Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:37
Tabular Output Report in Format: HTML
Building: RetailStripmall
Environment: RUNPERIOD 1 ** New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820
Simulation Timestamp: 2023-10-16 08:37:19
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:19
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1248.39 | 597.22 | 597.22 |
Net Site Energy | 1248.39 | 597.22 | 597.22 |
Total Source Energy | 3936.22 | 1883.07 | 1883.07 |
Net Source Energy | 3936.22 | 1883.07 | 1883.07 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 2090.32 |
Net Conditioned Building Area | 2090.32 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 8.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 494.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 366.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 60.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 128.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 131.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 58.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1240.02 | 8.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 8.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 494.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 366.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 60.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 128.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 131.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 58.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 8.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 494.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 366.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 60.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 128.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 131.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 58.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 204.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 327.77 | 4.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Other | 61.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 593.22 | 4.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 204.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 327.77 | 4.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Other | 61.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 593.22 | 4.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1240.024 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1240.024 | 100.00 |
Total On-Site and Utility Electric Sources | 1240.024 | 100.00 |
Total Electricity End Uses | 1240.024 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 87.30 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 87.30 | 100.00 |
Total Water End Uses | 87.30 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 1.17 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 1426.83 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTRIPMALL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 1B
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY IND_DELHI_NEWDELHI
| Environment |ZoneCoolingSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ZoneHeatingSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ZoneElectricSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |SpaceGainsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |PeakSpaceGainsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |SpaceGainComponentsAtCoolingPeakMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ComfortReportSimple55Monthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |OccupantComfortDataSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |DXReportMonthly
| PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL | PSZ-AC_3:3 COOLING COIL | PSZ-AC_4:4 COOLING COIL | PSZ-AC_5:5 COOLING COIL | PSZ-AC_6:6 COOLING COIL | PSZ-AC_7:7 COOLING COIL | PSZ-AC_8:8 COOLING COIL | PSZ-AC_9:9 COOLING COIL | PSZ-AC_10:10 COOLING COIL |WindowReportMonthly
| LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR |WindowEnergyReportMonthly
| LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR |WindowZoneSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |WindowEnergyZoneSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| GAS TANK1 | GAS TANK2 | GAS TANK3 | GAS TANK4 | GAS TANK5 | GAS TANK6 | GAS TANK7 |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC_1:1 HEATING COIL | PSZ-AC_2:2 HEATING COIL | PSZ-AC_3:3 HEATING COIL | PSZ-AC_4:4 HEATING COIL | PSZ-AC_5:5 HEATING COIL | PSZ-AC_6:6 HEATING COIL | PSZ-AC_7:7 HEATING COIL | PSZ-AC_8:8 HEATING COIL | PSZ-AC_9:9 HEATING COIL | PSZ-AC_10:10 HEATING COIL | PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL | PSZ-AC_3:3 COOLING COIL | PSZ-AC_4:4 COOLING COIL | PSZ-AC_5:5 COOLING COIL | PSZ-AC_6:6 COOLING COIL | PSZ-AC_7:7 COOLING COIL | PSZ-AC_8:8 COOLING COIL | PSZ-AC_9:9 COOLING COIL | PSZ-AC_10:10 COOLING COIL |FanReportMonthly
| PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN |ZoneTemperatureOscillationReportMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |MechanicalVentilationLoadsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:19
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:37 |
RunPeriod | RUNPERIOD 1 |
Weather File | New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820 |
Latitude [deg] | 28.58 |
Longitude [deg] | 77.20 |
Elevation [m] | 216.00 |
Time Zone | 5.50 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Above Ground Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Window Opening Area [m2] | 124.40 | 0.00 | 0.00 | 124.40 | 0.00 |
Gross Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Above Ground Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Above Ground Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Window Opening Area [m2] | 124.40 | 0.00 | 0.00 | 124.40 | 0.00 |
Gross Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Above Ground Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Total | |
Gross Roof Area [m2] | 2090.32 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
LGSTORE1 | 348.39 | Yes | Yes | 1805.20 | 1.00 | 276.30 | 0.00 | 20.77 | 20.77 | 15.3022 | 6.19 | 4.3000 |
SMSTORE1 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.38 | 10.38 | 18.2890 | 6.19 | 4.3000 |
SMSTORE2 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 16.6533 | 6.19 | 4.3000 |
SMSTORE3 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 16.6533 | 6.19 | 4.3000 |
SMSTORE4 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 16.6533 | 6.19 | 4.3000 |
LGSTORE2 | 348.39 | Yes | Yes | 1805.20 | 1.00 | 157.89 | 0.00 | 20.72 | 20.72 | 9.5842 | 6.19 | 4.3000 |
SMSTORE5 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 9.6995 | 6.19 | 4.3000 |
SMSTORE6 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 9.6995 | 6.19 | 4.3000 |
SMSTORE7 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 9.6995 | 6.19 | 4.3000 |
SMSTORE8 | 174.19 | Yes | Yes | 902.60 | 1.00 | 197.36 | 0.00 | 10.36 | 10.36 | 9.6995 | 6.19 | 4.3000 |
Total | 2090.32 | 10831.20 | 1184.15 | 0.00 | 124.40 | 124.40 | 13.0683 | 6.19 | 4.3000 | |||
Conditioned Total | 2090.32 | 10831.20 | 1184.15 | 0.00 | 124.40 | 124.40 | 13.0683 | 6.19 | 4.3000 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
LGSTORE1 | 348.39 | Yes | Yes | 1.00 | LGSTORE1 | GENERAL | LGSTORE1 | 15.3022 | 6.19 | 4.3000 | |
SMSTORE1 | 174.19 | Yes | Yes | 1.00 | SMSTORE1 | GENERAL | SMSTORE1 | 18.2890 | 6.19 | 4.3000 | |
SMSTORE2 | 174.19 | Yes | Yes | 1.00 | SMSTORE2 | GENERAL | SMSTORE2 | 16.6533 | 6.19 | 4.3000 | |
SMSTORE3 | 174.19 | Yes | Yes | 1.00 | SMSTORE3 | GENERAL | SMSTORE3 | 16.6533 | 6.19 | 4.3000 | |
SMSTORE4 | 174.19 | Yes | Yes | 1.00 | SMSTORE4 | GENERAL | SMSTORE4 | 16.6533 | 6.19 | 4.3000 | |
LGSTORE2 | 348.39 | Yes | Yes | 1.00 | LGSTORE2 | GENERAL | LGSTORE2 | 9.5842 | 6.19 | 4.3000 | |
SMSTORE5 | 174.19 | Yes | Yes | 1.00 | SMSTORE5 | GENERAL | SMSTORE5 | 9.6995 | 6.19 | 4.3000 | |
SMSTORE6 | 174.19 | Yes | Yes | 1.00 | SMSTORE6 | GENERAL | SMSTORE6 | 9.6995 | 6.19 | 4.3000 | |
SMSTORE7 | 174.19 | Yes | Yes | 1.00 | SMSTORE7 | GENERAL | SMSTORE7 | 9.6995 | 6.19 | 4.3000 | |
SMSTORE8 | 174.19 | Yes | Yes | 1.00 | SMSTORE8 | GENERAL | SMSTORE8 | 9.6995 | 6.19 | 4.3000 | |
Total | 2090.32 | 13.0683 | 3.10 | 4.3000 | |||||||
Conditioned Total | 2090.32 | 13.0683 | 3.10 | 4.3000 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 2090.32 | 2090.32 | 0.00 | 0.00 | 13.0683 | 6.19 | 4.3000 |
Total | 2090.32 | 2090.32 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:19
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 10-JUN-15:00 | 02-JAN-08:09 | - | - | - | - | - | - | - | - | - | - | 06-JAN-13:09 |
Heating | 0.00 | 124439.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 85981.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 23459.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 8059.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 12730.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 5415.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 135646.39 | 124439.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 124439.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 85981.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 23459.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 8059.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 12730.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 5415.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:19
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 9.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1566.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1161.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 190.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 405.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 417.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 185.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 3927.16 | 9.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 4.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 749.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 555.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 90.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 194.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 199.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 88.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1878.74 | 4.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 4.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 749.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 555.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 90.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 194.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 199.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 88.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1878.74 | 4.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:19
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
LGSTORE1 DIRECT AIR | 2.81 |
SMSTORE1 DIRECT AIR | 1.44 |
SMSTORE2 DIRECT AIR | 1.44 |
SMSTORE3 DIRECT AIR | 1.44 |
SMSTORE4 DIRECT AIR | 1.43 |
LGSTORE2 DIRECT AIR | 2.53 |
SMSTORE5 DIRECT AIR | 1.34 |
SMSTORE6 DIRECT AIR | 1.34 |
SMSTORE7 DIRECT AIR | 1.34 |
SMSTORE8 DIRECT AIR | 1.57 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC_1:1 | 2.81 | 2.81 | 2.81 | 2.81 | 2.81 | 2.81 | 1.00 | 1.00 | 2.81 |
PSZ-AC_2:2 | 1.44 | 1.44 | 1.44 | 1.44 | 1.44 | 1.44 | 1.00 | 1.00 | 1.44 |
PSZ-AC_3:3 | 1.44 | 1.44 | 1.44 | 1.44 | 1.44 | 1.44 | 1.00 | 1.00 | 1.44 |
PSZ-AC_4:4 | 1.44 | 1.44 | 1.44 | 1.44 | 1.44 | 1.44 | 1.00 | 1.000000 | 1.44 |
PSZ-AC_5:5 | 1.43 | 1.43 | 1.43 | 1.43 | 1.43 | 1.43 | 1.00 | 1.00 | 1.43 |
PSZ-AC_6:6 | 2.53 | 2.53 | 2.53 | 2.53 | 2.53 | 2.53 | 1.00 | 1.00 | 2.53 |
PSZ-AC_7:7 | 1.34 | 1.34 | 1.34 | 1.34 | 1.34 | 1.34 | 1.00 | 1.00 | 1.34 |
PSZ-AC_8:8 | 1.34 | 1.34 | 1.34 | 1.34 | 1.34 | 1.34 | 1.00 | 1.00 | 1.34 |
PSZ-AC_9:9 | 1.34 | 1.34 | 1.34 | 1.34 | 1.34 | 1.34 | 1.00 | 1.000000 | 1.34 |
PSZ-AC_10:10 | 1.57 | 1.57 | 1.57 | 1.57 | 1.57 | 1.57 | 1.00 | 1.00 | 1.57 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC_1:1_OA_CONTROLLER | 2.81 | 0.411479 |
PSZ-AC_2:2_OA_CONTROLLER | 1.44 | 0.205739 |
PSZ-AC_3:3_OA_CONTROLLER | 1.44 | 0.205739 |
PSZ-AC_4:4_OA_CONTROLLER | 1.44 | 0.205739 |
PSZ-AC_5:5_OA_CONTROLLER | 1.43 | 0.205739 |
PSZ-AC_6:6_OA_CONTROLLER | 2.53 | 0.411479 |
PSZ-AC_7:7_OA_CONTROLLER | 1.34 | 0.205739 |
PSZ-AC_8:8_OA_CONTROLLER | 1.34 | 0.205739 |
PSZ-AC_9:9_OA_CONTROLLER | 1.34 | 0.205739 |
PSZ-AC_10:10_OA_CONTROLLER | 1.57 | 0.205739 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | 2.81 | 3006.16 |
PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | 1.44 | 1538.32 |
PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | 1.44 | 1538.19 |
PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | 1.44 | 1541.61 |
PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | 1.43 | 1532.17 |
PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | 2.53 | 2712.08 |
PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | 1.34 | 1484.39 |
PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | 1.34 | 1479.42 |
PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | 1.34 | 1487.17 |
PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | 1.57 | 1680.33 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC_1:1_UNITARY_PACKAGE_DX | 2.81 | 2.81 | 2.81 | 1.85 | 64861.65 | 69785.06 | 40.00 | 1.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_DX | 1.44 | 1.44 | 1.44 | 0.948831 | 33107.66 | 35626.56 | 40.00 | 1.00 |
PSZ-AC_3:3_UNITARY_PACKAGE_DX | 1.44 | 1.44 | 1.44 | 0.948747 | 33105.47 | 35623.72 | 40.00 | 1.00 |
PSZ-AC_4:4_UNITARY_PACKAGE_DX | 1.44 | 1.44 | 1.44 | 0.950855 | 33164.68 | 35694.90 | 40.00 | 1.00 |
PSZ-AC_5:5_UNITARY_PACKAGE_DX | 1.43 | 1.43 | 1.43 | 0.945035 | 33001.29 | 35498.41 | 40.00 | 1.00 |
PSZ-AC_6:6_UNITARY_PACKAGE_DX | 2.53 | 2.53 | 2.53 | 1.67 | 59708.33 | 63661.27 | 40.00 | 1.00 |
PSZ-AC_7:7_UNITARY_PACKAGE_DX | 1.34 | 1.34 | 1.34 | 0.884873 | 31308.01 | 33467.33 | 40.00 | 1.00 |
PSZ-AC_8:8_UNITARY_PACKAGE_DX | 1.34 | 1.34 | 1.34 | 0.881915 | 31224.56 | 33367.46 | 40.00 | 1.00 |
PSZ-AC_9:9_UNITARY_PACKAGE_DX | 1.34 | 1.34 | 1.34 | 0.886531 | 31355.18 | 33523.31 | 40.00 | 1.00 |
PSZ-AC_10:10_UNITARY_PACKAGE_DX | 1.57 | 1.57 | 1.57 | 1.04 | 35310.39 | 38583.76 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-AC_1:1 COOLING COIL | 2.81 | 1.40 | 1.87 | 64861.65 | 32430.83 | 0.724600 | 0.724600 |
PSZ-AC_2:2 COOLING COIL | 1.44 | 0.718811 | 0.958413 | 33107.66 | 16553.83 | 0.725270 | 0.725270 |
PSZ-AC_3:3 COOLING COIL | 1.44 | 0.718747 | 0.958327 | 33105.47 | 16552.74 | 0.725260 | 0.725260 |
PSZ-AC_4:4 COOLING COIL | 1.44 | 0.720345 | 0.960460 | 33164.68 | 16582.34 | 0.725380 | 0.725380 |
PSZ-AC_5:5 COOLING COIL | 1.43 | 0.715936 | 0.954580 | 33001.29 | 16500.65 | 0.725060 | 0.725060 |
PSZ-AC_6:6 COOLING COIL | 2.53 | 1.27 | 1.69 | 59708.33 | 29854.17 | 0.717340 | 0.717340 |
PSZ-AC_7:7 COOLING COIL | 1.34 | 0.670358 | 0.893813 | 31308.01 | 15654.00 | 0.720620 | 0.720620 |
PSZ-AC_8:8 COOLING COIL | 1.34 | 0.668117 | 0.890820 | 31224.56 | 15612.28 | 0.720450 | 0.720450 |
PSZ-AC_9:9 COOLING COIL | 1.34 | 0.671615 | 0.895487 | 31355.18 | 15677.59 | 0.720720 | 0.720720 |
PSZ-AC_10:10 COOLING COIL | 1.57 | 0.785168 | 1.05 | 35310.39 | 17655.19 | 0.732660 | 0.732660 |
Design Size Nominal Capacity [W] | |
PSZ-AC_1:1 HEATING COIL | 69785.06 |
PSZ-AC_2:2 HEATING COIL | 35626.56 |
PSZ-AC_3:3 HEATING COIL | 35623.72 |
PSZ-AC_4:4 HEATING COIL | 35694.90 |
PSZ-AC_5:5 HEATING COIL | 35498.41 |
PSZ-AC_6:6 HEATING COIL | 63661.27 |
PSZ-AC_7:7 HEATING COIL | 33467.33 |
PSZ-AC_8:8 HEATING COIL | 33367.46 |
PSZ-AC_9:9 HEATING COIL | 33523.31 |
PSZ-AC_10:10 HEATING COIL | 38583.76 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:19
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
LGSTORE1_WALL_3 | LGSTORE1_WALL_3_DOOR_1 | LGSTORE1_WALL_3_DOOR_2 | |
LGSTORE1_WALL_1 | LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | |
SMSTORE1_WALL_1 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | |
SMSTORE1_WALL_3 | SMSTORE1_WALL_3_DOOR | |
SMSTORE2_WALL_1 | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | |
SMSTORE2_WALL_3 | SMSTORE2_WALL_3_DOOR | |
SMSTORE3_WALL_1 | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | |
SMSTORE3_WALL_3 | SMSTORE3_WALL_3_DOOR | |
SMSTORE4_WALL_1 | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | |
SMSTORE4_WALL_3 | SMSTORE4_WALL_3_DOOR | |
LGSTORE2_WALL_3 | LGSTORE2_WALL_3_DOOR_1 | LGSTORE2_WALL_3_DOOR_2 | |
LGSTORE2_WALL_1 | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | |
SMSTORE5_WALL_1 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | |
SMSTORE5_WALL_3 | SMSTORE5_WALL_3_DOOR | |
SMSTORE6_WALL_1 | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | |
SMSTORE6_WALL_3 | SMSTORE6_WALL_3_DOOR | |
SMSTORE7_WALL_1 | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | |
SMSTORE7_WALL_3 | SMSTORE7_WALL_3_DOOR | |
SMSTORE8_WALL_1 | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR | |
SMSTORE8_WALL_3 | SMSTORE8_WALL_3_DOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:19
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:19
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 25.10 | 19.60 | 14.50 | 13.40 | 17.00 | 22.40 | 29.10 | 33.00 | 33.60 | 31.70 | 30.00 | 28.70 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820 | 28.58 | 77.20 | 5.50 | 216.00 | 98757 | 1.1738 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 24.84 | 20.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RetailStripmall | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 10 | 118 | 48 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | LGSTORE1 | 0.0 | 0.00 | 0.00 | 0.00 | 7.62 | 11.43 | 2.59 | 1 | 1 | 1 | 0.00 | 15.24 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 1805.20 | TARP | TARP | 348.39 | 276.30 | 247.74 | 20.77 | 6 | 8 | 0 | Yes |
2 | SMSTORE1 | 0.0 | 0.00 | 0.00 | 0.00 | 19.05 | 11.43 | 2.59 | 1 | 1 | 1 | 15.24 | 22.86 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.66 | 10.38 | 6 | 4 | 0 | Yes |
3 | SMSTORE2 | 0.0 | 0.00 | 0.00 | 0.00 | 26.67 | 11.43 | 2.59 | 1 | 1 | 1 | 22.86 | 30.48 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
4 | SMSTORE3 | 0.0 | 0.00 | 0.00 | 0.00 | 34.29 | 11.43 | 2.59 | 1 | 1 | 1 | 30.48 | 38.10 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
5 | SMSTORE4 | 0.0 | 0.00 | 0.00 | 0.00 | 41.91 | 11.43 | 2.59 | 1 | 1 | 1 | 38.10 | 45.72 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
6 | LGSTORE2 | 0.0 | 0.00 | 0.00 | 0.00 | 53.34 | 11.43 | 2.59 | 1 | 1 | 1 | 45.72 | 60.96 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 1805.20 | TARP | TARP | 348.39 | 157.89 | 129.41 | 20.72 | 6 | 8 | 0 | Yes |
7 | SMSTORE5 | 0.0 | 0.00 | 0.00 | 0.00 | 64.77 | 11.43 | 2.59 | 1 | 1 | 1 | 60.96 | 68.58 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
8 | SMSTORE6 | 0.0 | 0.00 | 0.00 | 0.00 | 72.39 | 11.43 | 2.59 | 1 | 1 | 1 | 68.58 | 76.20 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
9 | SMSTORE7 | 0.0 | 0.00 | 0.00 | 0.00 | 80.01 | 11.43 | 2.59 | 1 | 1 | 1 | 76.20 | 83.82 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
10 | SMSTORE8 | 0.0 | 0.00 | 0.00 | 0.00 | 87.63 | 11.43 | 2.59 | 1 | 1 | 1 | 83.82 | 91.44 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 197.36 | 183.12 | 10.36 | 6 | 4 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | LGSTORE1 | 348.39 | 56.3 | 6.193 | 0.161 | 15.302 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 19.602 | No |
2 | SMSTORE1 | 174.19 | 28.1 | 6.194 | 0.161 | 18.289 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 22.589 | No |
3 | SMSTORE2 | 174.19 | 28.1 | 6.194 | 0.161 | 16.653 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 20.953 | No |
4 | SMSTORE3 | 174.19 | 28.1 | 6.194 | 0.161 | 16.653 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 20.953 | No |
5 | SMSTORE4 | 174.19 | 28.1 | 6.194 | 0.161 | 16.653 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 20.953 | No |
6 | LGSTORE2 | 348.39 | 56.3 | 6.193 | 0.161 | 9.584 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 13.884 | No |
7 | SMSTORE5 | 174.19 | 28.1 | 6.194 | 0.161 | 9.699 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 13.999 | No |
8 | SMSTORE6 | 174.19 | 28.1 | 6.194 | 0.161 | 9.699 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 13.999 | No |
9 | SMSTORE7 | 174.19 | 28.1 | 6.194 | 0.161 | 9.699 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 13.999 | No |
10 | SMSTORE8 | 174.19 | 28.1 | 6.194 | 0.161 | 9.699 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 13.999 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | LGSTORE1 | TYPE1_OCC_SCH | LGSTORE1 | 348.39 | 56.3 | 56.3 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 56 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | SMSTORE1 | TYPE1_OCC_SCH | SMSTORE1 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | SMSTORE2 | TYPE2_OCC_SCH | SMSTORE2 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | SMSTORE3 | TYPE2_OCC_SCH | SMSTORE3 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | SMSTORE4 | TYPE2_OCC_SCH | SMSTORE4 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | LGSTORE2 | TYPE3_OCC_SCH | LGSTORE2 | 348.39 | 56.3 | 56.3 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 56 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | SMSTORE5 | TYPE3_OCC_SCH | SMSTORE5 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | SMSTORE6 | TYPE3_OCC_SCH | SMSTORE6 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | SMSTORE7 | TYPE3_OCC_SCH | SMSTORE7 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | SMSTORE8 | TYPE3_OCC_SCH | SMSTORE8 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | LGSTORE1_LIGHTS | LTG_SCH_BASE_LPD1 | LGSTORE1 | 348.39 | 56.3 | 3346.345 | 9.605 | 59.490 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3346.345 |
2 | LGSTORE1_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | LGSTORE1 | 348.39 | 56.3 | 1984.726 | 5.697 | 35.284 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1984.726 |
3 | SMSTORE1_LIGHTS | LTG_SCH_BASE_SMALL_LPD1 | SMSTORE1 | 174.19 | 28.1 | 1693.257 | 9.721 | 60.206 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1693.257 |
4 | SMSTORE1_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | SMSTORE1 | 174.19 | 28.1 | 1492.567 | 8.568 | 53.070 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1492.567 |
5 | SMSTORE2_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE2 | 174.19 | 28.1 | 1689.582 | 9.699 | 60.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1689.582 |
6 | SMSTORE2_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE2 | 174.19 | 28.1 | 1211.319 | 6.954 | 43.070 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1211.319 |
7 | SMSTORE3_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE3 | 174.19 | 28.1 | 1689.582 | 9.699 | 60.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1689.582 |
8 | SMSTORE3_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE3 | 174.19 | 28.1 | 1211.319 | 6.954 | 43.070 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1211.319 |
9 | SMSTORE4_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE4 | 174.19 | 28.1 | 1689.582 | 9.699 | 60.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1689.582 |
10 | SMSTORE4_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE4 | 174.19 | 28.1 | 1211.319 | 6.954 | 43.070 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1211.319 |
11 | LGSTORE2_LIGHTS | LTG_SCH_BASE_LPD2 | LGSTORE2 | 348.39 | 56.3 | 3338.998 | 9.584 | 59.359 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3338.998 |
12 | LGSTORE2_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | LGSTORE2 | 348.39 | 56.3 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
13 | SMSTORE5_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE5 | 174.19 | 28.1 | 1689.582 | 9.699 | 60.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1689.582 |
14 | SMSTORE5_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE5 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
15 | SMSTORE6_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE6 | 174.19 | 28.1 | 1689.582 | 9.699 | 60.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1689.582 |
16 | SMSTORE6_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE6 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
17 | SMSTORE7_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE7 | 174.19 | 28.1 | 1689.582 | 9.699 | 60.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1689.582 |
18 | SMSTORE7_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE7 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
19 | SMSTORE8_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE8 | 174.19 | 28.1 | 1689.582 | 9.699 | 60.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1689.582 |
20 | SMSTORE8_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE8 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LGSTORE1_MISCPLUG_EQUIP | TYPE1_EQUIP_SCH | LGSTORE1 | 348.39 | 56.3 | 1498.062 | 4.300 | 26.632 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1498.062 |
2 | SMSTORE1_MISCPLUG_EQUIP | TYPE1_EQUIP_SCH | SMSTORE1 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
3 | SMSTORE2_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE2 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
4 | SMSTORE3_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE3 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
5 | SMSTORE4_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE4 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
6 | LGSTORE2_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | LGSTORE2 | 348.39 | 56.3 | 1498.062 | 4.300 | 26.632 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1498.062 |
7 | SMSTORE5_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE5 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
8 | SMSTORE6_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE6 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
9 | SMSTORE7_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE7 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
10 | SMSTORE8_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE8 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.2832 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
5 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 1.028 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
6 | LGSTORE1_FLOOR_FFACTOR | 36 | 2 | 7 | 0.167 | 0.1995 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
7 | SMSTORE1_FLOOR_FFACTOR | 37 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
8 | SMSTORE2_FLOOR_FFACTOR | 38 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | SMSTORE3_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
10 | SMSTORE4_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
11 | LGSTORE2_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | SMSTORE5_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | SMSTORE6_FLOOR_FFACTOR | 43 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | SMSTORE7_FLOOR_FFACTOR | 44 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | SMSTORE8_FLOOR_FFACTOR | 45 | 2 | 7 | 0.167 | 0.2888 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
6 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 3.472 |
7 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
8 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
10 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7383 |
11 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
12 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.937 |
13 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
14 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
15 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
16 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
17 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
18 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
19 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
20 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
21 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
22 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
23 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
24 | ~FC_Insulation_7 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_8 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_9 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_10 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.386 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
14 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
15 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
16 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
17 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
18 | 3 | -0.61927053E-06 | 0.12767249E-08 | -0.37968499E-05 | 0.16832131E-17 |
19 | 2 | 0.77611055 | 0.17315568E-02 | 1.0534842 | -0.72792597E-06 |
20 | 1 | -21.915918 | 0.11588205 | -6.3286394 | 0.20197014 |
21 | 0 | 21.365777 | 0.10835518 | 5.5011278 | |
22 | 7 | -0.27626373E-12 | 0.13670118E-14 | -0.80430638E-13 | 0.78416590E-16 |
23 | 6 | 0.25658824E-07 | 0.27941242E-09 | 0.59030768E-08 | -0.11909973E-12 |
24 | 5 | -0.17468948E-03 | 0.24402707E-05 | -0.90039107E-04 | 0.58437388E-08 |
25 | 4 | 0.27392503 | 0.12091412E-02 | 0.93138911E-01 | -0.31018751E-04 |
26 | 3 | -6.9050330 | 0.38055846E-01 | -2.2317352 | 0.27239655E-01 |
27 | 2 | 39.679098 | 0.13717309 | 14.824430 | -0.32006664 |
28 | 1 | -79.631803 | 0.62641324E-01 | -28.746304 | 1.0591428 |
29 | 0 | 46.824345 | 0.12749544E-02 | 16.300917 | |
30 | 7 | -0.21163652E-08 | -0.68723841E-15 | 0.43910983E-14 | -0.57684426E-16 |
31 | 6 | 0.56109385E-05 | 0.38186281E-08 | 0.31898696E-02 | -0.26759299E-04 |
32 | 5 | -0.40164657E-03 | 0.22608617E-05 | -0.22372456 | 0.19561502E-02 |
33 | 4 | 0.92272104E-02 | 0.10289840E-03 | 4.8295456 | -0.45264980E-01 |
34 | 3 | -0.80993241E-01 | 0.81813938E-03 | -38.021416 | 0.39865375 |
35 | 2 | 0.28754352 | 0.13608947E-02 | 116.48395 | -1.4179393 |
36 | 1 | -0.41499682 | 0.41453381E-03 | -143.90731 | 2.0490399 |
37 | 0 | 0.20232414 | 0.10048102E-04 | 60.838472 | |
38 | 7 | -0.37862368E-08 | -0.38757603E-14 | 0.11479940E-14 | -0.41635801E-16 |
39 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
40 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
41 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
42 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
43 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
44 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
45 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
46 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479937E-14 | -0.41635796E-16 |
47 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
48 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
49 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
50 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
51 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
52 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
53 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
54 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479940E-14 | -0.41635801E-16 |
55 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
56 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
57 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
58 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
59 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
60 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
61 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
62 | 7 | -0.37862368E-08 | -0.38757603E-14 | 0.11479940E-14 | -0.41635801E-16 |
63 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
64 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
65 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
66 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
67 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
68 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
69 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
70 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479937E-14 | -0.41635796E-16 |
71 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
72 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
73 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
74 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
75 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
76 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
77 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
78 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479937E-14 | -0.41635796E-16 |
79 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
80 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
81 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
82 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
83 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
84 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
85 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
86 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479940E-14 | -0.41635801E-16 |
87 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
88 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
89 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
90 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
91 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
92 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
93 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
94 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479936E-14 | -0.41635794E-16 |
95 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
96 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
97 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
98 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
99 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
100 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
101 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
102 | 7 | -0.14484255E-08 | -0.22640907E-15 | 0.11860658E-13 | -0.17473455E-15 |
103 | 6 | 0.80640390E-05 | 0.55493782E-08 | 0.31828288E-02 | -0.26700235E-04 |
104 | 5 | -0.58275339E-03 | 0.32892043E-05 | -0.22332434 | 0.19526176E-02 |
105 | 4 | 0.13421983E-01 | 0.14977251E-03 | 4.8228790 | -0.45200897E-01 |
106 | 3 | -0.11791368 | 0.11914425E-02 | -37.983753 | 0.39823745 |
107 | 2 | 0.41875064 | 0.19825898E-02 | 116.41064 | -1.4169588 |
108 | 1 | -0.60444169 | 0.60433957E-03 | -143.86415 | 2.0483306 |
109 | 0 | 0.29470347 | 0.14596444E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.503_SHGC_0.23 | 35 | 1 | VerySmooth | 2.860 | 2.860 | 1.000 | 0.231 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 1.93472E-002 | 0.14129 | 0.63061 | 0.63061 | 0.25300 | 0.16079 | 0.23715 | 0.00000 | 0.84000 | 0.84000 | 0.10783 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | GAS TANK1 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
2 | WaterHeater:Mixed | GAS TANK2 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
3 | WaterHeater:Mixed | GAS TANK3 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
4 | WaterHeater:Mixed | GAS TANK4 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
5 | WaterHeater:Mixed | GAS TANK5 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
6 | WaterHeater:Mixed | GAS TANK6 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
7 | WaterHeater:Mixed | GAS TANK7 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | LGSTORE1_WALL_2 | 0 | 118.41 | 56.08 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
2 | LGSTORE1_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
3 | LGSTORE1_WALL_3_DOOR_1 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
4 | LGSTORE1_WALL_3_DOOR_2 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
5 | LGSTORE1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
6 | LGSTORE1_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
7 | LGSTORE1_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
8 | LGSTORE1_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
9 | LGSTORE1_WALL_1_WINDOW_3 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
10 | LGSTORE1_WALL_1_WINDOW_4 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
11 | LGSTORE1_WALL_1_DOOR_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 1 | No | No |
12 | LGSTORE1_WALL_1_DOOR_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 1 | No | No |
13 | LGSTORE1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
14 | LGSTORE1_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
15 | LGSTORE1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
16 | SMSTORE1_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
17 | SMSTORE1_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
18 | SMSTORE1_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
19 | SMSTORE1_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
20 | SMSTORE1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
21 | SMSTORE1_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
22 | SMSTORE1_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
23 | SMSTORE1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
24 | SMSTORE1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
25 | SMSTORE1_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
26 | SMSTORE1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
27 | SMSTORE2_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
28 | SMSTORE2_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
29 | SMSTORE2_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
30 | SMSTORE2_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
31 | SMSTORE2_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
32 | SMSTORE2_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
33 | SMSTORE2_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
34 | SMSTORE2_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
35 | SMSTORE2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
36 | SMSTORE2_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
37 | SMSTORE2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
38 | SMSTORE3_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
39 | SMSTORE3_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
40 | SMSTORE3_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
41 | SMSTORE3_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
42 | SMSTORE3_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
43 | SMSTORE3_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
44 | SMSTORE3_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
45 | SMSTORE3_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
46 | SMSTORE3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
47 | SMSTORE3_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
48 | SMSTORE3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
49 | SMSTORE4_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
50 | SMSTORE4_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
51 | SMSTORE4_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
52 | SMSTORE4_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
53 | SMSTORE4_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
54 | SMSTORE4_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 3 | No | No |
55 | SMSTORE4_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
56 | SMSTORE4_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
57 | SMSTORE4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
58 | SMSTORE4_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
59 | SMSTORE4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
60 | LGSTORE2_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
61 | LGSTORE2_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 4 | No | No |
62 | LGSTORE2_WALL_3_DOOR_1 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
63 | LGSTORE2_WALL_3_DOOR_2 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
64 | LGSTORE2_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
65 | LGSTORE2_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 4 | No | No |
66 | LGSTORE2_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
67 | LGSTORE2_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
68 | LGSTORE2_WALL_1_WINDOW_3 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
69 | LGSTORE2_WALL_1_WINDOW_4 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
70 | LGSTORE2_WALL_1_DOOR_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
71 | LGSTORE2_WALL_1_DOOR_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
72 | LGSTORE2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
73 | LGSTORE2_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
74 | LGSTORE2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
75 | SMSTORE5_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
76 | SMSTORE5_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
77 | SMSTORE5_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
78 | SMSTORE5_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
79 | SMSTORE5_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
80 | SMSTORE5_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
81 | SMSTORE5_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
82 | SMSTORE5_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
83 | SMSTORE5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
84 | SMSTORE5_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
85 | SMSTORE5_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
86 | SMSTORE6_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
87 | SMSTORE6_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
88 | SMSTORE6_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
89 | SMSTORE6_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
90 | SMSTORE6_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
91 | SMSTORE6_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
92 | SMSTORE6_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
93 | SMSTORE6_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
94 | SMSTORE6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
95 | SMSTORE6_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
96 | SMSTORE6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
97 | SMSTORE7_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
98 | SMSTORE7_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
99 | SMSTORE7_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
100 | SMSTORE7_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
101 | SMSTORE7_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
102 | SMSTORE7_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 3 | No | No |
103 | SMSTORE7_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
104 | SMSTORE7_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
105 | SMSTORE7_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
106 | SMSTORE7_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
107 | SMSTORE7_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
108 | SMSTORE8_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 4 | No | No |
109 | SMSTORE8_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 2 | No | No |
110 | SMSTORE8_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 2 | No | No |
111 | SMSTORE8_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 1 | No | No |
112 | SMSTORE8_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
113 | SMSTORE8_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 3 | No | No |
114 | SMSTORE8_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
115 | SMSTORE8_WALL_4 | 0 | 118.41 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 3 | No | No |
116 | SMSTORE8_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
117 | SMSTORE8_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
118 | SMSTORE8_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | LGSTORE1_INFILTRATION | TYPE1_INFIL_SCH | LGSTORE1 | 348.39 | 56.3 | 0.157 | 4.517E-004 | 2.488E-004 | 0.314 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | LGSTORE1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LGSTORE1 | 348.39 | 56.3 | 0.389 | 1.116E-003 | 6.149E-004 | 0.776 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | SMSTORE1_INFILTRATION | TYPE1_INFIL_SCH | SMSTORE1 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | SMSTORE1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE1 | 174.19 | 28.1 | 0.222 | 1.276E-003 | 8.648E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | SMSTORE2_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE2 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | SMSTORE2_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE2 | 174.19 | 28.1 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | SMSTORE3_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE3 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | SMSTORE3_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE3 | 174.19 | 28.1 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | SMSTORE4_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE4 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | SMSTORE4_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE4 | 174.19 | 28.1 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | LGSTORE2_INFILTRATION | TYPE3_INFIL_SCH | LGSTORE2 | 348.39 | 56.3 | 8.993E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | LGSTORE2_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LGSTORE2 | 348.39 | 56.3 | 0.389 | 1.116E-003 | 7.565E-004 | 0.776 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | SMSTORE5_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE5 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | SMSTORE5_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE5 | 174.19 | 28.1 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | SMSTORE6_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE6 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | SMSTORE6_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE6 | 174.19 | 28.1 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | SMSTORE7_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE7 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
18 | SMSTORE7_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE7 | 174.19 | 28.1 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | SMSTORE8_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE8 | 174.19 | 28.1 | 0.112 | 6.453E-004 | 2.994E-004 | 0.448 | 0.000 | 0.000 | 0.224 | 0.000 |
20 | SMSTORE8_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE8 | 174.19 | 28.1 | 0.222 | 1.276E-003 | 5.921E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | LGSTORE1 | Mixing/Well-Stirred |
2 | SMSTORE1 | Mixing/Well-Stirred |
3 | SMSTORE2 | Mixing/Well-Stirred |
4 | SMSTORE3 | Mixing/Well-Stirred |
5 | SMSTORE4 | Mixing/Well-Stirred |
6 | LGSTORE2 | Mixing/Well-Stirred |
7 | SMSTORE5 | Mixing/Well-Stirred |
8 | SMSTORE6 | Mixing/Well-Stirred |
9 | SMSTORE7 | Mixing/Well-Stirred |
10 | SMSTORE8 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone LGSTORE1 | 1.2000 |
3 | Zone SMSTORE1 | 1.2000 |
4 | Zone SMSTORE2 | 1.2000 |
5 | Zone SMSTORE3 | 1.2000 |
6 | Zone SMSTORE4 | 1.2000 |
7 | Zone LGSTORE2 | 1.2000 |
8 | Zone SMSTORE5 | 1.2000 |
9 | Zone SMSTORE6 | 1.2000 |
10 | Zone SMSTORE7 | 1.2000 |
11 | Zone SMSTORE8 | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone LGSTORE1 | 1.2000 |
3 | Zone SMSTORE1 | 1.2000 |
4 | Zone SMSTORE2 | 1.2000 |
5 | Zone SMSTORE3 | 1.2000 |
6 | Zone SMSTORE4 | 1.2000 |
7 | Zone LGSTORE2 | 1.2000 |
8 | Zone SMSTORE5 | 1.2000 |
9 | Zone SMSTORE6 | 1.2000 |
10 | Zone SMSTORE7 | 1.2000 |
11 | Zone SMSTORE8 | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | LGSTORE1 | Cooling | 31009.68973 | 37211.62768 | 2.34114 | 2.80937 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:10:00 | 41.90300 | 9.15774E-003 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
2 | LGSTORE1 | Heating | 15229.82811 | 18275.79374 | 0.67355 | 0.80827 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 6.30000 | 6.07234E-003 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
3 | SMSTORE1 | Cooling | 15868.42860 | 19042.11432 | 1.19802 | 1.43762 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | 42.00000 | 9.15790E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
4 | SMSTORE1 | Heating | 7490.88406 | 8989.06087 | 0.33129 | 0.39755 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 6.30000 | 6.07234E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
5 | SMSTORE2 | Cooling | 15867.01797 | 19040.42157 | 1.19791 | 1.43749 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | 42.00000 | 9.15790E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
6 | SMSTORE2 | Heating | 7556.86701 | 9068.24041 | 0.33421 | 0.40105 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 6.30000 | 6.07234E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
7 | SMSTORE3 | Cooling | 15902.27887 | 19082.73464 | 1.20057 | 1.44069 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | 42.00000 | 9.15790E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
8 | SMSTORE3 | Heating | 7626.65479 | 9151.98575 | 0.33729 | 0.40475 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 6.30000 | 6.07234E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
9 | SMSTORE4 | Cooling | 15804.94462 | 18965.93355 | 1.19323 | 1.43187 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | 42.00000 | 9.15790E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
10 | SMSTORE4 | Heating | 7774.55428 | 9329.46514 | 0.34384 | 0.41260 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 6.30000 | 6.07234E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
11 | LGSTORE2 | Cooling | 27976.21687 | 33571.46024 | 2.11212 | 2.53454 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | 42.00000 | 9.15790E-003 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
12 | LGSTORE2 | Heating | 14744.79915 | 17693.75898 | 0.65210 | 0.78253 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 6.30000 | 6.07234E-003 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
13 | SMSTORE5 | Cooling | 14798.79323 | 17758.55188 | 1.11726 | 1.34072 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:50:00 | 41.91917 | 9.15777E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
14 | SMSTORE5 | Heating | 7987.77824 | 9585.33388 | 0.35327 | 0.42392 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 6.30000 | 6.07234E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
15 | SMSTORE6 | Cooling | 14749.31804 | 17699.18164 | 1.11353 | 1.33623 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:50:00 | 41.91917 | 9.15777E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
16 | SMSTORE6 | Heating | 7991.59268 | 9589.91121 | 0.35343 | 0.42412 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 6.30000 | 6.07234E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
17 | SMSTORE7 | Cooling | 14826.52523 | 17791.83027 | 1.11936 | 1.34323 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:50:00 | 41.91917 | 9.15777E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
18 | SMSTORE7 | Heating | 8242.98438 | 9891.58125 | 0.36455 | 0.43746 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 6.30000 | 6.07234E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
19 | SMSTORE8 | Cooling | 17333.82443 | 20800.58932 | 1.30861 | 1.57034 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:00:00 | 41.51500 | 9.15709E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
20 | SMSTORE8 | Heating | 9749.92914 | 11699.91497 | 0.43120 | 0.51744 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 6.30000 | 6.07234E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC_1:1 | Cooling | Sensible | 45518.00 | 2.80937 | 2.80937 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
2 | PSZ-AC_1:1 | Heating | Sensible | 25196.89 | 0.80827 | 0.80827 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
3 | PSZ-AC_2:2 | Cooling | Sensible | 23194.56 | 1.43762 | 1.43762 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
4 | PSZ-AC_2:2 | Heating | Sensible | 12451.75 | 0.39755 | 0.39755 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
5 | PSZ-AC_3:3 | Cooling | Sensible | 23192.89 | 1.43749 | 1.43749 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
6 | PSZ-AC_3:3 | Heating | Sensible | 12529.78 | 0.40105 | 0.40105 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
7 | PSZ-AC_4:4 | Cooling | Sensible | 23234.66 | 1.44069 | 1.44069 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
8 | PSZ-AC_4:4 | Heating | Sensible | 12612.30 | 0.40475 | 0.40475 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
9 | PSZ-AC_5:5 | Cooling | Sensible | 23119.35 | 1.43187 | 1.43187 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
10 | PSZ-AC_5:5 | Heating | Sensible | 12787.20 | 0.41260 | 0.41260 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
11 | PSZ-AC_6:6 | Cooling | Sensible | 41933.95 | 2.53454 | 2.53454 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
12 | PSZ-AC_6:6 | Heating | Sensible | 24623.34 | 0.78253 | 0.78253 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
13 | PSZ-AC_7:7 | Cooling | Sensible | 21927.32 | 1.34072 | 1.34072 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
14 | PSZ-AC_7:7 | Heating | Sensible | 13039.34 | 0.42392 | 0.42392 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
15 | PSZ-AC_8:8 | Cooling | Sensible | 21868.64 | 1.33623 | 1.33623 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
16 | PSZ-AC_8:8 | Heating | Sensible | 13043.85 | 0.42412 | 0.42412 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
17 | PSZ-AC_9:9 | Cooling | Sensible | 21959.21 | 1.34323 | 1.34323 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
18 | PSZ-AC_9:9 | Heating | Sensible | 13341.13 | 0.43746 | 0.43746 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
19 | PSZ-AC_10:10 | Cooling | Sensible | 24819.78 | 1.57034 | 1.57034 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
20 | PSZ-AC_10:10 | Heating | Sensible | 15123.11 | 0.51744 | 0.51744 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | LGSTORE1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.80937 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.43762 |
3 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.43749 |
4 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.44069 |
5 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE4 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.43187 |
6 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | LGSTORE2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.53454 |
7 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE5 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.34072 |
8 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.33623 |
9 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE7 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.34323 |
10 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE8 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.57034 |
11 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.80937 |
12 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.80937 |
13 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.80937 |
14 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 2.80937 |
15 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.80937 |
16 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Main Design Air Flow Rate [m3/s] | 2.80937 |
17 | AirLoopHVAC | PSZ-AC_1:1 | User Heating Air Flow Ratio [] | 1.00000 |
18 | AirLoopHVAC | PSZ-AC_1:1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
19 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.43762 |
20 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.43762 |
21 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.43762 |
22 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.43762 |
23 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.43762 |
24 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Main Design Air Flow Rate [m3/s] | 1.43762 |
25 | AirLoopHVAC | PSZ-AC_2:2 | User Heating Air Flow Ratio [] | 1.00000 |
26 | AirLoopHVAC | PSZ-AC_2:2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
27 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.43749 |
28 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.43749 |
29 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.43749 |
30 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.43749 |
31 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.43749 |
32 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Main Design Air Flow Rate [m3/s] | 1.43749 |
33 | AirLoopHVAC | PSZ-AC_3:3 | User Heating Air Flow Ratio [] | 1.00000 |
34 | AirLoopHVAC | PSZ-AC_3:3 | Calculated Heating Air Flow Ratio [] | 1.00000 |
35 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.44069 |
36 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.44069 |
37 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.44069 |
38 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.44069 |
39 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.44069 |
40 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Main Design Air Flow Rate [m3/s] | 1.44069 |
41 | AirLoopHVAC | PSZ-AC_4:4 | User Heating Air Flow Ratio [] | 1.00000 |
42 | AirLoopHVAC | PSZ-AC_4:4 | Calculated Heating Air Flow Ratio [] | 1.00000 |
43 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.43187 |
44 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.43187 |
45 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.43187 |
46 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.43187 |
47 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.43187 |
48 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Main Design Air Flow Rate [m3/s] | 1.43187 |
49 | AirLoopHVAC | PSZ-AC_5:5 | User Heating Air Flow Ratio [] | 1.00000 |
50 | AirLoopHVAC | PSZ-AC_5:5 | Calculated Heating Air Flow Ratio [] | 1.00000 |
51 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.53454 |
52 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.53454 |
53 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.53454 |
54 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Heating Design Air Flow Rate [m3/s] | 2.53454 |
55 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.53454 |
56 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Main Design Air Flow Rate [m3/s] | 2.53454 |
57 | AirLoopHVAC | PSZ-AC_6:6 | User Heating Air Flow Ratio [] | 1.00000 |
58 | AirLoopHVAC | PSZ-AC_6:6 | Calculated Heating Air Flow Ratio [] | 1.00000 |
59 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.34072 |
60 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.34072 |
61 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.34072 |
62 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.34072 |
63 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.34072 |
64 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Main Design Air Flow Rate [m3/s] | 1.34072 |
65 | AirLoopHVAC | PSZ-AC_7:7 | User Heating Air Flow Ratio [] | 1.00000 |
66 | AirLoopHVAC | PSZ-AC_7:7 | Calculated Heating Air Flow Ratio [] | 1.00000 |
67 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.33623 |
68 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.33623 |
69 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.33623 |
70 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.33623 |
71 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.33623 |
72 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Main Design Air Flow Rate [m3/s] | 1.33623 |
73 | AirLoopHVAC | PSZ-AC_8:8 | User Heating Air Flow Ratio [] | 1.00000 |
74 | AirLoopHVAC | PSZ-AC_8:8 | Calculated Heating Air Flow Ratio [] | 1.00000 |
75 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.34323 |
76 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.34323 |
77 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.34323 |
78 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.34323 |
79 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.34323 |
80 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Main Design Air Flow Rate [m3/s] | 1.34323 |
81 | AirLoopHVAC | PSZ-AC_9:9 | User Heating Air Flow Ratio [] | 1.00000 |
82 | AirLoopHVAC | PSZ-AC_9:9 | Calculated Heating Air Flow Ratio [] | 1.00000 |
83 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.57034 |
84 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.57034 |
85 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.57034 |
86 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.57034 |
87 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.57034 |
88 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Main Design Air Flow Rate [m3/s] | 1.57034 |
89 | AirLoopHVAC | PSZ-AC_10:10 | User Heating Air Flow Ratio [] | 1.00000 |
90 | AirLoopHVAC | PSZ-AC_10:10 | Calculated Heating Air Flow Ratio [] | 1.00000 |
91 | AirLoopHVAC | PSZ-AC_1:1 | Design Supply Air Flow Rate [m3/s] | 2.80937 |
92 | AirLoopHVAC | PSZ-AC_2:2 | Design Supply Air Flow Rate [m3/s] | 1.43762 |
93 | AirLoopHVAC | PSZ-AC_3:3 | Design Supply Air Flow Rate [m3/s] | 1.43749 |
94 | AirLoopHVAC | PSZ-AC_4:4 | Design Supply Air Flow Rate [m3/s] | 1.44069 |
95 | AirLoopHVAC | PSZ-AC_5:5 | Design Supply Air Flow Rate [m3/s] | 1.43187 |
96 | AirLoopHVAC | PSZ-AC_6:6 | Design Supply Air Flow Rate [m3/s] | 2.53454 |
97 | AirLoopHVAC | PSZ-AC_7:7 | Design Supply Air Flow Rate [m3/s] | 1.34072 |
98 | AirLoopHVAC | PSZ-AC_8:8 | Design Supply Air Flow Rate [m3/s] | 1.33623 |
99 | AirLoopHVAC | PSZ-AC_9:9 | Design Supply Air Flow Rate [m3/s] | 1.34323 |
100 | AirLoopHVAC | PSZ-AC_10:10 | Design Supply Air Flow Rate [m3/s] | 1.57034 |
101 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.80937 |
102 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41148 |
103 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.80937 |
104 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 3006.16032 |
105 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.80937 |
106 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.80937 |
107 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.80937 |
108 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.85419 |
109 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.80937 |
110 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.40469 |
111 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.87291 |
112 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 64861.65000 |
113 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 32430.82500 |
114 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.72460 |
115 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.72460 |
116 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 64861.65000 |
117 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 69785.06328 |
118 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
119 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
120 | Coil:Heating:Fuel | PSZ-AC_1:1 HEATING COIL | Design Size Nominal Capacity [W] | 69785.06328 |
121 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.43762 |
122 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
123 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.43762 |
124 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1538.32448 |
125 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.43762 |
126 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.43762 |
127 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.43762 |
128 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.94883 |
129 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.43762 |
130 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.71881 |
131 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.95841 |
132 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 33107.66000 |
133 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 16553.83000 |
134 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.72527 |
135 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.72527 |
136 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 33107.66000 |
137 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 35626.55916 |
138 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
139 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
140 | Coil:Heating:Fuel | PSZ-AC_2:2 HEATING COIL | Design Size Nominal Capacity [W] | 35626.55916 |
141 | Controller:OutdoorAir | PSZ-AC_3:3_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.43749 |
142 | Controller:OutdoorAir | PSZ-AC_3:3_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
143 | Fan:SystemModel | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.43749 |
144 | Fan:SystemModel | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1538.18742 |
145 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.43749 |
146 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.43749 |
147 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.43749 |
148 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.94875 |
149 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.43749 |
150 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.71875 |
151 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.95833 |
152 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 33105.47000 |
153 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 16552.73500 |
154 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.72526 |
155 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.72526 |
156 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 33105.47000 |
157 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 35623.72219 |
158 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
159 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
160 | Coil:Heating:Fuel | PSZ-AC_3:3 HEATING COIL | Design Size Nominal Capacity [W] | 35623.72219 |
161 | Controller:OutdoorAir | PSZ-AC_4:4_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.44069 |
162 | Controller:OutdoorAir | PSZ-AC_4:4_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
163 | Fan:SystemModel | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.44069 |
164 | Fan:SystemModel | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1541.60565 |
165 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.44069 |
166 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.44069 |
167 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.44069 |
168 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.95085 |
169 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.44069 |
170 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.72034 |
171 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.96046 |
172 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 33164.68000 |
173 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 16582.34000 |
174 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.72538 |
175 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.72538 |
176 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 33164.68000 |
177 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 35694.90279 |
178 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
179 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
180 | Coil:Heating:Fuel | PSZ-AC_4:4 HEATING COIL | Design Size Nominal Capacity [W] | 35694.90279 |
181 | Controller:OutdoorAir | PSZ-AC_5:5_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.43187 |
182 | Controller:OutdoorAir | PSZ-AC_5:5_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
183 | Fan:SystemModel | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.43187 |
184 | Fan:SystemModel | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1532.16967 |
185 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.43187 |
186 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.43187 |
187 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.43187 |
188 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.94503 |
189 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.43187 |
190 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.71594 |
191 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.95458 |
192 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 33001.29000 |
193 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 16500.64500 |
194 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.72506 |
195 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.72506 |
196 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 33001.29000 |
197 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 35498.41410 |
198 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
199 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
200 | Coil:Heating:Fuel | PSZ-AC_5:5 HEATING COIL | Design Size Nominal Capacity [W] | 35498.41410 |
201 | Controller:OutdoorAir | PSZ-AC_6:6_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.53454 |
202 | Controller:OutdoorAir | PSZ-AC_6:6_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41148 |
203 | Fan:SystemModel | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.53454 |
204 | Fan:SystemModel | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 2712.07639 |
205 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.53454 |
206 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.53454 |
207 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.53454 |
208 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.67280 |
209 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.53454 |
210 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.26727 |
211 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.68969 |
