Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:37
Tabular Output Report in Format: HTML
Building: RetailStripmall
Environment: RUNPERIOD 1 ** Rochester International Arpt MN USA TMY3 WMO#=726440
Simulation Timestamp: 2023-10-16 08:37:25
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:25
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1770.38 | 846.94 | 846.94 |
Net Site Energy | 1770.38 | 846.94 | 846.94 |
Total Source Energy | 3590.06 | 1717.47 | 1717.47 |
Net Source Energy | 3590.06 | 1717.47 | 1717.47 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 2090.32 |
Net Conditioned Building Area | 2090.32 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 968.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 74.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 366.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 60.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 128.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 106.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 66.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 802.19 | 968.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 968.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 74.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 366.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 60.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 128.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 106.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 66.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 968.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 74.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 366.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 60.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 128.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 106.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 66.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 204.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 118.21 | 463.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Other | 61.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 383.77 | 463.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 204.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 118.21 | 463.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Other | 61.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 383.77 | 463.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 802.193 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 802.193 | 100.00 |
Total On-Site and Utility Electric Sources | 802.193 | 100.00 |
Total Electricity End Uses | 802.193 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 87.30 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 87.30 | 100.00 |
Total Water End Uses | 87.30 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 7.83 |
Time Setpoint Not Met During Occupied Cooling | 0.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 3092.00 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTRIPMALL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6A
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_ROCHESTER
| Environment |ZoneCoolingSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ZoneHeatingSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ZoneElectricSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |SpaceGainsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |PeakSpaceGainsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |SpaceGainComponentsAtCoolingPeakMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ComfortReportSimple55Monthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |OccupantComfortDataSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |DXReportMonthly
| PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL | PSZ-AC_3:3 COOLING COIL | PSZ-AC_4:4 COOLING COIL | PSZ-AC_5:5 COOLING COIL | PSZ-AC_6:6 COOLING COIL | PSZ-AC_7:7 COOLING COIL | PSZ-AC_8:8 COOLING COIL | PSZ-AC_9:9 COOLING COIL | PSZ-AC_10:10 COOLING COIL |WindowReportMonthly
| LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR |WindowEnergyReportMonthly
| LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR |WindowZoneSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |WindowEnergyZoneSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| GAS TANK1 | GAS TANK2 | GAS TANK3 | GAS TANK4 | GAS TANK5 | GAS TANK6 | GAS TANK7 |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC_1:1 HEATING COIL | PSZ-AC_2:2 HEATING COIL | PSZ-AC_3:3 HEATING COIL | PSZ-AC_4:4 HEATING COIL | PSZ-AC_5:5 HEATING COIL | PSZ-AC_6:6 HEATING COIL | PSZ-AC_7:7 HEATING COIL | PSZ-AC_8:8 HEATING COIL | PSZ-AC_9:9 HEATING COIL | PSZ-AC_10:10 HEATING COIL | PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL | PSZ-AC_3:3 COOLING COIL | PSZ-AC_4:4 COOLING COIL | PSZ-AC_5:5 COOLING COIL | PSZ-AC_6:6 COOLING COIL | PSZ-AC_7:7 COOLING COIL | PSZ-AC_8:8 COOLING COIL | PSZ-AC_9:9 COOLING COIL | PSZ-AC_10:10 COOLING COIL |FanReportMonthly
| PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN |ZoneTemperatureOscillationReportMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |MechanicalVentilationLoadsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:25
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:37 |
RunPeriod | RUNPERIOD 1 |
Weather File | Rochester International Arpt MN USA TMY3 WMO#=726440 |
Latitude [deg] | 43.90 |
Longitude [deg] | -92.5 |
Elevation [m] | 398.00 |
Time Zone | -6.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Above Ground Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Window Opening Area [m2] | 124.40 | 0.00 | 0.00 | 124.40 | 0.00 |
Gross Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Above Ground Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Above Ground Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Window Opening Area [m2] | 124.40 | 0.00 | 0.00 | 124.40 | 0.00 |
Gross Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Above Ground Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Total | |
Gross Roof Area [m2] | 2090.32 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
LGSTORE1 | 348.39 | Yes | Yes | 1805.20 | 1.00 | 276.30 | 0.00 | 20.77 | 20.77 | 15.3022 | 6.19 | 4.3000 |
SMSTORE1 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.38 | 10.38 | 18.2890 | 6.19 | 4.3000 |
SMSTORE2 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 16.6533 | 6.19 | 4.3000 |
SMSTORE3 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 16.6533 | 6.19 | 4.3000 |
SMSTORE4 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 16.6533 | 6.19 | 4.3000 |
LGSTORE2 | 348.39 | Yes | Yes | 1805.20 | 1.00 | 157.89 | 0.00 | 20.72 | 20.72 | 9.5842 | 6.19 | 4.3000 |
SMSTORE5 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 9.6995 | 6.19 | 4.3000 |
SMSTORE6 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 9.6995 | 6.19 | 4.3000 |
SMSTORE7 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 9.6995 | 6.19 | 4.3000 |
SMSTORE8 | 174.19 | Yes | Yes | 902.60 | 1.00 | 197.36 | 0.00 | 10.36 | 10.36 | 9.6995 | 6.19 | 4.3000 |
Total | 2090.32 | 10831.20 | 1184.15 | 0.00 | 124.40 | 124.40 | 13.0683 | 6.19 | 4.3000 | |||
Conditioned Total | 2090.32 | 10831.20 | 1184.15 | 0.00 | 124.40 | 124.40 | 13.0683 | 6.19 | 4.3000 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
LGSTORE1 | 348.39 | Yes | Yes | 1.00 | LGSTORE1 | GENERAL | LGSTORE1 | 15.3022 | 6.19 | 4.3000 | |
SMSTORE1 | 174.19 | Yes | Yes | 1.00 | SMSTORE1 | GENERAL | SMSTORE1 | 18.2890 | 6.19 | 4.3000 | |
SMSTORE2 | 174.19 | Yes | Yes | 1.00 | SMSTORE2 | GENERAL | SMSTORE2 | 16.6533 | 6.19 | 4.3000 | |
SMSTORE3 | 174.19 | Yes | Yes | 1.00 | SMSTORE3 | GENERAL | SMSTORE3 | 16.6533 | 6.19 | 4.3000 | |
SMSTORE4 | 174.19 | Yes | Yes | 1.00 | SMSTORE4 | GENERAL | SMSTORE4 | 16.6533 | 6.19 | 4.3000 | |
LGSTORE2 | 348.39 | Yes | Yes | 1.00 | LGSTORE2 | GENERAL | LGSTORE2 | 9.5842 | 6.19 | 4.3000 | |
SMSTORE5 | 174.19 | Yes | Yes | 1.00 | SMSTORE5 | GENERAL | SMSTORE5 | 9.6995 | 6.19 | 4.3000 | |
SMSTORE6 | 174.19 | Yes | Yes | 1.00 | SMSTORE6 | GENERAL | SMSTORE6 | 9.6995 | 6.19 | 4.3000 | |
SMSTORE7 | 174.19 | Yes | Yes | 1.00 | SMSTORE7 | GENERAL | SMSTORE7 | 9.6995 | 6.19 | 4.3000 | |
SMSTORE8 | 174.19 | Yes | Yes | 1.00 | SMSTORE8 | GENERAL | SMSTORE8 | 9.6995 | 6.19 | 4.3000 | |
Total | 2090.32 | 13.0683 | 3.10 | 4.3000 | |||||||
Conditioned Total | 2090.32 | 13.0683 | 3.10 | 4.3000 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 2090.32 | 2090.32 | 0.00 | 0.00 | 13.0683 | 6.19 | 4.3000 |
Total | 2090.32 | 2090.32 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:25
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 04-AUG-15:09 | 02-FEB-12:09 | - | - | - | - | - | - | - | - | - | - | 06-JAN-13:09 |
Heating | 0.00 | 353922.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 49149.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 23459.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 8059.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 8121.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 8204.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 96994.64 | 353922.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 353922.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 49149.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 23459.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 8059.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 8121.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 8204.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:25
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 1049.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 237.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1161.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 190.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 405.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 336.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 209.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2540.55 | 1049.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 502.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 113.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 555.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 91.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 194.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 160.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 100.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1215.39 | 502.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 502.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 113.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 555.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 91.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 194.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 160.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 100.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1215.39 | 502.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:25
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
LGSTORE1 DIRECT AIR | 1.94 |
SMSTORE1 DIRECT AIR | 1.03 |
SMSTORE2 DIRECT AIR | 1.03 |
SMSTORE3 DIRECT AIR | 1.06 |
SMSTORE4 DIRECT AIR | 1.02 |
LGSTORE2 DIRECT AIR | 1.84 |
SMSTORE5 DIRECT AIR | 0.943946 |
SMSTORE6 DIRECT AIR | 0.936958 |
SMSTORE7 DIRECT AIR | 0.927044 |
SMSTORE8 DIRECT AIR | 1.15 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC_1:1 | 1.94 | 1.94 | 1.94 | 1.94 | 1.94 | 1.94 | 1.00 | 1.00 | 1.94 |
PSZ-AC_2:2 | 1.03 | 1.03 | 1.03 | 1.03 | 1.05 | 1.05 | 1.00 | 0.977225 | 1.05 |
PSZ-AC_3:3 | 1.03 | 1.03 | 1.03 | 1.03 | 1.06 | 1.06 | 1.00 | 0.974886 | 1.06 |
PSZ-AC_4:4 | 1.06 | 1.06 | 1.06 | 1.06 | 1.06 | 1.06 | 1.00 | 1.00 | 1.06 |
PSZ-AC_5:5 | 1.02 | 1.02 | 1.02 | 1.02 | 1.05 | 1.05 | 1.00 | 0.972747 | 1.05 |
PSZ-AC_6:6 | 1.84 | 1.84 | 1.84 | 1.84 | 1.84 | 1.84 | 1.00 | 1.00 | 1.84 |
PSZ-AC_7:7 | 0.943946 | 0.943946 | 0.943946 | 0.943946 | 0.951989 | 0.951989 | 1.00 | 0.991552 | 0.951989 |
PSZ-AC_8:8 | 0.936958 | 0.936958 | 0.936958 | 0.936958 | 0.945258 | 0.945258 | 1.00 | 0.991219 | 0.945258 |
PSZ-AC_9:9 | 0.927044 | 0.927044 | 0.927044 | 0.927044 | 0.938741 | 0.938741 | 1.00 | 0.987539 | 0.938741 |
PSZ-AC_10:10 | 1.15 | 1.15 | 1.15 | 1.15 | 1.15 | 1.15 | 1.00 | 1.00 | 1.15 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC_1:1_OA_CONTROLLER | 1.94 | 0.411479 |
PSZ-AC_2:2_OA_CONTROLLER | 1.05 | 0.205739 |
PSZ-AC_3:3_OA_CONTROLLER | 1.06 | 0.205739 |
PSZ-AC_4:4_OA_CONTROLLER | 1.06 | 0.205739 |
PSZ-AC_5:5_OA_CONTROLLER | 1.05 | 0.205739 |
PSZ-AC_6:6_OA_CONTROLLER | 1.84 | 0.411479 |
PSZ-AC_7:7_OA_CONTROLLER | 0.951989 | 0.205739 |
PSZ-AC_8:8_OA_CONTROLLER | 0.945258 | 0.205739 |
PSZ-AC_9:9_OA_CONTROLLER | 0.938741 | 0.205739 |
PSZ-AC_10:10_OA_CONTROLLER | 1.15 | 0.205739 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | 1.94 | 2074.32 |
PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | 1.05 | 1163.80 |
PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | 1.06 | 1170.80 |
PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | 1.06 | 1174.93 |
PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | 1.05 | 1163.33 |
PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | 1.84 | 1973.81 |
PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | 0.951989 | 1054.00 |
PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | 0.945258 | 1046.55 |
PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | 0.938741 | 1039.34 |
PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | 1.15 | 1268.78 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC_1:1_UNITARY_PACKAGE_DX | 1.94 | 1.94 | 1.94 | 1.28 | 44494.47 | 64741.21 | 40.00 | 1.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_DX | 1.05 | 1.05 | 1.05 | 0.693766 | 23588.56 | 33633.97 | 40.00 | 1.00 |
PSZ-AC_3:3_UNITARY_PACKAGE_DX | 1.06 | 1.06 | 1.06 | 0.697935 | 23695.28 | 33714.65 | 40.00 | 1.00 |
PSZ-AC_4:4_UNITARY_PACKAGE_DX | 1.06 | 1.06 | 1.06 | 0.700398 | 23757.00 | 34375.17 | 40.00 | 1.00 |
PSZ-AC_5:5_UNITARY_PACKAGE_DX | 1.05 | 1.05 | 1.05 | 0.693487 | 23586.13 | 33522.34 | 40.00 | 1.00 |
PSZ-AC_6:6_UNITARY_PACKAGE_DX | 1.84 | 1.84 | 1.84 | 1.22 | 42688.27 | 62691.16 | 40.00 | 1.00 |
PSZ-AC_7:7_UNITARY_PACKAGE_DX | 0.951989 | 0.951989 | 0.951989 | 0.628313 | 21966.03 | 31817.90 | 40.00 | 1.00 |
PSZ-AC_8:8_UNITARY_PACKAGE_DX | 0.945258 | 0.945258 | 0.945258 | 0.623870 | 21854.31 | 31665.50 | 40.00 | 1.00 |
PSZ-AC_9:9_UNITARY_PACKAGE_DX | 0.938741 | 0.938741 | 0.938741 | 0.619569 | 21746.54 | 31449.28 | 40.00 | 1.00 |
PSZ-AC_10:10_UNITARY_PACKAGE_DX | 1.15 | 1.15 | 1.15 | 0.756344 | 26235.97 | 36225.34 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-AC_1:1 COOLING COIL | 1.94 | 0.969267 | 1.29 | 44494.47 | 22247.24 | 0.726150 | 0.726150 |
PSZ-AC_2:2 COOLING COIL | 1.05 | 0.525580 | 0.700773 | 23588.56 | 11794.28 | 0.734210 | 0.734210 |
PSZ-AC_3:3 COOLING COIL | 1.06 | 0.528739 | 0.704987 | 23695.28 | 11847.64 | 0.734610 | 0.734610 |
PSZ-AC_4:4 COOLING COIL | 1.06 | 0.530604 | 0.707473 | 23757.00 | 11878.50 | 0.734860 | 0.734860 |
PSZ-AC_5:5 COOLING COIL | 1.05 | 0.525369 | 0.700493 | 23586.13 | 11793.07 | 0.734130 | 0.734130 |
PSZ-AC_6:6 COOLING COIL | 1.84 | 0.922299 | 1.23 | 42688.27 | 21344.13 | 0.723980 | 0.723980 |
PSZ-AC_7:7 COOLING COIL | 0.951990 | 0.475994 | 0.634660 | 21966.03 | 10983.01 | 0.724760 | 0.724760 |
PSZ-AC_8:8 COOLING COIL | 0.945260 | 0.472629 | 0.630173 | 21854.31 | 10927.16 | 0.724240 | 0.724240 |
PSZ-AC_9:9 COOLING COIL | 0.938740 | 0.469370 | 0.625827 | 21746.54 | 10873.27 | 0.722720 | 0.722720 |
PSZ-AC_10:10 COOLING COIL | 1.15 | 0.572988 | 0.763987 | 26235.97 | 13117.99 | 0.726830 | 0.726830 |
Design Size Nominal Capacity [W] | |
PSZ-AC_1:1 HEATING COIL | 64741.21 |
PSZ-AC_2:2 HEATING COIL | 33633.97 |
PSZ-AC_3:3 HEATING COIL | 33714.65 |
PSZ-AC_4:4 HEATING COIL | 34375.17 |
PSZ-AC_5:5 HEATING COIL | 33522.34 |
PSZ-AC_6:6 HEATING COIL | 62691.16 |
PSZ-AC_7:7 HEATING COIL | 31817.90 |
PSZ-AC_8:8 HEATING COIL | 31665.50 |
PSZ-AC_9:9 HEATING COIL | 31449.28 |
PSZ-AC_10:10 HEATING COIL | 36225.34 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:25
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
LGSTORE1_WALL_3 | LGSTORE1_WALL_3_DOOR_1 | LGSTORE1_WALL_3_DOOR_2 | |
LGSTORE1_WALL_1 | LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | |
SMSTORE1_WALL_1 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | |
SMSTORE1_WALL_3 | SMSTORE1_WALL_3_DOOR | |
SMSTORE2_WALL_1 | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | |
SMSTORE2_WALL_3 | SMSTORE2_WALL_3_DOOR | |
SMSTORE3_WALL_1 | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | |
SMSTORE3_WALL_3 | SMSTORE3_WALL_3_DOOR | |
SMSTORE4_WALL_1 | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | |
SMSTORE4_WALL_3 | SMSTORE4_WALL_3_DOOR | |
LGSTORE2_WALL_3 | LGSTORE2_WALL_3_DOOR_1 | LGSTORE2_WALL_3_DOOR_2 | |
LGSTORE2_WALL_1 | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | |
SMSTORE5_WALL_1 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | |
SMSTORE5_WALL_3 | SMSTORE5_WALL_3_DOOR | |
SMSTORE6_WALL_1 | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | |
SMSTORE6_WALL_3 | SMSTORE6_WALL_3_DOOR | |
SMSTORE7_WALL_1 | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | |
SMSTORE7_WALL_3 | SMSTORE7_WALL_3_DOOR | |
SMSTORE8_WALL_1 | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR | |
SMSTORE8_WALL_3 | SMSTORE8_WALL_3_DOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:25
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:25
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 7.40 | -0.00 | -7.60 | -12.60 | -7.70 | 0.30 | 7.00 | 14.20 | 19.20 | 20.90 | 20.00 | 15.40 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Rochester International Arpt MN USA TMY3 WMO#=726440 | 43.90 | -92.50 | -6.00 | 398.00 | 96634 | 1.1486 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 6.38 | 33.50 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RetailStripmall | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 10 | 118 | 48 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | LGSTORE1 | 0.0 | 0.00 | 0.00 | 0.00 | 7.62 | 11.43 | 2.59 | 1 | 1 | 1 | 0.00 | 15.24 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 1805.20 | TARP | TARP | 348.39 | 276.30 | 247.74 | 20.77 | 6 | 8 | 0 | Yes |
