Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:37
Tabular Output Report in Format: HTML
Building: RetailStripmall
Environment: RUNPERIOD 1 ** Miami Intl Ap FL USA TMY3 WMO#=722020
Simulation Timestamp: 2023-10-16 08:37:25
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:25
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1167.94 | 558.74 | 558.74 |
Net Site Energy | 1167.94 | 558.74 | 558.74 |
Total Source Energy | 3697.82 | 1769.02 | 1769.02 |
Net Source Energy | 3697.82 | 1769.02 | 1769.02 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 2090.32 |
Net Conditioned Building Area | 2090.32 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 0.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 451.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 366.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 60.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 128.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 102.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 58.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1167.44 | 0.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 451.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 366.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 60.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 128.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 102.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 58.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 0.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 451.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 366.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 60.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 128.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 102.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 58.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 204.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 293.01 | 0.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Other | 61.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 558.50 | 0.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 204.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 293.01 | 0.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Other | 61.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 558.50 | 0.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1167.441 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1167.441 | 100.00 |
Total On-Site and Utility Electric Sources | 1167.441 | 100.00 |
Total Electricity End Uses | 1167.441 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 87.30 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 87.30 | 100.00 |
Total Water End Uses | 87.30 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 0.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 1980.67 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTRIPMALL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 1A
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_FL_MIAMI
| Environment |ZoneCoolingSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ZoneHeatingSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ZoneElectricSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |SpaceGainsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |PeakSpaceGainsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |SpaceGainComponentsAtCoolingPeakMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ComfortReportSimple55Monthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |OccupantComfortDataSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |DXReportMonthly
| PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL | PSZ-AC_3:3 COOLING COIL | PSZ-AC_4:4 COOLING COIL | PSZ-AC_5:5 COOLING COIL | PSZ-AC_6:6 COOLING COIL | PSZ-AC_7:7 COOLING COIL | PSZ-AC_8:8 COOLING COIL | PSZ-AC_9:9 COOLING COIL | PSZ-AC_10:10 COOLING COIL |WindowReportMonthly
| LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR |WindowEnergyReportMonthly
| LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR |WindowZoneSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |WindowEnergyZoneSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| GAS TANK1 | GAS TANK2 | GAS TANK3 | GAS TANK4 | GAS TANK5 | GAS TANK6 | GAS TANK7 |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC_1:1 HEATING COIL | PSZ-AC_2:2 HEATING COIL | PSZ-AC_3:3 HEATING COIL | PSZ-AC_4:4 HEATING COIL | PSZ-AC_5:5 HEATING COIL | PSZ-AC_6:6 HEATING COIL | PSZ-AC_7:7 HEATING COIL | PSZ-AC_8:8 HEATING COIL | PSZ-AC_9:9 HEATING COIL | PSZ-AC_10:10 HEATING COIL | PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL | PSZ-AC_3:3 COOLING COIL | PSZ-AC_4:4 COOLING COIL | PSZ-AC_5:5 COOLING COIL | PSZ-AC_6:6 COOLING COIL | PSZ-AC_7:7 COOLING COIL | PSZ-AC_8:8 COOLING COIL | PSZ-AC_9:9 COOLING COIL | PSZ-AC_10:10 COOLING COIL |FanReportMonthly
| PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN |ZoneTemperatureOscillationReportMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |MechanicalVentilationLoadsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:25
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:37 |
RunPeriod | RUNPERIOD 1 |
Weather File | Miami Intl Ap FL USA TMY3 WMO#=722020 |
Latitude [deg] | 25.82 |
Longitude [deg] | -80.3 |
Elevation [m] | 11.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Above Ground Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Window Opening Area [m2] | 124.40 | 0.00 | 0.00 | 124.40 | 0.00 |
Gross Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Above Ground Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Above Ground Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Window Opening Area [m2] | 124.40 | 0.00 | 0.00 | 124.40 | 0.00 |
Gross Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Above Ground Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Total | |
Gross Roof Area [m2] | 2090.32 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
LGSTORE1 | 348.39 | Yes | Yes | 1805.20 | 1.00 | 276.30 | 0.00 | 20.77 | 20.77 | 15.3022 | 6.19 | 4.3000 |
SMSTORE1 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.38 | 10.38 | 18.2890 | 6.19 | 4.3000 |
SMSTORE2 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 16.6533 | 6.19 | 4.3000 |
SMSTORE3 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 16.6533 | 6.19 | 4.3000 |
SMSTORE4 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 16.6533 | 6.19 | 4.3000 |
LGSTORE2 | 348.39 | Yes | Yes | 1805.20 | 1.00 | 157.89 | 0.00 | 20.72 | 20.72 | 9.5842 | 6.19 | 4.3000 |
SMSTORE5 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 9.6995 | 6.19 | 4.3000 |
SMSTORE6 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 9.6995 | 6.19 | 4.3000 |
SMSTORE7 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 9.6995 | 6.19 | 4.3000 |
SMSTORE8 | 174.19 | Yes | Yes | 902.60 | 1.00 | 197.36 | 0.00 | 10.36 | 10.36 | 9.6995 | 6.19 | 4.3000 |
Total | 2090.32 | 10831.20 | 1184.15 | 0.00 | 124.40 | 124.40 | 13.0683 | 6.19 | 4.3000 | |||
Conditioned Total | 2090.32 | 10831.20 | 1184.15 | 0.00 | 124.40 | 124.40 | 13.0683 | 6.19 | 4.3000 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
LGSTORE1 | 348.39 | Yes | Yes | 1.00 | LGSTORE1 | GENERAL | LGSTORE1 | 15.3022 | 6.19 | 4.3000 | |
SMSTORE1 | 174.19 | Yes | Yes | 1.00 | SMSTORE1 | GENERAL | SMSTORE1 | 18.2890 | 6.19 | 4.3000 | |
SMSTORE2 | 174.19 | Yes | Yes | 1.00 | SMSTORE2 | GENERAL | SMSTORE2 | 16.6533 | 6.19 | 4.3000 | |
SMSTORE3 | 174.19 | Yes | Yes | 1.00 | SMSTORE3 | GENERAL | SMSTORE3 | 16.6533 | 6.19 | 4.3000 | |
SMSTORE4 | 174.19 | Yes | Yes | 1.00 | SMSTORE4 | GENERAL | SMSTORE4 | 16.6533 | 6.19 | 4.3000 | |
LGSTORE2 | 348.39 | Yes | Yes | 1.00 | LGSTORE2 | GENERAL | LGSTORE2 | 9.5842 | 6.19 | 4.3000 | |
SMSTORE5 | 174.19 | Yes | Yes | 1.00 | SMSTORE5 | GENERAL | SMSTORE5 | 9.6995 | 6.19 | 4.3000 | |
SMSTORE6 | 174.19 | Yes | Yes | 1.00 | SMSTORE6 | GENERAL | SMSTORE6 | 9.6995 | 6.19 | 4.3000 | |
SMSTORE7 | 174.19 | Yes | Yes | 1.00 | SMSTORE7 | GENERAL | SMSTORE7 | 9.6995 | 6.19 | 4.3000 | |
SMSTORE8 | 174.19 | Yes | Yes | 1.00 | SMSTORE8 | GENERAL | SMSTORE8 | 9.6995 | 6.19 | 4.3000 | |
Total | 2090.32 | 13.0683 | 3.10 | 4.3000 | |||||||
Conditioned Total | 2090.32 | 13.0683 | 3.10 | 4.3000 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 2090.32 | 2090.32 | 0.00 | 0.00 | 13.0683 | 6.19 | 4.3000 |
Total | 2090.32 | 2090.32 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:25
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 27-JUL-15:50 | 04-FEB-08:09 | - | - | - | - | - | - | - | - | - | - | 06-JAN-13:09 |
Heating | 0.00 | 44481.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 57940.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 23459.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 8059.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 8676.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 7522.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 105657.08 | 44481.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 44481.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 57940.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 23459.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 8059.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 8676.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 7522.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:25
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 0.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1429.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1161.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 190.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 405.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 324.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 186.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 3697.29 | 0.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 683.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 555.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 91.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 194.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 155.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 89.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1768.77 | 0.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 683.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 555.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 91.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 194.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 155.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 89.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1768.77 | 0.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:25
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
LGSTORE1 DIRECT AIR | 2.17 |
SMSTORE1 DIRECT AIR | 1.12 |
SMSTORE2 DIRECT AIR | 1.12 |
SMSTORE3 DIRECT AIR | 1.13 |
SMSTORE4 DIRECT AIR | 1.12 |
LGSTORE2 DIRECT AIR | 1.96 |
SMSTORE5 DIRECT AIR | 1.03 |
SMSTORE6 DIRECT AIR | 1.02 |
SMSTORE7 DIRECT AIR | 1.03 |
SMSTORE8 DIRECT AIR | 1.21 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC_1:1 | 2.17 | 2.17 | 2.17 | 2.17 | 2.17 | 2.17 | 1.00 | 1.00 | 2.17 |
PSZ-AC_2:2 | 1.12 | 1.12 | 1.12 | 1.12 | 1.12 | 1.12 | 1.00 | 1.00 | 1.12 |
PSZ-AC_3:3 | 1.12 | 1.12 | 1.12 | 1.12 | 1.12 | 1.12 | 1.00 | 1.00 | 1.12 |
PSZ-AC_4:4 | 1.13 | 1.13 | 1.13 | 1.13 | 1.13 | 1.13 | 1.00 | 1.00 | 1.13 |
PSZ-AC_5:5 | 1.12 | 1.12 | 1.12 | 1.12 | 1.12 | 1.12 | 1.00 | 1.000000 | 1.12 |
PSZ-AC_6:6 | 1.96 | 1.96 | 1.96 | 1.96 | 1.96 | 1.96 | 1.00 | 1.00 | 1.96 |
PSZ-AC_7:7 | 1.03 | 1.03 | 1.03 | 1.03 | 1.03 | 1.03 | 1.00 | 1.00 | 1.03 |
PSZ-AC_8:8 | 1.02 | 1.02 | 1.02 | 1.02 | 1.02 | 1.02 | 1.00 | 1.00 | 1.02 |
PSZ-AC_9:9 | 1.03 | 1.03 | 1.03 | 1.03 | 1.03 | 1.03 | 1.00 | 0.999962 | 1.03 |
PSZ-AC_10:10 | 1.21 | 1.21 | 1.21 | 1.21 | 1.21 | 1.21 | 1.00 | 1.00 | 1.21 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC_1:1_OA_CONTROLLER | 2.17 | 0.411479 |
PSZ-AC_2:2_OA_CONTROLLER | 1.12 | 0.205739 |
PSZ-AC_3:3_OA_CONTROLLER | 1.12 | 0.205739 |
PSZ-AC_4:4_OA_CONTROLLER | 1.13 | 0.205739 |
PSZ-AC_5:5_OA_CONTROLLER | 1.12 | 0.205739 |
PSZ-AC_6:6_OA_CONTROLLER | 1.96 | 0.411479 |
PSZ-AC_7:7_OA_CONTROLLER | 1.03 | 0.205739 |
PSZ-AC_8:8_OA_CONTROLLER | 1.02 | 0.205739 |
PSZ-AC_9:9_OA_CONTROLLER | 1.03 | 0.205739 |
PSZ-AC_10:10_OA_CONTROLLER | 1.21 | 0.205739 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | 2.17 | 2318.52 |
PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | 1.12 | 1242.56 |
PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | 1.12 | 1244.63 |
PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | 1.13 | 1248.09 |
PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | 1.12 | 1237.33 |
PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | 1.96 | 2098.30 |
PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | 1.03 | 1137.84 |
PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | 1.02 | 1133.10 |
PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | 1.03 | 1137.94 |
PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | 1.21 | 1343.49 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC_1:1_UNITARY_PACKAGE_DX | 2.17 | 2.17 | 2.17 | 1.43 | 53805.53 | 55640.09 | 40.00 | 1.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_DX | 1.12 | 1.12 | 1.12 | 0.740714 | 27869.24 | 28708.62 | 40.00 | 1.00 |
PSZ-AC_3:3_UNITARY_PACKAGE_DX | 1.12 | 1.12 | 1.12 | 0.741952 | 27915.79 | 28751.42 | 40.00 | 1.00 |
PSZ-AC_4:4_UNITARY_PACKAGE_DX | 1.13 | 1.13 | 1.13 | 0.744012 | 27993.32 | 28822.69 | 40.00 | 1.00 |
PSZ-AC_5:5_UNITARY_PACKAGE_DX | 1.12 | 1.12 | 1.12 | 0.737599 | 27752.04 | 28600.86 | 40.00 | 1.00 |
PSZ-AC_6:6_UNITARY_PACKAGE_DX | 1.96 | 1.96 | 1.96 | 1.29 | 48694.78 | 50941.17 | 40.00 | 1.00 |
PSZ-AC_7:7_UNITARY_PACKAGE_DX | 1.03 | 1.03 | 1.03 | 0.678290 | 25520.53 | 26549.21 | 40.00 | 1.00 |
PSZ-AC_8:8_UNITARY_PACKAGE_DX | 1.02 | 1.02 | 1.02 | 0.675462 | 25414.15 | 26451.41 | 40.00 | 1.00 |
PSZ-AC_9:9_UNITARY_PACKAGE_DX | 1.03 | 1.03 | 1.03 | 0.678346 | 25522.66 | 26550.29 | 40.00 | 1.00 |
PSZ-AC_10:10_UNITARY_PACKAGE_DX | 1.21 | 1.21 | 1.21 | 0.800883 | 30133.09 | 30790.14 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-AC_1:1 COOLING COIL | 2.17 | 1.08 | 1.44 | 53805.53 | 26902.76 | 0.701080 | 0.701080 |
PSZ-AC_2:2 COOLING COIL | 1.12 | 0.561147 | 0.748193 | 27869.24 | 13934.62 | 0.701080 | 0.701080 |
PSZ-AC_3:3 COOLING COIL | 1.12 | 0.562085 | 0.749447 | 27915.79 | 13957.90 | 0.701080 | 0.701080 |
PSZ-AC_4:4 COOLING COIL | 1.13 | 0.563645 | 0.751527 | 27993.32 | 13996.66 | 0.701080 | 0.701080 |
PSZ-AC_5:5 COOLING COIL | 1.12 | 0.558787 | 0.745047 | 27752.04 | 13876.02 | 0.701080 | 0.701080 |
PSZ-AC_6:6 COOLING COIL | 1.96 | 0.980469 | 1.31 | 48694.78 | 24347.39 | 0.701080 | 0.701080 |
PSZ-AC_7:7 COOLING COIL | 1.03 | 0.513856 | 0.685140 | 25520.53 | 12760.26 | 0.701080 | 0.701080 |
PSZ-AC_8:8 COOLING COIL | 1.02 | 0.511714 | 0.682287 | 25414.15 | 12707.08 | 0.701080 | 0.701080 |
PSZ-AC_9:9 COOLING COIL | 1.03 | 0.513899 | 0.685200 | 25522.66 | 12761.33 | 0.701080 | 0.701080 |
PSZ-AC_10:10 COOLING COIL | 1.21 | 0.606730 | 0.808973 | 30133.09 | 15066.55 | 0.701080 | 0.701080 |
Design Size Nominal Capacity [W] | |
PSZ-AC_1:1 HEATING COIL | 55640.09 |
PSZ-AC_2:2 HEATING COIL | 28708.62 |
PSZ-AC_3:3 HEATING COIL | 28751.42 |
PSZ-AC_4:4 HEATING COIL | 28822.69 |
PSZ-AC_5:5 HEATING COIL | 28600.86 |
PSZ-AC_6:6 HEATING COIL | 50941.17 |
PSZ-AC_7:7 HEATING COIL | 26549.21 |
PSZ-AC_8:8 HEATING COIL | 26451.41 |
PSZ-AC_9:9 HEATING COIL | 26550.29 |
PSZ-AC_10:10 HEATING COIL | 30790.14 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:25
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
LGSTORE1_WALL_3 | LGSTORE1_WALL_3_DOOR_1 | LGSTORE1_WALL_3_DOOR_2 | |
LGSTORE1_WALL_1 | LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | |
SMSTORE1_WALL_1 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | |
SMSTORE1_WALL_3 | SMSTORE1_WALL_3_DOOR | |
SMSTORE2_WALL_1 | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | |
SMSTORE2_WALL_3 | SMSTORE2_WALL_3_DOOR | |
SMSTORE3_WALL_1 | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | |
SMSTORE3_WALL_3 | SMSTORE3_WALL_3_DOOR | |
SMSTORE4_WALL_1 | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | |
SMSTORE4_WALL_3 | SMSTORE4_WALL_3_DOOR | |
LGSTORE2_WALL_3 | LGSTORE2_WALL_3_DOOR_1 | LGSTORE2_WALL_3_DOOR_2 | |
LGSTORE2_WALL_1 | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | |
SMSTORE5_WALL_1 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | |
SMSTORE5_WALL_3 | SMSTORE5_WALL_3_DOOR | |
SMSTORE6_WALL_1 | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | |
SMSTORE6_WALL_3 | SMSTORE6_WALL_3_DOOR | |
SMSTORE7_WALL_1 | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | |
SMSTORE7_WALL_3 | SMSTORE7_WALL_3_DOOR | |
SMSTORE8_WALL_1 | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR | |
SMSTORE8_WALL_3 | SMSTORE8_WALL_3_DOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:25
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:25
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 26.30 | 23.60 | 20.30 | 19.40 | 20.90 | 21.60 | 24.10 | 26.40 | 27.70 | 28.10 | 28.00 | 27.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Miami Intl Ap FL USA TMY3 WMO#=722020 | 25.82 | -80.30 | -5.00 | 11.00 | 101193 | 1.2027 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 24.49 | 8.70 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RetailStripmall | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 10 | 118 | 48 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | LGSTORE1 | 0.0 | 0.00 | 0.00 | 0.00 | 7.62 | 11.43 | 2.59 | 1 | 1 | 1 | 0.00 | 15.24 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 1805.20 | TARP | TARP | 348.39 | 276.30 | 247.74 | 20.77 | 6 | 8 | 0 | Yes |
2 | SMSTORE1 | 0.0 | 0.00 | 0.00 | 0.00 | 19.05 | 11.43 | 2.59 | 1 | 1 | 1 | 15.24 | 22.86 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.66 | 10.38 | 6 | 4 | 0 | Yes |
3 | SMSTORE2 | 0.0 | 0.00 | 0.00 | 0.00 | 26.67 | 11.43 | 2.59 | 1 | 1 | 1 | 22.86 | 30.48 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
4 | SMSTORE3 | 0.0 | 0.00 | 0.00 | 0.00 | 34.29 | 11.43 | 2.59 | 1 | 1 | 1 | 30.48 | 38.10 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
5 | SMSTORE4 | 0.0 | 0.00 | 0.00 | 0.00 | 41.91 | 11.43 | 2.59 | 1 | 1 | 1 | 38.10 | 45.72 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
6 | LGSTORE2 | 0.0 | 0.00 | 0.00 | 0.00 | 53.34 | 11.43 | 2.59 | 1 | 1 | 1 | 45.72 | 60.96 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 1805.20 | TARP | TARP | 348.39 | 157.89 | 129.41 | 20.72 | 6 | 8 | 0 | Yes |
7 | SMSTORE5 | 0.0 | 0.00 | 0.00 | 0.00 | 64.77 | 11.43 | 2.59 | 1 | 1 | 1 | 60.96 | 68.58 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
8 | SMSTORE6 | 0.0 | 0.00 | 0.00 | 0.00 | 72.39 | 11.43 | 2.59 | 1 | 1 | 1 | 68.58 | 76.20 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
9 | SMSTORE7 | 0.0 | 0.00 | 0.00 | 0.00 | 80.01 | 11.43 | 2.59 | 1 | 1 | 1 | 76.20 | 83.82 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
10 | SMSTORE8 | 0.0 | 0.00 | 0.00 | 0.00 | 87.63 | 11.43 | 2.59 | 1 | 1 | 1 | 83.82 | 91.44 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 197.36 | 183.12 | 10.36 | 6 | 4 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | LGSTORE1 | 348.39 | 56.3 | 6.193 | 0.161 | 15.302 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 19.602 | No |
2 | SMSTORE1 | 174.19 | 28.1 | 6.194 | 0.161 | 18.289 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 22.589 | No |
3 | SMSTORE2 | 174.19 | 28.1 | 6.194 | 0.161 | 16.653 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 20.953 | No |
4 | SMSTORE3 | 174.19 | 28.1 | 6.194 | 0.161 | 16.653 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 20.953 | No |
5 | SMSTORE4 | 174.19 | 28.1 | 6.194 | 0.161 | 16.653 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 20.953 | No |
6 | LGSTORE2 | 348.39 | 56.3 | 6.193 | 0.161 | 9.584 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 13.884 | No |
7 | SMSTORE5 | 174.19 | 28.1 | 6.194 | 0.161 | 9.699 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 13.999 | No |
8 | SMSTORE6 | 174.19 | 28.1 | 6.194 | 0.161 | 9.699 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 13.999 | No |
9 | SMSTORE7 | 174.19 | 28.1 | 6.194 | 0.161 | 9.699 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 13.999 | No |
10 | SMSTORE8 | 174.19 | 28.1 | 6.194 | 0.161 | 9.699 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 13.999 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | LGSTORE1 | TYPE1_OCC_SCH | LGSTORE1 | 348.39 | 56.3 | 56.3 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 56 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | SMSTORE1 | TYPE1_OCC_SCH | SMSTORE1 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | SMSTORE2 | TYPE2_OCC_SCH | SMSTORE2 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | SMSTORE3 | TYPE2_OCC_SCH | SMSTORE3 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | SMSTORE4 | TYPE2_OCC_SCH | SMSTORE4 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | LGSTORE2 | TYPE3_OCC_SCH | LGSTORE2 | 348.39 | 56.3 | 56.3 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 56 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | SMSTORE5 | TYPE3_OCC_SCH | SMSTORE5 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | SMSTORE6 | TYPE3_OCC_SCH | SMSTORE6 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | SMSTORE7 | TYPE3_OCC_SCH | SMSTORE7 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | SMSTORE8 | TYPE3_OCC_SCH | SMSTORE8 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | LGSTORE1_LIGHTS | LTG_SCH_BASE_LPD1 | LGSTORE1 | 348.39 | 56.3 | 3346.345 | 9.605 | 59.490 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3346.345 |
2 | LGSTORE1_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | LGSTORE1 | 348.39 | 56.3 | 1984.726 | 5.697 | 35.284 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1984.726 |
3 | SMSTORE1_LIGHTS | LTG_SCH_BASE_SMALL_LPD1 | SMSTORE1 | 174.19 | 28.1 | 1693.257 | 9.721 | 60.206 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1693.257 |
4 | SMSTORE1_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | SMSTORE1 | 174.19 | 28.1 | 1492.567 | 8.568 | 53.070 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1492.567 |
5 | SMSTORE2_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE2 | 174.19 | 28.1 | 1689.582 | 9.699 | 60.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1689.582 |
6 | SMSTORE2_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE2 | 174.19 | 28.1 | 1211.319 | 6.954 | 43.070 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1211.319 |
7 | SMSTORE3_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE3 | 174.19 | 28.1 | 1689.582 | 9.699 | 60.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1689.582 |
8 | SMSTORE3_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE3 | 174.19 | 28.1 | 1211.319 | 6.954 | 43.070 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1211.319 |
9 | SMSTORE4_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE4 | 174.19 | 28.1 | 1689.582 | 9.699 | 60.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1689.582 |
10 | SMSTORE4_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE4 | 174.19 | 28.1 | 1211.319 | 6.954 | 43.070 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1211.319 |
11 | LGSTORE2_LIGHTS | LTG_SCH_BASE_LPD2 | LGSTORE2 | 348.39 | 56.3 | 3338.998 | 9.584 | 59.359 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3338.998 |
12 | LGSTORE2_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | LGSTORE2 | 348.39 | 56.3 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
13 | SMSTORE5_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE5 | 174.19 | 28.1 | 1689.582 | 9.699 | 60.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1689.582 |
14 | SMSTORE5_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE5 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
15 | SMSTORE6_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE6 | 174.19 | 28.1 | 1689.582 | 9.699 | 60.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1689.582 |
16 | SMSTORE6_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE6 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
17 | SMSTORE7_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE7 | 174.19 | 28.1 | 1689.582 | 9.699 | 60.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1689.582 |
18 | SMSTORE7_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE7 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
19 | SMSTORE8_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE8 | 174.19 | 28.1 | 1689.582 | 9.699 | 60.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1689.582 |
20 | SMSTORE8_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE8 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LGSTORE1_MISCPLUG_EQUIP | TYPE1_EQUIP_SCH | LGSTORE1 | 348.39 | 56.3 | 1498.062 | 4.300 | 26.632 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1498.062 |
2 | SMSTORE1_MISCPLUG_EQUIP | TYPE1_EQUIP_SCH | SMSTORE1 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
3 | SMSTORE2_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE2 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
4 | SMSTORE3_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE3 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
5 | SMSTORE4_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE4 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
6 | LGSTORE2_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | LGSTORE2 | 348.39 | 56.3 | 1498.062 | 4.300 | 26.632 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1498.062 |
7 | SMSTORE5_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE5 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
8 | SMSTORE6_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE6 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
9 | SMSTORE7_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE7 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
10 | SMSTORE8_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE8 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.2832 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
5 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 1.028 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
6 | LGSTORE1_FLOOR_FFACTOR | 36 | 2 | 7 | 0.167 | 0.1995 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
7 | SMSTORE1_FLOOR_FFACTOR | 37 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
8 | SMSTORE2_FLOOR_FFACTOR | 38 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | SMSTORE3_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
10 | SMSTORE4_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
11 | LGSTORE2_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | SMSTORE5_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | SMSTORE6_FLOOR_FFACTOR | 43 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | SMSTORE7_FLOOR_FFACTOR | 44 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | SMSTORE8_FLOOR_FFACTOR | 45 | 2 | 7 | 0.167 | 0.2888 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
6 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 3.472 |
7 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
8 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
10 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7383 |
11 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
12 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.937 |
13 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
14 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
15 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
16 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
17 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
18 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
19 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
20 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
21 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
22 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
23 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
24 | ~FC_Insulation_7 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_8 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_9 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_10 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.386 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
14 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
15 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
16 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
17 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
18 | 3 | -0.61927053E-06 | 0.12767249E-08 | -0.37968499E-05 | 0.16832131E-17 |
19 | 2 | 0.77611055 | 0.17315568E-02 | 1.0534842 | -0.72792597E-06 |
20 | 1 | -21.915918 | 0.11588205 | -6.3286394 | 0.20197014 |
21 | 0 | 21.365777 | 0.10835518 | 5.5011278 | |
22 | 7 | -0.27626373E-12 | 0.13670118E-14 | -0.80430638E-13 | 0.78416590E-16 |
23 | 6 | 0.25658824E-07 | 0.27941242E-09 | 0.59030768E-08 | -0.11909973E-12 |
24 | 5 | -0.17468948E-03 | 0.24402707E-05 | -0.90039107E-04 | 0.58437388E-08 |
25 | 4 | 0.27392503 | 0.12091412E-02 | 0.93138911E-01 | -0.31018751E-04 |
26 | 3 | -6.9050330 | 0.38055846E-01 | -2.2317352 | 0.27239655E-01 |
27 | 2 | 39.679098 | 0.13717309 | 14.824430 | -0.32006664 |
28 | 1 | -79.631803 | 0.62641324E-01 | -28.746304 | 1.0591428 |
29 | 0 | 46.824345 | 0.12749544E-02 | 16.300917 | |
30 | 7 | -0.21163652E-08 | -0.68723841E-15 | 0.43910983E-14 | -0.57684426E-16 |
31 | 6 | 0.56109385E-05 | 0.38186281E-08 | 0.31898696E-02 | -0.26759299E-04 |
32 | 5 | -0.40164657E-03 | 0.22608617E-05 | -0.22372456 | 0.19561502E-02 |
33 | 4 | 0.92272104E-02 | 0.10289840E-03 | 4.8295456 | -0.45264980E-01 |
34 | 3 | -0.80993241E-01 | 0.81813938E-03 | -38.021416 | 0.39865375 |
35 | 2 | 0.28754352 | 0.13608947E-02 | 116.48395 | -1.4179393 |
36 | 1 | -0.41499682 | 0.41453381E-03 | -143.90731 | 2.0490399 |
37 | 0 | 0.20232414 | 0.10048102E-04 | 60.838472 | |
38 | 7 | -0.37862368E-08 | -0.38757603E-14 | 0.11479940E-14 | -0.41635801E-16 |
39 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
40 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
41 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
42 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
43 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
44 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
45 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
46 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479937E-14 | -0.41635796E-16 |
47 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
48 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
49 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
50 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
51 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
52 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
53 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
54 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479940E-14 | -0.41635801E-16 |
55 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
56 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
57 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
58 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
59 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
60 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
61 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
62 | 7 | -0.37862368E-08 | -0.38757603E-14 | 0.11479940E-14 | -0.41635801E-16 |
63 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
64 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
65 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
66 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
67 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
68 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
69 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
70 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479937E-14 | -0.41635796E-16 |
71 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
72 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
73 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
74 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
75 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
76 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
77 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
78 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479937E-14 | -0.41635796E-16 |
79 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
80 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
81 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
82 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
83 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
84 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
85 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
86 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479940E-14 | -0.41635801E-16 |
87 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
88 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
89 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
90 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
91 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
92 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
93 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
94 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479936E-14 | -0.41635794E-16 |
95 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
96 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
97 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
98 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
99 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
100 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
101 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
102 | 7 | -0.14484255E-08 | -0.22640907E-15 | 0.11860658E-13 | -0.17473455E-15 |
103 | 6 | 0.80640390E-05 | 0.55493782E-08 | 0.31828288E-02 | -0.26700235E-04 |
104 | 5 | -0.58275339E-03 | 0.32892043E-05 | -0.22332434 | 0.19526176E-02 |
105 | 4 | 0.13421983E-01 | 0.14977251E-03 | 4.8228790 | -0.45200897E-01 |
106 | 3 | -0.11791368 | 0.11914425E-02 | -37.983753 | 0.39823745 |
107 | 2 | 0.41875064 | 0.19825898E-02 | 116.41064 | -1.4169588 |
108 | 1 | -0.60444169 | 0.60433957E-03 | -143.86415 | 2.0483306 |
109 | 0 | 0.29470347 | 0.14596444E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.503_SHGC_0.23 | 35 | 1 | VerySmooth | 2.860 | 2.860 | 1.000 | 0.231 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 1.93472E-002 | 0.14129 | 0.63061 | 0.63061 | 0.25300 | 0.16079 | 0.23715 | 0.00000 | 0.84000 | 0.84000 | 0.10783 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | GAS TANK1 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
2 | WaterHeater:Mixed | GAS TANK2 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
3 | WaterHeater:Mixed | GAS TANK3 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
4 | WaterHeater:Mixed | GAS TANK4 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
5 | WaterHeater:Mixed | GAS TANK5 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
6 | WaterHeater:Mixed | GAS TANK6 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
7 | WaterHeater:Mixed | GAS TANK7 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | LGSTORE1_WALL_2 | 0 | 118.41 | 56.08 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
2 | LGSTORE1_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
3 | LGSTORE1_WALL_3_DOOR_1 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
4 | LGSTORE1_WALL_3_DOOR_2 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
5 | LGSTORE1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
6 | LGSTORE1_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
7 | LGSTORE1_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
8 | LGSTORE1_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
9 | LGSTORE1_WALL_1_WINDOW_3 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
10 | LGSTORE1_WALL_1_WINDOW_4 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
11 | LGSTORE1_WALL_1_DOOR_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 1 | No | No |
12 | LGSTORE1_WALL_1_DOOR_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 1 | No | No |
13 | LGSTORE1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
14 | LGSTORE1_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
15 | LGSTORE1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
16 | SMSTORE1_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
17 | SMSTORE1_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
18 | SMSTORE1_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
19 | SMSTORE1_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
20 | SMSTORE1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
21 | SMSTORE1_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
22 | SMSTORE1_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
23 | SMSTORE1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
24 | SMSTORE1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
25 | SMSTORE1_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
26 | SMSTORE1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
27 | SMSTORE2_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
28 | SMSTORE2_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
29 | SMSTORE2_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
30 | SMSTORE2_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
31 | SMSTORE2_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
32 | SMSTORE2_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
33 | SMSTORE2_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
34 | SMSTORE2_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
35 | SMSTORE2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
36 | SMSTORE2_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
37 | SMSTORE2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
38 | SMSTORE3_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
39 | SMSTORE3_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
40 | SMSTORE3_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
41 | SMSTORE3_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
42 | SMSTORE3_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
43 | SMSTORE3_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
44 | SMSTORE3_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
45 | SMSTORE3_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
46 | SMSTORE3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
47 | SMSTORE3_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
48 | SMSTORE3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
49 | SMSTORE4_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
50 | SMSTORE4_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
51 | SMSTORE4_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
52 | SMSTORE4_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
53 | SMSTORE4_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
54 | SMSTORE4_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 3 | No | No |
55 | SMSTORE4_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
56 | SMSTORE4_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
57 | SMSTORE4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
58 | SMSTORE4_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
59 | SMSTORE4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
60 | LGSTORE2_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
61 | LGSTORE2_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 4 | No | No |
62 | LGSTORE2_WALL_3_DOOR_1 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
63 | LGSTORE2_WALL_3_DOOR_2 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
64 | LGSTORE2_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
65 | LGSTORE2_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 4 | No | No |
66 | LGSTORE2_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
67 | LGSTORE2_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
68 | LGSTORE2_WALL_1_WINDOW_3 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
69 | LGSTORE2_WALL_1_WINDOW_4 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
70 | LGSTORE2_WALL_1_DOOR_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
71 | LGSTORE2_WALL_1_DOOR_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
72 | LGSTORE2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
73 | LGSTORE2_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
74 | LGSTORE2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
75 | SMSTORE5_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
76 | SMSTORE5_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
77 | SMSTORE5_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
78 | SMSTORE5_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
79 | SMSTORE5_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
80 | SMSTORE5_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
81 | SMSTORE5_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
82 | SMSTORE5_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
83 | SMSTORE5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
84 | SMSTORE5_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
85 | SMSTORE5_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
86 | SMSTORE6_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
87 | SMSTORE6_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
88 | SMSTORE6_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
89 | SMSTORE6_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
90 | SMSTORE6_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
91 | SMSTORE6_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
92 | SMSTORE6_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
93 | SMSTORE6_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
94 | SMSTORE6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
95 | SMSTORE6_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
96 | SMSTORE6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
97 | SMSTORE7_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
98 | SMSTORE7_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
99 | SMSTORE7_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
100 | SMSTORE7_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
101 | SMSTORE7_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
102 | SMSTORE7_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 3 | No | No |
103 | SMSTORE7_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
104 | SMSTORE7_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
105 | SMSTORE7_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
106 | SMSTORE7_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
107 | SMSTORE7_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
108 | SMSTORE8_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 4 | No | No |
109 | SMSTORE8_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 2 | No | No |
110 | SMSTORE8_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 2 | No | No |
111 | SMSTORE8_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 1 | No | No |
112 | SMSTORE8_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
113 | SMSTORE8_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 3 | No | No |
114 | SMSTORE8_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
115 | SMSTORE8_WALL_4 | 0 | 118.41 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 3 | No | No |
116 | SMSTORE8_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
117 | SMSTORE8_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
118 | SMSTORE8_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | LGSTORE1_INFILTRATION | TYPE1_INFIL_SCH | LGSTORE1 | 348.39 | 56.3 | 0.157 | 4.517E-004 | 2.488E-004 | 0.314 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | LGSTORE1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LGSTORE1 | 348.39 | 56.3 | 0.389 | 1.116E-003 | 6.149E-004 | 0.776 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | SMSTORE1_INFILTRATION | TYPE1_INFIL_SCH | SMSTORE1 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | SMSTORE1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE1 | 174.19 | 28.1 | 0.222 | 1.276E-003 | 8.648E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | SMSTORE2_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE2 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | SMSTORE2_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE2 | 174.19 | 28.1 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | SMSTORE3_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE3 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | SMSTORE3_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE3 | 174.19 | 28.1 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | SMSTORE4_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE4 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | SMSTORE4_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE4 | 174.19 | 28.1 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | LGSTORE2_INFILTRATION | TYPE3_INFIL_SCH | LGSTORE2 | 348.39 | 56.3 | 8.993E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | LGSTORE2_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LGSTORE2 | 348.39 | 56.3 | 0.389 | 1.116E-003 | 7.565E-004 | 0.776 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | SMSTORE5_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE5 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | SMSTORE5_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE5 | 174.19 | 28.1 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | SMSTORE6_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE6 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | SMSTORE6_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE6 | 174.19 | 28.1 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | SMSTORE7_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE7 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
18 | SMSTORE7_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE7 | 174.19 | 28.1 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | SMSTORE8_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE8 | 174.19 | 28.1 | 0.112 | 6.453E-004 | 2.994E-004 | 0.448 | 0.000 | 0.000 | 0.224 | 0.000 |
20 | SMSTORE8_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE8 | 174.19 | 28.1 | 0.222 | 1.276E-003 | 5.921E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | LGSTORE1 | Mixing/Well-Stirred |
2 | SMSTORE1 | Mixing/Well-Stirred |
3 | SMSTORE2 | Mixing/Well-Stirred |
4 | SMSTORE3 | Mixing/Well-Stirred |
5 | SMSTORE4 | Mixing/Well-Stirred |
6 | LGSTORE2 | Mixing/Well-Stirred |
7 | SMSTORE5 | Mixing/Well-Stirred |
8 | SMSTORE6 | Mixing/Well-Stirred |
9 | SMSTORE7 | Mixing/Well-Stirred |
10 | SMSTORE8 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone LGSTORE1 | 1.2000 |
3 | Zone SMSTORE1 | 1.2000 |
4 | Zone SMSTORE2 | 1.2000 |
5 | Zone SMSTORE3 | 1.2000 |
6 | Zone SMSTORE4 | 1.2000 |
7 | Zone LGSTORE2 | 1.2000 |
8 | Zone SMSTORE5 | 1.2000 |
9 | Zone SMSTORE6 | 1.2000 |
10 | Zone SMSTORE7 | 1.2000 |
11 | Zone SMSTORE8 | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone LGSTORE1 | 1.2000 |
3 | Zone SMSTORE1 | 1.2000 |
4 | Zone SMSTORE2 | 1.2000 |
5 | Zone SMSTORE3 | 1.2000 |
6 | Zone SMSTORE4 | 1.2000 |
7 | Zone LGSTORE2 | 1.2000 |
8 | Zone SMSTORE5 | 1.2000 |
9 | Zone SMSTORE6 | 1.2000 |
10 | Zone SMSTORE7 | 1.2000 |
11 | Zone SMSTORE8 | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | LGSTORE1 | Cooling | 24562.66101 | 29475.19321 | 1.80562 | 2.16675 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 32.93200 | 1.71667E-002 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
2 | LGSTORE1 | Heating | 13355.70940 | 16026.85128 | 0.57646 | 0.69176 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 8.70000 | 6.99286E-003 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
3 | SMSTORE1 | Cooling | 12722.49215 | 15266.99058 | 0.93525 | 1.12229 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 33.14417 | 1.71671E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
4 | SMSTORE1 | Heating | 6466.34186 | 7759.61023 | 0.27910 | 0.33492 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 8.70000 | 6.99286E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
5 | SMSTORE2 | Cooling | 12743.89717 | 15292.67660 | 0.93681 | 1.12417 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 33.08833 | 1.71670E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
6 | SMSTORE2 | Heating | 6529.76388 | 7835.71665 | 0.28184 | 0.33821 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 8.70000 | 6.99286E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
7 | SMSTORE3 | Cooling | 12779.28675 | 15335.14410 | 0.93941 | 1.12729 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 33.08833 | 1.71670E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
8 | SMSTORE3 | Heating | 6591.19860 | 7909.43832 | 0.28449 | 0.34139 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 8.70000 | 6.99286E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
9 | SMSTORE4 | Cooling | 12669.15229 | 15202.98275 | 0.93131 | 1.11757 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 33.08833 | 1.71670E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
10 | SMSTORE4 | Heating | 6727.14658 | 8072.57590 | 0.29036 | 0.34843 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 8.70000 | 6.99286E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
11 | LGSTORE2 | Cooling | 22230.65573 | 26676.78688 | 1.63412 | 1.96094 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 33.08833 | 1.71670E-002 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
12 | LGSTORE2 | Heating | 12765.02079 | 15318.02494 | 0.55097 | 0.66116 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 8.70000 | 6.99286E-003 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
13 | SMSTORE5 | Cooling | 11650.84057 | 13981.00869 | 0.85643 | 1.02771 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 33.03250 | 1.71669E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
14 | SMSTORE5 | Heating | 6897.48479 | 8276.98175 | 0.29771 | 0.35725 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 8.70000 | 6.99286E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
15 | SMSTORE6 | Cooling | 11602.28009 | 13922.73611 | 0.85286 | 1.02343 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 33.03250 | 1.71669E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
16 | SMSTORE6 | Heating | 6902.17670 | 8282.61204 | 0.29791 | 0.35750 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 8.70000 | 6.99286E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
17 | SMSTORE7 | Cooling | 11651.94414 | 13982.33296 | 0.85647 | 1.02776 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 32.97667 | 1.71668E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
18 | SMSTORE7 | Heating | 7133.46885 | 8560.16262 | 0.30790 | 0.36948 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 8.70000 | 6.99286E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
19 | SMSTORE8 | Cooling | 13758.45118 | 16510.14142 | 1.01122 | 1.21346 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | 32.86500 | 1.71666E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
20 | SMSTORE8 | Heating | 8625.65913 | 10350.79095 | 0.37230 | 0.44676 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 8.70000 | 6.99286E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC_1:1 | Cooling | Sensible | 33586.22 | 2.16675 | 2.16675 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-AC_1:1 | Heating | Sensible | 21964.65 | 0.69176 | 0.69176 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
3 | PSZ-AC_2:2 | Cooling | Sensible | 17345.27 | 1.12229 | 1.12229 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-AC_2:2 | Heating | Sensible | 10732.21 | 0.33492 | 0.33492 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
5 | PSZ-AC_3:3 | Cooling | Sensible | 17363.90 | 1.12417 | 1.12417 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
6 | PSZ-AC_3:3 | Heating | Sensible | 10807.21 | 0.33821 | 0.33821 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
7 | PSZ-AC_4:4 | Cooling | Sensible | 17404.30 | 1.12729 | 1.12729 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
8 | PSZ-AC_4:4 | Heating | Sensible | 10879.86 | 0.34139 | 0.34139 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
9 | PSZ-AC_5:5 | Cooling | Sensible | 17274.74 | 1.11757 | 1.11757 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
10 | PSZ-AC_5:5 | Heating | Sensible | 11040.62 | 0.34843 | 0.34843 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
11 | PSZ-AC_6:6 | Cooling | Sensible | 30880.55 | 1.96094 | 1.96094 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
12 | PSZ-AC_6:6 | Heating | Sensible | 21266.18 | 0.66116 | 0.66116 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
13 | PSZ-AC_7:7 | Cooling | Sensible | 16068.57 | 1.02771 | 1.02771 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
14 | PSZ-AC_7:7 | Heating | Sensible | 11242.04 | 0.35725 | 0.35725 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
15 | PSZ-AC_8:8 | Cooling | Sensible | 16010.86 | 1.02343 | 1.02343 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
16 | PSZ-AC_8:8 | Heating | Sensible | 11247.59 | 0.35750 | 0.35750 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
17 | PSZ-AC_9:9 | Cooling | Sensible | 16064.14 | 1.02780 | 1.02780 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
18 | PSZ-AC_9:9 | Heating | Sensible | 11521.10 | 0.36948 | 0.36948 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
19 | PSZ-AC_10:10 | Cooling | Sensible | 18488.08 | 1.21346 | 1.21346 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
20 | PSZ-AC_10:10 | Heating | Sensible | 13285.62 | 0.44676 | 0.44676 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | LGSTORE1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.16675 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.12229 |
3 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.12417 |
4 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.12729 |
5 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE4 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.11757 |
6 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | LGSTORE2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.96094 |
7 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE5 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.02771 |
8 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.02343 |
9 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE7 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.02776 |
10 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE8 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.21346 |
11 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.16675 |
12 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.16675 |
13 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.16675 |
14 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 2.16675 |
15 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.16675 |
16 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Main Design Air Flow Rate [m3/s] | 2.16675 |
17 | AirLoopHVAC | PSZ-AC_1:1 | User Heating Air Flow Ratio [] | 1.00000 |
18 | AirLoopHVAC | PSZ-AC_1:1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
19 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.12229 |
20 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.12229 |
21 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.12229 |
22 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.12229 |
23 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.12229 |
24 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Main Design Air Flow Rate [m3/s] | 1.12229 |
25 | AirLoopHVAC | PSZ-AC_2:2 | User Heating Air Flow Ratio [] | 1.00000 |
26 | AirLoopHVAC | PSZ-AC_2:2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
27 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.12417 |
28 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.12417 |
29 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.12417 |
30 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.12417 |
31 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.12417 |
32 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Main Design Air Flow Rate [m3/s] | 1.12417 |
33 | AirLoopHVAC | PSZ-AC_3:3 | User Heating Air Flow Ratio [] | 1.00000 |
34 | AirLoopHVAC | PSZ-AC_3:3 | Calculated Heating Air Flow Ratio [] | 1.00000 |
35 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.12729 |
36 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.12729 |
37 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.12729 |
38 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.12729 |
39 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.12729 |
40 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Main Design Air Flow Rate [m3/s] | 1.12729 |
41 | AirLoopHVAC | PSZ-AC_4:4 | User Heating Air Flow Ratio [] | 1.00000 |
42 | AirLoopHVAC | PSZ-AC_4:4 | Calculated Heating Air Flow Ratio [] | 1.00000 |
43 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.11757 |
44 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.11757 |
45 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.11757 |
46 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.11757 |
47 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.11757 |
48 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Main Design Air Flow Rate [m3/s] | 1.11757 |
49 | AirLoopHVAC | PSZ-AC_5:5 | User Heating Air Flow Ratio [] | 1.00000 |
50 | AirLoopHVAC | PSZ-AC_5:5 | Calculated Heating Air Flow Ratio [] | 1.00000 |
51 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.96094 |
52 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.96094 |
53 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.96094 |
54 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.96094 |
55 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.96094 |
56 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Main Design Air Flow Rate [m3/s] | 1.96094 |
57 | AirLoopHVAC | PSZ-AC_6:6 | User Heating Air Flow Ratio [] | 1.00000 |
58 | AirLoopHVAC | PSZ-AC_6:6 | Calculated Heating Air Flow Ratio [] | 1.00000 |
59 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.02771 |
60 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.02771 |
61 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.02771 |
62 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.02771 |
63 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.02771 |
64 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Main Design Air Flow Rate [m3/s] | 1.02771 |
65 | AirLoopHVAC | PSZ-AC_7:7 | User Heating Air Flow Ratio [] | 1.00000 |
66 | AirLoopHVAC | PSZ-AC_7:7 | Calculated Heating Air Flow Ratio [] | 1.00000 |
67 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.02343 |
68 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.02343 |
69 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.02343 |
70 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.02343 |
71 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.02343 |
72 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Main Design Air Flow Rate [m3/s] | 1.02343 |
73 | AirLoopHVAC | PSZ-AC_8:8 | User Heating Air Flow Ratio [] | 1.00000 |
74 | AirLoopHVAC | PSZ-AC_8:8 | Calculated Heating Air Flow Ratio [] | 1.00000 |
75 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.02776 |
76 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.02776 |
77 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.02776 |
78 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.02776 |
79 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.02780 |
80 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Main Design Air Flow Rate [m3/s] | 1.02780 |
81 | AirLoopHVAC | PSZ-AC_9:9 | User Heating Air Flow Ratio [] | 1.00000 |
82 | AirLoopHVAC | PSZ-AC_9:9 | Calculated Heating Air Flow Ratio [] | 0.99996 |
83 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.21346 |
84 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.21346 |
85 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.21346 |
86 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.21346 |
87 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.21346 |
88 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Main Design Air Flow Rate [m3/s] | 1.21346 |
89 | AirLoopHVAC | PSZ-AC_10:10 | User Heating Air Flow Ratio [] | 1.00000 |
90 | AirLoopHVAC | PSZ-AC_10:10 | Calculated Heating Air Flow Ratio [] | 1.00000 |
91 | AirLoopHVAC | PSZ-AC_1:1 | Design Supply Air Flow Rate [m3/s] | 2.16675 |
92 | AirLoopHVAC | PSZ-AC_2:2 | Design Supply Air Flow Rate [m3/s] | 1.12229 |
93 | AirLoopHVAC | PSZ-AC_3:3 | Design Supply Air Flow Rate [m3/s] | 1.12417 |
94 | AirLoopHVAC | PSZ-AC_4:4 | Design Supply Air Flow Rate [m3/s] | 1.12729 |
95 | AirLoopHVAC | PSZ-AC_5:5 | Design Supply Air Flow Rate [m3/s] | 1.11757 |
96 | AirLoopHVAC | PSZ-AC_6:6 | Design Supply Air Flow Rate [m3/s] | 1.96094 |
97 | AirLoopHVAC | PSZ-AC_7:7 | Design Supply Air Flow Rate [m3/s] | 1.02771 |
98 | AirLoopHVAC | PSZ-AC_8:8 | Design Supply Air Flow Rate [m3/s] | 1.02343 |
99 | AirLoopHVAC | PSZ-AC_9:9 | Design Supply Air Flow Rate [m3/s] | 1.02780 |
100 | AirLoopHVAC | PSZ-AC_10:10 | Design Supply Air Flow Rate [m3/s] | 1.21346 |
101 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.16675 |
102 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41148 |
103 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.16675 |
104 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 2318.52339 |
105 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.16675 |
106 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.16675 |
107 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.16675 |
108 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.43005 |
109 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.16675 |
110 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.08337 |
111 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.44450 |
112 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 53805.53000 |
113 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 26902.76500 |
114 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
115 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
116 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 53805.53000 |
117 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 55640.09087 |
118 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
119 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
120 | Coil:Heating:Fuel | PSZ-AC_1:1 HEATING COIL | Design Size Nominal Capacity [W] | 55640.09087 |
121 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.12229 |
122 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
123 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.12229 |
124 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1242.55807 |
125 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.12229 |
126 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.12229 |
127 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.12229 |
128 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.74071 |
129 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.12229 |
130 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.56115 |
131 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.74819 |
132 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 27869.24000 |
133 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 13934.62000 |
134 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
135 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
136 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 27869.24000 |
137 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 28708.61599 |
138 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
139 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
140 | Coil:Heating:Fuel | PSZ-AC_2:2 HEATING COIL | Design Size Nominal Capacity [W] | 28708.61599 |
141 | Controller:OutdoorAir | PSZ-AC_3:3_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.12417 |
142 | Controller:OutdoorAir | PSZ-AC_3:3_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
143 | Fan:SystemModel | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.12417 |
144 | Fan:SystemModel | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1244.63356 |
145 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.12417 |
146 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.12417 |
147 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.12417 |
148 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.74195 |
149 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.12417 |
150 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.56208 |
151 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.74945 |
152 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 27915.79000 |
153 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 13957.89500 |
154 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
155 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
156 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 27915.79000 |
157 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 28751.41536 |
158 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
159 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
160 | Coil:Heating:Fuel | PSZ-AC_3:3 HEATING COIL | Design Size Nominal Capacity [W] | 28751.41536 |
161 | Controller:OutdoorAir | PSZ-AC_4:4_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.12729 |
162 | Controller:OutdoorAir | PSZ-AC_4:4_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
163 | Fan:SystemModel | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.12729 |
164 | Fan:SystemModel | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1248.09008 |
165 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.12729 |
166 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.12729 |
167 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.12729 |
168 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.74401 |
169 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.12729 |
170 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.56365 |
171 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.75153 |
172 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 27993.32000 |
173 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 13996.66000 |
174 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
175 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
176 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 27993.32000 |
177 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 28822.69281 |
178 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
179 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
180 | Coil:Heating:Fuel | PSZ-AC_4:4 HEATING COIL | Design Size Nominal Capacity [W] | 28822.69281 |
181 | Controller:OutdoorAir | PSZ-AC_5:5_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.11757 |
182 | Controller:OutdoorAir | PSZ-AC_5:5_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
183 | Fan:SystemModel | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.11757 |
184 | Fan:SystemModel | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1237.33267 |
185 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.11757 |
186 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.11757 |
187 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.11757 |
188 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.73760 |
189 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.11757 |
190 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.55879 |
191 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.74505 |
192 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 27752.04000 |
193 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 13876.02000 |
194 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
195 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
196 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 27752.04000 |
197 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 28600.86062 |
198 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
199 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
200 | Coil:Heating:Fuel | PSZ-AC_5:5 HEATING COIL | Design Size Nominal Capacity [W] | 28600.86062 |
201 | Controller:OutdoorAir | PSZ-AC_6:6_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.96094 |
202 | Controller:OutdoorAir | PSZ-AC_6:6_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41148 |
203 | Fan:SystemModel | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.96094 |
204 | Fan:SystemModel | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 2098.29723 |
205 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.96094 |
206 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.96094 |
207 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.96094 |
208 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.29422 |
209 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.96094 |
210 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.98047 |
211 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.30729 |
212 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 48694.78000 |
213 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 24347.39000 |
214 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
215 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
