | 8760. |
TYPE1_EQUIP_SCH | 4868. | 8760. |
TYPE2_EQUIP_SCH | 3893. | 8760. |
TYPE3_EQUIP_SCH | 3584. | 8760. |
TYPE1_INFIL_SCH | 4302. | 8760. |
TYPE2_INFIL_SCH | 5164. | 8760. |
TYPE3_INFIL_SCH | 5438. | 8760. |
INFIL_DOOR_OPENING_SCH | 2505. | 4380. |
TYPE1_MINOA_MOTORIZEDDAMPER_SCH | 5579. | 5579. |
TYPE2_MINOA_MOTORIZEDDAMPER_SCH | 4429. | 4429. |
TYPE3_MINOA_MOTORIZEDDAMPER_SCH | 4064. | 4064. |
TYPE1_SWH_SCH | 2063. | 6048. |
TYPE2_SWH_SCH | 1831. | 4429. |
TYPE3_SWH_SCH | 1733. | 4064. |
AVERAGE_SWH_SCH | 1863. | 6152. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 7118. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 5839. | 5839. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 7300. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6570. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
TYPE1_HTGSETP_SCH_NO_OPTIMUM | LGSTORE1 DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
TYPE1_CLGSETP_SCH_NO_OPTIMUM | LGSTORE1 DUAL SP CONTROL | July | 23.89 | 365 | 23.89 | 365 |
TYPE2_HTGSETP_SCH_NO_OPTIMUM | SMSTORE2 DUAL SP CONTROL | January | 21.11 | 365 | 15.56 | 365 |
TYPE2_CLGSETP_SCH_NO_OPTIMUM | SMSTORE2 DUAL SP CONTROL | July | 23.89 | 365 | 29.44 | 365 |
TYPE3_HTGSETP_SCH_NO_OPTIMUM | LGSTORE2 DUAL SP CONTROL | January | 21.11 | 365 | 15.56 | 365 |
TYPE3_CLGSETP_SCH_NO_OPTIMUM | LGSTORE2 DUAL SP CONTROL | July | 23.89 | 365 | 29.44 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:06
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
LGSTORE1 | 8575.67 | 184.33 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 8757.00 | 3.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 6241.50 | 2515.67 | 2.83 | 0.00 | 0.00 |
SMSTORE3 | 6072.33 | 2684.67 | 3.00 | 0.00 | 0.00 |
SMSTORE4 | 6516.67 | 2240.33 | 3.00 | 0.00 | 0.00 |
LGSTORE2 | 7491.00 | 1266.50 | 2.50 | 0.00 | 0.00 |
SMSTORE5 | 7581.33 | 1177.00 | 1.67 | 0.00 | 0.00 |
SMSTORE6 | 7607.50 | 1150.83 | 1.67 | 0.00 | 0.00 |
SMSTORE7 | 7628.33 | 1129.83 | 1.83 | 0.00 | 0.00 |
SMSTORE8 | 7072.83 | 1660.50 | 26.67 | 0.00 | 0.00 |
Min | 6072.33 | 3.00 | 0.00 | 0.00 | 0.00 |
Max | 8757.00 | 2684.67 | 26.67 | 0.00 | 0.00 |
Average | 7354.42 | 1401.27 | 4.32 | 0.00 | 0.00 |
Sum | 73544.17 | 14012.67 | 43.17 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
LGSTORE1 | 89041.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 43777.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 25302.33 | 171.33 | 1.33 | 0.00 | 0.00 |
SMSTORE3 | 25302.00 | 171.67 | 1.33 | 0.00 | 0.00 |
SMSTORE4 | 25311.33 | 162.33 | 1.33 | 0.00 | 0.00 |
LGSTORE2 | 92795.00 | 410.00 | 6.00 | 0.00 | 0.00 |
SMSTORE5 | 45705.50 | 204.00 | 2.50 | 0.00 | 0.00 |
SMSTORE6 | 45706.00 | 203.50 | 2.50 | 0.00 | 0.00 |
SMSTORE7 | 45706.00 | 203.00 | 3.00 | 0.00 | 0.00 |
SMSTORE8 | 45681.00 | 224.00 | 7.00 | 0.00 | 0.00 |
Min | 25302.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 92795.00 | 410.00 | 7.00 | 0.00 | 0.00 |
Average | 48432.72 | 174.98 | 2.50 | 0.00 | 0.00 |
Sum | 484327.17 | 1749.83 | 25.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
LGSTORE1 | 2816.67 | 5943.33 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 5128.83 | 3631.17 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 1609.17 | 7150.83 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 1630.83 | 7129.17 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 1556.83 | 7203.17 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 1179.83 | 7580.17 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 1153.83 | 7606.17 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 1141.17 | 7618.83 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 1162.33 | 7597.67 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 1806.83 | 6914.17 | 39.00 | 0.00 | 0.00 |
Min | 1141.17 | 3631.17 | 0.00 | 0.00 | 0.00 |
Max | 5128.83 | 7618.83 | 39.00 | 0.00 | 0.00 |
Average | 1918.63 | 6837.47 | 3.90 | 0.00 | 0.00 |
Sum | 19186.33 | 68374.67 | 39.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
LGSTORE1 | 45365.50 | 43675.50 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 23539.67 | 20237.33 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 9710.83 | 15764.17 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 9789.67 | 15685.33 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 9405.17 | 16069.83 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 26693.17 | 66517.83 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 12599.83 | 33312.17 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 12458.17 | 33453.83 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 12715.83 | 33196.17 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 19876.50 | 26035.50 | 0.00 | 0.00 | 0.00 |
Min | 9405.17 | 15685.33 | 0.00 | 0.00 | 0.00 |
Max | 45365.50 | 66517.83 | 0.00 | 0.00 | 0.00 |
Average | 18215.43 | 30394.77 | 0.00 | 0.00 | 0.00 |
Sum | 182154.33 | 303947.67 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:06
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:06
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
For: Environment
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTRIPMALL
For: Environment
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 0A
For: Environment
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY VNM_HOCHIMINH_TANSONHOA
For: Environment
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: ZoneCoolingSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.199727E+11 | 36517.69 | 23-JAN-08:62 | 21.83 | 18.43 | 0.140990E+10 | 1686.09 | 08-JAN-13:20 | 21.83 | 18.43 |
February | 0.190003E+11 | 38293.38 | 21-FEB-08:61 | 26.33 | 21.23 | 0.127283E+10 | 1686.08 | 04-FEB-13:30 | 26.33 | 21.23 |
March | 0.214189E+11 | 34862.66 | 04-MAR-08:62 | 26.50 | 20.59 | 0.139780E+10 | 1686.07 | 05-MAR-13:20 | 31.60 | 23.84 |
April | 0.209702E+11 | 31636.38 | 27-APR-07:01 | 27.08 | 24.31 | 0.136191E+10 | 1685.98 | 16-APR-17:19 | 27.08 | 24.31 |
May | 0.215843E+11 | 29216.80 | 09-MAY-07:01 | 24.50 | 24.40 | 0.140192E+10 | 1685.99 | 28-MAY-16:10 | 27.83 | 25.75 |
June | 0.216035E+11 | 30430.55 | 25-JUN-07:02 | 25.75 | 24.65 | 0.135485E+10 | 1686.00 | 04-JUN-17:19 | 25.75 | 24.65 |
July | 0.200491E+11 | 34401.38 | 09-JUL-07:01 | 26.50 | 23.81 | 0.141298E+10 | 1686.08 | 30-JUL-12:09 | 31.08 | 24.50 |
August | 0.195008E+11 | 30563.67 | 24-AUG-07:02 | 25.75 | 25.32 | 0.139428E+10 | 1686.00 | 13-AUG-17:00 | 25.75 | 25.32 |
September | 0.193213E+11 | 31546.53 | 10-SEP-07:01 | 26.50 | 25.49 | 0.136540E+10 | 1686.02 | 22-SEP-12:20 | 28.17 | 25.85 |
October | 0.187698E+11 | 31259.92 | 08-OCT-07:02 | 25.75 | 24.25 | 0.140993E+10 | 1686.04 | 20-OCT-12:09 | 30.53 | 25.31 |
November | 0.186152E+11 | 35528.64 | 25-NOV-08:62 | 22.25 | 19.45 | 0.136342E+10 | 1686.04 | 05-NOV-16:10 | 22.25 | 19.45 |
December | 0.193911E+11 | 35903.33 | 27-DEC-08:62 | 23.50 | 19.75 | 0.141696E+10 | 1686.09 | 02-DEC-13:00 | 23.50 | 19.75 |
Annual Sum or Average | 0.240197E+12 | 0.165622E+11 | ||||||||
Minimum of Months | 0.186152E+11 | 29216.80 | 21.83 | 18.43 | 0.127283E+10 | 1685.98 | 21.83 | 18.43 | ||
Maximum of Months | 0.216035E+11 | 38293.38 | 27.08 | 25.49 | 0.141696E+10 | 1686.09 | 31.60 | 25.85 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.103176E+11 | 21208.60 | 16-JAN-08:62 | 22.05 | 20.01 | 0.704938E+09 | 843.02 | 29-JAN-13:30 | 31.25 | 23.22 |
February | 0.971182E+10 | 21891.86 | 21-FEB-08:61 | 26.33 | 21.23 | 0.636400E+09 | 843.00 | 03-FEB-13:09 | 26.33 | 21.23 |
March | 0.108223E+11 | 20156.13 | 03-MAR-08:62 | 26.17 | 20.16 | 0.698881E+09 | 842.99 | 05-MAR-13:09 | 31.50 | 23.79 |
April | 0.105857E+11 | 18507.06 | 27-APR-07:01 | 27.08 | 24.31 | 0.680933E+09 | 842.98 | 09-APR-16:49 | 27.08 | 24.31 |
May | 0.110057E+11 | 18131.69 | 12-MAY-07:02 | 25.75 | 25.62 | 0.700936E+09 | 842.98 | 14-MAY-17:19 | 32.00 | 26.79 |
June | 0.109453E+11 | 18685.80 | 25-JUN-07:02 | 25.75 | 24.65 | 0.677401E+09 | 842.99 | 11-JUN-17:49 | 25.75 | 24.65 |
July | 0.102487E+11 | 19969.23 | 08-JUL-07:02 | 25.08 | 22.66 | 0.706470E+09 | 843.00 | 07-JUL-12:09 | 25.08 | 22.66 |
August | 0.999942E+10 | 18511.92 | 24-AUG-07:02 | 25.75 | 25.32 | 0.697119E+09 | 842.99 | 13-AUG-17:00 | 25.75 | 25.32 |
September | 0.988022E+10 | 18836.19 | 09-SEP-07:02 | 25.08 | 24.00 | 0.682683E+09 | 842.98 | 24-SEP-17:49 | 29.17 | 26.15 |
October | 0.975223E+10 | 19026.68 | 09-OCT-07:01 | 25.50 | 24.67 | 0.704950E+09 | 842.99 | 15-OCT-17:30 | 28.25 | 25.80 |
November | 0.964274E+10 | 20608.36 | 25-NOV-08:62 | 22.25 | 19.45 | 0.681697E+09 | 843.00 | 05-NOV-16:10 | 22.25 | 19.45 |
December | 0.100547E+11 | 20688.22 | 27-DEC-08:62 | 23.50 | 19.75 | 0.708468E+09 | 843.02 | 08-DEC-13:09 | 23.50 | 19.75 |
Annual Sum or Average | 0.122966E+12 | 0.828088E+10 | ||||||||
Minimum of Months | 0.964274E+10 | 18131.69 | 22.05 | 19.45 | 0.636400E+09 | 842.98 | 22.25 | 19.45 | ||
Maximum of Months | 0.110057E+11 | 21891.86 | 27.08 | 25.62 | 0.708468E+09 | 843.02 | 32.00 | 26.79 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.801756E+10 | 18087.27 | 24-JAN-07:02 | 19.50 | 17.57 | 0.420824E+09 | 843.01 | 14-JAN-13:50 | 19.50 | 17.57 |
February | 0.761311E+10 | 18887.73 | 25-FEB-07:02 | 22.83 | 19.10 | 0.382298E+09 | 842.98 | 25-FEB-13:00 | 32.20 | 22.19 |
March | 0.859353E+10 | 17241.22 | 04-MAR-07:02 | 24.83 | 20.47 | 0.432094E+09 | 842.98 | 04-MAR-13:50 | 33.05 | 21.97 |
April | 0.828127E+10 | 15493.98 | 27-APR-06:01 | 26.15 | 23.95 | 0.411461E+09 | 842.90 | 08-APR-12:09 | 26.15 | 23.95 |
May | 0.868967E+10 | 13870.79 | 11-MAY-06:02 | 24.37 | 24.37 | 0.426615E+09 | 842.90 | 27-MAY-12:09 | 33.22 | 26.33 |
June | 0.869584E+10 | 13934.72 | 20-JUN-06:01 | 24.05 | 24.05 | 0.417498E+09 | 842.90 | 03-JUN-12:00 | 24.05 | 24.05 |
July | 0.784072E+10 | 15597.75 | 06-JUL-06:01 | 25.22 | 23.04 | 0.420447E+09 | 842.98 | 22-JUL-12:09 | 30.43 | 24.42 |
August | 0.782302E+10 | 14225.75 | 24-AUG-06:02 | 24.25 | 24.17 | 0.431917E+09 | 842.92 | 19-AUG-12:09 | 24.25 | 24.17 |
September | 0.762599E+10 | 13957.31 | 28-SEP-06:01 | 25.17 | 24.30 | 0.411210E+09 | 842.97 | 16-SEP-12:00 | 25.17 | 24.30 |
October | 0.747854E+10 | 13933.95 | 11-OCT-06:02 | 24.10 | 23.71 | 0.420768E+09 | 842.90 | 14-OCT-12:09 | 30.33 | 26.72 |
November | 0.747809E+10 | 16984.09 | 25-NOV-07:02 | 21.17 | 18.84 | 0.406474E+09 | 842.99 | 25-NOV-13:39 | 26.33 | 21.82 |
December | 0.773395E+10 | 17704.39 | 27-DEC-07:02 | 20.50 | 19.41 | 0.420188E+09 | 843.01 | 02-DEC-13:50 | 20.50 | 19.41 |
Annual Sum or Average | 0.958713E+11 | 0.500180E+10 | ||||||||
Minimum of Months | 0.747809E+10 | 13870.79 | 19.50 | 17.57 | 0.382298E+09 | 842.90 | 19.50 | 17.57 | ||
Maximum of Months | 0.869584E+10 | 18887.73 | 26.15 | 24.37 | 0.432094E+09 | 843.01 | 33.22 | 26.72 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.804813E+10 | 18163.71 | 24-JAN-07:02 | 19.50 | 17.57 | 0.420825E+09 | 843.01 | 14-JAN-13:50 | 19.50 | 17.57 |
February | 0.764465E+10 | 18977.14 | 25-FEB-07:02 | 22.83 | 19.10 | 0.382299E+09 | 842.98 | 25-FEB-13:00 | 32.20 | 22.19 |
March | 0.862919E+10 | 17306.90 | 04-MAR-07:02 | 24.83 | 20.47 | 0.432095E+09 | 842.98 | 04-MAR-13:50 | 33.05 | 21.97 |
April | 0.832421E+10 | 15572.35 | 27-APR-06:01 | 26.15 | 23.95 | 0.411463E+09 | 842.90 | 08-APR-12:09 | 26.15 | 23.95 |
May | 0.874472E+10 | 13985.19 | 09-MAY-06:01 | 24.03 | 24.01 | 0.426619E+09 | 842.90 | 27-MAY-12:09 | 33.22 | 26.33 |
June | 0.874892E+10 | 14056.16 | 20-JUN-06:01 | 24.05 | 24.05 | 0.417502E+09 | 842.90 | 03-JUN-12:00 | 24.05 | 24.05 |
July | 0.788622E+10 | 15702.22 | 06-JUL-06:01 | 25.22 | 23.04 | 0.420450E+09 | 842.98 | 22-JUL-12:09 | 30.43 | 24.42 |
August | 0.785152E+10 | 14278.43 | 24-AUG-06:02 | 24.25 | 24.17 | 0.431918E+09 | 842.92 | 19-AUG-12:09 | 24.25 | 24.17 |
September | 0.766064E+10 | 14027.22 | 28-SEP-06:01 | 25.17 | 24.30 | 0.411211E+09 | 842.97 | 16-SEP-12:00 | 25.17 | 24.30 |
October | 0.750772E+10 | 14022.78 | 11-OCT-06:02 | 24.10 | 23.71 | 0.420768E+09 | 842.90 | 14-OCT-12:09 | 30.33 | 26.72 |
November | 0.749742E+10 | 17057.63 | 25-NOV-07:02 | 21.17 | 18.84 | 0.406474E+09 | 842.99 | 25-NOV-13:39 | 26.33 | 21.82 |
December | 0.775278E+10 | 17785.44 | 27-DEC-07:02 | 20.50 | 19.41 | 0.420188E+09 | 843.01 | 02-DEC-13:50 | 20.50 | 19.41 |
Annual Sum or Average | 0.962961E+11 | 0.500181E+10 | ||||||||
Minimum of Months | 0.749742E+10 | 13985.19 | 19.50 | 17.57 | 0.382299E+09 | 842.90 | 19.50 | 17.57 | ||
Maximum of Months | 0.874892E+10 | 18977.14 | 26.15 | 24.30 | 0.432095E+09 | 843.01 | 33.22 | 26.72 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.789158E+10 | 17908.44 | 24-JAN-07:02 | 19.50 | 17.57 | 0.420793E+09 | 843.01 | 14-JAN-13:50 | 19.50 | 17.57 |
February | 0.750231E+10 | 18688.99 | 25-FEB-07:02 | 22.83 | 19.10 | 0.382270E+09 | 842.98 | 25-FEB-13:00 | 32.20 | 22.19 |
March | 0.846408E+10 | 17029.77 | 04-MAR-07:02 | 24.83 | 20.47 | 0.432062E+09 | 842.98 | 04-MAR-13:50 | 33.05 | 21.97 |
April | 0.816348E+10 | 15273.24 | 27-APR-06:01 | 26.15 | 23.95 | 0.411431E+09 | 842.90 | 08-APR-12:09 | 26.15 | 23.95 |
May | 0.858988E+10 | 13740.16 | 09-MAY-06:01 | 24.03 | 24.01 | 0.426587E+09 | 842.90 | 27-MAY-12:09 | 33.22 | 26.33 |
June | 0.859518E+10 | 13815.67 | 20-JUN-06:01 | 24.05 | 24.05 | 0.417471E+09 | 842.90 | 03-JUN-12:00 | 24.05 | 24.05 |
July | 0.773054E+10 | 15428.79 | 06-JUL-06:01 | 25.22 | 23.04 | 0.420418E+09 | 842.97 | 22-JUL-12:09 | 30.43 | 24.42 |
August | 0.768312E+10 | 13987.01 | 24-AUG-06:02 | 24.25 | 24.17 | 0.431885E+09 | 842.92 | 19-AUG-12:09 | 24.25 | 24.17 |
September | 0.750271E+10 | 13737.45 | 28-SEP-06:01 | 25.17 | 24.30 | 0.411180E+09 | 842.98 | 16-SEP-12:00 | 25.17 | 24.30 |
October | 0.734619E+10 | 13772.83 | 11-OCT-06:02 | 24.10 | 23.71 | 0.420736E+09 | 842.90 | 14-OCT-12:09 | 30.33 | 26.72 |
November | 0.733988E+10 | 16805.48 | 25-NOV-07:02 | 21.17 | 18.84 | 0.406443E+09 | 843.00 | 25-NOV-13:39 | 26.33 | 21.82 |
December | 0.759112E+10 | 17538.89 | 27-DEC-07:02 | 20.50 | 19.41 | 0.420156E+09 | 843.01 | 02-DEC-13:50 | 20.50 | 19.41 |
Annual Sum or Average | 0.944001E+11 | 0.500143E+10 | ||||||||
Minimum of Months | 0.733988E+10 | 13737.45 | 19.50 | 17.57 | 0.382270E+09 | 842.90 | 19.50 | 17.57 | ||
Maximum of Months | 0.859518E+10 | 18688.99 | 26.15 | 24.30 | 0.432062E+09 | 843.01 | 33.22 | 26.72 |
Report: ZoneCoolingSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.136261E+11 | 32357.52 | 24-JAN-08:62 | 19.83 | 17.92 | 0.143596E+10 | 2248.07 | 07-JAN-15:20 | 19.83 | 17.92 |
February | 0.129769E+11 | 33349.48 | 25-FEB-08:62 | 26.67 | 20.13 | 0.130742E+10 | 2248.06 | 25-FEB-15:09 | 31.83 | 22.04 |
March | 0.146224E+11 | 30728.36 | 04-MAR-08:62 | 26.50 | 20.59 | 0.148071E+10 | 2248.10 | 04-MAR-15:00 | 33.20 | 22.30 |
April | 0.140547E+11 | 27967.75 | 27-APR-07:01 | 27.08 | 24.31 | 0.141095E+10 | 2247.81 | 22-APR-14:00 | 27.08 | 24.31 |
May | 0.148514E+11 | 26184.57 | 09-MAY-07:01 | 24.50 | 24.40 | 0.145871E+10 | 2247.81 | 13-MAY-14:00 | 31.50 | 26.17 |
June | 0.149249E+11 | 27189.19 | 20-JUN-07:01 | 24.58 | 24.46 | 0.143054E+10 | 2247.81 | 03-JUN-14:00 | 24.58 | 24.46 |
July | 0.132675E+11 | 29006.37 | 06-JUL-07:02 | 25.92 | 23.26 | 0.143902E+10 | 2247.81 | 29-JUL-14:09 | 32.00 | 24.80 |
August | 0.131994E+11 | 25944.70 | 29-AUG-07:01 | 26.25 | 25.69 | 0.148028E+10 | 2247.91 | 19-AUG-14:50 | 26.25 | 25.69 |
September | 0.128736E+11 | 26254.79 | 06-SEP-07:01 | 27.17 | 25.69 | 0.141055E+10 | 2247.95 | 16-SEP-14:30 | 26.25 | 24.94 |
October | 0.125662E+11 | 26713.03 | 11-OCT-07:02 | 24.92 | 24.20 | 0.143582E+10 | 2247.81 | 21-OCT-14:50 | 29.58 | 25.84 |
November | 0.126025E+11 | 30796.53 | 25-NOV-08:62 | 22.25 | 19.45 | 0.138262E+10 | 2248.02 | 25-NOV-15:20 | 25.73 | 22.40 |
December | 0.130457E+11 | 32142.27 | 27-DEC-08:62 | 23.50 | 19.75 | 0.143834E+10 | 2248.03 | 02-DEC-15:30 | 23.50 | 19.75 |
Annual Sum or Average | 0.162611E+12 | 0.171109E+11 | ||||||||
Minimum of Months | 0.125662E+11 | 25944.70 | 19.83 | 17.92 | 0.130742E+10 | 2247.81 | 19.83 | 17.92 | ||
Maximum of Months | 0.149249E+11 | 33349.48 | 27.17 | 25.69 | 0.148071E+10 | 2248.10 | 33.20 | 26.17 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.712714E+10 | 16503.23 | 28-JAN-08:62 | 21.50 | 19.17 | 0.717946E+09 | 1124.00 | 07-JAN-15:09 | 21.50 | 19.17 |
February | 0.679624E+10 | 17457.07 | 25-FEB-08:62 | 26.67 | 20.13 | 0.653683E+09 | 1123.99 | 25-FEB-15:09 | 31.83 | 22.04 |
March | 0.766457E+10 | 16098.65 | 04-MAR-08:62 | 26.50 | 20.59 | 0.740314E+09 | 1124.02 | 04-MAR-15:00 | 33.20 | 22.30 |
April | 0.737472E+10 | 14678.64 | 27-APR-07:01 | 27.08 | 24.31 | 0.705435E+09 | 1123.87 | 22-APR-14:00 | 27.08 | 24.31 |
May | 0.779116E+10 | 13728.61 | 09-MAY-07:01 | 24.50 | 24.40 | 0.729312E+09 | 1123.87 | 13-MAY-14:00 | 31.50 | 26.17 |
June | 0.781552E+10 | 14260.48 | 20-JUN-07:01 | 24.58 | 24.46 | 0.715233E+09 | 1123.87 | 03-JUN-14:00 | 24.58 | 24.46 |
July | 0.693196E+10 | 15209.81 | 06-JUL-07:02 | 25.92 | 23.26 | 0.719458E+09 | 1123.87 | 29-JUL-14:09 | 32.00 | 24.80 |
August | 0.689689E+10 | 13635.74 | 29-AUG-07:01 | 26.25 | 25.69 | 0.740109E+09 | 1123.96 | 19-AUG-14:30 | 26.25 | 25.69 |
September | 0.673238E+10 | 13804.86 | 06-SEP-07:01 | 27.17 | 25.69 | 0.705239E+09 | 1123.95 | 16-SEP-14:30 | 26.25 | 24.94 |
October | 0.656325E+10 | 14032.22 | 11-OCT-07:02 | 24.92 | 24.20 | 0.717875E+09 | 1123.87 | 21-OCT-14:00 | 29.50 | 25.84 |
November | 0.657719E+10 | 16087.33 | 25-NOV-08:62 | 22.25 | 19.45 | 0.691283E+09 | 1123.87 | 25-NOV-15:09 | 25.82 | 22.39 |
December | 0.681258E+10 | 16812.34 | 27-DEC-08:62 | 23.50 | 19.75 | 0.719136E+09 | 1123.98 | 23-DEC-15:00 | 23.50 | 19.75 |
Annual Sum or Average | 0.850836E+11 | 0.855502E+10 | ||||||||
Minimum of Months | 0.656325E+10 | 13635.74 | 21.50 | 19.17 | 0.653683E+09 | 1123.87 | 21.50 | 19.17 | ||
Maximum of Months | 0.781552E+10 | 17457.07 | 27.17 | 25.69 | 0.740314E+09 | 1124.02 | 33.20 | 26.17 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.708348E+10 | 16408.47 | 28-JAN-08:62 | 21.50 | 19.17 | 0.717940E+09 | 1124.00 | 07-JAN-15:09 | 21.50 | 19.17 |
February | 0.675950E+10 | 17363.79 | 25-FEB-08:62 | 26.67 | 20.13 | 0.653678E+09 | 1123.99 | 25-FEB-15:09 | 31.83 | 22.04 |
March | 0.762574E+10 | 16012.54 | 04-MAR-08:62 | 26.50 | 20.59 | 0.740310E+09 | 1124.02 | 04-MAR-15:00 | 33.20 | 22.30 |
April | 0.734068E+10 | 14594.43 | 27-APR-07:01 | 27.08 | 24.31 | 0.705430E+09 | 1123.87 | 22-APR-14:00 | 27.08 | 24.31 |
May | 0.775572E+10 | 13653.38 | 09-MAY-07:01 | 24.50 | 24.40 | 0.729307E+09 | 1123.87 | 13-MAY-14:00 | 31.50 | 26.17 |
June | 0.777925E+10 | 14181.98 | 20-JUN-07:01 | 24.58 | 24.46 | 0.715229E+09 | 1123.87 | 03-JUN-14:00 | 24.58 | 24.46 |
July | 0.689688E+10 | 15125.25 | 06-JUL-07:02 | 25.92 | 23.26 | 0.719453E+09 | 1123.87 | 29-JUL-14:20 | 32.00 | 24.80 |
August | 0.686023E+10 | 13558.06 | 29-AUG-07:01 | 26.25 | 25.69 | 0.740105E+09 | 1123.93 | 19-AUG-14:50 | 26.25 | 25.69 |
September | 0.669840E+10 | 13730.46 | 06-SEP-07:01 | 27.17 | 25.69 | 0.705235E+09 | 1123.95 | 16-SEP-14:30 | 26.25 | 24.94 |
October | 0.652367E+10 | 13947.58 | 11-OCT-07:02 | 24.92 | 24.20 | 0.717870E+09 | 1123.87 | 21-OCT-14:50 | 29.58 | 25.84 |
November | 0.653607E+10 | 15996.62 | 25-NOV-08:62 | 22.25 | 19.45 | 0.691279E+09 | 1123.87 | 25-NOV-15:09 | 25.82 | 22.39 |
December | 0.676825E+10 | 16718.41 | 27-DEC-08:62 | 23.50 | 19.75 | 0.719129E+09 | 1123.98 | 23-DEC-15:00 | 23.50 | 19.75 |
Annual Sum or Average | 0.846279E+11 | 0.855496E+10 | ||||||||
Minimum of Months | 0.652367E+10 | 13558.06 | 21.50 | 19.17 | 0.653678E+09 | 1123.87 | 21.50 | 19.17 | ||
Maximum of Months | 0.777925E+10 | 17363.79 | 27.17 | 25.69 | 0.740310E+09 | 1124.02 | 33.20 | 26.17 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.710073E+10 | 16434.47 | 28-JAN-08:62 | 21.50 | 19.17 | 0.717940E+09 | 1124.00 | 07-JAN-15:09 | 21.50 | 19.17 |
February | 0.679896E+10 | 17393.68 | 25-FEB-08:62 | 26.67 | 20.13 | 0.653681E+09 | 1123.99 | 25-FEB-15:09 | 31.83 | 22.04 |
March | 0.768198E+10 | 15999.00 | 04-MAR-08:62 | 26.50 | 20.59 | 0.740315E+09 | 1124.02 | 04-MAR-15:00 | 33.20 | 22.30 |
April | 0.741537E+10 | 14651.08 | 27-APR-07:01 | 27.08 | 24.31 | 0.705436E+09 | 1123.87 | 22-APR-14:00 | 27.08 | 24.31 |
May | 0.782830E+10 | 13710.54 | 09-MAY-07:01 | 24.50 | 24.40 | 0.729315E+09 | 1123.87 | 13-MAY-14:00 | 31.50 | 26.17 |
June | 0.786133E+10 | 14269.60 | 20-JUN-07:01 | 24.58 | 24.46 | 0.715235E+09 | 1123.87 | 03-JUN-14:00 | 24.58 | 24.46 |
July | 0.695293E+10 | 15190.03 | 06-JUL-07:02 | 25.92 | 23.26 | 0.719460E+09 | 1123.87 | 29-JUL-14:09 | 32.00 | 24.80 |
August | 0.691050E+10 | 13645.52 | 29-AUG-07:01 | 26.25 | 25.69 | 0.740107E+09 | 1123.96 | 19-AUG-14:30 | 26.25 | 25.69 |
September | 0.675473E+10 | 13823.32 | 06-SEP-07:01 | 27.17 | 25.69 | 0.705239E+09 | 1123.94 | 16-SEP-14:39 | 26.50 | 25.13 |
October | 0.654443E+10 | 13972.00 | 11-OCT-07:02 | 24.92 | 24.20 | 0.717873E+09 | 1123.87 | 21-OCT-14:39 | 29.67 | 25.83 |
November | 0.655408E+10 | 16026.79 | 25-NOV-08:62 | 22.25 | 19.45 | 0.691279E+09 | 1123.87 | 25-NOV-15:09 | 25.82 | 22.39 |
December | 0.677607E+10 | 16739.82 | 27-DEC-08:62 | 23.50 | 19.75 | 0.719129E+09 | 1123.99 | 23-DEC-15:50 | 23.50 | 19.75 |
Annual Sum or Average | 0.851794E+11 | 0.855501E+10 | ||||||||
Minimum of Months | 0.654443E+10 | 13645.52 | 21.50 | 19.17 | 0.653681E+09 | 1123.87 | 21.50 | 19.17 | ||
Maximum of Months | 0.786133E+10 | 17393.68 | 27.17 | 25.69 | 0.740315E+09 | 1124.02 | 33.20 | 26.17 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.848304E+10 | 18621.44 | 28-JAN-08:62 | 21.50 | 19.17 | 0.718091E+09 | 1123.94 | 07-JAN-15:09 | 21.50 | 19.17 |
February | 0.828698E+10 | 20313.94 | 23-FEB-08:62 | 23.33 | 20.35 | 0.653833E+09 | 1124.02 | 18-FEB-15:00 | 23.33 | 20.35 |
March | 0.948827E+10 | 17944.91 | 04-MAR-08:62 | 26.50 | 20.59 | 0.740477E+09 | 1124.02 | 04-MAR-15:09 | 33.87 | 22.25 |
April | 0.928667E+10 | 16137.01 | 27-APR-07:01 | 27.08 | 24.31 | 0.705627E+09 | 1123.87 | 22-APR-14:00 | 27.08 | 24.31 |
May | 0.962775E+10 | 15114.48 | 11-MAY-07:02 | 26.50 | 26.26 | 0.729495E+09 | 1123.87 | 13-MAY-14:00 | 31.50 | 26.17 |
June | 0.978130E+10 | 16102.37 | 20-JUN-07:01 | 24.58 | 24.46 | 0.715395E+09 | 1123.87 | 03-JUN-14:00 | 24.58 | 24.46 |
July | 0.854078E+10 | 17744.87 | 11-JUL-07:02 | 24.67 | 23.95 | 0.719687E+09 | 1123.87 | 29-JUL-14:50 | 32.00 | 24.80 |
August | 0.852211E+10 | 15586.04 | 24-AUG-07:02 | 25.75 | 25.32 | 0.740237E+09 | 1123.96 | 19-AUG-14:39 | 25.75 | 25.32 |
September | 0.835505E+10 | 15857.30 | 12-SEP-07:02 | 26.13 | 25.27 | 0.705423E+09 | 1123.87 | 23-SEP-14:09 | 31.00 | 26.41 |
October | 0.782105E+10 | 15862.66 | 11-OCT-07:02 | 24.92 | 24.20 | 0.718030E+09 | 1123.87 | 14-OCT-14:09 | 30.58 | 26.79 |
November | 0.784982E+10 | 18264.61 | 25-NOV-08:62 | 22.25 | 19.45 | 0.691393E+09 | 1123.87 | 04-NOV-14:50 | 22.25 | 19.45 |
December | 0.807244E+10 | 18833.40 | 27-DEC-08:62 | 23.50 | 19.75 | 0.719276E+09 | 1123.98 | 02-DEC-15:09 | 23.50 | 19.75 |
Annual Sum or Average | 0.104115E+12 | 0.855696E+10 | ||||||||
Minimum of Months | 0.782105E+10 | 15114.48 | 21.50 | 19.17 | 0.653833E+09 | 1123.87 | 21.50 | 19.17 | ||
Maximum of Months | 0.978130E+10 | 20313.94 | 27.08 | 26.26 | 0.740477E+09 | 1124.02 | 33.87 | 26.79 |
Report: ZoneHeatingSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 30534069.67 | 4429.01 | 11-JAN-08:05 | 29.33 |
February | 30413673.20 | 3530.26 | 18-FEB-08:05 | 27.33 |
March | 36357036.69 | 3646.07 | 09-MAR-08:05 | 27.50 |
April | 27926489.50 | 3610.47 | 11-APR-07:06 | 28.42 |
May | 22052804.57 | 4718.92 | 06-MAY-07:06 | 30.67 |
June | 19707087.46 | 3914.67 | 15-JUN-07:07 | 29.50 |
July | 35194007.08 | 3194.91 | 29-JUL-07:05 | 26.73 |
August | 28891848.25 | 3696.38 | 09-AUG-07:07 | 28.75 |
September | 31298353.51 | 3564.59 | 14-SEP-07:05 | 27.75 |
October | 32905648.62 | 3065.70 | 30-OCT-07:05 | 26.75 |
November | 28001306.18 | 3400.12 | 07-NOV-08:05 | 27.25 |
December | 28523181.59 | 3436.45 | 09-DEC-08:05 | 27.33 |
Annual Sum or Average | 0.351806E+09 | |||
Minimum of Months | 19707087.46 | 3065.70 | 26.73 | |
Maximum of Months | 36357036.69 | 4718.92 | 30.67 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 12780319.37 | 2240.98 | 11-JAN-08:05 | 29.33 |
February | 12609228.67 | 1709.86 | 18-FEB-08:05 | 27.33 |
March | 16483634.26 | 1789.25 | 30-MAR-07:04 | 27.67 |
April | 10800345.90 | 1923.53 | 01-APR-07:05 | 27.83 |
May | 12392139.22 | 2796.71 | 28-MAY-07:06 | 32.25 |
June | 11845869.91 | 2168.01 | 15-JUN-07:06 | 29.50 |
July | 15743743.90 | 1704.40 | 03-JUL-07:04 | 26.83 |
August | 13146125.13 | 2060.41 | 09-AUG-07:05 | 28.75 |
September | 13890129.05 | 1993.39 | 01-SEP-07:05 | 28.17 |
October | 13865723.47 | 1898.51 | 05-OCT-07:05 | 27.75 |
November | 12582533.44 | 1798.61 | 14-NOV-08:04 | 27.67 |
December | 13187088.19 | 1764.96 | 09-DEC-08:05 | 27.33 |
Annual Sum or Average | 0.159327E+09 | |||
Minimum of Months | 10800345.90 | 1704.40 | 26.83 | |
Maximum of Months | 16483634.26 | 2796.71 | 32.25 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 72293525.58 | 1904.18 | 29-JAN-17:02 | 30.83 |
February | 81932617.67 | 1823.39 | 12-FEB-17:02 | 30.67 |
March | 98351391.75 | 2752.60 | 19-MAR-16:01 | 34.25 |
April | 0.120864E+09 | 2531.28 | 02-APR-16:01 | 33.25 |
May | 0.109262E+09 | 2824.44 | 29-MAY-16:01 | 34.50 |
June | 0.106975E+09 | 2760.05 | 11-JUN-16:01 | 34.25 |
July | 86969728.89 | 2402.33 | 15-JUL-17:02 | 32.83 |
August | 76349872.85 | 2376.49 | 27-AUG-16:02 | 32.83 |
September | 83362220.19 | 2385.54 | 04-SEP-16:02 | 32.83 |
October | 70536407.63 | 1592.83 | 08-OCT-16:02 | 29.72 |
November | 59821463.81 | 1602.31 | 17-NOV-20:03 | 29.48 |
December | 54504259.60 | 1437.07 | 10-DEC-17:02 | 29.00 |
Annual Sum or Average | 0.102122E+10 | |||
Minimum of Months | 54504259.60 | 1437.07 | 29.00 | |
Maximum of Months | 0.120864E+09 | 2824.44 | 34.50 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 71805975.61 | 1904.52 | 29-JAN-17:02 | 30.83 |
February | 81705012.32 | 1823.65 | 12-FEB-17:02 | 30.67 |
March | 97898472.87 | 2752.35 | 19-MAR-16:01 | 34.25 |
April | 0.120702E+09 | 2530.87 | 02-APR-16:01 | 33.25 |
May | 0.108618E+09 | 2823.83 | 29-MAY-16:01 | 34.50 |
June | 0.106651E+09 | 2759.21 | 11-JUN-16:01 | 34.25 |
July | 86475086.75 | 2402.29 | 15-JUL-17:02 | 32.83 |
August | 76098828.23 | 2376.11 | 27-AUG-16:02 | 32.83 |
September | 83033767.88 | 2384.91 | 04-SEP-16:02 | 32.83 |
October | 70234075.94 | 1592.94 | 08-OCT-16:02 | 29.72 |
November | 59675035.83 | 1603.63 | 17-NOV-20:03 | 29.48 |
December | 54247485.08 | 1437.50 | 10-DEC-17:02 | 29.00 |
Annual Sum or Average | 0.101714E+10 | |||
Minimum of Months | 54247485.08 | 1437.50 | 29.00 | |
Maximum of Months | 0.120702E+09 | 2823.83 | 34.50 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 73713384.30 | 1907.90 | 29-JAN-17:02 | 30.83 |
February | 82829610.53 | 1828.23 | 12-FEB-17:02 | 30.67 |
March | 99493336.96 | 2755.17 | 19-MAR-16:01 | 34.25 |
April | 0.121873E+09 | 2533.40 | 02-APR-16:01 | 33.25 |
May | 0.110036E+09 | 2826.23 | 29-MAY-16:01 | 34.50 |
June | 0.107864E+09 | 2761.69 | 11-JUN-16:01 | 34.25 |
July | 87762735.71 | 2407.09 | 15-JUL-17:02 | 32.83 |
August | 78279581.26 | 2379.70 | 27-AUG-16:02 | 32.83 |
September | 85133168.08 | 2387.96 | 04-SEP-16:02 | 32.83 |
October | 72319022.82 | 1597.24 | 08-OCT-16:02 | 29.72 |
November | 61396245.47 | 1609.30 | 17-NOV-20:03 | 29.48 |
December | 55642532.46 | 1441.65 | 10-DEC-17:02 | 29.00 |
Annual Sum or Average | 0.103634E+10 | |||
Minimum of Months | 55642532.46 | 1441.65 | 29.00 | |
Maximum of Months | 0.121873E+09 | 2826.23 | 34.50 |
Report: ZoneHeatingSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 71858046.73 | 4048.17 | 11-JAN-08:05 | 29.33 |
February | 91945083.01 | 3673.85 | 12-FEB-17:02 | 30.67 |
March | 93752945.23 | 5514.17 | 19-MAR-16:01 | 34.25 |
April | 0.106190E+09 | 5063.29 | 02-APR-16:01 | 33.25 |
May | 99409315.48 | 5655.62 | 29-MAY-16:01 | 34.50 |
June | 79875465.41 | 5527.83 | 11-JUN-16:01 | 34.25 |
July | 0.111754E+09 | 4820.03 | 15-JUL-17:02 | 32.83 |
August | 73510671.60 | 4772.38 | 27-AUG-16:02 | 32.83 |
September | 83084684.96 | 4785.33 | 04-SEP-16:02 | 32.83 |
October | 82862679.72 | 3352.57 | 29-OCT-08:07 | 28.33 |
November | 62267802.05 | 3495.64 | 23-NOV-09:06 | 28.57 |
December | 71815952.23 | 3436.19 | 31-DEC-09:06 | 28.47 |
Annual Sum or Average | 0.102833E+10 | |||
Minimum of Months | 62267802.05 | 3352.57 | 28.33 | |
Maximum of Months | 0.111754E+09 | 5655.62 | 34.50 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 36802619.31 | 2109.65 | 11-JAN-08:05 | 29.33 |
February | 44180564.45 | 1844.40 | 12-FEB-17:02 | 30.67 |
March | 46641463.11 | 2764.56 | 19-MAR-16:01 | 34.25 |
April | 52013423.72 | 2540.74 | 02-APR-16:01 | 33.25 |
May | 49871126.73 | 2833.95 | 29-MAY-16:01 | 34.50 |
June | 39532449.34 | 2770.93 | 11-JUN-16:01 | 34.25 |
July | 56837965.62 | 2426.51 | 15-JUL-17:02 | 32.83 |
August | 35731526.89 | 2392.92 | 27-AUG-16:02 | 32.83 |
September | 42681101.85 | 2399.01 | 04-SEP-16:02 | 32.83 |
October | 41384510.96 | 1686.90 | 29-OCT-08:07 | 28.33 |
November | 30268065.92 | 1703.16 | 23-NOV-09:06 | 28.57 |
December | 34888478.30 | 1715.05 | 31-DEC-09:06 | 28.47 |
Annual Sum or Average | 0.510833E+09 | |||
Minimum of Months | 30268065.92 | 1686.90 | 28.33 | |
Maximum of Months | 56837965.62 | 2833.95 | 34.50 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 36924018.04 | 2106.90 | 11-JAN-08:05 | 29.33 |
February | 44158936.42 | 1845.33 | 12-FEB-17:02 | 30.67 |
March | 46755391.42 | 2765.02 | 19-MAR-16:01 | 34.25 |
April | 52146523.75 | 2541.07 | 02-APR-16:01 | 33.25 |
May | 50020541.00 | 2834.31 | 29-MAY-16:01 | 34.50 |
June | 39760825.44 | 2771.35 | 11-JUN-16:01 | 34.25 |
July | 56967521.94 | 2427.29 | 15-JUL-17:02 | 32.83 |
August | 35790782.28 | 2393.42 | 27-AUG-16:02 | 32.83 |
September | 42853918.58 | 2399.48 | 04-SEP-16:02 | 32.83 |
October | 40906337.79 | 1682.24 | 29-OCT-08:07 | 28.33 |
November | 30456280.08 | 1696.42 | 23-NOV-09:06 | 28.57 |
December | 34984256.70 | 1709.68 | 31-DEC-09:06 | 28.47 |
Annual Sum or Average | 0.511725E+09 | |||
Minimum of Months | 30456280.08 | 1682.24 | 28.33 | |
Maximum of Months | 56967521.94 | 2834.31 | 34.50 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 36847325.08 | 2140.55 | 11-JAN-08:05 | 29.33 |
February | 43335209.69 | 1844.62 | 12-FEB-17:02 | 30.67 |
March | 47877505.24 | 2763.35 | 19-MAR-16:01 | 34.25 |
April | 52552571.24 | 2539.14 | 02-APR-16:01 | 33.25 |
May | 50565870.06 | 2832.18 | 29-MAY-16:01 | 34.50 |
June | 40182679.86 | 2768.75 | 11-JUN-16:01 | 34.25 |
July | 58005751.33 | 2425.19 | 15-JUL-17:02 | 32.83 |
August | 36795846.48 | 2391.08 | 27-AUG-16:02 | 32.83 |
September | 44079156.40 | 2396.96 | 04-SEP-16:02 | 32.83 |
October | 41905342.89 | 1735.94 | 08-OCT-08:06 | 28.25 |
November | 31027731.20 | 1727.99 | 11-NOV-09:05 | 28.23 |
December | 35098645.98 | 1690.41 | 31-DEC-09:06 | 28.47 |
Annual Sum or Average | 0.518274E+09 | |||
Minimum of Months | 31027731.20 | 1690.41 | 28.23 | |
Maximum of Months | 58005751.33 | 2832.18 | 34.50 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 33254864.52 | 2321.70 | 11-JAN-08:05 | 29.33 |
February | 37338130.49 | 1803.47 | 12-FEB-17:02 | 30.67 |
March | 40848406.98 | 2723.65 | 19-MAR-16:01 | 34.25 |
April | 47397260.45 | 2501.94 | 02-APR-16:01 | 33.25 |
May | 46148689.35 | 2789.76 | 29-MAY-16:01 | 34.50 |
June | 36201556.83 | 2722.06 | 11-JUN-16:01 | 34.25 |
July | 51481567.53 | 2373.86 | 15-JUL-17:02 | 32.83 |
August | 32137645.50 | 2340.23 | 27-AUG-16:02 | 32.83 |
September | 39744782.16 | 2347.94 | 04-SEP-16:02 | 32.83 |
October | 35625458.78 | 1775.93 | 06-OCT-07:05 | 27.50 |
November | 26063620.60 | 1884.16 | 23-NOV-09:06 | 28.57 |
December | 30479566.93 | 1846.19 | 09-DEC-08:05 | 27.33 |
Annual Sum or Average | 0.456722E+09 | |||
Minimum of Months | 26063620.60 | 1775.93 | 27.33 | |
Maximum of Months | 51481567.53 | 2789.76 | 34.50 |
Report: ZoneElectricSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.739462E+10 | 4621.63 | 01-JAN-10:09 | 0.222596E+10 | 1343.25 | 01-JAN-10:09 |
February | 0.668410E+10 | 4621.63 | 01-FEB-10:09 | 0.201408E+10 | 1343.25 | 01-FEB-10:09 |
March | 0.740180E+10 | 4621.63 | 01-MAR-10:09 | 0.223295E+10 | 1343.25 | 01-MAR-10:09 |
April | 0.716384E+10 | 4621.63 | 01-APR-09:09 | 0.215748E+10 | 1343.25 | 01-APR-09:09 |
May | 0.739462E+10 | 4621.63 | 01-MAY-09:09 | 0.222596E+10 | 1343.25 | 01-MAY-09:09 |
June | 0.716485E+10 | 4621.63 | 01-JUN-09:09 | 0.216232E+10 | 1343.25 | 01-JUN-09:09 |
July | 0.740069E+10 | 4621.63 | 01-JUL-09:09 | 0.222811E+10 | 1343.25 | 01-JUL-09:09 |
August | 0.739513E+10 | 4621.63 | 01-AUG-09:09 | 0.222838E+10 | 1343.25 | 01-AUG-09:09 |
September | 0.717041E+10 | 4621.63 | 01-SEP-09:09 | 0.216205E+10 | 1343.25 | 01-SEP-09:09 |
October | 0.739462E+10 | 4621.63 | 01-OCT-09:09 | 0.222596E+10 | 1343.25 | 01-OCT-09:09 |
November | 0.714323E+10 | 4621.63 | 01-NOV-09:09 | 0.215077E+10 | 1343.25 | 01-NOV-09:09 |
December | 0.740776E+10 | 4621.63 | 01-DEC-10:09 | 0.223509E+10 | 1343.25 | 01-DEC-10:09 |
Annual Sum or Average | 0.871157E+11 | 0.262491E+11 | ||||
Minimum of Months | 0.668410E+10 | 4621.63 | 0.201408E+10 | 1343.25 | ||
Maximum of Months | 0.740776E+10 | 4621.63 | 0.223509E+10 | 1343.25 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.451584E+10 | 2827.07 | 01-JAN-10:09 | 0.111298E+10 | 671.63 | 01-JAN-10:09 |
February | 0.408193E+10 | 2827.07 | 01-FEB-10:09 | 0.100704E+10 | 671.63 | 01-FEB-10:09 |
March | 0.452026E+10 | 2827.07 | 01-MAR-10:09 | 0.111647E+10 | 671.63 | 01-MAR-10:09 |
April | 0.437489E+10 | 2827.07 | 01-APR-09:09 | 0.107874E+10 | 671.63 | 01-APR-09:09 |
May | 0.451584E+10 | 2827.07 | 01-MAY-09:09 | 0.111298E+10 | 671.63 | 01-MAY-09:09 |
June | 0.437556E+10 | 2827.07 | 01-JUN-09:09 | 0.108116E+10 | 671.63 | 01-JUN-09:09 |
July | 0.451952E+10 | 2827.07 | 01-JUL-09:09 | 0.111405E+10 | 671.63 | 01-JUL-09:09 |
August | 0.451617E+10 | 2827.07 | 01-AUG-09:09 | 0.111419E+10 | 671.63 | 01-AUG-09:09 |
September | 0.437891E+10 | 2827.07 | 01-SEP-09:09 | 0.108102E+10 | 671.63 | 01-SEP-09:09 |
October | 0.451584E+10 | 2827.07 | 01-OCT-09:09 | 0.111298E+10 | 671.63 | 01-OCT-09:09 |
November | 0.436230E+10 | 2827.07 | 01-NOV-09:09 | 0.107538E+10 | 671.63 | 01-NOV-09:09 |
December | 0.452388E+10 | 2827.07 | 01-DEC-10:09 | 0.111755E+10 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.532009E+11 | 0.131245E+11 | ||||
Minimum of Months | 0.408193E+10 | 2827.07 | 0.100704E+10 | 671.63 | ||
Maximum of Months | 0.452388E+10 | 2827.07 | 0.111755E+10 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.317044E+10 | 2555.22 | 01-JAN-10:09 | 0.879849E+09 | 671.63 | 01-JAN-10:09 |
February | 0.287181E+10 | 2555.22 | 01-FEB-09:09 | 0.796766E+09 | 671.63 | 01-FEB-09:09 |
March | 0.324295E+10 | 2555.22 | 01-MAR-09:09 | 0.898128E+09 | 671.63 | 01-MAR-09:09 |
April | 0.307694E+10 | 2555.22 | 01-APR-08:09 | 0.853677E+09 | 671.63 | 01-APR-08:09 |
May | 0.320669E+10 | 2555.22 | 01-MAY-08:09 | 0.888989E+09 | 671.63 | 01-MAY-08:09 |
June | 0.313132E+10 | 2555.22 | 01-JUN-08:09 | 0.867387E+09 | 671.63 | 01-JUN-08:09 |
July | 0.315231E+10 | 2555.22 | 01-JUL-08:09 | 0.875279E+09 | 671.63 | 01-JUL-08:09 |
August | 0.324295E+10 | 2555.22 | 01-AUG-08:09 | 0.898128E+09 | 671.63 | 01-AUG-08:09 |
September | 0.307694E+10 | 2555.22 | 01-SEP-08:09 | 0.853677E+09 | 671.63 | 01-SEP-08:09 |
October | 0.317044E+10 | 2555.22 | 01-OCT-09:09 | 0.879849E+09 | 671.63 | 01-OCT-09:09 |
November | 0.307694E+10 | 2555.22 | 01-NOV-08:09 | 0.853679E+09 | 671.63 | 01-NOV-08:09 |
December | 0.315231E+10 | 2555.22 | 01-DEC-09:09 | 0.875279E+09 | 671.63 | 01-DEC-09:09 |
Annual Sum or Average | 0.375720E+11 | 0.104207E+11 | ||||
Minimum of Months | 0.287181E+10 | 2555.22 | 0.796766E+09 | 671.63 | ||
Maximum of Months | 0.324295E+10 | 2555.22 | 0.898128E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.317044E+10 | 2555.22 | 01-JAN-10:09 | 0.879849E+09 | 671.63 | 01-JAN-10:09 |
February | 0.287181E+10 | 2555.22 | 01-FEB-09:09 | 0.796766E+09 | 671.63 | 01-FEB-09:09 |
March | 0.324295E+10 | 2555.22 | 01-MAR-09:09 | 0.898128E+09 | 671.63 | 01-MAR-09:09 |
April | 0.307694E+10 | 2555.22 | 01-APR-08:09 | 0.853677E+09 | 671.63 | 01-APR-08:09 |
May | 0.320669E+10 | 2555.22 | 01-MAY-08:09 | 0.888989E+09 | 671.63 | 01-MAY-08:09 |
June | 0.313132E+10 | 2555.22 | 01-JUN-08:09 | 0.867387E+09 | 671.63 | 01-JUN-08:09 |
July | 0.315231E+10 | 2555.22 | 01-JUL-08:09 | 0.875279E+09 | 671.63 | 01-JUL-08:09 |
August | 0.324295E+10 | 2555.22 | 01-AUG-08:09 | 0.898128E+09 | 671.63 | 01-AUG-08:09 |
September | 0.307694E+10 | 2555.22 | 01-SEP-08:09 | 0.853677E+09 | 671.63 | 01-SEP-08:09 |
October | 0.317044E+10 | 2555.22 | 01-OCT-09:09 | 0.879849E+09 | 671.63 | 01-OCT-09:09 |
November | 0.307694E+10 | 2555.22 | 01-NOV-08:09 | 0.853679E+09 | 671.63 | 01-NOV-08:09 |
December | 0.315231E+10 | 2555.22 | 01-DEC-09:09 | 0.875279E+09 | 671.63 | 01-DEC-09:09 |
Annual Sum or Average | 0.375720E+11 | 0.104207E+11 | ||||
Minimum of Months | 0.287181E+10 | 2555.22 | 0.796766E+09 | 671.63 | ||
Maximum of Months | 0.324295E+10 | 2555.22 | 0.898128E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.317044E+10 | 2555.22 | 01-JAN-10:09 | 0.879849E+09 | 671.63 | 01-JAN-10:09 |
February | 0.287181E+10 | 2555.22 | 01-FEB-09:09 | 0.796766E+09 | 671.63 | 01-FEB-09:09 |
March | 0.324295E+10 | 2555.22 | 01-MAR-09:09 | 0.898128E+09 | 671.63 | 01-MAR-09:09 |
April | 0.307694E+10 | 2555.22 | 01-APR-08:09 | 0.853677E+09 | 671.63 | 01-APR-08:09 |
May | 0.320669E+10 | 2555.22 | 01-MAY-08:09 | 0.888989E+09 | 671.63 | 01-MAY-08:09 |
June | 0.313132E+10 | 2555.22 | 01-JUN-08:09 | 0.867387E+09 | 671.63 | 01-JUN-08:09 |
July | 0.315231E+10 | 2555.22 | 01-JUL-08:09 | 0.875279E+09 | 671.63 | 01-JUL-08:09 |
August | 0.324295E+10 | 2555.22 | 01-AUG-08:09 | 0.898128E+09 | 671.63 | 01-AUG-08:09 |
September | 0.307694E+10 | 2555.22 | 01-SEP-08:09 | 0.853677E+09 | 671.63 | 01-SEP-08:09 |
October | 0.317044E+10 | 2555.22 | 01-OCT-09:09 | 0.879849E+09 | 671.63 | 01-OCT-09:09 |
November | 0.307694E+10 | 2555.22 | 01-NOV-08:09 | 0.853679E+09 | 671.63 | 01-NOV-08:09 |
December | 0.315231E+10 | 2555.22 | 01-DEC-09:09 | 0.875279E+09 | 671.63 | 01-DEC-09:09 |
Annual Sum or Average | 0.375720E+11 | 0.104207E+11 | ||||
Minimum of Months | 0.287181E+10 | 2555.22 | 0.796766E+09 | 671.63 | ||
Maximum of Months | 0.324295E+10 | 2555.22 | 0.898128E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.313454E+10 | 2726.96 | 01-JAN-11:09 | 0.161799E+10 | 1343.25 | 01-JAN-11:09 |
February | 0.283982E+10 | 2726.96 | 01-FEB-10:09 | 0.146554E+10 | 1343.25 | 01-FEB-10:09 |
March | 0.321092E+10 | 2726.96 | 01-MAR-10:09 | 0.165455E+10 | 1343.25 | 01-MAR-10:09 |
April | 0.304266E+10 | 2726.96 | 01-APR-09:09 | 0.157022E+10 | 1343.25 | 01-APR-09:09 |
May | 0.317273E+10 | 2726.96 | 01-MAY-09:09 | 0.163627E+10 | 1343.25 | 01-MAY-09:09 |
June | 0.309995E+10 | 2726.96 | 01-JUN-09:09 | 0.159764E+10 | 1343.25 | 01-JUN-09:09 |
July | 0.311545E+10 | 2726.96 | 01-JUL-09:09 | 0.160885E+10 | 1343.25 | 01-JUL-09:09 |
August | 0.321092E+10 | 2726.96 | 01-AUG-09:09 | 0.165455E+10 | 1343.25 | 01-AUG-09:09 |
September | 0.304266E+10 | 2726.96 | 01-SEP-09:09 | 0.157022E+10 | 1343.25 | 01-SEP-09:09 |
October | 0.313454E+10 | 2726.96 | 01-OCT-10:09 | 0.161799E+10 | 1343.25 | 01-OCT-10:09 |
November | 0.304266E+10 | 2726.96 | 01-NOV-09:09 | 0.157022E+10 | 1343.25 | 01-NOV-09:09 |
December | 0.311545E+10 | 2726.96 | 01-DEC-10:09 | 0.160885E+10 | 1343.25 | 01-DEC-10:09 |
Annual Sum or Average | 0.371623E+11 | 0.191729E+11 | ||||
Minimum of Months | 0.283982E+10 | 2726.96 | 0.146554E+10 | 1343.25 | ||
Maximum of Months | 0.321092E+10 | 2726.96 | 0.165455E+10 | 1343.25 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.161274E+10 | 1404.46 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.146111E+10 | 1404.46 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.165211E+10 | 1404.46 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.156548E+10 | 1404.46 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.163243E+10 | 1404.46 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.159501E+10 | 1404.46 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.160290E+10 | 1404.46 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.165211E+10 | 1404.46 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.156548E+10 | 1404.46 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.161274E+10 | 1404.46 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.156548E+10 | 1404.46 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.160290E+10 | 1404.46 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.191205E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.146111E+10 | 1404.46 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.165211E+10 | 1404.46 | 0.827277E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.161274E+10 | 1404.46 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.146111E+10 | 1404.46 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.165211E+10 | 1404.46 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.156548E+10 | 1404.46 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.163243E+10 | 1404.46 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.159501E+10 | 1404.46 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.160290E+10 | 1404.46 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.165211E+10 | 1404.46 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.156548E+10 | 1404.46 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.161274E+10 | 1404.46 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.156548E+10 | 1404.46 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.160290E+10 | 1404.46 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.191205E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.146111E+10 | 1404.46 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.165211E+10 | 1404.46 | 0.827277E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.161274E+10 | 1404.46 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.146111E+10 | 1404.46 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.165211E+10 | 1404.46 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.156548E+10 | 1404.46 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.163243E+10 | 1404.46 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.159501E+10 | 1404.46 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.160290E+10 | 1404.46 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.165211E+10 | 1404.46 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.156548E+10 | 1404.46 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.161274E+10 | 1404.46 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.156548E+10 | 1404.46 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.160290E+10 | 1404.46 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.191205E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.146111E+10 | 1404.46 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.165211E+10 | 1404.46 | 0.827277E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.161274E+10 | 1404.46 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.146111E+10 | 1404.46 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.165211E+10 | 1404.46 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.156548E+10 | 1404.46 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.163243E+10 | 1404.46 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.159501E+10 | 1404.46 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.160290E+10 | 1404.46 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.165211E+10 | 1404.46 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.156548E+10 | 1404.46 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.161274E+10 | 1404.46 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.156548E+10 | 1404.46 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.160290E+10 | 1404.46 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.191205E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.146111E+10 | 1404.46 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.165211E+10 | 1404.46 | 0.827277E+09 | 671.63 |
Report: SpaceGainsMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.338624E+10 | 0.739462E+10 | 0.222596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222818E+10 | 48136639.84 |
February | 0.305697E+10 | 0.668410E+10 | 0.201408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.240582E+10 | 11207700.90 |
March | 0.335708E+10 | 0.740180E+10 | 0.223295E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.290830E+10 | 16172555.27 |
April | 0.327081E+10 | 0.716384E+10 | 0.215748E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.288925E+10 | 2590208.65 |
May | 0.336680E+10 | 0.739462E+10 | 0.222596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.292194E+10 | 7344567.25 |
June | 0.325380E+10 | 0.716485E+10 | 0.216232E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.285310E+10 | 8101334.78 |
July | 0.339353E+10 | 0.740069E+10 | 0.222811E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.214171E+10 | 6641736.83 |
August | 0.334857E+10 | 0.739513E+10 | 0.222838E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.217661E+10 | 15883799.48 |
September | 0.327932E+10 | 0.717041E+10 | 0.216205E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.214193E+10 | 7191713.05 |
October | 0.338624E+10 | 0.739462E+10 | 0.222596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188710E+10 | 15761607.82 |
November | 0.327446E+10 | 0.714323E+10 | 0.215077E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182133E+10 | 21446237.15 |
December | 0.340325E+10 | 0.740776E+10 | 0.223509E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.198108E+10 | 47513361.23 |
Annual Sum or Average | 0.397770E+11 | 0.871157E+11 | 0.262491E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.283564E+11 | 0.207991E+09 |
Minimum of Months | 0.305697E+10 | 0.668410E+10 | 0.201408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182133E+10 | 2590208.65 |
Maximum of Months | 0.340325E+10 | 0.740776E+10 | 0.223509E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.292194E+10 | 48136639.84 |
Report: SpaceGainsMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.169307E+10 | 0.451584E+10 | 0.111298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125639E+10 | 15974485.98 |
February | 0.152844E+10 | 0.408193E+10 | 0.100704E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135236E+10 | 3560085.40 |
March | 0.167849E+10 | 0.452026E+10 | 0.111647E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162385E+10 | 4744319.37 |
April | 0.163536E+10 | 0.437489E+10 | 0.107874E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161378E+10 | 867780.55 |
May | 0.168335E+10 | 0.451584E+10 | 0.111298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162691E+10 | 2184684.83 |
June | 0.162685E+10 | 0.437556E+10 | 0.108116E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159200E+10 | 2370434.32 |
July | 0.169671E+10 | 0.451952E+10 | 0.111405E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120050E+10 | 2042050.65 |
August | 0.167424E+10 | 0.451617E+10 | 0.111419E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121455E+10 | 5575084.93 |
September | 0.163961E+10 | 0.437891E+10 | 0.108102E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120293E+10 | 2197297.60 |