2 | SMSTORE1 | 0.0 | 0.00 | 0.00 | 0.00 | 19.05 | 11.43 | 2.59 | 1 | 1 | 1 | 15.24 | 22.86 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.66 | 10.38 | 6 | 4 | 0 | Yes |
3 | SMSTORE2 | 0.0 | 0.00 | 0.00 | 0.00 | 26.67 | 11.43 | 2.59 | 1 | 1 | 1 | 22.86 | 30.48 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
4 | SMSTORE3 | 0.0 | 0.00 | 0.00 | 0.00 | 34.29 | 11.43 | 2.59 | 1 | 1 | 1 | 30.48 | 38.10 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
5 | SMSTORE4 | 0.0 | 0.00 | 0.00 | 0.00 | 41.91 | 11.43 | 2.59 | 1 | 1 | 1 | 38.10 | 45.72 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
6 | LGSTORE2 | 0.0 | 0.00 | 0.00 | 0.00 | 53.34 | 11.43 | 2.59 | 1 | 1 | 1 | 45.72 | 60.96 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 1805.20 | TARP | TARP | 348.39 | 157.89 | 129.41 | 20.72 | 6 | 8 | 0 | Yes |
7 | SMSTORE5 | 0.0 | 0.00 | 0.00 | 0.00 | 64.77 | 11.43 | 2.59 | 1 | 1 | 1 | 60.96 | 68.58 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
8 | SMSTORE6 | 0.0 | 0.00 | 0.00 | 0.00 | 72.39 | 11.43 | 2.59 | 1 | 1 | 1 | 68.58 | 76.20 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
9 | SMSTORE7 | 0.0 | 0.00 | 0.00 | 0.00 | 80.01 | 11.43 | 2.59 | 1 | 1 | 1 | 76.20 | 83.82 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
10 | SMSTORE8 | 0.0 | 0.00 | 0.00 | 0.00 | 87.63 | 11.43 | 2.59 | 1 | 1 | 1 | 83.82 | 91.44 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 197.36 | 183.12 | 10.36 | 6 | 4 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | LGSTORE1 | 348.39 | 56.3 | 6.193 | 0.161 | 15.302 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 19.602 | No |
2 | SMSTORE1 | 174.19 | 28.1 | 6.194 | 0.161 | 18.289 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 22.589 | No |
3 | SMSTORE2 | 174.19 | 28.1 | 6.194 | 0.161 | 16.653 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 20.953 | No |
4 | SMSTORE3 | 174.19 | 28.1 | 6.194 | 0.161 | 16.653 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 20.953 | No |
5 | SMSTORE4 | 174.19 | 28.1 | 6.194 | 0.161 | 16.653 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 20.953 | No |
6 | LGSTORE2 | 348.39 | 56.3 | 6.193 | 0.161 | 9.584 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 13.884 | No |
7 | SMSTORE5 | 174.19 | 28.1 | 6.194 | 0.161 | 9.699 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 13.999 | No |
8 | SMSTORE6 | 174.19 | 28.1 | 6.194 | 0.161 | 9.699 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 13.999 | No |
9 | SMSTORE7 | 174.19 | 28.1 | 6.194 | 0.161 | 9.699 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 13.999 | No |
10 | SMSTORE8 | 174.19 | 28.1 | 6.194 | 0.161 | 9.699 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 13.999 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | LGSTORE1 | TYPE1_OCC_SCH | LGSTORE1 | 348.39 | 56.3 | 56.3 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 56 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | SMSTORE1 | TYPE1_OCC_SCH | SMSTORE1 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | SMSTORE2 | TYPE2_OCC_SCH | SMSTORE2 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | SMSTORE3 | TYPE2_OCC_SCH | SMSTORE3 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | SMSTORE4 | TYPE2_OCC_SCH | SMSTORE4 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | LGSTORE2 | TYPE3_OCC_SCH | LGSTORE2 | 348.39 | 56.3 | 56.3 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 56 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | SMSTORE5 | TYPE3_OCC_SCH | SMSTORE5 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | SMSTORE6 | TYPE3_OCC_SCH | SMSTORE6 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | SMSTORE7 | TYPE3_OCC_SCH | SMSTORE7 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | SMSTORE8 | TYPE3_OCC_SCH | SMSTORE8 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | LGSTORE1_LIGHTS | LTG_SCH_BASE_LPD1 | LGSTORE1 | 348.39 | 56.3 | 3346.345 | 9.605 | 59.490 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3346.345 |
2 | LGSTORE1_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | LGSTORE1 | 348.39 | 56.3 | 1984.726 | 5.697 | 35.284 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1984.726 |
3 | SMSTORE1_LIGHTS | LTG_SCH_BASE_SMALL_LPD1 | SMSTORE1 | 174.19 | 28.1 | 1693.257 | 9.721 | 60.206 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1693.257 |
4 | SMSTORE1_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | SMSTORE1 | 174.19 | 28.1 | 1492.567 | 8.568 | 53.070 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1492.567 |
5 | SMSTORE2_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE2 | 174.19 | 28.1 | 1689.582 | 9.699 | 60.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1689.582 |
6 | SMSTORE2_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE2 | 174.19 | 28.1 | 1211.319 | 6.954 | 43.070 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1211.319 |
7 | SMSTORE3_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE3 | 174.19 | 28.1 | 1689.582 | 9.699 | 60.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1689.582 |
8 | SMSTORE3_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE3 | 174.19 | 28.1 | 1211.319 | 6.954 | 43.070 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1211.319 |
9 | SMSTORE4_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE4 | 174.19 | 28.1 | 1689.582 | 9.699 | 60.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1689.582 |
10 | SMSTORE4_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE4 | 174.19 | 28.1 | 1211.319 | 6.954 | 43.070 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1211.319 |
11 | LGSTORE2_LIGHTS | LTG_SCH_BASE_LPD2 | LGSTORE2 | 348.39 | 56.3 | 3338.998 | 9.584 | 59.359 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3338.998 |
12 | LGSTORE2_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | LGSTORE2 | 348.39 | 56.3 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
13 | SMSTORE5_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE5 | 174.19 | 28.1 | 1689.582 | 9.699 | 60.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1689.582 |
14 | SMSTORE5_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE5 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
15 | SMSTORE6_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE6 | 174.19 | 28.1 | 1689.582 | 9.699 | 60.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1689.582 |
16 | SMSTORE6_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE6 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
17 | SMSTORE7_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE7 | 174.19 | 28.1 | 1689.582 | 9.699 | 60.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1689.582 |
18 | SMSTORE7_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE7 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
19 | SMSTORE8_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE8 | 174.19 | 28.1 | 1689.582 | 9.699 | 60.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1689.582 |
20 | SMSTORE8_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE8 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LGSTORE1_MISCPLUG_EQUIP | TYPE1_EQUIP_SCH | LGSTORE1 | 348.39 | 56.3 | 1498.062 | 4.300 | 26.632 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1498.062 |
2 | SMSTORE1_MISCPLUG_EQUIP | TYPE1_EQUIP_SCH | SMSTORE1 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
3 | SMSTORE2_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE2 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
4 | SMSTORE3_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE3 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
5 | SMSTORE4_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE4 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
6 | LGSTORE2_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | LGSTORE2 | 348.39 | 56.3 | 1498.062 | 4.300 | 26.632 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1498.062 |
7 | SMSTORE5_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE5 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
8 | SMSTORE6_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE6 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
9 | SMSTORE7_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE7 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
10 | SMSTORE8_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE8 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.770 | 0.700 | Rough |
5 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 0.5002 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
6 | LGSTORE1_FLOOR_FFACTOR | 36 | 2 | 7 | 0.167 | 0.1381 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
7 | SMSTORE1_FLOOR_FFACTOR | 37 | 2 | 7 | 0.167 | 0.7817E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
8 | SMSTORE2_FLOOR_FFACTOR | 38 | 2 | 7 | 0.167 | 0.7817E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | SMSTORE3_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.7817E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
10 | SMSTORE4_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.7817E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
11 | LGSTORE2_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.7817E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | SMSTORE5_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.7817E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | SMSTORE6_FLOOR_FFACTOR | 43 | 2 | 7 | 0.167 | 0.7817E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | SMSTORE7_FLOOR_FFACTOR | 44 | 2 | 7 | 0.167 | 0.7817E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | SMSTORE8_FLOOR_FFACTOR | 45 | 2 | 7 | 0.167 | 0.1990 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
6 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
7 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
8 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
10 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.765 |
11 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
12 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 7.167 |
13 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
14 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.72 |
15 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
16 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.72 |
17 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
18 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.72 |
19 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
20 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.72 |
21 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
22 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.72 |
23 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
24 | ~FC_Insulation_7 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.72 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_8 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.72 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_9 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.72 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_10 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.947 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
14 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
15 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
16 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
17 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
18 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
19 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
20 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
21 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
22 | 7 | -0.34830148E-12 | 0.72009358E-15 | -0.12050990E-12 | 0.11035014E-15 |
23 | 6 | 0.31919265E-07 | 0.14494330E-09 | 0.72848987E-08 | -0.15272991E-12 |
24 | 5 | -0.20646226E-03 | 0.12163433E-05 | -0.10595611E-03 | 0.71905312E-08 |
25 | 4 | 0.31108415 | 0.58168425E-03 | 0.10650364 | -0.36263669E-04 |
26 | 3 | -7.6409054 | 0.17741268E-01 | -2.4500961 | 0.30845998E-01 |
27 | 2 | 42.105983 | 0.62198429E-01 | 15.720002 | -0.34709621 |
28 | 1 | -81.491490 | 0.27724269E-01 | -29.549212 | 1.0987734 |
29 | 0 | 46.824333 | 0.55101924E-03 | 16.281706 | |
30 | 7 | -0.30768122E-08 | -0.20915384E-14 | 0.14239733E-14 | -0.43231278E-16 |
31 | 6 | 0.39835568E-05 | 0.26399824E-08 | 0.31946650E-02 | -0.26799527E-04 |
32 | 5 | -0.27951707E-03 | 0.15609240E-05 | -0.22399710 | 0.19585557E-02 |
33 | 4 | 0.63843515E-02 | 0.70996553E-04 | 4.8340844 | -0.45308610E-01 |
34 | 3 | -0.55922562E-01 | 0.56414668E-03 | -38.047054 | 0.39893714 |
35 | 2 | 0.19837327 | 0.93792475E-03 | 116.53385 | -1.4186067 |
36 | 1 | -0.28619643 | 0.28546699E-03 | -143.93668 | 2.0495227 |
37 | 0 | 0.13950394 | 0.69324754E-05 | 60.838472 | |
38 | 7 | -0.54670353E-08 | -0.11613337E-13 | 0.14223840E-14 | -0.37368711E-16 |
39 | 6 | 0.25207632E-05 | 0.15026623E-08 | 0.31993138E-02 | -0.26838525E-04 |
40 | 5 | -0.16410687E-03 | 0.88486983E-06 | -0.22426121 | 0.19608870E-02 |
41 | 4 | 0.36607299E-02 | 0.40162528E-04 | 4.8384812 | -0.45350877E-01 |
42 | 3 | -0.31781560E-01 | 0.31856588E-03 | -38.071881 | 0.39921157 |
43 | 2 | 0.11233251 | 0.52874598E-03 | 116.58215 | -1.4192529 |
44 | 1 | -0.16179893 | 0.16057723E-03 | -143.96511 | 2.0499900 |
45 | 0 | 0.78801674E-01 | 0.38948424E-05 | 60.838472 | |
46 | 7 | -0.54670353E-08 | -0.11613337E-13 | 0.14223844E-14 | -0.37368717E-16 |
47 | 6 | 0.25207632E-05 | 0.15026623E-08 | 0.31993138E-02 | -0.26838525E-04 |
48 | 5 | -0.16410687E-03 | 0.88486983E-06 | -0.22426121 | 0.19608870E-02 |
49 | 4 | 0.36607299E-02 | 0.40162528E-04 | 4.8384812 | -0.45350877E-01 |
50 | 3 | -0.31781560E-01 | 0.31856588E-03 | -38.071881 | 0.39921157 |
51 | 2 | 0.11233251 | 0.52874598E-03 | 116.58215 | -1.4192529 |
52 | 1 | -0.16179893 | 0.16057723E-03 | -143.96511 | 2.0499900 |
53 | 0 | 0.78801674E-01 | 0.38948424E-05 | 60.838472 | |
54 | 7 | -0.54670353E-08 | -0.11613337E-13 | 0.14223843E-14 | -0.37368715E-16 |
55 | 6 | 0.25207632E-05 | 0.15026623E-08 | 0.31993138E-02 | -0.26838525E-04 |
56 | 5 | -0.16410687E-03 | 0.88486983E-06 | -0.22426121 | 0.19608870E-02 |
57 | 4 | 0.36607299E-02 | 0.40162528E-04 | 4.8384812 | -0.45350877E-01 |
58 | 3 | -0.31781560E-01 | 0.31856588E-03 | -38.071881 | 0.39921157 |
59 | 2 | 0.11233251 | 0.52874598E-03 | 116.58215 | -1.4192529 |
60 | 1 | -0.16179893 | 0.16057723E-03 | -143.96511 | 2.0499900 |
61 | 0 | 0.78801674E-01 | 0.38948424E-05 | 60.838472 | |
62 | 7 | -0.54670353E-08 | -0.11613337E-13 | 0.14223847E-14 | -0.37368722E-16 |
63 | 6 | 0.25207632E-05 | 0.15026623E-08 | 0.31993138E-02 | -0.26838525E-04 |
64 | 5 | -0.16410687E-03 | 0.88486983E-06 | -0.22426121 | 0.19608870E-02 |
65 | 4 | 0.36607299E-02 | 0.40162528E-04 | 4.8384812 | -0.45350877E-01 |
66 | 3 | -0.31781560E-01 | 0.31856588E-03 | -38.071881 | 0.39921157 |
67 | 2 | 0.11233251 | 0.52874598E-03 | 116.58215 | -1.4192529 |
68 | 1 | -0.16179893 | 0.16057723E-03 | -143.96511 | 2.0499900 |
69 | 0 | 0.78801674E-01 | 0.38948424E-05 | 60.838472 | |
70 | 7 | -0.54670353E-08 | -0.11613337E-13 | 0.14223844E-14 | -0.37368717E-16 |
71 | 6 | 0.25207632E-05 | 0.15026623E-08 | 0.31993138E-02 | -0.26838525E-04 |
72 | 5 | -0.16410687E-03 | 0.88486983E-06 | -0.22426121 | 0.19608870E-02 |
73 | 4 | 0.36607299E-02 | 0.40162528E-04 | 4.8384812 | -0.45350877E-01 |
74 | 3 | -0.31781560E-01 | 0.31856588E-03 | -38.071881 | 0.39921157 |
75 | 2 | 0.11233251 | 0.52874598E-03 | 116.58215 | -1.4192529 |
76 | 1 | -0.16179893 | 0.16057723E-03 | -143.96511 | 2.0499900 |
77 | 0 | 0.78801674E-01 | 0.38948424E-05 | 60.838472 | |
78 | 7 | -0.54670353E-08 | -0.11613337E-13 | 0.14223845E-14 | -0.37368719E-16 |
79 | 6 | 0.25207632E-05 | 0.15026623E-08 | 0.31993138E-02 | -0.26838525E-04 |
80 | 5 | -0.16410687E-03 | 0.88486983E-06 | -0.22426121 | 0.19608870E-02 |
81 | 4 | 0.36607299E-02 | 0.40162528E-04 | 4.8384812 | -0.45350877E-01 |
82 | 3 | -0.31781560E-01 | 0.31856588E-03 | -38.071881 | 0.39921157 |
83 | 2 | 0.11233251 | 0.52874598E-03 | 116.58215 | -1.4192529 |
84 | 1 | -0.16179893 | 0.16057723E-03 | -143.96511 | 2.0499900 |
85 | 0 | 0.78801674E-01 | 0.38948424E-05 | 60.838472 | |
86 | 7 | -0.54670353E-08 | -0.11613337E-13 | 0.14223840E-14 | -0.37368711E-16 |
87 | 6 | 0.25207632E-05 | 0.15026623E-08 | 0.31993138E-02 | -0.26838525E-04 |
88 | 5 | -0.16410687E-03 | 0.88486983E-06 | -0.22426121 | 0.19608870E-02 |
89 | 4 | 0.36607299E-02 | 0.40162528E-04 | 4.8384812 | -0.45350877E-01 |
90 | 3 | -0.31781560E-01 | 0.31856588E-03 | -38.071881 | 0.39921157 |
91 | 2 | 0.11233251 | 0.52874598E-03 | 116.58215 | -1.4192529 |
92 | 1 | -0.16179893 | 0.16057723E-03 | -143.96511 | 2.0499900 |
93 | 0 | 0.78801674E-01 | 0.38948424E-05 | 60.838472 | |
94 | 7 | -0.54670353E-08 | -0.11613337E-13 | 0.14223844E-14 | -0.37368717E-16 |
95 | 6 | 0.25207632E-05 | 0.15026623E-08 | 0.31993138E-02 | -0.26838525E-04 |
96 | 5 | -0.16410687E-03 | 0.88486983E-06 | -0.22426121 | 0.19608870E-02 |
97 | 4 | 0.36607299E-02 | 0.40162528E-04 | 4.8384812 | -0.45350877E-01 |
98 | 3 | -0.31781560E-01 | 0.31856588E-03 | -38.071881 | 0.39921157 |
99 | 2 | 0.11233251 | 0.52874598E-03 | 116.58215 | -1.4192529 |
100 | 1 | -0.16179893 | 0.16057723E-03 | -143.96511 | 2.0499900 |
101 | 0 | 0.78801674E-01 | 0.38948424E-05 | 60.838472 | |
102 | 7 | -0.21207308E-08 | -0.69128065E-15 | 0.45866753E-14 | -0.60902147E-16 |
103 | 6 | 0.56000727E-05 | 0.38109606E-08 | 0.31899011E-02 | -0.26759564E-04 |
104 | 5 | -0.40083884E-03 | 0.22562489E-05 | -0.22372635 | 0.19561660E-02 |
105 | 4 | 0.92084614E-02 | 0.10268861E-03 | 4.8295754 | -0.45265267E-01 |
106 | 3 | -0.80828076E-01 | 0.81646647E-03 | -38.021585 | 0.39865561 |
107 | 2 | 0.28695633 | 0.13581156E-02 | 116.48428 | -1.4179437 |
108 | 1 | -0.41414885 | 0.41367783E-03 | -143.90750 | 2.0490431 |
109 | 0 | 0.20191061 | 0.10030641E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.342_SHGC_0.379 | 35 | 1 | VerySmooth | 1.943 | 1.943 | 1.000 | 0.380 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 3.82380E-002 | 0.29270 | 0.50360 | 0.50360 | 0.41690 | 0.13592 | 0.17539 | 0.00000 | 0.84000 | 0.84000 | 0.11194 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | GAS TANK1 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
2 | WaterHeater:Mixed | GAS TANK2 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
3 | WaterHeater:Mixed | GAS TANK3 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
4 | WaterHeater:Mixed | GAS TANK4 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