216 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 48694.78000 |
217 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 50941.16820 |
218 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
219 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
220 | Coil:Heating:Fuel | PSZ-AC_6:6 HEATING COIL | Design Size Nominal Capacity [W] | 50941.16820 |
221 | Controller:OutdoorAir | PSZ-AC_7:7_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.02771 |
222 | Controller:OutdoorAir | PSZ-AC_7:7_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
223 | Fan:SystemModel | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.02771 |
224 | Fan:SystemModel | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1137.83995 |
225 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.02771 |
226 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.02771 |
227 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.02771 |
228 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.67829 |
229 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.02771 |
230 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.51386 |
231 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.68514 |
232 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 25520.53000 |
233 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 12760.26500 |
234 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
235 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
236 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 25520.53000 |
237 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 26549.21276 |
238 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
239 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
240 | Coil:Heating:Fuel | PSZ-AC_7:7 HEATING COIL | Design Size Nominal Capacity [W] | 26549.21276 |
241 | Controller:OutdoorAir | PSZ-AC_8:8_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.02343 |
242 | Controller:OutdoorAir | PSZ-AC_8:8_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
243 | Fan:SystemModel | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.02343 |
244 | Fan:SystemModel | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1133.09709 |
245 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.02343 |
246 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.02343 |
247 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.02343 |
248 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.67546 |
249 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.02343 |
250 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.51171 |
251 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.68229 |
252 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 25414.15000 |
253 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 12707.07500 |
254 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
255 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
256 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 25414.15000 |
257 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 26451.40894 |
258 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
259 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
260 | Coil:Heating:Fuel | PSZ-AC_8:8 HEATING COIL | Design Size Nominal Capacity [W] | 26451.40894 |
261 | Controller:OutdoorAir | PSZ-AC_9:9_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.02780 |
262 | Controller:OutdoorAir | PSZ-AC_9:9_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
263 | Fan:SystemModel | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.02780 |
264 | Fan:SystemModel | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1137.93509 |
265 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.02780 |
266 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.02780 |
267 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.02780 |
268 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.67835 |
269 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.02780 |
270 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.51390 |
271 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.68520 |
272 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 25522.66000 |
273 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 12761.33000 |
274 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
275 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
276 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 25522.66000 |
277 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 26550.28971 |
278 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
279 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
280 | Coil:Heating:Fuel | PSZ-AC_9:9 HEATING COIL | Design Size Nominal Capacity [W] | 26550.28971 |
281 | Controller:OutdoorAir | PSZ-AC_10:10_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.21346 |
282 | Controller:OutdoorAir | PSZ-AC_10:10_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
283 | Fan:SystemModel | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.21346 |
284 | Fan:SystemModel | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1343.49253 |
285 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.21346 |
286 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.21346 |
287 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.21346 |
288 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.80088 |
289 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.21346 |
290 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.60673 |
291 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.80897 |
292 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 30133.09000 |
293 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 15066.54500 |
294 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
295 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
296 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 30133.09000 |
297 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 30790.13950 |
298 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
299 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
300 | Coil:Heating:Fuel | PSZ-AC_10:10 HEATING COIL | Design Size Nominal Capacity [W] | 30790.13950 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | 52096.2 | 11.77 | 11.77 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | 26983.9 | 11.95 | 11.95 | |||
3 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | 27028.9 | 11.95 | 11.95 | |||
4 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | 27104.0 | 11.95 | 11.95 | |||
5 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | 26870.4 | 11.95 | 11.95 | |||
6 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | 47147.8 | 11.77 | 11.77 | |||
7 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | 24709.8 | 11.95 | 11.95 | |||
8 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | 24606.8 | 11.95 | 11.95 | |||
9 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | 24711.8 | 11.95 | 11.95 | |||
10 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | 29175.8 | 11.95 | 11.95 |
Zone Name | # Surfaces | |
1 | LGSTORE1 | 15 |
2 | SMSTORE1 | 11 |
3 | SMSTORE2 | 11 |
4 | SMSTORE3 | 11 |
5 | SMSTORE4 | 11 |
6 | LGSTORE2 | 15 |
7 | SMSTORE5 | 11 |
8 | SMSTORE6 | 11 |
9 | SMSTORE7 | 11 |
10 | SMSTORE8 | 11 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | LGSTORE1_WALL_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | LGSTORE1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 71.15 | 78.94 | 71.15 | 0.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | LGSTORE1_WALL_3_DOOR_1 | Door | LGSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
4 | LGSTORE1_WALL_3_DOOR_2 | Door | LGSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
5 | LGSTORE1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
6 | LGSTORE1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 58.18 | 78.94 | 58.18 | 180.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
7 | LGSTORE1_WALL_1_WINDOW_1 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.23 | N/A | 2.860 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
8 | LGSTORE1_WALL_1_WINDOW_2 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.23 | N/A | 2.860 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
9 | LGSTORE1_WALL_1_WINDOW_3 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.23 | N/A | 2.860 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
10 | LGSTORE1_WALL_1_WINDOW_4 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.23 | N/A | 2.860 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
11 | LGSTORE1_WALL_1_DOOR_1 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.23 | N/A | 2.860 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
12 | LGSTORE1_WALL_1_DOOR_2 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.23 | N/A | 2.860 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
13 | LGSTORE1_FLOOR | Floor | CTF - ConductionTransferFunction | LGSTORE1_FLOOR_FFACTOR | 0.199 | 0.190 | 348.39 | 348.39 | 348.39 | 270.00 | 180.00 | 22.86 | 15.24 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | LGSTORE1_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 348.39 | 348.39 | 348.39 | 270.00 | 0.00 | 22.86 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
15 | LGSTORE1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 696.77 | 696.77 | 696.77 | 0.00 | 90.00 | 696.77 | 1.00 | 0.00 | LGSTORE1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
16 | SMSTORE1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 29.09 | 39.47 | 29.09 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
17 | SMSTORE1_WALL_1_WINDOW_1 | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.23 | N/A | 2.860 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
18 | SMSTORE1_WALL_1_WINDOW_2 | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.23 | N/A | 2.860 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
19 | SMSTORE1_WALL_1_DOOR | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.23 | N/A | 2.860 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
20 | SMSTORE1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | SMSTORE1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 35.57 | 39.47 | 35.57 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | SMSTORE1_WALL_3_DOOR | Door | SMSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
23 | SMSTORE1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE2_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | SMSTORE1_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE1_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | SMSTORE1_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
26 | SMSTORE1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
27 | SMSTORE2_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | SMSTORE2_WALL_1_WINDOW_1 | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.23 | N/A | 2.860 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
29 | SMSTORE2_WALL_1_WINDOW_2 | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.23 | N/A | 2.860 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
30 | SMSTORE2_WALL_1_DOOR | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.23 | N/A | 2.860 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
31 | SMSTORE2_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | SMSTORE2_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | SMSTORE2_WALL_3_DOOR | Door | SMSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
34 | SMSTORE2_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE3_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | SMSTORE2_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE2_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | SMSTORE2_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | SMSTORE2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | SMSTORE3_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | SMSTORE3_WALL_1_WINDOW_1 | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.23 | N/A | 2.860 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
40 | SMSTORE3_WALL_1_WINDOW_2 | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.23 | N/A | 2.860 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
41 | SMSTORE3_WALL_1_DOOR | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.23 | N/A | 2.860 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
42 | SMSTORE3_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE2_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | SMSTORE3_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | SMSTORE3_WALL_3_DOOR | Door | SMSTORE3_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
45 | SMSTORE3_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE4_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | SMSTORE3_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE3_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
47 | SMSTORE3_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
48 | SMSTORE3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
49 | SMSTORE4_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | SMSTORE4_WALL_1_WINDOW_1 | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.23 | N/A | 2.860 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
51 | SMSTORE4_WALL_1_WINDOW_2 | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.23 | N/A | 2.860 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
52 | SMSTORE4_WALL_1_DOOR | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.23 | N/A | 2.860 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | SMSTORE4_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE3_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | SMSTORE4_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | SMSTORE4_WALL_3_DOOR | Door | SMSTORE4_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | SMSTORE4_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE2_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | SMSTORE4_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE4_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | SMSTORE4_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | SMSTORE4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | LGSTORE2_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE4_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | LGSTORE2_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 71.19 | 78.94 | 71.19 | 0.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
62 | LGSTORE2_WALL_3_DOOR_1 | Door | LGSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
63 | LGSTORE2_WALL_3_DOOR_2 | Door | LGSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
64 | LGSTORE2_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE5_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LGSTORE2_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 58.22 | 78.94 | 58.22 | 180.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
66 | LGSTORE2_WALL_1_WINDOW_1 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.23 | N/A | 2.860 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | LGSTORE2_WALL_1_WINDOW_2 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.23 | N/A | 2.860 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | LGSTORE2_WALL_1_WINDOW_3 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.23 | N/A | 2.860 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | LGSTORE2_WALL_1_WINDOW_4 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.23 | N/A | 2.860 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LGSTORE2_WALL_1_DOOR_1 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.23 | N/A | 2.860 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
71 | LGSTORE2_WALL_1_DOOR_2 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.23 | N/A | 2.860 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
72 | LGSTORE2_FLOOR | Floor | CTF - ConductionTransferFunction | LGSTORE2_FLOOR_FFACTOR | 0.112 | 0.109 | 348.39 | 348.39 | 348.39 | 270.00 | 180.00 | 22.86 | 15.24 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
73 | LGSTORE2_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 348.39 | 348.39 | 348.39 | 270.00 | 0.00 | 22.86 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
74 | LGSTORE2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 696.77 | 696.77 | 696.77 | 0.00 | 90.00 | 696.77 | 1.00 | 0.00 | LGSTORE2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
75 | SMSTORE5_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | SMSTORE5_WALL_1_WINDOW_1 | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.23 | N/A | 2.860 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
77 | SMSTORE5_WALL_1_WINDOW_2 | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.23 | N/A | 2.860 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | SMSTORE5_WALL_1_DOOR | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.23 | N/A | 2.860 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
79 | SMSTORE5_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE2_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | SMSTORE5_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 35.59 | 39.47 | 35.59 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | SMSTORE5_WALL_3_DOOR | Door | SMSTORE5_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
82 | SMSTORE5_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE6_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
83 | SMSTORE5_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE5_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
84 | SMSTORE5_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
85 | SMSTORE5_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE5_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | SMSTORE6_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | SMSTORE6_WALL_1_WINDOW_1 | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.23 | N/A | 2.860 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | SMSTORE6_WALL_1_WINDOW_2 | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.23 | N/A | 2.860 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
89 | SMSTORE6_WALL_1_DOOR | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.23 | N/A | 2.860 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | SMSTORE6_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE5_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | SMSTORE6_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | SMSTORE6_WALL_3_DOOR | Door | SMSTORE6_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
93 | SMSTORE6_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE7_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | SMSTORE6_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE6_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
95 | SMSTORE6_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
96 | SMSTORE6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
97 | SMSTORE7_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | SMSTORE7_WALL_1_WINDOW_1 | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.23 | N/A | 2.860 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | SMSTORE7_WALL_1_WINDOW_2 | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.23 | N/A | 2.860 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
100 | SMSTORE7_WALL_1_DOOR | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.23 | N/A | 2.860 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
101 | SMSTORE7_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE6_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
102 | SMSTORE7_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 35.59 | 39.47 | 35.59 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | SMSTORE7_WALL_3_DOOR | Door | SMSTORE7_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
104 | SMSTORE7_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE8_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | SMSTORE7_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE7_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
106 | SMSTORE7_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
107 | SMSTORE7_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE7_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
108 | SMSTORE8_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | SMSTORE8_WALL_1_WINDOW_1 | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.23 | N/A | 2.860 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
110 | SMSTORE8_WALL_1_WINDOW_2 | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.23 | N/A | 2.860 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
111 | SMSTORE8_WALL_1_DOOR | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.23 | N/A | 2.860 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
112 | SMSTORE8_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE7_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | SMSTORE8_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | SMSTORE8_WALL_3_DOOR | Door | SMSTORE8_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
115 | SMSTORE8_WALL_4 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | SMSTORE8_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE8_FLOOR_FFACTOR | 0.289 | 0.270 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | SMSTORE8_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | SMSTORE8_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE8_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | LGSTORE1 | RunPeriod: RUNPERIOD 1 | 2.2218613913E-002 | 8.3968727334E-002 | Pass | Pass | 4.0491236859E-002 | 0.1489848296 | Pass | Pass |
2 | SMSTORE1 | RunPeriod: RUNPERIOD 1 | 2.5079220551E-002 | 0.1142048474 | Pass | Pass | 3.8312229416E-002 | 0.1520369071 | Pass | Pass |
3 | SMSTORE2 | RunPeriod: RUNPERIOD 1 | 3.6761425263E-002 | 0.1431360963 | Pass | Pass | 0.3417008397 | 2.9776592309 | Pass | Pass |
4 | SMSTORE3 | RunPeriod: RUNPERIOD 1 | 3.6705908962E-002 | 0.1425028532 | Pass | Pass | 0.3361584175 | 2.8847514951 | Pass | Pass |
5 | SMSTORE4 | RunPeriod: RUNPERIOD 1 | 3.5174718492E-002 | 0.1336269909 | Pass | Pass | 0.3677158232 | 2.7938043980 | Pass | Pass |
6 | LGSTORE2 | RunPeriod: RUNPERIOD 1 | 3.4485670557E-002 | 0.1302534159 | Pass | Pass | 0.2961395040 | 2.7257684770 | Pass | Pass |
7 | SMSTORE5 | RunPeriod: RUNPERIOD 1 | 3.2774023037E-002 | 0.1264273731 | Pass | Pass | 0.2960149510 | 2.2303062604 | Pass | Pass |
8 | SMSTORE6 | RunPeriod: RUNPERIOD 1 | 3.2463390480E-002 | 0.1241957716 | Pass | Pass | 0.2839727470 | 2.1569574481 | Pass | Pass |
9 | SMSTORE7 | RunPeriod: RUNPERIOD 1 | 3.1368722607E-002 | 0.1167664038 | Pass | Pass | 0.2671477027 | 2.0486285386 | Pass | Pass |
10 | SMSTORE8 | RunPeriod: RUNPERIOD 1 | 3.6290669570E-002 | 0.1152158870 | Pass | Pass | 0.5695043420 | 3.6955851796 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:25
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 3062.57 | -307.8 | 0.00 | -685.2 | 2317.39 | 4386.96 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:25
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 8.70 | 0.00 | 8.70 | Wetbulb [C] | 3.80 | 340.00 |
MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 33.20 | 6.70 | 25.30 | Wetbulb [C] | 4.50 | 140.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 65.00 | 29 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 38.00 | 14 | |||
May | 0.00 | 0 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 391.00 | 83 | |||
Sep | 0.00 | 0 | |||
Oct | 225.00 | 40 | |||
Nov | 0.00 | 0 | |||
Dec | 5.00 | 10 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:25
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_2 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE1_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 78.94 | 71.15 | 0.00 | 90.00 | N |
LGSTORE1_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 78.94 | 58.18 | 180.00 | 90.00 | S |
LGSTORE1_FLOOR | LGSTORE1_FLOOR_FFACTOR | 1.00 | 0.193 | 0.199 | 348.39 | 348.39 | 270.00 | 180.00 | |
LGSTORE1_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 348.39 | 348.39 | 270.00 | 0.00 | |
SMSTORE1_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 39.47 | 29.09 | 180.00 | 90.00 | S |
SMSTORE1_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 39.47 | 35.57 | 0.00 | 90.00 | N |
SMSTORE1_FLOOR | SMSTORE1_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE1_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE2_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE2_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE2_FLOOR | SMSTORE2_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE2_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE3_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE3_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE3_FLOOR | SMSTORE3_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE3_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE4_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE4_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE4_FLOOR | SMSTORE4_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE4_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
LGSTORE2_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 78.94 | 71.19 | 0.00 | 90.00 | N |
LGSTORE2_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 78.94 | 58.22 | 180.00 | 90.00 | S |
LGSTORE2_FLOOR | LGSTORE2_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 348.39 | 348.39 | 270.00 | 180.00 | |
LGSTORE2_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 348.39 | 348.39 | 270.00 | 0.00 | |
SMSTORE5_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE5_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE5_FLOOR | SMSTORE5_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE5_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE6_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE6_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE6_FLOOR | SMSTORE6_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE6_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE7_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE7_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE7_FLOOR | SMSTORE7_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE7_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE8_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE8_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE8_WALL_4 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE8_FLOOR | SMSTORE8_FLOOR_FFACTOR | 1.00 | 0.276 | 0.289 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE8_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE1_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE2_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE2_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE3_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE3_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE4_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE4_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
LGSTORE2_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE2_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE5_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE5_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE6_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE6_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE7_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE7_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE8_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 696.77 | 0.00 | 90.00 | N | ||
SMSTORE1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
LGSTORE2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 696.77 | 0.00 | 90.00 | N | ||
SMSTORE5_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE7_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE8_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.503_SHGC_0.23 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.860 | 0.231 | 0.254 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.503_SHGC_0.23 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.860 | 0.231 | 0.254 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_3 | NONRESWINDOW_U_0.503_SHGC_0.23 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.860 | 0.231 | 0.254 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_4 | NONRESWINDOW_U_0.503_SHGC_0.23 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.860 | 0.231 | 0.254 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_DOOR_1 | NONRESWINDOW_U_0.503_SHGC_0.23 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.860 | 0.231 | 0.254 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_DOOR_2 | NONRESWINDOW_U_0.503_SHGC_0.23 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.860 | 0.231 | 0.254 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.503_SHGC_0.23 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.860 | 0.231 | 0.254 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.503_SHGC_0.23 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.860 | 0.231 | 0.254 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_DOOR | NONRESWINDOW_U_0.503_SHGC_0.23 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.860 | 0.231 | 0.254 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.503_SHGC_0.23 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.860 | 0.231 | 0.254 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.503_SHGC_0.23 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.860 | 0.231 | 0.254 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_DOOR | NONRESWINDOW_U_0.503_SHGC_0.23 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.860 | 0.231 | 0.254 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.503_SHGC_0.23 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.860 | 0.231 | 0.254 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.503_SHGC_0.23 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.860 | 0.231 | 0.254 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_DOOR | NONRESWINDOW_U_0.503_SHGC_0.23 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.860 | 0.231 | 0.254 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.503_SHGC_0.23 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.860 | 0.231 | 0.254 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.503_SHGC_0.23 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.860 | 0.231 | 0.254 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_DOOR | NONRESWINDOW_U_0.503_SHGC_0.23 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.860 | 0.231 | 0.254 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.503_SHGC_0.23 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.860 | 0.231 | 0.254 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.503_SHGC_0.23 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.860 | 0.231 | 0.254 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_3 | NONRESWINDOW_U_0.503_SHGC_0.23 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.860 | 0.231 | 0.254 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_4 | NONRESWINDOW_U_0.503_SHGC_0.23 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.860 | 0.231 | 0.254 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_DOOR_1 | NONRESWINDOW_U_0.503_SHGC_0.23 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.860 | 0.231 | 0.254 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_DOOR_2 | NONRESWINDOW_U_0.503_SHGC_0.23 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.860 | 0.231 | 0.254 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.503_SHGC_0.23 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.860 | 0.231 | 0.254 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.503_SHGC_0.23 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.860 | 0.231 | 0.254 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_DOOR | NONRESWINDOW_U_0.503_SHGC_0.23 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.860 | 0.231 | 0.254 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.503_SHGC_0.23 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.860 | 0.231 | 0.254 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.503_SHGC_0.23 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.860 | 0.231 | 0.254 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_DOOR | NONRESWINDOW_U_0.503_SHGC_0.23 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.860 | 0.231 | 0.254 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.503_SHGC_0.23 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.860 | 0.231 | 0.254 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.503_SHGC_0.23 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.860 | 0.231 | 0.254 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_DOOR | NONRESWINDOW_U_0.503_SHGC_0.23 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.860 | 0.231 | 0.254 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.503_SHGC_0.23 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.860 | 0.231 | 0.254 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.503_SHGC_0.23 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.860 | 0.231 | 0.254 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_DOOR | NONRESWINDOW_U_0.503_SHGC_0.23 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.860 | 0.231 | 0.254 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
Total or Average | 124.40 | 2.860 | 0.231 | 0.254 | |||||||||||||||||
North Total or Average | 0.00 | - | - | - | |||||||||||||||||
Non-North Total or Average | 124.40 | 2.860 | 0.231 | 0.254 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
LGSTORE1_WALL_3_DOOR_1 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.90 | LGSTORE1_WALL_3 |
LGSTORE1_WALL_3_DOOR_2 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.90 | LGSTORE1_WALL_3 |
SMSTORE1_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.90 | SMSTORE1_WALL_3 |
SMSTORE2_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE2_WALL_3 |
SMSTORE3_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE3_WALL_3 |
SMSTORE4_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE4_WALL_3 |
LGSTORE2_WALL_3_DOOR_1 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | LGSTORE2_WALL_3 |
LGSTORE2_WALL_3_DOOR_2 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | LGSTORE2_WALL_3 |
SMSTORE5_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE5_WALL_3 |
SMSTORE6_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE6_WALL_3 |
SMSTORE7_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE7_WALL_3 |
SMSTORE8_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE8_WALL_3 |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:25
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
LGSTORE1_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_4 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_DOOR_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_DOOR_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_4 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_DOOR_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_DOOR_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:25
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
LGSTORE1_LIGHTS | LGSTORE1 | LGSTORE1 | GENERAL | 9.6053 | 348.39 | 3346.35 | LightsWired | LTG_SCH_BASE_LPD1 | 83.91 | 168.00 | 82.62 | 0.0000 | Y | 51.90 |
LGSTORE1_LIGHTS_ALLOWANCE | LGSTORE1 | LGSTORE1 | GENERAL | 5.6969 | 348.39 | 1984.73 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | 97.50 | 112.00 | 94.53 | 0.0000 | Y | 35.22 |
SMSTORE1_LIGHTS | SMSTORE1 | SMSTORE1 | GENERAL | 9.7206 | 174.19 | 1693.26 | LightsWired | LTG_SCH_BASE_SMALL_LPD1 | 85.41 | 168.00 | 84.05 | 0.0000 | Y | 26.72 |
SMSTORE1_LIGHTS_ALLOWANCE | SMSTORE1 | SMSTORE1 | GENERAL | 8.5685 | 174.19 | 1492.57 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | 97.50 | 112.00 | 94.53 | 0.0000 | Y | 26.49 |
SMSTORE2_LIGHTS | SMSTORE2 | SMSTORE2 | GENERAL | 9.6995 | 174.19 | 1689.58 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 68.73 | 168.00 | 65.95 | 0.0000 | Y | 20.92 |
SMSTORE2_LIGHTS_ALLOWANCE | SMSTORE2 | SMSTORE2 | GENERAL | 6.9539 | 174.19 | 1211.32 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 84.29 | 73.25 | 0.0000 | Y | 16.66 |
SMSTORE3_LIGHTS | SMSTORE3 | SMSTORE3 | GENERAL | 9.6995 | 174.19 | 1689.58 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 68.73 | 168.00 | 65.95 | 0.0000 | Y | 20.92 |
SMSTORE3_LIGHTS_ALLOWANCE | SMSTORE3 | SMSTORE3 | GENERAL | 6.9539 | 174.19 | 1211.32 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 84.29 | 73.25 | 0.0000 | Y | 16.66 |
SMSTORE4_LIGHTS | SMSTORE4 | SMSTORE4 | GENERAL | 9.6995 | 174.19 | 1689.58 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 68.73 | 168.00 | 65.95 | 0.0000 | Y | 20.92 |
SMSTORE4_LIGHTS_ALLOWANCE | SMSTORE4 | SMSTORE4 | GENERAL | 6.9539 | 174.19 | 1211.32 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 84.29 | 73.25 | 0.0000 | Y | 16.66 |
LGSTORE2_LIGHTS | LGSTORE2 | LGSTORE2 | GENERAL | 9.5842 | 348.39 | 3339.00 | LightsWired | LTG_SCH_BASE_LPD2 | 62.11 | 168.00 | 59.29 | 0.0000 | Y | 37.16 |
LGSTORE2_LIGHTS_ALLOWANCE | LGSTORE2 | LGSTORE2 | GENERAL | 0.0000 | 348.39 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE5_LIGHTS | SMSTORE5 | SMSTORE5 | GENERAL | 9.6995 | 174.19 | 1689.58 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 60.29 | 0.0000 | Y | 19.12 |
SMSTORE5_LIGHTS_ALLOWANCE | SMSTORE5 | SMSTORE5 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE6_LIGHTS | SMSTORE6 | SMSTORE6 | GENERAL | 9.6995 | 174.19 | 1689.58 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 60.29 | 0.0000 | Y | 19.12 |
SMSTORE6_LIGHTS_ALLOWANCE | SMSTORE6 | SMSTORE6 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE7_LIGHTS | SMSTORE7 | SMSTORE7 | GENERAL | 9.6995 | 174.19 | 1689.58 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 60.29 | 0.0000 | Y | 19.12 |
SMSTORE7_LIGHTS_ALLOWANCE | SMSTORE7 | SMSTORE7 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE8_LIGHTS | SMSTORE8 | SMSTORE8 | GENERAL | 9.6995 | 174.19 | 1689.58 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 60.29 | 0.0000 | Y | 19.12 |
SMSTORE8_LIGHTS_ALLOWANCE | SMSTORE8 | SMSTORE8 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
Interior Lighting Total | 6.5342 | 4180.64 | 27316.92 | 366.68 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 455.59 | AstronomicalClock | - | 41.82 | 41.82 | 3.58 | |
EXTERIOR_LIGHTS_B | 2744.24 | AstronomicalClock | - | 83.82 | 62.82 | 32.36 | |
EXTERIOR_LIGHTS_C | 2307.23 | AstronomicalClock | - | 83.82 | 55.82 | 24.18 | |
Exterior Lighting Total | 5507.06 | 60.12 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:25
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 53805.53 | 37721.98 | 16083.55 | 0.70 | 3.73 | |||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 27869.24 | 19538.57 | 8330.67 | 0.70 | 3.80 | |||
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 27915.79 | 19571.20 | 8344.59 | 0.70 | 3.80 | |||
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 27993.32 | 19625.56 | 8367.76 | 0.70 | 3.80 | |||
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 27752.04 | 19456.40 | 8295.64 | 0.70 | 3.80 | |||
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 48694.78 | 34138.94 | 14555.84 | 0.70 | 3.73 | |||
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 25520.53 | 17891.93 | 7628.60 | 0.70 | 3.80 | |||
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 25414.15 | 17817.35 | 7596.80 | 0.70 | 3.80 | |||
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 25522.66 | 17893.43 | 7629.23 | 0.70 | 3.80 | |||
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 30133.09 | 21125.71 | 9007.38 | 0.70 | 3.80 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC_1:1 COOLING COIL | 52096.2 | 11.77 | 11.77 | ||||
PSZ-AC_2:2 COOLING COIL | 26983.9 | 11.95 | 11.95 | ||||
PSZ-AC_3:3 COOLING COIL | 27028.9 | 11.95 | 11.95 | ||||
PSZ-AC_4:4 COOLING COIL | 27104.0 | 11.95 | 11.95 | ||||
PSZ-AC_5:5 COOLING COIL | 26870.4 | 11.95 | 11.95 | ||||
PSZ-AC_6:6 COOLING COIL | 47147.8 | 11.77 | 11.77 | ||||
PSZ-AC_7:7 COOLING COIL | 24709.8 | 11.95 | 11.95 | ||||
PSZ-AC_8:8 COOLING COIL | 24606.8 | 11.95 | 11.95 | ||||
PSZ-AC_9:9 COOLING COIL | 24711.8 | 11.95 | 11.95 | ||||
PSZ-AC_10:10 COOLING COIL | 29175.8 | 11.95 | 11.95 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | 55640.09 | 0.80 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | 28708.62 | 0.80 | |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | 28751.42 | 0.80 | |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | 28822.69 | 0.80 | |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | 28600.86 | 0.80 | |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | 50941.17 | 0.80 | |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | 26549.21 | 0.80 | |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | 26451.41 | 0.80 | |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | 26550.29 | 0.80 | |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | 30790.14 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 2.17 | 2318.52 | 1070.05 | 1.00 | 1.30 | General | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.12 | 1242.56 | 1107.16 | 1.00 | 1.37 | General | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.12 | 1244.63 | 1107.16 | 1.00 | 1.37 | General | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.13 | 1248.09 | 1107.16 | 1.00 | 1.37 | General | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.12 | 1237.33 | 1107.16 | 1.00 | 1.38 | General | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 |
PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 1.96 | 2098.30 | 1070.05 | 1.00 | 1.32 | General | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.03 | 1137.84 | 1107.16 | 1.00 | 1.40 | General | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.02 | 1133.10 | 1107.16 | 1.00 | 1.40 | General | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.03 | 1137.94 | 1107.16 | 1.00 | 1.40 | General | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 |
PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.21 | 1343.49 | 1107.16 | 1.00 | 1.36 | General | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
GAS TANK1 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK2 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK3 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK4 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK5 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK6 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK7 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:25
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
LGSTORE1 | 24562.66 | 29475.19 | 84.60 | 1.806 | 2.167 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 23.89 | 23.88 | 0.01050 | 32.93 | 0.01717 | 0.411 | 0.00 |
SMSTORE1 | 12722.49 | 15266.99 | 87.64 | 0.935 | 1.122 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 23.89 | 23.88 | 0.01054 | 33.14 | 0.01717 | 0.206 | 0.00 |
SMSTORE2 | 12743.90 | 15292.68 | 87.79 | 0.937 | 1.124 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 23.89 | 23.88 | 0.01054 | 33.09 | 0.01717 | 0.206 | 0.00 |
SMSTORE3 | 12779.29 | 15335.14 | 88.04 | 0.939 | 1.127 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 23.89 | 23.88 | 0.01053 | 33.09 | 0.01717 | 0.206 | 0.00 |
SMSTORE4 | 12669.15 | 15202.98 | 87.28 | 0.931 | 1.118 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 23.89 | 23.88 | 0.01055 | 33.09 | 0.01717 | 0.206 | 0.00 |
LGSTORE2 | 22230.66 | 26676.79 | 76.57 | 1.634 | 1.961 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 23.89 | 23.88 | 0.01061 | 33.09 | 0.01717 | 0.411 | 0.00 |
SMSTORE5 | 11650.84 | 13981.01 | 80.26 | 0.856 | 1.028 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 23.89 | 23.88 | 0.01069 | 33.03 | 0.01717 | 0.206 | 0.00 |
SMSTORE6 | 11602.28 | 13922.74 | 79.93 | 0.853 | 1.023 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 23.89 | 23.88 | 0.01069 | 33.03 | 0.01717 | 0.206 | 0.00 |
SMSTORE7 | 11651.94 | 13982.33 | 80.27 | 0.856 | 1.028 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 23.89 | 23.88 | 0.01068 | 32.98 | 0.01717 | 0.206 | 0.00 |
SMSTORE8 | 13758.45 | 16510.14 | 94.78 | 1.011 | 1.213 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | 23.89 | 23.88 | 0.01051 | 32.87 | 0.01717 | 0.206 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
LGSTORE1 | 13355.71 | 16026.85 | 46.00 | 0.576 | 0.692 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00761 | 8.70 | 0.00699 | 0.411 | 0.00 |
SMSTORE1 | 6466.34 | 7759.61 | 44.55 | 0.279 | 0.335 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00758 | 8.70 | 0.00699 | 0.206 | 0.00 |
SMSTORE2 | 6529.76 | 7835.72 | 44.98 | 0.282 | 0.338 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00758 | 8.70 | 0.00699 | 0.206 | 0.00 |
SMSTORE3 | 6591.20 | 7909.44 | 45.41 | 0.284 | 0.341 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00759 | 8.70 | 0.00699 | 0.206 | 0.00 |
SMSTORE4 | 6727.15 | 8072.58 | 46.34 | 0.290 | 0.348 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00759 | 8.70 | 0.00699 | 0.206 | 0.00 |
LGSTORE2 | 12765.02 | 15318.02 | 43.97 | 0.551 | 0.661 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00761 | 8.70 | 0.00699 | 0.411 | 0.00 |
SMSTORE5 | 6897.48 | 8276.98 | 47.52 | 0.298 | 0.357 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00759 | 8.70 | 0.00699 | 0.206 | 0.00 |
SMSTORE6 | 6902.18 | 8282.61 | 47.55 | 0.298 | 0.357 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00760 | 8.70 | 0.00699 | 0.206 | 0.00 |
SMSTORE7 | 7133.47 | 8560.16 | 49.14 | 0.308 | 0.369 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00760 | 8.70 | 0.00699 | 0.206 | 0.00 |
SMSTORE8 | 8625.66 | 10350.79 | 59.42 | 0.372 | 0.447 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00762 | 8.70 | 0.00699 | 0.206 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC_1:1 | 2.17 | 2.17 | 0.69 | 0.69 | 2.1667 | 2.1667 | 2.1667 | 1.0000 | 1.0000 |
PSZ-AC_2:2 | 1.12 | 1.12 | 0.33 | 0.33 | 1.1223 | 1.1223 | 1.1223 | 1.0000 | 1.0000 |
PSZ-AC_3:3 | 1.12 | 1.12 | 0.34 | 0.34 | 1.1242 | 1.1242 | 1.1242 | 1.0000 | 1.0000 |
PSZ-AC_4:4 | 1.13 | 1.13 | 0.34 | 0.34 | 1.1273 | 1.1273 | 1.1273 | 1.0000 | 1.0000 |
PSZ-AC_5:5 | 1.12 | 1.12 | 0.35 | 0.35 | 1.1176 | 1.1176 | 1.1176 | 1.0000 | 1.0000 |
PSZ-AC_6:6 | 1.96 | 1.96 | 0.66 | 0.66 | 1.9609 | 1.9609 | 1.9609 | 1.0000 | 1.0000 |
PSZ-AC_7:7 | 1.03 | 1.03 | 0.36 | 0.36 | 1.0277 | 1.0277 | 1.0277 | 1.0000 | 1.0000 |
PSZ-AC_8:8 | 1.02 | 1.02 | 0.36 | 0.36 | 1.0234 | 1.0234 | 1.0234 | 1.0000 | 1.0000 |
PSZ-AC_9:9 | 1.03 | 1.03 | 0.37 | 0.37 | 1.0278 | 1.0278 | 1.0278 | 1.0000 | 1.0000 |
PSZ-AC_10:10 | 1.21 | 1.21 | 0.45 | 0.45 | 1.2135 | 1.2135 | 1.2135 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 53805.530 | 37721.981 | 2.166750 | -999.0 | -999.000 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 26902.76 | 17386.23 | 1.444500 | 26.52 | 19.84 | 0.01177307 | 12.80 | 12.09 | 0.00850000 | 33.20 | 0.01716721 | 25.32 | 28.4859 | 23.88 | 0.01050492 | 56.7048 | 24505.72 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_1:1 | 55640.091 | 55640.091 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 55640.09 | 55640.09 | 2.166749 | 18.75 | 13.50 | 0.00749140 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 18.9906 | 21.11 | 0.00760828 | 48.8288 | 13355.71 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 27869.240 | 19538.567 | 1.122290 | -999.0 | -999.000 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 13934.62 | 9013.32 | 0.748193 | 26.49 | 19.82 | 0.01175734 | 12.80 | 12.09 | 0.00850000 | 33.20 | 0.01716721 | 25.32 | 27.4982 | 23.88 | 0.01054273 | 56.9058 | 12720.20 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_2:2 | 28708.616 | 28708.616 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 28708.62 | 28708.62 | 1.122294 | 18.83 | 13.52 | 0.00747375 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 18.3320 | 21.11 | 0.00758169 | 48.6603 | 6466.34 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_3:3 | 27915.790 | 19571.202 | 1.124170 | -999.0 | -999.000 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 13957.90 | 9030.96 | 0.749447 | 26.48 | 19.82 | 0.01175425 | 12.80 | 12.09 | 0.00850000 | 33.20 | 0.01716721 | 25.32 | 27.4522 | 23.88 | 0.01054078 | 56.8954 | 12735.97 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_3:3 | 28751.415 | 28751.415 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 28751.42 | 28751.42 | 1.124169 | 18.84 | 13.52 | 0.00747565 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 18.3015 | 21.11 | 0.00758380 | 48.6736 | 6529.76 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_4:4 | 27993.320 | 19625.557 | 1.127290 | -999.0 | -999.000 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 13996.66 | 9061.81 | 0.751527 | 26.48 | 19.81 | 0.01174740 | 12.80 | 12.09 | 0.00850000 | 33.20 | 0.01716721 | 25.32 | 27.3762 | 23.88 | 0.01053638 | 56.8721 | 12770.17 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_4:4 | 28822.693 | 28822.693 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 28822.69 | 28822.69 | 1.127291 | 18.84 | 13.52 | 0.00747761 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 18.2508 | 21.11 | 0.00758583 | 48.6865 | 6591.20 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_5:5 | 27752.040 | 19456.400 | 1.117570 | -999.0 | -999.000 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 13876.02 | 8965.29 | 0.745047 | 26.49 | 19.83 | 0.01176951 | 12.80 | 12.09 | 0.00850000 | 33.20 | 0.01716721 | 25.32 | 27.6143 | 23.88 | 0.01055062 | 56.9476 | 12660.51 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_5:5 | 28600.861 | 28600.861 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 28600.86 | 28600.86 | 1.117575 | 18.82 | 13.52 | 0.00748054 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 18.4095 | 21.11 | 0.00759057 | 48.7166 | 6727.15 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_6:6 | 48694.780 | 34138.936 | 1.960940 | -999.0 | -999.000 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 24347.39 | 15445.14 | 1.307293 | 26.70 | 20.06 | 0.01198830 | 12.80 | 12.09 | 0.00850000 | 33.20 | 0.01716721 | 25.32 | 31.4756 | 23.88 | 0.01061183 | 57.2711 | 22215.73 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_6:6 | 50941.168 | 50941.168 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 50941.17 | 50941.17 | 1.960939 | 18.51 | 13.40 | 0.00748340 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 20.9838 | 21.11 | 0.00761367 | 48.8629 | 12765.02 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_7:7 | 25520.530 | 17891.933 | 1.027710 | -999.0 | -999.000 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 12760.26 | 8081.08 | 0.685140 | 26.65 | 20.04 | 0.01199066 | 12.80 | 12.09 | 0.00850000 | 33.20 | 0.01716721 | 25.32 | 30.0288 | 23.88 | 0.01069348 | 57.7055 | 11639.60 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_7:7 | 26549.213 | 26549.213 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 26549.21 | 26549.21 | 1.027712 | 18.63 | 13.43 | 0.00747442 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 20.0192 | 21.11 | 0.00759495 | 48.7444 | 6897.48 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_8:8 | 25414.150 | 17817.352 | 1.023430 | -999.0 | -999.000 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 12707.08 | 8039.35 | 0.682287 | 26.65 | 20.05 | 0.01200199 | 12.80 | 12.09 | 0.00850000 | 33.20 | 0.01716721 | 25.32 | 30.1544 | 23.88 | 0.01070082 | 57.7444 | 11590.74 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_8:8 | 26451.409 | 26451.409 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 26451.41 | 26451.41 | 1.023428 | 18.61 | 13.43 | 0.00747408 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 20.1030 | 21.11 | 0.00759516 | 48.7457 | 6902.18 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_9:9 | 25522.660 | 17893.426 | 1.027800 | -999.0 | -999.000 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 12761.33 | 8081.11 | 0.685200 | 26.65 | 20.04 | 0.01199156 | 12.80 | 12.09 | 0.00850000 | 33.20 | 0.01716721 | 25.32 | 30.0262 | 23.88 | 0.01069409 | 57.7087 | 11635.85 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_9:9 | 26550.290 | 26550.290 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 26550.29 | 26550.29 | 1.027798 | 18.63 | 13.44 | 0.00748040 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 20.0175 | 21.11 | 0.00760242 | 48.7918 | 7133.47 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_10:10 | 30133.090 | 21125.707 | 1.213460 | -999.0 | -999.000 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | 15066.55 | 9828.34 | 0.808973 | 26.30 | 19.68 | 0.01164086 | 12.80 | 12.09 | 0.00850000 | 32.87 | 0.01716657 | 25.24 | 25.4322 | 23.88 | 0.01051271 | 56.7471 | 13758.45 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_10:10 | 30790.140 | 30790.140 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 30790.14 | 30790.14 | 1.213460 | 19.01 | 13.62 | 0.00751177 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 16.9548 | 21.11 | 0.00761771 | 48.8891 | 8625.66 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:37:25
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 53805.530 | 37721.981 | 2.166750 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1026.7255 | 1004.8586 | 1.2027 | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.166749 | 2.60603286 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | Sensible | 26902.76 | 17386.23 | 1.0000 | 1.73735639 | 1.444500 | 26.52 | 19.84 | 0.01177307 | 56674.4 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 26902.76 | 33.20 | 0.01716721 | 25.32 | 0.41147883 | 28.4859 | 23.88 | 0.01050492 | 23.88 | 0.01050492 | 56.7048 | 24505.72 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 55640.091 | 55640.091 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.166749 | 2.60603286 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 55640.09 | 55640.09 | 1.0000 | 2.60603286 | 2.166749 | 18.75 | 13.50 | 0.00749140 | 37840.2 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 55640.09 | 8.70 | 0.00699286 | 8.70 | 0.41147883 | 18.9906 | 21.11 | 0.00760828 | 21.11 | 0.00760828 | 48.8288 | 13355.71 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 27869.240 | 19538.567 | 1.122290 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1026.6963 | 1004.8586 | 1.2027 | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.122294 | 1.34982719 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | Sensible | 13934.62 | 9013.32 | 1.0000 | 0.89988125 | 0.748193 | 26.49 | 19.82 | 0.01175734 | 56598.2 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 13934.62 | 33.20 | 0.01716721 | 25.32 | 0.20573941 | 27.4982 | 23.88 | 0.01054273 | 23.88 | 0.01054273 | 56.9058 | 12720.20 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 28708.616 | 28708.616 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.122294 | 1.34982719 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 28708.62 | 28708.62 | 1.0000 | 1.34982719 | 1.122294 | 18.83 | 13.52 | 0.00747375 | 37878.7 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28708.62 | 8.70 | 0.00699286 | 8.70 | 0.20573941 | 18.3320 | 21.11 | 0.00758169 | 21.11 | 0.00758169 | 48.6603 | 6466.34 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 27915.790 | 19571.202 | 1.124170 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1026.6906 | 1004.8586 | 1.2027 | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.124169 | 1.35208186 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | Sensible | 13957.90 | 9030.96 | 1.0000 | 0.90138869 | 0.749447 | 26.48 | 19.82 | 0.01175425 | 56588.2 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 13957.90 | 33.20 | 0.01716721 | 25.32 | 0.20573941 | 27.4522 | 23.88 | 0.01054078 | 23.88 | 0.01054078 | 56.8954 | 12735.97 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 28751.415 | 28751.415 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.124169 | 1.35208186 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 28751.42 | 28751.42 | 1.0000 | 1.35208186 | 1.124169 | 18.84 | 13.52 | 0.00747565 | 37887.4 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28751.42 | 8.70 | 0.00699286 | 8.70 | 0.20573941 | 18.3015 | 21.11 | 0.00758380 | 21.11 | 0.00758380 | 48.6736 | 6529.76 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 27993.320 | 19625.557 | 1.127290 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1026.6778 | 1004.8586 | 1.2027 | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.127291 | 1.35583677 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | Sensible | 13996.66 | 9061.81 | 1.0000 | 0.90389038 | 0.751527 | 26.48 | 19.81 | 0.01174740 | 56566.0 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 13996.66 | 33.20 | 0.01716721 | 25.32 | 0.20573941 | 27.3762 | 23.88 | 0.01053638 | 23.88 | 0.01053638 | 56.8721 | 12770.17 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 28822.693 | 28822.693 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.127291 | 1.35583677 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 28822.69 | 28822.69 | 1.0000 | 1.35583677 | 1.127291 | 18.84 | 13.52 | 0.00747761 | 37898.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28822.69 | 8.70 | 0.00699286 | 8.70 | 0.20573941 | 18.2508 | 21.11 | 0.00758583 | 21.11 | 0.00758583 | 48.6865 | 6591.20 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 27752.040 | 19456.400 | 1.117570 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1026.7189 | 1004.8586 | 1.2027 | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.117575 | 1.34415069 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | Sensible | 13876.02 | 8965.29 | 1.0000 | 0.89609663 | 0.745047 | 26.49 | 19.83 | 0.01176951 | 56637.5 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 13876.02 | 33.20 | 0.01716721 | 25.32 | 0.20573941 | 27.6143 | 23.88 | 0.01055062 | 23.88 | 0.01055062 | 56.9476 | 12660.51 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 28600.861 | 28600.861 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.117575 | 1.34415069 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 28600.86 | 28600.86 | 1.0000 | 1.34415069 | 1.117575 | 18.82 | 13.52 | 0.00748054 | 37886.1 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28600.86 | 8.70 | 0.00699286 | 8.70 | 0.20573941 | 18.4095 | 21.11 | 0.00759057 | 21.11 | 0.00759057 | 48.7166 | 6727.15 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 48694.780 | 34138.936 | 1.960940 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1027.1256 | 1004.8586 | 1.2027 | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.960939 | 2.35849746 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | Sensible | 24347.39 | 15445.14 | 1.0000 | 1.57233259 | 1.307293 | 26.70 | 20.06 | 0.01198830 | 57411.1 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 24347.39 | 33.20 | 0.01716721 | 25.32 | 0.41147883 | 31.4756 | 23.88 | 0.01061183 | 23.88 | 0.01061183 | 57.2711 | 22215.73 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 50941.168 | 50941.168 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.960939 | 2.35849746 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 50941.17 | 50941.17 | 1.0000 | 2.35849746 | 1.960939 | 18.51 | 13.40 | 0.00748340 | 37568.0 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 50941.17 | 8.70 | 0.00699286 | 8.70 | 0.41147883 | 20.9838 | 21.11 | 0.00761367 | 21.11 | 0.00761367 | 48.8629 | 12765.02 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 25520.530 | 17891.933 | 1.027710 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1027.1300 | 1004.8586 | 1.2027 | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.027712 | 1.23606884 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | Sensible | 12760.26 | 8081.08 | 1.0000 | 0.82404455 | 0.685140 | 26.65 | 20.04 | 0.01199066 | 57355.8 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 12760.26 | 33.20 | 0.01716721 | 25.32 | 0.20573941 | 30.0288 | 23.88 | 0.01069348 | 23.88 | 0.01069348 | 57.7055 | 11639.60 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 26549.213 | 26549.213 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.027712 | 1.23606884 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 26549.21 | 26549.21 | 1.0000 | 1.23606884 | 1.027712 | 18.63 | 13.43 | 0.00747442 | 37667.1 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 26549.21 | 8.70 | 0.00699286 | 8.70 | 0.20573941 | 20.0192 | 21.11 | 0.00759495 | 21.11 | 0.00759495 | 48.7444 | 6897.48 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 25414.150 | 17817.352 | 1.023430 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1027.1511 | 1004.8586 | 1.2027 | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.023428 | 1.23091653 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | Sensible | 12707.08 | 8039.35 | 1.0000 | 0.82061274 | 0.682287 | 26.65 | 20.05 | 0.01200199 | 57392.8 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 12707.08 | 33.20 | 0.01716721 | 25.32 | 0.20573941 | 30.1544 | 23.88 | 0.01070082 | 23.88 | 0.01070082 | 57.7444 | 11590.74 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 26451.409 | 26451.409 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.023428 | 1.23091653 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 26451.41 | 26451.41 | 1.0000 | 1.23091653 | 1.023428 | 18.61 | 13.43 | 0.00747408 | 37655.7 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 26451.41 | 8.70 | 0.00699286 | 8.70 | 0.20573941 | 20.1030 | 21.11 | 0.00759516 | 21.11 | 0.00759516 | 48.7457 | 6902.18 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 25522.660 | 17893.426 | 1.027800 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1027.1317 | 1004.8586 | 1.2027 | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.027798 | 1.23617219 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | Sensible | 12761.33 | 8081.11 | 1.0000 | 0.82411672 | 0.685200 | 26.65 | 20.04 | 0.01199156 | 57358.8 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 12761.33 | 33.20 | 0.01716721 | 25.32 | 0.20573941 | 30.0262 | 23.88 | 0.01069409 | 23.88 | 0.01069409 | 57.7087 | 11635.85 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 26550.290 | 26550.290 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.027798 | 1.23617219 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 26550.29 | 26550.29 | 1.0000 | 1.23617219 | 1.027798 | 18.63 | 13.44 | 0.00748040 | 37682.5 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 26550.29 | 8.70 | 0.00699286 | 8.70 | 0.20573941 | 20.0175 | 21.11 | 0.00760242 | 21.11 | 0.00760242 | 48.7918 | 7133.47 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 30133.090 | 21125.707 | 1.213460 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1026.4798 | 1004.8586 | 1.2027 | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.213460 | 1.45947524 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | Sensible | 15066.55 | 9828.34 | 1.0000 | 0.97298373 | 0.808973 | 26.30 | 19.68 | 0.01164086 | 56112.7 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 15066.55 | 32.87 | 0.01716657 | 25.24 | 0.20573941 | 25.4322 | 23.88 | 0.01051271 | 23.88 | 0.01051271 | 56.7471 | 13758.45 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 30790.140 | 30790.140 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.213460 | 1.45947524 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 30790.14 | 30790.14 | 1.0000 | 1.45947524 | 1.213460 | 19.01 | 13.62 | 0.00751177 | 38149.1 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 30790.14 | 8.70 | 0.00699286 | 8.70 | 0.20573941 | 16.9548 | 21.11 | 0.00761771 | 21.11 | 0.00761771 | 48.8891 | 8625.66 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:25
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
LGSTORE1 | 5221.83 | 1381.00 | 1155.83 |
SMSTORE1 | 5090.00 | 1007.17 | 837.17 |
SMSTORE2 | 3982.67 | 1316.17 | 1171.33 |
SMSTORE3 | 3974.50 | 1313.17 | 1160.50 |
SMSTORE4 | 3949.83 | 1404.33 | 1236.17 |
LGSTORE2 | 3564.67 | 1622.83 | 1451.67 |
SMSTORE5 | 3517.50 | 1678.50 | 1490.83 |
SMSTORE6 | 3507.83 | 1709.33 | 1515.00 |
SMSTORE7 | 3498.33 | 1721.67 | 1515.33 |
SMSTORE8 | 3535.67 | 1269.00 | 1056.50 |
Facility | 5358.17 | 2315.00 | 1980.67 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
LGSTORE1 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 0.00 | 0.83 | 0.00 | 0.00 |
SMSTORE4 | 0.00 | 0.17 | 0.00 | 0.00 |
LGSTORE2 | 0.00 | 1.17 | 0.00 | 0.00 |
SMSTORE5 | 0.00 | 1.17 | 0.00 | 0.00 |
SMSTORE6 | 0.00 | 1.17 | 0.00 | 0.00 |
SMSTORE7 | 0.00 | 0.83 | 0.00 | 0.00 |
SMSTORE8 | 0.00 | 1.50 | 0.00 | 0.00 |
Facility | 0.00 | 2.33 | 0.00 | 0.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:25
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
LGSTORE1 | 16.92 | 56.25 | 1805.20 | 0.841 | 0.349 | 0.000 | 0.000 |
SMSTORE1 | 8.46 | 28.12 | 902.60 | 0.687 | 0.386 | 0.000 | 0.000 |
SMSTORE2 | 7.09 | 28.12 | 902.60 | 0.841 | 0.505 | 0.000 | 0.000 |
SMSTORE3 | 7.09 | 28.12 | 902.60 | 0.841 | 0.505 | 0.000 | 0.000 |
SMSTORE4 | 7.09 | 28.12 | 902.60 | 0.841 | 0.505 | 0.000 | 0.000 |
LGSTORE2 | 24.79 | 56.25 | 1805.20 | 0.841 | 0.473 | 0.000 | 0.000 |
SMSTORE5 | 12.40 | 28.12 | 902.60 | 0.842 | 0.539 | 0.000 | 0.000 |
SMSTORE6 | 12.40 | 28.12 | 902.60 | 0.842 | 0.539 | 0.000 | 0.000 |
SMSTORE7 | 12.40 | 28.12 | 902.60 | 0.842 | 0.539 | 0.000 | 0.000 |
SMSTORE8 | 12.40 | 28.12 | 902.60 | 0.841 | 0.560 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
LGSTORE1 | 16.92 | 56.25 | 1805.20 | 0.815 | 0.000 | 0.000 | 0.000 |
SMSTORE1 | 8.46 | 28.12 | 902.60 | 0.000 | 0.000 | 0.000 | 0.000 |
SMSTORE2 | 7.09 | 28.12 | 902.60 | 0.812 | 0.000 | 0.000 | 0.000 |
SMSTORE3 | 7.09 | 28.12 | 902.60 | 0.812 | 0.000 | 0.000 | 0.000 |
SMSTORE4 | 7.09 | 28.12 | 902.60 | 0.812 | 0.000 | 0.000 | 0.000 |
LGSTORE2 | 24.79 | 56.25 | 1805.20 | 0.816 | 0.000 | 0.000 | 0.000 |
SMSTORE5 | 12.40 | 28.12 | 902.60 | 0.816 | 0.000 | 0.000 | 0.000 |
SMSTORE6 | 12.40 | 28.12 | 902.60 | 0.816 | 0.000 | 0.000 | 0.000 |
SMSTORE7 | 12.40 | 28.12 | 902.60 | 0.816 | 0.000 | 0.000 | 0.000 |
SMSTORE8 | 12.40 | 28.12 | 902.60 | 0.816 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:37:25
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
LGSTORE1 | PSZ-AC_1:1 | 16.92 | 56.25 | 1805.20 | 348.39 | 0.4115 | 0.411 |
SMSTORE1 | PSZ-AC_2:2 | 8.46 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE2 | PSZ-AC_3:3 | 7.09 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE3 | PSZ-AC_4:4 | 7.09 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE4 | PSZ-AC_5:5 | 7.09 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
LGSTORE2 | PSZ-AC_6:6 | 24.79 | 56.25 | 1805.20 | 348.39 | 0.4115 | 0.411 |
SMSTORE5 | PSZ-AC_7:7 | 12.40 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE6 | PSZ-AC_8:8 | 12.40 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE7 | PSZ-AC_9:9 | 12.40 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE8 | PSZ-AC_10:10 | 12.40 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
Total Facility | 121.02 | 337.50 | 10831.20 | 2090.32 | 2.4689 | 2.469 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
LGSTORE1 | 8803550.28 | 0.00 | 8803550.28 | 3922069.04 | 12725619.31 | 12976396.34 | 2817.00 | 5943.00 | 0.00 | 103.00 |
SMSTORE1 | 3613526.53 | 0.00 | 3613526.53 | 2084204.97 | 5697731.51 | 6488198.17 | 4303.00 | 4457.00 | 0.00 | 103.00 |
SMSTORE2 | 3525571.37 | 0.00 | 3525571.37 | 2120315.80 | 5645887.16 | 6488198.17 | 4000.00 | 4760.00 | 0.00 | 365.00 |
SMSTORE3 | 3525570.90 | 0.00 | 3525570.90 | 2120315.80 | 5645886.69 | 6488198.17 | 4000.00 | 4760.00 | 0.00 | 365.00 |
SMSTORE4 | 3525571.57 | 0.00 | 3525571.57 | 2120315.80 | 5645887.36 | 6488198.17 | 4000.00 | 4760.00 | 0.00 | 365.00 |
LGSTORE2 | 6510467.88 | 0.00 | 6510467.88 | 3775854.81 | 10286322.70 | 12976396.34 | 4365.00 | 4395.00 | 0.00 | 365.00 |
SMSTORE5 | 3255229.70 | 0.00 | 3255229.70 | 2129269.13 | 5384498.84 | 6488198.17 | 4365.00 | 4395.00 | 0.00 | 365.00 |
SMSTORE6 | 3255229.60 | 0.00 | 3255229.60 | 2129269.13 | 5384498.74 | 6488198.17 | 4365.00 | 4395.00 | 0.00 | 365.00 |
SMSTORE7 | 3255229.58 | 0.00 | 3255229.58 | 2129269.13 | 5384498.72 | 6488198.17 | 4365.00 | 4395.00 | 0.00 | 365.00 |
SMSTORE8 | 3255222.71 | 0.00 | 3255222.71 | 2433207.91 | 5688430.63 | 6488198.17 | 4365.00 | 4395.00 | 0.00 | 365.00 |
Total Facility | 42525170.12 | 0.00 | 42525170.12 | 24964091.53 | 67489261.65 | 77858378.04 | 4365.00 | 6246.00 | 0.00 | 730.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
LGSTORE1 | 0.4115 | 0.0000 | 0.4115 | 0.1706 | 0.5821 | 0.4115 | 0.00 | 5840.00 | 0.00 |
SMSTORE1 | 0.1682 | 0.0000 | 0.1682 | 0.0943 | 0.2626 | 0.2057 | 1486.00 | 4354.00 | 0.00 |
SMSTORE2 | 0.2057 | 0.0000 | 0.2057 | 0.1235 | 0.3292 | 0.2057 | 0.00 | 4395.00 | 0.00 |
SMSTORE3 | 0.2057 | 0.0000 | 0.2057 | 0.1235 | 0.3292 | 0.2057 | 0.00 | 4395.00 | 0.00 |
SMSTORE4 | 0.2057 | 0.0000 | 0.2057 | 0.1235 | 0.3292 | 0.2057 | 0.00 | 4395.00 | 0.00 |
LGSTORE2 | 0.4115 | 0.0000 | 0.4115 | 0.2311 | 0.6426 | 0.4115 | 0.00 | 4030.00 | 0.00 |
SMSTORE5 | 0.2057 | 0.0000 | 0.2057 | 0.1316 | 0.3374 | 0.2057 | 0.00 | 4030.00 | 0.00 |
SMSTORE6 | 0.2057 | 0.0000 | 0.2057 | 0.1316 | 0.3374 | 0.2057 | 0.00 | 4030.00 | 0.00 |
SMSTORE7 | 0.2057 | 0.0000 | 0.2057 | 0.1316 | 0.3374 | 0.2057 | 0.00 | 4030.00 | 0.00 |
SMSTORE8 | 0.2057 | 0.0000 | 0.2057 | 0.1368 | 0.3425 | 0.2057 | 0.00 | 4030.00 | 0.00 |
Total Facility | 2.4314 | 0.0000 | 2.4314 | 1.3982 | 3.8296 | 2.4689 | 1486.00 | 5943.00 | 0.00 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-AC_1:1 | 12734985.83 | 0.00 | 12734985.83 | 12976396.34 | 2817.00 | 0.00 | 5943.00 | 103.00 |
PSZ-AC_2:2 | 5227229.53 | 0.00 | 5227229.53 | 6488198.17 | 4303.00 | 0.00 | 4457.00 | 103.00 |