212 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 59708.33000 |
213 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 29854.16500 |
214 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.71734 |
215 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.71734 |
216 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 59708.33000 |
217 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 63661.27440 |
218 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
219 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
220 | Coil:Heating:Fuel | PSZ-AC_6:6 HEATING COIL | Design Size Nominal Capacity [W] | 63661.27440 |
221 | Controller:OutdoorAir | PSZ-AC_7:7_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.34072 |
222 | Controller:OutdoorAir | PSZ-AC_7:7_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
223 | Fan:SystemModel | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.34072 |
224 | Fan:SystemModel | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1484.38653 |
225 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.34072 |
226 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.34072 |
227 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.34072 |
228 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.88487 |
229 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.34072 |
230 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.67036 |
231 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.89381 |
232 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 31308.01000 |
233 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 15654.00500 |
234 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.72062 |
235 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.72062 |
236 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 31308.01000 |
237 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 33467.33091 |
238 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
239 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
240 | Coil:Heating:Fuel | PSZ-AC_7:7 HEATING COIL | Design Size Nominal Capacity [W] | 33467.33091 |
241 | Controller:OutdoorAir | PSZ-AC_8:8_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.33623 |
242 | Controller:OutdoorAir | PSZ-AC_8:8_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
243 | Fan:SystemModel | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.33623 |
244 | Fan:SystemModel | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1479.42396 |
245 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.33623 |
246 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.33623 |
247 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.33623 |
248 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.88191 |
249 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.33623 |
250 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.66812 |
251 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.89082 |
252 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 31224.56000 |
253 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 15612.28000 |
254 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.72045 |
255 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.72045 |
256 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 31224.56000 |
257 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 33367.45723 |
258 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
259 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
260 | Coil:Heating:Fuel | PSZ-AC_8:8 HEATING COIL | Design Size Nominal Capacity [W] | 33367.45723 |
261 | Controller:OutdoorAir | PSZ-AC_9:9_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.34323 |
262 | Controller:OutdoorAir | PSZ-AC_9:9_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
263 | Fan:SystemModel | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.34323 |
264 | Fan:SystemModel | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1487.16790 |
265 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.34323 |
266 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.34323 |
267 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.34323 |
268 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.88653 |
269 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.34323 |
270 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.67161 |
271 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.89549 |
272 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 31355.18000 |
273 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 15677.59000 |
274 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.72072 |
275 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.72072 |
276 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 31355.18000 |
277 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 33523.30833 |
278 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
279 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
280 | Coil:Heating:Fuel | PSZ-AC_9:9 HEATING COIL | Design Size Nominal Capacity [W] | 33523.30833 |
281 | Controller:OutdoorAir | PSZ-AC_10:10_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.57034 |
282 | Controller:OutdoorAir | PSZ-AC_10:10_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
283 | Fan:SystemModel | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.57034 |
284 | Fan:SystemModel | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1680.33355 |
285 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.57034 |
286 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.57034 |
287 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.57034 |
288 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.03642 |
289 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.57034 |
290 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.78517 |
291 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.04689 |
292 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 35310.39000 |
293 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 17655.19500 |
294 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.73266 |
295 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.73266 |
296 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 35310.39000 |
297 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 38583.76070 |
298 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
299 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
300 | Coil:Heating:Fuel | PSZ-AC_10:10 HEATING COIL | Design Size Nominal Capacity [W] | 38583.76070 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | 62648.4 | 11.64 | 11.64 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | 31975.1 | 11.81 | 11.81 | |||
3 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | 31973.0 | 11.81 | 11.81 | |||
4 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | 32029.7 | 11.81 | 11.81 | |||
5 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | 31873.3 | 11.81 | 11.81 | |||
6 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | 57710.8 | 11.68 | 11.68 | |||
7 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | 30251.5 | 11.84 | 11.84 | |||
8 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | 30171.6 | 11.84 | 11.84 | |||
9 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | 30296.7 | 11.84 | 11.84 | |||
10 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | 34073.8 | 11.76 | 11.76 |
Zone Name | # Surfaces | |
1 | LGSTORE1 | 15 |
2 | SMSTORE1 | 11 |
3 | SMSTORE2 | 11 |
4 | SMSTORE3 | 11 |
5 | SMSTORE4 | 11 |
6 | LGSTORE2 | 15 |
7 | SMSTORE5 | 11 |
8 | SMSTORE6 | 11 |
9 | SMSTORE7 | 11 |
10 | SMSTORE8 | 11 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | LGSTORE1_WALL_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | LGSTORE1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 71.15 | 78.94 | 71.15 | 0.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | LGSTORE1_WALL_3_DOOR_1 | Door | LGSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
4 | LGSTORE1_WALL_3_DOOR_2 | Door | LGSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
5 | LGSTORE1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
6 | LGSTORE1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 58.18 | 78.94 | 58.18 | 180.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
7 | LGSTORE1_WALL_1_WINDOW_1 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.23 | N/A | 2.860 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
8 | LGSTORE1_WALL_1_WINDOW_2 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.23 | N/A | 2.860 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
9 | LGSTORE1_WALL_1_WINDOW_3 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.23 | N/A | 2.860 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
10 | LGSTORE1_WALL_1_WINDOW_4 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.23 | N/A | 2.860 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
11 | LGSTORE1_WALL_1_DOOR_1 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.23 | N/A | 2.860 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
12 | LGSTORE1_WALL_1_DOOR_2 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.23 | N/A | 2.860 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
13 | LGSTORE1_FLOOR | Floor | CTF - ConductionTransferFunction | LGSTORE1_FLOOR_FFACTOR | 0.199 | 0.190 | 348.39 | 348.39 | 348.39 | 270.00 | 180.00 | 22.86 | 15.24 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | LGSTORE1_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 348.39 | 348.39 | 348.39 | 270.00 | 0.00 | 22.86 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
15 | LGSTORE1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 696.77 | 696.77 | 696.77 | 0.00 | 90.00 | 696.77 | 1.00 | 0.00 | LGSTORE1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
16 | SMSTORE1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 29.09 | 39.47 | 29.09 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
17 | SMSTORE1_WALL_1_WINDOW_1 | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.23 | N/A | 2.860 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
18 | SMSTORE1_WALL_1_WINDOW_2 | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.23 | N/A | 2.860 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
19 | SMSTORE1_WALL_1_DOOR | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.23 | N/A | 2.860 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
20 | SMSTORE1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | SMSTORE1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 35.57 | 39.47 | 35.57 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | SMSTORE1_WALL_3_DOOR | Door | SMSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
23 | SMSTORE1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE2_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | SMSTORE1_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE1_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | SMSTORE1_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
26 | SMSTORE1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
27 | SMSTORE2_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | SMSTORE2_WALL_1_WINDOW_1 | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.23 | N/A | 2.860 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
29 | SMSTORE2_WALL_1_WINDOW_2 | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.23 | N/A | 2.860 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
30 | SMSTORE2_WALL_1_DOOR | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.23 | N/A | 2.860 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
31 | SMSTORE2_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | SMSTORE2_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | SMSTORE2_WALL_3_DOOR | Door | SMSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
34 | SMSTORE2_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE3_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | SMSTORE2_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE2_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | SMSTORE2_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | SMSTORE2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | SMSTORE3_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | SMSTORE3_WALL_1_WINDOW_1 | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.23 | N/A | 2.860 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
40 | SMSTORE3_WALL_1_WINDOW_2 | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.23 | N/A | 2.860 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
41 | SMSTORE3_WALL_1_DOOR | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.23 | N/A | 2.860 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
42 | SMSTORE3_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE2_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | SMSTORE3_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | SMSTORE3_WALL_3_DOOR | Door | SMSTORE3_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
45 | SMSTORE3_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE4_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | SMSTORE3_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE3_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
47 | SMSTORE3_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
48 | SMSTORE3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
49 | SMSTORE4_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | SMSTORE4_WALL_1_WINDOW_1 | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.23 | N/A | 2.860 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
51 | SMSTORE4_WALL_1_WINDOW_2 | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.23 | N/A | 2.860 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
52 | SMSTORE4_WALL_1_DOOR | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.23 | N/A | 2.860 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | SMSTORE4_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE3_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | SMSTORE4_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | SMSTORE4_WALL_3_DOOR | Door | SMSTORE4_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | SMSTORE4_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE2_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | SMSTORE4_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE4_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | SMSTORE4_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | SMSTORE4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | LGSTORE2_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE4_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | LGSTORE2_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 71.19 | 78.94 | 71.19 | 0.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
62 | LGSTORE2_WALL_3_DOOR_1 | Door | LGSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
63 | LGSTORE2_WALL_3_DOOR_2 | Door | LGSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
64 | LGSTORE2_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE5_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LGSTORE2_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 58.22 | 78.94 | 58.22 | 180.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
66 | LGSTORE2_WALL_1_WINDOW_1 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.23 | N/A | 2.860 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | LGSTORE2_WALL_1_WINDOW_2 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.23 | N/A | 2.860 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | LGSTORE2_WALL_1_WINDOW_3 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.23 | N/A | 2.860 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | LGSTORE2_WALL_1_WINDOW_4 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.23 | N/A | 2.860 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LGSTORE2_WALL_1_DOOR_1 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.23 | N/A | 2.860 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
71 | LGSTORE2_WALL_1_DOOR_2 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.23 | N/A | 2.860 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
72 | LGSTORE2_FLOOR | Floor | CTF - ConductionTransferFunction | LGSTORE2_FLOOR_FFACTOR | 0.112 | 0.109 | 348.39 | 348.39 | 348.39 | 270.00 | 180.00 | 22.86 | 15.24 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
73 | LGSTORE2_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 348.39 | 348.39 | 348.39 | 270.00 | 0.00 | 22.86 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
74 | LGSTORE2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 696.77 | 696.77 | 696.77 | 0.00 | 90.00 | 696.77 | 1.00 | 0.00 | LGSTORE2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
75 | SMSTORE5_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | SMSTORE5_WALL_1_WINDOW_1 | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.23 | N/A | 2.860 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
77 | SMSTORE5_WALL_1_WINDOW_2 | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.23 | N/A | 2.860 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | SMSTORE5_WALL_1_DOOR | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.23 | N/A | 2.860 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
79 | SMSTORE5_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE2_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | SMSTORE5_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 35.59 | 39.47 | 35.59 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | SMSTORE5_WALL_3_DOOR | Door | SMSTORE5_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
82 | SMSTORE5_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE6_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
83 | SMSTORE5_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE5_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
84 | SMSTORE5_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
85 | SMSTORE5_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE5_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | SMSTORE6_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | SMSTORE6_WALL_1_WINDOW_1 | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.23 | N/A | 2.860 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | SMSTORE6_WALL_1_WINDOW_2 | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.23 | N/A | 2.860 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
89 | SMSTORE6_WALL_1_DOOR | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.23 | N/A | 2.860 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | SMSTORE6_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE5_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | SMSTORE6_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | SMSTORE6_WALL_3_DOOR | Door | SMSTORE6_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
93 | SMSTORE6_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE7_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | SMSTORE6_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE6_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
95 | SMSTORE6_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
96 | SMSTORE6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
97 | SMSTORE7_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | SMSTORE7_WALL_1_WINDOW_1 | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.23 | N/A | 2.860 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | SMSTORE7_WALL_1_WINDOW_2 | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.23 | N/A | 2.860 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
100 | SMSTORE7_WALL_1_DOOR | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.23 | N/A | 2.860 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
101 | SMSTORE7_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE6_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
102 | SMSTORE7_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 35.59 | 39.47 | 35.59 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | SMSTORE7_WALL_3_DOOR | Door | SMSTORE7_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
104 | SMSTORE7_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE8_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | SMSTORE7_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE7_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
106 | SMSTORE7_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
107 | SMSTORE7_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE7_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
108 | SMSTORE8_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | SMSTORE8_WALL_1_WINDOW_1 | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.23 | N/A | 2.860 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
110 | SMSTORE8_WALL_1_WINDOW_2 | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.23 | N/A | 2.860 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
111 | SMSTORE8_WALL_1_DOOR | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.503_SHGC_0.23 | N/A | 2.860 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
112 | SMSTORE8_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE7_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | SMSTORE8_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | SMSTORE8_WALL_3_DOOR | Door | SMSTORE8_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
115 | SMSTORE8_WALL_4 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.028 | 0.891 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | SMSTORE8_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE8_FLOOR_FFACTOR | 0.289 | 0.270 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | SMSTORE8_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | SMSTORE8_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE8_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | LGSTORE1 | RunPeriod: RUNPERIOD 1 | 4.1793774247E-002 | 0.1305550897 | Pass | Pass | 9.0586840298E-002 | 0.2264913529 | Pass | Pass |
2 | SMSTORE1 | RunPeriod: RUNPERIOD 1 | 6.2869090098E-002 | 0.1028848499 | Pass | Pass | 0.3134704358 | 2.0422210681 | Pass | Pass |
3 | SMSTORE2 | RunPeriod: RUNPERIOD 1 | 3.6813301327E-002 | 0.1170753815 | Pass | Pass | 0.4537529484 | 4.3466363901 | Pass | Pass |
4 | SMSTORE3 | RunPeriod: RUNPERIOD 1 | 3.5240962236E-002 | 0.1521111227 | Pass | Pass | 0.2154778838 | 0.9587906418 | Pass | Pass |
5 | SMSTORE4 | RunPeriod: RUNPERIOD 1 | 3.7210965039E-002 | 0.1667869928 | Pass | Pass | 0.2819327575 | 0.9554730820 | Pass | Pass |
6 | LGSTORE2 | RunPeriod: RUNPERIOD 1 | 4.1312741387E-002 | 0.2051922812 | Pass | Pass | 0.4126905041 | 2.0430765991 | Pass | Pass |
7 | SMSTORE5 | RunPeriod: RUNPERIOD 1 | 4.1196186239E-002 | 0.2112111288 | Pass | Pass | 0.3064914325 | 1.0868730418 | Pass | Pass |
8 | SMSTORE6 | RunPeriod: RUNPERIOD 1 | 4.1760033464E-002 | 0.2147426293 | Pass | Pass | 0.3510420167 | 1.4973392480 | Pass | Pass |
9 | SMSTORE7 | RunPeriod: RUNPERIOD 1 | 4.4627367405E-002 | 0.2324640582 | Pass | Pass | 0.2192554839 | 0.9348363707 | Pass | Pass |
10 | SMSTORE8 | RunPeriod: RUNPERIOD 1 | 5.5678987938E-002 | 0.2902039508 | Pass | Pass | 0.9845195457 | 9.9271279696 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:19
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 2596.97 | -284.6 | 0.00 | -618.0 | 2360.02 | 4054.36 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:19
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 6.30 | 0.00 | 6.30 | Wetbulb [C] | 0.50 | 270.00 |
NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 42.00 | 9.70 | 22.20 | Wetbulb [C] | 3.20 | 320.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.60 | 4 | |||
Feb | 21.40 | 43 | |||
Mar | 12.00 | 35 | |||
Apr | 29.10 | 12 | |||
May | 29.10 | 57 | |||
Jun | 197.10 | 59 | |||
Jul | 47.90 | 83 | |||
Aug | 0.00 | 0 | |||
Sep | 171.60 | 106 | |||
Oct | 4.80 | 31 | |||
Nov | 1.20 | 7 | |||
Dec | 33.00 | 13 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:19
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_2 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE1_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 78.94 | 71.15 | 0.00 | 90.00 | N |
LGSTORE1_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 78.94 | 58.18 | 180.00 | 90.00 | S |
LGSTORE1_FLOOR | LGSTORE1_FLOOR_FFACTOR | 1.00 | 0.193 | 0.199 | 348.39 | 348.39 | 270.00 | 180.00 | |
LGSTORE1_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 348.39 | 348.39 | 270.00 | 0.00 | |
SMSTORE1_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 39.47 | 29.09 | 180.00 | 90.00 | S |
SMSTORE1_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 39.47 | 35.57 | 0.00 | 90.00 | N |
SMSTORE1_FLOOR | SMSTORE1_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE1_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE2_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE2_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE2_FLOOR | SMSTORE2_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE2_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE3_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE3_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE3_FLOOR | SMSTORE3_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE3_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE4_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE4_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE4_FLOOR | SMSTORE4_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE4_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
LGSTORE2_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 78.94 | 71.19 | 0.00 | 90.00 | N |
LGSTORE2_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 78.94 | 58.22 | 180.00 | 90.00 | S |
LGSTORE2_FLOOR | LGSTORE2_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 348.39 | 348.39 | 270.00 | 180.00 | |
LGSTORE2_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 348.39 | 348.39 | 270.00 | 0.00 | |
SMSTORE5_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE5_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE5_FLOOR | SMSTORE5_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE5_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE6_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE6_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE6_FLOOR | SMSTORE6_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE6_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE7_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE7_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE7_FLOOR | SMSTORE7_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE7_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE8_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE8_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE8_WALL_4 | NONRES_EXT_WALL_GRD | 0.30 | 0.891 | 1.028 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE8_FLOOR | SMSTORE8_FLOOR_FFACTOR | 1.00 | 0.276 | 0.289 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE8_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE1_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE2_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE2_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE3_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE3_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE4_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE4_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
LGSTORE2_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE2_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE5_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE5_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE6_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE6_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE7_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE7_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE8_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 696.77 | 0.00 | 90.00 | N | ||
SMSTORE1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
LGSTORE2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 696.77 | 0.00 | 90.00 | N | ||
SMSTORE5_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE7_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE8_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.503_SHGC_0.23 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.860 | 0.231 | 0.254 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.503_SHGC_0.23 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.860 | 0.231 | 0.254 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_3 | NONRESWINDOW_U_0.503_SHGC_0.23 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.860 | 0.231 | 0.254 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_4 | NONRESWINDOW_U_0.503_SHGC_0.23 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.860 | 0.231 | 0.254 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_DOOR_1 | NONRESWINDOW_U_0.503_SHGC_0.23 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.860 | 0.231 | 0.254 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_DOOR_2 | NONRESWINDOW_U_0.503_SHGC_0.23 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.860 | 0.231 | 0.254 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.503_SHGC_0.23 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.860 | 0.231 | 0.254 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.503_SHGC_0.23 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.860 | 0.231 | 0.254 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_DOOR | NONRESWINDOW_U_0.503_SHGC_0.23 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.860 | 0.231 | 0.254 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.503_SHGC_0.23 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.860 | 0.231 | 0.254 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.503_SHGC_0.23 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.860 | 0.231 | 0.254 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_DOOR | NONRESWINDOW_U_0.503_SHGC_0.23 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.860 | 0.231 | 0.254 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.503_SHGC_0.23 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.860 | 0.231 | 0.254 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.503_SHGC_0.23 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.860 | 0.231 | 0.254 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_DOOR | NONRESWINDOW_U_0.503_SHGC_0.23 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.860 | 0.231 | 0.254 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.503_SHGC_0.23 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.860 | 0.231 | 0.254 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.503_SHGC_0.23 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.860 | 0.231 | 0.254 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_DOOR | NONRESWINDOW_U_0.503_SHGC_0.23 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.860 | 0.231 | 0.254 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.503_SHGC_0.23 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.860 | 0.231 | 0.254 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.503_SHGC_0.23 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.860 | 0.231 | 0.254 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_3 | NONRESWINDOW_U_0.503_SHGC_0.23 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.860 | 0.231 | 0.254 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_4 | NONRESWINDOW_U_0.503_SHGC_0.23 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.860 | 0.231 | 0.254 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_DOOR_1 | NONRESWINDOW_U_0.503_SHGC_0.23 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.860 | 0.231 | 0.254 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_DOOR_2 | NONRESWINDOW_U_0.503_SHGC_0.23 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.860 | 0.231 | 0.254 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.503_SHGC_0.23 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.860 | 0.231 | 0.254 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.503_SHGC_0.23 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.860 | 0.231 | 0.254 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_DOOR | NONRESWINDOW_U_0.503_SHGC_0.23 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.860 | 0.231 | 0.254 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.503_SHGC_0.23 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.860 | 0.231 | 0.254 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.503_SHGC_0.23 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.860 | 0.231 | 0.254 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_DOOR | NONRESWINDOW_U_0.503_SHGC_0.23 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.860 | 0.231 | 0.254 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.503_SHGC_0.23 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.860 | 0.231 | 0.254 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.503_SHGC_0.23 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.860 | 0.231 | 0.254 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_DOOR | NONRESWINDOW_U_0.503_SHGC_0.23 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.860 | 0.231 | 0.254 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.503_SHGC_0.23 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.860 | 0.231 | 0.254 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.503_SHGC_0.23 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.860 | 0.231 | 0.254 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_DOOR | NONRESWINDOW_U_0.503_SHGC_0.23 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.860 | 0.231 | 0.254 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
Total or Average | 124.40 | 2.860 | 0.231 | 0.254 | |||||||||||||||||
North Total or Average | 0.00 | - | - | - | |||||||||||||||||
Non-North Total or Average | 124.40 | 2.860 | 0.231 | 0.254 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
LGSTORE1_WALL_3_DOOR_1 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.90 | LGSTORE1_WALL_3 |
LGSTORE1_WALL_3_DOOR_2 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.90 | LGSTORE1_WALL_3 |
SMSTORE1_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.90 | SMSTORE1_WALL_3 |
SMSTORE2_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE2_WALL_3 |
SMSTORE3_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE3_WALL_3 |
SMSTORE4_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE4_WALL_3 |
LGSTORE2_WALL_3_DOOR_1 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | LGSTORE2_WALL_3 |
LGSTORE2_WALL_3_DOOR_2 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | LGSTORE2_WALL_3 |
SMSTORE5_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE5_WALL_3 |
SMSTORE6_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE6_WALL_3 |
SMSTORE7_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE7_WALL_3 |
SMSTORE8_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE8_WALL_3 |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:19
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
LGSTORE1_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_4 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_DOOR_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_DOOR_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_4 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_DOOR_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_DOOR_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:19
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
LGSTORE1_LIGHTS | LGSTORE1 | LGSTORE1 | GENERAL | 9.6053 | 348.39 | 3346.35 | LightsWired | LTG_SCH_BASE_LPD1 | 83.91 | 168.00 | 82.62 | 0.0000 | Y | 51.90 |
LGSTORE1_LIGHTS_ALLOWANCE | LGSTORE1 | LGSTORE1 | GENERAL | 5.6969 | 348.39 | 1984.73 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | 97.50 | 112.00 | 94.53 | 0.0000 | Y | 35.22 |
SMSTORE1_LIGHTS | SMSTORE1 | SMSTORE1 | GENERAL | 9.7206 | 174.19 | 1693.26 | LightsWired | LTG_SCH_BASE_SMALL_LPD1 | 85.41 | 168.00 | 84.05 | 0.0000 | Y | 26.72 |
SMSTORE1_LIGHTS_ALLOWANCE | SMSTORE1 | SMSTORE1 | GENERAL | 8.5685 | 174.19 | 1492.57 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | 97.50 | 112.00 | 94.53 | 0.0000 | Y | 26.49 |
SMSTORE2_LIGHTS | SMSTORE2 | SMSTORE2 | GENERAL | 9.6995 | 174.19 | 1689.58 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 68.73 | 168.00 | 65.95 | 0.0000 | Y | 20.92 |
SMSTORE2_LIGHTS_ALLOWANCE | SMSTORE2 | SMSTORE2 | GENERAL | 6.9539 | 174.19 | 1211.32 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 84.29 | 73.25 | 0.0000 | Y | 16.66 |
SMSTORE3_LIGHTS | SMSTORE3 | SMSTORE3 | GENERAL | 9.6995 | 174.19 | 1689.58 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 68.73 | 168.00 | 65.95 | 0.0000 | Y | 20.92 |
SMSTORE3_LIGHTS_ALLOWANCE | SMSTORE3 | SMSTORE3 | GENERAL | 6.9539 | 174.19 | 1211.32 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 84.29 | 73.25 | 0.0000 | Y | 16.66 |
SMSTORE4_LIGHTS | SMSTORE4 | SMSTORE4 | GENERAL | 9.6995 | 174.19 | 1689.58 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 68.73 | 168.00 | 65.95 | 0.0000 | Y | 20.92 |
SMSTORE4_LIGHTS_ALLOWANCE | SMSTORE4 | SMSTORE4 | GENERAL | 6.9539 | 174.19 | 1211.32 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 84.29 | 73.25 | 0.0000 | Y | 16.66 |
LGSTORE2_LIGHTS | LGSTORE2 | LGSTORE2 | GENERAL | 9.5842 | 348.39 | 3339.00 | LightsWired | LTG_SCH_BASE_LPD2 | 62.11 | 168.00 | 59.29 | 0.0000 | Y | 37.16 |
LGSTORE2_LIGHTS_ALLOWANCE | LGSTORE2 | LGSTORE2 | GENERAL | 0.0000 | 348.39 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE5_LIGHTS | SMSTORE5 | SMSTORE5 | GENERAL | 9.6995 | 174.19 | 1689.58 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 60.29 | 0.0000 | Y | 19.12 |
SMSTORE5_LIGHTS_ALLOWANCE | SMSTORE5 | SMSTORE5 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE6_LIGHTS | SMSTORE6 | SMSTORE6 | GENERAL | 9.6995 | 174.19 | 1689.58 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 60.29 | 0.0000 | Y | 19.12 |
SMSTORE6_LIGHTS_ALLOWANCE | SMSTORE6 | SMSTORE6 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE7_LIGHTS | SMSTORE7 | SMSTORE7 | GENERAL | 9.6995 | 174.19 | 1689.58 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 60.29 | 0.0000 | Y | 19.12 |
SMSTORE7_LIGHTS_ALLOWANCE | SMSTORE7 | SMSTORE7 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE8_LIGHTS | SMSTORE8 | SMSTORE8 | GENERAL | 9.6995 | 174.19 | 1689.58 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 60.29 | 0.0000 | Y | 19.12 |
SMSTORE8_LIGHTS_ALLOWANCE | SMSTORE8 | SMSTORE8 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
Interior Lighting Total | 6.5342 | 4180.64 | 27316.92 | 366.68 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 455.59 | AstronomicalClock | - | 41.75 | 41.75 | 3.57 | |
EXTERIOR_LIGHTS_B | 2744.24 | AstronomicalClock | - | 83.75 | 62.75 | 32.33 | |
EXTERIOR_LIGHTS_C | 2307.23 | AstronomicalClock | - | 83.75 | 55.75 | 24.15 | |
Exterior Lighting Total | 5507.06 | 60.04 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:19
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 64861.65 | 46998.75 | 17862.90 | 0.72 | 3.73 | |||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 33107.66 | 24011.99 | 9095.67 | 0.73 | 3.80 | |||
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 33105.47 | 24010.07 | 9095.40 | 0.73 | 3.80 | |||
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 33164.68 | 24057.00 | 9107.68 | 0.73 | 3.80 | |||
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 33001.29 | 23927.92 | 9073.37 | 0.73 | 3.80 | |||
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 59708.33 | 42831.17 | 16877.16 | 0.72 | 3.73 | |||
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 31308.01 | 22561.18 | 8746.83 | 0.72 | 3.80 | |||
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 31224.56 | 22495.73 | 8728.83 | 0.72 | 3.80 | |||
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 31355.18 | 22598.31 | 8756.87 | 0.72 | 3.80 | |||
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 35310.39 | 25870.51 | 9439.88 | 0.73 | 3.80 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC_1:1 COOLING COIL | 62648.4 | 11.64 | 11.64 | ||||
PSZ-AC_2:2 COOLING COIL | 31975.1 | 11.81 | 11.81 | ||||
PSZ-AC_3:3 COOLING COIL | 31973.0 | 11.81 | 11.81 | ||||
PSZ-AC_4:4 COOLING COIL | 32029.7 | 11.81 | 11.81 | ||||
PSZ-AC_5:5 COOLING COIL | 31873.3 | 11.81 | 11.81 | ||||
PSZ-AC_6:6 COOLING COIL | 57710.8 | 11.68 | 11.68 | ||||
PSZ-AC_7:7 COOLING COIL | 30251.5 | 11.84 | 11.84 | ||||
PSZ-AC_8:8 COOLING COIL | 30171.6 | 11.84 | 11.84 | ||||
PSZ-AC_9:9 COOLING COIL | 30296.7 | 11.84 | 11.84 | ||||
PSZ-AC_10:10 COOLING COIL | 34073.8 | 11.76 | 11.76 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | 69785.06 | 0.80 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | 35626.56 | 0.80 | |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | 35623.72 | 0.80 | |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | 35694.90 | 0.80 | |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | 35498.41 | 0.80 | |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | 63661.27 | 0.80 | |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | 33467.33 | 0.80 | |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | 33367.46 | 0.80 | |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | 33523.31 | 0.80 | |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | 38583.76 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 2.81 | 3006.16 | 1070.05 | 1.00 | 1.27 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 1.44 | 1538.32 | 1070.05 | 1.00 | 1.37 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 1.44 | 1538.19 | 1070.05 | 1.00 | 1.37 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 1.44 | 1541.61 | 1070.05 | 1.00 | 1.37 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 |
PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 1.43 | 1532.17 | 1070.05 | 1.00 | 1.37 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 2.53 | 2712.08 | 1070.05 | 1.00 | 1.28 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.34 | 1484.39 | 1107.16 | 1.00 | 1.34 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.34 | 1479.42 | 1107.16 | 1.00 | 1.34 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.34 | 1487.17 | 1107.16 | 1.00 | 1.34 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:50:00 |
PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 1.57 | 1680.33 | 1070.05 | 1.00 | 1.35 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
GAS TANK1 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK2 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK3 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK4 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK5 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK6 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK7 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:19
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
LGSTORE1 | 31009.69 | 37211.63 | 106.81 | 2.341 | 2.809 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:10:00 | 23.89 | 23.89 | 0.00765 | 41.90 | 0.00916 | 0.411 | 0.00 |
SMSTORE1 | 15868.43 | 19042.11 | 109.32 | 1.198 | 1.438 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | 23.89 | 23.89 | 0.00766 | 42.00 | 0.00916 | 0.206 | 0.00 |
SMSTORE2 | 15867.02 | 19040.42 | 109.31 | 1.198 | 1.437 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | 23.89 | 23.89 | 0.00766 | 42.00 | 0.00916 | 0.206 | 0.00 |
SMSTORE3 | 15902.28 | 19082.73 | 109.55 | 1.201 | 1.441 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | 23.89 | 23.89 | 0.00766 | 42.00 | 0.00916 | 0.206 | 0.00 |
SMSTORE4 | 15804.94 | 18965.93 | 108.88 | 1.193 | 1.432 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | 23.89 | 23.89 | 0.00766 | 42.00 | 0.00916 | 0.206 | 0.00 |
LGSTORE2 | 27976.22 | 33571.46 | 96.36 | 2.112 | 2.535 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | 23.89 | 23.89 | 0.00770 | 42.00 | 0.00916 | 0.411 | 0.00 |
SMSTORE5 | 14798.79 | 17758.55 | 101.95 | 1.117 | 1.341 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:50:00 | 23.89 | 23.89 | 0.00770 | 41.92 | 0.00916 | 0.206 | 0.00 |
SMSTORE6 | 14749.32 | 17699.18 | 101.61 | 1.114 | 1.336 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:50:00 | 23.89 | 23.89 | 0.00770 | 41.92 | 0.00916 | 0.206 | 0.00 |
SMSTORE7 | 14826.53 | 17791.83 | 102.14 | 1.119 | 1.343 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:50:00 | 23.89 | 23.89 | 0.00770 | 41.92 | 0.00916 | 0.206 | 0.00 |
SMSTORE8 | 17333.82 | 20800.59 | 119.41 | 1.309 | 1.570 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:00:00 | 23.89 | 23.89 | 0.00762 | 41.52 | 0.00916 | 0.206 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
LGSTORE1 | 15229.83 | 18275.79 | 52.46 | 0.674 | 0.808 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00736 | 6.30 | 0.00607 | 0.411 | 0.00 |
SMSTORE1 | 7490.88 | 8989.06 | 51.60 | 0.331 | 0.398 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00729 | 6.30 | 0.00607 | 0.206 | 0.00 |
SMSTORE2 | 7556.87 | 9068.24 | 52.06 | 0.334 | 0.401 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00729 | 6.30 | 0.00607 | 0.206 | 0.00 |
SMSTORE3 | 7626.65 | 9151.99 | 52.54 | 0.337 | 0.405 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00730 | 6.30 | 0.00607 | 0.206 | 0.00 |
SMSTORE4 | 7774.55 | 9329.47 | 53.56 | 0.344 | 0.413 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00730 | 6.30 | 0.00607 | 0.206 | 0.00 |
LGSTORE2 | 14744.80 | 17693.76 | 50.79 | 0.652 | 0.783 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00735 | 6.30 | 0.00607 | 0.411 | 0.00 |
SMSTORE5 | 7987.78 | 9585.33 | 55.03 | 0.353 | 0.424 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00731 | 6.30 | 0.00607 | 0.206 | 0.00 |
SMSTORE6 | 7991.59 | 9589.91 | 55.05 | 0.353 | 0.424 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00731 | 6.30 | 0.00607 | 0.206 | 0.00 |
SMSTORE7 | 8242.98 | 9891.58 | 56.79 | 0.365 | 0.437 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00732 | 6.30 | 0.00607 | 0.206 | 0.00 |
SMSTORE8 | 9749.93 | 11699.91 | 67.17 | 0.431 | 0.517 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00738 | 6.30 | 0.00607 | 0.206 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC_1:1 | 2.81 | 2.81 | 0.81 | 0.81 | 2.8094 | 2.8094 | 2.8094 | 1.0000 | 1.0000 |
PSZ-AC_2:2 | 1.44 | 1.44 | 0.40 | 0.40 | 1.4376 | 1.4376 | 1.4376 | 1.0000 | 1.0000 |
PSZ-AC_3:3 | 1.44 | 1.44 | 0.40 | 0.40 | 1.4375 | 1.4375 | 1.4375 | 1.0000 | 1.0000 |
PSZ-AC_4:4 | 1.44 | 1.44 | 0.40 | 0.40 | 1.4407 | 1.4407 | 1.4407 | 1.0000 | 1.0000 |
PSZ-AC_5:5 | 1.43 | 1.43 | 0.41 | 0.41 | 1.4319 | 1.4319 | 1.4319 | 1.0000 | 1.0000 |
PSZ-AC_6:6 | 2.53 | 2.53 | 0.78 | 0.78 | 2.5345 | 2.5345 | 2.5345 | 1.0000 | 1.0000 |
PSZ-AC_7:7 | 1.34 | 1.34 | 0.42 | 0.42 | 1.3407 | 1.3407 | 1.3407 | 1.0000 | 1.0000 |
PSZ-AC_8:8 | 1.34 | 1.34 | 0.42 | 0.42 | 1.3362 | 1.3362 | 1.3362 | 1.0000 | 1.0000 |
PSZ-AC_9:9 | 1.34 | 1.34 | 0.44 | 0.44 | 1.3432 | 1.3432 | 1.3432 | 1.0000 | 1.0000 |
PSZ-AC_10:10 | 1.57 | 1.57 | 0.52 | 0.52 | 1.5703 | 1.5703 | 1.5703 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 64861.650 | 46998.752 | 2.809370 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:10:00 | 32430.83 | 29099.50 | 1.872913 | 27.43 | 16.79 | 0.00787117 | 12.80 | 10.34 | 0.00700000 | 42.00 | 0.00915790 | 22.26 | 21.9700 | 23.89 | 0.00765030 | 40.4724 | 31001.53 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_1:1 | 69785.063 | 69785.063 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 69785.06 | 69785.06 | 2.809372 | 18.94 | 13.04 | 0.00717111 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 14.6467 | 21.11 | 0.00735966 | 46.1165 | 15229.83 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 33107.660 | 24011.993 | 1.437620 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | 16553.83 | 14845.86 | 0.958413 | 27.37 | 16.77 | 0.00787270 | 12.80 | 10.34 | 0.00700000 | 42.00 | 0.00915790 | 22.26 | 21.4667 | 23.89 | 0.00765805 | 40.5129 | 15868.43 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_2:2 | 35626.559 | 35626.559 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 35626.56 | 35626.56 | 1.437623 | 18.99 | 13.01 | 0.00711636 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 14.3111 | 21.11 | 0.00729072 | 45.6899 | 7490.88 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_3:3 | 33105.470 | 24010.073 | 1.437490 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | 16552.74 | 14844.70 | 0.958327 | 27.37 | 16.77 | 0.00787281 | 12.80 | 10.34 | 0.00700000 | 42.00 | 0.00915790 | 22.26 | 21.4686 | 23.89 | 0.00765816 | 40.5134 | 15867.02 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_3:3 | 35623.722 | 35623.722 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 35623.72 | 35623.72 | 1.437495 | 18.99 | 13.01 | 0.00711814 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 14.3124 | 21.11 | 0.00729282 | 45.7029 | 7556.87 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_4:4 | 33164.680 | 24056.996 | 1.440690 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | 16582.34 | 14873.49 | 0.960460 | 27.37 | 16.77 | 0.00787128 | 12.80 | 10.34 | 0.00700000 | 42.00 | 0.00915790 | 22.26 | 21.4209 | 23.89 | 0.00765693 | 40.5070 | 15902.28 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_4:4 | 35694.903 | 35694.903 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 35694.90 | 35694.90 | 1.440689 | 18.99 | 13.01 | 0.00712135 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 14.2806 | 21.11 | 0.00729611 | 45.7233 | 7626.65 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_5:5 | 33001.290 | 23927.915 | 1.431870 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | 16500.65 | 14794.02 | 0.954580 | 27.38 | 16.78 | 0.00787554 | 12.80 | 10.34 | 0.00700000 | 42.00 | 0.00915790 | 22.26 | 21.5529 | 23.89 | 0.00766036 | 40.5249 | 15804.94 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_5:5 | 35498.414 | 35498.414 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 35498.41 | 35498.41 | 1.431871 | 18.98 | 13.01 | 0.00712647 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 14.3686 | 21.11 | 0.00730334 | 45.7681 | 7774.55 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_6:6 | 59708.330 | 42831.173 | 2.534540 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | 29854.17 | 26618.39 | 1.689693 | 27.72 | 16.95 | 0.00793877 | 12.80 | 10.34 | 0.00700000 | 42.00 | 0.00915790 | 22.26 | 24.3523 | 23.89 | 0.00770248 | 40.7450 | 27976.22 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_6:6 | 63661.274 | 63661.274 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 63661.27 | 63661.27 | 2.534539 | 18.70 | 12.92 | 0.00714416 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 16.2349 | 21.11 | 0.00735190 | 46.0683 | 14744.80 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_7:7 | 31308.010 | 22561.178 | 1.340720 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:50:00 | 15654.00 | 13974.28 | 0.893813 | 27.59 | 16.89 | 0.00792212 | 12.80 | 10.34 | 0.00700000 | 42.00 | 0.00915790 | 22.26 | 23.0182 | 23.89 | 0.00769810 | 40.7222 | 14798.74 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_7:7 | 33467.331 | 33467.331 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 33467.33 | 33467.33 | 1.340717 | 18.84 | 12.95 | 0.00712267 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 15.3455 | 21.11 | 0.00731306 | 45.8283 | 7987.78 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_8:8 | 31224.560 | 22495.734 | 1.336230 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:50:00 | 15612.28 | 13933.82 | 0.890820 | 27.60 | 16.89 | 0.00792454 | 12.80 | 10.34 | 0.00700000 | 42.00 | 0.00915790 | 22.26 | 23.0955 | 23.89 | 0.00770007 | 40.7324 | 14749.20 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_8:8 | 33367.457 | 33367.457 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 33367.46 | 33367.46 | 1.336235 | 18.83 | 12.95 | 0.00712221 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 15.3970 | 21.11 | 0.00731327 | 45.8296 | 7991.59 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_9:9 | 31355.180 | 22598.305 | 1.343230 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:50:00 | 15677.59 | 13997.06 | 0.895487 | 27.59 | 16.89 | 0.00792082 | 12.80 | 10.34 | 0.00700000 | 42.00 | 0.00915790 | 22.26 | 22.9752 | 23.89 | 0.00769705 | 40.7166 | 14825.66 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_9:9 | 33523.308 | 33523.308 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 33523.31 | 33523.31 | 1.343229 | 18.84 | 12.97 | 0.00713263 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 15.3168 | 21.11 | 0.00732441 | 45.8986 | 8242.98 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_10:10 | 35310.390 | 25870.510 | 1.570340 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:00:00 | 17655.19 | 15902.55 | 1.046893 | 27.10 | 16.64 | 0.00782430 | 12.80 | 10.34 | 0.00700000 | 41.60 | 0.00915722 | 22.15 | 19.6524 | 23.89 | 0.00762319 | 40.3308 | 17323.12 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_10:10 | 38583.761 | 38583.761 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 38583.76 | 38583.76 | 1.570336 | 19.17 | 13.16 | 0.00720520 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 13.1016 | 21.11 | 0.00737600 | 46.2185 | 9749.93 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:37:19
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 64861.650 | 46998.752 | 2.809370 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.4721 | 1004.8586 | 1.1738 | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.809372 | 3.29759943 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:10:00 | Sensible | 32430.83 | 29099.50 | 1.0000 | 2.19839844 | 1.872913 | 27.43 | 16.79 | 0.00787117 | 47654.0 | 12.80 | 10.34 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 32430.83 | 42.00 | 0.00915790 | 22.26 | 0.41147883 | 21.9700 | 23.89 | 0.00765030 | 23.89 | 0.00765030 | 40.4724 | 31001.53 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 69785.063 | 69785.063 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.809372 | 3.29759943 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 69785.06 | 69785.06 | 1.0000 | 3.29759943 | 2.809372 | 18.94 | 13.04 | 0.00717111 | 37218.6 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 69785.06 | 6.30 | 0.00607234 | 6.30 | 0.41147883 | 14.6467 | 21.11 | 0.00735966 | 21.11 | 0.00735966 | 46.1165 | 15229.83 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 33107.660 | 24011.993 | 1.437620 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.4750 | 1004.8586 | 1.1738 | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.437623 | 1.68746088 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | Sensible | 16553.83 | 14845.86 | 1.0000 | 1.12497164 | 0.958413 | 27.37 | 16.77 | 0.00787270 | 47595.2 | 12.80 | 10.34 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 16553.83 | 42.00 | 0.00915790 | 22.26 | 0.20573941 | 21.4667 | 23.89 | 0.00765805 | 23.89 | 0.00765805 | 40.5129 | 15868.43 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 35626.559 | 35626.559 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.437623 | 1.68746088 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 35626.56 | 35626.56 | 1.0000 | 1.68746088 | 1.437623 | 18.99 | 13.01 | 0.00711636 | 37130.3 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 35626.56 | 6.30 | 0.00607234 | 6.30 | 0.20573941 | 14.3111 | 21.11 | 0.00729072 | 21.11 | 0.00729072 | 45.6899 | 7490.88 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 33105.470 | 24010.073 | 1.437490 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.4752 | 1004.8586 | 1.1738 | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.437495 | 1.68731053 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | Sensible | 16552.74 | 14844.70 | 1.0000 | 1.12486991 | 0.958327 | 27.37 | 16.77 | 0.00787281 | 47595.7 | 12.80 | 10.34 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 16552.74 | 42.00 | 0.00915790 | 22.26 | 0.20573941 | 21.4686 | 23.89 | 0.00765816 | 23.89 | 0.00765816 | 40.5134 | 15867.02 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 35623.722 | 35623.722 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.437495 | 1.68731053 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 35623.72 | 35623.72 | 1.0000 | 1.68731053 | 1.437495 | 18.99 | 13.01 | 0.00711814 | 37134.6 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 35623.72 | 6.30 | 0.00607234 | 6.30 | 0.20573941 | 14.3124 | 21.11 | 0.00729282 | 21.11 | 0.00729282 | 45.7029 | 7556.87 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 33164.680 | 24056.996 | 1.440690 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.4723 | 1004.8586 | 1.1738 | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.440689 | 1.69106015 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | Sensible | 16582.34 | 14873.49 | 1.0000 | 1.12737398 | 0.960460 | 27.37 | 16.77 | 0.00787128 | 47586.0 | 12.80 | 10.34 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 16582.34 | 42.00 | 0.00915790 | 22.26 | 0.20573941 | 21.4209 | 23.89 | 0.00765693 | 23.89 | 0.00765693 | 40.5070 | 15902.28 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 35694.903 | 35694.903 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.440689 | 1.69106015 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 35694.90 | 35694.90 | 1.0000 | 1.69106015 | 1.440689 | 18.99 | 13.01 | 0.00712135 | 37147.5 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 35694.90 | 6.30 | 0.00607234 | 6.30 | 0.20573941 | 14.2806 | 21.11 | 0.00729611 | 21.11 | 0.00729611 | 45.7233 | 7626.65 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 33001.290 | 23927.915 | 1.431870 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.4802 | 1004.8586 | 1.1738 | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.431871 | 1.68070938 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | Sensible | 16500.65 | 14794.02 | 1.0000 | 1.12047212 | 0.954580 | 27.38 | 16.78 | 0.00787554 | 47613.1 | 12.80 | 10.34 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 16500.65 | 42.00 | 0.00915790 | 22.26 | 0.20573941 | 21.5529 | 23.89 | 0.00766036 | 23.89 | 0.00766036 | 40.5249 | 15804.94 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 35498.414 | 35498.414 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.431871 | 1.68070938 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 35498.41 | 35498.41 | 1.0000 | 1.68070938 | 1.431871 | 18.98 | 13.01 | 0.00712647 | 37147.2 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 35498.41 | 6.30 | 0.00607234 | 6.30 | 0.20573941 | 14.3686 | 21.11 | 0.00730334 | 21.11 | 0.00730334 | 45.7681 | 7774.55 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 59708.330 | 42831.173 | 2.534540 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.5978 | 1004.8586 | 1.1738 | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.534539 | 2.97500486 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | Sensible | 29854.17 | 26618.39 | 1.0000 | 1.98333747 | 1.689693 | 27.72 | 16.95 | 0.00793877 | 48119.0 | 12.80 | 10.34 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 29854.17 | 42.00 | 0.00915790 | 22.26 | 0.41147883 | 24.3523 | 23.89 | 0.00770248 | 23.89 | 0.00770248 | 40.7450 | 27976.22 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 63661.274 | 63661.274 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.534539 | 2.97500486 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 63661.27 | 63661.27 | 1.0000 | 2.97500486 | 2.534539 | 18.70 | 12.92 | 0.00714416 | 36910.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 63661.27 | 6.30 | 0.00607234 | 6.30 | 0.41147883 | 16.2349 | 21.11 | 0.00735190 | 21.11 | 0.00735190 | 46.0683 | 14744.80 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 31308.010 | 22561.178 | 1.340720 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.5668 | 1004.8586 | 1.1738 | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.340717 | 1.57371411 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:50:00 | Sensible | 15654.00 | 13974.28 | 1.0000 | 1.04914509 | 0.893813 | 27.59 | 16.89 | 0.00792212 | 47943.9 | 12.80 | 10.34 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 15654.00 | 42.00 | 0.00915790 | 22.26 | 0.20573941 | 23.0182 | 23.89 | 0.00769810 | 23.89 | 0.00769810 | 40.7222 | 14798.74 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 33467.331 | 33467.331 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.340717 | 1.57371411 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 33467.33 | 33467.33 | 1.0000 | 1.57371411 | 1.340717 | 18.84 | 12.95 | 0.00712267 | 36990.3 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 33467.33 | 6.30 | 0.00607234 | 6.30 | 0.20573941 | 15.3455 | 21.11 | 0.00731306 | 21.11 | 0.00731306 | 45.8283 | 7987.78 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 31224.560 | 22495.734 | 1.336230 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.5713 | 1004.8586 | 1.1738 | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.336235 | 1.56845290 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:50:00 | Sensible | 15612.28 | 13933.82 | 1.0000 | 1.04563156 | 0.890820 | 27.60 | 16.89 | 0.00792454 | 47959.6 | 12.80 | 10.34 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 15612.28 | 42.00 | 0.00915790 | 22.26 | 0.20573941 | 23.0955 | 23.89 | 0.00770007 | 23.89 | 0.00770007 | 40.7324 | 14749.20 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 33367.457 | 33367.457 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.336235 | 1.56845290 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 33367.46 | 33367.46 | 1.0000 | 1.56845290 | 1.336235 | 18.83 | 12.95 | 0.00712221 | 36981.4 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 33367.46 | 6.30 | 0.00607234 | 6.30 | 0.20573941 | 15.3970 | 21.11 | 0.00731327 | 21.11 | 0.00731327 | 45.8296 | 7991.59 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 31355.180 | 22598.305 | 1.343230 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.5644 | 1004.8586 | 1.1738 | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.343229 | 1.57666286 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:50:00 | Sensible | 15677.59 | 13997.06 | 1.0000 | 1.05110923 | 0.895487 | 27.59 | 16.89 | 0.00792082 | 47935.5 | 12.80 | 10.34 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 15677.59 | 42.00 | 0.00915790 | 22.26 | 0.20573941 | 22.9752 | 23.89 | 0.00769705 | 23.89 | 0.00769705 | 40.7166 | 14825.66 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 33523.308 | 33523.308 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.343229 | 1.57666286 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 33523.31 | 33523.31 | 1.0000 | 1.57666286 | 1.343229 | 18.84 | 12.97 | 0.00713263 | 37019.9 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 33523.31 | 6.30 | 0.00607234 | 6.30 | 0.20573941 | 15.3168 | 21.11 | 0.00732441 | 21.11 | 0.00732441 | 45.8986 | 8242.98 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 35310.390 | 25870.510 | 1.570340 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.3850 | 1004.8586 | 1.1738 | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.570336 | 1.84323734 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:00:00 | Sensible | 17655.19 | 15902.55 | 1.0000 | 1.22882817 | 1.046893 | 27.10 | 16.64 | 0.00782430 | 47196.1 | 12.80 | 10.34 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 17655.19 | 41.60 | 0.00915722 | 22.15 | 0.20573941 | 19.6524 | 23.89 | 0.00762319 | 23.89 | 0.00762319 | 40.3308 | 17323.12 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 38583.761 | 38583.761 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.570336 | 1.84323734 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 38583.76 | 38583.76 | 1.0000 | 1.84323734 | 1.570336 | 19.17 | 13.16 | 0.00720520 | 37537.9 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 38583.76 | 6.30 | 0.00607234 | 6.30 | 0.20573941 | 13.1016 | 21.11 | 0.00737600 | 21.11 | 0.00737600 | 46.2185 | 9749.93 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:19
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
LGSTORE1 | 4087.50 | 2033.67 | 1218.50 |
SMSTORE1 | 3968.17 | 1506.17 | 939.67 |
SMSTORE2 | 3112.33 | 1549.50 | 1040.17 |
SMSTORE3 | 3092.83 | 1584.83 | 1034.00 |
SMSTORE4 | 3048.17 | 1661.17 | 1040.83 |
LGSTORE2 | 2704.33 | 1638.33 | 972.67 |
SMSTORE5 | 2633.33 | 1679.33 | 980.50 |
SMSTORE6 | 2620.00 | 1699.33 | 983.67 |
SMSTORE7 | 2617.17 | 1729.33 | 977.00 |
SMSTORE8 | 2714.67 | 1638.67 | 877.83 |
Facility | 4240.67 | 2610.00 | 1426.83 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
LGSTORE1 | 0.00 | 1.33 | 0.00 | 1.17 |
SMSTORE1 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 0.00 | 5.83 | 0.00 | 0.00 |
SMSTORE3 | 0.00 | 6.67 | 0.00 | 0.00 |
SMSTORE4 | 0.00 | 5.00 | 0.00 | 0.00 |
LGSTORE2 | 0.00 | 4.50 | 0.00 | 0.00 |
SMSTORE5 | 0.00 | 4.00 | 0.00 | 0.00 |
SMSTORE6 | 0.00 | 4.00 | 0.00 | 0.00 |
SMSTORE7 | 0.00 | 3.83 | 0.00 | 0.00 |
SMSTORE8 | 0.00 | 6.67 | 0.00 | 0.00 |
Facility | 0.00 | 13.33 | 0.00 | 1.17 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:19
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
LGSTORE1 | 16.93 | 56.25 | 1805.20 | 0.848 | 0.333 | 0.000 | 0.000 |
SMSTORE1 | 8.46 | 28.12 | 902.60 | 0.682 | 0.375 | 0.000 | 0.000 |
SMSTORE2 | 7.08 | 28.12 | 902.60 | 0.848 | 0.494 | 0.000 | 0.000 |
SMSTORE3 | 7.08 | 28.12 | 902.60 | 0.848 | 0.494 | 0.000 | 0.000 |
SMSTORE4 | 7.08 | 28.12 | 902.60 | 0.848 | 0.494 | 0.000 | 0.000 |
LGSTORE2 | 24.77 | 56.25 | 1805.20 | 0.848 | 0.462 | 0.000 | 0.000 |
SMSTORE5 | 12.39 | 28.12 | 902.60 | 0.848 | 0.527 | 0.000 | 0.000 |
SMSTORE6 | 12.39 | 28.12 | 902.60 | 0.848 | 0.527 | 0.000 | 0.000 |
SMSTORE7 | 12.39 | 28.12 | 902.60 | 0.848 | 0.527 | 0.000 | 0.000 |
SMSTORE8 | 12.39 | 28.12 | 902.60 | 0.848 | 0.536 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
LGSTORE1 | 16.93 | 56.25 | 1805.20 | 0.777 | 0.000 | 0.000 | 0.000 |
SMSTORE1 | 8.46 | 28.12 | 902.60 | 0.000 | 0.000 | 0.000 | 0.000 |
SMSTORE2 | 7.08 | 28.12 | 902.60 | 0.774 | 0.000 | 0.000 | 0.000 |
SMSTORE3 | 7.08 | 28.12 | 902.60 | 0.774 | 0.000 | 0.000 | 0.000 |
SMSTORE4 | 7.08 | 28.12 | 902.60 | 0.774 | 0.000 | 0.000 | 0.000 |
LGSTORE2 | 24.77 | 56.25 | 1805.20 | 0.777 | 0.000 | 0.000 | 0.000 |
SMSTORE5 | 12.39 | 28.12 | 902.60 | 0.777 | 0.000 | 0.000 | 0.000 |
SMSTORE6 | 12.39 | 28.12 | 902.60 | 0.777 | 0.000 | 0.000 | 0.000 |
SMSTORE7 | 12.39 | 28.12 | 902.60 | 0.777 | 0.000 | 0.000 | 0.000 |
SMSTORE8 | 12.39 | 28.12 | 902.60 | 0.776 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:37:19
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
LGSTORE1 | PSZ-AC_1:1 | 16.93 | 56.25 | 1805.20 | 348.39 | 0.4115 | 0.411 |
SMSTORE1 | PSZ-AC_2:2 | 8.46 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE2 | PSZ-AC_3:3 | 7.08 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE3 | PSZ-AC_4:4 | 7.08 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE4 | PSZ-AC_5:5 | 7.08 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
LGSTORE2 | PSZ-AC_6:6 | 24.77 | 56.25 | 1805.20 | 348.39 | 0.4115 | 0.411 |
SMSTORE5 | PSZ-AC_7:7 | 12.39 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE6 | PSZ-AC_8:8 | 12.39 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE7 | PSZ-AC_9:9 | 12.39 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE8 | PSZ-AC_10:10 | 12.39 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
Total Facility | 120.95 | 337.50 | 10831.20 | 2090.32 | 2.4689 | 2.469 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
LGSTORE1 | 8803559.40 | 0.00 | 8803559.40 | 3505960.47 | 12309519.87 | 12976396.34 | 2817.00 | 5943.00 | 0.00 | 103.00 |
SMSTORE1 | 3556677.43 | 0.00 | 3556677.43 | 1952020.86 | 5508698.29 | 6488198.17 | 4303.00 | 4457.00 | 0.00 | 103.00 |
SMSTORE2 | 3525572.74 | 0.00 | 3525572.74 | 1960785.24 | 5486357.97 | 6488198.17 | 4000.00 | 4760.00 | 0.00 | 365.00 |
SMSTORE3 | 3525572.84 | 0.00 | 3525572.84 | 1960785.24 | 5486358.07 | 6488198.17 | 4000.00 | 4760.00 | 0.00 | 365.00 |
SMSTORE4 | 3525573.96 | 0.00 | 3525573.96 | 1960785.24 | 5486359.20 | 6488198.17 | 4000.00 | 4760.00 | 0.00 | 365.00 |
LGSTORE2 | 6510480.66 | 0.00 | 6510480.66 | 3452391.79 | 9962872.45 | 12976396.34 | 4365.00 | 4395.00 | 0.00 | 365.00 |
SMSTORE5 | 3255233.90 | 0.00 | 3255233.90 | 1964207.59 | 5219441.49 | 6488198.17 | 4365.00 | 4395.00 | 0.00 | 365.00 |
SMSTORE6 | 3255234.87 | 0.00 | 3255234.87 | 1964207.59 | 5219442.46 | 6488198.17 | 4365.00 | 4395.00 | 0.00 | 365.00 |
SMSTORE7 | 3255237.14 | 0.00 | 3255237.14 | 1964207.59 | 5219444.73 | 6488198.17 | 4365.00 | 4395.00 | 0.00 | 365.00 |
SMSTORE8 | 3255327.57 | 0.00 | 3255327.57 | 2060429.81 | 5315757.38 | 6488198.17 | 4365.00 | 4395.00 | 0.00 | 366.33 |
Total Facility | 42468470.52 | 0.00 | 42468470.52 | 22745781.39 | 65214251.91 | 77858378.04 | 4365.00 | 6246.00 | 0.00 | 731.33 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
LGSTORE1 | 0.4115 | 0.0000 | 0.4115 | 0.1614 | 0.5729 | 0.4115 | 0.00 | 5840.00 | 0.00 |
SMSTORE1 | 0.1655 | 0.0000 | 0.1655 | 0.0910 | 0.2566 | 0.2057 | 1486.00 | 4354.00 | 0.00 |
SMSTORE2 | 0.2057 | 0.0000 | 0.2057 | 0.1198 | 0.3256 | 0.2057 | 0.00 | 4395.00 | 0.00 |
SMSTORE3 | 0.2057 | 0.0000 | 0.2057 | 0.1198 | 0.3256 | 0.2057 | 0.00 | 4395.00 | 0.00 |
SMSTORE4 | 0.2057 | 0.0000 | 0.2057 | 0.1198 | 0.3256 | 0.2057 | 0.00 | 4395.00 | 0.00 |
LGSTORE2 | 0.4115 | 0.0000 | 0.4115 | 0.2239 | 0.6354 | 0.4115 | 0.00 | 4030.00 | 0.00 |
SMSTORE5 | 0.2057 | 0.0000 | 0.2057 | 0.1278 | 0.3335 | 0.2057 | 0.00 | 4030.00 | 0.00 |
SMSTORE6 | 0.2057 | 0.0000 | 0.2057 | 0.1278 | 0.3335 | 0.2057 | 0.00 | 4030.00 | 0.00 |
SMSTORE7 | 0.2057 | 0.0000 | 0.2057 | 0.1278 | 0.3335 | 0.2057 | 0.00 | 4030.00 | 0.00 |