5 | WaterHeater:Mixed | GAS TANK5 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
6 | WaterHeater:Mixed | GAS TANK6 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
7 | WaterHeater:Mixed | GAS TANK7 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | LGSTORE1_WALL_2 | 0 | 118.41 | 56.08 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
2 | LGSTORE1_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
3 | LGSTORE1_WALL_3_DOOR_1 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
4 | LGSTORE1_WALL_3_DOOR_2 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
5 | LGSTORE1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
6 | LGSTORE1_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
7 | LGSTORE1_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
8 | LGSTORE1_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
9 | LGSTORE1_WALL_1_WINDOW_3 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
10 | LGSTORE1_WALL_1_WINDOW_4 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
11 | LGSTORE1_WALL_1_DOOR_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 1 | No | No |
12 | LGSTORE1_WALL_1_DOOR_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 1 | No | No |
13 | LGSTORE1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
14 | LGSTORE1_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
15 | LGSTORE1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
16 | SMSTORE1_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
17 | SMSTORE1_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
18 | SMSTORE1_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
19 | SMSTORE1_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
20 | SMSTORE1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
21 | SMSTORE1_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
22 | SMSTORE1_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
23 | SMSTORE1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
24 | SMSTORE1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
25 | SMSTORE1_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
26 | SMSTORE1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
27 | SMSTORE2_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
28 | SMSTORE2_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
29 | SMSTORE2_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
30 | SMSTORE2_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
31 | SMSTORE2_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
32 | SMSTORE2_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
33 | SMSTORE2_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
34 | SMSTORE2_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
35 | SMSTORE2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
36 | SMSTORE2_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
37 | SMSTORE2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
38 | SMSTORE3_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
39 | SMSTORE3_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
40 | SMSTORE3_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
41 | SMSTORE3_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
42 | SMSTORE3_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
43 | SMSTORE3_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
44 | SMSTORE3_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
45 | SMSTORE3_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
46 | SMSTORE3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
47 | SMSTORE3_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
48 | SMSTORE3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
49 | SMSTORE4_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
50 | SMSTORE4_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
51 | SMSTORE4_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
52 | SMSTORE4_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
53 | SMSTORE4_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
54 | SMSTORE4_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 3 | No | No |
55 | SMSTORE4_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
56 | SMSTORE4_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
57 | SMSTORE4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
58 | SMSTORE4_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
59 | SMSTORE4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
60 | LGSTORE2_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
61 | LGSTORE2_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 4 | No | No |
62 | LGSTORE2_WALL_3_DOOR_1 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
63 | LGSTORE2_WALL_3_DOOR_2 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
64 | LGSTORE2_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
65 | LGSTORE2_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 4 | No | No |
66 | LGSTORE2_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
67 | LGSTORE2_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
68 | LGSTORE2_WALL_1_WINDOW_3 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
69 | LGSTORE2_WALL_1_WINDOW_4 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
70 | LGSTORE2_WALL_1_DOOR_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
71 | LGSTORE2_WALL_1_DOOR_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
72 | LGSTORE2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
73 | LGSTORE2_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
74 | LGSTORE2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
75 | SMSTORE5_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
76 | SMSTORE5_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
77 | SMSTORE5_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
78 | SMSTORE5_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
79 | SMSTORE5_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
80 | SMSTORE5_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
81 | SMSTORE5_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
82 | SMSTORE5_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
83 | SMSTORE5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
84 | SMSTORE5_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
85 | SMSTORE5_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
86 | SMSTORE6_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
87 | SMSTORE6_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
88 | SMSTORE6_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
89 | SMSTORE6_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
90 | SMSTORE6_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
91 | SMSTORE6_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
92 | SMSTORE6_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
93 | SMSTORE6_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
94 | SMSTORE6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
95 | SMSTORE6_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
96 | SMSTORE6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
97 | SMSTORE7_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
98 | SMSTORE7_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
99 | SMSTORE7_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
100 | SMSTORE7_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
101 | SMSTORE7_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
102 | SMSTORE7_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 3 | No | No |
103 | SMSTORE7_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
104 | SMSTORE7_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
105 | SMSTORE7_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
106 | SMSTORE7_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
107 | SMSTORE7_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
108 | SMSTORE8_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 4 | No | No |
109 | SMSTORE8_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 2 | No | No |
110 | SMSTORE8_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 2 | No | No |
111 | SMSTORE8_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 1 | No | No |
112 | SMSTORE8_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
113 | SMSTORE8_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 3 | No | No |
114 | SMSTORE8_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
115 | SMSTORE8_WALL_4 | 0 | 118.41 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 3 | No | No |
116 | SMSTORE8_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
117 | SMSTORE8_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
118 | SMSTORE8_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | LGSTORE1_INFILTRATION | TYPE1_INFIL_SCH | LGSTORE1 | 348.39 | 56.3 | 0.157 | 4.517E-004 | 2.488E-004 | 0.314 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | LGSTORE1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LGSTORE1 | 348.39 | 56.3 | 0.241 | 6.922E-004 | 3.813E-004 | 0.481 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | SMSTORE1_INFILTRATION | TYPE1_INFIL_SCH | SMSTORE1 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | SMSTORE1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE1 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | SMSTORE2_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE2 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | SMSTORE2_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE2 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | SMSTORE3_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE3 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | SMSTORE3_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE3 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | SMSTORE4_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE4 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | SMSTORE4_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE4 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | LGSTORE2_INFILTRATION | TYPE3_INFIL_SCH | LGSTORE2 | 348.39 | 56.3 | 8.993E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | LGSTORE2_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LGSTORE2 | 348.39 | 56.3 | 0.241 | 6.922E-004 | 4.692E-004 | 0.481 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | SMSTORE5_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE5 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | SMSTORE5_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE5 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | SMSTORE6_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE6 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | SMSTORE6_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE6 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | SMSTORE7_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE7 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
18 | SMSTORE7_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE7 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | SMSTORE8_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE8 | 174.19 | 28.1 | 0.112 | 6.453E-004 | 2.994E-004 | 0.448 | 0.000 | 0.000 | 0.224 | 0.000 |
20 | SMSTORE8_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE8 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 3.583E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | LGSTORE1 | Mixing/Well-Stirred |
2 | SMSTORE1 | Mixing/Well-Stirred |
3 | SMSTORE2 | Mixing/Well-Stirred |
4 | SMSTORE3 | Mixing/Well-Stirred |
5 | SMSTORE4 | Mixing/Well-Stirred |
6 | LGSTORE2 | Mixing/Well-Stirred |
7 | SMSTORE5 | Mixing/Well-Stirred |
8 | SMSTORE6 | Mixing/Well-Stirred |
9 | SMSTORE7 | Mixing/Well-Stirred |
10 | SMSTORE8 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone LGSTORE1 | 1.2000 |
3 | Zone SMSTORE1 | 1.2000 |
4 | Zone SMSTORE2 | 1.2000 |
5 | Zone SMSTORE3 | 1.2000 |
6 | Zone SMSTORE4 | 1.2000 |
7 | Zone LGSTORE2 | 1.2000 |
8 | Zone SMSTORE5 | 1.2000 |
9 | Zone SMSTORE6 | 1.2000 |
10 | Zone SMSTORE7 | 1.2000 |
11 | Zone SMSTORE8 | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone LGSTORE1 | 1.2000 |
3 | Zone SMSTORE1 | 1.2000 |
4 | Zone SMSTORE2 | 1.2000 |
5 | Zone SMSTORE3 | 1.2000 |
6 | Zone SMSTORE4 | 1.2000 |
7 | Zone LGSTORE2 | 1.2000 |
8 | Zone SMSTORE5 | 1.2000 |
9 | Zone SMSTORE6 | 1.2000 |
10 | Zone SMSTORE7 | 1.2000 |
11 | Zone SMSTORE8 | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | LGSTORE1 | Cooling | 20990.39816 | 25188.47780 | 1.61545 | 1.93853 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 31.20000 | 1.53651E-002 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
2 | LGSTORE1 | Heating | 34379.58031 | 41255.49637 | 1.55347 | 1.86417 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -26.20000 | 3.61342E-004 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
3 | SMSTORE1 | Cooling | 11447.69442 | 13737.23330 | 0.85602 | 1.02722 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 27.17200 | 1.53576E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
4 | SMSTORE1 | Heating | 16223.46882 | 19468.16259 | 0.73309 | 0.87971 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -26.20000 | 3.61342E-004 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
5 | SMSTORE2 | Cooling | 11487.99784 | 13785.59741 | 0.85910 | 1.03092 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 25.37000 | 1.53543E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
6 | SMSTORE2 | Heating | 16369.32384 | 19643.18861 | 0.73968 | 0.88762 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -26.20000 | 3.61342E-004 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
7 | SMSTORE3 | Cooling | 11491.27429 | 13789.52915 | 0.88434 | 1.06121 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 30.93500 | 1.53646E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
8 | SMSTORE3 | Heating | 16427.35592 | 19712.82710 | 0.74231 | 0.89077 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -26.20000 | 3.61342E-004 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
9 | SMSTORE4 | Cooling | 11392.33188 | 13670.79826 | 0.85175 | 1.02210 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 25.37000 | 1.53543E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
10 | SMSTORE4 | Heating | 16561.33159 | 19873.59791 | 0.74836 | 0.89803 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -26.20000 | 3.61342E-004 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
11 | LGSTORE2 | Cooling | 19974.38749 | 23969.26499 | 1.53716 | 1.84460 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 30.93500 | 1.53646E-002 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
12 | LGSTORE2 | Heating | 31538.17211 | 37845.80654 | 1.42515 | 1.71018 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -26.20000 | 3.61342E-004 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
13 | SMSTORE5 | Cooling | 10542.08510 | 12650.50212 | 0.78662 | 0.94395 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 27.17200 | 1.53576E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
14 | SMSTORE5 | Heating | 16893.37011 | 20272.04413 | 0.76337 | 0.91604 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -26.20000 | 3.61342E-004 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
15 | SMSTORE6 | Cooling | 10466.33478 | 12559.60173 | 0.78080 | 0.93696 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 27.17200 | 1.53576E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
16 | SMSTORE6 | Heating | 16878.58526 | 20254.30231 | 0.76270 | 0.91524 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -26.20000 | 3.61342E-004 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
17 | SMSTORE7 | Cooling | 10349.91185 | 12419.89422 | 0.77184 | 0.92621 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 27.17200 | 1.53576E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
18 | SMSTORE7 | Heating | 17096.27979 | 20515.53574 | 0.77254 | 0.92704 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -26.20000 | 3.61342E-004 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
19 | SMSTORE8 | Cooling | 10817.41932 | 12980.90318 | 0.80781 | 0.96937 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 27.17200 | 1.53576E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
20 | SMSTORE8 | Heating | 21135.45997 | 25362.55197 | 0.95498 | 1.14598 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -26.20000 | 3.61342E-004 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC_1:1 | Cooling | Sensible | 28273.29 | 1.93853 | 1.93853 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-AC_1:1 | Heating | Sensible | 63119.44 | 1.86417 | 1.86417 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
3 | PSZ-AC_2:2 | Cooling | Sensible | 15176.12 | 1.05116 | 1.05116 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-AC_2:2 | Heating | Sensible | 30417.15 | 0.87971 | 0.87971 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
5 | PSZ-AC_3:3 | Cooling | Sensible | 15249.09 | 1.05748 | 1.05748 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
6 | PSZ-AC_3:3 | Heating | Sensible | 30589.63 | 0.88762 | 0.88762 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
7 | PSZ-AC_4:4 | Cooling | Sensible | 15294.75 | 1.06121 | 1.06121 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
8 | PSZ-AC_4:4 | Heating | Sensible | 30658.25 | 0.89077 | 0.89077 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
9 | PSZ-AC_5:5 | Cooling | Sensible | 15161.64 | 1.05074 | 1.05074 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
10 | PSZ-AC_5:5 | Heating | Sensible | 30816.68 | 0.89803 | 0.89803 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
11 | PSZ-AC_6:6 | Cooling | Sensible | 27037.59 | 1.84460 | 1.84460 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
12 | PSZ-AC_6:6 | Heating | Sensible | 59759.83 | 1.71018 | 1.71018 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
13 | PSZ-AC_7:7 | Cooling | Sensible | 13896.32 | 0.95199 | 0.95199 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
14 | PSZ-AC_7:7 | Heating | Sensible | 31209.34 | 0.91604 | 0.91604 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
15 | PSZ-AC_8:8 | Cooling | Sensible | 13810.74 | 0.94526 | 0.94526 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
16 | PSZ-AC_8:8 | Heating | Sensible | 31191.85 | 0.91524 | 0.91524 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