PSZ-AC_3:3 | 5099994.33 | 0.00 | 5099994.33 | 6488198.17 | 4000.00 | 0.00 | 4760.00 | 365.00 |
PSZ-AC_4:4 | 5099994.33 | 0.00 | 5099994.33 | 6488198.17 | 4000.00 | 0.00 | 4760.00 | 365.00 |
PSZ-AC_5:5 | 5099994.33 | 0.00 | 5099994.33 | 6488198.17 | 4000.00 | 0.00 | 4760.00 | 365.00 |
PSZ-AC_6:6 | 9417846.67 | 0.00 | 9417846.67 | 12976396.34 | 4365.00 | 0.00 | 4395.00 | 365.00 |
PSZ-AC_7:7 | 4708923.33 | 0.00 | 4708923.33 | 6488198.17 | 4365.00 | 0.00 | 4395.00 | 365.00 |
PSZ-AC_8:8 | 4708923.33 | 0.00 | 4708923.33 | 6488198.17 | 4365.00 | 0.00 | 4395.00 | 365.00 |
PSZ-AC_9:9 | 4708923.33 | 0.00 | 4708923.33 | 6488198.17 | 4365.00 | 0.00 | 4395.00 | 365.00 |
PSZ-AC_10:10 | 4708923.33 | 0.00 | 4708923.33 | 6488198.17 | 4365.00 | 0.00 | 4395.00 | 365.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-AC_1:1 | 0.5952 | 0.0000 | 0.5952 | 0.4115 | 0.00 | 0.00 | 5840.00 |
PSZ-AC_2:2 | 0.2434 | 0.0000 | 0.2434 | 0.2057 | 1486.00 | 0.00 | 4354.00 |
PSZ-AC_3:3 | 0.2976 | 0.0000 | 0.2976 | 0.2057 | 0.00 | 0.00 | 4395.00 |
PSZ-AC_4:4 | 0.2976 | 0.0000 | 0.2976 | 0.2057 | 0.00 | 0.00 | 4395.00 |
PSZ-AC_5:5 | 0.2976 | 0.0000 | 0.2976 | 0.2057 | 0.00 | 0.00 | 4395.00 |
PSZ-AC_6:6 | 0.5952 | 0.0000 | 0.5952 | 0.4115 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_7:7 | 0.2976 | 0.0000 | 0.2976 | 0.2057 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_8:8 | 0.2976 | 0.0000 | 0.2976 | 0.2057 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_9:9 | 0.2976 | 0.0000 | 0.2976 | 0.2057 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_10:10 | 0.2976 | 0.0000 | 0.2976 | 0.2057 | 0.00 | 0.00 | 4030.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-AC_1:1 | 0.00 | 5943.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_2:2 | 0.00 | 5942.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_3:3 | 0.00 | 4760.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_4:4 | 0.00 | 4760.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_5:5 | 0.00 | 4760.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_6:6 | 0.00 | 4395.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_7:7 | 0.00 | 4395.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_8:8 | 0.00 | 4395.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_9:9 | 0.00 | 4395.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_10:10 | 0.00 | 4395.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-AC_1:1 | 0.0000 | 0.5952 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_2:2 | 0.0000 | 0.2434 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_3:3 | 0.0000 | 0.2977 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_4:4 | 0.0000 | 0.2977 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_5:5 | 0.0000 | 0.2977 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_6:6 | 0.0000 | 0.5954 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_7:7 | 0.0000 | 0.2977 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_8:8 | 0.0000 | 0.2977 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_9:9 | 0.0000 | 0.2977 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_10:10 | 0.0000 | 0.2977 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:25
Surfaces by ClassTotal | Outdoors | |
Wall | 40 | 22 |
Floor | 10 | 10 |
Roof | 10 | 10 |
Internal Mass | 10 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 36 | 36 |
Door | 12 | 12 |
Glass Door | 12 | 12 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 10 |
Conditioned Zones | 10 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 830 |
Defaulted Fields | 823 |
Fields with Defaults | 2682 |
Autosized Fields | 184 |
Autosizable Fields | 458 |
Autocalculated Fields | 128 |
Autocalculatable Fields | 256 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:37:25
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1167.44 | 2102.83 | 01-JAN-07:20 | 105657.08 | 27-JUL-15:50 |
Electricity:Building | 494.83 | 891.83 | 01-JAN-00:20 | 31518.67 | 01-JAN-11:10 |
Electricity:Zone:LGSTORE1 | 113.36 | 148.64 | 01-JAN-00:20 | 5964.88 | 01-JAN-10:10 |
Electricity:SpaceType:GENERAL | 494.83 | 891.83 | 01-JAN-00:20 | 31518.67 | 01-JAN-11:10 |
InteriorLights:Electricity | 366.68 | 450.00 | 01-JAN-00:20 | 23459.17 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:LGSTORE1 | 87.12 | 75.00 | 01-JAN-00:20 | 4621.63 | 01-JAN-10:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 366.68 | 450.00 | 01-JAN-00:20 | 23459.17 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity | 366.68 | 450.00 | 01-JAN-00:20 | 23459.17 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:LGSTORE1 | 87.12 | 75.00 | 01-JAN-00:20 | 4621.63 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 366.68 | 450.00 | 01-JAN-00:20 | 23459.17 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE1 | 66.33 | 74.32 | 01-JAN-00:20 | 3498.69 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE1 | 53.20 | 37.50 | 01-JAN-00:20 | 2827.07 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE1 | 53.20 | 37.50 | 01-JAN-00:20 | 2827.07 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE2 | 47.99 | 74.32 | 01-JAN-00:10 | 3226.84 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE2 | 37.57 | 37.50 | 01-JAN-00:10 | 2555.22 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE2 | 37.57 | 37.50 | 01-JAN-00:10 | 2555.22 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE3 | 47.99 | 74.32 | 01-JAN-00:10 | 3226.84 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE3 | 37.57 | 37.50 | 01-JAN-00:10 | 2555.22 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE3 | 37.57 | 37.50 | 01-JAN-00:10 | 2555.22 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE4 | 47.99 | 74.32 | 01-JAN-00:10 | 3226.84 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE4 | 37.57 | 37.50 | 01-JAN-00:10 | 2555.22 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE4 | 37.57 | 37.50 | 01-JAN-00:10 | 2555.22 | 01-JAN-10:10 |
Electricity:Zone:LGSTORE2 | 56.34 | 148.64 | 01-JAN-00:10 | 4070.21 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:LGSTORE2 | 37.16 | 75.00 | 01-JAN-00:10 | 2726.96 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:LGSTORE2 | 37.16 | 75.00 | 01-JAN-00:10 | 2726.96 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE5 | 28.71 | 74.32 | 01-JAN-00:10 | 2076.09 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE5 | 19.12 | 37.50 | 01-JAN-00:10 | 1404.46 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE5 | 19.12 | 37.50 | 01-JAN-00:10 | 1404.46 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE6 | 28.71 | 74.32 | 01-JAN-00:10 | 2076.09 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE6 | 19.12 | 37.50 | 01-JAN-00:10 | 1404.46 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE6 | 19.12 | 37.50 | 01-JAN-00:10 | 1404.46 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE7 | 28.71 | 74.32 | 01-JAN-00:10 | 2076.09 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE7 | 19.12 | 37.50 | 01-JAN-00:10 | 1404.46 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE7 | 19.12 | 37.50 | 01-JAN-00:10 | 1404.46 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE8 | 28.71 | 74.32 | 01-JAN-00:10 | 2076.09 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE8 | 19.12 | 37.50 | 01-JAN-00:10 | 1404.46 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE8 | 19.12 | 37.50 | 01-JAN-00:10 | 1404.46 | 01-JAN-11:10 |
InteriorEquipment:Electricity | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:LGSTORE1 | 26.25 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-10:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LGSTORE1 | 26.25 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE1 | 13.12 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE1 | 13.12 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE2 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE2 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE3 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE3 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE4 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE4 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:LGSTORE2 | 19.17 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LGSTORE2 | 19.17 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE5 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE5 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE6 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE6 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE7 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE7 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE8 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE8 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
ElectricityPurchased:Facility | 1167.44 | 2102.83 | 01-JAN-07:20 | 105657.08 | 27-JUL-15:50 |
ElectricityPurchased:Plant | 1167.44 | 2102.83 | 01-JAN-07:20 | 105657.08 | 27-JUL-15:50 |
Cogeneration:ElectricityPurchased | 1167.44 | 2102.83 | 01-JAN-07:20 | 105657.08 | 27-JUL-15:50 |
General:Cogeneration:ElectricityPurchased | 1167.44 | 2102.83 | 01-JAN-07:20 | 105657.08 | 27-JUL-15:50 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1167.44 | 2102.83 | 01-JAN-07:20 | 105657.08 | 27-JUL-15:50 |
ElectricityNet:Plant | 1167.44 | 2102.83 | 01-JAN-07:20 | 105657.08 | 27-JUL-15:50 |
Cogeneration:ElectricityNet | 1167.44 | 2102.83 | 01-JAN-07:20 | 105657.08 | 27-JUL-15:50 |
General:Cogeneration:ElectricityNet | 1167.44 | 2102.83 | 01-JAN-07:20 | 105657.08 | 27-JUL-15:50 |
Electricity:HVAC | 553.74 | 0.00 | 01-JAN-00:10 | 68449.05 | 27-JUL-16:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 451.24 | 0.00 | 01-JAN-00:10 | 59469.10 | 27-JUL-16:10 |
General:Cooling:Electricity | 451.24 | 0.00 | 01-JAN-00:10 | 59469.10 | 27-JUL-16:10 |
Fans:Electricity | 102.50 | 0.00 | 01-JAN-00:10 | 9239.78 | 22-AUG-13:00 |
General:Fans:Electricity | 102.50 | 0.00 | 01-JAN-00:10 | 9239.78 | 22-AUG-13:00 |
ExteriorLights:Electricity | 60.12 | 0.00 | 01-JAN-07:20 | 5507.06 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 60.12 | 0.00 | 01-JAN-07:20 | 5507.06 | 01-JAN-06:10 |
Electricity:Plant | 58.75 | 1211.00 | 29-MAY-16:20 | 11709.19 | 16-JAN-16:30 |
WaterSystems:Electricity | 58.75 | 1211.00 | 29-MAY-16:20 | 11709.19 | 16-JAN-16:30 |
Water Heater:WaterSystems:Electricity | 58.75 | 1211.00 | 29-MAY-16:20 | 11709.19 | 16-JAN-16:30 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 0.50 | 0.00 | 01-JAN-00:10 | 44481.47 | 04-FEB-08:10 |
NaturalGas:HVAC | 0.50 | 0.00 | 01-JAN-00:10 | 44481.47 | 04-FEB-08:10 |
Heating:NaturalGas | 0.50 | 0.00 | 01-JAN-00:10 | 44481.47 | 04-FEB-08:10 |
General:Heating:NaturalGas | 0.50 | 0.00 | 01-JAN-00:10 | 44481.47 | 04-FEB-08:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water:Plant | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
WaterSystems:Water | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water Heater:WaterSystems:Water | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
MainsWater:Facility | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
MainsWater:Plant | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
WaterSystems:MainsWater | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water Heater:WaterSystems:MainsWater | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 2779.06 | 0.00 | 01-JAN-00:10 | 348500.55 | 22-AUG-13:00 |
EnergyTransfer:Building | 912.62 | 0.00 | 01-JAN-00:10 | 111809.55 | 29-JUL-16:00 |
EnergyTransfer:Zone:LGSTORE1 | 190.51 | 0.00 | 01-JAN-00:10 | 19645.25 | 29-JUL-16:10 |
Heating:EnergyTransfer | 4.22 | 0.00 | 01-JAN-00:10 | 21761.80 | 29-JUL-17:10 |
Heating:EnergyTransfer:Zone:LGSTORE1 | 0.26 | 0.00 | 01-JAN-00:10 | 2216.00 | 10-JUN-07:20 |
General:Heating:EnergyTransfer | 4.22 | 0.00 | 01-JAN-00:10 | 21761.80 | 29-JUL-17:10 |
General:Heating:EnergyTransfer:Zone:LGSTORE1 | 0.26 | 0.00 | 01-JAN-00:10 | 2216.00 | 10-JUN-07:20 |
Cooling:EnergyTransfer | 908.40 | 0.00 | 01-JAN-00:10 | 111809.55 | 29-JUL-16:00 |
Cooling:EnergyTransfer:Zone:LGSTORE1 | 190.25 | 0.00 | 01-JAN-00:10 | 19645.25 | 29-JUL-16:10 |
General:Cooling:EnergyTransfer | 908.40 | 0.00 | 01-JAN-00:10 | 111809.55 | 29-JUL-16:00 |
General:Cooling:EnergyTransfer:Zone:LGSTORE1 | 190.25 | 0.00 | 01-JAN-00:10 | 19645.25 | 29-JUL-16:10 |
EnergyTransfer:Zone:SMSTORE1 | 100.29 | 0.00 | 01-JAN-00:10 | 9653.63 | 29-JUL-16:10 |
Heating:EnergyTransfer:Zone:SMSTORE1 | 0.12 | 0.00 | 01-JAN-00:10 | 892.84 | 06-MAY-07:20 |
General:Heating:EnergyTransfer:Zone:SMSTORE1 | 0.12 | 0.00 | 01-JAN-00:10 | 892.84 | 06-MAY-07:20 |
Cooling:EnergyTransfer:Zone:SMSTORE1 | 100.17 | 0.00 | 01-JAN-00:10 | 9653.63 | 29-JUL-16:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE1 | 100.17 | 0.00 | 01-JAN-00:10 | 9653.63 | 29-JUL-16:10 |
EnergyTransfer:Zone:SMSTORE2 | 76.26 | 0.00 | 01-JAN-00:10 | 9509.28 | 29-JUL-14:00 |
Heating:EnergyTransfer:Zone:SMSTORE2 | 0.62 | 0.00 | 01-JAN-00:10 | 2403.97 | 29-JUL-17:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE2 | 0.62 | 0.00 | 01-JAN-00:10 | 2403.97 | 29-JUL-17:10 |
Cooling:EnergyTransfer:Zone:SMSTORE2 | 75.64 | 0.00 | 01-JAN-00:10 | 9509.28 | 29-JUL-14:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE2 | 75.64 | 0.00 | 01-JAN-00:10 | 9509.28 | 29-JUL-14:00 |
EnergyTransfer:Zone:SMSTORE3 | 76.25 | 0.00 | 01-JAN-00:10 | 9536.38 | 29-JUL-14:00 |
Heating:EnergyTransfer:Zone:SMSTORE3 | 0.62 | 0.00 | 01-JAN-00:10 | 2403.47 | 29-JUL-17:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE3 | 0.62 | 0.00 | 01-JAN-00:10 | 2403.47 | 29-JUL-17:10 |
Cooling:EnergyTransfer:Zone:SMSTORE3 | 75.63 | 0.00 | 01-JAN-00:10 | 9536.38 | 29-JUL-14:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE3 | 75.63 | 0.00 | 01-JAN-00:10 | 9536.38 | 29-JUL-14:00 |
EnergyTransfer:Zone:SMSTORE4 | 74.15 | 0.00 | 01-JAN-00:10 | 9409.59 | 29-JUL-14:00 |
Heating:EnergyTransfer:Zone:SMSTORE4 | 0.63 | 0.00 | 01-JAN-00:10 | 2411.43 | 29-JUL-17:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE4 | 0.63 | 0.00 | 01-JAN-00:10 | 2411.43 | 29-JUL-17:10 |
Cooling:EnergyTransfer:Zone:SMSTORE4 | 73.52 | 0.00 | 01-JAN-00:10 | 9409.59 | 29-JUL-14:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE4 | 73.52 | 0.00 | 01-JAN-00:10 | 9409.59 | 29-JUL-14:00 |
EnergyTransfer:Zone:LGSTORE2 | 125.64 | 0.00 | 01-JAN-00:10 | 17291.11 | 29-JUL-14:40 |
Heating:EnergyTransfer:Zone:LGSTORE2 | 0.65 | 0.00 | 01-JAN-00:10 | 4851.59 | 29-JUL-17:10 |
General:Heating:EnergyTransfer:Zone:LGSTORE2 | 0.65 | 0.00 | 01-JAN-00:10 | 4851.59 | 29-JUL-17:10 |
Cooling:EnergyTransfer:Zone:LGSTORE2 | 124.99 | 0.00 | 01-JAN-00:10 | 17291.11 | 29-JUL-14:40 |
General:Cooling:EnergyTransfer:Zone:LGSTORE2 | 124.99 | 0.00 | 01-JAN-00:10 | 17291.11 | 29-JUL-14:40 |
EnergyTransfer:Zone:SMSTORE5 | 65.03 | 0.00 | 01-JAN-00:10 | 9143.26 | 29-JUL-14:40 |
Heating:EnergyTransfer:Zone:SMSTORE5 | 0.32 | 0.00 | 01-JAN-00:10 | 2447.81 | 29-JUL-17:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE5 | 0.32 | 0.00 | 01-JAN-00:10 | 2447.81 | 29-JUL-17:10 |
Cooling:EnergyTransfer:Zone:SMSTORE5 | 64.71 | 0.00 | 01-JAN-00:10 | 9143.26 | 29-JUL-14:40 |
General:Cooling:EnergyTransfer:Zone:SMSTORE5 | 64.71 | 0.00 | 01-JAN-00:10 | 9143.26 | 29-JUL-14:40 |
EnergyTransfer:Zone:SMSTORE6 | 64.50 | 0.00 | 01-JAN-00:10 | 9109.98 | 29-JUL-14:40 |
Heating:EnergyTransfer:Zone:SMSTORE6 | 0.32 | 0.00 | 01-JAN-00:10 | 2449.55 | 29-JUL-17:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE6 | 0.32 | 0.00 | 01-JAN-00:10 | 2449.55 | 29-JUL-17:10 |
Cooling:EnergyTransfer:Zone:SMSTORE6 | 64.18 | 0.00 | 01-JAN-00:10 | 9109.98 | 29-JUL-14:40 |
General:Cooling:EnergyTransfer:Zone:SMSTORE6 | 64.18 | 0.00 | 01-JAN-00:10 | 9109.98 | 29-JUL-14:40 |
EnergyTransfer:Zone:SMSTORE7 | 64.18 | 0.00 | 01-JAN-00:10 | 9188.56 | 29-JUL-14:40 |
Heating:EnergyTransfer:Zone:SMSTORE7 | 0.33 | 0.00 | 01-JAN-00:10 | 2445.92 | 29-JUL-17:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE7 | 0.33 | 0.00 | 01-JAN-00:10 | 2445.92 | 29-JUL-17:10 |
Cooling:EnergyTransfer:Zone:SMSTORE7 | 63.85 | 0.00 | 01-JAN-00:10 | 9188.56 | 29-JUL-14:40 |
General:Cooling:EnergyTransfer:Zone:SMSTORE7 | 63.85 | 0.00 | 01-JAN-00:10 | 9188.56 | 29-JUL-14:40 |
EnergyTransfer:Zone:SMSTORE8 | 75.79 | 0.00 | 01-JAN-00:10 | 11007.64 | 29-JUL-14:10 |
Heating:EnergyTransfer:Zone:SMSTORE8 | 0.34 | 0.00 | 01-JAN-00:10 | 6786.30 | 04-FEB-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE8 | 0.34 | 0.00 | 01-JAN-00:10 | 6786.30 | 04-FEB-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE8 | 75.46 | 0.00 | 01-JAN-00:10 | 11007.64 | 29-JUL-14:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE8 | 75.46 | 0.00 | 01-JAN-00:10 | 11007.64 | 29-JUL-14:10 |
EnergyTransfer:HVAC | 1866.45 | 0.00 | 01-JAN-00:10 | 244251.97 | 22-AUG-13:00 |
HeatingCoils:EnergyTransfer | 0.40 | 0.00 | 01-JAN-00:10 | 35585.18 | 04-FEB-08:10 |
CoolingCoils:EnergyTransfer | 1866.05 | 0.00 | 01-JAN-00:10 | 244251.97 | 22-AUG-13:00 |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:25
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
LGSTORE1 | 0.000 | 0.000 | 0.257 | -190.249 | 0.000 | 0.000 | 23.239 | 87.116 | 26.249 | 17.122 | 0.000 | 15.345 | 28.104 | 0.000 | -3.023 | 0.000 | -4.160 | -0.000 |
SMSTORE1 | 0.000 | 0.000 | 0.124 | -100.162 | 0.000 | 0.000 | 11.613 | 53.201 | 13.125 | 8.580 | 0.000 | 8.524 | 8.526 | 0.000 | -1.531 | 0.000 | -1.999 | -0.000 |
SMSTORE2 | 0.000 | 0.000 | 0.621 | -75.633 | 0.000 | 0.000 | 6.979 | 37.572 | 10.421 | 8.503 | 0.000 | 8.354 | 7.006 | 0.000 | -1.660 | 0.000 | -2.163 | -0.001 |
SMSTORE3 | 0.000 | 0.000 | 0.619 | -75.632 | 0.000 | 0.000 | 6.980 | 37.572 | 10.421 | 8.502 | 0.000 | 8.351 | 7.009 | 0.000 | -1.662 | 0.000 | -2.160 | -0.000 |
SMSTORE4 | 0.000 | 0.000 | 0.632 | -73.519 | 0.000 | 0.000 | 6.982 | 37.572 | 10.421 | 8.517 | 0.000 | 8.357 | 4.801 | 0.000 | -1.630 | 0.000 | -2.132 | -0.000 |
LGSTORE2 | 0.000 | 0.000 | 0.650 | -124.991 | 0.000 | 0.000 | 23.967 | 37.162 | 19.173 | 17.065 | 0.000 | 14.712 | 19.169 | 0.000 | -3.085 | 0.000 | -3.822 | -0.000 |
SMSTORE5 | 0.000 | 0.000 | 0.323 | -64.709 | 0.000 | 0.000 | 11.985 | 19.120 | 9.586 | 8.545 | 0.000 | 8.380 | 10.377 | 0.000 | -1.513 | 0.000 | -2.093 | -0.000 |
SMSTORE6 | 0.000 | 0.000 | 0.325 | -64.174 | 0.000 | 0.000 | 11.986 | 19.120 | 9.586 | 8.551 | 0.000 | 8.381 | 9.814 | 0.000 | -1.505 | 0.000 | -2.085 | -0.000 |
SMSTORE7 | 0.000 | 0.000 | 0.330 | -63.852 | 0.000 | 0.000 | 11.988 | 19.120 | 9.586 | 8.551 | 0.000 | 8.382 | 9.450 | 0.000 | -1.493 | 0.000 | -2.063 | -0.000 |
SMSTORE8 | 0.000 | 0.000 | 0.336 | -75.453 | 0.000 | 0.000 | 11.987 | 19.120 | 9.586 | 8.469 | 0.000 | 8.724 | 21.480 | 0.000 | -1.473 | 0.000 | -2.775 | -0.000 |
Total Facility | 0.000 | 0.000 | 4.217 | -908.374 | 0.000 | 0.000 | 127.705 | 366.677 | 128.154 | 102.404 | 0.000 | 97.510 | 125.734 | 0.000 | -18.576 | 0.000 | -25.452 | -0.003 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
LGSTORE1 | 18-OCT-07:02 | 0.00 | 0.00 | 0.00 | -36671.86 | 0.00 | 0.00 | 172.74 | 75.00 | 74.62 | 20.43 | 0.00 | 47.12 | 36281.95 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 02-JUL-07:01 | 0.00 | 0.00 | 0.00 | -20428.08 | 0.00 | 0.00 | 83.99 | 37.50 | 37.31 | 117.81 | 0.00 | 32.53 | 20118.94 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 18-OCT-06:02 | 0.00 | 0.00 | 0.00 | -19440.79 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 0.00 | 0.00 | 0.48 | 19411.22 | 0.00 | -45.24 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 18-OCT-06:02 | 0.00 | 0.00 | 0.00 | -19507.46 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 0.00 | 0.00 | 0.43 | 19478.34 | 0.00 | -45.63 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 18-OCT-06:02 | 0.00 | 0.00 | 0.00 | -19231.73 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 0.00 | 0.00 | 0.83 | 19200.21 | 0.00 | -43.62 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 18-OCT-07:02 | 0.00 | 0.00 | 0.00 | -33578.85 | 0.00 | 0.00 | 0.00 | 75.00 | 73.64 | 26.79 | 0.00 | 47.08 | 33356.34 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 18-OCT-07:02 | 0.00 | 0.00 | 0.00 | -17509.97 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 15.03 | 0.00 | 30.45 | 17390.17 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 18-OCT-07:02 | 0.00 | 0.00 | 0.00 | -17421.38 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 15.53 | 0.00 | 31.05 | 17300.47 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 18-OCT-07:02 | 0.00 | 0.00 | 0.00 | -17424.90 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 16.01 | 0.00 | 34.28 | 17300.28 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 18-OCT-07:02 | 0.00 | 0.00 | 0.00 | -19643.82 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 16.00 | 0.00 | 45.13 | 19508.37 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 18-OCT-07:02 | 0.00 | 0.00 | 0.00 | -169858.24 | 0.00 | 0.00 | 554.22 | 450.00 | 1452.23 | 194.35 | 0.00 | 425.13 | 166782.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
LGSTORE1 | 04-FEB-08:62 | 0.00 | 0.00 | 5918.82 | 0.00 | 0.00 | 0.00 | 0.00 | 75.00 | 73.64 | 187.15 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -1298.86 | -4955.75 |
SMSTORE1 | 11-AUG-07:05 | 0.00 | 0.00 | 2043.18 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 142.73 | 0.00 | 205.76 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2466.00 |
SMSTORE2 | 29-JUL-17:02 | 0.00 | 0.00 | 2768.83 | 0.00 | 0.00 | 0.00 | 98.50 | 1344.85 | 373.13 | 360.71 | 0.00 | 399.28 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -5345.30 |
SMSTORE3 | 29-JUL-17:02 | 0.00 | 0.00 | 2768.79 | 0.00 | 0.00 | 0.00 | 98.50 | 1344.85 | 373.13 | 360.62 | 0.00 | 399.26 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -5345.15 |
SMSTORE4 | 29-JUL-17:02 | 0.00 | 0.00 | 2772.26 | 0.00 | 0.00 | 0.00 | 98.50 | 1344.85 | 373.13 | 361.14 | 0.00 | 399.47 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -5349.34 |
LGSTORE2 | 29-JUL-17:02 | 0.00 | 0.00 | 5535.93 | 0.00 | 0.00 | 0.00 | 433.43 | 1435.23 | 746.25 | 720.69 | 0.00 | 709.38 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -9580.92 |
SMSTORE5 | 29-JUL-17:02 | 0.00 | 0.00 | 2784.62 | 0.00 | 0.00 | 0.00 | 216.71 | 739.19 | 373.13 | 364.30 | 0.00 | 400.61 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -4878.56 |
SMSTORE6 | 29-JUL-17:02 | 0.00 | 0.00 | 2785.14 | 0.00 | 0.00 | 0.00 | 216.71 | 739.19 | 373.13 | 364.53 | 0.00 | 400.67 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -4879.36 |
SMSTORE7 | 29-JUL-17:02 | 0.00 | 0.00 | 2783.45 | 0.00 | 0.00 | 0.00 | 216.71 | 739.19 | 373.13 | 363.74 | 0.00 | 400.55 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -4876.78 |
SMSTORE8 | 04-FEB-08:62 | 0.00 | 0.00 | 26918.61 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 126.81 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -772.57 | -26347.17 |
Total Facility | 04-FEB-08:62 | -17320.16 | 17320.16 | 35542.82 | -17320.16 | 0.00 | 0.00 | 346.82 | 450.00 | 1450.75 | 1061.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -7886.66 | -13644.91 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:25
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 2.1667 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 2.1667 | 0.1899 | 1.0000 | Not calculated | 0.4115 | 0.1899 | ||
PSZ-AC_2:2 | 1.1223 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.1223 | 0.1833 | 1.0000 | Not calculated | 0.2057 | 0.1833 | ||
PSZ-AC_3:3 | 1.1242 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.1242 | 0.1830 | 1.0000 | Not calculated | 0.2057 | 0.1830 | ||
PSZ-AC_4:4 | 1.1273 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.1273 | 0.1825 | 1.0000 | Not calculated | 0.2057 | 0.1825 | ||
PSZ-AC_5:5 | 1.1176 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.1176 | 0.1841 | 1.0000 | Not calculated | 0.2057 | 0.1841 | ||
PSZ-AC_6:6 | 1.9609 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 1.9609 | 0.2098 | 1.0000 | Not calculated | 0.4115 | 0.2098 | ||
PSZ-AC_7:7 | 1.0277 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0277 | 0.2002 | 1.0000 | Not calculated | 0.2057 | 0.2002 | ||
PSZ-AC_8:8 | 1.0234 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0234 | 0.2010 | 1.0000 | Not calculated | 0.2057 | 0.2010 | ||
PSZ-AC_9:9 | 1.0278 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0278 | 0.2002 | 1.0000 | Not calculated | 0.2057 | 0.2002 | ||
PSZ-AC_10:10 | 1.2135 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.2135 | 0.1695 | 1.0000 | Not calculated | 0.2057 | 0.1695 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 2.1667 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 2.1667 | 1.0000 | 1.0000 | Not calculated | 0.4115 | 0.1899 | ||
PSZ-AC_2:2 | 1.1223 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.1223 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1833 | ||
PSZ-AC_3:3 | 1.1242 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.1242 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1830 | ||
PSZ-AC_4:4 | 1.1273 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.1273 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1825 | ||
PSZ-AC_5:5 | 1.1176 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.1176 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1841 | ||
PSZ-AC_6:6 | 1.9609 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 1.9609 | 1.0000 | 1.0000 | Not calculated | 0.4115 | 0.2098 | ||
PSZ-AC_7:7 | 1.0277 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0277 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.2002 | ||
PSZ-AC_8:8 | 1.0234 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0234 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.2010 | ||
PSZ-AC_9:9 | 1.0278 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0278 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.2002 | ||
PSZ-AC_10:10 | 1.2135 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.2135 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1695 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
LGSTORE1 | PSZ-AC_1:1 | 0.000000 | 56.2505 | 0.001181 | 348.39 | 0.4115 | 1.0000 | 0.4115 | 1.000 | 0.4115 |
SMSTORE1 | PSZ-AC_2:2 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE2 | PSZ-AC_3:3 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE3 | PSZ-AC_4:4 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE4 | PSZ-AC_5:5 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
LGSTORE2 | PSZ-AC_6:6 | 0.000000 | 56.2505 | 0.001181 | 348.39 | 0.4115 | 1.0000 | 0.4115 | 1.000 | 0.4115 |
SMSTORE5 | PSZ-AC_7:7 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE6 | PSZ-AC_8:8 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE7 | PSZ-AC_9:9 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE8 | PSZ-AC_10:10 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC_1:1 | 0.000000 | 56.25 | 0.001181 | 348.3864 | 0.4115 | 0.4115 | 0.4115 |
PSZ-AC_2:2 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_3:3 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_4:4 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_5:5 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_6:6 | 0.000000 | 56.25 | 0.001181 | 348.3864 | 0.4115 | 0.4115 | 0.4115 |
PSZ-AC_7:7 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_8:8 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_9:9 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_10:10 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LGSTORE1 | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.1667 | 2.1667 | 2.1667 | No | 0.4115 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE1 | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1223 | 1.1223 | 1.1223 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE2 | PSZ-AC_3:3 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1242 | 1.1242 | 1.1242 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE3 | PSZ-AC_4:4 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1273 | 1.1273 | 1.1273 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE4 | PSZ-AC_5:5 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1176 | 1.1176 | 1.1176 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LGSTORE2 | PSZ-AC_6:6 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.9609 | 1.9609 | 1.9609 | No | 0.4115 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE5 | PSZ-AC_7:7 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0277 | 1.0277 | 1.0277 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE6 | PSZ-AC_8:8 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0234 | 1.0234 | 1.0234 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE7 | PSZ-AC_9:9 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0278 | 1.0278 | 1.0278 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE8 | PSZ-AC_10:10 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2135 | 1.2135 | 1.2135 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 2.1667 | 2.1667 | 2.1667 | 2.1667 | 0.4115 | 1.0000 |
PSZ-AC_2:2 | 1.1223 | 1.1223 | 1.1223 | 1.1223 | 0.2057 | 1.0000 |
PSZ-AC_3:3 | 1.1242 | 1.1242 | 1.1242 | 1.1242 | 0.2057 | 1.0000 |
PSZ-AC_4:4 | 1.1273 | 1.1273 | 1.1273 | 1.1273 | 0.2057 | 1.0000 |
PSZ-AC_5:5 | 1.1176 | 1.1176 | 1.1176 | 1.1176 | 0.2057 | 1.0000 |
PSZ-AC_6:6 | 1.9609 | 1.9609 | 1.9609 | 1.9609 | 0.4115 | 1.0000 |
PSZ-AC_7:7 | 1.0277 | 1.0277 | 1.0277 | 1.0277 | 0.2057 | 1.0000 |
PSZ-AC_8:8 | 1.0234 | 1.0234 | 1.0234 | 1.0234 | 0.2057 | 1.0000 |
PSZ-AC_9:9 | 1.0278 | 1.0278 | 1.0278 | 1.0278 | 0.2057 | 1.0000 |
PSZ-AC_10:10 | 1.2135 | 1.2135 | 1.2135 | 1.2135 | 0.2057 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LGSTORE1 | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.1667 | 2.1667 | 2.1667 | No | 0.4115 | 0.5948 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE1 | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1223 | 1.1223 | 1.1223 | No | 0.2057 | 0.6143 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE2 | PSZ-AC_3:3 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1242 | 1.1242 | 1.1242 | No | 0.2057 | 0.6083 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE3 | PSZ-AC_4:4 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1273 | 1.1273 | 1.1273 | No | 0.2057 | 0.6027 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE4 | PSZ-AC_5:5 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1176 | 1.1176 | 1.1176 | No | 0.2057 | 0.5905 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LGSTORE2 | PSZ-AC_6:6 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.9609 | 1.9609 | 1.9609 | No | 0.4115 | 0.6224 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE5 | PSZ-AC_7:7 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0277 | 1.0277 | 1.0277 | No | 0.2057 | 0.5759 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE6 | PSZ-AC_8:8 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0234 | 1.0234 | 1.0234 | No | 0.2057 | 0.5755 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE7 | PSZ-AC_9:9 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0278 | 1.0278 | 1.0278 | No | 0.2057 | 0.5568 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE8 | PSZ-AC_10:10 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2135 | 1.2135 | 1.2135 | No | 0.2057 | 0.4605 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 2.1667 | 2.1667 | 2.1667 | 2.1667 | 0.4115 | 1.0000 |
PSZ-AC_2:2 | 1.1223 | 1.1223 | 1.1223 | 1.1223 | 0.2057 | 1.0000 |
PSZ-AC_3:3 | 1.1242 | 1.1242 | 1.1242 | 1.1242 | 0.2057 | 1.0000 |
PSZ-AC_4:4 | 1.1273 | 1.1273 | 1.1273 | 1.1273 | 0.2057 | 1.0000 |
PSZ-AC_5:5 | 1.1176 | 1.1176 | 1.1176 | 1.1176 | 0.2057 | 1.0000 |
PSZ-AC_6:6 | 1.9609 | 1.9609 | 1.9609 | 1.9609 | 0.4115 | 1.0000 |
PSZ-AC_7:7 | 1.0277 | 1.0277 | 1.0277 | 1.0277 | 0.2057 | 1.0000 |
PSZ-AC_8:8 | 1.0234 | 1.0234 | 1.0234 | 1.0234 | 0.2057 | 1.0000 |
PSZ-AC_9:9 | 1.0278 | 1.0278 | 1.0278 | 1.0278 | 0.2057 | 1.0000 |
PSZ-AC_10:10 | 1.2135 | 1.2135 | 1.2135 | 1.2135 | 0.2057 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:25
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Miami Intl Ap FL USA TMY3 WMO#=722020 |
Total gross floor area [m2] | 2090.32 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
LGSTORE1 | 348.39 | 348.39 | 0.00 | 112.00 |
SMSTORE1 | 174.19 | 174.19 | 0.00 | 112.00 |
SMSTORE2 | 174.19 | 174.19 | 0.00 | 84.29 |
SMSTORE3 | 174.19 | 174.19 | 0.00 | 84.29 |
SMSTORE4 | 174.19 | 174.19 | 0.00 | 84.29 |
LGSTORE2 | 348.39 | 348.39 | 0.00 | 77.29 |
SMSTORE5 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE6 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE7 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE8 | 174.19 | 174.19 | 0.00 | 77.29 |
Totals | 2090.32 | 2090.32 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 0.00 |
Number of hours not met | 0.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.50 | 44481.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 451.24 | 59469.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 366.68 | 23459.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 60.12 | 5507.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 128.15 | 8059.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 102.50 | 9239.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 58.75 | 11709.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 128.15 | 1167.44 |
Natural Gas | 0.00 | 0.50 |
Additional | 0.00 | 0.00 |
Total | 128.15 | 1167.94 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 175.42 |
Space Heating | 0.00 |
Space Cooling | 215.87 |
Fans (All) | 49.03 |
Service Water Heating | 28.11 |
Receptacle Equipment | 61.31 |
Miscellaneous (All) | 558.50 |
Subtotal | 558.50 |
Natural Gas [MJ/m2] | |
Space Heating | 0.24 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 0.24 |
Subtotal | 0.24 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 31.40 |
Space Heating | 0.04 |
Space Cooling | 38.64 |
Fans (All) | 8.78 |
Service Water Heating | 5.03 |
Receptacle Equipment | 10.97 |
Miscellaneous | 5.15 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
TYPE1_OCC_SCH | 1630. | 5840. |
TYPE2_OCC_SCH | 995. | 4429. |
TYPE3_OCC_SCH | 1709. | 4064. |
LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 3767. | 8760. |
LTG_SCH_BASE_LPD2 | 3238. | 8760. |
LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 3296. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | 5084. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | 5084. | 8760. |
LTG_SCH_BASE_SMALL_LPD1 | 4453. | 8760. |
LTG_SCH_BASE_LPD1 | 4376. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | 3767. | 8760. |
LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 3584. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 4096. | 8760. |
TYPE1_EQUIP_SCH | 4868. | 8760. |
TYPE2_EQUIP_SCH | 3893. | 8760. |
TYPE3_EQUIP_SCH | 3584. | 8760. |
TYPE1_INFIL_SCH | 4302. | 8760. |
TYPE2_INFIL_SCH | 5164. | 8760. |
TYPE3_INFIL_SCH | 5438. | 8760. |
INFIL_DOOR_OPENING_SCH | 2505. | 4380. |
TYPE1_MINOA_MOTORIZEDDAMPER_SCH | 5579. | 5579. |
TYPE2_MINOA_MOTORIZEDDAMPER_SCH | 4429. | 4429. |
TYPE3_MINOA_MOTORIZEDDAMPER_SCH | 4064. | 4064. |
TYPE1_SWH_SCH | 2063. | 6048. |
TYPE2_SWH_SCH | 1831. | 4429. |
TYPE3_SWH_SCH | 1733. | 4064. |
AVERAGE_SWH_SCH | 1863. | 6152. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 7118. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 5839. | 5839. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 7300. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6570. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
TYPE1_HTGSETP_SCH_NO_OPTIMUM | LGSTORE1 DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
TYPE1_CLGSETP_SCH_NO_OPTIMUM | LGSTORE1 DUAL SP CONTROL | July | 23.89 | 365 | 23.89 | 365 |
TYPE2_HTGSETP_SCH_NO_OPTIMUM | SMSTORE2 DUAL SP CONTROL | January | 21.11 | 365 | 15.56 | 365 |
TYPE2_CLGSETP_SCH_NO_OPTIMUM | SMSTORE2 DUAL SP CONTROL | July | 23.89 | 365 | 29.44 | 365 |
TYPE3_HTGSETP_SCH_NO_OPTIMUM | LGSTORE2 DUAL SP CONTROL | January | 21.11 | 365 | 15.56 | 365 |
TYPE3_CLGSETP_SCH_NO_OPTIMUM | LGSTORE2 DUAL SP CONTROL | July | 23.89 | 365 | 29.44 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:25
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
LGSTORE1 | 8744.50 | 15.50 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 7755.67 | 1004.33 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 7617.67 | 1142.33 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 7887.00 | 873.00 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 8277.17 | 482.83 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 8313.00 | 447.00 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 8324.17 | 435.83 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 8332.33 | 427.67 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 8133.00 | 627.00 | 0.00 | 0.00 | 0.00 |
Min | 7617.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 1142.33 | 0.00 | 0.00 | 0.00 |
Average | 8214.45 | 545.55 | 0.00 | 0.00 | 0.00 |
Sum | 82144.50 | 5455.50 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
LGSTORE1 | 89041.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 43777.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 25385.33 | 89.67 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 25385.50 | 89.50 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 25391.33 | 83.67 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 92998.00 | 213.00 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 45806.50 | 105.50 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 45807.00 | 105.00 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 45807.00 | 105.00 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 45788.50 | 123.50 | 0.00 | 0.00 | 0.00 |
Min | 25385.33 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 92998.00 | 213.00 | 0.00 | 0.00 | 0.00 |
Average | 48518.72 | 91.48 | 0.00 | 0.00 | 0.00 |
Sum | 485187.17 | 914.83 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
LGSTORE1 | 5280.00 | 3480.00 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 7130.00 | 1630.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 3876.00 | 4884.00 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 3885.83 | 4874.17 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 3818.67 | 4941.33 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 3524.50 | 5235.50 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 3515.67 | 5244.33 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 3494.67 | 5265.33 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 3517.50 | 5242.50 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 3964.50 | 4795.50 | 0.00 | 0.00 | 0.00 |
Min | 3494.67 | 1630.00 | 0.00 | 0.00 | 0.00 |
Max | 7130.00 | 5265.33 | 0.00 | 0.00 | 0.00 |
Average | 4200.73 | 4559.27 | 0.00 | 0.00 | 0.00 |
Sum | 42007.33 | 45592.67 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
LGSTORE1 | 72518.33 | 16522.67 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 35869.83 | 7907.17 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 18642.17 | 6832.83 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 18697.00 | 6778.00 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 18231.17 | 7243.83 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 56229.83 | 36981.17 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 27040.83 | 18871.17 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 26799.83 | 19112.17 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 26872.00 | 19040.00 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 32861.00 | 13051.00 | 0.00 | 0.00 | 0.00 |
Min | 18231.17 | 6778.00 | 0.00 | 0.00 | 0.00 |
Max | 72518.33 | 36981.17 | 0.00 | 0.00 | 0.00 |
Average | 33376.20 | 15234.00 | 0.00 | 0.00 | 0.00 |
Sum | 333762.00 | 152340.00 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:25
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:25
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
For: Environment
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTRIPMALL
For: Environment
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 1A
For: Environment
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_FL_MIAMI
For: Environment
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: ZoneCoolingSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.105002E+11 | 28664.19 | 14-JAN-08:62 | 21.15 | 19.82 | 0.140431E+10 | 1686.03 | 01-JAN-13:00 | 21.15 | 19.82 |
February | 0.110647E+11 | 30204.80 | 18-FEB-08:62 | 23.40 | 20.75 | 0.126701E+10 | 1686.05 | 11-FEB-13:50 | 23.40 | 20.75 |
March | 0.125235E+11 | 27487.70 | 30-MAR-07:03 | 23.40 | 19.43 | 0.139216E+10 | 1686.01 | 26-MAR-12:50 | 23.40 | 19.43 |
April | 0.147936E+11 | 30825.50 | 16-APR-07:02 | 22.07 | 21.01 | 0.136149E+10 | 1686.04 | 09-APR-17:49 | 22.07 | 21.01 |
May | 0.178143E+11 | 34098.46 | 09-MAY-07:02 | 25.68 | 20.64 | 0.140175E+10 | 1686.04 | 12-MAY-12:00 | 30.00 | 23.65 |
June | 0.184159E+11 | 30847.92 | 17-JUN-07:02 | 25.78 | 21.73 | 0.135476E+10 | 1686.07 | 16-JUN-12:50 | 25.78 | 21.73 |
July | 0.206318E+11 | 35452.41 | 02-JUL-07:01 | 25.97 | 21.70 | 0.141295E+10 | 1686.06 | 02-JUL-12:09 | 30.50 | 24.19 |
August | 0.197705E+11 | 31698.18 | 08-AUG-07:02 | 28.07 | 24.21 | 0.139427E+10 | 1686.04 | 20-AUG-17:49 | 30.10 | 24.42 |
September | 0.195534E+11 | 31941.69 | 10-SEP-07:01 | 25.37 | 24.08 | 0.136537E+10 | 1686.06 | 08-SEP-12:09 | 25.37 | 24.08 |
October | 0.185382E+11 | 36682.12 | 18-OCT-07:02 | 25.18 | 18.80 | 0.140989E+10 | 1686.08 | 07-OCT-12:09 | 25.18 | 18.80 |
November | 0.148106E+11 | 32266.28 | 20-NOV-08:62 | 24.50 | 20.57 | 0.136264E+10 | 1686.03 | 05-NOV-17:00 | 24.50 | 20.57 |
December | 0.118356E+11 | 34473.69 | 01-DEC-08:62 | 23.48 | 18.65 | 0.141160E+10 | 1686.03 | 10-DEC-13:00 | 28.90 | 23.02 |
Annual Sum or Average | 0.190252E+12 | 0.165382E+11 | ||||||||
Minimum of Months | 0.105002E+11 | 27487.70 | 21.15 | 18.65 | 0.126701E+10 | 1686.01 | 21.15 | 18.80 | ||
Maximum of Months | 0.206318E+11 | 36682.12 | 28.07 | 24.21 | 0.141295E+10 | 1686.08 | 30.50 | 24.42 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.593731E+10 | 17062.74 | 14-JAN-08:62 | 21.15 | 19.82 | 0.703583E+09 | 842.99 | 15-JAN-13:30 | 25.30 | 16.95 |
February | 0.607092E+10 | 17808.63 | 18-FEB-08:62 | 23.40 | 20.75 | 0.635317E+09 | 843.00 | 11-FEB-13:39 | 23.40 | 20.75 |
March | 0.676546E+10 | 16568.46 | 06-MAR-08:62 | 23.40 | 21.79 | 0.697167E+09 | 842.98 | 26-MAR-12:39 | 26.83 | 22.23 |
April | 0.779836E+10 | 18431.31 | 16-APR-07:02 | 22.07 | 21.01 | 0.680764E+09 | 842.99 | 22-APR-12:30 | 27.20 | 20.57 |
May | 0.922276E+10 | 19210.85 | 08-MAY-07:02 | 25.00 | 19.79 | 0.700866E+09 | 843.00 | 12-MAY-12:00 | 30.00 | 23.65 |
June | 0.954662E+10 | 18332.23 | 12-JUN-07:01 | 26.47 | 24.56 | 0.677369E+09 | 843.01 | 16-JUN-12:39 | 30.00 | 23.77 |
July | 0.105501E+11 | 20428.98 | 02-JUL-07:01 | 25.97 | 21.70 | 0.706463E+09 | 843.02 | 07-JUL-12:09 | 33.62 | 23.53 |
August | 0.101357E+11 | 18621.56 | 28-AUG-07:02 | 25.73 | 24.26 | 0.697118E+09 | 843.00 | 20-AUG-17:00 | 25.73 | 24.26 |
September | 0.100457E+11 | 19310.17 | 04-SEP-07:02 | 24.27 | 22.84 | 0.682669E+09 | 843.00 | 24-SEP-17:49 | 29.50 | 24.51 |
October | 0.966536E+10 | 20263.13 | 18-OCT-07:02 | 25.18 | 18.80 | 0.704932E+09 | 843.01 | 13-OCT-12:09 | 25.18 | 18.80 |
November | 0.792304E+10 | 18881.03 | 09-NOV-08:62 | 22.85 | 21.36 | 0.681432E+09 | 843.00 | 03-NOV-12:20 | 22.85 | 21.36 |
December | 0.650401E+10 | 20229.17 | 01-DEC-08:62 | 23.48 | 18.65 | 0.707203E+09 | 843.00 | 10-DEC-13:00 | 28.90 | 23.02 |
Annual Sum or Average | 0.100165E+12 | 0.827488E+10 | ||||||||
Minimum of Months | 0.593731E+10 | 16568.46 | 21.15 | 18.65 | 0.635317E+09 | 842.98 | 22.85 | 16.95 | ||
Maximum of Months | 0.105501E+11 | 20428.98 | 26.47 | 24.56 | 0.707203E+09 | 843.02 | 33.62 | 24.51 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.425635E+10 | 15157.69 | 14-JAN-07:02 | 21.93 | 20.13 | 0.418171E+09 | 842.97 | 07-JAN-13:09 | 21.93 | 20.13 |
February | 0.444181E+10 | 15618.78 | 18-FEB-07:02 | 23.80 | 20.78 | 0.380217E+09 | 843.01 | 11-FEB-13:50 | 23.80 | 20.78 |
March | 0.496987E+10 | 17081.72 | 31-MAR-06:03 | 22.30 | 18.89 | 0.429212E+09 | 842.99 | 04-MAR-13:09 | 22.30 | 18.89 |
April | 0.575896E+10 | 17234.05 | 17-APR-06:02 | 18.98 | 16.80 | 0.410775E+09 | 842.99 | 22-APR-12:39 | 27.20 | 20.52 |
May | 0.702385E+10 | 17574.71 | 09-MAY-06:02 | 24.18 | 19.97 | 0.426246E+09 | 842.99 | 13-MAY-12:00 | 30.60 | 23.08 |
June | 0.739500E+10 | 15776.42 | 17-JUN-06:02 | 25.10 | 21.21 | 0.417338E+09 | 842.95 | 17-JUN-12:09 | 28.48 | 22.56 |
July | 0.812805E+10 | 15941.72 | 02-JUL-07:01 | 25.97 | 21.70 | 0.420561E+09 | 842.90 | 22-JUL-12:00 | 31.10 | 25.83 |
August | 0.793595E+10 | 15250.46 | 30-AUG-06:02 | 24.68 | 23.02 | 0.432060E+09 | 842.98 | 05-AUG-12:39 | 24.68 | 23.02 |
September | 0.773152E+10 | 15385.00 | 14-SEP-06:02 | 24.40 | 22.82 | 0.411366E+09 | 842.99 | 16-SEP-12:09 | 30.10 | 23.72 |
October | 0.738073E+10 | 19445.55 | 18-OCT-06:02 | 25.00 | 18.59 | 0.420745E+09 | 842.95 | 28-OCT-12:09 | 28.48 | 23.10 |
November | 0.595057E+10 | 16517.11 | 21-NOV-07:02 | 25.18 | 21.19 | 0.405998E+09 | 842.98 | 25-NOV-13:30 | 26.70 | 21.89 |
December | 0.466245E+10 | 15805.33 | 03-DEC-08:62 | 20.18 | 18.52 | 0.417863E+09 | 842.98 | 02-DEC-13:30 | 20.18 | 18.52 |
Annual Sum or Average | 0.756351E+11 | 0.499055E+10 | ||||||||
Minimum of Months | 0.425635E+10 | 15157.69 | 18.98 | 16.80 | 0.380217E+09 | 842.90 | 20.18 | 18.52 | ||
Maximum of Months | 0.812805E+10 | 19445.55 | 25.97 | 23.02 | 0.432060E+09 | 843.01 | 31.10 | 25.83 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.419485E+10 | 15186.08 | 14-JAN-07:02 | 21.93 | 20.13 | 0.418005E+09 | 842.98 | 07-JAN-13:09 | 21.93 | 20.13 |
February | 0.439136E+10 | 15658.26 | 18-FEB-07:02 | 23.80 | 20.78 | 0.380108E+09 | 843.01 | 11-FEB-13:50 | 23.80 | 20.78 |
March | 0.492883E+10 | 17131.16 | 31-MAR-06:03 | 22.30 | 18.89 | 0.429102E+09 | 842.99 | 04-MAR-13:09 | 22.30 | 18.89 |
April | 0.575542E+10 | 17342.81 | 17-APR-06:02 | 18.98 | 16.80 | 0.410771E+09 | 842.99 | 22-APR-12:00 | 27.20 | 20.41 |
May | 0.703623E+10 | 17632.88 | 09-MAY-06:02 | 24.18 | 19.97 | 0.426244E+09 | 842.98 | 13-MAY-12:00 | 30.60 | 23.08 |
June | 0.743193E+10 | 15859.75 | 17-JUN-06:02 | 25.10 | 21.21 | 0.417340E+09 | 842.95 | 17-JUN-12:09 | 28.48 | 22.56 |
July | 0.817907E+10 | 16043.72 | 02-JUL-07:01 | 25.97 | 21.70 | 0.420564E+09 | 842.90 | 15-JUL-12:09 | 30.68 | 24.89 |
August | 0.797273E+10 | 15310.56 | 30-AUG-06:02 | 24.68 | 23.02 | 0.432061E+09 | 842.98 | 05-AUG-12:39 | 24.68 | 23.02 |
September | 0.777917E+10 | 15461.20 | 14-SEP-06:02 | 24.40 | 22.82 | 0.411369E+09 | 842.99 | 16-SEP-12:09 | 30.10 | 23.72 |
October | 0.741060E+10 | 19512.25 | 18-OCT-06:02 | 25.00 | 18.59 | 0.420746E+09 | 842.95 | 28-OCT-12:09 | 28.48 | 23.10 |
November | 0.593831E+10 | 16570.54 | 21-NOV-07:02 | 25.18 | 21.19 | 0.405985E+09 | 842.98 | 25-NOV-13:30 | 26.70 | 21.89 |
December | 0.461587E+10 | 15766.86 | 03-DEC-08:62 | 20.18 | 18.52 | 0.417740E+09 | 842.99 | 02-DEC-13:30 | 20.18 | 18.52 |
Annual Sum or Average | 0.756344E+11 | 0.499003E+10 | ||||||||
Minimum of Months | 0.419485E+10 | 15186.08 | 18.98 | 16.80 | 0.380108E+09 | 842.90 | 20.18 | 18.52 | ||
Maximum of Months | 0.817907E+10 | 19512.25 | 25.97 | 23.02 | 0.432061E+09 | 843.01 | 30.68 | 24.89 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.399464E+10 | 14928.13 | 14-JAN-07:02 | 21.93 | 20.13 | 0.417556E+09 | 842.98 | 07-JAN-13:09 | 21.93 | 20.13 |
February | 0.420760E+10 | 15399.58 | 18-FEB-07:02 | 23.80 | 20.78 | 0.379791E+09 | 843.00 | 11-FEB-13:50 | 23.80 | 20.78 |
March | 0.472975E+10 | 15800.65 | 31-MAR-06:03 | 22.30 | 18.89 | 0.428751E+09 | 842.96 | 04-MAR-13:30 | 22.30 | 18.89 |
April | 0.557550E+10 | 17131.74 | 17-APR-06:02 | 18.98 | 16.80 | 0.410734E+09 | 842.99 | 22-APR-12:00 | 27.20 | 20.41 |
May | 0.686320E+10 | 17370.59 | 09-MAY-06:02 | 24.18 | 19.97 | 0.426212E+09 | 842.98 | 13-MAY-12:00 | 30.60 | 23.08 |
June | 0.726871E+10 | 15590.47 | 17-JUN-06:02 | 25.10 | 21.21 | 0.417307E+09 | 842.96 | 17-JUN-12:09 | 28.48 | 22.56 |
July | 0.802159E+10 | 15776.09 | 02-JUL-07:01 | 25.97 | 21.70 | 0.420532E+09 | 842.90 | 15-JUL-12:09 | 30.68 | 24.89 |
August | 0.780329E+10 | 15042.24 | 30-AUG-06:02 | 24.68 | 23.02 | 0.432027E+09 | 842.98 | 05-AUG-12:39 | 24.68 | 23.02 |
September | 0.762567E+10 | 15187.99 | 14-SEP-06:02 | 24.40 | 22.82 | 0.411337E+09 | 842.98 | 16-SEP-12:09 | 30.10 | 23.72 |
October | 0.724874E+10 | 19236.47 | 18-OCT-06:02 | 25.00 | 18.59 | 0.420714E+09 | 842.95 | 28-OCT-12:09 | 28.48 | 23.10 |
November | 0.576022E+10 | 16304.78 | 21-NOV-07:02 | 25.18 | 21.19 | 0.405929E+09 | 842.98 | 25-NOV-13:30 | 26.70 | 21.89 |
December | 0.442243E+10 | 15239.31 | 01-DEC-07:02 | 23.30 | 18.59 | 0.417398E+09 | 842.99 | 02-DEC-13:30 | 26.40 | 20.37 |
Annual Sum or Average | 0.735213E+11 | 0.498829E+10 | ||||||||
Minimum of Months | 0.399464E+10 | 14928.13 | 18.98 | 16.80 | 0.379791E+09 | 842.90 | 21.93 | 18.89 | ||
Maximum of Months | 0.802159E+10 | 19236.47 | 25.97 | 23.02 | 0.432027E+09 | 843.00 | 30.68 | 24.89 |
Report: ZoneCoolingSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.652500E+10 | 26095.57 | 14-JAN-08:62 | 21.15 | 19.82 | 0.142441E+10 | 2247.98 | 07-JAN-15:09 | 21.15 | 19.82 |
February | 0.695545E+10 | 27346.73 | 18-FEB-08:62 | 23.40 | 20.75 | 0.129962E+10 | 2248.03 | 11-FEB-15:00 | 23.40 | 20.75 |
March | 0.787821E+10 | 25668.28 | 27-MAR-07:03 | 20.78 | 18.60 | 0.146926E+10 | 2248.02 | 25-MAR-14:00 | 20.78 | 18.60 |
April | 0.943869E+10 | 29729.00 | 17-APR-07:03 | 19.60 | 17.17 | 0.140998E+10 | 2248.08 | 15-APR-14:39 | 19.60 | 17.17 |
May | 0.117776E+11 | 30493.64 | 09-MAY-07:02 | 25.68 | 20.64 | 0.145785E+10 | 2248.07 | 06-MAY-14:09 | 25.68 | 20.64 |
June | 0.124930E+11 | 27631.68 | 17-JUN-07:02 | 25.78 | 21.73 | 0.143008E+10 | 2247.95 | 17-JUN-14:20 | 29.40 | 22.66 |
July | 0.138247E+11 | 27964.45 | 07-JUL-07:02 | 25.97 | 22.68 | 0.143894E+10 | 2247.81 | 22-JUL-14:30 | 30.30 | 25.45 |
August | 0.134562E+11 | 27717.80 | 08-AUG-07:02 | 28.07 | 24.21 | 0.148037E+10 | 2247.95 | 05-AUG-14:30 | 28.07 | 24.21 |
September | 0.131613E+11 | 27756.89 | 14-SEP-07:02 | 24.78 | 23.34 | 0.141097E+10 | 2247.81 | 02-SEP-14:09 | 24.78 | 23.34 |
October | 0.124703E+11 | 33586.90 | 18-OCT-07:02 | 25.18 | 18.80 | 0.143585E+10 | 2248.01 | 28-OCT-14:09 | 28.80 | 23.05 |
November | 0.974863E+10 | 29189.08 | 07-NOV-08:62 | 21.57 | 20.92 | 0.138159E+10 | 2248.00 | 18-NOV-15:00 | 27.20 | 21.87 |
December | 0.726505E+10 | 29641.07 | 03-DEC-09:02 | 21.10 | 17.72 | 0.142904E+10 | 2248.03 | 02-DEC-15:00 | 21.10 | 17.72 |
Annual Sum or Average | 0.124994E+12 | 0.170679E+11 | ||||||||
Minimum of Months | 0.652500E+10 | 25668.28 | 19.60 | 17.17 | 0.129962E+10 | 2247.81 | 19.60 | 17.17 | ||
Maximum of Months | 0.138247E+11 | 33586.90 | 28.07 | 24.21 | 0.148037E+10 | 2248.08 | 30.30 | 25.45 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.329514E+10 | 12788.50 | 14-JAN-08:62 | 21.15 | 19.82 | 0.711688E+09 | 1123.96 | 07-JAN-15:09 | 21.15 | 19.82 |
February | 0.355119E+10 | 14251.84 | 18-FEB-08:62 | 23.40 | 20.75 | 0.649516E+09 | 1123.98 | 11-FEB-15:00 | 23.40 | 20.75 |
March | 0.401543E+10 | 12678.27 | 27-MAR-07:03 | 20.78 | 18.60 | 0.734169E+09 | 1123.97 | 25-MAR-14:00 | 20.78 | 18.60 |
April | 0.487424E+10 | 15428.32 | 17-APR-07:03 | 19.60 | 17.17 | 0.704955E+09 | 1124.02 | 15-APR-14:50 | 19.60 | 17.17 |
May | 0.612771E+10 | 15930.07 | 09-MAY-07:02 | 25.68 | 20.64 | 0.728894E+09 | 1124.00 | 06-MAY-14:09 | 25.68 | 20.64 |
June | 0.650863E+10 | 14423.02 | 17-JUN-07:02 | 25.78 | 21.73 | 0.715000E+09 | 1123.94 | 17-JUN-14:20 | 29.40 | 22.66 |
July | 0.722870E+10 | 14602.47 | 07-JUL-07:02 | 25.97 | 22.68 | 0.719424E+09 | 1123.87 | 22-JUL-14:30 | 30.30 | 25.45 |
August | 0.702160E+10 | 14522.69 | 08-AUG-07:02 | 28.07 | 24.21 | 0.740151E+09 | 1123.94 | 05-AUG-14:30 | 28.07 | 24.21 |
September | 0.686500E+10 | 14500.88 | 14-SEP-07:02 | 24.78 | 23.34 | 0.705441E+09 | 1123.87 | 02-SEP-14:09 | 24.78 | 23.34 |
October | 0.649685E+10 | 17514.34 | 18-OCT-07:02 | 25.18 | 18.80 | 0.717891E+09 | 1123.97 | 28-OCT-14:09 | 28.80 | 23.05 |
November | 0.503837E+10 | 15137.23 | 21-NOV-08:62 | 26.20 | 21.56 | 0.690767E+09 | 1123.97 | 18-NOV-15:00 | 26.20 | 21.56 |
December | 0.368815E+10 | 14903.50 | 01-DEC-08:62 | 23.48 | 18.65 | 0.714263E+09 | 1123.98 | 02-DEC-15:00 | 25.60 | 20.31 |
Annual Sum or Average | 0.647110E+11 | 0.853216E+10 | ||||||||
Minimum of Months | 0.329514E+10 | 12678.27 | 19.60 | 17.17 | 0.649516E+09 | 1123.87 | 19.60 | 17.17 | ||
Maximum of Months | 0.722870E+10 | 17514.34 | 28.07 | 24.21 | 0.740151E+09 | 1124.02 | 30.30 | 25.45 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.324350E+10 | 12419.27 | 14-JAN-08:62 | 21.15 | 19.82 | 0.711267E+09 | 1123.96 | 07-JAN-15:09 | 21.15 | 19.82 |
February | 0.350038E+10 | 14164.39 | 18-FEB-08:62 | 23.40 | 20.75 | 0.649335E+09 | 1123.98 | 11-FEB-15:00 | 23.40 | 20.75 |
March | 0.396432E+10 | 12319.47 | 27-MAR-07:03 | 20.78 | 18.60 | 0.733938E+09 | 1123.97 | 25-MAR-14:00 | 20.78 | 18.60 |
April | 0.482962E+10 | 15356.91 | 17-APR-07:03 | 19.60 | 17.17 | 0.704948E+09 | 1124.01 | 15-APR-14:39 | 19.60 | 17.17 |
May | 0.608477E+10 | 15842.90 | 09-MAY-07:02 | 25.68 | 20.64 | 0.728889E+09 | 1124.00 | 06-MAY-14:09 | 25.68 | 20.64 |
June | 0.646977E+10 | 14340.83 | 17-JUN-07:02 | 25.78 | 21.73 | 0.714996E+09 | 1123.94 | 17-JUN-14:20 | 29.40 | 22.66 |
July | 0.719105E+10 | 14517.67 | 07-JUL-07:02 | 25.97 | 22.68 | 0.719419E+09 | 1123.87 | 22-JUL-14:30 | 30.30 | 25.45 |
August | 0.698172E+10 | 14431.15 | 08-AUG-07:02 | 28.07 | 24.21 | 0.740148E+09 | 1123.94 | 05-AUG-14:30 | 28.07 | 24.21 |
September | 0.682841E+10 | 14416.55 | 14-SEP-07:02 | 24.78 | 23.34 | 0.705436E+09 | 1123.87 | 02-SEP-14:09 | 24.78 | 23.34 |
October | 0.645560E+10 | 17425.72 | 18-OCT-07:02 | 25.18 | 18.80 | 0.717885E+09 | 1123.97 | 28-OCT-14:09 | 28.80 | 23.05 |
November | 0.499208E+10 | 15049.81 | 21-NOV-08:62 | 26.20 | 21.56 | 0.690752E+09 | 1123.97 | 18-NOV-15:00 | 26.20 | 21.56 |
December | 0.363421E+10 | 14815.12 | 01-DEC-08:62 | 23.48 | 18.65 | 0.714016E+09 | 1123.98 | 02-DEC-15:00 | 25.60 | 20.31 |
Annual Sum or Average | 0.641754E+11 | 0.853103E+10 | ||||||||
Minimum of Months | 0.324350E+10 | 12319.47 | 19.60 | 17.17 | 0.649335E+09 | 1123.87 | 19.60 | 17.17 | ||
Maximum of Months | 0.719105E+10 | 17425.72 | 28.07 | 24.21 | 0.740148E+09 | 1124.01 | 30.30 | 25.45 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.313538E+10 | 11351.23 | 14-JAN-08:62 | 21.15 | 19.82 | 0.710311E+09 | 1123.97 | 07-JAN-15:09 | 21.15 | 19.82 |
February | 0.340249E+10 | 14129.70 | 18-FEB-08:62 | 23.40 | 20.75 | 0.648834E+09 | 1123.99 | 11-FEB-15:50 | 23.40 | 20.75 |
March | 0.387780E+10 | 11439.94 | 05-MAR-09:02 | 24.50 | 22.85 | 0.733483E+09 | 1123.94 | 04-MAR-15:00 | 24.50 | 22.85 |
April | 0.478618E+10 | 15370.83 | 17-APR-07:03 | 19.60 | 17.17 | 0.704936E+09 | 1124.01 | 15-APR-14:50 | 19.60 | 17.17 |
May | 0.608121E+10 | 15831.22 | 09-MAY-07:02 | 25.68 | 20.64 | 0.728888E+09 | 1124.00 | 06-MAY-14:09 | 25.68 | 20.64 |
June | 0.649959E+10 | 14345.63 | 17-JUN-07:02 | 25.78 | 21.73 | 0.714998E+09 | 1123.94 | 17-JUN-14:20 | 29.40 | 22.66 |
July | 0.724446E+10 | 14544.79 | 07-JUL-07:02 | 25.97 | 22.68 | 0.719425E+09 | 1123.87 | 22-JUL-14:30 | 30.30 | 25.45 |
August | 0.701781E+10 | 14455.19 | 08-AUG-07:02 | 28.07 | 24.21 | 0.740149E+09 | 1123.94 | 05-AUG-14:30 | 28.07 | 24.21 |
September | 0.687631E+10 | 14458.57 | 14-SEP-07:02 | 24.78 | 23.34 | 0.705440E+09 | 1123.87 | 02-SEP-14:09 | 24.78 | 23.34 |
October | 0.646495E+10 | 17429.29 | 18-OCT-07:02 | 25.18 | 18.80 | 0.717885E+09 | 1123.96 | 28-OCT-14:09 | 28.80 | 23.05 |
November | 0.494186E+10 | 15035.59 | 21-NOV-08:62 | 26.20 | 21.56 | 0.690707E+09 | 1123.97 | 18-NOV-15:00 | 26.20 | 21.56 |
December | 0.352589E+10 | 14787.12 | 01-DEC-08:62 | 23.48 | 18.65 | 0.713313E+09 | 1123.98 | 02-DEC-15:50 | 25.78 | 20.31 |
Annual Sum or Average | 0.638539E+11 | 0.852837E+10 | ||||||||
Minimum of Months | 0.313538E+10 | 11351.23 | 19.60 | 17.17 | 0.648834E+09 | 1123.87 | 19.60 | 17.17 | ||
Maximum of Months | 0.724446E+10 | 17429.29 | 28.07 | 24.21 | 0.740149E+09 | 1124.01 | 30.30 | 25.45 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.338637E+10 | 9182.42 | 14-JAN-08:62 | 21.15 | 19.82 | 0.710310E+09 | 1123.87 | 07-JAN-15:00 | 21.15 | 19.82 |
February | 0.378020E+10 | 14556.53 | 18-FEB-08:62 | 23.40 | 20.75 | 0.648474E+09 | 1123.91 | 11-FEB-15:09 | 23.40 | 20.75 |
March | 0.439379E+10 | 11716.58 | 05-MAR-09:02 | 24.50 | 22.85 | 0.734914E+09 | 1123.99 | 04-MAR-15:00 | 24.50 | 22.85 |
April | 0.568800E+10 | 14887.01 | 16-APR-08:62 | 24.08 | 21.61 | 0.705028E+09 | 1124.00 | 08-APR-14:20 | 24.08 | 21.61 |
May | 0.734568E+10 | 18001.07 | 08-MAY-07:02 | 25.00 | 19.79 | 0.729013E+09 | 1124.02 | 13-MAY-14:20 | 30.40 | 23.87 |
June | 0.792730E+10 | 15901.77 | 17-JUN-07:02 | 25.78 | 21.73 | 0.715127E+09 | 1123.88 | 17-JUN-14:00 | 29.40 | 22.43 |
July | 0.893803E+10 | 16481.38 | 06-JUL-07:02 | 25.55 | 22.29 | 0.719641E+09 | 1123.87 | 22-JUL-14:50 | 31.23 | 26.06 |
August | 0.849860E+10 | 16966.40 | 08-AUG-07:02 | 28.07 | 24.21 | 0.740273E+09 | 1123.97 | 05-AUG-14:09 | 28.07 | 24.21 |
September | 0.840127E+10 | 16446.14 | 14-SEP-07:02 | 24.78 | 23.34 | 0.705624E+09 | 1124.02 | 02-SEP-14:30 | 24.78 | 23.34 |
October | 0.768573E+10 | 19650.90 | 18-OCT-07:02 | 25.18 | 18.80 | 0.718024E+09 | 1123.90 | 21-OCT-14:00 | 28.90 | 20.91 |
November | 0.566049E+10 | 16653.58 | 09-NOV-08:62 | 22.85 | 21.36 | 0.690704E+09 | 1123.92 | 04-NOV-14:09 | 22.85 | 21.36 |
December | 0.375042E+10 | 17167.74 | 01-DEC-08:62 | 23.48 | 18.65 | 0.712459E+09 | 1123.98 | 09-DEC-15:00 | 26.10 | 22.26 |
Annual Sum or Average | 0.754559E+11 | 0.852959E+10 | ||||||||
Minimum of Months | 0.338637E+10 | 9182.42 | 21.15 | 18.65 | 0.648474E+09 | 1123.87 | 21.15 | 19.82 | ||
Maximum of Months | 0.893803E+10 | 19650.90 | 28.07 | 24.21 | 0.740273E+09 | 1124.02 | 31.23 | 26.06 |
Report: ZoneHeatingSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 2912148.67 | 1248.57 | 06-JAN-08:07 | 23.40 |
February | 8382422.17 | 5918.88 | 04-FEB-08:62 | 7.25 |
March | 13641607.19 | 1688.83 | 10-MAR-08:05 | 23.98 |
April | 20876870.37 | 2089.76 | 12-APR-07:06 | 25.78 |
May | 37329334.24 | 3133.65 | 20-MAY-07:05 | 26.88 |
June | 35713860.98 | 3643.12 | 08-JUN-07:06 | 28.40 |
July | 29643220.55 | 3605.31 | 08-JUL-07:05 | 28.07 |
August | 31699405.63 | 3792.41 | 17-AUG-07:05 | 28.48 |
September | 28842082.39 | 3378.23 | 22-SEP-07:06 | 27.80 |
October | 27847216.07 | 2905.46 | 12-OCT-07:05 | 26.38 |
November | 12569686.28 | 2818.74 | 21-NOV-08:05 | 26.20 |
December | 7794845.88 | 1885.94 | 06-DEC-08:05 | 24.08 |
Annual Sum or Average | 0.257253E+09 | |||
Minimum of Months | 2912148.67 | 1248.57 | 7.25 | |
Maximum of Months | 37329334.24 | 5918.88 | 28.48 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 1726846.34 | 758.62 | 06-JAN-08:07 | 23.40 |
February | 4203856.30 | 1125.83 | 11-FEB-08:05 | 24.50 |
March | 7873663.49 | 1019.52 | 10-MAR-08:05 | 23.98 |
April | 11447355.92 | 1131.59 | 14-APR-07:05 | 24.18 |
May | 15900495.10 | 1568.17 | 14-MAY-07:05 | 26.78 |
June | 15321068.75 | 1803.59 | 29-JUN-07:05 | 27.48 |
July | 16584079.01 | 2012.76 | 16-JUL-07:04 | 28.40 |
August | 13207045.28 | 2043.18 | 11-AUG-07:05 | 28.48 |
September | 13040159.93 | 1639.89 | 21-SEP-07:05 | 26.88 |
October | 13374778.78 | 1661.16 | 02-OCT-07:05 | 26.97 |
November | 6953207.28 | 1397.21 | 21-NOV-08:05 | 26.20 |
December | 4377438.69 | 1061.39 | 06-DEC-08:05 | 24.08 |
Annual Sum or Average | 0.124010E+09 | |||
Minimum of Months | 1726846.34 | 758.62 | 23.40 | |
Maximum of Months | 16584079.01 | 2043.18 | 28.48 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 3046047.01 | 651.85 | 06-JAN-07:07 | 22.88 |
February | 5946102.59 | 868.70 | 11-FEB-07:05 | 23.98 |
March | 12007265.01 | 824.67 | 05-MAR-17:03 | 26.42 |
April | 32771797.35 | 2062.14 | 15-APR-17:02 | 31.42 |
May | 66661586.13 | 2424.80 | 29-MAY-16:02 | 33.03 |
June | 99080612.68 | 1948.61 | 11-JUN-16:02 | 31.02 |
July | 0.105135E+09 | 2768.53 | 29-JUL-17:02 | 34.22 |
August | 97179757.52 | 1918.33 | 20-AUG-07:06 | 28.98 |
September | 98987342.43 | 1956.91 | 17-SEP-16:02 | 31.10 |
October | 62613827.64 | 1489.63 | 09-OCT-16:02 | 29.32 |
November | 29829903.65 | 1184.38 | 21-NOV-07:05 | 25.18 |
December | 7733858.86 | 1010.41 | 09-DEC-07:05 | 24.40 |
Annual Sum or Average | 0.620993E+09 | |||
Minimum of Months | 3046047.01 | 651.85 | 22.88 | |
Maximum of Months | 0.105135E+09 | 2768.53 | 34.22 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 3107228.92 | 645.31 | 06-JAN-07:07 | 22.88 |
February | 6007248.17 | 874.87 | 11-FEB-07:05 | 23.98 |
March | 12172275.39 | 840.11 | 05-MAR-08:05 | 23.98 |
April | 32891678.74 | 2062.89 | 15-APR-17:02 | 31.42 |
May | 66444445.67 | 2425.64 | 29-MAY-16:02 | 33.03 |
June | 98442878.65 | 1948.09 | 11-JUN-16:02 | 31.02 |
July | 0.104561E+09 | 2768.49 | 29-JUL-17:02 | 34.22 |
August | 97276814.76 | 1942.61 | 20-AUG-07:06 | 28.98 |
September | 98504955.74 | 1956.78 | 17-SEP-16:02 | 31.10 |
October | 62174215.51 | 1488.47 | 09-OCT-16:02 | 29.32 |
November | 29983130.82 | 1190.67 | 21-NOV-07:05 | 25.18 |
December | 7785705.28 | 1013.08 | 09-DEC-07:05 | 24.40 |
Annual Sum or Average | 0.619351E+09 | |||
Minimum of Months | 3107228.92 | 645.31 | 22.88 | |
Maximum of Months | 0.104561E+09 | 2768.49 | 34.22 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 3209664.23 | 620.79 | 07-JAN-07:05 | 22.80 |
February | 6208146.27 | 871.27 | 11-FEB-07:05 | 23.98 |
March | 12538904.24 | 847.17 | 05-MAR-08:05 | 23.98 |
April | 33178969.22 | 2067.36 | 15-APR-17:02 | 31.42 |
May | 68003404.47 | 2429.29 | 29-MAY-16:02 | 33.03 |
June | 0.100571E+09 | 1951.10 | 11-JUN-16:02 | 31.02 |
July | 0.105965E+09 | 2771.97 | 29-JUL-17:02 | 34.22 |
August | 98796341.82 | 1909.13 | 19-AUG-17:02 | 30.82 |
September | 0.100091E+09 | 1959.96 | 17-SEP-16:02 | 31.10 |
October | 64121057.29 | 1492.02 | 09-OCT-16:02 | 29.32 |
November | 30878501.46 | 1184.22 | 30-NOV-07:05 | 25.60 |
December | 7900084.70 | 964.96 | 09-DEC-07:05 | 24.40 |
Annual Sum or Average | 0.631462E+09 | |||
Minimum of Months | 3209664.23 | 620.79 | 22.80 | |
Maximum of Months | 0.105965E+09 | 2771.97 | 34.22 |
Report: ZoneHeatingSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 5784676.67 | 1165.61 | 29-JAN-17:03 | 25.40 |
February | 13051387.45 | 1737.62 | 11-FEB-08:05 | 24.50 |
March | 19461890.72 | 1662.02 | 05-MAR-17:03 | 26.42 |
April | 56117671.47 | 4130.38 | 15-APR-17:02 | 31.42 |
May | 78337588.84 | 4868.60 | 29-MAY-16:02 | 33.03 |
June | 80471677.86 | 3901.03 | 11-JUN-16:02 | 31.02 |
July | 0.104741E+09 | 5535.37 | 29-JUL-17:02 | 34.22 |
August | 73877155.89 | 3815.72 | 19-AUG-17:02 | 30.82 |
September | 98657188.64 | 3922.78 | 17-SEP-16:02 | 31.10 |
October | 71884481.40 | 2992.66 | 09-OCT-16:02 | 29.32 |
November | 31224108.05 | 2636.18 | 21-NOV-08:05 | 26.20 |
December | 16167738.14 | 2322.28 | 10-DEC-09:06 | 25.87 |
Annual Sum or Average | 0.649777E+09 | |||
Minimum of Months | 5784676.67 | 1165.61 | 24.50 | |
Maximum of Months | 0.104741E+09 | 5535.37 | 34.22 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 3245164.09 | 600.23 | 29-JAN-17:03 | 25.40 |
February | 7321981.25 | 1035.06 | 04-FEB-08:04 | 7.25 |
March | 10731145.85 | 863.26 | 05-MAR-09:05 | 24.50 |
April | 29397328.18 | 2082.58 | 15-APR-17:02 | 31.42 |
May | 36481498.57 | 2440.70 | 29-MAY-16:02 | 33.03 |
June | 39125235.91 | 1960.29 | 11-JUN-16:02 | 31.02 |
July | 52708064.22 | 2784.34 | 29-JUL-17:02 | 34.22 |
August | 35937193.38 | 1939.74 | 20-AUG-08:07 | 29.40 |
September | 49244360.64 | 1970.40 | 17-SEP-16:02 | 31.10 |
October | 35233458.70 | 1521.36 | 09-OCT-08:06 | 27.38 |
November | 15556580.77 | 1322.74 | 21-NOV-08:05 | 26.20 |
December | 8391880.81 | 1179.49 | 10-DEC-09:06 | 25.87 |
Annual Sum or Average | 0.323374E+09 | |||
Minimum of Months | 3245164.09 | 600.23 | 7.25 | |
Maximum of Months | 52708064.22 | 2784.34 | 34.22 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 3219666.39 | 602.23 | 29-JAN-17:03 | 25.40 |
February | 7423748.07 | 1526.70 | 04-FEB-08:04 | 7.25 |
March | 10914778.65 | 866.44 | 05-MAR-09:05 | 24.50 |
April | 29359053.34 | 2083.37 | 15-APR-17:02 | 31.42 |
May | 36649352.95 | 2441.46 | 29-MAY-16:02 | 33.03 |
June | 39291245.71 | 1960.78 | 11-JUN-16:02 | 31.02 |
July | 52982700.99 | 2784.85 | 29-JUL-17:02 | 34.22 |
August | 36015912.62 | 1938.14 | 20-AUG-08:07 | 29.40 |
September | 49296924.84 | 1970.96 | 17-SEP-16:02 | 31.10 |
October | 35400775.38 | 1515.79 | 09-OCT-08:06 | 27.38 |
November | 15674754.52 | 1312.06 | 21-NOV-08:05 | 26.20 |
December | 8460099.38 | 1168.34 | 10-DEC-09:06 | 25.87 |
Annual Sum or Average | 0.324689E+09 | |||
Minimum of Months | 3219666.39 | 602.23 | 7.25 | |
Maximum of Months | 52982700.99 | 2784.85 | 34.22 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 3530957.36 | 607.19 | 29-JAN-17:03 | 25.40 |
February | 8726042.35 | 2705.41 | 04-FEB-08:62 | 7.25 |
March | 11071855.76 | 902.73 | 16-MAR-07:10 | 6.97 |
April | 29378942.62 | 2083.42 | 15-APR-17:02 | 31.42 |
May | 37038713.05 | 2441.94 | 29-MAY-16:02 | 33.03 |
June | 39956450.16 | 1959.64 | 11-JUN-16:02 | 31.02 |
July | 54981763.57 | 2783.16 | 29-JUL-17:02 | 34.22 |
August | 36344233.65 | 1940.32 | 20-AUG-08:07 | 29.40 |
September | 48709763.18 | 1970.01 | 17-SEP-16:02 | 31.10 |
October | 35298791.95 | 1553.82 | 09-OCT-08:06 | 27.38 |
November | 16122821.68 | 1296.96 | 21-NOV-08:05 | 26.20 |
December | 8566221.83 | 1129.01 | 10-DEC-09:06 | 25.87 |
Annual Sum or Average | 0.329727E+09 | |||
Minimum of Months | 3530957.36 | 607.19 | 6.97 | |
Maximum of Months | 54981763.57 | 2783.16 | 34.22 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 6219421.28 | 3024.59 | 25-JAN-08:65 | 10.18 |
February | 20497006.18 | 26918.63 | 04-FEB-08:62 | 7.25 |
March | 17992807.95 | 7475.02 | 16-MAR-07:03 | 6.97 |
April | 29216785.42 | 2060.65 | 15-APR-17:02 | 31.42 |
May | 35871062.30 | 2412.01 | 29-MAY-16:02 | 33.03 |
June | 34845574.03 | 1934.33 | 11-JUN-16:02 | 31.02 |
July | 49343861.03 | 2744.05 | 29-JUL-17:02 | 34.22 |
August | 34604198.16 | 2066.91 | 17-AUG-07:05 | 28.48 |
September | 45571927.70 | 1940.62 | 17-SEP-16:02 | 31.10 |
October | 35001308.76 | 1705.59 | 29-OCT-08:05 | 27.48 |
November | 15624746.40 | 1398.41 | 21-NOV-08:05 | 26.20 |
December | 10738607.20 | 2113.24 | 15-DEC-08:63 | 8.68 |
Annual Sum or Average | 0.335527E+09 | |||
Minimum of Months | 6219421.28 | 1398.41 | 6.97 | |
Maximum of Months | 49343861.03 | 26918.63 | 34.22 |
Report: ZoneElectricSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.739462E+10 | 4621.63 | 01-JAN-10:09 | 0.222596E+10 | 1343.25 | 01-JAN-10:09 |
February | 0.668410E+10 | 4621.63 | 01-FEB-10:09 | 0.201408E+10 | 1343.25 | 01-FEB-10:09 |
March | 0.740180E+10 | 4621.63 | 01-MAR-10:09 | 0.223295E+10 | 1343.25 | 01-MAR-10:09 |
April | 0.716384E+10 | 4621.63 | 01-APR-09:09 | 0.215748E+10 | 1343.25 | 01-APR-09:09 |
May | 0.739462E+10 | 4621.63 | 01-MAY-09:09 | 0.222596E+10 | 1343.25 | 01-MAY-09:09 |
June | 0.716485E+10 | 4621.63 | 01-JUN-09:09 | 0.216232E+10 | 1343.25 | 01-JUN-09:09 |
July | 0.740069E+10 | 4621.63 | 01-JUL-09:09 | 0.222811E+10 | 1343.25 | 01-JUL-09:09 |
August | 0.739513E+10 | 4621.63 | 01-AUG-09:09 | 0.222838E+10 | 1343.25 | 01-AUG-09:09 |
September | 0.717041E+10 | 4621.63 | 01-SEP-09:09 | 0.216205E+10 | 1343.25 | 01-SEP-09:09 |
October | 0.739462E+10 | 4621.63 | 01-OCT-09:09 | 0.222596E+10 | 1343.25 | 01-OCT-09:09 |
November | 0.714323E+10 | 4621.63 | 01-NOV-09:09 | 0.215077E+10 | 1343.25 | 01-NOV-09:09 |
December | 0.740776E+10 | 4621.63 | 01-DEC-10:09 | 0.223509E+10 | 1343.25 | 01-DEC-10:09 |
Annual Sum or Average | 0.871157E+11 | 0.262491E+11 | ||||
Minimum of Months | 0.668410E+10 | 4621.63 | 0.201408E+10 | 1343.25 | ||
Maximum of Months | 0.740776E+10 | 4621.63 | 0.223509E+10 | 1343.25 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.451584E+10 | 2827.07 | 01-JAN-10:09 | 0.111298E+10 | 671.63 | 01-JAN-10:09 |
February | 0.408193E+10 | 2827.07 | 01-FEB-10:09 | 0.100704E+10 | 671.63 | 01-FEB-10:09 |
March | 0.452026E+10 | 2827.07 | 01-MAR-10:09 | 0.111647E+10 | 671.63 | 01-MAR-10:09 |
April | 0.437489E+10 | 2827.07 | 01-APR-09:09 | 0.107874E+10 | 671.63 | 01-APR-09:09 |
May | 0.451584E+10 | 2827.07 | 01-MAY-09:09 | 0.111298E+10 | 671.63 | 01-MAY-09:09 |
June | 0.437556E+10 | 2827.07 | 01-JUN-09:09 | 0.108116E+10 | 671.63 | 01-JUN-09:09 |
July | 0.451952E+10 | 2827.07 | 01-JUL-09:09 | 0.111405E+10 | 671.63 | 01-JUL-09:09 |
August | 0.451617E+10 | 2827.07 | 01-AUG-09:09 | 0.111419E+10 | 671.63 | 01-AUG-09:09 |
September | 0.437891E+10 | 2827.07 | 01-SEP-09:09 | 0.108102E+10 | 671.63 | 01-SEP-09:09 |
October | 0.451584E+10 | 2827.07 | 01-OCT-09:09 | 0.111298E+10 | 671.63 | 01-OCT-09:09 |
November | 0.436230E+10 | 2827.07 | 01-NOV-09:09 | 0.107538E+10 | 671.63 | 01-NOV-09:09 |
December | 0.452388E+10 | 2827.07 | 01-DEC-10:09 | 0.111755E+10 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.532009E+11 | 0.131245E+11 | ||||
Minimum of Months | 0.408193E+10 | 2827.07 | 0.100704E+10 | 671.63 | ||
Maximum of Months | 0.452388E+10 | 2827.07 | 0.111755E+10 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.317044E+10 | 2555.22 | 01-JAN-10:09 | 0.879849E+09 | 671.63 | 01-JAN-10:09 |
February | 0.287181E+10 | 2555.22 | 01-FEB-09:09 | 0.796766E+09 | 671.63 | 01-FEB-09:09 |
March | 0.324295E+10 | 2555.22 | 01-MAR-09:09 | 0.898128E+09 | 671.63 | 01-MAR-09:09 |
April | 0.307694E+10 | 2555.22 | 01-APR-08:09 | 0.853677E+09 | 671.63 | 01-APR-08:09 |
May | 0.320669E+10 | 2555.22 | 01-MAY-08:09 | 0.888989E+09 | 671.63 | 01-MAY-08:09 |
June | 0.313132E+10 | 2555.22 | 01-JUN-08:09 | 0.867387E+09 | 671.63 | 01-JUN-08:09 |
July | 0.315231E+10 | 2555.22 | 01-JUL-08:09 | 0.875279E+09 | 671.63 | 01-JUL-08:09 |
August | 0.324295E+10 | 2555.22 | 01-AUG-08:09 | 0.898128E+09 | 671.63 | 01-AUG-08:09 |