SMSTORE8 | 0.2057 | 0.0000 | 0.2057 | 0.1299 | 0.3356 | 0.2057 | 0.00 | 4030.00 | 0.00 |
Total Facility | 2.4287 | 0.0000 | 2.4287 | 1.3490 | 3.7777 | 2.4689 | 1486.00 | 5943.00 | 0.00 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-AC_1:1 | 12129228.48 | 0.00 | 12129228.48 | 12976396.34 | 2817.00 | 0.00 | 5943.00 | 103.00 |
PSZ-AC_2:2 | 4900250.76 | 0.00 | 4900250.76 | 6488198.17 | 4303.00 | 0.00 | 4457.00 | 103.00 |
PSZ-AC_3:3 | 4857405.99 | 0.00 | 4857405.99 | 6488198.17 | 4000.00 | 0.00 | 4760.00 | 365.00 |
PSZ-AC_4:4 | 4857405.99 | 0.00 | 4857405.99 | 6488198.17 | 4000.00 | 0.00 | 4760.00 | 365.00 |
PSZ-AC_5:5 | 4857405.99 | 0.00 | 4857405.99 | 6488198.17 | 4000.00 | 0.00 | 4760.00 | 365.00 |
PSZ-AC_6:6 | 8969873.66 | 0.00 | 8969873.66 | 12976396.34 | 4365.00 | 0.00 | 4395.00 | 365.00 |
PSZ-AC_7:7 | 4484936.83 | 0.00 | 4484936.83 | 6488198.17 | 4365.00 | 0.00 | 4395.00 | 365.00 |
PSZ-AC_8:8 | 4484936.83 | 0.00 | 4484936.83 | 6488198.17 | 4365.00 | 0.00 | 4395.00 | 365.00 |
PSZ-AC_9:9 | 4484936.83 | 0.00 | 4484936.83 | 6488198.17 | 4365.00 | 0.00 | 4395.00 | 365.00 |
PSZ-AC_10:10 | 4485073.14 | 0.00 | 4485073.14 | 6488198.17 | 4365.00 | 0.00 | 4395.00 | 366.33 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-AC_1:1 | 0.5669 | 0.0000 | 0.5669 | 0.4115 | 0.00 | 0.00 | 5840.00 |
PSZ-AC_2:2 | 0.2281 | 0.0000 | 0.2281 | 0.2057 | 1486.00 | 0.00 | 4354.00 |
PSZ-AC_3:3 | 0.2835 | 0.0000 | 0.2835 | 0.2057 | 0.00 | 0.00 | 4395.00 |
PSZ-AC_4:4 | 0.2835 | 0.0000 | 0.2835 | 0.2057 | 0.00 | 0.00 | 4395.00 |
PSZ-AC_5:5 | 0.2835 | 0.0000 | 0.2835 | 0.2057 | 0.00 | 0.00 | 4395.00 |
PSZ-AC_6:6 | 0.5669 | 0.0000 | 0.5669 | 0.4115 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_7:7 | 0.2835 | 0.0000 | 0.2835 | 0.2057 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_8:8 | 0.2835 | 0.0000 | 0.2835 | 0.2057 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_9:9 | 0.2835 | 0.0000 | 0.2835 | 0.2057 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_10:10 | 0.2835 | 0.0000 | 0.2835 | 0.2057 | 0.00 | 0.00 | 4030.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-AC_1:1 | 0.00 | 5943.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_2:2 | 0.00 | 5922.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_3:3 | 0.00 | 4760.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_4:4 | 0.00 | 4760.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_5:5 | 0.00 | 4760.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_6:6 | 0.00 | 4395.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_7:7 | 0.00 | 4395.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_8:8 | 0.00 | 4395.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_9:9 | 0.00 | 4395.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_10:10 | 0.00 | 4396.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-AC_1:1 | 0.0000 | 0.5669 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_2:2 | 0.0000 | 0.2289 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_3:3 | 0.0000 | 0.2835 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_4:4 | 0.0000 | 0.2835 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_5:5 | 0.0000 | 0.2835 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_6:6 | 0.0000 | 0.5671 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_7:7 | 0.0000 | 0.2835 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_8:8 | 0.0000 | 0.2835 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_9:9 | 0.0000 | 0.2835 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_10:10 | 0.0000 | 0.2835 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:19
Surfaces by ClassTotal | Outdoors | |
Wall | 40 | 22 |
Floor | 10 | 10 |
Roof | 10 | 10 |
Internal Mass | 10 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 36 | 36 |
Door | 12 | 12 |
Glass Door | 12 | 12 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 10 |
Conditioned Zones | 10 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 830 |
Defaulted Fields | 823 |
Fields with Defaults | 2682 |
Autosized Fields | 184 |
Autosizable Fields | 458 |
Autocalculated Fields | 128 |
Autocalculatable Fields | 256 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:37:19
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1240.02 | 2102.83 | 01-JAN-07:50 | 135646.39 | 10-JUN-16:00 |
Electricity:Building | 494.83 | 891.83 | 01-JAN-00:20 | 31518.67 | 01-JAN-11:10 |
Electricity:Zone:LGSTORE1 | 113.36 | 148.64 | 01-JAN-00:20 | 5964.88 | 01-JAN-10:10 |
Electricity:SpaceType:GENERAL | 494.83 | 891.83 | 01-JAN-00:20 | 31518.67 | 01-JAN-11:10 |
InteriorLights:Electricity | 366.68 | 450.00 | 01-JAN-00:20 | 23459.17 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:LGSTORE1 | 87.12 | 75.00 | 01-JAN-00:20 | 4621.63 | 01-JAN-10:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 366.68 | 450.00 | 01-JAN-00:20 | 23459.17 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity | 366.68 | 450.00 | 01-JAN-00:20 | 23459.17 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:LGSTORE1 | 87.12 | 75.00 | 01-JAN-00:20 | 4621.63 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 366.68 | 450.00 | 01-JAN-00:20 | 23459.17 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE1 | 66.33 | 74.32 | 01-JAN-00:20 | 3498.69 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE1 | 53.20 | 37.50 | 01-JAN-00:20 | 2827.07 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE1 | 53.20 | 37.50 | 01-JAN-00:20 | 2827.07 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE2 | 47.99 | 74.32 | 01-JAN-00:10 | 3226.84 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE2 | 37.57 | 37.50 | 01-JAN-00:10 | 2555.22 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE2 | 37.57 | 37.50 | 01-JAN-00:10 | 2555.22 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE3 | 47.99 | 74.32 | 01-JAN-00:10 | 3226.84 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE3 | 37.57 | 37.50 | 01-JAN-00:10 | 2555.22 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE3 | 37.57 | 37.50 | 01-JAN-00:10 | 2555.22 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE4 | 47.99 | 74.32 | 01-JAN-00:10 | 3226.84 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE4 | 37.57 | 37.50 | 01-JAN-00:10 | 2555.22 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE4 | 37.57 | 37.50 | 01-JAN-00:10 | 2555.22 | 01-JAN-10:10 |
Electricity:Zone:LGSTORE2 | 56.34 | 148.64 | 01-JAN-00:10 | 4070.21 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:LGSTORE2 | 37.16 | 75.00 | 01-JAN-00:10 | 2726.96 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:LGSTORE2 | 37.16 | 75.00 | 01-JAN-00:10 | 2726.96 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE5 | 28.71 | 74.32 | 01-JAN-00:10 | 2076.09 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE5 | 19.12 | 37.50 | 01-JAN-00:10 | 1404.46 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE5 | 19.12 | 37.50 | 01-JAN-00:10 | 1404.46 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE6 | 28.71 | 74.32 | 01-JAN-00:10 | 2076.09 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE6 | 19.12 | 37.50 | 01-JAN-00:10 | 1404.46 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE6 | 19.12 | 37.50 | 01-JAN-00:10 | 1404.46 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE7 | 28.71 | 74.32 | 01-JAN-00:10 | 2076.09 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE7 | 19.12 | 37.50 | 01-JAN-00:10 | 1404.46 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE7 | 19.12 | 37.50 | 01-JAN-00:10 | 1404.46 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE8 | 28.71 | 74.32 | 01-JAN-00:10 | 2076.09 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE8 | 19.12 | 37.50 | 01-JAN-00:10 | 1404.46 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE8 | 19.12 | 37.50 | 01-JAN-00:10 | 1404.46 | 01-JAN-11:10 |
InteriorEquipment:Electricity | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:LGSTORE1 | 26.25 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-10:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LGSTORE1 | 26.25 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE1 | 13.12 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE1 | 13.12 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE2 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE2 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE3 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE3 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE4 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE4 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:LGSTORE2 | 19.17 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LGSTORE2 | 19.17 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE5 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE5 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE6 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE6 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE7 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE7 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE8 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE8 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
ElectricityPurchased:Facility | 1240.02 | 2102.83 | 01-JAN-07:50 | 135646.39 | 10-JUN-16:00 |
ElectricityPurchased:Plant | 1240.02 | 2102.83 | 01-JAN-07:50 | 135646.39 | 10-JUN-16:00 |
Cogeneration:ElectricityPurchased | 1240.02 | 2102.83 | 01-JAN-07:50 | 135646.39 | 10-JUN-16:00 |
General:Cogeneration:ElectricityPurchased | 1240.02 | 2102.83 | 01-JAN-07:50 | 135646.39 | 10-JUN-16:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1240.02 | 2102.83 | 01-JAN-07:50 | 135646.39 | 10-JUN-16:00 |
ElectricityNet:Plant | 1240.02 | 2102.83 | 01-JAN-07:50 | 135646.39 | 10-JUN-16:00 |
Cogeneration:ElectricityNet | 1240.02 | 2102.83 | 01-JAN-07:50 | 135646.39 | 10-JUN-16:00 |
General:Cogeneration:ElectricityNet | 1240.02 | 2102.83 | 01-JAN-07:50 | 135646.39 | 10-JUN-16:00 |
Electricity:HVAC | 626.49 | 0.00 | 01-JAN-00:10 | 98938.22 | 22-JUN-16:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 494.57 | 0.00 | 01-JAN-00:10 | 85981.95 | 10-JUN-16:00 |
General:Cooling:Electricity | 494.57 | 0.00 | 01-JAN-00:10 | 85981.95 | 10-JUN-16:00 |
Fans:Electricity | 131.92 | 0.00 | 01-JAN-00:10 | 13439.89 | 01-JUL-15:00 |
General:Fans:Electricity | 131.92 | 0.00 | 01-JAN-00:10 | 13439.89 | 01-JUL-15:00 |
ExteriorLights:Electricity | 60.04 | 0.00 | 01-JAN-07:20 | 5507.06 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 60.04 | 0.00 | 01-JAN-07:20 | 5507.06 | 01-JAN-06:10 |
Electricity:Plant | 58.66 | 1211.00 | 03-JAN-08:10 | 9745.77 | 05-JAN-14:30 |
WaterSystems:Electricity | 58.66 | 1211.00 | 03-JAN-08:10 | 9745.77 | 05-JAN-14:30 |
Water Heater:WaterSystems:Electricity | 58.66 | 1211.00 | 03-JAN-08:10 | 9745.77 | 05-JAN-14:30 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 8.36 | 0.00 | 01-JAN-00:10 | 124439.16 | 02-JAN-08:10 |
NaturalGas:HVAC | 8.36 | 0.00 | 01-JAN-00:10 | 124439.16 | 02-JAN-08:10 |
Heating:NaturalGas | 8.36 | 0.00 | 01-JAN-00:10 | 124439.16 | 02-JAN-08:10 |
General:Heating:NaturalGas | 8.36 | 0.00 | 01-JAN-00:10 | 124439.16 | 02-JAN-08:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water:Plant | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
WaterSystems:Water | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water Heater:WaterSystems:Water | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
MainsWater:Facility | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
MainsWater:Plant | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
WaterSystems:MainsWater | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water Heater:WaterSystems:MainsWater | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 2870.37 | 0.00 | 01-JAN-00:10 | 444426.61 | 01-JUL-15:00 |
EnergyTransfer:Building | 999.90 | 0.00 | 01-JAN-00:10 | 156299.29 | 12-JUN-16:10 |
EnergyTransfer:Zone:LGSTORE1 | 204.17 | 0.00 | 01-JAN-00:10 | 26533.69 | 08-JUN-16:20 |
Heating:EnergyTransfer | 8.46 | 0.00 | 01-JAN-00:10 | 70680.39 | 02-JAN-08:10 |
Heating:EnergyTransfer:Zone:LGSTORE1 | 0.33 | 0.00 | 01-JAN-00:10 | 11124.96 | 01-JAN-08:10 |
General:Heating:EnergyTransfer | 8.46 | 0.00 | 01-JAN-00:10 | 70680.39 | 02-JAN-08:10 |
General:Heating:EnergyTransfer:Zone:LGSTORE1 | 0.33 | 0.00 | 01-JAN-00:10 | 11124.96 | 01-JAN-08:10 |
Cooling:EnergyTransfer | 991.43 | 0.00 | 01-JAN-00:10 | 156299.29 | 12-JUN-16:10 |
Cooling:EnergyTransfer:Zone:LGSTORE1 | 203.83 | 0.00 | 01-JAN-00:10 | 26533.69 | 08-JUN-16:20 |
General:Cooling:EnergyTransfer | 991.43 | 0.00 | 01-JAN-00:10 | 156299.29 | 12-JUN-16:10 |
General:Cooling:EnergyTransfer:Zone:LGSTORE1 | 203.83 | 0.00 | 01-JAN-00:10 | 26533.69 | 08-JUN-16:20 |
EnergyTransfer:Zone:SMSTORE1 | 106.13 | 0.00 | 01-JAN-00:10 | 12893.62 | 08-JUN-16:10 |
Heating:EnergyTransfer:Zone:SMSTORE1 | 0.11 | 0.00 | 01-JAN-00:10 | 2196.77 | 02-JAN-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE1 | 0.11 | 0.00 | 01-JAN-00:10 | 2196.77 | 02-JAN-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE1 | 106.02 | 0.00 | 01-JAN-00:10 | 12893.62 | 08-JUN-16:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE1 | 106.02 | 0.00 | 01-JAN-00:10 | 12893.62 | 08-JUN-16:10 |
EnergyTransfer:Zone:SMSTORE2 | 83.75 | 0.00 | 01-JAN-00:10 | 13061.05 | 12-JUN-16:10 |
Heating:EnergyTransfer:Zone:SMSTORE2 | 1.29 | 0.00 | 01-JAN-00:10 | 5285.75 | 01-JAN-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE2 | 1.29 | 0.00 | 01-JAN-00:10 | 5285.75 | 01-JAN-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE2 | 82.46 | 0.00 | 01-JAN-00:10 | 13061.05 | 12-JUN-16:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE2 | 82.46 | 0.00 | 01-JAN-00:10 | 13061.05 | 12-JUN-16:10 |
EnergyTransfer:Zone:SMSTORE3 | 83.83 | 0.00 | 01-JAN-00:10 | 13180.04 | 12-JUN-16:10 |
Heating:EnergyTransfer:Zone:SMSTORE3 | 1.30 | 0.00 | 01-JAN-00:10 | 6533.45 | 01-JAN-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE3 | 1.30 | 0.00 | 01-JAN-00:10 | 6533.45 | 01-JAN-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE3 | 82.53 | 0.00 | 01-JAN-00:10 | 13180.04 | 12-JUN-16:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE3 | 82.53 | 0.00 | 01-JAN-00:10 | 13180.04 | 12-JUN-16:10 |
EnergyTransfer:Zone:SMSTORE4 | 81.74 | 0.00 | 01-JAN-00:10 | 13134.32 | 12-JUN-16:10 |
Heating:EnergyTransfer:Zone:SMSTORE4 | 1.34 | 0.00 | 01-JAN-00:10 | 7115.72 | 01-JAN-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE4 | 1.34 | 0.00 | 01-JAN-00:10 | 7115.72 | 01-JAN-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE4 | 80.41 | 0.00 | 01-JAN-00:10 | 13134.32 | 12-JUN-16:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE4 | 80.41 | 0.00 | 01-JAN-00:10 | 13134.32 | 12-JUN-16:10 |
EnergyTransfer:Zone:LGSTORE2 | 138.93 | 0.00 | 01-JAN-00:10 | 24408.25 | 12-JUN-14:20 |
Heating:EnergyTransfer:Zone:LGSTORE2 | 1.20 | 0.00 | 01-JAN-00:10 | 15718.29 | 02-JAN-08:10 |
General:Heating:EnergyTransfer:Zone:LGSTORE2 | 1.20 | 0.00 | 01-JAN-00:10 | 15718.29 | 02-JAN-08:10 |
Cooling:EnergyTransfer:Zone:LGSTORE2 | 137.73 | 0.00 | 01-JAN-00:10 | 24408.25 | 12-JUN-14:20 |
General:Cooling:EnergyTransfer:Zone:LGSTORE2 | 137.73 | 0.00 | 01-JAN-00:10 | 24408.25 | 12-JUN-14:20 |
EnergyTransfer:Zone:SMSTORE5 | 72.34 | 0.00 | 01-JAN-00:10 | 13042.96 | 12-JUN-14:30 |
Heating:EnergyTransfer:Zone:SMSTORE5 | 0.62 | 0.00 | 01-JAN-00:10 | 8186.18 | 01-JAN-09:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE5 | 0.62 | 0.00 | 01-JAN-00:10 | 8186.18 | 01-JAN-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE5 | 71.71 | 0.00 | 01-JAN-00:10 | 13042.96 | 12-JUN-14:30 |
General:Cooling:EnergyTransfer:Zone:SMSTORE5 | 71.71 | 0.00 | 01-JAN-00:10 | 13042.96 | 12-JUN-14:30 |
EnergyTransfer:Zone:SMSTORE6 | 71.85 | 0.00 | 01-JAN-00:10 | 13023.59 | 12-JUN-14:30 |
Heating:EnergyTransfer:Zone:SMSTORE6 | 0.64 | 0.00 | 01-JAN-00:10 | 8332.73 | 01-JAN-09:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE6 | 0.64 | 0.00 | 01-JAN-00:10 | 8332.73 | 01-JAN-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE6 | 71.20 | 0.00 | 01-JAN-00:10 | 13023.59 | 12-JUN-14:30 |
General:Cooling:EnergyTransfer:Zone:SMSTORE6 | 71.20 | 0.00 | 01-JAN-00:10 | 13023.59 | 12-JUN-14:30 |
EnergyTransfer:Zone:SMSTORE7 | 71.83 | 0.00 | 01-JAN-00:10 | 13197.35 | 12-JUN-14:20 |
Heating:EnergyTransfer:Zone:SMSTORE7 | 0.70 | 0.00 | 01-JAN-00:10 | 8610.61 | 02-JAN-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE7 | 0.70 | 0.00 | 01-JAN-00:10 | 8610.61 | 02-JAN-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE7 | 71.13 | 0.00 | 01-JAN-00:10 | 13197.35 | 12-JUN-14:20 |
General:Cooling:EnergyTransfer:Zone:SMSTORE7 | 71.13 | 0.00 | 01-JAN-00:10 | 13197.35 | 12-JUN-14:20 |
EnergyTransfer:Zone:SMSTORE8 | 85.33 | 0.00 | 01-JAN-00:10 | 16117.63 | 12-JUN-12:20 |
Heating:EnergyTransfer:Zone:SMSTORE8 | 0.93 | 0.00 | 01-JAN-00:10 | 11908.10 | 02-JAN-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE8 | 0.93 | 0.00 | 01-JAN-00:10 | 11908.10 | 02-JAN-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE8 | 84.41 | 0.00 | 01-JAN-00:10 | 16117.63 | 12-JUN-12:20 |
General:Cooling:EnergyTransfer:Zone:SMSTORE8 | 84.41 | 0.00 | 01-JAN-00:10 | 16117.63 | 12-JUN-12:20 |
EnergyTransfer:HVAC | 1870.47 | 0.00 | 01-JAN-00:10 | 321019.11 | 01-JUL-16:00 |
HeatingCoils:EnergyTransfer | 6.69 | 0.00 | 01-JAN-00:10 | 99551.33 | 02-JAN-08:10 |
CoolingCoils:EnergyTransfer | 1863.78 | 0.00 | 01-JAN-00:10 | 321019.11 | 01-JUL-16:00 |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:19
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
LGSTORE1 | 0.000 | 0.000 | 0.333 | -203.832 | 0.000 | 0.000 | 23.359 | 87.116 | 26.249 | 20.612 | 0.000 | 25.291 | 30.162 | 0.000 | -4.384 | 0.000 | -4.905 | -0.001 |
SMSTORE1 | 0.000 | 0.000 | 0.110 | -106.020 | 0.000 | 0.000 | 11.639 | 53.201 | 13.125 | 10.337 | 0.000 | 14.231 | 8.379 | 0.000 | -2.261 | 0.000 | -2.740 | -0.002 |
SMSTORE2 | 0.000 | 0.000 | 1.292 | -82.453 | 0.000 | 0.000 | 7.004 | 37.572 | 10.421 | 10.170 | 0.000 | 14.032 | 7.024 | 0.000 | -2.314 | 0.000 | -2.748 | -0.001 |
SMSTORE3 | 0.000 | 0.000 | 1.297 | -82.533 | 0.000 | 0.000 | 7.008 | 37.572 | 10.421 | 10.163 | 0.000 | 14.028 | 7.076 | 0.000 | -2.303 | 0.000 | -2.728 | -0.001 |
SMSTORE4 | 0.000 | 0.000 | 1.339 | -80.404 | 0.000 | 0.000 | 7.014 | 37.572 | 10.421 | 10.186 | 0.000 | 14.033 | 4.799 | 0.000 | -2.267 | 0.000 | -2.691 | -0.000 |
LGSTORE2 | 0.000 | 0.000 | 1.196 | -137.730 | 0.000 | 0.000 | 24.096 | 37.162 | 19.173 | 20.444 | 0.000 | 24.627 | 20.035 | 0.000 | -4.356 | 0.000 | -4.648 | -0.001 |
SMSTORE5 | 0.000 | 0.000 | 0.625 | -71.710 | 0.000 | 0.000 | 12.052 | 19.120 | 9.586 | 10.254 | 0.000 | 14.047 | 10.800 | 0.000 | -2.159 | 0.000 | -2.615 | -0.000 |
SMSTORE6 | 0.000 | 0.000 | 0.644 | -71.201 | 0.000 | 0.000 | 12.056 | 19.120 | 9.586 | 10.262 | 0.000 | 14.048 | 10.235 | 0.000 | -2.149 | 0.000 | -2.602 | -0.000 |
SMSTORE7 | 0.000 | 0.000 | 0.703 | -71.126 | 0.000 | 0.000 | 12.065 | 19.120 | 9.586 | 10.258 | 0.000 | 14.046 | 10.044 | 0.000 | -2.129 | 0.000 | -2.569 | -0.000 |
SMSTORE8 | 0.000 | 0.000 | 0.926 | -84.406 | 0.000 | 0.000 | 12.067 | 19.120 | 9.586 | 10.137 | 0.000 | 14.376 | 23.049 | 0.000 | -2.076 | 0.000 | -2.780 | -0.000 |
Total Facility | 0.000 | 0.000 | 8.464 | -991.417 | 0.000 | 0.000 | 128.360 | 366.677 | 128.154 | 122.822 | 0.000 | 162.758 | 131.604 | 0.000 | -26.398 | 0.000 | -31.025 | -0.006 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
LGSTORE1 | 06-MAY-07:01 | 0.00 | 0.00 | 0.00 | -54544.07 | 0.00 | 0.00 | 0.00 | 75.00 | 73.64 | 336.92 | 0.00 | 303.55 | 53754.96 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 06-MAY-07:01 | 0.00 | 0.00 | 0.00 | -27802.13 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 171.66 | 0.00 | 171.51 | 27384.64 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 06-MAY-06:01 | 0.00 | 0.00 | 0.00 | -28267.03 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 42.81 | 0.00 | 4.44 | 28145.46 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 06-MAY-06:01 | 0.00 | 0.00 | 0.00 | -28370.07 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 40.33 | 0.00 | 4.31 | 28251.11 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 06-MAY-06:01 | 0.00 | 0.00 | 0.00 | -28158.56 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 42.71 | 0.00 | 4.49 | 28037.05 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 29-MAY-08:61 | 0.00 | 0.00 | 0.00 | -50595.91 | 0.00 | 0.00 | 0.00 | 75.00 | 73.64 | 617.03 | 0.00 | 419.80 | 49410.43 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 29-MAY-08:61 | 0.00 | 0.00 | 0.00 | -26476.91 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 310.99 | 0.00 | 237.02 | 25854.59 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 29-MAY-08:61 | 0.00 | 0.00 | 0.00 | -26411.95 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 310.99 | 0.00 | 236.88 | 25789.76 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 29-MAY-08:61 | 0.00 | 0.00 | 0.00 | -26534.16 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 309.19 | 0.00 | 235.41 | 25915.25 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 29-MAY-08:61 | 0.00 | 0.00 | 0.00 | -30424.36 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 293.57 | 0.00 | 268.02 | 29788.45 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 06-MAY-07:01 | 0.00 | 0.00 | 0.00 | -254284.46 | 0.00 | 0.00 | 295.51 | 450.00 | 1450.75 | 2102.32 | 0.00 | 2130.95 | 247854.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
LGSTORE1 | 02-JAN-08:61 | 0.00 | 0.00 | 63666.95 | 0.00 | 0.00 | 0.00 | 247.02 | 75.00 | 74.62 | 67.30 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -923.93 | -63206.96 |
SMSTORE1 | 02-JAN-08:61 | 0.00 | 0.00 | 13789.62 | 0.00 | 0.00 | 0.00 | 117.93 | 37.50 | 37.31 | 11.25 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -547.74 | -13445.87 |
SMSTORE2 | 01-JAN-08:62 | 0.00 | 0.00 | 25711.86 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 37.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -15.72 | 0.00 | -511.42 | -25259.54 |
SMSTORE3 | 01-JAN-08:62 | 0.00 | 0.00 | 31898.09 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 37.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -5.38 | 0.00 | -505.22 | -31462.30 |
SMSTORE4 | 01-JAN-08:62 | 0.00 | 0.00 | 31801.47 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 37.31 | 1.71 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -491.64 | -31386.36 |
LGSTORE2 | 01-JAN-09:01 | 0.00 | 0.00 | 59218.77 | 0.00 | 0.00 | 0.00 | 0.00 | 75.00 | 73.64 | 619.38 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -705.89 | -59280.89 |
SMSTORE5 | 01-JAN-09:01 | 0.00 | 0.00 | 31239.16 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 310.43 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -402.76 | -31221.14 |
SMSTORE6 | 01-JAN-09:01 | 0.00 | 0.00 | 31159.90 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 312.03 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -399.92 | -31146.33 |
SMSTORE7 | 01-JAN-09:01 | 0.00 | 0.00 | 31371.33 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 317.69 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -389.43 | -31373.92 |
SMSTORE8 | 01-JAN-09:01 | 0.00 | 0.00 | 36307.61 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 335.48 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -366.67 | -36350.75 |
Total Facility | 02-JAN-08:61 | 0.00 | 0.00 | 270392.68 | 0.00 | 0.00 | 0.00 | 711.76 | 450.00 | 1452.23 | 536.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -5826.08 | -267716.64 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:19
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 2.8094 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 2.8094 | 0.1465 | 1.0000 | Not calculated | 0.4115 | 0.1465 | ||
PSZ-AC_2:2 | 1.4376 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.4376 | 0.1431 | 1.0000 | Not calculated | 0.2057 | 0.1431 | ||
PSZ-AC_3:3 | 1.4375 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.4375 | 0.1431 | 1.0000 | Not calculated | 0.2057 | 0.1431 | ||
PSZ-AC_4:4 | 1.4407 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.4407 | 0.1428 | 1.0000 | Not calculated | 0.2057 | 0.1428 | ||
PSZ-AC_5:5 | 1.4319 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.4319 | 0.1437 | 1.0000 | Not calculated | 0.2057 | 0.1437 | ||
PSZ-AC_6:6 | 2.5345 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 2.5345 | 0.1623 | 1.0000 | Not calculated | 0.4115 | 0.1623 | ||
PSZ-AC_7:7 | 1.3407 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.3407 | 0.1535 | 1.0000 | Not calculated | 0.2057 | 0.1535 | ||
PSZ-AC_8:8 | 1.3362 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.3362 | 0.1540 | 1.0000 | Not calculated | 0.2057 | 0.1540 | ||
PSZ-AC_9:9 | 1.3432 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.3432 | 0.1532 | 1.0000 | Not calculated | 0.2057 | 0.1532 | ||
PSZ-AC_10:10 | 1.5703 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.5703 | 0.1310 | 1.0000 | Not calculated | 0.2057 | 0.1310 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 2.8094 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 2.8094 | 1.0000 | 1.0000 | Not calculated | 0.4115 | 0.1465 | ||
PSZ-AC_2:2 | 1.4376 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.4376 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1431 | ||
PSZ-AC_3:3 | 1.4375 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.4375 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1431 | ||
PSZ-AC_4:4 | 1.4407 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.4407 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1428 | ||
PSZ-AC_5:5 | 1.4319 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.4319 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1437 | ||
PSZ-AC_6:6 | 2.5345 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 2.5345 | 1.0000 | 1.0000 | Not calculated | 0.4115 | 0.1623 | ||
PSZ-AC_7:7 | 1.3407 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.3407 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1535 | ||
PSZ-AC_8:8 | 1.3362 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.3362 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1540 | ||
PSZ-AC_9:9 | 1.3432 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.3432 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1532 | ||
PSZ-AC_10:10 | 1.5703 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.5703 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1310 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
LGSTORE1 | PSZ-AC_1:1 | 0.000000 | 56.2505 | 0.001181 | 348.39 | 0.4115 | 1.0000 | 0.4115 | 1.000 | 0.4115 |
SMSTORE1 | PSZ-AC_2:2 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE2 | PSZ-AC_3:3 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE3 | PSZ-AC_4:4 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE4 | PSZ-AC_5:5 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
LGSTORE2 | PSZ-AC_6:6 | 0.000000 | 56.2505 | 0.001181 | 348.39 | 0.4115 | 1.0000 | 0.4115 | 1.000 | 0.4115 |
SMSTORE5 | PSZ-AC_7:7 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE6 | PSZ-AC_8:8 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE7 | PSZ-AC_9:9 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE8 | PSZ-AC_10:10 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC_1:1 | 0.000000 | 56.25 | 0.001181 | 348.3864 | 0.4115 | 0.4115 | 0.4115 |
PSZ-AC_2:2 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_3:3 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_4:4 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_5:5 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_6:6 | 0.000000 | 56.25 | 0.001181 | 348.3864 | 0.4115 | 0.4115 | 0.4115 |
PSZ-AC_7:7 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_8:8 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_9:9 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_10:10 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LGSTORE1 | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.8094 | 2.8094 | 2.8094 | No | 0.4115 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE1 | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.4376 | 1.4376 | 1.4376 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE2 | PSZ-AC_3:3 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.4375 | 1.4375 | 1.4375 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE3 | PSZ-AC_4:4 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.4407 | 1.4407 | 1.4407 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE4 | PSZ-AC_5:5 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.4319 | 1.4319 | 1.4319 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LGSTORE2 | PSZ-AC_6:6 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.5345 | 2.5345 | 2.5345 | No | 0.4115 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE5 | PSZ-AC_7:7 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.3407 | 1.3407 | 1.3407 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE6 | PSZ-AC_8:8 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.3362 | 1.3362 | 1.3362 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE7 | PSZ-AC_9:9 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.3432 | 1.3432 | 1.3432 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE8 | PSZ-AC_10:10 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.5703 | 1.5703 | 1.5703 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 2.8094 | 2.8094 | 2.8094 | 2.8094 | 0.4115 | 1.0000 |
PSZ-AC_2:2 | 1.4376 | 1.4376 | 1.4376 | 1.4376 | 0.2057 | 1.0000 |
PSZ-AC_3:3 | 1.4375 | 1.4375 | 1.4375 | 1.4375 | 0.2057 | 1.0000 |
PSZ-AC_4:4 | 1.4407 | 1.4407 | 1.4407 | 1.4407 | 0.2057 | 1.0000 |
PSZ-AC_5:5 | 1.4319 | 1.4319 | 1.4319 | 1.4319 | 0.2057 | 1.0000 |
PSZ-AC_6:6 | 2.5345 | 2.5345 | 2.5345 | 2.5345 | 0.4115 | 1.0000 |
PSZ-AC_7:7 | 1.3407 | 1.3407 | 1.3407 | 1.3407 | 0.2057 | 1.0000 |
PSZ-AC_8:8 | 1.3362 | 1.3362 | 1.3362 | 1.3362 | 0.2057 | 1.0000 |
PSZ-AC_9:9 | 1.3432 | 1.3432 | 1.3432 | 1.3432 | 0.2057 | 1.0000 |
PSZ-AC_10:10 | 1.5703 | 1.5703 | 1.5703 | 1.5703 | 0.2057 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LGSTORE1 | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.8094 | 2.8094 | 2.8094 | No | 0.4115 | 0.5091 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE1 | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.4376 | 1.4376 | 1.4376 | No | 0.2057 | 0.5175 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE2 | PSZ-AC_3:3 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.4375 | 1.4375 | 1.4375 | No | 0.2057 | 0.5130 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE3 | PSZ-AC_4:4 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.4407 | 1.4407 | 1.4407 | No | 0.2057 | 0.5083 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE4 | PSZ-AC_5:5 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.4319 | 1.4319 | 1.4319 | No | 0.2057 | 0.4986 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LGSTORE2 | PSZ-AC_6:6 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.5345 | 2.5345 | 2.5345 | No | 0.4115 | 0.5258 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE5 | PSZ-AC_7:7 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.3407 | 1.3407 | 1.3407 | No | 0.2057 | 0.4853 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE6 | PSZ-AC_8:8 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.3362 | 1.3362 | 1.3362 | No | 0.2057 | 0.4851 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE7 | PSZ-AC_9:9 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.3432 | 1.3432 | 1.3432 | No | 0.2057 | 0.4703 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE8 | PSZ-AC_10:10 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.5703 | 1.5703 | 1.5703 | No | 0.2057 | 0.3976 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 2.8094 | 2.8094 | 2.8094 | 2.8094 | 0.4115 | 1.0000 |
PSZ-AC_2:2 | 1.4376 | 1.4376 | 1.4376 | 1.4376 | 0.2057 | 1.0000 |
PSZ-AC_3:3 | 1.4375 | 1.4375 | 1.4375 | 1.4375 | 0.2057 | 1.0000 |
PSZ-AC_4:4 | 1.4407 | 1.4407 | 1.4407 | 1.4407 | 0.2057 | 1.0000 |
PSZ-AC_5:5 | 1.4319 | 1.4319 | 1.4319 | 1.4319 | 0.2057 | 1.0000 |
PSZ-AC_6:6 | 2.5345 | 2.5345 | 2.5345 | 2.5345 | 0.4115 | 1.0000 |
PSZ-AC_7:7 | 1.3407 | 1.3407 | 1.3407 | 1.3407 | 0.2057 | 1.0000 |
PSZ-AC_8:8 | 1.3362 | 1.3362 | 1.3362 | 1.3362 | 0.2057 | 1.0000 |
PSZ-AC_9:9 | 1.3432 | 1.3432 | 1.3432 | 1.3432 | 0.2057 | 1.0000 |
PSZ-AC_10:10 | 1.5703 | 1.5703 | 1.5703 | 1.5703 | 0.2057 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:19
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820 |
Total gross floor area [m2] | 2090.32 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
LGSTORE1 | 348.39 | 348.39 | 0.00 | 112.00 |
SMSTORE1 | 174.19 | 174.19 | 0.00 | 112.00 |
SMSTORE2 | 174.19 | 174.19 | 0.00 | 84.29 |
SMSTORE3 | 174.19 | 174.19 | 0.00 | 84.29 |
SMSTORE4 | 174.19 | 174.19 | 0.00 | 84.29 |
LGSTORE2 | 348.39 | 348.39 | 0.00 | 77.29 |
SMSTORE5 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE6 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE7 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE8 | 174.19 | 174.19 | 0.00 | 77.29 |
Totals | 2090.32 | 2090.32 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 1.17 |
Number of hours not met | 1.17 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 8.36 | 124439.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 494.57 | 85981.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 366.68 | 23459.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 60.04 | 5507.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 128.15 | 8059.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 131.92 | 13439.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 58.66 | 9745.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 128.15 | 1240.02 |
Natural Gas | 0.00 | 8.36 |
Additional | 0.00 | 0.00 |
Total | 128.15 | 1248.39 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 175.42 |
Space Heating | 0.00 |
Space Cooling | 236.60 |
Fans (All) | 63.11 |
Service Water Heating | 28.06 |
Receptacle Equipment | 61.31 |
Miscellaneous (All) | 593.22 |
Subtotal | 593.22 |
Natural Gas [MJ/m2] | |
Space Heating | 4.00 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 4.00 |
Subtotal | 4.00 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 29.37 |
Space Heating | 0.67 |
Space Cooling | 39.62 |
Fans (All) | 10.57 |
Service Water Heating | 4.70 |
Receptacle Equipment | 10.27 |
Miscellaneous | 4.81 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
TYPE1_OCC_SCH | 1630. | 5840. |
TYPE2_OCC_SCH | 995. | 4429. |
TYPE3_OCC_SCH | 1709. | 4064. |
LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 3767. | 8760. |
LTG_SCH_BASE_LPD2 | 3238. | 8760. |
LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 3296. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | 5084. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | 5084. | 8760. |
LTG_SCH_BASE_SMALL_LPD1 | 4453. | 8760. |
LTG_SCH_BASE_LPD1 | 4376. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | 3767. | 8760. |
LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 3584. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 4096. | 8760. |
TYPE1_EQUIP_SCH | 4868. | 8760. |
TYPE2_EQUIP_SCH | 3893. | 8760. |
TYPE3_EQUIP_SCH | 3584. | 8760. |
TYPE1_INFIL_SCH | 4302. | 8760. |
TYPE2_INFIL_SCH | 5164. | 8760. |
TYPE3_INFIL_SCH | 5438. | 8760. |
INFIL_DOOR_OPENING_SCH | 2505. | 4380. |
TYPE1_MINOA_MOTORIZEDDAMPER_SCH | 5579. | 5579. |
TYPE2_MINOA_MOTORIZEDDAMPER_SCH | 4429. | 4429. |
TYPE3_MINOA_MOTORIZEDDAMPER_SCH | 4064. | 4064. |
TYPE1_SWH_SCH | 2063. | 6048. |
TYPE2_SWH_SCH | 1831. | 4429. |
TYPE3_SWH_SCH | 1733. | 4064. |
AVERAGE_SWH_SCH | 1863. | 6152. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 7118. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 5839. | 5839. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 7300. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6570. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
TYPE1_HTGSETP_SCH_NO_OPTIMUM | LGSTORE1 DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
TYPE1_CLGSETP_SCH_NO_OPTIMUM | LGSTORE1 DUAL SP CONTROL | July | 23.89 | 365 | 23.89 | 365 |
TYPE2_HTGSETP_SCH_NO_OPTIMUM | SMSTORE2 DUAL SP CONTROL | January | 21.11 | 365 | 15.56 | 365 |
TYPE2_CLGSETP_SCH_NO_OPTIMUM | SMSTORE2 DUAL SP CONTROL | July | 23.89 | 365 | 29.44 | 365 |
TYPE3_HTGSETP_SCH_NO_OPTIMUM | LGSTORE2 DUAL SP CONTROL | January | 21.11 | 365 | 15.56 | 365 |
TYPE3_CLGSETP_SCH_NO_OPTIMUM | LGSTORE2 DUAL SP CONTROL | July | 23.89 | 365 | 29.44 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:19
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
LGSTORE1 | 8339.17 | 420.83 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 8580.83 | 179.17 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 7121.67 | 1633.83 | 4.50 | 0.00 | 0.00 |
SMSTORE3 | 7052.83 | 1699.33 | 7.83 | 0.00 | 0.00 |
SMSTORE4 | 7172.17 | 1580.67 | 7.17 | 0.00 | 0.00 |
LGSTORE2 | 7715.33 | 1040.17 | 4.50 | 0.00 | 0.00 |
SMSTORE5 | 7830.00 | 924.83 | 5.17 | 0.00 | 0.00 |
SMSTORE6 | 7844.67 | 910.17 | 5.17 | 0.00 | 0.00 |
SMSTORE7 | 7828.33 | 924.50 | 7.17 | 0.00 | 0.00 |
SMSTORE8 | 7434.00 | 1293.17 | 32.83 | 0.00 | 0.00 |
Min | 7052.83 | 179.17 | 0.00 | 0.00 | 0.00 |
Max | 8580.83 | 1699.33 | 32.83 | 0.00 | 0.00 |
Average | 7691.90 | 1060.67 | 7.43 | 0.00 | 0.00 |
Sum | 76919.00 | 10606.67 | 74.33 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
LGSTORE1 | 89041.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 43777.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 25345.17 | 128.67 | 1.17 | 0.00 | 0.00 |
SMSTORE3 | 25345.00 | 128.83 | 1.17 | 0.00 | 0.00 |
SMSTORE4 | 25347.83 | 126.00 | 1.17 | 0.00 | 0.00 |
LGSTORE2 | 92925.00 | 280.00 | 6.00 | 0.00 | 0.00 |
SMSTORE5 | 45769.00 | 139.50 | 3.50 | 0.00 | 0.00 |
SMSTORE6 | 45770.00 | 138.50 | 3.50 | 0.00 | 0.00 |
SMSTORE7 | 45770.00 | 138.50 | 3.50 | 0.00 | 0.00 |
SMSTORE8 | 45755.00 | 152.50 | 4.50 | 0.00 | 0.00 |
Min | 25345.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 92925.00 | 280.00 | 6.00 | 0.00 | 0.00 |
Average | 48484.50 | 123.25 | 2.45 | 0.00 | 0.00 |
Sum | 484845.00 | 1232.50 | 24.50 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
LGSTORE1 | 6604.33 | 2155.67 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 7359.67 | 1400.33 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 5823.17 | 2931.83 | 5.00 | 0.00 | 0.00 |
SMSTORE3 | 5818.33 | 2928.33 | 13.33 | 0.00 | 0.00 |
SMSTORE4 | 5828.67 | 2918.00 | 13.33 | 0.00 | 0.00 |
LGSTORE2 | 5936.33 | 2819.50 | 4.17 | 0.00 | 0.00 |
SMSTORE5 | 5946.33 | 2799.33 | 14.33 | 0.00 | 0.00 |
SMSTORE6 | 5947.50 | 2798.17 | 14.33 | 0.00 | 0.00 |
SMSTORE7 | 5965.67 | 2780.00 | 14.33 | 0.00 | 0.00 |
SMSTORE8 | 6002.83 | 2739.83 | 17.33 | 0.00 | 0.00 |
Min | 5818.33 | 1400.33 | 0.00 | 0.00 | 0.00 |
Max | 7359.67 | 2931.83 | 17.33 | 0.00 | 0.00 |
Average | 6123.28 | 2627.10 | 9.62 | 0.00 | 0.00 |
Sum | 61232.83 | 26271.00 | 96.17 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
LGSTORE1 | 74617.00 | 14424.00 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 37345.33 | 6431.67 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 20407.33 | 5067.33 | 0.33 | 0.00 | 0.00 |
SMSTORE3 | 20441.67 | 5033.00 | 0.33 | 0.00 | 0.00 |
SMSTORE4 | 20369.17 | 5105.50 | 0.33 | 0.00 | 0.00 |
LGSTORE2 | 73313.17 | 19895.83 | 2.00 | 0.00 | 0.00 |
SMSTORE5 | 35925.83 | 9985.17 | 1.00 | 0.00 | 0.00 |
SMSTORE6 | 35892.83 | 10018.17 | 1.00 | 0.00 | 0.00 |
SMSTORE7 | 36014.33 | 9896.67 | 1.00 | 0.00 | 0.00 |
SMSTORE8 | 37145.67 | 8765.33 | 1.00 | 0.00 | 0.00 |
Min | 20369.17 | 5033.00 | 0.00 | 0.00 | 0.00 |
Max | 74617.00 | 19895.83 | 2.00 | 0.00 | 0.00 |
Average | 39147.23 | 9462.27 | 0.70 | 0.00 | 0.00 |
Sum | 391472.33 | 94622.67 | 7.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:19
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:19
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
For: Environment
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTRIPMALL
For: Environment
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 1B
For: Environment
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY IND_DELHI_NEWDELHI
For: Environment
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: ZoneCoolingSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.533534E+10 | 6864.43 | 03-JAN-08:02 | 6.40 | 5.71 | 0.133021E+10 | 1685.92 | 08-JAN-18:49 | 16.28 | 12.44 |
February | 0.736323E+10 | 11187.38 | 22-FEB-15:00 | 27.10 | 16.20 | 0.125310E+10 | 1685.97 | 20-FEB-18:00 | 27.10 | 16.20 |
March | 0.134304E+11 | 26714.43 | 11-MAR-08:62 | 24.43 | 17.41 | 0.139614E+10 | 1686.05 | 12-MAR-17:49 | 29.35 | 19.37 |
April | 0.200307E+11 | 53129.71 | 28-APR-07:02 | 29.48 | 17.52 | 0.136169E+10 | 1686.13 | 16-APR-12:00 | 29.48 | 17.52 |
May | 0.250898E+11 | 54543.85 | 06-MAY-07:01 | 30.00 | 17.75 | 0.140195E+10 | 1686.18 | 07-MAY-12:50 | 40.73 | 21.37 |
June | 0.251402E+11 | 50625.16 | 07-JUN-07:01 | 34.92 | 19.62 | 0.135493E+10 | 1686.18 | 04-JUN-12:50 | 34.92 | 19.62 |
July | 0.244407E+11 | 42420.90 | 07-JUL-07:01 | 33.33 | 24.39 | 0.141315E+10 | 1686.08 | 04-JUL-17:49 | 33.33 | 24.39 |
August | 0.232257E+11 | 40658.02 | 03-AUG-07:01 | 28.70 | 23.41 | 0.139442E+10 | 1686.03 | 20-AUG-17:19 | 26.57 | 25.60 |
September | 0.209612E+11 | 43463.13 | 26-SEP-07:01 | 25.87 | 19.87 | 0.136544E+10 | 1686.12 | 30-SEP-12:00 | 34.20 | 23.67 |
October | 0.192269E+11 | 46708.13 | 05-OCT-07:02 | 23.83 | 18.71 | 0.140968E+10 | 1686.06 | 09-OCT-17:00 | 29.40 | 20.50 |
November | 0.127002E+11 | 14693.84 | 08-NOV-15:00 | 29.90 | 18.01 | 0.136146E+10 | 1686.03 | 18-NOV-13:00 | 26.50 | 17.10 |
December | 0.688933E+10 | 8875.49 | 01-DEC-14:00 | 23.50 | 13.07 | 0.137605E+10 | 1685.93 | 03-DEC-13:09 | 24.08 | 14.17 |
Annual Sum or Average | 0.203834E+12 | 0.164182E+11 | ||||||||
Minimum of Months | 0.533534E+10 | 6864.43 | 6.40 | 5.71 | 0.125310E+10 | 1685.92 | 16.28 | 12.44 | ||
Maximum of Months | 0.251402E+11 | 54543.85 | 34.92 | 24.39 | 0.141315E+10 | 1686.18 | 40.73 | 25.60 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.282270E+10 | 4014.47 | 12-JAN-15:00 | 23.60 | 14.20 | 0.687209E+09 | 843.08 | 29-JAN-18:00 | 15.00 | 10.78 |
February | 0.427300E+10 | 6053.36 | 22-FEB-15:00 | 27.10 | 16.20 | 0.631904E+09 | 843.22 | 19-FEB-18:00 | 27.10 | 16.20 |
March | 0.747797E+10 | 16104.56 | 11-MAR-08:62 | 24.43 | 17.41 | 0.698437E+09 | 843.26 | 26-MAR-17:19 | 28.67 | 15.92 |
April | 0.104546E+11 | 27348.19 | 30-APR-07:02 | 24.20 | 14.19 | 0.680839E+09 | 843.14 | 30-APR-17:49 | 35.60 | 17.47 |
May | 0.128011E+11 | 27801.97 | 06-MAY-07:01 | 30.00 | 17.75 | 0.700955E+09 | 843.10 | 07-MAY-17:30 | 40.25 | 21.97 |
June | 0.126762E+11 | 26486.26 | 07-JUN-07:01 | 34.92 | 19.62 | 0.677435E+09 | 843.06 | 04-JUN-12:30 | 34.92 | 19.62 |
July | 0.123574E+11 | 24112.75 | 07-JUL-07:01 | 33.33 | 24.39 | 0.706541E+09 | 843.01 | 02-JUL-17:30 | 33.33 | 24.39 |
August | 0.117232E+11 | 23082.09 | 03-AUG-07:01 | 28.70 | 23.41 | 0.697174E+09 | 843.04 | 20-AUG-17:40 | 26.43 | 25.55 |
September | 0.106704E+11 | 24860.05 | 26-SEP-07:01 | 25.87 | 19.87 | 0.682697E+09 | 843.04 | 30-SEP-12:50 | 34.07 | 23.68 |
October | 0.100187E+11 | 26004.43 | 02-OCT-07:02 | 24.92 | 18.38 | 0.704840E+09 | 843.24 | 22-OCT-17:30 | 29.40 | 17.52 |
November | 0.694336E+10 | 8274.98 | 09-NOV-08:63 | 19.90 | 16.70 | 0.681134E+09 | 843.23 | 23-NOV-18:00 | 18.70 | 13.33 |
December | 0.380279E+10 | 5090.85 | 02-DEC-14:00 | 24.10 | 13.15 | 0.699929E+09 | 843.02 | 24-DEC-18:00 | 16.00 | 11.76 |
Annual Sum or Average | 0.106021E+12 | 0.824909E+10 | ||||||||
Minimum of Months | 0.282270E+10 | 4014.47 | 19.90 | 13.15 | 0.631904E+09 | 843.01 | 15.00 | 10.78 | ||
Maximum of Months | 0.128011E+11 | 27801.97 | 34.92 | 24.39 | 0.706541E+09 | 843.26 | 40.25 | 25.55 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.200877E+10 | 3576.99 | 12-JAN-15:00 | 23.60 | 14.20 | 0.400321E+09 | 842.94 | 07-JAN-13:00 | 23.60 | 14.20 |
February | 0.305038E+10 | 5734.69 | 22-FEB-14:00 | 27.00 | 16.33 | 0.375946E+09 | 842.91 | 18-FEB-13:09 | 27.00 | 16.33 |
March | 0.563856E+10 | 17635.18 | 30-MAR-06:03 | 21.25 | 16.72 | 0.431148E+09 | 842.97 | 11-MAR-13:09 | 21.25 | 16.72 |
April | 0.816015E+10 | 28213.10 | 20-APR-06:01 | 26.07 | 17.13 | 0.411712E+09 | 842.97 | 01-APR-12:09 | 26.07 | 17.13 |
May | 0.103284E+11 | 28266.52 | 06-MAY-06:01 | 29.38 | 17.57 | 0.427422E+09 | 842.99 | 27-MAY-12:50 | 40.70 | 20.30 |
June | 0.102550E+11 | 25548.86 | 12-JUN-06:01 | 34.87 | 19.39 | 0.418307E+09 | 842.90 | 17-JUN-12:09 | 37.17 | 26.31 |
July | 0.968855E+10 | 21170.60 | 01-JUL-06:01 | 29.62 | 23.95 | 0.421177E+09 | 842.92 | 22-JUL-12:09 | 31.25 | 26.91 |
August | 0.932921E+10 | 18542.44 | 03-AUG-06:01 | 28.43 | 23.36 | 0.432533E+09 | 842.90 | 26-AUG-12:09 | 32.65 | 28.45 |
September | 0.831407E+10 | 21392.79 | 27-SEP-06:02 | 23.70 | 20.40 | 0.411573E+09 | 843.04 | 30-SEP-12:39 | 33.93 | 23.68 |
October | 0.772453E+10 | 25208.11 | 02-OCT-06:01 | 22.92 | 17.86 | 0.420903E+09 | 842.99 | 14-OCT-12:09 | 30.13 | 20.41 |
November | 0.524442E+10 | 7736.74 | 04-NOV-13:00 | 30.10 | 17.26 | 0.405215E+09 | 842.99 | 18-NOV-13:39 | 26.47 | 17.14 |
December | 0.271334E+10 | 4903.21 | 02-DEC-14:00 | 24.10 | 13.15 | 0.409698E+09 | 842.93 | 09-DEC-13:00 | 19.70 | 12.78 |
Annual Sum or Average | 0.824553E+11 | 0.496595E+10 | ||||||||
Minimum of Months | 0.200877E+10 | 3576.99 | 21.25 | 13.15 | 0.375946E+09 | 842.90 | 19.70 | 12.78 | ||
Maximum of Months | 0.103284E+11 | 28266.52 | 34.87 | 23.95 | 0.432533E+09 | 843.04 | 40.70 | 28.45 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.185667E+10 | 3647.11 | 03-JAN-07:04 | 5.50 | 5.17 | 0.397994E+09 | 842.93 | 07-JAN-13:00 | 20.90 | 13.29 |
February | 0.294940E+10 | 5658.62 | 22-FEB-14:00 | 27.00 | 16.33 | 0.375558E+09 | 842.91 | 18-FEB-13:09 | 27.00 | 16.33 |
March | 0.561105E+10 | 17849.64 | 30-MAR-06:03 | 21.25 | 16.72 | 0.431114E+09 | 842.97 | 11-MAR-13:09 | 21.25 | 16.72 |
April | 0.820756E+10 | 28325.15 | 20-APR-06:01 | 26.07 | 17.13 | 0.411715E+09 | 842.97 | 01-APR-12:09 | 26.07 | 17.13 |
May | 0.104329E+11 | 28369.56 | 06-MAY-06:01 | 29.38 | 17.57 | 0.427429E+09 | 842.99 | 27-MAY-12:50 | 40.70 | 20.30 |
June | 0.103550E+11 | 25874.41 | 12-JUN-06:01 | 34.87 | 19.39 | 0.418315E+09 | 842.90 | 17-JUN-12:09 | 37.17 | 26.31 |
July | 0.979473E+10 | 21326.27 | 01-JUL-06:01 | 29.62 | 23.95 | 0.421185E+09 | 842.91 | 22-JUL-12:09 | 31.25 | 26.91 |
August | 0.940551E+10 | 18663.79 | 03-AUG-06:01 | 28.43 | 23.36 | 0.432539E+09 | 842.90 | 26-AUG-12:09 | 32.65 | 28.45 |
September | 0.837473E+10 | 21501.24 | 27-SEP-06:02 | 23.70 | 20.40 | 0.411577E+09 | 843.04 | 30-SEP-12:39 | 33.93 | 23.68 |
October | 0.776371E+10 | 25599.30 | 23-OCT-06:02 | 19.08 | 14.21 | 0.420904E+09 | 842.99 | 14-OCT-12:09 | 19.08 | 14.21 |
November | 0.519631E+10 | 7720.08 | 04-NOV-13:00 | 30.10 | 17.26 | 0.405160E+09 | 842.99 | 18-NOV-13:50 | 26.48 | 17.12 |
December | 0.258717E+10 | 4831.44 | 02-DEC-14:00 | 24.10 | 13.15 | 0.408940E+09 | 842.93 | 09-DEC-13:00 | 19.70 | 12.78 |
Annual Sum or Average | 0.825348E+11 | 0.496243E+10 | ||||||||
Minimum of Months | 0.185667E+10 | 3647.11 | 5.50 | 5.17 | 0.375558E+09 | 842.90 | 19.08 | 12.78 | ||
Maximum of Months | 0.104329E+11 | 28369.56 | 34.87 | 23.95 | 0.432539E+09 | 843.04 | 40.70 | 28.45 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.164305E+10 | 3806.29 | 03-JAN-07:04 | 5.50 | 5.17 | 0.394388E+09 | 842.93 | 07-JAN-13:00 | 20.90 | 13.29 |
February | 0.274181E+10 | 5473.07 | 22-FEB-14:00 | 27.00 | 16.33 | 0.374699E+09 | 842.91 | 18-FEB-13:09 | 27.00 | 16.33 |
March | 0.539614E+10 | 16330.20 | 30-MAR-06:03 | 21.25 | 16.72 | 0.430976E+09 | 842.97 | 11-MAR-13:09 | 21.25 | 16.72 |
April | 0.803180E+10 | 28015.82 | 20-APR-06:01 | 26.07 | 17.13 | 0.411682E+09 | 842.97 | 01-APR-12:09 | 26.07 | 17.13 |
May | 0.102834E+11 | 28158.06 | 06-MAY-06:01 | 29.38 | 17.57 | 0.427400E+09 | 842.99 | 27-MAY-12:50 | 40.70 | 20.30 |
June | 0.102092E+11 | 25699.60 | 12-JUN-06:01 | 34.87 | 19.39 | 0.418285E+09 | 842.90 | 17-JUN-12:09 | 37.17 | 26.31 |
July | 0.966134E+10 | 21033.28 | 01-JUL-06:01 | 29.62 | 23.95 | 0.421156E+09 | 843.01 | 22-JUL-12:09 | 31.25 | 26.91 |
August | 0.925332E+10 | 18382.41 | 03-AUG-06:01 | 28.43 | 23.36 | 0.432507E+09 | 842.90 | 26-AUG-12:09 | 32.65 | 28.45 |
September | 0.822422E+10 | 21252.55 | 27-SEP-06:02 | 23.70 | 20.40 | 0.411546E+09 | 843.04 | 30-SEP-12:50 | 34.07 | 23.68 |
October | 0.759244E+10 | 25199.62 | 02-OCT-06:01 | 22.92 | 17.86 | 0.420869E+09 | 842.99 | 14-OCT-12:09 | 30.13 | 20.41 |
November | 0.500219E+10 | 7555.94 | 04-NOV-13:00 | 30.10 | 17.26 | 0.405021E+09 | 842.99 | 18-NOV-13:00 | 26.50 | 17.10 |
December | 0.236748E+10 | 4645.45 | 02-DEC-14:00 | 24.10 | 13.15 | 0.407433E+09 | 842.92 | 09-DEC-13:00 | 19.70 | 12.78 |
Annual Sum or Average | 0.804064E+11 | 0.495596E+10 | ||||||||
Minimum of Months | 0.164305E+10 | 3806.29 | 5.50 | 5.17 | 0.374699E+09 | 842.90 | 19.70 | 12.78 | ||
Maximum of Months | 0.102834E+11 | 28158.06 | 34.87 | 23.95 | 0.432507E+09 | 843.04 | 40.70 | 28.45 |
Report: ZoneCoolingSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.256232E+10 | 7002.83 | 04-JAN-08:03 | 6.42 | 5.61 | 0.133476E+10 | 2247.81 | 28-JAN-15:50 | 18.23 | 11.45 |
February | 0.431133E+10 | 9753.02 | 22-FEB-15:10 | 27.00 | 16.16 | 0.128163E+10 | 2247.85 | 18-FEB-15:00 | 27.00 | 16.16 |
March | 0.906684E+10 | 24856.09 | 11-MAR-08:62 | 24.43 | 17.41 | 0.147838E+10 | 2248.02 | 11-MAR-15:00 | 30.20 | 19.50 |
April | 0.138579E+11 | 49262.49 | 20-APR-07:02 | 26.55 | 16.63 | 0.141146E+10 | 2248.04 | 15-APR-14:20 | 26.55 | 16.63 |
May | 0.179161E+11 | 50594.15 | 29-MAY-08:61 | 32.12 | 19.78 | 0.146001E+10 | 2248.16 | 27-MAY-14:20 | 32.12 | 19.78 |
June | 0.178287E+11 | 46099.07 | 07-JUN-07:01 | 34.92 | 19.62 | 0.143147E+10 | 2247.81 | 17-JUN-14:09 | 38.42 | 25.70 |
July | 0.167954E+11 | 39789.92 | 07-JUL-07:01 | 33.33 | 24.39 | 0.144035E+10 | 2247.81 | 29-JUL-14:09 | 32.40 | 26.64 |
August | 0.161067E+11 | 36291.93 | 08-AUG-07:01 | 30.50 | 24.42 | 0.148118E+10 | 2248.04 | 19-AUG-14:20 | 27.83 | 26.32 |
September | 0.141917E+11 | 40127.48 | 27-SEP-07:02 | 24.98 | 20.39 | 0.141118E+10 | 2247.81 | 02-SEP-14:09 | 24.98 | 20.39 |
October | 0.131269E+11 | 44265.26 | 02-OCT-07:02 | 24.92 | 18.38 | 0.143652E+10 | 2247.99 | 28-OCT-14:00 | 29.30 | 18.44 |
November | 0.829351E+10 | 13753.78 | 04-NOV-14:20 | 30.27 | 17.30 | 0.138038E+10 | 2247.91 | 04-NOV-14:00 | 30.20 | 17.55 |
December | 0.367515E+10 | 7894.86 | 02-DEC-14:30 | 24.00 | 13.17 | 0.139126E+10 | 2247.87 | 09-DEC-15:50 | 18.98 | 13.15 |
Annual Sum or Average | 0.137733E+12 | 0.169386E+11 | ||||||||
Minimum of Months | 0.256232E+10 | 7002.83 | 6.42 | 5.61 | 0.128163E+10 | 2247.81 | 18.23 | 11.45 | ||
Maximum of Months | 0.179161E+11 | 50594.15 | 34.92 | 24.42 | 0.148118E+10 | 2248.16 | 38.42 | 26.64 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.118017E+10 | 3510.94 | 04-JAN-08:03 | 6.42 | 5.61 | 0.664566E+09 | 1123.87 | 14-JAN-15:20 | 21.57 | 15.20 |
February | 0.213555E+10 | 5092.90 | 22-FEB-15:10 | 27.00 | 16.16 | 0.640265E+09 | 1123.89 | 18-FEB-15:00 | 27.00 | 16.16 |
March | 0.468755E+10 | 11842.67 | 11-MAR-08:62 | 24.43 | 17.41 | 0.739163E+09 | 1123.98 | 11-MAR-15:00 | 30.20 | 19.50 |
April | 0.727983E+10 | 25806.99 | 20-APR-07:02 | 26.55 | 16.63 | 0.705688E+09 | 1124.00 | 15-APR-14:20 | 26.55 | 16.63 |
May | 0.945583E+10 | 26476.01 | 29-MAY-08:61 | 32.12 | 19.78 | 0.729963E+09 | 1124.09 | 06-MAY-14:00 | 32.12 | 19.78 |
June | 0.938798E+10 | 24127.13 | 07-JUN-07:01 | 34.92 | 19.62 | 0.715693E+09 | 1123.87 | 17-JUN-14:09 | 38.42 | 25.70 |
July | 0.882345E+10 | 20847.23 | 07-JUL-07:01 | 33.33 | 24.39 | 0.720128E+09 | 1123.87 | 29-JUL-14:20 | 32.50 | 26.60 |
August | 0.843597E+10 | 19013.36 | 08-AUG-07:01 | 30.50 | 24.42 | 0.740555E+09 | 1123.98 | 19-AUG-14:20 | 27.83 | 26.32 |
September | 0.743386E+10 | 20974.69 | 27-SEP-07:02 | 24.98 | 20.39 | 0.705553E+09 | 1123.87 | 02-SEP-14:09 | 24.98 | 20.39 |
October | 0.685671E+10 | 23108.85 | 02-OCT-07:02 | 24.92 | 18.38 | 0.718224E+09 | 1123.96 | 28-OCT-14:00 | 29.30 | 18.44 |
November | 0.427115E+10 | 7243.05 | 04-NOV-14:20 | 30.27 | 17.30 | 0.690185E+09 | 1123.92 | 04-NOV-14:00 | 30.20 | 17.55 |
December | 0.176358E+10 | 4066.29 | 02-DEC-14:30 | 24.00 | 13.17 | 0.694410E+09 | 1123.90 | 09-DEC-15:39 | 19.17 | 13.14 |
Annual Sum or Average | 0.717116E+11 | 0.846439E+10 | ||||||||
Minimum of Months | 0.118017E+10 | 3510.94 | 6.42 | 5.61 | 0.640265E+09 | 1123.87 | 19.17 | 13.14 | ||
Maximum of Months | 0.945583E+10 | 26476.01 | 34.92 | 24.42 | 0.740555E+09 | 1124.09 | 38.42 | 26.60 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.114259E+10 | 3495.01 | 04-JAN-08:03 | 6.42 | 5.61 | 0.662644E+09 | 1123.87 | 14-JAN-15:20 | 21.57 | 15.20 |
February | 0.208191E+10 | 5035.00 | 22-FEB-15:10 | 27.00 | 16.16 | 0.639693E+09 | 1123.89 | 18-FEB-15:00 | 27.00 | 16.16 |
March | 0.462805E+10 | 11436.43 | 11-MAR-08:62 | 24.43 | 17.41 | 0.739104E+09 | 1123.98 | 11-MAR-15:00 | 30.20 | 19.50 |
April | 0.723475E+10 | 25733.14 | 20-APR-07:02 | 26.55 | 16.63 | 0.705683E+09 | 1123.99 | 15-APR-14:30 | 26.55 | 16.63 |
May | 0.941789E+10 | 26411.05 | 29-MAY-08:61 | 32.12 | 19.78 | 0.729959E+09 | 1124.09 | 06-MAY-14:00 | 32.12 | 19.78 |
June | 0.934999E+10 | 24066.66 | 07-JUN-07:01 | 34.92 | 19.62 | 0.715690E+09 | 1123.87 | 17-JUN-14:09 | 38.42 | 25.70 |
July | 0.879171E+10 | 20786.38 | 07-JUL-07:01 | 33.33 | 24.39 | 0.720123E+09 | 1123.87 | 29-JUL-14:09 | 32.40 | 26.64 |
August | 0.840245E+10 | 18959.14 | 08-AUG-07:01 | 30.50 | 24.42 | 0.740551E+09 | 1123.98 | 19-AUG-14:20 | 27.83 | 26.32 |
September | 0.740068E+10 | 20905.74 | 27-SEP-07:02 | 24.98 | 20.39 | 0.705549E+09 | 1123.87 | 02-SEP-14:09 | 24.98 | 20.39 |
October | 0.681601E+10 | 23055.84 | 02-OCT-07:02 | 24.92 | 18.38 | 0.718218E+09 | 1123.96 | 28-OCT-14:00 | 29.30 | 18.44 |
November | 0.422039E+10 | 7197.07 | 04-NOV-14:20 | 30.27 | 17.30 | 0.690139E+09 | 1123.92 | 04-NOV-14:00 | 30.20 | 17.55 |
December | 0.171526E+10 | 4012.67 | 02-DEC-14:30 | 24.00 | 13.17 | 0.693235E+09 | 1123.90 | 09-DEC-15:30 | 19.35 | 13.13 |
Annual Sum or Average | 0.712017E+11 | 0.846059E+10 | ||||||||
Minimum of Months | 0.114259E+10 | 3495.01 | 6.42 | 5.61 | 0.639693E+09 | 1123.87 | 19.35 | 13.13 | ||
Maximum of Months | 0.941789E+10 | 26411.05 | 34.92 | 24.42 | 0.740551E+09 | 1124.09 | 38.42 | 26.64 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.104594E+10 | 3517.22 | 05-JAN-08:03 | 6.10 | 5.59 | 0.658267E+09 | 1123.89 | 07-JAN-15:00 | 19.90 | 13.23 |
February | 0.194463E+10 | 4924.70 | 22-FEB-15:10 | 27.00 | 16.16 | 0.638026E+09 | 1123.89 | 18-FEB-15:00 | 27.00 | 16.16 |
March | 0.450660E+10 | 10145.72 | 30-MAR-07:03 | 21.65 | 17.03 | 0.738887E+09 | 1123.98 | 11-MAR-15:00 | 21.65 | 17.03 |
April | 0.723652E+10 | 25755.86 | 20-APR-07:02 | 26.55 | 16.63 | 0.705682E+09 | 1123.99 | 15-APR-14:30 | 26.55 | 16.63 |
May | 0.950459E+10 | 26533.25 | 29-MAY-08:61 | 32.12 | 19.78 | 0.729965E+09 | 1124.07 | 06-MAY-14:00 | 32.12 | 19.78 |
June | 0.945054E+10 | 24224.10 | 07-JUN-07:01 | 34.92 | 19.62 | 0.715695E+09 | 1123.87 | 17-JUN-14:09 | 38.42 | 25.70 |
July | 0.890751E+10 | 20971.86 | 07-JUL-07:01 | 33.33 | 24.39 | 0.720134E+09 | 1123.87 | 29-JUL-14:09 | 32.40 | 26.64 |
August | 0.850989E+10 | 19153.89 | 08-AUG-07:01 | 30.50 | 24.42 | 0.740559E+09 | 1123.98 | 19-AUG-14:20 | 27.83 | 26.32 |
September | 0.747401E+10 | 21012.56 | 27-SEP-07:02 | 24.98 | 20.39 | 0.705555E+09 | 1123.87 | 02-SEP-14:09 | 24.98 | 20.39 |
October | 0.683055E+10 | 23158.61 | 02-OCT-07:02 | 24.92 | 18.38 | 0.718215E+09 | 1123.96 | 28-OCT-14:00 | 29.30 | 18.44 |
November | 0.412592E+10 | 7156.35 | 04-NOV-14:20 | 30.27 | 17.30 | 0.689978E+09 | 1123.92 | 04-NOV-14:00 | 30.20 | 17.55 |
December | 0.159076E+10 | 3875.63 | 02-DEC-14:30 | 24.00 | 13.17 | 0.690271E+09 | 1123.90 | 09-DEC-15:09 | 19.72 | 13.10 |
Annual Sum or Average | 0.711275E+11 | 0.845123E+10 | ||||||||
Minimum of Months | 0.104594E+10 | 3517.22 | 6.10 | 5.59 | 0.638026E+09 | 1123.87 | 19.72 | 13.10 | ||
Maximum of Months | 0.950459E+10 | 26533.25 | 34.92 | 24.42 | 0.740559E+09 | 1124.07 | 38.42 | 26.64 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.956322E+09 | 3674.83 | 05-JAN-08:03 | 6.10 | 5.59 | 0.658801E+09 | 1123.90 | 07-JAN-15:50 | 20.07 | 13.27 |
February | 0.201364E+10 | 5574.83 | 22-FEB-14:00 | 27.00 | 16.33 | 0.636312E+09 | 1123.88 | 18-FEB-15:00 | 27.00 | 16.33 |
March | 0.502882E+10 | 9789.25 | 28-MAR-15:00 | 35.60 | 18.50 | 0.738475E+09 | 1123.98 | 11-MAR-15:00 | 35.60 | 18.50 |
April | 0.864829E+10 | 28900.56 | 30-APR-08:62 | 26.15 | 14.14 | 0.705804E+09 | 1124.01 | 15-APR-14:39 | 26.15 | 14.14 |
May | 0.115621E+11 | 30423.71 | 29-MAY-08:61 | 32.12 | 19.78 | 0.730085E+09 | 1124.12 | 06-MAY-14:00 | 32.12 | 19.78 |
June | 0.114875E+11 | 28593.35 | 12-JUN-07:01 | 35.90 | 20.13 | 0.715811E+09 | 1123.87 | 17-JUN-14:00 | 38.50 | 25.76 |
July | 0.108584E+11 | 24630.00 | 07-JUL-07:01 | 33.33 | 24.39 | 0.720325E+09 | 1123.96 | 22-JUL-14:00 | 29.50 | 26.90 |
August | 0.104302E+11 | 21700.47 | 09-AUG-07:01 | 30.30 | 25.37 | 0.740717E+09 | 1123.99 | 19-AUG-14:09 | 28.02 | 26.43 |
September | 0.908078E+10 | 24261.97 | 27-SEP-07:02 | 24.98 | 20.39 | 0.705728E+09 | 1123.87 | 02-SEP-14:09 | 24.98 | 20.39 |
October | 0.815638E+10 | 26320.19 | 02-OCT-07:02 | 24.92 | 18.38 | 0.718367E+09 | 1123.96 | 28-OCT-14:00 | 29.30 | 18.44 |
November | 0.463890E+10 | 8054.25 | 04-NOV-14:10 | 30.28 | 17.23 | 0.689777E+09 | 1123.92 | 04-NOV-14:00 | 30.20 | 17.55 |
December | 0.154667E+10 | 4188.85 | 01-DEC-14:00 | 23.50 | 13.07 | 0.689541E+09 | 1123.89 | 09-DEC-15:09 | 19.72 | 13.10 |
Annual Sum or Average | 0.844080E+11 | 0.844974E+10 | ||||||||
Minimum of Months | 0.956322E+09 | 3674.83 | 6.10 | 5.59 | 0.636312E+09 | 1123.87 | 19.72 | 13.10 | ||
Maximum of Months | 0.115621E+11 | 30423.71 | 35.90 | 25.37 | 0.740717E+09 | 1124.12 | 38.50 | 26.90 |
Report: ZoneHeatingSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 97184986.64 | 63667.72 | 02-JAN-08:61 | 7.38 |
February | 3376991.69 | 2450.72 | 02-FEB-08:05 | 8.07 |
March | 3165625.63 | 2465.27 | 11-MAR-08:05 | 24.43 |
April | 48648583.04 | 4857.17 | 27-APR-07:05 | 30.20 |
May | 38099506.98 | 7306.27 | 04-MAY-07:04 | 34.62 |
June | 27317401.98 | 7202.49 | 12-JUN-07:05 | 35.90 |
July | 25868132.13 | 6292.34 | 08-JUL-07:05 | 33.13 |
August | 27295431.41 | 4994.65 | 08-AUG-07:05 | 30.50 |
September | 32852387.29 | 4242.84 | 22-SEP-07:04 | 28.37 |
October | 21063747.42 | 2935.80 | 03-OCT-07:04 | 24.75 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 7809343.33 | 14574.33 | 23-DEC-08:62 | 7.55 |
Annual Sum or Average | 0.332682E+09 | |||
Minimum of Months | 0.00 | 0.00 | 7.38 | |
Maximum of Months | 97184986.64 | 63667.72 | 35.90 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 10640480.96 | 13790.72 | 02-JAN-08:61 | 7.38 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 9.73 |
March | 1842842.16 | 1374.25 | 11-MAR-08:05 | 24.43 |
April | 24357872.26 | 2322.23 | 27-APR-07:05 | 30.20 |
May | 15313238.49 | 3533.96 | 04-MAY-07:04 | 34.62 |
June | 10406800.01 | 3920.60 | 12-JUN-07:04 | 35.90 |
July | 11036395.32 | 3348.16 | 07-JUL-07:04 | 33.33 |
August | 10151325.11 | 2598.84 | 07-AUG-07:04 | 30.33 |
September | 15051414.26 | 2177.69 | 22-SEP-07:04 | 28.37 |
October | 11170809.22 | 1638.31 | 03-OCT-07:04 | 24.75 |
November | 11016.31 | 55.08 | 09-NOV-08:07 | 19.90 |
December | 153262.42 | 1277.19 | 23-DEC-08:08 | 7.55 |
Annual Sum or Average | 0.110135E+09 | |||
Minimum of Months | 0.00 | 0.00 | 7.38 | |
Maximum of Months | 24357872.26 | 13790.72 | 35.90 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 34198723.82 | 25712.87 | 01-JAN-08:62 | 8.17 |
February | 502492.67 | 343.89 | 20-FEB-17:03 | 24.33 |
March | 36133469.98 | 1870.87 | 12-MAR-16:02 | 31.18 |
April | 0.186310E+09 | 3823.30 | 16-APR-16:01 | 39.13 |
May | 0.235674E+09 | 4548.37 | 07-MAY-16:01 | 42.17 |
June | 0.247817E+09 | 4871.44 | 11-JUN-16:01 | 43.35 |
July | 0.182802E+09 | 4179.39 | 02-JUL-16:01 | 40.38 |
August | 0.153309E+09 | 3187.72 | 06-AUG-16:01 | 36.25 |
September | 0.134266E+09 | 2774.20 | 24-SEP-16:01 | 34.68 |
October | 73804971.33 | 2881.76 | 01-OCT-16:01 | 35.32 |
November | 6354750.92 | 1136.93 | 04-NOV-17:03 | 27.72 |
December | 276838.47 | 646.59 | 23-DEC-07:10 | 6.25 |
Annual Sum or Average | 0.129145E+10 | |||
Minimum of Months | 276838.47 | 343.89 | 6.25 | |
Maximum of Months | 0.247817E+09 | 25712.87 | 43.35 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 48612054.84 | 31899.32 | 01-JAN-08:62 | 8.17 |
February | 549196.34 | 352.72 | 20-FEB-17:03 | 24.33 |
March | 36277326.68 | 1871.97 | 12-MAR-16:02 | 31.18 |
April | 0.186082E+09 | 3822.01 | 16-APR-16:01 | 39.13 |
May | 0.233373E+09 | 4546.22 | 07-MAY-16:01 | 42.17 |
June | 0.243614E+09 | 4869.00 | 11-JUN-16:01 | 43.35 |
July | 0.181924E+09 | 4177.35 | 02-JUL-16:01 | 40.38 |
August | 0.152495E+09 | 3185.93 | 06-AUG-16:01 | 36.25 |
September | 0.132947E+09 | 2772.79 | 24-SEP-16:01 | 34.68 |
October | 73627849.61 | 2880.47 | 01-OCT-16:01 | 35.32 |
November | 6405229.11 | 1139.23 | 04-NOV-17:03 | 27.72 |
December | 512985.74 | 512.78 | 23-DEC-07:10 | 6.25 |
Annual Sum or Average | 0.129642E+10 | |||
Minimum of Months | 512985.74 | 352.72 | 6.25 | |
Maximum of Months | 0.243614E+09 | 31899.32 | 43.35 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 70836220.33 | 31802.70 | 01-JAN-08:62 | 8.17 |
February | 704789.59 | 366.88 | 20-FEB-17:03 | 24.33 |
March | 37053124.18 | 1878.87 | 12-MAR-16:02 | 31.18 |
April | 0.187224E+09 | 3825.66 | 16-APR-16:01 | 39.13 |
May | 0.236683E+09 | 4549.01 | 07-MAY-16:01 | 42.17 |
June | 0.248383E+09 | 4871.10 | 11-JUN-16:01 | 43.35 |
July | 0.183714E+09 | 4179.85 | 02-JUL-16:01 | 40.38 |
August | 0.154859E+09 | 3188.66 | 06-AUG-16:01 | 36.25 |
September | 0.136613E+09 | 2776.49 | 24-SEP-16:01 | 34.68 |
October | 74644046.27 | 2884.48 | 01-OCT-16:01 | 35.32 |
November | 6646047.01 | 1147.90 | 04-NOV-17:03 | 27.72 |
December | 942929.77 | 1027.84 | 31-DEC-08:10 | 6.52 |
Annual Sum or Average | 0.133830E+10 | |||
Minimum of Months | 704789.59 | 366.88 | 6.52 | |
Maximum of Months | 0.248383E+09 | 31802.70 | 43.35 |
Report: ZoneHeatingSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.202906E+09 | 59219.81 | 01-JAN-09:01 | 9.20 |
February | 6280803.23 | 2561.15 | 01-FEB-08:07 | 9.43 |
March | 34777493.94 | 3834.82 | 12-MAR-16:02 | 31.18 |
April | 0.160823E+09 | 7717.69 | 16-APR-16:01 | 39.13 |
May | 0.154893E+09 | 9161.67 | 07-MAY-16:01 | 42.17 |
June | 0.134241E+09 | 9796.98 | 11-JUN-16:01 | 43.35 |
July | 0.143374E+09 | 8413.22 | 02-JUL-16:01 | 40.38 |
August | 0.106035E+09 | 6422.65 | 06-AUG-16:01 | 36.25 |
September | 0.124315E+09 | 5608.94 | 24-SEP-16:01 | 34.68 |
October | 0.103598E+09 | 5833.10 | 01-OCT-16:01 | 35.32 |
November | 13427989.54 | 2344.87 | 04-NOV-17:03 | 27.72 |
December | 11672762.00 | 16431.19 | 23-DEC-08:62 | 7.55 |
Annual Sum or Average | 0.119634E+10 | |||
Minimum of Months | 6280803.23 | 2344.87 | 7.55 | |
Maximum of Months | 0.202906E+09 | 59219.81 | 43.35 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.122385E+09 | 31239.69 | 01-JAN-09:01 | 9.20 |
February | 4220244.12 | 1998.19 | 11-FEB-08:62 | 11.12 |
March | 18779848.74 | 1925.43 | 12-MAR-16:02 | 31.18 |
April | 82608910.84 | 3862.16 | 16-APR-16:01 | 39.13 |
May | 77112885.68 | 4582.90 | 07-MAY-16:01 | 42.17 |
June | 66169301.75 | 4901.61 | 11-JUN-16:01 | 43.35 |
July | 72561732.60 | 4211.20 | 02-JUL-16:01 | 40.38 |
August | 51342547.80 | 3219.90 | 06-AUG-16:01 | 36.25 |
September | 62828012.16 | 2812.05 | 24-SEP-16:01 | 34.68 |
October | 53472204.99 | 2921.96 | 01-OCT-16:01 | 35.32 |
November | 7574901.88 | 1196.30 | 04-NOV-17:03 | 27.72 |
December | 5681239.74 | 9319.61 | 23-DEC-08:62 | 7.55 |
Annual Sum or Average | 0.624736E+09 | |||
Minimum of Months | 4220244.12 | 1196.30 | 7.55 | |
Maximum of Months | 0.122385E+09 | 31239.69 | 43.35 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.135995E+09 | 31160.42 | 01-JAN-09:01 | 9.20 |
February | 6759590.71 | 3626.94 | 11-FEB-08:62 | 11.12 |
March | 18896180.84 | 1927.10 | 12-MAR-16:02 | 31.18 |
April | 82843838.13 | 3863.05 | 16-APR-16:01 | 39.13 |
May | 77461560.27 | 4583.56 | 07-MAY-16:01 | 42.17 |
June | 65746070.08 | 4902.04 | 11-JUN-16:01 | 43.35 |
July | 72758399.51 | 4211.74 | 02-JUL-16:01 | 40.38 |
August | 51476808.13 | 3220.40 | 06-AUG-16:01 | 36.25 |
September | 62981947.86 | 2812.78 | 24-SEP-16:01 | 34.68 |
October | 53506039.67 | 2922.82 | 01-OCT-16:01 | 35.32 |
November | 7634492.07 | 1198.26 | 04-NOV-17:03 | 27.72 |
December | 7760887.73 | 10691.49 | 23-DEC-08:62 | 7.55 |
Annual Sum or Average | 0.643821E+09 | |||
Minimum of Months | 6759590.71 | 1198.26 | 7.55 | |
Maximum of Months | 0.135995E+09 | 31160.42 | 43.35 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.183980E+09 | 31371.86 | 01-JAN-09:01 | 9.20 |
February | 13145473.44 | 9444.19 | 11-FEB-08:62 | 11.12 |
March | 19484468.50 | 1929.15 | 12-MAR-16:02 | 31.18 |
April | 82378625.67 | 3861.05 | 16-APR-16:01 | 39.13 |
May | 77207820.78 | 4580.59 | 07-MAY-16:01 | 42.17 |
June | 65345597.94 | 4898.56 | 11-JUN-16:01 | 43.35 |
July | 72682730.98 | 4207.78 | 02-JUL-16:01 | 40.38 |
August | 50858652.16 | 3216.51 | 06-AUG-16:01 | 36.25 |
September | 62464507.55 | 2809.53 | 24-SEP-16:01 | 34.68 |
October | 53204757.15 | 2920.01 | 01-OCT-16:01 | 35.32 |
November | 7847749.48 | 1202.07 | 04-NOV-17:03 | 27.72 |
December | 14564467.09 | 15326.52 | 23-DEC-08:62 | 7.55 |
Annual Sum or Average | 0.703165E+09 | |||
Minimum of Months | 7847749.48 | 1202.07 | 7.55 | |
Maximum of Months | 0.183980E+09 | 31371.86 | 43.35 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.360152E+09 | 36308.22 | 01-JAN-09:01 | 9.20 |
February | 71051290.94 | 28602.58 | 11-FEB-08:62 | 11.12 |
March | 20260091.41 | 1900.67 | 12-MAR-16:12 | 31.07 |
April | 75916843.21 | 3787.75 | 16-APR-16:01 | 39.13 |
May | 62564283.43 | 4501.85 | 07-MAY-16:01 | 42.17 |
June | 56993079.16 | 4819.64 | 11-JUN-16:01 | 43.35 |
July | 62112188.24 | 4121.70 | 02-JUL-16:01 | 40.38 |
August | 42637324.17 | 3132.19 | 06-AUG-16:01 | 36.25 |
September | 54109967.94 | 2727.20 | 24-SEP-16:01 | 34.68 |
October | 50732844.88 | 2838.68 | 01-OCT-16:01 | 35.32 |
November | 7651945.66 | 1172.77 | 04-NOV-17:03 | 27.72 |
December | 61885924.35 | 31368.22 | 23-DEC-08:62 | 7.55 |
Annual Sum or Average | 0.926068E+09 | |||
Minimum of Months | 7651945.66 | 1172.77 | 7.55 | |
Maximum of Months | 0.360152E+09 | 36308.22 | 43.35 |
Report: ZoneElectricSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.739462E+10 | 4621.63 | 01-JAN-10:09 | 0.222596E+10 | 1343.25 | 01-JAN-10:09 |
February | 0.668410E+10 | 4621.63 | 01-FEB-10:09 | 0.201408E+10 | 1343.25 | 01-FEB-10:09 |
March | 0.740180E+10 | 4621.63 | 01-MAR-10:09 | 0.223295E+10 | 1343.25 | 01-MAR-10:09 |
April | 0.716384E+10 | 4621.63 | 01-APR-09:09 | 0.215748E+10 | 1343.25 | 01-APR-09:09 |
May | 0.739462E+10 | 4621.63 | 01-MAY-09:09 | 0.222596E+10 | 1343.25 | 01-MAY-09:09 |
June | 0.716485E+10 | 4621.63 | 01-JUN-09:09 | 0.216232E+10 | 1343.25 | 01-JUN-09:09 |
July | 0.740069E+10 | 4621.63 | 01-JUL-09:09 | 0.222811E+10 | 1343.25 | 01-JUL-09:09 |
August | 0.739513E+10 | 4621.63 | 01-AUG-09:09 | 0.222838E+10 | 1343.25 | 01-AUG-09:09 |
September | 0.717041E+10 | 4621.63 | 01-SEP-09:09 | 0.216205E+10 | 1343.25 | 01-SEP-09:09 |
October | 0.739462E+10 | 4621.63 | 01-OCT-09:09 | 0.222596E+10 | 1343.25 | 01-OCT-09:09 |
November | 0.714323E+10 | 4621.63 | 01-NOV-09:09 | 0.215077E+10 | 1343.25 | 01-NOV-09:09 |
December | 0.740776E+10 | 4621.63 | 01-DEC-10:09 | 0.223509E+10 | 1343.25 | 01-DEC-10:09 |
Annual Sum or Average | 0.871157E+11 | 0.262491E+11 | ||||
Minimum of Months | 0.668410E+10 | 4621.63 | 0.201408E+10 | 1343.25 | ||
Maximum of Months | 0.740776E+10 | 4621.63 | 0.223509E+10 | 1343.25 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.451584E+10 | 2827.07 | 01-JAN-10:09 | 0.111298E+10 | 671.63 | 01-JAN-10:09 |
February | 0.408193E+10 | 2827.07 | 01-FEB-10:09 | 0.100704E+10 | 671.63 | 01-FEB-10:09 |
March | 0.452026E+10 | 2827.07 | 01-MAR-10:09 | 0.111647E+10 | 671.63 | 01-MAR-10:09 |
April | 0.437489E+10 | 2827.07 | 01-APR-09:09 | 0.107874E+10 | 671.63 | 01-APR-09:09 |
May | 0.451584E+10 | 2827.07 | 01-MAY-09:09 | 0.111298E+10 | 671.63 | 01-MAY-09:09 |
June | 0.437556E+10 | 2827.07 | 01-JUN-09:09 | 0.108116E+10 | 671.63 | 01-JUN-09:09 |
July | 0.451952E+10 | 2827.07 | 01-JUL-09:09 | 0.111405E+10 | 671.63 | 01-JUL-09:09 |
August | 0.451617E+10 | 2827.07 | 01-AUG-09:09 | 0.111419E+10 | 671.63 | 01-AUG-09:09 |
September | 0.437891E+10 | 2827.07 | 01-SEP-09:09 | 0.108102E+10 | 671.63 | 01-SEP-09:09 |
October | 0.451584E+10 | 2827.07 | 01-OCT-09:09 | 0.111298E+10 | 671.63 | 01-OCT-09:09 |
November | 0.436230E+10 | 2827.07 | 01-NOV-09:09 | 0.107538E+10 | 671.63 | 01-NOV-09:09 |
December | 0.452388E+10 | 2827.07 | 01-DEC-10:09 | 0.111755E+10 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.532009E+11 | 0.131245E+11 | ||||
Minimum of Months | 0.408193E+10 | 2827.07 | 0.100704E+10 | 671.63 | ||
Maximum of Months | 0.452388E+10 | 2827.07 | 0.111755E+10 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.317044E+10 | 2555.22 | 01-JAN-10:09 | 0.879849E+09 | 671.63 | 01-JAN-10:09 |
February | 0.287181E+10 | 2555.22 | 01-FEB-09:09 | 0.796766E+09 | 671.63 | 01-FEB-09:09 |
March | 0.324295E+10 | 2555.22 | 01-MAR-09:09 | 0.898128E+09 | 671.63 | 01-MAR-09:09 |
April | 0.307694E+10 | 2555.22 | 01-APR-08:09 | 0.853677E+09 | 671.63 | 01-APR-08:09 |
May | 0.320669E+10 | 2555.22 | 01-MAY-08:09 | 0.888989E+09 | 671.63 | 01-MAY-08:09 |
June | 0.313132E+10 | 2555.22 | 01-JUN-08:09 | 0.867387E+09 | 671.63 | 01-JUN-08:09 |
July | 0.315231E+10 | 2555.22 | 01-JUL-08:09 | 0.875279E+09 | 671.63 | 01-JUL-08:09 |
August | 0.324295E+10 | 2555.22 | 01-AUG-08:09 | 0.898128E+09 | 671.63 | 01-AUG-08:09 |
September | 0.307694E+10 | 2555.22 | 01-SEP-08:09 | 0.853677E+09 | 671.63 | 01-SEP-08:09 |
