Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:37
Tabular Output Report in Format: HTML
Building: RetailStripmall
Environment: RUNPERIOD 1 ** International Falls Intl Ap MN USA TMY3 WMO#=727470
Simulation Timestamp: 2023-10-16 08:37:19
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:19
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1841.63 | 881.03 | 881.03 |
Net Site Energy | 1841.63 | 881.03 | 881.03 |
Total Source Energy | 3625.20 | 1734.28 | 1734.28 |
Net Source Energy | 3625.20 | 1734.28 | 1734.28 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 2090.32 |
Net Conditioned Building Area | 2090.32 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 1059.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 47.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 366.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 60.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 128.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 106.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 5.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 67.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 781.98 | 1059.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 1059.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 47.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 366.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 60.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 128.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 106.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 5.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 67.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 1059.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 47.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 366.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 60.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 128.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 106.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 5.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 67.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 204.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 105.91 | 506.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Other | 63.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 374.10 | 506.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 204.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 105.91 | 506.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Other | 63.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 374.10 | 506.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 781.984 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 781.984 | 100.00 |
Total On-Site and Utility Electric Sources | 781.984 | 100.00 |
Total Electricity End Uses | 781.984 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | 0.00 |
Air to Air Heat Recovery for Cooling | 3.95 | 3.62 |
Air to Air Heat Recovery for Heating | 105.19 | 96.38 |
High-Temperature Geothermal* | 0.00 | 0.00 |
Solar Water Thermal | 0.00 | 0.00 |
Solar Air Thermal | 0.00 | 0.00 |
Total On-Site Thermal Sources | 109.13 | 100.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 87.30 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 87.30 | 100.00 |
Total Water End Uses | 87.30 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 9.00 |
Time Setpoint Not Met During Occupied Cooling | 0.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 3318.17 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTRIPMALL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 7
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_INTERNATIONALFALLS
| Environment |ZoneCoolingSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ZoneHeatingSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ZoneElectricSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |SpaceGainsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |PeakSpaceGainsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |SpaceGainComponentsAtCoolingPeakMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ComfortReportSimple55Monthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |OccupantComfortDataSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |DXReportMonthly
| PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL | PSZ-AC_3:3 COOLING COIL | PSZ-AC_4:4 COOLING COIL | PSZ-AC_5:5 COOLING COIL | PSZ-AC_6:6 COOLING COIL | PSZ-AC_7:7 COOLING COIL | PSZ-AC_8:8 COOLING COIL | PSZ-AC_9:9 COOLING COIL | PSZ-AC_10:10 COOLING COIL |WindowReportMonthly
| LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR |WindowEnergyReportMonthly
| LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR |WindowZoneSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |WindowEnergyZoneSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| GAS TANK1 | GAS TANK2 | GAS TANK3 | GAS TANK4 | GAS TANK5 | GAS TANK6 | GAS TANK7 |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC_1:1 HEATING COIL | PSZ-AC_2:2 HEATING COIL | PSZ-AC_3:3 HEATING COIL | PSZ-AC_4:4 HEATING COIL | PSZ-AC_5:5 HEATING COIL | PSZ-AC_6:6 HEATING COIL | PSZ-AC_7:7 HEATING COIL | PSZ-AC_8:8 HEATING COIL | PSZ-AC_9:9 HEATING COIL | PSZ-AC_10:10 HEATING COIL | PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL | PSZ-AC_3:3 COOLING COIL | PSZ-AC_4:4 COOLING COIL | PSZ-AC_5:5 COOLING COIL | PSZ-AC_6:6 COOLING COIL | PSZ-AC_7:7 COOLING COIL | PSZ-AC_8:8 COOLING COIL | PSZ-AC_9:9 COOLING COIL | PSZ-AC_10:10 COOLING COIL |FanReportMonthly
| PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN |ZoneTemperatureOscillationReportMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |MechanicalVentilationLoadsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:19
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:37 |
RunPeriod | RUNPERIOD 1 |
Weather File | International Falls Intl Ap MN USA TMY3 WMO#=727470 |
Latitude [deg] | 48.57 |
Longitude [deg] | -93.4 |
Elevation [m] | 359.00 |
Time Zone | -6.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Above Ground Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Window Opening Area [m2] | 124.40 | 0.00 | 0.00 | 124.40 | 0.00 |
Gross Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Above Ground Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Above Ground Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Window Opening Area [m2] | 124.40 | 0.00 | 0.00 | 124.40 | 0.00 |
Gross Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Above Ground Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Total | |
Gross Roof Area [m2] | 2090.32 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
LGSTORE1 | 348.39 | Yes | Yes | 1805.20 | 1.00 | 276.30 | 0.00 | 20.77 | 20.77 | 15.3022 | 6.19 | 4.3000 |
SMSTORE1 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.38 | 10.38 | 18.2890 | 6.19 | 4.3000 |
SMSTORE2 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 16.6533 | 6.19 | 4.3000 |
SMSTORE3 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 16.6533 | 6.19 | 4.3000 |
SMSTORE4 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 16.6533 | 6.19 | 4.3000 |
LGSTORE2 | 348.39 | Yes | Yes | 1805.20 | 1.00 | 157.89 | 0.00 | 20.72 | 20.72 | 9.5842 | 6.19 | 4.3000 |
SMSTORE5 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 9.6995 | 6.19 | 4.3000 |
SMSTORE6 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 9.6995 | 6.19 | 4.3000 |
SMSTORE7 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 9.6995 | 6.19 | 4.3000 |
SMSTORE8 | 174.19 | Yes | Yes | 902.60 | 1.00 | 197.36 | 0.00 | 10.36 | 10.36 | 9.6995 | 6.19 | 4.3000 |
Total | 2090.32 | 10831.20 | 1184.15 | 0.00 | 124.40 | 124.40 | 13.0683 | 6.19 | 4.3000 | |||
Conditioned Total | 2090.32 | 10831.20 | 1184.15 | 0.00 | 124.40 | 124.40 | 13.0683 | 6.19 | 4.3000 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
LGSTORE1 | 348.39 | Yes | Yes | 1.00 | LGSTORE1 | GENERAL | LGSTORE1 | 15.3022 | 6.19 | 4.3000 | |
SMSTORE1 | 174.19 | Yes | Yes | 1.00 | SMSTORE1 | GENERAL | SMSTORE1 | 18.2890 | 6.19 | 4.3000 | |
SMSTORE2 | 174.19 | Yes | Yes | 1.00 | SMSTORE2 | GENERAL | SMSTORE2 | 16.6533 | 6.19 | 4.3000 | |
SMSTORE3 | 174.19 | Yes | Yes | 1.00 | SMSTORE3 | GENERAL | SMSTORE3 | 16.6533 | 6.19 | 4.3000 | |
SMSTORE4 | 174.19 | Yes | Yes | 1.00 | SMSTORE4 | GENERAL | SMSTORE4 | 16.6533 | 6.19 | 4.3000 | |
LGSTORE2 | 348.39 | Yes | Yes | 1.00 | LGSTORE2 | GENERAL | LGSTORE2 | 9.5842 | 6.19 | 4.3000 | |
SMSTORE5 | 174.19 | Yes | Yes | 1.00 | SMSTORE5 | GENERAL | SMSTORE5 | 9.6995 | 6.19 | 4.3000 | |
SMSTORE6 | 174.19 | Yes | Yes | 1.00 | SMSTORE6 | GENERAL | SMSTORE6 | 9.6995 | 6.19 | 4.3000 | |
SMSTORE7 | 174.19 | Yes | Yes | 1.00 | SMSTORE7 | GENERAL | SMSTORE7 | 9.6995 | 6.19 | 4.3000 | |
SMSTORE8 | 174.19 | Yes | Yes | 1.00 | SMSTORE8 | GENERAL | SMSTORE8 | 9.6995 | 6.19 | 4.3000 | |
Total | 2090.32 | 13.0683 | 3.10 | 4.3000 | |||||||
Conditioned Total | 2090.32 | 13.0683 | 3.10 | 4.3000 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 2090.32 | 2090.32 | 0.00 | 0.00 | 13.0683 | 6.19 | 4.3000 |
Total | 2090.32 | 2090.32 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:19
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 29-JUN-14:50 | 04-JAN-12:09 | - | - | - | - | - | - | - | - | - | - | 06-JAN-13:09 |
Heating | 0.00 | 336891.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 40741.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 23459.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 8059.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 7264.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 345.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 5452.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 85321.93 | 336891.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 336891.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 40741.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 23459.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 8059.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 7264.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 345.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 5452.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:19
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 1148.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 150.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1161.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 191.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 405.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 337.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 17.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 213.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2476.54 | 1148.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 549.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 71.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 555.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 91.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 194.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 161.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 8.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 101.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1184.77 | 549.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 549.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 71.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 555.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 91.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 194.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 161.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 8.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 101.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1184.77 | 549.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:19
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
LGSTORE1 DIRECT AIR | 1.94 |
SMSTORE1 DIRECT AIR | 0.996328 |
SMSTORE2 DIRECT AIR | 0.998362 |
SMSTORE3 DIRECT AIR | 1.03 |
SMSTORE4 DIRECT AIR | 1.02 |
LGSTORE2 DIRECT AIR | 1.82 |
SMSTORE5 DIRECT AIR | 0.977661 |
SMSTORE6 DIRECT AIR | 0.976887 |
SMSTORE7 DIRECT AIR | 0.989752 |
SMSTORE8 DIRECT AIR | 1.18 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC_1:1 | 1.94 | 1.94 | 1.94 | 1.94 | 1.94 | 1.94 | 1.00 | 1.00 | 1.94 |
PSZ-AC_2:2 | 0.996328 | 0.996328 | 0.996328 | 0.996328 | 1.02 | 1.02 | 1.00 | 0.977387 | 1.02 |
PSZ-AC_3:3 | 0.998362 | 0.998362 | 0.998362 | 0.998362 | 1.03 | 1.03 | 1.00 | 0.972716 | 1.03 |
PSZ-AC_4:4 | 1.03 | 1.03 | 1.03 | 1.03 | 1.03 | 1.03 | 1.00 | 1.00 | 1.03 |
PSZ-AC_5:5 | 1.02 | 1.02 | 1.02 | 1.02 | 1.02 | 1.02 | 1.00 | 1.00 | 1.02 |
PSZ-AC_6:6 | 1.82 | 1.82 | 1.82 | 1.82 | 1.82 | 1.82 | 1.00 | 1.00 | 1.82 |
PSZ-AC_7:7 | 0.977661 | 0.977661 | 0.977661 | 0.977661 | 0.977661 | 0.977661 | 1.00 | 1.00 | 0.977661 |
PSZ-AC_8:8 | 0.976887 | 0.976887 | 0.976887 | 0.976887 | 0.976887 | 0.976887 | 1.00 | 1.00 | 0.976887 |
PSZ-AC_9:9 | 0.989752 | 0.989752 | 0.989752 | 0.989752 | 0.989752 | 0.989752 | 1.00 | 1.00 | 0.989752 |
PSZ-AC_10:10 | 1.18 | 1.18 | 1.18 | 1.18 | 1.18 | 1.18 | 1.00 | 1.00 | 1.18 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC_1:1_OA_CONTROLLER | 1.94 | 0.411479 |
PSZ-AC_2:2_OA_CONTROLLER | 1.02 | 0.205739 |
PSZ-AC_3:3_OA_CONTROLLER | 1.03 | 0.205739 |
PSZ-AC_4:4_OA_CONTROLLER | 1.03 | 0.205739 |
PSZ-AC_5:5_OA_CONTROLLER | 1.02 | 0.205739 |
PSZ-AC_6:6_OA_CONTROLLER | 1.82 | 0.411479 |
PSZ-AC_7:7_OA_CONTROLLER | 0.977661 | 0.205739 |
PSZ-AC_8:8_OA_CONTROLLER | 0.976887 | 0.205739 |
PSZ-AC_9:9_OA_CONTROLLER | 0.989752 | 0.205739 |
PSZ-AC_10:10_OA_CONTROLLER | 1.18 | 0.205739 |
Design Size Nominal Supply Air Flow Rate [m3/s] | |
PSZ-AC_1:1 OA HEAT RECOVERY | 0.411479 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | 1.94 | 2080.36 |
PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | 1.02 | 1128.61 |
PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | 1.03 | 1136.35 |
PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | 1.03 | 1140.44 |
PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | 1.02 | 1128.70 |
PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | 1.82 | 1943.92 |
PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | 0.977661 | 1082.43 |
PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | 0.976887 | 1081.57 |
PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | 0.989752 | 1095.81 |
PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | 1.18 | 1308.55 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC_1:1_UNITARY_PACKAGE_DX | 1.94 | 1.94 | 1.94 | 1.28 | 40281.95 | 68267.32 | 40.00 | 1.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_DX | 1.02 | 1.02 | 1.02 | 0.672790 | 20699.19 | 34664.72 | 40.00 | 1.00 |
PSZ-AC_3:3_UNITARY_PACKAGE_DX | 1.03 | 1.03 | 1.03 | 0.677402 | 20809.70 | 34709.29 | 40.00 | 1.00 |
PSZ-AC_4:4_UNITARY_PACKAGE_DX | 1.03 | 1.03 | 1.03 | 0.679840 | 20868.24 | 35403.76 | 40.00 | 1.00 |
PSZ-AC_5:5_UNITARY_PACKAGE_DX | 1.02 | 1.02 | 1.02 | 0.672839 | 20700.74 | 35171.36 | 40.00 | 1.00 |
PSZ-AC_6:6_UNITARY_PACKAGE_DX | 1.82 | 1.82 | 1.82 | 1.20 | 37880.32 | 65473.01 | 40.00 | 1.00 |
PSZ-AC_7:7_UNITARY_PACKAGE_DX | 0.977661 | 0.977661 | 0.977661 | 0.645256 | 20324.37 | 34255.70 | 40.00 | 1.00 |
PSZ-AC_8:8_UNITARY_PACKAGE_DX | 0.976887 | 0.976887 | 0.976887 | 0.644745 | 20345.29 | 34238.74 | 40.00 | 1.00 |
PSZ-AC_9:9_UNITARY_PACKAGE_DX | 0.989752 | 0.989752 | 0.989752 | 0.653236 | 20659.84 | 34520.58 | 40.00 | 1.00 |
PSZ-AC_10:10_UNITARY_PACKAGE_DX | 1.18 | 1.18 | 1.18 | 0.780054 | 24611.20 | 38731.23 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-AC_1:1 COOLING COIL | 1.94 | 0.972088 | 1.30 | 40281.95 | 20140.97 | 0.762740 | 0.762740 |
PSZ-AC_2:2 COOLING COIL | 1.02 | 0.509689 | 0.679587 | 20699.19 | 10349.59 | 0.770720 | 0.770720 |
PSZ-AC_3:3 COOLING COIL | 1.03 | 0.513183 | 0.684247 | 20809.70 | 10404.85 | 0.771170 | 0.771170 |
PSZ-AC_4:4 COOLING COIL | 1.03 | 0.515030 | 0.686707 | 20868.24 | 10434.12 | 0.771410 | 0.771410 |
PSZ-AC_5:5 COOLING COIL | 1.02 | 0.509726 | 0.679633 | 20700.74 | 10350.37 | 0.770720 | 0.770720 |
PSZ-AC_6:6 COOLING COIL | 1.82 | 0.908334 | 1.21 | 37880.32 | 18940.16 | 0.759870 | 0.759870 |
PSZ-AC_7:7 COOLING COIL | 0.977660 | 0.488831 | 0.651773 | 20324.37 | 10162.18 | 0.761750 | 0.761750 |
PSZ-AC_8:8 COOLING COIL | 0.976890 | 0.488444 | 0.651260 | 20345.29 | 10172.65 | 0.760220 | 0.760220 |
PSZ-AC_9:9 COOLING COIL | 0.989750 | 0.494876 | 0.659833 | 20659.84 | 10329.92 | 0.759560 | 0.759560 |
PSZ-AC_10:10 COOLING COIL | 1.18 | 0.590950 | 0.787933 | 24611.20 | 12305.60 | 0.760270 | 0.760270 |
Design Size Nominal Capacity [W] | |
PSZ-AC_1:1 HEATING COIL | 68267.32 |
PSZ-AC_2:2 HEATING COIL | 34664.72 |
PSZ-AC_3:3 HEATING COIL | 34709.29 |
PSZ-AC_4:4 HEATING COIL | 35403.76 |
PSZ-AC_5:5 HEATING COIL | 35171.36 |
PSZ-AC_6:6 HEATING COIL | 65473.01 |
PSZ-AC_7:7 HEATING COIL | 34255.70 |
PSZ-AC_8:8 HEATING COIL | 34238.74 |
PSZ-AC_9:9 HEATING COIL | 34520.58 |
PSZ-AC_10:10 HEATING COIL | 38731.23 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:19
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
LGSTORE1_WALL_3 | LGSTORE1_WALL_3_DOOR_1 | LGSTORE1_WALL_3_DOOR_2 | |
LGSTORE1_WALL_1 | LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | |
SMSTORE1_WALL_1 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | |
SMSTORE1_WALL_3 | SMSTORE1_WALL_3_DOOR | |
SMSTORE2_WALL_1 | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | |
SMSTORE2_WALL_3 | SMSTORE2_WALL_3_DOOR | |
SMSTORE3_WALL_1 | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | |
SMSTORE3_WALL_3 | SMSTORE3_WALL_3_DOOR | |
SMSTORE4_WALL_1 | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | |
SMSTORE4_WALL_3 | SMSTORE4_WALL_3_DOOR | |
LGSTORE2_WALL_3 | LGSTORE2_WALL_3_DOOR_1 | LGSTORE2_WALL_3_DOOR_2 | |
LGSTORE2_WALL_1 | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | |
SMSTORE5_WALL_1 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | |
SMSTORE5_WALL_3 | SMSTORE5_WALL_3_DOOR | |
SMSTORE6_WALL_1 | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | |
SMSTORE6_WALL_3 | SMSTORE6_WALL_3_DOOR | |
SMSTORE7_WALL_1 | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | |
SMSTORE7_WALL_3 | SMSTORE7_WALL_3_DOOR | |
SMSTORE8_WALL_1 | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR | |
SMSTORE8_WALL_3 | SMSTORE8_WALL_3_DOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:19
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:19
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 5.40 | -2.00 | -14.60 | -16.90 | -11.50 | -6.20 | 4.00 | 13.40 | 18.00 | 19.70 | 17.90 | 12.30 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | International Falls Intl Ap MN USA TMY3 WMO#=727470 | 48.57 | -93.40 | -6.00 | 359.00 | 97086 | 1.1539 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 3.29 | 36.60 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RetailStripmall | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 10 | 118 | 48 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | LGSTORE1 | 0.0 | 0.00 | 0.00 | 0.00 | 7.62 | 11.43 | 2.59 | 1 | 1 | 1 | 0.00 | 15.24 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 1805.20 | TARP | TARP | 348.39 | 276.30 | 247.74 | 20.77 | 6 | 8 | 0 | Yes |
2 | SMSTORE1 | 0.0 | 0.00 | 0.00 | 0.00 | 19.05 | 11.43 | 2.59 | 1 | 1 | 1 | 15.24 | 22.86 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.66 | 10.38 | 6 | 4 | 0 | Yes |
3 | SMSTORE2 | 0.0 | 0.00 | 0.00 | 0.00 | 26.67 | 11.43 | 2.59 | 1 | 1 | 1 | 22.86 | 30.48 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
4 | SMSTORE3 | 0.0 | 0.00 | 0.00 | 0.00 | 34.29 | 11.43 | 2.59 | 1 | 1 | 1 | 30.48 | 38.10 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
5 | SMSTORE4 | 0.0 | 0.00 | 0.00 | 0.00 | 41.91 | 11.43 | 2.59 | 1 | 1 | 1 | 38.10 | 45.72 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
6 | LGSTORE2 | 0.0 | 0.00 | 0.00 | 0.00 | 53.34 | 11.43 | 2.59 | 1 | 1 | 1 | 45.72 | 60.96 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 1805.20 | TARP | TARP | 348.39 | 157.89 | 129.41 | 20.72 | 6 | 8 | 0 | Yes |
7 | SMSTORE5 | 0.0 | 0.00 | 0.00 | 0.00 | 64.77 | 11.43 | 2.59 | 1 | 1 | 1 | 60.96 | 68.58 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
8 | SMSTORE6 | 0.0 | 0.00 | 0.00 | 0.00 | 72.39 | 11.43 | 2.59 | 1 | 1 | 1 | 68.58 | 76.20 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
9 | SMSTORE7 | 0.0 | 0.00 | 0.00 | 0.00 | 80.01 | 11.43 | 2.59 | 1 | 1 | 1 | 76.20 | 83.82 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
10 | SMSTORE8 | 0.0 | 0.00 | 0.00 | 0.00 | 87.63 | 11.43 | 2.59 | 1 | 1 | 1 | 83.82 | 91.44 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 197.36 | 183.12 | 10.36 | 6 | 4 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | LGSTORE1 | 348.39 | 56.3 | 6.193 | 0.161 | 15.302 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 19.602 | No |
2 | SMSTORE1 | 174.19 | 28.1 | 6.194 | 0.161 | 18.289 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 22.589 | No |
3 | SMSTORE2 | 174.19 | 28.1 | 6.194 | 0.161 | 16.653 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 20.953 | No |
4 | SMSTORE3 | 174.19 | 28.1 | 6.194 | 0.161 | 16.653 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 20.953 | No |
5 | SMSTORE4 | 174.19 | 28.1 | 6.194 | 0.161 | 16.653 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 20.953 | No |
6 | LGSTORE2 | 348.39 | 56.3 | 6.193 | 0.161 | 9.584 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 13.884 | No |
7 | SMSTORE5 | 174.19 | 28.1 | 6.194 | 0.161 | 9.699 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 13.999 | No |
8 | SMSTORE6 | 174.19 | 28.1 | 6.194 | 0.161 | 9.699 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 13.999 | No |
9 | SMSTORE7 | 174.19 | 28.1 | 6.194 | 0.161 | 9.699 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 13.999 | No |
10 | SMSTORE8 | 174.19 | 28.1 | 6.194 | 0.161 | 9.699 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 13.999 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | LGSTORE1 | TYPE1_OCC_SCH | LGSTORE1 | 348.39 | 56.3 | 56.3 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 56 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | SMSTORE1 | TYPE1_OCC_SCH | SMSTORE1 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | SMSTORE2 | TYPE2_OCC_SCH | SMSTORE2 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | SMSTORE3 | TYPE2_OCC_SCH | SMSTORE3 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | SMSTORE4 | TYPE2_OCC_SCH | SMSTORE4 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | LGSTORE2 | TYPE3_OCC_SCH | LGSTORE2 | 348.39 | 56.3 | 56.3 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 56 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | SMSTORE5 | TYPE3_OCC_SCH | SMSTORE5 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | SMSTORE6 | TYPE3_OCC_SCH | SMSTORE6 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | SMSTORE7 | TYPE3_OCC_SCH | SMSTORE7 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | SMSTORE8 | TYPE3_OCC_SCH | SMSTORE8 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | LGSTORE1_LIGHTS | LTG_SCH_BASE_LPD1 | LGSTORE1 | 348.39 | 56.3 | 3346.345 | 9.605 | 59.490 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3346.345 |
2 | LGSTORE1_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | LGSTORE1 | 348.39 | 56.3 | 1984.726 | 5.697 | 35.284 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1984.726 |
3 | SMSTORE1_LIGHTS | LTG_SCH_BASE_SMALL_LPD1 | SMSTORE1 | 174.19 | 28.1 | 1693.257 | 9.721 | 60.206 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1693.257 |
4 | SMSTORE1_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | SMSTORE1 | 174.19 | 28.1 | 1492.567 | 8.568 | 53.070 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1492.567 |
5 | SMSTORE2_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE2 | 174.19 | 28.1 | 1689.582 | 9.699 | 60.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1689.582 |
6 | SMSTORE2_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE2 | 174.19 | 28.1 | 1211.319 | 6.954 | 43.070 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1211.319 |
7 | SMSTORE3_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE3 | 174.19 | 28.1 | 1689.582 | 9.699 | 60.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1689.582 |
8 | SMSTORE3_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE3 | 174.19 | 28.1 | 1211.319 | 6.954 | 43.070 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1211.319 |
9 | SMSTORE4_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE4 | 174.19 | 28.1 | 1689.582 | 9.699 | 60.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1689.582 |
10 | SMSTORE4_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE4 | 174.19 | 28.1 | 1211.319 | 6.954 | 43.070 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1211.319 |
11 | LGSTORE2_LIGHTS | LTG_SCH_BASE_LPD2 | LGSTORE2 | 348.39 | 56.3 | 3338.998 | 9.584 | 59.359 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3338.998 |
12 | LGSTORE2_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | LGSTORE2 | 348.39 | 56.3 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
13 | SMSTORE5_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE5 | 174.19 | 28.1 | 1689.582 | 9.699 | 60.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1689.582 |
14 | SMSTORE5_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE5 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
15 | SMSTORE6_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE6 | 174.19 | 28.1 | 1689.582 | 9.699 | 60.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1689.582 |
16 | SMSTORE6_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE6 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
17 | SMSTORE7_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE7 | 174.19 | 28.1 | 1689.582 | 9.699 | 60.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1689.582 |
18 | SMSTORE7_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE7 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
19 | SMSTORE8_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE8 | 174.19 | 28.1 | 1689.582 | 9.699 | 60.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1689.582 |
20 | SMSTORE8_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE8 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LGSTORE1_MISCPLUG_EQUIP | TYPE1_EQUIP_SCH | LGSTORE1 | 348.39 | 56.3 | 1498.062 | 4.300 | 26.632 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1498.062 |
2 | SMSTORE1_MISCPLUG_EQUIP | TYPE1_EQUIP_SCH | SMSTORE1 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
3 | SMSTORE2_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE2 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
4 | SMSTORE3_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE3 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
5 | SMSTORE4_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE4 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
6 | LGSTORE2_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | LGSTORE2 | 348.39 | 56.3 | 1498.062 | 4.300 | 26.632 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1498.062 |
7 | SMSTORE5_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE5 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
8 | SMSTORE6_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE6 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
9 | SMSTORE7_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE7 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
10 | SMSTORE8_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE8 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.1625 | 0.900 | 0.900 | 0.770 | 0.700 | Rough |
5 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 0.5002 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
6 | LGSTORE1_FLOOR_FFACTOR | 36 | 2 | 7 | 0.167 | 0.1381 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
7 | SMSTORE1_FLOOR_FFACTOR | 37 | 2 | 7 | 0.167 | 0.7817E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
8 | SMSTORE2_FLOOR_FFACTOR | 38 | 2 | 7 | 0.167 | 0.7817E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | SMSTORE3_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.7817E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
10 | SMSTORE4_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.7817E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
11 | LGSTORE2_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.7817E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | SMSTORE5_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.7817E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | SMSTORE6_FLOOR_FFACTOR | 43 | 2 | 7 | 0.167 | 0.7817E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | SMSTORE7_FLOOR_FFACTOR | 44 | 2 | 7 | 0.167 | 0.7817E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | SMSTORE8_FLOOR_FFACTOR | 45 | 2 | 7 | 0.167 | 0.1990 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
6 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 6.093 |
7 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
8 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
10 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.765 |
11 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
12 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 7.167 |
13 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
14 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.72 |
15 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
16 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.72 |
17 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
18 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.72 |
19 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
20 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.72 |
21 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
22 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.72 |
23 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
24 | ~FC_Insulation_7 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.72 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_8 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.72 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_9 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.72 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_10 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.947 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
14 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
15 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
16 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
17 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
18 | 3 | -0.63083111E-06 | 0.74112372E-09 | -0.38647046E-05 | 0.15329585E-16 |
19 | 2 | 0.78415922 | 0.99752939E-03 | 1.0633801 | -0.74093433E-06 |
20 | 1 | -22.010056 | 0.66447931E-01 | -6.3131541 | 0.20386814 |
21 | 0 | 21.355302 | 0.61958938E-01 | 5.3791822 | |
22 | 7 | -0.34830148E-12 | 0.72009358E-15 | -0.12050990E-12 | 0.11035014E-15 |
23 | 6 | 0.31919265E-07 | 0.14494330E-09 | 0.72848987E-08 | -0.15272991E-12 |
24 | 5 | -0.20646226E-03 | 0.12163433E-05 | -0.10595611E-03 | 0.71905312E-08 |
25 | 4 | 0.31108415 | 0.58168425E-03 | 0.10650364 | -0.36263669E-04 |
26 | 3 | -7.6409054 | 0.17741268E-01 | -2.4500961 | 0.30845998E-01 |
27 | 2 | 42.105983 | 0.62198429E-01 | 15.720002 | -0.34709621 |
28 | 1 | -81.491490 | 0.27724269E-01 | -29.549212 | 1.0987734 |
29 | 0 | 46.824333 | 0.55101924E-03 | 16.281706 | |
30 | 7 | -0.30768122E-08 | -0.20915384E-14 | 0.14239733E-14 | -0.43231278E-16 |
31 | 6 | 0.39835568E-05 | 0.26399824E-08 | 0.31946650E-02 | -0.26799527E-04 |
32 | 5 | -0.27951707E-03 | 0.15609240E-05 | -0.22399710 | 0.19585557E-02 |
33 | 4 | 0.63843515E-02 | 0.70996553E-04 | 4.8340844 | -0.45308610E-01 |
34 | 3 | -0.55922562E-01 | 0.56414668E-03 | -38.047054 | 0.39893714 |
35 | 2 | 0.19837327 | 0.93792475E-03 | 116.53385 | -1.4186067 |
36 | 1 | -0.28619643 | 0.28546699E-03 | -143.93668 | 2.0495227 |
37 | 0 | 0.13950394 | 0.69324754E-05 | 60.838472 | |
38 | 7 | -0.54670353E-08 | -0.11613337E-13 | 0.14223840E-14 | -0.37368711E-16 |
39 | 6 | 0.25207632E-05 | 0.15026623E-08 | 0.31993138E-02 | -0.26838525E-04 |
40 | 5 | -0.16410687E-03 | 0.88486983E-06 | -0.22426121 | 0.19608870E-02 |
41 | 4 | 0.36607299E-02 | 0.40162528E-04 | 4.8384812 | -0.45350877E-01 |
42 | 3 | -0.31781560E-01 | 0.31856588E-03 | -38.071881 | 0.39921157 |
43 | 2 | 0.11233251 | 0.52874598E-03 | 116.58215 | -1.4192529 |
44 | 1 | -0.16179893 | 0.16057723E-03 | -143.96511 | 2.0499900 |
45 | 0 | 0.78801674E-01 | 0.38948424E-05 | 60.838472 | |
46 | 7 | -0.54670353E-08 | -0.11613337E-13 | 0.14223844E-14 | -0.37368717E-16 |
47 | 6 | 0.25207632E-05 | 0.15026623E-08 | 0.31993138E-02 | -0.26838525E-04 |
48 | 5 | -0.16410687E-03 | 0.88486983E-06 | -0.22426121 | 0.19608870E-02 |
49 | 4 | 0.36607299E-02 | 0.40162528E-04 | 4.8384812 | -0.45350877E-01 |
50 | 3 | -0.31781560E-01 | 0.31856588E-03 | -38.071881 | 0.39921157 |
51 | 2 | 0.11233251 | 0.52874598E-03 | 116.58215 | -1.4192529 |
52 | 1 | -0.16179893 | 0.16057723E-03 | -143.96511 | 2.0499900 |
53 | 0 | 0.78801674E-01 | 0.38948424E-05 | 60.838472 | |
54 | 7 | -0.54670353E-08 | -0.11613337E-13 | 0.14223843E-14 | -0.37368715E-16 |
55 | 6 | 0.25207632E-05 | 0.15026623E-08 | 0.31993138E-02 | -0.26838525E-04 |
56 | 5 | -0.16410687E-03 | 0.88486983E-06 | -0.22426121 | 0.19608870E-02 |
57 | 4 | 0.36607299E-02 | 0.40162528E-04 | 4.8384812 | -0.45350877E-01 |
58 | 3 | -0.31781560E-01 | 0.31856588E-03 | -38.071881 | 0.39921157 |
59 | 2 | 0.11233251 | 0.52874598E-03 | 116.58215 | -1.4192529 |
60 | 1 | -0.16179893 | 0.16057723E-03 | -143.96511 | 2.0499900 |
61 | 0 | 0.78801674E-01 | 0.38948424E-05 | 60.838472 | |
62 | 7 | -0.54670353E-08 | -0.11613337E-13 | 0.14223847E-14 | -0.37368722E-16 |
63 | 6 | 0.25207632E-05 | 0.15026623E-08 | 0.31993138E-02 | -0.26838525E-04 |
64 | 5 | -0.16410687E-03 | 0.88486983E-06 | -0.22426121 | 0.19608870E-02 |
65 | 4 | 0.36607299E-02 | 0.40162528E-04 | 4.8384812 | -0.45350877E-01 |
66 | 3 | -0.31781560E-01 | 0.31856588E-03 | -38.071881 | 0.39921157 |
67 | 2 | 0.11233251 | 0.52874598E-03 | 116.58215 | -1.4192529 |
68 | 1 | -0.16179893 | 0.16057723E-03 | -143.96511 | 2.0499900 |
69 | 0 | 0.78801674E-01 | 0.38948424E-05 | 60.838472 | |
70 | 7 | -0.54670353E-08 | -0.11613337E-13 | 0.14223844E-14 | -0.37368717E-16 |
71 | 6 | 0.25207632E-05 | 0.15026623E-08 | 0.31993138E-02 | -0.26838525E-04 |
72 | 5 | -0.16410687E-03 | 0.88486983E-06 | -0.22426121 | 0.19608870E-02 |
73 | 4 | 0.36607299E-02 | 0.40162528E-04 | 4.8384812 | -0.45350877E-01 |
74 | 3 | -0.31781560E-01 | 0.31856588E-03 | -38.071881 | 0.39921157 |
75 | 2 | 0.11233251 | 0.52874598E-03 | 116.58215 | -1.4192529 |
76 | 1 | -0.16179893 | 0.16057723E-03 | -143.96511 | 2.0499900 |
77 | 0 | 0.78801674E-01 | 0.38948424E-05 | 60.838472 | |
78 | 7 | -0.54670353E-08 | -0.11613337E-13 | 0.14223845E-14 | -0.37368719E-16 |
79 | 6 | 0.25207632E-05 | 0.15026623E-08 | 0.31993138E-02 | -0.26838525E-04 |
80 | 5 | -0.16410687E-03 | 0.88486983E-06 | -0.22426121 | 0.19608870E-02 |
81 | 4 | 0.36607299E-02 | 0.40162528E-04 | 4.8384812 | -0.45350877E-01 |
82 | 3 | -0.31781560E-01 | 0.31856588E-03 | -38.071881 | 0.39921157 |
83 | 2 | 0.11233251 | 0.52874598E-03 | 116.58215 | -1.4192529 |
84 | 1 | -0.16179893 | 0.16057723E-03 | -143.96511 | 2.0499900 |
85 | 0 | 0.78801674E-01 | 0.38948424E-05 | 60.838472 | |
86 | 7 | -0.54670353E-08 | -0.11613337E-13 | 0.14223840E-14 | -0.37368711E-16 |
87 | 6 | 0.25207632E-05 | 0.15026623E-08 | 0.31993138E-02 | -0.26838525E-04 |
88 | 5 | -0.16410687E-03 | 0.88486983E-06 | -0.22426121 | 0.19608870E-02 |
89 | 4 | 0.36607299E-02 | 0.40162528E-04 | 4.8384812 | -0.45350877E-01 |
90 | 3 | -0.31781560E-01 | 0.31856588E-03 | -38.071881 | 0.39921157 |
91 | 2 | 0.11233251 | 0.52874598E-03 | 116.58215 | -1.4192529 |
92 | 1 | -0.16179893 | 0.16057723E-03 | -143.96511 | 2.0499900 |
93 | 0 | 0.78801674E-01 | 0.38948424E-05 | 60.838472 | |
94 | 7 | -0.54670353E-08 | -0.11613337E-13 | 0.14223844E-14 | -0.37368717E-16 |
95 | 6 | 0.25207632E-05 | 0.15026623E-08 | 0.31993138E-02 | -0.26838525E-04 |
96 | 5 | -0.16410687E-03 | 0.88486983E-06 | -0.22426121 | 0.19608870E-02 |
97 | 4 | 0.36607299E-02 | 0.40162528E-04 | 4.8384812 | -0.45350877E-01 |
98 | 3 | -0.31781560E-01 | 0.31856588E-03 | -38.071881 | 0.39921157 |
99 | 2 | 0.11233251 | 0.52874598E-03 | 116.58215 | -1.4192529 |
100 | 1 | -0.16179893 | 0.16057723E-03 | -143.96511 | 2.0499900 |
101 | 0 | 0.78801674E-01 | 0.38948424E-05 | 60.838472 | |
102 | 7 | -0.21207308E-08 | -0.69128065E-15 | 0.45866753E-14 | -0.60902147E-16 |
103 | 6 | 0.56000727E-05 | 0.38109606E-08 | 0.31899011E-02 | -0.26759564E-04 |
104 | 5 | -0.40083884E-03 | 0.22562489E-05 | -0.22372635 | 0.19561660E-02 |
105 | 4 | 0.92084614E-02 | 0.10268861E-03 | 4.8295754 | -0.45265267E-01 |
106 | 3 | -0.80828076E-01 | 0.81646647E-03 | -38.021585 | 0.39865561 |
107 | 2 | 0.28695633 | 0.13581156E-02 | 116.48428 | -1.4179437 |
108 | 1 | -0.41414885 | 0.41367783E-03 | -143.90750 | 2.0490431 |
109 | 0 | 0.20191061 | 0.10030641E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.292_SHGC_0.399 | 35 | 1 | VerySmooth | 1.658 | 1.658 | 1.000 | 0.400 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 4.24832E-002 | 0.31332 | 0.48955 | 0.48955 | 0.43890 | 0.13405 | 0.17050 | 0.00000 | 0.84000 | 0.84000 | 9.91083E-002 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | GAS TANK1 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
2 | WaterHeater:Mixed | GAS TANK2 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
3 | WaterHeater:Mixed | GAS TANK3 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
4 | WaterHeater:Mixed | GAS TANK4 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
5 | WaterHeater:Mixed | GAS TANK5 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
6 | WaterHeater:Mixed | GAS TANK6 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
7 | WaterHeater:Mixed | GAS TANK7 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | LGSTORE1_WALL_2 | 0 | 118.41 | 56.08 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
2 | LGSTORE1_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
3 | LGSTORE1_WALL_3_DOOR_1 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
4 | LGSTORE1_WALL_3_DOOR_2 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
5 | LGSTORE1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
6 | LGSTORE1_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
7 | LGSTORE1_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
8 | LGSTORE1_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
9 | LGSTORE1_WALL_1_WINDOW_3 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
10 | LGSTORE1_WALL_1_WINDOW_4 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
11 | LGSTORE1_WALL_1_DOOR_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 1 | No | No |
12 | LGSTORE1_WALL_1_DOOR_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 1 | No | No |
13 | LGSTORE1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
14 | LGSTORE1_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
15 | LGSTORE1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
16 | SMSTORE1_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
17 | SMSTORE1_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
18 | SMSTORE1_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
19 | SMSTORE1_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
20 | SMSTORE1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
21 | SMSTORE1_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
22 | SMSTORE1_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
23 | SMSTORE1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
24 | SMSTORE1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
25 | SMSTORE1_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
26 | SMSTORE1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
27 | SMSTORE2_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
28 | SMSTORE2_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
29 | SMSTORE2_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
30 | SMSTORE2_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
31 | SMSTORE2_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
32 | SMSTORE2_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
33 | SMSTORE2_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
34 | SMSTORE2_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
35 | SMSTORE2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
36 | SMSTORE2_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
37 | SMSTORE2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
38 | SMSTORE3_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
39 | SMSTORE3_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
40 | SMSTORE3_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
41 | SMSTORE3_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
42 | SMSTORE3_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
43 | SMSTORE3_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
44 | SMSTORE3_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
45 | SMSTORE3_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
46 | SMSTORE3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
47 | SMSTORE3_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
48 | SMSTORE3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
49 | SMSTORE4_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
50 | SMSTORE4_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
51 | SMSTORE4_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
52 | SMSTORE4_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
53 | SMSTORE4_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
54 | SMSTORE4_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 3 | No | No |
55 | SMSTORE4_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
56 | SMSTORE4_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
57 | SMSTORE4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
58 | SMSTORE4_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
59 | SMSTORE4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
60 | LGSTORE2_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
61 | LGSTORE2_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 4 | No | No |
62 | LGSTORE2_WALL_3_DOOR_1 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
63 | LGSTORE2_WALL_3_DOOR_2 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
64 | LGSTORE2_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
65 | LGSTORE2_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 4 | No | No |
66 | LGSTORE2_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
67 | LGSTORE2_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
68 | LGSTORE2_WALL_1_WINDOW_3 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
69 | LGSTORE2_WALL_1_WINDOW_4 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
70 | LGSTORE2_WALL_1_DOOR_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
71 | LGSTORE2_WALL_1_DOOR_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
72 | LGSTORE2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
73 | LGSTORE2_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
74 | LGSTORE2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
75 | SMSTORE5_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
76 | SMSTORE5_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
77 | SMSTORE5_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
78 | SMSTORE5_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
79 | SMSTORE5_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
80 | SMSTORE5_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
81 | SMSTORE5_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
82 | SMSTORE5_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
83 | SMSTORE5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
84 | SMSTORE5_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
85 | SMSTORE5_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
86 | SMSTORE6_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
87 | SMSTORE6_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
88 | SMSTORE6_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
89 | SMSTORE6_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
90 | SMSTORE6_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
91 | SMSTORE6_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
92 | SMSTORE6_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
93 | SMSTORE6_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
94 | SMSTORE6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
95 | SMSTORE6_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
96 | SMSTORE6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
97 | SMSTORE7_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
98 | SMSTORE7_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
99 | SMSTORE7_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
100 | SMSTORE7_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
101 | SMSTORE7_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
102 | SMSTORE7_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 3 | No | No |
103 | SMSTORE7_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
104 | SMSTORE7_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
105 | SMSTORE7_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
106 | SMSTORE7_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
107 | SMSTORE7_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
108 | SMSTORE8_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 4 | No | No |
109 | SMSTORE8_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 2 | No | No |
110 | SMSTORE8_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 2 | No | No |
111 | SMSTORE8_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 1 | No | No |
112 | SMSTORE8_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
113 | SMSTORE8_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 3 | No | No |
114 | SMSTORE8_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
115 | SMSTORE8_WALL_4 | 0 | 118.41 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 3 | No | No |
116 | SMSTORE8_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
117 | SMSTORE8_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
118 | SMSTORE8_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | LGSTORE1_INFILTRATION | TYPE1_INFIL_SCH | LGSTORE1 | 348.39 | 56.3 | 0.157 | 4.517E-004 | 2.488E-004 | 0.314 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | LGSTORE1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LGSTORE1 | 348.39 | 56.3 | 0.241 | 6.922E-004 | 3.813E-004 | 0.481 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | SMSTORE1_INFILTRATION | TYPE1_INFIL_SCH | SMSTORE1 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | SMSTORE1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE1 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | SMSTORE2_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE2 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | SMSTORE2_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE2 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | SMSTORE3_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE3 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | SMSTORE3_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE3 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | SMSTORE4_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE4 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | SMSTORE4_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE4 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | LGSTORE2_INFILTRATION | TYPE3_INFIL_SCH | LGSTORE2 | 348.39 | 56.3 | 8.993E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | LGSTORE2_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LGSTORE2 | 348.39 | 56.3 | 0.241 | 6.922E-004 | 4.692E-004 | 0.481 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | SMSTORE5_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE5 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | SMSTORE5_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE5 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | SMSTORE6_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE6 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | SMSTORE6_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE6 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | SMSTORE7_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE7 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
18 | SMSTORE7_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE7 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | SMSTORE8_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE8 | 174.19 | 28.1 | 0.112 | 6.453E-004 | 2.994E-004 | 0.448 | 0.000 | 0.000 | 0.224 | 0.000 |
20 | SMSTORE8_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE8 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 3.583E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | LGSTORE1 | Mixing/Well-Stirred |
2 | SMSTORE1 | Mixing/Well-Stirred |
3 | SMSTORE2 | Mixing/Well-Stirred |
4 | SMSTORE3 | Mixing/Well-Stirred |
5 | SMSTORE4 | Mixing/Well-Stirred |
6 | LGSTORE2 | Mixing/Well-Stirred |
7 | SMSTORE5 | Mixing/Well-Stirred |
8 | SMSTORE6 | Mixing/Well-Stirred |
9 | SMSTORE7 | Mixing/Well-Stirred |
10 | SMSTORE8 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone LGSTORE1 | 1.2000 |
3 | Zone SMSTORE1 | 1.2000 |
4 | Zone SMSTORE2 | 1.2000 |
5 | Zone SMSTORE3 | 1.2000 |
6 | Zone SMSTORE4 | 1.2000 |
7 | Zone LGSTORE2 | 1.2000 |
8 | Zone SMSTORE5 | 1.2000 |
9 | Zone SMSTORE6 | 1.2000 |
10 | Zone SMSTORE7 | 1.2000 |
11 | Zone SMSTORE8 | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone LGSTORE1 | 1.2000 |
3 | Zone SMSTORE1 | 1.2000 |
4 | Zone SMSTORE2 | 1.2000 |
5 | Zone SMSTORE3 | 1.2000 |
6 | Zone SMSTORE4 | 1.2000 |
7 | Zone LGSTORE2 | 1.2000 |
8 | Zone SMSTORE5 | 1.2000 |
9 | Zone SMSTORE6 | 1.2000 |
10 | Zone SMSTORE7 | 1.2000 |
11 | Zone SMSTORE8 | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | LGSTORE1 | Cooling | 20194.12944 | 24232.95532 | 1.54671 | 1.85605 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 30.10000 | 1.27259E-002 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
2 | LGSTORE1 | Heating | 36021.14502 | 43225.37402 | 1.62015 | 1.94418 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -32.70000 | 1.83376E-004 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
3 | SMSTORE1 | Cooling | 11164.16008 | 13396.99210 | 0.83027 | 0.99633 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 25.38800 | 1.27176E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
4 | SMSTORE1 | Heating | 17436.88449 | 20924.26139 | 0.78427 | 0.94113 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -32.70000 | 1.83376E-004 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
5 | SMSTORE2 | Cooling | 11187.06702 | 13424.48043 | 0.83197 | 0.99836 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 23.28000 | 1.27140E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
6 | SMSTORE2 | Heating | 17575.77898 | 21090.93477 | 0.79052 | 0.94862 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -32.70000 | 1.83376E-004 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
7 | SMSTORE3 | Cooling | 11207.37737 | 13448.85284 | 0.85838 | 1.03006 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 29.99667 | 1.27257E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
8 | SMSTORE3 | Heating | 17637.67840 | 21165.21408 | 0.79330 | 0.95196 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -32.70000 | 1.83376E-004 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
9 | SMSTORE4 | Cooling | 11091.97072 | 13310.36486 | 0.84954 | 1.01945 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 29.99667 | 1.27257E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
10 | SMSTORE4 | Heating | 17775.23358 | 21330.28029 | 0.79949 | 0.95939 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -32.70000 | 1.83376E-004 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
11 | LGSTORE2 | Cooling | 19399.37813 | 23279.25376 | 1.48581 | 1.78297 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 29.99667 | 1.27257E-002 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
12 | LGSTORE2 | Heating | 33657.96123 | 40389.55347 | 1.51389 | 1.81667 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -32.70000 | 1.83376E-004 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
13 | SMSTORE5 | Cooling | 10247.58184 | 12297.09821 | 0.76028 | 0.91234 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 25.38800 | 1.27176E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
14 | SMSTORE5 | Heating | 18113.75772 | 21736.50927 | 0.81472 | 0.97766 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -32.70000 | 1.83376E-004 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
15 | SMSTORE6 | Cooling | 10164.50218 | 12197.40261 | 0.75391 | 0.90469 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 25.38800 | 1.27176E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
16 | SMSTORE6 | Heating | 18099.41372 | 21719.29646 | 0.81407 | 0.97689 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -32.70000 | 1.83376E-004 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
17 | SMSTORE7 | Cooling | 10005.58979 | 12006.70775 | 0.74172 | 0.89007 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 25.38800 | 1.27176E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
18 | SMSTORE7 | Heating | 18337.75332 | 22005.30398 | 0.82479 | 0.98975 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -32.70000 | 1.83376E-004 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
19 | SMSTORE8 | Cooling | 10165.36352 | 12198.43623 | 0.77854 | 0.93424 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | 29.48000 | 1.27248E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
20 | SMSTORE8 | Heating | 21898.63046 | 26278.35655 | 0.98492 | 1.18190 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -32.70000 | 1.83376E-004 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC_1:1 | Cooling | Sensible | 26823.17 | 1.85605 | 1.85605 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-AC_1:1 | Heating | Sensible | 68267.32 | 1.94418 | 1.94418 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
3 | PSZ-AC_2:2 | Cooling | Sensible | 14586.00 | 1.01938 | 1.01938 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-AC_2:2 | Heating | Sensible | 33455.27 | 0.94113 | 0.94113 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
5 | PSZ-AC_3:3 | Cooling | Sensible | 14675.27 | 1.02637 | 1.02637 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
6 | PSZ-AC_3:3 | Heating | Sensible | 33619.52 | 0.94862 | 0.94862 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
7 | PSZ-AC_4:4 | Cooling | Sensible | 14722.01 | 1.03006 | 1.03006 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
8 | PSZ-AC_4:4 | Heating | Sensible | 33692.71 | 0.95196 | 0.95196 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
9 | PSZ-AC_5:5 | Cooling | Sensible | 14585.98 | 1.01945 | 1.01945 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
10 | PSZ-AC_5:5 | Heating | Sensible | 33855.38 | 0.95939 | 0.95939 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
11 | PSZ-AC_6:6 | Cooling | Sensible | 25880.71 | 1.78297 | 1.78297 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
12 | PSZ-AC_6:6 | Heating | Sensible | 65473.01 | 1.81667 | 1.81667 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
13 | PSZ-AC_7:7 | Cooling | Sensible | 13295.32 | 0.92132 | 0.92132 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
14 | PSZ-AC_7:7 | Heating | Sensible | 34255.70 | 0.97766 | 0.97766 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
15 | PSZ-AC_8:8 | Cooling | Sensible | 13202.71 | 0.91419 | 0.91419 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
16 | PSZ-AC_8:8 | Heating | Sensible | 34238.74 | 0.97689 | 0.97689 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
17 | PSZ-AC_9:9 | Cooling | Sensible | 13089.11 | 0.90298 | 0.90298 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
18 | PSZ-AC_9:9 | Heating | Sensible | 34520.58 | 0.98975 | 0.98975 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
19 | PSZ-AC_10:10 | Cooling | Sensible | 13395.32 | 0.93424 | 0.93424 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
20 | PSZ-AC_10:10 | Heating | Sensible | 38731.23 | 1.18190 | 1.18190 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | LGSTORE1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.94418 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.99633 |
3 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.99836 |
4 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.03006 |
5 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE4 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.01945 |
6 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | LGSTORE2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.81667 |
7 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE5 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.97766 |
8 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.97689 |
9 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE7 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.98975 |
10 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE8 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.18190 |
11 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.94418 |
12 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.94418 |
13 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.94418 |
14 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.94418 |
15 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.94418 |
16 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Main Design Air Flow Rate [m3/s] | 1.94418 |
17 | AirLoopHVAC | PSZ-AC_1:1 | User Heating Air Flow Ratio [] | 1.00000 |
18 | AirLoopHVAC | PSZ-AC_1:1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
19 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.99633 |
20 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.99633 |
21 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.99633 |
22 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.99633 |
23 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.01938 |
24 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Main Design Air Flow Rate [m3/s] | 1.01938 |
25 | AirLoopHVAC | PSZ-AC_2:2 | User Heating Air Flow Ratio [] | 1.00000 |
26 | AirLoopHVAC | PSZ-AC_2:2 | Calculated Heating Air Flow Ratio [] | 0.97739 |
27 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.99836 |
28 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.99836 |
29 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.99836 |
30 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.99836 |
31 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.02637 |
32 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Main Design Air Flow Rate [m3/s] | 1.02637 |
33 | AirLoopHVAC | PSZ-AC_3:3 | User Heating Air Flow Ratio [] | 1.00000 |
34 | AirLoopHVAC | PSZ-AC_3:3 | Calculated Heating Air Flow Ratio [] | 0.97272 |
35 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.03006 |
36 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.03006 |
37 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.03006 |
38 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.03006 |
39 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.03006 |
40 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Main Design Air Flow Rate [m3/s] | 1.03006 |
41 | AirLoopHVAC | PSZ-AC_4:4 | User Heating Air Flow Ratio [] | 1.00000 |
42 | AirLoopHVAC | PSZ-AC_4:4 | Calculated Heating Air Flow Ratio [] | 1.00000 |
43 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.01945 |
44 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.01945 |
45 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.01945 |
46 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.01945 |
47 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.01945 |
48 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Main Design Air Flow Rate [m3/s] | 1.01945 |
49 | AirLoopHVAC | PSZ-AC_5:5 | User Heating Air Flow Ratio [] | 1.00000 |
50 | AirLoopHVAC | PSZ-AC_5:5 | Calculated Heating Air Flow Ratio [] | 1.00000 |
51 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.81667 |
52 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.81667 |
53 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.81667 |
54 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.81667 |
55 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.81667 |
56 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Main Design Air Flow Rate [m3/s] | 1.81667 |
57 | AirLoopHVAC | PSZ-AC_6:6 | User Heating Air Flow Ratio [] | 1.00000 |
58 | AirLoopHVAC | PSZ-AC_6:6 | Calculated Heating Air Flow Ratio [] | 1.00000 |
59 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.97766 |
60 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.97766 |
61 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.97766 |
62 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.97766 |
63 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.97766 |
64 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Main Design Air Flow Rate [m3/s] | 0.97766 |
65 | AirLoopHVAC | PSZ-AC_7:7 | User Heating Air Flow Ratio [] | 1.00000 |
66 | AirLoopHVAC | PSZ-AC_7:7 | Calculated Heating Air Flow Ratio [] | 1.00000 |
67 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.97689 |
68 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.97689 |
69 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.97689 |
70 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.97689 |
71 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.97689 |
72 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Main Design Air Flow Rate [m3/s] | 0.97689 |
73 | AirLoopHVAC | PSZ-AC_8:8 | User Heating Air Flow Ratio [] | 1.00000 |
74 | AirLoopHVAC | PSZ-AC_8:8 | Calculated Heating Air Flow Ratio [] | 1.00000 |
75 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.98975 |
76 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.98975 |
77 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.98975 |
78 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.98975 |
79 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.98975 |
80 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Main Design Air Flow Rate [m3/s] | 0.98975 |
81 | AirLoopHVAC | PSZ-AC_9:9 | User Heating Air Flow Ratio [] | 1.00000 |
82 | AirLoopHVAC | PSZ-AC_9:9 | Calculated Heating Air Flow Ratio [] | 1.00000 |
83 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.18190 |
84 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.18190 |
85 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.18190 |
86 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.18190 |
87 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.18190 |
88 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Main Design Air Flow Rate [m3/s] | 1.18190 |
89 | AirLoopHVAC | PSZ-AC_10:10 | User Heating Air Flow Ratio [] | 1.00000 |
90 | AirLoopHVAC | PSZ-AC_10:10 | Calculated Heating Air Flow Ratio [] | 1.00000 |
91 | AirLoopHVAC | PSZ-AC_1:1 | Design Supply Air Flow Rate [m3/s] | 1.94418 |
92 | AirLoopHVAC | PSZ-AC_2:2 | Design Supply Air Flow Rate [m3/s] | 1.01938 |
93 | AirLoopHVAC | PSZ-AC_3:3 | Design Supply Air Flow Rate [m3/s] | 1.02637 |
94 | AirLoopHVAC | PSZ-AC_4:4 | Design Supply Air Flow Rate [m3/s] | 1.03006 |
95 | AirLoopHVAC | PSZ-AC_5:5 | Design Supply Air Flow Rate [m3/s] | 1.01945 |
96 | AirLoopHVAC | PSZ-AC_6:6 | Design Supply Air Flow Rate [m3/s] | 1.81667 |
97 | AirLoopHVAC | PSZ-AC_7:7 | Design Supply Air Flow Rate [m3/s] | 0.97766 |
98 | AirLoopHVAC | PSZ-AC_8:8 | Design Supply Air Flow Rate [m3/s] | 0.97689 |
99 | AirLoopHVAC | PSZ-AC_9:9 | Design Supply Air Flow Rate [m3/s] | 0.98975 |
100 | AirLoopHVAC | PSZ-AC_10:10 | Design Supply Air Flow Rate [m3/s] | 1.18190 |
101 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.94418 |
102 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41148 |
103 | HeatExchanger:AirToAir:SensibleAndLatent | PSZ-AC_1:1 OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 0.41148 |
104 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.94418 |
105 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 2080.36090 |
106 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.94418 |
107 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.94418 |
108 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.94418 |
109 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.28316 |
110 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.94418 |
111 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.97209 |
112 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.29612 |
113 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 40281.95000 |
114 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 20140.97500 |
115 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.76274 |
116 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.76274 |
117 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 40281.95000 |
118 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 68267.32274 |
119 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
120 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
121 | Coil:Heating:Fuel | PSZ-AC_1:1 HEATING COIL | Design Size Nominal Capacity [W] | 68267.32274 |
122 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.01938 |
123 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
124 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.01938 |
125 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1128.61386 |
126 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.01938 |
127 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.01938 |
128 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.01938 |
129 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.67279 |
130 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.01938 |
131 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.50969 |
132 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.67959 |
133 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 20699.19000 |
134 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 10349.59500 |
135 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.77072 |
136 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.77072 |
137 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 20699.19000 |
138 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 34664.71573 |
139 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
140 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
141 | Coil:Heating:Fuel | PSZ-AC_2:2 HEATING COIL | Design Size Nominal Capacity [W] | 34664.71573 |
142 | Controller:OutdoorAir | PSZ-AC_3:3_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.02637 |
143 | Controller:OutdoorAir | PSZ-AC_3:3_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
144 | Fan:SystemModel | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.02637 |
145 | Fan:SystemModel | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1136.35006 |
146 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.02637 |
147 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.02637 |
148 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.02637 |
149 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.67740 |
150 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.02637 |
151 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.51318 |
152 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.68425 |
153 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 20809.70000 |
154 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 10404.85000 |
155 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.77117 |
156 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.77117 |
157 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 20809.70000 |
158 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 34709.28886 |
159 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
160 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
161 | Coil:Heating:Fuel | PSZ-AC_3:3 HEATING COIL | Design Size Nominal Capacity [W] | 34709.28886 |
162 | Controller:OutdoorAir | PSZ-AC_4:4_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.03006 |
163 | Controller:OutdoorAir | PSZ-AC_4:4_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
164 | Fan:SystemModel | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.03006 |
165 | Fan:SystemModel | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1140.44000 |
166 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.03006 |
167 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.03006 |
168 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.03006 |
169 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.67984 |
170 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.03006 |
171 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.51503 |
172 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.68671 |
173 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 20868.24000 |
174 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 10434.12000 |
175 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.77141 |
176 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.77141 |
