Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:36
Tabular Output Report in Format: HTML
Building: RetailStripmall
Environment: RUNPERIOD 1 ** Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190
Simulation Timestamp: 2023-10-16 08:36:59
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:59
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1086.49 | 519.77 | 519.77 |
Net Site Energy | 1086.49 | 519.77 | 519.77 |
Total Source Energy | 3038.87 | 1453.78 | 1453.78 |
Net Source Energy | 3038.87 | 1453.78 | 1453.78 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 2090.32 |
Net Conditioned Building Area | 2090.32 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 193.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 180.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 366.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 60.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 128.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 96.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 62.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 893.48 | 193.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 193.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 180.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 366.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 60.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 128.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 96.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 62.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 193.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 180.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 366.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 60.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 128.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 96.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 62.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 204.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 161.98 | 92.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Other | 61.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 427.44 | 92.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 204.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 161.98 | 92.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Other | 61.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 427.44 | 92.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 893.476 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 893.476 | 100.00 |
Total On-Site and Utility Electric Sources | 893.476 | 100.00 |
Total Electricity End Uses | 893.476 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 87.30 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 87.30 | 100.00 |
Total Water End Uses | 87.30 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.83 |
Time Setpoint Not Met During Occupied Cooling | 0.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 1739.33 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTRIPMALL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3A
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_GA_ATLANTA
| Environment |ZoneCoolingSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ZoneHeatingSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ZoneElectricSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |SpaceGainsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |PeakSpaceGainsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |SpaceGainComponentsAtCoolingPeakMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ComfortReportSimple55Monthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |OccupantComfortDataSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |DXReportMonthly
| PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL | PSZ-AC_3:3 COOLING COIL | PSZ-AC_4:4 COOLING COIL | PSZ-AC_5:5 COOLING COIL | PSZ-AC_6:6 COOLING COIL | PSZ-AC_7:7 COOLING COIL | PSZ-AC_8:8 COOLING COIL | PSZ-AC_9:9 COOLING COIL | PSZ-AC_10:10 COOLING COIL |WindowReportMonthly
| LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR |WindowEnergyReportMonthly
| LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR |WindowZoneSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |WindowEnergyZoneSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| GAS TANK1 | GAS TANK2 | GAS TANK3 | GAS TANK4 | GAS TANK5 | GAS TANK6 | GAS TANK7 |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC_1:1 HEATING COIL | PSZ-AC_2:2 HEATING COIL | PSZ-AC_3:3 HEATING COIL | PSZ-AC_4:4 HEATING COIL | PSZ-AC_5:5 HEATING COIL | PSZ-AC_6:6 HEATING COIL | PSZ-AC_7:7 HEATING COIL | PSZ-AC_8:8 HEATING COIL | PSZ-AC_9:9 HEATING COIL | PSZ-AC_10:10 HEATING COIL | PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL | PSZ-AC_3:3 COOLING COIL | PSZ-AC_4:4 COOLING COIL | PSZ-AC_5:5 COOLING COIL | PSZ-AC_6:6 COOLING COIL | PSZ-AC_7:7 COOLING COIL | PSZ-AC_8:8 COOLING COIL | PSZ-AC_9:9 COOLING COIL | PSZ-AC_10:10 COOLING COIL |FanReportMonthly
| PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN |ZoneTemperatureOscillationReportMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |MechanicalVentilationLoadsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:59
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:36 |
RunPeriod | RUNPERIOD 1 |
Weather File | Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190 |
Latitude [deg] | 33.63 |
Longitude [deg] | -84.4 |
Elevation [m] | 308.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Above Ground Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Window Opening Area [m2] | 124.40 | 0.00 | 0.00 | 124.40 | 0.00 |
Gross Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Above Ground Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Above Ground Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Window Opening Area [m2] | 124.40 | 0.00 | 0.00 | 124.40 | 0.00 |
Gross Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Above Ground Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Total | |
Gross Roof Area [m2] | 2090.32 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
LGSTORE1 | 348.39 | Yes | Yes | 1805.20 | 1.00 | 276.30 | 0.00 | 20.77 | 20.77 | 15.3022 | 6.19 | 4.3000 |
SMSTORE1 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.38 | 10.38 | 18.2890 | 6.19 | 4.3000 |
SMSTORE2 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 16.6533 | 6.19 | 4.3000 |
SMSTORE3 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 16.6533 | 6.19 | 4.3000 |
SMSTORE4 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 16.6533 | 6.19 | 4.3000 |
LGSTORE2 | 348.39 | Yes | Yes | 1805.20 | 1.00 | 157.89 | 0.00 | 20.72 | 20.72 | 9.5842 | 6.19 | 4.3000 |
SMSTORE5 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 9.6995 | 6.19 | 4.3000 |
SMSTORE6 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 9.6995 | 6.19 | 4.3000 |
SMSTORE7 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 9.6995 | 6.19 | 4.3000 |
SMSTORE8 | 174.19 | Yes | Yes | 902.60 | 1.00 | 197.36 | 0.00 | 10.36 | 10.36 | 9.6995 | 6.19 | 4.3000 |
Total | 2090.32 | 10831.20 | 1184.15 | 0.00 | 124.40 | 124.40 | 13.0683 | 6.19 | 4.3000 | |||
Conditioned Total | 2090.32 | 10831.20 | 1184.15 | 0.00 | 124.40 | 124.40 | 13.0683 | 6.19 | 4.3000 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
LGSTORE1 | 348.39 | Yes | Yes | 1.00 | LGSTORE1 | GENERAL | LGSTORE1 | 15.3022 | 6.19 | 4.3000 | |
SMSTORE1 | 174.19 | Yes | Yes | 1.00 | SMSTORE1 | GENERAL | SMSTORE1 | 18.2890 | 6.19 | 4.3000 | |
SMSTORE2 | 174.19 | Yes | Yes | 1.00 | SMSTORE2 | GENERAL | SMSTORE2 | 16.6533 | 6.19 | 4.3000 | |
SMSTORE3 | 174.19 | Yes | Yes | 1.00 | SMSTORE3 | GENERAL | SMSTORE3 | 16.6533 | 6.19 | 4.3000 | |
SMSTORE4 | 174.19 | Yes | Yes | 1.00 | SMSTORE4 | GENERAL | SMSTORE4 | 16.6533 | 6.19 | 4.3000 | |
LGSTORE2 | 348.39 | Yes | Yes | 1.00 | LGSTORE2 | GENERAL | LGSTORE2 | 9.5842 | 6.19 | 4.3000 | |
SMSTORE5 | 174.19 | Yes | Yes | 1.00 | SMSTORE5 | GENERAL | SMSTORE5 | 9.6995 | 6.19 | 4.3000 | |
SMSTORE6 | 174.19 | Yes | Yes | 1.00 | SMSTORE6 | GENERAL | SMSTORE6 | 9.6995 | 6.19 | 4.3000 | |
SMSTORE7 | 174.19 | Yes | Yes | 1.00 | SMSTORE7 | GENERAL | SMSTORE7 | 9.6995 | 6.19 | 4.3000 | |
SMSTORE8 | 174.19 | Yes | Yes | 1.00 | SMSTORE8 | GENERAL | SMSTORE8 | 9.6995 | 6.19 | 4.3000 | |
Total | 2090.32 | 13.0683 | 3.10 | 4.3000 | |||||||
Conditioned Total | 2090.32 | 13.0683 | 3.10 | 4.3000 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 2090.32 | 2090.32 | 0.00 | 0.00 | 13.0683 | 6.19 | 4.3000 |
Total | 2090.32 | 2090.32 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:59
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 08-JUL-15:20 | 12-FEB-09:09 | - | - | - | - | - | - | - | - | - | - | 06-JAN-13:09 |
Heating | 0.00 | 205195.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 50048.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 23459.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 8059.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 7775.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 5426.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 94769.24 | 205195.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 205195.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 50048.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 23459.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 8059.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 7775.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 5426.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:59
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 209.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 570.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1161.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 190.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 405.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 305.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 196.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2829.64 | 209.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 100.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 273.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 555.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 91.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 194.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 145.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 93.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1353.69 | 100.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 100.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 273.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 555.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 91.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 194.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 145.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 93.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1353.69 | 100.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:59
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
LGSTORE1 DIRECT AIR | 2.00 |
SMSTORE1 DIRECT AIR | 1.06 |
SMSTORE2 DIRECT AIR | 1.07 |
SMSTORE3 DIRECT AIR | 1.07 |
SMSTORE4 DIRECT AIR | 1.06 |
LGSTORE2 DIRECT AIR | 1.86 |
SMSTORE5 DIRECT AIR | 0.964666 |
SMSTORE6 DIRECT AIR | 0.959816 |
SMSTORE7 DIRECT AIR | 0.960319 |
SMSTORE8 DIRECT AIR | 1.09 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC_1:1 | 2.00 | 2.00 | 2.00 | 2.00 | 2.00 | 2.00 | 1.00 | 1.00 | 2.00 |
PSZ-AC_2:2 | 1.06 | 1.06 | 1.06 | 1.06 | 1.06 | 1.06 | 1.00 | 1.00 | 1.06 |
PSZ-AC_3:3 | 1.07 | 1.07 | 1.07 | 1.07 | 1.07 | 1.07 | 1.00 | 1.00 | 1.07 |
PSZ-AC_4:4 | 1.07 | 1.07 | 1.07 | 1.07 | 1.07 | 1.07 | 1.00 | 1.000000 | 1.07 |
PSZ-AC_5:5 | 1.06 | 1.06 | 1.06 | 1.06 | 1.06 | 1.06 | 1.00 | 1.00 | 1.06 |
PSZ-AC_6:6 | 1.86 | 1.86 | 1.86 | 1.86 | 1.86 | 1.86 | 1.00 | 1.00 | 1.86 |
PSZ-AC_7:7 | 0.964666 | 0.964666 | 0.964666 | 0.964666 | 0.964666 | 0.964666 | 1.00 | 1.000000 | 0.964666 |
PSZ-AC_8:8 | 0.959816 | 0.959816 | 0.959816 | 0.959816 | 0.959816 | 0.959816 | 1.00 | 1.00 | 0.959816 |
PSZ-AC_9:9 | 0.960319 | 0.960319 | 0.960319 | 0.960319 | 0.960319 | 0.960319 | 1.00 | 1.000000 | 0.960319 |
PSZ-AC_10:10 | 1.09 | 1.09 | 1.09 | 1.09 | 1.09 | 1.09 | 1.00 | 1.00 | 1.09 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC_1:1_OA_CONTROLLER | 2.00 | 0.411479 |
PSZ-AC_2:2_OA_CONTROLLER | 1.06 | 0.205739 |
PSZ-AC_3:3_OA_CONTROLLER | 1.07 | 0.205739 |
PSZ-AC_4:4_OA_CONTROLLER | 1.07 | 0.205739 |
PSZ-AC_5:5_OA_CONTROLLER | 1.06 | 0.205739 |
PSZ-AC_6:6_OA_CONTROLLER | 1.86 | 0.411479 |
PSZ-AC_7:7_OA_CONTROLLER | 0.964666 | 0.205739 |
PSZ-AC_8:8_OA_CONTROLLER | 0.959816 | 0.205739 |
PSZ-AC_9:9_OA_CONTROLLER | 0.960319 | 0.205739 |
PSZ-AC_10:10_OA_CONTROLLER | 1.09 | 0.205739 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | 2.00 | 2142.88 |
PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | 1.06 | 1176.21 |
PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | 1.07 | 1180.91 |
PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | 1.07 | 1184.75 |
PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | 1.06 | 1173.22 |
PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | 1.86 | 1987.97 |
PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | 0.964666 | 1068.04 |
PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | 0.959816 | 1062.67 |
PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | 0.960319 | 1063.23 |
PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | 1.09 | 1209.36 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC_1:1_UNITARY_PACKAGE_DX | 2.00 | 2.00 | 2.00 | 1.32 | 46466.70 | 57296.53 | 40.00 | 1.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_DX | 1.06 | 1.06 | 1.06 | 0.701165 | 24302.11 | 29994.01 | 40.00 | 1.00 |
PSZ-AC_3:3_UNITARY_PACKAGE_DX | 1.07 | 1.07 | 1.07 | 0.703965 | 24374.47 | 30087.49 | 40.00 | 1.00 |
PSZ-AC_4:4_UNITARY_PACKAGE_DX | 1.07 | 1.07 | 1.07 | 0.706254 | 24432.76 | 30163.95 | 40.00 | 1.00 |
PSZ-AC_5:5_UNITARY_PACKAGE_DX | 1.06 | 1.06 | 1.06 | 0.699381 | 24258.66 | 29934.43 | 40.00 | 1.00 |
PSZ-AC_6:6_UNITARY_PACKAGE_DX | 1.86 | 1.86 | 1.86 | 1.23 | 43877.72 | 54104.70 | 40.00 | 1.00 |
PSZ-AC_7:7_UNITARY_PACKAGE_DX | 0.964666 | 0.964666 | 0.964666 | 0.636680 | 22660.67 | 27840.45 | 40.00 | 1.00 |
PSZ-AC_8:8_UNITARY_PACKAGE_DX | 0.959816 | 0.959816 | 0.959816 | 0.633479 | 22578.50 | 27733.55 | 40.00 | 1.00 |
PSZ-AC_9:9_UNITARY_PACKAGE_DX | 0.960319 | 0.960319 | 0.960319 | 0.633811 | 22587.68 | 27744.64 | 40.00 | 1.00 |
PSZ-AC_10:10_UNITARY_PACKAGE_DX | 1.09 | 1.09 | 1.09 | 0.720925 | 24800.25 | 30654.89 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-AC_1:1 COOLING COIL | 2.00 | 1.00 | 1.34 | 46466.70 | 23233.35 | 0.722290 | 0.722290 |
PSZ-AC_2:2 COOLING COIL | 1.06 | 0.531186 | 0.708247 | 24302.11 | 12151.06 | 0.727050 | 0.727050 |
PSZ-AC_3:3 COOLING COIL | 1.07 | 0.533307 | 0.711073 | 24374.47 | 12187.24 | 0.727320 | 0.727320 |
PSZ-AC_4:4 COOLING COIL | 1.07 | 0.535041 | 0.713387 | 24432.76 | 12216.38 | 0.727550 | 0.727550 |
PSZ-AC_5:5 COOLING COIL | 1.06 | 0.529834 | 0.706447 | 24258.66 | 12129.33 | 0.726850 | 0.726850 |
PSZ-AC_6:6 COOLING COIL | 1.86 | 0.928916 | 1.24 | 43877.72 | 21938.86 | 0.716690 | 0.716690 |
PSZ-AC_7:7 COOLING COIL | 0.964670 | 0.482333 | 0.643113 | 22660.67 | 11330.33 | 0.719080 | 0.719080 |
PSZ-AC_8:8 COOLING COIL | 0.959820 | 0.479908 | 0.639880 | 22578.50 | 11289.25 | 0.717720 | 0.717720 |
PSZ-AC_9:9 COOLING COIL | 0.960320 | 0.480160 | 0.640213 | 22587.68 | 11293.84 | 0.718750 | 0.718750 |
PSZ-AC_10:10 COOLING COIL | 1.09 | 0.546155 | 0.728207 | 24800.25 | 12400.12 | 0.730050 | 0.730050 |
Design Size Nominal Capacity [W] | |
PSZ-AC_1:1 HEATING COIL | 57296.53 |
PSZ-AC_2:2 HEATING COIL | 29994.01 |
PSZ-AC_3:3 HEATING COIL | 30087.49 |
PSZ-AC_4:4 HEATING COIL | 30163.95 |
PSZ-AC_5:5 HEATING COIL | 29934.43 |
PSZ-AC_6:6 HEATING COIL | 54104.70 |
PSZ-AC_7:7 HEATING COIL | 27840.45 |
PSZ-AC_8:8 HEATING COIL | 27733.55 |
PSZ-AC_9:9 HEATING COIL | 27744.64 |
PSZ-AC_10:10 HEATING COIL | 30654.89 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:59
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
LGSTORE1_WALL_3 | LGSTORE1_WALL_3_DOOR_1 | LGSTORE1_WALL_3_DOOR_2 | |
LGSTORE1_WALL_1 | LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | |
SMSTORE1_WALL_1 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | |
SMSTORE1_WALL_3 | SMSTORE1_WALL_3_DOOR | |
SMSTORE2_WALL_1 | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | |
SMSTORE2_WALL_3 | SMSTORE2_WALL_3_DOOR | |
SMSTORE3_WALL_1 | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | |
SMSTORE3_WALL_3 | SMSTORE3_WALL_3_DOOR | |
SMSTORE4_WALL_1 | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | |
SMSTORE4_WALL_3 | SMSTORE4_WALL_3_DOOR | |
LGSTORE2_WALL_3 | LGSTORE2_WALL_3_DOOR_1 | LGSTORE2_WALL_3_DOOR_2 | |
LGSTORE2_WALL_1 | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | |
SMSTORE5_WALL_1 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | |
SMSTORE5_WALL_3 | SMSTORE5_WALL_3_DOOR | |
SMSTORE6_WALL_1 | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | |
SMSTORE6_WALL_3 | SMSTORE6_WALL_3_DOOR | |
SMSTORE7_WALL_1 | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | |
SMSTORE7_WALL_3 | SMSTORE7_WALL_3_DOOR | |
SMSTORE8_WALL_1 | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR | |
SMSTORE8_WALL_3 | SMSTORE8_WALL_3_DOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:59
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:59
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 11.90 | 7.70 | 4.00 | 7.90 | 13.80 | 17.20 | 20.80 | 24.80 | 26.10 | 26.50 | 22.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190 | 33.63 | -84.43 | -5.00 | 308.00 | 97679 | 1.1610 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 16.60 | 22.50 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RetailStripmall | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 10 | 118 | 48 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | LGSTORE1 | 0.0 | 0.00 | 0.00 | 0.00 | 7.62 | 11.43 | 2.59 | 1 | 1 | 1 | 0.00 | 15.24 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 1805.20 | TARP | TARP | 348.39 | 276.30 | 247.74 | 20.77 | 6 | 8 | 0 | Yes |
2 | SMSTORE1 | 0.0 | 0.00 | 0.00 | 0.00 | 19.05 | 11.43 | 2.59 | 1 | 1 | 1 | 15.24 | 22.86 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.66 | 10.38 | 6 | 4 | 0 | Yes |
3 | SMSTORE2 | 0.0 | 0.00 | 0.00 | 0.00 | 26.67 | 11.43 | 2.59 | 1 | 1 | 1 | 22.86 | 30.48 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
4 | SMSTORE3 | 0.0 | 0.00 | 0.00 | 0.00 | 34.29 | 11.43 | 2.59 | 1 | 1 | 1 | 30.48 | 38.10 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
5 | SMSTORE4 | 0.0 | 0.00 | 0.00 | 0.00 | 41.91 | 11.43 | 2.59 | 1 | 1 | 1 | 38.10 | 45.72 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
6 | LGSTORE2 | 0.0 | 0.00 | 0.00 | 0.00 | 53.34 | 11.43 | 2.59 | 1 | 1 | 1 | 45.72 | 60.96 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 1805.20 | TARP | TARP | 348.39 | 157.89 | 129.41 | 20.72 | 6 | 8 | 0 | Yes |
7 | SMSTORE5 | 0.0 | 0.00 | 0.00 | 0.00 | 64.77 | 11.43 | 2.59 | 1 | 1 | 1 | 60.96 | 68.58 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
8 | SMSTORE6 | 0.0 | 0.00 | 0.00 | 0.00 | 72.39 | 11.43 | 2.59 | 1 | 1 | 1 | 68.58 | 76.20 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
9 | SMSTORE7 | 0.0 | 0.00 | 0.00 | 0.00 | 80.01 | 11.43 | 2.59 | 1 | 1 | 1 | 76.20 | 83.82 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
10 | SMSTORE8 | 0.0 | 0.00 | 0.00 | 0.00 | 87.63 | 11.43 | 2.59 | 1 | 1 | 1 | 83.82 | 91.44 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 197.36 | 183.12 | 10.36 | 6 | 4 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | LGSTORE1 | 348.39 | 56.3 | 6.193 | 0.161 | 15.302 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 19.602 | No |
2 | SMSTORE1 | 174.19 | 28.1 | 6.194 | 0.161 | 18.289 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 22.589 | No |
3 | SMSTORE2 | 174.19 | 28.1 | 6.194 | 0.161 | 16.653 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 20.953 | No |
4 | SMSTORE3 | 174.19 | 28.1 | 6.194 | 0.161 | 16.653 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 20.953 | No |
5 | SMSTORE4 | 174.19 | 28.1 | 6.194 | 0.161 | 16.653 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 20.953 | No |
6 | LGSTORE2 | 348.39 | 56.3 | 6.193 | 0.161 | 9.584 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 13.884 | No |
7 | SMSTORE5 | 174.19 | 28.1 | 6.194 | 0.161 | 9.699 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 13.999 | No |
8 | SMSTORE6 | 174.19 | 28.1 | 6.194 | 0.161 | 9.699 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 13.999 | No |
9 | SMSTORE7 | 174.19 | 28.1 | 6.194 | 0.161 | 9.699 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 13.999 | No |
10 | SMSTORE8 | 174.19 | 28.1 | 6.194 | 0.161 | 9.699 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 13.999 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | LGSTORE1 | TYPE1_OCC_SCH | LGSTORE1 | 348.39 | 56.3 | 56.3 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 56 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | SMSTORE1 | TYPE1_OCC_SCH | SMSTORE1 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | SMSTORE2 | TYPE2_OCC_SCH | SMSTORE2 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | SMSTORE3 | TYPE2_OCC_SCH | SMSTORE3 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | SMSTORE4 | TYPE2_OCC_SCH | SMSTORE4 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | LGSTORE2 | TYPE3_OCC_SCH | LGSTORE2 | 348.39 | 56.3 | 56.3 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 56 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | SMSTORE5 | TYPE3_OCC_SCH | SMSTORE5 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | SMSTORE6 | TYPE3_OCC_SCH | SMSTORE6 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | SMSTORE7 | TYPE3_OCC_SCH | SMSTORE7 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | SMSTORE8 | TYPE3_OCC_SCH | SMSTORE8 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | LGSTORE1_LIGHTS | LTG_SCH_BASE_LPD1 | LGSTORE1 | 348.39 | 56.3 | 3346.345 | 9.605 | 59.490 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3346.345 |
2 | LGSTORE1_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | LGSTORE1 | 348.39 | 56.3 | 1984.726 | 5.697 | 35.284 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1984.726 |
3 | SMSTORE1_LIGHTS | LTG_SCH_BASE_SMALL_LPD1 | SMSTORE1 | 174.19 | 28.1 | 1693.257 | 9.721 | 60.206 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1693.257 |
4 | SMSTORE1_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | SMSTORE1 | 174.19 | 28.1 | 1492.567 | 8.568 | 53.070 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1492.567 |
5 | SMSTORE2_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE2 | 174.19 | 28.1 | 1689.582 | 9.699 | 60.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1689.582 |
6 | SMSTORE2_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE2 | 174.19 | 28.1 | 1211.319 | 6.954 | 43.070 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1211.319 |
7 | SMSTORE3_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE3 | 174.19 | 28.1 | 1689.582 | 9.699 | 60.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1689.582 |
8 | SMSTORE3_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE3 | 174.19 | 28.1 | 1211.319 | 6.954 | 43.070 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1211.319 |
9 | SMSTORE4_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE4 | 174.19 | 28.1 | 1689.582 | 9.699 | 60.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1689.582 |
10 | SMSTORE4_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE4 | 174.19 | 28.1 | 1211.319 | 6.954 | 43.070 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1211.319 |
11 | LGSTORE2_LIGHTS | LTG_SCH_BASE_LPD2 | LGSTORE2 | 348.39 | 56.3 | 3338.998 | 9.584 | 59.359 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3338.998 |
12 | LGSTORE2_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | LGSTORE2 | 348.39 | 56.3 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
13 | SMSTORE5_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE5 | 174.19 | 28.1 | 1689.582 | 9.699 | 60.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1689.582 |
14 | SMSTORE5_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE5 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
15 | SMSTORE6_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE6 | 174.19 | 28.1 | 1689.582 | 9.699 | 60.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1689.582 |
16 | SMSTORE6_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE6 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
17 | SMSTORE7_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE7 | 174.19 | 28.1 | 1689.582 | 9.699 | 60.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1689.582 |
18 | SMSTORE7_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE7 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
19 | SMSTORE8_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE8 | 174.19 | 28.1 | 1689.582 | 9.699 | 60.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1689.582 |
20 | SMSTORE8_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE8 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LGSTORE1_MISCPLUG_EQUIP | TYPE1_EQUIP_SCH | LGSTORE1 | 348.39 | 56.3 | 1498.062 | 4.300 | 26.632 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1498.062 |
2 | SMSTORE1_MISCPLUG_EQUIP | TYPE1_EQUIP_SCH | SMSTORE1 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
3 | SMSTORE2_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE2 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
4 | SMSTORE3_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE3 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
5 | SMSTORE4_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE4 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
6 | LGSTORE2_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | LGSTORE2 | 348.39 | 56.3 | 1498.062 | 4.300 | 26.632 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1498.062 |
7 | SMSTORE5_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE5 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
8 | SMSTORE6_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE6 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
9 | SMSTORE7_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE7 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
10 | SMSTORE8_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE8 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.2284 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
5 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 0.6887 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
6 | LGSTORE1_FLOOR_FFACTOR | 36 | 2 | 7 | 0.167 | 0.1995 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
7 | SMSTORE1_FLOOR_FFACTOR | 37 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
8 | SMSTORE2_FLOOR_FFACTOR | 38 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | SMSTORE3_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
10 | SMSTORE4_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
11 | LGSTORE2_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | SMSTORE5_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | SMSTORE6_FLOOR_FFACTOR | 43 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | SMSTORE7_FLOOR_FFACTOR | 44 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | SMSTORE8_FLOOR_FFACTOR | 45 | 2 | 7 | 0.167 | 0.2888 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
6 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
7 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
8 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
10 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.218 |
11 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
12 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.937 |
13 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
14 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
15 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
16 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
17 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
18 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
19 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
20 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
21 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
22 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
23 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
24 | ~FC_Insulation_7 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_8 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_9 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_10 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.386 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
14 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
15 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
16 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
17 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
18 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
19 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
20 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
21 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
22 | 7 | -0.33074266E-12 | 0.10604805E-14 | -0.10376772E-12 | 0.10050050E-15 |
23 | 6 | 0.29711555E-07 | 0.19576406E-09 | 0.67975929E-08 | -0.14079383E-12 |
24 | 5 | -0.19537397E-03 | 0.16642354E-05 | -0.10041974E-03 | 0.67165186E-08 |
25 | 4 | 0.29828781 | 0.80514357E-03 | 0.10189302 | -0.34439683E-04 |
26 | 3 | -7.3878975 | 0.24810408E-01 | -2.3749899 | 0.29604922E-01 |
27 | 2 | 41.272027 | 0.87780140E-01 | 15.412956 | -0.33780550 |
28 | 1 | -80.852930 | 0.39442104E-01 | -29.274215 | 1.0851646 |
29 | 0 | 46.824337 | 0.79011109E-03 | 16.288086 | |
30 | 7 | -0.21163652E-08 | -0.68723841E-15 | 0.43910983E-14 | -0.57684426E-16 |
31 | 6 | 0.56109385E-05 | 0.38186281E-08 | 0.31898696E-02 | -0.26759299E-04 |
32 | 5 | -0.40164657E-03 | 0.22608617E-05 | -0.22372456 | 0.19561502E-02 |
33 | 4 | 0.92272104E-02 | 0.10289840E-03 | 4.8295456 | -0.45264980E-01 |
34 | 3 | -0.80993241E-01 | 0.81813938E-03 | -38.021416 | 0.39865375 |
35 | 2 | 0.28754352 | 0.13608947E-02 | 116.48395 | -1.4179393 |
36 | 1 | -0.41499682 | 0.41453381E-03 | -143.90731 | 2.0490399 |
37 | 0 | 0.20232414 | 0.10048102E-04 | 60.838472 | |
38 | 7 | -0.37862368E-08 | -0.38757603E-14 | 0.11479940E-14 | -0.41635801E-16 |
39 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
40 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
41 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
42 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
43 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
44 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
45 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
46 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479937E-14 | -0.41635796E-16 |
47 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
48 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
49 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
50 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
51 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
52 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
53 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
54 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479940E-14 | -0.41635801E-16 |
55 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
56 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
57 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
58 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
59 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
60 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
61 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
62 | 7 | -0.37862368E-08 | -0.38757603E-14 | 0.11479940E-14 | -0.41635801E-16 |
63 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
64 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
65 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
66 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
67 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
68 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
69 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
70 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479937E-14 | -0.41635796E-16 |
71 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
72 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
73 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
74 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
75 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
76 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
77 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
78 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479937E-14 | -0.41635796E-16 |
79 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
80 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
81 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
82 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
83 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
84 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
85 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
86 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479940E-14 | -0.41635801E-16 |
87 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
88 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
89 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
90 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
91 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
92 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
93 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
94 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479936E-14 | -0.41635794E-16 |
95 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
96 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
97 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
98 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
99 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
100 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
101 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
102 | 7 | -0.14484255E-08 | -0.22640907E-15 | 0.11860658E-13 | -0.17473455E-15 |
103 | 6 | 0.80640390E-05 | 0.55493782E-08 | 0.31828288E-02 | -0.26700235E-04 |
104 | 5 | -0.58275339E-03 | 0.32892043E-05 | -0.22332434 | 0.19526176E-02 |
105 | 4 | 0.13421983E-01 | 0.14977251E-03 | 4.8228790 | -0.45200897E-01 |
106 | 3 | -0.11791368 | 0.11914425E-02 | -37.983753 | 0.39823745 |
107 | 2 | 0.41875064 | 0.19825898E-02 | 116.41064 | -1.4169588 |
108 | 1 | -0.60444169 | 0.60433957E-03 | -143.86415 | 2.0483306 |
109 | 0 | 0.29470347 | 0.14596444E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.423_SHGC_0.25 | 35 | 1 | VerySmooth | 2.404 | 2.404 | 1.000 | 0.251 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 2.99333E-002 | 0.16139 | 0.62046 | 0.62046 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 0.12244 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | GAS TANK1 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
2 | WaterHeater:Mixed | GAS TANK2 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
3 | WaterHeater:Mixed | GAS TANK3 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
4 | WaterHeater:Mixed | GAS TANK4 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
5 | WaterHeater:Mixed | GAS TANK5 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
6 | WaterHeater:Mixed | GAS TANK6 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
7 | WaterHeater:Mixed | GAS TANK7 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | LGSTORE1_WALL_2 | 0 | 118.41 | 56.08 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
2 | LGSTORE1_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
3 | LGSTORE1_WALL_3_DOOR_1 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
4 | LGSTORE1_WALL_3_DOOR_2 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
5 | LGSTORE1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
6 | LGSTORE1_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
7 | LGSTORE1_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
8 | LGSTORE1_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
9 | LGSTORE1_WALL_1_WINDOW_3 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
10 | LGSTORE1_WALL_1_WINDOW_4 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
11 | LGSTORE1_WALL_1_DOOR_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 1 | No | No |
12 | LGSTORE1_WALL_1_DOOR_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 1 | No | No |
13 | LGSTORE1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
14 | LGSTORE1_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
15 | LGSTORE1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
16 | SMSTORE1_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
17 | SMSTORE1_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
18 | SMSTORE1_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
19 | SMSTORE1_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
20 | SMSTORE1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
21 | SMSTORE1_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
22 | SMSTORE1_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
23 | SMSTORE1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
24 | SMSTORE1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
25 | SMSTORE1_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
26 | SMSTORE1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
27 | SMSTORE2_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
28 | SMSTORE2_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
29 | SMSTORE2_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
30 | SMSTORE2_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
31 | SMSTORE2_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
32 | SMSTORE2_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
33 | SMSTORE2_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
34 | SMSTORE2_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
35 | SMSTORE2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
36 | SMSTORE2_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
37 | SMSTORE2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
38 | SMSTORE3_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
39 | SMSTORE3_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
40 | SMSTORE3_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
41 | SMSTORE3_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
42 | SMSTORE3_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
43 | SMSTORE3_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
44 | SMSTORE3_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
45 | SMSTORE3_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
46 | SMSTORE3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
47 | SMSTORE3_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
48 | SMSTORE3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
49 | SMSTORE4_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
50 | SMSTORE4_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
51 | SMSTORE4_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
52 | SMSTORE4_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
53 | SMSTORE4_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
54 | SMSTORE4_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 3 | No | No |
55 | SMSTORE4_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
56 | SMSTORE4_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
57 | SMSTORE4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
58 | SMSTORE4_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
59 | SMSTORE4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
60 | LGSTORE2_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
61 | LGSTORE2_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 4 | No | No |
62 | LGSTORE2_WALL_3_DOOR_1 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
63 | LGSTORE2_WALL_3_DOOR_2 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
64 | LGSTORE2_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
65 | LGSTORE2_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 4 | No | No |
66 | LGSTORE2_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
67 | LGSTORE2_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
68 | LGSTORE2_WALL_1_WINDOW_3 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
69 | LGSTORE2_WALL_1_WINDOW_4 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
70 | LGSTORE2_WALL_1_DOOR_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
71 | LGSTORE2_WALL_1_DOOR_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
72 | LGSTORE2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
73 | LGSTORE2_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
74 | LGSTORE2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
75 | SMSTORE5_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
76 | SMSTORE5_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
77 | SMSTORE5_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
78 | SMSTORE5_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
79 | SMSTORE5_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
80 | SMSTORE5_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
81 | SMSTORE5_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
82 | SMSTORE5_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
83 | SMSTORE5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
84 | SMSTORE5_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
85 | SMSTORE5_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
86 | SMSTORE6_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
87 | SMSTORE6_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
88 | SMSTORE6_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
89 | SMSTORE6_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
90 | SMSTORE6_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
91 | SMSTORE6_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
92 | SMSTORE6_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
93 | SMSTORE6_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
94 | SMSTORE6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
95 | SMSTORE6_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
96 | SMSTORE6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
97 | SMSTORE7_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
98 | SMSTORE7_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
99 | SMSTORE7_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
100 | SMSTORE7_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
101 | SMSTORE7_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
102 | SMSTORE7_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 3 | No | No |
103 | SMSTORE7_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
104 | SMSTORE7_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
105 | SMSTORE7_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
106 | SMSTORE7_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
107 | SMSTORE7_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
108 | SMSTORE8_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 4 | No | No |
109 | SMSTORE8_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 2 | No | No |
110 | SMSTORE8_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 2 | No | No |
111 | SMSTORE8_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 1 | No | No |
112 | SMSTORE8_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
113 | SMSTORE8_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 3 | No | No |
114 | SMSTORE8_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
115 | SMSTORE8_WALL_4 | 0 | 118.41 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 3 | No | No |
116 | SMSTORE8_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
117 | SMSTORE8_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
118 | SMSTORE8_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | LGSTORE1_INFILTRATION | TYPE1_INFIL_SCH | LGSTORE1 | 348.39 | 56.3 | 0.157 | 4.517E-004 | 2.488E-004 | 0.314 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | LGSTORE1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LGSTORE1 | 348.39 | 56.3 | 0.241 | 6.922E-004 | 3.813E-004 | 0.481 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | SMSTORE1_INFILTRATION | TYPE1_INFIL_SCH | SMSTORE1 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | SMSTORE1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE1 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | SMSTORE2_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE2 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | SMSTORE2_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE2 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | SMSTORE3_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE3 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | SMSTORE3_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE3 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | SMSTORE4_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE4 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | SMSTORE4_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE4 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | LGSTORE2_INFILTRATION | TYPE3_INFIL_SCH | LGSTORE2 | 348.39 | 56.3 | 8.993E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | LGSTORE2_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LGSTORE2 | 348.39 | 56.3 | 0.241 | 6.922E-004 | 4.692E-004 | 0.481 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | SMSTORE5_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE5 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | SMSTORE5_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE5 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | SMSTORE6_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE6 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | SMSTORE6_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE6 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | SMSTORE7_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE7 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
18 | SMSTORE7_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE7 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | SMSTORE8_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE8 | 174.19 | 28.1 | 0.112 | 6.453E-004 | 2.994E-004 | 0.448 | 0.000 | 0.000 | 0.224 | 0.000 |
20 | SMSTORE8_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE8 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 3.583E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | LGSTORE1 | Mixing/Well-Stirred |
2 | SMSTORE1 | Mixing/Well-Stirred |
3 | SMSTORE2 | Mixing/Well-Stirred |
4 | SMSTORE3 | Mixing/Well-Stirred |
5 | SMSTORE4 | Mixing/Well-Stirred |
6 | LGSTORE2 | Mixing/Well-Stirred |
7 | SMSTORE5 | Mixing/Well-Stirred |
8 | SMSTORE6 | Mixing/Well-Stirred |
9 | SMSTORE7 | Mixing/Well-Stirred |
10 | SMSTORE8 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone LGSTORE1 | 1.2000 |
3 | Zone SMSTORE1 | 1.2000 |
4 | Zone SMSTORE2 | 1.2000 |
5 | Zone SMSTORE3 | 1.2000 |
6 | Zone SMSTORE4 | 1.2000 |
7 | Zone LGSTORE2 | 1.2000 |
8 | Zone SMSTORE5 | 1.2000 |
9 | Zone SMSTORE6 | 1.2000 |
10 | Zone SMSTORE7 | 1.2000 |
11 | Zone SMSTORE8 | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone LGSTORE1 | 1.2000 |
3 | Zone SMSTORE1 | 1.2000 |
4 | Zone SMSTORE2 | 1.2000 |
5 | Zone SMSTORE3 | 1.2000 |
6 | Zone SMSTORE4 | 1.2000 |
7 | Zone LGSTORE2 | 1.2000 |
8 | Zone SMSTORE5 | 1.2000 |
9 | Zone SMSTORE6 | 1.2000 |
10 | Zone SMSTORE7 | 1.2000 |
11 | Zone SMSTORE8 | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | LGSTORE1 | Cooling | 21920.04394 | 26304.05272 | 1.66883 | 2.00260 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 34.40000 | 1.44733E-002 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
2 | LGSTORE1 | Heating | 21954.84964 | 26345.81957 | 0.98156 | 1.17787 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -6.30000 | 2.29779E-003 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
3 | SMSTORE1 | Cooling | 11628.61018 | 13954.33222 | 0.88531 | 1.06237 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 34.40000 | 1.44733E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
4 | SMSTORE1 | Heating | 10142.60764 | 12171.12917 | 0.45347 | 0.54416 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -6.30000 | 2.29779E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
5 | SMSTORE2 | Cooling | 11675.07068 | 14010.08482 | 0.88884 | 1.06661 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 34.32083 | 1.44731E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
6 | SMSTORE2 | Heating | 10290.90670 | 12349.08803 | 0.46010 | 0.55211 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -6.30000 | 2.29779E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
7 | SMSTORE3 | Cooling | 11713.03983 | 14055.64780 | 0.89173 | 1.07008 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 34.32083 | 1.44731E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
8 | SMSTORE3 | Heating | 10399.54970 | 12479.45964 | 0.46495 | 0.55794 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -6.30000 | 2.29779E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
9 | SMSTORE4 | Cooling | 11599.06183 | 13918.87420 | 0.88306 | 1.05967 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 34.32083 | 1.44731E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
10 | SMSTORE4 | Heating | 10567.23906 | 12680.68687 | 0.47245 | 0.56694 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -6.30000 | 2.29779E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
11 | LGSTORE2 | Cooling | 20335.86165 | 24403.03397 | 1.54819 | 1.85783 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 34.32083 | 1.44731E-002 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
12 | LGSTORE2 | Heating | 20466.06176 | 24559.27411 | 0.91502 | 1.09803 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -6.30000 | 2.29779E-003 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
13 | SMSTORE5 | Cooling | 10559.25600 | 12671.10721 | 0.80389 | 0.96467 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 34.24167 | 1.44730E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
14 | SMSTORE5 | Heating | 10892.83157 | 13071.39788 | 0.48701 | 0.58441 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -6.30000 | 2.29779E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
15 | SMSTORE6 | Cooling | 10506.16836 | 12607.40203 | 0.79985 | 0.95982 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 34.24167 | 1.44730E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
16 | SMSTORE6 | Heating | 10883.67550 | 13060.41060 | 0.48660 | 0.58392 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -6.30000 | 2.29779E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
17 | SMSTORE7 | Cooling | 10511.67745 | 12614.01294 | 0.80027 | 0.96032 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 34.24167 | 1.44730E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
18 | SMSTORE7 | Heating | 11108.58073 | 13330.29688 | 0.49665 | 0.59598 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -6.30000 | 2.29779E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
19 | SMSTORE8 | Cooling | 11957.20129 | 14348.64155 | 0.91026 | 1.09231 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | 33.92500 | 1.44724E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
20 | SMSTORE8 | Heating | 13768.74134 | 16522.48961 | 0.61555 | 0.73866 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -6.30000 | 2.29779E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC_1:1 | Cooling | Sensible | 30944.96 | 2.00260 | 2.00260 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-AC_1:1 | Heating | Sensible | 39118.23 | 1.17787 | 1.17787 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
3 | PSZ-AC_2:2 | Cooling | Sensible | 16262.35 | 1.06237 | 1.06237 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-AC_2:2 | Heating | Sensible | 18572.01 | 0.54416 | 0.54416 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
5 | PSZ-AC_3:3 | Cooling | Sensible | 16314.16 | 1.06661 | 1.06661 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
6 | PSZ-AC_3:3 | Heating | Sensible | 18747.38 | 0.55211 | 0.55211 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
7 | PSZ-AC_4:4 | Cooling | Sensible | 16358.27 | 1.07008 | 1.07008 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
8 | PSZ-AC_4:4 | Heating | Sensible | 18875.85 | 0.55794 | 0.55794 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
9 | PSZ-AC_5:5 | Cooling | Sensible | 16223.92 | 1.05967 | 1.05967 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
10 | PSZ-AC_5:5 | Heating | Sensible | 19074.15 | 0.56694 | 0.56694 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
11 | PSZ-AC_6:6 | Cooling | Sensible | 29068.30 | 1.85783 | 1.85783 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
12 | PSZ-AC_6:6 | Heating | Sensible | 37357.97 | 1.09803 | 1.09803 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
13 | PSZ-AC_7:7 | Cooling | Sensible | 14994.45 | 0.96467 | 0.96467 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
14 | PSZ-AC_7:7 | Heating | Sensible | 19459.17 | 0.58441 | 0.58441 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
15 | PSZ-AC_8:8 | Cooling | Sensible | 14931.66 | 0.95982 | 0.95982 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
16 | PSZ-AC_8:8 | Heating | Sensible | 19448.35 | 0.58392 | 0.58392 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
17 | PSZ-AC_9:9 | Cooling | Sensible | 14936.88 | 0.96032 | 0.96032 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
18 | PSZ-AC_9:9 | Heating | Sensible | 19714.30 | 0.59598 | 0.59598 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
19 | PSZ-AC_10:10 | Cooling | Sensible | 16538.81 | 1.09231 | 1.09231 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
20 | PSZ-AC_10:10 | Heating | Sensible | 22859.76 | 0.73866 | 0.73866 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | LGSTORE1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.00260 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.06237 |
3 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.06661 |
4 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.07008 |
5 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE4 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.05967 |
6 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | LGSTORE2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.85783 |
7 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE5 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.96467 |
8 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.95982 |
9 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE7 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.96032 |
10 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE8 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.09231 |
11 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.00260 |
12 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.00260 |
13 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.00260 |
14 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 2.00260 |
15 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.00260 |
16 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Main Design Air Flow Rate [m3/s] | 2.00260 |
17 | AirLoopHVAC | PSZ-AC_1:1 | User Heating Air Flow Ratio [] | 1.00000 |
18 | AirLoopHVAC | PSZ-AC_1:1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
19 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.06237 |
20 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.06237 |
21 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.06237 |
22 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.06237 |
23 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.06237 |
24 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Main Design Air Flow Rate [m3/s] | 1.06237 |
25 | AirLoopHVAC | PSZ-AC_2:2 | User Heating Air Flow Ratio [] | 1.00000 |
26 | AirLoopHVAC | PSZ-AC_2:2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
27 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.06661 |
28 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.06661 |
29 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.06661 |
30 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.06661 |
31 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.06661 |
32 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Main Design Air Flow Rate [m3/s] | 1.06661 |
33 | AirLoopHVAC | PSZ-AC_3:3 | User Heating Air Flow Ratio [] | 1.00000 |
34 | AirLoopHVAC | PSZ-AC_3:3 | Calculated Heating Air Flow Ratio [] | 1.00000 |
35 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.07008 |
36 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.07008 |
37 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.07008 |
38 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.07008 |
39 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.07008 |
40 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Main Design Air Flow Rate [m3/s] | 1.07008 |
41 | AirLoopHVAC | PSZ-AC_4:4 | User Heating Air Flow Ratio [] | 1.00000 |
42 | AirLoopHVAC | PSZ-AC_4:4 | Calculated Heating Air Flow Ratio [] | 1.00000 |
43 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.05967 |
44 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.05967 |
45 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.05967 |
46 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.05967 |
47 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.05967 |
48 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Main Design Air Flow Rate [m3/s] | 1.05967 |
49 | AirLoopHVAC | PSZ-AC_5:5 | User Heating Air Flow Ratio [] | 1.00000 |
50 | AirLoopHVAC | PSZ-AC_5:5 | Calculated Heating Air Flow Ratio [] | 1.00000 |
51 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.85783 |
52 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.85783 |
53 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.85783 |
54 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.85783 |
55 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.85783 |
56 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Main Design Air Flow Rate [m3/s] | 1.85783 |
57 | AirLoopHVAC | PSZ-AC_6:6 | User Heating Air Flow Ratio [] | 1.00000 |
58 | AirLoopHVAC | PSZ-AC_6:6 | Calculated Heating Air Flow Ratio [] | 1.00000 |
59 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.96467 |
60 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.96467 |
61 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.96467 |
62 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.96467 |
63 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.96467 |
64 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Main Design Air Flow Rate [m3/s] | 0.96467 |
65 | AirLoopHVAC | PSZ-AC_7:7 | User Heating Air Flow Ratio [] | 1.00000 |
66 | AirLoopHVAC | PSZ-AC_7:7 | Calculated Heating Air Flow Ratio [] | 1.00000 |
67 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.95982 |
68 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.95982 |
69 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.95982 |
70 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.95982 |
71 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.95982 |
72 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Main Design Air Flow Rate [m3/s] | 0.95982 |
73 | AirLoopHVAC | PSZ-AC_8:8 | User Heating Air Flow Ratio [] | 1.00000 |
74 | AirLoopHVAC | PSZ-AC_8:8 | Calculated Heating Air Flow Ratio [] | 1.00000 |
75 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.96032 |
76 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.96032 |
77 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.96032 |
78 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.96032 |
79 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.96032 |
80 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Main Design Air Flow Rate [m3/s] | 0.96032 |
81 | AirLoopHVAC | PSZ-AC_9:9 | User Heating Air Flow Ratio [] | 1.00000 |
82 | AirLoopHVAC | PSZ-AC_9:9 | Calculated Heating Air Flow Ratio [] | 1.00000 |
83 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.09231 |
84 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.09231 |
85 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.09231 |
86 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.09231 |
87 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.09231 |
88 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Main Design Air Flow Rate [m3/s] | 1.09231 |
89 | AirLoopHVAC | PSZ-AC_10:10 | User Heating Air Flow Ratio [] | 1.00000 |
90 | AirLoopHVAC | PSZ-AC_10:10 | Calculated Heating Air Flow Ratio [] | 1.00000 |
91 | AirLoopHVAC | PSZ-AC_1:1 | Design Supply Air Flow Rate [m3/s] | 2.00260 |
92 | AirLoopHVAC | PSZ-AC_2:2 | Design Supply Air Flow Rate [m3/s] | 1.06237 |
93 | AirLoopHVAC | PSZ-AC_3:3 | Design Supply Air Flow Rate [m3/s] | 1.06661 |
94 | AirLoopHVAC | PSZ-AC_4:4 | Design Supply Air Flow Rate [m3/s] | 1.07008 |
95 | AirLoopHVAC | PSZ-AC_5:5 | Design Supply Air Flow Rate [m3/s] | 1.05967 |
96 | AirLoopHVAC | PSZ-AC_6:6 | Design Supply Air Flow Rate [m3/s] | 1.85783 |
97 | AirLoopHVAC | PSZ-AC_7:7 | Design Supply Air Flow Rate [m3/s] | 0.96467 |
98 | AirLoopHVAC | PSZ-AC_8:8 | Design Supply Air Flow Rate [m3/s] | 0.95982 |
99 | AirLoopHVAC | PSZ-AC_9:9 | Design Supply Air Flow Rate [m3/s] | 0.96032 |
100 | AirLoopHVAC | PSZ-AC_10:10 | Design Supply Air Flow Rate [m3/s] | 1.09231 |
101 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.00260 |
102 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41148 |
103 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.00260 |
104 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 2142.87790 |
105 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.00260 |
106 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.00260 |
107 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.00260 |
108 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.32172 |
109 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.00260 |
110 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.00130 |
111 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.33507 |
112 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 46466.70000 |
113 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 23233.35000 |
114 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.72229 |
115 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.72229 |
116 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 46466.70000 |
117 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 57296.53456 |
118 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
119 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
120 | Coil:Heating:Fuel | PSZ-AC_1:1 HEATING COIL | Design Size Nominal Capacity [W] | 57296.53456 |
121 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.06237 |
122 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
123 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.06237 |
124 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1176.21390 |
125 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.06237 |
126 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.06237 |
127 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.06237 |
128 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.70117 |
129 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.06237 |
130 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.53119 |
131 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.70825 |
132 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 24302.11000 |
133 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 12151.05500 |
134 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.72705 |
135 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.72705 |
136 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 24302.11000 |
137 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 29994.00890 |
138 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
139 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
140 | Coil:Heating:Fuel | PSZ-AC_2:2 HEATING COIL | Design Size Nominal Capacity [W] | 29994.00890 |
141 | Controller:OutdoorAir | PSZ-AC_3:3_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.06661 |
142 | Controller:OutdoorAir | PSZ-AC_3:3_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
143 | Fan:SystemModel | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.06661 |
144 | Fan:SystemModel | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1180.91012 |
145 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.06661 |
146 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.06661 |
147 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.06661 |
148 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.70396 |
149 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.06661 |
150 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.53331 |
151 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.71107 |
152 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 24374.47000 |
153 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 12187.23500 |
154 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.72732 |
155 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.72732 |
156 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 24374.47000 |
157 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 30087.49443 |
158 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
159 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
160 | Coil:Heating:Fuel | PSZ-AC_3:3 HEATING COIL | Design Size Nominal Capacity [W] | 30087.49443 |
161 | Controller:OutdoorAir | PSZ-AC_4:4_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.07008 |
162 | Controller:OutdoorAir | PSZ-AC_4:4_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
163 | Fan:SystemModel | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.07008 |
164 | Fan:SystemModel | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1184.75062 |
165 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.07008 |
166 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.07008 |
167 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.07008 |
168 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.70625 |
169 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.07008 |
170 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.53504 |
171 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.71339 |
172 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 24432.76000 |
173 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 12216.38000 |
174 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.72755 |
175 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.72755 |
176 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 24432.76000 |
177 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 30163.94968 |
178 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
179 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
180 | Coil:Heating:Fuel | PSZ-AC_4:4 HEATING COIL | Design Size Nominal Capacity [W] | 30163.94968 |
181 | Controller:OutdoorAir | PSZ-AC_5:5_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.05967 |
182 | Controller:OutdoorAir | PSZ-AC_5:5_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
183 | Fan:SystemModel | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.05967 |
184 | Fan:SystemModel | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1173.22163 |
185 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.05967 |
186 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.05967 |
187 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.05967 |
188 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.69938 |
189 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.05967 |
190 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.52983 |
191 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.70645 |
192 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 24258.66000 |
193 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 12129.33000 |
194 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.72685 |
195 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.72685 |
196 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 24258.66000 |
197 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 29934.42682 |
198 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
199 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
200 | Coil:Heating:Fuel | PSZ-AC_5:5 HEATING COIL | Design Size Nominal Capacity [W] | 29934.42682 |
201 | Controller:OutdoorAir | PSZ-AC_6:6_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.85783 |
202 | Controller:OutdoorAir | PSZ-AC_6:6_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41148 |
203 | Fan:SystemModel | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.85783 |
204 | Fan:SystemModel | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1987.96872 |
205 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.85783 |
206 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.85783 |
207 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.85783 |
208 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.22617 |
209 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.85783 |
210 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.92892 |
211 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.23855 |
212 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 43877.72000 |
213 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 21938.86000 |
214 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.71669 |
215 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.71669 |
216 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 43877.72000 |
217 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 54104.69552 |
218 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