September | 0.307694E+10 | 2555.22 | 01-SEP-08:09 | 0.853677E+09 | 671.63 | 01-SEP-08:09 |
October | 0.317044E+10 | 2555.22 | 01-OCT-09:09 | 0.879849E+09 | 671.63 | 01-OCT-09:09 |
November | 0.307694E+10 | 2555.22 | 01-NOV-08:09 | 0.853679E+09 | 671.63 | 01-NOV-08:09 |
December | 0.315231E+10 | 2555.22 | 01-DEC-09:09 | 0.875279E+09 | 671.63 | 01-DEC-09:09 |
Annual Sum or Average | 0.375720E+11 | 0.104207E+11 | ||||
Minimum of Months | 0.287181E+10 | 2555.22 | 0.796766E+09 | 671.63 | ||
Maximum of Months | 0.324295E+10 | 2555.22 | 0.898128E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.317044E+10 | 2555.22 | 01-JAN-10:09 | 0.879849E+09 | 671.63 | 01-JAN-10:09 |
February | 0.287181E+10 | 2555.22 | 01-FEB-09:09 | 0.796766E+09 | 671.63 | 01-FEB-09:09 |
March | 0.324295E+10 | 2555.22 | 01-MAR-09:09 | 0.898128E+09 | 671.63 | 01-MAR-09:09 |
April | 0.307694E+10 | 2555.22 | 01-APR-08:09 | 0.853677E+09 | 671.63 | 01-APR-08:09 |
May | 0.320669E+10 | 2555.22 | 01-MAY-08:09 | 0.888989E+09 | 671.63 | 01-MAY-08:09 |
June | 0.313132E+10 | 2555.22 | 01-JUN-08:09 | 0.867387E+09 | 671.63 | 01-JUN-08:09 |
July | 0.315231E+10 | 2555.22 | 01-JUL-08:09 | 0.875279E+09 | 671.63 | 01-JUL-08:09 |
August | 0.324295E+10 | 2555.22 | 01-AUG-08:09 | 0.898128E+09 | 671.63 | 01-AUG-08:09 |
September | 0.307694E+10 | 2555.22 | 01-SEP-08:09 | 0.853677E+09 | 671.63 | 01-SEP-08:09 |
October | 0.317044E+10 | 2555.22 | 01-OCT-09:09 | 0.879849E+09 | 671.63 | 01-OCT-09:09 |
November | 0.307694E+10 | 2555.22 | 01-NOV-08:09 | 0.853679E+09 | 671.63 | 01-NOV-08:09 |
December | 0.315231E+10 | 2555.22 | 01-DEC-09:09 | 0.875279E+09 | 671.63 | 01-DEC-09:09 |
Annual Sum or Average | 0.375720E+11 | 0.104207E+11 | ||||
Minimum of Months | 0.287181E+10 | 2555.22 | 0.796766E+09 | 671.63 | ||
Maximum of Months | 0.324295E+10 | 2555.22 | 0.898128E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.317044E+10 | 2555.22 | 01-JAN-10:09 | 0.879849E+09 | 671.63 | 01-JAN-10:09 |
February | 0.287181E+10 | 2555.22 | 01-FEB-09:09 | 0.796766E+09 | 671.63 | 01-FEB-09:09 |
March | 0.324295E+10 | 2555.22 | 01-MAR-09:09 | 0.898128E+09 | 671.63 | 01-MAR-09:09 |
April | 0.307694E+10 | 2555.22 | 01-APR-08:09 | 0.853677E+09 | 671.63 | 01-APR-08:09 |
May | 0.320669E+10 | 2555.22 | 01-MAY-08:09 | 0.888989E+09 | 671.63 | 01-MAY-08:09 |
June | 0.313132E+10 | 2555.22 | 01-JUN-08:09 | 0.867387E+09 | 671.63 | 01-JUN-08:09 |
July | 0.315231E+10 | 2555.22 | 01-JUL-08:09 | 0.875279E+09 | 671.63 | 01-JUL-08:09 |
August | 0.324295E+10 | 2555.22 | 01-AUG-08:09 | 0.898128E+09 | 671.63 | 01-AUG-08:09 |
September | 0.307694E+10 | 2555.22 | 01-SEP-08:09 | 0.853677E+09 | 671.63 | 01-SEP-08:09 |
October | 0.317044E+10 | 2555.22 | 01-OCT-09:09 | 0.879849E+09 | 671.63 | 01-OCT-09:09 |
November | 0.307694E+10 | 2555.22 | 01-NOV-08:09 | 0.853679E+09 | 671.63 | 01-NOV-08:09 |
December | 0.315231E+10 | 2555.22 | 01-DEC-09:09 | 0.875279E+09 | 671.63 | 01-DEC-09:09 |
Annual Sum or Average | 0.375720E+11 | 0.104207E+11 | ||||
Minimum of Months | 0.287181E+10 | 2555.22 | 0.796766E+09 | 671.63 | ||
Maximum of Months | 0.324295E+10 | 2555.22 | 0.898128E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.313454E+10 | 2726.96 | 01-JAN-11:09 | 0.161799E+10 | 1343.25 | 01-JAN-11:09 |
February | 0.283982E+10 | 2726.96 | 01-FEB-10:09 | 0.146554E+10 | 1343.25 | 01-FEB-10:09 |
March | 0.321092E+10 | 2726.96 | 01-MAR-10:09 | 0.165455E+10 | 1343.25 | 01-MAR-10:09 |
April | 0.304266E+10 | 2726.96 | 01-APR-09:09 | 0.157022E+10 | 1343.25 | 01-APR-09:09 |
May | 0.317273E+10 | 2726.96 | 01-MAY-09:09 | 0.163627E+10 | 1343.25 | 01-MAY-09:09 |
June | 0.309995E+10 | 2726.96 | 01-JUN-09:09 | 0.159764E+10 | 1343.25 | 01-JUN-09:09 |
July | 0.311545E+10 | 2726.96 | 01-JUL-09:09 | 0.160885E+10 | 1343.25 | 01-JUL-09:09 |
August | 0.321092E+10 | 2726.96 | 01-AUG-09:09 | 0.165455E+10 | 1343.25 | 01-AUG-09:09 |
September | 0.304266E+10 | 2726.96 | 01-SEP-09:09 | 0.157022E+10 | 1343.25 | 01-SEP-09:09 |
October | 0.313454E+10 | 2726.96 | 01-OCT-10:09 | 0.161799E+10 | 1343.25 | 01-OCT-10:09 |
November | 0.304266E+10 | 2726.96 | 01-NOV-09:09 | 0.157022E+10 | 1343.25 | 01-NOV-09:09 |
December | 0.311545E+10 | 2726.96 | 01-DEC-10:09 | 0.160885E+10 | 1343.25 | 01-DEC-10:09 |
Annual Sum or Average | 0.371623E+11 | 0.191729E+11 | ||||
Minimum of Months | 0.283982E+10 | 2726.96 | 0.146554E+10 | 1343.25 | ||
Maximum of Months | 0.321092E+10 | 2726.96 | 0.165455E+10 | 1343.25 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.161274E+10 | 1404.46 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.146111E+10 | 1404.46 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.165211E+10 | 1404.46 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.156548E+10 | 1404.46 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.163243E+10 | 1404.46 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.159501E+10 | 1404.46 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.160290E+10 | 1404.46 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.165211E+10 | 1404.46 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.156548E+10 | 1404.46 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.161274E+10 | 1404.46 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.156548E+10 | 1404.46 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.160290E+10 | 1404.46 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.191205E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.146111E+10 | 1404.46 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.165211E+10 | 1404.46 | 0.827277E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.161274E+10 | 1404.46 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.146111E+10 | 1404.46 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.165211E+10 | 1404.46 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.156548E+10 | 1404.46 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.163243E+10 | 1404.46 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.159501E+10 | 1404.46 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.160290E+10 | 1404.46 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.165211E+10 | 1404.46 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.156548E+10 | 1404.46 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.161274E+10 | 1404.46 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.156548E+10 | 1404.46 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.160290E+10 | 1404.46 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.191205E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.146111E+10 | 1404.46 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.165211E+10 | 1404.46 | 0.827277E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.161274E+10 | 1404.46 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.146111E+10 | 1404.46 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.165211E+10 | 1404.46 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.156548E+10 | 1404.46 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.163243E+10 | 1404.46 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.159501E+10 | 1404.46 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.160290E+10 | 1404.46 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.165211E+10 | 1404.46 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.156548E+10 | 1404.46 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.161274E+10 | 1404.46 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.156548E+10 | 1404.46 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.160290E+10 | 1404.46 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.191205E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.146111E+10 | 1404.46 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.165211E+10 | 1404.46 | 0.827277E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.161274E+10 | 1404.46 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.146111E+10 | 1404.46 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.165211E+10 | 1404.46 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.156548E+10 | 1404.46 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.163243E+10 | 1404.46 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.159501E+10 | 1404.46 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.160290E+10 | 1404.46 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.165211E+10 | 1404.46 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.156548E+10 | 1404.46 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.161274E+10 | 1404.46 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.156548E+10 | 1404.46 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.160290E+10 | 1404.46 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.191205E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.146111E+10 | 1404.46 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.165211E+10 | 1404.46 | 0.827277E+09 | 671.63 |
Report: SpaceGainsMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.338624E+10 | 0.739462E+10 | 0.222596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.229233E+09 | 0.114099E+10 |
February | 0.305697E+10 | 0.668410E+10 | 0.201408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.394703E+09 | 0.649306E+09 |
March | 0.335708E+10 | 0.740180E+10 | 0.223295E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.429994E+09 | 0.748121E+09 |
April | 0.327081E+10 | 0.716384E+10 | 0.215748E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.981262E+09 | 0.159946E+09 |
May | 0.336680E+10 | 0.739462E+10 | 0.222596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.176724E+10 | 51050616.68 |
June | 0.325380E+10 | 0.716485E+10 | 0.216232E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192124E+10 | 10224372.22 |
July | 0.339353E+10 | 0.740069E+10 | 0.222811E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.247509E+10 | 13033270.12 |
August | 0.334857E+10 | 0.739513E+10 | 0.222838E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219906E+10 | 19572801.30 |
September | 0.327932E+10 | 0.717041E+10 | 0.216205E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.206136E+10 | 16272293.59 |
October | 0.338624E+10 | 0.739462E+10 | 0.222596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168018E+10 | 36950412.12 |
November | 0.327446E+10 | 0.714323E+10 | 0.215077E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.882892E+09 | 0.323054E+09 |
December | 0.340325E+10 | 0.740776E+10 | 0.223509E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.322771E+09 | 0.991833E+09 |
Annual Sum or Average | 0.397770E+11 | 0.871157E+11 | 0.262491E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153450E+11 | 0.416035E+10 |
Minimum of Months | 0.305697E+10 | 0.668410E+10 | 0.201408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.229233E+09 | 10224372.22 |
Maximum of Months | 0.340325E+10 | 0.740776E+10 | 0.223509E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.247509E+10 | 0.114099E+10 |
Report: SpaceGainsMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.169307E+10 | 0.451584E+10 | 0.111298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128329E+09 | 0.591140E+09 |
February | 0.152844E+10 | 0.408193E+10 | 0.100704E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.220068E+09 | 0.292379E+09 |
March | 0.167849E+10 | 0.452026E+10 | 0.111647E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.239101E+09 | 0.356156E+09 |
April | 0.163536E+10 | 0.437489E+10 | 0.107874E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.547882E+09 | 62284000.04 |
May | 0.168335E+10 | 0.451584E+10 | 0.111298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.977411E+09 | 19251656.64 |
June | 0.162685E+10 | 0.437556E+10 | 0.108116E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106051E+10 | 3862751.69 |
July | 0.169671E+10 | 0.451952E+10 | 0.111405E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138250E+10 | 5276540.66 |
August | 0.167424E+10 | 0.451617E+10 | 0.111419E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121719E+10 | 9068738.59 |
September | 0.163961E+10 | 0.437891E+10 | 0.108102E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114365E+10 | 4841416.75 |
October | 0.169307E+10 | 0.451584E+10 | 0.111298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.935289E+09 | 12101501.82 |
November | 0.163718E+10 | 0.436230E+10 | 0.107538E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.491622E+09 | 0.139746E+09 |
December | 0.170157E+10 | 0.452388E+10 | 0.111755E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180844E+09 | 0.502822E+09 |
Annual Sum or Average | 0.198880E+11 | 0.532009E+11 | 0.131245E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.852440E+10 | 0.199893E+10 |
Minimum of Months | 0.152844E+10 | 0.408193E+10 | 0.100704E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128329E+09 | 3862751.69 |
Maximum of Months | 0.170157E+10 | 0.452388E+10 | 0.111755E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138250E+10 | 0.591140E+09 |
Report: SpaceGainsMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.317044E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126962E+09 | 0.613087E+09 |
February | 0.914877E+09 | 0.287181E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.216142E+09 | 0.320954E+09 |
March | 0.103395E+10 | 0.324295E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.234919E+09 | 0.380215E+09 |
April | 0.984131E+09 | 0.307694E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.533340E+09 | 81125986.43 |
May | 0.102058E+10 | 0.320669E+10 | 0.888989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.958432E+09 | 29249436.74 |
June | 0.998711E+09 | 0.313132E+10 | 0.867387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104400E+10 | 6913790.85 |
July | 0.100600E+10 | 0.315231E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135597E+10 | 10343811.63 |
August | 0.103395E+10 | 0.324295E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119820E+10 | 10886672.19 |
September | 0.984131E+09 | 0.307694E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112001E+10 | 8117711.83 |
October | 0.100722E+10 | 0.317044E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.909787E+09 | 17691609.03 |
November | 0.973196E+09 | 0.307694E+10 | 0.853679E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.480373E+09 | 0.156916E+09 |
December | 0.100600E+10 | 0.315231E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175445E+09 | 0.527738E+09 |
Annual Sum or Average | 0.119700E+11 | 0.375720E+11 | 0.104207E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.835358E+10 | 0.216324E+10 |
Minimum of Months | 0.914877E+09 | 0.287181E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126962E+09 | 6913790.85 |
Maximum of Months | 0.103395E+10 | 0.324295E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135597E+10 | 0.613087E+09 |
Report: SpaceGainsMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.317044E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126965E+09 | 0.611552E+09 |
February | 0.914877E+09 | 0.287181E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.216147E+09 | 0.319441E+09 |
March | 0.103395E+10 | 0.324295E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.234924E+09 | 0.378842E+09 |
April | 0.984131E+09 | 0.307694E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.533297E+09 | 81223997.11 |
May | 0.102058E+10 | 0.320669E+10 | 0.888989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.958235E+09 | 29712724.04 |
June | 0.998711E+09 | 0.313132E+10 | 0.867387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104341E+10 | 7172262.35 |
July | 0.100600E+10 | 0.315231E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135543E+10 | 10706781.19 |
August | 0.103395E+10 | 0.324295E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119756E+10 | 11025646.53 |
September | 0.984131E+09 | 0.307694E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111931E+10 | 8427710.64 |
October | 0.100722E+10 | 0.317044E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.909500E+09 | 18156013.07 |
November | 0.973196E+09 | 0.307694E+10 | 0.853679E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.480322E+09 | 0.156759E+09 |
December | 0.100600E+10 | 0.315231E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175451E+09 | 0.526481E+09 |
Annual Sum or Average | 0.119700E+11 | 0.375720E+11 | 0.104207E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.835056E+10 | 0.215950E+10 |
Minimum of Months | 0.914877E+09 | 0.287181E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126965E+09 | 7172262.35 |
Maximum of Months | 0.103395E+10 | 0.324295E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135543E+10 | 0.611552E+09 |
Report: SpaceGainsMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.317044E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126972E+09 | 0.607426E+09 |
February | 0.914877E+09 | 0.287181E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.216165E+09 | 0.314965E+09 |
March | 0.103395E+10 | 0.324295E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.234948E+09 | 0.373658E+09 |
April | 0.984131E+09 | 0.307694E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.533469E+09 | 78948785.12 |
May | 0.102058E+10 | 0.320669E+10 | 0.888989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.958839E+09 | 27559626.36 |
June | 0.998711E+09 | 0.313132E+10 | 0.867387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104470E+10 | 6569331.41 |
July | 0.100600E+10 | 0.315231E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135628E+10 | 10092839.02 |
August | 0.103395E+10 | 0.324295E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119882E+10 | 10666846.88 |
September | 0.984131E+09 | 0.307694E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112035E+10 | 7852226.41 |
October | 0.100722E+10 | 0.317044E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.910155E+09 | 16906256.29 |
November | 0.973196E+09 | 0.307694E+10 | 0.853679E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.480680E+09 | 0.154535E+09 |
December | 0.100600E+10 | 0.315231E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175477E+09 | 0.522709E+09 |
Annual Sum or Average | 0.119700E+11 | 0.375720E+11 | 0.104207E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.835685E+10 | 0.213189E+10 |
Minimum of Months | 0.914877E+09 | 0.287181E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126972E+09 | 6569331.41 |
Maximum of Months | 0.103395E+10 | 0.324295E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135628E+10 | 0.607426E+09 |
Report: SpaceGainsMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.344359E+10 | 0.313454E+10 | 0.161799E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222904E+09 | 0.107293E+10 |
February | 0.313522E+10 | 0.283982E+10 | 0.146554E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.379718E+09 | 0.574673E+09 |
March | 0.355148E+10 | 0.321092E+10 | 0.165455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.412903E+09 | 0.669392E+09 |
April | 0.338259E+10 | 0.304266E+10 | 0.157022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.937762E+09 | 0.145119E+09 |
May | 0.349753E+10 | 0.317273E+10 | 0.163627E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168900E+10 | 46581848.65 |
June | 0.343071E+10 | 0.309995E+10 | 0.159764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.184494E+10 | 11717140.51 |
July | 0.344942E+10 | 0.311545E+10 | 0.160885E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.238276E+10 | 16906792.57 |
August | 0.355148E+10 | 0.321092E+10 | 0.165455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.211404E+10 | 19146818.30 |
September | 0.338259E+10 | 0.304266E+10 | 0.157022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.197347E+10 | 14997876.37 |
October | 0.344359E+10 | 0.313454E+10 | 0.161799E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160110E+10 | 32430159.74 |
November | 0.331698E+10 | 0.304266E+10 | 0.157022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.845788E+09 | 0.286150E+09 |
December | 0.344942E+10 | 0.311545E+10 | 0.160885E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.307915E+09 | 0.931834E+09 |
Annual Sum or Average | 0.410346E+11 | 0.371623E+11 | 0.191729E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147123E+11 | 0.382188E+10 |
Minimum of Months | 0.313522E+10 | 0.283982E+10 | 0.146554E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222904E+09 | 11717140.51 |
Maximum of Months | 0.355148E+10 | 0.321092E+10 | 0.165455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.238276E+10 | 0.107293E+10 |
Report: SpaceGainsMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.161274E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127029E+09 | 0.598483E+09 |
February | 0.156756E+10 | 0.146111E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.216254E+09 | 0.310302E+09 |
March | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235080E+09 | 0.365262E+09 |
April | 0.169125E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.534440E+09 | 75652153.75 |
May | 0.174872E+10 | 0.163243E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.961610E+09 | 23597228.61 |
June | 0.171530E+10 | 0.159501E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104976E+10 | 5866306.80 |
July | 0.172466E+10 | 0.160290E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135836E+10 | 8687447.38 |
August | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120340E+10 | 10313323.01 |
September | 0.169125E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112381E+10 | 7243418.56 |
October | 0.172174E+10 | 0.161274E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.912484E+09 | 16048638.82 |
November | 0.165844E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.482002E+09 | 0.153799E+09 |
December | 0.172466E+10 | 0.160290E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175502E+09 | 0.517848E+09 |
Annual Sum or Average | 0.205167E+11 | 0.191205E+11 | 0.958644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.837973E+10 | 0.209310E+10 |
Minimum of Months | 0.156756E+10 | 0.146111E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127029E+09 | 5866306.80 |
Maximum of Months | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135836E+10 | 0.598483E+09 |
Report: SpaceGainsMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.161274E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127032E+09 | 0.596560E+09 |
February | 0.156756E+10 | 0.146111E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.216264E+09 | 0.308839E+09 |
March | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235086E+09 | 0.363666E+09 |
April | 0.169125E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.534507E+09 | 75185953.97 |
May | 0.174872E+10 | 0.163243E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.961811E+09 | 23298476.07 |
June | 0.171530E+10 | 0.159501E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105001E+10 | 5783611.94 |
July | 0.172466E+10 | 0.160290E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135856E+10 | 8606728.61 |
August | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120363E+10 | 10261520.57 |
September | 0.169125E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112401E+10 | 7151355.41 |
October | 0.172174E+10 | 0.161274E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.912658E+09 | 15852294.42 |
November | 0.165844E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.482110E+09 | 0.153283E+09 |
December | 0.172466E+10 | 0.160290E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175513E+09 | 0.516379E+09 |
Annual Sum or Average | 0.205167E+11 | 0.191205E+11 | 0.958644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.838118E+10 | 0.208487E+10 |
Minimum of Months | 0.156756E+10 | 0.146111E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127032E+09 | 5783611.94 |
Maximum of Months | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135856E+10 | 0.596560E+09 |
Report: SpaceGainsMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.161274E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127037E+09 | 0.591559E+09 |
February | 0.156756E+10 | 0.146111E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.216280E+09 | 0.304319E+09 |
March | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235090E+09 | 0.359582E+09 |
April | 0.169125E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.534551E+09 | 73846709.39 |
May | 0.174872E+10 | 0.163243E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.962117E+09 | 22547300.84 |
June | 0.171530E+10 | 0.159501E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105016E+10 | 5625868.99 |
July | 0.172466E+10 | 0.160290E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135851E+10 | 8583169.95 |
August | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120371E+10 | 10180269.40 |
September | 0.169125E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112389E+10 | 7062733.02 |
October | 0.172174E+10 | 0.161274E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.912782E+09 | 15508680.94 |
November | 0.165844E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.482353E+09 | 0.151817E+09 |
December | 0.172466E+10 | 0.160290E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175526E+09 | 0.512033E+09 |
Annual Sum or Average | 0.205167E+11 | 0.191205E+11 | 0.958644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.838200E+10 | 0.206266E+10 |
Minimum of Months | 0.156756E+10 | 0.146111E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127037E+09 | 5625868.99 |
Maximum of Months | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135851E+10 | 0.591559E+09 |
Report: SpaceGainsMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.161274E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130983E+09 | 0.704726E+09 |
February | 0.156756E+10 | 0.146111E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.224433E+09 | 0.445666E+09 |
March | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.244709E+09 | 0.492142E+09 |
April | 0.169125E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.552020E+09 | 0.129586E+09 |
May | 0.174872E+10 | 0.163243E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100691E+10 | 42746832.57 |
June | 0.171530E+10 | 0.159501E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110689E+10 | 11703003.47 |
July | 0.172466E+10 | 0.160290E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140095E+10 | 16745014.29 |
August | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126054E+10 | 15288124.03 |
September | 0.169125E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117172E+10 | 18086488.81 |
October | 0.172174E+10 | 0.161274E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.944415E+09 | 34910607.80 |
November | 0.165844E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.499928E+09 | 0.234026E+09 |
December | 0.172466E+10 | 0.160290E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180584E+09 | 0.629789E+09 |
Annual Sum or Average | 0.205167E+11 | 0.191205E+11 | 0.958644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.872409E+10 | 0.277541E+10 |
Minimum of Months | 0.156756E+10 | 0.146111E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130983E+09 | 11703003.47 |
Maximum of Months | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140095E+10 | 0.704726E+09 |
Report: PeakSpaceGainsMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 4050.04 | 01-JAN-13:09 | 4621.63 | 01-JAN-10:09 | 1343.25 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2367.87 | 02-JAN-15:00 | 4533.99 | 24-JAN-12:10 |
February | 4050.04 | 03-FEB-13:09 | 4621.63 | 01-FEB-10:09 | 1343.25 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2611.88 | 11-FEB-14:00 | 4394.55 | 03-FEB-18:00 |
March | 4050.04 | 03-MAR-13:09 | 4621.63 | 01-MAR-10:09 | 1343.25 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2613.33 | 13-MAR-16:00 | 4689.80 | 15-MAR-11:05 |
April | 4050.04 | 01-APR-12:09 | 4621.63 | 01-APR-09:09 | 1343.25 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3882.01 | 17-APR-15:00 | 1598.08 | 25-APR-16:00 |
May | 4050.04 | 05-MAY-12:09 | 4621.63 | 01-MAY-09:09 | 1343.25 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4900.42 | 22-MAY-13:00 | 1092.68 | 10-MAY-15:00 |
June | 4050.04 | 02-JUN-12:09 | 4621.63 | 01-JUN-09:09 | 1343.25 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3871.02 | 11-JUN-13:00 | 521.58 | 05-JUN-15:00 |
July | 4050.04 | 01-JUL-12:09 | 4621.63 | 01-JUL-09:09 | 1343.25 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5358.49 | 29-JUL-16:00 | 530.64 | 02-JUL-16:00 |
August | 4050.04 | 04-AUG-12:09 | 4621.63 | 01-AUG-09:09 | 1343.25 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4697.13 | 23-AUG-13:00 | 817.24 | 28-AUG-12:00 |
September | 4050.04 | 01-SEP-12:09 | 4621.63 | 01-SEP-09:09 | 1343.25 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3946.64 | 20-SEP-14:00 | 100.17 | 16-SEP-05:00 |
October | 4050.04 | 01-OCT-12:09 | 4621.63 | 01-OCT-09:09 | 1343.25 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3861.62 | 14-OCT-13:00 | 1060.04 | 26-OCT-14:00 |
November | 4050.04 | 03-NOV-12:09 | 4621.63 | 01-NOV-09:09 | 1343.25 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2865.48 | 17-NOV-15:00 | 2775.89 | 12-NOV-18:00 |
December | 4050.04 | 01-DEC-13:09 | 4621.63 | 01-DEC-10:09 | 1343.25 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2409.79 | 10-DEC-15:00 | 4959.08 | 20-DEC-12:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 4050.04 | 4621.63 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 2367.87 | 100.17 | |||||
Maximum of Months | 4050.04 | 4621.63 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 5358.49 | 4959.08 |
Report: PeakSpaceGainsMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 01-JAN-13:09 | 2827.07 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1335.83 | 02-JAN-15:00 | 2605.58 | 24-JAN-12:10 |
February | 2024.96 | 03-FEB-13:09 | 2827.07 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1471.26 | 11-FEB-14:00 | 2507.63 | 03-FEB-12:10 |
March | 2024.96 | 03-MAR-13:09 | 2827.07 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1464.79 | 13-MAR-16:00 | 2786.83 | 15-MAR-11:05 |
April | 2024.96 | 01-APR-12:09 | 2827.07 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2182.64 | 17-APR-15:00 | 901.59 | 25-APR-16:00 |
May | 2024.96 | 05-MAY-12:09 | 2827.07 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2750.99 | 22-MAY-13:00 | 607.66 | 10-MAY-15:00 |
June | 2024.96 | 02-JUN-12:09 | 2827.07 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2187.35 | 11-JUN-13:00 | 296.13 | 05-JUN-15:00 |
July | 2024.96 | 01-JUL-12:09 | 2827.07 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3027.86 | 29-JUL-16:00 | 298.91 | 02-JUL-16:00 |
August | 2024.96 | 04-AUG-12:09 | 2827.07 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2636.87 | 23-AUG-13:00 | 462.52 | 28-AUG-12:00 |
September | 2024.96 | 01-SEP-12:09 | 2827.07 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2205.41 | 20-SEP-14:00 | 39.67 | 27-SEP-07:02 |
October | 2024.96 | 01-OCT-12:09 | 2827.07 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2178.62 | 14-OCT-13:00 | 598.04 | 26-OCT-14:00 |
November | 2024.96 | 03-NOV-12:09 | 2827.07 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1616.68 | 17-NOV-15:00 | 1558.35 | 12-NOV-18:00 |
December | 2024.96 | 01-DEC-13:09 | 2827.07 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1342.58 | 10-DEC-15:00 | 2905.71 | 20-DEC-12:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 2827.07 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1335.83 | 39.67 | |||||
Maximum of Months | 2024.96 | 2827.07 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 3027.86 | 2905.71 |
Report: PeakSpaceGainsMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 2555.22 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1335.96 | 02-JAN-15:00 | 2599.04 | 24-JAN-12:10 |
February | 2024.96 | 04-FEB-13:09 | 2555.22 | 01-FEB-09:09 | 671.63 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1471.25 | 11-FEB-14:00 | 2502.81 | 03-FEB-12:10 |
March | 2024.96 | 04-MAR-13:09 | 2555.22 | 01-MAR-09:09 | 671.63 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1464.74 | 13-MAR-16:00 | 2796.89 | 15-MAR-11:05 |
April | 2024.96 | 01-APR-12:09 | 2555.22 | 01-APR-08:09 | 671.63 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2182.64 | 17-APR-15:00 | 901.59 | 25-APR-16:00 |
May | 2024.96 | 06-MAY-12:09 | 2555.22 | 01-MAY-08:09 | 671.63 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2750.99 | 22-MAY-13:00 | 607.66 | 10-MAY-15:00 |
June | 2024.96 | 03-JUN-12:09 | 2555.22 | 01-JUN-08:09 | 671.63 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2187.35 | 11-JUN-13:00 | 296.13 | 05-JUN-15:00 |
July | 2024.96 | 01-JUL-12:09 | 2555.22 | 01-JUL-08:09 | 671.63 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3027.86 | 29-JUL-16:00 | 778.99 | 02-JUL-17:00 |
August | 2024.96 | 05-AUG-12:09 | 2555.22 | 01-AUG-08:09 | 671.63 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2636.87 | 23-AUG-13:00 | 462.52 | 28-AUG-12:00 |
September | 2024.96 | 02-SEP-12:09 | 2555.22 | 01-SEP-08:09 | 671.63 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2205.41 | 20-SEP-14:00 | 551.65 | 04-SEP-17:00 |
October | 2024.96 | 07-OCT-12:09 | 2555.22 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2178.62 | 14-OCT-13:00 | 598.04 | 26-OCT-14:00 |
November | 2024.96 | 04-NOV-12:09 | 2555.22 | 01-NOV-08:09 | 671.63 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1616.67 | 17-NOV-15:00 | 1534.66 | 12-NOV-18:00 |
December | 2024.96 | 02-DEC-13:09 | 2555.22 | 01-DEC-09:09 | 671.63 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1342.73 | 10-DEC-15:00 | 2900.62 | 20-DEC-12:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 2555.22 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1335.96 | 296.13 | |||||
Maximum of Months | 2024.96 | 2555.22 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 3027.86 | 2900.62 |
Report: PeakSpaceGainsMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 2555.22 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1335.98 | 02-JAN-15:00 | 2593.52 | 24-JAN-12:10 |
February | 2024.96 | 04-FEB-13:09 | 2555.22 | 01-FEB-09:09 | 671.63 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1471.25 | 11-FEB-14:00 | 2494.22 | 03-FEB-12:10 |
March | 2024.96 | 04-MAR-13:09 | 2555.22 | 01-MAR-09:09 | 671.63 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1464.73 | 13-MAR-16:00 | 2794.45 | 15-MAR-11:05 |
April | 2024.96 | 01-APR-12:09 | 2555.22 | 01-APR-08:09 | 671.63 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2182.64 | 17-APR-15:00 | 901.59 | 25-APR-16:00 |
May | 2024.96 | 06-MAY-12:09 | 2555.22 | 01-MAY-08:09 | 671.63 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2750.99 | 22-MAY-13:00 | 607.66 | 10-MAY-15:00 |
June | 2024.96 | 03-JUN-12:09 | 2555.22 | 01-JUN-08:09 | 671.63 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2187.35 | 11-JUN-13:00 | 296.13 | 05-JUN-15:00 |
July | 2024.96 | 01-JUL-12:09 | 2555.22 | 01-JUL-08:09 | 671.63 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3027.86 | 29-JUL-16:00 | 781.68 | 02-JUL-17:00 |
August | 2024.96 | 05-AUG-12:09 | 2555.22 | 01-AUG-08:09 | 671.63 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2636.87 | 23-AUG-13:00 | 462.52 | 28-AUG-12:00 |
September | 2024.96 | 02-SEP-12:09 | 2555.22 | 01-SEP-08:09 | 671.63 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2205.41 | 20-SEP-14:00 | 557.64 | 04-SEP-17:00 |
October | 2024.96 | 07-OCT-12:09 | 2555.22 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2178.62 | 14-OCT-13:00 | 598.04 | 26-OCT-14:00 |
November | 2024.96 | 04-NOV-12:09 | 2555.22 | 01-NOV-08:09 | 671.63 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1616.66 | 17-NOV-15:00 | 1527.03 | 12-NOV-18:00 |
December | 2024.96 | 02-DEC-13:09 | 2555.22 | 01-DEC-09:09 | 671.63 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1342.71 | 10-DEC-15:00 | 2894.31 | 20-DEC-12:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 2555.22 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1335.98 | 296.13 | |||||
Maximum of Months | 2024.96 | 2555.22 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 3027.86 | 2894.31 |
Report: PeakSpaceGainsMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 2555.22 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1335.99 | 02-JAN-15:00 | 2579.25 | 24-JAN-12:10 |
February | 2024.96 | 04-FEB-13:09 | 2555.22 | 01-FEB-09:09 | 671.63 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1471.26 | 11-FEB-14:00 | 2456.25 | 03-FEB-12:10 |
March | 2024.96 | 04-MAR-13:09 | 2555.22 | 01-MAR-09:09 | 671.63 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1464.72 | 13-MAR-16:00 | 2757.91 | 15-MAR-11:05 |
April | 2024.96 | 01-APR-12:09 | 2555.22 | 01-APR-08:09 | 671.63 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2182.64 | 17-APR-15:00 | 901.59 | 25-APR-16:00 |
May | 2024.96 | 06-MAY-12:09 | 2555.22 | 01-MAY-08:09 | 671.63 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2750.99 | 22-MAY-13:00 | 607.66 | 10-MAY-15:00 |
June | 2024.96 | 03-JUN-12:09 | 2555.22 | 01-JUN-08:09 | 671.63 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2187.35 | 11-JUN-13:00 | 296.13 | 05-JUN-15:00 |
July | 2024.96 | 01-JUL-12:09 | 2555.22 | 01-JUL-08:09 | 671.63 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3027.86 | 29-JUL-16:00 | 768.64 | 02-JUL-17:00 |
August | 2024.96 | 05-AUG-12:09 | 2555.22 | 01-AUG-08:09 | 671.63 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2636.87 | 23-AUG-13:00 | 462.52 | 28-AUG-12:00 |
September | 2024.96 | 02-SEP-12:09 | 2555.22 | 01-SEP-08:09 | 671.63 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2205.41 | 20-SEP-14:00 | 545.00 | 04-SEP-17:00 |
October | 2024.96 | 07-OCT-12:09 | 2555.22 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2178.62 | 14-OCT-13:00 | 598.04 | 26-OCT-14:00 |
November | 2024.96 | 04-NOV-12:09 | 2555.22 | 01-NOV-08:09 | 671.63 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1616.65 | 17-NOV-15:00 | 1506.56 | 12-NOV-18:00 |
December | 2024.96 | 02-DEC-13:09 | 2555.22 | 01-DEC-09:09 | 671.63 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1342.71 | 10-DEC-15:00 | 2852.02 | 20-DEC-12:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 2555.22 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1335.99 | 296.13 | |||||
Maximum of Months | 2024.96 | 2555.22 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 3027.86 | 2852.02 |
Report: PeakSpaceGainsMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 5400.05 | 07-JAN-15:09 | 2726.96 | 01-JAN-11:09 | 1343.25 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2341.46 | 02-JAN-15:00 | 4418.41 | 24-JAN-12:10 |
February | 5400.05 | 04-FEB-15:09 | 2726.96 | 01-FEB-10:09 | 1343.25 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2579.36 | 11-FEB-14:00 | 4203.04 | 03-FEB-12:10 |
March | 5400.05 | 04-MAR-15:09 | 2726.96 | 01-MAR-10:09 | 1343.25 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2569.90 | 13-MAR-16:00 | 4713.24 | 15-MAR-11:05 |
April | 5400.05 | 01-APR-14:09 | 2726.96 | 01-APR-09:09 | 1343.25 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3827.67 | 17-APR-15:00 | 1580.28 | 25-APR-16:00 |
May | 5400.05 | 06-MAY-14:09 | 2726.96 | 01-MAY-09:09 | 1343.25 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4825.32 | 22-MAY-13:00 | 1067.32 | 10-MAY-15:00 |
June | 5400.05 | 03-JUN-14:09 | 2726.96 | 01-JUN-09:09 | 1343.25 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3833.04 | 11-JUN-13:00 | 518.57 | 05-JUN-15:00 |
July | 5400.05 | 01-JUL-14:09 | 2726.96 | 01-JUL-09:09 | 1343.25 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5305.93 | 29-JUL-16:00 | 1280.05 | 02-JUL-17:00 |
August | 5400.05 | 05-AUG-14:09 | 2726.96 | 01-AUG-09:09 | 1343.25 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4625.14 | 23-AUG-13:00 | 810.32 | 28-AUG-12:00 |
September | 5400.05 | 02-SEP-14:09 | 2726.96 | 01-SEP-09:09 | 1343.25 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3870.95 | 20-SEP-14:00 | 912.08 | 04-SEP-17:00 |
October | 5400.05 | 07-OCT-14:09 | 2726.96 | 01-OCT-10:09 | 1343.25 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3818.61 | 14-OCT-13:00 | 1048.23 | 26-OCT-14:00 |
November | 5400.05 | 04-NOV-14:09 | 2726.96 | 01-NOV-09:09 | 1343.25 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2833.69 | 17-NOV-15:00 | 2515.16 | 12-NOV-18:00 |
December | 5400.05 | 02-DEC-15:09 | 2726.96 | 01-DEC-10:09 | 1343.25 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2357.55 | 10-DEC-15:00 | 4868.96 | 20-DEC-12:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 5400.05 | 2726.96 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 2341.46 | 518.57 | |||||
Maximum of Months | 5400.05 | 2726.96 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 5305.93 | 4868.96 |
Report: PeakSpaceGainsMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1404.46 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1335.85 | 02-JAN-15:00 | 2493.45 | 24-JAN-12:10 |
February | 2699.95 | 04-FEB-15:09 | 1404.46 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1471.26 | 11-FEB-14:00 | 2371.97 | 03-FEB-12:10 |
March | 2699.95 | 04-MAR-15:09 | 1404.46 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1464.81 | 13-MAR-16:00 | 2670.16 | 15-MAR-11:05 |
April | 2699.95 | 01-APR-14:09 | 1404.46 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2182.71 | 17-APR-15:00 | 901.59 | 25-APR-16:00 |
May | 2699.95 | 06-MAY-14:09 | 1404.46 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2750.99 | 22-MAY-13:00 | 607.66 | 10-MAY-15:00 |
June | 2699.95 | 03-JUN-14:09 | 1404.46 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2187.35 | 11-JUN-13:00 | 296.13 | 05-JUN-15:00 |
July | 2699.95 | 01-JUL-14:09 | 1404.46 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3027.86 | 29-JUL-16:00 | 711.23 | 02-JUL-17:00 |
August | 2699.95 | 05-AUG-14:09 | 1404.46 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2636.87 | 23-AUG-13:00 | 462.52 | 28-AUG-12:00 |
September | 2699.95 | 02-SEP-14:09 | 1404.46 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2205.41 | 20-SEP-14:00 | 495.35 | 04-SEP-17:00 |
October | 2699.95 | 07-OCT-14:09 | 1404.46 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2178.62 | 14-OCT-13:00 | 598.04 | 26-OCT-14:00 |
November | 2699.95 | 04-NOV-14:09 | 1404.46 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1616.70 | 17-NOV-15:00 | 1428.03 | 12-NOV-18:00 |
December | 2699.95 | 02-DEC-15:09 | 1404.46 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1342.59 | 10-DEC-15:00 | 2758.11 | 20-DEC-12:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1335.85 | 296.13 | |||||
Maximum of Months | 2699.95 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 3027.86 | 2758.11 |
Report: PeakSpaceGainsMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1404.46 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1335.85 | 02-JAN-15:00 | 2479.73 | 24-JAN-12:10 |
February | 2699.95 | 04-FEB-15:09 | 1404.46 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1471.26 | 11-FEB-14:00 | 2360.27 | 03-FEB-12:10 |
March | 2699.95 | 04-MAR-15:09 | 1404.46 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1464.81 | 13-MAR-16:00 | 2660.37 | 15-MAR-11:05 |
April | 2699.95 | 01-APR-14:09 | 1404.46 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2182.71 | 17-APR-15:00 | 901.59 | 25-APR-16:00 |
May | 2699.95 | 06-MAY-14:09 | 1404.46 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2750.99 | 22-MAY-13:00 | 607.66 | 10-MAY-15:00 |
June | 2699.95 | 03-JUN-14:09 | 1404.46 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2187.35 | 11-JUN-13:00 | 296.13 | 05-JUN-15:00 |
July | 2699.95 | 01-JUL-14:09 | 1404.46 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3027.86 | 29-JUL-16:00 | 707.80 | 02-JUL-17:00 |
August | 2699.95 | 05-AUG-14:09 | 1404.46 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2636.87 | 23-AUG-13:00 | 462.52 | 28-AUG-12:00 |
September | 2699.95 | 02-SEP-14:09 | 1404.46 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2205.41 | 20-SEP-14:00 | 492.55 | 04-SEP-17:00 |
October | 2699.95 | 07-OCT-14:09 | 1404.46 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2178.62 | 14-OCT-13:00 | 598.04 | 26-OCT-14:00 |
November | 2699.95 | 04-NOV-14:09 | 1404.46 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1616.70 | 17-NOV-15:00 | 1421.75 | 12-NOV-18:00 |
December | 2699.95 | 02-DEC-15:09 | 1404.46 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1342.59 | 10-DEC-15:00 | 2744.56 | 20-DEC-12:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1335.85 | 296.13 | |||||
Maximum of Months | 2699.95 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 3027.86 | 2744.56 |
Report: PeakSpaceGainsMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1404.46 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1335.87 | 02-JAN-15:00 | 2453.15 | 24-JAN-12:10 |
February | 2699.95 | 04-FEB-15:09 | 1404.46 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1471.26 | 11-FEB-14:00 | 2327.23 | 03-FEB-12:10 |
March | 2699.95 | 04-MAR-15:09 | 1404.46 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1464.79 | 13-MAR-16:00 | 2642.16 | 15-MAR-11:05 |
April | 2699.95 | 01-APR-14:09 | 1404.46 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2182.71 | 17-APR-15:00 | 901.59 | 25-APR-16:00 |
May | 2699.95 | 06-MAY-14:09 | 1404.46 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2750.99 | 22-MAY-13:00 | 607.66 | 10-MAY-15:00 |
June | 2699.95 | 03-JUN-14:09 | 1404.46 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2187.35 | 11-JUN-13:00 | 296.13 | 05-JUN-15:00 |
July | 2699.95 | 01-JUL-14:09 | 1404.46 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3027.86 | 29-JUL-16:00 | 710.86 | 02-JUL-17:00 |
August | 2699.95 | 05-AUG-14:09 | 1404.46 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2636.87 | 23-AUG-13:00 | 462.52 | 28-AUG-12:00 |
September | 2699.95 | 02-SEP-14:09 | 1404.46 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2205.41 | 20-SEP-14:00 | 495.38 | 04-SEP-17:00 |
October | 2699.95 | 07-OCT-14:09 | 1404.46 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2178.62 | 14-OCT-13:00 | 598.04 | 26-OCT-14:00 |
November | 2699.95 | 04-NOV-14:09 | 1404.46 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1616.69 | 17-NOV-15:00 | 1406.32 | 12-NOV-18:00 |
December | 2699.95 | 02-DEC-15:09 | 1404.46 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1342.62 | 10-DEC-15:00 | 2712.01 | 20-DEC-12:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1335.87 | 296.13 | |||||
Maximum of Months | 2699.95 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 3027.86 | 2712.01 |
Report: PeakSpaceGainsMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1404.46 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1362.35 | 02-JAN-15:00 | 2634.52 | 24-JAN-12:10 |
February | 2699.95 | 04-FEB-15:09 | 1404.46 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1503.55 | 11-FEB-14:00 | 2370.91 | 03-FEB-12:10 |
March | 2699.95 | 04-MAR-15:09 | 1404.46 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1508.08 | 13-MAR-16:00 | 2861.43 | 15-MAR-11:05 |
April | 2699.95 | 01-APR-14:09 | 1404.46 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2237.12 | 17-APR-15:00 | 919.39 | 25-APR-16:00 |
May | 2699.95 | 06-MAY-14:09 | 1404.46 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2826.10 | 22-MAY-13:00 | 633.02 | 10-MAY-15:00 |
June | 2699.95 | 03-JUN-14:09 | 1404.46 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2225.32 | 11-JUN-13:00 | 303.47 | 18-JUN-17:00 |
July | 2699.95 | 01-JUL-14:09 | 1404.46 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3080.42 | 29-JUL-16:00 | 812.00 | 02-JUL-17:00 |
August | 2699.95 | 05-AUG-14:09 | 1404.46 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2708.86 | 23-AUG-13:00 | 469.44 | 28-AUG-12:00 |
September | 2699.95 | 02-SEP-14:09 | 1404.46 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2281.11 | 20-SEP-14:00 | 624.39 | 04-SEP-17:00 |
October | 2699.95 | 07-OCT-14:09 | 1404.46 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2221.62 | 14-OCT-13:00 | 609.85 | 26-OCT-14:00 |
November | 2699.95 | 04-NOV-14:09 | 1404.46 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1648.50 | 17-NOV-15:00 | 1429.38 | 12-NOV-18:00 |
December | 2699.95 | 02-DEC-15:09 | 1404.46 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1394.94 | 10-DEC-15:00 | 2802.24 | 20-DEC-12:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1362.35 | 303.47 | |||||
Maximum of Months | 2699.95 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 3080.42 | 2861.43 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 28664.19 | 14-JAN-08:62 | 0.00 | 300.00 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 242.67 |
February | 30204.80 | 18-FEB-08:62 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.03 |
March | 27487.70 | 30-MAR-07:03 | 1350.01 | 300.00 | 298.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.25 |
April | 30825.50 | 16-APR-07:02 | 1687.52 | 375.00 | 373.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 153.02 |
May | 34098.46 | 09-MAY-07:02 | 1687.52 | 375.00 | 373.12 | 0.00 | 0.00 | 0.00 | 0.00 | 116.53 | 0.00 |
June | 30847.92 | 17-JUN-07:02 | 0.00 | 450.00 | 441.83 | 0.00 | 0.00 | 0.00 | 0.00 | 69.27 | 0.00 |
July | 35452.41 | 02-JUL-07:01 | 2362.52 | 525.00 | 522.37 | 0.00 | 0.00 | 0.00 | 0.00 | 55.49 | 0.00 |
August | 31698.18 | 08-AUG-07:02 | 2025.02 | 450.00 | 447.75 | 0.00 | 0.00 | 0.00 | 0.00 | 206.96 | 0.00 |
September | 31941.69 | 10-SEP-07:01 | 2362.52 | 525.00 | 522.37 | 0.00 | 0.00 | 0.00 | 0.00 | 14.65 | 0.00 |
October | 36682.12 | 18-OCT-07:02 | 1687.52 | 375.00 | 373.12 | 0.00 | 0.00 | 0.00 | 0.00 | 47.12 | 0.00 |
November | 32266.28 | 20-NOV-08:62 | 1687.52 | 375.00 | 373.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.87 |
December | 34473.69 | 01-DEC-08:62 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.97 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 27487.70 | 0.00 | 300.00 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 36682.12 | 2362.52 | 525.00 | 522.37 | 0.00 | 0.00 | 0.00 | 0.00 | 206.96 | 242.67 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 17062.74 | 14-JAN-08:62 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 123.95 |
February | 17808.63 | 18-FEB-08:62 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.82 |
March | 16568.46 | 06-MAR-08:62 | 674.99 | 150.00 | 149.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.44 |
April | 18431.31 | 16-APR-07:02 | 843.73 | 187.50 | 186.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.25 |
May | 19210.85 | 08-MAY-07:02 | 843.73 | 187.50 | 186.56 | 0.00 | 0.00 | 0.00 | 0.00 | 31.73 | 0.00 |
June | 18332.23 | 12-JUN-07:01 | 1181.23 | 262.50 | 261.19 | 0.00 | 0.00 | 0.00 | 0.00 | 45.74 | 0.00 |
July | 20428.98 | 02-JUL-07:01 | 1181.23 | 262.50 | 261.19 | 0.00 | 0.00 | 0.00 | 0.00 | 32.53 | 0.00 |
August | 18621.56 | 28-AUG-07:02 | 1012.48 | 225.00 | 223.88 | 0.00 | 0.00 | 0.00 | 0.00 | 26.39 | 0.00 |
September | 19310.17 | 04-SEP-07:02 | 1012.48 | 225.00 | 223.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.26 |
October | 20263.13 | 18-OCT-07:02 | 843.73 | 187.50 | 186.56 | 0.00 | 0.00 | 0.00 | 0.00 | 26.82 | 0.00 |
November | 18881.03 | 09-NOV-08:62 | 843.73 | 187.50 | 186.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.12 |
December | 20229.17 | 01-DEC-08:62 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.51 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 16568.46 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 20428.98 | 1181.23 | 262.50 | 261.19 | 0.00 | 0.00 | 0.00 | 0.00 | 45.74 | 123.95 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 15157.69 | 14-JAN-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.88 |
February | 15618.78 | 18-FEB-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.60 |
March | 17081.72 | 31-MAR-06:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.70 |
April | 17234.05 | 17-APR-06:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.65 |
May | 17574.71 | 09-MAY-06:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.12 |
June | 15776.42 | 17-JUN-06:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.48 |
July | 15941.72 | 02-JUL-07:01 | 0.00 | 262.50 | 261.19 | 0.00 | 0.00 | 0.00 | 0.00 | 16.76 | 0.00 |
August | 15250.46 | 30-AUG-06:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.20 |
September | 15385.00 | 14-SEP-06:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.43 |
October | 19445.55 | 18-OCT-06:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.48 | 0.00 |
November | 16517.11 | 21-NOV-07:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.75 | 0.00 |
December | 15805.33 | 03-DEC-08:62 | 0.00 | 150.00 | 149.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 158.41 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 15157.69 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19445.55 | 0.00 | 262.50 | 261.19 | 0.00 | 0.00 | 0.00 | 0.00 | 16.76 | 158.41 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 15186.08 | 14-JAN-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.85 |
February | 15658.26 | 18-FEB-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.60 |
March | 17131.16 | 31-MAR-06:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.72 |
April | 17342.81 | 17-APR-06:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.86 |
May | 17632.88 | 09-MAY-06:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.16 |
June | 15859.75 | 17-JUN-06:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 |
July | 16043.72 | 02-JUL-07:01 | 0.00 | 262.50 | 261.19 | 0.00 | 0.00 | 0.00 | 0.00 | 14.53 | 0.00 |
August | 15310.56 | 30-AUG-06:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.22 |
September | 15461.20 | 14-SEP-06:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.49 |
October | 19512.25 | 18-OCT-06:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.43 | 0.00 |
November | 16570.54 | 21-NOV-07:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.71 | 0.00 |
December | 15766.86 | 03-DEC-08:62 | 0.00 | 150.00 | 149.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 158.40 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 15186.08 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19512.25 | 0.00 | 262.50 | 261.19 | 0.00 | 0.00 | 0.00 | 0.00 | 14.53 | 158.40 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 14928.13 | 14-JAN-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.44 |
February | 15399.58 | 18-FEB-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.92 |
March | 15800.65 | 31-MAR-06:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.61 |
April | 17131.74 | 17-APR-06:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.63 |
May | 17370.59 | 09-MAY-06:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.76 |
June | 15590.47 | 17-JUN-06:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.10 |
July | 15776.09 | 02-JUL-07:01 | 0.00 | 262.50 | 261.19 | 0.00 | 0.00 | 0.00 | 0.00 | 19.17 | 0.00 |
August | 15042.24 | 30-AUG-06:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.08 |
September | 15187.99 | 14-SEP-06:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.28 |
October | 19236.47 | 18-OCT-06:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 0.00 |
November | 16304.78 | 21-NOV-07:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 1.25 | 0.00 |
December | 15239.31 | 01-DEC-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.27 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 14928.13 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19236.47 | 0.00 | 262.50 | 261.19 | 0.00 | 0.00 | 0.00 | 0.00 | 19.17 | 16.63 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 26095.57 | 14-JAN-08:62 | 0.00 | 300.00 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 218.65 |
February | 27346.73 | 18-FEB-08:62 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.29 |
March | 25668.28 | 27-MAR-07:03 | 0.00 | 300.00 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 243.03 |
April | 29729.00 | 17-APR-07:03 | 0.00 | 300.00 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 334.88 |
May | 30493.64 | 09-MAY-07:02 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 101.57 | 0.00 |
June | 27631.68 | 17-JUN-07:02 | 0.00 | 450.00 | 441.83 | 0.00 | 0.00 | 0.00 | 0.00 | 62.01 | 0.00 |
July | 27964.45 | 07-JUL-07:02 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 96.44 | 0.00 |
August | 27717.80 | 08-AUG-07:02 | 0.00 | 450.00 | 441.83 | 0.00 | 0.00 | 0.00 | 0.00 | 202.90 | 0.00 |
September | 27756.89 | 14-SEP-07:02 | 0.00 | 450.00 | 441.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.76 |
October | 33586.90 | 18-OCT-07:02 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 47.08 | 0.00 |
November | 29189.08 | 07-NOV-08:62 | 0.00 | 300.00 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 166.80 |
December | 29641.07 | 03-DEC-09:02 | 0.00 | 300.00 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 215.98 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 25668.28 | 0.00 | 300.00 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 33586.90 | 0.00 | 450.00 | 441.83 | 0.00 | 0.00 | 0.00 | 0.00 | 202.90 | 334.88 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 12788.50 | 14-JAN-08:62 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 122.11 |
February | 14251.84 | 18-FEB-08:62 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.16 |
March | 12678.27 | 27-MAR-07:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.78 |
April | 15428.32 | 17-APR-07:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 187.45 |
May | 15930.07 | 09-MAY-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.20 | 0.00 |
June | 14423.02 | 17-JUN-07:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 37.92 | 0.00 |
July | 14602.47 | 07-JUL-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 59.08 | 0.00 |
August | 14522.69 | 08-AUG-07:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 118.95 | 0.00 |
September | 14500.88 | 14-SEP-07:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.30 |
October | 17514.34 | 18-OCT-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.45 | 0.00 |
November | 15137.23 | 21-NOV-08:62 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 57.16 | 0.00 |
December | 14903.50 | 01-DEC-08:62 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.84 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 12678.27 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17514.34 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 118.95 | 187.45 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 12419.27 | 14-JAN-08:62 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 121.95 |
February | 14164.39 | 18-FEB-08:62 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.12 |
March | 12319.47 | 27-MAR-07:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.63 |
April | 15356.91 | 17-APR-07:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 186.94 |
May | 15842.90 | 09-MAY-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.93 | 0.00 |
June | 14340.83 | 17-JUN-07:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 38.69 | 0.00 |
July | 14517.67 | 07-JUL-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 59.56 | 0.00 |
August | 14431.15 | 08-AUG-07:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 119.57 | 0.00 |
September | 14416.55 | 14-SEP-07:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.86 |
October | 17425.72 | 18-OCT-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.05 | 0.00 |
November | 15049.81 | 21-NOV-08:62 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 58.01 | 0.00 |
December | 14815.12 | 01-DEC-08:62 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.17 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 12319.47 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17425.72 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 119.57 | 186.94 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 11351.23 | 14-JAN-08:62 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 121.44 |
February | 14129.70 | 18-FEB-08:62 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.82 |
March | 11439.94 | 05-MAR-09:02 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 14.04 | 0.00 |
April | 15370.83 | 17-APR-07:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 184.68 |
May | 15831.22 | 09-MAY-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 64.78 | 0.00 |
June | 14345.63 | 17-JUN-07:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 41.42 | 0.00 |
July | 14544.79 | 07-JUL-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.55 | 0.00 |
August | 14455.19 | 08-AUG-07:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 121.52 | 0.00 |
September | 14458.57 | 14-SEP-07:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.29 |
October | 17429.29 | 18-OCT-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.28 | 0.00 |
November | 15035.59 | 21-NOV-08:62 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 61.53 | 0.00 |
December | 14787.12 | 01-DEC-08:62 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.84 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 11351.23 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17429.29 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 121.52 | 184.68 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 9182.42 | 14-JAN-08:62 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 139.84 |
February | 14556.53 | 18-FEB-08:62 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.87 |
March | 11716.58 | 05-MAR-09:02 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 23.58 | 0.00 |
April | 14887.01 | 16-APR-08:62 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 3.25 | 0.00 |
May | 18001.07 | 08-MAY-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 47.12 | 0.00 |
June | 15901.77 | 17-JUN-07:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 48.29 | 0.00 |
July | 16481.38 | 06-JUL-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 50.36 | 0.00 |
August | 16966.40 | 08-AUG-07:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 125.15 | 0.00 |
September | 16446.14 | 14-SEP-07:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.78 |
October | 19650.90 | 18-OCT-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 45.13 | 0.00 |
November | 16653.58 | 09-NOV-08:62 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.92 |
December | 17167.74 | 01-DEC-08:62 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.80 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 9182.42 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19650.90 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 125.15 | 139.84 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.784418E+11 | 84555.98 | 02-JAN-14:09 | 54851953.33 | 15419.92 | 25-JAN-08:30 |
February | 0.753315E+11 | 89326.06 | 11-FEB-14:20 | 0.184659E+09 | 44481.47 | 04-FEB-08:09 |
March | 0.851724E+11 | 79510.66 | 04-MAR-14:09 | 0.204246E+09 | 31092.45 | 16-MAR-07:30 |
April | 0.899061E+11 | 86211.60 | 14-APR-14:20 | 0.00 | 0.00 | 01-APR-00:10 |
May | 0.104514E+12 | 96231.50 | 29-MAY-12:00 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 0.108522E+12 | 97836.00 | 29-JUN-13:30 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 0.116349E+12 | 105657.08 | 27-JUL-15:50 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.116032E+12 | 103252.19 | 22-AUG-12:00 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.110669E+12 | 101760.47 | 20-SEP-13:50 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 0.107243E+12 | 97794.71 | 14-OCT-13:39 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 0.931159E+11 | 88818.05 | 10-NOV-13:20 | 158931.53 | 140.40 | 13-NOV-08:30 |
December | 0.821455E+11 | 84253.42 | 09-DEC-13:00 | 51683734.08 | 11211.56 | 15-DEC-08:20 |
Annual Sum or Average | 0.116744E+13 | 0.495600E+09 | ||||
Minimum of Months | 0.753315E+11 | 79510.66 | 0.00 | 0.00 | ||
Maximum of Months | 0.116349E+12 | 105657.08 | 0.204246E+09 | 44481.47 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.310073E+11 | 0.601342E+10 | 0.108325E+11 | 0.00 | 0.825993E+10 | 0.00 | 0.00 | 0.172470E+11 | 0.00 | 0.00 | 0.00 | 0.508175E+10 | 0.00 |
February | 0.280657E+11 | 0.509817E+10 | 0.980803E+10 | 0.00 | 0.749225E+10 | 0.00 | 0.00 | 0.202763E+11 | 0.00 | 0.00 | 0.00 | 0.459099E+10 | 0.00 |
March | 0.314703E+11 | 0.519397E+10 | 0.110075E+11 | 0.00 | 0.841688E+10 | 0.00 | 0.00 | 0.240077E+11 | 0.00 | 0.00 | 0.00 | 0.507610E+10 | 0.00 |
April | 0.300741E+11 | 0.458600E+10 | 0.105079E+11 | 0.00 | 0.807411E+10 | 0.00 | 0.00 | 0.318308E+11 | 0.00 | 0.00 | 0.00 | 0.483317E+10 | 0.00 |
May | 0.312330E+11 | 0.434147E+10 | 0.109147E+11 | 0.00 | 0.856939E+10 | 0.00 | 0.00 | 0.445052E+11 | 0.00 | 0.00 | 0.00 | 0.494972E+10 | 0.00 |
June | 0.304143E+11 | 0.402097E+10 | 0.106386E+11 | 0.00 | 0.874495E+10 | 0.00 | 0.00 | 0.499406E+11 | 0.00 | 0.00 | 0.00 | 0.476275E+10 | 0.00 |
July | 0.309042E+11 | 0.421261E+10 | 0.107945E+11 | 0.00 | 0.947396E+10 | 0.00 | 0.00 | 0.560918E+11 | 0.00 | 0.00 | 0.00 | 0.487188E+10 | 0.00 |
August | 0.314595E+11 | 0.456286E+10 | 0.110006E+11 | 0.00 | 0.944649E+10 | 0.00 | 0.00 | 0.546465E+11 | 0.00 | 0.00 | 0.00 | 0.491647E+10 | 0.00 |
September | 0.300847E+11 | 0.484042E+10 | 0.105148E+11 | 0.00 | 0.895568E+10 | 0.00 | 0.00 | 0.515024E+11 | 0.00 | 0.00 | 0.00 | 0.477056E+10 | 0.00 |
October | 0.310073E+11 | 0.545830E+10 | 0.108325E+11 | 0.00 | 0.871585E+10 | 0.00 | 0.00 | 0.462559E+11 | 0.00 | 0.00 | 0.00 | 0.497277E+10 | 0.00 |
November | 0.300409E+11 | 0.568961E+10 | 0.104978E+11 | 0.00 | 0.809196E+10 | 0.00 | 0.00 | 0.339343E+11 | 0.00 | 0.00 | 0.00 | 0.486128E+10 | 0.00 |
December | 0.309156E+11 | 0.609933E+10 | 0.108050E+11 | 0.00 | 0.825521E+10 | 0.00 | 0.00 | 0.210029E+11 | 0.00 | 0.00 | 0.00 | 0.506739E+10 | 0.00 |
Annual Sum or Average | 0.366677E+12 | 0.601171E+11 | 0.128154E+12 | 0.00 | 0.102497E+12 | 0.00 | 0.00 | 0.451241E+12 | 0.00 | 0.00 | 0.00 | 0.587548E+11 | 0.00 |
Minimum of Months | 0.280657E+11 | 0.402097E+10 | 0.980803E+10 | 0.00 | 0.749225E+10 | 0.00 | 0.00 | 0.172470E+11 | 0.00 | 0.00 | 0.00 | 0.459099E+10 | 0.00 |
Maximum of Months | 0.314703E+11 | 0.609933E+10 | 0.110075E+11 | 0.00 | 0.947396E+10 | 0.00 | 0.00 | 0.560918E+11 | 0.00 | 0.00 | 0.00 | 0.508175E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 54851953.33 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.184659E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.204246E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 158931.53 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 51683734.08 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.495600E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.204246E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 23459.17 | 01-JAN-11:09 | 5507.06 | 01-JAN-06:10 | 8059.50 | 01-JAN-11:09 | 0.00 | 6953.32 | 14-JAN-08:09 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 23459.17 | 01-FEB-10:09 | 5507.06 | 01-FEB-06:10 | 8059.50 | 01-FEB-10:09 | 0.00 | 7077.19 | 11-FEB-08:09 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 23459.17 | 01-MAR-10:09 | 5507.06 | 01-MAR-06:10 | 8059.50 | 01-MAR-10:09 | 0.00 | 7109.78 | 06-MAR-08:09 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 23459.17 | 01-APR-09:09 | 5507.06 | 01-APR-05:10 | 8059.50 | 01-APR-09:09 | 0.00 | 7131.93 | 14-APR-07:10 | 0.00 | 0.00 | 01-APR-00:10 |
May | 23459.17 | 01-MAY-09:09 | 5507.06 | 01-MAY-05:10 | 8059.50 | 01-MAY-09:09 | 0.00 | 7994.21 | 29-MAY-12:00 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 23459.17 | 01-JUN-09:09 | 5507.06 | 01-JUN-05:10 | 8059.50 | 01-JUN-09:09 | 0.00 | 8054.48 | 08-JUN-07:10 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 23459.17 | 01-JUL-09:09 | 5507.06 | 01-JUL-05:10 | 8059.50 | 01-JUL-09:09 | 0.00 | 9024.11 | 31-JUL-13:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 23459.17 | 01-AUG-09:09 | 5507.06 | 01-AUG-05:10 | 8059.50 | 01-AUG-09:09 | 0.00 | 9239.78 | 22-AUG-12:00 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 23459.17 | 01-SEP-09:09 | 5507.06 | 01-SEP-05:10 | 8059.50 | 01-SEP-09:09 | 0.00 | 8811.20 | 20-SEP-12:00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 23459.17 | 01-OCT-10:09 | 5507.06 | 01-OCT-05:10 | 8059.50 | 01-OCT-10:09 | 0.00 | 8424.13 | 30-OCT-07:10 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 23459.17 | 01-NOV-09:09 | 5507.06 | 01-NOV-05:10 | 8059.50 | 01-NOV-09:09 | 0.00 | 7720.85 | 30-NOV-08:09 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 23459.17 | 01-DEC-10:09 | 5507.06 | 01-DEC-06:10 | 8059.50 | 01-DEC-10:09 | 0.00 | 7144.38 | 08-DEC-08:09 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||||
Minimum of Months | 23459.17 | 5507.06 | 8059.50 | 0.00 | 6953.32 | 0.00 | 0.00 | |||||
Maximum of Months | 23459.17 | 5507.06 | 8059.50 | 0.00 | 9239.78 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 41752.35 | 02-JAN-14:30 | 0.00 | 0.00 | 0.00 | 11709.19 | 16-JAN-16:30 | 0.00 |
February | 44872.78 | 11-FEB-13:00 | 0.00 | 0.00 | 0.00 | 7950.00 | 01-FEB-14:09 | 0.00 |
March | 38083.01 | 13-MAR-14:00 | 0.00 | 0.00 | 0.00 | 9666.50 | 24-MAR-13:39 | 0.00 |
April | 45679.91 | 14-APR-14:00 | 0.00 | 0.00 | 0.00 | 7552.71 | 08-APR-12:09 | 0.00 |
May | 53406.88 | 29-MAY-12:00 | 0.00 | 0.00 | 0.00 | 7534.20 | 15-MAY-11:00 | 0.00 |
June | 51311.22 | 24-JUN-12:00 | 0.00 | 0.00 | 0.00 | 8649.47 | 29-JUN-13:30 | 0.00 |
July | 59469.10 | 27-JUL-16:10 | 0.00 | 0.00 | 0.00 | 8203.61 | 27-JUL-23:19 | 0.00 |
August | 59171.76 | 22-AUG-12:00 | 0.00 | 0.00 | 0.00 | 7541.69 | 01-AUG-13:09 | 0.00 |