17 | PSZ-AC_9:9 | Cooling | Sensible | 13726.86 | 0.93874 | 0.93874 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
18 | PSZ-AC_9:9 | Heating | Sensible | 31449.28 | 0.92704 | 0.92704 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
19 | PSZ-AC_10:10 | Cooling | Sensible | 14363.54 | 0.99638 | 0.99638 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
20 | PSZ-AC_10:10 | Heating | Sensible | 36225.34 | 1.14598 | 1.14598 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | LGSTORE1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.93853 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.02722 |
3 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.03092 |
4 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.06121 |
5 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE4 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.02210 |
6 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | LGSTORE2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.84460 |
7 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE5 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.94395 |
8 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.93696 |
9 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE7 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.92704 |
10 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE8 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.14598 |
11 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.93853 |
12 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.93853 |
13 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.93853 |
14 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.93853 |
15 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.93853 |
16 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Main Design Air Flow Rate [m3/s] | 1.93853 |
17 | AirLoopHVAC | PSZ-AC_1:1 | User Heating Air Flow Ratio [] | 1.00000 |
18 | AirLoopHVAC | PSZ-AC_1:1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
19 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.02722 |
20 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.02722 |
21 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.02722 |
22 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.02722 |
23 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.05116 |
24 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Main Design Air Flow Rate [m3/s] | 1.05116 |
25 | AirLoopHVAC | PSZ-AC_2:2 | User Heating Air Flow Ratio [] | 1.00000 |
26 | AirLoopHVAC | PSZ-AC_2:2 | Calculated Heating Air Flow Ratio [] | 0.97723 |
27 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.03092 |
28 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.03092 |
29 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.03092 |
30 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.03092 |
31 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.05748 |
32 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Main Design Air Flow Rate [m3/s] | 1.05748 |
33 | AirLoopHVAC | PSZ-AC_3:3 | User Heating Air Flow Ratio [] | 1.00000 |
34 | AirLoopHVAC | PSZ-AC_3:3 | Calculated Heating Air Flow Ratio [] | 0.97489 |
35 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.06121 |
36 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.06121 |
37 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.06121 |
38 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.06121 |
39 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.06121 |
40 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Main Design Air Flow Rate [m3/s] | 1.06121 |
41 | AirLoopHVAC | PSZ-AC_4:4 | User Heating Air Flow Ratio [] | 1.00000 |
42 | AirLoopHVAC | PSZ-AC_4:4 | Calculated Heating Air Flow Ratio [] | 1.00000 |
43 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.02210 |
44 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.02210 |
45 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.02210 |
46 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.02210 |
47 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.05074 |
48 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Main Design Air Flow Rate [m3/s] | 1.05074 |
49 | AirLoopHVAC | PSZ-AC_5:5 | User Heating Air Flow Ratio [] | 1.00000 |
50 | AirLoopHVAC | PSZ-AC_5:5 | Calculated Heating Air Flow Ratio [] | 0.97275 |
51 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.84460 |
52 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.84460 |
53 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.84460 |
54 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.84460 |
55 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.84460 |
56 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Main Design Air Flow Rate [m3/s] | 1.84460 |
57 | AirLoopHVAC | PSZ-AC_6:6 | User Heating Air Flow Ratio [] | 1.00000 |
58 | AirLoopHVAC | PSZ-AC_6:6 | Calculated Heating Air Flow Ratio [] | 1.00000 |
59 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.94395 |
60 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.94395 |
61 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.94395 |
62 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.94395 |
63 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.95199 |
64 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Main Design Air Flow Rate [m3/s] | 0.95199 |
65 | AirLoopHVAC | PSZ-AC_7:7 | User Heating Air Flow Ratio [] | 1.00000 |
66 | AirLoopHVAC | PSZ-AC_7:7 | Calculated Heating Air Flow Ratio [] | 0.99155 |
67 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.93696 |
68 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.93696 |
69 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.93696 |
70 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.93696 |
71 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.94526 |
72 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Main Design Air Flow Rate [m3/s] | 0.94526 |
73 | AirLoopHVAC | PSZ-AC_8:8 | User Heating Air Flow Ratio [] | 1.00000 |
74 | AirLoopHVAC | PSZ-AC_8:8 | Calculated Heating Air Flow Ratio [] | 0.99122 |
75 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.92704 |
76 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.92704 |
77 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.92704 |
78 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.92704 |
79 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.93874 |
80 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Main Design Air Flow Rate [m3/s] | 0.93874 |
81 | AirLoopHVAC | PSZ-AC_9:9 | User Heating Air Flow Ratio [] | 1.00000 |
82 | AirLoopHVAC | PSZ-AC_9:9 | Calculated Heating Air Flow Ratio [] | 0.98754 |
83 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.14598 |
84 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.14598 |
85 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.14598 |
86 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.14598 |
87 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.14598 |
88 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Main Design Air Flow Rate [m3/s] | 1.14598 |
89 | AirLoopHVAC | PSZ-AC_10:10 | User Heating Air Flow Ratio [] | 1.00000 |
90 | AirLoopHVAC | PSZ-AC_10:10 | Calculated Heating Air Flow Ratio [] | 1.00000 |
91 | AirLoopHVAC | PSZ-AC_1:1 | Design Supply Air Flow Rate [m3/s] | 1.93853 |
92 | AirLoopHVAC | PSZ-AC_2:2 | Design Supply Air Flow Rate [m3/s] | 1.05116 |
93 | AirLoopHVAC | PSZ-AC_3:3 | Design Supply Air Flow Rate [m3/s] | 1.05748 |
94 | AirLoopHVAC | PSZ-AC_4:4 | Design Supply Air Flow Rate [m3/s] | 1.06121 |
95 | AirLoopHVAC | PSZ-AC_5:5 | Design Supply Air Flow Rate [m3/s] | 1.05074 |
96 | AirLoopHVAC | PSZ-AC_6:6 | Design Supply Air Flow Rate [m3/s] | 1.84460 |
97 | AirLoopHVAC | PSZ-AC_7:7 | Design Supply Air Flow Rate [m3/s] | 0.95199 |
98 | AirLoopHVAC | PSZ-AC_8:8 | Design Supply Air Flow Rate [m3/s] | 0.94526 |
99 | AirLoopHVAC | PSZ-AC_9:9 | Design Supply Air Flow Rate [m3/s] | 0.93874 |
100 | AirLoopHVAC | PSZ-AC_10:10 | Design Supply Air Flow Rate [m3/s] | 1.14598 |
101 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.93853 |
102 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41148 |
103 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.93853 |
104 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 2074.32365 |
105 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.93853 |
106 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.93853 |
107 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.93853 |
108 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.27943 |
109 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.93853 |
110 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.96927 |
111 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.29235 |
112 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 44494.47000 |
113 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 22247.23500 |
114 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.72615 |
115 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.72615 |
116 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 44494.47000 |
117 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 64741.21281 |
118 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
119 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
120 | Coil:Heating:Fuel | PSZ-AC_1:1 HEATING COIL | Design Size Nominal Capacity [W] | 64741.21281 |
121 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.05116 |
122 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
123 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.05116 |
124 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1163.80092 |
125 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.05116 |
126 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.05116 |
127 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.05116 |
128 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.69377 |
129 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.05116 |
130 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.52558 |
131 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.70077 |
132 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 23588.56000 |
133 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 11794.28000 |
134 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.73421 |
135 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.73421 |
136 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 23588.56000 |
137 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 33633.96585 |
138 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
139 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
140 | Coil:Heating:Fuel | PSZ-AC_2:2 HEATING COIL | Design Size Nominal Capacity [W] | 33633.96585 |
141 | Controller:OutdoorAir | PSZ-AC_3:3_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.05748 |
142 | Controller:OutdoorAir | PSZ-AC_3:3_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
143 | Fan:SystemModel | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.05748 |
144 | Fan:SystemModel | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1170.79560 |
145 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.05748 |
146 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.05748 |
147 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.05748 |
148 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.69794 |
149 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.05748 |
150 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.52874 |
151 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.70499 |
152 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 23695.28000 |
153 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 11847.64000 |
154 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.73461 |
155 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.73461 |
156 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 23695.28000 |
157 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 33714.65293 |
158 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
159 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
160 | Coil:Heating:Fuel | PSZ-AC_3:3 HEATING COIL | Design Size Nominal Capacity [W] | 33714.65293 |
161 | Controller:OutdoorAir | PSZ-AC_4:4_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.06121 |
162 | Controller:OutdoorAir | PSZ-AC_4:4_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
163 | Fan:SystemModel | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.06121 |
164 | Fan:SystemModel | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1174.92646 |
165 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.06121 |
166 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.06121 |
167 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.06121 |
168 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.70040 |
169 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.06121 |
170 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.53060 |
171 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.70747 |
172 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 23757.00000 |
173 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 11878.50000 |
174 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.73486 |
175 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.73486 |
176 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 23757.00000 |
177 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 34375.17398 |
178 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
179 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
180 | Coil:Heating:Fuel | PSZ-AC_4:4 HEATING COIL | Design Size Nominal Capacity [W] | 34375.17398 |
181 | Controller:OutdoorAir | PSZ-AC_5:5_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.05074 |
182 | Controller:OutdoorAir | PSZ-AC_5:5_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
183 | Fan:SystemModel | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.05074 |
184 | Fan:SystemModel | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1163.33401 |
185 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.05074 |
186 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.05074 |
187 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.05074 |
188 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.69349 |
189 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.05074 |
190 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.52537 |
191 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.70049 |
192 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 23586.13000 |
193 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 11793.06500 |
194 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.73413 |
195 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.73413 |
196 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 23586.13000 |
197 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 33522.34289 |
198 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
199 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
200 | Coil:Heating:Fuel | PSZ-AC_5:5 HEATING COIL | Design Size Nominal Capacity [W] | 33522.34289 |
201 | Controller:OutdoorAir | PSZ-AC_6:6_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.84460 |
202 | Controller:OutdoorAir | PSZ-AC_6:6_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41148 |
203 | Fan:SystemModel | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.84460 |
204 | Fan:SystemModel | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1973.80663 |
205 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.84460 |
206 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.84460 |
207 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.84460 |
208 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.21743 |
209 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.84460 |
210 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.92230 |
211 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.22973 |
212 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 42688.27000 |
213 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 21344.13500 |
214 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.72398 |
215 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.72398 |
216 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 42688.27000 |
217 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 62691.16215 |
218 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
219 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
220 | Coil:Heating:Fuel | PSZ-AC_6:6 HEATING COIL | Design Size Nominal Capacity [W] | 62691.16215 |
221 | Controller:OutdoorAir | PSZ-AC_7:7_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.95199 |
222 | Controller:OutdoorAir | PSZ-AC_7:7_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
223 | Fan:SystemModel | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.95199 |
224 | Fan:SystemModel | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1054.00264 |
225 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.95199 |
226 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.95199 |
227 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.95199 |
228 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.62831 |
229 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.95199 |
230 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.47599 |
231 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.63466 |
232 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 21966.03000 |
233 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 10983.01500 |
234 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.72476 |
235 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.72476 |
236 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 21966.03000 |
237 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 31817.90321 |
238 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
239 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
240 | Coil:Heating:Fuel | PSZ-AC_7:7 HEATING COIL | Design Size Nominal Capacity [W] | 31817.90321 |
241 | Controller:OutdoorAir | PSZ-AC_8:8_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.94526 |
242 | Controller:OutdoorAir | PSZ-AC_8:8_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
243 | Fan:SystemModel | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.94526 |