177 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 20868.24000 |
178 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 35403.76450 |
179 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
180 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
181 | Coil:Heating:Fuel | PSZ-AC_4:4 HEATING COIL | Design Size Nominal Capacity [W] | 35403.76450 |
182 | Controller:OutdoorAir | PSZ-AC_5:5_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.01945 |
183 | Controller:OutdoorAir | PSZ-AC_5:5_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
184 | Fan:SystemModel | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.01945 |
185 | Fan:SystemModel | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1128.69613 |
186 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.01945 |
187 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.01945 |
188 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.01945 |
189 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.67284 |
190 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.01945 |
191 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.50973 |
192 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.67963 |
193 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 20700.74000 |
194 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 10350.37000 |
195 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.77072 |
196 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.77072 |
197 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 20700.74000 |
198 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 35171.35966 |
199 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
200 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
201 | Coil:Heating:Fuel | PSZ-AC_5:5 HEATING COIL | Design Size Nominal Capacity [W] | 35171.35966 |
202 | Controller:OutdoorAir | PSZ-AC_6:6_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.81667 |
203 | Controller:OutdoorAir | PSZ-AC_6:6_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41148 |
204 | Fan:SystemModel | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.81667 |
205 | Fan:SystemModel | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1943.92045 |
206 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.81667 |
207 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.81667 |
208 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.81667 |
209 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.19900 |
210 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.81667 |
211 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.90833 |
212 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.21111 |
213 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 37880.32000 |
214 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 18940.16000 |
215 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.75987 |
216 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.75987 |
217 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 37880.32000 |
218 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 65473.00807 |
219 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
220 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
221 | Coil:Heating:Fuel | PSZ-AC_6:6 HEATING COIL | Design Size Nominal Capacity [W] | 65473.00807 |
222 | Controller:OutdoorAir | PSZ-AC_7:7_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.97766 |
223 | Controller:OutdoorAir | PSZ-AC_7:7_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
224 | Fan:SystemModel | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.97766 |
225 | Fan:SystemModel | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1082.42622 |
226 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.97766 |
227 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.97766 |
228 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.97766 |
229 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.64526 |
230 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.97766 |
231 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.48883 |
232 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.65177 |
233 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 20324.37000 |
234 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 10162.18500 |
235 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.76175 |
236 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.76175 |
237 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 20324.37000 |
238 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 34255.70002 |
239 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
240 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
241 | Coil:Heating:Fuel | PSZ-AC_7:7 HEATING COIL | Design Size Nominal Capacity [W] | 34255.70002 |
242 | Controller:OutdoorAir | PSZ-AC_8:8_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.97689 |
243 | Controller:OutdoorAir | PSZ-AC_8:8_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
244 | Fan:SystemModel | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.97689 |
245 | Fan:SystemModel | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1081.56905 |
246 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.97689 |
247 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.97689 |
248 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.97689 |
249 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.64475 |
250 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.97689 |
251 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.48844 |
252 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.65126 |
253 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 20345.29000 |
254 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 10172.64500 |
255 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.76022 |
256 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.76022 |
257 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 20345.29000 |
258 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 34238.73795 |
259 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
260 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
261 | Coil:Heating:Fuel | PSZ-AC_8:8 HEATING COIL | Design Size Nominal Capacity [W] | 34238.73795 |
262 | Controller:OutdoorAir | PSZ-AC_9:9_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.98975 |
263 | Controller:OutdoorAir | PSZ-AC_9:9_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
264 | Fan:SystemModel | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.98975 |
265 | Fan:SystemModel | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1095.81204 |
266 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.98975 |
267 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.98975 |
268 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.98975 |
269 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.65324 |
270 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.98975 |
271 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.49488 |
272 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.65983 |
273 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 20659.84000 |
274 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 10329.92000 |
275 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.75956 |
276 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.75956 |
277 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 20659.84000 |
278 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 34520.58172 |
279 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
280 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
281 | Coil:Heating:Fuel | PSZ-AC_9:9 HEATING COIL | Design Size Nominal Capacity [W] | 34520.58172 |
282 | Controller:OutdoorAir | PSZ-AC_10:10_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.18190 |
283 | Controller:OutdoorAir | PSZ-AC_10:10_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
284 | Fan:SystemModel | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.18190 |
285 | Fan:SystemModel | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1308.55144 |
286 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.18190 |
287 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.18190 |
288 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.18190 |
289 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.78005 |
290 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.18190 |
291 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.59095 |
292 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.78793 |
293 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 24611.20000 |
294 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 12305.60000 |
295 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.76027 |
296 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.76027 |
297 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 24611.20000 |
298 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 38731.22789 |
299 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
300 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
301 | Coil:Heating:Fuel | PSZ-AC_10:10 HEATING COIL | Design Size Nominal Capacity [W] | 38731.22789 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | 38753.2 | 11.43 | 11.43 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | 19897.9 | 11.56 | 11.56 | |||
3 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | 20002.9 | 11.56 | 11.56 | |||
4 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | 20058.6 | 11.56 | 11.56 | |||
5 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | 19899.4 | 11.56 | 11.56 | |||
6 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | 36451.7 | 11.62 | 11.62 | |||
7 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | 19555.6 | 11.61 | 11.61 | |||
8 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | 19577.1 | 11.61 | 11.61 | |||
9 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | 19881.5 | 11.62 | 11.62 | |||
10 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | 23681.8 | 11.61 | 11.61 |
Zone Name | # Surfaces | |
1 | LGSTORE1 | 15 |
2 | SMSTORE1 | 11 |
3 | SMSTORE2 | 11 |
4 | SMSTORE3 | 11 |
5 | SMSTORE4 | 11 |
6 | LGSTORE2 | 15 |
7 | SMSTORE5 | 11 |
8 | SMSTORE6 | 11 |
9 | SMSTORE7 | 11 |
10 | SMSTORE8 | 11 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | LGSTORE1_WALL_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.500 | 0.465 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | LGSTORE1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.500 | 0.465 | 71.15 | 78.94 | 71.15 | 0.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | LGSTORE1_WALL_3_DOOR_1 | Door | LGSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
4 | LGSTORE1_WALL_3_DOOR_2 | Door | LGSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
5 | LGSTORE1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
6 | LGSTORE1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.500 | 0.465 | 58.18 | 78.94 | 58.18 | 180.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
7 | LGSTORE1_WALL_1_WINDOW_1 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.292_SHGC_0.399 | N/A | 1.658 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
8 | LGSTORE1_WALL_1_WINDOW_2 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.292_SHGC_0.399 | N/A | 1.658 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
9 | LGSTORE1_WALL_1_WINDOW_3 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.292_SHGC_0.399 | N/A | 1.658 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
10 | LGSTORE1_WALL_1_WINDOW_4 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.292_SHGC_0.399 | N/A | 1.658 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
11 | LGSTORE1_WALL_1_DOOR_1 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.292_SHGC_0.399 | N/A | 1.658 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
12 | LGSTORE1_WALL_1_DOOR_2 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.292_SHGC_0.399 | N/A | 1.658 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
13 | LGSTORE1_FLOOR | Floor | CTF - ConductionTransferFunction | LGSTORE1_FLOOR_FFACTOR | 0.138 | 0.134 | 348.39 | 348.39 | 348.39 | 270.00 | 180.00 | 22.86 | 15.24 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | LGSTORE1_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.163 | 0.158 | 348.39 | 348.39 | 348.39 | 270.00 | 0.00 | 22.86 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
15 | LGSTORE1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 696.77 | 696.77 | 696.77 | 0.00 | 90.00 | 696.77 | 1.00 | 0.00 | LGSTORE1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
16 | SMSTORE1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.500 | 0.465 | 29.09 | 39.47 | 29.09 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
17 | SMSTORE1_WALL_1_WINDOW_1 | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.292_SHGC_0.399 | N/A | 1.658 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
18 | SMSTORE1_WALL_1_WINDOW_2 | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.292_SHGC_0.399 | N/A | 1.658 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
19 | SMSTORE1_WALL_1_DOOR | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.292_SHGC_0.399 | N/A | 1.658 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
20 | SMSTORE1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | SMSTORE1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.500 | 0.465 | 35.57 | 39.47 | 35.57 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | SMSTORE1_WALL_3_DOOR | Door | SMSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
23 | SMSTORE1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE2_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | SMSTORE1_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE1_FLOOR_FFACTOR | 7.817E-002 | 7.671E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | SMSTORE1_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.163 | 0.158 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
26 | SMSTORE1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
27 | SMSTORE2_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.500 | 0.465 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | SMSTORE2_WALL_1_WINDOW_1 | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.292_SHGC_0.399 | N/A | 1.658 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
29 | SMSTORE2_WALL_1_WINDOW_2 | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.292_SHGC_0.399 | N/A | 1.658 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
30 | SMSTORE2_WALL_1_DOOR | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.292_SHGC_0.399 | N/A | 1.658 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
31 | SMSTORE2_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | SMSTORE2_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.500 | 0.465 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | SMSTORE2_WALL_3_DOOR | Door | SMSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
34 | SMSTORE2_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE3_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | SMSTORE2_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE2_FLOOR_FFACTOR | 7.817E-002 | 7.671E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | SMSTORE2_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.163 | 0.158 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | SMSTORE2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | SMSTORE3_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.500 | 0.465 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | SMSTORE3_WALL_1_WINDOW_1 | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.292_SHGC_0.399 | N/A | 1.658 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
40 | SMSTORE3_WALL_1_WINDOW_2 | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.292_SHGC_0.399 | N/A | 1.658 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
41 | SMSTORE3_WALL_1_DOOR | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.292_SHGC_0.399 | N/A | 1.658 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
42 | SMSTORE3_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE2_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | SMSTORE3_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.500 | 0.465 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | SMSTORE3_WALL_3_DOOR | Door | SMSTORE3_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
45 | SMSTORE3_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE4_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | SMSTORE3_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE3_FLOOR_FFACTOR | 7.817E-002 | 7.671E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
47 | SMSTORE3_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.163 | 0.158 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
48 | SMSTORE3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
49 | SMSTORE4_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.500 | 0.465 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | SMSTORE4_WALL_1_WINDOW_1 | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.292_SHGC_0.399 | N/A | 1.658 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
51 | SMSTORE4_WALL_1_WINDOW_2 | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.292_SHGC_0.399 | N/A | 1.658 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
52 | SMSTORE4_WALL_1_DOOR | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.292_SHGC_0.399 | N/A | 1.658 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | SMSTORE4_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE3_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | SMSTORE4_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.500 | 0.465 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | SMSTORE4_WALL_3_DOOR | Door | SMSTORE4_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | SMSTORE4_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE2_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | SMSTORE4_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE4_FLOOR_FFACTOR | 7.817E-002 | 7.671E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | SMSTORE4_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.163 | 0.158 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | SMSTORE4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | LGSTORE2_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE4_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | LGSTORE2_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.500 | 0.465 | 71.19 | 78.94 | 71.19 | 0.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
62 | LGSTORE2_WALL_3_DOOR_1 | Door | LGSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
63 | LGSTORE2_WALL_3_DOOR_2 | Door | LGSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
64 | LGSTORE2_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE5_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LGSTORE2_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.500 | 0.465 | 58.22 | 78.94 | 58.22 | 180.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
66 | LGSTORE2_WALL_1_WINDOW_1 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.292_SHGC_0.399 | N/A | 1.658 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | LGSTORE2_WALL_1_WINDOW_2 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.292_SHGC_0.399 | N/A | 1.658 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | LGSTORE2_WALL_1_WINDOW_3 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.292_SHGC_0.399 | N/A | 1.658 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | LGSTORE2_WALL_1_WINDOW_4 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.292_SHGC_0.399 | N/A | 1.658 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LGSTORE2_WALL_1_DOOR_1 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.292_SHGC_0.399 | N/A | 1.658 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
71 | LGSTORE2_WALL_1_DOOR_2 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.292_SHGC_0.399 | N/A | 1.658 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
72 | LGSTORE2_FLOOR | Floor | CTF - ConductionTransferFunction | LGSTORE2_FLOOR_FFACTOR | 7.817E-002 | 7.671E-002 | 348.39 | 348.39 | 348.39 | 270.00 | 180.00 | 22.86 | 15.24 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
73 | LGSTORE2_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.163 | 0.158 | 348.39 | 348.39 | 348.39 | 270.00 | 0.00 | 22.86 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
74 | LGSTORE2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 696.77 | 696.77 | 696.77 | 0.00 | 90.00 | 696.77 | 1.00 | 0.00 | LGSTORE2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
75 | SMSTORE5_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.500 | 0.465 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | SMSTORE5_WALL_1_WINDOW_1 | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.292_SHGC_0.399 | N/A | 1.658 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
77 | SMSTORE5_WALL_1_WINDOW_2 | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.292_SHGC_0.399 | N/A | 1.658 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | SMSTORE5_WALL_1_DOOR | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.292_SHGC_0.399 | N/A | 1.658 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
79 | SMSTORE5_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE2_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | SMSTORE5_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.500 | 0.465 | 35.59 | 39.47 | 35.59 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | SMSTORE5_WALL_3_DOOR | Door | SMSTORE5_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
82 | SMSTORE5_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE6_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
83 | SMSTORE5_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE5_FLOOR_FFACTOR | 7.817E-002 | 7.671E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
84 | SMSTORE5_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.163 | 0.158 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
85 | SMSTORE5_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE5_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | SMSTORE6_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.500 | 0.465 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | SMSTORE6_WALL_1_WINDOW_1 | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.292_SHGC_0.399 | N/A | 1.658 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | SMSTORE6_WALL_1_WINDOW_2 | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.292_SHGC_0.399 | N/A | 1.658 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
89 | SMSTORE6_WALL_1_DOOR | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.292_SHGC_0.399 | N/A | 1.658 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | SMSTORE6_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE5_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | SMSTORE6_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.500 | 0.465 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | SMSTORE6_WALL_3_DOOR | Door | SMSTORE6_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
93 | SMSTORE6_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE7_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | SMSTORE6_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE6_FLOOR_FFACTOR | 7.817E-002 | 7.671E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
95 | SMSTORE6_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.163 | 0.158 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
96 | SMSTORE6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
97 | SMSTORE7_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.500 | 0.465 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | SMSTORE7_WALL_1_WINDOW_1 | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.292_SHGC_0.399 | N/A | 1.658 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | SMSTORE7_WALL_1_WINDOW_2 | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.292_SHGC_0.399 | N/A | 1.658 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
100 | SMSTORE7_WALL_1_DOOR | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.292_SHGC_0.399 | N/A | 1.658 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
101 | SMSTORE7_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE6_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
102 | SMSTORE7_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.500 | 0.465 | 35.59 | 39.47 | 35.59 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | SMSTORE7_WALL_3_DOOR | Door | SMSTORE7_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
104 | SMSTORE7_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE8_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | SMSTORE7_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE7_FLOOR_FFACTOR | 7.817E-002 | 7.671E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
106 | SMSTORE7_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.163 | 0.158 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
107 | SMSTORE7_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE7_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
108 | SMSTORE8_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.500 | 0.465 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | SMSTORE8_WALL_1_WINDOW_1 | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.292_SHGC_0.399 | N/A | 1.658 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
110 | SMSTORE8_WALL_1_WINDOW_2 | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.292_SHGC_0.399 | N/A | 1.658 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
111 | SMSTORE8_WALL_1_DOOR | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.292_SHGC_0.399 | N/A | 1.658 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
112 | SMSTORE8_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE7_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | SMSTORE8_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.500 | 0.465 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | SMSTORE8_WALL_3_DOOR | Door | SMSTORE8_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
115 | SMSTORE8_WALL_4 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.500 | 0.465 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | SMSTORE8_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE8_FLOOR_FFACTOR | 0.199 | 0.190 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | SMSTORE8_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.163 | 0.158 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | SMSTORE8_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE8_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | LGSTORE1 | RunPeriod: RUNPERIOD 1 | 9.9782336638E-002 | 0.4220309610 | Pass | Pass | 0.1354616163 | 0.4720381645 | Pass | Pass |
2 | SMSTORE1 | RunPeriod: RUNPERIOD 1 | 7.2769593060E-002 | 0.3857367617 | Pass | Pass | 0.1113333626 | 0.6624179953 | Pass | Pass |
3 | SMSTORE2 | RunPeriod: RUNPERIOD 1 | 0.1019625099 | 0.4343933428 | Pass | Pass | 4.4365295203E-002 | 0.1450055122 | Pass | Pass |
4 | SMSTORE3 | RunPeriod: RUNPERIOD 1 | 0.1124955954 | 0.4144812787 | Pass | Pass | 0.1974433466 | 0.6104357801 | Pass | Pass |
5 | SMSTORE4 | RunPeriod: RUNPERIOD 1 | 0.1288582167 | 0.4431388841 | Pass | Pass | 0.1298664885 | 0.4253135720 | Pass | Pass |
6 | LGSTORE2 | RunPeriod: RUNPERIOD 1 | 0.1572709948 | 0.4302546777 | Pass | Pass | 0.3292621934 | 0.9909734464 | Pass | Pass |
7 | SMSTORE5 | RunPeriod: RUNPERIOD 1 | 0.1555962415 | 0.4575851532 | Pass | Pass | 0.2053590434 | 0.5618541166 | Pass | Pass |
8 | SMSTORE6 | RunPeriod: RUNPERIOD 1 | 0.1586035772 | 0.4592307539 | Pass | Pass | 0.2006308089 | 0.5603724557 | Pass | Pass |
9 | SMSTORE7 | RunPeriod: RUNPERIOD 1 | 0.1623148589 | 0.4347874822 | Pass | Pass | 0.2636439248 | 0.6597240619 | Pass | Pass |
10 | SMSTORE8 | RunPeriod: RUNPERIOD 1 | 0.3516252179 | 0.5722974869 | Pass | Pass | 0.2200314164 | 0.4210631766 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:19
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 3597.20 | 348.95 | 0.00 | 815.21 | 449.84 | 5211.21 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:19
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | -32.70 | 0.00 | -32.70 | Wetbulb [C] | 2.40 | 210.00 |
INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 30.10 | 12.40 | 21.10 | Wetbulb [C] | 4.70 | 200.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 12.00 | 13 | |||
Apr | 16.00 | 23 | |||
May | 0.00 | 0 | |||
Jun | 190.00 | 53 | |||
Jul | 136.00 | 41 | |||
Aug | 87.00 | 42 | |||
Sep | 0.00 | 0 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:19
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_2 | NONRES_EXT_WALL_GRD | 0.30 | 0.465 | 0.500 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE1_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.465 | 0.500 | 78.94 | 71.15 | 0.00 | 90.00 | N |
LGSTORE1_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.465 | 0.500 | 78.94 | 58.18 | 180.00 | 90.00 | S |
LGSTORE1_FLOOR | LGSTORE1_FLOOR_FFACTOR | 1.00 | 0.135 | 0.138 | 348.39 | 348.39 | 270.00 | 180.00 | |
LGSTORE1_ROOF | NONRES_ROOF | 0.23 | 0.159 | 0.163 | 348.39 | 348.39 | 270.00 | 0.00 | |
SMSTORE1_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.465 | 0.500 | 39.47 | 29.09 | 180.00 | 90.00 | S |
SMSTORE1_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.465 | 0.500 | 39.47 | 35.57 | 0.00 | 90.00 | N |
SMSTORE1_FLOOR | SMSTORE1_FLOOR_FFACTOR | 1.00 | 0.077 | 0.078 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE1_ROOF | NONRES_ROOF | 0.23 | 0.159 | 0.163 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE2_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.465 | 0.500 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE2_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.465 | 0.500 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE2_FLOOR | SMSTORE2_FLOOR_FFACTOR | 1.00 | 0.077 | 0.078 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE2_ROOF | NONRES_ROOF | 0.23 | 0.159 | 0.163 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE3_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.465 | 0.500 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE3_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.465 | 0.500 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE3_FLOOR | SMSTORE3_FLOOR_FFACTOR | 1.00 | 0.077 | 0.078 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE3_ROOF | NONRES_ROOF | 0.23 | 0.159 | 0.163 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE4_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.465 | 0.500 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE4_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.465 | 0.500 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE4_FLOOR | SMSTORE4_FLOOR_FFACTOR | 1.00 | 0.077 | 0.078 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE4_ROOF | NONRES_ROOF | 0.23 | 0.159 | 0.163 | 174.19 | 174.19 | 270.00 | 0.00 | |
LGSTORE2_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.465 | 0.500 | 78.94 | 71.19 | 0.00 | 90.00 | N |
LGSTORE2_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.465 | 0.500 | 78.94 | 58.22 | 180.00 | 90.00 | S |
LGSTORE2_FLOOR | LGSTORE2_FLOOR_FFACTOR | 1.00 | 0.077 | 0.078 | 348.39 | 348.39 | 270.00 | 180.00 | |
LGSTORE2_ROOF | NONRES_ROOF | 0.23 | 0.159 | 0.163 | 348.39 | 348.39 | 270.00 | 0.00 | |
SMSTORE5_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.465 | 0.500 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE5_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.465 | 0.500 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE5_FLOOR | SMSTORE5_FLOOR_FFACTOR | 1.00 | 0.077 | 0.078 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE5_ROOF | NONRES_ROOF | 0.23 | 0.159 | 0.163 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE6_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.465 | 0.500 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE6_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.465 | 0.500 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE6_FLOOR | SMSTORE6_FLOOR_FFACTOR | 1.00 | 0.077 | 0.078 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE6_ROOF | NONRES_ROOF | 0.23 | 0.159 | 0.163 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE7_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.465 | 0.500 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE7_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.465 | 0.500 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE7_FLOOR | SMSTORE7_FLOOR_FFACTOR | 1.00 | 0.077 | 0.078 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE7_ROOF | NONRES_ROOF | 0.23 | 0.159 | 0.163 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE8_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.465 | 0.500 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE8_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.465 | 0.500 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE8_WALL_4 | NONRES_EXT_WALL_GRD | 0.30 | 0.465 | 0.500 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE8_FLOOR | SMSTORE8_FLOOR_FFACTOR | 1.00 | 0.193 | 0.199 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE8_ROOF | NONRES_ROOF | 0.23 | 0.159 | 0.163 | 174.19 | 174.19 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE1_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE2_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE2_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE3_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE3_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE4_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE4_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
LGSTORE2_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE2_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE5_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE5_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE6_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE6_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE7_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE7_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE8_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 696.77 | 0.00 | 90.00 | N | ||
SMSTORE1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
LGSTORE2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 696.77 | 0.00 | 90.00 | N | ||
SMSTORE5_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE7_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE8_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.292_SHGC_0.399 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.658 | 0.400 | 0.440 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.292_SHGC_0.399 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.658 | 0.400 | 0.440 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_3 | NONRESWINDOW_U_0.292_SHGC_0.399 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.658 | 0.400 | 0.440 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_4 | NONRESWINDOW_U_0.292_SHGC_0.399 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.658 | 0.400 | 0.440 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_DOOR_1 | NONRESWINDOW_U_0.292_SHGC_0.399 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 1.658 | 0.400 | 0.440 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_DOOR_2 | NONRESWINDOW_U_0.292_SHGC_0.399 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 1.658 | 0.400 | 0.440 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.292_SHGC_0.399 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.658 | 0.400 | 0.440 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.292_SHGC_0.399 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.658 | 0.400 | 0.440 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_DOOR | NONRESWINDOW_U_0.292_SHGC_0.399 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 1.658 | 0.400 | 0.440 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.292_SHGC_0.399 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.658 | 0.400 | 0.440 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.292_SHGC_0.399 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.658 | 0.400 | 0.440 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_DOOR | NONRESWINDOW_U_0.292_SHGC_0.399 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 1.658 | 0.400 | 0.440 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.292_SHGC_0.399 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.658 | 0.400 | 0.440 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.292_SHGC_0.399 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.658 | 0.400 | 0.440 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_DOOR | NONRESWINDOW_U_0.292_SHGC_0.399 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 1.658 | 0.400 | 0.440 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.292_SHGC_0.399 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.658 | 0.400 | 0.440 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.292_SHGC_0.399 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.658 | 0.400 | 0.440 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_DOOR | NONRESWINDOW_U_0.292_SHGC_0.399 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 1.658 | 0.400 | 0.440 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.292_SHGC_0.399 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.658 | 0.400 | 0.440 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.292_SHGC_0.399 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.658 | 0.400 | 0.440 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_3 | NONRESWINDOW_U_0.292_SHGC_0.399 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.658 | 0.400 | 0.440 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_4 | NONRESWINDOW_U_0.292_SHGC_0.399 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.658 | 0.400 | 0.440 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_DOOR_1 | NONRESWINDOW_U_0.292_SHGC_0.399 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 1.658 | 0.400 | 0.440 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_DOOR_2 | NONRESWINDOW_U_0.292_SHGC_0.399 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 1.658 | 0.400 | 0.440 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.292_SHGC_0.399 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.658 | 0.400 | 0.440 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.292_SHGC_0.399 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.658 | 0.400 | 0.440 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_DOOR | NONRESWINDOW_U_0.292_SHGC_0.399 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 1.658 | 0.400 | 0.440 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.292_SHGC_0.399 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.658 | 0.400 | 0.440 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.292_SHGC_0.399 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.658 | 0.400 | 0.440 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_DOOR | NONRESWINDOW_U_0.292_SHGC_0.399 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 1.658 | 0.400 | 0.440 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.292_SHGC_0.399 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.658 | 0.400 | 0.440 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.292_SHGC_0.399 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.658 | 0.400 | 0.440 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_DOOR | NONRESWINDOW_U_0.292_SHGC_0.399 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 1.658 | 0.400 | 0.440 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.292_SHGC_0.399 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.658 | 0.400 | 0.440 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.292_SHGC_0.399 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.658 | 0.400 | 0.440 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_DOOR | NONRESWINDOW_U_0.292_SHGC_0.399 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 1.658 | 0.400 | 0.440 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
Total or Average | 124.40 | 1.658 | 0.400 | 0.440 | |||||||||||||||||
North Total or Average | 0.00 | - | - | - | |||||||||||||||||
Non-North Total or Average | 124.40 | 1.658 | 0.400 | 0.440 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
LGSTORE1_WALL_3_DOOR_1 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.90 | LGSTORE1_WALL_3 |
LGSTORE1_WALL_3_DOOR_2 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.90 | LGSTORE1_WALL_3 |
SMSTORE1_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.90 | SMSTORE1_WALL_3 |
SMSTORE2_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE2_WALL_3 |
SMSTORE3_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE3_WALL_3 |
SMSTORE4_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE4_WALL_3 |
LGSTORE2_WALL_3_DOOR_1 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | LGSTORE2_WALL_3 |
LGSTORE2_WALL_3_DOOR_2 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | LGSTORE2_WALL_3 |
SMSTORE5_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE5_WALL_3 |
SMSTORE6_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE6_WALL_3 |
SMSTORE7_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE7_WALL_3 |
SMSTORE8_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE8_WALL_3 |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:19
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
LGSTORE1_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_DOOR_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_DOOR_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_DOOR_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_DOOR_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:19
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
LGSTORE1_LIGHTS | LGSTORE1 | LGSTORE1 | GENERAL | 9.6053 | 348.39 | 3346.35 | LightsWired | LTG_SCH_BASE_LPD1 | 83.91 | 168.00 | 82.62 | 0.0000 | Y | 51.90 |
LGSTORE1_LIGHTS_ALLOWANCE | LGSTORE1 | LGSTORE1 | GENERAL | 5.6969 | 348.39 | 1984.73 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | 97.50 | 112.00 | 94.53 | 0.0000 | Y | 35.22 |
SMSTORE1_LIGHTS | SMSTORE1 | SMSTORE1 | GENERAL | 9.7206 | 174.19 | 1693.26 | LightsWired | LTG_SCH_BASE_SMALL_LPD1 | 85.41 | 168.00 | 84.05 | 0.0000 | Y | 26.72 |
SMSTORE1_LIGHTS_ALLOWANCE | SMSTORE1 | SMSTORE1 | GENERAL | 8.5685 | 174.19 | 1492.57 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | 97.50 | 112.00 | 94.53 | 0.0000 | Y | 26.49 |
SMSTORE2_LIGHTS | SMSTORE2 | SMSTORE2 | GENERAL | 9.6995 | 174.19 | 1689.58 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 68.73 | 168.00 | 65.95 | 0.0000 | Y | 20.92 |
SMSTORE2_LIGHTS_ALLOWANCE | SMSTORE2 | SMSTORE2 | GENERAL | 6.9539 | 174.19 | 1211.32 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 84.29 | 73.25 | 0.0000 | Y | 16.66 |
SMSTORE3_LIGHTS | SMSTORE3 | SMSTORE3 | GENERAL | 9.6995 | 174.19 | 1689.58 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 68.73 | 168.00 | 65.95 | 0.0000 | Y | 20.92 |
SMSTORE3_LIGHTS_ALLOWANCE | SMSTORE3 | SMSTORE3 | GENERAL | 6.9539 | 174.19 | 1211.32 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 84.29 | 73.25 | 0.0000 | Y | 16.66 |
SMSTORE4_LIGHTS | SMSTORE4 | SMSTORE4 | GENERAL | 9.6995 | 174.19 | 1689.58 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 68.73 | 168.00 | 65.95 | 0.0000 | Y | 20.92 |
SMSTORE4_LIGHTS_ALLOWANCE | SMSTORE4 | SMSTORE4 | GENERAL | 6.9539 | 174.19 | 1211.32 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 84.29 | 73.25 | 0.0000 | Y | 16.66 |
LGSTORE2_LIGHTS | LGSTORE2 | LGSTORE2 | GENERAL | 9.5842 | 348.39 | 3339.00 | LightsWired | LTG_SCH_BASE_LPD2 | 62.11 | 168.00 | 59.29 | 0.0000 | Y | 37.16 |
LGSTORE2_LIGHTS_ALLOWANCE | LGSTORE2 | LGSTORE2 | GENERAL | 0.0000 | 348.39 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE5_LIGHTS | SMSTORE5 | SMSTORE5 | GENERAL | 9.6995 | 174.19 | 1689.58 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 60.29 | 0.0000 | Y | 19.12 |
SMSTORE5_LIGHTS_ALLOWANCE | SMSTORE5 | SMSTORE5 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE6_LIGHTS | SMSTORE6 | SMSTORE6 | GENERAL | 9.6995 | 174.19 | 1689.58 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 60.29 | 0.0000 | Y | 19.12 |
SMSTORE6_LIGHTS_ALLOWANCE | SMSTORE6 | SMSTORE6 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE7_LIGHTS | SMSTORE7 | SMSTORE7 | GENERAL | 9.6995 | 174.19 | 1689.58 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 60.29 | 0.0000 | Y | 19.12 |
SMSTORE7_LIGHTS_ALLOWANCE | SMSTORE7 | SMSTORE7 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE8_LIGHTS | SMSTORE8 | SMSTORE8 | GENERAL | 9.6995 | 174.19 | 1689.58 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 60.29 | 0.0000 | Y | 19.12 |
SMSTORE8_LIGHTS_ALLOWANCE | SMSTORE8 | SMSTORE8 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
Interior Lighting Total | 6.5342 | 4180.64 | 27316.92 | 366.68 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 455.59 | AstronomicalClock | - | 42.55 | 42.55 | 3.64 | |
EXTERIOR_LIGHTS_B | 2744.24 | AstronomicalClock | - | 83.52 | 63.04 | 32.47 | |
EXTERIOR_LIGHTS_C | 2307.23 | AstronomicalClock | - | 83.52 | 56.04 | 24.27 | |
Exterior Lighting Total | 5507.06 | 60.38 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:19
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 40281.95 | 30724.65 | 9557.30 | 0.76 | 3.73 | |||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 20699.19 | 15953.28 | 4745.91 | 0.77 | 3.80 | |||
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 20809.70 | 16047.82 | 4761.88 | 0.77 | 3.80 | |||
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 20868.24 | 16097.97 | 4770.27 | 0.77 | 3.80 | |||
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 20700.74 | 15954.47 | 4746.27 | 0.77 | 3.80 | |||
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 37880.32 | 28784.12 | 9096.20 | 0.76 | 3.80 | |||
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 20324.37 | 15482.09 | 4842.28 | 0.76 | 3.80 | |||
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 20345.29 | 15466.90 | 4878.39 | 0.76 | 3.80 | |||
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 20659.84 | 15692.39 | 4967.45 | 0.76 | 3.80 | |||
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 24611.20 | 18711.16 | 5900.04 | 0.76 | 3.80 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC_1:1 COOLING COIL | 38753.2 | 11.43 | 11.43 | ||||
PSZ-AC_2:2 COOLING COIL | 19897.9 | 11.56 | 11.56 | ||||
PSZ-AC_3:3 COOLING COIL | 20002.9 | 11.56 | 11.56 | ||||
PSZ-AC_4:4 COOLING COIL | 20058.6 | 11.56 | 11.56 | ||||
PSZ-AC_5:5 COOLING COIL | 19899.4 | 11.56 | 11.56 | ||||
PSZ-AC_6:6 COOLING COIL | 36451.7 | 11.62 | 11.62 | ||||
PSZ-AC_7:7 COOLING COIL | 19555.6 | 11.61 | 11.61 | ||||
PSZ-AC_8:8 COOLING COIL | 19577.1 | 11.61 | 11.61 | ||||
PSZ-AC_9:9 COOLING COIL | 19881.5 | 11.62 | 11.62 | ||||
PSZ-AC_10:10 COOLING COIL | 23681.8 | 11.61 | 11.61 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | 68267.32 | 0.80 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | 34664.72 | 0.80 | |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | 34709.29 | 0.80 | |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | 35403.76 | 0.80 | |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | 35171.36 | 0.80 | |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | 65473.01 | 0.80 | |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | 34255.70 | 0.80 | |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | 34238.74 | 0.80 | |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | 34520.58 | 0.80 | |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | 38731.23 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 1.94 | 2080.36 | 1070.05 | 1.00 | 1.32 | General | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.02 | 1128.61 | 1107.16 | 1.00 | 1.40 | General | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 |
PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.03 | 1136.35 | 1107.16 | 1.00 | 1.40 | General | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 |
PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.03 | 1140.44 | 1107.16 | 1.00 | 1.39 | General | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.02 | 1128.70 | 1107.16 | 1.00 | 1.40 | General | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 1.82 | 1943.92 | 1070.05 | 1.00 | 1.33 | General | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.98 | 1082.43 | 1107.16 | 1.00 | 1.41 | General | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.98 | 1081.57 | 1107.16 | 1.00 | 1.41 | General | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.99 | 1095.81 | 1107.16 | 1.00 | 1.40 | General | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.18 | 1308.55 | 1107.16 | 1.00 | 1.36 | General | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
GAS TANK1 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK2 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK3 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK4 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK5 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK6 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK7 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:19
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
LGSTORE1 | 20194.13 | 24232.96 | 69.56 | 1.547 | 1.856 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 23.89 | 23.89 | 0.00966 | 30.10 | 0.01273 | 0.411 | 0.00 |
SMSTORE1 | 11164.16 | 13396.99 | 76.91 | 0.830 | 0.996 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 23.89 | 23.89 | 0.00942 | 25.39 | 0.01272 | 0.206 | 0.00 |
SMSTORE2 | 11187.07 | 13424.48 | 77.07 | 0.832 | 0.998 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 23.89 | 23.89 | 0.00962 | 23.28 | 0.01271 | 0.206 | 0.00 |
SMSTORE3 | 11207.38 | 13448.85 | 77.21 | 0.858 | 1.030 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 23.89 | 23.89 | 0.00957 | 30.00 | 0.01273 | 0.206 | 0.00 |
SMSTORE4 | 11091.97 | 13310.36 | 76.41 | 0.850 | 1.019 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 23.89 | 23.89 | 0.00958 | 30.00 | 0.01273 | 0.206 | 0.00 |
LGSTORE2 | 19399.38 | 23279.25 | 66.82 | 1.486 | 1.783 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 23.89 | 23.89 | 0.00967 | 30.00 | 0.01273 | 0.411 | 0.00 |
SMSTORE5 | 10247.58 | 12297.10 | 70.59 | 0.760 | 0.912 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 23.89 | 23.88 | 0.00966 | 25.39 | 0.01272 | 0.206 | 0.00 |
SMSTORE6 | 10164.50 | 12197.40 | 70.02 | 0.754 | 0.905 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 23.89 | 23.88 | 0.00967 | 25.39 | 0.01272 | 0.206 | 0.00 |
SMSTORE7 | 10005.59 | 12006.71 | 68.93 | 0.742 | 0.890 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 23.89 | 23.88 | 0.00970 | 25.39 | 0.01272 | 0.206 | 0.00 |
SMSTORE8 | 10165.36 | 12198.44 | 70.03 | 0.779 | 0.934 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | 23.89 | 23.89 | 0.00972 | 29.48 | 0.01272 | 0.206 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
LGSTORE1 | 36021.15 | 43225.37 | 124.07 | 1.620 | 1.944 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00673 | -32.70 | 0.00018 | 0.411 | 0.00 |
SMSTORE1 | 17436.88 | 20924.26 | 120.12 | 0.784 | 0.941 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00662 | -32.70 | 0.00018 | 0.206 | 0.00 |
SMSTORE2 | 17575.78 | 21090.93 | 121.08 | 0.791 | 0.949 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00663 | -32.70 | 0.00018 | 0.206 | 0.00 |
SMSTORE3 | 17637.68 | 21165.21 | 121.50 | 0.793 | 0.952 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00664 | -32.70 | 0.00018 | 0.206 | 0.00 |
SMSTORE4 | 17775.23 | 21330.28 | 122.45 | 0.799 | 0.959 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00664 | -32.70 | 0.00018 | 0.206 | 0.00 |
LGSTORE2 | 33657.96 | 40389.55 | 115.93 | 1.514 | 1.817 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00671 | -32.70 | 0.00018 | 0.411 | 0.00 |
SMSTORE5 | 18113.76 | 21736.51 | 124.78 | 0.815 | 0.978 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00666 | -32.70 | 0.00018 | 0.206 | 0.00 |
SMSTORE6 | 18099.41 | 21719.30 | 124.69 | 0.814 | 0.977 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00666 | -32.70 | 0.00018 | 0.206 | 0.00 |
SMSTORE7 | 18337.75 | 22005.30 | 126.33 | 0.825 | 0.990 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00668 | -32.70 | 0.00018 | 0.206 | 0.00 |
SMSTORE8 | 21898.63 | 26278.36 | 150.86 | 0.985 | 1.182 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00677 | -32.70 | 0.00018 | 0.206 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC_1:1 | 1.86 | 1.86 | 1.94 | 1.94 | 1.9442 | 1.9442 | 1.9442 | 1.0000 | 1.0000 |
PSZ-AC_2:2 | 1.02 | 1.02 | 0.94 | 0.94 | 1.0194 | 0.9963 | 1.0194 | 0.9774 | 1.0000 |
PSZ-AC_3:3 | 1.03 | 1.03 | 0.95 | 0.95 | 1.0264 | 0.9984 | 1.0264 | 0.9727 | 1.0000 |
PSZ-AC_4:4 | 1.03 | 1.03 | 0.95 | 0.95 | 1.0301 | 1.0301 | 1.0301 | 1.0000 | 1.0000 |
PSZ-AC_5:5 | 1.02 | 1.02 | 0.96 | 0.96 | 1.0195 | 1.0195 | 1.0195 | 1.0000 | 1.0000 |
PSZ-AC_6:6 | 1.78 | 1.78 | 1.82 | 1.82 | 1.8167 | 1.8167 | 1.8167 | 1.0000 | 1.0000 |
PSZ-AC_7:7 | 0.92 | 0.92 | 0.98 | 0.98 | 0.9777 | 0.9777 | 0.9777 | 1.0000 | 1.0000 |
PSZ-AC_8:8 | 0.91 | 0.91 | 0.98 | 0.98 | 0.9769 | 0.9769 | 0.9769 | 1.0000 | 1.0000 |
PSZ-AC_9:9 | 0.90 | 0.90 | 0.99 | 0.99 | 0.9898 | 0.9898 | 0.9898 | 1.0000 | 1.0000 |
PSZ-AC_10:10 | 0.93 | 0.93 | 1.18 | 1.18 | 1.1819 | 1.1819 | 1.1819 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 40281.950 | 30724.655 | 1.944180 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 20140.97 | 15468.33 | 1.296120 | 26.17 | 18.18 | 0.01033968 | 12.80 | 11.72 | 0.00850000 | 30.10 | 0.01272586 | 21.13 | 31.7470 | 23.89 | 0.00965998 | 50.0819 | 20194.13 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_1:1 | 68267.323 | 68267.323 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 68267.32 | 68267.32 | 1.944177 | 9.72 | 6.96 | 0.00534147 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 21.1647 | 21.10 | 0.00672625 | 41.4916 | 36021.15 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 20699.190 | 15953.280 | 1.019380 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 10349.59 | 8063.35 | 0.679587 | 26.08 | 18.06 | 0.01021645 | 12.80 | 11.72 | 0.00850000 | 30.10 | 0.01272586 | 21.13 | 30.2742 | 23.89 | 0.00958191 | 49.6830 | 11091.14 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_2:2 | 34664.716 | 34664.716 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 34664.72 | 34664.72 | 1.019379 | 10.25 | 7.19 | 0.00532445 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 20.1828 | 21.10 | 0.00662444 | 40.8706 | 17436.88 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_3:3 | 20809.700 | 16047.816 | 1.026370 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 10404.85 | 8115.13 | 0.684247 | 26.07 | 18.05 | 0.01020715 | 12.80 | 11.72 | 0.00850000 | 30.10 | 0.01272586 | 21.13 | 30.0680 | 23.89 | 0.00957565 | 49.6510 | 11166.70 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_3:3 | 34709.289 | 34709.289 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 34709.29 | 34709.29 | 1.026366 | 10.32 | 7.25 | 0.00533981 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 20.0454 | 21.10 | 0.00663259 | 40.9203 | 17575.78 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_4:4 | 20868.240 | 16097.969 | 1.030060 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 10434.12 | 8142.51 | 0.686707 | 26.06 | 18.04 | 0.01020231 | 12.80 | 11.72 | 0.00850000 | 30.10 | 0.01272586 | 21.13 | 29.9603 | 23.89 | 0.00957239 | 49.6344 | 11206.26 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_4:4 | 35403.764 | 35403.764 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 35403.76 | 35403.76 | 1.030060 | 10.36 | 7.27 | 0.00534732 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 19.9735 | 21.10 | 0.00663618 | 40.9423 | 17637.68 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_5:5 | 20700.740 | 15954.474 | 1.019450 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 10350.37 | 8063.94 | 0.679633 | 26.08 | 18.06 | 0.01021646 | 12.80 | 11.72 | 0.00850000 | 30.10 | 0.01272586 | 21.13 | 30.2721 | 23.89 | 0.00958193 | 49.6831 | 11091.12 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_5:5 | 35171.360 | 35171.360 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 35171.36 | 35171.36 | 1.019453 | 10.25 | 7.21 | 0.00534026 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 20.1814 | 21.10 | 0.00664413 | 40.9908 | 17775.23 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_6:6 | 37880.320 | 28784.119 | 1.816670 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 18940.16 | 14498.20 | 1.211113 | 26.23 | 18.23 | 0.01037275 | 12.80 | 11.72 | 0.00850000 | 30.10 | 0.01272586 | 21.13 | 33.9753 | 23.89 | 0.00966663 | 50.1155 | 19396.47 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_6:6 | 65473.008 | 65473.008 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 65473.01 | 65473.01 | 1.816668 | 8.92 | 6.44 | 0.00522973 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 22.6502 | 21.10 | 0.00670744 | 41.3758 | 33657.96 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_7:7 | 20324.370 | 15482.089 | 0.977660 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | 10162.18 | 7786.88 | 0.651773 | 26.21 | 18.21 | 0.01036315 | 12.80 | 11.72 | 0.00850000 | 30.10 | 0.01272586 | 21.13 | 31.5661 | 23.89 | 0.00968160 | 50.1919 | 9998.69 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_7:7 | 34255.700 | 34255.700 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 34255.70 | 34255.70 | 0.977661 | 9.78 | 6.94 | 0.00529963 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 21.0440 | 21.10 | 0.00666326 | 41.1076 | 18113.76 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_8:8 | 20345.290 | 15466.896 | 0.976890 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | 10172.65 | 7784.99 | 0.651260 | 26.23 | 18.23 | 0.01037463 | 12.80 | 11.72 | 0.00850000 | 30.10 | 0.01272586 | 21.13 | 31.5910 | 23.89 | 0.00968946 | 50.2321 | 9920.29 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_8:8 | 34238.738 | 34238.738 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 34238.74 | 34238.74 | 0.976887 | 9.77 | 6.94 | 0.00529792 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 21.0607 | 21.10 | 0.00666246 | 41.1027 | 18099.41 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_9:9 | 20659.840 | 15692.388 | 0.989750 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 10329.92 | 7892.90 | 0.659833 | 26.24 | 18.24 | 0.01038889 | 12.80 | 11.72 | 0.00850000 | 30.10 | 0.01272586 | 21.13 | 31.1805 | 23.89 | 0.00969925 | 50.2820 | 9824.14 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_9:9 | 34520.582 | 34520.582 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 34520.58 | 34520.58 | 0.989752 | 9.92 | 7.04 | 0.00532607 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 20.7870 | 21.10 | 0.00667561 | 41.1830 | 18337.75 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_10:10 | 24611.200 | 18711.157 | 1.181900 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | 12305.60 | 9384.07 | 0.787933 | 26.18 | 18.23 | 0.01039692 | 12.80 | 11.72 | 0.00850000 | 30.00 | 0.01272568 | 21.10 | 26.1113 | 23.89 | 0.00973419 | 50.4609 | 10104.15 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_10:10 | 38731.228 | 38731.228 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 38731.23 | 38731.23 | 1.181900 | 11.74 | 8.23 | 0.00562478 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 17.4075 | 21.10 | 0.00677163 | 41.7707 | 21898.63 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:37:19
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 40281.950 | 30724.655 | 1.944180 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.0609 | 1004.8586 | 1.1539 | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.944177 | 2.24343374 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | Sensible | 20140.97 | 15468.33 | 1.0000 | 1.49562509 | 1.296120 | 26.17 | 18.18 | 0.01033968 | 52657.5 | 12.80 | 11.72 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 20140.97 | 30.10 | 0.01272586 | 21.13 | 0.41147883 | 31.7470 | 23.89 | 0.00965998 | 23.89 | 0.00965998 | 50.0819 | 20194.13 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 68267.323 | 68267.323 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.944177 | 2.24343374 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 68267.32 | 68267.32 | 1.0000 | 2.24343374 | 1.944177 | 9.72 | 6.96 | 0.00534147 | 23219.5 | 40.00 | 20.69 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 68267.32 | -32.70 | 0.00018338 | -32.70 | 0.41147883 | 21.1647 | 21.10 | 0.00672625 | 21.10 | 0.00672625 | 41.4916 | 36021.15 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 20699.190 | 15953.280 | 1.019380 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.8319 | 1004.8586 | 1.1539 | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.019379 | 1.17628624 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | Sensible | 10349.59 | 8063.35 | 1.0000 | 0.78419195 | 0.679587 | 26.08 | 18.06 | 0.01021645 | 52249.4 | 12.80 | 11.72 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10349.59 | 30.10 | 0.01272586 | 21.13 | 0.20573941 | 30.2742 | 23.89 | 0.00958191 | 23.89 | 0.00958191 | 49.6830 | 11091.14 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 34664.716 | 34664.716 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.019379 | 1.17628624 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 34664.72 | 34664.72 | 1.0000 | 1.17628624 | 1.019379 | 10.25 | 7.19 | 0.00532445 | 23712.7 | 40.00 | 20.69 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 34664.72 | -32.70 | 0.00018338 | -32.70 | 0.20573941 | 20.1828 | 21.10 | 0.00662444 | 21.10 | 0.00662444 | 40.8706 | 17436.88 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 20809.700 | 16047.816 | 1.026370 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.8146 | 1004.8586 | 1.1539 | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.026366 | 1.18434922 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | Sensible | 10404.85 | 8115.13 | 1.0000 | 0.78956924 | 0.684247 | 26.07 | 18.05 | 0.01020715 | 52217.0 | 12.80 | 11.72 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10404.85 | 30.10 | 0.01272586 | 21.13 | 0.20573941 | 30.0680 | 23.89 | 0.00957565 | 23.89 | 0.00957565 | 49.6510 | 11166.70 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 34709.289 | 34709.289 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.026366 | 1.18434922 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 34709.29 | 34709.29 | 1.0000 | 1.18434922 | 1.026366 | 10.32 | 7.25 | 0.00533981 | 23826.5 | 40.00 | 20.69 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 34709.29 | -32.70 | 0.00018338 | -32.70 | 0.20573941 | 20.0454 | 21.10 | 0.00663259 | 21.10 | 0.00663259 | 40.9203 | 17575.78 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 20868.240 | 16097.969 | 1.030060 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.8056 | 1004.8586 | 1.1539 | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.030060 | 1.18861191 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | Sensible | 10434.12 | 8142.51 | 1.0000 | 0.79240789 | 0.686707 | 26.06 | 18.04 | 0.01020231 | 52200.2 | 12.80 | 11.72 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10434.12 | 30.10 | 0.01272586 | 21.13 | 0.20573941 | 29.9603 | 23.89 | 0.00957239 | 23.89 | 0.00957239 | 49.6344 | 11206.26 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 35403.764 | 35403.764 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.030060 | 1.18861191 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 35403.76 | 35403.76 | 1.0000 | 1.18861191 | 1.030060 | 10.36 | 7.27 | 0.00534732 | 23884.6 | 40.00 | 20.69 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 35403.76 | -32.70 | 0.00018338 | -32.70 | 0.20573941 | 19.9735 | 21.10 | 0.00663618 | 21.10 | 0.00663618 | 40.9423 | 17637.68 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 20700.740 | 15954.474 | 1.019450 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.8319 | 1004.8586 | 1.1539 | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.019453 | 1.17637198 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | Sensible | 10350.37 | 8063.94 | 1.0000 | 0.78424580 | 0.679633 | 26.08 | 18.06 | 0.01021646 | 52249.5 | 12.80 | 11.72 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10350.37 | 30.10 | 0.01272586 | 21.13 | 0.20573941 | 30.2721 | 23.89 | 0.00958193 | 23.89 | 0.00958193 | 49.6831 | 11091.12 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 35171.360 | 35171.360 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.019453 | 1.17637198 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 35171.36 | 35171.36 | 1.0000 | 1.17637198 | 1.019453 | 10.25 | 7.21 | 0.00534026 | 23753.4 | 40.00 | 20.69 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 35171.36 | -32.70 | 0.00018338 | -32.70 | 0.20573941 | 20.1814 | 21.10 | 0.00664413 | 21.10 | 0.00664413 | 40.9908 | 17775.23 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 37880.320 | 28784.119 | 1.816670 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.1224 | 1004.8586 | 1.1539 | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.816668 | 2.09629816 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | Sensible | 18940.16 | 14498.20 | 1.0000 | 1.39753378 | 1.211113 | 26.23 | 18.23 | 0.01037275 | 52800.0 | 12.80 | 11.72 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 18940.16 | 30.10 | 0.01272586 | 21.13 | 0.41147883 | 33.9753 | 23.89 | 0.00966663 | 23.89 | 0.00966663 | 50.1155 | 19396.47 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 65473.008 | 65473.008 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.816668 | 2.09629816 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 65473.01 | 65473.01 | 1.0000 | 2.09629816 | 1.816668 | 8.92 | 6.44 | 0.00522973 | 22127.4 | 40.00 | 20.69 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 65473.01 | -32.70 | 0.00018338 | -32.70 | 0.41147883 | 22.6502 | 21.11 | 0.00670744 | 21.10 | 0.00670744 | 41.3758 | 33657.96 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 20324.370 | 15482.089 | 0.977660 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.1046 | 1004.8586 | 1.1539 | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.977661 | 1.12814764 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | Sensible | 10162.18 | 7786.88 | 1.0000 | 0.75209745 | 0.651773 | 26.21 | 18.21 | 0.01036315 | 52763.5 | 12.80 | 11.72 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10162.18 | 30.10 | 0.01272586 | 21.13 | 0.20573941 | 31.5661 | 23.89 | 0.00968160 | 23.89 | 0.00968160 | 50.1919 | 9998.69 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 34255.700 | 34255.700 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.977661 | 1.12814764 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 34255.70 | 34255.70 | 1.0000 | 1.12814764 | 0.977661 | 9.78 | 6.94 | 0.00529963 | 23180.0 | 40.00 | 20.69 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 34255.70 | -32.70 | 0.00018338 | -32.70 | 0.20573941 | 21.0440 | 21.11 | 0.00666326 | 21.10 | 0.00666326 | 41.1076 | 18113.76 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 20345.290 | 15466.896 | 0.976890 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.1259 | 1004.8586 | 1.1539 | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.976887 | 1.12725427 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | Sensible | 10172.65 | 7784.99 | 1.0000 | 0.75150510 | 0.651260 | 26.23 | 18.23 | 0.01037463 | 52804.0 | 12.80 | 11.72 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10172.65 | 30.10 | 0.01272586 | 21.13 | 0.20573941 | 31.5910 | 23.89 | 0.00968946 | 23.89 | 0.00968946 | 50.2321 | 9920.29 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 34238.738 | 34238.738 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.976887 | 1.12725427 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 34238.74 | 34238.74 | 1.0000 | 1.12725427 | 0.976887 | 9.77 | 6.94 | 0.00529792 | 23166.6 | 40.00 | 20.69 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 34238.74 | -32.70 | 0.00018338 | -32.70 | 0.20573941 | 21.0607 | 21.11 | 0.00666246 | 21.10 | 0.00666246 | 41.1027 | 18099.41 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 20659.840 | 15692.388 | 0.989750 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.1524 | 1004.8586 | 1.1539 | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.989752 | 1.14209887 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | Sensible | 10329.92 | 7892.90 | 1.0000 | 0.76139808 | 0.659833 | 26.24 | 18.24 | 0.01038889 | 52854.4 | 12.80 | 11.72 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10329.92 | 30.10 | 0.01272586 | 21.13 | 0.20573941 | 31.1805 | 23.89 | 0.00969925 | 23.89 | 0.00969925 | 50.2820 | 9824.14 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 34520.582 | 34520.582 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.989752 | 1.14209887 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 34520.58 | 34520.58 | 1.0000 | 1.14209887 | 0.989752 | 9.92 | 7.04 | 0.00532607 | 23387.0 | 40.00 | 20.69 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 34520.58 | -32.70 | 0.00018338 | -32.70 | 0.20573941 | 20.7870 | 21.11 | 0.00667561 | 21.10 | 0.00667561 | 41.1830 | 18337.75 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 24611.200 | 18711.157 | 1.181900 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.1674 | 1004.8586 | 1.1539 | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.181900 | 1.36382434 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | Sensible | 12305.60 | 9384.07 | 1.0000 | 0.90921586 | 0.787933 | 26.18 | 18.23 | 0.01039692 | 52811.1 | 12.80 | 11.72 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 12305.60 | 30.00 | 0.01272568 | 21.10 | 0.20573941 | 26.1113 | 23.89 | 0.00973419 | 23.89 | 0.00973419 | 50.4609 | 10104.15 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 38731.228 | 38731.228 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.181900 | 1.36382434 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 38731.23 | 38731.23 | 1.0000 | 1.36382434 | 1.181900 | 11.74 | 8.23 | 0.00562478 | 25985.1 | 40.00 | 20.69 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 38731.23 | -32.70 | 0.00018338 | -32.70 | 0.20573941 | 17.4075 | 21.10 | 0.00677163 | 21.10 | 0.00677163 | 41.7707 | 21898.63 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:19