October | 0.169307E+10 | 0.451584E+10 | 0.111298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106111E+10 | 5276137.23 |
November | 0.163718E+10 | 0.436230E+10 | 0.107538E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102714E+10 | 6634753.88 |
December | 0.170157E+10 | 0.452388E+10 | 0.111755E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111913E+10 | 14246621.21 |
Annual Sum or Average | 0.198880E+11 | 0.532009E+11 | 0.131245E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158906E+11 | 65673735.95 |
Minimum of Months | 0.152844E+10 | 0.408193E+10 | 0.100704E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102714E+10 | 867780.55 |
Maximum of Months | 0.170157E+10 | 0.452388E+10 | 0.111755E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162691E+10 | 15974485.98 |
Report: SpaceGainsMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.317044E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123083E+10 | 21151329.42 |
February | 0.914877E+09 | 0.287181E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132852E+10 | 5266313.36 |
March | 0.103395E+10 | 0.324295E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160033E+10 | 7312296.17 |
April | 0.984131E+09 | 0.307694E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158867E+10 | 1838590.69 |
May | 0.102058E+10 | 0.320669E+10 | 0.888989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160176E+10 | 3967304.44 |
June | 0.998711E+09 | 0.313132E+10 | 0.867387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156964E+10 | 5115532.19 |
July | 0.100600E+10 | 0.315231E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117330E+10 | 5769476.24 |
August | 0.103395E+10 | 0.324295E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119635E+10 | 9507339.13 |
September | 0.984131E+09 | 0.307694E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118153E+10 | 6159468.02 |
October | 0.100722E+10 | 0.317044E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103987E+10 | 11473825.85 |
November | 0.973196E+09 | 0.307694E+10 | 0.853679E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100889E+10 | 11893368.97 |
December | 0.100600E+10 | 0.315231E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109613E+10 | 20998716.43 |
Annual Sum or Average | 0.119700E+11 | 0.375720E+11 | 0.104207E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156158E+11 | 0.110454E+09 |
Minimum of Months | 0.914877E+09 | 0.287181E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100889E+10 | 1838590.69 |
Maximum of Months | 0.103395E+10 | 0.324295E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160176E+10 | 21151329.42 |
Report: SpaceGainsMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.317044E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123073E+10 | 21619909.86 |
February | 0.914877E+09 | 0.287181E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132829E+10 | 5553497.96 |
March | 0.103395E+10 | 0.324295E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159976E+10 | 7775481.81 |
April | 0.984131E+09 | 0.307694E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158781E+10 | 1940613.07 |
May | 0.102058E+10 | 0.320669E+10 | 0.888989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160085E+10 | 4170351.43 |
June | 0.998711E+09 | 0.313132E+10 | 0.867387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156882E+10 | 5364134.42 |
July | 0.100600E+10 | 0.315231E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117294E+10 | 6066632.58 |
August | 0.103395E+10 | 0.324295E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119603E+10 | 9837067.89 |
September | 0.984131E+09 | 0.307694E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118122E+10 | 6391210.15 |
October | 0.100722E+10 | 0.317044E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103974E+10 | 11827004.35 |
November | 0.973196E+09 | 0.307694E+10 | 0.853679E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100878E+10 | 12125972.80 |
December | 0.100600E+10 | 0.315231E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109607E+10 | 21308695.21 |
Annual Sum or Average | 0.119700E+11 | 0.375720E+11 | 0.104207E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156110E+11 | 0.113981E+09 |
Minimum of Months | 0.914877E+09 | 0.287181E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100878E+10 | 1940613.07 |
Maximum of Months | 0.103395E+10 | 0.324295E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160085E+10 | 21619909.86 |
Report: SpaceGainsMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.317044E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123108E+10 | 20575426.79 |
February | 0.914877E+09 | 0.287181E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132877E+10 | 4934580.95 |
March | 0.103395E+10 | 0.324295E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160072E+10 | 6709182.53 |
April | 0.984131E+09 | 0.307694E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158923E+10 | 1685149.93 |
May | 0.102058E+10 | 0.320669E+10 | 0.888989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160201E+10 | 3755828.28 |
June | 0.998711E+09 | 0.313132E+10 | 0.867387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156992E+10 | 4953741.97 |
July | 0.100600E+10 | 0.315231E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117355E+10 | 5546515.75 |
August | 0.103395E+10 | 0.324295E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119664E+10 | 8832915.05 |
September | 0.984131E+09 | 0.307694E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118178E+10 | 5786068.62 |
October | 0.100722E+10 | 0.317044E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104011E+10 | 10953646.51 |
November | 0.973196E+09 | 0.307694E+10 | 0.853679E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100914E+10 | 11304607.01 |
December | 0.100600E+10 | 0.315231E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109634E+10 | 20298406.99 |
Annual Sum or Average | 0.119700E+11 | 0.375720E+11 | 0.104207E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156193E+11 | 0.105336E+09 |
Minimum of Months | 0.914877E+09 | 0.287181E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100914E+10 | 1685149.93 |
Maximum of Months | 0.103395E+10 | 0.324295E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160201E+10 | 20575426.79 |
Report: SpaceGainsMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.344359E+10 | 0.313454E+10 | 0.161799E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.216139E+10 | 41121217.04 |
February | 0.313522E+10 | 0.283982E+10 | 0.146554E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.233189E+10 | 9288783.45 |
March | 0.355148E+10 | 0.321092E+10 | 0.165455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.281535E+10 | 10980233.58 |
April | 0.338259E+10 | 0.304266E+10 | 0.157022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.279594E+10 | 2600254.79 |
May | 0.349753E+10 | 0.317273E+10 | 0.163627E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.281791E+10 | 6194331.84 |
June | 0.343071E+10 | 0.309995E+10 | 0.159764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.276091E+10 | 8755808.31 |
July | 0.344942E+10 | 0.311545E+10 | 0.160885E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205939E+10 | 9348046.29 |
August | 0.355148E+10 | 0.321092E+10 | 0.165455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.210337E+10 | 14131414.89 |
September | 0.338259E+10 | 0.304266E+10 | 0.157022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.207362E+10 | 9584882.93 |
October | 0.344359E+10 | 0.313454E+10 | 0.161799E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182366E+10 | 19273604.54 |
November | 0.331698E+10 | 0.304266E+10 | 0.157022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.176898E+10 | 20814987.36 |
December | 0.344942E+10 | 0.311545E+10 | 0.160885E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192132E+10 | 39547026.60 |
Annual Sum or Average | 0.410346E+11 | 0.371623E+11 | 0.191729E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.274337E+11 | 0.191641E+09 |
Minimum of Months | 0.313522E+10 | 0.283982E+10 | 0.146554E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.176898E+10 | 2600254.79 |
Maximum of Months | 0.355148E+10 | 0.321092E+10 | 0.165455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.281791E+10 | 41121217.04 |
Report: SpaceGainsMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.161274E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123348E+10 | 20560115.37 |
February | 0.156756E+10 | 0.146111E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133032E+10 | 4434840.38 |
March | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160490E+10 | 5086384.70 |
April | 0.169125E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159361E+10 | 1240358.34 |
May | 0.174872E+10 | 0.163243E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160537E+10 | 2889368.55 |
June | 0.171530E+10 | 0.159501E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157359E+10 | 4239609.95 |
July | 0.172466E+10 | 0.160290E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117467E+10 | 4558253.14 |
August | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119886E+10 | 6992637.81 |
September | 0.169125E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118292E+10 | 4687950.64 |
October | 0.172174E+10 | 0.161274E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104038E+10 | 9539366.20 |
November | 0.165844E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100963E+10 | 10368543.75 |
December | 0.172466E+10 | 0.160290E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109674E+10 | 19321334.10 |
Annual Sum or Average | 0.205167E+11 | 0.191205E+11 | 0.958644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156445E+11 | 93918762.92 |
Minimum of Months | 0.156756E+10 | 0.146111E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100963E+10 | 1240358.34 |
Maximum of Months | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160537E+10 | 20560115.37 |
Report: SpaceGainsMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.161274E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123359E+10 | 20367560.24 |
February | 0.156756E+10 | 0.146111E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133046E+10 | 4361875.88 |
March | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160513E+10 | 4989950.28 |
April | 0.169125E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159385E+10 | 1211963.81 |
May | 0.174872E+10 | 0.163243E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160558E+10 | 2848854.36 |
June | 0.171530E+10 | 0.159501E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157380E+10 | 4193538.07 |
July | 0.172466E+10 | 0.160290E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117481E+10 | 4494808.89 |
August | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119902E+10 | 6897270.53 |
September | 0.169125E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118305E+10 | 4624744.67 |
October | 0.172174E+10 | 0.161274E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104050E+10 | 9404101.59 |
November | 0.165844E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100974E+10 | 10236058.09 |
December | 0.172466E+10 | 0.160290E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109684E+10 | 19121325.81 |
Annual Sum or Average | 0.205167E+11 | 0.191205E+11 | 0.958644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156464E+11 | 92752052.23 |
Minimum of Months | 0.156756E+10 | 0.146111E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100974E+10 | 1211963.81 |
Maximum of Months | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160558E+10 | 20367560.24 |
Report: SpaceGainsMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.161274E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123361E+10 | 20059025.82 |
February | 0.156756E+10 | 0.146111E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133043E+10 | 4259253.25 |
March | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160514E+10 | 4847042.03 |
April | 0.169125E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159367E+10 | 1173902.64 |
May | 0.174872E+10 | 0.163243E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160533E+10 | 2801283.17 |
June | 0.171530E+10 | 0.159501E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157355E+10 | 4170336.60 |
July | 0.172466E+10 | 0.160290E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117465E+10 | 4490932.79 |
August | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119899E+10 | 6722048.14 |
September | 0.169125E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118296E+10 | 4581016.18 |
October | 0.172174E+10 | 0.161274E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104053E+10 | 9235938.58 |
November | 0.165844E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100982E+10 | 9982981.78 |
December | 0.172466E+10 | 0.160290E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109686E+10 | 18782004.02 |
Annual Sum or Average | 0.205167E+11 | 0.191205E+11 | 0.958644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156455E+11 | 91105764.99 |
Minimum of Months | 0.156756E+10 | 0.146111E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100982E+10 | 1173902.64 |
Maximum of Months | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160533E+10 | 20059025.82 |
Report: SpaceGainsMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.161274E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125576E+10 | 44091606.84 |
February | 0.156756E+10 | 0.146111E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135904E+10 | 11554423.32 |
March | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165565E+10 | 14638136.36 |
April | 0.169125E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.164511E+10 | 2783840.85 |
May | 0.174872E+10 | 0.163243E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166457E+10 | 8215861.19 |
June | 0.171530E+10 | 0.159501E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162558E+10 | 11095115.98 |
July | 0.172466E+10 | 0.160290E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120411E+10 | 11602813.70 |
August | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123804E+10 | 15748421.10 |
September | 0.169125E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120998E+10 | 11563849.78 |
October | 0.172174E+10 | 0.161274E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106307E+10 | 20452452.18 |
November | 0.165844E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102780E+10 | 21900273.21 |
December | 0.172466E+10 | 0.160290E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111343E+10 | 45677468.75 |
Annual Sum or Average | 0.205167E+11 | 0.191205E+11 | 0.958644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160621E+11 | 0.219324E+09 |
Minimum of Months | 0.156756E+10 | 0.146111E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102780E+10 | 2783840.85 |
Maximum of Months | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166457E+10 | 45677468.75 |
Report: PeakSpaceGainsMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 4050.04 | 01-JAN-13:09 | 4621.63 | 01-JAN-10:09 | 1343.25 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4731.05 | 04-JAN-13:00 | 682.31 | 07-JAN-05:00 |
February | 4050.04 | 03-FEB-13:09 | 4621.63 | 01-FEB-10:09 | 1343.25 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5173.91 | 28-FEB-15:00 | 266.83 | 21-FEB-10:00 |
March | 4050.04 | 03-MAR-13:09 | 4621.63 | 01-MAR-10:09 | 1343.25 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5729.16 | 21-MAR-13:00 | 126.20 | 03-MAR-05:40 |
April | 4050.04 | 01-APR-12:09 | 4621.63 | 01-APR-09:09 | 1343.25 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5251.38 | 01-APR-14:00 | 473.24 | 14-APR-16:00 |
May | 4050.04 | 05-MAY-12:09 | 4621.63 | 01-MAY-09:09 | 1343.25 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6228.77 | 06-MAY-13:00 | 235.33 | 21-MAY-13:00 |
June | 4050.04 | 02-JUN-12:09 | 4621.63 | 01-JUN-09:09 | 1343.25 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5565.03 | 13-JUN-15:00 | 232.33 | 30-JUN-13:00 |
July | 4050.04 | 01-JUL-12:09 | 4621.63 | 01-JUL-09:09 | 1343.25 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4232.33 | 28-JUL-13:00 | 339.57 | 03-JUL-13:00 |
August | 4050.04 | 04-AUG-12:09 | 4621.63 | 01-AUG-09:09 | 1343.25 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4680.03 | 27-AUG-14:00 | 834.24 | 20-AUG-11:10 |
September | 4050.04 | 01-SEP-12:09 | 4621.63 | 01-SEP-09:09 | 1343.25 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4652.55 | 06-SEP-14:00 | 441.40 | 15-SEP-17:00 |
October | 4050.04 | 01-OCT-12:09 | 4621.63 | 01-OCT-09:09 | 1343.25 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4209.81 | 04-OCT-14:00 | 427.94 | 30-OCT-17:00 |
November | 4050.04 | 03-NOV-12:09 | 4621.63 | 01-NOV-09:09 | 1343.25 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4758.05 | 18-NOV-13:00 | 171.62 | 25-NOV-08:62 |
December | 4050.04 | 01-DEC-13:09 | 4621.63 | 01-DEC-10:09 | 1343.25 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4174.29 | 07-DEC-14:00 | 257.27 | 21-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 4050.04 | 4621.63 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 4174.29 | 126.20 | |||||
Maximum of Months | 4050.04 | 4621.63 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 6228.77 | 834.24 |
Report: PeakSpaceGainsMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 01-JAN-13:09 | 2827.07 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2661.66 | 04-JAN-13:00 | 207.33 | 07-JAN-05:00 |
February | 2024.96 | 03-FEB-13:09 | 2827.07 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2900.06 | 28-FEB-15:00 | 146.20 | 21-FEB-10:00 |
March | 2024.96 | 03-MAR-13:09 | 2827.07 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3223.19 | 21-MAR-13:00 | 37.18 | 03-MAR-05:40 |
April | 2024.96 | 01-APR-12:09 | 2827.07 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2977.67 | 01-APR-14:00 | 267.91 | 14-APR-16:00 |
May | 2024.96 | 05-MAY-12:09 | 2827.07 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3515.21 | 06-MAY-13:00 | 133.22 | 21-MAY-13:00 |
June | 2024.96 | 02-JUN-12:09 | 2827.07 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3130.85 | 13-JUN-15:00 | 132.37 | 30-JUN-13:00 |
July | 2024.96 | 01-JUL-12:09 | 2827.07 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2400.71 | 15-JUL-16:00 | 189.87 | 03-JUL-13:00 |
August | 2024.96 | 04-AUG-12:09 | 2827.07 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2632.96 | 27-AUG-14:00 | 469.34 | 20-AUG-11:10 |
September | 2024.96 | 01-SEP-12:09 | 2827.07 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2625.67 | 06-SEP-14:00 | 245.32 | 15-SEP-17:00 |
October | 2024.96 | 01-OCT-12:09 | 2827.07 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2375.81 | 04-OCT-14:00 | 241.51 | 30-OCT-17:00 |
November | 2024.96 | 03-NOV-12:09 | 2827.07 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2693.67 | 18-NOV-13:00 | 90.78 | 25-NOV-08:62 |
December | 2024.96 | 01-DEC-13:09 | 2827.07 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2363.18 | 07-DEC-14:00 | 110.73 | 21-DEC-08:62 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 2827.07 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 2363.18 | 37.18 | |||||
Maximum of Months | 2024.96 | 2827.07 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 3515.21 | 469.34 |
Report: PeakSpaceGainsMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 2555.22 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2661.66 | 04-JAN-13:00 | 229.44 | 01-JAN-18:00 |
February | 2024.96 | 04-FEB-13:09 | 2555.22 | 01-FEB-09:09 | 671.63 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2900.06 | 28-FEB-15:00 | 146.20 | 21-FEB-10:00 |
March | 2024.96 | 04-MAR-13:09 | 2555.22 | 01-MAR-09:09 | 671.63 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3223.19 | 21-MAR-13:00 | 77.68 | 05-MAR-18:00 |
April | 2024.96 | 01-APR-12:09 | 2555.22 | 01-APR-08:09 | 671.63 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2977.67 | 01-APR-14:00 | 267.91 | 14-APR-16:00 |
May | 2024.96 | 06-MAY-12:09 | 2555.22 | 01-MAY-08:09 | 671.63 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3515.21 | 06-MAY-13:00 | 133.22 | 21-MAY-13:00 |
June | 2024.96 | 03-JUN-12:09 | 2555.22 | 01-JUN-08:09 | 671.63 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3130.85 | 13-JUN-15:00 | 190.46 | 25-JUN-19:00 |
July | 2024.96 | 01-JUL-12:09 | 2555.22 | 01-JUL-08:09 | 671.63 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2400.71 | 15-JUL-16:00 | 415.28 | 16-JUL-17:00 |
August | 2024.96 | 05-AUG-12:09 | 2555.22 | 01-AUG-08:09 | 671.63 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2632.96 | 27-AUG-14:00 | 469.34 | 20-AUG-11:10 |
September | 2024.96 | 02-SEP-12:09 | 2555.22 | 01-SEP-08:09 | 671.63 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2625.67 | 06-SEP-14:00 | 429.25 | 03-SEP-17:00 |
October | 2024.96 | 07-OCT-12:09 | 2555.22 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2375.81 | 04-OCT-14:00 | 355.40 | 29-OCT-17:00 |
November | 2024.96 | 04-NOV-12:09 | 2555.22 | 01-NOV-08:09 | 671.63 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2693.67 | 18-NOV-13:00 | 501.61 | 26-NOV-18:00 |
December | 2024.96 | 02-DEC-13:09 | 2555.22 | 01-DEC-09:09 | 671.63 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2363.18 | 07-DEC-14:00 | 366.93 | 17-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 2555.22 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 2363.18 | 77.68 | |||||
Maximum of Months | 2024.96 | 2555.22 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 3515.21 | 501.61 |
Report: PeakSpaceGainsMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 2555.22 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2661.66 | 04-JAN-13:00 | 232.16 | 01-JAN-18:00 |
February | 2024.96 | 04-FEB-13:09 | 2555.22 | 01-FEB-09:09 | 671.63 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2900.06 | 28-FEB-15:00 | 146.20 | 21-FEB-10:00 |
March | 2024.96 | 04-MAR-13:09 | 2555.22 | 01-MAR-09:09 | 671.63 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3223.19 | 21-MAR-13:00 | 80.83 | 05-MAR-18:00 |
April | 2024.96 | 01-APR-12:09 | 2555.22 | 01-APR-08:09 | 671.63 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2977.67 | 01-APR-14:00 | 267.91 | 14-APR-16:00 |
May | 2024.96 | 06-MAY-12:09 | 2555.22 | 01-MAY-08:09 | 671.63 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3515.21 | 06-MAY-13:00 | 133.22 | 21-MAY-13:00 |
June | 2024.96 | 03-JUN-12:09 | 2555.22 | 01-JUN-08:09 | 671.63 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3130.85 | 13-JUN-15:00 | 195.23 | 25-JUN-19:00 |
July | 2024.96 | 01-JUL-12:09 | 2555.22 | 01-JUL-08:09 | 671.63 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2400.71 | 15-JUL-16:00 | 420.08 | 16-JUL-17:00 |
August | 2024.96 | 05-AUG-12:09 | 2555.22 | 01-AUG-08:09 | 671.63 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2632.96 | 27-AUG-14:00 | 469.34 | 20-AUG-11:10 |
September | 2024.96 | 02-SEP-12:09 | 2555.22 | 01-SEP-08:09 | 671.63 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2625.67 | 06-SEP-14:00 | 432.85 | 03-SEP-17:00 |
October | 2024.96 | 07-OCT-12:09 | 2555.22 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2375.81 | 04-OCT-14:00 | 360.51 | 29-OCT-17:00 |
November | 2024.96 | 04-NOV-12:09 | 2555.22 | 01-NOV-08:09 | 671.63 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2693.67 | 18-NOV-13:00 | 501.62 | 26-NOV-18:00 |
December | 2024.96 | 02-DEC-13:09 | 2555.22 | 01-DEC-09:09 | 671.63 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2363.18 | 07-DEC-14:00 | 367.23 | 17-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 2555.22 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 2363.18 | 80.83 | |||||
Maximum of Months | 2024.96 | 2555.22 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 3515.21 | 501.62 |
Report: PeakSpaceGainsMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 2555.22 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2661.66 | 04-JAN-13:00 | 219.31 | 01-JAN-18:00 |
February | 2024.96 | 04-FEB-13:09 | 2555.22 | 01-FEB-09:09 | 671.63 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2900.06 | 28-FEB-15:00 | 146.20 | 21-FEB-10:00 |
March | 2024.96 | 04-MAR-13:09 | 2555.22 | 01-MAR-09:09 | 671.63 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3223.19 | 21-MAR-13:00 | 67.32 | 05-MAR-18:00 |
April | 2024.96 | 01-APR-12:09 | 2555.22 | 01-APR-08:09 | 671.63 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2977.67 | 01-APR-14:00 | 267.91 | 14-APR-16:00 |
May | 2024.96 | 06-MAY-12:09 | 2555.22 | 01-MAY-08:09 | 671.63 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3515.21 | 06-MAY-13:00 | 133.22 | 21-MAY-13:00 |
June | 2024.96 | 03-JUN-12:09 | 2555.22 | 01-JUN-08:09 | 671.63 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3130.85 | 13-JUN-15:00 | 191.12 | 25-JUN-19:00 |
July | 2024.96 | 01-JUL-12:09 | 2555.22 | 01-JUL-08:09 | 671.63 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2400.71 | 15-JUL-16:00 | 407.66 | 16-JUL-17:00 |
August | 2024.96 | 05-AUG-12:09 | 2555.22 | 01-AUG-08:09 | 671.63 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2632.96 | 27-AUG-14:00 | 469.34 | 20-AUG-11:10 |
September | 2024.96 | 02-SEP-12:09 | 2555.22 | 01-SEP-08:09 | 671.63 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2625.67 | 06-SEP-14:00 | 420.14 | 03-SEP-17:00 |
October | 2024.96 | 07-OCT-12:09 | 2555.22 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2375.81 | 04-OCT-14:00 | 347.30 | 29-OCT-17:00 |
November | 2024.96 | 04-NOV-12:09 | 2555.22 | 01-NOV-08:09 | 671.63 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2693.67 | 18-NOV-13:00 | 487.79 | 26-NOV-18:00 |
December | 2024.96 | 02-DEC-13:09 | 2555.22 | 01-DEC-09:09 | 671.63 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2363.18 | 07-DEC-14:00 | 352.43 | 17-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 2555.22 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 2363.18 | 67.32 | |||||
Maximum of Months | 2024.96 | 2555.22 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 3515.21 | 487.79 |
Report: PeakSpaceGainsMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 5400.05 | 07-JAN-15:09 | 2726.96 | 01-JAN-11:09 | 1343.25 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4667.16 | 04-JAN-13:00 | 397.82 | 07-JAN-05:00 |
February | 5400.05 | 04-FEB-15:09 | 2726.96 | 01-FEB-10:09 | 1343.25 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5087.92 | 28-FEB-15:00 | 257.35 | 21-FEB-10:00 |
March | 5400.05 | 04-MAR-15:09 | 2726.96 | 01-MAR-10:09 | 1343.25 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5651.80 | 21-MAR-13:00 | 73.21 | 14-MAR-22:00 |
April | 5400.05 | 01-APR-14:09 | 2726.96 | 01-APR-09:09 | 1343.25 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5215.36 | 01-APR-14:00 | 469.36 | 14-APR-16:00 |
May | 5400.05 | 06-MAY-14:09 | 2726.96 | 01-MAY-09:09 | 1343.25 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6161.06 | 06-MAY-13:00 | 233.39 | 21-MAY-13:00 |
June | 5400.05 | 03-JUN-14:09 | 2726.96 | 01-JUN-09:09 | 1343.25 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5489.88 | 13-JUN-15:00 | 339.29 | 25-JUN-19:00 |
July | 5400.05 | 01-JUL-14:09 | 2726.96 | 01-JUL-09:09 | 1343.25 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4203.86 | 15-JUL-16:00 | 660.25 | 16-JUL-17:00 |
August | 5400.05 | 05-AUG-14:09 | 2726.96 | 01-AUG-09:09 | 1343.25 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4616.83 | 27-AUG-14:00 | 822.98 | 20-AUG-11:10 |
September | 5400.05 | 02-SEP-14:09 | 2726.96 | 01-SEP-09:09 | 1343.25 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4601.97 | 06-SEP-14:00 | 686.11 | 03-SEP-17:00 |
October | 5400.05 | 07-OCT-14:09 | 2726.96 | 01-OCT-10:09 | 1343.25 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4164.05 | 04-OCT-14:00 | 565.02 | 29-OCT-17:00 |
November | 5400.05 | 04-NOV-14:09 | 2726.96 | 01-NOV-09:09 | 1343.25 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4719.01 | 18-NOV-13:00 | 786.93 | 26-NOV-18:00 |
December | 5400.05 | 02-DEC-15:09 | 2726.96 | 01-DEC-10:09 | 1343.25 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4140.04 | 07-DEC-14:00 | 560.03 | 17-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 5400.05 | 2726.96 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 4140.04 | 73.21 | |||||
Maximum of Months | 5400.05 | 2726.96 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 6161.06 | 822.98 |
Report: PeakSpaceGainsMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1404.46 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2661.66 | 04-JAN-13:00 | 199.88 | 15-JAN-09:00 |
February | 2699.95 | 04-FEB-15:09 | 1404.46 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2900.06 | 28-FEB-15:00 | 146.20 | 21-FEB-10:00 |
March | 2699.95 | 04-MAR-15:09 | 1404.46 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3223.19 | 21-MAR-13:00 | 34.79 | 03-MAR-05:40 |
April | 2699.95 | 01-APR-14:09 | 1404.46 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2977.67 | 01-APR-14:00 | 267.91 | 14-APR-16:00 |
May | 2699.95 | 06-MAY-14:09 | 1404.46 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3515.21 | 06-MAY-13:00 | 133.22 | 21-MAY-13:00 |
June | 2699.95 | 03-JUN-14:09 | 1404.46 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3130.85 | 13-JUN-15:00 | 181.74 | 25-JUN-19:00 |
July | 2699.95 | 01-JUL-14:09 | 1404.46 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2400.72 | 15-JUL-16:00 | 358.99 | 16-JUL-17:00 |
August | 2699.95 | 05-AUG-14:09 | 1404.46 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2632.96 | 27-AUG-14:00 | 469.34 | 20-AUG-11:10 |
September | 2699.95 | 02-SEP-14:09 | 1404.46 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2625.67 | 06-SEP-14:00 | 373.24 | 03-SEP-17:00 |
October | 2699.95 | 07-OCT-14:09 | 1404.46 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2375.81 | 04-OCT-14:00 | 293.26 | 29-OCT-17:00 |
November | 2699.95 | 04-NOV-14:09 | 1404.46 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2693.67 | 18-NOV-13:00 | 435.69 | 26-NOV-18:00 |
December | 2699.95 | 02-DEC-15:09 | 1404.46 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2363.18 | 07-DEC-14:00 | 305.71 | 17-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 2363.18 | 34.79 | |||||
Maximum of Months | 2699.95 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 3515.21 | 469.34 |
Report: PeakSpaceGainsMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1404.46 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2661.66 | 04-JAN-13:00 | 198.79 | 15-JAN-09:00 |
February | 2699.95 | 04-FEB-15:09 | 1404.46 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2900.06 | 28-FEB-15:00 | 146.20 | 21-FEB-10:00 |
March | 2699.95 | 04-MAR-15:09 | 1404.46 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3223.19 | 21-MAR-13:00 | 34.55 | 03-MAR-05:50 |
April | 2699.95 | 01-APR-14:09 | 1404.46 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2977.67 | 01-APR-14:00 | 267.91 | 14-APR-16:00 |
May | 2699.95 | 06-MAY-14:09 | 1404.46 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3515.21 | 06-MAY-13:00 | 133.22 | 21-MAY-13:00 |
June | 2699.95 | 03-JUN-14:09 | 1404.46 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3130.85 | 13-JUN-15:00 | 180.91 | 25-JUN-19:00 |
July | 2699.95 | 01-JUL-14:09 | 1404.46 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2400.72 | 15-JUL-16:00 | 356.76 | 16-JUL-17:00 |
August | 2699.95 | 05-AUG-14:09 | 1404.46 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2632.96 | 27-AUG-14:00 | 469.34 | 20-AUG-11:10 |
September | 2699.95 | 02-SEP-14:09 | 1404.46 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2625.67 | 06-SEP-14:00 | 370.93 | 03-SEP-17:00 |
October | 2699.95 | 07-OCT-14:09 | 1404.46 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2375.81 | 04-OCT-14:00 | 289.51 | 29-OCT-17:00 |
November | 2699.95 | 04-NOV-14:09 | 1404.46 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2693.67 | 18-NOV-13:00 | 432.40 | 26-NOV-18:00 |
December | 2699.95 | 02-DEC-15:09 | 1404.46 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2363.18 | 07-DEC-14:00 | 302.86 | 17-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 2363.18 | 34.55 | |||||
Maximum of Months | 2699.95 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 3515.21 | 469.34 |
Report: PeakSpaceGainsMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1404.46 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2661.66 | 04-JAN-13:00 | 198.16 | 24-JAN-09:00 |
February | 2699.95 | 04-FEB-15:09 | 1404.46 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2900.06 | 28-FEB-15:00 | 146.20 | 21-FEB-10:00 |
March | 2699.95 | 04-MAR-15:09 | 1404.46 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3223.19 | 21-MAR-13:00 | 34.08 | 03-MAR-05:50 |
April | 2699.95 | 01-APR-14:09 | 1404.46 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2977.67 | 01-APR-14:00 | 267.91 | 14-APR-16:00 |
May | 2699.95 | 06-MAY-14:09 | 1404.46 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3515.21 | 06-MAY-13:00 | 133.22 | 21-MAY-13:00 |
June | 2699.95 | 03-JUN-14:09 | 1404.46 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3130.85 | 13-JUN-15:00 | 182.35 | 25-JUN-19:00 |
July | 2699.95 | 01-JUL-14:09 | 1404.46 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2400.72 | 15-JUL-16:00 | 360.67 | 16-JUL-17:00 |
August | 2699.95 | 05-AUG-14:09 | 1404.46 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2632.96 | 27-AUG-14:00 | 469.34 | 20-AUG-11:10 |
September | 2699.95 | 02-SEP-14:09 | 1404.46 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2625.67 | 06-SEP-14:00 | 375.72 | 03-SEP-17:00 |
October | 2699.95 | 07-OCT-14:09 | 1404.46 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2375.81 | 04-OCT-14:00 | 293.09 | 29-OCT-17:00 |
November | 2699.95 | 04-NOV-14:09 | 1404.46 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2693.67 | 18-NOV-13:00 | 429.27 | 26-NOV-18:00 |
December | 2699.95 | 02-DEC-15:09 | 1404.46 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2363.18 | 07-DEC-14:00 | 299.47 | 17-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 2363.18 | 34.08 | |||||
Maximum of Months | 2699.95 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 3515.21 | 469.34 |
Report: PeakSpaceGainsMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1404.46 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2725.54 | 04-JAN-13:00 | 447.60 | 07-JAN-05:00 |
February | 2699.95 | 04-FEB-15:09 | 1404.46 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2986.04 | 28-FEB-15:00 | 166.04 | 05-FEB-18:00 |
March | 2699.95 | 04-MAR-15:09 | 1404.46 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3300.56 | 21-MAR-13:00 | 115.86 | 05-MAR-18:00 |
April | 2699.95 | 01-APR-14:09 | 1404.46 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3013.70 | 01-APR-14:00 | 271.80 | 14-APR-16:00 |
May | 2699.95 | 06-MAY-14:09 | 1404.46 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3582.92 | 06-MAY-13:00 | 194.49 | 08-MAY-22:00 |
June | 2699.95 | 03-JUN-14:09 | 1404.46 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3206.00 | 13-JUN-15:00 | 290.98 | 25-JUN-19:00 |
July | 2699.95 | 01-JUL-14:09 | 1404.46 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2438.24 | 28-JUL-13:00 | 478.99 | 16-JUL-17:00 |
August | 2699.95 | 05-AUG-14:09 | 1404.46 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2696.16 | 27-AUG-14:00 | 480.61 | 20-AUG-11:10 |
September | 2699.95 | 02-SEP-14:09 | 1404.46 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2676.25 | 06-SEP-14:00 | 515.69 | 03-SEP-17:00 |
October | 2699.95 | 07-OCT-14:09 | 1404.46 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2421.57 | 04-OCT-14:00 | 412.41 | 09-OCT-17:00 |
November | 2699.95 | 04-NOV-14:09 | 1404.46 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2732.71 | 18-NOV-13:00 | 491.03 | 26-NOV-18:00 |
December | 2699.95 | 02-DEC-15:09 | 1404.46 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2397.44 | 07-DEC-14:00 | 365.76 | 17-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 2397.44 | 115.86 | |||||
Maximum of Months | 2699.95 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 3582.92 | 515.69 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 36517.69 | 23-JAN-08:62 | 1687.52 | 375.00 | 373.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 168.49 |
February | 38293.38 | 21-FEB-08:61 | 2700.03 | 600.00 | 597.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.79 | 0.00 |
March | 34862.66 | 04-MAR-08:62 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 165.36 | 0.00 |
April | 31636.38 | 27-APR-07:01 | 2362.52 | 525.00 | 522.37 | 0.00 | 0.00 | 0.00 | 0.00 | 112.23 | 0.00 |
May | 29216.80 | 09-MAY-07:01 | 2362.52 | 525.00 | 522.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.32 |
June | 30430.55 | 25-JUN-07:02 | 2025.02 | 450.00 | 447.75 | 0.00 | 0.00 | 0.00 | 0.00 | 36.06 | 0.00 |
July | 34401.38 | 09-JUL-07:01 | 2362.52 | 525.00 | 522.37 | 0.00 | 0.00 | 0.00 | 0.00 | 79.31 | 0.00 |
August | 30563.67 | 24-AUG-07:02 | 2025.02 | 450.00 | 447.75 | 0.00 | 0.00 | 0.00 | 0.00 | 41.81 | 0.00 |
September | 31546.53 | 10-SEP-07:01 | 2362.52 | 525.00 | 522.37 | 0.00 | 0.00 | 0.00 | 0.00 | 87.43 | 0.00 |
October | 31259.92 | 08-OCT-07:02 | 2025.02 | 450.00 | 447.75 | 0.00 | 0.00 | 0.00 | 0.00 | 52.75 | 0.00 |
November | 35528.64 | 25-NOV-08:62 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 171.62 |
December | 35903.33 | 27-DEC-08:62 | 1687.52 | 375.00 | 373.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.89 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 29216.80 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 38293.38 | 2700.03 | 600.00 | 597.00 | 0.00 | 0.00 | 0.00 | 0.00 | 165.36 | 171.62 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 21208.60 | 16-JAN-08:62 | 1012.48 | 225.00 | 223.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.04 |
February | 21891.86 | 21-FEB-08:61 | 1349.97 | 300.00 | 298.50 | 0.00 | 0.00 | 0.00 | 0.00 | 39.65 | 0.00 |
March | 20156.13 | 03-MAR-08:62 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 66.71 | 0.00 |
April | 18507.06 | 27-APR-07:01 | 1181.23 | 262.50 | 261.19 | 0.00 | 0.00 | 0.00 | 0.00 | 67.39 | 0.00 |
May | 18131.69 | 12-MAY-07:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 32.30 | 0.00 |
June | 18685.80 | 25-JUN-07:02 | 1012.48 | 225.00 | 223.88 | 0.00 | 0.00 | 0.00 | 0.00 | 24.51 | 0.00 |
July | 19969.23 | 08-JUL-07:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 6.96 | 0.00 |
August | 18511.92 | 24-AUG-07:02 | 1012.48 | 225.00 | 223.88 | 0.00 | 0.00 | 0.00 | 0.00 | 29.86 | 0.00 |
September | 18836.19 | 09-SEP-07:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 5.93 | 0.00 |
October | 19026.68 | 09-OCT-07:01 | 1181.23 | 262.50 | 261.19 | 0.00 | 0.00 | 0.00 | 0.00 | 11.88 | 0.00 |
November | 20608.36 | 25-NOV-08:62 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.78 |
December | 20688.22 | 27-DEC-08:62 | 843.73 | 187.50 | 186.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.89 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 18131.69 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21891.86 | 1349.97 | 300.00 | 298.50 | 0.00 | 0.00 | 0.00 | 0.00 | 67.39 | 100.04 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 18087.27 | 24-JAN-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.96 |
February | 18887.73 | 25-FEB-07:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 |
March | 17241.22 | 04-MAR-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.94 | 0.00 |
April | 15493.98 | 27-APR-06:01 | 0.00 | 262.50 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.53 | 0.00 |
May | 13870.79 | 11-MAY-06:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.73 |
June | 13934.72 | 20-JUN-06:01 | 0.00 | 262.50 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.72 |
July | 15597.75 | 06-JUL-06:01 | 0.00 | 262.50 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 |
August | 14225.75 | 24-AUG-06:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.15 |
September | 13957.31 | 28-SEP-06:01 | 0.00 | 262.50 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 |
October | 13933.95 | 11-OCT-06:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.95 |
November | 16984.09 | 25-NOV-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 |
December | 17704.39 | 27-DEC-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.74 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 13870.79 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18887.73 | 0.00 | 262.50 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.94 | 6.67 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 18163.71 | 24-JAN-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.99 |
February | 18977.14 | 25-FEB-07:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.68 |
March | 17306.90 | 04-MAR-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 | 0.00 |
April | 15572.35 | 27-APR-06:01 | 0.00 | 262.50 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.49 | 0.00 |
May | 13985.19 | 09-MAY-06:01 | 0.00 | 262.50 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.52 |
June | 14056.16 | 20-JUN-06:01 | 0.00 | 262.50 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.86 |
July | 15702.22 | 06-JUL-06:01 | 0.00 | 262.50 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.19 |
August | 14278.43 | 24-AUG-06:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.15 |
September | 14027.22 | 28-SEP-06:01 | 0.00 | 262.50 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.41 |
October | 14022.78 | 11-OCT-06:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.99 |
November | 17057.63 | 25-NOV-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.72 |
December | 17785.44 | 27-DEC-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.78 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 13985.19 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18977.14 | 0.00 | 262.50 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 | 6.72 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 17908.44 | 24-JAN-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.90 |
February | 18688.99 | 25-FEB-07:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.65 |
March | 17029.77 | 04-MAR-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.28 | 0.00 |
April | 15273.24 | 27-APR-06:01 | 0.00 | 262.50 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.63 | 0.00 |
May | 13740.16 | 09-MAY-06:01 | 0.00 | 262.50 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.49 |
June | 13815.67 | 20-JUN-06:01 | 0.00 | 262.50 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.65 |
July | 15428.79 | 06-JUL-06:01 | 0.00 | 262.50 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.14 |
August | 13987.01 | 24-AUG-06:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.13 |
September | 13737.45 | 28-SEP-06:01 | 0.00 | 262.50 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.06 |
October | 13772.83 | 11-OCT-06:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.90 |
November | 16805.48 | 25-NOV-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.55 |
December | 17538.89 | 27-DEC-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.68 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 13737.45 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18688.99 | 0.00 | 262.50 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 1.28 | 6.55 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 32357.52 | 24-JAN-08:62 | 0.00 | 300.00 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 301.46 |
February | 33349.48 | 25-FEB-08:62 | 0.00 | 450.00 | 441.83 | 0.00 | 0.00 | 0.00 | 0.00 | 119.80 | 0.00 |
March | 30728.36 | 04-MAR-08:62 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 150.50 | 0.00 |
April | 27967.75 | 27-APR-07:01 | 0.00 | 525.00 | 515.47 | 0.00 | 0.00 | 0.00 | 0.00 | 116.62 | 0.00 |
May | 26184.57 | 09-MAY-07:01 | 0.00 | 525.00 | 515.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.29 |
June | 27189.19 | 20-JUN-07:01 | 0.00 | 525.00 | 515.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.95 |
July | 29006.37 | 06-JUL-07:02 | 0.00 | 450.00 | 441.83 | 0.00 | 0.00 | 0.00 | 0.00 | 40.69 | 0.00 |
August | 25944.70 | 29-AUG-07:01 | 0.00 | 525.00 | 515.47 | 0.00 | 0.00 | 0.00 | 0.00 | 41.64 | 0.00 |
September | 26254.79 | 06-SEP-07:01 | 0.00 | 525.00 | 515.47 | 0.00 | 0.00 | 0.00 | 0.00 | 104.70 | 0.00 |
October | 26713.03 | 11-OCT-07:02 | 0.00 | 450.00 | 441.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.61 |
November | 30796.53 | 25-NOV-08:62 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 176.89 |
December | 32142.27 | 27-DEC-08:62 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.07 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 25944.70 | 0.00 | 300.00 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 33349.48 | 0.00 | 525.00 | 515.47 | 0.00 | 0.00 | 0.00 | 0.00 | 150.50 | 301.46 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 16503.23 | 28-JAN-08:62 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 114.87 |
February | 17457.07 | 25-FEB-08:62 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 72.17 | 0.00 |
March | 16098.65 | 04-MAR-08:62 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 88.29 | 0.00 |
April | 14678.64 | 27-APR-07:01 | 0.00 | 262.50 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 69.99 | 0.00 |
May | 13728.61 | 09-MAY-07:01 | 0.00 | 262.50 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.22 |
June | 14260.48 | 20-JUN-07:01 | 0.00 | 262.50 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.43 |
July | 15209.81 | 06-JUL-07:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 27.04 | 0.00 |
August | 13635.74 | 29-AUG-07:01 | 0.00 | 262.50 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 27.08 | 0.00 |
September | 13804.86 | 06-SEP-07:01 | 0.00 | 262.50 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 62.81 | 0.00 |
October | 14032.22 | 11-OCT-07:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.20 |
November | 16087.33 | 25-NOV-08:62 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.02 |
December | 16812.34 | 27-DEC-08:62 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.27 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 13635.74 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17457.07 | 0.00 | 262.50 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 88.29 | 114.87 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 16408.47 | 28-JAN-08:62 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 114.06 |
February | 17363.79 | 25-FEB-08:62 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 72.88 | 0.00 |
March | 16012.54 | 04-MAR-08:62 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 88.98 | 0.00 |
April | 14594.43 | 27-APR-07:01 | 0.00 | 262.50 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 70.59 | 0.00 |
May | 13653.38 | 09-MAY-07:01 | 0.00 | 262.50 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.72 |
June | 14181.98 | 20-JUN-07:01 | 0.00 | 262.50 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.02 |
July | 15125.25 | 06-JUL-07:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 27.52 | 0.00 |
August | 13558.06 | 29-AUG-07:01 | 0.00 | 262.50 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 27.48 | 0.00 |
September | 13730.46 | 06-SEP-07:01 | 0.00 | 262.50 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 63.13 | 0.00 |