244 | Fan:SystemModel | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1046.55038 |
245 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.94526 |
246 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.94526 |
247 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.94526 |
248 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.62387 |
249 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.94526 |
250 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.47263 |
251 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.63017 |
252 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 21854.31000 |
253 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 10927.15500 |
254 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.72424 |
255 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.72424 |
256 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 21854.31000 |
257 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 31665.49758 |
258 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
259 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
260 | Coil:Heating:Fuel | PSZ-AC_8:8 HEATING COIL | Design Size Nominal Capacity [W] | 31665.49758 |
261 | Controller:OutdoorAir | PSZ-AC_9:9_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.93874 |
262 | Controller:OutdoorAir | PSZ-AC_9:9_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
263 | Fan:SystemModel | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.93874 |
264 | Fan:SystemModel | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1039.33524 |
265 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.93874 |
266 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.93874 |
267 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.93874 |
268 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.61957 |
269 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.93874 |
270 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.46937 |
271 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.62583 |
272 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 21746.54000 |
273 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 10873.27000 |
274 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.72272 |
275 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.72272 |
276 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 21746.54000 |
277 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 31449.28465 |
278 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
279 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
280 | Coil:Heating:Fuel | PSZ-AC_9:9 HEATING COIL | Design Size Nominal Capacity [W] | 31449.28465 |
281 | Controller:OutdoorAir | PSZ-AC_10:10_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.14598 |
282 | Controller:OutdoorAir | PSZ-AC_10:10_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
283 | Fan:SystemModel | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.14598 |
284 | Fan:SystemModel | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1268.77641 |
285 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.14598 |
286 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.14598 |
287 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.14598 |
288 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.75634 |
289 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.14598 |
290 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.57299 |
291 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.76399 |
292 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 26235.97000 |
293 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 13117.98500 |
294 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.72683 |
295 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.72683 |
296 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 26235.97000 |
297 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 36225.33864 |
298 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
299 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
300 | Coil:Heating:Fuel | PSZ-AC_10:10 HEATING COIL | Design Size Nominal Capacity [W] | 36225.33864 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | 42967.4 | 11.63 | 11.63 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | 22760.9 | 11.76 | 11.76 | |||
3 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | 22862.6 | 11.76 | 11.76 | |||
4 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | 22921.4 | 11.76 | 11.76 | |||
5 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | 22758.8 | 11.76 | 11.76 | |||
6 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | 41235.0 | 11.64 | 11.64 | |||
7 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | 21216.0 | 11.81 | 11.81 | |||
8 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | 21109.6 | 11.82 | 11.82 | |||
9 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | 21006.9 | 11.82 | 11.82 | |||
10 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | 25333.3 | 11.80 | 11.80 |
Zone Name | # Surfaces | |
1 | LGSTORE1 | 15 |
2 | SMSTORE1 | 11 |
3 | SMSTORE2 | 11 |
4 | SMSTORE3 | 11 |
5 | SMSTORE4 | 11 |
6 | LGSTORE2 | 15 |
7 | SMSTORE5 | 11 |
8 | SMSTORE6 | 11 |
9 | SMSTORE7 | 11 |
10 | SMSTORE8 | 11 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | LGSTORE1_WALL_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.500 | 0.465 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | LGSTORE1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.500 | 0.465 | 71.15 | 78.94 | 71.15 | 0.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | LGSTORE1_WALL_3_DOOR_1 | Door | LGSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
4 | LGSTORE1_WALL_3_DOOR_2 | Door | LGSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
5 | LGSTORE1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
6 | LGSTORE1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.500 | 0.465 | 58.18 | 78.94 | 58.18 | 180.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
7 | LGSTORE1_WALL_1_WINDOW_1 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.342_SHGC_0.379 | N/A | 1.943 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
8 | LGSTORE1_WALL_1_WINDOW_2 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.342_SHGC_0.379 | N/A | 1.943 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
9 | LGSTORE1_WALL_1_WINDOW_3 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.342_SHGC_0.379 | N/A | 1.943 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
10 | LGSTORE1_WALL_1_WINDOW_4 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.342_SHGC_0.379 | N/A | 1.943 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
11 | LGSTORE1_WALL_1_DOOR_1 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.342_SHGC_0.379 | N/A | 1.943 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
12 | LGSTORE1_WALL_1_DOOR_2 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.342_SHGC_0.379 | N/A | 1.943 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
13 | LGSTORE1_FLOOR | Floor | CTF - ConductionTransferFunction | LGSTORE1_FLOOR_FFACTOR | 0.138 | 0.134 | 348.39 | 348.39 | 348.39 | 270.00 | 180.00 | 22.86 | 15.24 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | LGSTORE1_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 348.39 | 348.39 | 348.39 | 270.00 | 0.00 | 22.86 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
15 | LGSTORE1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 696.77 | 696.77 | 696.77 | 0.00 | 90.00 | 696.77 | 1.00 | 0.00 | LGSTORE1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
16 | SMSTORE1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.500 | 0.465 | 29.09 | 39.47 | 29.09 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
17 | SMSTORE1_WALL_1_WINDOW_1 | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.342_SHGC_0.379 | N/A | 1.943 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
18 | SMSTORE1_WALL_1_WINDOW_2 | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.342_SHGC_0.379 | N/A | 1.943 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
19 | SMSTORE1_WALL_1_DOOR | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.342_SHGC_0.379 | N/A | 1.943 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
20 | SMSTORE1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | SMSTORE1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.500 | 0.465 | 35.57 | 39.47 | 35.57 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | SMSTORE1_WALL_3_DOOR | Door | SMSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
23 | SMSTORE1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE2_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | SMSTORE1_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE1_FLOOR_FFACTOR | 7.817E-002 | 7.671E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | SMSTORE1_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
26 | SMSTORE1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
27 | SMSTORE2_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.500 | 0.465 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | SMSTORE2_WALL_1_WINDOW_1 | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.342_SHGC_0.379 | N/A | 1.943 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
29 | SMSTORE2_WALL_1_WINDOW_2 | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.342_SHGC_0.379 | N/A | 1.943 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
30 | SMSTORE2_WALL_1_DOOR | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.342_SHGC_0.379 | N/A | 1.943 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
31 | SMSTORE2_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | SMSTORE2_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.500 | 0.465 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | SMSTORE2_WALL_3_DOOR | Door | SMSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
34 | SMSTORE2_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE3_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | SMSTORE2_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE2_FLOOR_FFACTOR | 7.817E-002 | 7.671E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | SMSTORE2_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | SMSTORE2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | SMSTORE3_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.500 | 0.465 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | SMSTORE3_WALL_1_WINDOW_1 | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.342_SHGC_0.379 | N/A | 1.943 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
40 | SMSTORE3_WALL_1_WINDOW_2 | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.342_SHGC_0.379 | N/A | 1.943 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
41 | SMSTORE3_WALL_1_DOOR | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.342_SHGC_0.379 | N/A | 1.943 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
42 | SMSTORE3_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE2_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | SMSTORE3_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.500 | 0.465 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | SMSTORE3_WALL_3_DOOR | Door | SMSTORE3_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
45 | SMSTORE3_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE4_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | SMSTORE3_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE3_FLOOR_FFACTOR | 7.817E-002 | 7.671E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
47 | SMSTORE3_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
48 | SMSTORE3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
49 | SMSTORE4_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.500 | 0.465 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | SMSTORE4_WALL_1_WINDOW_1 | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.342_SHGC_0.379 | N/A | 1.943 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
51 | SMSTORE4_WALL_1_WINDOW_2 | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.342_SHGC_0.379 | N/A | 1.943 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
52 | SMSTORE4_WALL_1_DOOR | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.342_SHGC_0.379 | N/A | 1.943 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | SMSTORE4_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE3_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | SMSTORE4_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.500 | 0.465 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | SMSTORE4_WALL_3_DOOR | Door | SMSTORE4_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | SMSTORE4_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE2_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | SMSTORE4_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE4_FLOOR_FFACTOR | 7.817E-002 | 7.671E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | SMSTORE4_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | SMSTORE4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | LGSTORE2_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE4_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | LGSTORE2_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.500 | 0.465 | 71.19 | 78.94 | 71.19 | 0.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
62 | LGSTORE2_WALL_3_DOOR_1 | Door | LGSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
63 | LGSTORE2_WALL_3_DOOR_2 | Door | LGSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
64 | LGSTORE2_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE5_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LGSTORE2_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.500 | 0.465 | 58.22 | 78.94 | 58.22 | 180.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
66 | LGSTORE2_WALL_1_WINDOW_1 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.342_SHGC_0.379 | N/A | 1.943 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | LGSTORE2_WALL_1_WINDOW_2 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.342_SHGC_0.379 | N/A | 1.943 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | LGSTORE2_WALL_1_WINDOW_3 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.342_SHGC_0.379 | N/A | 1.943 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | LGSTORE2_WALL_1_WINDOW_4 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.342_SHGC_0.379 | N/A | 1.943 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LGSTORE2_WALL_1_DOOR_1 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.342_SHGC_0.379 | N/A | 1.943 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
71 | LGSTORE2_WALL_1_DOOR_2 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.342_SHGC_0.379 | N/A | 1.943 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
72 | LGSTORE2_FLOOR | Floor | CTF - ConductionTransferFunction | LGSTORE2_FLOOR_FFACTOR | 7.817E-002 | 7.671E-002 | 348.39 | 348.39 | 348.39 | 270.00 | 180.00 | 22.86 | 15.24 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
73 | LGSTORE2_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 348.39 | 348.39 | 348.39 | 270.00 | 0.00 | 22.86 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
74 | LGSTORE2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 696.77 | 696.77 | 696.77 | 0.00 | 90.00 | 696.77 | 1.00 | 0.00 | LGSTORE2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
75 | SMSTORE5_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.500 | 0.465 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | SMSTORE5_WALL_1_WINDOW_1 | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.342_SHGC_0.379 | N/A | 1.943 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
77 | SMSTORE5_WALL_1_WINDOW_2 | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.342_SHGC_0.379 | N/A | 1.943 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | SMSTORE5_WALL_1_DOOR | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.342_SHGC_0.379 | N/A | 1.943 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
79 | SMSTORE5_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE2_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | SMSTORE5_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.500 | 0.465 | 35.59 | 39.47 | 35.59 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | SMSTORE5_WALL_3_DOOR | Door | SMSTORE5_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
82 | SMSTORE5_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE6_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
83 | SMSTORE5_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE5_FLOOR_FFACTOR | 7.817E-002 | 7.671E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
84 | SMSTORE5_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
85 | SMSTORE5_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE5_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | SMSTORE6_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.500 | 0.465 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | SMSTORE6_WALL_1_WINDOW_1 | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.342_SHGC_0.379 | N/A | 1.943 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | SMSTORE6_WALL_1_WINDOW_2 | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.342_SHGC_0.379 | N/A | 1.943 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
89 | SMSTORE6_WALL_1_DOOR | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.342_SHGC_0.379 | N/A | 1.943 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | SMSTORE6_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE5_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | SMSTORE6_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.500 | 0.465 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | SMSTORE6_WALL_3_DOOR | Door | SMSTORE6_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
93 | SMSTORE6_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE7_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | SMSTORE6_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE6_FLOOR_FFACTOR | 7.817E-002 | 7.671E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
95 | SMSTORE6_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
96 | SMSTORE6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