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-AC_1:1_OA_CONTROLLER | DifferentialDryBulb | 0.41 | 1.94 | - | |||
PSZ-AC_2:2_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.02 | - | |||
PSZ-AC_3:3_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.03 | - | |||
PSZ-AC_4:4_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.03 | - | |||
PSZ-AC_5:5_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.02 | - | |||
PSZ-AC_6:6_OA_CONTROLLER | DifferentialDryBulb | 0.41 | 1.82 | - | |||
PSZ-AC_7:7_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 0.98 | - | |||
PSZ-AC_8:8_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 0.98 | - | |||
PSZ-AC_9:9_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 0.99 | - | |||
PSZ-AC_10:10_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.18 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
LGSTORE1 | 3686.83 | 4124.83 | 2637.67 |
SMSTORE1 | 3107.33 | 4058.17 | 1952.17 |
SMSTORE2 | 2613.00 | 3220.17 | 1800.17 |
SMSTORE3 | 2654.33 | 3243.50 | 1860.17 |
SMSTORE4 | 2699.00 | 3307.17 | 1943.83 |
LGSTORE2 | 2608.50 | 3152.33 | 2036.33 |
SMSTORE5 | 2579.67 | 3183.33 | 2051.17 |
SMSTORE6 | 2590.17 | 3205.83 | 2076.67 |
SMSTORE7 | 2636.50 | 3254.17 | 2161.33 |
SMSTORE8 | 2776.33 | 3357.00 | 2372.17 |
Facility | 4335.83 | 4807.00 | 3318.17 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
LGSTORE1 | 24.67 | 0.00 | 9.00 | 0.00 |
SMSTORE1 | 9.17 | 0.00 | 2.50 | 0.00 |
SMSTORE2 | 5.83 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 7.17 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 9.33 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 16.00 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 14.33 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 15.33 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 18.67 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 122.83 | 0.00 | 0.00 | 0.00 |
Facility | 146.33 | 0.00 | 9.00 | 0.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:19
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
LGSTORE1 | 17.08 | 56.25 | 1805.20 | 0.986 | 0.237 | 0.000 | 0.000 |
SMSTORE1 | 8.54 | 28.12 | 902.60 | 0.850 | 0.252 | 0.000 | 0.000 |
SMSTORE2 | 7.19 | 28.12 | 902.60 | 1.027 | 0.329 | 0.000 | 0.000 |
SMSTORE3 | 7.19 | 28.12 | 902.60 | 1.024 | 0.329 | 0.000 | 0.000 |
SMSTORE4 | 7.19 | 28.12 | 902.60 | 1.012 | 0.329 | 0.000 | 0.000 |
LGSTORE2 | 24.97 | 56.25 | 1805.20 | 0.979 | 0.316 | 0.000 | 0.000 |
SMSTORE5 | 12.48 | 28.12 | 902.60 | 0.995 | 0.351 | 0.000 | 0.000 |
SMSTORE6 | 12.48 | 28.12 | 902.60 | 0.990 | 0.351 | 0.000 | 0.000 |
SMSTORE7 | 12.48 | 28.12 | 902.60 | 0.982 | 0.351 | 0.000 | 0.000 |
SMSTORE8 | 12.48 | 28.12 | 902.60 | 1.000 | 0.372 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
LGSTORE1 | 17.08 | 56.25 | 1805.20 | 0.000 | 0.000 | 0.000 | 0.000 |
SMSTORE1 | 8.54 | 28.12 | 902.60 | 0.000 | 0.000 | 0.000 | 0.000 |
SMSTORE2 | 7.19 | 28.12 | 902.60 | 0.803 | 0.000 | 0.000 | 0.000 |
SMSTORE3 | 7.19 | 28.12 | 902.60 | 0.803 | 0.000 | 0.000 | 0.000 |
SMSTORE4 | 7.19 | 28.12 | 902.60 | 0.803 | 0.000 | 0.000 | 0.000 |
LGSTORE2 | 24.97 | 56.25 | 1805.20 | 0.804 | 0.000 | 0.000 | 0.000 |
SMSTORE5 | 12.48 | 28.12 | 902.60 | 0.804 | 0.000 | 0.000 | 0.000 |
SMSTORE6 | 12.48 | 28.12 | 902.60 | 0.804 | 0.000 | 0.000 | 0.000 |
SMSTORE7 | 12.48 | 28.12 | 902.60 | 0.804 | 0.000 | 0.000 | 0.000 |
SMSTORE8 | 12.48 | 28.12 | 902.60 | 0.803 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:37:19
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
LGSTORE1 | PSZ-AC_1:1 | 17.08 | 56.25 | 1805.20 | 348.39 | 0.4115 | 0.411 |
SMSTORE1 | PSZ-AC_2:2 | 8.54 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE2 | PSZ-AC_3:3 | 7.19 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE3 | PSZ-AC_4:4 | 7.19 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE4 | PSZ-AC_5:5 | 7.19 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
LGSTORE2 | PSZ-AC_6:6 | 24.97 | 56.25 | 1805.20 | 348.39 | 0.4115 | 0.411 |
SMSTORE5 | PSZ-AC_7:7 | 12.48 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE6 | PSZ-AC_8:8 | 12.48 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE7 | PSZ-AC_9:9 | 12.48 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE8 | PSZ-AC_10:10 | 12.48 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
Total Facility | 122.10 | 337.50 | 10831.20 | 2090.32 | 2.4689 | 2.469 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
LGSTORE1 | 10237605.93 | 0.00 | 10237605.93 | 2823803.34 | 13061409.27 | 12976396.34 | 3168.06 | 4338.17 | 1253.77 | 19.01 |
SMSTORE1 | 4417230.46 | 0.00 | 4417230.46 | 1417311.39 | 5834541.86 | 6488198.17 | 4343.02 | 3159.49 | 1257.49 | 23.43 |
SMSTORE2 | 4055848.53 | 0.00 | 4055848.53 | 1450477.46 | 5506325.99 | 6488198.17 | 4345.19 | 3571.08 | 843.72 | 82.97 |
SMSTORE3 | 4043187.17 | 0.00 | 4043187.17 | 1450477.46 | 5493664.63 | 6488198.17 | 4345.69 | 3588.75 | 825.56 | 78.17 |
SMSTORE4 | 3991800.43 | 0.00 | 3991800.43 | 1450477.46 | 5442277.89 | 6488198.17 | 4348.49 | 3626.92 | 784.59 | 74.84 |
LGSTORE2 | 7077974.36 | 0.00 | 7077974.36 | 2662411.94 | 9740386.31 | 12976396.34 | 4715.83 | 3325.17 | 719.00 | 64.12 |
SMSTORE5 | 3594915.80 | 0.00 | 3594915.80 | 1460774.73 | 5055690.53 | 6488198.17 | 4716.54 | 3332.08 | 711.37 | 62.96 |
SMSTORE6 | 3577464.41 | 0.00 | 3577464.41 | 1460774.73 | 5038239.15 | 6488198.17 | 4717.71 | 3346.67 | 695.62 | 60.10 |
SMSTORE7 | 3540504.90 | 0.00 | 3540504.90 | 1460774.73 | 5001279.63 | 6488198.17 | 4721.01 | 3392.50 | 646.49 | 49.49 |
SMSTORE8 | 3597054.42 | 0.00 | 3597054.42 | 1774287.82 | 5371342.24 | 6488198.17 | 4723.33 | 3462.83 | 573.83 | 23.03 |
Total Facility | 48133586.42 | 0.00 | 48133586.42 | 17411571.08 | 65545157.50 | 77858378.04 | 4724.58 | 4959.32 | 1439.68 | 163.98 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
LGSTORE1 | 0.4860 | 0.0000 | 0.4860 | 0.1172 | 0.6032 | 0.4115 | 252.07 | 4338.00 | 1249.92 |
SMSTORE1 | 0.2094 | 0.0000 | 0.2094 | 0.0624 | 0.2717 | 0.2057 | 1429.20 | 3159.49 | 1251.31 |
SMSTORE2 | 0.2533 | 0.0000 | 0.2533 | 0.0814 | 0.3348 | 0.2057 | 0.00 | 3570.42 | 824.58 |
SMSTORE3 | 0.2526 | 0.0000 | 0.2526 | 0.0814 | 0.3341 | 0.2057 | 0.00 | 3588.25 | 806.75 |
SMSTORE4 | 0.2497 | 0.0000 | 0.2497 | 0.0814 | 0.3312 | 0.2057 | 0.00 | 3626.83 | 768.17 |
LGSTORE2 | 0.4833 | 0.0000 | 0.4833 | 0.1564 | 0.6397 | 0.4115 | 0.00 | 3324.67 | 705.33 |
SMSTORE5 | 0.2455 | 0.0000 | 0.2455 | 0.0869 | 0.3323 | 0.2057 | 0.00 | 3331.50 | 698.50 |
SMSTORE6 | 0.2444 | 0.0000 | 0.2444 | 0.0869 | 0.3313 | 0.2057 | 0.00 | 3346.33 | 683.67 |
SMSTORE7 | 0.2424 | 0.0000 | 0.2424 | 0.0869 | 0.3292 | 0.2057 | 0.00 | 3392.50 | 637.50 |
SMSTORE8 | 0.2469 | 0.0000 | 0.2469 | 0.0919 | 0.3388 | 0.2057 | 0.00 | 3462.67 | 567.33 |
Total Facility | 2.9136 | 0.0000 | 2.9136 | 0.9328 | 3.8464 | 2.4689 | 1537.77 | 4956.90 | 1423.62 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-AC_1:1 | 13631651.36 | 0.00 | 13631651.36 | 12976396.34 | 3162.64 | 0.50 | 5596.86 | 19.01 |
PSZ-AC_2:2 | 5881838.87 | 0.00 | 5881838.87 | 6488198.17 | 4264.43 | 4.75 | 4490.82 | 23.43 |
PSZ-AC_3:3 | 5400661.16 | 0.00 | 5400661.16 | 6488198.17 | 4334.65 | 0.83 | 4424.51 | 82.64 |
PSZ-AC_4:4 | 5383802.99 | 0.00 | 5383802.99 | 6488198.17 | 4335.99 | 0.50 | 4423.51 | 77.51 |
PSZ-AC_5:5 | 5315377.39 | 0.00 | 5315377.39 | 6488198.17 | 4341.08 | 0.50 | 4418.42 | 74.84 |
PSZ-AC_6:6 | 9424859.91 | 0.00 | 9424859.91 | 12976396.34 | 4711.50 | 0.17 | 4048.33 | 64.12 |
PSZ-AC_7:7 | 4786886.63 | 0.00 | 4786886.63 | 6488198.17 | 4711.46 | 0.33 | 4048.21 | 62.96 |
PSZ-AC_8:8 | 4763645.65 | 0.00 | 4763645.65 | 6488198.17 | 4712.96 | 0.50 | 4046.54 | 59.93 |
PSZ-AC_9:9 | 4714416.94 | 0.00 | 4714416.94 | 6488198.17 | 4717.96 | 0.17 | 4041.87 | 49.32 |
PSZ-AC_10:10 | 4789669.95 | 0.00 | 4789669.95 | 6488198.17 | 4722.21 | 0.17 | 4037.62 | 23.03 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-AC_1:1 | 0.6472 | 0.0000 | 0.6472 | 0.4115 | 248.24 | 0.33 | 5591.43 |
PSZ-AC_2:2 | 0.2788 | 0.0000 | 0.2788 | 0.2057 | 1355.19 | 4.25 | 4480.56 |
PSZ-AC_3:3 | 0.3373 | 0.0000 | 0.3373 | 0.2057 | 0.00 | 0.00 | 4395.00 |
PSZ-AC_4:4 | 0.3364 | 0.0000 | 0.3364 | 0.2057 | 0.00 | 0.00 | 4395.00 |
PSZ-AC_5:5 | 0.3325 | 0.0000 | 0.3325 | 0.2057 | 0.00 | 0.00 | 4395.00 |
PSZ-AC_6:6 | 0.6435 | 0.0000 | 0.6435 | 0.4115 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_7:7 | 0.3269 | 0.0000 | 0.3269 | 0.2057 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_8:8 | 0.3255 | 0.0000 | 0.3255 | 0.2057 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_9:9 | 0.3227 | 0.0000 | 0.3227 | 0.2057 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_10:10 | 0.3288 | 0.0000 | 0.3288 | 0.2057 | 0.00 | 0.00 | 4030.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-AC_1:1 | 0.00 | 5083.21 | 566.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_2:2 | 0.00 | 4211.86 | 790.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_3:3 | 0.00 | 4135.99 | 341.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_4:4 | 0.00 | 4140.66 | 331.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_5:5 | 0.00 | 4155.27 | 314.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_6:6 | 0.00 | 3814.08 | 280.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_7:7 | 0.00 | 3797.51 | 295.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_8:8 | 0.00 | 3800.93 | 289.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_9:9 | 0.00 | 3811.37 | 267.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_10:10 | 0.00 | 3786.85 | 266.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-AC_1:1 | 0.0000 | 0.6566 | 0.8076 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_2:2 | 0.0000 | 0.3232 | 0.3479 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_3:3 | 0.0000 | 0.3287 | 0.4722 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_4:4 | 0.0000 | 0.3275 | 0.4787 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_5:5 | 0.0000 | 0.3242 | 0.4743 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_6:6 | 0.0000 | 0.6306 | 0.8687 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_7:7 | 0.0000 | 0.3191 | 0.4516 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_8:8 | 0.0000 | 0.3178 | 0.4510 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_9:9 | 0.0000 | 0.3154 | 0.4498 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_10:10 | 0.0000 | 0.3170 | 0.5134 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:19
Surfaces by ClassTotal | Outdoors | |
Wall | 40 | 22 |
Floor | 10 | 10 |
Roof | 10 | 10 |
Internal Mass | 10 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 36 | 36 |
Door | 12 | 12 |
Glass Door | 12 | 12 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 10 |
Conditioned Zones | 10 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 832 |
Defaulted Fields | 823 |
Fields with Defaults | 2702 |
Autosized Fields | 185 |
Autosizable Fields | 459 |
Autocalculated Fields | 128 |
Autocalculatable Fields | 256 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:37:19
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 781.98 | 2102.83 | 05-FEB-07:50 | 85321.93 | 29-JUN-14:50 |
Electricity:Building | 494.83 | 891.83 | 01-JAN-00:20 | 31518.67 | 01-JAN-11:10 |
Electricity:Zone:LGSTORE1 | 113.36 | 148.64 | 01-JAN-00:20 | 5964.88 | 01-JAN-10:10 |
Electricity:SpaceType:GENERAL | 494.83 | 891.83 | 01-JAN-00:20 | 31518.67 | 01-JAN-11:10 |
InteriorLights:Electricity | 366.68 | 450.00 | 01-JAN-00:20 | 23459.17 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:LGSTORE1 | 87.12 | 75.00 | 01-JAN-00:20 | 4621.63 | 01-JAN-10:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 366.68 | 450.00 | 01-JAN-00:20 | 23459.17 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity | 366.68 | 450.00 | 01-JAN-00:20 | 23459.17 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:LGSTORE1 | 87.12 | 75.00 | 01-JAN-00:20 | 4621.63 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 366.68 | 450.00 | 01-JAN-00:20 | 23459.17 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE1 | 66.33 | 74.32 | 01-JAN-00:20 | 3498.69 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE1 | 53.20 | 37.50 | 01-JAN-00:20 | 2827.07 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE1 | 53.20 | 37.50 | 01-JAN-00:20 | 2827.07 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE2 | 47.99 | 74.32 | 01-JAN-00:10 | 3226.84 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE2 | 37.57 | 37.50 | 01-JAN-00:10 | 2555.22 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE2 | 37.57 | 37.50 | 01-JAN-00:10 | 2555.22 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE3 | 47.99 | 74.32 | 01-JAN-00:10 | 3226.84 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE3 | 37.57 | 37.50 | 01-JAN-00:10 | 2555.22 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE3 | 37.57 | 37.50 | 01-JAN-00:10 | 2555.22 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE4 | 47.99 | 74.32 | 01-JAN-00:10 | 3226.84 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE4 | 37.57 | 37.50 | 01-JAN-00:10 | 2555.22 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE4 | 37.57 | 37.50 | 01-JAN-00:10 | 2555.22 | 01-JAN-10:10 |
Electricity:Zone:LGSTORE2 | 56.34 | 148.64 | 01-JAN-00:10 | 4070.21 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:LGSTORE2 | 37.16 | 75.00 | 01-JAN-00:10 | 2726.96 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:LGSTORE2 | 37.16 | 75.00 | 01-JAN-00:10 | 2726.96 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE5 | 28.71 | 74.32 | 01-JAN-00:10 | 2076.09 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE5 | 19.12 | 37.50 | 01-JAN-00:10 | 1404.46 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE5 | 19.12 | 37.50 | 01-JAN-00:10 | 1404.46 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE6 | 28.71 | 74.32 | 01-JAN-00:10 | 2076.09 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE6 | 19.12 | 37.50 | 01-JAN-00:10 | 1404.46 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE6 | 19.12 | 37.50 | 01-JAN-00:10 | 1404.46 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE7 | 28.71 | 74.32 | 01-JAN-00:10 | 2076.09 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE7 | 19.12 | 37.50 | 01-JAN-00:10 | 1404.46 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE7 | 19.12 | 37.50 | 01-JAN-00:10 | 1404.46 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE8 | 28.71 | 74.32 | 01-JAN-00:10 | 2076.09 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE8 | 19.12 | 37.50 | 01-JAN-00:10 | 1404.46 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE8 | 19.12 | 37.50 | 01-JAN-00:10 | 1404.46 | 01-JAN-11:10 |
InteriorEquipment:Electricity | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:LGSTORE1 | 26.25 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-10:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LGSTORE1 | 26.25 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE1 | 13.12 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE1 | 13.12 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE2 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE2 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE3 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE3 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE4 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE4 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:LGSTORE2 | 19.17 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LGSTORE2 | 19.17 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE5 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE5 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE6 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE6 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE7 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE7 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE8 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE8 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
ElectricityPurchased:Facility | 781.98 | 2102.83 | 05-FEB-07:50 | 85321.93 | 29-JUN-14:50 |
ElectricityPurchased:Plant | 781.98 | 2102.83 | 05-FEB-07:50 | 85321.93 | 29-JUN-14:50 |
Cogeneration:ElectricityPurchased | 781.98 | 2102.83 | 05-FEB-07:50 | 85321.93 | 29-JUN-14:50 |
General:Cogeneration:ElectricityPurchased | 781.98 | 2102.83 | 05-FEB-07:50 | 85321.93 | 29-JUN-14:50 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 781.98 | 2102.83 | 05-FEB-07:50 | 85321.93 | 29-JUN-14:50 |
ElectricityNet:Plant | 781.98 | 2102.83 | 05-FEB-07:50 | 85321.93 | 29-JUN-14:50 |
Cogeneration:ElectricityNet | 781.98 | 2102.83 | 05-FEB-07:50 | 85321.93 | 29-JUN-14:50 |
General:Cogeneration:ElectricityNet | 781.98 | 2102.83 | 05-FEB-07:50 | 85321.93 | 29-JUN-14:50 |
Electricity:HVAC | 159.49 | 0.00 | 02-JAN-00:40 | 50309.84 | 29-JUN-16:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 47.40 | 0.00 | 01-JAN-00:10 | 42398.65 | 29-JUN-16:10 |
General:Cooling:Electricity | 47.40 | 0.00 | 01-JAN-00:10 | 42398.65 | 29-JUN-16:10 |
Fans:Electricity | 106.71 | 0.00 | 02-JAN-00:40 | 10357.57 | 04-JAN-12:10 |
General:Fans:Electricity | 106.71 | 0.00 | 02-JAN-00:40 | 10357.57 | 04-JAN-12:10 |
ExteriorLights:Electricity | 60.38 | 0.00 | 01-JAN-08:20 | 5507.06 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 60.38 | 0.00 | 01-JAN-08:20 | 5507.06 | 01-JAN-06:10 |
HeatRecovery:Electricity | 5.38 | 0.00 | 01-JAN-00:10 | 345.24 | 01-JAN-09:10 |
General:HeatRecovery:Electricity | 5.38 | 0.00 | 01-JAN-00:10 | 345.24 | 01-JAN-09:10 |
Electricity:Plant | 67.28 | 1211.00 | 01-JAN-18:20 | 12066.72 | 27-JAN-19:00 |
WaterSystems:Electricity | 67.28 | 1211.00 | 01-JAN-18:20 | 12066.72 | 27-JAN-19:00 |
Water Heater:WaterSystems:Electricity | 67.28 | 1211.00 | 01-JAN-18:20 | 12066.72 | 27-JAN-19:00 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 1059.65 | 0.00 | 02-JAN-00:40 | 336891.44 | 04-JAN-12:10 |
NaturalGas:HVAC | 1059.65 | 0.00 | 02-JAN-00:40 | 336891.44 | 04-JAN-12:10 |
Heating:NaturalGas | 1059.65 | 0.00 | 02-JAN-00:40 | 336891.44 | 04-JAN-12:10 |
General:Heating:NaturalGas | 1059.65 | 0.00 | 02-JAN-00:40 | 336891.44 | 04-JAN-12:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water:Plant | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
WaterSystems:Water | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water Heater:WaterSystems:Water | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
MainsWater:Facility | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
MainsWater:Plant | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
WaterSystems:MainsWater | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water Heater:WaterSystems:MainsWater | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 1743.80 | 0.00 | 02-JAN-00:40 | 438279.43 | 09-JAN-08:10 |
EnergyTransfer:Building | 596.44 | 0.00 | 02-JAN-00:40 | 201876.40 | 09-JAN-08:10 |
EnergyTransfer:Zone:LGSTORE1 | 107.32 | 0.00 | 01-JAN-00:10 | 38051.94 | 09-JAN-08:10 |
Heating:EnergyTransfer | 363.61 | 0.00 | 02-JAN-00:40 | 201876.40 | 09-JAN-08:10 |
Heating:EnergyTransfer:Zone:LGSTORE1 | 59.63 | 0.00 | 01-JAN-00:10 | 38051.94 | 09-JAN-08:10 |
General:Heating:EnergyTransfer | 363.61 | 0.00 | 02-JAN-00:40 | 201876.40 | 09-JAN-08:10 |
General:Heating:EnergyTransfer:Zone:LGSTORE1 | 59.63 | 0.00 | 01-JAN-00:10 | 38051.94 | 09-JAN-08:10 |
Cooling:EnergyTransfer | 232.83 | 0.00 | 01-JAN-00:10 | 79281.14 | 30-JUN-13:00 |
Cooling:EnergyTransfer:Zone:LGSTORE1 | 47.69 | 0.00 | 01-JAN-00:10 | 21992.12 | 06-JAN-00:10 |
General:Cooling:EnergyTransfer | 232.83 | 0.00 | 01-JAN-00:10 | 79281.14 | 30-JUN-13:00 |
General:Cooling:EnergyTransfer:Zone:LGSTORE1 | 47.69 | 0.00 | 01-JAN-00:10 | 21992.12 | 06-JAN-00:10 |
EnergyTransfer:Zone:SMSTORE1 | 52.73 | 0.00 | 01-JAN-00:10 | 17173.43 | 09-JAN-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE1 | 20.75 | 0.00 | 01-JAN-00:10 | 17173.43 | 09-JAN-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE1 | 20.75 | 0.00 | 01-JAN-00:10 | 17173.43 | 09-JAN-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE1 | 31.97 | 0.00 | 01-JAN-00:10 | 7911.63 | 04-SEP-17:20 |
General:Cooling:EnergyTransfer:Zone:SMSTORE1 | 31.97 | 0.00 | 01-JAN-00:10 | 7911.63 | 04-SEP-17:20 |
EnergyTransfer:Zone:SMSTORE2 | 46.70 | 0.00 | 01-JAN-00:10 | 18781.55 | 24-DEC-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE2 | 23.98 | 0.00 | 01-JAN-00:10 | 18781.55 | 24-DEC-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE2 | 23.98 | 0.00 | 01-JAN-00:10 | 18781.55 | 24-DEC-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE2 | 22.72 | 0.00 | 01-JAN-00:10 | 7123.86 | 29-JUN-16:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE2 | 22.72 | 0.00 | 01-JAN-00:10 | 7123.86 | 29-JUN-16:10 |
EnergyTransfer:Zone:SMSTORE3 | 47.22 | 0.00 | 01-JAN-00:10 | 18856.69 | 24-DEC-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE3 | 25.30 | 0.00 | 01-JAN-00:10 | 18856.69 | 24-DEC-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE3 | 25.30 | 0.00 | 01-JAN-00:10 | 18856.69 | 24-DEC-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE3 | 21.92 | 0.00 | 01-JAN-00:10 | 7109.78 | 29-JUN-16:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE3 | 21.92 | 0.00 | 01-JAN-00:10 | 7109.78 | 29-JUN-16:10 |
EnergyTransfer:Zone:SMSTORE4 | 47.85 | 0.00 | 01-JAN-00:10 | 18750.19 | 24-DEC-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE4 | 27.53 | 0.00 | 01-JAN-00:10 | 18750.19 | 24-DEC-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE4 | 27.53 | 0.00 | 01-JAN-00:10 | 18750.19 | 24-DEC-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE4 | 20.32 | 0.00 | 01-JAN-00:10 | 6971.03 | 29-JUN-16:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE4 | 20.32 | 0.00 | 01-JAN-00:10 | 6971.03 | 29-JUN-16:10 |
EnergyTransfer:Zone:LGSTORE2 | 86.94 | 0.00 | 01-JAN-00:10 | 35343.32 | 13-JAN-08:10 |
Heating:EnergyTransfer:Zone:LGSTORE2 | 55.27 | 0.00 | 01-JAN-00:10 | 35343.32 | 13-JAN-08:10 |
General:Heating:EnergyTransfer:Zone:LGSTORE2 | 55.27 | 0.00 | 01-JAN-00:10 | 35343.32 | 13-JAN-08:10 |
Cooling:EnergyTransfer:Zone:LGSTORE2 | 31.67 | 0.00 | 01-JAN-00:10 | 12528.03 | 30-JUN-15:00 |
General:Cooling:EnergyTransfer:Zone:LGSTORE2 | 31.67 | 0.00 | 01-JAN-00:10 | 12528.03 | 30-JUN-15:00 |
EnergyTransfer:Zone:SMSTORE5 | 46.44 | 0.00 | 01-JAN-00:10 | 19501.30 | 09-JAN-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE5 | 30.72 | 0.00 | 01-JAN-00:10 | 19501.30 | 09-JAN-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE5 | 30.72 | 0.00 | 01-JAN-00:10 | 19501.30 | 09-JAN-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE5 | 15.72 | 0.00 | 01-JAN-00:10 | 6518.77 | 30-JUN-15:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE5 | 15.72 | 0.00 | 01-JAN-00:10 | 6518.77 | 30-JUN-15:00 |
EnergyTransfer:Zone:SMSTORE6 | 46.43 | 0.00 | 01-JAN-00:10 | 19546.20 | 09-JAN-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE6 | 31.22 | 0.00 | 01-JAN-00:10 | 19546.20 | 09-JAN-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE6 | 31.22 | 0.00 | 01-JAN-00:10 | 19546.20 | 09-JAN-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE6 | 15.21 | 0.00 | 01-JAN-00:10 | 6461.38 | 30-JUN-15:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE6 | 15.21 | 0.00 | 01-JAN-00:10 | 6461.38 | 30-JUN-15:00 |
EnergyTransfer:Zone:SMSTORE7 | 48.02 | 0.00 | 01-JAN-00:10 | 19984.82 | 09-JAN-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE7 | 34.16 | 0.00 | 01-JAN-00:10 | 19984.82 | 09-JAN-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE7 | 34.16 | 0.00 | 01-JAN-00:10 | 19984.82 | 09-JAN-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE7 | 13.86 | 0.00 | 01-JAN-00:10 | 6357.90 | 30-JUN-15:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE7 | 13.86 | 0.00 | 01-JAN-00:10 | 6357.90 | 30-JUN-15:00 |
EnergyTransfer:Zone:SMSTORE8 | 66.78 | 0.00 | 01-JAN-00:40 | 23894.31 | 09-JAN-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE8 | 55.04 | 0.00 | 01-JAN-00:40 | 23894.31 | 09-JAN-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE8 | 55.04 | 0.00 | 01-JAN-00:40 | 23894.31 | 09-JAN-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE8 | 11.74 | 0.00 | 01-JAN-00:10 | 6501.77 | 30-JUN-13:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE8 | 11.74 | 0.00 | 01-JAN-00:10 | 6501.77 | 30-JUN-13:00 |
EnergyTransfer:HVAC | 1147.36 | 0.00 | 02-JAN-00:40 | 269513.15 | 04-JAN-12:10 |
HeatingCoils:EnergyTransfer | 847.72 | 0.00 | 02-JAN-00:40 | 269513.15 | 04-JAN-12:10 |
CoolingCoils:EnergyTransfer | 190.51 | 0.00 | 01-JAN-00:10 | 168833.04 | 15-JUL-14:00 |
HeatRecoveryForHeating:EnergyTransfer | 105.19 | 0.00 | 01-JAN-00:10 | 15732.49 | 01-JAN-21:50 |
HeatRecoveryForCooling:EnergyTransfer | 3.95 | 0.00 | 01-JAN-00:10 | 7735.17 | 29-JUN-16:00 |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:19
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
LGSTORE1 | 0.000 | 0.000 | 59.633 | -47.690 | 0.000 | 0.000 | 25.345 | 87.116 | 26.249 | 23.126 | 0.000 | 0.870 | 0.002 | 0.000 | -11.836 | 0.000 | -57.001 | -105.813 |
SMSTORE1 | 0.000 | 0.000 | 20.754 | -31.974 | 0.000 | 0.000 | 12.698 | 53.201 | 13.125 | 11.501 | 0.000 | 0.471 | 0.000 | 0.000 | -6.100 | 0.000 | -28.115 | -45.560 |
SMSTORE2 | 0.000 | 0.000 | 23.981 | -22.723 | 0.000 | 0.000 | 7.717 | 37.572 | 10.421 | 11.489 | 0.000 | 0.465 | 0.001 | 0.000 | -6.019 | 0.000 | -28.749 | -34.154 |
SMSTORE3 | 0.000 | 0.000 | 25.301 | -21.916 | 0.000 | 0.000 | 7.725 | 37.572 | 10.421 | 11.503 | 0.000 | 0.465 | 0.004 | 0.000 | -5.968 | 0.000 | -28.684 | -36.418 |
SMSTORE4 | 0.000 | 0.000 | 27.526 | -20.324 | 0.000 | 0.000 | 7.737 | 37.572 | 10.421 | 11.523 | 0.000 | 0.465 | 0.003 | 0.000 | -5.917 | 0.000 | -28.610 | -40.392 |
LGSTORE2 | 0.000 | 0.000 | 55.270 | -31.674 | 0.000 | 0.000 | 26.591 | 37.162 | 19.173 | 23.130 | 0.000 | 0.839 | 0.003 | 0.000 | -11.547 | 0.000 | -52.398 | -66.544 |
SMSTORE5 | 0.000 | 0.000 | 30.718 | -15.724 | 0.000 | 0.000 | 13.300 | 19.120 | 9.586 | 11.545 | 0.000 | 0.466 | 0.000 | 0.000 | -5.788 | 0.000 | -28.674 | -34.550 |
SMSTORE6 | 0.000 | 0.000 | 31.215 | -15.213 | 0.000 | 0.000 | 13.308 | 19.120 | 9.586 | 11.554 | 0.000 | 0.466 | 0.000 | 0.000 | -5.771 | 0.000 | -28.646 | -35.620 |
SMSTORE7 | 0.000 | 0.000 | 34.164 | -13.856 | 0.000 | 0.000 | 13.329 | 19.120 | 9.586 | 11.581 | 0.000 | 0.467 | 0.001 | 0.000 | -5.704 | 0.000 | -28.550 | -40.139 |
SMSTORE8 | 0.000 | 0.000 | 55.044 | -11.735 | 0.000 | 0.000 | 13.370 | 19.120 | 9.586 | 11.668 | 0.000 | 0.492 | 0.000 | 0.000 | -5.430 | 0.000 | -34.902 | -57.214 |
Total Facility | 0.000 | 0.000 | 363.607 | -232.830 | 0.000 | 0.000 | 141.120 | 366.677 | 128.154 | 138.619 | 0.000 | 5.467 | 0.014 | 0.000 | -70.080 | 0.000 | -344.329 | -496.404 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
LGSTORE1 | 06-JAN-00:01 | 0.00 | 0.00 | 0.00 | -23959.41 | 0.00 | 0.00 | 231.22 | 243.23 | 746.25 | 0.00 | 0.00 | 0.00 | 24616.69 | 0.00 | -1540.56 | 0.00 | -337.43 | 0.00 |
SMSTORE1 | 21-MAY-19:06 | 0.00 | 0.00 | 0.00 | -15181.21 | 0.00 | 0.00 | 833.26 | 2827.07 | 671.63 | 0.00 | 0.00 | 0.00 | 10908.84 | 0.00 | -46.88 | 0.00 | -12.70 | 0.00 |
SMSTORE2 | 24-JUL-06:02 | 0.00 | 0.00 | 0.00 | -15629.07 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 54.52 | 0.00 | 0.00 | 15519.80 | 0.00 | -0.00 | 0.00 | -19.57 | 0.00 |
SMSTORE3 | 24-JUL-06:02 | 0.00 | 0.00 | 0.00 | -15729.17 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 53.74 | 0.00 | 0.00 | 15620.84 | 0.00 | -0.00 | 0.00 | -19.73 | 0.00 |
SMSTORE4 | 24-JUL-06:02 | 0.00 | 0.00 | 0.00 | -15489.17 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 54.88 | 0.00 | 0.00 | 15379.38 | 0.00 | -0.00 | 0.00 | -19.42 | 0.00 |
LGSTORE2 | 24-JUL-07:03 | 0.00 | 0.00 | 0.00 | -25084.29 | 0.00 | 0.00 | 0.00 | 75.00 | 73.64 | 416.74 | 0.00 | 0.00 | 24663.08 | 0.00 | -0.00 | 0.00 | -144.18 | 0.00 |
SMSTORE5 | 24-JUL-07:03 | 0.00 | 0.00 | 0.00 | -13347.16 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 209.50 | 0.00 | 0.00 | 13139.87 | 0.00 | -0.00 | 0.00 | -76.53 | 0.00 |
SMSTORE6 | 24-JUL-07:03 | 0.00 | 0.00 | 0.00 | -13288.54 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 210.28 | 0.00 | 0.00 | 13079.24 | 0.00 | -0.00 | 0.00 | -75.30 | 0.00 |
SMSTORE7 | 24-JUL-07:03 | 0.00 | 0.00 | 0.00 | -12656.31 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 212.77 | 0.00 | 0.00 | 12441.50 | 0.00 | -0.00 | 0.00 | -72.27 | 0.00 |
SMSTORE8 | 23-JUL-08:62 | 0.00 | 0.00 | 0.00 | -10651.59 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 509.42 | 0.00 | 0.00 | 10078.67 | 0.00 | -0.00 | 0.00 | -10.83 | 0.00 |
Total Facility | 24-JUL-07:03 | 0.00 | 0.00 | 0.00 | -111281.47 | 0.00 | 0.00 | 571.49 | 450.00 | 1452.23 | 2556.93 | 0.00 | 0.00 | 107138.52 | 0.00 | 0.00 | 0.00 | -887.69 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
LGSTORE1 | 06-JAN-08:61 | 0.00 | 0.00 | 68346.41 | 0.00 | 0.00 | 0.00 | 0.00 | 75.00 | 73.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1459.84 | 0.00 | -2375.61 | -64659.60 |
SMSTORE1 | 06-JAN-08:61 | 0.00 | 0.00 | 34649.59 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -746.81 | 0.00 | -1341.01 | -32636.09 |
SMSTORE2 | 25-DEC-08:61 | 0.00 | 0.00 | 34705.93 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 37.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -661.32 | 0.00 | -1246.82 | -32872.60 |
SMSTORE3 | 01-JAN-08:61 | 0.00 | 0.00 | 35397.63 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 37.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -642.84 | 0.00 | -1229.97 | -33599.63 |
SMSTORE4 | 25-DEC-08:61 | 0.00 | 0.00 | 35150.97 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 37.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -657.19 | 0.00 | -1248.16 | -33320.43 |
LGSTORE2 | 05-JAN-08:61 | 0.00 | 0.00 | 65588.69 | 0.00 | 0.00 | 0.00 | 0.00 | 75.00 | 73.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1406.88 | 0.00 | -2581.32 | -61749.13 |
SMSTORE5 | 05-JAN-08:61 | 0.00 | 0.00 | 34310.94 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -705.18 | 0.00 | -1419.53 | -32260.55 |
SMSTORE6 | 05-JAN-08:61 | 0.00 | 0.00 | 34296.09 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -705.01 | 0.00 | -1419.50 | -32245.90 |
SMSTORE7 | 05-JAN-08:61 | 0.00 | 0.00 | 34588.10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -703.37 | 0.00 | -1419.70 | -32539.35 |
SMSTORE8 | 05-JAN-08:61 | 0.00 | 0.00 | 38843.71 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -689.82 | 0.00 | -1697.81 | -36530.40 |
Total Facility | 09-JAN-08:61 | 0.00 | 0.00 | 339378.95 | 0.00 | 0.00 | 0.00 | 780.42 | 450.00 | 1452.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -8803.50 | 0.00 | -16940.14 | -316317.95 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:19
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 1.9442 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 1.9442 | 0.2217 | 1.0000 | Not calculated | 0.4115 | 0.2116 | ||
PSZ-AC_2:2 | 0.9963 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0194 | 0.2018 | 1.0000 | Not calculated | 0.2057 | 0.2018 | ||
PSZ-AC_3:3 | 0.9984 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0264 | 0.2005 | 1.0000 | Not calculated | 0.2057 | 0.2005 | ||
PSZ-AC_4:4 | 1.0301 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0301 | 0.1997 | 1.0000 | Not calculated | 0.2057 | 0.1997 | ||
PSZ-AC_5:5 | 1.0195 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0195 | 0.2018 | 1.0000 | Not calculated | 0.2057 | 0.2018 | ||
PSZ-AC_6:6 | 1.8167 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 1.8167 | 0.2308 | 1.0000 | Not calculated | 0.4115 | 0.2265 | ||
PSZ-AC_7:7 | 0.9777 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9777 | 0.2233 | 1.0000 | Not calculated | 0.2057 | 0.2104 | ||
PSZ-AC_8:8 | 0.9769 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9769 | 0.2251 | 1.0000 | Not calculated | 0.2057 | 0.2106 | ||
PSZ-AC_9:9 | 0.9898 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9898 | 0.2278 | 1.0000 | Not calculated | 0.2057 | 0.2079 | ||
PSZ-AC_10:10 | 1.1819 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.1819 | 0.2202 | 1.0000 | Not calculated | 0.2057 | 0.1741 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 1.9442 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 1.9442 | 1.0000 | 1.0000 | Not calculated | 0.4115 | 0.2116 | ||
PSZ-AC_2:2 | 0.9963 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9963 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.2065 | ||
PSZ-AC_3:3 | 0.9984 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9984 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.2061 | ||
PSZ-AC_4:4 | 1.0301 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0301 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1997 | ||
PSZ-AC_5:5 | 1.0195 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0195 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.2018 | ||
PSZ-AC_6:6 | 1.8167 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 1.8167 | 1.0000 | 1.0000 | Not calculated | 0.4115 | 0.2265 | ||
PSZ-AC_7:7 | 0.9777 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9777 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.2104 | ||
PSZ-AC_8:8 | 0.9769 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9769 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.2106 | ||
PSZ-AC_9:9 | 0.9898 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9898 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.2079 | ||
PSZ-AC_10:10 | 1.1819 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.1819 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1741 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
LGSTORE1 | PSZ-AC_1:1 | 0.000000 | 56.2505 | 0.001181 | 348.39 | 0.4115 | 1.0000 | 0.4115 | 1.000 | 0.4115 |
SMSTORE1 | PSZ-AC_2:2 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE2 | PSZ-AC_3:3 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE3 | PSZ-AC_4:4 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE4 | PSZ-AC_5:5 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
LGSTORE2 | PSZ-AC_6:6 | 0.000000 | 56.2505 | 0.001181 | 348.39 | 0.4115 | 1.0000 | 0.4115 | 1.000 | 0.4115 |
SMSTORE5 | PSZ-AC_7:7 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE6 | PSZ-AC_8:8 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE7 | PSZ-AC_9:9 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE8 | PSZ-AC_10:10 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC_1:1 | 0.000000 | 56.25 | 0.001181 | 348.3864 | 0.4115 | 0.4115 | 0.4115 |
PSZ-AC_2:2 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_3:3 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_4:4 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_5:5 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_6:6 | 0.000000 | 56.25 | 0.001181 | 348.3864 | 0.4115 | 0.4115 | 0.4115 |
PSZ-AC_7:7 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_8:8 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_9:9 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_10:10 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LGSTORE1 | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.9442 | 1.9442 | 1.9442 | No | 0.4115 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE1 | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9963 | 0.9963 | 0.9963 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE2 | PSZ-AC_3:3 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9984 | 0.9984 | 0.9984 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE3 | PSZ-AC_4:4 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0301 | 1.0301 | 1.0301 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE4 | PSZ-AC_5:5 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0195 | 1.0195 | 1.0195 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LGSTORE2 | PSZ-AC_6:6 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.8167 | 1.8167 | 1.8167 | No | 0.4115 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE5 | PSZ-AC_7:7 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9777 | 0.9777 | 0.9777 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE6 | PSZ-AC_8:8 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9769 | 0.9769 | 0.9769 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE7 | PSZ-AC_9:9 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9898 | 0.9898 | 0.9898 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE8 | PSZ-AC_10:10 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1819 | 1.1819 | 1.1819 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 1.9442 | 1.9442 | 1.9442 | 1.9442 | 0.4115 | 1.0000 |
PSZ-AC_2:2 | 0.9963 | 1.0194 | 0.9963 | 0.9963 | 0.2057 | 1.0000 |
PSZ-AC_3:3 | 0.9984 | 1.0264 | 0.9984 | 0.9984 | 0.2057 | 1.0000 |
PSZ-AC_4:4 | 1.0301 | 1.0301 | 1.0301 | 1.0301 | 0.2057 | 1.0000 |
PSZ-AC_5:5 | 1.0195 | 1.0195 | 1.0195 | 1.0195 | 0.2057 | 1.0000 |
PSZ-AC_6:6 | 1.8167 | 1.8167 | 1.8167 | 1.8167 | 0.4115 | 1.0000 |
PSZ-AC_7:7 | 0.9777 | 0.9777 | 0.9777 | 0.9777 | 0.2057 | 1.0000 |
PSZ-AC_8:8 | 0.9769 | 0.9769 | 0.9769 | 0.9769 | 0.2057 | 1.0000 |
PSZ-AC_9:9 | 0.9898 | 0.9898 | 0.9898 | 0.9898 | 0.2057 | 1.0000 |
PSZ-AC_10:10 | 1.1819 | 1.1819 | 1.1819 | 1.1819 | 0.2057 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LGSTORE1 | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.9442 | 1.9442 | 1.9442 | No | 0.4115 | 0.2116 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE1 | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9963 | 0.9963 | 0.9963 | No | 0.2057 | 0.2186 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE2 | PSZ-AC_3:3 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9984 | 0.9984 | 0.9984 | No | 0.2057 | 0.2169 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE3 | PSZ-AC_4:4 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0301 | 1.0301 | 1.0301 | No | 0.2057 | 0.2161 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE4 | PSZ-AC_5:5 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0195 | 1.0195 | 1.0195 | No | 0.2057 | 0.2144 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LGSTORE2 | PSZ-AC_6:6 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.8167 | 1.8167 | 1.8167 | No | 0.4115 | 0.2265 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE5 | PSZ-AC_7:7 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9777 | 0.9777 | 0.9777 | No | 0.2057 | 0.2104 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE6 | PSZ-AC_8:8 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9769 | 0.9769 | 0.9769 | No | 0.2057 | 0.2106 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE7 | PSZ-AC_9:9 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9898 | 0.9898 | 0.9898 | No | 0.2057 | 0.2079 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE8 | PSZ-AC_10:10 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1819 | 1.1819 | 1.1819 | No | 0.2057 | 0.1741 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 1.9442 | 1.9442 | 1.9442 | 1.9442 | 0.4115 | 1.0000 |
PSZ-AC_2:2 | 0.9963 | 0.9963 | 0.9963 | 0.9963 | 0.2057 | 1.0000 |
PSZ-AC_3:3 | 0.9984 | 0.9984 | 0.9984 | 0.9984 | 0.2057 | 1.0000 |
PSZ-AC_4:4 | 1.0301 | 1.0301 | 1.0301 | 1.0301 | 0.2057 | 1.0000 |
PSZ-AC_5:5 | 1.0195 | 1.0195 | 1.0195 | 1.0195 | 0.2057 | 1.0000 |
PSZ-AC_6:6 | 1.8167 | 1.8167 | 1.8167 | 1.8167 | 0.4115 | 1.0000 |
PSZ-AC_7:7 | 0.9777 | 0.9777 | 0.9777 | 0.9777 | 0.2057 | 1.0000 |
PSZ-AC_8:8 | 0.9769 | 0.9769 | 0.9769 | 0.9769 | 0.2057 | 1.0000 |
PSZ-AC_9:9 | 0.9898 | 0.9898 | 0.9898 | 0.9898 | 0.2057 | 1.0000 |
PSZ-AC_10:10 | 1.1819 | 1.1819 | 1.1819 | 1.1819 | 0.2057 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:19
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** International Falls Intl Ap MN USA TMY3 WMO#=727470 |
Total gross floor area [m2] | 2090.32 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
LGSTORE1 | 348.39 | 348.39 | 0.00 | 112.00 |
SMSTORE1 | 174.19 | 174.19 | 0.00 | 112.00 |
SMSTORE2 | 174.19 | 174.19 | 0.00 | 84.29 |
SMSTORE3 | 174.19 | 174.19 | 0.00 | 84.29 |
SMSTORE4 | 174.19 | 174.19 | 0.00 | 84.29 |
LGSTORE2 | 348.39 | 348.39 | 0.00 | 77.29 |
SMSTORE5 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE6 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE7 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE8 | 174.19 | 174.19 | 0.00 | 77.29 |
Totals | 2090.32 | 2090.32 | 0.00 |
Data | |
Number of hours heating loads not met | 9.00 |
Number of hours cooling loads not met | 0.00 |
Number of hours not met | 9.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 1059.65 | 336891.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 47.40 | 42398.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 366.68 | 23459.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 60.38 | 5507.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 128.15 | 8059.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 106.71 | 10357.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- General | 5.38 | 345.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 67.28 | 12066.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 128.15 | 781.98 |
Natural Gas | 0.00 | 1059.65 |
Additional | 0.00 | 0.00 |
Total | 128.15 | 1841.63 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 175.42 |
Space Heating | 0.00 |
Space Cooling | 22.68 |
Fans (All) | 51.05 |
Service Water Heating | 32.19 |
Receptacle Equipment | 61.31 |
Miscellaneous (All) | 374.10 |
Subtotal | 374.10 |
Natural Gas [MJ/m2] | |
Space Heating | 506.93 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 506.93 |
Subtotal | 506.93 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 19.91 |
Space Heating | 57.54 |
Space Cooling | 2.57 |
Fans (All) | 5.79 |
Service Water Heating | 3.65 |
Receptacle Equipment | 6.96 |
Miscellaneous | 3.57 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
TYPE1_OCC_SCH | 1630. | 5840. |
TYPE2_OCC_SCH | 995. | 4429. |
TYPE3_OCC_SCH | 1709. | 4064. |
LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 3767. | 8760. |
LTG_SCH_BASE_LPD2 | 3238. | 8760. |
LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 3296. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | 5084. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | 5084. | 8760. |
LTG_SCH_BASE_SMALL_LPD1 | 4453. | 8760. |
LTG_SCH_BASE_LPD1 | 4376. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | 3767. | 8760. |
LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 3584. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 4096. | 8760. |
TYPE1_EQUIP_SCH | 4868. | 8760. |
TYPE2_EQUIP_SCH | 3893. | 8760. |
TYPE3_EQUIP_SCH | 3584. | 8760. |
TYPE1_INFIL_SCH | 4302. | 8760. |
TYPE2_INFIL_SCH | 5164. | 8760. |
TYPE3_INFIL_SCH | 5438. | 8760. |
INFIL_DOOR_OPENING_SCH | 2477. | 4380. |
TYPE1_MINOA_MOTORIZEDDAMPER_SCH | 5579. | 5579. |
TYPE2_MINOA_MOTORIZEDDAMPER_SCH | 4429. | 4429. |
TYPE3_MINOA_MOTORIZEDDAMPER_SCH | 4064. | 4064. |
TYPE1_SWH_SCH | 2063. | 6048. |
TYPE2_SWH_SCH | 1831. | 4429. |
TYPE3_SWH_SCH | 1733. | 4064. |
AVERAGE_SWH_SCH | 1863. | 6152. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 7118. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 5839. | 5839. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 7300. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6570. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
TYPE1_HTGSETP_SCH_NO_OPTIMUM | LGSTORE1 DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
TYPE1_CLGSETP_SCH_NO_OPTIMUM | LGSTORE1 DUAL SP CONTROL | July | 23.89 | 365 | 23.89 | 365 |
TYPE2_HTGSETP_SCH_NO_OPTIMUM | SMSTORE2 DUAL SP CONTROL | January | 21.11 | 365 | 15.56 | 365 |
TYPE2_CLGSETP_SCH_NO_OPTIMUM | SMSTORE2 DUAL SP CONTROL | July | 23.89 | 365 | 29.44 | 365 |
TYPE3_HTGSETP_SCH_NO_OPTIMUM | LGSTORE2 DUAL SP CONTROL | January | 21.11 | 365 | 15.56 | 365 |
TYPE3_CLGSETP_SCH_NO_OPTIMUM | LGSTORE2 DUAL SP CONTROL | July | 23.89 | 365 | 29.44 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:19
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
LGSTORE1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 8749.33 | 10.67 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 8748.67 | 11.33 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 8751.00 | 9.00 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 8754.00 | 6.00 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 8755.17 | 4.83 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 8755.50 | 4.50 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 8756.33 | 3.67 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 8756.50 | 3.50 | 0.00 | 0.00 | 0.00 |
Min | 8748.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 11.33 | 0.00 | 0.00 | 0.00 |
Average | 8754.65 | 5.35 | 0.00 | 0.00 | 0.00 |
Sum | 87546.50 | 53.50 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
LGSTORE1 | 89041.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 43777.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 25471.67 | 3.33 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 25471.67 | 3.33 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 25472.00 | 3.00 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 93199.00 | 12.00 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 45906.50 | 5.50 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 45906.50 | 5.50 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 45907.00 | 5.00 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 45907.50 | 4.50 | 0.00 | 0.00 | 0.00 |
Min | 25471.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 93199.00 | 12.00 | 0.00 | 0.00 | 0.00 |
Average | 48605.98 | 4.22 | 0.00 | 0.00 | 0.00 |
Sum | 486059.83 | 42.17 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
LGSTORE1 | 8364.67 | 395.33 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 8544.67 | 215.33 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 8181.17 | 578.83 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 8187.83 | 572.17 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 8207.33 | 552.67 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 8216.50 | 543.50 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 8221.17 | 538.83 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 8226.67 | 533.33 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 8236.17 | 523.83 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 8298.33 | 461.67 | 0.00 | 0.00 | 0.00 |
Min | 8181.17 | 215.33 | 0.00 | 0.00 | 0.00 |
Max | 8544.67 | 578.83 | 0.00 | 0.00 | 0.00 |
Average | 8268.45 | 491.55 | 0.00 | 0.00 | 0.00 |
Sum | 82684.50 | 4915.50 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
LGSTORE1 | 86855.00 | 2186.00 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 42950.50 | 826.50 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 24756.17 | 718.83 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 24754.00 | 721.00 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 24740.33 | 734.67 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 89625.83 | 3585.17 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 44109.33 | 1802.67 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 44079.67 | 1832.33 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 43953.83 | 1958.17 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 43816.00 | 2096.00 | 0.00 | 0.00 | 0.00 |
Min | 24740.33 | 718.83 | 0.00 | 0.00 | 0.00 |
Max | 89625.83 | 3585.17 | 0.00 | 0.00 | 0.00 |
Average | 46964.07 | 1646.13 | 0.00 | 0.00 | 0.00 |
Sum | 469640.67 | 16461.33 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:19
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:19
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
For: Environment
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTRIPMALL
For: Environment
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 7
For: Environment
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_INTERNATIONALFALLS
For: Environment
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: ZoneCoolingSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.224179E+09 | 23959.48 | 06-JAN-00:01 | -32.3 | -32.4 | 0.106463E+10 | 1275.40 | 28-JAN-13:09 | -10.4 | -11.7 |
February | 0.272273E+09 | 20118.83 | 25-FEB-00:01 | -24.1 | -24.4 | 0.961331E+09 | 1288.80 | 20-FEB-18:30 | -24.1 | -24.4 |
March | 0.405146E+09 | 4422.03 | 03-MAR-00:12 | -17.6 | -17.8 | 0.106341E+10 | 1506.06 | 26-MAR-17:00 | 8.90 | 4.40 |
April | 0.138322E+10 | 6754.93 | 23-APR-16:03 | 26.60 | 16.90 | 0.113358E+10 | 1685.96 | 23-APR-17:10 | 26.02 | 16.64 |
May | 0.521917E+10 | 10224.72 | 25-MAY-16:10 | 29.12 | 19.57 | 0.136771E+10 | 1685.89 | 28-MAY-12:00 | 21.30 | 13.54 |
June | 0.820175E+10 | 22345.90 | 29-JUN-07:03 | 24.72 | 20.63 | 0.135241E+10 | 1686.06 | 30-JUN-12:00 | 31.70 | 24.46 |
July | 0.113730E+11 | 23781.17 | 04-JUL-07:03 | 22.70 | 19.72 | 0.141247E+10 | 1686.00 | 14-JUL-12:00 | 25.60 | 20.23 |
August | 0.105339E+11 | 22376.97 | 09-AUG-07:03 | 19.68 | 18.07 | 0.139306E+10 | 1686.00 | 11-AUG-12:00 | 24.40 | 18.25 |
September | 0.643037E+10 | 11448.71 | 01-SEP-16:10 | 25.82 | 17.71 | 0.134905E+10 | 1685.98 | 01-SEP-12:30 | 25.82 | 17.71 |
October | 0.275401E+10 | 7322.57 | 22-OCT-17:10 | 16.13 | 10.55 | 0.122010E+10 | 1685.88 | 22-OCT-16:19 | 16.13 | 10.55 |
November | 0.737310E+09 | 4076.70 | 25-NOV-00:12 | -15.0 | -15.5 | 0.104358E+10 | 1391.90 | 01-NOV-17:49 | -15.0 | -15.5 |
December | 0.156070E+09 | 18145.48 | 02-DEC-00:33 | -23.9 | -24.2 | 0.107032E+10 | 1275.41 | 08-DEC-13:09 | -13.0 | -13.9 |
Annual Sum or Average | 0.476905E+11 | 0.144317E+11 | ||||||||
Minimum of Months | 0.156070E+09 | 4076.70 | -32.3 | -32.4 | 0.961331E+09 | 1275.40 | -24.1 | -24.4 | ||
Maximum of Months | 0.113730E+11 | 23959.48 | 29.12 | 20.63 | 0.141247E+10 | 1686.06 | 31.70 | 24.46 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 31953413.89 | 8764.61 | 26-JAN-20:31 | -18.7 | -19.4 | 0.534476E+09 | 678.84 | 29-JAN-18:00 | -3.3 | -4.1 |
February | 0.140362E+09 | 6932.83 | 15-FEB-20:02 | -11.1 | -11.9 | 0.485519E+09 | 725.59 | 20-FEB-18:00 | 4.40 | 1.28 |
March | 0.401152E+09 | 4985.89 | 11-MAR-11:53 | -2.8 | -4.9 | 0.538804E+09 | 817.34 | 26-MAR-17:00 | 8.90 | 4.40 |
April | 0.146366E+10 | 12531.97 | 23-APR-20:27 | 20.55 | 13.80 | 0.567189E+09 | 842.95 | 23-APR-17:10 | 20.55 | 13.80 |
May | 0.403065E+10 | 15181.30 | 21-MAY-19:06 | 18.43 | 9.85 | 0.670055E+09 | 842.92 | 28-MAY-12:00 | 21.30 | 13.54 |
June | 0.529838E+10 | 14689.16 | 17-JUN-20:55 | 17.20 | 10.46 | 0.672104E+09 | 842.97 | 25-JUN-12:50 | 23.45 | 20.02 |
July | 0.677495E+10 | 14328.35 | 24-JUL-07:03 | 20.97 | 18.41 | 0.704346E+09 | 843.10 | 04-JUL-17:19 | 20.97 | 18.41 |
August | 0.630437E+10 | 14592.47 | 09-AUG-07:03 | 19.68 | 18.07 | 0.694077E+09 | 842.97 | 27-AUG-16:10 | 23.72 | 19.07 |
September | 0.449187E+10 | 13576.79 | 04-SEP-17:54 | 14.40 | 8.97 | 0.657499E+09 | 842.98 | 03-SEP-16:00 | 14.40 | 8.97 |
October | 0.239381E+10 | 4418.35 | 29-OCT-08:32 | -0.2 | -1.0 | 0.596213E+09 | 842.93 | 22-OCT-12:00 | -0.2 | -1.0 |
November | 0.599410E+09 | 4559.65 | 13-NOV-11:13 | -0.9 | -4.5 | 0.531975E+09 | 743.59 | 19-NOV-18:40 | 1.47 | -0.7 |
December | 44021951.15 | 1016.45 | 05-DEC-20:10 | 0.00 | -0.0 | 0.537620E+09 | 679.55 | 31-DEC-18:00 | -5.6 | -5.9 |
Annual Sum or Average | 0.319746E+11 | 0.718988E+10 | ||||||||
Minimum of Months | 31953413.89 | 1016.45 | -18.7 | -19.4 | 0.485519E+09 | 678.84 | -5.6 | -5.9 | ||
Maximum of Months | 0.677495E+10 | 15181.30 | 20.97 | 18.41 | 0.704346E+09 | 843.10 | 23.72 | 20.02 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 3276603.43 | 454.92 | 19-JAN-19:00 | -3.3 | -3.9 | 0.317182E+09 | 637.68 | 07-JAN-13:39 | -3.3 | -3.9 |
February | 58288013.92 | 5938.94 | 23-FEB-10:42 | -6.8 | -8.0 | 0.288104E+09 | 637.68 | 04-FEB-13:09 | -6.8 | -8.0 |
March | 0.205521E+09 | 5971.70 | 17-MAR-19:42 | -6.9 | -9.4 | 0.325612E+09 | 637.68 | 11-MAR-13:20 | -6.9 | -9.4 |
April | 0.104695E+10 | 4946.47 | 13-APR-07:01 | -1.8 | -3.5 | 0.326566E+09 | 778.11 | 22-APR-12:00 | 16.10 | 6.66 |
May | 0.289192E+10 | 8113.56 | 26-MAY-06:03 | 19.50 | 15.70 | 0.394286E+09 | 842.92 | 27-MAY-12:00 | 21.90 | 13.70 |
June | 0.379280E+10 | 12674.69 | 29-JUN-06:03 | 23.17 | 19.92 | 0.410928E+09 | 842.96 | 24-JUN-12:00 | 23.17 | 19.92 |
July | 0.485339E+10 | 15637.83 | 24-JUL-06:02 | 18.68 | 16.82 | 0.418646E+09 | 842.98 | 22-JUL-12:39 | 18.68 | 16.82 |
August | 0.458007E+10 | 15050.36 | 10-AUG-06:03 | 15.10 | 14.70 | 0.428974E+09 | 842.96 | 26-AUG-12:09 | 25.10 | 19.13 |
September | 0.323458E+10 | 10186.63 | 01-SEP-06:03 | 16.10 | 15.79 | 0.382867E+09 | 842.95 | 02-SEP-12:00 | 20.00 | 14.38 |
October | 0.167456E+10 | 5019.75 | 25-OCT-07:42 | -2.9 | -2.9 | 0.335432E+09 | 842.90 | 21-OCT-12:00 | -2.9 | -2.9 |
November | 0.373712E+09 | 5789.63 | 27-NOV-18:42 | -6.1 | -6.9 | 0.307783E+09 | 637.68 | 18-NOV-13:09 | -6.1 | -6.9 |
December | 7703152.29 | 4992.38 | 04-DEC-18:23 | -2.8 | -3.4 | 0.316799E+09 | 637.68 | 02-DEC-13:50 | -2.8 | -3.4 |
Annual Sum or Average | 0.227228E+11 | 0.425318E+10 | ||||||||
Minimum of Months | 3276603.43 | 454.92 | -6.9 | -9.4 | 0.288104E+09 | 637.68 | -6.9 | -9.4 | ||
Maximum of Months | 0.485339E+10 | 15637.83 | 23.17 | 19.92 | 0.428974E+09 | 842.98 | 25.10 | 19.92 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 2062394.67 | 356.81 | 19-JAN-19:00 | -3.3 | -3.9 | 0.317182E+09 | 637.68 | 07-JAN-13:30 | -3.3 | -3.9 |
February | 41781444.17 | 8110.02 | 10-FEB-18:52 | -16.1 | -16.9 | 0.288097E+09 | 637.68 | 18-FEB-13:39 | -11.7 | -12.9 |
March | 0.174451E+09 | 5918.48 | 17-MAR-10:52 | -6.7 | -8.4 | 0.325605E+09 | 637.68 | 04-MAR-13:09 | -6.7 | -8.4 |
April | 0.930740E+09 | 6027.23 | 04-APR-18:52 | -7.2 | -9.9 | 0.325197E+09 | 768.70 | 22-APR-12:00 | 16.10 | 6.66 |
May | 0.275292E+10 | 7983.99 | 26-MAY-06:03 | 19.50 | 15.70 | 0.392133E+09 | 842.92 | 27-MAY-12:00 | 21.90 | 13.70 |
June | 0.370340E+10 | 12716.03 | 29-JUN-06:03 | 23.17 | 19.92 | 0.410046E+09 | 842.96 | 24-JUN-12:00 | 23.17 | 19.92 |
July | 0.483385E+10 | 15738.00 | 24-JUL-06:02 | 18.68 | 16.82 | 0.418559E+09 | 843.00 | 22-JUL-12:50 | 18.68 | 16.82 |
August | 0.453842E+10 | 15098.42 | 10-AUG-06:03 | 15.10 | 14.70 | 0.428762E+09 | 842.96 | 26-AUG-12:09 | 25.10 | 19.13 |
September | 0.310599E+10 | 10195.73 | 01-SEP-06:03 | 16.10 | 15.79 | 0.380784E+09 | 842.95 | 02-SEP-12:00 | 20.00 | 14.38 |
October | 0.150287E+10 | 4168.38 | 21-OCT-07:03 | 2.67 | 2.14 | 0.334058E+09 | 842.90 | 21-OCT-12:00 | 19.40 | 11.32 |
November | 0.322623E+09 | 6849.71 | 28-NOV-18:02 | -10.8 | -11.5 | 0.307622E+09 | 637.68 | 18-NOV-13:09 | -10.8 | -11.5 |
December | 6615862.44 | 4363.66 | 05-DEC-19:03 | 0.00 | -0.0 | 0.316799E+09 | 637.68 | 02-DEC-13:39 | 0.00 | -0.0 |
Annual Sum or Average | 0.219157E+11 | 0.424484E+10 | ||||||||
Minimum of Months | 2062394.67 | 356.81 | -16.1 | -16.9 | 0.288097E+09 | 637.68 | -11.7 | -12.9 | ||
Maximum of Months | 0.483385E+10 | 15738.00 | 23.17 | 19.92 | 0.428762E+09 | 843.00 | 25.10 | 19.92 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 2036363.47 | 6596.53 | 20-JAN-18:12 | -9.6 | -10.3 | 0.317182E+09 | 637.68 | 07-JAN-13:09 | -9.6 | -10.3 |
February | 25700277.91 | 4225.78 | 21-FEB-19:33 | 0.60 | -0.6 | 0.288104E+09 | 637.68 | 04-FEB-13:00 | 0.60 | -0.6 |
March | 0.124527E+09 | 4648.73 | 22-MAR-18:12 | -1.3 | -3.5 | 0.325599E+09 | 637.68 | 04-MAR-13:39 | -1.3 | -3.5 |
April | 0.781300E+09 | 4640.98 | 02-APR-10:43 | -1.3 | -4.6 | 0.323369E+09 | 755.78 | 22-APR-12:00 | 16.10 | 6.66 |
May | 0.251750E+10 | 6323.48 | 26-MAY-06:03 | 19.50 | 15.70 | 0.389029E+09 | 842.92 | 27-MAY-12:00 | 21.90 | 13.70 |
June | 0.347328E+10 | 12456.60 | 29-JUN-06:03 | 23.17 | 19.92 | 0.408380E+09 | 842.90 | 24-JUN-12:09 | 23.17 | 19.92 |
July | 0.462718E+10 | 15497.82 | 24-JUL-06:02 | 18.68 | 16.82 | 0.418201E+09 | 842.99 | 22-JUL-12:50 | 18.68 | 16.82 |
August | 0.432578E+10 | 14346.70 | 09-AUG-06:03 | 18.98 | 17.80 | 0.428162E+09 | 842.96 | 26-AUG-12:09 | 25.10 | 19.13 |
September | 0.289833E+10 | 8958.81 | 01-SEP-06:03 | 16.10 | 15.79 | 0.378068E+09 | 842.95 | 02-SEP-12:00 | 20.00 | 14.38 |
October | 0.130572E+10 | 4111.17 | 21-OCT-07:03 | 2.67 | 2.14 | 0.332776E+09 | 842.90 | 21-OCT-12:00 | 19.40 | 11.32 |
November | 0.240901E+09 | 5409.32 | 07-NOV-10:43 | -4.7 | -6.8 | 0.307402E+09 | 637.68 | 18-NOV-13:09 | 5.00 | 1.49 |
December | 2112557.39 | 303.36 | 28-DEC-18:10 | -3.1 | -4.5 | 0.316799E+09 | 637.68 | 02-DEC-13:30 | -3.1 | -4.5 |
Annual Sum or Average | 0.203244E+11 | 0.423307E+10 | ||||||||
Minimum of Months | 2036363.47 | 303.36 | -9.6 | -10.3 | 0.288104E+09 | 637.68 | -9.6 | -10.3 | ||
Maximum of Months | 0.462718E+10 | 15497.82 | 23.17 | 19.92 | 0.428162E+09 | 842.99 | 25.10 | 19.92 |
Report: ZoneCoolingSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 7391.30 | 70.80 | 30-JAN-08:04 | -4.7 | -5.1 | 0.108442E+10 | 1700.53 | 14-JAN-15:30 | -4.7 | -5.1 |
February | 3170730.58 | 798.64 | 08-FEB-12:00 | 3.30 | -1.4 | 0.987309E+09 | 1700.53 | 04-FEB-15:39 | 3.30 | -1.4 |
March | 81686920.25 | 2599.77 | 31-MAR-17:10 | 8.80 | 3.21 | 0.111839E+10 | 1700.53 | 04-MAR-15:09 | 8.80 | 3.21 |
April | 0.104224E+10 | 7884.75 | 27-APR-19:03 | 1.93 | -1.5 | 0.110213E+10 | 2152.27 | 22-APR-14:00 | 1.93 | -1.5 |
May | 0.387015E+10 | 9279.04 | 25-MAY-15:00 | 28.90 | 19.67 | 0.131586E+10 | 2247.87 | 27-MAY-14:00 | 22.20 | 14.09 |
June | 0.556805E+10 | 21484.15 | 29-JUN-07:03 | 24.72 | 20.63 | 0.139127E+10 | 2247.83 | 24-JUN-14:30 | 24.72 | 20.63 |
July | 0.758829E+10 | 25097.59 | 24-JUL-07:03 | 20.97 | 18.41 | 0.143071E+10 | 2248.02 | 29-JUL-14:50 | 29.90 | 21.16 |
August | 0.703035E+10 | 22973.58 | 09-AUG-07:03 | 19.68 | 18.07 | 0.146458E+10 | 2247.92 | 19-AUG-14:20 | 21.87 | 14.61 |
September | 0.452262E+10 | 12374.42 | 01-SEP-07:03 | 16.38 | 15.95 | 0.128488E+10 | 2247.83 | 30-SEP-14:00 | 21.10 | 13.68 |
October | 0.178619E+10 | 7544.66 | 05-OCT-09:43 | 2.70 | 0.36 | 0.113117E+10 | 2247.80 | 21-OCT-14:09 | 20.00 | 11.42 |
November | 0.181929E+09 | 9352.53 | 03-NOV-18:42 | -1.0 | -2.5 | 0.104681E+10 | 1700.53 | 04-NOV-14:09 | -1.2 | -3.2 |
December | 15592.10 | 132.27 | 17-DEC-09:04 | -0.5 | -0.6 | 0.108625E+10 | 1700.53 | 02-DEC-15:50 | -0.5 | -0.6 |
Annual Sum or Average | 0.316747E+11 | 0.144438E+11 | ||||||||
Minimum of Months | 7391.30 | 70.80 | -4.7 | -5.1 | 0.987309E+09 | 1700.53 | -4.7 | -5.1 | ||
Maximum of Months | 0.758829E+10 | 25097.59 | 28.90 | 20.63 | 0.146458E+10 | 2248.02 | 29.90 | 21.16 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 1649.02 | 27.48 | 30-JAN-08:04 | -4.7 | -5.1 | 0.542193E+09 | 850.24 | 07-JAN-15:09 | -4.7 | -5.1 |
February | 1184859.09 | 353.50 | 08-FEB-12:00 | 3.30 | -1.4 | 0.493640E+09 | 850.24 | 04-FEB-15:50 | 3.30 | -1.4 |
March | 39625336.88 | 5041.55 | 17-MAR-17:33 | -2.9 | -6.5 | 0.559181E+09 | 850.24 | 11-MAR-15:09 | -2.9 | -6.5 |
April | 0.475078E+09 | 2881.09 | 10-APR-19:23 | 6.40 | 0.44 | 0.550160E+09 | 1065.30 | 22-APR-14:00 | 18.30 | 7.82 |
May | 0.187223E+10 | 4796.03 | 25-MAY-15:00 | 28.90 | 19.67 | 0.656209E+09 | 1123.90 | 27-MAY-14:00 | 22.20 | 14.09 |
June | 0.277808E+10 | 11415.22 | 29-JUN-07:03 | 24.72 | 20.63 | 0.694589E+09 | 1123.90 | 24-JUN-14:09 | 24.72 | 20.63 |
July | 0.385893E+10 | 13354.73 | 24-JUL-07:03 | 20.97 | 18.41 | 0.715209E+09 | 1123.99 | 22-JUL-14:20 | 20.97 | 18.41 |
August | 0.355401E+10 | 10752.03 | 09-AUG-07:03 | 19.68 | 18.07 | 0.732149E+09 | 1123.93 | 26-AUG-14:09 | 26.10 | 19.38 |
September | 0.221256E+10 | 5674.91 | 01-SEP-07:03 | 16.38 | 15.95 | 0.641636E+09 | 1123.88 | 30-SEP-14:00 | 21.10 | 13.68 |
October | 0.849673E+09 | 4520.83 | 31-OCT-17:42 | -0.6 | -3.0 | 0.565321E+09 | 1123.87 | 21-OCT-14:09 | -0.6 | -3.0 |
November | 83010093.94 | 5759.03 | 10-NOV-18:22 | -5.8 | -7.7 | 0.523322E+09 | 850.24 | 04-NOV-14:09 | -5.8 | -7.7 |
December | 3215.38 | 53.46 | 17-DEC-09:04 | -0.5 | -0.6 | 0.543112E+09 | 850.24 | 02-DEC-15:20 | -0.5 | -0.6 |
Annual Sum or Average | 0.157244E+11 | 0.721672E+10 | ||||||||
Minimum of Months | 1649.02 | 27.48 | -5.8 | -7.7 | 0.493640E+09 | 850.24 | -5.8 | -7.7 | ||
Maximum of Months | 0.385893E+10 | 13354.73 | 28.90 | 20.63 | 0.732149E+09 | 1123.99 | 26.10 | 20.63 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 1734.48 | 28.91 | 30-JAN-08:04 | -4.7 | -5.1 | 0.542193E+09 | 850.24 | 07-JAN-15:30 | -4.7 | -5.1 |
February | 2152822.62 | 3573.28 | 28-FEB-18:13 | 3.33 | -0.7 | 0.493640E+09 | 850.24 | 04-FEB-15:50 | 3.33 | -0.7 |
March | 32763761.72 | 4597.81 | 23-MAR-18:15 | -1.0 | -4.4 | 0.559180E+09 | 850.24 | 04-MAR-15:09 | -1.0 | -4.4 |
April | 0.441958E+09 | 3696.38 | 28-APR-10:23 | 2.80 | -1.2 | 0.549176E+09 | 1058.22 | 22-APR-14:00 | 2.80 | -1.2 |
May | 0.178074E+10 | 4684.16 | 25-MAY-15:00 | 28.90 | 19.67 | 0.653950E+09 | 1123.90 | 27-MAY-14:00 | 22.20 | 14.09 |
June | 0.268548E+10 | 11353.64 | 29-JUN-07:03 | 24.72 | 20.63 | 0.692861E+09 | 1123.91 | 24-JUN-14:09 | 24.72 | 20.63 |
July | 0.377931E+10 | 13296.09 | 24-JUL-07:03 | 20.97 | 18.41 | 0.714965E+09 | 1123.99 | 22-JUL-14:39 | 20.97 | 18.41 |
August | 0.347734E+10 | 10118.83 | 09-AUG-07:03 | 19.68 | 18.07 | 0.731646E+09 | 1123.93 | 26-AUG-14:09 | 26.10 | 19.38 |
September | 0.213669E+10 | 5494.62 | 01-SEP-15:00 | 26.10 | 17.82 | 0.640030E+09 | 1123.88 | 30-SEP-14:00 | 21.10 | 13.68 |
October | 0.803298E+09 | 4274.91 | 25-OCT-09:02 | 0.55 | 0.51 | 0.564820E+09 | 1123.87 | 21-OCT-14:09 | 0.55 | 0.51 |
November | 73844446.48 | 3527.49 | 14-NOV-19:43 | 3.58 | 2.29 | 0.523264E+09 | 850.24 | 04-NOV-14:00 | 3.58 | 2.29 |
December | 3211.22 | 53.52 | 17-DEC-09:04 | -0.5 | -0.6 | 0.543112E+09 | 850.24 | 02-DEC-15:09 | -0.5 | -0.6 |
Annual Sum or Average | 0.152136E+11 | 0.720884E+10 | ||||||||
Minimum of Months | 1734.48 | 28.91 | -4.7 | -5.1 | 0.493640E+09 | 850.24 | -4.7 | -5.1 | ||
Maximum of Months | 0.377931E+10 | 13296.09 | 28.90 | 20.63 | 0.731646E+09 | 1123.99 | 26.10 | 20.63 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 1318.94 | 21.98 | 20-JAN-08:04 | -7.9 | -8.4 | 0.542193E+09 | 850.24 | 07-JAN-15:39 | -7.9 | -8.4 |
February | 30086.13 | 57.69 | 05-FEB-09:04 | -2.2 | -3.2 | 0.493640E+09 | 850.24 | 04-FEB-15:30 | -2.2 | -3.2 |
March | 16220000.25 | 3028.64 | 27-MAR-18:13 | 5.73 | 1.94 | 0.559179E+09 | 850.24 | 04-MAR-15:00 | 5.73 | 1.94 |
April | 0.336241E+09 | 3227.18 | 01-APR-10:43 | 4.90 | 2.53 | 0.546420E+09 | 1037.51 | 22-APR-14:00 | 18.30 | 7.82 |
May | 0.152619E+10 | 4397.24 | 25-MAY-15:00 | 28.90 | 19.67 | 0.647925E+09 | 1123.90 | 27-MAY-14:00 | 22.20 | 14.09 |
June | 0.245234E+10 | 10922.18 | 30-JUN-07:02 | 26.02 | 21.73 | 0.688371E+09 | 1123.93 | 24-JUN-14:09 | 26.02 | 21.73 |
July | 0.357887E+10 | 12663.29 | 24-JUL-07:03 | 20.97 | 18.41 | 0.714137E+09 | 1123.97 | 22-JUL-14:00 | 20.97 | 18.41 |
August | 0.328291E+10 | 8256.78 | 09-AUG-07:03 | 19.68 | 18.07 | 0.730049E+09 | 1123.94 | 26-AUG-14:09 | 26.10 | 19.38 |
September | 0.194377E+10 | 5395.71 | 01-SEP-15:00 | 26.10 | 17.82 | 0.635933E+09 | 1123.87 | 09-SEP-14:30 | 18.05 | 10.28 |
October | 0.669911E+09 | 4153.51 | 13-OCT-18:03 | 1.02 | -0.3 | 0.563498E+09 | 1123.87 | 21-OCT-14:00 | 20.00 | 11.16 |
November | 49461878.94 | 4376.19 | 16-NOV-19:23 | 0.00 | -2.4 | 0.523051E+09 | 850.24 | 04-NOV-14:30 | 0.00 | -2.4 |
December | 12135.06 | 70.35 | 17-DEC-09:04 | -0.5 | -0.6 | 0.543112E+09 | 850.24 | 09-DEC-15:20 | -0.5 | -0.6 |
Annual Sum or Average | 0.138560E+11 | 0.718751E+10 | ||||||||
Minimum of Months | 1318.94 | 21.98 | -7.9 | -8.4 | 0.493640E+09 | 850.24 | -7.9 | -8.4 | ||
Maximum of Months | 0.357887E+10 | 12663.29 | 28.90 | 21.73 | 0.730049E+09 | 1123.97 | 26.10 | 21.73 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | -21.9 | -22.1 | 0.542193E+09 | 850.24 | 07-JAN-15:30 | -16.9 | -17.6 |
February | 13009.76 | 116.56 | 21-FEB-08:04 | 2.57 | 1.09 | 0.493640E+09 | 850.24 | 11-FEB-15:50 | 2.57 | 1.09 |
March | 25747.92 | 117.82 | 28-MAR-07:04 | 1.88 | 0.39 | 0.559181E+09 | 850.24 | 11-MAR-15:09 | 1.88 | 0.39 |
April | 0.139055E+09 | 1541.81 | 11-APR-18:55 | 11.70 | 4.37 | 0.541600E+09 | 990.67 | 22-APR-14:00 | 18.30 | 7.82 |
May | 0.101183E+10 | 4164.84 | 18-MAY-14:40 | 28.77 | 16.65 | 0.636628E+09 | 1123.90 | 27-MAY-14:00 | 22.20 | 14.09 |
June | 0.210902E+10 | 10329.10 | 30-JUN-07:02 | 26.02 | 21.73 | 0.679629E+09 | 1123.88 | 17-JUN-14:00 | 26.02 | 21.73 |
July | 0.341095E+10 | 10657.34 | 23-JUL-08:62 | 23.58 | 21.22 | 0.711666E+09 | 1123.97 | 15-JUL-14:50 | 23.58 | 21.22 |
August | 0.306585E+10 | 6062.99 | 08-AUG-14:50 | 30.50 | 23.28 | 0.725630E+09 | 1123.93 | 05-AUG-14:09 | 30.50 | 23.28 |
September | 0.158902E+10 | 5507.41 | 01-SEP-14:20 | 25.77 | 18.01 | 0.629062E+09 | 1123.85 | 30-SEP-14:50 | 20.92 | 13.53 |
October | 0.395759E+09 | 2578.75 | 20-OCT-19:50 | 7.98 | 5.25 | 0.561961E+09 | 1123.84 | 21-OCT-14:09 | 20.00 | 11.42 |
November | 13527454.69 | 1775.40 | 17-NOV-13:55 | 10.60 | 3.43 | 0.522694E+09 | 850.24 | 04-NOV-14:20 | 10.60 | 3.43 |
December | 5294.42 | 88.24 | 06-DEC-08:04 | -3.3 | -3.3 | 0.543112E+09 | 850.24 | 09-DEC-15:30 | -17.6 | -18.7 |
Annual Sum or Average | 0.117351E+11 | 0.714700E+10 | ||||||||
Minimum of Months | 0.00 | 0.00 | -21.9 | -22.1 | 0.493640E+09 | 850.24 | -17.6 | -18.7 | ||
Maximum of Months | 0.341095E+10 | 10657.34 | 30.50 | 23.28 | 0.725630E+09 | 1123.97 | 30.50 | 23.28 |
Report: ZoneHeatingSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.167969E+11 | 68346.43 | 06-JAN-08:61 | -35.1 |
February | 0.106022E+11 | 68209.52 | 14-FEB-08:61 | -31.2 |
March | 0.846743E+10 | 68162.87 | 12-MAR-07:01 | -24.5 |
April | 0.251671E+10 | 68095.10 | 05-APR-07:01 | -11.2 |
May | 0.138090E+09 | 68059.28 | 01-MAY-07:01 | -0.9 |
June | 49310537.78 | 1471.67 | 29-JUN-07:05 | 24.72 |
July | 24029913.59 | 1512.28 | 04-JUL-07:05 | 22.70 |
August | 22031133.52 | 1426.67 | 09-AUG-07:05 | 19.68 |
September | 63896677.99 | 1190.79 | 01-SEP-07:07 | 16.38 |
October | 0.790466E+09 | 68073.02 | 30-OCT-07:01 | -9.0 |
November | 0.496985E+10 | 68084.67 | 25-NOV-08:61 | -18.2 |
December | 0.151919E+11 | 68247.08 | 24-DEC-08:61 | -31.1 |
Annual Sum or Average | 0.596328E+11 | |||
Minimum of Months | 22031133.52 | 1190.79 | -35.1 | |
Maximum of Months | 0.167969E+11 | 68346.43 | 24.72 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.624126E+10 | 34649.65 | 06-JAN-08:61 | -35.1 |
February | 0.361104E+10 | 34635.44 | 25-FEB-08:61 | -28.1 |
March | 0.268787E+10 | 34623.16 | 12-MAR-07:01 | -24.5 |
April | 0.631761E+09 | 34590.54 | 05-APR-07:01 | -11.2 |
May | 42248607.54 | 33462.89 | 01-MAY-07:01 | -0.9 |
June | 16811645.89 | 821.59 | 29-JUN-07:05 | 24.72 |
July | 12739824.48 | 870.95 | 24-JUL-07:05 | 20.97 |
August | 14696165.72 | 884.80 | 09-AUG-07:05 | 19.68 |
September | 25974130.38 | 768.32 | 01-SEP-07:07 | 16.38 |
October | 0.203995E+09 | 34578.50 | 30-OCT-07:01 | -9.0 |
November | 0.159384E+10 | 34589.17 | 25-NOV-08:61 | -18.2 |
December | 0.567234E+10 | 34633.96 | 21-DEC-08:61 | -28.4 |
Annual Sum or Average | 0.207546E+11 | |||
Minimum of Months | 12739824.48 | 768.32 | -35.1 | |
Maximum of Months | 0.624126E+10 | 34649.65 | 24.72 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.691071E+10 | 34665.66 | 01-JAN-08:61 | -26.7 |
February | 0.416032E+10 | 34657.15 | 19-FEB-08:61 | -23.5 |
March | 0.313295E+10 | 34675.10 | 12-MAR-07:01 | -24.5 |
April | 0.845202E+09 | 34615.92 | 05-APR-06:01 | -13.5 |
May | 58084842.58 | 34125.25 | 01-MAY-06:01 | -3.5 |
June | 30199747.63 | 1815.42 | 29-JUN-19:03 | 30.73 |
July | 29823522.48 | 1561.31 | 23-JUL-16:02 | 29.72 |
August | 15936157.41 | 896.54 | 10-AUG-06:05 | 15.10 |
September | 27184301.67 | 1609.49 | 23-SEP-07:07 | 4.37 |
October | 0.383336E+09 | 34332.04 | 30-OCT-06:01 | -9.4 |
November | 0.207942E+10 | 34638.96 | 12-NOV-08:61 | -8.1 |
December | 0.630782E+10 | 34705.93 | 25-DEC-08:61 | -27.8 |
Annual Sum or Average | 0.239810E+11 | |||
Minimum of Months | 15936157.41 | 896.54 | -27.8 | |
Maximum of Months | 0.691071E+10 | 34705.93 | 30.73 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.719767E+10 | 35397.64 | 01-JAN-08:61 | -26.7 |
February | 0.436055E+10 | 35328.69 | 19-FEB-08:61 | -23.5 |
March | 0.331860E+10 | 35346.37 | 12-MAR-07:01 | -24.5 |
April | 0.939933E+09 | 35286.72 | 05-APR-06:01 | -13.5 |
May | 68771800.05 | 34786.32 | 01-MAY-06:01 | -3.5 |
June | 32166033.27 | 1817.08 | 29-JUN-19:03 | 30.73 |
July | 30387201.56 | 1562.11 | 23-JUL-16:02 | 29.72 |
August | 16065863.00 | 901.42 | 10-AUG-06:05 | 15.10 |
September | 29550110.78 | 1640.38 | 23-SEP-07:06 | 4.37 |
October | 0.470706E+09 | 34997.39 | 30-OCT-06:01 | -9.4 |
November | 0.226795E+10 | 35310.19 | 12-NOV-08:61 | -8.1 |
December | 0.656819E+10 | 35397.01 | 25-DEC-08:61 | -27.8 |
Annual Sum or Average | 0.253005E+11 | |||
Minimum of Months | 16065863.00 | 901.42 | -27.8 | |