219 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
220 | Coil:Heating:Fuel | PSZ-AC_6:6 HEATING COIL | Design Size Nominal Capacity [W] | 54104.69552 |
221 | Controller:OutdoorAir | PSZ-AC_7:7_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.96467 |
222 | Controller:OutdoorAir | PSZ-AC_7:7_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
223 | Fan:SystemModel | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.96467 |
224 | Fan:SystemModel | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1068.03874 |
225 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.96467 |
226 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.96467 |
227 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.96467 |
228 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.63668 |
229 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.96467 |
230 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.48233 |
231 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.64311 |
232 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 22660.67000 |
233 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 11330.33500 |
234 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.71908 |
235 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.71908 |
236 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 22660.67000 |
237 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 27840.45482 |
238 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
239 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
240 | Coil:Heating:Fuel | PSZ-AC_7:7 HEATING COIL | Design Size Nominal Capacity [W] | 27840.45482 |
241 | Controller:OutdoorAir | PSZ-AC_8:8_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.95982 |
242 | Controller:OutdoorAir | PSZ-AC_8:8_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
243 | Fan:SystemModel | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.95982 |
244 | Fan:SystemModel | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1062.66899 |
245 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.95982 |
246 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.95982 |
247 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.95982 |
248 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.63348 |
249 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.95982 |
250 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.47991 |
251 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.63988 |
252 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 22578.50000 |
253 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 11289.25000 |
254 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.71772 |
255 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.71772 |
256 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 22578.50000 |
257 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 27733.55421 |
258 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
259 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
260 | Coil:Heating:Fuel | PSZ-AC_8:8 HEATING COIL | Design Size Nominal Capacity [W] | 27733.55421 |
261 | Controller:OutdoorAir | PSZ-AC_9:9_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.96032 |
262 | Controller:OutdoorAir | PSZ-AC_9:9_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
263 | Fan:SystemModel | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.96032 |
264 | Fan:SystemModel | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1063.22595 |
265 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.96032 |
266 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.96032 |
267 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.96032 |
268 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.63381 |
269 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.96032 |
270 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.48016 |
271 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.64021 |
272 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 22587.68000 |
273 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 11293.84000 |
274 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.71875 |
275 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.71875 |
276 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 22587.68000 |
277 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 27744.63994 |
278 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
279 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
280 | Coil:Heating:Fuel | PSZ-AC_9:9 HEATING COIL | Design Size Nominal Capacity [W] | 27744.63994 |
281 | Controller:OutdoorAir | PSZ-AC_10:10_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.09231 |
282 | Controller:OutdoorAir | PSZ-AC_10:10_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
283 | Fan:SystemModel | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.09231 |
284 | Fan:SystemModel | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1209.36054 |
285 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.09231 |
286 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.09231 |
287 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.09231 |
288 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.72092 |
289 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.09231 |
290 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.54615 |
291 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.72821 |
292 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 24800.25000 |
293 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 12400.12500 |
294 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.73005 |
295 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.73005 |
296 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 24800.25000 |
297 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 30654.88971 |
298 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
299 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
300 | Coil:Heating:Fuel | PSZ-AC_10:10 HEATING COIL | Design Size Nominal Capacity [W] | 30654.88971 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | 44888.9 | 11.65 | 11.65 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | 23465.3 | 11.80 | 11.80 | |||
3 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | 23534.3 | 11.80 | 11.80 | |||
4 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | 23589.9 | 11.79 | 11.79 | |||
5 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | 23424.0 | 11.80 | 11.80 | |||
6 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | 42413.5 | 11.68 | 11.68 | |||
7 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | 21900.4 | 11.85 | 11.85 | |||
8 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | 21822.1 | 11.85 | 11.85 | |||
9 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | 21830.9 | 11.85 | 11.85 | |||
10 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | 23940.0 | 11.78 | 11.78 |
Zone Name | # Surfaces | |
1 | LGSTORE1 | 15 |
2 | SMSTORE1 | 11 |
3 | SMSTORE2 | 11 |
4 | SMSTORE3 | 11 |
5 | SMSTORE4 | 11 |
6 | LGSTORE2 | 15 |
7 | SMSTORE5 | 11 |
8 | SMSTORE6 | 11 |
9 | SMSTORE7 | 11 |
10 | SMSTORE8 | 11 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | LGSTORE1_WALL_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.689 | 0.624 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | LGSTORE1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.689 | 0.624 | 71.15 | 78.94 | 71.15 | 0.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | LGSTORE1_WALL_3_DOOR_1 | Door | LGSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
4 | LGSTORE1_WALL_3_DOOR_2 | Door | LGSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
5 | LGSTORE1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
6 | LGSTORE1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.689 | 0.624 | 58.18 | 78.94 | 58.18 | 180.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
7 | LGSTORE1_WALL_1_WINDOW_1 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.423_SHGC_0.25 | N/A | 2.404 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
8 | LGSTORE1_WALL_1_WINDOW_2 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.423_SHGC_0.25 | N/A | 2.404 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
9 | LGSTORE1_WALL_1_WINDOW_3 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.423_SHGC_0.25 | N/A | 2.404 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
10 | LGSTORE1_WALL_1_WINDOW_4 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.423_SHGC_0.25 | N/A | 2.404 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
11 | LGSTORE1_WALL_1_DOOR_1 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.423_SHGC_0.25 | N/A | 2.404 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
12 | LGSTORE1_WALL_1_DOOR_2 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.423_SHGC_0.25 | N/A | 2.404 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
13 | LGSTORE1_FLOOR | Floor | CTF - ConductionTransferFunction | LGSTORE1_FLOOR_FFACTOR | 0.199 | 0.190 | 348.39 | 348.39 | 348.39 | 270.00 | 180.00 | 22.86 | 15.24 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | LGSTORE1_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 348.39 | 348.39 | 348.39 | 270.00 | 0.00 | 22.86 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
15 | LGSTORE1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 696.77 | 696.77 | 696.77 | 0.00 | 90.00 | 696.77 | 1.00 | 0.00 | LGSTORE1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
16 | SMSTORE1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.689 | 0.624 | 29.09 | 39.47 | 29.09 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
17 | SMSTORE1_WALL_1_WINDOW_1 | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.423_SHGC_0.25 | N/A | 2.404 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
18 | SMSTORE1_WALL_1_WINDOW_2 | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.423_SHGC_0.25 | N/A | 2.404 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
19 | SMSTORE1_WALL_1_DOOR | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.423_SHGC_0.25 | N/A | 2.404 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
20 | SMSTORE1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | SMSTORE1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.689 | 0.624 | 35.57 | 39.47 | 35.57 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | SMSTORE1_WALL_3_DOOR | Door | SMSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
23 | SMSTORE1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE2_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | SMSTORE1_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE1_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | SMSTORE1_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
26 | SMSTORE1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
27 | SMSTORE2_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.689 | 0.624 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | SMSTORE2_WALL_1_WINDOW_1 | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.423_SHGC_0.25 | N/A | 2.404 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
29 | SMSTORE2_WALL_1_WINDOW_2 | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.423_SHGC_0.25 | N/A | 2.404 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
30 | SMSTORE2_WALL_1_DOOR | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.423_SHGC_0.25 | N/A | 2.404 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
31 | SMSTORE2_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | SMSTORE2_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.689 | 0.624 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | SMSTORE2_WALL_3_DOOR | Door | SMSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
34 | SMSTORE2_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE3_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | SMSTORE2_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE2_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | SMSTORE2_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | SMSTORE2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | SMSTORE3_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.689 | 0.624 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | SMSTORE3_WALL_1_WINDOW_1 | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.423_SHGC_0.25 | N/A | 2.404 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
40 | SMSTORE3_WALL_1_WINDOW_2 | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.423_SHGC_0.25 | N/A | 2.404 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
41 | SMSTORE3_WALL_1_DOOR | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.423_SHGC_0.25 | N/A | 2.404 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
42 | SMSTORE3_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE2_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | SMSTORE3_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.689 | 0.624 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | SMSTORE3_WALL_3_DOOR | Door | SMSTORE3_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
45 | SMSTORE3_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE4_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | SMSTORE3_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE3_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
47 | SMSTORE3_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
48 | SMSTORE3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
49 | SMSTORE4_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.689 | 0.624 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | SMSTORE4_WALL_1_WINDOW_1 | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.423_SHGC_0.25 | N/A | 2.404 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
51 | SMSTORE4_WALL_1_WINDOW_2 | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.423_SHGC_0.25 | N/A | 2.404 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
52 | SMSTORE4_WALL_1_DOOR | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.423_SHGC_0.25 | N/A | 2.404 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | SMSTORE4_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE3_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | SMSTORE4_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.689 | 0.624 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | SMSTORE4_WALL_3_DOOR | Door | SMSTORE4_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | SMSTORE4_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE2_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | SMSTORE4_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE4_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | SMSTORE4_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | SMSTORE4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | LGSTORE2_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE4_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | LGSTORE2_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.689 | 0.624 | 71.19 | 78.94 | 71.19 | 0.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
62 | LGSTORE2_WALL_3_DOOR_1 | Door | LGSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
63 | LGSTORE2_WALL_3_DOOR_2 | Door | LGSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
64 | LGSTORE2_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE5_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LGSTORE2_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.689 | 0.624 | 58.22 | 78.94 | 58.22 | 180.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
66 | LGSTORE2_WALL_1_WINDOW_1 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.423_SHGC_0.25 | N/A | 2.404 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | LGSTORE2_WALL_1_WINDOW_2 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.423_SHGC_0.25 | N/A | 2.404 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | LGSTORE2_WALL_1_WINDOW_3 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.423_SHGC_0.25 | N/A | 2.404 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | LGSTORE2_WALL_1_WINDOW_4 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.423_SHGC_0.25 | N/A | 2.404 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LGSTORE2_WALL_1_DOOR_1 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.423_SHGC_0.25 | N/A | 2.404 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
71 | LGSTORE2_WALL_1_DOOR_2 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.423_SHGC_0.25 | N/A | 2.404 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
72 | LGSTORE2_FLOOR | Floor | CTF - ConductionTransferFunction | LGSTORE2_FLOOR_FFACTOR | 0.112 | 0.109 | 348.39 | 348.39 | 348.39 | 270.00 | 180.00 | 22.86 | 15.24 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
73 | LGSTORE2_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 348.39 | 348.39 | 348.39 | 270.00 | 0.00 | 22.86 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
74 | LGSTORE2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 696.77 | 696.77 | 696.77 | 0.00 | 90.00 | 696.77 | 1.00 | 0.00 | LGSTORE2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
75 | SMSTORE5_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.689 | 0.624 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | SMSTORE5_WALL_1_WINDOW_1 | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.423_SHGC_0.25 | N/A | 2.404 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
77 | SMSTORE5_WALL_1_WINDOW_2 | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.423_SHGC_0.25 | N/A | 2.404 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | SMSTORE5_WALL_1_DOOR | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.423_SHGC_0.25 | N/A | 2.404 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
79 | SMSTORE5_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE2_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | SMSTORE5_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.689 | 0.624 | 35.59 | 39.47 | 35.59 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | SMSTORE5_WALL_3_DOOR | Door | SMSTORE5_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
82 | SMSTORE5_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE6_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
83 | SMSTORE5_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE5_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
84 | SMSTORE5_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
85 | SMSTORE5_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE5_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | SMSTORE6_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.689 | 0.624 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | SMSTORE6_WALL_1_WINDOW_1 | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.423_SHGC_0.25 | N/A | 2.404 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | SMSTORE6_WALL_1_WINDOW_2 | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.423_SHGC_0.25 | N/A | 2.404 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
89 | SMSTORE6_WALL_1_DOOR | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.423_SHGC_0.25 | N/A | 2.404 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | SMSTORE6_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE5_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | SMSTORE6_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.689 | 0.624 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | SMSTORE6_WALL_3_DOOR | Door | SMSTORE6_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
93 | SMSTORE6_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE7_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | SMSTORE6_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE6_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
95 | SMSTORE6_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
96 | SMSTORE6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
97 | SMSTORE7_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.689 | 0.624 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | SMSTORE7_WALL_1_WINDOW_1 | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.423_SHGC_0.25 | N/A | 2.404 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | SMSTORE7_WALL_1_WINDOW_2 | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.423_SHGC_0.25 | N/A | 2.404 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
100 | SMSTORE7_WALL_1_DOOR | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.423_SHGC_0.25 | N/A | 2.404 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
101 | SMSTORE7_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE6_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
102 | SMSTORE7_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.689 | 0.624 | 35.59 | 39.47 | 35.59 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | SMSTORE7_WALL_3_DOOR | Door | SMSTORE7_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
104 | SMSTORE7_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE8_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | SMSTORE7_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE7_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
106 | SMSTORE7_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
107 | SMSTORE7_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE7_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
108 | SMSTORE8_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.689 | 0.624 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | SMSTORE8_WALL_1_WINDOW_1 | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.423_SHGC_0.25 | N/A | 2.404 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
110 | SMSTORE8_WALL_1_WINDOW_2 | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.423_SHGC_0.25 | N/A | 2.404 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
111 | SMSTORE8_WALL_1_DOOR | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.423_SHGC_0.25 | N/A | 2.404 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
112 | SMSTORE8_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE7_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | SMSTORE8_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.689 | 0.624 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | SMSTORE8_WALL_3_DOOR | Door | SMSTORE8_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
115 | SMSTORE8_WALL_4 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.689 | 0.624 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | SMSTORE8_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE8_FLOOR_FFACTOR | 0.289 | 0.270 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | SMSTORE8_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | SMSTORE8_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE8_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | LGSTORE1 | RunPeriod: RUNPERIOD 1 | 2.1826890899E-002 | 0.1360875475 | Pass | Pass | 0.1957711074 | 0.4864927539 | Pass | Pass |
2 | SMSTORE1 | RunPeriod: RUNPERIOD 1 | 4.4453193329E-002 | 9.4933617033E-002 | Pass | Pass | 0.1086733718 | 0.4066406583 | Pass | Pass |
3 | SMSTORE2 | RunPeriod: RUNPERIOD 1 | 2.5318501219E-002 | 0.1394752214 | Pass | Pass | 0.1405755758 | 0.5375531518 | Pass | Pass |
4 | SMSTORE3 | RunPeriod: RUNPERIOD 1 | 3.1806387566E-002 | 0.1758732081 | Pass | Pass | 0.1681675901 | 0.7057715246 | Pass | Pass |
5 | SMSTORE4 | RunPeriod: RUNPERIOD 1 | 3.5418938426E-002 | 0.1764930261 | Pass | Pass | 0.4217294151 | 1.7801012237 | Pass | Pass |
6 | LGSTORE2 | RunPeriod: RUNPERIOD 1 | 3.9134036447E-002 | 0.2047792338 | Pass | Pass | 0.1196944501 | 0.6053436763 | Pass | Pass |
7 | SMSTORE5 | RunPeriod: RUNPERIOD 1 | 3.8666369691E-002 | 0.2069770588 | Pass | Pass | 0.1014196396 | 0.5361925742 | Pass | Pass |
8 | SMSTORE6 | RunPeriod: RUNPERIOD 1 | 3.9620294945E-002 | 0.2099390137 | Pass | Pass | 9.9815870958E-002 | 0.5543931101 | Pass | Pass |
9 | SMSTORE7 | RunPeriod: RUNPERIOD 1 | 4.3361424458E-002 | 0.2304489000 | Pass | Pass | 9.8768926074E-002 | 0.6407797939 | Pass | Pass |
10 | SMSTORE8 | RunPeriod: RUNPERIOD 1 | 5.8004467532E-002 | 0.3121804045 | Pass | Pass | 9.0977931920E-002 | 0.6582539495 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:59
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 2852.48 | 37.90 | 0.00 | 95.45 | 940.65 | 3926.49 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:59
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | -6.30 | 0.00 | -6.30 | Wetbulb [C] | 5.30 | 320.00 |
ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 34.40 | 9.50 | 23.50 | Wetbulb [C] | 4.00 | 300.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 0.00 | 0 | |||
Sep | 90.00 | 25 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:59
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_2 | NONRES_EXT_WALL_GRD | 0.30 | 0.624 | 0.689 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE1_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.624 | 0.689 | 78.94 | 71.15 | 0.00 | 90.00 | N |
LGSTORE1_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.624 | 0.689 | 78.94 | 58.18 | 180.00 | 90.00 | S |
LGSTORE1_FLOOR | LGSTORE1_FLOOR_FFACTOR | 1.00 | 0.193 | 0.199 | 348.39 | 348.39 | 270.00 | 180.00 | |
LGSTORE1_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 348.39 | 348.39 | 270.00 | 0.00 | |
SMSTORE1_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.624 | 0.689 | 39.47 | 29.09 | 180.00 | 90.00 | S |
SMSTORE1_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.624 | 0.689 | 39.47 | 35.57 | 0.00 | 90.00 | N |
SMSTORE1_FLOOR | SMSTORE1_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE1_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE2_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.624 | 0.689 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE2_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.624 | 0.689 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE2_FLOOR | SMSTORE2_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE2_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE3_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.624 | 0.689 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE3_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.624 | 0.689 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE3_FLOOR | SMSTORE3_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE3_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE4_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.624 | 0.689 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE4_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.624 | 0.689 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE4_FLOOR | SMSTORE4_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE4_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 | |
LGSTORE2_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.624 | 0.689 | 78.94 | 71.19 | 0.00 | 90.00 | N |
LGSTORE2_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.624 | 0.689 | 78.94 | 58.22 | 180.00 | 90.00 | S |
LGSTORE2_FLOOR | LGSTORE2_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 348.39 | 348.39 | 270.00 | 180.00 | |
LGSTORE2_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 348.39 | 348.39 | 270.00 | 0.00 | |
SMSTORE5_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.624 | 0.689 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE5_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.624 | 0.689 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE5_FLOOR | SMSTORE5_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE5_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE6_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.624 | 0.689 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE6_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.624 | 0.689 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE6_FLOOR | SMSTORE6_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE6_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE7_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.624 | 0.689 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE7_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.624 | 0.689 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE7_FLOOR | SMSTORE7_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE7_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE8_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.624 | 0.689 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE8_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.624 | 0.689 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE8_WALL_4 | NONRES_EXT_WALL_GRD | 0.30 | 0.624 | 0.689 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE8_FLOOR | SMSTORE8_FLOOR_FFACTOR | 1.00 | 0.276 | 0.289 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE8_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE1_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE2_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE2_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE3_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE3_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE4_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE4_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
LGSTORE2_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE2_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE5_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE5_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE6_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE6_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE7_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE7_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE8_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 696.77 | 0.00 | 90.00 | N | ||
SMSTORE1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
LGSTORE2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 696.77 | 0.00 | 90.00 | N | ||
SMSTORE5_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE7_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE8_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.423_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.404 | 0.251 | 0.276 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.423_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.404 | 0.251 | 0.276 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_3 | NONRESWINDOW_U_0.423_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.404 | 0.251 | 0.276 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_4 | NONRESWINDOW_U_0.423_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.404 | 0.251 | 0.276 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_DOOR_1 | NONRESWINDOW_U_0.423_SHGC_0.25 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.404 | 0.251 | 0.276 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_DOOR_2 | NONRESWINDOW_U_0.423_SHGC_0.25 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.404 | 0.251 | 0.276 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.423_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.404 | 0.251 | 0.276 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.423_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.404 | 0.251 | 0.276 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_DOOR | NONRESWINDOW_U_0.423_SHGC_0.25 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.404 | 0.251 | 0.276 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.423_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.404 | 0.251 | 0.276 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.423_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.404 | 0.251 | 0.276 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_DOOR | NONRESWINDOW_U_0.423_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.404 | 0.251 | 0.276 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.423_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.404 | 0.251 | 0.276 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.423_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.404 | 0.251 | 0.276 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_DOOR | NONRESWINDOW_U_0.423_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.404 | 0.251 | 0.276 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.423_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.404 | 0.251 | 0.276 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.423_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.404 | 0.251 | 0.276 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_DOOR | NONRESWINDOW_U_0.423_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.404 | 0.251 | 0.276 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.423_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.404 | 0.251 | 0.276 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.423_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.404 | 0.251 | 0.276 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_3 | NONRESWINDOW_U_0.423_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.404 | 0.251 | 0.276 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_4 | NONRESWINDOW_U_0.423_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.404 | 0.251 | 0.276 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_DOOR_1 | NONRESWINDOW_U_0.423_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.404 | 0.251 | 0.276 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_DOOR_2 | NONRESWINDOW_U_0.423_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.404 | 0.251 | 0.276 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.423_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.404 | 0.251 | 0.276 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.423_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.404 | 0.251 | 0.276 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_DOOR | NONRESWINDOW_U_0.423_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.404 | 0.251 | 0.276 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.423_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.404 | 0.251 | 0.276 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.423_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.404 | 0.251 | 0.276 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_DOOR | NONRESWINDOW_U_0.423_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.404 | 0.251 | 0.276 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.423_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.404 | 0.251 | 0.276 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.423_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.404 | 0.251 | 0.276 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_DOOR | NONRESWINDOW_U_0.423_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.404 | 0.251 | 0.276 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.423_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.404 | 0.251 | 0.276 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.423_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.404 | 0.251 | 0.276 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_DOOR | NONRESWINDOW_U_0.423_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.404 | 0.251 | 0.276 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
Total or Average | 124.40 | 2.404 | 0.251 | 0.276 | |||||||||||||||||
North Total or Average | 0.00 | - | - | - | |||||||||||||||||
Non-North Total or Average | 124.40 | 2.404 | 0.251 | 0.276 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
LGSTORE1_WALL_3_DOOR_1 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.90 | LGSTORE1_WALL_3 |
LGSTORE1_WALL_3_DOOR_2 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.90 | LGSTORE1_WALL_3 |
SMSTORE1_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.90 | SMSTORE1_WALL_3 |
SMSTORE2_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE2_WALL_3 |
SMSTORE3_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE3_WALL_3 |
SMSTORE4_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE4_WALL_3 |
LGSTORE2_WALL_3_DOOR_1 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | LGSTORE2_WALL_3 |
LGSTORE2_WALL_3_DOOR_2 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | LGSTORE2_WALL_3 |
SMSTORE5_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE5_WALL_3 |
SMSTORE6_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE6_WALL_3 |
SMSTORE7_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE7_WALL_3 |
SMSTORE8_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE8_WALL_3 |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:59
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
LGSTORE1_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_4 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_DOOR_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_DOOR_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_4 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_DOOR_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_DOOR_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:59
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
LGSTORE1_LIGHTS | LGSTORE1 | LGSTORE1 | GENERAL | 9.6053 | 348.39 | 3346.35 | LightsWired | LTG_SCH_BASE_LPD1 | 83.91 | 168.00 | 82.62 | 0.0000 | Y | 51.90 |
LGSTORE1_LIGHTS_ALLOWANCE | LGSTORE1 | LGSTORE1 | GENERAL | 5.6969 | 348.39 | 1984.73 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | 97.50 | 112.00 | 94.53 | 0.0000 | Y | 35.22 |
SMSTORE1_LIGHTS | SMSTORE1 | SMSTORE1 | GENERAL | 9.7206 | 174.19 | 1693.26 | LightsWired | LTG_SCH_BASE_SMALL_LPD1 | 85.41 | 168.00 | 84.05 | 0.0000 | Y | 26.72 |
SMSTORE1_LIGHTS_ALLOWANCE | SMSTORE1 | SMSTORE1 | GENERAL | 8.5685 | 174.19 | 1492.57 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | 97.50 | 112.00 | 94.53 | 0.0000 | Y | 26.49 |
SMSTORE2_LIGHTS | SMSTORE2 | SMSTORE2 | GENERAL | 9.6995 | 174.19 | 1689.58 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 68.73 | 168.00 | 65.95 | 0.0000 | Y | 20.92 |
SMSTORE2_LIGHTS_ALLOWANCE | SMSTORE2 | SMSTORE2 | GENERAL | 6.9539 | 174.19 | 1211.32 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 84.29 | 73.25 | 0.0000 | Y | 16.66 |
SMSTORE3_LIGHTS | SMSTORE3 | SMSTORE3 | GENERAL | 9.6995 | 174.19 | 1689.58 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 68.73 | 168.00 | 65.95 | 0.0000 | Y | 20.92 |
SMSTORE3_LIGHTS_ALLOWANCE | SMSTORE3 | SMSTORE3 | GENERAL | 6.9539 | 174.19 | 1211.32 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 84.29 | 73.25 | 0.0000 | Y | 16.66 |
SMSTORE4_LIGHTS | SMSTORE4 | SMSTORE4 | GENERAL | 9.6995 | 174.19 | 1689.58 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 68.73 | 168.00 | 65.95 | 0.0000 | Y | 20.92 |
SMSTORE4_LIGHTS_ALLOWANCE | SMSTORE4 | SMSTORE4 | GENERAL | 6.9539 | 174.19 | 1211.32 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 84.29 | 73.25 | 0.0000 | Y | 16.66 |
LGSTORE2_LIGHTS | LGSTORE2 | LGSTORE2 | GENERAL | 9.5842 | 348.39 | 3339.00 | LightsWired | LTG_SCH_BASE_LPD2 | 62.11 | 168.00 | 59.29 | 0.0000 | Y | 37.16 |
LGSTORE2_LIGHTS_ALLOWANCE | LGSTORE2 | LGSTORE2 | GENERAL | 0.0000 | 348.39 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE5_LIGHTS | SMSTORE5 | SMSTORE5 | GENERAL | 9.6995 | 174.19 | 1689.58 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 60.29 | 0.0000 | Y | 19.12 |
SMSTORE5_LIGHTS_ALLOWANCE | SMSTORE5 | SMSTORE5 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE6_LIGHTS | SMSTORE6 | SMSTORE6 | GENERAL | 9.6995 | 174.19 | 1689.58 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 60.29 | 0.0000 | Y | 19.12 |
SMSTORE6_LIGHTS_ALLOWANCE | SMSTORE6 | SMSTORE6 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE7_LIGHTS | SMSTORE7 | SMSTORE7 | GENERAL | 9.6995 | 174.19 | 1689.58 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 60.29 | 0.0000 | Y | 19.12 |
SMSTORE7_LIGHTS_ALLOWANCE | SMSTORE7 | SMSTORE7 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE8_LIGHTS | SMSTORE8 | SMSTORE8 | GENERAL | 9.6995 | 174.19 | 1689.58 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 60.29 | 0.0000 | Y | 19.12 |
SMSTORE8_LIGHTS_ALLOWANCE | SMSTORE8 | SMSTORE8 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
Interior Lighting Total | 6.5342 | 4180.64 | 27316.92 | 366.68 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 455.59 | AstronomicalClock | - | 41.77 | 41.77 | 3.57 | |
EXTERIOR_LIGHTS_B | 2744.24 | AstronomicalClock | - | 83.77 | 62.77 | 32.33 | |
EXTERIOR_LIGHTS_C | 2307.23 | AstronomicalClock | - | 83.77 | 55.77 | 24.15 | |
Exterior Lighting Total | 5507.06 | 60.06 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:59
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 46466.70 | 33562.43 | 12904.27 | 0.72 | 3.73 | |||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 24302.11 | 17668.85 | 6633.26 | 0.73 | 3.80 | |||
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 24374.47 | 17728.04 | 6646.43 | 0.73 | 3.80 | |||
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 24432.76 | 17776.05 | 6656.71 | 0.73 | 3.80 | |||
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 24258.66 | 17632.41 | 6626.25 | 0.73 | 3.80 | |||
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 43877.72 | 31446.72 | 12431.00 | 0.72 | 3.73 | |||
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 22660.67 | 16294.83 | 6365.84 | 0.72 | 3.80 | |||
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 22578.50 | 16205.04 | 6373.46 | 0.72 | 3.80 | |||
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 22587.68 | 16234.90 | 6352.78 | 0.72 | 3.80 | |||
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 24800.25 | 18105.42 | 6694.83 | 0.73 | 3.80 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC_1:1 COOLING COIL | 44888.9 | 11.65 | 11.65 | ||||
PSZ-AC_2:2 COOLING COIL | 23465.3 | 11.80 | 11.80 | ||||
PSZ-AC_3:3 COOLING COIL | 23534.3 | 11.80 | 11.80 | ||||
PSZ-AC_4:4 COOLING COIL | 23589.9 | 11.79 | 11.79 | ||||
PSZ-AC_5:5 COOLING COIL | 23424.0 | 11.80 | 11.80 | ||||
PSZ-AC_6:6 COOLING COIL | 42413.5 | 11.68 | 11.68 | ||||
PSZ-AC_7:7 COOLING COIL | 21900.4 | 11.85 | 11.85 | ||||
PSZ-AC_8:8 COOLING COIL | 21822.1 | 11.85 | 11.85 | ||||
PSZ-AC_9:9 COOLING COIL | 21830.9 | 11.85 | 11.85 | ||||
PSZ-AC_10:10 COOLING COIL | 23940.0 | 11.78 | 11.78 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | 57296.53 | 0.80 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | 29994.01 | 0.80 | |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | 30087.49 | 0.80 | |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | 30163.95 | 0.80 | |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | 29934.43 | 0.80 | |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | 54104.70 | 0.80 | |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | 27840.45 | 0.80 | |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | 27733.55 | 0.80 | |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | 27744.64 | 0.80 | |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | 30654.89 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 2.00 | 2142.88 | 1070.05 | 1.00 | 1.31 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.06 | 1176.21 | 1107.16 | 1.00 | 1.39 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.07 | 1180.91 | 1107.16 | 1.00 | 1.39 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.07 | 1184.75 | 1107.16 | 1.00 | 1.39 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 |
PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.06 | 1173.22 | 1107.16 | 1.00 | 1.39 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 1.86 | 1987.97 | 1070.05 | 1.00 | 1.33 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.96 | 1068.04 | 1107.16 | 1.00 | 1.41 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 |
PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.96 | 1062.67 | 1107.16 | 1.00 | 1.41 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.96 | 1063.23 | 1107.16 | 1.00 | 1.41 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 |
PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.09 | 1209.36 | 1107.16 | 1.00 | 1.38 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
GAS TANK1 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK2 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK3 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK4 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK5 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK6 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK7 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:59
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
LGSTORE1 | 21920.04 | 26304.05 | 75.50 | 1.669 | 2.003 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 23.89 | 23.88 | 0.00980 | 34.40 | 0.01447 | 0.411 | 0.00 |
SMSTORE1 | 11628.61 | 13954.33 | 80.11 | 0.885 | 1.062 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 23.89 | 23.88 | 0.00976 | 34.40 | 0.01447 | 0.206 | 0.00 |
SMSTORE2 | 11675.07 | 14010.08 | 80.43 | 0.889 | 1.067 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 23.89 | 23.89 | 0.00976 | 34.32 | 0.01447 | 0.206 | 0.00 |
SMSTORE3 | 11713.04 | 14055.65 | 80.69 | 0.892 | 1.070 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 23.89 | 23.89 | 0.00975 | 34.32 | 0.01447 | 0.206 | 0.00 |
SMSTORE4 | 11599.06 | 13918.87 | 79.90 | 0.883 | 1.060 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 23.89 | 23.89 | 0.00976 | 34.32 | 0.01447 | 0.206 | 0.00 |
LGSTORE2 | 20335.86 | 24403.03 | 70.05 | 1.548 | 1.858 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 23.89 | 23.89 | 0.00985 | 34.32 | 0.01447 | 0.411 | 0.00 |
SMSTORE5 | 10559.26 | 12671.11 | 72.74 | 0.804 | 0.965 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 23.89 | 23.89 | 0.00987 | 34.24 | 0.01447 | 0.206 | 0.00 |
SMSTORE6 | 10506.17 | 12607.40 | 72.38 | 0.800 | 0.960 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 23.89 | 23.89 | 0.00987 | 34.24 | 0.01447 | 0.206 | 0.00 |
SMSTORE7 | 10511.68 | 12614.01 | 72.41 | 0.800 | 0.960 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 23.89 | 23.89 | 0.00987 | 34.24 | 0.01447 | 0.206 | 0.00 |
SMSTORE8 | 11957.20 | 14348.64 | 82.37 | 0.910 | 1.092 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | 23.89 | 23.88 | 0.00979 | 33.92 | 0.01447 | 0.206 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
LGSTORE1 | 21954.85 | 26345.82 | 75.62 | 0.982 | 1.178 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00668 | -6.30 | 0.00230 | 0.411 | 0.00 |
SMSTORE1 | 10142.61 | 12171.13 | 69.87 | 0.453 | 0.544 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00661 | -6.30 | 0.00230 | 0.206 | 0.00 |
SMSTORE2 | 10290.91 | 12349.09 | 70.89 | 0.460 | 0.552 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00662 | -6.30 | 0.00230 | 0.206 | 0.00 |
SMSTORE3 | 10399.55 | 12479.46 | 71.64 | 0.465 | 0.558 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00663 | -6.30 | 0.00230 | 0.206 | 0.00 |
SMSTORE4 | 10567.24 | 12680.69 | 72.80 | 0.472 | 0.567 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00665 | -6.30 | 0.00230 | 0.206 | 0.00 |
LGSTORE2 | 20466.06 | 24559.27 | 70.49 | 0.915 | 1.098 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00672 | -6.30 | 0.00230 | 0.411 | 0.00 |
SMSTORE5 | 10892.83 | 13071.40 | 75.04 | 0.487 | 0.584 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00667 | -6.30 | 0.00230 | 0.206 | 0.00 |
SMSTORE6 | 10883.68 | 13060.41 | 74.98 | 0.487 | 0.584 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00667 | -6.30 | 0.00230 | 0.206 | 0.00 |
SMSTORE7 | 11108.58 | 13330.30 | 76.53 | 0.497 | 0.596 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00669 | -6.30 | 0.00230 | 0.206 | 0.00 |
SMSTORE8 | 13768.74 | 16522.49 | 94.85 | 0.616 | 0.739 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00671 | -6.30 | 0.00230 | 0.206 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC_1:1 | 2.00 | 2.00 | 1.18 | 1.18 | 2.0026 | 2.0026 | 2.0026 | 1.0000 | 1.0000 |
PSZ-AC_2:2 | 1.06 | 1.06 | 0.54 | 0.54 | 1.0624 | 1.0624 | 1.0624 | 1.0000 | 1.0000 |
PSZ-AC_3:3 | 1.07 | 1.07 | 0.55 | 0.55 | 1.0666 | 1.0666 | 1.0666 | 1.0000 | 1.0000 |
PSZ-AC_4:4 | 1.07 | 1.07 | 0.56 | 0.56 | 1.0701 | 1.0701 | 1.0701 | 1.0000 | 1.0000 |
PSZ-AC_5:5 | 1.06 | 1.06 | 0.57 | 0.57 | 1.0597 | 1.0597 | 1.0597 | 1.0000 | 1.0000 |
PSZ-AC_6:6 | 1.86 | 1.86 | 1.10 | 1.10 | 1.8578 | 1.8578 | 1.8578 | 1.0000 | 1.0000 |
PSZ-AC_7:7 | 0.96 | 0.96 | 0.58 | 0.58 | 0.9647 | 0.9647 | 0.9647 | 1.0000 | 1.0000 |
PSZ-AC_8:8 | 0.96 | 0.96 | 0.58 | 0.58 | 0.9598 | 0.9598 | 0.9598 | 1.0000 | 1.0000 |
PSZ-AC_9:9 | 0.96 | 0.96 | 0.60 | 0.60 | 0.9603 | 0.9603 | 0.9603 | 1.0000 | 1.0000 |
PSZ-AC_10:10 | 1.09 | 1.09 | 0.74 | 0.74 | 1.0923 | 1.0923 | 1.0923 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 46466.700 | 33562.433 | 2.002600 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 23233.35 | 17136.56 | 1.335067 | 26.94 | 18.82 | 0.01076286 | 12.80 | 11.77 | 0.00850000 | 34.40 | 0.01447326 | 23.54 | 30.8208 | 23.88 | 0.00980332 | 51.1268 | 21920.04 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_1:1 | 57296.535 | 57296.535 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 57296.53 | 57296.53 | 2.002601 | 15.48 | 10.11 | 0.00577953 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 20.5472 | 21.11 | 0.00667994 | 41.4537 | 21954.85 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 24302.110 | 17668.849 | 1.062370 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 12151.06 | 9043.33 | 0.708247 | 26.85 | 18.72 | 0.01067311 | 12.80 | 11.77 | 0.00850000 | 34.40 | 0.01447326 | 23.54 | 29.0491 | 23.88 | 0.00976042 | 50.9062 | 11628.61 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_2:2 | 29994.009 | 29994.009 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 29994.01 | 29994.01 | 1.062372 | 15.80 | 10.25 | 0.00577375 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 19.3661 | 21.11 | 0.00660857 | 41.0148 | 10142.61 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_3:3 | 24374.470 | 17728.040 | 1.066610 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 12187.24 | 9076.33 | 0.711073 | 26.84 | 18.72 | 0.01066639 | 12.80 | 11.77 | 0.00850000 | 34.40 | 0.01447326 | 23.54 | 28.9336 | 23.89 | 0.00975634 | 50.8853 | 11672.46 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_3:3 | 30087.494 | 30087.494 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 30087.49 | 30087.49 | 1.066613 | 15.82 | 10.27 | 0.00578775 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 19.2890 | 21.11 | 0.00662181 | 41.0961 | 10290.91 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_4:4 | 24432.760 | 17776.055 | 1.070080 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 12216.38 | 9103.21 | 0.713387 | 26.84 | 18.71 | 0.01066070 | 12.80 | 11.77 | 0.00850000 | 34.40 | 0.01447326 | 23.54 | 28.8398 | 23.89 | 0.00975288 | 50.8675 | 11709.80 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_4:4 | 30163.950 | 30163.950 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 30163.95 | 30163.95 | 1.070082 | 15.84 | 10.29 | 0.00579792 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 19.2265 | 21.11 | 0.00663105 | 41.1529 | 10399.55 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_5:5 | 24258.660 | 17632.407 | 1.059670 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 12129.33 | 9022.63 | 0.706447 | 26.86 | 18.73 | 0.01067816 | 12.80 | 11.77 | 0.00850000 | 34.40 | 0.01447326 | 23.54 | 29.1231 | 23.89 | 0.00976350 | 50.9220 | 11596.09 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_5:5 | 29934.427 | 29934.427 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 29934.43 | 29934.43 | 1.059669 | 15.79 | 10.27 | 0.00580133 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 19.4154 | 21.11 | 0.00664544 | 41.2413 | 10567.24 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_6:6 | 43877.720 | 31446.723 | 1.857830 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 21938.86 | 16023.00 | 1.238553 | 27.11 | 18.96 | 0.01087295 | 12.80 | 11.77 | 0.00850000 | 34.40 | 0.01447326 | 23.54 | 33.2225 | 23.89 | 0.00984841 | 51.3578 | 20331.68 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_6:6 | 54104.696 | 54104.696 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 54104.70 | 54104.70 | 1.857833 | 15.04 | 9.88 | 0.00574277 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 22.1483 | 21.11 | 0.00672285 | 41.7158 | 20466.06 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_7:7 | 22660.670 | 16294.835 | 0.964670 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 11330.33 | 8287.40 | 0.643113 | 27.06 | 18.93 | 0.01085191 | 12.80 | 11.77 | 0.00850000 | 34.40 | 0.01447326 | 23.54 | 31.9912 | 23.89 | 0.00986975 | 51.4675 | 10555.43 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_7:7 | 27840.455 | 27840.455 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 27840.45 | 27840.45 | 0.964666 | 15.26 | 9.98 | 0.00573916 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 21.3275 | 21.11 | 0.00667209 | 41.4049 | 10892.83 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_8:8 | 22578.500 | 16205.041 | 0.959820 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 11289.25 | 8249.85 | 0.639880 | 27.07 | 18.94 | 0.01086152 | 12.80 | 11.77 | 0.00850000 | 34.40 | 0.01447326 | 23.54 | 32.1528 | 23.89 | 0.00987566 | 51.4978 | 10502.29 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_8:8 | 27733.554 | 27733.554 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 27733.55 | 27733.55 | 0.959816 | 15.23 | 9.96 | 0.00573392 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 21.4353 | 21.11 | 0.00667141 | 41.4008 | 10883.68 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_9:9 | 22587.680 | 16234.895 | 0.960320 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 11293.84 | 8253.83 | 0.640213 | 27.07 | 18.94 | 0.01086072 | 12.80 | 11.77 | 0.00850000 | 34.40 | 0.01447326 | 23.54 | 32.1361 | 23.89 | 0.00987516 | 51.4953 | 10506.71 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_9:9 | 27744.640 | 27744.640 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 27744.64 | 27744.64 | 0.960319 | 15.24 | 9.98 | 0.00574825 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 21.4241 | 21.11 | 0.00668903 | 41.5090 | 11108.58 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_10:10 | 24800.250 | 18105.423 | 1.092310 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:10:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | 12400.12 | 9202.03 | 0.728207 | 26.72 | 18.69 | 0.01068016 | 12.80 | 11.77 | 0.00850000 | 34.00 | 0.01447253 | 23.44 | 28.2529 | 23.88 | 0.00979885 | 51.1042 | 11943.13 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_10:10 | 30654.890 | 30654.890 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 30654.89 | 30654.89 | 1.092310 | 15.94 | 10.42 | 0.00587666 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 18.8353 | 21.10 | 0.00670718 | 41.6230 | 13768.74 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:36:59
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 46466.700 | 33562.433 | 2.002600 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.8476 | 1004.8586 | 1.1610 | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.002601 | 2.32497296 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | Sensible | 23233.35 | 17136.56 | 1.0000 | 1.54998108 | 1.335067 | 26.94 | 18.82 | 0.01076286 | 54531.6 | 12.80 | 11.77 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 23233.35 | 34.40 | 0.01447326 | 23.54 | 0.41147883 | 30.8208 | 23.88 | 0.00980332 | 23.88 | 0.00980332 | 51.1268 | 21920.04 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 57296.535 | 57296.535 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.002601 | 2.32497296 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 57296.53 | 57296.53 | 1.0000 | 2.32497296 | 2.002601 | 15.48 | 10.11 | 0.00577953 | 30170.6 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 57296.53 | -6.30 | 0.00229779 | -6.30 | 0.41147883 | 20.5472 | 21.11 | 0.00667994 | 21.11 | 0.00667994 | 41.4537 | 21954.85 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 24302.110 | 17668.849 | 1.062370 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.6808 | 1004.8586 | 1.1610 | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.062372 | 1.23338840 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | Sensible | 12151.06 | 9043.33 | 1.0000 | 0.82225776 | 0.708247 | 26.85 | 18.72 | 0.01067311 | 54207.6 | 12.80 | 11.77 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 12151.06 | 34.40 | 0.01447326 | 23.54 | 0.20573941 | 29.0491 | 23.89 | 0.00976042 | 23.88 | 0.00976042 | 50.9062 | 11628.61 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 29994.009 | 29994.009 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.062372 | 1.23338840 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 29994.01 | 29994.01 | 1.0000 | 1.23338840 | 1.062372 | 15.80 | 10.25 | 0.00577375 | 30485.0 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 29994.01 | -6.30 | 0.00229779 | -6.30 | 0.20573941 | 19.3661 | 21.11 | 0.00660857 | 21.11 | 0.00660857 | 41.0148 | 10142.61 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 24374.470 | 17728.040 | 1.066610 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.6683 | 1004.8586 | 1.1610 | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.066613 | 1.23831290 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | Sensible | 12187.24 | 9076.33 | 1.0000 | 0.82553946 | 0.711073 | 26.84 | 18.72 | 0.01066639 | 54182.6 | 12.80 | 11.77 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 12187.24 | 34.40 | 0.01447326 | 23.54 | 0.20573941 | 28.9336 | 23.89 | 0.00975634 | 23.89 | 0.00975634 | 50.8853 | 11672.46 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 30087.494 | 30087.494 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.066613 | 1.23831290 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 30087.49 | 30087.49 | 1.0000 | 1.23831290 | 1.066613 | 15.82 | 10.27 | 0.00578775 | 30541.9 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 30087.49 | -6.30 | 0.00229779 | -6.30 | 0.20573941 | 19.2890 | 21.11 | 0.00662181 | 21.11 | 0.00662181 | 41.0961 | 10290.91 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 24432.760 | 17776.055 | 1.070080 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.6577 | 1004.8586 | 1.1610 | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.070082 | 1.24234008 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | Sensible | 12216.38 | 9103.21 | 1.0000 | 0.82822518 | 0.713387 | 26.84 | 18.71 | 0.01066070 | 54161.5 | 12.80 | 11.77 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 12216.38 | 34.40 | 0.01447326 | 23.54 | 0.20573941 | 28.8398 | 23.89 | 0.00975288 | 23.89 | 0.00975288 | 50.8675 | 11709.80 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 30163.950 | 30163.950 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.070082 | 1.24234008 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 30163.95 | 30163.95 | 1.0000 | 1.24234008 | 1.070082 | 15.84 | 10.29 | 0.00579792 | 30585.0 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 30163.95 | -6.30 | 0.00229779 | -6.30 | 0.20573941 | 19.2265 | 21.11 | 0.00663105 | 21.11 | 0.00663105 | 41.1529 | 10399.55 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 24258.660 | 17632.407 | 1.059670 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.6902 | 1004.8586 | 1.1610 | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.059669 | 1.23025068 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | Sensible | 12129.33 | 9022.63 | 1.0000 | 0.82016801 | 0.706447 | 26.86 | 18.73 | 0.01067816 | 54226.3 | 12.80 | 11.77 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 12129.33 | 34.40 | 0.01447326 | 23.54 | 0.20573941 | 29.1231 | 23.89 | 0.00976350 | 23.89 | 0.00976350 | 50.9220 | 11596.09 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 29934.427 | 29934.427 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.059669 | 1.23025068 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 29934.43 | 29934.43 | 1.0000 | 1.23025068 | 1.059669 | 15.79 | 10.27 | 0.00580133 | 30541.1 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 29934.43 | -6.30 | 0.00229779 | -6.30 | 0.20573941 | 19.4154 | 21.11 | 0.00664544 | 21.11 | 0.00664544 | 41.2413 | 10567.24 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 43877.720 | 31446.723 | 1.857830 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1025.0523 | 1004.8586 | 1.1610 | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.857833 | 2.15690008 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | Sensible | 21938.86 | 16023.00 | 1.0000 | 1.43793136 | 1.238553 | 27.11 | 18.96 | 0.01087295 | 54985.4 | 12.80 | 11.77 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 21938.86 | 34.40 | 0.01447326 | 23.54 | 0.41147883 | 33.2225 | 23.89 | 0.00984841 | 23.89 | 0.00984841 | 51.3578 | 20331.68 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 54104.696 | 54104.696 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.857833 | 2.15690008 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 54104.70 | 54104.70 | 1.0000 | 2.15690008 | 1.857833 | 15.04 | 9.88 | 0.00574277 | 29632.4 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 54104.70 | -6.30 | 0.00229779 | -6.30 | 0.41147883 | 22.1483 | 21.11 | 0.00672285 | 21.11 | 0.00672285 | 41.7158 | 20466.06 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 22660.670 | 16294.835 | 0.964670 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1025.0132 | 1004.8586 | 1.1610 | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.964666 | 1.11995496 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | Sensible | 11330.33 | 8287.40 | 1.0000 | 0.74663949 | 0.643113 | 27.06 | 18.93 | 0.01085191 | 54875.6 | 12.80 | 11.77 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11330.33 | 34.40 | 0.01447326 | 23.54 | 0.20573941 | 31.9912 | 23.89 | 0.00986975 | 23.89 | 0.00986975 | 51.4675 | 10555.43 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 27840.455 | 27840.455 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.964666 | 1.11995496 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 27840.45 | 27840.45 | 1.0000 | 1.11995496 | 0.964666 | 15.26 | 9.98 | 0.00573916 | 29851.6 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 27840.45 | -6.30 | 0.00229779 | -6.30 | 0.20573941 | 21.3275 | 21.11 | 0.00667209 | 21.11 | 0.00667209 | 41.4049 | 10892.83 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 22578.500 | 16205.041 | 0.959820 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1025.0310 | 1004.8586 | 1.1610 | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.959816 | 1.11432419 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | Sensible | 11289.25 | 8249.85 | 1.0000 | 0.74288567 | 0.639880 | 27.07 | 18.94 | 0.01086152 | 54911.7 | 12.80 | 11.77 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11289.25 | 34.40 | 0.01447326 | 23.54 | 0.20573941 | 32.1528 | 23.89 | 0.00987566 | 23.89 | 0.00987566 | 51.4978 | 10502.29 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 27733.554 | 27733.554 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.959816 | 1.11432419 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 27733.55 | 27733.55 | 1.0000 | 1.11432419 | 0.959816 | 15.23 | 9.96 | 0.00573392 | 29808.4 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 27733.55 | -6.30 | 0.00229779 | -6.30 | 0.20573941 | 21.4353 | 21.11 | 0.00667141 | 21.11 | 0.00667141 | 41.4008 | 10883.68 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 22587.680 | 16234.895 | 0.960320 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1025.0295 | 1004.8586 | 1.1610 | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.960319 | 1.11490823 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | Sensible | 11293.84 | 8253.83 | 1.0000 | 0.74327266 | 0.640213 | 27.07 | 18.94 | 0.01086072 | 54908.7 | 12.80 | 11.77 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11293.84 | 34.40 | 0.01447326 | 23.54 | 0.20573941 | 32.1361 | 23.89 | 0.00987516 | 23.89 | 0.00987516 | 51.4953 | 10506.71 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 27744.640 | 27744.640 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.960319 | 1.11490823 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 27744.64 | 27744.64 | 1.0000 | 1.11490823 | 0.960319 | 15.24 | 9.98 | 0.00574825 | 29847.7 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 27744.64 | -6.30 | 0.00229779 | -6.30 | 0.20573941 | 21.4241 | 21.11 | 0.00668903 | 21.11 | 0.00668903 | 41.5090 | 11108.58 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 24800.250 | 18105.423 | 1.092310 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.6939 | 1004.8586 | 1.1610 | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.092310 | 1.26814627 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:10:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:10:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | Sensible | 12400.12 | 9202.03 | 1.0000 | 0.84543086 | 0.728207 | 26.72 | 18.69 | 0.01068016 | 54094.6 | 12.80 | 11.77 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 12400.12 | 34.00 | 0.01447253 | 23.44 | 0.20573941 | 28.2529 | 23.89 | 0.00979885 | 23.88 | 0.00979885 | 51.1042 | 11943.13 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 30654.890 | 30654.890 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.092310 | 1.26814627 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 30654.89 | 30654.89 | 1.0000 | 1.26814627 | 1.092310 | 15.94 | 10.42 | 0.00587666 | 30892.4 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 30654.89 | -6.30 | 0.00229779 | -6.30 | 0.20573941 | 18.8353 | 21.11 | 0.00670718 | 21.10 | 0.00670718 | 41.6230 | 13768.74 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:59
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-AC_1:1_OA_CONTROLLER | DifferentialEnthalpy | 0.41 | 2.00 | - | |||
PSZ-AC_2:2_OA_CONTROLLER | DifferentialEnthalpy | 0.21 | 1.06 | - | |||
PSZ-AC_3:3_OA_CONTROLLER | DifferentialEnthalpy | 0.21 | 1.07 | - | |||
PSZ-AC_4:4_OA_CONTROLLER | DifferentialEnthalpy | 0.21 | 1.07 | - | |||
PSZ-AC_5:5_OA_CONTROLLER | DifferentialEnthalpy | 0.21 | 1.06 | - | |||
PSZ-AC_6:6_OA_CONTROLLER | DifferentialEnthalpy | 0.41 | 1.86 | - | |||
PSZ-AC_7:7_OA_CONTROLLER | DifferentialEnthalpy | 0.21 | 0.96 | - | |||
PSZ-AC_8:8_OA_CONTROLLER | DifferentialEnthalpy | 0.21 | 0.96 | - | |||
PSZ-AC_9:9_OA_CONTROLLER | DifferentialEnthalpy | 0.21 | 0.96 | - | |||
PSZ-AC_10:10_OA_CONTROLLER | DifferentialEnthalpy | 0.21 | 1.09 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
LGSTORE1 | 3232.33 | 3056.00 | 1031.33 |
SMSTORE1 | 2855.67 | 2575.83 | 422.17 |
SMSTORE2 | 2345.17 | 2240.33 | 648.00 |
SMSTORE3 | 2350.33 | 2266.00 | 669.50 |
SMSTORE4 | 2359.00 | 2354.83 | 748.83 |
LGSTORE2 | 2204.17 | 2373.17 | 950.67 |
SMSTORE5 | 2168.50 | 2412.67 | 969.00 |
SMSTORE6 | 2173.83 | 2440.50 | 995.17 |
SMSTORE7 | 2212.00 | 2506.50 | 1077.33 |
SMSTORE8 | 2389.00 | 2514.50 | 1223.50 |
Facility | 3802.17 | 3699.33 | 1739.33 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
LGSTORE1 | 3.67 | 0.00 | 0.83 | 0.00 |
SMSTORE1 | 0.17 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 0.17 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 0.33 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 0.50 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 1.33 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 1.17 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 1.50 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 3.17 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 10.33 | 0.00 | 0.00 | 0.00 |
Facility | 13.00 | 0.00 | 0.83 | 0.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:59
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
LGSTORE1 | 16.93 | 56.25 | 1805.20 | 0.949 | 0.227 | 0.000 | 0.000 |
SMSTORE1 | 8.47 | 28.12 | 902.60 | 0.821 | 0.241 | 0.000 | 0.000 |
SMSTORE2 | 7.08 | 28.12 | 902.60 | 1.005 | 0.314 | 0.000 | 0.000 |
SMSTORE3 | 7.08 | 28.12 | 902.60 | 1.002 | 0.314 | 0.000 | 0.000 |
SMSTORE4 | 7.08 | 28.12 | 902.60 | 0.988 | 0.314 | 0.000 | 0.000 |
LGSTORE2 | 24.75 | 56.25 | 1805.20 | 0.961 | 0.302 | 0.000 | 0.000 |
SMSTORE5 | 12.38 | 28.12 | 902.60 | 0.966 | 0.335 | 0.000 | 0.000 |
SMSTORE6 | 12.38 | 28.12 | 902.60 | 0.962 | 0.335 | 0.000 | 0.000 |
SMSTORE7 | 12.38 | 28.12 | 902.60 | 0.956 | 0.335 | 0.000 | 0.000 |
SMSTORE8 | 12.38 | 28.12 | 902.60 | 0.972 | 0.355 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
LGSTORE1 | 16.93 | 56.25 | 1805.20 | 0.000 | 0.000 | 0.000 | 0.000 |
SMSTORE1 | 8.47 | 28.12 | 902.60 | 0.000 | 0.000 | 0.000 | 0.000 |
SMSTORE2 | 7.08 | 28.12 | 902.60 | 0.801 | 0.000 | 0.000 | 0.000 |
SMSTORE3 | 7.08 | 28.12 | 902.60 | 0.801 | 0.000 | 0.000 | 0.000 |
SMSTORE4 | 7.08 | 28.12 | 902.60 | 0.801 | 0.000 | 0.000 | 0.000 |
LGSTORE2 | 24.75 | 56.25 | 1805.20 | 0.803 | 0.000 | 0.000 | 0.000 |
SMSTORE5 | 12.38 | 28.12 | 902.60 | 0.803 | 0.000 | 0.000 | 0.000 |
SMSTORE6 | 12.38 | 28.12 | 902.60 | 0.803 | 0.000 | 0.000 | 0.000 |
SMSTORE7 | 12.38 | 28.12 | 902.60 | 0.803 | 0.000 | 0.000 | 0.000 |
SMSTORE8 | 12.38 | 28.12 | 902.60 | 0.803 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:36:59
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
LGSTORE1 | PSZ-AC_1:1 | 16.93 | 56.25 | 1805.20 | 348.39 | 0.4115 | 0.411 |
SMSTORE1 | PSZ-AC_2:2 | 8.47 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE2 | PSZ-AC_3:3 | 7.08 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE3 | PSZ-AC_4:4 | 7.08 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE4 | PSZ-AC_5:5 | 7.08 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
LGSTORE2 | PSZ-AC_6:6 | 24.75 | 56.25 | 1805.20 | 348.39 | 0.4115 | 0.411 |
SMSTORE5 | PSZ-AC_7:7 | 12.38 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE6 | PSZ-AC_8:8 | 12.38 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE7 | PSZ-AC_9:9 | 12.38 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE8 | PSZ-AC_10:10 | 12.38 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
Total Facility | 120.88 | 337.50 | 10831.20 | 2090.32 | 2.4689 | 2.469 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
LGSTORE1 | 9837375.97 | 0.00 | 9837375.97 | 2731052.24 | 12568428.21 | 12976396.34 | 3174.94 | 4589.07 | 995.99 | 14.87 |
SMSTORE1 | 4252987.52 | 0.00 | 4252987.52 | 1359523.50 | 5612511.02 | 6488198.17 | 4442.39 | 3299.12 | 1018.49 | 14.06 |