97 | SMSTORE7_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.500 | 0.465 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | SMSTORE7_WALL_1_WINDOW_1 | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.342_SHGC_0.379 | N/A | 1.943 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | SMSTORE7_WALL_1_WINDOW_2 | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.342_SHGC_0.379 | N/A | 1.943 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
100 | SMSTORE7_WALL_1_DOOR | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.342_SHGC_0.379 | N/A | 1.943 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
101 | SMSTORE7_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE6_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
102 | SMSTORE7_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.500 | 0.465 | 35.59 | 39.47 | 35.59 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | SMSTORE7_WALL_3_DOOR | Door | SMSTORE7_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
104 | SMSTORE7_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE8_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | SMSTORE7_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE7_FLOOR_FFACTOR | 7.817E-002 | 7.671E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
106 | SMSTORE7_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
107 | SMSTORE7_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE7_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
108 | SMSTORE8_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.500 | 0.465 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | SMSTORE8_WALL_1_WINDOW_1 | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.342_SHGC_0.379 | N/A | 1.943 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
110 | SMSTORE8_WALL_1_WINDOW_2 | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.342_SHGC_0.379 | N/A | 1.943 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
111 | SMSTORE8_WALL_1_DOOR | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.342_SHGC_0.379 | N/A | 1.943 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
112 | SMSTORE8_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE7_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | SMSTORE8_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.500 | 0.465 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | SMSTORE8_WALL_3_DOOR | Door | SMSTORE8_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
115 | SMSTORE8_WALL_4 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.500 | 0.465 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | SMSTORE8_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE8_FLOOR_FFACTOR | 0.199 | 0.190 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | SMSTORE8_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | SMSTORE8_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE8_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | LGSTORE1 | RunPeriod: RUNPERIOD 1 | 5.1123917367E-002 | 0.2841789799 | Pass | Pass | 0.4703605377 | 2.8866256979 | Pass | Pass |
2 | SMSTORE1 | RunPeriod: RUNPERIOD 1 | 5.0254932071E-002 | 0.2264134125 | Pass | Pass | 9.5346879829E-002 | 0.4118647981 | Pass | Pass |
3 | SMSTORE2 | RunPeriod: RUNPERIOD 1 | 5.3462235468E-002 | 0.2842856433 | Pass | Pass | 8.7834899506E-002 | 0.6530421409 | Pass | Pass |
4 | SMSTORE3 | RunPeriod: RUNPERIOD 1 | 5.9492866634E-002 | 0.3195262606 | Pass | Pass | 7.2913812305E-002 | 0.5098306703 | Pass | Pass |
5 | SMSTORE4 | RunPeriod: RUNPERIOD 1 | 6.3745491694E-002 | 0.3400410687 | Pass | Pass | 6.9828236139E-002 | 0.4960937357 | Pass | Pass |
6 | LGSTORE2 | RunPeriod: RUNPERIOD 1 | 7.6107746424E-002 | 0.3881956119 | Pass | Pass | 2.6063921589E-002 | 9.2298818334E-002 | Pass | Pass |
7 | SMSTORE5 | RunPeriod: RUNPERIOD 1 | 7.5066157528E-002 | 0.3849134414 | Pass | Pass | 2.4934030517E-002 | 8.4538541174E-002 | Pass | Pass |
8 | SMSTORE6 | RunPeriod: RUNPERIOD 1 | 7.5925477476E-002 | 0.3895581446 | Pass | Pass | 2.4840156882E-002 | 8.4253650948E-002 | Pass | Pass |
9 | SMSTORE7 | RunPeriod: RUNPERIOD 1 | 8.0603229486E-002 | 0.4116559392 | Pass | Pass | 2.4435837153E-002 | 8.4482350009E-002 | Pass | Pass |
10 | SMSTORE8 | RunPeriod: RUNPERIOD 1 | 0.1584546004 | 0.4593666404 | Pass | Pass | 0.7911716878 | 4.0492465887 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:25
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 3976.43 | 310.22 | 0.00 | 647.65 | 569.92 | 5504.23 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:25
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | -26.20 | 0.00 | -26.20 | Wetbulb [C] | 5.70 | 310.00 |
ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 31.20 | 10.60 | 23.10 | Wetbulb [C] | 6.70 | 200.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 26.00 | 35 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 29.00 | 23 | |||
May | 0.00 | 0 | |||
Jun | 107.00 | 45 | |||
Jul | 72.00 | 29 | |||
Aug | 0.00 | 0 | |||
Sep | 20.00 | 11 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 4.00 | 8 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:25
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_2 | NONRES_EXT_WALL_GRD | 0.30 | 0.465 | 0.500 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE1_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.465 | 0.500 | 78.94 | 71.15 | 0.00 | 90.00 | N |
LGSTORE1_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.465 | 0.500 | 78.94 | 58.18 | 180.00 | 90.00 | S |
LGSTORE1_FLOOR | LGSTORE1_FLOOR_FFACTOR | 1.00 | 0.135 | 0.138 | 348.39 | 348.39 | 270.00 | 180.00 | |
LGSTORE1_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 348.39 | 348.39 | 270.00 | 0.00 | |
SMSTORE1_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.465 | 0.500 | 39.47 | 29.09 | 180.00 | 90.00 | S |
SMSTORE1_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.465 | 0.500 | 39.47 | 35.57 | 0.00 | 90.00 | N |
SMSTORE1_FLOOR | SMSTORE1_FLOOR_FFACTOR | 1.00 | 0.077 | 0.078 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE1_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE2_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.465 | 0.500 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE2_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.465 | 0.500 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE2_FLOOR | SMSTORE2_FLOOR_FFACTOR | 1.00 | 0.077 | 0.078 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE2_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE3_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.465 | 0.500 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE3_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.465 | 0.500 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE3_FLOOR | SMSTORE3_FLOOR_FFACTOR | 1.00 | 0.077 | 0.078 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE3_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE4_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.465 | 0.500 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE4_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.465 | 0.500 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE4_FLOOR | SMSTORE4_FLOOR_FFACTOR | 1.00 | 0.077 | 0.078 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE4_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
LGSTORE2_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.465 | 0.500 | 78.94 | 71.19 | 0.00 | 90.00 | N |
LGSTORE2_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.465 | 0.500 | 78.94 | 58.22 | 180.00 | 90.00 | S |
LGSTORE2_FLOOR | LGSTORE2_FLOOR_FFACTOR | 1.00 | 0.077 | 0.078 | 348.39 | 348.39 | 270.00 | 180.00 | |
LGSTORE2_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 348.39 | 348.39 | 270.00 | 0.00 | |
SMSTORE5_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.465 | 0.500 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE5_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.465 | 0.500 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE5_FLOOR | SMSTORE5_FLOOR_FFACTOR | 1.00 | 0.077 | 0.078 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE5_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE6_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.465 | 0.500 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE6_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.465 | 0.500 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE6_FLOOR | SMSTORE6_FLOOR_FFACTOR | 1.00 | 0.077 | 0.078 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE6_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE7_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.465 | 0.500 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE7_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.465 | 0.500 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE7_FLOOR | SMSTORE7_FLOOR_FFACTOR | 1.00 | 0.077 | 0.078 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE7_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE8_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.465 | 0.500 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE8_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.465 | 0.500 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE8_WALL_4 | NONRES_EXT_WALL_GRD | 0.30 | 0.465 | 0.500 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE8_FLOOR | SMSTORE8_FLOOR_FFACTOR | 1.00 | 0.193 | 0.199 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE8_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE1_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE2_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE2_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE3_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE3_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE4_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE4_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
LGSTORE2_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE2_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE5_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE5_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE6_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE6_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE7_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE7_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE8_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 696.77 | 0.00 | 90.00 | N | ||
SMSTORE1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
LGSTORE2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 696.77 | 0.00 | 90.00 | N | ||
SMSTORE5_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE7_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE8_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.342_SHGC_0.379 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.943 | 0.380 | 0.418 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.342_SHGC_0.379 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.943 | 0.380 | 0.418 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_3 | NONRESWINDOW_U_0.342_SHGC_0.379 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.943 | 0.380 | 0.418 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_4 | NONRESWINDOW_U_0.342_SHGC_0.379 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.943 | 0.380 | 0.418 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_DOOR_1 | NONRESWINDOW_U_0.342_SHGC_0.379 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 1.943 | 0.380 | 0.418 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_DOOR_2 | NONRESWINDOW_U_0.342_SHGC_0.379 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 1.943 | 0.380 | 0.418 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.342_SHGC_0.379 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.943 | 0.380 | 0.418 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.342_SHGC_0.379 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.943 | 0.380 | 0.418 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_DOOR | NONRESWINDOW_U_0.342_SHGC_0.379 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 1.943 | 0.380 | 0.418 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.342_SHGC_0.379 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.943 | 0.380 | 0.418 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.342_SHGC_0.379 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.943 | 0.380 | 0.418 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_DOOR | NONRESWINDOW_U_0.342_SHGC_0.379 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 1.943 | 0.380 | 0.418 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.342_SHGC_0.379 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.943 | 0.380 | 0.418 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.342_SHGC_0.379 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.943 | 0.380 | 0.418 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_DOOR | NONRESWINDOW_U_0.342_SHGC_0.379 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 1.943 | 0.380 | 0.418 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.342_SHGC_0.379 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.943 | 0.380 | 0.418 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.342_SHGC_0.379 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.943 | 0.380 | 0.418 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_DOOR | NONRESWINDOW_U_0.342_SHGC_0.379 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 1.943 | 0.380 | 0.418 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.342_SHGC_0.379 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.943 | 0.380 | 0.418 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.342_SHGC_0.379 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.943 | 0.380 | 0.418 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_3 | NONRESWINDOW_U_0.342_SHGC_0.379 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.943 | 0.380 | 0.418 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_4 | NONRESWINDOW_U_0.342_SHGC_0.379 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.943 | 0.380 | 0.418 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_DOOR_1 | NONRESWINDOW_U_0.342_SHGC_0.379 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 1.943 | 0.380 | 0.418 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_DOOR_2 | NONRESWINDOW_U_0.342_SHGC_0.379 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 1.943 | 0.380 | 0.418 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.342_SHGC_0.379 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.943 | 0.380 | 0.418 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.342_SHGC_0.379 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.943 | 0.380 | 0.418 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_DOOR | NONRESWINDOW_U_0.342_SHGC_0.379 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 1.943 | 0.380 | 0.418 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.342_SHGC_0.379 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.943 | 0.380 | 0.418 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.342_SHGC_0.379 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.943 | 0.380 | 0.418 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_DOOR | NONRESWINDOW_U_0.342_SHGC_0.379 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 1.943 | 0.380 | 0.418 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.342_SHGC_0.379 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.943 | 0.380 | 0.418 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.342_SHGC_0.379 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.943 | 0.380 | 0.418 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_DOOR | NONRESWINDOW_U_0.342_SHGC_0.379 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 1.943 | 0.380 | 0.418 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.342_SHGC_0.379 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.943 | 0.380 | 0.418 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.342_SHGC_0.379 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.943 | 0.380 | 0.418 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_DOOR | NONRESWINDOW_U_0.342_SHGC_0.379 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 1.943 | 0.380 | 0.418 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
Total or Average | 124.40 | 1.943 | 0.380 | 0.418 | |||||||||||||||||
North Total or Average | 0.00 | - | - | - | |||||||||||||||||
Non-North Total or Average | 124.40 | 1.943 | 0.380 | 0.418 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
LGSTORE1_WALL_3_DOOR_1 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.90 | LGSTORE1_WALL_3 |
LGSTORE1_WALL_3_DOOR_2 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.90 | LGSTORE1_WALL_3 |
SMSTORE1_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.90 | SMSTORE1_WALL_3 |
SMSTORE2_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE2_WALL_3 |
SMSTORE3_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE3_WALL_3 |
SMSTORE4_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE4_WALL_3 |
LGSTORE2_WALL_3_DOOR_1 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | LGSTORE2_WALL_3 |
LGSTORE2_WALL_3_DOOR_2 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | LGSTORE2_WALL_3 |
SMSTORE5_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE5_WALL_3 |
SMSTORE6_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE6_WALL_3 |
SMSTORE7_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE7_WALL_3 |
SMSTORE8_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE8_WALL_3 |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:25
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
LGSTORE1_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_DOOR_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_DOOR_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_DOOR_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_DOOR_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:25
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
LGSTORE1_LIGHTS | LGSTORE1 | LGSTORE1 | GENERAL | 9.6053 | 348.39 | 3346.35 | LightsWired | LTG_SCH_BASE_LPD1 | 83.91 | 168.00 | 82.62 | 0.0000 | Y | 51.90 |
LGSTORE1_LIGHTS_ALLOWANCE | LGSTORE1 | LGSTORE1 | GENERAL | 5.6969 | 348.39 | 1984.73 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | 97.50 | 112.00 | 94.53 | 0.0000 | Y | 35.22 |
SMSTORE1_LIGHTS | SMSTORE1 | SMSTORE1 | GENERAL | 9.7206 | 174.19 | 1693.26 | LightsWired | LTG_SCH_BASE_SMALL_LPD1 | 85.41 | 168.00 | 84.05 | 0.0000 | Y | 26.72 |