Maximum of Months | 0.719767E+10 | 35397.64 | 30.73 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.764761E+10 | 35129.51 | 09-JAN-07:01 | -32.3 |
February | 0.473220E+10 | 35105.68 | 19-FEB-08:61 | -23.5 |
March | 0.367601E+10 | 35123.03 | 12-MAR-07:01 | -24.5 |
April | 0.112040E+10 | 35064.03 | 05-APR-06:01 | -13.5 |
May | 84309990.43 | 34572.29 | 01-MAY-06:01 | -3.5 |
June | 34346248.17 | 1822.72 | 29-JUN-19:03 | 30.73 |
July | 30400605.28 | 1566.09 | 23-JUL-16:02 | 29.72 |
August | 16018570.26 | 854.24 | 09-AUG-06:05 | 18.98 |
September | 33394464.95 | 1842.34 | 28-SEP-07:05 | 6.78 |
October | 0.590555E+09 | 34780.20 | 30-OCT-06:01 | -9.4 |
November | 0.255885E+10 | 35087.50 | 12-NOV-08:61 | -8.1 |
December | 0.700167E+10 | 35150.97 | 25-DEC-08:61 | -27.8 |
Annual Sum or Average | 0.275258E+11 | |||
Minimum of Months | 16018570.26 | 854.24 | -32.3 | |
Maximum of Months | 0.764761E+10 | 35150.97 | 30.73 |
Report: ZoneHeatingSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.151029E+11 | 65588.71 | 05-JAN-08:61 | -32.3 |
February | 0.944053E+10 | 65558.75 | 14-FEB-08:61 | -31.2 |
March | 0.746807E+10 | 65499.10 | 06-MAR-08:61 | -18.7 |
April | 0.236821E+10 | 65396.72 | 05-APR-07:01 | -11.2 |
May | 0.186843E+09 | 65368.63 | 01-MAY-07:01 | -0.9 |
June | 55590747.29 | 2964.15 | 24-JUN-17:03 | 29.22 |
July | 51457133.31 | 3134.03 | 23-JUL-16:02 | 29.72 |
August | 26079706.02 | 1392.30 | 09-AUG-07:05 | 19.68 |
September | 81498450.61 | 28287.49 | 23-SEP-07:01 | 4.37 |
October | 0.130761E+10 | 65391.14 | 30-OCT-07:01 | -9.0 |
November | 0.526650E+10 | 65391.88 | 25-NOV-08:61 | -18.2 |
December | 0.139140E+11 | 65579.52 | 24-DEC-09:01 | -30.9 |
Annual Sum or Average | 0.552693E+11 | |||
Minimum of Months | 26079706.02 | 1392.30 | -32.3 | |
Maximum of Months | 0.151029E+11 | 65588.71 | 29.72 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.823901E+10 | 34310.94 | 05-JAN-08:61 | -32.3 |
February | 0.522712E+10 | 34246.31 | 25-FEB-08:61 | -28.1 |
March | 0.420977E+10 | 34254.88 | 05-MAR-09:01 | -20.9 |
April | 0.139990E+10 | 34204.39 | 05-APR-07:01 | -11.2 |
May | 0.115823E+09 | 34187.85 | 01-MAY-07:01 | -0.9 |
June | 31780204.64 | 2634.84 | 04-JUN-08:62 | 13.27 |
July | 27406560.90 | 1585.14 | 23-JUL-16:02 | 29.72 |
August | 15305765.21 | 735.22 | 09-AUG-07:05 | 19.68 |
September | 50529573.54 | 15167.56 | 23-SEP-07:01 | 4.37 |
October | 0.795831E+09 | 34202.50 | 30-OCT-07:01 | -9.0 |
November | 0.299782E+10 | 34204.30 | 25-NOV-08:61 | -18.2 |
December | 0.760774E+10 | 34286.93 | 19-DEC-08:61 | -25.9 |
Annual Sum or Average | 0.307180E+11 | |||
Minimum of Months | 15305765.21 | 735.22 | -32.3 | |
Maximum of Months | 0.823901E+10 | 34310.94 | 29.72 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.830017E+10 | 34296.10 | 05-JAN-08:61 | -32.3 |
February | 0.530169E+10 | 34243.32 | 14-FEB-08:61 | -31.2 |
March | 0.429755E+10 | 34239.65 | 05-MAR-09:01 | -20.9 |
April | 0.147661E+10 | 34187.42 | 05-APR-07:01 | -11.2 |
May | 0.128220E+09 | 34172.49 | 01-MAY-07:01 | -0.9 |
June | 33387070.04 | 5194.15 | 04-JUN-08:62 | 13.27 |
July | 27721998.75 | 1587.33 | 23-JUL-16:02 | 29.72 |
August | 16678018.97 | 716.79 | 09-AUG-07:05 | 19.68 |
September | 52369868.74 | 17188.73 | 23-SEP-07:01 | 4.37 |
October | 0.836440E+09 | 34186.09 | 30-OCT-07:01 | -9.0 |
November | 0.307387E+10 | 34187.99 | 25-NOV-08:61 | -18.2 |
December | 0.767053E+10 | 34288.23 | 20-DEC-08:61 | -29.2 |
Annual Sum or Average | 0.312152E+11 | |||
Minimum of Months | 16678018.97 | 716.79 | -32.3 | |
Maximum of Months | 0.830017E+10 | 34296.10 | 29.72 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.880058E+10 | 34588.11 | 05-JAN-08:61 | -32.3 |
February | 0.574682E+10 | 34561.11 | 14-FEB-08:61 | -31.2 |
March | 0.480791E+10 | 34510.79 | 12-MAR-08:61 | -21.0 |
April | 0.181788E+10 | 34464.34 | 05-APR-07:01 | -11.2 |
May | 0.193255E+09 | 34448.94 | 01-MAY-07:01 | -0.9 |
June | 42290332.69 | 12402.10 | 04-JUN-08:62 | 13.27 |
July | 30241510.16 | 1593.64 | 23-JUL-16:02 | 29.72 |
August | 21291955.82 | 663.92 | 09-AUG-07:05 | 19.68 |
September | 67519317.82 | 23874.54 | 23-SEP-07:01 | 4.37 |
October | 0.101903E+10 | 34460.52 | 30-OCT-07:01 | -9.0 |
November | 0.346050E+10 | 34459.86 | 25-NOV-08:61 | -18.2 |
December | 0.815693E+10 | 34543.29 | 26-DEC-08:61 | -26.3 |
Annual Sum or Average | 0.341643E+11 | |||
Minimum of Months | 21291955.82 | 663.92 | -32.3 | |
Maximum of Months | 0.880058E+10 | 34588.11 | 29.72 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.134287E+11 | 38843.71 | 05-JAN-08:61 | -32.3 |
February | 0.939128E+10 | 38741.54 | 02-FEB-08:61 | -24.9 |
March | 0.812619E+10 | 38642.07 | 15-MAR-07:01 | -23.7 |
April | 0.354026E+10 | 38572.46 | 04-APR-07:01 | -8.2 |
May | 0.534956E+09 | 38485.36 | 01-MAY-07:01 | -0.9 |
June | 85085396.36 | 28582.02 | 04-JUN-08:62 | 13.27 |
July | 44126067.83 | 1622.87 | 29-JUL-17:03 | 29.72 |
August | 42095868.46 | 7569.04 | 19-AUG-07:03 | 9.87 |
September | 0.174310E+09 | 37802.40 | 23-SEP-07:01 | 4.37 |
October | 0.185364E+10 | 38499.46 | 30-OCT-07:01 | -9.0 |
November | 0.549475E+10 | 38620.54 | 29-NOV-08:61 | -15.8 |
December | 0.123285E+11 | 38813.86 | 24-DEC-08:42 | -31.1 |
Annual Sum or Average | 0.550439E+11 | |||
Minimum of Months | 42095868.46 | 1622.87 | -32.3 | |
Maximum of Months | 0.134287E+11 | 38843.71 | 29.72 |
Report: ZoneElectricSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.739462E+10 | 4621.63 | 01-JAN-10:09 | 0.222596E+10 | 1343.25 | 01-JAN-10:09 |
February | 0.668410E+10 | 4621.63 | 01-FEB-10:09 | 0.201408E+10 | 1343.25 | 01-FEB-10:09 |
March | 0.740180E+10 | 4621.63 | 01-MAR-10:09 | 0.223295E+10 | 1343.25 | 01-MAR-10:09 |
April | 0.716384E+10 | 4621.63 | 01-APR-09:09 | 0.215748E+10 | 1343.25 | 01-APR-09:09 |
May | 0.739462E+10 | 4621.63 | 01-MAY-09:09 | 0.222596E+10 | 1343.25 | 01-MAY-09:09 |
June | 0.716485E+10 | 4621.63 | 01-JUN-09:09 | 0.216232E+10 | 1343.25 | 01-JUN-09:09 |
July | 0.740069E+10 | 4621.63 | 01-JUL-09:09 | 0.222811E+10 | 1343.25 | 01-JUL-09:09 |
August | 0.739513E+10 | 4621.63 | 01-AUG-09:09 | 0.222838E+10 | 1343.25 | 01-AUG-09:09 |
September | 0.717041E+10 | 4621.63 | 01-SEP-09:09 | 0.216205E+10 | 1343.25 | 01-SEP-09:09 |
October | 0.739462E+10 | 4621.63 | 01-OCT-09:09 | 0.222596E+10 | 1343.25 | 01-OCT-09:09 |
November | 0.714323E+10 | 4621.63 | 01-NOV-09:09 | 0.215077E+10 | 1343.25 | 01-NOV-09:09 |
December | 0.740776E+10 | 4621.63 | 01-DEC-10:09 | 0.223509E+10 | 1343.25 | 01-DEC-10:09 |
Annual Sum or Average | 0.871157E+11 | 0.262491E+11 | ||||
Minimum of Months | 0.668410E+10 | 4621.63 | 0.201408E+10 | 1343.25 | ||
Maximum of Months | 0.740776E+10 | 4621.63 | 0.223509E+10 | 1343.25 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.451584E+10 | 2827.07 | 01-JAN-10:09 | 0.111298E+10 | 671.63 | 01-JAN-10:09 |
February | 0.408193E+10 | 2827.07 | 01-FEB-10:09 | 0.100704E+10 | 671.63 | 01-FEB-10:09 |
March | 0.452026E+10 | 2827.07 | 01-MAR-10:09 | 0.111647E+10 | 671.63 | 01-MAR-10:09 |
April | 0.437489E+10 | 2827.07 | 01-APR-09:09 | 0.107874E+10 | 671.63 | 01-APR-09:09 |
May | 0.451584E+10 | 2827.07 | 01-MAY-09:09 | 0.111298E+10 | 671.63 | 01-MAY-09:09 |
June | 0.437556E+10 | 2827.07 | 01-JUN-09:09 | 0.108116E+10 | 671.63 | 01-JUN-09:09 |
July | 0.451952E+10 | 2827.07 | 01-JUL-09:09 | 0.111405E+10 | 671.63 | 01-JUL-09:09 |
August | 0.451617E+10 | 2827.07 | 01-AUG-09:09 | 0.111419E+10 | 671.63 | 01-AUG-09:09 |
September | 0.437891E+10 | 2827.07 | 01-SEP-09:09 | 0.108102E+10 | 671.63 | 01-SEP-09:09 |
October | 0.451584E+10 | 2827.07 | 01-OCT-09:09 | 0.111298E+10 | 671.63 | 01-OCT-09:09 |
November | 0.436230E+10 | 2827.07 | 01-NOV-09:09 | 0.107538E+10 | 671.63 | 01-NOV-09:09 |
December | 0.452388E+10 | 2827.07 | 01-DEC-10:09 | 0.111755E+10 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.532009E+11 | 0.131245E+11 | ||||
Minimum of Months | 0.408193E+10 | 2827.07 | 0.100704E+10 | 671.63 | ||
Maximum of Months | 0.452388E+10 | 2827.07 | 0.111755E+10 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.317044E+10 | 2555.22 | 01-JAN-10:09 | 0.879849E+09 | 671.63 | 01-JAN-10:09 |
February | 0.287181E+10 | 2555.22 | 01-FEB-09:09 | 0.796766E+09 | 671.63 | 01-FEB-09:09 |
March | 0.324295E+10 | 2555.22 | 01-MAR-09:09 | 0.898128E+09 | 671.63 | 01-MAR-09:09 |
April | 0.307694E+10 | 2555.22 | 01-APR-08:09 | 0.853677E+09 | 671.63 | 01-APR-08:09 |
May | 0.320669E+10 | 2555.22 | 01-MAY-08:09 | 0.888989E+09 | 671.63 | 01-MAY-08:09 |
June | 0.313132E+10 | 2555.22 | 01-JUN-08:09 | 0.867387E+09 | 671.63 | 01-JUN-08:09 |
July | 0.315231E+10 | 2555.22 | 01-JUL-08:09 | 0.875279E+09 | 671.63 | 01-JUL-08:09 |
August | 0.324295E+10 | 2555.22 | 01-AUG-08:09 | 0.898128E+09 | 671.63 | 01-AUG-08:09 |
September | 0.307694E+10 | 2555.22 | 01-SEP-08:09 | 0.853677E+09 | 671.63 | 01-SEP-08:09 |
October | 0.317044E+10 | 2555.22 | 01-OCT-09:09 | 0.879849E+09 | 671.63 | 01-OCT-09:09 |
November | 0.307694E+10 | 2555.22 | 01-NOV-08:09 | 0.853679E+09 | 671.63 | 01-NOV-08:09 |
December | 0.315231E+10 | 2555.22 | 01-DEC-09:09 | 0.875279E+09 | 671.63 | 01-DEC-09:09 |
Annual Sum or Average | 0.375720E+11 | 0.104207E+11 | ||||
Minimum of Months | 0.287181E+10 | 2555.22 | 0.796766E+09 | 671.63 | ||
Maximum of Months | 0.324295E+10 | 2555.22 | 0.898128E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.317044E+10 | 2555.22 | 01-JAN-10:09 | 0.879849E+09 | 671.63 | 01-JAN-10:09 |
February | 0.287181E+10 | 2555.22 | 01-FEB-09:09 | 0.796766E+09 | 671.63 | 01-FEB-09:09 |
March | 0.324295E+10 | 2555.22 | 01-MAR-09:09 | 0.898128E+09 | 671.63 | 01-MAR-09:09 |
April | 0.307694E+10 | 2555.22 | 01-APR-08:09 | 0.853677E+09 | 671.63 | 01-APR-08:09 |
May | 0.320669E+10 | 2555.22 | 01-MAY-08:09 | 0.888989E+09 | 671.63 | 01-MAY-08:09 |
June | 0.313132E+10 | 2555.22 | 01-JUN-08:09 | 0.867387E+09 | 671.63 | 01-JUN-08:09 |
July | 0.315231E+10 | 2555.22 | 01-JUL-08:09 | 0.875279E+09 | 671.63 | 01-JUL-08:09 |
August | 0.324295E+10 | 2555.22 | 01-AUG-08:09 | 0.898128E+09 | 671.63 | 01-AUG-08:09 |
September | 0.307694E+10 | 2555.22 | 01-SEP-08:09 | 0.853677E+09 | 671.63 | 01-SEP-08:09 |
October | 0.317044E+10 | 2555.22 | 01-OCT-09:09 | 0.879849E+09 | 671.63 | 01-OCT-09:09 |
November | 0.307694E+10 | 2555.22 | 01-NOV-08:09 | 0.853679E+09 | 671.63 | 01-NOV-08:09 |
December | 0.315231E+10 | 2555.22 | 01-DEC-09:09 | 0.875279E+09 | 671.63 | 01-DEC-09:09 |
Annual Sum or Average | 0.375720E+11 | 0.104207E+11 | ||||
Minimum of Months | 0.287181E+10 | 2555.22 | 0.796766E+09 | 671.63 | ||
Maximum of Months | 0.324295E+10 | 2555.22 | 0.898128E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.317044E+10 | 2555.22 | 01-JAN-10:09 | 0.879849E+09 | 671.63 | 01-JAN-10:09 |
February | 0.287181E+10 | 2555.22 | 01-FEB-09:09 | 0.796766E+09 | 671.63 | 01-FEB-09:09 |
March | 0.324295E+10 | 2555.22 | 01-MAR-09:09 | 0.898128E+09 | 671.63 | 01-MAR-09:09 |
April | 0.307694E+10 | 2555.22 | 01-APR-08:09 | 0.853677E+09 | 671.63 | 01-APR-08:09 |
May | 0.320669E+10 | 2555.22 | 01-MAY-08:09 | 0.888989E+09 | 671.63 | 01-MAY-08:09 |
June | 0.313132E+10 | 2555.22 | 01-JUN-08:09 | 0.867387E+09 | 671.63 | 01-JUN-08:09 |
July | 0.315231E+10 | 2555.22 | 01-JUL-08:09 | 0.875279E+09 | 671.63 | 01-JUL-08:09 |
August | 0.324295E+10 | 2555.22 | 01-AUG-08:09 | 0.898128E+09 | 671.63 | 01-AUG-08:09 |
September | 0.307694E+10 | 2555.22 | 01-SEP-08:09 | 0.853677E+09 | 671.63 | 01-SEP-08:09 |
October | 0.317044E+10 | 2555.22 | 01-OCT-09:09 | 0.879849E+09 | 671.63 | 01-OCT-09:09 |
November | 0.307694E+10 | 2555.22 | 01-NOV-08:09 | 0.853679E+09 | 671.63 | 01-NOV-08:09 |
December | 0.315231E+10 | 2555.22 | 01-DEC-09:09 | 0.875279E+09 | 671.63 | 01-DEC-09:09 |
Annual Sum or Average | 0.375720E+11 | 0.104207E+11 | ||||
Minimum of Months | 0.287181E+10 | 2555.22 | 0.796766E+09 | 671.63 | ||
Maximum of Months | 0.324295E+10 | 2555.22 | 0.898128E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.313454E+10 | 2726.96 | 01-JAN-11:09 | 0.161799E+10 | 1343.25 | 01-JAN-11:09 |
February | 0.283982E+10 | 2726.96 | 01-FEB-10:09 | 0.146554E+10 | 1343.25 | 01-FEB-10:09 |
March | 0.321092E+10 | 2726.96 | 01-MAR-10:09 | 0.165455E+10 | 1343.25 | 01-MAR-10:09 |
April | 0.304266E+10 | 2726.96 | 01-APR-09:09 | 0.157022E+10 | 1343.25 | 01-APR-09:09 |
May | 0.317273E+10 | 2726.96 | 01-MAY-09:09 | 0.163627E+10 | 1343.25 | 01-MAY-09:09 |
June | 0.309995E+10 | 2726.96 | 01-JUN-09:09 | 0.159764E+10 | 1343.25 | 01-JUN-09:09 |
July | 0.311545E+10 | 2726.96 | 01-JUL-09:09 | 0.160885E+10 | 1343.25 | 01-JUL-09:09 |
August | 0.321092E+10 | 2726.96 | 01-AUG-09:09 | 0.165455E+10 | 1343.25 | 01-AUG-09:09 |
September | 0.304266E+10 | 2726.96 | 01-SEP-09:09 | 0.157022E+10 | 1343.25 | 01-SEP-09:09 |
October | 0.313454E+10 | 2726.96 | 01-OCT-10:09 | 0.161799E+10 | 1343.25 | 01-OCT-10:09 |
November | 0.304266E+10 | 2726.96 | 01-NOV-09:09 | 0.157022E+10 | 1343.25 | 01-NOV-09:09 |
December | 0.311545E+10 | 2726.96 | 01-DEC-10:09 | 0.160885E+10 | 1343.25 | 01-DEC-10:09 |
Annual Sum or Average | 0.371623E+11 | 0.191729E+11 | ||||
Minimum of Months | 0.283982E+10 | 2726.96 | 0.146554E+10 | 1343.25 | ||
Maximum of Months | 0.321092E+10 | 2726.96 | 0.165455E+10 | 1343.25 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.161274E+10 | 1404.46 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.146111E+10 | 1404.46 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.165211E+10 | 1404.46 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.156548E+10 | 1404.46 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.163243E+10 | 1404.46 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.159501E+10 | 1404.46 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.160290E+10 | 1404.46 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.165211E+10 | 1404.46 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.156548E+10 | 1404.46 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.161274E+10 | 1404.46 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.156548E+10 | 1404.46 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.160290E+10 | 1404.46 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.191205E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.146111E+10 | 1404.46 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.165211E+10 | 1404.46 | 0.827277E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.161274E+10 | 1404.46 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.146111E+10 | 1404.46 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.165211E+10 | 1404.46 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.156548E+10 | 1404.46 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.163243E+10 | 1404.46 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.159501E+10 | 1404.46 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.160290E+10 | 1404.46 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.165211E+10 | 1404.46 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.156548E+10 | 1404.46 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.161274E+10 | 1404.46 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.156548E+10 | 1404.46 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.160290E+10 | 1404.46 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.191205E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.146111E+10 | 1404.46 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.165211E+10 | 1404.46 | 0.827277E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.161274E+10 | 1404.46 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.146111E+10 | 1404.46 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.165211E+10 | 1404.46 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.156548E+10 | 1404.46 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.163243E+10 | 1404.46 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.159501E+10 | 1404.46 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.160290E+10 | 1404.46 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.165211E+10 | 1404.46 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.156548E+10 | 1404.46 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.161274E+10 | 1404.46 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.156548E+10 | 1404.46 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.160290E+10 | 1404.46 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.191205E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.146111E+10 | 1404.46 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.165211E+10 | 1404.46 | 0.827277E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.161274E+10 | 1404.46 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.146111E+10 | 1404.46 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.165211E+10 | 1404.46 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.156548E+10 | 1404.46 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.163243E+10 | 1404.46 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.159501E+10 | 1404.46 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.160290E+10 | 1404.46 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.165211E+10 | 1404.46 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.156548E+10 | 1404.46 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.161274E+10 | 1404.46 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.156548E+10 | 1404.46 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.160290E+10 | 1404.46 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.191205E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.146111E+10 | 1404.46 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.165211E+10 | 1404.46 | 0.827277E+09 | 671.63 |
Report: SpaceGainsMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.338624E+10 | 0.739462E+10 | 0.222596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108149E+11 |
February | 0.305697E+10 | 0.668410E+10 | 0.201408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.792120E+10 |
March | 0.335708E+10 | 0.740180E+10 | 0.223295E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.688871E+10 |
April | 0.327081E+10 | 0.716384E+10 | 0.215748E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7123678.99 | 0.416465E+10 |
May | 0.336680E+10 | 0.739462E+10 | 0.222596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102755E+09 | 0.191243E+10 |
June | 0.325380E+10 | 0.716485E+10 | 0.216232E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.250765E+09 | 0.966626E+09 |
July | 0.339353E+10 | 0.740069E+10 | 0.222811E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.354731E+09 | 0.606215E+09 |
August | 0.334857E+10 | 0.739513E+10 | 0.222838E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147953E+09 | 0.952437E+09 |
September | 0.327932E+10 | 0.717041E+10 | 0.216205E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7115745.32 | 0.226656E+10 |
October | 0.338624E+10 | 0.739462E+10 | 0.222596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.391204E+10 |
November | 0.327446E+10 | 0.714323E+10 | 0.215077E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.611241E+10 |
December | 0.340325E+10 | 0.740776E+10 | 0.223509E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104831E+11 |
Annual Sum or Average | 0.397770E+11 | 0.871157E+11 | 0.262491E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.870443E+09 | 0.570012E+11 |
Minimum of Months | 0.305697E+10 | 0.668410E+10 | 0.201408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.606215E+09 |
Maximum of Months | 0.340325E+10 | 0.740776E+10 | 0.223509E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.354731E+09 | 0.108149E+11 |
Report: SpaceGainsMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.169307E+10 | 0.451584E+10 | 0.111298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.544766E+10 |
February | 0.152844E+10 | 0.408193E+10 | 0.100704E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.392712E+10 |
March | 0.167849E+10 | 0.452026E+10 | 0.111647E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.347547E+10 |
April | 0.163536E+10 | 0.437489E+10 | 0.107874E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3747543.81 | 0.200314E+10 |
May | 0.168335E+10 | 0.451584E+10 | 0.111298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 55956891.13 | 0.883888E+09 |
June | 0.162685E+10 | 0.437556E+10 | 0.108116E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134362E+09 | 0.443743E+09 |
July | 0.169671E+10 | 0.451952E+10 | 0.111405E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192350E+09 | 0.276263E+09 |
August | 0.167424E+10 | 0.451617E+10 | 0.111419E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 80352212.22 | 0.434179E+09 |
September | 0.163961E+10 | 0.437891E+10 | 0.108102E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3898262.06 | 0.105240E+10 |
October | 0.169307E+10 | 0.451584E+10 | 0.111298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.191141E+10 |
November | 0.163718E+10 | 0.436230E+10 | 0.107538E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.300910E+10 |
December | 0.170157E+10 | 0.452388E+10 | 0.111755E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.525077E+10 |
Annual Sum or Average | 0.198880E+11 | 0.532009E+11 | 0.131245E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.470667E+09 | 0.281151E+11 |
Minimum of Months | 0.152844E+10 | 0.408193E+10 | 0.100704E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.276263E+09 |
Maximum of Months | 0.170157E+10 | 0.452388E+10 | 0.111755E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192350E+09 | 0.544766E+10 |
Report: SpaceGainsMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.317044E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.556001E+10 |
February | 0.914877E+09 | 0.287181E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.404214E+10 |
March | 0.103395E+10 | 0.324295E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.353901E+10 |
April | 0.984131E+09 | 0.307694E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2824699.96 | 0.204459E+10 |
May | 0.102058E+10 | 0.320669E+10 | 0.888989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 55944773.77 | 0.893895E+09 |
June | 0.998711E+09 | 0.313132E+10 | 0.867387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133194E+09 | 0.457325E+09 |
July | 0.100600E+10 | 0.315231E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188572E+09 | 0.295074E+09 |
August | 0.103395E+10 | 0.324295E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 80267243.76 | 0.456355E+09 |
September | 0.984131E+09 | 0.307694E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3898130.33 | 0.105857E+10 |
October | 0.100722E+10 | 0.317044E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.193566E+10 |
November | 0.973196E+09 | 0.307694E+10 | 0.853679E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.308513E+10 |
December | 0.100600E+10 | 0.315231E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.538118E+10 |
Annual Sum or Average | 0.119700E+11 | 0.375720E+11 | 0.104207E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.464701E+09 | 0.287489E+11 |
Minimum of Months | 0.914877E+09 | 0.287181E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.295074E+09 |
Maximum of Months | 0.103395E+10 | 0.324295E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188572E+09 | 0.556001E+10 |
Report: SpaceGainsMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.317044E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.555515E+10 |
February | 0.914877E+09 | 0.287181E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.403741E+10 |
March | 0.103395E+10 | 0.324295E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.353559E+10 |
April | 0.984131E+09 | 0.307694E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2929512.07 | 0.203611E+10 |
May | 0.102058E+10 | 0.320669E+10 | 0.888989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 55944764.84 | 0.883816E+09 |
June | 0.998711E+09 | 0.313132E+10 | 0.867387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133171E+09 | 0.453132E+09 |
July | 0.100600E+10 | 0.315231E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188554E+09 | 0.294661E+09 |
August | 0.103395E+10 | 0.324295E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 80267116.94 | 0.455263E+09 |
September | 0.984131E+09 | 0.307694E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3898109.07 | 0.105009E+10 |
October | 0.100722E+10 | 0.317044E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192741E+10 |
November | 0.973196E+09 | 0.307694E+10 | 0.853679E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.307988E+10 |
December | 0.100600E+10 | 0.315231E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.537599E+10 |
Annual Sum or Average | 0.119700E+11 | 0.375720E+11 | 0.104207E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.464765E+09 | 0.286845E+11 |
Minimum of Months | 0.914877E+09 | 0.287181E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.294661E+09 |
Maximum of Months | 0.103395E+10 | 0.324295E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188554E+09 | 0.555515E+10 |
Report: SpaceGainsMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.317044E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.555169E+10 |
February | 0.914877E+09 | 0.287181E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.403355E+10 |
March | 0.103395E+10 | 0.324295E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.353251E+10 |
April | 0.984131E+09 | 0.307694E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3066301.65 | 0.202660E+10 |
May | 0.102058E+10 | 0.320669E+10 | 0.888989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 55945174.29 | 0.869967E+09 |
June | 0.998711E+09 | 0.313132E+10 | 0.867387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133286E+09 | 0.445318E+09 |
July | 0.100600E+10 | 0.315231E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188629E+09 | 0.292109E+09 |
August | 0.103395E+10 | 0.324295E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 80267505.44 | 0.451664E+09 |
September | 0.984131E+09 | 0.307694E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3898047.51 | 0.103922E+10 |
October | 0.100722E+10 | 0.317044E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192028E+10 |
November | 0.973196E+09 | 0.307694E+10 | 0.853679E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.307495E+10 |
December | 0.100600E+10 | 0.315231E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.537192E+10 |
Annual Sum or Average | 0.119700E+11 | 0.375720E+11 | 0.104207E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.465092E+09 | 0.286098E+11 |
Minimum of Months | 0.914877E+09 | 0.287181E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.292109E+09 |
Maximum of Months | 0.103395E+10 | 0.324295E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188629E+09 | 0.555169E+10 |
Report: SpaceGainsMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.344359E+10 | 0.313454E+10 | 0.161799E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101580E+11 |
February | 0.313522E+10 | 0.283982E+10 | 0.146554E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.739921E+10 |
March | 0.355148E+10 | 0.321092E+10 | 0.165455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.645948E+10 |
April | 0.338259E+10 | 0.304266E+10 | 0.157022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6125177.63 | 0.372046E+10 |
May | 0.349753E+10 | 0.317273E+10 | 0.163627E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100627E+09 | 0.157910E+10 |
June | 0.343071E+10 | 0.309995E+10 | 0.159764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.240891E+09 | 0.807305E+09 |
July | 0.344942E+10 | 0.311545E+10 | 0.160885E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.339830E+09 | 0.541253E+09 |
August | 0.355148E+10 | 0.321092E+10 | 0.165455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144438E+09 | 0.835608E+09 |
September | 0.338259E+10 | 0.304266E+10 | 0.157022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7004282.26 | 0.190214E+10 |
October | 0.344359E+10 | 0.313454E+10 | 0.161799E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.350707E+10 |
November | 0.331698E+10 | 0.304266E+10 | 0.157022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.564644E+10 |
December | 0.344942E+10 | 0.311545E+10 | 0.160885E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.984171E+10 |
Annual Sum or Average | 0.410346E+11 | 0.371623E+11 | 0.191729E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.838915E+09 | 0.523978E+11 |
Minimum of Months | 0.313522E+10 | 0.283982E+10 | 0.146554E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.541253E+09 |
Maximum of Months | 0.355148E+10 | 0.321092E+10 | 0.165455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.339830E+09 | 0.101580E+11 |
Report: SpaceGainsMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.161274E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.557771E+10 |
February | 0.156756E+10 | 0.146111E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.405077E+10 |
March | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.354754E+10 |
April | 0.169125E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3431297.38 | 0.202708E+10 |
May | 0.174872E+10 | 0.163243E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 55958615.55 | 0.853619E+09 |
June | 0.171530E+10 | 0.159501E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133781E+09 | 0.434162E+09 |
July | 0.172466E+10 | 0.160290E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188989E+09 | 0.291351E+09 |
August | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 80295769.60 | 0.450684E+09 |
September | 0.169125E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3897742.99 | 0.103415E+10 |
October | 0.172174E+10 | 0.161274E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192128E+10 |
November | 0.165844E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.308832E+10 |
December | 0.172466E+10 | 0.160290E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.539775E+10 |
Annual Sum or Average | 0.205167E+11 | 0.191205E+11 | 0.958644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.466353E+09 | 0.286744E+11 |
Minimum of Months | 0.156756E+10 | 0.146111E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.291351E+09 |
Maximum of Months | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188989E+09 | 0.557771E+10 |
Report: SpaceGainsMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.161274E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.557720E+10 |
February | 0.156756E+10 | 0.146111E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.405000E+10 |
March | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.354661E+10 |
April | 0.169125E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3494897.98 | 0.202346E+10 |
May | 0.174872E+10 | 0.163243E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 55959041.08 | 0.847156E+09 |
June | 0.171530E+10 | 0.159501E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133825E+09 | 0.429502E+09 |
July | 0.172466E+10 | 0.160290E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189021E+09 | 0.290226E+09 |
August | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 80296732.70 | 0.449036E+09 |
September | 0.169125E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3897683.59 | 0.102999E+10 |
October | 0.172174E+10 | 0.161274E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.191914E+10 |
November | 0.165844E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.308696E+10 |
December | 0.172466E+10 | 0.160290E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.539707E+10 |
Annual Sum or Average | 0.205167E+11 | 0.191205E+11 | 0.958644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.466494E+09 | 0.286464E+11 |
Minimum of Months | 0.156756E+10 | 0.146111E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.290226E+09 |
Maximum of Months | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189021E+09 | 0.557720E+10 |
Report: SpaceGainsMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.161274E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.557321E+10 |
February | 0.156756E+10 | 0.146111E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.404487E+10 |
March | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.354146E+10 |
April | 0.169125E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3698482.70 | 0.201105E+10 |
May | 0.174872E+10 | 0.163243E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 55959797.66 | 0.828906E+09 |
June | 0.171530E+10 | 0.159501E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133965E+09 | 0.416660E+09 |
July | 0.172466E+10 | 0.160290E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189088E+09 | 0.286374E+09 |
August | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 80299074.57 | 0.443749E+09 |
September | 0.169125E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3897713.68 | 0.101868E+10 |
October | 0.172174E+10 | 0.161274E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.191229E+10 |
November | 0.165844E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.308029E+10 |
December | 0.172466E+10 | 0.160290E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.539198E+10 |
Annual Sum or Average | 0.205167E+11 | 0.191205E+11 | 0.958644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.466908E+09 | 0.285495E+11 |
Minimum of Months | 0.156756E+10 | 0.146111E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.286374E+09 |
Maximum of Months | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189088E+09 | 0.557321E+10 |
Report: SpaceGainsMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.161274E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.669613E+10 |
February | 0.156756E+10 | 0.146111E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.500391E+10 |
March | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.421127E+10 |
April | 0.169125E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5288534.65 | 0.251299E+10 |
May | 0.174872E+10 | 0.163243E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 58180004.66 | 0.103592E+10 |
June | 0.171530E+10 | 0.159501E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143611E+09 | 0.528700E+09 |
July | 0.172466E+10 | 0.160290E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.197641E+09 | 0.383266E+09 |
August | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 83712414.53 | 0.594918E+09 |
September | 0.169125E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4009726.82 | 0.127878E+10 |
October | 0.172174E+10 | 0.161274E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230140E+10 |
November | 0.165844E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.380192E+10 |
December | 0.172466E+10 | 0.160290E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.655239E+10 |
Annual Sum or Average | 0.205167E+11 | 0.191205E+11 | 0.958644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.492442E+09 | 0.349016E+11 |
Minimum of Months | 0.156756E+10 | 0.146111E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.383266E+09 |
Maximum of Months | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.197641E+09 | 0.669613E+10 |
Report: PeakSpaceGainsMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 4050.04 | 01-JAN-13:09 | 4621.63 | 01-JAN-10:09 | 1343.25 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 18193.23 | 04-JAN-12:10 |
February | 4050.04 | 03-FEB-13:09 | 4621.63 | 01-FEB-10:09 | 1343.25 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 14908.32 | 13-FEB-12:10 |
March | 4050.04 | 03-MAR-13:09 | 4621.63 | 01-MAR-10:09 | 1343.25 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 12263.51 | 15-MAR-11:10 |
April | 4050.04 | 01-APR-12:09 | 4621.63 | 01-APR-09:09 | 1343.25 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 842.98 | 23-APR-16:00 | 8513.93 | 04-APR-17:00 |
May | 4050.04 | 05-MAY-12:09 | 4621.63 | 01-MAY-09:09 | 1343.25 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1467.17 | 25-MAY-17:00 | 4717.84 | 08-MAY-11:05 |
June | 4050.04 | 02-JUN-12:09 | 4621.63 | 01-JUN-09:09 | 1343.25 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3160.66 | 29-JUN-16:00 | 3568.98 | 09-JUN-11:10 |
July | 4050.04 | 01-JUL-12:09 | 4621.63 | 01-JUL-09:09 | 1343.25 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2107.18 | 15-JUL-15:00 | 3159.60 | 08-JUL-11:10 |
August | 4050.04 | 04-AUG-12:09 | 4621.63 | 01-AUG-09:09 | 1343.25 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1964.97 | 08-AUG-16:00 | 4129.55 | 17-AUG-14:00 |
September | 4050.04 | 01-SEP-12:09 | 4621.63 | 01-SEP-09:09 | 1343.25 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 626.38 | 01-SEP-15:00 | 4875.93 | 27-SEP-11:05 |
October | 4050.04 | 01-OCT-12:09 | 4621.63 | 01-OCT-09:09 | 1343.25 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 7095.57 | 31-OCT-17:00 |
November | 4050.04 | 03-NOV-12:09 | 4621.63 | 01-NOV-09:09 | 1343.25 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 12039.97 | 25-NOV-12:10 |
December | 4050.04 | 01-DEC-13:09 | 4621.63 | 01-DEC-10:09 | 1343.25 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 17459.21 | 24-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 4050.04 | 4621.63 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3159.60 | |||||
Maximum of Months | 4050.04 | 4621.63 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 3160.66 | 18193.23 |
Report: PeakSpaceGainsMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 01-JAN-13:09 | 2827.07 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 9736.58 | 04-JAN-12:10 |
February | 2024.96 | 03-FEB-13:09 | 2827.07 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 8221.95 | 01-FEB-18:00 |
March | 2024.96 | 03-MAR-13:09 | 2827.07 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 6688.26 | 15-MAR-11:10 |
April | 2024.96 | 01-APR-12:09 | 2827.07 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 445.87 | 23-APR-16:00 | 4573.77 | 04-APR-11:10 |
May | 2024.96 | 05-MAY-12:09 | 2827.07 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 810.12 | 25-MAY-17:00 | 2419.42 | 01-MAY-11:10 |
June | 2024.96 | 02-JUN-12:09 | 2827.07 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1706.48 | 29-JUN-16:00 | 1775.43 | 09-JUN-11:10 |
July | 2024.96 | 01-JUL-12:09 | 2827.07 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1126.80 | 15-JUL-15:00 | 1651.94 | 08-JUL-11:10 |
August | 2024.96 | 04-AUG-12:09 | 2827.07 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1058.40 | 08-AUG-16:00 | 2035.64 | 17-AUG-14:00 |
September | 2024.96 | 01-SEP-12:09 | 2827.07 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 343.18 | 01-SEP-15:00 | 2408.89 | 27-SEP-11:05 |
October | 2024.96 | 01-OCT-12:09 | 2827.07 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 3839.29 | 29-OCT-17:00 |
November | 2024.96 | 03-NOV-12:09 | 2827.07 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 6607.53 | 25-NOV-17:00 |
December | 2024.96 | 01-DEC-13:09 | 2827.07 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 9445.98 | 24-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 2827.07 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1651.94 | |||||
Maximum of Months | 2024.96 | 2827.07 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1706.48 | 9736.58 |
Report: PeakSpaceGainsMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 2555.22 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 9736.58 | 04-JAN-12:10 |
February | 2024.96 | 04-FEB-13:09 | 2555.22 | 01-FEB-09:09 | 671.63 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 8221.95 | 01-FEB-18:00 |
March | 2024.96 | 04-MAR-13:09 | 2555.22 | 01-MAR-09:09 | 671.63 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 6688.26 | 15-MAR-11:10 |
April | 2024.96 | 01-APR-12:09 | 2555.22 | 01-APR-08:09 | 671.63 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 445.87 | 23-APR-16:00 | 4573.77 | 04-APR-11:10 |
May | 2024.96 | 06-MAY-12:09 | 2555.22 | 01-MAY-08:09 | 671.63 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 810.12 | 25-MAY-17:00 | 2419.42 | 01-MAY-11:10 |
June | 2024.96 | 03-JUN-12:09 | 2555.22 | 01-JUN-08:09 | 671.63 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1706.48 | 29-JUN-16:00 | 1768.24 | 09-JUN-11:10 |
July | 2024.96 | 01-JUL-12:09 | 2555.22 | 01-JUL-08:09 | 671.63 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1126.80 | 15-JUL-15:00 | 1671.99 | 08-JUL-11:10 |
August | 2024.96 | 05-AUG-12:09 | 2555.22 | 01-AUG-08:09 | 671.63 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1058.40 | 08-AUG-16:00 | 2003.45 | 17-AUG-14:00 |
September | 2024.96 | 02-SEP-12:09 | 2555.22 | 01-SEP-08:09 | 671.63 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 343.17 | 01-SEP-15:00 | 2325.01 | 27-SEP-11:05 |
October | 2024.96 | 07-OCT-12:09 | 2555.22 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 3839.29 | 29-OCT-17:00 |
November | 2024.96 | 04-NOV-12:09 | 2555.22 | 01-NOV-08:09 | 671.63 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 6607.53 | 25-NOV-17:00 |
December | 2024.96 | 02-DEC-13:09 | 2555.22 | 01-DEC-09:09 | 671.63 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 9445.98 | 24-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 2555.22 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1671.99 | |||||
Maximum of Months | 2024.96 | 2555.22 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1706.48 | 9736.58 |
Report: PeakSpaceGainsMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 2555.22 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 9736.58 | 04-JAN-12:10 |
February | 2024.96 | 04-FEB-13:09 | 2555.22 | 01-FEB-09:09 | 671.63 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 8221.95 | 01-FEB-18:00 |
March | 2024.96 | 04-MAR-13:09 | 2555.22 | 01-MAR-09:09 | 671.63 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 6688.26 | 15-MAR-11:10 |
April | 2024.96 | 01-APR-12:09 | 2555.22 | 01-APR-08:09 | 671.63 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 445.87 | 23-APR-16:00 | 4573.77 | 04-APR-11:10 |
May | 2024.96 | 06-MAY-12:09 | 2555.22 | 01-MAY-08:09 | 671.63 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 810.11 | 25-MAY-17:00 | 2419.42 | 01-MAY-11:10 |
June | 2024.96 | 03-JUN-12:09 | 2555.22 | 01-JUN-08:09 | 671.63 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1706.48 | 29-JUN-16:00 | 1761.97 | 09-JUN-11:10 |
July | 2024.96 | 01-JUL-12:09 | 2555.22 | 01-JUL-08:09 | 671.63 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1126.80 | 15-JUL-15:00 | 1670.76 | 08-JUL-11:10 |
August | 2024.96 | 05-AUG-12:09 | 2555.22 | 01-AUG-08:09 | 671.63 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1058.40 | 08-AUG-16:00 | 1995.76 | 17-AUG-14:00 |
September | 2024.96 | 02-SEP-12:09 | 2555.22 | 01-SEP-08:09 | 671.63 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 343.17 | 01-SEP-15:00 | 2317.83 | 27-SEP-11:05 |
October | 2024.96 | 07-OCT-12:09 | 2555.22 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 3839.29 | 29-OCT-17:00 |
November | 2024.96 | 04-NOV-12:09 | 2555.22 | 01-NOV-08:09 | 671.63 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 6607.53 | 25-NOV-17:00 |
December | 2024.96 | 02-DEC-13:09 | 2555.22 | 01-DEC-09:09 | 671.63 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 9445.98 | 24-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 2555.22 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1670.76 | |||||
Maximum of Months | 2024.96 | 2555.22 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1706.48 | 9736.58 |
Report: PeakSpaceGainsMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 2555.22 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 9736.58 | 04-JAN-12:10 |
February | 2024.96 | 04-FEB-13:09 | 2555.22 | 01-FEB-09:09 | 671.63 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 8221.95 | 01-FEB-18:00 |
March | 2024.96 | 04-MAR-13:09 | 2555.22 | 01-MAR-09:09 | 671.63 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 6688.26 | 15-MAR-11:10 |
April | 2024.96 | 01-APR-12:09 | 2555.22 | 01-APR-08:09 | 671.63 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 445.87 | 23-APR-16:00 | 4573.77 | 04-APR-11:10 |
May | 2024.96 | 06-MAY-12:09 | 2555.22 | 01-MAY-08:09 | 671.63 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 810.11 | 25-MAY-17:00 | 2419.42 | 01-MAY-11:10 |
June | 2024.96 | 03-JUN-12:09 | 2555.22 | 01-JUN-08:09 | 671.63 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1706.48 | 29-JUN-16:00 | 1734.62 | 09-JUN-11:10 |
July | 2024.96 | 01-JUL-12:09 | 2555.22 | 01-JUL-08:09 | 671.63 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1126.80 | 15-JUL-15:00 | 1648.65 | 08-JUL-11:10 |
August | 2024.96 | 05-AUG-12:09 | 2555.22 | 01-AUG-08:09 | 671.63 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1058.40 | 08-AUG-16:00 | 1972.20 | 17-AUG-14:00 |
September | 2024.96 | 02-SEP-12:09 | 2555.22 | 01-SEP-08:09 | 671.63 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 343.17 | 01-SEP-15:00 | 2317.57 | 27-SEP-11:05 |
October | 2024.96 | 07-OCT-12:09 | 2555.22 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 3839.29 | 29-OCT-17:00 |
November | 2024.96 | 04-NOV-12:09 | 2555.22 | 01-NOV-08:09 | 671.63 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 6607.53 | 25-NOV-17:00 |
December | 2024.96 | 02-DEC-13:09 | 2555.22 | 01-DEC-09:09 | 671.63 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 9445.98 | 24-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 2555.22 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1648.65 | |||||
Maximum of Months | 2024.96 | 2555.22 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1706.48 | 9736.58 |
Report: PeakSpaceGainsMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 5400.05 | 07-JAN-15:09 | 2726.96 | 01-JAN-11:09 | 1343.25 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 17546.75 | 04-JAN-12:10 |
February | 5400.05 | 04-FEB-15:09 | 2726.96 | 01-FEB-10:09 | 1343.25 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 14741.82 | 01-FEB-18:00 |
March | 5400.05 | 04-MAR-15:09 | 2726.96 | 01-MAR-10:09 | 1343.25 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 12024.86 | 15-MAR-11:10 |
April | 5400.05 | 01-APR-14:09 | 2726.96 | 01-APR-09:09 | 1343.25 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 804.86 | 23-APR-16:00 | 8228.43 | 04-APR-11:10 |
May | 5400.05 | 06-MAY-14:09 | 2726.96 | 01-MAY-09:09 | 1343.25 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1454.27 | 25-MAY-17:00 | 4345.53 | 01-MAY-11:10 |
June | 5400.05 | 03-JUN-14:09 | 2726.96 | 01-JUN-09:09 | 1343.25 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3071.97 | 29-JUN-16:00 | 3021.20 | 09-JUN-11:10 |
July | 5400.05 | 01-JUL-14:09 | 2726.96 | 01-JUL-09:09 | 1343.25 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2030.87 | 15-JUL-15:00 | 2886.47 | 08-JUL-11:10 |
August | 5400.05 | 05-AUG-14:09 | 2726.96 | 01-AUG-09:09 | 1343.25 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1905.86 | 08-AUG-16:00 | 3437.53 | 17-AUG-14:00 |
September | 5400.05 | 02-SEP-14:09 | 2726.96 | 01-SEP-09:09 | 1343.25 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 616.64 | 01-SEP-15:00 | 4166.32 | 27-SEP-11:05 |
October | 5400.05 | 07-OCT-14:09 | 2726.96 | 01-OCT-10:09 | 1343.25 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 6894.74 | 29-OCT-17:00 |
November | 5400.05 | 04-NOV-14:09 | 2726.96 | 01-NOV-09:09 | 1343.25 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 11862.45 | 25-NOV-17:00 |
December | 5400.05 | 02-DEC-15:09 | 2726.96 | 01-DEC-10:09 | 1343.25 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 16999.87 | 24-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 5400.05 | 2726.96 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2886.47 | |||||
Maximum of Months | 5400.05 | 2726.96 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 3071.97 | 17546.75 |
Report: PeakSpaceGainsMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1404.46 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 9736.58 | 04-JAN-12:10 |
February | 2699.95 | 04-FEB-15:09 | 1404.46 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 8221.95 | 01-FEB-18:00 |
March | 2699.95 | 04-MAR-15:09 | 1404.46 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 6688.26 | 15-MAR-11:10 |
April | 2699.95 | 01-APR-14:09 | 1404.46 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 445.95 | 23-APR-16:00 | 4573.77 | 04-APR-11:10 |
May | 2699.95 | 06-MAY-14:09 | 1404.46 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 810.08 | 25-MAY-17:00 | 2419.42 | 01-MAY-11:10 |
June | 2699.95 | 03-JUN-14:09 | 1404.46 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1706.48 | 29-JUN-16:00 | 1674.01 | 09-JUN-11:10 |
July | 2699.95 | 01-JUL-14:09 | 1404.46 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1126.80 | 15-JUL-15:00 | 1603.50 | 08-JUL-11:10 |
August | 2699.95 | 05-AUG-14:09 | 1404.46 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1058.40 | 08-AUG-16:00 | 1904.55 | 17-AUG-14:00 |
September | 2699.95 | 02-SEP-14:09 | 1404.46 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 343.16 | 01-SEP-15:00 | 2317.57 | 27-SEP-11:05 |
October | 2699.95 | 07-OCT-14:09 | 1404.46 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 3839.29 | 29-OCT-17:00 |
November | 2699.95 | 04-NOV-14:09 | 1404.46 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 6607.53 | 25-NOV-17:00 |
December | 2699.95 | 02-DEC-15:09 | 1404.46 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 9445.98 | 24-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1603.50 | |||||
Maximum of Months | 2699.95 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1706.48 | 9736.58 |
Report: PeakSpaceGainsMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1404.46 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 9736.58 | 04-JAN-12:10 |
February | 2699.95 | 04-FEB-15:09 | 1404.46 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 8221.95 | 01-FEB-18:00 |
March | 2699.95 | 04-MAR-15:09 | 1404.46 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 6688.26 | 15-MAR-11:10 |
April | 2699.95 | 01-APR-14:09 | 1404.46 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 445.95 | 23-APR-16:00 | 4573.77 | 04-APR-11:10 |
May | 2699.95 | 06-MAY-14:09 | 1404.46 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 810.08 | 25-MAY-17:00 | 2419.42 | 01-MAY-11:10 |
June | 2699.95 | 03-JUN-14:09 | 1404.46 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1706.48 | 29-JUN-16:00 | 1661.20 | 09-JUN-11:10 |
July | 2699.95 | 01-JUL-14:09 | 1404.46 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1126.80 | 15-JUL-15:00 | 1595.25 | 08-JUL-11:10 |
August | 2699.95 | 05-AUG-14:09 | 1404.46 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1058.40 | 08-AUG-16:00 | 1894.57 | 17-AUG-14:00 |
September | 2699.95 | 02-SEP-14:09 | 1404.46 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 343.16 | 01-SEP-15:00 | 2317.57 | 27-SEP-11:05 |
October | 2699.95 | 07-OCT-14:09 | 1404.46 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 3839.29 | 29-OCT-17:00 |
November | 2699.95 | 04-NOV-14:09 | 1404.46 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 6607.53 | 25-NOV-17:00 |
December | 2699.95 | 02-DEC-15:09 | 1404.46 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 9445.98 | 24-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1595.25 | |||||
Maximum of Months | 2699.95 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1706.48 | 9736.58 |
Report: PeakSpaceGainsMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1404.46 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 9736.58 | 04-JAN-12:10 |
February | 2699.95 | 04-FEB-15:09 | 1404.46 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 8221.95 | 01-FEB-18:00 |
March | 2699.95 | 04-MAR-15:09 | 1404.46 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 6688.26 | 15-MAR-11:10 |
April | 2699.95 | 01-APR-14:09 | 1404.46 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 445.95 | 23-APR-16:00 | 4573.77 | 04-APR-11:10 |
May | 2699.95 | 06-MAY-14:09 | 1404.46 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 810.07 | 25-MAY-17:00 | 2419.42 | 01-MAY-11:10 |
June | 2699.95 | 03-JUN-14:09 | 1404.46 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1706.48 | 29-JUN-16:00 | 1620.00 | 09-JUN-11:10 |
July | 2699.95 | 01-JUL-14:09 | 1404.46 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1126.80 | 15-JUL-15:00 | 1565.57 | 08-JUL-11:10 |
August | 2699.95 | 05-AUG-14:09 | 1404.46 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1058.27 | 08-AUG-16:00 | 1862.81 | 17-AUG-14:00 |
September | 2699.95 | 02-SEP-14:09 | 1404.46 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 343.15 | 01-SEP-15:00 | 2317.57 | 27-SEP-11:10 |
October | 2699.95 | 07-OCT-14:09 | 1404.46 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 3839.29 | 29-OCT-17:00 |
November | 2699.95 | 04-NOV-14:09 | 1404.46 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 6607.53 | 25-NOV-17:00 |
December | 2699.95 | 02-DEC-15:09 | 1404.46 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 9445.98 | 24-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1565.57 | |||||
Maximum of Months | 2699.95 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1706.48 | 9736.58 |
Report: PeakSpaceGainsMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1404.46 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 10383.07 | 04-JAN-12:10 |
February | 2699.95 | 04-FEB-15:09 | 1404.46 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 8455.57 | 13-FEB-12:10 |
March | 2699.95 | 04-MAR-15:09 | 1404.46 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 6926.90 | 15-MAR-11:10 |
April | 2699.95 | 01-APR-14:09 | 1404.46 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 484.25 | 23-APR-16:00 | 4861.14 | 04-APR-17:00 |
May | 2699.95 | 06-MAY-14:09 | 1404.46 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 823.11 | 25-MAY-17:00 | 2474.17 | 01-MAY-11:10 |
June | 2699.95 | 03-JUN-14:09 | 1404.46 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1795.46 | 29-JUN-16:00 | 1586.33 | 09-JUN-11:10 |
July | 2699.95 | 01-JUL-14:09 | 1404.46 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1203.04 | 15-JUL-15:00 | 1513.99 | 08-JUL-11:10 |
August | 2699.95 | 05-AUG-14:09 | 1404.46 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1117.48 | 08-AUG-16:00 | 1956.48 | 17-AUG-14:00 |
September | 2699.95 | 02-SEP-14:09 | 1404.46 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 352.87 | 01-SEP-15:00 | 2396.99 | 27-SEP-11:05 |
October | 2699.95 | 07-OCT-14:09 | 1404.46 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 4035.44 | 31-OCT-17:00 |
November | 2699.95 | 04-NOV-14:09 | 1404.46 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 6810.79 | 25-NOV-12:10 |
December | 2699.95 | 02-DEC-15:09 | 1404.46 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 9905.32 | 24-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1513.99 | |||||
Maximum of Months | 2699.95 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1795.46 | 10383.07 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 23959.48 | 06-JAN-00:01 | 3375.03 | 2432.30 | 7462.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 337.43 |
February | 20118.83 | 25-FEB-00:01 | 3037.53 | 21891.86 | 6716.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 410.90 |
March | 4422.03 | 03-MAR-00:12 | 1350.01 | 972.92 | 2985.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6754.93 | 23-APR-16:03 | 12150.11 | 13864.89 | 4029.75 | 0.00 | 0.00 | 0.00 | 0.00 | 809.18 | 0.00 |
May | 10224.72 | 25-MAY-16:10 | 3375.03 | 4621.63 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 1453.31 | 0.00 |
June | 22345.90 | 29-JUN-07:03 | 1350.01 | 300.00 | 298.50 | 0.00 | 0.00 | 0.00 | 0.00 | 31.70 | 0.00 |
July | 23781.17 | 04-JUL-07:03 | 1350.01 | 300.00 | 298.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.48 |
August | 22376.97 | 09-AUG-07:03 | 1350.01 | 300.00 | 298.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 214.69 |
September | 11448.71 | 01-SEP-16:10 | 3375.03 | 4621.63 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 544.03 | 0.00 |
October | 7322.57 | 22-OCT-17:10 | 4050.04 | 4621.63 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 386.22 |
November | 4076.70 | 25-NOV-00:12 | 1350.01 | 9729.72 | 2985.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 682.60 |
December | 18145.48 | 02-DEC-00:33 | 1350.01 | 9729.72 | 2985.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 437.93 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4076.70 | 1350.01 | 300.00 | 298.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 23959.48 | 12150.11 | 21891.86 | 7462.50 | 0.00 | 0.00 | 0.00 | 0.00 | 1453.31 | 682.60 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 8764.61 | 26-JAN-20:31 | 7087.36 | 19789.47 | 4701.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 150.96 |
February | 6932.83 | 15-FEB-20:02 | 5062.40 | 14135.34 | 3358.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 155.81 |
March | 4985.89 | 11-MAR-11:53 | 1349.97 | 11308.27 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 661.64 |
April | 12531.97 | 23-APR-20:27 | 7087.36 | 19789.47 | 4701.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.92 |
May | 15181.30 | 21-MAY-19:06 | 6749.87 | 14135.34 | 3358.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.70 |
June | 14689.16 | 17-JUN-20:55 | 2024.96 | 5654.14 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.75 |
July | 14328.35 | 24-JUL-07:03 | 674.99 | 150.00 | 149.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.68 |
August | 14592.47 | 09-AUG-07:03 | 674.99 | 150.00 | 149.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.61 |
September | 13576.79 | 04-SEP-17:54 | 10124.81 | 14135.34 | 3358.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 221.40 |
October | 4418.35 | 29-OCT-08:32 | 674.99 | 5951.72 | 1492.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 531.97 |
November | 4559.65 | 13-NOV-11:13 | 1349.97 | 11308.27 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 608.25 |
December | 1016.45 | 05-DEC-20:10 | 1012.48 | 2827.07 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.16 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1016.45 | 674.99 | 150.00 | 149.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.70 | |
Maximum of Months | 15181.30 | 10124.81 | 19789.47 | 4701.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 661.64 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 454.92 | 19-JAN-19:00 | 1687.47 | 2555.22 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 647.40 |
February | 5938.94 | 23-FEB-10:42 | 1687.47 | 12776.09 | 3358.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 718.10 |
March | 5971.70 | 17-MAR-19:42 | 843.73 | 6724.26 | 1865.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.99 |
April | 4946.47 | 13-APR-07:01 | 1687.47 | 375.00 | 3731.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 545.86 |
May | 8113.56 | 26-MAY-06:03 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.79 |
June | 12674.69 | 29-JUN-06:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.05 |
July | 15637.83 | 24-JUL-06:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.57 |
August | 15050.36 | 10-AUG-06:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.90 |
September | 10186.63 | 01-SEP-06:03 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.84 |
October | 5019.75 | 25-OCT-07:42 | 674.99 | 5379.41 | 1492.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 529.78 |
November | 5789.63 | 27-NOV-18:42 | 8437.34 | 12776.09 | 3358.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 666.00 |
December | 4992.38 | 04-DEC-18:23 | 6749.87 | 10220.87 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 658.99 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 454.92 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.90 | |
Maximum of Months | 15637.83 | 8437.34 | 12776.09 | 3731.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 718.10 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 356.81 | 19-JAN-19:00 | 1687.47 | 2555.22 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 647.40 |
February | 8110.02 | 10-FEB-18:52 | 10124.81 | 15331.30 | 4029.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 854.38 |
March | 5918.48 | 17-MAR-10:52 | 1687.47 | 12776.09 | 3358.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 689.26 |
April | 6027.23 | 04-APR-18:52 | 3374.94 | 12776.09 | 3358.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 831.50 |
May | 7983.99 | 26-MAY-06:03 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.79 |
June | 12716.03 | 29-JUN-06:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.06 |
July | 15738.00 | 24-JUL-06:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.73 |
August | 15098.42 | 10-AUG-06:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.90 |
September | 10195.73 | 01-SEP-06:03 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.84 |
October | 4168.38 | 21-OCT-07:03 | 674.99 | 150.00 | 1492.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 473.66 |
November | 6849.71 | 28-NOV-18:02 | 8437.34 | 12776.09 | 3358.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 852.02 |
December | 4363.66 | 05-DEC-19:03 | 2699.95 | 10220.87 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 493.57 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 356.81 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.90 | |
Maximum of Months | 15738.00 | 10124.81 | 15331.30 | 4029.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 854.38 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6596.53 | 20-JAN-18:12 | 8437.34 | 12776.09 | 3358.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 783.96 |
February | 4225.78 | 21-FEB-19:33 | 2699.95 | 10220.87 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 588.04 |
March | 4648.73 | 22-MAR-18:12 | 2699.95 | 10220.87 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 602.54 |
April | 4640.98 | 02-APR-10:43 | 2699.95 | 10220.87 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 609.16 |
May | 6323.48 | 26-MAY-06:03 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.76 |
June | 12456.60 | 29-JUN-06:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.59 |
July | 15497.82 | 24-JUL-06:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.42 |
August | 14346.70 | 09-AUG-06:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.76 |
September | 8958.81 | 01-SEP-06:03 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.80 |
October | 4111.17 | 21-OCT-07:03 | 674.99 | 150.00 | 1492.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 467.06 |
November | 5409.32 | 07-NOV-10:43 | 1349.97 | 10220.87 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 673.89 |
December | 303.36 | 28-DEC-18:10 | 1687.47 | 2555.22 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 633.08 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 303.36 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.59 | |
Maximum of Months | 15497.82 | 8437.34 | 12776.09 | 3358.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 783.96 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 70.80 | 30-JAN-08:04 | 0.00 | 750.00 | 736.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1234.76 |
February | 798.64 | 08-FEB-12:00 | 2902.53 | 2726.96 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 781.84 |
March | 2599.77 | 31-MAR-17:10 | 4590.04 | 5453.92 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 583.65 |
April | 7884.75 | 27-APR-19:03 | 2227.52 | 4305.70 | 2238.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 9279.04 | 25-MAY-15:00 | 4657.54 | 2726.96 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 1383.94 | 0.00 |
June | 21484.15 | 29-JUN-07:03 | 0.00 | 300.00 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 22.79 | 0.00 |
July | 25097.59 | 24-JUL-07:03 | 0.00 | 300.00 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 144.18 |
August | 22973.58 | 09-AUG-07:03 | 0.00 | 300.00 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 190.41 |
September | 12374.42 | 01-SEP-07:03 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 311.55 |
October | 7544.66 | 05-OCT-09:43 | 2227.52 | 8180.88 | 4029.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 952.91 |
November | 9352.53 | 03-NOV-18:42 | 7020.07 | 10907.84 | 5373.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1036.68 |
December | 132.27 | 17-DEC-09:04 | 0.00 | 750.00 | 736.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1061.30 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 70.80 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 25097.59 | 7020.07 | 10907.84 | 5373.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1383.94 | 1234.76 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 27.48 | 30-JAN-08:04 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 682.14 |
February | 353.50 | 08-FEB-12:00 | 1451.22 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 430.45 |
March | 5041.55 | 17-MAR-17:33 | 4589.91 | 5617.86 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 576.92 |
April | 2881.09 | 10-APR-19:23 | 1113.73 | 2217.58 | 1119.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.50 |
May | 4796.03 | 25-MAY-15:00 | 2328.71 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 770.39 | 0.00 |
June | 11415.22 | 29-JUN-07:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 15.25 | 0.00 |
July | 13354.73 | 24-JUL-07:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.53 |
August | 10752.03 | 09-AUG-07:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.16 |
September | 5674.91 | 01-SEP-07:03 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 171.92 |
October | 4520.83 | 31-OCT-17:42 | 4589.91 | 5617.86 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 599.18 |
November | 5759.03 | 10-NOV-18:22 | 5737.39 | 7022.32 | 3358.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 649.37 |
December | 53.46 | 17-DEC-09:04 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 584.49 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 27.48 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13354.73 | 5737.39 | 7022.32 | 3358.13 | 0.00 | 0.00 | 0.00 | 0.00 | 770.39 | 682.14 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 28.91 | 30-JAN-08:04 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 680.29 |
February | 3573.28 | 28-FEB-18:13 | 3442.43 | 4213.39 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 457.33 |
March | 4597.81 | 23-MAR-18:15 | 3509.93 | 5617.86 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 543.61 |
April | 3696.38 | 28-APR-10:23 | 4353.67 | 4213.39 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 489.90 |
May | 4684.16 | 25-MAY-15:00 | 2328.71 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 770.39 | 0.00 |
June | 11353.64 | 29-JUN-07:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 16.45 | 0.00 |
July | 13296.09 | 24-JUL-07:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.30 |
August | 10118.83 | 09-AUG-07:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.02 |
September | 5494.62 | 01-SEP-15:00 | 2328.71 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 343.16 | 0.00 |
October | 4274.91 | 25-OCT-09:02 | 1484.97 | 5617.86 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 452.95 |
November | 3527.49 | 14-NOV-19:43 | 2632.45 | 4213.39 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 403.58 |
December | 53.52 | 17-DEC-09:04 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 582.82 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 28.91 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13296.09 | 4353.67 | 5617.86 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 770.39 | 680.29 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 21.98 | 20-JAN-08:04 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 819.86 |
February | 57.69 | 05-FEB-09:04 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 606.24 |
March | 3028.64 | 27-MAR-18:13 | 2632.45 | 4213.39 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 393.12 |
April | 3227.18 | 01-APR-10:43 | 5872.39 | 4213.39 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 461.68 |
May | 4397.24 | 25-MAY-15:00 | 2328.71 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 770.37 | 0.00 |
June | 10922.18 | 30-JUN-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.37 | 0.00 |
July | 12663.29 | 24-JUL-07:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.27 |
August | 8256.78 | 09-AUG-07:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.66 |
September | 5395.71 | 01-SEP-15:00 | 2328.71 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 343.15 | 0.00 |
October | 4153.51 | 13-OCT-18:03 | 3509.93 | 5617.86 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 463.47 |
November | 4376.19 | 16-NOV-19:23 | 3509.93 | 5617.86 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 509.69 |
December | 70.35 | 17-DEC-09:04 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 574.88 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 21.98 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12663.29 | 5872.39 | 5617.86 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 770.37 | 819.86 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1170.82 |
February | 116.56 | 21-FEB-08:04 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 654.30 |
March | 117.82 | 28-MAR-07:04 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 661.05 |
April | 1541.81 | 11-APR-18:55 | 1754.97 | 2808.93 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 247.96 |
May | 4164.84 | 18-MAY-14:40 | 2328.71 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 773.73 | 0.00 |