October | 13947.58 | 11-OCT-07:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.62 |
November | 15996.62 | 25-NOV-08:62 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.25 |
December | 16718.41 | 27-DEC-08:62 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.48 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 13558.06 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17363.79 | 0.00 | 262.50 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 88.98 | 114.06 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 16434.47 | 28-JAN-08:62 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.85 |
February | 17393.68 | 25-FEB-08:62 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 75.33 | 0.00 |
March | 15999.00 | 04-MAR-08:62 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 92.71 | 0.00 |
April | 14651.08 | 27-APR-07:01 | 0.00 | 262.50 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 71.79 | 0.00 |
May | 13710.54 | 09-MAY-07:01 | 0.00 | 262.50 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.43 |
June | 14269.60 | 20-JUN-07:01 | 0.00 | 262.50 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.38 |
July | 15190.03 | 06-JUL-07:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 28.64 | 0.00 |
August | 13645.52 | 29-AUG-07:01 | 0.00 | 262.50 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 28.00 | 0.00 |
September | 13823.32 | 06-SEP-07:01 | 0.00 | 262.50 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 63.43 | 0.00 |
October | 13972.00 | 11-OCT-07:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 | 0.00 |
November | 16026.79 | 25-NOV-08:62 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.13 |
December | 16739.82 | 27-DEC-08:62 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.76 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 13645.52 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17393.68 | 0.00 | 262.50 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 92.71 | 111.85 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 18621.44 | 28-JAN-08:62 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 110.29 |
February | 20313.94 | 23-FEB-08:62 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.21 |
March | 17944.91 | 04-MAR-08:62 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 106.84 | 0.00 |
April | 16137.01 | 27-APR-07:01 | 0.00 | 262.50 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 68.10 | 0.00 |
May | 15114.48 | 11-MAY-07:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 55.96 | 0.00 |
June | 16102.37 | 20-JUN-07:01 | 0.00 | 262.50 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.65 |
July | 17744.87 | 11-JUL-07:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.79 |
August | 15586.04 | 24-AUG-07:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 33.78 | 0.00 |
September | 15857.30 | 12-SEP-07:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 31.05 | 0.00 |
October | 15862.66 | 11-OCT-07:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 2.54 | 0.00 |
November | 18264.61 | 25-NOV-08:62 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.01 |
December | 18833.40 | 27-DEC-08:62 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 15114.48 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 20313.94 | 0.00 | 262.50 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 106.84 | 110.29 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.111016E+12 | 101064.78 | 04-JAN-13:00 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 0.104724E+12 | 108568.17 | 13-FEB-15:09 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 0.120013E+12 | 108779.72 | 27-MAR-13:30 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 0.121538E+12 | 115783.30 | 01-APR-12:00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 0.131467E+12 | 123270.59 | 04-MAY-12:00 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 0.130235E+12 | 126926.96 | 16-JUN-12:39 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 0.115321E+12 | 104388.01 | 15-JUL-15:50 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.124084E+12 | 118523.48 | 13-AUG-13:50 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.118200E+12 | 113117.61 | 30-SEP-12:20 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 0.117213E+12 | 106677.97 | 28-OCT-12:30 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 0.111404E+12 | 104579.67 | 11-NOV-13:30 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 0.110752E+12 | 100801.98 | 30-DEC-13:50 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.141597E+13 | 0.00 | ||||
Minimum of Months | 0.104724E+12 | 100801.98 | 0.00 | 0.00 | ||
Maximum of Months | 0.131467E+12 | 126926.96 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.310073E+11 | 0.546491E+10 | 0.108325E+11 | 0.00 | 0.904788E+10 | 0.00 | 0.00 | 0.497515E+11 | 0.00 | 0.00 | 0.00 | 0.491158E+10 | 0.00 |
February | 0.280657E+11 | 0.482722E+10 | 0.980803E+10 | 0.00 | 0.862727E+10 | 0.00 | 0.00 | 0.489559E+11 | 0.00 | 0.00 | 0.00 | 0.444013E+10 | 0.00 |
March | 0.314703E+11 | 0.511136E+10 | 0.110075E+11 | 0.00 | 0.986727E+10 | 0.00 | 0.00 | 0.576308E+11 | 0.00 | 0.00 | 0.00 | 0.492542E+10 | 0.00 |
April | 0.300741E+11 | 0.477764E+10 | 0.105079E+11 | 0.00 | 0.100773E+11 | 0.00 | 0.00 | 0.613766E+11 | 0.00 | 0.00 | 0.00 | 0.472456E+10 | 0.00 |
May | 0.312330E+11 | 0.481398E+10 | 0.109147E+11 | 0.00 | 0.111069E+11 | 0.00 | 0.00 | 0.685310E+11 | 0.00 | 0.00 | 0.00 | 0.486773E+10 | 0.00 |
June | 0.304143E+11 | 0.457939E+10 | 0.106386E+11 | 0.00 | 0.111507E+11 | 0.00 | 0.00 | 0.687411E+11 | 0.00 | 0.00 | 0.00 | 0.471079E+10 | 0.00 |
July | 0.309042E+11 | 0.478754E+10 | 0.107945E+11 | 0.00 | 0.949996E+10 | 0.00 | 0.00 | 0.545000E+11 | 0.00 | 0.00 | 0.00 | 0.483492E+10 | 0.00 |
August | 0.314595E+11 | 0.487676E+10 | 0.110006E+11 | 0.00 | 0.103951E+11 | 0.00 | 0.00 | 0.614792E+11 | 0.00 | 0.00 | 0.00 | 0.487303E+10 | 0.00 |
September | 0.300847E+11 | 0.489659E+10 | 0.105148E+11 | 0.00 | 0.987517E+10 | 0.00 | 0.00 | 0.581200E+11 | 0.00 | 0.00 | 0.00 | 0.470922E+10 | 0.00 |
October | 0.310073E+11 | 0.525014E+10 | 0.108325E+11 | 0.00 | 0.970356E+10 | 0.00 | 0.00 | 0.555417E+11 | 0.00 | 0.00 | 0.00 | 0.487828E+10 | 0.00 |
November | 0.300409E+11 | 0.527710E+10 | 0.104978E+11 | 0.00 | 0.911760E+10 | 0.00 | 0.00 | 0.517282E+11 | 0.00 | 0.00 | 0.00 | 0.474238E+10 | 0.00 |
December | 0.309156E+11 | 0.551627E+10 | 0.108050E+11 | 0.00 | 0.902705E+10 | 0.00 | 0.00 | 0.495750E+11 | 0.00 | 0.00 | 0.00 | 0.491273E+10 | 0.00 |
Annual Sum or Average | 0.366677E+12 | 0.601789E+11 | 0.128154E+12 | 0.00 | 0.117496E+12 | 0.00 | 0.00 | 0.685931E+12 | 0.00 | 0.00 | 0.00 | 0.575308E+11 | 0.00 |
Minimum of Months | 0.280657E+11 | 0.457939E+10 | 0.980803E+10 | 0.00 | 0.862727E+10 | 0.00 | 0.00 | 0.489559E+11 | 0.00 | 0.00 | 0.00 | 0.444013E+10 | 0.00 |
Maximum of Months | 0.314703E+11 | 0.551627E+10 | 0.110075E+11 | 0.00 | 0.111507E+11 | 0.00 | 0.00 | 0.687411E+11 | 0.00 | 0.00 | 0.00 | 0.492542E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 23459.17 | 01-JAN-11:09 | 5507.06 | 01-JAN-06:10 | 8059.50 | 01-JAN-11:09 | 0.00 | 8269.73 | 12-JAN-13:09 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 23459.17 | 01-FEB-10:09 | 5507.06 | 01-FEB-06:10 | 8059.50 | 01-FEB-10:09 | 0.00 | 9296.91 | 15-FEB-13:00 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 23459.17 | 01-MAR-10:09 | 5507.06 | 01-MAR-06:10 | 8059.50 | 01-MAR-10:09 | 0.00 | 9755.98 | 27-MAR-12:00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 23459.17 | 01-APR-09:09 | 5507.06 | 01-APR-05:10 | 8059.50 | 01-APR-09:09 | 0.00 | 10374.88 | 02-APR-14:00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 23459.17 | 01-MAY-09:09 | 5507.06 | 01-MAY-05:10 | 8059.50 | 01-MAY-09:09 | 0.00 | 11866.08 | 04-MAY-12:00 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 23459.17 | 01-JUN-09:09 | 5507.06 | 01-JUN-05:10 | 8059.50 | 01-JUN-09:09 | 0.00 | 12249.01 | 16-JUN-12:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 23459.17 | 01-JUL-09:09 | 5507.06 | 01-JUL-05:10 | 8059.50 | 01-JUL-09:09 | 0.00 | 8990.52 | 28-JUL-12:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 23459.17 | 01-AUG-09:09 | 5507.06 | 01-AUG-05:10 | 8059.50 | 01-AUG-09:09 | 0.00 | 11421.40 | 13-AUG-14:39 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 23459.17 | 01-SEP-09:09 | 5507.06 | 01-SEP-05:10 | 8059.50 | 01-SEP-09:09 | 0.00 | 10627.05 | 30-SEP-11:39 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 23459.17 | 01-OCT-10:09 | 5507.06 | 01-OCT-05:10 | 8059.50 | 01-OCT-10:09 | 0.00 | 9729.23 | 28-OCT-12:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 23459.17 | 01-NOV-09:09 | 5507.06 | 01-NOV-05:10 | 8059.50 | 01-NOV-09:09 | 0.00 | 9175.54 | 10-NOV-13:39 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 23459.17 | 01-DEC-10:09 | 5507.06 | 01-DEC-17:30 | 8059.50 | 01-DEC-10:09 | 0.00 | 8600.15 | 30-DEC-13:00 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||||
Minimum of Months | 23459.17 | 5507.06 | 8059.50 | 0.00 | 8269.73 | 0.00 | 0.00 | |||||
Maximum of Months | 23459.17 | 5507.06 | 8059.50 | 0.00 | 12249.01 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 54476.86 | 12-JAN-13:09 | 0.00 | 0.00 | 0.00 | 11748.27 | 02-JAN-15:09 | 0.00 |
February | 60929.11 | 15-FEB-13:00 | 0.00 | 0.00 | 0.00 | 7547.19 | 03-FEB-13:50 | 0.00 |
March | 63383.72 | 27-MAR-12:00 | 0.00 | 0.00 | 0.00 | 9638.18 | 09-MAR-15:00 | 0.00 |
April | 67405.29 | 01-APR-13:00 | 0.00 | 0.00 | 0.00 | 9650.63 | 18-APR-13:09 | 0.00 |
May | 76106.66 | 04-MAY-12:00 | 0.00 | 0.00 | 0.00 | 8820.17 | 11-MAY-12:30 | 0.00 |
June | 77657.47 | 16-JUN-12:00 | 0.00 | 0.00 | 0.00 | 9629.33 | 15-JUN-11:30 | 0.00 |
July | 58649.06 | 28-JUL-12:00 | 0.00 | 0.00 | 0.00 | 8300.03 | 02-JUL-12:50 | 0.00 |
August | 71462.26 | 13-AUG-14:39 | 0.00 | 0.00 | 0.00 | 9647.08 | 10-AUG-13:20 | 0.00 |
September | 66487.72 | 30-SEP-11:39 | 0.00 | 0.00 | 0.00 | 10178.63 | 22-SEP-18:40 | 0.00 |
October | 62198.42 | 28-OCT-12:00 | 0.00 | 0.00 | 0.00 | 9652.54 | 03-OCT-12:09 | 0.00 |
November | 59027.11 | 18-NOV-12:00 | 0.00 | 0.00 | 0.00 | 7546.36 | 03-NOV-12:00 | 0.00 |
December | 55973.92 | 30-DEC-13:00 | 0.00 | 0.00 | 0.00 | 9478.58 | 01-DEC-14:39 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 54476.86 | 0.00 | 0.00 | 0.00 | 7546.36 | 0.00 | ||
Maximum of Months | 77657.47 | 0.00 | 0.00 | 0.00 | 11748.27 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 101064.78 | 04-JAN-13:00 | 23459.17 | 8059.50 | 0.00 | 0.00 | 7965.68 | 0.00 | 0.00 | 54034.28 | 0.00 |
February | 108568.17 | 13-FEB-15:09 | 23459.17 | 8059.50 | 0.00 | 0.00 | 9188.35 | 0.00 | 0.00 | 60328.48 | 0.00 |
March | 108779.72 | 27-MAR-13:30 | 23459.17 | 8059.50 | 0.00 | 0.00 | 9512.10 | 0.00 | 0.00 | 62086.93 | 0.00 |
April | 115783.30 | 01-APR-12:00 | 23459.17 | 8059.50 | 0.00 | 0.00 | 10204.81 | 0.00 | 0.00 | 66515.10 | 0.00 |
May | 123270.59 | 04-MAY-12:00 | 23459.17 | 8059.50 | 0.00 | 0.00 | 11866.08 | 0.00 | 0.00 | 76106.66 | 0.00 |
June | 126926.96 | 16-JUN-12:39 | 23459.17 | 8059.50 | 0.00 | 0.00 | 11970.53 | 0.00 | 0.00 | 75895.53 | 0.00 |
July | 104388.01 | 15-JUL-15:50 | 23459.17 | 8059.50 | 0.00 | 0.00 | 8575.57 | 0.00 | 0.00 | 56715.09 | 0.00 |
August | 118523.48 | 13-AUG-13:50 | 23459.17 | 8059.50 | 0.00 | 0.00 | 11267.46 | 0.00 | 0.00 | 70680.69 | 0.00 |
September | 113117.61 | 30-SEP-12:20 | 23459.17 | 8059.50 | 0.00 | 0.00 | 10450.12 | 0.00 | 0.00 | 65719.61 | 0.00 |
October | 106677.97 | 28-OCT-12:30 | 23459.17 | 8059.50 | 0.00 | 0.00 | 9416.64 | 0.00 | 0.00 | 60307.47 | 0.00 |
November | 104579.67 | 11-NOV-13:30 | 23459.17 | 8059.50 | 0.00 | 0.00 | 8773.78 | 0.00 | 0.00 | 56775.04 | 0.00 |
December | 100801.98 | 30-DEC-13:50 | 23459.17 | 8059.50 | 0.00 | 0.00 | 8562.04 | 0.00 | 0.00 | 55763.13 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 100801.98 | 23459.17 | 8059.50 | 0.00 | 0.00 | 7965.68 | 0.00 | 0.00 | 54034.28 | 0.00 | |
Maximum of Months | 126926.96 | 23459.17 | 8059.50 | 0.00 | 0.00 | 11970.53 | 0.00 | 0.00 | 76106.66 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.48 | 0.33 | 24.48 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 24.48 | 0.67 | 24.48 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 1.50 | 24.48 | 1.00 | 24.48 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 24.48 | 0.67 | 24.48 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.49 | 0.00 | 24.49 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 24.59 | 0.00 | 24.59 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 24.56 | 0.00 | 24.56 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.55 | 0.00 | 24.55 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.49 | 0.00 | 24.49 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 5.50 | 24.56 | 0.00 | 24.56 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 24.59 | 0.00 | 24.59 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.52 | 0.00 | 24.52 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 24.63 | 0.00 | 24.63 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 24.58 | 0.00 | 24.58 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.53 | 0.00 | 24.53 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.50 | 0.00 | 24.50 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 6.50 | 24.58 | 0.00 | 24.58 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 24.63 | 0.00 | 24.63 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.52 | 0.00 | 24.52 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 24.60 | 0.00 | 24.60 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 24.58 | 0.00 | 24.58 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.53 | 0.00 | 24.53 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.48 | 0.00 | 24.48 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 4.50 | 24.57 | 0.00 | 24.57 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 24.60 | 0.00 | 24.60 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.48 | 0.00 | 24.48 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.45 | 0.00 | 24.45 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 24.61 | 0.00 | 24.61 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 24.76 | 0.00 | 24.76 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 24.54 | 0.00 | 24.54 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.45 | 0.00 | 24.45 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.65 | 0.00 | 24.65 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 24.55 | 0.00 | 24.55 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.48 | 0.00 | 24.48 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.48 | 0.00 | 24.48 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.56 | 0.00 | 24.56 |
Annual Sum or Average | 0.00 | 0.00 | 7.00 | 24.61 | 0.00 | 24.61 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 24.76 | 0.00 | 24.76 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 24.57 | 0.00 | 24.57 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 24.82 | 0.00 | 24.82 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 24.70 | 0.00 | 24.70 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.62 | 0.00 | 24.62 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 24.52 | 0.00 | 24.52 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.46 | 0.00 | 24.46 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.50 | 0.00 | 24.50 |
Annual Sum or Average | 0.00 | 0.00 | 5.17 | 24.65 | 0.00 | 24.65 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 24.82 | 0.00 | 24.82 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 24.57 | 0.00 | 24.57 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 24.82 | 0.00 | 24.82 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 24.70 | 0.00 | 24.70 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.61 | 0.00 | 24.61 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 24.54 | 0.00 | 24.54 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.45 | 0.00 | 24.45 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.50 | 0.00 | 24.50 |
Annual Sum or Average | 0.00 | 0.00 | 5.00 | 24.66 | 0.00 | 24.66 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 24.82 | 0.00 | 24.82 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 24.56 | 0.00 | 24.56 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 24.82 | 0.00 | 24.82 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 24.73 | 0.00 | 24.73 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.61 | 0.00 | 24.61 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.54 | 0.00 | 24.54 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.48 | 0.00 | 24.48 |
Annual Sum or Average | 0.00 | 0.00 | 4.50 | 24.67 | 0.00 | 24.67 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 24.82 | 0.00 | 24.82 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.53 | 0.00 | 24.53 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.47 | 0.00 | 24.47 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 24.67 | 0.00 | 24.67 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 24.85 | 0.00 | 24.85 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 24.70 | 0.00 | 24.70 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.48 | 0.00 | 24.48 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.61 | 0.00 | 24.61 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 24.62 | 0.00 | 24.62 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.51 | 0.00 | 24.51 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.48 | 0.00 | 24.48 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.54 | 0.00 | 24.54 |
Annual Sum or Average | 0.00 | 0.00 | 9.50 | 24.68 | 0.00 | 24.68 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 24.85 | 0.00 | 24.85 |
Report: ComfortReportSimple55Monthly
For: LGSTORE1
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 44.00 | 23.89 | 496.00 | 23.89 | 44.00 | 23.89 |
February | 27.17 | 23.90 | 448.00 | 23.89 | 27.17 | 23.89 |
March | 49.00 | 23.90 | 497.00 | 23.89 | 49.00 | 23.89 |
April | 235.50 | 23.89 | 479.00 | 23.89 | 235.50 | 23.89 |
May | 400.17 | 23.89 | 496.00 | 23.89 | 400.17 | 23.89 |
June | 394.50 | 23.89 | 481.00 | 23.89 | 394.50 | 23.89 |
July | 214.67 | 23.89 | 495.00 | 23.89 | 214.67 | 23.89 |
August | 447.17 | 23.89 | 497.00 | 23.89 | 447.17 | 23.89 |
September | 398.83 | 23.89 | 479.00 | 23.89 | 398.83 | 23.89 |
October | 418.17 | 23.89 | 496.00 | 23.89 | 418.17 | 23.89 |
November | 265.33 | 23.89 | 480.00 | 23.89 | 265.33 | 23.89 |
December | 120.67 | 23.89 | 496.00 | 23.89 | 120.67 | 23.89 |
Annual Sum or Average | 3015.17 | 23.89 | 5840.00 | 23.89 | 3015.17 | 23.89 |
Minimum of Months | 27.17 | 23.89 | 448.00 | 23.89 | 27.17 | 23.89 |
Maximum of Months | 447.17 | 23.90 | 497.00 | 23.89 | 447.17 | 23.89 |
Report: ComfortReportSimple55Monthly
For: SMSTORE1
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 20.17 | 23.89 | 494.33 | 23.89 | 20.17 | 23.89 |
February | 30.67 | 23.89 | 447.00 | 23.89 | 30.67 | 23.89 |
March | 25.17 | 23.89 | 495.50 | 23.89 | 25.17 | 23.89 |
April | 201.50 | 23.89 | 479.00 | 23.89 | 201.50 | 23.89 |
May | 328.50 | 23.89 | 496.00 | 23.89 | 328.50 | 23.89 |
June | 329.33 | 23.89 | 481.00 | 23.89 | 329.33 | 23.89 |
July | 180.50 | 23.89 | 495.00 | 23.89 | 180.50 | 23.89 |
August | 357.33 | 23.89 | 497.00 | 23.89 | 357.33 | 23.89 |
September | 322.67 | 23.89 | 479.00 | 23.89 | 322.67 | 23.89 |
October | 325.67 | 23.89 | 496.00 | 23.89 | 325.67 | 23.89 |
November | 195.67 | 23.89 | 479.83 | 23.89 | 195.67 | 23.89 |
December | 74.67 | 23.89 | 492.67 | 23.89 | 74.67 | 23.89 |
Annual Sum or Average | 2391.83 | 23.89 | 5832.33 | 23.89 | 2391.83 | 23.89 |
Minimum of Months | 20.17 | 23.89 | 447.00 | 23.89 | 20.17 | 23.89 |
Maximum of Months | 357.33 | 23.89 | 497.00 | 23.89 | 357.33 | 23.89 |
Report: ComfortReportSimple55Monthly
For: SMSTORE2
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 57.00 | 24.79 | 371.00 | 24.18 | 57.00 | 24.25 |
February | 58.67 | 24.67 | 336.00 | 24.18 | 58.67 | 24.24 |
March | 71.17 | 24.76 | 379.00 | 24.20 | 71.17 | 24.28 |
April | 229.67 | 24.23 | 360.00 | 24.16 | 229.67 | 24.18 |
May | 332.67 | 24.13 | 375.00 | 24.12 | 332.67 | 24.12 |
June | 346.33 | 24.12 | 366.00 | 24.11 | 346.33 | 24.12 |
July | 227.83 | 24.21 | 369.00 | 24.14 | 227.83 | 24.16 |
August | 373.33 | 24.08 | 379.00 | 24.08 | 373.33 | 24.08 |
September | 342.17 | 24.10 | 360.00 | 24.09 | 342.17 | 24.09 |
October | 347.17 | 24.09 | 371.00 | 24.08 | 347.17 | 24.08 |
November | 239.67 | 24.15 | 360.00 | 24.10 | 239.67 | 24.12 |
December | 114.17 | 24.38 | 369.00 | 24.14 | 114.17 | 24.19 |
Annual Sum or Average | 2739.83 | 24.18 | 4395.00 | 24.12 | 2739.83 | 24.14 |
Minimum of Months | 57.00 | 24.08 | 336.00 | 24.08 | 57.00 | 24.08 |
Maximum of Months | 373.33 | 24.79 | 379.00 | 24.20 | 373.33 | 24.28 |
Report: ComfortReportSimple55Monthly
For: SMSTORE3
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 56.50 | 24.80 | 371.00 | 24.18 | 56.50 | 24.25 |
February | 58.50 | 24.68 | 336.00 | 24.18 | 58.50 | 24.24 |
March | 70.00 | 24.78 | 379.00 | 24.20 | 70.00 | 24.28 |
April | 225.67 | 24.24 | 360.00 | 24.16 | 225.67 | 24.18 |
May | 330.00 | 24.13 | 375.00 | 24.12 | 330.00 | 24.12 |
June | 342.83 | 24.12 | 366.00 | 24.11 | 342.83 | 24.12 |
July | 224.83 | 24.22 | 369.00 | 24.14 | 224.83 | 24.16 |
August | 373.00 | 24.08 | 379.00 | 24.08 | 373.00 | 24.08 |
September | 340.50 | 24.10 | 360.00 | 24.09 | 340.50 | 24.09 |
October | 345.50 | 24.09 | 371.00 | 24.08 | 345.50 | 24.09 |
November | 239.50 | 24.15 | 360.00 | 24.10 | 239.50 | 24.12 |
December | 113.50 | 24.38 | 369.00 | 24.14 | 113.50 | 24.19 |
Annual Sum or Average | 2720.33 | 24.18 | 4395.00 | 24.13 | 2720.33 | 24.14 |
Minimum of Months | 56.50 | 24.08 | 336.00 | 24.08 | 56.50 | 24.08 |
Maximum of Months | 373.00 | 24.80 | 379.00 | 24.20 | 373.00 | 24.28 |
Report: ComfortReportSimple55Monthly
For: SMSTORE4
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 61.17 | 24.72 | 371.00 | 24.17 | 61.17 | 24.24 |
February | 62.67 | 24.62 | 336.00 | 24.17 | 62.67 | 24.23 |
March | 73.67 | 24.71 | 379.00 | 24.19 | 73.67 | 24.26 |
April | 239.00 | 24.22 | 360.00 | 24.15 | 239.00 | 24.17 |
May | 334.67 | 24.13 | 375.00 | 24.11 | 334.67 | 24.12 |
June | 349.83 | 24.11 | 366.00 | 24.11 | 349.83 | 24.11 |
July | 235.83 | 24.20 | 369.00 | 24.14 | 235.83 | 24.15 |
August | 375.33 | 24.07 | 379.00 | 24.07 | 375.33 | 24.07 |
September | 344.50 | 24.09 | 360.00 | 24.09 | 344.50 | 24.09 |
October | 350.50 | 24.08 | 371.00 | 24.08 | 350.50 | 24.08 |
November | 246.17 | 24.14 | 360.00 | 24.09 | 246.17 | 24.11 |
December | 120.50 | 24.34 | 369.00 | 24.13 | 120.50 | 24.18 |
Annual Sum or Average | 2793.83 | 24.17 | 4395.00 | 24.12 | 2793.83 | 24.13 |
Minimum of Months | 61.17 | 24.07 | 336.00 | 24.07 | 61.17 | 24.07 |
Maximum of Months | 375.33 | 24.72 | 379.00 | 24.19 | 375.33 | 24.26 |
Report: ComfortReportSimple55Monthly
For: LGSTORE2
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 68.50 | 24.21 | 340.00 | 24.01 | 68.50 | 24.04 |
February | 80.50 | 24.14 | 308.00 | 24.00 | 80.50 | 24.03 |
March | 91.00 | 24.14 | 348.00 | 24.00 | 91.00 | 24.02 |
April | 272.33 | 24.00 | 330.00 | 23.99 | 272.33 | 23.99 |
May | 332.50 | 23.97 | 344.00 | 23.97 | 332.50 | 23.97 |
June | 335.17 | 23.96 | 336.00 | 23.96 | 335.17 | 23.96 |
July | 283.50 | 24.00 | 338.00 | 23.99 | 283.50 | 24.00 |
August | 348.00 | 23.95 | 348.00 | 23.95 | 348.00 | 23.95 |
September | 329.67 | 23.97 | 330.00 | 23.97 | 329.67 | 23.97 |
October | 338.17 | 23.96 | 340.00 | 23.96 | 338.17 | 23.96 |
November | 261.17 | 23.96 | 330.00 | 23.96 | 261.17 | 23.96 |
December | 133.00 | 24.08 | 338.00 | 24.00 | 133.00 | 24.02 |
Annual Sum or Average | 2873.50 | 23.99 | 4030.00 | 23.98 | 2873.50 | 23.98 |
Minimum of Months | 68.50 | 23.95 | 308.00 | 23.95 | 68.50 | 23.95 |
Maximum of Months | 348.00 | 24.21 | 348.00 | 24.01 | 348.00 | 24.04 |
Report: ComfortReportSimple55Monthly
For: SMSTORE5
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 72.33 | 24.18 | 340.00 | 24.00 | 72.33 | 24.03 |
February | 84.67 | 24.13 | 308.00 | 24.00 | 84.67 | 24.03 |
March | 97.50 | 24.13 | 348.00 | 23.99 | 97.50 | 24.02 |
April | 274.67 | 23.99 | 330.00 | 23.99 | 274.67 | 23.99 |
May | 332.00 | 23.97 | 344.00 | 23.97 | 332.00 | 23.97 |
June | 334.83 | 23.96 | 336.00 | 23.96 | 334.83 | 23.96 |
July | 291.17 | 24.00 | 338.00 | 23.99 | 291.17 | 23.99 |
August | 348.00 | 23.95 | 348.00 | 23.95 | 348.00 | 23.95 |
September | 329.17 | 23.97 | 330.00 | 23.97 | 329.17 | 23.97 |
October | 338.00 | 23.96 | 340.00 | 23.96 | 338.00 | 23.96 |
November | 263.00 | 23.96 | 330.00 | 23.96 | 263.00 | 23.96 |
December | 134.33 | 24.08 | 338.00 | 24.00 | 134.33 | 24.01 |
Annual Sum or Average | 2899.67 | 23.99 | 4030.00 | 23.97 | 2899.67 | 23.98 |
Minimum of Months | 72.33 | 23.95 | 308.00 | 23.95 | 72.33 | 23.95 |
Maximum of Months | 348.00 | 24.18 | 348.00 | 24.00 | 348.00 | 24.03 |
Report: ComfortReportSimple55Monthly
For: SMSTORE6
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 73.83 | 24.17 | 340.00 | 24.00 | 73.83 | 24.03 |
February | 86.33 | 24.13 | 308.00 | 24.00 | 86.33 | 24.02 |
March | 102.33 | 24.11 | 348.00 | 23.99 | 102.33 | 24.01 |
April | 277.50 | 23.99 | 330.00 | 23.98 | 277.50 | 23.99 |
May | 332.33 | 23.97 | 344.00 | 23.97 | 332.33 | 23.97 |
June | 335.00 | 23.96 | 336.00 | 23.96 | 335.00 | 23.96 |
July | 293.67 | 24.00 | 338.00 | 23.99 | 293.67 | 23.99 |
August | 348.00 | 23.95 | 348.00 | 23.95 | 348.00 | 23.95 |
September | 329.50 | 23.97 | 330.00 | 23.97 | 329.50 | 23.97 |
October | 338.33 | 23.96 | 340.00 | 23.96 | 338.33 | 23.96 |
November | 264.83 | 23.96 | 330.00 | 23.95 | 264.83 | 23.96 |
December | 135.83 | 24.07 | 338.00 | 24.00 | 135.83 | 24.01 |
Annual Sum or Average | 2917.50 | 23.99 | 4030.00 | 23.97 | 2917.50 | 23.98 |
Minimum of Months | 73.83 | 23.95 | 308.00 | 23.95 | 73.83 | 23.95 |
Maximum of Months | 348.00 | 24.17 | 348.00 | 24.00 | 348.00 | 24.03 |
Report: ComfortReportSimple55Monthly
For: SMSTORE7
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 74.00 | 24.17 | 340.00 | 24.00 | 74.00 | 24.03 |
February | 84.83 | 24.13 | 308.00 | 24.00 | 84.83 | 24.02 |
March | 95.33 | 24.13 | 348.00 | 23.99 | 95.33 | 24.02 |
April | 272.33 | 24.00 | 330.00 | 23.99 | 272.33 | 23.99 |
May | 330.83 | 23.97 | 344.00 | 23.97 | 330.83 | 23.97 |
June | 334.33 | 23.96 | 336.00 | 23.96 | 334.33 | 23.96 |
July | 288.33 | 24.00 | 338.00 | 23.99 | 288.33 | 23.99 |
August | 348.00 | 23.95 | 348.00 | 23.95 | 348.00 | 23.95 |
September | 328.67 | 23.97 | 330.00 | 23.97 | 328.67 | 23.97 |
October | 338.17 | 23.96 | 340.00 | 23.96 | 338.17 | 23.96 |
November | 264.00 | 23.96 | 330.00 | 23.95 | 264.00 | 23.96 |
December | 136.33 | 24.07 | 338.00 | 24.00 | 136.33 | 24.01 |
Annual Sum or Average | 2895.17 | 23.99 | 4030.00 | 23.97 | 2895.17 | 23.98 |
Minimum of Months | 74.00 | 23.95 | 308.00 | 23.95 | 74.00 | 23.95 |
Maximum of Months | 348.00 | 24.17 | 348.00 | 24.00 | 348.00 | 24.03 |
Report: ComfortReportSimple55Monthly
For: SMSTORE8
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 42.17 | 24.49 | 340.00 | 24.03 | 42.17 | 24.08 |
February | 41.67 | 24.45 | 308.00 | 24.03 | 41.67 | 24.08 |
March | 35.33 | 24.59 | 348.00 | 24.02 | 35.33 | 24.07 |
April | 160.50 | 24.09 | 330.00 | 24.02 | 160.50 | 24.04 |
May | 277.67 | 24.00 | 344.00 | 23.99 | 277.67 | 23.99 |
June | 284.67 | 23.99 | 336.00 | 23.98 | 284.67 | 23.98 |
July | 172.50 | 24.10 | 338.00 | 24.03 | 172.50 | 24.05 |
August | 330.17 | 23.96 | 348.00 | 23.95 | 330.17 | 23.96 |
September | 291.00 | 23.99 | 330.00 | 23.98 | 291.00 | 23.98 |
October | 310.33 | 23.98 | 340.00 | 23.97 | 310.33 | 23.97 |
November | 216.17 | 23.99 | 330.00 | 23.97 | 216.17 | 23.97 |
December | 90.67 | 24.19 | 338.00 | 24.02 | 90.67 | 24.05 |
Annual Sum or Average | 2252.83 | 24.03 | 4030.00 | 23.99 | 2252.83 | 24.01 |
Minimum of Months | 35.33 | 23.96 | 308.00 | 23.95 | 35.33 | 23.96 |
Maximum of Months | 330.17 | 24.59 | 348.00 | 24.03 | 330.17 | 24.08 |
Report: OccupantComfortDataSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 496.00000 | 23.89016 | 59.03862 | 0.63488 | 13.51065 |
February | 448.00000 | 23.89084 | 59.16950 | 0.64438 | 13.77963 |
March | 497.00000 | 23.89161 | 60.20964 | 0.65356 | 14.02764 |
April | 479.00000 | 23.89253 | 64.64935 | 0.68717 | 14.97085 |
May | 496.00000 | 23.89349 | 68.24095 | -0.1277 | 5.42363 |
June | 481.00000 | 23.89324 | 67.94594 | -0.1180 | 5.39282 |
July | 495.00000 | 23.89147 | 63.89854 | -0.1710 | 5.68712 |
August | 497.00000 | 23.89230 | 69.40266 | -0.1458 | 5.53874 |
September | 479.00000 | 23.89186 | 68.10850 | -0.1462 | 5.53550 |
October | 496.00000 | 23.89150 | 68.06157 | 0.68543 | 14.92921 |
November | 480.00000 | 23.89190 | 65.05686 | 0.67106 | 14.51404 |
December | 496.00000 | 23.89059 | 61.41091 | 0.64580 | 13.81147 |
Annual Sum or Average | 5840.00000 | 23.89179 | 64.62403 | 0.32410 | 10.57241 |
Minimum of Months | 448.00000 | 23.89016 | 59.03862 | -0.1710 | 5.39282 |
Maximum of Months | 497.00000 | 23.89349 | 69.40266 | 0.68717 | 14.97085 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 496.00000 | 23.89017 | 56.20999 | 0.59370 | 12.47477 |
February | 448.00000 | 23.89076 | 56.60772 | 0.60137 | 12.67972 |
March | 497.00000 | 23.89127 | 57.87597 | 0.60891 | 12.86055 |
April | 479.00000 | 23.89201 | 62.20654 | 0.64097 | 13.70743 |
May | 496.00000 | 23.89241 | 65.58526 | -0.1836 | 5.82044 |
June | 481.00000 | 23.89217 | 65.42406 | -0.1764 | 5.78937 |
July | 495.00000 | 23.89090 | 61.18023 | -0.2245 | 6.17098 |
August | 497.00000 | 23.89159 | 66.47740 | -0.1983 | 5.96100 |
September | 479.00000 | 23.89135 | 65.18824 | -0.2007 | 5.98012 |
October | 496.00000 | 23.89103 | 64.75281 | 0.64334 | 13.80313 |
November | 480.00000 | 23.89123 | 61.92706 | 0.62886 | 13.40198 |
December | 496.00000 | 23.89047 | 58.17488 | 0.60321 | 12.72888 |
Annual Sum or Average | 5840.00000 | 23.89128 | 61.82307 | 0.27602 | 10.09790 |
Minimum of Months | 448.00000 | 23.89017 | 56.20999 | -0.2245 | 5.78937 |
Maximum of Months | 497.00000 | 23.89241 | 66.47740 | 0.64334 | 13.80313 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 24.08239 | 58.92882 | 0.65700 | 14.31122 |
February | 336.00000 | 24.08820 | 59.33830 | 0.66590 | 14.58195 |
March | 379.00000 | 24.09393 | 60.44605 | 0.67125 | 14.75315 |
April | 360.00000 | 24.11551 | 65.35612 | 0.71068 | 15.97045 |
May | 375.00000 | 24.10388 | 69.03280 | -0.0965 | 5.82503 |
June | 366.00000 | 24.10739 | 69.05175 | -0.0859 | 5.80190 |
July | 369.00000 | 24.09813 | 65.05676 | -0.1379 | 5.95457 |
August | 379.00000 | 24.07511 | 70.69894 | -0.1161 | 5.75136 |
September | 360.00000 | 24.08724 | 69.48810 | -0.1137 | 5.79573 |
October | 371.00000 | 24.07624 | 69.18381 | 0.71421 | 15.98508 |
November | 360.00000 | 24.06608 | 65.57665 | 0.69413 | 15.36214 |
December | 369.00000 | 24.06908 | 61.28667 | 0.66647 | 14.57571 |
Annual Sum or Average | 4395.00000 | 24.08858 | 65.32512 | 0.34927 | 11.18553 |
Minimum of Months | 336.00000 | 24.06608 | 58.92882 | -0.1379 | 5.75136 |
Maximum of Months | 379.00000 | 24.11551 | 70.69894 | 0.71421 | 15.98508 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 24.08255 | 58.88144 | 0.65759 | 14.32839 |
February | 336.00000 | 24.08842 | 59.28922 | 0.66658 | 14.60196 |
March | 379.00000 | 24.09417 | 60.39477 | 0.67192 | 14.77348 |
April | 360.00000 | 24.11592 | 65.28219 | 0.71148 | 15.99654 |
May | 375.00000 | 24.10438 | 68.93696 | -0.0950 | 5.82402 |
June | 366.00000 | 24.10788 | 68.95731 | -0.0844 | 5.80191 |
July | 369.00000 | 24.09851 | 64.97433 | -0.1366 | 5.95053 |
August | 379.00000 | 24.07520 | 70.64754 | -0.1153 | 5.75024 |
September | 360.00000 | 24.08747 | 69.42246 | -0.1127 | 5.79425 |
October | 371.00000 | 24.07637 | 69.12893 | 0.71466 | 15.99982 |
November | 360.00000 | 24.06608 | 65.54657 | 0.69445 | 15.37188 |
December | 369.00000 | 24.06907 | 61.25688 | 0.66678 | 14.58509 |
Annual Sum or Average | 4395.00000 | 24.08881 | 65.26452 | 0.35011 | 11.19459 |
Minimum of Months | 336.00000 | 24.06608 | 58.88144 | -0.1366 | 5.75024 |
Maximum of Months | 379.00000 | 24.11592 | 70.64754 | 0.71466 | 15.99982 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 24.07864 | 59.12271 | 0.65518 | 14.25165 |
February | 336.00000 | 24.08458 | 59.52575 | 0.66418 | 14.52459 |
March | 379.00000 | 24.09023 | 60.64179 | 0.66948 | 14.69386 |
April | 360.00000 | 24.11198 | 65.56041 | 0.70934 | 15.92071 |
May | 375.00000 | 24.10069 | 69.21971 | -0.0982 | 5.81461 |
June | 366.00000 | 24.10415 | 69.23938 | -0.0876 | 5.79022 |
July | 369.00000 | 24.09472 | 65.25949 | -0.1401 | 5.94953 |
August | 379.00000 | 24.07136 | 70.99731 | -0.1188 | 5.74738 |
September | 360.00000 | 24.08362 | 69.75270 | -0.1161 | 5.78962 |
October | 371.00000 | 24.07245 | 69.46705 | 0.71282 | 15.93415 |
November | 360.00000 | 24.06215 | 65.85161 | 0.69238 | 15.30164 |
December | 369.00000 | 24.06516 | 61.52920 | 0.66441 | 14.50963 |
Annual Sum or Average | 4395.00000 | 24.08496 | 65.55222 | 0.34739 | 11.14900 |
Minimum of Months | 336.00000 | 24.06215 | 59.12271 | -0.1401 | 5.74738 |
Maximum of Months | 379.00000 | 24.11198 | 70.99731 | 0.71282 | 15.93415 |
Report: OccupantComfortDataSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 23.96599 | 60.57891 | 0.63675 | 13.64748 |
February | 308.00000 | 23.96647 | 61.10340 | 0.64610 | 13.92247 |
March | 348.00000 | 23.95806 | 62.18361 | 0.64810 | 13.97548 |
April | 330.00000 | 23.97853 | 67.16165 | 0.68746 | 15.12625 |
May | 344.00000 | 23.97156 | 70.74478 | -0.1310 | 5.72251 |
June | 336.00000 | 23.96352 | 70.78382 | -0.1219 | 5.65644 |
July | 338.00000 | 23.98480 | 66.87858 | -0.1678 | 5.93922 |
August | 348.00000 | 23.94677 | 72.77520 | -0.1527 | 5.72360 |
September | 330.00000 | 23.96754 | 71.44389 | -0.1467 | 5.74800 |
October | 340.00000 | 23.96169 | 71.19779 | 0.69393 | 15.27130 |
November | 330.00000 | 23.94913 | 67.56052 | 0.67314 | 14.63684 |
December | 338.00000 | 23.96594 | 63.00839 | 0.64702 | 13.94817 |
Annual Sum or Average | 4030.00000 | 23.96494 | 67.15775 | 0.32267 | 10.74082 |
Minimum of Months | 308.00000 | 23.94677 | 60.57891 | -0.1678 | 5.65644 |
Maximum of Months | 348.00000 | 23.98480 | 72.77520 | 0.69393 | 15.27130 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 23.96511 | 60.63838 | 0.61872 | 13.16743 |
February | 308.00000 | 23.96584 | 61.16874 | 0.62752 | 13.42114 |
March | 348.00000 | 23.95707 | 62.23849 | 0.62946 | 13.46820 |
April | 330.00000 | 23.97726 | 67.28883 | 0.66924 | 14.60150 |
May | 344.00000 | 23.97047 | 70.93891 | -0.1564 | 5.86517 |
June | 336.00000 | 23.96251 | 71.01157 | -0.1484 | 5.79653 |
July | 338.00000 | 23.98306 | 67.04755 | -0.1927 | 6.11501 |
August | 348.00000 | 23.94606 | 73.02560 | -0.1755 | 5.87159 |
September | 330.00000 | 23.96650 | 71.68096 | -0.1704 | 5.89750 |
October | 340.00000 | 23.96083 | 71.43038 | 0.67821 | 14.81247 |
November | 330.00000 | 23.94854 | 67.74957 | 0.65675 | 14.17550 |
December | 338.00000 | 23.96496 | 63.12568 | 0.62992 | 13.48588 |
Annual Sum or Average | 4030.00000 | 23.96395 | 67.31863 | 0.30216 | 10.52359 |
Minimum of Months | 308.00000 | 23.94606 | 60.63838 | -0.1927 | 5.79653 |
Maximum of Months | 348.00000 | 23.98306 | 73.02560 | 0.67821 | 14.81247 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 23.96477 | 60.71021 | 0.61761 | 13.13704 |
February | 308.00000 | 23.96556 | 61.23416 | 0.62646 | 13.39211 |
March | 348.00000 | 23.95685 | 62.30138 | 0.62849 | 13.44150 |
April | 330.00000 | 23.97699 | 67.35385 | 0.66837 | 14.57582 |
May | 344.00000 | 23.97023 | 71.00965 | -0.1577 | 5.87187 |
June | 336.00000 | 23.96229 | 71.08342 | -0.1497 | 5.80306 |
July | 338.00000 | 23.98275 | 67.11746 | -0.1941 | 6.12384 |
August | 348.00000 | 23.94585 | 73.10708 | -0.1768 | 5.87973 |
September | 330.00000 | 23.96623 | 71.75795 | -0.1717 | 5.90503 |
October | 340.00000 | 23.96056 | 71.51905 | 0.67735 | 14.78667 |
November | 330.00000 | 23.94827 | 67.83605 | 0.65579 | 14.14785 |
December | 338.00000 | 23.96459 | 63.20599 | 0.62882 | 13.45518 |
Annual Sum or Average | 4030.00000 | 23.96368 | 67.39297 | 0.30102 | 10.51056 |
Minimum of Months | 308.00000 | 23.94585 | 60.71021 | -0.1941 | 5.80306 |
Maximum of Months | 348.00000 | 23.98275 | 73.10708 | 0.67735 | 14.78667 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 23.96481 | 60.68824 | 0.62028 | 13.20784 |
February | 308.00000 | 23.96573 | 61.17035 | 0.62978 | 13.48165 |
March | 348.00000 | 23.95712 | 62.21649 | 0.63213 | 13.54082 |
April | 330.00000 | 23.97738 | 67.21211 | 0.67243 | 14.69306 |
May | 344.00000 | 23.97065 | 70.87806 | -0.1521 | 5.84213 |
June | 336.00000 | 23.96267 | 70.92532 | -0.1438 | 5.77269 |
July | 338.00000 | 23.98319 | 67.00880 | -0.1889 | 6.08729 |
August | 348.00000 | 23.94597 | 73.00457 | -0.1719 | 5.84842 |
September | 330.00000 | 23.96651 | 71.63773 | -0.1665 | 5.87284 |
October | 340.00000 | 23.96069 | 71.48398 | 0.68015 | 14.86858 |
November | 330.00000 | 23.94827 | 67.80450 | 0.65848 | 14.22318 |
December | 338.00000 | 23.96457 | 63.19930 | 0.63129 | 13.52179 |
Annual Sum or Average | 4030.00000 | 23.96390 | 67.30898 | 0.30507 | 10.54674 |
Minimum of Months | 308.00000 | 23.94597 | 60.68824 | -0.1889 | 5.77269 |
Maximum of Months | 348.00000 | 23.98319 | 73.00457 | 0.68015 | 14.86858 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 23.97296 | 58.86947 | 0.65580 | 14.19595 |
February | 308.00000 | 23.97474 | 59.05005 | 0.67053 | 14.63577 |
March | 348.00000 | 23.96566 | 59.99179 | 0.67596 | 14.79676 |
April | 330.00000 | 23.98798 | 64.42876 | 0.71777 | 16.06926 |
May | 344.00000 | 23.98003 | 68.26935 | -0.0877 | 5.63542 |
June | 336.00000 | 23.97122 | 67.99146 | -0.0746 | 5.55988 |
July | 338.00000 | 23.99571 | 64.50010 | -0.1271 | 5.79365 |
August | 348.00000 | 23.95289 | 70.34801 | -0.1153 | 5.60573 |
September | 330.00000 | 23.97705 | 68.84137 | -0.1058 | 5.63531 |
October | 340.00000 | 23.96938 | 69.31435 | 0.71036 | 15.80063 |
November | 330.00000 | 23.95484 | 65.66652 | 0.68932 | 15.12941 |
December | 338.00000 | 23.97288 | 61.33426 | 0.66400 | 14.44679 |
Annual Sum or Average | 4030.00000 | 23.97287 | 64.92284 | 0.35280 | 11.06946 |
Minimum of Months | 308.00000 | 23.95289 | 58.86947 | -0.1271 | 5.55988 |
Maximum of Months | 348.00000 | 23.99571 | 70.34801 | 0.71777 | 16.06926 |
Report: DXReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.411229E+11 | 0.101996E+11 | 499.10 | 0.255599E+11 | 0.155630E+11 | 0.00 | 1.00 | 01-JAN-08:62 | 0.00 | 01-JAN-00:05 | 63156.71 | 10-JAN-08:62 | 40057.09 | 23-JAN-08:62 | 30024.33 | 10-JAN-08:03 | 14268.04 | 11-JAN-08:62 | 0.00 | 01-JAN-00:05 |
February | 0.400731E+11 | 0.100091E+11 | 452.53 | 0.249513E+11 | 0.151218E+11 | 0.00 | 1.00 | 01-FEB-08:62 | 0.00 | 01-FEB-00:05 | 62929.28 | 16-FEB-08:62 | 42739.62 | 21-FEB-08:61 | 28930.59 | 16-FEB-08:03 | 13929.07 | 18-FEB-08:62 | 0.00 | 01-FEB-00:05 |
March | 0.467135E+11 | 0.116980E+11 | 504.05 | 0.287043E+11 | 0.180092E+11 | 0.00 | 1.00 | 01-MAR-08:62 | 0.00 | 01-MAR-00:05 | 63860.08 | 28-MAR-07:01 | 40512.71 | 04-MAR-08:62 | 31754.50 | 25-MAR-07:03 | 13997.71 | 30-MAR-07:01 | 0.00 | 01-MAR-00:05 |
April | 0.515091E+11 | 0.126044E+11 | 486.54 | 0.286917E+11 | 0.228173E+11 | 0.00 | 1.00 | 01-APR-07:02 | 0.00 | 01-APR-00:05 | 64065.95 | 12-APR-07:01 | 36252.84 | 27-APR-07:01 | 32388.74 | 01-APR-07:03 | 14114.50 | 11-APR-07:03 | 0.00 | 01-APR-00:05 |
May | 0.577295E+11 | 0.138449E+11 | 502.91 | 0.295576E+11 | 0.281720E+11 | 0.00 | 1.00 | 01-MAY-07:01 | 0.00 | 01-MAY-00:10 | 65134.89 | 19-MAY-07:02 | 33408.32 | 11-MAY-07:02 | 39145.29 | 22-MAY-07:05 | 14734.32 | 28-MAY-07:04 | 0.00 | 01-MAY-00:10 |
June | 0.575725E+11 | 0.137717E+11 | 489.14 | 0.293509E+11 | 0.282216E+11 | 0.00 | 1.00 | 01-JUN-07:02 | 0.00 | 01-JUN-00:10 | 65146.80 | 17-JUN-07:01 | 34706.66 | 25-JUN-07:02 | 37918.87 | 10-JUN-07:04 | 14284.17 | 15-JUN-07:13 | 0.00 | 01-JUN-00:10 |
July | 0.467933E+11 | 0.112909E+11 | 500.45 | 0.259626E+11 | 0.208307E+11 | 0.00 | 1.00 | 01-JUL-07:02 | 0.00 | 01-JUL-00:05 | 63747.77 | 01-JUL-07:02 | 38995.51 | 09-JUL-07:01 | 32333.74 | 01-JUL-07:03 | 13856.72 | 15-JUL-07:02 | 0.00 | 01-JUL-00:05 |
August | 0.526800E+11 | 0.124022E+11 | 503.43 | 0.258054E+11 | 0.268746E+11 | 0.00 | 1.00 | 01-AUG-07:02 | 0.00 | 01-AUG-00:10 | 65203.80 | 11-AUG-07:02 | 34900.60 | 24-AUG-07:02 | 36708.32 | 11-AUG-07:03 | 14136.59 | 09-AUG-07:03 | 0.00 | 01-AUG-00:10 |
September | 0.502492E+11 | 0.118952E+11 | 486.61 | 0.254334E+11 | 0.248158E+11 | 0.00 | 1.00 | 01-SEP-07:02 | 0.00 | 01-SEP-00:05 | 64474.85 | 01-SEP-07:02 | 36029.29 | 10-SEP-07:01 | 34213.81 | 01-SEP-07:03 | 14054.20 | 01-SEP-07:03 | 0.00 | 01-SEP-00:05 |
October | 0.481045E+11 | 0.113689E+11 | 501.00 | 0.243242E+11 | 0.237802E+11 | 0.00 | 1.00 | 01-OCT-07:01 | 0.00 | 01-OCT-00:10 | 64014.91 | 14-OCT-07:02 | 35680.04 | 08-OCT-07:02 | 33605.94 | 14-OCT-07:02 | 14006.60 | 05-OCT-07:03 | 0.00 | 01-OCT-00:10 |
November | 0.442122E+11 | 0.105922E+11 | 484.54 | 0.238752E+11 | 0.203369E+11 | 0.00 | 1.00 | 01-NOV-07:02 | 0.00 | 01-NOV-00:10 | 63637.30 | 12-NOV-08:62 | 39041.46 | 25-NOV-08:62 | 31525.91 | 12-NOV-08:03 | 13997.79 | 14-NOV-08:03 | 0.00 | 01-NOV-00:10 |
December | 0.418616E+11 | 0.102301E+11 | 502.66 | 0.246082E+11 | 0.172534E+11 | 0.00 | 1.00 | 01-DEC-08:62 | 0.00 | 01-DEC-01:05 | 63031.48 | 30-DEC-08:62 | 40095.48 | 27-DEC-08:62 | 29377.25 | 12-DEC-08:03 | 13945.68 | 09-DEC-08:62 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.578621E+12 | 0.139907E+12 | 5912.96 | 0.316825E+12 | 0.261796E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.400731E+11 | 0.100091E+11 | 452.53 | 0.238752E+11 | 0.151218E+11 | 0.00 | 1.00 | 0.00 | 62929.28 | 33408.32 | 28930.59 | 13856.72 | 0.00 | |||||||
Maximum of Months | 0.577295E+11 | 0.138449E+11 | 504.05 | 0.295576E+11 | 0.282216E+11 | 0.00 | 1.00 | 0.00 | 65203.80 | 42739.62 | 39145.29 | 14734.32 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.202315E+11 | 0.496372E+10 | 500.03 | 0.129293E+11 | 0.730222E+10 | 0.00 | 1.00 | 01-JAN-08:62 | 0.00 | 01-JAN-00:05 | 31049.67 | 10-JAN-08:62 | 23271.52 | 23-JAN-08:62 | 10835.49 | 10-JAN-08:62 | 7099.74 | 11-JAN-08:62 | 0.00 | 01-JAN-00:05 |
February | 0.195412E+11 | 0.483224E+10 | 453.03 | 0.124568E+11 | 0.708437E+10 | 0.00 | 1.00 | 01-FEB-08:62 | 0.00 | 01-FEB-00:05 | 30971.20 | 16-FEB-08:62 | 24370.66 | 21-FEB-08:61 | 10480.74 | 16-FEB-08:62 | 6906.88 | 18-FEB-08:62 | 0.00 | 01-FEB-00:05 |
March | 0.225678E+11 | 0.560846E+10 | 504.24 | 0.141950E+11 | 0.837281E+10 | 0.00 | 1.00 | 01-MAR-08:62 | 0.00 | 01-MAR-00:05 | 31381.34 | 28-MAR-07:01 | 23202.14 | 03-MAR-08:62 | 12105.97 | 28-MAR-07:03 | 6978.02 | 30-MAR-07:01 | 0.00 | 01-MAR-00:05 |
April | 0.246943E+11 | 0.601200E+10 | 486.86 | 0.141223E+11 | 0.105720E+11 | 0.00 | 1.00 | 01-APR-07:02 | 0.00 | 01-APR-00:05 | 31497.88 | 12-APR-07:01 | 21244.36 | 28-APR-07:01 | 12443.93 | 12-APR-07:03 | 7048.15 | 11-APR-07:01 | 0.00 | 01-APR-00:05 |
May | 0.278623E+11 | 0.664672E+10 | 502.78 | 0.147040E+11 | 0.131583E+11 | 0.00 | 1.00 | 01-MAY-07:01 | 0.00 | 01-MAY-00:10 | 32234.37 | 22-MAY-07:02 | 20654.38 | 12-MAY-07:02 | 15255.84 | 22-MAY-07:03 | 7397.90 | 28-MAY-07:03 | 0.00 | 01-MAY-00:10 |
June | 0.277901E+11 | 0.660595E+10 | 488.56 | 0.145694E+11 | 0.132207E+11 | 0.00 | 1.00 | 01-JUN-07:02 | 0.00 | 01-JUN-00:10 | 32260.82 | 14-JUN-07:01 | 21182.62 | 25-JUN-07:02 | 15269.40 | 14-JUN-07:04 | 7149.30 | 15-JUN-07:03 | 0.00 | 01-JUN-00:10 |
July | 0.227094E+11 | 0.543411E+10 | 501.12 | 0.129544E+11 | 0.975507E+10 | 0.00 | 1.00 | 01-JUL-07:02 | 0.00 | 01-JUL-00:05 | 31111.44 | 01-JUL-07:02 | 22429.82 | 08-JUL-07:02 | 11185.12 | 01-JUL-07:02 | 6887.16 | 15-JUL-07:02 | 0.00 | 01-JUL-00:05 |
August | 0.256086E+11 | 0.597992E+10 | 503.23 | 0.129425E+11 | 0.126661E+11 | 0.00 | 1.00 | 01-AUG-07:02 | 0.00 | 01-AUG-00:10 | 31944.44 | 13-AUG-07:01 | 21034.94 | 24-AUG-07:02 | 14019.63 | 13-AUG-07:03 | 7085.85 | 09-AUG-07:02 | 0.00 | 01-AUG-00:10 |
September | 0.243412E+11 | 0.571940E+10 | 487.26 | 0.127101E+11 | 0.116311E+11 | 0.00 | 1.00 | 01-SEP-07:02 | 0.00 | 01-SEP-00:05 | 31386.18 | 03-SEP-07:01 | 21280.52 | 10-SEP-07:01 | 12205.07 | 01-SEP-07:03 | 7031.73 | 01-SEP-07:02 | 0.00 | 01-SEP-00:05 |
October | 0.235649E+11 | 0.551596E+10 | 502.13 | 0.123358E+11 | 0.112291E+11 | 0.00 | 1.00 | 01-OCT-07:01 | 0.00 | 01-OCT-00:10 | 31311.26 | 05-OCT-07:02 | 21436.75 | 08-OCT-07:02 | 12024.72 | 05-OCT-07:03 | 6994.34 | 05-OCT-07:02 | 0.00 | 01-OCT-00:10 |
November | 0.216693E+11 | 0.514057E+10 | 484.50 | 0.120990E+11 | 0.957033E+10 | 0.00 | 1.00 | 01-NOV-07:02 | 0.00 | 01-NOV-00:10 | 31016.00 | 12-NOV-08:62 | 22944.14 | 24-NOV-08:62 | 11117.99 | 10-NOV-13:30 | 6974.82 | 14-NOV-08:61 | 0.00 | 01-NOV-00:10 |
December | 0.206075E+11 | 0.498426E+10 | 502.44 | 0.125357E+11 | 0.807184E+10 | 0.00 | 1.00 | 01-DEC-08:62 | 0.00 | 01-DEC-01:05 | 30816.90 | 10-DEC-08:61 | 23118.46 | 27-DEC-08:62 | 10098.93 | 10-DEC-08:03 | 6927.90 | 09-DEC-08:62 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.281188E+12 | 0.674433E+11 | 5916.18 | 0.158554E+12 | 0.122634E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.195412E+11 | 0.483224E+10 | 453.03 | 0.120990E+11 | 0.708437E+10 | 0.00 | 1.00 | 0.00 | 30816.90 | 20654.38 | 10098.93 | 6887.16 | 0.00 | |||||||
Maximum of Months | 0.278623E+11 | 0.664672E+10 | 504.24 | 0.147040E+11 | 0.132207E+11 | 0.00 | 1.00 | 0.00 | 32260.82 | 24370.66 | 15269.40 | 7397.90 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_3:3 COOLING COIL
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.165134E+11 | 0.401228E+10 | 365.11 | 0.103335E+11 | 0.617984E+10 | 0.00 | 1.00 | 01-JAN-08:62 | 0.00 | 01-JAN-00:05 | 33061.04 | 02-JAN-07:02 | 19277.27 | 24-JAN-07:02 | 18619.87 | 02-JAN-07:03 | 6854.08 | 11-JAN-07:02 | 0.00 | 01-JAN-00:05 |
February | 0.160944E+11 | 0.393915E+10 | 331.37 | 0.100462E+11 | 0.604818E+10 | 0.00 | 1.00 | 01-FEB-07:02 | 0.00 | 01-FEB-00:05 | 32745.91 | 06-FEB-07:02 | 20615.78 | 25-FEB-07:02 | 17273.82 | 06-FEB-07:03 | 6910.90 | 18-FEB-07:02 | 0.00 | 01-FEB-00:05 |
March | 0.189103E+11 | 0.465687E+10 | 376.81 | 0.116447E+11 | 0.726556E+10 | 0.00 | 1.00 | 01-MAR-07:01 | 0.00 | 01-MAR-00:05 | 33297.62 | 27-MAR-06:01 | 19688.68 | 04-MAR-07:02 | 18622.93 | 27-MAR-06:04 | 6964.65 | 30-MAR-06:01 | 0.00 | 01-MAR-00:05 |
April | 0.205170E+11 | 0.493146E+10 | 358.96 | 0.113899E+11 | 0.912713E+10 | 0.00 | 1.00 | 01-APR-06:01 | 0.00 | 01-APR-00:05 | 33309.94 | 10-APR-06:02 | 17597.70 | 27-APR-06:01 | 20530.50 | 03-APR-06:05 | 7007.49 | 30-APR-07:01 | 0.00 | 01-APR-00:05 |
May | 0.235098E+11 | 0.553127E+10 | 374.30 | 0.119610E+11 | 0.115488E+11 | 0.00 | 1.00 | 01-MAY-06:01 | 0.00 | 01-MAY-00:10 | 33366.76 | 17-MAY-06:02 | 15601.40 | 11-MAY-06:02 | 23243.11 | 22-MAY-06:02 | 7354.17 | 28-MAY-07:01 | 0.00 | 01-MAY-00:10 |
June | 0.236262E+11 | 0.554506E+10 | 365.25 | 0.119338E+11 | 0.116924E+11 | 0.00 | 1.00 | 01-JUN-06:02 | 0.00 | 01-JUN-00:10 | 33363.09 | 26-JUN-06:03 | 15529.11 | 30-JUN-06:01 | 21702.00 | 05-JUN-06:04 | 7045.16 | 11-JUN-07:13 | 0.00 | 01-JUN-00:10 |
July | 0.186288E+11 | 0.438603E+10 | 366.60 | 0.101867E+11 | 0.844210E+10 | 0.00 | 1.00 | 01-JUL-06:02 | 0.00 | 01-JUL-00:05 | 33315.38 | 02-JUL-07:01 | 17477.96 | 06-JUL-06:01 | 18907.29 | 02-JUL-07:04 | 6920.29 | 09-JUL-07:03 | 0.00 | 01-JUL-00:05 |