SMSTORE2 | 3959152.10 | 0.00 | 3959152.10 | 1395493.01 | 5354645.11 | 6488198.17 | 4345.95 | 3661.87 | 752.18 | 76.99 |
SMSTORE3 | 3943262.58 | 0.00 | 3943262.58 | 1395493.01 | 5338755.59 | 6488198.17 | 4346.41 | 3685.42 | 728.18 | 72.33 |
SMSTORE4 | 3887804.13 | 0.00 | 3887804.13 | 1395493.01 | 5283297.13 | 6488198.17 | 4347.84 | 3738.50 | 673.66 | 66.79 |
LGSTORE2 | 6897691.24 | 0.00 | 6897691.24 | 2566144.11 | 9463835.35 | 12976396.34 | 4723.42 | 3438.42 | 598.16 | 40.76 |
SMSTORE5 | 3466796.86 | 0.00 | 3466796.86 | 1406000.65 | 4872797.51 | 6488198.17 | 4723.34 | 3450.25 | 586.41 | 40.30 |
SMSTORE6 | 3451750.53 | 0.00 | 3451750.53 | 1406000.65 | 4857751.18 | 6488198.17 | 4724.48 | 3463.92 | 571.60 | 37.71 |
SMSTORE7 | 3425814.03 | 0.00 | 3425814.03 | 1406000.65 | 4831814.68 | 6488198.17 | 4725.23 | 3494.50 | 540.27 | 30.94 |
SMSTORE8 | 3486489.28 | 0.00 | 3486489.28 | 1733578.79 | 5220068.07 | 6488198.17 | 4721.19 | 3524.83 | 513.97 | 19.56 |
Total Facility | 46609124.23 | 0.00 | 46609124.23 | 16794779.62 | 63403903.86 | 77858378.04 | 4729.43 | 5187.90 | 1346.59 | 138.84 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
LGSTORE1 | 0.4672 | 0.0000 | 0.4672 | 0.1116 | 0.5788 | 0.4115 | 257.81 | 4589.07 | 993.12 |
SMSTORE1 | 0.2020 | 0.0000 | 0.2020 | 0.0593 | 0.2613 | 0.2057 | 1525.28 | 3298.96 | 1015.77 |
SMSTORE2 | 0.2474 | 0.0000 | 0.2474 | 0.0773 | 0.3247 | 0.2057 | 0.00 | 3661.00 | 734.00 |
SMSTORE3 | 0.2465 | 0.0000 | 0.2465 | 0.0773 | 0.3238 | 0.2057 | 0.00 | 3684.58 | 710.42 |
SMSTORE4 | 0.2432 | 0.0000 | 0.2432 | 0.0773 | 0.3205 | 0.2057 | 0.00 | 3738.33 | 656.67 |
LGSTORE2 | 0.4729 | 0.0000 | 0.4729 | 0.1485 | 0.6214 | 0.4115 | 0.00 | 3437.83 | 592.17 |
SMSTORE5 | 0.2376 | 0.0000 | 0.2376 | 0.0824 | 0.3201 | 0.2057 | 0.00 | 3449.92 | 580.08 |
SMSTORE6 | 0.2367 | 0.0000 | 0.2367 | 0.0824 | 0.3192 | 0.2057 | 0.00 | 3463.58 | 566.42 |
SMSTORE7 | 0.2352 | 0.0000 | 0.2352 | 0.0824 | 0.3176 | 0.2057 | 0.00 | 3494.33 | 535.67 |
SMSTORE8 | 0.2392 | 0.0000 | 0.2392 | 0.0873 | 0.3265 | 0.2057 | 0.00 | 3524.67 | 505.33 |
Total Facility | 2.8279 | 0.0000 | 2.8279 | 0.8860 | 3.7139 | 2.4689 | 1628.64 | 5185.53 | 1325.73 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-AC_1:1 | 13259642.90 | 0.00 | 13259642.90 | 12976396.34 | 3170.36 | 0.00 | 5589.64 | 14.87 |
PSZ-AC_2:2 | 5732511.90 | 0.00 | 5732511.90 | 6488198.17 | 4380.52 | 4.92 | 4374.56 | 14.06 |
PSZ-AC_3:3 | 5336468.02 | 0.00 | 5336468.02 | 6488198.17 | 4337.74 | 0.17 | 4422.09 | 76.82 |
PSZ-AC_4:4 | 5315050.63 | 0.00 | 5315050.63 | 6488198.17 | 4338.24 | 0.50 | 4421.26 | 72.33 |
PSZ-AC_5:5 | 5240298.47 | 0.00 | 5240298.47 | 6488198.17 | 4342.09 | 0.17 | 4417.74 | 66.62 |
PSZ-AC_6:6 | 9297284.14 | 0.00 | 9297284.14 | 12976396.34 | 4719.76 | 0.00 | 4040.24 | 40.76 |
PSZ-AC_7:7 | 4672831.16 | 0.00 | 4672831.16 | 6488198.17 | 4718.84 | 0.00 | 4041.16 | 39.96 |
PSZ-AC_8:8 | 4652547.32 | 0.00 | 4652547.32 | 6488198.17 | 4719.92 | 0.00 | 4040.07 | 37.63 |
PSZ-AC_9:9 | 4617572.71 | 0.00 | 4617572.71 | 6488198.17 | 4722.31 | 0.33 | 4037.35 | 30.94 |
PSZ-AC_10:10 | 4699320.78 | 0.00 | 4699320.78 | 6488198.17 | 4719.35 | 0.00 | 4040.65 | 19.56 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-AC_1:1 | 0.6298 | 0.0000 | 0.6298 | 0.4115 | 254.90 | 0.00 | 5585.10 |
PSZ-AC_2:2 | 0.2723 | 0.0000 | 0.2723 | 0.2057 | 1464.08 | 4.92 | 4371.01 |
PSZ-AC_3:3 | 0.3335 | 0.0000 | 0.3335 | 0.2057 | 0.00 | 0.00 | 4395.00 |
PSZ-AC_4:4 | 0.3322 | 0.0000 | 0.3322 | 0.2057 | 0.00 | 0.00 | 4395.00 |
PSZ-AC_5:5 | 0.3278 | 0.0000 | 0.3278 | 0.2057 | 0.00 | 0.00 | 4395.00 |
PSZ-AC_6:6 | 0.6374 | 0.0000 | 0.6374 | 0.4115 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_7:7 | 0.3203 | 0.0000 | 0.3203 | 0.2057 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_8:8 | 0.3191 | 0.0000 | 0.3191 | 0.2057 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_9:9 | 0.3170 | 0.0000 | 0.3170 | 0.2057 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_10:10 | 0.3224 | 0.0000 | 0.3224 | 0.2057 | 0.00 | 0.00 | 4030.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-AC_1:1 | 0.00 | 5116.31 | 508.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_2:2 | 0.00 | 4479.46 | 771.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_3:3 | 0.00 | 4092.46 | 379.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_4:4 | 0.00 | 4103.26 | 364.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_5:5 | 0.00 | 4125.09 | 336.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_6:6 | 0.00 | 3825.19 | 245.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_7:7 | 0.00 | 3821.10 | 248.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_8:8 | 0.00 | 3828.10 | 239.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_9:9 | 0.00 | 3843.60 | 217.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_10:10 | 0.00 | 3830.07 | 219.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-AC_1:1 | 0.0000 | 0.6358 | 0.8620 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_2:2 | 0.0000 | 0.2953 | 0.3528 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_3:3 | 0.0000 | 0.3227 | 0.4780 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_4:4 | 0.0000 | 0.3216 | 0.4799 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_5:5 | 0.0000 | 0.3173 | 0.4864 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_6:6 | 0.0000 | 0.6238 | 0.8909 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_7:7 | 0.0000 | 0.3129 | 0.4564 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_8:8 | 0.0000 | 0.3119 | 0.4556 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_9:9 | 0.0000 | 0.3103 | 0.4545 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_10:10 | 0.0000 | 0.3132 | 0.4974 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:59
Surfaces by ClassTotal | Outdoors | |
Wall | 40 | 22 |
Floor | 10 | 10 |
Roof | 10 | 10 |
Internal Mass | 10 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 36 | 36 |
Door | 12 | 12 |
Glass Door | 12 | 12 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 10 |
Conditioned Zones | 10 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 830 |
Defaulted Fields | 823 |
Fields with Defaults | 2682 |
Autosized Fields | 184 |
Autosizable Fields | 458 |
Autocalculated Fields | 128 |
Autocalculatable Fields | 256 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:36:59
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 893.48 | 2102.83 | 01-JAN-07:50 | 94769.24 | 08-JUL-15:20 |
Electricity:Building | 494.83 | 891.83 | 01-JAN-00:20 | 31518.67 | 01-JAN-11:10 |
Electricity:Zone:LGSTORE1 | 113.36 | 148.64 | 01-JAN-00:20 | 5964.88 | 01-JAN-10:10 |
Electricity:SpaceType:GENERAL | 494.83 | 891.83 | 01-JAN-00:20 | 31518.67 | 01-JAN-11:10 |
InteriorLights:Electricity | 366.68 | 450.00 | 01-JAN-00:20 | 23459.17 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:LGSTORE1 | 87.12 | 75.00 | 01-JAN-00:20 | 4621.63 | 01-JAN-10:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 366.68 | 450.00 | 01-JAN-00:20 | 23459.17 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity | 366.68 | 450.00 | 01-JAN-00:20 | 23459.17 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:LGSTORE1 | 87.12 | 75.00 | 01-JAN-00:20 | 4621.63 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 366.68 | 450.00 | 01-JAN-00:20 | 23459.17 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE1 | 66.33 | 74.32 | 01-JAN-00:20 | 3498.69 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE1 | 53.20 | 37.50 | 01-JAN-00:20 | 2827.07 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE1 | 53.20 | 37.50 | 01-JAN-00:20 | 2827.07 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE2 | 47.99 | 74.32 | 01-JAN-00:10 | 3226.84 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE2 | 37.57 | 37.50 | 01-JAN-00:10 | 2555.22 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE2 | 37.57 | 37.50 | 01-JAN-00:10 | 2555.22 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE3 | 47.99 | 74.32 | 01-JAN-00:10 | 3226.84 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE3 | 37.57 | 37.50 | 01-JAN-00:10 | 2555.22 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE3 | 37.57 | 37.50 | 01-JAN-00:10 | 2555.22 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE4 | 47.99 | 74.32 | 01-JAN-00:10 | 3226.84 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE4 | 37.57 | 37.50 | 01-JAN-00:10 | 2555.22 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE4 | 37.57 | 37.50 | 01-JAN-00:10 | 2555.22 | 01-JAN-10:10 |
Electricity:Zone:LGSTORE2 | 56.34 | 148.64 | 01-JAN-00:10 | 4070.21 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:LGSTORE2 | 37.16 | 75.00 | 01-JAN-00:10 | 2726.96 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:LGSTORE2 | 37.16 | 75.00 | 01-JAN-00:10 | 2726.96 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE5 | 28.71 | 74.32 | 01-JAN-00:10 | 2076.09 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE5 | 19.12 | 37.50 | 01-JAN-00:10 | 1404.46 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE5 | 19.12 | 37.50 | 01-JAN-00:10 | 1404.46 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE6 | 28.71 | 74.32 | 01-JAN-00:10 | 2076.09 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE6 | 19.12 | 37.50 | 01-JAN-00:10 | 1404.46 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE6 | 19.12 | 37.50 | 01-JAN-00:10 | 1404.46 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE7 | 28.71 | 74.32 | 01-JAN-00:10 | 2076.09 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE7 | 19.12 | 37.50 | 01-JAN-00:10 | 1404.46 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE7 | 19.12 | 37.50 | 01-JAN-00:10 | 1404.46 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE8 | 28.71 | 74.32 | 01-JAN-00:10 | 2076.09 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE8 | 19.12 | 37.50 | 01-JAN-00:10 | 1404.46 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE8 | 19.12 | 37.50 | 01-JAN-00:10 | 1404.46 | 01-JAN-11:10 |
InteriorEquipment:Electricity | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:LGSTORE1 | 26.25 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-10:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LGSTORE1 | 26.25 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE1 | 13.12 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE1 | 13.12 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE2 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE2 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE3 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE3 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE4 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE4 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:LGSTORE2 | 19.17 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LGSTORE2 | 19.17 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE5 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE5 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE6 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE6 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE7 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE7 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE8 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE8 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
ElectricityPurchased:Facility | 893.48 | 2102.83 | 01-JAN-07:50 | 94769.24 | 08-JUL-15:20 |
ElectricityPurchased:Plant | 893.48 | 2102.83 | 01-JAN-07:50 | 94769.24 | 08-JUL-15:20 |
Cogeneration:ElectricityPurchased | 893.48 | 2102.83 | 01-JAN-07:50 | 94769.24 | 08-JUL-15:20 |
General:Cogeneration:ElectricityPurchased | 893.48 | 2102.83 | 01-JAN-07:50 | 94769.24 | 08-JUL-15:20 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 893.48 | 2102.83 | 01-JAN-07:50 | 94769.24 | 08-JUL-15:20 |
ElectricityNet:Plant | 893.48 | 2102.83 | 01-JAN-07:50 | 94769.24 | 08-JUL-15:20 |
Cogeneration:ElectricityNet | 893.48 | 2102.83 | 01-JAN-07:50 | 94769.24 | 08-JUL-15:20 |
General:Cogeneration:ElectricityNet | 893.48 | 2102.83 | 01-JAN-07:50 | 94769.24 | 08-JUL-15:20 |
Electricity:HVAC | 276.57 | 0.00 | 01-JAN-00:10 | 58893.56 | 08-JUL-14:00 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 180.23 | 0.00 | 01-JAN-00:10 | 50874.79 | 08-JUL-14:00 |
General:Cooling:Electricity | 180.23 | 0.00 | 01-JAN-00:10 | 50874.79 | 08-JUL-14:00 |
Fans:Electricity | 96.34 | 0.00 | 01-JAN-00:10 | 9070.86 | 12-FEB-09:10 |
General:Fans:Electricity | 96.34 | 0.00 | 01-JAN-00:10 | 9070.86 | 12-FEB-09:10 |
ExteriorLights:Electricity | 60.06 | 0.00 | 01-JAN-07:50 | 5507.06 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 60.06 | 0.00 | 01-JAN-07:50 | 5507.06 | 01-JAN-06:10 |
Electricity:Plant | 62.02 | 1211.00 | 03-JAN-07:10 | 13909.55 | 09-FEB-13:20 |
WaterSystems:Electricity | 62.02 | 1211.00 | 03-JAN-07:10 | 13909.55 | 09-FEB-13:20 |
Water Heater:WaterSystems:Electricity | 62.02 | 1211.00 | 03-JAN-07:10 | 13909.55 | 09-FEB-13:20 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 193.01 | 0.00 | 01-JAN-00:10 | 205195.73 | 12-FEB-09:10 |
NaturalGas:HVAC | 193.01 | 0.00 | 01-JAN-00:10 | 205195.73 | 12-FEB-09:10 |
Heating:NaturalGas | 193.01 | 0.00 | 01-JAN-00:10 | 205195.73 | 12-FEB-09:10 |
General:Heating:NaturalGas | 193.01 | 0.00 | 01-JAN-00:10 | 205195.73 | 12-FEB-09:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water:Plant | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
WaterSystems:Water | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water Heater:WaterSystems:Water | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
MainsWater:Facility | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
MainsWater:Plant | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
WaterSystems:MainsWater | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water Heater:WaterSystems:MainsWater | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 1416.27 | 0.00 | 01-JAN-00:10 | 307580.97 | 13-FEB-08:10 |
EnergyTransfer:Building | 540.05 | 0.00 | 01-JAN-00:10 | 146271.17 | 13-FEB-08:10 |
EnergyTransfer:Zone:LGSTORE1 | 113.84 | 0.00 | 01-JAN-00:10 | 31519.26 | 12-FEB-08:10 |
Heating:EnergyTransfer | 51.12 | 0.00 | 01-JAN-00:10 | 146271.17 | 13-FEB-08:10 |
Heating:EnergyTransfer:Zone:LGSTORE1 | 7.25 | 0.00 | 01-JAN-00:10 | 31519.26 | 12-FEB-08:10 |
General:Heating:EnergyTransfer | 51.12 | 0.00 | 01-JAN-00:10 | 146271.17 | 13-FEB-08:10 |
General:Heating:EnergyTransfer:Zone:LGSTORE1 | 7.25 | 0.00 | 01-JAN-00:10 | 31519.26 | 12-FEB-08:10 |
Cooling:EnergyTransfer | 488.92 | 0.00 | 01-JAN-00:10 | 93083.18 | 08-JUL-15:00 |
Cooling:EnergyTransfer:Zone:LGSTORE1 | 106.60 | 0.00 | 01-JAN-00:10 | 15940.88 | 08-JUL-16:10 |
General:Cooling:EnergyTransfer | 488.92 | 0.00 | 01-JAN-00:10 | 93083.18 | 08-JUL-15:00 |
General:Cooling:EnergyTransfer:Zone:LGSTORE1 | 106.60 | 0.00 | 01-JAN-00:10 | 15940.88 | 08-JUL-16:10 |
EnergyTransfer:Zone:SMSTORE1 | 61.01 | 0.00 | 01-JAN-00:10 | 11193.77 | 12-FEB-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE1 | 1.87 | 0.00 | 01-JAN-00:10 | 11193.77 | 12-FEB-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE1 | 1.87 | 0.00 | 01-JAN-00:10 | 11193.77 | 12-FEB-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE1 | 59.14 | 0.00 | 01-JAN-00:10 | 8439.51 | 11-OCT-20:40 |
General:Cooling:EnergyTransfer:Zone:SMSTORE1 | 59.14 | 0.00 | 01-JAN-00:10 | 8439.51 | 11-OCT-20:40 |
EnergyTransfer:Zone:SMSTORE2 | 46.24 | 0.00 | 01-JAN-00:10 | 12941.90 | 12-FEB-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE2 | 2.91 | 0.00 | 01-JAN-00:10 | 12941.90 | 12-FEB-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE2 | 2.91 | 0.00 | 01-JAN-00:10 | 12941.90 | 12-FEB-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE2 | 43.33 | 0.00 | 01-JAN-00:10 | 8123.07 | 08-JUL-13:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE2 | 43.33 | 0.00 | 01-JAN-00:10 | 8123.07 | 08-JUL-13:00 |
EnergyTransfer:Zone:SMSTORE3 | 45.90 | 0.00 | 01-JAN-00:10 | 13629.57 | 12-FEB-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE3 | 3.23 | 0.00 | 01-JAN-00:10 | 13629.57 | 12-FEB-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE3 | 3.23 | 0.00 | 01-JAN-00:10 | 13629.57 | 12-FEB-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE3 | 42.66 | 0.00 | 01-JAN-00:10 | 8158.77 | 08-JUL-13:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE3 | 42.66 | 0.00 | 01-JAN-00:10 | 8158.77 | 08-JUL-13:00 |
EnergyTransfer:Zone:SMSTORE4 | 44.19 | 0.00 | 01-JAN-00:10 | 14349.20 | 12-FEB-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE4 | 3.79 | 0.00 | 01-JAN-00:10 | 14349.20 | 12-FEB-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE4 | 3.79 | 0.00 | 01-JAN-00:10 | 14349.20 | 12-FEB-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE4 | 40.40 | 0.00 | 01-JAN-00:10 | 8013.61 | 08-JUL-13:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE4 | 40.40 | 0.00 | 01-JAN-00:10 | 8013.61 | 08-JUL-13:00 |
EnergyTransfer:Zone:LGSTORE2 | 73.66 | 0.00 | 01-JAN-00:10 | 29479.39 | 12-FEB-09:10 |
Heating:EnergyTransfer:Zone:LGSTORE2 | 7.75 | 0.00 | 01-JAN-00:10 | 29479.39 | 12-FEB-09:10 |
General:Heating:EnergyTransfer:Zone:LGSTORE2 | 7.75 | 0.00 | 01-JAN-00:10 | 29479.39 | 12-FEB-09:10 |
Cooling:EnergyTransfer:Zone:LGSTORE2 | 65.91 | 0.00 | 01-JAN-00:10 | 14688.83 | 08-JUL-15:00 |
General:Cooling:EnergyTransfer:Zone:LGSTORE2 | 65.91 | 0.00 | 01-JAN-00:10 | 14688.83 | 08-JUL-15:00 |
EnergyTransfer:Zone:SMSTORE5 | 37.89 | 0.00 | 01-JAN-00:10 | 15369.11 | 12-FEB-09:10 |
Heating:EnergyTransfer:Zone:SMSTORE5 | 4.49 | 0.00 | 01-JAN-00:10 | 15369.11 | 12-FEB-09:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE5 | 4.49 | 0.00 | 01-JAN-00:10 | 15369.11 | 12-FEB-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE5 | 33.41 | 0.00 | 01-JAN-00:10 | 7677.11 | 08-JUL-15:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE5 | 33.41 | 0.00 | 01-JAN-00:10 | 7677.11 | 08-JUL-15:00 |
EnergyTransfer:Zone:SMSTORE6 | 37.47 | 0.00 | 01-JAN-00:10 | 15554.41 | 12-FEB-09:10 |
Heating:EnergyTransfer:Zone:SMSTORE6 | 4.66 | 0.00 | 01-JAN-00:10 | 15554.41 | 12-FEB-09:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE6 | 4.66 | 0.00 | 01-JAN-00:10 | 15554.41 | 12-FEB-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE6 | 32.81 | 0.00 | 01-JAN-00:10 | 7638.62 | 08-JUL-15:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE6 | 32.81 | 0.00 | 01-JAN-00:10 | 7638.62 | 08-JUL-15:00 |
EnergyTransfer:Zone:SMSTORE7 | 37.06 | 0.00 | 01-JAN-00:10 | 16503.94 | 12-FEB-09:10 |
Heating:EnergyTransfer:Zone:SMSTORE7 | 5.52 | 0.00 | 01-JAN-00:10 | 16503.94 | 12-FEB-09:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE7 | 5.52 | 0.00 | 01-JAN-00:10 | 16503.94 | 12-FEB-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE7 | 31.54 | 0.00 | 01-JAN-00:10 | 7664.96 | 08-JUL-15:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE7 | 31.54 | 0.00 | 01-JAN-00:10 | 7664.96 | 08-JUL-15:00 |
EnergyTransfer:Zone:SMSTORE8 | 42.78 | 0.00 | 01-JAN-00:10 | 18684.33 | 13-FEB-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE8 | 9.65 | 0.00 | 01-JAN-00:10 | 18684.33 | 13-FEB-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE8 | 9.65 | 0.00 | 01-JAN-00:10 | 18684.33 | 13-FEB-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE8 | 33.13 | 0.00 | 01-JAN-00:10 | 8800.26 | 08-JUL-14:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE8 | 33.13 | 0.00 | 01-JAN-00:10 | 8800.26 | 08-JUL-14:10 |
EnergyTransfer:HVAC | 876.23 | 0.00 | 01-JAN-00:10 | 191719.60 | 08-JUL-14:00 |
HeatingCoils:EnergyTransfer | 154.41 | 0.00 | 01-JAN-00:10 | 164156.58 | 12-FEB-09:10 |
CoolingCoils:EnergyTransfer | 721.82 | 0.00 | 01-JAN-00:10 | 191719.60 | 08-JUL-14:00 |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:59
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
LGSTORE1 | 0.000 | 0.000 | 7.247 | -106.596 | 0.000 | 0.000 | 24.373 | 87.116 | 26.249 | 17.040 | 0.000 | 5.321 | 0.001 | 0.000 | -7.534 | 0.000 | -18.880 | -34.336 |
SMSTORE1 | 0.000 | 0.000 | 1.866 | -59.138 | 0.000 | 0.000 | 12.046 | 53.201 | 13.125 | 8.449 | 0.000 | 2.883 | 0.000 | 0.000 | -3.967 | 0.000 | -9.000 | -19.464 |
SMSTORE2 | 0.000 | 0.000 | 2.911 | -43.332 | 0.000 | 0.000 | 7.312 | 37.572 | 10.421 | 8.415 | 0.000 | 2.827 | 0.000 | 0.000 | -3.955 | 0.000 | -9.253 | -12.917 |
SMSTORE3 | 0.000 | 0.000 | 3.235 | -42.662 | 0.000 | 0.000 | 7.321 | 37.572 | 10.421 | 8.426 | 0.000 | 2.826 | 0.002 | 0.000 | -3.914 | 0.000 | -9.197 | -14.028 |
SMSTORE4 | 0.000 | 0.000 | 3.791 | -40.401 | 0.000 | 0.000 | 7.336 | 37.572 | 10.421 | 8.450 | 0.000 | 2.828 | 0.001 | 0.000 | -3.855 | 0.000 | -9.110 | -17.031 |
LGSTORE2 | 0.000 | 0.000 | 7.753 | -65.905 | 0.000 | 0.000 | 25.238 | 37.162 | 19.173 | 16.999 | 0.000 | 5.104 | 0.000 | 0.000 | -7.409 | 0.000 | -16.773 | -21.341 |
SMSTORE5 | 0.000 | 0.000 | 4.488 | -33.404 | 0.000 | 0.000 | 12.626 | 19.120 | 9.586 | 8.492 | 0.000 | 2.838 | 0.002 | 0.000 | -3.694 | 0.000 | -9.067 | -10.986 |
SMSTORE6 | 0.000 | 0.000 | 4.662 | -32.811 | 0.000 | 0.000 | 12.635 | 19.120 | 9.586 | 8.502 | 0.000 | 2.838 | 0.002 | 0.000 | -3.674 | 0.000 | -9.038 | -11.821 |
SMSTORE7 | 0.000 | 0.000 | 5.523 | -31.537 | 0.000 | 0.000 | 12.657 | 19.120 | 9.586 | 8.524 | 0.000 | 2.839 | 0.001 | 0.000 | -3.614 | 0.000 | -8.952 | -14.146 |
SMSTORE8 | 0.000 | 0.000 | 9.650 | -33.126 | 0.000 | 0.000 | 12.687 | 19.120 | 9.586 | 8.556 | 0.000 | 2.973 | 0.002 | 0.000 | -3.406 | 0.000 | -11.865 | -14.174 |
Total Facility | 0.000 | 0.000 | 51.124 | -488.912 | 0.000 | 0.000 | 134.231 | 366.677 | 128.154 | 101.853 | 0.000 | 33.275 | 0.012 | 0.000 | -45.022 | 0.000 | -111.137 | -170.244 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
LGSTORE1 | 16-SEP-07:03 | 0.00 | 0.00 | 0.00 | -31795.90 | 0.00 | 0.00 | 0.00 | 75.00 | 73.64 | 0.00 | 0.00 | 0.00 | 31789.59 | 0.00 | -62.46 | 0.00 | -79.88 | 0.00 |
SMSTORE1 | 17-JUL-07:02 | 0.00 | 0.00 | 0.00 | -18243.20 | 0.00 | 0.00 | 87.02 | 37.50 | 37.31 | 36.57 | 0.00 | 0.00 | 18102.25 | 0.00 | -0.00 | 0.00 | -57.45 | 0.00 |
SMSTORE2 | 26-AUG-06:03 | 0.00 | 0.00 | 0.00 | -17304.20 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 0.00 | 0.00 | 0.00 | 17359.77 | 0.00 | -123.23 | 0.00 | -6.65 | 0.00 |
SMSTORE3 | 26-AUG-06:03 | 0.00 | 0.00 | 0.00 | -17375.40 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 0.00 | 0.00 | 0.00 | 17431.55 | 0.00 | -123.76 | 0.00 | -6.71 | 0.00 |
SMSTORE4 | 16-SEP-06:02 | 0.00 | 0.00 | 0.00 | -16848.12 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 0.00 | 0.00 | 0.00 | 16838.18 | 0.00 | -60.94 | 0.00 | -3.43 | 0.00 |
LGSTORE2 | 15-JUN-07:02 | 0.00 | 0.00 | 0.00 | -29272.70 | 0.00 | 0.00 | 0.00 | 75.00 | 73.64 | 215.26 | 0.00 | 0.00 | 28994.67 | 0.00 | -0.00 | 0.00 | -85.86 | 0.00 |
SMSTORE5 | 15-JUN-07:02 | 0.00 | 0.00 | 0.00 | -15088.48 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 108.97 | 0.00 | 0.00 | 14950.74 | 0.00 | -0.00 | 0.00 | -45.54 | 0.00 |
SMSTORE6 | 15-JUN-07:02 | 0.00 | 0.00 | 0.00 | -14982.36 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 109.61 | 0.00 | 0.00 | 14843.30 | 0.00 | -0.00 | 0.00 | -44.87 | 0.00 |
SMSTORE7 | 15-JUN-07:02 | 0.00 | 0.00 | 0.00 | -14918.68 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 110.76 | 0.00 | 0.00 | 14776.39 | 0.00 | -0.00 | 0.00 | -42.79 | 0.00 |
SMSTORE8 | 17-JUL-07:02 | 0.00 | 0.00 | 0.00 | -15452.63 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 33.56 | 0.00 | 0.00 | 15412.99 | 0.00 | -0.00 | 0.00 | -68.25 | 0.00 |
Total Facility | 18-JUL-07:02 | 0.00 | 0.00 | 0.00 | -144068.46 | 0.00 | 0.00 | 563.98 | 450.00 | 1452.23 | 713.62 | 0.00 | 0.00 | 141499.06 | 0.00 | 0.00 | 0.00 | -610.43 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
LGSTORE1 | 12-FEB-08:61 | 0.00 | 0.00 | 57486.34 | 0.00 | 0.00 | 0.00 | 285.08 | 75.00 | 74.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -383.80 | 0.00 | -1744.20 | -55793.05 |
SMSTORE1 | 12-FEB-08:61 | 0.00 | 0.00 | 30089.90 | 0.00 | 0.00 | 0.00 | 134.78 | 37.50 | 37.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -228.25 | 0.00 | -878.43 | -29192.82 |
SMSTORE2 | 12-FEB-08:61 | 0.00 | 0.00 | 30190.61 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 37.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -217.19 | 0.00 | -863.04 | -29185.19 |
SMSTORE3 | 12-FEB-08:61 | 0.00 | 0.00 | 30265.31 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 37.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -211.74 | 0.00 | -855.77 | -29272.62 |
SMSTORE4 | 12-FEB-08:61 | 0.00 | 0.00 | 30043.52 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 37.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -206.63 | 0.00 | -848.19 | -29063.52 |
LGSTORE2 | 12-FEB-09:12 | 0.00 | 0.00 | 54477.23 | 0.00 | 0.00 | 0.00 | 0.00 | 75.00 | 73.64 | 1205.33 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -1554.54 | -54276.66 |
SMSTORE5 | 12-FEB-09:12 | 0.00 | 0.00 | 28093.61 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 600.23 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -851.56 | -27916.60 |
SMSTORE6 | 12-FEB-09:12 | 0.00 | 0.00 | 28002.77 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 601.38 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -850.24 | -27828.22 |
SMSTORE7 | 12-FEB-09:12 | 0.00 | 0.00 | 28068.98 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 606.36 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -845.26 | -27904.40 |
SMSTORE8 | 12-FEB-09:12 | 0.00 | 0.00 | 31009.80 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 621.52 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -1048.19 | -30657.45 |
Total Facility | 13-FEB-08:61 | 0.00 | 0.00 | 271980.25 | 0.00 | 0.00 | 0.00 | 759.37 | 450.00 | 1452.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1023.95 | 0.00 | -8828.94 | -264788.96 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:59
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 2.0026 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 2.0026 | 0.2055 | 1.0000 | Not calculated | 0.4115 | 0.2055 | ||
PSZ-AC_2:2 | 1.0624 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0624 | 0.1937 | 1.0000 | Not calculated | 0.2057 | 0.1937 | ||
PSZ-AC_3:3 | 1.0666 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0666 | 0.1929 | 1.0000 | Not calculated | 0.2057 | 0.1929 | ||
PSZ-AC_4:4 | 1.0701 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0701 | 0.1923 | 1.0000 | Not calculated | 0.2057 | 0.1923 | ||
PSZ-AC_5:5 | 1.0597 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0597 | 0.1942 | 1.0000 | Not calculated | 0.2057 | 0.1942 | ||
PSZ-AC_6:6 | 1.8578 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 1.8578 | 0.2215 | 1.0000 | Not calculated | 0.4115 | 0.2215 | ||
PSZ-AC_7:7 | 0.9647 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9647 | 0.2133 | 1.0000 | Not calculated | 0.2057 | 0.2133 | ||
PSZ-AC_8:8 | 0.9598 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9598 | 0.2144 | 1.0000 | Not calculated | 0.2057 | 0.2144 | ||
PSZ-AC_9:9 | 0.9603 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9603 | 0.2142 | 1.0000 | Not calculated | 0.2057 | 0.2142 | ||
PSZ-AC_10:10 | 1.0923 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0923 | 0.1884 | 1.0000 | Not calculated | 0.2057 | 0.1884 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 2.0026 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 2.0026 | 1.0000 | 1.0000 | Not calculated | 0.4115 | 0.2055 | ||
PSZ-AC_2:2 | 1.0624 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0624 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1937 | ||
PSZ-AC_3:3 | 1.0666 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0666 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1929 | ||
PSZ-AC_4:4 | 1.0701 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0701 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1923 | ||
PSZ-AC_5:5 | 1.0597 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0597 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1942 | ||
PSZ-AC_6:6 | 1.8578 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 1.8578 | 1.0000 | 1.0000 | Not calculated | 0.4115 | 0.2215 | ||
PSZ-AC_7:7 | 0.9647 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9647 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.2133 | ||
PSZ-AC_8:8 | 0.9598 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9598 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.2144 | ||
PSZ-AC_9:9 | 0.9603 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9603 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.2142 | ||
PSZ-AC_10:10 | 1.0923 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0923 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1884 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
LGSTORE1 | PSZ-AC_1:1 | 0.000000 | 56.2505 | 0.001181 | 348.39 | 0.4115 | 1.0000 | 0.4115 | 1.000 | 0.4115 |
SMSTORE1 | PSZ-AC_2:2 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE2 | PSZ-AC_3:3 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE3 | PSZ-AC_4:4 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE4 | PSZ-AC_5:5 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
LGSTORE2 | PSZ-AC_6:6 | 0.000000 | 56.2505 | 0.001181 | 348.39 | 0.4115 | 1.0000 | 0.4115 | 1.000 | 0.4115 |
SMSTORE5 | PSZ-AC_7:7 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE6 | PSZ-AC_8:8 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE7 | PSZ-AC_9:9 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE8 | PSZ-AC_10:10 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC_1:1 | 0.000000 | 56.25 | 0.001181 | 348.3864 | 0.4115 | 0.4115 | 0.4115 |
PSZ-AC_2:2 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_3:3 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_4:4 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_5:5 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_6:6 | 0.000000 | 56.25 | 0.001181 | 348.3864 | 0.4115 | 0.4115 | 0.4115 |
PSZ-AC_7:7 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_8:8 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_9:9 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_10:10 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LGSTORE1 | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.0026 | 2.0026 | 2.0026 | No | 0.4115 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE1 | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0624 | 1.0624 | 1.0624 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE2 | PSZ-AC_3:3 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0666 | 1.0666 | 1.0666 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE3 | PSZ-AC_4:4 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0701 | 1.0701 | 1.0701 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE4 | PSZ-AC_5:5 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0597 | 1.0597 | 1.0597 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LGSTORE2 | PSZ-AC_6:6 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.8578 | 1.8578 | 1.8578 | No | 0.4115 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE5 | PSZ-AC_7:7 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9647 | 0.9647 | 0.9647 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE6 | PSZ-AC_8:8 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9598 | 0.9598 | 0.9598 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE7 | PSZ-AC_9:9 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9603 | 0.9603 | 0.9603 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE8 | PSZ-AC_10:10 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0923 | 1.0923 | 1.0923 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 2.0026 | 2.0026 | 2.0026 | 2.0026 | 0.4115 | 1.0000 |
PSZ-AC_2:2 | 1.0624 | 1.0624 | 1.0624 | 1.0624 | 0.2057 | 1.0000 |
PSZ-AC_3:3 | 1.0666 | 1.0666 | 1.0666 | 1.0666 | 0.2057 | 1.0000 |
PSZ-AC_4:4 | 1.0701 | 1.0701 | 1.0701 | 1.0701 | 0.2057 | 1.0000 |
PSZ-AC_5:5 | 1.0597 | 1.0597 | 1.0597 | 1.0597 | 0.2057 | 1.0000 |
PSZ-AC_6:6 | 1.8578 | 1.8578 | 1.8578 | 1.8578 | 0.4115 | 1.0000 |
PSZ-AC_7:7 | 0.9647 | 0.9647 | 0.9647 | 0.9647 | 0.2057 | 1.0000 |
PSZ-AC_8:8 | 0.9598 | 0.9598 | 0.9598 | 0.9598 | 0.2057 | 1.0000 |
PSZ-AC_9:9 | 0.9603 | 0.9603 | 0.9603 | 0.9603 | 0.2057 | 1.0000 |
PSZ-AC_10:10 | 1.0923 | 1.0923 | 1.0923 | 1.0923 | 0.2057 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LGSTORE1 | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.0026 | 2.0026 | 2.0026 | No | 0.4115 | 0.3493 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE1 | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0624 | 1.0624 | 1.0624 | No | 0.2057 | 0.3781 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE2 | PSZ-AC_3:3 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0666 | 1.0666 | 1.0666 | No | 0.2057 | 0.3726 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE3 | PSZ-AC_4:4 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0701 | 1.0701 | 1.0701 | No | 0.2057 | 0.3687 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE4 | PSZ-AC_5:5 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0597 | 1.0597 | 1.0597 | No | 0.2057 | 0.3629 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LGSTORE2 | PSZ-AC_6:6 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.8578 | 1.8578 | 1.8578 | No | 0.4115 | 0.3747 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE5 | PSZ-AC_7:7 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9647 | 0.9647 | 0.9647 | No | 0.2057 | 0.3520 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE6 | PSZ-AC_8:8 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9598 | 0.9598 | 0.9598 | No | 0.2057 | 0.3523 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE7 | PSZ-AC_9:9 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9603 | 0.9603 | 0.9603 | No | 0.2057 | 0.3452 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE8 | PSZ-AC_10:10 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0923 | 1.0923 | 1.0923 | No | 0.2057 | 0.2785 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 2.0026 | 2.0026 | 2.0026 | 2.0026 | 0.4115 | 1.0000 |
PSZ-AC_2:2 | 1.0624 | 1.0624 | 1.0624 | 1.0624 | 0.2057 | 1.0000 |
PSZ-AC_3:3 | 1.0666 | 1.0666 | 1.0666 | 1.0666 | 0.2057 | 1.0000 |
PSZ-AC_4:4 | 1.0701 | 1.0701 | 1.0701 | 1.0701 | 0.2057 | 1.0000 |
PSZ-AC_5:5 | 1.0597 | 1.0597 | 1.0597 | 1.0597 | 0.2057 | 1.0000 |
PSZ-AC_6:6 | 1.8578 | 1.8578 | 1.8578 | 1.8578 | 0.4115 | 1.0000 |
PSZ-AC_7:7 | 0.9647 | 0.9647 | 0.9647 | 0.9647 | 0.2057 | 1.0000 |
PSZ-AC_8:8 | 0.9598 | 0.9598 | 0.9598 | 0.9598 | 0.2057 | 1.0000 |
PSZ-AC_9:9 | 0.9603 | 0.9603 | 0.9603 | 0.9603 | 0.2057 | 1.0000 |
PSZ-AC_10:10 | 1.0923 | 1.0923 | 1.0923 | 1.0923 | 0.2057 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:59
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190 |
Total gross floor area [m2] | 2090.32 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
LGSTORE1 | 348.39 | 348.39 | 0.00 | 112.00 |
SMSTORE1 | 174.19 | 174.19 | 0.00 | 112.00 |
SMSTORE2 | 174.19 | 174.19 | 0.00 | 84.29 |
SMSTORE3 | 174.19 | 174.19 | 0.00 | 84.29 |
SMSTORE4 | 174.19 | 174.19 | 0.00 | 84.29 |
LGSTORE2 | 348.39 | 348.39 | 0.00 | 77.29 |
SMSTORE5 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE6 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE7 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE8 | 174.19 | 174.19 | 0.00 | 77.29 |
Totals | 2090.32 | 2090.32 | 0.00 |
Data | |
Number of hours heating loads not met | 0.83 |
Number of hours cooling loads not met | 0.00 |
Number of hours not met | 0.83 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 193.01 | 205195.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 180.23 | 50874.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 366.68 | 23459.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 60.06 | 5507.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 128.15 | 8059.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 96.34 | 9070.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 62.02 | 13909.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 128.15 | 893.48 |
Natural Gas | 0.00 | 193.01 |
Additional | 0.00 | 0.00 |
Total | 128.15 | 1086.49 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 175.42 |
Space Heating | 0.00 |
Space Cooling | 86.22 |
Fans (All) | 46.09 |
Service Water Heating | 29.67 |
Receptacle Equipment | 61.31 |
Miscellaneous (All) | 427.44 |
Subtotal | 427.44 |
Natural Gas [MJ/m2] | |
Space Heating | 92.34 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 92.34 |
Subtotal | 92.34 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 33.75 |
Space Heating | 17.76 |
Space Cooling | 16.59 |
Fans (All) | 8.87 |
Service Water Heating | 5.71 |
Receptacle Equipment | 11.80 |
Miscellaneous | 5.53 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
TYPE1_OCC_SCH | 1630. | 5840. |
TYPE2_OCC_SCH | 995. | 4429. |
TYPE3_OCC_SCH | 1709. | 4064. |
LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 3767. | 8760. |
LTG_SCH_BASE_LPD2 | 3238. | 8760. |
LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 3296. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | 5084. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | 5084. | 8760. |
LTG_SCH_BASE_SMALL_LPD1 | 4453. | 8760. |
LTG_SCH_BASE_LPD1 | 4376. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | 3767. | 8760. |
LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 3584. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 4096. | 8760. |
TYPE1_EQUIP_SCH | 4868. | 8760. |
TYPE2_EQUIP_SCH | 3893. | 8760. |
TYPE3_EQUIP_SCH | 3584. | 8760. |
TYPE1_INFIL_SCH | 4302. | 8760. |
TYPE2_INFIL_SCH | 5164. | 8760. |
TYPE3_INFIL_SCH | 5438. | 8760. |
INFIL_DOOR_OPENING_SCH | 2477. | 4380. |
TYPE1_MINOA_MOTORIZEDDAMPER_SCH | 5579. | 5579. |
TYPE2_MINOA_MOTORIZEDDAMPER_SCH | 4429. | 4429. |
TYPE3_MINOA_MOTORIZEDDAMPER_SCH | 4064. | 4064. |
TYPE1_SWH_SCH | 2063. | 6048. |
TYPE2_SWH_SCH | 1831. | 4429. |
TYPE3_SWH_SCH | 1733. | 4064. |
AVERAGE_SWH_SCH | 1863. | 6152. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 7118. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 5839. | 5839. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 7300. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6570. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
TYPE1_HTGSETP_SCH_NO_OPTIMUM | LGSTORE1 DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
TYPE1_CLGSETP_SCH_NO_OPTIMUM | LGSTORE1 DUAL SP CONTROL | July | 23.89 | 365 | 23.89 | 365 |
TYPE2_HTGSETP_SCH_NO_OPTIMUM | SMSTORE2 DUAL SP CONTROL | January | 21.11 | 365 | 15.56 | 365 |
TYPE2_CLGSETP_SCH_NO_OPTIMUM | SMSTORE2 DUAL SP CONTROL | July | 23.89 | 365 | 29.44 | 365 |
TYPE3_HTGSETP_SCH_NO_OPTIMUM | LGSTORE2 DUAL SP CONTROL | January | 21.11 | 365 | 15.56 | 365 |
TYPE3_CLGSETP_SCH_NO_OPTIMUM | LGSTORE2 DUAL SP CONTROL | July | 23.89 | 365 | 29.44 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:59
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
LGSTORE1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 8573.50 | 186.50 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 8546.17 | 213.83 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 8593.50 | 166.50 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 8664.33 | 95.67 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 8677.00 | 83.00 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 8679.33 | 80.67 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 8682.67 | 77.33 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 8644.83 | 115.17 | 0.00 | 0.00 | 0.00 |
Min | 8546.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 213.83 | 0.00 | 0.00 | 0.00 |
Average | 8658.13 | 101.87 | 0.00 | 0.00 | 0.00 |
Sum | 86581.33 | 1018.67 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
LGSTORE1 | 89041.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 43777.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 25436.67 | 38.33 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 25436.67 | 38.33 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 25439.00 | 36.00 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 93115.00 | 96.00 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 45865.00 | 47.00 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 45865.00 | 47.00 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 45866.00 | 46.00 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 45860.00 | 52.00 | 0.00 | 0.00 | 0.00 |
Min | 25436.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 93115.00 | 96.00 | 0.00 | 0.00 | 0.00 |
Average | 48570.13 | 40.07 | 0.00 | 0.00 | 0.00 |
Sum | 485701.33 | 400.67 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
LGSTORE1 | 7662.50 | 1097.50 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 8520.83 | 239.17 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 7040.33 | 1719.67 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 7059.33 | 1700.67 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 7060.50 | 1699.50 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 7069.33 | 1690.67 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 7097.00 | 1663.00 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 7102.83 | 1657.17 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 7110.17 | 1649.83 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 7070.33 | 1689.67 | 0.00 | 0.00 | 0.00 |
Min | 7040.33 | 239.17 | 0.00 | 0.00 | 0.00 |
Max | 8520.83 | 1719.67 | 0.00 | 0.00 | 0.00 |
Average | 7279.32 | 1480.68 | 0.00 | 0.00 | 0.00 |
Sum | 72793.17 | 14806.83 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
LGSTORE1 | 85219.83 | 3821.17 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 42662.17 | 1114.83 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 24354.17 | 1120.83 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 24357.00 | 1118.00 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 24215.67 | 1259.33 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 85965.00 | 7246.00 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 42244.17 | 3667.83 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 42211.00 | 3701.00 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 42009.17 | 3902.83 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 42354.00 | 3558.00 | 0.00 | 0.00 | 0.00 |
Min | 24215.67 | 1114.83 | 0.00 | 0.00 | 0.00 |
Max | 85965.00 | 7246.00 | 0.00 | 0.00 | 0.00 |
Average | 45559.22 | 3050.98 | 0.00 | 0.00 | 0.00 |
Sum | 455592.17 | 30509.83 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:59
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:59
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
For: Environment
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTRIPMALL
For: Environment
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3A
For: Environment
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_GA_ATLANTA
For: Environment
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: ZoneCoolingSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.163542E+10 | 10607.70 | 27-JAN-00:02 | -3.9 | -6.1 | 0.108817E+10 | 1452.08 | 20-JAN-13:00 | -3.9 | -6.1 |
February | 0.267502E+10 | 11154.00 | 03-FEB-00:02 | -5.1 | -7.2 | 0.105815E+10 | 1685.85 | 26-FEB-17:10 | 23.72 | 11.96 |
March | 0.548264E+10 | 10163.50 | 30-MAR-16:10 | 27.62 | 17.53 | 0.127870E+10 | 1685.85 | 11-MAR-13:09 | 27.62 | 17.53 |
April | 0.715939E+10 | 10219.49 | 17-APR-16:20 | 28.70 | 16.48 | 0.132674E+10 | 1685.96 | 14-APR-12:30 | 28.70 | 16.48 |
May | 0.103731E+11 | 11911.61 | 19-MAY-17:00 | 30.60 | 19.15 | 0.139965E+10 | 1686.00 | 29-MAY-17:00 | 29.40 | 20.07 |
June | 0.142067E+11 | 30765.95 | 15-JUN-07:02 | 22.20 | 18.87 | 0.135449E+10 | 1686.05 | 25-JUN-12:39 | 31.83 | 23.38 |
July | 0.161768E+11 | 31016.02 | 17-JUL-07:02 | 22.07 | 19.58 | 0.141275E+10 | 1686.04 | 04-JUL-16:10 | 22.07 | 19.58 |
August | 0.171631E+11 | 30276.54 | 14-AUG-07:02 | 23.98 | 21.20 | 0.139415E+10 | 1686.05 | 06-AUG-12:09 | 23.98 | 21.20 |
September | 0.129339E+11 | 31805.24 | 16-SEP-07:03 | 22.20 | 20.70 | 0.136495E+10 | 1686.05 | 09-SEP-12:30 | 22.20 | 20.70 |
October | 0.924762E+10 | 25450.65 | 19-OCT-07:03 | 19.40 | 19.12 | 0.136156E+10 | 1686.02 | 09-OCT-17:19 | 19.40 | 19.12 |
November | 0.594471E+10 | 9198.23 | 05-NOV-16:07 | 24.03 | 17.90 | 0.124583E+10 | 1685.86 | 11-NOV-13:09 | 21.10 | 11.68 |
December | 0.359862E+10 | 7959.70 | 01-DEC-00:03 | 1.80 | 1.51 | 0.111910E+10 | 1635.33 | 10-DEC-18:40 | 15.57 | 7.68 |
Annual Sum or Average | 0.106597E+12 | 0.154042E+11 | ||||||||
Minimum of Months | 0.163542E+10 | 7959.70 | -5.1 | -7.2 | 0.105815E+10 | 1452.08 | -3.9 | -6.1 | ||
Maximum of Months | 0.171631E+11 | 31805.24 | 30.60 | 21.20 | 0.141275E+10 | 1686.05 | 31.83 | 23.38 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.892671E+09 | 3854.10 | 12-JAN-10:23 | 1.95 | -1.1 | 0.566479E+09 | 842.90 | 29-JAN-18:00 | 13.30 | 5.45 |
February | 0.151767E+10 | 16706.01 | 26-FEB-19:49 | 20.00 | 10.73 | 0.550456E+09 | 842.90 | 26-FEB-13:39 | 20.00 | 10.73 |
March | 0.315908E+10 | 16736.11 | 26-MAR-17:07 | 20.00 | 9.32 | 0.662882E+09 | 842.96 | 11-MAR-13:00 | 20.00 | 9.32 |
April | 0.435940E+10 | 16652.48 | 08-APR-20:02 | 20.13 | 9.99 | 0.670806E+09 | 842.95 | 14-APR-12:09 | 26.20 | 16.07 |
May | 0.612326E+10 | 15577.15 | 13-MAY-20:36 | 18.70 | 11.86 | 0.699690E+09 | 842.98 | 06-MAY-12:39 | 18.70 | 11.86 |
June | 0.783415E+10 | 17948.13 | 15-JUN-07:02 | 22.20 | 18.87 | 0.676365E+09 | 843.00 | 30-JUN-12:39 | 30.93 | 23.53 |
July | 0.871533E+10 | 18246.02 | 17-JUL-07:02 | 22.07 | 19.58 | 0.706353E+09 | 843.00 | 16-JUL-16:10 | 22.07 | 19.58 |
August | 0.910653E+10 | 17943.51 | 14-AUG-07:02 | 23.98 | 21.20 | 0.697069E+09 | 843.01 | 27-AUG-12:00 | 31.70 | 22.73 |
September | 0.712860E+10 | 17460.62 | 10-SEP-07:02 | 22.33 | 21.08 | 0.681960E+09 | 843.04 | 03-SEP-17:19 | 22.33 | 21.08 |
October | 0.514476E+10 | 17249.98 | 11-OCT-20:50 | 16.47 | 9.77 | 0.690971E+09 | 842.98 | 08-OCT-17:10 | 16.47 | 9.77 |
November | 0.329917E+10 | 11505.47 | 04-NOV-18:24 | 18.85 | 16.69 | 0.643810E+09 | 842.91 | 19-NOV-13:39 | 20.77 | 17.82 |
December | 0.185844E+10 | 3673.04 | 15-DEC-09:03 | 3.77 | 1.80 | 0.594623E+09 | 842.90 | 10-DEC-18:00 | 3.77 | 1.80 |
Annual Sum or Average | 0.591391E+11 | 0.784146E+10 | ||||||||
Minimum of Months | 0.892671E+09 | 3673.04 | 1.95 | -1.1 | 0.550456E+09 | 842.90 | 3.77 | 1.80 | ||
Maximum of Months | 0.910653E+10 | 18246.02 | 23.98 | 21.20 | 0.706353E+09 | 843.04 | 31.70 | 23.53 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.555042E+09 | 3821.87 | 03-JAN-11:43 | 2.12 | 1.71 | 0.324983E+09 | 702.41 | 31-JAN-18:00 | 17.80 | 12.69 |
February | 0.105729E+10 | 4686.33 | 01-FEB-08:61 | -0.6 | -1.9 | 0.317819E+09 | 842.88 | 25-FEB-13:50 | 19.82 | 9.21 |
March | 0.236293E+10 | 5341.74 | 30-MAR-16:10 | 27.62 | 17.53 | 0.395480E+09 | 842.96 | 11-MAR-13:00 | 27.62 | 17.53 |
April | 0.303148E+10 | 5421.23 | 17-APR-16:10 | 28.80 | 16.45 | 0.401114E+09 | 842.93 | 08-APR-12:09 | 28.80 | 16.45 |
May | 0.433681E+10 | 9112.80 | 19-MAY-06:03 | 16.57 | 15.54 | 0.425172E+09 | 842.98 | 06-MAY-12:50 | 16.57 | 15.54 |
June | 0.584813E+10 | 16375.12 | 15-JUN-06:02 | 22.20 | 18.57 | 0.417170E+09 | 842.96 | 03-JUN-12:09 | 22.20 | 18.57 |
July | 0.645637E+10 | 16715.16 | 25-JUL-06:02 | 21.10 | 18.18 | 0.420435E+09 | 842.99 | 01-JUL-12:20 | 21.10 | 18.18 |
August | 0.696632E+10 | 17308.93 | 26-AUG-06:03 | 21.78 | 17.46 | 0.432083E+09 | 842.99 | 05-AUG-12:00 | 21.78 | 17.46 |
September | 0.516806E+10 | 17054.35 | 16-SEP-06:02 | 22.70 | 20.23 | 0.410651E+09 | 842.97 | 23-SEP-12:09 | 27.98 | 18.51 |
October | 0.369346E+10 | 13752.00 | 18-OCT-06:03 | 19.90 | 19.90 | 0.406363E+09 | 842.94 | 14-OCT-12:00 | 19.90 | 19.90 |
November | 0.240955E+10 | 4113.34 | 05-NOV-14:00 | 23.30 | 18.52 | 0.372053E+09 | 842.90 | 18-NOV-13:00 | 21.10 | 10.33 |
December | 0.144816E+10 | 4019.03 | 15-DEC-08:61 | 2.88 | 0.94 | 0.334831E+09 | 702.44 | 12-DEC-17:40 | 2.88 | 0.94 |
Annual Sum or Average | 0.433336E+11 | 0.465815E+10 | ||||||||
Minimum of Months | 0.555042E+09 | 3821.87 | -0.6 | -1.9 | 0.317819E+09 | 702.41 | 2.88 | 0.94 | ||
Maximum of Months | 0.696632E+10 | 17308.93 | 28.80 | 20.23 | 0.432083E+09 | 842.99 | 28.80 | 19.90 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.477433E+09 | 4735.09 | 14-JAN-10:53 | -1.7 | -4.9 | 0.324269E+09 | 702.40 | 31-JAN-18:00 | 17.80 | 12.69 |
February | 0.960910E+09 | 4604.56 | 02-FEB-09:23 | -1.1 | -2.7 | 0.316273E+09 | 842.89 | 25-FEB-13:00 | 20.00 | 9.28 |
March | 0.224183E+10 | 5253.91 | 30-MAR-16:10 | 27.62 | 17.53 | 0.393434E+09 | 842.96 | 11-MAR-13:00 | 27.62 | 17.53 |
April | 0.295791E+10 | 5393.45 | 17-APR-16:10 | 28.80 | 16.45 | 0.400473E+09 | 842.93 | 08-APR-12:09 | 28.80 | 16.45 |
May | 0.429391E+10 | 9129.12 | 19-MAY-06:03 | 16.57 | 15.54 | 0.425121E+09 | 842.98 | 06-MAY-12:50 | 16.57 | 15.54 |
June | 0.586579E+10 | 16706.88 | 05-JUN-06:03 | 19.60 | 16.99 | 0.417169E+09 | 842.96 | 03-JUN-12:09 | 19.60 | 16.99 |
July | 0.649305E+10 | 16796.55 | 25-JUL-06:02 | 21.10 | 18.18 | 0.420436E+09 | 842.98 | 01-JUL-12:20 | 21.10 | 18.18 |
August | 0.700341E+10 | 17380.14 | 26-AUG-06:03 | 21.78 | 17.46 | 0.432085E+09 | 842.99 | 05-AUG-12:00 | 21.78 | 17.46 |
September | 0.516532E+10 | 17096.54 | 16-SEP-06:02 | 22.70 | 20.23 | 0.410644E+09 | 842.97 | 23-SEP-12:09 | 27.98 | 18.51 |
October | 0.361903E+10 | 13754.10 | 18-OCT-06:03 | 19.90 | 19.90 | 0.405469E+09 | 842.94 | 14-OCT-12:00 | 19.90 | 19.90 |
November | 0.227087E+10 | 4001.59 | 05-NOV-14:00 | 23.30 | 18.52 | 0.370351E+09 | 842.90 | 18-NOV-13:00 | 21.10 | 10.33 |
December | 0.131332E+10 | 3972.46 | 15-DEC-08:61 | 2.88 | 0.94 | 0.333469E+09 | 702.44 | 12-DEC-17:40 | 2.88 | 0.94 |
Annual Sum or Average | 0.426628E+11 | 0.464919E+10 | ||||||||
Minimum of Months | 0.477433E+09 | 3972.46 | -1.7 | -4.9 | 0.316273E+09 | 702.40 | 2.88 | 0.94 | ||
Maximum of Months | 0.700341E+10 | 17380.14 | 28.80 | 20.23 | 0.432085E+09 | 842.99 | 28.80 | 19.90 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.371479E+09 | 4701.08 | 27-JAN-11:02 | -1.5 | -4.5 | 0.323229E+09 | 695.90 | 31-JAN-18:49 | 17.98 | 12.78 |
February | 0.824406E+09 | 4917.89 | 03-FEB-11:23 | -2.5 | -5.7 | 0.313979E+09 | 842.88 | 25-FEB-13:00 | 20.00 | 9.28 |
March | 0.202628E+10 | 5019.13 | 30-MAR-16:10 | 27.62 | 17.53 | 0.389885E+09 | 842.96 | 11-MAR-13:50 | 27.62 | 17.53 |
April | 0.274813E+10 | 5222.74 | 17-APR-16:10 | 28.80 | 16.45 | 0.398847E+09 | 842.93 | 08-APR-12:20 | 28.80 | 16.45 |
May | 0.406468E+10 | 7731.08 | 19-MAY-06:03 | 16.57 | 15.54 | 0.424913E+09 | 842.98 | 06-MAY-12:00 | 16.57 | 15.54 |
June | 0.567080E+10 | 16166.45 | 15-JUN-06:02 | 22.20 | 18.57 | 0.417122E+09 | 842.99 | 24-JUN-12:20 | 31.47 | 23.66 |
July | 0.631268E+10 | 16541.48 | 25-JUL-06:02 | 21.10 | 18.18 | 0.420400E+09 | 842.97 | 01-JUL-12:20 | 21.10 | 18.18 |
August | 0.682187E+10 | 16319.82 | 26-AUG-06:03 | 21.78 | 17.46 | 0.432048E+09 | 842.98 | 05-AUG-12:00 | 21.78 | 17.46 |
September | 0.497592E+10 | 16852.53 | 16-SEP-06:02 | 22.70 | 20.23 | 0.410580E+09 | 843.00 | 09-SEP-12:20 | 22.70 | 20.23 |
October | 0.342108E+10 | 13208.76 | 19-OCT-06:03 | 19.90 | 19.84 | 0.403810E+09 | 842.94 | 14-OCT-12:00 | 19.90 | 19.84 |
November | 0.205001E+10 | 3858.85 | 14-NOV-08:62 | 2.90 | 1.20 | 0.367600E+09 | 842.90 | 18-NOV-13:00 | 21.10 | 10.33 |
December | 0.111471E+10 | 3905.83 | 15-DEC-08:61 | 2.88 | 0.94 | 0.331636E+09 | 702.44 | 12-DEC-17:30 | 2.88 | 0.94 |
Annual Sum or Average | 0.404021E+11 | 0.463405E+10 | ||||||||
Minimum of Months | 0.371479E+09 | 3858.85 | -2.5 | -5.7 | 0.313979E+09 | 695.90 | 2.88 | 0.94 | ||
Maximum of Months | 0.682187E+10 | 16852.53 | 28.80 | 20.23 | 0.432048E+09 | 843.00 | 31.47 | 23.66 |
Report: ZoneCoolingSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.419405E+09 | 8385.27 | 13-JAN-19:23 | 1.15 | -2.1 | 0.109984E+10 | 1880.20 | 31-JAN-15:39 | 20.37 | 13.40 |
February | 0.115422E+10 | 10003.34 | 02-FEB-19:12 | -2.4 | -4.9 | 0.106578E+10 | 2247.80 | 25-FEB-15:50 | 20.78 | 9.45 |
March | 0.310250E+10 | 8454.33 | 30-MAR-15:00 | 27.80 | 17.08 | 0.131774E+10 | 2247.80 | 04-MAR-15:09 | 27.80 | 17.08 |
April | 0.432711E+10 | 9171.18 | 17-APR-15:00 | 28.90 | 16.41 | 0.136119E+10 | 2247.85 | 15-APR-14:00 | 28.90 | 16.41 |
May | 0.656793E+10 | 10649.24 | 30-MAY-15:00 | 30.60 | 21.44 | 0.145443E+10 | 2248.00 | 06-MAY-14:20 | 30.60 | 21.44 |
June | 0.959515E+10 | 29280.79 | 15-JUN-07:02 | 22.20 | 18.87 | 0.143006E+10 | 2248.02 | 24-JUN-14:20 | 32.40 | 22.04 |
July | 0.107270E+11 | 29224.08 | 25-JUL-07:03 | 21.20 | 18.27 | 0.143872E+10 | 2248.02 | 22-JUL-14:00 | 21.20 | 18.27 |
August | 0.116719E+11 | 27509.14 | 03-AUG-07:02 | 24.18 | 22.24 | 0.148053E+10 | 2247.92 | 26-AUG-14:09 | 32.52 | 20.65 |
September | 0.827583E+10 | 28359.50 | 09-SEP-07:03 | 22.67 | 20.24 | 0.140933E+10 | 2247.98 | 09-SEP-14:39 | 24.83 | 21.63 |
October | 0.548042E+10 | 21484.65 | 19-OCT-07:03 | 19.40 | 19.12 | 0.136961E+10 | 2247.91 | 14-OCT-14:00 | 19.40 | 19.12 |
November | 0.305934E+10 | 6952.48 | 13-NOV-09:03 | 4.78 | 1.56 | 0.123961E+10 | 2247.80 | 18-NOV-15:00 | 21.10 | 9.81 |
December | 0.152580E+10 | 6489.74 | 14-DEC-09:03 | 6.20 | 4.89 | 0.112994E+10 | 1994.97 | 12-DEC-17:19 | 6.20 | 4.89 |
Annual Sum or Average | 0.659066E+11 | 0.157968E+11 | ||||||||
Minimum of Months | 0.419405E+09 | 6489.74 | -2.4 | -4.9 | 0.106578E+10 | 1880.20 | 6.20 | 4.89 | ||
Maximum of Months | 0.116719E+11 | 29280.79 | 30.60 | 22.24 | 0.148053E+10 | 2248.02 | 32.52 | 22.04 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.185219E+09 | 3074.41 | 13-JAN-11:03 | 5.78 | 4.79 | 0.549413E+09 | 929.36 | 31-JAN-15:39 | 20.37 | 13.40 |
February | 0.541554E+09 | 4677.48 | 11-FEB-11:43 | -1.1 | -1.8 | 0.531729E+09 | 1123.87 | 25-FEB-15:39 | 20.97 | 9.57 |
March | 0.148511E+10 | 4345.70 | 30-MAR-15:00 | 27.80 | 17.08 | 0.656657E+09 | 1123.87 | 04-MAR-15:20 | 27.80 | 17.08 |
April | 0.214402E+10 | 4762.32 | 17-APR-15:00 | 28.90 | 16.41 | 0.679482E+09 | 1123.89 | 15-APR-14:00 | 28.90 | 16.41 |
May | 0.333967E+10 | 5554.56 | 30-MAY-15:00 | 30.60 | 21.44 | 0.727084E+09 | 1123.97 | 06-MAY-14:20 | 30.60 | 21.44 |
June | 0.494579E+10 | 15092.73 | 15-JUN-07:02 | 22.20 | 18.87 | 0.714985E+09 | 1123.98 | 24-JUN-14:20 | 32.40 | 22.04 |
July | 0.554558E+10 | 15029.22 | 18-JUL-07:02 | 21.97 | 20.23 | 0.719315E+09 | 1123.98 | 22-JUL-14:00 | 30.00 | 23.58 |
August | 0.603488E+10 | 14163.75 | 03-AUG-07:02 | 24.18 | 22.24 | 0.740222E+09 | 1123.93 | 26-AUG-14:09 | 32.52 | 20.65 |
September | 0.425254E+10 | 14309.49 | 27-SEP-07:02 | 21.70 | 20.20 | 0.704644E+09 | 1123.96 | 09-SEP-14:39 | 21.70 | 20.20 |
October | 0.274940E+10 | 10231.25 | 19-OCT-07:03 | 19.40 | 19.12 | 0.683994E+09 | 1123.92 | 14-OCT-14:00 | 19.40 | 19.12 |
November | 0.147174E+10 | 3521.00 | 05-NOV-15:00 | 23.90 | 18.46 | 0.618437E+09 | 1123.87 | 18-NOV-15:00 | 21.10 | 9.81 |
December | 0.709553E+09 | 4039.33 | 17-DEC-11:23 | 1.40 | -2.1 | 0.564317E+09 | 997.45 | 12-DEC-17:19 | 1.40 | -2.1 |
Annual Sum or Average | 0.334051E+11 | 0.789028E+10 | ||||||||
Minimum of Months | 0.185219E+09 | 3074.41 | -1.1 | -2.1 | 0.531729E+09 | 929.36 | 1.40 | -2.1 | ||
Maximum of Months | 0.603488E+10 | 15092.73 | 30.60 | 22.24 | 0.740222E+09 | 1123.98 | 32.52 | 23.58 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.174181E+09 | 4076.09 | 13-JAN-19:03 | 1.52 | -1.9 | 0.549029E+09 | 923.81 | 31-JAN-15:39 | 20.37 | 13.40 |
February | 0.513844E+09 | 3611.43 | 04-FEB-11:33 | 3.33 | -1.6 | 0.530730E+09 | 1123.87 | 25-FEB-15:30 | 21.15 | 9.68 |
March | 0.142158E+10 | 4256.94 | 30-MAR-15:00 | 27.80 | 17.08 | 0.654590E+09 | 1123.87 | 04-MAR-15:20 | 27.80 | 17.08 |
April | 0.207231E+10 | 4686.33 | 17-APR-15:00 | 28.90 | 16.41 | 0.678087E+09 | 1123.89 | 15-APR-14:00 | 28.90 | 16.41 |
May | 0.326535E+10 | 5494.45 | 30-MAY-15:00 | 30.60 | 21.44 | 0.726898E+09 | 1123.97 | 06-MAY-14:39 | 30.60 | 21.44 |
June | 0.489245E+10 | 14986.61 | 15-JUN-07:02 | 22.20 | 18.87 | 0.714976E+09 | 1123.98 | 24-JUN-14:20 | 32.40 | 22.04 |
July | 0.549686E+10 | 14932.82 | 18-JUL-07:02 | 21.97 | 20.23 | 0.719305E+09 | 1123.98 | 22-JUL-14:00 | 30.00 | 23.58 |
August | 0.598651E+10 | 14070.33 | 03-AUG-07:02 | 24.18 | 22.24 | 0.740217E+09 | 1123.93 | 26-AUG-14:09 | 32.52 | 20.65 |
September | 0.420651E+10 | 14212.35 | 27-SEP-07:02 | 21.70 | 20.20 | 0.704619E+09 | 1123.96 | 09-SEP-14:39 | 21.70 | 20.20 |
October | 0.269541E+10 | 9841.16 | 19-OCT-07:03 | 19.40 | 19.12 | 0.682873E+09 | 1123.92 | 14-OCT-14:00 | 19.40 | 19.12 |
November | 0.141878E+10 | 3446.49 | 05-NOV-15:00 | 23.90 | 18.46 | 0.616817E+09 | 1123.87 | 18-NOV-15:00 | 21.10 | 9.81 |
December | 0.668288E+09 | 3173.88 | 14-DEC-09:03 | 6.20 | 4.89 | 0.563636E+09 | 997.45 | 12-DEC-17:19 | 6.20 | 4.89 |
Annual Sum or Average | 0.328121E+11 | 0.788178E+10 | ||||||||
Minimum of Months | 0.174181E+09 | 3173.88 | 1.52 | -1.9 | 0.530730E+09 | 923.81 | 6.20 | 4.89 | ||
Maximum of Months | 0.598651E+10 | 14986.61 | 30.60 | 22.24 | 0.740217E+09 | 1123.98 | 32.52 | 23.58 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.136124E+09 | 3328.54 | 04-JAN-18:33 | 4.60 | 1.60 | 0.547934E+09 | 909.89 | 31-JAN-15:39 | 20.37 | 13.40 |
February | 0.439468E+09 | 2274.98 | 28-FEB-15:30 | 24.15 | 13.12 | 0.528203E+09 | 1123.86 | 25-FEB-15:09 | 24.15 | 13.12 |
March | 0.124498E+10 | 4067.48 | 30-MAR-15:00 | 27.80 | 17.08 | 0.649319E+09 | 1123.87 | 04-MAR-15:30 | 27.80 | 17.08 |
April | 0.187693E+10 | 4498.30 | 17-APR-15:00 | 28.90 | 16.41 | 0.674169E+09 | 1123.89 | 15-APR-14:00 | 28.90 | 16.41 |
May | 0.307708E+10 | 5385.20 | 30-MAY-15:00 | 30.60 | 21.44 | 0.726250E+09 | 1123.97 | 06-MAY-14:00 | 30.60 | 21.44 |
June | 0.481065E+10 | 14922.95 | 15-JUN-07:02 | 22.20 | 18.87 | 0.714952E+09 | 1123.97 | 24-JUN-14:20 | 32.40 | 22.04 |
July | 0.545507E+10 | 14887.58 | 18-JUL-07:02 | 21.97 | 20.23 | 0.719291E+09 | 1123.98 | 22-JUL-14:00 | 30.00 | 23.58 |
August | 0.596349E+10 | 14033.22 | 03-AUG-07:02 | 24.18 | 22.24 | 0.740214E+09 | 1123.99 | 12-AUG-14:09 | 30.68 | 23.13 |
September | 0.413692E+10 | 14157.36 | 27-SEP-07:02 | 21.70 | 20.20 | 0.704514E+09 | 1123.96 | 09-SEP-14:39 | 21.70 | 20.20 |
October | 0.256605E+10 | 8675.38 | 19-OCT-07:03 | 19.40 | 19.12 | 0.679998E+09 | 1123.92 | 14-OCT-14:00 | 19.40 | 19.12 |
November | 0.127998E+10 | 3280.58 | 05-NOV-15:00 | 23.90 | 18.46 | 0.612845E+09 | 1123.87 | 18-NOV-15:00 | 21.10 | 9.81 |
December | 0.550840E+09 | 3341.34 | 01-DEC-20:43 | 4.50 | 0.17 | 0.561851E+09 | 997.44 | 12-DEC-17:19 | 21.13 | 15.93 |
Annual Sum or Average | 0.315376E+11 | 0.785954E+10 | ||||||||
Minimum of Months | 0.136124E+09 | 2274.98 | 4.50 | 0.17 | 0.528203E+09 | 909.89 | 19.40 | 9.81 | ||
Maximum of Months | 0.596349E+10 | 14922.95 | 30.60 | 22.24 | 0.740214E+09 | 1123.99 | 32.40 | 23.58 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 76500363.32 | 1090.47 | 20-JAN-19:30 | 14.45 | 10.16 | 0.546569E+09 | 894.53 | 31-JAN-15:39 | 20.37 | 13.40 |
February | 0.313259E+09 | 2167.72 | 28-FEB-15:30 | 24.15 | 13.12 | 0.525302E+09 | 1123.86 | 25-FEB-15:00 | 24.15 | 13.12 |
March | 0.910092E+09 | 4178.83 | 30-MAR-14:50 | 27.80 | 17.21 | 0.641921E+09 | 1123.87 | 04-MAR-15:00 | 27.80 | 17.21 |
April | 0.164773E+10 | 4606.54 | 17-APR-14:30 | 28.90 | 16.52 | 0.667940E+09 | 1123.89 | 15-APR-14:00 | 28.90 | 16.52 |
May | 0.313348E+10 | 5842.49 | 30-MAY-14:30 | 30.60 | 21.24 | 0.724812E+09 | 1123.98 | 06-MAY-14:00 | 30.60 | 21.24 |
June | 0.538322E+10 | 13527.81 | 14-JUN-07:02 | 22.30 | 20.01 | 0.714972E+09 | 1123.97 | 17-JUN-14:00 | 26.10 | 20.69 |
July | 0.625155E+10 | 15458.83 | 17-JUL-07:02 | 22.07 | 19.58 | 0.719357E+09 | 1123.93 | 01-JUL-14:09 | 22.07 | 19.58 |
August | 0.686815E+10 | 14552.40 | 10-AUG-07:02 | 25.37 | 23.14 | 0.740319E+09 | 1124.00 | 12-AUG-14:30 | 30.85 | 23.40 |
September | 0.460616E+10 | 14453.71 | 27-SEP-07:02 | 21.70 | 20.20 | 0.704065E+09 | 1123.98 | 09-SEP-14:00 | 21.70 | 20.20 |
October | 0.256104E+10 | 6323.57 | 10-OCT-14:10 | 29.32 | 20.98 | 0.676458E+09 | 1123.91 | 14-OCT-14:39 | 22.20 | 13.64 |
November | 0.105494E+10 | 3325.94 | 21-NOV-19:03 | 4.22 | 0.75 | 0.608615E+09 | 1123.87 | 18-NOV-15:00 | 4.22 | 0.75 |
December | 0.321446E+09 | 2904.47 | 08-DEC-19:53 | 6.10 | 1.40 | 0.559734E+09 | 997.43 | 12-DEC-13:00 | 22.80 | 17.07 |
Annual Sum or Average | 0.331276E+11 | 0.783007E+10 | ||||||||
Minimum of Months | 76500363.32 | 1090.47 | 4.22 | 0.75 | 0.525302E+09 | 894.53 | 4.22 | 0.75 | ||
Maximum of Months | 0.686815E+10 | 15458.83 | 30.60 | 23.14 | 0.740319E+09 | 1124.00 | 30.85 | 23.40 |
Report: ZoneHeatingSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.331946E+10 | 57480.40 | 28-JAN-08:61 | -4.0 |
February | 0.205101E+10 | 57486.30 | 12-FEB-08:61 | -11.9 |
March | 0.294671E+09 | 57437.43 | 20-MAR-07:01 | 5.10 |
April | 0.127919E+09 | 57455.57 | 07-APR-07:01 | 3.53 |
May | 37554168.65 | 1064.91 | 31-MAY-07:07 | 19.50 |
June | 29487482.02 | 1632.07 | 28-JUN-07:05 | 23.17 |
July | 28104394.81 | 1659.08 | 21-JUL-07:05 | 23.68 |
August | 25512291.95 | 1644.61 | 30-AUG-07:05 | 20.18 |
September | 27007536.64 | 1804.02 | 16-SEP-07:05 | 22.20 |
October | 75504320.66 | 37534.40 | 26-OCT-07:01 | 2.57 |
November | 0.198135E+09 | 57430.08 | 22-NOV-08:61 | -2.2 |
December | 0.103211E+10 | 57468.17 | 18-DEC-08:61 | -5.0 |
Annual Sum or Average | 0.724646E+10 | |||
Minimum of Months | 25512291.95 | 1064.91 | -11.9 | |
Maximum of Months | 0.331946E+10 | 57486.30 | 23.68 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.907899E+09 | 30084.12 | 28-JAN-08:61 | -4.0 |
February | 0.529751E+09 | 30089.89 | 12-FEB-08:61 | -11.9 |
March | 53780589.85 | 22458.05 | 23-MAR-07:01 | 6.20 |
April | 33535380.80 | 5210.46 | 07-APR-07:01 | 3.53 |
May | 15672610.51 | 740.77 | 31-MAY-07:07 | 19.50 |
June | 14321711.18 | 976.71 | 28-JUN-07:05 | 23.17 |
July | 15635879.99 | 1003.73 | 21-JUL-07:05 | 23.68 |
August | 12585997.23 | 982.92 | 30-AUG-07:05 | 20.18 |
September | 14535811.25 | 1028.38 | 16-SEP-07:05 | 22.20 |
October | 29929120.74 | 922.41 | 19-OCT-07:05 | 19.40 |
November | 55294625.41 | 30056.77 | 22-NOV-08:61 | -2.2 |
December | 0.183088E+09 | 30072.83 | 18-DEC-08:61 | -5.0 |
Annual Sum or Average | 0.186603E+10 | |||
Minimum of Months | 12585997.23 | 740.77 | -11.9 | |
Maximum of Months | 0.907899E+09 | 30089.89 | 23.68 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.124403E+10 | 30175.19 | 15-JAN-08:61 | -4.2 |
February | 0.713714E+09 | 30190.61 | 12-FEB-08:61 | -11.9 |
March | 73770828.91 | 15326.52 | 19-MAR-07:02 | 1.57 |
April | 38664658.46 | 2460.02 | 06-APR-07:03 | 2.25 |
May | 38114743.09 | 1606.60 | 29-MAY-16:03 | 30.00 |
June | 89008144.46 | 2367.23 | 25-JUN-16:02 | 33.22 |
July | 0.111847E+09 | 2683.86 | 08-JUL-17:02 | 34.40 |
August | 99302943.16 | 2305.31 | 06-AUG-16:02 | 32.70 |
September | 42972144.97 | 1661.35 | 03-SEP-16:02 | 30.00 |
October | 31936860.41 | 1056.78 | 09-OCT-16:03 | 27.62 |
November | 70187807.88 | 29471.37 | 22-NOV-07:02 | -3.2 |
December | 0.357012E+09 | 30064.37 | 03-DEC-08:61 | -3.4 |
Annual Sum or Average | 0.291056E+10 | |||
Minimum of Months | 31936860.41 | 1056.78 | -11.9 | |
Maximum of Months | 0.124403E+10 | 30190.61 | 34.40 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.139311E+10 | 30249.64 | 15-JAN-08:61 | -4.2 |
February | 0.785602E+09 | 30265.31 | 12-FEB-08:61 | -11.9 |
March | 88200972.89 | 19429.99 | 19-MAR-07:02 | 1.57 |
April | 41411303.57 | 2888.71 | 07-APR-06:05 | 2.80 |
May | 39267755.09 | 1609.79 | 29-MAY-16:03 | 30.00 |
June | 88935140.01 | 2367.22 | 25-JUN-16:02 | 33.22 |
July | 0.111620E+09 | 2683.50 | 08-JUL-17:02 | 34.40 |
August | 98835987.36 | 2305.64 | 06-AUG-16:02 | 32.70 |
September | 43047708.64 | 1663.24 | 03-SEP-16:02 | 30.00 |
October | 33273421.42 | 2965.57 | 26-OCT-07:04 | 2.57 |
November | 79556443.99 | 29542.02 | 22-NOV-07:02 | -3.2 |
December | 0.431875E+09 | 30138.23 | 03-DEC-08:61 | -3.4 |
Annual Sum or Average | 0.323473E+10 | |||
Minimum of Months | 33273421.42 | 1609.79 | -11.9 | |
Maximum of Months | 0.139311E+10 | 30265.31 | 34.40 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.163845E+10 | 30028.09 | 15-JAN-08:61 | -4.2 |
February | 0.929875E+09 | 30043.52 | 12-FEB-08:61 | -11.9 |
March | 0.110703E+09 | 23587.12 | 19-MAR-07:02 | 1.57 |
April | 49647189.96 | 4818.72 | 07-APR-06:05 | 2.80 |
May | 40335088.17 | 1616.91 | 29-MAY-16:03 | 30.00 |
June | 90226553.71 | 2371.86 | 25-JUN-16:02 | 33.22 |
July | 0.112346E+09 | 2688.12 | 08-JUL-17:02 | 34.40 |
August | 0.100553E+09 | 2308.71 | 06-AUG-16:02 | 32.70 |
September | 43308962.07 | 1667.70 | 03-SEP-16:02 | 30.00 |
October | 36792115.94 | 2576.38 | 26-OCT-07:03 | 2.57 |
November | 97267792.55 | 29332.64 | 22-NOV-07:02 | -3.2 |
December | 0.541200E+09 | 29918.61 | 03-DEC-08:61 | -3.4 |
Annual Sum or Average | 0.379071E+10 | |||
Minimum of Months | 36792115.94 | 1616.91 | -11.9 | |
Maximum of Months | 0.163845E+10 | 30043.52 | 34.40 |
Report: ZoneHeatingSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.345380E+10 | 54378.36 | 28-JAN-08:61 | -4.0 |
February | 0.198415E+10 | 54477.26 | 12-FEB-09:12 | -9.8 |
March | 0.290806E+09 | 54342.86 | 20-MAR-07:01 | 5.10 |
April | 0.116128E+09 | 54349.66 | 07-APR-07:01 | 3.53 |
May | 63167398.83 | 3250.84 | 29-MAY-16:03 | 30.00 |
June | 97413923.03 | 4757.62 | 25-JUN-16:02 | 33.22 |
July | 0.116698E+09 | 5382.82 | 08-JUL-17:02 | 34.40 |
August | 85835791.83 | 4608.43 | 06-AUG-16:02 | 32.70 |
September | 59467764.62 | 3329.45 | 03-SEP-16:02 | 30.00 |
October | 86024680.77 | 34367.69 | 26-OCT-07:01 | 2.57 |
November | 0.204045E+09 | 54340.05 | 22-NOV-08:61 | -2.2 |
December | 0.119547E+10 | 54372.14 | 18-DEC-08:61 | -5.0 |
Annual Sum or Average | 0.775301E+10 | |||
Minimum of Months | 59467764.62 | 3250.84 | -9.8 | |
Maximum of Months | 0.345380E+10 | 54477.26 | 34.40 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.199346E+10 | 27996.18 | 28-JAN-08:61 | -4.0 |
February | 0.115289E+10 | 28093.62 | 12-FEB-09:12 | -9.8 |
March | 0.171066E+09 | 27975.92 | 20-MAR-07:01 | 5.10 |
April | 65678522.31 | 27979.91 | 07-APR-07:01 | 3.53 |
May | 35276039.41 | 1636.53 | 29-MAY-16:03 | 30.00 |
June | 50432763.30 | 2387.99 | 25-JUN-16:02 | 33.22 |
July | 59970579.05 | 2705.84 | 08-JUL-17:02 | 34.40 |
August | 44193123.43 | 2316.15 | 06-AUG-16:02 | 32.70 |
September | 31086562.96 | 1677.46 | 03-SEP-16:02 | 30.00 |
October | 47627187.57 | 18280.06 | 26-OCT-07:01 | 2.57 |
November | 0.123274E+09 | 27975.70 | 22-NOV-08:61 | -2.2 |
December | 0.712589E+09 | 27992.74 | 18-DEC-08:61 | -5.0 |
Annual Sum or Average | 0.448754E+10 | |||
Minimum of Months | 31086562.96 | 1636.53 | -9.8 | |
Maximum of Months | 0.199346E+10 | 28093.62 | 34.40 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.206142E+10 | 27891.85 | 28-JAN-08:61 | -4.0 |
February | 0.119362E+10 | 28002.79 | 12-FEB-09:12 | -9.8 |
March | 0.187280E+09 | 27871.44 | 20-MAR-07:01 | 5.10 |
April | 69573109.20 | 27875.55 | 07-APR-07:01 | 3.53 |
May | 36314263.29 | 1638.68 | 29-MAY-16:03 | 30.00 |
June | 50658524.52 | 2388.99 | 25-JUN-16:02 | 33.22 |
July | 60026575.32 | 2706.65 | 08-JUL-17:02 | 34.40 |
August | 44294856.70 | 2316.60 | 06-AUG-16:02 | 32.70 |
September | 31337933.36 | 1678.11 | 03-SEP-16:02 | 30.00 |
October | 49657772.98 | 20556.18 | 26-OCT-07:01 | 2.57 |
November | 0.130808E+09 | 27871.58 | 22-NOV-08:61 | -2.2 |
December | 0.747354E+09 | 27888.37 | 18-DEC-08:61 | -5.0 |
Annual Sum or Average | 0.466234E+10 | |||
Minimum of Months | 31337933.36 | 1638.68 | -9.8 | |
Maximum of Months | 0.206142E+10 | 28002.79 | 34.40 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.239819E+10 | 27904.58 | 28-JAN-08:61 | -4.0 |
February | 0.140538E+10 | 28069.00 | 12-FEB-09:12 | -9.8 |
March | 0.252578E+09 | 27885.33 | 20-MAR-07:01 | 5.10 |
April | 87012902.31 | 27889.38 | 07-APR-07:01 | 3.53 |
May | 43033195.01 | 1646.03 | 29-MAY-16:03 | 30.00 |
June | 51039414.00 | 2390.21 | 25-JUN-16:02 | 33.22 |
July | 59710289.08 | 2706.07 | 08-JUL-17:02 | 34.40 |
August | 43605559.27 | 2316.67 | 06-AUG-16:02 | 32.70 |
September | 33252245.76 | 1680.59 | 03-SEP-16:02 | 30.00 |
October | 59411372.68 | 27517.23 | 26-OCT-07:01 | 2.57 |
November | 0.168137E+09 | 27883.71 | 22-NOV-08:61 | -2.2 |
December | 0.921156E+09 | 27901.64 | 18-DEC-08:61 | -5.0 |
Annual Sum or Average | 0.552251E+10 | |||
Minimum of Months | 33252245.76 | 1646.03 | -9.8 | |
Maximum of Months | 0.239819E+10 | 28069.00 | 34.40 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.396375E+10 | 30962.30 | 10-JAN-08:12 | -4.8 |
February | 0.249992E+10 | 31009.80 | 12-FEB-09:12 | -9.8 |
March | 0.589015E+09 | 30712.50 | 20-MAR-07:01 | 5.10 |
April | 0.195650E+09 | 30716.92 | 07-APR-07:01 | 3.53 |
May | 57032481.54 | 3943.43 | 11-MAY-07:03 | 10.28 |
June | 52825995.72 | 2374.28 | 25-JUN-16:02 | 33.22 |
July | 60222130.47 | 2679.93 | 08-JUL-17:02 | 34.40 |
August | 42288351.03 | 2302.75 | 06-AUG-16:02 | 32.70 |
September | 41453381.48 | 1684.24 | 03-SEP-16:02 | 30.00 |
October | 0.115971E+09 | 30254.73 | 26-OCT-07:01 | 2.57 |
November | 0.367798E+09 | 30704.04 | 22-NOV-08:61 | -2.2 |
December | 0.166387E+10 | 30731.11 | 18-DEC-08:61 | -5.0 |
Annual Sum or Average | 0.964980E+10 | |||
Minimum of Months | 41453381.48 | 1684.24 | -9.8 | |
Maximum of Months | 0.396375E+10 | 31009.80 | 34.40 |
Report: ZoneElectricSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.739462E+10 | 4621.63 | 01-JAN-10:09 | 0.222596E+10 | 1343.25 | 01-JAN-10:09 |
February | 0.668410E+10 | 4621.63 | 01-FEB-10:09 | 0.201408E+10 | 1343.25 | 01-FEB-10:09 |
March | 0.740180E+10 | 4621.63 | 01-MAR-10:09 | 0.223295E+10 | 1343.25 | 01-MAR-10:09 |
April | 0.716384E+10 | 4621.63 | 01-APR-09:09 | 0.215748E+10 | 1343.25 | 01-APR-09:09 |
May | 0.739462E+10 | 4621.63 | 01-MAY-09:09 | 0.222596E+10 | 1343.25 | 01-MAY-09:09 |
June | 0.716485E+10 | 4621.63 | 01-JUN-09:09 | 0.216232E+10 | 1343.25 | 01-JUN-09:09 |
July | 0.740069E+10 | 4621.63 | 01-JUL-09:09 | 0.222811E+10 | 1343.25 | 01-JUL-09:09 |
August | 0.739513E+10 | 4621.63 | 01-AUG-09:09 | 0.222838E+10 | 1343.25 | 01-AUG-09:09 |
September | 0.717041E+10 | 4621.63 | 01-SEP-09:09 | 0.216205E+10 | 1343.25 | 01-SEP-09:09 |
October | 0.739462E+10 | 4621.63 | 01-OCT-09:09 | 0.222596E+10 | 1343.25 | 01-OCT-09:09 |
November | 0.714323E+10 | 4621.63 | 01-NOV-09:09 | 0.215077E+10 | 1343.25 | 01-NOV-09:09 |
December | 0.740776E+10 | 4621.63 | 01-DEC-10:09 | 0.223509E+10 | 1343.25 | 01-DEC-10:09 |
Annual Sum or Average | 0.871157E+11 | 0.262491E+11 | ||||
Minimum of Months | 0.668410E+10 | 4621.63 | 0.201408E+10 | 1343.25 | ||