October | 0.317044E+10 | 2555.22 | 01-OCT-09:09 | 0.879849E+09 | 671.63 | 01-OCT-09:09 |
November | 0.307694E+10 | 2555.22 | 01-NOV-08:09 | 0.853679E+09 | 671.63 | 01-NOV-08:09 |
December | 0.315231E+10 | 2555.22 | 01-DEC-09:09 | 0.875279E+09 | 671.63 | 01-DEC-09:09 |
Annual Sum or Average | 0.375720E+11 | 0.104207E+11 | ||||
Minimum of Months | 0.287181E+10 | 2555.22 | 0.796766E+09 | 671.63 | ||
Maximum of Months | 0.324295E+10 | 2555.22 | 0.898128E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.317044E+10 | 2555.22 | 01-JAN-10:09 | 0.879849E+09 | 671.63 | 01-JAN-10:09 |
February | 0.287181E+10 | 2555.22 | 01-FEB-09:09 | 0.796766E+09 | 671.63 | 01-FEB-09:09 |
March | 0.324295E+10 | 2555.22 | 01-MAR-09:09 | 0.898128E+09 | 671.63 | 01-MAR-09:09 |
April | 0.307694E+10 | 2555.22 | 01-APR-08:09 | 0.853677E+09 | 671.63 | 01-APR-08:09 |
May | 0.320669E+10 | 2555.22 | 01-MAY-08:09 | 0.888989E+09 | 671.63 | 01-MAY-08:09 |
June | 0.313132E+10 | 2555.22 | 01-JUN-08:09 | 0.867387E+09 | 671.63 | 01-JUN-08:09 |
July | 0.315231E+10 | 2555.22 | 01-JUL-08:09 | 0.875279E+09 | 671.63 | 01-JUL-08:09 |
August | 0.324295E+10 | 2555.22 | 01-AUG-08:09 | 0.898128E+09 | 671.63 | 01-AUG-08:09 |
September | 0.307694E+10 | 2555.22 | 01-SEP-08:09 | 0.853677E+09 | 671.63 | 01-SEP-08:09 |
October | 0.317044E+10 | 2555.22 | 01-OCT-09:09 | 0.879849E+09 | 671.63 | 01-OCT-09:09 |
November | 0.307694E+10 | 2555.22 | 01-NOV-08:09 | 0.853679E+09 | 671.63 | 01-NOV-08:09 |
December | 0.315231E+10 | 2555.22 | 01-DEC-09:09 | 0.875279E+09 | 671.63 | 01-DEC-09:09 |
Annual Sum or Average | 0.375720E+11 | 0.104207E+11 | ||||
Minimum of Months | 0.287181E+10 | 2555.22 | 0.796766E+09 | 671.63 | ||
Maximum of Months | 0.324295E+10 | 2555.22 | 0.898128E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.317044E+10 | 2555.22 | 01-JAN-10:09 | 0.879849E+09 | 671.63 | 01-JAN-10:09 |
February | 0.287181E+10 | 2555.22 | 01-FEB-09:09 | 0.796766E+09 | 671.63 | 01-FEB-09:09 |
March | 0.324295E+10 | 2555.22 | 01-MAR-09:09 | 0.898128E+09 | 671.63 | 01-MAR-09:09 |
April | 0.307694E+10 | 2555.22 | 01-APR-08:09 | 0.853677E+09 | 671.63 | 01-APR-08:09 |
May | 0.320669E+10 | 2555.22 | 01-MAY-08:09 | 0.888989E+09 | 671.63 | 01-MAY-08:09 |
June | 0.313132E+10 | 2555.22 | 01-JUN-08:09 | 0.867387E+09 | 671.63 | 01-JUN-08:09 |
July | 0.315231E+10 | 2555.22 | 01-JUL-08:09 | 0.875279E+09 | 671.63 | 01-JUL-08:09 |
August | 0.324295E+10 | 2555.22 | 01-AUG-08:09 | 0.898128E+09 | 671.63 | 01-AUG-08:09 |
September | 0.307694E+10 | 2555.22 | 01-SEP-08:09 | 0.853677E+09 | 671.63 | 01-SEP-08:09 |
October | 0.317044E+10 | 2555.22 | 01-OCT-09:09 | 0.879849E+09 | 671.63 | 01-OCT-09:09 |
November | 0.307694E+10 | 2555.22 | 01-NOV-08:09 | 0.853679E+09 | 671.63 | 01-NOV-08:09 |
December | 0.315231E+10 | 2555.22 | 01-DEC-09:09 | 0.875279E+09 | 671.63 | 01-DEC-09:09 |
Annual Sum or Average | 0.375720E+11 | 0.104207E+11 | ||||
Minimum of Months | 0.287181E+10 | 2555.22 | 0.796766E+09 | 671.63 | ||
Maximum of Months | 0.324295E+10 | 2555.22 | 0.898128E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.313454E+10 | 2726.96 | 01-JAN-11:09 | 0.161799E+10 | 1343.25 | 01-JAN-11:09 |
February | 0.283982E+10 | 2726.96 | 01-FEB-10:09 | 0.146554E+10 | 1343.25 | 01-FEB-10:09 |
March | 0.321092E+10 | 2726.96 | 01-MAR-10:09 | 0.165455E+10 | 1343.25 | 01-MAR-10:09 |
April | 0.304266E+10 | 2726.96 | 01-APR-09:09 | 0.157022E+10 | 1343.25 | 01-APR-09:09 |
May | 0.317273E+10 | 2726.96 | 01-MAY-09:09 | 0.163627E+10 | 1343.25 | 01-MAY-09:09 |
June | 0.309995E+10 | 2726.96 | 01-JUN-09:09 | 0.159764E+10 | 1343.25 | 01-JUN-09:09 |
July | 0.311545E+10 | 2726.96 | 01-JUL-09:09 | 0.160885E+10 | 1343.25 | 01-JUL-09:09 |
August | 0.321092E+10 | 2726.96 | 01-AUG-09:09 | 0.165455E+10 | 1343.25 | 01-AUG-09:09 |
September | 0.304266E+10 | 2726.96 | 01-SEP-09:09 | 0.157022E+10 | 1343.25 | 01-SEP-09:09 |
October | 0.313454E+10 | 2726.96 | 01-OCT-10:09 | 0.161799E+10 | 1343.25 | 01-OCT-10:09 |
November | 0.304266E+10 | 2726.96 | 01-NOV-09:09 | 0.157022E+10 | 1343.25 | 01-NOV-09:09 |
December | 0.311545E+10 | 2726.96 | 01-DEC-10:09 | 0.160885E+10 | 1343.25 | 01-DEC-10:09 |
Annual Sum or Average | 0.371623E+11 | 0.191729E+11 | ||||
Minimum of Months | 0.283982E+10 | 2726.96 | 0.146554E+10 | 1343.25 | ||
Maximum of Months | 0.321092E+10 | 2726.96 | 0.165455E+10 | 1343.25 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.161274E+10 | 1404.46 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.146111E+10 | 1404.46 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.165211E+10 | 1404.46 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.156548E+10 | 1404.46 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.163243E+10 | 1404.46 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.159501E+10 | 1404.46 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.160290E+10 | 1404.46 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.165211E+10 | 1404.46 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.156548E+10 | 1404.46 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.161274E+10 | 1404.46 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.156548E+10 | 1404.46 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.160290E+10 | 1404.46 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.191205E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.146111E+10 | 1404.46 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.165211E+10 | 1404.46 | 0.827277E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.161274E+10 | 1404.46 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.146111E+10 | 1404.46 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.165211E+10 | 1404.46 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.156548E+10 | 1404.46 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.163243E+10 | 1404.46 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.159501E+10 | 1404.46 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.160290E+10 | 1404.46 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.165211E+10 | 1404.46 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.156548E+10 | 1404.46 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.161274E+10 | 1404.46 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.156548E+10 | 1404.46 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.160290E+10 | 1404.46 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.191205E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.146111E+10 | 1404.46 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.165211E+10 | 1404.46 | 0.827277E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.161274E+10 | 1404.46 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.146111E+10 | 1404.46 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.165211E+10 | 1404.46 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.156548E+10 | 1404.46 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.163243E+10 | 1404.46 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.159501E+10 | 1404.46 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.160290E+10 | 1404.46 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.165211E+10 | 1404.46 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.156548E+10 | 1404.46 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.161274E+10 | 1404.46 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.156548E+10 | 1404.46 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.160290E+10 | 1404.46 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.191205E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.146111E+10 | 1404.46 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.165211E+10 | 1404.46 | 0.827277E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.161274E+10 | 1404.46 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.146111E+10 | 1404.46 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.165211E+10 | 1404.46 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.156548E+10 | 1404.46 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.163243E+10 | 1404.46 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.159501E+10 | 1404.46 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.160290E+10 | 1404.46 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.165211E+10 | 1404.46 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.156548E+10 | 1404.46 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.161274E+10 | 1404.46 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.156548E+10 | 1404.46 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.160290E+10 | 1404.46 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.191205E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.146111E+10 | 1404.46 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.165211E+10 | 1404.46 | 0.827277E+09 | 671.63 |
Report: SpaceGainsMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.338624E+10 | 0.739462E+10 | 0.222596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192163E+10 |
February | 0.305697E+10 | 0.668410E+10 | 0.201408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120652E+09 | 0.812477E+09 |
March | 0.335708E+10 | 0.740180E+10 | 0.223295E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122859E+10 | 0.197532E+09 |
April | 0.327081E+10 | 0.716384E+10 | 0.215748E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.329547E+10 | 10845763.03 |
May | 0.336680E+10 | 0.739462E+10 | 0.222596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.466111E+10 | 2904140.85 |
June | 0.325380E+10 | 0.716485E+10 | 0.216232E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.422982E+10 | 1487508.90 |
July | 0.339353E+10 | 0.740069E+10 | 0.222811E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.340966E+10 | 806581.70 |
August | 0.334857E+10 | 0.739513E+10 | 0.222838E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.289027E+10 | 1238917.23 |
September | 0.327932E+10 | 0.717041E+10 | 0.216205E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.252458E+10 | 2605953.66 |
October | 0.338624E+10 | 0.739462E+10 | 0.222596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.218200E+10 | 36878963.12 |
November | 0.327446E+10 | 0.714323E+10 | 0.215077E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.743421E+09 | 0.250705E+09 |
December | 0.340325E+10 | 0.740776E+10 | 0.223509E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5212711.42 | 0.166609E+10 |
Annual Sum or Average | 0.397770E+11 | 0.871157E+11 | 0.262491E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.252908E+11 | 0.490520E+10 |
Minimum of Months | 0.305697E+10 | 0.668410E+10 | 0.201408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 806581.70 |
Maximum of Months | 0.340325E+10 | 0.740776E+10 | 0.223509E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.466111E+10 | 0.192163E+10 |
Report: SpaceGainsMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.169307E+10 | 0.451584E+10 | 0.111298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110204E+10 |
February | 0.152844E+10 | 0.408193E+10 | 0.100704E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 68407744.38 | 0.442798E+09 |
March | 0.167849E+10 | 0.452026E+10 | 0.111647E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.695277E+09 | 93183349.04 |
April | 0.163536E+10 | 0.437489E+10 | 0.107874E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185724E+10 | 4330123.54 |
May | 0.168335E+10 | 0.451584E+10 | 0.111298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.261074E+10 | 917632.04 |
June | 0.162685E+10 | 0.437556E+10 | 0.108116E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.237912E+10 | 449241.76 |
July | 0.169671E+10 | 0.451952E+10 | 0.111405E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190383E+10 | 231974.49 |
August | 0.167424E+10 | 0.451617E+10 | 0.111419E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162458E+10 | 344014.03 |
September | 0.163961E+10 | 0.437891E+10 | 0.108102E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142665E+10 | 723324.29 |
October | 0.169307E+10 | 0.451584E+10 | 0.111298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123914E+10 | 18684838.53 |
November | 0.163718E+10 | 0.436230E+10 | 0.107538E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.422975E+09 | 0.135816E+09 |
December | 0.170157E+10 | 0.452388E+10 | 0.111755E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2960838.99 | 0.940602E+09 |
Annual Sum or Average | 0.198880E+11 | 0.532009E+11 | 0.131245E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142309E+11 | 0.274012E+10 |
Minimum of Months | 0.152844E+10 | 0.408193E+10 | 0.100704E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 231974.49 |
Maximum of Months | 0.170157E+10 | 0.452388E+10 | 0.111755E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.261074E+10 | 0.110204E+10 |
Report: SpaceGainsMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.317044E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107920E+10 |
February | 0.914877E+09 | 0.287181E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 68319650.61 | 0.453909E+09 |
March | 0.103395E+10 | 0.324295E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.683586E+09 | 0.102974E+09 |
April | 0.984131E+09 | 0.307694E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183236E+10 | 5461846.45 |
May | 0.102058E+10 | 0.320669E+10 | 0.888989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258209E+10 | 1179010.81 |
June | 0.998711E+09 | 0.313132E+10 | 0.867387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235772E+10 | 577662.05 |
July | 0.100600E+10 | 0.315231E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187108E+10 | 287981.78 |
August | 0.103395E+10 | 0.324295E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160252E+10 | 997493.41 |
September | 0.984131E+09 | 0.307694E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140209E+10 | 1410236.09 |
October | 0.100722E+10 | 0.317044E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121124E+10 | 19705013.95 |
November | 0.973196E+09 | 0.307694E+10 | 0.853679E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.418371E+09 | 0.144096E+09 |
December | 0.100600E+10 | 0.315231E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2961106.86 | 0.938295E+09 |
Annual Sum or Average | 0.119700E+11 | 0.375720E+11 | 0.104207E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140323E+11 | 0.274809E+10 |
Minimum of Months | 0.914877E+09 | 0.287181E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 287981.78 |
Maximum of Months | 0.103395E+10 | 0.324295E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258209E+10 | 0.107920E+10 |
Report: SpaceGainsMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.317044E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106609E+10 |
February | 0.914877E+09 | 0.287181E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 68320278.19 | 0.451402E+09 |
March | 0.103395E+10 | 0.324295E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.683564E+09 | 0.102738E+09 |
April | 0.984131E+09 | 0.307694E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183204E+10 | 5534033.61 |
May | 0.102058E+10 | 0.320669E+10 | 0.888989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258106E+10 | 1263423.73 |
June | 0.998711E+09 | 0.313132E+10 | 0.867387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235702E+10 | 627281.03 |
July | 0.100600E+10 | 0.315231E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.186991E+10 | 319163.94 |
August | 0.103395E+10 | 0.324295E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160194E+10 | 1063592.56 |
September | 0.984131E+09 | 0.307694E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140178E+10 | 1538278.25 |
October | 0.100722E+10 | 0.317044E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121104E+10 | 19747308.22 |
November | 0.973196E+09 | 0.307694E+10 | 0.853679E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.418381E+09 | 0.143702E+09 |
December | 0.100600E+10 | 0.315231E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2961124.60 | 0.933597E+09 |
Annual Sum or Average | 0.119700E+11 | 0.375720E+11 | 0.104207E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140280E+11 | 0.272762E+10 |
Minimum of Months | 0.914877E+09 | 0.287181E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 319163.94 |
Maximum of Months | 0.103395E+10 | 0.324295E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258106E+10 | 0.106609E+10 |
Report: SpaceGainsMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.317044E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104682E+10 |
February | 0.914877E+09 | 0.287181E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 68321230.67 | 0.446251E+09 |
March | 0.103395E+10 | 0.324295E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.683787E+09 | 0.101293E+09 |
April | 0.984131E+09 | 0.307694E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183250E+10 | 5332886.18 |
May | 0.102058E+10 | 0.320669E+10 | 0.888989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258185E+10 | 1150112.00 |
June | 0.998711E+09 | 0.313132E+10 | 0.867387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235763E+10 | 590042.60 |
July | 0.100600E+10 | 0.315231E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187088E+10 | 276477.85 |
August | 0.103395E+10 | 0.324295E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160260E+10 | 951582.53 |
September | 0.984131E+09 | 0.307694E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140218E+10 | 1317758.56 |
October | 0.100722E+10 | 0.317044E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121139E+10 | 19610786.65 |
November | 0.973196E+09 | 0.307694E+10 | 0.853679E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.418428E+09 | 0.142607E+09 |
December | 0.100600E+10 | 0.315231E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2961153.17 | 0.925206E+09 |
Annual Sum or Average | 0.119700E+11 | 0.375720E+11 | 0.104207E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140325E+11 | 0.269141E+10 |
Minimum of Months | 0.914877E+09 | 0.287181E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 276477.85 |
Maximum of Months | 0.103395E+10 | 0.324295E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258185E+10 | 0.104682E+10 |
Report: SpaceGainsMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.344359E+10 | 0.313454E+10 | 0.161799E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178939E+10 |
February | 0.313522E+10 | 0.283982E+10 | 0.146554E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119671E+09 | 0.776627E+09 |
March | 0.355148E+10 | 0.321092E+10 | 0.165455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119943E+10 | 0.180507E+09 |
April | 0.338259E+10 | 0.304266E+10 | 0.157022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.321470E+10 | 10118137.90 |
May | 0.349753E+10 | 0.317273E+10 | 0.163627E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.453523E+10 | 2231512.25 |
June | 0.343071E+10 | 0.309995E+10 | 0.159764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.413884E+10 | 1385940.74 |
July | 0.344942E+10 | 0.311545E+10 | 0.160885E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.328816E+10 | 449493.38 |
August | 0.355148E+10 | 0.321092E+10 | 0.165455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.281289E+10 | 1556730.75 |
September | 0.338259E+10 | 0.304266E+10 | 0.157022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.245693E+10 | 2572510.63 |
October | 0.344359E+10 | 0.313454E+10 | 0.161799E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.212325E+10 | 36376580.78 |
November | 0.331698E+10 | 0.304266E+10 | 0.157022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.732859E+09 | 0.249356E+09 |
December | 0.344942E+10 | 0.311545E+10 | 0.160885E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5187296.54 | 0.159703E+10 |
Annual Sum or Average | 0.410346E+11 | 0.371623E+11 | 0.191729E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.246271E+11 | 0.464760E+10 |
Minimum of Months | 0.313522E+10 | 0.283982E+10 | 0.146554E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 449493.38 |
Maximum of Months | 0.355148E+10 | 0.321092E+10 | 0.165455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.453523E+10 | 0.178939E+10 |
Report: SpaceGainsMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.161274E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100746E+10 |
February | 0.156756E+10 | 0.146111E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 68323103.51 | 0.435529E+09 |
March | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.684792E+09 | 98576886.53 |
April | 0.169125E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183397E+10 | 5300113.88 |
May | 0.174872E+10 | 0.163243E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258477E+10 | 1059731.16 |
June | 0.171530E+10 | 0.159501E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.236017E+10 | 672107.59 |
July | 0.172466E+10 | 0.160290E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187336E+10 | 201909.30 |
August | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160429E+10 | 714566.24 |
September | 0.169125E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140247E+10 | 1163592.98 |
October | 0.172174E+10 | 0.161274E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121286E+10 | 20290651.56 |
November | 0.165844E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.418600E+09 | 0.140787E+09 |
December | 0.172466E+10 | 0.160290E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2962362.08 | 0.903133E+09 |
Annual Sum or Average | 0.205167E+11 | 0.191205E+11 | 0.958644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140466E+11 | 0.261489E+10 |
Minimum of Months | 0.156756E+10 | 0.146111E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 201909.30 |
Maximum of Months | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258477E+10 | 0.100746E+10 |
Report: SpaceGainsMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.161274E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100132E+10 |
February | 0.156756E+10 | 0.146111E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 68324364.14 | 0.433477E+09 |
March | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.684861E+09 | 98055494.83 |
April | 0.169125E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183409E+10 | 5255598.12 |
May | 0.174872E+10 | 0.163243E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258492E+10 | 1044314.95 |
June | 0.171530E+10 | 0.159501E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.236031E+10 | 665268.88 |
July | 0.172466E+10 | 0.160290E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187352E+10 | 197728.74 |
August | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160440E+10 | 700270.27 |
September | 0.169125E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140257E+10 | 1135849.53 |
October | 0.172174E+10 | 0.161274E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121296E+10 | 20245167.83 |
November | 0.165844E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.418614E+09 | 0.140390E+09 |
December | 0.172466E+10 | 0.160290E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2962475.78 | 0.899306E+09 |
Annual Sum or Average | 0.205167E+11 | 0.191205E+11 | 0.958644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140475E+11 | 0.260180E+10 |
Minimum of Months | 0.156756E+10 | 0.146111E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 197728.74 |
Maximum of Months | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258492E+10 | 0.100132E+10 |
Report: SpaceGainsMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.161274E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.987268E+09 |
February | 0.156756E+10 | 0.146111E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 68325502.74 | 0.427335E+09 |
March | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.684964E+09 | 96176793.45 |
April | 0.169125E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183415E+10 | 5136147.31 |
May | 0.174872E+10 | 0.163243E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258468E+10 | 1011902.08 |
June | 0.171530E+10 | 0.159501E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.236010E+10 | 667816.72 |
July | 0.172466E+10 | 0.160290E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187297E+10 | 194497.02 |
August | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160409E+10 | 717967.10 |
September | 0.169125E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140240E+10 | 1125012.30 |
October | 0.172174E+10 | 0.161274E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121287E+10 | 20175886.94 |
November | 0.165844E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.418633E+09 | 0.139116E+09 |
December | 0.172466E+10 | 0.160290E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2962711.75 | 0.889731E+09 |
Annual Sum or Average | 0.205167E+11 | 0.191205E+11 | 0.958644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140462E+11 | 0.256866E+10 |
Minimum of Months | 0.156756E+10 | 0.146111E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 194497.02 |
Maximum of Months | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258468E+10 | 0.987268E+09 |
Report: SpaceGainsMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.161274E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103733E+10 |
February | 0.156756E+10 | 0.146111E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 69156712.25 | 0.478938E+09 |
March | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.694555E+09 | 0.130418E+09 |
April | 0.169125E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187408E+10 | 8259231.76 |
May | 0.174872E+10 | 0.163243E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.266608E+10 | 2629964.00 |
June | 0.171530E+10 | 0.159501E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.242128E+10 | 1646335.41 |
July | 0.172466E+10 | 0.160290E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.193893E+10 | 671327.23 |
August | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.164188E+10 | 2064806.44 |
September | 0.169125E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142398E+10 | 3810556.59 |
October | 0.172174E+10 | 0.161274E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122207E+10 | 24886437.34 |
November | 0.165844E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.421365E+09 | 0.152605E+09 |
December | 0.172466E+10 | 0.160290E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2990079.98 | 0.936551E+09 |
Annual Sum or Average | 0.205167E+11 | 0.191205E+11 | 0.958644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143764E+11 | 0.277981E+10 |
Minimum of Months | 0.156756E+10 | 0.146111E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 671327.23 |
Maximum of Months | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.266608E+10 | 0.103733E+10 |
Report: PeakSpaceGainsMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 4050.04 | 01-JAN-13:09 | 4621.63 | 01-JAN-10:09 | 1343.25 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 4048.37 | 15-JAN-18:00 |
February | 4050.04 | 03-FEB-13:09 | 4621.63 | 01-FEB-10:09 | 1343.25 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1446.89 | 22-FEB-15:00 | 3557.47 | 10-FEB-18:00 |
March | 4050.04 | 03-MAR-13:09 | 4621.63 | 01-MAR-10:09 | 1343.25 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5081.39 | 28-MAR-15:00 | 1577.45 | 18-MAR-17:00 |
April | 4050.04 | 01-APR-12:09 | 4621.63 | 01-APR-09:09 | 1343.25 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7286.15 | 15-APR-15:00 | 292.96 | 10-APR-07:05 |
May | 4050.04 | 05-MAY-12:09 | 4621.63 | 01-MAY-09:09 | 1343.25 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8780.03 | 03-MAY-15:00 | 64.75 | 13-MAY-05:00 |
June | 4050.04 | 02-JUN-12:09 | 4621.63 | 01-JUN-09:09 | 1343.25 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8804.30 | 06-JUN-15:00 | 80.78 | 18-JUN-05:00 |
July | 4050.04 | 01-JUL-12:09 | 4621.63 | 01-JUL-09:09 | 1343.25 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7081.27 | 07-JUL-15:00 | 69.74 | 19-JUL-03:00 |
August | 4050.04 | 04-AUG-12:09 | 4621.63 | 01-AUG-09:09 | 1343.25 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5868.59 | 07-AUG-15:00 | 73.40 | 16-AUG-07:01 |
September | 4050.04 | 01-SEP-12:09 | 4621.63 | 01-SEP-09:09 | 1343.25 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5404.44 | 29-SEP-13:00 | 57.64 | 07-SEP-07:02 |
October | 4050.04 | 01-OCT-12:09 | 4621.63 | 01-OCT-09:09 | 1343.25 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5498.51 | 02-OCT-14:00 | 505.76 | 11-OCT-17:00 |
November | 4050.04 | 03-NOV-12:09 | 4621.63 | 01-NOV-09:09 | 1343.25 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2857.78 | 04-NOV-14:00 | 2233.31 | 30-NOV-18:00 |
December | 4050.04 | 01-DEC-13:09 | 4621.63 | 01-DEC-10:09 | 1343.25 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 323.63 | 28-DEC-14:00 | 4808.33 | 31-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 4050.04 | 4621.63 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.64 | |||||
Maximum of Months | 4050.04 | 4621.63 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 8804.30 | 4808.33 |
Report: PeakSpaceGainsMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 01-JAN-13:09 | 2827.07 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 2384.38 | 15-JAN-18:00 |
February | 2024.96 | 03-FEB-13:09 | 2827.07 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 823.06 | 22-FEB-15:00 | 2154.16 | 10-FEB-18:00 |
March | 2024.96 | 03-MAR-13:09 | 2827.07 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2904.53 | 28-MAR-15:00 | 894.17 | 18-MAR-17:00 |
April | 2024.96 | 01-APR-12:09 | 2827.07 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4077.77 | 15-APR-15:00 | 162.69 | 10-APR-07:05 |
May | 2024.96 | 05-MAY-12:09 | 2827.07 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4973.50 | 03-MAY-15:00 | 19.80 | 13-MAY-05:00 |
June | 2024.96 | 02-JUN-12:09 | 2827.07 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4981.85 | 07-JUN-16:00 | 24.41 | 18-JUN-05:00 |
July | 2024.96 | 01-JUL-12:09 | 2827.07 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4019.10 | 07-JUL-15:00 | 20.35 | 19-JUL-03:00 |
August | 2024.96 | 04-AUG-12:09 | 2827.07 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3322.37 | 07-AUG-15:00 | 32.48 | 16-AUG-07:01 |
September | 2024.96 | 01-SEP-12:09 | 2827.07 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3056.68 | 29-SEP-13:00 | 23.69 | 07-SEP-07:02 |
October | 2024.96 | 01-OCT-12:09 | 2827.07 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3124.74 | 02-OCT-14:00 | 286.69 | 11-OCT-17:00 |
November | 2024.96 | 03-NOV-12:09 | 2827.07 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1627.71 | 04-NOV-14:00 | 1272.85 | 30-NOV-18:00 |
December | 2024.96 | 01-DEC-13:09 | 2827.07 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 183.34 | 28-DEC-14:00 | 2780.92 | 31-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 2827.07 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.80 | |||||
Maximum of Months | 2024.96 | 2827.07 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 4981.85 | 2780.92 |
Report: PeakSpaceGainsMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 2555.22 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 2238.84 | 15-JAN-17:00 |
February | 2024.96 | 04-FEB-13:09 | 2555.22 | 01-FEB-09:09 | 671.63 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 823.06 | 22-FEB-15:00 | 2125.40 | 10-FEB-18:00 |
March | 2024.96 | 04-MAR-13:09 | 2555.22 | 01-MAR-09:09 | 671.63 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2904.53 | 28-MAR-15:00 | 894.17 | 18-MAR-17:00 |
April | 2024.96 | 01-APR-12:09 | 2555.22 | 01-APR-08:09 | 671.63 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4077.30 | 15-APR-15:00 | 168.48 | 22-APR-19:00 |
May | 2024.96 | 06-MAY-12:09 | 2555.22 | 01-MAY-08:09 | 671.63 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4973.44 | 03-MAY-15:00 | 23.25 | 15-MAY-03:00 |
June | 2024.96 | 03-JUN-12:09 | 2555.22 | 01-JUN-08:09 | 671.63 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4981.85 | 07-JUN-16:00 | 28.49 | 18-JUN-05:00 |
July | 2024.96 | 01-JUL-12:09 | 2555.22 | 01-JUL-08:09 | 671.63 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4019.10 | 07-JUL-15:00 | 22.16 | 19-JUL-03:00 |
August | 2024.96 | 05-AUG-12:09 | 2555.22 | 01-AUG-08:09 | 671.63 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3322.37 | 07-AUG-15:00 | 177.74 | 20-AUG-17:00 |
September | 2024.96 | 02-SEP-12:09 | 2555.22 | 01-SEP-08:09 | 671.63 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3056.77 | 29-SEP-13:00 | 92.38 | 03-SEP-17:00 |
October | 2024.96 | 07-OCT-12:09 | 2555.22 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3124.73 | 02-OCT-14:00 | 286.69 | 11-OCT-17:00 |
November | 2024.96 | 04-NOV-12:09 | 2555.22 | 01-NOV-08:09 | 671.63 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1627.71 | 04-NOV-14:00 | 1272.84 | 30-NOV-18:00 |
December | 2024.96 | 02-DEC-13:09 | 2555.22 | 01-DEC-09:09 | 671.63 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 183.34 | 28-DEC-14:00 | 2706.13 | 21-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 2555.22 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.16 | |||||
Maximum of Months | 2024.96 | 2555.22 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 4981.85 | 2706.13 |
Report: PeakSpaceGainsMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 2555.22 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 2211.74 | 15-JAN-17:00 |
February | 2024.96 | 04-FEB-13:09 | 2555.22 | 01-FEB-09:09 | 671.63 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 823.06 | 22-FEB-15:00 | 2105.10 | 10-FEB-18:00 |
March | 2024.96 | 04-MAR-13:09 | 2555.22 | 01-MAR-09:09 | 671.63 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2904.53 | 28-MAR-15:00 | 894.17 | 18-MAR-17:00 |
April | 2024.96 | 01-APR-12:09 | 2555.22 | 01-APR-08:09 | 671.63 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4077.31 | 15-APR-15:00 | 168.73 | 22-APR-19:00 |
May | 2024.96 | 06-MAY-12:09 | 2555.22 | 01-MAY-08:09 | 671.63 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4973.44 | 03-MAY-15:00 | 24.97 | 15-MAY-03:00 |
June | 2024.96 | 03-JUN-12:09 | 2555.22 | 01-JUN-08:09 | 671.63 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4981.85 | 07-JUN-16:00 | 30.48 | 18-JUN-07:01 |
July | 2024.96 | 01-JUL-12:09 | 2555.22 | 01-JUL-08:09 | 671.63 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4019.10 | 07-JUL-15:00 | 22.64 | 19-JUL-03:00 |
August | 2024.96 | 05-AUG-12:09 | 2555.22 | 01-AUG-08:09 | 671.63 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3322.37 | 07-AUG-15:00 | 182.39 | 20-AUG-17:00 |
September | 2024.96 | 02-SEP-12:09 | 2555.22 | 01-SEP-08:09 | 671.63 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3056.76 | 29-SEP-13:00 | 99.17 | 03-SEP-17:00 |
October | 2024.96 | 07-OCT-12:09 | 2555.22 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3124.71 | 02-OCT-14:00 | 286.69 | 11-OCT-17:00 |
November | 2024.96 | 04-NOV-12:09 | 2555.22 | 01-NOV-08:09 | 671.63 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1627.71 | 04-NOV-14:00 | 1272.84 | 30-NOV-18:00 |
December | 2024.96 | 02-DEC-13:09 | 2555.22 | 01-DEC-09:09 | 671.63 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 183.34 | 28-DEC-14:00 | 2685.88 | 21-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 2555.22 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.64 | |||||
Maximum of Months | 2024.96 | 2555.22 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 4981.85 | 2685.88 |
Report: PeakSpaceGainsMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 2555.22 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 2178.04 | 01-JAN-18:00 |
February | 2024.96 | 04-FEB-13:09 | 2555.22 | 01-FEB-09:09 | 671.63 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 823.06 | 22-FEB-15:00 | 2060.42 | 10-FEB-18:00 |
March | 2024.96 | 04-MAR-13:09 | 2555.22 | 01-MAR-09:09 | 671.63 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2904.53 | 28-MAR-15:00 | 894.17 | 18-MAR-17:00 |
April | 2024.96 | 01-APR-12:09 | 2555.22 | 01-APR-08:09 | 671.63 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4077.32 | 15-APR-15:00 | 163.86 | 22-APR-19:00 |
May | 2024.96 | 06-MAY-12:09 | 2555.22 | 01-MAY-08:09 | 671.63 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4973.44 | 03-MAY-15:00 | 23.90 | 15-MAY-03:00 |
June | 2024.96 | 03-JUN-12:09 | 2555.22 | 01-JUN-08:09 | 671.63 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4981.86 | 07-JUN-16:00 | 28.86 | 18-JUN-05:00 |
July | 2024.96 | 01-JUL-12:09 | 2555.22 | 01-JUL-08:09 | 671.63 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4019.10 | 07-JUL-15:00 | 21.74 | 19-JUL-03:00 |
August | 2024.96 | 05-AUG-12:09 | 2555.22 | 01-AUG-08:09 | 671.63 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3322.37 | 07-AUG-15:00 | 170.10 | 20-AUG-17:00 |
September | 2024.96 | 02-SEP-12:09 | 2555.22 | 01-SEP-08:09 | 671.63 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3056.78 | 29-SEP-13:00 | 87.52 | 03-SEP-17:00 |
October | 2024.96 | 07-OCT-12:09 | 2555.22 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3124.72 | 02-OCT-14:00 | 286.69 | 11-OCT-17:00 |
November | 2024.96 | 04-NOV-12:09 | 2555.22 | 01-NOV-08:09 | 671.63 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1627.71 | 04-NOV-14:00 | 1272.84 | 30-NOV-18:00 |
December | 2024.96 | 02-DEC-13:09 | 2555.22 | 01-DEC-09:09 | 671.63 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 183.34 | 28-DEC-14:00 | 2644.44 | 21-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 2555.22 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.74 | |||||
Maximum of Months | 2024.96 | 2555.22 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 4981.86 | 2644.44 |
Report: PeakSpaceGainsMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 5400.05 | 07-JAN-15:09 | 2726.96 | 01-JAN-11:09 | 1343.25 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 3811.12 | 01-JAN-18:00 |
February | 5400.05 | 04-FEB-15:09 | 2726.96 | 01-FEB-10:09 | 1343.25 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1440.86 | 22-FEB-15:00 | 3458.78 | 10-FEB-18:00 |
March | 5400.05 | 04-MAR-15:09 | 2726.96 | 01-MAR-10:09 | 1343.25 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5081.39 | 28-MAR-15:00 | 1566.20 | 18-MAR-17:00 |
April | 5400.05 | 01-APR-14:09 | 2726.96 | 01-APR-09:09 | 1343.25 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7155.26 | 15-APR-15:00 | 286.06 | 10-APR-07:05 |
May | 5400.05 | 06-MAY-14:09 | 2726.96 | 01-MAY-09:09 | 1343.25 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8712.15 | 03-MAY-15:00 | 44.73 | 15-MAY-03:00 |
June | 5400.05 | 03-JUN-14:09 | 2726.96 | 01-JUN-09:09 | 1343.25 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8728.05 | 07-JUN-16:00 | 109.23 | 18-JUN-07:01 |
July | 5400.05 | 01-JUL-14:09 | 2726.96 | 01-JUL-09:09 | 1343.25 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7038.45 | 07-JUL-15:00 | 39.93 | 19-JUL-03:00 |
August | 5400.05 | 05-AUG-14:09 | 2726.96 | 01-AUG-09:09 | 1343.25 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5820.44 | 07-AUG-15:00 | 257.90 | 20-AUG-17:00 |
September | 5400.05 | 02-SEP-14:09 | 2726.96 | 01-SEP-09:09 | 1343.25 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5355.70 | 29-SEP-13:00 | 115.37 | 03-SEP-17:00 |
October | 5400.05 | 07-OCT-14:09 | 2726.96 | 01-OCT-10:09 | 1343.25 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5470.99 | 02-OCT-14:00 | 502.15 | 11-OCT-17:00 |
November | 5400.05 | 04-NOV-14:09 | 2726.96 | 01-NOV-09:09 | 1343.25 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2849.04 | 04-NOV-14:00 | 2227.74 | 30-NOV-18:00 |
December | 5400.05 | 02-DEC-15:09 | 2726.96 | 01-DEC-10:09 | 1343.25 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 321.45 | 28-DEC-14:00 | 4523.31 | 21-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 5400.05 | 2726.96 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.93 | |||||
Maximum of Months | 5400.05 | 2726.96 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 8728.05 | 4523.31 |
Report: PeakSpaceGainsMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1404.46 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 2178.04 | 01-JAN-18:00 |
February | 2699.95 | 04-FEB-15:09 | 1404.46 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 823.04 | 22-FEB-15:00 | 1952.95 | 10-FEB-18:00 |
March | 2699.95 | 04-MAR-15:09 | 1404.46 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2904.53 | 28-MAR-15:00 | 894.17 | 18-MAR-17:00 |
April | 2699.95 | 01-APR-14:09 | 1404.46 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4077.51 | 15-APR-15:00 | 162.52 | 10-APR-07:05 |
May | 2699.95 | 06-MAY-14:09 | 1404.46 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4973.44 | 03-MAY-15:00 | 22.19 | 15-MAY-03:00 |
June | 2699.95 | 03-JUN-14:09 | 1404.46 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4981.83 | 07-JUN-16:00 | 58.05 | 18-JUN-07:01 |
July | 2699.95 | 01-JUL-14:09 | 1404.46 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4019.10 | 07-JUL-15:00 | 19.41 | 19-JUL-03:00 |
August | 2699.95 | 05-AUG-14:09 | 1404.46 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3322.38 | 07-AUG-15:00 | 124.44 | 20-AUG-17:00 |
September | 2699.95 | 02-SEP-14:09 | 1404.46 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3057.05 | 29-SEP-13:00 | 44.10 | 04-SEP-07:01 |
October | 2699.95 | 07-OCT-14:09 | 1404.46 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3124.60 | 02-OCT-14:00 | 286.69 | 11-OCT-17:00 |
November | 2699.95 | 04-NOV-14:09 | 1404.46 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1627.69 | 04-NOV-14:00 | 1272.84 | 30-NOV-18:00 |
December | 2699.95 | 02-DEC-15:09 | 1404.46 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 183.50 | 28-DEC-14:00 | 2570.50 | 21-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.41 | |||||
Maximum of Months | 2699.95 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 4981.83 | 2570.50 |
Report: PeakSpaceGainsMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1404.46 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 2178.04 | 01-JAN-18:00 |
February | 2699.95 | 04-FEB-15:09 | 1404.46 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 823.03 | 22-FEB-15:00 | 1936.21 | 10-FEB-18:00 |
March | 2699.95 | 04-MAR-15:09 | 1404.46 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2904.53 | 28-MAR-15:00 | 894.17 | 18-MAR-17:00 |
April | 2699.95 | 01-APR-14:09 | 1404.46 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4077.51 | 15-APR-15:00 | 162.37 | 10-APR-07:05 |
May | 2699.95 | 06-MAY-14:09 | 1404.46 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4973.44 | 03-MAY-15:00 | 22.05 | 15-MAY-03:00 |
June | 2699.95 | 03-JUN-14:09 | 1404.46 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4981.83 | 07-JUN-16:00 | 57.37 | 18-JUN-07:01 |
July | 2699.95 | 01-JUL-14:09 | 1404.46 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4019.10 | 07-JUL-15:00 | 19.28 | 19-JUL-03:00 |
August | 2699.95 | 05-AUG-14:09 | 1404.46 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3322.38 | 07-AUG-15:00 | 121.82 | 20-AUG-17:00 |
September | 2699.95 | 02-SEP-14:09 | 1404.46 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3057.05 | 29-SEP-13:00 | 43.74 | 04-SEP-07:01 |
October | 2699.95 | 07-OCT-14:09 | 1404.46 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3124.60 | 02-OCT-14:00 | 286.69 | 11-OCT-17:00 |
November | 2699.95 | 04-NOV-14:09 | 1404.46 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1627.69 | 04-NOV-14:00 | 1272.84 | 30-NOV-18:00 |
December | 2699.95 | 02-DEC-15:09 | 1404.46 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 183.50 | 28-DEC-14:00 | 2557.97 | 21-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.28 | |||||
Maximum of Months | 2699.95 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 4981.83 | 2557.97 |
Report: PeakSpaceGainsMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1404.46 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 2178.04 | 01-JAN-18:00 |
February | 2699.95 | 04-FEB-15:09 | 1404.46 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 823.03 | 22-FEB-15:00 | 1891.65 | 10-FEB-18:00 |
March | 2699.95 | 04-MAR-15:09 | 1404.46 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2904.53 | 28-MAR-15:00 | 894.17 | 18-MAR-17:00 |
April | 2699.95 | 01-APR-14:09 | 1404.46 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4077.51 | 15-APR-15:00 | 161.81 | 10-APR-07:05 |
May | 2699.95 | 06-MAY-14:09 | 1404.46 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4973.44 | 03-MAY-15:00 | 21.87 | 15-MAY-03:00 |
June | 2699.95 | 03-JUN-14:09 | 1404.46 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4981.83 | 07-JUN-16:00 | 57.10 | 18-JUN-07:01 |
July | 2699.95 | 01-JUL-14:09 | 1404.46 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4019.10 | 07-JUL-15:00 | 19.11 | 19-JUL-03:00 |
August | 2699.95 | 05-AUG-14:09 | 1404.46 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3322.38 | 07-AUG-15:00 | 126.37 | 20-AUG-17:00 |
September | 2699.95 | 02-SEP-14:09 | 1404.46 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3057.05 | 29-SEP-13:00 | 46.85 | 03-SEP-17:00 |
October | 2699.95 | 07-OCT-14:09 | 1404.46 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3124.59 | 02-OCT-14:00 | 286.69 | 11-OCT-17:00 |
November | 2699.95 | 04-NOV-14:09 | 1404.46 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1627.69 | 04-NOV-14:00 | 1272.83 | 30-NOV-18:00 |
December | 2699.95 | 02-DEC-15:09 | 1404.46 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 183.50 | 28-DEC-14:00 | 2521.69 | 21-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.11 | |||||
Maximum of Months | 2699.95 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 4981.83 | 2521.69 |
Report: PeakSpaceGainsMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1404.46 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 2182.29 | 01-JAN-18:00 |
February | 2699.95 | 04-FEB-15:09 | 1404.46 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 829.04 | 22-FEB-15:00 | 1804.63 | 10-FEB-18:00 |
March | 2699.95 | 04-MAR-15:09 | 1404.46 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2904.53 | 28-MAR-15:00 | 905.42 | 18-MAR-17:00 |
April | 2699.95 | 01-APR-14:09 | 1404.46 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4207.96 | 15-APR-15:00 | 193.07 | 22-APR-18:10 |
May | 2699.95 | 06-MAY-14:09 | 1404.46 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5040.73 | 03-MAY-15:00 | 56.35 | 15-MAY-03:00 |
June | 2699.95 | 03-JUN-14:09 | 1404.46 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5080.09 | 06-JUN-15:00 | 71.91 | 18-JUN-07:01 |
July | 2699.95 | 01-JUL-14:09 | 1404.46 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4061.93 | 07-JUL-15:00 | 49.83 | 19-JUL-03:00 |
August | 2699.95 | 05-AUG-14:09 | 1404.46 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3370.53 | 07-AUG-15:00 | 238.99 | 20-AUG-17:00 |
September | 2699.95 | 02-SEP-14:09 | 1404.46 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3105.82 | 29-SEP-13:00 | 144.51 | 03-SEP-17:00 |
October | 2699.95 | 07-OCT-14:09 | 1404.46 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3151.79 | 02-OCT-14:00 | 290.29 | 11-OCT-17:00 |
November | 2699.95 | 04-NOV-14:09 | 1404.46 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1636.40 | 04-NOV-14:00 | 1278.40 | 30-NOV-18:00 |
December | 2699.95 | 02-DEC-15:09 | 1404.46 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 185.80 | 28-DEC-14:00 | 2505.72 | 21-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.83 | |||||
Maximum of Months | 2699.95 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 5080.09 | 2505.72 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6864.43 | 03-JAN-08:02 | 3037.53 | 675.00 | 671.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1077.31 |
February | 11187.38 | 22-FEB-15:00 | 2700.03 | 4621.63 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 1446.89 | 0.00 |
March | 26714.43 | 11-MAR-08:62 | 0.00 | 300.00 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 30.02 | 0.00 |
April | 53129.71 | 28-APR-07:02 | 0.00 | 450.00 | 441.83 | 0.00 | 0.00 | 0.00 | 0.00 | 341.39 | 0.00 |
May | 54543.85 | 06-MAY-07:01 | 0.00 | 600.00 | 589.11 | 0.00 | 0.00 | 0.00 | 0.00 | 303.55 | 0.00 |
June | 50625.16 | 07-JUN-07:01 | 3375.03 | 750.00 | 746.25 | 0.00 | 0.00 | 0.00 | 0.00 | 609.36 | 0.00 |
July | 42420.90 | 07-JUL-07:01 | 0.00 | 750.00 | 736.39 | 0.00 | 0.00 | 0.00 | 0.00 | 476.96 | 0.00 |
August | 40658.02 | 03-AUG-07:01 | 3037.53 | 675.00 | 671.62 | 0.00 | 0.00 | 0.00 | 0.00 | 173.93 | 0.00 |
September | 43463.13 | 26-SEP-07:01 | 2362.52 | 525.00 | 522.37 | 0.00 | 0.00 | 0.00 | 0.00 | 51.93 | 0.00 |
October | 46708.13 | 05-OCT-07:02 | 1687.52 | 375.00 | 373.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.42 |
November | 14693.84 | 08-NOV-15:00 | 2700.03 | 4621.63 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 2680.95 | 0.00 |
December | 8875.49 | 01-DEC-14:00 | 4050.04 | 4621.63 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 181.30 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 6864.43 | 0.00 | 300.00 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 54543.85 | 4050.04 | 4621.63 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 2680.95 | 1077.31 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4014.47 | 12-JAN-15:00 | 1349.97 | 2827.07 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.16 |
February | 6053.36 | 22-FEB-15:00 | 1349.97 | 2827.07 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 823.06 | 0.00 |
March | 16104.56 | 11-MAR-08:62 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 15.81 | 0.00 |
April | 27348.19 | 30-APR-07:02 | 1012.48 | 225.00 | 223.88 | 0.00 | 0.00 | 0.00 | 0.00 | 1.57 | 0.00 |
May | 27801.97 | 06-MAY-07:01 | 0.00 | 300.00 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 171.51 | 0.00 |
June | 26486.26 | 07-JUN-07:01 | 1687.47 | 375.00 | 373.13 | 0.00 | 0.00 | 0.00 | 0.00 | 333.09 | 0.00 |
July | 24112.75 | 07-JUL-07:01 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 268.95 | 0.00 |
August | 23082.09 | 03-AUG-07:01 | 1518.72 | 337.50 | 335.81 | 0.00 | 0.00 | 0.00 | 0.00 | 105.16 | 0.00 |
September | 24860.05 | 26-SEP-07:01 | 1181.23 | 262.50 | 261.19 | 0.00 | 0.00 | 0.00 | 0.00 | 35.67 | 0.00 |
October | 26004.43 | 02-OCT-07:02 | 1012.48 | 225.00 | 223.88 | 0.00 | 0.00 | 0.00 | 0.00 | 22.13 | 0.00 |
November | 8274.98 | 09-NOV-08:63 | 506.24 | 112.50 | 111.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 156.02 |
December | 5090.85 | 02-DEC-14:00 | 2024.96 | 2827.07 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 52.91 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4014.47 | 0.00 | 112.50 | 111.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 27801.97 | 2024.96 | 2827.07 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 823.06 | 156.02 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3576.99 | 12-JAN-15:00 | 1012.48 | 2555.22 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.15 |
February | 5734.69 | 22-FEB-14:00 | 1349.97 | 2555.22 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 797.43 | 0.00 |
March | 17635.18 | 30-MAR-06:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.31 |
April | 28213.10 | 20-APR-06:01 | 0.00 | 262.50 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 2.77 | 0.00 |
May | 28266.52 | 06-MAY-06:01 | 0.00 | 300.00 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 4.44 | 0.00 |
June | 25548.86 | 12-JUN-06:01 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 17.02 | 0.00 |
July | 21170.60 | 01-JUL-06:01 | 0.00 | 337.50 | 331.38 | 0.00 | 0.00 | 0.00 | 0.00 | 5.37 | 0.00 |
August | 18542.44 | 03-AUG-06:01 | 0.00 | 300.00 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 3.59 | 0.00 |
September | 21392.79 | 27-SEP-06:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.73 |
October | 25208.11 | 02-OCT-06:01 | 0.00 | 262.50 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.24 |
November | 7736.74 | 04-NOV-13:00 | 2024.96 | 2555.22 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1578.97 | 0.00 |
December | 4903.21 | 02-DEC-14:00 | 2024.96 | 2555.22 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 52.91 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3576.99 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 28266.52 | 2024.96 | 2555.22 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1578.97 | 78.15 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3647.11 | 03-JAN-07:04 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.93 |
February | 5658.62 | 22-FEB-14:00 | 1349.97 | 2555.22 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 797.43 | 0.00 |
March | 17849.64 | 30-MAR-06:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.31 |
April | 28325.15 | 20-APR-06:01 | 0.00 | 262.50 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 2.64 | 0.00 |
May | 28369.56 | 06-MAY-06:01 | 0.00 | 300.00 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 | 0.00 |
June | 25874.41 | 12-JUN-06:01 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 16.52 | 0.00 |
July | 21326.27 | 01-JUL-06:01 | 0.00 | 337.50 | 331.38 | 0.00 | 0.00 | 0.00 | 0.00 | 5.23 | 0.00 |
August | 18663.79 | 03-AUG-06:01 | 0.00 | 300.00 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 3.48 | 0.00 |
September | 21501.24 | 27-SEP-06:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.76 |
October | 25599.30 | 23-OCT-06:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.96 |
November | 7720.08 | 04-NOV-13:00 | 2024.96 | 2555.22 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1578.97 | 0.00 |
December | 4831.44 | 02-DEC-14:00 | 2024.96 | 2555.22 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 52.91 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3647.11 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 28369.56 | 2024.96 | 2555.22 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1578.97 | 7.93 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3806.29 | 03-JAN-07:04 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.99 |
February | 5473.07 | 22-FEB-14:00 | 1349.97 | 2555.22 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 797.43 | 0.00 |
March | 16330.20 | 30-MAR-06:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.31 |
April | 28015.82 | 20-APR-06:01 | 0.00 | 262.50 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 0.00 |
May | 28158.06 | 06-MAY-06:01 | 0.00 | 300.00 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 4.49 | 0.00 |
June | 25699.60 | 12-JUN-06:01 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 16.58 | 0.00 |
July | 21033.28 | 01-JUL-06:01 | 0.00 | 337.50 | 331.38 | 0.00 | 0.00 | 0.00 | 0.00 | 5.43 | 0.00 |
August | 18382.41 | 03-AUG-06:01 | 0.00 | 300.00 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 3.70 | 0.00 |
September | 21252.55 | 27-SEP-06:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.70 |
October | 25199.62 | 02-OCT-06:01 | 0.00 | 262.50 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.24 |
November | 7555.94 | 04-NOV-13:00 | 2024.96 | 2555.22 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1578.97 | 0.00 |
December | 4645.45 | 02-DEC-14:00 | 2024.96 | 2555.22 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 52.91 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3806.29 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 28158.06 | 2024.96 | 2555.22 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1578.97 | 7.99 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7002.83 | 04-JAN-08:03 | 0.00 | 525.00 | 515.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1049.08 |
February | 9753.02 | 22-FEB-15:10 | 4657.54 | 2726.96 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 1397.19 | 0.00 |
March | 24856.09 | 11-MAR-08:62 | 0.00 | 300.00 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 30.28 | 0.00 |
April | 49262.49 | 20-APR-07:02 | 0.00 | 450.00 | 441.83 | 0.00 | 0.00 | 0.00 | 0.00 | 138.71 | 0.00 |
May | 50594.15 | 29-MAY-08:61 | 0.00 | 750.00 | 736.39 | 0.00 | 0.00 | 0.00 | 0.00 | 419.80 | 0.00 |
June | 46099.07 | 07-JUN-07:01 | 0.00 | 750.00 | 736.39 | 0.00 | 0.00 | 0.00 | 0.00 | 577.24 | 0.00 |
July | 39789.92 | 07-JUL-07:01 | 0.00 | 750.00 | 736.39 | 0.00 | 0.00 | 0.00 | 0.00 | 448.85 | 0.00 |
August | 36291.93 | 08-AUG-07:01 | 0.00 | 750.00 | 736.39 | 0.00 | 0.00 | 0.00 | 0.00 | 260.63 | 0.00 |
September | 40127.48 | 27-SEP-07:02 | 0.00 | 450.00 | 441.83 | 0.00 | 0.00 | 0.00 | 0.00 | 17.06 | 0.00 |
October | 44265.26 | 02-OCT-07:02 | 0.00 | 450.00 | 441.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.60 |
November | 13753.78 | 04-NOV-14:20 | 5400.05 | 2726.96 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 2832.63 | 0.00 |
December | 7894.86 | 02-DEC-14:30 | 5197.55 | 2726.96 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 46.92 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 7002.83 | 0.00 | 300.00 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 50594.15 | 5400.05 | 2726.96 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 2832.63 | 1049.08 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3510.94 | 04-JAN-08:03 | 0.00 | 262.50 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 601.58 |
February | 5092.90 | 22-FEB-15:10 | 2328.71 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 798.03 | 0.00 |
March | 11842.67 | 11-MAR-08:62 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 17.39 | 0.00 |
April | 25806.99 | 20-APR-07:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 83.28 | 0.00 |
May | 26476.01 | 29-MAY-08:61 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 237.02 | 0.00 |
June | 24127.13 | 07-JUN-07:01 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 331.30 | 0.00 |
July | 20847.23 | 07-JUL-07:01 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 259.46 | 0.00 |
August | 19013.36 | 08-AUG-07:01 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 151.80 | 0.00 |
September | 20974.69 | 27-SEP-07:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 14.43 | 0.00 |
October | 23108.85 | 02-OCT-07:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.97 | 0.00 |
November | 7243.05 | 04-NOV-14:20 | 2699.95 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1618.39 | 0.00 |
December | 4066.29 | 02-DEC-14:30 | 2598.70 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 26.82 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3510.94 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 26476.01 | 2699.95 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1618.39 | 601.58 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3495.01 | 04-JAN-08:03 | 0.00 | 262.50 | 257.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 598.85 |
February | 5035.00 | 22-FEB-15:10 | 2328.71 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 798.03 | 0.00 |
March | 11436.43 | 11-MAR-08:62 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 17.52 | 0.00 |
April | 25733.14 | 20-APR-07:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 84.13 | 0.00 |
May | 26411.05 | 29-MAY-08:61 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 236.88 | 0.00 |
June | 24066.66 | 07-JUN-07:01 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 331.68 | 0.00 |
July | 20786.38 | 07-JUL-07:01 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 259.75 | 0.00 |
August | 18959.14 | 08-AUG-07:01 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 152.00 | 0.00 |
September | 20905.74 | 27-SEP-07:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 14.95 | 0.00 |
October | 23055.84 | 02-OCT-07:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 1.15 | 0.00 |
November | 7197.07 | 04-NOV-14:20 | 2699.95 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1618.39 | 0.00 |
December | 4012.67 | 02-DEC-14:30 | 2598.70 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 26.82 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3495.01 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 26411.05 | 2699.95 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1618.39 | 598.85 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3517.22 | 05-JAN-08:03 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 614.17 |
February | 4924.70 | 22-FEB-15:10 | 2328.71 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 798.03 | 0.00 |
March | 10145.72 | 30-MAR-07:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.96 |
April | 25755.86 | 20-APR-07:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 86.65 | 0.00 |
May | 26533.25 | 29-MAY-08:61 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 235.41 | 0.00 |
June | 24224.10 | 07-JUN-07:01 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 329.49 | 0.00 |
July | 20971.86 | 07-JUL-07:01 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 257.31 | 0.00 |
August | 19153.89 | 08-AUG-07:01 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 149.41 | 0.00 |
September | 21012.56 | 27-SEP-07:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 14.85 | 0.00 |
October | 23158.61 | 02-OCT-07:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.63 | 0.00 |
November | 7156.35 | 04-NOV-14:20 | 2699.95 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1618.39 | 0.00 |
December | 3875.63 | 02-DEC-14:30 | 2598.70 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 26.82 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3517.22 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 26533.25 | 2699.95 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1618.39 | 614.17 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3674.83 | 05-JAN-08:03 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 603.37 |
February | 5574.83 | 22-FEB-14:00 | 2396.20 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 801.67 | 0.00 |
March | 9789.25 | 28-MAR-15:00 | 2328.71 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 2904.53 | 0.00 |
April | 28900.56 | 30-APR-08:62 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 67.63 | 0.00 |
May | 30423.71 | 29-MAY-08:61 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 268.02 | 0.00 |
June | 28593.35 | 12-JUN-07:01 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 329.88 | 0.00 |
July | 24630.00 | 07-JUL-07:01 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 258.33 | 0.00 |
August | 21700.47 | 09-AUG-07:01 | 0.00 | 337.50 | 331.38 | 0.00 | 0.00 | 0.00 | 0.00 | 136.98 | 0.00 |
September | 24261.97 | 27-SEP-07:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 14.54 | 0.00 |
October | 26320.19 | 02-OCT-07:02 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 2.73 | 0.00 |
November | 8054.25 | 04-NOV-14:10 | 2699.95 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1631.33 | 0.00 |
December | 4188.85 | 01-DEC-14:00 | 2396.20 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.80 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3674.83 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 30423.71 | 2699.95 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 2904.53 | 603.37 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.656818E+11 | 58753.74 | 14-JAN-14:50 | 0.624636E+10 | 124439.16 | 02-JAN-08:09 |
February | 0.661967E+11 | 67847.66 | 22-FEB-13:50 | 0.891882E+09 | 41703.11 | 02-FEB-08:09 |
March | 0.891128E+11 | 87068.91 | 28-MAR-15:00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 0.105547E+12 | 106314.06 | 16-APR-14:00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 0.130591E+12 | 123235.50 | 03-MAY-14:50 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 0.134889E+12 | 135646.39 | 10-JUN-15:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 0.137329E+12 | 134191.89 | 01-JUL-15:30 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.136268E+12 | 127113.72 | 27-AUG-14:39 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.119976E+12 | 114976.08 | 14-SEP-14:50 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 0.103775E+12 | 99668.49 | 03-OCT-13:50 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 0.823524E+11 | 79310.66 | 04-NOV-14:09 | 1295931.95 | 969.55 | 27-NOV-08:30 |
December | 0.683047E+11 | 61693.56 | 28-DEC-13:00 | 0.122417E+10 | 64875.33 | 23-DEC-08:09 |
Annual Sum or Average | 0.124002E+13 | 0.836370E+10 | ||||
Minimum of Months | 0.656818E+11 | 58753.74 | 0.00 | 0.00 | ||
Maximum of Months | 0.137329E+12 | 135646.39 | 0.624636E+10 | 124439.16 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.310073E+11 | 0.606628E+10 | 0.108325E+11 | 0.00 | 0.105703E+11 | 0.00 | 0.00 | 0.197176E+10 | 0.00 | 0.00 | 0.00 | 0.523373E+10 | 0.00 |
February | 0.280657E+11 | 0.516426E+10 | 0.980803E+10 | 0.00 | 0.949005E+10 | 0.00 | 0.00 | 0.897376E+10 | 0.00 | 0.00 | 0.00 | 0.469484E+10 | 0.00 |
March | 0.314703E+11 | 0.520718E+10 | 0.110075E+11 | 0.00 | 0.106642E+11 | 0.00 | 0.00 | 0.256286E+11 | 0.00 | 0.00 | 0.00 | 0.513511E+10 | 0.00 |
April | 0.300741E+11 | 0.453974E+10 | 0.105079E+11 | 0.00 | 0.103144E+11 | 0.00 | 0.00 | 0.452870E+11 | 0.00 | 0.00 | 0.00 | 0.482426E+10 | 0.00 |
May | 0.312330E+11 | 0.425226E+10 | 0.109147E+11 | 0.00 | 0.117016E+11 | 0.00 | 0.00 | 0.676201E+11 | 0.00 | 0.00 | 0.00 | 0.486939E+10 | 0.00 |
June | 0.304143E+11 | 0.387889E+10 | 0.106386E+11 | 0.00 | 0.121309E+11 | 0.00 | 0.00 | 0.731895E+11 | 0.00 | 0.00 | 0.00 | 0.463646E+10 | 0.00 |
July | 0.309042E+11 | 0.413661E+10 | 0.107945E+11 | 0.00 | 0.124779E+11 | 0.00 | 0.00 | 0.742903E+11 | 0.00 | 0.00 | 0.00 | 0.472528E+10 | 0.00 |
August | 0.314595E+11 | 0.449016E+10 | 0.110006E+11 | 0.00 | 0.124792E+11 | 0.00 | 0.00 | 0.720562E+11 | 0.00 | 0.00 | 0.00 | 0.478245E+10 | 0.00 |
September | 0.300847E+11 | 0.482390E+10 | 0.105148E+11 | 0.00 | 0.109271E+11 | 0.00 | 0.00 | 0.589317E+11 | 0.00 | 0.00 | 0.00 | 0.469391E+10 | 0.00 |
October | 0.310073E+11 | 0.550456E+10 | 0.108325E+11 | 0.00 | 0.105588E+11 | 0.00 | 0.00 | 0.409134E+11 | 0.00 | 0.00 | 0.00 | 0.495872E+10 | 0.00 |
November | 0.300409E+11 | 0.575900E+10 | 0.104978E+11 | 0.00 | 0.101601E+11 | 0.00 | 0.00 | 0.209732E+11 | 0.00 | 0.00 | 0.00 | 0.492136E+10 | 0.00 |
December | 0.309156E+11 | 0.622158E+10 | 0.108050E+11 | 0.00 | 0.104435E+11 | 0.00 | 0.00 | 0.473261E+10 | 0.00 | 0.00 | 0.00 | 0.518638E+10 | 0.00 |
Annual Sum or Average | 0.366677E+12 | 0.600444E+11 | 0.128154E+12 | 0.00 | 0.131918E+12 | 0.00 | 0.00 | 0.494568E+12 | 0.00 | 0.00 | 0.00 | 0.586619E+11 | 0.00 |
Minimum of Months | 0.280657E+11 | 0.387889E+10 | 0.980803E+10 | 0.00 | 0.949005E+10 | 0.00 | 0.00 | 0.197176E+10 | 0.00 | 0.00 | 0.00 | 0.463646E+10 | 0.00 |
Maximum of Months | 0.314703E+11 | 0.622158E+10 | 0.110075E+11 | 0.00 | 0.124792E+11 | 0.00 | 0.00 | 0.742903E+11 | 0.00 | 0.00 | 0.00 | 0.523373E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.624636E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.891882E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 1295931.95 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.122417E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.836370E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.624636E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 23459.17 | 01-JAN-11:09 | 5507.06 | 01-JAN-06:10 | 8059.50 | 01-JAN-11:09 | 0.00 | 9796.95 | 02-JAN-08:09 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 23459.17 | 01-FEB-10:09 | 5507.06 | 01-FEB-06:10 | 8059.50 | 01-FEB-10:09 | 0.00 | 8070.69 | 02-FEB-08:09 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 23459.17 | 01-MAR-10:09 | 5507.06 | 01-MAR-06:10 | 8059.50 | 01-MAR-10:09 | 0.00 | 7552.08 | 11-MAR-08:09 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 23459.17 | 01-APR-09:09 | 5507.06 | 01-APR-05:10 | 8059.50 | 01-APR-09:09 | 0.00 | 8966.04 | 17-APR-07:10 | 0.00 | 0.00 | 01-APR-00:10 |
May | 23459.17 | 01-MAY-09:09 | 5507.06 | 01-MAY-05:10 | 8059.50 | 01-MAY-09:09 | 0.00 | 11114.22 | 17-MAY-16:10 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 23459.17 | 01-JUN-09:09 | 5507.06 | 01-JUN-05:10 | 8059.50 | 01-JUN-09:09 | 0.00 | 13306.36 | 22-JUN-16:10 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 23459.17 | 01-JUL-09:09 | 5507.06 | 01-JUL-05:10 | 8059.50 | 01-JUL-09:09 | 0.00 | 13439.89 | 01-JUL-14:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 23459.17 | 01-AUG-09:09 | 5507.06 | 01-AUG-05:10 | 8059.50 | 01-AUG-09:09 | 0.00 | 12916.03 | 27-AUG-14:09 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 23459.17 | 01-SEP-09:09 | 5507.06 | 01-SEP-05:10 | 8059.50 | 01-SEP-09:09 | 0.00 | 10975.23 | 14-SEP-16:10 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 23459.17 | 01-OCT-10:09 | 5507.06 | 01-OCT-05:10 | 8059.50 | 01-OCT-10:09 | 0.00 | 8806.48 | 03-OCT-07:10 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 23459.17 | 01-NOV-09:09 | 5507.06 | 01-NOV-05:10 | 8059.50 | 01-NOV-09:09 | 0.00 | 7220.20 | 27-NOV-08:30 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 23459.17 | 01-DEC-10:09 | 5507.06 | 01-DEC-06:10 | 8059.50 | 01-DEC-10:09 | 0.00 | 8554.05 | 23-DEC-08:09 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||||
Minimum of Months | 23459.17 | 5507.06 | 8059.50 | 0.00 | 7220.20 | 0.00 | 0.00 | |||||
Maximum of Months | 23459.17 | 5507.06 | 8059.50 | 0.00 | 13439.89 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 12565.05 | 12-JAN-15:09 | 0.00 | 0.00 | 0.00 | 9745.77 | 05-JAN-14:30 | 0.00 |
February | 24007.83 | 22-FEB-13:00 | 0.00 | 0.00 | 0.00 | 7567.66 | 15-FEB-13:30 | 0.00 |
March | 43632.47 | 28-MAR-14:00 | 0.00 | 0.00 | 0.00 | 7564.70 | 02-MAR-13:39 | 0.00 |
April | 62520.25 | 16-APR-14:00 | 0.00 | 0.00 | 0.00 | 7550.39 | 13-APR-13:09 | 0.00 |
May | 76003.74 | 03-MAY-14:00 | 0.00 | 0.00 | 0.00 | 7543.00 | 05-MAY-13:00 | 0.00 |
June | 85981.95 | 10-JUN-15:00 | 0.00 | 0.00 | 0.00 | 7532.19 | 16-JUN-13:50 | 0.00 |
July | 84118.91 | 01-JUL-14:00 | 0.00 | 0.00 | 0.00 | 9635.47 | 25-JUL-13:09 | 0.00 |