August | 0.216940E+11 | 0.499049E+10 | 377.86 | 0.104721E+11 | 0.112219E+11 | 0.00 | 1.00 | 01-AUG-06:02 | 0.00 | 01-AUG-00:10 | 33364.95 | 21-AUG-06:02 | 15976.25 | 24-AUG-06:02 | 21803.92 | 14-AUG-06:04 | 6995.20 | 13-AUG-07:13 | 0.00 | 01-AUG-00:10 |
September | 0.202955E+11 | 0.469467E+10 | 358.77 | 0.101271E+11 | 0.101685E+11 | 0.00 | 1.00 | 01-SEP-06:02 | 0.00 | 01-SEP-00:05 | 33365.49 | 18-SEP-06:02 | 15841.35 | 13-SEP-06:02 | 21368.32 | 25-SEP-06:04 | 6982.62 | 03-SEP-07:13 | 0.00 | 01-SEP-00:05 |
October | 0.195546E+11 | 0.450680E+10 | 369.13 | 0.977521E+10 | 0.977936E+10 | 0.00 | 1.00 | 01-OCT-07:01 | 0.00 | 01-OCT-00:10 | 33366.32 | 02-OCT-06:02 | 15641.21 | 11-OCT-06:02 | 20359.30 | 16-OCT-06:04 | 6927.18 | 05-OCT-06:03 | 0.00 | 01-OCT-00:10 |
November | 0.179137E+11 | 0.419606E+10 | 357.65 | 0.968149E+10 | 0.823219E+10 | 0.00 | 1.00 | 01-NOV-06:02 | 0.00 | 01-NOV-00:10 | 33345.86 | 20-NOV-07:01 | 18431.23 | 25-NOV-07:02 | 20364.54 | 13-NOV-07:03 | 6976.05 | 23-NOV-08:03 | 0.00 | 01-NOV-00:10 |
December | 0.167417E+11 | 0.401299E+10 | 363.83 | 0.996118E+10 | 0.678053E+10 | 0.00 | 1.00 | 01-DEC-07:02 | 0.00 | 01-DEC-00:10 | 33360.34 | 11-DEC-07:02 | 19067.87 | 27-DEC-07:02 | 20744.83 | 11-DEC-07:03 | 6897.48 | 10-DEC-08:04 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.233999E+12 | 0.554031E+11 | 4365.61 | 0.127513E+12 | 0.106486E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.160944E+11 | 0.393915E+10 | 331.37 | 0.968149E+10 | 0.604818E+10 | 0.00 | 1.00 | 0.00 | 32745.91 | 15529.11 | 17273.82 | 6854.08 | 0.00 | |||||||
Maximum of Months | 0.236262E+11 | 0.554506E+10 | 377.86 | 0.119610E+11 | 0.116924E+11 | 0.00 | 1.00 | 0.00 | 33366.76 | 20615.78 | 23243.11 | 7354.17 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_4:4 COOLING COIL
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.165575E+11 | 0.402341E+10 | 365.33 | 0.103662E+11 | 0.619130E+10 | 0.00 | 1.00 | 01-JAN-08:62 | 0.00 | 01-JAN-00:05 | 33157.62 | 02-JAN-07:02 | 19358.83 | 24-JAN-07:02 | 18638.82 | 02-JAN-07:03 | 6872.95 | 11-JAN-07:02 | 0.00 | 01-JAN-00:05 |
February | 0.161385E+11 | 0.395009E+10 | 331.51 | 0.100795E+11 | 0.605901E+10 | 0.00 | 1.00 | 01-FEB-07:02 | 0.00 | 01-FEB-00:05 | 32844.40 | 06-FEB-07:02 | 20707.51 | 25-FEB-07:02 | 17278.72 | 06-FEB-07:03 | 6930.00 | 18-FEB-07:02 | 0.00 | 01-FEB-00:05 |
March | 0.189613E+11 | 0.466975E+10 | 376.83 | 0.116826E+11 | 0.727873E+10 | 0.00 | 1.00 | 01-MAR-07:01 | 0.00 | 01-MAR-00:05 | 33403.48 | 27-MAR-06:01 | 19761.00 | 04-MAR-07:02 | 18609.28 | 27-MAR-06:04 | 6983.80 | 30-MAR-06:01 | 0.00 | 01-MAR-00:05 |
April | 0.205803E+11 | 0.494682E+10 | 358.91 | 0.114349E+11 | 0.914535E+10 | 0.00 | 1.00 | 01-APR-06:01 | 0.00 | 01-APR-00:05 | 33406.96 | 10-APR-06:02 | 17677.44 | 27-APR-06:01 | 20508.14 | 03-APR-06:05 | 7026.78 | 30-APR-07:01 | 0.00 | 01-APR-00:05 |
May | 0.235935E+11 | 0.555160E+10 | 374.32 | 0.120194E+11 | 0.115741E+11 | 0.00 | 1.00 | 01-MAY-06:01 | 0.00 | 01-MAY-00:10 | 33458.60 | 17-MAY-06:02 | 15675.91 | 11-MAY-06:02 | 23243.63 | 22-MAY-06:02 | 7374.41 | 28-MAY-07:01 | 0.00 | 01-MAY-00:10 |
June | 0.237060E+11 | 0.556461E+10 | 365.12 | 0.119900E+11 | 0.117160E+11 | 0.00 | 1.00 | 01-JUN-06:02 | 0.00 | 01-JUN-00:10 | 33454.91 | 26-JUN-06:02 | 15618.69 | 30-JUN-06:01 | 21704.02 | 05-JUN-06:04 | 7064.55 | 11-JUN-07:13 | 0.00 | 01-JUN-00:10 |
July | 0.186977E+11 | 0.440218E+10 | 366.65 | 0.102347E+11 | 0.846297E+10 | 0.00 | 1.00 | 01-JUL-06:02 | 0.00 | 01-JUL-00:05 | 33407.07 | 02-JUL-07:01 | 17580.14 | 06-JUL-06:01 | 18927.13 | 02-JUL-07:04 | 6939.31 | 09-JUL-07:03 | 0.00 | 01-JUL-00:05 |
August | 0.217376E+11 | 0.500145E+10 | 377.99 | 0.105026E+11 | 0.112350E+11 | 0.00 | 1.00 | 01-AUG-06:02 | 0.00 | 01-AUG-00:10 | 33456.78 | 21-AUG-06:02 | 16033.81 | 24-AUG-06:02 | 21792.79 | 14-AUG-06:04 | 7014.45 | 13-AUG-07:13 | 0.00 | 01-AUG-00:10 |
September | 0.203485E+11 | 0.470752E+10 | 358.85 | 0.101639E+11 | 0.101846E+11 | 0.00 | 1.00 | 01-SEP-06:02 | 0.00 | 01-SEP-00:05 | 33457.33 | 18-SEP-06:02 | 15916.48 | 13-SEP-06:02 | 21368.90 | 25-SEP-06:04 | 7002.04 | 03-SEP-07:13 | 0.00 | 01-SEP-00:05 |
October | 0.195996E+11 | 0.451783E+10 | 369.23 | 0.980631E+10 | 0.979333E+10 | 0.00 | 1.00 | 01-OCT-07:01 | 0.00 | 01-OCT-00:10 | 33458.15 | 02-OCT-06:02 | 15730.45 | 11-OCT-06:02 | 20364.24 | 16-OCT-06:04 | 6946.15 | 05-OCT-06:03 | 0.00 | 01-OCT-00:10 |
November | 0.179419E+11 | 0.420353E+10 | 357.65 | 0.970246E+10 | 0.823943E+10 | 0.00 | 1.00 | 01-NOV-06:02 | 0.00 | 01-NOV-00:10 | 33447.37 | 20-NOV-07:01 | 18511.70 | 25-NOV-07:02 | 20382.99 | 13-NOV-07:03 | 6995.25 | 23-NOV-08:03 | 0.00 | 01-NOV-00:10 |
December | 0.167697E+11 | 0.402063E+10 | 364.08 | 0.998197E+10 | 0.678770E+10 | 0.00 | 1.00 | 01-DEC-07:02 | 0.00 | 01-DEC-00:10 | 33452.16 | 11-DEC-07:02 | 19153.91 | 27-DEC-07:02 | 20747.56 | 11-DEC-07:03 | 6916.40 | 10-DEC-08:04 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.234632E+12 | 0.555594E+11 | 4366.47 | 0.127965E+12 | 0.106668E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.161385E+11 | 0.395009E+10 | 331.51 | 0.970246E+10 | 0.605901E+10 | 0.00 | 1.00 | 0.00 | 32844.40 | 15618.69 | 17278.72 | 6872.95 | 0.00 | |||||||
Maximum of Months | 0.237060E+11 | 0.556461E+10 | 377.99 | 0.120194E+11 | 0.117160E+11 | 0.00 | 1.00 | 0.00 | 33458.60 | 20707.51 | 23243.63 | 7374.41 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_5:5 COOLING COIL
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.163373E+11 | 0.397090E+10 | 365.13 | 0.102023E+11 | 0.613495E+10 | 0.00 | 1.00 | 01-JAN-08:62 | 0.00 | 01-JAN-00:05 | 32870.77 | 02-JAN-07:02 | 19083.89 | 24-JAN-07:02 | 18563.00 | 02-JAN-07:03 | 6815.58 | 11-JAN-07:02 | 0.00 | 01-JAN-00:05 |
February | 0.159396E+11 | 0.390171E+10 | 331.48 | 0.993043E+10 | 0.600919E+10 | 0.00 | 1.00 | 01-FEB-07:02 | 0.00 | 01-FEB-00:05 | 32559.81 | 06-FEB-07:02 | 20405.32 | 25-FEB-07:02 | 17207.62 | 06-FEB-07:03 | 6872.04 | 18-FEB-07:02 | 0.00 | 01-FEB-00:05 |
March | 0.187279E+11 | 0.461250E+10 | 377.02 | 0.115095E+11 | 0.721836E+10 | 0.00 | 1.00 | 01-MAR-07:01 | 0.00 | 01-MAR-00:05 | 33114.77 | 27-MAR-06:01 | 19466.19 | 04-MAR-07:02 | 18511.78 | 27-MAR-06:04 | 6925.55 | 30-MAR-06:01 | 0.00 | 01-MAR-00:05 |
April | 0.203414E+11 | 0.488842E+10 | 358.96 | 0.112660E+11 | 0.907536E+10 | 0.00 | 1.00 | 01-APR-06:01 | 0.00 | 01-APR-00:05 | 33118.60 | 10-APR-06:02 | 17379.09 | 27-APR-06:01 | 20410.93 | 03-APR-06:05 | 6968.14 | 30-APR-07:01 | 0.00 | 01-APR-00:05 |
May | 0.233547E+11 | 0.549281E+10 | 374.26 | 0.118557E+11 | 0.114990E+11 | 0.00 | 1.00 | 01-MAY-06:01 | 0.00 | 01-MAY-00:10 | 33179.38 | 17-MAY-06:02 | 15400.41 | 11-MAY-06:02 | 23141.69 | 22-MAY-06:02 | 7312.87 | 28-MAY-07:01 | 0.00 | 01-MAY-00:10 |
June | 0.234716E+11 | 0.550672E+10 | 365.22 | 0.118276E+11 | 0.116440E+11 | 0.00 | 1.00 | 01-JUN-06:02 | 0.00 | 01-JUN-00:10 | 33175.72 | 26-JUN-06:02 | 15320.97 | 30-JUN-06:01 | 21608.60 | 05-JUN-06:04 | 7005.60 | 11-JUN-07:13 | 0.00 | 01-JUN-00:10 |
July | 0.184646E+11 | 0.434709E+10 | 366.77 | 0.100714E+11 | 0.839314E+10 | 0.00 | 1.00 | 01-JUL-06:02 | 0.00 | 01-JUL-00:05 | 33128.28 | 02-JUL-07:01 | 17302.92 | 06-JUL-06:01 | 18878.89 | 02-JUL-07:04 | 6881.43 | 09-JUL-07:03 | 0.00 | 01-JUL-00:05 |
August | 0.214702E+11 | 0.493860E+10 | 377.77 | 0.103250E+11 | 0.111452E+11 | 0.00 | 1.00 | 01-AUG-06:02 | 0.00 | 01-AUG-00:10 | 33177.57 | 21-AUG-06:02 | 15739.54 | 24-AUG-06:02 | 21684.57 | 14-AUG-06:04 | 6955.91 | 13-AUG-07:13 | 0.00 | 01-AUG-00:10 |
September | 0.201011E+11 | 0.464916E+10 | 358.47 | 0.999731E+10 | 0.101038E+11 | 0.00 | 1.00 | 01-SEP-06:02 | 0.00 | 01-SEP-00:05 | 33178.12 | 18-SEP-06:03 | 15640.13 | 13-SEP-06:02 | 21271.36 | 25-SEP-06:04 | 6942.12 | 03-SEP-07:13 | 0.00 | 01-SEP-00:05 |
October | 0.193461E+11 | 0.445869E+10 | 369.29 | 0.963627E+10 | 0.970983E+10 | 0.00 | 1.00 | 01-OCT-07:01 | 0.00 | 01-OCT-00:10 | 33178.94 | 02-OCT-06:02 | 15469.52 | 11-OCT-06:02 | 20277.42 | 16-OCT-06:04 | 6888.30 | 05-OCT-06:03 | 0.00 | 01-OCT-00:10 |
November | 0.177040E+11 | 0.414792E+10 | 357.76 | 0.953716E+10 | 0.816682E+10 | 0.00 | 1.00 | 01-NOV-06:02 | 0.00 | 01-NOV-00:10 | 33158.19 | 20-NOV-07:01 | 18238.94 | 25-NOV-07:02 | 20327.49 | 12-NOV-08:03 | 6936.87 | 23-NOV-08:03 | 0.00 | 01-NOV-00:10 |
December | 0.165374E+11 | 0.396624E+10 | 364.01 | 0.981346E+10 | 0.672397E+10 | 0.00 | 1.00 | 01-DEC-07:02 | 0.00 | 01-DEC-00:10 | 33173.00 | 11-DEC-07:02 | 18885.37 | 27-DEC-07:02 | 20652.05 | 11-DEC-07:03 | 6858.80 | 10-DEC-08:04 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.231796E+12 | 0.548808E+11 | 4366.15 | 0.125972E+12 | 0.105823E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.159396E+11 | 0.390171E+10 | 331.48 | 0.953716E+10 | 0.600919E+10 | 0.00 | 1.00 | 0.00 | 32559.81 | 15320.97 | 17207.62 | 6815.58 | 0.00 | |||||||
Maximum of Months | 0.234716E+11 | 0.550672E+10 | 377.77 | 0.118557E+11 | 0.116440E+11 | 0.00 | 1.00 | 0.00 | 33179.38 | 20405.32 | 23141.69 | 7312.87 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_6:6 COOLING COIL
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.295046E+11 | 0.724855E+10 | 355.67 | 0.181579E+11 | 0.113467E+11 | 0.00 | 1.00 | 01-JAN-09:02 | 0.00 | 01-JAN-00:05 | 57669.14 | 02-JAN-08:62 | 34580.70 | 24-JAN-08:62 | 32471.18 | 02-JAN-08:03 | 12678.70 | 11-JAN-08:62 | 0.00 | 01-JAN-00:05 |
February | 0.288493E+11 | 0.714418E+10 | 323.32 | 0.177164E+11 | 0.111330E+11 | 0.00 | 1.00 | 01-FEB-08:62 | 0.00 | 01-FEB-00:05 | 57109.37 | 06-FEB-08:62 | 37885.52 | 25-FEB-08:62 | 29786.33 | 06-FEB-08:03 | 12550.39 | 20-FEB-09:13 | 0.00 | 01-FEB-00:05 |
March | 0.338357E+11 | 0.843011E+10 | 369.38 | 0.205247E+11 | 0.133110E+11 | 0.00 | 1.00 | 01-MAR-08:62 | 0.00 | 01-MAR-00:05 | 57987.27 | 27-MAR-07:01 | 35567.29 | 04-MAR-08:62 | 32395.71 | 27-MAR-07:04 | 12662.52 | 26-MAR-08:04 | 0.00 | 01-MAR-00:05 |
April | 0.367891E+11 | 0.893504E+10 | 348.95 | 0.200608E+11 | 0.167283E+11 | 0.00 | 1.00 | 01-APR-07:02 | 0.00 | 01-APR-00:05 | 58019.63 | 10-APR-07:02 | 32036.13 | 27-APR-07:01 | 35672.14 | 03-APR-07:06 | 12635.07 | 30-APR-08:13 | 0.00 | 01-APR-00:05 |
May | 0.423693E+11 | 0.100750E+11 | 365.18 | 0.211312E+11 | 0.212381E+11 | 0.00 | 1.00 | 01-MAY-07:01 | 0.00 | 01-MAY-00:10 | 57987.27 | 15-MAY-07:06 | 29346.59 | 31-MAY-07:01 | 40078.55 | 22-MAY-07:02 | 12909.73 | 06-MAY-07:13 | 0.00 | 01-MAY-00:10 |
June | 0.428195E+11 | 0.101609E+11 | 357.46 | 0.211993E+11 | 0.216202E+11 | 0.00 | 1.00 | 01-JUN-07:02 | 0.00 | 01-JUN-00:10 | 58049.03 | 26-JUN-07:03 | 29830.97 | 20-JUN-07:01 | 37716.87 | 05-JUN-07:06 | 12750.54 | 18-JUN-08:12 | 0.00 | 01-JUN-00:10 |
July | 0.331563E+11 | 0.788760E+10 | 354.52 | 0.177510E+11 | 0.154054E+11 | 0.00 | 1.00 | 01-JUL-07:02 | 0.00 | 01-JUL-00:05 | 58009.59 | 05-JUL-07:01 | 32775.70 | 06-JUL-07:02 | 33183.91 | 02-JUL-08:04 | 12436.92 | 30-JUL-08:04 | 0.00 | 01-JUL-00:05 |
August | 0.388935E+11 | 0.903298E+10 | 369.67 | 0.182618E+11 | 0.206317E+11 | 0.00 | 1.00 | 01-AUG-07:02 | 0.00 | 01-AUG-00:10 | 58114.70 | 21-AUG-07:04 | 29661.83 | 16-AUG-07:02 | 37488.91 | 14-AUG-07:04 | 12652.43 | 13-AUG-08:13 | 0.00 | 01-AUG-00:10 |
September | 0.362760E+11 | 0.847416E+10 | 348.61 | 0.176580E+11 | 0.186180E+11 | 0.00 | 1.00 | 01-SEP-07:02 | 0.00 | 01-SEP-00:05 | 58180.57 | 18-SEP-07:02 | 30186.22 | 06-SEP-07:01 | 37397.89 | 25-SEP-07:06 | 12557.87 | 10-SEP-08:61 | 0.00 | 01-SEP-00:05 |
October | 0.348218E+11 | 0.810126E+10 | 358.10 | 0.169358E+11 | 0.178860E+11 | 0.00 | 1.00 | 01-OCT-08:61 | 0.00 | 01-OCT-00:10 | 58179.79 | 23-OCT-07:02 | 29976.36 | 11-OCT-07:02 | 35639.39 | 23-OCT-07:02 | 12539.03 | 29-OCT-08:13 | 0.00 | 01-OCT-00:10 |
November | 0.318844E+11 | 0.754127E+10 | 348.77 | 0.167983E+11 | 0.150861E+11 | 0.00 | 1.00 | 01-NOV-07:02 | 0.00 | 01-NOV-00:10 | 58075.49 | 20-NOV-08:61 | 33361.76 | 25-NOV-08:62 | 35553.62 | 12-NOV-09:05 | 12564.91 | 23-NOV-09:02 | 0.00 | 01-NOV-00:10 |
December | 0.296989E+11 | 0.718803E+10 | 354.22 | 0.173234E+11 | 0.123755E+11 | 0.00 | 1.00 | 01-DEC-08:62 | 0.00 | 01-DEC-00:10 | 58087.62 | 11-DEC-08:03 | 35452.20 | 27-DEC-08:62 | 35865.94 | 11-DEC-08:05 | 12543.78 | 31-DEC-09:05 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.418898E+12 | 0.100219E+12 | 4253.84 | 0.223518E+12 | 0.195380E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.288493E+11 | 0.714418E+10 | 323.32 | 0.167983E+11 | 0.111330E+11 | 0.00 | 1.00 | 0.00 | 57109.37 | 29346.59 | 29786.33 | 12436.92 | 0.00 | |||||||
Maximum of Months | 0.428195E+11 | 0.101609E+11 | 369.67 | 0.211993E+11 | 0.216202E+11 | 0.00 | 1.00 | 0.00 | 58180.57 | 37885.52 | 40078.55 | 12909.73 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_7:7 COOLING COIL
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.153289E+11 | 0.370947E+10 | 357.50 | 0.944456E+10 | 0.588433E+10 | 0.00 | 1.00 | 01-JAN-09:02 | 0.00 | 01-JAN-00:05 | 30360.02 | 02-JAN-08:62 | 18083.90 | 18-JAN-08:62 | 17141.42 | 02-JAN-08:03 | 6551.90 | 11-JAN-08:62 | 0.00 | 01-JAN-00:05 |
February | 0.149984E+11 | 0.365904E+10 | 324.48 | 0.921760E+10 | 0.578078E+10 | 0.00 | 1.00 | 01-FEB-08:62 | 0.00 | 01-FEB-00:05 | 30058.63 | 06-FEB-08:62 | 19932.46 | 25-FEB-08:62 | 15736.99 | 06-FEB-08:03 | 6485.53 | 20-FEB-09:13 | 0.00 | 01-FEB-00:05 |
March | 0.175814E+11 | 0.431640E+10 | 369.28 | 0.106739E+11 | 0.690754E+10 | 0.00 | 1.00 | 01-MAR-08:62 | 0.00 | 01-MAR-00:05 | 30500.07 | 27-MAR-07:01 | 18725.17 | 04-MAR-08:62 | 17063.56 | 27-MAR-07:04 | 6543.74 | 26-MAR-08:04 | 0.00 | 01-MAR-00:05 |
April | 0.191159E+11 | 0.457675E+10 | 349.14 | 0.104372E+11 | 0.867870E+10 | 0.00 | 1.00 | 01-APR-07:02 | 0.00 | 01-APR-00:05 | 30517.09 | 10-APR-07:02 | 16894.84 | 27-APR-07:01 | 18802.81 | 03-APR-07:05 | 6530.35 | 30-APR-08:13 | 0.00 | 01-APR-00:05 |
May | 0.220032E+11 | 0.515639E+10 | 365.23 | 0.109934E+11 | 0.110098E+11 | 0.00 | 1.00 | 01-MAY-07:01 | 0.00 | 01-MAY-00:10 | 30500.07 | 15-MAY-07:03 | 15526.65 | 31-MAY-07:01 | 21185.23 | 22-MAY-07:02 | 6672.56 | 06-MAY-07:13 | 0.00 | 01-MAY-00:10 |
June | 0.222163E+11 | 0.519460E+10 | 357.39 | 0.110143E+11 | 0.112020E+11 | 0.00 | 1.00 | 01-JUN-07:02 | 0.00 | 01-JUN-00:10 | 30532.56 | 26-JUN-07:03 | 15762.50 | 20-JUN-07:01 | 19948.98 | 05-JUN-07:04 | 6588.95 | 18-JUN-08:12 | 0.00 | 01-JUN-00:10 |
July | 0.172085E+11 | 0.403329E+10 | 355.06 | 0.922704E+10 | 0.798146E+10 | 0.00 | 1.00 | 01-JUL-07:02 | 0.00 | 01-JUL-00:05 | 30545.87 | 05-JUL-07:01 | 17293.95 | 06-JUL-07:02 | 17513.78 | 02-JUL-08:03 | 6426.91 | 30-JUL-08:04 | 0.00 | 01-JUL-00:05 |
August | 0.201660E+11 | 0.461607E+10 | 369.64 | 0.948741E+10 | 0.106786E+11 | 0.00 | 1.00 | 01-AUG-07:02 | 0.00 | 01-AUG-00:10 | 30567.09 | 21-AUG-07:02 | 15654.01 | 16-AUG-07:02 | 19787.94 | 14-AUG-07:04 | 6538.26 | 13-AUG-08:13 | 0.00 | 01-AUG-00:10 |
September | 0.188247E+11 | 0.433317E+10 | 348.45 | 0.917930E+10 | 0.964538E+10 | 0.00 | 1.00 | 01-SEP-07:02 | 0.00 | 01-SEP-00:05 | 30601.74 | 18-SEP-07:02 | 15947.05 | 06-SEP-07:01 | 19714.58 | 25-SEP-07:06 | 6489.39 | 10-SEP-08:61 | 0.00 | 01-SEP-00:05 |
October | 0.180672E+11 | 0.414158E+10 | 358.75 | 0.880306E+10 | 0.926410E+10 | 0.00 | 1.00 | 01-OCT-08:61 | 0.00 | 01-OCT-00:10 | 30601.33 | 23-OCT-07:02 | 15852.33 | 11-OCT-07:02 | 18789.64 | 16-OCT-07:04 | 6479.76 | 29-OCT-08:13 | 0.00 | 01-OCT-00:10 |
November | 0.165398E+11 | 0.385482E+10 | 349.30 | 0.872791E+10 | 0.781193E+10 | 0.00 | 1.00 | 01-NOV-07:02 | 0.00 | 01-NOV-00:10 | 30546.47 | 20-NOV-08:61 | 17594.57 | 25-NOV-08:62 | 18796.84 | 12-NOV-09:05 | 6493.05 | 23-NOV-09:01 | 0.00 | 01-NOV-00:10 |
December | 0.154174E+11 | 0.367628E+10 | 355.41 | 0.900421E+10 | 0.641316E+10 | 0.00 | 1.00 | 01-DEC-08:62 | 0.00 | 01-DEC-00:10 | 30552.85 | 11-DEC-08:03 | 18697.00 | 27-DEC-08:62 | 18984.44 | 11-DEC-08:05 | 6477.15 | 31-DEC-09:04 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.217468E+12 | 0.512679E+11 | 4259.64 | 0.116210E+12 | 0.101258E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.149984E+11 | 0.365904E+10 | 324.48 | 0.872791E+10 | 0.578078E+10 | 0.00 | 1.00 | 0.00 | 30058.63 | 15526.65 | 15736.99 | 6426.91 | 0.00 | |||||||
Maximum of Months | 0.222163E+11 | 0.519460E+10 | 369.64 | 0.110143E+11 | 0.112020E+11 | 0.00 | 1.00 | 0.00 | 30601.74 | 19932.46 | 21185.23 | 6672.56 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_8:8 COOLING COIL
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.152654E+11 | 0.369366E+10 | 357.38 | 0.939841E+10 | 0.586695E+10 | 0.00 | 1.00 | 01-JAN-09:02 | 0.00 | 01-JAN-00:05 | 30240.08 | 02-JAN-08:62 | 17978.19 | 18-JAN-08:62 | 17088.25 | 02-JAN-08:03 | 6526.21 | 11-JAN-08:62 | 0.00 | 01-JAN-00:05 |
February | 0.149453E+11 | 0.364551E+10 | 324.54 | 0.917880E+10 | 0.576648E+10 | 0.00 | 1.00 | 01-FEB-08:62 | 0.00 | 01-FEB-00:05 | 29939.98 | 06-FEB-08:62 | 19829.21 | 25-FEB-08:62 | 15687.03 | 06-FEB-08:03 | 6460.10 | 20-FEB-09:13 | 0.00 | 01-FEB-00:05 |
March | 0.175243E+11 | 0.430155E+10 | 369.32 | 0.106326E+11 | 0.689170E+10 | 0.00 | 1.00 | 01-MAR-08:62 | 0.00 | 01-MAR-00:05 | 30380.53 | 27-MAR-07:01 | 18627.73 | 04-MAR-08:62 | 17003.36 | 27-MAR-07:04 | 6518.06 | 26-MAR-08:04 | 0.00 | 01-MAR-00:05 |
April | 0.190640E+11 | 0.456305E+10 | 349.12 | 0.104010E+11 | 0.866302E+10 | 0.00 | 1.00 | 01-APR-07:02 | 0.00 | 01-APR-00:05 | 30397.48 | 10-APR-07:02 | 16802.76 | 27-APR-07:01 | 18731.80 | 03-APR-07:05 | 6504.50 | 30-APR-08:13 | 0.00 | 01-APR-00:05 |
May | 0.219475E+11 | 0.514184E+10 | 365.23 | 0.109557E+11 | 0.109918E+11 | 0.00 | 1.00 | 01-MAY-07:01 | 0.00 | 01-MAY-00:10 | 30380.53 | 15-MAY-07:03 | 15443.30 | 31-MAY-07:01 | 21113.16 | 22-MAY-07:02 | 6646.24 | 06-MAY-07:13 | 0.00 | 01-MAY-00:10 |
June | 0.221597E+11 | 0.517980E+10 | 357.34 | 0.109757E+11 | 0.111839E+11 | 0.00 | 1.00 | 01-JUN-07:02 | 0.00 | 01-JUN-00:10 | 30412.89 | 26-JUN-07:02 | 15675.22 | 20-JUN-07:01 | 19883.51 | 05-JUN-07:04 | 6563.13 | 18-JUN-08:12 | 0.00 | 01-JUN-00:10 |
July | 0.171541E+11 | 0.401962E+10 | 355.06 | 0.918967E+10 | 0.796446E+10 | 0.00 | 1.00 | 01-JUL-07:02 | 0.00 | 01-JUL-00:05 | 30425.81 | 05-JUL-07:01 | 17199.60 | 06-JUL-07:02 | 17458.13 | 02-JUL-08:03 | 6401.71 | 30-JUL-08:04 | 0.00 | 01-JUL-00:05 |
August | 0.201063E+11 | 0.460110E+10 | 369.62 | 0.944842E+10 | 0.106579E+11 | 0.00 | 1.00 | 01-AUG-07:02 | 0.00 | 01-AUG-00:10 | 30447.29 | 21-AUG-07:02 | 15563.15 | 16-AUG-07:02 | 19716.29 | 14-AUG-07:04 | 6512.63 | 13-AUG-08:13 | 0.00 | 01-AUG-00:10 |
September | 0.187700E+11 | 0.431938E+10 | 348.45 | 0.914304E+10 | 0.962701E+10 | 0.00 | 1.00 | 01-SEP-07:02 | 0.00 | 01-SEP-00:05 | 30481.80 | 18-SEP-07:02 | 15863.88 | 06-SEP-07:01 | 19646.90 | 25-SEP-07:06 | 6463.95 | 10-SEP-08:61 | 0.00 | 01-SEP-00:05 |
October | 0.180042E+11 | 0.412628E+10 | 358.91 | 0.876166E+10 | 0.924257E+10 | 0.00 | 1.00 | 01-OCT-08:61 | 0.00 | 01-OCT-00:10 | 30481.40 | 23-OCT-07:02 | 15758.46 | 11-OCT-07:02 | 18725.95 | 16-OCT-07:04 | 6454.17 | 29-OCT-08:13 | 0.00 | 01-OCT-00:10 |
November | 0.164756E+11 | 0.383911E+10 | 349.33 | 0.868423E+10 | 0.779138E+10 | 0.00 | 1.00 | 01-NOV-07:02 | 0.00 | 01-NOV-00:10 | 30426.75 | 20-NOV-08:61 | 17494.01 | 25-NOV-08:62 | 18738.58 | 12-NOV-09:05 | 6467.60 | 23-NOV-09:01 | 0.00 | 01-NOV-00:10 |
December | 0.153513E+11 | 0.366007E+10 | 355.39 | 0.895739E+10 | 0.639388E+10 | 0.00 | 1.00 | 01-DEC-08:62 | 0.00 | 01-DEC-00:10 | 30433.10 | 11-DEC-08:03 | 18592.31 | 27-DEC-08:62 | 18922.70 | 11-DEC-08:05 | 6451.74 | 31-DEC-09:04 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.216768E+12 | 0.510910E+11 | 4259.68 | 0.115727E+12 | 0.101041E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.149453E+11 | 0.364551E+10 | 324.54 | 0.868423E+10 | 0.576648E+10 | 0.00 | 1.00 | 0.00 | 29939.98 | 15443.30 | 15687.03 | 6401.71 | 0.00 | |||||||
Maximum of Months | 0.221597E+11 | 0.517980E+10 | 369.62 | 0.109757E+11 | 0.111839E+11 | 0.00 | 1.00 | 0.00 | 30481.80 | 19829.21 | 21113.16 | 6646.24 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_9:9 COOLING COIL
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.152909E+11 | 0.370150E+10 | 357.59 | 0.941790E+10 | 0.587296E+10 | 0.00 | 1.00 | 01-JAN-09:02 | 0.00 | 01-JAN-00:05 | 30369.38 | 02-JAN-08:62 | 18022.17 | 18-JAN-08:62 | 17203.70 | 02-JAN-08:03 | 6556.10 | 11-JAN-08:62 | 0.00 | 01-JAN-00:05 |
February | 0.150023E+11 | 0.366054E+10 | 324.60 | 0.922147E+10 | 0.578082E+10 | 0.00 | 1.00 | 01-FEB-08:62 | 0.00 | 01-FEB-00:05 | 30070.58 | 06-FEB-08:62 | 19888.77 | 25-FEB-08:62 | 15774.94 | 06-FEB-08:03 | 6489.67 | 20-FEB-09:13 | 0.00 | 01-FEB-00:05 |
March | 0.176023E+11 | 0.432187E+10 | 369.19 | 0.106912E+11 | 0.691113E+10 | 0.00 | 1.00 | 01-MAR-08:62 | 0.00 | 01-MAR-00:05 | 30519.59 | 27-MAR-07:01 | 18649.53 | 04-MAR-08:62 | 17088.09 | 27-MAR-07:04 | 6548.07 | 26-MAR-08:04 | 0.00 | 01-MAR-00:05 |
April | 0.191723E+11 | 0.459045E+10 | 348.95 | 0.104793E+11 | 0.869295E+10 | 0.00 | 1.00 | 01-APR-07:02 | 0.00 | 01-APR-00:05 | 30536.62 | 10-APR-07:02 | 16882.43 | 27-APR-07:01 | 18833.14 | 03-APR-07:05 | 6534.49 | 30-APR-08:13 | 0.00 | 01-APR-00:05 |
May | 0.220545E+11 | 0.516963E+10 | 365.24 | 0.110323E+11 | 0.110221E+11 | 0.00 | 1.00 | 01-MAY-07:01 | 0.00 | 01-MAY-00:10 | 30519.59 | 15-MAY-07:04 | 15537.19 | 31-MAY-07:01 | 21230.59 | 22-MAY-07:02 | 6676.84 | 06-MAY-07:13 | 0.00 | 01-MAY-00:10 |
June | 0.222826E+11 | 0.521132E+10 | 357.17 | 0.110625E+11 | 0.112201E+11 | 0.00 | 1.00 | 01-JUN-07:02 | 0.00 | 01-JUN-00:10 | 30552.10 | 26-JUN-07:02 | 15781.12 | 20-JUN-07:01 | 20001.70 | 05-JUN-07:04 | 6593.17 | 18-JUN-08:12 | 0.00 | 01-JUN-00:10 |
July | 0.172373E+11 | 0.403993E+10 | 355.01 | 0.924795E+10 | 0.798935E+10 | 0.00 | 1.00 | 01-JUL-07:02 | 0.00 | 01-JUL-00:05 | 30561.03 | 05-JUL-07:01 | 17289.24 | 06-JUL-07:02 | 17541.21 | 02-JUL-08:03 | 6431.04 | 30-JUL-08:04 | 0.00 | 01-JUL-00:05 |
August | 0.201809E+11 | 0.462042E+10 | 369.46 | 0.950135E+10 | 0.106796E+11 | 0.00 | 1.00 | 01-AUG-07:02 | 0.00 | 01-AUG-00:10 | 30586.66 | 21-AUG-07:02 | 15653.43 | 16-AUG-07:02 | 19806.85 | 14-AUG-07:04 | 6542.44 | 13-AUG-08:13 | 0.00 | 01-AUG-00:10 |
September | 0.188533E+11 | 0.434020E+10 | 348.01 | 0.920176E+10 | 0.965154E+10 | 0.00 | 1.00 | 01-SEP-07:02 | 0.00 | 01-SEP-00:05 | 30621.32 | 18-SEP-07:02 | 15972.71 | 06-SEP-07:01 | 19756.53 | 25-SEP-07:06 | 6493.58 | 10-SEP-08:13 | 0.00 | 01-SEP-00:05 |
October | 0.180330E+11 | 0.413488E+10 | 358.65 | 0.878368E+10 | 0.924933E+10 | 0.00 | 1.00 | 01-OCT-08:61 | 0.00 | 01-OCT-00:10 | 30620.92 | 23-OCT-07:02 | 15809.97 | 11-OCT-07:02 | 18851.92 | 23-OCT-07:02 | 6483.68 | 29-OCT-08:13 | 0.00 | 01-OCT-00:10 |
November | 0.165010E+11 | 0.384687E+10 | 349.10 | 0.870374E+10 | 0.779724E+10 | 0.00 | 1.00 | 01-NOV-07:02 | 0.00 | 01-NOV-00:10 | 30566.02 | 20-NOV-08:61 | 17538.20 | 25-NOV-08:62 | 18853.92 | 12-NOV-09:05 | 6497.21 | 23-NOV-09:01 | 0.00 | 01-NOV-00:10 |
December | 0.153631E+11 | 0.366487E+10 | 355.31 | 0.896707E+10 | 0.639608E+10 | 0.00 | 1.00 | 01-DEC-08:62 | 0.00 | 01-DEC-00:10 | 30572.40 | 11-DEC-08:62 | 18634.59 | 27-DEC-08:62 | 19030.66 | 11-DEC-08:05 | 6481.55 | 31-DEC-09:04 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.217573E+12 | 0.513025E+11 | 4258.29 | 0.116310E+12 | 0.101263E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.150023E+11 | 0.366054E+10 | 324.60 | 0.870374E+10 | 0.578082E+10 | 0.00 | 1.00 | 0.00 | 30070.58 | 15537.19 | 15774.94 | 6431.04 | 0.00 | |||||||
Maximum of Months | 0.222826E+11 | 0.521132E+10 | 369.46 | 0.110625E+11 | 0.112201E+11 | 0.00 | 1.00 | 0.00 | 30621.32 | 19888.77 | 21230.59 | 6676.84 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_10:10 COOLING COIL
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.173205E+11 | 0.422832E+10 | 357.86 | 0.108979E+11 | 0.642257E+10 | 0.00 | 1.00 | 01-JAN-09:02 | 0.00 | 01-JAN-00:05 | 35736.40 | 09-JAN-08:62 | 20936.30 | 18-JAN-08:62 | 20398.18 | 02-JAN-08:62 | 7677.41 | 11-JAN-08:03 | 0.00 | 01-JAN-00:05 |
February | 0.171542E+11 | 0.421437E+10 | 325.66 | 0.108029E+11 | 0.635132E+10 | 0.00 | 1.00 | 01-FEB-08:62 | 0.00 | 01-FEB-00:05 | 35389.23 | 20-FEB-09:01 | 22565.51 | 25-FEB-08:62 | 18682.21 | 06-FEB-08:03 | 7600.25 | 20-FEB-09:13 | 0.00 | 01-FEB-00:05 |
March | 0.202790E+11 | 0.501527E+10 | 369.57 | 0.126137E+11 | 0.766524E+10 | 0.00 | 1.00 | 01-MAR-08:62 | 0.00 | 01-MAR-00:05 | 35743.26 | 27-MAR-07:03 | 21119.19 | 04-MAR-08:62 | 20846.30 | 27-MAR-07:04 | 7656.99 | 26-MAR-08:04 | 0.00 | 01-MAR-00:05 |
April | 0.220435E+11 | 0.532819E+10 | 349.17 | 0.124662E+11 | 0.957729E+10 | 0.00 | 1.00 | 01-APR-07:02 | 0.00 | 01-APR-00:05 | 35812.13 | 24-APR-07:01 | 18703.15 | 27-APR-07:01 | 22082.14 | 03-APR-07:05 | 7650.60 | 30-APR-08:13 | 0.00 | 01-APR-00:05 |
May | 0.249419E+11 | 0.592087E+10 | 365.57 | 0.129541E+11 | 0.119878E+11 | 0.00 | 1.00 | 01-MAY-07:01 | 0.00 | 01-MAY-00:10 | 35810.11 | 17-MAY-07:02 | 17734.01 | 11-MAY-07:02 | 25098.47 | 22-MAY-07:02 | 7855.37 | 07-MAY-08:25 | 0.00 | 01-MAY-00:10 |
June | 0.253420E+11 | 0.600041E+10 | 357.41 | 0.131075E+11 | 0.122344E+11 | 0.00 | 1.00 | 01-JUN-07:02 | 0.00 | 01-JUN-00:10 | 35781.33 | 26-JUN-07:03 | 17998.62 | 20-JUN-07:01 | 23665.44 | 05-JUN-07:03 | 7754.91 | 18-JUN-08:25 | 0.00 | 01-JUN-00:10 |
July | 0.197003E+11 | 0.465919E+10 | 355.94 | 0.109430E+11 | 0.875732E+10 | 0.00 | 1.00 | 01-JUL-07:02 | 0.00 | 01-JUL-00:05 | 35821.81 | 05-JUL-07:01 | 20065.97 | 11-JUL-07:02 | 20748.42 | 02-JUL-08:04 | 7529.86 | 30-JUL-08:04 | 0.00 | 01-JUL-00:05 |
August | 0.228468E+11 | 0.529600E+10 | 369.81 | 0.112295E+11 | 0.116173E+11 | 0.00 | 1.00 | 01-AUG-07:02 | 0.00 | 01-AUG-00:10 | 35821.81 | 21-AUG-07:02 | 18147.95 | 16-AUG-07:02 | 23226.33 | 14-AUG-07:04 | 7662.23 | 13-AUG-08:13 | 0.00 | 01-AUG-00:10 |
September | 0.214129E+11 | 0.498717E+10 | 348.62 | 0.109108E+11 | 0.105021E+11 | 0.00 | 1.00 | 01-SEP-07:02 | 0.00 | 01-SEP-00:05 | 35862.41 | 18-SEP-07:02 | 18351.55 | 12-SEP-07:02 | 23132.56 | 25-SEP-07:04 | 7608.99 | 10-SEP-08:13 | 0.00 | 01-SEP-00:05 |
October | 0.201115E+11 | 0.466947E+10 | 359.71 | 0.101630E+11 | 0.994858E+10 | 0.00 | 1.00 | 01-OCT-08:61 | 0.00 | 01-OCT-00:10 | 35861.93 | 23-OCT-07:02 | 18167.31 | 11-OCT-07:02 | 22222.05 | 16-OCT-07:04 | 7591.45 | 29-OCT-08:13 | 0.00 | 01-OCT-00:10 |
November | 0.185285E+11 | 0.436577E+10 | 349.73 | 0.100965E+11 | 0.843196E+10 | 0.00 | 1.00 | 01-NOV-07:02 | 0.00 | 01-NOV-00:10 | 35833.12 | 05-NOV-08:61 | 20327.09 | 25-NOV-08:62 | 22140.01 | 12-NOV-09:05 | 7611.75 | 23-NOV-09:13 | 0.00 | 01-NOV-00:10 |
December | 0.173123E+11 | 0.417156E+10 | 355.65 | 0.103625E+11 | 0.694986E+10 | 0.00 | 1.00 | 01-DEC-08:62 | 0.00 | 01-DEC-00:10 | 35805.11 | 11-DEC-08:62 | 21298.91 | 27-DEC-08:62 | 22149.67 | 11-DEC-08:03 | 7589.57 | 31-DEC-09:04 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.246993E+12 | 0.588566E+11 | 4264.72 | 0.136548E+12 | 0.110446E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.171542E+11 | 0.417156E+10 | 325.66 | 0.100965E+11 | 0.635132E+10 | 0.00 | 1.00 | 0.00 | 35389.23 | 17734.01 | 18682.21 | 7529.86 | 0.00 | |||||||
Maximum of Months | 0.253420E+11 | 0.600041E+10 | 369.81 | 0.131075E+11 | 0.122344E+11 | 0.00 | 1.00 | 0.00 | 35862.41 | 22565.51 | 25098.47 | 7855.37 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 52.90 | 22.07 | 30.83 | 114.47 | 9.31 | 0.00 | 0.00 | 0.00 |
February | 44.92 | 14.64 | 30.27 | 104.53 | 6.99 | 0.00 | 0.00 | 0.00 |
March | 30.65 | 4.12 | 26.54 | 78.42 | 4.76 | 0.00 | 0.00 | 0.00 |
April | 22.85 | 0.01 | 22.84 | 61.47 | 2.13 | 0.00 | 0.00 | 0.00 |
May | 22.87 | 0.00 | 22.87 | 63.24 | 2.65 | 0.00 | 0.00 | 0.00 |
June | 22.79 | 0.00 | 22.79 | 62.24 | 2.91 | 0.00 | 0.00 | 0.00 |
July | 23.47 | 0.00 | 23.47 | 56.30 | 5.26 | 0.00 | 0.00 | 0.00 |
August | 22.85 | 0.04 | 22.82 | 54.35 | 4.07 | 0.00 | 0.00 | 0.00 |
September | 25.30 | 0.83 | 24.47 | 62.07 | 4.13 | 0.00 | 0.00 | 0.00 |
October | 33.10 | 5.28 | 27.82 | 75.04 | 5.24 | 0.00 | 0.00 | 0.00 |
November | 43.04 | 13.13 | 29.91 | 94.68 | 6.53 | 0.00 | 0.00 | 0.00 |
December | 52.87 | 22.49 | 30.37 | 112.59 | 10.77 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 33.09 | 6.86 | 26.23 | 78.16 | 5.40 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 22.79 | 0.00 | 22.79 | 54.35 | 2.13 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 52.90 | 22.49 | 30.83 | 114.47 | 10.77 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 52.90 | 22.07 | 30.83 | 114.47 | 9.31 | 0.00 | 0.00 | 0.00 |
February | 44.92 | 14.64 | 30.27 | 104.53 | 6.99 | 0.00 | 0.00 | 0.00 |
March | 30.65 | 4.12 | 26.54 | 78.42 | 4.76 | 0.00 | 0.00 | 0.00 |
April | 22.85 | 0.01 | 22.84 | 61.47 | 2.13 | 0.00 | 0.00 | 0.00 |
May | 22.87 | 0.00 | 22.87 | 63.24 | 2.65 | 0.00 | 0.00 | 0.00 |
June | 22.79 | 0.00 | 22.79 | 62.24 | 2.91 | 0.00 | 0.00 | 0.00 |
July | 23.47 | 0.00 | 23.47 | 56.30 | 5.26 | 0.00 | 0.00 | 0.00 |
August | 22.85 | 0.04 | 22.82 | 54.35 | 4.07 | 0.00 | 0.00 | 0.00 |
September | 25.30 | 0.83 | 24.47 | 62.07 | 4.13 | 0.00 | 0.00 | 0.00 |
October | 33.10 | 5.28 | 27.82 | 75.04 | 5.24 | 0.00 | 0.00 | 0.00 |
November | 43.04 | 13.13 | 29.91 | 94.68 | 6.53 | 0.00 | 0.00 | 0.00 |
December | 52.87 | 22.49 | 30.37 | 112.59 | 10.77 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 33.09 | 6.86 | 26.23 | 78.16 | 5.40 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 22.79 | 0.00 | 22.79 | 54.35 | 2.13 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 52.90 | 22.49 | 30.83 | 114.47 | 10.77 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 52.90 | 22.07 | 30.83 | 114.47 | 9.31 | 0.00 | 0.00 | 0.00 |
February | 44.92 | 14.64 | 30.27 | 104.53 | 6.99 | 0.00 | 0.00 | 0.00 |
March | 30.65 | 4.12 | 26.54 | 78.42 | 4.76 | 0.00 | 0.00 | 0.00 |
April | 22.85 | 0.01 | 22.84 | 61.47 | 2.13 | 0.00 | 0.00 | 0.00 |
May | 22.87 | 0.00 | 22.87 | 63.24 | 2.65 | 0.00 | 0.00 | 0.00 |
June | 22.79 | 0.00 | 22.79 | 62.24 | 2.91 | 0.00 | 0.00 | 0.00 |
July | 23.47 | 0.00 | 23.47 | 56.30 | 5.26 | 0.00 | 0.00 | 0.00 |
August | 22.85 | 0.04 | 22.82 | 54.35 | 4.07 | 0.00 | 0.00 | 0.00 |
September | 25.30 | 0.83 | 24.47 | 62.07 | 4.13 | 0.00 | 0.00 | 0.00 |
October | 33.10 | 5.28 | 27.82 | 75.04 | 5.24 | 0.00 | 0.00 | 0.00 |
November | 43.04 | 13.13 | 29.91 | 94.68 | 6.53 | 0.00 | 0.00 | 0.00 |
December | 52.87 | 22.49 | 30.37 | 112.59 | 10.77 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 33.09 | 6.86 | 26.23 | 78.16 | 5.40 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 22.79 | 0.00 | 22.79 | 54.35 | 2.13 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 52.90 | 22.49 | 30.83 | 114.47 | 10.77 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 52.90 | 22.07 | 30.83 | 114.47 | 9.31 | 0.00 | 0.00 | 0.00 |
February | 44.92 | 14.64 | 30.27 | 104.53 | 6.99 | 0.00 | 0.00 | 0.00 |
March | 30.65 | 4.12 | 26.54 | 78.42 | 4.76 | 0.00 | 0.00 | 0.00 |
April | 22.85 | 0.01 | 22.84 | 61.47 | 2.13 | 0.00 | 0.00 | 0.00 |
May | 22.87 | 0.00 | 22.87 | 63.24 | 2.65 | 0.00 | 0.00 | 0.00 |
June | 22.79 | 0.00 | 22.79 | 62.24 | 2.91 | 0.00 | 0.00 | 0.00 |
July | 23.47 | 0.00 | 23.47 | 56.30 | 5.26 | 0.00 | 0.00 | 0.00 |
August | 22.85 | 0.04 | 22.82 | 54.35 | 4.07 | 0.00 | 0.00 | 0.00 |
September | 25.30 | 0.83 | 24.47 | 62.07 | 4.13 | 0.00 | 0.00 | 0.00 |
October | 33.10 | 5.28 | 27.82 | 75.04 | 5.24 | 0.00 | 0.00 | 0.00 |
November | 43.04 | 13.13 | 29.91 | 94.68 | 6.53 | 0.00 | 0.00 | 0.00 |
December | 52.87 | 22.49 | 30.37 | 112.59 | 10.77 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 33.09 | 6.86 | 26.23 | 78.16 | 5.40 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 22.79 | 0.00 | 22.79 | 54.35 | 2.13 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 52.90 | 22.49 | 30.83 | 114.47 | 10.77 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 63.59 | 26.53 | 37.06 | 137.15 | 11.22 | 0.00 | 0.00 | 0.00 |
February | 54.00 | 17.60 | 36.39 | 125.12 | 8.47 | 0.00 | 0.00 | 0.00 |
March | 36.85 | 4.95 | 31.90 | 93.67 | 5.83 | 0.00 | 0.00 | 0.00 |
April | 27.47 | 0.01 | 27.46 | 73.18 | 2.61 | 0.00 | 0.00 | 0.00 |
May | 27.49 | 0.00 | 27.49 | 75.35 | 3.20 | 0.00 | 0.00 | 0.00 |
June | 27.39 | 0.00 | 27.39 | 74.14 | 3.52 | 0.00 | 0.00 | 0.00 |
July | 28.22 | 0.00 | 28.22 | 67.27 | 6.32 | 0.00 | 0.00 | 0.00 |
August | 27.47 | 0.04 | 27.43 | 64.88 | 4.93 | 0.00 | 0.00 | 0.00 |
September | 30.41 | 0.99 | 29.42 | 74.19 | 4.98 | 0.00 | 0.00 | 0.00 |
October | 39.79 | 6.34 | 33.44 | 89.85 | 6.29 | 0.00 | 0.00 | 0.00 |
November | 51.74 | 15.78 | 35.95 | 113.41 | 7.85 | 0.00 | 0.00 | 0.00 |
December | 63.56 | 27.04 | 36.52 | 134.93 | 12.94 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 39.78 | 8.24 | 31.53 | 93.44 | 6.52 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 27.39 | 0.00 | 27.39 | 64.88 | 2.61 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 63.59 | 27.04 | 37.06 | 137.15 | 12.94 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 63.59 | 26.53 | 37.06 | 137.15 | 11.22 | 0.00 | 0.00 | 0.00 |
February | 54.00 | 17.60 | 36.39 | 125.12 | 8.47 | 0.00 | 0.00 | 0.00 |
March | 36.85 | 4.95 | 31.90 | 93.67 | 5.83 | 0.00 | 0.00 | 0.00 |
April | 27.47 | 0.01 | 27.46 | 73.18 | 2.61 | 0.00 | 0.00 | 0.00 |
May | 27.49 | 0.00 | 27.49 | 75.35 | 3.20 | 0.00 | 0.00 | 0.00 |
June | 27.39 | 0.00 | 27.39 | 74.14 | 3.52 | 0.00 | 0.00 | 0.00 |
July | 28.22 | 0.00 | 28.22 | 67.27 | 6.32 | 0.00 | 0.00 | 0.00 |
August | 27.47 | 0.04 | 27.43 | 64.88 | 4.93 | 0.00 | 0.00 | 0.00 |
September | 30.41 | 0.99 | 29.42 | 74.19 | 4.98 | 0.00 | 0.00 | 0.00 |
October | 39.79 | 6.34 | 33.44 | 89.85 | 6.29 | 0.00 | 0.00 | 0.00 |
November | 51.74 | 15.78 | 35.95 | 113.41 | 7.85 | 0.00 | 0.00 | 0.00 |
December | 63.56 | 27.04 | 36.52 | 134.93 | 12.94 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 39.78 | 8.24 | 31.53 | 93.44 | 6.52 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 27.39 | 0.00 | 27.39 | 64.88 | 2.61 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 63.59 | 27.04 | 37.06 | 137.15 | 12.94 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 52.90 | 22.07 | 30.83 | 114.93 | 9.22 | 0.00 | 0.00 | 0.00 |
February | 44.92 | 14.64 | 30.27 | 105.21 | 6.84 | 0.00 | 0.00 | 0.00 |
March | 30.65 | 4.12 | 26.54 | 79.34 | 4.56 | 0.00 | 0.00 | 0.00 |
April | 22.85 | 0.01 | 22.84 | 62.63 | 1.97 | 0.00 | 0.00 | 0.00 |
May | 22.87 | 0.00 | 22.87 | 64.29 | 2.55 | 0.00 | 0.00 | 0.00 |
June | 22.79 | 0.00 | 22.79 | 63.36 | 2.76 | 0.00 | 0.00 | 0.00 |
July | 23.47 | 0.00 | 23.47 | 57.06 | 5.09 | 0.00 | 0.00 | 0.00 |
August | 22.85 | 0.04 | 22.82 | 55.14 | 3.92 | 0.00 | 0.00 | 0.00 |
September | 25.30 | 0.83 | 24.47 | 62.85 | 3.98 | 0.00 | 0.00 | 0.00 |
October | 33.10 | 5.28 | 27.82 | 75.57 | 5.16 | 0.00 | 0.00 | 0.00 |
November | 43.04 | 13.13 | 29.91 | 95.20 | 6.45 | 0.00 | 0.00 | 0.00 |
December | 52.87 | 22.49 | 30.37 | 112.98 | 10.70 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 33.09 | 6.86 | 26.23 | 78.92 | 5.27 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 22.79 | 0.00 | 22.79 | 55.14 | 1.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 52.90 | 22.49 | 30.83 | 114.93 | 10.70 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 52.90 | 22.07 | 30.83 | 114.93 | 9.22 | 0.00 | 0.00 | 0.00 |
February | 44.92 | 14.64 | 30.27 | 105.21 | 6.84 | 0.00 | 0.00 | 0.00 |
March | 30.65 | 4.12 | 26.54 | 79.34 | 4.56 | 0.00 | 0.00 | 0.00 |
April | 22.85 | 0.01 | 22.84 | 62.63 | 1.97 | 0.00 | 0.00 | 0.00 |
May | 22.87 | 0.00 | 22.87 | 64.29 | 2.55 | 0.00 | 0.00 | 0.00 |
June | 22.79 | 0.00 | 22.79 | 63.36 | 2.76 | 0.00 | 0.00 | 0.00 |
July | 23.47 | 0.00 | 23.47 | 57.06 | 5.09 | 0.00 | 0.00 | 0.00 |
August | 22.85 | 0.04 | 22.82 | 55.14 | 3.92 | 0.00 | 0.00 | 0.00 |
September | 25.30 | 0.83 | 24.47 | 62.85 | 3.98 | 0.00 | 0.00 | 0.00 |
October | 33.10 | 5.28 | 27.82 | 75.57 | 5.16 | 0.00 | 0.00 | 0.00 |
November | 43.04 | 13.13 | 29.91 | 95.20 | 6.45 | 0.00 | 0.00 | 0.00 |
December | 52.87 | 22.49 | 30.37 | 112.98 | 10.70 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 33.09 | 6.86 | 26.23 | 78.92 | 5.27 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 22.79 | 0.00 | 22.79 | 55.14 | 1.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 52.90 | 22.49 | 30.83 | 114.93 | 10.70 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 63.59 | 26.53 | 37.06 | 137.72 | 11.10 | 0.00 | 0.00 | 0.00 |
February | 54.00 | 17.60 | 36.39 | 125.94 | 8.28 | 0.00 | 0.00 | 0.00 |
March | 36.85 | 4.95 | 31.90 | 94.76 | 5.58 | 0.00 | 0.00 | 0.00 |
April | 27.47 | 0.01 | 27.46 | 74.55 | 2.43 | 0.00 | 0.00 | 0.00 |
May | 27.49 | 0.00 | 27.49 | 76.60 | 3.09 | 0.00 | 0.00 | 0.00 |
June | 27.39 | 0.00 | 27.39 | 75.47 | 3.34 | 0.00 | 0.00 | 0.00 |
July | 28.22 | 0.00 | 28.22 | 68.18 | 6.12 | 0.00 | 0.00 | 0.00 |
August | 27.47 | 0.04 | 27.43 | 65.83 | 4.76 | 0.00 | 0.00 | 0.00 |
September | 30.41 | 0.99 | 29.42 | 75.13 | 4.80 | 0.00 | 0.00 | 0.00 |
October | 39.79 | 6.34 | 33.44 | 90.50 | 6.20 | 0.00 | 0.00 | 0.00 |
November | 51.74 | 15.78 | 35.95 | 114.05 | 7.76 | 0.00 | 0.00 | 0.00 |
December | 63.56 | 27.04 | 36.52 | 135.42 | 12.85 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 39.78 | 8.24 | 31.53 | 94.36 | 6.36 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 27.39 | 0.00 | 27.39 | 65.83 | 2.43 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 63.59 | 27.04 | 37.06 | 137.72 | 12.85 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 52.90 | 22.07 | 30.83 | 114.60 | 11.36 | 0.00 | 0.00 | 0.00 |
February | 44.92 | 14.64 | 30.27 | 104.74 | 8.95 | 0.00 | 0.00 | 0.00 |
March | 30.65 | 4.12 | 26.54 | 78.58 | 6.40 | 0.00 | 0.00 | 0.00 |
April | 22.85 | 0.01 | 22.84 | 60.58 | 2.88 | 0.00 | 0.00 | 0.00 |
May | 22.87 | 0.00 | 22.87 | 62.27 | 3.56 | 0.00 | 0.00 | 0.00 |
June | 22.79 | 0.00 | 22.79 | 61.48 | 3.88 | 0.00 | 0.00 | 0.00 |
July | 23.47 | 0.00 | 23.47 | 55.83 | 6.76 | 0.00 | 0.00 | 0.00 |
August | 22.85 | 0.04 | 22.82 | 54.38 | 5.55 | 0.00 | 0.00 | 0.00 |
September | 25.30 | 0.83 | 24.47 | 61.74 | 5.53 | 0.00 | 0.00 | 0.00 |
October | 33.10 | 5.28 | 27.82 | 74.94 | 6.97 | 0.00 | 0.00 | 0.00 |
November | 43.04 | 13.13 | 29.91 | 94.80 | 8.27 | 0.00 | 0.00 | 0.00 |
December | 52.87 | 22.49 | 30.37 | 112.81 | 12.80 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 33.09 | 6.86 | 26.23 | 77.94 | 6.91 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 22.79 | 0.00 | 22.79 | 54.38 | 2.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 52.90 | 22.49 | 30.83 | 114.60 | 12.80 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 52.90 | 22.07 | 30.83 | 114.60 | 11.36 | 0.00 | 0.00 | 0.00 |
February | 44.92 | 14.64 | 30.27 | 104.74 | 8.95 | 0.00 | 0.00 | 0.00 |
March | 30.65 | 4.12 | 26.54 | 78.58 | 6.40 | 0.00 | 0.00 | 0.00 |
April | 22.85 | 0.01 | 22.84 | 60.58 | 2.88 | 0.00 | 0.00 | 0.00 |
May | 22.87 | 0.00 | 22.87 | 62.27 | 3.56 | 0.00 | 0.00 | 0.00 |
June | 22.79 | 0.00 | 22.79 | 61.48 | 3.88 | 0.00 | 0.00 | 0.00 |
July | 23.47 | 0.00 | 23.47 | 55.83 | 6.76 | 0.00 | 0.00 | 0.00 |
August | 22.85 | 0.04 | 22.82 | 54.38 | 5.55 | 0.00 | 0.00 | 0.00 |
September | 25.30 | 0.83 | 24.47 | 61.74 | 5.53 | 0.00 | 0.00 | 0.00 |
October | 33.10 | 5.28 | 27.82 | 74.94 | 6.97 | 0.00 | 0.00 | 0.00 |
November | 43.04 | 13.13 | 29.91 | 94.80 | 8.27 | 0.00 | 0.00 | 0.00 |
December | 52.87 | 22.49 | 30.37 | 112.81 | 12.80 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 33.09 | 6.86 | 26.23 | 77.94 | 6.91 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 22.79 | 0.00 | 22.79 | 54.38 | 2.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 52.90 | 22.49 | 30.83 | 114.60 | 12.80 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 63.24 | 26.38 | 36.86 | 136.59 | 13.55 | 0.00 | 0.00 | 0.00 |
February | 53.70 | 17.51 | 36.19 | 124.74 | 10.72 | 0.00 | 0.00 | 0.00 |
March | 36.65 | 4.92 | 31.73 | 93.42 | 7.75 | 0.00 | 0.00 | 0.00 |
April | 27.32 | 0.01 | 27.31 | 71.81 | 3.53 | 0.00 | 0.00 | 0.00 |
May | 27.34 | 0.00 | 27.34 | 73.85 | 4.27 | 0.00 | 0.00 | 0.00 |
June | 27.24 | 0.00 | 27.24 | 72.91 | 4.66 | 0.00 | 0.00 | 0.00 |
July | 28.06 | 0.00 | 28.06 | 66.40 | 8.05 | 0.00 | 0.00 | 0.00 |
August | 27.32 | 0.04 | 27.28 | 64.61 | 6.65 | 0.00 | 0.00 | 0.00 |
September | 30.25 | 0.99 | 29.26 | 73.44 | 6.59 | 0.00 | 0.00 | 0.00 |
October | 39.57 | 6.31 | 33.26 | 89.28 | 8.29 | 0.00 | 0.00 | 0.00 |
November | 51.45 | 15.70 | 35.76 | 112.98 | 9.85 | 0.00 | 0.00 | 0.00 |
December | 63.21 | 26.89 | 36.32 | 134.48 | 15.23 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 39.56 | 8.20 | 31.36 | 92.72 | 8.26 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 27.24 | 0.00 | 27.24 | 64.61 | 3.53 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 63.24 | 26.89 | 36.86 | 136.59 | 15.23 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 52.90 | 22.07 | 30.83 | 114.56 | 11.51 | 0.00 | 0.00 | 0.00 |
February | 44.92 | 14.64 | 30.27 | 104.69 | 9.11 | 0.00 | 0.00 | 0.00 |
March | 30.65 | 4.12 | 26.54 | 78.54 | 6.58 | 0.00 | 0.00 | 0.00 |
April | 22.85 | 0.01 | 22.84 | 60.49 | 3.05 | 0.00 | 0.00 | 0.00 |
May | 22.87 | 0.00 | 22.87 | 62.12 | 3.71 | 0.00 | 0.00 | 0.00 |
June | 22.79 | 0.00 | 22.79 | 61.37 | 4.07 | 0.00 | 0.00 | 0.00 |
July | 23.47 | 0.00 | 23.47 | 55.76 | 6.95 | 0.00 | 0.00 | 0.00 |
August | 22.85 | 0.04 | 22.82 | 54.34 | 5.69 | 0.00 | 0.00 | 0.00 |
September | 25.30 | 0.83 | 24.47 | 61.68 | 5.69 | 0.00 | 0.00 | 0.00 |
October | 33.10 | 5.28 | 27.82 | 74.90 | 7.12 | 0.00 | 0.00 | 0.00 |
November | 43.04 | 13.13 | 29.91 | 94.77 | 8.39 | 0.00 | 0.00 | 0.00 |
December | 52.87 | 22.49 | 30.37 | 112.78 | 12.91 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 33.09 | 6.86 | 26.23 | 77.87 | 7.07 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 22.79 | 0.00 | 22.79 | 54.34 | 3.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 52.90 | 22.49 | 30.83 | 114.56 | 12.91 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 52.90 | 22.07 | 30.83 | 114.56 | 11.51 | 0.00 | 0.00 | 0.00 |
February | 44.92 | 14.64 | 30.27 | 104.69 | 9.11 | 0.00 | 0.00 | 0.00 |
March | 30.65 | 4.12 | 26.54 | 78.54 | 6.58 | 0.00 | 0.00 | 0.00 |
April | 22.85 | 0.01 | 22.84 | 60.49 | 3.05 | 0.00 | 0.00 | 0.00 |
May | 22.87 | 0.00 | 22.87 | 62.12 | 3.71 | 0.00 | 0.00 | 0.00 |
June | 22.79 | 0.00 | 22.79 | 61.37 | 4.07 | 0.00 | 0.00 | 0.00 |
July | 23.47 | 0.00 | 23.47 | 55.76 | 6.95 | 0.00 | 0.00 | 0.00 |
August | 22.85 | 0.04 | 22.82 | 54.34 | 5.69 | 0.00 | 0.00 | 0.00 |
September | 25.30 | 0.83 | 24.47 | 61.68 | 5.69 | 0.00 | 0.00 | 0.00 |
October | 33.10 | 5.28 | 27.82 | 74.90 | 7.12 | 0.00 | 0.00 | 0.00 |
November | 43.04 | 13.13 | 29.91 | 94.77 | 8.39 | 0.00 | 0.00 | 0.00 |
December | 52.87 | 22.49 | 30.37 | 112.78 | 12.91 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 33.09 | 6.86 | 26.23 | 77.87 | 7.07 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 22.79 | 0.00 | 22.79 | 54.34 | 3.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 52.90 | 22.49 | 30.83 | 114.56 | 12.91 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 63.24 | 26.38 | 36.86 | 136.55 | 13.73 | 0.00 | 0.00 | 0.00 |
February | 53.70 | 17.51 | 36.19 | 124.68 | 10.92 | 0.00 | 0.00 | 0.00 |
March | 36.65 | 4.92 | 31.73 | 93.37 | 7.97 | 0.00 | 0.00 | 0.00 |
April | 27.32 | 0.01 | 27.31 | 71.71 | 3.73 | 0.00 | 0.00 | 0.00 |
May | 27.34 | 0.00 | 27.34 | 73.68 | 4.45 | 0.00 | 0.00 | 0.00 |
June | 27.24 | 0.00 | 27.24 | 72.78 | 4.88 | 0.00 | 0.00 | 0.00 |
July | 28.06 | 0.00 | 28.06 | 66.32 | 8.28 | 0.00 | 0.00 | 0.00 |
August | 27.32 | 0.04 | 27.28 | 64.56 | 6.83 | 0.00 | 0.00 | 0.00 |
September | 30.25 | 0.99 | 29.26 | 73.38 | 6.79 | 0.00 | 0.00 | 0.00 |
October | 39.57 | 6.31 | 33.26 | 89.23 | 8.47 | 0.00 | 0.00 | 0.00 |
November | 51.45 | 15.70 | 35.76 | 112.94 | 9.99 | 0.00 | 0.00 | 0.00 |
December | 63.21 | 26.89 | 36.32 | 134.45 | 15.36 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 39.56 | 8.20 | 31.36 | 92.65 | 8.45 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 27.24 | 0.00 | 27.24 | 64.56 | 3.73 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 63.24 | 26.89 | 36.86 | 136.55 | 15.36 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 52.90 | 22.07 | 30.83 | 114.67 | 11.25 | 0.00 | 0.00 | 0.00 |
February | 44.92 | 14.64 | 30.27 | 104.81 | 8.85 | 0.00 | 0.00 | 0.00 |
March | 30.65 | 4.12 | 26.54 | 78.65 | 6.30 | 0.00 | 0.00 | 0.00 |
April | 22.85 | 0.01 | 22.84 | 60.65 | 2.83 | 0.00 | 0.00 | 0.00 |
May | 22.87 | 0.00 | 22.87 | 62.29 | 3.53 | 0.00 | 0.00 | 0.00 |
June | 22.79 | 0.00 | 22.79 | 61.53 | 3.87 | 0.00 | 0.00 | 0.00 |
July | 23.47 | 0.00 | 23.47 | 55.87 | 6.70 | 0.00 | 0.00 | 0.00 |
August | 22.85 | 0.04 | 22.82 | 54.46 | 5.42 | 0.00 | 0.00 | 0.00 |
September | 25.30 | 0.83 | 24.47 | 61.81 | 5.43 | 0.00 | 0.00 | 0.00 |
October | 33.10 | 5.28 | 27.82 | 75.01 | 6.85 | 0.00 | 0.00 | 0.00 |
November | 43.04 | 13.13 | 29.91 | 94.89 | 8.13 | 0.00 | 0.00 | 0.00 |
December | 52.87 | 22.49 | 30.37 | 112.89 | 12.65 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 33.09 | 6.86 | 26.23 | 78.00 | 6.82 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 22.79 | 0.00 | 22.79 | 54.46 | 2.83 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 52.90 | 22.49 | 30.83 | 114.67 | 12.65 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 52.90 | 22.07 | 30.83 | 114.67 | 11.25 | 0.00 | 0.00 | 0.00 |
February | 44.92 | 14.64 | 30.27 | 104.81 | 8.85 | 0.00 | 0.00 | 0.00 |
March | 30.65 | 4.12 | 26.54 | 78.65 | 6.30 | 0.00 | 0.00 | 0.00 |
April | 22.85 | 0.01 | 22.84 | 60.65 | 2.83 | 0.00 | 0.00 | 0.00 |
May | 22.87 | 0.00 | 22.87 | 62.29 | 3.53 | 0.00 | 0.00 | 0.00 |
June | 22.79 | 0.00 | 22.79 | 61.53 | 3.87 | 0.00 | 0.00 | 0.00 |
July | 23.47 | 0.00 | 23.47 | 55.87 | 6.70 | 0.00 | 0.00 | 0.00 |
August | 22.85 | 0.04 | 22.82 | 54.46 | 5.42 | 0.00 | 0.00 | 0.00 |
September | 25.30 | 0.83 | 24.47 | 61.81 | 5.43 | 0.00 | 0.00 | 0.00 |
October | 33.10 | 5.28 | 27.82 | 75.01 | 6.85 | 0.00 | 0.00 | 0.00 |
November | 43.04 | 13.13 | 29.91 | 94.89 | 8.13 | 0.00 | 0.00 | 0.00 |
December | 52.87 | 22.49 | 30.37 | 112.89 | 12.65 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 33.09 | 6.86 | 26.23 | 78.00 | 6.82 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 22.79 | 0.00 | 22.79 | 54.46 | 2.83 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 52.90 | 22.49 | 30.83 | 114.67 | 12.65 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 63.24 | 26.38 | 36.86 | 136.68 | 13.42 | 0.00 | 0.00 | 0.00 |
February | 53.70 | 17.51 | 36.19 | 124.81 | 10.61 | 0.00 | 0.00 | 0.00 |
March | 36.65 | 4.92 | 31.73 | 93.50 | 7.63 | 0.00 | 0.00 | 0.00 |
April | 27.32 | 0.01 | 27.31 | 71.89 | 3.47 | 0.00 | 0.00 | 0.00 |
May | 27.34 | 0.00 | 27.34 | 73.87 | 4.23 | 0.00 | 0.00 | 0.00 |
June | 27.24 | 0.00 | 27.24 | 72.96 | 4.64 | 0.00 | 0.00 | 0.00 |
July | 28.06 | 0.00 | 28.06 | 66.45 | 7.98 | 0.00 | 0.00 | 0.00 |
August | 27.32 | 0.04 | 27.28 | 64.71 | 6.50 | 0.00 | 0.00 | 0.00 |
September | 30.25 | 0.99 | 29.26 | 73.53 | 6.49 | 0.00 | 0.00 | 0.00 |
October | 39.57 | 6.31 | 33.26 | 89.37 | 8.15 | 0.00 | 0.00 | 0.00 |
November | 51.45 | 15.70 | 35.76 | 113.08 | 9.69 | 0.00 | 0.00 | 0.00 |
December | 63.21 | 26.89 | 36.32 | 134.59 | 15.05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 39.56 | 8.20 | 31.36 | 92.80 | 8.16 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 27.24 | 0.00 | 27.24 | 64.71 | 3.47 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 63.24 | 26.89 | 36.86 | 136.68 | 15.05 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 52.90 | 22.07 | 30.83 | 114.49 | 10.42 | 0.00 | 0.00 | 0.00 |
February | 44.92 | 14.64 | 30.27 | 104.54 | 7.98 | 0.00 | 0.00 | 0.00 |
March | 30.65 | 4.12 | 26.54 | 78.44 | 5.47 | 0.00 | 0.00 | 0.00 |
April | 22.85 | 0.01 | 22.84 | 60.68 | 2.33 | 0.00 | 0.00 | 0.00 |