Maximum of Months | 0.740776E+10 | 4621.63 | 0.223509E+10 | 1343.25 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.451584E+10 | 2827.07 | 01-JAN-10:09 | 0.111298E+10 | 671.63 | 01-JAN-10:09 |
February | 0.408193E+10 | 2827.07 | 01-FEB-10:09 | 0.100704E+10 | 671.63 | 01-FEB-10:09 |
March | 0.452026E+10 | 2827.07 | 01-MAR-10:09 | 0.111647E+10 | 671.63 | 01-MAR-10:09 |
April | 0.437489E+10 | 2827.07 | 01-APR-09:09 | 0.107874E+10 | 671.63 | 01-APR-09:09 |
May | 0.451584E+10 | 2827.07 | 01-MAY-09:09 | 0.111298E+10 | 671.63 | 01-MAY-09:09 |
June | 0.437556E+10 | 2827.07 | 01-JUN-09:09 | 0.108116E+10 | 671.63 | 01-JUN-09:09 |
July | 0.451952E+10 | 2827.07 | 01-JUL-09:09 | 0.111405E+10 | 671.63 | 01-JUL-09:09 |
August | 0.451617E+10 | 2827.07 | 01-AUG-09:09 | 0.111419E+10 | 671.63 | 01-AUG-09:09 |
September | 0.437891E+10 | 2827.07 | 01-SEP-09:09 | 0.108102E+10 | 671.63 | 01-SEP-09:09 |
October | 0.451584E+10 | 2827.07 | 01-OCT-09:09 | 0.111298E+10 | 671.63 | 01-OCT-09:09 |
November | 0.436230E+10 | 2827.07 | 01-NOV-09:09 | 0.107538E+10 | 671.63 | 01-NOV-09:09 |
December | 0.452388E+10 | 2827.07 | 01-DEC-10:09 | 0.111755E+10 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.532009E+11 | 0.131245E+11 | ||||
Minimum of Months | 0.408193E+10 | 2827.07 | 0.100704E+10 | 671.63 | ||
Maximum of Months | 0.452388E+10 | 2827.07 | 0.111755E+10 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.317044E+10 | 2555.22 | 01-JAN-10:09 | 0.879849E+09 | 671.63 | 01-JAN-10:09 |
February | 0.287181E+10 | 2555.22 | 01-FEB-09:09 | 0.796766E+09 | 671.63 | 01-FEB-09:09 |
March | 0.324295E+10 | 2555.22 | 01-MAR-09:09 | 0.898128E+09 | 671.63 | 01-MAR-09:09 |
April | 0.307694E+10 | 2555.22 | 01-APR-08:09 | 0.853677E+09 | 671.63 | 01-APR-08:09 |
May | 0.320669E+10 | 2555.22 | 01-MAY-08:09 | 0.888989E+09 | 671.63 | 01-MAY-08:09 |
June | 0.313132E+10 | 2555.22 | 01-JUN-08:09 | 0.867387E+09 | 671.63 | 01-JUN-08:09 |
July | 0.315231E+10 | 2555.22 | 01-JUL-08:09 | 0.875279E+09 | 671.63 | 01-JUL-08:09 |
August | 0.324295E+10 | 2555.22 | 01-AUG-08:09 | 0.898128E+09 | 671.63 | 01-AUG-08:09 |
September | 0.307694E+10 | 2555.22 | 01-SEP-08:09 | 0.853677E+09 | 671.63 | 01-SEP-08:09 |
October | 0.317044E+10 | 2555.22 | 01-OCT-09:09 | 0.879849E+09 | 671.63 | 01-OCT-09:09 |
November | 0.307694E+10 | 2555.22 | 01-NOV-08:09 | 0.853679E+09 | 671.63 | 01-NOV-08:09 |
December | 0.315231E+10 | 2555.22 | 01-DEC-09:09 | 0.875279E+09 | 671.63 | 01-DEC-09:09 |
Annual Sum or Average | 0.375720E+11 | 0.104207E+11 | ||||
Minimum of Months | 0.287181E+10 | 2555.22 | 0.796766E+09 | 671.63 | ||
Maximum of Months | 0.324295E+10 | 2555.22 | 0.898128E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.317044E+10 | 2555.22 | 01-JAN-10:09 | 0.879849E+09 | 671.63 | 01-JAN-10:09 |
February | 0.287181E+10 | 2555.22 | 01-FEB-09:09 | 0.796766E+09 | 671.63 | 01-FEB-09:09 |
March | 0.324295E+10 | 2555.22 | 01-MAR-09:09 | 0.898128E+09 | 671.63 | 01-MAR-09:09 |
April | 0.307694E+10 | 2555.22 | 01-APR-08:09 | 0.853677E+09 | 671.63 | 01-APR-08:09 |
May | 0.320669E+10 | 2555.22 | 01-MAY-08:09 | 0.888989E+09 | 671.63 | 01-MAY-08:09 |
June | 0.313132E+10 | 2555.22 | 01-JUN-08:09 | 0.867387E+09 | 671.63 | 01-JUN-08:09 |
July | 0.315231E+10 | 2555.22 | 01-JUL-08:09 | 0.875279E+09 | 671.63 | 01-JUL-08:09 |
August | 0.324295E+10 | 2555.22 | 01-AUG-08:09 | 0.898128E+09 | 671.63 | 01-AUG-08:09 |
September | 0.307694E+10 | 2555.22 | 01-SEP-08:09 | 0.853677E+09 | 671.63 | 01-SEP-08:09 |
October | 0.317044E+10 | 2555.22 | 01-OCT-09:09 | 0.879849E+09 | 671.63 | 01-OCT-09:09 |
November | 0.307694E+10 | 2555.22 | 01-NOV-08:09 | 0.853679E+09 | 671.63 | 01-NOV-08:09 |
December | 0.315231E+10 | 2555.22 | 01-DEC-09:09 | 0.875279E+09 | 671.63 | 01-DEC-09:09 |
Annual Sum or Average | 0.375720E+11 | 0.104207E+11 | ||||
Minimum of Months | 0.287181E+10 | 2555.22 | 0.796766E+09 | 671.63 | ||
Maximum of Months | 0.324295E+10 | 2555.22 | 0.898128E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.317044E+10 | 2555.22 | 01-JAN-10:09 | 0.879849E+09 | 671.63 | 01-JAN-10:09 |
February | 0.287181E+10 | 2555.22 | 01-FEB-09:09 | 0.796766E+09 | 671.63 | 01-FEB-09:09 |
March | 0.324295E+10 | 2555.22 | 01-MAR-09:09 | 0.898128E+09 | 671.63 | 01-MAR-09:09 |
April | 0.307694E+10 | 2555.22 | 01-APR-08:09 | 0.853677E+09 | 671.63 | 01-APR-08:09 |
May | 0.320669E+10 | 2555.22 | 01-MAY-08:09 | 0.888989E+09 | 671.63 | 01-MAY-08:09 |
June | 0.313132E+10 | 2555.22 | 01-JUN-08:09 | 0.867387E+09 | 671.63 | 01-JUN-08:09 |
July | 0.315231E+10 | 2555.22 | 01-JUL-08:09 | 0.875279E+09 | 671.63 | 01-JUL-08:09 |
August | 0.324295E+10 | 2555.22 | 01-AUG-08:09 | 0.898128E+09 | 671.63 | 01-AUG-08:09 |
September | 0.307694E+10 | 2555.22 | 01-SEP-08:09 | 0.853677E+09 | 671.63 | 01-SEP-08:09 |
October | 0.317044E+10 | 2555.22 | 01-OCT-09:09 | 0.879849E+09 | 671.63 | 01-OCT-09:09 |
November | 0.307694E+10 | 2555.22 | 01-NOV-08:09 | 0.853679E+09 | 671.63 | 01-NOV-08:09 |
December | 0.315231E+10 | 2555.22 | 01-DEC-09:09 | 0.875279E+09 | 671.63 | 01-DEC-09:09 |
Annual Sum or Average | 0.375720E+11 | 0.104207E+11 | ||||
Minimum of Months | 0.287181E+10 | 2555.22 | 0.796766E+09 | 671.63 | ||
Maximum of Months | 0.324295E+10 | 2555.22 | 0.898128E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.313454E+10 | 2726.96 | 01-JAN-11:09 | 0.161799E+10 | 1343.25 | 01-JAN-11:09 |
February | 0.283982E+10 | 2726.96 | 01-FEB-10:09 | 0.146554E+10 | 1343.25 | 01-FEB-10:09 |
March | 0.321092E+10 | 2726.96 | 01-MAR-10:09 | 0.165455E+10 | 1343.25 | 01-MAR-10:09 |
April | 0.304266E+10 | 2726.96 | 01-APR-09:09 | 0.157022E+10 | 1343.25 | 01-APR-09:09 |
May | 0.317273E+10 | 2726.96 | 01-MAY-09:09 | 0.163627E+10 | 1343.25 | 01-MAY-09:09 |
June | 0.309995E+10 | 2726.96 | 01-JUN-09:09 | 0.159764E+10 | 1343.25 | 01-JUN-09:09 |
July | 0.311545E+10 | 2726.96 | 01-JUL-09:09 | 0.160885E+10 | 1343.25 | 01-JUL-09:09 |
August | 0.321092E+10 | 2726.96 | 01-AUG-09:09 | 0.165455E+10 | 1343.25 | 01-AUG-09:09 |
September | 0.304266E+10 | 2726.96 | 01-SEP-09:09 | 0.157022E+10 | 1343.25 | 01-SEP-09:09 |
October | 0.313454E+10 | 2726.96 | 01-OCT-10:09 | 0.161799E+10 | 1343.25 | 01-OCT-10:09 |
November | 0.304266E+10 | 2726.96 | 01-NOV-09:09 | 0.157022E+10 | 1343.25 | 01-NOV-09:09 |
December | 0.311545E+10 | 2726.96 | 01-DEC-10:09 | 0.160885E+10 | 1343.25 | 01-DEC-10:09 |
Annual Sum or Average | 0.371623E+11 | 0.191729E+11 | ||||
Minimum of Months | 0.283982E+10 | 2726.96 | 0.146554E+10 | 1343.25 | ||
Maximum of Months | 0.321092E+10 | 2726.96 | 0.165455E+10 | 1343.25 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.161274E+10 | 1404.46 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.146111E+10 | 1404.46 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.165211E+10 | 1404.46 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.156548E+10 | 1404.46 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.163243E+10 | 1404.46 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.159501E+10 | 1404.46 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.160290E+10 | 1404.46 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.165211E+10 | 1404.46 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.156548E+10 | 1404.46 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.161274E+10 | 1404.46 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.156548E+10 | 1404.46 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.160290E+10 | 1404.46 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.191205E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.146111E+10 | 1404.46 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.165211E+10 | 1404.46 | 0.827277E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.161274E+10 | 1404.46 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.146111E+10 | 1404.46 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.165211E+10 | 1404.46 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.156548E+10 | 1404.46 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.163243E+10 | 1404.46 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.159501E+10 | 1404.46 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.160290E+10 | 1404.46 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.165211E+10 | 1404.46 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.156548E+10 | 1404.46 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.161274E+10 | 1404.46 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.156548E+10 | 1404.46 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.160290E+10 | 1404.46 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.191205E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.146111E+10 | 1404.46 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.165211E+10 | 1404.46 | 0.827277E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.161274E+10 | 1404.46 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.146111E+10 | 1404.46 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.165211E+10 | 1404.46 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.156548E+10 | 1404.46 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.163243E+10 | 1404.46 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.159501E+10 | 1404.46 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.160290E+10 | 1404.46 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.165211E+10 | 1404.46 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.156548E+10 | 1404.46 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.161274E+10 | 1404.46 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.156548E+10 | 1404.46 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.160290E+10 | 1404.46 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.191205E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.146111E+10 | 1404.46 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.165211E+10 | 1404.46 | 0.827277E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.161274E+10 | 1404.46 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.146111E+10 | 1404.46 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.165211E+10 | 1404.46 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.156548E+10 | 1404.46 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.163243E+10 | 1404.46 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.159501E+10 | 1404.46 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.160290E+10 | 1404.46 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.165211E+10 | 1404.46 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.156548E+10 | 1404.46 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.161274E+10 | 1404.46 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.156548E+10 | 1404.46 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.160290E+10 | 1404.46 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.191205E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.146111E+10 | 1404.46 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.165211E+10 | 1404.46 | 0.827277E+09 | 671.63 |
Report: SpaceGainsMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.338624E+10 | 0.739462E+10 | 0.222596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.456280E+10 |
February | 0.305697E+10 | 0.668410E+10 | 0.201408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4234202.28 | 0.322421E+10 |
March | 0.335708E+10 | 0.740180E+10 | 0.223295E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36079759.06 | 0.199083E+10 |
April | 0.327081E+10 | 0.716384E+10 | 0.215748E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.198149E+09 | 0.981902E+09 |
May | 0.336680E+10 | 0.739462E+10 | 0.222596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.469935E+09 | 0.480379E+09 |
June | 0.325380E+10 | 0.716485E+10 | 0.216232E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119475E+10 | 0.170784E+09 |
July | 0.339353E+10 | 0.740069E+10 | 0.222811E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139116E+10 | 0.152564E+09 |
August | 0.334857E+10 | 0.739513E+10 | 0.222838E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136695E+10 | 70568238.65 |
September | 0.327932E+10 | 0.717041E+10 | 0.216205E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.551630E+09 | 0.305852E+09 |
October | 0.338624E+10 | 0.739462E+10 | 0.222596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107573E+09 | 0.138684E+10 |
November | 0.327446E+10 | 0.714323E+10 | 0.215077E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 654804.82 | 0.216597E+10 |
December | 0.340325E+10 | 0.740776E+10 | 0.223509E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.338743E+10 |
Annual Sum or Average | 0.397770E+11 | 0.871157E+11 | 0.262491E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.532112E+10 | 0.188801E+11 |
Minimum of Months | 0.305697E+10 | 0.668410E+10 | 0.201408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70568238.65 |
Maximum of Months | 0.340325E+10 | 0.740776E+10 | 0.223509E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139116E+10 | 0.456280E+10 |
Report: SpaceGainsMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.169307E+10 | 0.451584E+10 | 0.111298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.223242E+10 |
February | 0.152844E+10 | 0.408193E+10 | 0.100704E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2281997.61 | 0.154497E+10 |
March | 0.167849E+10 | 0.452026E+10 | 0.111647E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19339894.37 | 0.973424E+09 |
April | 0.163536E+10 | 0.437489E+10 | 0.107874E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108512E+09 | 0.456459E+09 |
May | 0.168335E+10 | 0.451584E+10 | 0.111298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.256216E+09 | 0.196092E+09 |
June | 0.162685E+10 | 0.437556E+10 | 0.108116E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.643972E+09 | 57466608.13 |
July | 0.169671E+10 | 0.451952E+10 | 0.111405E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.753696E+09 | 60859439.53 |
August | 0.167424E+10 | 0.451617E+10 | 0.111419E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.739020E+09 | 23057034.74 |
September | 0.163961E+10 | 0.437891E+10 | 0.108102E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.300518E+09 | 0.128852E+09 |
October | 0.169307E+10 | 0.451584E+10 | 0.111298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 58610206.20 | 0.653756E+09 |
November | 0.163718E+10 | 0.436230E+10 | 0.107538E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 356329.89 | 0.103922E+10 |
December | 0.170157E+10 | 0.452388E+10 | 0.111755E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163381E+10 |
Annual Sum or Average | 0.198880E+11 | 0.532009E+11 | 0.131245E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.288252E+10 | 0.900039E+10 |
Minimum of Months | 0.152844E+10 | 0.408193E+10 | 0.100704E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23057034.74 |
Maximum of Months | 0.170157E+10 | 0.452388E+10 | 0.111755E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.753696E+09 | 0.223242E+10 |
Report: SpaceGainsMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.317044E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.228301E+10 |
February | 0.914877E+09 | 0.287181E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2281997.61 | 0.158280E+10 |
March | 0.103395E+10 | 0.324295E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19306566.69 | 0.990010E+09 |
April | 0.984131E+09 | 0.307694E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105974E+09 | 0.476469E+09 |
May | 0.102058E+10 | 0.320669E+10 | 0.888989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.250602E+09 | 0.213061E+09 |
June | 0.998711E+09 | 0.313132E+10 | 0.867387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.633599E+09 | 65426421.25 |
July | 0.100600E+10 | 0.315231E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.739606E+09 | 67347318.57 |
August | 0.103395E+10 | 0.324295E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.727991E+09 | 28253908.99 |
September | 0.984131E+09 | 0.307694E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.291315E+09 | 0.140971E+09 |
October | 0.100722E+10 | 0.317044E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 55605324.35 | 0.674987E+09 |
November | 0.973196E+09 | 0.307694E+10 | 0.853679E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 343472.60 | 0.105975E+10 |
December | 0.100600E+10 | 0.315231E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.167116E+10 |
Annual Sum or Average | 0.119700E+11 | 0.375720E+11 | 0.104207E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.282662E+10 | 0.925325E+10 |
Minimum of Months | 0.914877E+09 | 0.287181E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28253908.99 |
Maximum of Months | 0.103395E+10 | 0.324295E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.739606E+09 | 0.228301E+10 |
Report: SpaceGainsMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.317044E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.227510E+10 |
February | 0.914877E+09 | 0.287181E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2281997.61 | 0.157242E+10 |
March | 0.103395E+10 | 0.324295E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19307127.66 | 0.978795E+09 |
April | 0.984131E+09 | 0.307694E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105981E+09 | 0.472818E+09 |
May | 0.102058E+10 | 0.320669E+10 | 0.888989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.250611E+09 | 0.212458E+09 |
June | 0.998711E+09 | 0.313132E+10 | 0.867387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.633493E+09 | 65758367.43 |
July | 0.100600E+10 | 0.315231E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.739336E+09 | 67747336.48 |
August | 0.103395E+10 | 0.324295E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.727777E+09 | 28783109.26 |
September | 0.984131E+09 | 0.307694E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.291304E+09 | 0.140966E+09 |
October | 0.100722E+10 | 0.317044E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 55622522.37 | 0.670396E+09 |
November | 0.973196E+09 | 0.307694E+10 | 0.853679E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 343472.40 | 0.105080E+10 |
December | 0.100600E+10 | 0.315231E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166120E+10 |
Annual Sum or Average | 0.119700E+11 | 0.375720E+11 | 0.104207E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.282606E+10 | 0.919725E+10 |
Minimum of Months | 0.914877E+09 | 0.287181E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28783109.26 |
Maximum of Months | 0.103395E+10 | 0.324295E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.739336E+09 | 0.227510E+10 |
Report: SpaceGainsMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.317044E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.226670E+10 |
February | 0.914877E+09 | 0.287181E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2281997.61 | 0.155946E+10 |
March | 0.103395E+10 | 0.324295E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19308540.00 | 0.961506E+09 |
April | 0.984131E+09 | 0.307694E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106015E+09 | 0.464640E+09 |
May | 0.102058E+10 | 0.320669E+10 | 0.888989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.250730E+09 | 0.209810E+09 |
June | 0.998711E+09 | 0.313132E+10 | 0.867387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.633828E+09 | 64153183.45 |
July | 0.100600E+10 | 0.315231E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.739871E+09 | 66530934.03 |
August | 0.103395E+10 | 0.324295E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.728201E+09 | 27436335.25 |
September | 0.984131E+09 | 0.307694E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.291480E+09 | 0.139505E+09 |
October | 0.100722E+10 | 0.317044E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 55679918.10 | 0.661994E+09 |
November | 0.973196E+09 | 0.307694E+10 | 0.853679E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 343472.18 | 0.103810E+10 |
December | 0.100600E+10 | 0.315231E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165030E+10 |
Annual Sum or Average | 0.119700E+11 | 0.375720E+11 | 0.104207E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.282774E+10 | 0.911013E+10 |
Minimum of Months | 0.914877E+09 | 0.287181E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27436335.25 |
Maximum of Months | 0.103395E+10 | 0.324295E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.739871E+09 | 0.226670E+10 |
Report: SpaceGainsMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.344359E+10 | 0.313454E+10 | 0.161799E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.416581E+10 |
February | 0.313522E+10 | 0.283982E+10 | 0.146554E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4108875.54 | 0.286718E+10 |
March | 0.355148E+10 | 0.321092E+10 | 0.165455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34828233.32 | 0.174870E+10 |
April | 0.338259E+10 | 0.304266E+10 | 0.157022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190767E+09 | 0.851871E+09 |
May | 0.349753E+10 | 0.317273E+10 | 0.163627E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.451721E+09 | 0.399075E+09 |
June | 0.343071E+10 | 0.309995E+10 | 0.159764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114440E+10 | 0.128015E+09 |
July | 0.344942E+10 | 0.311545E+10 | 0.160885E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133588E+10 | 0.128127E+09 |
August | 0.355148E+10 | 0.321092E+10 | 0.165455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131531E+10 | 54035702.86 |
September | 0.338259E+10 | 0.304266E+10 | 0.157022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.525547E+09 | 0.264518E+09 |
October | 0.344359E+10 | 0.313454E+10 | 0.161799E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100441E+09 | 0.121899E+10 |
November | 0.331698E+10 | 0.304266E+10 | 0.157022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 617736.26 | 0.190136E+10 |
December | 0.344942E+10 | 0.311545E+10 | 0.160885E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.304573E+10 |
Annual Sum or Average | 0.410346E+11 | 0.371623E+11 | 0.191729E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.510363E+10 | 0.167734E+11 |
Minimum of Months | 0.313522E+10 | 0.283982E+10 | 0.146554E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54035702.86 |
Maximum of Months | 0.355148E+10 | 0.321092E+10 | 0.165455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133588E+10 | 0.416581E+10 |
Report: SpaceGainsMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.161274E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.227248E+10 |
February | 0.156756E+10 | 0.146111E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2281998.24 | 0.155376E+10 |
March | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19329759.42 | 0.941972E+09 |
April | 0.169125E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106202E+09 | 0.454814E+09 |
May | 0.174872E+10 | 0.163243E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.251341E+09 | 0.210019E+09 |
June | 0.171530E+10 | 0.159501E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.635872E+09 | 64688288.39 |
July | 0.172466E+10 | 0.160290E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.742760E+09 | 66892036.07 |
August | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.731137E+09 | 26719583.05 |
September | 0.169125E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.292429E+09 | 0.140317E+09 |
October | 0.172174E+10 | 0.161274E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 55881301.43 | 0.656042E+09 |
November | 0.165844E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 343472.28 | 0.102711E+10 |
December | 0.172466E+10 | 0.160290E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165215E+10 |
Annual Sum or Average | 0.205167E+11 | 0.191205E+11 | 0.958644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.283758E+10 | 0.906696E+10 |
Minimum of Months | 0.156756E+10 | 0.146111E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26719583.05 |
Maximum of Months | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.742760E+09 | 0.227248E+10 |
Report: SpaceGainsMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.161274E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.227038E+10 |
February | 0.156756E+10 | 0.146111E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2281998.73 | 0.155011E+10 |
March | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19330010.74 | 0.935878E+09 |
April | 0.169125E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106236E+09 | 0.450822E+09 |
May | 0.174872E+10 | 0.163243E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.251403E+09 | 0.208896E+09 |
June | 0.171530E+10 | 0.159501E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.635970E+09 | 64307743.46 |
July | 0.172466E+10 | 0.160290E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.742897E+09 | 66613631.80 |
August | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.731241E+09 | 26466075.20 |
September | 0.169125E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.292477E+09 | 0.139975E+09 |
October | 0.172174E+10 | 0.161274E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 55904266.26 | 0.652945E+09 |
November | 0.165844E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 343472.92 | 0.102266E+10 |
December | 0.172466E+10 | 0.160290E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.164923E+10 |
Annual Sum or Average | 0.205167E+11 | 0.191205E+11 | 0.958644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.283808E+10 | 0.903829E+10 |
Minimum of Months | 0.156756E+10 | 0.146111E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26466075.20 |
Maximum of Months | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.742897E+09 | 0.227038E+10 |
Report: SpaceGainsMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.161274E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.226163E+10 |
February | 0.156756E+10 | 0.146111E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2282005.82 | 0.153856E+10 |
March | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19331305.52 | 0.919236E+09 |
April | 0.169125E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106361E+09 | 0.439047E+09 |
May | 0.174872E+10 | 0.163243E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.251566E+09 | 0.204907E+09 |
June | 0.171530E+10 | 0.159501E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.636121E+09 | 63141238.04 |
July | 0.172466E+10 | 0.160290E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.743017E+09 | 65857529.31 |
August | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.731299E+09 | 25878967.58 |
September | 0.169125E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.292557E+09 | 0.138860E+09 |
October | 0.172174E+10 | 0.161274E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 55954546.78 | 0.644500E+09 |
November | 0.165844E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 343477.83 | 0.101097E+10 |
December | 0.172466E+10 | 0.160290E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163947E+10 |
Annual Sum or Average | 0.205167E+11 | 0.191205E+11 | 0.958644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.283883E+10 | 0.895206E+10 |
Minimum of Months | 0.156756E+10 | 0.146111E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25878967.58 |
Maximum of Months | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.743017E+09 | 0.226163E+10 |
Report: SpaceGainsMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.161274E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.283494E+10 |
February | 0.156756E+10 | 0.146111E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2407339.30 | 0.201620E+10 |
March | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20569875.31 | 0.119596E+10 |
April | 0.169125E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109779E+09 | 0.605693E+09 |
May | 0.174872E+10 | 0.163243E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.260840E+09 | 0.322955E+09 |
June | 0.171530E+10 | 0.159501E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.671501E+09 | 0.129557E+09 |
July | 0.172466E+10 | 0.160290E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.778753E+09 | 0.111152E+09 |
August | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.767724E+09 | 57487798.59 |
September | 0.169125E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.302934E+09 | 0.216327E+09 |
October | 0.172174E+10 | 0.161274E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 57930222.84 | 0.882989E+09 |
November | 0.165844E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 357286.27 | 0.134442E+10 |
December | 0.172466E+10 | 0.160290E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.214722E+10 |
Annual Sum or Average | 0.205167E+11 | 0.191205E+11 | 0.958644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.297279E+10 | 0.118649E+11 |
Minimum of Months | 0.156756E+10 | 0.146111E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57487798.59 |
Maximum of Months | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.778753E+09 | 0.283494E+10 |
Report: PeakSpaceGainsMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 4050.04 | 01-JAN-13:09 | 4621.63 | 01-JAN-10:09 | 1343.25 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 8886.97 | 07-JAN-18:00 |
February | 4050.04 | 03-FEB-13:09 | 4621.63 | 01-FEB-10:09 | 1343.25 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 340.89 | 28-FEB-15:00 | 9043.12 | 11-FEB-18:00 |
March | 4050.04 | 03-MAR-13:09 | 4621.63 | 01-MAR-10:09 | 1343.25 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1152.87 | 30-MAR-16:00 | 5360.18 | 22-MAR-11:10 |
April | 4050.04 | 01-APR-12:09 | 4621.63 | 01-APR-09:09 | 1343.25 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1440.80 | 12-APR-14:00 | 4240.80 | 05-APR-11:05 |
May | 4050.04 | 05-MAY-12:09 | 4621.63 | 01-MAY-09:09 | 1343.25 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1932.04 | 19-MAY-16:00 | 1837.95 | 10-MAY-11:10 |
June | 4050.04 | 02-JUN-12:09 | 4621.63 | 01-JUN-09:09 | 1343.25 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3040.53 | 06-JUN-15:00 | 781.60 | 07-JUN-11:10 |
July | 4050.04 | 01-JUL-12:09 | 4621.63 | 01-JUL-09:09 | 1343.25 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3502.57 | 08-JUL-15:00 | 1533.97 | 28-JUL-17:00 |
August | 4050.04 | 04-AUG-12:09 | 4621.63 | 01-AUG-09:09 | 1343.25 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3186.20 | 01-AUG-17:00 | 327.81 | 31-AUG-17:00 |
September | 4050.04 | 01-SEP-12:09 | 4621.63 | 01-SEP-09:09 | 1343.25 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2205.52 | 07-SEP-15:00 | 2035.80 | 28-SEP-17:00 |
October | 4050.04 | 01-OCT-12:09 | 4621.63 | 01-OCT-09:09 | 1343.25 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1728.24 | 10-OCT-16:00 | 3804.56 | 25-OCT-11:10 |
November | 4050.04 | 03-NOV-12:09 | 4621.63 | 01-NOV-09:09 | 1343.25 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 151.55 | 19-NOV-15:00 | 5549.45 | 20-NOV-12:10 |
December | 4050.04 | 01-DEC-13:09 | 4621.63 | 01-DEC-10:09 | 1343.25 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 6436.76 | 17-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 4050.04 | 4621.63 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 327.81 | |||||
Maximum of Months | 4050.04 | 4621.63 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 3502.57 | 9043.12 |
Report: PeakSpaceGainsMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 01-JAN-13:09 | 2827.07 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 4741.61 | 07-JAN-18:00 |
February | 2024.96 | 03-FEB-13:09 | 2827.07 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 180.69 | 28-FEB-15:00 | 4803.70 | 11-FEB-18:00 |
March | 2024.96 | 03-MAR-13:09 | 2827.07 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 620.97 | 30-MAR-16:00 | 2880.54 | 22-MAR-11:10 |
April | 2024.96 | 01-APR-12:09 | 2827.07 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 789.32 | 12-APR-14:00 | 2394.14 | 05-APR-11:05 |
May | 2024.96 | 05-MAY-12:09 | 2827.07 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1050.37 | 19-MAY-16:00 | 1075.58 | 10-MAY-11:10 |
June | 2024.96 | 02-JUN-12:09 | 2827.07 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1630.28 | 06-JUN-15:00 | 422.30 | 07-JUN-11:10 |
July | 2024.96 | 01-JUL-12:09 | 2827.07 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1932.95 | 08-JUL-15:00 | 826.15 | 28-JUL-17:00 |
August | 2024.96 | 04-AUG-12:09 | 2827.07 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1724.10 | 01-AUG-17:00 | 177.38 | 31-AUG-17:00 |
September | 2024.96 | 01-SEP-12:09 | 2827.07 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1205.34 | 07-SEP-15:00 | 1101.59 | 28-SEP-17:00 |
October | 2024.96 | 01-OCT-12:09 | 2827.07 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 946.77 | 10-OCT-16:00 | 2138.80 | 25-OCT-11:10 |
November | 2024.96 | 03-NOV-12:09 | 2827.07 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 81.26 | 19-NOV-15:00 | 2981.02 | 20-NOV-12:10 |
December | 2024.96 | 01-DEC-13:09 | 2827.07 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 3499.39 | 17-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 2827.07 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 177.38 | |||||
Maximum of Months | 2024.96 | 2827.07 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1932.95 | 4803.70 |
Report: PeakSpaceGainsMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 2555.22 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 4741.61 | 07-JAN-18:00 |
February | 2024.96 | 04-FEB-13:09 | 2555.22 | 01-FEB-09:09 | 671.63 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 180.69 | 28-FEB-15:00 | 4803.70 | 11-FEB-18:00 |
March | 2024.96 | 04-MAR-13:09 | 2555.22 | 01-MAR-09:09 | 671.63 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 620.97 | 30-MAR-16:00 | 2880.54 | 22-MAR-11:10 |
April | 2024.96 | 01-APR-12:09 | 2555.22 | 01-APR-08:09 | 671.63 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 789.32 | 12-APR-14:00 | 2386.82 | 05-APR-11:05 |
May | 2024.96 | 06-MAY-12:09 | 2555.22 | 01-MAY-08:09 | 671.63 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1050.36 | 19-MAY-16:00 | 1074.78 | 10-MAY-11:10 |
June | 2024.96 | 03-JUN-12:09 | 2555.22 | 01-JUN-08:09 | 671.63 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1630.31 | 06-JUN-15:00 | 422.30 | 07-JUN-11:10 |
July | 2024.96 | 01-JUL-12:09 | 2555.22 | 01-JUL-08:09 | 671.63 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1932.95 | 08-JUL-15:00 | 826.15 | 28-JUL-17:00 |
August | 2024.96 | 05-AUG-12:09 | 2555.22 | 01-AUG-08:09 | 671.63 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1724.10 | 01-AUG-17:00 | 177.38 | 31-AUG-17:00 |
September | 2024.96 | 02-SEP-12:09 | 2555.22 | 01-SEP-08:09 | 671.63 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1205.15 | 07-SEP-15:00 | 1101.60 | 28-SEP-17:00 |
October | 2024.96 | 07-OCT-12:09 | 2555.22 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 946.76 | 10-OCT-16:00 | 2111.73 | 25-OCT-11:10 |
November | 2024.96 | 04-NOV-12:09 | 2555.22 | 01-NOV-08:09 | 671.63 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 81.26 | 19-NOV-15:00 | 2975.51 | 20-NOV-12:10 |
December | 2024.96 | 02-DEC-13:09 | 2555.22 | 01-DEC-09:09 | 671.63 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 3499.39 | 17-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 2555.22 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 177.38 | |||||
Maximum of Months | 2024.96 | 2555.22 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1932.95 | 4803.70 |
Report: PeakSpaceGainsMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 2555.22 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 4741.61 | 07-JAN-18:00 |
February | 2024.96 | 04-FEB-13:09 | 2555.22 | 01-FEB-09:09 | 671.63 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 180.69 | 28-FEB-15:00 | 4803.70 | 11-FEB-18:00 |
March | 2024.96 | 04-MAR-13:09 | 2555.22 | 01-MAR-09:09 | 671.63 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 620.97 | 30-MAR-16:00 | 2880.54 | 22-MAR-11:10 |
April | 2024.96 | 01-APR-12:09 | 2555.22 | 01-APR-08:09 | 671.63 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 789.32 | 12-APR-14:00 | 2373.35 | 05-APR-11:05 |
May | 2024.96 | 06-MAY-12:09 | 2555.22 | 01-MAY-08:09 | 671.63 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1050.36 | 19-MAY-16:00 | 1073.17 | 10-MAY-11:10 |
June | 2024.96 | 03-JUN-12:09 | 2555.22 | 01-JUN-08:09 | 671.63 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1630.32 | 06-JUN-15:00 | 422.30 | 07-JUN-11:10 |
July | 2024.96 | 01-JUL-12:09 | 2555.22 | 01-JUL-08:09 | 671.63 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1932.95 | 08-JUL-15:00 | 826.15 | 28-JUL-17:00 |
August | 2024.96 | 05-AUG-12:09 | 2555.22 | 01-AUG-08:09 | 671.63 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1724.10 | 01-AUG-17:00 | 177.38 | 31-AUG-17:00 |
September | 2024.96 | 02-SEP-12:09 | 2555.22 | 01-SEP-08:09 | 671.63 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1205.16 | 07-SEP-15:00 | 1101.60 | 28-SEP-17:00 |
October | 2024.96 | 07-OCT-12:09 | 2555.22 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 946.76 | 10-OCT-16:00 | 2095.68 | 25-OCT-11:10 |
November | 2024.96 | 04-NOV-12:09 | 2555.22 | 01-NOV-08:09 | 671.63 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 81.26 | 19-NOV-15:00 | 2975.51 | 20-NOV-12:10 |
December | 2024.96 | 02-DEC-13:09 | 2555.22 | 01-DEC-09:09 | 671.63 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 3499.39 | 17-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 2555.22 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 177.38 | |||||
Maximum of Months | 2024.96 | 2555.22 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1932.95 | 4803.70 |
Report: PeakSpaceGainsMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 2555.22 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 4741.61 | 07-JAN-18:00 |
February | 2024.96 | 04-FEB-13:09 | 2555.22 | 01-FEB-09:09 | 671.63 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 180.69 | 28-FEB-15:00 | 4803.70 | 11-FEB-18:00 |
March | 2024.96 | 04-MAR-13:09 | 2555.22 | 01-MAR-09:09 | 671.63 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 620.96 | 30-MAR-16:00 | 2880.54 | 22-MAR-11:10 |
April | 2024.96 | 01-APR-12:09 | 2555.22 | 01-APR-08:09 | 671.63 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 789.32 | 12-APR-14:00 | 2336.11 | 05-APR-11:05 |
May | 2024.96 | 06-MAY-12:09 | 2555.22 | 01-MAY-08:09 | 671.63 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1050.36 | 19-MAY-16:00 | 1066.01 | 10-MAY-11:10 |
June | 2024.96 | 03-JUN-12:09 | 2555.22 | 01-JUN-08:09 | 671.63 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1630.32 | 06-JUN-15:00 | 422.29 | 07-JUN-11:10 |
July | 2024.96 | 01-JUL-12:09 | 2555.22 | 01-JUL-08:09 | 671.63 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1932.95 | 08-JUL-15:00 | 826.23 | 28-JUL-17:00 |
August | 2024.96 | 05-AUG-12:09 | 2555.22 | 01-AUG-08:09 | 671.63 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1724.10 | 01-AUG-17:00 | 177.38 | 31-AUG-17:00 |
September | 2024.96 | 02-SEP-12:09 | 2555.22 | 01-SEP-08:09 | 671.63 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1205.17 | 07-SEP-15:00 | 1101.60 | 28-SEP-17:00 |
October | 2024.96 | 07-OCT-12:09 | 2555.22 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 946.75 | 10-OCT-16:00 | 2065.38 | 25-OCT-11:10 |
November | 2024.96 | 04-NOV-12:09 | 2555.22 | 01-NOV-08:09 | 671.63 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 81.26 | 19-NOV-15:00 | 2975.51 | 20-NOV-12:10 |
December | 2024.96 | 02-DEC-13:09 | 2555.22 | 01-DEC-09:09 | 671.63 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 3499.39 | 17-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 2555.22 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 177.38 | |||||
Maximum of Months | 2024.96 | 2555.22 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1932.95 | 4803.70 |
Report: PeakSpaceGainsMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 5400.05 | 07-JAN-15:09 | 2726.96 | 01-JAN-11:09 | 1343.25 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 8548.36 | 07-JAN-18:00 |
February | 5400.05 | 04-FEB-15:09 | 2726.96 | 01-FEB-10:09 | 1343.25 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 326.02 | 28-FEB-15:00 | 8665.12 | 11-FEB-18:00 |
March | 5400.05 | 04-MAR-15:09 | 2726.96 | 01-MAR-10:09 | 1343.25 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1118.13 | 30-MAR-16:00 | 5188.45 | 22-MAR-11:10 |
April | 5400.05 | 01-APR-14:09 | 2726.96 | 01-APR-09:09 | 1343.25 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1418.30 | 12-APR-14:00 | 4076.56 | 05-APR-11:05 |
May | 5400.05 | 06-MAY-14:09 | 2726.96 | 01-MAY-09:09 | 1343.25 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1889.18 | 19-MAY-16:00 | 1868.63 | 10-MAY-11:10 |
June | 5400.05 | 03-JUN-14:09 | 2726.96 | 01-JUN-09:09 | 1343.25 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2937.16 | 06-JUN-15:00 | 760.13 | 07-JUN-11:10 |
July | 5400.05 | 01-JUL-14:09 | 2726.96 | 01-JUL-09:09 | 1343.25 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3470.21 | 08-JUL-15:00 | 1487.76 | 28-JUL-17:00 |
August | 5400.05 | 05-AUG-14:09 | 2726.96 | 01-AUG-09:09 | 1343.25 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3102.80 | 01-AUG-17:00 | 319.23 | 31-AUG-17:00 |
September | 5400.05 | 02-SEP-14:09 | 2726.96 | 01-SEP-09:09 | 1343.25 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2166.53 | 07-SEP-15:00 | 1982.49 | 28-SEP-17:00 |
October | 5400.05 | 07-OCT-14:09 | 2726.96 | 01-OCT-10:09 | 1343.25 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1701.25 | 10-OCT-16:00 | 3676.61 | 25-OCT-11:10 |
November | 5400.05 | 04-NOV-14:09 | 2726.96 | 01-NOV-09:09 | 1343.25 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 146.40 | 19-NOV-15:00 | 5361.03 | 20-NOV-12:10 |
December | 5400.05 | 02-DEC-15:09 | 2726.96 | 01-DEC-10:09 | 1343.25 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 6294.04 | 17-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 5400.05 | 2726.96 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 319.23 | |||||
Maximum of Months | 5400.05 | 2726.96 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 3470.21 | 8665.12 |
Report: PeakSpaceGainsMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1404.46 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 4741.61 | 07-JAN-18:00 |
February | 2699.95 | 04-FEB-15:09 | 1404.46 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 180.69 | 28-FEB-15:00 | 4803.70 | 11-FEB-18:00 |
March | 2699.95 | 04-MAR-15:09 | 1404.46 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 620.94 | 30-MAR-16:00 | 2880.54 | 22-MAR-11:10 |
April | 2699.95 | 01-APR-14:09 | 1404.46 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 789.30 | 12-APR-14:00 | 2255.13 | 05-APR-11:05 |
May | 2699.95 | 06-MAY-14:09 | 1404.46 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1050.35 | 19-MAY-16:00 | 1028.68 | 10-MAY-11:10 |
June | 2699.95 | 03-JUN-14:09 | 1404.46 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1630.19 | 06-JUN-15:00 | 422.29 | 07-JUN-11:10 |
July | 2699.95 | 01-JUL-14:09 | 1404.46 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1932.95 | 08-JUL-15:00 | 826.19 | 28-JUL-17:00 |
August | 2699.95 | 05-AUG-14:09 | 1404.46 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1724.10 | 01-AUG-17:00 | 177.38 | 31-AUG-17:00 |
September | 2699.95 | 02-SEP-14:09 | 1404.46 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1205.34 | 07-SEP-15:00 | 1101.60 | 28-SEP-17:00 |
October | 2699.95 | 07-OCT-14:09 | 1404.46 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 946.77 | 10-OCT-16:00 | 2040.89 | 25-OCT-11:10 |
November | 2699.95 | 04-NOV-14:09 | 1404.46 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 81.26 | 19-NOV-15:00 | 2975.51 | 20-NOV-12:10 |
December | 2699.95 | 02-DEC-15:09 | 1404.46 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 3499.39 | 17-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 177.38 | |||||
Maximum of Months | 2699.95 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1932.95 | 4803.70 |
Report: PeakSpaceGainsMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1404.46 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 4741.61 | 07-JAN-18:00 |
February | 2699.95 | 04-FEB-15:09 | 1404.46 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 180.69 | 28-FEB-15:00 | 4803.70 | 11-FEB-18:00 |
March | 2699.95 | 04-MAR-15:09 | 1404.46 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 620.94 | 30-MAR-16:00 | 2880.54 | 22-MAR-11:10 |
April | 2699.95 | 01-APR-14:09 | 1404.46 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 789.30 | 12-APR-14:00 | 2241.24 | 05-APR-11:05 |
May | 2699.95 | 06-MAY-14:09 | 1404.46 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1050.35 | 19-MAY-16:00 | 1020.01 | 10-MAY-11:10 |
June | 2699.95 | 03-JUN-14:09 | 1404.46 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1630.19 | 06-JUN-15:00 | 422.29 | 07-JUN-11:10 |
July | 2699.95 | 01-JUL-14:09 | 1404.46 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1932.95 | 08-JUL-15:00 | 826.19 | 28-JUL-17:00 |
August | 2699.95 | 05-AUG-14:09 | 1404.46 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1724.10 | 01-AUG-17:00 | 177.38 | 31-AUG-17:00 |
September | 2699.95 | 02-SEP-14:09 | 1404.46 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1205.34 | 07-SEP-15:00 | 1101.60 | 28-SEP-17:00 |
October | 2699.95 | 07-OCT-14:09 | 1404.46 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 946.77 | 10-OCT-16:00 | 2039.76 | 25-OCT-11:10 |
November | 2699.95 | 04-NOV-14:09 | 1404.46 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 81.26 | 19-NOV-15:00 | 2975.51 | 20-NOV-12:10 |
December | 2699.95 | 02-DEC-15:09 | 1404.46 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 3499.39 | 17-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 177.38 | |||||
Maximum of Months | 2699.95 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1932.95 | 4803.70 |
Report: PeakSpaceGainsMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1404.46 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 4741.61 | 07-JAN-18:00 |
February | 2699.95 | 04-FEB-15:09 | 1404.46 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 180.69 | 28-FEB-15:00 | 4803.70 | 11-FEB-18:00 |
March | 2699.95 | 04-MAR-15:09 | 1404.46 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 621.07 | 30-MAR-16:00 | 2880.54 | 22-MAR-11:10 |
April | 2699.95 | 01-APR-14:09 | 1404.46 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 789.30 | 12-APR-14:00 | 2238.47 | 05-APR-11:05 |
May | 2699.95 | 06-MAY-14:09 | 1404.46 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1050.35 | 19-MAY-16:00 | 992.17 | 10-MAY-11:10 |
June | 2699.95 | 03-JUN-14:09 | 1404.46 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1630.20 | 06-JUN-15:00 | 422.29 | 07-JUN-11:10 |
July | 2699.95 | 01-JUL-14:09 | 1404.46 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1932.95 | 08-JUL-15:00 | 826.17 | 28-JUL-17:00 |
August | 2699.95 | 05-AUG-14:09 | 1404.46 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1724.10 | 01-AUG-17:00 | 177.38 | 31-AUG-17:00 |
September | 2699.95 | 02-SEP-14:09 | 1404.46 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1205.34 | 07-SEP-15:00 | 1101.60 | 28-SEP-17:00 |
October | 2699.95 | 07-OCT-14:09 | 1404.46 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 946.76 | 10-OCT-16:00 | 2039.18 | 25-OCT-11:10 |
November | 2699.95 | 04-NOV-14:09 | 1404.46 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 81.26 | 19-NOV-15:00 | 2975.51 | 20-NOV-12:10 |
December | 2699.95 | 02-DEC-15:09 | 1404.46 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 3499.39 | 17-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 177.38 | |||||
Maximum of Months | 2699.95 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1932.95 | 4803.70 |
Report: PeakSpaceGainsMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1404.46 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 5080.22 | 07-JAN-18:00 |
February | 2699.95 | 04-FEB-15:09 | 1404.46 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 195.56 | 28-FEB-15:00 | 5181.70 | 11-FEB-18:00 |
March | 2699.95 | 04-MAR-15:09 | 1404.46 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 655.78 | 30-MAR-16:00 | 3052.26 | 22-MAR-11:10 |
April | 2699.95 | 01-APR-14:09 | 1404.46 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 811.78 | 12-APR-14:00 | 2434.73 | 05-APR-11:05 |
May | 2699.95 | 06-MAY-14:09 | 1404.46 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1093.18 | 19-MAY-16:00 | 1031.06 | 10-MAY-11:10 |
June | 2699.95 | 03-JUN-14:09 | 1404.46 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1733.43 | 06-JUN-15:00 | 471.51 | 07-JUN-07:00 |
July | 2699.95 | 01-JUL-14:09 | 1404.46 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1965.31 | 08-JUL-15:00 | 872.23 | 28-JUL-17:00 |
August | 2699.95 | 05-AUG-14:09 | 1404.46 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1807.51 | 01-AUG-17:00 | 195.15 | 25-AUG-05:00 |
September | 2699.95 | 02-SEP-14:09 | 1404.46 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1244.32 | 07-SEP-15:00 | 1154.91 | 28-SEP-17:00 |
October | 2699.95 | 07-OCT-14:09 | 1404.46 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 973.70 | 10-OCT-16:00 | 2168.30 | 25-OCT-11:10 |
November | 2699.95 | 04-NOV-14:09 | 1404.46 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 86.42 | 19-NOV-15:00 | 3163.92 | 20-NOV-12:10 |
December | 2699.95 | 02-DEC-15:09 | 1404.46 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 3642.11 | 17-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 195.15 | |||||
Maximum of Months | 2699.95 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1965.31 | 5181.70 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 10607.70 | 27-JAN-00:02 | 1687.52 | 1216.15 | 3731.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 295.81 |
February | 11154.00 | 03-FEB-00:02 | 1687.52 | 1216.15 | 3731.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 488.89 |
March | 10163.50 | 30-MAR-16:10 | 3375.03 | 4621.63 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 1098.33 | 0.00 |
April | 10219.49 | 17-APR-16:20 | 3375.03 | 4621.63 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 1345.13 | 0.00 |
May | 11911.61 | 19-MAY-17:00 | 3375.03 | 4621.63 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 1889.64 | 0.00 |
June | 30765.95 | 15-JUN-07:02 | 1687.52 | 375.00 | 373.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.69 |
July | 31016.02 | 17-JUL-07:02 | 2025.02 | 450.00 | 447.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.54 |
August | 30276.54 | 14-AUG-07:02 | 2025.02 | 450.00 | 447.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.05 |
September | 31805.24 | 16-SEP-07:03 | 0.00 | 300.00 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.88 |
October | 25450.65 | 19-OCT-07:03 | 1350.01 | 300.00 | 298.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 222.94 |
November | 9198.23 | 05-NOV-16:07 | 12150.11 | 13864.89 | 4029.75 | 0.00 | 0.00 | 0.00 | 0.00 | 38.86 | 0.00 |
December | 7959.70 | 01-DEC-00:03 | 1012.51 | 729.69 | 2238.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 433.77 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 7959.70 | 0.00 | 300.00 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 31805.24 | 12150.11 | 13864.89 | 4029.75 | 0.00 | 0.00 | 0.00 | 0.00 | 1889.64 | 488.89 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3854.10 | 12-JAN-10:23 | 1012.48 | 8481.20 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 497.50 |
February | 16706.01 | 26-FEB-19:49 | 13499.74 | 28270.68 | 6716.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.54 |
March | 16736.11 | 26-MAR-17:07 | 20249.61 | 28270.68 | 6716.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.00 |
April | 16652.48 | 08-APR-20:02 | 10124.81 | 28270.68 | 6716.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.32 |
May | 15577.15 | 13-MAY-20:36 | 5062.40 | 14135.34 | 3358.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.47 |
June | 17948.13 | 15-JUN-07:02 | 843.73 | 187.50 | 186.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.31 |
July | 18246.02 | 17-JUL-07:02 | 1012.48 | 225.00 | 223.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.45 |
August | 17943.51 | 14-AUG-07:02 | 1012.48 | 225.00 | 223.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.96 |
September | 17460.62 | 10-SEP-07:02 | 843.73 | 187.50 | 186.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.88 |
October | 17249.98 | 11-OCT-20:50 | 3037.44 | 8481.20 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.34 |
November | 11505.47 | 04-NOV-18:24 | 8437.34 | 14135.34 | 3358.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.16 |
December | 3673.04 | 15-DEC-09:03 | 506.24 | 112.50 | 1119.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 505.33 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3673.04 | 506.24 | 112.50 | 186.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.47 | |
Maximum of Months | 18246.02 | 20249.61 | 28270.68 | 6716.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 505.33 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3821.87 | 03-JAN-11:43 | 1012.48 | 7665.65 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 505.07 |
February | 4686.33 | 01-FEB-08:61 | 1687.47 | 375.00 | 3731.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 642.28 |
March | 5341.74 | 30-MAR-16:10 | 1687.47 | 2555.22 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 591.82 | 0.00 |
April | 5421.23 | 17-APR-16:10 | 1687.47 | 2555.22 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 758.68 | 0.00 |
May | 9112.80 | 19-MAY-06:03 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.29 |
June | 16375.12 | 15-JUN-06:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.54 |
July | 16715.16 | 25-JUL-06:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.29 |
August | 17308.93 | 26-AUG-06:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.65 |
September | 17054.35 | 16-SEP-06:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.70 |
October | 13752.00 | 18-OCT-06:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.46 |
November | 4113.34 | 05-NOV-14:00 | 1012.48 | 2555.22 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.17 |
December | 4019.03 | 15-DEC-08:61 | 1181.23 | 262.50 | 2611.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 521.93 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3821.87 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17308.93 | 1687.47 | 7665.65 | 3731.25 | 0.00 | 0.00 | 0.00 | 0.00 | 758.68 | 642.28 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4735.09 | 14-JAN-10:53 | 1349.97 | 10220.87 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 573.14 |
February | 4604.56 | 02-FEB-09:23 | 1349.97 | 10220.87 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 650.55 |
March | 5253.91 | 30-MAR-16:10 | 1687.47 | 2555.22 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 591.82 | 0.00 |
April | 5393.45 | 17-APR-16:10 | 1687.47 | 2555.22 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 758.69 | 0.00 |
May | 9129.12 | 19-MAY-06:03 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.29 |
June | 16706.88 | 05-JUN-06:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.88 |
July | 16796.55 | 25-JUL-06:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.39 |
August | 17380.14 | 26-AUG-06:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.71 |
September | 17096.54 | 16-SEP-06:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.71 |
October | 13754.10 | 18-OCT-06:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.38 |
November | 4001.59 | 05-NOV-14:00 | 1012.48 | 2555.22 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.17 |
December | 3972.46 | 15-DEC-08:61 | 1181.23 | 262.50 | 2611.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 516.73 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3972.46 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17380.14 | 1687.47 | 10220.87 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 758.69 | 650.55 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4701.08 | 27-JAN-11:02 | 1349.97 | 10220.87 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 621.92 |
February | 4917.89 | 03-FEB-11:23 | 1349.97 | 10220.87 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 659.92 |
March | 5019.13 | 30-MAR-16:10 | 1687.47 | 2555.22 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 591.81 | 0.00 |
April | 5222.74 | 17-APR-16:10 | 1687.47 | 2555.22 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 758.68 | 0.00 |
May | 7731.08 | 19-MAY-06:03 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.29 |
June | 16166.45 | 15-JUN-06:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.21 |
July | 16541.48 | 25-JUL-06:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.06 |
August | 16319.82 | 26-AUG-06:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.56 |
September | 16852.53 | 16-SEP-06:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.43 |
October | 13208.76 | 19-OCT-06:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.60 |
November | 3858.85 | 14-NOV-08:62 | 1012.48 | 225.00 | 2238.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 449.68 |
December | 3905.83 | 15-DEC-08:61 | 1181.23 | 262.50 | 2611.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 508.29 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3858.85 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16852.53 | 1687.47 | 10220.87 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 758.68 | 659.92 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 8385.27 | 13-JAN-19:23 | 7020.07 | 10907.84 | 5373.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 990.15 |
February | 10003.34 | 02-FEB-19:12 | 7020.07 | 10907.84 | 5373.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1166.87 |
March | 8454.33 | 30-MAR-15:00 | 4657.54 | 2726.96 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 1114.78 | 0.00 |
April | 9171.18 | 17-APR-15:00 | 4657.54 | 2726.96 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 1399.70 | 0.00 |
May | 10649.24 | 30-MAY-15:00 | 4657.54 | 2726.96 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 1867.21 | 0.00 |
June | 29280.79 | 15-JUN-07:02 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.86 |
July | 29224.08 | 25-JUL-07:03 | 0.00 | 300.00 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 123.24 |
August | 27509.14 | 03-AUG-07:02 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.39 |
September | 28359.50 | 09-SEP-07:03 | 0.00 | 300.00 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.90 |
October | 21484.65 | 19-OCT-07:03 | 0.00 | 300.00 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 199.15 |
November | 6952.48 | 13-NOV-09:03 | 2227.52 | 225.00 | 2238.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 826.31 |
December | 6489.74 | 14-DEC-09:03 | 2227.52 | 225.00 | 2238.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 737.67 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 6489.74 | 0.00 | 225.00 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 29280.79 | 7020.07 | 10907.84 | 5373.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1867.21 | 1166.87 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3074.41 | 13-JAN-11:03 | 4353.67 | 4213.39 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 418.53 |
February | 4677.48 | 11-FEB-11:43 | 7829.85 | 5617.86 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 706.78 |
March | 4345.70 | 30-MAR-15:00 | 2328.71 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 619.26 | 0.00 |
April | 4762.32 | 17-APR-15:00 | 2328.71 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 779.18 | 0.00 |
May | 5554.56 | 30-MAY-15:00 | 2328.71 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1039.12 | 0.00 |
June | 15092.73 | 15-JUN-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.54 |
July | 15029.22 | 18-JUL-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.45 |
August | 14163.75 | 03-AUG-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.57 |
September | 14309.49 | 27-SEP-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.35 |
October | 10231.25 | 19-OCT-07:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.20 |
November | 3521.00 | 05-NOV-15:00 | 2328.71 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.46 | 0.00 |
December | 4039.33 | 17-DEC-11:23 | 1113.73 | 4213.39 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 567.20 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3074.41 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15092.73 | 7829.85 | 5617.86 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 1039.12 | 706.78 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4076.09 | 13-JAN-19:03 | 3509.93 | 5617.86 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 529.86 |
February | 3611.43 | 04-FEB-11:33 | 5872.39 | 4213.39 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 464.57 |
March | 4256.94 | 30-MAR-15:00 | 2328.71 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 619.26 | 0.00 |
April | 4686.33 | 17-APR-15:00 | 2328.71 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 779.18 | 0.00 |
May | 5494.45 | 30-MAY-15:00 | 2328.71 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1039.12 | 0.00 |
June | 14986.61 | 15-JUN-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.87 |
July | 14932.82 | 18-JUL-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.00 |
August | 14070.33 | 03-AUG-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.06 |
September | 14212.35 | 27-SEP-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.86 |
October | 9841.16 | 19-OCT-07:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.11 |
November | 3446.49 | 05-NOV-15:00 | 2328.71 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.46 | 0.00 |
December | 3173.88 | 14-DEC-09:03 | 1113.73 | 112.50 | 1119.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 400.02 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3173.88 | 0.00 | 112.50 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14986.61 | 5872.39 | 5617.86 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 1039.12 | 529.86 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3328.54 | 04-JAN-18:33 | 3442.43 | 4213.39 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 439.40 |
February | 2274.98 | 28-FEB-15:30 | 2328.71 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 41.15 | 0.00 |
March | 4067.48 | 30-MAR-15:00 | 2328.71 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 619.28 | 0.00 |
April | 4498.30 | 17-APR-15:00 | 2328.71 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 779.18 | 0.00 |
May | 5385.20 | 30-MAY-15:00 | 2328.71 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1039.11 | 0.00 |
June | 14922.95 | 15-JUN-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.79 |
July | 14887.58 | 18-JUL-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.48 |
August | 14033.22 | 03-AUG-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.86 |
September | 14157.36 | 27-SEP-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.09 |
October | 8675.38 | 19-OCT-07:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.87 |
November | 3280.58 | 05-NOV-15:00 | 2328.71 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.46 | 0.00 |
December | 3341.34 | 01-DEC-20:43 | 1113.73 | 2217.58 | 1119.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.26 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2274.98 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14922.95 | 3442.43 | 4213.39 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 1039.11 | 439.40 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1090.47 | 20-JAN-19:30 | 877.48 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 206.52 |
February | 2167.72 | 28-FEB-15:30 | 2328.71 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 44.00 | 0.00 |
March | 4178.83 | 30-MAR-14:50 | 2328.71 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 650.38 | 0.00 |
April | 4606.54 | 17-APR-14:30 | 2328.71 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 790.11 | 0.00 |
May | 5842.49 | 30-MAY-14:30 | 2328.71 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1072.02 | 0.00 |
June | 13527.81 | 14-JUN-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.07 |
July | 15458.83 | 17-JUL-07:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.25 |
August | 14552.40 | 10-AUG-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.65 | 0.00 |
September | 14453.71 | 27-SEP-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.24 |
October | 6323.57 | 10-OCT-14:10 | 2328.71 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 866.63 | 0.00 |
November | 3325.94 | 21-NOV-19:03 | 2632.45 | 4213.39 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 526.27 |
December | 2904.47 | 08-DEC-19:53 | 2632.45 | 4213.39 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 511.82 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1090.47 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15458.83 | 2632.45 | 4213.39 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 1072.02 | 526.27 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.628890E+11 | 55579.06 | 09-JAN-18:49 | 0.851544E+11 | 183340.40 | 09-JAN-08:09 |
February | 0.565359E+11 | 53844.92 | 26-FEB-15:20 | 0.485600E+11 | 205195.73 | 12-FEB-09:09 |
March | 0.635530E+11 | 67148.19 | 30-MAR-14:20 | 0.860084E+10 | 87860.76 | 19-MAR-08:09 |
April | 0.658542E+11 | 66108.66 | 17-APR-13:39 | 0.130212E+10 | 66797.84 | 07-APR-07:10 |
May | 0.774061E+11 | 74109.97 | 30-MAY-14:00 | 3476070.30 | 1545.13 | 11-MAY-07:10 |
June | 0.905459E+11 | 83481.31 | 27-JUN-13:09 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 0.982130E+11 | 94769.24 | 08-JUL-15:20 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.103478E+12 | 91615.12 | 19-AUG-12:00 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.831917E+11 | 85585.79 | 06-SEP-13:09 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 0.692257E+11 | 74440.04 | 10-OCT-15:09 | 0.145942E+10 | 50304.34 | 26-OCT-08:09 |
November | 0.605115E+11 | 58974.14 | 05-NOV-14:00 | 0.934893E+10 | 104079.67 | 22-NOV-08:09 |
December | 0.620720E+11 | 51363.21 | 12-DEC-14:00 | 0.385859E+11 | 139214.88 | 18-DEC-08:09 |
Annual Sum or Average | 0.893476E+12 | 0.193015E+12 | ||||
Minimum of Months | 0.565359E+11 | 51363.21 | 0.00 | 0.00 | ||
Maximum of Months | 0.103478E+12 | 94769.24 | 0.851544E+11 | 205195.73 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.310073E+11 | 0.631741E+10 | 0.108325E+11 | 0.00 | 0.923000E+10 | 0.00 | 0.00 | 765305.46 | 0.00 | 0.00 | 0.00 | 0.550110E+10 | 0.00 |
February | 0.280657E+11 | 0.527990E+10 | 0.980803E+10 | 0.00 | 0.787207E+10 | 0.00 | 0.00 | 0.543067E+09 | 0.00 | 0.00 | 0.00 | 0.496713E+10 | 0.00 |
March | 0.314703E+11 | 0.522701E+10 | 0.110075E+11 | 0.00 | 0.803718E+10 | 0.00 | 0.00 | 0.235212E+10 | 0.00 | 0.00 | 0.00 | 0.545896E+10 | 0.00 |
April | 0.300741E+11 | 0.444061E+10 | 0.105079E+11 | 0.00 | 0.756357E+10 | 0.00 | 0.00 | 0.811807E+10 | 0.00 | 0.00 | 0.00 | 0.514992E+10 | 0.00 |
May | 0.312330E+11 | 0.405070E+10 | 0.109147E+11 | 0.00 | 0.782828E+10 | 0.00 | 0.00 | 0.181709E+11 | 0.00 | 0.00 | 0.00 | 0.520851E+10 | 0.00 |
June | 0.304143E+11 | 0.368394E+10 | 0.106386E+11 | 0.00 | 0.773476E+10 | 0.00 | 0.00 | 0.331195E+11 | 0.00 | 0.00 | 0.00 | 0.495475E+10 | 0.00 |
July | 0.309042E+11 | 0.389540E+10 | 0.107945E+11 | 0.00 | 0.815900E+10 | 0.00 | 0.00 | 0.394319E+11 | 0.00 | 0.00 | 0.00 | 0.502793E+10 | 0.00 |
August | 0.314595E+11 | 0.434478E+10 | 0.110006E+11 | 0.00 | 0.842362E+10 | 0.00 | 0.00 | 0.431927E+11 | 0.00 | 0.00 | 0.00 | 0.505724E+10 | 0.00 |
September | 0.300847E+11 | 0.479086E+10 | 0.105148E+11 | 0.00 | 0.761407E+10 | 0.00 | 0.00 | 0.252595E+11 | 0.00 | 0.00 | 0.00 | 0.492788E+10 | 0.00 |
October | 0.310073E+11 | 0.559047E+10 | 0.108325E+11 | 0.00 | 0.781834E+10 | 0.00 | 0.00 | 0.879092E+10 | 0.00 | 0.00 | 0.00 | 0.518620E+10 | 0.00 |
November | 0.300409E+11 | 0.597047E+10 | 0.104978E+11 | 0.00 | 0.769707E+10 | 0.00 | 0.00 | 0.116157E+10 | 0.00 | 0.00 | 0.00 | 0.514362E+10 | 0.00 |
December | 0.309156E+11 | 0.646940E+10 | 0.108050E+11 | 0.00 | 0.835730E+10 | 0.00 | 0.00 | 91675093.81 | 0.00 | 0.00 | 0.00 | 0.543302E+10 | 0.00 |
Annual Sum or Average | 0.366677E+12 | 0.600610E+11 | 0.128154E+12 | 0.00 | 0.963353E+11 | 0.00 | 0.00 | 0.180233E+12 | 0.00 | 0.00 | 0.00 | 0.620162E+11 | 0.00 |
Minimum of Months | 0.280657E+11 | 0.368394E+10 | 0.980803E+10 | 0.00 | 0.756357E+10 | 0.00 | 0.00 | 765305.46 | 0.00 | 0.00 | 0.00 | 0.492788E+10 | 0.00 |
Maximum of Months | 0.314703E+11 | 0.646940E+10 | 0.110075E+11 | 0.00 | 0.923000E+10 | 0.00 | 0.00 | 0.431927E+11 | 0.00 | 0.00 | 0.00 | 0.550110E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.851544E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.485600E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.860084E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.130212E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 3476070.30 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.145942E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.934893E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.385859E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.193015E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.851544E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 23459.17 | 01-JAN-11:09 | 5507.06 | 01-JAN-06:10 | 8059.50 | 01-JAN-11:09 | 0.00 | 8667.40 | 09-JAN-08:09 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 23459.17 | 01-FEB-10:09 | 5507.06 | 01-FEB-06:10 | 8059.50 | 01-FEB-10:09 | 0.00 | 9070.86 | 12-FEB-09:09 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 23459.17 | 01-MAR-10:09 | 5507.06 | 01-MAR-06:10 | 8059.50 | 01-MAR-10:09 | 0.00 | 6917.27 | 19-MAR-08:09 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 23459.17 | 01-APR-09:09 | 5507.06 | 01-APR-05:10 | 8059.50 | 01-APR-09:09 | 0.00 | 6530.83 | 07-APR-07:10 | 0.00 | 0.00 | 01-APR-00:10 |