September | 56266.88 | 20-SEP-12:00 | 0.00 | 0.00 | 0.00 | 7547.28 | 21-SEP-12:39 | 0.00 |
October | 53092.16 | 03-OCT-14:39 | 0.00 | 0.00 | 0.00 | 7552.03 | 25-OCT-12:09 | 0.00 |
November | 45805.92 | 10-NOV-13:00 | 0.00 | 0.00 | 0.00 | 7555.72 | 10-NOV-13:20 | 0.00 |
December | 41378.25 | 10-DEC-13:00 | 0.00 | 0.00 | 0.00 | 9225.93 | 28-DEC-13:39 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 38083.01 | 0.00 | 0.00 | 0.00 | 7534.20 | 0.00 | ||
Maximum of Months | 59469.10 | 0.00 | 0.00 | 0.00 | 11709.19 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 84555.98 | 02-JAN-14:09 | 23459.17 | 8059.50 | 0.00 | 0.00 | 5935.74 | 0.00 | 0.00 | 40796.40 | 0.00 |
February | 89326.06 | 11-FEB-14:20 | 23459.17 | 8059.50 | 0.00 | 0.00 | 6530.46 | 0.00 | 0.00 | 43720.92 | 0.00 |
March | 79510.66 | 04-MAR-14:09 | 23459.17 | 8059.50 | 0.00 | 0.00 | 5656.72 | 0.00 | 0.00 | 36895.49 | 0.00 |
April | 86211.60 | 14-APR-14:20 | 23459.17 | 8059.50 | 0.00 | 0.00 | 6577.82 | 0.00 | 0.00 | 44795.87 | 0.00 |
May | 96231.50 | 29-MAY-12:00 | 23459.17 | 8059.50 | 0.00 | 0.00 | 7994.21 | 0.00 | 0.00 | 53406.88 | 0.00 |
June | 97836.00 | 29-JUN-13:30 | 23459.17 | 8059.50 | 0.00 | 0.00 | 7607.95 | 0.00 | 0.00 | 50059.91 | 0.00 |
July | 105657.08 | 27-JUL-15:50 | 23459.17 | 8059.50 | 0.00 | 0.00 | 8676.09 | 0.00 | 0.00 | 57940.22 | 0.00 |
August | 103252.19 | 22-AUG-12:00 | 23459.17 | 8059.50 | 0.00 | 0.00 | 9239.78 | 0.00 | 0.00 | 59171.76 | 0.00 |
September | 101760.47 | 20-SEP-13:50 | 23459.17 | 8059.50 | 0.00 | 0.00 | 8713.42 | 0.00 | 0.00 | 56094.07 | 0.00 |
October | 97794.71 | 14-OCT-13:39 | 23459.17 | 8059.50 | 0.00 | 0.00 | 7789.19 | 0.00 | 0.00 | 51343.23 | 0.00 |
November | 88818.05 | 10-NOV-13:20 | 23459.17 | 8059.50 | 0.00 | 0.00 | 6552.79 | 0.00 | 0.00 | 43190.87 | 0.00 |
December | 84253.42 | 09-DEC-13:00 | 23459.17 | 8059.50 | 0.00 | 0.00 | 5661.63 | 0.00 | 0.00 | 38320.31 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 79510.66 | 23459.17 | 8059.50 | 0.00 | 0.00 | 5656.72 | 0.00 | 0.00 | 36895.49 | 0.00 | |
Maximum of Months | 105657.08 | 23459.17 | 8059.50 | 0.00 | 0.00 | 9239.78 | 0.00 | 0.00 | 59171.76 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 15419.92 | 25-JAN-08:30 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 44481.47 | 04-FEB-08:09 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 31092.45 | 16-MAR-07:30 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 140.40 | 13-NOV-08:30 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 11211.56 | 15-DEC-08:20 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 44481.47 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.45 | 0.00 | 24.45 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.47 | 0.00 | 24.47 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.46 | 0.00 | 24.46 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.83 | 24.46 | 0.00 | 24.46 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.47 | 0.00 | 24.47 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.45 | 0.00 | 24.45 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.17 | 24.45 | 0.00 | 24.45 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.45 | 0.00 | 24.45 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.50 | 0.00 | 24.50 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.56 | 0.00 | 24.56 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.51 | 0.00 | 24.51 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 1.17 | 24.53 | 0.00 | 24.53 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.56 | 0.00 | 24.56 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.47 | 0.00 | 24.47 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.52 | 0.00 | 24.52 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.48 | 0.00 | 24.48 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 1.17 | 24.49 | 0.00 | 24.49 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.52 | 0.00 | 24.52 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.47 | 0.00 | 24.47 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.52 | 0.00 | 24.52 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.48 | 0.00 | 24.48 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 1.17 | 24.49 | 0.00 | 24.49 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.52 | 0.00 | 24.52 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.47 | 0.00 | 24.47 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.51 | 0.00 | 24.51 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.48 | 0.00 | 24.48 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.83 | 24.50 | 0.00 | 24.50 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.51 | 0.00 | 24.51 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.48 | 0.00 | 24.48 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.52 | 0.00 | 24.52 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.60 | 0.00 | 24.60 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.47 | 0.00 | 24.47 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 1.50 | 24.53 | 0.00 | 24.53 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.60 | 0.00 | 24.60 |
Report: ComfortReportSimple55Monthly
For: LGSTORE1
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 99.00 | 23.31 | 327.00 | 23.75 | 31.33 | 23.76 |
February | 75.33 | 23.32 | 318.33 | 23.78 | 28.67 | 23.79 |
March | 100.00 | 23.34 | 381.50 | 23.77 | 51.33 | 23.78 |
April | 28.17 | 23.82 | 450.50 | 23.88 | 25.00 | 23.88 |
May | 100.50 | 23.89 | 496.00 | 23.89 | 100.50 | 23.89 |
June | 173.00 | 23.89 | 481.00 | 23.89 | 173.00 | 23.89 |
July | 139.17 | 23.90 | 495.00 | 23.89 | 139.17 | 23.89 |
August | 186.67 | 23.89 | 497.00 | 23.89 | 186.67 | 23.89 |
September | 127.67 | 23.89 | 479.00 | 23.89 | 127.67 | 23.89 |
October | 120.00 | 23.89 | 496.00 | 23.89 | 120.00 | 23.89 |
November | 115.33 | 23.80 | 430.67 | 23.87 | 104.33 | 23.87 |
December | 116.17 | 23.45 | 369.83 | 23.78 | 68.17 | 23.79 |
Annual Sum or Average | 1381.00 | 23.73 | 5221.83 | 23.86 | 1155.83 | 23.86 |
Minimum of Months | 28.17 | 23.31 | 318.33 | 23.75 | 25.00 | 23.76 |
Maximum of Months | 186.67 | 23.90 | 497.00 | 23.89 | 186.67 | 23.89 |
Report: ComfortReportSimple55Monthly
For: SMSTORE1
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 67.33 | 23.45 | 302.50 | 23.81 | 18.33 | 23.81 |
February | 48.83 | 23.53 | 292.67 | 23.84 | 15.50 | 23.84 |
March | 73.67 | 23.41 | 359.17 | 23.81 | 30.67 | 23.81 |
April | 13.67 | 23.83 | 422.33 | 23.89 | 11.17 | 23.89 |
May | 64.17 | 23.89 | 491.50 | 23.89 | 64.17 | 23.89 |
June | 135.33 | 23.89 | 481.00 | 23.89 | 135.33 | 23.89 |
July | 118.83 | 23.89 | 494.67 | 23.89 | 118.83 | 23.89 |
August | 153.50 | 23.89 | 497.00 | 23.89 | 153.50 | 23.89 |
September | 100.17 | 23.89 | 479.00 | 23.89 | 100.17 | 23.89 |
October | 74.50 | 23.89 | 492.00 | 23.89 | 74.50 | 23.89 |
November | 86.83 | 23.83 | 420.17 | 23.88 | 79.17 | 23.88 |
December | 70.33 | 23.55 | 358.00 | 23.83 | 35.83 | 23.84 |
Annual Sum or Average | 1007.17 | 23.78 | 5090.00 | 23.87 | 837.17 | 23.87 |
Minimum of Months | 13.67 | 23.41 | 292.67 | 23.81 | 11.17 | 23.81 |
Maximum of Months | 153.50 | 23.89 | 497.00 | 23.89 | 153.50 | 23.89 |
Report: ComfortReportSimple55Monthly
For: SMSTORE2
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 73.83 | 23.55 | 257.17 | 23.88 | 31.67 | 23.90 |
February | 55.83 | 23.60 | 250.67 | 23.94 | 26.83 | 23.95 |
March | 84.17 | 23.57 | 293.50 | 23.92 | 44.83 | 23.94 |
April | 27.50 | 24.50 | 341.67 | 24.08 | 26.50 | 24.11 |
May | 95.67 | 24.30 | 375.00 | 24.11 | 95.67 | 24.15 |
June | 173.33 | 24.26 | 366.00 | 24.14 | 173.33 | 24.17 |
July | 159.00 | 24.34 | 369.00 | 24.18 | 159.00 | 24.22 |
August | 199.67 | 24.24 | 379.00 | 24.14 | 199.67 | 24.17 |
September | 144.00 | 24.36 | 360.00 | 24.18 | 144.00 | 24.22 |
October | 111.33 | 24.29 | 371.00 | 24.12 | 111.33 | 24.16 |
November | 109.67 | 24.14 | 334.17 | 24.06 | 104.50 | 24.09 |
December | 82.17 | 23.73 | 285.50 | 23.93 | 54.00 | 23.96 |
Annual Sum or Average | 1316.17 | 24.13 | 3982.67 | 24.08 | 1171.33 | 24.11 |
Minimum of Months | 27.50 | 23.55 | 250.67 | 23.88 | 26.50 | 23.90 |
Maximum of Months | 199.67 | 24.50 | 379.00 | 24.18 | 199.67 | 24.22 |
Report: ComfortReportSimple55Monthly
For: SMSTORE3
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 77.50 | 23.53 | 255.00 | 23.87 | 31.50 | 23.89 |
February | 57.67 | 23.58 | 250.00 | 23.93 | 27.50 | 23.95 |
March | 85.67 | 23.56 | 291.17 | 23.91 | 45.67 | 23.93 |
April | 28.00 | 24.50 | 341.83 | 24.08 | 27.00 | 24.11 |
May | 95.67 | 24.30 | 375.00 | 24.11 | 95.67 | 24.15 |
June | 170.83 | 24.26 | 366.00 | 24.15 | 170.83 | 24.17 |
July | 155.83 | 24.35 | 369.00 | 24.18 | 155.83 | 24.22 |
August | 195.33 | 24.24 | 379.00 | 24.14 | 195.33 | 24.17 |
September | 142.00 | 24.37 | 360.00 | 24.18 | 142.00 | 24.22 |
October | 110.00 | 24.30 | 371.00 | 24.13 | 110.00 | 24.16 |
November | 110.17 | 24.14 | 333.17 | 24.06 | 104.50 | 24.09 |
December | 84.50 | 23.71 | 283.33 | 23.93 | 54.67 | 23.96 |
Annual Sum or Average | 1313.17 | 24.13 | 3974.50 | 24.07 | 1160.50 | 24.11 |
Minimum of Months | 28.00 | 23.53 | 250.00 | 23.87 | 27.00 | 23.89 |
Maximum of Months | 195.33 | 24.50 | 379.00 | 24.18 | 195.33 | 24.22 |
Report: ComfortReportSimple55Monthly
For: SMSTORE4
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 87.50 | 23.50 | 250.50 | 23.85 | 35.67 | 23.87 |
February | 63.17 | 23.54 | 247.67 | 23.91 | 30.50 | 23.93 |
March | 92.50 | 23.54 | 286.00 | 23.89 | 49.50 | 23.92 |
April | 30.00 | 24.46 | 340.83 | 24.08 | 29.00 | 24.11 |
May | 102.17 | 24.28 | 375.00 | 24.11 | 102.17 | 24.14 |
June | 182.50 | 24.23 | 366.00 | 24.14 | 182.50 | 24.16 |
July | 165.00 | 24.32 | 369.00 | 24.17 | 165.00 | 24.21 |
August | 206.00 | 24.22 | 379.00 | 24.13 | 206.00 | 24.16 |
September | 150.00 | 24.34 | 360.00 | 24.17 | 150.00 | 24.21 |
October | 116.33 | 24.28 | 371.00 | 24.12 | 116.33 | 24.15 |
November | 116.50 | 24.12 | 331.67 | 24.06 | 110.67 | 24.08 |
December | 92.67 | 23.67 | 273.17 | 23.90 | 58.83 | 23.94 |
Annual Sum or Average | 1404.33 | 24.10 | 3949.83 | 24.06 | 1236.17 | 24.10 |
Minimum of Months | 30.00 | 23.50 | 247.67 | 23.85 | 29.00 | 23.87 |
Maximum of Months | 206.00 | 24.46 | 379.00 | 24.17 | 206.00 | 24.21 |
Report: ComfortReportSimple55Monthly
For: LGSTORE2
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 100.83 | 23.52 | 216.83 | 23.79 | 45.50 | 23.81 |
February | 78.67 | 23.62 | 219.83 | 23.85 | 47.67 | 23.87 |
March | 109.33 | 23.59 | 250.83 | 23.83 | 64.00 | 23.85 |
April | 37.83 | 24.18 | 309.50 | 23.98 | 37.17 | 24.00 |
May | 105.67 | 24.05 | 344.00 | 23.97 | 105.67 | 23.99 |
June | 218.17 | 23.98 | 336.00 | 23.96 | 218.17 | 23.97 |
July | 202.83 | 24.04 | 338.00 | 24.00 | 202.83 | 24.01 |
August | 234.00 | 23.98 | 348.00 | 23.96 | 234.00 | 23.97 |
September | 179.33 | 24.05 | 330.00 | 24.01 | 179.33 | 24.02 |
October | 132.17 | 24.05 | 340.00 | 23.99 | 132.17 | 24.00 |
November | 124.67 | 23.95 | 298.17 | 23.94 | 119.83 | 23.95 |
December | 99.33 | 23.62 | 233.50 | 23.84 | 65.33 | 23.87 |
Annual Sum or Average | 1622.83 | 23.91 | 3564.67 | 23.94 | 1451.67 | 23.96 |
Minimum of Months | 37.83 | 23.52 | 216.83 | 23.79 | 37.17 | 23.81 |
Maximum of Months | 234.00 | 24.18 | 348.00 | 24.01 | 234.00 | 24.02 |
Report: ComfortReportSimple55Monthly
For: SMSTORE5
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 106.67 | 23.52 | 204.33 | 23.78 | 47.00 | 23.81 |
February | 85.83 | 23.63 | 211.50 | 23.85 | 50.50 | 23.87 |
March | 115.17 | 23.59 | 244.17 | 23.82 | 65.17 | 23.85 |
April | 40.33 | 24.14 | 304.17 | 23.98 | 39.33 | 24.00 |
May | 110.50 | 24.04 | 344.00 | 23.97 | 110.50 | 23.98 |
June | 222.17 | 23.98 | 336.00 | 23.96 | 222.17 | 23.97 |
July | 205.00 | 24.03 | 338.00 | 24.00 | 205.00 | 24.01 |
August | 237.00 | 23.98 | 348.00 | 23.96 | 237.00 | 23.96 |
September | 189.00 | 24.04 | 330.00 | 24.00 | 189.00 | 24.01 |
October | 134.83 | 24.04 | 340.00 | 23.98 | 134.83 | 24.00 |
November | 127.33 | 23.95 | 293.50 | 23.94 | 121.83 | 23.95 |
December | 104.67 | 23.62 | 223.83 | 23.84 | 68.50 | 23.86 |
Annual Sum or Average | 1678.50 | 23.91 | 3517.50 | 23.94 | 1490.83 | 23.95 |
Minimum of Months | 40.33 | 23.52 | 204.33 | 23.78 | 39.33 | 23.81 |
Maximum of Months | 237.00 | 24.14 | 348.00 | 24.00 | 237.00 | 24.01 |
Report: ComfortReportSimple55Monthly
For: SMSTORE6
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 111.17 | 23.50 | 200.00 | 23.77 | 48.00 | 23.80 |
February | 89.00 | 23.63 | 209.83 | 23.84 | 52.50 | 23.86 |
March | 118.00 | 23.59 | 243.17 | 23.82 | 67.00 | 23.84 |
April | 41.50 | 24.13 | 303.33 | 23.98 | 40.50 | 24.00 |
May | 111.67 | 24.03 | 344.00 | 23.97 | 111.67 | 23.98 |
June | 224.83 | 23.98 | 336.00 | 23.96 | 224.83 | 23.97 |
July | 208.50 | 24.03 | 338.00 | 24.00 | 208.50 | 24.01 |
August | 240.17 | 23.97 | 348.00 | 23.96 | 240.17 | 23.96 |
September | 191.50 | 24.04 | 330.00 | 24.00 | 191.50 | 24.01 |
October | 137.67 | 24.04 | 340.00 | 23.98 | 137.67 | 24.00 |
November | 128.50 | 23.95 | 292.33 | 23.94 | 122.67 | 23.95 |
December | 106.83 | 23.61 | 223.17 | 23.83 | 70.00 | 23.86 |
Annual Sum or Average | 1709.33 | 23.90 | 3507.83 | 23.93 | 1515.00 | 23.95 |
Minimum of Months | 41.50 | 23.50 | 200.00 | 23.77 | 40.50 | 23.80 |
Maximum of Months | 240.17 | 24.13 | 348.00 | 24.00 | 240.17 | 24.01 |
Report: ComfortReportSimple55Monthly
For: SMSTORE7
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 117.50 | 23.46 | 195.33 | 23.74 | 50.67 | 23.78 |
February | 93.33 | 23.60 | 208.17 | 23.83 | 55.33 | 23.85 |
March | 122.00 | 23.56 | 242.33 | 23.81 | 69.00 | 23.83 |
April | 43.33 | 24.12 | 303.83 | 23.98 | 42.17 | 23.99 |
May | 112.17 | 24.04 | 344.00 | 23.97 | 112.17 | 23.98 |
June | 223.00 | 23.98 | 336.00 | 23.96 | 223.00 | 23.97 |
July | 203.67 | 24.04 | 338.00 | 24.00 | 203.67 | 24.01 |
August | 237.33 | 23.97 | 348.00 | 23.96 | 237.33 | 23.96 |
September | 188.17 | 24.04 | 330.00 | 24.00 | 188.17 | 24.01 |
October | 137.00 | 24.04 | 340.00 | 23.98 | 137.00 | 24.00 |
November | 131.00 | 23.94 | 291.50 | 23.93 | 124.33 | 23.94 |
December | 113.17 | 23.57 | 221.17 | 23.81 | 72.50 | 23.84 |
Annual Sum or Average | 1721.67 | 23.89 | 3498.33 | 23.93 | 1515.33 | 23.95 |
Minimum of Months | 43.33 | 23.46 | 195.33 | 23.74 | 42.17 | 23.78 |
Maximum of Months | 237.33 | 24.12 | 348.00 | 24.00 | 237.33 | 24.01 |
Report: ComfortReportSimple55Monthly
For: SMSTORE8
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 113.17 | 23.39 | 204.67 | 23.73 | 45.17 | 23.76 |
February | 82.00 | 23.52 | 218.67 | 23.82 | 45.00 | 23.84 |
March | 110.67 | 23.58 | 248.83 | 23.82 | 59.33 | 23.85 |
April | 34.50 | 24.24 | 311.50 | 23.99 | 33.33 | 24.01 |
May | 83.83 | 24.10 | 344.00 | 23.98 | 83.83 | 24.00 |
June | 147.67 | 24.03 | 336.00 | 23.98 | 147.67 | 23.99 |
July | 115.50 | 24.18 | 338.00 | 24.04 | 115.50 | 24.07 |
August | 153.17 | 24.04 | 348.00 | 23.98 | 153.17 | 23.99 |
September | 108.67 | 24.18 | 330.00 | 24.04 | 108.67 | 24.07 |
October | 96.67 | 24.13 | 340.00 | 24.01 | 96.67 | 24.03 |
November | 112.33 | 23.95 | 295.67 | 23.94 | 105.67 | 23.95 |
December | 110.83 | 23.47 | 220.33 | 23.77 | 62.50 | 23.81 |
Annual Sum or Average | 1269.00 | 23.89 | 3535.67 | 23.94 | 1056.50 | 23.96 |
Minimum of Months | 34.50 | 23.39 | 204.67 | 23.73 | 33.33 | 23.76 |
Maximum of Months | 153.17 | 24.24 | 348.00 | 24.04 | 153.17 | 24.07 |
Report: OccupantComfortDataSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 496.00000 | 23.76398 | 50.12034 | 0.44471 | 9.70769 |
February | 448.00000 | 23.79135 | 50.12569 | 0.46784 | 10.16980 |
March | 497.00000 | 23.77758 | 51.95280 | 0.48410 | 10.62949 |
April | 479.00000 | 23.88330 | 54.96849 | 0.55832 | 11.65712 |
May | 496.00000 | 23.89008 | 60.56206 | -0.2286 | 6.17771 |
June | 481.00000 | 23.89148 | 63.63443 | -0.1885 | 5.81297 |
July | 495.00000 | 23.89172 | 62.81830 | -0.1718 | 5.70704 |
August | 497.00000 | 23.89192 | 64.01634 | -0.1769 | 5.74883 |
September | 479.00000 | 23.89146 | 62.76335 | -0.1762 | 5.74220 |
October | 496.00000 | 23.89105 | 60.64073 | 0.63381 | 13.50510 |
November | 480.00000 | 23.86652 | 57.87218 | 0.57536 | 12.23737 |
December | 496.00000 | 23.78259 | 54.09064 | 0.49234 | 10.63769 |
Annual Sum or Average | 5840.00000 | 23.85121 | 57.83795 | 0.22457 | 8.96906 |
Minimum of Months | 448.00000 | 23.76398 | 50.12034 | -0.2286 | 5.70704 |
Maximum of Months | 497.00000 | 23.89192 | 64.01634 | 0.63381 | 13.50510 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 496.00000 | 23.82324 | 47.38672 | 0.44349 | 9.48242 |
February | 448.00000 | 23.84703 | 47.87325 | 0.46317 | 9.84381 |
March | 497.00000 | 23.81600 | 49.54046 | 0.47130 | 10.14546 |
April | 479.00000 | 23.88489 | 52.45888 | 0.52885 | 10.98363 |
May | 496.00000 | 23.89005 | 57.84854 | -0.2738 | 6.68021 |
June | 481.00000 | 23.89114 | 60.97188 | -0.2350 | 6.25712 |
July | 495.00000 | 23.89117 | 60.33752 | -0.2245 | 6.17692 |
August | 497.00000 | 23.89144 | 61.44843 | -0.2271 | 6.20179 |
September | 479.00000 | 23.89110 | 60.17906 | -0.2266 | 6.19753 |
October | 496.00000 | 23.89074 | 57.81248 | 0.59643 | 12.56693 |
November | 480.00000 | 23.87574 | 55.07282 | 0.54882 | 11.55156 |
December | 496.00000 | 23.83770 | 50.92492 | 0.48211 | 10.21743 |
Annual Sum or Average | 5840.00000 | 23.86918 | 55.19216 | 0.19385 | 8.85173 |
Minimum of Months | 448.00000 | 23.81600 | 47.38672 | -0.2738 | 6.17692 |
Maximum of Months | 497.00000 | 23.89144 | 61.44843 | 0.59643 | 12.56693 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 23.86241 | 49.16060 | 0.46340 | 10.03806 |
February | 336.00000 | 23.91161 | 49.63688 | 0.48882 | 10.57598 |
March | 379.00000 | 23.88908 | 51.22528 | 0.49599 | 10.90027 |
April | 360.00000 | 24.03703 | 55.08616 | 0.57814 | 12.23531 |
May | 375.00000 | 24.06468 | 60.76812 | -0.2039 | 6.25740 |
June | 366.00000 | 24.09082 | 64.07740 | -0.1563 | 6.01127 |
July | 369.00000 | 24.11035 | 63.76177 | -0.1356 | 5.98699 |
August | 379.00000 | 24.09079 | 64.72241 | -0.1465 | 5.95979 |
September | 360.00000 | 24.10462 | 63.44593 | -0.1410 | 5.98919 |
October | 371.00000 | 24.07370 | 60.80836 | 0.65792 | 14.34570 |
November | 360.00000 | 24.01518 | 58.02449 | 0.60009 | 12.92194 |
December | 369.00000 | 23.88858 | 53.10000 | 0.50722 | 10.95502 |
Annual Sum or Average | 4395.00000 | 24.01195 | 57.87108 | 0.24790 | 9.32897 |
Minimum of Months | 336.00000 | 23.86241 | 49.16060 | -0.2039 | 5.95979 |
Maximum of Months | 379.00000 | 24.11035 | 64.72241 | 0.65792 | 14.34570 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 23.85330 | 49.24435 | 0.45951 | 9.98922 |
February | 336.00000 | 23.90577 | 49.71620 | 0.48592 | 10.53481 |
March | 379.00000 | 23.88342 | 51.28184 | 0.49356 | 10.87037 |
April | 360.00000 | 24.03659 | 55.09162 | 0.57794 | 12.22974 |
May | 375.00000 | 24.06456 | 60.74782 | -0.2036 | 6.25521 |
June | 366.00000 | 24.09108 | 64.01045 | -0.1552 | 6.00641 |
July | 369.00000 | 24.11083 | 63.67388 | -0.1340 | 5.98226 |
August | 379.00000 | 24.09102 | 64.65944 | -0.1455 | 5.95587 |
September | 360.00000 | 24.10508 | 63.35811 | -0.1395 | 5.98488 |
October | 371.00000 | 24.07383 | 60.75474 | 0.65844 | 14.36119 |
November | 360.00000 | 24.01394 | 58.03856 | 0.59940 | 12.91047 |
December | 369.00000 | 23.88200 | 53.18931 | 0.50449 | 10.91534 |
Annual Sum or Average | 4395.00000 | 24.00968 | 57.86635 | 0.24735 | 9.31403 |
Minimum of Months | 336.00000 | 23.85330 | 49.24435 | -0.2036 | 5.95587 |
Maximum of Months | 379.00000 | 24.11083 | 64.65944 | 0.65844 | 14.36119 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 23.83086 | 49.55057 | 0.45092 | 9.87199 |
February | 336.00000 | 23.88954 | 50.01905 | 0.47884 | 10.42782 |
March | 379.00000 | 23.86613 | 51.58838 | 0.48662 | 10.77213 |
April | 360.00000 | 24.03201 | 55.37536 | 0.57457 | 12.14259 |
May | 375.00000 | 24.06060 | 61.04525 | -0.2080 | 6.27629 |
June | 366.00000 | 24.08713 | 64.31108 | -0.1591 | 6.01035 |
July | 369.00000 | 24.10697 | 63.94138 | -0.1377 | 5.98041 |
August | 379.00000 | 24.08707 | 64.95730 | -0.1493 | 5.95773 |
September | 360.00000 | 24.10122 | 63.63616 | -0.1432 | 5.98463 |
October | 371.00000 | 24.06995 | 61.02909 | 0.65612 | 14.28804 |
November | 360.00000 | 24.00797 | 58.35412 | 0.59596 | 12.82640 |
December | 369.00000 | 23.86402 | 53.53936 | 0.49759 | 10.80723 |
Annual Sum or Average | 4395.00000 | 24.00070 | 58.16476 | 0.24251 | 9.26031 |
Minimum of Months | 336.00000 | 23.83086 | 49.55057 | -0.2080 | 5.95773 |
Maximum of Months | 379.00000 | 24.10697 | 64.95730 | 0.65612 | 14.28804 |
Report: OccupantComfortDataSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 23.77321 | 51.17409 | 0.43326 | 9.53214 |
February | 308.00000 | 23.83568 | 51.70070 | 0.46446 | 10.09640 |
March | 348.00000 | 23.79968 | 53.20912 | 0.46989 | 10.38920 |
April | 330.00000 | 23.95204 | 56.97250 | 0.55901 | 11.72566 |
May | 344.00000 | 23.94841 | 62.72495 | -0.2387 | 6.39254 |
June | 336.00000 | 23.95105 | 66.03983 | -0.1943 | 6.01155 |
July | 338.00000 | 23.98202 | 65.50942 | -0.1674 | 5.93444 |
August | 348.00000 | 23.94959 | 66.67758 | -0.1840 | 5.95085 |
September | 330.00000 | 23.97948 | 65.20330 | -0.1720 | 5.96785 |
October | 340.00000 | 23.96254 | 62.52502 | 0.63877 | 13.73586 |
November | 330.00000 | 23.92040 | 60.09958 | 0.57923 | 12.30784 |
December | 338.00000 | 23.81411 | 55.21296 | 0.48253 | 10.48341 |
Annual Sum or Average | 4030.00000 | 23.90579 | 59.80742 | 0.21961 | 9.02624 |
Minimum of Months | 308.00000 | 23.77321 | 51.17409 | -0.2387 | 5.93444 |
Maximum of Months | 348.00000 | 23.98202 | 66.67758 | 0.63877 | 13.73586 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 23.76828 | 51.18615 | 0.42053 | 9.30888 |
February | 308.00000 | 23.83235 | 51.73125 | 0.45087 | 9.83998 |
March | 348.00000 | 23.79452 | 53.25420 | 0.45548 | 10.11361 |
April | 330.00000 | 23.95112 | 57.03462 | 0.54397 | 11.37022 |
May | 344.00000 | 23.94764 | 62.82367 | -0.2621 | 6.63109 |
June | 336.00000 | 23.95001 | 66.19174 | -0.2188 | 6.21485 |
July | 338.00000 | 23.98045 | 65.64860 | -0.1937 | 6.12108 |
August | 348.00000 | 23.94875 | 66.82472 | -0.2087 | 6.14375 |
September | 330.00000 | 23.97805 | 65.35144 | -0.1978 | 6.15441 |
October | 340.00000 | 23.96176 | 62.62999 | 0.62188 | 13.28337 |
November | 330.00000 | 23.91984 | 60.19927 | 0.56480 | 11.95365 |
December | 338.00000 | 23.81201 | 55.27407 | 0.46979 | 10.22444 |
Annual Sum or Average | 4030.00000 | 23.90383 | 59.89950 | 0.20085 | 8.93090 |
Minimum of Months | 308.00000 | 23.76828 | 51.18615 | -0.2621 | 6.12108 |
Maximum of Months | 348.00000 | 23.98045 | 66.82472 | 0.62188 | 13.28337 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 23.75932 | 51.28062 | 0.41673 | 9.26572 |
February | 308.00000 | 23.82815 | 51.82329 | 0.44807 | 9.80263 |
March | 348.00000 | 23.79011 | 53.34206 | 0.45292 | 10.08098 |
April | 330.00000 | 23.95070 | 57.11213 | 0.54269 | 11.34027 |
May | 344.00000 | 23.94737 | 62.90445 | -0.2639 | 6.64854 |
June | 336.00000 | 23.94978 | 66.26939 | -0.2203 | 6.22724 |
July | 338.00000 | 23.98013 | 65.71849 | -0.1952 | 6.13092 |
August | 348.00000 | 23.94854 | 66.90099 | -0.2102 | 6.15511 |
September | 330.00000 | 23.97776 | 65.42247 | -0.1993 | 6.16437 |
October | 340.00000 | 23.96146 | 62.70465 | 0.62085 | 13.25533 |
November | 330.00000 | 23.91900 | 60.28769 | 0.56340 | 11.92324 |
December | 338.00000 | 23.80566 | 55.38649 | 0.46664 | 10.17973 |
Annual Sum or Average | 4030.00000 | 23.90160 | 59.98303 | 0.19887 | 8.91568 |
Minimum of Months | 308.00000 | 23.75932 | 51.28062 | -0.2639 | 6.13092 |
Maximum of Months | 348.00000 | 23.98013 | 66.90099 | 0.62085 | 13.25533 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 23.73595 | 51.48659 | 0.41004 | 9.21861 |
February | 308.00000 | 23.81575 | 52.00841 | 0.44398 | 9.77774 |
March | 348.00000 | 23.77978 | 53.49725 | 0.45037 | 10.07803 |
April | 330.00000 | 23.95008 | 57.20043 | 0.54381 | 11.36835 |
May | 344.00000 | 23.94729 | 62.92961 | -0.2606 | 6.61412 |
June | 336.00000 | 23.94992 | 66.21615 | -0.2159 | 6.18999 |
July | 338.00000 | 23.98051 | 65.62769 | -0.1900 | 6.09392 |
August | 348.00000 | 23.94860 | 66.84167 | -0.2057 | 6.11940 |
September | 330.00000 | 23.97803 | 65.33931 | -0.1944 | 6.12862 |
October | 340.00000 | 23.96147 | 62.69843 | 0.62336 | 13.32220 |
November | 330.00000 | 23.91655 | 60.38475 | 0.56373 | 11.94634 |
December | 338.00000 | 23.78628 | 55.62369 | 0.46100 | 10.13198 |
Annual Sum or Average | 4030.00000 | 23.89598 | 60.04067 | 0.19950 | 8.90022 |
Minimum of Months | 308.00000 | 23.73595 | 51.48659 | -0.2606 | 6.09392 |
Maximum of Months | 348.00000 | 23.98051 | 66.84167 | 0.62336 | 13.32220 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 23.72103 | 51.11106 | 0.41364 | 9.41345 |
February | 308.00000 | 23.80552 | 51.54105 | 0.45400 | 10.08721 |
March | 348.00000 | 23.79714 | 52.83424 | 0.46964 | 10.47090 |
April | 330.00000 | 23.95559 | 56.10544 | 0.57163 | 12.05876 |
May | 344.00000 | 23.95404 | 61.31916 | -0.2095 | 6.16584 |
June | 336.00000 | 23.95709 | 64.09410 | -0.1604 | 5.82026 |
July | 338.00000 | 23.99242 | 63.21760 | -0.1238 | 5.76560 |
August | 348.00000 | 23.95525 | 64.83038 | -0.1505 | 5.79386 |
September | 330.00000 | 23.98838 | 63.13050 | -0.1330 | 5.80901 |
October | 340.00000 | 23.96919 | 61.11742 | 0.65587 | 14.23370 |
November | 330.00000 | 23.91696 | 59.31894 | 0.58313 | 12.47762 |
December | 338.00000 | 23.75748 | 55.26011 | 0.45994 | 10.31323 |
Annual Sum or Average | 4030.00000 | 23.89776 | 58.70412 | 0.23310 | 9.01546 |
Minimum of Months | 308.00000 | 23.72103 | 51.11106 | -0.2095 | 5.76560 |
Maximum of Months | 348.00000 | 23.99242 | 64.83038 | 0.65587 | 14.23370 |
Report: DXReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.142694E+11 | 0.365170E+10 | 420.18 | 0.930252E+10 | 0.496686E+10 | 0.00 | 1.00 | 02-JAN-14:10 | 0.00 | 01-JAN-00:05 | 58944.71 | 14-JAN-08:62 | 31513.76 | 14-JAN-08:62 | 28140.18 | 07-JAN-08:62 | 12420.79 | 14-JAN-08:62 | 0.00 | 01-JAN-00:05 |
February | 0.166455E+11 | 0.424539E+10 | 398.60 | 0.112992E+11 | 0.534630E+10 | 0.00 | 1.00 | 02-FEB-08:62 | 0.00 | 01-FEB-00:10 | 59721.91 | 11-FEB-08:62 | 33724.75 | 18-FEB-08:62 | 28767.39 | 11-FEB-08:62 | 12843.82 | 11-FEB-08:62 | 0.00 | 01-FEB-00:10 |
March | 0.203526E+11 | 0.511904E+10 | 449.65 | 0.130846E+11 | 0.726796E+10 | 0.00 | 1.00 | 04-MAR-08:62 | 0.00 | 01-MAR-00:05 | 60110.70 | 14-MAR-07:03 | 30850.91 | 30-MAR-07:03 | 31255.93 | 14-MAR-07:03 | 12786.92 | 10-MAR-08:62 | 0.00 | 01-MAR-00:05 |
April | 0.266932E+11 | 0.671654E+10 | 476.02 | 0.175320E+11 | 0.916123E+10 | 0.00 | 1.00 | 01-APR-07:03 | 0.00 | 01-APR-00:05 | 59896.13 | 13-APR-07:02 | 34500.37 | 25-APR-07:03 | 28560.54 | 13-APR-07:02 | 13003.76 | 12-APR-07:02 | 0.00 | 01-APR-00:05 |
May | 0.375402E+11 | 0.922447E+10 | 500.23 | 0.226969E+11 | 0.148433E+11 | 0.00 | 1.00 | 02-MAY-07:03 | 0.00 | 01-MAY-00:10 | 61063.46 | 29-MAY-07:02 | 39097.09 | 09-MAY-07:02 | 33451.38 | 29-MAY-07:02 | 13165.18 | 31-MAY-07:02 | 0.00 | 01-MAY-00:10 |
June | 0.425802E+11 | 0.102708E+11 | 487.68 | 0.241519E+11 | 0.184284E+11 | 0.00 | 1.00 | 01-JUN-07:02 | 0.00 | 01-JUN-00:10 | 60700.33 | 08-JUN-07:01 | 35024.98 | 17-JUN-07:02 | 30405.62 | 22-JUN-07:02 | 13386.65 | 09-JUN-07:03 | 0.00 | 01-JUN-00:10 |
July | 0.472979E+11 | 0.115043E+11 | 502.52 | 0.273953E+11 | 0.199026E+11 | 0.00 | 1.00 | 01-JUL-07:02 | 0.00 | 01-JUL-00:05 | 60116.42 | 09-JUL-07:01 | 39666.56 | 02-JUL-07:01 | 28462.86 | 27-JUL-07:03 | 13381.19 | 16-JUL-07:01 | 0.00 | 01-JUL-00:05 |
August | 0.461451E+11 | 0.111428E+11 | 502.54 | 0.260652E+11 | 0.200800E+11 | 0.00 | 1.00 | 01-AUG-07:01 | 0.00 | 01-AUG-00:10 | 60426.79 | 20-AUG-07:01 | 37085.81 | 08-AUG-07:02 | 30087.54 | 10-AUG-07:03 | 13476.60 | 20-AUG-07:04 | 0.00 | 01-AUG-00:10 |
September | 0.440049E+11 | 0.106339E+11 | 485.12 | 0.253645E+11 | 0.186404E+11 | 0.00 | 1.00 | 01-SEP-07:02 | 0.00 | 01-SEP-00:05 | 60600.38 | 22-SEP-07:01 | 35695.66 | 11-SEP-07:01 | 29575.89 | 22-SEP-07:03 | 13309.69 | 09-SEP-07:01 | 0.00 | 01-SEP-00:05 |
October | 0.393541E+11 | 0.956264E+10 | 499.74 | 0.233585E+11 | 0.159956E+11 | 0.00 | 1.00 | 01-OCT-07:01 | 0.00 | 01-OCT-00:10 | 61349.27 | 04-OCT-07:02 | 41454.12 | 18-OCT-07:02 | 33399.93 | 03-OCT-07:03 | 13170.23 | 02-OCT-07:03 | 0.00 | 01-OCT-00:10 |
November | 0.288546E+11 | 0.704127E+10 | 469.74 | 0.171474E+11 | 0.117072E+11 | 0.00 | 1.00 | 01-NOV-07:03 | 0.00 | 01-NOV-00:10 | 61087.30 | 30-NOV-08:62 | 36368.89 | 20-NOV-08:62 | 32643.02 | 30-NOV-08:03 | 13036.71 | 21-NOV-08:62 | 0.00 | 01-NOV-00:10 |
December | 0.184243E+11 | 0.458684E+10 | 436.01 | 0.112471E+11 | 0.717718E+10 | 0.00 | 1.00 | 01-DEC-08:62 | 0.00 | 01-DEC-01:05 | 59836.55 | 09-DEC-08:62 | 38310.41 | 01-DEC-08:62 | 28209.22 | 09-DEC-08:62 | 12869.82 | 09-DEC-08:62 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.382162E+12 | 0.936997E+11 | 5628.03 | 0.228645E+12 | 0.153517E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.142694E+11 | 0.365170E+10 | 398.60 | 0.930252E+10 | 0.496686E+10 | 0.00 | 1.00 | 0.00 | 58944.71 | 30850.91 | 28140.18 | 12420.79 | 0.00 | |||||||
Maximum of Months | 0.472979E+11 | 0.115043E+11 | 502.54 | 0.273953E+11 | 0.200800E+11 | 0.00 | 1.00 | 0.00 | 61349.27 | 41454.12 | 33451.38 | 13476.60 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.831325E+10 | 0.209218E+10 | 454.43 | 0.569124E+10 | 0.262201E+10 | 0.00 | 1.00 | 02-JAN-14:00 | 0.00 | 01-JAN-00:05 | 29791.68 | 14-JAN-08:62 | 18880.58 | 14-JAN-08:62 | 10911.10 | 14-JAN-08:62 | 6247.11 | 14-JAN-08:62 | 0.00 | 01-JAN-00:05 |
February | 0.915496E+10 | 0.229686E+10 | 419.44 | 0.641836E+10 | 0.273660E+10 | 0.00 | 1.00 | 02-FEB-08:62 | 0.00 | 01-FEB-00:10 | 29971.41 | 11-FEB-08:62 | 19900.60 | 18-FEB-08:62 | 10986.08 | 11-FEB-08:62 | 6486.31 | 11-FEB-08:62 | 0.00 | 01-FEB-00:10 |
March | 0.107568E+11 | 0.267133E+10 | 465.03 | 0.717681E+10 | 0.357998E+10 | 0.00 | 1.00 | 04-MAR-08:62 | 0.00 | 01-MAR-00:05 | 30285.40 | 14-MAR-07:03 | 18919.68 | 06-MAR-08:62 | 12583.03 | 14-MAR-07:03 | 6455.20 | 05-MAR-08:62 | 0.00 | 01-MAR-00:05 |
April | 0.135423E+11 | 0.336654E+10 | 477.97 | 0.912738E+10 | 0.441495E+10 | 0.00 | 1.00 | 01-APR-07:03 | 0.00 | 01-APR-00:05 | 30093.60 | 13-APR-07:02 | 20998.57 | 14-APR-07:03 | 11134.32 | 13-APR-07:02 | 6573.95 | 12-APR-07:02 | 0.00 | 01-APR-00:05 |
May | 0.184894E+11 | 0.450691E+10 | 500.84 | 0.114851E+11 | 0.700430E+10 | 0.00 | 1.00 | 02-MAY-07:03 | 0.00 | 01-MAY-00:10 | 30439.78 | 27-MAY-07:02 | 21858.85 | 09-MAY-07:02 | 12658.10 | 27-MAY-07:02 | 6671.68 | 31-MAY-07:02 | 0.00 | 01-MAY-00:10 |
June | 0.207897E+11 | 0.498350E+10 | 488.21 | 0.121252E+11 | 0.866452E+10 | 0.00 | 1.00 | 01-JUN-07:02 | 0.00 | 01-JUN-00:10 | 30409.92 | 08-JUN-07:01 | 20896.50 | 02-JUN-07:02 | 11941.58 | 08-JUN-07:03 | 6809.86 | 08-JUN-07:01 | 0.00 | 01-JUN-00:10 |
July | 0.229969E+11 | 0.556102E+10 | 502.02 | 0.136619E+11 | 0.933496E+10 | 0.00 | 1.00 | 01-JUL-07:02 | 0.00 | 01-JUL-00:05 | 30153.38 | 09-JUL-07:01 | 22827.30 | 02-JUL-07:01 | 10986.64 | 09-JUL-07:03 | 6788.35 | 09-JUL-07:01 | 0.00 | 01-JUL-00:05 |
August | 0.224441E+11 | 0.538702E+10 | 502.98 | 0.130136E+11 | 0.943050E+10 | 0.00 | 1.00 | 01-AUG-07:01 | 0.00 | 01-AUG-00:10 | 30332.55 | 27-AUG-07:01 | 21622.22 | 08-AUG-07:02 | 11712.28 | 27-AUG-07:03 | 6856.71 | 20-AUG-07:01 | 0.00 | 01-AUG-00:10 |
September | 0.214439E+11 | 0.514906E+10 | 486.49 | 0.126908E+11 | 0.875316E+10 | 0.00 | 1.00 | 01-SEP-07:02 | 0.00 | 01-SEP-00:05 | 30394.61 | 19-SEP-07:01 | 21472.74 | 04-SEP-07:02 | 11704.96 | 19-SEP-07:03 | 6756.08 | 22-SEP-07:01 | 0.00 | 01-SEP-00:05 |
October | 0.194370E+11 | 0.468371E+10 | 499.24 | 0.118884E+11 | 0.754862E+10 | 0.00 | 1.00 | 01-OCT-07:01 | 0.00 | 01-OCT-00:10 | 30682.00 | 04-OCT-07:02 | 22940.25 | 18-OCT-07:02 | 13355.20 | 03-OCT-07:03 | 6694.26 | 02-OCT-07:02 | 0.00 | 01-OCT-00:10 |
November | 0.147687E+11 | 0.356484E+10 | 473.66 | 0.911745E+10 | 0.565128E+10 | 0.00 | 1.00 | 01-NOV-07:03 | 0.00 | 01-NOV-00:10 | 30693.48 | 30-NOV-08:62 | 21129.01 | 20-NOV-08:62 | 13162.35 | 30-NOV-08:62 | 6608.78 | 30-NOV-08:62 | 0.00 | 01-NOV-00:10 |
December | 0.100788E+11 | 0.248309E+10 | 463.91 | 0.648831E+10 | 0.359048E+10 | 0.00 | 1.00 | 01-DEC-08:62 | 0.00 | 01-DEC-01:05 | 29913.48 | 09-DEC-08:62 | 22529.55 | 01-DEC-08:62 | 10357.50 | 09-DEC-08:62 | 6495.46 | 09-DEC-08:62 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.192216E+12 | 0.467461E+11 | 5734.22 | 0.118885E+12 | 0.733313E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.831325E+10 | 0.209218E+10 | 419.44 | 0.569124E+10 | 0.262201E+10 | 0.00 | 1.00 | 0.00 | 29791.68 | 18880.58 | 10357.50 | 6247.11 | 0.00 | |||||||
Maximum of Months | 0.229969E+11 | 0.556102E+10 | 502.98 | 0.136619E+11 | 0.943050E+10 | 0.00 | 1.00 | 0.00 | 30693.48 | 22940.25 | 13355.20 | 6856.71 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_3:3 COOLING COIL
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.586639E+10 | 0.147046E+10 | 302.07 | 0.388767E+10 | 0.197872E+10 | 0.00 | 1.00 | 01-JAN-08:63 | 0.00 | 01-JAN-00:05 | 31002.06 | 30-JAN-07:03 | 16626.14 | 14-JAN-07:02 | 15917.78 | 30-JAN-07:03 | 6444.36 | 07-JAN-07:03 | 0.00 | 01-JAN-00:05 |
February | 0.682380E+10 | 0.170895E+10 | 288.39 | 0.467984E+10 | 0.214397E+10 | 0.00 | 1.00 | 02-FEB-07:03 | 0.00 | 01-FEB-00:10 | 31142.16 | 11-FEB-07:03 | 17588.01 | 18-FEB-07:02 | 15399.29 | 11-FEB-07:03 | 6518.95 | 11-FEB-07:03 | 0.00 | 01-FEB-00:10 |
March | 0.807937E+10 | 0.199667E+10 | 326.24 | 0.522718E+10 | 0.285219E+10 | 0.00 | 1.00 | 04-MAR-07:03 | 0.00 | 01-MAR-00:05 | 31449.54 | 06-MAR-07:03 | 19168.25 | 31-MAR-06:03 | 16978.66 | 06-MAR-07:03 | 6522.74 | 05-MAR-08:62 | 0.00 | 01-MAR-00:05 |
April | 0.105188E+11 | 0.259933E+10 | 348.40 | 0.690484E+10 | 0.361391E+10 | 0.00 | 1.00 | 01-APR-06:03 | 0.00 | 01-APR-00:05 | 31174.53 | 13-APR-06:02 | 18980.19 | 01-APR-06:03 | 15057.59 | 13-APR-06:02 | 6584.06 | 12-APR-06:02 | 0.00 | 01-APR-00:05 |
May | 0.149553E+11 | 0.360945E+10 | 370.93 | 0.903741E+10 | 0.591787E+10 | 0.00 | 1.00 | 01-MAY-06:03 | 0.00 | 01-MAY-00:10 | 32202.03 | 29-MAY-07:02 | 19816.64 | 09-MAY-06:02 | 19182.85 | 29-MAY-07:02 | 6702.90 | 14-MAY-07:03 | 0.00 | 01-MAY-00:10 |
June | 0.171153E+11 | 0.403258E+10 | 363.66 | 0.961835E+10 | 0.749694E+10 | 0.00 | 1.00 | 01-JUN-06:02 | 0.00 | 01-JUN-00:10 | 31994.75 | 19-JUN-06:02 | 17760.08 | 17-JUN-06:02 | 18291.65 | 19-JUN-06:02 | 6813.84 | 08-JUN-06:04 | 0.00 | 01-JUN-00:10 |
July | 0.189531E+11 | 0.451958E+10 | 367.66 | 0.108652E+11 | 0.808797E+10 | 0.00 | 1.00 | 01-JUL-06:02 | 0.00 | 01-JUL-00:05 | 32136.89 | 31-JUL-06:01 | 17951.08 | 02-JUL-07:01 | 17929.54 | 31-JUL-06:03 | 6822.10 | 16-JUL-07:03 | 0.00 | 01-JUL-00:05 |
August | 0.187067E+11 | 0.442576E+10 | 377.33 | 0.104794E+11 | 0.822730E+10 | 0.00 | 1.00 | 01-AUG-06:01 | 0.00 | 01-AUG-00:10 | 32192.65 | 28-AUG-06:01 | 17370.19 | 30-AUG-06:02 | 18713.40 | 28-AUG-06:03 | 6859.83 | 20-AUG-07:04 | 0.00 | 01-AUG-00:10 |
September | 0.175210E+11 | 0.413734E+10 | 356.69 | 0.998870E+10 | 0.753235E+10 | 0.00 | 1.00 | 01-SEP-06:01 | 0.00 | 01-SEP-00:05 | 31947.34 | 18-SEP-06:01 | 17277.80 | 02-SEP-06:01 | 17335.57 | 25-SEP-06:04 | 6778.32 | 09-SEP-06:02 | 0.00 | 01-SEP-00:05 |
October | 0.157321E+11 | 0.374196E+10 | 366.44 | 0.931942E+10 | 0.641271E+10 | 0.00 | 1.00 | 01-OCT-07:01 | 0.00 | 01-OCT-00:10 | 32152.55 | 02-OCT-06:03 | 21725.93 | 18-OCT-06:02 | 19483.33 | 30-OCT-06:04 | 6672.08 | 02-OCT-06:02 | 0.00 | 01-OCT-00:10 |
November | 0.116374E+11 | 0.277958E+10 | 343.66 | 0.695322E+10 | 0.468422E+10 | 0.00 | 1.00 | 01-NOV-06:03 | 0.00 | 01-NOV-00:10 | 32180.91 | 05-NOV-07:02 | 18613.57 | 21-NOV-07:02 | 18616.82 | 05-NOV-07:03 | 6621.01 | 04-NOV-06:03 | 0.00 | 01-NOV-00:10 |
December | 0.722225E+10 | 0.176861E+10 | 315.39 | 0.451148E+10 | 0.271077E+10 | 0.00 | 1.00 | 01-DEC-07:02 | 0.00 | 01-DEC-00:10 | 31596.55 | 24-DEC-08:62 | 17250.62 | 01-DEC-07:02 | 17919.66 | 24-DEC-08:62 | 6544.46 | 09-DEC-07:02 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.153132E+12 | 0.367903E+11 | 4126.86 | 0.914727E+11 | 0.616589E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.586639E+10 | 0.147046E+10 | 288.39 | 0.388767E+10 | 0.197872E+10 | 0.00 | 1.00 | 0.00 | 31002.06 | 16626.14 | 15057.59 | 6444.36 | 0.00 | |||||||
Maximum of Months | 0.189531E+11 | 0.451958E+10 | 377.33 | 0.108652E+11 | 0.822730E+10 | 0.00 | 1.00 | 0.00 | 32202.03 | 21725.93 | 19483.33 | 6859.83 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_4:4 COOLING COIL
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.579430E+10 | 0.145380E+10 | 300.49 | 0.383205E+10 | 0.196225E+10 | 0.00 | 1.00 | 01-JAN-08:63 | 0.00 | 01-JAN-00:05 | 31084.58 | 30-JAN-07:03 | 16664.37 | 14-JAN-07:02 | 15994.27 | 30-JAN-07:03 | 6462.29 | 07-JAN-07:03 | 0.00 | 01-JAN-00:05 |
February | 0.676313E+10 | 0.169561E+10 | 287.64 | 0.463480E+10 | 0.212833E+10 | 0.00 | 1.00 | 02-FEB-07:03 | 0.00 | 01-FEB-00:10 | 31228.63 | 11-FEB-07:03 | 17636.97 | 18-FEB-07:02 | 15456.06 | 11-FEB-07:03 | 6537.06 | 11-FEB-07:03 | 0.00 | 01-FEB-00:10 |
March | 0.803131E+10 | 0.198640E+10 | 326.03 | 0.519105E+10 | 0.284026E+10 | 0.00 | 1.00 | 04-MAR-07:03 | 0.00 | 01-MAR-00:05 | 31537.10 | 06-MAR-07:03 | 19227.56 | 31-MAR-06:03 | 17028.60 | 06-MAR-07:03 | 6540.83 | 05-MAR-08:62 | 0.00 | 01-MAR-00:05 |
April | 0.105152E+11 | 0.259982E+10 | 348.40 | 0.690313E+10 | 0.361206E+10 | 0.00 | 1.00 | 01-APR-06:03 | 0.00 | 01-APR-00:05 | 31262.82 | 13-APR-06:02 | 19037.14 | 01-APR-06:03 | 15099.02 | 13-APR-06:02 | 6602.36 | 12-APR-06:02 | 0.00 | 01-APR-00:05 |
May | 0.149746E+11 | 0.361532E+10 | 370.93 | 0.905184E+10 | 0.592272E+10 | 0.00 | 1.00 | 01-MAY-06:03 | 0.00 | 01-MAY-00:10 | 32291.48 | 29-MAY-07:02 | 19882.45 | 09-MAY-06:02 | 19225.93 | 29-MAY-07:02 | 6721.49 | 14-MAY-07:03 | 0.00 | 01-MAY-00:10 |
June | 0.171713E+11 | 0.404601E+10 | 363.97 | 0.965771E+10 | 0.751360E+10 | 0.00 | 1.00 | 01-JUN-06:02 | 0.00 | 01-JUN-00:10 | 32089.14 | 19-JUN-06:02 | 17843.53 | 17-JUN-06:02 | 18311.44 | 19-JUN-06:02 | 6832.72 | 08-JUN-06:04 | 0.00 | 01-JUN-00:10 |
July | 0.190284E+11 | 0.453734E+10 | 367.53 | 0.109188E+11 | 0.810964E+10 | 0.00 | 1.00 | 01-JUL-06:02 | 0.00 | 01-JUL-00:05 | 32239.07 | 31-JUL-06:01 | 18049.18 | 02-JUL-07:01 | 17910.20 | 31-JUL-06:04 | 6840.95 | 16-JUL-07:03 | 0.00 | 01-JUL-00:05 |
August | 0.187612E+11 | 0.443882E+10 | 377.17 | 0.105179E+11 | 0.824333E+10 | 0.00 | 1.00 | 01-AUG-06:01 | 0.00 | 01-AUG-00:10 | 32282.07 | 28-AUG-06:01 | 17435.94 | 30-AUG-06:02 | 18722.66 | 28-AUG-06:03 | 6878.65 | 20-AUG-07:04 | 0.00 | 01-AUG-00:10 |
September | 0.175922E+11 | 0.415387E+10 | 356.83 | 0.100387E+11 | 0.755348E+10 | 0.00 | 1.00 | 01-SEP-06:01 | 0.00 | 01-SEP-00:05 | 32049.52 | 18-SEP-06:01 | 17366.51 | 02-SEP-06:01 | 17320.73 | 25-SEP-06:04 | 6797.12 | 09-SEP-06:02 | 0.00 | 01-SEP-00:05 |
October | 0.157774E+11 | 0.375310E+10 | 366.57 | 0.935148E+10 | 0.642587E+10 | 0.00 | 1.00 | 01-OCT-07:01 | 0.00 | 01-OCT-00:10 | 32241.86 | 30-OCT-06:01 | 21799.65 | 18-OCT-06:02 | 19498.26 | 30-OCT-06:04 | 6690.61 | 02-OCT-06:02 | 0.00 | 01-OCT-00:10 |
November | 0.116241E+11 | 0.277785E+10 | 343.39 | 0.694322E+10 | 0.468088E+10 | 0.00 | 1.00 | 01-NOV-06:03 | 0.00 | 01-NOV-00:10 | 32273.75 | 05-NOV-07:02 | 18674.11 | 21-NOV-07:02 | 18648.00 | 05-NOV-07:03 | 6639.36 | 04-NOV-06:03 | 0.00 | 01-NOV-00:10 |
December | 0.716125E+10 | 0.175501E+10 | 313.72 | 0.446971E+10 | 0.269154E+10 | 0.00 | 1.00 | 01-DEC-07:02 | 0.00 | 01-DEC-00:10 | 31681.60 | 24-DEC-08:62 | 17301.88 | 01-DEC-07:02 | 18011.16 | 24-DEC-08:62 | 6562.68 | 09-DEC-07:02 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.153194E+12 | 0.368130E+11 | 4122.65 | 0.915104E+11 | 0.616840E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.579430E+10 | 0.145380E+10 | 287.64 | 0.383205E+10 | 0.196225E+10 | 0.00 | 1.00 | 0.00 | 31084.58 | 16664.37 | 15099.02 | 6462.29 | 0.00 | |||||||
Maximum of Months | 0.190284E+11 | 0.453734E+10 | 377.17 | 0.109188E+11 | 0.824333E+10 | 0.00 | 1.00 | 0.00 | 32291.48 | 21799.65 | 19498.26 | 6878.65 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_5:5 COOLING COIL
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.553268E+10 | 0.139046E+10 | 292.52 | 0.363530E+10 | 0.189738E+10 | 0.00 | 1.00 | 01-JAN-08:63 | 0.00 | 01-JAN-00:05 | 30787.94 | 07-JAN-07:03 | 16394.38 | 14-JAN-07:02 | 15262.64 | 07-JAN-07:03 | 6406.29 | 07-JAN-07:03 | 0.00 | 01-JAN-00:05 |
February | 0.652085E+10 | 0.163830E+10 | 285.42 | 0.445395E+10 | 0.206690E+10 | 0.00 | 1.00 | 02-FEB-07:03 | 0.00 | 01-FEB-00:10 | 30949.67 | 11-FEB-07:03 | 17363.91 | 18-FEB-07:02 | 15458.20 | 11-FEB-07:03 | 6480.47 | 11-FEB-07:03 | 0.00 | 01-FEB-00:10 |
March | 0.776444E+10 | 0.192354E+10 | 322.86 | 0.499404E+10 | 0.277041E+10 | 0.00 | 1.00 | 04-MAR-07:03 | 0.00 | 01-MAR-00:05 | 31252.45 | 06-MAR-07:03 | 17621.65 | 30-MAR-06:03 | 16966.58 | 06-MAR-07:03 | 6484.28 | 05-MAR-08:62 | 0.00 | 01-MAR-00:05 |
April | 0.102646E+11 | 0.254149E+10 | 348.38 | 0.671825E+10 | 0.354635E+10 | 0.00 | 1.00 | 01-APR-06:03 | 0.00 | 01-APR-00:05 | 30982.69 | 13-APR-06:02 | 17995.26 | 17-APR-06:02 | 15090.24 | 13-APR-06:02 | 6545.19 | 12-APR-06:02 | 0.00 | 01-APR-00:05 |
May | 0.147222E+11 | 0.355715E+10 | 370.73 | 0.887216E+10 | 0.585003E+10 | 0.00 | 1.00 | 02-MAY-06:03 | 0.00 | 01-MAY-00:10 | 32013.17 | 29-MAY-07:02 | 19600.70 | 09-MAY-06:02 | 19169.29 | 29-MAY-07:02 | 6663.64 | 14-MAY-07:03 | 0.00 | 01-MAY-00:10 |
June | 0.169271E+11 | 0.398907E+10 | 363.49 | 0.948638E+10 | 0.744077E+10 | 0.00 | 1.00 | 01-JUN-06:02 | 0.00 | 01-JUN-00:10 | 31801.26 | 19-JUN-06:02 | 17566.00 | 17-JUN-06:02 | 18227.64 | 19-JUN-06:02 | 6768.48 | 08-JUN-06:03 | 0.00 | 01-JUN-00:10 |
July | 0.187981E+11 | 0.448185E+10 | 367.75 | 0.107534E+11 | 0.804476E+10 | 0.00 | 1.00 | 01-JUL-06:02 | 0.00 | 01-JUL-00:05 | 31952.48 | 31-JUL-06:01 | 17782.46 | 02-JUL-07:01 | 17818.17 | 31-JUL-06:03 | 6782.14 | 16-JUL-07:03 | 0.00 | 01-JUL-00:05 |
August | 0.185077E+11 | 0.437904E+10 | 377.19 | 0.103404E+11 | 0.816735E+10 | 0.00 | 1.00 | 01-AUG-06:01 | 0.00 | 01-AUG-00:10 | 32003.84 | 28-AUG-06:01 | 17151.42 | 30-AUG-06:02 | 18649.26 | 28-AUG-06:03 | 6819.57 | 20-AUG-07:04 | 0.00 | 01-AUG-00:10 |
September | 0.173653E+11 | 0.410033E+10 | 356.44 | 0.987754E+10 | 0.748774E+10 | 0.00 | 1.00 | 01-SEP-06:01 | 0.00 | 01-SEP-00:05 | 31763.44 | 18-SEP-06:01 | 17077.30 | 02-SEP-06:01 | 17223.07 | 25-SEP-06:04 | 6738.56 | 09-SEP-06:02 | 0.00 | 01-SEP-00:05 |
October | 0.155415E+11 | 0.369834E+10 | 366.54 | 0.918248E+10 | 0.635898E+10 | 0.00 | 1.00 | 01-OCT-07:01 | 0.00 | 01-OCT-00:10 | 31963.99 | 02-OCT-06:02 | 21509.94 | 18-OCT-06:02 | 19412.00 | 30-OCT-06:04 | 6632.95 | 02-OCT-06:02 | 0.00 | 01-OCT-00:10 |
November | 0.113690E+11 | 0.271968E+10 | 342.75 | 0.676064E+10 | 0.460832E+10 | 0.00 | 1.00 | 01-NOV-06:03 | 0.00 | 01-NOV-00:10 | 31986.36 | 05-NOV-07:02 | 18398.69 | 21-NOV-07:02 | 18593.12 | 05-NOV-07:02 | 6582.21 | 04-NOV-06:03 | 0.00 | 01-NOV-00:10 |
December | 0.689180E+10 | 0.169090E+10 | 310.37 | 0.427789E+10 | 0.261391E+10 | 0.00 | 1.00 | 01-DEC-07:02 | 0.00 | 01-DEC-00:10 | 31400.31 | 24-DEC-08:62 | 17010.96 | 01-DEC-07:02 | 18005.23 | 24-DEC-08:62 | 6505.93 | 09-DEC-07:02 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.150205E+12 | 0.361101E+11 | 4104.46 | 0.893524E+11 | 0.608529E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.553268E+10 | 0.139046E+10 | 285.42 | 0.363530E+10 | 0.189738E+10 | 0.00 | 1.00 | 0.00 | 30787.94 | 16394.38 | 15090.24 | 6406.29 | 0.00 | |||||||
Maximum of Months | 0.187981E+11 | 0.448185E+10 | 377.19 | 0.107534E+11 | 0.816735E+10 | 0.00 | 1.00 | 0.00 | 32013.17 | 21509.94 | 19412.00 | 6819.57 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_6:6 COOLING COIL
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.931719E+10 | 0.237164E+10 | 274.62 | 0.594674E+10 | 0.337045E+10 | 0.00 | 1.00 | 01-JAN-09:03 | 0.00 | 01-JAN-00:05 | 53252.25 | 14-JAN-08:62 | 28352.08 | 14-JAN-08:62 | 25447.71 | 07-JAN-08:62 | 11233.19 | 14-JAN-08:62 | 0.00 | 01-JAN-00:05 |
February | 0.111871E+11 | 0.284858E+10 | 281.85 | 0.749807E+10 | 0.368898E+10 | 0.00 | 1.00 | 02-FEB-08:62 | 0.00 | 01-FEB-00:10 | 54076.60 | 11-FEB-08:62 | 30309.69 | 18-FEB-08:62 | 26553.61 | 11-FEB-08:62 | 11624.61 | 11-FEB-08:62 | 0.00 | 01-FEB-00:10 |
March | 0.134218E+11 | 0.336233E+10 | 315.64 | 0.843007E+10 | 0.499176E+10 | 0.00 | 1.00 | 04-MAR-08:62 | 0.00 | 01-MAR-00:05 | 54831.62 | 06-MAR-08:62 | 28115.90 | 31-MAR-07:03 | 29864.73 | 06-MAR-08:62 | 11636.74 | 05-MAR-09:02 | 0.00 | 01-MAR-00:05 |
April | 0.180754E+11 | 0.452260E+10 | 338.97 | 0.116128E+11 | 0.646261E+10 | 0.00 | 1.00 | 01-APR-07:03 | 0.00 | 01-APR-00:05 | 53988.37 | 13-APR-07:02 | 31877.44 | 25-APR-07:03 | 25381.64 | 13-APR-07:02 | 11762.85 | 12-APR-07:02 | 0.00 | 01-APR-00:05 |
May | 0.263518E+11 | 0.642334E+10 | 362.47 | 0.156014E+11 | 0.107504E+11 | 0.00 | 1.00 | 02-MAY-07:03 | 0.00 | 01-MAY-00:10 | 56023.27 | 29-MAY-08:62 | 34820.53 | 09-MAY-07:02 | 33393.39 | 29-MAY-08:04 | 11986.43 | 14-MAY-08:03 | 0.00 | 01-MAY-00:10 |
June | 0.304788E+11 | 0.725715E+10 | 355.49 | 0.167761E+11 | 0.137027E+11 | 0.00 | 1.00 | 01-JUN-07:02 | 0.00 | 01-JUN-00:10 | 55909.57 | 26-JUN-07:02 | 31263.33 | 17-JUN-07:02 | 31690.97 | 19-JUN-07:02 | 12136.44 | 11-JUN-08:04 | 0.00 | 01-JUN-00:10 |
July | 0.338490E+11 | 0.815730E+10 | 356.66 | 0.190796E+11 | 0.147694E+11 | 0.00 | 1.00 | 01-JUL-07:02 | 0.00 | 01-JUL-00:05 | 56062.43 | 31-JUL-07:01 | 32195.21 | 07-JUL-07:02 | 31191.63 | 31-JUL-07:04 | 12288.15 | 23-JUL-08:04 | 0.00 | 01-JUL-00:05 |
August | 0.333873E+11 | 0.798581E+10 | 369.01 | 0.183448E+11 | 0.150425E+11 | 0.00 | 1.00 | 01-AUG-07:01 | 0.00 | 01-AUG-00:10 | 56152.28 | 28-AUG-07:02 | 32508.90 | 08-AUG-07:02 | 32580.72 | 28-AUG-07:03 | 12246.89 | 20-AUG-08:13 | 0.00 | 01-AUG-00:10 |
September | 0.313167E+11 | 0.747440E+10 | 346.18 | 0.175253E+11 | 0.137914E+11 | 0.00 | 1.00 | 01-SEP-07:02 | 0.00 | 01-SEP-00:05 | 55792.56 | 10-SEP-08:61 | 31335.94 | 09-SEP-07:01 | 30670.81 | 25-SEP-07:04 | 12044.98 | 09-SEP-07:01 | 0.00 | 01-SEP-00:05 |
October | 0.278563E+11 | 0.669445E+10 | 356.15 | 0.161834E+11 | 0.116729E+11 | 0.00 | 1.00 | 01-OCT-08:61 | 0.00 | 01-OCT-00:10 | 56085.16 | 30-OCT-07:05 | 37750.46 | 18-OCT-07:02 | 34245.58 | 30-OCT-07:05 | 11974.79 | 29-OCT-08:03 | 0.00 | 01-OCT-00:10 |
November | 0.202032E+11 | 0.487779E+10 | 336.02 | 0.117199E+11 | 0.848332E+10 | 0.00 | 1.00 | 01-NOV-07:03 | 0.00 | 01-NOV-00:10 | 56187.21 | 05-NOV-08:62 | 32886.30 | 21-NOV-08:62 | 33390.73 | 05-NOV-08:03 | 11787.19 | 21-NOV-08:62 | 0.00 | 01-NOV-00:10 |
December | 0.116211E+11 | 0.287605E+10 | 291.56 | 0.701973E+10 | 0.460134E+10 | 0.00 | 1.00 | 01-DEC-08:62 | 0.00 | 01-DEC-00:10 | 54750.00 | 10-DEC-09:02 | 32087.81 | 03-DEC-09:02 | 30121.09 | 24-DEC-09:03 | 11789.49 | 10-DEC-09:02 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.267066E+12 | 0.648514E+11 | 3984.62 | 0.155738E+12 | 0.111328E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.931719E+10 | 0.237164E+10 | 274.62 | 0.594674E+10 | 0.337045E+10 | 0.00 | 1.00 | 0.00 | 53252.25 | 28115.90 | 25381.64 | 11233.19 | 0.00 | |||||||
Maximum of Months | 0.338490E+11 | 0.815730E+10 | 369.01 | 0.190796E+11 | 0.150425E+11 | 0.00 | 1.00 | 0.00 | 56187.21 | 37750.46 | 34245.58 | 12288.15 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_7:7 COOLING COIL
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.478151E+10 | 0.119792E+10 | 271.71 | 0.305267E+10 | 0.172884E+10 | 0.00 | 1.00 | 01-JAN-09:03 | 0.00 | 01-JAN-00:05 | 26165.90 | 14-JAN-08:62 | 13915.16 | 14-JAN-08:62 | 12252.50 | 07-JAN-08:62 | 5424.21 | 14-JAN-08:62 | 0.00 | 01-JAN-00:05 |
February | 0.575950E+10 | 0.144377E+10 | 281.40 | 0.386475E+10 | 0.189475E+10 | 0.00 | 1.00 | 02-FEB-08:62 | 0.00 | 01-FEB-00:10 | 28327.48 | 11-FEB-08:62 | 15919.14 | 18-FEB-08:62 | 13862.61 | 11-FEB-08:62 | 5985.19 | 11-FEB-08:62 | 0.00 | 01-FEB-00:10 |
March | 0.690421E+10 | 0.170307E+10 | 314.06 | 0.433790E+10 | 0.256631E+10 | 0.00 | 1.00 | 04-MAR-08:62 | 0.00 | 01-MAR-00:05 | 28752.42 | 06-MAR-08:62 | 14189.01 | 14-MAR-07:03 | 15681.85 | 06-MAR-08:62 | 5991.86 | 05-MAR-09:02 | 0.00 | 01-MAR-00:05 |
April | 0.933891E+10 | 0.230087E+10 | 339.38 | 0.600533E+10 | 0.333358E+10 | 0.00 | 1.00 | 01-APR-07:03 | 0.00 | 01-APR-00:05 | 28280.16 | 13-APR-07:02 | 16443.82 | 17-APR-07:03 | 13254.91 | 13-APR-07:02 | 6056.17 | 12-APR-07:02 | 0.00 | 01-APR-00:05 |
May | 0.136518E+11 | 0.327777E+10 | 363.23 | 0.809038E+10 | 0.556139E+10 | 0.00 | 1.00 | 02-MAY-07:03 | 0.00 | 01-MAY-00:10 | 29361.34 | 29-MAY-08:62 | 18284.97 | 09-MAY-07:02 | 17547.69 | 29-MAY-08:04 | 6171.86 | 14-MAY-08:03 | 0.00 | 01-MAY-00:10 |
June | 0.157885E+11 | 0.370312E+10 | 356.08 | 0.869990E+10 | 0.708860E+10 | 0.00 | 1.00 | 01-JUN-07:02 | 0.00 | 01-JUN-00:10 | 29323.83 | 26-JUN-07:02 | 16403.62 | 17-JUN-07:02 | 16668.68 | 19-JUN-07:02 | 6249.27 | 11-JUN-08:04 | 0.00 | 01-JUN-00:10 |
July | 0.175628E+11 | 0.416947E+10 | 356.70 | 0.990949E+10 | 0.765331E+10 | 0.00 | 1.00 | 01-JUL-07:02 | 0.00 | 01-JUL-00:05 | 29398.00 | 10-JUL-07:01 | 16912.86 | 07-JUL-07:02 | 16435.67 | 31-JUL-07:03 | 6327.35 | 23-JUL-08:04 | 0.00 | 01-JUL-00:05 |
August | 0.173077E+11 | 0.407798E+10 | 369.20 | 0.951982E+10 | 0.778786E+10 | 0.00 | 1.00 | 01-AUG-07:01 | 0.00 | 01-AUG-00:10 | 29428.96 | 28-AUG-07:02 | 17095.54 | 08-AUG-07:02 | 17186.97 | 28-AUG-07:03 | 6306.37 | 20-AUG-08:13 | 0.00 | 01-AUG-00:10 |
September | 0.162359E+11 | 0.381668E+10 | 347.53 | 0.909685E+10 | 0.713908E+10 | 0.00 | 1.00 | 01-SEP-07:02 | 0.00 | 01-SEP-00:05 | 29251.82 | 18-SEP-07:01 | 16452.62 | 09-SEP-07:01 | 16123.28 | 25-SEP-07:04 | 6201.70 | 09-SEP-07:01 | 0.00 | 01-SEP-00:05 |
October | 0.144463E+11 | 0.341869E+10 | 357.54 | 0.840264E+10 | 0.604371E+10 | 0.00 | 1.00 | 01-OCT-08:61 | 0.00 | 01-OCT-00:10 | 29393.78 | 30-OCT-07:05 | 19800.10 | 18-OCT-07:02 | 17992.72 | 30-OCT-07:05 | 6165.81 | 29-OCT-08:03 | 0.00 | 01-OCT-00:10 |
November | 0.104484E+11 | 0.248403E+10 | 336.92 | 0.606905E+10 | 0.437936E+10 | 0.00 | 1.00 | 01-NOV-07:03 | 0.00 | 01-NOV-00:10 | 29447.26 | 05-NOV-08:62 | 17261.40 | 21-NOV-08:62 | 17541.70 | 05-NOV-08:03 | 6068.57 | 21-NOV-08:62 | 0.00 | 01-NOV-00:10 |
December | 0.597540E+10 | 0.145564E+10 | 290.85 | 0.361105E+10 | 0.236435E+10 | 0.00 | 1.00 | 01-DEC-08:62 | 0.00 | 01-DEC-00:10 | 28705.25 | 10-DEC-09:02 | 16590.69 | 01-DEC-08:62 | 14753.38 | 11-DEC-08:62 | 6070.41 | 10-DEC-09:02 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.138201E+12 | 0.330490E+11 | 3984.60 | 0.806598E+11 | 0.575411E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.478151E+10 | 0.119792E+10 | 271.71 | 0.305267E+10 | 0.172884E+10 | 0.00 | 1.00 | 0.00 | 26165.90 | 13915.16 | 12252.50 | 5424.21 | 0.00 | |||||||
Maximum of Months | 0.175628E+11 | 0.416947E+10 | 369.20 | 0.990949E+10 | 0.778786E+10 | 0.00 | 1.00 | 0.00 | 29447.26 | 19800.10 | 17992.72 | 6327.35 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_8:8 COOLING COIL
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.471265E+10 | 0.118104E+10 | 268.62 | 0.300278E+10 | 0.170987E+10 | 0.00 | 1.00 | 01-JAN-09:03 | 0.00 | 01-JAN-00:05 | 25413.54 | 14-JAN-08:62 | 13467.23 | 14-JAN-08:62 | 11958.78 | 07-JAN-08:62 | 5268.93 | 14-JAN-08:62 | 0.00 | 01-JAN-00:05 |
February | 0.568991E+10 | 0.142688E+10 | 280.65 | 0.381385E+10 | 0.187605E+10 | 0.00 | 1.00 | 02-FEB-08:62 | 0.00 | 01-FEB-00:10 | 28210.39 | 11-FEB-08:62 | 15824.73 | 18-FEB-08:62 | 13841.28 | 11-FEB-08:62 | 5960.27 | 11-FEB-08:62 | 0.00 | 01-FEB-00:10 |
March | 0.683314E+10 | 0.168592E+10 | 312.89 | 0.428687E+10 | 0.254627E+10 | 0.00 | 1.00 | 04-MAR-08:62 | 0.00 | 01-MAR-00:05 | 28629.96 | 06-MAR-08:62 | 14095.57 | 14-MAR-07:03 | 15634.87 | 06-MAR-08:62 | 5966.87 | 05-MAR-09:02 | 0.00 | 01-MAR-00:05 |
April | 0.927380E+10 | 0.228509E+10 | 339.04 | 0.595836E+10 | 0.331543E+10 | 0.00 | 1.00 | 01-APR-07:03 | 0.00 | 01-APR-00:05 | 28163.21 | 13-APR-07:02 | 16360.27 | 17-APR-07:03 | 13231.01 | 13-APR-07:02 | 6030.96 | 12-APR-07:02 | 0.00 | 01-APR-00:05 |
May | 0.135860E+11 | 0.326172E+10 | 363.29 | 0.804482E+10 | 0.554121E+10 | 0.00 | 1.00 | 02-MAY-07:03 | 0.00 | 01-MAY-00:10 | 29238.93 | 29-MAY-08:62 | 18186.19 | 09-MAY-07:02 | 17492.16 | 29-MAY-08:04 | 6146.13 | 14-MAY-08:03 | 0.00 | 01-MAY-00:10 |
June | 0.157283E+11 | 0.368823E+10 | 356.08 | 0.865856E+10 | 0.706974E+10 | 0.00 | 1.00 | 01-JUN-07:02 | 0.00 | 01-JUN-00:10 | 29202.05 | 26-JUN-07:02 | 16313.55 | 17-JUN-07:02 | 16612.36 | 19-JUN-07:02 | 6223.19 | 11-JUN-08:04 | 0.00 | 01-JUN-00:10 |
July | 0.175056E+11 | 0.415485E+10 | 356.74 | 0.986935E+10 | 0.763623E+10 | 0.00 | 1.00 | 01-JUL-07:02 | 0.00 | 01-JUL-00:05 | 29275.44 | 10-JUL-07:01 | 16816.37 | 07-JUL-07:02 | 16374.45 | 31-JUL-07:03 | 6300.95 | 23-JUL-08:04 | 0.00 | 01-JUL-00:05 |
August | 0.172461E+11 | 0.406253E+10 | 369.14 | 0.947747E+10 | 0.776859E+10 | 0.00 | 1.00 | 01-AUG-07:01 | 0.00 | 01-AUG-00:10 | 29306.26 | 28-AUG-07:02 | 16995.25 | 08-AUG-07:02 | 17129.76 | 28-AUG-07:03 | 6280.00 | 20-AUG-08:13 | 0.00 | 01-AUG-00:10 |
September | 0.161802E+11 | 0.380274E+10 | 347.37 | 0.905802E+10 | 0.712223E+10 | 0.00 | 1.00 | 01-SEP-07:02 | 0.00 | 01-SEP-00:05 | 29130.26 | 18-SEP-07:01 | 16359.18 | 09-SEP-07:01 | 16065.61 | 25-SEP-07:04 | 6175.88 | 09-SEP-07:01 | 0.00 | 01-SEP-00:05 |
October | 0.143841E+11 | 0.340346E+10 | 357.53 | 0.835883E+10 | 0.602528E+10 | 0.00 | 1.00 | 01-OCT-08:61 | 0.00 | 01-OCT-00:10 | 29271.23 | 30-OCT-07:03 | 19698.85 | 18-OCT-07:02 | 17929.32 | 30-OCT-07:05 | 6140.09 | 29-OCT-08:03 | 0.00 | 01-OCT-00:10 |
November | 0.103792E+11 | 0.246752E+10 | 336.50 | 0.602052E+10 | 0.435872E+10 | 0.00 | 1.00 | 01-NOV-07:03 | 0.00 | 01-NOV-00:10 | 29324.49 | 05-NOV-08:62 | 17165.73 | 21-NOV-08:62 | 17484.82 | 05-NOV-08:03 | 6043.27 | 21-NOV-08:62 | 0.00 | 01-NOV-00:10 |
December | 0.589790E+10 | 0.143683E+10 | 288.98 | 0.355730E+10 | 0.234060E+10 | 0.00 | 1.00 | 01-DEC-08:62 | 0.00 | 01-DEC-00:10 | 28584.36 | 10-DEC-09:02 | 16491.03 | 01-DEC-08:62 | 14710.38 | 11-DEC-08:62 | 6045.11 | 10-DEC-09:02 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.137417E+12 | 0.328568E+11 | 3976.84 | 0.801067E+11 | 0.573102E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.471265E+10 | 0.118104E+10 | 268.62 | 0.300278E+10 | 0.170987E+10 | 0.00 | 1.00 | 0.00 | 25413.54 | 13467.23 | 11958.78 | 5268.93 | 0.00 | |||||||
Maximum of Months | 0.175056E+11 | 0.415485E+10 | 369.14 | 0.986935E+10 | 0.776859E+10 | 0.00 | 1.00 | 0.00 | 29324.49 | 19698.85 | 17929.32 | 6300.95 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_9:9 COOLING COIL
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.458057E+10 | 0.114989E+10 | 264.21 | 0.290834E+10 | 0.167223E+10 | 0.00 | 1.00 | 01-JAN-09:03 | 0.00 | 01-JAN-00:05 | 23217.52 | 14-JAN-08:62 | 12176.76 | 14-JAN-08:62 | 11040.76 | 14-JAN-08:62 | 4816.14 | 14-JAN-08:62 | 0.00 | 01-JAN-00:05 |
February | 0.556621E+10 | 0.139847E+10 | 277.89 | 0.372471E+10 | 0.184151E+10 | 0.00 | 1.00 | 11-FEB-08:62 | 0.00 | 01-FEB-00:10 | 27825.77 | 18-FEB-08:62 | 15816.70 | 18-FEB-08:62 | 13047.52 | 11-FEB-08:62 | 5897.68 | 18-FEB-08:62 | 0.00 | 01-FEB-00:10 |
March | 0.672635E+10 | 0.166201E+10 | 310.06 | 0.421226E+10 | 0.251409E+10 | 0.00 | 1.00 | 04-MAR-08:62 | 0.00 | 01-MAR-00:05 | 28739.87 | 06-MAR-08:62 | 13396.73 | 05-MAR-09:02 | 15766.97 | 06-MAR-08:62 | 5992.28 | 05-MAR-09:02 | 0.00 | 01-MAR-00:05 |
April | 0.921382E+10 | 0.227260E+10 | 338.59 | 0.591708E+10 | 0.329674E+10 | 0.00 | 1.00 | 01-APR-07:03 | 0.00 | 01-APR-00:05 | 28274.26 | 13-APR-07:02 | 16399.51 | 17-APR-07:03 | 13343.60 | 13-APR-07:02 | 6056.37 | 12-APR-07:02 | 0.00 | 01-APR-00:05 |
May | 0.135792E+11 | 0.326230E+10 | 363.05 | 0.804299E+10 | 0.553622E+10 | 0.00 | 1.00 | 02-MAY-07:03 | 0.00 | 01-MAY-00:10 | 29363.77 | 29-MAY-08:62 | 18207.16 | 09-MAY-07:02 | 17623.73 | 29-MAY-08:04 | 6172.53 | 14-MAY-08:03 | 0.00 | 01-MAY-00:10 |
June | 0.157717E+11 | 0.369966E+10 | 356.17 | 0.869008E+10 | 0.708162E+10 | 0.00 | 1.00 | 01-JUN-07:02 | 0.00 | 01-JUN-00:10 | 29319.17 | 26-JUN-07:02 | 16346.91 | 17-JUN-07:02 | 16725.75 | 19-JUN-07:02 | 6249.91 | 11-JUN-08:04 | 0.00 | 01-JUN-00:10 |
July | 0.175810E+11 | 0.417377E+10 | 356.57 | 0.992411E+10 | 0.765689E+10 | 0.00 | 1.00 | 01-JUL-07:02 | 0.00 | 01-JUL-00:05 | 29400.38 | 10-JUL-07:01 | 16866.89 | 07-JUL-07:02 | 16443.12 | 31-JUL-07:03 | 6325.30 | 23-JUL-08:03 | 0.00 | 01-JUL-00:05 |
August | 0.172977E+11 | 0.407628E+10 | 369.07 | 0.951608E+10 | 0.778165E+10 | 0.00 | 1.00 | 01-AUG-07:01 | 0.00 | 01-AUG-00:10 | 29431.39 | 28-AUG-07:02 | 17045.88 | 08-AUG-07:02 | 17228.75 | 28-AUG-07:03 | 6306.87 | 20-AUG-08:13 | 0.00 | 01-AUG-00:10 |
September | 0.162525E+11 | 0.382071E+10 | 347.84 | 0.910945E+10 | 0.714302E+10 | 0.00 | 1.00 | 01-SEP-07:02 | 0.00 | 01-SEP-00:05 | 29252.91 | 18-SEP-07:01 | 16440.89 | 09-SEP-07:01 | 16122.59 | 25-SEP-07:04 | 6202.18 | 09-SEP-07:01 | 0.00 | 01-SEP-00:05 |
October | 0.143984E+11 | 0.340848E+10 | 357.41 | 0.837040E+10 | 0.602804E+10 | 0.00 | 1.00 | 01-OCT-08:61 | 0.00 | 01-OCT-00:10 | 29396.21 | 30-OCT-07:02 | 19739.83 | 18-OCT-07:02 | 18037.79 | 30-OCT-07:05 | 6166.61 | 29-OCT-08:03 | 0.00 | 01-OCT-00:10 |
November | 0.103105E+11 | 0.245341E+10 | 335.78 | 0.597296E+10 | 0.433757E+10 | 0.00 | 1.00 | 01-NOV-07:03 | 0.00 | 01-NOV-00:10 | 29449.70 | 05-NOV-08:62 | 17186.85 | 21-NOV-08:62 | 17595.25 | 05-NOV-08:62 | 6068.67 | 21-NOV-08:62 | 0.00 | 01-NOV-00:10 |
December | 0.575729E+10 | 0.140390E+10 | 283.11 | 0.346117E+10 | 0.229612E+10 | 0.00 | 1.00 | 01-DEC-08:62 | 0.00 | 01-DEC-00:10 | 28696.09 | 10-DEC-09:02 | 16494.16 | 01-DEC-08:62 | 14815.96 | 11-DEC-08:62 | 6070.97 | 10-DEC-09:02 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.137035E+12 | 0.327815E+11 | 3959.76 | 0.798496E+11 | 0.571857E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.458057E+10 | 0.114989E+10 | 264.21 | 0.290834E+10 | 0.167223E+10 | 0.00 | 1.00 | 0.00 | 23217.52 | 12176.76 | 11040.76 | 4816.14 | 0.00 | |||||||
Maximum of Months | 0.175810E+11 | 0.417377E+10 | 369.07 | 0.992411E+10 | 0.778165E+10 | 0.00 | 1.00 | 0.00 | 29449.70 | 19739.83 | 18037.79 | 6325.30 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_10:10 COOLING COIL
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.508387E+10 | 0.128790E+10 | 267.24 | 0.328324E+10 | 0.180063E+10 | 0.00 | 1.00 | 07-JAN-08:62 | 0.00 | 01-JAN-00:05 | 20138.80 | 14-JAN-08:62 | 9667.68 | 14-JAN-08:62 | 10471.13 | 14-JAN-08:62 | 4159.33 | 14-JAN-08:62 | 0.00 | 01-JAN-00:05 |
February | 0.620300E+10 | 0.157347E+10 | 278.77 | 0.420749E+10 | 0.199551E+10 | 0.00 | 1.00 | 11-FEB-08:62 | 0.00 | 01-FEB-00:10 | 30977.62 | 18-FEB-08:62 | 16525.71 | 18-FEB-08:62 | 14451.91 | 18-FEB-08:62 | 6527.84 | 18-FEB-08:62 | 0.00 | 01-FEB-00:10 |
March | 0.760703E+10 | 0.189744E+10 | 314.46 | 0.485064E+10 | 0.275639E+10 | 0.00 | 1.00 | 05-MAR-09:02 | 0.00 | 01-MAR-00:05 | 31378.30 | 05-MAR-09:02 | 13930.43 | 05-MAR-09:02 | 17447.87 | 05-MAR-09:02 | 6517.43 | 05-MAR-09:02 | 0.00 | 01-MAR-00:05 |
April | 0.105733E+11 | 0.262594E+10 | 339.26 | 0.691880E+10 | 0.365446E+10 | 0.00 | 1.00 | 12-APR-07:02 | 0.00 | 01-APR-00:05 | 33859.89 | 13-APR-07:02 | 17428.21 | 16-APR-08:62 | 17735.08 | 13-APR-07:02 | 7160.53 | 12-APR-07:02 | 0.00 | 01-APR-00:05 |
May | 0.155325E+11 | 0.376679E+10 | 363.08 | 0.941218E+10 | 0.612032E+10 | 0.00 | 1.00 | 03-MAY-07:02 | 0.00 | 01-MAY-00:10 | 34668.07 | 29-MAY-08:62 | 20770.70 | 09-MAY-07:02 | 21344.54 | 29-MAY-08:04 | 7280.26 | 14-MAY-08:03 | 0.00 | 01-MAY-00:10 |
June | 0.180312E+11 | 0.427040E+10 | 356.59 | 0.102219E+11 | 0.780933E+10 | 0.00 | 1.00 | 01-JUN-07:02 | 0.00 | 01-JUN-00:10 | 34696.83 | 26-JUN-07:02 | 18328.79 | 17-JUN-07:02 | 19911.88 | 26-JUN-07:03 | 7373.12 | 11-JUN-08:04 | 0.00 | 01-JUN-00:10 |
July | 0.201540E+11 | 0.483237E+10 | 356.70 | 0.117280E+11 | 0.842599E+10 | 0.00 | 1.00 | 01-JUL-07:02 | 0.00 | 01-JUL-00:05 | 34711.36 | 10-JUL-07:01 | 19201.92 | 06-JUL-07:02 | 19866.30 | 31-JUL-07:03 | 7469.36 | 23-JUL-08:04 | 0.00 | 01-JUL-00:05 |
August | 0.196062E+11 | 0.467048E+10 | 369.24 | 0.111044E+11 | 0.850175E+10 | 0.00 | 1.00 | 01-AUG-07:01 | 0.00 | 01-AUG-00:10 | 34747.91 | 28-AUG-07:02 | 20050.84 | 08-AUG-07:02 | 20584.21 | 13-AUG-08:62 | 7437.95 | 20-AUG-08:13 | 0.00 | 01-AUG-00:10 |
September | 0.186081E+11 | 0.441332E+10 | 348.16 | 0.107368E+11 | 0.787124E+10 | 0.00 | 1.00 | 01-SEP-07:02 | 0.00 | 01-SEP-00:05 | 34656.54 | 24-SEP-08:61 | 18671.53 | 14-SEP-07:02 | 19161.39 | 25-SEP-07:04 | 7323.65 | 09-SEP-07:03 | 0.00 | 01-SEP-00:05 |
October | 0.162754E+11 | 0.389107E+10 | 356.97 | 0.968999E+10 | 0.658542E+10 | 0.00 | 1.00 | 01-OCT-08:61 | 0.00 | 01-OCT-00:10 | 34721.62 | 03-OCT-07:02 | 22555.32 | 18-OCT-07:02 | 21867.39 | 30-OCT-07:05 | 7273.17 | 29-OCT-08:03 | 0.00 | 01-OCT-00:10 |
November | 0.114828E+11 | 0.276832E+10 | 335.26 | 0.679490E+10 | 0.468791E+10 | 0.00 | 1.00 | 03-NOV-07:02 | 0.00 | 01-NOV-00:10 | 34769.52 | 05-NOV-08:03 | 19150.76 | 21-NOV-08:62 | 21260.32 | 05-NOV-08:03 | 7182.40 | 21-NOV-08:62 | 0.00 | 01-NOV-00:10 |
December | 0.626653E+10 | 0.154604E+10 | 277.53 | 0.382316E+10 | 0.244337E+10 | 0.00 | 1.00 | 01-DEC-08:62 | 0.00 | 01-DEC-00:10 | 34019.23 | 10-DEC-09:02 | 19471.08 | 01-DEC-08:62 | 18101.25 | 10-DEC-09:02 | 7166.52 | 10-DEC-09:02 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.155424E+12 | 0.375435E+11 | 3963.26 | 0.927715E+11 | 0.626523E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.508387E+10 | 0.128790E+10 | 267.24 | 0.328324E+10 | 0.180063E+10 | 0.00 | 1.00 | 0.00 | 20138.80 | 9667.68 | 10471.13 | 4159.33 | 0.00 | |||||||
Maximum of Months | 0.201540E+11 | 0.483237E+10 | 369.24 | 0.117280E+11 | 0.850175E+10 | 0.00 | 1.00 | 0.00 | 34769.52 | 22555.32 | 21867.39 | 7469.36 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.67 | 43.96 | 23.71 | 112.42 | 33.67 | 0.00 | 0.00 | 0.00 |
February | 61.22 | 35.42 | 25.80 | 107.48 | 27.93 | 0.00 | 0.00 | 0.00 |
March | 47.00 | 19.87 | 27.13 | 83.80 | 23.14 | 0.00 | 0.00 | 0.00 |
April | 31.96 | 5.60 | 26.36 | 62.58 | 15.51 | 0.00 | 0.00 | 0.00 |
May | 25.61 | 0.55 | 25.06 | 54.53 | 7.17 | 0.00 | 0.00 | 0.00 |
June | 24.42 | 0.05 | 24.37 | 56.09 | 3.28 | 0.00 | 0.00 | 0.00 |
July | 26.15 | 0.24 | 25.90 | 62.94 | 4.67 | 0.00 | 0.00 | 0.00 |
August | 29.67 | 2.50 | 27.17 | 67.65 | 3.37 | 0.00 | 0.00 | 0.00 |
September | 37.99 | 9.31 | 28.68 | 87.02 | 5.90 | 0.00 | 0.00 | 0.00 |
October | 52.24 | 24.51 | 27.73 | 105.99 | 9.23 | 0.00 | 0.00 | 0.00 |
November | 59.44 | 33.17 | 26.26 | 108.35 | 17.29 | 0.00 | 0.00 | 0.00 |
December | 65.22 | 41.14 | 24.08 | 110.68 | 29.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 43.97 | 17.95 | 26.02 | 84.85 | 14.99 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 24.42 | 0.05 | 23.71 | 54.53 | 3.28 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 67.67 | 43.96 | 28.68 | 112.42 | 33.67 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.67 | 43.96 | 23.71 | 112.42 | 33.67 | 0.00 | 0.00 | 0.00 |
February | 61.22 | 35.42 | 25.80 | 107.48 | 27.93 | 0.00 | 0.00 | 0.00 |
March | 47.00 | 19.87 | 27.13 | 83.80 | 23.14 | 0.00 | 0.00 | 0.00 |
April | 31.96 | 5.60 | 26.36 | 62.58 | 15.51 | 0.00 | 0.00 | 0.00 |
May | 25.61 | 0.55 | 25.06 | 54.53 | 7.17 | 0.00 | 0.00 | 0.00 |
June | 24.42 | 0.05 | 24.37 | 56.09 | 3.28 | 0.00 | 0.00 | 0.00 |
July | 26.15 | 0.24 | 25.90 | 62.94 | 4.67 | 0.00 | 0.00 | 0.00 |
August | 29.67 | 2.50 | 27.17 | 67.65 | 3.37 | 0.00 | 0.00 | 0.00 |
September | 37.99 | 9.31 | 28.68 | 87.02 | 5.90 | 0.00 | 0.00 | 0.00 |
October | 52.24 | 24.51 | 27.73 | 105.99 | 9.23 | 0.00 | 0.00 | 0.00 |
November | 59.44 | 33.17 | 26.26 | 108.35 | 17.29 | 0.00 | 0.00 | 0.00 |
December | 65.22 | 41.14 | 24.08 | 110.68 | 29.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 43.97 | 17.95 | 26.02 | 84.85 | 14.99 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 24.42 | 0.05 | 23.71 | 54.53 | 3.28 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 67.67 | 43.96 | 28.68 | 112.42 | 33.67 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.67 | 43.96 | 23.71 | 112.42 | 33.67 | 0.00 | 0.00 | 0.00 |
February | 61.22 | 35.42 | 25.80 | 107.48 | 27.93 | 0.00 | 0.00 | 0.00 |
March | 47.00 | 19.87 | 27.13 | 83.80 | 23.14 | 0.00 | 0.00 | 0.00 |
April | 31.96 | 5.60 | 26.36 | 62.58 | 15.51 | 0.00 | 0.00 | 0.00 |
May | 25.61 | 0.55 | 25.06 | 54.53 | 7.17 | 0.00 | 0.00 | 0.00 |
June | 24.42 | 0.05 | 24.37 | 56.09 | 3.28 | 0.00 | 0.00 | 0.00 |
July | 26.15 | 0.24 | 25.90 | 62.94 | 4.67 | 0.00 | 0.00 | 0.00 |
August | 29.67 | 2.50 | 27.17 | 67.65 | 3.37 | 0.00 | 0.00 | 0.00 |
September | 37.99 | 9.31 | 28.68 | 87.02 | 5.90 | 0.00 | 0.00 | 0.00 |
October | 52.24 | 24.51 | 27.73 | 105.99 | 9.23 | 0.00 | 0.00 | 0.00 |
November | 59.44 | 33.17 | 26.26 | 108.35 | 17.29 | 0.00 | 0.00 | 0.00 |
December | 65.22 | 41.14 | 24.08 | 110.68 | 29.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 43.97 | 17.95 | 26.02 | 84.85 | 14.99 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 24.42 | 0.05 | 23.71 | 54.53 | 3.28 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 67.67 | 43.96 | 28.68 | 112.42 | 33.67 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.67 | 43.96 | 23.71 | 112.42 | 33.67 | 0.00 | 0.00 | 0.00 |
February | 61.22 | 35.42 | 25.80 | 107.48 | 27.93 | 0.00 | 0.00 | 0.00 |
March | 47.00 | 19.87 | 27.13 | 83.80 | 23.14 | 0.00 | 0.00 | 0.00 |
April | 31.96 | 5.60 | 26.36 | 62.58 | 15.51 | 0.00 | 0.00 | 0.00 |
May | 25.61 | 0.55 | 25.06 | 54.53 | 7.17 | 0.00 | 0.00 | 0.00 |
June | 24.42 | 0.05 | 24.37 | 56.09 | 3.28 | 0.00 | 0.00 | 0.00 |
July | 26.15 | 0.24 | 25.90 | 62.94 | 4.67 | 0.00 | 0.00 | 0.00 |
August | 29.67 | 2.50 | 27.17 | 67.65 | 3.37 | 0.00 | 0.00 | 0.00 |
September | 37.99 | 9.31 | 28.68 | 87.02 | 5.90 | 0.00 | 0.00 | 0.00 |
October | 52.24 | 24.51 | 27.73 | 105.99 | 9.23 | 0.00 | 0.00 | 0.00 |
November | 59.44 | 33.17 | 26.26 | 108.35 | 17.29 | 0.00 | 0.00 | 0.00 |
December | 65.22 | 41.14 | 24.08 | 110.68 | 29.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 43.97 | 17.95 | 26.02 | 84.85 | 14.99 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 24.42 | 0.05 | 23.71 | 54.53 | 3.28 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 67.67 | 43.96 | 28.68 | 112.42 | 33.67 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 81.35 | 52.85 | 28.50 | 135.19 | 40.17 | 0.00 | 0.00 | 0.00 |
February | 73.59 | 42.58 | 31.01 | 129.27 | 33.35 | 0.00 | 0.00 | 0.00 |
March | 56.50 | 23.89 | 32.61 | 100.83 | 27.68 | 0.00 | 0.00 | 0.00 |
April | 38.42 | 6.74 | 31.68 | 75.12 | 18.62 | 0.00 | 0.00 | 0.00 |
May | 30.79 | 0.67 | 30.12 | 65.24 | 8.72 | 0.00 | 0.00 | 0.00 |
June | 29.35 | 0.06 | 29.30 | 66.93 | 3.97 | 0.00 | 0.00 | 0.00 |
July | 31.43 | 0.29 | 31.14 | 75.14 | 5.66 | 0.00 | 0.00 | 0.00 |
August | 35.67 | 3.01 | 32.66 | 80.82 | 4.08 | 0.00 | 0.00 | 0.00 |
September | 45.67 | 11.19 | 34.48 | 104.14 | 7.11 | 0.00 | 0.00 | 0.00 |
October | 62.80 | 29.46 | 33.34 | 127.10 | 11.16 | 0.00 | 0.00 | 0.00 |
November | 71.45 | 39.88 | 31.57 | 130.17 | 20.74 | 0.00 | 0.00 | 0.00 |
December | 78.40 | 49.45 | 28.95 | 133.11 | 34.99 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 52.86 | 21.58 | 31.28 | 101.78 | 17.96 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 29.35 | 0.06 | 28.50 | 65.24 | 3.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 81.35 | 52.85 | 34.48 | 135.19 | 40.17 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 81.35 | 52.85 | 28.50 | 135.19 | 40.17 | 0.00 | 0.00 | 0.00 |
February | 73.59 | 42.58 | 31.01 | 129.27 | 33.35 | 0.00 | 0.00 | 0.00 |
March | 56.50 | 23.89 | 32.61 | 100.83 | 27.68 | 0.00 | 0.00 | 0.00 |
April | 38.42 | 6.74 | 31.68 | 75.12 | 18.62 | 0.00 | 0.00 | 0.00 |
May | 30.79 | 0.67 | 30.12 | 65.24 | 8.72 | 0.00 | 0.00 | 0.00 |
June | 29.35 | 0.06 | 29.30 | 66.93 | 3.97 | 0.00 | 0.00 | 0.00 |
July | 31.43 | 0.29 | 31.14 | 75.14 | 5.66 | 0.00 | 0.00 | 0.00 |
August | 35.67 | 3.01 | 32.66 | 80.82 | 4.08 | 0.00 | 0.00 | 0.00 |
September | 45.67 | 11.19 | 34.48 | 104.14 | 7.11 | 0.00 | 0.00 | 0.00 |
October | 62.80 | 29.46 | 33.34 | 127.10 | 11.16 | 0.00 | 0.00 | 0.00 |
November | 71.45 | 39.88 | 31.57 | 130.17 | 20.74 | 0.00 | 0.00 | 0.00 |
December | 78.40 | 49.45 | 28.95 | 133.11 | 34.99 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 52.86 | 21.58 | 31.28 | 101.78 | 17.96 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 29.35 | 0.06 | 28.50 | 65.24 | 3.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 81.35 | 52.85 | 34.48 | 135.19 | 40.17 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.67 | 43.96 | 23.71 | 111.84 | 34.48 | 0.00 | 0.00 | 0.00 |
February | 61.22 | 35.42 | 25.80 | 106.99 | 28.67 | 0.00 | 0.00 | 0.00 |
March | 47.00 | 19.87 | 27.13 | 83.46 | 23.63 | 0.00 | 0.00 | 0.00 |
April | 31.96 | 5.60 | 26.36 | 62.70 | 15.61 | 0.00 | 0.00 | 0.00 |
May | 25.61 | 0.55 | 25.06 | 55.03 | 7.09 | 0.00 | 0.00 | 0.00 |
June | 24.42 | 0.05 | 24.37 | 56.82 | 3.27 | 0.00 | 0.00 | 0.00 |
July | 26.15 | 0.24 | 25.90 | 63.77 | 4.57 | 0.00 | 0.00 | 0.00 |
August | 29.67 | 2.50 | 27.17 | 68.46 | 3.25 | 0.00 | 0.00 | 0.00 |
September | 37.99 | 9.31 | 28.68 | 87.74 | 5.82 | 0.00 | 0.00 | 0.00 |
October | 52.24 | 24.51 | 27.73 | 106.32 | 9.08 | 0.00 | 0.00 | 0.00 |
November | 59.44 | 33.17 | 26.26 | 108.27 | 17.43 | 0.00 | 0.00 | 0.00 |
December | 65.22 | 41.14 | 24.08 | 110.25 | 30.03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 43.97 | 17.95 | 26.02 | 85.03 | 15.19 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 24.42 | 0.05 | 23.71 | 55.03 | 3.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 67.67 | 43.96 | 28.68 | 111.84 | 34.48 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.67 | 43.96 | 23.71 | 111.84 | 34.48 | 0.00 | 0.00 | 0.00 |
February | 61.22 | 35.42 | 25.80 | 106.99 | 28.67 | 0.00 | 0.00 | 0.00 |
March | 47.00 | 19.87 | 27.13 | 83.46 | 23.63 | 0.00 | 0.00 | 0.00 |
April | 31.96 | 5.60 | 26.36 | 62.70 | 15.61 | 0.00 | 0.00 | 0.00 |