June | 10329.10 | 30-JUN-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 55.06 | 0.00 |
July | 10657.34 | 23-JUL-08:62 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.83 |
August | 6062.99 | 08-AUG-14:50 | 2328.71 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1094.79 | 0.00 |
September | 5507.41 | 01-SEP-14:20 | 2328.71 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 301.09 | 0.00 |
October | 2578.75 | 20-OCT-19:50 | 371.24 | 739.19 | 373.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.42 |
November | 1775.40 | 17-NOV-13:55 | 4792.41 | 2808.93 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1832.14 |
December | 88.24 | 06-DEC-08:04 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 790.76 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 10657.34 | 4792.41 | 2808.93 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 1094.79 | 1832.14 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.671831E+11 | 57810.05 | 13-JAN-17:49 | 0.264663E+12 | 336891.44 | 04-JAN-12:09 |
February | 0.590998E+11 | 55792.39 | 23-FEB-19:30 | 0.177641E+12 | 268935.47 | 14-FEB-08:09 |
March | 0.643721E+11 | 53415.19 | 22-MAR-18:30 | 0.151421E+12 | 252664.72 | 15-MAR-07:10 |
April | 0.592918E+11 | 53469.40 | 23-APR-14:50 | 0.588222E+11 | 178799.29 | 04-APR-07:10 |
May | 0.637037E+11 | 66358.48 | 25-MAY-15:39 | 0.591957E+10 | 113322.82 | 01-MAY-07:10 |
June | 0.683904E+11 | 85321.93 | 29-JUN-14:50 | 0.127424E+09 | 12364.70 | 04-JUN-08:09 |
July | 0.759799E+11 | 84362.65 | 15-JUL-13:50 | 1038820.28 | 771.71 | 09-JUL-09:30 |
August | 0.722982E+11 | 77766.25 | 08-AUG-15:09 | 9107149.78 | 3170.51 | 19-AUG-07:10 |
September | 0.601875E+11 | 67947.69 | 01-SEP-14:50 | 0.347337E+10 | 31355.02 | 23-SEP-07:10 |
October | 0.622476E+11 | 50851.83 | 13-OCT-17:40 | 0.428159E+11 | 147425.58 | 30-OCT-07:10 |
November | 0.623604E+11 | 53658.43 | 08-NOV-17:40 | 0.111889E+12 | 222514.56 | 25-NOV-08:09 |
December | 0.668692E+11 | 56993.93 | 02-DEC-17:40 | 0.242869E+12 | 324249.93 | 24-DEC-12:09 |
Annual Sum or Average | 0.781984E+12 | 0.105965E+13 | ||||
Minimum of Months | 0.590998E+11 | 50851.83 | 1038820.28 | 771.71 | ||
Maximum of Months | 0.759799E+11 | 85321.93 | 0.264663E+12 | 336891.44 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [J] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.310073E+11 | 0.721946E+10 | 0.108325E+11 | 0.00 | 0.116489E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.587869E+09 | 0.588711E+10 | 0.00 |
February | 0.280657E+11 | 0.574580E+10 | 0.980803E+10 | 0.00 | 0.958359E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.531941E+09 | 0.536470E+10 | 0.00 |
March | 0.314703E+11 | 0.530961E+10 | 0.110075E+11 | 0.00 | 0.100219E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.590355E+09 | 0.597251E+10 | 0.00 |
April | 0.300741E+11 | 0.408045E+10 | 0.105079E+11 | 0.00 | 0.825605E+10 | 0.00 | 0.00 | 0.154661E+09 | 0.00 | 0.00 | 0.552034E+09 | 0.566661E+10 | 0.00 |
May | 0.312330E+11 | 0.340561E+10 | 0.109147E+11 | 0.00 | 0.783461E+10 | 0.00 | 0.00 | 0.419045E+10 | 0.00 | 0.00 | 0.391499E+09 | 0.573382E+10 | 0.00 |
June | 0.304143E+11 | 0.290248E+10 | 0.106386E+11 | 0.00 | 0.765475E+10 | 0.00 | 0.00 | 0.110608E+11 | 0.00 | 0.00 | 0.267213E+09 | 0.545230E+10 | 0.00 |
July | 0.309042E+11 | 0.314167E+10 | 0.107945E+11 | 0.00 | 0.773200E+10 | 0.00 | 0.00 | 0.176565E+11 | 0.00 | 0.00 | 0.261206E+09 | 0.548984E+10 | 0.00 |
August | 0.314595E+11 | 0.380040E+10 | 0.110006E+11 | 0.00 | 0.785922E+10 | 0.00 | 0.00 | 0.124920E+11 | 0.00 | 0.00 | 0.184149E+09 | 0.550223E+10 | 0.00 |
September | 0.300847E+11 | 0.467521E+10 | 0.105148E+11 | 0.00 | 0.753105E+10 | 0.00 | 0.00 | 0.175063E+10 | 0.00 | 0.00 | 0.310920E+09 | 0.532024E+10 | 0.00 |
October | 0.310073E+11 | 0.592751E+10 | 0.108325E+11 | 0.00 | 0.825947E+10 | 0.00 | 0.00 | 97460345.31 | 0.00 | 0.00 | 0.544370E+09 | 0.557910E+10 | 0.00 |
November | 0.300409E+11 | 0.669740E+10 | 0.104978E+11 | 0.00 | 0.904939E+10 | 0.00 | 0.00 | 61054.02 | 0.00 | 0.00 | 0.567984E+09 | 0.550681E+10 | 0.00 |
December | 0.309156E+11 | 0.747389E+10 | 0.108050E+11 | 0.00 | 0.112792E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.590355E+09 | 0.580515E+10 | 0.00 |
Annual Sum or Average | 0.366677E+12 | 0.603795E+11 | 0.128154E+12 | 0.00 | 0.106710E+12 | 0.00 | 0.00 | 0.474026E+11 | 0.00 | 0.00 | 0.537990E+10 | 0.672804E+11 | 0.00 |
Minimum of Months | 0.280657E+11 | 0.290248E+10 | 0.980803E+10 | 0.00 | 0.753105E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.184149E+09 | 0.532024E+10 | 0.00 |
Maximum of Months | 0.314703E+11 | 0.747389E+10 | 0.110075E+11 | 0.00 | 0.116489E+11 | 0.00 | 0.00 | 0.176565E+11 | 0.00 | 0.00 | 0.590355E+09 | 0.597251E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.264663E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.177641E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.151421E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.588222E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.591957E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.127424E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 1038820.28 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 9107149.78 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.347337E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.428159E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.111889E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.242869E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.105965E+13 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 1038820.28 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.264663E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 23459.17 | 01-JAN-11:09 | 5507.06 | 01-JAN-06:10 | 8059.50 | 01-JAN-11:09 | 0.00 | 10357.57 | 04-JAN-12:09 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 23459.17 | 01-FEB-10:09 | 5507.06 | 01-FEB-06:10 | 8059.50 | 01-FEB-10:09 | 0.00 | 9332.50 | 14-FEB-08:09 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 23459.17 | 01-MAR-10:09 | 5507.06 | 01-MAR-06:10 | 8059.50 | 01-MAR-10:09 | 0.00 | 9078.55 | 15-MAR-07:10 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 23459.17 | 01-APR-09:09 | 5507.06 | 01-APR-05:10 | 8059.50 | 01-APR-09:09 | 0.00 | 7960.39 | 04-APR-07:10 | 0.00 | 0.00 | 01-APR-00:10 |
May | 23459.17 | 01-MAY-09:09 | 5507.06 | 01-MAY-19:30 | 8059.50 | 01-MAY-09:09 | 0.00 | 6974.22 | 01-MAY-07:10 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 23459.17 | 01-JUN-09:09 | 5507.06 | 01-JUN-19:00 | 8059.50 | 01-JUN-09:09 | 0.00 | 7565.96 | 29-JUN-16:10 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 23459.17 | 01-JUL-09:09 | 5507.06 | 01-JUL-20:19 | 8059.50 | 01-JUL-09:09 | 0.00 | 7281.37 | 15-JUL-13:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 23459.17 | 01-AUG-09:09 | 5507.06 | 01-AUG-19:49 | 8059.50 | 01-AUG-09:09 | 0.00 | 6284.86 | 08-AUG-14:00 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 23459.17 | 01-SEP-09:09 | 5507.06 | 01-SEP-05:10 | 8059.50 | 01-SEP-09:09 | 0.00 | 5732.91 | 23-SEP-07:10 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 23459.17 | 01-OCT-10:09 | 5507.06 | 01-OCT-05:10 | 8059.50 | 01-OCT-10:09 | 0.00 | 7492.90 | 30-OCT-07:10 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 23459.17 | 01-NOV-09:09 | 5507.06 | 01-NOV-05:10 | 8059.50 | 01-NOV-09:09 | 0.00 | 8623.68 | 25-NOV-08:09 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 23459.17 | 01-DEC-10:09 | 5507.06 | 01-DEC-06:10 | 8059.50 | 01-DEC-10:09 | 0.00 | 10165.72 | 24-DEC-12:09 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||||
Minimum of Months | 23459.17 | 5507.06 | 8059.50 | 0.00 | 5732.91 | 0.00 | 0.00 | |||||
Maximum of Months | 23459.17 | 5507.06 | 8059.50 | 0.00 | 10357.57 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY {Maximum} [W] | HEATRECOVERY:ELECTRICITY {TIMESTAMP} | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 345.24 | 01-JAN-09:09 | 12066.72 | 27-JAN-18:00 | 0.00 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 345.24 | 01-FEB-21:10 | 11464.95 | 23-FEB-19:30 | 0.00 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 345.24 | 01-MAR-21:19 | 9704.69 | 22-MAR-18:30 | 0.00 |
April | 11621.45 | 23-APR-15:00 | 0.00 | 0.00 | 345.24 | 01-APR-08:30 | 11051.02 | 14-APR-12:50 | 0.00 |
May | 24509.68 | 25-MAY-16:10 | 0.00 | 0.00 | 345.24 | 01-MAY-20:19 | 9747.77 | 06-MAY-12:39 | 0.00 |
June | 42398.65 | 29-JUN-16:10 | 0.00 | 0.00 | 345.24 | 04-JUN-08:09 | 11812.74 | 13-JUN-16:49 | 0.00 |
July | 39290.64 | 15-JUL-13:00 | 0.00 | 0.00 | 345.24 | 03-JUL-19:10 | 8362.33 | 05-JUL-15:09 | 0.00 |
August | 34878.08 | 08-AUG-14:00 | 0.00 | 0.00 | 345.24 | 08-AUG-19:10 | 9694.51 | 31-AUG-11:09 | 0.00 |
September | 23267.68 | 01-SEP-14:20 | 0.00 | 0.00 | 345.24 | 06-SEP-08:09 | 10280.39 | 21-SEP-13:00 | 0.00 |
October | 5105.74 | 19-OCT-14:00 | 0.00 | 0.00 | 345.24 | 01-OCT-08:20 | 9724.69 | 13-OCT-13:09 | 0.00 |
November | 101.76 | 01-NOV-20:40 | 0.00 | 0.00 | 345.24 | 02-NOV-10:20 | 9736.34 | 09-NOV-13:50 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 345.24 | 01-DEC-00:20 | 10750.57 | 02-DEC-17:40 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 345.24 | 8362.33 | 0.00 | |||
Maximum of Months | 42398.65 | 0.00 | 0.00 | 345.24 | 12066.72 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 57810.05 | 13-JAN-17:49 | 23459.17 | 8059.50 | 5507.06 | 0.00 | 9752.18 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 55792.39 | 23-FEB-19:30 | 23459.17 | 8059.50 | 5507.06 | 0.00 | 6956.48 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 53415.19 | 22-MAR-18:30 | 23459.17 | 8059.50 | 5507.06 | 0.00 | 6339.53 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 53469.40 | 23-APR-14:50 | 23459.17 | 8059.50 | 0.00 | 0.00 | 5250.70 | 0.00 | 0.00 | 10914.76 | 0.00 |
May | 66358.48 | 25-MAY-15:39 | 23459.17 | 8059.50 | 0.00 | 0.00 | 5250.70 | 0.00 | 0.00 | 23793.49 | 0.00 |
June | 85321.93 | 29-JUN-14:50 | 23459.17 | 8059.50 | 0.00 | 0.00 | 7264.06 | 0.00 | 0.00 | 40741.07 | 0.00 |
July | 84362.65 | 15-JUL-13:50 | 23459.17 | 8059.50 | 0.00 | 0.00 | 6990.92 | 0.00 | 0.00 | 37915.87 | 0.00 |
August | 77766.25 | 08-AUG-15:09 | 23459.17 | 8059.50 | 0.00 | 0.00 | 6156.95 | 0.00 | 0.00 | 34303.08 | 0.00 |
September | 67947.69 | 01-SEP-14:50 | 23459.17 | 8059.50 | 0.00 | 0.00 | 5250.70 | 0.00 | 0.00 | 23262.26 | 0.00 |
October | 50851.83 | 13-OCT-17:40 | 23459.17 | 8059.50 | 5507.06 | 0.00 | 5913.64 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 53658.43 | 08-NOV-17:40 | 23459.17 | 8059.50 | 5507.06 | 0.00 | 6591.84 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 56993.93 | 02-DEC-17:40 | 23459.17 | 8059.50 | 5507.06 | 0.00 | 8872.40 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 50851.83 | 23459.17 | 8059.50 | 0.00 | 0.00 | 5250.70 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 85321.93 | 23459.17 | 8059.50 | 5507.06 | 0.00 | 9752.18 | 0.00 | 0.00 | 40741.07 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 336891.44 | 04-JAN-12:09 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 268935.47 | 14-FEB-08:09 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 252664.72 | 15-MAR-07:10 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 178799.29 | 04-APR-07:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 113322.82 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 12364.70 | 04-JUN-08:09 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 771.71 | 09-JUL-09:30 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 3170.51 | 19-AUG-07:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 31355.02 | 23-SEP-07:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 147425.58 | 30-OCT-07:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 222514.56 | 25-NOV-08:09 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 324249.93 | 24-DEC-12:09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 771.71 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 336891.44 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 7.17 | 20.11 | 3.00 | 20.15 | 0.00 | 20.15 | 0.00 | 20.15 |
February | 5.00 | 20.05 | 1.83 | 20.10 | 0.00 | 20.10 | 0.00 | 20.10 |
March | 4.17 | 20.32 | 1.50 | 20.29 | 0.00 | 20.29 | 0.00 | 20.29 |
April | 0.83 | 20.50 | 0.00 | 20.50 | 0.00 | 20.50 | 0.00 | 20.50 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.33 | 20.50 | 0.00 | 20.50 | 0.00 | 20.50 | 0.00 | 20.50 |
November | 0.83 | 20.44 | 0.17 | 20.45 | 0.00 | 20.45 | 0.00 | 20.45 |
December | 6.33 | 20.25 | 2.50 | 20.25 | 0.00 | 20.25 | 0.00 | 20.25 |
Annual Sum or Average | 24.67 | 20.20 | 9.00 | 20.21 | 0.00 | 20.21 | 0.00 | 20.21 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 7.17 | 20.50 | 3.00 | 20.50 | 0.00 | 20.50 | 0.00 | 20.50 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.67 | 20.39 | 1.17 | 20.38 | 0.00 | 20.38 | 0.00 | 20.38 |
February | 1.83 | 20.48 | 0.33 | 20.49 | 0.00 | 20.49 | 0.00 | 20.49 |
March | 0.50 | 20.47 | 0.00 | 20.47 | 0.00 | 20.47 | 0.00 | 20.47 |
April | 0.33 | 20.46 | 0.00 | 20.46 | 0.00 | 20.46 | 0.00 | 20.46 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.33 | 20.48 | 0.00 | 20.48 | 0.00 | 20.48 | 0.00 | 20.48 |
December | 2.50 | 20.39 | 1.00 | 20.39 | 0.00 | 20.39 | 0.00 | 20.39 |
Annual Sum or Average | 9.17 | 20.42 | 2.50 | 20.41 | 0.00 | 20.41 | 0.00 | 20.41 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3.67 | 20.48 | 1.17 | 20.49 | 0.00 | 20.49 | 0.00 | 20.49 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.67 | 20.31 | 0.00 | 20.31 | 0.00 | 20.31 | 0.00 | 20.31 |
February | 1.17 | 20.41 | 0.00 | 20.41 | 0.00 | 20.41 | 0.00 | 20.41 |
March | 0.33 | 20.38 | 0.00 | 20.38 | 0.00 | 20.38 | 0.00 | 20.38 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1.67 | 20.31 | 0.00 | 20.31 | 0.00 | 20.31 | 0.00 | 20.31 |
Annual Sum or Average | 5.83 | 20.34 | 0.00 | 20.34 | 0.00 | 20.34 | 0.00 | 20.34 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.67 | 20.41 | 0.00 | 20.41 | 0.00 | 20.41 | 0.00 | 20.41 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.67 | 20.27 | 0.00 | 20.27 | 0.00 | 20.27 | 0.00 | 20.27 |
February | 1.67 | 20.39 | 0.00 | 20.39 | 0.00 | 20.39 | 0.00 | 20.39 |
March | 0.67 | 20.41 | 0.00 | 20.41 | 0.00 | 20.41 | 0.00 | 20.41 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 2.17 | 20.33 | 0.00 | 20.33 | 0.00 | 20.33 | 0.00 | 20.33 |
Annual Sum or Average | 7.17 | 20.33 | 0.00 | 20.33 | 0.00 | 20.33 | 0.00 | 20.33 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.67 | 20.41 | 0.00 | 20.41 | 0.00 | 20.41 | 0.00 | 20.41 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.33 | 20.29 | 0.00 | 20.29 | 0.00 | 20.29 | 0.00 | 20.29 |
February | 2.17 | 20.36 | 0.00 | 20.36 | 0.00 | 20.36 | 0.00 | 20.36 |
March | 1.00 | 20.37 | 0.00 | 20.37 | 0.00 | 20.37 | 0.00 | 20.37 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 2.83 | 19.99 | 0.00 | 19.99 | 0.00 | 19.99 | 0.00 | 19.99 |
Annual Sum or Average | 9.33 | 20.22 | 0.00 | 20.22 | 0.00 | 20.22 | 0.00 | 20.22 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3.33 | 20.37 | 0.00 | 20.37 | 0.00 | 20.37 | 0.00 | 20.37 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 5.67 | 19.45 | 0.00 | 19.45 | 0.00 | 19.45 | 0.00 | 19.45 |
February | 3.33 | 20.23 | 0.00 | 20.23 | 0.00 | 20.23 | 0.00 | 20.23 |
March | 1.83 | 20.27 | 0.00 | 20.27 | 0.00 | 20.27 | 0.00 | 20.27 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.83 | 20.40 | 0.00 | 20.40 | 0.00 | 20.40 | 0.00 | 20.40 |
December | 4.33 | 19.62 | 0.00 | 19.62 | 0.00 | 19.62 | 0.00 | 19.62 |
Annual Sum or Average | 16.00 | 19.80 | 0.00 | 19.80 | 0.00 | 19.80 | 0.00 | 19.80 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 5.67 | 20.40 | 0.00 | 20.40 | 0.00 | 20.40 | 0.00 | 20.40 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 4.83 | 20.05 | 0.00 | 20.05 | 0.00 | 20.05 | 0.00 | 20.05 |
February | 3.33 | 19.98 | 0.00 | 19.98 | 0.00 | 19.98 | 0.00 | 19.98 |
March | 1.50 | 20.26 | 0.00 | 20.26 | 0.00 | 20.26 | 0.00 | 20.26 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.67 | 20.40 | 0.00 | 20.40 | 0.00 | 20.40 | 0.00 | 20.40 |
December | 4.00 | 19.83 | 0.00 | 19.83 | 0.00 | 19.83 | 0.00 | 19.83 |
Annual Sum or Average | 14.33 | 20.01 | 0.00 | 20.01 | 0.00 | 20.01 | 0.00 | 20.01 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4.83 | 20.40 | 0.00 | 20.40 | 0.00 | 20.40 | 0.00 | 20.40 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 5.17 | 19.90 | 0.00 | 19.90 | 0.00 | 19.90 | 0.00 | 19.90 |
February | 3.33 | 20.27 | 0.00 | 20.27 | 0.00 | 20.27 | 0.00 | 20.27 |
March | 1.83 | 20.29 | 0.00 | 20.29 | 0.00 | 20.29 | 0.00 | 20.29 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.67 | 20.38 | 0.00 | 20.38 | 0.00 | 20.38 | 0.00 | 20.38 |
December | 4.33 | 19.44 | 0.00 | 19.44 | 0.00 | 19.44 | 0.00 | 19.44 |
Annual Sum or Average | 15.33 | 19.92 | 0.00 | 19.92 | 0.00 | 19.92 | 0.00 | 19.92 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 5.17 | 20.38 | 0.00 | 20.38 | 0.00 | 20.38 | 0.00 | 20.38 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 5.50 | 19.59 | 0.00 | 19.59 | 0.00 | 19.59 | 0.00 | 19.59 |
February | 4.17 | 19.60 | 0.00 | 19.60 | 0.00 | 19.60 | 0.00 | 19.60 |
March | 2.50 | 20.29 | 0.00 | 20.29 | 0.00 | 20.29 | 0.00 | 20.29 |
April | 0.50 | 20.50 | 0.00 | 20.50 | 0.00 | 20.50 | 0.00 | 20.50 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1.17 | 20.36 | 0.00 | 20.36 | 0.00 | 20.36 | 0.00 | 20.36 |
December | 4.83 | 19.50 | 0.00 | 19.50 | 0.00 | 19.50 | 0.00 | 19.50 |
Annual Sum or Average | 18.67 | 19.73 | 0.00 | 19.73 | 0.00 | 19.73 | 0.00 | 19.73 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 5.50 | 20.50 | 0.00 | 20.50 | 0.00 | 20.50 | 0.00 | 20.50 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 39.50 | 15.48 | 0.00 | 15.48 | 0.00 | 15.48 | 0.00 | 15.48 |
February | 25.83 | 15.81 | 0.00 | 15.81 | 0.00 | 15.81 | 0.00 | 15.81 |
March | 16.17 | 16.60 | 0.00 | 16.60 | 0.00 | 16.60 | 0.00 | 16.60 |
April | 3.33 | 18.97 | 0.00 | 18.97 | 0.00 | 18.97 | 0.00 | 18.97 |
May | 0.17 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.17 | 20.26 | 0.00 | 20.26 | 0.00 | 20.26 | 0.00 | 20.26 |
November | 4.50 | 18.35 | 0.00 | 18.35 | 0.00 | 18.35 | 0.00 | 18.35 |
December | 33.17 | 15.65 | 0.00 | 15.65 | 0.00 | 15.65 | 0.00 | 15.65 |
Annual Sum or Average | 122.83 | 15.96 | 0.00 | 15.96 | 0.00 | 15.96 | 0.00 | 15.96 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 39.50 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 |
Report: ComfortReportSimple55Monthly
For: LGSTORE1
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 496.00 | 21.04 | 496.00 | 21.04 | 496.00 | 21.04 |
February | 448.00 | 21.05 | 427.50 | 21.05 | 427.50 | 21.05 |
March | 497.00 | 21.12 | 421.00 | 21.09 | 421.00 | 21.08 |
April | 469.17 | 21.79 | 194.33 | 21.59 | 194.33 | 21.47 |
May | 308.83 | 23.21 | 79.50 | 23.31 | 6.17 | 23.27 |
June | 165.17 | 23.78 | 247.50 | 23.85 | 86.33 | 23.85 |
July | 104.33 | 23.88 | 445.67 | 23.89 | 96.83 | 23.89 |
August | 71.00 | 23.84 | 411.00 | 23.88 | 58.33 | 23.88 |
September | 155.17 | 23.33 | 119.00 | 23.57 | 10.17 | 23.59 |
October | 434.17 | 22.05 | 33.67 | 22.00 | 29.33 | 21.95 |
November | 480.00 | 21.19 | 315.67 | 21.15 | 315.67 | 21.13 |
December | 496.00 | 21.06 | 496.00 | 21.06 | 496.00 | 21.06 |
Annual Sum or Average | 4124.83 | 21.74 | 3686.83 | 21.89 | 2637.67 | 21.75 |
Minimum of Months | 71.00 | 21.04 | 33.67 | 21.04 | 6.17 | 21.04 |
Maximum of Months | 497.00 | 23.88 | 496.00 | 23.89 | 496.00 | 23.89 |
Report: ComfortReportSimple55Monthly
For: SMSTORE1
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 496.00 | 21.12 | 472.33 | 21.11 | 472.33 | 21.10 |
February | 448.00 | 21.18 | 339.50 | 21.14 | 339.50 | 21.13 |
March | 497.00 | 21.28 | 288.17 | 21.22 | 288.17 | 21.20 |
April | 467.83 | 21.90 | 64.00 | 21.83 | 60.17 | 21.75 |
May | 301.17 | 22.94 | 82.67 | 23.13 | 1.50 | 23.12 |
June | 142.00 | 23.64 | 269.00 | 23.79 | 72.67 | 23.81 |
July | 68.83 | 23.84 | 447.83 | 23.86 | 64.33 | 23.86 |
August | 45.33 | 23.64 | 410.33 | 23.85 | 34.17 | 23.85 |
September | 174.17 | 22.71 | 116.67 | 23.17 | 7.33 | 23.19 |
October | 441.83 | 21.93 | 7.00 | 21.94 | 2.17 | 21.94 |
November | 480.00 | 21.42 | 148.17 | 21.35 | 148.17 | 21.31 |
December | 496.00 | 21.13 | 461.67 | 21.12 | 461.67 | 21.11 |
Annual Sum or Average | 4058.17 | 21.73 | 3107.33 | 21.97 | 1952.17 | 21.84 |
Minimum of Months | 45.33 | 21.12 | 7.00 | 21.11 | 1.50 | 21.10 |
Maximum of Months | 497.00 | 23.84 | 472.33 | 23.86 | 472.33 | 23.86 |
Report: ComfortReportSimple55Monthly
For: SMSTORE2
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 371.00 | 21.11 | 371.00 | 21.11 | 371.00 | 21.11 |
February | 336.00 | 21.11 | 295.67 | 21.11 | 295.67 | 21.11 |
March | 379.00 | 21.11 | 268.33 | 21.11 | 268.33 | 21.11 |
April | 355.33 | 21.46 | 95.83 | 21.40 | 94.83 | 21.35 |
May | 236.00 | 22.40 | 77.50 | 22.76 | 5.00 | 22.73 |
June | 146.00 | 23.52 | 201.17 | 23.81 | 74.83 | 23.85 |
July | 78.33 | 24.03 | 336.67 | 24.02 | 71.33 | 24.04 |
August | 58.17 | 23.67 | 323.00 | 23.94 | 38.83 | 23.95 |
September | 186.83 | 22.28 | 73.00 | 22.75 | 12.17 | 22.80 |
October | 344.50 | 21.35 | 20.83 | 21.36 | 18.17 | 21.35 |
November | 360.00 | 21.14 | 183.00 | 21.13 | 183.00 | 21.12 |
December | 369.00 | 21.11 | 367.00 | 21.11 | 367.00 | 21.11 |
Annual Sum or Average | 3220.17 | 21.57 | 2613.00 | 21.86 | 1800.17 | 21.76 |
Minimum of Months | 58.17 | 21.11 | 20.83 | 21.11 | 5.00 | 21.11 |
Maximum of Months | 379.00 | 24.03 | 371.00 | 24.02 | 371.00 | 24.04 |
Report: ComfortReportSimple55Monthly
For: SMSTORE3
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 371.00 | 21.11 | 371.00 | 21.11 | 371.00 | 21.11 |
February | 336.00 | 21.11 | 305.83 | 21.11 | 305.83 | 21.11 |
March | 379.00 | 21.11 | 276.17 | 21.11 | 276.17 | 21.11 |
April | 355.67 | 21.43 | 107.00 | 21.36 | 106.17 | 21.32 |
May | 239.17 | 22.33 | 77.33 | 22.69 | 6.17 | 22.66 |
June | 154.00 | 23.47 | 190.83 | 23.78 | 74.83 | 23.82 |
July | 79.17 | 24.02 | 335.67 | 24.02 | 71.33 | 24.03 |
August | 61.00 | 23.64 | 321.83 | 23.93 | 39.67 | 23.95 |
September | 192.50 | 22.21 | 69.83 | 22.67 | 12.17 | 22.72 |
October | 347.00 | 21.33 | 26.17 | 21.33 | 24.17 | 21.32 |
November | 360.00 | 21.13 | 203.83 | 21.12 | 203.83 | 21.12 |
December | 369.00 | 21.11 | 368.83 | 21.11 | 368.83 | 21.11 |
Annual Sum or Average | 3243.50 | 21.56 | 2654.33 | 21.84 | 1860.17 | 21.74 |
Minimum of Months | 61.00 | 21.11 | 26.17 | 21.11 | 6.17 | 21.11 |
Maximum of Months | 379.00 | 24.02 | 371.00 | 24.02 | 371.00 | 24.03 |
Report: ComfortReportSimple55Monthly
For: SMSTORE4
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 371.00 | 21.11 | 371.00 | 21.11 | 371.00 | 21.11 |
February | 336.00 | 21.11 | 312.83 | 21.11 | 312.83 | 21.11 |
March | 379.00 | 21.11 | 295.67 | 21.11 | 295.67 | 21.11 |
April | 356.17 | 21.39 | 121.17 | 21.32 | 120.33 | 21.28 |
May | 251.33 | 22.26 | 75.50 | 22.60 | 8.33 | 22.56 |
June | 170.50 | 23.40 | 178.17 | 23.71 | 77.67 | 23.77 |
July | 84.83 | 23.97 | 332.67 | 24.01 | 74.00 | 24.02 |
August | 75.67 | 23.58 | 317.67 | 23.91 | 44.83 | 23.92 |
September | 202.50 | 22.14 | 67.00 | 22.59 | 12.67 | 22.64 |
October | 351.17 | 21.32 | 33.33 | 21.31 | 32.50 | 21.29 |
November | 360.00 | 21.13 | 225.00 | 21.12 | 225.00 | 21.12 |
December | 369.00 | 21.11 | 369.00 | 21.11 | 369.00 | 21.11 |
Annual Sum or Average | 3307.17 | 21.56 | 2699.00 | 21.82 | 1943.83 | 21.73 |
Minimum of Months | 75.67 | 21.11 | 33.33 | 21.11 | 8.33 | 21.11 |
Maximum of Months | 379.00 | 23.97 | 371.00 | 24.01 | 371.00 | 24.02 |
Report: ComfortReportSimple55Monthly
For: LGSTORE2
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.11 | 340.00 | 21.11 | 340.00 | 21.11 |
February | 308.00 | 21.11 | 308.00 | 21.11 | 308.00 | 21.11 |
March | 348.00 | 21.11 | 309.33 | 21.11 | 309.33 | 21.11 |
April | 328.67 | 21.35 | 167.17 | 21.27 | 167.00 | 21.23 |
May | 241.50 | 22.20 | 51.83 | 22.39 | 11.00 | 22.35 |
June | 182.50 | 23.28 | 145.00 | 23.56 | 78.50 | 23.63 |
July | 94.50 | 23.82 | 292.33 | 23.91 | 78.17 | 23.93 |
August | 101.00 | 23.48 | 277.50 | 23.80 | 67.33 | 23.81 |
September | 207.67 | 22.15 | 56.67 | 22.51 | 16.33 | 22.57 |
October | 332.50 | 21.36 | 67.67 | 21.32 | 67.67 | 21.29 |
November | 330.00 | 21.12 | 255.00 | 21.12 | 255.00 | 21.12 |
December | 338.00 | 21.11 | 338.00 | 21.11 | 338.00 | 21.11 |
Annual Sum or Average | 3152.33 | 21.60 | 2608.50 | 21.77 | 2036.33 | 21.69 |
Minimum of Months | 94.50 | 21.11 | 51.83 | 21.11 | 11.00 | 21.11 |
Maximum of Months | 348.00 | 23.82 | 340.00 | 23.91 | 340.00 | 23.93 |
Report: ComfortReportSimple55Monthly
For: SMSTORE5
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.11 | 340.00 | 21.11 | 340.00 | 21.11 |
February | 308.00 | 21.11 | 307.50 | 21.11 | 307.50 | 21.11 |
March | 348.00 | 21.11 | 310.67 | 21.11 | 310.67 | 21.11 |
April | 329.00 | 21.34 | 171.33 | 21.26 | 171.33 | 21.22 |
May | 246.83 | 22.20 | 49.17 | 22.36 | 13.00 | 22.31 |
June | 192.50 | 23.28 | 139.00 | 23.55 | 78.00 | 23.61 |
July | 97.50 | 23.82 | 275.50 | 23.91 | 80.50 | 23.93 |
August | 104.83 | 23.49 | 269.00 | 23.80 | 69.50 | 23.81 |
September | 213.67 | 22.18 | 53.17 | 22.51 | 16.33 | 22.57 |
October | 335.00 | 21.38 | 70.33 | 21.33 | 70.33 | 21.30 |
November | 330.00 | 21.12 | 256.00 | 21.12 | 256.00 | 21.11 |
December | 338.00 | 21.11 | 338.00 | 21.11 | 338.00 | 21.11 |
Annual Sum or Average | 3183.33 | 21.61 | 2579.67 | 21.76 | 2051.17 | 21.68 |
Minimum of Months | 97.50 | 21.11 | 49.17 | 21.11 | 13.00 | 21.11 |
Maximum of Months | 348.00 | 23.82 | 340.00 | 23.91 | 340.00 | 23.93 |
Report: ComfortReportSimple55Monthly
For: SMSTORE6
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.11 | 340.00 | 21.11 | 340.00 | 21.11 |
February | 308.00 | 21.11 | 308.00 | 21.11 | 308.00 | 21.11 |
March | 348.00 | 21.11 | 315.00 | 21.11 | 315.00 | 21.11 |
April | 329.00 | 21.33 | 177.33 | 21.25 | 177.33 | 21.22 |
May | 249.50 | 22.17 | 49.17 | 22.32 | 15.00 | 22.26 |
June | 201.17 | 23.25 | 138.17 | 23.52 | 79.00 | 23.59 |
July | 99.17 | 23.80 | 272.17 | 23.91 | 80.67 | 23.93 |
August | 109.17 | 23.47 | 265.17 | 23.79 | 71.67 | 23.80 |
September | 217.83 | 22.17 | 51.50 | 22.48 | 16.33 | 22.54 |
October | 336.00 | 21.38 | 75.50 | 21.33 | 75.50 | 21.30 |
November | 330.00 | 21.12 | 260.17 | 21.12 | 260.17 | 21.11 |
December | 338.00 | 21.11 | 338.00 | 21.11 | 338.00 | 21.11 |
Annual Sum or Average | 3205.83 | 21.61 | 2590.17 | 21.76 | 2076.67 | 21.67 |
Minimum of Months | 99.17 | 21.11 | 49.17 | 21.11 | 15.00 | 21.11 |
Maximum of Months | 348.00 | 23.80 | 340.00 | 23.91 | 340.00 | 23.93 |
Report: ComfortReportSimple55Monthly
For: SMSTORE7
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.11 | 340.00 | 21.11 | 340.00 | 21.11 |
February | 308.00 | 21.11 | 308.00 | 21.11 | 308.00 | 21.11 |
March | 348.00 | 21.11 | 325.67 | 21.11 | 325.67 | 21.11 |
April | 329.17 | 21.29 | 198.33 | 21.22 | 198.33 | 21.19 |
May | 257.50 | 22.10 | 50.17 | 22.18 | 23.33 | 22.10 |
June | 215.33 | 23.16 | 136.67 | 23.44 | 82.00 | 23.52 |
July | 104.00 | 23.76 | 263.83 | 23.89 | 83.17 | 23.91 |
August | 120.17 | 23.42 | 257.67 | 23.76 | 77.00 | 23.78 |
September | 227.50 | 22.13 | 48.83 | 22.42 | 16.50 | 22.47 |
October | 336.50 | 21.36 | 94.67 | 21.31 | 94.67 | 21.27 |
November | 330.00 | 21.12 | 274.67 | 21.12 | 274.67 | 21.11 |
December | 338.00 | 21.11 | 338.00 | 21.11 | 338.00 | 21.11 |
Annual Sum or Average | 3254.17 | 21.61 | 2636.50 | 21.74 | 2161.33 | 21.66 |
Minimum of Months | 104.00 | 21.11 | 48.83 | 21.11 | 16.50 | 21.11 |
Maximum of Months | 348.00 | 23.76 | 340.00 | 23.89 | 340.00 | 23.91 |
Report: ComfortReportSimple55Monthly
For: SMSTORE8
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.11 | 340.00 | 21.11 | 340.00 | 21.11 |
February | 308.00 | 21.11 | 308.00 | 21.11 | 308.00 | 21.11 |
March | 348.00 | 21.11 | 348.00 | 21.11 | 348.00 | 21.11 |
April | 330.00 | 21.23 | 271.17 | 21.18 | 271.17 | 21.16 |
May | 288.00 | 22.07 | 60.50 | 22.02 | 45.17 | 21.92 |
June | 240.33 | 23.02 | 126.00 | 23.28 | 80.50 | 23.36 |
July | 113.00 | 23.64 | 245.50 | 23.85 | 86.00 | 23.88 |
August | 139.33 | 23.26 | 239.83 | 23.67 | 80.17 | 23.70 |
September | 245.33 | 22.08 | 40.83 | 22.29 | 16.67 | 22.32 |
October | 337.00 | 21.34 | 146.67 | 21.27 | 146.67 | 21.23 |
November | 330.00 | 21.12 | 311.83 | 21.11 | 311.83 | 21.11 |
December | 338.00 | 21.11 | 338.00 | 21.11 | 338.00 | 21.11 |
Annual Sum or Average | 3357.00 | 21.61 | 2776.33 | 21.68 | 2372.17 | 21.61 |
Minimum of Months | 113.00 | 21.11 | 40.83 | 21.11 | 16.67 | 21.11 |
Maximum of Months | 348.00 | 23.64 | 348.00 | 23.85 | 348.00 | 23.88 |
Report: OccupantComfortDataSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 496.00000 | 21.03988 | 10.39637 | -0.7839 | 18.27142 |
February | 448.00000 | 21.05098 | 12.73462 | -0.7221 | 16.32056 |
March | 497.00000 | 21.11560 | 16.92075 | -0.6543 | 14.38225 |
April | 479.00000 | 21.83717 | 21.36787 | -0.3796 | 9.72296 |
May | 496.00000 | 23.46793 | 32.87719 | -0.7878 | 20.15883 |
June | 481.00000 | 23.85184 | 47.70568 | -0.4895 | 10.57256 |
July | 495.00000 | 23.88650 | 53.88690 | -0.3728 | 8.08383 |
August | 497.00000 | 23.88111 | 52.66673 | -0.3933 | 8.45263 |
September | 479.00000 | 23.70619 | 40.32068 | -0.6024 | 13.49441 |
October | 496.00000 | 22.27559 | 30.50970 | -0.1537 | 7.46870 |
November | 480.00000 | 21.18835 | 20.53146 | -0.5620 | 12.15126 |
December | 496.00000 | 21.05830 | 11.82896 | -0.7587 | 17.35937 |
Annual Sum or Average | 5840.00000 | 22.37088 | 29.41406 | -0.5542 | 13.02693 |
Minimum of Months | 448.00000 | 21.03988 | 10.39637 | -0.7878 | 7.46870 |
Maximum of Months | 497.00000 | 23.88650 | 53.88690 | -0.1537 | 20.15883 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 496.00000 | 21.11739 | 10.97002 | -0.6863 | 15.09682 |
February | 448.00000 | 21.17633 | 13.16746 | -0.6162 | 13.25076 |
March | 497.00000 | 21.28402 | 17.00223 | -0.5431 | 11.60654 |
April | 479.00000 | 21.94511 | 21.37711 | -0.2992 | 8.22810 |
May | 496.00000 | 23.29844 | 32.83006 | -0.7889 | 20.34776 |
June | 481.00000 | 23.79136 | 47.02661 | -0.4798 | 10.42754 |
July | 495.00000 | 23.84926 | 52.85079 | -0.3748 | 8.12638 |
August | 497.00000 | 23.83603 | 51.89723 | -0.3964 | 8.53662 |
September | 479.00000 | 23.43293 | 40.45594 | -0.6583 | 15.76252 |
October | 496.00000 | 22.14101 | 31.05420 | -0.1519 | 7.02979 |
November | 480.00000 | 21.41628 | 20.72537 | -0.4607 | 9.99961 |
December | 496.00000 | 21.13106 | 12.25298 | -0.6660 | 14.50241 |
Annual Sum or Average | 5840.00000 | 22.37496 | 29.39973 | -0.5097 | 11.90711 |
Minimum of Months | 448.00000 | 21.11739 | 10.97002 | -0.7889 | 7.02979 |
Maximum of Months | 497.00000 | 23.84926 | 52.85079 | -0.1519 | 20.34776 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 21.11000 | 7.73477 | -0.7256 | 16.21689 |
February | 336.00000 | 21.10973 | 9.94193 | -0.6607 | 14.36042 |
March | 379.00000 | 21.10997 | 14.04233 | -0.6022 | 12.82695 |
April | 360.00000 | 21.49618 | 18.61460 | -0.4089 | 9.53823 |
May | 375.00000 | 22.97890 | 32.78696 | -0.8894 | 25.02216 |
June | 366.00000 | 23.78418 | 47.07438 | -0.4886 | 11.26035 |
July | 369.00000 | 23.98076 | 53.21473 | -0.3348 | 7.77800 |
August | 379.00000 | 23.90724 | 52.46113 | -0.3745 | 8.43624 |
September | 360.00000 | 23.05638 | 39.96527 | -0.7775 | 20.59932 |
October | 371.00000 | 21.53504 | 29.43366 | -0.2929 | 8.05955 |
November | 360.00000 | 21.13690 | 18.25927 | -0.5403 | 11.43910 |
December | 369.00000 | 21.10996 | 9.32702 | -0.7056 | 15.60976 |
Annual Sum or Average | 4395.00000 | 22.20352 | 27.89513 | -0.5661 | 13.42268 |
Minimum of Months | 336.00000 | 21.10973 | 7.73477 | -0.8894 | 7.77800 |
Maximum of Months | 379.00000 | 23.98076 | 53.21473 | -0.2929 | 25.02216 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 21.11000 | 7.73475 | -0.7353 | 16.51208 |
February | 336.00000 | 21.10983 | 9.94160 | -0.6706 | 14.63477 |
March | 379.00000 | 21.10982 | 14.04251 | -0.6114 | 13.06140 |
April | 360.00000 | 21.46260 | 18.65482 | -0.4262 | 9.76367 |
May | 375.00000 | 22.91685 | 32.90852 | -0.9186 | 26.27044 |
June | 366.00000 | 23.75219 | 47.17800 | -0.5043 | 11.78028 |
July | 369.00000 | 23.97774 | 53.24054 | -0.3367 | 7.81554 |
August | 379.00000 | 23.89947 | 52.51687 | -0.3787 | 8.53685 |
September | 360.00000 | 22.99266 | 40.13218 | -0.8056 | 21.72026 |
October | 371.00000 | 21.49650 | 29.51732 | -0.3126 | 8.25592 |
November | 360.00000 | 21.13296 | 18.26989 | -0.5522 | 11.70334 |
December | 369.00000 | 21.10992 | 9.32705 | -0.7148 | 15.88901 |
Annual Sum or Average | 4395.00000 | 22.18309 | 27.94600 | -0.5799 | 13.82238 |
Minimum of Months | 336.00000 | 21.10982 | 7.73475 | -0.9186 | 7.81554 |
Maximum of Months | 379.00000 | 23.97774 | 53.24054 | -0.3126 | 26.27044 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 21.10996 | 7.73500 | -0.7476 | 16.90334 |
February | 336.00000 | 21.10992 | 9.94206 | -0.6848 | 15.04503 |
March | 379.00000 | 21.10992 | 14.04266 | -0.6255 | 13.43603 |
April | 360.00000 | 21.41829 | 18.70642 | -0.4486 | 10.08808 |
May | 375.00000 | 22.82668 | 33.10831 | -0.9591 | 27.96261 |
June | 366.00000 | 23.69199 | 47.45401 | -0.5332 | 12.67579 |
July | 369.00000 | 23.96356 | 53.46782 | -0.3472 | 7.99283 |
August | 379.00000 | 23.87486 | 52.73593 | -0.3930 | 8.84211 |
September | 360.00000 | 22.90789 | 40.37710 | -0.8416 | 23.09489 |
October | 371.00000 | 21.46034 | 29.59828 | -0.3319 | 8.45970 |
November | 360.00000 | 21.12784 | 18.28401 | -0.5677 | 12.05766 |
December | 369.00000 | 21.11000 | 9.32709 | -0.7276 | 16.28073 |
Annual Sum or Average | 4395.00000 | 22.15304 | 28.05636 | -0.6000 | 14.39752 |
Minimum of Months | 336.00000 | 21.10992 | 7.73500 | -0.9591 | 7.99283 |
Maximum of Months | 379.00000 | 23.96356 | 53.46782 | -0.3319 | 27.96261 |
Report: OccupantComfortDataSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.11000 | 9.14447 | -0.7900 | 18.26493 |
February | 308.00000 | 21.11000 | 11.40017 | -0.7272 | 16.28662 |
March | 348.00000 | 21.11000 | 15.55737 | -0.6659 | 14.52191 |
April | 330.00000 | 21.36321 | 20.10436 | -0.4932 | 10.86294 |
May | 344.00000 | 22.70276 | 34.86931 | -1.0270 | 30.64271 |
June | 336.00000 | 23.56295 | 49.08712 | -0.5951 | 14.35900 |
July | 338.00000 | 23.88444 | 54.82088 | -0.3836 | 8.53100 |
August | 348.00000 | 23.78251 | 54.31609 | -0.4342 | 9.64219 |
September | 330.00000 | 22.79344 | 41.94818 | -0.8993 | 25.25282 |
October | 340.00000 | 21.41834 | 31.11603 | -0.3689 | 8.94583 |
November | 330.00000 | 21.12367 | 19.67066 | -0.6110 | 13.11013 |
December | 338.00000 | 21.11000 | 10.74895 | -0.7706 | 17.63023 |
Annual Sum or Average | 4030.00000 | 22.09966 | 29.56212 | -0.6465 | 15.66496 |
Minimum of Months | 308.00000 | 21.11000 | 9.14447 | -1.0270 | 8.53100 |
Maximum of Months | 348.00000 | 23.88444 | 54.82088 | -0.3689 | 30.64271 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.11000 | 9.04397 | -0.7786 | 17.88147 |
February | 308.00000 | 21.11000 | 11.30100 | -0.7202 | 16.06512 |
March | 348.00000 | 21.10985 | 15.45931 | -0.6624 | 14.40904 |
April | 330.00000 | 21.35294 | 20.01609 | -0.5003 | 10.96108 |
May | 344.00000 | 22.68255 | 34.82911 | -1.0493 | 31.53838 |
June | 336.00000 | 23.54708 | 49.10529 | -0.6183 | 14.99880 |
July | 338.00000 | 23.88248 | 54.88173 | -0.4035 | 8.85305 |
August | 348.00000 | 23.78214 | 54.37761 | -0.4525 | 9.97841 |
September | 330.00000 | 22.78779 | 41.88972 | -0.9181 | 25.91913 |
October | 340.00000 | 21.41692 | 31.02151 | -0.3757 | 9.02299 |
November | 330.00000 | 21.12278 | 19.57333 | -0.6096 | 13.05919 |
December | 338.00000 | 21.11000 | 10.64720 | -0.7601 | 17.28453 |
Annual Sum or Average | 4030.00000 | 22.09491 | 29.50960 | -0.6535 | 15.82772 |
Minimum of Months | 308.00000 | 21.10985 | 9.04397 | -1.0493 | 8.85305 |
Maximum of Months | 348.00000 | 23.88248 | 54.88173 | -0.3757 | 31.53838 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.11000 | 9.04399 | -0.7804 | 17.93982 |
February | 308.00000 | 21.10993 | 11.30110 | -0.7230 | 16.14942 |
March | 348.00000 | 21.10990 | 15.45929 | -0.6662 | 14.51277 |
April | 330.00000 | 21.33908 | 20.03055 | -0.5092 | 11.11512 |
May | 344.00000 | 22.64612 | 34.91484 | -1.0690 | 32.39600 |
June | 336.00000 | 23.51435 | 49.24730 | -0.6357 | 15.60038 |
July | 338.00000 | 23.87776 | 54.95767 | -0.4092 | 8.97226 |
August | 348.00000 | 23.77197 | 54.46374 | -0.4599 | 10.16788 |
September | 330.00000 | 22.75836 | 41.98696 | -0.9329 | 26.49966 |
October | 340.00000 | 21.40907 | 31.04163 | -0.3821 | 9.10420 |
November | 330.00000 | 21.12217 | 19.57513 | -0.6139 | 13.16517 |
December | 338.00000 | 21.11000 | 10.64720 | -0.7620 | 17.34724 |
Annual Sum or Average | 4030.00000 | 22.08354 | 29.55357 | -0.6614 | 16.07870 |
Minimum of Months | 308.00000 | 21.10990 | 9.04399 | -1.0690 | 8.97226 |
Maximum of Months | 348.00000 | 23.87776 | 54.95767 | -0.3821 | 32.39600 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.11000 | 9.04387 | -0.7919 | 18.32151 |
February | 308.00000 | 21.11000 | 11.30030 | -0.7371 | 16.58640 |
March | 348.00000 | 21.10987 | 15.45907 | -0.6833 | 14.99730 |
April | 330.00000 | 21.30073 | 20.07046 | -0.5364 | 11.64571 |
May | 344.00000 | 22.54899 | 35.16422 | -1.1198 | 34.64927 |
June | 336.00000 | 23.42863 | 49.65436 | -0.6770 | 17.10741 |
July | 338.00000 | 23.86135 | 55.22770 | -0.4216 | 9.27552 |
August | 348.00000 | 23.73883 | 54.74949 | -0.4775 | 10.67650 |
September | 330.00000 | 22.68069 | 42.24668 | -0.9689 | 27.94492 |
October | 340.00000 | 21.38858 | 31.09163 | -0.3996 | 9.36164 |
November | 330.00000 | 21.11950 | 19.58155 | -0.6297 | 13.57649 |
December | 338.00000 | 21.11000 | 10.64694 | -0.7741 | 17.73880 |
Annual Sum or Average | 4030.00000 | 22.05242 | 29.68528 | -0.6842 | 16.82352 |
Minimum of Months | 308.00000 | 21.10987 | 9.04387 | -1.1198 | 9.27552 |
Maximum of Months | 348.00000 | 23.86135 | 55.22770 | -0.3996 | 34.64927 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.11000 | 8.90531 | -0.8712 | 21.13603 |
February | 308.00000 | 21.11000 | 11.12226 | -0.8156 | 19.19897 |
March | 348.00000 | 21.11000 | 15.28967 | -0.7674 | 17.60480 |
April | 330.00000 | 21.23389 | 19.98370 | -0.6234 | 13.71152 |
May | 344.00000 | 22.36581 | 35.39939 | -1.2427 | 40.23440 |
June | 336.00000 | 23.27136 | 50.18533 | -0.7647 | 20.40778 |
July | 338.00000 | 23.81718 | 55.54099 | -0.4494 | 10.13030 |
August | 348.00000 | 23.65030 | 55.20357 | -0.5200 | 12.07398 |
September | 330.00000 | 22.54368 | 42.48306 | -1.0446 | 31.25708 |
October | 340.00000 | 21.36360 | 30.97682 | -0.4527 | 10.38221 |
November | 330.00000 | 21.11518 | 19.48308 | -0.6948 | 15.44119 |
December | 338.00000 | 21.11000 | 10.50086 | -0.8497 | 20.36324 |
Annual Sum or Average | 4030.00000 | 21.99317 | 29.75744 | -0.7575 | 19.32938 |
Minimum of Months | 308.00000 | 21.11000 | 8.90531 | -1.2427 | 10.13030 |
Maximum of Months | 348.00000 | 23.81718 | 55.54099 | -0.4494 | 40.23440 |
Report: DXReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 |
April | 0.188334E+09 | 51748586.97 | 39.67 | 0.161920E+09 | 26413532.28 | 0.00 | 0.53 | 23-APR-16:10 | 0.00 | 01-APR-00:10 | 9145.00 | 23-APR-16:10 | 7911.83 | 23-APR-16:03 | 1277.06 | 23-APR-17:00 | 2501.55 | 23-APR-16:10 | 0.00 | 01-APR-00:10 |
May | 0.293302E+10 | 0.791109E+09 | 242.79 | 0.252872E+10 | 0.404300E+09 | 0.00 | 0.78 | 25-MAY-16:10 | 0.00 | 01-MAY-00:05 | 14568.63 | 25-MAY-16:10 | 11684.47 | 25-MAY-16:10 | 3910.44 | 26-MAY-12:50 | 3840.04 | 25-MAY-16:10 | 0.00 | 01-MAY-00:05 |
June | 0.780273E+10 | 0.202616E+10 | 343.07 | 0.572470E+10 | 0.207803E+10 | 0.00 | 1.00 | 25-JUN-07:03 | 0.00 | 01-JUN-00:10 | 44056.55 | 30-JUN-07:02 | 25915.16 | 29-JUN-07:03 | 18393.53 | 30-JUN-07:02 | 9747.91 | 30-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.130017E+11 | 0.329658E+10 | 425.14 | 0.895513E+10 | 0.404656E+10 | 0.00 | 1.00 | 04-JUL-07:03 | 0.00 | 01-JUL-00:05 | 44401.23 | 23-JUL-07:02 | 24063.16 | 04-JUL-07:03 | 24143.46 | 23-JUL-07:02 | 9415.22 | 23-JUL-07:02 | 0.00 | 01-JUL-00:05 |
August | 0.934146E+10 | 0.235926E+10 | 370.59 | 0.649866E+10 | 0.284280E+10 | 0.00 | 1.00 | 08-AUG-16:10 | 0.00 | 01-AUG-00:10 | 34214.02 | 09-AUG-07:03 | 17886.95 | 09-AUG-07:03 | 16327.07 | 09-AUG-07:03 | 7344.09 | 09-AUG-07:03 | 0.00 | 01-AUG-00:10 |
September | 0.141323E+10 | 0.369482E+09 | 235.31 | 0.113731E+10 | 0.275921E+09 | 0.00 | 0.80 | 01-SEP-13:00 | 0.00 | 01-SEP-00:05 | 15389.33 | 01-SEP-13:00 | 12504.97 | 01-SEP-16:10 | 4140.60 | 01-SEP-11:50 | 3748.55 | 01-SEP-14:00 | 0.00 | 01-SEP-00:05 |
October | 0.109292E+09 | 30308618.13 | 75.58 | 0.101243E+09 | 8048270.08 | 0.00 | 0.27 | 19-OCT-15:00 | 0.00 | 01-OCT-00:10 | 4155.84 | 19-OCT-15:00 | 3950.12 | 19-OCT-15:00 | 409.98 | 22-OCT-14:00 | 1140.89 | 19-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.347897E+11 | 0.892465E+10 | 1732.15 | 0.251077E+11 | 0.968207E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.130017E+11 | 0.329658E+10 | 425.14 | 0.895513E+10 | 0.404656E+10 | 0.00 | 1.00 | 0.00 | 44401.23 | 25915.16 | 24143.46 | 9747.91 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 |
April | 0.132705E+09 | 33925922.03 | 10.78 | 0.116719E+09 | 15985269.90 | 0.00 | 1.00 | 23-APR-18:41 | 0.00 | 01-APR-00:10 | 20400.44 | 23-APR-18:41 | 18617.94 | 23-APR-18:49 | 3012.61 | 23-APR-20:27 | 4519.35 | 23-APR-18:41 | 0.00 | 01-APR-00:10 |
May | 0.218707E+10 | 0.550712E+09 | 157.64 | 0.191593E+10 | 0.271139E+09 | 0.00 | 1.00 | 10-MAY-20:01 | 0.00 | 01-MAY-00:05 | 21000.44 | 25-MAY-20:32 | 19512.52 | 10-MAY-20:09 | 6304.15 | 25-MAY-23:23 | 4612.60 | 25-MAY-20:32 | 0.00 | 01-MAY-00:05 |
June | 0.559786E+10 | 0.135985E+10 | 289.73 | 0.406357E+10 | 0.153429E+10 | 0.00 | 1.00 | 04-JUN-17:01 | 0.00 | 01-JUN-00:10 | 22505.74 | 27-JUN-20:03 | 19771.19 | 17-JUN-18:08 | 12347.77 | 19-JUN-20:13 | 4896.21 | 30-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.899163E+10 | 0.213275E+10 | 385.97 | 0.610521E+10 | 0.288642E+10 | 0.00 | 1.00 | 01-JUL-18:02 | 0.00 | 01-JUL-00:05 | 22663.88 | 23-JUL-07:02 | 17213.14 | 02-JUL-17:03 | 12486.69 | 25-JUL-20:03 | 4797.55 | 22-JUL-20:05 | 0.00 | 01-JUL-00:05 |
August | 0.640347E+10 | 0.152331E+10 | 337.05 | 0.440588E+10 | 0.199759E+10 | 0.00 | 1.00 | 03-AUG-20:03 | 0.00 | 01-AUG-00:10 | 22464.40 | 31-AUG-20:03 | 18593.17 | 05-AUG-18:02 | 10806.95 | 31-AUG-20:03 | 4767.13 | 31-AUG-20:03 | 0.00 | 01-AUG-00:10 |
September | 0.104640E+10 | 0.259542E+09 | 116.88 | 0.839836E+09 | 0.206561E+09 | 0.00 | 1.00 | 01-SEP-20:03 | 0.00 | 01-SEP-00:05 | 21545.01 | 17-SEP-17:03 | 17056.84 | 24-SEP-17:01 | 9271.83 | 01-SEP-20:10 | 4558.48 | 17-SEP-17:03 | 0.00 | 01-SEP-00:05 |
October | 84564521.67 | 22777334.85 | 20.86 | 78969604.58 | 5594917.09 | 0.00 | 0.37 | 20-OCT-20:10 | 0.00 | 01-OCT-00:10 | 3001.48 | 20-OCT-20:10 | 3001.48 | 20-OCT-20:10 | 300.74 | 22-OCT-13:00 | 769.24 | 20-OCT-20:10 | 0.00 | 01-OCT-00:10 |
November | 217265.59 | 61054.02 | 0.17 | 171864.34 | 45401.25 | 0.00 | 0.05 | 01-NOV-20:40 | 0.00 | 01-NOV-00:05 | 362.11 | 01-NOV-20:40 | 286.44 | 01-NOV-20:40 | 75.67 | 01-NOV-20:40 | 101.76 | 01-NOV-20:40 | 0.00 | 01-NOV-00:05 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.244439E+11 | 0.588293E+10 | 1319.08 | 0.175263E+11 | 0.691763E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.899163E+10 | 0.213275E+10 | 385.97 | 0.610521E+10 | 0.288642E+10 | 0.00 | 1.00 | 0.00 | 22663.88 | 19771.19 | 12486.69 | 4896.21 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_3:3 COOLING COIL
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 |
April | 41683719.02 | 11299259.52 | 3.83 | 36697061.92 | 4986657.10 | 0.00 | 0.48 | 23-APR-16:00 | 0.00 | 01-APR-00:10 | 4223.21 | 23-APR-16:00 | 3802.88 | 23-APR-16:00 | 447.95 | 23-APR-14:50 | 1152.45 | 23-APR-16:00 | 0.00 | 01-APR-00:10 |
May | 0.153188E+10 | 0.398485E+09 | 124.81 | 0.133867E+10 | 0.193212E+09 | 0.00 | 0.89 | 26-MAY-06:03 | 0.00 | 01-MAY-00:05 | 9001.90 | 26-MAY-06:03 | 7286.48 | 25-MAY-16:10 | 2960.21 | 26-MAY-06:03 | 2219.24 | 25-MAY-16:10 | 0.00 | 01-MAY-00:05 |
June | 0.404062E+10 | 0.100218E+10 | 231.90 | 0.298817E+10 | 0.105245E+10 | 0.00 | 1.00 | 25-JUN-07:03 | 0.00 | 01-JUN-00:10 | 23071.65 | 30-JUN-06:02 | 13028.74 | 29-JUN-06:03 | 10838.87 | 25-JUN-07:03 | 4986.63 | 30-JUN-06:02 | 0.00 | 01-JUN-00:10 |
July | 0.630617E+10 | 0.152885E+10 | 311.31 | 0.440057E+10 | 0.190560E+10 | 0.00 | 1.00 | 03-JUL-06:03 | 0.00 | 01-JUL-00:05 | 22963.94 | 23-JUL-07:02 | 12031.99 | 04-JUL-07:03 | 12335.68 | 23-JUL-07:02 | 4780.17 | 23-JUL-07:02 | 0.00 | 01-JUL-00:05 |
August | 0.454280E+10 | 0.110571E+10 | 280.62 | 0.317276E+10 | 0.137004E+10 | 0.00 | 1.00 | 08-AUG-12:10 | 0.00 | 01-AUG-00:10 | 21891.61 | 09-AUG-06:03 | 11278.13 | 09-AUG-06:03 | 10613.48 | 09-AUG-06:03 | 4617.08 | 09-AUG-06:03 | 0.00 | 01-AUG-00:10 |
September | 0.660138E+09 | 0.167997E+09 | 87.94 | 0.542444E+09 | 0.117694E+09 | 0.00 | 1.00 | 01-SEP-06:03 | 0.00 | 01-SEP-00:05 | 12190.62 | 01-SEP-06:03 | 6928.60 | 01-SEP-16:10 | 6381.80 | 01-SEP-06:03 | 2591.00 | 01-SEP-06:03 | 0.00 | 01-SEP-00:05 |
October | 42418294.83 | 11595632.45 | 12.50 | 39868849.26 | 2549445.58 | 0.00 | 0.24 | 19-OCT-15:00 | 0.00 | 01-OCT-00:10 | 1919.63 | 19-OCT-15:00 | 1847.86 | 19-OCT-15:00 | 175.45 | 22-OCT-13:50 | 521.44 | 19-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.171657E+11 | 0.422612E+10 | 1052.92 | 0.125192E+11 | 0.464653E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.630617E+10 | 0.152885E+10 | 311.31 | 0.440057E+10 | 0.190560E+10 | 0.00 | 1.00 | 0.00 | 23071.65 | 13028.74 | 12335.68 | 4986.63 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_4:4 COOLING COIL
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 |
April | 37572599.15 | 10271063.51 | 3.67 | 33076267.64 | 4496331.51 | 0.00 | 0.45 | 23-APR-16:00 | 0.00 | 01-APR-00:10 | 3960.72 | 23-APR-16:00 | 3562.12 | 23-APR-16:00 | 420.73 | 23-APR-15:00 | 1089.25 | 23-APR-16:00 | 0.00 | 01-APR-00:10 |
May | 0.147949E+10 | 0.385866E+09 | 119.47 | 0.129070E+10 | 0.188789E+09 | 0.00 | 0.88 | 25-MAY-16:10 | 0.00 | 01-MAY-00:05 | 8867.57 | 25-MAY-16:10 | 7232.04 | 25-MAY-16:10 | 2893.12 | 26-MAY-06:03 | 2208.29 | 25-MAY-16:10 | 0.00 | 01-MAY-00:05 |
June | 0.397836E+10 | 0.987370E+09 | 227.73 | 0.293452E+10 | 0.104384E+10 | 0.00 | 1.00 | 25-JUN-07:03 | 0.00 | 01-JUN-00:10 | 23140.90 | 30-JUN-06:02 | 13069.15 | 29-JUN-06:03 | 10869.96 | 25-JUN-07:03 | 5000.70 | 30-JUN-06:02 | 0.00 | 01-JUN-00:10 |
July | 0.628526E+10 | 0.152484E+10 | 311.48 | 0.438463E+10 | 0.190063E+10 | 0.00 | 1.00 | 03-JUL-06:03 | 0.00 | 01-JUL-00:05 | 23029.22 | 23-JUL-07:02 | 12068.71 | 04-JUL-07:03 | 12365.44 | 23-JUL-07:02 | 4793.65 | 23-JUL-07:02 | 0.00 | 01-JUL-00:05 |
August | 0.449886E+10 | 0.109625E+10 | 279.46 | 0.314105E+10 | 0.135781E+10 | 0.00 | 1.00 | 08-AUG-12:10 | 0.00 | 01-AUG-00:10 | 21953.70 | 09-AUG-06:03 | 11311.40 | 09-AUG-06:03 | 10642.29 | 09-AUG-06:03 | 4630.14 | 09-AUG-06:03 | 0.00 | 01-AUG-00:10 |
September | 0.626981E+09 | 0.159382E+09 | 80.61 | 0.514723E+09 | 0.112258E+09 | 0.00 | 1.00 | 01-SEP-06:03 | 0.00 | 01-SEP-00:05 | 12191.01 | 01-SEP-06:03 | 6915.97 | 01-SEP-16:10 | 6383.37 | 01-SEP-06:03 | 2591.09 | 01-SEP-06:03 | 0.00 | 01-SEP-00:05 |
October | 33290103.85 | 9154585.37 | 11.00 | 31387044.40 | 1903059.45 | 0.00 | 0.22 | 19-OCT-15:00 | 0.00 | 01-OCT-00:10 | 1720.10 | 19-OCT-15:00 | 1655.99 | 19-OCT-15:00 | 143.02 | 22-OCT-14:00 | 470.25 | 19-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.169398E+11 | 0.417313E+10 | 1033.42 | 0.123301E+11 | 0.460973E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.628526E+10 | 0.152484E+10 | 311.48 | 0.438463E+10 | 0.190063E+10 | 0.00 | 1.00 | 0.00 | 23140.90 | 13069.15 | 12365.44 | 5000.70 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_5:5 COOLING COIL
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 |
April | 33003827.08 | 9103702.66 | 3.67 | 29024353.36 | 3979473.72 | 0.00 | 0.42 | 23-APR-16:00 | 0.00 | 01-APR-00:10 | 3639.55 | 23-APR-16:00 | 3266.31 | 23-APR-16:00 | 389.16 | 23-APR-15:00 | 1009.26 | 23-APR-16:00 | 0.00 | 01-APR-00:10 |
May | 0.137274E+10 | 0.359810E+09 | 113.14 | 0.119544E+10 | 0.177306E+09 | 0.00 | 0.86 | 25-MAY-16:10 | 0.00 | 01-MAY-00:05 | 8647.80 | 25-MAY-16:10 | 7038.53 | 25-MAY-16:10 | 2130.97 | 26-MAY-12:10 | 2161.13 | 25-MAY-16:10 | 0.00 | 01-MAY-00:05 |
June | 0.378291E+10 | 0.940569E+09 | 220.98 | 0.277609E+10 | 0.100682E+10 | 0.00 | 1.00 | 25-JUN-07:03 | 0.00 | 01-JUN-00:10 | 22939.16 | 30-JUN-06:02 | 12918.02 | 29-JUN-06:03 | 10824.35 | 25-JUN-07:03 | 4960.39 | 30-JUN-06:02 | 0.00 | 01-JUN-00:10 |
July | 0.605670E+10 | 0.147259E+10 | 307.26 | 0.421665E+10 | 0.184005E+10 | 0.00 | 1.00 | 03-JUL-16:10 | 0.00 | 01-JUL-00:05 | 22841.66 | 23-JUL-07:02 | 11923.97 | 04-JUL-07:03 | 12300.30 | 23-JUL-07:02 | 4755.02 | 23-JUL-07:02 | 0.00 | 01-JUL-00:05 |
August | 0.429691E+10 | 0.104989E+10 | 271.87 | 0.299684E+10 | 0.130007E+10 | 0.00 | 1.00 | 08-AUG-12:10 | 0.00 | 01-AUG-00:10 | 21774.87 | 09-AUG-06:03 | 11182.74 | 09-AUG-06:03 | 10592.13 | 09-AUG-06:03 | 4592.61 | 09-AUG-06:03 | 0.00 | 01-AUG-00:10 |
September | 0.569918E+09 | 0.144862E+09 | 73.94 | 0.466752E+09 | 0.103166E+09 | 0.00 | 0.98 | 01-SEP-06:03 | 0.00 | 01-SEP-00:05 | 10263.95 | 01-SEP-06:03 | 6773.30 | 01-SEP-16:10 | 5419.42 | 01-SEP-06:03 | 2198.66 | 01-SEP-06:03 | 0.00 | 01-SEP-00:05 |
October | 22662029.05 | 6277714.61 | 9.67 | 21436343.00 | 1225686.05 | 0.00 | 0.19 | 19-OCT-15:00 | 0.00 | 01-OCT-00:10 | 1446.56 | 19-OCT-15:00 | 1391.36 | 19-OCT-15:00 | 103.05 | 22-OCT-14:00 | 398.76 | 19-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.161348E+11 | 0.398311E+10 | 1000.54 | 0.117022E+11 | 0.443261E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.605670E+10 | 0.147259E+10 | 307.26 | 0.421665E+10 | 0.184005E+10 | 0.00 | 1.00 | 0.00 | 22939.16 | 12918.02 | 12300.30 | 4960.39 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_6:6 COOLING COIL
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 |
April | 55072724.17 | 15228566.18 | 3.33 | 47062975.16 | 8009749.01 | 0.00 | 0.41 | 23-APR-15:00 | 0.00 | 01-APR-00:10 | 6512.83 | 23-APR-15:00 | 5555.06 | 23-APR-15:00 | 957.77 | 23-APR-15:00 | 1775.08 | 23-APR-15:00 | 0.00 | 01-APR-00:10 |
May | 0.229697E+10 | 0.605710E+09 | 106.31 | 0.195561E+10 | 0.341366E+09 | 0.00 | 0.87 | 25-MAY-15:00 | 0.00 | 01-MAY-00:05 | 16041.21 | 25-MAY-15:00 | 12478.38 | 25-MAY-15:00 | 4154.46 | 26-MAY-12:10 | 3969.86 | 25-MAY-15:00 | 0.00 | 01-MAY-00:05 |
June | 0.652628E+10 | 0.162442E+10 | 209.16 | 0.466100E+10 | 0.186528E+10 | 0.00 | 1.00 | 24-JUN-14:10 | 0.00 | 01-JUN-00:10 | 41551.81 | 30-JUN-07:02 | 24653.20 | 29-JUN-07:03 | 17745.95 | 30-JUN-07:02 | 9010.21 | 30-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.105960E+11 | 0.257743E+10 | 296.06 | 0.719991E+10 | 0.339608E+10 | 0.00 | 1.00 | 03-JUL-15:00 | 0.00 | 01-JUL-00:05 | 41851.67 | 23-JUL-08:62 | 26389.20 | 30-JUL-08:62 | 21274.54 | 22-JUL-07:03 | 8818.07 | 30-JUL-08:62 | 0.00 | 01-JUL-00:05 |
August | 0.744463E+10 | 0.182316E+10 | 258.56 | 0.506781E+10 | 0.237682E+10 | 0.00 | 1.00 | 08-AUG-12:10 | 0.00 | 01-AUG-00:10 | 35326.70 | 09-AUG-07:03 | 18623.27 | 09-AUG-07:03 | 16703.43 | 09-AUG-07:03 | 7450.19 | 09-AUG-07:03 | 0.00 | 01-AUG-00:10 |
September | 0.928857E+09 | 0.236010E+09 | 62.11 | 0.746307E+09 | 0.182550E+09 | 0.00 | 0.86 | 01-SEP-14:40 | 0.00 | 01-SEP-00:05 | 15719.38 | 01-SEP-14:10 | 12521.55 | 01-SEP-15:00 | 5931.37 | 01-SEP-07:03 | 3742.72 | 01-SEP-15:00 | 0.00 | 01-SEP-00:05 |
October | 30964241.64 | 8601220.95 | 7.50 | 29087916.45 | 1876325.19 | 0.00 | 0.19 | 19-OCT-15:00 | 0.00 | 01-OCT-00:10 | 2662.39 | 19-OCT-15:00 | 2502.83 | 19-OCT-15:00 | 173.32 | 19-OCT-14:30 | 733.83 | 19-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.278788E+11 | 0.689056E+10 | 943.02 | 0.197068E+11 | 0.817198E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.105960E+11 | 0.257743E+10 | 296.06 | 0.719991E+10 | 0.339608E+10 | 0.00 | 1.00 | 0.00 | 41851.67 | 26389.20 | 21274.54 | 9010.21 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_7:7 COOLING COIL
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 |
April | 26403008.03 | 7351174.05 | 3.17 | 22610974.72 | 3792033.31 | 0.00 | 0.39 | 23-APR-15:00 | 0.00 | 01-APR-00:10 | 3242.23 | 23-APR-15:00 | 2768.63 | 23-APR-15:00 | 473.60 | 23-APR-15:00 | 890.30 | 23-APR-15:00 | 0.00 | 01-APR-00:10 |
May | 0.114913E+10 | 0.304876E+09 | 103.14 | 0.980277E+09 | 0.168853E+09 | 0.00 | 0.84 | 25-MAY-15:00 | 0.00 | 01-MAY-00:05 | 8273.60 | 25-MAY-15:00 | 6439.93 | 25-MAY-15:00 | 2112.87 | 26-MAY-12:10 | 2065.80 | 25-MAY-15:00 | 0.00 | 01-MAY-00:05 |
June | 0.330227E+10 | 0.826645E+09 | 202.45 | 0.235889E+10 | 0.943380E+09 | 0.00 | 1.00 | 25-JUN-08:63 | 0.00 | 01-JUN-00:10 | 22283.95 | 30-JUN-07:02 | 13269.56 | 29-JUN-07:03 | 9509.14 | 30-JUN-07:02 | 4834.02 | 30-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.539121E+10 | 0.131958E+10 | 292.93 | 0.367476E+10 | 0.171645E+10 | 0.00 | 1.00 | 04-JUL-08:62 | 0.00 | 01-JUL-00:05 | 22458.52 | 23-JUL-08:62 | 14155.00 | 30-JUL-08:62 | 11318.41 | 23-JUL-08:62 | 4731.38 | 30-JUL-08:62 | 0.00 | 01-JUL-00:05 |
August | 0.375828E+10 | 0.925882E+09 | 251.92 | 0.256870E+10 | 0.118958E+10 | 0.00 | 1.00 | 08-AUG-12:20 | 0.00 | 01-AUG-00:10 | 16312.73 | 09-AUG-07:03 | 8572.96 | 09-AUG-07:03 | 7739.78 | 09-AUG-07:03 | 3441.57 | 09-AUG-07:03 | 0.00 | 01-AUG-00:10 |
September | 0.451445E+09 | 0.114989E+09 | 57.81 | 0.362891E+09 | 88554534.81 | 0.00 | 0.83 | 01-SEP-14:50 | 0.00 | 01-SEP-00:05 | 8142.60 | 01-SEP-14:20 | 6511.41 | 01-SEP-15:00 | 2114.54 | 01-SEP-11:50 | 1955.58 | 01-SEP-15:00 | 0.00 | 01-SEP-00:05 |
October | 12486725.61 | 3483876.83 | 6.50 | 11779857.83 | 706867.78 | 0.00 | 0.17 | 19-OCT-15:00 | 0.00 | 01-OCT-00:10 | 1279.32 | 19-OCT-15:00 | 1207.36 | 19-OCT-15:00 | 76.12 | 19-OCT-14:30 | 354.34 | 19-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.140912E+11 | 0.350281E+10 | 917.91 | 0.997991E+10 | 0.411132E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.539121E+10 | 0.131958E+10 | 292.93 | 0.367476E+10 | 0.171645E+10 | 0.00 | 1.00 | 0.00 | 22458.52 | 14155.00 | 11318.41 | 4834.02 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_8:8 COOLING COIL
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 |
April | 24791614.17 | 6926592.83 | 3.00 | 21175849.48 | 3615764.69 | 0.00 | 0.37 | 23-APR-15:00 | 0.00 | 01-APR-00:10 | 3115.28 | 23-APR-15:00 | 2652.53 | 23-APR-15:00 | 462.75 | 23-APR-15:00 | 858.74 | 23-APR-15:00 | 0.00 | 01-APR-00:10 |
May | 0.110598E+10 | 0.294263E+09 | 101.22 | 0.941286E+09 | 0.164698E+09 | 0.00 | 0.83 | 25-MAY-15:00 | 0.00 | 01-MAY-00:05 | 8152.94 | 25-MAY-15:00 | 6327.86 | 25-MAY-15:00 | 2088.57 | 26-MAY-12:10 | 2042.23 | 25-MAY-15:00 | 0.00 | 01-MAY-00:05 |
June | 0.322409E+10 | 0.808093E+09 | 198.03 | 0.229374E+10 | 0.930348E+09 | 0.00 | 1.00 | 25-JUN-08:63 | 0.00 | 01-JUN-00:10 | 22301.84 | 30-JUN-07:02 | 13247.19 | 29-JUN-07:03 | 9583.86 | 30-JUN-07:02 | 4838.83 | 30-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.530848E+10 | 0.130105E+10 | 292.29 | 0.360975E+10 | 0.169873E+10 | 0.00 | 1.00 | 04-JUL-08:62 | 0.00 | 01-JUL-00:05 | 22480.29 | 23-JUL-08:62 | 13871.95 | 30-JUL-08:62 | 11354.20 | 23-JUL-08:62 | 4726.04 | 23-JUL-08:62 | 0.00 | 01-JUL-00:05 |
August | 0.368503E+10 | 0.909080E+09 | 248.06 | 0.251415E+10 | 0.117088E+10 | 0.00 | 1.00 | 08-AUG-12:20 | 0.00 | 01-AUG-00:10 | 15275.53 | 09-AUG-07:03 | 8188.72 | 08-AUG-15:00 | 7285.59 | 09-AUG-07:03 | 3223.40 | 09-AUG-07:03 | 0.00 | 01-AUG-00:10 |
September | 0.434376E+09 | 0.110659E+09 | 55.81 | 0.347789E+09 | 86586259.62 | 0.00 | 0.83 | 01-SEP-14:40 | 0.00 | 01-SEP-00:05 | 8089.94 | 01-SEP-14:20 | 6455.18 | 01-SEP-15:00 | 2102.92 | 01-SEP-11:50 | 1945.86 | 01-SEP-15:00 | 0.00 | 01-SEP-00:05 |
October | 10461118.22 | 2925219.53 | 6.33 | 9859682.55 | 601435.67 | 0.00 | 0.16 | 19-OCT-15:00 | 0.00 | 01-OCT-00:10 | 1207.11 | 19-OCT-15:00 | 1136.60 | 19-OCT-15:00 | 73.42 | 19-OCT-14:40 | 335.14 | 19-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.137932E+11 | 0.343300E+10 | 904.74 | 0.973775E+10 | 0.405546E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.530848E+10 | 0.130105E+10 | 292.29 | 0.360975E+10 | 0.169873E+10 | 0.00 | 1.00 | 0.00 | 22480.29 | 13871.95 | 11354.20 | 4838.83 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_9:9 COOLING COIL
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 |
April | 20288339.38 | 5736217.85 | 2.83 | 17275824.76 | 3012514.62 | 0.00 | 0.33 | 23-APR-15:00 | 0.00 | 01-APR-00:10 | 2736.57 | 23-APR-15:00 | 2321.12 | 23-APR-15:00 | 415.46 | 23-APR-15:00 | 763.83 | 23-APR-15:00 | 0.00 | 01-APR-00:10 |
May | 0.994339E+09 | 0.266863E+09 | 94.50 | 0.844161E+09 | 0.150178E+09 | 0.00 | 0.79 | 25-MAY-15:00 | 0.00 | 01-MAY-00:05 | 7827.00 | 25-MAY-15:00 | 6047.18 | 25-MAY-15:00 | 1998.43 | 26-MAY-12:10 | 1982.69 | 25-MAY-15:00 | 0.00 | 01-MAY-00:05 |
June | 0.302144E+10 | 0.761225E+09 | 190.84 | 0.213623E+10 | 0.885211E+09 | 0.00 | 1.00 | 25-JUN-08:63 | 0.00 | 01-JUN-00:10 | 22630.62 | 30-JUN-07:02 | 12736.79 | 30-JUN-07:02 | 9893.83 | 30-JUN-07:02 | 4913.10 | 30-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.509039E+10 | 0.125401E+10 | 283.69 | 0.345264E+10 | 0.163775E+10 | 0.00 | 1.00 | 04-JUL-08:62 | 0.00 | 01-JUL-00:05 | 22822.99 | 23-JUL-08:62 | 11330.02 | 24-JUL-07:03 | 11571.50 | 23-JUL-08:62 | 4798.89 | 23-JUL-08:62 | 0.00 | 01-JUL-00:05 |
August | 0.349198E+10 | 0.865525E+09 | 237.53 | 0.238085E+10 | 0.111113E+10 | 0.00 | 1.00 | 08-AUG-12:40 | 0.00 | 01-AUG-00:10 | 12448.72 | 08-AUG-15:00 | 8043.93 | 08-AUG-15:00 | 5871.90 | 09-AUG-07:03 | 2939.40 | 08-AUG-15:00 | 0.00 | 01-AUG-00:10 |
September | 0.391767E+09 | 99917170.69 | 48.67 | 0.311525E+09 | 80241765.83 | 0.00 | 0.81 | 01-SEP-14:50 | 0.00 | 01-SEP-00:05 | 7985.68 | 01-SEP-14:20 | 6362.20 | 01-SEP-15:00 | 2066.95 | 01-SEP-11:50 | 1932.59 | 01-SEP-15:00 | 0.00 | 01-SEP-00:05 |
October | 5972325.97 | 1679438.88 | 4.00 | 5604195.55 | 368130.42 | 0.00 | 0.13 | 19-OCT-15:00 | 0.00 | 01-OCT-00:10 | 1019.83 | 19-OCT-15:00 | 959.13 | 19-OCT-15:00 | 61.56 | 19-OCT-14:50 | 285.03 | 19-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.130162E+11 | 0.325496E+10 | 862.06 | 0.914829E+10 | 0.386789E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.509039E+10 | 0.125401E+10 | 283.69 | 0.345264E+10 | 0.163775E+10 | 0.00 | 1.00 | 0.00 | 22822.99 | 12736.79 | 11571.50 | 4913.10 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_10:10 COOLING COIL
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 |
April | 10484448.38 | 3069770.42 | 2.17 | 8859731.80 | 1624716.58 | 0.00 | 0.19 | 23-APR-16:00 | 0.00 | 01-APR-00:10 | 1813.36 | 23-APR-16:00 | 1550.11 | 23-APR-16:00 | 280.42 | 23-APR-15:00 | 534.82 | 23-APR-16:00 | 0.00 | 01-APR-00:10 |
May | 0.845457E+09 | 0.232755E+09 | 77.08 | 0.714172E+09 | 0.131284E+09 | 0.00 | 0.66 | 25-MAY-15:00 | 0.00 | 01-MAY-00:05 | 7459.65 | 25-MAY-15:00 | 5884.18 | 18-MAY-15:00 | 1864.81 | 26-MAY-12:10 | 1969.19 | 25-MAY-15:00 | 0.00 | 01-MAY-00:05 |
June | 0.281142E+10 | 0.724249E+09 | 172.76 | 0.197537E+10 | 0.836052E+09 | 0.00 | 1.00 | 29-JUN-12:30 | 0.00 | 01-JUN-00:10 | 25875.47 | 30-JUN-07:02 | 12319.73 | 30-JUN-07:02 | 13555.74 | 30-JUN-07:02 | 5528.70 | 30-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.494568E+10 | 0.124882E+10 | 254.85 | 0.336508E+10 | 0.158060E+10 | 0.00 | 1.00 | 15-JUL-13:50 | 0.00 | 01-JUL-00:05 | 23909.41 | 23-JUL-08:62 | 11590.71 | 23-JUL-08:62 | 12318.71 | 23-JUL-08:62 | 5026.64 | 23-JUL-08:62 | 0.00 | 01-JUL-00:05 |
August | 0.329527E+10 | 0.833972E+09 | 206.29 | 0.226559E+10 | 0.102968E+10 | 0.00 | 0.99 | 08-AUG-15:00 | 0.00 | 01-AUG-00:10 | 12735.87 | 08-AUG-15:00 | 8213.45 | 08-AUG-15:00 | 4522.42 | 08-AUG-15:00 | 3033.66 | 08-AUG-15:00 | 0.00 | 01-AUG-00:10 |
September | 0.341298E+09 | 87786795.84 | 31.83 | 0.269305E+09 | 71993494.19 | 0.00 | 0.72 | 01-SEP-14:10 | 0.00 | 01-SEP-00:05 | 8269.10 | 01-SEP-14:10 | 6549.00 | 01-SEP-15:00 | 2286.46 | 01-SEP-11:50 | 2048.18 | 01-SEP-14:20 | 0.00 | 01-SEP-00:05 |
October | 2306482.52 | 656703.72 | 1.83 | 2153336.18 | 153146.34 | 0.00 | 0.08 | 19-OCT-15:00 | 0.00 | 01-OCT-00:10 | 683.62 | 19-OCT-15:00 | 644.38 | 19-OCT-15:00 | 39.24 | 19-OCT-15:00 | 193.87 | 19-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.122519E+11 | 0.313131E+10 | 746.81 | 0.860053E+10 | 0.365139E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.494568E+10 | 0.124882E+10 | 254.85 | 0.336508E+10 | 0.158060E+10 | 0.00 | 1.00 | 0.00 | 25875.47 | 12319.73 | 13555.74 | 5528.70 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 113.07 | 78.69 | 34.38 | 100.88 | 115.21 | 0.00 | 0.00 | 0.00 |
February | 143.17 | 96.74 | 46.43 | 144.79 | 95.29 | 0.00 | 0.00 | 0.00 |
March | 126.09 | 79.81 | 46.28 | 131.42 | 77.38 | 0.00 | 0.00 | 0.00 |
April | 114.13 | 61.92 | 52.22 | 130.22 | 51.10 | 0.00 | 0.00 | 0.00 |
May | 95.90 | 32.71 | 63.19 | 117.83 | 29.93 | 0.00 | 0.00 | 0.00 |
June | 86.04 | 22.85 | 63.19 | 111.82 | 20.68 | 0.00 | 0.00 | 0.00 |
July | 94.07 | 29.72 | 64.35 | 127.25 | 19.07 | 0.00 | 0.00 | 0.00 |
August | 100.51 | 41.99 | 58.52 | 131.40 | 22.89 | 0.00 | 0.00 | 0.00 |
September | 107.74 | 57.38 | 50.37 | 130.30 | 36.97 | 0.00 | 0.00 | 0.00 |
October | 92.06 | 54.17 | 37.89 | 99.28 | 53.27 | 0.00 | 0.00 | 0.00 |
November | 82.02 | 51.50 | 30.52 | 78.74 | 74.19 | 0.00 | 0.00 | 0.00 |
December | 87.30 | 57.27 | 30.03 | 71.90 | 111.64 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 103.25 | 55.13 | 48.12 | 114.43 | 58.82 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 82.02 | 22.85 | 30.03 | 71.90 | 19.07 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 143.17 | 96.74 | 64.35 | 144.79 | 115.21 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 113.07 | 78.69 | 34.38 | 100.88 | 115.21 | 0.00 | 0.00 | 0.00 |
February | 143.17 | 96.74 | 46.43 | 144.79 | 95.29 | 0.00 | 0.00 | 0.00 |
March | 126.09 | 79.81 | 46.28 | 131.42 | 77.38 | 0.00 | 0.00 | 0.00 |
April | 114.13 | 61.92 | 52.22 | 130.22 | 51.10 | 0.00 | 0.00 | 0.00 |
May | 95.90 | 32.71 | 63.19 | 117.83 | 29.93 | 0.00 | 0.00 | 0.00 |
June | 86.04 | 22.85 | 63.19 | 111.82 | 20.68 | 0.00 | 0.00 | 0.00 |
July | 94.07 | 29.72 | 64.35 | 127.25 | 19.07 | 0.00 | 0.00 | 0.00 |
August | 100.51 | 41.99 | 58.52 | 131.40 | 22.89 | 0.00 | 0.00 | 0.00 |
September | 107.74 | 57.38 | 50.37 | 130.30 | 36.97 | 0.00 | 0.00 | 0.00 |
October | 92.06 | 54.17 | 37.89 | 99.28 | 53.27 | 0.00 | 0.00 | 0.00 |
November | 82.02 | 51.50 | 30.52 | 78.74 | 74.19 | 0.00 | 0.00 | 0.00 |
December | 87.30 | 57.27 | 30.03 | 71.90 | 111.64 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 103.25 | 55.13 | 48.12 | 114.43 | 58.82 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 82.02 | 22.85 | 30.03 | 71.90 | 19.07 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 143.17 | 96.74 | 64.35 | 144.79 | 115.21 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 113.07 | 78.69 | 34.38 | 100.88 | 115.21 | 0.00 | 0.00 | 0.00 |
February | 143.17 | 96.74 | 46.43 | 144.79 | 95.29 | 0.00 | 0.00 | 0.00 |
March | 126.09 | 79.81 | 46.28 | 131.42 | 77.38 | 0.00 | 0.00 | 0.00 |
April | 114.13 | 61.92 | 52.22 | 130.22 | 51.10 | 0.00 | 0.00 | 0.00 |
May | 95.90 | 32.71 | 63.19 | 117.83 | 29.93 | 0.00 | 0.00 | 0.00 |
June | 86.04 | 22.85 | 63.19 | 111.82 | 20.68 | 0.00 | 0.00 | 0.00 |
July | 94.07 | 29.72 | 64.35 | 127.25 | 19.07 | 0.00 | 0.00 | 0.00 |
August | 100.51 | 41.99 | 58.52 | 131.40 | 22.89 | 0.00 | 0.00 | 0.00 |
September | 107.74 | 57.38 | 50.37 | 130.30 | 36.97 | 0.00 | 0.00 | 0.00 |
October | 92.06 | 54.17 | 37.89 | 99.28 | 53.27 | 0.00 | 0.00 | 0.00 |
November | 82.02 | 51.50 | 30.52 | 78.74 | 74.19 | 0.00 | 0.00 | 0.00 |
December | 87.30 | 57.27 | 30.03 | 71.90 | 111.64 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 103.25 | 55.13 | 48.12 | 114.43 | 58.82 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 82.02 | 22.85 | 30.03 | 71.90 | 19.07 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 143.17 | 96.74 | 64.35 | 144.79 | 115.21 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 113.07 | 78.69 | 34.38 | 100.88 | 115.21 | 0.00 | 0.00 | 0.00 |
February | 143.17 | 96.74 | 46.43 | 144.79 | 95.29 | 0.00 | 0.00 | 0.00 |
March | 126.09 | 79.81 | 46.28 | 131.42 | 77.38 | 0.00 | 0.00 | 0.00 |
April | 114.13 | 61.92 | 52.22 | 130.22 | 51.10 | 0.00 | 0.00 | 0.00 |
May | 95.90 | 32.71 | 63.19 | 117.83 | 29.93 | 0.00 | 0.00 | 0.00 |
June | 86.04 | 22.85 | 63.19 | 111.82 | 20.68 | 0.00 | 0.00 | 0.00 |
July | 94.07 | 29.72 | 64.35 | 127.25 | 19.07 | 0.00 | 0.00 | 0.00 |
August | 100.51 | 41.99 | 58.52 | 131.40 | 22.89 | 0.00 | 0.00 | 0.00 |
September | 107.74 | 57.38 | 50.37 | 130.30 | 36.97 | 0.00 | 0.00 | 0.00 |
October | 92.06 | 54.17 | 37.89 | 99.28 | 53.27 | 0.00 | 0.00 | 0.00 |
November | 82.02 | 51.50 | 30.52 | 78.74 | 74.19 | 0.00 | 0.00 | 0.00 |
December | 87.30 | 57.27 | 30.03 | 71.90 | 111.64 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 103.25 | 55.13 | 48.12 | 114.43 | 58.82 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 82.02 | 22.85 | 30.03 | 71.90 | 19.07 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 143.17 | 96.74 | 64.35 | 144.79 | 115.21 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 135.93 | 94.60 | 41.33 | 121.81 | 136.95 | 0.00 | 0.00 | 0.00 |
February | 172.12 | 116.29 | 55.82 | 174.65 | 113.34 | 0.00 | 0.00 | 0.00 |
March | 151.58 | 95.94 | 55.64 | 158.37 | 92.09 | 0.00 | 0.00 | 0.00 |
April | 137.21 | 74.43 | 62.77 | 156.82 | 60.89 | 0.00 | 0.00 | 0.00 |
May | 115.29 | 39.33 | 75.96 | 141.77 | 35.74 | 0.00 | 0.00 | 0.00 |
June | 103.44 | 27.47 | 75.96 | 134.44 | 24.74 | 0.00 | 0.00 | 0.00 |
July | 113.08 | 35.72 | 77.36 | 152.92 | 22.84 | 0.00 | 0.00 | 0.00 |
August | 120.83 | 50.48 | 70.34 | 158.01 | 27.37 | 0.00 | 0.00 | 0.00 |
September | 129.52 | 68.97 | 60.55 | 156.81 | 44.11 | 0.00 | 0.00 | 0.00 |
October | 110.67 | 65.11 | 45.56 | 119.58 | 63.50 | 0.00 | 0.00 | 0.00 |
November | 98.60 | 61.91 | 36.69 | 95.00 | 88.27 | 0.00 | 0.00 | 0.00 |
December | 104.95 | 68.84 | 36.11 | 86.88 | 132.64 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 124.12 | 66.28 | 57.85 | 137.81 | 70.02 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 98.60 | 27.47 | 36.11 | 86.88 | 22.84 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 172.12 | 116.29 | 77.36 | 174.65 | 136.95 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 135.93 | 94.60 | 41.33 | 121.81 | 136.95 | 0.00 | 0.00 | 0.00 |
February | 172.12 | 116.29 | 55.82 | 174.65 | 113.34 | 0.00 | 0.00 | 0.00 |
March | 151.58 | 95.94 | 55.64 | 158.37 | 92.09 | 0.00 | 0.00 | 0.00 |
April | 137.21 | 74.43 | 62.77 | 156.82 | 60.89 | 0.00 | 0.00 | 0.00 |
May | 115.29 | 39.33 | 75.96 | 141.77 | 35.74 | 0.00 | 0.00 | 0.00 |
June | 103.44 | 27.47 | 75.96 | 134.44 | 24.74 | 0.00 | 0.00 | 0.00 |
July | 113.08 | 35.72 | 77.36 | 152.92 | 22.84 | 0.00 | 0.00 | 0.00 |
August | 120.83 | 50.48 | 70.34 | 158.01 | 27.37 | 0.00 | 0.00 | 0.00 |
September | 129.52 | 68.97 | 60.55 | 156.81 | 44.11 | 0.00 | 0.00 | 0.00 |
October | 110.67 | 65.11 | 45.56 | 119.58 | 63.50 | 0.00 | 0.00 | 0.00 |
November | 98.60 | 61.91 | 36.69 | 95.00 | 88.27 | 0.00 | 0.00 | 0.00 |
December | 104.95 | 68.84 | 36.11 | 86.88 | 132.64 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 124.12 | 66.28 | 57.85 | 137.81 | 70.02 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 98.60 | 27.47 | 36.11 | 86.88 | 22.84 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 172.12 | 116.29 | 77.36 | 174.65 | 136.95 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 113.07 | 78.69 | 34.38 | 99.90 | 118.42 | 0.00 | 0.00 | 0.00 |
February | 143.17 | 96.74 | 46.43 | 143.53 | 98.51 | 0.00 | 0.00 | 0.00 |
March | 126.09 | 79.81 | 46.28 | 130.28 | 80.58 | 0.00 | 0.00 | 0.00 |
April | 114.13 | 61.92 | 52.22 | 129.27 | 53.58 | 0.00 | 0.00 | 0.00 |
May | 95.90 | 32.71 | 63.19 | 117.36 | 30.82 | 0.00 | 0.00 | 0.00 |
June | 86.04 | 22.85 | 63.19 | 111.33 | 21.29 | 0.00 | 0.00 | 0.00 |
July | 94.07 | 29.72 | 64.35 | 126.94 | 19.47 | 0.00 | 0.00 | 0.00 |
August | 100.51 | 41.99 | 58.52 | 131.14 | 23.32 | 0.00 | 0.00 | 0.00 |
September | 107.74 | 57.38 | 50.37 | 130.34 | 37.30 | 0.00 | 0.00 | 0.00 |
October | 92.06 | 54.17 | 37.89 | 99.12 | 54.30 | 0.00 | 0.00 | 0.00 |
November | 82.02 | 51.50 | 30.52 | 77.99 | 76.99 | 0.00 | 0.00 | 0.00 |
December | 87.30 | 57.27 | 30.03 | 71.10 | 114.92 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 103.25 | 55.13 | 48.12 | 113.80 | 60.63 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 82.02 | 22.85 | 30.03 | 71.10 | 19.47 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 143.17 | 96.74 | 64.35 | 143.53 | 118.42 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 113.07 | 78.69 | 34.38 | 99.90 | 118.42 | 0.00 | 0.00 | 0.00 |
February | 143.17 | 96.74 | 46.43 | 143.53 | 98.51 | 0.00 | 0.00 | 0.00 |
March | 126.09 | 79.81 | 46.28 | 130.28 | 80.58 | 0.00 | 0.00 | 0.00 |
April | 114.13 | 61.92 | 52.22 | 129.27 | 53.58 | 0.00 | 0.00 | 0.00 |
May | 95.90 | 32.71 | 63.19 | 117.36 | 30.82 | 0.00 | 0.00 | 0.00 |
June | 86.04 | 22.85 | 63.19 | 111.33 | 21.29 | 0.00 | 0.00 | 0.00 |
July | 94.07 | 29.72 | 64.35 | 126.94 | 19.47 | 0.00 | 0.00 | 0.00 |
August | 100.51 | 41.99 | 58.52 | 131.14 | 23.32 | 0.00 | 0.00 | 0.00 |
September | 107.74 | 57.38 | 50.37 | 130.34 | 37.30 | 0.00 | 0.00 | 0.00 |
October | 92.06 | 54.17 | 37.89 | 99.12 | 54.30 | 0.00 | 0.00 | 0.00 |
November | 82.02 | 51.50 | 30.52 | 77.99 | 76.99 | 0.00 | 0.00 | 0.00 |