August | 79439.00 | 27-AUG-14:09 | 0.00 | 0.00 | 0.00 | 9627.63 | 17-AUG-11:09 | 0.00 |
September | 68560.89 | 14-SEP-16:10 | 0.00 | 0.00 | 0.00 | 7527.18 | 13-SEP-14:30 | 0.00 |
October | 55163.91 | 03-OCT-14:09 | 0.00 | 0.00 | 0.00 | 9661.88 | 20-OCT-13:39 | 0.00 |
November | 33700.82 | 09-NOV-13:50 | 0.00 | 0.00 | 0.00 | 9617.01 | 02-NOV-19:49 | 0.00 |
December | 16646.62 | 28-DEC-13:00 | 0.00 | 0.00 | 0.00 | 9664.40 | 30-DEC-15:50 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 12565.05 | 0.00 | 0.00 | 0.00 | 7527.18 | 0.00 | ||
Maximum of Months | 85981.95 | 0.00 | 0.00 | 0.00 | 9745.77 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 58753.74 | 14-JAN-14:50 | 23459.17 | 8059.50 | 0.00 | 0.00 | 7199.93 | 0.00 | 0.00 | 10698.08 | 0.00 |
February | 67847.66 | 22-FEB-13:50 | 23459.17 | 8059.50 | 0.00 | 0.00 | 7199.93 | 0.00 | 0.00 | 23692.51 | 0.00 |
March | 87068.91 | 28-MAR-15:00 | 23459.17 | 8059.50 | 0.00 | 0.00 | 7199.93 | 0.00 | 0.00 | 42924.90 | 0.00 |
April | 106314.06 | 16-APR-14:00 | 23459.17 | 8059.50 | 0.00 | 0.00 | 8961.98 | 0.00 | 0.00 | 62520.25 | 0.00 |
May | 123235.50 | 03-MAY-14:50 | 23459.17 | 8059.50 | 0.00 | 0.00 | 10900.29 | 0.00 | 0.00 | 75390.57 | 0.00 |
June | 135646.39 | 10-JUN-15:00 | 23459.17 | 8059.50 | 0.00 | 0.00 | 12730.03 | 0.00 | 0.00 | 85981.95 | 0.00 |
July | 134191.89 | 01-JUL-15:30 | 23459.17 | 8059.50 | 0.00 | 0.00 | 13399.05 | 0.00 | 0.00 | 83860.12 | 0.00 |
August | 127113.72 | 27-AUG-14:39 | 23459.17 | 8059.50 | 0.00 | 0.00 | 12913.14 | 0.00 | 0.00 | 79373.05 | 0.00 |
September | 114976.08 | 14-SEP-14:50 | 23459.17 | 8059.50 | 0.00 | 0.00 | 10711.82 | 0.00 | 0.00 | 67323.02 | 0.00 |
October | 99668.49 | 03-OCT-13:50 | 23459.17 | 8059.50 | 0.00 | 0.00 | 7922.91 | 0.00 | 0.00 | 54794.07 | 0.00 |
November | 79310.66 | 04-NOV-14:09 | 23459.17 | 8059.50 | 0.00 | 0.00 | 7199.93 | 0.00 | 0.00 | 33518.19 | 0.00 |
December | 61693.56 | 28-DEC-13:00 | 23459.17 | 8059.50 | 0.00 | 0.00 | 7199.93 | 0.00 | 0.00 | 16646.62 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 58753.74 | 23459.17 | 8059.50 | 0.00 | 0.00 | 7199.93 | 0.00 | 0.00 | 10698.08 | 0.00 | |
Maximum of Months | 135646.39 | 23459.17 | 8059.50 | 0.00 | 0.00 | 13399.05 | 0.00 | 0.00 | 85981.95 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 124439.16 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 41703.11 | 02-FEB-08:09 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 969.55 | 27-NOV-08:30 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 64875.33 | 23-DEC-08:09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 124439.16 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.47 | 0.17 | 24.47 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 24.52 | 0.83 | 24.53 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.46 | 0.17 | 24.46 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 1.33 | 24.51 | 1.17 | 24.51 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 24.52 | 0.83 | 24.53 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 24.49 | 0.00 | 24.49 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 24.60 | 0.00 | 24.60 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 24.55 | 0.00 | 24.55 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.46 | 0.00 | 24.46 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 5.83 | 24.56 | 0.00 | 24.56 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 24.60 | 0.00 | 24.60 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 24.52 | 0.00 | 24.52 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 24.63 | 0.00 | 24.63 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 24.59 | 0.00 | 24.59 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.47 | 0.00 | 24.47 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 6.67 | 24.59 | 0.00 | 24.59 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 24.63 | 0.00 | 24.63 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 24.50 | 0.00 | 24.50 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 24.64 | 0.00 | 24.64 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 24.58 | 0.00 | 24.58 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.48 | 0.00 | 24.48 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 5.00 | 24.60 | 0.00 | 24.60 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 24.64 | 0.00 | 24.64 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.63 | 0.00 | 24.63 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 24.77 | 0.00 | 24.77 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 24.72 | 0.00 | 24.72 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.48 | 0.00 | 24.48 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 4.50 | 24.71 | 0.00 | 24.71 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 24.77 | 0.00 | 24.77 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.59 | 0.00 | 24.59 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 24.74 | 0.00 | 24.74 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 24.73 | 0.00 | 24.73 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.46 | 0.00 | 24.46 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 4.00 | 24.70 | 0.00 | 24.70 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 24.74 | 0.00 | 24.74 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.59 | 0.00 | 24.59 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 24.74 | 0.00 | 24.74 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 24.73 | 0.00 | 24.73 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.46 | 0.00 | 24.46 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 4.00 | 24.70 | 0.00 | 24.70 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 24.74 | 0.00 | 24.74 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.69 | 0.00 | 24.69 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 24.74 | 0.00 | 24.74 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 24.75 | 0.00 | 24.75 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.52 | 0.00 | 24.52 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 3.83 | 24.73 | 0.00 | 24.73 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 24.75 | 0.00 | 24.75 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.46 | 0.00 | 24.46 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 25.72 | 0.00 | 25.72 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 25.29 | 0.00 | 25.29 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 24.76 | 0.00 | 24.76 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.55 | 0.00 | 24.55 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 6.67 | 25.13 | 0.00 | 25.13 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 25.72 | 0.00 | 25.72 |
Report: ComfortReportSimple55Monthly
For: LGSTORE1
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 366.33 | 22.56 | 8.17 | 22.59 | 0.33 | 22.59 |
February | 139.50 | 22.64 | 86.17 | 23.12 | 0.00 | 23.12 |
March | 36.33 | 23.24 | 297.33 | 23.82 | 0.00 | 23.82 |
April | 2.83 | 23.83 | 422.83 | 23.89 | 0.00 | 23.89 |
May | 24.33 | 23.90 | 496.00 | 23.89 | 24.33 | 23.89 |
June | 138.00 | 23.89 | 481.00 | 23.89 | 138.00 | 23.89 |
July | 374.17 | 23.89 | 495.00 | 23.89 | 374.17 | 23.89 |
August | 410.67 | 23.89 | 497.00 | 23.89 | 410.67 | 23.89 |
September | 264.83 | 23.89 | 479.00 | 23.89 | 264.83 | 23.89 |
October | 7.17 | 23.81 | 477.17 | 23.89 | 6.17 | 23.89 |
November | 40.33 | 23.18 | 303.50 | 23.81 | 0.00 | 23.81 |
December | 229.17 | 22.64 | 44.33 | 22.84 | 0.00 | 22.84 |
Annual Sum or Average | 2033.67 | 23.40 | 4087.50 | 23.73 | 1218.50 | 23.76 |
Minimum of Months | 2.83 | 22.56 | 8.17 | 22.59 | 0.00 | 22.59 |
Maximum of Months | 410.67 | 23.90 | 497.00 | 23.89 | 410.67 | 23.89 |
Report: ComfortReportSimple55Monthly
For: SMSTORE1
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 259.83 | 22.94 | 10.50 | 22.98 | 0.00 | 22.98 |
February | 94.00 | 22.94 | 83.83 | 23.39 | 0.00 | 23.39 |
March | 25.33 | 23.47 | 273.67 | 23.85 | 0.00 | 23.85 |
April | 1.67 | 23.80 | 394.83 | 23.89 | 0.00 | 23.89 |
May | 16.33 | 23.89 | 496.00 | 23.89 | 16.33 | 23.89 |
June | 109.67 | 23.89 | 481.00 | 23.89 | 109.67 | 23.89 |
July | 292.33 | 23.89 | 495.00 | 23.89 | 292.33 | 23.89 |
August | 323.83 | 23.89 | 497.00 | 23.89 | 323.83 | 23.89 |
September | 195.83 | 23.89 | 479.00 | 23.89 | 195.83 | 23.89 |
October | 2.83 | 23.76 | 450.00 | 23.89 | 1.67 | 23.89 |
November | 29.50 | 23.40 | 260.67 | 23.84 | 0.00 | 23.84 |
December | 155.00 | 23.01 | 46.67 | 23.22 | 0.00 | 23.22 |
Annual Sum or Average | 1506.17 | 23.56 | 3968.17 | 23.80 | 939.67 | 23.81 |
Minimum of Months | 1.67 | 22.94 | 10.50 | 22.98 | 0.00 | 22.98 |
Maximum of Months | 323.83 | 23.89 | 497.00 | 23.89 | 323.83 | 23.89 |
Report: ComfortReportSimple55Monthly
For: SMSTORE2
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 249.33 | 22.67 | 8.00 | 22.71 | 0.00 | 22.71 |
February | 82.83 | 22.66 | 68.50 | 23.29 | 0.00 | 23.29 |
March | 20.17 | 23.48 | 248.00 | 24.05 | 0.50 | 24.06 |
April | 7.67 | 28.21 | 317.17 | 24.27 | 7.50 | 24.36 |
May | 38.00 | 26.20 | 375.00 | 24.37 | 38.00 | 24.52 |
June | 132.67 | 24.64 | 366.00 | 24.31 | 132.67 | 24.38 |
July | 298.00 | 24.24 | 369.00 | 24.20 | 298.00 | 24.21 |
August | 335.50 | 24.17 | 379.00 | 24.15 | 335.50 | 24.16 |
September | 216.00 | 24.25 | 360.00 | 24.17 | 216.00 | 24.19 |
October | 12.00 | 25.85 | 360.67 | 24.15 | 12.00 | 24.20 |
November | 21.00 | 23.15 | 233.33 | 23.95 | 0.00 | 23.95 |
December | 136.33 | 22.72 | 27.67 | 22.93 | 0.00 | 22.93 |
Annual Sum or Average | 1549.50 | 23.84 | 3112.33 | 24.04 | 1040.17 | 24.10 |
Minimum of Months | 7.67 | 22.66 | 8.00 | 22.71 | 0.00 | 22.71 |
Maximum of Months | 335.50 | 28.21 | 379.00 | 24.37 | 335.50 | 24.52 |
Report: ComfortReportSimple55Monthly
For: SMSTORE3
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 274.50 | 22.68 | 6.50 | 22.71 | 0.00 | 22.71 |
February | 88.00 | 22.65 | 64.17 | 23.24 | 0.00 | 23.24 |
March | 20.50 | 23.45 | 245.67 | 24.05 | 0.50 | 24.06 |
April | 7.67 | 28.23 | 318.00 | 24.27 | 7.50 | 24.36 |
May | 37.33 | 26.24 | 375.00 | 24.37 | 37.33 | 24.53 |
June | 131.17 | 24.65 | 366.00 | 24.31 | 131.17 | 24.38 |
July | 296.33 | 24.24 | 369.00 | 24.20 | 296.33 | 24.21 |
August | 334.17 | 24.17 | 379.00 | 24.15 | 334.17 | 24.16 |
September | 215.00 | 24.25 | 360.00 | 24.17 | 215.00 | 24.19 |
October | 12.00 | 25.86 | 360.67 | 24.15 | 12.00 | 24.20 |
November | 21.83 | 23.11 | 228.17 | 23.94 | 0.00 | 23.94 |
December | 146.33 | 22.72 | 20.67 | 22.87 | 0.00 | 22.87 |
Annual Sum or Average | 1584.83 | 23.81 | 3092.83 | 24.03 | 1034.00 | 24.09 |
Minimum of Months | 7.67 | 22.65 | 6.50 | 22.71 | 0.00 | 22.71 |
Maximum of Months | 334.17 | 28.23 | 379.00 | 24.37 | 334.17 | 24.53 |
Report: ComfortReportSimple55Monthly
For: SMSTORE4
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 305.67 | 22.67 | 3.50 | 22.68 | 0.17 | 22.68 |
February | 99.67 | 22.66 | 56.83 | 23.16 | 0.00 | 23.16 |
March | 24.17 | 23.40 | 231.50 | 24.04 | 0.50 | 24.04 |
April | 7.33 | 28.12 | 315.33 | 24.26 | 7.00 | 24.35 |
May | 38.17 | 26.15 | 375.00 | 24.36 | 38.17 | 24.52 |
June | 133.00 | 24.63 | 366.00 | 24.31 | 133.00 | 24.37 |
July | 297.17 | 24.23 | 369.00 | 24.20 | 297.17 | 24.21 |
August | 335.83 | 24.17 | 379.00 | 24.15 | 335.83 | 24.16 |
September | 217.00 | 24.24 | 360.00 | 24.17 | 217.00 | 24.19 |
October | 12.00 | 25.69 | 359.50 | 24.14 | 12.00 | 24.19 |
November | 25.67 | 23.11 | 219.50 | 23.92 | 0.00 | 23.92 |
December | 165.50 | 22.72 | 13.00 | 22.81 | 0.00 | 22.81 |
Annual Sum or Average | 1661.17 | 23.76 | 3048.17 | 24.00 | 1040.83 | 24.07 |
Minimum of Months | 7.33 | 22.66 | 3.50 | 22.68 | 0.00 | 22.68 |
Maximum of Months | 335.83 | 28.12 | 379.00 | 24.36 | 335.83 | 24.52 |
Report: ComfortReportSimple55Monthly
For: LGSTORE2
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 310.00 | 22.66 | 0.17 | 22.66 | 0.17 | 22.65 |
February | 123.83 | 22.98 | 34.50 | 23.19 | 0.00 | 23.19 |
March | 22.00 | 23.47 | 187.50 | 23.92 | 0.50 | 23.93 |
April | 4.17 | 28.38 | 277.33 | 24.07 | 4.00 | 24.14 |
May | 25.50 | 25.21 | 344.00 | 24.09 | 25.50 | 24.16 |
June | 120.50 | 24.14 | 336.00 | 24.03 | 120.50 | 24.05 |
July | 279.17 | 24.04 | 338.00 | 24.03 | 279.17 | 24.03 |
August | 325.50 | 23.97 | 348.00 | 23.97 | 325.50 | 23.97 |
September | 203.00 | 24.04 | 330.00 | 24.00 | 203.00 | 24.01 |
October | 14.33 | 24.74 | 329.50 | 24.01 | 14.33 | 24.04 |
November | 18.17 | 23.31 | 179.33 | 23.89 | 0.00 | 23.89 |
December | 192.17 | 22.88 | 0.00 | 22.88 | 0.00 | 22.88 |
Annual Sum or Average | 1638.33 | 23.58 | 2704.33 | 23.83 | 972.67 | 23.88 |
Minimum of Months | 4.17 | 22.66 | 0.00 | 22.66 | 0.00 | 22.65 |
Maximum of Months | 325.50 | 28.38 | 348.00 | 24.09 | 325.50 | 24.16 |
Report: ComfortReportSimple55Monthly
For: SMSTORE5
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 313.83 | 22.64 | 0.50 | 22.64 | 0.50 | 22.63 |
February | 137.83 | 23.05 | 28.67 | 23.21 | 0.00 | 23.21 |
March | 25.17 | 23.49 | 168.83 | 23.92 | 0.33 | 23.92 |
April | 3.83 | 28.22 | 256.83 | 24.08 | 3.50 | 24.14 |
May | 27.00 | 25.13 | 344.00 | 24.08 | 27.00 | 24.16 |
June | 121.83 | 24.13 | 336.00 | 24.02 | 121.83 | 24.05 |
July | 279.67 | 24.04 | 338.00 | 24.03 | 279.67 | 24.03 |
August | 326.00 | 23.97 | 348.00 | 23.97 | 326.00 | 23.97 |
September | 205.00 | 24.04 | 330.00 | 24.00 | 205.00 | 24.01 |
October | 16.67 | 24.54 | 323.83 | 24.01 | 16.67 | 24.03 |
November | 20.67 | 23.38 | 158.67 | 23.89 | 0.00 | 23.89 |
December | 201.83 | 22.91 | 0.00 | 22.91 | 0.00 | 22.91 |
Annual Sum or Average | 1679.33 | 23.57 | 2633.33 | 23.83 | 980.50 | 23.87 |
Minimum of Months | 3.83 | 22.64 | 0.00 | 22.64 | 0.00 | 22.63 |
Maximum of Months | 326.00 | 28.22 | 348.00 | 24.08 | 326.00 | 24.16 |
Report: ComfortReportSimple55Monthly
For: SMSTORE6
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 315.17 | 22.61 | 0.50 | 22.61 | 0.50 | 22.61 |
February | 142.50 | 23.05 | 24.00 | 23.18 | 0.00 | 23.18 |
March | 27.00 | 23.49 | 165.17 | 23.91 | 0.33 | 23.92 |
April | 3.83 | 28.21 | 254.83 | 24.08 | 3.50 | 24.14 |
May | 27.33 | 25.11 | 344.00 | 24.08 | 27.33 | 24.15 |
June | 121.83 | 24.13 | 336.00 | 24.02 | 121.83 | 24.05 |
July | 280.00 | 24.04 | 338.00 | 24.03 | 280.00 | 24.03 |
August | 327.17 | 23.97 | 348.00 | 23.97 | 327.17 | 23.97 |
September | 206.17 | 24.03 | 330.00 | 24.00 | 206.17 | 24.01 |
October | 16.83 | 24.50 | 322.67 | 24.01 | 16.83 | 24.03 |
November | 22.00 | 23.38 | 156.83 | 23.89 | 0.00 | 23.89 |
December | 209.50 | 22.91 | 0.00 | 22.91 | 0.00 | 22.91 |
Annual Sum or Average | 1699.33 | 23.56 | 2620.00 | 23.82 | 983.67 | 23.87 |
Minimum of Months | 3.83 | 22.61 | 0.00 | 22.61 | 0.00 | 22.61 |
Maximum of Months | 327.17 | 28.21 | 348.00 | 24.08 | 327.17 | 24.15 |
Report: ComfortReportSimple55Monthly
For: SMSTORE7
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 316.67 | 22.54 | 1.00 | 22.53 | 1.00 | 22.53 |
February | 154.50 | 23.03 | 21.00 | 23.14 | 0.00 | 23.14 |
March | 31.17 | 23.43 | 161.83 | 23.89 | 0.33 | 23.90 |
April | 4.17 | 27.87 | 257.67 | 24.08 | 3.50 | 24.14 |
May | 27.33 | 25.11 | 344.00 | 24.08 | 27.33 | 24.16 |
June | 121.50 | 24.14 | 336.00 | 24.03 | 121.50 | 24.05 |
July | 278.00 | 24.04 | 338.00 | 24.03 | 278.00 | 24.03 |
August | 324.00 | 23.97 | 348.00 | 23.97 | 324.00 | 23.97 |
September | 204.17 | 24.04 | 330.00 | 24.00 | 204.17 | 24.01 |
October | 17.33 | 24.51 | 324.00 | 24.01 | 17.17 | 24.03 |
November | 24.67 | 23.34 | 155.67 | 23.87 | 0.00 | 23.87 |
December | 225.83 | 22.89 | 0.00 | 22.89 | 0.00 | 22.89 |
Annual Sum or Average | 1729.33 | 23.53 | 2617.17 | 23.81 | 977.00 | 23.86 |
Minimum of Months | 4.17 | 22.54 | 0.00 | 22.53 | 0.00 | 22.53 |
Maximum of Months | 324.00 | 27.87 | 348.00 | 24.08 | 324.00 | 24.16 |
Report: ComfortReportSimple55Monthly
For: SMSTORE8
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 316.17 | 22.52 | 3.50 | 22.50 | 3.50 | 22.49 |
February | 155.33 | 22.93 | 25.33 | 23.08 | 0.00 | 23.08 |
March | 37.33 | 23.32 | 185.17 | 23.87 | 0.50 | 23.88 |
April | 6.00 | 27.77 | 292.17 | 24.08 | 5.00 | 24.16 |
May | 26.17 | 25.33 | 344.00 | 24.10 | 26.17 | 24.18 |
June | 104.67 | 24.21 | 336.00 | 24.04 | 104.67 | 24.07 |
July | 258.00 | 24.07 | 338.00 | 24.05 | 258.00 | 24.05 |
August | 286.50 | 24.00 | 348.00 | 23.99 | 286.50 | 23.99 |
September | 181.83 | 24.07 | 330.00 | 24.02 | 181.83 | 24.03 |
October | 12.17 | 25.55 | 329.83 | 24.05 | 11.67 | 24.10 |
November | 26.33 | 23.22 | 182.67 | 23.86 | 0.00 | 23.86 |
December | 228.17 | 22.84 | 0.00 | 22.84 | 0.00 | 22.84 |
Annual Sum or Average | 1638.67 | 23.50 | 2714.67 | 23.81 | 877.83 | 23.86 |
Minimum of Months | 6.00 | 22.52 | 0.00 | 22.50 | 0.00 | 22.49 |
Maximum of Months | 316.17 | 27.77 | 348.00 | 24.10 | 286.50 | 24.18 |
Report: OccupantComfortDataSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 496.00000 | 22.90219 | 41.59955 | 0.09926 | 6.41649 |
February | 448.00000 | 23.49246 | 42.79330 | 0.28568 | 7.48339 |
March | 497.00000 | 23.84053 | 42.67329 | 0.43006 | 9.07960 |
April | 479.00000 | 23.88848 | 42.35735 | 0.51457 | 10.67360 |
May | 496.00000 | 23.89184 | 51.52509 | -0.2063 | 6.01129 |
June | 481.00000 | 23.89275 | 58.01001 | -0.1432 | 5.55106 |
July | 495.00000 | 23.89380 | 64.99712 | -0.1053 | 5.32228 |
August | 497.00000 | 23.89308 | 66.83550 | -0.1065 | 5.33745 |
September | 479.00000 | 23.89142 | 63.72502 | -0.1528 | 5.58871 |
October | 496.00000 | 23.88488 | 48.94601 | 0.55326 | 11.51524 |
November | 480.00000 | 23.82652 | 42.71353 | 0.42838 | 9.03190 |
December | 496.00000 | 23.30266 | 40.40057 | 0.21593 | 6.99333 |
Annual Sum or Average | 5840.00000 | 23.71682 | 50.59852 | 0.14986 | 7.41298 |
Minimum of Months | 448.00000 | 22.90219 | 40.40057 | -0.2063 | 5.32228 |
Maximum of Months | 497.00000 | 23.89380 | 66.83550 | 0.55326 | 11.51524 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 496.00000 | 23.37894 | 41.08225 | 0.21431 | 6.73993 |
February | 448.00000 | 23.68603 | 41.19195 | 0.33087 | 7.70404 |
March | 497.00000 | 23.86715 | 41.12879 | 0.42640 | 8.93078 |
April | 479.00000 | 23.88795 | 41.42904 | 0.48885 | 10.09670 |
May | 496.00000 | 23.89158 | 50.02823 | -0.2593 | 6.50279 |
June | 481.00000 | 23.89209 | 56.19253 | -0.2048 | 5.99009 |
July | 495.00000 | 23.89267 | 62.78347 | -0.1660 | 5.68156 |
August | 497.00000 | 23.89222 | 64.45680 | -0.1670 | 5.71736 |
September | 479.00000 | 23.89112 | 60.96163 | -0.2101 | 6.05528 |
October | 496.00000 | 23.88549 | 46.67610 | 0.51939 | 10.75354 |
November | 480.00000 | 23.85850 | 40.89270 | 0.42077 | 8.82419 |
December | 496.00000 | 23.61471 | 39.21909 | 0.28691 | 7.26712 |
Annual Sum or Average | 5840.00000 | 23.80329 | 48.88783 | 0.13862 | 7.51784 |
Minimum of Months | 448.00000 | 23.37894 | 39.21909 | -0.2593 | 5.68156 |
Maximum of Months | 497.00000 | 23.89267 | 64.45680 | 0.51939 | 10.75354 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 23.06207 | 39.81395 | 0.13583 | 6.48769 |
February | 336.00000 | 23.62304 | 41.01727 | 0.31259 | 7.70046 |
March | 379.00000 | 23.99951 | 41.27385 | 0.45411 | 9.58428 |
April | 360.00000 | 24.13813 | 41.19977 | 0.53907 | 11.51936 |
May | 375.00000 | 24.18447 | 50.78533 | -0.1684 | 6.60118 |
June | 366.00000 | 24.19028 | 57.59326 | -0.1077 | 6.33889 |
July | 369.00000 | 24.17191 | 65.41640 | -0.0667 | 6.14139 |
August | 379.00000 | 24.13780 | 67.64681 | -0.0733 | 5.95800 |
September | 360.00000 | 24.12507 | 64.01445 | -0.1202 | 6.03495 |
October | 371.00000 | 24.08733 | 47.99789 | 0.57459 | 12.21292 |
November | 360.00000 | 23.93174 | 41.00661 | 0.44037 | 9.25729 |
December | 369.00000 | 23.45961 | 38.20839 | 0.24764 | 7.09146 |
Annual Sum or Average | 4395.00000 | 23.92784 | 49.74780 | 0.17895 | 7.90589 |
Minimum of Months | 336.00000 | 23.06207 | 38.20839 | -0.1684 | 5.95800 |
Maximum of Months | 379.00000 | 24.19028 | 67.64681 | 0.57459 | 12.21292 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 22.99176 | 40.01698 | 0.11255 | 6.41657 |
February | 336.00000 | 23.60051 | 41.12324 | 0.30325 | 7.62133 |
March | 379.00000 | 23.99658 | 41.29146 | 0.45252 | 9.55956 |
April | 360.00000 | 24.13857 | 41.17799 | 0.54049 | 11.55394 |
May | 375.00000 | 24.18542 | 50.72211 | -0.1645 | 6.58320 |
June | 366.00000 | 24.19124 | 57.50288 | -0.1042 | 6.33385 |
July | 369.00000 | 24.17296 | 65.28435 | -0.0633 | 6.14484 |
August | 379.00000 | 24.13856 | 67.53829 | -0.0710 | 5.95902 |
September | 360.00000 | 24.12570 | 63.92523 | -0.1182 | 6.03048 |
October | 371.00000 | 24.08757 | 47.96529 | 0.57559 | 12.23850 |
November | 360.00000 | 23.92664 | 41.04262 | 0.43760 | 9.21607 |
December | 369.00000 | 23.42514 | 38.33890 | 0.23488 | 7.02147 |
Annual Sum or Average | 4395.00000 | 23.91704 | 49.74326 | 0.17631 | 7.88550 |
Minimum of Months | 336.00000 | 22.99176 | 38.33890 | -0.1645 | 5.95902 |
Maximum of Months | 379.00000 | 24.19124 | 67.53829 | 0.57559 | 12.23850 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 22.88358 | 40.32334 | 0.07997 | 6.32158 |
February | 336.00000 | 23.55459 | 41.34926 | 0.28635 | 7.47505 |
March | 379.00000 | 23.98435 | 41.43088 | 0.44494 | 9.42671 |
April | 360.00000 | 24.13469 | 41.24573 | 0.53614 | 11.44576 |
May | 375.00000 | 24.18210 | 50.82257 | -0.1686 | 6.58512 |
June | 366.00000 | 24.18795 | 57.64897 | -0.1079 | 6.32007 |
July | 369.00000 | 24.16968 | 65.46541 | -0.0661 | 6.12623 |
August | 379.00000 | 24.13492 | 67.76599 | -0.0742 | 5.94203 |
September | 360.00000 | 24.12201 | 64.16003 | -0.1220 | 6.02536 |
October | 371.00000 | 24.08343 | 48.11098 | 0.57201 | 12.14422 |
November | 360.00000 | 23.91333 | 41.18037 | 0.43021 | 9.09365 |
December | 369.00000 | 23.36316 | 38.57329 | 0.21433 | 6.90724 |
Annual Sum or Average | 4395.00000 | 23.89493 | 49.92204 | 0.16714 | 7.81397 |
Minimum of Months | 336.00000 | 22.88358 | 38.57329 | -0.1686 | 5.94203 |
Maximum of Months | 379.00000 | 24.18795 | 67.76599 | 0.57201 | 12.14422 |
Report: OccupantComfortDataSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 22.76532 | 41.99821 | 0.03467 | 6.10792 |
February | 308.00000 | 23.53390 | 42.53252 | 0.26586 | 7.15502 |
March | 348.00000 | 23.90177 | 42.37749 | 0.42186 | 8.93568 |
April | 330.00000 | 23.98987 | 42.25711 | 0.51093 | 10.75114 |
May | 344.00000 | 24.00378 | 52.09926 | -0.2080 | 6.44236 |
June | 336.00000 | 23.98674 | 58.97673 | -0.1526 | 5.96719 |
July | 338.00000 | 24.01800 | 66.73920 | -0.1003 | 5.88021 |
August | 348.00000 | 23.96920 | 69.15124 | -0.1133 | 5.68713 |
September | 330.00000 | 23.98388 | 65.42342 | -0.1566 | 5.93417 |
October | 340.00000 | 23.97909 | 48.97606 | 0.55345 | 11.62079 |
November | 330.00000 | 23.89192 | 41.97623 | 0.41877 | 8.81313 |
December | 338.00000 | 23.30905 | 40.23181 | 0.18875 | 6.63684 |
Annual Sum or Average | 4030.00000 | 23.77908 | 51.14752 | 0.13683 | 7.49048 |
Minimum of Months | 308.00000 | 22.76532 | 40.23181 | -0.2080 | 5.68713 |
Maximum of Months | 348.00000 | 24.01800 | 69.15124 | 0.55345 | 11.62079 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 22.73601 | 41.94546 | 0.01969 | 6.07662 |
February | 308.00000 | 23.52727 | 42.49811 | 0.25373 | 7.02840 |
March | 348.00000 | 23.90127 | 42.37069 | 0.40794 | 8.68507 |
April | 330.00000 | 23.98879 | 42.22447 | 0.49166 | 10.33482 |
May | 344.00000 | 24.00291 | 52.11662 | -0.2383 | 6.71162 |
June | 336.00000 | 23.98579 | 59.07983 | -0.1834 | 6.17169 |
July | 338.00000 | 24.01680 | 66.97535 | -0.1288 | 6.00140 |
August | 348.00000 | 23.96850 | 69.44645 | -0.1402 | 5.82232 |
September | 330.00000 | 23.98291 | 65.64268 | -0.1823 | 6.10715 |
October | 340.00000 | 23.97836 | 49.04109 | 0.53585 | 11.20946 |
November | 330.00000 | 23.89239 | 41.97244 | 0.40571 | 8.58071 |
December | 338.00000 | 23.29877 | 40.17328 | 0.17686 | 6.55801 |
Annual Sum or Average | 4030.00000 | 23.77469 | 51.21078 | 0.11634 | 7.43812 |
Minimum of Months | 308.00000 | 22.73601 | 40.17328 | -0.2383 | 5.82232 |
Maximum of Months | 348.00000 | 24.01680 | 69.44645 | 0.53585 | 11.20946 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 22.70391 | 42.02928 | 0.00938 | 6.07382 |
February | 308.00000 | 23.51242 | 42.56861 | 0.24731 | 6.98519 |
March | 348.00000 | 23.89848 | 42.41036 | 0.40503 | 8.64063 |
April | 330.00000 | 23.98849 | 42.24207 | 0.49005 | 10.30094 |
May | 344.00000 | 24.00274 | 52.14689 | -0.2400 | 6.72677 |
June | 336.00000 | 23.98561 | 59.12444 | -0.1849 | 6.18229 |
July | 338.00000 | 24.01657 | 67.02663 | -0.1301 | 6.00630 |
August | 348.00000 | 23.96832 | 69.50278 | -0.1415 | 5.82819 |
September | 330.00000 | 23.98265 | 65.69742 | -0.1837 | 6.11583 |
October | 340.00000 | 23.97801 | 49.07551 | 0.53453 | 11.17904 |
November | 330.00000 | 23.89003 | 42.00983 | 0.40321 | 8.54185 |
December | 338.00000 | 23.27501 | 40.24716 | 0.16874 | 6.52318 |
Annual Sum or Average | 4030.00000 | 23.76828 | 51.26022 | 0.11299 | 7.42311 |
Minimum of Months | 308.00000 | 22.70391 | 40.24716 | -0.2400 | 5.82819 |
Maximum of Months | 348.00000 | 24.01657 | 69.50278 | 0.53453 | 11.17904 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 22.63053 | 42.22026 | -0.0119 | 6.09987 |
February | 308.00000 | 23.46800 | 42.76322 | 0.23228 | 6.91622 |
March | 348.00000 | 23.88821 | 42.51477 | 0.40028 | 8.58692 |
April | 330.00000 | 23.98845 | 42.25095 | 0.49241 | 10.35349 |
May | 344.00000 | 24.00301 | 52.10597 | -0.2333 | 6.66511 |
June | 336.00000 | 23.98589 | 59.04230 | -0.1780 | 6.13394 |
July | 338.00000 | 24.01713 | 66.87163 | -0.1231 | 5.97910 |
August | 348.00000 | 23.96870 | 69.33466 | -0.1349 | 5.79643 |
September | 330.00000 | 23.98300 | 65.59663 | -0.1778 | 6.07714 |
October | 340.00000 | 23.97797 | 49.08072 | 0.53722 | 11.24340 |
November | 330.00000 | 23.88172 | 42.09901 | 0.39994 | 8.50547 |
December | 338.00000 | 23.21212 | 40.43497 | 0.15052 | 6.47238 |
Annual Sum or Average | 4030.00000 | 23.75200 | 51.27833 | 0.11105 | 7.40040 |
Minimum of Months | 308.00000 | 22.63053 | 40.43497 | -0.2333 | 5.79643 |
Maximum of Months | 348.00000 | 24.01713 | 69.33466 | 0.53722 | 11.24340 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 22.61594 | 42.25985 | -0.0242 | 6.23356 |
February | 308.00000 | 23.41920 | 42.90951 | 0.22100 | 7.02313 |
March | 348.00000 | 23.86886 | 42.61102 | 0.41307 | 8.93222 |
April | 330.00000 | 23.99505 | 42.11500 | 0.54187 | 11.48972 |
May | 344.00000 | 24.00890 | 51.52172 | -0.1457 | 6.06118 |
June | 336.00000 | 23.99161 | 58.00905 | -0.0931 | 5.74261 |
July | 338.00000 | 24.02682 | 65.17633 | -0.0462 | 5.85919 |
August | 348.00000 | 23.97673 | 67.29723 | -0.0625 | 5.60763 |
September | 330.00000 | 23.99213 | 63.99561 | -0.1099 | 5.77577 |
October | 340.00000 | 23.98630 | 48.59932 | 0.58190 | 12.35786 |
November | 330.00000 | 23.87263 | 42.09967 | 0.41816 | 8.89892 |
December | 338.00000 | 23.17460 | 40.47512 | 0.13926 | 6.57063 |
Annual Sum or Average | 4030.00000 | 23.74595 | 50.66760 | 0.15143 | 7.54198 |
Minimum of Months | 308.00000 | 22.61594 | 40.47512 | -0.1457 | 5.60763 |
Maximum of Months | 348.00000 | 24.02682 | 67.29723 | 0.58190 | 12.35786 |
Report: DXReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.149964E+10 | 0.418036E+09 | 148.58 | 0.134040E+10 | 0.159241E+09 | 0.00 | 0.33 | 12-JAN-15:00 | 0.00 | 01-JAN-00:10 | 8445.94 | 12-JAN-15:00 | 7902.22 | 12-JAN-15:00 | 1444.38 | 14-JAN-14:00 | 2334.71 | 12-JAN-15:00 | 0.00 | 01-JAN-00:10 |
February | 0.672751E+10 | 0.185085E+10 | 302.00 | 0.585057E+10 | 0.876948E+09 | 0.00 | 0.56 | 22-FEB-15:00 | 0.00 | 01-FEB-00:05 | 15261.86 | 22-FEB-15:00 | 13962.70 | 22-FEB-15:00 | 3879.88 | 25-FEB-18:05 | 4203.09 | 22-FEB-15:00 | 0.00 | 01-FEB-00:05 |
March | 0.187160E+11 | 0.518827E+10 | 459.47 | 0.161094E+11 | 0.260660E+10 | 0.00 | 1.00 | 11-MAR-08:62 | 0.00 | 01-MAR-00:10 | 40690.61 | 11-MAR-08:62 | 30410.77 | 11-MAR-08:62 | 10279.84 | 11-MAR-08:62 | 9158.70 | 11-MAR-08:62 | 0.00 | 01-MAR-00:10 |
April | 0.318706E+11 | 0.928922E+10 | 480.85 | 0.285494E+11 | 0.332129E+10 | 0.00 | 1.00 | 02-APR-07:02 | 0.00 | 01-APR-00:05 | 67559.67 | 26-APR-07:02 | 62441.91 | 28-APR-07:02 | 17397.07 | 26-APR-07:02 | 16326.27 | 27-APR-07:02 | 0.00 | 01-APR-00:05 |
May | 0.467266E+11 | 0.136175E+11 | 502.36 | 0.373392E+11 | 0.938744E+10 | 0.00 | 1.00 | 01-MAY-07:01 | 0.00 | 01-MAY-00:10 | 71598.36 | 24-MAY-07:02 | 62785.79 | 06-MAY-07:01 | 31311.82 | 24-MAY-07:02 | 17185.39 | 04-MAY-07:01 | 0.00 | 01-MAY-00:10 |
June | 0.530472E+11 | 0.148555E+11 | 489.16 | 0.373851E+11 | 0.156621E+11 | 0.00 | 1.00 | 01-JUN-07:02 | 0.00 | 01-JUN-00:10 | 72998.13 | 26-JUN-07:01 | 59859.29 | 07-JUN-07:01 | 36193.36 | 26-JUN-07:03 | 17640.95 | 12-JUN-07:01 | 0.00 | 01-JUN-00:10 |
July | 0.597987E+11 | 0.153401E+11 | 503.34 | 0.348138E+11 | 0.249850E+11 | 0.00 | 1.00 | 01-JUL-07:01 | 0.00 | 01-JUL-00:03 | 73875.52 | 25-JUL-07:01 | 50522.16 | 07-JUL-07:01 | 38601.93 | 25-JUL-07:03 | 17258.20 | 05-JUL-07:12 | 0.00 | 01-JUL-00:03 |
August | 0.590493E+11 | 0.146189E+11 | 504.00 | 0.320791E+11 | 0.269702E+11 | 0.00 | 1.00 | 01-AUG-07:01 | 0.00 | 01-AUG-00:10 | 73457.52 | 10-AUG-07:01 | 46704.71 | 03-AUG-07:01 | 36192.50 | 10-AUG-07:04 | 16550.89 | 08-AUG-07:02 | 0.00 | 01-AUG-00:10 |
September | 0.484871E+11 | 0.121992E+11 | 487.21 | 0.284451E+11 | 0.200419E+11 | 0.00 | 1.00 | 01-SEP-07:01 | 0.00 | 01-SEP-00:03 | 72841.77 | 03-SEP-07:01 | 49394.59 | 26-SEP-07:01 | 34516.74 | 03-SEP-07:02 | 16128.48 | 22-SEP-07:01 | 0.00 | 01-SEP-00:03 |
October | 0.309623E+11 | 0.835167E+10 | 491.25 | 0.243221E+11 | 0.664025E+10 | 0.00 | 1.00 | 01-OCT-07:02 | 0.00 | 01-OCT-00:10 | 69047.45 | 11-OCT-07:02 | 53461.10 | 05-OCT-07:02 | 25013.56 | 12-OCT-07:03 | 15624.96 | 04-OCT-07:02 | 0.00 | 01-OCT-00:10 |
November | 0.153558E+11 | 0.418387E+10 | 428.31 | 0.131655E+11 | 0.219033E+10 | 0.00 | 0.73 | 08-NOV-15:00 | 0.00 | 01-NOV-00:10 | 20864.58 | 09-NOV-14:20 | 18921.95 | 04-NOV-14:00 | 5685.78 | 09-NOV-08:63 | 5724.44 | 08-NOV-15:00 | 0.00 | 01-NOV-00:10 |
December | 0.349695E+10 | 0.967508E+09 | 245.25 | 0.304307E+10 | 0.453879E+09 | 0.00 | 0.42 | 28-DEC-15:00 | 0.00 | 01-DEC-00:10 | 11132.72 | 28-DEC-15:00 | 10250.99 | 03-DEC-14:00 | 1685.08 | 16-DEC-14:00 | 3043.86 | 28-DEC-15:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.375738E+12 | 0.100881E+12 | 5041.78 | 0.262443E+12 | 0.113295E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.149964E+10 | 0.418036E+09 | 148.58 | 0.134040E+10 | 0.159241E+09 | 0.00 | 0.33 | 0.00 | 8445.94 | 7902.22 | 1444.38 | 2334.71 | 0.00 | |||||||
Maximum of Months | 0.597987E+11 | 0.153401E+11 | 504.00 | 0.373851E+11 | 0.269702E+11 | 0.00 | 1.00 | 0.00 | 73875.52 | 62785.79 | 38601.93 | 17640.95 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.167877E+10 | 0.457362E+09 | 285.33 | 0.145686E+10 | 0.221912E+09 | 0.00 | 0.37 | 12-JAN-15:00 | 0.00 | 01-JAN-00:10 | 4855.07 | 12-JAN-15:00 | 4557.40 | 12-JAN-15:00 | 928.48 | 16-JAN-18:30 | 1304.96 | 12-JAN-15:00 | 0.00 | 01-JAN-00:10 |
February | 0.455797E+10 | 0.122263E+10 | 365.17 | 0.394659E+10 | 0.611381E+09 | 0.00 | 0.58 | 22-FEB-15:00 | 0.00 | 01-FEB-00:05 | 8133.00 | 22-FEB-15:00 | 7454.93 | 22-FEB-15:00 | 2075.27 | 25-FEB-18:05 | 2187.29 | 22-FEB-15:00 | 0.00 | 01-FEB-00:05 |
March | 0.101992E+11 | 0.276596E+10 | 474.06 | 0.886118E+10 | 0.133797E+10 | 0.00 | 1.00 | 11-MAR-08:62 | 0.00 | 01-MAR-00:10 | 22113.64 | 11-MAR-08:62 | 18387.55 | 11-MAR-08:62 | 3726.09 | 11-MAR-08:62 | 4924.96 | 11-MAR-08:62 | 0.00 | 01-MAR-00:10 |
April | 0.157284E+11 | 0.452603E+10 | 480.95 | 0.141845E+11 | 0.154397E+10 | 0.00 | 1.00 | 02-APR-07:02 | 0.00 | 01-APR-00:05 | 33586.36 | 26-APR-07:02 | 31973.78 | 28-APR-07:02 | 5278.59 | 26-APR-07:02 | 8102.23 | 27-APR-07:02 | 0.00 | 01-APR-00:05 |
May | 0.225293E+11 | 0.652231E+10 | 502.39 | 0.181995E+11 | 0.432977E+10 | 0.00 | 1.00 | 01-MAY-07:01 | 0.00 | 01-MAY-00:10 | 35444.34 | 24-MAY-07:02 | 32044.63 | 06-MAY-07:01 | 11480.17 | 24-MAY-07:02 | 8588.29 | 04-MAY-07:01 | 0.00 | 01-MAY-00:10 |
June | 0.252667E+11 | 0.704593E+10 | 489.00 | 0.180587E+11 | 0.720799E+10 | 0.00 | 1.00 | 01-JUN-07:02 | 0.00 | 01-JUN-00:10 | 35702.40 | 26-JUN-07:01 | 31324.35 | 07-JUN-07:01 | 12950.07 | 26-JUN-07:03 | 8780.10 | 12-JUN-07:01 | 0.00 | 01-JUN-00:10 |
July | 0.284323E+11 | 0.726955E+10 | 502.97 | 0.169150E+11 | 0.115173E+11 | 0.00 | 1.00 | 01-JUL-07:01 | 0.00 | 01-JUL-00:03 | 36190.38 | 25-JUL-07:01 | 28492.96 | 07-JUL-07:01 | 14468.69 | 25-JUL-07:03 | 8628.28 | 05-JUL-07:01 | 0.00 | 01-JUL-00:03 |
August | 0.281636E+11 | 0.693991E+10 | 503.86 | 0.156764E+11 | 0.124871E+11 | 0.00 | 1.00 | 01-AUG-07:01 | 0.00 | 01-AUG-00:10 | 36093.04 | 10-AUG-07:01 | 26437.02 | 07-AUG-07:01 | 13460.40 | 10-AUG-07:02 | 8277.69 | 08-AUG-07:01 | 0.00 | 01-AUG-00:10 |
September | 0.231860E+11 | 0.579830E+10 | 487.06 | 0.139774E+11 | 0.920868E+10 | 0.00 | 1.00 | 01-SEP-07:01 | 0.00 | 01-SEP-00:03 | 35844.71 | 03-SEP-07:01 | 28192.67 | 26-SEP-07:01 | 12803.33 | 03-SEP-07:02 | 8011.65 | 22-SEP-07:01 | 0.00 | 01-SEP-00:03 |
October | 0.155367E+11 | 0.413177E+10 | 492.49 | 0.124272E+11 | 0.310945E+10 | 0.00 | 1.00 | 01-OCT-07:02 | 0.00 | 01-OCT-00:10 | 34192.88 | 11-OCT-07:02 | 29583.30 | 02-OCT-07:02 | 7837.57 | 12-OCT-07:03 | 7726.75 | 04-OCT-07:02 | 0.00 | 01-OCT-00:10 |
November | 0.878594E+10 | 0.234060E+10 | 450.89 | 0.758678E+10 | 0.119916E+10 | 0.00 | 0.74 | 09-NOV-13:50 | 0.00 | 01-NOV-00:10 | 10909.54 | 09-NOV-13:50 | 9988.39 | 04-NOV-14:00 | 2203.19 | 09-NOV-08:63 | 2905.28 | 04-NOV-13:00 | 0.00 | 01-NOV-00:10 |
December | 0.313507E+10 | 0.847179E+09 | 378.75 | 0.267668E+10 | 0.458390E+09 | 0.00 | 0.46 | 03-DEC-14:00 | 0.00 | 01-DEC-01:05 | 6159.29 | 03-DEC-14:00 | 5841.28 | 03-DEC-14:00 | 1195.76 | 10-DEC-18:20 | 1640.92 | 03-DEC-14:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.187200E+12 | 0.498675E+11 | 5412.92 | 0.133967E+12 | 0.532331E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.167877E+10 | 0.457362E+09 | 285.33 | 0.145686E+10 | 0.221912E+09 | 0.00 | 0.37 | 0.00 | 4855.07 | 4557.40 | 928.48 | 1304.96 | 0.00 | |||||||
Maximum of Months | 0.284323E+11 | 0.726955E+10 | 503.86 | 0.181995E+11 | 0.124871E+11 | 0.00 | 1.00 | 0.00 | 36190.38 | 32044.63 | 14468.69 | 8780.10 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_3:3 COOLING COIL
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.740413E+09 | 0.202262E+09 | 132.33 | 0.672910E+09 | 67503483.75 | 0.00 | 0.34 | 12-JAN-15:00 | 0.00 | 01-JAN-00:10 | 4377.49 | 12-JAN-15:00 | 4120.15 | 12-JAN-15:00 | 805.35 | 14-JAN-14:00 | 1187.33 | 12-JAN-15:00 | 0.00 | 01-JAN-00:10 |
February | 0.295431E+10 | 0.798086E+09 | 226.00 | 0.261544E+10 | 0.338865E+09 | 0.00 | 0.56 | 22-FEB-14:00 | 0.00 | 01-FEB-00:05 | 7746.66 | 22-FEB-14:00 | 7112.82 | 22-FEB-14:00 | 1721.69 | 25-FEB-16:30 | 2094.20 | 22-FEB-14:00 | 0.00 | 01-FEB-00:05 |
March | 0.777085E+10 | 0.211864E+10 | 334.60 | 0.680103E+10 | 0.969822E+09 | 0.00 | 1.00 | 11-MAR-07:03 | 0.00 | 01-MAR-00:10 | 27474.58 | 11-MAR-07:03 | 19453.42 | 30-MAR-06:03 | 8307.95 | 11-MAR-07:03 | 5973.45 | 11-MAR-07:03 | 0.00 | 01-MAR-00:10 |
April | 0.126638E+11 | 0.362460E+10 | 354.47 | 0.114280E+11 | 0.123578E+10 | 0.00 | 1.00 | 02-APR-07:02 | 0.00 | 01-APR-00:05 | 34984.20 | 17-APR-06:01 | 32053.65 | 28-APR-06:01 | 9141.35 | 17-APR-06:01 | 8210.62 | 27-APR-06:01 | 0.00 | 01-APR-00:05 |
May | 0.188153E+11 | 0.539462E+10 | 376.68 | 0.150976E+11 | 0.371763E+10 | 0.00 | 1.00 | 01-MAY-06:01 | 0.00 | 01-MAY-00:10 | 37389.74 | 23-MAY-06:02 | 32317.98 | 06-MAY-06:01 | 18944.41 | 23-MAY-06:03 | 8435.06 | 04-MAY-06:01 | 0.00 | 01-MAY-00:10 |
June | 0.212437E+11 | 0.582596E+10 | 368.15 | 0.149222E+11 | 0.632152E+10 | 0.00 | 1.00 | 01-JUN-06:01 | 0.00 | 01-JUN-00:10 | 38065.56 | 26-JUN-06:01 | 30121.62 | 12-JUN-06:01 | 22952.03 | 26-JUN-06:04 | 8709.15 | 12-JUN-06:01 | 0.00 | 01-JUN-00:10 |
July | 0.235966E+11 | 0.590230E+10 | 370.86 | 0.135489E+11 | 0.100477E+11 | 0.00 | 1.00 | 01-JUL-06:01 | 0.00 | 01-JUL-00:03 | 38098.84 | 23-JUL-07:01 | 24561.92 | 01-JUL-06:01 | 23112.57 | 24-JUL-06:04 | 8620.91 | 02-JUL-07:12 | 0.00 | 01-JUL-00:03 |
August | 0.238291E+11 | 0.576579E+10 | 378.95 | 0.127773E+11 | 0.110518E+11 | 0.00 | 1.00 | 01-AUG-06:01 | 0.00 | 01-AUG-00:10 | 38181.75 | 21-AUG-06:03 | 21559.22 | 03-AUG-06:01 | 24582.60 | 28-AUG-06:05 | 8261.08 | 08-AUG-06:03 | 0.00 | 01-AUG-00:10 |
September | 0.191703E+11 | 0.471115E+10 | 359.57 | 0.111773E+11 | 0.799300E+10 | 0.00 | 1.00 | 01-SEP-06:01 | 0.00 | 01-SEP-00:03 | 38191.21 | 10-SEP-07:03 | 24120.11 | 27-SEP-06:02 | 24012.65 | 11-SEP-06:03 | 8013.68 | 22-SEP-06:01 | 0.00 | 01-SEP-00:03 |
October | 0.123734E+11 | 0.328634E+10 | 360.13 | 0.984751E+10 | 0.252592E+10 | 0.00 | 1.00 | 01-OCT-07:02 | 0.00 | 01-OCT-00:10 | 36035.94 | 12-OCT-06:02 | 27769.69 | 02-OCT-06:01 | 14722.93 | 12-OCT-06:02 | 7787.94 | 04-OCT-06:02 | 0.00 | 01-OCT-00:10 |
November | 0.655124E+10 | 0.175780E+10 | 307.56 | 0.575036E+10 | 0.800877E+09 | 0.00 | 0.73 | 04-NOV-13:00 | 0.00 | 01-NOV-00:10 | 11442.42 | 09-NOV-07:03 | 9912.25 | 04-NOV-14:00 | 3828.13 | 09-NOV-07:03 | 2897.34 | 04-NOV-13:00 | 0.00 | 01-NOV-00:10 |
December | 0.171852E+10 | 0.466536E+09 | 219.17 | 0.152046E+10 | 0.198056E+09 | 0.00 | 0.42 | 02-DEC-14:00 | 0.00 | 01-DEC-00:10 | 5627.17 | 28-DEC-14:00 | 5568.50 | 02-DEC-14:00 | 918.65 | 16-DEC-14:00 | 1516.05 | 28-DEC-14:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.151428E+12 | 0.398541E+11 | 3788.46 | 0.106159E+12 | 0.452685E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.740413E+09 | 0.202262E+09 | 132.33 | 0.672910E+09 | 67503483.75 | 0.00 | 0.34 | 0.00 | 4377.49 | 4120.15 | 805.35 | 1187.33 | 0.00 | |||||||
Maximum of Months | 0.238291E+11 | 0.590230E+10 | 378.95 | 0.150976E+11 | 0.110518E+11 | 0.00 | 1.00 | 0.00 | 38191.21 | 32317.98 | 24582.60 | 8709.15 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_4:4 COOLING COIL
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.661839E+09 | 0.181139E+09 | 122.17 | 0.600586E+09 | 61253027.57 | 0.00 | 0.32 | 12-JAN-15:00 | 0.00 | 01-JAN-00:10 | 4234.26 | 12-JAN-15:00 | 3984.33 | 12-JAN-15:00 | 784.13 | 14-JAN-14:00 | 1151.80 | 12-JAN-15:00 | 0.00 | 01-JAN-00:10 |
February | 0.286279E+10 | 0.774779E+09 | 223.00 | 0.253487E+10 | 0.327916E+09 | 0.00 | 0.55 | 22-FEB-14:00 | 0.00 | 01-FEB-00:05 | 7666.49 | 22-FEB-14:00 | 7038.16 | 22-FEB-14:00 | 1704.74 | 25-FEB-16:30 | 2076.01 | 22-FEB-14:00 | 0.00 | 01-FEB-00:05 |
March | 0.774361E+10 | 0.211251E+10 | 334.10 | 0.677666E+10 | 0.966953E+09 | 0.00 | 1.00 | 11-MAR-07:03 | 0.00 | 01-MAR-00:10 | 27560.01 | 11-MAR-07:03 | 19719.24 | 30-MAR-06:03 | 8332.49 | 11-MAR-07:03 | 5991.78 | 11-MAR-07:03 | 0.00 | 01-MAR-00:10 |
April | 0.127180E+11 | 0.363890E+10 | 354.48 | 0.114776E+11 | 0.124042E+10 | 0.00 | 1.00 | 02-APR-07:02 | 0.00 | 01-APR-00:05 | 35074.35 | 17-APR-06:01 | 32137.89 | 28-APR-06:01 | 9027.28 | 17-APR-06:01 | 8226.07 | 27-APR-06:01 | 0.00 | 01-APR-00:05 |
May | 0.189408E+11 | 0.542777E+10 | 376.79 | 0.152080E+11 | 0.373280E+10 | 0.00 | 1.00 | 01-MAY-06:01 | 0.00 | 01-MAY-00:10 | 37461.69 | 23-MAY-06:02 | 32408.37 | 06-MAY-06:01 | 18889.62 | 23-MAY-06:03 | 8451.43 | 04-MAY-06:01 | 0.00 | 01-MAY-00:10 |
June | 0.213739E+11 | 0.585977E+10 | 368.58 | 0.150303E+11 | 0.634365E+10 | 0.00 | 1.00 | 01-JUN-06:01 | 0.00 | 01-JUN-00:10 | 38133.61 | 26-JUN-06:01 | 30415.76 | 12-JUN-06:01 | 22890.25 | 26-JUN-06:04 | 8728.24 | 12-JUN-06:01 | 0.00 | 01-JUN-00:10 |
July | 0.237418E+11 | 0.593734E+10 | 371.05 | 0.136601E+11 | 0.100817E+11 | 0.00 | 1.00 | 01-JUL-06:01 | 0.00 | 01-JUL-00:03 | 38166.95 | 23-JUL-07:01 | 24791.95 | 05-JUL-06:01 | 23057.67 | 24-JUL-06:04 | 8636.13 | 02-JUL-07:12 | 0.00 | 01-JUL-00:03 |
August | 0.239380E+11 | 0.579167E+10 | 379.11 | 0.128579E+11 | 0.110801E+11 | 0.00 | 1.00 | 01-AUG-06:01 | 0.00 | 01-AUG-00:10 | 38250.01 | 21-AUG-06:02 | 21677.56 | 03-AUG-06:01 | 24488.64 | 28-AUG-06:06 | 8283.50 | 08-AUG-06:13 | 0.00 | 01-AUG-00:10 |
September | 0.192562E+11 | 0.473140E+10 | 359.61 | 0.112417E+11 | 0.801449E+10 | 0.00 | 1.00 | 01-SEP-06:01 | 0.00 | 01-SEP-00:03 | 38259.49 | 10-SEP-07:02 | 24234.34 | 27-SEP-06:02 | 24016.03 | 11-SEP-06:03 | 8028.11 | 22-SEP-06:01 | 0.00 | 01-SEP-00:03 |
October | 0.124220E+11 | 0.329865E+10 | 360.10 | 0.988889E+10 | 0.253312E+10 | 0.00 | 1.00 | 01-OCT-07:02 | 0.00 | 01-OCT-00:10 | 36102.45 | 12-OCT-06:02 | 27953.06 | 02-OCT-06:01 | 14718.33 | 12-OCT-06:02 | 7802.44 | 04-OCT-06:02 | 0.00 | 01-OCT-00:10 |
November | 0.650179E+10 | 0.174612E+10 | 306.72 | 0.570631E+10 | 0.795486E+09 | 0.00 | 0.73 | 04-NOV-13:00 | 0.00 | 01-NOV-00:10 | 11152.59 | 09-NOV-07:03 | 9895.06 | 04-NOV-14:00 | 3736.42 | 09-NOV-07:03 | 2894.65 | 04-NOV-13:00 | 0.00 | 01-NOV-00:10 |
December | 0.160559E+10 | 0.436763E+09 | 212.17 | 0.142167E+10 | 0.183922E+09 | 0.00 | 0.42 | 02-DEC-14:00 | 0.00 | 01-DEC-00:10 | 5498.13 | 02-DEC-14:00 | 5498.13 | 02-DEC-14:00 | 898.36 | 16-DEC-14:00 | 1479.86 | 28-DEC-14:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.151766E+12 | 0.399368E+11 | 3767.87 | 0.106405E+12 | 0.453618E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.661839E+09 | 0.181139E+09 | 122.17 | 0.600586E+09 | 61253027.57 | 0.00 | 0.32 | 0.00 | 4234.26 | 3984.33 | 784.13 | 1151.80 | 0.00 | |||||||
Maximum of Months | 0.239380E+11 | 0.593734E+10 | 379.11 | 0.152080E+11 | 0.110801E+11 | 0.00 | 1.00 | 0.00 | 38259.49 | 32408.37 | 24488.64 | 8728.24 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_5:5 COOLING COIL
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.534699E+09 | 0.146847E+09 | 107.50 | 0.483789E+09 | 50909727.72 | 0.00 | 0.31 | 12-JAN-15:00 | 0.00 | 01-JAN-00:10 | 3953.51 | 12-JAN-15:00 | 3716.21 | 12-JAN-15:00 | 734.38 | 14-JAN-14:00 | 1080.84 | 12-JAN-15:00 | 0.00 | 01-JAN-00:10 |
February | 0.266047E+10 | 0.722594E+09 | 216.25 | 0.235678E+10 | 0.303691E+09 | 0.00 | 0.54 | 22-FEB-14:00 | 0.00 | 01-FEB-00:05 | 7466.76 | 22-FEB-14:00 | 6848.90 | 22-FEB-14:00 | 1635.56 | 25-FEB-16:30 | 2027.79 | 22-FEB-14:00 | 0.00 | 01-FEB-00:05 |
March | 0.750114E+10 | 0.205178E+10 | 330.93 | 0.656092E+10 | 0.940217E+09 | 0.00 | 1.00 | 11-MAR-07:03 | 0.00 | 01-MAR-00:10 | 24888.01 | 11-MAR-07:03 | 17861.34 | 30-MAR-06:03 | 7682.44 | 11-MAR-07:03 | 5414.94 | 11-MAR-07:03 | 0.00 | 01-MAR-00:10 |
April | 0.125228E+11 | 0.358834E+10 | 354.50 | 0.112962E+11 | 0.122661E+10 | 0.00 | 1.00 | 02-APR-07:02 | 0.00 | 01-APR-00:05 | 34889.94 | 17-APR-06:01 | 31930.10 | 28-APR-06:01 | 9059.72 | 17-APR-06:01 | 8183.50 | 27-APR-06:01 | 0.00 | 01-APR-00:05 |
May | 0.187575E+11 | 0.537769E+10 | 376.66 | 0.150489E+11 | 0.370855E+10 | 0.00 | 1.00 | 01-MAY-06:01 | 0.00 | 01-MAY-00:10 | 37268.56 | 23-MAY-06:02 | 32204.17 | 06-MAY-06:01 | 18937.53 | 23-MAY-06:03 | 8407.79 | 04-MAY-06:01 | 0.00 | 01-MAY-00:10 |
June | 0.211797E+11 | 0.580788E+10 | 368.13 | 0.148726E+11 | 0.630716E+10 | 0.00 | 1.00 | 01-JUN-06:01 | 0.00 | 01-JUN-00:10 | 37945.75 | 26-JUN-06:01 | 30223.43 | 12-JUN-06:01 | 22883.55 | 26-JUN-06:04 | 8684.84 | 12-JUN-06:01 | 0.00 | 01-JUN-00:10 |
July | 0.235503E+11 | 0.588939E+10 | 370.79 | 0.135181E+11 | 0.100322E+11 | 0.00 | 1.00 | 01-JUL-06:01 | 0.00 | 01-JUL-00:03 | 37978.92 | 23-JUL-07:01 | 24607.97 | 05-JUL-06:01 | 23040.31 | 24-JUL-06:04 | 8593.28 | 02-JUL-07:12 | 0.00 | 01-JUL-00:03 |
August | 0.237144E+11 | 0.573740E+10 | 378.86 | 0.126958E+11 | 0.110186E+11 | 0.00 | 1.00 | 01-AUG-06:01 | 0.00 | 01-AUG-00:10 | 38061.58 | 21-AUG-06:03 | 21398.05 | 03-AUG-06:01 | 24467.00 | 28-AUG-06:06 | 8242.73 | 08-AUG-06:13 | 0.00 | 01-AUG-00:10 |
September | 0.190390E+11 | 0.467944E+10 | 359.07 | 0.110815E+11 | 0.795748E+10 | 0.00 | 1.00 | 01-SEP-06:01 | 0.00 | 01-SEP-00:03 | 38071.01 | 10-SEP-07:02 | 23963.99 | 27-SEP-06:02 | 24027.18 | 11-SEP-06:03 | 7988.46 | 22-SEP-06:01 | 0.00 | 01-SEP-00:03 |
October | 0.122134E+11 | 0.324817E+10 | 359.23 | 0.971259E+10 | 0.250078E+10 | 0.00 | 1.00 | 01-OCT-07:02 | 0.00 | 01-OCT-00:10 | 35917.63 | 12-OCT-06:02 | 27731.99 | 02-OCT-06:01 | 14808.77 | 12-OCT-06:02 | 7763.12 | 04-OCT-06:02 | 0.00 | 01-OCT-00:10 |
November | 0.628494E+10 | 0.169223E+10 | 302.97 | 0.551273E+10 | 0.772208E+09 | 0.00 | 0.72 | 04-NOV-13:00 | 0.00 | 01-NOV-00:10 | 10598.07 | 09-NOV-13:40 | 9733.78 | 04-NOV-14:00 | 3149.22 | 09-NOV-07:03 | 2853.20 | 04-NOV-13:00 | 0.00 | 01-NOV-00:10 |
December | 0.139801E+10 | 0.381521E+09 | 198.00 | 0.123991E+10 | 0.158106E+09 | 0.00 | 0.41 | 02-DEC-14:00 | 0.00 | 01-DEC-00:10 | 5308.40 | 02-DEC-14:00 | 5308.40 | 02-DEC-14:00 | 854.36 | 16-DEC-14:00 | 1425.64 | 02-DEC-14:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.149356E+12 | 0.393233E+11 | 3722.89 | 0.104380E+12 | 0.449765E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.534699E+09 | 0.146847E+09 | 107.50 | 0.483789E+09 | 50909727.72 | 0.00 | 0.31 | 0.00 | 3953.51 | 3716.21 | 734.38 | 1080.84 | 0.00 | |||||||
Maximum of Months | 0.237144E+11 | 0.588939E+10 | 378.86 | 0.150489E+11 | 0.110186E+11 | 0.00 | 1.00 | 0.00 | 38071.01 | 32204.17 | 24467.00 | 8684.84 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_6:6 COOLING COIL
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.752908E+09 | 0.210979E+09 | 85.83 | 0.665286E+09 | 87622151.44 | 0.00 | 0.30 | 12-JAN-15:10 | 0.00 | 01-JAN-00:10 | 7015.30 | 12-JAN-15:10 | 6411.48 | 12-JAN-15:10 | 1375.59 | 14-JAN-15:10 | 1953.31 | 12-JAN-15:10 | 0.00 | 01-JAN-00:10 |
February | 0.439434E+10 | 0.121865E+10 | 209.33 | 0.381861E+10 | 0.575724E+09 | 0.00 | 0.55 | 22-FEB-14:00 | 0.00 | 01-FEB-00:05 | 13794.26 | 22-FEB-14:00 | 12360.52 | 22-FEB-15:10 | 3426.23 | 25-FEB-16:00 | 3799.25 | 22-FEB-14:00 | 0.00 | 01-FEB-00:05 |
March | 0.133957E+11 | 0.373198E+10 | 328.22 | 0.115070E+11 | 0.188864E+10 | 0.00 | 1.00 | 11-MAR-08:62 | 0.00 | 01-MAR-00:10 | 39845.40 | 11-MAR-08:62 | 28206.82 | 11-MAR-08:62 | 11638.59 | 11-MAR-08:62 | 8932.49 | 11-MAR-08:62 | 0.00 | 01-MAR-00:10 |
April | 0.227610E+11 | 0.663653E+10 | 343.85 | 0.203892E+11 | 0.237182E+10 | 0.00 | 1.00 | 02-APR-08:62 | 0.00 | 01-APR-00:05 | 62969.65 | 17-APR-07:01 | 57232.56 | 28-APR-07:02 | 17606.59 | 17-APR-07:03 | 15059.06 | 16-APR-08:61 | 0.00 | 01-APR-00:05 |
May | 0.343783E+11 | 0.100182E+11 | 367.37 | 0.273326E+11 | 0.704568E+10 | 0.00 | 1.00 | 01-MAY-07:01 | 0.00 | 01-MAY-00:10 | 66090.55 | 21-MAY-08:61 | 58039.20 | 07-MAY-08:61 | 28278.85 | 21-MAY-08:04 | 15855.10 | 04-MAY-07:01 | 0.00 | 01-MAY-00:10 |
June | 0.388817E+11 | 0.108377E+11 | 359.25 | 0.270453E+11 | 0.118364E+11 | 0.00 | 1.00 | 01-JUN-07:02 | 0.00 | 01-JUN-00:10 | 68629.50 | 25-JUN-08:62 | 54687.53 | 07-JUN-07:01 | 41339.51 | 26-JUN-07:04 | 16229.07 | 12-JUN-07:01 | 0.00 | 01-JUN-00:10 |
July | 0.429338E+11 | 0.108861E+11 | 359.66 | 0.242493E+11 | 0.186845E+11 | 0.00 | 1.00 | 01-JUL-07:01 | 0.00 | 01-JUL-00:03 | 68615.59 | 23-JUL-08:61 | 47288.87 | 07-JUL-07:01 | 41643.04 | 23-JUL-08:04 | 15917.99 | 02-JUL-08:14 | 0.00 | 01-JUL-00:03 |
August | 0.434788E+11 | 0.106554E+11 | 370.77 | 0.228067E+11 | 0.206720E+11 | 0.00 | 1.00 | 01-AUG-07:01 | 0.00 | 01-AUG-00:10 | 68831.45 | 21-AUG-07:02 | 42186.62 | 08-AUG-07:01 | 43968.12 | 28-AUG-07:06 | 15235.60 | 08-AUG-07:01 | 0.00 | 01-AUG-00:10 |
September | 0.345514E+11 | 0.861146E+10 | 348.46 | 0.197672E+11 | 0.147842E+11 | 0.00 | 1.00 | 01-SEP-07:01 | 0.00 | 01-SEP-00:03 | 68862.67 | 04-SEP-08:61 | 45412.41 | 27-SEP-07:02 | 43495.31 | 11-SEP-07:03 | 14863.39 | 24-SEP-08:04 | 0.00 | 01-SEP-00:03 |
October | 0.221752E+11 | 0.598495E+10 | 348.69 | 0.173505E+11 | 0.482473E+10 | 0.00 | 1.00 | 01-OCT-08:62 | 0.00 | 01-OCT-00:10 | 64180.15 | 01-OCT-08:62 | 49663.16 | 02-OCT-07:02 | 24691.50 | 12-OCT-07:03 | 14349.84 | 04-OCT-07:02 | 0.00 | 01-OCT-00:10 |
November | 0.110221E+11 | 0.302250E+10 | 305.31 | 0.946864E+10 | 0.155343E+10 | 0.00 | 0.74 | 04-NOV-14:30 | 0.00 | 01-NOV-00:10 | 19737.84 | 09-NOV-13:40 | 17963.78 | 04-NOV-14:20 | 4722.69 | 09-NOV-08:63 | 5398.07 | 04-NOV-14:30 | 0.00 | 01-NOV-00:10 |
December | 0.205234E+10 | 0.570870E+09 | 158.92 | 0.178928E+10 | 0.263059E+09 | 0.00 | 0.39 | 02-DEC-14:20 | 0.00 | 01-DEC-00:10 | 9299.99 | 28-DEC-14:00 | 9041.58 | 02-DEC-14:20 | 1585.53 | 16-DEC-15:10 | 2571.66 | 28-DEC-14:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.270777E+12 | 0.723853E+11 | 3585.65 | 0.186190E+12 | 0.845878E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.752908E+09 | 0.210979E+09 | 85.83 | 0.665286E+09 | 87622151.44 | 0.00 | 0.30 | 0.00 | 7015.30 | 6411.48 | 1375.59 | 1953.31 | 0.00 | |||||||
Maximum of Months | 0.434788E+11 | 0.108861E+11 | 370.77 | 0.273326E+11 | 0.206720E+11 | 0.00 | 1.00 | 0.00 | 68862.67 | 58039.20 | 43968.12 | 16229.07 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_7:7 COOLING COIL
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.347434E+09 | 95829255.77 | 79.17 | 0.307759E+09 | 39674665.30 | 0.00 | 0.29 | 12-JAN-15:10 | 0.00 | 01-JAN-00:10 | 3573.44 | 12-JAN-15:10 | 3286.27 | 12-JAN-15:10 | 673.82 | 14-JAN-15:10 | 979.62 | 12-JAN-15:10 | 0.00 | 01-JAN-00:10 |
February | 0.223100E+10 | 0.608936E+09 | 206.83 | 0.194998E+10 | 0.281015E+09 | 0.00 | 0.54 | 22-FEB-15:10 | 0.00 | 01-FEB-00:05 | 7145.55 | 22-FEB-14:00 | 6448.06 | 22-FEB-15:10 | 1720.59 | 25-FEB-16:00 | 1936.83 | 22-FEB-14:00 | 0.00 | 01-FEB-00:05 |
March | 0.692610E+10 | 0.189889E+10 | 328.14 | 0.597534E+10 | 0.950765E+09 | 0.00 | 1.00 | 11-MAR-08:62 | 0.00 | 01-MAR-00:10 | 18996.03 | 11-MAR-08:62 | 13459.30 | 11-MAR-08:62 | 5536.73 | 11-MAR-08:62 | 4185.68 | 11-MAR-08:62 | 0.00 | 01-MAR-00:10 |
April | 0.118174E+11 | 0.339187E+10 | 343.89 | 0.106109E+11 | 0.120650E+10 | 0.00 | 1.00 | 02-APR-08:62 | 0.00 | 01-APR-00:05 | 33040.23 | 17-APR-07:01 | 29995.75 | 28-APR-07:02 | 8850.39 | 17-APR-07:03 | 7757.01 | 16-APR-08:61 | 0.00 | 01-APR-00:05 |
May | 0.178749E+11 | 0.513199E+10 | 367.47 | 0.142429E+11 | 0.363194E+10 | 0.00 | 1.00 | 01-MAY-07:01 | 0.00 | 01-MAY-00:10 | 34661.03 | 21-MAY-08:61 | 30449.03 | 29-MAY-08:61 | 14845.37 | 21-MAY-08:04 | 8164.50 | 04-MAY-07:01 | 0.00 | 01-MAY-00:10 |
June | 0.201905E+11 | 0.554725E+10 | 358.95 | 0.140775E+11 | 0.611303E+10 | 0.00 | 1.00 | 01-JUN-07:02 | 0.00 | 01-JUN-00:10 | 35985.81 | 25-JUN-08:62 | 28688.43 | 07-JUN-07:01 | 21748.94 | 26-JUN-07:04 | 8360.76 | 12-JUN-07:01 | 0.00 | 01-JUN-00:10 |
July | 0.222966E+11 | 0.557003E+10 | 359.53 | 0.126300E+11 | 0.966660E+10 | 0.00 | 1.00 | 01-JUL-07:01 | 0.00 | 01-JUL-00:03 | 35978.51 | 23-JUL-08:61 | 24848.39 | 07-JUL-07:01 | 21888.41 | 23-JUL-08:04 | 8201.09 | 02-JUL-08:14 | 0.00 | 01-JUL-00:03 |
August | 0.225606E+11 | 0.544738E+10 | 370.84 | 0.118678E+11 | 0.106928E+11 | 0.00 | 1.00 | 01-AUG-07:01 | 0.00 | 01-AUG-00:10 | 36091.70 | 21-AUG-07:02 | 22195.60 | 08-AUG-07:01 | 23289.04 | 28-AUG-07:04 | 7848.59 | 08-AUG-07:01 | 0.00 | 01-AUG-00:10 |
September | 0.179353E+11 | 0.440194E+10 | 348.51 | 0.102911E+11 | 0.764418E+10 | 0.00 | 1.00 | 01-SEP-07:01 | 0.00 | 01-SEP-00:03 | 36108.07 | 04-SEP-08:61 | 23925.49 | 27-SEP-07:02 | 22942.62 | 11-SEP-07:03 | 7656.98 | 24-SEP-08:04 | 0.00 | 01-SEP-00:03 |
October | 0.115024E+11 | 0.305593E+10 | 349.23 | 0.903475E+10 | 0.246766E+10 | 0.00 | 1.00 | 01-OCT-08:62 | 0.00 | 01-OCT-00:10 | 33672.18 | 01-OCT-08:62 | 26116.76 | 02-OCT-07:02 | 11818.92 | 12-OCT-07:03 | 7390.26 | 04-OCT-07:02 | 0.00 | 01-OCT-00:10 |
November | 0.570315E+10 | 0.153870E+10 | 305.56 | 0.492290E+10 | 0.780254E+09 | 0.00 | 0.74 | 04-NOV-14:30 | 0.00 | 01-NOV-00:10 | 10285.41 | 06-NOV-14:00 | 9399.55 | 04-NOV-14:20 | 2069.74 | 09-NOV-08:63 | 2767.80 | 04-NOV-14:40 | 0.00 | 01-NOV-00:10 |
December | 0.101131E+10 | 0.276809E+09 | 152.33 | 0.887791E+09 | 0.123515E+09 | 0.00 | 0.38 | 02-DEC-14:20 | 0.00 | 01-DEC-00:10 | 4755.59 | 28-DEC-14:00 | 4688.11 | 02-DEC-14:20 | 785.72 | 16-DEC-15:10 | 1295.05 | 28-DEC-14:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.140397E+12 | 0.369655E+11 | 3570.45 | 0.967986E+11 | 0.435980E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.347434E+09 | 95829255.77 | 79.17 | 0.307759E+09 | 39674665.30 | 0.00 | 0.29 | 0.00 | 3573.44 | 3286.27 | 673.82 | 979.62 | 0.00 | |||||||
Maximum of Months | 0.225606E+11 | 0.557003E+10 | 370.84 | 0.142429E+11 | 0.106928E+11 | 0.00 | 1.00 | 0.00 | 36108.07 | 30449.03 | 23289.04 | 8360.76 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_8:8 COOLING COIL
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.325459E+09 | 89854638.82 | 75.17 | 0.287868E+09 | 37590936.19 | 0.00 | 0.29 | 12-JAN-15:10 | 0.00 | 01-JAN-00:10 | 3500.44 | 12-JAN-15:10 | 3217.77 | 12-JAN-15:10 | 658.43 | 14-JAN-15:10 | 960.85 | 12-JAN-15:10 | 0.00 | 01-JAN-00:10 |
February | 0.217742E+10 | 0.594925E+09 | 205.75 | 0.190334E+10 | 0.274086E+09 | 0.00 | 0.54 | 22-FEB-15:10 | 0.00 | 01-FEB-00:05 | 7078.12 | 22-FEB-15:10 | 6388.20 | 22-FEB-15:10 | 1698.25 | 25-FEB-16:00 | 1920.72 | 22-FEB-15:10 | 0.00 | 01-FEB-00:05 |
March | 0.685710E+10 | 0.188119E+10 | 326.72 | 0.591424E+10 | 0.942856E+09 | 0.00 | 1.00 | 11-MAR-08:62 | 0.00 | 01-MAR-00:10 | 18356.54 | 11-MAR-08:62 | 12972.34 | 11-MAR-08:62 | 5384.21 | 11-MAR-08:62 | 4045.51 | 11-MAR-08:62 | 0.00 | 01-MAR-00:10 |
April | 0.117655E+11 | 0.337760E+10 | 344.00 | 0.105629E+11 | 0.120260E+10 | 0.00 | 1.00 | 02-APR-08:62 | 0.00 | 01-APR-00:05 | 32951.43 | 17-APR-07:01 | 29911.20 | 28-APR-07:02 | 8762.10 | 17-APR-07:03 | 7736.17 | 16-APR-08:61 | 0.00 | 01-APR-00:05 |
May | 0.178262E+11 | 0.511769E+10 | 367.47 | 0.142018E+11 | 0.362442E+10 | 0.00 | 1.00 | 01-MAY-07:01 | 0.00 | 01-MAY-00:10 | 34567.74 | 21-MAY-08:61 | 30371.20 | 29-MAY-08:61 | 14810.96 | 21-MAY-08:04 | 8142.71 | 04-MAY-07:01 | 0.00 | 01-MAY-00:10 |
June | 0.201391E+11 | 0.553246E+10 | 359.03 | 0.140369E+11 | 0.610218E+10 | 0.00 | 1.00 | 01-JUN-07:02 | 0.00 | 01-JUN-00:10 | 35889.93 | 25-JUN-08:62 | 28618.83 | 07-JUN-07:01 | 21702.66 | 26-JUN-07:04 | 8338.63 | 12-JUN-07:01 | 0.00 | 01-JUN-00:10 |
July | 0.222487E+11 | 0.555686E+10 | 359.53 | 0.125952E+11 | 0.965343E+10 | 0.00 | 1.00 | 01-JUL-07:01 | 0.00 | 01-JUL-00:03 | 35882.66 | 23-JUL-08:03 | 24778.41 | 07-JUL-07:01 | 21841.83 | 23-JUL-08:04 | 8179.02 | 02-JUL-08:14 | 0.00 | 01-JUL-00:03 |
August | 0.225095E+11 | 0.543384E+10 | 370.84 | 0.118312E+11 | 0.106783E+11 | 0.00 | 1.00 | 01-AUG-07:01 | 0.00 | 01-AUG-00:10 | 35995.54 | 21-AUG-07:03 | 22132.43 | 08-AUG-07:01 | 23228.34 | 28-AUG-07:04 | 7827.69 | 08-AUG-07:01 | 0.00 | 01-AUG-00:10 |
September | 0.178861E+11 | 0.438927E+10 | 348.52 | 0.102551E+11 | 0.763100E+10 | 0.00 | 1.00 | 01-SEP-07:01 | 0.00 | 01-SEP-00:03 | 36011.86 | 04-SEP-08:61 | 23847.08 | 27-SEP-07:02 | 22900.37 | 11-SEP-07:03 | 7636.57 | 24-SEP-08:04 | 0.00 | 01-SEP-00:03 |
October | 0.114511E+11 | 0.304279E+10 | 348.94 | 0.899140E+10 | 0.245974E+10 | 0.00 | 1.00 | 01-OCT-08:62 | 0.00 | 01-OCT-00:10 | 33581.35 | 01-OCT-08:62 | 26049.74 | 02-OCT-07:02 | 11677.65 | 12-OCT-07:03 | 7370.75 | 04-OCT-07:02 | 0.00 | 01-OCT-00:10 |
November | 0.564401E+10 | 0.152363E+10 | 304.47 | 0.487067E+10 | 0.773338E+09 | 0.00 | 0.74 | 04-NOV-14:30 | 0.00 | 01-NOV-00:10 | 10232.55 | 06-NOV-14:00 | 9351.60 | 04-NOV-14:20 | 2020.68 | 08-NOV-18:00 | 2755.32 | 04-NOV-14:40 | 0.00 | 01-NOV-00:10 |
December | 0.970072E+09 | 0.265750E+09 | 148.75 | 0.851996E+09 | 0.118076E+09 | 0.00 | 0.38 | 02-DEC-14:20 | 0.00 | 01-DEC-00:10 | 4686.50 | 28-DEC-14:00 | 4632.10 | 02-DEC-14:20 | 770.44 | 16-DEC-15:10 | 1277.66 | 28-DEC-14:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.139800E+12 | 0.368058E+11 | 3559.20 | 0.963027E+11 | 0.434976E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.325459E+09 | 89854638.82 | 75.17 | 0.287868E+09 | 37590936.19 | 0.00 | 0.29 | 0.00 | 3500.44 | 3217.77 | 658.43 | 960.85 | 0.00 | |||||||
Maximum of Months | 0.225095E+11 | 0.555686E+10 | 370.84 | 0.142018E+11 | 0.106783E+11 | 0.00 | 1.00 | 0.00 | 36011.86 | 30371.20 | 23228.34 | 8338.63 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_9:9 COOLING COIL
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.282728E+09 | 78240073.65 | 69.33 | 0.249448E+09 | 33279825.77 | 0.00 | 0.27 | 12-JAN-15:10 | 0.00 | 01-JAN-00:10 | 3348.88 | 12-JAN-15:10 | 3077.61 | 12-JAN-15:10 | 624.77 | 14-JAN-15:10 | 922.37 | 12-JAN-15:10 | 0.00 | 01-JAN-00:10 |
February | 0.205776E+10 | 0.563858E+09 | 199.58 | 0.180068E+10 | 0.257076E+09 | 0.00 | 0.53 | 22-FEB-15:10 | 0.00 | 01-FEB-00:05 | 6961.40 | 22-FEB-15:10 | 6281.10 | 22-FEB-15:10 | 1643.51 | 25-FEB-16:00 | 1894.27 | 22-FEB-15:10 | 0.00 | 01-FEB-00:05 |
March | 0.672505E+10 | 0.184899E+10 | 323.14 | 0.580066E+10 | 0.924386E+09 | 0.00 | 0.99 | 11-MAR-08:62 | 0.00 | 01-MAR-00:10 | 16163.31 | 11-MAR-08:62 | 12137.42 | 28-MAR-15:00 | 4835.38 | 11-MAR-08:62 | 3571.22 | 11-MAR-08:62 | 0.00 | 01-MAR-00:10 |
April | 0.117703E+11 | 0.338110E+10 | 344.36 | 0.105689E+11 | 0.120136E+10 | 0.00 | 1.00 | 02-APR-08:62 | 0.00 | 01-APR-00:05 | 33084.24 | 17-APR-07:01 | 30022.81 | 28-APR-07:02 | 8821.73 | 03-APR-07:02 | 7767.95 | 16-APR-08:61 | 0.00 | 01-APR-00:05 |
May | 0.179289E+11 | 0.514852E+10 | 367.40 | 0.142947E+11 | 0.363417E+10 | 0.00 | 1.00 | 01-MAY-07:01 | 0.00 | 01-MAY-00:10 | 34708.36 | 21-MAY-08:61 | 30505.83 | 29-MAY-08:61 | 14882.86 | 21-MAY-08:04 | 8177.15 | 04-MAY-07:01 | 0.00 | 01-MAY-00:10 |
June | 0.202653E+11 | 0.556901E+10 | 359.02 | 0.141444E+11 | 0.612084E+10 | 0.00 | 1.00 | 01-JUN-07:02 | 0.00 | 01-JUN-00:10 | 36040.04 | 25-JUN-08:62 | 28788.85 | 07-JUN-07:01 | 21826.56 | 26-JUN-07:04 | 8374.64 | 12-JUN-07:01 | 0.00 | 01-JUN-00:10 |
July | 0.224087E+11 | 0.559883E+10 | 359.46 | 0.127185E+11 | 0.969015E+10 | 0.00 | 1.00 | 01-JUL-07:01 | 0.00 | 01-JUL-00:03 | 36032.73 | 23-JUL-08:61 | 24970.48 | 07-JUL-07:01 | 21941.44 | 23-JUL-08:04 | 8213.26 | 02-JUL-08:14 | 0.00 | 01-JUL-00:03 |
August | 0.226656E+11 | 0.547321E+10 | 370.89 | 0.119461E+11 | 0.107194E+11 | 0.00 | 1.00 | 01-AUG-07:01 | 0.00 | 01-AUG-00:10 | 36146.09 | 21-AUG-07:02 | 22333.63 | 08-AUG-07:01 | 23252.93 | 28-AUG-07:06 | 7860.40 | 08-AUG-07:01 | 0.00 | 01-AUG-00:10 |
September | 0.179884E+11 | 0.441568E+10 | 348.48 | 0.103342E+11 | 0.765417E+10 | 0.00 | 1.00 | 01-SEP-07:01 | 0.00 | 01-SEP-00:03 | 36162.48 | 04-SEP-08:61 | 23969.56 | 27-SEP-07:02 | 23031.55 | 11-SEP-07:03 | 7668.53 | 24-SEP-08:04 | 0.00 | 01-SEP-00:03 |
October | 0.114696E+11 | 0.304873E+10 | 348.64 | 0.901019E+10 | 0.245945E+10 | 0.00 | 1.00 | 01-OCT-08:62 | 0.00 | 01-OCT-00:10 | 33722.51 | 01-OCT-08:62 | 26169.22 | 02-OCT-07:02 | 11516.53 | 01-OCT-08:62 | 7400.61 | 04-OCT-07:02 | 0.00 | 01-OCT-00:10 |
November | 0.554240E+10 | 0.149879E+10 | 301.22 | 0.478367E+10 | 0.758721E+09 | 0.00 | 0.73 | 04-NOV-14:30 | 0.00 | 01-NOV-00:10 | 10204.22 | 09-NOV-13:50 | 9314.04 | 04-NOV-14:20 | 2007.62 | 08-NOV-18:00 | 2748.56 | 04-NOV-14:40 | 0.00 | 01-NOV-00:10 |
December | 0.884214E+09 | 0.242792E+09 | 138.08 | 0.777989E+09 | 0.106224E+09 | 0.00 | 0.37 | 02-DEC-14:20 | 0.00 | 01-DEC-00:10 | 4560.39 | 28-DEC-14:00 | 4497.25 | 02-DEC-14:20 | 737.69 | 16-DEC-15:10 | 1246.84 | 28-DEC-14:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.139989E+12 | 0.368678E+11 | 3529.61 | 0.964296E+11 | 0.435593E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.282728E+09 | 78240073.65 | 69.33 | 0.249448E+09 | 33279825.77 | 0.00 | 0.27 | 0.00 | 3348.88 | 3077.61 | 624.77 | 922.37 | 0.00 | |||||||
Maximum of Months | 0.226656E+11 | 0.559883E+10 | 370.89 | 0.142947E+11 | 0.107194E+11 | 0.00 | 1.00 | 0.00 | 36162.48 | 30505.83 | 23252.93 | 8374.64 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_10:10 COOLING COIL
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.329311E+09 | 91207986.55 | 73.17 | 0.295872E+09 | 33439585.84 | 0.00 | 0.26 | 12-JAN-15:10 | 0.00 | 01-JAN-00:10 | 3596.17 | 12-JAN-15:10 | 3357.44 | 12-JAN-15:10 | 624.25 | 14-JAN-15:10 | 993.64 | 12-JAN-15:10 | 0.00 | 01-JAN-00:10 |
February | 0.225167E+10 | 0.618450E+09 | 200.00 | 0.200121E+10 | 0.250459E+09 | 0.00 | 0.52 | 22-FEB-14:00 | 0.00 | 01-FEB-00:05 | 7693.03 | 22-FEB-14:00 | 7009.20 | 22-FEB-14:00 | 1617.65 | 25-FEB-16:00 | 2098.44 | 22-FEB-14:00 | 0.00 | 01-FEB-00:05 |
March | 0.735579E+10 | 0.203041E+10 | 320.32 | 0.643109E+10 | 0.924702E+09 | 0.00 | 0.87 | 28-MAR-15:00 | 0.00 | 01-MAR-00:10 | 13736.31 | 29-MAR-13:00 | 13335.89 | 28-MAR-15:00 | 3611.77 | 11-MAR-08:62 | 3925.98 | 28-MAR-15:00 | 0.00 | 01-MAR-00:10 |
April | 0.133310E+11 | 0.383282E+10 | 345.04 | 0.120846E+11 | 0.124639E+10 | 0.00 | 1.00 | 02-APR-08:62 | 0.00 | 01-APR-00:05 | 37312.16 | 17-APR-07:01 | 33917.18 | 28-APR-07:02 | 9799.42 | 17-APR-07:01 | 8748.64 | 16-APR-08:61 | 0.00 | 01-APR-00:05 |
May | 0.203375E+11 | 0.586383E+10 | 368.71 | 0.164872E+11 | 0.385027E+10 | 0.00 | 1.00 | 01-MAY-07:01 | 0.00 | 01-MAY-00:10 | 39405.12 | 24-MAY-07:02 | 34873.15 | 29-MAY-08:61 | 18687.75 | 24-MAY-07:02 | 9218.49 | 04-MAY-07:01 | 0.00 | 01-MAY-00:10 |
June | 0.227841E+11 | 0.630803E+10 | 360.57 | 0.163152E+11 | 0.646889E+10 | 0.00 | 1.00 | 01-JUN-07:02 | 0.00 | 01-JUN-00:10 | 40586.19 | 25-JUN-08:62 | 33604.36 | 12-JUN-07:01 | 25245.72 | 26-JUN-07:04 | 9436.32 | 12-JUN-07:01 | 0.00 | 01-JUN-00:10 |
July | 0.251451E+11 | 0.633987E+10 | 361.24 | 0.148072E+11 | 0.103379E+11 | 0.00 | 1.00 | 01-JUL-07:01 | 0.00 | 01-JUL-00:03 | 40577.96 | 23-JUL-08:03 | 29036.72 | 07-JUL-07:01 | 25131.02 | 23-JUL-08:04 | 9250.99 | 02-JUL-08:14 | 0.00 | 01-JUL-00:03 |
August | 0.254171E+11 | 0.619271E+10 | 371.56 | 0.139980E+11 | 0.114191E+11 | 0.00 | 1.00 | 01-AUG-07:01 | 0.00 | 01-AUG-00:10 | 40705.62 | 21-AUG-07:02 | 25391.67 | 09-AUG-07:01 | 25765.03 | 28-AUG-07:07 | 8851.98 | 08-AUG-07:03 | 0.00 | 01-AUG-00:10 |
September | 0.201846E+11 | 0.499390E+10 | 349.57 | 0.120564E+11 | 0.812817E+10 | 0.00 | 1.00 | 01-SEP-07:01 | 0.00 | 01-SEP-00:03 | 40724.08 | 04-SEP-08:61 | 27950.40 | 27-SEP-07:02 | 25729.07 | 10-SEP-08:62 | 8635.82 | 24-SEP-08:04 | 0.00 | 01-SEP-00:03 |
October | 0.130284E+11 | 0.346434E+10 | 347.91 | 0.104378E+11 | 0.259061E+10 | 0.00 | 1.00 | 01-OCT-08:62 | 0.00 | 01-OCT-00:10 | 38022.02 | 01-OCT-08:62 | 30097.87 | 02-OCT-07:02 | 12364.59 | 01-OCT-08:62 | 8329.15 | 04-OCT-07:02 | 0.00 | 01-OCT-00:10 |
November | 0.616048E+10 | 0.166899E+10 | 299.64 | 0.539794E+10 | 0.762542E+09 | 0.00 | 0.72 | 09-NOV-13:30 | 0.00 | 01-NOV-00:10 | 11372.69 | 09-NOV-13:30 | 10293.32 | 04-NOV-14:10 | 2058.48 | 08-NOV-18:00 | 3035.28 | 09-NOV-13:30 | 0.00 | 01-NOV-00:10 |
December | 0.100748E+10 | 0.276886E+09 | 143.25 | 0.901268E+09 | 0.106209E+09 | 0.00 | 0.35 | 02-DEC-14:10 | 0.00 | 01-DEC-00:10 | 4948.73 | 28-DEC-14:00 | 4820.98 | 02-DEC-14:10 | 762.71 | 16-DEC-14:30 | 1357.51 | 28-DEC-14:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.157333E+12 | 0.416814E+11 | 3540.98 | 0.111214E+12 | 0.461187E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.329311E+09 | 91207986.55 | 73.17 | 0.295872E+09 | 33439585.84 | 0.00 | 0.26 | 0.00 | 3596.17 | 3357.44 | 624.25 | 993.64 | 0.00 | |||||||
Maximum of Months | 0.254171E+11 | 0.633987E+10 | 371.56 | 0.164872E+11 | 0.114191E+11 | 0.00 | 1.00 | 0.00 | 40724.08 | 34873.15 | 25765.03 | 9436.32 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.69 | 41.13 | 26.56 | 102.14 | 55.60 | 0.00 | 0.00 | 0.00 |
February | 64.36 | 35.75 | 28.61 | 105.28 | 44.59 | 0.00 | 0.00 | 0.00 |
March | 55.03 | 24.31 | 30.72 | 104.85 | 26.72 | 0.00 | 0.00 | 0.00 |
April | 38.65 | 10.91 | 27.74 | 99.02 | 9.05 | 0.00 | 0.00 | 0.00 |
May | 27.80 | 2.06 | 25.74 | 91.69 | 1.47 | 0.00 | 0.00 | 0.00 |
June | 25.43 | 0.43 | 24.99 | 89.40 | 1.13 | 0.00 | 0.00 | 0.00 |
July | 26.52 | 0.36 | 26.16 | 83.34 | 0.33 | 0.00 | 0.00 | 0.00 |
August | 28.14 | 1.50 | 26.63 | 77.79 | 1.04 | 0.00 | 0.00 | 0.00 |
September | 37.72 | 9.79 | 27.93 | 88.22 | 4.21 | 0.00 | 0.00 | 0.00 |
October | 64.89 | 36.23 | 28.66 | 130.55 | 21.43 | 0.00 | 0.00 | 0.00 |
November | 81.05 | 53.57 | 27.48 | 142.36 | 41.05 | 0.00 | 0.00 | 0.00 |
December | 72.34 | 45.33 | 27.01 | 112.57 | 55.73 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 49.05 | 21.70 | 27.35 | 102.22 | 21.76 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 25.43 | 0.36 | 24.99 | 77.79 | 0.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 81.05 | 53.57 | 30.72 | 142.36 | 55.73 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.69 | 41.13 | 26.56 | 102.14 | 55.60 | 0.00 | 0.00 | 0.00 |
February | 64.36 | 35.75 | 28.61 | 105.28 | 44.59 | 0.00 | 0.00 | 0.00 |
March | 55.03 | 24.31 | 30.72 | 104.85 | 26.72 | 0.00 | 0.00 | 0.00 |
April | 38.65 | 10.91 | 27.74 | 99.02 | 9.05 | 0.00 | 0.00 | 0.00 |
May | 27.80 | 2.06 | 25.74 | 91.69 | 1.47 | 0.00 | 0.00 | 0.00 |
June | 25.43 | 0.43 | 24.99 | 89.40 | 1.13 | 0.00 | 0.00 | 0.00 |
July | 26.52 | 0.36 | 26.16 | 83.34 | 0.33 | 0.00 | 0.00 | 0.00 |
August | 28.14 | 1.50 | 26.63 | 77.79 | 1.04 | 0.00 | 0.00 | 0.00 |
September | 37.72 | 9.79 | 27.93 | 88.22 | 4.21 | 0.00 | 0.00 | 0.00 |
October | 64.89 | 36.23 | 28.66 | 130.55 | 21.43 | 0.00 | 0.00 | 0.00 |
November | 81.05 | 53.57 | 27.48 | 142.36 | 41.05 | 0.00 | 0.00 | 0.00 |
December | 72.34 | 45.33 | 27.01 | 112.57 | 55.73 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 49.05 | 21.70 | 27.35 | 102.22 | 21.76 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 25.43 | 0.36 | 24.99 | 77.79 | 0.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 81.05 | 53.57 | 30.72 | 142.36 | 55.73 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.69 | 41.13 | 26.56 | 102.14 | 55.60 | 0.00 | 0.00 | 0.00 |
February | 64.36 | 35.75 | 28.61 | 105.28 | 44.59 | 0.00 | 0.00 | 0.00 |
March | 55.03 | 24.31 | 30.72 | 104.85 | 26.72 | 0.00 | 0.00 | 0.00 |
April | 38.65 | 10.91 | 27.74 | 99.02 | 9.05 | 0.00 | 0.00 | 0.00 |
May | 27.80 | 2.06 | 25.74 | 91.69 | 1.47 | 0.00 | 0.00 | 0.00 |
June | 25.43 | 0.43 | 24.99 | 89.40 | 1.13 | 0.00 | 0.00 | 0.00 |
July | 26.52 | 0.36 | 26.16 | 83.34 | 0.33 | 0.00 | 0.00 | 0.00 |
August | 28.14 | 1.50 | 26.63 | 77.79 | 1.04 | 0.00 | 0.00 | 0.00 |
September | 37.72 | 9.79 | 27.93 | 88.22 | 4.21 | 0.00 | 0.00 | 0.00 |
October | 64.89 | 36.23 | 28.66 | 130.55 | 21.43 | 0.00 | 0.00 | 0.00 |
November | 81.05 | 53.57 | 27.48 | 142.36 | 41.05 | 0.00 | 0.00 | 0.00 |
December | 72.34 | 45.33 | 27.01 | 112.57 | 55.73 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 49.05 | 21.70 | 27.35 | 102.22 | 21.76 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 25.43 | 0.36 | 24.99 | 77.79 | 0.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 81.05 | 53.57 | 30.72 | 142.36 | 55.73 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.69 | 41.13 | 26.56 | 102.14 | 55.60 | 0.00 | 0.00 | 0.00 |
February | 64.36 | 35.75 | 28.61 | 105.28 | 44.59 | 0.00 | 0.00 | 0.00 |
March | 55.03 | 24.31 | 30.72 | 104.85 | 26.72 | 0.00 | 0.00 | 0.00 |
April | 38.65 | 10.91 | 27.74 | 99.02 | 9.05 | 0.00 | 0.00 | 0.00 |
May | 27.80 | 2.06 | 25.74 | 91.69 | 1.47 | 0.00 | 0.00 | 0.00 |
June | 25.43 | 0.43 | 24.99 | 89.40 | 1.13 | 0.00 | 0.00 | 0.00 |
July | 26.52 | 0.36 | 26.16 | 83.34 | 0.33 | 0.00 | 0.00 | 0.00 |
August | 28.14 | 1.50 | 26.63 | 77.79 | 1.04 | 0.00 | 0.00 | 0.00 |
September | 37.72 | 9.79 | 27.93 | 88.22 | 4.21 | 0.00 | 0.00 | 0.00 |
October | 64.89 | 36.23 | 28.66 | 130.55 | 21.43 | 0.00 | 0.00 | 0.00 |
November | 81.05 | 53.57 | 27.48 | 142.36 | 41.05 | 0.00 | 0.00 | 0.00 |
December | 72.34 | 45.33 | 27.01 | 112.57 | 55.73 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 49.05 | 21.70 | 27.35 | 102.22 | 21.76 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 25.43 | 0.36 | 24.99 | 77.79 | 0.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 81.05 | 53.57 | 30.72 | 142.36 | 55.73 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 81.37 | 49.44 | 31.93 | 122.84 | 66.26 | 0.00 | 0.00 | 0.00 |
February | 77.37 | 42.98 | 34.40 | 126.57 | 53.15 | 0.00 | 0.00 | 0.00 |
March | 66.16 | 29.22 | 36.94 | 125.78 | 31.94 | 0.00 | 0.00 | 0.00 |
April | 46.47 | 13.11 | 33.35 | 118.36 | 10.83 | 0.00 | 0.00 | 0.00 |
May | 33.42 | 2.47 | 30.94 | 109.10 | 1.79 | 0.00 | 0.00 | 0.00 |
June | 30.57 | 0.52 | 30.05 | 106.40 | 1.36 | 0.00 | 0.00 | 0.00 |
July | 31.88 | 0.44 | 31.45 | 99.24 | 0.40 | 0.00 | 0.00 | 0.00 |
August | 33.82 | 1.81 | 32.02 | 92.84 | 1.26 | 0.00 | 0.00 | 0.00 |
September | 45.34 | 11.77 | 33.57 | 105.50 | 5.04 | 0.00 | 0.00 | 0.00 |
October | 78.01 | 43.56 | 34.45 | 156.43 | 25.63 | 0.00 | 0.00 | 0.00 |
November | 97.44 | 64.40 | 33.03 | 170.85 | 49.02 | 0.00 | 0.00 | 0.00 |
December | 86.96 | 54.49 | 32.47 | 135.28 | 66.45 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 58.96 | 26.09 | 32.87 | 122.37 | 25.98 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.57 | 0.44 | 30.05 | 92.84 | 0.40 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 97.44 | 64.40 | 36.94 | 170.85 | 66.45 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 81.37 | 49.44 | 31.93 | 122.84 | 66.26 | 0.00 | 0.00 | 0.00 |
February | 77.37 | 42.98 | 34.40 | 126.57 | 53.15 | 0.00 | 0.00 | 0.00 |
March | 66.16 | 29.22 | 36.94 | 125.78 | 31.94 | 0.00 | 0.00 | 0.00 |
April | 46.47 | 13.11 | 33.35 | 118.36 | 10.83 | 0.00 | 0.00 | 0.00 |
May | 33.42 | 2.47 | 30.94 | 109.10 | 1.79 | 0.00 | 0.00 | 0.00 |
June | 30.57 | 0.52 | 30.05 | 106.40 | 1.36 | 0.00 | 0.00 | 0.00 |
July | 31.88 | 0.44 | 31.45 | 99.24 | 0.40 | 0.00 | 0.00 | 0.00 |
August | 33.82 | 1.81 | 32.02 | 92.84 | 1.26 | 0.00 | 0.00 | 0.00 |
September | 45.34 | 11.77 | 33.57 | 105.50 | 5.04 | 0.00 | 0.00 | 0.00 |
October | 78.01 | 43.56 | 34.45 | 156.43 | 25.63 | 0.00 | 0.00 | 0.00 |
November | 97.44 | 64.40 | 33.03 | 170.85 | 49.02 | 0.00 | 0.00 | 0.00 |
December | 86.96 | 54.49 | 32.47 | 135.28 | 66.45 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 58.96 | 26.09 | 32.87 | 122.37 | 25.98 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.57 | 0.44 | 30.05 | 92.84 | 0.40 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 97.44 | 64.40 | 36.94 | 170.85 | 66.45 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.69 | 41.13 | 26.56 | 100.78 | 58.78 | 8.00 | 0.00 | 0.00 |
February | 64.36 | 35.75 | 28.61 | 104.31 | 46.48 | 0.00 | 0.00 | 0.00 |
March | 55.03 | 24.31 | 30.72 | 104.57 | 27.44 | 0.00 | 0.00 | 0.00 |
April | 38.65 | 10.91 | 27.74 | 99.63 | 9.24 | 0.00 | 0.00 | 0.00 |
May | 27.80 | 2.06 | 25.74 | 92.99 | 1.45 | 0.00 | 0.00 | 0.00 |
June | 25.43 | 0.43 | 24.99 | 91.00 | 1.13 | 0.00 | 0.00 | 0.00 |