May | 25.61 | 0.55 | 25.06 | 55.03 | 7.09 | 0.00 | 0.00 | 0.00 |
June | 24.42 | 0.05 | 24.37 | 56.82 | 3.27 | 0.00 | 0.00 | 0.00 |
July | 26.15 | 0.24 | 25.90 | 63.77 | 4.57 | 0.00 | 0.00 | 0.00 |
August | 29.67 | 2.50 | 27.17 | 68.46 | 3.25 | 0.00 | 0.00 | 0.00 |
September | 37.99 | 9.31 | 28.68 | 87.74 | 5.82 | 0.00 | 0.00 | 0.00 |
October | 52.24 | 24.51 | 27.73 | 106.32 | 9.08 | 0.00 | 0.00 | 0.00 |
November | 59.44 | 33.17 | 26.26 | 108.27 | 17.43 | 0.00 | 0.00 | 0.00 |
December | 65.22 | 41.14 | 24.08 | 110.25 | 30.03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 43.97 | 17.95 | 26.02 | 85.03 | 15.19 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 24.42 | 0.05 | 23.71 | 55.03 | 3.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 67.67 | 43.96 | 28.68 | 111.84 | 34.48 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 81.35 | 52.85 | 28.50 | 134.53 | 41.13 | 0.00 | 0.00 | 0.00 |
February | 73.59 | 42.58 | 31.01 | 128.74 | 34.21 | 0.00 | 0.00 | 0.00 |
March | 56.50 | 23.89 | 32.61 | 100.47 | 28.25 | 0.00 | 0.00 | 0.00 |
April | 38.42 | 6.74 | 31.68 | 75.29 | 18.73 | 0.00 | 0.00 | 0.00 |
May | 30.79 | 0.67 | 30.12 | 65.83 | 8.62 | 0.00 | 0.00 | 0.00 |
June | 29.35 | 0.06 | 29.30 | 67.80 | 3.96 | 0.00 | 0.00 | 0.00 |
July | 31.43 | 0.29 | 31.14 | 76.13 | 5.54 | 0.00 | 0.00 | 0.00 |
August | 35.67 | 3.01 | 32.66 | 81.79 | 3.94 | 0.00 | 0.00 | 0.00 |
September | 45.67 | 11.19 | 34.48 | 105.02 | 7.02 | 0.00 | 0.00 | 0.00 |
October | 62.80 | 29.46 | 33.34 | 127.52 | 10.99 | 0.00 | 0.00 | 0.00 |
November | 71.45 | 39.88 | 31.57 | 130.11 | 20.91 | 0.00 | 0.00 | 0.00 |
December | 78.40 | 49.45 | 28.95 | 132.64 | 35.81 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 52.86 | 21.58 | 31.28 | 102.02 | 18.19 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 29.35 | 0.06 | 28.50 | 65.83 | 3.94 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 81.35 | 52.85 | 34.48 | 134.53 | 41.13 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.67 | 43.96 | 23.71 | 111.95 | 35.24 | 0.00 | 0.00 | 0.00 |
February | 61.22 | 35.42 | 25.80 | 107.08 | 29.59 | 0.00 | 0.00 | 0.00 |
March | 47.00 | 19.87 | 27.13 | 83.42 | 24.62 | 0.00 | 0.00 | 0.00 |
April | 31.96 | 5.60 | 26.36 | 62.42 | 17.14 | 0.00 | 0.00 | 0.00 |
May | 25.61 | 0.55 | 25.06 | 54.57 | 8.83 | 0.00 | 0.00 | 0.00 |
June | 24.42 | 0.05 | 24.37 | 55.12 | 4.28 | 0.00 | 0.00 | 0.00 |
July | 26.15 | 0.24 | 25.90 | 62.33 | 6.15 | 0.00 | 0.00 | 0.00 |
August | 29.67 | 2.50 | 27.17 | 67.17 | 4.57 | 0.00 | 0.00 | 0.00 |
September | 37.99 | 9.31 | 28.68 | 85.97 | 7.05 | 0.00 | 0.00 | 0.00 |
October | 52.24 | 24.51 | 27.73 | 105.91 | 11.15 | 0.00 | 0.00 | 0.00 |
November | 59.44 | 33.17 | 26.26 | 108.21 | 19.01 | 0.00 | 0.00 | 0.00 |
December | 65.22 | 41.14 | 24.08 | 110.31 | 31.04 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 43.97 | 17.95 | 26.02 | 84.43 | 16.50 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 24.42 | 0.05 | 23.71 | 54.57 | 4.28 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 67.67 | 43.96 | 28.68 | 111.95 | 35.24 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.67 | 43.96 | 23.71 | 111.95 | 35.24 | 0.00 | 0.00 | 0.00 |
February | 61.22 | 35.42 | 25.80 | 107.08 | 29.59 | 0.00 | 0.00 | 0.00 |
March | 47.00 | 19.87 | 27.13 | 83.42 | 24.62 | 0.00 | 0.00 | 0.00 |
April | 31.96 | 5.60 | 26.36 | 62.42 | 17.14 | 0.00 | 0.00 | 0.00 |
May | 25.61 | 0.55 | 25.06 | 54.57 | 8.83 | 0.00 | 0.00 | 0.00 |
June | 24.42 | 0.05 | 24.37 | 55.12 | 4.28 | 0.00 | 0.00 | 0.00 |
July | 26.15 | 0.24 | 25.90 | 62.33 | 6.15 | 0.00 | 0.00 | 0.00 |
August | 29.67 | 2.50 | 27.17 | 67.17 | 4.57 | 0.00 | 0.00 | 0.00 |
September | 37.99 | 9.31 | 28.68 | 85.97 | 7.05 | 0.00 | 0.00 | 0.00 |
October | 52.24 | 24.51 | 27.73 | 105.91 | 11.15 | 0.00 | 0.00 | 0.00 |
November | 59.44 | 33.17 | 26.26 | 108.21 | 19.01 | 0.00 | 0.00 | 0.00 |
December | 65.22 | 41.14 | 24.08 | 110.31 | 31.04 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 43.97 | 17.95 | 26.02 | 84.43 | 16.50 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 24.42 | 0.05 | 23.71 | 54.57 | 4.28 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 67.67 | 43.96 | 28.68 | 111.95 | 35.24 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 80.91 | 52.56 | 28.34 | 133.94 | 41.77 | 0.00 | 0.00 | 0.00 |
February | 73.19 | 42.35 | 30.84 | 128.14 | 35.09 | 0.00 | 0.00 | 0.00 |
March | 56.20 | 23.76 | 32.44 | 99.87 | 29.25 | 0.00 | 0.00 | 0.00 |
April | 38.21 | 6.70 | 31.51 | 74.55 | 20.41 | 0.00 | 0.00 | 0.00 |
May | 30.62 | 0.66 | 29.96 | 64.96 | 10.62 | 0.00 | 0.00 | 0.00 |
June | 29.19 | 0.06 | 29.14 | 65.49 | 5.16 | 0.00 | 0.00 | 0.00 |
July | 31.26 | 0.29 | 30.97 | 74.07 | 7.38 | 0.00 | 0.00 | 0.00 |
August | 35.48 | 2.99 | 32.48 | 79.88 | 5.50 | 0.00 | 0.00 | 0.00 |
September | 45.42 | 11.13 | 34.29 | 102.41 | 8.44 | 0.00 | 0.00 | 0.00 |
October | 62.46 | 29.30 | 33.15 | 126.38 | 13.36 | 0.00 | 0.00 | 0.00 |
November | 71.06 | 39.66 | 31.40 | 129.34 | 22.63 | 0.00 | 0.00 | 0.00 |
December | 77.97 | 49.18 | 28.79 | 131.99 | 36.78 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 52.57 | 21.46 | 31.11 | 100.78 | 19.63 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 29.19 | 0.06 | 28.34 | 64.96 | 5.16 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 80.91 | 52.56 | 34.29 | 133.94 | 41.77 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.67 | 43.96 | 23.71 | 112.03 | 35.02 | 0.00 | 0.00 | 0.00 |
February | 61.22 | 35.42 | 25.80 | 107.15 | 29.41 | 0.00 | 0.00 | 0.00 |
March | 47.00 | 19.87 | 27.13 | 83.47 | 24.50 | 0.00 | 0.00 | 0.00 |
April | 31.96 | 5.60 | 26.36 | 62.42 | 17.17 | 0.00 | 0.00 | 0.00 |
May | 25.61 | 0.55 | 25.06 | 54.55 | 8.93 | 0.00 | 0.00 | 0.00 |
June | 24.42 | 0.05 | 24.37 | 55.03 | 4.42 | 0.00 | 0.00 | 0.00 |
July | 26.15 | 0.24 | 25.90 | 62.25 | 6.35 | 0.00 | 0.00 | 0.00 |
August | 29.67 | 2.50 | 27.17 | 67.10 | 4.73 | 0.00 | 0.00 | 0.00 |
September | 37.99 | 9.31 | 28.68 | 85.87 | 7.22 | 0.00 | 0.00 | 0.00 |
October | 52.24 | 24.51 | 27.73 | 105.88 | 11.30 | 0.00 | 0.00 | 0.00 |
November | 59.44 | 33.17 | 26.26 | 108.23 | 19.00 | 0.00 | 0.00 | 0.00 |
December | 65.22 | 41.14 | 24.08 | 110.36 | 30.88 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 43.97 | 17.95 | 26.02 | 84.42 | 16.52 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 24.42 | 0.05 | 23.71 | 54.55 | 4.42 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 67.67 | 43.96 | 28.68 | 112.03 | 35.02 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.67 | 43.96 | 23.71 | 112.03 | 35.02 | 0.00 | 0.00 | 0.00 |
February | 61.22 | 35.42 | 25.80 | 107.15 | 29.41 | 0.00 | 0.00 | 0.00 |
March | 47.00 | 19.87 | 27.13 | 83.47 | 24.50 | 0.00 | 0.00 | 0.00 |
April | 31.96 | 5.60 | 26.36 | 62.42 | 17.17 | 0.00 | 0.00 | 0.00 |
May | 25.61 | 0.55 | 25.06 | 54.55 | 8.93 | 0.00 | 0.00 | 0.00 |
June | 24.42 | 0.05 | 24.37 | 55.03 | 4.42 | 0.00 | 0.00 | 0.00 |
July | 26.15 | 0.24 | 25.90 | 62.25 | 6.35 | 0.00 | 0.00 | 0.00 |
August | 29.67 | 2.50 | 27.17 | 67.10 | 4.73 | 0.00 | 0.00 | 0.00 |
September | 37.99 | 9.31 | 28.68 | 85.87 | 7.22 | 0.00 | 0.00 | 0.00 |
October | 52.24 | 24.51 | 27.73 | 105.88 | 11.30 | 0.00 | 0.00 | 0.00 |
November | 59.44 | 33.17 | 26.26 | 108.23 | 19.00 | 0.00 | 0.00 | 0.00 |
December | 65.22 | 41.14 | 24.08 | 110.36 | 30.88 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 43.97 | 17.95 | 26.02 | 84.42 | 16.52 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 24.42 | 0.05 | 23.71 | 54.55 | 4.42 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 67.67 | 43.96 | 28.68 | 112.03 | 35.02 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 80.91 | 52.56 | 28.34 | 134.03 | 41.52 | 0.00 | 0.00 | 0.00 |
February | 73.19 | 42.35 | 30.84 | 128.23 | 34.87 | 0.00 | 0.00 | 0.00 |
March | 56.20 | 23.76 | 32.44 | 99.94 | 29.10 | 0.00 | 0.00 | 0.00 |
April | 38.21 | 6.70 | 31.51 | 74.55 | 20.44 | 0.00 | 0.00 | 0.00 |
May | 30.62 | 0.66 | 29.96 | 64.93 | 10.73 | 0.00 | 0.00 | 0.00 |
June | 29.19 | 0.06 | 29.14 | 65.39 | 5.32 | 0.00 | 0.00 | 0.00 |
July | 31.26 | 0.29 | 30.97 | 73.98 | 7.62 | 0.00 | 0.00 | 0.00 |
August | 35.48 | 2.99 | 32.48 | 79.81 | 5.69 | 0.00 | 0.00 | 0.00 |
September | 45.42 | 11.13 | 34.29 | 102.29 | 8.64 | 0.00 | 0.00 | 0.00 |
October | 62.46 | 29.30 | 33.15 | 126.34 | 13.54 | 0.00 | 0.00 | 0.00 |
November | 71.06 | 39.66 | 31.40 | 129.36 | 22.63 | 0.00 | 0.00 | 0.00 |
December | 77.97 | 49.18 | 28.79 | 132.05 | 36.58 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 52.57 | 21.46 | 31.11 | 100.77 | 19.66 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 29.19 | 0.06 | 28.34 | 64.93 | 5.32 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 80.91 | 52.56 | 34.29 | 134.03 | 41.52 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.67 | 43.96 | 23.71 | 112.22 | 34.58 | 0.00 | 0.00 | 0.00 |
February | 61.22 | 35.42 | 25.80 | 107.33 | 28.98 | 0.00 | 0.00 | 0.00 |
March | 47.00 | 19.87 | 27.13 | 83.64 | 24.09 | 0.00 | 0.00 | 0.00 |
April | 31.96 | 5.60 | 26.36 | 62.54 | 16.84 | 0.00 | 0.00 | 0.00 |
May | 25.61 | 0.55 | 25.06 | 54.67 | 8.63 | 0.00 | 0.00 | 0.00 |
June | 24.42 | 0.05 | 24.37 | 55.21 | 4.21 | 0.00 | 0.00 | 0.00 |
July | 26.15 | 0.24 | 25.90 | 62.38 | 6.11 | 0.00 | 0.00 | 0.00 |
August | 29.67 | 2.50 | 27.17 | 67.25 | 4.47 | 0.00 | 0.00 | 0.00 |
September | 37.99 | 9.31 | 28.68 | 86.02 | 7.01 | 0.00 | 0.00 | 0.00 |
October | 52.24 | 24.51 | 27.73 | 105.97 | 11.01 | 0.00 | 0.00 | 0.00 |
November | 59.44 | 33.17 | 26.26 | 108.35 | 18.67 | 0.00 | 0.00 | 0.00 |
December | 65.22 | 41.14 | 24.08 | 110.52 | 30.46 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 43.97 | 17.95 | 26.02 | 84.56 | 16.20 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 24.42 | 0.05 | 23.71 | 54.67 | 4.21 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 67.67 | 43.96 | 28.68 | 112.22 | 34.58 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.67 | 43.96 | 23.71 | 112.22 | 34.58 | 0.00 | 0.00 | 0.00 |
February | 61.22 | 35.42 | 25.80 | 107.33 | 28.98 | 0.00 | 0.00 | 0.00 |
March | 47.00 | 19.87 | 27.13 | 83.64 | 24.09 | 0.00 | 0.00 | 0.00 |
April | 31.96 | 5.60 | 26.36 | 62.54 | 16.84 | 0.00 | 0.00 | 0.00 |
May | 25.61 | 0.55 | 25.06 | 54.67 | 8.63 | 0.00 | 0.00 | 0.00 |
June | 24.42 | 0.05 | 24.37 | 55.21 | 4.21 | 0.00 | 0.00 | 0.00 |
July | 26.15 | 0.24 | 25.90 | 62.38 | 6.11 | 0.00 | 0.00 | 0.00 |
August | 29.67 | 2.50 | 27.17 | 67.25 | 4.47 | 0.00 | 0.00 | 0.00 |
September | 37.99 | 9.31 | 28.68 | 86.02 | 7.01 | 0.00 | 0.00 | 0.00 |
October | 52.24 | 24.51 | 27.73 | 105.97 | 11.01 | 0.00 | 0.00 | 0.00 |
November | 59.44 | 33.17 | 26.26 | 108.35 | 18.67 | 0.00 | 0.00 | 0.00 |
December | 65.22 | 41.14 | 24.08 | 110.52 | 30.46 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 43.97 | 17.95 | 26.02 | 84.56 | 16.20 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 24.42 | 0.05 | 23.71 | 54.67 | 4.21 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 67.67 | 43.96 | 28.68 | 112.22 | 34.58 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 80.91 | 52.56 | 28.34 | 134.26 | 41.00 | 0.00 | 0.00 | 0.00 |
February | 73.19 | 42.35 | 30.84 | 128.44 | 34.37 | 0.00 | 0.00 | 0.00 |
March | 56.20 | 23.76 | 32.44 | 100.14 | 28.62 | 0.00 | 0.00 | 0.00 |
April | 38.21 | 6.70 | 31.51 | 74.69 | 20.06 | 0.00 | 0.00 | 0.00 |
May | 30.62 | 0.66 | 29.96 | 65.08 | 10.38 | 0.00 | 0.00 | 0.00 |
June | 29.19 | 0.06 | 29.14 | 65.59 | 5.07 | 0.00 | 0.00 | 0.00 |
July | 31.26 | 0.29 | 30.97 | 74.13 | 7.34 | 0.00 | 0.00 | 0.00 |
August | 35.48 | 2.99 | 32.48 | 79.98 | 5.39 | 0.00 | 0.00 | 0.00 |
September | 45.42 | 11.13 | 34.29 | 102.46 | 8.39 | 0.00 | 0.00 | 0.00 |
October | 62.46 | 29.30 | 33.15 | 126.45 | 13.20 | 0.00 | 0.00 | 0.00 |
November | 71.06 | 39.66 | 31.40 | 129.50 | 22.24 | 0.00 | 0.00 | 0.00 |
December | 77.97 | 49.18 | 28.79 | 132.24 | 36.09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 52.57 | 21.46 | 31.11 | 100.94 | 19.28 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 29.19 | 0.06 | 28.34 | 65.08 | 5.07 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 80.91 | 52.56 | 34.29 | 134.26 | 41.00 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.67 | 43.96 | 23.71 | 112.67 | 33.45 | 0.00 | 0.00 | 0.00 |
February | 61.22 | 35.42 | 25.80 | 107.75 | 27.86 | 0.00 | 0.00 | 0.00 |
March | 47.00 | 19.87 | 27.13 | 84.05 | 23.05 | 0.00 | 0.00 | 0.00 |
April | 31.96 | 5.60 | 26.36 | 62.64 | 15.91 | 0.00 | 0.00 | 0.00 |
May | 25.61 | 0.55 | 25.06 | 54.54 | 7.75 | 0.00 | 0.00 | 0.00 |
June | 24.42 | 0.05 | 24.37 | 55.37 | 3.65 | 0.00 | 0.00 | 0.00 |
July | 26.15 | 0.24 | 25.90 | 62.27 | 5.44 | 0.00 | 0.00 | 0.00 |
August | 29.67 | 2.50 | 27.17 | 67.29 | 3.76 | 0.00 | 0.00 | 0.00 |
September | 37.99 | 9.31 | 28.68 | 86.14 | 6.44 | 0.00 | 0.00 | 0.00 |
October | 52.24 | 24.51 | 27.73 | 105.92 | 10.18 | 0.00 | 0.00 | 0.00 |
November | 59.44 | 33.17 | 26.26 | 108.50 | 17.73 | 0.00 | 0.00 | 0.00 |
December | 65.22 | 41.14 | 24.08 | 110.90 | 29.42 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 43.97 | 17.95 | 26.02 | 84.72 | 15.33 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 24.42 | 0.05 | 23.71 | 54.54 | 3.65 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 67.67 | 43.96 | 28.68 | 112.67 | 33.45 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.67 | 43.96 | 23.71 | 112.67 | 33.45 | 0.00 | 0.00 | 0.00 |
February | 61.22 | 35.42 | 25.80 | 107.75 | 27.86 | 0.00 | 0.00 | 0.00 |
March | 47.00 | 19.87 | 27.13 | 84.05 | 23.05 | 0.00 | 0.00 | 0.00 |
April | 31.96 | 5.60 | 26.36 | 62.64 | 15.91 | 0.00 | 0.00 | 0.00 |
May | 25.61 | 0.55 | 25.06 | 54.54 | 7.75 | 0.00 | 0.00 | 0.00 |
June | 24.42 | 0.05 | 24.37 | 55.37 | 3.65 | 0.00 | 0.00 | 0.00 |
July | 26.15 | 0.24 | 25.90 | 62.27 | 5.44 | 0.00 | 0.00 | 0.00 |
August | 29.67 | 2.50 | 27.17 | 67.29 | 3.76 | 0.00 | 0.00 | 0.00 |
September | 37.99 | 9.31 | 28.68 | 86.14 | 6.44 | 0.00 | 0.00 | 0.00 |
October | 52.24 | 24.51 | 27.73 | 105.92 | 10.18 | 0.00 | 0.00 | 0.00 |
November | 59.44 | 33.17 | 26.26 | 108.50 | 17.73 | 0.00 | 0.00 | 0.00 |
December | 65.22 | 41.14 | 24.08 | 110.90 | 29.42 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 43.97 | 17.95 | 26.02 | 84.72 | 15.33 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 24.42 | 0.05 | 23.71 | 54.54 | 3.65 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 67.67 | 43.96 | 28.68 | 112.67 | 33.45 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.67 | 43.96 | 23.71 | 112.67 | 33.45 | 0.00 | 0.00 | 0.00 |
February | 61.22 | 35.42 | 25.80 | 107.75 | 27.86 | 0.00 | 0.00 | 0.00 |
March | 47.00 | 19.87 | 27.13 | 84.05 | 23.05 | 0.00 | 0.00 | 0.00 |
April | 31.96 | 5.60 | 26.36 | 62.64 | 15.91 | 0.00 | 0.00 | 0.00 |
May | 25.61 | 0.55 | 25.06 | 54.54 | 7.75 | 0.00 | 0.00 | 0.00 |
June | 24.42 | 0.05 | 24.37 | 55.37 | 3.65 | 0.00 | 0.00 | 0.00 |
July | 26.15 | 0.24 | 25.90 | 62.27 | 5.44 | 0.00 | 0.00 | 0.00 |
August | 29.67 | 2.50 | 27.17 | 67.29 | 3.76 | 0.00 | 0.00 | 0.00 |
September | 37.99 | 9.31 | 28.68 | 86.14 | 6.44 | 0.00 | 0.00 | 0.00 |
October | 52.24 | 24.51 | 27.73 | 105.92 | 10.18 | 0.00 | 0.00 | 0.00 |
November | 59.44 | 33.17 | 26.26 | 108.50 | 17.73 | 0.00 | 0.00 | 0.00 |
December | 65.22 | 41.14 | 24.08 | 110.90 | 29.42 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 43.97 | 17.95 | 26.02 | 84.72 | 15.33 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 24.42 | 0.05 | 23.71 | 54.54 | 3.65 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 67.67 | 43.96 | 28.68 | 112.67 | 33.45 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.67 | 43.96 | 23.71 | 112.67 | 33.45 | 0.00 | 0.00 | 0.00 |
February | 61.22 | 35.42 | 25.80 | 107.75 | 27.86 | 0.00 | 0.00 | 0.00 |
March | 47.00 | 19.87 | 27.13 | 84.05 | 23.05 | 0.00 | 0.00 | 0.00 |
April | 31.96 | 5.60 | 26.36 | 62.64 | 15.91 | 0.00 | 0.00 | 0.00 |
May | 25.61 | 0.55 | 25.06 | 54.54 | 7.75 | 0.00 | 0.00 | 0.00 |
June | 24.42 | 0.05 | 24.37 | 55.37 | 3.65 | 0.00 | 0.00 | 0.00 |
July | 26.15 | 0.24 | 25.90 | 62.27 | 5.44 | 0.00 | 0.00 | 0.00 |
August | 29.67 | 2.50 | 27.17 | 67.29 | 3.76 | 0.00 | 0.00 | 0.00 |
September | 37.99 | 9.31 | 28.68 | 86.14 | 6.44 | 0.00 | 0.00 | 0.00 |
October | 52.24 | 24.51 | 27.73 | 105.92 | 10.18 | 0.00 | 0.00 | 0.00 |
November | 59.44 | 33.17 | 26.26 | 108.50 | 17.73 | 0.00 | 0.00 | 0.00 |
December | 65.22 | 41.14 | 24.08 | 110.90 | 29.42 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 43.97 | 17.95 | 26.02 | 84.72 | 15.33 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 24.42 | 0.05 | 23.71 | 54.54 | 3.65 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 67.67 | 43.96 | 28.68 | 112.67 | 33.45 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 80.91 | 52.56 | 28.34 | 134.75 | 39.67 | 0.00 | 0.00 | 0.00 |
February | 73.19 | 42.35 | 30.84 | 128.90 | 33.06 | 0.00 | 0.00 | 0.00 |
March | 56.20 | 23.76 | 32.44 | 100.60 | 27.39 | 0.00 | 0.00 | 0.00 |
April | 38.21 | 6.70 | 31.51 | 74.80 | 18.96 | 0.00 | 0.00 | 0.00 |
May | 30.62 | 0.66 | 29.96 | 64.92 | 9.33 | 0.00 | 0.00 | 0.00 |
June | 29.19 | 0.06 | 29.14 | 65.78 | 4.39 | 0.00 | 0.00 | 0.00 |
July | 31.26 | 0.29 | 30.97 | 74.00 | 6.54 | 0.00 | 0.00 | 0.00 |
August | 35.48 | 2.99 | 32.48 | 80.02 | 4.53 | 0.00 | 0.00 | 0.00 |
September | 45.42 | 11.13 | 34.29 | 102.60 | 7.71 | 0.00 | 0.00 | 0.00 |
October | 62.46 | 29.30 | 33.15 | 126.36 | 12.20 | 0.00 | 0.00 | 0.00 |
November | 71.06 | 39.66 | 31.40 | 129.66 | 21.12 | 0.00 | 0.00 | 0.00 |
December | 77.97 | 49.18 | 28.79 | 132.66 | 34.87 | 1.67 | 0.00 | 0.00 |
Annual Sum or Average | 52.57 | 21.46 | 31.11 | 101.12 | 18.25 | 1.67 | 0.00 | 0.00 |
Minimum of Months | 29.19 | 0.06 | 28.34 | 64.92 | 4.39 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 80.91 | 52.56 | 34.29 | 134.75 | 39.67 | 1.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 80.91 | 52.56 | 28.34 | 134.75 | 39.67 | 0.00 | 0.00 | 0.00 |
February | 73.19 | 42.35 | 30.84 | 128.90 | 33.06 | 0.00 | 0.00 | 0.00 |
March | 56.20 | 23.76 | 32.44 | 100.60 | 27.39 | 0.00 | 0.00 | 0.00 |
April | 38.21 | 6.70 | 31.51 | 74.80 | 18.96 | 0.00 | 0.00 | 0.00 |
May | 30.62 | 0.66 | 29.96 | 64.92 | 9.33 | 0.00 | 0.00 | 0.00 |
June | 29.19 | 0.06 | 29.14 | 65.78 | 4.39 | 0.00 | 0.00 | 0.00 |
July | 31.26 | 0.29 | 30.97 | 74.00 | 6.54 | 0.00 | 0.00 | 0.00 |
August | 35.48 | 2.99 | 32.48 | 80.02 | 4.53 | 0.00 | 0.00 | 0.00 |
September | 45.42 | 11.13 | 34.29 | 102.60 | 7.71 | 0.00 | 0.00 | 0.00 |
October | 62.46 | 29.30 | 33.15 | 126.36 | 12.20 | 0.00 | 0.00 | 0.00 |
November | 71.06 | 39.66 | 31.40 | 129.66 | 21.12 | 0.00 | 0.00 | 0.00 |
December | 77.97 | 49.18 | 28.79 | 132.66 | 34.87 | 1.67 | 0.00 | 0.00 |
Annual Sum or Average | 52.57 | 21.46 | 31.11 | 101.12 | 18.25 | 1.67 | 0.00 | 0.00 |
Minimum of Months | 29.19 | 0.06 | 28.34 | 64.92 | 4.39 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 80.91 | 52.56 | 34.29 | 134.75 | 39.67 | 1.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.67 | 43.96 | 23.71 | 112.52 | 33.25 | 0.00 | 0.00 | 0.00 |
February | 61.22 | 35.42 | 25.80 | 107.61 | 27.63 | 0.00 | 0.00 | 0.00 |
March | 47.00 | 19.87 | 27.13 | 83.96 | 22.77 | 0.00 | 0.00 | 0.00 |
April | 31.96 | 5.60 | 26.36 | 62.71 | 15.58 | 0.00 | 0.00 | 0.00 |
May | 25.61 | 0.55 | 25.06 | 54.79 | 7.38 | 0.00 | 0.00 | 0.00 |
June | 24.42 | 0.05 | 24.37 | 55.83 | 3.41 | 0.00 | 0.00 | 0.00 |
July | 26.15 | 0.24 | 25.90 | 62.66 | 5.13 | 0.00 | 0.00 | 0.00 |
August | 29.67 | 2.50 | 27.17 | 67.69 | 3.46 | 0.00 | 0.00 | 0.00 |
September | 37.99 | 9.31 | 28.68 | 86.47 | 6.18 | 0.00 | 0.00 | 0.00 |
October | 52.24 | 24.51 | 27.73 | 106.00 | 9.77 | 0.00 | 0.00 | 0.00 |
November | 59.44 | 33.17 | 26.26 | 108.45 | 17.40 | 0.00 | 0.00 | 0.00 |
December | 65.22 | 41.14 | 24.08 | 110.75 | 29.20 | 2.17 | 0.00 | 0.00 |
Annual Sum or Average | 43.97 | 17.95 | 26.02 | 84.84 | 15.04 | 2.17 | 0.00 | 0.00 |
Minimum of Months | 24.42 | 0.05 | 23.71 | 54.79 | 3.41 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 67.67 | 43.96 | 28.68 | 112.52 | 33.25 | 2.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.67 | 43.96 | 23.71 | 112.52 | 33.25 | 0.00 | 0.00 | 0.00 |
February | 61.22 | 35.42 | 25.80 | 107.61 | 27.63 | 0.00 | 0.00 | 0.00 |
March | 47.00 | 19.87 | 27.13 | 83.96 | 22.77 | 0.00 | 0.00 | 0.00 |
April | 31.96 | 5.60 | 26.36 | 62.71 | 15.58 | 0.00 | 0.00 | 0.00 |
May | 25.61 | 0.55 | 25.06 | 54.79 | 7.38 | 0.00 | 0.00 | 0.00 |
June | 24.42 | 0.05 | 24.37 | 55.83 | 3.41 | 0.00 | 0.00 | 0.00 |
July | 26.15 | 0.24 | 25.90 | 62.66 | 5.13 | 0.00 | 0.00 | 0.00 |
August | 29.67 | 2.50 | 27.17 | 67.69 | 3.46 | 0.00 | 0.00 | 0.00 |
September | 37.99 | 9.31 | 28.68 | 86.47 | 6.18 | 0.00 | 0.00 | 0.00 |
October | 52.24 | 24.51 | 27.73 | 106.00 | 9.77 | 0.00 | 0.00 | 0.00 |
November | 59.44 | 33.17 | 26.26 | 108.45 | 17.40 | 0.00 | 0.00 | 0.00 |
December | 65.22 | 41.14 | 24.08 | 110.75 | 29.20 | 2.17 | 0.00 | 0.00 |
Annual Sum or Average | 43.97 | 17.95 | 26.02 | 84.84 | 15.04 | 2.17 | 0.00 | 0.00 |
Minimum of Months | 24.42 | 0.05 | 23.71 | 54.79 | 3.41 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 67.67 | 43.96 | 28.68 | 112.52 | 33.25 | 2.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 80.91 | 52.56 | 28.34 | 134.62 | 39.42 | 0.00 | 0.00 | 0.00 |
February | 73.19 | 42.35 | 30.84 | 128.78 | 32.77 | 0.00 | 0.00 | 0.00 |
March | 56.20 | 23.76 | 32.44 | 100.53 | 27.06 | 0.00 | 0.00 | 0.00 |
April | 38.21 | 6.70 | 31.51 | 74.90 | 18.57 | 0.00 | 0.00 | 0.00 |
May | 30.62 | 0.66 | 29.96 | 65.22 | 8.90 | 0.00 | 0.00 | 0.00 |
June | 29.19 | 0.06 | 29.14 | 66.31 | 4.11 | 0.00 | 0.00 | 0.00 |
July | 31.26 | 0.29 | 30.97 | 74.46 | 6.17 | 0.00 | 0.00 | 0.00 |
August | 35.48 | 2.99 | 32.48 | 80.48 | 4.17 | 0.00 | 0.00 | 0.00 |
September | 45.42 | 11.13 | 34.29 | 103.00 | 7.39 | 0.00 | 0.00 | 0.00 |
October | 62.46 | 29.30 | 33.15 | 126.48 | 11.73 | 0.00 | 0.00 | 0.00 |
November | 71.06 | 39.66 | 31.40 | 129.63 | 20.73 | 0.00 | 0.00 | 0.00 |
December | 77.97 | 49.18 | 28.79 | 132.52 | 34.60 | 2.50 | 0.00 | 0.00 |
Annual Sum or Average | 52.57 | 21.46 | 31.11 | 101.27 | 17.91 | 2.50 | 0.00 | 0.00 |
Minimum of Months | 29.19 | 0.06 | 28.34 | 65.22 | 4.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 80.91 | 52.56 | 34.29 | 134.62 | 39.42 | 2.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.67 | 43.96 | 23.71 | 112.60 | 33.10 | 0.00 | 0.00 | 0.00 |
February | 61.22 | 35.42 | 25.80 | 107.69 | 27.49 | 0.00 | 0.00 | 0.00 |
March | 47.00 | 19.87 | 27.13 | 84.03 | 22.64 | 0.00 | 0.00 | 0.00 |
April | 31.96 | 5.60 | 26.36 | 62.75 | 15.49 | 0.00 | 0.00 | 0.00 |
May | 25.61 | 0.55 | 25.06 | 54.84 | 7.31 | 0.00 | 0.00 | 0.00 |
June | 24.42 | 0.05 | 24.37 | 55.89 | 3.37 | 0.00 | 0.00 | 0.00 |
July | 26.15 | 0.24 | 25.90 | 62.71 | 5.08 | 0.00 | 0.00 | 0.00 |
August | 29.67 | 2.50 | 27.17 | 67.74 | 3.42 | 0.00 | 0.00 | 0.00 |
September | 37.99 | 9.31 | 28.68 | 86.53 | 6.14 | 0.00 | 0.00 | 0.00 |
October | 52.24 | 24.51 | 27.73 | 106.04 | 9.71 | 0.00 | 0.00 | 0.00 |
November | 59.44 | 33.17 | 26.26 | 108.50 | 17.31 | 0.00 | 0.00 | 0.00 |
December | 65.22 | 41.14 | 24.08 | 110.82 | 29.05 | 2.50 | 0.00 | 0.00 |
Annual Sum or Average | 43.97 | 17.95 | 26.02 | 84.90 | 14.95 | 2.50 | 0.00 | 0.00 |
Minimum of Months | 24.42 | 0.05 | 23.71 | 54.84 | 3.37 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 67.67 | 43.96 | 28.68 | 112.60 | 33.10 | 2.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.67 | 43.96 | 23.71 | 112.60 | 33.10 | 0.00 | 0.00 | 0.00 |
February | 61.22 | 35.42 | 25.80 | 107.69 | 27.49 | 0.00 | 0.00 | 0.00 |
March | 47.00 | 19.87 | 27.13 | 84.03 | 22.64 | 0.00 | 0.00 | 0.00 |
April | 31.96 | 5.60 | 26.36 | 62.75 | 15.49 | 0.00 | 0.00 | 0.00 |
May | 25.61 | 0.55 | 25.06 | 54.84 | 7.31 | 0.00 | 0.00 | 0.00 |
June | 24.42 | 0.05 | 24.37 | 55.89 | 3.37 | 0.00 | 0.00 | 0.00 |
July | 26.15 | 0.24 | 25.90 | 62.71 | 5.08 | 0.00 | 0.00 | 0.00 |
August | 29.67 | 2.50 | 27.17 | 67.74 | 3.42 | 0.00 | 0.00 | 0.00 |
September | 37.99 | 9.31 | 28.68 | 86.53 | 6.14 | 0.00 | 0.00 | 0.00 |
October | 52.24 | 24.51 | 27.73 | 106.04 | 9.71 | 0.00 | 0.00 | 0.00 |
November | 59.44 | 33.17 | 26.26 | 108.50 | 17.31 | 0.00 | 0.00 | 0.00 |
December | 65.22 | 41.14 | 24.08 | 110.82 | 29.05 | 2.50 | 0.00 | 0.00 |
Annual Sum or Average | 43.97 | 17.95 | 26.02 | 84.90 | 14.95 | 2.50 | 0.00 | 0.00 |
Minimum of Months | 24.42 | 0.05 | 23.71 | 54.84 | 3.37 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 67.67 | 43.96 | 28.68 | 112.60 | 33.10 | 2.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 80.91 | 52.56 | 28.34 | 134.73 | 39.24 | 0.00 | 0.00 | 0.00 |
February | 73.19 | 42.35 | 30.84 | 128.87 | 32.61 | 0.00 | 0.00 | 0.00 |
March | 56.20 | 23.76 | 32.44 | 100.62 | 26.92 | 0.00 | 0.00 | 0.00 |
April | 38.21 | 6.70 | 31.51 | 74.96 | 18.47 | 0.00 | 0.00 | 0.00 |
May | 30.62 | 0.66 | 29.96 | 65.28 | 8.82 | 0.00 | 0.00 | 0.00 |
June | 29.19 | 0.06 | 29.14 | 66.39 | 4.06 | 0.00 | 0.00 | 0.00 |
July | 31.26 | 0.29 | 30.97 | 74.52 | 6.12 | 0.00 | 0.00 | 0.00 |
August | 35.48 | 2.99 | 32.48 | 80.55 | 4.11 | 0.00 | 0.00 | 0.00 |
September | 45.42 | 11.13 | 34.29 | 103.06 | 7.34 | 0.00 | 0.00 | 0.00 |
October | 62.46 | 29.30 | 33.15 | 126.53 | 11.65 | 0.00 | 0.00 | 0.00 |
November | 71.06 | 39.66 | 31.40 | 129.70 | 20.63 | 0.00 | 0.00 | 0.00 |
December | 77.97 | 49.18 | 28.79 | 132.61 | 34.43 | 2.50 | 0.00 | 0.00 |
Annual Sum or Average | 52.57 | 21.46 | 31.11 | 101.35 | 17.80 | 2.50 | 0.00 | 0.00 |
Minimum of Months | 29.19 | 0.06 | 28.34 | 65.28 | 4.06 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 80.91 | 52.56 | 34.29 | 134.73 | 39.24 | 2.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.67 | 43.96 | 23.71 | 112.78 | 32.72 | 0.00 | 0.00 | 0.00 |
February | 61.22 | 35.42 | 25.80 | 107.84 | 27.15 | 0.00 | 0.00 | 0.00 |
March | 47.00 | 19.87 | 27.13 | 84.13 | 22.37 | 0.00 | 0.00 | 0.00 |
April | 31.96 | 5.60 | 26.36 | 62.76 | 15.36 | 0.00 | 0.00 | 0.00 |
May | 25.61 | 0.55 | 25.06 | 54.80 | 7.28 | 0.00 | 0.00 | 0.00 |
June | 24.42 | 0.05 | 24.37 | 55.77 | 3.39 | 0.00 | 0.00 | 0.00 |
July | 26.15 | 0.24 | 25.90 | 62.59 | 5.16 | 0.00 | 0.00 | 0.00 |
August | 29.67 | 2.50 | 27.17 | 67.62 | 3.46 | 0.00 | 0.00 | 0.00 |
September | 37.99 | 9.31 | 28.68 | 86.39 | 6.19 | 0.00 | 0.00 | 0.00 |
October | 52.24 | 24.51 | 27.73 | 105.98 | 9.72 | 0.00 | 0.00 | 0.00 |
November | 59.44 | 33.17 | 26.26 | 108.54 | 17.19 | 0.00 | 0.00 | 0.00 |
December | 65.22 | 41.14 | 24.08 | 110.97 | 28.70 | 2.67 | 0.00 | 0.00 |
Annual Sum or Average | 43.97 | 17.95 | 26.02 | 84.90 | 14.84 | 2.67 | 0.00 | 0.00 |
Minimum of Months | 24.42 | 0.05 | 23.71 | 54.80 | 3.39 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 67.67 | 43.96 | 28.68 | 112.78 | 32.72 | 2.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.67 | 43.96 | 23.71 | 112.78 | 32.72 | 0.00 | 0.00 | 0.00 |
February | 61.22 | 35.42 | 25.80 | 107.84 | 27.15 | 0.00 | 0.00 | 0.00 |
March | 47.00 | 19.87 | 27.13 | 84.13 | 22.37 | 0.00 | 0.00 | 0.00 |
April | 31.96 | 5.60 | 26.36 | 62.76 | 15.36 | 0.00 | 0.00 | 0.00 |
May | 25.61 | 0.55 | 25.06 | 54.80 | 7.28 | 0.00 | 0.00 | 0.00 |
June | 24.42 | 0.05 | 24.37 | 55.77 | 3.39 | 0.00 | 0.00 | 0.00 |
July | 26.15 | 0.24 | 25.90 | 62.59 | 5.16 | 0.00 | 0.00 | 0.00 |
August | 29.67 | 2.50 | 27.17 | 67.62 | 3.46 | 0.00 | 0.00 | 0.00 |
September | 37.99 | 9.31 | 28.68 | 86.39 | 6.19 | 0.00 | 0.00 | 0.00 |
October | 52.24 | 24.51 | 27.73 | 105.98 | 9.72 | 0.00 | 0.00 | 0.00 |
November | 59.44 | 33.17 | 26.26 | 108.54 | 17.19 | 0.00 | 0.00 | 0.00 |
December | 65.22 | 41.14 | 24.08 | 110.97 | 28.70 | 2.67 | 0.00 | 0.00 |
Annual Sum or Average | 43.97 | 17.95 | 26.02 | 84.90 | 14.84 | 2.67 | 0.00 | 0.00 |
Minimum of Months | 24.42 | 0.05 | 23.71 | 54.80 | 3.39 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 67.67 | 43.96 | 28.68 | 112.78 | 32.72 | 2.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 80.91 | 52.56 | 28.34 | 134.93 | 38.80 | 0.00 | 0.00 | 0.00 |
February | 73.19 | 42.35 | 30.84 | 129.06 | 32.21 | 0.00 | 0.00 | 0.00 |
March | 56.20 | 23.76 | 32.44 | 100.73 | 26.60 | 0.00 | 0.00 | 0.00 |
April | 38.21 | 6.70 | 31.51 | 74.97 | 18.32 | 0.00 | 0.00 | 0.00 |
May | 30.62 | 0.66 | 29.96 | 65.23 | 8.79 | 0.00 | 0.00 | 0.00 |
June | 29.19 | 0.06 | 29.14 | 66.25 | 4.09 | 0.00 | 0.00 | 0.00 |
July | 31.26 | 0.29 | 30.97 | 74.38 | 6.21 | 0.00 | 0.00 | 0.00 |
August | 35.48 | 2.99 | 32.48 | 80.41 | 4.17 | 0.00 | 0.00 | 0.00 |
September | 45.42 | 11.13 | 34.29 | 102.90 | 7.41 | 0.00 | 0.00 | 0.00 |
October | 62.46 | 29.30 | 33.15 | 126.47 | 11.67 | 0.00 | 0.00 | 0.00 |
November | 71.06 | 39.66 | 31.40 | 129.74 | 20.49 | 0.00 | 0.00 | 0.00 |
December | 77.97 | 49.18 | 28.79 | 132.79 | 34.01 | 2.83 | 0.00 | 0.00 |
Annual Sum or Average | 52.57 | 21.46 | 31.11 | 101.35 | 17.67 | 2.83 | 0.00 | 0.00 |
Minimum of Months | 29.19 | 0.06 | 28.34 | 65.23 | 4.09 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 80.91 | 52.56 | 34.29 | 134.93 | 38.80 | 2.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.67 | 43.96 | 23.71 | 112.80 | 31.45 | 0.00 | 0.00 | 0.00 |
February | 61.22 | 35.42 | 25.80 | 107.75 | 25.95 | 0.00 | 0.00 | 0.00 |
March | 47.00 | 19.87 | 27.13 | 83.73 | 21.38 | 0.00 | 0.00 | 0.00 |
April | 31.96 | 5.60 | 26.36 | 62.06 | 14.99 | 0.00 | 0.00 | 0.00 |
May | 25.61 | 0.55 | 25.06 | 53.77 | 7.47 | 0.00 | 0.00 | 0.00 |
June | 24.42 | 0.05 | 24.37 | 54.23 | 3.70 | 0.00 | 0.00 | 0.00 |
July | 26.15 | 0.24 | 25.90 | 61.02 | 5.80 | 0.00 | 0.00 | 0.00 |
August | 29.67 | 2.50 | 27.17 | 66.18 | 3.99 | 0.00 | 0.00 | 0.00 |
September | 37.99 | 9.31 | 28.68 | 84.76 | 6.73 | 0.00 | 0.00 | 0.00 |
October | 52.24 | 24.51 | 27.73 | 105.03 | 10.21 | 0.00 | 0.00 | 0.00 |
November | 59.44 | 33.17 | 26.26 | 108.08 | 16.99 | 0.00 | 0.00 | 0.00 |
December | 65.22 | 41.14 | 24.08 | 110.99 | 27.58 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 43.97 | 17.95 | 26.02 | 84.08 | 14.64 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 24.42 | 0.05 | 23.71 | 53.77 | 3.70 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 67.67 | 43.96 | 28.68 | 112.80 | 31.45 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.67 | 43.96 | 23.71 | 112.80 | 31.45 | 0.00 | 0.00 | 0.00 |
February | 61.22 | 35.42 | 25.80 | 107.75 | 25.95 | 0.00 | 0.00 | 0.00 |
March | 47.00 | 19.87 | 27.13 | 83.73 | 21.38 | 0.00 | 0.00 | 0.00 |
April | 31.96 | 5.60 | 26.36 | 62.06 | 14.99 | 0.00 | 0.00 | 0.00 |
May | 25.61 | 0.55 | 25.06 | 53.77 | 7.47 | 0.00 | 0.00 | 0.00 |
June | 24.42 | 0.05 | 24.37 | 54.23 | 3.70 | 0.00 | 0.00 | 0.00 |
July | 26.15 | 0.24 | 25.90 | 61.02 | 5.80 | 0.00 | 0.00 | 0.00 |
August | 29.67 | 2.50 | 27.17 | 66.18 | 3.99 | 0.00 | 0.00 | 0.00 |
September | 37.99 | 9.31 | 28.68 | 84.76 | 6.73 | 0.00 | 0.00 | 0.00 |
October | 52.24 | 24.51 | 27.73 | 105.03 | 10.21 | 0.00 | 0.00 | 0.00 |
November | 59.44 | 33.17 | 26.26 | 108.08 | 16.99 | 0.00 | 0.00 | 0.00 |
December | 65.22 | 41.14 | 24.08 | 110.99 | 27.58 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 43.97 | 17.95 | 26.02 | 84.08 | 14.64 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 24.42 | 0.05 | 23.71 | 53.77 | 3.70 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 67.67 | 43.96 | 28.68 | 112.80 | 31.45 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 80.91 | 52.56 | 28.34 | 134.96 | 37.31 | 0.00 | 0.00 | 0.00 |
February | 73.19 | 42.35 | 30.84 | 128.94 | 30.82 | 0.00 | 0.00 | 0.00 |
March | 56.20 | 23.76 | 32.44 | 100.25 | 25.44 | 0.00 | 0.00 | 0.00 |
April | 38.21 | 6.70 | 31.51 | 74.12 | 17.88 | 0.00 | 0.00 | 0.00 |
May | 30.62 | 0.66 | 29.96 | 64.00 | 9.03 | 0.00 | 0.00 | 0.00 |
June | 29.19 | 0.06 | 29.14 | 64.42 | 4.47 | 0.00 | 0.00 | 0.00 |
July | 31.26 | 0.29 | 30.97 | 72.50 | 6.97 | 0.00 | 0.00 | 0.00 |
August | 35.48 | 2.99 | 32.48 | 78.69 | 4.81 | 0.00 | 0.00 | 0.00 |
September | 45.42 | 11.13 | 34.29 | 100.96 | 8.05 | 0.00 | 0.00 | 0.00 |
October | 62.46 | 29.30 | 33.15 | 125.33 | 12.25 | 0.00 | 0.00 | 0.00 |
November | 71.06 | 39.66 | 31.40 | 129.19 | 20.26 | 0.00 | 0.00 | 0.00 |
December | 77.97 | 49.18 | 28.79 | 132.81 | 32.70 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 52.57 | 21.46 | 31.11 | 100.37 | 17.44 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 29.19 | 0.06 | 28.34 | 64.00 | 4.47 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 80.91 | 52.56 | 34.29 | 134.96 | 37.31 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.181252E+09 | 0.117756E+09 | 63496794.47 | 0.301118E+09 | 90188655.38 |
February | 0.148101E+09 | 85694897.39 | 62406549.68 | 0.260009E+09 | 67578409.75 |
March | 0.125891E+09 | 53225820.30 | 72665452.91 | 0.224442E+09 | 61979017.76 |
April | 82842367.82 | 14527355.03 | 68315012.79 | 0.162199E+09 | 40210050.79 |
May | 68597603.70 | 1484092.73 | 67113510.97 | 0.146061E+09 | 19214898.27 |
June | 63292116.53 | 119442.84 | 63172673.69 | 0.145380E+09 | 8491543.03 |
July | 70027636.61 | 649095.06 | 69378541.55 | 0.168578E+09 | 12520025.80 |
August | 79479136.08 | 6706883.71 | 72772252.37 | 0.181198E+09 | 9015988.46 |
September | 98461796.94 | 24128278.69 | 74333518.25 | 0.225560E+09 | 15303158.77 |
October | 0.139918E+09 | 65645307.86 | 74272853.43 | 0.283875E+09 | 24708710.58 |
November | 0.154061E+09 | 85982896.30 | 68077800.51 | 0.280831E+09 | 44812128.14 |
December | 0.174677E+09 | 0.110176E+09 | 64500497.36 | 0.296443E+09 | 78583803.22 |
Annual Sum or Average | 0.138660E+10 | 0.566096E+09 | 0.820505E+09 | 0.267569E+10 | 0.472606E+09 |
Minimum of Months | 63292116.53 | 119442.84 | 62406549.68 | 0.145380E+09 | 8491543.03 |
Maximum of Months | 0.181252E+09 | 0.117756E+09 | 74333518.25 | 0.301118E+09 | 90188655.38 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.181252E+09 | 0.117756E+09 | 63496794.47 | 0.301118E+09 | 90188655.38 |
February | 0.148101E+09 | 85694897.39 | 62406549.68 | 0.260009E+09 | 67578409.75 |
March | 0.125891E+09 | 53225820.30 | 72665452.91 | 0.224442E+09 | 61979017.76 |
April | 82842367.82 | 14527355.03 | 68315012.79 | 0.162199E+09 | 40210050.79 |
May | 68597603.70 | 1484092.73 | 67113510.97 | 0.146061E+09 | 19214898.27 |
June | 63292116.53 | 119442.84 | 63172673.69 | 0.145380E+09 | 8491543.03 |
July | 70027636.61 | 649095.06 | 69378541.55 | 0.168578E+09 | 12520025.80 |
August | 79479136.08 | 6706883.71 | 72772252.37 | 0.181198E+09 | 9015988.46 |
September | 98461796.94 | 24128278.69 | 74333518.25 | 0.225560E+09 | 15303158.77 |
October | 0.139918E+09 | 65645307.86 | 74272853.43 | 0.283875E+09 | 24708710.58 |
November | 0.154061E+09 | 85982896.30 | 68077800.51 | 0.280831E+09 | 44812128.14 |
December | 0.174677E+09 | 0.110176E+09 | 64500497.36 | 0.296443E+09 | 78583803.22 |
Annual Sum or Average | 0.138660E+10 | 0.566096E+09 | 0.820505E+09 | 0.267569E+10 | 0.472606E+09 |
Minimum of Months | 63292116.53 | 119442.84 | 62406549.68 | 0.145380E+09 | 8491543.03 |
Maximum of Months | 0.181252E+09 | 0.117756E+09 | 74333518.25 | 0.301118E+09 | 90188655.38 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.181252E+09 | 0.117756E+09 | 63496794.47 | 0.301118E+09 | 90188655.38 |
February | 0.148101E+09 | 85694897.39 | 62406549.68 | 0.260009E+09 | 67578409.75 |
March | 0.125891E+09 | 53225820.30 | 72665452.91 | 0.224442E+09 | 61979017.76 |
April | 82842367.82 | 14527355.03 | 68315012.79 | 0.162199E+09 | 40210050.79 |
May | 68597603.70 | 1484092.73 | 67113510.97 | 0.146061E+09 | 19214898.27 |
June | 63292116.53 | 119442.84 | 63172673.69 | 0.145380E+09 | 8491543.03 |
July | 70027636.61 | 649095.06 | 69378541.55 | 0.168578E+09 | 12520025.80 |
August | 79479136.08 | 6706883.71 | 72772252.37 | 0.181198E+09 | 9015988.46 |
September | 98461796.94 | 24128278.69 | 74333518.25 | 0.225560E+09 | 15303158.77 |
October | 0.139918E+09 | 65645307.86 | 74272853.43 | 0.283875E+09 | 24708710.58 |
November | 0.154061E+09 | 85982896.30 | 68077800.51 | 0.280831E+09 | 44812128.14 |
December | 0.174677E+09 | 0.110176E+09 | 64500497.36 | 0.296443E+09 | 78583803.22 |
Annual Sum or Average | 0.138660E+10 | 0.566096E+09 | 0.820505E+09 | 0.267569E+10 | 0.472606E+09 |
Minimum of Months | 63292116.53 | 119442.84 | 62406549.68 | 0.145380E+09 | 8491543.03 |
Maximum of Months | 0.181252E+09 | 0.117756E+09 | 74333518.25 | 0.301118E+09 | 90188655.38 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.181252E+09 | 0.117756E+09 | 63496794.47 | 0.301118E+09 | 90188655.38 |
February | 0.148101E+09 | 85694897.39 | 62406549.68 | 0.260009E+09 | 67578409.75 |
March | 0.125891E+09 | 53225820.30 | 72665452.91 | 0.224442E+09 | 61979017.76 |
April | 82842367.82 | 14527355.03 | 68315012.79 | 0.162199E+09 | 40210050.79 |
May | 68597603.70 | 1484092.73 | 67113510.97 | 0.146061E+09 | 19214898.27 |
June | 63292116.53 | 119442.84 | 63172673.69 | 0.145380E+09 | 8491543.03 |
July | 70027636.61 | 649095.06 | 69378541.55 | 0.168578E+09 | 12520025.80 |
August | 79479136.08 | 6706883.71 | 72772252.37 | 0.181198E+09 | 9015988.46 |
September | 98461796.94 | 24128278.69 | 74333518.25 | 0.225560E+09 | 15303158.77 |
October | 0.139918E+09 | 65645307.86 | 74272853.43 | 0.283875E+09 | 24708710.58 |
November | 0.154061E+09 | 85982896.30 | 68077800.51 | 0.280831E+09 | 44812128.14 |
December | 0.174677E+09 | 0.110176E+09 | 64500497.36 | 0.296443E+09 | 78583803.22 |
Annual Sum or Average | 0.138660E+10 | 0.566096E+09 | 0.820505E+09 | 0.267569E+10 | 0.472606E+09 |
Minimum of Months | 63292116.53 | 119442.84 | 62406549.68 | 0.145380E+09 | 8491543.03 |
Maximum of Months | 0.181252E+09 | 0.117756E+09 | 74333518.25 | 0.301118E+09 | 90188655.38 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.217893E+09 | 0.141560E+09 | 76332922.34 | 0.362100E+09 | 0.107602E+09 |
February | 0.178041E+09 | 0.103018E+09 | 75022280.27 | 0.312734E+09 | 80677396.40 |
March | 0.151341E+09 | 63985630.17 | 87355061.31 | 0.270063E+09 | 74126071.98 |
April | 99589279.77 | 17464117.24 | 82125162.53 | 0.194704E+09 | 48272445.09 |
May | 82464880.31 | 1784107.94 | 80680772.37 | 0.174734E+09 | 23367826.60 |
June | 76086867.95 | 143588.68 | 75943279.27 | 0.173492E+09 | 10298520.11 |
July | 84184000.02 | 780312.19 | 83403687.84 | 0.201249E+09 | 15161964.94 |
August | 95546157.45 | 8062706.75 | 87483450.71 | 0.216475E+09 | 10920720.64 |
September | 0.118366E+09 | 29005905.56 | 89360332.65 | 0.269939E+09 | 18437418.81 |
October | 0.168203E+09 | 78915766.21 | 89287404.19 | 0.340434E+09 | 29887501.13 |
November | 0.185205E+09 | 0.103365E+09 | 81839996.85 | 0.337388E+09 | 53761950.38 |
December | 0.209988E+09 | 0.132449E+09 | 77539527.74 | 0.356519E+09 | 93729355.04 |
Annual Sum or Average | 0.166691E+10 | 0.680534E+09 | 0.986374E+09 | 0.320983E+10 | 0.566243E+09 |
Minimum of Months | 76086867.95 | 143588.68 | 75022280.27 | 0.173492E+09 | 10298520.11 |
Maximum of Months | 0.217893E+09 | 0.141560E+09 | 89360332.65 | 0.362100E+09 | 0.107602E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.217893E+09 | 0.141560E+09 | 76332922.34 | 0.362100E+09 | 0.107602E+09 |
February | 0.178041E+09 | 0.103018E+09 | 75022280.27 | 0.312734E+09 | 80677396.40 |
March | 0.151341E+09 | 63985630.17 | 87355061.31 | 0.270063E+09 | 74126071.98 |
April | 99589279.77 | 17464117.24 | 82125162.53 | 0.194704E+09 | 48272445.09 |
May | 82464880.31 | 1784107.94 | 80680772.37 | 0.174734E+09 | 23367826.60 |
June | 76086867.95 | 143588.68 | 75943279.27 | 0.173492E+09 | 10298520.11 |
July | 84184000.02 | 780312.19 | 83403687.84 | 0.201249E+09 | 15161964.94 |
August | 95546157.45 | 8062706.75 | 87483450.71 | 0.216475E+09 | 10920720.64 |
September | 0.118366E+09 | 29005905.56 | 89360332.65 | 0.269939E+09 | 18437418.81 |
October | 0.168203E+09 | 78915766.21 | 89287404.19 | 0.340434E+09 | 29887501.13 |
November | 0.185205E+09 | 0.103365E+09 | 81839996.85 | 0.337388E+09 | 53761950.38 |
December | 0.209988E+09 | 0.132449E+09 | 77539527.74 | 0.356519E+09 | 93729355.04 |
Annual Sum or Average | 0.166691E+10 | 0.680534E+09 | 0.986374E+09 | 0.320983E+10 | 0.566243E+09 |
Minimum of Months | 76086867.95 | 143588.68 | 75022280.27 | 0.173492E+09 | 10298520.11 |
Maximum of Months | 0.217893E+09 | 0.141560E+09 | 89360332.65 | 0.362100E+09 | 0.107602E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.181252E+09 | 0.117756E+09 | 63496794.47 | 0.299541E+09 | 92352026.13 |
February | 0.148101E+09 | 85694897.39 | 62406549.68 | 0.258841E+09 | 69351085.87 |
March | 0.125891E+09 | 53225820.30 | 72665452.91 | 0.223545E+09 | 63296713.45 |
April | 82842367.82 | 14527355.03 | 68315012.79 | 0.162520E+09 | 40453515.66 |
May | 68597603.70 | 1484092.73 | 67113510.97 | 0.147379E+09 | 18987487.31 |
June | 63292116.53 | 119442.84 | 63172673.69 | 0.147276E+09 | 8469014.23 |
July | 70027636.61 | 649095.06 | 69378541.55 | 0.170806E+09 | 12235694.97 |
August | 79479136.08 | 6706883.71 | 72772252.37 | 0.183366E+09 | 8715999.36 |
September | 98461796.94 | 24128278.69 | 74333518.25 | 0.227427E+09 | 15093138.85 |
October | 0.139918E+09 | 65645307.86 | 74272853.43 | 0.284764E+09 | 24317303.06 |
November | 0.154061E+09 | 85982896.30 | 68077800.51 | 0.280642E+09 | 45188700.86 |
December | 0.174677E+09 | 0.110176E+09 | 64500497.36 | 0.295288E+09 | 80439990.02 |
Annual Sum or Average | 0.138660E+10 | 0.566096E+09 | 0.820505E+09 | 0.268140E+10 | 0.478901E+09 |
Minimum of Months | 63292116.53 | 119442.84 | 62406549.68 | 0.147276E+09 | 8469014.23 |
Maximum of Months | 0.181252E+09 | 0.117756E+09 | 74333518.25 | 0.299541E+09 | 92352026.13 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.181252E+09 | 0.117756E+09 | 63496794.47 | 0.299541E+09 | 92352026.13 |
February | 0.148101E+09 | 85694897.39 | 62406549.68 | 0.258841E+09 | 69351085.87 |
March | 0.125891E+09 | 53225820.30 | 72665452.91 | 0.223545E+09 | 63296713.45 |
April | 82842367.82 | 14527355.03 | 68315012.79 | 0.162520E+09 | 40453515.66 |
May | 68597603.70 | 1484092.73 | 67113510.97 | 0.147379E+09 | 18987487.31 |
June | 63292116.53 | 119442.84 | 63172673.69 | 0.147276E+09 | 8469014.23 |
July | 70027636.61 | 649095.06 | 69378541.55 | 0.170806E+09 | 12235694.97 |
August | 79479136.08 | 6706883.71 | 72772252.37 | 0.183366E+09 | 8715999.36 |
September | 98461796.94 | 24128278.69 | 74333518.25 | 0.227427E+09 | 15093138.85 |
October | 0.139918E+09 | 65645307.86 | 74272853.43 | 0.284764E+09 | 24317303.06 |
November | 0.154061E+09 | 85982896.30 | 68077800.51 | 0.280642E+09 | 45188700.86 |
December | 0.174677E+09 | 0.110176E+09 | 64500497.36 | 0.295288E+09 | 80439990.02 |
Annual Sum or Average | 0.138660E+10 | 0.566096E+09 | 0.820505E+09 | 0.268140E+10 | 0.478901E+09 |
Minimum of Months | 63292116.53 | 119442.84 | 62406549.68 | 0.147276E+09 | 8469014.23 |
Maximum of Months | 0.181252E+09 | 0.117756E+09 | 74333518.25 | 0.299541E+09 | 92352026.13 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.217893E+09 | 0.141560E+09 | 76332922.34 | 0.360336E+09 | 0.110151E+09 |
February | 0.178041E+09 | 0.103018E+09 | 75022280.27 | 0.311449E+09 | 82749862.39 |
March | 0.151341E+09 | 63985630.17 | 87355061.31 | 0.269102E+09 | 75670355.60 |
April | 99589279.77 | 17464117.24 | 82125162.53 | 0.195139E+09 | 48557743.93 |
May | 82464880.31 | 1784107.94 | 80680772.37 | 0.176307E+09 | 23097036.07 |
June | 76086867.95 | 143588.68 | 75943279.27 | 0.175740E+09 | 10276796.70 |
July | 84184000.02 | 780312.19 | 83403687.84 | 0.203906E+09 | 14831489.36 |
August | 95546157.45 | 8062706.75 | 87483450.71 | 0.219059E+09 | 10559153.35 |
September | 0.118366E+09 | 29005905.56 | 89360332.65 | 0.272202E+09 | 18186323.54 |
October | 0.168203E+09 | 78915766.21 | 89287404.19 | 0.341555E+09 | 29423850.77 |
November | 0.185205E+09 | 0.103365E+09 | 81839996.85 | 0.337253E+09 | 54198238.58 |
December | 0.209988E+09 | 0.132449E+09 | 77539527.74 | 0.355264E+09 | 95904149.43 |
Annual Sum or Average | 0.166691E+10 | 0.680534E+09 | 0.986374E+09 | 0.321731E+10 | 0.573606E+09 |
Minimum of Months | 76086867.95 | 143588.68 | 75022280.27 | 0.175740E+09 | 10276796.70 |
Maximum of Months | 0.217893E+09 | 0.141560E+09 | 89360332.65 | 0.360336E+09 | 0.110151E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.181252E+09 | 0.117756E+09 | 63496794.47 | 0.299851E+09 | 94390046.31 |
February | 0.148101E+09 | 85694897.39 | 62406549.68 | 0.259056E+09 | 71587602.72 |
March | 0.125891E+09 | 53225820.30 | 72665452.91 | 0.223432E+09 | 65952182.19 |
April | 82842367.82 | 14527355.03 | 68315012.79 | 0.161803E+09 | 44424480.81 |
May | 68597603.70 | 1484092.73 | 67113510.97 | 0.146171E+09 | 23654874.16 |
June | 63292116.53 | 119442.84 | 63172673.69 | 0.142860E+09 | 11102855.76 |
July | 70027636.61 | 649095.06 | 69378541.55 | 0.166933E+09 | 16460687.53 |
August | 79479136.08 | 6706883.71 | 72772252.37 | 0.179904E+09 | 12241198.57 |
September | 98461796.94 | 24128278.69 | 74333518.25 | 0.222837E+09 | 18277898.61 |
October | 0.139918E+09 | 65645307.86 | 74272853.43 | 0.283681E+09 | 29855953.76 |
November | 0.154061E+09 | 85982896.30 | 68077800.51 | 0.280492E+09 | 49263371.61 |
December | 0.174677E+09 | 0.110176E+09 | 64500497.36 | 0.295456E+09 | 83141221.70 |
Annual Sum or Average | 0.138660E+10 | 0.566096E+09 | 0.820505E+09 | 0.266248E+10 | 0.520352E+09 |
Minimum of Months | 63292116.53 | 119442.84 | 62406549.68 | 0.142860E+09 | 11102855.76 |
Maximum of Months | 0.181252E+09 | 0.117756E+09 | 74333518.25 | 0.299851E+09 | 94390046.31 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.181252E+09 | 0.117756E+09 | 63496794.47 | 0.299851E+09 | 94390046.31 |
February | 0.148101E+09 | 85694897.39 | 62406549.68 | 0.259056E+09 | 71587602.72 |
March | 0.125891E+09 | 53225820.30 | 72665452.91 | 0.223432E+09 | 65952182.19 |
April | 82842367.82 | 14527355.03 | 68315012.79 | 0.161803E+09 | 44424480.81 |
May | 68597603.70 | 1484092.73 | 67113510.97 | 0.146171E+09 | 23654874.16 |
June | 63292116.53 | 119442.84 | 63172673.69 | 0.142860E+09 | 11102855.76 |
July | 70027636.61 | 649095.06 | 69378541.55 | 0.166933E+09 | 16460687.53 |
August | 79479136.08 | 6706883.71 | 72772252.37 | 0.179904E+09 | 12241198.57 |
September | 98461796.94 | 24128278.69 | 74333518.25 | 0.222837E+09 | 18277898.61 |
October | 0.139918E+09 | 65645307.86 | 74272853.43 | 0.283681E+09 | 29855953.76 |
November | 0.154061E+09 | 85982896.30 | 68077800.51 | 0.280492E+09 | 49263371.61 |
December | 0.174677E+09 | 0.110176E+09 | 64500497.36 | 0.295456E+09 | 83141221.70 |
Annual Sum or Average | 0.138660E+10 | 0.566096E+09 | 0.820505E+09 | 0.266248E+10 | 0.520352E+09 |
Minimum of Months | 63292116.53 | 119442.84 | 62406549.68 | 0.142860E+09 | 11102855.76 |
Maximum of Months | 0.181252E+09 | 0.117756E+09 | 74333518.25 | 0.299851E+09 | 94390046.31 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.216703E+09 | 0.140787E+09 | 75915802.54 | 0.358734E+09 | 0.111890E+09 |
February | 0.177068E+09 | 0.102456E+09 | 74612322.45 | 0.309999E+09 | 84878203.87 |
March | 0.150514E+09 | 63635981.91 | 86877711.25 | 0.267504E+09 | 78329956.79 |
April | 99045076.06 | 17368684.91 | 81676391.15 | 0.193244E+09 | 52912619.48 |
May | 82014252.54 | 1774358.72 | 80239893.83 | 0.173979E+09 | 28434292.18 |
June | 75671092.72 | 142804.05 | 75528288.67 | 0.169742E+09 | 13374938.63 |
July | 83723978.17 | 776048.19 | 82947929.98 | 0.198377E+09 | 19770502.02 |
August | 95024047.30 | 8018648.24 | 87005399.06 | 0.213960E+09 | 14733776.02 |
September | 0.117719E+09 | 28847403.34 | 88872024.82 | 0.265443E+09 | 21865588.40 |
October | 0.167284E+09 | 78484532.51 | 88799494.88 | 0.338483E+09 | 35772546.69 |
November | 0.184193E+09 | 0.102800E+09 | 81392783.75 | 0.335254E+09 | 58654505.56 |
December | 0.208841E+09 | 0.131725E+09 | 77115814.47 | 0.353520E+09 | 98498687.85 |
Annual Sum or Average | 0.165780E+10 | 0.676816E+09 | 0.980984E+09 | 0.317824E+10 | 0.619115E+09 |
Minimum of Months | 75671092.72 | 142804.05 | 74612322.45 | 0.169742E+09 | 13374938.63 |
Maximum of Months | 0.216703E+09 | 0.140787E+09 | 88872024.82 | 0.358734E+09 | 0.111890E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.181252E+09 | 0.117756E+09 | 63496794.47 | 0.300071E+09 | 93809615.85 |
February | 0.148101E+09 | 85694897.39 | 62406549.68 | 0.259226E+09 | 71148869.71 |
March | 0.125891E+09 | 53225820.30 | 72665452.91 | 0.223568E+09 | 65614719.81 |
April | 82842367.82 | 14527355.03 | 68315012.79 | 0.161804E+09 | 44491749.90 |
May | 68597603.70 | 1484092.73 | 67113510.97 | 0.146120E+09 | 23922586.19 |
June | 63292116.53 | 119442.84 | 63172673.69 | 0.142636E+09 | 11457489.83 |
July | 70027636.61 | 649095.06 | 69378541.55 | 0.166733E+09 | 17011466.60 |
August | 79479136.08 | 6706883.71 | 72772252.37 | 0.179733E+09 | 12658383.62 |
September | 98461796.94 | 24128278.69 | 74333518.25 | 0.222563E+09 | 18708846.70 |
October | 0.139918E+09 | 65645307.86 | 74272853.43 | 0.283601E+09 | 30274696.06 |
November | 0.154061E+09 | 85982896.30 | 68077800.51 | 0.280523E+09 | 49260073.77 |
December | 0.174677E+09 | 0.110176E+09 | 64500497.36 | 0.295601E+09 | 82705984.88 |
Annual Sum or Average | 0.138660E+10 | 0.566096E+09 | 0.820505E+09 | 0.266218E+10 | 0.521064E+09 |
Minimum of Months | 63292116.53 | 119442.84 | 62406549.68 | 0.142636E+09 | 11457489.83 |
Maximum of Months | 0.181252E+09 | 0.117756E+09 | 74333518.25 | 0.300071E+09 | 93809615.85 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.181252E+09 | 0.117756E+09 | 63496794.47 | 0.300071E+09 | 93809615.85 |
February | 0.148101E+09 | 85694897.39 | 62406549.68 | 0.259226E+09 | 71148869.71 |
March | 0.125891E+09 | 53225820.30 | 72665452.91 | 0.223568E+09 | 65614719.81 |
April | 82842367.82 | 14527355.03 | 68315012.79 | 0.161804E+09 | 44491749.90 |
May | 68597603.70 | 1484092.73 | 67113510.97 | 0.146120E+09 | 23922586.19 |
June | 63292116.53 | 119442.84 | 63172673.69 | 0.142636E+09 | 11457489.83 |
July | 70027636.61 | 649095.06 | 69378541.55 | 0.166733E+09 | 17011466.60 |
August | 79479136.08 | 6706883.71 | 72772252.37 | 0.179733E+09 | 12658383.62 |
September | 98461796.94 | 24128278.69 | 74333518.25 | 0.222563E+09 | 18708846.70 |
October | 0.139918E+09 | 65645307.86 | 74272853.43 | 0.283601E+09 | 30274696.06 |
November | 0.154061E+09 | 85982896.30 | 68077800.51 | 0.280523E+09 | 49260073.77 |
December | 0.174677E+09 | 0.110176E+09 | 64500497.36 | 0.295601E+09 | 82705984.88 |
Annual Sum or Average | 0.138660E+10 | 0.566096E+09 | 0.820505E+09 | 0.266218E+10 | 0.521064E+09 |
Minimum of Months | 63292116.53 | 119442.84 | 62406549.68 | 0.142636E+09 | 11457489.83 |
Maximum of Months | 0.181252E+09 | 0.117756E+09 | 74333518.25 | 0.300071E+09 | 93809615.85 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.216703E+09 | 0.140787E+09 | 75915802.54 | 0.358997E+09 | 0.111203E+09 |
February | 0.177068E+09 | 0.102456E+09 | 74612322.45 | 0.310203E+09 | 84361862.36 |
March | 0.150514E+09 | 63635981.91 | 86877711.25 | 0.267667E+09 | 77932883.56 |
April | 99045076.06 | 17368684.91 | 81676391.15 | 0.193246E+09 | 52992209.00 |
May | 82014252.54 | 1774358.72 | 80239893.83 | 0.173918E+09 | 28749852.84 |
June | 75671092.72 | 142804.05 | 75528288.67 | 0.169480E+09 | 13800814.72 |
July | 83723978.17 | 776048.19 | 82947929.98 | 0.198139E+09 | 20422491.48 |
August | 95024047.30 | 8018648.24 | 87005399.06 | 0.213762E+09 | 15232020.03 |
September | 0.117719E+09 | 28847403.34 | 88872024.82 | 0.265127E+09 | 22384216.91 |
October | 0.167284E+09 | 78484532.51 | 88799494.88 | 0.338386E+09 | 36266873.20 |
November | 0.184193E+09 | 0.102800E+09 | 81392783.75 | 0.335291E+09 | 58651156.56 |
December | 0.208841E+09 | 0.131725E+09 | 77115814.47 | 0.353694E+09 | 97984490.07 |
Annual Sum or Average | 0.165780E+10 | 0.676816E+09 | 0.980984E+09 | 0.317791E+10 | 0.619982E+09 |
Minimum of Months | 75671092.72 | 142804.05 | 74612322.45 | 0.169480E+09 | 13800814.72 |
Maximum of Months | 0.216703E+09 | 0.140787E+09 | 88872024.82 | 0.358997E+09 | 0.111203E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.181252E+09 | 0.117756E+09 | 63496794.47 | 0.300568E+09 | 92628042.76 |
February | 0.148101E+09 | 85694897.39 | 62406549.68 | 0.259657E+09 | 70120167.60 |
March | 0.125891E+09 | 53225820.30 | 72665452.91 | 0.224031E+09 | 64523360.63 |
April | 82842367.82 | 14527355.03 | 68315012.79 | 0.162104E+09 | 43639259.40 |
May | 68597603.70 | 1484092.73 | 67113510.97 | 0.146440E+09 | 23120897.86 |
June | 63292116.53 | 119442.84 | 63172673.69 | 0.143094E+09 | 10900304.67 |
July | 70027636.61 | 649095.06 | 69378541.55 | 0.167071E+09 | 16368257.53 |
August | 79479136.08 | 6706883.71 | 72772252.37 | 0.180115E+09 | 11975502.24 |
September | 98461796.94 | 24128278.69 | 74333518.25 | 0.222951E+09 | 18161367.25 |
October | 0.139918E+09 | 65645307.86 | 74272853.43 | 0.283840E+09 | 29487825.44 |
November | 0.154061E+09 | 85982896.30 | 68077800.51 | 0.280840E+09 | 48395105.87 |
December | 0.174677E+09 | 0.110176E+09 | 64500497.36 | 0.296017E+09 | 81583371.15 |
Annual Sum or Average | 0.138660E+10 | 0.566096E+09 | 0.820505E+09 | 0.266673E+10 | 0.510903E+09 |
Minimum of Months | 63292116.53 | 119442.84 | 62406549.68 | 0.143094E+09 | 10900304.67 |
Maximum of Months | 0.181252E+09 | 0.117756E+09 | 74333518.25 | 0.300568E+09 | 92628042.76 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.181252E+09 | 0.117756E+09 | 63496794.47 | 0.300568E+09 | 92628042.76 |
February | 0.148101E+09 | 85694897.39 | 62406549.68 | 0.259657E+09 | 70120167.60 |
March | 0.125891E+09 | 53225820.30 | 72665452.91 | 0.224031E+09 | 64523360.63 |
April | 82842367.82 | 14527355.03 | 68315012.79 | 0.162104E+09 | 43639259.40 |
May | 68597603.70 | 1484092.73 | 67113510.97 | 0.146440E+09 | 23120897.86 |
June | 63292116.53 | 119442.84 | 63172673.69 | 0.143094E+09 | 10900304.67 |
July | 70027636.61 | 649095.06 | 69378541.55 | 0.167071E+09 | 16368257.53 |
August | 79479136.08 | 6706883.71 | 72772252.37 | 0.180115E+09 | 11975502.24 |
September | 98461796.94 | 24128278.69 | 74333518.25 | 0.222951E+09 | 18161367.25 |
October | 0.139918E+09 | 65645307.86 | 74272853.43 | 0.283840E+09 | 29487825.44 |
November | 0.154061E+09 | 85982896.30 | 68077800.51 | 0.280840E+09 | 48395105.87 |
December | 0.174677E+09 | 0.110176E+09 | 64500497.36 | 0.296017E+09 | 81583371.15 |
Annual Sum or Average | 0.138660E+10 | 0.566096E+09 | 0.820505E+09 | 0.266673E+10 | 0.510903E+09 |
Minimum of Months | 63292116.53 | 119442.84 | 62406549.68 | 0.143094E+09 | 10900304.67 |
Maximum of Months | 0.181252E+09 | 0.117756E+09 | 74333518.25 | 0.300568E+09 | 92628042.76 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.216703E+09 | 0.140787E+09 | 75915802.54 | 0.359591E+09 | 0.109815E+09 |
February | 0.177068E+09 | 0.102456E+09 | 74612322.45 | 0.310719E+09 | 83155780.37 |
March | 0.150514E+09 | 63635981.91 | 86877711.25 | 0.268222E+09 | 76656103.67 |
April | 99045076.06 | 17368684.91 | 81676391.15 | 0.193607E+09 | 51993393.14 |
May | 82014252.54 | 1774358.72 | 80239893.83 | 0.174301E+09 | 27813094.70 |
June | 75671092.72 | 142804.05 | 75528288.67 | 0.170017E+09 | 13138184.03 |
July | 83723978.17 | 776048.19 | 82947929.98 | 0.198539E+09 | 19666005.31 |
August | 95024047.30 | 8018648.24 | 87005399.06 | 0.214213E+09 | 14424875.20 |
September | 0.117719E+09 | 28847403.34 | 88872024.82 | 0.265582E+09 | 21734723.61 |
October | 0.167284E+09 | 78484532.51 | 88799494.88 | 0.338673E+09 | 35344743.20 |
November | 0.184193E+09 | 0.102800E+09 | 81392783.75 | 0.335672E+09 | 57635135.03 |
December | 0.208841E+09 | 0.131725E+09 | 77115814.47 | 0.354192E+09 | 96665969.12 |
Annual Sum or Average | 0.165780E+10 | 0.676816E+09 | 0.980984E+09 | 0.318333E+10 | 0.608043E+09 |
Minimum of Months | 75671092.72 | 142804.05 | 74612322.45 | 0.170017E+09 | 13138184.03 |
Maximum of Months | 0.216703E+09 | 0.140787E+09 | 88872024.82 | 0.359591E+09 | 0.109815E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.181252E+09 | 0.117756E+09 | 63496794.47 | 0.301765E+09 | 89604920.15 |
February | 0.148101E+09 | 85694897.39 | 62406549.68 | 0.260667E+09 | 67405819.76 |
March | 0.125891E+09 | 53225820.30 | 72665452.91 | 0.225127E+09 | 61724739.29 |
April | 82842367.82 | 14527355.03 | 68315012.79 | 0.162366E+09 | 41231400.55 |
May | 68597603.70 | 1484092.73 | 67113510.97 | 0.146087E+09 | 20746463.05 |
June | 63292116.53 | 119442.84 | 63172673.69 | 0.143518E+09 | 9450476.28 |
July | 70027636.61 | 649095.06 | 69378541.55 | 0.166779E+09 | 14583860.89 |
August | 79479136.08 | 6706883.71 | 72772252.37 | 0.180227E+09 | 10078473.62 |
September | 98461796.94 | 24128278.69 | 74333518.25 | 0.223273E+09 | 16700408.22 |
October | 0.139918E+09 | 65645307.86 | 74272853.43 | 0.283689E+09 | 27268121.45 |
November | 0.154061E+09 | 85982896.30 | 68077800.51 | 0.281234E+09 | 45943946.72 |
December | 0.174677E+09 | 0.110176E+09 | 64500497.36 | 0.297043E+09 | 78803188.66 |
Annual Sum or Average | 0.138660E+10 | 0.566096E+09 | 0.820505E+09 | 0.267177E+10 | 0.483542E+09 |
Minimum of Months | 63292116.53 | 119442.84 | 62406549.68 | 0.143518E+09 | 9450476.28 |
Maximum of Months | 0.181252E+09 | 0.117756E+09 | 74333518.25 | 0.301765E+09 | 89604920.15 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.181252E+09 | 0.117756E+09 | 63496794.47 | 0.301765E+09 | 89604920.15 |
February | 0.148101E+09 | 85694897.39 | 62406549.68 | 0.260667E+09 | 67405819.76 |
March | 0.125891E+09 | 53225820.30 | 72665452.91 | 0.225127E+09 | 61724739.29 |
April | 82842367.82 | 14527355.03 | 68315012.79 | 0.162366E+09 | 41231400.55 |
May | 68597603.70 | 1484092.73 | 67113510.97 | 0.146087E+09 | 20746463.05 |
June | 63292116.53 | 119442.84 | 63172673.69 | 0.143518E+09 | 9450476.28 |
July | 70027636.61 | 649095.06 | 69378541.55 | 0.166779E+09 | 14583860.89 |
August | 79479136.08 | 6706883.71 | 72772252.37 | 0.180227E+09 | 10078473.62 |
September | 98461796.94 | 24128278.69 | 74333518.25 | 0.223273E+09 | 16700408.22 |
October | 0.139918E+09 | 65645307.86 | 74272853.43 | 0.283689E+09 | 27268121.45 |
November | 0.154061E+09 | 85982896.30 | 68077800.51 | 0.281234E+09 | 45943946.72 |
December | 0.174677E+09 | 0.110176E+09 | 64500497.36 | 0.297043E+09 | 78803188.66 |
Annual Sum or Average | 0.138660E+10 | 0.566096E+09 | 0.820505E+09 | 0.267177E+10 | 0.483542E+09 |
Minimum of Months | 63292116.53 | 119442.84 | 62406549.68 | 0.143518E+09 | 9450476.28 |
Maximum of Months | 0.181252E+09 | 0.117756E+09 | 74333518.25 | 0.301765E+09 | 89604920.15 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.181252E+09 | 0.117756E+09 | 63496794.47 | 0.301765E+09 | 89604920.15 |
February | 0.148101E+09 | 85694897.39 | 62406549.68 | 0.260667E+09 | 67405819.76 |
March | 0.125891E+09 | 53225820.30 | 72665452.91 | 0.225127E+09 | 61724739.29 |
April | 82842367.82 | 14527355.03 | 68315012.79 | 0.162366E+09 | 41231400.55 |
May | 68597603.70 | 1484092.73 | 67113510.97 | 0.146087E+09 | 20746463.05 |
June | 63292116.53 | 119442.84 | 63172673.69 | 0.143518E+09 | 9450476.28 |
July | 70027636.61 | 649095.06 | 69378541.55 | 0.166779E+09 | 14583860.89 |
August | 79479136.08 | 6706883.71 | 72772252.37 | 0.180227E+09 | 10078473.62 |
September | 98461796.94 | 24128278.69 | 74333518.25 | 0.223273E+09 | 16700408.22 |
October | 0.139918E+09 | 65645307.86 | 74272853.43 | 0.283689E+09 | 27268121.45 |
November | 0.154061E+09 | 85982896.30 | 68077800.51 | 0.281234E+09 | 45943946.72 |
December | 0.174677E+09 | 0.110176E+09 | 64500497.36 | 0.297043E+09 | 78803188.66 |
Annual Sum or Average | 0.138660E+10 | 0.566096E+09 | 0.820505E+09 | 0.267177E+10 | 0.483542E+09 |
Minimum of Months | 63292116.53 | 119442.84 | 62406549.68 | 0.143518E+09 | 9450476.28 |
Maximum of Months | 0.181252E+09 | 0.117756E+09 | 74333518.25 | 0.301765E+09 | 89604920.15 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.181252E+09 | 0.117756E+09 | 63496794.47 | 0.301765E+09 | 89604920.15 |
February | 0.148101E+09 | 85694897.39 | 62406549.68 | 0.260667E+09 | 67405819.76 |
March | 0.125891E+09 | 53225820.30 | 72665452.91 | 0.225127E+09 | 61724739.29 |
April | 82842367.82 | 14527355.03 | 68315012.79 | 0.162366E+09 | 41231400.55 |
May | 68597603.70 | 1484092.73 | 67113510.97 | 0.146087E+09 | 20746463.05 |
June | 63292116.53 | 119442.84 | 63172673.69 | 0.143518E+09 | 9450476.28 |
July | 70027636.61 | 649095.06 | 69378541.55 | 0.166779E+09 | 14583860.89 |
August | 79479136.08 | 6706883.71 | 72772252.37 | 0.180227E+09 | 10078473.62 |
September | 98461796.94 | 24128278.69 | 74333518.25 | 0.223273E+09 | 16700408.22 |
October | 0.139918E+09 | 65645307.86 | 74272853.43 | 0.283689E+09 | 27268121.45 |
November | 0.154061E+09 | 85982896.30 | 68077800.51 | 0.281234E+09 | 45943946.72 |
December | 0.174677E+09 | 0.110176E+09 | 64500497.36 | 0.297043E+09 | 78803188.66 |
Annual Sum or Average | 0.138660E+10 | 0.566096E+09 | 0.820505E+09 | 0.267177E+10 | 0.483542E+09 |
Minimum of Months | 63292116.53 | 119442.84 | 62406549.68 | 0.143518E+09 | 9450476.28 |
Maximum of Months | 0.181252E+09 | 0.117756E+09 | 74333518.25 | 0.301765E+09 | 89604920.15 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.216703E+09 | 0.140787E+09 | 75915802.54 | 0.360918E+09 | 0.106255E+09 |
February | 0.177068E+09 | 0.102456E+09 | 74612322.45 | 0.311831E+09 | 79969939.31 |
March | 0.150514E+09 | 63635981.91 | 86877711.25 | 0.269437E+09 | 73360880.68 |
April | 99045076.06 | 17368684.91 | 81676391.15 | 0.193887E+09 | 49140630.27 |
May | 82014252.54 | 1774358.72 | 80239893.83 | 0.173895E+09 | 24990036.50 |
June | 75671092.72 | 142804.05 | 75528288.67 | 0.170508E+09 | 11371238.65 |
July | 83723978.17 | 776048.19 | 82947929.98 | 0.198206E+09 | 17511145.40 |
August | 95024047.30 | 8018648.24 | 87005399.06 | 0.214329E+09 | 12120273.99 |
September | 0.117719E+09 | 28847403.34 | 88872024.82 | 0.265935E+09 | 19971629.77 |
October | 0.167284E+09 | 78484532.51 | 88799494.88 | 0.338451E+09 | 32686121.19 |
November | 0.184193E+09 | 0.102800E+09 | 81392783.75 | 0.336070E+09 | 54731426.60 |
December | 0.208841E+09 | 0.131725E+09 | 77115814.47 | 0.355313E+09 | 93397169.44 |
Annual Sum or Average | 0.165780E+10 | 0.676816E+09 | 0.980984E+09 | 0.318878E+10 | 0.575506E+09 |
Minimum of Months | 75671092.72 | 142804.05 | 74612322.45 | 0.170508E+09 | 11371238.65 |
Maximum of Months | 0.216703E+09 | 0.140787E+09 | 88872024.82 | 0.360918E+09 | 0.106255E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.216703E+09 | 0.140787E+09 | 75915802.54 | 0.360918E+09 | 0.106255E+09 |
February | 0.177068E+09 | 0.102456E+09 | 74612322.45 | 0.311831E+09 | 79969939.31 |
March | 0.150514E+09 | 63635981.91 | 86877711.25 | 0.269437E+09 | 73360880.68 |
April | 99045076.06 | 17368684.91 | 81676391.15 | 0.193887E+09 | 49140630.27 |
May | 82014252.54 | 1774358.72 | 80239893.83 | 0.173895E+09 | 24990036.50 |
June | 75671092.72 | 142804.05 | 75528288.67 | 0.170508E+09 | 11371238.65 |
July | 83723978.17 | 776048.19 | 82947929.98 | 0.198206E+09 | 17511145.40 |
August | 95024047.30 | 8018648.24 | 87005399.06 | 0.214329E+09 | 12120273.99 |
September | 0.117719E+09 | 28847403.34 | 88872024.82 | 0.265935E+09 | 19971629.77 |
October | 0.167284E+09 | 78484532.51 | 88799494.88 | 0.338451E+09 | 32686121.19 |
November | 0.184193E+09 | 0.102800E+09 | 81392783.75 | 0.336070E+09 | 54731426.60 |
December | 0.208841E+09 | 0.131725E+09 | 77115814.47 | 0.355313E+09 | 93397169.44 |
Annual Sum or Average | 0.165780E+10 | 0.676816E+09 | 0.980984E+09 | 0.318878E+10 | 0.575506E+09 |
Minimum of Months | 75671092.72 | 142804.05 | 74612322.45 | 0.170508E+09 | 11371238.65 |
Maximum of Months | 0.216703E+09 | 0.140787E+09 | 88872024.82 | 0.360918E+09 | 0.106255E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.181252E+09 | 0.117756E+09 | 63496794.47 | 0.301372E+09 | 89043751.33 |
February | 0.148101E+09 | 85694897.39 | 62406549.68 | 0.260323E+09 | 66835636.77 |
March | 0.125891E+09 | 53225820.30 | 72665452.91 | 0.224887E+09 | 60977025.21 |
April | 82842367.82 | 14527355.03 | 68315012.79 | 0.162533E+09 | 40374239.99 |
May | 68597603.70 | 1484092.73 | 67113510.97 | 0.146746E+09 | 19754637.10 |
June | 63292116.53 | 119442.84 | 63172673.69 | 0.144704E+09 | 8833362.77 |
July | 70027636.61 | 649095.06 | 69378541.55 | 0.167836E+09 | 13739789.50 |
August | 79479136.08 | 6706883.71 | 72772252.37 | 0.181288E+09 | 9280478.72 |
September | 98461796.94 | 24128278.69 | 74333518.25 | 0.224133E+09 | 16006977.59 |
October | 0.139918E+09 | 65645307.86 | 74272853.43 | 0.283898E+09 | 26181174.68 |
November | 0.154061E+09 | 85982896.30 | 68077800.51 | 0.281100E+09 | 45097281.84 |
December | 0.174677E+09 | 0.110176E+09 | 64500497.36 | 0.296631E+09 | 78208534.86 |
Annual Sum or Average | 0.138660E+10 | 0.566096E+09 | 0.820505E+09 | 0.267545E+10 | 0.474333E+09 |
Minimum of Months | 63292116.53 | 119442.84 | 62406549.68 | 0.144704E+09 | 8833362.77 |
Maximum of Months | 0.181252E+09 | 0.117756E+09 | 74333518.25 | 0.301372E+09 | 89043751.33 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.181252E+09 | 0.117756E+09 | 63496794.47 | 0.301372E+09 | 89043751.33 |
February | 0.148101E+09 | 85694897.39 | 62406549.68 | 0.260323E+09 | 66835636.77 |
March | 0.125891E+09 | 53225820.30 | 72665452.91 | 0.224887E+09 | 60977025.21 |
April | 82842367.82 | 14527355.03 | 68315012.79 | 0.162533E+09 | 40374239.99 |
May | 68597603.70 | 1484092.73 | 67113510.97 | 0.146746E+09 | 19754637.10 |
June | 63292116.53 | 119442.84 | 63172673.69 | 0.144704E+09 | 8833362.77 |
July | 70027636.61 | 649095.06 | 69378541.55 | 0.167836E+09 | 13739789.50 |
August | 79479136.08 | 6706883.71 | 72772252.37 | 0.181288E+09 | 9280478.72 |
September | 98461796.94 | 24128278.69 | 74333518.25 | 0.224133E+09 | 16006977.59 |
October | 0.139918E+09 | 65645307.86 | 74272853.43 | 0.283898E+09 | 26181174.68 |
November | 0.154061E+09 | 85982896.30 | 68077800.51 | 0.281100E+09 | 45097281.84 |
December | 0.174677E+09 | 0.110176E+09 | 64500497.36 | 0.296631E+09 | 78208534.86 |
Annual Sum or Average | 0.138660E+10 | 0.566096E+09 | 0.820505E+09 | 0.267545E+10 | 0.474333E+09 |
Minimum of Months | 63292116.53 | 119442.84 | 62406549.68 | 0.144704E+09 | 8833362.77 |
Maximum of Months | 0.181252E+09 | 0.117756E+09 | 74333518.25 | 0.301372E+09 | 89043751.33 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.216703E+09 | 0.140787E+09 | 75915802.54 | 0.360576E+09 | 0.105575E+09 |
February | 0.177068E+09 | 0.102456E+09 | 74612322.45 | 0.311537E+09 | 79288494.79 |
March | 0.150514E+09 | 63635981.91 | 86877711.25 | 0.269263E+09 | 72481061.21 |
April | 99045076.06 | 17368684.91 | 81676391.15 | 0.194140E+09 | 48142531.26 |
May | 82014252.54 | 1774358.72 | 80239893.83 | 0.174679E+09 | 23841651.58 |
June | 75671092.72 | 142804.05 | 75528288.67 | 0.171886E+09 | 10643873.16 |
July | 83723978.17 | 776048.19 | 82947929.98 | 0.199446E+09 | 16529278.23 |
August | 95024047.30 | 8018648.24 | 87005399.06 | 0.215567E+09 | 11171798.86 |
September | 0.117719E+09 | 28847403.34 | 88872024.82 | 0.266972E+09 | 19150351.50 |
October | 0.167284E+09 | 78484532.51 | 88799494.88 | 0.338770E+09 | 31421210.59 |
November | 0.184193E+09 | 0.102800E+09 | 81392783.75 | 0.336012E+09 | 53740885.88 |
December | 0.208841E+09 | 0.131725E+09 | 77115814.47 | 0.354953E+09 | 92674283.10 |
Annual Sum or Average | 0.165780E+10 | 0.676816E+09 | 0.980984E+09 | 0.319380E+10 | 0.564660E+09 |
Minimum of Months | 75671092.72 | 142804.05 | 74612322.45 | 0.171886E+09 | 10643873.16 |
Maximum of Months | 0.216703E+09 | 0.140787E+09 | 88872024.82 | 0.360576E+09 | 0.105575E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.181252E+09 | 0.117756E+09 | 63496794.47 | 0.301600E+09 | 88642111.52 |
February | 0.148101E+09 | 85694897.39 | 62406549.68 | 0.260519E+09 | 66498149.90 |
March | 0.125891E+09 | 53225820.30 | 72665452.91 | 0.225079E+09 | 60649293.74 |
April | 82842367.82 | 14527355.03 | 68315012.79 | 0.162658E+09 | 40146377.03 |
May | 68597603.70 | 1484092.73 | 67113510.97 | 0.146883E+09 | 19572767.45 |
June | 63292116.53 | 119442.84 | 63172673.69 | 0.144872E+09 | 8731398.20 |
July | 70027636.61 | 649095.06 | 69378541.55 | 0.167972E+09 | 13616766.19 |
August | 79479136.08 | 6706883.71 | 72772252.37 | 0.181439E+09 | 9153326.11 |
September | 98461796.94 | 24128278.69 | 74333518.25 | 0.224276E+09 | 15902530.57 |
October | 0.139918E+09 | 65645307.86 | 74272853.43 | 0.284007E+09 | 25994624.62 |
November | 0.154061E+09 | 85982896.30 | 68077800.51 | 0.281239E+09 | 44865269.50 |
December | 0.174677E+09 | 0.110176E+09 | 64500497.36 | 0.296831E+09 | 77813070.33 |
Annual Sum or Average | 0.138660E+10 | 0.566096E+09 | 0.820505E+09 | 0.267737E+10 | 0.471586E+09 |
Minimum of Months | 63292116.53 | 119442.84 | 62406549.68 | 0.144872E+09 | 8731398.20 |
Maximum of Months | 0.181252E+09 | 0.117756E+09 | 74333518.25 | 0.301600E+09 | 88642111.52 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.181252E+09 | 0.117756E+09 | 63496794.47 | 0.301600E+09 | 88642111.52 |
February | 0.148101E+09 | 85694897.39 | 62406549.68 | 0.260519E+09 | 66498149.90 |
March | 0.125891E+09 | 53225820.30 | 72665452.91 | 0.225079E+09 | 60649293.74 |
April | 82842367.82 | 14527355.03 | 68315012.79 | 0.162658E+09 | 40146377.03 |
May | 68597603.70 | 1484092.73 | 67113510.97 | 0.146883E+09 | 19572767.45 |
June | 63292116.53 | 119442.84 | 63172673.69 | 0.144872E+09 | 8731398.20 |
July | 70027636.61 | 649095.06 | 69378541.55 | 0.167972E+09 | 13616766.19 |
August | 79479136.08 | 6706883.71 | 72772252.37 | 0.181439E+09 | 9153326.11 |
September | 98461796.94 | 24128278.69 | 74333518.25 | 0.224276E+09 | 15902530.57 |
October | 0.139918E+09 | 65645307.86 | 74272853.43 | 0.284007E+09 | 25994624.62 |
November | 0.154061E+09 | 85982896.30 | 68077800.51 | 0.281239E+09 | 44865269.50 |
December | 0.174677E+09 | 0.110176E+09 | 64500497.36 | 0.296831E+09 | 77813070.33 |
Annual Sum or Average | 0.138660E+10 | 0.566096E+09 | 0.820505E+09 | 0.267737E+10 | 0.471586E+09 |
Minimum of Months | 63292116.53 | 119442.84 | 62406549.68 | 0.144872E+09 | 8731398.20 |
Maximum of Months | 0.181252E+09 | 0.117756E+09 | 74333518.25 | 0.301600E+09 | 88642111.52 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.216703E+09 | 0.140787E+09 | 75915802.54 | 0.360848E+09 | 0.105100E+09 |
February | 0.177068E+09 | 0.102456E+09 | 74612322.45 | 0.311772E+09 | 78890179.10 |