SMSTORE1_LIGHTS_ALLOWANCE | SMSTORE1 | SMSTORE1 | GENERAL | 8.5685 | 174.19 | 1492.57 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | 97.50 | 112.00 | 94.53 | 0.0000 | Y | 26.49 |
SMSTORE2_LIGHTS | SMSTORE2 | SMSTORE2 | GENERAL | 9.6995 | 174.19 | 1689.58 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 68.73 | 168.00 | 65.95 | 0.0000 | Y | 20.92 |
SMSTORE2_LIGHTS_ALLOWANCE | SMSTORE2 | SMSTORE2 | GENERAL | 6.9539 | 174.19 | 1211.32 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 84.29 | 73.25 | 0.0000 | Y | 16.66 |
SMSTORE3_LIGHTS | SMSTORE3 | SMSTORE3 | GENERAL | 9.6995 | 174.19 | 1689.58 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 68.73 | 168.00 | 65.95 | 0.0000 | Y | 20.92 |
SMSTORE3_LIGHTS_ALLOWANCE | SMSTORE3 | SMSTORE3 | GENERAL | 6.9539 | 174.19 | 1211.32 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 84.29 | 73.25 | 0.0000 | Y | 16.66 |
SMSTORE4_LIGHTS | SMSTORE4 | SMSTORE4 | GENERAL | 9.6995 | 174.19 | 1689.58 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 68.73 | 168.00 | 65.95 | 0.0000 | Y | 20.92 |
SMSTORE4_LIGHTS_ALLOWANCE | SMSTORE4 | SMSTORE4 | GENERAL | 6.9539 | 174.19 | 1211.32 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 84.29 | 73.25 | 0.0000 | Y | 16.66 |
LGSTORE2_LIGHTS | LGSTORE2 | LGSTORE2 | GENERAL | 9.5842 | 348.39 | 3339.00 | LightsWired | LTG_SCH_BASE_LPD2 | 62.11 | 168.00 | 59.29 | 0.0000 | Y | 37.16 |
LGSTORE2_LIGHTS_ALLOWANCE | LGSTORE2 | LGSTORE2 | GENERAL | 0.0000 | 348.39 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE5_LIGHTS | SMSTORE5 | SMSTORE5 | GENERAL | 9.6995 | 174.19 | 1689.58 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 60.29 | 0.0000 | Y | 19.12 |
SMSTORE5_LIGHTS_ALLOWANCE | SMSTORE5 | SMSTORE5 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE6_LIGHTS | SMSTORE6 | SMSTORE6 | GENERAL | 9.6995 | 174.19 | 1689.58 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 60.29 | 0.0000 | Y | 19.12 |
SMSTORE6_LIGHTS_ALLOWANCE | SMSTORE6 | SMSTORE6 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE7_LIGHTS | SMSTORE7 | SMSTORE7 | GENERAL | 9.6995 | 174.19 | 1689.58 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 60.29 | 0.0000 | Y | 19.12 |
SMSTORE7_LIGHTS_ALLOWANCE | SMSTORE7 | SMSTORE7 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE8_LIGHTS | SMSTORE8 | SMSTORE8 | GENERAL | 9.6995 | 174.19 | 1689.58 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 60.29 | 0.0000 | Y | 19.12 |
SMSTORE8_LIGHTS_ALLOWANCE | SMSTORE8 | SMSTORE8 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
Interior Lighting Total | 6.5342 | 4180.64 | 27316.92 | 366.68 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 455.59 | AstronomicalClock | - | 42.24 | 42.24 | 3.61 | |
EXTERIOR_LIGHTS_B | 2744.24 | AstronomicalClock | - | 83.63 | 62.93 | 32.42 | |
EXTERIOR_LIGHTS_C | 2307.23 | AstronomicalClock | - | 83.63 | 55.93 | 24.23 | |
Exterior Lighting Total | 5507.06 | 60.26 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:25
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 44494.47 | 32309.66 | 12184.81 | 0.73 | 3.73 | |||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 23588.56 | 17318.96 | 6269.60 | 0.73 | 3.80 | |||
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 23695.28 | 17406.79 | 6288.49 | 0.73 | 3.80 | |||
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 23757.00 | 17458.07 | 6298.93 | 0.73 | 3.80 | |||
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 23586.13 | 17315.29 | 6270.84 | 0.73 | 3.80 | |||
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 42688.27 | 30905.45 | 11782.82 | 0.72 | 3.73 | |||
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 21966.03 | 15920.10 | 6045.93 | 0.72 | 3.80 | |||
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 21854.31 | 15827.77 | 6026.54 | 0.72 | 3.80 | |||
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 21746.54 | 15716.66 | 6029.88 | 0.72 | 3.80 | |||
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 26235.97 | 19069.09 | 7166.88 | 0.73 | 3.80 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC_1:1 COOLING COIL | 42967.4 | 11.63 | 11.63 | ||||
PSZ-AC_2:2 COOLING COIL | 22760.9 | 11.76 | 11.76 | ||||
PSZ-AC_3:3 COOLING COIL | 22862.6 | 11.76 | 11.76 | ||||
PSZ-AC_4:4 COOLING COIL | 22921.4 | 11.76 | 11.76 | ||||
PSZ-AC_5:5 COOLING COIL | 22758.8 | 11.76 | 11.76 | ||||
PSZ-AC_6:6 COOLING COIL | 41235.0 | 11.64 | 11.64 | ||||
PSZ-AC_7:7 COOLING COIL | 21216.0 | 11.81 | 11.81 | ||||
PSZ-AC_8:8 COOLING COIL | 21109.6 | 11.82 | 11.82 | ||||
PSZ-AC_9:9 COOLING COIL | 21006.9 | 11.82 | 11.82 | ||||
PSZ-AC_10:10 COOLING COIL | 25333.3 | 11.80 | 11.80 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | 64741.21 | 0.80 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | 33633.97 | 0.80 | |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | 33714.65 | 0.80 | |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | 34375.17 | 0.80 | |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | 33522.34 | 0.80 | |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | 62691.16 | 0.80 | |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | 31817.90 | 0.80 | |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | 31665.50 | 0.80 | |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | 31449.28 | 0.80 | |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | 36225.34 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 1.94 | 2074.32 | 1070.05 | 1.00 | 1.32 | General | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.05 | 1163.80 | 1107.16 | 1.00 | 1.39 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 |
PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.06 | 1170.80 | 1107.16 | 1.00 | 1.39 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 |
PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.06 | 1174.93 | 1107.16 | 1.00 | 1.39 | General | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.05 | 1163.33 | 1107.16 | 1.00 | 1.39 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 |
PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 1.84 | 1973.81 | 1070.05 | 1.00 | 1.33 | General | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.95 | 1054.00 | 1107.16 | 1.00 | 1.41 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 |
PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.95 | 1046.55 | 1107.16 | 1.00 | 1.42 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 |
PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.94 | 1039.34 | 1107.16 | 1.00 | 1.42 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 |
PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.15 | 1268.78 | 1107.16 | 1.00 | 1.37 | General | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
GAS TANK1 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK2 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK3 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK4 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK5 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK6 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK7 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:25
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
LGSTORE1 | 20990.40 | 25188.48 | 72.30 | 1.615 | 1.939 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 23.89 | 23.88 | 0.01005 | 31.20 | 0.01537 | 0.411 | 0.00 |
SMSTORE1 | 11447.69 | 13737.23 | 78.86 | 0.856 | 1.027 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 23.89 | 23.89 | 0.00949 | 27.17 | 0.01536 | 0.206 | 0.00 |
SMSTORE2 | 11488.00 | 13785.60 | 79.14 | 0.859 | 1.031 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 23.89 | 23.88 | 0.00967 | 25.37 | 0.01535 | 0.206 | 0.00 |
SMSTORE3 | 11491.27 | 13789.53 | 79.16 | 0.884 | 1.061 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 23.89 | 23.88 | 0.00993 | 30.93 | 0.01536 | 0.206 | 0.00 |
SMSTORE4 | 11392.33 | 13670.80 | 78.48 | 0.852 | 1.022 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 23.89 | 23.88 | 0.00969 | 25.37 | 0.01535 | 0.206 | 0.00 |
LGSTORE2 | 19974.39 | 23969.26 | 68.80 | 1.537 | 1.845 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 23.89 | 23.88 | 0.01003 | 30.93 | 0.01536 | 0.411 | 0.00 |
SMSTORE5 | 10542.09 | 12650.50 | 72.62 | 0.787 | 0.944 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 23.89 | 23.88 | 0.00973 | 27.17 | 0.01536 | 0.206 | 0.00 |
SMSTORE6 | 10466.33 | 12559.60 | 72.10 | 0.781 | 0.937 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 23.89 | 23.88 | 0.00974 | 27.17 | 0.01536 | 0.206 | 0.00 |
SMSTORE7 | 10349.91 | 12419.89 | 71.30 | 0.772 | 0.926 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 23.89 | 23.88 | 0.00976 | 27.17 | 0.01536 | 0.206 | 0.00 |
SMSTORE8 | 10817.42 | 12980.90 | 74.52 | 0.808 | 0.969 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 23.89 | 23.88 | 0.00982 | 27.17 | 0.01536 | 0.206 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
LGSTORE1 | 34379.58 | 41255.50 | 118.42 | 1.553 | 1.864 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00661 | -26.20 | 0.00036 | 0.411 | 0.00 |
SMSTORE1 | 16223.47 | 19468.16 | 111.76 | 0.733 | 0.880 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00654 | -26.20 | 0.00036 | 0.206 | 0.00 |
SMSTORE2 | 16369.32 | 19643.19 | 112.77 | 0.740 | 0.888 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00655 | -26.20 | 0.00036 | 0.206 | 0.00 |
SMSTORE3 | 16427.36 | 19712.83 | 113.17 | 0.742 | 0.891 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00655 | -26.20 | 0.00036 | 0.206 | 0.00 |
SMSTORE4 | 16561.33 | 19873.60 | 114.09 | 0.748 | 0.898 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00656 | -26.20 | 0.00036 | 0.206 | 0.00 |
LGSTORE2 | 31538.17 | 37845.81 | 108.63 | 1.425 | 1.710 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00662 | -26.20 | 0.00036 | 0.411 | 0.00 |
SMSTORE5 | 16893.37 | 20272.04 | 116.38 | 0.763 | 0.916 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00658 | -26.20 | 0.00036 | 0.206 | 0.00 |
SMSTORE6 | 16878.59 | 20254.30 | 116.27 | 0.763 | 0.915 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00658 | -26.20 | 0.00036 | 0.206 | 0.00 |
SMSTORE7 | 17096.28 | 20515.54 | 117.77 | 0.773 | 0.927 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00659 | -26.20 | 0.00036 | 0.206 | 0.00 |
SMSTORE8 | 21135.46 | 25362.55 | 145.60 | 0.955 | 1.146 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00664 | -26.20 | 0.00036 | 0.206 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC_1:1 | 1.94 | 1.94 | 1.86 | 1.86 | 1.9385 | 1.9385 | 1.9385 | 1.0000 | 1.0000 |
PSZ-AC_2:2 | 1.05 | 1.05 | 0.88 | 0.88 | 1.0512 | 1.0272 | 1.0512 | 0.9772 | 1.0000 |
PSZ-AC_3:3 | 1.06 | 1.06 | 0.89 | 0.89 | 1.0575 | 1.0309 | 1.0575 | 0.9749 | 1.0000 |
PSZ-AC_4:4 | 1.06 | 1.06 | 0.89 | 0.89 | 1.0612 | 1.0612 | 1.0612 | 1.0000 | 1.0000 |
PSZ-AC_5:5 | 1.05 | 1.05 | 0.90 | 0.90 | 1.0507 | 1.0221 | 1.0507 | 0.9727 | 1.0000 |
PSZ-AC_6:6 | 1.84 | 1.84 | 1.71 | 1.71 | 1.8446 | 1.8446 | 1.8446 | 1.0000 | 1.0000 |
PSZ-AC_7:7 | 0.95 | 0.95 | 0.92 | 0.92 | 0.9520 | 0.9439 | 0.9520 | 0.9916 | 1.0000 |
PSZ-AC_8:8 | 0.95 | 0.95 | 0.92 | 0.92 | 0.9453 | 0.9370 | 0.9453 | 0.9912 | 1.0000 |
PSZ-AC_9:9 | 0.94 | 0.94 | 0.93 | 0.93 | 0.9387 | 0.9270 | 0.9387 | 0.9875 | 1.0000 |
PSZ-AC_10:10 | 1.00 | 1.00 | 1.15 | 1.15 | 1.1460 | 1.1460 | 1.1460 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 44494.470 | 32309.659 | 1.938530 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 22247.24 | 15527.56 | 1.292353 | 26.35 | 18.83 | 0.01117789 | 12.80 | 11.68 | 0.00850000 | 31.20 | 0.01536508 | 23.13 | 31.8395 | 23.88 | 0.01004961 | 51.8326 | 20990.40 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_1:1 | 64741.213 | 64741.213 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 64741.21 | 64741.21 | 1.938535 | 11.06 | 7.49 | 0.00528062 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 21.2263 | 21.10 | 0.00660616 | 40.5701 | 34379.58 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 23588.560 | 17318.957 | 1.051160 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 11794.28 | 8381.13 | 0.700773 | 26.26 | 18.67 | 0.01100580 | 12.80 | 11.68 | 0.00850000 | 31.20 | 0.01536508 | 23.13 | 29.3589 | 23.88 | 0.00994412 | 51.2964 | 11375.08 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_2:2 | 33633.966 | 33633.966 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 33633.97 | 33633.97 | 1.051160 | 11.85 | 7.91 | 0.00532863 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 19.5726 | 21.10 | 0.00653746 | 40.1518 | 16223.47 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_3:3 | 23695.280 | 17406.790 | 1.057480 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 11847.64 | 8428.63 | 0.704987 | 26.25 | 18.66 | 0.01099472 | 12.80 | 11.68 | 0.00850000 | 31.20 | 0.01536508 | 23.13 | 29.1834 | 23.88 | 0.00993747 | 51.2626 | 11436.85 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_3:3 | 33714.653 | 33714.653 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 33714.65 | 33714.65 | 1.057478 | 11.90 | 7.95 | 0.00534363 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 19.4557 | 21.10 | 0.00654712 | 40.2105 | 16369.32 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_4:4 | 23757.000 | 17458.069 | 1.061210 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 11878.50 | 8456.58 | 0.707473 | 26.24 | 18.65 | 0.01098782 | 12.80 | 11.68 | 0.00850000 | 31.20 | 0.01536508 | 23.13 | 29.0809 | 23.88 | 0.00993333 | 51.2416 | 11475.49 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_4:4 | 34375.174 | 34375.174 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 34375.17 | 34375.17 | 1.061209 | 11.93 | 7.98 | 0.00535092 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 19.3873 | 21.10 | 0.00655091 | 40.2336 | 16427.36 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_5:5 | 23586.130 | 17315.286 | 1.050740 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 11793.07 | 8378.34 | 0.700493 | 26.26 | 18.67 | 0.01100805 | 12.80 | 11.68 | 0.00850000 | 31.20 | 0.01536508 | 23.13 | 29.3706 | 23.88 | 0.00994548 | 51.3033 | 11362.83 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_5:5 | 33522.343 | 33522.343 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 33522.34 | 33522.34 | 1.050738 | 11.84 | 7.93 | 0.00534600 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 19.5805 | 21.10 | 0.00655966 | 40.2868 | 16561.33 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_6:6 | 42688.270 | 30905.454 | 1.844600 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 21344.13 | 14836.99 | 1.229733 | 26.43 | 18.89 | 0.01122807 | 12.80 | 11.68 | 0.00850000 | 31.20 | 0.01536508 | 23.13 | 33.4608 | 23.88 | 0.01003800 | 51.7727 | 19944.61 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_6:6 | 62691.162 | 62691.162 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 62691.16 | 62691.16 | 1.844598 | 10.55 | 7.19 | 0.00522626 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 22.3072 | 21.10 | 0.00662309 | 40.6710 | 31538.17 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_7:7 | 21966.030 | 15920.100 | 0.951990 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 10983.01 | 7640.46 | 0.634660 | 26.41 | 18.88 | 0.01121792 | 12.80 | 11.68 | 0.00850000 | 31.20 | 0.01536508 | 23.13 | 32.4173 | 23.88 | 0.01007221 | 51.9465 | 10291.84 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_7:7 | 31817.903 | 31817.903 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 31817.90 | 31817.90 | 0.951989 | 10.88 | 7.35 | 0.00523674 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 21.6115 | 21.10 | 0.00658087 | 40.4156 | 16893.37 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_8:8 | 21854.310 | 15827.765 | 0.945260 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 10927.16 | 7590.12 | 0.630173 | 26.42 | 18.89 | 0.01123337 | 12.80 | 11.68 | 0.00850000 | 31.20 | 0.01536508 | 23.13 | 32.6481 | 23.88 | 0.01008158 | 51.9941 | 10219.40 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_8:8 | 31665.498 | 31665.498 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 31665.50 | 31665.50 | 0.945258 | 10.81 | 7.31 | 0.00522644 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 21.7654 | 21.10 | 0.00657995 | 40.4100 | 16878.59 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_9:9 | 21746.540 | 15716.659 | 0.938740 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 10873.27 | 7541.43 | 0.625827 | 26.43 | 18.91 | 0.01124868 | 12.80 | 11.68 | 0.00850000 | 31.20 | 0.01536508 | 23.13 | 32.8748 | 23.88 | 0.01009088 | 52.0413 | 10148.40 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_9:9 | 31449.285 | 31449.285 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 31449.28 | 31449.28 | 0.938741 | 10.74 | 7.28 | 0.00522760 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 21.9165 | 21.10 | 0.00659346 | 40.4922 | 17096.28 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_10:10 | 26235.970 | 19069.090 | 1.145980 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:10:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | 13117.99 | 9086.03 | 0.763987 | 26.25 | 18.84 | 0.01122840 | 12.80 | 11.68 | 0.00850000 | 30.76 | 0.01536427 | 23.01 | 26.9297 | 23.88 | 0.01015051 | 52.3453 | 10757.90 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_10:10 | 36225.339 | 36225.339 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 36225.34 | 36225.34 | 1.145975 | 12.61 | 8.46 | 0.00551141 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 17.9532 | 21.10 | 0.00663833 | 40.7683 | 21135.46 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:37:25