July | 26.52 | 0.36 | 26.16 | 84.88 | 0.30 | 0.00 | 0.00 | 0.00 |
August | 28.14 | 1.50 | 26.63 | 79.11 | 0.95 | 0.00 | 0.00 | 0.00 |
September | 37.72 | 9.79 | 27.93 | 89.10 | 3.98 | 0.00 | 0.00 | 0.00 |
October | 64.89 | 36.23 | 28.66 | 130.90 | 21.40 | 0.00 | 0.00 | 0.00 |
November | 81.05 | 53.57 | 27.48 | 142.06 | 41.61 | 0.00 | 0.00 | 0.00 |
December | 72.34 | 45.33 | 27.01 | 111.48 | 57.95 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 49.05 | 21.70 | 27.35 | 102.52 | 22.46 | 8.00 | 0.00 | 0.00 |
Minimum of Months | 25.43 | 0.36 | 24.99 | 79.11 | 0.30 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 81.05 | 53.57 | 30.72 | 142.06 | 58.78 | 8.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.69 | 41.13 | 26.56 | 100.78 | 58.78 | 8.00 | 0.00 | 0.00 |
February | 64.36 | 35.75 | 28.61 | 104.31 | 46.48 | 0.00 | 0.00 | 0.00 |
March | 55.03 | 24.31 | 30.72 | 104.57 | 27.44 | 0.00 | 0.00 | 0.00 |
April | 38.65 | 10.91 | 27.74 | 99.63 | 9.24 | 0.00 | 0.00 | 0.00 |
May | 27.80 | 2.06 | 25.74 | 92.99 | 1.45 | 0.00 | 0.00 | 0.00 |
June | 25.43 | 0.43 | 24.99 | 91.00 | 1.13 | 0.00 | 0.00 | 0.00 |
July | 26.52 | 0.36 | 26.16 | 84.88 | 0.30 | 0.00 | 0.00 | 0.00 |
August | 28.14 | 1.50 | 26.63 | 79.11 | 0.95 | 0.00 | 0.00 | 0.00 |
September | 37.72 | 9.79 | 27.93 | 89.10 | 3.98 | 0.00 | 0.00 | 0.00 |
October | 64.89 | 36.23 | 28.66 | 130.90 | 21.40 | 0.00 | 0.00 | 0.00 |
November | 81.05 | 53.57 | 27.48 | 142.06 | 41.61 | 0.00 | 0.00 | 0.00 |
December | 72.34 | 45.33 | 27.01 | 111.48 | 57.95 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 49.05 | 21.70 | 27.35 | 102.52 | 22.46 | 8.00 | 0.00 | 0.00 |
Minimum of Months | 25.43 | 0.36 | 24.99 | 79.11 | 0.30 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 81.05 | 53.57 | 30.72 | 142.06 | 58.78 | 8.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 81.37 | 49.44 | 31.93 | 121.25 | 70.02 | 8.50 | 0.00 | 0.00 |
February | 77.37 | 42.98 | 34.40 | 125.44 | 55.37 | 0.00 | 0.00 | 0.00 |
March | 66.16 | 29.22 | 36.94 | 125.47 | 32.79 | 0.00 | 0.00 | 0.00 |
April | 46.47 | 13.11 | 33.35 | 119.09 | 11.06 | 0.00 | 0.00 | 0.00 |
May | 33.42 | 2.47 | 30.94 | 110.63 | 1.77 | 0.00 | 0.00 | 0.00 |
June | 30.57 | 0.52 | 30.05 | 108.29 | 1.36 | 0.00 | 0.00 | 0.00 |
July | 31.88 | 0.44 | 31.45 | 101.07 | 0.37 | 0.00 | 0.00 | 0.00 |
August | 33.82 | 1.81 | 32.02 | 94.42 | 1.15 | 0.00 | 0.00 | 0.00 |
September | 45.34 | 11.77 | 33.57 | 106.57 | 4.77 | 0.00 | 0.00 | 0.00 |
October | 78.01 | 43.56 | 34.45 | 156.87 | 25.60 | 0.00 | 0.00 | 0.00 |
November | 97.44 | 64.40 | 33.03 | 170.53 | 49.68 | 0.00 | 0.00 | 0.00 |
December | 86.96 | 54.49 | 32.47 | 134.01 | 69.08 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 58.96 | 26.09 | 32.87 | 122.74 | 26.80 | 8.50 | 0.00 | 0.00 |
Minimum of Months | 30.57 | 0.44 | 30.05 | 94.42 | 0.37 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 97.44 | 64.40 | 36.94 | 170.53 | 70.02 | 8.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.69 | 41.13 | 26.56 | 101.30 | 57.22 | 0.00 | 0.00 | 0.00 |
February | 64.36 | 35.75 | 28.61 | 104.53 | 46.39 | 0.00 | 0.00 | 0.00 |
March | 55.03 | 24.31 | 30.72 | 104.36 | 28.69 | 0.00 | 0.00 | 0.00 |
April | 38.65 | 10.91 | 27.74 | 97.82 | 10.55 | 0.00 | 0.00 | 0.00 |
May | 27.80 | 2.06 | 25.74 | 89.39 | 2.03 | 0.00 | 0.00 | 0.00 |
June | 25.43 | 0.43 | 24.99 | 87.20 | 1.62 | 0.00 | 0.00 | 0.00 |
July | 26.52 | 0.36 | 26.16 | 80.75 | 0.49 | 0.00 | 0.00 | 0.00 |
August | 28.14 | 1.50 | 26.63 | 76.32 | 1.59 | 0.00 | 0.00 | 0.00 |
September | 37.72 | 9.79 | 27.93 | 87.40 | 5.51 | 0.00 | 0.00 | 0.00 |
October | 64.89 | 36.23 | 28.66 | 130.40 | 23.53 | 0.00 | 0.00 | 0.00 |
November | 81.05 | 53.57 | 27.48 | 142.11 | 42.63 | 0.00 | 0.00 | 0.00 |
December | 72.34 | 45.33 | 27.01 | 111.84 | 57.31 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 49.05 | 21.70 | 27.35 | 101.06 | 23.03 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 25.43 | 0.36 | 24.99 | 76.32 | 0.49 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 81.05 | 53.57 | 30.72 | 142.11 | 57.31 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.69 | 41.13 | 26.56 | 101.30 | 57.22 | 0.00 | 0.00 | 0.00 |
February | 64.36 | 35.75 | 28.61 | 104.53 | 46.39 | 0.00 | 0.00 | 0.00 |
March | 55.03 | 24.31 | 30.72 | 104.36 | 28.69 | 0.00 | 0.00 | 0.00 |
April | 38.65 | 10.91 | 27.74 | 97.82 | 10.55 | 0.00 | 0.00 | 0.00 |
May | 27.80 | 2.06 | 25.74 | 89.39 | 2.03 | 0.00 | 0.00 | 0.00 |
June | 25.43 | 0.43 | 24.99 | 87.20 | 1.62 | 0.00 | 0.00 | 0.00 |
July | 26.52 | 0.36 | 26.16 | 80.75 | 0.49 | 0.00 | 0.00 | 0.00 |
August | 28.14 | 1.50 | 26.63 | 76.32 | 1.59 | 0.00 | 0.00 | 0.00 |
September | 37.72 | 9.79 | 27.93 | 87.40 | 5.51 | 0.00 | 0.00 | 0.00 |
October | 64.89 | 36.23 | 28.66 | 130.40 | 23.53 | 0.00 | 0.00 | 0.00 |
November | 81.05 | 53.57 | 27.48 | 142.11 | 42.63 | 0.00 | 0.00 | 0.00 |
December | 72.34 | 45.33 | 27.01 | 111.84 | 57.31 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 49.05 | 21.70 | 27.35 | 101.06 | 23.03 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 25.43 | 0.36 | 24.99 | 76.32 | 0.49 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 81.05 | 53.57 | 30.72 | 142.11 | 57.31 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 80.93 | 49.17 | 31.75 | 121.21 | 67.79 | 0.00 | 0.00 | 0.00 |
February | 76.95 | 42.74 | 34.21 | 125.01 | 54.96 | 0.00 | 0.00 | 0.00 |
March | 65.79 | 29.06 | 36.73 | 124.55 | 34.07 | 0.00 | 0.00 | 0.00 |
April | 46.21 | 13.04 | 33.17 | 116.33 | 12.55 | 0.00 | 0.00 | 0.00 |
May | 33.23 | 2.46 | 30.77 | 105.85 | 2.45 | 0.00 | 0.00 | 0.00 |
June | 30.40 | 0.52 | 29.88 | 103.26 | 1.93 | 0.00 | 0.00 | 0.00 |
July | 31.71 | 0.44 | 31.27 | 95.72 | 0.60 | 0.00 | 0.00 | 0.00 |
August | 33.64 | 1.80 | 31.84 | 90.65 | 1.91 | 0.00 | 0.00 | 0.00 |
September | 45.09 | 11.70 | 33.39 | 104.02 | 6.56 | 0.00 | 0.00 | 0.00 |
October | 77.58 | 43.32 | 34.26 | 155.43 | 27.94 | 0.00 | 0.00 | 0.00 |
November | 96.90 | 64.05 | 32.85 | 169.65 | 50.58 | 0.00 | 0.00 | 0.00 |
December | 86.48 | 54.19 | 32.29 | 133.71 | 67.93 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 58.64 | 25.94 | 32.69 | 120.38 | 27.32 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.40 | 0.44 | 29.88 | 90.65 | 0.60 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 96.90 | 64.05 | 36.73 | 169.65 | 67.93 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.69 | 41.13 | 26.56 | 101.64 | 56.24 | 0.00 | 0.00 | 0.00 |
February | 64.36 | 35.75 | 28.61 | 104.70 | 45.92 | 0.00 | 0.00 | 0.00 |
March | 55.03 | 24.31 | 30.72 | 104.39 | 28.62 | 0.00 | 0.00 | 0.00 |
April | 38.65 | 10.91 | 27.74 | 97.71 | 10.72 | 0.00 | 0.00 | 0.00 |
May | 27.80 | 2.06 | 25.74 | 89.04 | 2.18 | 0.00 | 0.00 | 0.00 |
June | 25.43 | 0.43 | 24.99 | 86.78 | 1.72 | 0.00 | 0.00 | 0.00 |
July | 26.52 | 0.36 | 26.16 | 80.28 | 0.54 | 0.00 | 0.00 | 0.00 |
August | 28.14 | 1.50 | 26.63 | 76.05 | 1.70 | 0.00 | 0.00 | 0.00 |
September | 37.72 | 9.79 | 27.93 | 87.31 | 5.76 | 0.00 | 0.00 | 0.00 |
October | 64.89 | 36.23 | 28.66 | 130.36 | 23.69 | 0.00 | 0.00 | 0.00 |
November | 81.05 | 53.57 | 27.48 | 142.17 | 42.47 | 0.00 | 0.00 | 0.00 |
December | 72.34 | 45.33 | 27.01 | 112.07 | 56.70 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 49.05 | 21.70 | 27.35 | 100.98 | 22.92 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 25.43 | 0.36 | 24.99 | 76.05 | 0.54 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 81.05 | 53.57 | 30.72 | 142.17 | 56.70 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.69 | 41.13 | 26.56 | 101.64 | 56.24 | 0.00 | 0.00 | 0.00 |
February | 64.36 | 35.75 | 28.61 | 104.70 | 45.92 | 0.00 | 0.00 | 0.00 |
March | 55.03 | 24.31 | 30.72 | 104.39 | 28.62 | 0.00 | 0.00 | 0.00 |
April | 38.65 | 10.91 | 27.74 | 97.71 | 10.72 | 0.00 | 0.00 | 0.00 |
May | 27.80 | 2.06 | 25.74 | 89.04 | 2.18 | 0.00 | 0.00 | 0.00 |
June | 25.43 | 0.43 | 24.99 | 86.78 | 1.72 | 0.00 | 0.00 | 0.00 |
July | 26.52 | 0.36 | 26.16 | 80.28 | 0.54 | 0.00 | 0.00 | 0.00 |
August | 28.14 | 1.50 | 26.63 | 76.05 | 1.70 | 0.00 | 0.00 | 0.00 |
September | 37.72 | 9.79 | 27.93 | 87.31 | 5.76 | 0.00 | 0.00 | 0.00 |
October | 64.89 | 36.23 | 28.66 | 130.36 | 23.69 | 0.00 | 0.00 | 0.00 |
November | 81.05 | 53.57 | 27.48 | 142.17 | 42.47 | 0.00 | 0.00 | 0.00 |
December | 72.34 | 45.33 | 27.01 | 112.07 | 56.70 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 49.05 | 21.70 | 27.35 | 100.98 | 22.92 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 25.43 | 0.36 | 24.99 | 76.05 | 0.54 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 81.05 | 53.57 | 30.72 | 142.17 | 56.70 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 80.93 | 49.17 | 31.75 | 121.61 | 66.63 | 0.00 | 0.00 | 0.00 |
February | 76.95 | 42.74 | 34.21 | 125.22 | 54.40 | 0.00 | 0.00 | 0.00 |
March | 65.79 | 29.06 | 36.73 | 124.58 | 33.98 | 0.00 | 0.00 | 0.00 |
April | 46.21 | 13.04 | 33.17 | 116.21 | 12.75 | 0.00 | 0.00 | 0.00 |
May | 33.23 | 2.46 | 30.77 | 105.44 | 2.64 | 0.00 | 0.00 | 0.00 |
June | 30.40 | 0.52 | 29.88 | 102.77 | 2.04 | 0.00 | 0.00 | 0.00 |
July | 31.71 | 0.44 | 31.27 | 95.16 | 0.66 | 0.00 | 0.00 | 0.00 |
August | 33.64 | 1.80 | 31.84 | 90.33 | 2.04 | 0.00 | 0.00 | 0.00 |
September | 45.09 | 11.70 | 33.39 | 103.91 | 6.85 | 0.00 | 0.00 | 0.00 |
October | 77.58 | 43.32 | 34.26 | 155.38 | 28.14 | 0.00 | 0.00 | 0.00 |
November | 96.90 | 64.05 | 32.85 | 169.72 | 50.39 | 0.00 | 0.00 | 0.00 |
December | 86.48 | 54.19 | 32.29 | 133.99 | 67.21 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 58.64 | 25.94 | 32.69 | 120.29 | 27.19 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.40 | 0.44 | 29.88 | 90.33 | 0.66 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 96.90 | 64.05 | 36.73 | 169.72 | 67.21 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.69 | 41.13 | 26.56 | 102.08 | 55.21 | 0.00 | 0.00 | 0.00 |
February | 64.36 | 35.75 | 28.61 | 104.98 | 45.27 | 0.00 | 0.00 | 0.00 |
March | 55.03 | 24.31 | 30.72 | 104.56 | 28.21 | 0.00 | 0.00 | 0.00 |
April | 38.65 | 10.91 | 27.74 | 97.88 | 10.46 | 0.00 | 0.00 | 0.00 |
May | 27.80 | 2.06 | 25.74 | 89.28 | 2.07 | 0.00 | 0.00 | 0.00 |
June | 25.43 | 0.43 | 24.99 | 87.08 | 1.65 | 0.00 | 0.00 | 0.00 |
July | 26.52 | 0.36 | 26.16 | 80.53 | 0.49 | 0.00 | 0.00 | 0.00 |
August | 28.14 | 1.50 | 26.63 | 76.27 | 1.59 | 0.00 | 0.00 | 0.00 |
September | 37.72 | 9.79 | 27.93 | 87.42 | 5.51 | 0.00 | 0.00 | 0.00 |
October | 64.89 | 36.23 | 28.66 | 130.45 | 23.40 | 0.00 | 0.00 | 0.00 |
November | 81.05 | 53.57 | 27.48 | 142.32 | 42.08 | 0.00 | 0.00 | 0.00 |
December | 72.34 | 45.33 | 27.01 | 112.42 | 55.99 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 49.05 | 21.70 | 27.35 | 101.22 | 22.56 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 25.43 | 0.36 | 24.99 | 76.27 | 0.49 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 81.05 | 53.57 | 30.72 | 142.32 | 55.99 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.69 | 41.13 | 26.56 | 102.08 | 55.21 | 0.00 | 0.00 | 0.00 |
February | 64.36 | 35.75 | 28.61 | 104.98 | 45.27 | 0.00 | 0.00 | 0.00 |
March | 55.03 | 24.31 | 30.72 | 104.56 | 28.21 | 0.00 | 0.00 | 0.00 |
April | 38.65 | 10.91 | 27.74 | 97.88 | 10.46 | 0.00 | 0.00 | 0.00 |
May | 27.80 | 2.06 | 25.74 | 89.28 | 2.07 | 0.00 | 0.00 | 0.00 |
June | 25.43 | 0.43 | 24.99 | 87.08 | 1.65 | 0.00 | 0.00 | 0.00 |
July | 26.52 | 0.36 | 26.16 | 80.53 | 0.49 | 0.00 | 0.00 | 0.00 |
August | 28.14 | 1.50 | 26.63 | 76.27 | 1.59 | 0.00 | 0.00 | 0.00 |
September | 37.72 | 9.79 | 27.93 | 87.42 | 5.51 | 0.00 | 0.00 | 0.00 |
October | 64.89 | 36.23 | 28.66 | 130.45 | 23.40 | 0.00 | 0.00 | 0.00 |
November | 81.05 | 53.57 | 27.48 | 142.32 | 42.08 | 0.00 | 0.00 | 0.00 |
December | 72.34 | 45.33 | 27.01 | 112.42 | 55.99 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 49.05 | 21.70 | 27.35 | 101.22 | 22.56 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 25.43 | 0.36 | 24.99 | 76.27 | 0.49 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 81.05 | 53.57 | 30.72 | 142.32 | 55.99 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 80.93 | 49.17 | 31.75 | 122.14 | 65.41 | 0.00 | 0.00 | 0.00 |
February | 76.95 | 42.74 | 34.21 | 125.56 | 53.63 | 0.00 | 0.00 | 0.00 |
March | 65.79 | 29.06 | 36.73 | 124.78 | 33.49 | 0.00 | 0.00 | 0.00 |
April | 46.21 | 13.04 | 33.17 | 116.41 | 12.44 | 0.00 | 0.00 | 0.00 |
May | 33.23 | 2.46 | 30.77 | 105.72 | 2.51 | 0.00 | 0.00 | 0.00 |
June | 30.40 | 0.52 | 29.88 | 103.12 | 1.97 | 0.00 | 0.00 | 0.00 |
July | 31.71 | 0.44 | 31.27 | 95.46 | 0.60 | 0.00 | 0.00 | 0.00 |
August | 33.64 | 1.80 | 31.84 | 90.59 | 1.90 | 0.00 | 0.00 | 0.00 |
September | 45.09 | 11.70 | 33.39 | 104.04 | 6.55 | 0.00 | 0.00 | 0.00 |
October | 77.58 | 43.32 | 34.26 | 155.49 | 27.79 | 0.00 | 0.00 | 0.00 |
November | 96.90 | 64.05 | 32.85 | 169.90 | 49.94 | 0.00 | 0.00 | 0.00 |
December | 86.48 | 54.19 | 32.29 | 134.40 | 66.37 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 58.64 | 25.94 | 32.69 | 120.56 | 26.76 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.40 | 0.44 | 29.88 | 90.59 | 0.60 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 96.90 | 64.05 | 36.73 | 169.90 | 66.37 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.69 | 41.13 | 26.56 | 103.05 | 53.07 | 0.00 | 0.00 | 0.00 |
February | 64.36 | 35.75 | 28.61 | 105.66 | 43.76 | 0.00 | 0.00 | 0.00 |
March | 55.03 | 24.31 | 30.72 | 104.89 | 27.04 | 0.00 | 0.00 | 0.00 |
April | 38.65 | 10.91 | 27.74 | 98.13 | 9.68 | 0.00 | 0.00 | 0.00 |
May | 27.80 | 2.06 | 25.74 | 89.55 | 1.78 | 0.00 | 0.00 | 0.00 |
June | 25.43 | 0.43 | 24.99 | 87.58 | 1.49 | 0.00 | 0.00 | 0.00 |
July | 26.52 | 0.36 | 26.16 | 80.70 | 0.36 | 0.00 | 0.00 | 0.00 |
August | 28.14 | 1.50 | 26.63 | 76.48 | 1.26 | 0.00 | 0.00 | 0.00 |
September | 37.72 | 9.79 | 27.93 | 87.42 | 4.81 | 0.00 | 0.00 | 0.00 |
October | 64.89 | 36.23 | 28.66 | 130.41 | 22.50 | 0.00 | 0.00 | 0.00 |
November | 81.05 | 53.57 | 27.48 | 142.55 | 41.12 | 0.00 | 0.00 | 0.00 |
December | 72.34 | 45.33 | 27.01 | 113.15 | 54.39 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 49.05 | 21.70 | 27.35 | 101.57 | 21.67 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 25.43 | 0.36 | 24.99 | 76.48 | 0.36 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 81.05 | 53.57 | 30.72 | 142.55 | 54.39 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.69 | 41.13 | 26.56 | 103.05 | 53.07 | 0.00 | 0.00 | 0.00 |
February | 64.36 | 35.75 | 28.61 | 105.66 | 43.76 | 0.00 | 0.00 | 0.00 |
March | 55.03 | 24.31 | 30.72 | 104.89 | 27.04 | 0.00 | 0.00 | 0.00 |
April | 38.65 | 10.91 | 27.74 | 98.13 | 9.68 | 0.00 | 0.00 | 0.00 |
May | 27.80 | 2.06 | 25.74 | 89.55 | 1.78 | 0.00 | 0.00 | 0.00 |
June | 25.43 | 0.43 | 24.99 | 87.58 | 1.49 | 0.00 | 0.00 | 0.00 |
July | 26.52 | 0.36 | 26.16 | 80.70 | 0.36 | 0.00 | 0.00 | 0.00 |
August | 28.14 | 1.50 | 26.63 | 76.48 | 1.26 | 0.00 | 0.00 | 0.00 |
September | 37.72 | 9.79 | 27.93 | 87.42 | 4.81 | 0.00 | 0.00 | 0.00 |
October | 64.89 | 36.23 | 28.66 | 130.41 | 22.50 | 0.00 | 0.00 | 0.00 |
November | 81.05 | 53.57 | 27.48 | 142.55 | 41.12 | 0.00 | 0.00 | 0.00 |
December | 72.34 | 45.33 | 27.01 | 113.15 | 54.39 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 49.05 | 21.70 | 27.35 | 101.57 | 21.67 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 25.43 | 0.36 | 24.99 | 76.48 | 0.36 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 81.05 | 53.57 | 30.72 | 142.55 | 54.39 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.69 | 41.13 | 26.56 | 103.05 | 53.07 | 0.00 | 0.00 | 0.00 |
February | 64.36 | 35.75 | 28.61 | 105.66 | 43.76 | 0.00 | 0.00 | 0.00 |
March | 55.03 | 24.31 | 30.72 | 104.89 | 27.04 | 0.00 | 0.00 | 0.00 |
April | 38.65 | 10.91 | 27.74 | 98.13 | 9.68 | 0.00 | 0.00 | 0.00 |
May | 27.80 | 2.06 | 25.74 | 89.55 | 1.78 | 0.00 | 0.00 | 0.00 |
June | 25.43 | 0.43 | 24.99 | 87.58 | 1.49 | 0.00 | 0.00 | 0.00 |
July | 26.52 | 0.36 | 26.16 | 80.70 | 0.36 | 0.00 | 0.00 | 0.00 |
August | 28.14 | 1.50 | 26.63 | 76.48 | 1.26 | 0.00 | 0.00 | 0.00 |
September | 37.72 | 9.79 | 27.93 | 87.42 | 4.81 | 0.00 | 0.00 | 0.00 |
October | 64.89 | 36.23 | 28.66 | 130.41 | 22.50 | 0.00 | 0.00 | 0.00 |
November | 81.05 | 53.57 | 27.48 | 142.55 | 41.12 | 0.00 | 0.00 | 0.00 |
December | 72.34 | 45.33 | 27.01 | 113.15 | 54.39 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 49.05 | 21.70 | 27.35 | 101.57 | 21.67 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 25.43 | 0.36 | 24.99 | 76.48 | 0.36 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 81.05 | 53.57 | 30.72 | 142.55 | 54.39 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.69 | 41.13 | 26.56 | 103.05 | 53.07 | 0.00 | 0.00 | 0.00 |
February | 64.36 | 35.75 | 28.61 | 105.66 | 43.76 | 0.00 | 0.00 | 0.00 |
March | 55.03 | 24.31 | 30.72 | 104.89 | 27.04 | 0.00 | 0.00 | 0.00 |
April | 38.65 | 10.91 | 27.74 | 98.13 | 9.68 | 0.00 | 0.00 | 0.00 |
May | 27.80 | 2.06 | 25.74 | 89.55 | 1.78 | 0.00 | 0.00 | 0.00 |
June | 25.43 | 0.43 | 24.99 | 87.58 | 1.49 | 0.00 | 0.00 | 0.00 |
July | 26.52 | 0.36 | 26.16 | 80.70 | 0.36 | 0.00 | 0.00 | 0.00 |
August | 28.14 | 1.50 | 26.63 | 76.48 | 1.26 | 0.00 | 0.00 | 0.00 |
September | 37.72 | 9.79 | 27.93 | 87.42 | 4.81 | 0.00 | 0.00 | 0.00 |
October | 64.89 | 36.23 | 28.66 | 130.41 | 22.50 | 0.00 | 0.00 | 0.00 |
November | 81.05 | 53.57 | 27.48 | 142.55 | 41.12 | 0.00 | 0.00 | 0.00 |
December | 72.34 | 45.33 | 27.01 | 113.15 | 54.39 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 49.05 | 21.70 | 27.35 | 101.57 | 21.67 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 25.43 | 0.36 | 24.99 | 76.48 | 0.36 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 81.05 | 53.57 | 30.72 | 142.55 | 54.39 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 80.93 | 49.17 | 31.75 | 123.27 | 62.89 | 0.00 | 0.00 | 0.00 |
February | 76.95 | 42.74 | 34.21 | 126.33 | 51.86 | 0.00 | 0.00 | 0.00 |
March | 65.79 | 29.06 | 36.73 | 125.17 | 32.12 | 0.00 | 0.00 | 0.00 |
April | 46.21 | 13.04 | 33.17 | 116.72 | 11.51 | 0.00 | 0.00 | 0.00 |
May | 33.23 | 2.46 | 30.77 | 106.07 | 2.16 | 0.00 | 0.00 | 0.00 |
June | 30.40 | 0.52 | 29.88 | 103.75 | 1.77 | 0.00 | 0.00 | 0.00 |
July | 31.71 | 0.44 | 31.27 | 95.68 | 0.44 | 0.00 | 0.00 | 0.00 |
August | 33.64 | 1.80 | 31.84 | 90.85 | 1.51 | 0.00 | 0.00 | 0.00 |
September | 45.09 | 11.70 | 33.39 | 104.05 | 5.72 | 0.00 | 0.00 | 0.00 |
October | 77.58 | 43.32 | 34.26 | 155.43 | 26.72 | 0.00 | 0.00 | 0.00 |
November | 96.90 | 64.05 | 32.85 | 170.16 | 48.79 | 0.00 | 0.00 | 0.00 |
December | 86.48 | 54.19 | 32.29 | 135.25 | 64.48 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 58.64 | 25.94 | 32.69 | 120.99 | 25.71 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.40 | 0.44 | 29.88 | 90.85 | 0.44 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 96.90 | 64.05 | 36.73 | 170.16 | 64.48 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 80.93 | 49.17 | 31.75 | 123.27 | 62.89 | 0.00 | 0.00 | 0.00 |
February | 76.95 | 42.74 | 34.21 | 126.33 | 51.86 | 0.00 | 0.00 | 0.00 |
March | 65.79 | 29.06 | 36.73 | 125.17 | 32.12 | 0.00 | 0.00 | 0.00 |
April | 46.21 | 13.04 | 33.17 | 116.72 | 11.51 | 0.00 | 0.00 | 0.00 |
May | 33.23 | 2.46 | 30.77 | 106.07 | 2.16 | 0.00 | 0.00 | 0.00 |
June | 30.40 | 0.52 | 29.88 | 103.75 | 1.77 | 0.00 | 0.00 | 0.00 |
July | 31.71 | 0.44 | 31.27 | 95.68 | 0.44 | 0.00 | 0.00 | 0.00 |
August | 33.64 | 1.80 | 31.84 | 90.85 | 1.51 | 0.00 | 0.00 | 0.00 |
September | 45.09 | 11.70 | 33.39 | 104.05 | 5.72 | 0.00 | 0.00 | 0.00 |
October | 77.58 | 43.32 | 34.26 | 155.43 | 26.72 | 0.00 | 0.00 | 0.00 |
November | 96.90 | 64.05 | 32.85 | 170.16 | 48.79 | 0.00 | 0.00 | 0.00 |
December | 86.48 | 54.19 | 32.29 | 135.25 | 64.48 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 58.64 | 25.94 | 32.69 | 120.99 | 25.71 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.40 | 0.44 | 29.88 | 90.85 | 0.44 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 96.90 | 64.05 | 36.73 | 170.16 | 64.48 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.69 | 41.13 | 26.56 | 102.98 | 52.90 | 0.00 | 0.00 | 0.00 |
February | 64.36 | 35.75 | 28.61 | 105.54 | 43.63 | 0.00 | 0.00 | 0.00 |
March | 55.03 | 24.31 | 30.72 | 104.90 | 26.80 | 0.00 | 0.00 | 0.00 |
April | 38.65 | 10.91 | 27.74 | 98.49 | 9.42 | 0.00 | 0.00 | 0.00 |
May | 27.80 | 2.06 | 25.74 | 90.37 | 1.64 | 0.00 | 0.00 | 0.00 |
June | 25.43 | 0.43 | 24.99 | 88.50 | 1.41 | 0.00 | 0.00 | 0.00 |
July | 26.52 | 0.36 | 26.16 | 81.56 | 0.31 | 0.00 | 0.00 | 0.00 |
August | 28.14 | 1.50 | 26.63 | 77.11 | 1.12 | 0.00 | 0.00 | 0.00 |
September | 37.72 | 9.79 | 27.93 | 87.76 | 4.49 | 0.00 | 0.00 | 0.00 |
October | 64.89 | 36.23 | 28.66 | 130.51 | 22.16 | 0.00 | 0.00 | 0.00 |
November | 81.05 | 53.57 | 27.48 | 142.49 | 40.91 | 0.00 | 0.00 | 0.00 |
December | 72.34 | 45.33 | 27.01 | 113.07 | 54.27 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 49.05 | 21.70 | 27.35 | 101.89 | 21.49 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 25.43 | 0.36 | 24.99 | 77.11 | 0.31 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 81.05 | 53.57 | 30.72 | 142.49 | 54.27 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.69 | 41.13 | 26.56 | 102.98 | 52.90 | 0.00 | 0.00 | 0.00 |
February | 64.36 | 35.75 | 28.61 | 105.54 | 43.63 | 0.00 | 0.00 | 0.00 |
March | 55.03 | 24.31 | 30.72 | 104.90 | 26.80 | 0.00 | 0.00 | 0.00 |
April | 38.65 | 10.91 | 27.74 | 98.49 | 9.42 | 0.00 | 0.00 | 0.00 |
May | 27.80 | 2.06 | 25.74 | 90.37 | 1.64 | 0.00 | 0.00 | 0.00 |
June | 25.43 | 0.43 | 24.99 | 88.50 | 1.41 | 0.00 | 0.00 | 0.00 |
July | 26.52 | 0.36 | 26.16 | 81.56 | 0.31 | 0.00 | 0.00 | 0.00 |
August | 28.14 | 1.50 | 26.63 | 77.11 | 1.12 | 0.00 | 0.00 | 0.00 |
September | 37.72 | 9.79 | 27.93 | 87.76 | 4.49 | 0.00 | 0.00 | 0.00 |
October | 64.89 | 36.23 | 28.66 | 130.51 | 22.16 | 0.00 | 0.00 | 0.00 |
November | 81.05 | 53.57 | 27.48 | 142.49 | 40.91 | 0.00 | 0.00 | 0.00 |
December | 72.34 | 45.33 | 27.01 | 113.07 | 54.27 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 49.05 | 21.70 | 27.35 | 101.89 | 21.49 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 25.43 | 0.36 | 24.99 | 77.11 | 0.31 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 81.05 | 53.57 | 30.72 | 142.49 | 54.27 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 80.93 | 49.17 | 31.75 | 123.22 | 62.67 | 0.00 | 0.00 | 0.00 |
February | 76.95 | 42.74 | 34.21 | 126.24 | 51.69 | 0.00 | 0.00 | 0.00 |
March | 65.79 | 29.06 | 36.73 | 125.20 | 31.83 | 0.00 | 0.00 | 0.00 |
April | 46.21 | 13.04 | 33.17 | 117.15 | 11.21 | 0.00 | 0.00 | 0.00 |
May | 33.23 | 2.46 | 30.77 | 107.01 | 1.99 | 0.00 | 0.00 | 0.00 |
June | 30.40 | 0.52 | 29.88 | 104.81 | 1.67 | 0.00 | 0.00 | 0.00 |
July | 31.71 | 0.44 | 31.27 | 96.67 | 0.38 | 0.00 | 0.00 | 0.00 |
August | 33.64 | 1.80 | 31.84 | 91.60 | 1.34 | 0.00 | 0.00 | 0.00 |
September | 45.09 | 11.70 | 33.39 | 104.45 | 5.34 | 0.00 | 0.00 | 0.00 |
October | 77.58 | 43.32 | 34.26 | 155.58 | 26.32 | 0.00 | 0.00 | 0.00 |
November | 96.90 | 64.05 | 32.85 | 170.12 | 48.54 | 0.00 | 0.00 | 0.00 |
December | 86.48 | 54.19 | 32.29 | 135.19 | 64.32 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 58.64 | 25.94 | 32.69 | 121.37 | 25.49 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.40 | 0.44 | 29.88 | 91.60 | 0.38 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 96.90 | 64.05 | 36.73 | 170.12 | 64.32 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.69 | 41.13 | 26.56 | 103.13 | 52.59 | 0.00 | 0.00 | 0.00 |
February | 64.36 | 35.75 | 28.61 | 105.66 | 43.40 | 0.00 | 0.00 | 0.00 |
March | 55.03 | 24.31 | 30.72 | 104.97 | 26.67 | 0.00 | 0.00 | 0.00 |
April | 38.65 | 10.91 | 27.74 | 98.56 | 9.36 | 0.00 | 0.00 | 0.00 |
May | 27.80 | 2.06 | 25.74 | 90.44 | 1.62 | 0.00 | 0.00 | 0.00 |
June | 25.43 | 0.43 | 24.99 | 88.58 | 1.40 | 0.00 | 0.00 | 0.00 |
July | 26.52 | 0.36 | 26.16 | 81.63 | 0.30 | 0.00 | 0.00 | 0.00 |
August | 28.14 | 1.50 | 26.63 | 77.17 | 1.11 | 0.00 | 0.00 | 0.00 |
September | 37.72 | 9.79 | 27.93 | 87.80 | 4.45 | 0.00 | 0.00 | 0.00 |
October | 64.89 | 36.23 | 28.66 | 130.55 | 22.09 | 0.00 | 0.00 | 0.00 |
November | 81.05 | 53.57 | 27.48 | 142.55 | 40.79 | 0.00 | 0.00 | 0.00 |
December | 72.34 | 45.33 | 27.01 | 113.21 | 54.02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 49.05 | 21.70 | 27.35 | 101.97 | 21.39 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 25.43 | 0.36 | 24.99 | 77.17 | 0.30 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 81.05 | 53.57 | 30.72 | 142.55 | 54.02 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.69 | 41.13 | 26.56 | 103.13 | 52.59 | 0.00 | 0.00 | 0.00 |
February | 64.36 | 35.75 | 28.61 | 105.66 | 43.40 | 0.00 | 0.00 | 0.00 |
March | 55.03 | 24.31 | 30.72 | 104.97 | 26.67 | 0.00 | 0.00 | 0.00 |
April | 38.65 | 10.91 | 27.74 | 98.56 | 9.36 | 0.00 | 0.00 | 0.00 |
May | 27.80 | 2.06 | 25.74 | 90.44 | 1.62 | 0.00 | 0.00 | 0.00 |
June | 25.43 | 0.43 | 24.99 | 88.58 | 1.40 | 0.00 | 0.00 | 0.00 |
July | 26.52 | 0.36 | 26.16 | 81.63 | 0.30 | 0.00 | 0.00 | 0.00 |
August | 28.14 | 1.50 | 26.63 | 77.17 | 1.11 | 0.00 | 0.00 | 0.00 |
September | 37.72 | 9.79 | 27.93 | 87.80 | 4.45 | 0.00 | 0.00 | 0.00 |
October | 64.89 | 36.23 | 28.66 | 130.55 | 22.09 | 0.00 | 0.00 | 0.00 |
November | 81.05 | 53.57 | 27.48 | 142.55 | 40.79 | 0.00 | 0.00 | 0.00 |
December | 72.34 | 45.33 | 27.01 | 113.21 | 54.02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 49.05 | 21.70 | 27.35 | 101.97 | 21.39 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 25.43 | 0.36 | 24.99 | 77.17 | 0.30 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 81.05 | 53.57 | 30.72 | 142.55 | 54.02 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 80.93 | 49.17 | 31.75 | 123.40 | 62.31 | 0.00 | 0.00 | 0.00 |
February | 76.95 | 42.74 | 34.21 | 126.39 | 51.42 | 0.00 | 0.00 | 0.00 |
March | 65.79 | 29.06 | 36.73 | 125.29 | 31.68 | 0.00 | 0.00 | 0.00 |
April | 46.21 | 13.04 | 33.17 | 117.23 | 11.13 | 0.00 | 0.00 | 0.00 |
May | 33.23 | 2.46 | 30.77 | 107.09 | 1.97 | 0.00 | 0.00 | 0.00 |
June | 30.40 | 0.52 | 29.88 | 104.91 | 1.65 | 0.00 | 0.00 | 0.00 |
July | 31.71 | 0.44 | 31.27 | 96.75 | 0.37 | 0.00 | 0.00 | 0.00 |
August | 33.64 | 1.80 | 31.84 | 91.67 | 1.32 | 0.00 | 0.00 | 0.00 |
September | 45.09 | 11.70 | 33.39 | 104.50 | 5.29 | 0.00 | 0.00 | 0.00 |
October | 77.58 | 43.32 | 34.26 | 155.62 | 26.24 | 0.00 | 0.00 | 0.00 |
November | 96.90 | 64.05 | 32.85 | 170.20 | 48.41 | 0.00 | 0.00 | 0.00 |
December | 86.48 | 54.19 | 32.29 | 135.36 | 64.03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 58.64 | 25.94 | 32.69 | 121.47 | 25.37 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.40 | 0.44 | 29.88 | 91.67 | 0.37 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 96.90 | 64.05 | 36.73 | 170.20 | 64.03 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.69 | 41.13 | 26.56 | 103.47 | 51.81 | 0.00 | 0.00 | 0.00 |
February | 64.36 | 35.75 | 28.61 | 105.97 | 42.75 | 0.00 | 0.00 | 0.00 |
March | 55.03 | 24.31 | 30.72 | 105.12 | 26.33 | 0.00 | 0.00 | 0.00 |
April | 38.65 | 10.91 | 27.74 | 98.49 | 9.32 | 0.00 | 0.00 | 0.00 |
May | 27.80 | 2.06 | 25.74 | 90.18 | 1.67 | 0.00 | 0.00 | 0.00 |
June | 25.43 | 0.43 | 24.99 | 88.24 | 1.42 | 0.00 | 0.00 | 0.00 |
July | 26.52 | 0.36 | 26.16 | 81.21 | 0.32 | 0.00 | 0.00 | 0.00 |
August | 28.14 | 1.50 | 26.63 | 76.84 | 1.17 | 0.00 | 0.00 | 0.00 |
September | 37.72 | 9.79 | 27.93 | 87.64 | 4.58 | 0.00 | 0.00 | 0.00 |
October | 64.89 | 36.23 | 28.66 | 130.49 | 22.13 | 0.00 | 0.00 | 0.00 |
November | 81.05 | 53.57 | 27.48 | 142.68 | 40.53 | 0.00 | 0.00 | 0.00 |
December | 72.34 | 45.33 | 27.01 | 113.54 | 53.36 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 49.05 | 21.70 | 27.35 | 101.93 | 21.19 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 25.43 | 0.36 | 24.99 | 76.84 | 0.32 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 81.05 | 53.57 | 30.72 | 142.68 | 53.36 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.69 | 41.13 | 26.56 | 103.47 | 51.81 | 0.00 | 0.00 | 0.00 |
February | 64.36 | 35.75 | 28.61 | 105.97 | 42.75 | 0.00 | 0.00 | 0.00 |
March | 55.03 | 24.31 | 30.72 | 105.12 | 26.33 | 0.00 | 0.00 | 0.00 |
April | 38.65 | 10.91 | 27.74 | 98.49 | 9.32 | 0.00 | 0.00 | 0.00 |
May | 27.80 | 2.06 | 25.74 | 90.18 | 1.67 | 0.00 | 0.00 | 0.00 |
June | 25.43 | 0.43 | 24.99 | 88.24 | 1.42 | 0.00 | 0.00 | 0.00 |
July | 26.52 | 0.36 | 26.16 | 81.21 | 0.32 | 0.00 | 0.00 | 0.00 |
August | 28.14 | 1.50 | 26.63 | 76.84 | 1.17 | 0.00 | 0.00 | 0.00 |
September | 37.72 | 9.79 | 27.93 | 87.64 | 4.58 | 0.00 | 0.00 | 0.00 |
October | 64.89 | 36.23 | 28.66 | 130.49 | 22.13 | 0.00 | 0.00 | 0.00 |
November | 81.05 | 53.57 | 27.48 | 142.68 | 40.53 | 0.00 | 0.00 | 0.00 |
December | 72.34 | 45.33 | 27.01 | 113.54 | 53.36 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 49.05 | 21.70 | 27.35 | 101.93 | 21.19 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 25.43 | 0.36 | 24.99 | 76.84 | 0.32 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 81.05 | 53.57 | 30.72 | 142.68 | 53.36 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 80.93 | 49.17 | 31.75 | 123.80 | 61.39 | 0.00 | 0.00 | 0.00 |
February | 76.95 | 42.74 | 34.21 | 126.75 | 50.65 | 0.00 | 0.00 | 0.00 |
March | 65.79 | 29.06 | 36.73 | 125.47 | 31.28 | 0.00 | 0.00 | 0.00 |
April | 46.21 | 13.04 | 33.17 | 117.15 | 11.09 | 0.00 | 0.00 | 0.00 |
May | 33.23 | 2.46 | 30.77 | 106.78 | 2.02 | 0.00 | 0.00 | 0.00 |
June | 30.40 | 0.52 | 29.88 | 104.51 | 1.68 | 0.00 | 0.00 | 0.00 |
July | 31.71 | 0.44 | 31.27 | 96.25 | 0.39 | 0.00 | 0.00 | 0.00 |
August | 33.64 | 1.80 | 31.84 | 91.28 | 1.40 | 0.00 | 0.00 | 0.00 |
September | 45.09 | 11.70 | 33.39 | 104.31 | 5.45 | 0.00 | 0.00 | 0.00 |
October | 77.58 | 43.32 | 34.26 | 155.56 | 26.28 | 0.00 | 0.00 | 0.00 |
November | 96.90 | 64.05 | 32.85 | 170.34 | 48.10 | 0.00 | 0.00 | 0.00 |
December | 86.48 | 54.19 | 32.29 | 135.75 | 63.25 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 58.64 | 25.94 | 32.69 | 121.42 | 25.13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.40 | 0.44 | 29.88 | 91.28 | 0.39 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 96.90 | 64.05 | 36.73 | 170.34 | 63.25 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.69 | 41.13 | 26.56 | 103.87 | 49.37 | 0.00 | 0.00 | 0.00 |
February | 64.36 | 35.75 | 28.61 | 106.34 | 40.48 | 0.00 | 0.00 | 0.00 |
March | 55.03 | 24.31 | 30.72 | 105.00 | 25.07 | 0.00 | 0.00 | 0.00 |
April | 38.65 | 10.91 | 27.74 | 97.19 | 9.27 | 0.00 | 0.00 | 0.00 |
May | 27.80 | 2.06 | 25.74 | 87.68 | 1.95 | 0.00 | 0.00 | 0.00 |
June | 25.43 | 0.43 | 24.99 | 85.26 | 1.60 | 0.00 | 0.00 | 0.00 |
July | 26.52 | 0.36 | 26.16 | 77.93 | 0.48 | 0.00 | 0.00 | 0.00 |
August | 28.14 | 1.50 | 26.63 | 74.20 | 1.67 | 0.00 | 0.00 | 0.00 |
September | 37.72 | 9.79 | 27.93 | 86.02 | 5.63 | 0.00 | 0.00 | 0.00 |
October | 64.89 | 36.23 | 28.66 | 129.55 | 22.63 | 0.00 | 0.00 | 0.00 |
November | 81.05 | 53.57 | 27.48 | 142.55 | 39.64 | 0.00 | 0.00 | 0.00 |
December | 72.34 | 45.33 | 27.01 | 113.96 | 51.20 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 49.05 | 21.70 | 27.35 | 100.73 | 20.66 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 25.43 | 0.36 | 24.99 | 74.20 | 0.48 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 81.05 | 53.57 | 30.72 | 142.55 | 51.20 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 67.69 | 41.13 | 26.56 | 103.87 | 49.37 | 0.00 | 0.00 | 0.00 |
February | 64.36 | 35.75 | 28.61 | 106.34 | 40.48 | 0.00 | 0.00 | 0.00 |
March | 55.03 | 24.31 | 30.72 | 105.00 | 25.07 | 0.00 | 0.00 | 0.00 |
April | 38.65 | 10.91 | 27.74 | 97.19 | 9.27 | 0.00 | 0.00 | 0.00 |
May | 27.80 | 2.06 | 25.74 | 87.68 | 1.95 | 0.00 | 0.00 | 0.00 |
June | 25.43 | 0.43 | 24.99 | 85.26 | 1.60 | 0.00 | 0.00 | 0.00 |
July | 26.52 | 0.36 | 26.16 | 77.93 | 0.48 | 0.00 | 0.00 | 0.00 |
August | 28.14 | 1.50 | 26.63 | 74.20 | 1.67 | 0.00 | 0.00 | 0.00 |
September | 37.72 | 9.79 | 27.93 | 86.02 | 5.63 | 0.00 | 0.00 | 0.00 |
October | 64.89 | 36.23 | 28.66 | 129.55 | 22.63 | 0.00 | 0.00 | 0.00 |
November | 81.05 | 53.57 | 27.48 | 142.55 | 39.64 | 0.00 | 0.00 | 0.00 |
December | 72.34 | 45.33 | 27.01 | 113.96 | 51.20 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 49.05 | 21.70 | 27.35 | 100.73 | 20.66 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 25.43 | 0.36 | 24.99 | 74.20 | 0.48 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 81.05 | 53.57 | 30.72 | 142.55 | 51.20 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 80.93 | 49.17 | 31.75 | 124.29 | 58.51 | 0.00 | 0.00 | 0.00 |
February | 76.95 | 42.74 | 34.21 | 127.19 | 47.97 | 0.00 | 0.00 | 0.00 |
March | 65.79 | 29.06 | 36.73 | 125.32 | 29.80 | 0.00 | 0.00 | 0.00 |
April | 46.21 | 13.04 | 33.17 | 115.57 | 11.03 | 0.00 | 0.00 | 0.00 |
May | 33.23 | 2.46 | 30.77 | 103.80 | 2.37 | 0.00 | 0.00 | 0.00 |
June | 30.40 | 0.52 | 29.88 | 100.94 | 1.90 | 0.00 | 0.00 | 0.00 |
July | 31.71 | 0.44 | 31.27 | 92.36 | 0.59 | 0.00 | 0.00 | 0.00 |
August | 33.64 | 1.80 | 31.84 | 88.12 | 2.00 | 0.00 | 0.00 | 0.00 |
September | 45.09 | 11.70 | 33.39 | 102.36 | 6.70 | 0.00 | 0.00 | 0.00 |
October | 77.58 | 43.32 | 34.26 | 154.42 | 26.88 | 0.00 | 0.00 | 0.00 |
November | 96.90 | 64.05 | 32.85 | 170.18 | 47.05 | 0.00 | 0.00 | 0.00 |
December | 86.48 | 54.19 | 32.29 | 136.25 | 60.69 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 58.64 | 25.94 | 32.69 | 119.99 | 24.52 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.40 | 0.44 | 29.88 | 88.12 | 0.59 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 96.90 | 64.05 | 36.73 | 170.18 | 60.69 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.181296E+09 | 0.110160E+09 | 71136080.39 | 0.273570E+09 | 0.148920E+09 |
February | 0.155704E+09 | 86482410.97 | 69221597.04 | 0.254695E+09 | 0.107877E+09 |
March | 0.147395E+09 | 65103030.68 | 82291697.41 | 0.280820E+09 | 71577357.09 |
April | 0.100191E+09 | 28276943.91 | 71913896.18 | 0.256656E+09 | 23449731.50 |
May | 74452123.42 | 5511480.70 | 68940642.72 | 0.245594E+09 | 3943355.65 |
June | 65907601.50 | 1124695.11 | 64782906.39 | 0.231737E+09 | 2937828.73 |
July | 71039507.28 | 977090.27 | 70062417.01 | 0.223207E+09 | 880797.90 |
August | 75357876.56 | 4024678.80 | 71333197.76 | 0.208359E+09 | 2789335.21 |
September | 97764495.24 | 25374984.65 | 72389510.59 | 0.228674E+09 | 10901853.62 |
October | 0.173800E+09 | 97049275.04 | 76750855.36 | 0.349678E+09 | 57396837.53 |
November | 0.210083E+09 | 0.138860E+09 | 71222517.68 | 0.369000E+09 | 0.106397E+09 |
December | 0.193743E+09 | 0.121405E+09 | 72338408.04 | 0.301508E+09 | 0.149260E+09 |
Annual Sum or Average | 0.154673E+10 | 0.684350E+09 | 0.862384E+09 | 0.322350E+10 | 0.686331E+09 |
Minimum of Months | 65907601.50 | 977090.27 | 64782906.39 | 0.208359E+09 | 880797.90 |
Maximum of Months | 0.210083E+09 | 0.138860E+09 | 82291697.41 | 0.369000E+09 | 0.149260E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.181296E+09 | 0.110160E+09 | 71136080.39 | 0.273570E+09 | 0.148920E+09 |
February | 0.155704E+09 | 86482410.97 | 69221597.04 | 0.254695E+09 | 0.107877E+09 |
March | 0.147395E+09 | 65103030.68 | 82291697.41 | 0.280820E+09 | 71577357.09 |
April | 0.100191E+09 | 28276943.91 | 71913896.18 | 0.256656E+09 | 23449731.50 |
May | 74452123.42 | 5511480.70 | 68940642.72 | 0.245594E+09 | 3943355.65 |
June | 65907601.50 | 1124695.11 | 64782906.39 | 0.231737E+09 | 2937828.73 |
July | 71039507.28 | 977090.27 | 70062417.01 | 0.223207E+09 | 880797.90 |
August | 75357876.56 | 4024678.80 | 71333197.76 | 0.208359E+09 | 2789335.21 |
September | 97764495.24 | 25374984.65 | 72389510.59 | 0.228674E+09 | 10901853.62 |
October | 0.173800E+09 | 97049275.04 | 76750855.36 | 0.349678E+09 | 57396837.53 |
November | 0.210083E+09 | 0.138860E+09 | 71222517.68 | 0.369000E+09 | 0.106397E+09 |
December | 0.193743E+09 | 0.121405E+09 | 72338408.04 | 0.301508E+09 | 0.149260E+09 |
Annual Sum or Average | 0.154673E+10 | 0.684350E+09 | 0.862384E+09 | 0.322350E+10 | 0.686331E+09 |
Minimum of Months | 65907601.50 | 977090.27 | 64782906.39 | 0.208359E+09 | 880797.90 |
Maximum of Months | 0.210083E+09 | 0.138860E+09 | 82291697.41 | 0.369000E+09 | 0.149260E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.181296E+09 | 0.110160E+09 | 71136080.39 | 0.273570E+09 | 0.148920E+09 |
February | 0.155704E+09 | 86482410.97 | 69221597.04 | 0.254695E+09 | 0.107877E+09 |
March | 0.147395E+09 | 65103030.68 | 82291697.41 | 0.280820E+09 | 71577357.09 |
April | 0.100191E+09 | 28276943.91 | 71913896.18 | 0.256656E+09 | 23449731.50 |
May | 74452123.42 | 5511480.70 | 68940642.72 | 0.245594E+09 | 3943355.65 |
June | 65907601.50 | 1124695.11 | 64782906.39 | 0.231737E+09 | 2937828.73 |
July | 71039507.28 | 977090.27 | 70062417.01 | 0.223207E+09 | 880797.90 |
August | 75357876.56 | 4024678.80 | 71333197.76 | 0.208359E+09 | 2789335.21 |
September | 97764495.24 | 25374984.65 | 72389510.59 | 0.228674E+09 | 10901853.62 |
October | 0.173800E+09 | 97049275.04 | 76750855.36 | 0.349678E+09 | 57396837.53 |
November | 0.210083E+09 | 0.138860E+09 | 71222517.68 | 0.369000E+09 | 0.106397E+09 |
December | 0.193743E+09 | 0.121405E+09 | 72338408.04 | 0.301508E+09 | 0.149260E+09 |
Annual Sum or Average | 0.154673E+10 | 0.684350E+09 | 0.862384E+09 | 0.322350E+10 | 0.686331E+09 |
Minimum of Months | 65907601.50 | 977090.27 | 64782906.39 | 0.208359E+09 | 880797.90 |
Maximum of Months | 0.210083E+09 | 0.138860E+09 | 82291697.41 | 0.369000E+09 | 0.149260E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.181296E+09 | 0.110160E+09 | 71136080.39 | 0.273570E+09 | 0.148920E+09 |
February | 0.155704E+09 | 86482410.97 | 69221597.04 | 0.254695E+09 | 0.107877E+09 |
March | 0.147395E+09 | 65103030.68 | 82291697.41 | 0.280820E+09 | 71577357.09 |
April | 0.100191E+09 | 28276943.91 | 71913896.18 | 0.256656E+09 | 23449731.50 |
May | 74452123.42 | 5511480.70 | 68940642.72 | 0.245594E+09 | 3943355.65 |
June | 65907601.50 | 1124695.11 | 64782906.39 | 0.231737E+09 | 2937828.73 |
July | 71039507.28 | 977090.27 | 70062417.01 | 0.223207E+09 | 880797.90 |
August | 75357876.56 | 4024678.80 | 71333197.76 | 0.208359E+09 | 2789335.21 |
September | 97764495.24 | 25374984.65 | 72389510.59 | 0.228674E+09 | 10901853.62 |
October | 0.173800E+09 | 97049275.04 | 76750855.36 | 0.349678E+09 | 57396837.53 |
November | 0.210083E+09 | 0.138860E+09 | 71222517.68 | 0.369000E+09 | 0.106397E+09 |
December | 0.193743E+09 | 0.121405E+09 | 72338408.04 | 0.301508E+09 | 0.149260E+09 |
Annual Sum or Average | 0.154673E+10 | 0.684350E+09 | 0.862384E+09 | 0.322350E+10 | 0.686331E+09 |
Minimum of Months | 65907601.50 | 977090.27 | 64782906.39 | 0.208359E+09 | 880797.90 |
Maximum of Months | 0.210083E+09 | 0.138860E+09 | 82291697.41 | 0.369000E+09 | 0.149260E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.217946E+09 | 0.132430E+09 | 85516520.10 | 0.329013E+09 | 0.177471E+09 |
February | 0.187180E+09 | 0.103965E+09 | 83215016.38 | 0.306190E+09 | 0.128580E+09 |
March | 0.177191E+09 | 78263865.55 | 98927289.16 | 0.336898E+09 | 85561149.06 |
April | 0.120445E+09 | 33993239.84 | 86451574.42 | 0.306778E+09 | 28081843.23 |
May | 89502914.32 | 6625648.30 | 82877266.02 | 0.292225E+09 | 4799775.29 |
June | 79231083.54 | 1352056.67 | 77879026.87 | 0.275787E+09 | 3514876.44 |
July | 85400424.35 | 1174612.92 | 84225811.42 | 0.265793E+09 | 1077921.56 |
August | 90591769.04 | 4838283.52 | 85753485.52 | 0.248658E+09 | 3372084.99 |
September | 0.117528E+09 | 30504638.05 | 87023336.16 | 0.273458E+09 | 13069217.62 |
October | 0.208935E+09 | 0.116668E+09 | 92266344.01 | 0.418992E+09 | 68649427.24 |
November | 0.252552E+09 | 0.166931E+09 | 85620431.03 | 0.442841E+09 | 0.127050E+09 |
December | 0.232909E+09 | 0.145947E+09 | 86961903.03 | 0.362344E+09 | 0.177973E+09 |
Annual Sum or Average | 0.185941E+10 | 0.822694E+09 | 0.103672E+10 | 0.385898E+10 | 0.819200E+09 |
Minimum of Months | 79231083.54 | 1174612.92 | 77879026.87 | 0.248658E+09 | 1077921.56 |
Maximum of Months | 0.252552E+09 | 0.166931E+09 | 98927289.16 | 0.442841E+09 | 0.177973E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.217946E+09 | 0.132430E+09 | 85516520.10 | 0.329013E+09 | 0.177471E+09 |
February | 0.187180E+09 | 0.103965E+09 | 83215016.38 | 0.306190E+09 | 0.128580E+09 |
March | 0.177191E+09 | 78263865.55 | 98927289.16 | 0.336898E+09 | 85561149.06 |
April | 0.120445E+09 | 33993239.84 | 86451574.42 | 0.306778E+09 | 28081843.23 |
May | 89502914.32 | 6625648.30 | 82877266.02 | 0.292225E+09 | 4799775.29 |
June | 79231083.54 | 1352056.67 | 77879026.87 | 0.275787E+09 | 3514876.44 |
July | 85400424.35 | 1174612.92 | 84225811.42 | 0.265793E+09 | 1077921.56 |
August | 90591769.04 | 4838283.52 | 85753485.52 | 0.248658E+09 | 3372084.99 |
September | 0.117528E+09 | 30504638.05 | 87023336.16 | 0.273458E+09 | 13069217.62 |
October | 0.208935E+09 | 0.116668E+09 | 92266344.01 | 0.418992E+09 | 68649427.24 |
November | 0.252552E+09 | 0.166931E+09 | 85620431.03 | 0.442841E+09 | 0.127050E+09 |
December | 0.232909E+09 | 0.145947E+09 | 86961903.03 | 0.362344E+09 | 0.177973E+09 |
Annual Sum or Average | 0.185941E+10 | 0.822694E+09 | 0.103672E+10 | 0.385898E+10 | 0.819200E+09 |
Minimum of Months | 79231083.54 | 1174612.92 | 77879026.87 | 0.248658E+09 | 1077921.56 |
Maximum of Months | 0.252552E+09 | 0.166931E+09 | 98927289.16 | 0.442841E+09 | 0.177973E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.181296E+09 | 0.110160E+09 | 71136080.39 | 0.269938E+09 | 0.157444E+09 |
February | 0.155704E+09 | 86482410.97 | 69221597.04 | 0.252339E+09 | 0.112432E+09 |
March | 0.147395E+09 | 65103030.68 | 82291697.41 | 0.280070E+09 | 73492280.02 |
April | 0.100191E+09 | 28276943.91 | 71913896.18 | 0.258235E+09 | 23940973.71 |
May | 74452123.42 | 5511480.70 | 68940642.72 | 0.249063E+09 | 3881471.73 |
June | 65907601.50 | 1124695.11 | 64782906.39 | 0.235869E+09 | 2938480.34 |
July | 71039507.28 | 977090.27 | 70062417.01 | 0.227346E+09 | 809593.07 |
August | 75357876.56 | 4024678.80 | 71333197.76 | 0.211892E+09 | 2546926.53 |
September | 97764495.24 | 25374984.65 | 72389510.59 | 0.230959E+09 | 10317989.36 |
October | 0.173800E+09 | 97049275.04 | 76750855.36 | 0.350609E+09 | 57330563.79 |
November | 0.210083E+09 | 0.138860E+09 | 71222517.68 | 0.368232E+09 | 0.107858E+09 |
December | 0.193743E+09 | 0.121405E+09 | 72338408.04 | 0.298576E+09 | 0.155222E+09 |
Annual Sum or Average | 0.154673E+10 | 0.684350E+09 | 0.862384E+09 | 0.323313E+10 | 0.708215E+09 |
Minimum of Months | 65907601.50 | 977090.27 | 64782906.39 | 0.211892E+09 | 809593.07 |
Maximum of Months | 0.210083E+09 | 0.138860E+09 | 82291697.41 | 0.368232E+09 | 0.157444E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.181296E+09 | 0.110160E+09 | 71136080.39 | 0.269938E+09 | 0.157444E+09 |
February | 0.155704E+09 | 86482410.97 | 69221597.04 | 0.252339E+09 | 0.112432E+09 |
March | 0.147395E+09 | 65103030.68 | 82291697.41 | 0.280070E+09 | 73492280.02 |
April | 0.100191E+09 | 28276943.91 | 71913896.18 | 0.258235E+09 | 23940973.71 |
May | 74452123.42 | 5511480.70 | 68940642.72 | 0.249063E+09 | 3881471.73 |
June | 65907601.50 | 1124695.11 | 64782906.39 | 0.235869E+09 | 2938480.34 |
July | 71039507.28 | 977090.27 | 70062417.01 | 0.227346E+09 | 809593.07 |
August | 75357876.56 | 4024678.80 | 71333197.76 | 0.211892E+09 | 2546926.53 |
September | 97764495.24 | 25374984.65 | 72389510.59 | 0.230959E+09 | 10317989.36 |
October | 0.173800E+09 | 97049275.04 | 76750855.36 | 0.350609E+09 | 57330563.79 |
November | 0.210083E+09 | 0.138860E+09 | 71222517.68 | 0.368232E+09 | 0.107858E+09 |
December | 0.193743E+09 | 0.121405E+09 | 72338408.04 | 0.298576E+09 | 0.155222E+09 |
Annual Sum or Average | 0.154673E+10 | 0.684350E+09 | 0.862384E+09 | 0.323313E+10 | 0.708215E+09 |
Minimum of Months | 65907601.50 | 977090.27 | 64782906.39 | 0.211892E+09 | 809593.07 |
Maximum of Months | 0.210083E+09 | 0.138860E+09 | 82291697.41 | 0.368232E+09 | 0.157444E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.217946E+09 | 0.132430E+09 | 85516520.10 | 0.324751E+09 | 0.187544E+09 |
February | 0.187180E+09 | 0.103965E+09 | 83215016.38 | 0.303453E+09 | 0.133957E+09 |
March | 0.177191E+09 | 78263865.55 | 98927289.16 | 0.336057E+09 | 87831822.06 |
April | 0.120445E+09 | 33993239.84 | 86451574.42 | 0.308673E+09 | 28670083.86 |
May | 89502914.32 | 6625648.30 | 82877266.02 | 0.296302E+09 | 4728372.93 |
June | 79231083.54 | 1352056.67 | 77879026.87 | 0.280679E+09 | 3514194.61 |
July | 85400424.35 | 1174612.92 | 84225811.42 | 0.270693E+09 | 994473.86 |
August | 90591769.04 | 4838283.52 | 85753485.52 | 0.252881E+09 | 3077440.93 |
September | 0.117528E+09 | 30504638.05 | 87023336.16 | 0.276230E+09 | 12374914.62 |
October | 0.208935E+09 | 0.116668E+09 | 92266344.01 | 0.420168E+09 | 68559052.87 |
November | 0.252552E+09 | 0.166931E+09 | 85620431.03 | 0.442003E+09 | 0.128778E+09 |
December | 0.232909E+09 | 0.145947E+09 | 86961903.03 | 0.358920E+09 | 0.185021E+09 |
Annual Sum or Average | 0.185941E+10 | 0.822694E+09 | 0.103672E+10 | 0.387081E+10 | 0.845051E+09 |
Minimum of Months | 79231083.54 | 1174612.92 | 77879026.87 | 0.252881E+09 | 994473.86 |
Maximum of Months | 0.252552E+09 | 0.166931E+09 | 98927289.16 | 0.442003E+09 | 0.187544E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.181296E+09 | 0.110160E+09 | 71136080.39 | 0.271331E+09 | 0.153265E+09 |
February | 0.155704E+09 | 86482410.97 | 69221597.04 | 0.252869E+09 | 0.112235E+09 |
March | 0.147395E+09 | 65103030.68 | 82291697.41 | 0.279518E+09 | 76842906.91 |
April | 0.100191E+09 | 28276943.91 | 71913896.18 | 0.253537E+09 | 27353442.72 |
May | 74452123.42 | 5511480.70 | 68940642.72 | 0.239416E+09 | 5426527.36 |
June | 65907601.50 | 1124695.11 | 64782906.39 | 0.226011E+09 | 4207329.00 |
July | 71039507.28 | 977090.27 | 70062417.01 | 0.216293E+09 | 1314554.17 |
August | 75357876.56 | 4024678.80 | 71333197.76 | 0.204408E+09 | 4267947.16 |
September | 97764495.24 | 25374984.65 | 72389510.59 | 0.226535E+09 | 14293525.78 |
October | 0.173800E+09 | 97049275.04 | 76750855.36 | 0.349254E+09 | 63014468.61 |
November | 0.210083E+09 | 0.138860E+09 | 71222517.68 | 0.368362E+09 | 0.110485E+09 |
December | 0.193743E+09 | 0.121405E+09 | 72338408.04 | 0.299561E+09 | 0.153508E+09 |
Annual Sum or Average | 0.154673E+10 | 0.684350E+09 | 0.862384E+09 | 0.318709E+10 | 0.726213E+09 |
Minimum of Months | 65907601.50 | 977090.27 | 64782906.39 | 0.204408E+09 | 1314554.17 |
Maximum of Months | 0.210083E+09 | 0.138860E+09 | 82291697.41 | 0.368362E+09 | 0.153508E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.181296E+09 | 0.110160E+09 | 71136080.39 | 0.271331E+09 | 0.153265E+09 |
February | 0.155704E+09 | 86482410.97 | 69221597.04 | 0.252869E+09 | 0.112235E+09 |
March | 0.147395E+09 | 65103030.68 | 82291697.41 | 0.279518E+09 | 76842906.91 |
April | 0.100191E+09 | 28276943.91 | 71913896.18 | 0.253537E+09 | 27353442.72 |
May | 74452123.42 | 5511480.70 | 68940642.72 | 0.239416E+09 | 5426527.36 |
June | 65907601.50 | 1124695.11 | 64782906.39 | 0.226011E+09 | 4207329.00 |
July | 71039507.28 | 977090.27 | 70062417.01 | 0.216293E+09 | 1314554.17 |
August | 75357876.56 | 4024678.80 | 71333197.76 | 0.204408E+09 | 4267947.16 |
September | 97764495.24 | 25374984.65 | 72389510.59 | 0.226535E+09 | 14293525.78 |
October | 0.173800E+09 | 97049275.04 | 76750855.36 | 0.349254E+09 | 63014468.61 |
November | 0.210083E+09 | 0.138860E+09 | 71222517.68 | 0.368362E+09 | 0.110485E+09 |
December | 0.193743E+09 | 0.121405E+09 | 72338408.04 | 0.299561E+09 | 0.153508E+09 |
Annual Sum or Average | 0.154673E+10 | 0.684350E+09 | 0.862384E+09 | 0.318709E+10 | 0.726213E+09 |
Minimum of Months | 65907601.50 | 977090.27 | 64782906.39 | 0.204408E+09 | 1314554.17 |
Maximum of Months | 0.210083E+09 | 0.138860E+09 | 82291697.41 | 0.368362E+09 | 0.153508E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.216755E+09 | 0.131706E+09 | 85049216.71 | 0.324642E+09 | 0.181573E+09 |
February | 0.186157E+09 | 0.103397E+09 | 82760289.51 | 0.302433E+09 | 0.132958E+09 |
March | 0.176223E+09 | 77836194.16 | 98386702.88 | 0.333584E+09 | 91242358.14 |
April | 0.119787E+09 | 33807484.43 | 85979161.45 | 0.301531E+09 | 32534518.99 |
May | 89013827.36 | 6589442.57 | 82424384.79 | 0.283495E+09 | 6567292.82 |
June | 78798126.80 | 1344668.38 | 77453458.41 | 0.267657E+09 | 4994498.02 |
July | 84933755.36 | 1168194.27 | 83765561.09 | 0.256375E+09 | 1608160.52 |
August | 90096732.05 | 4811844.81 | 85284887.24 | 0.242807E+09 | 5107750.49 |
September | 0.116886E+09 | 30337946.04 | 86547798.80 | 0.269608E+09 | 17010240.96 |
October | 0.207793E+09 | 0.116031E+09 | 91762156.34 | 0.416297E+09 | 74840997.85 |
November | 0.251172E+09 | 0.166019E+09 | 85152559.82 | 0.439744E+09 | 0.131105E+09 |
December | 0.231637E+09 | 0.145150E+09 | 86486701.37 | 0.358135E+09 | 0.181952E+09 |
Annual Sum or Average | 0.184925E+10 | 0.818199E+09 | 0.103105E+10 | 0.379631E+10 | 0.861494E+09 |
Minimum of Months | 78798126.80 | 1168194.27 | 77453458.41 | 0.242807E+09 | 1608160.52 |
Maximum of Months | 0.251172E+09 | 0.166019E+09 | 98386702.88 | 0.439744E+09 | 0.181952E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.181296E+09 | 0.110160E+09 | 71136080.39 | 0.272228E+09 | 0.150629E+09 |
February | 0.155704E+09 | 86482410.97 | 69221597.04 | 0.253279E+09 | 0.111085E+09 |
March | 0.147395E+09 | 65103030.68 | 82291697.41 | 0.279599E+09 | 76645328.96 |
April | 0.100191E+09 | 28276943.91 | 71913896.18 | 0.253274E+09 | 27779801.94 |
May | 74452123.42 | 5511480.70 | 68940642.72 | 0.238484E+09 | 5835076.99 |
June | 65907601.50 | 1124695.11 | 64782906.39 | 0.224931E+09 | 4456753.02 |
July | 71039507.28 | 977090.27 | 70062417.01 | 0.215034E+09 | 1442329.07 |
August | 75357876.56 | 4024678.80 | 71333197.76 | 0.203682E+09 | 4554473.28 |
September | 97764495.24 | 25374984.65 | 72389510.59 | 0.226297E+09 | 14921949.73 |
October | 0.173800E+09 | 97049275.04 | 76750855.36 | 0.349158E+09 | 63457040.22 |
November | 0.210083E+09 | 0.138860E+09 | 71222517.68 | 0.368505E+09 | 0.110077E+09 |
December | 0.193743E+09 | 0.121405E+09 | 72338408.04 | 0.300180E+09 | 0.151874E+09 |
Annual Sum or Average | 0.154673E+10 | 0.684350E+09 | 0.862384E+09 | 0.318465E+10 | 0.722757E+09 |
Minimum of Months | 65907601.50 | 977090.27 | 64782906.39 | 0.203682E+09 | 1442329.07 |
Maximum of Months | 0.210083E+09 | 0.138860E+09 | 82291697.41 | 0.368505E+09 | 0.151874E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.181296E+09 | 0.110160E+09 | 71136080.39 | 0.272228E+09 | 0.150629E+09 |
February | 0.155704E+09 | 86482410.97 | 69221597.04 | 0.253279E+09 | 0.111085E+09 |
March | 0.147395E+09 | 65103030.68 | 82291697.41 | 0.279599E+09 | 76645328.96 |
April | 0.100191E+09 | 28276943.91 | 71913896.18 | 0.253274E+09 | 27779801.94 |
May | 74452123.42 | 5511480.70 | 68940642.72 | 0.238484E+09 | 5835076.99 |
June | 65907601.50 | 1124695.11 | 64782906.39 | 0.224931E+09 | 4456753.02 |
July | 71039507.28 | 977090.27 | 70062417.01 | 0.215034E+09 | 1442329.07 |
August | 75357876.56 | 4024678.80 | 71333197.76 | 0.203682E+09 | 4554473.28 |
September | 97764495.24 | 25374984.65 | 72389510.59 | 0.226297E+09 | 14921949.73 |
October | 0.173800E+09 | 97049275.04 | 76750855.36 | 0.349158E+09 | 63457040.22 |
November | 0.210083E+09 | 0.138860E+09 | 71222517.68 | 0.368505E+09 | 0.110077E+09 |
December | 0.193743E+09 | 0.121405E+09 | 72338408.04 | 0.300180E+09 | 0.151874E+09 |
Annual Sum or Average | 0.154673E+10 | 0.684350E+09 | 0.862384E+09 | 0.318465E+10 | 0.722757E+09 |
Minimum of Months | 65907601.50 | 977090.27 | 64782906.39 | 0.203682E+09 | 1442329.07 |
Maximum of Months | 0.210083E+09 | 0.138860E+09 | 82291697.41 | 0.368505E+09 | 0.151874E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.216755E+09 | 0.131706E+09 | 85049216.71 | 0.325716E+09 | 0.178450E+09 |
February | 0.186157E+09 | 0.103397E+09 | 82760289.51 | 0.302924E+09 | 0.131598E+09 |
March | 0.176223E+09 | 77836194.16 | 98386702.88 | 0.333681E+09 | 91009563.05 |
April | 0.119787E+09 | 33807484.43 | 85979161.45 | 0.301217E+09 | 33041087.02 |
May | 89013827.36 | 6589442.57 | 82424384.79 | 0.282399E+09 | 7062636.60 |
June | 78798126.80 | 1344668.38 | 77453458.41 | 0.266375E+09 | 5292289.39 |
July | 84933755.36 | 1168194.27 | 83765561.09 | 0.254888E+09 | 1763916.94 |
August | 90096732.05 | 4811844.81 | 85284887.24 | 0.241948E+09 | 5451737.32 |
September | 0.116886E+09 | 30337946.04 | 86547798.80 | 0.269325E+09 | 17756799.33 |
October | 0.207793E+09 | 0.116031E+09 | 91762156.34 | 0.416182E+09 | 75367252.75 |
November | 0.251172E+09 | 0.166019E+09 | 85152559.82 | 0.439916E+09 | 0.130621E+09 |
December | 0.231637E+09 | 0.145150E+09 | 86486701.37 | 0.358875E+09 | 0.180016E+09 |
Annual Sum or Average | 0.184925E+10 | 0.818199E+09 | 0.103105E+10 | 0.379345E+10 | 0.857430E+09 |
Minimum of Months | 78798126.80 | 1168194.27 | 77453458.41 | 0.241948E+09 | 1763916.94 |
Maximum of Months | 0.251172E+09 | 0.166019E+09 | 98386702.88 | 0.439916E+09 | 0.180016E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.181296E+09 | 0.110160E+09 | 71136080.39 | 0.273419E+09 | 0.147873E+09 |
February | 0.155704E+09 | 86482410.97 | 69221597.04 | 0.253973E+09 | 0.109512E+09 |
March | 0.147395E+09 | 65103030.68 | 82291697.41 | 0.280045E+09 | 75544280.78 |
April | 0.100191E+09 | 28276943.91 | 71913896.18 | 0.253708E+09 | 27100409.54 |
May | 74452123.42 | 5511480.70 | 68940642.72 | 0.239126E+09 | 5546916.40 |
June | 65907601.50 | 1124695.11 | 64782906.39 | 0.225704E+09 | 4289505.01 |
July | 71039507.28 | 977090.27 | 70062417.01 | 0.215702E+09 | 1309496.43 |
August | 75357876.56 | 4024678.80 | 71333197.76 | 0.204270E+09 | 4247232.30 |
September | 97764495.24 | 25374984.65 | 72389510.59 | 0.226592E+09 | 14270819.10 |
October | 0.173800E+09 | 97049275.04 | 76750855.36 | 0.349396E+09 | 62675935.93 |
November | 0.210083E+09 | 0.138860E+09 | 71222517.68 | 0.368896E+09 | 0.109076E+09 |
December | 0.193743E+09 | 0.121405E+09 | 72338408.04 | 0.301097E+09 | 0.149968E+09 |
Annual Sum or Average | 0.154673E+10 | 0.684350E+09 | 0.862384E+09 | 0.319193E+10 | 0.711414E+09 |
Minimum of Months | 65907601.50 | 977090.27 | 64782906.39 | 0.204270E+09 | 1309496.43 |
Maximum of Months | 0.210083E+09 | 0.138860E+09 | 82291697.41 | 0.368896E+09 | 0.149968E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.181296E+09 | 0.110160E+09 | 71136080.39 | 0.273419E+09 | 0.147873E+09 |
February | 0.155704E+09 | 86482410.97 | 69221597.04 | 0.253973E+09 | 0.109512E+09 |
March | 0.147395E+09 | 65103030.68 | 82291697.41 | 0.280045E+09 | 75544280.78 |
April | 0.100191E+09 | 28276943.91 | 71913896.18 | 0.253708E+09 | 27100409.54 |
May | 74452123.42 | 5511480.70 | 68940642.72 | 0.239126E+09 | 5546916.40 |
June | 65907601.50 | 1124695.11 | 64782906.39 | 0.225704E+09 | 4289505.01 |
July | 71039507.28 | 977090.27 | 70062417.01 | 0.215702E+09 | 1309496.43 |
August | 75357876.56 | 4024678.80 | 71333197.76 | 0.204270E+09 | 4247232.30 |
September | 97764495.24 | 25374984.65 | 72389510.59 | 0.226592E+09 | 14270819.10 |
October | 0.173800E+09 | 97049275.04 | 76750855.36 | 0.349396E+09 | 62675935.93 |
November | 0.210083E+09 | 0.138860E+09 | 71222517.68 | 0.368896E+09 | 0.109076E+09 |
December | 0.193743E+09 | 0.121405E+09 | 72338408.04 | 0.301097E+09 | 0.149968E+09 |
Annual Sum or Average | 0.154673E+10 | 0.684350E+09 | 0.862384E+09 | 0.319193E+10 | 0.711414E+09 |
Minimum of Months | 65907601.50 | 977090.27 | 64782906.39 | 0.204270E+09 | 1309496.43 |
Maximum of Months | 0.210083E+09 | 0.138860E+09 | 82291697.41 | 0.368896E+09 | 0.149968E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.216755E+09 | 0.131706E+09 | 85049216.71 | 0.327141E+09 | 0.175193E+09 |
February | 0.186157E+09 | 0.103397E+09 | 82760289.51 | 0.303755E+09 | 0.129743E+09 |
March | 0.176223E+09 | 77836194.16 | 98386702.88 | 0.334217E+09 | 89711798.68 |
April | 0.119787E+09 | 33807484.43 | 85979161.45 | 0.301739E+09 | 32239787.25 |
May | 89013827.36 | 6589442.57 | 82424384.79 | 0.283153E+09 | 6716821.38 |
June | 78798126.80 | 1344668.38 | 77453458.41 | 0.267288E+09 | 5093433.43 |
July | 84933755.36 | 1168194.27 | 83765561.09 | 0.255670E+09 | 1602681.51 |
August | 90096732.05 | 4811844.81 | 85284887.24 | 0.242641E+09 | 5086605.51 |
September | 0.116886E+09 | 30337946.04 | 86547798.80 | 0.269678E+09 | 16990130.55 |
October | 0.207793E+09 | 0.116031E+09 | 91762156.34 | 0.416469E+09 | 74444564.37 |
November | 0.251172E+09 | 0.166019E+09 | 85152559.82 | 0.440387E+09 | 0.129440E+09 |
December | 0.231637E+09 | 0.145150E+09 | 86486701.37 | 0.359971E+09 | 0.177763E+09 |
Annual Sum or Average | 0.184925E+10 | 0.818199E+09 | 0.103105E+10 | 0.380211E+10 | 0.844025E+09 |
Minimum of Months | 78798126.80 | 1168194.27 | 77453458.41 | 0.242641E+09 | 1602681.51 |
Maximum of Months | 0.251172E+09 | 0.166019E+09 | 98386702.88 | 0.440387E+09 | 0.177763E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.181296E+09 | 0.110160E+09 | 71136080.39 | 0.276010E+09 | 0.142144E+09 |
February | 0.155704E+09 | 86482410.97 | 69221597.04 | 0.255601E+09 | 0.105875E+09 |
March | 0.147395E+09 | 65103030.68 | 82291697.41 | 0.280937E+09 | 72434999.32 |
April | 0.100191E+09 | 28276943.91 | 71913896.18 | 0.254354E+09 | 25089592.99 |
May | 74452123.42 | 5511480.70 | 68940642.72 | 0.239852E+09 | 4777138.11 |
June | 65907601.50 | 1124695.11 | 64782906.39 | 0.227004E+09 | 3864694.35 |
July | 71039507.28 | 977090.27 | 70062417.01 | 0.216143E+09 | 972614.79 |
August | 75357876.56 | 4024678.80 | 71333197.76 | 0.204833E+09 | 3380215.60 |
September | 97764495.24 | 25374984.65 | 72389510.59 | 0.226602E+09 | 12457849.85 |
October | 0.173800E+09 | 97049275.04 | 76750855.36 | 0.349280E+09 | 60252993.95 |
November | 0.210083E+09 | 0.138860E+09 | 71222517.68 | 0.369501E+09 | 0.106576E+09 |
December | 0.193743E+09 | 0.121405E+09 | 72338408.04 | 0.303067E+09 | 0.145686E+09 |
Annual Sum or Average | 0.154673E+10 | 0.684350E+09 | 0.862384E+09 | 0.320318E+10 | 0.683512E+09 |
Minimum of Months | 65907601.50 | 977090.27 | 64782906.39 | 0.204833E+09 | 972614.79 |
Maximum of Months | 0.210083E+09 | 0.138860E+09 | 82291697.41 | 0.369501E+09 | 0.145686E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.181296E+09 | 0.110160E+09 | 71136080.39 | 0.276010E+09 | 0.142144E+09 |
February | 0.155704E+09 | 86482410.97 | 69221597.04 | 0.255601E+09 | 0.105875E+09 |
March | 0.147395E+09 | 65103030.68 | 82291697.41 | 0.280937E+09 | 72434999.32 |
April | 0.100191E+09 | 28276943.91 | 71913896.18 | 0.254354E+09 | 25089592.99 |
May | 74452123.42 | 5511480.70 | 68940642.72 | 0.239852E+09 | 4777138.11 |
June | 65907601.50 | 1124695.11 | 64782906.39 | 0.227004E+09 | 3864694.35 |
July | 71039507.28 | 977090.27 | 70062417.01 | 0.216143E+09 | 972614.79 |
August | 75357876.56 | 4024678.80 | 71333197.76 | 0.204833E+09 | 3380215.60 |
September | 97764495.24 | 25374984.65 | 72389510.59 | 0.226602E+09 | 12457849.85 |
October | 0.173800E+09 | 97049275.04 | 76750855.36 | 0.349280E+09 | 60252993.95 |
November | 0.210083E+09 | 0.138860E+09 | 71222517.68 | 0.369501E+09 | 0.106576E+09 |
December | 0.193743E+09 | 0.121405E+09 | 72338408.04 | 0.303067E+09 | 0.145686E+09 |
Annual Sum or Average | 0.154673E+10 | 0.684350E+09 | 0.862384E+09 | 0.320318E+10 | 0.683512E+09 |
Minimum of Months | 65907601.50 | 977090.27 | 64782906.39 | 0.204833E+09 | 972614.79 |
Maximum of Months | 0.210083E+09 | 0.138860E+09 | 82291697.41 | 0.369501E+09 | 0.145686E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.181296E+09 | 0.110160E+09 | 71136080.39 | 0.276010E+09 | 0.142144E+09 |
February | 0.155704E+09 | 86482410.97 | 69221597.04 | 0.255601E+09 | 0.105875E+09 |
March | 0.147395E+09 | 65103030.68 | 82291697.41 | 0.280937E+09 | 72434999.32 |
April | 0.100191E+09 | 28276943.91 | 71913896.18 | 0.254354E+09 | 25089592.99 |
May | 74452123.42 | 5511480.70 | 68940642.72 | 0.239852E+09 | 4777138.11 |
June | 65907601.50 | 1124695.11 | 64782906.39 | 0.227004E+09 | 3864694.35 |
July | 71039507.28 | 977090.27 | 70062417.01 | 0.216143E+09 | 972614.79 |
August | 75357876.56 | 4024678.80 | 71333197.76 | 0.204833E+09 | 3380215.60 |
September | 97764495.24 | 25374984.65 | 72389510.59 | 0.226602E+09 | 12457849.85 |
October | 0.173800E+09 | 97049275.04 | 76750855.36 | 0.349280E+09 | 60252993.95 |
November | 0.210083E+09 | 0.138860E+09 | 71222517.68 | 0.369501E+09 | 0.106576E+09 |
December | 0.193743E+09 | 0.121405E+09 | 72338408.04 | 0.303067E+09 | 0.145686E+09 |
Annual Sum or Average | 0.154673E+10 | 0.684350E+09 | 0.862384E+09 | 0.320318E+10 | 0.683512E+09 |
Minimum of Months | 65907601.50 | 977090.27 | 64782906.39 | 0.204833E+09 | 972614.79 |
Maximum of Months | 0.210083E+09 | 0.138860E+09 | 82291697.41 | 0.369501E+09 | 0.145686E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.181296E+09 | 0.110160E+09 | 71136080.39 | 0.276010E+09 | 0.142144E+09 |
February | 0.155704E+09 | 86482410.97 | 69221597.04 | 0.255601E+09 | 0.105875E+09 |
March | 0.147395E+09 | 65103030.68 | 82291697.41 | 0.280937E+09 | 72434999.32 |
April | 0.100191E+09 | 28276943.91 | 71913896.18 | 0.254354E+09 | 25089592.99 |
May | 74452123.42 | 5511480.70 | 68940642.72 | 0.239852E+09 | 4777138.11 |
June | 65907601.50 | 1124695.11 | 64782906.39 | 0.227004E+09 | 3864694.35 |
July | 71039507.28 | 977090.27 | 70062417.01 | 0.216143E+09 | 972614.79 |
August | 75357876.56 | 4024678.80 | 71333197.76 | 0.204833E+09 | 3380215.60 |
September | 97764495.24 | 25374984.65 | 72389510.59 | 0.226602E+09 | 12457849.85 |
October | 0.173800E+09 | 97049275.04 | 76750855.36 | 0.349280E+09 | 60252993.95 |
November | 0.210083E+09 | 0.138860E+09 | 71222517.68 | 0.369501E+09 | 0.106576E+09 |
December | 0.193743E+09 | 0.121405E+09 | 72338408.04 | 0.303067E+09 | 0.145686E+09 |
Annual Sum or Average | 0.154673E+10 | 0.684350E+09 | 0.862384E+09 | 0.320318E+10 | 0.683512E+09 |
Minimum of Months | 65907601.50 | 977090.27 | 64782906.39 | 0.204833E+09 | 972614.79 |
Maximum of Months | 0.210083E+09 | 0.138860E+09 | 82291697.41 | 0.369501E+09 | 0.145686E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.216755E+09 | 0.131706E+09 | 85049216.71 | 0.330158E+09 | 0.168437E+09 |
February | 0.186157E+09 | 0.103397E+09 | 82760289.51 | 0.305626E+09 | 0.125459E+09 |
March | 0.176223E+09 | 77836194.16 | 98386702.88 | 0.335245E+09 | 86031987.14 |
April | 0.119787E+09 | 33807484.43 | 85979161.45 | 0.302529E+09 | 29836726.40 |
May | 89013827.36 | 6589442.57 | 82424384.79 | 0.284101E+09 | 5775635.41 |
June | 78798126.80 | 1344668.38 | 77453458.41 | 0.268915E+09 | 4575573.52 |
July | 84933755.36 | 1168194.27 | 83765561.09 | 0.256266E+09 | 1189343.70 |
August | 90096732.05 | 4811844.81 | 85284887.24 | 0.243341E+09 | 4043023.78 |
September | 0.116886E+09 | 30337946.04 | 86547798.80 | 0.269696E+09 | 14815521.60 |
October | 0.207793E+09 | 0.116031E+09 | 91762156.34 | 0.416314E+09 | 71561576.90 |
November | 0.251172E+09 | 0.166019E+09 | 85152559.82 | 0.441056E+09 | 0.126472E+09 |
December | 0.231637E+09 | 0.145150E+09 | 86486701.37 | 0.362251E+09 | 0.172704E+09 |
Annual Sum or Average | 0.184925E+10 | 0.818199E+09 | 0.103105E+10 | 0.381550E+10 | 0.810901E+09 |
Minimum of Months | 78798126.80 | 1168194.27 | 77453458.41 | 0.243341E+09 | 1189343.70 |
Maximum of Months | 0.251172E+09 | 0.166019E+09 | 98386702.88 | 0.441056E+09 | 0.172704E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.216755E+09 | 0.131706E+09 | 85049216.71 | 0.330158E+09 | 0.168437E+09 |
February | 0.186157E+09 | 0.103397E+09 | 82760289.51 | 0.305626E+09 | 0.125459E+09 |
March | 0.176223E+09 | 77836194.16 | 98386702.88 | 0.335245E+09 | 86031987.14 |
April | 0.119787E+09 | 33807484.43 | 85979161.45 | 0.302529E+09 | 29836726.40 |
May | 89013827.36 | 6589442.57 | 82424384.79 | 0.284101E+09 | 5775635.41 |
June | 78798126.80 | 1344668.38 | 77453458.41 | 0.268915E+09 | 4575573.52 |
July | 84933755.36 | 1168194.27 | 83765561.09 | 0.256266E+09 | 1189343.70 |
August | 90096732.05 | 4811844.81 | 85284887.24 | 0.243341E+09 | 4043023.78 |
September | 0.116886E+09 | 30337946.04 | 86547798.80 | 0.269696E+09 | 14815521.60 |
October | 0.207793E+09 | 0.116031E+09 | 91762156.34 | 0.416314E+09 | 71561576.90 |
November | 0.251172E+09 | 0.166019E+09 | 85152559.82 | 0.441056E+09 | 0.126472E+09 |
December | 0.231637E+09 | 0.145150E+09 | 86486701.37 | 0.362251E+09 | 0.172704E+09 |
Annual Sum or Average | 0.184925E+10 | 0.818199E+09 | 0.103105E+10 | 0.381550E+10 | 0.810901E+09 |
Minimum of Months | 78798126.80 | 1168194.27 | 77453458.41 | 0.243341E+09 | 1189343.70 |
Maximum of Months | 0.251172E+09 | 0.166019E+09 | 98386702.88 | 0.441056E+09 | 0.172704E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.181296E+09 | 0.110160E+09 | 71136080.39 | 0.275818E+09 | 0.141684E+09 |
February | 0.155704E+09 | 86482410.97 | 69221597.04 | 0.255329E+09 | 0.105544E+09 |
March | 0.147395E+09 | 65103030.68 | 82291697.41 | 0.280961E+09 | 71774537.29 |
April | 0.100191E+09 | 28276943.91 | 71913896.18 | 0.255298E+09 | 24417622.69 |
May | 74452123.42 | 5511480.70 | 68940642.72 | 0.242052E+09 | 4402389.10 |
June | 65907601.50 | 1124695.11 | 64782906.39 | 0.229396E+09 | 3652469.63 |
July | 71039507.28 | 977090.27 | 70062417.01 | 0.218450E+09 | 830973.25 |
August | 75357876.56 | 4024678.80 | 71333197.76 | 0.206526E+09 | 3005115.84 |
September | 97764495.24 | 25374984.65 | 72389510.59 | 0.227464E+09 | 11631901.10 |
October | 0.173800E+09 | 97049275.04 | 76750855.36 | 0.349560E+09 | 59347034.19 |
November | 0.210083E+09 | 0.138860E+09 | 71222517.68 | 0.369338E+09 | 0.106034E+09 |
December | 0.193743E+09 | 0.121405E+09 | 72338408.04 | 0.302857E+09 | 0.145350E+09 |
Annual Sum or Average | 0.154673E+10 | 0.684350E+09 | 0.862384E+09 | 0.321305E+10 | 0.677675E+09 |
Minimum of Months | 65907601.50 | 977090.27 | 64782906.39 | 0.206526E+09 | 830973.25 |
Maximum of Months | 0.210083E+09 | 0.138860E+09 | 82291697.41 | 0.369338E+09 | 0.145350E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.181296E+09 | 0.110160E+09 | 71136080.39 | 0.275818E+09 | 0.141684E+09 |
February | 0.155704E+09 | 86482410.97 | 69221597.04 | 0.255329E+09 | 0.105544E+09 |
March | 0.147395E+09 | 65103030.68 | 82291697.41 | 0.280961E+09 | 71774537.29 |
April | 0.100191E+09 | 28276943.91 | 71913896.18 | 0.255298E+09 | 24417622.69 |
May | 74452123.42 | 5511480.70 | 68940642.72 | 0.242052E+09 | 4402389.10 |
June | 65907601.50 | 1124695.11 | 64782906.39 | 0.229396E+09 | 3652469.63 |
July | 71039507.28 | 977090.27 | 70062417.01 | 0.218450E+09 | 830973.25 |
August | 75357876.56 | 4024678.80 | 71333197.76 | 0.206526E+09 | 3005115.84 |
September | 97764495.24 | 25374984.65 | 72389510.59 | 0.227464E+09 | 11631901.10 |
October | 0.173800E+09 | 97049275.04 | 76750855.36 | 0.349560E+09 | 59347034.19 |
November | 0.210083E+09 | 0.138860E+09 | 71222517.68 | 0.369338E+09 | 0.106034E+09 |
December | 0.193743E+09 | 0.121405E+09 | 72338408.04 | 0.302857E+09 | 0.145350E+09 |
Annual Sum or Average | 0.154673E+10 | 0.684350E+09 | 0.862384E+09 | 0.321305E+10 | 0.677675E+09 |
Minimum of Months | 65907601.50 | 977090.27 | 64782906.39 | 0.206526E+09 | 830973.25 |
Maximum of Months | 0.210083E+09 | 0.138860E+09 | 82291697.41 | 0.369338E+09 | 0.145350E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.216755E+09 | 0.131706E+09 | 85049216.71 | 0.330032E+09 | 0.167865E+09 |
February | 0.186157E+09 | 0.103397E+09 | 82760289.51 | 0.305399E+09 | 0.125046E+09 |
March | 0.176223E+09 | 77836194.16 | 98386702.88 | 0.335345E+09 | 85249882.77 |
April | 0.119787E+09 | 33807484.43 | 85979161.45 | 0.303656E+09 | 29046758.99 |
May | 89013827.36 | 6589442.57 | 82424384.79 | 0.286616E+09 | 5329072.21 |
June | 78798126.80 | 1344668.38 | 77453458.41 | 0.271679E+09 | 4323637.01 |
July | 84933755.36 | 1168194.27 | 83765561.09 | 0.258930E+09 | 1017943.66 |
August | 90096732.05 | 4811844.81 | 85284887.24 | 0.245332E+09 | 3599076.51 |
September | 0.116886E+09 | 30337946.04 | 86547798.80 | 0.270742E+09 | 13839271.31 |
October | 0.207793E+09 | 0.116031E+09 | 91762156.34 | 0.416707E+09 | 70485274.18 |
November | 0.251172E+09 | 0.166019E+09 | 85152559.82 | 0.440953E+09 | 0.125820E+09 |
December | 0.231637E+09 | 0.145150E+09 | 86486701.37 | 0.362095E+09 | 0.172279E+09 |
Annual Sum or Average | 0.184925E+10 | 0.818199E+09 | 0.103105E+10 | 0.382749E+10 | 0.803901E+09 |
Minimum of Months | 78798126.80 | 1168194.27 | 77453458.41 | 0.245332E+09 | 1017943.66 |
Maximum of Months | 0.251172E+09 | 0.166019E+09 | 98386702.88 | 0.440953E+09 | 0.172279E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.181296E+09 | 0.110160E+09 | 71136080.39 | 0.276226E+09 | 0.140869E+09 |
February | 0.155704E+09 | 86482410.97 | 69221597.04 | 0.255625E+09 | 0.104994E+09 |
March | 0.147395E+09 | 65103030.68 | 82291697.41 | 0.281164E+09 | 71428252.76 |
April | 0.100191E+09 | 28276943.91 | 71913896.18 | 0.255460E+09 | 24257502.61 |
May | 74452123.42 | 5511480.70 | 68940642.72 | 0.242241E+09 | 4352375.28 |
June | 65907601.50 | 1124695.11 | 64782906.39 | 0.229604E+09 | 3618029.55 |
July | 71039507.28 | 977090.27 | 70062417.01 | 0.218630E+09 | 815911.83 |
August | 75357876.56 | 4024678.80 | 71333197.76 | 0.206682E+09 | 2960053.06 |
September | 97764495.24 | 25374984.65 | 72389510.59 | 0.227574E+09 | 11523974.82 |
October | 0.173800E+09 | 97049275.04 | 76750855.36 | 0.349656E+09 | 59166978.11 |
November | 0.210083E+09 | 0.138860E+09 | 71222517.68 | 0.369502E+09 | 0.105738E+09 |
December | 0.193743E+09 | 0.121405E+09 | 72338408.04 | 0.303227E+09 | 0.144696E+09 |
Annual Sum or Average | 0.154673E+10 | 0.684350E+09 | 0.862384E+09 | 0.321559E+10 | 0.674421E+09 |
Minimum of Months | 65907601.50 | 977090.27 | 64782906.39 | 0.206682E+09 | 815911.83 |
Maximum of Months | 0.210083E+09 | 0.138860E+09 | 82291697.41 | 0.369502E+09 | 0.144696E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.181296E+09 | 0.110160E+09 | 71136080.39 | 0.276226E+09 | 0.140869E+09 |
February | 0.155704E+09 | 86482410.97 | 69221597.04 | 0.255625E+09 | 0.104994E+09 |
March | 0.147395E+09 | 65103030.68 | 82291697.41 | 0.281164E+09 | 71428252.76 |
April | 0.100191E+09 | 28276943.91 | 71913896.18 | 0.255460E+09 | 24257502.61 |