December | 87.30 | 57.27 | 30.03 | 71.10 | 114.92 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 103.25 | 55.13 | 48.12 | 113.80 | 60.63 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 82.02 | 22.85 | 30.03 | 71.10 | 19.47 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 143.17 | 96.74 | 64.35 | 143.53 | 118.42 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 135.93 | 94.60 | 41.33 | 120.65 | 140.75 | 0.00 | 0.00 | 0.00 |
February | 172.12 | 116.29 | 55.82 | 173.16 | 117.14 | 0.00 | 0.00 | 0.00 |
March | 151.58 | 95.94 | 55.64 | 157.01 | 95.88 | 0.00 | 0.00 | 0.00 |
April | 137.21 | 74.43 | 62.77 | 155.69 | 63.82 | 0.00 | 0.00 | 0.00 |
May | 115.29 | 39.33 | 75.96 | 141.21 | 36.79 | 0.00 | 0.00 | 0.00 |
June | 103.44 | 27.47 | 75.96 | 133.86 | 25.47 | 0.00 | 0.00 | 0.00 |
July | 113.08 | 35.72 | 77.36 | 152.57 | 23.32 | 0.00 | 0.00 | 0.00 |
August | 120.83 | 50.48 | 70.34 | 157.72 | 27.88 | 0.00 | 0.00 | 0.00 |
September | 129.52 | 68.97 | 60.55 | 156.88 | 44.49 | 0.00 | 0.00 | 0.00 |
October | 110.67 | 65.11 | 45.56 | 119.41 | 64.70 | 0.00 | 0.00 | 0.00 |
November | 98.60 | 61.91 | 36.69 | 94.11 | 91.57 | 0.00 | 0.00 | 0.00 |
December | 104.95 | 68.84 | 36.11 | 85.93 | 136.50 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 124.12 | 66.28 | 57.85 | 137.08 | 72.17 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 98.60 | 27.47 | 36.11 | 85.93 | 23.32 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 172.12 | 116.29 | 77.36 | 173.16 | 140.75 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 113.07 | 78.69 | 34.38 | 100.05 | 116.59 | 0.00 | 0.00 | 0.00 |
February | 143.17 | 96.74 | 46.43 | 143.64 | 97.03 | 0.00 | 0.00 | 0.00 |
March | 126.09 | 79.81 | 46.28 | 130.33 | 79.42 | 0.00 | 0.00 | 0.00 |
April | 114.13 | 61.92 | 52.22 | 129.53 | 52.34 | 0.00 | 0.00 | 0.00 |
May | 95.90 | 32.71 | 63.19 | 117.68 | 30.58 | 0.00 | 0.00 | 0.00 |
June | 86.04 | 22.85 | 63.19 | 111.34 | 21.79 | 0.00 | 0.00 | 0.00 |
July | 94.07 | 29.72 | 64.35 | 126.60 | 20.58 | 0.00 | 0.00 | 0.00 |
August | 100.51 | 41.99 | 58.52 | 131.02 | 24.29 | 0.00 | 0.00 | 0.00 |
September | 107.74 | 57.38 | 50.37 | 130.68 | 37.14 | 0.00 | 0.00 | 0.00 |
October | 92.06 | 54.17 | 37.89 | 99.52 | 52.79 | 0.00 | 0.00 | 0.00 |
November | 82.02 | 51.50 | 30.52 | 78.15 | 75.56 | 0.00 | 0.00 | 0.00 |
December | 87.30 | 57.27 | 30.03 | 71.21 | 113.18 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 103.25 | 55.13 | 48.12 | 113.92 | 59.95 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 82.02 | 22.85 | 30.03 | 71.21 | 20.58 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 143.17 | 96.74 | 64.35 | 143.64 | 116.59 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 113.07 | 78.69 | 34.38 | 100.05 | 116.59 | 0.00 | 0.00 | 0.00 |
February | 143.17 | 96.74 | 46.43 | 143.64 | 97.03 | 0.00 | 0.00 | 0.00 |
March | 126.09 | 79.81 | 46.28 | 130.33 | 79.42 | 0.00 | 0.00 | 0.00 |
April | 114.13 | 61.92 | 52.22 | 129.53 | 52.34 | 0.00 | 0.00 | 0.00 |
May | 95.90 | 32.71 | 63.19 | 117.68 | 30.58 | 0.00 | 0.00 | 0.00 |
June | 86.04 | 22.85 | 63.19 | 111.34 | 21.79 | 0.00 | 0.00 | 0.00 |
July | 94.07 | 29.72 | 64.35 | 126.60 | 20.58 | 0.00 | 0.00 | 0.00 |
August | 100.51 | 41.99 | 58.52 | 131.02 | 24.29 | 0.00 | 0.00 | 0.00 |
September | 107.74 | 57.38 | 50.37 | 130.68 | 37.14 | 0.00 | 0.00 | 0.00 |
October | 92.06 | 54.17 | 37.89 | 99.52 | 52.79 | 0.00 | 0.00 | 0.00 |
November | 82.02 | 51.50 | 30.52 | 78.15 | 75.56 | 0.00 | 0.00 | 0.00 |
December | 87.30 | 57.27 | 30.03 | 71.21 | 113.18 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 103.25 | 55.13 | 48.12 | 113.92 | 59.95 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 82.02 | 22.85 | 30.03 | 71.21 | 20.58 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 143.17 | 96.74 | 64.35 | 143.64 | 116.59 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 135.19 | 94.08 | 41.11 | 120.16 | 137.82 | 0.00 | 0.00 | 0.00 |
February | 171.17 | 115.66 | 55.52 | 172.36 | 114.77 | 0.00 | 0.00 | 0.00 |
March | 150.75 | 95.42 | 55.33 | 156.22 | 93.99 | 0.00 | 0.00 | 0.00 |
April | 136.46 | 74.03 | 62.43 | 155.15 | 62.01 | 0.00 | 0.00 | 0.00 |
May | 114.66 | 39.11 | 75.55 | 140.83 | 36.31 | 0.00 | 0.00 | 0.00 |
June | 102.87 | 27.32 | 75.55 | 133.14 | 25.91 | 0.00 | 0.00 | 0.00 |
July | 112.47 | 35.53 | 76.94 | 151.34 | 24.48 | 0.00 | 0.00 | 0.00 |
August | 120.17 | 50.20 | 69.96 | 156.71 | 28.86 | 0.00 | 0.00 | 0.00 |
September | 128.81 | 68.60 | 60.22 | 156.43 | 44.06 | 0.00 | 0.00 | 0.00 |
October | 110.07 | 64.76 | 45.31 | 119.23 | 62.57 | 0.00 | 0.00 | 0.00 |
November | 98.06 | 61.57 | 36.49 | 93.79 | 89.39 | 0.00 | 0.00 | 0.00 |
December | 104.38 | 68.47 | 35.91 | 85.59 | 133.71 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 123.44 | 65.91 | 57.53 | 136.48 | 70.97 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 98.06 | 27.32 | 35.91 | 85.59 | 24.48 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 171.17 | 115.66 | 76.94 | 172.36 | 137.82 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 113.07 | 78.69 | 34.38 | 100.14 | 115.84 | 0.00 | 0.00 | 0.00 |
February | 143.17 | 96.74 | 46.43 | 143.77 | 96.34 | 0.00 | 0.00 | 0.00 |
March | 126.09 | 79.81 | 46.28 | 130.44 | 78.80 | 0.00 | 0.00 | 0.00 |
April | 114.13 | 61.92 | 52.22 | 129.73 | 51.66 | 0.00 | 0.00 | 0.00 |
May | 95.90 | 32.71 | 63.19 | 117.94 | 30.12 | 0.00 | 0.00 | 0.00 |
June | 86.04 | 22.85 | 63.19 | 111.51 | 21.55 | 0.00 | 0.00 | 0.00 |
July | 94.07 | 29.72 | 64.35 | 126.63 | 20.55 | 0.00 | 0.00 | 0.00 |
August | 100.51 | 41.99 | 58.52 | 131.06 | 24.21 | 0.00 | 0.00 | 0.00 |
September | 107.74 | 57.38 | 50.37 | 130.88 | 36.69 | 0.00 | 0.00 | 0.00 |
October | 92.06 | 54.17 | 37.89 | 99.73 | 52.06 | 0.00 | 0.00 | 0.00 |
November | 82.02 | 51.50 | 30.52 | 78.27 | 74.84 | 0.00 | 0.00 | 0.00 |
December | 87.30 | 57.27 | 30.03 | 71.28 | 112.45 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 103.25 | 55.13 | 48.12 | 114.06 | 59.44 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 82.02 | 22.85 | 30.03 | 71.28 | 20.55 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 143.17 | 96.74 | 64.35 | 143.77 | 115.84 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 113.07 | 78.69 | 34.38 | 100.14 | 115.84 | 0.00 | 0.00 | 0.00 |
February | 143.17 | 96.74 | 46.43 | 143.77 | 96.34 | 0.00 | 0.00 | 0.00 |
March | 126.09 | 79.81 | 46.28 | 130.44 | 78.80 | 0.00 | 0.00 | 0.00 |
April | 114.13 | 61.92 | 52.22 | 129.73 | 51.66 | 0.00 | 0.00 | 0.00 |
May | 95.90 | 32.71 | 63.19 | 117.94 | 30.12 | 0.00 | 0.00 | 0.00 |
June | 86.04 | 22.85 | 63.19 | 111.51 | 21.55 | 0.00 | 0.00 | 0.00 |
July | 94.07 | 29.72 | 64.35 | 126.63 | 20.55 | 0.00 | 0.00 | 0.00 |
August | 100.51 | 41.99 | 58.52 | 131.06 | 24.21 | 0.00 | 0.00 | 0.00 |
September | 107.74 | 57.38 | 50.37 | 130.88 | 36.69 | 0.00 | 0.00 | 0.00 |
October | 92.06 | 54.17 | 37.89 | 99.73 | 52.06 | 0.00 | 0.00 | 0.00 |
November | 82.02 | 51.50 | 30.52 | 78.27 | 74.84 | 0.00 | 0.00 | 0.00 |
December | 87.30 | 57.27 | 30.03 | 71.28 | 112.45 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 103.25 | 55.13 | 48.12 | 114.06 | 59.44 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 82.02 | 22.85 | 30.03 | 71.28 | 20.55 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 143.17 | 96.74 | 64.35 | 143.77 | 115.84 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 135.19 | 94.08 | 41.11 | 120.29 | 136.93 | 0.00 | 0.00 | 0.00 |
February | 171.17 | 115.66 | 55.52 | 172.51 | 113.94 | 0.00 | 0.00 | 0.00 |
March | 150.75 | 95.42 | 55.33 | 156.35 | 93.25 | 0.00 | 0.00 | 0.00 |
April | 136.46 | 74.03 | 62.43 | 155.39 | 61.21 | 0.00 | 0.00 | 0.00 |
May | 114.66 | 39.11 | 75.55 | 141.14 | 35.76 | 0.00 | 0.00 | 0.00 |
June | 102.87 | 27.32 | 75.55 | 133.34 | 25.63 | 0.00 | 0.00 | 0.00 |
July | 112.47 | 35.53 | 76.94 | 151.36 | 24.45 | 0.00 | 0.00 | 0.00 |
August | 120.17 | 50.20 | 69.96 | 156.76 | 28.76 | 0.00 | 0.00 | 0.00 |
September | 128.81 | 68.60 | 60.22 | 156.66 | 43.52 | 0.00 | 0.00 | 0.00 |
October | 110.07 | 64.76 | 45.31 | 119.48 | 61.71 | 0.00 | 0.00 | 0.00 |
November | 98.06 | 61.57 | 36.49 | 93.93 | 88.54 | 0.00 | 0.00 | 0.00 |
December | 104.38 | 68.47 | 35.91 | 85.69 | 132.84 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 123.44 | 65.91 | 57.53 | 136.64 | 70.36 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 98.06 | 27.32 | 35.91 | 85.69 | 24.45 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 171.17 | 115.66 | 76.94 | 172.51 | 136.93 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 113.07 | 78.69 | 34.38 | 100.27 | 115.28 | 0.00 | 0.00 | 0.00 |
February | 143.17 | 96.74 | 46.43 | 143.94 | 95.74 | 0.00 | 0.00 | 0.00 |
March | 126.09 | 79.81 | 46.28 | 130.60 | 78.22 | 0.00 | 0.00 | 0.00 |
April | 114.13 | 61.92 | 52.22 | 129.98 | 51.06 | 0.00 | 0.00 | 0.00 |
May | 95.90 | 32.71 | 63.19 | 118.30 | 29.60 | 0.00 | 0.00 | 0.00 |
June | 86.04 | 22.85 | 63.19 | 111.81 | 21.16 | 0.00 | 0.00 | 0.00 |
July | 94.07 | 29.72 | 64.35 | 126.76 | 20.31 | 0.00 | 0.00 | 0.00 |
August | 100.51 | 41.99 | 58.52 | 131.20 | 23.93 | 0.00 | 0.00 | 0.00 |
September | 107.74 | 57.38 | 50.37 | 131.13 | 36.19 | 0.00 | 0.00 | 0.00 |
October | 92.06 | 54.17 | 37.89 | 99.93 | 51.50 | 0.00 | 0.00 | 0.00 |
November | 82.02 | 51.50 | 30.52 | 78.42 | 74.21 | 0.00 | 0.00 | 0.00 |
December | 87.30 | 57.27 | 30.03 | 71.39 | 111.85 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 103.25 | 55.13 | 48.12 | 114.25 | 58.93 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 82.02 | 22.85 | 30.03 | 71.39 | 20.31 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 143.17 | 96.74 | 64.35 | 143.94 | 115.28 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 113.07 | 78.69 | 34.38 | 100.27 | 115.28 | 0.00 | 0.00 | 0.00 |
February | 143.17 | 96.74 | 46.43 | 143.94 | 95.74 | 0.00 | 0.00 | 0.00 |
March | 126.09 | 79.81 | 46.28 | 130.60 | 78.22 | 0.00 | 0.00 | 0.00 |
April | 114.13 | 61.92 | 52.22 | 129.98 | 51.06 | 0.00 | 0.00 | 0.00 |
May | 95.90 | 32.71 | 63.19 | 118.30 | 29.60 | 0.00 | 0.00 | 0.00 |
June | 86.04 | 22.85 | 63.19 | 111.81 | 21.16 | 0.00 | 0.00 | 0.00 |
July | 94.07 | 29.72 | 64.35 | 126.76 | 20.31 | 0.00 | 0.00 | 0.00 |
August | 100.51 | 41.99 | 58.52 | 131.20 | 23.93 | 0.00 | 0.00 | 0.00 |
September | 107.74 | 57.38 | 50.37 | 131.13 | 36.19 | 0.00 | 0.00 | 0.00 |
October | 92.06 | 54.17 | 37.89 | 99.93 | 51.50 | 0.00 | 0.00 | 0.00 |
November | 82.02 | 51.50 | 30.52 | 78.42 | 74.21 | 0.00 | 0.00 | 0.00 |
December | 87.30 | 57.27 | 30.03 | 71.39 | 111.85 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 103.25 | 55.13 | 48.12 | 114.25 | 58.93 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 82.02 | 22.85 | 30.03 | 71.39 | 20.31 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 143.17 | 96.74 | 64.35 | 143.94 | 115.28 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 135.19 | 94.08 | 41.11 | 120.43 | 136.27 | 0.00 | 0.00 | 0.00 |
February | 171.17 | 115.66 | 55.52 | 172.72 | 113.24 | 0.00 | 0.00 | 0.00 |
March | 150.75 | 95.42 | 55.33 | 156.54 | 92.57 | 0.00 | 0.00 | 0.00 |
April | 136.46 | 74.03 | 62.43 | 155.69 | 60.49 | 0.00 | 0.00 | 0.00 |
May | 114.66 | 39.11 | 75.55 | 141.56 | 35.14 | 0.00 | 0.00 | 0.00 |
June | 102.87 | 27.32 | 75.55 | 133.71 | 25.16 | 0.00 | 0.00 | 0.00 |
July | 112.47 | 35.53 | 76.94 | 151.53 | 24.17 | 0.00 | 0.00 | 0.00 |
August | 120.17 | 50.20 | 69.96 | 156.93 | 28.43 | 0.00 | 0.00 | 0.00 |
September | 128.81 | 68.60 | 60.22 | 156.96 | 42.93 | 0.00 | 0.00 | 0.00 |
October | 110.07 | 64.76 | 45.31 | 119.73 | 61.04 | 0.00 | 0.00 | 0.00 |
November | 98.06 | 61.57 | 36.49 | 94.11 | 87.79 | 0.00 | 0.00 | 0.00 |
December | 104.38 | 68.47 | 35.91 | 85.82 | 132.13 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 123.44 | 65.91 | 57.53 | 136.87 | 69.77 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 98.06 | 27.32 | 35.91 | 85.82 | 24.17 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 171.17 | 115.66 | 76.94 | 172.72 | 136.27 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 113.07 | 78.69 | 34.38 | 100.82 | 113.07 | 0.00 | 0.00 | 0.00 |
February | 143.17 | 96.74 | 46.43 | 144.71 | 93.69 | 0.00 | 0.00 | 0.00 |
March | 126.09 | 79.81 | 46.28 | 131.22 | 76.36 | 0.00 | 0.00 | 0.00 |
April | 114.13 | 61.92 | 52.22 | 130.55 | 49.51 | 0.00 | 0.00 | 0.00 |
May | 95.90 | 32.71 | 63.19 | 118.80 | 28.50 | 0.00 | 0.00 | 0.00 |
June | 86.04 | 22.85 | 63.19 | 112.18 | 20.29 | 0.00 | 0.00 | 0.00 |
July | 94.07 | 29.72 | 64.35 | 126.77 | 19.66 | 0.00 | 0.00 | 0.00 |
August | 100.51 | 41.99 | 58.52 | 131.28 | 23.21 | 0.00 | 0.00 | 0.00 |
September | 107.74 | 57.38 | 50.37 | 131.42 | 35.23 | 0.00 | 0.00 | 0.00 |
October | 92.06 | 54.17 | 37.89 | 100.34 | 50.29 | 0.00 | 0.00 | 0.00 |
November | 82.02 | 51.50 | 30.52 | 78.89 | 72.36 | 0.00 | 0.00 | 0.00 |
December | 87.30 | 57.27 | 30.03 | 71.87 | 109.60 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 103.25 | 55.13 | 48.12 | 114.68 | 57.50 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 82.02 | 22.85 | 30.03 | 71.87 | 19.66 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 143.17 | 96.74 | 64.35 | 144.71 | 113.07 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 113.07 | 78.69 | 34.38 | 100.82 | 113.07 | 0.00 | 0.00 | 0.00 |
February | 143.17 | 96.74 | 46.43 | 144.71 | 93.69 | 0.00 | 0.00 | 0.00 |
March | 126.09 | 79.81 | 46.28 | 131.22 | 76.36 | 0.00 | 0.00 | 0.00 |
April | 114.13 | 61.92 | 52.22 | 130.55 | 49.51 | 0.00 | 0.00 | 0.00 |
May | 95.90 | 32.71 | 63.19 | 118.80 | 28.50 | 0.00 | 0.00 | 0.00 |
June | 86.04 | 22.85 | 63.19 | 112.18 | 20.29 | 0.00 | 0.00 | 0.00 |
July | 94.07 | 29.72 | 64.35 | 126.77 | 19.66 | 0.00 | 0.00 | 0.00 |
August | 100.51 | 41.99 | 58.52 | 131.28 | 23.21 | 0.00 | 0.00 | 0.00 |
September | 107.74 | 57.38 | 50.37 | 131.42 | 35.23 | 0.00 | 0.00 | 0.00 |
October | 92.06 | 54.17 | 37.89 | 100.34 | 50.29 | 0.00 | 0.00 | 0.00 |
November | 82.02 | 51.50 | 30.52 | 78.89 | 72.36 | 0.00 | 0.00 | 0.00 |
December | 87.30 | 57.27 | 30.03 | 71.87 | 109.60 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 103.25 | 55.13 | 48.12 | 114.68 | 57.50 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 82.02 | 22.85 | 30.03 | 71.87 | 19.66 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 143.17 | 96.74 | 64.35 | 144.71 | 113.07 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 113.07 | 78.69 | 34.38 | 100.82 | 113.07 | 0.00 | 0.00 | 0.00 |
February | 143.17 | 96.74 | 46.43 | 144.71 | 93.69 | 0.00 | 0.00 | 0.00 |
March | 126.09 | 79.81 | 46.28 | 131.22 | 76.36 | 0.00 | 0.00 | 0.00 |
April | 114.13 | 61.92 | 52.22 | 130.55 | 49.51 | 0.00 | 0.00 | 0.00 |
May | 95.90 | 32.71 | 63.19 | 118.80 | 28.50 | 0.00 | 0.00 | 0.00 |
June | 86.04 | 22.85 | 63.19 | 112.18 | 20.29 | 0.00 | 0.00 | 0.00 |
July | 94.07 | 29.72 | 64.35 | 126.77 | 19.66 | 0.00 | 0.00 | 0.00 |
August | 100.51 | 41.99 | 58.52 | 131.28 | 23.21 | 0.00 | 0.00 | 0.00 |
September | 107.74 | 57.38 | 50.37 | 131.42 | 35.23 | 0.00 | 0.00 | 0.00 |
October | 92.06 | 54.17 | 37.89 | 100.34 | 50.29 | 0.00 | 0.00 | 0.00 |
November | 82.02 | 51.50 | 30.52 | 78.89 | 72.36 | 0.00 | 0.00 | 0.00 |
December | 87.30 | 57.27 | 30.03 | 71.87 | 109.60 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 103.25 | 55.13 | 48.12 | 114.68 | 57.50 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 82.02 | 22.85 | 30.03 | 71.87 | 19.66 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 143.17 | 96.74 | 64.35 | 144.71 | 113.07 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 113.07 | 78.69 | 34.38 | 100.82 | 113.07 | 0.00 | 0.00 | 0.00 |
February | 143.17 | 96.74 | 46.43 | 144.71 | 93.69 | 0.00 | 0.00 | 0.00 |
March | 126.09 | 79.81 | 46.28 | 131.22 | 76.36 | 0.00 | 0.00 | 0.00 |
April | 114.13 | 61.92 | 52.22 | 130.55 | 49.51 | 0.00 | 0.00 | 0.00 |
May | 95.90 | 32.71 | 63.19 | 118.80 | 28.50 | 0.00 | 0.00 | 0.00 |
June | 86.04 | 22.85 | 63.19 | 112.18 | 20.29 | 0.00 | 0.00 | 0.00 |
July | 94.07 | 29.72 | 64.35 | 126.77 | 19.66 | 0.00 | 0.00 | 0.00 |
August | 100.51 | 41.99 | 58.52 | 131.28 | 23.21 | 0.00 | 0.00 | 0.00 |
September | 107.74 | 57.38 | 50.37 | 131.42 | 35.23 | 0.00 | 0.00 | 0.00 |
October | 92.06 | 54.17 | 37.89 | 100.34 | 50.29 | 0.00 | 0.00 | 0.00 |
November | 82.02 | 51.50 | 30.52 | 78.89 | 72.36 | 0.00 | 0.00 | 0.00 |
December | 87.30 | 57.27 | 30.03 | 71.87 | 109.60 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 103.25 | 55.13 | 48.12 | 114.68 | 57.50 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 82.02 | 22.85 | 30.03 | 71.87 | 19.66 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 143.17 | 96.74 | 64.35 | 144.71 | 113.07 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 135.19 | 94.08 | 41.11 | 121.07 | 133.70 | 0.00 | 0.00 | 0.00 |
February | 171.17 | 115.66 | 55.52 | 173.61 | 110.86 | 0.00 | 0.00 | 0.00 |
March | 150.75 | 95.42 | 55.33 | 157.26 | 90.40 | 0.00 | 0.00 | 0.00 |
April | 136.46 | 74.03 | 62.43 | 156.36 | 58.67 | 0.00 | 0.00 | 0.00 |
May | 114.66 | 39.11 | 75.55 | 142.15 | 33.85 | 0.00 | 0.00 | 0.00 |
June | 102.87 | 27.32 | 75.55 | 134.14 | 24.13 | 0.00 | 0.00 | 0.00 |
July | 112.47 | 35.53 | 76.94 | 151.53 | 23.40 | 0.00 | 0.00 | 0.00 |
August | 120.17 | 50.20 | 69.96 | 157.00 | 27.59 | 0.00 | 0.00 | 0.00 |
September | 128.81 | 68.60 | 60.22 | 157.28 | 41.80 | 0.00 | 0.00 | 0.00 |
October | 110.07 | 64.76 | 45.31 | 120.19 | 59.62 | 0.00 | 0.00 | 0.00 |
November | 98.06 | 61.57 | 36.49 | 94.66 | 85.63 | 0.00 | 0.00 | 0.00 |
December | 104.38 | 68.47 | 35.91 | 86.37 | 129.53 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 123.44 | 65.91 | 57.53 | 137.36 | 68.09 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 98.06 | 27.32 | 35.91 | 86.37 | 23.40 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 171.17 | 115.66 | 76.94 | 173.61 | 133.70 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 135.19 | 94.08 | 41.11 | 121.07 | 133.70 | 0.00 | 0.00 | 0.00 |
February | 171.17 | 115.66 | 55.52 | 173.61 | 110.86 | 0.00 | 0.00 | 0.00 |
March | 150.75 | 95.42 | 55.33 | 157.26 | 90.40 | 0.00 | 0.00 | 0.00 |
April | 136.46 | 74.03 | 62.43 | 156.36 | 58.67 | 0.00 | 0.00 | 0.00 |
May | 114.66 | 39.11 | 75.55 | 142.15 | 33.85 | 0.00 | 0.00 | 0.00 |
June | 102.87 | 27.32 | 75.55 | 134.14 | 24.13 | 0.00 | 0.00 | 0.00 |
July | 112.47 | 35.53 | 76.94 | 151.53 | 23.40 | 0.00 | 0.00 | 0.00 |
August | 120.17 | 50.20 | 69.96 | 157.00 | 27.59 | 0.00 | 0.00 | 0.00 |
September | 128.81 | 68.60 | 60.22 | 157.28 | 41.80 | 0.00 | 0.00 | 0.00 |
October | 110.07 | 64.76 | 45.31 | 120.19 | 59.62 | 0.00 | 0.00 | 0.00 |
November | 98.06 | 61.57 | 36.49 | 94.66 | 85.63 | 0.00 | 0.00 | 0.00 |
December | 104.38 | 68.47 | 35.91 | 86.37 | 129.53 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 123.44 | 65.91 | 57.53 | 137.36 | 68.09 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 98.06 | 27.32 | 35.91 | 86.37 | 23.40 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 171.17 | 115.66 | 76.94 | 173.61 | 133.70 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 113.07 | 78.69 | 34.38 | 100.42 | 113.76 | 0.00 | 0.00 | 0.00 |
February | 143.17 | 96.74 | 46.43 | 144.25 | 94.20 | 0.00 | 0.00 | 0.00 |
March | 126.09 | 79.81 | 46.28 | 130.88 | 76.72 | 0.00 | 0.00 | 0.00 |
April | 114.13 | 61.92 | 52.22 | 130.32 | 49.55 | 0.00 | 0.00 | 0.00 |
May | 95.90 | 32.71 | 63.19 | 118.75 | 28.35 | 0.00 | 0.00 | 0.00 |
June | 86.04 | 22.85 | 63.19 | 112.21 | 20.10 | 0.00 | 0.00 | 0.00 |
July | 94.07 | 29.72 | 64.35 | 126.76 | 19.49 | 0.00 | 0.00 | 0.00 |
August | 100.51 | 41.99 | 58.52 | 131.19 | 23.05 | 0.00 | 0.00 | 0.00 |
September | 107.74 | 57.38 | 50.37 | 131.29 | 35.11 | 0.00 | 0.00 | 0.00 |
October | 92.06 | 54.17 | 37.89 | 100.15 | 50.30 | 0.00 | 0.00 | 0.00 |
November | 82.02 | 51.50 | 30.52 | 78.63 | 72.69 | 0.00 | 0.00 | 0.00 |
December | 87.30 | 57.27 | 30.03 | 71.55 | 110.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 103.25 | 55.13 | 48.12 | 114.47 | 57.65 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 82.02 | 22.85 | 30.03 | 71.55 | 19.49 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 143.17 | 96.74 | 64.35 | 144.25 | 113.76 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 113.07 | 78.69 | 34.38 | 100.42 | 113.76 | 0.00 | 0.00 | 0.00 |
February | 143.17 | 96.74 | 46.43 | 144.25 | 94.20 | 0.00 | 0.00 | 0.00 |
March | 126.09 | 79.81 | 46.28 | 130.88 | 76.72 | 0.00 | 0.00 | 0.00 |
April | 114.13 | 61.92 | 52.22 | 130.32 | 49.55 | 0.00 | 0.00 | 0.00 |
May | 95.90 | 32.71 | 63.19 | 118.75 | 28.35 | 0.00 | 0.00 | 0.00 |
June | 86.04 | 22.85 | 63.19 | 112.21 | 20.10 | 0.00 | 0.00 | 0.00 |
July | 94.07 | 29.72 | 64.35 | 126.76 | 19.49 | 0.00 | 0.00 | 0.00 |
August | 100.51 | 41.99 | 58.52 | 131.19 | 23.05 | 0.00 | 0.00 | 0.00 |
September | 107.74 | 57.38 | 50.37 | 131.29 | 35.11 | 0.00 | 0.00 | 0.00 |
October | 92.06 | 54.17 | 37.89 | 100.15 | 50.30 | 0.00 | 0.00 | 0.00 |
November | 82.02 | 51.50 | 30.52 | 78.63 | 72.69 | 0.00 | 0.00 | 0.00 |
December | 87.30 | 57.27 | 30.03 | 71.55 | 110.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 103.25 | 55.13 | 48.12 | 114.47 | 57.65 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 82.02 | 22.85 | 30.03 | 71.55 | 19.49 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 143.17 | 96.74 | 64.35 | 144.25 | 113.76 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 135.19 | 94.08 | 41.11 | 120.63 | 134.46 | 0.00 | 0.00 | 0.00 |
February | 171.17 | 115.66 | 55.52 | 173.10 | 111.41 | 0.00 | 0.00 | 0.00 |
March | 150.75 | 95.42 | 55.33 | 156.89 | 90.78 | 0.00 | 0.00 | 0.00 |
April | 136.46 | 74.03 | 62.43 | 156.11 | 58.71 | 0.00 | 0.00 | 0.00 |
May | 114.66 | 39.11 | 75.55 | 142.11 | 33.66 | 0.00 | 0.00 | 0.00 |
June | 102.87 | 27.32 | 75.55 | 134.19 | 23.90 | 0.00 | 0.00 | 0.00 |
July | 112.47 | 35.53 | 76.94 | 151.53 | 23.19 | 0.00 | 0.00 | 0.00 |
August | 120.17 | 50.20 | 69.96 | 156.93 | 27.39 | 0.00 | 0.00 | 0.00 |
September | 128.81 | 68.60 | 60.22 | 157.16 | 41.64 | 0.00 | 0.00 | 0.00 |
October | 110.07 | 64.76 | 45.31 | 120.00 | 59.62 | 0.00 | 0.00 | 0.00 |
November | 98.06 | 61.57 | 36.49 | 94.38 | 85.98 | 0.00 | 0.00 | 0.00 |
December | 104.38 | 68.47 | 35.91 | 86.02 | 130.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 123.44 | 65.91 | 57.53 | 137.15 | 68.25 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 98.06 | 27.32 | 35.91 | 86.02 | 23.19 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 171.17 | 115.66 | 76.94 | 173.10 | 134.46 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 113.07 | 78.69 | 34.38 | 100.44 | 113.67 | 0.00 | 0.00 | 0.00 |
February | 143.17 | 96.74 | 46.43 | 144.29 | 94.07 | 0.00 | 0.00 | 0.00 |
March | 126.09 | 79.81 | 46.28 | 130.93 | 76.55 | 0.00 | 0.00 | 0.00 |
April | 114.13 | 61.92 | 52.22 | 130.43 | 49.29 | 0.00 | 0.00 | 0.00 |
May | 95.90 | 32.71 | 63.19 | 118.96 | 28.09 | 0.00 | 0.00 | 0.00 |
June | 86.04 | 22.85 | 63.19 | 112.41 | 19.89 | 0.00 | 0.00 | 0.00 |
July | 94.07 | 29.72 | 64.35 | 126.85 | 19.38 | 0.00 | 0.00 | 0.00 |
August | 100.51 | 41.99 | 58.52 | 131.27 | 22.92 | 0.00 | 0.00 | 0.00 |
September | 107.74 | 57.38 | 50.37 | 131.41 | 34.90 | 0.00 | 0.00 | 0.00 |
October | 92.06 | 54.17 | 37.89 | 100.22 | 50.10 | 0.00 | 0.00 | 0.00 |
November | 82.02 | 51.50 | 30.52 | 78.68 | 72.50 | 0.00 | 0.00 | 0.00 |
December | 87.30 | 57.27 | 30.03 | 71.57 | 110.24 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 103.25 | 55.13 | 48.12 | 114.56 | 57.48 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 82.02 | 22.85 | 30.03 | 71.57 | 19.38 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 143.17 | 96.74 | 64.35 | 144.29 | 113.67 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 113.07 | 78.69 | 34.38 | 100.44 | 113.67 | 0.00 | 0.00 | 0.00 |
February | 143.17 | 96.74 | 46.43 | 144.29 | 94.07 | 0.00 | 0.00 | 0.00 |
March | 126.09 | 79.81 | 46.28 | 130.93 | 76.55 | 0.00 | 0.00 | 0.00 |
April | 114.13 | 61.92 | 52.22 | 130.43 | 49.29 | 0.00 | 0.00 | 0.00 |
May | 95.90 | 32.71 | 63.19 | 118.96 | 28.09 | 0.00 | 0.00 | 0.00 |
June | 86.04 | 22.85 | 63.19 | 112.41 | 19.89 | 0.00 | 0.00 | 0.00 |
July | 94.07 | 29.72 | 64.35 | 126.85 | 19.38 | 0.00 | 0.00 | 0.00 |
August | 100.51 | 41.99 | 58.52 | 131.27 | 22.92 | 0.00 | 0.00 | 0.00 |
September | 107.74 | 57.38 | 50.37 | 131.41 | 34.90 | 0.00 | 0.00 | 0.00 |
October | 92.06 | 54.17 | 37.89 | 100.22 | 50.10 | 0.00 | 0.00 | 0.00 |
November | 82.02 | 51.50 | 30.52 | 78.68 | 72.50 | 0.00 | 0.00 | 0.00 |
December | 87.30 | 57.27 | 30.03 | 71.57 | 110.24 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 103.25 | 55.13 | 48.12 | 114.56 | 57.48 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 82.02 | 22.85 | 30.03 | 71.57 | 19.38 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 143.17 | 96.74 | 64.35 | 144.29 | 113.67 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 135.19 | 94.08 | 41.11 | 120.65 | 134.36 | 0.00 | 0.00 | 0.00 |
February | 171.17 | 115.66 | 55.52 | 173.15 | 111.26 | 0.00 | 0.00 | 0.00 |
March | 150.75 | 95.42 | 55.33 | 156.95 | 90.58 | 0.00 | 0.00 | 0.00 |
April | 136.46 | 74.03 | 62.43 | 156.24 | 58.40 | 0.00 | 0.00 | 0.00 |
May | 114.66 | 39.11 | 75.55 | 142.36 | 33.36 | 0.00 | 0.00 | 0.00 |
June | 102.87 | 27.32 | 75.55 | 134.43 | 23.66 | 0.00 | 0.00 | 0.00 |
July | 112.47 | 35.53 | 76.94 | 151.64 | 23.07 | 0.00 | 0.00 | 0.00 |
August | 120.17 | 50.20 | 69.96 | 157.03 | 27.24 | 0.00 | 0.00 | 0.00 |
September | 128.81 | 68.60 | 60.22 | 157.31 | 41.40 | 0.00 | 0.00 | 0.00 |
October | 110.07 | 64.76 | 45.31 | 120.09 | 59.38 | 0.00 | 0.00 | 0.00 |
November | 98.06 | 61.57 | 36.49 | 94.44 | 85.76 | 0.00 | 0.00 | 0.00 |
December | 104.38 | 68.47 | 35.91 | 86.04 | 130.22 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 123.44 | 65.91 | 57.53 | 137.25 | 68.05 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 98.06 | 27.32 | 35.91 | 86.04 | 23.07 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 171.17 | 115.66 | 76.94 | 173.15 | 134.36 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 113.07 | 78.69 | 34.38 | 100.55 | 113.01 | 0.00 | 0.00 | 0.00 |
February | 143.17 | 96.74 | 46.43 | 144.47 | 93.28 | 0.00 | 0.00 | 0.00 |
March | 126.09 | 79.81 | 46.28 | 131.14 | 75.64 | 0.00 | 0.00 | 0.00 |
April | 114.13 | 61.92 | 52.22 | 130.79 | 48.30 | 0.00 | 0.00 | 0.00 |
May | 95.90 | 32.71 | 63.19 | 119.50 | 27.32 | 0.00 | 0.00 | 0.00 |
June | 86.04 | 22.85 | 63.19 | 112.92 | 19.32 | 0.00 | 0.00 | 0.00 |
July | 94.07 | 29.72 | 64.35 | 127.06 | 19.09 | 0.00 | 0.00 | 0.00 |
August | 100.51 | 41.99 | 58.52 | 131.48 | 22.58 | 0.00 | 0.00 | 0.00 |
September | 107.74 | 57.38 | 50.37 | 131.71 | 34.33 | 0.00 | 0.00 | 0.00 |
October | 92.06 | 54.17 | 37.89 | 100.44 | 49.42 | 0.00 | 0.00 | 0.00 |
November | 82.02 | 51.50 | 30.52 | 78.86 | 71.67 | 0.00 | 0.00 | 0.00 |
December | 87.30 | 57.27 | 30.03 | 71.68 | 109.51 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 103.25 | 55.13 | 48.12 | 114.82 | 56.81 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 82.02 | 22.85 | 30.03 | 71.68 | 19.09 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 143.17 | 96.74 | 64.35 | 144.47 | 113.01 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 113.07 | 78.69 | 34.38 | 100.55 | 113.01 | 0.00 | 0.00 | 0.00 |
February | 143.17 | 96.74 | 46.43 | 144.47 | 93.28 | 0.00 | 0.00 | 0.00 |
March | 126.09 | 79.81 | 46.28 | 131.14 | 75.64 | 0.00 | 0.00 | 0.00 |
April | 114.13 | 61.92 | 52.22 | 130.79 | 48.30 | 0.00 | 0.00 | 0.00 |
May | 95.90 | 32.71 | 63.19 | 119.50 | 27.32 | 0.00 | 0.00 | 0.00 |
June | 86.04 | 22.85 | 63.19 | 112.92 | 19.32 | 0.00 | 0.00 | 0.00 |
July | 94.07 | 29.72 | 64.35 | 127.06 | 19.09 | 0.00 | 0.00 | 0.00 |
August | 100.51 | 41.99 | 58.52 | 131.48 | 22.58 | 0.00 | 0.00 | 0.00 |
September | 107.74 | 57.38 | 50.37 | 131.71 | 34.33 | 0.00 | 0.00 | 0.00 |
October | 92.06 | 54.17 | 37.89 | 100.44 | 49.42 | 0.00 | 0.00 | 0.00 |
November | 82.02 | 51.50 | 30.52 | 78.86 | 71.67 | 0.00 | 0.00 | 0.00 |
December | 87.30 | 57.27 | 30.03 | 71.68 | 109.51 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 103.25 | 55.13 | 48.12 | 114.82 | 56.81 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 82.02 | 22.85 | 30.03 | 71.68 | 19.09 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 143.17 | 96.74 | 64.35 | 144.47 | 113.01 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 135.19 | 94.08 | 41.11 | 120.79 | 133.57 | 0.00 | 0.00 | 0.00 |
February | 171.17 | 115.66 | 55.52 | 173.37 | 110.32 | 0.00 | 0.00 | 0.00 |
March | 150.75 | 95.42 | 55.33 | 157.21 | 89.50 | 0.00 | 0.00 | 0.00 |
April | 136.46 | 74.03 | 62.43 | 156.68 | 57.23 | 0.00 | 0.00 | 0.00 |
May | 114.66 | 39.11 | 75.55 | 143.02 | 32.46 | 0.00 | 0.00 | 0.00 |
June | 102.87 | 27.32 | 75.55 | 135.04 | 22.99 | 0.00 | 0.00 | 0.00 |
July | 112.47 | 35.53 | 76.94 | 151.90 | 22.72 | 0.00 | 0.00 | 0.00 |
August | 120.17 | 50.20 | 69.96 | 157.27 | 26.83 | 0.00 | 0.00 | 0.00 |
September | 128.81 | 68.60 | 60.22 | 157.66 | 40.73 | 0.00 | 0.00 | 0.00 |
October | 110.07 | 64.76 | 45.31 | 120.35 | 58.58 | 0.00 | 0.00 | 0.00 |
November | 98.06 | 61.57 | 36.49 | 94.66 | 84.77 | 0.00 | 0.00 | 0.00 |
December | 104.38 | 68.47 | 35.91 | 86.17 | 129.36 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 123.44 | 65.91 | 57.53 | 137.57 | 67.24 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 98.06 | 27.32 | 35.91 | 86.17 | 22.72 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 171.17 | 115.66 | 76.94 | 173.37 | 133.57 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 113.07 | 78.69 | 34.38 | 101.30 | 109.65 | 0.00 | 0.00 | 0.00 |
February | 143.17 | 96.74 | 46.43 | 145.38 | 89.75 | 0.00 | 0.00 | 0.00 |
March | 126.09 | 79.81 | 46.28 | 132.11 | 71.60 | 0.00 | 0.00 | 0.00 |
April | 114.13 | 61.92 | 52.22 | 131.98 | 44.39 | 0.00 | 0.00 | 0.00 |
May | 95.90 | 32.71 | 63.19 | 121.00 | 24.79 | 0.00 | 0.00 | 0.00 |
June | 86.04 | 22.85 | 63.19 | 114.15 | 17.54 | 0.00 | 0.00 | 0.00 |
July | 94.07 | 29.72 | 64.35 | 127.64 | 17.98 | 0.00 | 0.00 | 0.00 |
August | 100.51 | 41.99 | 58.52 | 132.00 | 21.37 | 0.00 | 0.00 | 0.00 |
September | 107.74 | 57.38 | 50.37 | 132.40 | 32.52 | 0.00 | 0.00 | 0.00 |
October | 92.06 | 54.17 | 37.89 | 101.11 | 46.94 | 0.00 | 0.00 | 0.00 |
November | 82.02 | 51.50 | 30.52 | 79.56 | 68.21 | 0.00 | 0.00 | 0.00 |
December | 87.30 | 57.27 | 30.03 | 72.29 | 105.99 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 103.25 | 55.13 | 48.12 | 115.68 | 54.09 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 82.02 | 22.85 | 30.03 | 72.29 | 17.54 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 143.17 | 96.74 | 64.35 | 145.38 | 109.65 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 113.07 | 78.69 | 34.38 | 101.30 | 109.65 | 0.00 | 0.00 | 0.00 |
February | 143.17 | 96.74 | 46.43 | 145.38 | 89.75 | 0.00 | 0.00 | 0.00 |
March | 126.09 | 79.81 | 46.28 | 132.11 | 71.60 | 0.00 | 0.00 | 0.00 |
April | 114.13 | 61.92 | 52.22 | 131.98 | 44.39 | 0.00 | 0.00 | 0.00 |
May | 95.90 | 32.71 | 63.19 | 121.00 | 24.79 | 0.00 | 0.00 | 0.00 |
June | 86.04 | 22.85 | 63.19 | 114.15 | 17.54 | 0.00 | 0.00 | 0.00 |
July | 94.07 | 29.72 | 64.35 | 127.64 | 17.98 | 0.00 | 0.00 | 0.00 |
August | 100.51 | 41.99 | 58.52 | 132.00 | 21.37 | 0.00 | 0.00 | 0.00 |
September | 107.74 | 57.38 | 50.37 | 132.40 | 32.52 | 0.00 | 0.00 | 0.00 |
October | 92.06 | 54.17 | 37.89 | 101.11 | 46.94 | 0.00 | 0.00 | 0.00 |
November | 82.02 | 51.50 | 30.52 | 79.56 | 68.21 | 0.00 | 0.00 | 0.00 |
December | 87.30 | 57.27 | 30.03 | 72.29 | 105.99 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 103.25 | 55.13 | 48.12 | 115.68 | 54.09 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 82.02 | 22.85 | 30.03 | 72.29 | 17.54 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 143.17 | 96.74 | 64.35 | 145.38 | 109.65 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 135.19 | 94.08 | 41.11 | 121.71 | 129.56 | 0.00 | 0.00 | 0.00 |
February | 171.17 | 115.66 | 55.52 | 174.47 | 106.11 | 0.00 | 0.00 | 0.00 |
March | 150.75 | 95.42 | 55.33 | 158.39 | 84.70 | 0.00 | 0.00 | 0.00 |
April | 136.46 | 74.03 | 62.43 | 158.12 | 52.60 | 0.00 | 0.00 | 0.00 |
May | 114.66 | 39.11 | 75.55 | 144.81 | 29.46 | 0.00 | 0.00 | 0.00 |
June | 102.87 | 27.32 | 75.55 | 136.51 | 20.87 | 0.00 | 0.00 | 0.00 |
July | 112.47 | 35.53 | 76.94 | 152.59 | 21.41 | 0.00 | 0.00 | 0.00 |
August | 120.17 | 50.20 | 69.96 | 157.90 | 25.41 | 0.00 | 0.00 | 0.00 |
September | 128.81 | 68.60 | 60.22 | 158.49 | 38.59 | 0.00 | 0.00 | 0.00 |
October | 110.07 | 64.76 | 45.31 | 121.16 | 55.64 | 0.00 | 0.00 | 0.00 |
November | 98.06 | 61.57 | 36.49 | 95.51 | 80.68 | 0.00 | 0.00 | 0.00 |
December | 104.38 | 68.47 | 35.91 | 86.93 | 125.16 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 123.44 | 65.91 | 57.53 | 138.61 | 64.01 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 98.06 | 27.32 | 35.91 | 86.93 | 20.87 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 171.17 | 115.66 | 76.94 | 174.47 | 129.56 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.302858E+09 | 0.210765E+09 | 92093031.39 | 0.270208E+09 | 0.308580E+09 |
February | 0.346363E+09 | 0.234030E+09 | 0.112333E+09 | 0.350266E+09 | 0.230516E+09 |
March | 0.337723E+09 | 0.213765E+09 | 0.123958E+09 | 0.351993E+09 | 0.207261E+09 |
April | 0.295836E+09 | 0.160488E+09 | 0.135347E+09 | 0.337533E+09 | 0.132459E+09 |
May | 0.256871E+09 | 87622647.49 | 0.169249E+09 | 0.315588E+09 | 80164210.94 |
June | 0.223021E+09 | 59233638.45 | 0.163787E+09 | 0.289849E+09 | 53608712.90 |
July | 0.251953E+09 | 79589879.61 | 0.172364E+09 | 0.340824E+09 | 51082773.69 |
August | 0.269199E+09 | 0.112471E+09 | 0.156728E+09 | 0.351943E+09 | 61304335.70 |
September | 0.279264E+09 | 0.148717E+09 | 0.130546E+09 | 0.337732E+09 | 95817840.44 |
October | 0.246573E+09 | 0.145076E+09 | 0.101497E+09 | 0.265906E+09 | 0.142684E+09 |
November | 0.212599E+09 | 0.133485E+09 | 79113904.12 | 0.204103E+09 | 0.192293E+09 |
December | 0.233830E+09 | 0.153385E+09 | 80445064.04 | 0.192574E+09 | 0.299026E+09 |
Annual Sum or Average | 0.325609E+10 | 0.173863E+10 | 0.151746E+10 | 0.360852E+10 | 0.185480E+10 |
Minimum of Months | 0.212599E+09 | 59233638.45 | 79113904.12 | 0.192574E+09 | 51082773.69 |
Maximum of Months | 0.346363E+09 | 0.234030E+09 | 0.172364E+09 | 0.351993E+09 | 0.308580E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.302858E+09 | 0.210765E+09 | 92093031.39 | 0.270208E+09 | 0.308580E+09 |
February | 0.346363E+09 | 0.234030E+09 | 0.112333E+09 | 0.350266E+09 | 0.230516E+09 |
March | 0.337723E+09 | 0.213765E+09 | 0.123958E+09 | 0.351993E+09 | 0.207261E+09 |
April | 0.295836E+09 | 0.160488E+09 | 0.135347E+09 | 0.337533E+09 | 0.132459E+09 |
May | 0.256871E+09 | 87622647.49 | 0.169249E+09 | 0.315588E+09 | 80164210.94 |
June | 0.223021E+09 | 59233638.45 | 0.163787E+09 | 0.289849E+09 | 53608712.90 |
July | 0.251953E+09 | 79589879.61 | 0.172364E+09 | 0.340824E+09 | 51082773.69 |
August | 0.269199E+09 | 0.112471E+09 | 0.156728E+09 | 0.351943E+09 | 61304335.70 |
September | 0.279264E+09 | 0.148717E+09 | 0.130546E+09 | 0.337732E+09 | 95817840.44 |
October | 0.246573E+09 | 0.145076E+09 | 0.101497E+09 | 0.265906E+09 | 0.142684E+09 |
November | 0.212599E+09 | 0.133485E+09 | 79113904.12 | 0.204103E+09 | 0.192293E+09 |
December | 0.233830E+09 | 0.153385E+09 | 80445064.04 | 0.192574E+09 | 0.299026E+09 |
Annual Sum or Average | 0.325609E+10 | 0.173863E+10 | 0.151746E+10 | 0.360852E+10 | 0.185480E+10 |
Minimum of Months | 0.212599E+09 | 59233638.45 | 79113904.12 | 0.192574E+09 | 51082773.69 |
Maximum of Months | 0.346363E+09 | 0.234030E+09 | 0.172364E+09 | 0.351993E+09 | 0.308580E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.302858E+09 | 0.210765E+09 | 92093031.39 | 0.270208E+09 | 0.308580E+09 |
February | 0.346363E+09 | 0.234030E+09 | 0.112333E+09 | 0.350266E+09 | 0.230516E+09 |
March | 0.337723E+09 | 0.213765E+09 | 0.123958E+09 | 0.351993E+09 | 0.207261E+09 |
April | 0.295836E+09 | 0.160488E+09 | 0.135347E+09 | 0.337533E+09 | 0.132459E+09 |
May | 0.256871E+09 | 87622647.49 | 0.169249E+09 | 0.315588E+09 | 80164210.94 |
June | 0.223021E+09 | 59233638.45 | 0.163787E+09 | 0.289849E+09 | 53608712.90 |
July | 0.251953E+09 | 79589879.61 | 0.172364E+09 | 0.340824E+09 | 51082773.69 |
August | 0.269199E+09 | 0.112471E+09 | 0.156728E+09 | 0.351943E+09 | 61304335.70 |
September | 0.279264E+09 | 0.148717E+09 | 0.130546E+09 | 0.337732E+09 | 95817840.44 |
October | 0.246573E+09 | 0.145076E+09 | 0.101497E+09 | 0.265906E+09 | 0.142684E+09 |
November | 0.212599E+09 | 0.133485E+09 | 79113904.12 | 0.204103E+09 | 0.192293E+09 |
December | 0.233830E+09 | 0.153385E+09 | 80445064.04 | 0.192574E+09 | 0.299026E+09 |
Annual Sum or Average | 0.325609E+10 | 0.173863E+10 | 0.151746E+10 | 0.360852E+10 | 0.185480E+10 |
Minimum of Months | 0.212599E+09 | 59233638.45 | 79113904.12 | 0.192574E+09 | 51082773.69 |
Maximum of Months | 0.346363E+09 | 0.234030E+09 | 0.172364E+09 | 0.351993E+09 | 0.308580E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.302858E+09 | 0.210765E+09 | 92093031.39 | 0.270208E+09 | 0.308580E+09 |
February | 0.346363E+09 | 0.234030E+09 | 0.112333E+09 | 0.350266E+09 | 0.230516E+09 |
March | 0.337723E+09 | 0.213765E+09 | 0.123958E+09 | 0.351993E+09 | 0.207261E+09 |
April | 0.295836E+09 | 0.160488E+09 | 0.135347E+09 | 0.337533E+09 | 0.132459E+09 |
May | 0.256871E+09 | 87622647.49 | 0.169249E+09 | 0.315588E+09 | 80164210.94 |
June | 0.223021E+09 | 59233638.45 | 0.163787E+09 | 0.289849E+09 | 53608712.90 |
July | 0.251953E+09 | 79589879.61 | 0.172364E+09 | 0.340824E+09 | 51082773.69 |
August | 0.269199E+09 | 0.112471E+09 | 0.156728E+09 | 0.351943E+09 | 61304335.70 |
September | 0.279264E+09 | 0.148717E+09 | 0.130546E+09 | 0.337732E+09 | 95817840.44 |
October | 0.246573E+09 | 0.145076E+09 | 0.101497E+09 | 0.265906E+09 | 0.142684E+09 |
November | 0.212599E+09 | 0.133485E+09 | 79113904.12 | 0.204103E+09 | 0.192293E+09 |
December | 0.233830E+09 | 0.153385E+09 | 80445064.04 | 0.192574E+09 | 0.299026E+09 |
Annual Sum or Average | 0.325609E+10 | 0.173863E+10 | 0.151746E+10 | 0.360852E+10 | 0.185480E+10 |
Minimum of Months | 0.212599E+09 | 59233638.45 | 79113904.12 | 0.192574E+09 | 51082773.69 |
Maximum of Months | 0.346363E+09 | 0.234030E+09 | 0.172364E+09 | 0.351993E+09 | 0.308580E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.364082E+09 | 0.253372E+09 | 0.110710E+09 | 0.326255E+09 | 0.366818E+09 |
February | 0.416382E+09 | 0.281340E+09 | 0.135041E+09 | 0.422502E+09 | 0.274181E+09 |
March | 0.405996E+09 | 0.256979E+09 | 0.149017E+09 | 0.424167E+09 | 0.246648E+09 |
April | 0.355640E+09 | 0.192932E+09 | 0.162708E+09 | 0.406482E+09 | 0.157820E+09 |
May | 0.308799E+09 | 0.105336E+09 | 0.203463E+09 | 0.379712E+09 | 95724333.15 |
June | 0.268105E+09 | 71207952.49 | 0.196897E+09 | 0.348481E+09 | 64131900.72 |
July | 0.302887E+09 | 95679288.23 | 0.207208E+09 | 0.409591E+09 | 61178225.32 |
August | 0.323619E+09 | 0.135208E+09 | 0.188412E+09 | 0.423213E+09 | 73299786.09 |
September | 0.335718E+09 | 0.178781E+09 | 0.156937E+09 | 0.406462E+09 | 0.114325E+09 |
October | 0.296419E+09 | 0.174404E+09 | 0.122015E+09 | 0.320289E+09 | 0.170088E+09 |
November | 0.255576E+09 | 0.160469E+09 | 95107092.41 | 0.246243E+09 | 0.228785E+09 |
December | 0.281099E+09 | 0.184392E+09 | 96707351.57 | 0.232708E+09 | 0.355267E+09 |
Annual Sum or Average | 0.391432E+10 | 0.209010E+10 | 0.182422E+10 | 0.434610E+10 | 0.220827E+10 |
Minimum of Months | 0.255576E+09 | 71207952.49 | 95107092.41 | 0.232708E+09 | 61178225.32 |
Maximum of Months | 0.416382E+09 | 0.281340E+09 | 0.207208E+09 | 0.424167E+09 | 0.366818E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.364082E+09 | 0.253372E+09 | 0.110710E+09 | 0.326255E+09 | 0.366818E+09 |
February | 0.416382E+09 | 0.281340E+09 | 0.135041E+09 | 0.422502E+09 | 0.274181E+09 |
March | 0.405996E+09 | 0.256979E+09 | 0.149017E+09 | 0.424167E+09 | 0.246648E+09 |
April | 0.355640E+09 | 0.192932E+09 | 0.162708E+09 | 0.406482E+09 | 0.157820E+09 |
May | 0.308799E+09 | 0.105336E+09 | 0.203463E+09 | 0.379712E+09 | 95724333.15 |
June | 0.268105E+09 | 71207952.49 | 0.196897E+09 | 0.348481E+09 | 64131900.72 |
July | 0.302887E+09 | 95679288.23 | 0.207208E+09 | 0.409591E+09 | 61178225.32 |
August | 0.323619E+09 | 0.135208E+09 | 0.188412E+09 | 0.423213E+09 | 73299786.09 |
September | 0.335718E+09 | 0.178781E+09 | 0.156937E+09 | 0.406462E+09 | 0.114325E+09 |
October | 0.296419E+09 | 0.174404E+09 | 0.122015E+09 | 0.320289E+09 | 0.170088E+09 |
November | 0.255576E+09 | 0.160469E+09 | 95107092.41 | 0.246243E+09 | 0.228785E+09 |
December | 0.281099E+09 | 0.184392E+09 | 96707351.57 | 0.232708E+09 | 0.355267E+09 |
Annual Sum or Average | 0.391432E+10 | 0.209010E+10 | 0.182422E+10 | 0.434610E+10 | 0.220827E+10 |
Minimum of Months | 0.255576E+09 | 71207952.49 | 95107092.41 | 0.232708E+09 | 61178225.32 |
Maximum of Months | 0.416382E+09 | 0.281340E+09 | 0.207208E+09 | 0.424167E+09 | 0.366818E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.302858E+09 | 0.210765E+09 | 92093031.39 | 0.267576E+09 | 0.317188E+09 |
February | 0.346363E+09 | 0.234030E+09 | 0.112333E+09 | 0.347222E+09 | 0.238303E+09 |
March | 0.337723E+09 | 0.213765E+09 | 0.123958E+09 | 0.348930E+09 | 0.215827E+09 |
April | 0.295836E+09 | 0.160488E+09 | 0.135347E+09 | 0.335072E+09 | 0.138881E+09 |
May | 0.256871E+09 | 87622647.49 | 0.169249E+09 | 0.314324E+09 | 82551942.08 |
June | 0.223021E+09 | 59233638.45 | 0.163787E+09 | 0.288576E+09 | 55192237.45 |
July | 0.251953E+09 | 79589879.61 | 0.172364E+09 | 0.340007E+09 | 52157908.33 |
August | 0.269199E+09 | 0.112471E+09 | 0.156728E+09 | 0.351251E+09 | 62473191.22 |
September | 0.279264E+09 | 0.148717E+09 | 0.130546E+09 | 0.337846E+09 | 96685292.69 |
October | 0.246573E+09 | 0.145076E+09 | 0.101497E+09 | 0.265495E+09 | 0.145430E+09 |
November | 0.212599E+09 | 0.133485E+09 | 79113904.12 | 0.202148E+09 | 0.199554E+09 |
December | 0.233830E+09 | 0.153385E+09 | 80445064.04 | 0.190436E+09 | 0.307807E+09 |
Annual Sum or Average | 0.325609E+10 | 0.173863E+10 | 0.151746E+10 | 0.358889E+10 | 0.191205E+10 |
Minimum of Months | 0.212599E+09 | 59233638.45 | 79113904.12 | 0.190436E+09 | 52157908.33 |
Maximum of Months | 0.346363E+09 | 0.234030E+09 | 0.172364E+09 | 0.351251E+09 | 0.317188E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.302858E+09 | 0.210765E+09 | 92093031.39 | 0.267576E+09 | 0.317188E+09 |
February | 0.346363E+09 | 0.234030E+09 | 0.112333E+09 | 0.347222E+09 | 0.238303E+09 |
March | 0.337723E+09 | 0.213765E+09 | 0.123958E+09 | 0.348930E+09 | 0.215827E+09 |
April | 0.295836E+09 | 0.160488E+09 | 0.135347E+09 | 0.335072E+09 | 0.138881E+09 |
May | 0.256871E+09 | 87622647.49 | 0.169249E+09 | 0.314324E+09 | 82551942.08 |
June | 0.223021E+09 | 59233638.45 | 0.163787E+09 | 0.288576E+09 | 55192237.45 |
July | 0.251953E+09 | 79589879.61 | 0.172364E+09 | 0.340007E+09 | 52157908.33 |
August | 0.269199E+09 | 0.112471E+09 | 0.156728E+09 | 0.351251E+09 | 62473191.22 |
September | 0.279264E+09 | 0.148717E+09 | 0.130546E+09 | 0.337846E+09 | 96685292.69 |
October | 0.246573E+09 | 0.145076E+09 | 0.101497E+09 | 0.265495E+09 | 0.145430E+09 |
November | 0.212599E+09 | 0.133485E+09 | 79113904.12 | 0.202148E+09 | 0.199554E+09 |
December | 0.233830E+09 | 0.153385E+09 | 80445064.04 | 0.190436E+09 | 0.307807E+09 |
Annual Sum or Average | 0.325609E+10 | 0.173863E+10 | 0.151746E+10 | 0.358889E+10 | 0.191205E+10 |
Minimum of Months | 0.212599E+09 | 59233638.45 | 79113904.12 | 0.190436E+09 | 52157908.33 |
Maximum of Months | 0.346363E+09 | 0.234030E+09 | 0.172364E+09 | 0.351251E+09 | 0.317188E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.364082E+09 | 0.253372E+09 | 0.110710E+09 | 0.323143E+09 | 0.376983E+09 |
February | 0.416382E+09 | 0.281340E+09 | 0.135041E+09 | 0.418913E+09 | 0.283384E+09 |
March | 0.405996E+09 | 0.256979E+09 | 0.149017E+09 | 0.420523E+09 | 0.256802E+09 |
April | 0.355640E+09 | 0.192932E+09 | 0.162708E+09 | 0.403551E+09 | 0.165418E+09 |
May | 0.308799E+09 | 0.105336E+09 | 0.203463E+09 | 0.378214E+09 | 98550338.06 |
June | 0.268105E+09 | 71207952.49 | 0.196897E+09 | 0.346974E+09 | 66017770.24 |
July | 0.302887E+09 | 95679288.23 | 0.207208E+09 | 0.408641E+09 | 62458162.37 |
August | 0.323619E+09 | 0.135208E+09 | 0.188412E+09 | 0.422426E+09 | 74679406.26 |
September | 0.335718E+09 | 0.178781E+09 | 0.156937E+09 | 0.406636E+09 | 0.115327E+09 |
October | 0.296419E+09 | 0.174404E+09 | 0.122015E+09 | 0.319822E+09 | 0.173300E+09 |
November | 0.255576E+09 | 0.160469E+09 | 95107092.41 | 0.243926E+09 | 0.237349E+09 |
December | 0.281099E+09 | 0.184392E+09 | 96707351.57 | 0.230164E+09 | 0.365608E+09 |
Annual Sum or Average | 0.391432E+10 | 0.209010E+10 | 0.182422E+10 | 0.432293E+10 | 0.227587E+10 |
Minimum of Months | 0.255576E+09 | 71207952.49 | 95107092.41 | 0.230164E+09 | 62458162.37 |
Maximum of Months | 0.416382E+09 | 0.281340E+09 | 0.207208E+09 | 0.422426E+09 | 0.376983E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.302858E+09 | 0.210765E+09 | 92093031.39 | 0.267963E+09 | 0.312266E+09 |
February | 0.346363E+09 | 0.234030E+09 | 0.112333E+09 | 0.347504E+09 | 0.234738E+09 |
March | 0.337723E+09 | 0.213765E+09 | 0.123958E+09 | 0.349082E+09 | 0.212715E+09 |
April | 0.295836E+09 | 0.160488E+09 | 0.135347E+09 | 0.335733E+09 | 0.135657E+09 |
May | 0.256871E+09 | 87622647.49 | 0.169249E+09 | 0.315196E+09 | 81913263.78 |
June | 0.223021E+09 | 59233638.45 | 0.163787E+09 | 0.288592E+09 | 56486947.70 |
July | 0.251953E+09 | 79589879.61 | 0.172364E+09 | 0.339099E+09 | 55111541.57 |
August | 0.269199E+09 | 0.112471E+09 | 0.156728E+09 | 0.350930E+09 | 65066849.29 |
September | 0.279264E+09 | 0.148717E+09 | 0.130546E+09 | 0.338726E+09 | 96275037.12 |
October | 0.246573E+09 | 0.145076E+09 | 0.101497E+09 | 0.266562E+09 | 0.141386E+09 |
November | 0.212599E+09 | 0.133485E+09 | 79113904.12 | 0.202570E+09 | 0.195847E+09 |
December | 0.233830E+09 | 0.153385E+09 | 80445064.04 | 0.190718E+09 | 0.303142E+09 |
Annual Sum or Average | 0.325609E+10 | 0.173863E+10 | 0.151746E+10 | 0.359267E+10 | 0.189061E+10 |
Minimum of Months | 0.212599E+09 | 59233638.45 | 79113904.12 | 0.190718E+09 | 55111541.57 |
Maximum of Months | 0.346363E+09 | 0.234030E+09 | 0.172364E+09 | 0.350930E+09 | 0.312266E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.302858E+09 | 0.210765E+09 | 92093031.39 | 0.267963E+09 | 0.312266E+09 |
February | 0.346363E+09 | 0.234030E+09 | 0.112333E+09 | 0.347504E+09 | 0.234738E+09 |
March | 0.337723E+09 | 0.213765E+09 | 0.123958E+09 | 0.349082E+09 | 0.212715E+09 |
April | 0.295836E+09 | 0.160488E+09 | 0.135347E+09 | 0.335733E+09 | 0.135657E+09 |
May | 0.256871E+09 | 87622647.49 | 0.169249E+09 | 0.315196E+09 | 81913263.78 |
June | 0.223021E+09 | 59233638.45 | 0.163787E+09 | 0.288592E+09 | 56486947.70 |
July | 0.251953E+09 | 79589879.61 | 0.172364E+09 | 0.339099E+09 | 55111541.57 |
August | 0.269199E+09 | 0.112471E+09 | 0.156728E+09 | 0.350930E+09 | 65066849.29 |
September | 0.279264E+09 | 0.148717E+09 | 0.130546E+09 | 0.338726E+09 | 96275037.12 |
October | 0.246573E+09 | 0.145076E+09 | 0.101497E+09 | 0.266562E+09 | 0.141386E+09 |
November | 0.212599E+09 | 0.133485E+09 | 79113904.12 | 0.202570E+09 | 0.195847E+09 |
December | 0.233830E+09 | 0.153385E+09 | 80445064.04 | 0.190718E+09 | 0.303142E+09 |
Annual Sum or Average | 0.325609E+10 | 0.173863E+10 | 0.151746E+10 | 0.359267E+10 | 0.189061E+10 |
Minimum of Months | 0.212599E+09 | 59233638.45 | 79113904.12 | 0.190718E+09 | 55111541.57 |
Maximum of Months | 0.346363E+09 | 0.234030E+09 | 0.172364E+09 | 0.350930E+09 | 0.312266E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.362093E+09 | 0.251988E+09 | 0.110105E+09 | 0.321850E+09 | 0.369137E+09 |
February | 0.414106E+09 | 0.279803E+09 | 0.134304E+09 | 0.416972E+09 | 0.277654E+09 |
March | 0.403777E+09 | 0.255575E+09 | 0.148202E+09 | 0.418413E+09 | 0.251739E+09 |
April | 0.353697E+09 | 0.191878E+09 | 0.161819E+09 | 0.402144E+09 | 0.160733E+09 |
May | 0.307111E+09 | 0.104760E+09 | 0.202351E+09 | 0.377188E+09 | 97249846.74 |
June | 0.266640E+09 | 70818837.99 | 0.195821E+09 | 0.345107E+09 | 67163543.02 |
July | 0.301232E+09 | 95156450.59 | 0.206075E+09 | 0.405340E+09 | 65574696.94 |
August | 0.321851E+09 | 0.134469E+09 | 0.187382E+09 | 0.419742E+09 | 77304140.93 |
September | 0.333883E+09 | 0.177804E+09 | 0.156079E+09 | 0.405464E+09 | 0.114199E+09 |
October | 0.294799E+09 | 0.173451E+09 | 0.121348E+09 | 0.319356E+09 | 0.167590E+09 |
November | 0.254180E+09 | 0.159592E+09 | 94587381.53 | 0.243110E+09 | 0.231698E+09 |
December | 0.279563E+09 | 0.183384E+09 | 96178896.10 | 0.229251E+09 | 0.358129E+09 |
Annual Sum or Average | 0.389293E+10 | 0.207868E+10 | 0.181425E+10 | 0.430394E+10 | 0.223817E+10 |
Minimum of Months | 0.254180E+09 | 70818837.99 | 94587381.53 | 0.229251E+09 | 65574696.94 |
Maximum of Months | 0.414106E+09 | 0.279803E+09 | 0.206075E+09 | 0.419742E+09 | 0.369137E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.302858E+09 | 0.210765E+09 | 92093031.39 | 0.268227E+09 | 0.310263E+09 |
February | 0.346363E+09 | 0.234030E+09 | 0.112333E+09 | 0.347805E+09 | 0.233054E+09 |
March | 0.337723E+09 | 0.213765E+09 | 0.123958E+09 | 0.349371E+09 | 0.211058E+09 |
April | 0.295836E+09 | 0.160488E+09 | 0.135347E+09 | 0.336253E+09 | 0.133910E+09 |
May | 0.256871E+09 | 87622647.49 | 0.169249E+09 | 0.315888E+09 | 80661620.84 |
June | 0.223021E+09 | 59233638.45 | 0.163787E+09 | 0.289029E+09 | 55864423.38 |
July | 0.251953E+09 | 79589879.61 | 0.172364E+09 | 0.339153E+09 | 55033796.36 |
August | 0.269199E+09 | 0.112471E+09 | 0.156728E+09 | 0.351036E+09 | 64842969.86 |
September | 0.279264E+09 | 0.148717E+09 | 0.130546E+09 | 0.339234E+09 | 95090856.26 |
October | 0.246573E+09 | 0.145076E+09 | 0.101497E+09 | 0.267114E+09 | 0.139431E+09 |
November | 0.212599E+09 | 0.133485E+09 | 79113904.12 | 0.202869E+09 | 0.193992E+09 |
December | 0.233830E+09 | 0.153385E+09 | 80445064.04 | 0.190926E+09 | 0.301174E+09 |
Annual Sum or Average | 0.325609E+10 | 0.173863E+10 | 0.151746E+10 | 0.359691E+10 | 0.187438E+10 |
Minimum of Months | 0.212599E+09 | 59233638.45 | 79113904.12 | 0.190926E+09 | 55033796.36 |
Maximum of Months | 0.346363E+09 | 0.234030E+09 | 0.172364E+09 | 0.351036E+09 | 0.310263E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.302858E+09 | 0.210765E+09 | 92093031.39 | 0.268227E+09 | 0.310263E+09 |
February | 0.346363E+09 | 0.234030E+09 | 0.112333E+09 | 0.347805E+09 | 0.233054E+09 |
March | 0.337723E+09 | 0.213765E+09 | 0.123958E+09 | 0.349371E+09 | 0.211058E+09 |
April | 0.295836E+09 | 0.160488E+09 | 0.135347E+09 | 0.336253E+09 | 0.133910E+09 |
May | 0.256871E+09 | 87622647.49 | 0.169249E+09 | 0.315888E+09 | 80661620.84 |
June | 0.223021E+09 | 59233638.45 | 0.163787E+09 | 0.289029E+09 | 55864423.38 |
July | 0.251953E+09 | 79589879.61 | 0.172364E+09 | 0.339153E+09 | 55033796.36 |
August | 0.269199E+09 | 0.112471E+09 | 0.156728E+09 | 0.351036E+09 | 64842969.86 |
September | 0.279264E+09 | 0.148717E+09 | 0.130546E+09 | 0.339234E+09 | 95090856.26 |
October | 0.246573E+09 | 0.145076E+09 | 0.101497E+09 | 0.267114E+09 | 0.139431E+09 |
November | 0.212599E+09 | 0.133485E+09 | 79113904.12 | 0.202869E+09 | 0.193992E+09 |
December | 0.233830E+09 | 0.153385E+09 | 80445064.04 | 0.190926E+09 | 0.301174E+09 |
Annual Sum or Average | 0.325609E+10 | 0.173863E+10 | 0.151746E+10 | 0.359691E+10 | 0.187438E+10 |
Minimum of Months | 0.212599E+09 | 59233638.45 | 79113904.12 | 0.190926E+09 | 55033796.36 |
Maximum of Months | 0.346363E+09 | 0.234030E+09 | 0.172364E+09 | 0.351036E+09 | 0.310263E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.362093E+09 | 0.251988E+09 | 0.110105E+09 | 0.322172E+09 | 0.366755E+09 |
February | 0.414106E+09 | 0.279803E+09 | 0.134304E+09 | 0.417338E+09 | 0.275655E+09 |
March | 0.403777E+09 | 0.255575E+09 | 0.148202E+09 | 0.418764E+09 | 0.249769E+09 |
April | 0.353697E+09 | 0.191878E+09 | 0.161819E+09 | 0.402769E+09 | 0.158659E+09 |
May | 0.307111E+09 | 0.104760E+09 | 0.202351E+09 | 0.378016E+09 | 95768714.14 |
June | 0.266640E+09 | 70818837.99 | 0.195821E+09 | 0.345630E+09 | 66426686.61 |
July | 0.301232E+09 | 95156450.59 | 0.206075E+09 | 0.405406E+09 | 65482479.91 |
August | 0.321851E+09 | 0.134469E+09 | 0.187382E+09 | 0.419869E+09 | 77038715.13 |
September | 0.333883E+09 | 0.177804E+09 | 0.156079E+09 | 0.406072E+09 | 0.112798E+09 |
October | 0.294799E+09 | 0.173451E+09 | 0.121348E+09 | 0.320022E+09 | 0.165271E+09 |
November | 0.254180E+09 | 0.159592E+09 | 94587381.53 | 0.243472E+09 | 0.229495E+09 |
December | 0.279563E+09 | 0.183384E+09 | 96178896.10 | 0.229505E+09 | 0.355789E+09 |
Annual Sum or Average | 0.389293E+10 | 0.207868E+10 | 0.181425E+10 | 0.430904E+10 | 0.221891E+10 |
Minimum of Months | 0.254180E+09 | 70818837.99 | 94587381.53 | 0.229505E+09 | 65482479.91 |
Maximum of Months | 0.414106E+09 | 0.279803E+09 | 0.206075E+09 | 0.419869E+09 | 0.366755E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.302858E+09 | 0.210765E+09 | 92093031.39 | 0.268553E+09 | 0.308771E+09 |
February | 0.346363E+09 | 0.234030E+09 | 0.112333E+09 | 0.348217E+09 | 0.231615E+09 |
March | 0.337723E+09 | 0.213765E+09 | 0.123958E+09 | 0.349804E+09 | 0.209508E+09 |
April | 0.295836E+09 | 0.160488E+09 | 0.135347E+09 | 0.336911E+09 | 0.132341E+09 |
May | 0.256871E+09 | 87622647.49 | 0.169249E+09 | 0.316846E+09 | 79268720.65 |
June | 0.223021E+09 | 59233638.45 | 0.163787E+09 | 0.289819E+09 | 54847855.67 |
July | 0.251953E+09 | 79589879.61 | 0.172364E+09 | 0.339523E+09 | 54401955.72 |
August | 0.269199E+09 | 0.112471E+09 | 0.156728E+09 | 0.351405E+09 | 64093499.87 |
September | 0.279264E+09 | 0.148717E+09 | 0.130546E+09 | 0.339881E+09 | 93807596.93 |
October | 0.246573E+09 | 0.145076E+09 | 0.101497E+09 | 0.267662E+09 | 0.137938E+09 |
November | 0.212599E+09 | 0.133485E+09 | 79113904.12 | 0.203258E+09 | 0.192363E+09 |
December | 0.233830E+09 | 0.153385E+09 | 80445064.04 | 0.191208E+09 | 0.299581E+09 |
Annual Sum or Average | 0.325609E+10 | 0.173863E+10 | 0.151746E+10 | 0.360309E+10 | 0.185854E+10 |
Minimum of Months | 0.212599E+09 | 59233638.45 | 79113904.12 | 0.191208E+09 | 54401955.72 |
Maximum of Months | 0.346363E+09 | 0.234030E+09 | 0.172364E+09 | 0.351405E+09 | 0.308771E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.302858E+09 | 0.210765E+09 | 92093031.39 | 0.268553E+09 | 0.308771E+09 |
February | 0.346363E+09 | 0.234030E+09 | 0.112333E+09 | 0.348217E+09 | 0.231615E+09 |
March | 0.337723E+09 | 0.213765E+09 | 0.123958E+09 | 0.349804E+09 | 0.209508E+09 |
April | 0.295836E+09 | 0.160488E+09 | 0.135347E+09 | 0.336911E+09 | 0.132341E+09 |
May | 0.256871E+09 | 87622647.49 | 0.169249E+09 | 0.316846E+09 | 79268720.65 |
June | 0.223021E+09 | 59233638.45 | 0.163787E+09 | 0.289819E+09 | 54847855.67 |
July | 0.251953E+09 | 79589879.61 | 0.172364E+09 | 0.339523E+09 | 54401955.72 |
August | 0.269199E+09 | 0.112471E+09 | 0.156728E+09 | 0.351405E+09 | 64093499.87 |
September | 0.279264E+09 | 0.148717E+09 | 0.130546E+09 | 0.339881E+09 | 93807596.93 |
October | 0.246573E+09 | 0.145076E+09 | 0.101497E+09 | 0.267662E+09 | 0.137938E+09 |
November | 0.212599E+09 | 0.133485E+09 | 79113904.12 | 0.203258E+09 | 0.192363E+09 |
December | 0.233830E+09 | 0.153385E+09 | 80445064.04 | 0.191208E+09 | 0.299581E+09 |
Annual Sum or Average | 0.325609E+10 | 0.173863E+10 | 0.151746E+10 | 0.360309E+10 | 0.185854E+10 |
Minimum of Months | 0.212599E+09 | 59233638.45 | 79113904.12 | 0.191208E+09 | 54401955.72 |
Maximum of Months | 0.346363E+09 | 0.234030E+09 | 0.172364E+09 | 0.351405E+09 | 0.308771E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.362093E+09 | 0.251988E+09 | 0.110105E+09 | 0.322568E+09 | 0.364980E+09 |
February | 0.414106E+09 | 0.279803E+09 | 0.134304E+09 | 0.417838E+09 | 0.273946E+09 |
March | 0.403777E+09 | 0.255575E+09 | 0.148202E+09 | 0.419290E+09 | 0.247927E+09 |
April | 0.353697E+09 | 0.191878E+09 | 0.161819E+09 | 0.403560E+09 | 0.156800E+09 |
May | 0.307111E+09 | 0.104760E+09 | 0.202351E+09 | 0.379160E+09 | 94124599.08 |
June | 0.266640E+09 | 70818837.99 | 0.195821E+09 | 0.346576E+09 | 65226691.38 |
July | 0.301232E+09 | 95156450.59 | 0.206075E+09 | 0.405850E+09 | 64736994.39 |
August | 0.321851E+09 | 0.134469E+09 | 0.187382E+09 | 0.420312E+09 | 76155676.45 |
September | 0.333883E+09 | 0.177804E+09 | 0.156079E+09 | 0.406846E+09 | 0.111282E+09 |
October | 0.294799E+09 | 0.173451E+09 | 0.121348E+09 | 0.320682E+09 | 0.163502E+09 |
November | 0.254180E+09 | 0.159592E+09 | 94587381.53 | 0.243945E+09 | 0.227563E+09 |
December | 0.279563E+09 | 0.183384E+09 | 96178896.10 | 0.229851E+09 | 0.353896E+09 |
Annual Sum or Average | 0.389293E+10 | 0.207868E+10 | 0.181425E+10 | 0.431648E+10 | 0.220014E+10 |
Minimum of Months | 0.254180E+09 | 70818837.99 | 94587381.53 | 0.229851E+09 | 64736994.39 |
Maximum of Months | 0.414106E+09 | 0.279803E+09 | 0.206075E+09 | 0.420312E+09 | 0.364980E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.302858E+09 | 0.210765E+09 | 92093031.39 | 0.270040E+09 | 0.302843E+09 |
February | 0.346363E+09 | 0.234030E+09 | 0.112333E+09 | 0.350093E+09 | 0.226658E+09 |
March | 0.337723E+09 | 0.213765E+09 | 0.123958E+09 | 0.351458E+09 | 0.204533E+09 |
April | 0.295836E+09 | 0.160488E+09 | 0.135347E+09 | 0.338391E+09 | 0.128317E+09 |
May | 0.256871E+09 | 87622647.49 | 0.169249E+09 | 0.318193E+09 | 76329438.22 |
June | 0.223021E+09 | 59233638.45 | 0.163787E+09 | 0.290778E+09 | 52579807.35 |
July | 0.251953E+09 | 79589879.61 | 0.172364E+09 | 0.339535E+09 | 52666338.63 |
August | 0.269199E+09 | 0.112471E+09 | 0.156728E+09 | 0.351607E+09 | 62178800.63 |
September | 0.279264E+09 | 0.148717E+09 | 0.130546E+09 | 0.340629E+09 | 91320091.52 |
October | 0.246573E+09 | 0.145076E+09 | 0.101497E+09 | 0.268739E+09 | 0.134691E+09 |
November | 0.212599E+09 | 0.133485E+09 | 79113904.12 | 0.204483E+09 | 0.187562E+09 |
December | 0.233830E+09 | 0.153385E+09 | 80445064.04 | 0.192496E+09 | 0.293562E+09 |
Annual Sum or Average | 0.325609E+10 | 0.173863E+10 | 0.151746E+10 | 0.361644E+10 | 0.181324E+10 |
Minimum of Months | 0.212599E+09 | 59233638.45 | 79113904.12 | 0.192496E+09 | 52579807.35 |
Maximum of Months | 0.346363E+09 | 0.234030E+09 | 0.172364E+09 | 0.351607E+09 | 0.302843E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.302858E+09 | 0.210765E+09 | 92093031.39 | 0.270040E+09 | 0.302843E+09 |
February | 0.346363E+09 | 0.234030E+09 | 0.112333E+09 | 0.350093E+09 | 0.226658E+09 |
March | 0.337723E+09 | 0.213765E+09 | 0.123958E+09 | 0.351458E+09 | 0.204533E+09 |
April | 0.295836E+09 | 0.160488E+09 | 0.135347E+09 | 0.338391E+09 | 0.128317E+09 |
May | 0.256871E+09 | 87622647.49 | 0.169249E+09 | 0.318193E+09 | 76329438.22 |
June | 0.223021E+09 | 59233638.45 | 0.163787E+09 | 0.290778E+09 | 52579807.35 |
July | 0.251953E+09 | 79589879.61 | 0.172364E+09 | 0.339535E+09 | 52666338.63 |
August | 0.269199E+09 | 0.112471E+09 | 0.156728E+09 | 0.351607E+09 | 62178800.63 |
September | 0.279264E+09 | 0.148717E+09 | 0.130546E+09 | 0.340629E+09 | 91320091.52 |
October | 0.246573E+09 | 0.145076E+09 | 0.101497E+09 | 0.268739E+09 | 0.134691E+09 |
November | 0.212599E+09 | 0.133485E+09 | 79113904.12 | 0.204483E+09 | 0.187562E+09 |
December | 0.233830E+09 | 0.153385E+09 | 80445064.04 | 0.192496E+09 | 0.293562E+09 |
Annual Sum or Average | 0.325609E+10 | 0.173863E+10 | 0.151746E+10 | 0.361644E+10 | 0.181324E+10 |
Minimum of Months | 0.212599E+09 | 59233638.45 | 79113904.12 | 0.192496E+09 | 52579807.35 |
Maximum of Months | 0.346363E+09 | 0.234030E+09 | 0.172364E+09 | 0.351607E+09 | 0.302843E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.302858E+09 | 0.210765E+09 | 92093031.39 | 0.270040E+09 | 0.302843E+09 |
February | 0.346363E+09 | 0.234030E+09 | 0.112333E+09 | 0.350093E+09 | 0.226658E+09 |
March | 0.337723E+09 | 0.213765E+09 | 0.123958E+09 | 0.351458E+09 | 0.204533E+09 |
April | 0.295836E+09 | 0.160488E+09 | 0.135347E+09 | 0.338391E+09 | 0.128317E+09 |
May | 0.256871E+09 | 87622647.49 | 0.169249E+09 | 0.318193E+09 | 76329438.22 |
June | 0.223021E+09 | 59233638.45 | 0.163787E+09 | 0.290778E+09 | 52579807.35 |
July | 0.251953E+09 | 79589879.61 | 0.172364E+09 | 0.339535E+09 | 52666338.63 |
August | 0.269199E+09 | 0.112471E+09 | 0.156728E+09 | 0.351607E+09 | 62178800.63 |
September | 0.279264E+09 | 0.148717E+09 | 0.130546E+09 | 0.340629E+09 | 91320091.52 |
October | 0.246573E+09 | 0.145076E+09 | 0.101497E+09 | 0.268739E+09 | 0.134691E+09 |
November | 0.212599E+09 | 0.133485E+09 | 79113904.12 | 0.204483E+09 | 0.187562E+09 |
December | 0.233830E+09 | 0.153385E+09 | 80445064.04 | 0.192496E+09 | 0.293562E+09 |
Annual Sum or Average | 0.325609E+10 | 0.173863E+10 | 0.151746E+10 | 0.361644E+10 | 0.181324E+10 |
Minimum of Months | 0.212599E+09 | 59233638.45 | 79113904.12 | 0.192496E+09 | 52579807.35 |
Maximum of Months | 0.346363E+09 | 0.234030E+09 | 0.172364E+09 | 0.351607E+09 | 0.302843E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.302858E+09 | 0.210765E+09 | 92093031.39 | 0.270040E+09 | 0.302843E+09 |
February | 0.346363E+09 | 0.234030E+09 | 0.112333E+09 | 0.350093E+09 | 0.226658E+09 |
March | 0.337723E+09 | 0.213765E+09 | 0.123958E+09 | 0.351458E+09 | 0.204533E+09 |
April | 0.295836E+09 | 0.160488E+09 | 0.135347E+09 | 0.338391E+09 | 0.128317E+09 |
May | 0.256871E+09 | 87622647.49 | 0.169249E+09 | 0.318193E+09 | 76329438.22 |
June | 0.223021E+09 | 59233638.45 | 0.163787E+09 | 0.290778E+09 | 52579807.35 |
July | 0.251953E+09 | 79589879.61 | 0.172364E+09 | 0.339535E+09 | 52666338.63 |
August | 0.269199E+09 | 0.112471E+09 | 0.156728E+09 | 0.351607E+09 | 62178800.63 |
September | 0.279264E+09 | 0.148717E+09 | 0.130546E+09 | 0.340629E+09 | 91320091.52 |
October | 0.246573E+09 | 0.145076E+09 | 0.101497E+09 | 0.268739E+09 | 0.134691E+09 |
November | 0.212599E+09 | 0.133485E+09 | 79113904.12 | 0.204483E+09 | 0.187562E+09 |
December | 0.233830E+09 | 0.153385E+09 | 80445064.04 | 0.192496E+09 | 0.293562E+09 |
Annual Sum or Average | 0.325609E+10 | 0.173863E+10 | 0.151746E+10 | 0.361644E+10 | 0.181324E+10 |
Minimum of Months | 0.212599E+09 | 59233638.45 | 79113904.12 | 0.192496E+09 | 52579807.35 |
Maximum of Months | 0.346363E+09 | 0.234030E+09 | 0.172364E+09 | 0.351607E+09 | 0.302843E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.362093E+09 | 0.251988E+09 | 0.110105E+09 | 0.324285E+09 | 0.358109E+09 |
February | 0.414106E+09 | 0.279803E+09 | 0.134304E+09 | 0.419993E+09 | 0.268185E+09 |
March | 0.403777E+09 | 0.255575E+09 | 0.148202E+09 | 0.421214E+09 | 0.242120E+09 |
April | 0.353697E+09 | 0.191878E+09 | 0.161819E+09 | 0.405279E+09 | 0.152083E+09 |
May | 0.307111E+09 | 0.104760E+09 | 0.202351E+09 | 0.380729E+09 | 90660926.76 |
June | 0.266640E+09 | 70818837.99 | 0.195821E+09 | 0.347698E+09 | 62539562.30 |
July | 0.301232E+09 | 95156450.59 | 0.206075E+09 | 0.405847E+09 | 62680365.72 |
August | 0.321851E+09 | 0.134469E+09 | 0.187382E+09 | 0.420519E+09 | 73895641.50 |
September | 0.333883E+09 | 0.177804E+09 | 0.156079E+09 | 0.407683E+09 | 0.108358E+09 |
October | 0.294799E+09 | 0.173451E+09 | 0.121348E+09 | 0.321926E+09 | 0.159696E+09 |
November | 0.254180E+09 | 0.159592E+09 | 94587381.53 | 0.245370E+09 | 0.221956E+09 |
December | 0.279563E+09 | 0.183384E+09 | 96178896.10 | 0.231347E+09 | 0.346931E+09 |
Annual Sum or Average | 0.389293E+10 | 0.207868E+10 | 0.181425E+10 | 0.433189E+10 | 0.214721E+10 |
Minimum of Months | 0.254180E+09 | 70818837.99 | 94587381.53 | 0.231347E+09 | 62539562.30 |
Maximum of Months | 0.414106E+09 | 0.279803E+09 | 0.206075E+09 | 0.421214E+09 | 0.358109E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.362093E+09 | 0.251988E+09 | 0.110105E+09 | 0.324285E+09 | 0.358109E+09 |
February | 0.414106E+09 | 0.279803E+09 | 0.134304E+09 | 0.419993E+09 | 0.268185E+09 |
March | 0.403777E+09 | 0.255575E+09 | 0.148202E+09 | 0.421214E+09 | 0.242120E+09 |
April | 0.353697E+09 | 0.191878E+09 | 0.161819E+09 | 0.405279E+09 | 0.152083E+09 |
May | 0.307111E+09 | 0.104760E+09 | 0.202351E+09 | 0.380729E+09 | 90660926.76 |
June | 0.266640E+09 | 70818837.99 | 0.195821E+09 | 0.347698E+09 | 62539562.30 |
July | 0.301232E+09 | 95156450.59 | 0.206075E+09 | 0.405847E+09 | 62680365.72 |
August | 0.321851E+09 | 0.134469E+09 | 0.187382E+09 | 0.420519E+09 | 73895641.50 |
September | 0.333883E+09 | 0.177804E+09 | 0.156079E+09 | 0.407683E+09 | 0.108358E+09 |
October | 0.294799E+09 | 0.173451E+09 | 0.121348E+09 | 0.321926E+09 | 0.159696E+09 |
November | 0.254180E+09 | 0.159592E+09 | 94587381.53 | 0.245370E+09 | 0.221956E+09 |
December | 0.279563E+09 | 0.183384E+09 | 96178896.10 | 0.231347E+09 | 0.346931E+09 |
Annual Sum or Average | 0.389293E+10 | 0.207868E+10 | 0.181425E+10 | 0.433189E+10 | 0.214721E+10 |
Minimum of Months | 0.254180E+09 | 70818837.99 | 94587381.53 | 0.231347E+09 | 62539562.30 |
Maximum of Months | 0.414106E+09 | 0.279803E+09 | 0.206075E+09 | 0.421214E+09 | 0.358109E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.302858E+09 | 0.210765E+09 | 92093031.39 | 0.268960E+09 | 0.304688E+09 |
February | 0.346363E+09 | 0.234030E+09 | 0.112333E+09 | 0.348975E+09 | 0.227881E+09 |
March | 0.337723E+09 | 0.213765E+09 | 0.123958E+09 | 0.350540E+09 | 0.205481E+09 |
April | 0.295836E+09 | 0.160488E+09 | 0.135347E+09 | 0.337787E+09 | 0.128426E+09 |
May | 0.256871E+09 | 87622647.49 | 0.169249E+09 | 0.318062E+09 | 75923456.88 |
June | 0.223021E+09 | 59233638.45 | 0.163787E+09 | 0.290845E+09 | 52090573.16 |
July | 0.251953E+09 | 79589879.61 | 0.172364E+09 | 0.339508E+09 | 52197135.93 |
August | 0.269199E+09 | 0.112471E+09 | 0.156728E+09 | 0.351384E+09 | 61735167.81 |
September | 0.279264E+09 | 0.148717E+09 | 0.130546E+09 | 0.340296E+09 | 90994327.17 |
October | 0.246573E+09 | 0.145076E+09 | 0.101497E+09 | 0.268237E+09 | 0.134726E+09 |
November | 0.212599E+09 | 0.133485E+09 | 79113904.12 | 0.203821E+09 | 0.188407E+09 |
December | 0.233830E+09 | 0.153385E+09 | 80445064.04 | 0.191638E+09 | 0.295541E+09 |
Annual Sum or Average | 0.325609E+10 | 0.173863E+10 | 0.151746E+10 | 0.361005E+10 | 0.181809E+10 |
Minimum of Months | 0.212599E+09 | 59233638.45 | 79113904.12 | 0.191638E+09 | 52090573.16 |
Maximum of Months | 0.346363E+09 | 0.234030E+09 | 0.172364E+09 | 0.351384E+09 | 0.304688E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.302858E+09 | 0.210765E+09 | 92093031.39 | 0.268960E+09 | 0.304688E+09 |
February | 0.346363E+09 | 0.234030E+09 | 0.112333E+09 | 0.348975E+09 | 0.227881E+09 |
March | 0.337723E+09 | 0.213765E+09 | 0.123958E+09 | 0.350540E+09 | 0.205481E+09 |
April | 0.295836E+09 | 0.160488E+09 | 0.135347E+09 | 0.337787E+09 | 0.128426E+09 |
May | 0.256871E+09 | 87622647.49 | 0.169249E+09 | 0.318062E+09 | 75923456.88 |
June | 0.223021E+09 | 59233638.45 | 0.163787E+09 | 0.290845E+09 | 52090573.16 |
July | 0.251953E+09 | 79589879.61 | 0.172364E+09 | 0.339508E+09 | 52197135.93 |
August | 0.269199E+09 | 0.112471E+09 | 0.156728E+09 | 0.351384E+09 | 61735167.81 |
September | 0.279264E+09 | 0.148717E+09 | 0.130546E+09 | 0.340296E+09 | 90994327.17 |
October | 0.246573E+09 | 0.145076E+09 | 0.101497E+09 | 0.268237E+09 | 0.134726E+09 |
November | 0.212599E+09 | 0.133485E+09 | 79113904.12 | 0.203821E+09 | 0.188407E+09 |
December | 0.233830E+09 | 0.153385E+09 | 80445064.04 | 0.191638E+09 | 0.295541E+09 |
Annual Sum or Average | 0.325609E+10 | 0.173863E+10 | 0.151746E+10 | 0.361005E+10 | 0.181809E+10 |
Minimum of Months | 0.212599E+09 | 59233638.45 | 79113904.12 | 0.191638E+09 | 52090573.16 |
Maximum of Months | 0.346363E+09 | 0.234030E+09 | 0.172364E+09 | 0.351384E+09 | 0.304688E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.362093E+09 | 0.251988E+09 | 0.110105E+09 | 0.323089E+09 | 0.360150E+09 |
February | 0.414106E+09 | 0.279803E+09 | 0.134304E+09 | 0.418771E+09 | 0.269529E+09 |
March | 0.403777E+09 | 0.255575E+09 | 0.148202E+09 | 0.420207E+09 | 0.243155E+09 |
April | 0.353697E+09 | 0.191878E+09 | 0.161819E+09 | 0.404640E+09 | 0.152166E+09 |
May | 0.307111E+09 | 0.104760E+09 | 0.202351E+09 | 0.380638E+09 | 90166399.52 |
June | 0.266640E+09 | 70818837.99 | 0.195821E+09 | 0.347821E+09 | 61955636.03 |
July | 0.301232E+09 | 95156450.59 | 0.206075E+09 | 0.405863E+09 | 62124245.37 |
August | 0.321851E+09 | 0.134469E+09 | 0.187382E+09 | 0.420315E+09 | 73360578.17 |
September | 0.333883E+09 | 0.177804E+09 | 0.156079E+09 | 0.407361E+09 | 0.107944E+09 |
October | 0.294799E+09 | 0.173451E+09 | 0.121348E+09 | 0.321395E+09 | 0.159689E+09 |
November | 0.254180E+09 | 0.159592E+09 | 94587381.53 | 0.244646E+09 | 0.222872E+09 |
December | 0.279563E+09 | 0.183384E+09 | 96178896.10 | 0.230391E+09 | 0.349112E+09 |
Annual Sum or Average | 0.389293E+10 | 0.207868E+10 | 0.181425E+10 | 0.432514E+10 | 0.215222E+10 |
Minimum of Months | 0.254180E+09 | 70818837.99 | 94587381.53 | 0.230391E+09 | 61955636.03 |
Maximum of Months | 0.414106E+09 | 0.279803E+09 | 0.206075E+09 | 0.420315E+09 | 0.360150E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.302858E+09 | 0.210765E+09 | 92093031.39 | 0.269008E+09 | 0.304452E+09 |
February | 0.346363E+09 | 0.234030E+09 | 0.112333E+09 | 0.349060E+09 | 0.227569E+09 |
March | 0.337723E+09 | 0.213765E+09 | 0.123958E+09 | 0.350670E+09 | 0.205021E+09 |
April | 0.295836E+09 | 0.160488E+09 | 0.135347E+09 | 0.338075E+09 | 0.127758E+09 |
May | 0.256871E+09 | 87622647.49 | 0.169249E+09 | 0.318611E+09 | 75234178.54 |
June | 0.223021E+09 | 59233638.45 | 0.163787E+09 | 0.291372E+09 | 51552036.11 |
July | 0.251953E+09 | 79589879.61 | 0.172364E+09 | 0.339744E+09 | 51916307.45 |
August | 0.269199E+09 | 0.112471E+09 | 0.156728E+09 | 0.351606E+09 | 61395002.08 |
September | 0.279264E+09 | 0.148717E+09 | 0.130546E+09 | 0.340609E+09 | 90454020.01 |
October | 0.246573E+09 | 0.145076E+09 | 0.101497E+09 | 0.268440E+09 | 0.134189E+09 |
November | 0.212599E+09 | 0.133485E+09 | 79113904.12 | 0.203940E+09 | 0.187923E+09 |
December | 0.233830E+09 | 0.153385E+09 | 80445064.04 | 0.191686E+09 | 0.295272E+09 |