May | 23459.17 | 01-MAY-09:09 | 5507.06 | 01-MAY-05:10 | 8059.50 | 01-MAY-09:09 | 0.00 | 5328.95 | 11-MAY-07:10 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 23459.17 | 01-JUN-09:09 | 5507.06 | 01-JUN-05:10 | 8059.50 | 01-JUN-09:09 | 0.00 | 6814.32 | 26-JUN-07:10 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 23459.17 | 01-JUL-09:09 | 5507.06 | 01-JUL-05:10 | 8059.50 | 01-JUL-09:09 | 0.00 | 8018.77 | 08-JUL-13:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 23459.17 | 01-AUG-09:09 | 5507.06 | 01-AUG-05:10 | 8059.50 | 01-AUG-09:09 | 0.00 | 7484.90 | 19-AUG-13:00 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 23459.17 | 01-SEP-09:09 | 5507.06 | 01-SEP-05:10 | 8059.50 | 01-SEP-09:09 | 0.00 | 6756.25 | 05-SEP-07:10 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 23459.17 | 01-OCT-10:09 | 5507.06 | 01-OCT-05:10 | 8059.50 | 01-OCT-10:09 | 0.00 | 6222.27 | 26-OCT-08:09 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 23459.17 | 01-NOV-09:09 | 5507.06 | 01-NOV-05:10 | 8059.50 | 01-NOV-09:09 | 0.00 | 7216.39 | 22-NOV-08:09 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 23459.17 | 01-DEC-10:09 | 5507.06 | 01-DEC-06:10 | 8059.50 | 01-DEC-10:09 | 0.00 | 7862.15 | 18-DEC-08:09 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||||
Minimum of Months | 23459.17 | 5507.06 | 8059.50 | 0.00 | 5328.95 | 0.00 | 0.00 | |||||
Maximum of Months | 23459.17 | 5507.06 | 8059.50 | 0.00 | 9070.86 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 362.89 | 31-JAN-22:49 | 0.00 | 0.00 | 0.00 | 12560.05 | 09-JAN-15:30 | 0.00 |
February | 12019.87 | 28-FEB-15:09 | 0.00 | 0.00 | 0.00 | 13909.55 | 09-FEB-13:20 | 0.00 |
March | 22598.52 | 30-MAR-14:09 | 0.00 | 0.00 | 0.00 | 9669.05 | 06-MAR-16:10 | 0.00 |
April | 22397.19 | 17-APR-16:10 | 0.00 | 0.00 | 0.00 | 9742.01 | 08-APR-11:00 | 0.00 |
May | 31854.77 | 30-MAY-14:00 | 0.00 | 0.00 | 0.00 | 9693.59 | 02-MAY-12:20 | 0.00 |
June | 41345.90 | 23-JUN-12:00 | 0.00 | 0.00 | 0.00 | 7562.01 | 16-JUN-12:39 | 0.00 |
July | 50874.79 | 08-JUL-13:00 | 0.00 | 0.00 | 0.00 | 7553.01 | 31-JUL-13:09 | 0.00 |
August | 46906.38 | 19-AUG-13:00 | 0.00 | 0.00 | 0.00 | 10099.06 | 31-AUG-13:30 | 0.00 |
September | 41371.77 | 07-SEP-16:10 | 0.00 | 0.00 | 0.00 | 9679.34 | 22-SEP-12:50 | 0.00 |
October | 31685.44 | 10-OCT-16:10 | 0.00 | 0.00 | 0.00 | 7620.19 | 07-OCT-15:09 | 0.00 |
November | 18838.19 | 05-NOV-14:00 | 0.00 | 0.00 | 0.00 | 9692.29 | 09-NOV-14:09 | 0.00 |
December | 8484.92 | 12-DEC-13:00 | 0.00 | 0.00 | 0.00 | 9619.24 | 11-DEC-10:00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 362.89 | 0.00 | 0.00 | 0.00 | 7553.01 | 0.00 | ||
Maximum of Months | 50874.79 | 0.00 | 0.00 | 0.00 | 13909.55 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 55579.06 | 09-JAN-18:49 | 23459.17 | 8059.50 | 5507.06 | 0.00 | 6609.80 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 53844.92 | 26-FEB-15:20 | 23459.17 | 8059.50 | 0.00 | 0.00 | 5299.69 | 0.00 | 0.00 | 11600.50 | 0.00 |
March | 67148.19 | 30-MAR-14:20 | 23459.17 | 8059.50 | 0.00 | 0.00 | 5299.69 | 0.00 | 0.00 | 22514.76 | 0.00 |
April | 66108.66 | 17-APR-13:39 | 23459.17 | 8059.50 | 0.00 | 0.00 | 5299.69 | 0.00 | 0.00 | 21715.36 | 0.00 |
May | 74109.97 | 30-MAY-14:00 | 23459.17 | 8059.50 | 0.00 | 0.00 | 5299.69 | 0.00 | 0.00 | 31854.77 | 0.00 |
June | 83481.31 | 27-JUN-13:09 | 23459.17 | 8059.50 | 0.00 | 0.00 | 6235.17 | 0.00 | 0.00 | 40285.96 | 0.00 |
July | 94769.24 | 08-JUL-15:20 | 23459.17 | 8059.50 | 0.00 | 0.00 | 7775.82 | 0.00 | 0.00 | 50048.23 | 0.00 |
August | 91615.12 | 19-AUG-12:00 | 23459.17 | 8059.50 | 0.00 | 0.00 | 7225.21 | 0.00 | 0.00 | 45317.10 | 0.00 |
September | 85585.79 | 06-SEP-13:09 | 23459.17 | 8059.50 | 0.00 | 0.00 | 6429.67 | 0.00 | 0.00 | 40561.18 | 0.00 |
October | 74440.04 | 10-OCT-15:09 | 23459.17 | 8059.50 | 0.00 | 0.00 | 5299.69 | 0.00 | 0.00 | 30593.63 | 0.00 |
November | 58974.14 | 05-NOV-14:00 | 23459.17 | 8059.50 | 0.00 | 0.00 | 5299.69 | 0.00 | 0.00 | 18838.19 | 0.00 |
December | 51363.21 | 12-DEC-14:00 | 23459.17 | 8059.50 | 0.00 | 0.00 | 5299.69 | 0.00 | 0.00 | 7167.89 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 51363.21 | 23459.17 | 8059.50 | 0.00 | 0.00 | 5299.69 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 94769.24 | 23459.17 | 8059.50 | 5507.06 | 0.00 | 7775.82 | 0.00 | 0.00 | 50048.23 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 183340.40 | 09-JAN-08:09 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 205195.73 | 12-FEB-09:09 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 87860.76 | 19-MAR-08:09 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 66797.84 | 07-APR-07:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 1545.13 | 11-MAY-07:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 50304.34 | 26-OCT-08:09 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 104079.67 | 22-NOV-08:09 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 139214.88 | 18-DEC-08:09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 205195.73 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.50 | 20.50 | 0.33 | 20.49 | 0.00 | 20.49 | 0.00 | 20.49 |
February | 1.17 | 20.40 | 0.50 | 20.37 | 0.00 | 20.37 | 0.00 | 20.37 |
March | 0.17 | 20.52 | 0.00 | 20.52 | 0.00 | 20.52 | 0.00 | 20.52 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.17 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 |
December | 0.67 | 20.45 | 0.00 | 20.45 | 0.00 | 20.45 | 0.00 | 20.45 |
Annual Sum or Average | 3.67 | 20.46 | 0.83 | 20.44 | 0.00 | 20.44 | 0.00 | 20.44 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.50 | 20.52 | 0.50 | 20.52 | 0.00 | 20.52 | 0.00 | 20.52 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.17 | 20.55 | 0.00 | 20.55 | 0.00 | 20.55 | 0.00 | 20.55 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.17 | 20.55 | 0.00 | 20.55 | 0.00 | 20.55 | 0.00 | 20.55 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 20.55 | 0.00 | 20.55 | 0.00 | 20.55 | 0.00 | 20.55 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.17 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.17 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.33 | 20.47 | 0.00 | 20.47 | 0.00 | 20.47 | 0.00 | 20.47 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.33 | 20.47 | 0.00 | 20.47 | 0.00 | 20.47 | 0.00 | 20.47 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.33 | 20.47 | 0.00 | 20.47 | 0.00 | 20.47 | 0.00 | 20.47 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 20.53 | 0.00 | 20.53 | 0.00 | 20.53 | 0.00 | 20.53 |
February | 0.33 | 20.40 | 0.00 | 20.40 | 0.00 | 20.40 | 0.00 | 20.40 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.50 | 20.44 | 0.00 | 20.44 | 0.00 | 20.44 | 0.00 | 20.44 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.33 | 20.53 | 0.00 | 20.53 | 0.00 | 20.53 | 0.00 | 20.53 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.83 | 20.44 | 0.00 | 20.44 | 0.00 | 20.44 | 0.00 | 20.44 |
February | 0.50 | 20.21 | 0.00 | 20.21 | 0.00 | 20.21 | 0.00 | 20.21 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1.33 | 20.35 | 0.00 | 20.35 | 0.00 | 20.35 | 0.00 | 20.35 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.83 | 20.44 | 0.00 | 20.44 | 0.00 | 20.44 | 0.00 | 20.44 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.67 | 20.44 | 0.00 | 20.44 | 0.00 | 20.44 | 0.00 | 20.44 |
February | 0.50 | 20.23 | 0.00 | 20.23 | 0.00 | 20.23 | 0.00 | 20.23 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1.17 | 20.35 | 0.00 | 20.35 | 0.00 | 20.35 | 0.00 | 20.35 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.67 | 20.44 | 0.00 | 20.44 | 0.00 | 20.44 | 0.00 | 20.44 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.00 | 20.45 | 0.00 | 20.45 | 0.00 | 20.45 | 0.00 | 20.45 |
February | 0.50 | 20.20 | 0.00 | 20.20 | 0.00 | 20.20 | 0.00 | 20.20 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1.50 | 20.37 | 0.00 | 20.37 | 0.00 | 20.37 | 0.00 | 20.37 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.00 | 20.45 | 0.00 | 20.45 | 0.00 | 20.45 | 0.00 | 20.45 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.00 | 20.42 | 0.00 | 20.42 | 0.00 | 20.42 | 0.00 | 20.42 |
February | 1.17 | 20.31 | 0.00 | 20.31 | 0.00 | 20.31 | 0.00 | 20.31 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3.17 | 20.38 | 0.00 | 20.38 | 0.00 | 20.38 | 0.00 | 20.38 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.00 | 20.42 | 0.00 | 20.42 | 0.00 | 20.42 | 0.00 | 20.42 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 4.33 | 19.52 | 0.00 | 19.52 | 0.00 | 19.52 | 0.00 | 19.52 |
February | 4.17 | 17.64 | 0.00 | 17.64 | 0.00 | 17.64 | 0.00 | 17.64 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.17 | 20.53 | 0.00 | 20.53 | 0.00 | 20.53 | 0.00 | 20.53 |
December | 1.67 | 20.31 | 0.00 | 20.31 | 0.00 | 20.31 | 0.00 | 20.31 |
Annual Sum or Average | 10.33 | 18.90 | 0.00 | 18.90 | 0.00 | 18.90 | 0.00 | 18.90 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4.33 | 20.53 | 0.00 | 20.53 | 0.00 | 20.53 | 0.00 | 20.53 |
Report: ComfortReportSimple55Monthly
For: LGSTORE1
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 496.00 | 21.22 | 246.33 | 21.17 | 246.33 | 21.15 |
February | 439.67 | 21.74 | 156.17 | 21.56 | 156.17 | 21.45 |
March | 373.33 | 22.25 | 63.67 | 22.39 | 14.83 | 22.35 |
April | 226.50 | 22.87 | 158.67 | 23.25 | 28.83 | 23.26 |
May | 110.67 | 23.66 | 367.50 | 23.83 | 77.33 | 23.83 |
June | 54.33 | 23.87 | 420.00 | 23.89 | 46.67 | 23.89 |
July | 100.50 | 23.89 | 494.00 | 23.89 | 100.50 | 23.89 |
August | 114.33 | 23.89 | 496.83 | 23.89 | 114.33 | 23.89 |
September | 85.00 | 23.86 | 451.33 | 23.88 | 79.83 | 23.88 |
October | 219.67 | 22.72 | 192.00 | 23.26 | 47.50 | 23.32 |
November | 366.17 | 22.31 | 88.33 | 22.54 | 28.50 | 22.55 |
December | 469.83 | 21.29 | 97.50 | 21.30 | 90.50 | 21.29 |
Annual Sum or Average | 3056.00 | 22.19 | 3232.33 | 22.83 | 1031.33 | 22.77 |
Minimum of Months | 54.33 | 21.22 | 63.67 | 21.17 | 14.83 | 21.15 |
Maximum of Months | 496.00 | 23.89 | 496.83 | 23.89 | 246.33 | 23.89 |
Report: ComfortReportSimple55Monthly
For: SMSTORE1
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 496.00 | 21.64 | 103.00 | 21.58 | 103.00 | 21.53 |
February | 408.00 | 22.11 | 61.83 | 22.02 | 58.50 | 21.94 |
March | 345.00 | 22.85 | 60.00 | 23.00 | 0.83 | 22.99 |
April | 156.33 | 23.19 | 158.83 | 23.54 | 5.50 | 23.54 |
May | 55.33 | 23.72 | 338.67 | 23.86 | 28.67 | 23.86 |
June | 19.83 | 23.68 | 406.33 | 23.88 | 9.67 | 23.88 |
July | 59.50 | 23.89 | 488.67 | 23.89 | 59.50 | 23.89 |
August | 50.00 | 23.89 | 494.17 | 23.89 | 50.00 | 23.89 |
September | 40.17 | 23.87 | 431.67 | 23.89 | 39.00 | 23.89 |
October | 163.67 | 23.08 | 184.00 | 23.51 | 31.50 | 23.53 |
November | 319.33 | 22.80 | 88.00 | 23.02 | 13.50 | 23.03 |
December | 462.67 | 21.93 | 40.50 | 22.00 | 22.50 | 22.00 |
Annual Sum or Average | 2575.83 | 22.45 | 2855.67 | 23.12 | 422.17 | 23.09 |
Minimum of Months | 19.83 | 21.64 | 40.50 | 21.58 | 0.83 | 21.53 |
Maximum of Months | 496.00 | 23.89 | 494.17 | 23.89 | 103.00 | 23.89 |
Report: ComfortReportSimple55Monthly
For: SMSTORE2
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 371.00 | 21.29 | 128.67 | 21.25 | 128.67 | 21.22 |
February | 321.00 | 21.80 | 71.67 | 21.68 | 71.67 | 21.59 |
March | 269.50 | 22.35 | 60.17 | 22.61 | 4.17 | 22.59 |
April | 140.00 | 22.93 | 127.50 | 23.47 | 10.83 | 23.49 |
May | 66.17 | 23.75 | 289.33 | 23.98 | 48.50 | 23.98 |
June | 34.33 | 24.45 | 326.00 | 24.13 | 30.00 | 24.16 |
July | 91.67 | 24.40 | 369.00 | 24.15 | 91.67 | 24.20 |
August | 107.83 | 24.40 | 378.83 | 24.16 | 107.83 | 24.20 |
September | 67.00 | 24.17 | 345.33 | 24.06 | 63.83 | 24.08 |
October | 162.00 | 22.82 | 144.17 | 23.39 | 37.33 | 23.45 |
November | 262.17 | 22.38 | 56.83 | 22.63 | 14.50 | 22.65 |
December | 347.67 | 21.40 | 47.67 | 21.47 | 39.00 | 21.48 |
Annual Sum or Average | 2240.33 | 22.33 | 2345.17 | 23.06 | 648.00 | 23.07 |
Minimum of Months | 34.33 | 21.29 | 47.67 | 21.25 | 4.17 | 21.22 |
Maximum of Months | 371.00 | 24.45 | 378.83 | 24.16 | 128.67 | 24.20 |
Report: ComfortReportSimple55Monthly
For: SMSTORE3
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 371.00 | 21.27 | 139.83 | 21.23 | 139.83 | 21.21 |
February | 326.33 | 21.79 | 75.50 | 21.66 | 75.50 | 21.57 |
March | 276.50 | 22.30 | 58.17 | 22.55 | 5.33 | 22.53 |
April | 145.00 | 22.91 | 122.17 | 23.42 | 12.17 | 23.44 |
May | 68.50 | 23.74 | 288.00 | 23.98 | 49.33 | 23.98 |
June | 33.33 | 24.48 | 325.83 | 24.13 | 29.00 | 24.17 |
July | 90.67 | 24.41 | 369.00 | 24.16 | 90.67 | 24.20 |
August | 105.00 | 24.42 | 378.83 | 24.16 | 105.00 | 24.21 |
September | 67.33 | 24.17 | 345.33 | 24.06 | 64.00 | 24.08 |
October | 165.83 | 22.78 | 143.00 | 23.35 | 38.50 | 23.42 |
November | 267.67 | 22.34 | 53.17 | 22.57 | 15.17 | 22.59 |
December | 348.83 | 21.37 | 51.50 | 21.43 | 45.00 | 21.44 |
Annual Sum or Average | 2266.00 | 22.31 | 2350.33 | 23.03 | 669.50 | 23.03 |
Minimum of Months | 33.33 | 21.27 | 51.50 | 21.23 | 5.33 | 21.21 |
Maximum of Months | 371.00 | 24.48 | 378.83 | 24.16 | 139.83 | 24.21 |
Report: ComfortReportSimple55Monthly
For: SMSTORE4
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 371.00 | 21.24 | 155.33 | 21.21 | 155.33 | 21.19 |
February | 328.67 | 21.73 | 90.50 | 21.60 | 90.50 | 21.51 |
March | 285.33 | 22.22 | 52.83 | 22.44 | 7.00 | 22.41 |
April | 158.83 | 22.86 | 110.33 | 23.33 | 12.50 | 23.34 |
May | 75.67 | 23.70 | 283.50 | 23.96 | 51.50 | 23.96 |
June | 40.00 | 24.37 | 324.33 | 24.12 | 35.00 | 24.15 |
July | 95.67 | 24.36 | 369.00 | 24.14 | 95.67 | 24.18 |
August | 116.67 | 24.35 | 378.83 | 24.15 | 116.67 | 24.19 |
September | 77.17 | 24.12 | 343.83 | 24.05 | 72.83 | 24.07 |
October | 172.17 | 22.70 | 140.00 | 23.29 | 39.50 | 23.36 |
November | 282.17 | 22.30 | 50.33 | 22.50 | 17.00 | 22.52 |
December | 351.50 | 21.34 | 60.17 | 21.38 | 55.33 | 21.39 |
Annual Sum or Average | 2354.83 | 22.29 | 2359.00 | 22.98 | 748.83 | 22.98 |
Minimum of Months | 40.00 | 21.24 | 50.33 | 21.21 | 7.00 | 21.19 |
Maximum of Months | 371.00 | 24.37 | 378.83 | 24.15 | 155.33 | 24.19 |
Report: ComfortReportSimple55Monthly
For: LGSTORE2
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.21 | 213.00 | 21.18 | 213.00 | 21.16 |
February | 308.00 | 21.71 | 114.17 | 21.55 | 114.17 | 21.45 |
March | 282.17 | 22.20 | 29.00 | 22.27 | 9.67 | 22.23 |
April | 176.83 | 22.95 | 77.33 | 23.24 | 20.83 | 23.27 |
May | 83.50 | 23.70 | 249.17 | 23.87 | 59.50 | 23.87 |
June | 58.17 | 24.04 | 293.17 | 23.97 | 53.67 | 23.99 |
July | 111.67 | 24.11 | 338.00 | 24.01 | 111.67 | 24.03 |
August | 134.00 | 24.02 | 347.67 | 23.97 | 134.00 | 23.98 |
September | 95.83 | 24.00 | 301.33 | 23.96 | 92.00 | 23.98 |
October | 167.67 | 22.63 | 120.67 | 23.17 | 38.67 | 23.24 |
November | 285.33 | 22.32 | 38.50 | 22.45 | 21.33 | 22.48 |
December | 330.00 | 21.35 | 82.17 | 21.35 | 82.17 | 21.36 |
Annual Sum or Average | 2373.17 | 22.34 | 2204.17 | 22.86 | 950.67 | 22.83 |
Minimum of Months | 58.17 | 21.21 | 29.00 | 21.18 | 9.67 | 21.16 |
Maximum of Months | 340.00 | 24.11 | 347.67 | 24.01 | 213.00 | 24.03 |
Report: ComfortReportSimple55Monthly
For: SMSTORE5
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.21 | 213.00 | 21.17 | 213.00 | 21.16 |
February | 308.00 | 21.69 | 114.83 | 21.54 | 114.83 | 21.44 |
March | 288.83 | 22.20 | 26.17 | 22.24 | 11.17 | 22.21 |
April | 184.83 | 22.96 | 66.67 | 23.20 | 22.17 | 23.23 |
May | 89.00 | 23.70 | 241.00 | 23.87 | 60.33 | 23.87 |
June | 61.17 | 24.01 | 287.33 | 23.97 | 54.83 | 23.98 |
July | 113.83 | 24.10 | 338.00 | 24.01 | 113.83 | 24.03 |
August | 136.17 | 24.00 | 347.67 | 23.97 | 136.17 | 23.97 |
September | 98.50 | 24.00 | 292.17 | 23.96 | 94.00 | 23.98 |
October | 171.83 | 22.65 | 118.17 | 23.16 | 39.00 | 23.24 |
November | 290.00 | 22.32 | 36.33 | 22.43 | 22.50 | 22.46 |
December | 330.50 | 21.35 | 87.17 | 21.35 | 87.17 | 21.35 |
Annual Sum or Average | 2412.67 | 22.35 | 2168.50 | 22.84 | 969.00 | 22.82 |
Minimum of Months | 61.17 | 21.21 | 26.17 | 21.17 | 11.17 | 21.16 |
Maximum of Months | 340.00 | 24.10 | 347.67 | 24.01 | 213.00 | 24.03 |
Report: ComfortReportSimple55Monthly
For: SMSTORE6
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.20 | 220.00 | 21.17 | 220.00 | 21.15 |
February | 308.00 | 21.68 | 118.33 | 21.52 | 118.33 | 21.43 |
March | 292.17 | 22.18 | 24.67 | 22.20 | 12.50 | 22.16 |
April | 191.33 | 22.94 | 63.67 | 23.17 | 23.83 | 23.20 |
May | 92.33 | 23.69 | 237.83 | 23.86 | 61.33 | 23.86 |
June | 63.33 | 24.01 | 286.33 | 23.97 | 56.83 | 23.98 |
July | 114.50 | 24.10 | 338.00 | 24.00 | 114.50 | 24.02 |
August | 137.50 | 24.00 | 347.50 | 23.97 | 137.50 | 23.97 |
September | 99.50 | 24.00 | 291.33 | 23.96 | 94.67 | 23.97 |
October | 176.17 | 22.64 | 117.33 | 23.15 | 39.17 | 23.22 |
November | 293.50 | 22.31 | 35.67 | 22.41 | 23.33 | 22.44 |
December | 332.17 | 21.35 | 93.17 | 21.35 | 93.17 | 21.34 |
Annual Sum or Average | 2440.50 | 22.35 | 2173.83 | 22.83 | 995.17 | 22.80 |
Minimum of Months | 63.33 | 21.20 | 24.67 | 21.17 | 12.50 | 21.15 |
Maximum of Months | 340.00 | 24.10 | 347.50 | 24.00 | 220.00 | 24.02 |
Report: ComfortReportSimple55Monthly
For: SMSTORE7
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.19 | 238.50 | 21.16 | 238.50 | 21.15 |
February | 308.00 | 21.63 | 129.00 | 21.48 | 129.00 | 21.39 |
March | 299.00 | 22.12 | 25.00 | 22.10 | 18.33 | 22.05 |
April | 209.67 | 22.90 | 59.83 | 23.09 | 32.67 | 23.14 |
May | 100.67 | 23.63 | 233.33 | 23.83 | 62.67 | 23.83 |
June | 71.50 | 23.99 | 285.83 | 23.96 | 63.83 | 23.97 |
July | 117.00 | 24.09 | 338.00 | 24.00 | 117.00 | 24.02 |
August | 141.00 | 24.00 | 347.50 | 23.97 | 141.00 | 23.97 |
September | 103.83 | 23.98 | 290.33 | 23.96 | 97.33 | 23.97 |
October | 182.17 | 22.58 | 116.17 | 23.09 | 39.83 | 23.16 |
November | 297.50 | 22.25 | 38.17 | 22.34 | 26.83 | 22.36 |
December | 336.17 | 21.35 | 110.33 | 21.34 | 110.33 | 21.33 |
Annual Sum or Average | 2506.50 | 22.33 | 2212.00 | 22.79 | 1077.33 | 22.76 |
Minimum of Months | 71.50 | 21.19 | 25.00 | 21.16 | 18.33 | 21.15 |
Maximum of Months | 340.00 | 24.09 | 347.50 | 24.00 | 238.50 | 24.02 |
Report: ComfortReportSimple55Monthly
For: SMSTORE8
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.17 | 274.33 | 21.14 | 274.33 | 21.13 |
February | 308.00 | 21.58 | 164.17 | 21.42 | 164.17 | 21.34 |
March | 312.67 | 22.05 | 46.67 | 21.97 | 42.67 | 21.88 |
April | 225.33 | 22.76 | 54.83 | 22.90 | 40.50 | 22.95 |
May | 111.33 | 23.49 | 226.33 | 23.76 | 64.50 | 23.75 |
June | 68.33 | 24.04 | 293.50 | 23.98 | 61.83 | 23.99 |
July | 105.83 | 24.13 | 338.00 | 24.01 | 105.83 | 24.04 |
August | 125.00 | 24.04 | 347.83 | 23.98 | 125.00 | 23.99 |
September | 95.83 | 23.96 | 298.17 | 23.95 | 86.83 | 23.97 |
October | 184.00 | 22.45 | 117.17 | 23.00 | 40.50 | 23.07 |
November | 301.17 | 22.18 | 51.67 | 22.23 | 41.00 | 22.21 |
December | 337.00 | 21.33 | 176.33 | 21.29 | 176.33 | 21.27 |
Annual Sum or Average | 2514.50 | 22.26 | 2389.00 | 22.69 | 1223.50 | 22.62 |
Minimum of Months | 68.33 | 21.17 | 46.67 | 21.14 | 40.50 | 21.13 |
Maximum of Months | 340.00 | 24.13 | 347.83 | 24.01 | 274.33 | 24.04 |
Report: OccupantComfortDataSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 496.00000 | 21.22153 | 24.96605 | -0.5053 | 11.28284 |
February | 448.00000 | 21.78203 | 28.09921 | -0.3260 | 9.49819 |
March | 497.00000 | 22.65438 | 33.89543 | -0.0144 | 7.14117 |
April | 479.00000 | 23.39887 | 42.53668 | 0.24580 | 7.73991 |
May | 496.00000 | 23.83468 | 50.96107 | -0.4420 | 9.59555 |
June | 481.00000 | 23.88630 | 52.88354 | -0.3351 | 7.59368 |
July | 495.00000 | 23.88802 | 59.26149 | -0.2619 | 6.52351 |
August | 497.00000 | 23.89009 | 59.45632 | -0.2414 | 6.30406 |
September | 479.00000 | 23.88087 | 55.18612 | -0.3352 | 7.54194 |
October | 496.00000 | 23.36682 | 45.97457 | 0.29943 | 8.26854 |
November | 480.00000 | 22.67926 | 34.75210 | 0.01687 | 7.35854 |
December | 496.00000 | 21.42533 | 30.14130 | -0.3612 | 9.22734 |
Annual Sum or Average | 5840.00000 | 22.99703 | 43.26357 | -0.1882 | 8.16865 |
Minimum of Months | 448.00000 | 21.22153 | 24.96605 | -0.5053 | 6.30406 |
Maximum of Months | 497.00000 | 23.89009 | 59.45632 | 0.29943 | 11.28284 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 496.00000 | 21.63766 | 26.99346 | -0.3631 | 8.92471 |
February | 448.00000 | 22.26985 | 28.84396 | -0.1786 | 7.95363 |
March | 497.00000 | 23.16251 | 33.32079 | 0.11330 | 6.70098 |
April | 479.00000 | 23.64122 | 40.79915 | 0.30913 | 7.77294 |
May | 496.00000 | 23.86241 | 47.92246 | -0.4378 | 9.32188 |
June | 481.00000 | 23.87330 | 50.41358 | -0.3602 | 7.96288 |
July | 495.00000 | 23.88733 | 56.19324 | -0.2949 | 6.93441 |
August | 497.00000 | 23.89002 | 56.53095 | -0.2792 | 6.74392 |
September | 479.00000 | 23.87729 | 52.42438 | -0.3588 | 7.86876 |
October | 496.00000 | 23.61278 | 44.39368 | 0.34945 | 8.27737 |
November | 480.00000 | 23.15795 | 34.16806 | 0.12962 | 7.02715 |
December | 496.00000 | 22.06228 | 31.68127 | -0.1943 | 7.36901 |
Annual Sum or Average | 5840.00000 | 23.24817 | 42.05295 | -0.1307 | 7.73705 |
Minimum of Months | 448.00000 | 21.63766 | 26.99346 | -0.4378 | 6.70098 |
Maximum of Months | 497.00000 | 23.89002 | 56.53095 | 0.34945 | 9.32188 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 21.28582 | 24.68781 | -0.4546 | 10.15859 |
February | 336.00000 | 21.90132 | 27.18173 | -0.2702 | 8.61437 |
March | 379.00000 | 22.80633 | 33.71750 | 0.04168 | 7.04653 |
April | 360.00000 | 23.57495 | 40.73575 | 0.29113 | 7.99585 |
May | 375.00000 | 23.96188 | 50.23495 | -0.3991 | 8.90010 |
June | 366.00000 | 24.06989 | 52.57872 | -0.2921 | 7.38038 |
July | 369.00000 | 24.09371 | 59.40180 | -0.2158 | 6.51267 |
August | 379.00000 | 24.09234 | 59.37782 | -0.2026 | 6.38906 |
September | 360.00000 | 24.02289 | 54.77696 | -0.3043 | 7.36437 |
October | 371.00000 | 23.47048 | 44.84731 | 0.32120 | 8.48553 |
November | 360.00000 | 22.79825 | 33.36500 | 0.04979 | 7.20622 |
December | 369.00000 | 21.54263 | 29.35716 | -0.3114 | 8.51745 |
Annual Sum or Average | 4395.00000 | 23.14351 | 42.64930 | -0.1454 | 7.87537 |
Minimum of Months | 336.00000 | 21.28582 | 24.68781 | -0.4546 | 6.38906 |
Maximum of Months | 379.00000 | 24.09371 | 59.40180 | 0.32120 | 10.15859 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 21.26816 | 24.73383 | -0.4690 | 10.37779 |
February | 336.00000 | 21.85287 | 27.28907 | -0.2901 | 8.74885 |
March | 379.00000 | 22.74642 | 33.86546 | 0.02204 | 7.08108 |
April | 360.00000 | 23.54965 | 40.83318 | 0.28212 | 7.94419 |
May | 375.00000 | 23.95782 | 50.29059 | -0.4023 | 8.96816 |
June | 366.00000 | 24.06992 | 52.56067 | -0.2914 | 7.37246 |
July | 369.00000 | 24.09397 | 59.35630 | -0.2145 | 6.50274 |
August | 379.00000 | 24.09263 | 59.32469 | -0.2013 | 6.38061 |
September | 360.00000 | 24.02218 | 54.78817 | -0.3046 | 7.36955 |
October | 371.00000 | 23.44083 | 44.97121 | 0.31173 | 8.44953 |
November | 360.00000 | 22.74123 | 33.51654 | 0.03053 | 7.21523 |
December | 369.00000 | 21.50848 | 29.42079 | -0.3282 | 8.70701 |
Annual Sum or Average | 4395.00000 | 23.12068 | 42.70610 | -0.1544 | 7.92053 |
Minimum of Months | 336.00000 | 21.26816 | 24.73383 | -0.4690 | 6.38061 |
Maximum of Months | 379.00000 | 24.09397 | 59.35630 | 0.31173 | 10.37779 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 21.24293 | 24.79973 | -0.4878 | 10.68169 |
February | 336.00000 | 21.78221 | 27.44043 | -0.3179 | 8.97640 |
March | 379.00000 | 22.64232 | 34.12894 | -0.0097 | 7.13034 |
April | 360.00000 | 23.48561 | 41.06326 | 0.26068 | 7.80967 |
May | 375.00000 | 23.94090 | 50.53033 | -0.4153 | 9.23107 |
June | 366.00000 | 24.06444 | 52.83771 | -0.2980 | 7.44220 |
July | 369.00000 | 24.08955 | 59.64610 | -0.2196 | 6.52711 |
August | 379.00000 | 24.08834 | 59.61199 | -0.2062 | 6.39903 |
September | 360.00000 | 24.01515 | 55.05641 | -0.3116 | 7.45751 |
October | 371.00000 | 23.38272 | 45.26099 | 0.29390 | 8.34901 |
November | 360.00000 | 22.64926 | 33.75952 | 0.00175 | 7.22324 |
December | 369.00000 | 21.46311 | 29.51162 | -0.3495 | 8.95082 |
Annual Sum or Average | 4395.00000 | 23.07946 | 42.93140 | -0.1713 | 8.00853 |
Minimum of Months | 336.00000 | 21.24293 | 24.79973 | -0.4878 | 6.39903 |
Maximum of Months | 379.00000 | 24.08955 | 59.64610 | 0.29390 | 10.68169 |
Report: OccupantComfortDataSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.21251 | 26.34688 | -0.5304 | 11.48657 |
February | 308.00000 | 21.70967 | 28.99115 | -0.3667 | 9.54284 |
March | 348.00000 | 22.51481 | 35.79074 | -0.0588 | 7.13169 |
April | 330.00000 | 23.40019 | 42.54490 | 0.22499 | 7.47810 |
May | 344.00000 | 23.87643 | 51.84258 | -0.4532 | 9.82069 |
June | 336.00000 | 23.94919 | 54.22814 | -0.3374 | 7.75188 |
July | 338.00000 | 23.97477 | 61.07838 | -0.2550 | 6.66748 |
August | 348.00000 | 23.95348 | 60.95999 | -0.2457 | 6.51555 |
September | 330.00000 | 23.93409 | 56.53032 | -0.3439 | 7.79451 |
October | 340.00000 | 23.29002 | 46.75488 | 0.26298 | 8.12267 |
November | 330.00000 | 22.53151 | 35.30609 | -0.0450 | 7.24437 |
December | 338.00000 | 21.40998 | 31.11179 | -0.3901 | 9.46869 |
Annual Sum or Average | 4030.00000 | 22.98873 | 44.42028 | -0.2112 | 8.24396 |
Minimum of Months | 308.00000 | 21.21251 | 26.34688 | -0.5304 | 6.51555 |
Maximum of Months | 348.00000 | 23.97477 | 61.07838 | 0.26298 | 11.48657 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.20704 | 26.25846 | -0.5320 | 11.48917 |
February | 308.00000 | 21.69409 | 28.93192 | -0.3738 | 9.57660 |
March | 348.00000 | 22.48874 | 35.76893 | -0.0740 | 7.16515 |
April | 330.00000 | 23.38449 | 42.55519 | 0.21067 | 7.37089 |
May | 344.00000 | 23.87370 | 51.88957 | -0.4709 | 10.16216 |
June | 336.00000 | 23.94789 | 54.26230 | -0.3591 | 8.05380 |
July | 338.00000 | 23.97326 | 61.14052 | -0.2781 | 6.91012 |
August | 348.00000 | 23.95217 | 61.02424 | -0.2697 | 6.76030 |
September | 330.00000 | 23.93385 | 56.55941 | -0.3629 | 8.06189 |
October | 340.00000 | 23.28451 | 46.73124 | 0.25055 | 7.98970 |
November | 330.00000 | 22.51728 | 35.27153 | -0.0572 | 7.25502 |
December | 338.00000 | 21.40255 | 31.03470 | -0.3969 | 9.55101 |
Annual Sum or Average | 4030.00000 | 22.98069 | 44.41597 | -0.2259 | 8.35513 |
Minimum of Months | 308.00000 | 21.20704 | 26.25846 | -0.5320 | 6.76030 |
Maximum of Months | 348.00000 | 23.97326 | 61.14052 | 0.25055 | 11.48917 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.20158 | 26.27210 | -0.5370 | 11.58577 |
February | 308.00000 | 21.67708 | 28.96686 | -0.3818 | 9.66408 |
March | 348.00000 | 22.45539 | 35.85426 | -0.0859 | 7.20911 |
April | 330.00000 | 23.35650 | 42.66349 | 0.20003 | 7.32607 |
May | 344.00000 | 23.86769 | 51.97484 | -0.4774 | 10.31365 |
June | 336.00000 | 23.94734 | 54.29330 | -0.3620 | 8.09798 |
July | 338.00000 | 23.97274 | 61.17964 | -0.2806 | 6.93636 |
August | 348.00000 | 23.95190 | 61.05532 | -0.2720 | 6.78425 |
September | 330.00000 | 23.93269 | 56.60034 | -0.3657 | 8.10565 |
October | 340.00000 | 23.26457 | 46.81546 | 0.24352 | 7.96387 |
November | 330.00000 | 22.48801 | 35.35153 | -0.0674 | 7.27967 |
December | 338.00000 | 21.39315 | 31.05912 | -0.4032 | 9.63336 |
Annual Sum or Average | 4030.00000 | 22.96816 | 44.47091 | -0.2322 | 8.40130 |
Minimum of Months | 308.00000 | 21.20158 | 26.27210 | -0.5370 | 6.78425 |
Maximum of Months | 348.00000 | 23.97274 | 61.17964 | 0.24352 | 11.58577 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.18626 | 26.31019 | -0.5540 | 11.94675 |
February | 308.00000 | 21.63323 | 29.06077 | -0.4037 | 9.96762 |
March | 348.00000 | 22.36935 | 36.08557 | -0.1153 | 7.35636 |
April | 330.00000 | 23.27444 | 43.06142 | 0.17299 | 7.24610 |
May | 344.00000 | 23.84622 | 52.28747 | -0.4923 | 10.71438 |
June | 336.00000 | 23.94603 | 54.47229 | -0.3624 | 8.11459 |
July | 338.00000 | 23.97188 | 61.33496 | -0.2788 | 6.91747 |
August | 348.00000 | 23.95179 | 61.16538 | -0.2693 | 6.75561 |
September | 330.00000 | 23.92874 | 56.76900 | -0.3667 | 8.13907 |
October | 340.00000 | 23.21125 | 47.06224 | 0.22792 | 7.94175 |
November | 330.00000 | 22.41595 | 35.54626 | -0.0904 | 7.36776 |
December | 338.00000 | 21.36801 | 31.12107 | -0.4205 | 9.89361 |
Annual Sum or Average | 4030.00000 | 22.93452 | 44.65377 | -0.2457 | 8.52257 |
Minimum of Months | 308.00000 | 21.18626 | 26.31019 | -0.5540 | 6.75561 |
Maximum of Months | 348.00000 | 23.97188 | 61.33496 | 0.22792 | 11.94675 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.16692 | 26.19133 | -0.6116 | 13.40513 |
February | 308.00000 | 21.58218 | 28.92577 | -0.4597 | 11.08304 |
March | 348.00000 | 22.23966 | 36.32795 | -0.1751 | 7.84242 |
April | 330.00000 | 23.13202 | 43.57170 | 0.12013 | 7.20490 |
May | 344.00000 | 23.79481 | 52.59768 | -0.5154 | 11.52558 |
June | 336.00000 | 23.94774 | 54.48568 | -0.3322 | 7.74377 |
July | 338.00000 | 23.97631 | 60.92567 | -0.2400 | 6.56996 |
August | 348.00000 | 23.95737 | 60.75134 | -0.2262 | 6.36101 |
September | 330.00000 | 23.91931 | 56.71378 | -0.3451 | 7.95650 |
October | 340.00000 | 23.13610 | 47.19389 | 0.20760 | 8.14377 |
November | 330.00000 | 22.33364 | 35.57821 | -0.1275 | 7.68396 |
December | 338.00000 | 21.33759 | 30.96385 | -0.4665 | 10.78727 |
Annual Sum or Average | 4030.00000 | 22.88633 | 44.64967 | -0.2637 | 8.84750 |
Minimum of Months | 308.00000 | 21.16692 | 26.19133 | -0.6116 | 6.36101 |
Maximum of Months | 348.00000 | 23.97631 | 60.92567 | 0.20760 | 13.40513 |
Report: DXReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 0.394488E+09 | 0.109691E+09 | 29.58 | 0.394083E+09 | 404854.55 | 0.00 | 0.41 | 26-FEB-15:10 | 0.00 | 01-FEB-00:10 | 7535.05 | 26-FEB-15:10 | 7535.05 | 26-FEB-15:10 | 67.44 | 28-FEB-19:50 | 2089.10 | 26-FEB-15:10 | 0.00 | 01-FEB-00:10 |
March | 0.181459E+10 | 0.490738E+09 | 94.92 | 0.144105E+10 | 0.373538E+09 | 0.00 | 0.71 | 30-MAR-16:10 | 0.00 | 01-MAR-00:10 | 14908.29 | 30-MAR-16:10 | 12830.81 | 30-MAR-16:10 | 3417.80 | 30-MAR-12:10 | 3931.11 | 30-MAR-16:10 | 0.00 | 01-MAR-00:10 |
April | 0.592788E+10 | 0.160269E+10 | 237.61 | 0.483778E+10 | 0.109009E+10 | 0.00 | 0.70 | 17-APR-16:10 | 0.00 | 01-APR-00:10 | 14123.21 | 17-APR-16:40 | 13459.31 | 17-APR-16:10 | 4617.30 | 23-APR-13:00 | 3852.84 | 17-APR-16:10 | 0.00 | 01-APR-00:10 |
May | 0.141995E+11 | 0.370265E+10 | 399.17 | 0.103551E+11 | 0.384443E+10 | 0.00 | 0.90 | 29-MAY-16:50 | 0.00 | 01-MAY-00:10 | 20966.85 | 30-MAY-17:00 | 16030.24 | 19-MAY-17:00 | 7405.46 | 31-MAY-13:10 | 5269.62 | 30-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 0.263593E+11 | 0.669949E+10 | 470.40 | 0.182106E+11 | 0.814869E+10 | 0.00 | 1.00 | 05-JUN-07:03 | 0.00 | 01-JUN-00:10 | 50521.76 | 26-JUN-07:02 | 34973.25 | 15-JUN-07:02 | 20694.01 | 27-JUN-07:03 | 10928.60 | 26-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.327673E+11 | 0.819603E+10 | 488.82 | 0.211476E+11 | 0.116197E+11 | 0.00 | 1.00 | 01-JUL-07:03 | 0.00 | 01-JUL-00:05 | 51528.38 | 27-JUL-07:03 | 34858.56 | 17-JUL-07:02 | 24599.07 | 27-JUL-07:03 | 11120.02 | 07-JUL-07:02 | 0.00 | 01-JUL-00:05 |
August | 0.359565E+11 | 0.885056E+10 | 497.27 | 0.224971E+11 | 0.134594E+11 | 0.00 | 1.00 | 01-AUG-07:02 | 0.00 | 01-AUG-00:10 | 51628.64 | 12-AUG-07:02 | 34366.31 | 27-AUG-07:02 | 29171.40 | 23-AUG-07:02 | 11206.25 | 19-AUG-07:02 | 0.00 | 01-AUG-00:10 |
September | 0.211613E+11 | 0.526798E+10 | 429.68 | 0.138986E+11 | 0.726266E+10 | 0.00 | 1.00 | 01-SEP-07:03 | 0.00 | 01-SEP-00:05 | 51301.33 | 17-SEP-07:02 | 36639.43 | 16-SEP-07:03 | 23633.77 | 28-SEP-07:03 | 10913.73 | 17-SEP-07:02 | 0.00 | 01-SEP-00:05 |
October | 0.734709E+10 | 0.185862E+10 | 226.36 | 0.503350E+10 | 0.231359E+10 | 0.00 | 1.00 | 18-OCT-07:03 | 0.00 | 01-OCT-00:10 | 47524.25 | 19-OCT-07:03 | 19871.82 | 19-OCT-07:03 | 27652.42 | 19-OCT-07:03 | 10095.52 | 19-OCT-07:03 | 0.00 | 01-OCT-00:10 |
November | 0.105082E+10 | 0.280730E+09 | 77.17 | 0.740475E+09 | 0.310340E+09 | 0.00 | 0.66 | 05-NOV-16:07 | 0.00 | 01-NOV-00:10 | 14068.39 | 05-NOV-16:07 | 10112.44 | 05-NOV-16:03 | 4554.59 | 05-NOV-13:40 | 3519.99 | 05-NOV-16:07 | 0.00 | 01-NOV-00:10 |
December | 68419920.76 | 18904382.28 | 8.50 | 48629141.01 | 19790779.75 | 0.00 | 0.32 | 12-DEC-14:30 | 0.00 | 01-DEC-00:03 | 6063.73 | 12-DEC-14:20 | 4330.34 | 12-DEC-14:40 | 1889.30 | 12-DEC-14:00 | 1648.20 | 12-DEC-14:30 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.147047E+12 | 0.370781E+11 | 2959.47 | 0.986045E+11 | 0.484427E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.359565E+11 | 0.885056E+10 | 497.27 | 0.224971E+11 | 0.134594E+11 | 0.00 | 1.00 | 0.00 | 51628.64 | 36639.43 | 29171.40 | 11206.25 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 2772405.14 | 765305.46 | 1.50 | 2187212.11 | 585193.04 | 0.00 | 0.14 | 31-JAN-22:50 | 0.00 | 01-JAN-00:10 | 1324.00 | 31-JAN-22:50 | 1084.13 | 31-JAN-22:50 | 500.92 | 19-JAN-21:20 | 362.89 | 31-JAN-22:50 | 0.00 | 01-JAN-00:10 |
February | 0.353031E+09 | 91261741.97 | 38.08 | 0.350935E+09 | 2096335.39 | 0.00 | 1.00 | 26-FEB-18:01 | 0.00 | 01-FEB-00:10 | 22869.82 | 26-FEB-18:37 | 22869.82 | 26-FEB-18:37 | 993.67 | 28-FEB-21:50 | 4922.64 | 26-FEB-18:01 | 0.00 | 01-FEB-00:10 |
March | 0.133450E+10 | 0.344946E+09 | 114.53 | 0.107794E+10 | 0.256561E+09 | 0.00 | 1.00 | 04-MAR-19:01 | 0.00 | 01-MAR-00:10 | 24216.90 | 04-MAR-19:30 | 22869.82 | 26-MAR-17:30 | 6546.91 | 04-MAR-20:33 | 5241.23 | 11-MAR-19:09 | 0.00 | 01-MAR-00:10 |
April | 0.424114E+10 | 0.108839E+10 | 261.90 | 0.344945E+10 | 0.791683E+09 | 0.00 | 1.00 | 08-APR-18:01 | 0.00 | 01-APR-00:10 | 25337.50 | 22-APR-18:02 | 22875.39 | 08-APR-18:08 | 11991.74 | 22-APR-18:02 | 5358.45 | 22-APR-18:02 | 0.00 | 01-APR-00:10 |
May | 0.856317E+10 | 0.217436E+10 | 434.19 | 0.638980E+10 | 0.217337E+10 | 0.00 | 1.00 | 01-MAY-20:03 | 0.00 | 01-MAY-00:10 | 25670.74 | 25-MAY-20:02 | 23286.29 | 13-MAY-18:17 | 13232.07 | 25-MAY-20:02 | 5442.97 | 14-MAY-17:38 | 0.00 | 01-MAY-00:10 |
June | 0.138518E+11 | 0.346517E+10 | 466.23 | 0.990761E+10 | 0.394421E+10 | 0.00 | 1.00 | 02-JUN-20:22 | 0.00 | 01-JUN-00:10 | 25576.85 | 29-JUN-07:03 | 23075.06 | 10-JUN-19:22 | 7008.67 | 27-JUN-07:03 | 5532.47 | 26-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.166139E+11 | 0.411911E+10 | 493.12 | 0.110631E+11 | 0.555078E+10 | 0.00 | 1.00 | 01-JUL-07:03 | 0.00 | 01-JUL-00:05 | 26030.52 | 27-JUL-07:03 | 20613.47 | 04-JUL-07:02 | 14111.40 | 28-JUL-20:10 | 5627.04 | 07-JUL-07:02 | 0.00 | 01-JUL-00:05 |
August | 0.179330E+11 | 0.438259E+10 | 500.21 | 0.116388E+11 | 0.629414E+10 | 0.00 | 1.00 | 01-AUG-07:02 | 0.00 | 01-AUG-00:10 | 26111.18 | 23-AUG-07:02 | 20371.51 | 27-AUG-07:02 | 8855.76 | 29-AUG-07:03 | 5690.58 | 19-AUG-07:02 | 0.00 | 01-AUG-00:10 |
September | 0.113186E+11 | 0.277449E+10 | 434.98 | 0.771423E+10 | 0.360440E+10 | 0.00 | 1.00 | 01-SEP-07:03 | 0.00 | 01-SEP-00:05 | 25969.35 | 17-SEP-07:02 | 20006.32 | 16-SEP-07:03 | 13571.55 | 21-SEP-20:02 | 5542.30 | 17-SEP-07:02 | 0.00 | 01-SEP-00:05 |
October | 0.436955E+10 | 0.107814E+10 | 240.73 | 0.311730E+10 | 0.125225E+10 | 0.00 | 1.00 | 02-OCT-21:32 | 0.00 | 01-OCT-00:10 | 26016.48 | 19-OCT-07:03 | 21611.50 | 11-OCT-20:07 | 14225.57 | 19-OCT-07:03 | 5449.98 | 19-OCT-07:03 | 0.00 | 01-OCT-00:10 |
November | 0.871535E+09 | 0.225193E+09 | 104.48 | 0.630857E+09 | 0.240678E+09 | 0.00 | 1.00 | 03-NOV-20:02 | 0.00 | 01-NOV-00:10 | 25024.17 | 04-NOV-18:02 | 14024.43 | 04-NOV-18:08 | 11112.20 | 04-NOV-18:24 | 5308.10 | 04-NOV-18:02 | 0.00 | 01-NOV-00:10 |
December | 71589185.82 | 19293304.99 | 17.39 | 50850757.94 | 20738427.88 | 0.00 | 0.40 | 12-DEC-14:10 | 0.00 | 01-DEC-00:03 | 4125.36 | 12-DEC-14:00 | 2925.64 | 12-DEC-14:30 | 1268.33 | 12-DEC-14:00 | 1075.29 | 12-DEC-14:00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.795246E+11 | 0.197637E+11 | 3107.34 | 0.553931E+11 | 0.241315E+11 | 0.00 | ||||||||||||||
Minimum of Months | 2772405.14 | 765305.46 | 1.50 | 2187212.11 | 585193.04 | 0.00 | 0.14 | 0.00 | 1324.00 | 1084.13 | 500.92 | 362.89 | 0.00 | |||||||
Maximum of Months | 0.179330E+11 | 0.438259E+10 | 500.21 | 0.116388E+11 | 0.629414E+10 | 0.00 | 1.00 | 0.00 | 26111.18 | 23286.29 | 14225.57 | 5690.58 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_3:3 COOLING COIL
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 0.210140E+09 | 57192466.75 | 28.00 | 0.210076E+09 | 64185.90 | 0.00 | 0.43 | 28-FEB-15:10 | 0.00 | 01-FEB-00:10 | 4217.65 | 28-FEB-15:10 | 4217.65 | 28-FEB-15:10 | 21.20 | 28-FEB-20:00 | 1137.32 | 28-FEB-15:10 | 0.00 | 01-FEB-00:10 |
March | 0.835683E+09 | 0.221433E+09 | 80.25 | 0.669587E+09 | 0.166097E+09 | 0.00 | 0.72 | 30-MAR-14:00 | 0.00 | 01-MAR-00:10 | 7943.26 | 30-MAR-14:00 | 6719.57 | 30-MAR-16:10 | 1865.72 | 30-MAR-12:10 | 2052.58 | 30-MAR-14:00 | 0.00 | 01-MAR-00:10 |
April | 0.273993E+10 | 0.725675E+09 | 193.42 | 0.228726E+10 | 0.452664E+09 | 0.00 | 0.70 | 17-APR-16:10 | 0.00 | 01-APR-00:10 | 7383.89 | 17-APR-14:00 | 7085.55 | 17-APR-16:10 | 2424.91 | 04-APR-14:00 | 1983.69 | 17-APR-14:00 | 0.00 | 01-APR-00:10 |
May | 0.598973E+10 | 0.153329E+10 | 314.94 | 0.443566E+10 | 0.155407E+10 | 0.00 | 1.00 | 31-MAY-06:03 | 0.00 | 01-MAY-00:10 | 14447.27 | 31-MAY-06:03 | 8175.42 | 19-MAY-16:10 | 7863.31 | 31-MAY-06:03 | 3037.05 | 31-MAY-06:03 | 0.00 | 01-MAY-00:10 |
June | 0.108474E+11 | 0.270605E+10 | 350.35 | 0.755419E+10 | 0.329322E+10 | 0.00 | 1.00 | 04-JUN-07:03 | 0.00 | 01-JUN-00:10 | 26731.07 | 23-JUN-06:03 | 17773.29 | 12-JUN-06:02 | 15000.36 | 19-JUN-06:03 | 5634.12 | 26-JUN-06:02 | 0.00 | 01-JUN-00:10 |
July | 0.129623E+11 | 0.318397E+10 | 362.73 | 0.838869E+10 | 0.457358E+10 | 0.00 | 1.00 | 01-JUL-06:03 | 0.00 | 01-JUL-00:05 | 27258.02 | 27-JUL-06:02 | 18422.34 | 04-JUL-07:02 | 15811.18 | 31-JUL-06:03 | 5679.43 | 07-JUL-06:02 | 0.00 | 01-JUL-00:05 |
August | 0.144440E+11 | 0.349648E+10 | 373.37 | 0.911415E+10 | 0.532989E+10 | 0.00 | 1.00 | 01-AUG-06:02 | 0.00 | 01-AUG-00:10 | 27654.29 | 21-AUG-06:02 | 20063.83 | 26-AUG-06:03 | 15119.07 | 23-AUG-06:02 | 5712.28 | 09-AUG-06:02 | 0.00 | 01-AUG-00:10 |
September | 0.843351E+10 | 0.206628E+10 | 323.95 | 0.562841E+10 | 0.280510E+10 | 0.00 | 1.00 | 01-SEP-06:03 | 0.00 | 01-SEP-00:05 | 27577.65 | 17-SEP-07:02 | 19487.98 | 16-SEP-06:02 | 15351.72 | 03-SEP-07:03 | 5645.28 | 17-SEP-07:02 | 0.00 | 01-SEP-00:05 |
October | 0.297783E+10 | 0.742152E+09 | 182.04 | 0.208178E+10 | 0.896046E+09 | 0.00 | 1.00 | 18-OCT-06:03 | 0.00 | 01-OCT-00:10 | 26610.76 | 19-OCT-06:03 | 11194.31 | 18-OCT-06:03 | 15931.49 | 19-OCT-06:03 | 5518.70 | 19-OCT-06:03 | 0.00 | 01-OCT-00:10 |
November | 0.449806E+09 | 0.119046E+09 | 71.33 | 0.332609E+09 | 0.117197E+09 | 0.00 | 0.60 | 05-NOV-14:00 | 0.00 | 01-NOV-00:10 | 6700.27 | 05-NOV-14:00 | 4565.49 | 05-NOV-15:00 | 2305.28 | 05-NOV-13:30 | 1650.36 | 05-NOV-14:00 | 0.00 | 01-NOV-00:10 |
December | 39872206.92 | 10806356.39 | 11.25 | 28341871.75 | 11530335.18 | 0.00 | 0.34 | 12-DEC-14:00 | 0.00 | 01-DEC-00:03 | 3504.26 | 12-DEC-14:00 | 2422.36 | 12-DEC-14:00 | 1081.91 | 12-DEC-14:00 | 927.46 | 12-DEC-14:00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.599302E+11 | 0.148624E+11 | 2291.63 | 0.407308E+11 | 0.191995E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.144440E+11 | 0.349648E+10 | 373.37 | 0.911415E+10 | 0.532989E+10 | 0.00 | 1.00 | 0.00 | 27654.29 | 20063.83 | 15931.49 | 5712.28 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_4:4 COOLING COIL
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 0.191072E+09 | 52241852.61 | 26.33 | 0.191021E+09 | 50732.81 | 0.00 | 0.42 | 28-FEB-15:10 | 0.00 | 01-FEB-00:10 | 4063.25 | 28-FEB-15:10 | 4063.25 | 28-FEB-15:10 | 17.21 | 28-FEB-20:00 | 1100.40 | 28-FEB-15:10 | 0.00 | 01-FEB-00:10 |
March | 0.789650E+09 | 0.209854E+09 | 78.58 | 0.632680E+09 | 0.156970E+09 | 0.00 | 0.71 | 30-MAR-14:00 | 0.00 | 01-MAR-00:10 | 7834.28 | 30-MAR-14:00 | 6633.35 | 30-MAR-16:10 | 1849.36 | 30-MAR-12:10 | 2030.12 | 30-MAR-14:00 | 0.00 | 01-MAR-00:10 |
April | 0.268058E+10 | 0.711407E+09 | 189.42 | 0.223888E+10 | 0.441701E+09 | 0.00 | 0.69 | 17-APR-16:10 | 0.00 | 01-APR-00:10 | 7356.43 | 17-APR-14:00 | 7059.33 | 17-APR-16:10 | 2377.93 | 23-APR-13:00 | 1978.39 | 17-APR-14:00 | 0.00 | 01-APR-00:10 |
May | 0.594260E+10 | 0.152302E+10 | 312.11 | 0.440139E+10 | 0.154121E+10 | 0.00 | 1.00 | 31-MAY-06:03 | 0.00 | 01-MAY-00:10 | 14333.50 | 31-MAY-06:03 | 8164.41 | 19-MAY-16:10 | 7804.74 | 31-MAY-06:03 | 3013.24 | 31-MAY-06:03 | 0.00 | 01-MAY-00:10 |
June | 0.108694E+11 | 0.271198E+10 | 350.56 | 0.757304E+10 | 0.329635E+10 | 0.00 | 1.00 | 04-JUN-07:03 | 0.00 | 01-JUN-00:10 | 26799.03 | 23-JUN-06:03 | 17861.94 | 12-JUN-06:02 | 15030.64 | 19-JUN-06:03 | 5648.32 | 26-JUN-06:02 | 0.00 | 01-JUN-00:10 |
July | 0.130084E+11 | 0.319509E+10 | 363.00 | 0.842703E+10 | 0.458140E+10 | 0.00 | 1.00 | 01-JUL-06:03 | 0.00 | 01-JUL-00:05 | 27326.25 | 27-JUL-06:02 | 18493.18 | 04-JUL-07:02 | 15846.62 | 31-JUL-06:03 | 5693.42 | 07-JUL-06:02 | 0.00 | 01-JUL-00:05 |
August | 0.144940E+11 | 0.350827E+10 | 373.23 | 0.915315E+10 | 0.534082E+10 | 0.00 | 1.00 | 01-AUG-06:02 | 0.00 | 01-AUG-00:10 | 27728.61 | 21-AUG-06:02 | 18208.88 | 27-AUG-07:02 | 15149.06 | 23-AUG-06:02 | 5726.06 | 09-AUG-06:02 | 0.00 | 01-AUG-00:10 |
September | 0.843058E+10 | 0.206641E+10 | 323.68 | 0.562866E+10 | 0.280192E+10 | 0.00 | 1.00 | 01-SEP-06:03 | 0.00 | 01-SEP-00:05 | 27643.33 | 17-SEP-07:02 | 19541.01 | 16-SEP-06:02 | 15390.23 | 03-SEP-07:03 | 5658.78 | 17-SEP-07:02 | 0.00 | 01-SEP-00:05 |
October | 0.293325E+10 | 0.731991E+09 | 179.12 | 0.204829E+10 | 0.884959E+09 | 0.00 | 1.00 | 18-OCT-06:03 | 0.00 | 01-OCT-00:10 | 26674.56 | 19-OCT-06:03 | 11214.09 | 18-OCT-06:03 | 15975.00 | 19-OCT-06:03 | 5531.91 | 19-OCT-06:03 | 0.00 | 01-OCT-00:10 |
November | 0.401729E+09 | 0.106607E+09 | 65.42 | 0.297028E+09 | 0.104700E+09 | 0.00 | 0.59 | 05-NOV-14:00 | 0.00 | 01-NOV-00:10 | 6547.30 | 05-NOV-14:00 | 4460.19 | 05-NOV-15:00 | 2254.05 | 05-NOV-13:30 | 1618.59 | 05-NOV-14:00 | 0.00 | 01-NOV-00:10 |
December | 32777106.30 | 8925817.11 | 8.67 | 23422024.97 | 9355081.33 | 0.00 | 0.31 | 12-DEC-14:00 | 0.00 | 01-DEC-00:03 | 3190.25 | 12-DEC-14:00 | 2203.82 | 12-DEC-14:00 | 986.42 | 12-DEC-14:00 | 851.00 | 12-DEC-14:00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.597740E+11 | 0.148258E+11 | 2270.12 | 0.406146E+11 | 0.191594E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.144940E+11 | 0.350827E+10 | 373.23 | 0.915315E+10 | 0.534082E+10 | 0.00 | 1.00 | 0.00 | 27728.61 | 19541.01 | 15975.00 | 5726.06 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_5:5 COOLING COIL
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 0.163601E+09 | 45029111.11 | 24.50 | 0.163563E+09 | 38034.33 | 0.00 | 0.39 | 28-FEB-15:10 | 0.00 | 01-FEB-00:10 | 3765.83 | 28-FEB-15:10 | 3765.83 | 28-FEB-15:10 | 12.56 | 28-FEB-19:40 | 1026.95 | 28-FEB-15:10 | 0.00 | 01-FEB-00:10 |
March | 0.705501E+09 | 0.188455E+09 | 69.67 | 0.565176E+09 | 0.140325E+09 | 0.00 | 0.69 | 30-MAR-14:00 | 0.00 | 01-MAR-00:10 | 7544.90 | 30-MAR-14:00 | 6394.06 | 30-MAR-16:10 | 1780.30 | 30-MAR-12:10 | 1965.18 | 30-MAR-14:00 | 0.00 | 01-MAR-00:10 |
April | 0.251631E+10 | 0.670975E+09 | 181.17 | 0.210101E+10 | 0.415304E+09 | 0.00 | 0.68 | 17-APR-16:10 | 0.00 | 01-APR-00:10 | 7161.27 | 17-APR-14:00 | 6884.03 | 17-APR-16:10 | 2275.57 | 23-APR-13:00 | 1932.32 | 17-APR-14:00 | 0.00 | 01-APR-00:10 |
May | 0.569873E+10 | 0.146528E+10 | 306.86 | 0.421266E+10 | 0.148607E+10 | 0.00 | 0.94 | 31-MAY-06:03 | 0.00 | 01-MAY-00:10 | 11815.12 | 31-MAY-06:03 | 8012.62 | 19-MAY-16:10 | 6471.54 | 31-MAY-06:03 | 2659.84 | 30-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 0.106168E+11 | 0.265285E+10 | 349.91 | 0.737130E+10 | 0.324553E+10 | 0.00 | 1.00 | 05-JUN-06:03 | 0.00 | 01-JUN-00:10 | 26595.91 | 23-JUN-06:03 | 17604.75 | 12-JUN-06:02 | 14951.32 | 19-JUN-06:03 | 5607.25 | 26-JUN-06:02 | 0.00 | 01-JUN-00:10 |
July | 0.127638E+11 | 0.313791E+10 | 362.55 | 0.824443E+10 | 0.451933E+10 | 0.00 | 1.00 | 01-JUL-06:03 | 0.00 | 01-JUL-00:05 | 27121.62 | 27-JUL-06:02 | 18222.08 | 04-JUL-07:02 | 15762.54 | 31-JUL-06:03 | 5652.21 | 07-JUL-06:02 | 0.00 | 01-JUL-00:05 |
August | 0.142452E+11 | 0.345059E+10 | 373.14 | 0.896270E+10 | 0.528250E+10 | 0.00 | 1.00 | 01-AUG-06:02 | 0.00 | 01-AUG-00:10 | 27522.33 | 21-AUG-06:02 | 18839.79 | 26-AUG-06:03 | 15074.28 | 23-AUG-06:02 | 5685.08 | 09-AUG-06:02 | 0.00 | 01-AUG-00:10 |
September | 0.820542E+10 | 0.201495E+10 | 320.65 | 0.545923E+10 | 0.274619E+10 | 0.00 | 1.00 | 01-SEP-06:03 | 0.00 | 01-SEP-00:05 | 27437.02 | 17-SEP-07:02 | 19245.17 | 16-SEP-06:02 | 15315.41 | 03-SEP-07:03 | 5618.35 | 17-SEP-07:02 | 0.00 | 01-SEP-00:05 |
October | 0.279145E+10 | 0.698509E+09 | 170.67 | 0.193968E+10 | 0.851778E+09 | 0.00 | 1.00 | 18-OCT-06:03 | 0.00 | 01-OCT-00:10 | 26482.40 | 19-OCT-06:03 | 10581.76 | 19-OCT-06:03 | 15900.65 | 19-OCT-06:03 | 5492.31 | 19-OCT-06:03 | 0.00 | 01-OCT-00:10 |
November | 0.330913E+09 | 88172452.48 | 58.00 | 0.243978E+09 | 86935197.25 | 0.00 | 0.56 | 05-NOV-14:00 | 0.00 | 01-NOV-00:10 | 6214.72 | 05-NOV-14:00 | 4233.08 | 05-NOV-16:00 | 2147.40 | 05-NOV-13:40 | 1548.27 | 05-NOV-15:00 | 0.00 | 01-NOV-00:10 |
December | 25596442.81 | 7026856.99 | 6.00 | 18305503.58 | 7290939.23 | 0.00 | 0.27 | 12-DEC-14:00 | 0.00 | 01-DEC-00:03 | 2744.31 | 12-DEC-14:00 | 1891.43 | 12-DEC-14:00 | 852.88 | 12-DEC-14:00 | 739.75 | 12-DEC-14:00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.580633E+11 | 0.144198E+11 | 2223.11 | 0.392820E+11 | 0.187813E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.142452E+11 | 0.345059E+10 | 373.14 | 0.896270E+10 | 0.528250E+10 | 0.00 | 1.00 | 0.00 | 27522.33 | 19245.17 | 15900.65 | 5685.08 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_6:6 COOLING COIL
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 0.248713E+09 | 70094668.40 | 22.42 | 0.248645E+09 | 68381.23 | 0.00 | 0.39 | 28-FEB-15:10 | 0.00 | 01-FEB-00:10 | 6808.29 | 28-FEB-15:10 | 6808.29 | 28-FEB-15:10 | 17.56 | 28-FEB-19:00 | 1889.39 | 28-FEB-15:10 | 0.00 | 01-FEB-00:10 |
March | 0.118878E+10 | 0.325329E+09 | 64.75 | 0.930114E+09 | 0.258667E+09 | 0.00 | 0.69 | 30-MAR-14:10 | 0.00 | 01-MAR-00:10 | 13691.39 | 30-MAR-14:10 | 11139.81 | 30-MAR-15:00 | 3406.83 | 30-MAR-12:30 | 3624.39 | 30-MAR-14:10 | 0.00 | 01-MAR-00:10 |
April | 0.427835E+10 | 0.116624E+10 | 175.50 | 0.349264E+10 | 0.785702E+09 | 0.00 | 0.70 | 17-APR-14:40 | 0.00 | 01-APR-00:10 | 13409.83 | 17-APR-14:30 | 12391.87 | 17-APR-15:00 | 4382.44 | 04-APR-14:10 | 3659.55 | 17-APR-14:30 | 0.00 | 01-APR-00:10 |
May | 0.100307E+11 | 0.262892E+10 | 295.67 | 0.724484E+10 | 0.278589E+10 | 0.00 | 0.93 | 30-MAY-15:00 | 0.00 | 01-MAY-00:10 | 20638.60 | 30-MAY-15:00 | 14713.26 | 30-MAY-15:00 | 7672.16 | 31-MAY-13:00 | 5187.98 | 30-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 0.193056E+11 | 0.489801E+10 | 342.01 | 0.131142E+11 | 0.619138E+10 | 0.00 | 1.00 | 04-JUN-08:63 | 0.00 | 01-JUN-00:10 | 48092.31 | 26-JUN-07:02 | 33108.68 | 15-JUN-07:02 | 26732.44 | 19-JUN-07:03 | 10344.41 | 26-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.230788E+11 | 0.576010E+10 | 344.79 | 0.146179E+11 | 0.846092E+10 | 0.00 | 1.00 | 01-JUL-07:03 | 0.00 | 01-JUL-00:05 | 48757.29 | 31-JUL-07:03 | 33442.27 | 25-JUL-07:03 | 29842.53 | 31-JUL-07:03 | 10616.54 | 16-JUL-08:62 | 0.00 | 01-JUL-00:05 |
August | 0.258938E+11 | 0.637109E+10 | 363.76 | 0.159356E+11 | 0.995825E+10 | 0.00 | 1.00 | 01-AUG-07:02 | 0.00 | 01-AUG-00:10 | 49810.97 | 21-AUG-07:02 | 31179.16 | 03-AUG-07:02 | 27521.35 | 23-AUG-07:02 | 10552.17 | 19-AUG-07:02 | 0.00 | 01-AUG-00:10 |
September | 0.146017E+11 | 0.364036E+10 | 307.18 | 0.946941E+10 | 0.513231E+10 | 0.00 | 1.00 | 01-SEP-07:03 | 0.00 | 01-SEP-00:05 | 49662.77 | 17-SEP-08:62 | 32553.63 | 09-SEP-07:03 | 27572.12 | 17-SEP-08:62 | 10402.90 | 17-SEP-08:62 | 0.00 | 01-SEP-00:05 |
October | 0.487028E+10 | 0.123994E+10 | 162.64 | 0.327361E+10 | 0.159667E+10 | 0.00 | 1.00 | 18-OCT-07:03 | 0.00 | 01-OCT-00:10 | 39901.60 | 19-OCT-07:03 | 16549.06 | 19-OCT-07:03 | 23352.54 | 19-OCT-07:03 | 8479.78 | 19-OCT-07:03 | 0.00 | 01-OCT-00:10 |
November | 0.484152E+09 | 0.131679E+09 | 47.42 | 0.353262E+09 | 0.130890E+09 | 0.00 | 0.58 | 05-NOV-15:00 | 0.00 | 01-NOV-00:10 | 11659.59 | 05-NOV-15:00 | 7660.90 | 05-NOV-15:00 | 4109.93 | 05-NOV-14:10 | 2959.99 | 05-NOV-15:00 | 0.00 | 01-NOV-00:10 |
December | 39308119.27 | 11048982.64 | 4.33 | 27639206.14 | 11668913.13 | 0.00 | 0.25 | 12-DEC-14:00 | 0.00 | 01-DEC-00:03 | 4497.32 | 12-DEC-14:00 | 3042.88 | 12-DEC-14:00 | 1454.44 | 12-DEC-14:00 | 1241.59 | 12-DEC-14:00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.104020E+12 | 0.262428E+11 | 2130.47 | 0.687079E+11 | 0.353124E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.258938E+11 | 0.637109E+10 | 363.76 | 0.159356E+11 | 0.995825E+10 | 0.00 | 1.00 | 0.00 | 49810.97 | 33442.27 | 29842.53 | 10616.54 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_7:7 COOLING COIL
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 0.119976E+09 | 33288306.35 | 20.75 | 0.119959E+09 | 16180.24 | 0.00 | 0.39 | 28-FEB-15:10 | 0.00 | 01-FEB-00:10 | 3448.84 | 28-FEB-15:10 | 3448.84 | 28-FEB-15:10 | 6.07 | 28-FEB-19:00 | 942.19 | 28-FEB-15:10 | 0.00 | 01-FEB-00:10 |
March | 0.586414E+09 | 0.157940E+09 | 60.50 | 0.460907E+09 | 0.125507E+09 | 0.00 | 0.68 | 30-MAR-14:10 | 0.00 | 01-MAR-00:10 | 6987.15 | 30-MAR-14:10 | 5718.11 | 30-MAR-15:00 | 1713.89 | 30-MAR-12:30 | 1821.05 | 30-MAR-14:10 | 0.00 | 01-MAR-00:10 |
April | 0.215332E+10 | 0.577626E+09 | 173.58 | 0.176582E+10 | 0.387501E+09 | 0.00 | 0.70 | 17-APR-14:50 | 0.00 | 01-APR-00:10 | 6903.99 | 17-APR-14:40 | 6402.37 | 17-APR-15:00 | 2196.11 | 04-APR-14:10 | 1852.48 | 17-APR-14:40 | 0.00 | 01-APR-00:10 |
May | 0.510981E+10 | 0.131714E+10 | 290.92 | 0.370301E+10 | 0.140680E+10 | 0.00 | 0.93 | 30-MAY-15:00 | 0.00 | 01-MAY-00:10 | 10654.98 | 30-MAY-15:00 | 7615.71 | 30-MAY-15:00 | 3927.49 | 31-MAY-13:00 | 2632.76 | 30-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 0.989470E+10 | 0.247023E+10 | 342.11 | 0.674183E+10 | 0.315287E+10 | 0.00 | 1.00 | 05-JUN-07:03 | 0.00 | 01-JUN-00:10 | 24848.44 | 26-JUN-07:02 | 17147.90 | 15-JUN-07:02 | 13788.89 | 19-JUN-07:03 | 5249.36 | 26-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.118404E+11 | 0.290815E+10 | 345.14 | 0.752665E+10 | 0.431370E+10 | 0.00 | 1.00 | 01-JUL-07:03 | 0.00 | 01-JUL-00:05 | 25187.67 | 31-JUL-07:03 | 17061.10 | 18-JUL-07:02 | 15404.68 | 31-JUL-07:03 | 5387.08 | 16-JUL-08:62 | 0.00 | 01-JUL-00:05 |
August | 0.132880E+11 | 0.321785E+10 | 364.29 | 0.820811E+10 | 0.507989E+10 | 0.00 | 1.00 | 01-AUG-07:02 | 0.00 | 01-AUG-00:10 | 25739.32 | 21-AUG-07:02 | 16136.02 | 03-AUG-07:02 | 14185.90 | 23-AUG-07:02 | 5353.63 | 19-AUG-07:02 | 0.00 | 01-AUG-00:10 |
September | 0.749238E+10 | 0.183712E+10 | 306.78 | 0.487841E+10 | 0.261397E+10 | 0.00 | 1.00 | 01-SEP-07:03 | 0.00 | 01-SEP-00:05 | 25652.22 | 17-SEP-08:62 | 16298.26 | 27-SEP-07:02 | 14240.87 | 17-SEP-08:62 | 5278.42 | 17-SEP-08:62 | 0.00 | 01-SEP-00:05 |
October | 0.248423E+10 | 0.621709E+09 | 160.47 | 0.167518E+10 | 0.809048E+09 | 0.00 | 1.00 | 18-OCT-07:03 | 0.00 | 01-OCT-00:10 | 18809.43 | 19-OCT-07:03 | 7793.19 | 19-OCT-07:03 | 11016.24 | 19-OCT-07:03 | 3928.31 | 19-OCT-07:03 | 0.00 | 01-OCT-00:10 |
November | 0.229521E+09 | 61354182.45 | 43.58 | 0.167855E+09 | 61666225.40 | 0.00 | 0.58 | 05-NOV-15:00 | 0.00 | 01-NOV-00:10 | 5980.88 | 05-NOV-15:00 | 3944.31 | 05-NOV-15:00 | 2085.05 | 05-NOV-14:10 | 1493.19 | 05-NOV-15:00 | 0.00 | 01-NOV-00:10 |
December | 17768863.10 | 4925481.26 | 4.33 | 12561990.12 | 5206872.98 | 0.00 | 0.23 | 12-DEC-14:00 | 0.00 | 01-DEC-00:03 | 2133.68 | 12-DEC-14:00 | 1447.72 | 12-DEC-14:00 | 685.96 | 12-DEC-14:00 | 581.65 | 12-DEC-14:00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.532165E+11 | 0.132073E+11 | 2112.46 | 0.352603E+11 | 0.179562E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.132880E+11 | 0.321785E+10 | 364.29 | 0.820811E+10 | 0.507989E+10 | 0.00 | 1.00 | 0.00 | 25739.32 | 17147.90 | 15404.68 | 5387.08 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_8:8 COOLING COIL
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 0.113384E+09 | 31519576.64 | 20.42 | 0.113367E+09 | 16672.49 | 0.00 | 0.38 | 28-FEB-15:10 | 0.00 | 01-FEB-00:10 | 3355.04 | 28-FEB-15:10 | 3355.04 | 28-FEB-15:10 | 6.68 | 28-FEB-19:00 | 918.65 | 28-FEB-15:10 | 0.00 | 01-FEB-00:10 |
March | 0.563804E+09 | 0.152109E+09 | 59.00 | 0.442539E+09 | 0.121264E+09 | 0.00 | 0.68 | 30-MAR-14:10 | 0.00 | 01-MAR-00:10 | 6892.73 | 30-MAR-14:10 | 5627.28 | 30-MAR-15:00 | 1696.98 | 30-MAR-12:40 | 1799.39 | 30-MAR-14:10 | 0.00 | 01-MAR-00:10 |
April | 0.209277E+10 | 0.562363E+09 | 170.25 | 0.171541E+10 | 0.377355E+09 | 0.00 | 0.69 | 17-APR-14:50 | 0.00 | 01-APR-00:10 | 6830.83 | 17-APR-14:40 | 6324.25 | 17-APR-15:00 | 2134.04 | 04-APR-14:10 | 1835.09 | 17-APR-14:40 | 0.00 | 01-APR-00:10 |
May | 0.502655E+10 | 0.129690E+10 | 288.58 | 0.363573E+10 | 0.139081E+10 | 0.00 | 0.93 | 30-MAY-15:00 | 0.00 | 01-MAY-00:10 | 10589.64 | 30-MAY-15:00 | 7553.50 | 30-MAY-15:00 | 3917.65 | 31-MAY-13:00 | 2617.93 | 30-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 0.983473E+10 | 0.245554E+10 | 342.11 | 0.668688E+10 | 0.314785E+10 | 0.00 | 1.00 | 05-JUN-07:03 | 0.00 | 01-JUN-00:10 | 24754.77 | 26-JUN-07:02 | 17025.06 | 15-JUN-07:02 | 13753.57 | 19-JUN-07:03 | 5230.12 | 26-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.117823E+11 | 0.289392E+10 | 344.87 | 0.747620E+10 | 0.430614E+10 | 0.00 | 1.00 | 01-JUL-07:03 | 0.00 | 01-JUL-00:05 | 25095.33 | 31-JUL-07:03 | 16948.57 | 18-JUL-07:02 | 15359.44 | 31-JUL-07:03 | 5367.44 | 16-JUL-08:62 | 0.00 | 01-JUL-00:05 |
August | 0.132309E+11 | 0.320397E+10 | 364.11 | 0.815678E+10 | 0.507416E+10 | 0.00 | 1.00 | 01-AUG-07:02 | 0.00 | 01-AUG-00:10 | 25643.79 | 21-AUG-07:02 | 16025.30 | 03-AUG-07:02 | 14148.70 | 23-AUG-07:02 | 5333.91 | 19-AUG-07:02 | 0.00 | 01-AUG-00:10 |
September | 0.744255E+10 | 0.182514E+10 | 306.28 | 0.483597E+10 | 0.260657E+10 | 0.00 | 1.00 | 01-SEP-07:03 | 0.00 | 01-SEP-00:05 | 25557.37 | 17-SEP-08:62 | 16185.73 | 27-SEP-07:02 | 14228.09 | 17-SEP-08:62 | 5259.27 | 17-SEP-08:62 | 0.00 | 01-SEP-00:05 |
October | 0.244694E+10 | 0.612750E+09 | 159.19 | 0.164533E+10 | 0.801609E+09 | 0.00 | 1.00 | 18-OCT-07:03 | 0.00 | 01-OCT-00:10 | 18030.90 | 19-OCT-07:03 | 7558.81 | 10-OCT-16:10 | 10580.41 | 19-OCT-07:03 | 3766.16 | 19-OCT-07:03 | 0.00 | 01-OCT-00:10 |
November | 0.215044E+09 | 57532691.36 | 41.50 | 0.156682E+09 | 58361923.62 | 0.00 | 0.57 | 05-NOV-15:00 | 0.00 | 01-NOV-00:10 | 5883.25 | 05-NOV-15:00 | 3867.77 | 05-NOV-15:00 | 2057.45 | 05-NOV-14:10 | 1471.41 | 05-NOV-15:00 | 0.00 | 01-NOV-00:10 |
December | 16404317.63 | 4556515.59 | 4.17 | 11584944.61 | 4819373.02 | 0.00 | 0.22 | 12-DEC-14:00 | 0.00 | 01-DEC-00:03 | 2022.04 | 12-DEC-14:00 | 1369.12 | 12-DEC-14:00 | 652.92 | 12-DEC-14:00 | 552.77 | 12-DEC-14:00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.527654E+11 | 0.130963E+11 | 2100.49 | 0.348765E+11 | 0.178890E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.132309E+11 | 0.320397E+10 | 364.11 | 0.815678E+10 | 0.507416E+10 | 0.00 | 1.00 | 0.00 | 25643.79 | 17025.06 | 15359.44 | 5367.44 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_9:9 COOLING COIL
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 98399622.01 | 27499901.64 | 18.17 | 98394100.20 | 5521.80 | 0.00 | 0.36 | 28-FEB-15:10 | 0.00 | 01-FEB-00:10 | 3142.14 | 28-FEB-15:10 | 3142.14 | 28-FEB-15:10 | 3.91 | 28-FEB-19:00 | 865.61 | 28-FEB-15:10 | 0.00 | 01-FEB-00:10 |
March | 0.506511E+09 | 0.137367E+09 | 55.67 | 0.398390E+09 | 0.108121E+09 | 0.00 | 0.66 | 30-MAR-14:10 | 0.00 | 01-MAR-00:10 | 6661.64 | 30-MAR-14:10 | 5438.01 | 30-MAR-15:00 | 1634.23 | 30-MAR-12:40 | 1748.77 | 30-MAR-14:10 | 0.00 | 01-MAR-00:10 |
April | 0.191445E+10 | 0.517956E+09 | 164.00 | 0.157916E+10 | 0.335289E+09 | 0.00 | 0.67 | 17-APR-14:50 | 0.00 | 01-APR-00:10 | 6622.34 | 17-APR-14:40 | 6136.65 | 17-APR-15:00 | 1963.23 | 04-APR-14:10 | 1788.52 | 17-APR-14:40 | 0.00 | 01-APR-00:10 |
May | 0.480599E+10 | 0.124472E+10 | 279.83 | 0.347857E+10 | 0.132743E+10 | 0.00 | 0.92 | 30-MAY-15:00 | 0.00 | 01-MAY-00:10 | 10440.99 | 30-MAY-15:00 | 7444.79 | 30-MAY-15:00 | 3873.38 | 31-MAY-13:00 | 2589.35 | 30-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 0.972201E+10 | 0.242999E+10 | 342.14 | 0.660784E+10 | 0.311417E+10 | 0.00 | 1.00 | 05-JUN-07:03 | 0.00 | 01-JUN-00:10 | 24751.95 | 26-JUN-07:02 | 16947.30 | 15-JUN-07:02 | 12253.59 | 19-JUN-07:03 | 5231.52 | 26-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.117119E+11 | 0.287803E+10 | 343.84 | 0.743812E+10 | 0.427377E+10 | 0.00 | 1.00 | 01-JUL-07:03 | 0.00 | 01-JUL-00:05 | 25102.58 | 31-JUL-07:03 | 16896.17 | 18-JUL-07:02 | 15390.24 | 31-JUL-07:03 | 5369.30 | 16-JUL-08:62 | 0.00 | 01-JUL-00:05 |
August | 0.131882E+11 | 0.319482E+10 | 365.27 | 0.813463E+10 | 0.505359E+10 | 0.00 | 1.00 | 01-AUG-07:02 | 0.00 | 01-AUG-00:10 | 25645.81 | 21-AUG-07:02 | 15981.42 | 03-AUG-07:02 | 14168.79 | 23-AUG-07:02 | 5335.73 | 19-AUG-07:02 | 0.00 | 01-AUG-00:10 |
September | 0.735652E+10 | 0.180575E+10 | 302.49 | 0.478150E+10 | 0.257503E+10 | 0.00 | 1.00 | 01-SEP-07:03 | 0.00 | 01-SEP-00:05 | 25557.93 | 17-SEP-08:62 | 16118.00 | 27-SEP-07:02 | 14322.17 | 17-SEP-08:62 | 5261.37 | 17-SEP-08:62 | 0.00 | 01-SEP-00:05 |
October | 0.235401E+10 | 0.590882E+09 | 154.31 | 0.157906E+10 | 0.774955E+09 | 0.00 | 1.00 | 19-OCT-07:03 | 0.00 | 01-OCT-00:10 | 15626.15 | 19-OCT-07:03 | 7486.41 | 10-OCT-16:10 | 9220.70 | 19-OCT-07:03 | 3265.46 | 19-OCT-07:03 | 0.00 | 01-OCT-00:10 |
November | 0.182946E+09 | 49073171.34 | 37.50 | 0.132412E+09 | 50534342.49 | 0.00 | 0.55 | 05-NOV-15:00 | 0.00 | 01-NOV-00:10 | 5647.79 | 05-NOV-15:00 | 3702.44 | 05-NOV-15:00 | 1971.63 | 05-NOV-14:10 | 1420.39 | 05-NOV-15:00 | 0.00 | 01-NOV-00:10 |
December | 12769032.16 | 3568032.62 | 4.00 | 9041817.11 | 3727215.05 | 0.00 | 0.19 | 12-DEC-14:00 | 0.00 | 01-DEC-00:03 | 1727.85 | 12-DEC-14:00 | 1170.24 | 12-DEC-14:00 | 557.61 | 12-DEC-14:00 | 476.14 | 12-DEC-14:00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.518537E+11 | 0.128797E+11 | 2067.20 | 0.342371E+11 | 0.176166E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.131882E+11 | 0.319482E+10 | 365.27 | 0.813463E+10 | 0.505359E+10 | 0.00 | 1.00 | 0.00 | 25645.81 | 16947.30 | 15390.24 | 5369.30 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_10:10 COOLING COIL
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 89670117.22 | 25248209.05 | 16.00 | 89670117.22 | -0.0 | 0.00 | 0.33 | 28-FEB-15:10 | 0.00 | 01-FEB-00:10 | 3167.53 | 28-FEB-15:10 | 3167.53 | 28-FEB-15:10 | 0.00 | 26-FEB-15:10 | 879.22 | 28-FEB-15:10 | 0.00 | 01-FEB-00:10 |
March | 0.452469E+09 | 0.123947E+09 | 47.67 | 0.361104E+09 | 91365435.07 | 0.00 | 0.62 | 30-MAR-14:10 | 0.00 | 01-MAR-00:10 | 6846.94 | 30-MAR-14:10 | 5609.22 | 30-MAR-14:50 | 1643.82 | 30-MAR-12:40 | 1816.84 | 30-MAR-14:10 | 0.00 | 01-MAR-00:10 |
April | 0.180900E+10 | 0.494741E+09 | 149.25 | 0.153432E+10 | 0.274686E+09 | 0.00 | 0.64 | 17-APR-14:10 | 0.00 | 01-APR-00:10 | 6802.50 | 17-APR-14:10 | 6304.12 | 17-APR-14:30 | 1787.74 | 04-APR-15:00 | 1856.71 | 17-APR-14:10 | 0.00 | 01-APR-00:10 |
May | 0.492668E+10 | 0.128469E+10 | 264.50 | 0.362633E+10 | 0.130035E+10 | 0.00 | 0.89 | 30-MAY-15:00 | 0.00 | 01-MAY-00:10 | 10975.56 | 30-MAY-15:00 | 7960.85 | 30-MAY-14:30 | 3976.61 | 31-MAY-13:00 | 2754.19 | 30-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 0.104786E+11 | 0.263020E+10 | 340.34 | 0.723719E+10 | 0.324140E+10 | 0.00 | 1.00 | 06-JUN-12:10 | 0.00 | 01-JUN-00:10 | 27525.33 | 26-JUN-07:02 | 15529.78 | 14-JUN-07:02 | 12784.58 | 26-JUN-07:02 | 5760.48 | 26-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.128183E+11 | 0.315963E+10 | 333.91 | 0.831821E+10 | 0.450007E+10 | 0.00 | 1.00 | 01-JUL-11:20 | 0.00 | 01-JUL-00:05 | 27549.70 | 09-JUL-08:62 | 17687.74 | 18-JUL-07:02 | 14938.05 | 09-JUL-08:62 | 5900.41 | 16-JUL-08:62 | 0.00 | 01-JUL-00:05 |
August | 0.144624E+11 | 0.351643E+10 | 366.36 | 0.911603E+10 | 0.534637E+10 | 0.00 | 1.00 | 01-AUG-07:02 | 0.00 | 01-AUG-00:10 | 28443.27 | 20-AUG-08:62 | 16900.93 | 27-AUG-08:62 | 16150.73 | 20-AUG-08:03 | 5891.25 | 19-AUG-07:02 | 0.00 | 01-AUG-00:10 |
September | 0.796981E+10 | 0.196098E+10 | 294.69 | 0.530551E+10 | 0.266430E+10 | 0.00 | 1.00 | 04-SEP-08:62 | 0.00 | 01-SEP-00:05 | 27446.88 | 17-SEP-08:62 | 16697.55 | 27-SEP-07:02 | 15496.21 | 05-SEP-07:03 | 5724.50 | 10-SEP-08:62 | 0.00 | 01-SEP-00:05 |
October | 0.244716E+10 | 0.616218E+09 | 146.06 | 0.166859E+10 | 0.778572E+09 | 0.00 | 0.92 | 10-OCT-14:10 | 0.00 | 01-OCT-00:10 | 11353.27 | 10-OCT-14:10 | 8125.51 | 10-OCT-14:10 | 5459.69 | 19-OCT-07:03 | 2770.68 | 10-OCT-14:10 | 0.00 | 01-OCT-00:10 |
November | 0.156508E+09 | 42183543.33 | 33.50 | 0.112252E+09 | 44256440.54 | 0.00 | 0.51 | 05-NOV-15:00 | 0.00 | 01-NOV-00:10 | 5685.07 | 05-NOV-15:00 | 3766.03 | 05-NOV-15:00 | 1948.65 | 05-NOV-14:10 | 1446.18 | 05-NOV-15:00 | 0.00 | 01-NOV-00:10 |
December | 9297963.00 | 2619363.94 | 3.00 | 6693954.86 | 2604008.14 | 0.00 | 0.15 | 12-DEC-14:00 | 0.00 | 01-DEC-00:03 | 1452.05 | 12-DEC-14:00 | 995.74 | 12-DEC-14:00 | 456.31 | 12-DEC-14:00 | 404.63 | 12-DEC-14:00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.556199E+11 | 0.138569E+11 | 1995.28 | 0.373759E+11 | 0.182440E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.144624E+11 | 0.351643E+10 | 366.36 | 0.911603E+10 | 0.534637E+10 | 0.00 | 1.00 | 0.00 | 28443.27 | 17687.74 | 16150.73 | 5900.41 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.03 | 51.62 | 22.42 | 90.25 | 73.74 | 0.00 | 0.00 | 0.00 |
February | 69.10 | 46.32 | 22.78 | 91.35 | 62.50 | 0.00 | 0.00 | 0.00 |
March | 62.14 | 32.39 | 29.76 | 89.64 | 42.59 | 0.00 | 0.00 | 0.00 |
April | 46.54 | 15.15 | 31.39 | 73.84 | 35.76 | 0.00 | 0.00 | 0.00 |
May | 37.60 | 4.37 | 33.23 | 62.28 | 23.77 | 0.00 | 0.00 | 0.00 |
June | 34.77 | 1.93 | 32.83 | 67.41 | 14.85 | 0.00 | 0.00 | 0.00 |
July | 35.15 | 2.62 | 32.53 | 71.84 | 10.25 | 0.00 | 0.00 | 0.00 |
August | 41.97 | 7.84 | 34.13 | 86.64 | 8.63 | 0.00 | 0.00 | 0.00 |
September | 46.15 | 17.17 | 28.99 | 81.55 | 20.58 | 0.00 | 0.00 | 0.00 |
October | 66.91 | 43.34 | 23.57 | 102.70 | 41.96 | 0.00 | 0.00 | 0.00 |
November | 71.98 | 47.77 | 24.22 | 100.49 | 53.49 | 0.00 | 0.00 | 0.00 |
December | 72.98 | 51.34 | 21.64 | 94.53 | 62.81 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.88 | 26.73 | 28.15 | 84.36 | 37.44 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 34.77 | 1.93 | 21.64 | 62.28 | 8.63 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 74.03 | 51.62 | 34.13 | 102.70 | 73.74 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.03 | 51.62 | 22.42 | 90.25 | 73.74 | 0.00 | 0.00 | 0.00 |
February | 69.10 | 46.32 | 22.78 | 91.35 | 62.50 | 0.00 | 0.00 | 0.00 |
March | 62.14 | 32.39 | 29.76 | 89.64 | 42.59 | 0.00 | 0.00 | 0.00 |
April | 46.54 | 15.15 | 31.39 | 73.84 | 35.76 | 0.00 | 0.00 | 0.00 |
May | 37.60 | 4.37 | 33.23 | 62.28 | 23.77 | 0.00 | 0.00 | 0.00 |
June | 34.77 | 1.93 | 32.83 | 67.41 | 14.85 | 0.00 | 0.00 | 0.00 |
July | 35.15 | 2.62 | 32.53 | 71.84 | 10.25 | 0.00 | 0.00 | 0.00 |
August | 41.97 | 7.84 | 34.13 | 86.64 | 8.63 | 0.00 | 0.00 | 0.00 |
September | 46.15 | 17.17 | 28.99 | 81.55 | 20.58 | 0.00 | 0.00 | 0.00 |
October | 66.91 | 43.34 | 23.57 | 102.70 | 41.96 | 0.00 | 0.00 | 0.00 |
November | 71.98 | 47.77 | 24.22 | 100.49 | 53.49 | 0.00 | 0.00 | 0.00 |
December | 72.98 | 51.34 | 21.64 | 94.53 | 62.81 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.88 | 26.73 | 28.15 | 84.36 | 37.44 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 34.77 | 1.93 | 21.64 | 62.28 | 8.63 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 74.03 | 51.62 | 34.13 | 102.70 | 73.74 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.03 | 51.62 | 22.42 | 90.25 | 73.74 | 0.00 | 0.00 | 0.00 |
February | 69.10 | 46.32 | 22.78 | 91.35 | 62.50 | 0.00 | 0.00 | 0.00 |
March | 62.14 | 32.39 | 29.76 | 89.64 | 42.59 | 0.00 | 0.00 | 0.00 |
April | 46.54 | 15.15 | 31.39 | 73.84 | 35.76 | 0.00 | 0.00 | 0.00 |
May | 37.60 | 4.37 | 33.23 | 62.28 | 23.77 | 0.00 | 0.00 | 0.00 |
June | 34.77 | 1.93 | 32.83 | 67.41 | 14.85 | 0.00 | 0.00 | 0.00 |
July | 35.15 | 2.62 | 32.53 | 71.84 | 10.25 | 0.00 | 0.00 | 0.00 |
August | 41.97 | 7.84 | 34.13 | 86.64 | 8.63 | 0.00 | 0.00 | 0.00 |
September | 46.15 | 17.17 | 28.99 | 81.55 | 20.58 | 0.00 | 0.00 | 0.00 |
October | 66.91 | 43.34 | 23.57 | 102.70 | 41.96 | 0.00 | 0.00 | 0.00 |
November | 71.98 | 47.77 | 24.22 | 100.49 | 53.49 | 0.00 | 0.00 | 0.00 |
December | 72.98 | 51.34 | 21.64 | 94.53 | 62.81 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.88 | 26.73 | 28.15 | 84.36 | 37.44 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 34.77 | 1.93 | 21.64 | 62.28 | 8.63 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 74.03 | 51.62 | 34.13 | 102.70 | 73.74 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.03 | 51.62 | 22.42 | 90.25 | 73.74 | 0.00 | 0.00 | 0.00 |
February | 69.10 | 46.32 | 22.78 | 91.35 | 62.50 | 0.00 | 0.00 | 0.00 |
March | 62.14 | 32.39 | 29.76 | 89.64 | 42.59 | 0.00 | 0.00 | 0.00 |
April | 46.54 | 15.15 | 31.39 | 73.84 | 35.76 | 0.00 | 0.00 | 0.00 |
May | 37.60 | 4.37 | 33.23 | 62.28 | 23.77 | 0.00 | 0.00 | 0.00 |
June | 34.77 | 1.93 | 32.83 | 67.41 | 14.85 | 0.00 | 0.00 | 0.00 |
July | 35.15 | 2.62 | 32.53 | 71.84 | 10.25 | 0.00 | 0.00 | 0.00 |
August | 41.97 | 7.84 | 34.13 | 86.64 | 8.63 | 0.00 | 0.00 | 0.00 |
September | 46.15 | 17.17 | 28.99 | 81.55 | 20.58 | 0.00 | 0.00 | 0.00 |
October | 66.91 | 43.34 | 23.57 | 102.70 | 41.96 | 0.00 | 0.00 | 0.00 |
November | 71.98 | 47.77 | 24.22 | 100.49 | 53.49 | 0.00 | 0.00 | 0.00 |
December | 72.98 | 51.34 | 21.64 | 94.53 | 62.81 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.88 | 26.73 | 28.15 | 84.36 | 37.44 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 34.77 | 1.93 | 21.64 | 62.28 | 8.63 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 74.03 | 51.62 | 34.13 | 102.70 | 73.74 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.00 | 62.05 | 26.95 | 108.91 | 87.47 | 0.00 | 0.00 | 0.00 |
February | 83.07 | 55.68 | 27.39 | 110.18 | 74.17 | 0.00 | 0.00 | 0.00 |
March | 74.71 | 38.93 | 35.77 | 108.03 | 50.69 | 0.00 | 0.00 | 0.00 |
April | 55.95 | 18.21 | 37.74 | 88.87 | 42.60 | 0.00 | 0.00 | 0.00 |
May | 45.21 | 5.25 | 39.95 | 74.82 | 28.37 | 0.00 | 0.00 | 0.00 |
June | 41.80 | 2.33 | 39.47 | 80.74 | 17.79 | 0.00 | 0.00 | 0.00 |
July | 42.26 | 3.15 | 39.11 | 86.01 | 12.29 | 0.00 | 0.00 | 0.00 |
August | 50.45 | 9.42 | 41.03 | 103.79 | 10.38 | 0.00 | 0.00 | 0.00 |
September | 55.48 | 20.64 | 34.85 | 97.90 | 24.62 | 0.00 | 0.00 | 0.00 |
October | 80.44 | 52.11 | 28.33 | 123.55 | 49.98 | 0.00 | 0.00 | 0.00 |
November | 86.53 | 57.42 | 29.11 | 121.00 | 63.66 | 0.00 | 0.00 | 0.00 |
December | 87.73 | 61.72 | 26.01 | 114.01 | 74.61 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 65.98 | 32.13 | 33.84 | 101.46 | 44.56 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 41.80 | 2.33 | 26.01 | 74.82 | 10.38 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 89.00 | 62.05 | 41.03 | 123.55 | 87.47 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.00 | 62.05 | 26.95 | 108.91 | 87.47 | 0.00 | 0.00 | 0.00 |
February | 83.07 | 55.68 | 27.39 | 110.18 | 74.17 | 0.00 | 0.00 | 0.00 |
March | 74.71 | 38.93 | 35.77 | 108.03 | 50.69 | 0.00 | 0.00 | 0.00 |
April | 55.95 | 18.21 | 37.74 | 88.87 | 42.60 | 0.00 | 0.00 | 0.00 |
May | 45.21 | 5.25 | 39.95 | 74.82 | 28.37 | 0.00 | 0.00 | 0.00 |
June | 41.80 | 2.33 | 39.47 | 80.74 | 17.79 | 0.00 | 0.00 | 0.00 |
July | 42.26 | 3.15 | 39.11 | 86.01 | 12.29 | 0.00 | 0.00 | 0.00 |
August | 50.45 | 9.42 | 41.03 | 103.79 | 10.38 | 0.00 | 0.00 | 0.00 |
September | 55.48 | 20.64 | 34.85 | 97.90 | 24.62 | 0.00 | 0.00 | 0.00 |
October | 80.44 | 52.11 | 28.33 | 123.55 | 49.98 | 0.00 | 0.00 | 0.00 |
November | 86.53 | 57.42 | 29.11 | 121.00 | 63.66 | 0.00 | 0.00 | 0.00 |
December | 87.73 | 61.72 | 26.01 | 114.01 | 74.61 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 65.98 | 32.13 | 33.84 | 101.46 | 44.56 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 41.80 | 2.33 | 26.01 | 74.82 | 10.38 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 89.00 | 62.05 | 41.03 | 123.55 | 87.47 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.03 | 51.62 | 22.42 | 88.97 | 77.96 | 0.00 | 0.00 | 0.00 |
February | 69.10 | 46.32 | 22.78 | 89.91 | 66.75 | 0.00 | 0.00 | 0.00 |
March | 62.14 | 32.39 | 29.76 | 88.05 | 45.77 | 0.00 | 0.00 | 0.00 |
April | 46.54 | 15.15 | 31.39 | 72.69 | 37.84 | 0.00 | 0.00 | 0.00 |
May | 37.60 | 4.37 | 33.23 | 61.83 | 24.70 | 0.00 | 0.00 | 0.00 |
June | 34.77 | 1.93 | 32.83 | 67.47 | 15.16 | 0.00 | 0.00 | 0.00 |
July | 35.15 | 2.62 | 32.53 | 72.07 | 10.48 | 0.00 | 0.00 | 0.00 |
August | 41.97 | 7.84 | 34.13 | 86.95 | 8.71 | 0.00 | 0.00 | 0.00 |
September | 46.15 | 17.17 | 28.99 | 81.52 | 20.83 | 0.00 | 0.00 | 0.00 |
October | 66.91 | 43.34 | 23.57 | 102.01 | 43.60 | 0.00 | 0.00 | 0.00 |
November | 71.98 | 47.77 | 24.22 | 99.24 | 56.31 | 0.00 | 0.00 | 0.00 |
December | 72.98 | 51.34 | 21.64 | 93.18 | 66.99 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.88 | 26.73 | 28.15 | 83.64 | 39.45 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 34.77 | 1.93 | 21.64 | 61.83 | 8.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 74.03 | 51.62 | 34.13 | 102.01 | 77.96 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.03 | 51.62 | 22.42 | 88.97 | 77.96 | 0.00 | 0.00 | 0.00 |
February | 69.10 | 46.32 | 22.78 | 89.91 | 66.75 | 0.00 | 0.00 | 0.00 |
March | 62.14 | 32.39 | 29.76 | 88.05 | 45.77 | 0.00 | 0.00 | 0.00 |
April | 46.54 | 15.15 | 31.39 | 72.69 | 37.84 | 0.00 | 0.00 | 0.00 |
May | 37.60 | 4.37 | 33.23 | 61.83 | 24.70 | 0.00 | 0.00 | 0.00 |
June | 34.77 | 1.93 | 32.83 | 67.47 | 15.16 | 0.00 | 0.00 | 0.00 |
July | 35.15 | 2.62 | 32.53 | 72.07 | 10.48 | 0.00 | 0.00 | 0.00 |
August | 41.97 | 7.84 | 34.13 | 86.95 | 8.71 | 0.00 | 0.00 | 0.00 |
September | 46.15 | 17.17 | 28.99 | 81.52 | 20.83 | 0.00 | 0.00 | 0.00 |
October | 66.91 | 43.34 | 23.57 | 102.01 | 43.60 | 0.00 | 0.00 | 0.00 |
November | 71.98 | 47.77 | 24.22 | 99.24 | 56.31 | 0.00 | 0.00 | 0.00 |
December | 72.98 | 51.34 | 21.64 | 93.18 | 66.99 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.88 | 26.73 | 28.15 | 83.64 | 39.45 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 34.77 | 1.93 | 21.64 | 61.83 | 8.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 74.03 | 51.62 | 34.13 | 102.01 | 77.96 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_DOOR
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.00 | 62.05 | 26.95 | 107.42 | 92.41 | 0.00 | 0.00 | 0.00 |
February | 83.07 | 55.68 | 27.39 | 108.48 | 79.15 | 0.00 | 0.00 | 0.00 |