March | 0.150514E+09 | 63635981.91 | 86877711.25 | 0.269493E+09 | 72095437.47 |
April | 99045076.06 | 17368684.91 | 81676391.15 | 0.194292E+09 | 47873408.03 |
May | 82014252.54 | 1774358.72 | 80239893.83 | 0.174843E+09 | 23626610.15 |
June | 75671092.72 | 142804.05 | 75528288.67 | 0.172084E+09 | 10522169.80 |
July | 83723978.17 | 776048.19 | 82947929.98 | 0.199607E+09 | 16382939.73 |
August | 95024047.30 | 8018648.24 | 87005399.06 | 0.215746E+09 | 11019098.33 |
September | 0.117719E+09 | 28847403.34 | 88872024.82 | 0.267142E+09 | 19024920.91 |
October | 0.167284E+09 | 78484532.51 | 88799494.88 | 0.338901E+09 | 31199805.18 |
November | 0.184193E+09 | 0.102800E+09 | 81392783.75 | 0.336179E+09 | 53466269.55 |
December | 0.208841E+09 | 0.131725E+09 | 77115814.47 | 0.355191E+09 | 92207217.67 |
Annual Sum or Average | 0.165780E+10 | 0.676816E+09 | 0.980984E+09 | 0.319610E+10 | 0.561408E+09 |
Minimum of Months | 75671092.72 | 142804.05 | 74612322.45 | 0.172084E+09 | 10522169.80 |
Maximum of Months | 0.216703E+09 | 0.140787E+09 | 88872024.82 | 0.360848E+09 | 0.105100E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.181252E+09 | 0.117756E+09 | 63496794.47 | 0.302072E+09 | 87650040.05 |
February | 0.148101E+09 | 85694897.39 | 62406549.68 | 0.260891E+09 | 65675599.87 |
March | 0.125891E+09 | 53225820.30 | 72665452.91 | 0.225333E+09 | 59917939.24 |
April | 82842367.82 | 14527355.03 | 68315012.79 | 0.162679E+09 | 39815130.50 |
May | 68597603.70 | 1484092.73 | 67113510.97 | 0.146780E+09 | 19500320.11 |
June | 63292116.53 | 119442.84 | 63172673.69 | 0.144568E+09 | 8794852.00 |
July | 70027636.61 | 649095.06 | 69378541.55 | 0.167642E+09 | 13827923.64 |
August | 79479136.08 | 6706883.71 | 72772252.37 | 0.181120E+09 | 9269013.43 |
September | 98461796.94 | 24128278.69 | 74333518.25 | 0.223911E+09 | 16052767.47 |
October | 0.139918E+09 | 65645307.86 | 74272853.43 | 0.283861E+09 | 26042582.46 |
November | 0.154061E+09 | 85982896.30 | 68077800.51 | 0.281338E+09 | 44552919.48 |
December | 0.174677E+09 | 0.110176E+09 | 64500497.36 | 0.297217E+09 | 76871697.21 |
Annual Sum or Average | 0.138660E+10 | 0.566096E+09 | 0.820505E+09 | 0.267741E+10 | 0.467971E+09 |
Minimum of Months | 63292116.53 | 119442.84 | 62406549.68 | 0.144568E+09 | 8794852.00 |
Maximum of Months | 0.181252E+09 | 0.117756E+09 | 74333518.25 | 0.302072E+09 | 87650040.05 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.181252E+09 | 0.117756E+09 | 63496794.47 | 0.302072E+09 | 87650040.05 |
February | 0.148101E+09 | 85694897.39 | 62406549.68 | 0.260891E+09 | 65675599.87 |
March | 0.125891E+09 | 53225820.30 | 72665452.91 | 0.225333E+09 | 59917939.24 |
April | 82842367.82 | 14527355.03 | 68315012.79 | 0.162679E+09 | 39815130.50 |
May | 68597603.70 | 1484092.73 | 67113510.97 | 0.146780E+09 | 19500320.11 |
June | 63292116.53 | 119442.84 | 63172673.69 | 0.144568E+09 | 8794852.00 |
July | 70027636.61 | 649095.06 | 69378541.55 | 0.167642E+09 | 13827923.64 |
August | 79479136.08 | 6706883.71 | 72772252.37 | 0.181120E+09 | 9269013.43 |
September | 98461796.94 | 24128278.69 | 74333518.25 | 0.223911E+09 | 16052767.47 |
October | 0.139918E+09 | 65645307.86 | 74272853.43 | 0.283861E+09 | 26042582.46 |
November | 0.154061E+09 | 85982896.30 | 68077800.51 | 0.281338E+09 | 44552919.48 |
December | 0.174677E+09 | 0.110176E+09 | 64500497.36 | 0.297217E+09 | 76871697.21 |
Annual Sum or Average | 0.138660E+10 | 0.566096E+09 | 0.820505E+09 | 0.267741E+10 | 0.467971E+09 |
Minimum of Months | 63292116.53 | 119442.84 | 62406549.68 | 0.144568E+09 | 8794852.00 |
Maximum of Months | 0.181252E+09 | 0.117756E+09 | 74333518.25 | 0.302072E+09 | 87650040.05 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.216703E+09 | 0.140787E+09 | 75915802.54 | 0.361409E+09 | 0.103934E+09 |
February | 0.177068E+09 | 0.102456E+09 | 74612322.45 | 0.312215E+09 | 77928722.74 |
March | 0.150514E+09 | 63635981.91 | 86877711.25 | 0.269795E+09 | 71241458.47 |
April | 99045076.06 | 17368684.91 | 81676391.15 | 0.194316E+09 | 47491090.80 |
May | 82014252.54 | 1774358.72 | 80239893.83 | 0.174718E+09 | 23550143.00 |
June | 75671092.72 | 142804.05 | 75528288.67 | 0.171720E+09 | 10603287.37 |
July | 83723978.17 | 776048.19 | 82947929.98 | 0.199212E+09 | 16639495.43 |
August | 95024047.30 | 8018648.24 | 87005399.06 | 0.215366E+09 | 11165534.54 |
September | 0.117719E+09 | 28847403.34 | 88872024.82 | 0.266708E+09 | 19212048.61 |
October | 0.167284E+09 | 78484532.51 | 88799494.88 | 0.338726E+09 | 31265136.90 |
November | 0.184193E+09 | 0.102800E+09 | 81392783.75 | 0.336296E+09 | 53104601.61 |
December | 0.208841E+09 | 0.131725E+09 | 77115814.47 | 0.355652E+09 | 91102627.17 |
Annual Sum or Average | 0.165780E+10 | 0.676816E+09 | 0.980984E+09 | 0.319613E+10 | 0.557238E+09 |
Minimum of Months | 75671092.72 | 142804.05 | 74612322.45 | 0.171720E+09 | 10603287.37 |
Maximum of Months | 0.216703E+09 | 0.140787E+09 | 88872024.82 | 0.361409E+09 | 0.103934E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.181252E+09 | 0.117756E+09 | 63496794.47 | 0.302130E+09 | 84240915.53 |
February | 0.148101E+09 | 85694897.39 | 62406549.68 | 0.260669E+09 | 62789800.48 |
March | 0.125891E+09 | 53225820.30 | 72665452.91 | 0.224273E+09 | 57270229.20 |
April | 82842367.82 | 14527355.03 | 68315012.79 | 0.160847E+09 | 38843641.58 |
May | 68597603.70 | 1484092.73 | 67113510.97 | 0.144016E+09 | 20018255.55 |
June | 63292116.53 | 119442.84 | 63172673.69 | 0.140573E+09 | 9600496.45 |
July | 70027636.61 | 649095.06 | 69378541.55 | 0.163438E+09 | 15539071.87 |
August | 79479136.08 | 6706883.71 | 72772252.37 | 0.177250E+09 | 10678277.18 |
September | 98461796.94 | 24128278.69 | 74333518.25 | 0.219706E+09 | 17432839.91 |
October | 0.139918E+09 | 65645307.86 | 74272853.43 | 0.281323E+09 | 27348956.97 |
November | 0.154061E+09 | 85982896.30 | 68077800.51 | 0.280156E+09 | 44043464.98 |
December | 0.174677E+09 | 0.110176E+09 | 64500497.36 | 0.297281E+09 | 73870061.38 |
Annual Sum or Average | 0.138660E+10 | 0.566096E+09 | 0.820505E+09 | 0.265166E+10 | 0.461676E+09 |
Minimum of Months | 63292116.53 | 119442.84 | 62406549.68 | 0.140573E+09 | 9600496.45 |
Maximum of Months | 0.181252E+09 | 0.117756E+09 | 74333518.25 | 0.302130E+09 | 84240915.53 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.181252E+09 | 0.117756E+09 | 63496794.47 | 0.302130E+09 | 84240915.53 |
February | 0.148101E+09 | 85694897.39 | 62406549.68 | 0.260669E+09 | 62789800.48 |
March | 0.125891E+09 | 53225820.30 | 72665452.91 | 0.224273E+09 | 57270229.20 |
April | 82842367.82 | 14527355.03 | 68315012.79 | 0.160847E+09 | 38843641.58 |
May | 68597603.70 | 1484092.73 | 67113510.97 | 0.144016E+09 | 20018255.55 |
June | 63292116.53 | 119442.84 | 63172673.69 | 0.140573E+09 | 9600496.45 |
July | 70027636.61 | 649095.06 | 69378541.55 | 0.163438E+09 | 15539071.87 |
August | 79479136.08 | 6706883.71 | 72772252.37 | 0.177250E+09 | 10678277.18 |
September | 98461796.94 | 24128278.69 | 74333518.25 | 0.219706E+09 | 17432839.91 |
October | 0.139918E+09 | 65645307.86 | 74272853.43 | 0.281323E+09 | 27348956.97 |
November | 0.154061E+09 | 85982896.30 | 68077800.51 | 0.280156E+09 | 44043464.98 |
December | 0.174677E+09 | 0.110176E+09 | 64500497.36 | 0.297281E+09 | 73870061.38 |
Annual Sum or Average | 0.138660E+10 | 0.566096E+09 | 0.820505E+09 | 0.265166E+10 | 0.461676E+09 |
Minimum of Months | 63292116.53 | 119442.84 | 62406549.68 | 0.140573E+09 | 9600496.45 |
Maximum of Months | 0.181252E+09 | 0.117756E+09 | 74333518.25 | 0.302130E+09 | 84240915.53 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.216703E+09 | 0.140787E+09 | 75915802.54 | 0.361468E+09 | 99919306.06 |
February | 0.177068E+09 | 0.102456E+09 | 74612322.45 | 0.311937E+09 | 74548875.33 |
March | 0.150514E+09 | 63635981.91 | 86877711.25 | 0.268516E+09 | 68135962.67 |
April | 99045076.06 | 17368684.91 | 81676391.15 | 0.192112E+09 | 46355057.12 |
May | 82014252.54 | 1774358.72 | 80239893.83 | 0.171415E+09 | 24172953.45 |
June | 75671092.72 | 142804.05 | 75528288.67 | 0.166969E+09 | 11581266.37 |
July | 83723978.17 | 776048.19 | 82947929.98 | 0.194184E+09 | 18676295.98 |
August | 95024047.30 | 8018648.24 | 87005399.06 | 0.210770E+09 | 12872314.17 |
September | 0.117719E+09 | 28847403.34 | 88872024.82 | 0.261698E+09 | 20875296.80 |
October | 0.167284E+09 | 78484532.51 | 88799494.88 | 0.335675E+09 | 32820080.88 |
November | 0.184193E+09 | 0.102800E+09 | 81392783.75 | 0.334868E+09 | 52518396.23 |
December | 0.208841E+09 | 0.131725E+09 | 77115814.47 | 0.355719E+09 | 87570683.16 |
Annual Sum or Average | 0.165780E+10 | 0.676816E+09 | 0.980984E+09 | 0.316533E+10 | 0.550046E+09 |
Minimum of Months | 75671092.72 | 142804.05 | 74612322.45 | 0.166969E+09 | 11581266.37 |
Maximum of Months | 0.216703E+09 | 0.140787E+09 | 88872024.82 | 0.361468E+09 | 99919306.06 |
Report: WindowZoneSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 720.08 | 215.04 | 433.39 | 281.56 | 151.83 | 0.00 | 0.00 |
February | 688.45 | 178.43 | 392.07 | 226.86 | 165.21 | 0.00 | 0.00 |
March | 536.85 | 147.91 | 301.02 | 127.27 | 173.75 | 0.00 | 0.00 |
April | 400.54 | 99.30 | 204.69 | 35.89 | 168.79 | 0.00 | 0.00 |
May | 348.61 | 46.14 | 164.02 | 3.55 | 160.47 | 0.00 | 0.00 |
June | 358.22 | 21.05 | 156.38 | 0.30 | 156.09 | 0.00 | 0.00 |
July | 402.03 | 30.02 | 167.44 | 1.55 | 165.89 | 0.00 | 0.00 |
August | 432.25 | 21.62 | 190.04 | 16.04 | 174.01 | 0.00 | 0.00 |
September | 556.37 | 37.84 | 243.28 | 59.62 | 183.66 | 0.00 | 0.00 |
October | 678.15 | 59.22 | 334.56 | 156.96 | 177.59 | 0.00 | 0.00 |
November | 693.71 | 110.63 | 380.65 | 212.45 | 168.21 | 0.00 | 0.00 |
December | 708.93 | 187.35 | 417.67 | 263.44 | 154.23 | 0.00 | 0.00 |
Annual Sum or Average | 542.95 | 95.85 | 281.59 | 114.96 | 166.63 | 0.00 | 0.00 |
Minimum of Months | 348.61 | 21.05 | 156.38 | 0.30 | 151.83 | 0.00 | 0.00 |
Maximum of Months | 720.08 | 215.04 | 433.39 | 281.56 | 183.66 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 358.21 | 110.09 | 216.70 | 140.78 | 75.91 | 0.00 | 0.00 |
February | 342.73 | 91.54 | 196.03 | 113.43 | 82.60 | 0.00 | 0.00 |
March | 267.40 | 75.52 | 150.51 | 63.63 | 86.87 | 0.00 | 0.00 |
April | 200.69 | 49.95 | 102.34 | 17.95 | 84.40 | 0.00 | 0.00 |
May | 175.87 | 22.80 | 82.01 | 1.77 | 80.24 | 0.00 | 0.00 |
June | 181.44 | 10.50 | 78.19 | 0.15 | 78.04 | 0.00 | 0.00 |
July | 203.67 | 14.67 | 83.72 | 0.78 | 82.95 | 0.00 | 0.00 |
August | 218.71 | 10.45 | 95.02 | 8.02 | 87.00 | 0.00 | 0.00 |
September | 280.50 | 18.66 | 121.64 | 29.81 | 91.83 | 0.00 | 0.00 |
October | 340.16 | 29.14 | 167.28 | 78.48 | 88.80 | 0.00 | 0.00 |
November | 346.66 | 55.78 | 190.33 | 106.22 | 84.10 | 0.00 | 0.00 |
December | 353.14 | 95.87 | 208.83 | 131.72 | 77.11 | 0.00 | 0.00 |
Annual Sum or Average | 272.07 | 48.56 | 140.79 | 57.48 | 83.31 | 0.00 | 0.00 |
Minimum of Months | 175.87 | 10.45 | 78.19 | 0.15 | 75.91 | 0.00 | 0.00 |
Maximum of Months | 358.21 | 110.09 | 216.70 | 140.78 | 91.83 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 357.84 | 112.26 | 216.25 | 140.49 | 75.76 | 0.00 | 0.00 |
February | 342.31 | 94.27 | 195.63 | 113.20 | 82.43 | 0.00 | 0.00 |
March | 266.71 | 78.49 | 150.20 | 63.50 | 86.70 | 0.00 | 0.00 |
April | 199.40 | 54.69 | 102.13 | 17.91 | 84.22 | 0.00 | 0.00 |
May | 174.10 | 28.28 | 81.84 | 1.77 | 80.07 | 0.00 | 0.00 |
June | 175.72 | 13.73 | 78.03 | 0.15 | 77.88 | 0.00 | 0.00 |
July | 198.72 | 19.67 | 83.55 | 0.77 | 82.78 | 0.00 | 0.00 |
August | 214.22 | 14.64 | 94.83 | 8.00 | 86.82 | 0.00 | 0.00 |
September | 274.35 | 22.54 | 121.39 | 29.75 | 91.64 | 0.00 | 0.00 |
October | 338.20 | 35.65 | 166.94 | 78.32 | 88.61 | 0.00 | 0.00 |
November | 345.77 | 60.64 | 189.94 | 106.01 | 83.93 | 0.00 | 0.00 |
December | 352.61 | 98.86 | 208.41 | 131.45 | 76.96 | 0.00 | 0.00 |
Annual Sum or Average | 269.63 | 52.63 | 140.51 | 57.36 | 83.14 | 0.00 | 0.00 |
Minimum of Months | 174.10 | 13.73 | 78.03 | 0.15 | 75.76 | 0.00 | 0.00 |
Maximum of Months | 357.84 | 112.26 | 216.25 | 140.49 | 91.64 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 358.10 | 111.57 | 216.25 | 140.49 | 75.76 | 0.00 | 0.00 |
February | 342.53 | 93.69 | 195.63 | 113.20 | 82.43 | 0.00 | 0.00 |
March | 266.88 | 78.09 | 150.20 | 63.50 | 86.70 | 0.00 | 0.00 |
April | 199.40 | 54.77 | 102.13 | 17.91 | 84.22 | 0.00 | 0.00 |
May | 174.04 | 28.60 | 81.84 | 1.77 | 80.07 | 0.00 | 0.00 |
June | 175.44 | 14.16 | 78.03 | 0.15 | 77.88 | 0.00 | 0.00 |
July | 198.48 | 20.33 | 83.55 | 0.77 | 82.78 | 0.00 | 0.00 |
August | 214.02 | 15.14 | 94.83 | 8.00 | 86.82 | 0.00 | 0.00 |
September | 274.02 | 23.07 | 121.39 | 29.75 | 91.64 | 0.00 | 0.00 |
October | 338.11 | 36.15 | 166.94 | 78.32 | 88.61 | 0.00 | 0.00 |
November | 345.81 | 60.64 | 189.94 | 106.01 | 83.93 | 0.00 | 0.00 |
December | 352.78 | 98.34 | 208.41 | 131.45 | 76.96 | 0.00 | 0.00 |
Annual Sum or Average | 269.60 | 52.70 | 140.51 | 57.36 | 83.14 | 0.00 | 0.00 |
Minimum of Months | 174.04 | 14.16 | 78.03 | 0.15 | 75.76 | 0.00 | 0.00 |
Maximum of Months | 358.10 | 111.57 | 216.25 | 140.49 | 91.64 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 358.69 | 110.17 | 216.25 | 140.49 | 75.76 | 0.00 | 0.00 |
February | 343.10 | 92.34 | 195.63 | 113.20 | 82.43 | 0.00 | 0.00 |
March | 267.43 | 76.80 | 150.20 | 63.50 | 86.70 | 0.00 | 0.00 |
April | 199.77 | 53.73 | 102.13 | 17.91 | 84.22 | 0.00 | 0.00 |
May | 174.43 | 27.65 | 81.84 | 1.77 | 80.07 | 0.00 | 0.00 |
June | 176.00 | 13.48 | 78.03 | 0.15 | 77.88 | 0.00 | 0.00 |
July | 198.88 | 19.56 | 83.55 | 0.77 | 82.78 | 0.00 | 0.00 |
August | 214.47 | 14.33 | 94.83 | 8.00 | 86.82 | 0.00 | 0.00 |
September | 274.49 | 22.40 | 121.39 | 29.75 | 91.64 | 0.00 | 0.00 |
October | 338.39 | 35.22 | 166.94 | 78.32 | 88.61 | 0.00 | 0.00 |
November | 346.20 | 59.58 | 189.94 | 106.01 | 83.93 | 0.00 | 0.00 |
December | 353.28 | 97.01 | 208.41 | 131.45 | 76.96 | 0.00 | 0.00 |
Annual Sum or Average | 270.07 | 51.68 | 140.51 | 57.36 | 83.14 | 0.00 | 0.00 |
Minimum of Months | 174.43 | 13.48 | 78.03 | 0.15 | 75.76 | 0.00 | 0.00 |
Maximum of Months | 358.69 | 110.17 | 216.25 | 140.49 | 91.64 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 720.17 | 213.16 | 432.50 | 280.99 | 151.52 | 0.00 | 0.00 |
February | 688.79 | 177.56 | 391.26 | 226.39 | 164.87 | 0.00 | 0.00 |
March | 537.40 | 146.96 | 300.40 | 127.01 | 173.39 | 0.00 | 0.00 |
April | 400.17 | 101.55 | 204.27 | 35.82 | 168.45 | 0.00 | 0.00 |
May | 348.02 | 49.64 | 163.69 | 3.54 | 160.15 | 0.00 | 0.00 |
June | 353.04 | 23.36 | 156.06 | 0.29 | 155.77 | 0.00 | 0.00 |
July | 397.08 | 34.85 | 167.10 | 1.55 | 165.55 | 0.00 | 0.00 |
August | 429.20 | 24.10 | 189.65 | 16.00 | 173.65 | 0.00 | 0.00 |
September | 549.75 | 41.18 | 242.78 | 59.49 | 183.29 | 0.00 | 0.00 |
October | 676.39 | 65.13 | 333.87 | 156.64 | 177.23 | 0.00 | 0.00 |
November | 693.32 | 113.13 | 379.87 | 212.01 | 167.86 | 0.00 | 0.00 |
December | 708.93 | 187.43 | 416.81 | 262.90 | 153.91 | 0.00 | 0.00 |
Annual Sum or Average | 541.12 | 97.83 | 281.01 | 114.73 | 166.29 | 0.00 | 0.00 |
Minimum of Months | 348.02 | 23.36 | 156.06 | 0.29 | 151.52 | 0.00 | 0.00 |
Maximum of Months | 720.17 | 213.16 | 432.50 | 280.99 | 183.29 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 359.66 | 105.91 | 216.25 | 140.49 | 75.76 | 0.00 | 0.00 |
February | 343.99 | 88.03 | 195.63 | 113.20 | 82.43 | 0.00 | 0.00 |
March | 268.46 | 72.59 | 150.20 | 63.50 | 86.70 | 0.00 | 0.00 |
April | 200.31 | 49.73 | 102.13 | 17.91 | 84.22 | 0.00 | 0.00 |
May | 174.79 | 23.65 | 81.84 | 1.77 | 80.07 | 0.00 | 0.00 |
June | 177.97 | 10.92 | 78.03 | 0.15 | 77.88 | 0.00 | 0.00 |
July | 199.79 | 16.43 | 83.55 | 0.77 | 82.78 | 0.00 | 0.00 |
August | 215.85 | 11.10 | 94.83 | 8.00 | 86.82 | 0.00 | 0.00 |
September | 275.94 | 19.74 | 121.39 | 29.75 | 91.64 | 0.00 | 0.00 |
October | 338.47 | 31.28 | 166.94 | 78.32 | 88.61 | 0.00 | 0.00 |
November | 346.53 | 55.53 | 189.94 | 106.01 | 83.93 | 0.00 | 0.00 |
December | 354.02 | 93.00 | 208.41 | 131.45 | 76.96 | 0.00 | 0.00 |
Annual Sum or Average | 270.95 | 47.99 | 140.51 | 57.36 | 83.14 | 0.00 | 0.00 |
Minimum of Months | 174.79 | 10.92 | 78.03 | 0.15 | 75.76 | 0.00 | 0.00 |
Maximum of Months | 359.66 | 105.91 | 216.25 | 140.49 | 91.64 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 359.93 | 105.43 | 216.25 | 140.49 | 75.76 | 0.00 | 0.00 |
February | 344.25 | 87.59 | 195.63 | 113.20 | 82.43 | 0.00 | 0.00 |
March | 268.69 | 72.21 | 150.20 | 63.50 | 86.70 | 0.00 | 0.00 |
April | 200.47 | 49.45 | 102.13 | 17.91 | 84.22 | 0.00 | 0.00 |
May | 174.96 | 23.44 | 81.84 | 1.77 | 80.07 | 0.00 | 0.00 |
June | 178.17 | 10.80 | 78.03 | 0.15 | 77.88 | 0.00 | 0.00 |
July | 199.95 | 16.28 | 83.55 | 0.77 | 82.78 | 0.00 | 0.00 |
August | 216.03 | 10.95 | 94.83 | 8.00 | 86.82 | 0.00 | 0.00 |
September | 276.12 | 19.61 | 121.39 | 29.75 | 91.64 | 0.00 | 0.00 |
October | 338.60 | 31.06 | 166.94 | 78.32 | 88.61 | 0.00 | 0.00 |
November | 346.70 | 55.25 | 189.94 | 106.01 | 83.93 | 0.00 | 0.00 |
December | 354.26 | 92.53 | 208.41 | 131.45 | 76.96 | 0.00 | 0.00 |
Annual Sum or Average | 271.15 | 47.71 | 140.51 | 57.36 | 83.14 | 0.00 | 0.00 |
Minimum of Months | 174.96 | 10.80 | 78.03 | 0.15 | 75.76 | 0.00 | 0.00 |
Maximum of Months | 359.93 | 105.43 | 216.25 | 140.49 | 91.64 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 360.50 | 104.25 | 216.25 | 140.49 | 75.76 | 0.00 | 0.00 |
February | 344.74 | 86.51 | 195.63 | 113.20 | 82.43 | 0.00 | 0.00 |
March | 268.99 | 71.34 | 150.20 | 63.50 | 86.70 | 0.00 | 0.00 |
April | 200.49 | 49.04 | 102.13 | 17.91 | 84.22 | 0.00 | 0.00 |
May | 174.83 | 23.35 | 81.84 | 1.77 | 80.07 | 0.00 | 0.00 |
June | 177.80 | 10.88 | 78.03 | 0.15 | 77.88 | 0.00 | 0.00 |
July | 199.56 | 16.54 | 83.55 | 0.77 | 82.78 | 0.00 | 0.00 |
August | 215.65 | 11.09 | 94.83 | 8.00 | 86.82 | 0.00 | 0.00 |
September | 275.67 | 19.80 | 121.39 | 29.75 | 91.64 | 0.00 | 0.00 |
October | 338.43 | 31.12 | 166.94 | 78.32 | 88.61 | 0.00 | 0.00 |
November | 346.83 | 54.86 | 189.94 | 106.01 | 83.93 | 0.00 | 0.00 |
December | 354.72 | 91.42 | 208.41 | 131.45 | 76.96 | 0.00 | 0.00 |
Annual Sum or Average | 271.15 | 47.35 | 140.51 | 57.36 | 83.14 | 0.00 | 0.00 |
Minimum of Months | 174.83 | 10.88 | 78.03 | 0.15 | 75.76 | 0.00 | 0.00 |
Maximum of Months | 360.50 | 104.25 | 216.25 | 140.49 | 91.64 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 360.56 | 100.21 | 216.25 | 140.49 | 75.76 | 0.00 | 0.00 |
February | 344.44 | 82.73 | 195.63 | 113.20 | 82.43 | 0.00 | 0.00 |
March | 267.72 | 68.20 | 150.20 | 63.50 | 86.70 | 0.00 | 0.00 |
April | 198.23 | 47.86 | 102.13 | 17.91 | 84.22 | 0.00 | 0.00 |
May | 171.54 | 23.97 | 81.84 | 1.77 | 80.07 | 0.00 | 0.00 |
June | 172.88 | 11.88 | 78.03 | 0.15 | 77.88 | 0.00 | 0.00 |
July | 194.54 | 18.58 | 83.55 | 0.77 | 82.78 | 0.00 | 0.00 |
August | 211.05 | 12.78 | 94.83 | 8.00 | 86.82 | 0.00 | 0.00 |
September | 270.49 | 21.50 | 121.39 | 29.75 | 91.64 | 0.00 | 0.00 |
October | 335.39 | 32.68 | 166.94 | 78.32 | 88.61 | 0.00 | 0.00 |
November | 345.36 | 54.25 | 189.94 | 106.01 | 83.93 | 0.00 | 0.00 |
December | 354.79 | 87.85 | 208.41 | 131.45 | 76.96 | 0.00 | 0.00 |
Annual Sum or Average | 268.54 | 46.72 | 140.51 | 57.36 | 83.14 | 0.00 | 0.00 |
Minimum of Months | 171.54 | 11.88 | 78.03 | 0.15 | 75.76 | 0.00 | 0.00 |
Maximum of Months | 360.56 | 100.21 | 216.25 | 140.49 | 91.64 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.192867E+10 | 0.575958E+09 | 0.116080E+10 | 0.754143E+09 | 0.406653E+09 | 0.00 | 0.00 |
February | 0.166550E+10 | 0.431668E+09 | 0.948487E+09 | 0.548817E+09 | 0.399671E+09 | 0.00 | 0.00 |
March | 0.143789E+10 | 0.396168E+09 | 0.806246E+09 | 0.340875E+09 | 0.465372E+09 | 0.00 | 0.00 |
April | 0.103820E+10 | 0.257385E+09 | 0.530548E+09 | 93037654.60 | 0.437510E+09 | 0.00 | 0.00 |
May | 0.933707E+09 | 0.123592E+09 | 0.439320E+09 | 9504586.80 | 0.429816E+09 | 0.00 | 0.00 |
June | 0.928500E+09 | 54559704.95 | 0.405342E+09 | 764948.74 | 0.404577E+09 | 0.00 | 0.00 |
July | 0.107681E+10 | 80401103.96 | 0.448479E+09 | 4157004.61 | 0.444322E+09 | 0.00 | 0.00 |
August | 0.115774E+10 | 57901155.83 | 0.509009E+09 | 42952948.32 | 0.466056E+09 | 0.00 | 0.00 |
September | 0.144211E+10 | 98082980.76 | 0.630580E+09 | 0.154525E+09 | 0.476055E+09 | 0.00 | 0.00 |
October | 0.181636E+10 | 0.158604E+09 | 0.896079E+09 | 0.420413E+09 | 0.475666E+09 | 0.00 | 0.00 |
November | 0.179809E+10 | 0.286766E+09 | 0.986652E+09 | 0.550661E+09 | 0.435991E+09 | 0.00 | 0.00 |
December | 0.189881E+10 | 0.501794E+09 | 0.111868E+10 | 0.705602E+09 | 0.413081E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.171224E+11 | 0.302288E+10 | 0.888022E+10 | 0.362545E+10 | 0.525477E+10 | 0.00 | 0.00 |
Minimum of Months | 0.928500E+09 | 54559704.95 | 0.405342E+09 | 764948.74 | 0.399671E+09 | 0.00 | 0.00 |
Maximum of Months | 0.192867E+10 | 0.575958E+09 | 0.116080E+10 | 0.754143E+09 | 0.476055E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.959418E+09 | 0.294855E+09 | 0.580398E+09 | 0.377072E+09 | 0.203327E+09 | 0.00 | 0.00 |
February | 0.829132E+09 | 0.221452E+09 | 0.474244E+09 | 0.274408E+09 | 0.199835E+09 | 0.00 | 0.00 |
March | 0.716191E+09 | 0.202263E+09 | 0.403123E+09 | 0.170437E+09 | 0.232686E+09 | 0.00 | 0.00 |
April | 0.520178E+09 | 0.129464E+09 | 0.265274E+09 | 46518827.30 | 0.218755E+09 | 0.00 | 0.00 |
May | 0.471060E+09 | 61066684.79 | 0.219660E+09 | 4752293.40 | 0.214908E+09 | 0.00 | 0.00 |
June | 0.470289E+09 | 27212730.89 | 0.202671E+09 | 382474.37 | 0.202289E+09 | 0.00 | 0.00 |
July | 0.545517E+09 | 39301700.14 | 0.224239E+09 | 2078502.30 | 0.222161E+09 | 0.00 | 0.00 |
August | 0.585789E+09 | 27988904.38 | 0.254504E+09 | 21476474.16 | 0.233028E+09 | 0.00 | 0.00 |
September | 0.727054E+09 | 48370390.47 | 0.315290E+09 | 77262462.94 | 0.238027E+09 | 0.00 | 0.00 |
October | 0.911081E+09 | 78056432.12 | 0.448039E+09 | 0.210206E+09 | 0.237833E+09 | 0.00 | 0.00 |
November | 0.898535E+09 | 0.144574E+09 | 0.493326E+09 | 0.275330E+09 | 0.217996E+09 | 0.00 | 0.00 |
December | 0.945840E+09 | 0.256784E+09 | 0.559342E+09 | 0.352801E+09 | 0.206541E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.858008E+10 | 0.153139E+10 | 0.444011E+10 | 0.181273E+10 | 0.262738E+10 | 0.00 | 0.00 |
Minimum of Months | 0.470289E+09 | 27212730.89 | 0.202671E+09 | 382474.37 | 0.199835E+09 | 0.00 | 0.00 |
Maximum of Months | 0.959418E+09 | 0.294855E+09 | 0.580398E+09 | 0.377072E+09 | 0.238027E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.958436E+09 | 0.300670E+09 | 0.579208E+09 | 0.376298E+09 | 0.202909E+09 | 0.00 | 0.00 |
February | 0.828110E+09 | 0.228053E+09 | 0.473271E+09 | 0.273845E+09 | 0.199425E+09 | 0.00 | 0.00 |
March | 0.714369E+09 | 0.210234E+09 | 0.402296E+09 | 0.170088E+09 | 0.232209E+09 | 0.00 | 0.00 |
April | 0.516849E+09 | 0.141761E+09 | 0.264730E+09 | 46423394.97 | 0.218306E+09 | 0.00 | 0.00 |
May | 0.466321E+09 | 75743658.83 | 0.219209E+09 | 4742544.18 | 0.214467E+09 | 0.00 | 0.00 |
June | 0.455461E+09 | 35579186.73 | 0.202255E+09 | 381689.73 | 0.201874E+09 | 0.00 | 0.00 |
July | 0.532243E+09 | 52691434.23 | 0.223779E+09 | 2074238.30 | 0.221705E+09 | 0.00 | 0.00 |
August | 0.573766E+09 | 39214445.18 | 0.253982E+09 | 21432415.65 | 0.232550E+09 | 0.00 | 0.00 |
September | 0.711115E+09 | 58419812.39 | 0.314643E+09 | 77103960.73 | 0.237539E+09 | 0.00 | 0.00 |
October | 0.905845E+09 | 95484382.90 | 0.447120E+09 | 0.209775E+09 | 0.237345E+09 | 0.00 | 0.00 |
November | 0.896236E+09 | 0.157180E+09 | 0.492314E+09 | 0.274766E+09 | 0.217548E+09 | 0.00 | 0.00 |
December | 0.944432E+09 | 0.264781E+09 | 0.558194E+09 | 0.352077E+09 | 0.206117E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.850318E+10 | 0.165981E+10 | 0.443100E+10 | 0.180901E+10 | 0.262199E+10 | 0.00 | 0.00 |
Minimum of Months | 0.455461E+09 | 35579186.73 | 0.202255E+09 | 381689.73 | 0.199425E+09 | 0.00 | 0.00 |
Maximum of Months | 0.958436E+09 | 0.300670E+09 | 0.579208E+09 | 0.376298E+09 | 0.237539E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.959139E+09 | 0.298822E+09 | 0.579208E+09 | 0.376298E+09 | 0.202909E+09 | 0.00 | 0.00 |
February | 0.828655E+09 | 0.226660E+09 | 0.473271E+09 | 0.273845E+09 | 0.199425E+09 | 0.00 | 0.00 |
March | 0.714803E+09 | 0.209162E+09 | 0.402296E+09 | 0.170088E+09 | 0.232209E+09 | 0.00 | 0.00 |
April | 0.516854E+09 | 0.141975E+09 | 0.264730E+09 | 46423394.97 | 0.218306E+09 | 0.00 | 0.00 |
May | 0.466157E+09 | 76594747.74 | 0.219209E+09 | 4742544.18 | 0.214467E+09 | 0.00 | 0.00 |
June | 0.454749E+09 | 36713674.12 | 0.202255E+09 | 381689.73 | 0.201874E+09 | 0.00 | 0.00 |
July | 0.531604E+09 | 54445047.10 | 0.223779E+09 | 2074238.30 | 0.221705E+09 | 0.00 | 0.00 |
August | 0.573226E+09 | 40547247.73 | 0.253982E+09 | 21432415.65 | 0.232550E+09 | 0.00 | 0.00 |
September | 0.710252E+09 | 59800908.87 | 0.314643E+09 | 77103960.73 | 0.237539E+09 | 0.00 | 0.00 |
October | 0.905588E+09 | 96816185.24 | 0.447120E+09 | 0.209775E+09 | 0.237345E+09 | 0.00 | 0.00 |
November | 0.896335E+09 | 0.157170E+09 | 0.492314E+09 | 0.274766E+09 | 0.217548E+09 | 0.00 | 0.00 |
December | 0.944896E+09 | 0.263396E+09 | 0.558194E+09 | 0.352077E+09 | 0.206117E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.850226E+10 | 0.166210E+10 | 0.443100E+10 | 0.180901E+10 | 0.262199E+10 | 0.00 | 0.00 |
Minimum of Months | 0.454749E+09 | 36713674.12 | 0.202255E+09 | 381689.73 | 0.199425E+09 | 0.00 | 0.00 |
Maximum of Months | 0.959139E+09 | 0.298822E+09 | 0.579208E+09 | 0.376298E+09 | 0.237539E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.960727E+09 | 0.295071E+09 | 0.579208E+09 | 0.376298E+09 | 0.202909E+09 | 0.00 | 0.00 |
February | 0.830033E+09 | 0.223396E+09 | 0.473271E+09 | 0.273845E+09 | 0.199425E+09 | 0.00 | 0.00 |
March | 0.716284E+09 | 0.205703E+09 | 0.402296E+09 | 0.170088E+09 | 0.232209E+09 | 0.00 | 0.00 |
April | 0.517815E+09 | 0.139272E+09 | 0.264730E+09 | 46423394.97 | 0.218306E+09 | 0.00 | 0.00 |
May | 0.467180E+09 | 74054389.28 | 0.219209E+09 | 4742544.18 | 0.214467E+09 | 0.00 | 0.00 |
June | 0.456204E+09 | 34937204.77 | 0.202255E+09 | 381689.73 | 0.201874E+09 | 0.00 | 0.00 |
July | 0.532681E+09 | 52402001.06 | 0.223779E+09 | 2074238.30 | 0.221705E+09 | 0.00 | 0.00 |
August | 0.574442E+09 | 38375222.24 | 0.253982E+09 | 21432415.65 | 0.232550E+09 | 0.00 | 0.00 |
September | 0.711482E+09 | 58055379.22 | 0.314643E+09 | 77103960.73 | 0.237539E+09 | 0.00 | 0.00 |
October | 0.906353E+09 | 94320079.70 | 0.447120E+09 | 0.209775E+09 | 0.237345E+09 | 0.00 | 0.00 |
November | 0.897352E+09 | 0.154425E+09 | 0.492314E+09 | 0.274766E+09 | 0.217548E+09 | 0.00 | 0.00 |
December | 0.946225E+09 | 0.259833E+09 | 0.558194E+09 | 0.352077E+09 | 0.206117E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.851678E+10 | 0.162984E+10 | 0.443100E+10 | 0.180901E+10 | 0.262199E+10 | 0.00 | 0.00 |
Minimum of Months | 0.456204E+09 | 34937204.77 | 0.202255E+09 | 381689.73 | 0.199425E+09 | 0.00 | 0.00 |
Maximum of Months | 0.960727E+09 | 0.295071E+09 | 0.579208E+09 | 0.376298E+09 | 0.237539E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.192889E+10 | 0.570930E+09 | 0.115842E+10 | 0.752596E+09 | 0.405819E+09 | 0.00 | 0.00 |
February | 0.166633E+10 | 0.429563E+09 | 0.946541E+09 | 0.547691E+09 | 0.398851E+09 | 0.00 | 0.00 |
March | 0.143938E+10 | 0.393620E+09 | 0.804592E+09 | 0.340175E+09 | 0.464417E+09 | 0.00 | 0.00 |
April | 0.103723E+10 | 0.263206E+09 | 0.529460E+09 | 92846789.93 | 0.436613E+09 | 0.00 | 0.00 |
May | 0.932135E+09 | 0.132964E+09 | 0.438419E+09 | 9485088.36 | 0.428934E+09 | 0.00 | 0.00 |
June | 0.915084E+09 | 60540417.64 | 0.404511E+09 | 763379.46 | 0.403747E+09 | 0.00 | 0.00 |
July | 0.106353E+10 | 93355460.70 | 0.447559E+09 | 4148476.60 | 0.443410E+09 | 0.00 | 0.00 |
August | 0.114956E+10 | 64548025.95 | 0.507965E+09 | 42864831.31 | 0.465100E+09 | 0.00 | 0.00 |
September | 0.142496E+10 | 0.106743E+09 | 0.629286E+09 | 0.154208E+09 | 0.475078E+09 | 0.00 | 0.00 |
October | 0.181166E+10 | 0.174443E+09 | 0.894241E+09 | 0.419550E+09 | 0.474690E+09 | 0.00 | 0.00 |
November | 0.179707E+10 | 0.293237E+09 | 0.984628E+09 | 0.549531E+09 | 0.435097E+09 | 0.00 | 0.00 |
December | 0.189880E+10 | 0.502007E+09 | 0.111639E+10 | 0.704155E+09 | 0.412234E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.170646E+11 | 0.308516E+10 | 0.886200E+10 | 0.361801E+10 | 0.524399E+10 | 0.00 | 0.00 |
Minimum of Months | 0.915084E+09 | 60540417.64 | 0.404511E+09 | 763379.46 | 0.398851E+09 | 0.00 | 0.00 |
Maximum of Months | 0.192889E+10 | 0.570930E+09 | 0.115842E+10 | 0.752596E+09 | 0.475078E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.963321E+09 | 0.283662E+09 | 0.579208E+09 | 0.376298E+09 | 0.202909E+09 | 0.00 | 0.00 |
February | 0.832182E+09 | 0.212960E+09 | 0.473271E+09 | 0.273845E+09 | 0.199425E+09 | 0.00 | 0.00 |
March | 0.719038E+09 | 0.194435E+09 | 0.402296E+09 | 0.170088E+09 | 0.232209E+09 | 0.00 | 0.00 |
April | 0.519205E+09 | 0.128891E+09 | 0.264730E+09 | 46423394.97 | 0.218306E+09 | 0.00 | 0.00 |
May | 0.468168E+09 | 63349019.61 | 0.219209E+09 | 4742544.18 | 0.214467E+09 | 0.00 | 0.00 |
June | 0.461292E+09 | 28309573.16 | 0.202255E+09 | 381689.73 | 0.201874E+09 | 0.00 | 0.00 |
July | 0.535117E+09 | 44008225.95 | 0.223779E+09 | 2074238.30 | 0.221705E+09 | 0.00 | 0.00 |
August | 0.578140E+09 | 29730415.18 | 0.253982E+09 | 21432415.65 | 0.232550E+09 | 0.00 | 0.00 |
September | 0.715235E+09 | 51161392.86 | 0.314643E+09 | 77103960.73 | 0.237539E+09 | 0.00 | 0.00 |
October | 0.906564E+09 | 83782491.47 | 0.447120E+09 | 0.209775E+09 | 0.237345E+09 | 0.00 | 0.00 |
November | 0.898211E+09 | 0.143935E+09 | 0.492314E+09 | 0.274766E+09 | 0.217548E+09 | 0.00 | 0.00 |
December | 0.948215E+09 | 0.249091E+09 | 0.558194E+09 | 0.352077E+09 | 0.206117E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.854469E+10 | 0.151331E+10 | 0.443100E+10 | 0.180901E+10 | 0.262199E+10 | 0.00 | 0.00 |
Minimum of Months | 0.461292E+09 | 28309573.16 | 0.202255E+09 | 381689.73 | 0.199425E+09 | 0.00 | 0.00 |
Maximum of Months | 0.963321E+09 | 0.283662E+09 | 0.579208E+09 | 0.376298E+09 | 0.237539E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.964048E+09 | 0.282384E+09 | 0.579208E+09 | 0.376298E+09 | 0.202909E+09 | 0.00 | 0.00 |
February | 0.832809E+09 | 0.211886E+09 | 0.473271E+09 | 0.273845E+09 | 0.199425E+09 | 0.00 | 0.00 |
March | 0.719651E+09 | 0.193394E+09 | 0.402296E+09 | 0.170088E+09 | 0.232209E+09 | 0.00 | 0.00 |
April | 0.519608E+09 | 0.128166E+09 | 0.264730E+09 | 46423394.97 | 0.218306E+09 | 0.00 | 0.00 |
May | 0.468606E+09 | 62770111.97 | 0.219209E+09 | 4742544.18 | 0.214467E+09 | 0.00 | 0.00 |
June | 0.461827E+09 | 27983914.69 | 0.202255E+09 | 381689.73 | 0.201874E+09 | 0.00 | 0.00 |
July | 0.535549E+09 | 43615653.07 | 0.223779E+09 | 2074238.30 | 0.221705E+09 | 0.00 | 0.00 |
August | 0.578622E+09 | 29323213.41 | 0.253982E+09 | 21432415.65 | 0.232550E+09 | 0.00 | 0.00 |
September | 0.715692E+09 | 50827991.80 | 0.314643E+09 | 77103960.73 | 0.237539E+09 | 0.00 | 0.00 |
October | 0.906913E+09 | 83188152.97 | 0.447120E+09 | 0.209775E+09 | 0.237345E+09 | 0.00 | 0.00 |
November | 0.898657E+09 | 0.143196E+09 | 0.492314E+09 | 0.274766E+09 | 0.217548E+09 | 0.00 | 0.00 |
December | 0.948852E+09 | 0.247833E+09 | 0.558194E+09 | 0.352077E+09 | 0.206117E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.855083E+10 | 0.150457E+10 | 0.443100E+10 | 0.180901E+10 | 0.262199E+10 | 0.00 | 0.00 |
Minimum of Months | 0.461827E+09 | 27983914.69 | 0.202255E+09 | 381689.73 | 0.199425E+09 | 0.00 | 0.00 |
Maximum of Months | 0.964048E+09 | 0.282384E+09 | 0.579208E+09 | 0.376298E+09 | 0.237539E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.965553E+09 | 0.279234E+09 | 0.579208E+09 | 0.376298E+09 | 0.202909E+09 | 0.00 | 0.00 |
February | 0.833997E+09 | 0.209280E+09 | 0.473271E+09 | 0.273845E+09 | 0.199425E+09 | 0.00 | 0.00 |
March | 0.720460E+09 | 0.191077E+09 | 0.402296E+09 | 0.170088E+09 | 0.232209E+09 | 0.00 | 0.00 |
April | 0.519674E+09 | 0.127121E+09 | 0.264730E+09 | 46423394.97 | 0.218306E+09 | 0.00 | 0.00 |
May | 0.468276E+09 | 62548572.79 | 0.219209E+09 | 4742544.18 | 0.214467E+09 | 0.00 | 0.00 |
June | 0.460856E+09 | 28191982.43 | 0.202255E+09 | 381689.73 | 0.201874E+09 | 0.00 | 0.00 |
July | 0.534497E+09 | 44294913.30 | 0.223779E+09 | 2074238.30 | 0.221705E+09 | 0.00 | 0.00 |
August | 0.577604E+09 | 29701794.44 | 0.253982E+09 | 21432415.65 | 0.232550E+09 | 0.00 | 0.00 |
September | 0.714527E+09 | 51314508.96 | 0.314643E+09 | 77103960.73 | 0.237539E+09 | 0.00 | 0.00 |
October | 0.906447E+09 | 83349421.93 | 0.447120E+09 | 0.209775E+09 | 0.237345E+09 | 0.00 | 0.00 |
November | 0.898972E+09 | 0.142210E+09 | 0.492314E+09 | 0.274766E+09 | 0.217548E+09 | 0.00 | 0.00 |
December | 0.950086E+09 | 0.244846E+09 | 0.558194E+09 | 0.352077E+09 | 0.206117E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.855095E+10 | 0.149317E+10 | 0.443100E+10 | 0.180901E+10 | 0.262199E+10 | 0.00 | 0.00 |
Minimum of Months | 0.460856E+09 | 28191982.43 | 0.202255E+09 | 381689.73 | 0.199425E+09 | 0.00 | 0.00 |
Maximum of Months | 0.965553E+09 | 0.279234E+09 | 0.579208E+09 | 0.376298E+09 | 0.237539E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.965728E+09 | 0.268401E+09 | 0.579208E+09 | 0.376298E+09 | 0.202909E+09 | 0.00 | 0.00 |
February | 0.833274E+09 | 0.200128E+09 | 0.473271E+09 | 0.273845E+09 | 0.199425E+09 | 0.00 | 0.00 |
March | 0.717063E+09 | 0.182676E+09 | 0.402296E+09 | 0.170088E+09 | 0.232209E+09 | 0.00 | 0.00 |
April | 0.513805E+09 | 0.124042E+09 | 0.264730E+09 | 46423394.97 | 0.218306E+09 | 0.00 | 0.00 |
May | 0.459447E+09 | 64208479.09 | 0.219209E+09 | 4742544.18 | 0.214467E+09 | 0.00 | 0.00 |
June | 0.448113E+09 | 30780107.37 | 0.202255E+09 | 381689.73 | 0.201874E+09 | 0.00 | 0.00 |
July | 0.521058E+09 | 49753508.81 | 0.223779E+09 | 2074238.30 | 0.221705E+09 | 0.00 | 0.00 |
August | 0.565268E+09 | 34226244.93 | 0.253982E+09 | 21432415.65 | 0.232550E+09 | 0.00 | 0.00 |
September | 0.701108E+09 | 55739810.49 | 0.314643E+09 | 77103960.73 | 0.237539E+09 | 0.00 | 0.00 |
October | 0.898319E+09 | 87517321.29 | 0.447120E+09 | 0.209775E+09 | 0.237345E+09 | 0.00 | 0.00 |
November | 0.895180E+09 | 0.140605E+09 | 0.492314E+09 | 0.274766E+09 | 0.217548E+09 | 0.00 | 0.00 |
December | 0.950282E+09 | 0.235311E+09 | 0.558194E+09 | 0.352077E+09 | 0.206117E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.846864E+10 | 0.147339E+10 | 0.443100E+10 | 0.180901E+10 | 0.262199E+10 | 0.00 | 0.00 |
Minimum of Months | 0.448113E+09 | 30780107.37 | 0.202255E+09 | 381689.73 | 0.199425E+09 | 0.00 | 0.00 |
Maximum of Months | 0.965728E+09 | 0.268401E+09 | 0.579208E+09 | 0.376298E+09 | 0.237539E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 19.42 | 15.96 | 13.59 | 3.30 | 9.49 | 57.21 | 169.93 | 0.03 |
February | 20.87 | 16.70 | 13.89 | 5.53 | 11.19 | 68.99 | 182.59 | 0.00 |
March | 21.57 | 17.63 | 15.09 | 5.59 | 12.13 | 85.97 | 199.13 | 0.00 |
April | 24.11 | 19.68 | 17.40 | 4.69 | 15.31 | 97.05 | 212.67 | 0.01 |
May | 26.41 | 22.40 | 20.67 | 5.05 | 18.50 | 110.67 | 177.92 | 0.00 |
June | 27.68 | 24.06 | 22.67 | 3.87 | 20.33 | 120.35 | 147.07 | 0.00 |
July | 28.13 | 24.25 | 22.77 | 2.86 | 20.30 | 124.71 | 163.26 | 0.00 |
August | 27.97 | 24.38 | 23.03 | 3.45 | 20.36 | 120.27 | 145.14 | 0.08 |
September | 27.49 | 23.91 | 22.56 | 3.39 | 20.13 | 107.67 | 134.94 | 0.00 |
October | 26.35 | 22.68 | 21.10 | 3.72 | 17.49 | 81.44 | 160.40 | 0.04 |
November | 23.59 | 20.24 | 18.46 | 4.39 | 14.74 | 70.67 | 140.11 | 0.00 |
December | 20.30 | 17.47 | 15.75 | 3.70 | 12.21 | 59.50 | 147.31 | 0.00 |
Annual Sum or Average | 24.51 | 20.80 | 18.94 | 4.12 | 16.04 | 92.16 | 164.97 | 0.01 |
Minimum of Months | 19.42 | 15.96 | 13.59 | 2.86 | 9.49 | 57.21 | 134.94 | 0.00 |
Maximum of Months | 28.13 | 24.38 | 23.03 | 5.59 | 20.36 | 124.71 | 212.67 | 0.08 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 28.90 | 02-JAN-14:20 | 24.35 | 22.57 | 2.37 | 19.46 | 142.33 | 666.50 |
February | 29.40 | 11-FEB-13:00 | 24.15 | 22.20 | 4.60 | 20.75 | 178.50 | 682.00 |
March | 29.40 | 13-MAR-15:00 | 22.41 | 19.40 | 6.20 | 21.27 | 178.00 | 499.00 |
April | 32.20 | 17-APR-14:00 | 19.76 | 12.80 | 5.20 | 21.27 | 367.00 | 219.50 |
May | 34.40 | 22-MAY-12:00 | 23.24 | 18.30 | 5.70 | 25.99 | 382.50 | 457.50 |
June | 32.20 | 11-JUN-12:00 | 23.83 | 20.60 | 3.60 | 23.15 | 181.50 | 762.50 |
July | 35.60 | 29-JUL-15:00 | 24.39 | 20.00 | 3.60 | 25.66 | 281.50 | 374.50 |
August | 33.90 | 23-AUG-12:00 | 25.44 | 22.20 | 5.70 | 24.50 | 261.50 | 640.00 |
September | 32.20 | 08-SEP-14:00 | 23.42 | 20.00 | 2.10 | 21.61 | 221.50 | 576.00 |
October | 32.20 | 09-OCT-10:00 | 23.83 | 20.60 | 3.10 | 25.16 | 286.50 | 457.50 |
November | 30.00 | 17-NOV-14:00 | 22.20 | 18.90 | 4.10 | 19.35 | 178.50 | 412.50 |
December | 28.90 | 10-DEC-14:20 | 22.91 | 20.40 | 7.87 | 19.82 | 162.67 | 585.17 |
Annual Sum or Average | ||||||||
Minimum of Months | 28.90 | 19.76 | 12.80 | 2.10 | 19.35 | 142.33 | 219.50 | |
Maximum of Months | 35.60 | 25.44 | 22.57 | 7.87 | 25.99 | 382.50 | 762.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 9.40 | 25-JAN-04:00 | 4.59 | -1.7 | 3.10 | -7.3 | 0.00 | 0.00 |
February | 5.00 | 04-FEB-06:00 | 1.99 | -2.8 | 5.70 | -11.9 | 0.00 | 0.00 |
March | 6.70 | 16-MAR-04:00 | 4.49 | 1.70 | 4.60 | -9.2 | 0.00 | 0.00 |
April | 14.40 | 02-APR-05:49 | 13.38 | 12.70 | 1.60 | 0.69 | 0.00 | 0.00 |
May | 20.60 | 01-MAY-04:00 | 19.45 | 18.90 | 1.00 | 7.95 | 0.00 | 0.00 |
June | 22.80 | 05-JUN-14:00 | 20.57 | 19.40 | 2.10 | 18.46 | 245.00 | 55.00 |
July | 22.80 | 02-JUL-15:00 | 21.59 | 21.10 | 4.60 | 20.92 | 155.00 | 8.50 |
August | 22.20 | 12-AUG-06:00 | 21.85 | 21.70 | 2.60 | 20.40 | 65.50 | 0.00 |
September | 22.20 | 05-SEP-05:00 | 21.37 | 21.10 | 2.60 | 13.54 | 0.00 | 0.00 |
October | 21.10 | 28-OCT-02:00 | 20.29 | 20.00 | 2.60 | 8.54 | 0.00 | 0.00 |
November | 10.00 | 27-NOV-02:00 | 8.82 | 7.80 | 3.10 | -4.6 | 0.00 | 0.00 |
December | 7.80 | 15-DEC-05:40 | 5.61 | 3.13 | 6.37 | -7.8 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 5.00 | 1.99 | -2.8 | 1.00 | -11.9 | 0.00 | 0.00 | |
Maximum of Months | 22.80 | 21.85 | 21.70 | 6.37 | 20.92 | 245.00 | 55.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 24.83 | 02-JAN-13:00 | 28.90 | 23.30 | 1.50 | 19.87 | 151.00 | 613.50 |
February | 24.15 | 11-FEB-13:00 | 29.40 | 22.20 | 4.60 | 20.75 | 178.50 | 682.00 |
March | 23.83 | 14-MAR-09:00 | 26.70 | 22.80 | 11.30 | 19.52 | 243.50 | 478.00 |
April | 24.58 | 01-APR-15:00 | 28.30 | 23.30 | 3.60 | 16.30 | 93.50 | 759.50 |
May | 26.05 | 28-MAY-14:00 | 28.90 | 25.00 | 5.20 | 25.66 | 289.00 | 98.50 |
June | 26.06 | 28-JUN-11:00 | 28.90 | 25.00 | 1.50 | 22.98 | 404.50 | 373.50 |
July | 26.39 | 12-JUL-10:00 | 30.60 | 25.00 | 4.60 | 23.82 | 287.50 | 574.00 |
August | 26.46 | 21-AUG-15:00 | 32.20 | 24.40 | 3.60 | 24.50 | 205.50 | 366.00 |
September | 26.31 | 22-SEP-16:00 | 30.00 | 25.00 | 6.20 | 28.91 | 54.00 | 21.00 |
October | 26.52 | 01-OCT-11:00 | 29.40 | 25.60 | 6.20 | 28.43 | 283.50 | 0.00 |
November | 25.31 | 04-NOV-13:00 | 27.80 | 24.40 | 2.10 | 26.48 | 199.00 | 3.00 |
December | 24.31 | 24-DEC-14:00 | 27.20 | 23.30 | 2.10 | 23.66 | 201.50 | 114.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 23.83 | 26.70 | 22.20 | 1.50 | 16.30 | 54.00 | 0.00 | |
Maximum of Months | 26.52 | 32.20 | 25.60 | 11.30 | 28.91 | 404.50 | 759.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 23.30 | 02-JAN-13:00 | 28.90 | 24.83 | 1.50 | 19.87 | 151.00 | 613.50 |
February | 22.80 | 11-FEB-16:19 | 27.60 | 24.09 | 5.70 | 18.94 | 101.33 | 565.33 |
March | 22.80 | 14-MAR-09:20 | 25.57 | 23.60 | 9.63 | 22.18 | 176.17 | 527.17 |
April | 23.30 | 01-APR-14:00 | 27.80 | 24.57 | 5.70 | 15.76 | 108.00 | 831.00 |
May | 25.00 | 28-MAY-12:00 | 27.80 | 25.74 | 6.70 | 22.98 | 249.50 | 244.50 |
June | 25.00 | 06-JUN-18:00 | 27.20 | 25.59 | 3.60 | 23.99 | 17.50 | 0.00 |
July | 25.00 | 12-JUL-03:00 | 27.20 | 25.59 | 1.50 | 19.70 | 0.00 | 0.00 |
August | 25.60 | 21-AUG-11:00 | 28.90 | 26.35 | 2.60 | 23.15 | 567.00 | 173.50 |
September | 25.00 | 22-SEP-00:00 | 27.80 | 25.31 | 3.60 | 20.92 | 0.00 | 0.00 |
October | 25.60 | 01-OCT-11:00 | 29.40 | 26.52 | 6.20 | 28.43 | 283.50 | 0.00 |
November | 24.40 | 05-NOV-01:19 | 26.10 | 24.93 | 2.03 | 16.37 | 0.00 | 0.00 |
December | 23.90 | 24-DEC-08:00 | 23.90 | 23.90 | 2.60 | 17.75 | 168.50 | 167.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 22.80 | 23.90 | 23.60 | 1.50 | 15.76 | 0.00 | 0.00 | |
Maximum of Months | 25.60 | 29.40 | 26.52 | 9.63 | 28.43 | 567.00 | 831.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 24.73 | 28.77 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 25.06 | 35.04 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 26.11 | 42.49 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 27.63 | 49.05 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 29.20 | 48.15 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 30.41 | 45.99 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 30.92 | 49.88 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 30.58 | 45.60 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 29.50 | 40.49 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 27.97 | 35.89 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 26.40 | 29.31 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 25.21 | 26.63 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 27.83 | 39.80 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 24.73 | 26.63 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 30.92 | 49.88 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK1
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.281671E+09 | -168217049.6 | 0.00 | 0.00 | 744.00 | 0.00 | -113454171.5 | 58.99 | 0.00 | 0.00 |
February | 0.253633E+09 | -151267883.2 | 0.00 | 0.00 | 672.00 | 0.00 | -102365062.5 | 58.99 | 0.00 | 0.00 |
March | 0.278096E+09 | -164976393.9 | 0.00 | 0.00 | 744.00 | 0.00 | -113119470.9 | 58.99 | 0.00 | 0.00 |
April | 0.258997E+09 | -150316296.7 | 0.00 | 0.00 | 720.00 | 0.00 | -108680977.5 | 58.99 | 0.00 | 0.00 |
May | 0.259588E+09 | -147767849.5 | 0.00 | 0.00 | 744.00 | 0.00 | -111820193.1 | 58.99 | 0.00 | 0.00 |
June | 0.246506E+09 | -138601067.6 | 0.00 | 0.00 | 720.00 | 0.00 | -107904710.0 | 58.99 | 0.00 | 0.00 |
July | 0.249265E+09 | -137802774.8 | 0.00 | 0.00 | 744.00 | 0.00 | -111462540.1 | 58.99 | 0.00 | 0.00 |
August | 0.253782E+09 | -142411820.2 | 0.00 | 0.00 | 744.00 | 0.00 | -111370167.6 | 58.99 | 0.00 | 0.00 |
September | 0.249288E+09 | -141459928.7 | 0.00 | 0.00 | 720.00 | 0.00 | -107827595.6 | 58.99 | 0.00 | 0.00 |
October | 0.263953E+09 | -152297482.8 | 0.00 | 0.00 | 744.00 | 0.00 | -111655104.3 | 59.00 | 0.00 | 0.00 |
November | 0.263094E+09 | -154419017.8 | 0.00 | 0.00 | 720.00 | 0.00 | -108674624.6 | 58.99 | 0.00 | 0.00 |
December | 0.279212E+09 | -166055408.4 | 0.00 | 0.00 | 744.00 | 0.00 | -113156675.2 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.313708E+10 | -0.181559E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.132149E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.246506E+09 | -168217049.6 | 0.00 | 0.00 | 672.00 | 0.00 | -113454171.5 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.281671E+09 | -137802774.8 | 0.00 | 0.00 | 744.00 | 0.00 | -102365062.5 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK2
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.281160E+09 | -168211590.8 | 0.00 | 0.00 | 744.00 | 0.00 | -112948754.4 | 58.99 | 0.00 | 0.00 |
February | 0.253181E+09 | -151267143.3 | 0.00 | 0.00 | 672.00 | 0.00 | -101914347.0 | 58.99 | 0.00 | 0.00 |
March | 0.277699E+09 | -164973236.2 | 0.00 | 0.00 | 744.00 | 0.00 | -112725544.7 | 58.99 | 0.00 | 0.00 |
April | 0.258824E+09 | -150321554.0 | 0.00 | 0.00 | 720.00 | 0.00 | -108502000.1 | 58.99 | 0.00 | 0.00 |
May | 0.259494E+09 | -147771674.1 | 0.00 | 0.00 | 744.00 | 0.00 | -111722419.5 | 58.99 | 0.00 | 0.00 |
June | 0.246460E+09 | -138597897.6 | 0.00 | 0.00 | 720.00 | 0.00 | -107862417.2 | 58.99 | 0.00 | 0.00 |
July | 0.249246E+09 | -137811984.0 | 0.00 | 0.00 | 744.00 | 0.00 | -111433644.8 | 58.99 | 0.00 | 0.00 |
August | 0.253805E+09 | -142415923.2 | 0.00 | 0.00 | 744.00 | 0.00 | -111389099.4 | 58.99 | 0.00 | 0.00 |
September | 0.249279E+09 | -141457532.4 | 0.00 | 0.00 | 720.00 | 0.00 | -107821329.1 | 58.99 | 0.00 | 0.00 |
October | 0.263894E+09 | -152328026.3 | 0.00 | 0.00 | 744.00 | 0.00 | -111565508.9 | 58.98 | 0.00 | 0.00 |
November | 0.262910E+09 | -154429167.0 | 0.00 | 0.00 | 720.00 | 0.00 | -108480526.5 | 58.99 | 0.00 | 0.00 |
December | 0.278763E+09 | -166061018.9 | 0.00 | 0.00 | 744.00 | 0.00 | -112702263.0 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.313471E+10 | -0.181565E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.131907E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.246460E+09 | -168211590.8 | 0.00 | 0.00 | 672.00 | 0.00 | -112948754.4 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.281160E+09 | -137811984.0 | 0.00 | 0.00 | 744.00 | 0.00 | -101914347.0 | 58.99 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK3
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.260344E+09 | -147925555.2 | 0.00 | 0.00 | 744.00 | 0.00 | -112418601.0 | 58.99 | 0.00 | 0.00 |
February | 0.234413E+09 | -133136449.7 | 0.00 | 0.00 | 672.00 | 0.00 | -101276893.4 | 58.99 | 0.00 | 0.00 |
March | 0.259120E+09 | -147246523.4 | 0.00 | 0.00 | 744.00 | 0.00 | -111873420.0 | 58.99 | 0.00 | 0.00 |
April | 0.239395E+09 | -132192904.9 | 0.00 | 0.00 | 720.00 | 0.00 | -107201627.7 | 58.99 | 0.00 | 0.00 |
May | 0.241164E+09 | -131064390.9 | 0.00 | 0.00 | 744.00 | 0.00 | -110099450.7 | 58.99 | 0.00 | 0.00 |
June | 0.229455E+09 | -123444550.4 | 0.00 | 0.00 | 720.00 | 0.00 | -106010424.7 | 58.99 | 0.00 | 0.00 |
July | 0.229775E+09 | -120471569.2 | 0.00 | 0.00 | 744.00 | 0.00 | -109303683.2 | 58.99 | 0.00 | 0.00 |
August | 0.236729E+09 | -127196998.6 | 0.00 | 0.00 | 744.00 | 0.00 | -109531722.0 | 58.99 | 0.00 | 0.00 |
September | 0.230146E+09 | -124348167.0 | 0.00 | 0.00 | 720.00 | 0.00 | -105797690.6 | 58.99 | 0.00 | 0.00 |
October | 0.243762E+09 | -133947365.9 | 0.00 | 0.00 | 744.00 | 0.00 | -109814633.4 | 58.99 | 0.00 | 0.00 |
November | 0.243635E+09 | -136308044.3 | 0.00 | 0.00 | 720.00 | 0.00 | -107327438.8 | 59.00 | 0.00 | 0.00 |
December | 0.256903E+09 | -144956295.1 | 0.00 | 0.00 | 744.00 | 0.00 | -111946803.0 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.290484E+10 | -0.160224E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.130260E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.229455E+09 | -147925555.2 | 0.00 | 0.00 | 672.00 | 0.00 | -112418601.0 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.260344E+09 | -120471569.2 | 0.00 | 0.00 | 744.00 | 0.00 | -101276893.4 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK4
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.260446E+09 | -147922113.7 | 0.00 | 0.00 | 744.00 | 0.00 | -112524161.5 | 58.99 | 0.00 | 0.00 |
February | 0.234489E+09 | -133130207.0 | 0.00 | 0.00 | 672.00 | 0.00 | -101358832.9 | 58.99 | 0.00 | 0.00 |
March | 0.259172E+09 | -147239648.2 | 0.00 | 0.00 | 744.00 | 0.00 | -111932400.8 | 58.99 | 0.00 | 0.00 |
April | 0.239380E+09 | -132201377.3 | 0.00 | 0.00 | 720.00 | 0.00 | -107178226.8 | 58.99 | 0.00 | 0.00 |
May | 0.241121E+09 | -131062642.4 | 0.00 | 0.00 | 744.00 | 0.00 | -110058581.1 | 58.99 | 0.00 | 0.00 |
June | 0.229367E+09 | -123438859.6 | 0.00 | 0.00 | 720.00 | 0.00 | -105928505.1 | 58.99 | 0.00 | 0.00 |
July | 0.229667E+09 | -120468915.5 | 0.00 | 0.00 | 744.00 | 0.00 | -109197597.3 | 58.99 | 0.00 | 0.00 |
August | 0.236646E+09 | -127198899.6 | 0.00 | 0.00 | 744.00 | 0.00 | -109446970.4 | 58.99 | 0.00 | 0.00 |
September | 0.230043E+09 | -124355948.4 | 0.00 | 0.00 | 720.00 | 0.00 | -105686894.6 | 58.99 | 0.00 | 0.00 |
October | 0.243687E+09 | -133965024.6 | 0.00 | 0.00 | 744.00 | 0.00 | -109722094.4 | 58.99 | 0.00 | 0.00 |
November | 0.243634E+09 | -136310718.6 | 0.00 | 0.00 | 720.00 | 0.00 | -107322936.4 | 59.00 | 0.00 | 0.00 |
December | 0.256974E+09 | -144956021.3 | 0.00 | 0.00 | 744.00 | 0.00 | -112018246.7 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.290463E+10 | -0.160225E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.130238E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.229367E+09 | -147922113.7 | 0.00 | 0.00 | 672.00 | 0.00 | -112524161.5 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.260446E+09 | -120468915.5 | 0.00 | 0.00 | 744.00 | 0.00 | -101358832.9 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK5
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.253099E+09 | -139756914.0 | 0.00 | 0.00 | 744.00 | 0.00 | -113341942.1 | 59.01 | 0.00 | 0.00 |
February | 0.227930E+09 | -125908943.8 | 0.00 | 0.00 | 672.00 | 0.00 | -102020797.5 | 58.99 | 0.00 | 0.00 |
March | 0.251993E+09 | -139322197.5 | 0.00 | 0.00 | 744.00 | 0.00 | -112671187.1 | 58.99 | 0.00 | 0.00 |
April | 0.232860E+09 | -125093273.3 | 0.00 | 0.00 | 720.00 | 0.00 | -107767029.4 | 58.99 | 0.00 | 0.00 |
May | 0.234603E+09 | -123950807.1 | 0.00 | 0.00 | 744.00 | 0.00 | -110652280.1 | 58.99 | 0.00 | 0.00 |
June | 0.223353E+09 | -116794999.8 | 0.00 | 0.00 | 720.00 | 0.00 | -106557693.1 | 58.99 | 0.00 | 0.00 |
July | 0.223714E+09 | -113947467.0 | 0.00 | 0.00 | 744.00 | 0.00 | -109766485.9 | 58.99 | 0.00 | 0.00 |
August | 0.230436E+09 | -120376420.8 | 0.00 | 0.00 | 744.00 | 0.00 | -110060069.6 | 58.99 | 0.00 | 0.00 |
September | 0.223896E+09 | -117681153.4 | 0.00 | 0.00 | 720.00 | 0.00 | -106215226.3 | 58.98 | 0.00 | 0.00 |
October | 0.236884E+09 | -126606556.7 | 0.00 | 0.00 | 744.00 | 0.00 | -110277714.3 | 58.99 | 0.00 | 0.00 |
November | 0.236658E+09 | -128761946.5 | 0.00 | 0.00 | 720.00 | 0.00 | -107895568.4 | 58.99 | 0.00 | 0.00 |
December | 0.249786E+09 | -137072473.2 | 0.00 | 0.00 | 744.00 | 0.00 | -112713820.6 | 59.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.282521E+10 | -0.151527E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.130994E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.223353E+09 | -139756914.0 | 0.00 | 0.00 | 672.00 | 0.00 | -113341942.1 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.253099E+09 | -113947467.0 | 0.00 | 0.00 | 744.00 | 0.00 | -102020797.5 | 59.01 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK6
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.253164E+09 | -139764467.3 | 0.00 | 0.00 | 744.00 | 0.00 | -113399390.9 | 59.01 | 0.00 | 0.00 |
February | 0.227992E+09 | -125924188.9 | 0.00 | 0.00 | 672.00 | 0.00 | -102067375.9 | 58.98 | 0.00 | 0.00 |
March | 0.252069E+09 | -139310824.2 | 0.00 | 0.00 | 744.00 | 0.00 | -112757801.8 | 58.99 | 0.00 | 0.00 |
April | 0.232948E+09 | -125084972.8 | 0.00 | 0.00 | 720.00 | 0.00 | -107863103.0 | 58.99 | 0.00 | 0.00 |
May | 0.234698E+09 | -123947890.5 | 0.00 | 0.00 | 744.00 | 0.00 | -110750020.3 | 58.99 | 0.00 | 0.00 |
June | 0.223474E+09 | -116804605.2 | 0.00 | 0.00 | 720.00 | 0.00 | -106669059.6 | 58.99 | 0.00 | 0.00 |
July | 0.223846E+09 | -113942439.7 | 0.00 | 0.00 | 744.00 | 0.00 | -109903125.6 | 58.99 | 0.00 | 0.00 |
August | 0.230562E+09 | -120338864.5 | 0.00 | 0.00 | 744.00 | 0.00 | -110222772.0 | 59.00 | 0.00 | 0.00 |
September | 0.224032E+09 | -117670689.2 | 0.00 | 0.00 | 720.00 | 0.00 | -106361756.8 | 58.99 | 0.00 | 0.00 |
October | 0.236997E+09 | -126607146.4 | 0.00 | 0.00 | 744.00 | 0.00 | -110389823.2 | 58.99 | 0.00 | 0.00 |
November | 0.236751E+09 | -128773184.2 | 0.00 | 0.00 | 720.00 | 0.00 | -107977378.7 | 58.99 | 0.00 | 0.00 |
December | 0.249856E+09 | -137070681.2 | 0.00 | 0.00 | 744.00 | 0.00 | -112785487.0 | 59.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.282639E+10 | -0.151524E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.131115E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.223474E+09 | -139764467.3 | 0.00 | 0.00 | 672.00 | 0.00 | -113399390.9 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.253164E+09 | -113942439.7 | 0.00 | 0.00 | 744.00 | 0.00 | -102067375.9 | 59.01 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK7
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.253238E+09 | -139772595.6 | 0.00 | 0.00 | 744.00 | 0.00 | -113465715.5 | 59.00 | 0.00 | 0.00 |
February | 0.228052E+09 | -125940871.1 | 0.00 | 0.00 | 672.00 | 0.00 | -102110766.5 | 58.98 | 0.00 | 0.00 |
March | 0.252125E+09 | -139307326.8 | 0.00 | 0.00 | 744.00 | 0.00 | -112817769.2 | 58.99 | 0.00 | 0.00 |
April | 0.232987E+09 | -125092601.6 | 0.00 | 0.00 | 720.00 | 0.00 | -107894553.7 | 58.99 | 0.00 | 0.00 |
May | 0.234724E+09 | -123925117.7 | 0.00 | 0.00 | 744.00 | 0.00 | -110798704.5 | 58.99 | 0.00 | 0.00 |
June | 0.223511E+09 | -116816643.7 | 0.00 | 0.00 | 720.00 | 0.00 | -106694056.9 | 58.99 | 0.00 | 0.00 |
July | 0.223874E+09 | -113960766.7 | 0.00 | 0.00 | 744.00 | 0.00 | -109913109.2 | 58.99 | 0.00 | 0.00 |
August | 0.230594E+09 | -120347832.6 | 0.00 | 0.00 | 744.00 | 0.00 | -110246158.2 | 58.99 | 0.00 | 0.00 |
September | 0.224057E+09 | -117686370.1 | 0.00 | 0.00 | 720.00 | 0.00 | -106370560.1 | 58.98 | 0.00 | 0.00 |
October | 0.237031E+09 | -126608830.9 | 0.00 | 0.00 | 744.00 | 0.00 | -110422584.2 | 58.99 | 0.00 | 0.00 |
November | 0.236784E+09 | -128776487.2 | 0.00 | 0.00 | 720.00 | 0.00 | -108007310.0 | 58.99 | 0.00 | 0.00 |
December | 0.249932E+09 | -137098770.7 | 0.00 | 0.00 | 744.00 | 0.00 | -112832896.1 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.282691E+10 | -0.151533E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.131157E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.223511E+09 | -139772595.6 | 0.00 | 0.00 | 672.00 | 0.00 | -113465715.5 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.253238E+09 | -113960766.7 | 0.00 | 0.00 | 744.00 | 0.00 | -102110766.5 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 287.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 304.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 362.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 357.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 389.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 388.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 403.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 348.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 349.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 323.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 314.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 282.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4111.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 282.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 403.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 HEATING COIL
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 4285861.55 | 2577.43 | 25-JAN-08:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 27218449.92 | 11862.00 | 04-FEB-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 26087113.63 | 6778.79 | 16-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6285184.65 | 4360.20 | 15-DEC-08:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 63876609.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 27218449.92 | 11862.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 HEATING COIL
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3210295.44 | 2522.31 | 04-FEB-08:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 3792600.19 | 1963.28 | 16-MAR-07:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 7002895.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3792600.19 | 2522.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3 HEATING COIL
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 8229124.42 | 2151.51 | 04-FEB-07:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5734361.67 | 1446.54 | 16-MAR-06:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 13963486.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8229124.42 | 2151.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4 HEATING COIL
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 9637035.15 | 2860.00 | 04-FEB-07:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6466402.34 | 1608.49 | 16-MAR-06:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 89125.85 | 424.57 | 15-DEC-08:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 16192563.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 9637035.15 | 2860.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5 HEATING COIL
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 268400.87 | 286.44 | 25-JAN-08:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 12056600.38 | 3810.27 | 04-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 8058703.44 | 1889.39 | 16-MAR-06:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 457037.59 | 580.48 | 15-DEC-08:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 20840742.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12056600.38 | 3810.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6 HEATING COIL
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 7272495.42 | 3057.49 | 25-JAN-08:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 20596306.40 | 7314.70 | 04-FEB-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 25899141.77 | 6233.59 | 16-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 3170671.05 | 2416.23 | 15-DEC-08:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 56938614.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 25899141.77 | 7314.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7 HEATING COIL
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 3055216.02 | 1374.12 | 25-JAN-08:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 10440585.15 | 3917.46 | 04-FEB-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 11646416.65 | 2991.32 | 16-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1008152.80 | 974.85 | 15-DEC-08:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 26150370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11646416.65 | 3917.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8 HEATING COIL
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 3966973.70 | 1371.09 | 25-JAN-08:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 11206201.32 | 4424.35 | 04-FEB-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 12879736.11 | 3536.88 | 16-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1320822.70 | 991.84 | 15-DEC-08:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 29373733.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12879736.11 | 4424.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9 HEATING COIL
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 6528520.94 | 2369.71 | 25-JAN-08:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 14431751.05 | 5661.32 | 04-FEB-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 18615282.18 | 3877.83 | 16-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 3676336.68 | 1960.60 | 15-DEC-08:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 43251890.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18615282.18 | 5661.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10 HEATING COIL
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 18504094.17 | 5369.93 | 25-JAN-08:65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 30701023.83 | 30790.14 | 04-FEB-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 44217193.31 | 10747.46 | 16-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 127145.22 | 199.18 | 13-NOV-08:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 25339655.95 | 4714.51 | 15-DEC-08:63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.118889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 44217193.31 | 30790.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.142694E+11 | 0.930252E+10 | 58944.71 | 14-JAN-08:62 | 31513.76 | 0.00 |
February | 0.00 | 0.00 | 0.166455E+11 | 0.112992E+11 | 59721.91 | 11-FEB-08:62 | 30954.52 | 0.00 |
March | 0.00 | 0.00 | 0.203526E+11 | 0.130846E+11 | 60110.70 | 14-MAR-07:03 | 28854.77 | 0.00 |
April | 0.00 | 0.00 | 0.266932E+11 | 0.175320E+11 | 59896.13 | 13-APR-07:02 | 31335.59 | 0.00 |
May | 0.00 | 0.00 | 0.375402E+11 | 0.226969E+11 | 61063.46 | 29-MAY-07:02 | 27612.08 | 0.00 |
June | 0.00 | 0.00 | 0.425802E+11 | 0.241519E+11 | 60700.33 | 08-JUN-07:01 | 31062.45 | 0.00 |
July | 0.00 | 0.00 | 0.472979E+11 | 0.273953E+11 | 60116.42 | 09-JUL-07:01 | 32591.95 | 0.00 |
August | 0.00 | 0.00 | 0.461451E+11 | 0.260652E+11 | 60426.79 | 20-AUG-07:01 | 32207.28 | 0.00 |
September | 0.00 | 0.00 | 0.440049E+11 | 0.253645E+11 | 60600.38 | 22-SEP-07:01 | 31291.55 | 0.00 |
October | 0.00 | 0.00 | 0.393541E+11 | 0.233585E+11 | 61349.27 | 04-OCT-07:02 | 28442.46 | 0.00 |
November | 0.00 | 0.00 | 0.288546E+11 | 0.171474E+11 | 61087.30 | 30-NOV-08:62 | 28577.08 | 0.00 |
December | 0.00 | 0.00 | 0.184243E+11 | 0.112471E+11 | 59836.55 | 09-DEC-08:62 | 31627.33 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.382162E+12 | 0.228645E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.142694E+11 | 0.930252E+10 | 58944.71 | 27612.08 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.472979E+11 | 0.273953E+11 | 61349.27 | 32591.95 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.831325E+10 | 0.569124E+10 | 29791.68 | 14-JAN-08:62 | 18880.58 | 0.00 |
February | 0.00 | 0.00 | 0.915496E+10 | 0.641836E+10 | 29971.41 | 11-FEB-08:62 | 18985.32 | 0.00 |
March | 0.00 | 0.00 | 0.107568E+11 | 0.717681E+10 | 30285.40 | 14-MAR-07:03 | 17702.36 | 0.00 |
April | 0.00 | 0.00 | 0.135423E+11 | 0.912738E+10 | 30093.60 | 13-APR-07:02 | 18959.28 | 0.00 |
May | 0.00 | 0.00 | 0.184894E+11 | 0.114851E+11 | 30439.78 | 27-MAY-07:02 | 17781.68 | 0.00 |
June | 0.00 | 0.00 | 0.207897E+11 | 0.121252E+11 | 30409.92 | 08-JUN-07:01 | 18731.77 | 0.00 |
July | 0.00 | 0.00 | 0.229969E+11 | 0.136619E+11 | 30153.38 | 09-JUL-07:01 | 19466.94 | 0.00 |
August | 0.00 | 0.00 | 0.224441E+11 | 0.130136E+11 | 30332.55 | 27-AUG-07:01 | 18908.70 | 0.00 |
September | 0.00 | 0.00 | 0.214439E+11 | 0.126908E+11 | 30394.61 | 19-SEP-07:01 | 18956.00 | 0.00 |
October | 0.00 | 0.00 | 0.194370E+11 | 0.118884E+11 | 30682.00 | 04-OCT-07:02 | 17728.88 | 0.00 |
November | 0.00 | 0.00 | 0.147687E+11 | 0.911745E+10 | 30693.48 | 30-NOV-08:62 | 17531.12 | 0.00 |
December | 0.00 | 0.00 | 0.100788E+11 | 0.648831E+10 | 29913.48 | 09-DEC-08:62 | 19555.98 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.192216E+12 | 0.118885E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.831325E+10 | 0.569124E+10 | 29791.68 | 17531.12 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.229969E+11 | 0.136619E+11 | 30693.48 | 19555.98 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3 COOLING COIL
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.586639E+10 | 0.388767E+10 | 31002.06 | 30-JAN-07:03 | 15084.28 | 0.00 |
February | 0.00 | 0.00 | 0.682380E+10 | 0.467984E+10 | 31142.16 | 11-FEB-07:03 | 15742.88 | 0.00 |
March | 0.00 | 0.00 | 0.807937E+10 | 0.522718E+10 | 31449.54 | 06-MAR-07:03 | 14470.87 | 0.00 |
April | 0.00 | 0.00 | 0.105188E+11 | 0.690484E+10 | 31174.53 | 13-APR-06:02 | 16116.94 | 0.00 |
May | 0.00 | 0.00 | 0.149553E+11 | 0.903741E+10 | 32202.03 | 29-MAY-07:02 | 13019.18 | 0.00 |
June | 0.00 | 0.00 | 0.171153E+11 | 0.961835E+10 | 31994.75 | 19-JUN-06:02 | 13703.10 | 0.00 |
July | 0.00 | 0.00 | 0.189531E+11 | 0.108652E+11 | 32136.89 | 31-JUL-06:01 | 14221.03 | 0.00 |
August | 0.00 | 0.00 | 0.187067E+11 | 0.104794E+11 | 32192.65 | 28-AUG-06:01 | 13558.35 | 0.00 |
September | 0.00 | 0.00 | 0.175210E+11 | 0.998870E+10 | 31947.34 | 18-SEP-06:01 | 15257.63 | 0.00 |
October | 0.00 | 0.00 | 0.157321E+11 | 0.931942E+10 | 32152.55 | 02-OCT-06:03 | 13164.39 | 0.00 |
November | 0.00 | 0.00 | 0.116374E+11 | 0.695322E+10 | 32180.91 | 05-NOV-07:02 | 13565.12 | 0.00 |
December | 0.00 | 0.00 | 0.722225E+10 | 0.451148E+10 | 31596.55 | 24-DEC-08:62 | 13676.89 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.153132E+12 | 0.914727E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.586639E+10 | 0.388767E+10 | 31002.06 | 13019.18 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.189531E+11 | 0.108652E+11 | 32202.03 | 16116.94 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4 COOLING COIL
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.579430E+10 | 0.383205E+10 | 31084.58 | 30-JAN-07:03 | 15090.31 | 0.00 |
February | 0.00 | 0.00 | 0.676313E+10 | 0.463480E+10 | 31228.63 | 11-FEB-07:03 | 15772.57 | 0.00 |
March | 0.00 | 0.00 | 0.803131E+10 | 0.519105E+10 | 31537.10 | 06-MAR-07:03 | 14508.50 | 0.00 |
April | 0.00 | 0.00 | 0.105152E+11 | 0.690313E+10 | 31262.82 | 13-APR-06:02 | 16163.80 | 0.00 |
May | 0.00 | 0.00 | 0.149746E+11 | 0.905184E+10 | 32291.48 | 29-MAY-07:02 | 13065.55 | 0.00 |
June | 0.00 | 0.00 | 0.171713E+11 | 0.965771E+10 | 32089.14 | 19-JUN-06:02 | 13777.70 | 0.00 |
July | 0.00 | 0.00 | 0.190284E+11 | 0.109188E+11 | 32239.07 | 31-JUL-06:01 | 14347.65 | 0.00 |
August | 0.00 | 0.00 | 0.187612E+11 | 0.105179E+11 | 32282.07 | 28-AUG-06:01 | 13645.98 | 0.00 |
September | 0.00 | 0.00 | 0.175922E+11 | 0.100387E+11 | 32049.52 | 18-SEP-06:01 | 15384.20 | 0.00 |
October | 0.00 | 0.00 | 0.157774E+11 | 0.935148E+10 | 32241.86 | 30-OCT-06:01 | 12915.71 | 0.00 |
November | 0.00 | 0.00 | 0.116241E+11 | 0.694322E+10 | 32273.75 | 05-NOV-07:02 | 13628.45 | 0.00 |
December | 0.00 | 0.00 | 0.716125E+10 | 0.446971E+10 | 31681.60 | 24-DEC-08:62 | 13670.44 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.153194E+12 | 0.915104E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.579430E+10 | 0.383205E+10 | 31084.58 | 12915.71 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.190284E+11 | 0.109188E+11 | 32291.48 | 16163.80 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5 COOLING COIL
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.553268E+10 | 0.363530E+10 | 30787.94 | 07-JAN-07:03 | 15525.30 | 0.00 |
February | 0.00 | 0.00 | 0.652085E+10 | 0.445395E+10 | 30949.67 | 11-FEB-07:03 | 15491.46 | 0.00 |
March | 0.00 | 0.00 | 0.776444E+10 | 0.499404E+10 | 31252.45 | 06-MAR-07:03 | 14285.87 | 0.00 |
April | 0.00 | 0.00 | 0.102646E+11 | 0.671825E+10 | 30982.69 | 13-APR-06:02 | 15892.45 | 0.00 |
May | 0.00 | 0.00 | 0.147222E+11 | 0.887216E+10 | 32013.17 | 29-MAY-07:02 | 12843.88 | 0.00 |
June | 0.00 | 0.00 | 0.169271E+11 | 0.948638E+10 | 31801.26 | 19-JUN-06:02 | 13573.63 | 0.00 |
July | 0.00 | 0.00 | 0.187981E+11 | 0.107534E+11 | 31952.48 | 31-JUL-06:01 | 14147.07 | 0.00 |
August | 0.00 | 0.00 | 0.185077E+11 | 0.103404E+11 | 32003.84 | 28-AUG-06:01 | 13431.28 | 0.00 |
September | 0.00 | 0.00 | 0.173653E+11 | 0.987754E+10 | 31763.44 | 18-SEP-06:01 | 15168.74 | 0.00 |
October | 0.00 | 0.00 | 0.155415E+11 | 0.918248E+10 | 31963.99 | 02-OCT-06:02 | 13136.60 | 0.00 |
November | 0.00 | 0.00 | 0.113690E+11 | 0.676064E+10 | 31986.36 | 05-NOV-07:02 | 13393.24 | 0.00 |
December | 0.00 | 0.00 | 0.689180E+10 | 0.427789E+10 | 31400.31 | 24-DEC-08:62 | 13395.08 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.150205E+12 | 0.893524E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.553268E+10 | 0.363530E+10 | 30787.94 | 12843.88 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.187981E+11 | 0.107534E+11 | 32013.17 | 15892.45 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6 COOLING COIL
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.931719E+10 | 0.594674E+10 | 53252.25 | 14-JAN-08:62 | 28352.08 | 0.00 |
February | 0.00 | 0.00 | 0.111871E+11 | 0.749807E+10 | 54076.60 | 11-FEB-08:62 | 27522.99 | 0.00 |
March | 0.00 | 0.00 | 0.134218E+11 | 0.843007E+10 | 54831.62 | 06-MAR-08:62 | 24966.88 | 0.00 |
April | 0.00 | 0.00 | 0.180754E+11 | 0.116128E+11 | 53988.37 | 13-APR-07:02 | 28606.73 | 0.00 |
May | 0.00 | 0.00 | 0.263518E+11 | 0.156014E+11 | 56023.27 | 29-MAY-08:62 | 22754.20 | 0.00 |
June | 0.00 | 0.00 | 0.304788E+11 | 0.167761E+11 | 55909.57 | 26-JUN-07:02 | 25025.85 | 0.00 |
July | 0.00 | 0.00 | 0.338490E+11 | 0.190796E+11 | 56062.43 | 31-JUL-07:01 | 24902.11 | 0.00 |
August | 0.00 | 0.00 | 0.333873E+11 | 0.183448E+11 | 56152.28 | 28-AUG-07:02 | 23656.15 | 0.00 |
September | 0.00 | 0.00 | 0.313167E+11 | 0.175253E+11 | 55792.56 | 10-SEP-08:61 | 25663.54 | 0.00 |
October | 0.00 | 0.00 | 0.278563E+11 | 0.161834E+11 | 56085.16 | 30-OCT-07:05 | 21839.58 | 0.00 |
November | 0.00 | 0.00 | 0.202032E+11 | 0.117199E+11 | 56187.21 | 05-NOV-08:62 | 22802.69 | 0.00 |
December | 0.00 | 0.00 | 0.116211E+11 | 0.701973E+10 | 54750.00 | 10-DEC-09:02 | 26812.30 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.267066E+12 | 0.155738E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.931719E+10 | 0.594674E+10 | 53252.25 | 21839.58 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.338490E+11 | 0.190796E+11 | 56187.21 | 28606.73 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7 COOLING COIL
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.478151E+10 | 0.305267E+10 | 26165.90 | 14-JAN-08:62 | 13915.16 | 0.00 |
February | 0.00 | 0.00 | 0.575950E+10 | 0.386475E+10 | 28327.48 | 11-FEB-08:62 | 14464.87 | 0.00 |
March | 0.00 | 0.00 | 0.690421E+10 | 0.433790E+10 | 28752.42 | 06-MAR-08:62 | 13070.58 | 0.00 |
April | 0.00 | 0.00 | 0.933891E+10 | 0.600533E+10 | 28280.16 | 13-APR-07:02 | 15025.25 | 0.00 |
May | 0.00 | 0.00 | 0.136518E+11 | 0.809038E+10 | 29361.34 | 29-MAY-08:62 | 11875.24 | 0.00 |
June | 0.00 | 0.00 | 0.157885E+11 | 0.869990E+10 | 29323.83 | 26-JUN-07:02 | 13063.10 | 0.00 |
July | 0.00 | 0.00 | 0.175628E+11 | 0.990949E+10 | 29398.00 | 10-JUL-07:01 | 13293.16 | 0.00 |
August | 0.00 | 0.00 | 0.173077E+11 | 0.951982E+10 | 29428.96 | 28-AUG-07:02 | 12299.64 | 0.00 |
September | 0.00 | 0.00 | 0.162359E+11 | 0.909685E+10 | 29251.82 | 18-SEP-07:01 | 13786.86 | 0.00 |
October | 0.00 | 0.00 | 0.144463E+11 | 0.840264E+10 | 29393.78 | 30-OCT-07:05 | 11401.06 | 0.00 |
November | 0.00 | 0.00 | 0.104484E+11 | 0.606905E+10 | 29447.26 | 05-NOV-08:62 | 11913.04 | 0.00 |