Annual Sum or Average | 0.325609E+10 | 0.173863E+10 | 0.151746E+10 | 0.361282E+10 | 0.181274E+10 |
Minimum of Months | 0.212599E+09 | 59233638.45 | 79113904.12 | 0.191686E+09 | 51552036.11 |
Maximum of Months | 0.346363E+09 | 0.234030E+09 | 0.172364E+09 | 0.351606E+09 | 0.304452E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.302858E+09 | 0.210765E+09 | 92093031.39 | 0.269008E+09 | 0.304452E+09 |
February | 0.346363E+09 | 0.234030E+09 | 0.112333E+09 | 0.349060E+09 | 0.227569E+09 |
March | 0.337723E+09 | 0.213765E+09 | 0.123958E+09 | 0.350670E+09 | 0.205021E+09 |
April | 0.295836E+09 | 0.160488E+09 | 0.135347E+09 | 0.338075E+09 | 0.127758E+09 |
May | 0.256871E+09 | 87622647.49 | 0.169249E+09 | 0.318611E+09 | 75234178.54 |
June | 0.223021E+09 | 59233638.45 | 0.163787E+09 | 0.291372E+09 | 51552036.11 |
July | 0.251953E+09 | 79589879.61 | 0.172364E+09 | 0.339744E+09 | 51916307.45 |
August | 0.269199E+09 | 0.112471E+09 | 0.156728E+09 | 0.351606E+09 | 61395002.08 |
September | 0.279264E+09 | 0.148717E+09 | 0.130546E+09 | 0.340609E+09 | 90454020.01 |
October | 0.246573E+09 | 0.145076E+09 | 0.101497E+09 | 0.268440E+09 | 0.134189E+09 |
November | 0.212599E+09 | 0.133485E+09 | 79113904.12 | 0.203940E+09 | 0.187923E+09 |
December | 0.233830E+09 | 0.153385E+09 | 80445064.04 | 0.191686E+09 | 0.295272E+09 |
Annual Sum or Average | 0.325609E+10 | 0.173863E+10 | 0.151746E+10 | 0.361282E+10 | 0.181274E+10 |
Minimum of Months | 0.212599E+09 | 59233638.45 | 79113904.12 | 0.191686E+09 | 51552036.11 |
Maximum of Months | 0.346363E+09 | 0.234030E+09 | 0.172364E+09 | 0.351606E+09 | 0.304452E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.362093E+09 | 0.251988E+09 | 0.110105E+09 | 0.323148E+09 | 0.359869E+09 |
February | 0.414106E+09 | 0.279803E+09 | 0.134304E+09 | 0.418873E+09 | 0.269158E+09 |
March | 0.403777E+09 | 0.255575E+09 | 0.148202E+09 | 0.420364E+09 | 0.242608E+09 |
April | 0.353697E+09 | 0.191878E+09 | 0.161819E+09 | 0.404987E+09 | 0.151374E+09 |
May | 0.307111E+09 | 0.104760E+09 | 0.202351E+09 | 0.381295E+09 | 89350608.47 |
June | 0.266640E+09 | 70818837.99 | 0.195821E+09 | 0.348451E+09 | 61316942.83 |
July | 0.301232E+09 | 95156450.59 | 0.206075E+09 | 0.406147E+09 | 61791032.66 |
August | 0.321851E+09 | 0.134469E+09 | 0.187382E+09 | 0.420582E+09 | 72957490.78 |
September | 0.333883E+09 | 0.177804E+09 | 0.156079E+09 | 0.407736E+09 | 0.107303E+09 |
October | 0.294799E+09 | 0.173451E+09 | 0.121348E+09 | 0.321639E+09 | 0.159051E+09 |
November | 0.254180E+09 | 0.159592E+09 | 94587381.53 | 0.244791E+09 | 0.222298E+09 |
December | 0.279563E+09 | 0.183384E+09 | 96178896.10 | 0.230451E+09 | 0.348792E+09 |
Annual Sum or Average | 0.389293E+10 | 0.207868E+10 | 0.181425E+10 | 0.432846E+10 | 0.214587E+10 |
Minimum of Months | 0.254180E+09 | 70818837.99 | 94587381.53 | 0.230451E+09 | 61316942.83 |
Maximum of Months | 0.414106E+09 | 0.279803E+09 | 0.206075E+09 | 0.420582E+09 | 0.359869E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.302858E+09 | 0.210765E+09 | 92093031.39 | 0.269320E+09 | 0.302682E+09 |
February | 0.346363E+09 | 0.234030E+09 | 0.112333E+09 | 0.349505E+09 | 0.225664E+09 |
March | 0.337723E+09 | 0.213765E+09 | 0.123958E+09 | 0.351248E+09 | 0.202587E+09 |
April | 0.295836E+09 | 0.160488E+09 | 0.135347E+09 | 0.339006E+09 | 0.125202E+09 |
May | 0.256871E+09 | 87622647.49 | 0.169249E+09 | 0.320079E+09 | 73187239.06 |
June | 0.223021E+09 | 59233638.45 | 0.163787E+09 | 0.292685E+09 | 50090220.36 |
July | 0.251953E+09 | 79589879.61 | 0.172364E+09 | 0.340325E+09 | 51127959.66 |
August | 0.269199E+09 | 0.112471E+09 | 0.156728E+09 | 0.352149E+09 | 60466461.62 |
September | 0.279264E+09 | 0.148717E+09 | 0.130546E+09 | 0.341384E+09 | 88990311.78 |
October | 0.246573E+09 | 0.145076E+09 | 0.101497E+09 | 0.269022E+09 | 0.132375E+09 |
November | 0.212599E+09 | 0.133485E+09 | 79113904.12 | 0.204402E+09 | 0.185757E+09 |
December | 0.233830E+09 | 0.153385E+09 | 80445064.04 | 0.191976E+09 | 0.293320E+09 |
Annual Sum or Average | 0.325609E+10 | 0.173863E+10 | 0.151746E+10 | 0.362110E+10 | 0.179145E+10 |
Minimum of Months | 0.212599E+09 | 59233638.45 | 79113904.12 | 0.191976E+09 | 50090220.36 |
Maximum of Months | 0.346363E+09 | 0.234030E+09 | 0.172364E+09 | 0.352149E+09 | 0.302682E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.302858E+09 | 0.210765E+09 | 92093031.39 | 0.269320E+09 | 0.302682E+09 |
February | 0.346363E+09 | 0.234030E+09 | 0.112333E+09 | 0.349505E+09 | 0.225664E+09 |
March | 0.337723E+09 | 0.213765E+09 | 0.123958E+09 | 0.351248E+09 | 0.202587E+09 |
April | 0.295836E+09 | 0.160488E+09 | 0.135347E+09 | 0.339006E+09 | 0.125202E+09 |
May | 0.256871E+09 | 87622647.49 | 0.169249E+09 | 0.320079E+09 | 73187239.06 |
June | 0.223021E+09 | 59233638.45 | 0.163787E+09 | 0.292685E+09 | 50090220.36 |
July | 0.251953E+09 | 79589879.61 | 0.172364E+09 | 0.340325E+09 | 51127959.66 |
August | 0.269199E+09 | 0.112471E+09 | 0.156728E+09 | 0.352149E+09 | 60466461.62 |
September | 0.279264E+09 | 0.148717E+09 | 0.130546E+09 | 0.341384E+09 | 88990311.78 |
October | 0.246573E+09 | 0.145076E+09 | 0.101497E+09 | 0.269022E+09 | 0.132375E+09 |
November | 0.212599E+09 | 0.133485E+09 | 79113904.12 | 0.204402E+09 | 0.185757E+09 |
December | 0.233830E+09 | 0.153385E+09 | 80445064.04 | 0.191976E+09 | 0.293320E+09 |
Annual Sum or Average | 0.325609E+10 | 0.173863E+10 | 0.151746E+10 | 0.362110E+10 | 0.179145E+10 |
Minimum of Months | 0.212599E+09 | 59233638.45 | 79113904.12 | 0.191976E+09 | 50090220.36 |
Maximum of Months | 0.346363E+09 | 0.234030E+09 | 0.172364E+09 | 0.352149E+09 | 0.302682E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.362093E+09 | 0.251988E+09 | 0.110105E+09 | 0.323528E+09 | 0.357762E+09 |
February | 0.414106E+09 | 0.279803E+09 | 0.134304E+09 | 0.419412E+09 | 0.266895E+09 |
March | 0.403777E+09 | 0.255575E+09 | 0.148202E+09 | 0.421069E+09 | 0.239718E+09 |
April | 0.353697E+09 | 0.191878E+09 | 0.161819E+09 | 0.406109E+09 | 0.148343E+09 |
May | 0.307111E+09 | 0.104760E+09 | 0.202351E+09 | 0.383052E+09 | 86931094.12 |
June | 0.266640E+09 | 70818837.99 | 0.195821E+09 | 0.350019E+09 | 59588116.40 |
July | 0.301232E+09 | 95156450.59 | 0.206075E+09 | 0.406842E+09 | 60860786.43 |
August | 0.321851E+09 | 0.134469E+09 | 0.187382E+09 | 0.421234E+09 | 71863667.77 |
September | 0.333883E+09 | 0.177804E+09 | 0.156079E+09 | 0.408660E+09 | 0.105572E+09 |
October | 0.294799E+09 | 0.173451E+09 | 0.121348E+09 | 0.322342E+09 | 0.156903E+09 |
November | 0.254180E+09 | 0.159592E+09 | 94587381.53 | 0.245351E+09 | 0.219727E+09 |
December | 0.279563E+09 | 0.183384E+09 | 96178896.10 | 0.230806E+09 | 0.346473E+09 |
Annual Sum or Average | 0.389293E+10 | 0.207868E+10 | 0.181425E+10 | 0.433842E+10 | 0.212064E+10 |
Minimum of Months | 0.254180E+09 | 70818837.99 | 94587381.53 | 0.230806E+09 | 59588116.40 |
Maximum of Months | 0.414106E+09 | 0.279803E+09 | 0.206075E+09 | 0.421234E+09 | 0.357762E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.302858E+09 | 0.210765E+09 | 92093031.39 | 0.271335E+09 | 0.293692E+09 |
February | 0.346363E+09 | 0.234030E+09 | 0.112333E+09 | 0.351705E+09 | 0.217121E+09 |
March | 0.337723E+09 | 0.213765E+09 | 0.123958E+09 | 0.353856E+09 | 0.191776E+09 |
April | 0.295836E+09 | 0.160488E+09 | 0.135347E+09 | 0.342088E+09 | 0.115060E+09 |
May | 0.256871E+09 | 87622647.49 | 0.169249E+09 | 0.324077E+09 | 66388182.07 |
June | 0.223021E+09 | 59233638.45 | 0.163787E+09 | 0.295877E+09 | 45455098.64 |
July | 0.251953E+09 | 79589879.61 | 0.172364E+09 | 0.341880E+09 | 48156017.52 |
August | 0.269199E+09 | 0.112471E+09 | 0.156728E+09 | 0.353551E+09 | 57241917.63 |
September | 0.279264E+09 | 0.148717E+09 | 0.130546E+09 | 0.343184E+09 | 84301200.46 |
October | 0.246573E+09 | 0.145076E+09 | 0.101497E+09 | 0.270815E+09 | 0.125731E+09 |
November | 0.212599E+09 | 0.133485E+09 | 79113904.12 | 0.206222E+09 | 0.176813E+09 |
December | 0.233830E+09 | 0.153385E+09 | 80445064.04 | 0.193633E+09 | 0.283893E+09 |
Annual Sum or Average | 0.325609E+10 | 0.173863E+10 | 0.151746E+10 | 0.364823E+10 | 0.170563E+10 |
Minimum of Months | 0.212599E+09 | 59233638.45 | 79113904.12 | 0.193633E+09 | 45455098.64 |
Maximum of Months | 0.346363E+09 | 0.234030E+09 | 0.172364E+09 | 0.353856E+09 | 0.293692E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.302858E+09 | 0.210765E+09 | 92093031.39 | 0.271335E+09 | 0.293692E+09 |
February | 0.346363E+09 | 0.234030E+09 | 0.112333E+09 | 0.351705E+09 | 0.217121E+09 |
March | 0.337723E+09 | 0.213765E+09 | 0.123958E+09 | 0.353856E+09 | 0.191776E+09 |
April | 0.295836E+09 | 0.160488E+09 | 0.135347E+09 | 0.342088E+09 | 0.115060E+09 |
May | 0.256871E+09 | 87622647.49 | 0.169249E+09 | 0.324077E+09 | 66388182.07 |
June | 0.223021E+09 | 59233638.45 | 0.163787E+09 | 0.295877E+09 | 45455098.64 |
July | 0.251953E+09 | 79589879.61 | 0.172364E+09 | 0.341880E+09 | 48156017.52 |
August | 0.269199E+09 | 0.112471E+09 | 0.156728E+09 | 0.353551E+09 | 57241917.63 |
September | 0.279264E+09 | 0.148717E+09 | 0.130546E+09 | 0.343184E+09 | 84301200.46 |
October | 0.246573E+09 | 0.145076E+09 | 0.101497E+09 | 0.270815E+09 | 0.125731E+09 |
November | 0.212599E+09 | 0.133485E+09 | 79113904.12 | 0.206222E+09 | 0.176813E+09 |
December | 0.233830E+09 | 0.153385E+09 | 80445064.04 | 0.193633E+09 | 0.283893E+09 |
Annual Sum or Average | 0.325609E+10 | 0.173863E+10 | 0.151746E+10 | 0.364823E+10 | 0.170563E+10 |
Minimum of Months | 0.212599E+09 | 59233638.45 | 79113904.12 | 0.193633E+09 | 45455098.64 |
Maximum of Months | 0.346363E+09 | 0.234030E+09 | 0.172364E+09 | 0.353856E+09 | 0.293692E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.362093E+09 | 0.251988E+09 | 0.110105E+09 | 0.325989E+09 | 0.347005E+09 |
February | 0.414106E+09 | 0.279803E+09 | 0.134304E+09 | 0.422084E+09 | 0.256705E+09 |
March | 0.403777E+09 | 0.255575E+09 | 0.148202E+09 | 0.424243E+09 | 0.226854E+09 |
April | 0.353697E+09 | 0.191878E+09 | 0.161819E+09 | 0.409838E+09 | 0.136338E+09 |
May | 0.307111E+09 | 0.104760E+09 | 0.202351E+09 | 0.387846E+09 | 78901402.68 |
June | 0.266640E+09 | 70818837.99 | 0.195821E+09 | 0.353828E+09 | 54101682.14 |
July | 0.301232E+09 | 95156450.59 | 0.206075E+09 | 0.408698E+09 | 57342777.08 |
August | 0.321851E+09 | 0.134469E+09 | 0.187382E+09 | 0.422910E+09 | 68057305.21 |
September | 0.333883E+09 | 0.177804E+09 | 0.156079E+09 | 0.410816E+09 | 0.100033E+09 |
October | 0.294799E+09 | 0.173451E+09 | 0.121348E+09 | 0.324514E+09 | 0.149038E+09 |
November | 0.254180E+09 | 0.159592E+09 | 94587381.53 | 0.247562E+09 | 0.209134E+09 |
December | 0.279563E+09 | 0.183384E+09 | 96178896.10 | 0.232840E+09 | 0.335226E+09 |
Annual Sum or Average | 0.389293E+10 | 0.207868E+10 | 0.181425E+10 | 0.437117E+10 | 0.201874E+10 |
Minimum of Months | 0.254180E+09 | 70818837.99 | 94587381.53 | 0.232840E+09 | 54101682.14 |
Maximum of Months | 0.414106E+09 | 0.279803E+09 | 0.206075E+09 | 0.424243E+09 | 0.347005E+09 |
Report: WindowZoneSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 647.15 | 734.75 | 724.16 | 503.96 | 220.20 | 0.00 | 0.00 |
February | 928.43 | 607.81 | 916.92 | 619.54 | 297.38 | 0.00 | 0.00 |
March | 842.41 | 493.71 | 807.53 | 511.13 | 296.40 | 0.00 | 0.00 |
April | 834.53 | 326.19 | 730.95 | 396.53 | 334.42 | 0.00 | 0.00 |
May | 754.84 | 191.20 | 614.20 | 209.51 | 404.69 | 0.00 | 0.00 |
June | 716.19 | 132.21 | 551.04 | 146.35 | 404.68 | 0.00 | 0.00 |
July | 814.84 | 121.97 | 602.44 | 190.31 | 412.14 | 0.00 | 0.00 |
August | 841.62 | 146.29 | 643.68 | 268.93 | 374.75 | 0.00 | 0.00 |
September | 834.82 | 236.08 | 690.00 | 367.45 | 322.55 | 0.00 | 0.00 |
October | 636.28 | 340.10 | 589.58 | 346.89 | 242.69 | 0.00 | 0.00 |
November | 504.97 | 473.28 | 525.29 | 329.81 | 195.47 | 0.00 | 0.00 |
December | 461.36 | 711.85 | 559.11 | 366.76 | 192.35 | 0.00 | 0.00 |
Annual Sum or Average | 733.33 | 375.31 | 661.24 | 353.08 | 308.16 | 0.00 | 0.00 |
Minimum of Months | 461.36 | 121.97 | 525.29 | 146.35 | 192.35 | 0.00 | 0.00 |
Maximum of Months | 928.43 | 734.75 | 916.92 | 619.54 | 412.14 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 320.45 | 377.60 | 362.08 | 251.98 | 110.10 | 0.00 | 0.00 |
February | 460.22 | 314.15 | 458.46 | 309.77 | 148.69 | 0.00 | 0.00 |
March | 417.56 | 257.04 | 403.76 | 255.57 | 148.20 | 0.00 | 0.00 |
April | 414.23 | 170.98 | 365.48 | 198.27 | 167.21 | 0.00 | 0.00 |
May | 375.92 | 98.44 | 307.10 | 104.76 | 202.34 | 0.00 | 0.00 |
June | 356.53 | 68.06 | 275.52 | 73.18 | 202.34 | 0.00 | 0.00 |
July | 406.46 | 62.27 | 301.22 | 95.15 | 206.07 | 0.00 | 0.00 |
August | 420.00 | 74.53 | 321.84 | 134.46 | 187.38 | 0.00 | 0.00 |
September | 417.56 | 119.10 | 345.00 | 183.73 | 161.28 | 0.00 | 0.00 |
October | 317.66 | 173.30 | 294.79 | 173.45 | 121.34 | 0.00 | 0.00 |
November | 250.08 | 245.55 | 262.64 | 164.91 | 97.74 | 0.00 | 0.00 |
December | 228.13 | 366.35 | 279.55 | 183.38 | 96.18 | 0.00 | 0.00 |
Annual Sum or Average | 364.68 | 193.43 | 330.62 | 176.54 | 154.08 | 0.00 | 0.00 |
Minimum of Months | 228.13 | 62.27 | 262.64 | 73.18 | 96.18 | 0.00 | 0.00 |
Maximum of Months | 460.22 | 377.60 | 458.46 | 309.77 | 206.07 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 320.26 | 370.99 | 361.34 | 251.46 | 109.88 | 0.00 | 0.00 |
February | 459.65 | 308.83 | 457.52 | 309.14 | 148.38 | 0.00 | 0.00 |
March | 416.88 | 252.83 | 402.94 | 255.04 | 147.89 | 0.00 | 0.00 |
April | 414.20 | 166.68 | 364.73 | 197.86 | 166.86 | 0.00 | 0.00 |
May | 376.19 | 97.47 | 306.47 | 104.54 | 201.93 | 0.00 | 0.00 |
June | 355.82 | 69.50 | 274.95 | 73.03 | 201.93 | 0.00 | 0.00 |
July | 404.55 | 65.64 | 300.60 | 94.96 | 205.65 | 0.00 | 0.00 |
August | 418.76 | 77.45 | 321.18 | 134.19 | 186.99 | 0.00 | 0.00 |
September | 417.79 | 118.34 | 344.29 | 183.35 | 160.95 | 0.00 | 0.00 |
October | 318.28 | 168.15 | 294.19 | 173.09 | 121.10 | 0.00 | 0.00 |
November | 250.10 | 240.51 | 262.11 | 164.57 | 97.54 | 0.00 | 0.00 |
December | 228.00 | 360.07 | 278.98 | 183.00 | 95.98 | 0.00 | 0.00 |
Annual Sum or Average | 364.32 | 190.87 | 329.94 | 176.18 | 153.77 | 0.00 | 0.00 |
Minimum of Months | 228.00 | 65.64 | 262.11 | 73.03 | 95.98 | 0.00 | 0.00 |
Maximum of Months | 459.65 | 370.99 | 457.52 | 309.14 | 205.65 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 320.57 | 368.61 | 361.34 | 251.46 | 109.88 | 0.00 | 0.00 |
February | 460.05 | 306.61 | 457.52 | 309.14 | 148.38 | 0.00 | 0.00 |
March | 417.23 | 250.85 | 402.94 | 255.04 | 147.89 | 0.00 | 0.00 |
April | 414.84 | 164.54 | 364.73 | 197.86 | 166.86 | 0.00 | 0.00 |
May | 377.01 | 95.99 | 306.47 | 104.54 | 201.93 | 0.00 | 0.00 |
June | 356.36 | 68.73 | 274.95 | 73.03 | 201.93 | 0.00 | 0.00 |
July | 404.61 | 65.54 | 300.60 | 94.96 | 205.65 | 0.00 | 0.00 |
August | 418.89 | 77.18 | 321.18 | 134.19 | 186.99 | 0.00 | 0.00 |
September | 418.42 | 116.89 | 344.29 | 183.35 | 160.95 | 0.00 | 0.00 |
October | 318.94 | 165.82 | 294.19 | 173.09 | 121.10 | 0.00 | 0.00 |
November | 250.47 | 238.22 | 262.11 | 164.57 | 97.54 | 0.00 | 0.00 |
December | 228.25 | 357.73 | 278.98 | 183.00 | 95.98 | 0.00 | 0.00 |
Annual Sum or Average | 364.75 | 189.23 | 329.94 | 176.18 | 153.77 | 0.00 | 0.00 |
Minimum of Months | 228.25 | 65.54 | 262.11 | 73.03 | 95.98 | 0.00 | 0.00 |
Maximum of Months | 460.05 | 368.61 | 457.52 | 309.14 | 205.65 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 320.96 | 366.83 | 361.34 | 251.46 | 109.88 | 0.00 | 0.00 |
February | 460.60 | 304.72 | 457.52 | 309.14 | 148.38 | 0.00 | 0.00 |
March | 417.75 | 249.01 | 402.94 | 255.04 | 147.89 | 0.00 | 0.00 |
April | 415.66 | 162.61 | 364.73 | 197.86 | 166.86 | 0.00 | 0.00 |
May | 378.16 | 94.33 | 306.47 | 104.54 | 201.93 | 0.00 | 0.00 |
June | 357.34 | 67.49 | 274.95 | 73.03 | 201.93 | 0.00 | 0.00 |
July | 405.05 | 64.79 | 300.60 | 94.96 | 205.65 | 0.00 | 0.00 |
August | 419.33 | 76.29 | 321.18 | 134.19 | 186.99 | 0.00 | 0.00 |
September | 419.22 | 115.32 | 344.29 | 183.35 | 160.95 | 0.00 | 0.00 |
October | 319.60 | 164.04 | 294.19 | 173.09 | 121.10 | 0.00 | 0.00 |
November | 250.95 | 236.22 | 262.11 | 164.57 | 97.54 | 0.00 | 0.00 |
December | 228.59 | 355.83 | 278.98 | 183.00 | 95.98 | 0.00 | 0.00 |
Annual Sum or Average | 365.38 | 187.63 | 329.94 | 176.18 | 153.77 | 0.00 | 0.00 |
Minimum of Months | 228.59 | 64.79 | 262.11 | 73.03 | 95.98 | 0.00 | 0.00 |
Maximum of Months | 460.60 | 366.83 | 457.52 | 309.14 | 205.65 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 645.43 | 719.68 | 722.68 | 502.93 | 219.75 | 0.00 | 0.00 |
February | 926.07 | 596.48 | 915.04 | 618.27 | 296.77 | 0.00 | 0.00 |
March | 839.40 | 486.25 | 805.87 | 510.08 | 295.79 | 0.00 | 0.00 |
April | 834.92 | 315.37 | 729.45 | 395.72 | 333.73 | 0.00 | 0.00 |
May | 759.49 | 181.69 | 612.94 | 209.08 | 403.86 | 0.00 | 0.00 |
June | 717.02 | 129.40 | 549.91 | 146.05 | 403.85 | 0.00 | 0.00 |
July | 810.12 | 125.46 | 601.21 | 189.92 | 411.29 | 0.00 | 0.00 |
August | 839.11 | 148.04 | 642.36 | 268.38 | 373.98 | 0.00 | 0.00 |
September | 840.23 | 224.54 | 688.59 | 366.70 | 321.89 | 0.00 | 0.00 |
October | 641.73 | 320.40 | 588.37 | 346.18 | 242.19 | 0.00 | 0.00 |
November | 504.89 | 460.71 | 524.21 | 329.14 | 195.07 | 0.00 | 0.00 |
December | 460.23 | 697.47 | 557.96 | 366.00 | 191.96 | 0.00 | 0.00 |
Annual Sum or Average | 733.43 | 366.16 | 659.89 | 352.36 | 307.53 | 0.00 | 0.00 |
Minimum of Months | 460.23 | 125.46 | 524.21 | 146.05 | 191.96 | 0.00 | 0.00 |
Maximum of Months | 926.07 | 719.68 | 915.04 | 618.27 | 411.29 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 321.46 | 361.98 | 361.34 | 251.46 | 109.88 | 0.00 | 0.00 |
February | 461.61 | 299.81 | 457.52 | 309.14 | 148.38 | 0.00 | 0.00 |
March | 418.64 | 244.22 | 402.94 | 255.04 | 147.89 | 0.00 | 0.00 |
April | 416.75 | 157.80 | 364.73 | 197.86 | 166.86 | 0.00 | 0.00 |
May | 379.62 | 90.36 | 306.47 | 104.54 | 201.93 | 0.00 | 0.00 |
June | 358.61 | 64.10 | 274.95 | 73.03 | 201.93 | 0.00 | 0.00 |
July | 405.05 | 62.17 | 300.60 | 94.96 | 205.65 | 0.00 | 0.00 |
August | 419.31 | 73.49 | 321.18 | 134.19 | 186.99 | 0.00 | 0.00 |
September | 419.73 | 111.86 | 344.29 | 183.35 | 160.95 | 0.00 | 0.00 |
October | 320.29 | 160.22 | 294.19 | 173.09 | 121.10 | 0.00 | 0.00 |
November | 251.65 | 231.36 | 262.11 | 164.57 | 97.54 | 0.00 | 0.00 |
December | 229.11 | 351.03 | 278.98 | 183.00 | 95.98 | 0.00 | 0.00 |
Annual Sum or Average | 366.10 | 183.55 | 329.94 | 176.18 | 153.77 | 0.00 | 0.00 |
Minimum of Months | 229.11 | 62.17 | 262.11 | 73.03 | 95.98 | 0.00 | 0.00 |
Maximum of Months | 461.61 | 361.98 | 457.52 | 309.14 | 205.65 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 321.52 | 361.70 | 361.34 | 251.46 | 109.88 | 0.00 | 0.00 |
February | 461.72 | 299.39 | 457.52 | 309.14 | 148.38 | 0.00 | 0.00 |
March | 418.80 | 243.67 | 402.94 | 255.04 | 147.89 | 0.00 | 0.00 |
April | 417.10 | 156.98 | 364.73 | 197.86 | 166.86 | 0.00 | 0.00 |
May | 380.27 | 89.54 | 306.47 | 104.54 | 201.93 | 0.00 | 0.00 |
June | 359.26 | 63.43 | 274.95 | 73.03 | 201.93 | 0.00 | 0.00 |
July | 405.33 | 61.84 | 300.60 | 94.96 | 205.65 | 0.00 | 0.00 |
August | 419.58 | 73.08 | 321.18 | 134.19 | 186.99 | 0.00 | 0.00 |
September | 420.12 | 111.19 | 344.29 | 183.35 | 160.95 | 0.00 | 0.00 |
October | 320.53 | 159.58 | 294.19 | 173.09 | 121.10 | 0.00 | 0.00 |
November | 251.80 | 230.77 | 262.11 | 164.57 | 97.54 | 0.00 | 0.00 |
December | 229.17 | 350.71 | 278.98 | 183.00 | 95.98 | 0.00 | 0.00 |
Annual Sum or Average | 366.38 | 183.01 | 329.94 | 176.18 | 153.77 | 0.00 | 0.00 |
Minimum of Months | 229.17 | 61.84 | 262.11 | 73.03 | 95.98 | 0.00 | 0.00 |
Maximum of Months | 461.72 | 361.70 | 457.52 | 309.14 | 205.65 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 321.90 | 359.59 | 361.34 | 251.46 | 109.88 | 0.00 | 0.00 |
February | 462.31 | 296.88 | 457.52 | 309.14 | 148.38 | 0.00 | 0.00 |
March | 419.49 | 240.77 | 402.94 | 255.04 | 147.89 | 0.00 | 0.00 |
April | 418.26 | 153.84 | 364.73 | 197.86 | 166.86 | 0.00 | 0.00 |
May | 382.02 | 87.11 | 306.47 | 104.54 | 201.93 | 0.00 | 0.00 |
June | 360.88 | 61.64 | 274.95 | 73.03 | 201.93 | 0.00 | 0.00 |
July | 406.02 | 60.90 | 300.60 | 94.96 | 205.65 | 0.00 | 0.00 |
August | 420.23 | 71.98 | 321.18 | 134.19 | 186.99 | 0.00 | 0.00 |
September | 421.08 | 109.40 | 344.29 | 183.35 | 160.95 | 0.00 | 0.00 |
October | 321.23 | 157.43 | 294.19 | 173.09 | 121.10 | 0.00 | 0.00 |
November | 252.37 | 228.10 | 262.11 | 164.57 | 97.54 | 0.00 | 0.00 |
December | 229.52 | 348.38 | 278.98 | 183.00 | 95.98 | 0.00 | 0.00 |
Annual Sum or Average | 367.22 | 180.86 | 329.94 | 176.18 | 153.77 | 0.00 | 0.00 |
Minimum of Months | 229.52 | 60.90 | 262.11 | 73.03 | 95.98 | 0.00 | 0.00 |
Maximum of Months | 462.31 | 359.59 | 457.52 | 309.14 | 205.65 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 324.32 | 348.86 | 361.34 | 251.46 | 109.88 | 0.00 | 0.00 |
February | 465.23 | 285.61 | 457.52 | 309.14 | 148.38 | 0.00 | 0.00 |
March | 422.62 | 227.90 | 402.94 | 255.04 | 147.89 | 0.00 | 0.00 |
April | 422.07 | 141.38 | 364.73 | 197.86 | 166.86 | 0.00 | 0.00 |
May | 386.80 | 79.03 | 306.47 | 104.54 | 201.93 | 0.00 | 0.00 |
June | 364.81 | 55.95 | 274.95 | 73.03 | 201.93 | 0.00 | 0.00 |
July | 407.88 | 57.37 | 300.60 | 94.96 | 205.65 | 0.00 | 0.00 |
August | 421.90 | 68.15 | 321.18 | 134.19 | 186.99 | 0.00 | 0.00 |
September | 423.30 | 103.64 | 344.29 | 183.35 | 160.95 | 0.00 | 0.00 |
October | 323.38 | 149.53 | 294.19 | 173.09 | 121.10 | 0.00 | 0.00 |
November | 254.63 | 217.11 | 262.11 | 164.57 | 97.54 | 0.00 | 0.00 |
December | 231.52 | 337.14 | 278.98 | 183.00 | 95.98 | 0.00 | 0.00 |
Annual Sum or Average | 369.98 | 172.18 | 329.94 | 176.18 | 153.77 | 0.00 | 0.00 |
Minimum of Months | 231.52 | 55.95 | 262.11 | 73.03 | 95.98 | 0.00 | 0.00 |
Maximum of Months | 465.23 | 348.86 | 457.52 | 309.14 | 205.65 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.173334E+10 | 0.196795E+10 | 0.193960E+10 | 0.134981E+10 | 0.589792E+09 | 0.00 | 0.00 |
February | 0.224607E+10 | 0.147043E+10 | 0.221822E+10 | 0.149880E+10 | 0.719415E+09 | 0.00 | 0.00 |
March | 0.225630E+10 | 0.132234E+10 | 0.216288E+10 | 0.136902E+10 | 0.793866E+09 | 0.00 | 0.00 |
April | 0.216309E+10 | 0.845477E+09 | 0.189462E+10 | 0.102782E+10 | 0.866806E+09 | 0.00 | 0.00 |
May | 0.202178E+10 | 0.512106E+09 | 0.164508E+10 | 0.561162E+09 | 0.108392E+10 | 0.00 | 0.00 |
June | 0.185636E+10 | 0.342697E+09 | 0.142829E+10 | 0.379350E+09 | 0.104894E+10 | 0.00 | 0.00 |
July | 0.218248E+10 | 0.326687E+09 | 0.161359E+10 | 0.509718E+09 | 0.110387E+10 | 0.00 | 0.00 |
August | 0.225420E+10 | 0.391817E+09 | 0.172404E+10 | 0.720300E+09 | 0.100374E+10 | 0.00 | 0.00 |
September | 0.216385E+10 | 0.611921E+09 | 0.178849E+10 | 0.952432E+09 | 0.836058E+09 | 0.00 | 0.00 |
October | 0.170420E+10 | 0.910912E+09 | 0.157913E+10 | 0.929113E+09 | 0.650019E+09 | 0.00 | 0.00 |
November | 0.130889E+10 | 0.122674E+10 | 0.136155E+10 | 0.854877E+09 | 0.506670E+09 | 0.00 | 0.00 |
December | 0.123570E+10 | 0.190663E+10 | 0.149752E+10 | 0.982322E+09 | 0.515195E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.231263E+11 | 0.118357E+11 | 0.208530E+11 | 0.111347E+11 | 0.971829E+10 | 0.00 | 0.00 |
Minimum of Months | 0.123570E+10 | 0.326687E+09 | 0.136155E+10 | 0.379350E+09 | 0.506670E+09 | 0.00 | 0.00 |
Maximum of Months | 0.225630E+10 | 0.196795E+10 | 0.221822E+10 | 0.149880E+10 | 0.110387E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.858294E+09 | 0.101136E+10 | 0.969799E+09 | 0.674903E+09 | 0.294896E+09 | 0.00 | 0.00 |
February | 0.111336E+10 | 0.759990E+09 | 0.110911E+10 | 0.749400E+09 | 0.359707E+09 | 0.00 | 0.00 |
March | 0.111838E+10 | 0.688454E+09 | 0.108144E+10 | 0.684509E+09 | 0.396933E+09 | 0.00 | 0.00 |
April | 0.107370E+10 | 0.443179E+09 | 0.947312E+09 | 0.513909E+09 | 0.433403E+09 | 0.00 | 0.00 |
May | 0.100686E+10 | 0.263654E+09 | 0.822542E+09 | 0.280581E+09 | 0.541960E+09 | 0.00 | 0.00 |
June | 0.924126E+09 | 0.176402E+09 | 0.714146E+09 | 0.189675E+09 | 0.524471E+09 | 0.00 | 0.00 |
July | 0.108866E+10 | 0.166774E+09 | 0.806794E+09 | 0.254859E+09 | 0.551935E+09 | 0.00 | 0.00 |
August | 0.112493E+10 | 0.199626E+09 | 0.862018E+09 | 0.360150E+09 | 0.501868E+09 | 0.00 | 0.00 |
September | 0.108233E+10 | 0.308697E+09 | 0.894245E+09 | 0.476216E+09 | 0.418029E+09 | 0.00 | 0.00 |
October | 0.850811E+09 | 0.464159E+09 | 0.789566E+09 | 0.464556E+09 | 0.325010E+09 | 0.00 | 0.00 |
November | 0.648219E+09 | 0.636454E+09 | 0.680773E+09 | 0.427439E+09 | 0.253335E+09 | 0.00 | 0.00 |
December | 0.611035E+09 | 0.981219E+09 | 0.748759E+09 | 0.491161E+09 | 0.257597E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.115007E+11 | 0.609997E+10 | 0.104265E+11 | 0.556736E+10 | 0.485914E+10 | 0.00 | 0.00 |
Minimum of Months | 0.611035E+09 | 0.166774E+09 | 0.680773E+09 | 0.189675E+09 | 0.253335E+09 | 0.00 | 0.00 |
Maximum of Months | 0.112493E+10 | 0.101136E+10 | 0.110911E+10 | 0.749400E+09 | 0.551935E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.857774E+09 | 0.993669E+09 | 0.967809E+09 | 0.673518E+09 | 0.294291E+09 | 0.00 | 0.00 |
February | 0.111198E+10 | 0.747129E+09 | 0.110683E+10 | 0.747863E+09 | 0.358969E+09 | 0.00 | 0.00 |
March | 0.111658E+10 | 0.677168E+09 | 0.107922E+10 | 0.683105E+09 | 0.396119E+09 | 0.00 | 0.00 |
April | 0.107361E+10 | 0.432047E+09 | 0.945369E+09 | 0.512855E+09 | 0.432514E+09 | 0.00 | 0.00 |
May | 0.100758E+10 | 0.261076E+09 | 0.820854E+09 | 0.280006E+09 | 0.540849E+09 | 0.00 | 0.00 |
June | 0.922290E+09 | 0.180137E+09 | 0.712681E+09 | 0.189286E+09 | 0.523395E+09 | 0.00 | 0.00 |
July | 0.108354E+10 | 0.175798E+09 | 0.805139E+09 | 0.254336E+09 | 0.550802E+09 | 0.00 | 0.00 |
August | 0.112160E+10 | 0.207438E+09 | 0.860250E+09 | 0.359411E+09 | 0.500839E+09 | 0.00 | 0.00 |
September | 0.108292E+10 | 0.306749E+09 | 0.892410E+09 | 0.475239E+09 | 0.417172E+09 | 0.00 | 0.00 |
October | 0.852479E+09 | 0.450362E+09 | 0.787946E+09 | 0.463603E+09 | 0.324343E+09 | 0.00 | 0.00 |
November | 0.648249E+09 | 0.623390E+09 | 0.679377E+09 | 0.426562E+09 | 0.252815E+09 | 0.00 | 0.00 |
December | 0.610685E+09 | 0.964412E+09 | 0.747223E+09 | 0.490154E+09 | 0.257069E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.114893E+11 | 0.601938E+10 | 0.104051E+11 | 0.555594E+10 | 0.484918E+10 | 0.00 | 0.00 |
Minimum of Months | 0.610685E+09 | 0.175798E+09 | 0.679377E+09 | 0.189286E+09 | 0.252815E+09 | 0.00 | 0.00 |
Maximum of Months | 0.112160E+10 | 0.993669E+09 | 0.110683E+10 | 0.747863E+09 | 0.550802E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.858626E+09 | 0.987280E+09 | 0.967809E+09 | 0.673518E+09 | 0.294291E+09 | 0.00 | 0.00 |
February | 0.111295E+10 | 0.741762E+09 | 0.110683E+10 | 0.747863E+09 | 0.358969E+09 | 0.00 | 0.00 |
March | 0.111751E+10 | 0.671884E+09 | 0.107922E+10 | 0.683105E+09 | 0.396119E+09 | 0.00 | 0.00 |
April | 0.107527E+10 | 0.426478E+09 | 0.945369E+09 | 0.512855E+09 | 0.432514E+09 | 0.00 | 0.00 |
May | 0.100979E+10 | 0.257092E+09 | 0.820854E+09 | 0.280006E+09 | 0.540849E+09 | 0.00 | 0.00 |
June | 0.923687E+09 | 0.178156E+09 | 0.712681E+09 | 0.189286E+09 | 0.523395E+09 | 0.00 | 0.00 |
July | 0.108371E+10 | 0.175550E+09 | 0.805139E+09 | 0.254336E+09 | 0.550802E+09 | 0.00 | 0.00 |
August | 0.112194E+10 | 0.206725E+09 | 0.860250E+09 | 0.359411E+09 | 0.500839E+09 | 0.00 | 0.00 |
September | 0.108454E+10 | 0.302979E+09 | 0.892410E+09 | 0.475239E+09 | 0.417172E+09 | 0.00 | 0.00 |
October | 0.854249E+09 | 0.444133E+09 | 0.787946E+09 | 0.463603E+09 | 0.324343E+09 | 0.00 | 0.00 |
November | 0.649209E+09 | 0.617477E+09 | 0.679377E+09 | 0.426562E+09 | 0.252815E+09 | 0.00 | 0.00 |
December | 0.611355E+09 | 0.958134E+09 | 0.747223E+09 | 0.490154E+09 | 0.257069E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.115028E+11 | 0.596765E+10 | 0.104051E+11 | 0.555594E+10 | 0.484918E+10 | 0.00 | 0.00 |
Minimum of Months | 0.611355E+09 | 0.175550E+09 | 0.679377E+09 | 0.189286E+09 | 0.252815E+09 | 0.00 | 0.00 |
Maximum of Months | 0.112194E+10 | 0.987280E+09 | 0.110683E+10 | 0.747863E+09 | 0.550802E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.859673E+09 | 0.982520E+09 | 0.967809E+09 | 0.673518E+09 | 0.294291E+09 | 0.00 | 0.00 |
February | 0.111427E+10 | 0.737174E+09 | 0.110683E+10 | 0.747863E+09 | 0.358969E+09 | 0.00 | 0.00 |
March | 0.111890E+10 | 0.666942E+09 | 0.107922E+10 | 0.683105E+09 | 0.396119E+09 | 0.00 | 0.00 |
April | 0.107738E+10 | 0.421481E+09 | 0.945369E+09 | 0.512855E+09 | 0.432514E+09 | 0.00 | 0.00 |
May | 0.101285E+10 | 0.252662E+09 | 0.820854E+09 | 0.280006E+09 | 0.540849E+09 | 0.00 | 0.00 |
June | 0.926214E+09 | 0.174922E+09 | 0.712681E+09 | 0.189286E+09 | 0.523395E+09 | 0.00 | 0.00 |
July | 0.108490E+10 | 0.173541E+09 | 0.805139E+09 | 0.254336E+09 | 0.550802E+09 | 0.00 | 0.00 |
August | 0.112312E+10 | 0.204342E+09 | 0.860250E+09 | 0.359411E+09 | 0.500839E+09 | 0.00 | 0.00 |
September | 0.108661E+10 | 0.298897E+09 | 0.892410E+09 | 0.475239E+09 | 0.417172E+09 | 0.00 | 0.00 |
October | 0.856004E+09 | 0.439378E+09 | 0.787946E+09 | 0.463603E+09 | 0.324343E+09 | 0.00 | 0.00 |
November | 0.650459E+09 | 0.612288E+09 | 0.679377E+09 | 0.426562E+09 | 0.252815E+09 | 0.00 | 0.00 |
December | 0.612262E+09 | 0.953053E+09 | 0.747223E+09 | 0.490154E+09 | 0.257069E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.115226E+11 | 0.591720E+10 | 0.104051E+11 | 0.555594E+10 | 0.484918E+10 | 0.00 | 0.00 |
Minimum of Months | 0.612262E+09 | 0.173541E+09 | 0.679377E+09 | 0.189286E+09 | 0.252815E+09 | 0.00 | 0.00 |
Maximum of Months | 0.112312E+10 | 0.982520E+09 | 0.110683E+10 | 0.747863E+09 | 0.550802E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.172873E+10 | 0.192758E+10 | 0.193562E+10 | 0.134704E+10 | 0.588582E+09 | 0.00 | 0.00 |
February | 0.224035E+10 | 0.144300E+10 | 0.221366E+10 | 0.149573E+10 | 0.717939E+09 | 0.00 | 0.00 |
March | 0.224826E+10 | 0.130237E+10 | 0.215845E+10 | 0.136621E+10 | 0.792237E+09 | 0.00 | 0.00 |
April | 0.216412E+10 | 0.817434E+09 | 0.189074E+10 | 0.102571E+10 | 0.865028E+09 | 0.00 | 0.00 |
May | 0.203423E+10 | 0.486639E+09 | 0.164171E+10 | 0.560011E+09 | 0.108170E+10 | 0.00 | 0.00 |
June | 0.185851E+10 | 0.335398E+09 | 0.142536E+10 | 0.378572E+09 | 0.104679E+10 | 0.00 | 0.00 |
July | 0.216983E+10 | 0.336026E+09 | 0.161028E+10 | 0.508672E+09 | 0.110160E+10 | 0.00 | 0.00 |
August | 0.224747E+10 | 0.396506E+09 | 0.172050E+10 | 0.718822E+09 | 0.100168E+10 | 0.00 | 0.00 |
September | 0.217788E+10 | 0.581996E+09 | 0.178482E+10 | 0.950478E+09 | 0.834343E+09 | 0.00 | 0.00 |
October | 0.171881E+10 | 0.858157E+09 | 0.157589E+10 | 0.927207E+09 | 0.648686E+09 | 0.00 | 0.00 |
November | 0.130867E+10 | 0.119416E+10 | 0.135875E+10 | 0.853123E+09 | 0.505630E+09 | 0.00 | 0.00 |
December | 0.123267E+10 | 0.186810E+10 | 0.149445E+10 | 0.980307E+09 | 0.514138E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.231295E+11 | 0.115474E+11 | 0.208102E+11 | 0.111119E+11 | 0.969835E+10 | 0.00 | 0.00 |
Minimum of Months | 0.123267E+10 | 0.335398E+09 | 0.135875E+10 | 0.378572E+09 | 0.505630E+09 | 0.00 | 0.00 |
Maximum of Months | 0.224826E+10 | 0.192758E+10 | 0.221366E+10 | 0.149573E+10 | 0.110160E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.861008E+09 | 0.969522E+09 | 0.967809E+09 | 0.673518E+09 | 0.294291E+09 | 0.00 | 0.00 |
February | 0.111672E+10 | 0.725290E+09 | 0.110683E+10 | 0.747863E+09 | 0.358969E+09 | 0.00 | 0.00 |
March | 0.112129E+10 | 0.654114E+09 | 0.107922E+10 | 0.683105E+09 | 0.396119E+09 | 0.00 | 0.00 |
April | 0.108021E+10 | 0.409018E+09 | 0.945369E+09 | 0.512855E+09 | 0.432514E+09 | 0.00 | 0.00 |
May | 0.101676E+10 | 0.242013E+09 | 0.820854E+09 | 0.280006E+09 | 0.540849E+09 | 0.00 | 0.00 |
June | 0.929511E+09 | 0.166137E+09 | 0.712681E+09 | 0.189286E+09 | 0.523395E+09 | 0.00 | 0.00 |
July | 0.108488E+10 | 0.166519E+09 | 0.805139E+09 | 0.254336E+09 | 0.550802E+09 | 0.00 | 0.00 |
August | 0.112308E+10 | 0.196831E+09 | 0.860250E+09 | 0.359411E+09 | 0.500839E+09 | 0.00 | 0.00 |
September | 0.108795E+10 | 0.289932E+09 | 0.892410E+09 | 0.475239E+09 | 0.417172E+09 | 0.00 | 0.00 |
October | 0.857869E+09 | 0.429140E+09 | 0.787946E+09 | 0.463603E+09 | 0.324343E+09 | 0.00 | 0.00 |
November | 0.652286E+09 | 0.599685E+09 | 0.679377E+09 | 0.426562E+09 | 0.252815E+09 | 0.00 | 0.00 |
December | 0.613659E+09 | 0.940187E+09 | 0.747223E+09 | 0.490154E+09 | 0.257069E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.115452E+11 | 0.578839E+10 | 0.104051E+11 | 0.555594E+10 | 0.484918E+10 | 0.00 | 0.00 |
Minimum of Months | 0.613659E+09 | 0.166137E+09 | 0.679377E+09 | 0.189286E+09 | 0.252815E+09 | 0.00 | 0.00 |
Maximum of Months | 0.112308E+10 | 0.969522E+09 | 0.110683E+10 | 0.747863E+09 | 0.550802E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.861162E+09 | 0.968769E+09 | 0.967809E+09 | 0.673518E+09 | 0.294291E+09 | 0.00 | 0.00 |
February | 0.111699E+10 | 0.724296E+09 | 0.110683E+10 | 0.747863E+09 | 0.358969E+09 | 0.00 | 0.00 |
March | 0.112170E+10 | 0.652647E+09 | 0.107922E+10 | 0.683105E+09 | 0.396119E+09 | 0.00 | 0.00 |
April | 0.108114E+10 | 0.406890E+09 | 0.945369E+09 | 0.512855E+09 | 0.432514E+09 | 0.00 | 0.00 |
May | 0.101852E+10 | 0.239819E+09 | 0.820854E+09 | 0.280006E+09 | 0.540849E+09 | 0.00 | 0.00 |
June | 0.931195E+09 | 0.164421E+09 | 0.712681E+09 | 0.189286E+09 | 0.523395E+09 | 0.00 | 0.00 |
July | 0.108563E+10 | 0.165623E+09 | 0.805139E+09 | 0.254336E+09 | 0.550802E+09 | 0.00 | 0.00 |
August | 0.112379E+10 | 0.195747E+09 | 0.860250E+09 | 0.359411E+09 | 0.500839E+09 | 0.00 | 0.00 |
September | 0.108895E+10 | 0.288211E+09 | 0.892410E+09 | 0.475239E+09 | 0.417172E+09 | 0.00 | 0.00 |
October | 0.858519E+09 | 0.427428E+09 | 0.787946E+09 | 0.463603E+09 | 0.324343E+09 | 0.00 | 0.00 |
November | 0.652670E+09 | 0.598143E+09 | 0.679377E+09 | 0.426562E+09 | 0.252815E+09 | 0.00 | 0.00 |
December | 0.613817E+09 | 0.939329E+09 | 0.747223E+09 | 0.490154E+09 | 0.257069E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.115541E+11 | 0.577132E+10 | 0.104051E+11 | 0.555594E+10 | 0.484918E+10 | 0.00 | 0.00 |
Minimum of Months | 0.613817E+09 | 0.164421E+09 | 0.679377E+09 | 0.189286E+09 | 0.252815E+09 | 0.00 | 0.00 |
Maximum of Months | 0.112379E+10 | 0.968769E+09 | 0.110683E+10 | 0.747863E+09 | 0.550802E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.862165E+09 | 0.963124E+09 | 0.967809E+09 | 0.673518E+09 | 0.294291E+09 | 0.00 | 0.00 |
February | 0.111842E+10 | 0.718223E+09 | 0.110683E+10 | 0.747863E+09 | 0.358969E+09 | 0.00 | 0.00 |
March | 0.112356E+10 | 0.644891E+09 | 0.107922E+10 | 0.683105E+09 | 0.396119E+09 | 0.00 | 0.00 |
April | 0.108412E+10 | 0.398747E+09 | 0.945369E+09 | 0.512855E+09 | 0.432514E+09 | 0.00 | 0.00 |
May | 0.102321E+10 | 0.233306E+09 | 0.820854E+09 | 0.280006E+09 | 0.540849E+09 | 0.00 | 0.00 |
June | 0.935389E+09 | 0.159768E+09 | 0.712681E+09 | 0.189286E+09 | 0.523395E+09 | 0.00 | 0.00 |
July | 0.108749E+10 | 0.163117E+09 | 0.805139E+09 | 0.254336E+09 | 0.550802E+09 | 0.00 | 0.00 |
August | 0.112553E+10 | 0.192796E+09 | 0.860250E+09 | 0.359411E+09 | 0.500839E+09 | 0.00 | 0.00 |
September | 0.109143E+10 | 0.283553E+09 | 0.892410E+09 | 0.475239E+09 | 0.417172E+09 | 0.00 | 0.00 |
October | 0.860384E+09 | 0.421653E+09 | 0.787946E+09 | 0.463603E+09 | 0.324343E+09 | 0.00 | 0.00 |
November | 0.654155E+09 | 0.591240E+09 | 0.679377E+09 | 0.426562E+09 | 0.252815E+09 | 0.00 | 0.00 |
December | 0.614753E+09 | 0.933109E+09 | 0.747223E+09 | 0.490154E+09 | 0.257069E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.115806E+11 | 0.570353E+10 | 0.104051E+11 | 0.555594E+10 | 0.484918E+10 | 0.00 | 0.00 |
Minimum of Months | 0.614753E+09 | 0.159768E+09 | 0.679377E+09 | 0.189286E+09 | 0.252815E+09 | 0.00 | 0.00 |
Maximum of Months | 0.112553E+10 | 0.963124E+09 | 0.110683E+10 | 0.747863E+09 | 0.550802E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.868655E+09 | 0.934384E+09 | 0.967809E+09 | 0.673518E+09 | 0.294291E+09 | 0.00 | 0.00 |
February | 0.112549E+10 | 0.690947E+09 | 0.110683E+10 | 0.747863E+09 | 0.358969E+09 | 0.00 | 0.00 |
March | 0.113195E+10 | 0.610406E+09 | 0.107922E+10 | 0.683105E+09 | 0.396119E+09 | 0.00 | 0.00 |
April | 0.109401E+10 | 0.366458E+09 | 0.945369E+09 | 0.512855E+09 | 0.432514E+09 | 0.00 | 0.00 |
May | 0.103600E+10 | 0.211678E+09 | 0.820854E+09 | 0.280006E+09 | 0.540849E+09 | 0.00 | 0.00 |
June | 0.945582E+09 | 0.145012E+09 | 0.712681E+09 | 0.189286E+09 | 0.523395E+09 | 0.00 | 0.00 |
July | 0.109246E+10 | 0.153655E+09 | 0.805139E+09 | 0.254336E+09 | 0.550802E+09 | 0.00 | 0.00 |
August | 0.113001E+10 | 0.182541E+09 | 0.860250E+09 | 0.359411E+09 | 0.500839E+09 | 0.00 | 0.00 |
September | 0.109718E+10 | 0.268635E+09 | 0.892410E+09 | 0.475239E+09 | 0.417172E+09 | 0.00 | 0.00 |
October | 0.866144E+09 | 0.400498E+09 | 0.787946E+09 | 0.463603E+09 | 0.324343E+09 | 0.00 | 0.00 |
November | 0.660005E+09 | 0.562759E+09 | 0.679377E+09 | 0.426562E+09 | 0.252815E+09 | 0.00 | 0.00 |
December | 0.620099E+09 | 0.903005E+09 | 0.747223E+09 | 0.490154E+09 | 0.257069E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.116676E+11 | 0.542998E+10 | 0.104051E+11 | 0.555594E+10 | 0.484918E+10 | 0.00 | 0.00 |
Minimum of Months | 0.620099E+09 | 0.145012E+09 | 0.679377E+09 | 0.189286E+09 | 0.252815E+09 | 0.00 | 0.00 |
Maximum of Months | 0.113195E+10 | 0.934384E+09 | 0.110683E+10 | 0.747863E+09 | 0.550802E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -16.9 | -17.4 | -20.0 | 3.73 | -31.9 | 33.25 | 98.18 | 0.00 |
February | -11.6 | -12.7 | -16.7 | 4.33 | -26.7 | 48.91 | 138.70 | 0.00 |
March | -6.2 | -7.6 | -10.8 | 3.55 | -19.4 | 56.69 | 163.76 | 0.01 |
April | 3.97 | 0.41 | -4.8 | 4.72 | -9.1 | 70.41 | 207.70 | 0.01 |
May | 13.43 | 8.45 | 3.53 | 3.60 | 2.20 | 102.27 | 202.62 | 0.00 |
June | 18.03 | 14.19 | 11.55 | 3.74 | 7.84 | 104.36 | 210.60 | 0.06 |
July | 19.67 | 16.51 | 14.78 | 3.14 | 8.97 | 101.67 | 223.82 | 0.04 |
August | 17.94 | 15.20 | 13.59 | 3.45 | 8.99 | 87.39 | 175.79 | 0.04 |
September | 12.29 | 9.87 | 7.80 | 3.78 | 3.34 | 70.27 | 143.96 | 0.00 |
October | 5.42 | 3.47 | 1.07 | 3.53 | -4.7 | 51.74 | 90.11 | 0.00 |
November | -2.0 | -3.6 | -6.9 | 4.42 | -13.7 | 34.68 | 65.95 | 0.00 |
December | -14.6 | -15.1 | -18.1 | 3.91 | -28.3 | 29.58 | 68.99 | 0.00 |
Annual Sum or Average | 3.36 | 1.04 | -2.0 | 3.82 | -8.4 | 66.03 | 149.18 | 0.01 |
Minimum of Months | -16.9 | -17.4 | -20.0 | 3.14 | -31.9 | 29.58 | 65.95 | 0.00 |
Maximum of Months | 19.67 | 16.51 | 14.78 | 4.72 | 8.99 | 104.36 | 223.82 | 0.06 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 1.10 | 29-JAN-14:00 | -1.0 | -4.4 | 2.60 | -11.4 | 145.00 | 110.00 |
February | 8.90 | 20-FEB-15:00 | 2.87 | -6.7 | 8.80 | -9.0 | 49.00 | 646.00 |
March | 11.10 | 26-MAR-15:00 | 5.48 | -1.1 | 5.20 | -5.7 | 53.00 | 842.00 |
April | 26.70 | 23-APR-15:00 | 16.95 | 11.10 | 11.30 | 12.03 | 75.50 | 811.00 |
May | 29.40 | 25-MAY-17:00 | 19.26 | 13.90 | 1.50 | 16.49 | 47.50 | 582.00 |
June | 35.00 | 29-JUN-15:00 | 24.72 | 21.10 | 6.70 | 24.66 | 132.00 | 705.00 |
July | 31.10 | 15-JUL-14:20 | 25.35 | 23.33 | 8.07 | 19.93 | 299.67 | 518.33 |
August | 30.60 | 08-AUG-14:00 | 23.36 | 20.60 | 6.70 | 17.93 | 163.50 | 672.50 |
September | 26.10 | 01-SEP-14:00 | 17.82 | 13.30 | 3.60 | 14.28 | 112.00 | 751.50 |
October | 22.20 | 19-OCT-14:00 | 13.62 | 7.20 | 6.70 | 8.15 | 35.50 | 701.50 |
November | 18.30 | 01-NOV-14:00 | 13.44 | 10.00 | 3.10 | 11.84 | 105.00 | 30.50 |
December | 1.10 | 28-DEC-02:00 | 0.43 | -0.6 | 4.60 | -5.5 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 1.10 | -1.0 | -6.7 | 1.50 | -11.4 | 0.00 | 0.00 | |
Maximum of Months | 35.00 | 25.35 | 23.33 | 11.30 | 24.66 | 299.67 | 842.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -35.6 | 06-JAN-08:00 | -35.7 | -37.8 | 0.00 | -57.8 | 27.00 | 381.00 |
February | -33.3 | 14-FEB-06:00 | -33.4 | -36.7 | 0.00 | -55.6 | 0.00 | 0.00 |
March | -28.9 | 05-MAR-06:00 | -29.1 | -32.2 | 1.50 | -50.6 | 27.00 | 41.50 |
April | -13.9 | 05-APR-05:00 | -14.4 | -16.1 | 0.00 | -32.5 | 14.50 | 199.00 |
May | -3.9 | 01-MAY-05:00 | -6.2 | -12.2 | 0.00 | -22.4 | 35.00 | 415.00 |
June | 1.10 | 04-JUN-04:00 | 0.62 | 0.00 | 0.00 | -14.9 | 37.00 | 169.50 |
July | 6.10 | 02-JUL-04:00 | 6.10 | 6.10 | 0.00 | -8.8 | 33.50 | 204.50 |
August | 4.40 | 19-AUG-03:00 | 4.40 | 4.40 | 0.00 | -10.7 | 0.00 | 0.00 |
September | 1.10 | 06-SEP-03:00 | 1.10 | 1.10 | 0.00 | -14.7 | 0.00 | 0.00 |
October | -10.0 | 30-OCT-03:00 | -10.7 | -12.8 | 1.50 | -28.2 | 0.00 | 0.00 |
November | -20.6 | 29-NOV-05:00 | -20.8 | -22.2 | 2.10 | -37.8 | 0.00 | 0.00 |
December | -31.1 | 24-DEC-06:19 | -31.3 | -35.1 | 3.33 | -53.1 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -35.6 | -35.7 | -37.8 | 0.00 | -57.8 | 0.00 | 0.00 | |
Maximum of Months | 6.10 | 6.10 | 6.10 | 3.33 | -8.8 | 37.00 | 415.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -0.5 | 16-JAN-12:00 | 0.00 | -1.1 | 5.70 | -6.6 | 172.50 | 3.00 |
February | 3.34 | 21-FEB-12:00 | 6.70 | -1.1 | 7.70 | -6.0 | 270.00 | 303.00 |
March | 5.48 | 26-MAR-15:00 | 11.10 | -1.1 | 5.20 | -5.7 | 53.00 | 842.00 |
April | 16.95 | 23-APR-15:00 | 26.70 | 11.10 | 11.30 | 12.03 | 75.50 | 811.00 |
May | 19.91 | 26-MAY-11:00 | 25.60 | 17.20 | 6.20 | 22.64 | 300.50 | 6.00 |
June | 24.72 | 29-JUN-15:00 | 35.00 | 21.10 | 6.70 | 24.66 | 132.00 | 705.00 |
July | 25.76 | 15-JUL-13:00 | 31.10 | 23.90 | 7.70 | 18.99 | 333.00 | 421.00 |
August | 23.36 | 08-AUG-14:00 | 30.60 | 20.60 | 6.70 | 17.93 | 163.50 | 672.50 |
September | 18.67 | 01-SEP-00:00 | 19.00 | 17.50 | 2.80 | 16.30 | 0.00 | 0.00 |
October | 13.72 | 19-OCT-13:00 | 21.70 | 7.80 | 5.70 | 7.75 | 54.50 | 739.00 |
November | 14.29 | 21-NOV-12:00 | 15.00 | 13.90 | 5.20 | 11.46 | 134.50 | 25.50 |
December | 0.43 | 28-DEC-02:00 | 1.10 | -0.6 | 4.60 | -5.5 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -0.5 | 0.00 | -1.1 | 2.80 | -6.6 | 0.00 | 0.00 | |
Maximum of Months | 25.76 | 35.00 | 23.90 | 11.30 | 24.66 | 333.00 | 842.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -1.1 | 16-JAN-11:00 | -0.6 | -0.8 | 5.70 | -7.3 | 164.50 | 5.00 |
February | -0.6 | 21-FEB-08:00 | 4.40 | 2.25 | 8.80 | -6.6 | 123.00 | 89.50 |
March | 0.00 | 29-MAR-20:00 | 1.70 | 0.95 | 1.50 | -4.8 | 0.00 | 0.00 |
April | 11.10 | 23-APR-13:00 | 24.40 | 16.08 | 10.80 | 9.72 | 98.50 | 903.50 |
May | 17.20 | 26-MAY-11:00 | 25.60 | 19.91 | 6.20 | 22.64 | 300.50 | 6.00 |
June | 22.80 | 29-JUN-23:19 | 26.30 | 23.71 | 5.20 | 14.28 | 0.00 | 0.00 |
July | 23.90 | 15-JUL-13:00 | 31.10 | 25.76 | 7.70 | 18.99 | 333.00 | 421.00 |
August | 20.60 | 08-AUG-14:00 | 30.60 | 23.36 | 6.70 | 17.93 | 163.50 | 672.50 |
September | 17.92 | 01-SEP-00:10 | 19.75 | 18.15 | 3.22 | 13.23 | 0.00 | 0.00 |
October | 12.20 | 07-OCT-12:20 | 14.47 | 13.17 | 3.43 | 9.20 | 163.17 | 18.50 |
November | 13.90 | 21-NOV-12:00 | 15.00 | 14.29 | 5.20 | 11.46 | 134.50 | 25.50 |
December | -0.0 | 05-DEC-17:00 | 0.00 | -0.0 | 1.50 | -6.4 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -1.1 | -0.6 | -0.8 | 1.50 | -7.3 | 0.00 | 0.00 | |
Maximum of Months | 23.90 | 31.10 | 25.76 | 10.80 | 22.64 | 333.00 | 903.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 1.89 | 11.66 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 0.58 | 19.92 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 0.81 | 26.63 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 2.58 | 37.52 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 5.43 | 45.25 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 8.61 | 47.76 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 11.25 | 48.86 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 12.66 | 38.94 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 12.41 | 29.23 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 10.60 | 17.37 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 7.72 | 10.89 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 4.55 | 9.11 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 6.63 | 28.63 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 0.58 | 9.11 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 12.66 | 48.86 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK1
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.407175E+09 | -280351771.0 | 0.00 | 0.00 | 744.00 | 0.00 | -126823528.1 | 59.00 | 0.00 | 0.00 |
February | 0.374620E+09 | -260417334.2 | 0.00 | 0.00 | 672.00 | 0.00 | -114202660.2 | 58.99 | 0.00 | 0.00 |
March | 0.417443E+09 | -291899898.2 | 0.00 | 0.00 | 744.00 | 0.00 | -125542780.9 | 58.99 | 0.00 | 0.00 |
April | 0.388691E+09 | -270394859.9 | 0.00 | 0.00 | 720.00 | 0.00 | -118296298.1 | 58.99 | 0.00 | 0.00 |
May | 0.381477E+09 | -265738239.7 | 0.00 | 0.00 | 744.00 | 0.00 | -115738772.3 | 58.99 | 0.00 | 0.00 |
June | 0.354377E+09 | -244333114.2 | 0.00 | 0.00 | 720.00 | 0.00 | -110044002.5 | 58.99 | 0.00 | 0.00 |
July | 0.347264E+09 | -234323303.9 | 0.00 | 0.00 | 744.00 | 0.00 | -112940904.9 | 58.99 | 0.00 | 0.00 |
August | 0.345268E+09 | -232297672.4 | 0.00 | 0.00 | 744.00 | 0.00 | -112970207.1 | 58.99 | 0.00 | 0.00 |
September | 0.333961E+09 | -223464227.6 | 0.00 | 0.00 | 720.00 | 0.00 | -110496722.5 | 58.99 | 0.00 | 0.00 |
October | 0.357083E+09 | -237648863.9 | 0.00 | 0.00 | 744.00 | 0.00 | -119433976.0 | 58.99 | 0.00 | 0.00 |
November | 0.363250E+09 | -242960533.0 | 0.00 | 0.00 | 720.00 | 0.00 | -120289784.9 | 58.99 | 0.00 | 0.00 |
December | 0.394149E+09 | -267641071.8 | 0.00 | 0.00 | 744.00 | 0.00 | -126507735.1 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.446476E+10 | -0.305147E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.141329E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.333961E+09 | -291899898.2 | 0.00 | 0.00 | 672.00 | 0.00 | -126823528.1 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.417443E+09 | -223464227.6 | 0.00 | 0.00 | 744.00 | 0.00 | -110044002.5 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK2
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.405804E+09 | -280357043.6 | 0.00 | 0.00 | 744.00 | 0.00 | -125446561.5 | 59.00 | 0.00 | 0.00 |
February | 0.373162E+09 | -260431583.9 | 0.00 | 0.00 | 672.00 | 0.00 | -112730616.5 | 58.99 | 0.00 | 0.00 |
March | 0.415774E+09 | -291896631.5 | 0.00 | 0.00 | 744.00 | 0.00 | -123877393.6 | 58.99 | 0.00 | 0.00 |
April | 0.387329E+09 | -270391967.4 | 0.00 | 0.00 | 720.00 | 0.00 | -116936939.7 | 58.99 | 0.00 | 0.00 |
May | 0.381142E+09 | -265734183.2 | 0.00 | 0.00 | 744.00 | 0.00 | -115407692.3 | 58.99 | 0.00 | 0.00 |
June | 0.354009E+09 | -244332827.4 | 0.00 | 0.00 | 720.00 | 0.00 | -109676037.7 | 58.99 | 0.00 | 0.00 |
July | 0.346996E+09 | -234336782.1 | 0.00 | 0.00 | 744.00 | 0.00 | -112659709.8 | 58.99 | 0.00 | 0.00 |
August | 0.345026E+09 | -232299832.1 | 0.00 | 0.00 | 744.00 | 0.00 | -112726365.9 | 58.99 | 0.00 | 0.00 |
September | 0.334190E+09 | -223453685.6 | 0.00 | 0.00 | 720.00 | 0.00 | -110736783.5 | 58.99 | 0.00 | 0.00 |
October | 0.356791E+09 | -237652401.2 | 0.00 | 0.00 | 744.00 | 0.00 | -119138231.0 | 58.99 | 0.00 | 0.00 |
November | 0.361747E+09 | -242953160.5 | 0.00 | 0.00 | 720.00 | 0.00 | -118793425.7 | 58.99 | 0.00 | 0.00 |
December | 0.392765E+09 | -267642943.5 | 0.00 | 0.00 | 744.00 | 0.00 | -125122349.9 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.445474E+10 | -0.305148E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.140325E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.334190E+09 | -291896631.5 | 0.00 | 0.00 | 672.00 | 0.00 | -125446561.5 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.415774E+09 | -223453685.6 | 0.00 | 0.00 | 744.00 | 0.00 | -109676037.7 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK3
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.374017E+09 | -246541417.2 | 0.00 | 0.00 | 744.00 | 0.00 | -127475954.1 | 59.00 | 0.00 | 0.00 |
February | 0.343496E+09 | -229187146.6 | 0.00 | 0.00 | 672.00 | 0.00 | -114308454.2 | 58.99 | 0.00 | 0.00 |
March | 0.385867E+09 | -260509972.0 | 0.00 | 0.00 | 744.00 | 0.00 | -125356941.4 | 58.99 | 0.00 | 0.00 |
April | 0.356379E+09 | -237805960.3 | 0.00 | 0.00 | 720.00 | 0.00 | -118573047.8 | 59.00 | 0.00 | 0.00 |
May | 0.351741E+09 | -235678723.0 | 0.00 | 0.00 | 744.00 | 0.00 | -116062315.3 | 59.00 | 0.00 | 0.00 |
June | 0.326883E+09 | -217615311.9 | 0.00 | 0.00 | 720.00 | 0.00 | -109267323.4 | 58.98 | 0.00 | 0.00 |
July | 0.316308E+09 | -204841438.7 | 0.00 | 0.00 | 744.00 | 0.00 | -111467026.2 | 58.99 | 0.00 | 0.00 |
August | 0.319351E+09 | -207489290.9 | 0.00 | 0.00 | 744.00 | 0.00 | -111861545.0 | 58.99 | 0.00 | 0.00 |
September | 0.307685E+09 | -196385019.4 | 0.00 | 0.00 | 720.00 | 0.00 | -111299498.8 | 59.00 | 0.00 | 0.00 |
October | 0.330001E+09 | -209004987.4 | 0.00 | 0.00 | 744.00 | 0.00 | -120995715.8 | 58.99 | 0.00 | 0.00 |
November | 0.334932E+09 | -214517912.3 | 0.00 | 0.00 | 720.00 | 0.00 | -120414536.9 | 58.99 | 0.00 | 0.00 |
December | 0.360707E+09 | -233597093.7 | 0.00 | 0.00 | 744.00 | 0.00 | -127109969.8 | 59.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.410737E+10 | -0.269317E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.141419E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.307685E+09 | -260509972.0 | 0.00 | 0.00 | 672.00 | 0.00 | -127475954.1 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.385867E+09 | -196385019.4 | 0.00 | 0.00 | 744.00 | 0.00 | -109267323.4 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK4
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.374423E+09 | -246548360.4 | 0.00 | 0.00 | 744.00 | 0.00 | -127874509.1 | 58.99 | 0.00 | 0.00 |
February | 0.343877E+09 | -229171007.5 | 0.00 | 0.00 | 672.00 | 0.00 | -114705629.7 | 59.00 | 0.00 | 0.00 |
March | 0.386222E+09 | -260514333.8 | 0.00 | 0.00 | 744.00 | 0.00 | -125707565.6 | 58.99 | 0.00 | 0.00 |
April | 0.356820E+09 | -237795916.8 | 0.00 | 0.00 | 720.00 | 0.00 | -119024178.4 | 59.00 | 0.00 | 0.00 |
May | 0.352154E+09 | -235705815.5 | 0.00 | 0.00 | 744.00 | 0.00 | -116448222.9 | 58.99 | 0.00 | 0.00 |
June | 0.327111E+09 | -217594142.3 | 0.00 | 0.00 | 720.00 | 0.00 | -109516489.3 | 58.99 | 0.00 | 0.00 |
July | 0.316334E+09 | -204831981.3 | 0.00 | 0.00 | 744.00 | 0.00 | -111502244.7 | 59.00 | 0.00 | 0.00 |
August | 0.319411E+09 | -207492701.4 | 0.00 | 0.00 | 744.00 | 0.00 | -111918588.4 | 58.99 | 0.00 | 0.00 |
September | 0.308056E+09 | -196374217.0 | 0.00 | 0.00 | 720.00 | 0.00 | -111681939.6 | 59.00 | 0.00 | 0.00 |
October | 0.330473E+09 | -209033251.3 | 0.00 | 0.00 | 744.00 | 0.00 | -121439574.2 | 58.98 | 0.00 | 0.00 |
November | 0.335322E+09 | -214507097.5 | 0.00 | 0.00 | 720.00 | 0.00 | -120814858.3 | 58.99 | 0.00 | 0.00 |
December | 0.361100E+09 | -233621565.0 | 0.00 | 0.00 | 744.00 | 0.00 | -127478913.2 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.411130E+10 | -0.269319E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.141811E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.308056E+09 | -260514333.8 | 0.00 | 0.00 | 672.00 | 0.00 | -127874509.1 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.386222E+09 | -196374217.0 | 0.00 | 0.00 | 744.00 | 0.00 | -109516489.3 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK5
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.362611E+09 | -233032089.4 | 0.00 | 0.00 | 744.00 | 0.00 | -129578830.1 | 58.99 | 0.00 | 0.00 |
February | 0.333019E+09 | -216739643.0 | 0.00 | 0.00 | 672.00 | 0.00 | -116279379.8 | 58.99 | 0.00 | 0.00 |
March | 0.373849E+09 | -246500646.9 | 0.00 | 0.00 | 744.00 | 0.00 | -127348693.3 | 58.99 | 0.00 | 0.00 |
April | 0.345627E+09 | -225034809.1 | 0.00 | 0.00 | 720.00 | 0.00 | -120592189.2 | 59.00 | 0.00 | 0.00 |
May | 0.340926E+09 | -222906631.3 | 0.00 | 0.00 | 744.00 | 0.00 | -118018928.6 | 58.99 | 0.00 | 0.00 |
June | 0.316685E+09 | -205867190.3 | 0.00 | 0.00 | 720.00 | 0.00 | -110818187.5 | 59.00 | 0.00 | 0.00 |
July | 0.305981E+09 | -193728779.4 | 0.00 | 0.00 | 744.00 | 0.00 | -112252391.9 | 58.99 | 0.00 | 0.00 |
August | 0.309082E+09 | -196332442.5 | 0.00 | 0.00 | 744.00 | 0.00 | -112749760.3 | 58.99 | 0.00 | 0.00 |
September | 0.298701E+09 | -185846379.1 | 0.00 | 0.00 | 720.00 | 0.00 | -112855046.0 | 58.99 | 0.00 | 0.00 |
October | 0.320279E+09 | -197554293.6 | 0.00 | 0.00 | 744.00 | 0.00 | -122725171.4 | 58.99 | 0.00 | 0.00 |
November | 0.324904E+09 | -202624031.2 | 0.00 | 0.00 | 720.00 | 0.00 | -122279613.0 | 58.98 | 0.00 | 0.00 |
December | 0.350129E+09 | -220928604.8 | 0.00 | 0.00 | 744.00 | 0.00 | -129200568.2 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.398179E+10 | -0.254710E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.143470E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.298701E+09 | -246500646.9 | 0.00 | 0.00 | 672.00 | 0.00 | -129578830.1 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.373849E+09 | -185846379.1 | 0.00 | 0.00 | 744.00 | 0.00 | -110818187.5 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK6
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.362457E+09 | -233020844.7 | 0.00 | 0.00 | 744.00 | 0.00 | -129435704.6 | 58.99 | 0.00 | 0.00 |
February | 0.332901E+09 | -216729882.0 | 0.00 | 0.00 | 672.00 | 0.00 | -116171292.9 | 58.99 | 0.00 | 0.00 |
March | 0.373753E+09 | -246487564.1 | 0.00 | 0.00 | 744.00 | 0.00 | -127265790.3 | 59.00 | 0.00 | 0.00 |
April | 0.345648E+09 | -225036850.1 | 0.00 | 0.00 | 720.00 | 0.00 | -120611191.4 | 59.00 | 0.00 | 0.00 |
May | 0.341054E+09 | -222902958.1 | 0.00 | 0.00 | 744.00 | 0.00 | -118150883.6 | 58.99 | 0.00 | 0.00 |
June | 0.316826E+09 | -205866192.6 | 0.00 | 0.00 | 720.00 | 0.00 | -110959971.9 | 59.00 | 0.00 | 0.00 |
July | 0.306083E+09 | -193724960.6 | 0.00 | 0.00 | 744.00 | 0.00 | -112358079.3 | 58.99 | 0.00 | 0.00 |
August | 0.309179E+09 | -196342144.1 | 0.00 | 0.00 | 744.00 | 0.00 | -112836406.6 | 58.99 | 0.00 | 0.00 |
September | 0.298803E+09 | -185841199.6 | 0.00 | 0.00 | 720.00 | 0.00 | -112961857.9 | 58.99 | 0.00 | 0.00 |
October | 0.320323E+09 | -197548943.8 | 0.00 | 0.00 | 744.00 | 0.00 | -122773861.1 | 58.99 | 0.00 | 0.00 |
November | 0.324853E+09 | -202577716.0 | 0.00 | 0.00 | 720.00 | 0.00 | -122274813.8 | 59.00 | 0.00 | 0.00 |
December | 0.349966E+09 | -220936543.1 | 0.00 | 0.00 | 744.00 | 0.00 | -129029503.9 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.398185E+10 | -0.254702E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.143483E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.298803E+09 | -246487564.1 | 0.00 | 0.00 | 672.00 | 0.00 | -129435704.6 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.373753E+09 | -185841199.6 | 0.00 | 0.00 | 744.00 | 0.00 | -110959971.9 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK7
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.362499E+09 | -233025103.3 | 0.00 | 0.00 | 744.00 | 0.00 | -129474056.1 | 58.99 | 0.00 | 0.00 |
February | 0.332961E+09 | -216733051.8 | 0.00 | 0.00 | 672.00 | 0.00 | -116227469.1 | 58.99 | 0.00 | 0.00 |
March | 0.373850E+09 | -246488799.5 | 0.00 | 0.00 | 744.00 | 0.00 | -127360923.8 | 59.00 | 0.00 | 0.00 |
April | 0.345819E+09 | -225033604.7 | 0.00 | 0.00 | 720.00 | 0.00 | -120785040.7 | 59.00 | 0.00 | 0.00 |
May | 0.341299E+09 | -222897513.3 | 0.00 | 0.00 | 744.00 | 0.00 | -118401641.2 | 58.99 | 0.00 | 0.00 |
June | 0.317009E+09 | -205919464.9 | 0.00 | 0.00 | 720.00 | 0.00 | -111089818.6 | 58.98 | 0.00 | 0.00 |
July | 0.306178E+09 | -193733609.4 | 0.00 | 0.00 | 744.00 | 0.00 | -112444619.8 | 58.99 | 0.00 | 0.00 |
August | 0.309272E+09 | -196329904.5 | 0.00 | 0.00 | 744.00 | 0.00 | -112942514.6 | 58.99 | 0.00 | 0.00 |
September | 0.298977E+09 | -185846635.3 | 0.00 | 0.00 | 720.00 | 0.00 | -113130245.1 | 58.99 | 0.00 | 0.00 |
October | 0.320452E+09 | -197541933.2 | 0.00 | 0.00 | 744.00 | 0.00 | -122910524.0 | 58.99 | 0.00 | 0.00 |
November | 0.324950E+09 | -202568494.5 | 0.00 | 0.00 | 720.00 | 0.00 | -122381102.3 | 59.00 | 0.00 | 0.00 |
December | 0.350020E+09 | -220925957.2 | 0.00 | 0.00 | 744.00 | 0.00 | -129093848.5 | 59.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.398329E+10 | -0.254704E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.143624E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.298977E+09 | -246488799.5 | 0.00 | 0.00 | 672.00 | 0.00 | -129474056.1 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.373850E+09 | -185846635.3 | 0.00 | 0.00 | 744.00 | 0.00 | -111089818.6 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 243.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 265.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 254.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 296.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 437.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 401.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 409.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 352.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 344.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 299.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 255.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 226.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3785.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 226.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 437.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 HEATING COIL
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.285708E+11 | 68267.32 | 01-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.164392E+11 | 68267.32 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.125295E+11 | 68267.32 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.372932E+10 | 68267.32 | 01-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 88485493.28 | 68267.32 | 01-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.135022E+10 | 68267.32 | 06-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.788100E+10 | 68267.32 | 01-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.248172E+11 | 68267.32 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.954058E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.285708E+11 | 68267.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 HEATING COIL
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.163006E+11 | 34664.72 | 01-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.107713E+11 | 34664.72 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.897002E+10 | 34664.72 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.292066E+10 | 34664.72 | 02-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 95403571.12 | 33529.38 | 01-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 5227981.87 | 1543.33 | 28-SEP-08:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.187642E+10 | 34664.72 | 30-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.643820E+10 | 34664.72 | 04-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.150254E+11 | 34664.72 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.624032E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.163006E+11 | 34664.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3 HEATING COIL
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.177164E+11 | 34709.29 | 01-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.120371E+11 | 34709.29 | 01-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.102291E+11 | 34709.29 | 01-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.372358E+10 | 34709.29 | 02-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.235431E+09 | 34709.29 | 01-MAY-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 78536957.07 | 5077.60 | 23-SEP-07:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.272361E+10 | 34709.29 | 30-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.756834E+10 | 34709.29 | 05-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.163510E+11 | 34709.29 | 01-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.706631E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.177164E+11 | 34709.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4 HEATING COIL
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.180030E+11 | 35403.76 | 01-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.122524E+11 | 35403.76 | 01-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.104434E+11 | 35403.76 | 01-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.391172E+10 | 35403.76 | 02-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.290928E+09 | 35403.76 | 01-MAY-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.129977E+09 | 5108.22 | 23-SEP-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.294660E+10 | 35403.76 | 30-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.780322E+10 | 35403.76 | 04-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.166110E+11 | 35403.76 | 01-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.723923E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.180030E+11 | 35403.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5 HEATING COIL
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.184530E+11 | 35171.36 | 01-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.126405E+11 | 35171.36 | 01-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.108515E+11 | 35171.36 | 01-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.422009E+10 | 35171.36 | 02-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.374170E+09 | 35171.36 | 01-MAY-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.198647E+09 | 5303.78 | 23-SEP-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.322882E+10 | 35171.36 | 30-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.817533E+10 | 35171.36 | 04-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.170494E+11 | 35171.36 | 01-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.751914E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.184530E+11 | 35171.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6 HEATING COIL
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.349151E+11 | 65473.01 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.239012E+11 | 65473.01 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.206921E+11 | 65473.01 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.829628E+10 | 65473.01 | 01-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.857673E+09 | 65473.01 | 01-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 2271872.22 | 1597.10 | 03-JUN-08:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.604655E+09 | 28048.75 | 23-SEP-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.662823E+10 | 65473.01 | 05-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.158275E+11 | 65473.01 | 01-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.323684E+11 | 65473.01 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144093E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.349151E+11 | 65473.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7 HEATING COIL
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.180559E+11 | 34255.70 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.123834E+11 | 34255.70 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.107438E+11 | 34255.70 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.434078E+10 | 34255.70 | 01-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.457314E+09 | 34255.70 | 01-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 1501644.29 | 2284.54 | 04-JUN-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.316028E+09 | 15047.72 | 23-SEP-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.343343E+10 | 34255.70 | 05-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.821451E+10 | 34255.70 | 01-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.167478E+11 | 34255.70 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.746945E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.180559E+11 | 34255.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8 HEATING COIL
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.181166E+11 | 34238.74 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.124560E+11 | 34238.74 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.108375E+11 | 34238.74 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.444393E+10 | 34238.74 | 01-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.498532E+09 | 34238.74 | 01-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 2979721.91 | 4921.91 | 04-JUN-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.344728E+09 | 17127.01 | 23-SEP-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.351160E+10 | 34238.74 | 05-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.829870E+10 | 34238.74 | 01-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168101E+11 | 34238.74 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.753206E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.181166E+11 | 34238.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9 HEATING COIL
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.185985E+11 | 34520.58 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.128880E+11 | 34520.58 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.113474E+11 | 34520.58 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.486147E+10 | 34520.58 | 01-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.652940E+09 | 34520.58 | 01-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 12610149.56 | 12395.02 | 04-JUN-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.428152E+09 | 24036.23 | 23-SEP-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.379703E+10 | 34520.58 | 04-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.869470E+10 | 34520.58 | 01-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.172791E+11 | 34520.58 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.785599E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.185985E+11 | 34520.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10 HEATING COIL
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.230005E+11 | 38731.23 | 01-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.163434E+11 | 38731.23 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.144921E+11 | 38731.23 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.660989E+10 | 38731.23 | 01-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.118478E+10 | 38731.23 | 01-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 82575620.36 | 29609.28 | 04-JUN-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 831056.22 | 617.37 | 09-JUL-09:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7285719.82 | 7609.23 | 19-AUG-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.672747E+09 | 38731.23 | 23-SEP-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.475678E+10 | 38731.23 | 03-OCT-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.106098E+11 | 38731.23 | 01-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.212359E+11 | 38731.23 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.989967E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 831056.22 | 617.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.230005E+11 | 38731.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.188334E+09 | 0.161920E+09 | 9145.00 | 23-APR-16:10 | 7906.40 | 0.00 |
May | 0.00 | 0.00 | 0.293302E+10 | 0.252872E+10 | 14568.63 | 25-MAY-16:10 | 11684.47 | 0.00 |
June | 0.00 | 0.00 | 0.780273E+10 | 0.572470E+10 | 44056.55 | 30-JUN-07:02 | 25663.01 | 0.00 |
July | 0.00 | 0.00 | 0.130017E+11 | 0.895513E+10 | 44401.23 | 23-JUL-07:02 | 20257.76 | 0.00 |
August | 0.00 | 0.00 | 0.934146E+10 | 0.649866E+10 | 34214.02 | 09-AUG-07:03 | 17886.95 | 0.00 |
September | 0.00 | 0.00 | 0.141323E+10 | 0.113731E+10 | 15389.33 | 01-SEP-13:00 | 11726.41 | 0.00 |
October | 0.00 | 0.00 | 0.109292E+09 | 0.101243E+09 | 4155.84 | 19-OCT-15:00 | 3950.12 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.347897E+11 | 0.251077E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.130017E+11 | 0.895513E+10 | 44401.23 | 25663.01 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.132705E+09 | 0.116719E+09 | 20400.44 | 23-APR-18:41 | 18606.30 | 0.00 |
May | 0.00 | 0.00 | 0.218707E+10 | 0.191593E+10 | 21000.44 | 25-MAY-20:32 | 16687.48 | 0.00 |
June | 0.00 | 0.00 | 0.559786E+10 | 0.406357E+10 | 22505.74 | 27-JUN-20:03 | 11562.94 | 0.00 |
July | 0.00 | 0.00 | 0.899163E+10 | 0.610521E+10 | 22663.88 | 23-JUL-07:02 | 11134.46 | 0.00 |
August | 0.00 | 0.00 | 0.640347E+10 | 0.440588E+10 | 22464.40 | 31-AUG-20:03 | 11657.44 | 0.00 |
September | 0.00 | 0.00 | 0.104640E+10 | 0.839836E+09 | 21545.01 | 17-SEP-17:03 | 12366.36 | 0.00 |
October | 0.00 | 0.00 | 84564521.67 | 78969604.58 | 3001.48 | 20-OCT-20:10 | 3001.48 | 0.00 |
November | 0.00 | 0.00 | 217265.59 | 171864.34 | 362.11 | 01-NOV-20:40 | 286.44 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.244439E+11 | 0.175263E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.899163E+10 | 0.610521E+10 | 22663.88 | 18606.30 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3 COOLING COIL
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 41683719.02 | 36697061.92 | 4223.21 | 23-APR-16:00 | 3802.88 | 0.00 |
May | 0.00 | 0.00 | 0.153188E+10 | 0.133867E+10 | 9001.90 | 26-MAY-06:03 | 6041.68 | 0.00 |
June | 0.00 | 0.00 | 0.404062E+10 | 0.298817E+10 | 23071.65 | 30-JUN-06:02 | 12875.00 | 0.00 |
July | 0.00 | 0.00 | 0.630617E+10 | 0.440057E+10 | 22963.94 | 23-JUL-07:02 | 10628.27 | 0.00 |
August | 0.00 | 0.00 | 0.454280E+10 | 0.317276E+10 | 21891.61 | 09-AUG-06:03 | 11278.13 | 0.00 |
September | 0.00 | 0.00 | 0.660138E+09 | 0.542444E+09 | 12190.62 | 01-SEP-06:03 | 5808.82 | 0.00 |
October | 0.00 | 0.00 | 42418294.83 | 39868849.26 | 1919.63 | 19-OCT-15:00 | 1847.86 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.171657E+11 | 0.125192E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.630617E+10 | 0.440057E+10 | 23071.65 | 12875.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4 COOLING COIL
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 37572599.15 | 33076267.64 | 3960.72 | 23-APR-16:00 | 3562.12 | 0.00 |