May | 74452123.42 | 5511480.70 | 68940642.72 | 0.242241E+09 | 4352375.28 |
June | 65907601.50 | 1124695.11 | 64782906.39 | 0.229604E+09 | 3618029.55 |
July | 71039507.28 | 977090.27 | 70062417.01 | 0.218630E+09 | 815911.83 |
August | 75357876.56 | 4024678.80 | 71333197.76 | 0.206682E+09 | 2960053.06 |
September | 97764495.24 | 25374984.65 | 72389510.59 | 0.227574E+09 | 11523974.82 |
October | 0.173800E+09 | 97049275.04 | 76750855.36 | 0.349656E+09 | 59166978.11 |
November | 0.210083E+09 | 0.138860E+09 | 71222517.68 | 0.369502E+09 | 0.105738E+09 |
December | 0.193743E+09 | 0.121405E+09 | 72338408.04 | 0.303227E+09 | 0.144696E+09 |
Annual Sum or Average | 0.154673E+10 | 0.684350E+09 | 0.862384E+09 | 0.321559E+10 | 0.674421E+09 |
Minimum of Months | 65907601.50 | 977090.27 | 64782906.39 | 0.206682E+09 | 815911.83 |
Maximum of Months | 0.210083E+09 | 0.138860E+09 | 82291697.41 | 0.369502E+09 | 0.144696E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.216755E+09 | 0.131706E+09 | 85049216.71 | 0.330520E+09 | 0.166900E+09 |
February | 0.186157E+09 | 0.103397E+09 | 82760289.51 | 0.305753E+09 | 0.124395E+09 |
March | 0.176223E+09 | 77836194.16 | 98386702.88 | 0.335589E+09 | 84839761.22 |
April | 0.119787E+09 | 33807484.43 | 85979161.45 | 0.303850E+09 | 28856349.97 |
May | 89013827.36 | 6589442.57 | 82424384.79 | 0.286840E+09 | 5268831.12 |
June | 78798126.80 | 1344668.38 | 77453458.41 | 0.271928E+09 | 4282640.73 |
July | 84933755.36 | 1168194.27 | 83765561.09 | 0.259144E+09 | 999498.28 |
August | 90096732.05 | 4811844.81 | 85284887.24 | 0.245517E+09 | 3545388.44 |
September | 0.116886E+09 | 30337946.04 | 86547798.80 | 0.270873E+09 | 13710700.00 |
October | 0.207793E+09 | 0.116031E+09 | 91762156.34 | 0.416823E+09 | 70271816.87 |
November | 0.251172E+09 | 0.166019E+09 | 85152559.82 | 0.441150E+09 | 0.125469E+09 |
December | 0.231637E+09 | 0.145150E+09 | 86486701.37 | 0.362536E+09 | 0.171505E+09 |
Annual Sum or Average | 0.184925E+10 | 0.818199E+09 | 0.103105E+10 | 0.383052E+10 | 0.800044E+09 |
Minimum of Months | 78798126.80 | 1168194.27 | 77453458.41 | 0.245517E+09 | 999498.28 |
Maximum of Months | 0.251172E+09 | 0.166019E+09 | 98386702.88 | 0.441150E+09 | 0.171505E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.181296E+09 | 0.110160E+09 | 71136080.39 | 0.277129E+09 | 0.138763E+09 |
February | 0.155704E+09 | 86482410.97 | 69221597.04 | 0.256358E+09 | 0.103410E+09 |
March | 0.147395E+09 | 65103030.68 | 82291697.41 | 0.281553E+09 | 70533199.47 |
April | 0.100191E+09 | 28276943.91 | 71913896.18 | 0.255293E+09 | 24154793.78 |
May | 74452123.42 | 5511480.70 | 68940642.72 | 0.241540E+09 | 4467969.96 |
June | 65907601.50 | 1124695.11 | 64782906.39 | 0.228730E+09 | 3687843.10 |
July | 71039507.28 | 977090.27 | 70062417.01 | 0.217500E+09 | 860742.97 |
August | 75357876.56 | 4024678.80 | 71333197.76 | 0.205813E+09 | 3122385.72 |
September | 97764495.24 | 25374984.65 | 72389510.59 | 0.227153E+09 | 11878850.75 |
October | 0.173800E+09 | 97049275.04 | 76750855.36 | 0.349515E+09 | 59263765.16 |
November | 0.210083E+09 | 0.138860E+09 | 71222517.68 | 0.369816E+09 | 0.105060E+09 |
December | 0.193743E+09 | 0.121405E+09 | 72338408.04 | 0.304117E+09 | 0.142911E+09 |
Annual Sum or Average | 0.154673E+10 | 0.684350E+09 | 0.862384E+09 | 0.321452E+10 | 0.668113E+09 |
Minimum of Months | 65907601.50 | 977090.27 | 64782906.39 | 0.205813E+09 | 860742.97 |
Maximum of Months | 0.210083E+09 | 0.138860E+09 | 82291697.41 | 0.369816E+09 | 0.142911E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.181296E+09 | 0.110160E+09 | 71136080.39 | 0.277129E+09 | 0.138763E+09 |
February | 0.155704E+09 | 86482410.97 | 69221597.04 | 0.256358E+09 | 0.103410E+09 |
March | 0.147395E+09 | 65103030.68 | 82291697.41 | 0.281553E+09 | 70533199.47 |
April | 0.100191E+09 | 28276943.91 | 71913896.18 | 0.255293E+09 | 24154793.78 |
May | 74452123.42 | 5511480.70 | 68940642.72 | 0.241540E+09 | 4467969.96 |
June | 65907601.50 | 1124695.11 | 64782906.39 | 0.228730E+09 | 3687843.10 |
July | 71039507.28 | 977090.27 | 70062417.01 | 0.217500E+09 | 860742.97 |
August | 75357876.56 | 4024678.80 | 71333197.76 | 0.205813E+09 | 3122385.72 |
September | 97764495.24 | 25374984.65 | 72389510.59 | 0.227153E+09 | 11878850.75 |
October | 0.173800E+09 | 97049275.04 | 76750855.36 | 0.349515E+09 | 59263765.16 |
November | 0.210083E+09 | 0.138860E+09 | 71222517.68 | 0.369816E+09 | 0.105060E+09 |
December | 0.193743E+09 | 0.121405E+09 | 72338408.04 | 0.304117E+09 | 0.142911E+09 |
Annual Sum or Average | 0.154673E+10 | 0.684350E+09 | 0.862384E+09 | 0.321452E+10 | 0.668113E+09 |
Minimum of Months | 65907601.50 | 977090.27 | 64782906.39 | 0.205813E+09 | 860742.97 |
Maximum of Months | 0.210083E+09 | 0.138860E+09 | 82291697.41 | 0.369816E+09 | 0.142911E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.216755E+09 | 0.131706E+09 | 85049216.71 | 0.331598E+09 | 0.164414E+09 |
February | 0.186157E+09 | 0.103397E+09 | 82760289.51 | 0.306629E+09 | 0.122529E+09 |
March | 0.176223E+09 | 77836194.16 | 98386702.88 | 0.336055E+09 | 83788639.25 |
April | 0.119787E+09 | 33807484.43 | 85979161.45 | 0.303649E+09 | 28739795.70 |
May | 89013827.36 | 6589442.57 | 82424384.79 | 0.286004E+09 | 5414087.26 |
June | 78798126.80 | 1344668.38 | 77453458.41 | 0.270878E+09 | 4367121.70 |
July | 84933755.36 | 1168194.27 | 83765561.09 | 0.257796E+09 | 1054907.38 |
August | 90096732.05 | 4811844.81 | 85284887.24 | 0.244478E+09 | 3742565.67 |
September | 0.116886E+09 | 30337946.04 | 86547798.80 | 0.270368E+09 | 14139011.49 |
October | 0.207793E+09 | 0.116031E+09 | 91762156.34 | 0.416653E+09 | 70393959.83 |
November | 0.251172E+09 | 0.166019E+09 | 85152559.82 | 0.441525E+09 | 0.124671E+09 |
December | 0.231637E+09 | 0.145150E+09 | 86486701.37 | 0.363596E+09 | 0.169396E+09 |
Annual Sum or Average | 0.184925E+10 | 0.818199E+09 | 0.103105E+10 | 0.382923E+10 | 0.792650E+09 |
Minimum of Months | 78798126.80 | 1168194.27 | 77453458.41 | 0.244478E+09 | 1054907.38 |
Maximum of Months | 0.251172E+09 | 0.166019E+09 | 98386702.88 | 0.441525E+09 | 0.169396E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.181296E+09 | 0.110160E+09 | 71136080.39 | 0.278212E+09 | 0.132245E+09 |
February | 0.155704E+09 | 86482410.97 | 69221597.04 | 0.257258E+09 | 97924395.76 |
March | 0.147395E+09 | 65103030.68 | 82291697.41 | 0.281241E+09 | 67158158.98 |
April | 0.100191E+09 | 28276943.91 | 71913896.18 | 0.251906E+09 | 24028108.27 |
May | 74452123.42 | 5511480.70 | 68940642.72 | 0.234851E+09 | 5232344.85 |
June | 65907601.50 | 1124695.11 | 64782906.39 | 0.220988E+09 | 4148994.57 |
July | 71039507.28 | 977090.27 | 70062417.01 | 0.208736E+09 | 1284860.55 |
August | 75357876.56 | 4024678.80 | 71333197.76 | 0.198731E+09 | 4478080.48 |
September | 97764495.24 | 25374984.65 | 72389510.59 | 0.222960E+09 | 14601338.93 |
October | 0.173800E+09 | 97049275.04 | 76750855.36 | 0.346984E+09 | 60611555.58 |
November | 0.210083E+09 | 0.138860E+09 | 71222517.68 | 0.369483E+09 | 0.102751E+09 |
December | 0.193743E+09 | 0.121405E+09 | 72338408.04 | 0.305231E+09 | 0.137121E+09 |
Annual Sum or Average | 0.154673E+10 | 0.684350E+09 | 0.862384E+09 | 0.317658E+10 | 0.651585E+09 |
Minimum of Months | 65907601.50 | 977090.27 | 64782906.39 | 0.198731E+09 | 1284860.55 |
Maximum of Months | 0.210083E+09 | 0.138860E+09 | 82291697.41 | 0.369483E+09 | 0.137121E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.181296E+09 | 0.110160E+09 | 71136080.39 | 0.278212E+09 | 0.132245E+09 |
February | 0.155704E+09 | 86482410.97 | 69221597.04 | 0.257258E+09 | 97924395.76 |
March | 0.147395E+09 | 65103030.68 | 82291697.41 | 0.281241E+09 | 67158158.98 |
April | 0.100191E+09 | 28276943.91 | 71913896.18 | 0.251906E+09 | 24028108.27 |
May | 74452123.42 | 5511480.70 | 68940642.72 | 0.234851E+09 | 5232344.85 |
June | 65907601.50 | 1124695.11 | 64782906.39 | 0.220988E+09 | 4148994.57 |
July | 71039507.28 | 977090.27 | 70062417.01 | 0.208736E+09 | 1284860.55 |
August | 75357876.56 | 4024678.80 | 71333197.76 | 0.198731E+09 | 4478080.48 |
September | 97764495.24 | 25374984.65 | 72389510.59 | 0.222960E+09 | 14601338.93 |
October | 0.173800E+09 | 97049275.04 | 76750855.36 | 0.346984E+09 | 60611555.58 |
November | 0.210083E+09 | 0.138860E+09 | 71222517.68 | 0.369483E+09 | 0.102751E+09 |
December | 0.193743E+09 | 0.121405E+09 | 72338408.04 | 0.305231E+09 | 0.137121E+09 |
Annual Sum or Average | 0.154673E+10 | 0.684350E+09 | 0.862384E+09 | 0.317658E+10 | 0.651585E+09 |
Minimum of Months | 65907601.50 | 977090.27 | 64782906.39 | 0.198731E+09 | 1284860.55 |
Maximum of Months | 0.210083E+09 | 0.138860E+09 | 82291697.41 | 0.369483E+09 | 0.137121E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.216755E+09 | 0.131706E+09 | 85049216.71 | 0.332910E+09 | 0.156707E+09 |
February | 0.186157E+09 | 0.103397E+09 | 82760289.51 | 0.307705E+09 | 0.116061E+09 |
March | 0.176223E+09 | 77836194.16 | 98386702.88 | 0.335665E+09 | 79806896.08 |
April | 0.119787E+09 | 33807484.43 | 85979161.45 | 0.299569E+09 | 28593538.71 |
May | 89013827.36 | 6589442.57 | 82424384.79 | 0.278020E+09 | 6343313.38 |
June | 78798126.80 | 1344668.38 | 77453458.41 | 0.261626E+09 | 4921013.08 |
July | 84933755.36 | 1168194.27 | 83765561.09 | 0.247378E+09 | 1578493.58 |
August | 90096732.05 | 4811844.81 | 85284887.24 | 0.236025E+09 | 5366438.64 |
September | 0.116886E+09 | 30337946.04 | 86547798.80 | 0.265327E+09 | 17378474.98 |
October | 0.207793E+09 | 0.116031E+09 | 91762156.34 | 0.413593E+09 | 72000052.90 |
November | 0.251172E+09 | 0.166019E+09 | 85152559.82 | 0.441107E+09 | 0.121942E+09 |
December | 0.231637E+09 | 0.145150E+09 | 86486701.37 | 0.364927E+09 | 0.162548E+09 |
Annual Sum or Average | 0.184925E+10 | 0.818199E+09 | 0.103105E+10 | 0.378385E+10 | 0.773246E+09 |
Minimum of Months | 78798126.80 | 1168194.27 | 77453458.41 | 0.236025E+09 | 1578493.58 |
Maximum of Months | 0.251172E+09 | 0.166019E+09 | 98386702.88 | 0.441107E+09 | 0.162548E+09 |
Report: WindowZoneSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 654.24 | 354.92 | 433.50 | 263.40 | 170.09 | 0.00 | 0.00 |
February | 674.26 | 284.67 | 412.19 | 228.94 | 183.25 | 0.00 | 0.00 |
March | 670.95 | 170.79 | 352.43 | 155.67 | 196.77 | 0.00 | 0.00 |
April | 632.79 | 57.86 | 247.55 | 69.87 | 177.68 | 0.00 | 0.00 |
May | 584.99 | 9.47 | 178.02 | 13.18 | 164.84 | 0.00 | 0.00 |
June | 570.42 | 7.25 | 162.84 | 2.78 | 160.07 | 0.00 | 0.00 |
July | 531.81 | 2.12 | 169.86 | 2.34 | 167.53 | 0.00 | 0.00 |
August | 496.85 | 6.68 | 180.19 | 9.62 | 170.56 | 0.00 | 0.00 |
September | 563.89 | 26.91 | 241.56 | 62.70 | 178.86 | 0.00 | 0.00 |
October | 835.09 | 136.98 | 415.57 | 232.05 | 183.52 | 0.00 | 0.00 |
November | 911.14 | 262.23 | 519.07 | 343.10 | 175.98 | 0.00 | 0.00 |
December | 720.85 | 355.80 | 463.26 | 290.29 | 172.97 | 0.00 | 0.00 |
Annual Sum or Average | 653.60 | 139.01 | 314.11 | 138.98 | 175.13 | 0.00 | 0.00 |
Minimum of Months | 496.85 | 2.12 | 162.84 | 2.34 | 160.07 | 0.00 | 0.00 |
Maximum of Months | 911.14 | 355.80 | 519.07 | 343.10 | 196.77 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 322.81 | 187.59 | 216.75 | 131.70 | 85.05 | 0.00 | 0.00 |
February | 334.05 | 148.32 | 206.10 | 114.47 | 91.62 | 0.00 | 0.00 |
March | 334.60 | 87.67 | 176.22 | 77.83 | 98.38 | 0.00 | 0.00 |
April | 318.34 | 29.53 | 123.78 | 34.93 | 88.84 | 0.00 | 0.00 |
May | 296.60 | 4.66 | 89.01 | 6.59 | 82.42 | 0.00 | 0.00 |
June | 290.28 | 3.62 | 81.42 | 1.39 | 80.03 | 0.00 | 0.00 |
July | 270.83 | 0.98 | 84.93 | 1.17 | 83.76 | 0.00 | 0.00 |
August | 252.64 | 3.05 | 90.09 | 4.81 | 85.28 | 0.00 | 0.00 |
September | 284.78 | 12.74 | 120.78 | 31.35 | 89.43 | 0.00 | 0.00 |
October | 418.68 | 68.41 | 207.79 | 116.03 | 91.76 | 0.00 | 0.00 |
November | 454.66 | 132.91 | 259.54 | 171.55 | 87.99 | 0.00 | 0.00 |
December | 356.96 | 184.99 | 231.63 | 145.15 | 86.48 | 0.00 | 0.00 |
Annual Sum or Average | 327.79 | 71.71 | 157.05 | 69.49 | 87.57 | 0.00 | 0.00 |
Minimum of Months | 252.64 | 0.98 | 81.42 | 1.17 | 80.03 | 0.00 | 0.00 |
Maximum of Months | 454.66 | 187.59 | 259.54 | 171.55 | 98.38 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 323.81 | 182.24 | 216.30 | 131.43 | 84.87 | 0.00 | 0.00 |
February | 334.07 | 147.75 | 205.67 | 114.24 | 91.44 | 0.00 | 0.00 |
March | 333.27 | 91.45 | 175.86 | 77.67 | 98.18 | 0.00 | 0.00 |
April | 311.96 | 33.66 | 123.52 | 34.86 | 88.66 | 0.00 | 0.00 |
May | 284.62 | 6.50 | 88.83 | 6.58 | 82.25 | 0.00 | 0.00 |
June | 277.65 | 5.17 | 81.26 | 1.39 | 79.87 | 0.00 | 0.00 |
July | 257.23 | 1.58 | 84.76 | 1.17 | 83.59 | 0.00 | 0.00 |
August | 243.29 | 5.09 | 89.91 | 4.80 | 85.11 | 0.00 | 0.00 |
September | 278.81 | 17.59 | 120.53 | 31.28 | 89.25 | 0.00 | 0.00 |
October | 416.22 | 75.00 | 207.36 | 115.79 | 91.57 | 0.00 | 0.00 |
November | 453.88 | 135.83 | 259.00 | 171.20 | 87.81 | 0.00 | 0.00 |
December | 357.40 | 182.56 | 231.15 | 144.85 | 86.31 | 0.00 | 0.00 |
Annual Sum or Average | 322.50 | 73.37 | 156.73 | 69.35 | 87.39 | 0.00 | 0.00 |
Minimum of Months | 243.29 | 1.58 | 81.26 | 1.17 | 79.87 | 0.00 | 0.00 |
Maximum of Months | 453.88 | 182.56 | 259.00 | 171.20 | 98.18 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 324.88 | 179.10 | 216.30 | 131.43 | 84.87 | 0.00 | 0.00 |
February | 334.61 | 146.23 | 205.67 | 114.24 | 91.44 | 0.00 | 0.00 |
March | 333.36 | 91.21 | 175.86 | 77.67 | 98.18 | 0.00 | 0.00 |
April | 311.64 | 34.18 | 123.52 | 34.86 | 88.66 | 0.00 | 0.00 |
May | 283.51 | 6.99 | 88.83 | 6.58 | 82.25 | 0.00 | 0.00 |
June | 276.33 | 5.48 | 81.26 | 1.39 | 79.87 | 0.00 | 0.00 |
July | 255.73 | 1.74 | 84.76 | 1.17 | 83.59 | 0.00 | 0.00 |
August | 242.43 | 5.44 | 89.91 | 4.80 | 85.11 | 0.00 | 0.00 |
September | 278.52 | 18.36 | 120.53 | 31.28 | 89.25 | 0.00 | 0.00 |
October | 416.11 | 75.52 | 207.36 | 115.79 | 91.57 | 0.00 | 0.00 |
November | 454.06 | 135.33 | 259.00 | 171.20 | 87.81 | 0.00 | 0.00 |
December | 358.14 | 180.62 | 231.15 | 144.85 | 86.31 | 0.00 | 0.00 |
Annual Sum or Average | 322.26 | 73.03 | 156.73 | 69.35 | 87.39 | 0.00 | 0.00 |
Minimum of Months | 242.43 | 1.74 | 81.26 | 1.17 | 79.87 | 0.00 | 0.00 |
Maximum of Months | 454.06 | 180.62 | 259.00 | 171.20 | 98.18 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 326.31 | 175.83 | 216.30 | 131.43 | 84.87 | 0.00 | 0.00 |
February | 335.52 | 144.17 | 205.67 | 114.24 | 91.44 | 0.00 | 0.00 |
March | 333.90 | 89.90 | 175.86 | 77.67 | 98.18 | 0.00 | 0.00 |
April | 312.17 | 33.35 | 123.52 | 34.86 | 88.66 | 0.00 | 0.00 |
May | 284.28 | 6.65 | 88.83 | 6.58 | 82.25 | 0.00 | 0.00 |
June | 277.27 | 5.27 | 81.26 | 1.39 | 79.87 | 0.00 | 0.00 |
July | 256.52 | 1.58 | 84.76 | 1.17 | 83.59 | 0.00 | 0.00 |
August | 243.12 | 5.07 | 89.91 | 4.80 | 85.11 | 0.00 | 0.00 |
September | 278.88 | 17.57 | 120.53 | 31.28 | 89.25 | 0.00 | 0.00 |
October | 416.39 | 74.60 | 207.36 | 115.79 | 91.57 | 0.00 | 0.00 |
November | 454.54 | 134.10 | 259.00 | 171.20 | 87.81 | 0.00 | 0.00 |
December | 359.23 | 178.35 | 231.15 | 144.85 | 86.31 | 0.00 | 0.00 |
Annual Sum or Average | 322.99 | 71.88 | 156.73 | 69.35 | 87.39 | 0.00 | 0.00 |
Minimum of Months | 243.12 | 1.58 | 81.26 | 1.17 | 79.87 | 0.00 | 0.00 |
Maximum of Months | 454.54 | 178.35 | 259.00 | 171.20 | 98.18 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 658.73 | 338.06 | 432.61 | 262.86 | 169.74 | 0.00 | 0.00 |
February | 675.29 | 278.78 | 411.35 | 228.47 | 182.87 | 0.00 | 0.00 |
March | 669.89 | 172.42 | 351.71 | 155.35 | 196.36 | 0.00 | 0.00 |
April | 625.95 | 61.74 | 247.04 | 69.72 | 177.32 | 0.00 | 0.00 |
May | 570.34 | 11.45 | 177.66 | 13.15 | 164.51 | 0.00 | 0.00 |
June | 557.81 | 9.49 | 162.51 | 2.77 | 159.74 | 0.00 | 0.00 |
July | 514.15 | 2.34 | 169.51 | 2.33 | 167.18 | 0.00 | 0.00 |
August | 487.61 | 8.07 | 179.82 | 9.60 | 170.21 | 0.00 | 0.00 |
September | 557.79 | 30.66 | 241.06 | 62.57 | 178.49 | 0.00 | 0.00 |
October | 832.49 | 143.42 | 414.72 | 231.58 | 183.14 | 0.00 | 0.00 |
November | 910.54 | 262.06 | 518.01 | 342.39 | 175.62 | 0.00 | 0.00 |
December | 723.11 | 346.53 | 462.31 | 289.70 | 172.61 | 0.00 | 0.00 |
Annual Sum or Average | 648.27 | 138.12 | 313.47 | 138.69 | 174.77 | 0.00 | 0.00 |
Minimum of Months | 487.61 | 2.34 | 162.51 | 2.33 | 159.74 | 0.00 | 0.00 |
Maximum of Months | 910.54 | 346.53 | 518.01 | 342.39 | 196.36 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 329.18 | 168.47 | 216.30 | 131.43 | 84.87 | 0.00 | 0.00 |
February | 337.32 | 138.94 | 205.67 | 114.24 | 91.44 | 0.00 | 0.00 |
March | 335.00 | 85.42 | 175.86 | 77.67 | 98.18 | 0.00 | 0.00 |
April | 314.14 | 30.05 | 123.52 | 34.86 | 88.66 | 0.00 | 0.00 |
May | 287.75 | 5.28 | 88.83 | 6.58 | 82.25 | 0.00 | 0.00 |
June | 281.82 | 4.49 | 81.26 | 1.39 | 79.87 | 0.00 | 0.00 |
July | 259.79 | 1.00 | 84.76 | 1.17 | 83.59 | 0.00 | 0.00 |
August | 245.81 | 3.59 | 89.91 | 4.80 | 85.11 | 0.00 | 0.00 |
September | 279.97 | 14.31 | 120.53 | 31.28 | 89.25 | 0.00 | 0.00 |
October | 416.60 | 70.63 | 207.36 | 115.79 | 91.57 | 0.00 | 0.00 |
November | 455.10 | 130.36 | 259.00 | 171.20 | 87.81 | 0.00 | 0.00 |
December | 361.34 | 172.86 | 231.15 | 144.85 | 86.31 | 0.00 | 0.00 |
Annual Sum or Average | 325.14 | 68.47 | 156.73 | 69.35 | 87.39 | 0.00 | 0.00 |
Minimum of Months | 245.81 | 1.00 | 81.26 | 1.17 | 79.87 | 0.00 | 0.00 |
Maximum of Months | 455.10 | 172.86 | 259.00 | 171.20 | 98.18 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 329.66 | 167.50 | 216.30 | 131.43 | 84.87 | 0.00 | 0.00 |
February | 337.72 | 138.22 | 205.67 | 114.24 | 91.44 | 0.00 | 0.00 |
March | 335.24 | 85.01 | 175.86 | 77.67 | 98.18 | 0.00 | 0.00 |
April | 314.34 | 29.85 | 123.52 | 34.86 | 88.66 | 0.00 | 0.00 |
May | 287.98 | 5.22 | 88.83 | 6.58 | 82.25 | 0.00 | 0.00 |
June | 282.07 | 4.44 | 81.26 | 1.39 | 79.87 | 0.00 | 0.00 |
July | 260.01 | 0.98 | 84.76 | 1.17 | 83.59 | 0.00 | 0.00 |
August | 246.00 | 3.53 | 89.91 | 4.80 | 85.11 | 0.00 | 0.00 |
September | 280.10 | 14.18 | 120.53 | 31.28 | 89.25 | 0.00 | 0.00 |
October | 416.72 | 70.42 | 207.36 | 115.79 | 91.57 | 0.00 | 0.00 |
November | 455.31 | 129.99 | 259.00 | 171.20 | 87.81 | 0.00 | 0.00 |
December | 361.78 | 172.08 | 231.15 | 144.85 | 86.31 | 0.00 | 0.00 |
Annual Sum or Average | 325.40 | 68.14 | 156.73 | 69.35 | 87.39 | 0.00 | 0.00 |
Minimum of Months | 246.00 | 0.98 | 81.26 | 1.17 | 79.87 | 0.00 | 0.00 |
Maximum of Months | 455.31 | 172.08 | 259.00 | 171.20 | 98.18 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 330.74 | 165.00 | 216.30 | 131.43 | 84.87 | 0.00 | 0.00 |
February | 338.68 | 136.14 | 205.67 | 114.24 | 91.44 | 0.00 | 0.00 |
March | 335.71 | 83.95 | 175.86 | 77.67 | 98.18 | 0.00 | 0.00 |
April | 314.13 | 29.73 | 123.52 | 34.86 | 88.66 | 0.00 | 0.00 |
May | 287.14 | 5.36 | 88.83 | 6.58 | 82.25 | 0.00 | 0.00 |
June | 280.99 | 4.53 | 81.26 | 1.39 | 79.87 | 0.00 | 0.00 |
July | 258.66 | 1.04 | 84.76 | 1.17 | 83.59 | 0.00 | 0.00 |
August | 244.96 | 3.73 | 89.91 | 4.80 | 85.11 | 0.00 | 0.00 |
September | 279.58 | 14.62 | 120.53 | 31.28 | 89.25 | 0.00 | 0.00 |
October | 416.55 | 70.54 | 207.36 | 115.79 | 91.57 | 0.00 | 0.00 |
November | 455.69 | 129.16 | 259.00 | 171.20 | 87.81 | 0.00 | 0.00 |
December | 362.84 | 169.96 | 231.15 | 144.85 | 86.31 | 0.00 | 0.00 |
Annual Sum or Average | 325.29 | 67.51 | 156.73 | 69.35 | 87.39 | 0.00 | 0.00 |
Minimum of Months | 244.96 | 1.04 | 81.26 | 1.17 | 79.87 | 0.00 | 0.00 |
Maximum of Months | 455.69 | 169.96 | 259.00 | 171.20 | 98.18 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 332.04 | 157.26 | 216.30 | 131.43 | 84.87 | 0.00 | 0.00 |
February | 339.87 | 128.93 | 205.67 | 114.24 | 91.44 | 0.00 | 0.00 |
March | 335.33 | 79.94 | 175.86 | 77.67 | 98.18 | 0.00 | 0.00 |
April | 309.95 | 29.57 | 123.52 | 34.86 | 88.66 | 0.00 | 0.00 |
May | 279.17 | 6.27 | 88.83 | 6.58 | 82.25 | 0.00 | 0.00 |
June | 271.45 | 5.10 | 81.26 | 1.39 | 79.87 | 0.00 | 0.00 |
July | 248.23 | 1.55 | 84.76 | 1.17 | 83.59 | 0.00 | 0.00 |
August | 236.52 | 5.35 | 89.91 | 4.80 | 85.11 | 0.00 | 0.00 |
September | 274.40 | 17.97 | 120.53 | 31.28 | 89.25 | 0.00 | 0.00 |
October | 413.52 | 72.14 | 207.36 | 115.79 | 91.57 | 0.00 | 0.00 |
November | 455.27 | 126.33 | 259.00 | 171.20 | 87.81 | 0.00 | 0.00 |
December | 364.17 | 163.08 | 231.15 | 144.85 | 86.31 | 0.00 | 0.00 |
Annual Sum or Average | 321.44 | 65.84 | 156.73 | 69.35 | 87.39 | 0.00 | 0.00 |
Minimum of Months | 236.52 | 1.55 | 81.26 | 1.17 | 79.87 | 0.00 | 0.00 |
Maximum of Months | 455.27 | 163.08 | 259.00 | 171.20 | 98.18 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.175231E+10 | 0.950620E+09 | 0.116108E+10 | 0.705501E+09 | 0.455577E+09 | 0.00 | 0.00 |
February | 0.163116E+10 | 0.688667E+09 | 0.997176E+09 | 0.553860E+09 | 0.443316E+09 | 0.00 | 0.00 |
March | 0.179708E+10 | 0.457431E+09 | 0.943961E+09 | 0.416940E+09 | 0.527021E+09 | 0.00 | 0.00 |
April | 0.164018E+10 | 0.149962E+09 | 0.641653E+09 | 0.181094E+09 | 0.460559E+09 | 0.00 | 0.00 |
May | 0.156682E+10 | 25371229.48 | 0.476814E+09 | 35297219.41 | 0.441517E+09 | 0.00 | 0.00 |
June | 0.147852E+10 | 18779753.06 | 0.422093E+09 | 7202893.78 | 0.414890E+09 | 0.00 | 0.00 |
July | 0.142441E+10 | 5678433.64 | 0.454959E+09 | 6257586.91 | 0.448701E+09 | 0.00 | 0.00 |
August | 0.133075E+10 | 17900548.88 | 0.482615E+09 | 25775282.24 | 0.456840E+09 | 0.00 | 0.00 |
September | 0.146161E+10 | 69745239.55 | 0.626114E+09 | 0.162509E+09 | 0.463605E+09 | 0.00 | 0.00 |
October | 0.223669E+10 | 0.366886E+09 | 0.111307E+10 | 0.621533E+09 | 0.491536E+09 | 0.00 | 0.00 |
November | 0.236168E+10 | 0.679689E+09 | 0.134543E+10 | 0.889304E+09 | 0.456131E+09 | 0.00 | 0.00 |
December | 0.193072E+10 | 0.952986E+09 | 0.124079E+10 | 0.777515E+09 | 0.463277E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.206119E+11 | 0.438372E+10 | 0.990576E+10 | 0.438279E+10 | 0.552297E+10 | 0.00 | 0.00 |
Minimum of Months | 0.133075E+10 | 5678433.64 | 0.422093E+09 | 6257586.91 | 0.414890E+09 | 0.00 | 0.00 |
Maximum of Months | 0.236168E+10 | 0.952986E+09 | 0.134543E+10 | 0.889304E+09 | 0.527021E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.864625E+09 | 0.502432E+09 | 0.580539E+09 | 0.352751E+09 | 0.227789E+09 | 0.00 | 0.00 |
February | 0.808130E+09 | 0.358821E+09 | 0.498588E+09 | 0.276930E+09 | 0.221658E+09 | 0.00 | 0.00 |
March | 0.896197E+09 | 0.234816E+09 | 0.471981E+09 | 0.208470E+09 | 0.263511E+09 | 0.00 | 0.00 |
April | 0.825143E+09 | 76551498.80 | 0.320826E+09 | 90547127.65 | 0.230279E+09 | 0.00 | 0.00 |
May | 0.794426E+09 | 12490124.17 | 0.238407E+09 | 17648609.70 | 0.220759E+09 | 0.00 | 0.00 |
June | 0.752417E+09 | 9390378.20 | 0.211046E+09 | 3601446.89 | 0.207445E+09 | 0.00 | 0.00 |
July | 0.725385E+09 | 2613453.78 | 0.227479E+09 | 3128793.45 | 0.224351E+09 | 0.00 | 0.00 |
August | 0.676665E+09 | 8170433.02 | 0.241308E+09 | 12887641.12 | 0.228420E+09 | 0.00 | 0.00 |
September | 0.738148E+09 | 33010074.00 | 0.313057E+09 | 81254607.36 | 0.231802E+09 | 0.00 | 0.00 |
October | 0.112139E+10 | 0.183220E+09 | 0.556535E+09 | 0.310767E+09 | 0.245768E+09 | 0.00 | 0.00 |
November | 0.117847E+10 | 0.344494E+09 | 0.672717E+09 | 0.444652E+09 | 0.228065E+09 | 0.00 | 0.00 |
December | 0.956072E+09 | 0.495464E+09 | 0.620396E+09 | 0.388757E+09 | 0.231639E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.103371E+11 | 0.226147E+10 | 0.495288E+10 | 0.219139E+10 | 0.276149E+10 | 0.00 | 0.00 |
Minimum of Months | 0.676665E+09 | 2613453.78 | 0.211046E+09 | 3128793.45 | 0.207445E+09 | 0.00 | 0.00 |
Maximum of Months | 0.117847E+10 | 0.502432E+09 | 0.672717E+09 | 0.444652E+09 | 0.263511E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.867303E+09 | 0.488103E+09 | 0.579348E+09 | 0.352027E+09 | 0.227321E+09 | 0.00 | 0.00 |
February | 0.808171E+09 | 0.357427E+09 | 0.497565E+09 | 0.276362E+09 | 0.221203E+09 | 0.00 | 0.00 |
March | 0.892619E+09 | 0.244928E+09 | 0.471012E+09 | 0.208042E+09 | 0.262970E+09 | 0.00 | 0.00 |
April | 0.808604E+09 | 87241182.44 | 0.320168E+09 | 90361372.24 | 0.229807E+09 | 0.00 | 0.00 |
May | 0.762326E+09 | 17418678.38 | 0.237918E+09 | 17612403.98 | 0.220306E+09 | 0.00 | 0.00 |
June | 0.719679E+09 | 13408715.87 | 0.210613E+09 | 3594058.60 | 0.207019E+09 | 0.00 | 0.00 |
July | 0.688960E+09 | 4236260.87 | 0.227013E+09 | 3122374.80 | 0.223890E+09 | 0.00 | 0.00 |
August | 0.651622E+09 | 13642990.79 | 0.240812E+09 | 12861202.41 | 0.227951E+09 | 0.00 | 0.00 |
September | 0.722677E+09 | 45596961.21 | 0.312415E+09 | 81087915.35 | 0.231327E+09 | 0.00 | 0.00 |
October | 0.111480E+10 | 0.200870E+09 | 0.555393E+09 | 0.310129E+09 | 0.245264E+09 | 0.00 | 0.00 |
November | 0.117647E+10 | 0.352075E+09 | 0.671337E+09 | 0.443740E+09 | 0.227598E+09 | 0.00 | 0.00 |
December | 0.957257E+09 | 0.488968E+09 | 0.619123E+09 | 0.387960E+09 | 0.231164E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.101705E+11 | 0.231391E+10 | 0.494272E+10 | 0.218690E+10 | 0.275582E+10 | 0.00 | 0.00 |
Minimum of Months | 0.651622E+09 | 4236260.87 | 0.210613E+09 | 3122374.80 | 0.207019E+09 | 0.00 | 0.00 |
Maximum of Months | 0.117647E+10 | 0.488968E+09 | 0.671337E+09 | 0.443740E+09 | 0.262970E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.870171E+09 | 0.479707E+09 | 0.579348E+09 | 0.352027E+09 | 0.227321E+09 | 0.00 | 0.00 |
February | 0.809482E+09 | 0.353767E+09 | 0.497565E+09 | 0.276362E+09 | 0.221203E+09 | 0.00 | 0.00 |
March | 0.892879E+09 | 0.244300E+09 | 0.471012E+09 | 0.208042E+09 | 0.262970E+09 | 0.00 | 0.00 |
April | 0.807766E+09 | 88600602.78 | 0.320168E+09 | 90361372.24 | 0.229807E+09 | 0.00 | 0.00 |
May | 0.759366E+09 | 18730636.17 | 0.237918E+09 | 17612403.98 | 0.220306E+09 | 0.00 | 0.00 |
June | 0.716236E+09 | 14205362.55 | 0.210613E+09 | 3594058.60 | 0.207019E+09 | 0.00 | 0.00 |
July | 0.684954E+09 | 4647062.14 | 0.227013E+09 | 3122374.80 | 0.223890E+09 | 0.00 | 0.00 |
August | 0.649312E+09 | 14560222.40 | 0.240812E+09 | 12861202.41 | 0.227951E+09 | 0.00 | 0.00 |
September | 0.721918E+09 | 47600252.81 | 0.312415E+09 | 81087915.35 | 0.231327E+09 | 0.00 | 0.00 |
October | 0.111450E+10 | 0.202281E+09 | 0.555393E+09 | 0.310129E+09 | 0.245264E+09 | 0.00 | 0.00 |
November | 0.117693E+10 | 0.350775E+09 | 0.671337E+09 | 0.443740E+09 | 0.227598E+09 | 0.00 | 0.00 |
December | 0.959235E+09 | 0.483763E+09 | 0.619123E+09 | 0.387960E+09 | 0.231164E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.101627E+11 | 0.230294E+10 | 0.494272E+10 | 0.218690E+10 | 0.275582E+10 | 0.00 | 0.00 |
Minimum of Months | 0.649312E+09 | 4647062.14 | 0.210613E+09 | 3122374.80 | 0.207019E+09 | 0.00 | 0.00 |
Maximum of Months | 0.117693E+10 | 0.483763E+09 | 0.671337E+09 | 0.443740E+09 | 0.262970E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.873978E+09 | 0.470939E+09 | 0.579348E+09 | 0.352027E+09 | 0.227321E+09 | 0.00 | 0.00 |
February | 0.811701E+09 | 0.348765E+09 | 0.497565E+09 | 0.276362E+09 | 0.221203E+09 | 0.00 | 0.00 |
March | 0.894306E+09 | 0.240800E+09 | 0.471012E+09 | 0.208042E+09 | 0.262970E+09 | 0.00 | 0.00 |
April | 0.809155E+09 | 86440606.33 | 0.320168E+09 | 90361372.24 | 0.229807E+09 | 0.00 | 0.00 |
May | 0.761403E+09 | 17808206.48 | 0.237918E+09 | 17612403.98 | 0.220306E+09 | 0.00 | 0.00 |
June | 0.718695E+09 | 13671996.80 | 0.210613E+09 | 3594058.60 | 0.207019E+09 | 0.00 | 0.00 |
July | 0.687073E+09 | 4220519.42 | 0.227013E+09 | 3122374.80 | 0.223890E+09 | 0.00 | 0.00 |
August | 0.651181E+09 | 13580294.37 | 0.240812E+09 | 12861202.41 | 0.227951E+09 | 0.00 | 0.00 |
September | 0.722862E+09 | 45531641.42 | 0.312415E+09 | 81087915.35 | 0.231327E+09 | 0.00 | 0.00 |
October | 0.111526E+10 | 0.199796E+09 | 0.555393E+09 | 0.310129E+09 | 0.245264E+09 | 0.00 | 0.00 |
November | 0.117818E+10 | 0.347593E+09 | 0.671337E+09 | 0.443740E+09 | 0.227598E+09 | 0.00 | 0.00 |
December | 0.962164E+09 | 0.477699E+09 | 0.619123E+09 | 0.387960E+09 | 0.231164E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.101860E+11 | 0.226685E+10 | 0.494272E+10 | 0.218690E+10 | 0.275582E+10 | 0.00 | 0.00 |
Minimum of Months | 0.651181E+09 | 4220519.42 | 0.210613E+09 | 3122374.80 | 0.207019E+09 | 0.00 | 0.00 |
Maximum of Months | 0.117818E+10 | 0.477699E+09 | 0.671337E+09 | 0.443740E+09 | 0.262970E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.176435E+10 | 0.905452E+09 | 0.115870E+10 | 0.704054E+09 | 0.454643E+09 | 0.00 | 0.00 |
February | 0.163366E+10 | 0.674417E+09 | 0.995131E+09 | 0.552724E+09 | 0.442407E+09 | 0.00 | 0.00 |
March | 0.179424E+10 | 0.461804E+09 | 0.942025E+09 | 0.416085E+09 | 0.525940E+09 | 0.00 | 0.00 |
April | 0.162247E+10 | 0.160032E+09 | 0.640337E+09 | 0.180723E+09 | 0.459614E+09 | 0.00 | 0.00 |
May | 0.152761E+10 | 30657389.84 | 0.475836E+09 | 35224807.95 | 0.440611E+09 | 0.00 | 0.00 |
June | 0.144584E+10 | 24608746.29 | 0.421227E+09 | 7188117.20 | 0.414039E+09 | 0.00 | 0.00 |
July | 0.137710E+10 | 6267886.73 | 0.454026E+09 | 6244749.61 | 0.447781E+09 | 0.00 | 0.00 |
August | 0.130601E+10 | 21605752.85 | 0.481625E+09 | 25722404.83 | 0.455903E+09 | 0.00 | 0.00 |
September | 0.144580E+10 | 79461628.73 | 0.624829E+09 | 0.162176E+09 | 0.462654E+09 | 0.00 | 0.00 |
October | 0.222975E+10 | 0.384135E+09 | 0.111079E+10 | 0.620258E+09 | 0.490528E+09 | 0.00 | 0.00 |
November | 0.236012E+10 | 0.679248E+09 | 0.134267E+10 | 0.887480E+09 | 0.455195E+09 | 0.00 | 0.00 |
December | 0.193677E+10 | 0.928151E+09 | 0.123825E+10 | 0.775920E+09 | 0.462327E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.204437E+11 | 0.435584E+10 | 0.988544E+10 | 0.437380E+10 | 0.551164E+10 | 0.00 | 0.00 |
Minimum of Months | 0.130601E+10 | 6267886.73 | 0.421227E+09 | 6244749.61 | 0.414039E+09 | 0.00 | 0.00 |
Maximum of Months | 0.236012E+10 | 0.928151E+09 | 0.134267E+10 | 0.887480E+09 | 0.525940E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.881669E+09 | 0.451233E+09 | 0.579348E+09 | 0.352027E+09 | 0.227321E+09 | 0.00 | 0.00 |
February | 0.816056E+09 | 0.336134E+09 | 0.497565E+09 | 0.276362E+09 | 0.221203E+09 | 0.00 | 0.00 |
March | 0.897267E+09 | 0.228799E+09 | 0.471012E+09 | 0.208042E+09 | 0.262970E+09 | 0.00 | 0.00 |
April | 0.814251E+09 | 77881659.56 | 0.320168E+09 | 90361372.24 | 0.229807E+09 | 0.00 | 0.00 |
May | 0.770719E+09 | 14132322.37 | 0.237918E+09 | 17612403.98 | 0.220306E+09 | 0.00 | 0.00 |
June | 0.730471E+09 | 11628193.93 | 0.210613E+09 | 3594058.60 | 0.207019E+09 | 0.00 | 0.00 |
July | 0.695830E+09 | 2679040.30 | 0.227013E+09 | 3122374.80 | 0.223890E+09 | 0.00 | 0.00 |
August | 0.658383E+09 | 9608820.96 | 0.240812E+09 | 12861202.41 | 0.227951E+09 | 0.00 | 0.00 |
September | 0.725670E+09 | 37102828.33 | 0.312415E+09 | 81087915.35 | 0.231327E+09 | 0.00 | 0.00 |
October | 0.111583E+10 | 0.189179E+09 | 0.555393E+09 | 0.310129E+09 | 0.245264E+09 | 0.00 | 0.00 |
November | 0.117963E+10 | 0.337889E+09 | 0.671337E+09 | 0.443740E+09 | 0.227598E+09 | 0.00 | 0.00 |
December | 0.967809E+09 | 0.462979E+09 | 0.619123E+09 | 0.387960E+09 | 0.231164E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.102536E+11 | 0.215925E+10 | 0.494272E+10 | 0.218690E+10 | 0.275582E+10 | 0.00 | 0.00 |
Minimum of Months | 0.658383E+09 | 2679040.30 | 0.210613E+09 | 3122374.80 | 0.207019E+09 | 0.00 | 0.00 |
Maximum of Months | 0.117963E+10 | 0.462979E+09 | 0.671337E+09 | 0.443740E+09 | 0.262970E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.882971E+09 | 0.448637E+09 | 0.579348E+09 | 0.352027E+09 | 0.227321E+09 | 0.00 | 0.00 |
February | 0.817002E+09 | 0.334384E+09 | 0.497565E+09 | 0.276362E+09 | 0.221203E+09 | 0.00 | 0.00 |
March | 0.897916E+09 | 0.227696E+09 | 0.471012E+09 | 0.208042E+09 | 0.262970E+09 | 0.00 | 0.00 |
April | 0.814769E+09 | 77371216.73 | 0.320168E+09 | 90361372.24 | 0.229807E+09 | 0.00 | 0.00 |
May | 0.771320E+09 | 13972232.01 | 0.237918E+09 | 17612403.98 | 0.220306E+09 | 0.00 | 0.00 |
June | 0.731137E+09 | 11518502.39 | 0.210613E+09 | 3594058.60 | 0.207019E+09 | 0.00 | 0.00 |
July | 0.696403E+09 | 2630717.68 | 0.227013E+09 | 3122374.80 | 0.223890E+09 | 0.00 | 0.00 |
August | 0.658880E+09 | 9465278.99 | 0.240812E+09 | 12861202.41 | 0.227951E+09 | 0.00 | 0.00 |
September | 0.726020E+09 | 36758376.14 | 0.312415E+09 | 81087915.35 | 0.231327E+09 | 0.00 | 0.00 |
October | 0.111613E+10 | 0.188606E+09 | 0.555393E+09 | 0.310129E+09 | 0.245264E+09 | 0.00 | 0.00 |
November | 0.118015E+10 | 0.336945E+09 | 0.671337E+09 | 0.443740E+09 | 0.227598E+09 | 0.00 | 0.00 |
December | 0.968990E+09 | 0.460897E+09 | 0.619123E+09 | 0.387960E+09 | 0.231164E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.102617E+11 | 0.214888E+10 | 0.494272E+10 | 0.218690E+10 | 0.275582E+10 | 0.00 | 0.00 |
Minimum of Months | 0.658880E+09 | 2630717.68 | 0.210613E+09 | 3122374.80 | 0.207019E+09 | 0.00 | 0.00 |
Maximum of Months | 0.118015E+10 | 0.460897E+09 | 0.671337E+09 | 0.443740E+09 | 0.262970E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.885856E+09 | 0.441939E+09 | 0.579348E+09 | 0.352027E+09 | 0.227321E+09 | 0.00 | 0.00 |
February | 0.819345E+09 | 0.329350E+09 | 0.497565E+09 | 0.276362E+09 | 0.221203E+09 | 0.00 | 0.00 |
March | 0.899162E+09 | 0.224855E+09 | 0.471012E+09 | 0.208042E+09 | 0.262970E+09 | 0.00 | 0.00 |
April | 0.814235E+09 | 77049041.14 | 0.320168E+09 | 90361372.24 | 0.229807E+09 | 0.00 | 0.00 |
May | 0.769081E+09 | 14347151.08 | 0.237918E+09 | 17612403.98 | 0.220306E+09 | 0.00 | 0.00 |
June | 0.728337E+09 | 11742645.65 | 0.210613E+09 | 3594058.60 | 0.207019E+09 | 0.00 | 0.00 |
July | 0.692796E+09 | 2775882.22 | 0.227013E+09 | 3122374.80 | 0.223890E+09 | 0.00 | 0.00 |
August | 0.656104E+09 | 9987079.55 | 0.240812E+09 | 12861202.41 | 0.227951E+09 | 0.00 | 0.00 |
September | 0.724673E+09 | 37896444.30 | 0.312415E+09 | 81087915.35 | 0.231327E+09 | 0.00 | 0.00 |
October | 0.111568E+10 | 0.188921E+09 | 0.555393E+09 | 0.310129E+09 | 0.245264E+09 | 0.00 | 0.00 |
November | 0.118116E+10 | 0.334791E+09 | 0.671337E+09 | 0.443740E+09 | 0.227598E+09 | 0.00 | 0.00 |
December | 0.971830E+09 | 0.455218E+09 | 0.619123E+09 | 0.387960E+09 | 0.231164E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.102583E+11 | 0.212887E+10 | 0.494272E+10 | 0.218690E+10 | 0.275582E+10 | 0.00 | 0.00 |
Minimum of Months | 0.656104E+09 | 2775882.22 | 0.210613E+09 | 3122374.80 | 0.207019E+09 | 0.00 | 0.00 |
Maximum of Months | 0.118116E+10 | 0.455218E+09 | 0.671337E+09 | 0.443740E+09 | 0.262970E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.889333E+09 | 0.421196E+09 | 0.579348E+09 | 0.352027E+09 | 0.227321E+09 | 0.00 | 0.00 |
February | 0.822220E+09 | 0.311909E+09 | 0.497565E+09 | 0.276362E+09 | 0.221203E+09 | 0.00 | 0.00 |
March | 0.898146E+09 | 0.214123E+09 | 0.471012E+09 | 0.208042E+09 | 0.262970E+09 | 0.00 | 0.00 |
April | 0.803381E+09 | 76649707.28 | 0.320168E+09 | 90361372.24 | 0.229807E+09 | 0.00 | 0.00 |
May | 0.747720E+09 | 16806073.95 | 0.237918E+09 | 17612403.98 | 0.220306E+09 | 0.00 | 0.00 |
June | 0.703600E+09 | 13218063.53 | 0.210613E+09 | 3594058.60 | 0.207019E+09 | 0.00 | 0.00 |
July | 0.664849E+09 | 4147088.93 | 0.227013E+09 | 3122374.80 | 0.223890E+09 | 0.00 | 0.00 |
August | 0.633487E+09 | 14322002.73 | 0.240812E+09 | 12861202.41 | 0.227951E+09 | 0.00 | 0.00 |
September | 0.711247E+09 | 46581024.61 | 0.312415E+09 | 81087915.35 | 0.231327E+09 | 0.00 | 0.00 |
October | 0.110756E+10 | 0.193223E+09 | 0.555393E+09 | 0.310129E+09 | 0.245264E+09 | 0.00 | 0.00 |
November | 0.118007E+10 | 0.327444E+09 | 0.671337E+09 | 0.443740E+09 | 0.227598E+09 | 0.00 | 0.00 |
December | 0.975390E+09 | 0.436790E+09 | 0.619123E+09 | 0.387960E+09 | 0.231164E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.101370E+11 | 0.207641E+10 | 0.494272E+10 | 0.218690E+10 | 0.275582E+10 | 0.00 | 0.00 |
Minimum of Months | 0.633487E+09 | 4147088.93 | 0.210613E+09 | 3122374.80 | 0.207019E+09 | 0.00 | 0.00 |
Maximum of Months | 0.118007E+10 | 0.436790E+09 | 0.671337E+09 | 0.443740E+09 | 0.262970E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 13.39 | 10.38 | 7.87 | 1.20 | 0.38 | 63.33 | 149.51 | 0.00 |
February | 16.97 | 12.78 | 9.69 | 1.81 | 4.63 | 75.94 | 163.32 | 0.01 |
March | 22.37 | 15.60 | 11.23 | 1.86 | 10.07 | 92.70 | 193.23 | 0.00 |
April | 29.13 | 18.33 | 11.93 | 1.64 | 16.17 | 89.20 | 259.84 | 0.01 |
May | 32.98 | 21.97 | 16.72 | 2.17 | 21.14 | 97.31 | 248.85 | 0.02 |
June | 33.59 | 24.39 | 20.62 | 1.55 | 23.45 | 107.22 | 203.36 | 0.06 |
July | 31.67 | 26.29 | 24.51 | 2.27 | 24.88 | 132.35 | 83.14 | 0.02 |
August | 30.03 | 26.31 | 25.11 | 1.75 | 23.81 | 127.44 | 60.46 | 0.00 |
September | 28.75 | 24.70 | 23.21 | 1.33 | 20.22 | 105.62 | 105.60 | 0.08 |
October | 25.09 | 18.74 | 15.36 | 0.77 | 12.83 | 75.09 | 190.08 | 0.00 |
November | 19.63 | 14.46 | 10.99 | 0.66 | 5.78 | 58.54 | 201.10 | 0.00 |
December | 14.52 | 10.88 | 7.89 | 0.97 | 0.94 | 60.91 | 153.60 | 0.01 |
Annual Sum or Average | 24.88 | 18.77 | 15.46 | 1.50 | 13.74 | 90.59 | 167.44 | 0.02 |
Minimum of Months | 13.39 | 10.38 | 7.87 | 0.66 | 0.38 | 58.54 | 60.46 | 0.00 |
Maximum of Months | 33.59 | 26.31 | 25.11 | 2.27 | 24.88 | 132.35 | 259.84 | 0.08 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 23.60 | 12-JAN-14:00 | 14.20 | 7.40 | 3.80 | 8.15 | 163.00 | 476.00 |
February | 27.10 | 22-FEB-14:00 | 16.20 | 9.10 | 1.50 | 15.39 | 225.00 | 451.00 |
March | 35.60 | 28-MAR-14:00 | 18.50 | 7.70 | 0.00 | 19.52 | 182.00 | 699.00 |
April | 40.30 | 15-APR-14:00 | 20.67 | 10.00 | 6.70 | 28.43 | 201.00 | 649.50 |
May | 44.50 | 03-MAY-14:00 | 20.64 | 5.30 | 2.80 | 28.91 | 150.00 | 809.00 |
June | 44.60 | 07-JUN-15:00 | 21.53 | 9.10 | 3.10 | 28.43 | 167.00 | 640.50 |
July | 40.40 | 02-JUL-15:00 | 26.36 | 21.60 | 2.10 | 29.87 | 200.00 | 545.50 |
August | 37.30 | 07-AUG-14:00 | 26.58 | 22.90 | 3.00 | 29.87 | 311.00 | 370.00 |
September | 37.50 | 17-SEP-19:00 | 27.68 | 24.60 | 0.20 | 28.59 | 0.00 | 0.00 |
October | 36.40 | 02-OCT-14:20 | 21.05 | 13.00 | 1.80 | 21.61 | 187.33 | 678.83 |
November | 30.30 | 04-NOV-13:00 | 17.17 | 8.90 | 1.10 | 14.84 | 155.00 | 710.00 |
December | 24.60 | 28-DEC-13:00 | 15.30 | 8.90 | 2.80 | 10.88 | 181.50 | 535.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 23.60 | 14.20 | 5.30 | 0.00 | 8.15 | 0.00 | 0.00 | |
Maximum of Months | 44.60 | 27.68 | 24.60 | 6.70 | 29.87 | 311.00 | 809.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 4.80 | 05-JAN-06:00 | 4.73 | 4.60 | 0.00 | -10.2 | 0.00 | 0.00 |
February | 6.90 | 02-FEB-05:00 | 6.67 | 6.50 | 0.00 | -7.8 | 0.00 | 0.00 |
March | 13.30 | 01-MAR-03:00 | 10.56 | 8.30 | 0.80 | -1.4 | 0.00 | 0.00 |
April | 17.40 | 11-APR-04:00 | 13.58 | 10.90 | 0.00 | 3.06 | 0.00 | 0.00 |
May | 22.70 | 13-MAY-04:00 | 20.32 | 19.30 | 2.10 | 20.40 | 0.00 | 0.00 |
June | 23.30 | 18-JUN-04:00 | 21.80 | 21.20 | 2.70 | 17.75 | 0.00 | 0.00 |
July | 23.20 | 19-JUL-02:00 | 23.20 | 23.20 | 2.30 | 15.39 | 0.00 | 0.00 |
August | 23.40 | 15-AUG-23:00 | 22.91 | 22.80 | 2.40 | 21.78 | 0.00 | 0.00 |
September | 23.00 | 27-SEP-04:00 | 20.74 | 19.70 | 0.00 | 10.30 | 0.00 | 0.00 |
October | 15.50 | 31-OCT-04:00 | 14.07 | 13.20 | 0.00 | 1.80 | 0.00 | 0.00 |
November | 9.50 | 27-NOV-05:00 | 8.75 | 8.10 | 0.00 | -5.0 | 0.00 | 0.00 |
December | 5.00 | 21-DEC-04:00 | 4.08 | 3.00 | 0.00 | -10.5 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 4.80 | 4.08 | 3.00 | 0.00 | -10.5 | 0.00 | 0.00 | |
Maximum of Months | 23.40 | 23.20 | 23.20 | 2.70 | 21.78 | 0.00 | 0.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 15.62 | 17-JAN-14:00 | 18.20 | 14.10 | 1.00 | 11.07 | 198.00 | 56.50 |
February | 18.14 | 25-FEB-16:00 | 21.20 | 16.60 | 5.90 | 10.88 | 107.50 | 156.50 |
March | 21.38 | 10-MAR-18:49 | 29.25 | 17.73 | 2.10 | 21.44 | 0.00 | 0.00 |
April | 23.42 | 18-APR-13:00 | 37.10 | 17.80 | 5.70 | 23.49 | 233.50 | 671.50 |
May | 27.40 | 22-MAY-22:00 | 29.40 | 26.80 | 0.00 | 20.40 | 0.00 | 0.00 |
June | 28.92 | 28-JUN-12:00 | 34.40 | 27.50 | 1.00 | 25.49 | 332.50 | 501.50 |
July | 29.18 | 01-JUL-16:00 | 37.20 | 26.80 | 2.30 | 25.66 | 196.00 | 196.00 |
August | 29.17 | 27-AUG-15:00 | 35.10 | 27.40 | 1.30 | 29.55 | 256.00 | 129.00 |
September | 28.10 | 14-SEP-16:00 | 33.70 | 26.40 | 1.40 | 26.48 | 122.50 | 108.50 |
October | 23.06 | 06-OCT-10:00 | 28.60 | 20.80 | 1.30 | 20.22 | 327.00 | 348.50 |
November | 18.93 | 08-NOV-17:10 | 27.55 | 14.47 | 0.17 | 16.67 | 28.00 | 65.33 |
December | 15.64 | 29-DEC-19:00 | 16.80 | 14.90 | 4.80 | 13.54 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 15.62 | 16.80 | 14.10 | 0.00 | 10.88 | 0.00 | 0.00 | |
Maximum of Months | 29.18 | 37.20 | 27.50 | 5.90 | 29.55 | 332.50 | 671.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 14.10 | 17-JAN-13:00 | 17.80 | 15.48 | 0.90 | 9.72 | 260.50 | 81.50 |
February | 16.60 | 25-FEB-16:00 | 21.20 | 18.14 | 5.90 | 10.88 | 107.50 | 156.50 |
March | 18.30 | 10-MAR-19:00 | 27.70 | 21.26 | 2.10 | 21.44 | 0.00 | 0.00 |
April | 19.30 | 26-APR-23:10 | 28.53 | 22.04 | 0.00 | 15.61 | 0.00 | 0.00 |
May | 26.80 | 22-MAY-22:00 | 29.40 | 27.40 | 0.00 | 20.40 | 0.00 | 0.00 |
June | 27.50 | 28-JUN-12:00 | 34.40 | 28.92 | 1.00 | 25.49 | 332.50 | 501.50 |
July | 27.30 | 18-JUL-06:19 | 29.10 | 27.70 | 1.17 | 26.48 | 20.00 | 0.00 |
August | 28.80 | 12-AUG-07:00 | 29.10 | 28.83 | 2.90 | 26.81 | 113.00 | 6.50 |
September | 26.50 | 12-SEP-14:00 | 30.50 | 27.38 | 0.90 | 25.99 | 260.00 | 20.00 |
October | 21.10 | 06-OCT-08:00 | 25.50 | 22.41 | 0.30 | 17.21 | 239.00 | 159.00 |
November | 16.30 | 08-NOV-21:19 | 20.10 | 17.59 | 0.00 | 10.95 | 0.00 | 0.00 |
December | 14.90 | 29-DEC-20:10 | 16.72 | 15.59 | 4.73 | 13.13 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 14.10 | 16.72 | 15.48 | 0.00 | 9.72 | 0.00 | 0.00 | |
Maximum of Months | 28.80 | 34.40 | 28.92 | 5.90 | 26.81 | 332.50 | 501.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 20.92 | 27.26 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 21.74 | 33.91 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 24.21 | 44.04 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 27.79 | 55.91 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 31.48 | 58.43 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 34.27 | 54.82 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 35.42 | 39.75 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 34.60 | 34.68 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 32.04 | 35.55 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 28.44 | 39.44 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 24.77 | 33.85 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 22.02 | 26.79 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 28.18 | 40.37 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 20.92 | 26.79 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 35.42 | 58.43 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK1
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.304518E+09 | -186908699.2 | 0.00 | 0.00 | 744.00 | 0.00 | -117609273.0 | 59.00 | 0.00 | 0.00 |
February | 0.270170E+09 | -166091978.2 | 0.00 | 0.00 | 672.00 | 0.00 | -104078154.8 | 58.99 | 0.00 | 0.00 |
March | 0.287672E+09 | -174469337.0 | 0.00 | 0.00 | 744.00 | 0.00 | -113202509.4 | 58.99 | 0.00 | 0.00 |
April | 0.257829E+09 | -149532399.3 | 0.00 | 0.00 | 720.00 | 0.00 | -108297035.3 | 58.98 | 0.00 | 0.00 |
May | 0.247627E+09 | -136563879.8 | 0.00 | 0.00 | 744.00 | 0.00 | -111063455.9 | 58.99 | 0.00 | 0.00 |
June | 0.227045E+09 | -119845397.8 | 0.00 | 0.00 | 720.00 | 0.00 | -107199611.4 | 58.99 | 0.00 | 0.00 |
July | 0.226271E+09 | -115667915.1 | 0.00 | 0.00 | 744.00 | 0.00 | -110603578.1 | 58.99 | 0.00 | 0.00 |
August | 0.233082E+09 | -122282905.5 | 0.00 | 0.00 | 744.00 | 0.00 | -110799407.4 | 58.99 | 0.00 | 0.00 |
September | 0.236934E+09 | -129353348.8 | 0.00 | 0.00 | 720.00 | 0.00 | -107581001.9 | 58.99 | 0.00 | 0.00 |
October | 0.262059E+09 | -150070647.2 | 0.00 | 0.00 | 744.00 | 0.00 | -111988628.8 | 58.99 | 0.00 | 0.00 |
November | 0.271830E+09 | -162154743.1 | 0.00 | 0.00 | 720.00 | 0.00 | -109675378.3 | 58.99 | 0.00 | 0.00 |
December | 0.297719E+09 | -181761421.8 | 0.00 | 0.00 | 744.00 | 0.00 | -115957629.5 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.312276E+10 | -0.179470E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.132806E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.226271E+09 | -186908699.2 | 0.00 | 0.00 | 672.00 | 0.00 | -117609273.0 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.304518E+09 | -115667915.1 | 0.00 | 0.00 | 744.00 | 0.00 | -104078154.8 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK2
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.302582E+09 | -186922405.6 | 0.00 | 0.00 | 744.00 | 0.00 | -115659151.2 | 58.99 | 0.00 | 0.00 |
February | 0.269188E+09 | -166087595.9 | 0.00 | 0.00 | 672.00 | 0.00 | -103100132.2 | 58.99 | 0.00 | 0.00 |
March | 0.287245E+09 | -174466766.4 | 0.00 | 0.00 | 744.00 | 0.00 | -112778651.0 | 58.99 | 0.00 | 0.00 |
April | 0.257709E+09 | -149508684.2 | 0.00 | 0.00 | 720.00 | 0.00 | -108200780.2 | 58.99 | 0.00 | 0.00 |
May | 0.247642E+09 | -136568720.4 | 0.00 | 0.00 | 744.00 | 0.00 | -111073506.8 | 58.99 | 0.00 | 0.00 |
June | 0.227153E+09 | -119852128.6 | 0.00 | 0.00 | 720.00 | 0.00 | -107300523.8 | 58.99 | 0.00 | 0.00 |
July | 0.226405E+09 | -115658278.1 | 0.00 | 0.00 | 744.00 | 0.00 | -110746736.7 | 58.99 | 0.00 | 0.00 |
August | 0.233190E+09 | -122267283.5 | 0.00 | 0.00 | 744.00 | 0.00 | -110923015.7 | 58.99 | 0.00 | 0.00 |
September | 0.237005E+09 | -129347991.3 | 0.00 | 0.00 | 720.00 | 0.00 | -107656653.8 | 58.99 | 0.00 | 0.00 |
October | 0.261970E+09 | -150053559.4 | 0.00 | 0.00 | 744.00 | 0.00 | -111916328.8 | 58.99 | 0.00 | 0.00 |
November | 0.271460E+09 | -162147486.7 | 0.00 | 0.00 | 720.00 | 0.00 | -109312892.2 | 58.99 | 0.00 | 0.00 |
December | 0.296320E+09 | -181753254.5 | 0.00 | 0.00 | 744.00 | 0.00 | -114566899.3 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.311787E+10 | -0.179463E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.132324E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.226405E+09 | -186922405.6 | 0.00 | 0.00 | 672.00 | 0.00 | -115659151.2 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.302582E+09 | -115658278.1 | 0.00 | 0.00 | 744.00 | 0.00 | -103100132.2 | 58.99 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK3
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.281176E+09 | -164375133.1 | 0.00 | 0.00 | 744.00 | 0.00 | -116801014.7 | 58.99 | 0.00 | 0.00 |
February | 0.249363E+09 | -146188323.9 | 0.00 | 0.00 | 672.00 | 0.00 | -103175019.7 | 58.99 | 0.00 | 0.00 |
March | 0.267389E+09 | -155707843.3 | 0.00 | 0.00 | 744.00 | 0.00 | -111681366.7 | 58.99 | 0.00 | 0.00 |
April | 0.237602E+09 | -131521163.7 | 0.00 | 0.00 | 720.00 | 0.00 | -106080581.4 | 58.99 | 0.00 | 0.00 |
May | 0.229577E+09 | -121153709.7 | 0.00 | 0.00 | 744.00 | 0.00 | -108423668.1 | 58.99 | 0.00 | 0.00 |
June | 0.211411E+09 | -106777410.8 | 0.00 | 0.00 | 720.00 | 0.00 | -104633997.5 | 58.98 | 0.00 | 0.00 |
July | 0.209111E+09 | -101135109.0 | 0.00 | 0.00 | 744.00 | 0.00 | -107975939.0 | 58.99 | 0.00 | 0.00 |
August | 0.217818E+09 | -109228666.8 | 0.00 | 0.00 | 744.00 | 0.00 | -108589803.5 | 58.99 | 0.00 | 0.00 |
September | 0.219207E+09 | -113741575.0 | 0.00 | 0.00 | 720.00 | 0.00 | -105465825.5 | 58.99 | 0.00 | 0.00 |
October | 0.242070E+09 | -132004203.3 | 0.00 | 0.00 | 744.00 | 0.00 | -110065860.8 | 58.99 | 0.00 | 0.00 |
November | 0.251811E+09 | -143181310.6 | 0.00 | 0.00 | 720.00 | 0.00 | -108630103.0 | 58.99 | 0.00 | 0.00 |
December | 0.273784E+09 | -158649019.6 | 0.00 | 0.00 | 744.00 | 0.00 | -115134579.2 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.289032E+10 | -0.158366E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.130666E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.209111E+09 | -164375133.1 | 0.00 | 0.00 | 672.00 | 0.00 | -116801014.7 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.281176E+09 | -101135109.0 | 0.00 | 0.00 | 744.00 | 0.00 | -103175019.7 | 58.99 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK4
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.281654E+09 | -164346555.7 | 0.00 | 0.00 | 744.00 | 0.00 | -117307656.3 | 59.00 | 0.00 | 0.00 |
February | 0.249570E+09 | -146196020.2 | 0.00 | 0.00 | 672.00 | 0.00 | -103373773.8 | 58.99 | 0.00 | 0.00 |
March | 0.267427E+09 | -155700154.8 | 0.00 | 0.00 | 744.00 | 0.00 | -111726742.0 | 58.99 | 0.00 | 0.00 |
April | 0.237504E+09 | -131508357.0 | 0.00 | 0.00 | 720.00 | 0.00 | -105995719.0 | 58.99 | 0.00 | 0.00 |
May | 0.229392E+09 | -121188077.7 | 0.00 | 0.00 | 744.00 | 0.00 | -108203596.9 | 58.98 | 0.00 | 0.00 |
June | 0.211211E+09 | -106742192.1 | 0.00 | 0.00 | 720.00 | 0.00 | -104468329.4 | 58.98 | 0.00 | 0.00 |
July | 0.208903E+09 | -101115328.9 | 0.00 | 0.00 | 744.00 | 0.00 | -107787680.6 | 58.99 | 0.00 | 0.00 |
August | 0.217669E+09 | -109232353.4 | 0.00 | 0.00 | 744.00 | 0.00 | -108436310.6 | 58.99 | 0.00 | 0.00 |
September | 0.219078E+09 | -113714382.4 | 0.00 | 0.00 | 720.00 | 0.00 | -105363541.4 | 59.00 | 0.00 | 0.00 |
October | 0.241998E+09 | -132003353.4 | 0.00 | 0.00 | 744.00 | 0.00 | -109994883.9 | 58.99 | 0.00 | 0.00 |
November | 0.251877E+09 | -143164004.9 | 0.00 | 0.00 | 720.00 | 0.00 | -108713257.8 | 58.99 | 0.00 | 0.00 |
December | 0.274087E+09 | -158644690.0 | 0.00 | 0.00 | 744.00 | 0.00 | -115442304.0 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.289037E+10 | -0.158356E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.130681E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.208903E+09 | -164346555.7 | 0.00 | 0.00 | 672.00 | 0.00 | -117307656.3 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.281654E+09 | -101115328.9 | 0.00 | 0.00 | 744.00 | 0.00 | -103373773.8 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK5
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.274352E+09 | -155357490.1 | 0.00 | 0.00 | 744.00 | 0.00 | -118994793.4 | 58.99 | 0.00 | 0.00 |
February | 0.242614E+09 | -138239031.2 | 0.00 | 0.00 | 672.00 | 0.00 | -104375340.1 | 58.99 | 0.00 | 0.00 |
March | 0.259934E+09 | -147295417.5 | 0.00 | 0.00 | 744.00 | 0.00 | -112638586.7 | 59.00 | 0.00 | 0.00 |
April | 0.231206E+09 | -124450928.5 | 0.00 | 0.00 | 720.00 | 0.00 | -106754821.5 | 58.99 | 0.00 | 0.00 |
May | 0.223498E+09 | -114612576.2 | 0.00 | 0.00 | 744.00 | 0.00 | -108885052.8 | 58.98 | 0.00 | 0.00 |
June | 0.206174E+09 | -101004439.8 | 0.00 | 0.00 | 720.00 | 0.00 | -105169288.3 | 58.98 | 0.00 | 0.00 |
July | 0.203882E+09 | -95628839.6 | 0.00 | 0.00 | 744.00 | 0.00 | -108253300.5 | 58.99 | 0.00 | 0.00 |
August | 0.212392E+09 | -103364601.5 | 0.00 | 0.00 | 744.00 | 0.00 | -109027602.9 | 58.98 | 0.00 | 0.00 |
September | 0.213543E+09 | -107621832.3 | 0.00 | 0.00 | 720.00 | 0.00 | -105921074.0 | 58.99 | 0.00 | 0.00 |
October | 0.235376E+09 | -124750222.6 | 0.00 | 0.00 | 744.00 | 0.00 | -110626138.2 | 58.99 | 0.00 | 0.00 |
November | 0.244564E+09 | -135245946.5 | 0.00 | 0.00 | 720.00 | 0.00 | -109318403.7 | 58.98 | 0.00 | 0.00 |
December | 0.266728E+09 | -150037952.4 | 0.00 | 0.00 | 744.00 | 0.00 | -116689732.3 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.281426E+10 | -0.149761E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.131665E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.203882E+09 | -155357490.1 | 0.00 | 0.00 | 672.00 | 0.00 | -118994793.4 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.274352E+09 | -95628839.6 | 0.00 | 0.00 | 744.00 | 0.00 | -104375340.1 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK6
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.274461E+09 | -155354055.5 | 0.00 | 0.00 | 744.00 | 0.00 | -119107376.0 | 58.99 | 0.00 | 0.00 |
February | 0.242661E+09 | -138244174.9 | 0.00 | 0.00 | 672.00 | 0.00 | -104416548.9 | 58.99 | 0.00 | 0.00 |
March | 0.260004E+09 | -147309750.4 | 0.00 | 0.00 | 744.00 | 0.00 | -112694267.3 | 58.99 | 0.00 | 0.00 |
April | 0.231340E+09 | -124457941.4 | 0.00 | 0.00 | 720.00 | 0.00 | -106881627.9 | 58.99 | 0.00 | 0.00 |
May | 0.223634E+09 | -114565044.7 | 0.00 | 0.00 | 744.00 | 0.00 | -109069104.7 | 58.99 | 0.00 | 0.00 |
June | 0.206344E+09 | -100955681.5 | 0.00 | 0.00 | 720.00 | 0.00 | -105388666.1 | 59.00 | 0.00 | 0.00 |
July | 0.204076E+09 | -95646762.7 | 0.00 | 0.00 | 744.00 | 0.00 | -108428915.4 | 58.99 | 0.00 | 0.00 |
August | 0.212550E+09 | -103333281.6 | 0.00 | 0.00 | 744.00 | 0.00 | -109217007.2 | 58.99 | 0.00 | 0.00 |
September | 0.213679E+09 | -107598587.0 | 0.00 | 0.00 | 720.00 | 0.00 | -106080562.1 | 59.00 | 0.00 | 0.00 |
October | 0.235498E+09 | -124755792.7 | 0.00 | 0.00 | 744.00 | 0.00 | -110741957.3 | 58.99 | 0.00 | 0.00 |
November | 0.244629E+09 | -135244921.6 | 0.00 | 0.00 | 720.00 | 0.00 | -109383789.9 | 58.98 | 0.00 | 0.00 |
December | 0.266788E+09 | -150033907.3 | 0.00 | 0.00 | 744.00 | 0.00 | -116753695.9 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.281566E+10 | -0.149750E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.131816E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.204076E+09 | -155354055.5 | 0.00 | 0.00 | 672.00 | 0.00 | -119107376.0 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.274461E+09 | -95646762.7 | 0.00 | 0.00 | 744.00 | 0.00 | -104416548.9 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK7
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.274623E+09 | -155349197.0 | 0.00 | 0.00 | 744.00 | 0.00 | -119273635.6 | 58.99 | 0.00 | 0.00 |
February | 0.242760E+09 | -138250233.2 | 0.00 | 0.00 | 672.00 | 0.00 | -104509310.0 | 58.99 | 0.00 | 0.00 |
March | 0.260066E+09 | -147334489.0 | 0.00 | 0.00 | 744.00 | 0.00 | -112731655.9 | 58.99 | 0.00 | 0.00 |
April | 0.231377E+09 | -124454433.7 | 0.00 | 0.00 | 720.00 | 0.00 | -106922464.5 | 58.99 | 0.00 | 0.00 |
May | 0.223673E+09 | -114580604.8 | 0.00 | 0.00 | 744.00 | 0.00 | -109092408.6 | 58.99 | 0.00 | 0.00 |
June | 0.206382E+09 | -101007683.4 | 0.00 | 0.00 | 720.00 | 0.00 | -105373857.2 | 58.98 | 0.00 | 0.00 |
July | 0.204080E+09 | -95630771.0 | 0.00 | 0.00 | 744.00 | 0.00 | -108449556.8 | 58.99 | 0.00 | 0.00 |
August | 0.212578E+09 | -103366621.3 | 0.00 | 0.00 | 744.00 | 0.00 | -109211294.3 | 58.98 | 0.00 | 0.00 |
September | 0.213720E+09 | -107649107.2 | 0.00 | 0.00 | 720.00 | 0.00 | -106070675.9 | 58.99 | 0.00 | 0.00 |
October | 0.235529E+09 | -124754777.8 | 0.00 | 0.00 | 744.00 | 0.00 | -110774050.0 | 58.99 | 0.00 | 0.00 |
November | 0.244681E+09 | -135176199.0 | 0.00 | 0.00 | 720.00 | 0.00 | -109504875.5 | 59.00 | 0.00 | 0.00 |
December | 0.266910E+09 | -150056199.6 | 0.00 | 0.00 | 744.00 | 0.00 | -116853809.8 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.281638E+10 | -0.149761E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.131877E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.204080E+09 | -155349197.0 | 0.00 | 0.00 | 672.00 | 0.00 | -119273635.6 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.274623E+09 | -95630771.0 | 0.00 | 0.00 | 744.00 | 0.00 | -104509310.0 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 319.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 303.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 364.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 379.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 406.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 386.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 379.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 372.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 344.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 347.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 317.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 315.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4237.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 303.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 406.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 HEATING COIL
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.667472E+09 | 69785.06 | 02-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 93958130.52 | 7445.50 | 02-FEB-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.128768E+09 | 20276.67 | 23-DEC-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.890199E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.667472E+09 | 69785.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 HEATING COIL
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.126335E+09 | 16547.92 | 02-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4076399.38 | 1221.20 | 02-FEB-08:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 15668735.99 | 3860.91 | 23-DEC-08:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.146081E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.126335E+09 | 16547.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3 HEATING COIL
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.294374E+09 | 29151.47 | 02-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 25875053.66 | 2050.19 | 02-FEB-07:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 38455531.92 | 3519.54 | 23-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.358705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.294374E+09 | 29151.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4 HEATING COIL
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.360536E+09 | 35694.90 | 01-JAN-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 36513839.77 | 2502.28 | 02-FEB-07:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 50530969.09 | 3424.27 | 23-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.447581E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.360536E+09 | 35694.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5 HEATING COIL
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.445176E+09 | 35498.41 | 01-JAN-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 54611647.34 | 2275.13 | 01-FEB-07:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 70370597.62 | 3861.68 | 31-DEC-08:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.570158E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.445176E+09 | 35498.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6 HEATING COIL
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.864330E+09 | 63661.27 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.115305E+09 | 7001.00 | 02-FEB-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.163039E+09 | 22234.66 | 23-DEC-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.114267E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.864330E+09 | 63661.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7 HEATING COIL
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.452569E+09 | 33467.33 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 57514401.54 | 3841.57 | 11-FEB-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 79282541.24 | 12219.68 | 23-DEC-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.589366E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.452569E+09 | 33467.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8 HEATING COIL
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.475736E+09 | 33367.46 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 64529372.69 | 5512.27 | 11-FEB-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 88372596.84 | 13645.19 | 23-DEC-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.628638E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.475736E+09 | 33367.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9 HEATING COIL
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.552985E+09 | 33523.31 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 87574416.85 | 11510.87 | 11-FEB-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.120398E+09 | 18479.08 | 23-DEC-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.760957E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.552985E+09 | 33523.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10 HEATING COIL
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.757576E+09 | 38583.76 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.173548E+09 | 31953.06 | 11-FEB-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1036745.56 | 775.64 | 27-NOV-08:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.224446E+09 | 35774.45 | 23-DEC-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.115661E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.757576E+09 | 38583.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.149964E+10 | 0.134040E+10 | 8445.94 | 12-JAN-15:00 | 7902.22 | 0.00 |
February | 0.00 | 0.00 | 0.672751E+10 | 0.585057E+10 | 15261.86 | 22-FEB-15:00 | 13962.70 | 0.00 |
March | 0.00 | 0.00 | 0.187160E+11 | 0.161094E+11 | 40690.61 | 11-MAR-08:62 | 30410.77 | 0.00 |
April | 0.00 | 0.00 | 0.318706E+11 | 0.285494E+11 | 67559.67 | 26-APR-07:02 | 50162.60 | 0.00 |
May | 0.00 | 0.00 | 0.467266E+11 | 0.373392E+11 | 71598.36 | 24-MAY-07:02 | 40286.54 | 0.00 |
June | 0.00 | 0.00 | 0.530472E+11 | 0.373851E+11 | 72998.13 | 26-JUN-07:01 | 37259.55 | 0.00 |
July | 0.00 | 0.00 | 0.597987E+11 | 0.348138E+11 | 73875.52 | 25-JUL-07:01 | 35627.47 | 0.00 |
August | 0.00 | 0.00 | 0.590493E+11 | 0.320791E+11 | 73457.52 | 10-AUG-07:01 | 38411.18 | 0.00 |
September | 0.00 | 0.00 | 0.484871E+11 | 0.284451E+11 | 72841.77 | 03-SEP-07:01 | 38815.88 | 0.00 |
October | 0.00 | 0.00 | 0.309623E+11 | 0.243221E+11 | 69047.45 | 11-OCT-07:02 | 47819.14 | 0.00 |
November | 0.00 | 0.00 | 0.153558E+11 | 0.131655E+11 | 20864.58 | 09-NOV-14:20 | 18409.14 | 0.00 |
December | 0.00 | 0.00 | 0.349695E+10 | 0.304307E+10 | 11132.72 | 28-DEC-15:00 | 9945.23 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.375738E+12 | 0.262443E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.149964E+10 | 0.134040E+10 | 8445.94 | 7902.22 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.597987E+11 | 0.373851E+11 | 73875.52 | 50162.60 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.167877E+10 | 0.145686E+10 | 4855.07 | 12-JAN-15:00 | 4557.40 | 0.00 |
February | 0.00 | 0.00 | 0.455797E+10 | 0.394659E+10 | 8133.00 | 22-FEB-15:00 | 7454.93 | 0.00 |
March | 0.00 | 0.00 | 0.101992E+11 | 0.886118E+10 | 22113.64 | 11-MAR-08:62 | 18387.55 | 0.00 |
April | 0.00 | 0.00 | 0.157284E+11 | 0.141845E+11 | 33586.36 | 26-APR-07:02 | 28307.77 | 0.00 |
May | 0.00 | 0.00 | 0.225293E+11 | 0.181995E+11 | 35444.34 | 24-MAY-07:02 | 23964.18 | 0.00 |
June | 0.00 | 0.00 | 0.252667E+11 | 0.180587E+11 | 35702.40 | 26-JUN-07:01 | 23294.47 | 0.00 |
July | 0.00 | 0.00 | 0.284323E+11 | 0.169150E+11 | 36190.38 | 25-JUL-07:01 | 22190.47 | 0.00 |
August | 0.00 | 0.00 | 0.281636E+11 | 0.156764E+11 | 36093.04 | 10-AUG-07:01 | 23099.52 | 0.00 |
September | 0.00 | 0.00 | 0.231860E+11 | 0.139774E+11 | 35844.71 | 03-SEP-07:01 | 23528.91 | 0.00 |
October | 0.00 | 0.00 | 0.155367E+11 | 0.124272E+11 | 34192.88 | 11-OCT-07:02 | 27613.26 | 0.00 |
November | 0.00 | 0.00 | 0.878594E+10 | 0.758678E+10 | 10909.54 | 09-NOV-13:50 | 9561.27 | 0.00 |
December | 0.00 | 0.00 | 0.313507E+10 | 0.267668E+10 | 6159.29 | 03-DEC-14:00 | 5841.28 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.187200E+12 | 0.133967E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.167877E+10 | 0.145686E+10 | 4855.07 | 4557.40 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.284323E+11 | 0.181995E+11 | 36190.38 | 28307.77 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3 COOLING COIL
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.740413E+09 | 0.672910E+09 | 4377.49 | 12-JAN-15:00 | 4120.15 | 0.00 |
February | 0.00 | 0.00 | 0.295431E+10 | 0.261544E+10 | 7746.66 | 22-FEB-14:00 | 7112.82 | 0.00 |
March | 0.00 | 0.00 | 0.777085E+10 | 0.680103E+10 | 27474.58 | 11-MAR-07:03 | 19166.63 | 0.00 |
April | 0.00 | 0.00 | 0.126638E+11 | 0.114280E+11 | 34984.20 | 17-APR-06:01 | 25842.85 | 0.00 |
May | 0.00 | 0.00 | 0.188153E+11 | 0.150976E+11 | 37389.74 | 23-MAY-06:02 | 18555.39 | 0.00 |
June | 0.00 | 0.00 | 0.212437E+11 | 0.149222E+11 | 38065.56 | 26-JUN-06:01 | 15492.51 | 0.00 |
July | 0.00 | 0.00 | 0.235966E+11 | 0.135489E+11 | 38098.84 | 23-JUL-07:01 | 15585.03 | 0.00 |
August | 0.00 | 0.00 | 0.238291E+11 | 0.127773E+11 | 38181.75 | 21-AUG-06:03 | 14136.93 | 0.00 |
September | 0.00 | 0.00 | 0.191703E+11 | 0.111773E+11 | 38191.21 | 10-SEP-07:03 | 14762.37 | 0.00 |
October | 0.00 | 0.00 | 0.123734E+11 | 0.984751E+10 | 36035.94 | 12-OCT-06:02 | 21313.01 | 0.00 |
November | 0.00 | 0.00 | 0.655124E+10 | 0.575036E+10 | 11442.42 | 09-NOV-07:03 | 7614.29 | 0.00 |
December | 0.00 | 0.00 | 0.171852E+10 | 0.152046E+10 | 5627.17 | 28-DEC-14:00 | 5105.67 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.151428E+12 | 0.106159E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.740413E+09 | 0.672910E+09 | 4377.49 | 4120.15 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.238291E+11 | 0.150976E+11 | 38191.21 | 25842.85 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4 COOLING COIL
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.661839E+09 | 0.600586E+09 | 4234.26 | 12-JAN-15:00 | 3984.33 | 0.00 |
February | 0.00 | 0.00 | 0.286279E+10 | 0.253487E+10 | 7666.49 | 22-FEB-14:00 | 7038.16 | 0.00 |
March | 0.00 | 0.00 | 0.774361E+10 | 0.677666E+10 | 27560.01 | 11-MAR-07:03 | 19227.53 | 0.00 |
April | 0.00 | 0.00 | 0.127180E+11 | 0.114776E+11 | 35074.35 | 17-APR-06:01 | 26047.07 | 0.00 |
May | 0.00 | 0.00 | 0.189408E+11 | 0.152080E+11 | 37461.69 | 23-MAY-06:02 | 18691.12 | 0.00 |
June | 0.00 | 0.00 | 0.213739E+11 | 0.150303E+11 | 38133.61 | 26-JUN-06:01 | 15647.45 | 0.00 |
July | 0.00 | 0.00 | 0.237418E+11 | 0.136601E+11 | 38166.95 | 23-JUL-07:01 | 15710.19 | 0.00 |
August | 0.00 | 0.00 | 0.239380E+11 | 0.128579E+11 | 38250.01 | 21-AUG-06:02 | 14361.59 | 0.00 |
September | 0.00 | 0.00 | 0.192562E+11 | 0.112417E+11 | 38259.49 | 10-SEP-07:02 | 14954.81 | 0.00 |
October | 0.00 | 0.00 | 0.124220E+11 | 0.988889E+10 | 36102.45 | 12-OCT-06:02 | 21384.13 | 0.00 |
November | 0.00 | 0.00 | 0.650179E+10 | 0.570631E+10 | 11152.59 | 09-NOV-07:03 | 7416.17 | 0.00 |
December | 0.00 | 0.00 | 0.160559E+10 | 0.142167E+10 | 5498.13 | 02-DEC-14:00 | 5498.13 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.151766E+12 | 0.106405E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.661839E+09 | 0.600586E+09 | 4234.26 | 3984.33 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.239380E+11 | 0.152080E+11 | 38259.49 | 26047.07 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5 COOLING COIL
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.534699E+09 | 0.483789E+09 | 3953.51 | 12-JAN-15:00 | 3716.21 | 0.00 |
February | 0.00 | 0.00 | 0.266047E+10 | 0.235678E+10 | 7466.76 | 22-FEB-14:00 | 6848.90 | 0.00 |
March | 0.00 | 0.00 | 0.750114E+10 | 0.656092E+10 | 24888.01 | 11-MAR-07:03 | 17205.57 | 0.00 |
April | 0.00 | 0.00 | 0.125228E+11 | 0.112962E+11 | 34889.94 | 17-APR-06:01 | 25830.22 | 0.00 |
May | 0.00 | 0.00 | 0.187575E+11 | 0.150489E+11 | 37268.56 | 23-MAY-06:02 | 18439.50 | 0.00 |
June | 0.00 | 0.00 | 0.211797E+11 | 0.148726E+11 | 37945.75 | 26-JUN-06:01 | 15453.34 | 0.00 |
July | 0.00 | 0.00 | 0.235503E+11 | 0.135181E+11 | 37978.92 | 23-JUL-07:01 | 15489.20 | 0.00 |
August | 0.00 | 0.00 | 0.237144E+11 | 0.126958E+11 | 38061.58 | 21-AUG-06:03 | 14063.95 | 0.00 |
September | 0.00 | 0.00 | 0.190390E+11 | 0.110815E+11 | 38071.01 | 10-SEP-07:02 | 14717.00 | 0.00 |
October | 0.00 | 0.00 | 0.122134E+11 | 0.971259E+10 | 35917.63 | 12-OCT-06:02 | 21108.86 | 0.00 |
November | 0.00 | 0.00 | 0.628494E+10 | 0.551273E+10 | 10598.07 | 09-NOV-13:40 | 9241.29 | 0.00 |
December | 0.00 | 0.00 | 0.139801E+10 | 0.123991E+10 | 5308.40 | 02-DEC-14:00 | 5308.40 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.149356E+12 | 0.104380E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.534699E+09 | 0.483789E+09 | 3953.51 | 3716.21 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.237144E+11 | 0.150489E+11 | 38071.01 | 25830.22 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6 COOLING COIL
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.752908E+09 | 0.665286E+09 | 7015.30 | 12-JAN-15:10 | 6411.48 | 0.00 |
February | 0.00 | 0.00 | 0.439434E+10 | 0.381861E+10 | 13794.26 | 22-FEB-14:00 | 12338.38 | 0.00 |
March | 0.00 | 0.00 | 0.133957E+11 | 0.115070E+11 | 39845.40 | 11-MAR-08:62 | 28206.82 | 0.00 |
April | 0.00 | 0.00 | 0.227610E+11 | 0.203892E+11 | 62969.65 | 17-APR-07:01 | 46153.28 | 0.00 |
May | 0.00 | 0.00 | 0.343783E+11 | 0.273326E+11 | 66090.55 | 21-MAY-08:61 | 38775.74 | 0.00 |
June | 0.00 | 0.00 | 0.388817E+11 | 0.270453E+11 | 68629.50 | 25-JUN-08:62 | 29003.63 | 0.00 |
July | 0.00 | 0.00 | 0.429338E+11 | 0.242493E+11 | 68615.59 | 23-JUL-08:61 | 27486.92 | 0.00 |
August | 0.00 | 0.00 | 0.434788E+11 | 0.228067E+11 | 68831.45 | 21-AUG-07:02 | 25465.58 | 0.00 |
September | 0.00 | 0.00 | 0.345514E+11 | 0.197672E+11 | 68862.67 | 04-SEP-08:61 | 27893.61 | 0.00 |
October | 0.00 | 0.00 | 0.221752E+11 | 0.173505E+11 | 64180.15 | 01-OCT-08:62 | 42249.67 | 0.00 |
November | 0.00 | 0.00 | 0.110221E+11 | 0.946864E+10 | 19737.84 | 09-NOV-13:40 | 16837.10 | 0.00 |
December | 0.00 | 0.00 | 0.205234E+10 | 0.178928E+10 | 9299.99 | 28-DEC-14:00 | 8183.69 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.270777E+12 | 0.186190E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.752908E+09 | 0.665286E+09 | 7015.30 | 6411.48 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.434788E+11 | 0.273326E+11 | 68862.67 | 46153.28 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7 COOLING COIL
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.347434E+09 | 0.307759E+09 | 3573.44 | 12-JAN-15:10 | 3286.27 | 0.00 |
February | 0.00 | 0.00 | 0.223100E+10 | 0.194998E+10 | 7145.55 | 22-FEB-14:00 | 6421.05 | 0.00 |
March | 0.00 | 0.00 | 0.692610E+10 | 0.597534E+10 | 18996.03 | 11-MAR-08:62 | 13459.30 | 0.00 |
April | 0.00 | 0.00 | 0.118174E+11 | 0.106109E+11 | 33040.23 | 17-APR-07:01 | 24265.63 | 0.00 |
May | 0.00 | 0.00 | 0.178749E+11 | 0.142429E+11 | 34661.03 | 21-MAY-08:61 | 20345.58 | 0.00 |
June | 0.00 | 0.00 | 0.201905E+11 | 0.140775E+11 | 35985.81 | 25-JUN-08:62 | 15116.04 | 0.00 |
July | 0.00 | 0.00 | 0.222966E+11 | 0.126300E+11 | 35978.51 | 23-JUL-08:61 | 14350.92 | 0.00 |
August | 0.00 | 0.00 | 0.225606E+11 | 0.118678E+11 | 36091.70 | 21-AUG-07:02 | 13217.63 | 0.00 |
September | 0.00 | 0.00 | 0.179353E+11 | 0.102911E+11 | 36108.07 | 04-SEP-08:61 | 14532.25 | 0.00 |