May | 22.87 | 0.00 | 22.87 | 62.23 | 2.99 | 0.00 | 0.00 | 0.00 |
June | 22.79 | 0.00 | 22.79 | 61.49 | 3.32 | 0.00 | 0.00 | 0.00 |
July | 23.47 | 0.00 | 23.47 | 55.67 | 5.96 | 0.00 | 0.00 | 0.00 |
August | 22.85 | 0.04 | 22.82 | 54.29 | 4.58 | 0.00 | 0.00 | 0.00 |
September | 25.30 | 0.83 | 24.47 | 61.72 | 4.73 | 0.00 | 0.00 | 0.00 |
October | 33.10 | 5.28 | 27.82 | 74.91 | 6.05 | 0.00 | 0.00 | 0.00 |
November | 43.04 | 13.13 | 29.91 | 94.71 | 7.34 | 0.00 | 0.00 | 0.00 |
December | 52.87 | 22.49 | 30.37 | 112.72 | 11.83 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 33.09 | 6.86 | 26.23 | 77.87 | 6.08 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 22.79 | 0.00 | 22.79 | 54.29 | 2.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 52.90 | 22.49 | 30.83 | 114.49 | 11.83 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 52.90 | 22.07 | 30.83 | 114.49 | 10.42 | 0.00 | 0.00 | 0.00 |
February | 44.92 | 14.64 | 30.27 | 104.54 | 7.98 | 0.00 | 0.00 | 0.00 |
March | 30.65 | 4.12 | 26.54 | 78.44 | 5.47 | 0.00 | 0.00 | 0.00 |
April | 22.85 | 0.01 | 22.84 | 60.68 | 2.33 | 0.00 | 0.00 | 0.00 |
May | 22.87 | 0.00 | 22.87 | 62.23 | 2.99 | 0.00 | 0.00 | 0.00 |
June | 22.79 | 0.00 | 22.79 | 61.49 | 3.32 | 0.00 | 0.00 | 0.00 |
July | 23.47 | 0.00 | 23.47 | 55.67 | 5.96 | 0.00 | 0.00 | 0.00 |
August | 22.85 | 0.04 | 22.82 | 54.29 | 4.58 | 0.00 | 0.00 | 0.00 |
September | 25.30 | 0.83 | 24.47 | 61.72 | 4.73 | 0.00 | 0.00 | 0.00 |
October | 33.10 | 5.28 | 27.82 | 74.91 | 6.05 | 0.00 | 0.00 | 0.00 |
November | 43.04 | 13.13 | 29.91 | 94.71 | 7.34 | 0.00 | 0.00 | 0.00 |
December | 52.87 | 22.49 | 30.37 | 112.72 | 11.83 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 33.09 | 6.86 | 26.23 | 77.87 | 6.08 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 22.79 | 0.00 | 22.79 | 54.29 | 2.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 52.90 | 22.49 | 30.83 | 114.49 | 11.83 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 52.90 | 22.07 | 30.83 | 114.49 | 10.42 | 0.00 | 0.00 | 0.00 |
February | 44.92 | 14.64 | 30.27 | 104.54 | 7.98 | 0.00 | 0.00 | 0.00 |
March | 30.65 | 4.12 | 26.54 | 78.44 | 5.47 | 0.00 | 0.00 | 0.00 |
April | 22.85 | 0.01 | 22.84 | 60.68 | 2.33 | 0.00 | 0.00 | 0.00 |
May | 22.87 | 0.00 | 22.87 | 62.23 | 2.99 | 0.00 | 0.00 | 0.00 |
June | 22.79 | 0.00 | 22.79 | 61.49 | 3.32 | 0.00 | 0.00 | 0.00 |
July | 23.47 | 0.00 | 23.47 | 55.67 | 5.96 | 0.00 | 0.00 | 0.00 |
August | 22.85 | 0.04 | 22.82 | 54.29 | 4.58 | 0.00 | 0.00 | 0.00 |
September | 25.30 | 0.83 | 24.47 | 61.72 | 4.73 | 0.00 | 0.00 | 0.00 |
October | 33.10 | 5.28 | 27.82 | 74.91 | 6.05 | 0.00 | 0.00 | 0.00 |
November | 43.04 | 13.13 | 29.91 | 94.71 | 7.34 | 0.00 | 0.00 | 0.00 |
December | 52.87 | 22.49 | 30.37 | 112.72 | 11.83 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 33.09 | 6.86 | 26.23 | 77.87 | 6.08 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 22.79 | 0.00 | 22.79 | 54.29 | 2.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 52.90 | 22.49 | 30.83 | 114.49 | 11.83 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 52.90 | 22.07 | 30.83 | 114.49 | 10.42 | 0.00 | 0.00 | 0.00 |
February | 44.92 | 14.64 | 30.27 | 104.54 | 7.98 | 0.00 | 0.00 | 0.00 |
March | 30.65 | 4.12 | 26.54 | 78.44 | 5.47 | 0.00 | 0.00 | 0.00 |
April | 22.85 | 0.01 | 22.84 | 60.68 | 2.33 | 0.00 | 0.00 | 0.00 |
May | 22.87 | 0.00 | 22.87 | 62.23 | 2.99 | 0.00 | 0.00 | 0.00 |
June | 22.79 | 0.00 | 22.79 | 61.49 | 3.32 | 0.00 | 0.00 | 0.00 |
July | 23.47 | 0.00 | 23.47 | 55.67 | 5.96 | 0.00 | 0.00 | 0.00 |
August | 22.85 | 0.04 | 22.82 | 54.29 | 4.58 | 0.00 | 0.00 | 0.00 |
September | 25.30 | 0.83 | 24.47 | 61.72 | 4.73 | 0.00 | 0.00 | 0.00 |
October | 33.10 | 5.28 | 27.82 | 74.91 | 6.05 | 0.00 | 0.00 | 0.00 |
November | 43.04 | 13.13 | 29.91 | 94.71 | 7.34 | 0.00 | 0.00 | 0.00 |
December | 52.87 | 22.49 | 30.37 | 112.72 | 11.83 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 33.09 | 6.86 | 26.23 | 77.87 | 6.08 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 22.79 | 0.00 | 22.79 | 54.29 | 2.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 52.90 | 22.49 | 30.83 | 114.49 | 11.83 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 63.24 | 26.38 | 36.86 | 136.45 | 12.43 | 0.00 | 0.00 | 0.00 |
February | 53.70 | 17.51 | 36.19 | 124.50 | 9.57 | 0.00 | 0.00 | 0.00 |
March | 36.65 | 4.92 | 31.73 | 93.26 | 6.63 | 0.00 | 0.00 | 0.00 |
April | 27.32 | 0.01 | 27.31 | 71.93 | 2.84 | 0.00 | 0.00 | 0.00 |
May | 27.34 | 0.00 | 27.34 | 73.82 | 3.59 | 0.00 | 0.00 | 0.00 |
June | 27.24 | 0.00 | 27.24 | 72.93 | 3.98 | 0.00 | 0.00 | 0.00 |
July | 28.06 | 0.00 | 28.06 | 66.21 | 7.10 | 0.00 | 0.00 | 0.00 |
August | 27.32 | 0.04 | 27.28 | 64.52 | 5.50 | 0.00 | 0.00 | 0.00 |
September | 30.25 | 0.99 | 29.26 | 73.43 | 5.64 | 0.00 | 0.00 | 0.00 |
October | 39.57 | 6.31 | 33.26 | 89.25 | 7.19 | 0.00 | 0.00 | 0.00 |
November | 51.45 | 15.70 | 35.76 | 112.87 | 8.75 | 0.00 | 0.00 | 0.00 |
December | 63.21 | 26.89 | 36.32 | 134.38 | 14.09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 39.56 | 8.20 | 31.36 | 92.65 | 7.28 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 27.24 | 0.00 | 27.24 | 64.52 | 2.84 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 63.24 | 26.89 | 36.86 | 136.45 | 14.09 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 63.24 | 26.38 | 36.86 | 136.45 | 12.43 | 0.00 | 0.00 | 0.00 |
February | 53.70 | 17.51 | 36.19 | 124.50 | 9.57 | 0.00 | 0.00 | 0.00 |
March | 36.65 | 4.92 | 31.73 | 93.26 | 6.63 | 0.00 | 0.00 | 0.00 |
April | 27.32 | 0.01 | 27.31 | 71.93 | 2.84 | 0.00 | 0.00 | 0.00 |
May | 27.34 | 0.00 | 27.34 | 73.82 | 3.59 | 0.00 | 0.00 | 0.00 |
June | 27.24 | 0.00 | 27.24 | 72.93 | 3.98 | 0.00 | 0.00 | 0.00 |
July | 28.06 | 0.00 | 28.06 | 66.21 | 7.10 | 0.00 | 0.00 | 0.00 |
August | 27.32 | 0.04 | 27.28 | 64.52 | 5.50 | 0.00 | 0.00 | 0.00 |
September | 30.25 | 0.99 | 29.26 | 73.43 | 5.64 | 0.00 | 0.00 | 0.00 |
October | 39.57 | 6.31 | 33.26 | 89.25 | 7.19 | 0.00 | 0.00 | 0.00 |
November | 51.45 | 15.70 | 35.76 | 112.87 | 8.75 | 0.00 | 0.00 | 0.00 |
December | 63.21 | 26.89 | 36.32 | 134.38 | 14.09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 39.56 | 8.20 | 31.36 | 92.65 | 7.28 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 27.24 | 0.00 | 27.24 | 64.52 | 2.84 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 63.24 | 26.89 | 36.86 | 136.45 | 14.09 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 52.90 | 22.07 | 30.83 | 114.66 | 10.08 | 0.00 | 0.00 | 0.00 |
February | 44.92 | 14.64 | 30.27 | 104.78 | 7.61 | 0.00 | 0.00 | 0.00 |
March | 30.65 | 4.12 | 26.54 | 78.78 | 5.07 | 0.00 | 0.00 | 0.00 |
April | 22.85 | 0.01 | 22.84 | 61.24 | 2.07 | 0.00 | 0.00 | 0.00 |
May | 22.87 | 0.00 | 22.87 | 62.78 | 2.76 | 0.00 | 0.00 | 0.00 |
June | 22.79 | 0.00 | 22.79 | 62.06 | 3.05 | 0.00 | 0.00 | 0.00 |
July | 23.47 | 0.00 | 23.47 | 55.98 | 5.63 | 0.00 | 0.00 | 0.00 |
August | 22.85 | 0.04 | 22.82 | 54.63 | 4.23 | 0.00 | 0.00 | 0.00 |
September | 25.30 | 0.83 | 24.47 | 62.04 | 4.42 | 0.00 | 0.00 | 0.00 |
October | 33.10 | 5.28 | 27.82 | 75.14 | 5.72 | 0.00 | 0.00 | 0.00 |
November | 43.04 | 13.13 | 29.91 | 94.91 | 7.02 | 0.00 | 0.00 | 0.00 |
December | 52.87 | 22.49 | 30.37 | 112.86 | 11.50 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 33.09 | 6.86 | 26.23 | 78.19 | 5.77 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 22.79 | 0.00 | 22.79 | 54.63 | 2.07 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 52.90 | 22.49 | 30.83 | 114.66 | 11.50 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 52.90 | 22.07 | 30.83 | 114.66 | 10.08 | 0.00 | 0.00 | 0.00 |
February | 44.92 | 14.64 | 30.27 | 104.78 | 7.61 | 0.00 | 0.00 | 0.00 |
March | 30.65 | 4.12 | 26.54 | 78.78 | 5.07 | 0.00 | 0.00 | 0.00 |
April | 22.85 | 0.01 | 22.84 | 61.24 | 2.07 | 0.00 | 0.00 | 0.00 |
May | 22.87 | 0.00 | 22.87 | 62.78 | 2.76 | 0.00 | 0.00 | 0.00 |
June | 22.79 | 0.00 | 22.79 | 62.06 | 3.05 | 0.00 | 0.00 | 0.00 |
July | 23.47 | 0.00 | 23.47 | 55.98 | 5.63 | 0.00 | 0.00 | 0.00 |
August | 22.85 | 0.04 | 22.82 | 54.63 | 4.23 | 0.00 | 0.00 | 0.00 |
September | 25.30 | 0.83 | 24.47 | 62.04 | 4.42 | 0.00 | 0.00 | 0.00 |
October | 33.10 | 5.28 | 27.82 | 75.14 | 5.72 | 0.00 | 0.00 | 0.00 |
November | 43.04 | 13.13 | 29.91 | 94.91 | 7.02 | 0.00 | 0.00 | 0.00 |
December | 52.87 | 22.49 | 30.37 | 112.86 | 11.50 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 33.09 | 6.86 | 26.23 | 78.19 | 5.77 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 22.79 | 0.00 | 22.79 | 54.63 | 2.07 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 52.90 | 22.49 | 30.83 | 114.66 | 11.50 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 63.24 | 26.38 | 36.86 | 136.68 | 12.03 | 0.00 | 0.00 | 0.00 |
February | 53.70 | 17.51 | 36.19 | 124.79 | 9.13 | 0.00 | 0.00 | 0.00 |
March | 36.65 | 4.92 | 31.73 | 93.65 | 6.17 | 0.00 | 0.00 | 0.00 |
April | 27.32 | 0.01 | 27.31 | 72.58 | 2.54 | 0.00 | 0.00 | 0.00 |
May | 27.34 | 0.00 | 27.34 | 74.45 | 3.31 | 0.17 | 0.00 | 0.00 |
June | 27.24 | 0.00 | 27.24 | 73.58 | 3.67 | 0.00 | 0.00 | 0.00 |
July | 28.06 | 0.00 | 28.06 | 66.58 | 6.72 | 0.00 | 0.00 | 0.00 |
August | 27.32 | 0.04 | 27.28 | 64.92 | 5.09 | 0.00 | 0.00 | 0.00 |
September | 30.25 | 0.99 | 29.26 | 73.81 | 5.29 | 0.00 | 0.00 | 0.00 |
October | 39.57 | 6.31 | 33.26 | 89.53 | 6.81 | 0.00 | 0.00 | 0.00 |
November | 51.45 | 15.70 | 35.76 | 113.12 | 8.36 | 0.00 | 0.00 | 0.00 |
December | 63.21 | 26.89 | 36.32 | 134.57 | 13.70 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 39.56 | 8.20 | 31.36 | 93.04 | 6.90 | 0.17 | 0.00 | 0.00 |
Minimum of Months | 27.24 | 0.00 | 27.24 | 64.92 | 2.54 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 63.24 | 26.89 | 36.86 | 136.68 | 13.70 | 0.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 52.90 | 22.07 | 30.83 | 114.71 | 10.02 | 0.00 | 0.00 | 0.00 |
February | 44.92 | 14.64 | 30.27 | 104.82 | 7.55 | 0.00 | 0.00 | 0.00 |
March | 30.65 | 4.12 | 26.54 | 78.83 | 5.01 | 0.00 | 0.00 | 0.00 |
April | 22.85 | 0.01 | 22.84 | 61.30 | 2.04 | 0.00 | 0.00 | 0.00 |
May | 22.87 | 0.00 | 22.87 | 62.84 | 2.72 | 0.00 | 0.00 | 0.00 |
June | 22.79 | 0.00 | 22.79 | 62.12 | 3.02 | 0.00 | 0.00 | 0.00 |
July | 23.47 | 0.00 | 23.47 | 56.02 | 5.59 | 0.00 | 0.00 | 0.00 |
August | 22.85 | 0.04 | 22.82 | 54.67 | 4.18 | 0.00 | 0.00 | 0.00 |
September | 25.30 | 0.83 | 24.47 | 62.09 | 4.38 | 0.00 | 0.00 | 0.00 |
October | 33.10 | 5.28 | 27.82 | 75.19 | 5.67 | 0.00 | 0.00 | 0.00 |
November | 43.04 | 13.13 | 29.91 | 94.96 | 6.96 | 0.00 | 0.00 | 0.00 |
December | 52.87 | 22.49 | 30.37 | 112.91 | 11.44 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 33.09 | 6.86 | 26.23 | 78.24 | 5.72 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 22.79 | 0.00 | 22.79 | 54.67 | 2.04 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 52.90 | 22.49 | 30.83 | 114.71 | 11.44 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 52.90 | 22.07 | 30.83 | 114.71 | 10.02 | 0.00 | 0.00 | 0.00 |
February | 44.92 | 14.64 | 30.27 | 104.82 | 7.55 | 0.00 | 0.00 | 0.00 |
March | 30.65 | 4.12 | 26.54 | 78.83 | 5.01 | 0.00 | 0.00 | 0.00 |
April | 22.85 | 0.01 | 22.84 | 61.30 | 2.04 | 0.00 | 0.00 | 0.00 |
May | 22.87 | 0.00 | 22.87 | 62.84 | 2.72 | 0.00 | 0.00 | 0.00 |
June | 22.79 | 0.00 | 22.79 | 62.12 | 3.02 | 0.00 | 0.00 | 0.00 |
July | 23.47 | 0.00 | 23.47 | 56.02 | 5.59 | 0.00 | 0.00 | 0.00 |
August | 22.85 | 0.04 | 22.82 | 54.67 | 4.18 | 0.00 | 0.00 | 0.00 |
September | 25.30 | 0.83 | 24.47 | 62.09 | 4.38 | 0.00 | 0.00 | 0.00 |
October | 33.10 | 5.28 | 27.82 | 75.19 | 5.67 | 0.00 | 0.00 | 0.00 |
November | 43.04 | 13.13 | 29.91 | 94.96 | 6.96 | 0.00 | 0.00 | 0.00 |
December | 52.87 | 22.49 | 30.37 | 112.91 | 11.44 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 33.09 | 6.86 | 26.23 | 78.24 | 5.72 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 22.79 | 0.00 | 22.79 | 54.67 | 2.04 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 52.90 | 22.49 | 30.83 | 114.71 | 11.44 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 63.24 | 26.38 | 36.86 | 136.74 | 11.96 | 0.00 | 0.00 | 0.00 |
February | 53.70 | 17.51 | 36.19 | 124.85 | 9.07 | 0.00 | 0.00 | 0.00 |
March | 36.65 | 4.92 | 31.73 | 93.71 | 6.10 | 0.00 | 0.00 | 0.00 |
April | 27.32 | 0.01 | 27.31 | 72.65 | 2.50 | 0.00 | 0.00 | 0.00 |
May | 27.34 | 0.00 | 27.34 | 74.52 | 3.27 | 0.17 | 0.00 | 0.00 |
June | 27.24 | 0.00 | 27.24 | 73.65 | 3.63 | 0.00 | 0.00 | 0.00 |
July | 28.06 | 0.00 | 28.06 | 66.63 | 6.66 | 0.00 | 0.00 | 0.00 |
August | 27.32 | 0.04 | 27.28 | 64.97 | 5.03 | 0.00 | 0.00 | 0.00 |
September | 30.25 | 0.99 | 29.26 | 73.86 | 5.23 | 0.00 | 0.00 | 0.00 |
October | 39.57 | 6.31 | 33.26 | 89.59 | 6.75 | 0.00 | 0.00 | 0.00 |
November | 51.45 | 15.70 | 35.76 | 113.18 | 8.29 | 0.00 | 0.00 | 0.00 |
December | 63.21 | 26.89 | 36.32 | 134.63 | 13.62 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 39.56 | 8.20 | 31.36 | 93.10 | 6.85 | 0.17 | 0.00 | 0.00 |
Minimum of Months | 27.24 | 0.00 | 27.24 | 64.97 | 2.50 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 63.24 | 26.89 | 36.86 | 136.74 | 13.62 | 0.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 52.90 | 22.07 | 30.83 | 114.66 | 10.03 | 0.00 | 0.00 | 0.00 |
February | 44.92 | 14.64 | 30.27 | 104.74 | 7.60 | 0.00 | 0.00 | 0.00 |
March | 30.65 | 4.12 | 26.54 | 78.71 | 5.09 | 0.00 | 0.00 | 0.00 |
April | 22.85 | 0.01 | 22.84 | 61.11 | 2.11 | 0.00 | 0.00 | 0.00 |
May | 22.87 | 0.00 | 22.87 | 62.63 | 2.79 | 0.00 | 0.00 | 0.00 |
June | 22.79 | 0.00 | 22.79 | 61.92 | 3.10 | 0.00 | 0.00 | 0.00 |
July | 23.47 | 0.00 | 23.47 | 55.89 | 5.69 | 0.00 | 0.00 | 0.00 |
August | 22.85 | 0.04 | 22.82 | 54.56 | 4.25 | 0.00 | 0.00 | 0.00 |
September | 25.30 | 0.83 | 24.47 | 61.95 | 4.47 | 0.00 | 0.00 | 0.00 |
October | 33.10 | 5.28 | 27.82 | 75.11 | 5.71 | 0.00 | 0.00 | 0.00 |
November | 43.04 | 13.13 | 29.91 | 94.90 | 6.98 | 0.00 | 0.00 | 0.00 |
December | 52.87 | 22.49 | 30.37 | 112.88 | 11.44 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 33.09 | 6.86 | 26.23 | 78.13 | 5.77 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 22.79 | 0.00 | 22.79 | 54.56 | 2.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 52.90 | 22.49 | 30.83 | 114.66 | 11.44 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 52.90 | 22.07 | 30.83 | 114.66 | 10.03 | 0.00 | 0.00 | 0.00 |
February | 44.92 | 14.64 | 30.27 | 104.74 | 7.60 | 0.00 | 0.00 | 0.00 |
March | 30.65 | 4.12 | 26.54 | 78.71 | 5.09 | 0.00 | 0.00 | 0.00 |
April | 22.85 | 0.01 | 22.84 | 61.11 | 2.11 | 0.00 | 0.00 | 0.00 |
May | 22.87 | 0.00 | 22.87 | 62.63 | 2.79 | 0.00 | 0.00 | 0.00 |
June | 22.79 | 0.00 | 22.79 | 61.92 | 3.10 | 0.00 | 0.00 | 0.00 |
July | 23.47 | 0.00 | 23.47 | 55.89 | 5.69 | 0.00 | 0.00 | 0.00 |
August | 22.85 | 0.04 | 22.82 | 54.56 | 4.25 | 0.00 | 0.00 | 0.00 |
September | 25.30 | 0.83 | 24.47 | 61.95 | 4.47 | 0.00 | 0.00 | 0.00 |
October | 33.10 | 5.28 | 27.82 | 75.11 | 5.71 | 0.00 | 0.00 | 0.00 |
November | 43.04 | 13.13 | 29.91 | 94.90 | 6.98 | 0.00 | 0.00 | 0.00 |
December | 52.87 | 22.49 | 30.37 | 112.88 | 11.44 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 33.09 | 6.86 | 26.23 | 78.13 | 5.77 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 22.79 | 0.00 | 22.79 | 54.56 | 2.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 52.90 | 22.49 | 30.83 | 114.66 | 11.44 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 63.24 | 26.38 | 36.86 | 136.68 | 11.98 | 0.00 | 0.00 | 0.00 |
February | 53.70 | 17.51 | 36.19 | 124.74 | 9.13 | 0.00 | 0.00 | 0.00 |
March | 36.65 | 4.92 | 31.73 | 93.58 | 6.20 | 0.00 | 0.00 | 0.00 |
April | 27.32 | 0.01 | 27.31 | 72.42 | 2.59 | 0.00 | 0.00 | 0.00 |
May | 27.34 | 0.00 | 27.34 | 74.28 | 3.35 | 0.00 | 0.00 | 0.00 |
June | 27.24 | 0.00 | 27.24 | 73.41 | 3.73 | 0.00 | 0.00 | 0.00 |
July | 28.06 | 0.00 | 28.06 | 66.47 | 6.78 | 0.00 | 0.00 | 0.00 |
August | 27.32 | 0.04 | 27.28 | 64.83 | 5.13 | 0.00 | 0.00 | 0.00 |
September | 30.25 | 0.99 | 29.26 | 73.70 | 5.34 | 0.00 | 0.00 | 0.00 |
October | 39.57 | 6.31 | 33.26 | 89.50 | 6.79 | 0.00 | 0.00 | 0.00 |
November | 51.45 | 15.70 | 35.76 | 113.11 | 8.32 | 0.00 | 0.00 | 0.00 |
December | 63.21 | 26.89 | 36.32 | 134.59 | 13.63 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 39.56 | 8.20 | 31.36 | 92.96 | 6.92 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 27.24 | 0.00 | 27.24 | 64.83 | 2.59 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 63.24 | 26.89 | 36.86 | 136.68 | 13.63 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 52.90 | 22.07 | 30.83 | 113.59 | 10.46 | 0.00 | 0.00 | 0.00 |
February | 44.92 | 14.64 | 30.27 | 103.39 | 8.21 | 0.00 | 0.00 | 0.00 |
March | 30.65 | 4.12 | 26.54 | 77.20 | 5.79 | 0.00 | 0.00 | 0.00 |
April | 22.85 | 0.01 | 22.84 | 59.05 | 2.71 | 0.00 | 0.00 | 0.00 |
May | 22.87 | 0.00 | 22.87 | 60.62 | 3.32 | 5.50 | 0.00 | 0.00 |
June | 22.79 | 0.00 | 22.79 | 59.89 | 3.78 | 0.00 | 0.00 | 0.00 |
July | 23.47 | 0.00 | 23.47 | 54.39 | 6.51 | 0.00 | 0.00 | 0.00 |
August | 22.85 | 0.04 | 22.82 | 53.11 | 4.99 | 0.00 | 0.00 | 0.00 |
September | 25.30 | 0.83 | 24.47 | 60.39 | 5.23 | 0.00 | 0.00 | 0.00 |
October | 33.10 | 5.28 | 27.82 | 73.98 | 6.26 | 0.00 | 0.00 | 0.00 |
November | 43.04 | 13.13 | 29.91 | 93.79 | 7.45 | 0.00 | 0.00 | 0.00 |
December | 52.87 | 22.49 | 30.37 | 111.91 | 11.83 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 33.09 | 6.86 | 26.23 | 76.65 | 6.38 | 5.50 | 0.00 | 0.00 |
Minimum of Months | 22.79 | 0.00 | 22.79 | 53.11 | 2.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 52.90 | 22.49 | 30.83 | 113.59 | 11.83 | 5.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 52.90 | 22.07 | 30.83 | 113.59 | 10.46 | 0.00 | 0.00 | 0.00 |
February | 44.92 | 14.64 | 30.27 | 103.39 | 8.21 | 0.00 | 0.00 | 0.00 |
March | 30.65 | 4.12 | 26.54 | 77.20 | 5.79 | 0.00 | 0.00 | 0.00 |
April | 22.85 | 0.01 | 22.84 | 59.05 | 2.71 | 0.00 | 0.00 | 0.00 |
May | 22.87 | 0.00 | 22.87 | 60.62 | 3.32 | 5.50 | 0.00 | 0.00 |
June | 22.79 | 0.00 | 22.79 | 59.89 | 3.78 | 0.00 | 0.00 | 0.00 |
July | 23.47 | 0.00 | 23.47 | 54.39 | 6.51 | 0.00 | 0.00 | 0.00 |
August | 22.85 | 0.04 | 22.82 | 53.11 | 4.99 | 0.00 | 0.00 | 0.00 |
September | 25.30 | 0.83 | 24.47 | 60.39 | 5.23 | 0.00 | 0.00 | 0.00 |
October | 33.10 | 5.28 | 27.82 | 73.98 | 6.26 | 0.00 | 0.00 | 0.00 |
November | 43.04 | 13.13 | 29.91 | 93.79 | 7.45 | 0.00 | 0.00 | 0.00 |
December | 52.87 | 22.49 | 30.37 | 111.91 | 11.83 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 33.09 | 6.86 | 26.23 | 76.65 | 6.38 | 5.50 | 0.00 | 0.00 |
Minimum of Months | 22.79 | 0.00 | 22.79 | 53.11 | 2.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 52.90 | 22.49 | 30.83 | 113.59 | 11.83 | 5.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 63.24 | 26.38 | 36.86 | 135.39 | 12.49 | 0.00 | 0.00 | 0.00 |
February | 53.70 | 17.51 | 36.19 | 123.13 | 9.86 | 0.00 | 0.00 | 0.00 |
March | 36.65 | 4.92 | 31.73 | 91.77 | 7.03 | 0.00 | 0.00 | 0.00 |
April | 27.32 | 0.01 | 27.31 | 69.98 | 3.32 | 0.00 | 0.00 | 0.00 |
May | 27.34 | 0.00 | 27.34 | 71.88 | 4.00 | 7.00 | 0.00 | 0.00 |
June | 27.24 | 0.00 | 27.24 | 71.00 | 4.54 | 0.00 | 0.00 | 0.00 |
July | 28.06 | 0.00 | 28.06 | 64.68 | 7.76 | 0.00 | 0.00 | 0.00 |
August | 27.32 | 0.04 | 27.28 | 63.10 | 6.00 | 0.00 | 0.00 | 0.00 |
September | 30.25 | 0.99 | 29.26 | 71.84 | 6.25 | 0.00 | 0.00 | 0.00 |
October | 39.57 | 6.31 | 33.26 | 88.14 | 7.46 | 0.00 | 0.00 | 0.00 |
November | 51.45 | 15.70 | 35.76 | 111.77 | 8.89 | 0.00 | 0.00 | 0.00 |
December | 63.21 | 26.89 | 36.32 | 133.43 | 14.09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 39.56 | 8.20 | 31.36 | 91.19 | 7.64 | 7.00 | 0.00 | 0.00 |
Minimum of Months | 27.24 | 0.00 | 27.24 | 63.10 | 3.32 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 63.24 | 26.89 | 36.86 | 135.39 | 14.09 | 7.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.141674E+09 | 59108158.25 | 82566185.41 | 0.306594E+09 | 24948829.21 |
February | 0.108661E+09 | 35427459.24 | 73233200.81 | 0.252882E+09 | 16902632.27 |
March | 82099843.80 | 11026068.83 | 71073774.97 | 0.210029E+09 | 12758080.49 |
April | 59234895.43 | 26590.99 | 59208304.43 | 0.159328E+09 | 5513590.85 |
May | 61251186.16 | 0.00 | 61251186.16 | 0.169388E+09 | 7095833.69 |
June | 59061954.14 | 0.00 | 59061954.14 | 0.161318E+09 | 7550129.43 |
July | 62870807.71 | 0.00 | 62870807.71 | 0.150794E+09 | 14092741.38 |
August | 61205207.47 | 94593.94 | 61110613.53 | 0.145573E+09 | 10906466.87 |
September | 65572777.12 | 2141655.19 | 63431121.93 | 0.160888E+09 | 10708105.78 |
October | 88647948.83 | 14134216.17 | 74513732.66 | 0.200994E+09 | 14024121.38 |
November | 0.111553E+09 | 34033352.30 | 77519716.59 | 0.245404E+09 | 16923159.67 |
December | 0.141602E+09 | 60245791.02 | 81356055.69 | 0.301571E+09 | 28854849.57 |
Annual Sum or Average | 0.104343E+10 | 0.216238E+09 | 0.827197E+09 | 0.246476E+10 | 0.170279E+09 |
Minimum of Months | 59061954.14 | 0.00 | 59061954.14 | 0.145573E+09 | 5513590.85 |
Maximum of Months | 0.141674E+09 | 60245791.02 | 82566185.41 | 0.306594E+09 | 28854849.57 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.141674E+09 | 59108158.25 | 82566185.41 | 0.306594E+09 | 24948829.21 |
February | 0.108661E+09 | 35427459.24 | 73233200.81 | 0.252882E+09 | 16902632.27 |
March | 82099843.80 | 11026068.83 | 71073774.97 | 0.210029E+09 | 12758080.49 |
April | 59234895.43 | 26590.99 | 59208304.43 | 0.159328E+09 | 5513590.85 |
May | 61251186.16 | 0.00 | 61251186.16 | 0.169388E+09 | 7095833.69 |
June | 59061954.14 | 0.00 | 59061954.14 | 0.161318E+09 | 7550129.43 |
July | 62870807.71 | 0.00 | 62870807.71 | 0.150794E+09 | 14092741.38 |
August | 61205207.47 | 94593.94 | 61110613.53 | 0.145573E+09 | 10906466.87 |
September | 65572777.12 | 2141655.19 | 63431121.93 | 0.160888E+09 | 10708105.78 |
October | 88647948.83 | 14134216.17 | 74513732.66 | 0.200994E+09 | 14024121.38 |
November | 0.111553E+09 | 34033352.30 | 77519716.59 | 0.245404E+09 | 16923159.67 |
December | 0.141602E+09 | 60245791.02 | 81356055.69 | 0.301571E+09 | 28854849.57 |
Annual Sum or Average | 0.104343E+10 | 0.216238E+09 | 0.827197E+09 | 0.246476E+10 | 0.170279E+09 |
Minimum of Months | 59061954.14 | 0.00 | 59061954.14 | 0.145573E+09 | 5513590.85 |
Maximum of Months | 0.141674E+09 | 60245791.02 | 82566185.41 | 0.306594E+09 | 28854849.57 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.141674E+09 | 59108158.25 | 82566185.41 | 0.306594E+09 | 24948829.21 |
February | 0.108661E+09 | 35427459.24 | 73233200.81 | 0.252882E+09 | 16902632.27 |
March | 82099843.80 | 11026068.83 | 71073774.97 | 0.210029E+09 | 12758080.49 |
April | 59234895.43 | 26590.99 | 59208304.43 | 0.159328E+09 | 5513590.85 |
May | 61251186.16 | 0.00 | 61251186.16 | 0.169388E+09 | 7095833.69 |
June | 59061954.14 | 0.00 | 59061954.14 | 0.161318E+09 | 7550129.43 |
July | 62870807.71 | 0.00 | 62870807.71 | 0.150794E+09 | 14092741.38 |
August | 61205207.47 | 94593.94 | 61110613.53 | 0.145573E+09 | 10906466.87 |
September | 65572777.12 | 2141655.19 | 63431121.93 | 0.160888E+09 | 10708105.78 |
October | 88647948.83 | 14134216.17 | 74513732.66 | 0.200994E+09 | 14024121.38 |
November | 0.111553E+09 | 34033352.30 | 77519716.59 | 0.245404E+09 | 16923159.67 |
December | 0.141602E+09 | 60245791.02 | 81356055.69 | 0.301571E+09 | 28854849.57 |
Annual Sum or Average | 0.104343E+10 | 0.216238E+09 | 0.827197E+09 | 0.246476E+10 | 0.170279E+09 |
Minimum of Months | 59061954.14 | 0.00 | 59061954.14 | 0.145573E+09 | 5513590.85 |
Maximum of Months | 0.141674E+09 | 60245791.02 | 82566185.41 | 0.306594E+09 | 28854849.57 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.141674E+09 | 59108158.25 | 82566185.41 | 0.306594E+09 | 24948829.21 |
February | 0.108661E+09 | 35427459.24 | 73233200.81 | 0.252882E+09 | 16902632.27 |
March | 82099843.80 | 11026068.83 | 71073774.97 | 0.210029E+09 | 12758080.49 |
April | 59234895.43 | 26590.99 | 59208304.43 | 0.159328E+09 | 5513590.85 |
May | 61251186.16 | 0.00 | 61251186.16 | 0.169388E+09 | 7095833.69 |
June | 59061954.14 | 0.00 | 59061954.14 | 0.161318E+09 | 7550129.43 |
July | 62870807.71 | 0.00 | 62870807.71 | 0.150794E+09 | 14092741.38 |
August | 61205207.47 | 94593.94 | 61110613.53 | 0.145573E+09 | 10906466.87 |
September | 65572777.12 | 2141655.19 | 63431121.93 | 0.160888E+09 | 10708105.78 |
October | 88647948.83 | 14134216.17 | 74513732.66 | 0.200994E+09 | 14024121.38 |
November | 0.111553E+09 | 34033352.30 | 77519716.59 | 0.245404E+09 | 16923159.67 |
December | 0.141602E+09 | 60245791.02 | 81356055.69 | 0.301571E+09 | 28854849.57 |
Annual Sum or Average | 0.104343E+10 | 0.216238E+09 | 0.827197E+09 | 0.246476E+10 | 0.170279E+09 |
Minimum of Months | 59061954.14 | 0.00 | 59061954.14 | 0.145573E+09 | 5513590.85 |
Maximum of Months | 0.141674E+09 | 60245791.02 | 82566185.41 | 0.306594E+09 | 28854849.57 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.170314E+09 | 71057105.98 | 99257266.00 | 0.367347E+09 | 30045160.73 |
February | 0.130627E+09 | 42589260.10 | 88037581.69 | 0.302701E+09 | 20483373.28 |
March | 98696651.59 | 13255032.20 | 85441619.39 | 0.250877E+09 | 15612659.02 |
April | 71209463.57 | 31966.47 | 71177497.10 | 0.189672E+09 | 6772185.86 |
May | 73633355.44 | 0.00 | 73633355.44 | 0.201813E+09 | 8579191.90 |
June | 71001561.52 | 0.00 | 71001561.52 | 0.192162E+09 | 9127645.28 |
July | 75580389.88 | 0.00 | 75580389.88 | 0.180166E+09 | 16939771.87 |
August | 73578081.98 | 113716.47 | 73464365.50 | 0.173775E+09 | 13209112.01 |
September | 78828573.09 | 2574599.25 | 76253973.83 | 0.192294E+09 | 12899377.38 |
October | 0.106568E+09 | 16991503.81 | 89576978.12 | 0.240660E+09 | 16852151.11 |
November | 0.134104E+09 | 40913328.93 | 93190633.57 | 0.293954E+09 | 20345984.68 |
December | 0.170227E+09 | 72424715.70 | 97802503.77 | 0.361408E+09 | 34646659.47 |
Annual Sum or Average | 0.125437E+10 | 0.259951E+09 | 0.994418E+09 | 0.294683E+10 | 0.205513E+09 |
Minimum of Months | 71001561.52 | 0.00 | 71001561.52 | 0.173775E+09 | 6772185.86 |
Maximum of Months | 0.170314E+09 | 72424715.70 | 99257266.00 | 0.367347E+09 | 34646659.47 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.170314E+09 | 71057105.98 | 99257266.00 | 0.367347E+09 | 30045160.73 |
February | 0.130627E+09 | 42589260.10 | 88037581.69 | 0.302701E+09 | 20483373.28 |
March | 98696651.59 | 13255032.20 | 85441619.39 | 0.250877E+09 | 15612659.02 |
April | 71209463.57 | 31966.47 | 71177497.10 | 0.189672E+09 | 6772185.86 |
May | 73633355.44 | 0.00 | 73633355.44 | 0.201813E+09 | 8579191.90 |
June | 71001561.52 | 0.00 | 71001561.52 | 0.192162E+09 | 9127645.28 |
July | 75580389.88 | 0.00 | 75580389.88 | 0.180166E+09 | 16939771.87 |
August | 73578081.98 | 113716.47 | 73464365.50 | 0.173775E+09 | 13209112.01 |
September | 78828573.09 | 2574599.25 | 76253973.83 | 0.192294E+09 | 12899377.38 |
October | 0.106568E+09 | 16991503.81 | 89576978.12 | 0.240660E+09 | 16852151.11 |
November | 0.134104E+09 | 40913328.93 | 93190633.57 | 0.293954E+09 | 20345984.68 |
December | 0.170227E+09 | 72424715.70 | 97802503.77 | 0.361408E+09 | 34646659.47 |
Annual Sum or Average | 0.125437E+10 | 0.259951E+09 | 0.994418E+09 | 0.294683E+10 | 0.205513E+09 |
Minimum of Months | 71001561.52 | 0.00 | 71001561.52 | 0.173775E+09 | 6772185.86 |
Maximum of Months | 0.170314E+09 | 72424715.70 | 99257266.00 | 0.367347E+09 | 34646659.47 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.141674E+09 | 59108158.25 | 82566185.41 | 0.307820E+09 | 24694510.97 |
February | 0.108661E+09 | 35427459.24 | 73233200.81 | 0.254515E+09 | 16535822.27 |
March | 82099843.80 | 11026068.83 | 71073774.97 | 0.212513E+09 | 12216872.17 |
April | 59234895.43 | 26590.99 | 59208304.43 | 0.162335E+09 | 5102924.94 |
May | 61251186.16 | 0.00 | 61251186.16 | 0.172208E+09 | 6829731.91 |
June | 59061954.14 | 0.00 | 59061954.14 | 0.164226E+09 | 7157189.66 |
July | 62870807.71 | 0.00 | 62870807.71 | 0.152829E+09 | 13645814.91 |
August | 61205207.47 | 94593.94 | 61110613.53 | 0.147697E+09 | 10509958.27 |
September | 65572777.12 | 2141655.19 | 63431121.93 | 0.162920E+09 | 10321634.41 |
October | 88647948.83 | 14134216.17 | 74513732.66 | 0.202410E+09 | 13810552.66 |
November | 0.111553E+09 | 34033352.30 | 77519716.59 | 0.246750E+09 | 16730601.19 |
December | 0.141602E+09 | 60245791.02 | 81356055.69 | 0.302616E+09 | 28666513.17 |
Annual Sum or Average | 0.104343E+10 | 0.216238E+09 | 0.827197E+09 | 0.248884E+10 | 0.166222E+09 |
Minimum of Months | 59061954.14 | 0.00 | 59061954.14 | 0.147697E+09 | 5102924.94 |
Maximum of Months | 0.141674E+09 | 60245791.02 | 82566185.41 | 0.307820E+09 | 28666513.17 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.141674E+09 | 59108158.25 | 82566185.41 | 0.307820E+09 | 24694510.97 |
February | 0.108661E+09 | 35427459.24 | 73233200.81 | 0.254515E+09 | 16535822.27 |
March | 82099843.80 | 11026068.83 | 71073774.97 | 0.212513E+09 | 12216872.17 |
April | 59234895.43 | 26590.99 | 59208304.43 | 0.162335E+09 | 5102924.94 |
May | 61251186.16 | 0.00 | 61251186.16 | 0.172208E+09 | 6829731.91 |
June | 59061954.14 | 0.00 | 59061954.14 | 0.164226E+09 | 7157189.66 |
July | 62870807.71 | 0.00 | 62870807.71 | 0.152829E+09 | 13645814.91 |
August | 61205207.47 | 94593.94 | 61110613.53 | 0.147697E+09 | 10509958.27 |
September | 65572777.12 | 2141655.19 | 63431121.93 | 0.162920E+09 | 10321634.41 |
October | 88647948.83 | 14134216.17 | 74513732.66 | 0.202410E+09 | 13810552.66 |
November | 0.111553E+09 | 34033352.30 | 77519716.59 | 0.246750E+09 | 16730601.19 |
December | 0.141602E+09 | 60245791.02 | 81356055.69 | 0.302616E+09 | 28666513.17 |
Annual Sum or Average | 0.104343E+10 | 0.216238E+09 | 0.827197E+09 | 0.248884E+10 | 0.166222E+09 |
Minimum of Months | 59061954.14 | 0.00 | 59061954.14 | 0.147697E+09 | 5102924.94 |
Maximum of Months | 0.141674E+09 | 60245791.02 | 82566185.41 | 0.307820E+09 | 28666513.17 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.170314E+09 | 71057105.98 | 99257266.00 | 0.368862E+09 | 29728422.83 |
February | 0.130627E+09 | 42589260.10 | 88037581.69 | 0.304667E+09 | 20029970.47 |
March | 98696651.59 | 13255032.20 | 85441619.39 | 0.253816E+09 | 14952566.05 |
April | 71209463.57 | 31966.47 | 71177497.10 | 0.193234E+09 | 6291278.52 |
May | 73633355.44 | 0.00 | 73633355.44 | 0.205158E+09 | 8262919.21 |
June | 71001561.52 | 0.00 | 71001561.52 | 0.195612E+09 | 8660513.15 |
July | 75580389.88 | 0.00 | 75580389.88 | 0.182609E+09 | 16402914.96 |
August | 73578081.98 | 113716.47 | 73464365.50 | 0.176307E+09 | 12735908.84 |
September | 78828573.09 | 2574599.25 | 76253973.83 | 0.194739E+09 | 12437433.59 |
October | 0.106568E+09 | 16991503.81 | 89576978.12 | 0.242393E+09 | 16593377.62 |
November | 0.134104E+09 | 40913328.93 | 93190633.57 | 0.295620E+09 | 20114701.80 |
December | 0.170227E+09 | 72424715.70 | 97802503.77 | 0.362717E+09 | 34409519.95 |
Annual Sum or Average | 0.125437E+10 | 0.259951E+09 | 0.994418E+09 | 0.297573E+10 | 0.200620E+09 |
Minimum of Months | 71001561.52 | 0.00 | 71001561.52 | 0.176307E+09 | 6291278.52 |
Maximum of Months | 0.170314E+09 | 72424715.70 | 99257266.00 | 0.368862E+09 | 34409519.95 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.141674E+09 | 59108158.25 | 82566185.41 | 0.306938E+09 | 30434517.10 |
February | 0.108661E+09 | 35427459.24 | 73233200.81 | 0.253392E+09 | 21644754.77 |
March | 82099843.80 | 11026068.83 | 71073774.97 | 0.210467E+09 | 17141032.82 |
April | 59234895.43 | 26590.99 | 59208304.43 | 0.157028E+09 | 7471253.13 |
May | 61251186.16 | 0.00 | 61251186.16 | 0.166791E+09 | 9537586.22 |
June | 59061954.14 | 0.00 | 59061954.14 | 0.159369E+09 | 10069063.37 |
July | 62870807.71 | 0.00 | 62870807.71 | 0.149543E+09 | 18099651.53 |
August | 61205207.47 | 94593.94 | 61110613.53 | 0.145641E+09 | 14854135.77 |
September | 65572777.12 | 2141655.19 | 63431121.93 | 0.160029E+09 | 14321859.55 |
October | 88647948.83 | 14134216.17 | 74513732.66 | 0.200709E+09 | 18665733.94 |
November | 0.111553E+09 | 34033352.30 | 77519716.59 | 0.245717E+09 | 21446383.45 |
December | 0.141602E+09 | 60245791.02 | 81356055.69 | 0.302142E+09 | 34279053.30 |
Annual Sum or Average | 0.104343E+10 | 0.216238E+09 | 0.827197E+09 | 0.245777E+10 | 0.217965E+09 |
Minimum of Months | 59061954.14 | 0.00 | 59061954.14 | 0.145641E+09 | 7471253.13 |
Maximum of Months | 0.141674E+09 | 60245791.02 | 82566185.41 | 0.306938E+09 | 34279053.30 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.141674E+09 | 59108158.25 | 82566185.41 | 0.306938E+09 | 30434517.10 |
February | 0.108661E+09 | 35427459.24 | 73233200.81 | 0.253392E+09 | 21644754.77 |
March | 82099843.80 | 11026068.83 | 71073774.97 | 0.210467E+09 | 17141032.82 |
April | 59234895.43 | 26590.99 | 59208304.43 | 0.157028E+09 | 7471253.13 |
May | 61251186.16 | 0.00 | 61251186.16 | 0.166791E+09 | 9537586.22 |
June | 59061954.14 | 0.00 | 59061954.14 | 0.159369E+09 | 10069063.37 |
July | 62870807.71 | 0.00 | 62870807.71 | 0.149543E+09 | 18099651.53 |
August | 61205207.47 | 94593.94 | 61110613.53 | 0.145641E+09 | 14854135.77 |
September | 65572777.12 | 2141655.19 | 63431121.93 | 0.160029E+09 | 14321859.55 |
October | 88647948.83 | 14134216.17 | 74513732.66 | 0.200709E+09 | 18665733.94 |
November | 0.111553E+09 | 34033352.30 | 77519716.59 | 0.245717E+09 | 21446383.45 |
December | 0.141602E+09 | 60245791.02 | 81356055.69 | 0.302142E+09 | 34279053.30 |
Annual Sum or Average | 0.104343E+10 | 0.216238E+09 | 0.827197E+09 | 0.245777E+10 | 0.217965E+09 |
Minimum of Months | 59061954.14 | 0.00 | 59061954.14 | 0.145641E+09 | 7471253.13 |
Maximum of Months | 0.141674E+09 | 60245791.02 | 82566185.41 | 0.306938E+09 | 34279053.30 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.169384E+09 | 70668815.78 | 98714876.57 | 0.365854E+09 | 36287424.50 |
February | 0.129913E+09 | 42356531.90 | 87556502.01 | 0.301763E+09 | 25940175.16 |
March | 98157325.63 | 13182600.33 | 84974725.30 | 0.250225E+09 | 20769150.26 |
April | 70820340.82 | 31791.79 | 70788549.03 | 0.186143E+09 | 9139321.66 |
May | 73230987.38 | 0.00 | 73230987.38 | 0.197806E+09 | 11438931.90 |
June | 70613574.84 | 0.00 | 70613574.84 | 0.188973E+09 | 12077321.10 |
July | 75167382.29 | 0.00 | 75167382.29 | 0.177842E+09 | 21559918.64 |
August | 73176015.95 | 113095.07 | 73062920.88 | 0.173047E+09 | 17818335.01 |
September | 78397815.86 | 2560530.40 | 75837285.45 | 0.190366E+09 | 17086452.04 |
October | 0.105986E+09 | 16898654.06 | 89087486.43 | 0.239118E+09 | 22197790.72 |
November | 0.133371E+09 | 40689758.83 | 92681395.14 | 0.292831E+09 | 25539001.45 |
December | 0.169297E+09 | 72028952.23 | 97268063.86 | 0.360202E+09 | 40787444.09 |
Annual Sum or Average | 0.124751E+10 | 0.258531E+09 | 0.988984E+09 | 0.292417E+10 | 0.260641E+09 |
Minimum of Months | 70613574.84 | 0.00 | 70613574.84 | 0.173047E+09 | 9139321.66 |
Maximum of Months | 0.169384E+09 | 72028952.23 | 98714876.57 | 0.365854E+09 | 40787444.09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.141674E+09 | 59108158.25 | 82566185.41 | 0.306831E+09 | 30840725.32 |
February | 0.108661E+09 | 35427459.24 | 73233200.81 | 0.253278E+09 | 22042275.13 |
March | 82099843.80 | 11026068.83 | 71073774.97 | 0.210357E+09 | 17625094.85 |
April | 59234895.43 | 26590.99 | 59208304.43 | 0.156783E+09 | 7910222.46 |
May | 61251186.16 | 0.00 | 61251186.16 | 0.166390E+09 | 9941932.86 |
June | 59061954.14 | 0.00 | 59061954.14 | 0.159083E+09 | 10551830.60 |
July | 62870807.71 | 0.00 | 62870807.71 | 0.149358E+09 | 18609996.92 |
August | 61205207.47 | 94593.94 | 61110613.53 | 0.145540E+09 | 15250727.50 |
September | 65572777.12 | 2141655.19 | 63431121.93 | 0.159886E+09 | 14742985.21 |
October | 88647948.83 | 14134216.17 | 74513732.66 | 0.200612E+09 | 19070540.33 |
November | 0.111553E+09 | 34033352.30 | 77519716.59 | 0.245638E+09 | 21754055.30 |
December | 0.141602E+09 | 60245791.02 | 81356055.69 | 0.302067E+09 | 34580807.14 |
Annual Sum or Average | 0.104343E+10 | 0.216238E+09 | 0.827197E+09 | 0.245582E+10 | 0.222921E+09 |
Minimum of Months | 59061954.14 | 0.00 | 59061954.14 | 0.145540E+09 | 7910222.46 |
Maximum of Months | 0.141674E+09 | 60245791.02 | 82566185.41 | 0.306831E+09 | 34580807.14 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.141674E+09 | 59108158.25 | 82566185.41 | 0.306831E+09 | 30840725.32 |
February | 0.108661E+09 | 35427459.24 | 73233200.81 | 0.253278E+09 | 22042275.13 |
March | 82099843.80 | 11026068.83 | 71073774.97 | 0.210357E+09 | 17625094.85 |
April | 59234895.43 | 26590.99 | 59208304.43 | 0.156783E+09 | 7910222.46 |
May | 61251186.16 | 0.00 | 61251186.16 | 0.166390E+09 | 9941932.86 |
June | 59061954.14 | 0.00 | 59061954.14 | 0.159083E+09 | 10551830.60 |
July | 62870807.71 | 0.00 | 62870807.71 | 0.149358E+09 | 18609996.92 |
August | 61205207.47 | 94593.94 | 61110613.53 | 0.145540E+09 | 15250727.50 |
September | 65572777.12 | 2141655.19 | 63431121.93 | 0.159886E+09 | 14742985.21 |
October | 88647948.83 | 14134216.17 | 74513732.66 | 0.200612E+09 | 19070540.33 |
November | 0.111553E+09 | 34033352.30 | 77519716.59 | 0.245638E+09 | 21754055.30 |
December | 0.141602E+09 | 60245791.02 | 81356055.69 | 0.302067E+09 | 34580807.14 |
Annual Sum or Average | 0.104343E+10 | 0.216238E+09 | 0.827197E+09 | 0.245582E+10 | 0.222921E+09 |
Minimum of Months | 59061954.14 | 0.00 | 59061954.14 | 0.145540E+09 | 7910222.46 |
Maximum of Months | 0.141674E+09 | 60245791.02 | 82566185.41 | 0.306831E+09 | 34580807.14 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.169384E+09 | 70668815.78 | 98714876.57 | 0.365727E+09 | 36767059.68 |
February | 0.129913E+09 | 42356531.90 | 87556502.01 | 0.301625E+09 | 26409915.08 |
March | 98157325.63 | 13182600.33 | 84974725.30 | 0.250095E+09 | 21341062.99 |
April | 70820340.82 | 31791.79 | 70788549.03 | 0.185860E+09 | 9667115.81 |
May | 73230987.38 | 0.00 | 73230987.38 | 0.197339E+09 | 11924065.07 |
June | 70613574.84 | 0.00 | 70613574.84 | 0.188642E+09 | 12657258.29 |
July | 75167382.29 | 0.00 | 75167382.29 | 0.177624E+09 | 22164406.76 |
August | 73176015.95 | 113095.07 | 73062920.88 | 0.172926E+09 | 18286243.84 |
September | 78397815.86 | 2560530.40 | 75837285.45 | 0.190199E+09 | 17586741.82 |
October | 0.105986E+09 | 16898654.06 | 89087486.43 | 0.239002E+09 | 22677450.72 |
November | 0.133371E+09 | 40689758.83 | 92681395.14 | 0.292737E+09 | 25902409.13 |
December | 0.169297E+09 | 72028952.23 | 97268063.86 | 0.360113E+09 | 41143577.02 |
Annual Sum or Average | 0.124751E+10 | 0.258531E+09 | 0.988984E+09 | 0.292189E+10 | 0.266527E+09 |
Minimum of Months | 70613574.84 | 0.00 | 70613574.84 | 0.172926E+09 | 9667115.81 |
Maximum of Months | 0.169384E+09 | 72028952.23 | 98714876.57 | 0.365727E+09 | 41143577.02 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.141674E+09 | 59108158.25 | 82566185.41 | 0.307125E+09 | 30135792.18 |
February | 0.108661E+09 | 35427459.24 | 73233200.81 | 0.253545E+09 | 21399932.22 |
March | 82099843.80 | 11026068.83 | 71073774.97 | 0.210649E+09 | 16863718.99 |
April | 59234895.43 | 26590.99 | 59208304.43 | 0.157200E+09 | 7339530.93 |
May | 61251186.16 | 0.00 | 61251186.16 | 0.166841E+09 | 9444461.28 |
June | 59061954.14 | 0.00 | 59061954.14 | 0.159492E+09 | 10025034.29 |
July | 62870807.71 | 0.00 | 62870807.71 | 0.149654E+09 | 17941665.44 |
August | 61205207.47 | 94593.94 | 61110613.53 | 0.145859E+09 | 14510353.06 |
September | 65572777.12 | 2141655.19 | 63431121.93 | 0.160208E+09 | 14086983.78 |
October | 88647948.83 | 14134216.17 | 74513732.66 | 0.200916E+09 | 18338615.71 |
November | 0.111553E+09 | 34033352.30 | 77519716.59 | 0.245949E+09 | 21080974.76 |
December | 0.141602E+09 | 60245791.02 | 81356055.69 | 0.302377E+09 | 33878705.69 |
Annual Sum or Average | 0.104343E+10 | 0.216238E+09 | 0.827197E+09 | 0.245982E+10 | 0.215046E+09 |
Minimum of Months | 59061954.14 | 0.00 | 59061954.14 | 0.145859E+09 | 7339530.93 |
Maximum of Months | 0.141674E+09 | 60245791.02 | 82566185.41 | 0.307125E+09 | 33878705.69 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.141674E+09 | 59108158.25 | 82566185.41 | 0.307125E+09 | 30135792.18 |
February | 0.108661E+09 | 35427459.24 | 73233200.81 | 0.253545E+09 | 21399932.22 |
March | 82099843.80 | 11026068.83 | 71073774.97 | 0.210649E+09 | 16863718.99 |
April | 59234895.43 | 26590.99 | 59208304.43 | 0.157200E+09 | 7339530.93 |
May | 61251186.16 | 0.00 | 61251186.16 | 0.166841E+09 | 9444461.28 |
June | 59061954.14 | 0.00 | 59061954.14 | 0.159492E+09 | 10025034.29 |
July | 62870807.71 | 0.00 | 62870807.71 | 0.149654E+09 | 17941665.44 |
August | 61205207.47 | 94593.94 | 61110613.53 | 0.145859E+09 | 14510353.06 |
September | 65572777.12 | 2141655.19 | 63431121.93 | 0.160208E+09 | 14086983.78 |
October | 88647948.83 | 14134216.17 | 74513732.66 | 0.200916E+09 | 18338615.71 |
November | 0.111553E+09 | 34033352.30 | 77519716.59 | 0.245949E+09 | 21080974.76 |
December | 0.141602E+09 | 60245791.02 | 81356055.69 | 0.302377E+09 | 33878705.69 |
Annual Sum or Average | 0.104343E+10 | 0.216238E+09 | 0.827197E+09 | 0.245982E+10 | 0.215046E+09 |
Minimum of Months | 59061954.14 | 0.00 | 59061954.14 | 0.145859E+09 | 7339530.93 |
Maximum of Months | 0.141674E+09 | 60245791.02 | 82566185.41 | 0.307125E+09 | 33878705.69 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.169384E+09 | 70668815.78 | 98714876.57 | 0.366078E+09 | 35940934.35 |
February | 0.129913E+09 | 42356531.90 | 87556502.01 | 0.301946E+09 | 25656149.62 |
March | 98157325.63 | 13182600.33 | 84974725.30 | 0.250442E+09 | 20446881.98 |
April | 70820340.82 | 31791.79 | 70788549.03 | 0.186342E+09 | 8982735.23 |
May | 73230987.38 | 0.00 | 73230987.38 | 0.197866E+09 | 11331887.18 |
June | 70613574.84 | 0.00 | 70613574.84 | 0.189120E+09 | 12030354.86 |
July | 75167382.29 | 0.00 | 75167382.29 | 0.177976E+09 | 21379444.53 |
August | 73176015.95 | 113095.07 | 73062920.88 | 0.173306E+09 | 17418934.88 |
September | 78397815.86 | 2560530.40 | 75837285.45 | 0.190580E+09 | 16815080.71 |
October | 0.105986E+09 | 16898654.06 | 89087486.43 | 0.239366E+09 | 21818039.55 |
November | 0.133371E+09 | 40689758.83 | 92681395.14 | 0.293109E+09 | 25111481.67 |
December | 0.169297E+09 | 72028952.23 | 97268063.86 | 0.360484E+09 | 40319496.38 |
Annual Sum or Average | 0.124751E+10 | 0.258531E+09 | 0.988984E+09 | 0.292661E+10 | 0.257251E+09 |
Minimum of Months | 70613574.84 | 0.00 | 70613574.84 | 0.173306E+09 | 8982735.23 |
Maximum of Months | 0.169384E+09 | 72028952.23 | 98714876.57 | 0.366078E+09 | 40319496.38 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.141674E+09 | 59108158.25 | 82566185.41 | 0.306640E+09 | 27913902.90 |
February | 0.108661E+09 | 35427459.24 | 73233200.81 | 0.252906E+09 | 19304154.13 |
March | 82099843.80 | 11026068.83 | 71073774.97 | 0.210107E+09 | 14638975.93 |
April | 59234895.43 | 26590.99 | 59208304.43 | 0.157286E+09 | 6033240.01 |
May | 61251186.16 | 0.00 | 61251186.16 | 0.166683E+09 | 8015341.44 |
June | 59061954.14 | 0.00 | 59061954.14 | 0.159395E+09 | 8595191.01 |
July | 62870807.71 | 0.00 | 62870807.71 | 0.149105E+09 | 15952895.26 |
August | 61205207.47 | 94593.94 | 61110613.53 | 0.145413E+09 | 12256580.31 |
September | 65572777.12 | 2141655.19 | 63431121.93 | 0.159989E+09 | 12258780.86 |
October | 88647948.83 | 14134216.17 | 74513732.66 | 0.200648E+09 | 16195950.02 |
November | 0.111553E+09 | 34033352.30 | 77519716.59 | 0.245492E+09 | 19029367.51 |
December | 0.141602E+09 | 60245791.02 | 81356055.69 | 0.301906E+09 | 31695213.92 |
Annual Sum or Average | 0.104343E+10 | 0.216238E+09 | 0.827197E+09 | 0.245557E+10 | 0.191890E+09 |
Minimum of Months | 59061954.14 | 0.00 | 59061954.14 | 0.145413E+09 | 6033240.01 |
Maximum of Months | 0.141674E+09 | 60245791.02 | 82566185.41 | 0.306640E+09 | 31695213.92 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.141674E+09 | 59108158.25 | 82566185.41 | 0.306640E+09 | 27913902.90 |
February | 0.108661E+09 | 35427459.24 | 73233200.81 | 0.252906E+09 | 19304154.13 |
March | 82099843.80 | 11026068.83 | 71073774.97 | 0.210107E+09 | 14638975.93 |
April | 59234895.43 | 26590.99 | 59208304.43 | 0.157286E+09 | 6033240.01 |
May | 61251186.16 | 0.00 | 61251186.16 | 0.166683E+09 | 8015341.44 |
June | 59061954.14 | 0.00 | 59061954.14 | 0.159395E+09 | 8595191.01 |
July | 62870807.71 | 0.00 | 62870807.71 | 0.149105E+09 | 15952895.26 |
August | 61205207.47 | 94593.94 | 61110613.53 | 0.145413E+09 | 12256580.31 |
September | 65572777.12 | 2141655.19 | 63431121.93 | 0.159989E+09 | 12258780.86 |
October | 88647948.83 | 14134216.17 | 74513732.66 | 0.200648E+09 | 16195950.02 |
November | 0.111553E+09 | 34033352.30 | 77519716.59 | 0.245492E+09 | 19029367.51 |
December | 0.141602E+09 | 60245791.02 | 81356055.69 | 0.301906E+09 | 31695213.92 |
Annual Sum or Average | 0.104343E+10 | 0.216238E+09 | 0.827197E+09 | 0.245557E+10 | 0.191890E+09 |
Minimum of Months | 59061954.14 | 0.00 | 59061954.14 | 0.145413E+09 | 6033240.01 |
Maximum of Months | 0.141674E+09 | 60245791.02 | 82566185.41 | 0.306640E+09 | 31695213.92 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.141674E+09 | 59108158.25 | 82566185.41 | 0.306640E+09 | 27913902.90 |
February | 0.108661E+09 | 35427459.24 | 73233200.81 | 0.252906E+09 | 19304154.13 |
March | 82099843.80 | 11026068.83 | 71073774.97 | 0.210107E+09 | 14638975.93 |
April | 59234895.43 | 26590.99 | 59208304.43 | 0.157286E+09 | 6033240.01 |
May | 61251186.16 | 0.00 | 61251186.16 | 0.166683E+09 | 8015341.44 |
June | 59061954.14 | 0.00 | 59061954.14 | 0.159395E+09 | 8595191.01 |
July | 62870807.71 | 0.00 | 62870807.71 | 0.149105E+09 | 15952895.26 |
August | 61205207.47 | 94593.94 | 61110613.53 | 0.145413E+09 | 12256580.31 |
September | 65572777.12 | 2141655.19 | 63431121.93 | 0.159989E+09 | 12258780.86 |
October | 88647948.83 | 14134216.17 | 74513732.66 | 0.200648E+09 | 16195950.02 |
November | 0.111553E+09 | 34033352.30 | 77519716.59 | 0.245492E+09 | 19029367.51 |
December | 0.141602E+09 | 60245791.02 | 81356055.69 | 0.301906E+09 | 31695213.92 |
Annual Sum or Average | 0.104343E+10 | 0.216238E+09 | 0.827197E+09 | 0.245557E+10 | 0.191890E+09 |
Minimum of Months | 59061954.14 | 0.00 | 59061954.14 | 0.145413E+09 | 6033240.01 |
Maximum of Months | 0.141674E+09 | 60245791.02 | 82566185.41 | 0.306640E+09 | 31695213.92 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.141674E+09 | 59108158.25 | 82566185.41 | 0.306640E+09 | 27913902.90 |
February | 0.108661E+09 | 35427459.24 | 73233200.81 | 0.252906E+09 | 19304154.13 |
March | 82099843.80 | 11026068.83 | 71073774.97 | 0.210107E+09 | 14638975.93 |
April | 59234895.43 | 26590.99 | 59208304.43 | 0.157286E+09 | 6033240.01 |
May | 61251186.16 | 0.00 | 61251186.16 | 0.166683E+09 | 8015341.44 |
June | 59061954.14 | 0.00 | 59061954.14 | 0.159395E+09 | 8595191.01 |
July | 62870807.71 | 0.00 | 62870807.71 | 0.149105E+09 | 15952895.26 |
August | 61205207.47 | 94593.94 | 61110613.53 | 0.145413E+09 | 12256580.31 |
September | 65572777.12 | 2141655.19 | 63431121.93 | 0.159989E+09 | 12258780.86 |
October | 88647948.83 | 14134216.17 | 74513732.66 | 0.200648E+09 | 16195950.02 |
November | 0.111553E+09 | 34033352.30 | 77519716.59 | 0.245492E+09 | 19029367.51 |
December | 0.141602E+09 | 60245791.02 | 81356055.69 | 0.301906E+09 | 31695213.92 |
Annual Sum or Average | 0.104343E+10 | 0.216238E+09 | 0.827197E+09 | 0.245557E+10 | 0.191890E+09 |
Minimum of Months | 59061954.14 | 0.00 | 59061954.14 | 0.145413E+09 | 6033240.01 |
Maximum of Months | 0.141674E+09 | 60245791.02 | 82566185.41 | 0.306640E+09 | 31695213.92 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.169384E+09 | 70668815.78 | 98714876.57 | 0.365479E+09 | 33300179.14 |