May | 0.00 | 0.00 | 0.147949E+10 | 0.129070E+10 | 8867.57 | 25-MAY-16:10 | 7232.04 | 0.00 |
June | 0.00 | 0.00 | 0.397836E+10 | 0.293452E+10 | 23140.90 | 30-JUN-06:02 | 12939.01 | 0.00 |
July | 0.00 | 0.00 | 0.628526E+10 | 0.438463E+10 | 23029.22 | 23-JUL-07:02 | 10663.78 | 0.00 |
August | 0.00 | 0.00 | 0.449886E+10 | 0.314105E+10 | 21953.70 | 09-AUG-06:03 | 11311.40 | 0.00 |
September | 0.00 | 0.00 | 0.626981E+09 | 0.514723E+09 | 12191.01 | 01-SEP-06:03 | 5807.64 | 0.00 |
October | 0.00 | 0.00 | 33290103.85 | 31387044.40 | 1720.10 | 19-OCT-15:00 | 1655.99 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.169398E+11 | 0.123301E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.628526E+10 | 0.438463E+10 | 23140.90 | 12939.01 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5 COOLING COIL
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 33003827.08 | 29024353.36 | 3639.55 | 23-APR-16:00 | 3266.31 | 0.00 |
May | 0.00 | 0.00 | 0.137274E+10 | 0.119544E+10 | 8647.80 | 25-MAY-16:10 | 7038.53 | 0.00 |
June | 0.00 | 0.00 | 0.378291E+10 | 0.277609E+10 | 22939.16 | 30-JUN-06:02 | 12669.55 | 0.00 |
July | 0.00 | 0.00 | 0.605670E+10 | 0.421665E+10 | 22841.66 | 23-JUL-07:02 | 10541.37 | 0.00 |
August | 0.00 | 0.00 | 0.429691E+10 | 0.299684E+10 | 21774.87 | 09-AUG-06:03 | 11182.74 | 0.00 |
September | 0.00 | 0.00 | 0.569918E+09 | 0.466752E+09 | 10263.95 | 01-SEP-06:03 | 4844.53 | 0.00 |
October | 0.00 | 0.00 | 22662029.05 | 21436343.00 | 1446.56 | 19-OCT-15:00 | 1391.36 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.161348E+11 | 0.117022E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.605670E+10 | 0.421665E+10 | 22939.16 | 12669.55 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6 COOLING COIL
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 55072724.17 | 47062975.16 | 6512.83 | 23-APR-15:00 | 5555.06 | 0.00 |
May | 0.00 | 0.00 | 0.229697E+10 | 0.195561E+10 | 16041.21 | 25-MAY-15:00 | 12478.38 | 0.00 |
June | 0.00 | 0.00 | 0.652628E+10 | 0.466100E+10 | 41551.81 | 30-JUN-07:02 | 23805.86 | 0.00 |
July | 0.00 | 0.00 | 0.105960E+11 | 0.719991E+10 | 41851.67 | 23-JUL-08:62 | 20718.35 | 0.00 |
August | 0.00 | 0.00 | 0.744463E+10 | 0.506781E+10 | 35326.70 | 09-AUG-07:03 | 18623.27 | 0.00 |
September | 0.00 | 0.00 | 0.928857E+09 | 0.746307E+09 | 15719.38 | 01-SEP-14:10 | 12257.79 | 0.00 |
October | 0.00 | 0.00 | 30964241.64 | 29087916.45 | 2662.39 | 19-OCT-15:00 | 2502.83 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.278788E+11 | 0.197068E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.105960E+11 | 0.719991E+10 | 41851.67 | 23805.86 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7 COOLING COIL
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 26403008.03 | 22610974.72 | 3242.23 | 23-APR-15:00 | 2768.63 | 0.00 |
May | 0.00 | 0.00 | 0.114913E+10 | 0.980277E+09 | 8273.60 | 25-MAY-15:00 | 6439.93 | 0.00 |
June | 0.00 | 0.00 | 0.330227E+10 | 0.235889E+10 | 22283.95 | 30-JUN-07:02 | 12774.80 | 0.00 |
July | 0.00 | 0.00 | 0.539121E+10 | 0.367476E+10 | 22458.52 | 23-JUL-08:62 | 11140.11 | 0.00 |
August | 0.00 | 0.00 | 0.375828E+10 | 0.256870E+10 | 16312.73 | 09-AUG-07:03 | 8572.96 | 0.00 |
September | 0.00 | 0.00 | 0.451445E+09 | 0.362891E+09 | 8142.60 | 01-SEP-14:20 | 6400.22 | 0.00 |
October | 0.00 | 0.00 | 12486725.61 | 11779857.83 | 1279.32 | 19-OCT-15:00 | 1207.36 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.140912E+11 | 0.997991E+10 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.539121E+10 | 0.367476E+10 | 22458.52 | 12774.80 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8 COOLING COIL
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 24791614.17 | 21175849.48 | 3115.28 | 23-APR-15:00 | 2652.53 | 0.00 |
May | 0.00 | 0.00 | 0.110598E+10 | 0.941286E+09 | 8152.94 | 25-MAY-15:00 | 6327.86 | 0.00 |
June | 0.00 | 0.00 | 0.322409E+10 | 0.229374E+10 | 22301.84 | 30-JUN-07:02 | 12717.98 | 0.00 |
July | 0.00 | 0.00 | 0.530848E+10 | 0.360975E+10 | 22480.29 | 23-JUL-08:62 | 11126.10 | 0.00 |
August | 0.00 | 0.00 | 0.368503E+10 | 0.251415E+10 | 15275.53 | 09-AUG-07:03 | 7989.94 | 0.00 |
September | 0.00 | 0.00 | 0.434376E+09 | 0.347789E+09 | 8089.94 | 01-SEP-14:20 | 6344.87 | 0.00 |
October | 0.00 | 0.00 | 10461118.22 | 9859682.55 | 1207.11 | 19-OCT-15:00 | 1136.60 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.137932E+11 | 0.973775E+10 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.530848E+10 | 0.360975E+10 | 22480.29 | 12717.98 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9 COOLING COIL
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 20288339.38 | 17275824.76 | 2736.57 | 23-APR-15:00 | 2321.12 | 0.00 |
May | 0.00 | 0.00 | 0.994339E+09 | 0.844161E+09 | 7827.00 | 25-MAY-15:00 | 6047.18 | 0.00 |
June | 0.00 | 0.00 | 0.302144E+10 | 0.213623E+10 | 22630.62 | 30-JUN-07:02 | 12736.79 | 0.00 |
July | 0.00 | 0.00 | 0.509039E+10 | 0.345264E+10 | 22822.99 | 23-JUL-08:62 | 11251.49 | 0.00 |
August | 0.00 | 0.00 | 0.349198E+10 | 0.238085E+10 | 12448.72 | 08-AUG-15:00 | 8043.93 | 0.00 |
September | 0.00 | 0.00 | 0.391767E+09 | 0.311525E+09 | 7985.68 | 01-SEP-14:20 | 6250.35 | 0.00 |
October | 0.00 | 0.00 | 5972325.97 | 5604195.55 | 1019.83 | 19-OCT-15:00 | 959.13 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.130162E+11 | 0.914829E+10 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.509039E+10 | 0.345264E+10 | 22822.99 | 12736.79 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10 COOLING COIL
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 10484448.38 | 8859731.80 | 1813.36 | 23-APR-16:00 | 1550.11 | 0.00 |
May | 0.00 | 0.00 | 0.845457E+09 | 0.714172E+09 | 7459.65 | 25-MAY-15:00 | 5710.51 | 0.00 |
June | 0.00 | 0.00 | 0.281142E+10 | 0.197537E+10 | 25875.47 | 30-JUN-07:02 | 12319.73 | 0.00 |
July | 0.00 | 0.00 | 0.494568E+10 | 0.336508E+10 | 23909.41 | 23-JUL-08:62 | 11590.71 | 0.00 |
August | 0.00 | 0.00 | 0.329527E+10 | 0.226559E+10 | 12735.87 | 08-AUG-15:00 | 8213.45 | 0.00 |
September | 0.00 | 0.00 | 0.341298E+09 | 0.269305E+09 | 8269.10 | 01-SEP-14:10 | 6456.14 | 0.00 |
October | 0.00 | 0.00 | 2306482.52 | 2153336.18 | 683.62 | 19-OCT-15:00 | 644.38 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.122519E+11 | 0.860053E+10 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.494568E+10 | 0.336508E+10 | 25875.47 | 12319.73 | 0.00 |
Report: FanReportMonthly
For: PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.204110E+10 | 0.49 | 2080.36 | 01-JAN-08:61 | 0.92 |
February | 0.167084E+10 | 0.44 | 2080.36 | 01-FEB-08:61 | 0.92 |
March | 0.174832E+10 | 0.42 | 2080.36 | 01-MAR-08:61 | 0.92 |
April | 0.153123E+10 | 0.39 | 2080.36 | 01-APR-07:01 | 0.92 |
May | 0.151146E+10 | 0.37 | 2080.36 | 01-MAY-07:01 | 0.92 |
June | 0.147068E+10 | 0.37 | 2080.36 | 29-JUN-07:03 | 0.90 |
July | 0.151077E+10 | 0.37 | 2080.36 | 04-JUL-07:03 | 0.90 |
August | 0.151297E+10 | 0.37 | 1598.08 | 09-AUG-07:03 | 0.80 |
September | 0.146491E+10 | 0.37 | 832.14 | 02-SEP-12:00 | 0.55 |
October | 0.153465E+10 | 0.38 | 2080.36 | 06-OCT-07:01 | 0.92 |
November | 0.160474E+10 | 0.41 | 2080.36 | 01-NOV-07:01 | 0.92 |
December | 0.197523E+10 | 0.46 | 2080.36 | 01-DEC-08:61 | 0.92 |
Annual Sum or Average | 0.195769E+11 | 0.41 | |||
Minimum of Months | 0.146491E+10 | 0.37 | 832.14 | 0.55 | |
Maximum of Months | 0.204110E+10 | 0.49 | 2080.36 | 0.92 |
Report: FanReportMonthly
For: PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.937722E+09 | 0.49 | 1128.61 | 01-JAN-08:61 | 0.95 |
February | 0.767186E+09 | 0.43 | 1128.61 | 01-FEB-08:61 | 0.95 |
March | 0.798945E+09 | 0.37 | 1128.61 | 01-MAR-08:61 | 0.95 |
April | 0.664112E+09 | 0.33 | 1128.61 | 02-APR-07:01 | 0.95 |
May | 0.728237E+09 | 0.37 | 1106.44 | 01-MAY-07:01 | 0.94 |
June | 0.744733E+09 | 0.38 | 1128.61 | 25-JUN-07:03 | 0.93 |
July | 0.761028E+09 | 0.37 | 1128.61 | 04-JUL-07:03 | 0.93 |
August | 0.769783E+09 | 0.38 | 1128.61 | 09-AUG-07:03 | 0.93 |
September | 0.724649E+09 | 0.38 | 481.59 | 28-SEP-08:30 | 0.60 |
October | 0.683238E+09 | 0.34 | 1128.61 | 30-OCT-07:01 | 0.95 |
November | 0.721048E+09 | 0.34 | 1128.61 | 04-NOV-07:01 | 0.95 |
December | 0.907988E+09 | 0.47 | 1128.61 | 01-DEC-08:61 | 0.95 |
Annual Sum or Average | 0.920867E+10 | 0.39 | |||
Minimum of Months | 0.664112E+09 | 0.33 | 481.59 | 0.60 | |
Maximum of Months | 0.937722E+09 | 0.49 | 1128.61 | 0.95 |
Report: FanReportMonthly
For: PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.100599E+10 | 0.40 | 1136.35 | 01-JAN-08:61 | 0.95 |
February | 0.832080E+09 | 0.38 | 1136.35 | 01-FEB-07:01 | 0.95 |
March | 0.871836E+09 | 0.37 | 1136.35 | 01-MAR-07:01 | 0.95 |
April | 0.711318E+09 | 0.33 | 1136.35 | 02-APR-07:01 | 0.95 |
May | 0.668980E+09 | 0.31 | 1136.35 | 01-MAY-06:01 | 0.95 |
June | 0.656878E+09 | 0.32 | 1136.35 | 25-JUN-07:03 | 0.93 |
July | 0.660566E+09 | 0.31 | 1136.35 | 04-JUL-07:03 | 0.93 |
August | 0.672816E+09 | 0.31 | 1136.35 | 09-AUG-06:03 | 0.93 |
September | 0.639737E+09 | 0.31 | 554.28 | 23-SEP-07:07 | 0.65 |
October | 0.711311E+09 | 0.33 | 1136.35 | 30-OCT-06:01 | 0.95 |
November | 0.786842E+09 | 0.35 | 1136.35 | 05-NOV-07:01 | 0.95 |
December | 0.975810E+09 | 0.40 | 1136.35 | 01-DEC-07:01 | 0.95 |
Annual Sum or Average | 0.919416E+10 | 0.34 | |||
Minimum of Months | 0.639737E+09 | 0.31 | 554.28 | 0.65 | |
Maximum of Months | 0.100599E+10 | 0.40 | 1136.35 | 0.95 |
Report: FanReportMonthly
For: PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.100860E+10 | 0.41 | 1140.44 | 01-JAN-08:61 | 0.95 |
February | 0.834581E+09 | 0.38 | 1140.44 | 01-FEB-07:01 | 0.95 |
March | 0.875160E+09 | 0.37 | 1140.44 | 01-MAR-07:01 | 0.95 |
April | 0.716075E+09 | 0.33 | 1140.44 | 02-APR-07:01 | 0.95 |
May | 0.672370E+09 | 0.31 | 1140.44 | 01-MAY-06:01 | 0.95 |
June | 0.659073E+09 | 0.32 | 1140.44 | 25-JUN-07:03 | 0.93 |
July | 0.662713E+09 | 0.31 | 1140.44 | 04-JUL-07:03 | 0.93 |
August | 0.675160E+09 | 0.31 | 1140.44 | 09-AUG-06:03 | 0.93 |
September | 0.643003E+09 | 0.31 | 554.90 | 23-SEP-07:06 | 0.65 |
October | 0.717128E+09 | 0.33 | 1140.44 | 30-OCT-06:01 | 0.95 |
November | 0.791287E+09 | 0.36 | 1140.44 | 04-NOV-06:02 | 0.95 |
December | 0.978205E+09 | 0.40 | 1140.44 | 01-DEC-07:01 | 0.95 |
Annual Sum or Average | 0.923335E+10 | 0.34 | |||
Minimum of Months | 0.643003E+09 | 0.31 | 554.90 | 0.65 | |
Maximum of Months | 0.100860E+10 | 0.41 | 1140.44 | 0.95 |
Report: FanReportMonthly
For: PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.100949E+10 | 0.41 | 1128.70 | 01-JAN-08:61 | 0.95 |
February | 0.835038E+09 | 0.39 | 1128.70 | 01-FEB-07:01 | 0.95 |
March | 0.875326E+09 | 0.38 | 1128.70 | 01-MAR-07:01 | 0.95 |
April | 0.715133E+09 | 0.34 | 1128.70 | 02-APR-07:01 | 0.95 |
May | 0.667085E+09 | 0.31 | 1128.70 | 01-MAY-06:01 | 0.95 |
June | 0.651876E+09 | 0.32 | 1128.70 | 25-JUN-07:03 | 0.93 |
July | 0.655206E+09 | 0.31 | 1128.70 | 04-JUL-07:03 | 0.93 |
August | 0.668009E+09 | 0.31 | 1128.70 | 09-AUG-06:03 | 0.93 |
September | 0.637701E+09 | 0.31 | 553.60 | 23-SEP-07:04 | 0.65 |
October | 0.715550E+09 | 0.33 | 1128.70 | 30-OCT-06:01 | 0.95 |
November | 0.791290E+09 | 0.36 | 1128.70 | 04-NOV-06:02 | 0.95 |
December | 0.978903E+09 | 0.40 | 1128.70 | 01-DEC-07:01 | 0.95 |
Annual Sum or Average | 0.920060E+10 | 0.35 | |||
Minimum of Months | 0.637701E+09 | 0.31 | 553.60 | 0.65 | |
Maximum of Months | 0.100949E+10 | 0.41 | 1128.70 | 0.95 |
Report: FanReportMonthly
For: PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.166489E+10 | 0.40 | 1943.92 | 01-JAN-09:01 | 0.92 |
February | 0.136700E+10 | 0.35 | 1943.92 | 01-FEB-08:61 | 0.92 |
March | 0.142976E+10 | 0.34 | 1943.92 | 01-MAR-08:61 | 0.92 |
April | 0.115552E+10 | 0.30 | 1943.92 | 01-APR-07:01 | 0.92 |
May | 0.106500E+10 | 0.28 | 1943.92 | 01-MAY-07:01 | 0.92 |
June | 0.104025E+10 | 0.28 | 1943.92 | 29-JUN-07:03 | 0.90 |
July | 0.104391E+10 | 0.27 | 1943.92 | 04-JUL-08:62 | 0.90 |
August | 0.106408E+10 | 0.28 | 1678.27 | 09-AUG-07:03 | 0.84 |
September | 0.101850E+10 | 0.28 | 1277.24 | 23-SEP-07:01 | 0.74 |
October | 0.115660E+10 | 0.30 | 1943.92 | 05-OCT-07:01 | 0.91 |
November | 0.128968E+10 | 0.32 | 1943.92 | 01-NOV-07:01 | 0.92 |
December | 0.161262E+10 | 0.38 | 1943.92 | 01-DEC-08:61 | 0.92 |
Annual Sum or Average | 0.149078E+11 | 0.32 | |||
Minimum of Months | 0.101850E+10 | 0.27 | 1277.24 | 0.74 | |
Maximum of Months | 0.166489E+10 | 0.40 | 1943.92 | 0.92 |
Report: FanReportMonthly
For: PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.922638E+09 | 0.40 | 1082.43 | 01-JAN-09:01 | 0.95 |
February | 0.758735E+09 | 0.36 | 1082.43 | 01-FEB-08:61 | 0.95 |
March | 0.794565E+09 | 0.35 | 1082.43 | 01-MAR-08:61 | 0.95 |
April | 0.643427E+09 | 0.31 | 1082.43 | 01-APR-07:01 | 0.95 |
May | 0.593180E+09 | 0.29 | 1082.43 | 01-MAY-07:01 | 0.95 |
June | 0.577646E+09 | 0.29 | 1082.43 | 29-JUN-07:03 | 0.93 |
July | 0.579131E+09 | 0.28 | 1082.43 | 04-JUL-08:62 | 0.93 |
August | 0.591953E+09 | 0.29 | 774.88 | 09-AUG-07:03 | 0.80 |
September | 0.567121E+09 | 0.29 | 718.26 | 23-SEP-07:01 | 0.77 |
October | 0.643370E+09 | 0.31 | 1082.43 | 05-OCT-07:01 | 0.94 |
November | 0.716869E+09 | 0.33 | 1082.43 | 01-NOV-07:01 | 0.95 |
December | 0.894154E+09 | 0.39 | 1082.43 | 01-DEC-08:61 | 0.95 |
Annual Sum or Average | 0.828279E+10 | 0.33 | |||
Minimum of Months | 0.567121E+09 | 0.28 | 718.26 | 0.77 | |
Maximum of Months | 0.922638E+09 | 0.40 | 1082.43 | 0.95 |
Report: FanReportMonthly
For: PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.923336E+09 | 0.41 | 1081.57 | 01-JAN-09:01 | 0.95 |
February | 0.759748E+09 | 0.37 | 1081.57 | 01-FEB-08:61 | 0.95 |
March | 0.795822E+09 | 0.35 | 1081.57 | 01-MAR-08:61 | 0.95 |
April | 0.644913E+09 | 0.31 | 1081.57 | 01-APR-07:01 | 0.95 |
May | 0.593496E+09 | 0.29 | 1081.57 | 01-MAY-07:01 | 0.95 |
June | 0.576961E+09 | 0.29 | 1081.57 | 29-JUN-07:03 | 0.93 |
July | 0.578325E+09 | 0.28 | 1081.57 | 04-JUL-08:62 | 0.93 |
August | 0.591377E+09 | 0.29 | 710.73 | 09-AUG-07:03 | 0.76 |
September | 0.567219E+09 | 0.29 | 757.24 | 23-SEP-07:01 | 0.80 |
October | 0.644374E+09 | 0.31 | 1081.57 | 05-OCT-07:01 | 0.94 |
November | 0.717974E+09 | 0.34 | 1081.57 | 01-NOV-07:01 | 0.95 |
December | 0.894842E+09 | 0.39 | 1081.57 | 01-DEC-08:61 | 0.95 |
Annual Sum or Average | 0.828839E+10 | 0.33 | |||
Minimum of Months | 0.567219E+09 | 0.28 | 710.73 | 0.76 | |
Maximum of Months | 0.923336E+09 | 0.41 | 1081.57 | 0.95 |
Report: FanReportMonthly
For: PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.943006E+09 | 0.42 | 1095.81 | 01-JAN-09:01 | 0.95 |
February | 0.776440E+09 | 0.37 | 1095.81 | 01-FEB-08:61 | 0.95 |
March | 0.814478E+09 | 0.36 | 1095.81 | 01-MAR-08:61 | 0.95 |
April | 0.660662E+09 | 0.32 | 1095.81 | 01-APR-07:01 | 0.95 |
May | 0.604175E+09 | 0.29 | 1095.81 | 01-MAY-07:01 | 0.95 |
June | 0.583667E+09 | 0.29 | 1095.81 | 30-JUN-07:02 | 0.93 |
July | 0.584728E+09 | 0.28 | 1095.81 | 23-JUL-08:62 | 0.93 |
August | 0.598769E+09 | 0.29 | 528.10 | 08-AUG-15:00 | 0.64 |
September | 0.576224E+09 | 0.29 | 896.12 | 23-SEP-07:01 | 0.86 |
October | 0.657746E+09 | 0.31 | 1095.81 | 04-OCT-07:01 | 0.95 |
November | 0.733670E+09 | 0.34 | 1095.81 | 01-NOV-07:01 | 0.95 |
December | 0.913705E+09 | 0.40 | 1095.81 | 01-DEC-08:61 | 0.95 |
Annual Sum or Average | 0.844727E+10 | 0.33 | |||
Minimum of Months | 0.576224E+09 | 0.28 | 528.10 | 0.64 | |
Maximum of Months | 0.943006E+09 | 0.42 | 1095.81 | 0.95 |
Report: FanReportMonthly
For: PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.119215E+10 | 0.57 | 1308.55 | 01-JAN-08:61 | 0.95 |
February | 0.981940E+09 | 0.52 | 1308.55 | 01-FEB-08:61 | 0.95 |
March | 0.101769E+10 | 0.45 | 1308.55 | 01-MAR-08:61 | 0.95 |
April | 0.813659E+09 | 0.34 | 1308.55 | 01-APR-07:01 | 0.95 |
May | 0.730635E+09 | 0.29 | 1308.55 | 01-MAY-07:01 | 0.95 |
June | 0.692982E+09 | 0.29 | 1219.14 | 30-JUN-07:02 | 0.90 |
July | 0.695627E+09 | 0.28 | 1119.02 | 23-JUL-08:62 | 0.86 |
August | 0.714303E+09 | 0.29 | 677.67 | 19-AUG-07:03 | 0.67 |
September | 0.691990E+09 | 0.29 | 1308.55 | 23-SEP-07:01 | 0.95 |
October | 0.795506E+09 | 0.31 | 1308.55 | 03-OCT-07:02 | 0.95 |
November | 0.895993E+09 | 0.37 | 1308.55 | 01-NOV-07:01 | 0.95 |
December | 0.114773E+10 | 0.53 | 1308.55 | 01-DEC-08:61 | 0.95 |
Annual Sum or Average | 0.103702E+11 | 0.38 | |||
Minimum of Months | 0.691990E+09 | 0.28 | 677.67 | 0.67 | |
Maximum of Months | 0.119215E+10 | 0.57 | 1308.55 | 0.95 |
Report: ZoneTemperatureOscillationReportMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.204110E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.167084E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.174832E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.158298E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.230257E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.349684E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.480734E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.387223E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.183439E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.156496E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.160474E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.197523E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.285015E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.156496E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.480734E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.937722E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.767186E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.798945E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.698038E+09 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.127895E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.210458E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.289378E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.229310E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.984191E+09 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.706016E+09 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.721109E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.907988E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.150916E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.698038E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.289378E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_3:3
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.100599E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.832080E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.871836E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.722617E+09 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.106747E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.165906E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.218942E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.177853E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.807734E+09 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.722907E+09 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.786842E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.975810E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.134203E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.722617E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.218942E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_4:4
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.100860E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.834581E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.875160E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.726346E+09 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.105824E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.164644E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.218756E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.177141E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.802385E+09 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.726283E+09 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.791287E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.978205E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.134065E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.726283E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.218756E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_5:5
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.100949E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.835038E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.875326E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.724236E+09 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.102690E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.159244E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.212780E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.171790E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.782563E+09 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.721828E+09 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.791290E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.978903E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.131837E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.721828E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.212780E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_6:6
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.166489E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.136700E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.142976E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.117075E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.167071E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.266468E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.362135E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.288723E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.125451E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.116520E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.128968E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.161262E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.217984E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.116520E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.362135E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_7:7
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.922638E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.758735E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.794565E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.650778E+09 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.898057E+09 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.140429E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.189871E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.151784E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.682111E+09 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.646854E+09 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.716869E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.894154E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.117856E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.646854E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.189871E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_8:8
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.923336E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.759748E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.795822E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.651840E+09 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.887759E+09 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.138505E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.187937E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.150046E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.677878E+09 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.647300E+09 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.717974E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.894842E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.117214E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.647300E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.187937E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_9:9
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.943006E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.776440E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.814478E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.666398E+09 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.871038E+09 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.134489E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.183874E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.146429E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.676141E+09 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.659425E+09 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.733670E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.913705E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.117022E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.659425E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.183874E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_10:10
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.119215E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.981940E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.101769E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.816729E+09 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.963390E+09 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.141723E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.194445E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.154827E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.779777E+09 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.796163E+09 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.895993E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.114773E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.135015E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.779777E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.194445E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.204110E+10 | 0.00 | 0.285708E+11 | 0.167084E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.167084E+10 | 0.00 | 0.164392E+11 | 0.155531E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.174832E+10 | 0.00 | 0.125295E+11 | 0.154139E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.153123E+10 | 0.188334E+09 | 0.372932E+10 | 0.934616E+10 | 10497898.54 | 0.00 | 0.00 | 0.00 |
May | 0.151146E+10 | 0.293302E+10 | 88485493.28 | 0.344619E+10 | 0.204201E+09 | 0.00 | 0.00 | 0.00 |
June | 0.147068E+10 | 0.780273E+10 | 0.00 | 0.103686E+10 | 0.117763E+10 | 0.00 | 0.00 | 0.00 |
July | 0.151077E+10 | 0.130017E+11 | 0.00 | 0.250205E+09 | 0.182091E+10 | 0.00 | 0.00 | 0.00 |
August | 0.151297E+10 | 0.934146E+10 | 0.00 | 0.491939E+09 | 0.704482E+09 | 0.00 | 0.00 | 0.00 |
September | 0.146491E+10 | 0.141323E+10 | 0.00 | 0.312053E+10 | 28840151.78 | 0.00 | 0.00 | 0.00 |
October | 0.153465E+10 | 0.109292E+09 | 0.135022E+10 | 0.917883E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.160474E+10 | 0.00 | 0.788100E+10 | 0.131139E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.197523E+10 | 0.00 | 0.248172E+11 | 0.175284E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.195769E+11 | 0.347897E+11 | 0.954058E+11 | 0.105188E+12 | 0.394656E+10 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.146491E+10 | 0.00 | 0.00 | 0.250205E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.204110E+10 | 0.130017E+11 | 0.285708E+11 | 0.175284E+11 | 0.182091E+10 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.937722E+09 | 0.00 | 0.163006E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.767186E+09 | 0.00 | 0.107713E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.798945E+09 | 0.00 | 0.897002E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.664112E+09 | 0.124179E+09 | 0.292066E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.728237E+09 | 0.209385E+10 | 95403571.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.744733E+09 | 0.538937E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.761028E+09 | 0.859146E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.769783E+09 | 0.612170E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.724649E+09 | 0.100541E+10 | 5227981.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.683238E+09 | 84564521.67 | 0.187642E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.721048E+09 | 217265.59 | 0.643820E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.907988E+09 | 0.00 | 0.150254E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.920867E+10 | 0.234108E+11 | 0.624032E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.664112E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.937722E+09 | 0.859146E+10 | 0.163006E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_3:3
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.100599E+10 | 0.00 | 0.177164E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.832080E+09 | 0.00 | 0.120371E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.871836E+09 | 0.00 | 0.102291E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.711318E+09 | 41683719.02 | 0.372358E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.668980E+09 | 0.153188E+10 | 0.235431E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.656878E+09 | 0.404062E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.660566E+09 | 0.630617E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.672816E+09 | 0.454280E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.639737E+09 | 0.660138E+09 | 78536957.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.711311E+09 | 42418294.83 | 0.272361E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.786842E+09 | 0.00 | 0.756834E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.975810E+09 | 0.00 | 0.163510E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.919416E+10 | 0.171657E+11 | 0.706631E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.639737E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.100599E+10 | 0.630617E+10 | 0.177164E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_4:4
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.100860E+10 | 0.00 | 0.180030E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.834581E+09 | 0.00 | 0.122524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.875160E+09 | 0.00 | 0.104434E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.716075E+09 | 37572599.15 | 0.391172E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.672370E+09 | 0.147949E+10 | 0.290928E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.659073E+09 | 0.397836E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.662713E+09 | 0.628526E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.675160E+09 | 0.449886E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.643003E+09 | 0.626981E+09 | 0.129977E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.717128E+09 | 33290103.85 | 0.294660E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.791287E+09 | 0.00 | 0.780322E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.978205E+09 | 0.00 | 0.166110E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.923335E+10 | 0.169398E+11 | 0.723923E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.643003E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.100860E+10 | 0.628526E+10 | 0.180030E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_5:5
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.100949E+10 | 0.00 | 0.184530E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.835038E+09 | 0.00 | 0.126405E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.875326E+09 | 0.00 | 0.108515E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.715133E+09 | 33003827.08 | 0.422009E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.667085E+09 | 0.137274E+10 | 0.374170E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.651876E+09 | 0.378291E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.655206E+09 | 0.605670E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.668009E+09 | 0.429691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.637701E+09 | 0.569918E+09 | 0.198647E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.715550E+09 | 22662029.05 | 0.322882E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.791290E+09 | 0.00 | 0.817533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.978903E+09 | 0.00 | 0.170494E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.920060E+10 | 0.161348E+11 | 0.751914E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.637701E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.100949E+10 | 0.605670E+10 | 0.184530E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_6:6
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.166489E+10 | 0.00 | 0.349151E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.136700E+10 | 0.00 | 0.239012E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.142976E+10 | 0.00 | 0.206921E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115552E+10 | 55072724.17 | 0.829628E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.106500E+10 | 0.229697E+10 | 0.857673E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.104025E+10 | 0.652628E+10 | 2271872.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.104391E+10 | 0.105960E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.106408E+10 | 0.744463E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.101850E+10 | 0.928857E+09 | 0.604655E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.115660E+10 | 30964241.64 | 0.662823E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.128968E+10 | 0.00 | 0.158275E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.161262E+10 | 0.00 | 0.323684E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.149078E+11 | 0.278788E+11 | 0.144093E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.101850E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.166489E+10 | 0.105960E+11 | 0.349151E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_7:7
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.922638E+09 | 0.00 | 0.180559E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.758735E+09 | 0.00 | 0.123834E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.794565E+09 | 0.00 | 0.107438E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.643427E+09 | 26403008.03 | 0.434078E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.593180E+09 | 0.114913E+10 | 0.457314E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.577646E+09 | 0.330227E+10 | 1501644.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.579131E+09 | 0.539121E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.591953E+09 | 0.375828E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.567121E+09 | 0.451445E+09 | 0.316028E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.643370E+09 | 12486725.61 | 0.343343E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.716869E+09 | 0.00 | 0.821451E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.894154E+09 | 0.00 | 0.167478E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.828279E+10 | 0.140912E+11 | 0.746945E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.567121E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.922638E+09 | 0.539121E+10 | 0.180559E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_8:8
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.923336E+09 | 0.00 | 0.181166E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.759748E+09 | 0.00 | 0.124560E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.795822E+09 | 0.00 | 0.108375E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.644913E+09 | 24791614.17 | 0.444393E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.593496E+09 | 0.110598E+10 | 0.498532E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.576961E+09 | 0.322409E+10 | 2979721.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.578325E+09 | 0.530848E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.591377E+09 | 0.368503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.567219E+09 | 0.434376E+09 | 0.344728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.644374E+09 | 10461118.22 | 0.351160E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.717974E+09 | 0.00 | 0.829870E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.894842E+09 | 0.00 | 0.168101E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.828839E+10 | 0.137932E+11 | 0.753206E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.567219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.923336E+09 | 0.530848E+10 | 0.181166E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_9:9
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.943006E+09 | 0.00 | 0.185985E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.776440E+09 | 0.00 | 0.128880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.814478E+09 | 0.00 | 0.113474E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.660662E+09 | 20288339.38 | 0.486147E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.604175E+09 | 0.994339E+09 | 0.652940E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.583667E+09 | 0.302144E+10 | 12610149.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.584728E+09 | 0.509039E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.598769E+09 | 0.349198E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.576224E+09 | 0.391767E+09 | 0.428152E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.657746E+09 | 5972325.97 | 0.379703E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.733670E+09 | 0.00 | 0.869470E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.913705E+09 | 0.00 | 0.172791E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.844727E+10 | 0.130162E+11 | 0.785599E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.576224E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.943006E+09 | 0.509039E+10 | 0.185985E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_10:10
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.119215E+10 | 0.00 | 0.230005E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.981940E+09 | 0.00 | 0.163434E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.101769E+10 | 0.00 | 0.144921E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.813659E+09 | 10484448.38 | 0.660989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.730635E+09 | 0.845457E+09 | 0.118478E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.692982E+09 | 0.281142E+10 | 82575620.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.695627E+09 | 0.494568E+10 | 831056.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.714303E+09 | 0.329527E+10 | 7285719.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.691990E+09 | 0.341298E+09 | 0.672747E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.795506E+09 | 2306482.52 | 0.475678E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.895993E+09 | 0.00 | 0.106098E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.114773E+10 | 0.00 | 0.212359E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.103702E+11 | 0.122519E+11 | 0.989967E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.691990E+09 | 0.00 | 831056.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.119215E+10 | 0.494568E+10 | 0.230005E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.204110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.167084E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.174832E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.153123E+10 | 0.00 | 0.00 | 0.00 | 51748586.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.151146E+10 | 0.00 | 0.00 | 0.00 | 0.791109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.147068E+10 | 0.00 | 0.00 | 0.00 | 0.202616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.151077E+10 | 0.00 | 0.00 | 0.00 | 0.329658E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.151297E+10 | 0.00 | 0.00 | 0.00 | 0.235926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.146491E+10 | 0.00 | 0.00 | 0.00 | 0.369482E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.153465E+10 | 0.00 | 0.00 | 0.00 | 30308618.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.160474E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.197523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.195769E+11 | 0.00 | 0.00 | 0.00 | 0.892465E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.146491E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.204110E+10 | 0.00 | 0.00 | 0.00 | 0.329658E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.937722E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.767186E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.798945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.664112E+09 | 0.00 | 0.00 | 0.00 | 33925922.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.728237E+09 | 0.00 | 0.00 | 0.00 | 0.550712E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.744733E+09 | 0.00 | 0.00 | 0.00 | 0.135985E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.761028E+09 | 0.00 | 0.00 | 0.00 | 0.213275E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.769783E+09 | 0.00 | 0.00 | 0.00 | 0.152331E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.724649E+09 | 0.00 | 0.00 | 0.00 | 0.259542E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.683238E+09 | 0.00 | 0.00 | 0.00 | 22777334.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.721048E+09 | 0.00 | 0.00 | 0.00 | 61054.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.907988E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.920867E+10 | 0.00 | 0.00 | 0.00 | 0.588293E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.664112E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.937722E+09 | 0.00 | 0.00 | 0.00 | 0.213275E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_3:3
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.100599E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.832080E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.871836E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.711318E+09 | 0.00 | 0.00 | 0.00 | 11299259.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.668980E+09 | 0.00 | 0.00 | 0.00 | 0.398485E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.656878E+09 | 0.00 | 0.00 | 0.00 | 0.100218E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.660566E+09 | 0.00 | 0.00 | 0.00 | 0.152885E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.672816E+09 | 0.00 | 0.00 | 0.00 | 0.110571E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.639737E+09 | 0.00 | 0.00 | 0.00 | 0.167997E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.711311E+09 | 0.00 | 0.00 | 0.00 | 11595632.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.786842E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.975810E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.919416E+10 | 0.00 | 0.00 | 0.00 | 0.422612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.639737E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.100599E+10 | 0.00 | 0.00 | 0.00 | 0.152885E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_4:4
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.100860E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.834581E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.875160E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.716075E+09 | 0.00 | 0.00 | 0.00 | 10271063.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.672370E+09 | 0.00 | 0.00 | 0.00 | 0.385866E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.659073E+09 | 0.00 | 0.00 | 0.00 | 0.987370E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.662713E+09 | 0.00 | 0.00 | 0.00 | 0.152484E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.675160E+09 | 0.00 | 0.00 | 0.00 | 0.109625E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.643003E+09 | 0.00 | 0.00 | 0.00 | 0.159382E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.717128E+09 | 0.00 | 0.00 | 0.00 | 9154585.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.791287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.978205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.923335E+10 | 0.00 | 0.00 | 0.00 | 0.417313E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.643003E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.100860E+10 | 0.00 | 0.00 | 0.00 | 0.152484E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_5:5
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.100949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.835038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.875326E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.715133E+09 | 0.00 | 0.00 | 0.00 | 9103702.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.667085E+09 | 0.00 | 0.00 | 0.00 | 0.359810E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.651876E+09 | 0.00 | 0.00 | 0.00 | 0.940569E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.655206E+09 | 0.00 | 0.00 | 0.00 | 0.147259E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.668009E+09 | 0.00 | 0.00 | 0.00 | 0.104989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.637701E+09 | 0.00 | 0.00 | 0.00 | 0.144862E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.715550E+09 | 0.00 | 0.00 | 0.00 | 6277714.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.791290E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.978903E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.920060E+10 | 0.00 | 0.00 | 0.00 | 0.398311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.637701E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.100949E+10 | 0.00 | 0.00 | 0.00 | 0.147259E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_6:6
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.166489E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.136700E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.142976E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115552E+10 | 0.00 | 0.00 | 0.00 | 15228566.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.106500E+10 | 0.00 | 0.00 | 0.00 | 0.605710E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.104025E+10 | 0.00 | 0.00 | 0.00 | 0.162442E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.104391E+10 | 0.00 | 0.00 | 0.00 | 0.257743E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.106408E+10 | 0.00 | 0.00 | 0.00 | 0.182316E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.101850E+10 | 0.00 | 0.00 | 0.00 | 0.236010E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.115660E+10 | 0.00 | 0.00 | 0.00 | 8601220.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.128968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.161262E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.149078E+11 | 0.00 | 0.00 | 0.00 | 0.689056E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.101850E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.166489E+10 | 0.00 | 0.00 | 0.00 | 0.257743E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_7:7
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.922638E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.758735E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.794565E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.643427E+09 | 0.00 | 0.00 | 0.00 | 7351174.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.593180E+09 | 0.00 | 0.00 | 0.00 | 0.304876E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.577646E+09 | 0.00 | 0.00 | 0.00 | 0.826645E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.579131E+09 | 0.00 | 0.00 | 0.00 | 0.131958E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.591953E+09 | 0.00 | 0.00 | 0.00 | 0.925882E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.567121E+09 | 0.00 | 0.00 | 0.00 | 0.114989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.643370E+09 | 0.00 | 0.00 | 0.00 | 3483876.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.716869E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.894154E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.828279E+10 | 0.00 | 0.00 | 0.00 | 0.350281E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.567121E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.922638E+09 | 0.00 | 0.00 | 0.00 | 0.131958E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_8:8
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.923336E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.759748E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.795822E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.644913E+09 | 0.00 | 0.00 | 0.00 | 6926592.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.593496E+09 | 0.00 | 0.00 | 0.00 | 0.294263E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.576961E+09 | 0.00 | 0.00 | 0.00 | 0.808093E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.578325E+09 | 0.00 | 0.00 | 0.00 | 0.130105E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.591377E+09 | 0.00 | 0.00 | 0.00 | 0.909080E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.567219E+09 | 0.00 | 0.00 | 0.00 | 0.110659E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.644374E+09 | 0.00 | 0.00 | 0.00 | 2925219.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.717974E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.894842E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.828839E+10 | 0.00 | 0.00 | 0.00 | 0.343300E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.567219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.923336E+09 | 0.00 | 0.00 | 0.00 | 0.130105E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_9:9
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.943006E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.776440E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.814478E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.660662E+09 | 0.00 | 0.00 | 0.00 | 5736217.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.604175E+09 | 0.00 | 0.00 | 0.00 | 0.266863E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.583667E+09 | 0.00 | 0.00 | 0.00 | 0.761225E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.584728E+09 | 0.00 | 0.00 | 0.00 | 0.125401E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.598769E+09 | 0.00 | 0.00 | 0.00 | 0.865525E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.576224E+09 | 0.00 | 0.00 | 0.00 | 99917170.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.657746E+09 | 0.00 | 0.00 | 0.00 | 1679438.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.733670E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.913705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.844727E+10 | 0.00 | 0.00 | 0.00 | 0.325496E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.576224E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.943006E+09 | 0.00 | 0.00 | 0.00 | 0.125401E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_10:10
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.119215E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.981940E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.101769E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.813659E+09 | 0.00 | 0.00 | 0.00 | 3069770.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.730635E+09 | 0.00 | 0.00 | 0.00 | 0.232755E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.692982E+09 | 0.00 | 0.00 | 0.00 | 0.724249E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.695627E+09 | 0.00 | 0.00 | 0.00 | 0.124882E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.714303E+09 | 0.00 | 0.00 | 0.00 | 0.833972E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.691990E+09 | 0.00 | 0.00 | 0.00 | 87786795.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.795506E+09 | 0.00 | 0.00 | 0.00 | 656703.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.895993E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.114773E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.103702E+11 | 0.00 | 0.00 | 0.00 | 0.313131E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.691990E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.119215E+10 | 0.00 | 0.00 | 0.00 | 0.124882E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.427269E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142525E+11 | 0.00 | 0.00 | 0.52 |
February | 0.744669E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.758840E+10 | 0.00 | 0.00 | 0.53 |
March | 0.120620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.563493E+10 | 0.00 | 0.00 | 0.53 |
April | 0.232730E+10 | 3431185.97 | 0.00 | 750800.43 | 726675.86 | 0.166602E+10 | 0.592958E+09 | 0.00 | 0.54 |
May | 0.102559E+10 | 98867927.99 | 0.00 | 7643529.94 | 0.00 | 36261668.97 | 0.383013E+10 | 0.00 | 0.70 |
June | 0.178188E+09 | 0.951956E+09 | 0.00 | 10146205.40 | 184661.19 | 0.00 | 0.416076E+10 | 0.00 | 0.85 |
July | 21586428.85 | 0.166783E+10 | 0.00 | 11766663.78 | 135496.99 | 0.00 | 0.363546E+10 | 0.00 | 0.90 |
August | 68410331.51 | 0.837198E+09 | 0.00 | 15148680.21 | 0.00 | 0.00 | 0.514789E+10 | 0.00 | 0.96 |
September | 0.655298E+09 | 33395705.72 | 0.00 | 10765248.02 | 0.00 | 0.00 | 0.685177E+10 | 0.00 | 0.75 |
October | 0.287768E+10 | 0.00 | 0.00 | 2237052.35 | 0.00 | 0.818651E+09 | 0.184034E+10 | 0.00 | 0.56 |
November | 0.210535E+10 | 0.00 | 311400.95 | 0.00 | 9588.05 | 0.373439E+10 | 0.00 | 3256.16 | 0.53 |
December | 0.298634E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120904E+11 | 0.00 | 0.00 | 0.52 |
Annual Sum or Average | 0.119362E+11 | 0.359268E+10 | 311400.95 | 58458180.14 | 1056422.09 | 0.458215E+11 | 0.260593E+11 | 3256.16 | 0.66 |
Minimum of Months | 21586428.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.52 |
Maximum of Months | 0.287768E+10 | 0.166783E+10 | 311400.95 | 15148680.21 | 726675.86 | 0.142525E+11 | 0.685177E+10 | 3256.16 | 0.96 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.491906E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109010E+11 | 0.00 | 0.00 | 0.39 |
February | 0.116726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.721891E+10 | 0.00 | 0.00 | 0.39 |
March | 0.229702E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.556987E+10 | 0.00 | 0.00 | 0.39 |
April | 0.270245E+10 | 6176195.21 | 0.00 | 384953.44 | 0.00 | 0.169000E+10 | 0.297560E+09 | 0.00 | 0.41 |
May | 0.149006E+10 | 0.148098E+09 | 0.00 | 3759220.96 | 0.00 | 19919836.22 | 0.191879E+10 | 0.00 | 0.67 |
June | 0.373874E+09 | 0.978338E+09 | 0.00 | 5124148.33 | 0.00 | 0.00 | 0.206289E+10 | 0.00 | 0.83 |
July | 83468973.46 | 0.167285E+10 | 0.00 | 4862039.65 | 647582.96 | 0.00 | 0.162096E+10 | 0.00 | 0.84 |
August | 0.135896E+09 | 0.759476E+09 | 0.00 | 7194815.45 | 0.00 | 0.00 | 0.245261E+10 | 0.00 | 0.94 |
September | 0.135408E+10 | 29570043.64 | 0.00 | 5604972.16 | 0.00 | 0.00 | 0.341706E+10 | 0.00 | 0.75 |
October | 0.360016E+10 | 0.00 | 0.00 | 1056568.05 | 0.00 | 0.762605E+09 | 0.761339E+09 | 0.00 | 0.45 |
November | 0.243062E+10 | 0.00 | 0.00 | 3679.44 | 0.00 | 0.410008E+10 | 2575798.48 | 0.00 | 0.39 |
December | 0.698531E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.995844E+10 | 0.00 | 0.00 | 0.38 |
Annual Sum or Average | 0.168253E+11 | 0.359451E+10 | 0.00 | 27990397.47 | 647582.96 | 0.402208E+11 | 0.125338E+11 | 0.00 | 0.57 |
Minimum of Months | 83468973.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.360016E+10 | 0.167285E+10 | 0.00 | 7194815.45 | 647582.96 | 0.109010E+11 | 0.341706E+10 | 0.00 | 0.94 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 85996117.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119322E+11 | 0.00 | 0.00 | 0.41 |
February | 0.608491E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.833579E+10 | 0.00 | 0.00 | 0.41 |
March | 0.133266E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.705901E+10 | 0.00 | 0.00 | 0.42 |
April | 0.253521E+10 | 4111634.03 | 0.00 | 81563.23 | 1368000.66 | 0.218591E+10 | 87449058.98 | 0.00 | 0.42 |
May | 0.184710E+10 | 0.144345E+09 | 0.00 | 1379757.03 | 1572942.56 | 54921878.24 | 0.748765E+09 | 0.00 | 0.55 |
June | 0.589148E+09 | 0.799756E+09 | 0.00 | 2826828.32 | 36579181.23 | 0.00 | 0.115667E+10 | 0.00 | 0.69 |
July | 0.175823E+09 | 0.123512E+10 | 0.00 | 2999024.88 | 77363786.16 | 0.00 | 0.106863E+10 | 0.00 | 0.70 |
August | 0.329731E+09 | 0.646422E+09 | 0.00 | 3944082.93 | 17346386.11 | 0.00 | 0.161843E+10 | 0.00 | 0.77 |
September | 0.188793E+10 | 30490797.02 | 0.00 | 2631890.46 | 0.00 | 4288643.94 | 0.171748E+10 | 0.00 | 0.61 |
October | 0.332188E+10 | 0.00 | 0.00 | 376635.91 | 0.00 | 0.133264E+10 | 0.274455E+09 | 0.00 | 0.44 |
November | 0.198130E+10 | 0.00 | 47619.35 | 0.00 | 0.00 | 0.486859E+10 | 0.00 | 3696.88 | 0.41 |
December | 0.133981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110942E+11 | 0.00 | 0.00 | 0.41 |
Annual Sum or Average | 0.148293E+11 | 0.286025E+10 | 47619.35 | 14239782.76 | 0.134230E+09 | 0.468676E+11 | 0.667188E+10 | 3696.88 | 0.52 |
Minimum of Months | 85996117.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.332188E+10 | 0.123512E+10 | 47619.35 | 3944082.93 | 77363786.16 | 0.119322E+11 | 0.171748E+10 | 3696.88 | 0.77 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 72583540.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119457E+11 | 0.00 | 0.00 | 0.41 |
February | 0.511442E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.843280E+10 | 0.00 | 0.00 | 0.41 |
March | 0.121312E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.717849E+10 | 0.00 | 0.00 | 0.42 |
April | 0.241254E+10 | 3954971.58 | 0.00 | 55748.05 | 1445004.19 | 0.232200E+10 | 58385896.77 | 0.00 | 0.42 |
May | 0.184055E+10 | 0.142983E+09 | 0.00 | 1283542.46 | 1564864.65 | 68637152.80 | 0.698491E+09 | 0.00 | 0.55 |
June | 0.604466E+09 | 0.797569E+09 | 0.00 | 2682486.53 | 36539620.71 | 0.00 | 0.110862E+10 | 0.00 | 0.69 |
July | 0.183350E+09 | 0.123365E+10 | 0.00 | 2980739.57 | 77233825.30 | 0.00 | 0.106105E+10 | 0.00 | 0.70 |
August | 0.367859E+09 | 0.643297E+09 | 0.00 | 3901504.15 | 17255311.85 | 0.00 | 0.157897E+10 | 0.00 | 0.77 |
September | 0.192859E+10 | 30432659.85 | 0.00 | 2477729.49 | 0.00 | 5637851.24 | 0.162877E+10 | 0.00 | 0.60 |
October | 0.313908E+10 | 0.00 | 0.00 | 334368.27 | 0.00 | 0.151174E+10 | 0.254735E+09 | 0.00 | 0.44 |
November | 0.176883E+10 | 0.00 | 46466.90 | 0.00 | 0.00 | 0.507973E+10 | 0.00 | 4973.88 | 0.41 |
December | 0.104788E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111234E+11 | 0.00 | 0.00 | 0.41 |
Annual Sum or Average | 0.141472E+11 | 0.285189E+10 | 46466.90 | 13716118.53 | 0.134039E+09 | 0.476680E+11 | 0.638902E+10 | 4973.88 | 0.52 |
Minimum of Months | 72583540.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.313908E+10 | 0.123365E+10 | 46466.90 | 3901504.15 | 77233825.30 | 0.119457E+11 | 0.162877E+10 | 4973.88 | 0.77 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 32331924.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119859E+11 | 0.00 | 0.00 | 0.41 |
February | 0.328052E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.861632E+10 | 0.00 | 0.00 | 0.41 |
March | 0.939238E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.745244E+10 | 0.00 | 0.00 | 0.42 |
April | 0.210510E+10 | 3780403.47 | 0.00 | 33617.76 | 1494207.01 | 0.263176E+10 | 35986680.54 | 0.00 | 0.42 |
May | 0.183163E+10 | 0.139133E+09 | 0.00 | 1094484.22 | 1548215.33 | 96318331.35 | 0.604970E+09 | 0.00 | 0.53 |
June | 0.647659E+09 | 0.782621E+09 | 0.00 | 2359519.45 | 35947855.96 | 0.00 | 0.996975E+09 | 0.00 | 0.67 |
July | 0.208814E+09 | 0.120647E+10 | 0.00 | 2783320.16 | 76826776.54 | 0.00 | 0.101419E+10 | 0.00 | 0.69 |
August | 0.436860E+09 | 0.624416E+09 | 0.00 | 3605310.38 | 16969153.86 | 0.00 | 0.146603E+10 | 0.00 | 0.75 |
September | 0.199556E+10 | 29529460.30 | 0.00 | 2201874.27 | 0.00 | 10698326.44 | 0.145997E+10 | 0.00 | 0.59 |
October | 0.287369E+10 | 0.00 | 0.00 | 278733.28 | 0.00 | 0.177702E+10 | 0.226889E+09 | 0.00 | 0.44 |
November | 0.150905E+10 | 0.00 | 44829.81 | 0.00 | 0.00 | 0.533778E+10 | 0.00 | 6971.77 | 0.41 |
December | 67533663.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111607E+11 | 0.00 | 0.00 | 0.41 |
Annual Sum or Average | 0.129755E+11 | 0.278595E+10 | 44829.81 | 12356859.50 | 0.132786E+09 | 0.490689E+11 | 0.580500E+10 | 6971.77 | 0.51 |
Minimum of Months | 32331924.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.287369E+10 | 0.120647E+10 | 44829.81 | 3605310.38 | 76826776.54 | 0.119859E+11 | 0.146603E+10 | 6971.77 | 0.75 |
Report: MechanicalVentilationLoadsMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.221632E+11 | 0.00 | 0.00 | 0.38 |
February | 0.114226E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163292E+11 | 0.00 | 0.00 | 0.38 |
March | 0.834196E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146299E+11 | 0.00 | 0.00 | 0.39 |
April | 0.319418E+10 | 3928133.54 | 0.00 | 27880.41 | 3635846.86 | 0.556000E+10 | 34887388.29 | 0.00 | 0.38 |
May | 0.327028E+10 | 0.211263E+09 | 0.00 | 1686950.34 | 0.00 | 0.175042E+09 | 0.104233E+10 | 0.00 | 0.47 |
June | 0.120651E+10 | 0.143908E+10 | 0.00 | 3643512.79 | 17227222.82 | 0.00 | 0.171434E+10 | 0.00 | 0.57 |
July | 0.307860E+09 | 0.222036E+10 | 0.00 | 4549646.82 | 67036154.70 | 0.00 | 0.183778E+10 | 0.00 | 0.59 |
August | 0.715699E+09 | 0.106714E+10 | 0.00 | 5948907.72 | 4006396.89 | 0.00 | 0.257155E+10 | 0.00 | 0.65 |
September | 0.366683E+10 | 42113985.20 | 0.00 | 3423009.90 | 0.00 | 11987919.80 | 0.247803E+10 | 0.00 | 0.50 |
October | 0.468836E+10 | 0.00 | 0.00 | 361446.16 | 0.00 | 0.397638E+10 | 0.357609E+09 | 0.00 | 0.39 |
November | 0.144000E+10 | 0.00 | 485587.79 | 0.00 | 0.00 | 0.112739E+11 | 0.00 | 4373.59 | 0.38 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.207531E+11 | 0.00 | 0.00 | 0.37 |
Annual Sum or Average | 0.194381E+11 | 0.498388E+10 | 485587.79 | 19641354.15 | 91905621.28 | 0.948728E+11 | 0.100365E+11 | 4373.59 | 0.45 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.37 |
Maximum of Months | 0.468836E+10 | 0.222036E+10 | 485587.79 | 5948907.72 | 67036154.70 | 0.221632E+11 | 0.257155E+10 | 4373.59 | 0.65 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110697E+11 | 0.00 | 0.00 | 0.38 |
February | 43782180.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.816729E+10 | 0.00 | 0.00 | 0.38 |
March | 0.369834E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.735021E+10 | 0.00 | 0.00 | 0.39 |
April | 0.148637E+10 | 1963380.49 | 0.00 | 5827.32 | 1877461.73 | 0.288514E+10 | 7565922.19 | 0.00 | 0.38 |
May | 0.161272E+10 | 0.106189E+09 | 0.00 | 782257.84 | 0.00 | 0.135862E+09 | 0.486971E+09 | 0.00 | 0.47 |
June | 0.622924E+09 | 0.719584E+09 | 0.00 | 1771163.61 | 8660565.33 | 0.00 | 0.852855E+09 | 0.00 | 0.59 |
July | 0.154590E+09 | 0.110818E+10 | 0.00 | 2287883.33 | 33469049.54 | 0.00 | 0.968490E+09 | 0.00 | 0.62 |
August | 0.358288E+09 | 0.532500E+09 | 0.00 | 2995093.65 | 2197284.24 | 0.00 | 0.135404E+10 | 0.00 | 0.68 |
September | 0.181435E+10 | 21269210.91 | 0.00 | 1686366.73 | 0.00 | 27123089.12 | 0.125190E+10 | 0.00 | 0.51 |
October | 0.219362E+10 | 0.00 | 0.00 | 170798.51 | 0.00 | 0.213075E+10 | 0.175788E+09 | 0.00 | 0.40 |
November | 0.623483E+09 | 0.00 | 233088.11 | 0.00 | 0.00 | 0.572155E+10 | 0.00 | 2652.82 | 0.38 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103646E+11 | 0.00 | 0.00 | 0.37 |
Annual Sum or Average | 0.927997E+10 | 0.248968E+10 | 233088.11 | 9699390.99 | 46204360.83 | 0.478522E+11 | 0.509761E+10 | 2652.82 | 0.46 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.37 |
Maximum of Months | 0.219362E+10 | 0.110818E+10 | 233088.11 | 2995093.65 | 33469049.54 | 0.110697E+11 | 0.135404E+10 | 2652.82 | 0.68 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110697E+11 | 0.00 | 0.00 | 0.38 |
February | 37942875.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.817311E+10 | 0.00 | 0.00 | 0.38 |
March | 0.324569E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.739549E+10 | 0.00 | 0.00 | 0.39 |
April | 0.140359E+10 | 1908096.85 | 0.00 | 3654.73 | 1918987.92 | 0.296970E+10 | 1220996.82 | 0.00 | 0.38 |
May | 0.161007E+10 | 0.105047E+09 | 0.00 | 721023.13 | 0.00 | 0.152401E+09 | 0.449344E+09 | 0.00 | 0.47 |
June | 0.634212E+09 | 0.714780E+09 | 0.00 | 1663098.19 | 8723727.19 | 0.00 | 0.816514E+09 | 0.00 | 0.58 |
July | 0.156592E+09 | 0.110069E+10 | 0.00 | 2215671.57 | 33457591.22 | 0.00 | 0.957936E+09 | 0.00 | 0.61 |
August | 0.367730E+09 | 0.527857E+09 | 0.00 | 2899518.04 | 2339082.85 | 0.00 | 0.133112E+10 | 0.00 | 0.67 |
September | 0.181410E+10 | 21138166.02 | 0.00 | 1600460.14 | 0.00 | 35116350.46 | 0.120931E+10 | 0.00 | 0.50 |
October | 0.213483E+10 | 0.00 | 0.00 | 157738.28 | 0.00 | 0.219026E+10 | 0.168414E+09 | 0.00 | 0.39 |
November | 0.592824E+09 | 0.00 | 233084.34 | 0.00 | 0.00 | 0.575200E+10 | 0.00 | 2831.50 | 0.38 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103646E+11 | 0.00 | 0.00 | 0.37 |
Annual Sum or Average | 0.907646E+10 | 0.247142E+10 | 233084.34 | 9261164.09 | 46439389.19 | 0.481024E+11 | 0.493386E+10 | 2831.50 | 0.46 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.37 |
Maximum of Months | 0.213483E+10 | 0.110069E+10 | 233084.34 | 2899518.04 | 33457591.22 | 0.110697E+11 | 0.133112E+10 | 2831.50 | 0.67 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110697E+11 | 0.00 | 0.00 | 0.38 |
February | 2788168.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.820820E+10 | 0.00 | 0.00 | 0.38 |
March | 0.183271E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.753674E+10 | 0.00 | 0.00 | 0.39 |
April | 0.111450E+10 | 1703440.23 | 848380.59 | 1368.19 | 1143376.97 | 0.324651E+10 | 619012.63 | 1087.81 | 0.38 |
May | 0.150030E+10 | 0.100712E+09 | 0.00 | 561010.27 | 708.80 | 0.276054E+09 | 0.377421E+09 | 0.00 | 0.46 |
June | 0.668202E+09 | 0.695574E+09 | 0.00 | 1416736.40 | 10150789.55 | 751569.98 | 0.724918E+09 | 0.00 | 0.57 |
July | 0.164267E+09 | 0.107423E+10 | 0.00 | 2030728.77 | 33310834.43 | 0.00 | 0.934089E+09 | 0.00 | 0.61 |
August | 0.411760E+09 | 0.513009E+09 | 0.00 | 2651344.54 | 2655485.24 | 0.00 | 0.126058E+10 | 0.00 | 0.66 |
September | 0.180831E+10 | 20541194.41 | 0.00 | 1385080.44 | 0.00 | 75479341.25 | 0.109319E+10 | 0.00 | 0.49 |
October | 0.183043E+10 | 0.00 | 0.00 | 127517.32 | 0.00 | 0.250022E+10 | 0.147526E+09 | 0.00 | 0.39 |
November | 0.381557E+09 | 0.00 | 233281.88 | 0.00 | 0.00 | 0.596227E+10 | 0.00 | 3595.25 | 0.38 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103645E+11 | 0.00 | 0.00 | 0.37 |
Annual Sum or Average | 0.806538E+10 | 0.240577E+10 | 1081662.47 | 8173785.92 | 47261195.00 | 0.492405E+11 | 0.453833E+10 | 4683.06 | 0.45 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.37 |
Maximum of Months | 0.183043E+10 | 0.107423E+10 | 848380.59 | 2651344.54 | 33310834.43 | 0.110697E+11 | 0.126058E+10 | 3595.25 | 0.66 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110521E+11 | 0.00 | 0.00 | 0.38 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.819052E+10 | 0.00 | 0.00 | 0.38 |
March | 2055874.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.769581E+10 | 0.00 | 0.00 | 0.39 |
April | 0.510154E+09 | 1302443.13 | 689502.16 | 0.00 | 1827501.79 | 0.381016E+10 | 0.00 | 6801.58 | 0.38 |
May | 0.118237E+10 | 96700260.90 | 0.00 | 312825.21 | 662084.93 | 0.644905E+09 | 0.224757E+09 | 0.00 | 0.45 |
June | 0.688036E+09 | 0.673439E+09 | 74843.21 | 1092500.26 | 12261196.59 | 10152016.27 | 0.644657E+09 | 85.21 | 0.59 |
July | 0.174891E+09 | 0.105359E+10 | 0.00 | 1787514.92 | 33715470.13 | 0.00 | 0.967674E+09 | 0.00 | 0.64 |
August | 0.496361E+09 | 0.506805E+09 | 0.00 | 2270577.36 | 2624839.39 | 646265.57 | 0.120946E+10 | 0.00 | 0.71 |
September | 0.158722E+10 | 21770582.32 | 0.00 | 1122123.58 | 0.00 | 0.316852E+09 | 0.981636E+09 | 0.00 | 0.49 |
October | 0.113272E+10 | 0.00 | 0.00 | 95095.71 | 0.00 | 0.317890E+10 | 0.128723E+09 | 0.00 | 0.39 |
November | 64620305.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.626414E+10 | 0.00 | 0.00 | 0.38 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103462E+11 | 0.00 | 0.00 | 0.37 |
Annual Sum or Average | 0.583844E+10 | 0.235361E+10 | 764345.37 | 6680637.03 | 51091092.83 | 0.515103E+11 | 0.415691E+10 | 6886.79 | 0.46 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.37 |
Maximum of Months | 0.158722E+10 | 0.105359E+10 | 689502.16 | 2270577.36 | 33715470.13 | 0.110521E+11 | 0.120946E+10 | 6801.58 | 0.71 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:37:19
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.112051E+12 | 0.685304E+11 | 0.00 | 0.146637E+12 | 0.529322E+11 |
February | 0.198986E+12 | 0.503637E+11 | 0.00 | 0.110466E+12 | 0.355281E+11 |
March | 0.305540E+12 | 0.442826E+11 | 0.00 | 0.104399E+12 | 0.302841E+11 |
April | 0.410657E+12 | 0.266104E+11 | 0.00 | 0.611917E+11 | 0.124894E+11 |
May | 0.496245E+12 | 0.113876E+11 | 0.00 | 0.314326E+11 | 0.212704E+11 |
June | 0.511274E+12 | 0.252709E+10 | 0.00 | 0.116325E+11 | 0.551742E+11 |
July | 0.524263E+12 | -0.254008E+10 | 0.00 | 0.100398E+09 | 0.896299E+11 |
August | 0.432110E+12 | 0.272409E+10 | 0.00 | 0.167962E+11 | 0.632526E+11 |
September | 0.308963E+12 | 0.142607E+11 | 0.00 | 0.440499E+11 | 0.930970E+10 |
October | 0.164800E+12 | 0.252466E+11 | 0.00 | 0.632049E+11 | 0.901507E+10 |
November | 0.663763E+11 | 0.390521E+11 | 0.00 | 0.870288E+11 | 0.223781E+11 |
December | 0.659347E+11 | 0.665028E+11 | 0.00 | 0.138267E+12 | 0.485738E+11 |
Annual Sum or Average | 0.359720E+13 | 0.348948E+12 | 0.00 | 0.815206E+12 | 0.449838E+12 |
Minimum of Months | 0.659347E+11 | -0.254008E+10 | 0.00 | 0.100398E+09 | 0.901507E+10 |