March | 74.71 | 38.93 | 35.77 | 106.18 | 54.42 | 0.00 | 0.00 | 0.00 |
April | 55.95 | 18.21 | 37.74 | 87.51 | 45.04 | 0.00 | 0.00 | 0.00 |
May | 45.21 | 5.25 | 39.95 | 74.29 | 29.46 | 0.00 | 0.00 | 0.00 |
June | 41.80 | 2.33 | 39.47 | 80.82 | 18.17 | 0.00 | 0.00 | 0.00 |
July | 42.26 | 3.15 | 39.11 | 86.29 | 12.56 | 0.00 | 0.00 | 0.00 |
August | 50.45 | 9.42 | 41.03 | 104.17 | 10.47 | 0.00 | 0.00 | 0.00 |
September | 55.48 | 20.64 | 34.85 | 97.88 | 24.91 | 0.00 | 0.00 | 0.00 |
October | 80.44 | 52.11 | 28.33 | 122.76 | 51.90 | 0.00 | 0.00 | 0.00 |
November | 86.53 | 57.42 | 29.11 | 119.54 | 66.97 | 0.00 | 0.00 | 0.00 |
December | 87.73 | 61.72 | 26.01 | 112.43 | 79.50 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 65.98 | 32.13 | 33.84 | 100.63 | 46.91 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 41.80 | 2.33 | 26.01 | 74.29 | 10.47 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 89.00 | 62.05 | 41.03 | 122.76 | 92.41 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.03 | 51.62 | 22.42 | 89.24 | 75.67 | 0.00 | 0.00 | 0.00 |
February | 69.10 | 46.32 | 22.78 | 90.20 | 64.98 | 0.00 | 0.00 | 0.00 |
March | 62.14 | 32.39 | 29.76 | 88.33 | 44.91 | 0.00 | 0.00 | 0.00 |
April | 46.54 | 15.15 | 31.39 | 72.60 | 38.12 | 0.00 | 0.00 | 0.00 |
May | 37.60 | 4.37 | 33.23 | 61.55 | 25.67 | 0.00 | 0.00 | 0.00 |
June | 34.77 | 1.93 | 32.83 | 66.80 | 16.67 | 0.00 | 0.00 | 0.00 |
July | 35.15 | 2.62 | 32.53 | 70.90 | 11.89 | 0.00 | 0.00 | 0.00 |
August | 41.97 | 7.84 | 34.13 | 86.01 | 10.23 | 0.00 | 0.00 | 0.00 |
September | 46.15 | 17.17 | 28.99 | 81.18 | 22.25 | 0.00 | 0.00 | 0.00 |
October | 66.91 | 43.34 | 23.57 | 102.00 | 43.82 | 0.00 | 0.00 | 0.00 |
November | 71.98 | 47.77 | 24.22 | 99.59 | 55.41 | 0.00 | 0.00 | 0.00 |
December | 72.98 | 51.34 | 21.64 | 93.53 | 64.84 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.88 | 26.73 | 28.15 | 83.48 | 39.40 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 34.77 | 1.93 | 21.64 | 61.55 | 10.23 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 74.03 | 51.62 | 34.13 | 102.00 | 75.67 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.03 | 51.62 | 22.42 | 89.24 | 75.67 | 0.00 | 0.00 | 0.00 |
February | 69.10 | 46.32 | 22.78 | 90.20 | 64.98 | 0.00 | 0.00 | 0.00 |
March | 62.14 | 32.39 | 29.76 | 88.33 | 44.91 | 0.00 | 0.00 | 0.00 |
April | 46.54 | 15.15 | 31.39 | 72.60 | 38.12 | 0.00 | 0.00 | 0.00 |
May | 37.60 | 4.37 | 33.23 | 61.55 | 25.67 | 0.00 | 0.00 | 0.00 |
June | 34.77 | 1.93 | 32.83 | 66.80 | 16.67 | 0.00 | 0.00 | 0.00 |
July | 35.15 | 2.62 | 32.53 | 70.90 | 11.89 | 0.00 | 0.00 | 0.00 |
August | 41.97 | 7.84 | 34.13 | 86.01 | 10.23 | 0.00 | 0.00 | 0.00 |
September | 46.15 | 17.17 | 28.99 | 81.18 | 22.25 | 0.00 | 0.00 | 0.00 |
October | 66.91 | 43.34 | 23.57 | 102.00 | 43.82 | 0.00 | 0.00 | 0.00 |
November | 71.98 | 47.77 | 24.22 | 99.59 | 55.41 | 0.00 | 0.00 | 0.00 |
December | 72.98 | 51.34 | 21.64 | 93.53 | 64.84 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.88 | 26.73 | 28.15 | 83.48 | 39.40 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 34.77 | 1.93 | 21.64 | 61.55 | 10.23 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 74.03 | 51.62 | 34.13 | 102.00 | 75.67 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_DOOR
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 88.52 | 61.71 | 26.80 | 107.16 | 89.23 | 0.00 | 0.00 | 0.00 |
February | 82.61 | 55.38 | 27.24 | 108.24 | 76.65 | 0.00 | 0.00 | 0.00 |
March | 74.30 | 38.72 | 35.58 | 105.93 | 53.13 | 0.00 | 0.00 | 0.00 |
April | 55.64 | 18.11 | 37.53 | 86.93 | 45.12 | 0.00 | 0.00 | 0.00 |
May | 44.96 | 5.23 | 39.73 | 73.56 | 30.43 | 0.00 | 0.00 | 0.00 |
June | 41.57 | 2.31 | 39.26 | 79.59 | 19.83 | 0.00 | 0.00 | 0.00 |
July | 42.03 | 3.13 | 38.89 | 84.47 | 14.16 | 0.00 | 0.00 | 0.00 |
August | 50.18 | 9.37 | 40.80 | 102.53 | 12.21 | 0.00 | 0.00 | 0.00 |
September | 55.18 | 20.52 | 34.66 | 96.95 | 26.44 | 0.00 | 0.00 | 0.00 |
October | 80.00 | 51.82 | 28.17 | 122.08 | 51.86 | 0.00 | 0.00 | 0.00 |
November | 86.06 | 57.11 | 28.95 | 119.31 | 65.54 | 0.00 | 0.00 | 0.00 |
December | 87.25 | 61.38 | 25.87 | 112.25 | 76.57 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 65.62 | 31.96 | 33.66 | 99.89 | 46.60 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 41.57 | 2.31 | 25.87 | 73.56 | 12.21 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 88.52 | 61.71 | 40.80 | 122.08 | 89.23 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.03 | 51.62 | 22.42 | 89.43 | 74.68 | 0.00 | 0.00 | 0.00 |
February | 69.10 | 46.32 | 22.78 | 90.45 | 64.00 | 0.00 | 0.00 | 0.00 |
March | 62.14 | 32.39 | 29.76 | 88.60 | 44.18 | 0.00 | 0.00 | 0.00 |
April | 46.54 | 15.15 | 31.39 | 72.73 | 37.76 | 0.00 | 0.00 | 0.00 |
May | 37.60 | 4.37 | 33.23 | 61.60 | 25.56 | 0.00 | 0.00 | 0.00 |
June | 34.77 | 1.93 | 32.83 | 66.77 | 16.75 | 0.00 | 0.00 | 0.00 |
July | 35.15 | 2.62 | 32.53 | 70.85 | 12.02 | 0.00 | 0.00 | 0.00 |
August | 41.97 | 7.84 | 34.13 | 85.97 | 10.37 | 0.00 | 0.00 | 0.00 |
September | 46.15 | 17.17 | 28.99 | 81.18 | 22.27 | 0.00 | 0.00 | 0.00 |
October | 66.91 | 43.34 | 23.57 | 102.09 | 43.44 | 0.00 | 0.00 | 0.00 |
November | 71.98 | 47.77 | 24.22 | 99.84 | 54.67 | 0.00 | 0.00 | 0.00 |
December | 72.98 | 51.34 | 21.64 | 93.75 | 63.92 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.88 | 26.73 | 28.15 | 83.59 | 39.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 34.77 | 1.93 | 21.64 | 61.60 | 10.37 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 74.03 | 51.62 | 34.13 | 102.09 | 74.68 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.03 | 51.62 | 22.42 | 89.43 | 74.68 | 0.00 | 0.00 | 0.00 |
February | 69.10 | 46.32 | 22.78 | 90.45 | 64.00 | 0.00 | 0.00 | 0.00 |
March | 62.14 | 32.39 | 29.76 | 88.60 | 44.18 | 0.00 | 0.00 | 0.00 |
April | 46.54 | 15.15 | 31.39 | 72.73 | 37.76 | 0.00 | 0.00 | 0.00 |
May | 37.60 | 4.37 | 33.23 | 61.60 | 25.56 | 0.00 | 0.00 | 0.00 |
June | 34.77 | 1.93 | 32.83 | 66.77 | 16.75 | 0.00 | 0.00 | 0.00 |
July | 35.15 | 2.62 | 32.53 | 70.85 | 12.02 | 0.00 | 0.00 | 0.00 |
August | 41.97 | 7.84 | 34.13 | 85.97 | 10.37 | 0.00 | 0.00 | 0.00 |
September | 46.15 | 17.17 | 28.99 | 81.18 | 22.27 | 0.00 | 0.00 | 0.00 |
October | 66.91 | 43.34 | 23.57 | 102.09 | 43.44 | 0.00 | 0.00 | 0.00 |
November | 71.98 | 47.77 | 24.22 | 99.84 | 54.67 | 0.00 | 0.00 | 0.00 |
December | 72.98 | 51.34 | 21.64 | 93.75 | 63.92 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.88 | 26.73 | 28.15 | 83.59 | 39.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 34.77 | 1.93 | 21.64 | 61.60 | 10.37 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 74.03 | 51.62 | 34.13 | 102.09 | 74.68 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_DOOR
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 88.52 | 61.71 | 26.80 | 107.39 | 88.06 | 0.00 | 0.00 | 0.00 |
February | 82.61 | 55.38 | 27.24 | 108.53 | 75.49 | 0.00 | 0.00 | 0.00 |
March | 74.30 | 38.72 | 35.58 | 106.25 | 52.26 | 0.00 | 0.00 | 0.00 |
April | 55.64 | 18.11 | 37.53 | 87.09 | 44.70 | 0.00 | 0.00 | 0.00 |
May | 44.96 | 5.23 | 39.73 | 73.62 | 30.30 | 0.00 | 0.00 | 0.00 |
June | 41.57 | 2.31 | 39.26 | 79.57 | 19.93 | 0.00 | 0.00 | 0.00 |
July | 42.03 | 3.13 | 38.89 | 84.41 | 14.31 | 0.00 | 0.00 | 0.00 |
August | 50.18 | 9.37 | 40.80 | 102.48 | 12.38 | 0.00 | 0.00 | 0.00 |
September | 55.18 | 20.52 | 34.66 | 96.95 | 26.45 | 0.00 | 0.00 | 0.00 |
October | 80.00 | 51.82 | 28.17 | 122.19 | 51.41 | 0.00 | 0.00 | 0.00 |
November | 86.06 | 57.11 | 28.95 | 119.61 | 64.67 | 0.00 | 0.00 | 0.00 |
December | 87.25 | 61.38 | 25.87 | 112.51 | 75.47 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 65.62 | 31.96 | 33.66 | 100.03 | 46.13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 41.57 | 2.31 | 25.87 | 73.62 | 12.38 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 88.52 | 61.71 | 40.80 | 122.19 | 88.06 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.03 | 51.62 | 22.42 | 89.68 | 73.81 | 0.00 | 0.00 | 0.00 |
February | 69.10 | 46.32 | 22.78 | 90.77 | 63.00 | 0.00 | 0.00 | 0.00 |
March | 62.14 | 32.39 | 29.76 | 89.02 | 43.29 | 0.00 | 0.00 | 0.00 |
April | 46.54 | 15.15 | 31.39 | 73.04 | 37.12 | 0.00 | 0.00 | 0.00 |
May | 37.60 | 4.37 | 33.23 | 61.78 | 25.16 | 0.00 | 0.00 | 0.00 |
June | 34.77 | 1.93 | 32.83 | 66.91 | 16.45 | 0.00 | 0.00 | 0.00 |
July | 35.15 | 2.62 | 32.53 | 70.97 | 11.75 | 0.00 | 0.00 | 0.00 |
August | 41.97 | 7.84 | 34.13 | 86.08 | 10.10 | 0.00 | 0.00 | 0.00 |
September | 46.15 | 17.17 | 28.99 | 81.29 | 21.95 | 0.00 | 0.00 | 0.00 |
October | 66.91 | 43.34 | 23.57 | 102.30 | 42.85 | 0.00 | 0.00 | 0.00 |
November | 71.98 | 47.77 | 24.22 | 100.19 | 53.83 | 0.00 | 0.00 | 0.00 |
December | 72.98 | 51.34 | 21.64 | 94.03 | 63.10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.88 | 26.73 | 28.15 | 83.82 | 38.40 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 34.77 | 1.93 | 21.64 | 61.78 | 10.10 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 74.03 | 51.62 | 34.13 | 102.30 | 73.81 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.03 | 51.62 | 22.42 | 89.68 | 73.81 | 0.00 | 0.00 | 0.00 |
February | 69.10 | 46.32 | 22.78 | 90.77 | 63.00 | 0.00 | 0.00 | 0.00 |
March | 62.14 | 32.39 | 29.76 | 89.02 | 43.29 | 0.00 | 0.00 | 0.00 |
April | 46.54 | 15.15 | 31.39 | 73.04 | 37.12 | 0.00 | 0.00 | 0.00 |
May | 37.60 | 4.37 | 33.23 | 61.78 | 25.16 | 0.00 | 0.00 | 0.00 |
June | 34.77 | 1.93 | 32.83 | 66.91 | 16.45 | 0.00 | 0.00 | 0.00 |
July | 35.15 | 2.62 | 32.53 | 70.97 | 11.75 | 0.00 | 0.00 | 0.00 |
August | 41.97 | 7.84 | 34.13 | 86.08 | 10.10 | 0.00 | 0.00 | 0.00 |
September | 46.15 | 17.17 | 28.99 | 81.29 | 21.95 | 0.00 | 0.00 | 0.00 |
October | 66.91 | 43.34 | 23.57 | 102.30 | 42.85 | 0.00 | 0.00 | 0.00 |
November | 71.98 | 47.77 | 24.22 | 100.19 | 53.83 | 0.00 | 0.00 | 0.00 |
December | 72.98 | 51.34 | 21.64 | 94.03 | 63.10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.88 | 26.73 | 28.15 | 83.82 | 38.40 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 34.77 | 1.93 | 21.64 | 61.78 | 10.10 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 74.03 | 51.62 | 34.13 | 102.30 | 73.81 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_DOOR
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 88.52 | 61.71 | 26.80 | 107.68 | 87.03 | 0.00 | 0.00 | 0.00 |
February | 82.61 | 55.38 | 27.24 | 108.92 | 74.32 | 0.00 | 0.00 | 0.00 |
March | 74.30 | 38.72 | 35.58 | 106.75 | 51.22 | 0.00 | 0.00 | 0.00 |
April | 55.64 | 18.11 | 37.53 | 87.45 | 43.94 | 0.00 | 0.00 | 0.00 |
May | 44.96 | 5.23 | 39.73 | 73.84 | 29.83 | 0.00 | 0.00 | 0.00 |
June | 41.57 | 2.31 | 39.26 | 79.72 | 19.57 | 0.00 | 0.00 | 0.00 |
July | 42.03 | 3.13 | 38.89 | 84.56 | 14.00 | 0.00 | 0.00 | 0.00 |
August | 50.18 | 9.37 | 40.80 | 102.61 | 12.07 | 0.00 | 0.00 | 0.00 |
September | 55.18 | 20.52 | 34.66 | 97.08 | 26.08 | 0.00 | 0.00 | 0.00 |
October | 80.00 | 51.82 | 28.17 | 122.44 | 50.72 | 0.00 | 0.00 | 0.00 |
November | 86.06 | 57.11 | 28.95 | 120.03 | 63.68 | 0.00 | 0.00 | 0.00 |
December | 87.25 | 61.38 | 25.87 | 112.84 | 74.51 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 65.62 | 31.96 | 33.66 | 100.30 | 45.42 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 41.57 | 2.31 | 25.87 | 73.84 | 12.07 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 88.52 | 61.71 | 40.80 | 122.44 | 87.03 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.03 | 51.62 | 22.42 | 90.57 | 71.30 | 0.00 | 0.00 | 0.00 |
February | 69.10 | 46.32 | 22.78 | 91.70 | 60.51 | 0.00 | 0.00 | 0.00 |
March | 62.14 | 32.39 | 29.76 | 89.96 | 41.38 | 0.00 | 0.00 | 0.00 |
April | 46.54 | 15.15 | 31.39 | 73.73 | 35.58 | 0.00 | 0.00 | 0.00 |
May | 37.60 | 4.37 | 33.23 | 62.07 | 24.05 | 0.00 | 0.00 | 0.00 |
June | 34.77 | 1.93 | 32.83 | 66.94 | 15.53 | 0.00 | 0.00 | 0.00 |
July | 35.15 | 2.62 | 32.53 | 71.00 | 11.00 | 0.00 | 0.00 | 0.00 |
August | 41.97 | 7.84 | 34.13 | 86.08 | 9.33 | 0.00 | 0.00 | 0.00 |
September | 46.15 | 17.17 | 28.99 | 81.38 | 21.09 | 0.00 | 0.00 | 0.00 |
October | 66.91 | 43.34 | 23.57 | 102.75 | 41.53 | 0.00 | 0.00 | 0.00 |
November | 71.98 | 47.77 | 24.22 | 100.98 | 52.01 | 0.00 | 0.00 | 0.00 |
December | 72.98 | 51.34 | 21.64 | 94.89 | 61.03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.88 | 26.73 | 28.15 | 84.32 | 36.90 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 34.77 | 1.93 | 21.64 | 62.07 | 9.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 74.03 | 51.62 | 34.13 | 102.75 | 71.30 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.03 | 51.62 | 22.42 | 90.57 | 71.30 | 0.00 | 0.00 | 0.00 |
February | 69.10 | 46.32 | 22.78 | 91.70 | 60.51 | 0.00 | 0.00 | 0.00 |
March | 62.14 | 32.39 | 29.76 | 89.96 | 41.38 | 0.00 | 0.00 | 0.00 |
April | 46.54 | 15.15 | 31.39 | 73.73 | 35.58 | 0.00 | 0.00 | 0.00 |
May | 37.60 | 4.37 | 33.23 | 62.07 | 24.05 | 0.00 | 0.00 | 0.00 |
June | 34.77 | 1.93 | 32.83 | 66.94 | 15.53 | 0.00 | 0.00 | 0.00 |
July | 35.15 | 2.62 | 32.53 | 71.00 | 11.00 | 0.00 | 0.00 | 0.00 |
August | 41.97 | 7.84 | 34.13 | 86.08 | 9.33 | 0.00 | 0.00 | 0.00 |
September | 46.15 | 17.17 | 28.99 | 81.38 | 21.09 | 0.00 | 0.00 | 0.00 |
October | 66.91 | 43.34 | 23.57 | 102.75 | 41.53 | 0.00 | 0.00 | 0.00 |
November | 71.98 | 47.77 | 24.22 | 100.98 | 52.01 | 0.00 | 0.00 | 0.00 |
December | 72.98 | 51.34 | 21.64 | 94.89 | 61.03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.88 | 26.73 | 28.15 | 84.32 | 36.90 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 34.77 | 1.93 | 21.64 | 62.07 | 9.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 74.03 | 51.62 | 34.13 | 102.75 | 71.30 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.03 | 51.62 | 22.42 | 90.57 | 71.30 | 0.00 | 0.00 | 0.00 |
February | 69.10 | 46.32 | 22.78 | 91.70 | 60.51 | 0.00 | 0.00 | 0.00 |
March | 62.14 | 32.39 | 29.76 | 89.96 | 41.38 | 0.00 | 0.00 | 0.00 |
April | 46.54 | 15.15 | 31.39 | 73.73 | 35.58 | 0.00 | 0.00 | 0.00 |
May | 37.60 | 4.37 | 33.23 | 62.07 | 24.05 | 0.00 | 0.00 | 0.00 |
June | 34.77 | 1.93 | 32.83 | 66.94 | 15.53 | 0.00 | 0.00 | 0.00 |
July | 35.15 | 2.62 | 32.53 | 71.00 | 11.00 | 0.00 | 0.00 | 0.00 |
August | 41.97 | 7.84 | 34.13 | 86.08 | 9.33 | 0.00 | 0.00 | 0.00 |
September | 46.15 | 17.17 | 28.99 | 81.38 | 21.09 | 0.00 | 0.00 | 0.00 |
October | 66.91 | 43.34 | 23.57 | 102.75 | 41.53 | 0.00 | 0.00 | 0.00 |
November | 71.98 | 47.77 | 24.22 | 100.98 | 52.01 | 0.00 | 0.00 | 0.00 |
December | 72.98 | 51.34 | 21.64 | 94.89 | 61.03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.88 | 26.73 | 28.15 | 84.32 | 36.90 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 34.77 | 1.93 | 21.64 | 62.07 | 9.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 74.03 | 51.62 | 34.13 | 102.75 | 71.30 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.03 | 51.62 | 22.42 | 90.57 | 71.30 | 0.00 | 0.00 | 0.00 |
February | 69.10 | 46.32 | 22.78 | 91.70 | 60.51 | 0.00 | 0.00 | 0.00 |
March | 62.14 | 32.39 | 29.76 | 89.96 | 41.38 | 0.00 | 0.00 | 0.00 |
April | 46.54 | 15.15 | 31.39 | 73.73 | 35.58 | 0.00 | 0.00 | 0.00 |
May | 37.60 | 4.37 | 33.23 | 62.07 | 24.05 | 0.00 | 0.00 | 0.00 |
June | 34.77 | 1.93 | 32.83 | 66.94 | 15.53 | 0.00 | 0.00 | 0.00 |
July | 35.15 | 2.62 | 32.53 | 71.00 | 11.00 | 0.00 | 0.00 | 0.00 |
August | 41.97 | 7.84 | 34.13 | 86.08 | 9.33 | 0.00 | 0.00 | 0.00 |
September | 46.15 | 17.17 | 28.99 | 81.38 | 21.09 | 0.00 | 0.00 | 0.00 |
October | 66.91 | 43.34 | 23.57 | 102.75 | 41.53 | 0.00 | 0.00 | 0.00 |
November | 71.98 | 47.77 | 24.22 | 100.98 | 52.01 | 0.00 | 0.00 | 0.00 |
December | 72.98 | 51.34 | 21.64 | 94.89 | 61.03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.88 | 26.73 | 28.15 | 84.32 | 36.90 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 34.77 | 1.93 | 21.64 | 62.07 | 9.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 74.03 | 51.62 | 34.13 | 102.75 | 71.30 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 88.52 | 61.71 | 26.80 | 108.71 | 84.12 | 0.00 | 0.00 | 0.00 |
February | 82.61 | 55.38 | 27.24 | 110.00 | 71.42 | 0.00 | 0.00 | 0.00 |
March | 74.30 | 38.72 | 35.58 | 107.83 | 48.98 | 0.00 | 0.00 | 0.00 |
April | 55.64 | 18.11 | 37.53 | 88.26 | 42.14 | 0.00 | 0.00 | 0.00 |
May | 44.96 | 5.23 | 39.73 | 74.17 | 28.53 | 0.00 | 0.00 | 0.00 |
June | 41.57 | 2.31 | 39.26 | 79.77 | 18.48 | 0.00 | 0.00 | 0.00 |
July | 42.03 | 3.13 | 38.89 | 84.59 | 13.10 | 0.00 | 0.00 | 0.00 |
August | 50.18 | 9.37 | 40.80 | 102.60 | 11.14 | 0.00 | 0.00 | 0.00 |
September | 55.18 | 20.52 | 34.66 | 97.18 | 25.05 | 0.00 | 0.00 | 0.00 |
October | 80.00 | 51.82 | 28.17 | 122.95 | 49.17 | 0.00 | 0.00 | 0.00 |
November | 86.06 | 57.11 | 28.95 | 120.93 | 61.55 | 0.00 | 0.00 | 0.00 |
December | 87.25 | 61.38 | 25.87 | 113.84 | 72.10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 65.62 | 31.96 | 33.66 | 100.88 | 43.67 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 41.57 | 2.31 | 25.87 | 74.17 | 11.14 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 88.52 | 61.71 | 40.80 | 122.95 | 84.12 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 88.52 | 61.71 | 26.80 | 108.71 | 84.12 | 0.00 | 0.00 | 0.00 |
February | 82.61 | 55.38 | 27.24 | 110.00 | 71.42 | 0.00 | 0.00 | 0.00 |
March | 74.30 | 38.72 | 35.58 | 107.83 | 48.98 | 0.00 | 0.00 | 0.00 |
April | 55.64 | 18.11 | 37.53 | 88.26 | 42.14 | 0.00 | 0.00 | 0.00 |
May | 44.96 | 5.23 | 39.73 | 74.17 | 28.53 | 0.00 | 0.00 | 0.00 |
June | 41.57 | 2.31 | 39.26 | 79.77 | 18.48 | 0.00 | 0.00 | 0.00 |
July | 42.03 | 3.13 | 38.89 | 84.59 | 13.10 | 0.00 | 0.00 | 0.00 |
August | 50.18 | 9.37 | 40.80 | 102.60 | 11.14 | 0.00 | 0.00 | 0.00 |
September | 55.18 | 20.52 | 34.66 | 97.18 | 25.05 | 0.00 | 0.00 | 0.00 |
October | 80.00 | 51.82 | 28.17 | 122.95 | 49.17 | 0.00 | 0.00 | 0.00 |
November | 86.06 | 57.11 | 28.95 | 120.93 | 61.55 | 0.00 | 0.00 | 0.00 |
December | 87.25 | 61.38 | 25.87 | 113.84 | 72.10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 65.62 | 31.96 | 33.66 | 100.88 | 43.67 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 41.57 | 2.31 | 25.87 | 74.17 | 11.14 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 88.52 | 61.71 | 40.80 | 122.95 | 84.12 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.03 | 51.62 | 22.42 | 90.21 | 71.64 | 0.00 | 0.00 | 0.00 |
February | 69.10 | 46.32 | 22.78 | 91.43 | 60.68 | 0.00 | 0.00 | 0.00 |
March | 62.14 | 32.39 | 29.76 | 89.80 | 41.22 | 0.00 | 0.00 | 0.00 |
April | 46.54 | 15.15 | 31.39 | 73.67 | 35.42 | 0.00 | 0.00 | 0.00 |
May | 37.60 | 4.37 | 33.23 | 62.08 | 23.87 | 0.00 | 0.00 | 0.00 |
June | 34.77 | 1.93 | 32.83 | 67.10 | 15.27 | 0.00 | 0.00 | 0.00 |
July | 35.15 | 2.62 | 32.53 | 71.20 | 10.73 | 0.00 | 0.00 | 0.00 |
August | 41.97 | 7.84 | 34.13 | 86.25 | 9.02 | 0.00 | 0.00 | 0.00 |
September | 46.15 | 17.17 | 28.99 | 81.38 | 20.84 | 0.00 | 0.00 | 0.00 |
October | 66.91 | 43.34 | 23.57 | 102.60 | 41.39 | 0.00 | 0.00 | 0.00 |
November | 71.98 | 47.77 | 24.22 | 100.82 | 51.94 | 0.00 | 0.00 | 0.00 |
December | 72.98 | 51.34 | 21.64 | 94.59 | 61.14 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.88 | 26.73 | 28.15 | 84.24 | 36.80 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 34.77 | 1.93 | 21.64 | 62.08 | 9.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 74.03 | 51.62 | 34.13 | 102.60 | 71.64 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.03 | 51.62 | 22.42 | 90.21 | 71.64 | 0.00 | 0.00 | 0.00 |
February | 69.10 | 46.32 | 22.78 | 91.43 | 60.68 | 0.00 | 0.00 | 0.00 |
March | 62.14 | 32.39 | 29.76 | 89.80 | 41.22 | 0.00 | 0.00 | 0.00 |
April | 46.54 | 15.15 | 31.39 | 73.67 | 35.42 | 0.00 | 0.00 | 0.00 |
May | 37.60 | 4.37 | 33.23 | 62.08 | 23.87 | 0.00 | 0.00 | 0.00 |
June | 34.77 | 1.93 | 32.83 | 67.10 | 15.27 | 0.00 | 0.00 | 0.00 |
July | 35.15 | 2.62 | 32.53 | 71.20 | 10.73 | 0.00 | 0.00 | 0.00 |
August | 41.97 | 7.84 | 34.13 | 86.25 | 9.02 | 0.00 | 0.00 | 0.00 |
September | 46.15 | 17.17 | 28.99 | 81.38 | 20.84 | 0.00 | 0.00 | 0.00 |
October | 66.91 | 43.34 | 23.57 | 102.60 | 41.39 | 0.00 | 0.00 | 0.00 |
November | 71.98 | 47.77 | 24.22 | 100.82 | 51.94 | 0.00 | 0.00 | 0.00 |
December | 72.98 | 51.34 | 21.64 | 94.59 | 61.14 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.88 | 26.73 | 28.15 | 84.24 | 36.80 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 34.77 | 1.93 | 21.64 | 62.08 | 9.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 74.03 | 51.62 | 34.13 | 102.60 | 71.64 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_DOOR
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 88.52 | 61.71 | 26.80 | 108.33 | 84.48 | 0.00 | 0.00 | 0.00 |
February | 82.61 | 55.38 | 27.24 | 109.71 | 71.58 | 0.00 | 0.00 | 0.00 |
March | 74.30 | 38.72 | 35.58 | 107.69 | 48.78 | 0.00 | 0.00 | 0.00 |
April | 55.64 | 18.11 | 37.53 | 88.21 | 41.94 | 0.00 | 0.00 | 0.00 |
May | 44.96 | 5.23 | 39.73 | 74.21 | 28.31 | 0.00 | 0.00 | 0.00 |
June | 41.57 | 2.31 | 39.26 | 79.96 | 18.17 | 0.00 | 0.00 | 0.00 |
July | 42.03 | 3.13 | 38.89 | 84.83 | 12.78 | 0.00 | 0.00 | 0.00 |
August | 50.18 | 9.37 | 40.80 | 102.81 | 10.78 | 0.00 | 0.00 | 0.00 |
September | 55.18 | 20.52 | 34.66 | 97.20 | 24.77 | 0.00 | 0.00 | 0.00 |
October | 80.00 | 51.82 | 28.17 | 122.80 | 48.99 | 0.00 | 0.00 | 0.00 |
November | 86.06 | 57.11 | 28.95 | 120.78 | 61.44 | 0.00 | 0.00 | 0.00 |
December | 87.25 | 61.38 | 25.87 | 113.53 | 72.20 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 65.62 | 31.96 | 33.66 | 100.81 | 43.53 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 41.57 | 2.31 | 25.87 | 74.21 | 10.78 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 88.52 | 61.71 | 40.80 | 122.80 | 84.48 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.03 | 51.62 | 22.42 | 90.28 | 71.40 | 0.00 | 0.00 | 0.00 |
February | 69.10 | 46.32 | 22.78 | 91.54 | 60.37 | 0.00 | 0.00 | 0.00 |
March | 62.14 | 32.39 | 29.76 | 89.98 | 40.88 | 0.00 | 0.00 | 0.00 |
April | 46.54 | 15.15 | 31.39 | 73.84 | 35.12 | 0.00 | 0.00 | 0.00 |
May | 37.60 | 4.37 | 33.23 | 62.19 | 23.70 | 0.00 | 0.00 | 0.00 |
June | 34.77 | 1.93 | 32.83 | 67.16 | 15.18 | 0.00 | 0.00 | 0.00 |
July | 35.15 | 2.62 | 32.53 | 71.25 | 10.66 | 0.00 | 0.00 | 0.00 |
August | 41.97 | 7.84 | 34.13 | 86.29 | 8.95 | 0.00 | 0.00 | 0.00 |
September | 46.15 | 17.17 | 28.99 | 81.42 | 20.76 | 0.00 | 0.00 | 0.00 |
October | 66.91 | 43.34 | 23.57 | 102.69 | 41.18 | 0.00 | 0.00 | 0.00 |
November | 71.98 | 47.77 | 24.22 | 100.96 | 51.65 | 0.00 | 0.00 | 0.00 |
December | 72.98 | 51.34 | 21.64 | 94.69 | 60.88 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.88 | 26.73 | 28.15 | 84.34 | 36.60 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 34.77 | 1.93 | 21.64 | 62.19 | 8.95 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 74.03 | 51.62 | 34.13 | 102.69 | 71.40 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.03 | 51.62 | 22.42 | 90.28 | 71.40 | 0.00 | 0.00 | 0.00 |
February | 69.10 | 46.32 | 22.78 | 91.54 | 60.37 | 0.00 | 0.00 | 0.00 |
March | 62.14 | 32.39 | 29.76 | 89.98 | 40.88 | 0.00 | 0.00 | 0.00 |
April | 46.54 | 15.15 | 31.39 | 73.84 | 35.12 | 0.00 | 0.00 | 0.00 |
May | 37.60 | 4.37 | 33.23 | 62.19 | 23.70 | 0.00 | 0.00 | 0.00 |
June | 34.77 | 1.93 | 32.83 | 67.16 | 15.18 | 0.00 | 0.00 | 0.00 |
July | 35.15 | 2.62 | 32.53 | 71.25 | 10.66 | 0.00 | 0.00 | 0.00 |
August | 41.97 | 7.84 | 34.13 | 86.29 | 8.95 | 0.00 | 0.00 | 0.00 |
September | 46.15 | 17.17 | 28.99 | 81.42 | 20.76 | 0.00 | 0.00 | 0.00 |
October | 66.91 | 43.34 | 23.57 | 102.69 | 41.18 | 0.00 | 0.00 | 0.00 |
November | 71.98 | 47.77 | 24.22 | 100.96 | 51.65 | 0.00 | 0.00 | 0.00 |
December | 72.98 | 51.34 | 21.64 | 94.69 | 60.88 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.88 | 26.73 | 28.15 | 84.34 | 36.60 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 34.77 | 1.93 | 21.64 | 62.19 | 8.95 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 74.03 | 51.62 | 34.13 | 102.69 | 71.40 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_DOOR
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 88.52 | 61.71 | 26.80 | 108.42 | 84.19 | 0.00 | 0.00 | 0.00 |
February | 82.61 | 55.38 | 27.24 | 109.85 | 71.22 | 0.00 | 0.00 | 0.00 |
March | 74.30 | 38.72 | 35.58 | 107.90 | 48.37 | 0.00 | 0.00 | 0.00 |
April | 55.64 | 18.11 | 37.53 | 88.41 | 41.58 | 0.00 | 0.00 | 0.00 |
May | 44.96 | 5.23 | 39.73 | 74.33 | 28.11 | 0.00 | 0.00 | 0.00 |
June | 41.57 | 2.31 | 39.26 | 80.03 | 18.07 | 0.00 | 0.00 | 0.00 |
July | 42.03 | 3.13 | 38.89 | 84.89 | 12.70 | 0.00 | 0.00 | 0.00 |
August | 50.18 | 9.37 | 40.80 | 102.86 | 10.70 | 0.00 | 0.00 | 0.00 |
September | 55.18 | 20.52 | 34.66 | 97.25 | 24.66 | 0.00 | 0.00 | 0.00 |
October | 80.00 | 51.82 | 28.17 | 122.91 | 48.74 | 0.00 | 0.00 | 0.00 |
November | 86.06 | 57.11 | 28.95 | 120.95 | 61.10 | 0.00 | 0.00 | 0.00 |
December | 87.25 | 61.38 | 25.87 | 113.64 | 71.89 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 65.62 | 31.96 | 33.66 | 100.93 | 43.29 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 41.57 | 2.31 | 25.87 | 74.33 | 10.70 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 88.52 | 61.71 | 40.80 | 122.91 | 84.19 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.03 | 51.62 | 22.42 | 90.55 | 70.33 | 0.00 | 0.00 | 0.00 |
February | 69.10 | 46.32 | 22.78 | 91.84 | 59.31 | 0.00 | 0.00 | 0.00 |
March | 62.14 | 32.39 | 29.76 | 90.42 | 39.87 | 0.00 | 0.00 | 0.00 |
April | 46.54 | 15.15 | 31.39 | 74.28 | 34.23 | 0.00 | 0.00 | 0.00 |
May | 37.60 | 4.37 | 33.23 | 62.45 | 23.22 | 0.00 | 0.00 | 0.00 |
June | 34.77 | 1.93 | 32.83 | 67.21 | 15.03 | 0.00 | 0.00 | 0.00 |
July | 35.15 | 2.62 | 32.53 | 71.25 | 10.59 | 0.00 | 0.00 | 0.00 |
August | 41.97 | 7.84 | 34.13 | 86.27 | 8.92 | 0.00 | 0.00 | 0.00 |
September | 46.15 | 17.17 | 28.99 | 81.45 | 20.61 | 0.00 | 0.00 | 0.00 |
October | 66.91 | 43.34 | 23.57 | 102.89 | 40.62 | 0.00 | 0.00 | 0.00 |
November | 71.98 | 47.77 | 24.22 | 101.29 | 50.88 | 0.00 | 0.00 | 0.00 |
December | 72.98 | 51.34 | 21.64 | 94.97 | 59.97 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.88 | 26.73 | 28.15 | 84.55 | 36.01 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 34.77 | 1.93 | 21.64 | 62.45 | 8.92 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 74.03 | 51.62 | 34.13 | 102.89 | 70.33 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.03 | 51.62 | 22.42 | 90.55 | 70.33 | 0.00 | 0.00 | 0.00 |
February | 69.10 | 46.32 | 22.78 | 91.84 | 59.31 | 0.00 | 0.00 | 0.00 |
March | 62.14 | 32.39 | 29.76 | 90.42 | 39.87 | 0.00 | 0.00 | 0.00 |
April | 46.54 | 15.15 | 31.39 | 74.28 | 34.23 | 0.00 | 0.00 | 0.00 |
May | 37.60 | 4.37 | 33.23 | 62.45 | 23.22 | 0.00 | 0.00 | 0.00 |
June | 34.77 | 1.93 | 32.83 | 67.21 | 15.03 | 0.00 | 0.00 | 0.00 |
July | 35.15 | 2.62 | 32.53 | 71.25 | 10.59 | 0.00 | 0.00 | 0.00 |
August | 41.97 | 7.84 | 34.13 | 86.27 | 8.92 | 0.00 | 0.00 | 0.00 |
September | 46.15 | 17.17 | 28.99 | 81.45 | 20.61 | 0.00 | 0.00 | 0.00 |
October | 66.91 | 43.34 | 23.57 | 102.89 | 40.62 | 0.00 | 0.00 | 0.00 |
November | 71.98 | 47.77 | 24.22 | 101.29 | 50.88 | 0.00 | 0.00 | 0.00 |
December | 72.98 | 51.34 | 21.64 | 94.97 | 59.97 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.88 | 26.73 | 28.15 | 84.55 | 36.01 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 34.77 | 1.93 | 21.64 | 62.45 | 8.92 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 74.03 | 51.62 | 34.13 | 102.89 | 70.33 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_DOOR
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 88.52 | 61.71 | 26.80 | 108.74 | 82.93 | 0.00 | 0.00 | 0.00 |
February | 82.61 | 55.38 | 27.24 | 110.22 | 69.96 | 0.00 | 0.00 | 0.00 |
March | 74.30 | 38.72 | 35.58 | 108.42 | 47.19 | 0.00 | 0.00 | 0.00 |
April | 55.64 | 18.11 | 37.53 | 88.94 | 40.54 | 0.00 | 0.00 | 0.00 |
May | 44.96 | 5.23 | 39.73 | 74.64 | 27.54 | 0.00 | 0.00 | 0.00 |
June | 41.57 | 2.31 | 39.26 | 80.09 | 17.89 | 0.00 | 0.00 | 0.00 |
July | 42.03 | 3.13 | 38.89 | 84.89 | 12.61 | 0.00 | 0.00 | 0.00 |
August | 50.18 | 9.37 | 40.80 | 102.83 | 10.66 | 0.00 | 0.00 | 0.00 |
September | 55.18 | 20.52 | 34.66 | 97.29 | 24.49 | 0.00 | 0.00 | 0.00 |
October | 80.00 | 51.82 | 28.17 | 123.15 | 48.08 | 0.00 | 0.00 | 0.00 |
November | 86.06 | 57.11 | 28.95 | 121.34 | 60.20 | 0.00 | 0.00 | 0.00 |
December | 87.25 | 61.38 | 25.87 | 113.98 | 70.82 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 65.62 | 31.96 | 33.66 | 101.18 | 42.60 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 41.57 | 2.31 | 25.87 | 74.64 | 10.66 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 88.52 | 61.71 | 40.80 | 123.15 | 82.93 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.03 | 51.62 | 22.42 | 91.44 | 65.92 | 0.00 | 0.00 | 0.00 |
February | 69.10 | 46.32 | 22.78 | 92.64 | 55.28 | 0.00 | 0.00 | 0.00 |
March | 62.14 | 32.39 | 29.76 | 91.38 | 36.50 | 0.00 | 0.00 | 0.00 |
April | 46.54 | 15.15 | 31.39 | 75.21 | 31.21 | 0.00 | 0.00 | 0.00 |
May | 37.60 | 4.37 | 33.23 | 62.91 | 21.45 | 0.00 | 0.00 | 0.00 |
June | 34.77 | 1.93 | 32.83 | 66.87 | 14.51 | 0.00 | 0.00 | 0.00 |
July | 35.15 | 2.62 | 32.53 | 70.65 | 10.45 | 0.00 | 0.00 | 0.00 |
August | 41.97 | 7.84 | 34.13 | 85.58 | 9.03 | 0.00 | 0.00 | 0.00 |
September | 46.15 | 17.17 | 28.99 | 81.17 | 20.22 | 0.00 | 0.00 | 0.00 |
October | 66.91 | 43.34 | 23.57 | 103.14 | 38.91 | 0.00 | 0.00 | 0.00 |
November | 71.98 | 47.77 | 24.22 | 101.91 | 48.52 | 0.00 | 0.00 | 0.00 |
December | 72.98 | 51.34 | 21.64 | 95.78 | 56.53 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.88 | 26.73 | 28.15 | 84.87 | 33.93 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 34.77 | 1.93 | 21.64 | 62.91 | 9.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 74.03 | 51.62 | 34.13 | 103.14 | 65.92 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.03 | 51.62 | 22.42 | 91.44 | 65.92 | 0.00 | 0.00 | 0.00 |
February | 69.10 | 46.32 | 22.78 | 92.64 | 55.28 | 0.00 | 0.00 | 0.00 |
March | 62.14 | 32.39 | 29.76 | 91.38 | 36.50 | 0.00 | 0.00 | 0.00 |
April | 46.54 | 15.15 | 31.39 | 75.21 | 31.21 | 0.00 | 0.00 | 0.00 |
May | 37.60 | 4.37 | 33.23 | 62.91 | 21.45 | 0.00 | 0.00 | 0.00 |
June | 34.77 | 1.93 | 32.83 | 66.87 | 14.51 | 0.00 | 0.00 | 0.00 |
July | 35.15 | 2.62 | 32.53 | 70.65 | 10.45 | 0.00 | 0.00 | 0.00 |
August | 41.97 | 7.84 | 34.13 | 85.58 | 9.03 | 0.00 | 0.00 | 0.00 |
September | 46.15 | 17.17 | 28.99 | 81.17 | 20.22 | 0.00 | 0.00 | 0.00 |
October | 66.91 | 43.34 | 23.57 | 103.14 | 38.91 | 0.00 | 0.00 | 0.00 |
November | 71.98 | 47.77 | 24.22 | 101.91 | 48.52 | 0.00 | 0.00 | 0.00 |
December | 72.98 | 51.34 | 21.64 | 95.78 | 56.53 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.88 | 26.73 | 28.15 | 84.87 | 33.93 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 34.77 | 1.93 | 21.64 | 62.91 | 9.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 74.03 | 51.62 | 34.13 | 103.14 | 65.92 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_DOOR
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 88.52 | 61.71 | 26.80 | 109.82 | 77.73 | 0.00 | 0.00 | 0.00 |
February | 82.61 | 55.38 | 27.24 | 111.18 | 65.22 | 0.00 | 0.00 | 0.00 |
March | 74.30 | 38.72 | 35.58 | 109.58 | 43.23 | 0.00 | 0.00 | 0.00 |
April | 55.64 | 18.11 | 37.53 | 90.05 | 36.98 | 0.00 | 0.00 | 0.00 |
May | 44.96 | 5.23 | 39.73 | 75.20 | 25.46 | 0.00 | 0.00 | 0.00 |
June | 41.57 | 2.31 | 39.26 | 79.69 | 17.29 | 0.00 | 0.00 | 0.00 |
July | 42.03 | 3.13 | 38.89 | 84.17 | 12.46 | 0.00 | 0.00 | 0.00 |
August | 50.18 | 9.37 | 40.80 | 102.01 | 10.80 | 0.00 | 0.00 | 0.00 |
September | 55.18 | 20.52 | 34.66 | 96.95 | 24.03 | 0.00 | 0.00 | 0.00 |
October | 80.00 | 51.82 | 28.17 | 123.46 | 46.07 | 0.00 | 0.00 | 0.00 |
November | 86.06 | 57.11 | 28.95 | 122.09 | 57.41 | 0.00 | 0.00 | 0.00 |
December | 87.25 | 61.38 | 25.87 | 114.96 | 66.77 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 65.62 | 31.96 | 33.66 | 101.56 | 40.15 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 41.57 | 2.31 | 25.87 | 75.20 | 10.80 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 88.52 | 61.71 | 40.80 | 123.46 | 77.73 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.198295E+09 | 0.138251E+09 | 60044475.52 | 0.241714E+09 | 0.197515E+09 |
February | 0.167165E+09 | 0.112055E+09 | 55109791.18 | 0.221002E+09 | 0.151210E+09 |
March | 0.166446E+09 | 86741742.44 | 79704060.20 | 0.240083E+09 | 0.114063E+09 |
April | 0.120636E+09 | 39269464.32 | 81366106.23 | 0.191402E+09 | 92694298.35 |
May | 0.100718E+09 | 11706113.22 | 89011474.34 | 0.166804E+09 | 63674136.46 |
June | 90119995.22 | 5014823.53 | 85105171.69 | 0.174729E+09 | 38488590.99 |
July | 94146554.65 | 7020104.51 | 87126450.14 | 0.192414E+09 | 27448445.19 |
August | 0.112404E+09 | 20997518.03 | 91406771.71 | 0.232049E+09 | 23109757.39 |
September | 0.119629E+09 | 44495913.07 | 75133499.15 | 0.211372E+09 | 53343622.32 |
October | 0.179210E+09 | 0.116092E+09 | 63117399.48 | 0.275060E+09 | 0.112398E+09 |
November | 0.186578E+09 | 0.123810E+09 | 62767874.88 | 0.260460E+09 | 0.138646E+09 |
December | 0.195464E+09 | 0.137511E+09 | 57953675.66 | 0.253180E+09 | 0.168235E+09 |
Annual Sum or Average | 0.173081E+10 | 0.842965E+09 | 0.887847E+09 | 0.266027E+10 | 0.118083E+10 |
Minimum of Months | 90119995.22 | 5014823.53 | 55109791.18 | 0.166804E+09 | 23109757.39 |
Maximum of Months | 0.198295E+09 | 0.138251E+09 | 91406771.71 | 0.275060E+09 | 0.197515E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.198295E+09 | 0.138251E+09 | 60044475.52 | 0.241714E+09 | 0.197515E+09 |
February | 0.167165E+09 | 0.112055E+09 | 55109791.18 | 0.221002E+09 | 0.151210E+09 |
March | 0.166446E+09 | 86741742.44 | 79704060.20 | 0.240083E+09 | 0.114063E+09 |
April | 0.120636E+09 | 39269464.32 | 81366106.23 | 0.191402E+09 | 92694298.35 |
May | 0.100718E+09 | 11706113.22 | 89011474.34 | 0.166804E+09 | 63674136.46 |
June | 90119995.22 | 5014823.53 | 85105171.69 | 0.174729E+09 | 38488590.99 |
July | 94146554.65 | 7020104.51 | 87126450.14 | 0.192414E+09 | 27448445.19 |
August | 0.112404E+09 | 20997518.03 | 91406771.71 | 0.232049E+09 | 23109757.39 |
September | 0.119629E+09 | 44495913.07 | 75133499.15 | 0.211372E+09 | 53343622.32 |
October | 0.179210E+09 | 0.116092E+09 | 63117399.48 | 0.275060E+09 | 0.112398E+09 |
November | 0.186578E+09 | 0.123810E+09 | 62767874.88 | 0.260460E+09 | 0.138646E+09 |
December | 0.195464E+09 | 0.137511E+09 | 57953675.66 | 0.253180E+09 | 0.168235E+09 |
Annual Sum or Average | 0.173081E+10 | 0.842965E+09 | 0.887847E+09 | 0.266027E+10 | 0.118083E+10 |
Minimum of Months | 90119995.22 | 5014823.53 | 55109791.18 | 0.166804E+09 | 23109757.39 |
Maximum of Months | 0.198295E+09 | 0.138251E+09 | 91406771.71 | 0.275060E+09 | 0.197515E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.198295E+09 | 0.138251E+09 | 60044475.52 | 0.241714E+09 | 0.197515E+09 |
February | 0.167165E+09 | 0.112055E+09 | 55109791.18 | 0.221002E+09 | 0.151210E+09 |
March | 0.166446E+09 | 86741742.44 | 79704060.20 | 0.240083E+09 | 0.114063E+09 |
April | 0.120636E+09 | 39269464.32 | 81366106.23 | 0.191402E+09 | 92694298.35 |
May | 0.100718E+09 | 11706113.22 | 89011474.34 | 0.166804E+09 | 63674136.46 |
June | 90119995.22 | 5014823.53 | 85105171.69 | 0.174729E+09 | 38488590.99 |
July | 94146554.65 | 7020104.51 | 87126450.14 | 0.192414E+09 | 27448445.19 |
August | 0.112404E+09 | 20997518.03 | 91406771.71 | 0.232049E+09 | 23109757.39 |
September | 0.119629E+09 | 44495913.07 | 75133499.15 | 0.211372E+09 | 53343622.32 |
October | 0.179210E+09 | 0.116092E+09 | 63117399.48 | 0.275060E+09 | 0.112398E+09 |
November | 0.186578E+09 | 0.123810E+09 | 62767874.88 | 0.260460E+09 | 0.138646E+09 |
December | 0.195464E+09 | 0.137511E+09 | 57953675.66 | 0.253180E+09 | 0.168235E+09 |
Annual Sum or Average | 0.173081E+10 | 0.842965E+09 | 0.887847E+09 | 0.266027E+10 | 0.118083E+10 |
Minimum of Months | 90119995.22 | 5014823.53 | 55109791.18 | 0.166804E+09 | 23109757.39 |
Maximum of Months | 0.198295E+09 | 0.138251E+09 | 91406771.71 | 0.275060E+09 | 0.197515E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.198295E+09 | 0.138251E+09 | 60044475.52 | 0.241714E+09 | 0.197515E+09 |
February | 0.167165E+09 | 0.112055E+09 | 55109791.18 | 0.221002E+09 | 0.151210E+09 |
March | 0.166446E+09 | 86741742.44 | 79704060.20 | 0.240083E+09 | 0.114063E+09 |
April | 0.120636E+09 | 39269464.32 | 81366106.23 | 0.191402E+09 | 92694298.35 |
May | 0.100718E+09 | 11706113.22 | 89011474.34 | 0.166804E+09 | 63674136.46 |
June | 90119995.22 | 5014823.53 | 85105171.69 | 0.174729E+09 | 38488590.99 |
July | 94146554.65 | 7020104.51 | 87126450.14 | 0.192414E+09 | 27448445.19 |
August | 0.112404E+09 | 20997518.03 | 91406771.71 | 0.232049E+09 | 23109757.39 |
September | 0.119629E+09 | 44495913.07 | 75133499.15 | 0.211372E+09 | 53343622.32 |
October | 0.179210E+09 | 0.116092E+09 | 63117399.48 | 0.275060E+09 | 0.112398E+09 |
November | 0.186578E+09 | 0.123810E+09 | 62767874.88 | 0.260460E+09 | 0.138646E+09 |
December | 0.195464E+09 | 0.137511E+09 | 57953675.66 | 0.253180E+09 | 0.168235E+09 |
Annual Sum or Average | 0.173081E+10 | 0.842965E+09 | 0.887847E+09 | 0.266027E+10 | 0.118083E+10 |
Minimum of Months | 90119995.22 | 5014823.53 | 55109791.18 | 0.166804E+09 | 23109757.39 |
Maximum of Months | 0.198295E+09 | 0.138251E+09 | 91406771.71 | 0.275060E+09 | 0.197515E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.238381E+09 | 0.166199E+09 | 72182703.48 | 0.291714E+09 | 0.234281E+09 |
February | 0.200958E+09 | 0.134708E+09 | 66250453.20 | 0.266545E+09 | 0.179438E+09 |
March | 0.200093E+09 | 0.104277E+09 | 95816550.87 | 0.289356E+09 | 0.135764E+09 |
April | 0.145023E+09 | 47207941.68 | 97814586.08 | 0.230341E+09 | 0.110412E+09 |
May | 0.121078E+09 | 14072550.26 | 0.107005E+09 | 0.200386E+09 | 75984853.91 |
June | 0.108338E+09 | 6028589.92 | 0.102310E+09 | 0.209286E+09 | 46116644.96 |
July | 0.113179E+09 | 8439246.37 | 0.104739E+09 | 0.230380E+09 | 32906893.20 |
August | 0.135127E+09 | 25242249.26 | 0.109885E+09 | 0.277986E+09 | 27800260.60 |
September | 0.143813E+09 | 53490937.69 | 90322032.85 | 0.253747E+09 | 63804499.20 |
October | 0.215437E+09 | 0.139561E+09 | 75876831.16 | 0.330910E+09 | 0.133866E+09 |
November | 0.224295E+09 | 0.148839E+09 | 75456648.77 | 0.313632E+09 | 0.165006E+09 |
December | 0.234978E+09 | 0.165309E+09 | 69669240.16 | 0.305373E+09 | 0.199848E+09 |
Annual Sum or Average | 0.208070E+10 | 0.101337E+10 | 0.106733E+10 | 0.319966E+10 | 0.140523E+10 |
Minimum of Months | 0.108338E+09 | 6028589.92 | 66250453.20 | 0.200386E+09 | 27800260.60 |
Maximum of Months | 0.238381E+09 | 0.166199E+09 | 0.109885E+09 | 0.330910E+09 | 0.234281E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.238381E+09 | 0.166199E+09 | 72182703.48 | 0.291714E+09 | 0.234281E+09 |
February | 0.200958E+09 | 0.134708E+09 | 66250453.20 | 0.266545E+09 | 0.179438E+09 |
March | 0.200093E+09 | 0.104277E+09 | 95816550.87 | 0.289356E+09 | 0.135764E+09 |
April | 0.145023E+09 | 47207941.68 | 97814586.08 | 0.230341E+09 | 0.110412E+09 |
May | 0.121078E+09 | 14072550.26 | 0.107005E+09 | 0.200386E+09 | 75984853.91 |
June | 0.108338E+09 | 6028589.92 | 0.102310E+09 | 0.209286E+09 | 46116644.96 |
July | 0.113179E+09 | 8439246.37 | 0.104739E+09 | 0.230380E+09 | 32906893.20 |
August | 0.135127E+09 | 25242249.26 | 0.109885E+09 | 0.277986E+09 | 27800260.60 |
September | 0.143813E+09 | 53490937.69 | 90322032.85 | 0.253747E+09 | 63804499.20 |
October | 0.215437E+09 | 0.139561E+09 | 75876831.16 | 0.330910E+09 | 0.133866E+09 |
November | 0.224295E+09 | 0.148839E+09 | 75456648.77 | 0.313632E+09 | 0.165006E+09 |
December | 0.234978E+09 | 0.165309E+09 | 69669240.16 | 0.305373E+09 | 0.199848E+09 |
Annual Sum or Average | 0.208070E+10 | 0.101337E+10 | 0.106733E+10 | 0.319966E+10 | 0.140523E+10 |
Minimum of Months | 0.108338E+09 | 6028589.92 | 66250453.20 | 0.200386E+09 | 27800260.60 |
Maximum of Months | 0.238381E+09 | 0.166199E+09 | 0.109885E+09 | 0.330910E+09 | 0.234281E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.198295E+09 | 0.138251E+09 | 60044475.52 | 0.238293E+09 | 0.208807E+09 |
February | 0.167165E+09 | 0.112055E+09 | 55109791.18 | 0.217507E+09 | 0.161482E+09 |
March | 0.166446E+09 | 86741742.44 | 79704060.20 | 0.235844E+09 | 0.122580E+09 |
April | 0.120636E+09 | 39269464.32 | 81366106.23 | 0.188408E+09 | 98077999.22 |
May | 0.100718E+09 | 11706113.22 | 89011474.34 | 0.165608E+09 | 66160855.16 |
June | 90119995.22 | 5014823.53 | 85105171.69 | 0.174895E+09 | 39305225.21 |
July | 94146554.65 | 7020104.51 | 87126450.14 | 0.193023E+09 | 28058987.99 |
August | 0.112404E+09 | 20997518.03 | 91406771.71 | 0.232886E+09 | 23318764.78 |
September | 0.119629E+09 | 44495913.07 | 75133499.15 | 0.211299E+09 | 54000697.53 |
October | 0.179210E+09 | 0.116092E+09 | 63117399.48 | 0.273213E+09 | 0.116774E+09 |
November | 0.186578E+09 | 0.123810E+09 | 62767874.88 | 0.257222E+09 | 0.145958E+09 |
December | 0.195464E+09 | 0.137511E+09 | 57953675.66 | 0.249562E+09 | 0.179426E+09 |
Annual Sum or Average | 0.173081E+10 | 0.842965E+09 | 0.887847E+09 | 0.263776E+10 | 0.124395E+10 |
Minimum of Months | 90119995.22 | 5014823.53 | 55109791.18 | 0.165608E+09 | 23318764.78 |
Maximum of Months | 0.198295E+09 | 0.138251E+09 | 91406771.71 | 0.273213E+09 | 0.208807E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.198295E+09 | 0.138251E+09 | 60044475.52 | 0.238293E+09 | 0.208807E+09 |
February | 0.167165E+09 | 0.112055E+09 | 55109791.18 | 0.217507E+09 | 0.161482E+09 |
March | 0.166446E+09 | 86741742.44 | 79704060.20 | 0.235844E+09 | 0.122580E+09 |
April | 0.120636E+09 | 39269464.32 | 81366106.23 | 0.188408E+09 | 98077999.22 |
May | 0.100718E+09 | 11706113.22 | 89011474.34 | 0.165608E+09 | 66160855.16 |
June | 90119995.22 | 5014823.53 | 85105171.69 | 0.174895E+09 | 39305225.21 |
July | 94146554.65 | 7020104.51 | 87126450.14 | 0.193023E+09 | 28058987.99 |
August | 0.112404E+09 | 20997518.03 | 91406771.71 | 0.232886E+09 | 23318764.78 |
September | 0.119629E+09 | 44495913.07 | 75133499.15 | 0.211299E+09 | 54000697.53 |
October | 0.179210E+09 | 0.116092E+09 | 63117399.48 | 0.273213E+09 | 0.116774E+09 |
November | 0.186578E+09 | 0.123810E+09 | 62767874.88 | 0.257222E+09 | 0.145958E+09 |
December | 0.195464E+09 | 0.137511E+09 | 57953675.66 | 0.249562E+09 | 0.179426E+09 |
Annual Sum or Average | 0.173081E+10 | 0.842965E+09 | 0.887847E+09 | 0.263776E+10 | 0.124395E+10 |
Minimum of Months | 90119995.22 | 5014823.53 | 55109791.18 | 0.165608E+09 | 23318764.78 |
Maximum of Months | 0.198295E+09 | 0.138251E+09 | 91406771.71 | 0.273213E+09 | 0.208807E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_DOOR
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.238381E+09 | 0.166199E+09 | 72182703.48 | 0.287704E+09 | 0.247521E+09 |
February | 0.200958E+09 | 0.134708E+09 | 66250453.20 | 0.262436E+09 | 0.191486E+09 |
March | 0.200093E+09 | 0.104277E+09 | 95816550.87 | 0.284389E+09 | 0.145769E+09 |
April | 0.145023E+09 | 47207941.68 | 97814586.08 | 0.226815E+09 | 0.116746E+09 |
May | 0.121078E+09 | 14072550.26 | 0.107005E+09 | 0.198977E+09 | 78915385.19 |
June | 0.108338E+09 | 6028589.92 | 0.102310E+09 | 0.209482E+09 | 47083695.83 |
July | 0.113179E+09 | 8439246.37 | 0.104739E+09 | 0.231108E+09 | 33630609.84 |
August | 0.135127E+09 | 25242249.26 | 0.109885E+09 | 0.279006E+09 | 28051547.61 |
September | 0.143813E+09 | 53490937.69 | 90322032.85 | 0.253702E+09 | 64576549.20 |
October | 0.215437E+09 | 0.139561E+09 | 75876831.16 | 0.328796E+09 | 0.138996E+09 |
November | 0.224295E+09 | 0.148839E+09 | 75456648.77 | 0.309855E+09 | 0.173579E+09 |
December | 0.234978E+09 | 0.165309E+09 | 69669240.16 | 0.301140E+09 | 0.212943E+09 |
Annual Sum or Average | 0.208070E+10 | 0.101337E+10 | 0.106733E+10 | 0.317341E+10 | 0.147930E+10 |
Minimum of Months | 0.108338E+09 | 6028589.92 | 66250453.20 | 0.198977E+09 | 28051547.61 |
Maximum of Months | 0.238381E+09 | 0.166199E+09 | 0.109885E+09 | 0.328796E+09 | 0.247521E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.198295E+09 | 0.138251E+09 | 60044475.52 | 0.239020E+09 | 0.202681E+09 |
February | 0.167165E+09 | 0.112055E+09 | 55109791.18 | 0.218221E+09 | 0.157203E+09 |
March | 0.166446E+09 | 86741742.44 | 79704060.20 | 0.236588E+09 | 0.120287E+09 |
April | 0.120636E+09 | 39269464.32 | 81366106.23 | 0.188181E+09 | 98817729.69 |
May | 0.100718E+09 | 11706113.22 | 89011474.34 | 0.164867E+09 | 68766601.25 |
June | 90119995.22 | 5014823.53 | 85105171.69 | 0.173138E+09 | 43209748.76 |
July | 94146554.65 | 7020104.51 | 87126450.14 | 0.189900E+09 | 31851629.44 |
August | 0.112404E+09 | 20997518.03 | 91406771.71 | 0.230378E+09 | 27388008.71 |
September | 0.119629E+09 | 44495913.07 | 75133499.15 | 0.210421E+09 | 57678370.32 |
October | 0.179210E+09 | 0.116092E+09 | 63117399.48 | 0.273185E+09 | 0.117372E+09 |
November | 0.186578E+09 | 0.123810E+09 | 62767874.88 | 0.258131E+09 | 0.143612E+09 |
December | 0.195464E+09 | 0.137511E+09 | 57953675.66 | 0.250518E+09 | 0.173680E+09 |
Annual Sum or Average | 0.173081E+10 | 0.842965E+09 | 0.887847E+09 | 0.263255E+10 | 0.124255E+10 |
Minimum of Months | 90119995.22 | 5014823.53 | 55109791.18 | 0.164867E+09 | 27388008.71 |
Maximum of Months | 0.198295E+09 | 0.138251E+09 | 91406771.71 | 0.273185E+09 | 0.202681E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.198295E+09 | 0.138251E+09 | 60044475.52 | 0.239020E+09 | 0.202681E+09 |
February | 0.167165E+09 | 0.112055E+09 | 55109791.18 | 0.218221E+09 | 0.157203E+09 |
March | 0.166446E+09 | 86741742.44 | 79704060.20 | 0.236588E+09 | 0.120287E+09 |
April | 0.120636E+09 | 39269464.32 | 81366106.23 | 0.188181E+09 | 98817729.69 |
May | 0.100718E+09 | 11706113.22 | 89011474.34 | 0.164867E+09 | 68766601.25 |
June | 90119995.22 | 5014823.53 | 85105171.69 | 0.173138E+09 | 43209748.76 |
July | 94146554.65 | 7020104.51 | 87126450.14 | 0.189900E+09 | 31851629.44 |
August | 0.112404E+09 | 20997518.03 | 91406771.71 | 0.230378E+09 | 27388008.71 |
September | 0.119629E+09 | 44495913.07 | 75133499.15 | 0.210421E+09 | 57678370.32 |
October | 0.179210E+09 | 0.116092E+09 | 63117399.48 | 0.273185E+09 | 0.117372E+09 |
November | 0.186578E+09 | 0.123810E+09 | 62767874.88 | 0.258131E+09 | 0.143612E+09 |
December | 0.195464E+09 | 0.137511E+09 | 57953675.66 | 0.250518E+09 | 0.173680E+09 |
Annual Sum or Average | 0.173081E+10 | 0.842965E+09 | 0.887847E+09 | 0.263255E+10 | 0.124255E+10 |
Minimum of Months | 90119995.22 | 5014823.53 | 55109791.18 | 0.164867E+09 | 27388008.71 |
Maximum of Months | 0.198295E+09 | 0.138251E+09 | 91406771.71 | 0.273185E+09 | 0.202681E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_DOOR
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.237079E+09 | 0.165291E+09 | 71788262.47 | 0.287010E+09 | 0.239000E+09 |
February | 0.199860E+09 | 0.133972E+09 | 65888428.86 | 0.261858E+09 | 0.185436E+09 |
March | 0.199000E+09 | 0.103707E+09 | 95292963.16 | 0.283719E+09 | 0.142291E+09 |
April | 0.144230E+09 | 46949974.78 | 97280080.14 | 0.225316E+09 | 0.116958E+09 |
May | 0.120416E+09 | 13995651.08 | 0.106421E+09 | 0.197029E+09 | 81515471.13 |
June | 0.107746E+09 | 5995646.81 | 0.101750E+09 | 0.206306E+09 | 51400121.80 |
July | 0.112560E+09 | 8393130.27 | 0.104167E+09 | 0.226251E+09 | 37918483.03 |
August | 0.134389E+09 | 25104313.47 | 0.109285E+09 | 0.274606E+09 | 32702574.62 |
September | 0.143027E+09 | 53198637.49 | 89828469.83 | 0.251295E+09 | 68520090.40 |
October | 0.214260E+09 | 0.138798E+09 | 75462203.67 | 0.326974E+09 | 0.138910E+09 |
November | 0.223070E+09 | 0.148025E+09 | 75044317.36 | 0.309245E+09 | 0.169874E+09 |
December | 0.233694E+09 | 0.164406E+09 | 69288533.93 | 0.300642E+09 | 0.205072E+09 |
Annual Sum or Average | 0.206933E+10 | 0.100784E+10 | 0.106150E+10 | 0.315025E+10 | 0.146960E+10 |
Minimum of Months | 0.107746E+09 | 5995646.81 | 65888428.86 | 0.197029E+09 | 32702574.62 |
Maximum of Months | 0.237079E+09 | 0.165291E+09 | 0.109285E+09 | 0.326974E+09 | 0.239000E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.198295E+09 | 0.138251E+09 | 60044475.52 | 0.239536E+09 | 0.200025E+09 |
February | 0.167165E+09 | 0.112055E+09 | 55109791.18 | 0.218806E+09 | 0.154826E+09 |
March | 0.166446E+09 | 86741742.44 | 79704060.20 | 0.237311E+09 | 0.118326E+09 |
April | 0.120636E+09 | 39269464.32 | 81366106.23 | 0.188523E+09 | 97878588.04 |
May | 0.100718E+09 | 11706113.22 | 89011474.34 | 0.164984E+09 | 68466053.71 |
June | 90119995.22 | 5014823.53 | 85105171.69 | 0.173078E+09 | 43421755.30 |
July | 94146554.65 | 7020104.51 | 87126450.14 | 0.189767E+09 | 32200648.23 |
August | 0.112404E+09 | 20997518.03 | 91406771.71 | 0.230270E+09 | 27780231.12 |
September | 0.119629E+09 | 44495913.07 | 75133499.15 | 0.210419E+09 | 57717734.06 |
October | 0.179210E+09 | 0.116092E+09 | 63117399.48 | 0.273446E+09 | 0.116356E+09 |
November | 0.186578E+09 | 0.123810E+09 | 62767874.88 | 0.258777E+09 | 0.141700E+09 |
December | 0.195464E+09 | 0.137511E+09 | 57953675.66 | 0.251112E+09 | 0.171193E+09 |
Annual Sum or Average | 0.173081E+10 | 0.842965E+09 | 0.887847E+09 | 0.263603E+10 | 0.122989E+10 |
Minimum of Months | 90119995.22 | 5014823.53 | 55109791.18 | 0.164984E+09 | 27780231.12 |
Maximum of Months | 0.198295E+09 | 0.138251E+09 | 91406771.71 | 0.273446E+09 | 0.200025E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.198295E+09 | 0.138251E+09 | 60044475.52 | 0.239536E+09 | 0.200025E+09 |
February | 0.167165E+09 | 0.112055E+09 | 55109791.18 | 0.218806E+09 | 0.154826E+09 |
March | 0.166446E+09 | 86741742.44 | 79704060.20 | 0.237311E+09 | 0.118326E+09 |
April | 0.120636E+09 | 39269464.32 | 81366106.23 | 0.188523E+09 | 97878588.04 |
May | 0.100718E+09 | 11706113.22 | 89011474.34 | 0.164984E+09 | 68466053.71 |
June | 90119995.22 | 5014823.53 | 85105171.69 | 0.173078E+09 | 43421755.30 |
July | 94146554.65 | 7020104.51 | 87126450.14 | 0.189767E+09 | 32200648.23 |
August | 0.112404E+09 | 20997518.03 | 91406771.71 | 0.230270E+09 | 27780231.12 |
September | 0.119629E+09 | 44495913.07 | 75133499.15 | 0.210419E+09 | 57717734.06 |
October | 0.179210E+09 | 0.116092E+09 | 63117399.48 | 0.273446E+09 | 0.116356E+09 |
November | 0.186578E+09 | 0.123810E+09 | 62767874.88 | 0.258777E+09 | 0.141700E+09 |
December | 0.195464E+09 | 0.137511E+09 | 57953675.66 | 0.251112E+09 | 0.171193E+09 |
Annual Sum or Average | 0.173081E+10 | 0.842965E+09 | 0.887847E+09 | 0.263603E+10 | 0.122989E+10 |
Minimum of Months | 90119995.22 | 5014823.53 | 55109791.18 | 0.164984E+09 | 27780231.12 |
Maximum of Months | 0.198295E+09 | 0.138251E+09 | 91406771.71 | 0.273446E+09 | 0.200025E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_DOOR
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.237079E+09 | 0.165291E+09 | 71788262.47 | 0.287631E+09 | 0.235861E+09 |
February | 0.199860E+09 | 0.133972E+09 | 65888428.86 | 0.262558E+09 | 0.182632E+09 |
March | 0.199000E+09 | 0.103707E+09 | 95292963.16 | 0.284582E+09 | 0.139978E+09 |
April | 0.144230E+09 | 46949974.78 | 97280080.14 | 0.225725E+09 | 0.115851E+09 |
May | 0.120416E+09 | 13995651.08 | 0.106421E+09 | 0.197171E+09 | 81161418.59 |
June | 0.107746E+09 | 5995646.81 | 0.101750E+09 | 0.206235E+09 | 51650551.72 |
July | 0.112560E+09 | 8393130.27 | 0.104167E+09 | 0.226093E+09 | 38331029.05 |
August | 0.134389E+09 | 25104313.47 | 0.109285E+09 | 0.274477E+09 | 33166751.69 |
September | 0.143027E+09 | 53198637.49 | 89828469.83 | 0.251292E+09 | 68566266.64 |
October | 0.214260E+09 | 0.138798E+09 | 75462203.67 | 0.327285E+09 | 0.137709E+09 |
November | 0.223070E+09 | 0.148025E+09 | 75044317.36 | 0.310018E+09 | 0.167618E+09 |
December | 0.233694E+09 | 0.164406E+09 | 69288533.93 | 0.301357E+09 | 0.202137E+09 |
Annual Sum or Average | 0.206933E+10 | 0.100784E+10 | 0.106150E+10 | 0.315442E+10 | 0.145466E+10 |
Minimum of Months | 0.107746E+09 | 5995646.81 | 65888428.86 | 0.197171E+09 | 33166751.69 |
Maximum of Months | 0.237079E+09 | 0.165291E+09 | 0.109285E+09 | 0.327285E+09 | 0.235861E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.198295E+09 | 0.138251E+09 | 60044475.52 | 0.240188E+09 | 0.197699E+09 |
February | 0.167165E+09 | 0.112055E+09 | 55109791.18 | 0.219597E+09 | 0.152414E+09 |
March | 0.166446E+09 | 86741742.44 | 79704060.20 | 0.238444E+09 | 0.115951E+09 |
April | 0.120636E+09 | 39269464.32 | 81366106.23 | 0.189324E+09 | 96208993.96 |
May | 0.100718E+09 | 11706113.22 | 89011474.34 | 0.165477E+09 | 67395987.20 |
June | 90119995.22 | 5014823.53 | 85105171.69 | 0.173419E+09 | 42644815.22 |
July | 94146554.65 | 7020104.51 | 87126450.14 | 0.190092E+09 | 31483976.58 |
August | 0.112404E+09 | 20997518.03 | 91406771.71 | 0.230566E+09 | 27059799.65 |
September | 0.119629E+09 | 44495913.07 | 75133499.15 | 0.210696E+09 | 56896527.73 |
October | 0.179210E+09 | 0.116092E+09 | 63117399.48 | 0.274001E+09 | 0.114765E+09 |
November | 0.186578E+09 | 0.123810E+09 | 62767874.88 | 0.259701E+09 | 0.139527E+09 |
December | 0.195464E+09 | 0.137511E+09 | 57953675.66 | 0.251849E+09 | 0.169017E+09 |
Annual Sum or Average | 0.173081E+10 | 0.842965E+09 | 0.887847E+09 | 0.264335E+10 | 0.121106E+10 |
Minimum of Months | 90119995.22 | 5014823.53 | 55109791.18 | 0.165477E+09 | 27059799.65 |
Maximum of Months | 0.198295E+09 | 0.138251E+09 | 91406771.71 | 0.274001E+09 | 0.197699E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.198295E+09 | 0.138251E+09 | 60044475.52 | 0.240188E+09 | 0.197699E+09 |
February | 0.167165E+09 | 0.112055E+09 | 55109791.18 | 0.219597E+09 | 0.152414E+09 |
March | 0.166446E+09 | 86741742.44 | 79704060.20 | 0.238444E+09 | 0.115951E+09 |
April | 0.120636E+09 | 39269464.32 | 81366106.23 | 0.189324E+09 | 96208993.96 |
May | 0.100718E+09 | 11706113.22 | 89011474.34 | 0.165477E+09 | 67395987.20 |
June | 90119995.22 | 5014823.53 | 85105171.69 | 0.173419E+09 | 42644815.22 |
July | 94146554.65 | 7020104.51 | 87126450.14 | 0.190092E+09 | 31483976.58 |
August | 0.112404E+09 | 20997518.03 | 91406771.71 | 0.230566E+09 | 27059799.65 |
September | 0.119629E+09 | 44495913.07 | 75133499.15 | 0.210696E+09 | 56896527.73 |
October | 0.179210E+09 | 0.116092E+09 | 63117399.48 | 0.274001E+09 | 0.114765E+09 |
November | 0.186578E+09 | 0.123810E+09 | 62767874.88 | 0.259701E+09 | 0.139527E+09 |
December | 0.195464E+09 | 0.137511E+09 | 57953675.66 | 0.251849E+09 | 0.169017E+09 |
Annual Sum or Average | 0.173081E+10 | 0.842965E+09 | 0.887847E+09 | 0.264335E+10 | 0.121106E+10 |
Minimum of Months | 90119995.22 | 5014823.53 | 55109791.18 | 0.165477E+09 | 27059799.65 |
Maximum of Months | 0.198295E+09 | 0.138251E+09 | 91406771.71 | 0.274001E+09 | 0.197699E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_DOOR
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.237079E+09 | 0.165291E+09 | 71788262.47 | 0.288417E+09 | 0.233113E+09 |
February | 0.199860E+09 | 0.133972E+09 | 65888428.86 | 0.263507E+09 | 0.179789E+09 |
March | 0.199000E+09 | 0.103707E+09 | 95292963.16 | 0.285932E+09 | 0.137186E+09 |
April | 0.144230E+09 | 46949974.78 | 97280080.14 | 0.226682E+09 | 0.113889E+09 |
May | 0.120416E+09 | 13995651.08 | 0.106421E+09 | 0.197764E+09 | 79903905.54 |
June | 0.107746E+09 | 5995646.81 | 0.101750E+09 | 0.206644E+09 | 50738145.51 |
July | 0.112560E+09 | 8393130.27 | 0.104167E+09 | 0.226481E+09 | 37489212.23 |
August | 0.134389E+09 | 25104313.47 | 0.109285E+09 | 0.274831E+09 | 32319273.78 |
September | 0.143027E+09 | 53198637.49 | 89828469.83 | 0.251627E+09 | 67600393.62 |
October | 0.214260E+09 | 0.138798E+09 | 75462203.67 | 0.327950E+09 | 0.135837E+09 |
November | 0.223070E+09 | 0.148025E+09 | 75044317.36 | 0.311121E+09 | 0.165056E+09 |
December | 0.233694E+09 | 0.164406E+09 | 69288533.93 | 0.302242E+09 | 0.199571E+09 |
Annual Sum or Average | 0.206933E+10 | 0.100784E+10 | 0.106150E+10 | 0.316320E+10 | 0.143249E+10 |
Minimum of Months | 0.107746E+09 | 5995646.81 | 65888428.86 | 0.197764E+09 | 32319273.78 |
Maximum of Months | 0.237079E+09 | 0.165291E+09 | 0.109285E+09 | 0.327950E+09 | 0.233113E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.198295E+09 | 0.138251E+09 | 60044475.52 | 0.242585E+09 | 0.190979E+09 |
February | 0.167165E+09 | 0.112055E+09 | 55109791.18 | 0.221847E+09 | 0.146397E+09 |
March | 0.166446E+09 | 86741742.44 | 79704060.20 | 0.240954E+09 | 0.110826E+09 |
April | 0.120636E+09 | 39269464.32 | 81366106.23 | 0.191117E+09 | 92235033.86 |
May | 0.100718E+09 | 11706113.22 | 89011474.34 | 0.166247E+09 | 64421935.94 |
June | 90119995.22 | 5014823.53 | 85105171.69 | 0.173512E+09 | 40243635.04 |
July | 94146554.65 | 7020104.51 | 87126450.14 | 0.190166E+09 | 29463089.87 |
August | 0.112404E+09 | 20997518.03 | 91406771.71 | 0.230555E+09 | 24991380.24 |
September | 0.119629E+09 | 44495913.07 | 75133499.15 | 0.210932E+09 | 54655719.96 |
October | 0.179210E+09 | 0.116092E+09 | 63117399.48 | 0.275202E+09 | 0.111222E+09 |
November | 0.186578E+09 | 0.123810E+09 | 62767874.88 | 0.261738E+09 | 0.134811E+09 |
December | 0.195464E+09 | 0.137511E+09 | 57953675.66 | 0.254167E+09 | 0.163462E+09 |
Annual Sum or Average | 0.173081E+10 | 0.842965E+09 | 0.887847E+09 | 0.265902E+10 | 0.116371E+10 |
Minimum of Months | 90119995.22 | 5014823.53 | 55109791.18 | 0.166247E+09 | 24991380.24 |
Maximum of Months | 0.198295E+09 | 0.138251E+09 | 91406771.71 | 0.275202E+09 | 0.190979E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.198295E+09 | 0.138251E+09 | 60044475.52 | 0.242585E+09 | 0.190979E+09 |
February | 0.167165E+09 | 0.112055E+09 | 55109791.18 | 0.221847E+09 | 0.146397E+09 |
March | 0.166446E+09 | 86741742.44 | 79704060.20 | 0.240954E+09 | 0.110826E+09 |
April | 0.120636E+09 | 39269464.32 | 81366106.23 | 0.191117E+09 | 92235033.86 |
May | 0.100718E+09 | 11706113.22 | 89011474.34 | 0.166247E+09 | 64421935.94 |
June | 90119995.22 | 5014823.53 | 85105171.69 | 0.173512E+09 | 40243635.04 |
July | 94146554.65 | 7020104.51 | 87126450.14 | 0.190166E+09 | 29463089.87 |
August | 0.112404E+09 | 20997518.03 | 91406771.71 | 0.230555E+09 | 24991380.24 |
September | 0.119629E+09 | 44495913.07 | 75133499.15 | 0.210932E+09 | 54655719.96 |
October | 0.179210E+09 | 0.116092E+09 | 63117399.48 | 0.275202E+09 | 0.111222E+09 |
November | 0.186578E+09 | 0.123810E+09 | 62767874.88 | 0.261738E+09 | 0.134811E+09 |
December | 0.195464E+09 | 0.137511E+09 | 57953675.66 | 0.254167E+09 | 0.163462E+09 |
Annual Sum or Average | 0.173081E+10 | 0.842965E+09 | 0.887847E+09 | 0.265902E+10 | 0.116371E+10 |
Minimum of Months | 90119995.22 | 5014823.53 | 55109791.18 | 0.166247E+09 | 24991380.24 |
Maximum of Months | 0.198295E+09 | 0.138251E+09 | 91406771.71 | 0.275202E+09 | 0.190979E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.198295E+09 | 0.138251E+09 | 60044475.52 | 0.242585E+09 | 0.190979E+09 |
February | 0.167165E+09 | 0.112055E+09 | 55109791.18 | 0.221847E+09 | 0.146397E+09 |
March | 0.166446E+09 | 86741742.44 | 79704060.20 | 0.240954E+09 | 0.110826E+09 |
April | 0.120636E+09 | 39269464.32 | 81366106.23 | 0.191117E+09 | 92235033.86 |
May | 0.100718E+09 | 11706113.22 | 89011474.34 | 0.166247E+09 | 64421935.94 |
June | 90119995.22 | 5014823.53 | 85105171.69 | 0.173512E+09 | 40243635.04 |
July | 94146554.65 | 7020104.51 | 87126450.14 | 0.190166E+09 | 29463089.87 |
August | 0.112404E+09 | 20997518.03 | 91406771.71 | 0.230555E+09 | 24991380.24 |
September | 0.119629E+09 | 44495913.07 | 75133499.15 | 0.210932E+09 | 54655719.96 |
October | 0.179210E+09 | 0.116092E+09 | 63117399.48 | 0.275202E+09 | 0.111222E+09 |
November | 0.186578E+09 | 0.123810E+09 | 62767874.88 | 0.261738E+09 | 0.134811E+09 |
December | 0.195464E+09 | 0.137511E+09 | 57953675.66 | 0.254167E+09 | 0.163462E+09 |
Annual Sum or Average | 0.173081E+10 | 0.842965E+09 | 0.887847E+09 | 0.265902E+10 | 0.116371E+10 |
Minimum of Months | 90119995.22 | 5014823.53 | 55109791.18 | 0.166247E+09 | 24991380.24 |
Maximum of Months | 0.198295E+09 | 0.138251E+09 | 91406771.71 | 0.275202E+09 | 0.190979E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.198295E+09 | 0.138251E+09 | 60044475.52 | 0.242585E+09 | 0.190979E+09 |
February | 0.167165E+09 | 0.112055E+09 | 55109791.18 | 0.221847E+09 | 0.146397E+09 |
March | 0.166446E+09 | 86741742.44 | 79704060.20 | 0.240954E+09 | 0.110826E+09 |
April | 0.120636E+09 | 39269464.32 | 81366106.23 | 0.191117E+09 | 92235033.86 |
May | 0.100718E+09 | 11706113.22 | 89011474.34 | 0.166247E+09 | 64421935.94 |
June | 90119995.22 | 5014823.53 | 85105171.69 | 0.173512E+09 | 40243635.04 |
July | 94146554.65 | 7020104.51 | 87126450.14 | 0.190166E+09 | 29463089.87 |
August | 0.112404E+09 | 20997518.03 | 91406771.71 | 0.230555E+09 | 24991380.24 |
September | 0.119629E+09 | 44495913.07 | 75133499.15 | 0.210932E+09 | 54655719.96 |
October | 0.179210E+09 | 0.116092E+09 | 63117399.48 | 0.275202E+09 | 0.111222E+09 |
November | 0.186578E+09 | 0.123810E+09 | 62767874.88 | 0.261738E+09 | 0.134811E+09 |
December | 0.195464E+09 | 0.137511E+09 | 57953675.66 | 0.254167E+09 | 0.163462E+09 |
Annual Sum or Average | 0.173081E+10 | 0.842965E+09 | 0.887847E+09 | 0.265902E+10 | 0.116371E+10 |
Minimum of Months | 90119995.22 | 5014823.53 | 55109791.18 | 0.166247E+09 | 24991380.24 |
Maximum of Months | 0.198295E+09 | 0.138251E+09 | 91406771.71 | 0.275202E+09 | 0.190979E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.237079E+09 | 0.165291E+09 | 71788262.47 | 0.291178E+09 | 0.225306E+09 |
February | 0.199860E+09 | 0.133972E+09 | 65888428.86 | 0.266106E+09 | 0.172785E+09 |
March | 0.199000E+09 | 0.103707E+09 | 95292963.16 | 0.288825E+09 | 0.131190E+09 |
April | 0.144230E+09 | 46949974.78 | 97280080.14 | 0.228766E+09 | 0.109237E+09 |
May | 0.120416E+09 | 13995651.08 | 0.106421E+09 | 0.198666E+09 | 76409067.62 |
June | 0.107746E+09 | 5995646.81 | 0.101750E+09 | 0.206765E+09 | 47892812.24 |
July | 0.112560E+09 | 8393130.27 | 0.104167E+09 | 0.226567E+09 | 35080060.80 |
August | 0.134389E+09 | 25104313.47 | 0.109285E+09 | 0.274806E+09 | 29846827.08 |
September | 0.143027E+09 | 53198637.49 | 89828469.83 | 0.251885E+09 | 64942068.92 |
October | 0.214260E+09 | 0.138798E+09 | 75462203.67 | 0.329303E+09 | 0.131690E+09 |
November | 0.223070E+09 | 0.148025E+09 | 75044317.36 | 0.313460E+09 | 0.159535E+09 |
December | 0.233694E+09 | 0.164406E+09 | 69288533.93 | 0.304901E+09 | 0.193107E+09 |
Annual Sum or Average | 0.206933E+10 | 0.100784E+10 | 0.106150E+10 | 0.318123E+10 | 0.137702E+10 |
Minimum of Months | 0.107746E+09 | 5995646.81 | 65888428.86 | 0.198666E+09 | 29846827.08 |
Maximum of Months | 0.237079E+09 | 0.165291E+09 | 0.109285E+09 | 0.329303E+09 | 0.225306E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.237079E+09 | 0.165291E+09 | 71788262.47 | 0.291178E+09 | 0.225306E+09 |
February | 0.199860E+09 | 0.133972E+09 | 65888428.86 | 0.266106E+09 | 0.172785E+09 |
March | 0.199000E+09 | 0.103707E+09 | 95292963.16 | 0.288825E+09 | 0.131190E+09 |
April | 0.144230E+09 | 46949974.78 | 97280080.14 | 0.228766E+09 | 0.109237E+09 |
May | 0.120416E+09 | 13995651.08 | 0.106421E+09 | 0.198666E+09 | 76409067.62 |
June | 0.107746E+09 | 5995646.81 | 0.101750E+09 | 0.206765E+09 | 47892812.24 |
July | 0.112560E+09 | 8393130.27 | 0.104167E+09 | 0.226567E+09 | 35080060.80 |
August | 0.134389E+09 | 25104313.47 | 0.109285E+09 | 0.274806E+09 | 29846827.08 |
September | 0.143027E+09 | 53198637.49 | 89828469.83 | 0.251885E+09 | 64942068.92 |
October | 0.214260E+09 | 0.138798E+09 | 75462203.67 | 0.329303E+09 | 0.131690E+09 |
November | 0.223070E+09 | 0.148025E+09 | 75044317.36 | 0.313460E+09 | 0.159535E+09 |
December | 0.233694E+09 | 0.164406E+09 | 69288533.93 | 0.304901E+09 | 0.193107E+09 |
Annual Sum or Average | 0.206933E+10 | 0.100784E+10 | 0.106150E+10 | 0.318123E+10 | 0.137702E+10 |
Minimum of Months | 0.107746E+09 | 5995646.81 | 65888428.86 | 0.198666E+09 | 29846827.08 |
Maximum of Months | 0.237079E+09 | 0.165291E+09 | 0.109285E+09 | 0.329303E+09 | 0.225306E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.198295E+09 | 0.138251E+09 | 60044475.52 | 0.241616E+09 | 0.191888E+09 |
February | 0.167165E+09 | 0.112055E+09 | 55109791.18 | 0.221178E+09 | 0.146786E+09 |
March | 0.166446E+09 | 86741742.44 | 79704060.20 | 0.240530E+09 | 0.110416E+09 |
April | 0.120636E+09 | 39269464.32 | 81366106.23 | 0.190949E+09 | 91806438.64 |
May | 0.100718E+09 | 11706113.22 | 89011474.34 | 0.166280E+09 | 63929098.91 |
June | 90119995.22 | 5014823.53 | 85105171.69 | 0.173914E+09 | 39569023.09 |
July | 94146554.65 | 7020104.51 | 87126450.14 | 0.190689E+09 | 28748640.91 |
August | 0.112404E+09 | 20997518.03 | 91406771.71 | 0.230999E+09 | 24159495.95 |
September | 0.119629E+09 | 44495913.07 | 75133499.15 | 0.210938E+09 | 54024838.18 |
October | 0.179210E+09 | 0.116092E+09 | 63117399.48 | 0.274792E+09 | 0.110867E+09 |
November | 0.186578E+09 | 0.123810E+09 | 62767874.88 | 0.261320E+09 | 0.134619E+09 |
December | 0.195464E+09 | 0.137511E+09 | 57953675.66 | 0.253355E+09 | 0.163768E+09 |
Annual Sum or Average | 0.173081E+10 | 0.842965E+09 | 0.887847E+09 | 0.265656E+10 | 0.116058E+10 |
Minimum of Months | 90119995.22 | 5014823.53 | 55109791.18 | 0.166280E+09 | 24159495.95 |
Maximum of Months | 0.198295E+09 | 0.138251E+09 | 91406771.71 | 0.274792E+09 | 0.191888E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.198295E+09 | 0.138251E+09 | 60044475.52 | 0.241616E+09 | 0.191888E+09 |
February | 0.167165E+09 | 0.112055E+09 | 55109791.18 | 0.221178E+09 | 0.146786E+09 |
March | 0.166446E+09 | 86741742.44 | 79704060.20 | 0.240530E+09 | 0.110416E+09 |
April | 0.120636E+09 | 39269464.32 | 81366106.23 | 0.190949E+09 | 91806438.64 |
May | 0.100718E+09 | 11706113.22 | 89011474.34 | 0.166280E+09 | 63929098.91 |
June | 90119995.22 | 5014823.53 | 85105171.69 | 0.173914E+09 | 39569023.09 |
July | 94146554.65 | 7020104.51 | 87126450.14 | 0.190689E+09 | 28748640.91 |
August | 0.112404E+09 | 20997518.03 | 91406771.71 | 0.230999E+09 | 24159495.95 |
September | 0.119629E+09 | 44495913.07 | 75133499.15 | 0.210938E+09 | 54024838.18 |
October | 0.179210E+09 | 0.116092E+09 | 63117399.48 | 0.274792E+09 | 0.110867E+09 |
November | 0.186578E+09 | 0.123810E+09 | 62767874.88 | 0.261320E+09 | 0.134619E+09 |
December | 0.195464E+09 | 0.137511E+09 | 57953675.66 | 0.253355E+09 | 0.163768E+09 |
Annual Sum or Average | 0.173081E+10 | 0.842965E+09 | 0.887847E+09 | 0.265656E+10 | 0.116058E+10 |
Minimum of Months | 90119995.22 | 5014823.53 | 55109791.18 | 0.166280E+09 | 24159495.95 |
Maximum of Months | 0.198295E+09 | 0.138251E+09 | 91406771.71 | 0.274792E+09 | 0.191888E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_DOOR
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.237079E+09 | 0.165291E+09 | 71788262.47 | 0.290153E+09 | 0.226258E+09 |
February | 0.199860E+09 | 0.133972E+09 | 65888428.86 | 0.265420E+09 | 0.173160E+09 |
March | 0.199000E+09 | 0.103707E+09 | 95292963.16 | 0.288434E+09 | 0.130666E+09 |
April | 0.144230E+09 | 46949974.78 | 97280080.14 | 0.228638E+09 | 0.108702E+09 |
May | 0.120416E+09 | 13995651.08 | 0.106421E+09 | 0.198753E+09 | 75814676.11 |
June | 0.107746E+09 | 5995646.81 | 0.101750E+09 | 0.207253E+09 | 47101157.99 |
July | 0.112560E+09 | 8393130.27 | 0.104167E+09 | 0.227196E+09 | 34240359.12 |
August | 0.134389E+09 | 25104313.47 | 0.109285E+09 | 0.275357E+09 | 28872584.53 |
September | 0.143027E+09 | 53198637.49 | 89828469.83 | 0.251945E+09 | 64194410.03 |
October | 0.214260E+09 | 0.138798E+09 | 75462203.67 | 0.328917E+09 | 0.131227E+09 |
November | 0.223070E+09 | 0.148025E+09 | 75044317.36 | 0.313068E+09 | 0.159252E+09 |
December | 0.233694E+09 | 0.164406E+09 | 69288533.93 | 0.304066E+09 | 0.193378E+09 |
Annual Sum or Average | 0.206933E+10 | 0.100784E+10 | 0.106150E+10 | 0.317920E+10 | 0.137287E+10 |
Minimum of Months | 0.107746E+09 | 5995646.81 | 65888428.86 | 0.198753E+09 | 28872584.53 |
Maximum of Months | 0.237079E+09 | 0.165291E+09 | 0.109285E+09 | 0.328917E+09 | 0.226258E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.198295E+09 | 0.138251E+09 | 60044475.52 | 0.241812E+09 | 0.191237E+09 |
February | 0.167165E+09 | 0.112055E+09 | 55109791.18 | 0.221444E+09 | 0.146055E+09 |
March | 0.166446E+09 | 86741742.44 | 79704060.20 | 0.241005E+09 | 0.109481E+09 |
April | 0.120636E+09 | 39269464.32 | 81366106.23 | 0.191393E+09 | 91025023.91 |
May | 0.100718E+09 | 11706113.22 | 89011474.34 | 0.166562E+09 | 63486649.56 |
June | 90119995.22 | 5014823.53 | 85105171.69 | 0.174067E+09 | 39350673.69 |
July | 94146554.65 | 7020104.51 | 87126450.14 | 0.190835E+09 | 28560219.14 |
August | 0.112404E+09 | 20997518.03 | 91406771.71 | 0.231127E+09 | 23980286.59 |
September | 0.119629E+09 | 44495913.07 | 75133499.15 | 0.211050E+09 | 53798134.60 |
October | 0.179210E+09 | 0.116092E+09 | 63117399.48 | 0.275033E+09 | 0.110285E+09 |
November | 0.186578E+09 | 0.123810E+09 | 62767874.88 | 0.261681E+09 | 0.133869E+09 |
December | 0.195464E+09 | 0.137511E+09 | 57953675.66 | 0.253606E+09 | 0.163068E+09 |
Annual Sum or Average | 0.173081E+10 | 0.842965E+09 | 0.887847E+09 | 0.265962E+10 | 0.115420E+10 |
Minimum of Months | 90119995.22 | 5014823.53 | 55109791.18 | 0.166562E+09 | 23980286.59 |
Maximum of Months | 0.198295E+09 | 0.138251E+09 | 91406771.71 | 0.275033E+09 | 0.191237E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.198295E+09 | 0.138251E+09 | 60044475.52 | 0.241812E+09 | 0.191237E+09 |
February | 0.167165E+09 | 0.112055E+09 | 55109791.18 | 0.221444E+09 | 0.146055E+09 |
March | 0.166446E+09 | 86741742.44 | 79704060.20 | 0.241005E+09 | 0.109481E+09 |
April | 0.120636E+09 | 39269464.32 | 81366106.23 | 0.191393E+09 | 91025023.91 |
May | 0.100718E+09 | 11706113.22 | 89011474.34 | 0.166562E+09 | 63486649.56 |
June | 90119995.22 | 5014823.53 | 85105171.69 | 0.174067E+09 | 39350673.69 |
July | 94146554.65 | 7020104.51 | 87126450.14 | 0.190835E+09 | 28560219.14 |
August | 0.112404E+09 | 20997518.03 | 91406771.71 | 0.231127E+09 | 23980286.59 |
September | 0.119629E+09 | 44495913.07 | 75133499.15 | 0.211050E+09 | 53798134.60 |
October | 0.179210E+09 | 0.116092E+09 | 63117399.48 | 0.275033E+09 | 0.110285E+09 |
November | 0.186578E+09 | 0.123810E+09 | 62767874.88 | 0.261681E+09 | 0.133869E+09 |
December | 0.195464E+09 | 0.137511E+09 | 57953675.66 | 0.253606E+09 | 0.163068E+09 |
Annual Sum or Average | 0.173081E+10 | 0.842965E+09 | 0.887847E+09 | 0.265962E+10 | 0.115420E+10 |
Minimum of Months | 90119995.22 | 5014823.53 | 55109791.18 | 0.166562E+09 | 23980286.59 |
Maximum of Months | 0.198295E+09 | 0.138251E+09 | 91406771.71 | 0.275033E+09 | 0.191237E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_DOOR
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.237079E+09 | 0.165291E+09 | 71788262.47 | 0.290390E+09 | 0.225489E+09 |
February | 0.199860E+09 | 0.133972E+09 | 65888428.86 | 0.265738E+09 | 0.172295E+09 |
March | 0.199000E+09 | 0.103707E+09 | 95292963.16 | 0.289000E+09 | 0.129562E+09 |