February | 0.129913E+09 | 42356531.90 | 87556502.01 | 0.301185E+09 | 23155265.52 |
March | 98157325.63 | 13182600.33 | 84974725.30 | 0.249793E+09 | 17760191.55 |
April | 70820340.82 | 31791.79 | 70788549.03 | 0.186454E+09 | 7365667.80 |
May | 73230987.38 | 0.00 | 73230987.38 | 0.197722E+09 | 9615333.90 |
June | 70613574.84 | 0.00 | 70613574.84 | 0.189031E+09 | 10308028.67 |
July | 75167382.29 | 0.00 | 75167382.29 | 0.177343E+09 | 19011537.56 |
August | 73176015.95 | 113095.07 | 73062920.88 | 0.172806E+09 | 14730346.13 |
September | 78397815.86 | 2560530.40 | 75837285.45 | 0.190332E+09 | 14630168.48 |
October | 0.105986E+09 | 16898654.06 | 89087486.43 | 0.239051E+09 | 19270427.09 |
November | 0.133371E+09 | 40689758.83 | 92681395.14 | 0.292563E+09 | 22672367.46 |
December | 0.169297E+09 | 72028952.23 | 97268063.86 | 0.359915E+09 | 37733207.26 |
Annual Sum or Average | 0.124751E+10 | 0.258531E+09 | 0.988984E+09 | 0.292167E+10 | 0.229553E+09 |
Minimum of Months | 70613574.84 | 0.00 | 70613574.84 | 0.172806E+09 | 7365667.80 |
Maximum of Months | 0.169384E+09 | 72028952.23 | 98714876.57 | 0.365479E+09 | 37733207.26 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.169384E+09 | 70668815.78 | 98714876.57 | 0.365479E+09 | 33300179.14 |
February | 0.129913E+09 | 42356531.90 | 87556502.01 | 0.301185E+09 | 23155265.52 |
March | 98157325.63 | 13182600.33 | 84974725.30 | 0.249793E+09 | 17760191.55 |
April | 70820340.82 | 31791.79 | 70788549.03 | 0.186454E+09 | 7365667.80 |
May | 73230987.38 | 0.00 | 73230987.38 | 0.197722E+09 | 9615333.90 |
June | 70613574.84 | 0.00 | 70613574.84 | 0.189031E+09 | 10308028.67 |
July | 75167382.29 | 0.00 | 75167382.29 | 0.177343E+09 | 19011537.56 |
August | 73176015.95 | 113095.07 | 73062920.88 | 0.172806E+09 | 14730346.13 |
September | 78397815.86 | 2560530.40 | 75837285.45 | 0.190332E+09 | 14630168.48 |
October | 0.105986E+09 | 16898654.06 | 89087486.43 | 0.239051E+09 | 19270427.09 |
November | 0.133371E+09 | 40689758.83 | 92681395.14 | 0.292563E+09 | 22672367.46 |
December | 0.169297E+09 | 72028952.23 | 97268063.86 | 0.359915E+09 | 37733207.26 |
Annual Sum or Average | 0.124751E+10 | 0.258531E+09 | 0.988984E+09 | 0.292167E+10 | 0.229553E+09 |
Minimum of Months | 70613574.84 | 0.00 | 70613574.84 | 0.172806E+09 | 7365667.80 |
Maximum of Months | 0.169384E+09 | 72028952.23 | 98714876.57 | 0.365479E+09 | 37733207.26 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.141674E+09 | 59108158.25 | 82566185.41 | 0.307095E+09 | 26992995.83 |
February | 0.108661E+09 | 35427459.24 | 73233200.81 | 0.253475E+09 | 18399090.04 |
March | 82099843.80 | 11026068.83 | 71073774.97 | 0.211002E+09 | 13568343.83 |
April | 59234895.43 | 26590.99 | 59208304.43 | 0.158745E+09 | 5366505.63 |
May | 61251186.16 | 0.00 | 61251186.16 | 0.168147E+09 | 7380689.20 |
June | 59061954.14 | 0.00 | 59061954.14 | 0.160859E+09 | 7917794.12 |
July | 62870807.71 | 0.00 | 62870807.71 | 0.149929E+09 | 15087736.20 |
August | 61205207.47 | 94593.94 | 61110613.53 | 0.146319E+09 | 11329145.33 |
September | 65572777.12 | 2141655.19 | 63431121.93 | 0.160810E+09 | 11468328.06 |
October | 88647948.83 | 14134216.17 | 74513732.66 | 0.201249E+09 | 15333580.20 |
November | 0.111553E+09 | 34033352.30 | 77519716.59 | 0.245998E+09 | 18185772.58 |
December | 0.141602E+09 | 60245791.02 | 81356055.69 | 0.302285E+09 | 30803572.38 |
Annual Sum or Average | 0.104343E+10 | 0.216238E+09 | 0.827197E+09 | 0.246591E+10 | 0.181834E+09 |
Minimum of Months | 59061954.14 | 0.00 | 59061954.14 | 0.146319E+09 | 5366505.63 |
Maximum of Months | 0.141674E+09 | 60245791.02 | 82566185.41 | 0.307095E+09 | 30803572.38 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.141674E+09 | 59108158.25 | 82566185.41 | 0.307095E+09 | 26992995.83 |
February | 0.108661E+09 | 35427459.24 | 73233200.81 | 0.253475E+09 | 18399090.04 |
March | 82099843.80 | 11026068.83 | 71073774.97 | 0.211002E+09 | 13568343.83 |
April | 59234895.43 | 26590.99 | 59208304.43 | 0.158745E+09 | 5366505.63 |
May | 61251186.16 | 0.00 | 61251186.16 | 0.168147E+09 | 7380689.20 |
June | 59061954.14 | 0.00 | 59061954.14 | 0.160859E+09 | 7917794.12 |
July | 62870807.71 | 0.00 | 62870807.71 | 0.149929E+09 | 15087736.20 |
August | 61205207.47 | 94593.94 | 61110613.53 | 0.146319E+09 | 11329145.33 |
September | 65572777.12 | 2141655.19 | 63431121.93 | 0.160810E+09 | 11468328.06 |
October | 88647948.83 | 14134216.17 | 74513732.66 | 0.201249E+09 | 15333580.20 |
November | 0.111553E+09 | 34033352.30 | 77519716.59 | 0.245998E+09 | 18185772.58 |
December | 0.141602E+09 | 60245791.02 | 81356055.69 | 0.302285E+09 | 30803572.38 |
Annual Sum or Average | 0.104343E+10 | 0.216238E+09 | 0.827197E+09 | 0.246591E+10 | 0.181834E+09 |
Minimum of Months | 59061954.14 | 0.00 | 59061954.14 | 0.146319E+09 | 5366505.63 |
Maximum of Months | 0.141674E+09 | 60245791.02 | 82566185.41 | 0.307095E+09 | 30803572.38 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.169384E+09 | 70668815.78 | 98714876.57 | 0.366077E+09 | 32219612.97 |
February | 0.129913E+09 | 42356531.90 | 87556502.01 | 0.301891E+09 | 22098874.34 |
March | 98157325.63 | 13182600.33 | 84974725.30 | 0.250845E+09 | 16517056.89 |
April | 70820340.82 | 31791.79 | 70788549.03 | 0.188128E+09 | 6582919.05 |
May | 73230987.38 | 0.00 | 73230987.38 | 0.199419E+09 | 8867371.37 |
June | 70613574.84 | 0.00 | 70613574.84 | 0.190723E+09 | 9505766.67 |
July | 75167382.29 | 0.00 | 75167382.29 | 0.178326E+09 | 17993468.58 |
August | 73176015.95 | 113095.07 | 73062920.88 | 0.173869E+09 | 13644045.71 |
September | 78397815.86 | 2560530.40 | 75837285.45 | 0.191313E+09 | 13700289.86 |
October | 0.105986E+09 | 16898654.06 | 89087486.43 | 0.239802E+09 | 18252932.94 |
November | 0.133371E+09 | 40689758.83 | 92681395.14 | 0.293215E+09 | 21680113.64 |
December | 0.169297E+09 | 72028952.23 | 97268063.86 | 0.360432E+09 | 36682611.08 |
Annual Sum or Average | 0.124751E+10 | 0.258531E+09 | 0.988984E+09 | 0.293404E+10 | 0.217745E+09 |
Minimum of Months | 70613574.84 | 0.00 | 70613574.84 | 0.173869E+09 | 6582919.05 |
Maximum of Months | 0.169384E+09 | 72028952.23 | 98714876.57 | 0.366077E+09 | 36682611.08 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.141674E+09 | 59108158.25 | 82566185.41 | 0.307235E+09 | 26826649.79 |
February | 0.108661E+09 | 35427459.24 | 73233200.81 | 0.253592E+09 | 18264135.17 |
March | 82099843.80 | 11026068.83 | 71073774.97 | 0.211126E+09 | 13427250.92 |
April | 59234895.43 | 26590.99 | 59208304.43 | 0.158892E+09 | 5280522.30 |
May | 61251186.16 | 0.00 | 61251186.16 | 0.168299E+09 | 7294995.12 |
June | 59061954.14 | 0.00 | 59061954.14 | 0.161009E+09 | 7826747.85 |
July | 62870807.71 | 0.00 | 62870807.71 | 0.150044E+09 | 14962920.05 |
August | 61205207.47 | 94593.94 | 61110613.53 | 0.146441E+09 | 11195333.45 |
September | 65572777.12 | 2141655.19 | 63431121.93 | 0.160926E+09 | 11350439.89 |
October | 88647948.83 | 14134216.17 | 74513732.66 | 0.201380E+09 | 15177496.32 |
November | 0.111553E+09 | 34033352.30 | 77519716.59 | 0.246132E+09 | 18030075.40 |
December | 0.141602E+09 | 60245791.02 | 81356055.69 | 0.302425E+09 | 30628736.94 |
Annual Sum or Average | 0.104343E+10 | 0.216238E+09 | 0.827197E+09 | 0.246750E+10 | 0.180265E+09 |
Minimum of Months | 59061954.14 | 0.00 | 59061954.14 | 0.146441E+09 | 5280522.30 |
Maximum of Months | 0.141674E+09 | 60245791.02 | 82566185.41 | 0.307235E+09 | 30628736.94 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.141674E+09 | 59108158.25 | 82566185.41 | 0.307235E+09 | 26826649.79 |
February | 0.108661E+09 | 35427459.24 | 73233200.81 | 0.253592E+09 | 18264135.17 |
March | 82099843.80 | 11026068.83 | 71073774.97 | 0.211126E+09 | 13427250.92 |
April | 59234895.43 | 26590.99 | 59208304.43 | 0.158892E+09 | 5280522.30 |
May | 61251186.16 | 0.00 | 61251186.16 | 0.168299E+09 | 7294995.12 |
June | 59061954.14 | 0.00 | 59061954.14 | 0.161009E+09 | 7826747.85 |
July | 62870807.71 | 0.00 | 62870807.71 | 0.150044E+09 | 14962920.05 |
August | 61205207.47 | 94593.94 | 61110613.53 | 0.146441E+09 | 11195333.45 |
September | 65572777.12 | 2141655.19 | 63431121.93 | 0.160926E+09 | 11350439.89 |
October | 88647948.83 | 14134216.17 | 74513732.66 | 0.201380E+09 | 15177496.32 |
November | 0.111553E+09 | 34033352.30 | 77519716.59 | 0.246132E+09 | 18030075.40 |
December | 0.141602E+09 | 60245791.02 | 81356055.69 | 0.302425E+09 | 30628736.94 |
Annual Sum or Average | 0.104343E+10 | 0.216238E+09 | 0.827197E+09 | 0.246750E+10 | 0.180265E+09 |
Minimum of Months | 59061954.14 | 0.00 | 59061954.14 | 0.146441E+09 | 5280522.30 |
Maximum of Months | 0.141674E+09 | 60245791.02 | 82566185.41 | 0.307235E+09 | 30628736.94 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.169384E+09 | 70668815.78 | 98714876.57 | 0.366244E+09 | 32022956.44 |
February | 0.129913E+09 | 42356531.90 | 87556502.01 | 0.302030E+09 | 21938538.02 |
March | 98157325.63 | 13182600.33 | 84974725.30 | 0.250991E+09 | 16349622.55 |
April | 70820340.82 | 31791.79 | 70788549.03 | 0.188302E+09 | 6479564.25 |
May | 73230987.38 | 0.00 | 73230987.38 | 0.199601E+09 | 8764987.36 |
June | 70613574.84 | 0.00 | 70613574.84 | 0.190901E+09 | 9397129.48 |
July | 75167382.29 | 0.00 | 75167382.29 | 0.178464E+09 | 17845476.55 |
August | 73176015.95 | 113095.07 | 73062920.88 | 0.174014E+09 | 13484936.28 |
September | 78397815.86 | 2560530.40 | 75837285.45 | 0.191451E+09 | 13559798.07 |
October | 0.105986E+09 | 16898654.06 | 89087486.43 | 0.239959E+09 | 18067751.66 |
November | 0.133371E+09 | 40689758.83 | 92681395.14 | 0.293375E+09 | 21495414.26 |
December | 0.169297E+09 | 72028952.23 | 97268063.86 | 0.360599E+09 | 36474650.27 |
Annual Sum or Average | 0.124751E+10 | 0.258531E+09 | 0.988984E+09 | 0.293593E+10 | 0.215881E+09 |
Minimum of Months | 70613574.84 | 0.00 | 70613574.84 | 0.174014E+09 | 6479564.25 |
Maximum of Months | 0.169384E+09 | 72028952.23 | 98714876.57 | 0.366244E+09 | 36474650.27 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.141674E+09 | 59108158.25 | 82566185.41 | 0.307100E+09 | 26870837.67 |
February | 0.108661E+09 | 35427459.24 | 73233200.81 | 0.253379E+09 | 18391712.78 |
March | 82099843.80 | 11026068.83 | 71073774.97 | 0.210826E+09 | 13629325.71 |
April | 59234895.43 | 26590.99 | 59208304.43 | 0.158387E+09 | 5472231.04 |
May | 61251186.16 | 0.00 | 61251186.16 | 0.167758E+09 | 7470158.26 |
June | 59061954.14 | 0.00 | 59061954.14 | 0.160495E+09 | 8042412.64 |
July | 62870807.71 | 0.00 | 62870807.71 | 0.149694E+09 | 15229969.00 |
August | 61205207.47 | 94593.94 | 61110613.53 | 0.146121E+09 | 11395052.10 |
September | 65572777.12 | 2141655.19 | 63431121.93 | 0.160575E+09 | 11574040.00 |
October | 88647948.83 | 14134216.17 | 74513732.66 | 0.201171E+09 | 15280621.29 |
November | 0.111553E+09 | 34033352.30 | 77519716.59 | 0.245979E+09 | 18085788.70 |
December | 0.141602E+09 | 60245791.02 | 81356055.69 | 0.302333E+09 | 30640137.52 |
Annual Sum or Average | 0.104343E+10 | 0.216238E+09 | 0.827197E+09 | 0.246382E+10 | 0.182082E+09 |
Minimum of Months | 59061954.14 | 0.00 | 59061954.14 | 0.146121E+09 | 5472231.04 |
Maximum of Months | 0.141674E+09 | 60245791.02 | 82566185.41 | 0.307100E+09 | 30640137.52 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.141674E+09 | 59108158.25 | 82566185.41 | 0.307100E+09 | 26870837.67 |
February | 0.108661E+09 | 35427459.24 | 73233200.81 | 0.253379E+09 | 18391712.78 |
March | 82099843.80 | 11026068.83 | 71073774.97 | 0.210826E+09 | 13629325.71 |
April | 59234895.43 | 26590.99 | 59208304.43 | 0.158387E+09 | 5472231.04 |
May | 61251186.16 | 0.00 | 61251186.16 | 0.167758E+09 | 7470158.26 |
June | 59061954.14 | 0.00 | 59061954.14 | 0.160495E+09 | 8042412.64 |
July | 62870807.71 | 0.00 | 62870807.71 | 0.149694E+09 | 15229969.00 |
August | 61205207.47 | 94593.94 | 61110613.53 | 0.146121E+09 | 11395052.10 |
September | 65572777.12 | 2141655.19 | 63431121.93 | 0.160575E+09 | 11574040.00 |
October | 88647948.83 | 14134216.17 | 74513732.66 | 0.201171E+09 | 15280621.29 |
November | 0.111553E+09 | 34033352.30 | 77519716.59 | 0.245979E+09 | 18085788.70 |
December | 0.141602E+09 | 60245791.02 | 81356055.69 | 0.302333E+09 | 30640137.52 |
Annual Sum or Average | 0.104343E+10 | 0.216238E+09 | 0.827197E+09 | 0.246382E+10 | 0.182082E+09 |
Minimum of Months | 59061954.14 | 0.00 | 59061954.14 | 0.146121E+09 | 5472231.04 |
Maximum of Months | 0.141674E+09 | 60245791.02 | 82566185.41 | 0.307100E+09 | 30640137.52 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.169384E+09 | 70668815.78 | 98714876.57 | 0.366080E+09 | 32083076.32 |
February | 0.129913E+09 | 42356531.90 | 87556502.01 | 0.301774E+09 | 22096943.09 |
March | 98157325.63 | 13182600.33 | 84974725.30 | 0.250632E+09 | 16596823.82 |
April | 70820340.82 | 31791.79 | 70788549.03 | 0.187701E+09 | 6714327.49 |
May | 73230987.38 | 0.00 | 73230987.38 | 0.198956E+09 | 8980297.40 |
June | 70613574.84 | 0.00 | 70613574.84 | 0.190291E+09 | 9661952.07 |
July | 75167382.29 | 0.00 | 75167382.29 | 0.178044E+09 | 18170294.94 |
August | 73176015.95 | 113095.07 | 73062920.88 | 0.173632E+09 | 13731007.22 |
September | 78397815.86 | 2560530.40 | 75837285.45 | 0.191031E+09 | 13832889.07 |
October | 0.105986E+09 | 16898654.06 | 89087486.43 | 0.239708E+09 | 18198007.65 |
November | 0.133371E+09 | 40689758.83 | 92681395.14 | 0.293188E+09 | 21568257.55 |
December | 0.169297E+09 | 72028952.23 | 97268063.86 | 0.360486E+09 | 36495624.48 |
Annual Sum or Average | 0.124751E+10 | 0.258531E+09 | 0.988984E+09 | 0.293152E+10 | 0.218130E+09 |
Minimum of Months | 70613574.84 | 0.00 | 70613574.84 | 0.173632E+09 | 6714327.49 |
Maximum of Months | 0.169384E+09 | 72028952.23 | 98714876.57 | 0.366080E+09 | 36495624.48 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.141674E+09 | 59108158.25 | 82566185.41 | 0.304234E+09 | 28015054.05 |
February | 0.108661E+09 | 35427459.24 | 73233200.81 | 0.250117E+09 | 19858674.88 |
March | 82099843.80 | 11026068.83 | 71073774.97 | 0.206782E+09 | 15508730.55 |
April | 59234895.43 | 26590.99 | 59208304.43 | 0.153070E+09 | 7035700.73 |
May | 61251186.16 | 0.00 | 61251186.16 | 0.162358E+09 | 8901130.76 |
June | 59061954.14 | 0.00 | 59061954.14 | 0.155235E+09 | 9797435.99 |
July | 62870807.71 | 0.00 | 62870807.71 | 0.145668E+09 | 17441174.37 |
August | 61205207.47 | 94593.94 | 61110613.53 | 0.142241E+09 | 13365978.46 |
September | 65572777.12 | 2141655.19 | 63431121.93 | 0.156543E+09 | 13561282.91 |
October | 88647948.83 | 14134216.17 | 74513732.66 | 0.198140E+09 | 16769092.00 |
November | 0.111553E+09 | 34033352.30 | 77519716.59 | 0.243098E+09 | 19314968.03 |
December | 0.141602E+09 | 60245791.02 | 81356055.69 | 0.299750E+09 | 31673268.79 |
Annual Sum or Average | 0.104343E+10 | 0.216238E+09 | 0.827197E+09 | 0.241724E+10 | 0.201242E+09 |
Minimum of Months | 59061954.14 | 0.00 | 59061954.14 | 0.142241E+09 | 7035700.73 |
Maximum of Months | 0.141674E+09 | 60245791.02 | 82566185.41 | 0.304234E+09 | 31673268.79 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.141674E+09 | 59108158.25 | 82566185.41 | 0.304234E+09 | 28015054.05 |
February | 0.108661E+09 | 35427459.24 | 73233200.81 | 0.250117E+09 | 19858674.88 |
March | 82099843.80 | 11026068.83 | 71073774.97 | 0.206782E+09 | 15508730.55 |
April | 59234895.43 | 26590.99 | 59208304.43 | 0.153070E+09 | 7035700.73 |
May | 61251186.16 | 0.00 | 61251186.16 | 0.162358E+09 | 8901130.76 |
June | 59061954.14 | 0.00 | 59061954.14 | 0.155235E+09 | 9797435.99 |
July | 62870807.71 | 0.00 | 62870807.71 | 0.145668E+09 | 17441174.37 |
August | 61205207.47 | 94593.94 | 61110613.53 | 0.142241E+09 | 13365978.46 |
September | 65572777.12 | 2141655.19 | 63431121.93 | 0.156543E+09 | 13561282.91 |
October | 88647948.83 | 14134216.17 | 74513732.66 | 0.198140E+09 | 16769092.00 |
November | 0.111553E+09 | 34033352.30 | 77519716.59 | 0.243098E+09 | 19314968.03 |
December | 0.141602E+09 | 60245791.02 | 81356055.69 | 0.299750E+09 | 31673268.79 |
Annual Sum or Average | 0.104343E+10 | 0.216238E+09 | 0.827197E+09 | 0.241724E+10 | 0.201242E+09 |
Minimum of Months | 59061954.14 | 0.00 | 59061954.14 | 0.142241E+09 | 7035700.73 |
Maximum of Months | 0.141674E+09 | 60245791.02 | 82566185.41 | 0.304234E+09 | 31673268.79 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.169384E+09 | 70668815.78 | 98714876.57 | 0.362633E+09 | 33449601.88 |
February | 0.129913E+09 | 42356531.90 | 87556502.01 | 0.297865E+09 | 23853435.88 |
March | 98157325.63 | 13182600.33 | 84974725.30 | 0.245798E+09 | 18837315.16 |
April | 70820340.82 | 31791.79 | 70788549.03 | 0.181389E+09 | 8613293.60 |
May | 73230987.38 | 0.00 | 73230987.38 | 0.192528E+09 | 10703182.21 |
June | 70613574.84 | 0.00 | 70613574.84 | 0.184032E+09 | 11767576.42 |
July | 75167382.29 | 0.00 | 75167382.29 | 0.173227E+09 | 20796207.22 |
August | 73176015.95 | 113095.07 | 73062920.88 | 0.168996E+09 | 16077348.40 |
September | 78397815.86 | 2560530.40 | 75837285.45 | 0.186203E+09 | 16198946.21 |
October | 0.105986E+09 | 16898654.06 | 89087486.43 | 0.236066E+09 | 19970658.63 |
November | 0.133371E+09 | 40689758.83 | 92681395.14 | 0.289717E+09 | 23029989.76 |
December | 0.169297E+09 | 72028952.23 | 97268063.86 | 0.357371E+09 | 37728030.81 |
Annual Sum or Average | 0.124751E+10 | 0.258531E+09 | 0.988984E+09 | 0.287583E+10 | 0.241026E+09 |
Minimum of Months | 70613574.84 | 0.00 | 70613574.84 | 0.168996E+09 | 8613293.60 |
Maximum of Months | 0.169384E+09 | 72028952.23 | 98714876.57 | 0.362633E+09 | 37728030.81 |
Report: WindowZoneSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 732.18 | 59.69 | 338.76 | 141.33 | 197.42 | 0.00 | 0.00 |
February | 668.37 | 44.88 | 287.66 | 93.79 | 193.87 | 0.00 | 0.00 |
March | 500.99 | 30.70 | 196.31 | 26.36 | 169.94 | 0.00 | 0.00 |
April | 392.23 | 13.73 | 146.36 | 0.07 | 146.29 | 0.00 | 0.00 |
May | 403.67 | 17.00 | 146.46 | 0.00 | 146.46 | 0.00 | 0.00 |
June | 397.22 | 18.69 | 145.93 | 0.00 | 145.93 | 0.00 | 0.00 |
July | 359.73 | 33.69 | 150.33 | 0.00 | 150.33 | 0.00 | 0.00 |
August | 347.16 | 26.15 | 146.35 | 0.23 | 146.12 | 0.00 | 0.00 |
September | 396.66 | 26.48 | 162.02 | 5.29 | 156.73 | 0.00 | 0.00 |
October | 479.87 | 33.53 | 211.97 | 33.80 | 178.17 | 0.00 | 0.00 |
November | 605.53 | 41.81 | 275.63 | 84.09 | 191.54 | 0.00 | 0.00 |
December | 720.24 | 68.96 | 338.58 | 144.05 | 194.53 | 0.00 | 0.00 |
Annual Sum or Average | 499.51 | 34.63 | 211.90 | 43.91 | 167.99 | 0.00 | 0.00 |
Minimum of Months | 347.16 | 13.73 | 145.93 | 0.00 | 145.93 | 0.00 | 0.00 |
Maximum of Months | 732.18 | 68.96 | 338.76 | 144.05 | 197.42 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 367.57 | 29.54 | 169.38 | 70.67 | 98.71 | 0.00 | 0.00 |
February | 336.35 | 21.95 | 143.83 | 46.89 | 96.93 | 0.00 | 0.00 |
March | 253.45 | 14.70 | 98.15 | 13.18 | 84.97 | 0.00 | 0.00 |
April | 199.81 | 6.36 | 73.18 | 0.03 | 73.15 | 0.00 | 0.00 |
May | 205.19 | 8.18 | 73.23 | 0.00 | 73.23 | 0.00 | 0.00 |
June | 202.18 | 8.86 | 72.97 | 0.00 | 72.97 | 0.00 | 0.00 |
July | 182.30 | 16.31 | 75.17 | 0.00 | 75.17 | 0.00 | 0.00 |
August | 176.11 | 12.60 | 73.17 | 0.11 | 73.06 | 0.00 | 0.00 |
September | 200.84 | 12.76 | 81.01 | 2.65 | 78.36 | 0.00 | 0.00 |
October | 241.64 | 16.51 | 105.98 | 16.90 | 89.08 | 0.00 | 0.00 |
November | 304.44 | 20.67 | 137.81 | 42.04 | 95.77 | 0.00 | 0.00 |
December | 361.39 | 34.25 | 169.29 | 72.03 | 97.27 | 0.00 | 0.00 |
Annual Sum or Average | 252.20 | 16.90 | 105.95 | 21.96 | 83.99 | 0.00 | 0.00 |
Minimum of Months | 176.11 | 6.36 | 72.97 | 0.00 | 72.97 | 0.00 | 0.00 |
Maximum of Months | 367.57 | 34.25 | 169.38 | 72.03 | 98.71 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 365.79 | 36.27 | 169.03 | 70.52 | 98.51 | 0.00 | 0.00 |
February | 334.22 | 28.62 | 143.53 | 46.80 | 96.74 | 0.00 | 0.00 |
March | 250.58 | 20.55 | 97.95 | 13.16 | 84.80 | 0.00 | 0.00 |
April | 192.98 | 9.29 | 73.03 | 0.03 | 73.00 | 0.00 | 0.00 |
May | 198.40 | 11.39 | 73.08 | 0.00 | 73.08 | 0.00 | 0.00 |
June | 195.88 | 12.43 | 72.82 | 0.00 | 72.82 | 0.00 | 0.00 |
July | 178.06 | 21.56 | 75.01 | 0.00 | 75.01 | 0.00 | 0.00 |
August | 173.36 | 17.74 | 73.02 | 0.11 | 72.91 | 0.00 | 0.00 |
September | 196.92 | 17.64 | 80.84 | 2.64 | 78.20 | 0.00 | 0.00 |
October | 239.15 | 22.23 | 105.77 | 16.86 | 88.90 | 0.00 | 0.00 |
November | 302.57 | 26.40 | 137.53 | 41.96 | 95.57 | 0.00 | 0.00 |
December | 360.10 | 40.82 | 168.94 | 71.88 | 97.07 | 0.00 | 0.00 |
Annual Sum or Average | 248.60 | 22.09 | 105.73 | 21.91 | 83.82 | 0.00 | 0.00 |
Minimum of Months | 173.36 | 9.29 | 72.82 | 0.00 | 72.82 | 0.00 | 0.00 |
Maximum of Months | 365.79 | 40.82 | 169.03 | 71.88 | 98.51 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 365.66 | 36.76 | 169.03 | 70.52 | 98.51 | 0.00 | 0.00 |
February | 334.07 | 29.14 | 143.53 | 46.80 | 96.74 | 0.00 | 0.00 |
March | 250.45 | 21.13 | 97.95 | 13.16 | 84.80 | 0.00 | 0.00 |
April | 192.68 | 9.83 | 73.03 | 0.03 | 73.00 | 0.00 | 0.00 |
May | 197.92 | 11.88 | 73.08 | 0.00 | 73.08 | 0.00 | 0.00 |
June | 195.53 | 13.02 | 72.82 | 0.00 | 72.82 | 0.00 | 0.00 |
July | 177.84 | 22.17 | 75.01 | 0.00 | 75.01 | 0.00 | 0.00 |
August | 173.24 | 18.22 | 73.02 | 0.11 | 72.91 | 0.00 | 0.00 |
September | 196.75 | 18.16 | 80.84 | 2.64 | 78.20 | 0.00 | 0.00 |
October | 239.03 | 22.71 | 105.77 | 16.86 | 88.90 | 0.00 | 0.00 |
November | 302.47 | 26.78 | 137.53 | 41.96 | 95.57 | 0.00 | 0.00 |
December | 360.01 | 41.18 | 168.94 | 71.88 | 97.07 | 0.00 | 0.00 |
Annual Sum or Average | 248.40 | 22.59 | 105.73 | 21.91 | 83.82 | 0.00 | 0.00 |
Minimum of Months | 173.24 | 9.83 | 72.82 | 0.00 | 72.82 | 0.00 | 0.00 |
Maximum of Months | 365.66 | 41.18 | 169.03 | 71.88 | 98.51 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 366.01 | 35.92 | 169.03 | 70.52 | 98.51 | 0.00 | 0.00 |
February | 334.42 | 28.30 | 143.53 | 46.80 | 96.74 | 0.00 | 0.00 |
March | 250.80 | 20.23 | 97.95 | 13.16 | 84.80 | 0.00 | 0.00 |
April | 193.19 | 9.13 | 73.03 | 0.03 | 73.00 | 0.00 | 0.00 |
May | 198.46 | 11.28 | 73.08 | 0.00 | 73.08 | 0.00 | 0.00 |
June | 196.03 | 12.38 | 72.82 | 0.00 | 72.82 | 0.00 | 0.00 |
July | 178.20 | 21.38 | 75.01 | 0.00 | 75.01 | 0.00 | 0.00 |
August | 173.62 | 17.34 | 73.02 | 0.11 | 72.91 | 0.00 | 0.00 |
September | 197.14 | 17.36 | 80.84 | 2.64 | 78.20 | 0.00 | 0.00 |
October | 239.40 | 21.84 | 105.77 | 16.86 | 88.90 | 0.00 | 0.00 |
November | 302.86 | 25.95 | 137.53 | 41.96 | 95.57 | 0.00 | 0.00 |
December | 360.38 | 40.35 | 168.94 | 71.88 | 97.07 | 0.00 | 0.00 |
Annual Sum or Average | 248.80 | 21.80 | 105.73 | 21.91 | 83.82 | 0.00 | 0.00 |
Minimum of Months | 173.62 | 9.13 | 72.82 | 0.00 | 72.82 | 0.00 | 0.00 |
Maximum of Months | 366.01 | 40.35 | 169.03 | 71.88 | 98.51 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 730.85 | 66.55 | 338.06 | 141.04 | 197.02 | 0.00 | 0.00 |
February | 667.16 | 51.06 | 287.07 | 93.59 | 193.47 | 0.00 | 0.00 |
March | 500.30 | 35.12 | 195.91 | 26.31 | 169.60 | 0.00 | 0.00 |
April | 386.59 | 14.99 | 146.06 | 0.07 | 145.99 | 0.00 | 0.00 |
May | 396.57 | 19.15 | 146.16 | 0.00 | 146.16 | 0.00 | 0.00 |
June | 391.84 | 21.22 | 145.63 | 0.00 | 145.63 | 0.00 | 0.00 |
July | 355.10 | 38.02 | 150.02 | 0.00 | 150.02 | 0.00 | 0.00 |
August | 346.20 | 29.30 | 146.05 | 0.23 | 145.82 | 0.00 | 0.00 |
September | 393.76 | 30.21 | 161.68 | 5.28 | 156.40 | 0.00 | 0.00 |
October | 478.16 | 38.58 | 211.53 | 33.73 | 177.80 | 0.00 | 0.00 |
November | 604.59 | 46.86 | 275.06 | 83.92 | 191.14 | 0.00 | 0.00 |
December | 719.63 | 75.51 | 337.89 | 143.76 | 194.13 | 0.00 | 0.00 |
Annual Sum or Average | 496.75 | 38.90 | 211.47 | 43.82 | 167.64 | 0.00 | 0.00 |
Minimum of Months | 346.20 | 14.99 | 145.63 | 0.00 | 145.63 | 0.00 | 0.00 |
Maximum of Months | 730.85 | 75.51 | 338.06 | 143.76 | 197.02 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 365.99 | 32.18 | 169.03 | 70.52 | 98.51 | 0.00 | 0.00 |
February | 334.34 | 24.35 | 143.53 | 46.80 | 96.74 | 0.00 | 0.00 |
March | 251.21 | 16.30 | 97.95 | 13.16 | 84.80 | 0.00 | 0.00 |
April | 195.07 | 6.68 | 73.03 | 0.03 | 73.00 | 0.00 | 0.00 |
May | 200.01 | 8.82 | 73.08 | 0.00 | 73.08 | 0.00 | 0.00 |
June | 197.70 | 9.78 | 72.82 | 0.00 | 72.82 | 0.00 | 0.00 |
July | 178.53 | 17.98 | 75.01 | 0.00 | 75.01 | 0.00 | 0.00 |
August | 174.17 | 13.55 | 73.02 | 0.11 | 72.91 | 0.00 | 0.00 |
September | 197.89 | 14.13 | 80.84 | 2.64 | 78.20 | 0.00 | 0.00 |
October | 239.81 | 18.26 | 105.77 | 16.86 | 88.90 | 0.00 | 0.00 |
November | 302.94 | 22.40 | 137.53 | 41.96 | 95.57 | 0.00 | 0.00 |
December | 360.29 | 36.70 | 168.94 | 71.88 | 97.07 | 0.00 | 0.00 |
Annual Sum or Average | 249.42 | 18.44 | 105.73 | 21.91 | 83.82 | 0.00 | 0.00 |
Minimum of Months | 174.17 | 6.68 | 72.82 | 0.00 | 72.82 | 0.00 | 0.00 |
Maximum of Months | 365.99 | 36.70 | 169.03 | 71.88 | 98.51 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 366.16 | 31.99 | 169.03 | 70.52 | 98.51 | 0.00 | 0.00 |
February | 334.50 | 24.17 | 143.53 | 46.80 | 96.74 | 0.00 | 0.00 |
March | 251.36 | 16.13 | 97.95 | 13.16 | 84.80 | 0.00 | 0.00 |
April | 195.25 | 6.57 | 73.03 | 0.03 | 73.00 | 0.00 | 0.00 |
May | 200.19 | 8.72 | 73.08 | 0.00 | 73.08 | 0.00 | 0.00 |
June | 197.88 | 9.66 | 72.82 | 0.00 | 72.82 | 0.00 | 0.00 |
July | 178.67 | 17.84 | 75.01 | 0.00 | 75.01 | 0.00 | 0.00 |
August | 174.32 | 13.39 | 73.02 | 0.11 | 72.91 | 0.00 | 0.00 |
September | 198.03 | 13.99 | 80.84 | 2.64 | 78.20 | 0.00 | 0.00 |
October | 239.96 | 18.08 | 105.77 | 16.86 | 88.90 | 0.00 | 0.00 |
November | 303.10 | 22.20 | 137.53 | 41.96 | 95.57 | 0.00 | 0.00 |
December | 360.46 | 36.49 | 168.94 | 71.88 | 97.07 | 0.00 | 0.00 |
Annual Sum or Average | 249.59 | 18.28 | 105.73 | 21.91 | 83.82 | 0.00 | 0.00 |
Minimum of Months | 174.32 | 6.57 | 72.82 | 0.00 | 72.82 | 0.00 | 0.00 |
Maximum of Months | 366.16 | 36.49 | 169.03 | 71.88 | 98.51 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 365.99 | 32.04 | 169.03 | 70.52 | 98.51 | 0.00 | 0.00 |
February | 334.21 | 24.34 | 143.53 | 46.80 | 96.74 | 0.00 | 0.00 |
March | 251.00 | 16.37 | 97.95 | 13.16 | 84.80 | 0.00 | 0.00 |
April | 194.63 | 6.81 | 73.03 | 0.03 | 73.00 | 0.00 | 0.00 |
May | 199.55 | 8.93 | 73.08 | 0.00 | 73.08 | 0.00 | 0.00 |
June | 197.25 | 9.93 | 72.82 | 0.00 | 72.82 | 0.00 | 0.00 |
July | 178.25 | 18.16 | 75.01 | 0.00 | 75.01 | 0.00 | 0.00 |
August | 173.94 | 13.64 | 73.02 | 0.11 | 72.91 | 0.00 | 0.00 |
September | 197.60 | 14.27 | 80.84 | 2.64 | 78.20 | 0.00 | 0.00 |
October | 239.71 | 18.20 | 105.77 | 16.86 | 88.90 | 0.00 | 0.00 |
November | 302.91 | 22.28 | 137.53 | 41.96 | 95.57 | 0.00 | 0.00 |
December | 360.35 | 36.51 | 168.94 | 71.88 | 97.07 | 0.00 | 0.00 |
Annual Sum or Average | 249.21 | 18.46 | 105.73 | 21.91 | 83.82 | 0.00 | 0.00 |
Minimum of Months | 173.94 | 6.81 | 72.82 | 0.00 | 72.82 | 0.00 | 0.00 |
Maximum of Months | 365.99 | 36.51 | 169.03 | 71.88 | 98.51 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 362.57 | 33.41 | 169.03 | 70.52 | 98.51 | 0.00 | 0.00 |
February | 329.90 | 26.28 | 143.53 | 46.80 | 96.74 | 0.00 | 0.00 |
March | 246.18 | 18.61 | 97.95 | 13.16 | 84.80 | 0.00 | 0.00 |
April | 188.09 | 8.75 | 73.03 | 0.03 | 73.00 | 0.00 | 0.00 |
May | 193.12 | 10.64 | 73.08 | 0.00 | 73.08 | 0.00 | 0.00 |
June | 190.78 | 12.10 | 72.82 | 0.00 | 72.82 | 0.00 | 0.00 |
July | 173.45 | 20.79 | 75.01 | 0.00 | 75.01 | 0.00 | 0.00 |
August | 169.31 | 15.98 | 73.02 | 0.11 | 72.91 | 0.00 | 0.00 |
September | 192.63 | 16.71 | 80.84 | 2.64 | 78.20 | 0.00 | 0.00 |
October | 236.09 | 19.98 | 105.77 | 16.86 | 88.90 | 0.00 | 0.00 |
November | 299.35 | 23.79 | 137.53 | 41.96 | 95.57 | 0.00 | 0.00 |
December | 357.25 | 37.74 | 168.94 | 71.88 | 97.07 | 0.00 | 0.00 |
Annual Sum or Average | 244.49 | 20.41 | 105.73 | 21.91 | 83.82 | 0.00 | 0.00 |
Minimum of Months | 169.31 | 8.75 | 72.82 | 0.00 | 72.82 | 0.00 | 0.00 |
Maximum of Months | 362.57 | 37.74 | 169.03 | 71.88 | 98.51 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.196107E+10 | 0.159882E+09 | 0.907326E+09 | 0.378547E+09 | 0.528779E+09 | 0.00 | 0.00 |
February | 0.161692E+10 | 0.108568E+09 | 0.695896E+09 | 0.226888E+09 | 0.469008E+09 | 0.00 | 0.00 |
March | 0.134185E+10 | 82239767.08 | 0.525793E+09 | 70614339.72 | 0.455178E+09 | 0.00 | 0.00 |
April | 0.101665E+10 | 35594815.75 | 0.379359E+09 | 170296.90 | 0.379188E+09 | 0.00 | 0.00 |
May | 0.108118E+10 | 45538731.11 | 0.392271E+09 | 0.00 | 0.392271E+09 | 0.00 | 0.00 |
June | 0.102960E+10 | 48455320.39 | 0.378251E+09 | 0.00 | 0.378251E+09 | 0.00 | 0.00 |
July | 0.963505E+09 | 90248214.06 | 0.402644E+09 | 0.00 | 0.402644E+09 | 0.00 | 0.00 |
August | 0.929840E+09 | 70040451.68 | 0.391977E+09 | 605808.70 | 0.391371E+09 | 0.00 | 0.00 |
September | 0.102814E+10 | 68628701.38 | 0.419948E+09 | 13715819.27 | 0.406232E+09 | 0.00 | 0.00 |
October | 0.128530E+10 | 89798836.31 | 0.567729E+09 | 90519872.30 | 0.477209E+09 | 0.00 | 0.00 |
November | 0.156952E+10 | 0.108384E+09 | 0.714420E+09 | 0.217960E+09 | 0.496460E+09 | 0.00 | 0.00 |
December | 0.192910E+10 | 0.184709E+09 | 0.906862E+09 | 0.385833E+09 | 0.521029E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.157527E+11 | 0.109209E+10 | 0.668248E+10 | 0.138485E+10 | 0.529762E+10 | 0.00 | 0.00 |
Minimum of Months | 0.929840E+09 | 35594815.75 | 0.378251E+09 | 0.00 | 0.378251E+09 | 0.00 | 0.00 |
Maximum of Months | 0.196107E+10 | 0.184709E+09 | 0.907326E+09 | 0.385833E+09 | 0.528779E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.984499E+09 | 79114534.61 | 0.453663E+09 | 0.189273E+09 | 0.264390E+09 | 0.00 | 0.00 |
February | 0.813693E+09 | 53097789.66 | 0.347948E+09 | 0.113444E+09 | 0.234504E+09 | 0.00 | 0.00 |
March | 0.678840E+09 | 39383759.50 | 0.262896E+09 | 35307169.86 | 0.227589E+09 | 0.00 | 0.00 |
April | 0.517903E+09 | 16495614.33 | 0.189679E+09 | 85148.45 | 0.189594E+09 | 0.00 | 0.00 |
May | 0.549573E+09 | 21921625.17 | 0.196136E+09 | 0.00 | 0.196136E+09 | 0.00 | 0.00 |
June | 0.524062E+09 | 22974430.24 | 0.189125E+09 | 0.00 | 0.189125E+09 | 0.00 | 0.00 |
July | 0.488267E+09 | 43693816.50 | 0.201322E+09 | 0.00 | 0.201322E+09 | 0.00 | 0.00 |
August | 0.471699E+09 | 33753670.64 | 0.195988E+09 | 302904.35 | 0.195686E+09 | 0.00 | 0.00 |
September | 0.520577E+09 | 33079736.29 | 0.209974E+09 | 6857909.64 | 0.203116E+09 | 0.00 | 0.00 |
October | 0.647212E+09 | 44213952.58 | 0.283864E+09 | 45259936.15 | 0.238604E+09 | 0.00 | 0.00 |
November | 0.789119E+09 | 53575342.34 | 0.357210E+09 | 0.108980E+09 | 0.248230E+09 | 0.00 | 0.00 |
December | 0.967949E+09 | 91741735.04 | 0.453431E+09 | 0.192916E+09 | 0.260515E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.795339E+10 | 0.533046E+09 | 0.334124E+10 | 0.692427E+09 | 0.264881E+10 | 0.00 | 0.00 |
Minimum of Months | 0.471699E+09 | 16495614.33 | 0.189125E+09 | 0.00 | 0.189125E+09 | 0.00 | 0.00 |
Maximum of Months | 0.984499E+09 | 91741735.04 | 0.453663E+09 | 0.192916E+09 | 0.264390E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.979729E+09 | 97155180.81 | 0.452732E+09 | 0.188885E+09 | 0.263847E+09 | 0.00 | 0.00 |
February | 0.808546E+09 | 69228671.09 | 0.347234E+09 | 0.113211E+09 | 0.234023E+09 | 0.00 | 0.00 |
March | 0.671158E+09 | 55050581.72 | 0.262357E+09 | 35234737.99 | 0.227122E+09 | 0.00 | 0.00 |
April | 0.500198E+09 | 24080059.93 | 0.189290E+09 | 84973.77 | 0.189205E+09 | 0.00 | 0.00 |
May | 0.531385E+09 | 30512929.22 | 0.195733E+09 | 0.00 | 0.195733E+09 | 0.00 | 0.00 |
June | 0.507709E+09 | 32213849.57 | 0.188737E+09 | 0.00 | 0.188737E+09 | 0.00 | 0.00 |
July | 0.476928E+09 | 57758962.58 | 0.200909E+09 | 0.00 | 0.200909E+09 | 0.00 | 0.00 |
August | 0.464329E+09 | 47526443.08 | 0.195586E+09 | 302282.95 | 0.195284E+09 | 0.00 | 0.00 |
September | 0.510423E+09 | 45729954.23 | 0.209543E+09 | 6843840.79 | 0.202700E+09 | 0.00 | 0.00 |
October | 0.640536E+09 | 59529005.08 | 0.283282E+09 | 45167086.40 | 0.238115E+09 | 0.00 | 0.00 |
November | 0.784265E+09 | 68431569.37 | 0.356477E+09 | 0.108756E+09 | 0.247721E+09 | 0.00 | 0.00 |
December | 0.964486E+09 | 0.109345E+09 | 0.452501E+09 | 0.192521E+09 | 0.259980E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.783969E+10 | 0.696562E+09 | 0.333438E+10 | 0.691007E+09 | 0.264338E+10 | 0.00 | 0.00 |
Minimum of Months | 0.464329E+09 | 24080059.93 | 0.188737E+09 | 0.00 | 0.188737E+09 | 0.00 | 0.00 |
Maximum of Months | 0.979729E+09 | 0.109345E+09 | 0.452732E+09 | 0.192521E+09 | 0.263847E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.979388E+09 | 98447653.82 | 0.452732E+09 | 0.188885E+09 | 0.263847E+09 | 0.00 | 0.00 |
February | 0.808180E+09 | 70493314.31 | 0.347234E+09 | 0.113211E+09 | 0.234023E+09 | 0.00 | 0.00 |
March | 0.670809E+09 | 56590422.98 | 0.262357E+09 | 35234737.99 | 0.227122E+09 | 0.00 | 0.00 |
April | 0.499423E+09 | 25485011.55 | 0.189290E+09 | 84973.77 | 0.189205E+09 | 0.00 | 0.00 |
May | 0.530119E+09 | 31806660.53 | 0.195733E+09 | 0.00 | 0.195733E+09 | 0.00 | 0.00 |
June | 0.506805E+09 | 33759135.11 | 0.188737E+09 | 0.00 | 0.188737E+09 | 0.00 | 0.00 |
July | 0.476339E+09 | 59383993.29 | 0.200909E+09 | 0.00 | 0.200909E+09 | 0.00 | 0.00 |
August | 0.464006E+09 | 48787654.76 | 0.195586E+09 | 302282.95 | 0.195284E+09 | 0.00 | 0.00 |
September | 0.509971E+09 | 47072440.24 | 0.209543E+09 | 6843840.79 | 0.202700E+09 | 0.00 | 0.00 |
October | 0.640226E+09 | 60818436.86 | 0.283282E+09 | 45167086.40 | 0.238115E+09 | 0.00 | 0.00 |
November | 0.784013E+09 | 69410357.26 | 0.356477E+09 | 0.108756E+09 | 0.247721E+09 | 0.00 | 0.00 |
December | 0.964248E+09 | 0.110305E+09 | 0.452501E+09 | 0.192521E+09 | 0.259980E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.783353E+10 | 0.712360E+09 | 0.333438E+10 | 0.691007E+09 | 0.264338E+10 | 0.00 | 0.00 |
Minimum of Months | 0.464006E+09 | 25485011.55 | 0.188737E+09 | 0.00 | 0.188737E+09 | 0.00 | 0.00 |
Maximum of Months | 0.979388E+09 | 0.110305E+09 | 0.452732E+09 | 0.192521E+09 | 0.263847E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.980328E+09 | 96211649.57 | 0.452732E+09 | 0.188885E+09 | 0.263847E+09 | 0.00 | 0.00 |
February | 0.809034E+09 | 68455375.66 | 0.347234E+09 | 0.113211E+09 | 0.234023E+09 | 0.00 | 0.00 |
March | 0.671738E+09 | 54171867.09 | 0.262357E+09 | 35234737.99 | 0.227122E+09 | 0.00 | 0.00 |
April | 0.500740E+09 | 23659072.99 | 0.189290E+09 | 84973.77 | 0.189205E+09 | 0.00 | 0.00 |
May | 0.531546E+09 | 30219518.55 | 0.195733E+09 | 0.00 | 0.195733E+09 | 0.00 | 0.00 |
June | 0.508103E+09 | 32079073.11 | 0.188737E+09 | 0.00 | 0.188737E+09 | 0.00 | 0.00 |
July | 0.477283E+09 | 57262455.10 | 0.200909E+09 | 0.00 | 0.200909E+09 | 0.00 | 0.00 |
August | 0.465023E+09 | 46439501.98 | 0.195586E+09 | 302282.95 | 0.195284E+09 | 0.00 | 0.00 |
September | 0.510996E+09 | 44988653.08 | 0.209543E+09 | 6843840.79 | 0.202700E+09 | 0.00 | 0.00 |
October | 0.641199E+09 | 58495064.75 | 0.283282E+09 | 45167086.40 | 0.238115E+09 | 0.00 | 0.00 |
November | 0.785008E+09 | 67273282.05 | 0.356477E+09 | 0.108756E+09 | 0.247721E+09 | 0.00 | 0.00 |
December | 0.965237E+09 | 0.108077E+09 | 0.452501E+09 | 0.192521E+09 | 0.259980E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.784624E+10 | 0.687332E+09 | 0.333438E+10 | 0.691007E+09 | 0.264338E+10 | 0.00 | 0.00 |
Minimum of Months | 0.465023E+09 | 23659072.99 | 0.188737E+09 | 0.00 | 0.188737E+09 | 0.00 | 0.00 |
Maximum of Months | 0.980328E+09 | 0.108077E+09 | 0.452732E+09 | 0.192521E+09 | 0.263847E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.195752E+10 | 0.178254E+09 | 0.905465E+09 | 0.377770E+09 | 0.527694E+09 | 0.00 | 0.00 |
February | 0.161399E+10 | 0.123523E+09 | 0.694469E+09 | 0.226423E+09 | 0.468046E+09 | 0.00 | 0.00 |
March | 0.134001E+10 | 94073289.16 | 0.524714E+09 | 70469475.98 | 0.454245E+09 | 0.00 | 0.00 |
April | 0.100205E+10 | 38861996.86 | 0.378580E+09 | 169947.54 | 0.378410E+09 | 0.00 | 0.00 |
May | 0.106217E+10 | 51291191.75 | 0.391467E+09 | 0.00 | 0.391467E+09 | 0.00 | 0.00 |
June | 0.101564E+10 | 54994541.66 | 0.377475E+09 | 0.00 | 0.377475E+09 | 0.00 | 0.00 |
July | 0.951106E+09 | 0.101834E+09 | 0.401818E+09 | 0.00 | 0.401818E+09 | 0.00 | 0.00 |
August | 0.927262E+09 | 78485604.06 | 0.391173E+09 | 604565.89 | 0.390568E+09 | 0.00 | 0.00 |
September | 0.102062E+10 | 78294686.23 | 0.419087E+09 | 13687681.57 | 0.405399E+09 | 0.00 | 0.00 |
October | 0.128070E+10 | 0.103324E+09 | 0.566564E+09 | 90334172.81 | 0.476230E+09 | 0.00 | 0.00 |
November | 0.156709E+10 | 0.121462E+09 | 0.712955E+09 | 0.217513E+09 | 0.495442E+09 | 0.00 | 0.00 |
December | 0.192745E+10 | 0.202247E+09 | 0.905001E+09 | 0.385041E+09 | 0.519960E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.156656E+11 | 0.122665E+10 | 0.666877E+10 | 0.138201E+10 | 0.528675E+10 | 0.00 | 0.00 |
Minimum of Months | 0.927262E+09 | 38861996.86 | 0.377475E+09 | 0.00 | 0.377475E+09 | 0.00 | 0.00 |
Maximum of Months | 0.195752E+10 | 0.202247E+09 | 0.905465E+09 | 0.385041E+09 | 0.527694E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.980266E+09 | 86204259.28 | 0.452732E+09 | 0.188885E+09 | 0.263847E+09 | 0.00 | 0.00 |
February | 0.808840E+09 | 58895684.51 | 0.347234E+09 | 0.113211E+09 | 0.234023E+09 | 0.00 | 0.00 |
March | 0.672847E+09 | 43651854.82 | 0.262357E+09 | 35234737.99 | 0.227122E+09 | 0.00 | 0.00 |
April | 0.505615E+09 | 17313939.09 | 0.189290E+09 | 84973.77 | 0.189205E+09 | 0.00 | 0.00 |
May | 0.535712E+09 | 23627655.81 | 0.195733E+09 | 0.00 | 0.195733E+09 | 0.00 | 0.00 |
June | 0.512441E+09 | 25340124.58 | 0.188737E+09 | 0.00 | 0.188737E+09 | 0.00 | 0.00 |
July | 0.478185E+09 | 48168711.90 | 0.200909E+09 | 0.00 | 0.200909E+09 | 0.00 | 0.00 |
August | 0.466506E+09 | 36301022.33 | 0.195586E+09 | 302282.95 | 0.195284E+09 | 0.00 | 0.00 |
September | 0.512933E+09 | 36636400.39 | 0.209543E+09 | 6843840.79 | 0.202700E+09 | 0.00 | 0.00 |
October | 0.642300E+09 | 48919345.25 | 0.283282E+09 | 45167086.40 | 0.238115E+09 | 0.00 | 0.00 |
November | 0.785212E+09 | 58051543.76 | 0.356477E+09 | 0.108756E+09 | 0.247721E+09 | 0.00 | 0.00 |
December | 0.965001E+09 | 98289368.22 | 0.452501E+09 | 0.192521E+09 | 0.259980E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.786586E+10 | 0.581400E+09 | 0.333438E+10 | 0.691007E+09 | 0.264338E+10 | 0.00 | 0.00 |
Minimum of Months | 0.466506E+09 | 17313939.09 | 0.188737E+09 | 0.00 | 0.188737E+09 | 0.00 | 0.00 |
Maximum of Months | 0.980266E+09 | 98289368.22 | 0.452732E+09 | 0.192521E+09 | 0.263847E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.980712E+09 | 85674562.48 | 0.452732E+09 | 0.188885E+09 | 0.263847E+09 | 0.00 | 0.00 |
February | 0.809212E+09 | 58465497.44 | 0.347234E+09 | 0.113211E+09 | 0.234023E+09 | 0.00 | 0.00 |
March | 0.673240E+09 | 43202284.42 | 0.262357E+09 | 35234737.99 | 0.227122E+09 | 0.00 | 0.00 |
April | 0.506086E+09 | 17039381.78 | 0.189290E+09 | 84973.77 | 0.189205E+09 | 0.00 | 0.00 |
May | 0.536199E+09 | 23353803.05 | 0.195733E+09 | 0.00 | 0.195733E+09 | 0.00 | 0.00 |
June | 0.512917E+09 | 25049224.18 | 0.188737E+09 | 0.00 | 0.188737E+09 | 0.00 | 0.00 |
July | 0.478552E+09 | 47771086.55 | 0.200909E+09 | 0.00 | 0.200909E+09 | 0.00 | 0.00 |
August | 0.466895E+09 | 35874416.39 | 0.195586E+09 | 302282.95 | 0.195284E+09 | 0.00 | 0.00 |
September | 0.513304E+09 | 36260224.53 | 0.209543E+09 | 6843840.79 | 0.202700E+09 | 0.00 | 0.00 |
October | 0.642719E+09 | 48422073.10 | 0.283282E+09 | 45167086.40 | 0.238115E+09 | 0.00 | 0.00 |
November | 0.785639E+09 | 57555315.69 | 0.356477E+09 | 0.108756E+09 | 0.247721E+09 | 0.00 | 0.00 |
December | 0.965448E+09 | 97731342.27 | 0.452501E+09 | 0.192521E+09 | 0.259980E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.787092E+10 | 0.576399E+09 | 0.333438E+10 | 0.691007E+09 | 0.264338E+10 | 0.00 | 0.00 |
Minimum of Months | 0.466895E+09 | 17039381.78 | 0.188737E+09 | 0.00 | 0.188737E+09 | 0.00 | 0.00 |
Maximum of Months | 0.980712E+09 | 97731342.27 | 0.452732E+09 | 0.192521E+09 | 0.263847E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.980278E+09 | 85823084.64 | 0.452732E+09 | 0.188885E+09 | 0.263847E+09 | 0.00 | 0.00 |
February | 0.808531E+09 | 58878997.10 | 0.347234E+09 | 0.113211E+09 | 0.234023E+09 | 0.00 | 0.00 |
March | 0.672283E+09 | 43854154.93 | 0.262357E+09 | 35234737.99 | 0.227122E+09 | 0.00 | 0.00 |
April | 0.504473E+09 | 17656575.71 | 0.189290E+09 | 84973.77 | 0.189205E+09 | 0.00 | 0.00 |
May | 0.534469E+09 | 23918620.18 | 0.195733E+09 | 0.00 | 0.195733E+09 | 0.00 | 0.00 |
June | 0.511280E+09 | 25744885.32 | 0.188737E+09 | 0.00 | 0.188737E+09 | 0.00 | 0.00 |
July | 0.477432E+09 | 48629724.89 | 0.200909E+09 | 0.00 | 0.200909E+09 | 0.00 | 0.00 |
August | 0.465874E+09 | 36520424.31 | 0.195586E+09 | 302282.95 | 0.195284E+09 | 0.00 | 0.00 |
September | 0.512181E+09 | 36980560.30 | 0.209543E+09 | 6843840.79 | 0.202700E+09 | 0.00 | 0.00 |
October | 0.642050E+09 | 48758747.98 | 0.283282E+09 | 45167086.40 | 0.238115E+09 | 0.00 | 0.00 |
November | 0.785147E+09 | 57739695.45 | 0.356477E+09 | 0.108756E+09 | 0.247721E+09 | 0.00 | 0.00 |
December | 0.965152E+09 | 97775510.46 | 0.452501E+09 | 0.192521E+09 | 0.259980E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.785915E+10 | 0.582281E+09 | 0.333438E+10 | 0.691007E+09 | 0.264338E+10 | 0.00 | 0.00 |
Minimum of Months | 0.465874E+09 | 17656575.71 | 0.188737E+09 | 0.00 | 0.188737E+09 | 0.00 | 0.00 |
Maximum of Months | 0.980278E+09 | 97775510.46 | 0.452732E+09 | 0.192521E+09 | 0.263847E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.971099E+09 | 89477381.41 | 0.452732E+09 | 0.188885E+09 | 0.263847E+09 | 0.00 | 0.00 |
February | 0.798096E+09 | 63567752.58 | 0.347234E+09 | 0.113211E+09 | 0.234023E+09 | 0.00 | 0.00 |
March | 0.659357E+09 | 49851064.34 | 0.262357E+09 | 35234737.99 | 0.227122E+09 | 0.00 | 0.00 |
April | 0.487526E+09 | 22681865.96 | 0.189290E+09 | 84973.77 | 0.189205E+09 | 0.00 | 0.00 |
May | 0.517244E+09 | 28503961.24 | 0.195733E+09 | 0.00 | 0.195733E+09 | 0.00 | 0.00 |
June | 0.494501E+09 | 31361443.96 | 0.188737E+09 | 0.00 | 0.188737E+09 | 0.00 | 0.00 |
July | 0.464563E+09 | 55678473.74 | 0.200909E+09 | 0.00 | 0.200909E+09 | 0.00 | 0.00 |
August | 0.453477E+09 | 42807795.00 | 0.195586E+09 | 302282.95 | 0.195284E+09 | 0.00 | 0.00 |
September | 0.499287E+09 | 43320954.32 | 0.209543E+09 | 6843840.79 | 0.202700E+09 | 0.00 | 0.00 |
October | 0.632346E+09 | 53508229.99 | 0.283282E+09 | 45167086.40 | 0.238115E+09 | 0.00 | 0.00 |
November | 0.775914E+09 | 61659846.27 | 0.356477E+09 | 0.108756E+09 | 0.247721E+09 | 0.00 | 0.00 |
December | 0.956871E+09 | 0.101074E+09 | 0.452501E+09 | 0.192521E+09 | 0.259980E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.771028E+10 | 0.643493E+09 | 0.333438E+10 | 0.691007E+09 | 0.264338E+10 | 0.00 | 0.00 |
Minimum of Months | 0.453477E+09 | 22681865.96 | 0.188737E+09 | 0.00 | 0.188737E+09 | 0.00 | 0.00 |
Maximum of Months | 0.971099E+09 | 0.101074E+09 | 0.452732E+09 | 0.192521E+09 | 0.263847E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 26.42 | 22.38 | 20.70 | 2.25 | 18.66 | 103.85 | 146.57 | 0.01 |
February | 27.50 | 22.91 | 21.01 | 2.37 | 18.54 | 110.59 | 164.59 | 0.00 |
March | 28.33 | 23.63 | 21.77 | 3.67 | 19.85 | 110.33 | 194.39 | 0.01 |
April | 29.15 | 25.37 | 24.04 | 2.98 | 21.51 | 118.69 | 185.56 | 0.03 |
May | 29.01 | 26.53 | 25.72 | 3.19 | 23.00 | 127.71 | 124.87 | 0.08 |
June | 28.86 | 26.50 | 25.74 | 3.10 | 22.78 | 123.38 | 156.09 | 0.05 |
July | 27.25 | 24.29 | 23.20 | 2.32 | 21.53 | 137.39 | 88.28 | 0.02 |
August | 27.54 | 25.86 | 25.31 | 3.22 | 21.55 | 129.55 | 122.00 | 0.07 |
September | 27.58 | 25.59 | 24.93 | 2.22 | 22.01 | 128.30 | 103.37 | 0.04 |
October | 26.89 | 25.07 | 24.46 | 2.18 | 21.39 | 123.79 | 92.41 | 0.11 |
November | 26.68 | 24.14 | 23.20 | 1.94 | 20.29 | 113.70 | 103.30 | 0.02 |
December | 25.97 | 22.85 | 21.57 | 2.00 | 18.63 | 101.83 | 131.96 | 0.00 |
Annual Sum or Average | 27.59 | 24.60 | 23.48 | 2.62 | 20.82 | 119.14 | 134.17 | 0.04 |
Minimum of Months | 25.97 | 22.38 | 20.70 | 1.94 | 18.54 | 101.83 | 88.28 | 0.00 |
Maximum of Months | 29.15 | 26.53 | 25.74 | 3.67 | 23.00 | 137.39 | 194.39 | 0.11 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 34.10 | 04-JAN-12:00 | 23.67 | 19.40 | 5.00 | 24.66 | 266.50 | 576.50 |
February | 35.00 | 21-FEB-13:00 | 22.02 | 16.00 | 2.10 | 24.16 | 230.00 | 672.50 |
March | 36.40 | 21-MAR-12:00 | 23.01 | 17.00 | 5.00 | 26.97 | 269.50 | 658.50 |
April | 35.50 | 01-APR-13:00 | 26.96 | 24.00 | 2.50 | 27.14 | 295.50 | 519.50 |
May | 37.60 | 06-MAY-12:00 | 26.43 | 22.60 | 4.00 | 29.39 | 317.00 | 525.50 |
June | 36.00 | 12-JUN-14:00 | 27.60 | 25.00 | 4.00 | 28.43 | 235.00 | 472.00 |
July | 33.20 | 15-JUL-15:00 | 25.63 | 23.00 | 2.00 | 27.95 | 219.00 | 181.00 |
August | 34.00 | 10-AUG-13:00 | 27.86 | 26.00 | 5.00 | 26.65 | 344.50 | 278.50 |
September | 34.00 | 06-SEP-13:00 | 26.51 | 24.00 | 4.00 | 25.00 | 258.00 | 581.50 |
October | 33.00 | 04-OCT-13:00 | 26.23 | 24.00 | 4.00 | 25.16 | 303.00 | 428.50 |
November | 34.30 | 18-NOV-12:00 | 25.34 | 22.20 | 3.00 | 25.49 | 289.50 | 511.50 |
December | 33.00 | 07-DEC-13:00 | 23.23 | 19.00 | 3.00 | 22.98 | 215.00 | 596.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 33.00 | 22.02 | 16.00 | 2.00 | 22.98 | 215.00 | 181.00 | |
Maximum of Months | 37.60 | 27.86 | 26.00 | 5.00 | 29.39 | 344.50 | 672.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 18.70 | 23-JAN-05:00 | 16.92 | 16.00 | 2.00 | 7.75 | 0.00 | 0.00 |
February | 20.30 | 21-FEB-09:00 | 19.04 | 18.40 | 2.00 | 10.50 | 258.50 | 564.00 |
March | 22.00 | 03-MAR-05:00 | 19.94 | 19.00 | 3.00 | 13.35 | 0.00 | 0.00 |
April | 22.90 | 14-APR-15:00 | 22.90 | 22.90 | 3.00 | 14.65 | 199.50 | 264.50 |
May | 22.00 | 10-MAY-19:00 | 22.00 | 22.00 | 2.00 | 18.28 | 0.00 | 0.00 |
June | 23.00 | 20-JUN-23:00 | 23.00 | 23.00 | 2.00 | 19.35 | 0.00 | 0.00 |
July | 23.00 | 13-JUL-04:00 | 22.27 | 22.00 | 0.00 | 13.91 | 0.00 | 0.00 |
August | 22.00 | 20-AUG-10:00 | 22.00 | 22.00 | 5.00 | 18.28 | 430.50 | 41.50 |
September | 22.90 | 19-SEP-03:00 | 22.78 | 22.78 | 0.00 | 21.27 | 0.00 | 0.00 |
October | 22.50 | 23-OCT-04:00 | 22.50 | 22.50 | 2.80 | 18.82 | 0.00 | 0.00 |
November | 20.00 | 25-NOV-04:00 | 18.63 | 18.00 | 2.00 | 10.69 | 0.00 | 0.00 |
December | 18.00 | 21-DEC-04:00 | 17.36 | 17.00 | 3.00 | 9.13 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 18.00 | 16.92 | 16.00 | 0.00 | 7.75 | 0.00 | 0.00 | |
Maximum of Months | 23.00 | 23.00 | 23.00 | 5.00 | 21.27 | 430.50 | 564.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 25.53 | 12-JAN-12:00 | 32.40 | 23.10 | 2.00 | 25.00 | 353.00 | 347.00 |
February | 26.17 | 14-FEB-15:00 | 32.30 | 24.20 | 2.00 | 25.16 | 200.00 | 199.00 |
March | 26.28 | 27-MAR-12:00 | 34.20 | 23.60 | 4.00 | 26.32 | 326.00 | 535.00 |
April | 27.93 | 10-APR-16:49 | 31.52 | 26.85 | 4.08 | 27.70 | 110.67 | 57.00 |
May | 29.00 | 28-MAY-20:00 | 29.00 | 29.00 | 3.00 | 22.47 | 0.00 | 0.00 |
June | 30.11 | 15-JUN-09:00 | 33.20 | 29.20 | 5.00 | 26.48 | 320.50 | 421.00 |
July | 26.43 | 20-JUL-14:00 | 32.80 | 24.20 | 1.00 | 26.65 | 305.00 | 253.00 |
August | 28.81 | 14-AUG-16:00 | 32.00 | 28.00 | 1.00 | 25.16 | 107.50 | 223.00 |
September | 30.06 | 30-SEP-10:00 | 32.80 | 29.40 | 3.00 | 25.66 | 398.00 | 359.50 |
October | 27.36 | 16-OCT-14:00 | 31.50 | 26.00 | 3.00 | 24.16 | 239.00 | 346.50 |
November | 27.56 | 10-NOV-12:00 | 31.00 | 26.40 | 6.00 | 28.11 | 388.00 | 95.50 |
December | 26.86 | 03-DEC-12:00 | 31.50 | 25.30 | 1.00 | 23.49 | 301.00 | 468.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 25.53 | 29.00 | 23.10 | 1.00 | 22.47 | 0.00 | 0.00 | |
Maximum of Months | 30.11 | 34.20 | 29.40 | 6.00 | 28.11 | 398.00 | 535.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 24.20 | 09-JAN-21:00 | 26.50 | 24.77 | 4.00 | 25.16 | 0.00 | 0.00 |