October | 0.00 | 0.00 | 0.115024E+11 | 0.903475E+10 | 33672.18 | 01-OCT-08:62 | 22163.42 | 0.00 |
November | 0.00 | 0.00 | 0.570315E+10 | 0.492290E+10 | 10285.41 | 06-NOV-14:00 | 8521.75 | 0.00 |
December | 0.00 | 0.00 | 0.101131E+10 | 0.887791E+09 | 4755.59 | 28-DEC-14:00 | 4206.95 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.140397E+12 | 0.967986E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.347434E+09 | 0.307759E+09 | 3573.44 | 3286.27 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.225606E+11 | 0.142429E+11 | 36108.07 | 24265.63 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8 COOLING COIL
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.325459E+09 | 0.287868E+09 | 3500.44 | 12-JAN-15:10 | 3217.77 | 0.00 |
February | 0.00 | 0.00 | 0.217742E+10 | 0.190334E+10 | 7078.12 | 22-FEB-15:10 | 6388.20 | 0.00 |
March | 0.00 | 0.00 | 0.685710E+10 | 0.591424E+10 | 18356.54 | 11-MAR-08:62 | 12972.34 | 0.00 |
April | 0.00 | 0.00 | 0.117655E+11 | 0.105629E+11 | 32951.43 | 17-APR-07:01 | 24199.49 | 0.00 |
May | 0.00 | 0.00 | 0.178262E+11 | 0.142018E+11 | 34567.74 | 21-MAY-08:61 | 20283.63 | 0.00 |
June | 0.00 | 0.00 | 0.201391E+11 | 0.140369E+11 | 35889.93 | 25-JUN-08:62 | 15048.11 | 0.00 |
July | 0.00 | 0.00 | 0.222487E+11 | 0.125952E+11 | 35882.66 | 23-JUL-08:03 | 14182.38 | 0.00 |
August | 0.00 | 0.00 | 0.225095E+11 | 0.118312E+11 | 35995.54 | 21-AUG-07:03 | 13091.37 | 0.00 |
September | 0.00 | 0.00 | 0.178861E+11 | 0.102551E+11 | 36011.86 | 04-SEP-08:61 | 14486.51 | 0.00 |
October | 0.00 | 0.00 | 0.114511E+11 | 0.899140E+10 | 33581.35 | 01-OCT-08:62 | 22099.60 | 0.00 |
November | 0.00 | 0.00 | 0.564401E+10 | 0.487067E+10 | 10232.55 | 06-NOV-14:00 | 8474.53 | 0.00 |
December | 0.00 | 0.00 | 0.970072E+09 | 0.851996E+09 | 4686.50 | 28-DEC-14:00 | 4143.93 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.139800E+12 | 0.963027E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.325459E+09 | 0.287868E+09 | 3500.44 | 3217.77 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.225095E+11 | 0.142018E+11 | 36011.86 | 24199.49 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9 COOLING COIL
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.282728E+09 | 0.249448E+09 | 3348.88 | 12-JAN-15:10 | 3077.61 | 0.00 |
February | 0.00 | 0.00 | 0.205776E+10 | 0.180068E+10 | 6961.40 | 22-FEB-15:10 | 6281.10 | 0.00 |
March | 0.00 | 0.00 | 0.672505E+10 | 0.580066E+10 | 16163.31 | 11-MAR-08:62 | 11327.94 | 0.00 |
April | 0.00 | 0.00 | 0.117703E+11 | 0.105689E+11 | 33084.24 | 17-APR-07:01 | 24283.40 | 0.00 |
May | 0.00 | 0.00 | 0.179289E+11 | 0.142947E+11 | 34708.36 | 21-MAY-08:61 | 20359.59 | 0.00 |
June | 0.00 | 0.00 | 0.202653E+11 | 0.141444E+11 | 36040.04 | 25-JUN-08:62 | 15047.16 | 0.00 |
July | 0.00 | 0.00 | 0.224087E+11 | 0.127185E+11 | 36032.73 | 23-JUL-08:61 | 14362.77 | 0.00 |
August | 0.00 | 0.00 | 0.226656E+11 | 0.119461E+11 | 36146.09 | 21-AUG-07:02 | 13236.09 | 0.00 |
September | 0.00 | 0.00 | 0.179884E+11 | 0.103342E+11 | 36162.48 | 04-SEP-08:61 | 14557.20 | 0.00 |
October | 0.00 | 0.00 | 0.114696E+11 | 0.901019E+10 | 33722.51 | 01-OCT-08:62 | 22205.98 | 0.00 |
November | 0.00 | 0.00 | 0.554240E+10 | 0.478367E+10 | 10204.22 | 09-NOV-13:50 | 8761.07 | 0.00 |
December | 0.00 | 0.00 | 0.884214E+09 | 0.777989E+09 | 4560.39 | 28-DEC-14:00 | 4030.95 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.139989E+12 | 0.964296E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.282728E+09 | 0.249448E+09 | 3348.88 | 3077.61 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.226656E+11 | 0.142947E+11 | 36162.48 | 24283.40 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10 COOLING COIL
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.329311E+09 | 0.295872E+09 | 3596.17 | 12-JAN-15:10 | 3357.44 | 0.00 |
February | 0.00 | 0.00 | 0.225167E+10 | 0.200121E+10 | 7693.03 | 22-FEB-14:00 | 7009.20 | 0.00 |
March | 0.00 | 0.00 | 0.735579E+10 | 0.643109E+10 | 13736.31 | 29-MAR-13:00 | 11413.14 | 0.00 |
April | 0.00 | 0.00 | 0.133310E+11 | 0.120846E+11 | 37312.16 | 17-APR-07:01 | 27512.74 | 0.00 |
May | 0.00 | 0.00 | 0.203375E+11 | 0.164872E+11 | 39405.12 | 24-MAY-07:02 | 20717.37 | 0.00 |
June | 0.00 | 0.00 | 0.227841E+11 | 0.163152E+11 | 40586.19 | 25-JUN-08:62 | 16761.11 | 0.00 |
July | 0.00 | 0.00 | 0.251451E+11 | 0.148072E+11 | 40577.96 | 23-JUL-08:03 | 15622.89 | 0.00 |
August | 0.00 | 0.00 | 0.254171E+11 | 0.139980E+11 | 40705.62 | 21-AUG-07:02 | 15372.90 | 0.00 |
September | 0.00 | 0.00 | 0.201846E+11 | 0.120564E+11 | 40724.08 | 04-SEP-08:61 | 16618.73 | 0.00 |
October | 0.00 | 0.00 | 0.130284E+11 | 0.104378E+11 | 38022.02 | 01-OCT-08:62 | 25657.43 | 0.00 |
November | 0.00 | 0.00 | 0.616048E+10 | 0.539794E+10 | 11372.69 | 09-NOV-13:30 | 9846.67 | 0.00 |
December | 0.00 | 0.00 | 0.100748E+10 | 0.901268E+09 | 4948.73 | 28-DEC-14:00 | 4443.25 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.157333E+12 | 0.111214E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.329311E+09 | 0.295872E+09 | 3596.17 | 3357.44 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.254171E+11 | 0.164872E+11 | 40724.08 | 27512.74 | 0.00 |
Report: FanReportMonthly
For: PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.219900E+10 | 0.37 | 3006.16 | 02-JAN-08:61 | 0.90 |
February | 0.197639E+10 | 0.37 | 1394.90 | 02-FEB-08:05 | 0.60 |
March | 0.219048E+10 | 0.37 | 1592.25 | 11-MAR-08:62 | 0.64 |
April | 0.212929E+10 | 0.37 | 3006.16 | 15-APR-07:02 | 0.89 |
May | 0.234327E+10 | 0.38 | 3006.16 | 01-MAY-07:01 | 0.89 |
June | 0.240571E+10 | 0.39 | 3006.16 | 01-JUN-07:02 | 0.89 |
July | 0.249627E+10 | 0.39 | 3006.16 | 01-JUL-07:01 | 0.89 |
August | 0.246885E+10 | 0.39 | 3006.16 | 01-AUG-07:01 | 0.88 |
September | 0.222427E+10 | 0.38 | 3006.16 | 01-SEP-07:01 | 0.88 |
October | 0.218663E+10 | 0.37 | 3006.16 | 01-OCT-07:02 | 0.89 |
November | 0.210816E+10 | 0.37 | 1202.46 | 03-NOV-22:30 | 0.54 |
December | 0.219374E+10 | 0.37 | 1726.54 | 23-DEC-08:62 | 0.68 |
Annual Sum or Average | 0.269221E+11 | 0.38 | |||
Minimum of Months | 0.197639E+10 | 0.37 | 1202.46 | 0.54 | |
Maximum of Months | 0.249627E+10 | 0.39 | 3006.16 | 0.90 |
Report: FanReportMonthly
For: PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.867228E+09 | 0.37 | 1044.04 | 02-JAN-08:61 | 0.74 |
February | 0.801376E+09 | 0.38 | 646.97 | 02-FEB-08:40 | 0.56 |
March | 0.923526E+09 | 0.38 | 910.42 | 11-MAR-08:62 | 0.69 |
April | 0.926158E+09 | 0.38 | 1538.32 | 15-APR-07:02 | 0.89 |
May | 0.106595E+10 | 0.39 | 1538.32 | 01-MAY-07:01 | 0.89 |
June | 0.111361E+10 | 0.40 | 1538.32 | 01-JUN-07:02 | 0.89 |
July | 0.116396E+10 | 0.40 | 1538.32 | 01-JUL-07:01 | 0.89 |
August | 0.114544E+10 | 0.40 | 1538.32 | 01-AUG-07:01 | 0.89 |
September | 0.100607E+10 | 0.38 | 1538.32 | 01-SEP-07:01 | 0.89 |
October | 0.945242E+09 | 0.38 | 1538.32 | 01-OCT-07:02 | 0.89 |
November | 0.877372E+09 | 0.38 | 615.33 | 06-NOV-10:10 | 0.54 |
December | 0.872409E+09 | 0.38 | 715.36 | 23-DEC-08:08 | 0.60 |
Annual Sum or Average | 0.117083E+11 | 0.38 | |||
Minimum of Months | 0.801376E+09 | 0.37 | 615.33 | 0.54 | |
Maximum of Months | 0.116396E+10 | 0.40 | 1538.32 | 0.89 |
Report: FanReportMonthly
For: PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.898052E+09 | 0.29 | 1370.51 | 02-JAN-07:02 | 0.85 |
February | 0.806927E+09 | 0.29 | 668.39 | 02-FEB-07:15 | 0.57 |
March | 0.908416E+09 | 0.30 | 1146.47 | 11-MAR-07:03 | 0.77 |
April | 0.871723E+09 | 0.29 | 1538.19 | 02-APR-07:02 | 0.89 |
May | 0.979775E+09 | 0.31 | 1538.19 | 01-MAY-06:01 | 0.90 |
June | 0.101319E+10 | 0.32 | 1538.19 | 01-JUN-06:01 | 0.89 |
July | 0.103325E+10 | 0.31 | 1538.19 | 01-JUL-06:01 | 0.89 |
August | 0.104272E+10 | 0.32 | 1538.19 | 01-AUG-06:01 | 0.88 |
September | 0.913854E+09 | 0.30 | 1538.19 | 01-SEP-06:01 | 0.88 |
October | 0.893545E+09 | 0.29 | 1538.19 | 01-OCT-07:02 | 0.89 |
November | 0.863846E+09 | 0.29 | 615.27 | 30-NOV-10:10 | 0.54 |
December | 0.886992E+09 | 0.29 | 706.46 | 23-DEC-07:10 | 0.59 |
Annual Sum or Average | 0.111123E+11 | 0.30 | |||
Minimum of Months | 0.806927E+09 | 0.29 | 615.27 | 0.54 | |
Maximum of Months | 0.104272E+10 | 0.32 | 1538.19 | 0.90 |
Report: FanReportMonthly
For: PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.901747E+09 | 0.30 | 1541.61 | 01-JAN-08:62 | 0.89 |
February | 0.808994E+09 | 0.29 | 681.48 | 02-FEB-07:15 | 0.58 |
March | 0.910448E+09 | 0.30 | 1150.82 | 11-MAR-07:03 | 0.77 |
April | 0.873820E+09 | 0.30 | 1541.61 | 02-APR-07:02 | 0.89 |
May | 0.983557E+09 | 0.31 | 1541.61 | 01-MAY-06:01 | 0.90 |
June | 0.101718E+10 | 0.32 | 1541.61 | 01-JUN-06:01 | 0.89 |
July | 0.103777E+10 | 0.31 | 1541.61 | 01-JUL-06:01 | 0.89 |
August | 0.104636E+10 | 0.32 | 1541.61 | 01-AUG-06:01 | 0.88 |
September | 0.916453E+09 | 0.30 | 1541.61 | 01-SEP-06:01 | 0.88 |
October | 0.895671E+09 | 0.29 | 1541.61 | 01-OCT-07:02 | 0.89 |
November | 0.865766E+09 | 0.29 | 616.64 | 06-NOV-18:40 | 0.54 |
December | 0.889274E+09 | 0.29 | 705.38 | 23-DEC-07:10 | 0.59 |
Annual Sum or Average | 0.111470E+11 | 0.30 | |||
Minimum of Months | 0.808994E+09 | 0.29 | 616.64 | 0.54 | |
Maximum of Months | 0.104636E+10 | 0.32 | 1541.61 | 0.90 |
Report: FanReportMonthly
For: PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.898471E+09 | 0.30 | 1532.17 | 01-JAN-08:62 | 0.89 |
February | 0.804516E+09 | 0.29 | 671.79 | 01-FEB-07:15 | 0.58 |
March | 0.904796E+09 | 0.30 | 1011.55 | 11-MAR-07:03 | 0.73 |
April | 0.867844E+09 | 0.29 | 1532.17 | 02-APR-07:02 | 0.89 |
May | 0.975878E+09 | 0.31 | 1532.17 | 01-MAY-06:01 | 0.90 |
June | 0.100907E+10 | 0.32 | 1532.17 | 01-JUN-06:01 | 0.89 |
July | 0.102966E+10 | 0.31 | 1532.17 | 01-JUL-06:01 | 0.89 |
August | 0.103742E+10 | 0.32 | 1532.17 | 01-AUG-06:01 | 0.88 |
September | 0.908861E+09 | 0.30 | 1532.17 | 01-SEP-06:01 | 0.88 |
October | 0.889933E+09 | 0.29 | 1532.17 | 01-OCT-07:02 | 0.89 |
November | 0.860466E+09 | 0.29 | 612.87 | 01-NOV-18:30 | 0.54 |
December | 0.884352E+09 | 0.29 | 712.87 | 31-DEC-08:10 | 0.60 |
Annual Sum or Average | 0.110713E+11 | 0.30 | |||
Minimum of Months | 0.804516E+09 | 0.29 | 612.87 | 0.54 | |
Maximum of Months | 0.103742E+10 | 0.32 | 1532.17 | 0.90 |
Report: FanReportMonthly
For: PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.147099E+10 | 0.27 | 2712.08 | 01-JAN-09:01 | 0.89 |
February | 0.131516E+10 | 0.27 | 1263.78 | 02-FEB-08:05 | 0.60 |
March | 0.148024E+10 | 0.28 | 1543.96 | 11-MAR-08:62 | 0.67 |
April | 0.142464E+10 | 0.27 | 2712.08 | 02-APR-08:62 | 0.89 |
May | 0.163799E+10 | 0.29 | 2712.08 | 01-MAY-07:01 | 0.90 |
June | 0.170669E+10 | 0.30 | 2712.08 | 01-JUN-07:02 | 0.89 |
July | 0.175222E+10 | 0.30 | 2712.08 | 01-JUL-07:01 | 0.89 |
August | 0.176086E+10 | 0.30 | 2712.08 | 01-AUG-07:01 | 0.88 |
September | 0.152045E+10 | 0.28 | 2712.08 | 01-SEP-07:01 | 0.88 |
October | 0.145633E+10 | 0.27 | 2712.08 | 01-OCT-08:62 | 0.89 |
November | 0.140594E+10 | 0.27 | 1084.83 | 09-NOV-20:05 | 0.54 |
December | 0.144526E+10 | 0.27 | 1653.17 | 23-DEC-08:62 | 0.70 |
Annual Sum or Average | 0.183768E+11 | 0.28 | |||
Minimum of Months | 0.131516E+10 | 0.27 | 1084.83 | 0.54 | |
Maximum of Months | 0.176086E+10 | 0.30 | 2712.08 | 0.90 |
Report: FanReportMonthly
For: PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.805062E+09 | 0.28 | 1484.39 | 01-JAN-09:01 | 0.93 |
February | 0.719736E+09 | 0.28 | 695.99 | 11-FEB-08:62 | 0.62 |
March | 0.810143E+09 | 0.29 | 742.21 | 11-MAR-08:62 | 0.64 |
April | 0.779761E+09 | 0.28 | 1484.39 | 02-APR-08:62 | 0.92 |
May | 0.897631E+09 | 0.30 | 1484.39 | 01-MAY-07:01 | 0.93 |
June | 0.934114E+09 | 0.31 | 1484.39 | 01-JUN-07:02 | 0.92 |
July | 0.957546E+09 | 0.31 | 1484.39 | 01-JUL-07:01 | 0.92 |
August | 0.961895E+09 | 0.31 | 1484.39 | 01-AUG-07:01 | 0.91 |
September | 0.831091E+09 | 0.29 | 1484.39 | 01-SEP-07:01 | 0.91 |
October | 0.796796E+09 | 0.28 | 1484.39 | 01-OCT-08:62 | 0.92 |
November | 0.769506E+09 | 0.28 | 593.75 | 01-NOV-11:00 | 0.56 |
December | 0.790853E+09 | 0.28 | 918.94 | 23-DEC-08:62 | 0.73 |
Annual Sum or Average | 0.100541E+11 | 0.29 | |||
Minimum of Months | 0.719736E+09 | 0.28 | 593.75 | 0.56 | |
Maximum of Months | 0.961895E+09 | 0.31 | 1484.39 | 0.93 |
Report: FanReportMonthly
For: PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.803023E+09 | 0.28 | 1479.42 | 01-JAN-09:01 | 0.93 |
February | 0.717521E+09 | 0.28 | 738.41 | 11-FEB-08:62 | 0.64 |
March | 0.807428E+09 | 0.29 | 707.88 | 11-MAR-08:62 | 0.63 |
April | 0.777109E+09 | 0.28 | 1479.42 | 02-APR-08:62 | 0.92 |
May | 0.894765E+09 | 0.30 | 1479.42 | 01-MAY-07:01 | 0.93 |
June | 0.931119E+09 | 0.31 | 1479.42 | 01-JUN-07:02 | 0.92 |
July | 0.954728E+09 | 0.31 | 1479.42 | 01-JUL-07:01 | 0.92 |
August | 0.958989E+09 | 0.31 | 1479.42 | 01-AUG-07:01 | 0.91 |
September | 0.828408E+09 | 0.29 | 1479.42 | 01-SEP-07:01 | 0.91 |
October | 0.794109E+09 | 0.28 | 1479.42 | 01-OCT-08:62 | 0.92 |
November | 0.766933E+09 | 0.28 | 591.77 | 01-NOV-11:40 | 0.56 |
December | 0.788458E+09 | 0.28 | 954.76 | 23-DEC-08:62 | 0.75 |
Annual Sum or Average | 0.100226E+11 | 0.29 | |||
Minimum of Months | 0.717521E+09 | 0.28 | 591.77 | 0.56 | |
Maximum of Months | 0.958989E+09 | 0.31 | 1479.42 | 0.93 |
Report: FanReportMonthly
For: PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.809224E+09 | 0.28 | 1487.17 | 01-JAN-09:01 | 0.93 |
February | 0.721882E+09 | 0.28 | 901.26 | 11-FEB-08:62 | 0.72 |
March | 0.811637E+09 | 0.29 | 594.87 | 03-MAR-20:15 | 0.56 |
April | 0.781198E+09 | 0.28 | 1487.17 | 03-APR-07:02 | 0.92 |
May | 0.900872E+09 | 0.30 | 1487.17 | 01-MAY-07:01 | 0.93 |
June | 0.937806E+09 | 0.31 | 1487.17 | 01-JUN-07:02 | 0.92 |
July | 0.962338E+09 | 0.31 | 1487.17 | 01-JUL-07:01 | 0.92 |
August | 0.966027E+09 | 0.31 | 1487.17 | 01-AUG-07:01 | 0.91 |
September | 0.833809E+09 | 0.29 | 1487.17 | 01-SEP-07:01 | 0.91 |
October | 0.798301E+09 | 0.28 | 1487.17 | 01-OCT-08:62 | 0.92 |
November | 0.770948E+09 | 0.28 | 594.87 | 04-NOV-14:30 | 0.56 |
December | 0.793426E+09 | 0.28 | 1086.73 | 23-DEC-08:62 | 0.80 |
Annual Sum or Average | 0.100875E+11 | 0.29 | |||
Minimum of Months | 0.721882E+09 | 0.28 | 594.87 | 0.56 | |
Maximum of Months | 0.966027E+09 | 0.31 | 1487.17 | 0.93 |
Report: FanReportMonthly
For: PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.917497E+09 | 0.27 | 1680.33 | 01-JAN-09:01 | 0.89 |
February | 0.817547E+09 | 0.27 | 1507.07 | 11-FEB-08:62 | 0.85 |
March | 0.917059E+09 | 0.28 | 672.13 | 08-MAR-18:30 | 0.54 |
April | 0.882848E+09 | 0.27 | 1680.33 | 16-APR-08:61 | 0.89 |
May | 0.102195E+10 | 0.29 | 1680.33 | 01-MAY-07:01 | 0.90 |
June | 0.106236E+10 | 0.30 | 1680.33 | 01-JUN-07:02 | 0.89 |
July | 0.109020E+10 | 0.30 | 1680.33 | 01-JUL-07:01 | 0.88 |
August | 0.109067E+10 | 0.30 | 1680.33 | 01-AUG-07:01 | 0.88 |
September | 0.943803E+09 | 0.28 | 1680.33 | 01-SEP-07:01 | 0.88 |
October | 0.902281E+09 | 0.27 | 1680.33 | 01-OCT-08:62 | 0.89 |
November | 0.871112E+09 | 0.27 | 692.40 | 27-NOV-08:30 | 0.55 |
December | 0.898727E+09 | 0.27 | 1606.93 | 23-DEC-08:62 | 0.88 |
Annual Sum or Average | 0.114160E+11 | 0.28 | |||
Minimum of Months | 0.817547E+09 | 0.27 | 672.13 | 0.54 | |
Maximum of Months | 0.109067E+10 | 0.30 | 1680.33 | 0.90 |
Report: ZoneTemperatureOscillationReportMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.261704E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.382724E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.737875E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.114185E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.159608E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.172612E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.178363E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.170877E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.144234E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.105383E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.629203E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.316124E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.127803E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.261704E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.178363E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.132459E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.202401E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.368949E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.545219E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.758826E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.815954E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.843352E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.808534E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.680437E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.507702E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.321797E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.171959E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.615759E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.132459E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.843352E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_3:3
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.110031E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.160501E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.302706E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.449632E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.637439E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.683915E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.693555E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.680850E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.562501E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.417989E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.262164E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.135353E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.509664E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.110031E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.693555E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_4:4
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.108289E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.158377E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.302296E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.451272E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.641132E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.687694E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.697511E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.683803E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.564786E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.419432E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.261189E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.132604E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.510839E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.108289E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.697511E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_5:5
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.104532E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.152711E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.295658E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.445618E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.635357E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.681695E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.691905E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.677482E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.558830E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.413811E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.255269E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.126587E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.503946E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.104532E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.691905E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_6:6
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.168197E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.253381E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.521222E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.806117E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.116561E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.125444E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.126383E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.124163E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.101319E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.744129E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.442844E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.201613E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.907621E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.168197E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.126383E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_7:7
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.900892E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.132867E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.270903E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.417163E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.602962E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.648137E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.652758E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.640927E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.523303E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.385272E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.230821E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.106766E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.470197E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.900892E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.652758E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_8:8
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.892878E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.131245E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.268862E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.415471E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.601245E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.646357E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.651159E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.639282E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.521767E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.383690E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.229056E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.105421E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.468284E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.892878E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.651159E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_9:9
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.887464E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.128574E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.266063E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.416230E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.604940E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.650682E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.656117E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.643924E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.524949E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.384703E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.226973E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.103622E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.469552E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.887464E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.656117E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_10:10
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.100870E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.143600E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.294747E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.471567E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.688578E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.737039E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.743007E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.728338E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.593770E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.436662E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.254011E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.117561E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.530975E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.100870E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.743007E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.219900E+10 | 0.149964E+10 | 0.667472E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.197639E+10 | 0.672751E+10 | 93958130.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.219048E+10 | 0.187160E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.212929E+10 | 0.318706E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.234327E+10 | 0.467266E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.240571E+10 | 0.530472E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.249627E+10 | 0.597987E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.246885E+10 | 0.590493E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.222427E+10 | 0.484871E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.218663E+10 | 0.309623E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.210816E+10 | 0.153558E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.219374E+10 | 0.349695E+10 | 0.128768E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.269221E+11 | 0.375738E+12 | 0.890199E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.197639E+10 | 0.149964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.249627E+10 | 0.597987E+11 | 0.667472E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.867228E+09 | 0.167877E+10 | 0.126335E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.801376E+09 | 0.455797E+10 | 4076399.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.923526E+09 | 0.101992E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.926158E+09 | 0.157284E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.106595E+10 | 0.225293E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.111361E+10 | 0.252667E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116396E+10 | 0.284323E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.114544E+10 | 0.281636E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.100607E+10 | 0.231860E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.945242E+09 | 0.155367E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.877372E+09 | 0.878594E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.872409E+09 | 0.313507E+10 | 15668735.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.117083E+11 | 0.187200E+12 | 0.146081E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.801376E+09 | 0.167877E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.116396E+10 | 0.284323E+11 | 0.126335E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_3:3
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.898052E+09 | 0.740413E+09 | 0.294374E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.806927E+09 | 0.295431E+10 | 25875053.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.908416E+09 | 0.777085E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.871723E+09 | 0.126638E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.979775E+09 | 0.188153E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.101319E+10 | 0.212437E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.103325E+10 | 0.235966E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.104272E+10 | 0.238291E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.913854E+09 | 0.191703E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.893545E+09 | 0.123734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.863846E+09 | 0.655124E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.886992E+09 | 0.171852E+10 | 38455531.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.111123E+11 | 0.151428E+12 | 0.358705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.806927E+09 | 0.740413E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.104272E+10 | 0.238291E+11 | 0.294374E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_4:4
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.901747E+09 | 0.661839E+09 | 0.360536E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.808994E+09 | 0.286279E+10 | 36513839.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.910448E+09 | 0.774361E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.873820E+09 | 0.127180E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.983557E+09 | 0.189408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.101718E+10 | 0.213739E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.103777E+10 | 0.237418E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.104636E+10 | 0.239380E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.916453E+09 | 0.192562E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.895671E+09 | 0.124220E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.865766E+09 | 0.650179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.889274E+09 | 0.160559E+10 | 50530969.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.111470E+11 | 0.151766E+12 | 0.447581E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.808994E+09 | 0.661839E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.104636E+10 | 0.239380E+11 | 0.360536E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_5:5
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.898471E+09 | 0.534699E+09 | 0.445176E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.804516E+09 | 0.266047E+10 | 54611647.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.904796E+09 | 0.750114E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.867844E+09 | 0.125228E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.975878E+09 | 0.187575E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.100907E+10 | 0.211797E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.102966E+10 | 0.235503E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.103742E+10 | 0.237144E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.908861E+09 | 0.190390E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.889933E+09 | 0.122134E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.860466E+09 | 0.628494E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.884352E+09 | 0.139801E+10 | 70370597.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.110713E+11 | 0.149356E+12 | 0.570158E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.804516E+09 | 0.534699E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.103742E+10 | 0.237144E+11 | 0.445176E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_6:6
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.147099E+10 | 0.752908E+09 | 0.864330E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.131516E+10 | 0.439434E+10 | 0.115305E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.148024E+10 | 0.133957E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.142464E+10 | 0.227610E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.163799E+10 | 0.343783E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.170669E+10 | 0.388817E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.175222E+10 | 0.429338E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.176086E+10 | 0.434788E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.152045E+10 | 0.345514E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.145633E+10 | 0.221752E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.140594E+10 | 0.110221E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.144526E+10 | 0.205234E+10 | 0.163039E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.183768E+11 | 0.270777E+12 | 0.114267E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.131516E+10 | 0.752908E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.176086E+10 | 0.434788E+11 | 0.864330E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_7:7
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.805062E+09 | 0.347434E+09 | 0.452569E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.719736E+09 | 0.223100E+10 | 57514401.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.810143E+09 | 0.692610E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.779761E+09 | 0.118174E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.897631E+09 | 0.178749E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.934114E+09 | 0.201905E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.957546E+09 | 0.222966E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.961895E+09 | 0.225606E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.831091E+09 | 0.179353E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.796796E+09 | 0.115024E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.769506E+09 | 0.570315E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.790853E+09 | 0.101131E+10 | 79282541.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.100541E+11 | 0.140397E+12 | 0.589366E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.719736E+09 | 0.347434E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.961895E+09 | 0.225606E+11 | 0.452569E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_8:8
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.803023E+09 | 0.325459E+09 | 0.475736E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.717521E+09 | 0.217742E+10 | 64529372.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.807428E+09 | 0.685710E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.777109E+09 | 0.117655E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.894765E+09 | 0.178262E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.931119E+09 | 0.201391E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.954728E+09 | 0.222487E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.958989E+09 | 0.225095E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.828408E+09 | 0.178861E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.794109E+09 | 0.114511E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.766933E+09 | 0.564401E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.788458E+09 | 0.970072E+09 | 88372596.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.100226E+11 | 0.139800E+12 | 0.628638E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.717521E+09 | 0.325459E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.958989E+09 | 0.225095E+11 | 0.475736E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_9:9
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.809224E+09 | 0.282728E+09 | 0.552985E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.721882E+09 | 0.205776E+10 | 87574416.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.811637E+09 | 0.672505E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.781198E+09 | 0.117703E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.900872E+09 | 0.179289E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.937806E+09 | 0.202653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.962338E+09 | 0.224087E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.966027E+09 | 0.226656E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.833809E+09 | 0.179884E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.798301E+09 | 0.114696E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.770948E+09 | 0.554240E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.793426E+09 | 0.884214E+09 | 0.120398E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.100875E+11 | 0.139989E+12 | 0.760957E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.721882E+09 | 0.282728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.966027E+09 | 0.226656E+11 | 0.552985E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_10:10
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.917497E+09 | 0.329311E+09 | 0.757576E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.817547E+09 | 0.225167E+10 | 0.173548E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.917059E+09 | 0.735579E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.882848E+09 | 0.133310E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.102195E+10 | 0.203375E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.106236E+10 | 0.227841E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.109020E+10 | 0.251451E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.109067E+10 | 0.254171E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.943803E+09 | 0.201846E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.902281E+09 | 0.130284E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.871112E+09 | 0.616048E+10 | 1036745.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.898727E+09 | 0.100748E+10 | 0.224446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.114160E+11 | 0.157333E+12 | 0.115661E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.817547E+09 | 0.329311E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.109067E+10 | 0.254171E+11 | 0.757576E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.219900E+10 | 0.00 | 0.00 | 0.00 | 0.418036E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.197639E+10 | 0.00 | 0.00 | 0.00 | 0.185085E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.219048E+10 | 0.00 | 0.00 | 0.00 | 0.518827E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.212929E+10 | 0.00 | 0.00 | 0.00 | 0.928922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.234327E+10 | 0.00 | 0.00 | 0.00 | 0.136175E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.240571E+10 | 0.00 | 0.00 | 0.00 | 0.148555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.249627E+10 | 0.00 | 0.00 | 0.00 | 0.153401E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.246885E+10 | 0.00 | 0.00 | 0.00 | 0.146189E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.222427E+10 | 0.00 | 0.00 | 0.00 | 0.121992E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.218663E+10 | 0.00 | 0.00 | 0.00 | 0.835167E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.210816E+10 | 0.00 | 0.00 | 0.00 | 0.418387E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.219374E+10 | 0.00 | 0.00 | 0.00 | 0.967508E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.269221E+11 | 0.00 | 0.00 | 0.00 | 0.100881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.197639E+10 | 0.00 | 0.00 | 0.00 | 0.418036E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.249627E+10 | 0.00 | 0.00 | 0.00 | 0.153401E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.867228E+09 | 0.00 | 0.00 | 0.00 | 0.457362E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.801376E+09 | 0.00 | 0.00 | 0.00 | 0.122263E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.923526E+09 | 0.00 | 0.00 | 0.00 | 0.276596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.926158E+09 | 0.00 | 0.00 | 0.00 | 0.452603E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.106595E+10 | 0.00 | 0.00 | 0.00 | 0.652231E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.111361E+10 | 0.00 | 0.00 | 0.00 | 0.704593E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116396E+10 | 0.00 | 0.00 | 0.00 | 0.726955E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.114544E+10 | 0.00 | 0.00 | 0.00 | 0.693991E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.100607E+10 | 0.00 | 0.00 | 0.00 | 0.579830E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.945242E+09 | 0.00 | 0.00 | 0.00 | 0.413177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.877372E+09 | 0.00 | 0.00 | 0.00 | 0.234060E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.872409E+09 | 0.00 | 0.00 | 0.00 | 0.847179E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.117083E+11 | 0.00 | 0.00 | 0.00 | 0.498675E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.801376E+09 | 0.00 | 0.00 | 0.00 | 0.457362E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.116396E+10 | 0.00 | 0.00 | 0.00 | 0.726955E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_3:3
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.898052E+09 | 0.00 | 0.00 | 0.00 | 0.202262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.806927E+09 | 0.00 | 0.00 | 0.00 | 0.798086E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.908416E+09 | 0.00 | 0.00 | 0.00 | 0.211864E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.871723E+09 | 0.00 | 0.00 | 0.00 | 0.362460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.979775E+09 | 0.00 | 0.00 | 0.00 | 0.539462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.101319E+10 | 0.00 | 0.00 | 0.00 | 0.582596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.103325E+10 | 0.00 | 0.00 | 0.00 | 0.590230E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.104272E+10 | 0.00 | 0.00 | 0.00 | 0.576579E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.913854E+09 | 0.00 | 0.00 | 0.00 | 0.471115E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.893545E+09 | 0.00 | 0.00 | 0.00 | 0.328634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.863846E+09 | 0.00 | 0.00 | 0.00 | 0.175780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.886992E+09 | 0.00 | 0.00 | 0.00 | 0.466536E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.111123E+11 | 0.00 | 0.00 | 0.00 | 0.398541E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.806927E+09 | 0.00 | 0.00 | 0.00 | 0.202262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.104272E+10 | 0.00 | 0.00 | 0.00 | 0.590230E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_4:4
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.901747E+09 | 0.00 | 0.00 | 0.00 | 0.181139E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.774779E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.910448E+09 | 0.00 | 0.00 | 0.00 | 0.211251E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.873820E+09 | 0.00 | 0.00 | 0.00 | 0.363890E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.983557E+09 | 0.00 | 0.00 | 0.00 | 0.542777E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.101718E+10 | 0.00 | 0.00 | 0.00 | 0.585977E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.103777E+10 | 0.00 | 0.00 | 0.00 | 0.593734E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.104636E+10 | 0.00 | 0.00 | 0.00 | 0.579167E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.916453E+09 | 0.00 | 0.00 | 0.00 | 0.473140E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.895671E+09 | 0.00 | 0.00 | 0.00 | 0.329865E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.865766E+09 | 0.00 | 0.00 | 0.00 | 0.174612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.889274E+09 | 0.00 | 0.00 | 0.00 | 0.436763E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.111470E+11 | 0.00 | 0.00 | 0.00 | 0.399368E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.181139E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.104636E+10 | 0.00 | 0.00 | 0.00 | 0.593734E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_5:5
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.898471E+09 | 0.00 | 0.00 | 0.00 | 0.146847E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.804516E+09 | 0.00 | 0.00 | 0.00 | 0.722594E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.904796E+09 | 0.00 | 0.00 | 0.00 | 0.205178E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.867844E+09 | 0.00 | 0.00 | 0.00 | 0.358834E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.975878E+09 | 0.00 | 0.00 | 0.00 | 0.537769E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.100907E+10 | 0.00 | 0.00 | 0.00 | 0.580788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.102966E+10 | 0.00 | 0.00 | 0.00 | 0.588939E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.103742E+10 | 0.00 | 0.00 | 0.00 | 0.573740E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.908861E+09 | 0.00 | 0.00 | 0.00 | 0.467944E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.889933E+09 | 0.00 | 0.00 | 0.00 | 0.324817E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.860466E+09 | 0.00 | 0.00 | 0.00 | 0.169223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.884352E+09 | 0.00 | 0.00 | 0.00 | 0.381521E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.110713E+11 | 0.00 | 0.00 | 0.00 | 0.393233E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.804516E+09 | 0.00 | 0.00 | 0.00 | 0.146847E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.103742E+10 | 0.00 | 0.00 | 0.00 | 0.588939E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_6:6
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.147099E+10 | 0.00 | 0.00 | 0.00 | 0.210979E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.131516E+10 | 0.00 | 0.00 | 0.00 | 0.121865E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.148024E+10 | 0.00 | 0.00 | 0.00 | 0.373198E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.142464E+10 | 0.00 | 0.00 | 0.00 | 0.663653E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.163799E+10 | 0.00 | 0.00 | 0.00 | 0.100182E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.170669E+10 | 0.00 | 0.00 | 0.00 | 0.108377E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.175222E+10 | 0.00 | 0.00 | 0.00 | 0.108861E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.176086E+10 | 0.00 | 0.00 | 0.00 | 0.106554E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.152045E+10 | 0.00 | 0.00 | 0.00 | 0.861146E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.145633E+10 | 0.00 | 0.00 | 0.00 | 0.598495E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.140594E+10 | 0.00 | 0.00 | 0.00 | 0.302250E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.144526E+10 | 0.00 | 0.00 | 0.00 | 0.570870E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.183768E+11 | 0.00 | 0.00 | 0.00 | 0.723853E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.131516E+10 | 0.00 | 0.00 | 0.00 | 0.210979E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.176086E+10 | 0.00 | 0.00 | 0.00 | 0.108861E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_7:7
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.805062E+09 | 0.00 | 0.00 | 0.00 | 95829255.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.719736E+09 | 0.00 | 0.00 | 0.00 | 0.608936E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.810143E+09 | 0.00 | 0.00 | 0.00 | 0.189889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.779761E+09 | 0.00 | 0.00 | 0.00 | 0.339187E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.897631E+09 | 0.00 | 0.00 | 0.00 | 0.513199E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.934114E+09 | 0.00 | 0.00 | 0.00 | 0.554725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.957546E+09 | 0.00 | 0.00 | 0.00 | 0.557003E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.961895E+09 | 0.00 | 0.00 | 0.00 | 0.544738E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.831091E+09 | 0.00 | 0.00 | 0.00 | 0.440194E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.796796E+09 | 0.00 | 0.00 | 0.00 | 0.305593E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.769506E+09 | 0.00 | 0.00 | 0.00 | 0.153870E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.790853E+09 | 0.00 | 0.00 | 0.00 | 0.276809E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.100541E+11 | 0.00 | 0.00 | 0.00 | 0.369655E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.719736E+09 | 0.00 | 0.00 | 0.00 | 95829255.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.961895E+09 | 0.00 | 0.00 | 0.00 | 0.557003E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_8:8
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.803023E+09 | 0.00 | 0.00 | 0.00 | 89854638.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.717521E+09 | 0.00 | 0.00 | 0.00 | 0.594925E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.807428E+09 | 0.00 | 0.00 | 0.00 | 0.188119E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.777109E+09 | 0.00 | 0.00 | 0.00 | 0.337760E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.894765E+09 | 0.00 | 0.00 | 0.00 | 0.511769E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.931119E+09 | 0.00 | 0.00 | 0.00 | 0.553246E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.954728E+09 | 0.00 | 0.00 | 0.00 | 0.555686E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.958989E+09 | 0.00 | 0.00 | 0.00 | 0.543384E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.828408E+09 | 0.00 | 0.00 | 0.00 | 0.438927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.794109E+09 | 0.00 | 0.00 | 0.00 | 0.304279E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.766933E+09 | 0.00 | 0.00 | 0.00 | 0.152363E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.788458E+09 | 0.00 | 0.00 | 0.00 | 0.265750E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.100226E+11 | 0.00 | 0.00 | 0.00 | 0.368058E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.717521E+09 | 0.00 | 0.00 | 0.00 | 89854638.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.958989E+09 | 0.00 | 0.00 | 0.00 | 0.555686E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_9:9
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.809224E+09 | 0.00 | 0.00 | 0.00 | 78240073.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.721882E+09 | 0.00 | 0.00 | 0.00 | 0.563858E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.811637E+09 | 0.00 | 0.00 | 0.00 | 0.184899E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.781198E+09 | 0.00 | 0.00 | 0.00 | 0.338110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.900872E+09 | 0.00 | 0.00 | 0.00 | 0.514852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.937806E+09 | 0.00 | 0.00 | 0.00 | 0.556901E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.962338E+09 | 0.00 | 0.00 | 0.00 | 0.559883E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.966027E+09 | 0.00 | 0.00 | 0.00 | 0.547321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.833809E+09 | 0.00 | 0.00 | 0.00 | 0.441568E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.798301E+09 | 0.00 | 0.00 | 0.00 | 0.304873E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.770948E+09 | 0.00 | 0.00 | 0.00 | 0.149879E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.793426E+09 | 0.00 | 0.00 | 0.00 | 0.242792E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.100875E+11 | 0.00 | 0.00 | 0.00 | 0.368678E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.721882E+09 | 0.00 | 0.00 | 0.00 | 78240073.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.966027E+09 | 0.00 | 0.00 | 0.00 | 0.559883E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_10:10
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.917497E+09 | 0.00 | 0.00 | 0.00 | 91207986.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.817547E+09 | 0.00 | 0.00 | 0.00 | 0.618450E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.917059E+09 | 0.00 | 0.00 | 0.00 | 0.203041E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.882848E+09 | 0.00 | 0.00 | 0.00 | 0.383282E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.102195E+10 | 0.00 | 0.00 | 0.00 | 0.586383E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.106236E+10 | 0.00 | 0.00 | 0.00 | 0.630803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.109020E+10 | 0.00 | 0.00 | 0.00 | 0.633987E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.109067E+10 | 0.00 | 0.00 | 0.00 | 0.619271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.943803E+09 | 0.00 | 0.00 | 0.00 | 0.499390E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.902281E+09 | 0.00 | 0.00 | 0.00 | 0.346434E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.871112E+09 | 0.00 | 0.00 | 0.00 | 0.166899E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.898727E+09 | 0.00 | 0.00 | 0.00 | 0.276886E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.114160E+11 | 0.00 | 0.00 | 0.00 | 0.416814E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.817547E+09 | 0.00 | 0.00 | 0.00 | 91207986.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.109067E+10 | 0.00 | 0.00 | 0.00 | 0.633987E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.525583E+10 | 0.00 | 0.00 | 3533516.73 | 0.00 | 0.344710E+09 | 0.204851E+10 | 0.00 | 0.57 |
February | 0.194340E+10 | 0.145540E+09 | 0.00 | 7509001.26 | 0.00 | 31996663.08 | 0.197527E+10 | 0.00 | 0.57 |
March | 0.346604E+09 | 0.253446E+10 | 0.00 | 5320712.18 | 3376628.27 | 0.00 | 0.702190E+09 | 0.00 | 0.57 |
April | 4608866.18 | 0.803562E+10 | 0.00 | 445272.23 | 72766377.63 | 0.00 | 24202362.85 | 0.00 | 0.57 |
May | 0.00 | 0.159049E+11 | 0.00 | 101439.56 | 0.122824E+09 | 0.00 | 0.00 | 0.00 | 0.58 |
June | 0.00 | 0.204849E+11 | 0.00 | 0.00 | 0.135906E+09 | 0.00 | 0.00 | 0.00 | 0.58 |
July | 0.00 | 0.249705E+11 | 0.00 | 0.00 | 0.135421E+09 | 0.00 | 0.00 | 0.00 | 0.58 |
August | 0.00 | 0.249216E+11 | 0.00 | 0.00 | 0.151411E+09 | 0.00 | 0.00 | 0.00 | 0.58 |
September | 0.00 | 0.189026E+11 | 0.00 | 0.00 | 0.171310E+09 | 0.00 | 0.00 | 0.00 | 0.58 |
October | 45263655.55 | 0.707567E+10 | 0.00 | 1046251.94 | 54339579.92 | 0.00 | 0.102301E+09 | 0.00 | 0.57 |
November | 0.575355E+09 | 0.125277E+10 | 0.00 | 7738974.28 | 0.00 | 0.00 | 0.168975E+10 | 0.00 | 0.57 |
December | 0.364358E+10 | 5044747.78 | 0.00 | 7021169.20 | 0.00 | 43672271.70 | 0.322756E+10 | 0.00 | 0.57 |
Annual Sum or Average | 0.118146E+11 | 0.124234E+12 | 0.00 | 32716337.38 | 0.847355E+09 | 0.420379E+09 | 0.976978E+10 | 0.00 | 0.58 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.57 |
Maximum of Months | 0.525583E+10 | 0.249705E+11 | 0.00 | 7738974.28 | 0.171310E+09 | 0.344710E+09 | 0.322756E+10 | 0.00 | 0.58 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.137315E+10 | 0.00 | 0.00 | 3295155.66 | 0.00 | 73358036.83 | 0.121327E+10 | 0.00 | 0.43 |
February | 0.552605E+09 | 79452324.09 | 0.00 | 4839542.86 | 143860.19 | 0.00 | 0.626832E+09 | 0.00 | 0.44 |
March | 0.100051E+09 | 0.119845E+10 | 0.00 | 2758618.58 | 8053093.14 | 0.00 | 0.158367E+09 | 0.00 | 0.46 |
April | 979617.74 | 0.345417E+10 | 0.00 | 257403.77 | 49572062.23 | 0.00 | 4703080.03 | 0.00 | 0.46 |
May | 0.00 | 0.685316E+10 | 0.00 | 0.00 | 64421941.66 | 0.00 | 0.00 | 0.00 | 0.48 |
June | 0.00 | 0.880039E+10 | 0.00 | 0.00 | 63312623.41 | 0.00 | 0.00 | 0.00 | 0.49 |
July | 0.00 | 0.106960E+11 | 0.00 | 0.00 | 77316687.86 | 0.00 | 0.00 | 0.00 | 0.49 |
August | 0.00 | 0.107596E+11 | 0.00 | 0.00 | 82185308.96 | 0.00 | 0.00 | 0.00 | 0.49 |
September | 0.00 | 0.803369E+10 | 0.00 | 0.00 | 0.107149E+09 | 0.00 | 0.00 | 0.00 | 0.48 |
October | 1902429.92 | 0.317609E+10 | 0.00 | 161232.56 | 55456316.69 | 0.00 | 7145155.03 | 0.00 | 0.46 |
November | 0.139093E+09 | 0.650921E+09 | 0.00 | 4161737.66 | 1261428.04 | 0.00 | 0.340737E+09 | 0.00 | 0.45 |
December | 0.947813E+09 | 2912208.43 | 0.00 | 5276124.91 | 0.00 | 562351.05 | 0.121190E+10 | 0.00 | 0.43 |
Annual Sum or Average | 0.311560E+10 | 0.537048E+11 | 0.00 | 20749816.00 | 0.508872E+09 | 73920387.88 | 0.356296E+10 | 0.00 | 0.46 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.43 |
Maximum of Months | 0.137315E+10 | 0.107596E+11 | 0.00 | 5276124.91 | 0.107149E+09 | 73358036.83 | 0.121327E+10 | 0.00 | 0.49 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.185805E+10 | 8610.37 | 0.00 | 1522896.46 | 0.00 | 0.113428E+09 | 0.730701E+09 | 0.00 | 0.45 |
February | 0.867294E+09 | 80998800.91 | 0.00 | 2610144.90 | 325899.63 | 0.00 | 0.471452E+09 | 0.00 | 0.45 |
March | 0.218323E+09 | 0.104556E+10 | 0.00 | 1717628.74 | 55885003.94 | 0.00 | 0.195491E+09 | 0.00 | 0.46 |
April | 1655149.89 | 0.303487E+10 | 0.00 | 199903.83 | 0.217109E+09 | 0.00 | 7251018.03 | 0.00 | 0.46 |
May | 27062.46 | 0.594712E+10 | 0.00 | 136170.66 | 0.413525E+09 | 0.00 | 46522.76 | 0.00 | 0.47 |
June | 0.00 | 0.741712E+10 | 0.00 | 0.00 | 0.542065E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
July | 0.00 | 0.881104E+10 | 0.00 | 0.00 | 0.605487E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
August | 0.00 | 0.895862E+10 | 0.00 | 0.00 | 0.625699E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
September | 0.00 | 0.661663E+10 | 0.00 | 25291.40 | 0.493675E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
October | 12516696.30 | 0.268655E+10 | 0.00 | 696661.85 | 0.173852E+09 | 0.00 | 79627374.23 | 0.00 | 0.46 |
November | 0.392542E+09 | 0.612334E+09 | 0.00 | 2057629.23 | 11637946.05 | 0.00 | 0.323600E+09 | 0.00 | 0.46 |
December | 0.139141E+10 | 3293614.18 | 0.00 | 2947111.94 | 0.00 | 3809599.74 | 0.880938E+09 | 0.00 | 0.45 |
Annual Sum or Average | 0.474182E+10 | 0.452142E+11 | 0.00 | 11913439.03 | 0.313926E+10 | 0.117237E+09 | 0.268911E+10 | 0.00 | 0.46 |
Minimum of Months | 0.00 | 8610.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.45 |
Maximum of Months | 0.185805E+10 | 0.895862E+10 | 0.00 | 2947111.94 | 0.625699E+09 | 0.113428E+09 | 0.880938E+09 | 0.00 | 0.47 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.186954E+10 | 5211.56 | 0.00 | 1338899.52 | 0.00 | 0.153458E+09 | 0.657090E+09 | 0.00 | 0.45 |
February | 0.874151E+09 | 79939735.96 | 0.00 | 2497222.71 | 322025.86 | 0.00 | 0.461567E+09 | 0.00 | 0.45 |
March | 0.220224E+09 | 0.104477E+10 | 0.00 | 1699172.29 | 55876606.84 | 0.00 | 0.192891E+09 | 0.00 | 0.46 |
April | 1652224.60 | 0.303842E+10 | 0.00 | 211647.51 | 0.216935E+09 | 0.00 | 7179395.15 | 0.00 | 0.46 |
May | 30411.18 | 0.595974E+10 | 0.00 | 142364.15 | 0.411973E+09 | 0.00 | 46513.74 | 0.00 | 0.47 |
June | 0.00 | 0.743933E+10 | 0.00 | 0.00 | 0.536056E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
July | 0.00 | 0.883643E+10 | 0.00 | 0.00 | 0.604387E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
August | 0.00 | 0.898011E+10 | 0.00 | 0.00 | 0.624857E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
September | 0.00 | 0.663753E+10 | 0.00 | 28743.25 | 0.488767E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
October | 12550486.40 | 0.269182E+10 | 0.00 | 713002.88 | 0.173816E+09 | 0.00 | 79255373.24 | 0.00 | 0.46 |
November | 0.398262E+09 | 0.610932E+09 | 0.00 | 2017733.35 | 11628738.11 | 0.00 | 0.317652E+09 | 0.00 | 0.46 |
December | 0.140155E+10 | 3192296.99 | 0.00 | 2754193.63 | 0.00 | 6401984.06 | 0.862498E+09 | 0.00 | 0.45 |
Annual Sum or Average | 0.477795E+10 | 0.453222E+11 | 0.00 | 11402979.30 | 0.312462E+10 | 0.159860E+09 | 0.257818E+10 | 0.00 | 0.46 |
Minimum of Months | 0.00 | 5211.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.45 |
Maximum of Months | 0.186954E+10 | 0.898011E+10 | 0.00 | 2754193.63 | 0.624857E+09 | 0.153458E+09 | 0.862498E+09 | 0.00 | 0.47 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.189065E+10 | 1014.97 | 0.00 | 1061523.76 | 0.00 | 0.228490E+09 | 0.527884E+09 | 0.00 | 0.45 |
February | 0.899353E+09 | 77668988.03 | 0.00 | 2270438.20 | 304508.04 | 0.00 | 0.432470E+09 | 0.00 | 0.45 |
March | 0.232754E+09 | 0.103400E+10 | 0.00 | 1595373.76 | 55788963.00 | 0.00 | 0.182428E+09 | 0.00 | 0.46 |
April | 1758457.04 | 0.302902E+10 | 0.00 | 183457.50 | 0.217315E+09 | 0.00 | 7229357.84 | 0.00 | 0.46 |
May | 25433.32 | 0.594398E+10 | 0.00 | 131155.08 | 0.411866E+09 | 0.00 | 48183.62 | 0.00 | 0.47 |
June | 0.00 | 0.741150E+10 | 0.00 | 0.00 | 0.540037E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
July | 0.00 | 0.880523E+10 | 0.00 | 0.00 | 0.605017E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
August | 0.00 | 0.893823E+10 | 0.00 | 0.00 | 0.627055E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
September | 0.00 | 0.659588E+10 | 0.00 | 26703.88 | 0.491804E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
October | 14740409.41 | 0.267142E+10 | 0.00 | 664921.64 | 0.174574E+09 | 0.00 | 79763027.40 | 0.00 | 0.46 |
November | 0.422624E+09 | 0.603175E+09 | 0.00 | 1881868.78 | 11619005.84 | 0.00 | 0.296039E+09 | 0.00 | 0.46 |
December | 0.142968E+10 | 3026123.58 | 0.00 | 2386873.62 | 0.00 | 19927948.52 | 0.812242E+09 | 0.00 | 0.45 |
Annual Sum or Average | 0.489158E+10 | 0.451131E+11 | 0.00 | 10202316.21 | 0.313538E+10 | 0.248418E+09 | 0.233810E+10 | 0.00 | 0.46 |
Minimum of Months | 0.00 | 1014.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.45 |
Maximum of Months | 0.189065E+10 | 0.893823E+10 | 0.00 | 2386873.62 | 0.627055E+09 | 0.228490E+09 | 0.812242E+09 | 0.00 | 0.47 |
Report: MechanicalVentilationLoadsMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.325532E+10 | 0.00 | 0.00 | 1461951.18 | 0.00 | 0.607496E+09 | 0.926622E+09 | 0.00 | 0.42 |
February | 0.137862E+10 | 92416859.88 | 0.00 | 4191384.57 | 229772.69 | 54354673.32 | 0.938370E+09 | 0.00 | 0.42 |
March | 0.298020E+09 | 0.193819E+10 | 0.00 | 3272196.06 | 41755667.81 | 0.00 | 0.314968E+09 | 0.00 | 0.43 |
April | 2032131.77 | 0.589045E+10 | 0.00 | 163937.93 | 0.201389E+09 | 0.00 | 6512631.78 | 0.00 | 0.42 |
May | 0.00 | 0.116175E+11 | 0.00 | 80419.34 | 0.278683E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
June | 0.00 | 0.145205E+11 | 0.00 | 0.00 | 0.311418E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
July | 0.00 | 0.169287E+11 | 0.00 | 0.00 | 0.449472E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
August | 0.00 | 0.175170E+11 | 0.00 | 0.00 | 0.390120E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
September | 0.00 | 0.127487E+11 | 0.00 | 50386.09 | 0.422271E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
October | 32963991.39 | 0.519416E+10 | 0.00 | 584610.36 | 0.170350E+09 | 0.00 | 53642427.82 | 0.00 | 0.42 |
November | 0.460816E+09 | 0.101022E+10 | 0.00 | 3415045.72 | 17823403.18 | 0.00 | 0.631957E+09 | 0.00 | 0.42 |
December | 0.265679E+10 | 1244793.81 | 0.00 | 3453859.04 | 0.00 | 43196132.51 | 0.150147E+10 | 0.00 | 0.41 |
Annual Sum or Average | 0.808456E+10 | 0.874591E+11 | 0.00 | 16673790.28 | 0.228351E+10 | 0.705047E+09 | 0.437354E+10 | 0.00 | 0.43 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.325532E+10 | 0.175170E+11 | 0.00 | 4191384.57 | 0.449472E+09 | 0.607496E+09 | 0.150147E+10 | 0.00 | 0.44 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.162796E+10 | 0.00 | 0.00 | 632718.60 | 0.00 | 0.332920E+09 | 0.406753E+09 | 0.00 | 0.42 |
February | 0.696643E+09 | 46856216.64 | 0.00 | 2036330.53 | 113388.79 | 27554768.07 | 0.453441E+09 | 0.00 | 0.42 |
March | 0.153662E+09 | 0.968827E+09 | 0.00 | 1640768.18 | 20428498.31 | 0.00 | 0.151212E+09 | 0.00 | 0.43 |
April | 1133916.78 | 0.294610E+10 | 0.00 | 80846.86 | 0.104260E+09 | 0.00 | 3123752.00 | 0.00 | 0.42 |
May | 0.00 | 0.581058E+10 | 0.00 | 35941.91 | 0.136338E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
June | 0.00 | 0.725744E+10 | 0.00 | 0.00 | 0.145232E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
July | 0.00 | 0.842812E+10 | 0.00 | 0.00 | 0.230184E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
August | 0.00 | 0.871423E+10 | 0.00 | 0.00 | 0.197334E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
September | 0.00 | 0.634805E+10 | 0.00 | 44254.47 | 0.208017E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
October | 15853822.81 | 0.258866E+10 | 0.00 | 285475.56 | 83736800.62 | 0.00 | 28240631.57 | 0.00 | 0.42 |
November | 0.235810E+09 | 0.503988E+09 | 0.00 | 1717723.03 | 8737159.48 | 0.00 | 0.309298E+09 | 0.00 | 0.42 |
December | 0.136332E+10 | 660377.71 | 0.00 | 1632927.24 | 0.00 | 19905878.82 | 0.703408E+09 | 0.00 | 0.41 |
Annual Sum or Average | 0.409439E+10 | 0.436135E+11 | 0.00 | 8106986.38 | 0.113438E+10 | 0.380380E+09 | 0.205548E+10 | 0.00 | 0.43 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.162796E+10 | 0.871423E+10 | 0.00 | 2036330.53 | 0.230184E+09 | 0.332920E+09 | 0.703408E+09 | 0.00 | 0.44 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.162124E+10 | 0.00 | 0.00 | 585690.54 | 0.00 | 0.355069E+09 | 0.381497E+09 | 0.00 | 0.42 |
February | 0.696265E+09 | 46434488.69 | 0.00 | 1971818.83 | 114314.39 | 31935653.14 | 0.447964E+09 | 0.00 | 0.42 |
March | 0.154468E+09 | 0.965619E+09 | 0.00 | 1610832.88 | 20460361.36 | 0.00 | 0.150747E+09 | 0.00 | 0.43 |
April | 1306278.67 | 0.294342E+10 | 0.00 | 80205.47 | 0.104340E+09 | 0.00 | 2978613.45 | 0.00 | 0.42 |
May | 0.00 | 0.580580E+10 | 0.00 | 35624.55 | 0.136272E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
June | 0.00 | 0.724868E+10 | 0.00 | 0.00 | 0.147040E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
July | 0.00 | 0.841995E+10 | 0.00 | 0.00 | 0.230310E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
August | 0.00 | 0.870485E+10 | 0.00 | 0.00 | 0.197510E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
September | 0.00 | 0.633979E+10 | 0.00 | 44773.23 | 0.207766E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
October | 16640329.10 | 0.258366E+10 | 0.00 | 283870.74 | 83767937.19 | 0.00 | 27849556.43 | 0.00 | 0.42 |
November | 0.237334E+09 | 0.501742E+09 | 0.00 | 1687497.42 | 8747087.17 | 0.00 | 0.308896E+09 | 0.00 | 0.42 |
December | 0.138603E+10 | 631201.04 | 0.00 | 1551571.43 | 0.00 | 27828679.74 | 0.667127E+09 | 0.00 | 0.41 |
Annual Sum or Average | 0.411329E+10 | 0.435606E+11 | 0.00 | 7851885.09 | 0.113633E+10 | 0.414833E+09 | 0.198706E+10 | 0.00 | 0.43 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.162124E+10 | 0.870485E+10 | 0.00 | 1971818.83 | 0.230310E+09 | 0.355069E+09 | 0.667127E+09 | 0.00 | 0.44 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.160934E+10 | 0.00 | 0.00 | 490671.14 | 0.00 | 0.394714E+09 | 0.330859E+09 | 0.00 | 0.42 |
February | 0.669613E+09 | 45436511.01 | 0.00 | 1821569.44 | 116247.45 | 62305650.32 | 0.437316E+09 | 0.00 | 0.42 |
March | 0.159037E+09 | 0.958079E+09 | 0.00 | 1530419.84 | 21221726.97 | 0.00 | 0.145225E+09 | 0.00 | 0.43 |
April | 1143421.58 | 0.294237E+10 | 0.00 | 76765.16 | 0.103805E+09 | 0.00 | 3218661.36 | 0.00 | 0.42 |
May | 0.00 | 0.581419E+10 | 0.00 | 35158.28 | 0.133544E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
June | 0.00 | 0.726379E+10 | 0.00 | 0.00 | 0.144271E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
July | 0.00 | 0.845196E+10 | 0.00 | 0.00 | 0.222956E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
August | 0.00 | 0.874250E+10 | 0.00 | 0.00 | 0.187608E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
September | 0.00 | 0.635481E+10 | 0.00 | 44656.72 | 0.207905E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
October | 17161752.33 | 0.258382E+10 | 0.00 | 269439.46 | 83062358.76 | 0.00 | 27983409.75 | 0.00 | 0.42 |
November | 0.245999E+09 | 0.497232E+09 | 0.00 | 1599190.56 | 8761777.17 | 0.00 | 0.300548E+09 | 0.00 | 0.42 |
December | 0.141130E+10 | 571207.20 | 0.00 | 1372900.92 | 0.00 | 64423027.68 | 0.588635E+09 | 0.00 | 0.41 |
Annual Sum or Average | 0.411360E+10 | 0.436548E+11 | 0.00 | 7240771.53 | 0.111325E+10 | 0.521442E+09 | 0.183379E+10 | 0.00 | 0.43 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.160934E+10 | 0.874250E+10 | 0.00 | 1821569.44 | 0.222956E+09 | 0.394714E+09 | 0.588635E+09 | 0.00 | 0.44 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.147145E+10 | 0.00 | 0.00 | 538418.51 | 0.00 | 0.519017E+09 | 0.335301E+09 | 0.00 | 0.42 |
February | 0.595886E+09 | 45110385.58 | 0.00 | 1992634.92 | 106528.61 | 0.117200E+09 | 0.429983E+09 | 0.00 | 0.42 |
March | 0.151564E+09 | 0.955584E+09 | 0.00 | 1675041.67 | 20483005.52 | 0.00 | 0.143743E+09 | 0.00 | 0.43 |
April | 1914445.23 | 0.296298E+10 | 0.00 | 85892.43 | 91025586.09 | 0.00 | 2794210.63 | 0.00 | 0.42 |
May | 0.00 | 0.590099E+10 | 0.00 | 38970.81 | 0.105935E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
June | 0.00 | 0.740742E+10 | 0.00 | 29127.39 | 0.127024E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
July | 0.00 | 0.869253E+10 | 0.00 | 0.00 | 0.192742E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
August | 0.00 | 0.905053E+10 | 0.00 | 0.00 | 0.162693E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
September | 0.00 | 0.658974E+10 | 0.00 | 68055.52 | 0.192278E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
October | 18960086.27 | 0.265263E+10 | 0.00 | 258036.57 | 76871902.02 | 0.00 | 25123560.86 | 0.00 | 0.42 |
November | 0.242852E+09 | 0.501250E+09 | 0.00 | 1733125.62 | 8304412.33 | 0.00 | 0.290056E+09 | 0.00 | 0.42 |
December | 0.128253E+10 | 540089.70 | 0.00 | 1510142.37 | 0.00 | 0.174643E+09 | 0.574959E+09 | 0.00 | 0.41 |
Annual Sum or Average | 0.376516E+10 | 0.447593E+11 | 0.00 | 7929445.80 | 0.977463E+09 | 0.810860E+09 | 0.180196E+10 | 0.00 | 0.43 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.147145E+10 | 0.905053E+10 | 0.00 | 1992634.92 | 0.192742E+09 | 0.519017E+09 | 0.574959E+09 | 0.00 | 0.44 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.148542E+12 | 0.143729E+11 | 0.00 | 0.803368E+11 | 0.103742E+11 |
February | 0.174678E+12 | 0.543299E+10 | 0.00 | 0.464112E+11 | 0.420274E+11 |
March | 0.246390E+12 | -0.780586E+10 | 0.00 | 0.322912E+10 | 0.118819E+12 |
April | 0.284427E+12 | -0.229123E+11 | 0.00 | -0.559159E+11 | 0.202236E+12 |
May | 0.307624E+12 | -0.418147E+11 | 0.00 | -0.114380E+12 | 0.301735E+12 |
June | 0.287280E+12 | -0.494991E+11 | 0.00 | -0.152356E+12 | 0.337561E+12 |
July | 0.235561E+12 | -0.608362E+11 | 0.00 | -0.179807E+12 | 0.368443E+12 |
August | 0.200393E+12 | -0.617309E+11 | 0.00 | -0.177616E+12 | 0.367382E+12 |
September | 0.209471E+12 | -0.467583E+11 | 0.00 | -0.133943E+12 | 0.296616E+12 |
October | 0.202473E+12 | -0.212009E+11 | 0.00 | -0.402886E+11 | 0.194048E+12 |
November | 0.167708E+12 | -0.402814E+10 | 0.00 | 0.288401E+11 | 0.985253E+11 |
December | 0.132422E+12 | 0.121750E+11 | 0.00 | 0.774194E+11 | 0.222570E+11 |
Annual Sum or Average | 0.259697E+13 | -0.284606E+12 | 0.00 | -0.618071E+12 | 0.236002E+13 |
Minimum of Months | 0.132422E+12 | -0.617309E+11 | 0.00 | -0.179807E+12 | 0.103742E+11 |
Maximum of Months | 0.307624E+12 | 0.143729E+11 | 0.00 | 0.803368E+11 | 0.368443E+12 |