April | 0.144230E+09 | 46949974.78 | 97280080.14 | 0.229169E+09 | 0.107782E+09 |
May | 0.120416E+09 | 13995651.08 | 0.106421E+09 | 0.199092E+09 | 75292826.09 |
June | 0.107746E+09 | 5995646.81 | 0.101750E+09 | 0.207436E+09 | 46842897.38 |
July | 0.112560E+09 | 8393130.27 | 0.104167E+09 | 0.227371E+09 | 34017154.41 |
August | 0.134389E+09 | 25104313.47 | 0.109285E+09 | 0.275510E+09 | 28660522.35 |
September | 0.143027E+09 | 53198637.49 | 89828469.83 | 0.252080E+09 | 63925859.77 |
October | 0.214260E+09 | 0.138798E+09 | 75462203.67 | 0.329205E+09 | 0.130541E+09 |
November | 0.223070E+09 | 0.148025E+09 | 75044317.36 | 0.313499E+09 | 0.158366E+09 |
December | 0.233694E+09 | 0.164406E+09 | 69288533.93 | 0.304369E+09 | 0.192552E+09 |
Annual Sum or Average | 0.206933E+10 | 0.100784E+10 | 0.106150E+10 | 0.318286E+10 | 0.136533E+10 |
Minimum of Months | 0.107746E+09 | 5995646.81 | 65888428.86 | 0.199092E+09 | 28660522.35 |
Maximum of Months | 0.237079E+09 | 0.165291E+09 | 0.109285E+09 | 0.329205E+09 | 0.225489E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.198295E+09 | 0.138251E+09 | 60044475.52 | 0.242517E+09 | 0.188385E+09 |
February | 0.167165E+09 | 0.112055E+09 | 55109791.18 | 0.222190E+09 | 0.143475E+09 |
March | 0.166446E+09 | 86741742.44 | 79704060.20 | 0.242175E+09 | 0.106788E+09 |
April | 0.120636E+09 | 39269464.32 | 81366106.23 | 0.192543E+09 | 88717246.81 |
May | 0.100718E+09 | 11706113.22 | 89011474.34 | 0.167254E+09 | 62190493.75 |
June | 90119995.22 | 5014823.53 | 85105171.69 | 0.174200E+09 | 38954328.41 |
July | 94146554.65 | 7020104.51 | 87126450.14 | 0.190835E+09 | 28358219.72 |
August | 0.112404E+09 | 20997518.03 | 91406771.71 | 0.231061E+09 | 23889071.82 |
September | 0.119629E+09 | 44495913.07 | 75133499.15 | 0.211131E+09 | 53411812.30 |
October | 0.179210E+09 | 0.116092E+09 | 63117399.48 | 0.275580E+09 | 0.108789E+09 |
November | 0.186578E+09 | 0.123810E+09 | 62767874.88 | 0.262537E+09 | 0.131888E+09 |
December | 0.195464E+09 | 0.137511E+09 | 57953675.66 | 0.254359E+09 | 0.160627E+09 |
Annual Sum or Average | 0.173081E+10 | 0.842965E+09 | 0.887847E+09 | 0.266638E+10 | 0.113547E+10 |
Minimum of Months | 90119995.22 | 5014823.53 | 55109791.18 | 0.167254E+09 | 23889071.82 |
Maximum of Months | 0.198295E+09 | 0.138251E+09 | 91406771.71 | 0.275580E+09 | 0.188385E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.198295E+09 | 0.138251E+09 | 60044475.52 | 0.242517E+09 | 0.188385E+09 |
February | 0.167165E+09 | 0.112055E+09 | 55109791.18 | 0.222190E+09 | 0.143475E+09 |
March | 0.166446E+09 | 86741742.44 | 79704060.20 | 0.242175E+09 | 0.106788E+09 |
April | 0.120636E+09 | 39269464.32 | 81366106.23 | 0.192543E+09 | 88717246.81 |
May | 0.100718E+09 | 11706113.22 | 89011474.34 | 0.167254E+09 | 62190493.75 |
June | 90119995.22 | 5014823.53 | 85105171.69 | 0.174200E+09 | 38954328.41 |
July | 94146554.65 | 7020104.51 | 87126450.14 | 0.190835E+09 | 28358219.72 |
August | 0.112404E+09 | 20997518.03 | 91406771.71 | 0.231061E+09 | 23889071.82 |
September | 0.119629E+09 | 44495913.07 | 75133499.15 | 0.211131E+09 | 53411812.30 |
October | 0.179210E+09 | 0.116092E+09 | 63117399.48 | 0.275580E+09 | 0.108789E+09 |
November | 0.186578E+09 | 0.123810E+09 | 62767874.88 | 0.262537E+09 | 0.131888E+09 |
December | 0.195464E+09 | 0.137511E+09 | 57953675.66 | 0.254359E+09 | 0.160627E+09 |
Annual Sum or Average | 0.173081E+10 | 0.842965E+09 | 0.887847E+09 | 0.266638E+10 | 0.113547E+10 |
Minimum of Months | 90119995.22 | 5014823.53 | 55109791.18 | 0.167254E+09 | 23889071.82 |
Maximum of Months | 0.198295E+09 | 0.138251E+09 | 91406771.71 | 0.275580E+09 | 0.188385E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_DOOR
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.237079E+09 | 0.165291E+09 | 71788262.47 | 0.291243E+09 | 0.222124E+09 |
February | 0.199860E+09 | 0.133972E+09 | 65888428.86 | 0.266634E+09 | 0.169256E+09 |
March | 0.199000E+09 | 0.103707E+09 | 95292963.16 | 0.290397E+09 | 0.126394E+09 |
April | 0.144230E+09 | 46949974.78 | 97280080.14 | 0.230542E+09 | 0.105068E+09 |
May | 0.120416E+09 | 13995651.08 | 0.106421E+09 | 0.199918E+09 | 73767681.75 |
June | 0.107746E+09 | 5995646.81 | 0.101750E+09 | 0.207596E+09 | 46380817.20 |
July | 0.112560E+09 | 8393130.27 | 0.104167E+09 | 0.227370E+09 | 33784843.30 |
August | 0.134389E+09 | 25104313.47 | 0.109285E+09 | 0.275430E+09 | 28559110.36 |
September | 0.143027E+09 | 53198637.49 | 89828469.83 | 0.252177E+09 | 63474648.08 |
October | 0.214260E+09 | 0.138798E+09 | 75462203.67 | 0.329857E+09 | 0.128780E+09 |
November | 0.223070E+09 | 0.148025E+09 | 75044317.36 | 0.314520E+09 | 0.156031E+09 |
December | 0.233694E+09 | 0.164406E+09 | 69288533.93 | 0.305274E+09 | 0.189673E+09 |
Annual Sum or Average | 0.206933E+10 | 0.100784E+10 | 0.106150E+10 | 0.319096E+10 | 0.134329E+10 |
Minimum of Months | 0.107746E+09 | 5995646.81 | 65888428.86 | 0.199918E+09 | 28559110.36 |
Maximum of Months | 0.237079E+09 | 0.165291E+09 | 0.109285E+09 | 0.329857E+09 | 0.222124E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.198295E+09 | 0.138251E+09 | 60044475.52 | 0.244909E+09 | 0.176564E+09 |
February | 0.167165E+09 | 0.112055E+09 | 55109791.18 | 0.224120E+09 | 0.133737E+09 |
March | 0.166446E+09 | 86741742.44 | 79704060.20 | 0.244752E+09 | 97766878.60 |
April | 0.120636E+09 | 39269464.32 | 81366106.23 | 0.194947E+09 | 80892311.47 |
May | 0.100718E+09 | 11706113.22 | 89011474.34 | 0.168510E+09 | 57442775.29 |
June | 90119995.22 | 5014823.53 | 85105171.69 | 0.173338E+09 | 37617407.65 |
July | 94146554.65 | 7020104.51 | 87126450.14 | 0.189218E+09 | 27998671.10 |
August | 0.112404E+09 | 20997518.03 | 91406771.71 | 0.229224E+09 | 24194960.91 |
September | 0.119629E+09 | 44495913.07 | 75133499.15 | 0.210394E+09 | 52400145.42 |
October | 0.179210E+09 | 0.116092E+09 | 63117399.48 | 0.276257E+09 | 0.104204E+09 |
November | 0.186578E+09 | 0.123810E+09 | 62767874.88 | 0.264155E+09 | 0.125756E+09 |
December | 0.195464E+09 | 0.137511E+09 | 57953675.66 | 0.256535E+09 | 0.151420E+09 |
Annual Sum or Average | 0.173081E+10 | 0.842965E+09 | 0.887847E+09 | 0.267636E+10 | 0.106999E+10 |
Minimum of Months | 90119995.22 | 5014823.53 | 55109791.18 | 0.168510E+09 | 24194960.91 |
Maximum of Months | 0.198295E+09 | 0.138251E+09 | 91406771.71 | 0.276257E+09 | 0.176564E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.198295E+09 | 0.138251E+09 | 60044475.52 | 0.244909E+09 | 0.176564E+09 |
February | 0.167165E+09 | 0.112055E+09 | 55109791.18 | 0.224120E+09 | 0.133737E+09 |
March | 0.166446E+09 | 86741742.44 | 79704060.20 | 0.244752E+09 | 97766878.60 |
April | 0.120636E+09 | 39269464.32 | 81366106.23 | 0.194947E+09 | 80892311.47 |
May | 0.100718E+09 | 11706113.22 | 89011474.34 | 0.168510E+09 | 57442775.29 |
June | 90119995.22 | 5014823.53 | 85105171.69 | 0.173338E+09 | 37617407.65 |
July | 94146554.65 | 7020104.51 | 87126450.14 | 0.189218E+09 | 27998671.10 |
August | 0.112404E+09 | 20997518.03 | 91406771.71 | 0.229224E+09 | 24194960.91 |
September | 0.119629E+09 | 44495913.07 | 75133499.15 | 0.210394E+09 | 52400145.42 |
October | 0.179210E+09 | 0.116092E+09 | 63117399.48 | 0.276257E+09 | 0.104204E+09 |
November | 0.186578E+09 | 0.123810E+09 | 62767874.88 | 0.264155E+09 | 0.125756E+09 |
December | 0.195464E+09 | 0.137511E+09 | 57953675.66 | 0.256535E+09 | 0.151420E+09 |
Annual Sum or Average | 0.173081E+10 | 0.842965E+09 | 0.887847E+09 | 0.267636E+10 | 0.106999E+10 |
Minimum of Months | 90119995.22 | 5014823.53 | 55109791.18 | 0.168510E+09 | 24194960.91 |
Maximum of Months | 0.198295E+09 | 0.138251E+09 | 91406771.71 | 0.276257E+09 | 0.176564E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_DOOR
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.237079E+09 | 0.165291E+09 | 71788262.47 | 0.294147E+09 | 0.208196E+09 |
February | 0.199860E+09 | 0.133972E+09 | 65888428.86 | 0.268961E+09 | 0.157781E+09 |
March | 0.199000E+09 | 0.103707E+09 | 95292963.16 | 0.293486E+09 | 0.115780E+09 |
April | 0.144230E+09 | 46949974.78 | 97280080.14 | 0.233414E+09 | 95864075.47 |
May | 0.120416E+09 | 13995651.08 | 0.106421E+09 | 0.201414E+09 | 68179838.70 |
June | 0.107746E+09 | 5995646.81 | 0.101750E+09 | 0.206557E+09 | 44811208.20 |
July | 0.112560E+09 | 8393130.27 | 0.104167E+09 | 0.225430E+09 | 33370278.23 |
August | 0.134389E+09 | 25104313.47 | 0.109285E+09 | 0.273224E+09 | 28930832.54 |
September | 0.143027E+09 | 53198637.49 | 89828469.83 | 0.251284E+09 | 62288552.84 |
October | 0.214260E+09 | 0.138798E+09 | 75462203.67 | 0.330663E+09 | 0.123383E+09 |
November | 0.223070E+09 | 0.148025E+09 | 75044317.36 | 0.316461E+09 | 0.148813E+09 |
December | 0.233694E+09 | 0.164406E+09 | 69288533.93 | 0.307904E+09 | 0.178840E+09 |
Annual Sum or Average | 0.206933E+10 | 0.100784E+10 | 0.106150E+10 | 0.320295E+10 | 0.126624E+10 |
Minimum of Months | 0.107746E+09 | 5995646.81 | 65888428.86 | 0.201414E+09 | 28930832.54 |
Maximum of Months | 0.237079E+09 | 0.165291E+09 | 0.109285E+09 | 0.330663E+09 | 0.208196E+09 |
Report: WindowZoneSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 578.81 | 469.91 | 474.14 | 330.57 | 143.57 | 0.00 | 0.00 |
February | 585.77 | 398.36 | 442.53 | 296.64 | 145.89 | 0.00 | 0.00 |
March | 574.61 | 271.72 | 397.99 | 207.41 | 190.58 | 0.00 | 0.00 |
April | 473.11 | 228.24 | 298.07 | 97.03 | 201.04 | 0.00 | 0.00 |
May | 398.74 | 151.83 | 240.83 | 27.99 | 212.83 | 0.00 | 0.00 |
June | 431.13 | 94.98 | 222.67 | 12.39 | 210.28 | 0.00 | 0.00 |
July | 459.38 | 65.56 | 225.11 | 16.79 | 208.33 | 0.00 | 0.00 |
August | 554.12 | 55.27 | 268.77 | 50.21 | 218.56 | 0.00 | 0.00 |
September | 521.98 | 131.55 | 295.58 | 109.94 | 185.64 | 0.00 | 0.00 |
October | 657.88 | 267.82 | 428.51 | 277.59 | 150.92 | 0.00 | 0.00 |
November | 643.94 | 341.28 | 461.00 | 305.91 | 155.09 | 0.00 | 0.00 |
December | 606.13 | 400.48 | 467.37 | 328.80 | 138.57 | 0.00 | 0.00 |
Annual Sum or Average | 540.35 | 238.89 | 351.49 | 171.19 | 180.30 | 0.00 | 0.00 |
Minimum of Months | 398.74 | 55.27 | 222.67 | 12.39 | 138.57 | 0.00 | 0.00 |
Maximum of Months | 657.88 | 469.91 | 474.14 | 330.57 | 218.56 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 285.35 | 248.33 | 237.07 | 165.29 | 71.79 | 0.00 | 0.00 |
February | 288.30 | 212.65 | 221.27 | 148.32 | 72.95 | 0.00 | 0.00 |
March | 282.29 | 145.96 | 198.99 | 103.70 | 95.29 | 0.00 | 0.00 |
April | 232.88 | 120.72 | 149.03 | 48.51 | 100.52 | 0.00 | 0.00 |
May | 197.95 | 78.87 | 120.41 | 14.00 | 106.42 | 0.00 | 0.00 |
June | 215.77 | 48.49 | 111.33 | 6.20 | 105.14 | 0.00 | 0.00 |
July | 230.42 | 33.51 | 112.56 | 8.39 | 104.16 | 0.00 | 0.00 |
August | 278.07 | 27.89 | 134.38 | 25.10 | 109.28 | 0.00 | 0.00 |
September | 260.92 | 66.58 | 147.79 | 54.97 | 92.82 | 0.00 | 0.00 |
October | 326.77 | 139.09 | 214.25 | 138.79 | 75.46 | 0.00 | 0.00 |
November | 318.02 | 179.59 | 230.50 | 152.95 | 77.54 | 0.00 | 0.00 |
December | 298.78 | 213.48 | 233.69 | 164.40 | 69.29 | 0.00 | 0.00 |
Annual Sum or Average | 267.91 | 125.80 | 175.75 | 85.59 | 90.15 | 0.00 | 0.00 |
Minimum of Months | 197.95 | 27.89 | 111.33 | 6.20 | 69.29 | 0.00 | 0.00 |
Maximum of Months | 326.77 | 248.33 | 237.07 | 165.29 | 109.28 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 285.64 | 240.58 | 236.59 | 164.95 | 71.64 | 0.00 | 0.00 |
February | 288.65 | 206.61 | 220.81 | 148.02 | 72.80 | 0.00 | 0.00 |
March | 282.59 | 142.95 | 198.59 | 103.49 | 95.09 | 0.00 | 0.00 |
April | 232.13 | 121.37 | 148.73 | 48.41 | 100.31 | 0.00 | 0.00 |
May | 196.67 | 81.78 | 120.17 | 13.97 | 106.20 | 0.00 | 0.00 |
June | 213.19 | 53.17 | 111.11 | 6.18 | 104.92 | 0.00 | 0.00 |
July | 226.27 | 37.94 | 112.33 | 8.38 | 103.95 | 0.00 | 0.00 |
August | 274.55 | 32.66 | 134.11 | 25.05 | 109.06 | 0.00 | 0.00 |
September | 259.31 | 70.94 | 147.49 | 54.86 | 92.63 | 0.00 | 0.00 |
October | 326.07 | 139.51 | 213.81 | 138.51 | 75.31 | 0.00 | 0.00 |
November | 318.48 | 176.35 | 230.03 | 152.64 | 77.38 | 0.00 | 0.00 |
December | 299.31 | 206.25 | 233.21 | 164.06 | 69.14 | 0.00 | 0.00 |
Annual Sum or Average | 266.85 | 125.40 | 175.39 | 85.42 | 89.97 | 0.00 | 0.00 |
Minimum of Months | 196.67 | 32.66 | 111.11 | 6.18 | 69.14 | 0.00 | 0.00 |
Maximum of Months | 326.07 | 240.58 | 236.59 | 164.95 | 109.06 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 286.25 | 237.42 | 236.59 | 164.95 | 71.64 | 0.00 | 0.00 |
February | 289.42 | 203.49 | 220.81 | 148.02 | 72.80 | 0.00 | 0.00 |
March | 283.45 | 140.62 | 198.59 | 103.49 | 95.09 | 0.00 | 0.00 |
April | 232.55 | 120.22 | 148.73 | 48.41 | 100.31 | 0.00 | 0.00 |
May | 196.81 | 81.43 | 120.17 | 13.97 | 106.20 | 0.00 | 0.00 |
June | 213.11 | 53.43 | 111.11 | 6.18 | 104.92 | 0.00 | 0.00 |
July | 226.12 | 38.36 | 112.33 | 8.38 | 103.95 | 0.00 | 0.00 |
August | 274.42 | 33.13 | 134.11 | 25.05 | 109.06 | 0.00 | 0.00 |
September | 259.31 | 70.99 | 147.49 | 54.86 | 92.63 | 0.00 | 0.00 |
October | 326.38 | 138.30 | 213.81 | 138.51 | 75.31 | 0.00 | 0.00 |
November | 319.28 | 174.00 | 230.03 | 152.64 | 77.38 | 0.00 | 0.00 |
December | 300.02 | 203.30 | 233.21 | 164.06 | 69.14 | 0.00 | 0.00 |
Annual Sum or Average | 267.20 | 124.13 | 175.39 | 85.42 | 89.97 | 0.00 | 0.00 |
Minimum of Months | 196.81 | 33.13 | 111.11 | 6.18 | 69.14 | 0.00 | 0.00 |
Maximum of Months | 326.38 | 237.42 | 236.59 | 164.95 | 109.06 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 287.03 | 234.66 | 236.59 | 164.95 | 71.64 | 0.00 | 0.00 |
February | 290.47 | 200.32 | 220.81 | 148.02 | 72.80 | 0.00 | 0.00 |
March | 284.80 | 137.80 | 198.59 | 103.49 | 95.09 | 0.00 | 0.00 |
April | 233.54 | 118.17 | 148.73 | 48.41 | 100.31 | 0.00 | 0.00 |
May | 197.40 | 80.16 | 120.17 | 13.97 | 106.20 | 0.00 | 0.00 |
June | 213.53 | 52.48 | 111.11 | 6.18 | 104.92 | 0.00 | 0.00 |
July | 226.50 | 37.51 | 112.33 | 8.38 | 103.95 | 0.00 | 0.00 |
August | 274.78 | 32.27 | 134.11 | 25.05 | 109.06 | 0.00 | 0.00 |
September | 259.65 | 69.98 | 147.49 | 54.86 | 92.63 | 0.00 | 0.00 |
October | 327.04 | 136.41 | 213.81 | 138.51 | 75.31 | 0.00 | 0.00 |
November | 320.42 | 171.34 | 230.03 | 152.64 | 77.38 | 0.00 | 0.00 |
December | 300.90 | 200.72 | 233.21 | 164.06 | 69.14 | 0.00 | 0.00 |
Annual Sum or Average | 267.94 | 122.23 | 175.39 | 85.42 | 89.97 | 0.00 | 0.00 |
Minimum of Months | 197.40 | 32.27 | 111.11 | 6.18 | 69.14 | 0.00 | 0.00 |
Maximum of Months | 327.04 | 234.66 | 236.59 | 164.95 | 109.06 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 579.71 | 453.45 | 473.17 | 329.89 | 143.28 | 0.00 | 0.00 |
February | 586.80 | 384.90 | 441.63 | 296.03 | 145.59 | 0.00 | 0.00 |
March | 575.52 | 263.47 | 397.17 | 206.98 | 190.19 | 0.00 | 0.00 |
April | 471.45 | 226.63 | 297.45 | 96.83 | 200.63 | 0.00 | 0.00 |
May | 396.62 | 153.27 | 240.33 | 27.93 | 212.40 | 0.00 | 0.00 |
June | 427.31 | 99.06 | 222.21 | 12.37 | 209.85 | 0.00 | 0.00 |
July | 453.18 | 70.20 | 224.65 | 16.75 | 207.90 | 0.00 | 0.00 |
August | 549.52 | 59.61 | 268.22 | 50.10 | 218.11 | 0.00 | 0.00 |
September | 519.87 | 134.45 | 294.97 | 109.71 | 185.26 | 0.00 | 0.00 |
October | 656.89 | 264.44 | 427.63 | 277.02 | 150.61 | 0.00 | 0.00 |
November | 645.78 | 331.14 | 460.05 | 305.28 | 154.77 | 0.00 | 0.00 |
December | 607.25 | 388.31 | 466.41 | 328.13 | 138.29 | 0.00 | 0.00 |
Annual Sum or Average | 539.02 | 234.93 | 350.77 | 170.84 | 179.93 | 0.00 | 0.00 |
Minimum of Months | 396.62 | 59.61 | 222.21 | 12.37 | 138.29 | 0.00 | 0.00 |
Maximum of Months | 656.89 | 453.45 | 473.17 | 329.89 | 218.11 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 288.75 | 227.76 | 236.59 | 164.95 | 71.64 | 0.00 | 0.00 |
February | 292.57 | 192.93 | 220.81 | 148.02 | 72.80 | 0.00 | 0.00 |
March | 287.30 | 131.23 | 198.59 | 103.49 | 95.09 | 0.00 | 0.00 |
April | 235.55 | 112.78 | 148.73 | 48.41 | 100.31 | 0.00 | 0.00 |
May | 198.37 | 76.04 | 120.17 | 13.97 | 106.20 | 0.00 | 0.00 |
June | 214.15 | 48.70 | 111.11 | 6.18 | 104.92 | 0.00 | 0.00 |
July | 227.22 | 34.25 | 112.33 | 8.38 | 103.95 | 0.00 | 0.00 |
August | 275.30 | 28.82 | 134.11 | 25.05 | 109.06 | 0.00 | 0.00 |
September | 259.96 | 66.45 | 147.49 | 54.86 | 92.63 | 0.00 | 0.00 |
October | 327.99 | 131.78 | 213.81 | 138.51 | 75.31 | 0.00 | 0.00 |
November | 322.42 | 165.31 | 230.03 | 152.64 | 77.38 | 0.00 | 0.00 |
December | 302.71 | 194.49 | 233.21 | 164.06 | 69.14 | 0.00 | 0.00 |
Annual Sum or Average | 269.29 | 117.14 | 175.39 | 85.42 | 89.97 | 0.00 | 0.00 |
Minimum of Months | 198.37 | 28.82 | 111.11 | 6.18 | 69.14 | 0.00 | 0.00 |
Maximum of Months | 327.99 | 227.76 | 236.59 | 164.95 | 109.06 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 288.98 | 226.99 | 236.59 | 164.95 | 71.64 | 0.00 | 0.00 |
February | 292.92 | 191.97 | 220.81 | 148.02 | 72.80 | 0.00 | 0.00 |
March | 287.86 | 130.12 | 198.59 | 103.49 | 95.09 | 0.00 | 0.00 |
April | 236.09 | 111.82 | 148.73 | 48.41 | 100.31 | 0.00 | 0.00 |
May | 198.71 | 75.52 | 120.17 | 13.97 | 106.20 | 0.00 | 0.00 |
June | 214.34 | 48.44 | 111.11 | 6.18 | 104.92 | 0.00 | 0.00 |
July | 227.39 | 34.03 | 112.33 | 8.38 | 103.95 | 0.00 | 0.00 |
August | 275.45 | 28.61 | 134.11 | 25.05 | 109.06 | 0.00 | 0.00 |
September | 260.10 | 66.17 | 147.49 | 54.86 | 92.63 | 0.00 | 0.00 |
October | 328.28 | 131.09 | 213.81 | 138.51 | 75.31 | 0.00 | 0.00 |
November | 322.86 | 164.39 | 230.03 | 152.64 | 77.38 | 0.00 | 0.00 |
December | 303.01 | 193.66 | 233.21 | 164.06 | 69.14 | 0.00 | 0.00 |
Annual Sum or Average | 269.60 | 116.49 | 175.39 | 85.42 | 89.97 | 0.00 | 0.00 |
Minimum of Months | 198.71 | 28.61 | 111.11 | 6.18 | 69.14 | 0.00 | 0.00 |
Maximum of Months | 328.28 | 226.99 | 236.59 | 164.95 | 109.06 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 289.83 | 223.60 | 236.59 | 164.95 | 71.64 | 0.00 | 0.00 |
February | 293.90 | 188.58 | 220.81 | 148.02 | 72.80 | 0.00 | 0.00 |
March | 289.26 | 126.93 | 198.59 | 103.49 | 95.09 | 0.00 | 0.00 |
April | 237.51 | 108.99 | 148.73 | 48.41 | 100.31 | 0.00 | 0.00 |
May | 199.53 | 73.98 | 120.17 | 13.97 | 106.20 | 0.00 | 0.00 |
June | 214.50 | 47.95 | 111.11 | 6.18 | 104.92 | 0.00 | 0.00 |
July | 227.39 | 33.79 | 112.33 | 8.38 | 103.95 | 0.00 | 0.00 |
August | 275.37 | 28.50 | 134.11 | 25.05 | 109.06 | 0.00 | 0.00 |
September | 260.20 | 65.70 | 147.49 | 54.86 | 92.63 | 0.00 | 0.00 |
October | 328.93 | 129.32 | 213.81 | 138.51 | 75.31 | 0.00 | 0.00 |
November | 323.92 | 161.96 | 230.03 | 152.64 | 77.38 | 0.00 | 0.00 |
December | 303.91 | 190.76 | 233.21 | 164.06 | 69.14 | 0.00 | 0.00 |
Annual Sum or Average | 270.29 | 114.61 | 175.39 | 85.42 | 89.97 | 0.00 | 0.00 |
Minimum of Months | 199.53 | 28.50 | 111.11 | 6.18 | 69.14 | 0.00 | 0.00 |
Maximum of Months | 328.93 | 223.60 | 236.59 | 164.95 | 109.06 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 292.70 | 209.57 | 236.59 | 164.95 | 71.64 | 0.00 | 0.00 |
February | 296.46 | 175.78 | 220.81 | 148.02 | 72.80 | 0.00 | 0.00 |
March | 292.33 | 116.23 | 198.59 | 103.49 | 95.09 | 0.00 | 0.00 |
April | 240.47 | 99.40 | 148.73 | 48.41 | 100.31 | 0.00 | 0.00 |
May | 201.03 | 68.35 | 120.17 | 13.97 | 106.20 | 0.00 | 0.00 |
June | 213.44 | 46.31 | 111.11 | 6.18 | 104.92 | 0.00 | 0.00 |
July | 225.46 | 33.37 | 112.33 | 8.38 | 103.95 | 0.00 | 0.00 |
August | 273.18 | 28.87 | 134.11 | 25.05 | 109.06 | 0.00 | 0.00 |
September | 259.29 | 64.46 | 147.49 | 54.86 | 92.63 | 0.00 | 0.00 |
October | 329.74 | 123.88 | 213.81 | 138.51 | 75.31 | 0.00 | 0.00 |
November | 325.92 | 154.45 | 230.03 | 152.64 | 77.38 | 0.00 | 0.00 |
December | 306.52 | 179.84 | 233.21 | 164.06 | 69.14 | 0.00 | 0.00 |
Annual Sum or Average | 271.30 | 108.01 | 175.39 | 85.42 | 89.97 | 0.00 | 0.00 |
Minimum of Months | 201.03 | 28.87 | 111.11 | 6.18 | 69.14 | 0.00 | 0.00 |
Maximum of Months | 329.74 | 209.57 | 236.59 | 164.95 | 109.06 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.155028E+10 | 0.125862E+10 | 0.126994E+10 | 0.885401E+09 | 0.384543E+09 | 0.00 | 0.00 |
February | 0.141709E+10 | 0.963714E+09 | 0.107058E+10 | 0.717638E+09 | 0.352940E+09 | 0.00 | 0.00 |
March | 0.153904E+10 | 0.727777E+09 | 0.106597E+10 | 0.555521E+09 | 0.510449E+09 | 0.00 | 0.00 |
April | 0.122629E+10 | 0.591600E+09 | 0.772587E+09 | 0.251494E+09 | 0.521094E+09 | 0.00 | 0.00 |
May | 0.106799E+10 | 0.406666E+09 | 0.645026E+09 | 74969553.42 | 0.570057E+09 | 0.00 | 0.00 |
June | 0.111748E+10 | 0.246186E+09 | 0.577156E+09 | 32116473.97 | 0.545040E+09 | 0.00 | 0.00 |
July | 0.123042E+10 | 0.175606E+09 | 0.602944E+09 | 44958910.78 | 0.557985E+09 | 0.00 | 0.00 |
August | 0.148417E+10 | 0.148038E+09 | 0.719872E+09 | 0.134475E+09 | 0.585397E+09 | 0.00 | 0.00 |
September | 0.135298E+10 | 0.340982E+09 | 0.766144E+09 | 0.284966E+09 | 0.481178E+09 | 0.00 | 0.00 |
October | 0.176206E+10 | 0.717322E+09 | 0.114771E+10 | 0.743490E+09 | 0.404223E+09 | 0.00 | 0.00 |
November | 0.166910E+10 | 0.884594E+09 | 0.119490E+10 | 0.792917E+09 | 0.401985E+09 | 0.00 | 0.00 |
December | 0.162346E+10 | 0.107263E+10 | 0.125181E+10 | 0.880660E+09 | 0.371153E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.170404E+11 | 0.753374E+10 | 0.110846E+11 | 0.539860E+10 | 0.568604E+10 | 0.00 | 0.00 |
Minimum of Months | 0.106799E+10 | 0.148038E+09 | 0.577156E+09 | 32116473.97 | 0.352940E+09 | 0.00 | 0.00 |
Maximum of Months | 0.176206E+10 | 0.125862E+10 | 0.126994E+10 | 0.885401E+09 | 0.585397E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.764289E+09 | 0.665133E+09 | 0.634972E+09 | 0.442700E+09 | 0.192272E+09 | 0.00 | 0.00 |
February | 0.697449E+09 | 0.514450E+09 | 0.535289E+09 | 0.358819E+09 | 0.176470E+09 | 0.00 | 0.00 |
March | 0.756076E+09 | 0.390927E+09 | 0.532985E+09 | 0.277760E+09 | 0.255225E+09 | 0.00 | 0.00 |
April | 0.603630E+09 | 0.312901E+09 | 0.386294E+09 | 0.125747E+09 | 0.260547E+09 | 0.00 | 0.00 |
May | 0.530193E+09 | 0.211237E+09 | 0.322513E+09 | 37484776.71 | 0.285028E+09 | 0.00 | 0.00 |
June | 0.559270E+09 | 0.125693E+09 | 0.288578E+09 | 16058236.99 | 0.272520E+09 | 0.00 | 0.00 |
July | 0.617152E+09 | 89747439.09 | 0.301472E+09 | 22479455.39 | 0.278992E+09 | 0.00 | 0.00 |
August | 0.744776E+09 | 74687304.26 | 0.359936E+09 | 67237285.33 | 0.292699E+09 | 0.00 | 0.00 |
September | 0.676300E+09 | 0.172577E+09 | 0.383072E+09 | 0.142483E+09 | 0.240589E+09 | 0.00 | 0.00 |
October | 0.875220E+09 | 0.372544E+09 | 0.573857E+09 | 0.371745E+09 | 0.202112E+09 | 0.00 | 0.00 |
November | 0.824299E+09 | 0.465494E+09 | 0.597451E+09 | 0.396458E+09 | 0.200992E+09 | 0.00 | 0.00 |
December | 0.800261E+09 | 0.571793E+09 | 0.625907E+09 | 0.440330E+09 | 0.185577E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.844892E+10 | 0.396718E+10 | 0.554232E+10 | 0.269930E+10 | 0.284302E+10 | 0.00 | 0.00 |
Minimum of Months | 0.530193E+09 | 74687304.26 | 0.288578E+09 | 16058236.99 | 0.176470E+09 | 0.00 | 0.00 |
Maximum of Months | 0.875220E+09 | 0.665133E+09 | 0.634972E+09 | 0.442700E+09 | 0.292699E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.765047E+09 | 0.644359E+09 | 0.633669E+09 | 0.441792E+09 | 0.191877E+09 | 0.00 | 0.00 |
February | 0.698298E+09 | 0.499841E+09 | 0.534191E+09 | 0.358083E+09 | 0.176108E+09 | 0.00 | 0.00 |
March | 0.756893E+09 | 0.382864E+09 | 0.531892E+09 | 0.277191E+09 | 0.254701E+09 | 0.00 | 0.00 |
April | 0.601678E+09 | 0.314593E+09 | 0.385501E+09 | 0.125489E+09 | 0.260012E+09 | 0.00 | 0.00 |
May | 0.526763E+09 | 0.219048E+09 | 0.321852E+09 | 37407877.53 | 0.284444E+09 | 0.00 | 0.00 |
June | 0.552582E+09 | 0.137819E+09 | 0.287986E+09 | 16025293.87 | 0.271961E+09 | 0.00 | 0.00 |
July | 0.606051E+09 | 0.101621E+09 | 0.300853E+09 | 22433339.29 | 0.278420E+09 | 0.00 | 0.00 |
August | 0.735362E+09 | 87478215.03 | 0.359197E+09 | 67099349.54 | 0.292098E+09 | 0.00 | 0.00 |
September | 0.672137E+09 | 0.183877E+09 | 0.382286E+09 | 0.142190E+09 | 0.240095E+09 | 0.00 | 0.00 |
October | 0.873344E+09 | 0.373653E+09 | 0.572679E+09 | 0.370982E+09 | 0.201697E+09 | 0.00 | 0.00 |
November | 0.825506E+09 | 0.457097E+09 | 0.596225E+09 | 0.395645E+09 | 0.200580E+09 | 0.00 | 0.00 |
December | 0.801675E+09 | 0.552429E+09 | 0.624623E+09 | 0.439427E+09 | 0.185196E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.841534E+10 | 0.395468E+10 | 0.553095E+10 | 0.269376E+10 | 0.283719E+10 | 0.00 | 0.00 |
Minimum of Months | 0.526763E+09 | 87478215.03 | 0.287986E+09 | 16025293.87 | 0.176108E+09 | 0.00 | 0.00 |
Maximum of Months | 0.873344E+09 | 0.644359E+09 | 0.633669E+09 | 0.441792E+09 | 0.292098E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.766701E+09 | 0.635910E+09 | 0.633669E+09 | 0.441792E+09 | 0.191877E+09 | 0.00 | 0.00 |
February | 0.700170E+09 | 0.492284E+09 | 0.534191E+09 | 0.358083E+09 | 0.176108E+09 | 0.00 | 0.00 |
March | 0.759203E+09 | 0.376628E+09 | 0.531892E+09 | 0.277191E+09 | 0.254701E+09 | 0.00 | 0.00 |
April | 0.602771E+09 | 0.311608E+09 | 0.385501E+09 | 0.125489E+09 | 0.260012E+09 | 0.00 | 0.00 |
May | 0.527139E+09 | 0.218093E+09 | 0.321852E+09 | 37407877.53 | 0.284444E+09 | 0.00 | 0.00 |
June | 0.552391E+09 | 0.138494E+09 | 0.287986E+09 | 16025293.87 | 0.271961E+09 | 0.00 | 0.00 |
July | 0.605628E+09 | 0.102732E+09 | 0.300853E+09 | 22433339.29 | 0.278420E+09 | 0.00 | 0.00 |
August | 0.735016E+09 | 88727053.18 | 0.359197E+09 | 67099349.54 | 0.292098E+09 | 0.00 | 0.00 |
September | 0.672129E+09 | 0.184002E+09 | 0.382286E+09 | 0.142190E+09 | 0.240095E+09 | 0.00 | 0.00 |
October | 0.874176E+09 | 0.370421E+09 | 0.572679E+09 | 0.370982E+09 | 0.201697E+09 | 0.00 | 0.00 |
November | 0.827573E+09 | 0.451018E+09 | 0.596225E+09 | 0.395645E+09 | 0.200580E+09 | 0.00 | 0.00 |
December | 0.803578E+09 | 0.544521E+09 | 0.624623E+09 | 0.439427E+09 | 0.185196E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.842647E+10 | 0.391444E+10 | 0.553095E+10 | 0.269376E+10 | 0.283719E+10 | 0.00 | 0.00 |
Minimum of Months | 0.527139E+09 | 88727053.18 | 0.287986E+09 | 16025293.87 | 0.176108E+09 | 0.00 | 0.00 |
Maximum of Months | 0.874176E+09 | 0.635910E+09 | 0.633669E+09 | 0.441792E+09 | 0.292098E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.768792E+09 | 0.628509E+09 | 0.633669E+09 | 0.441792E+09 | 0.191877E+09 | 0.00 | 0.00 |
February | 0.702700E+09 | 0.484615E+09 | 0.534191E+09 | 0.358083E+09 | 0.176108E+09 | 0.00 | 0.00 |
March | 0.762819E+09 | 0.369088E+09 | 0.531892E+09 | 0.277191E+09 | 0.254701E+09 | 0.00 | 0.00 |
April | 0.605330E+09 | 0.306306E+09 | 0.385501E+09 | 0.125489E+09 | 0.260012E+09 | 0.00 | 0.00 |
May | 0.528718E+09 | 0.214696E+09 | 0.321852E+09 | 37407877.53 | 0.284444E+09 | 0.00 | 0.00 |
June | 0.553482E+09 | 0.136028E+09 | 0.287986E+09 | 16025293.87 | 0.271961E+09 | 0.00 | 0.00 |
July | 0.606663E+09 | 0.100457E+09 | 0.300853E+09 | 22433339.29 | 0.278420E+09 | 0.00 | 0.00 |
August | 0.735963E+09 | 86438619.58 | 0.359197E+09 | 67099349.54 | 0.292098E+09 | 0.00 | 0.00 |
September | 0.673018E+09 | 0.181393E+09 | 0.382286E+09 | 0.142190E+09 | 0.240095E+09 | 0.00 | 0.00 |
October | 0.875952E+09 | 0.365366E+09 | 0.572679E+09 | 0.370982E+09 | 0.201697E+09 | 0.00 | 0.00 |
November | 0.830523E+09 | 0.444110E+09 | 0.596225E+09 | 0.395645E+09 | 0.200580E+09 | 0.00 | 0.00 |
December | 0.805939E+09 | 0.537603E+09 | 0.624623E+09 | 0.439427E+09 | 0.185196E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.844990E+10 | 0.385461E+10 | 0.553095E+10 | 0.269376E+10 | 0.283719E+10 | 0.00 | 0.00 |
Minimum of Months | 0.528718E+09 | 86438619.58 | 0.287986E+09 | 16025293.87 | 0.176108E+09 | 0.00 | 0.00 |
Maximum of Months | 0.875952E+09 | 0.628509E+09 | 0.633669E+09 | 0.441792E+09 | 0.292098E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.155269E+10 | 0.121452E+10 | 0.126734E+10 | 0.883584E+09 | 0.383754E+09 | 0.00 | 0.00 |
February | 0.141960E+10 | 0.931158E+09 | 0.106838E+10 | 0.716166E+09 | 0.352216E+09 | 0.00 | 0.00 |
March | 0.154146E+10 | 0.705685E+09 | 0.106378E+10 | 0.554381E+09 | 0.509402E+09 | 0.00 | 0.00 |
April | 0.122200E+10 | 0.587413E+09 | 0.771002E+09 | 0.250978E+09 | 0.520025E+09 | 0.00 | 0.00 |
May | 0.106232E+10 | 0.410505E+09 | 0.643703E+09 | 74815755.05 | 0.568887E+09 | 0.00 | 0.00 |
June | 0.110758E+10 | 0.256760E+09 | 0.575972E+09 | 32050587.74 | 0.543922E+09 | 0.00 | 0.00 |
July | 0.121380E+10 | 0.188012E+09 | 0.601707E+09 | 44866678.58 | 0.556840E+09 | 0.00 | 0.00 |
August | 0.147183E+10 | 0.159658E+09 | 0.718395E+09 | 0.134199E+09 | 0.584196E+09 | 0.00 | 0.00 |
September | 0.134750E+10 | 0.348506E+09 | 0.764572E+09 | 0.284381E+09 | 0.480191E+09 | 0.00 | 0.00 |
October | 0.175941E+10 | 0.708266E+09 | 0.114536E+10 | 0.741965E+09 | 0.403394E+09 | 0.00 | 0.00 |
November | 0.167387E+10 | 0.858313E+09 | 0.119245E+10 | 0.791290E+09 | 0.401160E+09 | 0.00 | 0.00 |
December | 0.162647E+10 | 0.104006E+10 | 0.124925E+10 | 0.878853E+09 | 0.370392E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.169985E+11 | 0.740886E+10 | 0.110619E+11 | 0.538753E+10 | 0.567438E+10 | 0.00 | 0.00 |
Minimum of Months | 0.106232E+10 | 0.159658E+09 | 0.575972E+09 | 32050587.74 | 0.352216E+09 | 0.00 | 0.00 |
Maximum of Months | 0.175941E+10 | 0.121452E+10 | 0.126734E+10 | 0.883584E+09 | 0.584196E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.773383E+09 | 0.610031E+09 | 0.633669E+09 | 0.441792E+09 | 0.191877E+09 | 0.00 | 0.00 |
February | 0.707776E+09 | 0.466732E+09 | 0.534191E+09 | 0.358083E+09 | 0.176108E+09 | 0.00 | 0.00 |
March | 0.769493E+09 | 0.351498E+09 | 0.531892E+09 | 0.277191E+09 | 0.254701E+09 | 0.00 | 0.00 |
April | 0.610535E+09 | 0.292314E+09 | 0.385501E+09 | 0.125489E+09 | 0.260012E+09 | 0.00 | 0.00 |
May | 0.531312E+09 | 0.203672E+09 | 0.321852E+09 | 37407877.53 | 0.284444E+09 | 0.00 | 0.00 |
June | 0.555081E+09 | 0.126238E+09 | 0.287986E+09 | 16025293.87 | 0.271961E+09 | 0.00 | 0.00 |
July | 0.608575E+09 | 91737167.30 | 0.300853E+09 | 22433339.29 | 0.278420E+09 | 0.00 | 0.00 |
August | 0.737356E+09 | 77191048.11 | 0.359197E+09 | 67099349.54 | 0.292098E+09 | 0.00 | 0.00 |
September | 0.673821E+09 | 0.172244E+09 | 0.382286E+09 | 0.142190E+09 | 0.240095E+09 | 0.00 | 0.00 |
October | 0.878500E+09 | 0.352959E+09 | 0.572679E+09 | 0.370982E+09 | 0.201697E+09 | 0.00 | 0.00 |
November | 0.835709E+09 | 0.428490E+09 | 0.596225E+09 | 0.395645E+09 | 0.200580E+09 | 0.00 | 0.00 |
December | 0.810774E+09 | 0.520911E+09 | 0.624623E+09 | 0.439427E+09 | 0.185196E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.849231E+10 | 0.369402E+10 | 0.553095E+10 | 0.269376E+10 | 0.283719E+10 | 0.00 | 0.00 |
Minimum of Months | 0.531312E+09 | 77191048.11 | 0.287986E+09 | 16025293.87 | 0.176108E+09 | 0.00 | 0.00 |
Maximum of Months | 0.878500E+09 | 0.610031E+09 | 0.633669E+09 | 0.441792E+09 | 0.292098E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.774012E+09 | 0.607960E+09 | 0.633669E+09 | 0.441792E+09 | 0.191877E+09 | 0.00 | 0.00 |
February | 0.708626E+09 | 0.464403E+09 | 0.534191E+09 | 0.358083E+09 | 0.176108E+09 | 0.00 | 0.00 |
March | 0.771010E+09 | 0.348524E+09 | 0.531892E+09 | 0.277191E+09 | 0.254701E+09 | 0.00 | 0.00 |
April | 0.611954E+09 | 0.289831E+09 | 0.385501E+09 | 0.125489E+09 | 0.260012E+09 | 0.00 | 0.00 |
May | 0.532215E+09 | 0.202266E+09 | 0.321852E+09 | 37407877.53 | 0.284444E+09 | 0.00 | 0.00 |
June | 0.555571E+09 | 0.125544E+09 | 0.287986E+09 | 16025293.87 | 0.271961E+09 | 0.00 | 0.00 |
July | 0.609040E+09 | 91136854.05 | 0.300853E+09 | 22433339.29 | 0.278420E+09 | 0.00 | 0.00 |
August | 0.737763E+09 | 76620491.16 | 0.359197E+09 | 67099349.54 | 0.292098E+09 | 0.00 | 0.00 |
September | 0.674179E+09 | 0.171522E+09 | 0.382286E+09 | 0.142190E+09 | 0.240095E+09 | 0.00 | 0.00 |
October | 0.879269E+09 | 0.351110E+09 | 0.572679E+09 | 0.370982E+09 | 0.201697E+09 | 0.00 | 0.00 |
November | 0.836861E+09 | 0.426104E+09 | 0.596225E+09 | 0.395645E+09 | 0.200580E+09 | 0.00 | 0.00 |
December | 0.811579E+09 | 0.518686E+09 | 0.624623E+09 | 0.439427E+09 | 0.185196E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.850208E+10 | 0.367371E+10 | 0.553095E+10 | 0.269376E+10 | 0.283719E+10 | 0.00 | 0.00 |
Minimum of Months | 0.532215E+09 | 76620491.16 | 0.287986E+09 | 16025293.87 | 0.176108E+09 | 0.00 | 0.00 |
Maximum of Months | 0.879269E+09 | 0.607960E+09 | 0.633669E+09 | 0.441792E+09 | 0.292098E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.776273E+09 | 0.598889E+09 | 0.633669E+09 | 0.441792E+09 | 0.191877E+09 | 0.00 | 0.00 |
February | 0.711012E+09 | 0.456202E+09 | 0.534191E+09 | 0.358083E+09 | 0.176108E+09 | 0.00 | 0.00 |
March | 0.774746E+09 | 0.339969E+09 | 0.531892E+09 | 0.277191E+09 | 0.254701E+09 | 0.00 | 0.00 |
April | 0.615628E+09 | 0.282502E+09 | 0.385501E+09 | 0.125489E+09 | 0.260012E+09 | 0.00 | 0.00 |
May | 0.534426E+09 | 0.198148E+09 | 0.321852E+09 | 37407877.53 | 0.284444E+09 | 0.00 | 0.00 |
June | 0.555996E+09 | 0.124289E+09 | 0.287986E+09 | 16025293.87 | 0.271961E+09 | 0.00 | 0.00 |
July | 0.609039E+09 | 90500604.21 | 0.300853E+09 | 22433339.29 | 0.278420E+09 | 0.00 | 0.00 |
August | 0.737551E+09 | 76336620.38 | 0.359197E+09 | 67099349.54 | 0.292098E+09 | 0.00 | 0.00 |
September | 0.674439E+09 | 0.170298E+09 | 0.382286E+09 | 0.142190E+09 | 0.240095E+09 | 0.00 | 0.00 |
October | 0.881016E+09 | 0.346359E+09 | 0.572679E+09 | 0.370982E+09 | 0.201697E+09 | 0.00 | 0.00 |
November | 0.839593E+09 | 0.419806E+09 | 0.596225E+09 | 0.395645E+09 | 0.200580E+09 | 0.00 | 0.00 |
December | 0.813991E+09 | 0.510927E+09 | 0.624623E+09 | 0.439427E+09 | 0.185196E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.852371E+10 | 0.361423E+10 | 0.553095E+10 | 0.269376E+10 | 0.283719E+10 | 0.00 | 0.00 |
Minimum of Months | 0.534426E+09 | 76336620.38 | 0.287986E+09 | 16025293.87 | 0.176108E+09 | 0.00 | 0.00 |
Maximum of Months | 0.881016E+09 | 0.598889E+09 | 0.633669E+09 | 0.441792E+09 | 0.292098E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.783963E+09 | 0.561322E+09 | 0.633669E+09 | 0.441792E+09 | 0.191877E+09 | 0.00 | 0.00 |
February | 0.717200E+09 | 0.425255E+09 | 0.534191E+09 | 0.358083E+09 | 0.176108E+09 | 0.00 | 0.00 |
March | 0.782989E+09 | 0.311313E+09 | 0.531892E+09 | 0.277191E+09 | 0.254701E+09 | 0.00 | 0.00 |
April | 0.623308E+09 | 0.257648E+09 | 0.385501E+09 | 0.125489E+09 | 0.260012E+09 | 0.00 | 0.00 |
May | 0.538433E+09 | 0.183065E+09 | 0.321852E+09 | 37407877.53 | 0.284444E+09 | 0.00 | 0.00 |
June | 0.553232E+09 | 0.120046E+09 | 0.287986E+09 | 16025293.87 | 0.271961E+09 | 0.00 | 0.00 |
July | 0.603865E+09 | 89366870.32 | 0.300853E+09 | 22433339.29 | 0.278420E+09 | 0.00 | 0.00 |
August | 0.731673E+09 | 77320149.38 | 0.359197E+09 | 67099349.54 | 0.292098E+09 | 0.00 | 0.00 |
September | 0.672071E+09 | 0.167089E+09 | 0.382286E+09 | 0.142190E+09 | 0.240095E+09 | 0.00 | 0.00 |
October | 0.883177E+09 | 0.331789E+09 | 0.572679E+09 | 0.370982E+09 | 0.201697E+09 | 0.00 | 0.00 |
November | 0.844772E+09 | 0.400324E+09 | 0.596225E+09 | 0.395645E+09 | 0.200580E+09 | 0.00 | 0.00 |
December | 0.820972E+09 | 0.481679E+09 | 0.624623E+09 | 0.439427E+09 | 0.185196E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.855565E+10 | 0.340622E+10 | 0.553095E+10 | 0.269376E+10 | 0.283719E+10 | 0.00 | 0.00 |
Minimum of Months | 0.538433E+09 | 77320149.38 | 0.287986E+09 | 16025293.87 | 0.176108E+09 | 0.00 | 0.00 |
Maximum of Months | 0.883177E+09 | 0.561322E+09 | 0.633669E+09 | 0.441792E+09 | 0.292098E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 3.96 | 1.39 | -3.0 | 4.56 | -7.8 | 48.74 | 150.20 | 0.00 |
February | 7.94 | 4.18 | -1.3 | 5.19 | -4.0 | 51.84 | 169.20 | 0.00 |
March | 13.76 | 8.97 | 3.80 | 4.89 | 2.25 | 76.95 | 193.22 | 0.00 |
April | 17.21 | 12.54 | 8.82 | 3.95 | 6.45 | 95.37 | 211.82 | 0.00 |
May | 20.84 | 16.44 | 13.69 | 3.50 | 11.46 | 117.34 | 200.00 | 0.00 |
June | 24.80 | 19.35 | 16.45 | 3.85 | 15.08 | 121.81 | 213.08 | 0.00 |
July | 26.06 | 21.68 | 19.85 | 3.24 | 17.64 | 119.92 | 194.46 | 0.00 |
August | 26.55 | 22.42 | 20.72 | 3.39 | 18.21 | 115.12 | 179.15 | 0.00 |
September | 22.53 | 18.74 | 16.82 | 3.06 | 13.44 | 83.74 | 156.58 | 0.02 |
October | 16.03 | 13.02 | 10.77 | 4.05 | 5.85 | 53.01 | 190.38 | 0.00 |
November | 11.94 | 8.22 | 4.17 | 4.16 | 0.30 | 52.20 | 150.38 | 0.00 |
December | 7.70 | 4.64 | 0.26 | 4.69 | -4.1 | 44.81 | 142.03 | 0.00 |
Annual Sum or Average | 16.65 | 12.68 | 9.31 | 4.04 | 6.29 | 81.91 | 179.25 | 0.00 |
Minimum of Months | 3.96 | 1.39 | -3.0 | 3.06 | -7.8 | 44.81 | 142.03 | 0.00 |
Maximum of Months | 26.55 | 22.42 | 20.72 | 5.19 | 18.21 | 121.81 | 213.08 | 0.02 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 21.10 | 31-JAN-14:00 | 12.97 | 6.70 | 5.70 | 12.22 | 200.50 | 90.50 |
February | 25.00 | 26-FEB-14:00 | 12.75 | 1.70 | 4.10 | 8.15 | 91.50 | 816.00 |
March | 27.80 | 30-MAR-13:00 | 17.87 | 12.20 | 5.70 | 16.30 | 231.50 | 710.50 |
April | 28.90 | 17-APR-14:20 | 16.56 | 8.13 | 2.03 | 13.35 | 125.83 | 887.67 |
May | 30.60 | 19-MAY-13:00 | 18.49 | 11.70 | 4.60 | 15.76 | 140.00 | 875.50 |
June | 34.40 | 06-JUN-14:00 | 22.39 | 17.20 | 8.20 | 22.13 | 251.00 | 561.00 |
July | 36.70 | 08-JUL-14:00 | 23.91 | 18.90 | 2.10 | 24.66 | 274.00 | 567.00 |
August | 35.00 | 01-AUG-14:00 | 23.84 | 19.40 | 2.60 | 26.15 | 306.00 | 508.00 |
September | 31.70 | 07-SEP-15:09 | 23.05 | 19.60 | 4.02 | 22.55 | 218.67 | 591.33 |
October | 30.00 | 10-OCT-15:00 | 20.56 | 16.10 | 3.60 | 17.57 | 97.00 | 561.00 |
November | 24.40 | 05-NOV-15:00 | 17.95 | 14.40 | 2.10 | 14.10 | 117.50 | 361.50 |
December | 22.80 | 12-DEC-14:20 | 16.78 | 13.33 | 5.20 | 13.35 | 144.17 | 433.83 |
Annual Sum or Average | ||||||||
Minimum of Months | 21.10 | 12.75 | 1.70 | 2.03 | 8.15 | 91.50 | 90.50 | |
Maximum of Months | 36.70 | 23.91 | 19.60 | 8.20 | 26.15 | 306.00 | 887.67 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -6.7 | 14-JAN-06:10 | -7.8 | -10.6 | 4.95 | -24.7 | 0.00 | 0.00 |
February | -12.8 | 12-FEB-06:00 | -13.8 | -18.3 | 7.20 | -30.1 | 0.00 | 0.00 |
March | 1.10 | 19-MAR-06:00 | -1.5 | -6.1 | 0.00 | -16.2 | 17.00 | 290.50 |
April | 0.00 | 06-APR-04:00 | -1.1 | -2.8 | 3.10 | -16.5 | 0.00 | 0.00 |
May | 7.80 | 11-MAY-05:00 | 5.45 | 2.80 | 4.10 | -7.8 | 21.50 | 204.50 |
June | 11.10 | 10-JUN-04:00 | 8.73 | 6.70 | 0.00 | -2.5 | 0.00 | 0.00 |
July | 17.20 | 28-JUL-22:00 | 16.88 | 16.70 | 4.10 | 14.28 | 0.00 | 0.00 |
August | 18.30 | 25-AUG-05:00 | 17.20 | 16.70 | 3.60 | 5.13 | 0.00 | 0.00 |
September | 11.70 | 29-SEP-03:00 | 11.07 | 10.60 | 2.60 | -2.3 | 0.00 | 0.00 |
October | 2.20 | 26-OCT-04:00 | 1.95 | 1.70 | 3.10 | -13.4 | 0.00 | 0.00 |
November | -3.3 | 22-NOV-05:00 | -4.0 | -5.6 | 5.20 | -20.2 | 0.00 | 0.00 |
December | -5.6 | 18-DEC-07:00 | -7.3 | -11.7 | 2.60 | -22.7 | 17.00 | 320.50 |
Annual Sum or Average | ||||||||
Minimum of Months | -12.8 | -13.8 | -18.3 | 0.00 | -30.1 | 0.00 | 0.00 | |
Maximum of Months | 18.30 | 17.20 | 16.70 | 7.20 | 14.28 | 21.50 | 320.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 16.51 | 19-JAN-21:00 | 18.30 | 15.60 | 8.80 | 15.21 | 0.00 | 0.00 |
February | 15.81 | 18-FEB-15:00 | 17.20 | 15.00 | 5.20 | 13.91 | 73.00 | 1.00 |
March | 18.16 | 30-MAR-12:30 | 25.85 | 13.85 | 5.45 | 15.39 | 323.00 | 600.00 |
April | 20.01 | 04-APR-13:00 | 25.00 | 17.80 | 9.30 | 18.64 | 307.00 | 197.50 |
May | 22.34 | 30-MAY-17:00 | 27.80 | 20.00 | 4.10 | 21.96 | 97.50 | 79.50 |
June | 24.32 | 23-JUN-11:39 | 31.13 | 21.87 | 4.83 | 22.98 | 338.17 | 565.17 |
July | 25.06 | 07-JUL-11:00 | 33.30 | 22.20 | 3.60 | 20.75 | 116.50 | 900.00 |
August | 25.13 | 19-AUG-16:00 | 30.00 | 23.30 | 3.10 | 23.66 | 197.00 | 136.50 |
September | 24.10 | 09-SEP-10:00 | 30.60 | 21.70 | 2.60 | 21.27 | 236.00 | 482.00 |
October | 23.20 | 18-OCT-15:00 | 25.60 | 22.20 | 5.70 | 23.82 | 159.00 | 2.00 |
November | 18.88 | 19-NOV-14:00 | 24.40 | 16.10 | 8.20 | 13.91 | 143.00 | 384.50 |
December | 17.57 | 13-DEC-10:00 | 19.40 | 16.70 | 4.60 | 14.47 | 227.50 | 77.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 15.81 | 17.20 | 13.85 | 2.60 | 13.91 | 0.00 | 0.00 | |
Maximum of Months | 25.13 | 33.30 | 23.30 | 9.30 | 23.82 | 338.17 | 900.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 15.60 | 19-JAN-17:00 | 17.20 | 16.13 | 6.70 | 14.10 | 0.00 | 0.00 |
February | 15.00 | 18-FEB-16:19 | 17.20 | 15.81 | 5.53 | 13.91 | 50.33 | 1.00 |
March | 16.10 | 31-MAR-10:00 | 21.70 | 18.06 | 13.90 | 18.64 | 268.00 | 8.00 |
April | 17.80 | 04-APR-09:20 | 20.77 | 18.74 | 7.53 | 16.79 | 242.00 | 111.50 |
May | 20.60 | 30-MAY-19:00 | 25.00 | 21.79 | 2.60 | 12.41 | 0.00 | 0.00 |
June | 22.80 | 18-JUN-16:00 | 28.30 | 24.23 | 0.00 | 24.66 | 140.50 | 115.50 |
July | 23.30 | 26-JUL-09:00 | 26.10 | 24.10 | 3.60 | 24.66 | 338.00 | 251.50 |
August | 23.90 | 08-AUG-19:00 | 26.10 | 24.51 | 1.50 | 24.83 | 0.00 | 0.00 |
September | 23.30 | 16-SEP-16:00 | 25.60 | 23.89 | 2.10 | 22.13 | 108.00 | 57.50 |
October | 22.20 | 18-OCT-14:00 | 25.00 | 23.04 | 4.60 | 23.32 | 234.50 | 2.00 |
November | 17.20 | 04-NOV-13:00 | 17.80 | 17.48 | 3.60 | 15.02 | 276.50 | 2.50 |
December | 16.70 | 13-DEC-16:19 | 17.03 | 16.82 | 2.93 | 14.10 | 54.00 | 4.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 15.00 | 17.03 | 15.81 | 0.00 | 12.41 | 0.00 | 0.00 | |
Maximum of Months | 23.90 | 28.30 | 24.51 | 13.90 | 24.83 | 338.00 | 251.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 13.74 | 22.89 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 13.65 | 27.55 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 15.17 | 38.46 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 17.98 | 47.59 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 21.32 | 52.44 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 24.28 | 55.84 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 26.07 | 52.33 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 26.20 | 48.31 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 24.63 | 36.35 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 21.78 | 31.91 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 18.45 | 24.33 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 15.51 | 20.76 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 19.94 | 38.29 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 13.65 | 20.76 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 26.20 | 55.84 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK1
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.346318E+09 | -222158073.4 | 0.00 | 0.00 | 744.00 | 0.00 | -124159786.6 | 58.99 | 0.00 | 0.00 |
February | 0.312388E+09 | -202141202.3 | 0.00 | 0.00 | 672.00 | 0.00 | -110246861.2 | 58.99 | 0.00 | 0.00 |
March | 0.338071E+09 | -219837208.7 | 0.00 | 0.00 | 744.00 | 0.00 | -118234034.7 | 58.99 | 0.00 | 0.00 |
April | 0.308390E+09 | -196548449.9 | 0.00 | 0.00 | 720.00 | 0.00 | -111841714.3 | 58.99 | 0.00 | 0.00 |
May | 0.300393E+09 | -186942556.7 | 0.00 | 0.00 | 744.00 | 0.00 | -113450557.3 | 58.99 | 0.00 | 0.00 |
June | 0.277132E+09 | -168311444.0 | 0.00 | 0.00 | 720.00 | 0.00 | -108820473.0 | 58.99 | 0.00 | 0.00 |
July | 0.273606E+09 | -161586407.0 | 0.00 | 0.00 | 744.00 | 0.00 | -112019384.1 | 58.99 | 0.00 | 0.00 |
August | 0.276182E+09 | -164384542.7 | 0.00 | 0.00 | 744.00 | 0.00 | -111797301.0 | 58.99 | 0.00 | 0.00 |
September | 0.273644E+09 | -164894013.8 | 0.00 | 0.00 | 720.00 | 0.00 | -108750042.3 | 58.99 | 0.00 | 0.00 |
October | 0.297643E+09 | -182723534.2 | 0.00 | 0.00 | 744.00 | 0.00 | -114919301.8 | 58.99 | 0.00 | 0.00 |
November | 0.306194E+09 | -192109804.5 | 0.00 | 0.00 | 720.00 | 0.00 | -114084556.2 | 58.99 | 0.00 | 0.00 |
December | 0.336357E+09 | -213738771.0 | 0.00 | 0.00 | 744.00 | 0.00 | -122618674.3 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.364632E+10 | -0.227538E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.137094E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.273606E+09 | -222158073.4 | 0.00 | 0.00 | 672.00 | 0.00 | -124159786.6 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.346318E+09 | -161586407.0 | 0.00 | 0.00 | 744.00 | 0.00 | -108750042.3 | 58.99 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK2
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.344268E+09 | -222152185.9 | 0.00 | 0.00 | 744.00 | 0.00 | -122116011.5 | 58.99 | 0.00 | 0.00 |
February | 0.310334E+09 | -202138920.9 | 0.00 | 0.00 | 672.00 | 0.00 | -108195006.3 | 58.99 | 0.00 | 0.00 |
March | 0.335925E+09 | -219827879.3 | 0.00 | 0.00 | 744.00 | 0.00 | -116097139.4 | 58.99 | 0.00 | 0.00 |
April | 0.307091E+09 | -196554295.4 | 0.00 | 0.00 | 720.00 | 0.00 | -110536806.2 | 58.99 | 0.00 | 0.00 |
May | 0.299849E+09 | -186949979.7 | 0.00 | 0.00 | 744.00 | 0.00 | -112899325.3 | 58.99 | 0.00 | 0.00 |
June | 0.276915E+09 | -168313894.4 | 0.00 | 0.00 | 720.00 | 0.00 | -108600673.2 | 58.99 | 0.00 | 0.00 |
July | 0.273427E+09 | -161572776.8 | 0.00 | 0.00 | 744.00 | 0.00 | -111854195.1 | 58.99 | 0.00 | 0.00 |
August | 0.276064E+09 | -164394600.1 | 0.00 | 0.00 | 744.00 | 0.00 | -111669862.3 | 58.99 | 0.00 | 0.00 |
September | 0.273461E+09 | -164886396.8 | 0.00 | 0.00 | 720.00 | 0.00 | -108574687.1 | 58.99 | 0.00 | 0.00 |
October | 0.296533E+09 | -182736193.2 | 0.00 | 0.00 | 744.00 | 0.00 | -113797080.5 | 58.99 | 0.00 | 0.00 |
November | 0.304323E+09 | -192109674.1 | 0.00 | 0.00 | 720.00 | 0.00 | -112213385.2 | 58.99 | 0.00 | 0.00 |
December | 0.333835E+09 | -213751149.0 | 0.00 | 0.00 | 744.00 | 0.00 | -120084100.2 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.363203E+10 | -0.227539E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.135664E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.273427E+09 | -222152185.9 | 0.00 | 0.00 | 672.00 | 0.00 | -122116011.5 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.344268E+09 | -161572776.8 | 0.00 | 0.00 | 744.00 | 0.00 | -108195006.3 | 58.99 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK3
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.319172E+09 | -195342775.2 | 0.00 | 0.00 | 744.00 | 0.00 | -123829603.7 | 59.00 | 0.00 | 0.00 |
February | 0.287371E+09 | -177909458.0 | 0.00 | 0.00 | 672.00 | 0.00 | -109461589.9 | 58.99 | 0.00 | 0.00 |
March | 0.313081E+09 | -196189916.6 | 0.00 | 0.00 | 744.00 | 0.00 | -116891235.1 | 58.99 | 0.00 | 0.00 |
April | 0.283160E+09 | -172861429.3 | 0.00 | 0.00 | 720.00 | 0.00 | -110298536.6 | 58.99 | 0.00 | 0.00 |
May | 0.277785E+09 | -165849587.6 | 0.00 | 0.00 | 744.00 | 0.00 | -111935510.9 | 58.99 | 0.00 | 0.00 |
June | 0.256916E+09 | -149883613.7 | 0.00 | 0.00 | 720.00 | 0.00 | -107032673.2 | 58.99 | 0.00 | 0.00 |
July | 0.251182E+09 | -141241910.8 | 0.00 | 0.00 | 744.00 | 0.00 | -109940491.6 | 58.99 | 0.00 | 0.00 |
August | 0.256667E+09 | -146788606.1 | 0.00 | 0.00 | 744.00 | 0.00 | -109877914.2 | 59.01 | 0.00 | 0.00 |
September | 0.252237E+09 | -144937207.8 | 0.00 | 0.00 | 720.00 | 0.00 | -107299671.0 | 58.99 | 0.00 | 0.00 |
October | 0.274355E+09 | -160735210.5 | 0.00 | 0.00 | 744.00 | 0.00 | -113619360.2 | 58.98 | 0.00 | 0.00 |
November | 0.282647E+09 | -169628754.3 | 0.00 | 0.00 | 720.00 | 0.00 | -113018267.6 | 58.99 | 0.00 | 0.00 |
December | 0.308412E+09 | -186575072.4 | 0.00 | 0.00 | 744.00 | 0.00 | -121837268.5 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.336299E+10 | -0.200794E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.135504E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.251182E+09 | -196189916.6 | 0.00 | 0.00 | 672.00 | 0.00 | -123829603.7 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.319172E+09 | -141241910.8 | 0.00 | 0.00 | 744.00 | 0.00 | -107032673.2 | 59.01 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK4
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.319604E+09 | -195356875.0 | 0.00 | 0.00 | 744.00 | 0.00 | -124247237.1 | 58.99 | 0.00 | 0.00 |
February | 0.287799E+09 | -177902654.6 | 0.00 | 0.00 | 672.00 | 0.00 | -109896421.5 | 58.99 | 0.00 | 0.00 |
March | 0.313502E+09 | -196184608.4 | 0.00 | 0.00 | 744.00 | 0.00 | -117317050.2 | 58.99 | 0.00 | 0.00 |
April | 0.283356E+09 | -172875751.9 | 0.00 | 0.00 | 720.00 | 0.00 | -110479913.0 | 58.99 | 0.00 | 0.00 |
May | 0.277843E+09 | -165854609.9 | 0.00 | 0.00 | 744.00 | 0.00 | -111988054.7 | 58.99 | 0.00 | 0.00 |
June | 0.256864E+09 | -149892586.6 | 0.00 | 0.00 | 720.00 | 0.00 | -106971142.2 | 58.99 | 0.00 | 0.00 |
July | 0.251104E+09 | -141268075.2 | 0.00 | 0.00 | 744.00 | 0.00 | -109835539.8 | 58.98 | 0.00 | 0.00 |
August | 0.256590E+09 | -146795594.7 | 0.00 | 0.00 | 744.00 | 0.00 | -109794358.9 | 59.01 | 0.00 | 0.00 |
September | 0.252227E+09 | -144938480.1 | 0.00 | 0.00 | 720.00 | 0.00 | -107288679.3 | 58.99 | 0.00 | 0.00 |
October | 0.274545E+09 | -160739266.2 | 0.00 | 0.00 | 744.00 | 0.00 | -113806114.0 | 58.98 | 0.00 | 0.00 |
November | 0.283043E+09 | -169590337.7 | 0.00 | 0.00 | 720.00 | 0.00 | -113452949.9 | 59.00 | 0.00 | 0.00 |
December | 0.308855E+09 | -186561283.0 | 0.00 | 0.00 | 744.00 | 0.00 | -122293999.1 | 59.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.336533E+10 | -0.200796E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.135737E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.251104E+09 | -196184608.4 | 0.00 | 0.00 | 672.00 | 0.00 | -124247237.1 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.319604E+09 | -141268075.2 | 0.00 | 0.00 | 744.00 | 0.00 | -106971142.2 | 59.01 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK5
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.310485E+09 | -184638146.2 | 0.00 | 0.00 | 744.00 | 0.00 | -125846407.8 | 58.99 | 0.00 | 0.00 |
February | 0.279743E+09 | -168236421.9 | 0.00 | 0.00 | 672.00 | 0.00 | -111506252.4 | 58.99 | 0.00 | 0.00 |
March | 0.304667E+09 | -185618657.4 | 0.00 | 0.00 | 744.00 | 0.00 | -119048618.3 | 59.00 | 0.00 | 0.00 |
April | 0.275389E+09 | -163595947.4 | 0.00 | 0.00 | 720.00 | 0.00 | -111793367.1 | 58.99 | 0.00 | 0.00 |
May | 0.269740E+09 | -156848807.3 | 0.00 | 0.00 | 744.00 | 0.00 | -112890847.2 | 58.99 | 0.00 | 0.00 |
June | 0.249575E+09 | -141856598.7 | 0.00 | 0.00 | 720.00 | 0.00 | -107718016.1 | 58.98 | 0.00 | 0.00 |
July | 0.244150E+09 | -133607102.9 | 0.00 | 0.00 | 744.00 | 0.00 | -110542928.4 | 58.99 | 0.00 | 0.00 |
August | 0.249401E+09 | -138931824.0 | 0.00 | 0.00 | 744.00 | 0.00 | -110469617.9 | 58.99 | 0.00 | 0.00 |
September | 0.245089E+09 | -137197588.4 | 0.00 | 0.00 | 720.00 | 0.00 | -107891199.1 | 58.98 | 0.00 | 0.00 |
October | 0.266827E+09 | -151906554.3 | 0.00 | 0.00 | 744.00 | 0.00 | -114920119.4 | 58.99 | 0.00 | 0.00 |
November | 0.275130E+09 | -160204577.3 | 0.00 | 0.00 | 720.00 | 0.00 | -114925628.5 | 58.99 | 0.00 | 0.00 |
December | 0.300182E+09 | -176451368.2 | 0.00 | 0.00 | 744.00 | 0.00 | -123730628.6 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.327038E+10 | -0.189909E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.137128E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.244150E+09 | -185618657.4 | 0.00 | 0.00 | 672.00 | 0.00 | -125846407.8 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.310485E+09 | -133607102.9 | 0.00 | 0.00 | 744.00 | 0.00 | -107718016.1 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK6
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.310443E+09 | -184640667.8 | 0.00 | 0.00 | 744.00 | 0.00 | -125801922.7 | 58.99 | 0.00 | 0.00 |
February | 0.279764E+09 | -168235973.2 | 0.00 | 0.00 | 672.00 | 0.00 | -111528437.2 | 58.99 | 0.00 | 0.00 |
March | 0.304776E+09 | -185622471.8 | 0.00 | 0.00 | 744.00 | 0.00 | -119153941.5 | 59.00 | 0.00 | 0.00 |
April | 0.275481E+09 | -163595943.6 | 0.00 | 0.00 | 720.00 | 0.00 | -111884849.9 | 58.99 | 0.00 | 0.00 |
May | 0.269818E+09 | -156842323.4 | 0.00 | 0.00 | 744.00 | 0.00 | -112975447.5 | 58.99 | 0.00 | 0.00 |
June | 0.249677E+09 | -141811895.7 | 0.00 | 0.00 | 720.00 | 0.00 | -107865603.1 | 59.00 | 0.00 | 0.00 |
July | 0.244255E+09 | -133582702.6 | 0.00 | 0.00 | 744.00 | 0.00 | -110672436.6 | 58.99 | 0.00 | 0.00 |
August | 0.249525E+09 | -138937850.3 | 0.00 | 0.00 | 744.00 | 0.00 | -110587288.4 | 58.99 | 0.00 | 0.00 |
September | 0.245186E+09 | -137139239.9 | 0.00 | 0.00 | 720.00 | 0.00 | -108046703.8 | 59.00 | 0.00 | 0.00 |
October | 0.266895E+09 | -151904190.7 | 0.00 | 0.00 | 744.00 | 0.00 | -114991149.2 | 58.99 | 0.00 | 0.00 |
November | 0.275217E+09 | -160203439.8 | 0.00 | 0.00 | 720.00 | 0.00 | -115013544.6 | 58.99 | 0.00 | 0.00 |
December | 0.300192E+09 | -176448628.8 | 0.00 | 0.00 | 744.00 | 0.00 | -123743311.0 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.327123E+10 | -0.189897E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.137226E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.244255E+09 | -185622471.8 | 0.00 | 0.00 | 672.00 | 0.00 | -125801922.7 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.310443E+09 | -133582702.6 | 0.00 | 0.00 | 744.00 | 0.00 | -107865603.1 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK7
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.310548E+09 | -184638336.1 | 0.00 | 0.00 | 744.00 | 0.00 | -125909461.5 | 58.99 | 0.00 | 0.00 |
February | 0.279896E+09 | -168235456.7 | 0.00 | 0.00 | 672.00 | 0.00 | -111660399.1 | 58.99 | 0.00 | 0.00 |
March | 0.304968E+09 | -185654486.8 | 0.00 | 0.00 | 744.00 | 0.00 | -119313834.5 | 58.99 | 0.00 | 0.00 |
April | 0.275658E+09 | -163575331.4 | 0.00 | 0.00 | 720.00 | 0.00 | -112082196.5 | 59.00 | 0.00 | 0.00 |
May | 0.269914E+09 | -156841133.9 | 0.00 | 0.00 | 744.00 | 0.00 | -113072971.4 | 58.99 | 0.00 | 0.00 |
June | 0.249723E+09 | -141864919.2 | 0.00 | 0.00 | 720.00 | 0.00 | -107857997.2 | 58.98 | 0.00 | 0.00 |
July | 0.244306E+09 | -133594534.2 | 0.00 | 0.00 | 744.00 | 0.00 | -110711485.5 | 58.99 | 0.00 | 0.00 |
August | 0.249563E+09 | -138940085.0 | 0.00 | 0.00 | 744.00 | 0.00 | -110622867.8 | 58.99 | 0.00 | 0.00 |
September | 0.245211E+09 | -137182032.5 | 0.00 | 0.00 | 720.00 | 0.00 | -108029112.9 | 58.98 | 0.00 | 0.00 |
October | 0.267027E+09 | -151909983.2 | 0.00 | 0.00 | 744.00 | 0.00 | -115117033.0 | 58.99 | 0.00 | 0.00 |
November | 0.275379E+09 | -160199633.0 | 0.00 | 0.00 | 720.00 | 0.00 | -115179407.5 | 58.99 | 0.00 | 0.00 |
December | 0.300308E+09 | -176441997.9 | 0.00 | 0.00 | 744.00 | 0.00 | -123866401.8 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.327250E+10 | -0.189908E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.137342E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.244306E+09 | -185654486.8 | 0.00 | 0.00 | 672.00 | 0.00 | -125909461.5 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.310548E+09 | -133594534.2 | 0.00 | 0.00 | 744.00 | 0.00 | -107857997.2 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 290.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 263.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 351.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 369.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 407.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 411.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 411.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 390.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 298.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 293.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 299.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 285.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4071.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 263.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 411.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 HEATING COIL
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.128994E+11 | 57296.53 | 02-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.738385E+10 | 57296.53 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.113788E+10 | 57296.53 | 18-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.196776E+09 | 57296.53 | 06-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.131216E+09 | 37474.04 | 26-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.128493E+10 | 57296.53 | 21-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.581796E+10 | 57296.53 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.288520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.128994E+11 | 57296.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 HEATING COIL
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.396328E+10 | 29994.01 | 02-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.222433E+10 | 29994.01 | 02-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.213319E+09 | 22232.14 | 23-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 17228524.50 | 4758.42 | 07-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 10454241.69 | 2629.18 | 26-OCT-08:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.230710E+09 | 29994.01 | 22-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.128702E+10 | 29994.01 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.794634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.396328E+10 | 29994.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3 HEATING COIL
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.494780E+10 | 30087.49 | 02-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.274862E+10 | 30087.49 | 03-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.347731E+09 | 15384.04 | 19-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 43790014.26 | 6389.13 | 06-APR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 32790658.99 | 4632.27 | 26-OCT-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.413765E+09 | 30087.49 | 22-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.199924E+10 | 30087.49 | 02-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.105337E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.494780E+10 | 30087.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4 HEATING COIL
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.516039E+10 | 30163.95 | 01-JAN-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.286734E+10 | 30163.95 | 03-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.396874E+09 | 19699.55 | 19-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 48966155.79 | 5672.67 | 06-APR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 47110157.59 | 6812.17 | 26-OCT-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.472558E+09 | 30163.95 | 22-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.217493E+10 | 30163.95 | 02-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.111682E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.516039E+10 | 30163.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5 HEATING COIL
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.550228E+10 | 29934.43 | 01-JAN-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.308522E+10 | 29934.43 | 03-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.483871E+09 | 24092.50 | 19-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 64045397.31 | 4807.93 | 07-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 73527136.59 | 6428.14 | 26-OCT-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.568829E+09 | 29934.43 | 22-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.244621E+10 | 29934.43 | 02-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.122240E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.550228E+10 | 29934.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6 HEATING COIL
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.107409E+11 | 54104.70 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.606666E+10 | 54104.70 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.108557E+10 | 54104.70 | 18-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.127411E+09 | 54104.70 | 06-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.212995E+09 | 34187.33 | 26-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.126586E+10 | 54104.70 | 21-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.501437E+10 | 54104.70 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.245138E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.107409E+11 | 54104.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7 HEATING COIL
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.560985E+10 | 27840.45 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.317784E+10 | 27840.45 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.576259E+09 | 27840.45 | 18-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 68430212.19 | 27840.45 | 06-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.112357E+09 | 18192.26 | 26-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.659736E+09 | 27840.45 | 21-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.262565E+10 | 27840.45 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.128301E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.560985E+10 | 27840.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8 HEATING COIL
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.568864E+10 | 27733.55 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.323320E+10 | 27733.55 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.618181E+09 | 27733.55 | 07-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 77691728.22 | 27733.55 | 06-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.123175E+09 | 20536.91 | 26-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.689361E+09 | 27733.55 | 21-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.269744E+10 | 27733.55 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.131277E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.568864E+10 | 27733.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9 HEATING COIL
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.605142E+10 | 27744.64 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.347986E+10 | 27744.64 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.763606E+09 | 27744.64 | 03-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115072E+09 | 27744.64 | 06-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.156793E+09 | 27744.64 | 26-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.790709E+09 | 27744.64 | 21-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.296970E+10 | 27744.64 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.143272E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.605142E+10 | 27744.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10 HEATING COIL
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.755950E+10 | 30654.89 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.458104E+10 | 30654.89 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.125738E+10 | 30654.89 | 02-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.282287E+09 | 30654.89 | 06-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2780856.24 | 3708.30 | 11-MAY-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.267117E+09 | 30654.89 | 26-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.110269E+10 | 30654.89 | 14-NOV-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.383620E+10 | 30654.89 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.188890E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.755950E+10 | 30654.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.394488E+09 | 0.394083E+09 | 7535.05 | 26-FEB-15:10 | 7535.05 | 0.00 |
March | 0.00 | 0.00 | 0.181459E+10 | 0.144105E+10 | 14908.29 | 30-MAR-16:10 | 12830.81 | 0.00 |
April | 0.00 | 0.00 | 0.592788E+10 | 0.483778E+10 | 14123.21 | 17-APR-16:40 | 13264.28 | 0.00 |
May | 0.00 | 0.00 | 0.141995E+11 | 0.103551E+11 | 20966.85 | 30-MAY-17:00 | 13719.69 | 0.00 |
June | 0.00 | 0.00 | 0.263593E+11 | 0.182106E+11 | 50521.76 | 26-JUN-07:02 | 30452.32 | 0.00 |
July | 0.00 | 0.00 | 0.327673E+11 | 0.211476E+11 | 51528.38 | 27-JUL-07:03 | 26929.31 | 0.00 |
August | 0.00 | 0.00 | 0.359565E+11 | 0.224971E+11 | 51628.64 | 12-AUG-07:02 | 27176.22 | 0.00 |
September | 0.00 | 0.00 | 0.211613E+11 | 0.138986E+11 | 51301.33 | 17-SEP-07:02 | 27718.47 | 0.00 |
October | 0.00 | 0.00 | 0.734709E+10 | 0.503350E+10 | 47524.25 | 19-OCT-07:03 | 19871.82 | 0.00 |
November | 0.00 | 0.00 | 0.105082E+10 | 0.740475E+09 | 14068.39 | 05-NOV-16:07 | 10112.37 | 0.00 |
December | 0.00 | 0.00 | 68419920.76 | 48629141.01 | 6063.73 | 12-DEC-14:20 | 4266.87 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.147047E+12 | 0.986045E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.359565E+11 | 0.224971E+11 | 51628.64 | 30452.32 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 2772405.14 | 2187212.11 | 1324.00 | 31-JAN-22:50 | 1084.13 | 0.00 |
February | 0.00 | 0.00 | 0.353031E+09 | 0.350935E+09 | 22869.82 | 26-FEB-18:37 | 22869.82 | 0.00 |
March | 0.00 | 0.00 | 0.133450E+10 | 0.107794E+10 | 24216.90 | 04-MAR-19:30 | 18272.58 | 0.00 |
April | 0.00 | 0.00 | 0.424114E+10 | 0.344945E+10 | 25337.50 | 22-APR-18:02 | 13345.76 | 0.00 |
May | 0.00 | 0.00 | 0.856317E+10 | 0.638980E+10 | 25670.74 | 25-MAY-20:02 | 12438.67 | 0.00 |
June | 0.00 | 0.00 | 0.138518E+11 | 0.990761E+10 | 25576.85 | 29-JUN-07:03 | 18577.08 | 0.00 |
July | 0.00 | 0.00 | 0.166139E+11 | 0.110631E+11 | 26030.52 | 27-JUL-07:03 | 17453.08 | 0.00 |
August | 0.00 | 0.00 | 0.179330E+11 | 0.116388E+11 | 26111.18 | 23-AUG-07:02 | 17490.59 | 0.00 |
September | 0.00 | 0.00 | 0.113186E+11 | 0.771423E+10 | 25969.35 | 17-SEP-07:02 | 17505.01 | 0.00 |
October | 0.00 | 0.00 | 0.436955E+10 | 0.311730E+10 | 26016.48 | 19-OCT-07:03 | 11790.91 | 0.00 |
November | 0.00 | 0.00 | 0.871535E+09 | 0.630857E+09 | 25024.17 | 04-NOV-18:02 | 13963.75 | 0.00 |
December | 0.00 | 0.00 | 71589185.82 | 50850757.94 | 4125.36 | 12-DEC-14:00 | 2857.04 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.795246E+11 | 0.553931E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 2772405.14 | 2187212.11 | 1324.00 | 1084.13 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.179330E+11 | 0.116388E+11 | 26111.18 | 22869.82 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3 COOLING COIL
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.210140E+09 | 0.210076E+09 | 4217.65 | 28-FEB-15:10 | 4217.65 | 0.00 |
March | 0.00 | 0.00 | 0.835683E+09 | 0.669587E+09 | 7943.26 | 30-MAR-14:00 | 6545.83 | 0.00 |
April | 0.00 | 0.00 | 0.273993E+10 | 0.228726E+10 | 7383.89 | 17-APR-14:00 | 6887.05 | 0.00 |
May | 0.00 | 0.00 | 0.598973E+10 | 0.443566E+10 | 14447.27 | 31-MAY-06:03 | 6583.97 | 0.00 |
June | 0.00 | 0.00 | 0.108474E+11 | 0.755419E+10 | 26731.07 | 23-JUN-06:03 | 15461.31 | 0.00 |
July | 0.00 | 0.00 | 0.129623E+11 | 0.838869E+10 | 27258.02 | 27-JUL-06:02 | 14023.44 | 0.00 |
August | 0.00 | 0.00 | 0.144440E+11 | 0.911415E+10 | 27654.29 | 21-AUG-06:02 | 13152.63 | 0.00 |
September | 0.00 | 0.00 | 0.843351E+10 | 0.562841E+10 | 27577.65 | 17-SEP-07:02 | 12882.94 | 0.00 |
October | 0.00 | 0.00 | 0.297783E+10 | 0.208178E+10 | 26610.76 | 19-OCT-06:03 | 10679.27 | 0.00 |
November | 0.00 | 0.00 | 0.449806E+09 | 0.332609E+09 | 6700.27 | 05-NOV-14:00 | 4434.74 | 0.00 |
December | 0.00 | 0.00 | 39872206.92 | 28341871.75 | 3504.26 | 12-DEC-14:00 | 2422.36 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.599302E+11 | 0.407308E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.144440E+11 | 0.911415E+10 | 27654.29 | 15461.31 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4 COOLING COIL
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.191072E+09 | 0.191021E+09 | 4063.25 | 28-FEB-15:10 | 4063.25 | 0.00 |
March | 0.00 | 0.00 | 0.789650E+09 | 0.632680E+09 | 7834.28 | 30-MAR-14:00 | 6450.75 | 0.00 |
April | 0.00 | 0.00 | 0.268058E+10 | 0.223888E+10 | 7356.43 | 17-APR-14:00 | 6862.96 | 0.00 |
May | 0.00 | 0.00 | 0.594260E+10 | 0.440139E+10 | 14333.50 | 31-MAY-06:03 | 6528.77 | 0.00 |
June | 0.00 | 0.00 | 0.108694E+11 | 0.757304E+10 | 26799.03 | 23-JUN-06:03 | 15519.85 | 0.00 |
July | 0.00 | 0.00 | 0.130084E+11 | 0.842703E+10 | 27326.25 | 27-JUL-06:02 | 14070.84 | 0.00 |
August | 0.00 | 0.00 | 0.144940E+11 | 0.915315E+10 | 27728.61 | 21-AUG-06:02 | 13251.88 | 0.00 |
September | 0.00 | 0.00 | 0.843058E+10 | 0.562866E+10 | 27643.33 | 17-SEP-07:02 | 12907.74 | 0.00 |
October | 0.00 | 0.00 | 0.293325E+10 | 0.204829E+10 | 26674.56 | 19-OCT-06:03 | 10699.56 | 0.00 |
November | 0.00 | 0.00 | 0.401729E+09 | 0.297028E+09 | 6547.30 | 05-NOV-14:00 | 4324.77 | 0.00 |
December | 0.00 | 0.00 | 32777106.30 | 23422024.97 | 3190.25 | 12-DEC-14:00 | 2203.82 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.597740E+11 | 0.406146E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.144940E+11 | 0.915315E+10 | 27728.61 | 15519.85 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5 COOLING COIL
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.163601E+09 | 0.163563E+09 | 3765.83 | 28-FEB-15:10 | 3765.83 | 0.00 |
March | 0.00 | 0.00 | 0.705501E+09 | 0.565176E+09 | 7544.90 | 30-MAR-14:00 | 6191.26 | 0.00 |
April | 0.00 | 0.00 | 0.251631E+10 | 0.210101E+10 | 7161.27 | 17-APR-14:00 | 6672.29 | 0.00 |
May | 0.00 | 0.00 | 0.569873E+10 | 0.421266E+10 | 11815.12 | 31-MAY-06:03 | 5343.58 | 0.00 |
June | 0.00 | 0.00 | 0.106168E+11 | 0.737130E+10 | 26595.91 | 23-JUN-06:03 | 15257.50 | 0.00 |
July | 0.00 | 0.00 | 0.127638E+11 | 0.824443E+10 | 27121.62 | 27-JUL-06:02 | 13822.03 | 0.00 |
August | 0.00 | 0.00 | 0.142452E+11 | 0.896270E+10 | 27522.33 | 21-AUG-06:02 | 13051.40 | 0.00 |
September | 0.00 | 0.00 | 0.820542E+10 | 0.545923E+10 | 27437.02 | 17-SEP-07:02 | 12663.19 | 0.00 |
October | 0.00 | 0.00 | 0.279145E+10 | 0.193968E+10 | 26482.40 | 19-OCT-06:03 | 10581.76 | 0.00 |
November | 0.00 | 0.00 | 0.330913E+09 | 0.243978E+09 | 6214.72 | 05-NOV-14:00 | 4079.98 | 0.00 |
December | 0.00 | 0.00 | 25596442.81 | 18305503.58 | 2744.31 | 12-DEC-14:00 | 1891.43 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.580633E+11 | 0.392820E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.142452E+11 | 0.896270E+10 | 27522.33 | 15257.50 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6 COOLING COIL
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.248713E+09 | 0.248645E+09 | 6808.29 | 28-FEB-15:10 | 6808.29 | 0.00 |
March | 0.00 | 0.00 | 0.118878E+10 | 0.930114E+09 | 13691.39 | 30-MAR-14:10 | 11024.06 | 0.00 |
April | 0.00 | 0.00 | 0.427835E+10 | 0.349264E+10 | 13409.83 | 17-APR-14:30 | 12343.03 | 0.00 |
May | 0.00 | 0.00 | 0.100307E+11 | 0.724484E+10 | 20638.60 | 30-MAY-15:00 | 14713.26 | 0.00 |
June | 0.00 | 0.00 | 0.193056E+11 | 0.131142E+11 | 48092.31 | 26-JUN-07:02 | 28326.57 | 0.00 |
July | 0.00 | 0.00 | 0.230788E+11 | 0.146179E+11 | 48757.29 | 31-JUL-07:03 | 18914.75 | 0.00 |
August | 0.00 | 0.00 | 0.258938E+11 | 0.159356E+11 | 49810.97 | 21-AUG-07:02 | 23035.45 | 0.00 |
September | 0.00 | 0.00 | 0.146017E+11 | 0.946941E+10 | 49662.77 | 17-SEP-08:62 | 22090.65 | 0.00 |
October | 0.00 | 0.00 | 0.487028E+10 | 0.327361E+10 | 39901.60 | 19-OCT-07:03 | 16549.06 | 0.00 |
November | 0.00 | 0.00 | 0.484152E+09 | 0.353262E+09 | 11659.59 | 05-NOV-15:00 | 7660.90 | 0.00 |