February | 24.40 | 15-FEB-18:00 | 28.30 | 25.33 | 4.00 | 20.75 | 0.00 | 0.00 |
March | 25.30 | 28-MAR-06:00 | 27.20 | 25.72 | 3.00 | 19.87 | 103.00 | 28.00 |
April | 27.00 | 10-APR-17:00 | 30.50 | 27.87 | 4.50 | 25.00 | 20.00 | 20.50 |
May | 29.00 | 28-MAY-20:00 | 29.00 | 29.00 | 3.00 | 22.47 | 0.00 | 0.00 |
June | 29.20 | 15-JUN-09:00 | 33.20 | 30.11 | 5.00 | 26.48 | 320.50 | 421.00 |
July | 26.00 | 10-JUL-14:00 | 26.50 | 26.11 | 2.30 | 23.49 | 286.00 | 36.50 |
August | 28.00 | 02-AUG-10:00 | 31.00 | 28.65 | 4.00 | 24.16 | 419.00 | 195.50 |
September | 29.40 | 30-SEP-10:00 | 32.80 | 30.06 | 3.00 | 25.66 | 398.00 | 359.50 |
October | 26.50 | 16-OCT-08:00 | 29.00 | 27.04 | 2.50 | 21.78 | 300.00 | 326.00 |
November | 26.40 | 10-NOV-12:00 | 31.00 | 27.56 | 6.00 | 28.11 | 388.00 | 95.50 |
December | 26.00 | 10-DEC-17:00 | 29.00 | 26.74 | 3.00 | 21.78 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 24.20 | 26.50 | 24.77 | 2.30 | 19.87 | 0.00 | 0.00 | |
Maximum of Months | 29.40 | 33.20 | 30.11 | 6.00 | 28.11 | 419.00 | 421.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 29.71 | 38.82 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 29.90 | 44.34 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 30.35 | 50.49 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 30.97 | 51.18 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 31.58 | 43.47 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 32.02 | 46.77 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 32.16 | 39.95 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 31.97 | 43.65 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 31.50 | 40.53 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 30.87 | 37.35 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 30.27 | 35.77 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 29.84 | 36.19 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 30.93 | 42.35 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 29.71 | 35.77 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 32.16 | 51.18 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK1
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.255452E+09 | -143758629.3 | 0.00 | 0.00 | 744.00 | 0.00 | -111693703.6 | 58.99 | 0.00 | 0.00 |
February | 0.230467E+09 | -129698107.2 | 0.00 | 0.00 | 672.00 | 0.00 | -100768938.6 | 58.99 | 0.00 | 0.00 |
March | 0.255102E+09 | -143669010.2 | 0.00 | 0.00 | 744.00 | 0.00 | -111433153.0 | 58.99 | 0.00 | 0.00 |
April | 0.241899E+09 | -134262250.7 | 0.00 | 0.00 | 720.00 | 0.00 | -107636359.1 | 58.99 | 0.00 | 0.00 |
May | 0.247112E+09 | -135932988.7 | 0.00 | 0.00 | 744.00 | 0.00 | -111179144.8 | 58.99 | 0.00 | 0.00 |
June | 0.238367E+09 | -130798056.7 | 0.00 | 0.00 | 720.00 | 0.00 | -107568703.3 | 58.99 | 0.00 | 0.00 |
July | 0.243073E+09 | -131708172.3 | 0.00 | 0.00 | 744.00 | 0.00 | -111365164.2 | 58.99 | 0.00 | 0.00 |
August | 0.246845E+09 | -135470298.3 | 0.00 | 0.00 | 744.00 | 0.00 | -111374634.8 | 58.99 | 0.00 | 0.00 |
September | 0.239651E+09 | -131874320.4 | 0.00 | 0.00 | 720.00 | 0.00 | -107776975.3 | 58.99 | 0.00 | 0.00 |
October | 0.249517E+09 | -138049868.1 | 0.00 | 0.00 | 744.00 | 0.00 | -111467187.4 | 58.99 | 0.00 | 0.00 |
November | 0.244054E+09 | -136110540.7 | 0.00 | 0.00 | 720.00 | 0.00 | -107943340.4 | 58.99 | 0.00 | 0.00 |
December | 0.255093E+09 | -143329841.4 | 0.00 | 0.00 | 744.00 | 0.00 | -111762724.8 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.294663E+10 | -0.163466E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.131197E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.230467E+09 | -143758629.3 | 0.00 | 0.00 | 672.00 | 0.00 | -111762724.8 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.255452E+09 | -129698107.2 | 0.00 | 0.00 | 744.00 | 0.00 | -100768938.6 | 58.99 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK2
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.255373E+09 | -143756680.4 | 0.00 | 0.00 | 744.00 | 0.00 | -111616381.2 | 58.99 | 0.00 | 0.00 |
February | 0.230432E+09 | -129697128.0 | 0.00 | 0.00 | 672.00 | 0.00 | -100734780.3 | 58.99 | 0.00 | 0.00 |
March | 0.255096E+09 | -143672033.0 | 0.00 | 0.00 | 744.00 | 0.00 | -111424115.4 | 58.99 | 0.00 | 0.00 |
April | 0.241937E+09 | -134258973.4 | 0.00 | 0.00 | 720.00 | 0.00 | -107678399.8 | 58.99 | 0.00 | 0.00 |
May | 0.247143E+09 | -135933418.2 | 0.00 | 0.00 | 744.00 | 0.00 | -111209950.2 | 58.99 | 0.00 | 0.00 |
June | 0.238410E+09 | -130798042.3 | 0.00 | 0.00 | 720.00 | 0.00 | -107612127.3 | 58.99 | 0.00 | 0.00 |
July | 0.243077E+09 | -131708111.6 | 0.00 | 0.00 | 744.00 | 0.00 | -111368967.0 | 58.99 | 0.00 | 0.00 |
August | 0.246852E+09 | -135469804.3 | 0.00 | 0.00 | 744.00 | 0.00 | -111381868.3 | 58.99 | 0.00 | 0.00 |
September | 0.239662E+09 | -131875015.2 | 0.00 | 0.00 | 720.00 | 0.00 | -107787324.6 | 58.99 | 0.00 | 0.00 |
October | 0.249486E+09 | -138051795.0 | 0.00 | 0.00 | 744.00 | 0.00 | -111434055.8 | 58.99 | 0.00 | 0.00 |
November | 0.244008E+09 | -136111258.7 | 0.00 | 0.00 | 720.00 | 0.00 | -107896900.7 | 58.99 | 0.00 | 0.00 |
December | 0.254999E+09 | -143322022.6 | 0.00 | 0.00 | 744.00 | 0.00 | -111677215.8 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.294648E+10 | -0.163465E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.131182E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.230432E+09 | -143756680.4 | 0.00 | 0.00 | 672.00 | 0.00 | -111677215.8 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.255373E+09 | -129697128.0 | 0.00 | 0.00 | 744.00 | 0.00 | -100734780.3 | 58.99 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK3
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.236213E+09 | -126450366.8 | 0.00 | 0.00 | 744.00 | 0.00 | -109762648.5 | 58.98 | 0.00 | 0.00 |
February | 0.213167E+09 | -114152133.0 | 0.00 | 0.00 | 672.00 | 0.00 | -99014806.3 | 58.99 | 0.00 | 0.00 |
March | 0.237772E+09 | -128221035.3 | 0.00 | 0.00 | 744.00 | 0.00 | -109551322.4 | 58.99 | 0.00 | 0.00 |
April | 0.223718E+09 | -118078205.7 | 0.00 | 0.00 | 720.00 | 0.00 | -105640259.0 | 58.99 | 0.00 | 0.00 |
May | 0.229675E+09 | -120538937.7 | 0.00 | 0.00 | 744.00 | 0.00 | -109136297.6 | 58.99 | 0.00 | 0.00 |
June | 0.222092E+09 | -116522987.7 | 0.00 | 0.00 | 720.00 | 0.00 | -105568630.8 | 58.98 | 0.00 | 0.00 |
July | 0.224480E+09 | -115182499.2 | 0.00 | 0.00 | 744.00 | 0.00 | -109297793.8 | 58.98 | 0.00 | 0.00 |
August | 0.230627E+09 | -121008614.7 | 0.00 | 0.00 | 744.00 | 0.00 | -109618200.0 | 58.99 | 0.00 | 0.00 |
September | 0.221816E+09 | -115902531.1 | 0.00 | 0.00 | 720.00 | 0.00 | -105913163.3 | 58.99 | 0.00 | 0.00 |
October | 0.231051E+09 | -121408962.4 | 0.00 | 0.00 | 744.00 | 0.00 | -109642246.3 | 58.99 | 0.00 | 0.00 |
November | 0.226433E+09 | -120173977.1 | 0.00 | 0.00 | 720.00 | 0.00 | -106258883.1 | 58.99 | 0.00 | 0.00 |
December | 0.235064E+09 | -125111554.1 | 0.00 | 0.00 | 744.00 | 0.00 | -109952474.0 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.273211E+10 | -0.144275E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.128936E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.213167E+09 | -128221035.3 | 0.00 | 0.00 | 672.00 | 0.00 | -109952474.0 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.237772E+09 | -114152133.0 | 0.00 | 0.00 | 744.00 | 0.00 | -99014806.3 | 58.99 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK4
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.236140E+09 | -126456686.3 | 0.00 | 0.00 | 744.00 | 0.00 | -109683795.3 | 58.98 | 0.00 | 0.00 |
February | 0.213092E+09 | -114146259.7 | 0.00 | 0.00 | 672.00 | 0.00 | -98946084.3 | 58.99 | 0.00 | 0.00 |
March | 0.237685E+09 | -128228097.5 | 0.00 | 0.00 | 744.00 | 0.00 | -109456709.0 | 58.99 | 0.00 | 0.00 |
April | 0.223611E+09 | -118079970.0 | 0.00 | 0.00 | 720.00 | 0.00 | -105530923.4 | 58.99 | 0.00 | 0.00 |
May | 0.229571E+09 | -120553356.9 | 0.00 | 0.00 | 744.00 | 0.00 | -109017342.7 | 58.99 | 0.00 | 0.00 |
June | 0.221972E+09 | -116482378.7 | 0.00 | 0.00 | 720.00 | 0.00 | -105489305.1 | 58.99 | 0.00 | 0.00 |
July | 0.224361E+09 | -115139633.6 | 0.00 | 0.00 | 744.00 | 0.00 | -109221504.9 | 58.99 | 0.00 | 0.00 |
August | 0.230555E+09 | -120987760.5 | 0.00 | 0.00 | 744.00 | 0.00 | -109566939.1 | 58.99 | 0.00 | 0.00 |
September | 0.221740E+09 | -115905990.7 | 0.00 | 0.00 | 720.00 | 0.00 | -105834329.5 | 58.99 | 0.00 | 0.00 |
October | 0.230962E+09 | -121385141.6 | 0.00 | 0.00 | 744.00 | 0.00 | -109576712.6 | 58.99 | 0.00 | 0.00 |
November | 0.226377E+09 | -120166604.5 | 0.00 | 0.00 | 720.00 | 0.00 | -106210788.4 | 58.99 | 0.00 | 0.00 |
December | 0.235009E+09 | -125113163.0 | 0.00 | 0.00 | 744.00 | 0.00 | -109896292.1 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.273108E+10 | -0.144265E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.128843E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.213092E+09 | -128228097.5 | 0.00 | 0.00 | 672.00 | 0.00 | -109896292.1 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.237685E+09 | -114146259.7 | 0.00 | 0.00 | 744.00 | 0.00 | -98946084.3 | 58.99 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK5
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.229747E+09 | -119480223.3 | 0.00 | 0.00 | 744.00 | 0.00 | -110266902.2 | 58.99 | 0.00 | 0.00 |
February | 0.207397E+09 | -107949914.0 | 0.00 | 0.00 | 672.00 | 0.00 | -99446759.2 | 58.99 | 0.00 | 0.00 |
March | 0.231398E+09 | -121315107.6 | 0.00 | 0.00 | 744.00 | 0.00 | -110082635.6 | 58.99 | 0.00 | 0.00 |
April | 0.217846E+09 | -111730276.0 | 0.00 | 0.00 | 720.00 | 0.00 | -106115768.0 | 58.99 | 0.00 | 0.00 |
May | 0.223540E+09 | -114004906.2 | 0.00 | 0.00 | 744.00 | 0.00 | -109534944.0 | 58.99 | 0.00 | 0.00 |
June | 0.216258E+09 | -110185344.7 | 0.00 | 0.00 | 720.00 | 0.00 | -106072751.4 | 59.00 | 0.00 | 0.00 |
July | 0.218611E+09 | -108904990.3 | 0.00 | 0.00 | 744.00 | 0.00 | -109706507.8 | 58.99 | 0.00 | 0.00 |
August | 0.224636E+09 | -114520895.5 | 0.00 | 0.00 | 744.00 | 0.00 | -110115339.7 | 58.98 | 0.00 | 0.00 |
September | 0.216028E+09 | -109688666.9 | 0.00 | 0.00 | 720.00 | 0.00 | -106339371.8 | 58.99 | 0.00 | 0.00 |
October | 0.224838E+09 | -114771810.9 | 0.00 | 0.00 | 744.00 | 0.00 | -110066252.6 | 58.98 | 0.00 | 0.00 |
November | 0.220218E+09 | -113501442.8 | 0.00 | 0.00 | 720.00 | 0.00 | -106716420.0 | 58.99 | 0.00 | 0.00 |
December | 0.228734E+09 | -118339073.3 | 0.00 | 0.00 | 744.00 | 0.00 | -110395258.1 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.265925E+10 | -0.136439E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.129486E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.207397E+09 | -121315107.6 | 0.00 | 0.00 | 672.00 | 0.00 | -110395258.1 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.231398E+09 | -107949914.0 | 0.00 | 0.00 | 744.00 | 0.00 | -99446759.2 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK6
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.229869E+09 | -119485373.9 | 0.00 | 0.00 | 744.00 | 0.00 | -110383437.3 | 58.99 | 0.00 | 0.00 |
February | 0.207513E+09 | -107943455.3 | 0.00 | 0.00 | 672.00 | 0.00 | -99569344.1 | 58.99 | 0.00 | 0.00 |
March | 0.231525E+09 | -121325480.5 | 0.00 | 0.00 | 744.00 | 0.00 | -110199275.3 | 58.99 | 0.00 | 0.00 |
April | 0.217990E+09 | -111748546.8 | 0.00 | 0.00 | 720.00 | 0.00 | -106241150.1 | 58.99 | 0.00 | 0.00 |
May | 0.223663E+09 | -113985845.5 | 0.00 | 0.00 | 744.00 | 0.00 | -109677057.1 | 58.99 | 0.00 | 0.00 |
June | 0.216432E+09 | -110297129.5 | 0.00 | 0.00 | 720.00 | 0.00 | -106135258.6 | 58.98 | 0.00 | 0.00 |
July | 0.218768E+09 | -108946131.0 | 0.00 | 0.00 | 744.00 | 0.00 | -109821958.2 | 58.98 | 0.00 | 0.00 |
August | 0.224756E+09 | -114513923.0 | 0.00 | 0.00 | 744.00 | 0.00 | -110241903.9 | 58.98 | 0.00 | 0.00 |
September | 0.216151E+09 | -109684632.1 | 0.00 | 0.00 | 720.00 | 0.00 | -106466706.7 | 58.99 | 0.00 | 0.00 |
October | 0.224965E+09 | -114747287.4 | 0.00 | 0.00 | 744.00 | 0.00 | -110218205.7 | 58.99 | 0.00 | 0.00 |
November | 0.220336E+09 | -113507209.3 | 0.00 | 0.00 | 720.00 | 0.00 | -106829185.9 | 58.99 | 0.00 | 0.00 |
December | 0.228856E+09 | -118337165.6 | 0.00 | 0.00 | 744.00 | 0.00 | -110518700.0 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.266082E+10 | -0.136452E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.129630E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.207513E+09 | -121325480.5 | 0.00 | 0.00 | 672.00 | 0.00 | -110518700.0 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.231525E+09 | -107943455.3 | 0.00 | 0.00 | 744.00 | 0.00 | -99569344.1 | 58.99 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK7
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.229902E+09 | -119488217.0 | 0.00 | 0.00 | 744.00 | 0.00 | -110413404.5 | 58.99 | 0.00 | 0.00 |
February | 0.207539E+09 | -107940055.7 | 0.00 | 0.00 | 672.00 | 0.00 | -99598855.7 | 58.99 | 0.00 | 0.00 |
March | 0.231553E+09 | -121331825.6 | 0.00 | 0.00 | 744.00 | 0.00 | -110221642.4 | 58.99 | 0.00 | 0.00 |
April | 0.218013E+09 | -111746002.2 | 0.00 | 0.00 | 720.00 | 0.00 | -106267368.1 | 58.99 | 0.00 | 0.00 |
May | 0.223689E+09 | -113988181.0 | 0.00 | 0.00 | 744.00 | 0.00 | -109701238.4 | 58.99 | 0.00 | 0.00 |
June | 0.216455E+09 | -110317132.6 | 0.00 | 0.00 | 720.00 | 0.00 | -106138117.0 | 58.97 | 0.00 | 0.00 |
July | 0.218798E+09 | -108976847.4 | 0.00 | 0.00 | 744.00 | 0.00 | -109820754.3 | 58.97 | 0.00 | 0.00 |
August | 0.224792E+09 | -114536309.7 | 0.00 | 0.00 | 744.00 | 0.00 | -110255512.9 | 58.98 | 0.00 | 0.00 |
September | 0.216179E+09 | -109683952.2 | 0.00 | 0.00 | 720.00 | 0.00 | -106495201.5 | 58.99 | 0.00 | 0.00 |
October | 0.224988E+09 | -114773891.7 | 0.00 | 0.00 | 744.00 | 0.00 | -110214386.2 | 58.98 | 0.00 | 0.00 |
November | 0.220366E+09 | -113498425.6 | 0.00 | 0.00 | 720.00 | 0.00 | -106867314.3 | 58.99 | 0.00 | 0.00 |
December | 0.228893E+09 | -118319832.9 | 0.00 | 0.00 | 744.00 | 0.00 | -110572671.6 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.266117E+10 | -0.136460E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.129657E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.207539E+09 | -121331825.6 | 0.00 | 0.00 | 672.00 | 0.00 | -110572671.6 | 58.97 | 0.00 | 0.00 |
Maximum of Months | 0.231553E+09 | -107940055.7 | 0.00 | 0.00 | 744.00 | 0.00 | -99598855.7 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 350.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 361.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 358.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 376.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 370.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 383.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 369.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 357.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 356.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 337.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 349.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4292.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 383.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 HEATING COIL
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 HEATING COIL
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3 HEATING COIL
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4 HEATING COIL
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5 HEATING COIL
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6 HEATING COIL
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7 HEATING COIL
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8 HEATING COIL
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9 HEATING COIL
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10 HEATING COIL
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.411229E+11 | 0.255599E+11 | 63156.71 | 10-JAN-08:62 | 33503.66 | 0.00 |
February | 0.00 | 0.00 | 0.400731E+11 | 0.249513E+11 | 62929.28 | 16-FEB-08:62 | 34433.16 | 0.00 |
March | 0.00 | 0.00 | 0.467135E+11 | 0.287043E+11 | 63860.08 | 28-MAR-07:01 | 32673.30 | 0.00 |
April | 0.00 | 0.00 | 0.515091E+11 | 0.286917E+11 | 64065.95 | 12-APR-07:01 | 32346.67 | 0.00 |
May | 0.00 | 0.00 | 0.577295E+11 | 0.295576E+11 | 65134.89 | 19-MAY-07:02 | 26985.79 | 0.00 |
June | 0.00 | 0.00 | 0.575725E+11 | 0.293509E+11 | 65146.80 | 17-JUN-07:01 | 29764.10 | 0.00 |
July | 0.00 | 0.00 | 0.467933E+11 | 0.259626E+11 | 63747.77 | 01-JUL-07:02 | 31676.03 | 0.00 |
August | 0.00 | 0.00 | 0.526800E+11 | 0.258054E+11 | 65203.80 | 11-AUG-07:02 | 28650.03 | 0.00 |
September | 0.00 | 0.00 | 0.502492E+11 | 0.254334E+11 | 64474.85 | 01-SEP-07:02 | 30489.27 | 0.00 |
October | 0.00 | 0.00 | 0.481045E+11 | 0.243242E+11 | 64014.91 | 14-OCT-07:02 | 30408.97 | 0.00 |
November | 0.00 | 0.00 | 0.442122E+11 | 0.238752E+11 | 63637.30 | 12-NOV-08:62 | 32460.72 | 0.00 |
December | 0.00 | 0.00 | 0.418616E+11 | 0.246082E+11 | 63031.48 | 30-DEC-08:62 | 34519.78 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.578621E+12 | 0.316825E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.400731E+11 | 0.238752E+11 | 62929.28 | 26985.79 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.577295E+11 | 0.295576E+11 | 65203.80 | 34519.78 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.202315E+11 | 0.129293E+11 | 31049.67 | 10-JAN-08:62 | 20214.18 | 0.00 |
February | 0.00 | 0.00 | 0.195412E+11 | 0.124568E+11 | 30971.20 | 16-FEB-08:62 | 20490.45 | 0.00 |
March | 0.00 | 0.00 | 0.225678E+11 | 0.141950E+11 | 31381.34 | 28-MAR-07:01 | 19597.59 | 0.00 |
April | 0.00 | 0.00 | 0.246943E+11 | 0.141223E+11 | 31497.88 | 12-APR-07:01 | 19351.36 | 0.00 |
May | 0.00 | 0.00 | 0.278623E+11 | 0.147040E+11 | 32234.37 | 22-MAY-07:02 | 17235.34 | 0.00 |
June | 0.00 | 0.00 | 0.277901E+11 | 0.145694E+11 | 32260.82 | 14-JUN-07:01 | 17595.13 | 0.00 |
July | 0.00 | 0.00 | 0.227094E+11 | 0.129544E+11 | 31111.44 | 01-JUL-07:02 | 19926.32 | 0.00 |
August | 0.00 | 0.00 | 0.256086E+11 | 0.129425E+11 | 31944.44 | 13-AUG-07:01 | 18180.43 | 0.00 |
September | 0.00 | 0.00 | 0.243412E+11 | 0.127101E+11 | 31386.18 | 03-SEP-07:01 | 19699.05 | 0.00 |
October | 0.00 | 0.00 | 0.235649E+11 | 0.123358E+11 | 31311.26 | 05-OCT-07:02 | 19661.97 | 0.00 |
November | 0.00 | 0.00 | 0.216693E+11 | 0.120990E+11 | 31016.00 | 12-NOV-08:62 | 20401.51 | 0.00 |
December | 0.00 | 0.00 | 0.206075E+11 | 0.125357E+11 | 30816.90 | 10-DEC-08:61 | 21144.39 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.281188E+12 | 0.158554E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.195412E+11 | 0.120990E+11 | 30816.90 | 17235.34 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.278623E+11 | 0.147040E+11 | 32260.82 | 21144.39 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3 COOLING COIL
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.165134E+11 | 0.103335E+11 | 33061.04 | 02-JAN-07:02 | 14455.52 | 0.00 |
February | 0.00 | 0.00 | 0.160944E+11 | 0.100462E+11 | 32745.91 | 06-FEB-07:02 | 15531.29 | 0.00 |
March | 0.00 | 0.00 | 0.189103E+11 | 0.116447E+11 | 33297.62 | 27-MAR-06:01 | 14725.18 | 0.00 |
April | 0.00 | 0.00 | 0.205170E+11 | 0.113899E+11 | 33309.94 | 10-APR-06:02 | 13912.04 | 0.00 |
May | 0.00 | 0.00 | 0.235098E+11 | 0.119610E+11 | 33366.76 | 17-MAY-06:02 | 13178.54 | 0.00 |
June | 0.00 | 0.00 | 0.236262E+11 | 0.119338E+11 | 33363.09 | 26-JUN-06:03 | 12177.92 | 0.00 |
July | 0.00 | 0.00 | 0.186288E+11 | 0.101867E+11 | 33315.38 | 02-JUL-07:01 | 14478.30 | 0.00 |
August | 0.00 | 0.00 | 0.216940E+11 | 0.104721E+11 | 33364.95 | 21-AUG-06:02 | 12446.24 | 0.00 |
September | 0.00 | 0.00 | 0.202955E+11 | 0.101271E+11 | 33365.49 | 18-SEP-06:02 | 12500.26 | 0.00 |
October | 0.00 | 0.00 | 0.195546E+11 | 0.977521E+10 | 33366.32 | 02-OCT-06:02 | 13577.71 | 0.00 |
November | 0.00 | 0.00 | 0.179137E+11 | 0.968149E+10 | 33345.86 | 20-NOV-07:01 | 14065.32 | 0.00 |
December | 0.00 | 0.00 | 0.167417E+11 | 0.996118E+10 | 33360.34 | 11-DEC-07:02 | 12657.08 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.233999E+12 | 0.127513E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.160944E+11 | 0.968149E+10 | 32745.91 | 12177.92 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.236262E+11 | 0.119610E+11 | 33366.76 | 15531.29 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4 COOLING COIL
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.165575E+11 | 0.103662E+11 | 33157.62 | 02-JAN-07:02 | 14536.01 | 0.00 |
February | 0.00 | 0.00 | 0.161385E+11 | 0.100795E+11 | 32844.40 | 06-FEB-07:02 | 15628.85 | 0.00 |
March | 0.00 | 0.00 | 0.189613E+11 | 0.116826E+11 | 33403.48 | 27-MAR-06:01 | 14858.72 | 0.00 |
April | 0.00 | 0.00 | 0.205803E+11 | 0.114349E+11 | 33406.96 | 10-APR-06:02 | 13992.68 | 0.00 |
May | 0.00 | 0.00 | 0.235935E+11 | 0.120194E+11 | 33458.60 | 17-MAY-06:02 | 13255.52 | 0.00 |
June | 0.00 | 0.00 | 0.237060E+11 | 0.119900E+11 | 33454.91 | 26-JUN-06:02 | 12315.02 | 0.00 |
July | 0.00 | 0.00 | 0.186977E+11 | 0.102347E+11 | 33407.07 | 02-JUL-07:01 | 14560.96 | 0.00 |
August | 0.00 | 0.00 | 0.217376E+11 | 0.105026E+11 | 33456.78 | 21-AUG-06:02 | 12482.21 | 0.00 |
September | 0.00 | 0.00 | 0.203485E+11 | 0.101639E+11 | 33457.33 | 18-SEP-06:02 | 12564.41 | 0.00 |
October | 0.00 | 0.00 | 0.195996E+11 | 0.980631E+10 | 33458.15 | 02-OCT-06:02 | 13671.01 | 0.00 |
November | 0.00 | 0.00 | 0.179419E+11 | 0.970246E+10 | 33447.37 | 20-NOV-07:01 | 14167.55 | 0.00 |
December | 0.00 | 0.00 | 0.167697E+11 | 0.998197E+10 | 33452.16 | 11-DEC-07:02 | 12750.63 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.234632E+12 | 0.127965E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.161385E+11 | 0.970246E+10 | 32844.40 | 12315.02 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.237060E+11 | 0.120194E+11 | 33458.60 | 15628.85 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5 COOLING COIL
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.163373E+11 | 0.102023E+11 | 32870.77 | 02-JAN-07:02 | 14318.37 | 0.00 |
February | 0.00 | 0.00 | 0.159396E+11 | 0.993043E+10 | 32559.81 | 06-FEB-07:02 | 15407.20 | 0.00 |
March | 0.00 | 0.00 | 0.187279E+11 | 0.115095E+11 | 33114.77 | 27-MAR-06:01 | 14649.60 | 0.00 |
April | 0.00 | 0.00 | 0.203414E+11 | 0.112660E+11 | 33118.60 | 10-APR-06:02 | 13776.81 | 0.00 |
May | 0.00 | 0.00 | 0.233547E+11 | 0.118557E+11 | 33179.38 | 17-MAY-06:02 | 13009.21 | 0.00 |
June | 0.00 | 0.00 | 0.234716E+11 | 0.118276E+11 | 33175.72 | 26-JUN-06:02 | 12124.65 | 0.00 |
July | 0.00 | 0.00 | 0.184646E+11 | 0.100714E+11 | 33128.28 | 02-JUL-07:01 | 14316.36 | 0.00 |
August | 0.00 | 0.00 | 0.214702E+11 | 0.103250E+11 | 33177.57 | 21-AUG-06:02 | 12254.94 | 0.00 |
September | 0.00 | 0.00 | 0.201011E+11 | 0.999731E+10 | 33178.12 | 18-SEP-06:03 | 12300.07 | 0.00 |
October | 0.00 | 0.00 | 0.193461E+11 | 0.963627E+10 | 33178.94 | 02-OCT-06:02 | 13468.62 | 0.00 |
November | 0.00 | 0.00 | 0.177040E+11 | 0.953716E+10 | 33158.19 | 20-NOV-07:01 | 13959.20 | 0.00 |
December | 0.00 | 0.00 | 0.165374E+11 | 0.981346E+10 | 33173.00 | 11-DEC-07:02 | 12559.41 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.231796E+12 | 0.125972E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.159396E+11 | 0.953716E+10 | 32559.81 | 12124.65 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.234716E+11 | 0.118557E+11 | 33179.38 | 15407.20 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6 COOLING COIL
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.295046E+11 | 0.181579E+11 | 57669.14 | 02-JAN-08:62 | 25227.27 | 0.00 |
February | 0.00 | 0.00 | 0.288493E+11 | 0.177164E+11 | 57109.37 | 06-FEB-08:62 | 27416.57 | 0.00 |
March | 0.00 | 0.00 | 0.338357E+11 | 0.205247E+11 | 57987.27 | 27-MAR-07:01 | 25757.15 | 0.00 |
April | 0.00 | 0.00 | 0.367891E+11 | 0.200608E+11 | 58019.63 | 10-APR-07:02 | 23951.21 | 0.00 |
May | 0.00 | 0.00 | 0.423693E+11 | 0.211312E+11 | 57987.27 | 15-MAY-07:06 | 21282.42 | 0.00 |
June | 0.00 | 0.00 | 0.428195E+11 | 0.211993E+11 | 58049.03 | 26-JUN-07:03 | 21130.69 | 0.00 |
July | 0.00 | 0.00 | 0.331563E+11 | 0.177510E+11 | 58009.59 | 05-JUL-07:01 | 25223.78 | 0.00 |
August | 0.00 | 0.00 | 0.388935E+11 | 0.182618E+11 | 58114.70 | 21-AUG-07:04 | 21066.52 | 0.00 |
September | 0.00 | 0.00 | 0.362760E+11 | 0.176580E+11 | 58180.57 | 18-SEP-07:02 | 21441.17 | 0.00 |
October | 0.00 | 0.00 | 0.348218E+11 | 0.169358E+11 | 58179.79 | 23-OCT-07:02 | 22540.40 | 0.00 |
November | 0.00 | 0.00 | 0.318844E+11 | 0.167983E+11 | 58075.49 | 20-NOV-08:61 | 25124.80 | 0.00 |
December | 0.00 | 0.00 | 0.296989E+11 | 0.173234E+11 | 58087.62 | 11-DEC-08:03 | 22291.32 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.418898E+12 | 0.223518E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.288493E+11 | 0.167983E+11 | 57109.37 | 21066.52 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.428195E+11 | 0.211993E+11 | 58180.57 | 27416.57 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7 COOLING COIL
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.153289E+11 | 0.944456E+10 | 30360.02 | 02-JAN-08:62 | 13227.43 | 0.00 |
February | 0.00 | 0.00 | 0.149984E+11 | 0.921760E+10 | 30058.63 | 06-FEB-08:62 | 14369.46 | 0.00 |
March | 0.00 | 0.00 | 0.175814E+11 | 0.106739E+11 | 30500.07 | 27-MAR-07:01 | 13515.44 | 0.00 |
April | 0.00 | 0.00 | 0.191159E+11 | 0.104372E+11 | 30517.09 | 10-APR-07:02 | 12528.55 | 0.00 |
May | 0.00 | 0.00 | 0.220032E+11 | 0.109934E+11 | 30500.07 | 15-MAY-07:03 | 11240.20 | 0.00 |
June | 0.00 | 0.00 | 0.222163E+11 | 0.110143E+11 | 30532.56 | 26-JUN-07:03 | 11035.98 | 0.00 |
July | 0.00 | 0.00 | 0.172085E+11 | 0.922704E+10 | 30545.87 | 05-JUL-07:01 | 13182.62 | 0.00 |
August | 0.00 | 0.00 | 0.201660E+11 | 0.948741E+10 | 30567.09 | 21-AUG-07:02 | 11053.29 | 0.00 |
September | 0.00 | 0.00 | 0.188247E+11 | 0.917930E+10 | 30601.74 | 18-SEP-07:02 | 11173.94 | 0.00 |
October | 0.00 | 0.00 | 0.180672E+11 | 0.880306E+10 | 30601.33 | 23-OCT-07:02 | 11834.81 | 0.00 |
November | 0.00 | 0.00 | 0.165398E+11 | 0.872791E+10 | 30546.47 | 20-NOV-08:61 | 13068.37 | 0.00 |
December | 0.00 | 0.00 | 0.154174E+11 | 0.900421E+10 | 30552.85 | 11-DEC-08:03 | 11594.27 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.217468E+12 | 0.116210E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.149984E+11 | 0.872791E+10 | 30058.63 | 11035.98 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.222163E+11 | 0.110143E+11 | 30601.74 | 14369.46 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8 COOLING COIL
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.152654E+11 | 0.939841E+10 | 30240.08 | 02-JAN-08:62 | 13159.66 | 0.00 |
February | 0.00 | 0.00 | 0.149453E+11 | 0.917880E+10 | 29939.98 | 06-FEB-08:62 | 14299.43 | 0.00 |
March | 0.00 | 0.00 | 0.175243E+11 | 0.106326E+11 | 30380.53 | 27-MAR-07:01 | 13454.81 | 0.00 |
April | 0.00 | 0.00 | 0.190640E+11 | 0.104010E+11 | 30397.48 | 10-APR-07:02 | 12464.87 | 0.00 |
May | 0.00 | 0.00 | 0.219475E+11 | 0.109557E+11 | 30380.53 | 15-MAY-07:03 | 11189.20 | 0.00 |
June | 0.00 | 0.00 | 0.221597E+11 | 0.109757E+11 | 30412.89 | 26-JUN-07:02 | 11012.87 | 0.00 |
July | 0.00 | 0.00 | 0.171541E+11 | 0.918967E+10 | 30425.81 | 05-JUL-07:01 | 13118.26 | 0.00 |
August | 0.00 | 0.00 | 0.201063E+11 | 0.944842E+10 | 30447.29 | 21-AUG-07:02 | 10986.31 | 0.00 |
September | 0.00 | 0.00 | 0.187700E+11 | 0.914304E+10 | 30481.80 | 18-SEP-07:02 | 11115.47 | 0.00 |
October | 0.00 | 0.00 | 0.180042E+11 | 0.876166E+10 | 30481.40 | 23-OCT-07:02 | 11770.12 | 0.00 |
November | 0.00 | 0.00 | 0.164756E+11 | 0.868423E+10 | 30426.75 | 20-NOV-08:61 | 13001.66 | 0.00 |
December | 0.00 | 0.00 | 0.153513E+11 | 0.895739E+10 | 30433.10 | 11-DEC-08:03 | 11533.96 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.216768E+12 | 0.115727E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.149453E+11 | 0.868423E+10 | 29939.98 | 10986.31 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.221597E+11 | 0.109757E+11 | 30481.80 | 14299.43 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9 COOLING COIL
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.152909E+11 | 0.941790E+10 | 30369.38 | 02-JAN-08:62 | 13170.10 | 0.00 |
February | 0.00 | 0.00 | 0.150023E+11 | 0.922147E+10 | 30070.58 | 06-FEB-08:62 | 14338.92 | 0.00 |
March | 0.00 | 0.00 | 0.176023E+11 | 0.106912E+11 | 30519.59 | 27-MAR-07:01 | 13512.35 | 0.00 |
April | 0.00 | 0.00 | 0.191723E+11 | 0.104793E+11 | 30536.62 | 10-APR-07:02 | 12494.10 | 0.00 |
May | 0.00 | 0.00 | 0.220545E+11 | 0.110323E+11 | 30519.59 | 15-MAY-07:04 | 11186.18 | 0.00 |
June | 0.00 | 0.00 | 0.222826E+11 | 0.110625E+11 | 30552.10 | 26-JUN-07:02 | 11045.52 | 0.00 |
July | 0.00 | 0.00 | 0.172373E+11 | 0.924795E+10 | 30561.03 | 05-JUL-07:01 | 13168.52 | 0.00 |
August | 0.00 | 0.00 | 0.201809E+11 | 0.950135E+10 | 30586.66 | 21-AUG-07:02 | 10967.06 | 0.00 |
September | 0.00 | 0.00 | 0.188533E+11 | 0.920176E+10 | 30621.32 | 18-SEP-07:02 | 11133.97 | 0.00 |
October | 0.00 | 0.00 | 0.180330E+11 | 0.878368E+10 | 30620.92 | 23-OCT-07:02 | 11769.00 | 0.00 |
November | 0.00 | 0.00 | 0.165010E+11 | 0.870374E+10 | 30566.02 | 20-NOV-08:61 | 13027.20 | 0.00 |
December | 0.00 | 0.00 | 0.153631E+11 | 0.896707E+10 | 30572.40 | 11-DEC-08:62 | 11591.13 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.217573E+12 | 0.116310E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.150023E+11 | 0.870374E+10 | 30070.58 | 10967.06 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.222826E+11 | 0.110625E+11 | 30621.32 | 14338.92 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10 COOLING COIL
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.173205E+11 | 0.108979E+11 | 35736.40 | 09-JAN-08:62 | 15343.59 | 0.00 |
February | 0.00 | 0.00 | 0.171542E+11 | 0.108029E+11 | 35389.23 | 20-FEB-09:01 | 18082.84 | 0.00 |
March | 0.00 | 0.00 | 0.202790E+11 | 0.126137E+11 | 35743.26 | 27-MAR-07:03 | 14976.42 | 0.00 |
April | 0.00 | 0.00 | 0.220435E+11 | 0.124662E+11 | 35812.13 | 24-APR-07:01 | 15070.51 | 0.00 |
May | 0.00 | 0.00 | 0.249419E+11 | 0.129541E+11 | 35810.11 | 17-MAY-07:02 | 14614.51 | 0.00 |
June | 0.00 | 0.00 | 0.253420E+11 | 0.131075E+11 | 35781.33 | 26-JUN-07:03 | 13341.34 | 0.00 |
July | 0.00 | 0.00 | 0.197003E+11 | 0.109430E+11 | 35821.81 | 05-JUL-07:01 | 15343.06 | 0.00 |
August | 0.00 | 0.00 | 0.228468E+11 | 0.112295E+11 | 35821.81 | 21-AUG-07:02 | 12822.70 | 0.00 |
September | 0.00 | 0.00 | 0.214129E+11 | 0.109108E+11 | 35862.41 | 18-SEP-07:02 | 13114.86 | 0.00 |
October | 0.00 | 0.00 | 0.201115E+11 | 0.101630E+11 | 35861.93 | 23-OCT-07:02 | 13693.53 | 0.00 |
November | 0.00 | 0.00 | 0.185285E+11 | 0.100965E+11 | 35833.12 | 05-NOV-08:61 | 15149.67 | 0.00 |
December | 0.00 | 0.00 | 0.173123E+11 | 0.103625E+11 | 35805.11 | 11-DEC-08:62 | 13705.28 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.246993E+12 | 0.136548E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.171542E+11 | 0.100965E+11 | 35389.23 | 12822.70 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.253420E+11 | 0.131075E+11 | 35862.41 | 18082.84 | 0.00 |
Report: FanReportMonthly
For: PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.183481E+10 | 0.36 | 2444.19 | 01-JAN-08:62 | 0.86 |
February | 0.173226E+10 | 0.37 | 2444.19 | 01-FEB-08:62 | 0.87 |
March | 0.195451E+10 | 0.38 | 2444.19 | 01-MAR-08:62 | 0.86 |
April | 0.198886E+10 | 0.39 | 2444.19 | 01-APR-07:02 | 0.86 |
May | 0.214929E+10 | 0.39 | 2444.19 | 01-MAY-07:01 | 0.86 |
June | 0.214689E+10 | 0.40 | 2444.19 | 01-JUN-07:02 | 0.86 |
July | 0.190554E+10 | 0.37 | 2444.19 | 01-JUL-07:02 | 0.86 |
August | 0.203113E+10 | 0.38 | 2444.19 | 01-AUG-07:02 | 0.86 |
September | 0.195274E+10 | 0.38 | 2444.19 | 01-SEP-07:02 | 0.86 |
October | 0.193562E+10 | 0.37 | 2444.19 | 01-OCT-07:01 | 0.86 |
November | 0.182996E+10 | 0.37 | 2444.19 | 01-NOV-07:02 | 0.86 |
December | 0.184358E+10 | 0.36 | 2444.19 | 01-DEC-08:62 | 0.86 |
Annual Sum or Average | 0.233052E+11 | 0.38 | |||
Minimum of Months | 0.173226E+10 | 0.36 | 2444.19 | 0.86 | |
Maximum of Months | 0.214929E+10 | 0.40 | 2444.19 | 0.87 |
Report: FanReportMonthly
For: PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.857308E+09 | 0.39 | 1287.13 | 01-JAN-08:62 | 0.90 |
February | 0.814117E+09 | 0.40 | 1287.13 | 01-FEB-08:62 | 0.90 |
March | 0.925399E+09 | 0.40 | 1287.13 | 01-MAR-08:62 | 0.90 |
April | 0.957837E+09 | 0.41 | 1287.13 | 01-APR-07:02 | 0.89 |
May | 0.104958E+10 | 0.42 | 1287.13 | 01-MAY-07:01 | 0.89 |
June | 0.104676E+10 | 0.42 | 1287.13 | 01-JUN-07:02 | 0.89 |
July | 0.907457E+09 | 0.40 | 1287.13 | 01-JUL-07:02 | 0.90 |
August | 0.977972E+09 | 0.41 | 1287.13 | 01-AUG-07:02 | 0.89 |
September | 0.937671E+09 | 0.41 | 1287.13 | 01-SEP-07:02 | 0.89 |
October | 0.922779E+09 | 0.40 | 1287.13 | 01-OCT-07:01 | 0.90 |
November | 0.866644E+09 | 0.39 | 1287.13 | 01-NOV-07:02 | 0.90 |
December | 0.859511E+09 | 0.39 | 1287.13 | 01-DEC-08:62 | 0.90 |
Annual Sum or Average | 0.111230E+11 | 0.40 | |||
Minimum of Months | 0.814117E+09 | 0.39 | 1287.13 | 0.89 | |
Maximum of Months | 0.104958E+10 | 0.42 | 1287.13 | 0.90 |
Report: FanReportMonthly
For: PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.774257E+09 | 0.30 | 1288.73 | 01-JAN-08:62 | 0.89 |
February | 0.734283E+09 | 0.31 | 1288.73 | 01-FEB-07:02 | 0.89 |
March | 0.841366E+09 | 0.32 | 1288.73 | 01-MAR-07:01 | 0.89 |
April | 0.853916E+09 | 0.32 | 1288.73 | 01-APR-06:01 | 0.89 |
May | 0.939378E+09 | 0.33 | 1288.73 | 01-MAY-06:01 | 0.88 |
June | 0.942530E+09 | 0.34 | 1288.73 | 01-JUN-06:02 | 0.89 |
July | 0.807293E+09 | 0.31 | 1288.73 | 01-JUL-06:02 | 0.89 |
August | 0.886538E+09 | 0.32 | 1288.73 | 01-AUG-06:02 | 0.89 |
September | 0.838390E+09 | 0.32 | 1288.73 | 01-SEP-06:02 | 0.89 |
October | 0.827208E+09 | 0.31 | 1288.73 | 01-OCT-07:01 | 0.89 |
November | 0.779123E+09 | 0.31 | 1288.73 | 01-NOV-06:02 | 0.89 |
December | 0.772008E+09 | 0.30 | 1288.73 | 01-DEC-07:02 | 0.89 |
Annual Sum or Average | 0.999629E+10 | 0.32 | |||
Minimum of Months | 0.734283E+09 | 0.30 | 1288.73 | 0.88 | |
Maximum of Months | 0.942530E+09 | 0.34 | 1288.73 | 0.89 |
Report: FanReportMonthly
For: PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.776022E+09 | 0.30 | 1292.27 | 01-JAN-08:62 | 0.89 |
February | 0.735864E+09 | 0.31 | 1292.27 | 01-FEB-07:02 | 0.89 |
March | 0.843250E+09 | 0.32 | 1292.27 | 01-MAR-07:01 | 0.89 |
April | 0.855989E+09 | 0.32 | 1292.27 | 01-APR-06:01 | 0.89 |
May | 0.942291E+09 | 0.33 | 1292.27 | 01-MAY-06:01 | 0.88 |
June | 0.945461E+09 | 0.34 | 1292.27 | 01-JUN-06:02 | 0.89 |
July | 0.809450E+09 | 0.31 | 1292.27 | 01-JUL-06:02 | 0.89 |
August | 0.888306E+09 | 0.32 | 1292.27 | 01-AUG-06:02 | 0.89 |
September | 0.840303E+09 | 0.32 | 1292.27 | 01-SEP-06:02 | 0.89 |
October | 0.828880E+09 | 0.31 | 1292.27 | 01-OCT-07:01 | 0.89 |
November | 0.780591E+09 | 0.31 | 1292.27 | 01-NOV-06:02 | 0.89 |
December | 0.773731E+09 | 0.30 | 1292.27 | 01-DEC-07:02 | 0.89 |
Annual Sum or Average | 0.100201E+11 | 0.32 | |||
Minimum of Months | 0.735864E+09 | 0.30 | 1292.27 | 0.88 | |
Maximum of Months | 0.945461E+09 | 0.34 | 1292.27 | 0.89 |
Report: FanReportMonthly
For: PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.768681E+09 | 0.30 | 1281.49 | 01-JAN-08:62 | 0.89 |
February | 0.728690E+09 | 0.31 | 1281.49 | 01-FEB-07:02 | 0.89 |
March | 0.835081E+09 | 0.32 | 1281.49 | 01-MAR-07:01 | 0.89 |
April | 0.847472E+09 | 0.32 | 1281.49 | 01-APR-06:01 | 0.89 |
May | 0.933348E+09 | 0.33 | 1281.49 | 01-MAY-06:01 | 0.88 |
June | 0.936543E+09 | 0.34 | 1281.49 | 01-JUN-06:02 | 0.89 |
July | 0.801406E+09 | 0.31 | 1281.49 | 01-JUL-06:02 | 0.89 |
August | 0.879494E+09 | 0.32 | 1281.49 | 01-AUG-06:02 | 0.89 |
September | 0.832003E+09 | 0.32 | 1281.49 | 01-SEP-06:02 | 0.89 |
October | 0.820559E+09 | 0.31 | 1281.49 | 01-OCT-07:01 | 0.89 |
November | 0.772730E+09 | 0.31 | 1281.49 | 01-NOV-06:02 | 0.89 |
December | 0.766405E+09 | 0.30 | 1281.49 | 01-DEC-07:02 | 0.89 |
Annual Sum or Average | 0.992241E+10 | 0.32 | |||
Minimum of Months | 0.728690E+09 | 0.30 | 1281.49 | 0.88 | |
Maximum of Months | 0.936543E+09 | 0.34 | 1281.49 | 0.89 |
Report: FanReportMonthly
For: PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.124293E+10 | 0.27 | 2171.67 | 01-JAN-09:02 | 0.86 |
February | 0.119579E+10 | 0.28 | 2171.67 | 01-FEB-08:62 | 0.87 |
March | 0.137276E+10 | 0.29 | 2171.67 | 01-MAR-08:62 | 0.86 |
April | 0.140539E+10 | 0.30 | 2171.67 | 01-APR-07:02 | 0.86 |
May | 0.157024E+10 | 0.31 | 2171.67 | 01-MAY-07:01 | 0.85 |
June | 0.158366E+10 | 0.32 | 2171.67 | 01-JUN-07:02 | 0.86 |
July | 0.131358E+10 | 0.28 | 2171.67 | 01-JUL-07:02 | 0.86 |
August | 0.145856E+10 | 0.30 | 2171.67 | 01-AUG-07:02 | 0.86 |
September | 0.137811E+10 | 0.29 | 2171.67 | 01-SEP-07:02 | 0.86 |
October | 0.134831E+10 | 0.28 | 2171.67 | 01-OCT-08:61 | 0.86 |
November | 0.126130E+10 | 0.28 | 2171.67 | 01-NOV-07:02 | 0.86 |
December | 0.123538E+10 | 0.27 | 2171.67 | 01-DEC-08:62 | 0.86 |
Annual Sum or Average | 0.163660E+11 | 0.29 | |||
Minimum of Months | 0.119579E+10 | 0.27 | 2171.67 | 0.85 | |
Maximum of Months | 0.158366E+10 | 0.32 | 2171.67 | 0.87 |
Report: FanReportMonthly
For: PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.674591E+09 | 0.28 | 1181.87 | 01-JAN-09:02 | 0.89 |
February | 0.648877E+09 | 0.29 | 1181.87 | 01-FEB-08:62 | 0.90 |
March | 0.745105E+09 | 0.30 | 1181.87 | 01-MAR-08:62 | 0.89 |
April | 0.762298E+09 | 0.31 | 1181.87 | 01-APR-07:02 | 0.89 |
May | 0.849133E+09 | 0.32 | 1181.87 | 01-MAY-07:01 | 0.88 |
June | 0.854695E+09 | 0.33 | 1181.87 | 01-JUN-07:02 | 0.89 |
July | 0.711863E+09 | 0.29 | 1181.87 | 01-JUL-07:02 | 0.89 |
August | 0.789004E+09 | 0.31 | 1181.87 | 01-AUG-07:02 | 0.89 |
September | 0.746165E+09 | 0.30 | 1181.87 | 01-SEP-07:02 | 0.89 |
October | 0.730387E+09 | 0.29 | 1181.87 | 01-OCT-08:61 | 0.89 |
November | 0.683737E+09 | 0.29 | 1181.87 | 01-NOV-07:02 | 0.89 |
December | 0.670312E+09 | 0.28 | 1181.87 | 01-DEC-08:62 | 0.89 |
Annual Sum or Average | 0.886617E+10 | 0.30 | |||
Minimum of Months | 0.648877E+09 | 0.28 | 1181.87 | 0.88 | |
Maximum of Months | 0.854695E+09 | 0.33 | 1181.87 | 0.90 |
Report: FanReportMonthly
For: PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.672114E+09 | 0.28 | 1177.23 | 01-JAN-09:02 | 0.89 |
February | 0.646712E+09 | 0.29 | 1177.23 | 01-FEB-08:62 | 0.90 |
March | 0.742745E+09 | 0.30 | 1177.23 | 01-MAR-08:62 | 0.89 |
April | 0.760141E+09 | 0.31 | 1177.23 | 01-APR-07:02 | 0.89 |
May | 0.846983E+09 | 0.32 | 1177.23 | 01-MAY-07:01 | 0.88 |
June | 0.852539E+09 | 0.33 | 1177.23 | 01-JUN-07:02 | 0.89 |
July | 0.709599E+09 | 0.29 | 1177.23 | 01-JUL-07:02 | 0.89 |
August | 0.786681E+09 | 0.31 | 1177.23 | 01-AUG-07:02 | 0.89 |
September | 0.743983E+09 | 0.30 | 1177.23 | 01-SEP-07:02 | 0.89 |
October | 0.727941E+09 | 0.29 | 1177.23 | 01-OCT-08:61 | 0.89 |
November | 0.681285E+09 | 0.29 | 1177.23 | 01-NOV-07:02 | 0.89 |
December | 0.667789E+09 | 0.28 | 1177.23 | 01-DEC-08:62 | 0.89 |
Annual Sum or Average | 0.883851E+10 | 0.30 | |||
Minimum of Months | 0.646712E+09 | 0.28 | 1177.23 | 0.88 | |
Maximum of Months | 0.852539E+09 | 0.33 | 1177.23 | 0.90 |
Report: FanReportMonthly
For: PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.674422E+09 | 0.28 | 1182.62 | 01-JAN-09:02 | 0.89 |
February | 0.649387E+09 | 0.29 | 1182.62 | 01-FEB-08:62 | 0.90 |
March | 0.746467E+09 | 0.30 | 1182.62 | 01-MAR-08:62 | 0.89 |
April | 0.764560E+09 | 0.31 | 1182.62 | 01-APR-07:02 | 0.89 |
May | 0.851912E+09 | 0.32 | 1182.62 | 01-MAY-07:01 | 0.88 |
June | 0.857957E+09 | 0.33 | 1182.62 | 01-JUN-07:02 | 0.89 |
July | 0.713220E+09 | 0.29 | 1182.62 | 01-JUL-07:02 | 0.89 |
August | 0.790570E+09 | 0.31 | 1182.62 | 01-AUG-07:02 | 0.89 |
September | 0.747877E+09 | 0.30 | 1182.62 | 01-SEP-07:02 | 0.89 |
October | 0.730441E+09 | 0.29 | 1182.62 | 01-OCT-08:61 | 0.89 |
November | 0.683530E+09 | 0.29 | 1182.62 | 01-NOV-07:02 | 0.89 |
December | 0.669923E+09 | 0.28 | 1182.62 | 01-DEC-08:62 | 0.89 |
Annual Sum or Average | 0.888026E+10 | 0.30 | |||
Minimum of Months | 0.649387E+09 | 0.28 | 1182.62 | 0.88 | |
Maximum of Months | 0.857957E+09 | 0.33 | 1182.62 | 0.90 |
Report: FanReportMonthly
For: PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.772744E+09 | 0.28 | 1385.04 | 01-JAN-09:02 | 0.89 |
February | 0.741282E+09 | 0.29 | 1385.04 | 01-FEB-08:62 | 0.90 |
March | 0.860589E+09 | 0.30 | 1385.04 | 01-MAR-08:62 | 0.89 |
April | 0.880790E+09 | 0.30 | 1385.04 | 01-APR-07:02 | 0.89 |
May | 0.974721E+09 | 0.32 | 1385.04 | 01-MAY-07:01 | 0.88 |
June | 0.983715E+09 | 0.32 | 1385.04 | 01-JUN-07:02 | 0.89 |
July | 0.820552E+09 | 0.29 | 1385.04 | 01-JUL-07:02 | 0.89 |
August | 0.906869E+09 | 0.30 | 1385.04 | 01-AUG-07:02 | 0.89 |
September | 0.857922E+09 | 0.30 | 1385.04 | 01-SEP-07:02 | 0.89 |
October | 0.831437E+09 | 0.29 | 1385.04 | 01-OCT-08:61 | 0.89 |
November | 0.778699E+09 | 0.28 | 1385.04 | 01-NOV-07:02 | 0.89 |
December | 0.768414E+09 | 0.28 | 1385.04 | 01-DEC-08:62 | 0.89 |
Annual Sum or Average | 0.101777E+11 | 0.30 | |||
Minimum of Months | 0.741282E+09 | 0.28 | 1385.04 | 0.88 | |
Maximum of Months | 0.983715E+09 | 0.32 | 1385.04 | 0.90 |
Report: ZoneTemperatureOscillationReportMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.120345E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.117413E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.136525E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.145933E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.159941E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.159186E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.131965E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.144333E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.138479E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.133045E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.124222E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.120737E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.163212E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.117413E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.159941E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.582103E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.564636E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.653386E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.696984E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.769629E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.765271E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.634157E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.695789E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.665707E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.643873E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.600721E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.584377E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.785663E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.564636E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.769629E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_3:3
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.478653E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.467343E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.549823E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.578537E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.647065E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.648759E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.519333E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.587703E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.553306E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.533401E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.497518E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.478500E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.653994E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.467343E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.648759E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_4:4
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.479943E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.468596E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.551300E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.580281E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.649389E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.651007E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.521163E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.588976E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.554783E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.534671E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.498412E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.479436E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.655796E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.468596E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.651007E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_5:5
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.473958E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.463040E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.544758E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.573590E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.642616E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.644326E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.514850E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.581809E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.548116E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.527925E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.492065E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.473265E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.648032E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.463040E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.644326E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_6:6
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.849148E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.833997E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.980286E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.103404E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.116452E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.117445E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.920118E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.104915E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.985228E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.944956E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.880257E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.842342E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.116585E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.833997E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.117445E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_7:7
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.438407E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.430792E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.506150E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.533905E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.600553E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.604929E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.474515E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.540507E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.507933E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.487196E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.453856E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.434659E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.601340E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.430792E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.604929E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_8:8