December | 0.00 | 0.00 | 0.597540E+10 | 0.361105E+10 | 28705.25 | 10-DEC-09:02 | 14005.38 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.138201E+12 | 0.806598E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.478151E+10 | 0.305267E+10 | 26165.90 | 11401.06 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.175628E+11 | 0.990949E+10 | 29447.26 | 15025.25 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8 COOLING COIL
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.471265E+10 | 0.300278E+10 | 25413.54 | 14-JAN-08:62 | 13467.23 | 0.00 |
February | 0.00 | 0.00 | 0.568991E+10 | 0.381385E+10 | 28210.39 | 11-FEB-08:62 | 14369.11 | 0.00 |
March | 0.00 | 0.00 | 0.683314E+10 | 0.428687E+10 | 28629.96 | 06-MAR-08:62 | 12995.09 | 0.00 |
April | 0.00 | 0.00 | 0.927380E+10 | 0.595836E+10 | 28163.21 | 13-APR-07:02 | 14932.20 | 0.00 |
May | 0.00 | 0.00 | 0.135860E+11 | 0.804482E+10 | 29238.93 | 29-MAY-08:62 | 11806.30 | 0.00 |
June | 0.00 | 0.00 | 0.157283E+11 | 0.865856E+10 | 29202.05 | 26-JUN-07:02 | 12997.13 | 0.00 |
July | 0.00 | 0.00 | 0.175056E+11 | 0.986935E+10 | 29275.44 | 10-JUL-07:01 | 13228.49 | 0.00 |
August | 0.00 | 0.00 | 0.172461E+11 | 0.947747E+10 | 29306.26 | 28-AUG-07:02 | 12232.69 | 0.00 |
September | 0.00 | 0.00 | 0.161802E+11 | 0.905802E+10 | 29130.26 | 18-SEP-07:01 | 13722.61 | 0.00 |
October | 0.00 | 0.00 | 0.143841E+11 | 0.835883E+10 | 29271.23 | 30-OCT-07:03 | 11403.03 | 0.00 |
November | 0.00 | 0.00 | 0.103792E+11 | 0.602052E+10 | 29324.49 | 05-NOV-08:62 | 11845.94 | 0.00 |
December | 0.00 | 0.00 | 0.589790E+10 | 0.355730E+10 | 28584.36 | 10-DEC-09:02 | 13923.96 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.137417E+12 | 0.801067E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.471265E+10 | 0.300278E+10 | 25413.54 | 11403.03 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.175056E+11 | 0.986935E+10 | 29324.49 | 14932.20 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9 COOLING COIL
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.458057E+10 | 0.290834E+10 | 23217.52 | 14-JAN-08:62 | 12176.76 | 0.00 |
February | 0.00 | 0.00 | 0.556621E+10 | 0.372471E+10 | 27825.77 | 18-FEB-08:62 | 15816.70 | 0.00 |
March | 0.00 | 0.00 | 0.672635E+10 | 0.421226E+10 | 28739.87 | 06-MAR-08:62 | 12972.90 | 0.00 |
April | 0.00 | 0.00 | 0.921382E+10 | 0.591708E+10 | 28274.26 | 13-APR-07:02 | 14930.66 | 0.00 |
May | 0.00 | 0.00 | 0.135792E+11 | 0.804299E+10 | 29363.77 | 29-MAY-08:62 | 11796.73 | 0.00 |
June | 0.00 | 0.00 | 0.157717E+11 | 0.869008E+10 | 29319.17 | 26-JUN-07:02 | 13021.95 | 0.00 |
July | 0.00 | 0.00 | 0.175810E+11 | 0.992411E+10 | 29400.38 | 10-JUL-07:01 | 13273.41 | 0.00 |
August | 0.00 | 0.00 | 0.172977E+11 | 0.951608E+10 | 29431.39 | 28-AUG-07:02 | 12255.89 | 0.00 |
September | 0.00 | 0.00 | 0.162525E+11 | 0.910945E+10 | 29252.91 | 18-SEP-07:01 | 13782.27 | 0.00 |
October | 0.00 | 0.00 | 0.143984E+11 | 0.837040E+10 | 29396.21 | 30-OCT-07:02 | 11482.86 | 0.00 |
November | 0.00 | 0.00 | 0.103105E+11 | 0.597296E+10 | 29449.70 | 05-NOV-08:62 | 11854.45 | 0.00 |
December | 0.00 | 0.00 | 0.575729E+10 | 0.346117E+10 | 28696.09 | 10-DEC-09:02 | 13926.67 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.137035E+12 | 0.798496E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.458057E+10 | 0.290834E+10 | 23217.52 | 11482.86 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.175810E+11 | 0.992411E+10 | 29449.70 | 15816.70 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10 COOLING COIL
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.508387E+10 | 0.328324E+10 | 20138.80 | 14-JAN-08:62 | 9667.68 | 0.00 |
February | 0.00 | 0.00 | 0.620300E+10 | 0.420749E+10 | 30977.62 | 18-FEB-08:62 | 16525.71 | 0.00 |
March | 0.00 | 0.00 | 0.760703E+10 | 0.485064E+10 | 31378.30 | 05-MAR-09:02 | 13930.43 | 0.00 |
April | 0.00 | 0.00 | 0.105733E+11 | 0.691880E+10 | 33859.89 | 13-APR-07:02 | 16124.81 | 0.00 |
May | 0.00 | 0.00 | 0.155325E+11 | 0.941218E+10 | 34668.07 | 29-MAY-08:62 | 13364.59 | 0.00 |
June | 0.00 | 0.00 | 0.180312E+11 | 0.102219E+11 | 34696.83 | 26-JUN-07:02 | 14874.88 | 0.00 |
July | 0.00 | 0.00 | 0.201540E+11 | 0.117280E+11 | 34711.36 | 10-JUL-07:01 | 15395.63 | 0.00 |
August | 0.00 | 0.00 | 0.196062E+11 | 0.111044E+11 | 34747.91 | 28-AUG-07:02 | 14414.74 | 0.00 |
September | 0.00 | 0.00 | 0.186081E+11 | 0.107368E+11 | 34656.54 | 24-SEP-08:61 | 15986.83 | 0.00 |
October | 0.00 | 0.00 | 0.162754E+11 | 0.968999E+10 | 34721.62 | 03-OCT-07:02 | 14217.25 | 0.00 |
November | 0.00 | 0.00 | 0.114828E+11 | 0.679490E+10 | 34769.52 | 05-NOV-08:03 | 13509.21 | 0.00 |
December | 0.00 | 0.00 | 0.626653E+10 | 0.382316E+10 | 34019.23 | 10-DEC-09:02 | 15917.98 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.155424E+12 | 0.927715E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.508387E+10 | 0.328324E+10 | 20138.80 | 9667.68 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.201540E+11 | 0.117280E+11 | 34769.52 | 16525.71 | 0.00 |
Report: FanReportMonthly
For: PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.168355E+10 | 0.36 | 2318.52 | 14-JAN-08:62 | 0.86 |
February | 0.152537E+10 | 0.36 | 2318.52 | 11-FEB-08:62 | 0.86 |
March | 0.169203E+10 | 0.36 | 2318.52 | 05-MAR-08:62 | 0.86 |
April | 0.163733E+10 | 0.36 | 2318.52 | 12-APR-07:02 | 0.86 |
May | 0.171664E+10 | 0.36 | 2318.52 | 03-MAY-07:02 | 0.87 |
June | 0.172636E+10 | 0.37 | 2318.52 | 01-JUN-07:02 | 0.86 |
July | 0.187572E+10 | 0.38 | 2318.52 | 01-JUL-07:02 | 0.86 |
August | 0.185177E+10 | 0.38 | 2318.52 | 01-AUG-07:01 | 0.86 |
September | 0.177696E+10 | 0.37 | 2318.52 | 01-SEP-07:02 | 0.86 |
October | 0.174726E+10 | 0.36 | 2318.52 | 01-OCT-07:01 | 0.86 |
November | 0.163689E+10 | 0.36 | 2318.52 | 03-NOV-07:02 | 0.86 |
December | 0.169207E+10 | 0.36 | 2318.52 | 01-DEC-08:62 | 0.87 |
Annual Sum or Average | 0.205619E+11 | 0.36 | |||
Minimum of Months | 0.152537E+10 | 0.36 | 2318.52 | 0.86 | |
Maximum of Months | 0.187572E+10 | 0.38 | 2318.52 | 0.87 |
Report: FanReportMonthly
For: PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.752076E+09 | 0.39 | 1242.56 | 14-JAN-08:62 | 0.90 |
February | 0.684453E+09 | 0.39 | 1242.56 | 11-FEB-08:62 | 0.90 |
March | 0.771554E+09 | 0.39 | 1242.56 | 05-MAR-08:62 | 0.90 |
April | 0.756176E+09 | 0.39 | 1242.56 | 12-APR-07:02 | 0.90 |
May | 0.814245E+09 | 0.39 | 1242.56 | 03-MAY-07:02 | 0.90 |
June | 0.835410E+09 | 0.39 | 1242.56 | 01-JUN-07:02 | 0.90 |
July | 0.906337E+09 | 0.40 | 1242.56 | 01-JUL-07:02 | 0.90 |
August | 0.895611E+09 | 0.40 | 1242.56 | 01-AUG-07:01 | 0.89 |
September | 0.858437E+09 | 0.40 | 1242.56 | 01-SEP-07:02 | 0.90 |
October | 0.832966E+09 | 0.39 | 1242.56 | 01-OCT-07:01 | 0.90 |
November | 0.761105E+09 | 0.39 | 1242.56 | 03-NOV-07:02 | 0.90 |
December | 0.763053E+09 | 0.39 | 1242.56 | 01-DEC-08:62 | 0.90 |
Annual Sum or Average | 0.963142E+10 | 0.39 | |||
Minimum of Months | 0.684453E+09 | 0.39 | 1242.56 | 0.89 | |
Maximum of Months | 0.906337E+09 | 0.40 | 1242.56 | 0.90 |
Report: FanReportMonthly
For: PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.721119E+09 | 0.30 | 1244.63 | 07-JAN-07:03 | 0.89 |
February | 0.653764E+09 | 0.30 | 1244.63 | 11-FEB-07:03 | 0.89 |
March | 0.736485E+09 | 0.30 | 1244.63 | 05-MAR-08:62 | 0.89 |
April | 0.702374E+09 | 0.30 | 1244.63 | 01-APR-06:03 | 0.90 |
May | 0.741286E+09 | 0.30 | 1244.63 | 03-MAY-06:02 | 0.90 |
June | 0.750986E+09 | 0.31 | 1244.63 | 01-JUN-06:02 | 0.89 |
July | 0.805105E+09 | 0.31 | 1244.63 | 01-JUL-06:02 | 0.89 |
August | 0.809129E+09 | 0.32 | 1244.63 | 01-AUG-06:01 | 0.89 |
September | 0.763921E+09 | 0.31 | 1244.63 | 01-SEP-06:01 | 0.89 |
October | 0.749774E+09 | 0.30 | 1244.63 | 01-OCT-07:01 | 0.89 |
November | 0.703584E+09 | 0.30 | 1244.63 | 01-NOV-06:03 | 0.89 |
December | 0.718317E+09 | 0.29 | 1244.63 | 01-DEC-07:02 | 0.89 |
Annual Sum or Average | 0.885584E+10 | 0.30 | |||
Minimum of Months | 0.653764E+09 | 0.29 | 1244.63 | 0.89 | |
Maximum of Months | 0.809129E+09 | 0.32 | 1244.63 | 0.90 |
Report: FanReportMonthly
For: PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.723094E+09 | 0.29 | 1248.09 | 07-JAN-07:03 | 0.89 |
February | 0.655539E+09 | 0.30 | 1248.09 | 11-FEB-07:03 | 0.89 |
March | 0.738508E+09 | 0.30 | 1248.09 | 05-MAR-08:62 | 0.89 |
April | 0.704197E+09 | 0.30 | 1248.09 | 01-APR-06:03 | 0.90 |
May | 0.743104E+09 | 0.30 | 1248.09 | 03-MAY-06:02 | 0.90 |
June | 0.752893E+09 | 0.31 | 1248.09 | 01-JUN-06:02 | 0.89 |
July | 0.807314E+09 | 0.31 | 1248.09 | 01-JUL-06:02 | 0.89 |
August | 0.811028E+09 | 0.32 | 1248.09 | 01-AUG-06:01 | 0.89 |
September | 0.766000E+09 | 0.31 | 1248.09 | 01-SEP-06:01 | 0.89 |
October | 0.751633E+09 | 0.30 | 1248.09 | 01-OCT-07:01 | 0.89 |
November | 0.705451E+09 | 0.30 | 1248.09 | 01-NOV-06:03 | 0.89 |
December | 0.720264E+09 | 0.29 | 1248.09 | 01-DEC-07:02 | 0.89 |
Annual Sum or Average | 0.887903E+10 | 0.30 | |||
Minimum of Months | 0.655539E+09 | 0.29 | 1248.09 | 0.89 | |
Maximum of Months | 0.811028E+09 | 0.32 | 1248.09 | 0.90 |
Report: FanReportMonthly
For: PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.716722E+09 | 0.29 | 1237.33 | 07-JAN-07:03 | 0.89 |
February | 0.649776E+09 | 0.30 | 1237.33 | 11-FEB-07:03 | 0.89 |
March | 0.732002E+09 | 0.30 | 1237.33 | 05-MAR-08:62 | 0.89 |
April | 0.697718E+09 | 0.30 | 1237.33 | 12-APR-06:02 | 0.89 |
May | 0.736085E+09 | 0.30 | 1237.33 | 03-MAY-06:02 | 0.90 |
June | 0.745071E+09 | 0.31 | 1237.33 | 01-JUN-06:02 | 0.89 |
July | 0.799121E+09 | 0.31 | 1237.33 | 01-JUL-06:02 | 0.89 |
August | 0.802617E+09 | 0.32 | 1237.33 | 01-AUG-06:01 | 0.89 |
September | 0.758259E+09 | 0.31 | 1237.33 | 01-SEP-06:01 | 0.89 |
October | 0.744452E+09 | 0.30 | 1237.33 | 01-OCT-07:01 | 0.89 |
November | 0.699019E+09 | 0.30 | 1237.33 | 01-NOV-06:03 | 0.89 |
December | 0.713895E+09 | 0.29 | 1237.33 | 01-DEC-07:02 | 0.89 |
Annual Sum or Average | 0.879474E+10 | 0.30 | |||
Minimum of Months | 0.649776E+09 | 0.29 | 1237.33 | 0.89 | |
Maximum of Months | 0.802617E+09 | 0.32 | 1237.33 | 0.90 |
Report: FanReportMonthly
For: PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.112225E+10 | 0.26 | 2098.30 | 14-JAN-08:62 | 0.86 |
February | 0.101833E+10 | 0.26 | 2098.30 | 11-FEB-08:62 | 0.86 |
March | 0.114771E+10 | 0.27 | 2098.30 | 05-MAR-09:02 | 0.86 |
April | 0.109691E+10 | 0.26 | 2098.30 | 12-APR-07:02 | 0.86 |
May | 0.117261E+10 | 0.27 | 2098.30 | 03-MAY-07:02 | 0.87 |
June | 0.121161E+10 | 0.28 | 2098.30 | 01-JUN-07:02 | 0.86 |
July | 0.131703E+10 | 0.29 | 2098.30 | 01-JUL-07:02 | 0.86 |
August | 0.131730E+10 | 0.29 | 2098.30 | 01-AUG-07:01 | 0.86 |
September | 0.124154E+10 | 0.28 | 2098.30 | 01-SEP-07:02 | 0.86 |
October | 0.119739E+10 | 0.27 | 2098.30 | 01-OCT-08:61 | 0.86 |
November | 0.110054E+10 | 0.26 | 2098.30 | 03-NOV-07:02 | 0.86 |
December | 0.111758E+10 | 0.26 | 2098.30 | 01-DEC-08:62 | 0.87 |
Annual Sum or Average | 0.140608E+11 | 0.27 | |||
Minimum of Months | 0.101833E+10 | 0.26 | 2098.30 | 0.86 | |
Maximum of Months | 0.131730E+10 | 0.29 | 2098.30 | 0.87 |
Report: FanReportMonthly
For: PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.608458E+09 | 0.27 | 1053.12 | 14-JAN-08:62 | 0.86 |
February | 0.552062E+09 | 0.27 | 1137.84 | 11-FEB-08:62 | 0.89 |
March | 0.622188E+09 | 0.28 | 1137.84 | 05-MAR-09:02 | 0.89 |
April | 0.594404E+09 | 0.27 | 1137.84 | 12-APR-07:02 | 0.89 |
May | 0.635116E+09 | 0.28 | 1137.84 | 03-MAY-07:02 | 0.90 |
June | 0.655288E+09 | 0.29 | 1137.84 | 01-JUN-07:02 | 0.89 |
July | 0.712963E+09 | 0.30 | 1137.84 | 01-JUL-07:02 | 0.89 |
August | 0.712670E+09 | 0.30 | 1137.84 | 01-AUG-07:01 | 0.89 |
September | 0.671498E+09 | 0.29 | 1137.84 | 01-SEP-07:02 | 0.89 |
October | 0.648134E+09 | 0.28 | 1137.84 | 01-OCT-08:61 | 0.89 |
November | 0.596143E+09 | 0.27 | 1137.84 | 03-NOV-07:02 | 0.89 |
December | 0.605839E+09 | 0.27 | 1137.84 | 01-DEC-08:62 | 0.90 |
Annual Sum or Average | 0.761476E+10 | 0.28 | |||
Minimum of Months | 0.552062E+09 | 0.27 | 1053.12 | 0.86 | |
Maximum of Months | 0.712963E+09 | 0.30 | 1137.84 | 0.90 |
Report: FanReportMonthly
For: PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.605920E+09 | 0.27 | 1017.51 | 14-JAN-08:62 | 0.85 |
February | 0.549755E+09 | 0.27 | 1133.10 | 11-FEB-08:62 | 0.89 |
March | 0.619589E+09 | 0.28 | 1133.10 | 05-MAR-09:02 | 0.89 |
April | 0.591887E+09 | 0.27 | 1133.10 | 12-APR-07:02 | 0.89 |
May | 0.632562E+09 | 0.28 | 1133.10 | 03-MAY-07:02 | 0.90 |
June | 0.652888E+09 | 0.29 | 1133.10 | 01-JUN-07:02 | 0.89 |
July | 0.710641E+09 | 0.30 | 1133.10 | 01-JUL-07:02 | 0.89 |
August | 0.710205E+09 | 0.30 | 1133.10 | 01-AUG-07:01 | 0.89 |
September | 0.669199E+09 | 0.29 | 1133.10 | 01-SEP-07:02 | 0.89 |
October | 0.645634E+09 | 0.28 | 1133.10 | 01-OCT-08:61 | 0.89 |
November | 0.593633E+09 | 0.27 | 1133.10 | 03-NOV-07:02 | 0.89 |
December | 0.603290E+09 | 0.27 | 1133.10 | 01-DEC-08:62 | 0.90 |
Annual Sum or Average | 0.758520E+10 | 0.28 | |||
Minimum of Months | 0.549755E+09 | 0.27 | 1017.51 | 0.85 | |
Maximum of Months | 0.710641E+09 | 0.30 | 1133.10 | 0.90 |
Report: FanReportMonthly
For: PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.608474E+09 | 0.27 | 910.01 | 14-JAN-08:62 | 0.81 |
February | 0.552025E+09 | 0.27 | 1137.94 | 18-FEB-08:62 | 0.89 |
March | 0.622205E+09 | 0.28 | 1137.94 | 05-MAR-09:02 | 0.89 |
April | 0.594087E+09 | 0.27 | 1137.94 | 12-APR-07:02 | 0.89 |
May | 0.634843E+09 | 0.28 | 1137.94 | 03-MAY-07:02 | 0.90 |
June | 0.655494E+09 | 0.29 | 1137.94 | 01-JUN-07:02 | 0.89 |
July | 0.714239E+09 | 0.30 | 1137.94 | 01-JUL-07:02 | 0.89 |
August | 0.713224E+09 | 0.30 | 1137.94 | 01-AUG-07:01 | 0.89 |
September | 0.672445E+09 | 0.29 | 1137.94 | 01-SEP-07:02 | 0.89 |
October | 0.647895E+09 | 0.28 | 1137.94 | 01-OCT-08:61 | 0.89 |
November | 0.595765E+09 | 0.27 | 1137.94 | 03-NOV-07:02 | 0.89 |
December | 0.605768E+09 | 0.27 | 1137.94 | 01-DEC-08:62 | 0.90 |
Annual Sum or Average | 0.761646E+10 | 0.28 | |||
Minimum of Months | 0.552025E+09 | 0.27 | 910.01 | 0.81 | |
Maximum of Months | 0.714239E+09 | 0.30 | 1137.94 | 0.90 |
Report: FanReportMonthly
For: PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.718263E+09 | 0.27 | 711.08 | 14-JAN-08:62 | 0.64 |
February | 0.651173E+09 | 0.27 | 1343.49 | 04-FEB-08:62 | 0.91 |
March | 0.734601E+09 | 0.28 | 1216.53 | 05-MAR-09:02 | 0.85 |
April | 0.699035E+09 | 0.27 | 1343.49 | 12-APR-07:02 | 0.89 |
May | 0.742901E+09 | 0.28 | 1343.49 | 03-MAY-07:02 | 0.89 |
June | 0.758948E+09 | 0.29 | 1343.49 | 01-JUN-07:02 | 0.89 |
July | 0.825490E+09 | 0.29 | 1343.49 | 01-JUL-07:02 | 0.89 |
August | 0.822935E+09 | 0.30 | 1343.49 | 01-AUG-07:01 | 0.89 |
September | 0.777415E+09 | 0.29 | 1343.49 | 01-SEP-07:02 | 0.89 |
October | 0.750711E+09 | 0.28 | 1343.49 | 01-OCT-08:61 | 0.89 |
November | 0.699830E+09 | 0.27 | 1343.49 | 03-NOV-07:02 | 0.89 |
December | 0.715133E+09 | 0.27 | 1343.49 | 01-DEC-08:62 | 0.90 |
Annual Sum or Average | 0.889643E+10 | 0.28 | |||
Minimum of Months | 0.651173E+09 | 0.27 | 711.08 | 0.64 | |
Maximum of Months | 0.825490E+09 | 0.30 | 1343.49 | 0.91 |
Report: ZoneTemperatureOscillationReportMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.533524E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.577076E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.681107E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.835386E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.109411E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.119972E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.133800E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.129946E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.124109E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.113099E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.867816E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.627892E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.114262E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.533524E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.133800E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.284425E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.298131E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.344288E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.412272E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.532116E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.581891E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.646736E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.628263E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.600749E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.551668E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.432595E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.324614E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.563775E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.284425E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.646736E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_3:3
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.219158E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.236272E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.273316E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.330170E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.435074E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.478357E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.532468E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.523489E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.490126E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.449174E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.348316E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.248692E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.456461E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.219158E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.532468E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_4:4
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.217690E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.235115E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.272490E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.330402E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.435843E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.479890E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.534466E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.524985E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.491987E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.450474E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.348330E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.247527E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.456920E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.217690E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.534466E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_5:5
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.210718E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.228808E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.265554E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.323920E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.429323E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.473414E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.528097E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.518165E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.485859E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.444279E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.341870E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.240480E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.449049E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.210718E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.528097E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_6:6
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.349389E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.386691E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.451004E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.561951E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.759595E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.846876E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.947433E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.930311E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.871595E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.789184E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.597833E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.399362E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.789123E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.349389E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.947433E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_7:7
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.180637E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.199584E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.232526E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.289527E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.391289E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.435841E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.488244E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.479065E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.448818E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.406682E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.308017E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.206148E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.406638E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.180637E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.488244E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_8:8
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.178696E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.197664E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.230551E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.287698E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.389428E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.434112E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.486549E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.477274E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.447194E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.404909E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.306115E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.204012E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.404420E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.178696E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.486549E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_9:9
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.175837E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.195050E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.228421E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.286668E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.389715E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.435516E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.488801E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.478951E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.449316E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.405637E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.304918E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.200967E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.403980E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.175837E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.488801E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_10:10
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.200616E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.222464E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.263204E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.332497E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.450969E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.502935E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.565786E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.549342E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.519074E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.464178E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.346815E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.226118E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.464400E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.200616E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.565786E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.168355E+10 | 0.142694E+11 | 4285861.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.152537E+10 | 0.166455E+11 | 27218449.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.169203E+10 | 0.203526E+11 | 26087113.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.163733E+10 | 0.266932E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.171664E+10 | 0.375402E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.172636E+10 | 0.425802E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.187572E+10 | 0.472979E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.185177E+10 | 0.461451E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.177696E+10 | 0.440049E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174726E+10 | 0.393541E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.163689E+10 | 0.288546E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.169207E+10 | 0.184243E+11 | 6285184.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.205619E+11 | 0.382162E+12 | 63876609.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.152537E+10 | 0.142694E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.187572E+10 | 0.472979E+11 | 27218449.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.752076E+09 | 0.831325E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.684453E+09 | 0.915496E+10 | 3210295.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.771554E+09 | 0.107568E+11 | 3792600.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.756176E+09 | 0.135423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.814245E+09 | 0.184894E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.835410E+09 | 0.207897E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.906337E+09 | 0.229969E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.895611E+09 | 0.224441E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.858437E+09 | 0.214439E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.832966E+09 | 0.194370E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.761105E+09 | 0.147687E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.763053E+09 | 0.100788E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.963142E+10 | 0.192216E+12 | 7002895.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.684453E+09 | 0.831325E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.906337E+09 | 0.229969E+11 | 3792600.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_3:3
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.721119E+09 | 0.586639E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.653764E+09 | 0.682380E+10 | 8229124.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.736485E+09 | 0.807937E+10 | 5734361.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.702374E+09 | 0.105188E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.741286E+09 | 0.149553E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.750986E+09 | 0.171153E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.805105E+09 | 0.189531E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.809129E+09 | 0.187067E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.763921E+09 | 0.175210E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.749774E+09 | 0.157321E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.703584E+09 | 0.116374E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.718317E+09 | 0.722225E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.885584E+10 | 0.153132E+12 | 13963486.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.653764E+09 | 0.586639E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.809129E+09 | 0.189531E+11 | 8229124.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_4:4
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.723094E+09 | 0.579430E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.655539E+09 | 0.676313E+10 | 9637035.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.738508E+09 | 0.803131E+10 | 6466402.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.704197E+09 | 0.105152E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.743104E+09 | 0.149746E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.752893E+09 | 0.171713E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.807314E+09 | 0.190284E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.811028E+09 | 0.187612E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.766000E+09 | 0.175922E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.751633E+09 | 0.157774E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.705451E+09 | 0.116241E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.720264E+09 | 0.716125E+10 | 89125.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.887903E+10 | 0.153194E+12 | 16192563.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.655539E+09 | 0.579430E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.811028E+09 | 0.190284E+11 | 9637035.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_5:5
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.716722E+09 | 0.553268E+10 | 268400.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.649776E+09 | 0.652085E+10 | 12056600.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.732002E+09 | 0.776444E+10 | 8058703.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.697718E+09 | 0.102646E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.736085E+09 | 0.147222E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.745071E+09 | 0.169271E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.799121E+09 | 0.187981E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.802617E+09 | 0.185077E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.758259E+09 | 0.173653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.744452E+09 | 0.155415E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.699019E+09 | 0.113690E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.713895E+09 | 0.689180E+10 | 457037.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.879474E+10 | 0.150205E+12 | 20840742.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.649776E+09 | 0.553268E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.802617E+09 | 0.187981E+11 | 12056600.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_6:6
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.112225E+10 | 0.931719E+10 | 7272495.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.101833E+10 | 0.111871E+11 | 20596306.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.114771E+10 | 0.134218E+11 | 25899141.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.109691E+10 | 0.180754E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.117261E+10 | 0.263518E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.121161E+10 | 0.304788E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.131703E+10 | 0.338490E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.131730E+10 | 0.333873E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.124154E+10 | 0.313167E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.119739E+10 | 0.278563E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.110054E+10 | 0.202032E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.111758E+10 | 0.116211E+11 | 3170671.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.140608E+11 | 0.267066E+12 | 56938614.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.101833E+10 | 0.931719E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.131730E+10 | 0.338490E+11 | 25899141.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_7:7
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.608458E+09 | 0.478151E+10 | 3055216.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.552062E+09 | 0.575950E+10 | 10440585.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.622188E+09 | 0.690421E+10 | 11646416.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.594404E+09 | 0.933891E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.635116E+09 | 0.136518E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.655288E+09 | 0.157885E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.712963E+09 | 0.175628E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.712670E+09 | 0.173077E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.671498E+09 | 0.162359E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.648134E+09 | 0.144463E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.596143E+09 | 0.104484E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.605839E+09 | 0.597540E+10 | 1008152.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.761476E+10 | 0.138201E+12 | 26150370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.552062E+09 | 0.478151E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.712963E+09 | 0.175628E+11 | 11646416.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_8:8
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.605920E+09 | 0.471265E+10 | 3966973.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.549755E+09 | 0.568991E+10 | 11206201.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.619589E+09 | 0.683314E+10 | 12879736.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.591887E+09 | 0.927380E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.632562E+09 | 0.135860E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.652888E+09 | 0.157283E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.710641E+09 | 0.175056E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.710205E+09 | 0.172461E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.669199E+09 | 0.161802E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.645634E+09 | 0.143841E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.593633E+09 | 0.103792E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.603290E+09 | 0.589790E+10 | 1320822.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.758520E+10 | 0.137417E+12 | 29373733.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.549755E+09 | 0.471265E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.710641E+09 | 0.175056E+11 | 12879736.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_9:9
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.608474E+09 | 0.458057E+10 | 6528520.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.552025E+09 | 0.556621E+10 | 14431751.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.622205E+09 | 0.672635E+10 | 18615282.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.594087E+09 | 0.921382E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.634843E+09 | 0.135792E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.655494E+09 | 0.157717E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.714239E+09 | 0.175810E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.713224E+09 | 0.172977E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.672445E+09 | 0.162525E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.647895E+09 | 0.143984E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.595765E+09 | 0.103105E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.605768E+09 | 0.575729E+10 | 3676336.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.761646E+10 | 0.137035E+12 | 43251890.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.552025E+09 | 0.458057E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.714239E+09 | 0.175810E+11 | 18615282.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_10:10
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.718263E+09 | 0.508387E+10 | 18504094.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.651173E+09 | 0.620300E+10 | 30701023.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.734601E+09 | 0.760703E+10 | 44217193.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.699035E+09 | 0.105733E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.742901E+09 | 0.155325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.758948E+09 | 0.180312E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.825490E+09 | 0.201540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.822935E+09 | 0.196062E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.777415E+09 | 0.186081E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.750711E+09 | 0.162754E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.699830E+09 | 0.114828E+11 | 127145.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.715133E+09 | 0.626653E+10 | 25339655.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.889643E+10 | 0.155424E+12 | 0.118889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.651173E+09 | 0.508387E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.825490E+09 | 0.201540E+11 | 44217193.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.168355E+10 | 0.00 | 0.00 | 0.00 | 0.365170E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.152537E+10 | 0.00 | 0.00 | 0.00 | 0.424539E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.169203E+10 | 0.00 | 0.00 | 0.00 | 0.511904E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.163733E+10 | 0.00 | 0.00 | 0.00 | 0.671654E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.171664E+10 | 0.00 | 0.00 | 0.00 | 0.922447E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.172636E+10 | 0.00 | 0.00 | 0.00 | 0.102708E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.187572E+10 | 0.00 | 0.00 | 0.00 | 0.115043E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.185177E+10 | 0.00 | 0.00 | 0.00 | 0.111428E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.177696E+10 | 0.00 | 0.00 | 0.00 | 0.106339E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174726E+10 | 0.00 | 0.00 | 0.00 | 0.956264E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.163689E+10 | 0.00 | 0.00 | 0.00 | 0.704127E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.169207E+10 | 0.00 | 0.00 | 0.00 | 0.458684E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.205619E+11 | 0.00 | 0.00 | 0.00 | 0.936997E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.152537E+10 | 0.00 | 0.00 | 0.00 | 0.365170E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.187572E+10 | 0.00 | 0.00 | 0.00 | 0.115043E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.752076E+09 | 0.00 | 0.00 | 0.00 | 0.209218E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.684453E+09 | 0.00 | 0.00 | 0.00 | 0.229686E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.771554E+09 | 0.00 | 0.00 | 0.00 | 0.267133E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.756176E+09 | 0.00 | 0.00 | 0.00 | 0.336654E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.814245E+09 | 0.00 | 0.00 | 0.00 | 0.450691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.835410E+09 | 0.00 | 0.00 | 0.00 | 0.498350E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.906337E+09 | 0.00 | 0.00 | 0.00 | 0.556102E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.895611E+09 | 0.00 | 0.00 | 0.00 | 0.538702E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.858437E+09 | 0.00 | 0.00 | 0.00 | 0.514906E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.832966E+09 | 0.00 | 0.00 | 0.00 | 0.468371E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.761105E+09 | 0.00 | 0.00 | 0.00 | 0.356484E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.763053E+09 | 0.00 | 0.00 | 0.00 | 0.248309E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.963142E+10 | 0.00 | 0.00 | 0.00 | 0.467461E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.684453E+09 | 0.00 | 0.00 | 0.00 | 0.209218E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.906337E+09 | 0.00 | 0.00 | 0.00 | 0.556102E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_3:3
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.721119E+09 | 0.00 | 0.00 | 0.00 | 0.147046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.653764E+09 | 0.00 | 0.00 | 0.00 | 0.170895E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.736485E+09 | 0.00 | 0.00 | 0.00 | 0.199667E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.702374E+09 | 0.00 | 0.00 | 0.00 | 0.259933E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.741286E+09 | 0.00 | 0.00 | 0.00 | 0.360945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.750986E+09 | 0.00 | 0.00 | 0.00 | 0.403258E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.805105E+09 | 0.00 | 0.00 | 0.00 | 0.451958E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.809129E+09 | 0.00 | 0.00 | 0.00 | 0.442576E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.763921E+09 | 0.00 | 0.00 | 0.00 | 0.413734E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.749774E+09 | 0.00 | 0.00 | 0.00 | 0.374196E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.703584E+09 | 0.00 | 0.00 | 0.00 | 0.277958E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.718317E+09 | 0.00 | 0.00 | 0.00 | 0.176861E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.885584E+10 | 0.00 | 0.00 | 0.00 | 0.367903E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.653764E+09 | 0.00 | 0.00 | 0.00 | 0.147046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.809129E+09 | 0.00 | 0.00 | 0.00 | 0.451958E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_4:4
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.723094E+09 | 0.00 | 0.00 | 0.00 | 0.145380E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.655539E+09 | 0.00 | 0.00 | 0.00 | 0.169561E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.738508E+09 | 0.00 | 0.00 | 0.00 | 0.198640E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.704197E+09 | 0.00 | 0.00 | 0.00 | 0.259982E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.743104E+09 | 0.00 | 0.00 | 0.00 | 0.361532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.752893E+09 | 0.00 | 0.00 | 0.00 | 0.404601E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.807314E+09 | 0.00 | 0.00 | 0.00 | 0.453734E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.811028E+09 | 0.00 | 0.00 | 0.00 | 0.443882E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.766000E+09 | 0.00 | 0.00 | 0.00 | 0.415387E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.751633E+09 | 0.00 | 0.00 | 0.00 | 0.375310E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.705451E+09 | 0.00 | 0.00 | 0.00 | 0.277785E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.720264E+09 | 0.00 | 0.00 | 0.00 | 0.175501E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.887903E+10 | 0.00 | 0.00 | 0.00 | 0.368130E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.655539E+09 | 0.00 | 0.00 | 0.00 | 0.145380E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.811028E+09 | 0.00 | 0.00 | 0.00 | 0.453734E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_5:5
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.716722E+09 | 0.00 | 0.00 | 0.00 | 0.139046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.649776E+09 | 0.00 | 0.00 | 0.00 | 0.163830E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.732002E+09 | 0.00 | 0.00 | 0.00 | 0.192354E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.697718E+09 | 0.00 | 0.00 | 0.00 | 0.254149E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.736085E+09 | 0.00 | 0.00 | 0.00 | 0.355715E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.745071E+09 | 0.00 | 0.00 | 0.00 | 0.398907E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.799121E+09 | 0.00 | 0.00 | 0.00 | 0.448185E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.802617E+09 | 0.00 | 0.00 | 0.00 | 0.437904E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.758259E+09 | 0.00 | 0.00 | 0.00 | 0.410033E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.744452E+09 | 0.00 | 0.00 | 0.00 | 0.369834E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.699019E+09 | 0.00 | 0.00 | 0.00 | 0.271968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.713895E+09 | 0.00 | 0.00 | 0.00 | 0.169090E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.879474E+10 | 0.00 | 0.00 | 0.00 | 0.361101E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.649776E+09 | 0.00 | 0.00 | 0.00 | 0.139046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.802617E+09 | 0.00 | 0.00 | 0.00 | 0.448185E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_6:6
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.112225E+10 | 0.00 | 0.00 | 0.00 | 0.237164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.101833E+10 | 0.00 | 0.00 | 0.00 | 0.284858E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.114771E+10 | 0.00 | 0.00 | 0.00 | 0.336233E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.109691E+10 | 0.00 | 0.00 | 0.00 | 0.452260E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.117261E+10 | 0.00 | 0.00 | 0.00 | 0.642334E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.121161E+10 | 0.00 | 0.00 | 0.00 | 0.725715E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.131703E+10 | 0.00 | 0.00 | 0.00 | 0.815730E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.131730E+10 | 0.00 | 0.00 | 0.00 | 0.798581E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.124154E+10 | 0.00 | 0.00 | 0.00 | 0.747440E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.119739E+10 | 0.00 | 0.00 | 0.00 | 0.669445E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.110054E+10 | 0.00 | 0.00 | 0.00 | 0.487779E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.111758E+10 | 0.00 | 0.00 | 0.00 | 0.287605E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.140608E+11 | 0.00 | 0.00 | 0.00 | 0.648514E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.101833E+10 | 0.00 | 0.00 | 0.00 | 0.237164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.131730E+10 | 0.00 | 0.00 | 0.00 | 0.815730E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_7:7
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.608458E+09 | 0.00 | 0.00 | 0.00 | 0.119792E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.552062E+09 | 0.00 | 0.00 | 0.00 | 0.144377E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.622188E+09 | 0.00 | 0.00 | 0.00 | 0.170307E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.594404E+09 | 0.00 | 0.00 | 0.00 | 0.230087E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.635116E+09 | 0.00 | 0.00 | 0.00 | 0.327777E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.655288E+09 | 0.00 | 0.00 | 0.00 | 0.370312E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.712963E+09 | 0.00 | 0.00 | 0.00 | 0.416947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.712670E+09 | 0.00 | 0.00 | 0.00 | 0.407798E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.671498E+09 | 0.00 | 0.00 | 0.00 | 0.381668E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.648134E+09 | 0.00 | 0.00 | 0.00 | 0.341869E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.596143E+09 | 0.00 | 0.00 | 0.00 | 0.248403E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.605839E+09 | 0.00 | 0.00 | 0.00 | 0.145564E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.761476E+10 | 0.00 | 0.00 | 0.00 | 0.330490E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.552062E+09 | 0.00 | 0.00 | 0.00 | 0.119792E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.712963E+09 | 0.00 | 0.00 | 0.00 | 0.416947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_8:8
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.605920E+09 | 0.00 | 0.00 | 0.00 | 0.118104E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.549755E+09 | 0.00 | 0.00 | 0.00 | 0.142688E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.619589E+09 | 0.00 | 0.00 | 0.00 | 0.168592E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.591887E+09 | 0.00 | 0.00 | 0.00 | 0.228509E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.632562E+09 | 0.00 | 0.00 | 0.00 | 0.326172E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.652888E+09 | 0.00 | 0.00 | 0.00 | 0.368823E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.710641E+09 | 0.00 | 0.00 | 0.00 | 0.415485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.710205E+09 | 0.00 | 0.00 | 0.00 | 0.406253E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.669199E+09 | 0.00 | 0.00 | 0.00 | 0.380274E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.645634E+09 | 0.00 | 0.00 | 0.00 | 0.340346E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.593633E+09 | 0.00 | 0.00 | 0.00 | 0.246752E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.603290E+09 | 0.00 | 0.00 | 0.00 | 0.143683E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.758520E+10 | 0.00 | 0.00 | 0.00 | 0.328568E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.549755E+09 | 0.00 | 0.00 | 0.00 | 0.118104E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.710641E+09 | 0.00 | 0.00 | 0.00 | 0.415485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_9:9
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.608474E+09 | 0.00 | 0.00 | 0.00 | 0.114989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.552025E+09 | 0.00 | 0.00 | 0.00 | 0.139847E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.622205E+09 | 0.00 | 0.00 | 0.00 | 0.166201E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.594087E+09 | 0.00 | 0.00 | 0.00 | 0.227260E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.634843E+09 | 0.00 | 0.00 | 0.00 | 0.326230E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.655494E+09 | 0.00 | 0.00 | 0.00 | 0.369966E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.714239E+09 | 0.00 | 0.00 | 0.00 | 0.417377E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.713224E+09 | 0.00 | 0.00 | 0.00 | 0.407628E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.672445E+09 | 0.00 | 0.00 | 0.00 | 0.382071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.647895E+09 | 0.00 | 0.00 | 0.00 | 0.340848E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.595765E+09 | 0.00 | 0.00 | 0.00 | 0.245341E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.605768E+09 | 0.00 | 0.00 | 0.00 | 0.140390E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.761646E+10 | 0.00 | 0.00 | 0.00 | 0.327815E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.552025E+09 | 0.00 | 0.00 | 0.00 | 0.114989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.714239E+09 | 0.00 | 0.00 | 0.00 | 0.417377E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_10:10
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.718263E+09 | 0.00 | 0.00 | 0.00 | 0.128790E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.651173E+09 | 0.00 | 0.00 | 0.00 | 0.157347E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.734601E+09 | 0.00 | 0.00 | 0.00 | 0.189744E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.699035E+09 | 0.00 | 0.00 | 0.00 | 0.262594E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.742901E+09 | 0.00 | 0.00 | 0.00 | 0.376679E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.758948E+09 | 0.00 | 0.00 | 0.00 | 0.427040E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.825490E+09 | 0.00 | 0.00 | 0.00 | 0.483237E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.822935E+09 | 0.00 | 0.00 | 0.00 | 0.467048E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.777415E+09 | 0.00 | 0.00 | 0.00 | 0.441332E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.750711E+09 | 0.00 | 0.00 | 0.00 | 0.389107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.699830E+09 | 0.00 | 0.00 | 0.00 | 0.276832E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.715133E+09 | 0.00 | 0.00 | 0.00 | 0.154604E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.889643E+10 | 0.00 | 0.00 | 0.00 | 0.375435E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.651173E+09 | 0.00 | 0.00 | 0.00 | 0.128790E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.825490E+09 | 0.00 | 0.00 | 0.00 | 0.483237E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.880808E+09 | 0.245027E+10 | 0.00 | 6040552.71 | 26285951.58 | 0.00 | 0.196959E+10 | 0.00 | 0.57 |
February | 0.638441E+09 | 0.284252E+10 | 0.00 | 3748784.48 | 21576058.36 | 13390728.15 | 0.747595E+09 | 0.00 | 0.57 |
March | 0.603225E+09 | 0.441143E+10 | 0.00 | 3549113.80 | 37622945.98 | 1496185.71 | 0.891728E+09 | 0.00 | 0.57 |
April | 18953101.42 | 0.667711E+10 | 0.00 | 1274598.03 | 74074300.62 | 0.00 | 0.134609E+09 | 0.00 | 0.57 |
May | 0.00 | 0.125046E+11 | 0.00 | 0.00 | 0.122499E+09 | 0.00 | 0.00 | 0.00 | 0.57 |
June | 0.00 | 0.160621E+11 | 0.00 | 0.00 | 0.153188E+09 | 0.00 | 0.00 | 0.00 | 0.57 |
July | 0.00 | 0.179684E+11 | 0.00 | 0.00 | 0.179761E+09 | 0.00 | 0.00 | 0.00 | 0.57 |
August | 0.00 | 0.176186E+11 | 0.00 | 0.00 | 0.158999E+09 | 0.00 | 0.00 | 0.00 | 0.57 |
September | 0.00 | 0.162474E+11 | 0.00 | 0.00 | 0.139105E+09 | 0.00 | 0.00 | 0.00 | 0.57 |
October | 27984.58 | 0.133029E+11 | 0.00 | 52801.36 | 0.121218E+09 | 0.00 | 67829.80 | 0.00 | 0.57 |
November | 0.139877E+09 | 0.854045E+10 | 0.00 | 2046341.98 | 69844711.28 | 0.00 | 0.444383E+09 | 0.00 | 0.57 |
December | 0.755771E+09 | 0.402764E+10 | 0.00 | 5268971.05 | 42066423.88 | 0.00 | 0.155520E+10 | 0.00 | 0.57 |
Annual Sum or Average | 0.303710E+10 | 0.122653E+12 | 0.00 | 21981163.41 | 0.114624E+10 | 14886913.85 | 0.574318E+10 | 0.00 | 0.57 |
Minimum of Months | 0.00 | 0.245027E+10 | 0.00 | 0.00 | 21576058.36 | 0.00 | 0.00 | 0.00 | 0.57 |
Maximum of Months | 0.880808E+09 | 0.179684E+11 | 0.00 | 6040552.71 | 0.179761E+09 | 13390728.15 | 0.196959E+10 | 0.00 | 0.57 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.248398E+09 | 0.121932E+10 | 0.00 | 3474501.92 | 31964378.63 | 0.00 | 0.718673E+09 | 0.00 | 0.45 |
February | 0.158679E+09 | 0.138117E+10 | 0.00 | 2003859.89 | 24559777.81 | 0.00 | 0.253960E+09 | 0.00 | 0.45 |
March | 0.241757E+09 | 0.199963E+10 | 0.00 | 1836768.29 | 45856353.51 | 0.00 | 0.304469E+09 | 0.00 | 0.46 |
April | 5444091.24 | 0.299958E+10 | 0.00 | 599305.39 | 70012241.80 | 0.00 | 42564882.90 | 0.00 | 0.46 |
May | 0.00 | 0.547328E+10 | 0.00 | 0.00 | 95006668.06 | 0.00 | 0.00 | 0.00 | 0.47 |
June | 0.00 | 0.696269E+10 | 0.00 | 0.00 | 0.110190E+09 | 0.00 | 0.00 | 0.00 | 0.48 |
July | 0.00 | 0.786453E+10 | 0.00 | 0.00 | 0.126146E+09 | 0.00 | 0.00 | 0.00 | 0.48 |
August | 0.00 | 0.769818E+10 | 0.00 | 0.00 | 0.108526E+09 | 0.00 | 0.00 | 0.00 | 0.48 |
September | 0.00 | 0.708793E+10 | 0.00 | 0.00 | 0.101207E+09 | 0.00 | 0.00 | 0.00 | 0.48 |
October | 0.00 | 0.581866E+10 | 0.00 | 0.00 | 99633819.47 | 0.00 | 0.00 | 0.00 | 0.47 |
November | 48147601.73 | 0.381017E+10 | 0.00 | 1041800.18 | 69453185.88 | 0.00 | 0.103292E+09 | 0.00 | 0.46 |
December | 0.186151E+09 | 0.181896E+10 | 0.00 | 2842031.38 | 52114455.52 | 0.00 | 0.575815E+09 | 0.00 | 0.45 |
Annual Sum or Average | 0.888577E+09 | 0.541341E+11 | 0.00 | 11798267.06 | 0.934670E+09 | 0.00 | 0.199877E+10 | 0.00 | 0.47 |
Minimum of Months | 0.00 | 0.121932E+10 | 0.00 | 0.00 | 24559777.81 | 0.00 | 0.00 | 0.00 | 0.45 |
Maximum of Months | 0.248398E+09 | 0.786453E+10 | 0.00 | 3474501.92 | 0.126146E+09 | 0.00 | 0.718673E+09 | 0.00 | 0.48 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.510065E+09 | 0.959438E+09 | 0.00 | 2233892.08 | 41767243.98 | 0.00 | 0.612896E+09 | 0.00 | 0.45 |
February | 0.305533E+09 | 0.115250E+10 | 0.00 | 1122677.76 | 48144675.41 | 0.00 | 0.204789E+09 | 0.00 | 0.45 |
March | 0.390883E+09 | 0.159949E+10 | 0.00 | 1225184.96 | 0.100774E+09 | 0.00 | 0.243646E+09 | 0.00 | 0.46 |
April | 28448219.34 | 0.245570E+10 | 0.00 | 663069.98 | 0.159406E+09 | 0.00 | 61266763.61 | 0.00 | 0.45 |
May | 40101.13 | 0.456575E+10 | 0.00 | 135491.65 | 0.310834E+09 | 0.00 | 137189.44 | 0.00 | 0.46 |
June | 0.00 | 0.578161E+10 | 0.00 | 43430.59 | 0.411804E+09 | 0.00 | 43740.54 | 0.00 | 0.46 |
July | 0.00 | 0.661977E+10 | 0.00 | 0.00 | 0.429978E+09 | 0.00 | 0.00 | 0.00 | 0.45 |
August | 0.00 | 0.648774E+10 | 0.00 | 40401.66 | 0.434413E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
September | 0.00 | 0.583803E+10 | 0.00 | 110606.13 | 0.399556E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
October | 395956.95 | 0.480420E+10 | 0.00 | 182229.79 | 0.317545E+09 | 0.00 | 443399.69 | 0.00 | 0.46 |
November | 91230668.95 | 0.308967E+10 | 0.00 | 942225.31 | 0.210034E+09 | 0.00 | 0.109427E+09 | 0.00 | 0.46 |
December | 0.398008E+09 | 0.139551E+10 | 0.00 | 2090322.30 | 77317203.79 | 0.00 | 0.520250E+09 | 0.00 | 0.45 |
Annual Sum or Average | 0.172460E+10 | 0.447494E+11 | 0.00 | 8789532.22 | 0.294157E+10 | 0.00 | 0.175290E+10 | 0.00 | 0.46 |
Minimum of Months | 0.00 | 0.959438E+09 | 0.00 | 0.00 | 41767243.98 | 0.00 | 0.00 | 0.00 | 0.45 |
Maximum of Months | 0.510065E+09 | 0.661977E+10 | 0.00 | 2233892.08 | 0.434413E+09 | 0.00 | 0.612896E+09 | 0.00 | 0.46 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.515940E+09 | 0.953528E+09 | 0.00 | 2167861.33 | 41584205.21 | 0.00 | 0.607249E+09 | 0.00 | 0.45 |
February | 0.314202E+09 | 0.114420E+10 | 0.00 | 1109610.51 | 48174159.05 | 0.00 | 0.195494E+09 | 0.00 | 0.45 |
March | 0.399308E+09 | 0.159451E+10 | 0.00 | 1217506.13 | 0.100413E+09 | 0.00 | 0.235004E+09 | 0.00 | 0.46 |
April | 28256159.13 | 0.245495E+10 | 0.00 | 668752.00 | 0.159351E+09 | 0.00 | 61167880.54 | 0.00 | 0.45 |
May | 42444.54 | 0.457134E+10 | 0.00 | 140008.52 | 0.309309E+09 | 0.00 | 137933.18 | 0.00 | 0.46 |
June | 0.00 | 0.579440E+10 | 0.00 | 44813.12 | 0.411173E+09 | 0.00 | 44793.13 | 0.00 | 0.46 |
July | 0.00 | 0.663653E+10 | 0.00 | 0.00 | 0.429147E+09 | 0.00 | 0.00 | 0.00 | 0.45 |
August | 0.00 | 0.649854E+10 | 0.00 | 43606.65 | 0.435354E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
September | 0.00 | 0.585555E+10 | 0.00 | 115261.93 | 0.397407E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
October | 393042.34 | 0.481425E+10 | 0.00 | 188790.70 | 0.317326E+09 | 0.00 | 439463.10 | 0.00 | 0.46 |
November | 91759628.41 | 0.308880E+10 | 0.00 | 936014.33 | 0.209910E+09 | 0.00 | 0.108901E+09 | 0.00 | 0.46 |
December | 0.413616E+09 | 0.138973E+10 | 0.00 | 2057616.15 | 76780714.76 | 0.00 | 0.507318E+09 | 0.00 | 0.45 |
Annual Sum or Average | 0.176352E+10 | 0.447963E+11 | 0.00 | 8689841.37 | 0.293593E+10 | 0.00 | 0.171576E+10 | 0.00 | 0.46 |
Minimum of Months | 0.00 | 0.953528E+09 | 0.00 | 0.00 | 41584205.21 | 0.00 | 0.00 | 0.00 | 0.45 |
Maximum of Months | 0.515940E+09 | 0.663653E+10 | 0.00 | 2167861.33 | 0.435354E+09 | 0.00 | 0.607249E+09 | 0.00 | 0.46 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.551505E+09 | 0.926305E+09 | 0.00 | 1977015.50 | 40744712.81 | 0.00 | 0.577012E+09 | 0.00 | 0.45 |
February | 0.342726E+09 | 0.111112E+10 | 0.00 | 1076108.04 | 48115136.75 | 2173251.70 | 0.166034E+09 | 0.00 | 0.45 |
March | 0.422018E+09 | 0.155757E+10 | 0.00 | 1142153.19 | 99125368.80 | 0.00 | 0.213417E+09 | 0.00 | 0.46 |
April | 30165254.66 | 0.241426E+10 | 0.00 | 634887.75 | 0.157716E+09 | 0.00 | 60920019.01 | 0.00 | 0.45 |
May | 58934.28 | 0.452275E+10 | 0.00 | 129826.98 | 0.308898E+09 | 0.00 | 149048.28 | 0.00 | 0.46 |
June | 0.00 | 0.574679E+10 | 0.00 | 41856.45 | 0.410093E+09 | 0.00 | 43003.56 | 0.00 | 0.46 |
July | 0.00 | 0.659269E+10 | 0.00 | 0.00 | 0.429068E+09 | 0.00 | 0.00 | 0.00 | 0.45 |
August | 0.00 | 0.644931E+10 | 0.00 | 39957.54 | 0.434269E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
September | 0.00 | 0.581108E+10 | 0.00 | 109609.54 | 0.397384E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
October | 411141.19 | 0.477027E+10 | 0.00 | 174706.43 | 0.316658E+09 | 0.00 | 460796.48 | 0.00 | 0.46 |
November | 0.101104E+09 | 0.304511E+10 | 0.00 | 870374.07 | 0.208381E+09 | 0.00 | 0.102538E+09 | 0.00 | 0.46 |
December | 0.435116E+09 | 0.135923E+10 | 0.00 | 1896702.35 | 75274341.36 | 0.00 | 0.497789E+09 | 0.00 | 0.45 |
Annual Sum or Average | 0.188310E+10 | 0.443065E+11 | 0.00 | 8093197.84 | 0.292573E+10 | 2173251.70 | 0.161836E+10 | 0.00 | 0.46 |
Minimum of Months | 0.00 | 0.926305E+09 | 0.00 | 0.00 | 40744712.81 | 0.00 | 0.00 | 0.00 | 0.45 |
Maximum of Months | 0.551505E+09 | 0.659269E+10 | 0.00 | 1977015.50 | 0.434269E+09 | 2173251.70 | 0.577012E+09 | 0.00 | 0.46 |
Report: MechanicalVentilationLoadsMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.100853E+10 | 0.159902E+10 | 0.00 | 3284056.19 | 46136202.35 | 0.00 | 0.109541E+10 | 0.00 | 0.42 |
February | 0.497852E+09 | 0.187094E+10 | 0.00 | 2335508.02 | 57138445.00 | 3012877.03 | 0.370511E+09 | 0.00 | 0.42 |
March | 0.671619E+09 | 0.274503E+10 | 0.00 | 2220637.73 | 89506405.56 | 1486359.59 | 0.503991E+09 | 0.00 | 0.43 |
April | 18286282.29 | 0.438708E+10 | 0.00 | 1068583.09 | 0.160330E+09 | 0.00 | 0.123213E+09 | 0.00 | 0.42 |
May | 0.00 | 0.846898E+10 | 0.00 | 37800.54 | 0.239058E+09 | 0.00 | 49010.40 | 0.00 | 0.43 |
June | 0.00 | 0.109055E+11 | 0.00 | 84595.93 | 0.290987E+09 | 0.00 | 64409.10 | 0.00 | 0.43 |
July | 0.00 | 0.124543E+11 | 0.00 | 0.00 | 0.380431E+09 | 0.00 | 0.00 | 0.00 | 0.42 |
August | 0.00 | 0.122706E+11 | 0.00 | 0.00 | 0.283297E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
September | 0.00 | 0.110235E+11 | 0.00 | 0.00 | 0.331168E+09 | 0.00 | 0.00 | 0.00 | 0.42 |
October | 3418.17 | 0.896385E+10 | 0.00 | 155052.29 | 0.263985E+09 | 0.00 | 157646.76 | 0.00 | 0.42 |
November | 0.119436E+09 | 0.571947E+10 | 0.00 | 1358719.85 | 0.157504E+09 | 0.00 | 0.191828E+09 | 0.00 | 0.42 |
December | 0.696827E+09 | 0.237824E+10 | 0.00 | 3099374.58 | 96815002.11 | 0.00 | 0.111465E+10 | 0.00 | 0.42 |
Annual Sum or Average | 0.301255E+10 | 0.827866E+11 | 0.00 | 13644328.23 | 0.239636E+10 | 4499236.62 | 0.339987E+10 | 0.00 | 0.42 |
Minimum of Months | 0.00 | 0.159902E+10 | 0.00 | 0.00 | 46136202.35 | 0.00 | 0.00 | 0.00 | 0.42 |
Maximum of Months | 0.100853E+10 | 0.124543E+11 | 0.00 | 3284056.19 | 0.380431E+09 | 3012877.03 | 0.111465E+10 | 0.00 | 0.43 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.532737E+09 | 0.794091E+09 | 0.00 | 1597521.16 | 22918555.41 | 0.00 | 0.513328E+09 | 0.00 | 0.42 |
February | 0.249064E+09 | 0.930694E+09 | 0.00 | 1158321.90 | 27674643.50 | 1504713.12 | 0.182048E+09 | 0.00 | 0.42 |
March | 0.345003E+09 | 0.136463E+10 | 0.00 | 1085624.38 | 43561980.64 | 0.00 | 0.238348E+09 | 0.00 | 0.43 |
April | 9161673.45 | 0.218603E+10 | 0.00 | 536504.56 | 78908416.94 | 0.00 | 60858523.88 | 0.00 | 0.42 |
May | 0.00 | 0.422575E+10 | 0.00 | 23606.56 | 0.116025E+09 | 0.00 | 26424.87 | 0.00 | 0.43 |
June | 0.00 | 0.543711E+10 | 0.00 | 40441.80 | 0.142685E+09 | 0.00 | 38807.61 | 0.00 | 0.43 |
July | 0.00 | 0.620835E+10 | 0.00 | 0.00 | 0.192642E+09 | 0.00 | 0.00 | 0.00 | 0.42 |
August | 0.00 | 0.611893E+10 | 0.00 | 3546.91 | 0.139626E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
September | 0.00 | 0.549643E+10 | 0.00 | 0.00 | 0.162540E+09 | 0.00 | 0.00 | 0.00 | 0.42 |
October | 1048.17 | 0.447132E+10 | 0.00 | 82905.38 | 0.129266E+09 | 0.00 | 74448.98 | 0.00 | 0.42 |
November | 60066138.14 | 0.284809E+10 | 0.00 | 675138.27 | 76436158.71 | 0.00 | 94664482.10 | 0.00 | 0.42 |
December | 0.351687E+09 | 0.117976E+10 | 0.00 | 1512003.91 | 47175705.83 | 0.00 | 0.551515E+09 | 0.00 | 0.42 |
Annual Sum or Average | 0.154772E+10 | 0.412612E+11 | 0.00 | 6715614.84 | 0.117946E+10 | 1504713.12 | 0.164090E+10 | 0.00 | 0.42 |
Minimum of Months | 0.00 | 0.794091E+09 | 0.00 | 0.00 | 22918555.41 | 0.00 | 0.00 | 0.00 | 0.42 |
Maximum of Months | 0.532737E+09 | 0.620835E+10 | 0.00 | 1597521.16 | 0.192642E+09 | 1504713.12 | 0.551515E+09 | 0.00 | 0.43 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.551417E+09 | 0.786570E+09 | 0.00 | 1553098.96 | 22986556.69 | 0.00 | 0.495431E+09 | 0.00 | 0.42 |
February | 0.250854E+09 | 0.921442E+09 | 0.00 | 1139464.00 | 27892085.37 | 2389738.63 | 0.180457E+09 | 0.00 | 0.42 |
March | 0.345945E+09 | 0.135446E+10 | 0.00 | 1069041.41 | 43286122.03 | 740563.08 | 0.237185E+09 | 0.00 | 0.43 |
April | 9165512.47 | 0.217535E+10 | 0.00 | 529565.03 | 78246694.15 | 0.00 | 61230875.28 | 0.00 | 0.42 |
May | 0.00 | 0.421396E+10 | 0.00 | 23006.34 | 0.114909E+09 | 0.00 | 25420.87 | 0.00 | 0.43 |
June | 0.00 | 0.542528E+10 | 0.00 | 39912.77 | 0.142402E+09 | 0.00 | 38634.69 | 0.00 | 0.43 |
July | 0.00 | 0.619824E+10 | 0.00 | 0.00 | 0.191858E+09 | 0.00 | 0.00 | 0.00 | 0.42 |
August | 0.00 | 0.610685E+10 | 0.00 | 3287.55 | 0.139363E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
September | 0.00 | 0.548584E+10 | 0.00 | 0.00 | 0.162278E+09 | 0.00 | 0.00 | 0.00 | 0.42 |
October | 1762.09 | 0.445981E+10 | 0.00 | 81456.23 | 0.128949E+09 | 0.00 | 74915.30 | 0.00 | 0.42 |
November | 59993575.21 | 0.283580E+10 | 0.00 | 668670.41 | 76398072.25 | 0.00 | 95406049.10 | 0.00 | 0.42 |
December | 0.354567E+09 | 0.117038E+10 | 0.00 | 1466638.46 | 47008385.23 | 0.00 | 0.551453E+09 | 0.00 | 0.42 |
Annual Sum or Average | 0.157194E+10 | 0.411340E+11 | 0.00 | 6574141.13 | 0.117558E+10 | 3130301.71 | 0.162130E+10 | 0.00 | 0.42 |
Minimum of Months | 0.00 | 0.786570E+09 | 0.00 | 0.00 | 22986556.69 | 0.00 | 0.00 | 0.00 | 0.42 |
Maximum of Months | 0.551417E+09 | 0.619824E+10 | 0.00 | 1553098.96 | 0.191858E+09 | 2389738.63 | 0.551453E+09 | 0.00 | 0.43 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.589685E+09 | 0.771809E+09 | 0.00 | 1457653.04 | 23474146.86 | 912277.62 | 0.456461E+09 | 0.00 | 0.42 |
February | 0.243701E+09 | 0.903463E+09 | 0.00 | 1085833.86 | 28943771.21 | 11283273.02 | 0.179484E+09 | 0.00 | 0.42 |
March | 0.352956E+09 | 0.133706E+10 | 0.00 | 1027044.20 | 42969174.19 | 735858.76 | 0.230718E+09 | 0.00 | 0.43 |
April | 12554093.59 | 0.216186E+10 | 0.00 | 514835.37 | 77471358.97 | 0.00 | 58299726.46 | 0.00 | 0.42 |
May | 0.00 | 0.420676E+10 | 0.00 | 20110.70 | 0.115452E+09 | 0.00 | 20512.22 | 0.00 | 0.43 |
June | 0.00 | 0.542999E+10 | 0.00 | 37901.09 | 0.143696E+09 | 0.00 | 35937.62 | 0.00 | 0.43 |
July | 0.00 | 0.620406E+10 | 0.00 | 0.00 | 0.198169E+09 | 0.00 | 0.00 | 0.00 | 0.42 |
August | 0.00 | 0.610648E+10 | 0.00 | 2120.28 | 0.147698E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
September | 0.00 | 0.549789E+10 | 0.00 | 0.00 | 0.161990E+09 | 0.00 | 0.00 | 0.00 | 0.42 |
October | 28035.23 | 0.445789E+10 | 0.00 | 77224.56 | 0.130516E+09 | 0.00 | 46453.24 | 0.00 | 0.42 |
November | 61520040.02 | 0.282188E+10 | 0.00 | 656649.50 | 77155228.85 | 0.00 | 94899364.04 | 0.00 | 0.42 |
December | 0.365620E+09 | 0.115432E+10 | 0.00 | 1348343.48 | 46944783.99 | 0.00 | 0.545278E+09 | 0.00 | 0.42 |
Annual Sum or Average | 0.162606E+10 | 0.410535E+11 | 0.00 | 6227716.09 | 0.119448E+10 | 12931409.39 | 0.156524E+10 | 0.00 | 0.42 |
Minimum of Months | 0.00 | 0.771809E+09 | 0.00 | 0.00 | 23474146.86 | 0.00 | 0.00 | 0.00 | 0.42 |
Maximum of Months | 0.589685E+09 | 0.620406E+10 | 0.00 | 1457653.04 | 0.198169E+09 | 11283273.02 | 0.545278E+09 | 0.00 | 0.43 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.551642E+09 | 0.811133E+09 | 0.00 | 1495788.03 | 22722080.48 | 9723035.58 | 0.455451E+09 | 0.00 | 0.42 |
February | 0.230047E+09 | 0.943057E+09 | 0.00 | 1075155.19 | 22869041.01 | 14201821.03 | 0.165287E+09 | 0.00 | 0.42 |
March | 0.310093E+09 | 0.140493E+10 | 0.00 | 1116100.78 | 34001615.76 | 22299596.83 | 0.248775E+09 | 0.00 | 0.43 |
April | 15773762.50 | 0.228638E+10 | 0.00 | 538792.16 | 63861419.22 | 0.00 | 50104654.37 | 0.00 | 0.42 |
May | 3667.21 | 0.440809E+10 | 0.00 | 59704.13 | 0.100676E+09 | 0.00 | 58486.77 | 0.00 | 0.42 |
June | 0.00 | 0.569765E+10 | 0.00 | 30341.38 | 0.129494E+09 | 0.00 | 35955.09 | 0.00 | 0.43 |
July | 0.00 | 0.652671E+10 | 0.00 | 0.00 | 0.182215E+09 | 0.00 | 0.00 | 0.00 | 0.42 |
August | 0.00 | 0.636783E+10 | 0.00 | 35691.46 | 0.137987E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
September | 0.00 | 0.577341E+10 | 0.00 | 16429.05 | 0.149182E+09 | 0.00 | 0.00 | 0.00 | 0.42 |
October | 113485.45 | 0.465180E+10 | 0.00 | 208253.31 | 0.120330E+09 | 0.00 | 207360.94 | 0.00 | 0.42 |
November | 53207198.17 | 0.294723E+10 | 0.00 | 672095.42 | 69259860.31 | 0.00 | 87181363.67 | 0.00 | 0.42 |
December | 0.384049E+09 | 0.120771E+10 | 0.00 | 1232286.39 | 44218456.29 | 9408207.50 | 0.497305E+09 | 0.00 | 0.42 |
Annual Sum or Average | 0.154493E+10 | 0.430259E+11 | 0.00 | 6480637.28 | 0.107682E+10 | 55632660.94 | 0.150441E+10 | 0.00 | 0.42 |
Minimum of Months | 0.00 | 0.811133E+09 | 0.00 | 0.00 | 22722080.48 | 0.00 | 0.00 | 0.00 | 0.42 |
Maximum of Months | 0.551642E+09 | 0.652671E+10 | 0.00 | 1495788.03 | 0.182215E+09 | 22299596.83 | 0.497305E+09 | 0.00 | 0.43 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.185204E+12 | -113068892.9 | 0.00 | 0.226546E+11 | 0.855097E+11 |
February | 0.204211E+12 | -0.577367E+10 | 0.00 | 0.599301E+10 | 0.100627E+12 |
March | 0.284407E+12 | -0.821345E+10 | 0.00 | -0.655324E+10 | 0.120526E+12 |
April | 0.317077E+12 | -0.187415E+11 | 0.00 | -0.347779E+11 | 0.159840E+12 |
May | 0.310728E+12 | -0.343458E+11 | 0.00 | -0.797161E+11 | 0.227888E+12 |
June | 0.282911E+12 | -0.415913E+11 | 0.00 | -0.112045E+12 | 0.260323E+12 |
July | 0.309692E+12 | -0.475262E+11 | 0.00 | -0.123885E+12 | 0.289819E+12 |
August | 0.325690E+12 | -0.462892E+11 | 0.00 | -0.124741E+12 | 0.284056E+12 |
September | 0.250041E+12 | -0.427540E+11 | 0.00 | -0.109910E+12 | 0.268023E+12 |
October | 0.237603E+12 | -0.357197E+11 | 0.00 | -0.883080E+11 | 0.239459E+12 |
November | 0.172589E+12 | -0.214681E+11 | 0.00 | -0.401743E+11 | 0.175012E+12 |
December | 0.182422E+12 | -0.530808E+10 | 0.00 | 0.628673E+10 | 0.106310E+12 |
Annual Sum or Average | 0.306257E+13 | -0.307844E+12 | 0.00 | -0.685176E+12 | 0.231739E+13 |
Minimum of Months | 0.172589E+12 | -0.475262E+11 | 0.00 | -0.124741E+12 | 0.855097E+11 |
Maximum of Months | 0.325690E+12 | -113068892.9 | 0.00 | 0.226546E+11 | 0.289819E+12 |