December | 0.00 | 0.00 | 39308119.27 | 27639206.14 | 4497.32 | 12-DEC-14:00 | 3042.88 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.104020E+12 | 0.687079E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.258938E+11 | 0.159356E+11 | 49810.97 | 28326.57 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7 COOLING COIL
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.119976E+09 | 0.119959E+09 | 3448.84 | 28-FEB-15:10 | 3448.84 | 0.00 |
March | 0.00 | 0.00 | 0.586414E+09 | 0.460907E+09 | 6987.15 | 30-MAR-14:10 | 5638.99 | 0.00 |
April | 0.00 | 0.00 | 0.215332E+10 | 0.176582E+10 | 6903.99 | 17-APR-14:40 | 6386.41 | 0.00 |
May | 0.00 | 0.00 | 0.510981E+10 | 0.370301E+10 | 10654.98 | 30-MAY-15:00 | 7615.71 | 0.00 |
June | 0.00 | 0.00 | 0.989470E+10 | 0.674183E+10 | 24848.44 | 26-JUN-07:02 | 14652.67 | 0.00 |
July | 0.00 | 0.00 | 0.118404E+11 | 0.752665E+10 | 25187.67 | 31-JUL-07:03 | 9783.00 | 0.00 |
August | 0.00 | 0.00 | 0.132880E+11 | 0.820811E+10 | 25739.32 | 21-AUG-07:02 | 11868.73 | 0.00 |
September | 0.00 | 0.00 | 0.749238E+10 | 0.487841E+10 | 25652.22 | 17-SEP-08:62 | 11411.35 | 0.00 |
October | 0.00 | 0.00 | 0.248423E+10 | 0.167518E+10 | 18809.43 | 19-OCT-07:03 | 7793.19 | 0.00 |
November | 0.00 | 0.00 | 0.229521E+09 | 0.167855E+09 | 5980.88 | 05-NOV-15:00 | 3944.31 | 0.00 |
December | 0.00 | 0.00 | 17768863.10 | 12561990.12 | 2133.68 | 12-DEC-14:00 | 1447.72 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.532165E+11 | 0.352603E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.132880E+11 | 0.820811E+10 | 25739.32 | 14652.67 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8 COOLING COIL
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.113384E+09 | 0.113367E+09 | 3355.04 | 28-FEB-15:10 | 3355.04 | 0.00 |
March | 0.00 | 0.00 | 0.563804E+09 | 0.442539E+09 | 6892.73 | 30-MAR-14:10 | 5548.88 | 0.00 |
April | 0.00 | 0.00 | 0.209277E+10 | 0.171541E+10 | 6830.83 | 17-APR-14:40 | 6307.02 | 0.00 |
May | 0.00 | 0.00 | 0.502655E+10 | 0.363573E+10 | 10589.64 | 30-MAY-15:00 | 7553.50 | 0.00 |
June | 0.00 | 0.00 | 0.983473E+10 | 0.668688E+10 | 24754.77 | 26-JUN-07:02 | 14553.55 | 0.00 |
July | 0.00 | 0.00 | 0.117823E+11 | 0.747620E+10 | 25095.33 | 31-JUL-07:03 | 9735.88 | 0.00 |
August | 0.00 | 0.00 | 0.132309E+11 | 0.815678E+10 | 25643.79 | 21-AUG-07:02 | 11788.86 | 0.00 |
September | 0.00 | 0.00 | 0.744255E+10 | 0.483597E+10 | 25557.37 | 17-SEP-08:62 | 11329.28 | 0.00 |
October | 0.00 | 0.00 | 0.244694E+10 | 0.164533E+10 | 18030.90 | 19-OCT-07:03 | 7450.48 | 0.00 |
November | 0.00 | 0.00 | 0.215044E+09 | 0.156682E+09 | 5883.25 | 05-NOV-15:00 | 3867.77 | 0.00 |
December | 0.00 | 0.00 | 16404317.63 | 11584944.61 | 2022.04 | 12-DEC-14:00 | 1369.12 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.527654E+11 | 0.348765E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.132309E+11 | 0.815678E+10 | 25643.79 | 14553.55 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9 COOLING COIL
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 98399622.01 | 98394100.20 | 3142.14 | 28-FEB-15:10 | 3142.14 | 0.00 |
March | 0.00 | 0.00 | 0.506511E+09 | 0.398390E+09 | 6661.64 | 30-MAR-14:10 | 5357.55 | 0.00 |
April | 0.00 | 0.00 | 0.191445E+10 | 0.157916E+10 | 6622.34 | 17-APR-14:40 | 6118.50 | 0.00 |
May | 0.00 | 0.00 | 0.480599E+10 | 0.347857E+10 | 10440.99 | 30-MAY-15:00 | 7444.79 | 0.00 |
June | 0.00 | 0.00 | 0.972201E+10 | 0.660784E+10 | 24751.95 | 26-JUN-07:02 | 14477.17 | 0.00 |
July | 0.00 | 0.00 | 0.117119E+11 | 0.743812E+10 | 25102.58 | 31-JUL-07:03 | 9712.34 | 0.00 |
August | 0.00 | 0.00 | 0.131882E+11 | 0.813463E+10 | 25645.81 | 21-AUG-07:02 | 11734.94 | 0.00 |
September | 0.00 | 0.00 | 0.735652E+10 | 0.478150E+10 | 25557.93 | 17-SEP-08:62 | 11235.76 | 0.00 |
October | 0.00 | 0.00 | 0.235401E+10 | 0.157906E+10 | 15626.15 | 19-OCT-07:03 | 6405.45 | 0.00 |
November | 0.00 | 0.00 | 0.182946E+09 | 0.132412E+09 | 5647.79 | 05-NOV-15:00 | 3702.44 | 0.00 |
December | 0.00 | 0.00 | 12769032.16 | 9041817.11 | 1727.85 | 12-DEC-14:00 | 1170.24 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.518537E+11 | 0.342371E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.131882E+11 | 0.813463E+10 | 25645.81 | 14477.17 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10 COOLING COIL
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 89670117.22 | 89670117.22 | 3167.53 | 28-FEB-15:10 | 3167.53 | 0.00 |
March | 0.00 | 0.00 | 0.452469E+09 | 0.361104E+09 | 6846.94 | 30-MAR-14:10 | 5557.81 | 0.00 |
April | 0.00 | 0.00 | 0.180900E+10 | 0.153432E+10 | 6802.50 | 17-APR-14:10 | 6291.37 | 0.00 |
May | 0.00 | 0.00 | 0.492668E+10 | 0.362633E+10 | 10975.56 | 30-MAY-15:00 | 7944.08 | 0.00 |
June | 0.00 | 0.00 | 0.104786E+11 | 0.723719E+10 | 27525.33 | 26-JUN-07:02 | 14740.76 | 0.00 |
July | 0.00 | 0.00 | 0.128183E+11 | 0.831821E+10 | 27549.70 | 09-JUL-08:62 | 12611.65 | 0.00 |
August | 0.00 | 0.00 | 0.144624E+11 | 0.911603E+10 | 28443.27 | 20-AUG-08:62 | 12295.95 | 0.00 |
September | 0.00 | 0.00 | 0.796981E+10 | 0.530551E+10 | 27446.88 | 17-SEP-08:62 | 12093.46 | 0.00 |
October | 0.00 | 0.00 | 0.244716E+10 | 0.166859E+10 | 11353.27 | 10-OCT-14:10 | 8125.51 | 0.00 |
November | 0.00 | 0.00 | 0.156508E+09 | 0.112252E+09 | 5685.07 | 05-NOV-15:00 | 3766.03 | 0.00 |
December | 0.00 | 0.00 | 9297963.00 | 6693954.86 | 1452.05 | 12-DEC-14:00 | 995.74 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.556199E+11 | 0.373759E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.144624E+11 | 0.911603E+10 | 28443.27 | 14740.76 | 0.00 |
Report: FanReportMonthly
For: PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.184642E+10 | 0.42 | 2142.88 | 02-JAN-08:61 | 0.91 |
February | 0.157384E+10 | 0.40 | 2142.88 | 01-FEB-08:61 | 0.91 |
March | 0.158697E+10 | 0.38 | 2142.88 | 18-MAR-07:01 | 0.91 |
April | 0.151026E+10 | 0.37 | 2142.88 | 06-APR-07:01 | 0.91 |
May | 0.155522E+10 | 0.37 | 857.15 | 08-MAY-21:50 | 0.55 |
June | 0.152871E+10 | 0.37 | 2142.88 | 14-JUN-07:02 | 0.90 |
July | 0.162326E+10 | 0.38 | 2142.88 | 04-JUL-07:02 | 0.90 |
August | 0.164673E+10 | 0.38 | 2142.88 | 01-AUG-07:02 | 0.89 |
September | 0.151966E+10 | 0.37 | 2142.88 | 03-SEP-07:03 | 0.89 |
October | 0.155846E+10 | 0.37 | 2008.74 | 19-OCT-07:03 | 0.87 |
November | 0.153166E+10 | 0.38 | 2142.88 | 21-NOV-08:61 | 0.91 |
December | 0.169243E+10 | 0.40 | 2142.88 | 01-DEC-08:61 | 0.91 |
Annual Sum or Average | 0.191736E+11 | 0.38 | |||
Minimum of Months | 0.151026E+10 | 0.37 | 857.15 | 0.55 | |
Maximum of Months | 0.184642E+10 | 0.42 | 2142.88 | 0.91 |
Report: FanReportMonthly
For: PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.737099E+09 | 0.33 | 1176.21 | 02-JAN-08:61 | 0.94 |
February | 0.674308E+09 | 0.35 | 1176.21 | 02-FEB-08:61 | 0.94 |
March | 0.745109E+09 | 0.38 | 993.58 | 23-MAR-07:01 | 0.87 |
April | 0.733454E+09 | 0.38 | 582.45 | 07-APR-07:01 | 0.65 |
May | 0.752712E+09 | 0.39 | 470.49 | 06-MAY-17:15 | 0.56 |
June | 0.742643E+09 | 0.39 | 1176.21 | 14-JUN-07:02 | 0.93 |
July | 0.804330E+09 | 0.40 | 1176.21 | 04-JUL-07:02 | 0.93 |
August | 0.820442E+09 | 0.40 | 1176.21 | 01-AUG-07:02 | 0.93 |
September | 0.746652E+09 | 0.39 | 1176.21 | 03-SEP-07:03 | 0.93 |
October | 0.772211E+09 | 0.38 | 1176.21 | 19-OCT-07:03 | 0.93 |
November | 0.727266E+09 | 0.37 | 1176.21 | 22-NOV-08:61 | 0.94 |
December | 0.682468E+09 | 0.31 | 1176.21 | 01-DEC-08:61 | 0.94 |
Annual Sum or Average | 0.893869E+10 | 0.37 | |||
Minimum of Months | 0.674308E+09 | 0.31 | 470.49 | 0.56 | |
Maximum of Months | 0.820442E+09 | 0.40 | 1176.21 | 0.94 |
Report: FanReportMonthly
For: PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.800124E+09 | 0.34 | 1180.91 | 02-JAN-07:01 | 0.94 |
February | 0.683715E+09 | 0.33 | 1180.91 | 03-FEB-07:01 | 0.95 |
March | 0.705398E+09 | 0.32 | 834.65 | 19-MAR-07:02 | 0.80 |
April | 0.664230E+09 | 0.31 | 622.83 | 06-APR-07:03 | 0.68 |
May | 0.690424E+09 | 0.31 | 554.20 | 31-MAY-06:03 | 0.62 |
June | 0.680748E+09 | 0.31 | 1180.91 | 12-JUN-06:02 | 0.93 |
July | 0.710018E+09 | 0.31 | 1180.91 | 01-JUL-06:03 | 0.93 |
August | 0.735439E+09 | 0.32 | 1180.91 | 01-AUG-06:02 | 0.92 |
September | 0.667866E+09 | 0.31 | 1180.91 | 01-SEP-06:03 | 0.93 |
October | 0.684590E+09 | 0.31 | 1180.91 | 18-OCT-06:03 | 0.92 |
November | 0.672943E+09 | 0.31 | 1180.91 | 22-NOV-07:02 | 0.94 |
December | 0.727285E+09 | 0.32 | 1180.91 | 02-DEC-07:02 | 0.94 |
Annual Sum or Average | 0.842278E+10 | 0.32 | |||
Minimum of Months | 0.664230E+09 | 0.31 | 554.20 | 0.62 | |
Maximum of Months | 0.800124E+09 | 0.34 | 1180.91 | 0.95 |
Report: FanReportMonthly
For: PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.807439E+09 | 0.34 | 1184.75 | 01-JAN-08:62 | 0.94 |
February | 0.688571E+09 | 0.33 | 1184.75 | 03-FEB-07:01 | 0.95 |
March | 0.708830E+09 | 0.32 | 938.14 | 19-MAR-07:02 | 0.85 |
April | 0.666510E+09 | 0.31 | 607.58 | 06-APR-07:02 | 0.67 |
May | 0.692667E+09 | 0.31 | 547.93 | 31-MAY-06:03 | 0.62 |
June | 0.682822E+09 | 0.31 | 1184.75 | 12-JUN-06:02 | 0.93 |
July | 0.712221E+09 | 0.31 | 1184.75 | 01-JUL-06:03 | 0.93 |
August | 0.737625E+09 | 0.32 | 1184.75 | 01-AUG-06:02 | 0.92 |
September | 0.669951E+09 | 0.31 | 1184.75 | 01-SEP-06:03 | 0.93 |
October | 0.687152E+09 | 0.31 | 1184.75 | 18-OCT-06:03 | 0.92 |
November | 0.676492E+09 | 0.31 | 1184.75 | 22-NOV-07:02 | 0.94 |
December | 0.733671E+09 | 0.32 | 1184.75 | 02-DEC-07:02 | 0.94 |
Annual Sum or Average | 0.846395E+10 | 0.32 | |||
Minimum of Months | 0.666510E+09 | 0.31 | 547.93 | 0.62 | |
Maximum of Months | 0.807439E+09 | 0.34 | 1184.75 | 0.95 |
Report: FanReportMonthly
For: PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.808545E+09 | 0.34 | 1173.22 | 01-JAN-08:62 | 0.94 |
February | 0.687507E+09 | 0.33 | 1173.22 | 03-FEB-07:01 | 0.95 |
March | 0.704049E+09 | 0.32 | 1035.84 | 19-MAR-07:02 | 0.89 |
April | 0.660387E+09 | 0.31 | 582.35 | 07-APR-06:05 | 0.65 |
May | 0.685912E+09 | 0.31 | 469.29 | 09-MAY-17:00 | 0.57 |
June | 0.675343E+09 | 0.31 | 1173.22 | 12-JUN-06:02 | 0.93 |
July | 0.703638E+09 | 0.31 | 1173.22 | 01-JUL-06:03 | 0.93 |
August | 0.728247E+09 | 0.32 | 1173.22 | 01-AUG-06:02 | 0.92 |
September | 0.663029E+09 | 0.31 | 1173.22 | 03-SEP-07:03 | 0.92 |
October | 0.681079E+09 | 0.31 | 1173.22 | 19-OCT-06:03 | 0.92 |
November | 0.672258E+09 | 0.31 | 1173.22 | 22-NOV-07:02 | 0.94 |
December | 0.733300E+09 | 0.32 | 1173.22 | 02-DEC-07:02 | 0.94 |
Annual Sum or Average | 0.840330E+10 | 0.32 | |||
Minimum of Months | 0.660387E+09 | 0.31 | 469.29 | 0.57 | |
Maximum of Months | 0.808545E+09 | 0.34 | 1173.22 | 0.95 |
Report: FanReportMonthly
For: PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.129885E+10 | 0.31 | 1987.97 | 01-JAN-09:01 | 0.91 |
February | 0.109560E+10 | 0.30 | 1987.97 | 01-FEB-08:61 | 0.91 |
March | 0.110889E+10 | 0.28 | 1987.97 | 18-MAR-07:01 | 0.91 |
April | 0.103337E+10 | 0.27 | 1987.97 | 06-APR-07:01 | 0.91 |
May | 0.107350E+10 | 0.28 | 795.19 | 26-MAY-19:05 | 0.54 |
June | 0.106679E+10 | 0.28 | 1987.97 | 12-JUN-07:03 | 0.90 |
July | 0.112189E+10 | 0.28 | 1987.97 | 04-JUL-08:62 | 0.90 |
August | 0.116806E+10 | 0.29 | 1987.97 | 01-AUG-07:02 | 0.90 |
September | 0.104108E+10 | 0.27 | 1987.97 | 04-SEP-08:62 | 0.89 |
October | 0.106693E+10 | 0.27 | 1614.38 | 19-OCT-07:03 | 0.81 |
November | 0.105847E+10 | 0.28 | 1987.97 | 21-NOV-08:61 | 0.91 |
December | 0.116687E+10 | 0.29 | 1987.97 | 01-DEC-08:61 | 0.91 |
Annual Sum or Average | 0.133003E+11 | 0.28 | |||
Minimum of Months | 0.103337E+10 | 0.27 | 795.19 | 0.54 | |
Maximum of Months | 0.129885E+10 | 0.31 | 1987.97 | 0.91 |
Report: FanReportMonthly
For: PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.699715E+09 | 0.32 | 1068.04 | 01-JAN-09:01 | 0.94 |
February | 0.589907E+09 | 0.31 | 1068.04 | 01-FEB-08:61 | 0.94 |
March | 0.596157E+09 | 0.29 | 1068.04 | 18-MAR-07:01 | 0.94 |
April | 0.555246E+09 | 0.28 | 1068.04 | 06-APR-07:01 | 0.94 |
May | 0.576741E+09 | 0.28 | 427.22 | 14-MAY-11:20 | 0.57 |
June | 0.572894E+09 | 0.29 | 1068.04 | 12-JUN-07:03 | 0.93 |
July | 0.602508E+09 | 0.29 | 1068.04 | 05-JUL-07:02 | 0.93 |
August | 0.627092E+09 | 0.30 | 1068.04 | 01-AUG-07:02 | 0.93 |
September | 0.559145E+09 | 0.28 | 1068.04 | 04-SEP-08:62 | 0.92 |
October | 0.573248E+09 | 0.28 | 845.96 | 26-OCT-07:01 | 0.84 |
November | 0.568857E+09 | 0.29 | 1068.04 | 21-NOV-08:61 | 0.94 |
December | 0.627949E+09 | 0.30 | 1068.04 | 01-DEC-08:61 | 0.94 |
Annual Sum or Average | 0.714946E+10 | 0.29 | |||
Minimum of Months | 0.555246E+09 | 0.28 | 427.22 | 0.57 | |
Maximum of Months | 0.699715E+09 | 0.32 | 1068.04 | 0.94 |
Report: FanReportMonthly
For: PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.698504E+09 | 0.32 | 1062.67 | 01-JAN-09:01 | 0.94 |
February | 0.588494E+09 | 0.31 | 1062.67 | 01-FEB-08:61 | 0.94 |
March | 0.594174E+09 | 0.29 | 1062.67 | 07-MAR-08:61 | 0.94 |
April | 0.552674E+09 | 0.28 | 1062.67 | 06-APR-07:01 | 0.94 |
May | 0.573841E+09 | 0.28 | 425.07 | 25-MAY-13:30 | 0.56 |
June | 0.569968E+09 | 0.29 | 1062.67 | 12-JUN-07:03 | 0.93 |
July | 0.599637E+09 | 0.29 | 1062.67 | 05-JUL-07:02 | 0.93 |
August | 0.624149E+09 | 0.30 | 1062.67 | 01-AUG-07:02 | 0.93 |
September | 0.556332E+09 | 0.28 | 1062.67 | 04-SEP-08:62 | 0.92 |
October | 0.570612E+09 | 0.28 | 897.22 | 26-OCT-07:01 | 0.87 |
November | 0.566736E+09 | 0.29 | 1062.67 | 21-NOV-08:61 | 0.94 |
December | 0.626675E+09 | 0.30 | 1062.67 | 01-DEC-08:61 | 0.94 |
Annual Sum or Average | 0.712179E+10 | 0.29 | |||
Minimum of Months | 0.552674E+09 | 0.28 | 425.07 | 0.56 | |
Maximum of Months | 0.698504E+09 | 0.32 | 1062.67 | 0.94 |
Report: FanReportMonthly
For: PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.707159E+09 | 0.33 | 1063.23 | 01-JAN-09:01 | 0.94 |
February | 0.594444E+09 | 0.31 | 1063.23 | 01-FEB-08:61 | 0.94 |
March | 0.597824E+09 | 0.30 | 1063.23 | 03-MAR-08:61 | 0.94 |
April | 0.553822E+09 | 0.28 | 1063.23 | 06-APR-07:01 | 0.94 |
May | 0.574142E+09 | 0.28 | 425.29 | 12-MAY-17:50 | 0.57 |
June | 0.569317E+09 | 0.29 | 1063.23 | 14-JUN-07:02 | 0.93 |
July | 0.599421E+09 | 0.29 | 1063.23 | 05-JUL-07:02 | 0.93 |
August | 0.624141E+09 | 0.30 | 1063.23 | 01-AUG-07:02 | 0.93 |
September | 0.556463E+09 | 0.28 | 1063.23 | 05-SEP-07:03 | 0.92 |
October | 0.571650E+09 | 0.28 | 1063.23 | 26-OCT-07:01 | 0.94 |
November | 0.569357E+09 | 0.29 | 1063.23 | 21-NOV-08:61 | 0.94 |
December | 0.633238E+09 | 0.30 | 1063.23 | 01-DEC-08:61 | 0.94 |
Annual Sum or Average | 0.715098E+10 | 0.29 | |||
Minimum of Months | 0.553822E+09 | 0.28 | 425.29 | 0.57 | |
Maximum of Months | 0.707159E+09 | 0.33 | 1063.23 | 0.94 |
Report: FanReportMonthly
For: PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.826153E+09 | 0.34 | 1209.36 | 01-JAN-09:01 | 0.94 |
February | 0.695687E+09 | 0.33 | 1209.36 | 01-FEB-08:61 | 0.94 |
March | 0.689784E+09 | 0.30 | 1209.36 | 02-MAR-08:62 | 0.94 |
April | 0.633614E+09 | 0.29 | 1209.36 | 06-APR-07:01 | 0.94 |
May | 0.653121E+09 | 0.28 | 571.52 | 11-MAY-07:03 | 0.63 |
June | 0.645524E+09 | 0.29 | 1209.36 | 26-JUN-07:02 | 0.92 |
July | 0.682085E+09 | 0.29 | 1209.36 | 05-JUL-07:02 | 0.92 |
August | 0.711690E+09 | 0.30 | 1209.36 | 01-AUG-07:02 | 0.92 |
September | 0.633893E+09 | 0.28 | 1209.36 | 05-SEP-07:03 | 0.92 |
October | 0.652412E+09 | 0.28 | 1209.36 | 26-OCT-07:01 | 0.94 |
November | 0.653034E+09 | 0.29 | 1209.36 | 14-NOV-08:62 | 0.94 |
December | 0.733410E+09 | 0.31 | 1209.36 | 01-DEC-08:61 | 0.94 |
Annual Sum or Average | 0.821041E+10 | 0.30 | |||
Minimum of Months | 0.633614E+09 | 0.28 | 571.52 | 0.63 | |
Maximum of Months | 0.826153E+09 | 0.34 | 1209.36 | 0.94 |
Report: ZoneTemperatureOscillationReportMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.184642E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.168353E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.207771E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.311295E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.525786E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.822820E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.981928E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.104973E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.678764E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.341708E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.181239E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.171133E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.562517E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.168353E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.104973E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.737864E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.765570E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.109006E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.182184E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.292707E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.420781E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.492344E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.520304E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.352115E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.185036E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.952459E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.701761E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.287024E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.701761E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.520304E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_3:3
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.800124E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.740907E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.926831E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.138991E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.222371E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.338679E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.389399E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.423192E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.273415E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.142674E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.791989E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.738092E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.232852E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.738092E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.423192E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_4:4
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.807439E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.740813E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.918684E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.137792E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.221568E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.339481E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.390732E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.424590E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.273636E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.141914E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.783099E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.742597E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.232898E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.740813E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.424590E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_5:5
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.808545E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.732537E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.892504E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.133136E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.215119E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.332820E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.384155E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.417884E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.267798E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.137959E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.760430E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.740327E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.228230E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.732537E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.417884E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_6:6
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.129885E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.116570E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.143422E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.219962E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.370242E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.596481E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.688199E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.753915E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.468144E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.230688E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.119015E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.117792E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.395431E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.116570E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.753915E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_7:7
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.699715E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.623195E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.754097E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.113287E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.189388E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.304313E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.351066E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.384495E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.239627E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.119496E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.630211E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.632875E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.203568E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.623195E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.384495E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_8:8
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.698504E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.620013E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.746284E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.111504E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.187074E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.302551E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.349356E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.382812E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.238148E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.118336E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.624269E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.631231E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.202181E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.620013E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.382812E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_9:9
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.707159E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.621944E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.735191E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.107178E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.181886E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.299931E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.347746E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.381897E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.236221E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.116253E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.618430E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.636806E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.200306E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.618430E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.381897E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_10:10
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.826153E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.720935E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.813731E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.112835E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.193781E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.327572E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.384172E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.422812E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.259487E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.126863E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.695217E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.736030E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.220673E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.695217E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.422812E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.184642E+10 | 0.00 | 0.128994E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.157384E+10 | 0.394488E+09 | 0.738385E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.158697E+10 | 0.181459E+10 | 0.113788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.151026E+10 | 0.592788E+10 | 0.196776E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.155522E+10 | 0.141995E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.152871E+10 | 0.263593E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.162326E+10 | 0.327673E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.164673E+10 | 0.359565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.151966E+10 | 0.211613E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.155846E+10 | 0.734709E+10 | 0.131216E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.153166E+10 | 0.105082E+10 | 0.128493E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.169243E+10 | 68419920.76 | 0.581796E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.191736E+11 | 0.147047E+12 | 0.288520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.151026E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.184642E+10 | 0.359565E+11 | 0.128994E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.737099E+09 | 2772405.14 | 0.396328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.674308E+09 | 0.331182E+09 | 0.222433E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.745109E+09 | 0.129338E+10 | 0.213319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.733454E+09 | 0.410182E+10 | 17228524.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.752712E+09 | 0.848986E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.742643E+09 | 0.137651E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.804330E+09 | 0.166126E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.820442E+09 | 0.179330E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.746652E+09 | 0.112433E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.772211E+09 | 0.431128E+10 | 10454241.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.727266E+09 | 0.868816E+09 | 0.230710E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.682468E+09 | 71589185.82 | 0.128702E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.893869E+10 | 0.790248E+11 | 0.794634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.674308E+09 | 2772405.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.820442E+09 | 0.179330E+11 | 0.396328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_3:3
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.800124E+09 | 0.00 | 0.494780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.683715E+09 | 0.210140E+09 | 0.274862E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.705398E+09 | 0.835683E+09 | 0.347731E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.664230E+09 | 0.273993E+10 | 43790014.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.690424E+09 | 0.598973E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.680748E+09 | 0.108474E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.710018E+09 | 0.129623E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.735439E+09 | 0.144440E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.667866E+09 | 0.843351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.684590E+09 | 0.297783E+10 | 32790658.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.672943E+09 | 0.449806E+09 | 0.413765E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.727285E+09 | 39872206.92 | 0.199924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.842278E+10 | 0.599302E+11 | 0.105337E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.664230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.800124E+09 | 0.144440E+11 | 0.494780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_4:4
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.807439E+09 | 0.00 | 0.516039E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.688571E+09 | 0.191072E+09 | 0.286734E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.708830E+09 | 0.789650E+09 | 0.396874E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.666510E+09 | 0.268058E+10 | 48966155.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.692667E+09 | 0.594260E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.682822E+09 | 0.108694E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.712221E+09 | 0.130084E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.737625E+09 | 0.144940E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.669951E+09 | 0.843058E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.687152E+09 | 0.293325E+10 | 47110157.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.676492E+09 | 0.401729E+09 | 0.472558E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.733671E+09 | 32777106.30 | 0.217493E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.846395E+10 | 0.597740E+11 | 0.111682E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.666510E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.807439E+09 | 0.144940E+11 | 0.516039E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_5:5
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.808545E+09 | 0.00 | 0.550228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.687507E+09 | 0.163601E+09 | 0.308522E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.704049E+09 | 0.705501E+09 | 0.483871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.660387E+09 | 0.251631E+10 | 64045397.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.685912E+09 | 0.569873E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.675343E+09 | 0.106168E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.703638E+09 | 0.127638E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.728247E+09 | 0.142452E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.663029E+09 | 0.820542E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.681079E+09 | 0.279145E+10 | 73527136.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.672258E+09 | 0.330913E+09 | 0.568829E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.733300E+09 | 25596442.81 | 0.244621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.840330E+10 | 0.580633E+11 | 0.122240E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.660387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.808545E+09 | 0.142452E+11 | 0.550228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_6:6
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.129885E+10 | 0.00 | 0.107409E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109560E+10 | 0.248713E+09 | 0.606666E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.110889E+10 | 0.118878E+10 | 0.108557E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.103337E+10 | 0.427835E+10 | 0.127411E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.107350E+10 | 0.100307E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.106679E+10 | 0.193056E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.112189E+10 | 0.230788E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.116806E+10 | 0.258938E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.104108E+10 | 0.146017E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.106693E+10 | 0.487028E+10 | 0.212995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.105847E+10 | 0.484152E+09 | 0.126586E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116687E+10 | 39308119.27 | 0.501437E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.133003E+11 | 0.104020E+12 | 0.245138E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.103337E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.129885E+10 | 0.258938E+11 | 0.107409E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_7:7
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.699715E+09 | 0.00 | 0.560985E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.589907E+09 | 0.119976E+09 | 0.317784E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.596157E+09 | 0.586414E+09 | 0.576259E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.555246E+09 | 0.215332E+10 | 68430212.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.576741E+09 | 0.510981E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.572894E+09 | 0.989470E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.602508E+09 | 0.118404E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.627092E+09 | 0.132880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.559145E+09 | 0.749238E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.573248E+09 | 0.248423E+10 | 0.112357E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.568857E+09 | 0.229521E+09 | 0.659736E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.627949E+09 | 17768863.10 | 0.262565E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.714946E+10 | 0.532165E+11 | 0.128301E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.555246E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.699715E+09 | 0.132880E+11 | 0.560985E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_8:8
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.698504E+09 | 0.00 | 0.568864E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.588494E+09 | 0.113384E+09 | 0.323320E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.594174E+09 | 0.563804E+09 | 0.618181E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.552674E+09 | 0.209277E+10 | 77691728.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.573841E+09 | 0.502655E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.569968E+09 | 0.983473E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.599637E+09 | 0.117823E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.624149E+09 | 0.132309E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.556332E+09 | 0.744255E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.570612E+09 | 0.244694E+10 | 0.123175E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.566736E+09 | 0.215044E+09 | 0.689361E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.626675E+09 | 16404317.63 | 0.269744E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.712179E+10 | 0.527654E+11 | 0.131277E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.552674E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.698504E+09 | 0.132309E+11 | 0.568864E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_9:9
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.707159E+09 | 0.00 | 0.605142E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.594444E+09 | 98399622.01 | 0.347986E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.597824E+09 | 0.506511E+09 | 0.763606E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.553822E+09 | 0.191445E+10 | 0.115072E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.574142E+09 | 0.480599E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.569317E+09 | 0.972201E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.599421E+09 | 0.117119E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.624141E+09 | 0.131882E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.556463E+09 | 0.735652E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.571650E+09 | 0.235401E+10 | 0.156793E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.569357E+09 | 0.182946E+09 | 0.790709E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.633238E+09 | 12769032.16 | 0.296970E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.715098E+10 | 0.518537E+11 | 0.143272E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.553822E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.707159E+09 | 0.131882E+11 | 0.605142E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_10:10
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.826153E+09 | 0.00 | 0.755950E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.695687E+09 | 89670117.22 | 0.458104E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.689784E+09 | 0.452469E+09 | 0.125738E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.633614E+09 | 0.180900E+10 | 0.282287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.653121E+09 | 0.492668E+10 | 2780856.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.645524E+09 | 0.104786E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.682085E+09 | 0.128183E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.711690E+09 | 0.144624E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.633893E+09 | 0.796981E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.652412E+09 | 0.244716E+10 | 0.267117E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.653034E+09 | 0.156508E+09 | 0.110269E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.733410E+09 | 9297963.00 | 0.383620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.821041E+10 | 0.556199E+11 | 0.188890E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.633614E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.826153E+09 | 0.144624E+11 | 0.755950E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.184642E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.157384E+10 | 0.00 | 0.00 | 0.00 | 0.109691E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.158697E+10 | 0.00 | 0.00 | 0.00 | 0.490738E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.151026E+10 | 0.00 | 0.00 | 0.00 | 0.160269E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.155522E+10 | 0.00 | 0.00 | 0.00 | 0.370265E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.152871E+10 | 0.00 | 0.00 | 0.00 | 0.669949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.162326E+10 | 0.00 | 0.00 | 0.00 | 0.819603E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.164673E+10 | 0.00 | 0.00 | 0.00 | 0.885056E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.151966E+10 | 0.00 | 0.00 | 0.00 | 0.526798E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.155846E+10 | 0.00 | 0.00 | 0.00 | 0.185862E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.153166E+10 | 0.00 | 0.00 | 0.00 | 0.280730E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.169243E+10 | 0.00 | 0.00 | 0.00 | 18904382.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.191736E+11 | 0.00 | 0.00 | 0.00 | 0.370781E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.151026E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.184642E+10 | 0.00 | 0.00 | 0.00 | 0.885056E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.737099E+09 | 0.00 | 0.00 | 0.00 | 765305.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.674308E+09 | 0.00 | 0.00 | 0.00 | 91261741.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.745109E+09 | 0.00 | 0.00 | 0.00 | 0.344946E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.733454E+09 | 0.00 | 0.00 | 0.00 | 0.108839E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.752712E+09 | 0.00 | 0.00 | 0.00 | 0.217436E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.742643E+09 | 0.00 | 0.00 | 0.00 | 0.346517E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.804330E+09 | 0.00 | 0.00 | 0.00 | 0.411911E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.820442E+09 | 0.00 | 0.00 | 0.00 | 0.438259E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.746652E+09 | 0.00 | 0.00 | 0.00 | 0.277449E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.772211E+09 | 0.00 | 0.00 | 0.00 | 0.107814E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.727266E+09 | 0.00 | 0.00 | 0.00 | 0.225193E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.682468E+09 | 0.00 | 0.00 | 0.00 | 19293304.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.893869E+10 | 0.00 | 0.00 | 0.00 | 0.197637E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.674308E+09 | 0.00 | 0.00 | 0.00 | 765305.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.820442E+09 | 0.00 | 0.00 | 0.00 | 0.438259E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_3:3
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.800124E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.683715E+09 | 0.00 | 0.00 | 0.00 | 57192466.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.705398E+09 | 0.00 | 0.00 | 0.00 | 0.221433E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.664230E+09 | 0.00 | 0.00 | 0.00 | 0.725675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.690424E+09 | 0.00 | 0.00 | 0.00 | 0.153329E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.680748E+09 | 0.00 | 0.00 | 0.00 | 0.270605E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.710018E+09 | 0.00 | 0.00 | 0.00 | 0.318397E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.735439E+09 | 0.00 | 0.00 | 0.00 | 0.349648E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.667866E+09 | 0.00 | 0.00 | 0.00 | 0.206628E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.684590E+09 | 0.00 | 0.00 | 0.00 | 0.742152E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.672943E+09 | 0.00 | 0.00 | 0.00 | 0.119046E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.727285E+09 | 0.00 | 0.00 | 0.00 | 10806356.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.842278E+10 | 0.00 | 0.00 | 0.00 | 0.148624E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.664230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.800124E+09 | 0.00 | 0.00 | 0.00 | 0.349648E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_4:4
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.807439E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.688571E+09 | 0.00 | 0.00 | 0.00 | 52241852.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.708830E+09 | 0.00 | 0.00 | 0.00 | 0.209854E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.666510E+09 | 0.00 | 0.00 | 0.00 | 0.711407E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.692667E+09 | 0.00 | 0.00 | 0.00 | 0.152302E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.682822E+09 | 0.00 | 0.00 | 0.00 | 0.271198E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.712221E+09 | 0.00 | 0.00 | 0.00 | 0.319509E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.737625E+09 | 0.00 | 0.00 | 0.00 | 0.350827E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.669951E+09 | 0.00 | 0.00 | 0.00 | 0.206641E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.687152E+09 | 0.00 | 0.00 | 0.00 | 0.731991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.676492E+09 | 0.00 | 0.00 | 0.00 | 0.106607E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.733671E+09 | 0.00 | 0.00 | 0.00 | 8925817.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.846395E+10 | 0.00 | 0.00 | 0.00 | 0.148258E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.666510E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.807439E+09 | 0.00 | 0.00 | 0.00 | 0.350827E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_5:5
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.808545E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.687507E+09 | 0.00 | 0.00 | 0.00 | 45029111.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.704049E+09 | 0.00 | 0.00 | 0.00 | 0.188455E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.660387E+09 | 0.00 | 0.00 | 0.00 | 0.670975E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.685912E+09 | 0.00 | 0.00 | 0.00 | 0.146528E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.675343E+09 | 0.00 | 0.00 | 0.00 | 0.265285E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.703638E+09 | 0.00 | 0.00 | 0.00 | 0.313791E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.728247E+09 | 0.00 | 0.00 | 0.00 | 0.345059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.663029E+09 | 0.00 | 0.00 | 0.00 | 0.201495E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.681079E+09 | 0.00 | 0.00 | 0.00 | 0.698509E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.672258E+09 | 0.00 | 0.00 | 0.00 | 88172452.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.733300E+09 | 0.00 | 0.00 | 0.00 | 7026856.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.840330E+10 | 0.00 | 0.00 | 0.00 | 0.144198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.660387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.808545E+09 | 0.00 | 0.00 | 0.00 | 0.345059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_6:6
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.129885E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109560E+10 | 0.00 | 0.00 | 0.00 | 70094668.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.110889E+10 | 0.00 | 0.00 | 0.00 | 0.325329E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.103337E+10 | 0.00 | 0.00 | 0.00 | 0.116624E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.107350E+10 | 0.00 | 0.00 | 0.00 | 0.262892E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.106679E+10 | 0.00 | 0.00 | 0.00 | 0.489801E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.112189E+10 | 0.00 | 0.00 | 0.00 | 0.576010E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.116806E+10 | 0.00 | 0.00 | 0.00 | 0.637109E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.104108E+10 | 0.00 | 0.00 | 0.00 | 0.364036E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.106693E+10 | 0.00 | 0.00 | 0.00 | 0.123994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.105847E+10 | 0.00 | 0.00 | 0.00 | 0.131679E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116687E+10 | 0.00 | 0.00 | 0.00 | 11048982.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.133003E+11 | 0.00 | 0.00 | 0.00 | 0.262428E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.103337E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.129885E+10 | 0.00 | 0.00 | 0.00 | 0.637109E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_7:7
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.699715E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.589907E+09 | 0.00 | 0.00 | 0.00 | 33288306.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.596157E+09 | 0.00 | 0.00 | 0.00 | 0.157940E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.555246E+09 | 0.00 | 0.00 | 0.00 | 0.577626E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.576741E+09 | 0.00 | 0.00 | 0.00 | 0.131714E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.572894E+09 | 0.00 | 0.00 | 0.00 | 0.247023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.602508E+09 | 0.00 | 0.00 | 0.00 | 0.290815E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.627092E+09 | 0.00 | 0.00 | 0.00 | 0.321785E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.559145E+09 | 0.00 | 0.00 | 0.00 | 0.183712E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.573248E+09 | 0.00 | 0.00 | 0.00 | 0.621709E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.568857E+09 | 0.00 | 0.00 | 0.00 | 61354182.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.627949E+09 | 0.00 | 0.00 | 0.00 | 4925481.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.714946E+10 | 0.00 | 0.00 | 0.00 | 0.132073E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.555246E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.699715E+09 | 0.00 | 0.00 | 0.00 | 0.321785E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_8:8
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.698504E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.588494E+09 | 0.00 | 0.00 | 0.00 | 31519576.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.594174E+09 | 0.00 | 0.00 | 0.00 | 0.152109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.552674E+09 | 0.00 | 0.00 | 0.00 | 0.562363E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.573841E+09 | 0.00 | 0.00 | 0.00 | 0.129690E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.569968E+09 | 0.00 | 0.00 | 0.00 | 0.245554E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.599637E+09 | 0.00 | 0.00 | 0.00 | 0.289392E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.624149E+09 | 0.00 | 0.00 | 0.00 | 0.320397E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.556332E+09 | 0.00 | 0.00 | 0.00 | 0.182514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.570612E+09 | 0.00 | 0.00 | 0.00 | 0.612750E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.566736E+09 | 0.00 | 0.00 | 0.00 | 57532691.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.626675E+09 | 0.00 | 0.00 | 0.00 | 4556515.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.712179E+10 | 0.00 | 0.00 | 0.00 | 0.130963E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.552674E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.698504E+09 | 0.00 | 0.00 | 0.00 | 0.320397E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_9:9
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.707159E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.594444E+09 | 0.00 | 0.00 | 0.00 | 27499901.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.597824E+09 | 0.00 | 0.00 | 0.00 | 0.137367E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.553822E+09 | 0.00 | 0.00 | 0.00 | 0.517956E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.574142E+09 | 0.00 | 0.00 | 0.00 | 0.124472E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.569317E+09 | 0.00 | 0.00 | 0.00 | 0.242999E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.599421E+09 | 0.00 | 0.00 | 0.00 | 0.287803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.624141E+09 | 0.00 | 0.00 | 0.00 | 0.319482E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.556463E+09 | 0.00 | 0.00 | 0.00 | 0.180575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.571650E+09 | 0.00 | 0.00 | 0.00 | 0.590882E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.569357E+09 | 0.00 | 0.00 | 0.00 | 49073171.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.633238E+09 | 0.00 | 0.00 | 0.00 | 3568032.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.715098E+10 | 0.00 | 0.00 | 0.00 | 0.128797E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.553822E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.707159E+09 | 0.00 | 0.00 | 0.00 | 0.319482E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_10:10
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.826153E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.695687E+09 | 0.00 | 0.00 | 0.00 | 25248209.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.689784E+09 | 0.00 | 0.00 | 0.00 | 0.123947E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.633614E+09 | 0.00 | 0.00 | 0.00 | 0.494741E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.653121E+09 | 0.00 | 0.00 | 0.00 | 0.128469E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.645524E+09 | 0.00 | 0.00 | 0.00 | 0.263020E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.682085E+09 | 0.00 | 0.00 | 0.00 | 0.315963E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.711690E+09 | 0.00 | 0.00 | 0.00 | 0.351643E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.633893E+09 | 0.00 | 0.00 | 0.00 | 0.196098E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.652412E+09 | 0.00 | 0.00 | 0.00 | 0.616218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.653034E+09 | 0.00 | 0.00 | 0.00 | 42183543.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.733410E+09 | 0.00 | 0.00 | 0.00 | 2619363.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.821041E+10 | 0.00 | 0.00 | 0.00 | 0.138569E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.633614E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.826153E+09 | 0.00 | 0.00 | 0.00 | 0.351643E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.618213E+10 | 0.00 | 0.00 | 21289.97 | 0.00 | 0.763456E+10 | 42885182.67 | 0.00 | 0.52 |
February | 0.479802E+10 | 1209426.91 | 0.00 | 1540438.68 | 0.00 | 0.443522E+10 | 0.748186E+09 | 0.00 | 0.59 |
March | 0.461416E+10 | 0.155280E+09 | 0.00 | 3542069.22 | 42587.05 | 0.477597E+09 | 0.221514E+10 | 0.00 | 0.66 |
April | 0.197552E+10 | 0.515714E+09 | 0.00 | 6818550.67 | 3100453.41 | 48030839.53 | 0.247730E+10 | 0.00 | 0.74 |
May | 0.279318E+09 | 0.257661E+10 | 0.00 | 5461989.14 | 9051.57 | 0.00 | 0.192691E+10 | 0.00 | 0.74 |
June | 13122765.17 | 0.824306E+10 | 0.00 | 2829566.92 | 0.00 | 0.00 | 0.470876E+09 | 0.00 | 0.60 |
July | 1657068.42 | 0.117053E+11 | 0.00 | 747093.89 | 0.00 | 0.00 | 0.385095E+09 | 0.00 | 0.56 |
August | 0.00 | 0.131578E+11 | 0.00 | 119470.18 | 0.00 | 0.00 | 17264809.42 | 0.00 | 0.54 |
September | 69246253.03 | 0.571419E+10 | 0.00 | 4494040.98 | 0.00 | 0.00 | 0.158072E+10 | 0.00 | 0.66 |
October | 0.268417E+10 | 0.121253E+10 | 0.00 | 7809794.33 | 0.00 | 14852553.09 | 0.364431E+10 | 0.00 | 0.74 |
November | 0.532111E+10 | 23051046.46 | 0.00 | 4250646.99 | 2751217.23 | 0.239049E+09 | 0.297129E+10 | 0.00 | 0.69 |
December | 0.786099E+10 | 0.00 | 0.00 | 555597.97 | 0.00 | 0.246872E+10 | 0.521207E+09 | 0.00 | 0.55 |
Annual Sum or Average | 0.337994E+11 | 0.433048E+11 | 0.00 | 38190548.94 | 5903309.27 | 0.153180E+11 | 0.170012E+11 | 0.00 | 0.63 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 21289.97 | 0.00 | 0.00 | 17264809.42 | 0.00 | 0.52 |
Maximum of Months | 0.786099E+10 | 0.131578E+11 | 0.00 | 7809794.33 | 3100453.41 | 0.763456E+10 | 0.364431E+10 | 0.00 | 0.74 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.272647E+10 | 0.00 | 0.00 | 96985.60 | 0.00 | 0.223937E+10 | 95112619.70 | 0.00 | 0.39 |
February | 0.176867E+10 | 657278.24 | 0.00 | 1264399.03 | 0.00 | 0.139982E+10 | 0.768233E+09 | 0.00 | 0.51 |
March | 0.160380E+10 | 83525805.52 | 0.00 | 2600348.57 | 0.00 | 64728770.35 | 0.172402E+10 | 0.00 | 0.62 |
April | 0.602621E+09 | 0.286125E+09 | 0.00 | 3337926.30 | 460764.75 | 0.00 | 0.132815E+10 | 0.00 | 0.67 |
May | 45194072.60 | 0.135645E+10 | 0.00 | 2339406.07 | 0.00 | 0.00 | 0.767506E+09 | 0.00 | 0.61 |
June | 733635.91 | 0.383163E+10 | 0.00 | 992446.75 | 0.00 | 0.00 | 0.175246E+09 | 0.00 | 0.50 |
July | 0.00 | 0.528978E+10 | 0.00 | 342230.59 | 0.00 | 0.00 | 0.133585E+09 | 0.00 | 0.47 |
August | 0.00 | 0.589030E+10 | 0.00 | 10816.11 | 0.00 | 0.00 | 92198.43 | 0.00 | 0.45 |
September | 7065430.48 | 0.264165E+10 | 0.00 | 1946745.77 | 0.00 | 0.00 | 0.681990E+09 | 0.00 | 0.57 |
October | 0.890788E+09 | 0.603735E+09 | 0.00 | 4443640.85 | 0.00 | 0.00 | 0.217249E+10 | 0.00 | 0.71 |
November | 0.168829E+10 | 18548514.31 | 0.00 | 3303483.25 | 1179065.48 | 17934869.14 | 0.216406E+10 | 0.00 | 0.66 |
December | 0.310099E+10 | 0.00 | 0.00 | 534575.63 | 0.00 | 0.472215E+09 | 0.397624E+09 | 0.00 | 0.43 |
Annual Sum or Average | 0.124346E+11 | 0.200024E+11 | 0.00 | 21213004.51 | 1639830.23 | 0.419407E+10 | 0.104081E+11 | 0.00 | 0.55 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 10816.11 | 0.00 | 0.00 | 92198.43 | 0.00 | 0.39 |
Maximum of Months | 0.310099E+10 | 0.589030E+10 | 0.00 | 4443640.85 | 1179065.48 | 0.223937E+10 | 0.217249E+10 | 0.00 | 0.71 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.211501E+10 | 0.00 | 0.00 | 19284.26 | 0.00 | 0.310622E+10 | 31880334.95 | 0.00 | 0.41 |
February | 0.180036E+10 | 785962.15 | 0.00 | 501886.08 | 0.00 | 0.172263E+10 | 0.246249E+09 | 0.00 | 0.47 |
March | 0.188722E+10 | 69669150.77 | 0.00 | 1168543.05 | 3503136.58 | 0.150436E+09 | 0.840220E+09 | 0.00 | 0.54 |
April | 0.890369E+09 | 0.246564E+09 | 0.00 | 1402870.50 | 9144161.84 | 6901849.52 | 0.692181E+09 | 0.00 | 0.57 |
May | 0.156598E+09 | 0.107364E+10 | 0.00 | 1739220.88 | 49571799.54 | 0.00 | 0.704416E+09 | 0.00 | 0.60 |
June | 22159558.46 | 0.325222E+10 | 0.00 | 690070.25 | 0.189627E+09 | 0.00 | 0.166974E+09 | 0.00 | 0.48 |
July | 4847708.80 | 0.431454E+10 | 0.00 | 638736.13 | 0.284449E+09 | 0.00 | 0.167301E+09 | 0.00 | 0.45 |
August | 18396.84 | 0.485274E+10 | 0.00 | 201328.23 | 0.318260E+09 | 0.00 | 26056342.58 | 0.00 | 0.44 |
September | 61833975.01 | 0.209999E+10 | 0.00 | 1398299.08 | 0.125245E+09 | 0.00 | 0.560192E+09 | 0.00 | 0.53 |
October | 0.119406E+10 | 0.460010E+09 | 0.00 | 2532572.54 | 30503719.25 | 3481481.05 | 0.126269E+10 | 0.00 | 0.61 |
November | 0.205890E+10 | 9148821.31 | 0.00 | 1700189.91 | 5790890.81 | 71971529.78 | 0.113516E+10 | 0.00 | 0.57 |
December | 0.289623E+10 | 0.00 | 0.00 | 256137.16 | 0.00 | 0.902934E+09 | 0.187019E+09 | 0.00 | 0.44 |
Annual Sum or Average | 0.130876E+11 | 0.163793E+11 | 0.00 | 12249138.08 | 0.101610E+10 | 0.596457E+10 | 0.602034E+10 | 0.00 | 0.51 |
Minimum of Months | 18396.84 | 0.00 | 0.00 | 19284.26 | 0.00 | 0.00 | 26056342.58 | 0.00 | 0.41 |
Maximum of Months | 0.289623E+10 | 0.485274E+10 | 0.00 | 2532572.54 | 0.318260E+09 | 0.310622E+10 | 0.126269E+10 | 0.00 | 0.61 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.191904E+10 | 0.00 | 0.00 | 8631.48 | 0.00 | 0.330937E+10 | 16402202.49 | 0.00 | 0.41 |
February | 0.171871E+10 | 788832.18 | 0.00 | 437037.96 | 0.00 | 0.181248E+10 | 0.210695E+09 | 0.00 | 0.47 |
March | 0.190798E+10 | 67647992.14 | 0.00 | 1060585.18 | 3386931.31 | 0.159560E+09 | 0.766292E+09 | 0.00 | 0.53 |
April | 0.896576E+09 | 0.242740E+09 | 0.00 | 1342899.46 | 8963374.98 | 15943409.89 | 0.658670E+09 | 0.00 | 0.57 |
May | 0.162379E+09 | 0.106878E+10 | 0.00 | 1706330.80 | 49312355.23 | 0.00 | 0.695361E+09 | 0.00 | 0.60 |
June | 22179730.54 | 0.325524E+10 | 0.00 | 696085.09 | 0.189464E+09 | 0.00 | 0.167800E+09 | 0.00 | 0.48 |
July | 4865360.88 | 0.432213E+10 | 0.00 | 651016.69 | 0.284283E+09 | 0.00 | 0.168320E+09 | 0.00 | 0.45 |
August | 30649.35 | 0.486149E+10 | 0.00 | 208809.70 | 0.318126E+09 | 0.00 | 25945875.89 | 0.00 | 0.44 |
September | 65930403.96 | 0.209961E+10 | 0.00 | 1394457.08 | 0.125043E+09 | 0.00 | 0.556502E+09 | 0.00 | 0.53 |
October | 0.119628E+10 | 0.456219E+09 | 0.00 | 2456910.57 | 30271832.20 | 7070827.71 | 0.123423E+10 | 0.00 | 0.61 |
November | 0.207542E+10 | 8410412.87 | 0.00 | 1546356.63 | 6272864.40 | 82184120.07 | 0.106515E+10 | 0.00 | 0.56 |
December | 0.274240E+10 | 0.00 | 0.00 | 219020.88 | 0.00 | 0.104637E+10 | 0.174979E+09 | 0.00 | 0.43 |
Annual Sum or Average | 0.127118E+11 | 0.163831E+11 | 0.00 | 11728141.53 | 0.101512E+10 | 0.643297E+10 | 0.574034E+10 | 0.00 | 0.51 |
Minimum of Months | 30649.35 | 0.00 | 0.00 | 8631.48 | 0.00 | 0.00 | 16402202.49 | 0.00 | 0.41 |
Maximum of Months | 0.274240E+10 | 0.486149E+10 | 0.00 | 2456910.57 | 0.318126E+09 | 0.330937E+10 | 0.123423E+10 | 0.00 | 0.61 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.161014E+10 | 0.00 | 0.00 | 1994.67 | 0.00 | 0.361988E+10 | 5220575.57 | 0.00 | 0.41 |
February | 0.154570E+10 | 782530.02 | 0.00 | 352503.16 | 0.00 | 0.198462E+10 | 0.173549E+09 | 0.00 | 0.46 |
March | 0.191596E+10 | 64432201.17 | 0.00 | 852186.61 | 3208573.99 | 0.200731E+09 | 0.634149E+09 | 0.00 | 0.52 |
April | 0.906262E+09 | 0.235210E+09 | 0.00 | 1137538.29 | 8708529.82 | 29353456.93 | 0.574078E+09 | 0.00 | 0.56 |
May | 0.179301E+09 | 0.104548E+10 | 0.00 | 1531026.97 | 48827835.07 | 0.00 | 0.649428E+09 | 0.00 | 0.59 |
June | 26441876.75 | 0.321671E+10 | 0.00 | 657708.73 | 0.188883E+09 | 0.00 | 0.160968E+09 | 0.00 | 0.48 |
July | 4955621.25 | 0.428302E+10 | 0.00 | 609413.30 | 0.283314E+09 | 0.00 | 0.171347E+09 | 0.00 | 0.45 |
August | 21923.09 | 0.481898E+10 | 0.00 | 192256.54 | 0.317021E+09 | 0.00 | 26639539.60 | 0.00 | 0.44 |
September | 77297890.45 | 0.206759E+10 | 0.00 | 1287194.10 | 0.124155E+09 | 0.00 | 0.528750E+09 | 0.00 | 0.53 |
October | 0.122511E+10 | 0.442207E+09 | 0.00 | 2237118.17 | 29744619.73 | 9166860.25 | 0.113867E+10 | 0.00 | 0.60 |
November | 0.209582E+10 | 7328310.39 | 0.00 | 1275827.82 | 6794186.65 | 0.127398E+09 | 0.915899E+09 | 0.00 | 0.55 |
December | 0.256174E+10 | 0.00 | 0.00 | 164152.20 | 0.00 | 0.122549E+10 | 0.144209E+09 | 0.00 | 0.43 |
Annual Sum or Average | 0.121487E+11 | 0.161817E+11 | 0.00 | 10298920.55 | 0.101066E+10 | 0.719664E+10 | 0.512291E+10 | 0.00 | 0.50 |
Minimum of Months | 21923.09 | 0.00 | 0.00 | 1994.67 | 0.00 | 0.00 | 5220575.57 | 0.00 | 0.41 |
Maximum of Months | 0.256174E+10 | 0.481898E+10 | 0.00 | 2237118.17 | 0.317021E+09 | 0.361988E+10 | 0.113867E+10 | 0.00 | 0.60 |
Report: MechanicalVentilationLoadsMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.195195E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.773688E+10 | 0.00 | 0.00 | 0.38 |
February | 0.223628E+10 | 95348.54 | 0.00 | 547179.00 | 0.00 | 0.421746E+10 | 0.321236E+09 | 0.00 | 0.42 |
March | 0.345423E+10 | 97212555.94 | 0.00 | 1215549.35 | 30196.99 | 0.441657E+09 | 0.976468E+09 | 0.00 | 0.46 |
April | 0.150230E+10 | 0.316543E+09 | 0.00 | 1928434.49 | 14992468.80 | 44391890.53 | 0.990277E+09 | 0.00 | 0.50 |
May | 0.211167E+09 | 0.186767E+10 | 0.00 | 2338813.49 | 40885262.87 | 0.00 | 0.107733E+10 | 0.00 | 0.51 |
June | 19147945.04 | 0.619184E+10 | 0.00 | 870096.67 | 0.102396E+09 | 0.00 | 0.228038E+09 | 0.00 | 0.43 |
July | 266620.56 | 0.817949E+10 | 0.00 | 800854.01 | 0.192953E+09 | 0.00 | 0.302346E+09 | 0.00 | 0.40 |
August | 0.00 | 0.929311E+10 | 0.00 | 121556.94 | 0.143070E+09 | 0.00 | 13098911.54 | 0.00 | 0.40 |
September | 81125686.99 | 0.380437E+10 | 0.00 | 1914533.94 | 98649599.70 | 0.00 | 0.872483E+09 | 0.00 | 0.47 |
October | 0.205274E+10 | 0.796766E+09 | 0.00 | 3522365.27 | 16883307.49 | 32257845.72 | 0.200720E+10 | 0.00 | 0.52 |
November | 0.379699E+10 | 5764042.09 | 0.00 | 1707462.64 | 13880548.99 | 0.312981E+09 | 0.149387E+10 | 0.00 | 0.47 |
December | 0.436904E+10 | 0.00 | 20305.13 | 168410.52 | 0.00 | 0.263400E+10 | 0.182339E+09 | 1455.97 | 0.38 |
Annual Sum or Average | 0.196752E+11 | 0.305529E+11 | 20305.13 | 15135256.32 | 0.623741E+09 | 0.154196E+11 | 0.846470E+10 | 1455.97 | 0.44 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.436904E+10 | 0.929311E+10 | 20305.13 | 3522365.27 | 0.192953E+09 | 0.773688E+10 | 0.200720E+10 | 1455.97 | 0.52 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.853997E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.397630E+10 | 0.00 | 0.00 | 0.38 |
February | 0.100657E+10 | 52360.22 | 0.00 | 249589.17 | 28501.15 | 0.221539E+10 | 0.148557E+09 | 0.00 | 0.42 |
March | 0.171579E+10 | 48557594.06 | 0.00 | 552197.53 | 39145.86 | 0.245726E+09 | 0.451188E+09 | 0.00 | 0.46 |
April | 0.761792E+09 | 0.158123E+09 | 0.00 | 926540.05 | 7667556.74 | 22185458.83 | 0.477463E+09 | 0.00 | 0.51 |
May | 0.114217E+09 | 0.927728E+09 | 0.00 | 1167314.65 | 20412383.01 | 0.00 | 0.539360E+09 | 0.00 | 0.52 |
June | 9482632.38 | 0.309144E+10 | 0.00 | 432958.67 | 51238761.11 | 0.00 | 0.115509E+09 | 0.00 | 0.43 |
July | 155730.46 | 0.408342E+10 | 0.00 | 395376.04 | 95960123.89 | 0.00 | 0.158120E+09 | 0.00 | 0.41 |
August | 0.00 | 0.463837E+10 | 0.00 | 58828.07 | 71153710.49 | 0.00 | 6976505.23 | 0.00 | 0.40 |
September | 40854110.75 | 0.189825E+10 | 0.00 | 962176.74 | 48871956.60 | 0.00 | 0.443590E+09 | 0.00 | 0.47 |
October | 0.104664E+10 | 0.397025E+09 | 0.00 | 1746722.56 | 8366483.76 | 22993621.55 | 0.981939E+09 | 0.00 | 0.52 |
November | 0.185291E+10 | 2779273.36 | 0.00 | 803131.66 | 7033196.38 | 0.225701E+09 | 0.709821E+09 | 0.00 | 0.47 |
December | 0.206537E+10 | 0.00 | 7079.31 | 71379.73 | 0.00 | 0.143310E+10 | 77821343.38 | 907.85 | 0.38 |
Annual Sum or Average | 0.946778E+10 | 0.152458E+11 | 7079.31 | 7366214.86 | 0.310772E+09 | 0.814140E+10 | 0.411034E+10 | 907.85 | 0.45 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.206537E+10 | 0.463837E+10 | 7079.31 | 1746722.56 | 95960123.89 | 0.397630E+10 | 0.981939E+09 | 907.85 | 0.52 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.811078E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.401739E+10 | 0.00 | 0.00 | 0.38 |
February | 0.957859E+09 | 53259.23 | 0.00 | 230652.94 | 68851.93 | 0.226362E+10 | 0.140214E+09 | 0.00 | 0.42 |
March | 0.170318E+10 | 47813600.00 | 0.00 | 501196.86 | 62108.34 | 0.268607E+09 | 0.419753E+09 | 0.00 | 0.45 |
April | 0.779585E+09 | 0.155691E+09 | 0.00 | 866990.39 | 8186137.81 | 21523602.33 | 0.445311E+09 | 0.00 | 0.50 |
May | 0.117837E+09 | 0.921746E+09 | 0.00 | 1129440.89 | 20566702.12 | 0.00 | 0.530036E+09 | 0.00 | 0.52 |
June | 9838650.82 | 0.308722E+10 | 0.00 | 423330.25 | 51329574.89 | 0.00 | 0.113404E+09 | 0.00 | 0.43 |
July | 2798820.23 | 0.407850E+10 | 0.00 | 389413.66 | 96005046.49 | 0.00 | 0.155264E+09 | 0.00 | 0.41 |
August | 0.00 | 0.463373E+10 | 0.00 | 57312.91 | 71223384.88 | 0.00 | 6988999.10 | 0.00 | 0.40 |
September | 42402109.42 | 0.189408E+10 | 0.00 | 936774.97 | 48842466.11 | 0.00 | 0.436821E+09 | 0.00 | 0.47 |
October | 0.106683E+10 | 0.393893E+09 | 0.00 | 1688690.70 | 8400746.63 | 26702645.67 | 0.940975E+09 | 0.00 | 0.52 |
November | 0.185328E+10 | 2606636.19 | 0.00 | 748165.32 | 7270264.72 | 0.243778E+09 | 0.669952E+09 | 0.00 | 0.47 |
December | 0.201485E+10 | 0.00 | 7050.63 | 64405.16 | 0.00 | 0.148635E+10 | 70052027.76 | 1003.81 | 0.38 |
Annual Sum or Average | 0.935953E+10 | 0.152153E+11 | 7050.63 | 7036374.07 | 0.311955E+09 | 0.832797E+10 | 0.392877E+10 | 1003.81 | 0.44 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.201485E+10 | 0.463373E+10 | 7050.63 | 1688690.70 | 96005046.49 | 0.401739E+10 | 0.940975E+09 | 1003.81 | 0.52 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.570260E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.425292E+10 | 0.00 | 0.00 | 0.38 |
February | 0.818649E+09 | 53599.79 | 0.00 | 189541.81 | 244444.11 | 0.239769E+10 | 0.123772E+09 | 0.00 | 0.41 |
March | 0.165129E+10 | 44826195.48 | 0.00 | 379080.94 | 151615.45 | 0.347781E+09 | 0.344276E+09 | 0.00 | 0.45 |
April | 0.781078E+09 | 0.143980E+09 | 0.00 | 784729.49 | 9490063.30 | 33730147.59 | 0.406501E+09 | 0.00 | 0.50 |
May | 0.125560E+09 | 0.894181E+09 | 0.00 | 1009661.10 | 21955818.26 | 0.00 | 0.503268E+09 | 0.00 | 0.51 |
June | 14498465.26 | 0.306255E+10 | 0.00 | 400370.38 | 51187660.04 | 0.00 | 0.105792E+09 | 0.00 | 0.43 |
July | 5486037.24 | 0.405842E+10 | 0.00 | 364063.74 | 95689784.42 | 0.00 | 0.153854E+09 | 0.00 | 0.41 |
August | 0.00 | 0.461723E+10 | 0.00 | 55081.10 | 71126214.97 | 0.00 | 7152277.60 | 0.00 | 0.40 |
September | 50666281.22 | 0.187587E+10 | 0.00 | 879952.30 | 48557808.07 | 0.00 | 0.416312E+09 | 0.00 | 0.46 |
October | 0.107442E+10 | 0.382769E+09 | 0.00 | 1574571.94 | 8507532.62 | 50865669.88 | 0.875530E+09 | 0.00 | 0.51 |
November | 0.182402E+10 | 2202336.43 | 0.00 | 628952.24 | 7803712.79 | 0.308594E+09 | 0.586896E+09 | 0.00 | 0.46 |
December | 0.176382E+10 | 0.00 | 6909.14 | 46043.46 | 0.00 | 0.173853E+10 | 57148146.44 | 1351.80 | 0.38 |
Annual Sum or Average | 0.867974E+10 | 0.150821E+11 | 6909.14 | 6312048.51 | 0.314715E+09 | 0.913011E+10 | 0.358050E+10 | 1351.80 | 0.44 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.182402E+10 | 0.461723E+10 | 6909.14 | 1574571.94 | 95689784.42 | 0.425292E+10 | 0.875530E+09 | 1351.80 | 0.51 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.254697E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.453995E+10 | 0.00 | 0.00 | 0.38 |
February | 0.555758E+09 | 115289.69 | 0.00 | 151322.08 | 267532.73 | 0.262851E+10 | 0.108328E+09 | 0.00 | 0.42 |
March | 0.144724E+10 | 41641820.72 | 0.00 | 245223.62 | 354808.48 | 0.590171E+09 | 0.242244E+09 | 0.00 | 0.45 |
April | 0.733007E+09 | 0.133013E+09 | 363591.00 | 629884.77 | 11171795.26 | 79243830.93 | 0.367745E+09 | 136.33 | 0.51 |
May | 0.140062E+09 | 0.884019E+09 | 0.00 | 899562.01 | 22696753.47 | 0.00 | 0.482303E+09 | 0.00 | 0.52 |
June | 16364501.30 | 0.304707E+10 | 0.00 | 442728.65 | 50787538.11 | 0.00 | 0.111162E+09 | 0.00 | 0.44 |
July | 9337979.64 | 0.411048E+10 | 0.00 | 328228.09 | 95675338.21 | 0.00 | 0.156438E+09 | 0.00 | 0.40 |
August | 308143.85 | 0.466537E+10 | 0.00 | 106654.86 | 71215953.35 | 0.00 | 15949772.40 | 0.00 | 0.40 |
September | 68263571.95 | 0.188905E+10 | 0.00 | 917345.89 | 48188146.93 | 0.00 | 0.401432E+09 | 0.00 | 0.48 |
October | 0.972583E+09 | 0.381631E+09 | 0.00 | 1603472.22 | 8224067.15 | 0.134477E+09 | 0.928047E+09 | 0.00 | 0.54 |
November | 0.151713E+10 | 1822869.25 | 2035297.26 | 562320.81 | 2887278.08 | 0.609263E+09 | 0.558123E+09 | 469.59 | 0.47 |
December | 0.105618E+10 | 0.00 | 0.00 | 32604.91 | 0.00 | 0.242151E+10 | 42683969.61 | 0.00 | 0.38 |
Annual Sum or Average | 0.677093E+10 | 0.151542E+11 | 2398888.25 | 5919347.92 | 0.311469E+09 | 0.110031E+11 | 0.341446E+10 | 605.92 | 0.45 |
Minimum of Months | 308143.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.151713E+10 | 0.466537E+10 | 2035297.26 | 1603472.22 | 95675338.21 | 0.453995E+10 | 0.928047E+09 | 469.59 | 0.54 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.147583E+12 | 0.294238E+11 | 0.00 | 0.659388E+11 | 0.170344E+11 |
February | 0.156993E+12 | 0.207767E+11 | 0.00 | 0.465609E+11 | 0.122375E+11 |
March | 0.252172E+12 | 0.129674E+11 | 0.00 | 0.330057E+11 | 0.128502E+11 |
April | 0.300181E+12 | 0.492784E+10 | 0.00 | 0.161619E+11 | 0.387322E+11 |
May | 0.342572E+12 | -0.339210E+10 | 0.00 | -0.342122E+10 | 0.884651E+11 |
June | 0.341193E+12 | -0.156170E+11 | 0.00 | -0.391545E+11 | 0.164900E+12 |
July | 0.330547E+12 | -0.210383E+11 | 0.00 | -0.538092E+11 | 0.198779E+12 |
August | 0.304415E+12 | -0.237081E+11 | 0.00 | -0.626304E+11 | 0.220329E+12 |
September | 0.225738E+12 | -0.908194E+10 | 0.00 | -0.195837E+11 | 0.127672E+12 |
October | 0.202088E+12 | 0.630963E+10 | 0.00 | 0.233299E+11 | 0.441046E+11 |
November | 0.132698E+12 | 0.141421E+11 | 0.00 | 0.388813E+11 | 0.740433E+10 |
December | 0.116299E+12 | 0.221925E+11 | 0.00 | 0.501717E+11 | 0.814265E+10 |
Annual Sum or Average | 0.285248E+13 | 0.379025E+11 | 0.00 | 0.954511E+11 | 0.940651E+12 |
Minimum of Months | 0.116299E+12 | -0.237081E+11 | 0.00 | -0.626304E+11 | 0.740433E+10 |
Maximum of Months | 0.342572E+12 | 0.294238E+11 | 0.00 | 0.659388E+11 | 0.220329E+12 |