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.436577E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.429222E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.504430E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.532319E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.598882E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.603234E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.472922E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.538778E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.506336E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.485422E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.452040E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.432786E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.599295E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.429222E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.603234E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_9:9
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.437592E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.430993E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.506834E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.535501E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.602155E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.606927E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.475315E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.541099E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.508808E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.486532E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.453040E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.433479E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.601827E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.430993E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.606927E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_10:10
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.500106E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.495565E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.587586E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.620898E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.689559E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.698413E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.547975E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.620287E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.584509E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.550091E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.514447E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.493997E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.690343E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.493997E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.698413E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.183481E+10 | 0.411229E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.173226E+10 | 0.400731E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.195451E+10 | 0.467135E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.198886E+10 | 0.515091E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.214929E+10 | 0.577295E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.214689E+10 | 0.575725E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.190554E+10 | 0.467933E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.203113E+10 | 0.526800E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.195274E+10 | 0.502492E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.193562E+10 | 0.481045E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.182996E+10 | 0.442122E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.184358E+10 | 0.418616E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.233052E+11 | 0.578621E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.173226E+10 | 0.400731E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.214929E+10 | 0.577295E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.857308E+09 | 0.202315E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.814117E+09 | 0.195412E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.925399E+09 | 0.225678E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.957837E+09 | 0.246943E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.104958E+10 | 0.278623E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.104676E+10 | 0.277901E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.907457E+09 | 0.227094E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.977972E+09 | 0.256086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.937671E+09 | 0.243412E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.922779E+09 | 0.235649E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.866644E+09 | 0.216693E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.859511E+09 | 0.206075E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.111230E+11 | 0.281188E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.814117E+09 | 0.195412E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.104958E+10 | 0.278623E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_3:3
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.774257E+09 | 0.165134E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.734283E+09 | 0.160944E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.841366E+09 | 0.189103E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.853916E+09 | 0.205170E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.939378E+09 | 0.235098E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.942530E+09 | 0.236262E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.807293E+09 | 0.186288E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.886538E+09 | 0.216940E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.838390E+09 | 0.202955E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.827208E+09 | 0.195546E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.779123E+09 | 0.179137E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.772008E+09 | 0.167417E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.999629E+10 | 0.233999E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.734283E+09 | 0.160944E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.942530E+09 | 0.236262E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_4:4
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.776022E+09 | 0.165575E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.735864E+09 | 0.161385E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.843250E+09 | 0.189613E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.855989E+09 | 0.205803E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.942291E+09 | 0.235935E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.945461E+09 | 0.237060E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.809450E+09 | 0.186977E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.888306E+09 | 0.217376E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.840303E+09 | 0.203485E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.828880E+09 | 0.195996E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.780591E+09 | 0.179419E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.773731E+09 | 0.167697E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.100201E+11 | 0.234632E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.735864E+09 | 0.161385E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.945461E+09 | 0.237060E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_5:5
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.768681E+09 | 0.163373E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.728690E+09 | 0.159396E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.835081E+09 | 0.187279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.847472E+09 | 0.203414E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.933348E+09 | 0.233547E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.936543E+09 | 0.234716E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.801406E+09 | 0.184646E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.879494E+09 | 0.214702E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.832003E+09 | 0.201011E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.820559E+09 | 0.193461E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.772730E+09 | 0.177040E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.766405E+09 | 0.165374E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.992241E+10 | 0.231796E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.728690E+09 | 0.159396E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.936543E+09 | 0.234716E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_6:6
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.124293E+10 | 0.295046E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.119579E+10 | 0.288493E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.137276E+10 | 0.338357E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.140539E+10 | 0.367891E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.157024E+10 | 0.423693E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.158366E+10 | 0.428195E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.131358E+10 | 0.331563E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.145856E+10 | 0.388935E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.137811E+10 | 0.362760E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.134831E+10 | 0.348218E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.126130E+10 | 0.318844E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.123538E+10 | 0.296989E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.163660E+11 | 0.418898E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.119579E+10 | 0.288493E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.158366E+10 | 0.428195E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_7:7
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.674591E+09 | 0.153289E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.648877E+09 | 0.149984E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.745105E+09 | 0.175814E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.762298E+09 | 0.191159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.849133E+09 | 0.220032E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.854695E+09 | 0.222163E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.711863E+09 | 0.172085E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.789004E+09 | 0.201660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.746165E+09 | 0.188247E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.730387E+09 | 0.180672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.683737E+09 | 0.165398E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.670312E+09 | 0.154174E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.886617E+10 | 0.217468E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.648877E+09 | 0.149984E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.854695E+09 | 0.222163E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_8:8
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.672114E+09 | 0.152654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.646712E+09 | 0.149453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.742745E+09 | 0.175243E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.760141E+09 | 0.190640E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.846983E+09 | 0.219475E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.852539E+09 | 0.221597E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.709599E+09 | 0.171541E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.786681E+09 | 0.201063E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.743983E+09 | 0.187700E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.727941E+09 | 0.180042E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.681285E+09 | 0.164756E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.667789E+09 | 0.153513E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.883851E+10 | 0.216768E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.646712E+09 | 0.149453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.852539E+09 | 0.221597E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_9:9
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.674422E+09 | 0.152909E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.649387E+09 | 0.150023E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.746467E+09 | 0.176023E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.764560E+09 | 0.191723E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.851912E+09 | 0.220545E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.857957E+09 | 0.222826E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.713220E+09 | 0.172373E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.790570E+09 | 0.201809E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.747877E+09 | 0.188533E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.730441E+09 | 0.180330E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.683530E+09 | 0.165010E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.669923E+09 | 0.153631E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.888026E+10 | 0.217573E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.649387E+09 | 0.150023E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.857957E+09 | 0.222826E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_10:10
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.772744E+09 | 0.173205E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.741282E+09 | 0.171542E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.860589E+09 | 0.202790E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.880790E+09 | 0.220435E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.974721E+09 | 0.249419E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.983715E+09 | 0.253420E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.820552E+09 | 0.197003E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.906869E+09 | 0.228468E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.857922E+09 | 0.214129E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.831437E+09 | 0.201115E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.778699E+09 | 0.185285E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.768414E+09 | 0.173123E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.101777E+11 | 0.246993E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.741282E+09 | 0.171542E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.983715E+09 | 0.253420E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.183481E+10 | 0.00 | 0.00 | 0.00 | 0.101996E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.173226E+10 | 0.00 | 0.00 | 0.00 | 0.100091E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.195451E+10 | 0.00 | 0.00 | 0.00 | 0.116980E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.198886E+10 | 0.00 | 0.00 | 0.00 | 0.126044E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.214929E+10 | 0.00 | 0.00 | 0.00 | 0.138449E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.214689E+10 | 0.00 | 0.00 | 0.00 | 0.137717E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.190554E+10 | 0.00 | 0.00 | 0.00 | 0.112909E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.203113E+10 | 0.00 | 0.00 | 0.00 | 0.124022E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.195274E+10 | 0.00 | 0.00 | 0.00 | 0.118952E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.193562E+10 | 0.00 | 0.00 | 0.00 | 0.113689E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.182996E+10 | 0.00 | 0.00 | 0.00 | 0.105922E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.184358E+10 | 0.00 | 0.00 | 0.00 | 0.102301E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.233052E+11 | 0.00 | 0.00 | 0.00 | 0.139907E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.173226E+10 | 0.00 | 0.00 | 0.00 | 0.100091E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.214929E+10 | 0.00 | 0.00 | 0.00 | 0.138449E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.857308E+09 | 0.00 | 0.00 | 0.00 | 0.496372E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.814117E+09 | 0.00 | 0.00 | 0.00 | 0.483224E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.925399E+09 | 0.00 | 0.00 | 0.00 | 0.560846E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.957837E+09 | 0.00 | 0.00 | 0.00 | 0.601200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.104958E+10 | 0.00 | 0.00 | 0.00 | 0.664672E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.104676E+10 | 0.00 | 0.00 | 0.00 | 0.660595E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.907457E+09 | 0.00 | 0.00 | 0.00 | 0.543411E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.977972E+09 | 0.00 | 0.00 | 0.00 | 0.597992E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.937671E+09 | 0.00 | 0.00 | 0.00 | 0.571940E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.922779E+09 | 0.00 | 0.00 | 0.00 | 0.551596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.866644E+09 | 0.00 | 0.00 | 0.00 | 0.514057E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.859511E+09 | 0.00 | 0.00 | 0.00 | 0.498426E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.111230E+11 | 0.00 | 0.00 | 0.00 | 0.674433E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.814117E+09 | 0.00 | 0.00 | 0.00 | 0.483224E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.104958E+10 | 0.00 | 0.00 | 0.00 | 0.664672E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_3:3
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.774257E+09 | 0.00 | 0.00 | 0.00 | 0.401228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.734283E+09 | 0.00 | 0.00 | 0.00 | 0.393915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.841366E+09 | 0.00 | 0.00 | 0.00 | 0.465687E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.853916E+09 | 0.00 | 0.00 | 0.00 | 0.493146E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.939378E+09 | 0.00 | 0.00 | 0.00 | 0.553127E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.942530E+09 | 0.00 | 0.00 | 0.00 | 0.554506E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.807293E+09 | 0.00 | 0.00 | 0.00 | 0.438603E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.886538E+09 | 0.00 | 0.00 | 0.00 | 0.499049E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.838390E+09 | 0.00 | 0.00 | 0.00 | 0.469467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.827208E+09 | 0.00 | 0.00 | 0.00 | 0.450680E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.779123E+09 | 0.00 | 0.00 | 0.00 | 0.419606E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.772008E+09 | 0.00 | 0.00 | 0.00 | 0.401299E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.999629E+10 | 0.00 | 0.00 | 0.00 | 0.554031E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.734283E+09 | 0.00 | 0.00 | 0.00 | 0.393915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.942530E+09 | 0.00 | 0.00 | 0.00 | 0.554506E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_4:4
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.776022E+09 | 0.00 | 0.00 | 0.00 | 0.402341E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.735864E+09 | 0.00 | 0.00 | 0.00 | 0.395009E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.843250E+09 | 0.00 | 0.00 | 0.00 | 0.466975E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.855989E+09 | 0.00 | 0.00 | 0.00 | 0.494682E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.942291E+09 | 0.00 | 0.00 | 0.00 | 0.555160E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.945461E+09 | 0.00 | 0.00 | 0.00 | 0.556461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.809450E+09 | 0.00 | 0.00 | 0.00 | 0.440218E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.888306E+09 | 0.00 | 0.00 | 0.00 | 0.500145E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.840303E+09 | 0.00 | 0.00 | 0.00 | 0.470752E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.828880E+09 | 0.00 | 0.00 | 0.00 | 0.451783E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.780591E+09 | 0.00 | 0.00 | 0.00 | 0.420353E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.773731E+09 | 0.00 | 0.00 | 0.00 | 0.402063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.100201E+11 | 0.00 | 0.00 | 0.00 | 0.555594E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.735864E+09 | 0.00 | 0.00 | 0.00 | 0.395009E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.945461E+09 | 0.00 | 0.00 | 0.00 | 0.556461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_5:5
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.768681E+09 | 0.00 | 0.00 | 0.00 | 0.397090E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.728690E+09 | 0.00 | 0.00 | 0.00 | 0.390171E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.835081E+09 | 0.00 | 0.00 | 0.00 | 0.461250E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.847472E+09 | 0.00 | 0.00 | 0.00 | 0.488842E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.933348E+09 | 0.00 | 0.00 | 0.00 | 0.549281E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.936543E+09 | 0.00 | 0.00 | 0.00 | 0.550672E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.801406E+09 | 0.00 | 0.00 | 0.00 | 0.434709E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.879494E+09 | 0.00 | 0.00 | 0.00 | 0.493860E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.832003E+09 | 0.00 | 0.00 | 0.00 | 0.464916E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.820559E+09 | 0.00 | 0.00 | 0.00 | 0.445869E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.772730E+09 | 0.00 | 0.00 | 0.00 | 0.414792E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.766405E+09 | 0.00 | 0.00 | 0.00 | 0.396624E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.992241E+10 | 0.00 | 0.00 | 0.00 | 0.548808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.728690E+09 | 0.00 | 0.00 | 0.00 | 0.390171E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.936543E+09 | 0.00 | 0.00 | 0.00 | 0.550672E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_6:6
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.124293E+10 | 0.00 | 0.00 | 0.00 | 0.724855E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.119579E+10 | 0.00 | 0.00 | 0.00 | 0.714418E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.137276E+10 | 0.00 | 0.00 | 0.00 | 0.843011E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.140539E+10 | 0.00 | 0.00 | 0.00 | 0.893504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.157024E+10 | 0.00 | 0.00 | 0.00 | 0.100750E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.158366E+10 | 0.00 | 0.00 | 0.00 | 0.101609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.131358E+10 | 0.00 | 0.00 | 0.00 | 0.788760E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.145856E+10 | 0.00 | 0.00 | 0.00 | 0.903298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.137811E+10 | 0.00 | 0.00 | 0.00 | 0.847416E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.134831E+10 | 0.00 | 0.00 | 0.00 | 0.810126E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.126130E+10 | 0.00 | 0.00 | 0.00 | 0.754127E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.123538E+10 | 0.00 | 0.00 | 0.00 | 0.718803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.163660E+11 | 0.00 | 0.00 | 0.00 | 0.100219E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.119579E+10 | 0.00 | 0.00 | 0.00 | 0.714418E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.158366E+10 | 0.00 | 0.00 | 0.00 | 0.101609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_7:7
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.674591E+09 | 0.00 | 0.00 | 0.00 | 0.370947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.648877E+09 | 0.00 | 0.00 | 0.00 | 0.365904E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.745105E+09 | 0.00 | 0.00 | 0.00 | 0.431640E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.762298E+09 | 0.00 | 0.00 | 0.00 | 0.457675E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.849133E+09 | 0.00 | 0.00 | 0.00 | 0.515639E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.854695E+09 | 0.00 | 0.00 | 0.00 | 0.519460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.711863E+09 | 0.00 | 0.00 | 0.00 | 0.403329E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.789004E+09 | 0.00 | 0.00 | 0.00 | 0.461607E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.746165E+09 | 0.00 | 0.00 | 0.00 | 0.433317E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.730387E+09 | 0.00 | 0.00 | 0.00 | 0.414158E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.683737E+09 | 0.00 | 0.00 | 0.00 | 0.385482E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.670312E+09 | 0.00 | 0.00 | 0.00 | 0.367628E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.886617E+10 | 0.00 | 0.00 | 0.00 | 0.512679E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.648877E+09 | 0.00 | 0.00 | 0.00 | 0.365904E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.854695E+09 | 0.00 | 0.00 | 0.00 | 0.519460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_8:8
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.672114E+09 | 0.00 | 0.00 | 0.00 | 0.369366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.646712E+09 | 0.00 | 0.00 | 0.00 | 0.364551E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.742745E+09 | 0.00 | 0.00 | 0.00 | 0.430155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.760141E+09 | 0.00 | 0.00 | 0.00 | 0.456305E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.846983E+09 | 0.00 | 0.00 | 0.00 | 0.514184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.852539E+09 | 0.00 | 0.00 | 0.00 | 0.517980E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.709599E+09 | 0.00 | 0.00 | 0.00 | 0.401962E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.786681E+09 | 0.00 | 0.00 | 0.00 | 0.460110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.743983E+09 | 0.00 | 0.00 | 0.00 | 0.431938E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.727941E+09 | 0.00 | 0.00 | 0.00 | 0.412628E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.681285E+09 | 0.00 | 0.00 | 0.00 | 0.383911E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.667789E+09 | 0.00 | 0.00 | 0.00 | 0.366007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.883851E+10 | 0.00 | 0.00 | 0.00 | 0.510910E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.646712E+09 | 0.00 | 0.00 | 0.00 | 0.364551E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.852539E+09 | 0.00 | 0.00 | 0.00 | 0.517980E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_9:9
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.674422E+09 | 0.00 | 0.00 | 0.00 | 0.370150E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.649387E+09 | 0.00 | 0.00 | 0.00 | 0.366054E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.746467E+09 | 0.00 | 0.00 | 0.00 | 0.432187E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.764560E+09 | 0.00 | 0.00 | 0.00 | 0.459045E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.851912E+09 | 0.00 | 0.00 | 0.00 | 0.516963E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.857957E+09 | 0.00 | 0.00 | 0.00 | 0.521132E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.713220E+09 | 0.00 | 0.00 | 0.00 | 0.403993E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.790570E+09 | 0.00 | 0.00 | 0.00 | 0.462042E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.747877E+09 | 0.00 | 0.00 | 0.00 | 0.434020E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.730441E+09 | 0.00 | 0.00 | 0.00 | 0.413488E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.683530E+09 | 0.00 | 0.00 | 0.00 | 0.384687E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.669923E+09 | 0.00 | 0.00 | 0.00 | 0.366487E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.888026E+10 | 0.00 | 0.00 | 0.00 | 0.513025E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.649387E+09 | 0.00 | 0.00 | 0.00 | 0.366054E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.857957E+09 | 0.00 | 0.00 | 0.00 | 0.521132E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_10:10
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.772744E+09 | 0.00 | 0.00 | 0.00 | 0.422832E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.741282E+09 | 0.00 | 0.00 | 0.00 | 0.421437E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.860589E+09 | 0.00 | 0.00 | 0.00 | 0.501527E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.880790E+09 | 0.00 | 0.00 | 0.00 | 0.532819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.974721E+09 | 0.00 | 0.00 | 0.00 | 0.592087E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.983715E+09 | 0.00 | 0.00 | 0.00 | 0.600041E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.820552E+09 | 0.00 | 0.00 | 0.00 | 0.465919E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.906869E+09 | 0.00 | 0.00 | 0.00 | 0.529600E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.857922E+09 | 0.00 | 0.00 | 0.00 | 0.498717E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.831437E+09 | 0.00 | 0.00 | 0.00 | 0.466947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.778699E+09 | 0.00 | 0.00 | 0.00 | 0.436577E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.768414E+09 | 0.00 | 0.00 | 0.00 | 0.417156E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.101777E+11 | 0.00 | 0.00 | 0.00 | 0.588566E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.741282E+09 | 0.00 | 0.00 | 0.00 | 0.417156E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.983715E+09 | 0.00 | 0.00 | 0.00 | 0.600041E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 35535.28 | 0.139061E+11 | 0.00 | 253930.61 | 0.130456E+09 | 0.00 | 4139827.29 | 0.00 | 0.57 |
February | 0.00 | 0.141014E+11 | 0.00 | 160780.24 | 0.123585E+09 | 0.00 | 2102988.44 | 0.00 | 0.57 |
March | 0.00 | 0.170158E+11 | 0.00 | 0.00 | 0.151131E+09 | 0.00 | 0.00 | 0.00 | 0.58 |
April | 0.00 | 0.210670E+11 | 0.00 | 0.00 | 0.136492E+09 | 0.00 | 0.00 | 0.00 | 0.58 |
May | 0.00 | 0.248914E+11 | 0.00 | 0.00 | 0.146423E+09 | 0.00 | 0.00 | 0.00 | 0.58 |
June | 0.00 | 0.247186E+11 | 0.00 | 0.00 | 0.127773E+09 | 0.00 | 0.00 | 0.00 | 0.58 |
July | 0.00 | 0.179214E+11 | 0.00 | 0.00 | 0.186824E+09 | 0.00 | 0.00 | 0.00 | 0.58 |
August | 0.00 | 0.223407E+11 | 0.00 | 0.00 | 0.167156E+09 | 0.00 | 0.00 | 0.00 | 0.58 |
September | 0.00 | 0.209044E+11 | 0.00 | 0.00 | 0.184350E+09 | 0.00 | 0.00 | 0.00 | 0.58 |
October | 0.00 | 0.195300E+11 | 0.00 | 0.00 | 0.188898E+09 | 0.00 | 0.00 | 0.00 | 0.58 |
November | 0.00 | 0.169848E+11 | 0.00 | 0.00 | 0.141243E+09 | 0.00 | 0.00 | 0.00 | 0.57 |
December | 0.00 | 0.147497E+11 | 0.00 | 4752.31 | 0.141409E+09 | 0.00 | 357997.02 | 0.00 | 0.58 |
Annual Sum or Average | 35535.28 | 0.228131E+12 | 0.00 | 419463.15 | 0.182574E+10 | 0.00 | 6600812.75 | 0.00 | 0.58 |
Minimum of Months | 0.00 | 0.139061E+11 | 0.00 | 0.00 | 0.123585E+09 | 0.00 | 0.00 | 0.00 | 0.57 |
Maximum of Months | 35535.28 | 0.248914E+11 | 0.00 | 253930.61 | 0.188898E+09 | 0.00 | 4139827.29 | 0.00 | 0.58 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.611653E+10 | 0.00 | 0.00 | 0.100651E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
February | 0.00 | 0.618684E+10 | 0.00 | 0.00 | 84622679.95 | 0.00 | 0.00 | 0.00 | 0.48 |
March | 0.00 | 0.743310E+10 | 0.00 | 0.00 | 0.109934E+09 | 0.00 | 0.00 | 0.00 | 0.48 |
April | 0.00 | 0.915813E+10 | 0.00 | 0.00 | 98071368.90 | 0.00 | 0.00 | 0.00 | 0.49 |
May | 0.00 | 0.109432E+11 | 0.00 | 0.00 | 0.110378E+09 | 0.00 | 0.00 | 0.00 | 0.49 |
June | 0.00 | 0.109335E+11 | 0.00 | 0.00 | 0.103199E+09 | 0.00 | 0.00 | 0.00 | 0.49 |
July | 0.00 | 0.780826E+10 | 0.00 | 0.00 | 0.124957E+09 | 0.00 | 0.00 | 0.00 | 0.48 |
August | 0.00 | 0.987793E+10 | 0.00 | 0.00 | 0.124131E+09 | 0.00 | 0.00 | 0.00 | 0.49 |
September | 0.00 | 0.916797E+10 | 0.00 | 0.00 | 0.123505E+09 | 0.00 | 0.00 | 0.00 | 0.48 |
October | 0.00 | 0.860080E+10 | 0.00 | 0.00 | 0.132746E+09 | 0.00 | 0.00 | 0.00 | 0.48 |
November | 0.00 | 0.749159E+10 | 0.00 | 0.00 | 97469744.19 | 0.00 | 0.00 | 0.00 | 0.48 |
December | 0.00 | 0.649980E+10 | 0.00 | 0.00 | 0.106523E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
Annual Sum or Average | 0.00 | 0.100218E+12 | 0.00 | 0.00 | 0.131619E+10 | 0.00 | 0.00 | 0.00 | 0.48 |
Minimum of Months | 0.00 | 0.611653E+10 | 0.00 | 0.00 | 84622679.95 | 0.00 | 0.00 | 0.00 | 0.47 |
Maximum of Months | 0.00 | 0.109432E+11 | 0.00 | 0.00 | 0.132746E+09 | 0.00 | 0.00 | 0.00 | 0.49 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 4039107.19 | 0.507256E+10 | 0.00 | 361414.37 | 0.335848E+09 | 0.00 | 10710923.05 | 0.00 | 0.46 |
February | 1748441.29 | 0.515602E+10 | 0.00 | 331197.38 | 0.332999E+09 | 0.00 | 1602346.17 | 0.00 | 0.46 |
March | 0.00 | 0.637409E+10 | 0.00 | 45365.36 | 0.397911E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
April | 0.00 | 0.757964E+10 | 0.00 | 0.00 | 0.517589E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
May | 0.00 | 0.916842E+10 | 0.00 | 0.00 | 0.571134E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
June | 0.00 | 0.925235E+10 | 0.00 | 27309.69 | 0.574235E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
July | 0.00 | 0.645725E+10 | 0.00 | 0.00 | 0.426320E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
August | 0.00 | 0.842622E+10 | 0.00 | 18038.15 | 0.511296E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
September | 0.00 | 0.765207E+10 | 0.00 | 27497.49 | 0.488520E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
October | 0.00 | 0.719968E+10 | 0.00 | 69751.78 | 0.452305E+09 | 0.00 | 21958.44 | 0.00 | 0.46 |
November | 582051.63 | 0.621263E+10 | 0.00 | 281502.40 | 0.398704E+09 | 0.00 | 1454991.20 | 0.00 | 0.46 |
December | 106386.54 | 0.533105E+10 | 0.00 | 488693.63 | 0.336789E+09 | 0.00 | 778259.00 | 0.00 | 0.46 |
Annual Sum or Average | 6475986.65 | 0.838820E+11 | 0.00 | 1650770.26 | 0.534365E+10 | 0.00 | 14568477.86 | 0.00 | 0.46 |
Minimum of Months | 0.00 | 0.507256E+10 | 0.00 | 0.00 | 0.332999E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
Maximum of Months | 4039107.19 | 0.925235E+10 | 0.00 | 488693.63 | 0.574235E+09 | 0.00 | 10710923.05 | 0.00 | 0.47 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 4016477.01 | 0.508122E+10 | 0.00 | 372670.98 | 0.335813E+09 | 0.00 | 10504679.84 | 0.00 | 0.46 |
February | 1715951.30 | 0.516362E+10 | 0.00 | 343147.43 | 0.333651E+09 | 0.00 | 1571877.81 | 0.00 | 0.46 |
March | 0.00 | 0.638440E+10 | 0.00 | 51231.46 | 0.397491E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
April | 0.00 | 0.759312E+10 | 0.00 | 0.00 | 0.517590E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
May | 0.00 | 0.918665E+10 | 0.00 | 0.00 | 0.571164E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
June | 0.00 | 0.927111E+10 | 0.00 | 29374.67 | 0.573103E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
July | 0.00 | 0.647389E+10 | 0.00 | 0.00 | 0.424837E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
August | 0.00 | 0.843640E+10 | 0.00 | 19461.77 | 0.511399E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
September | 0.00 | 0.766646E+10 | 0.00 | 28534.55 | 0.486270E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
October | 0.00 | 0.721089E+10 | 0.00 | 73260.11 | 0.451675E+09 | 0.00 | 22176.98 | 0.00 | 0.46 |
November | 634724.70 | 0.622005E+10 | 0.00 | 294138.09 | 0.397186E+09 | 0.00 | 1354248.15 | 0.00 | 0.46 |
December | 102941.31 | 0.533713E+10 | 0.00 | 501248.17 | 0.336660E+09 | 0.00 | 786126.69 | 0.00 | 0.46 |
Annual Sum or Average | 6470094.33 | 0.840249E+11 | 0.00 | 1713067.21 | 0.533684E+10 | 0.00 | 14239109.47 | 0.00 | 0.46 |
Minimum of Months | 0.00 | 0.508122E+10 | 0.00 | 0.00 | 0.333651E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
Maximum of Months | 4016477.01 | 0.927111E+10 | 0.00 | 501248.17 | 0.573103E+09 | 0.00 | 10504679.84 | 0.00 | 0.47 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 3897614.90 | 0.504534E+10 | 0.00 | 354909.52 | 0.333209E+09 | 0.00 | 11473155.80 | 0.00 | 0.46 |
February | 1779553.86 | 0.512973E+10 | 0.00 | 320275.92 | 0.332735E+09 | 0.00 | 1808928.97 | 0.00 | 0.46 |
March | 0.00 | 0.634565E+10 | 0.00 | 45548.20 | 0.394749E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
April | 0.00 | 0.754741E+10 | 0.00 | 0.00 | 0.517232E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
May | 0.00 | 0.913963E+10 | 0.00 | 0.00 | 0.569328E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
June | 0.00 | 0.922417E+10 | 0.00 | 27732.56 | 0.572443E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
July | 0.00 | 0.642680E+10 | 0.00 | 0.00 | 0.424529E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
August | 0.00 | 0.837470E+10 | 0.00 | 17386.12 | 0.512202E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
September | 0.00 | 0.760789E+10 | 0.00 | 26368.34 | 0.490292E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
October | 0.00 | 0.715039E+10 | 0.00 | 68310.08 | 0.455118E+09 | 0.00 | 21564.39 | 0.00 | 0.46 |
November | 608497.66 | 0.617107E+10 | 0.00 | 276112.49 | 0.396479E+09 | 0.00 | 1491476.85 | 0.00 | 0.46 |
December | 149141.37 | 0.529458E+10 | 0.00 | 475316.79 | 0.334218E+09 | 0.00 | 842409.55 | 0.00 | 0.46 |
Annual Sum or Average | 6434807.79 | 0.834574E+11 | 0.00 | 1611960.02 | 0.533253E+10 | 0.00 | 15637535.57 | 0.00 | 0.46 |
Minimum of Months | 0.00 | 0.504534E+10 | 0.00 | 0.00 | 0.332735E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
Maximum of Months | 3897614.90 | 0.922417E+10 | 0.00 | 475316.79 | 0.572443E+09 | 0.00 | 11473155.80 | 0.00 | 0.47 |
Report: MechanicalVentilationLoadsMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 2310533.55 | 0.968879E+10 | 0.00 | 725472.69 | 0.247918E+09 | 0.00 | 10819852.28 | 0.00 | 0.42 |
February | 7944.97 | 0.985545E+10 | 0.00 | 262280.56 | 0.289878E+09 | 0.00 | 138664.84 | 0.00 | 0.42 |
March | 0.00 | 0.120805E+11 | 0.00 | 0.00 | 0.303494E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
April | 0.00 | 0.144804E+11 | 0.00 | 0.00 | 0.386892E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
May | 0.00 | 0.174696E+11 | 0.00 | 0.00 | 0.381888E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
June | 0.00 | 0.178139E+11 | 0.00 | 0.00 | 0.346639E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
July | 0.00 | 0.121532E+11 | 0.00 | 0.00 | 0.397838E+09 | 0.00 | 0.00 | 0.00 | 0.42 |
August | 0.00 | 0.160654E+11 | 0.00 | 0.00 | 0.350740E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
September | 0.00 | 0.145336E+11 | 0.00 | 127008.42 | 0.388745E+09 | 0.00 | 69297.95 | 0.00 | 0.43 |
October | 0.00 | 0.135938E+11 | 0.00 | 51072.60 | 0.383421E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
November | 428158.53 | 0.118088E+11 | 0.00 | 408217.68 | 0.288595E+09 | 0.00 | 1423070.94 | 0.00 | 0.43 |
December | 16347.24 | 0.100486E+11 | 0.00 | 356607.95 | 0.310452E+09 | 0.00 | 704866.12 | 0.00 | 0.42 |
Annual Sum or Average | 2762984.29 | 0.159592E+12 | 0.00 | 1930659.90 | 0.407650E+10 | 0.00 | 13155752.13 | 0.00 | 0.43 |
Minimum of Months | 0.00 | 0.968879E+10 | 0.00 | 0.00 | 0.247918E+09 | 0.00 | 0.00 | 0.00 | 0.42 |
Maximum of Months | 2310533.55 | 0.178139E+11 | 0.00 | 725472.69 | 0.397838E+09 | 0.00 | 10819852.28 | 0.00 | 0.44 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 1045213.48 | 0.483868E+10 | 0.00 | 352596.76 | 0.123080E+09 | 0.00 | 5372048.07 | 0.00 | 0.42 |
February | 3573.61 | 0.492375E+10 | 0.00 | 131310.16 | 0.142030E+09 | 0.00 | 66188.59 | 0.00 | 0.42 |
March | 0.00 | 0.603544E+10 | 0.00 | 0.00 | 0.152395E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
April | 0.00 | 0.722903E+10 | 0.00 | 0.00 | 0.191064E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
May | 0.00 | 0.871340E+10 | 0.00 | 0.00 | 0.188567E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
June | 0.00 | 0.888035E+10 | 0.00 | 0.00 | 0.171179E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
July | 0.00 | 0.605622E+10 | 0.00 | 0.00 | 0.198676E+09 | 0.00 | 0.00 | 0.00 | 0.42 |
August | 0.00 | 0.800294E+10 | 0.00 | 0.00 | 0.171674E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
September | 0.00 | 0.723661E+10 | 0.00 | 62332.09 | 0.194698E+09 | 0.00 | 51273.12 | 0.00 | 0.43 |
October | 0.00 | 0.677027E+10 | 0.00 | 29952.59 | 0.187867E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
November | 241838.38 | 0.588283E+10 | 0.00 | 218056.36 | 0.141636E+09 | 0.00 | 767577.28 | 0.00 | 0.43 |
December | 9147.16 | 0.501336E+10 | 0.00 | 172970.88 | 0.151255E+09 | 0.00 | 367737.88 | 0.00 | 0.42 |
Annual Sum or Average | 1299772.62 | 0.795829E+11 | 0.00 | 967218.84 | 0.201412E+10 | 0.00 | 6624824.94 | 0.00 | 0.43 |
Minimum of Months | 0.00 | 0.483868E+10 | 0.00 | 0.00 | 0.123080E+09 | 0.00 | 0.00 | 0.00 | 0.42 |
Maximum of Months | 1045213.48 | 0.888035E+10 | 0.00 | 352596.76 | 0.198676E+09 | 0.00 | 5372048.07 | 0.00 | 0.44 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 1062685.31 | 0.482754E+10 | 0.00 | 347514.75 | 0.122969E+09 | 0.00 | 5521815.57 | 0.00 | 0.42 |
February | 4570.50 | 0.491448E+10 | 0.00 | 130548.73 | 0.141869E+09 | 0.00 | 67719.43 | 0.00 | 0.42 |
March | 0.00 | 0.602548E+10 | 0.00 | 0.00 | 0.152165E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
April | 0.00 | 0.721848E+10 | 0.00 | 0.00 | 0.191528E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
May | 0.00 | 0.870212E+10 | 0.00 | 0.00 | 0.188348E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
June | 0.00 | 0.886912E+10 | 0.00 | 0.00 | 0.170983E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
July | 0.00 | 0.604549E+10 | 0.00 | 0.00 | 0.198362E+09 | 0.00 | 0.00 | 0.00 | 0.42 |
August | 0.00 | 0.798984E+10 | 0.00 | 0.00 | 0.171377E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
September | 0.00 | 0.722550E+10 | 0.00 | 61914.72 | 0.193861E+09 | 0.00 | 51715.89 | 0.00 | 0.43 |
October | 0.00 | 0.675724E+10 | 0.00 | 29817.02 | 0.186847E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
November | 244784.22 | 0.587005E+10 | 0.00 | 216190.44 | 0.140867E+09 | 0.00 | 775325.21 | 0.00 | 0.43 |
December | 9316.11 | 0.499761E+10 | 0.00 | 170643.63 | 0.154251E+09 | 0.00 | 378324.94 | 0.00 | 0.42 |
Annual Sum or Average | 1321356.15 | 0.794429E+11 | 0.00 | 956629.28 | 0.201343E+10 | 0.00 | 6794901.05 | 0.00 | 0.43 |
Minimum of Months | 0.00 | 0.482754E+10 | 0.00 | 0.00 | 0.122969E+09 | 0.00 | 0.00 | 0.00 | 0.42 |
Maximum of Months | 1062685.31 | 0.886912E+10 | 0.00 | 347514.75 | 0.198362E+09 | 0.00 | 5521815.57 | 0.00 | 0.44 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 1104437.20 | 0.482879E+10 | 0.00 | 332236.47 | 0.124023E+09 | 0.00 | 5706356.23 | 0.00 | 0.42 |
February | 4317.41 | 0.492301E+10 | 0.00 | 123025.97 | 0.141281E+09 | 0.00 | 65155.17 | 0.00 | 0.42 |
March | 0.00 | 0.603554E+10 | 0.00 | 0.00 | 0.153801E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
April | 0.00 | 0.723654E+10 | 0.00 | 0.00 | 0.193737E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
May | 0.00 | 0.871947E+10 | 0.00 | 0.00 | 0.190860E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
June | 0.00 | 0.888495E+10 | 0.00 | 0.00 | 0.179046E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
July | 0.00 | 0.605738E+10 | 0.00 | 0.00 | 0.201865E+09 | 0.00 | 0.00 | 0.00 | 0.42 |
August | 0.00 | 0.799733E+10 | 0.00 | 0.00 | 0.178402E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
September | 0.00 | 0.723930E+10 | 0.00 | 59457.26 | 0.196848E+09 | 0.00 | 51019.52 | 0.00 | 0.43 |
October | 0.00 | 0.675545E+10 | 0.00 | 28684.52 | 0.191553E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
November | 252966.58 | 0.587055E+10 | 0.00 | 205649.87 | 0.143204E+09 | 0.00 | 781295.75 | 0.00 | 0.43 |
December | 9274.68 | 0.499316E+10 | 0.00 | 163016.55 | 0.158019E+09 | 0.00 | 386493.69 | 0.00 | 0.42 |
Annual Sum or Average | 1370995.86 | 0.795415E+11 | 0.00 | 912070.64 | 0.205264E+10 | 0.00 | 6990320.36 | 0.00 | 0.43 |
Minimum of Months | 0.00 | 0.482879E+10 | 0.00 | 0.00 | 0.124023E+09 | 0.00 | 0.00 | 0.00 | 0.42 |
Maximum of Months | 1104437.20 | 0.888495E+10 | 0.00 | 332236.47 | 0.201865E+09 | 0.00 | 5706356.23 | 0.00 | 0.44 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 1236728.42 | 0.507956E+10 | 0.00 | 400707.76 | 0.113670E+09 | 0.00 | 5058283.89 | 0.00 | 0.42 |
February | 32264.77 | 0.520023E+10 | 0.00 | 218643.36 | 0.129609E+09 | 0.00 | 223638.40 | 0.00 | 0.42 |
March | 0.00 | 0.634646E+10 | 0.00 | 89.94 | 0.126892E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
April | 0.00 | 0.761251E+10 | 0.00 | 0.00 | 0.167733E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
May | 0.00 | 0.907344E+10 | 0.00 | 0.00 | 0.173920E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
June | 0.00 | 0.928643E+10 | 0.00 | 0.00 | 0.155226E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
July | 0.00 | 0.642502E+10 | 0.00 | 0.00 | 0.177540E+09 | 0.00 | 0.00 | 0.00 | 0.42 |
August | 0.00 | 0.837404E+10 | 0.00 | 0.00 | 0.158328E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
September | 0.00 | 0.762180E+10 | 0.00 | 62678.58 | 0.185354E+09 | 0.00 | 58328.41 | 0.00 | 0.43 |
October | 0.00 | 0.705717E+10 | 0.00 | 37999.94 | 0.178766E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
November | 32978.60 | 0.617445E+10 | 0.00 | 223933.67 | 0.126651E+09 | 0.00 | 581182.22 | 0.00 | 0.43 |
December | 5955.45 | 0.526864E+10 | 0.00 | 178918.00 | 0.135577E+09 | 0.00 | 668184.47 | 0.00 | 0.42 |
Annual Sum or Average | 1307927.24 | 0.835197E+11 | 0.00 | 1122971.24 | 0.182927E+10 | 0.00 | 6589617.39 | 0.00 | 0.43 |
Minimum of Months | 0.00 | 0.507956E+10 | 0.00 | 0.00 | 0.113670E+09 | 0.00 | 0.00 | 0.00 | 0.42 |
Maximum of Months | 1236728.42 | 0.928643E+10 | 0.00 | 400707.76 | 0.185354E+09 | 0.00 | 5058283.89 | 0.00 | 0.43 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:37:06
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.243107E+12 | -0.376477E+11 | 0.00 | -0.848557E+11 | 0.253224E+12 |
February | 0.242001E+12 | -0.391117E+11 | 0.00 | -0.900855E+11 | 0.247692E+12 |
March | 0.317521E+12 | -0.471112E+11 | 0.00 | -0.115160E+12 | 0.290334E+12 |
April | 0.318229E+12 | -0.546780E+11 | 0.00 | -0.142249E+12 | 0.315203E+12 |
May | 0.318802E+12 | -0.642752E+11 | 0.00 | -0.171270E+12 | 0.357897E+12 |
June | 0.332344E+12 | -0.645547E+11 | 0.00 | -0.167850E+12 | 0.359727E+12 |
July | 0.275972E+12 | -0.465320E+11 | 0.00 | -0.121189E+12 | 0.284250E+12 |
August | 0.339208E+12 | -0.580162E+11 | 0.00 | -0.151146E+12 | 0.326863E+12 |
September | 0.268397E+12 | -0.539118E+11 | 0.00 | -0.140272E+12 | 0.307593E+12 |
October | 0.288169E+12 | -0.506807E+11 | 0.00 | -0.129787E+12 | 0.294749E+12 |
November | 0.236400E+12 | -0.438898E+11 | 0.00 | -0.108718E+12 | 0.271099E+12 |
December | 0.228870E+12 | -0.388079E+11 | 0.00 | -0.873170E+11 | 0.255236E+12 |
Annual Sum or Average | 0.340902E+13 | -0.599217E+12 | 0.00 | -0.150990E+13 | 0.356387E+13 |
Minimum of Months | 0.228870E+12 | -0.645547E+11 | 0.00 | -0.171270E+12 | 0.247692E+12 |
Maximum of Months | 0.339208E+12 | -0.376477E+11 | 0.00 | -0.848557E+11 | 0.359727E+12 |