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 44494.470 | 32309.659 | 1.938530 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1025.6191 | 1004.8586 | 1.1486 | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.938535 | 2.22651520 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | Sensible | 22247.24 | 15527.56 | 1.0000 | 1.48433995 | 1.292353 | 26.35 | 18.83 | 0.01117789 | 54975.6 | 12.80 | 11.68 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 22247.24 | 31.20 | 0.01536508 | 23.13 | 0.41147883 | 31.8395 | 23.88 | 0.01004961 | 23.88 | 0.01004961 | 51.8326 | 20990.40 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 64741.213 | 64741.213 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.938535 | 2.22651520 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 64741.21 | 64741.21 | 1.0000 | 2.22651520 | 1.938535 | 11.06 | 7.49 | 0.00528062 | 24431.9 | 40.00 | 20.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 64741.21 | -26.20 | 0.00036134 | -26.20 | 0.41147883 | 21.2263 | 21.10 | 0.00660616 | 21.10 | 0.00660616 | 40.5701 | 34379.58 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 23588.560 | 17318.957 | 1.051160 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1025.2992 | 1004.8586 | 1.1486 | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.051160 | 1.20731588 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | Sensible | 11794.28 | 8381.13 | 1.0000 | 0.80487730 | 0.700773 | 26.26 | 18.67 | 0.01100580 | 54446.5 | 12.80 | 11.68 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11794.28 | 31.20 | 0.01536508 | 23.13 | 0.20573941 | 29.3589 | 23.88 | 0.00994412 | 23.88 | 0.00994412 | 51.2964 | 11375.08 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 33633.966 | 33633.966 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.051160 | 1.20731588 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 33633.97 | 33633.97 | 1.0000 | 1.20731588 | 1.051160 | 11.85 | 7.91 | 0.00532863 | 25347.2 | 40.00 | 20.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 33633.97 | -26.20 | 0.00036134 | -26.20 | 0.20573941 | 19.5726 | 21.10 | 0.00653746 | 21.10 | 0.00653746 | 40.1518 | 16223.47 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 23695.280 | 17406.790 | 1.057480 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1025.2786 | 1004.8586 | 1.1486 | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.057478 | 1.21457210 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | Sensible | 11847.64 | 8428.63 | 1.0000 | 0.80971654 | 0.704987 | 26.25 | 18.66 | 0.01099472 | 54410.3 | 12.80 | 11.68 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11847.64 | 31.20 | 0.01536508 | 23.13 | 0.20573941 | 29.1834 | 23.88 | 0.00993747 | 23.88 | 0.00993747 | 51.2626 | 11436.85 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 33714.653 | 33714.653 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.057478 | 1.21457210 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 33714.65 | 33714.65 | 1.0000 | 1.21457210 | 1.057478 | 11.90 | 7.95 | 0.00534363 | 25441.1 | 40.00 | 20.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 33714.65 | -26.20 | 0.00036134 | -26.20 | 0.20573941 | 19.4557 | 21.10 | 0.00654712 | 21.10 | 0.00654712 | 40.2105 | 16369.32 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 23757.000 | 17458.069 | 1.061210 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1025.2658 | 1004.8586 | 1.1486 | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.061209 | 1.21885742 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | Sensible | 11878.50 | 8456.58 | 1.0000 | 0.81257262 | 0.707473 | 26.24 | 18.65 | 0.01098782 | 54387.8 | 12.80 | 11.68 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11878.50 | 31.20 | 0.01536508 | 23.13 | 0.20573941 | 29.0809 | 23.88 | 0.00993333 | 23.88 | 0.00993333 | 51.2416 | 11475.49 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 34375.174 | 34375.174 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.061209 | 1.21885742 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 34375.17 | 34375.17 | 1.0000 | 1.21885742 | 1.061209 | 11.93 | 7.98 | 0.00535092 | 25492.4 | 40.00 | 20.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 34375.17 | -26.20 | 0.00036134 | -26.20 | 0.20573941 | 19.3873 | 21.10 | 0.00655091 | 21.10 | 0.00655091 | 40.2336 | 16427.36 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 23586.130 | 17315.286 | 1.050740 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1025.3034 | 1004.8586 | 1.1486 | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.050738 | 1.20683152 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | Sensible | 11793.07 | 8378.34 | 1.0000 | 0.80455570 | 0.700493 | 26.26 | 18.67 | 0.01100805 | 54453.8 | 12.80 | 11.68 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11793.07 | 31.20 | 0.01536508 | 23.13 | 0.20573941 | 29.3706 | 23.88 | 0.00994548 | 23.88 | 0.00994548 | 51.3033 | 11362.83 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 33522.343 | 33522.343 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.050738 | 1.20683152 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 33522.34 | 33522.34 | 1.0000 | 1.20683152 | 1.050738 | 11.84 | 7.93 | 0.00534600 | 25387.2 | 40.00 | 20.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 33522.34 | -26.20 | 0.00036134 | -26.20 | 0.20573941 | 19.5805 | 21.10 | 0.00655966 | 21.10 | 0.00655966 | 40.2868 | 16561.33 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 42688.270 | 30905.454 | 1.844600 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1025.7124 | 1004.8586 | 1.1486 | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.844598 | 2.11862333 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | Sensible | 21344.13 | 14836.99 | 1.0000 | 1.41241739 | 1.229733 | 26.43 | 18.89 | 0.01122807 | 55187.3 | 12.80 | 11.68 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 21344.13 | 31.20 | 0.01536508 | 23.13 | 0.41147883 | 33.4608 | 23.88 | 0.01003800 | 23.88 | 0.01003800 | 51.7727 | 19944.61 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 62691.162 | 62691.162 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.844598 | 2.11862333 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 62691.16 | 62691.16 | 1.0000 | 2.11862333 | 1.844598 | 10.55 | 7.19 | 0.00522626 | 23776.7 | 40.00 | 20.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 62691.16 | -26.20 | 0.00036134 | -26.20 | 0.41147883 | 22.3072 | 21.10 | 0.00662309 | 21.10 | 0.00662309 | 40.6710 | 31538.17 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 21966.030 | 15920.100 | 0.951990 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1025.6935 | 1004.8586 | 1.1486 | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.951989 | 1.09341220 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | Sensible | 10983.01 | 7640.46 | 1.0000 | 0.72894244 | 0.634660 | 26.41 | 18.88 | 0.01121792 | 55141.6 | 12.80 | 11.68 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10983.01 | 31.20 | 0.01536508 | 23.13 | 0.20573941 | 32.4173 | 23.88 | 0.01007221 | 23.88 | 0.01007221 | 51.9465 | 10291.84 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 31817.903 | 31817.903 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.951989 | 1.09341220 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 31817.90 | 31817.90 | 1.0000 | 1.09341220 | 0.951989 | 10.88 | 7.35 | 0.00523674 | 24136.8 | 40.00 | 20.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 31817.90 | -26.20 | 0.00036134 | -26.20 | 0.20573941 | 21.6115 | 21.10 | 0.00658087 | 21.10 | 0.00658087 | 40.4156 | 16893.37 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 21854.310 | 15827.765 | 0.945260 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1025.7223 | 1004.8586 | 1.1486 | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.945258 | 1.08568130 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | Sensible | 10927.16 | 7590.12 | 1.0000 | 0.72378925 | 0.630173 | 26.42 | 18.89 | 0.01123337 | 55192.5 | 12.80 | 11.68 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10927.16 | 31.20 | 0.01536508 | 23.13 | 0.20573941 | 32.6481 | 23.88 | 0.01008158 | 23.88 | 0.01008158 | 51.9941 | 10219.40 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 31665.498 | 31665.498 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.945258 | 1.08568130 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 31665.50 | 31665.50 | 1.0000 | 1.08568130 | 0.945258 | 10.81 | 7.31 | 0.00522644 | 24037.0 | 40.00 | 20.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 31665.50 | -26.20 | 0.00036134 | -26.20 | 0.20573941 | 21.7654 | 21.10 | 0.00657995 | 21.10 | 0.00657995 | 40.4100 | 16878.59 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 21746.540 | 15716.659 | 0.938740 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1025.7507 | 1004.8586 | 1.1486 | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.938741 | 1.07819639 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | Sensible | 10873.27 | 7541.43 | 1.0000 | 0.71879687 | 0.625827 | 26.43 | 18.91 | 0.01124868 | 55243.0 | 12.80 | 11.68 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10873.27 | 31.20 | 0.01536508 | 23.13 | 0.20573941 | 32.8748 | 23.88 | 0.01009088 | 23.88 | 0.01009088 | 52.0413 | 10148.40 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 31449.285 | 31449.285 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.938741 | 1.07819639 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 31449.28 | 31449.28 | 1.0000 | 1.07819639 | 0.938741 | 10.74 | 7.28 | 0.00522760 | 23967.4 | 40.00 | 20.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 31449.28 | -26.20 | 0.00036134 | -26.20 | 0.20573941 | 21.9165 | 21.10 | 0.00659346 | 21.10 | 0.00659346 | 40.4922 | 17096.28 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 26235.970 | 19069.090 | 1.145980 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1025.7130 | 1004.8586 | 1.1486 | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.145975 | 1.31621645 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:10:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | Sensible | 13117.99 | 9086.03 | 1.0000 | 0.87748134 | 0.763987 | 26.25 | 18.84 | 0.01122840 | 55002.0 | 12.80 | 11.68 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 13117.99 | 30.76 | 0.01536427 | 23.01 | 0.20573941 | 26.9297 | 23.88 | 0.01015051 | 23.88 | 0.01015051 | 52.3453 | 10757.90 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 36225.339 | 36225.339 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.145975 | 1.31621645 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 36225.34 | 36225.34 | 1.0000 | 1.31621645 | 1.145975 | 12.61 | 8.46 | 0.00551141 | 26584.7 | 40.00 | 20.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 36225.34 | -26.20 | 0.00036134 | -26.20 | 0.20573941 | 17.9532 | 21.10 | 0.00663833 | 21.10 | 0.00663833 | 40.7683 | 21135.46 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:25
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-AC_1:1_OA_CONTROLLER | DifferentialDryBulb | 0.41 | 1.94 | - | |||
PSZ-AC_2:2_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.05 | - | |||
PSZ-AC_3:3_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.06 | - | |||
PSZ-AC_4:4_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.06 | - | |||
PSZ-AC_5:5_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.05 | - | |||
PSZ-AC_6:6_OA_CONTROLLER | DifferentialDryBulb | 0.41 | 1.84 | - | |||
PSZ-AC_7:7_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 0.95 | - | |||
PSZ-AC_8:8_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 0.95 | - | |||
PSZ-AC_9:9_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 0.94 | - | |||
PSZ-AC_10:10_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.15 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
LGSTORE1 | 3746.00 | 4316.83 | 2528.50 |
SMSTORE1 | 3107.17 | 3937.17 | 1671.17 |
SMSTORE2 | 2649.33 | 3126.83 | 1610.83 |
SMSTORE3 | 2697.33 | 3151.50 | 1674.17 |
SMSTORE4 | 2733.00 | 3200.17 | 1750.00 |
LGSTORE2 | 2588.00 | 3019.50 | 1781.00 |
SMSTORE5 | 2548.83 | 3053.00 | 1791.50 |
SMSTORE6 | 2552.50 | 3075.17 | 1816.33 |
SMSTORE7 | 2606.67 | 3117.50 | 1906.67 |
SMSTORE8 | 2777.17 | 3193.33 | 2142.00 |
Facility | 4355.50 | 4698.00 | 3092.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
LGSTORE1 | 24.83 | 0.00 | 7.83 | 0.00 |
SMSTORE1 | 8.00 | 0.00 | 2.83 | 0.00 |
SMSTORE2 | 5.17 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 5.83 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 7.50 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 13.33 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 12.83 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 13.33 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 18.00 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 106.17 | 0.00 | 0.00 | 0.00 |
Facility | 127.67 | 0.00 | 7.83 | 0.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:25
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
LGSTORE1 | 16.93 | 56.25 | 1805.20 | 0.976 | 0.244 | 0.000 | 0.000 |
SMSTORE1 | 8.46 | 28.12 | 902.60 | 0.836 | 0.255 | 0.000 | 0.000 |
SMSTORE2 | 7.08 | 28.12 | 902.60 | 1.020 | 0.331 | 0.000 | 0.000 |
SMSTORE3 | 7.08 | 28.12 | 902.60 | 1.018 | 0.331 | 0.000 | 0.000 |
SMSTORE4 | 7.08 | 28.12 | 902.60 | 1.008 | 0.331 | 0.000 | 0.000 |
LGSTORE2 | 24.78 | 56.25 | 1805.20 | 0.973 | 0.319 | 0.000 | 0.000 |
SMSTORE5 | 12.39 | 28.12 | 902.60 | 0.978 | 0.353 | 0.000 | 0.000 |
SMSTORE6 | 12.39 | 28.12 | 902.60 | 0.974 | 0.353 | 0.000 | 0.000 |
SMSTORE7 | 12.39 | 28.12 | 902.60 | 0.966 | 0.353 | 0.000 | 0.000 |
SMSTORE8 | 12.39 | 28.12 | 902.60 | 0.994 | 0.381 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
LGSTORE1 | 16.93 | 56.25 | 1805.20 | 0.000 | 0.000 | 0.000 | 0.000 |
SMSTORE1 | 8.46 | 28.12 | 902.60 | 0.000 | 0.000 | 0.000 | 0.000 |
SMSTORE2 | 7.08 | 28.12 | 902.60 | 0.807 | 0.000 | 0.000 | 0.000 |
SMSTORE3 | 7.08 | 28.12 | 902.60 | 0.807 | 0.000 | 0.000 | 0.000 |
SMSTORE4 | 7.08 | 28.12 | 902.60 | 0.807 | 0.000 | 0.000 | 0.000 |
LGSTORE2 | 24.78 | 56.25 | 1805.20 | 0.807 | 0.000 | 0.000 | 0.000 |
SMSTORE5 | 12.39 | 28.12 | 902.60 | 0.807 | 0.000 | 0.000 | 0.000 |
SMSTORE6 | 12.39 | 28.12 | 902.60 | 0.807 | 0.000 | 0.000 | 0.000 |
SMSTORE7 | 12.39 | 28.12 | 902.60 | 0.807 | 0.000 | 0.000 | 0.000 |
SMSTORE8 | 12.39 | 28.12 | 902.60 | 0.807 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:37:25
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
LGSTORE1 | PSZ-AC_1:1 | 16.93 | 56.25 | 1805.20 | 348.39 | 0.4115 | 0.411 |
SMSTORE1 | PSZ-AC_2:2 | 8.46 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE2 | PSZ-AC_3:3 | 7.08 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE3 | PSZ-AC_4:4 | 7.08 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE4 | PSZ-AC_5:5 | 7.08 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
LGSTORE2 | PSZ-AC_6:6 | 24.78 | 56.25 | 1805.20 | 348.39 | 0.4115 | 0.411 |
SMSTORE5 | PSZ-AC_7:7 | 12.39 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE6 | PSZ-AC_8:8 | 12.39 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE7 | PSZ-AC_9:9 | 12.39 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE8 | PSZ-AC_10:10 | 12.39 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
Total Facility | 120.98 | 337.50 | 10831.20 | 2090.32 | 2.4689 | 2.469 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
LGSTORE1 | 10146243.94 | 0.00 | 10146243.94 | 3107580.01 | 13253823.95 | 12976396.34 | 3152.02 | 4510.92 | 1097.07 | 21.44 |
SMSTORE1 | 4346298.69 | 0.00 | 4346298.69 | 1491508.06 | 5837806.76 | 6488198.17 | 4367.72 | 3279.12 | 1113.15 | 23.78 |
SMSTORE2 | 4046402.60 | 0.00 | 4046402.60 | 1541822.49 | 5588225.08 | 6488198.17 | 4329.47 | 3643.58 | 786.95 | 86.84 |
SMSTORE3 | 4037824.83 | 0.00 | 4037824.83 | 1541822.49 | 5579647.32 | 6488198.17 | 4329.97 | 3661.67 | 768.37 | 85.18 |
SMSTORE4 | 3992273.79 | 0.00 | 3992273.79 | 1541822.49 | 5534096.28 | 6488198.17 | 4333.02 | 3701.58 | 725.40 | 82.92 |
LGSTORE2 | 7069925.22 | 0.00 | 7069925.22 | 2859306.10 | 9929231.32 | 12976396.34 | 4700.04 | 3410.00 | 649.96 | 75.38 |
SMSTORE5 | 3555614.38 | 0.00 | 3555614.38 | 1557761.16 | 5113375.54 | 6488198.17 | 4699.59 | 3418.50 | 641.91 | 75.58 |
SMSTORE6 | 3537668.88 | 0.00 | 3537668.88 | 1557761.16 | 5095430.04 | 6488198.17 | 4701.01 | 3430.75 | 628.24 | 73.08 |
SMSTORE7 | 3498641.97 | 0.00 | 3498641.97 | 1557761.16 | 5056403.14 | 6488198.17 | 4706.76 | 3459.64 | 593.60 | 65.58 |
SMSTORE8 | 3591530.18 | 0.00 | 3591530.18 | 2037920.93 | 5629451.11 | 6488198.17 | 4713.72 | 3503.50 | 542.78 | 42.72 |
Total Facility | 47822424.48 | 0.00 | 47822424.48 | 18795066.06 | 66617490.54 | 77858378.04 | 4715.42 | 4975.01 | 1338.49 | 178.49 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
LGSTORE1 | 0.4812 | 0.0000 | 0.4812 | 0.1205 | 0.6018 | 0.4115 | 238.88 | 4510.75 | 1090.37 |
SMSTORE1 | 0.2057 | 0.0000 | 0.2057 | 0.0630 | 0.2687 | 0.2057 | 1460.42 | 3278.79 | 1100.79 |
SMSTORE2 | 0.2514 | 0.0000 | 0.2514 | 0.0819 | 0.3332 | 0.2057 | 0.00 | 3643.42 | 751.58 |
SMSTORE3 | 0.2509 | 0.0000 | 0.2509 | 0.0819 | 0.3327 | 0.2057 | 0.00 | 3661.50 | 733.50 |
SMSTORE4 | 0.2484 | 0.0000 | 0.2484 | 0.0819 | 0.3302 | 0.2057 | 0.00 | 3701.17 | 693.83 |
LGSTORE2 | 0.4796 | 0.0000 | 0.4796 | 0.1573 | 0.6369 | 0.4115 | 0.00 | 3409.33 | 620.67 |
SMSTORE5 | 0.2412 | 0.0000 | 0.2412 | 0.0872 | 0.3284 | 0.2057 | 0.00 | 3417.58 | 612.42 |
SMSTORE6 | 0.2401 | 0.0000 | 0.2401 | 0.0872 | 0.3273 | 0.2057 | 0.00 | 3430.17 | 599.83 |
SMSTORE7 | 0.2380 | 0.0000 | 0.2380 | 0.0872 | 0.3252 | 0.2057 | 0.00 | 3459.42 | 570.58 |
SMSTORE8 | 0.2451 | 0.0000 | 0.2451 | 0.0942 | 0.3393 | 0.2057 | 0.00 | 3503.17 | 526.83 |
Total Facility | 2.8816 | 0.0000 | 2.8816 | 0.9422 | 3.8237 | 2.4689 | 1565.51 | 4972.04 | 1309.57 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-AC_1:1 | 13385107.89 | 0.00 | 13385107.89 | 12976396.34 | 3145.52 | 0.17 | 5614.32 | 21.44 |
PSZ-AC_2:2 | 5733676.89 | 0.00 | 5733676.89 | 6488198.17 | 4319.07 | 3.33 | 4437.60 | 23.78 |
PSZ-AC_3:3 | 5338077.58 | 0.00 | 5338077.58 | 6488198.17 | 4317.60 | 1.00 | 4441.40 | 86.68 |
PSZ-AC_4:4 | 5326761.51 | 0.00 | 5326761.51 | 6488198.17 | 4318.43 | 0.67 | 4440.90 | 85.18 |
PSZ-AC_5:5 | 5266666.30 | 0.00 | 5266666.30 | 6488198.17 | 4323.27 | 0.83 | 4435.90 | 82.92 |
PSZ-AC_6:6 | 9326790.98 | 0.00 | 9326790.98 | 12976396.34 | 4691.04 | 0.83 | 4068.13 | 75.38 |
PSZ-AC_7:7 | 4690624.54 | 0.00 | 4690624.54 | 6488198.17 | 4690.92 | 0.83 | 4068.24 | 75.33 |
PSZ-AC_8:8 | 4666946.48 | 0.00 | 4666946.48 | 6488198.17 | 4694.01 | 0.83 | 4065.16 | 72.99 |
PSZ-AC_9:9 | 4615444.09 | 0.00 | 4615444.09 | 6488198.17 | 4700.96 | 0.00 | 4059.04 | 65.33 |
PSZ-AC_10:10 | 4737916.13 | 0.00 | 4737916.13 | 6488198.17 | 4710.25 | 0.39 | 4049.36 | 42.55 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-AC_1:1 | 0.6348 | 0.0000 | 0.6348 | 0.4115 | 234.96 | 0.17 | 5604.87 |
PSZ-AC_2:2 | 0.2714 | 0.0000 | 0.2714 | 0.2057 | 1413.35 | 3.17 | 4423.48 |
PSZ-AC_3:3 | 0.3316 | 0.0000 | 0.3316 | 0.2057 | 0.00 | 0.00 | 4395.00 |
PSZ-AC_4:4 | 0.3310 | 0.0000 | 0.3310 | 0.2057 | 0.00 | 0.00 | 4395.00 |
PSZ-AC_5:5 | 0.3277 | 0.0000 | 0.3277 | 0.2057 | 0.00 | 0.00 | 4395.00 |
PSZ-AC_6:6 | 0.6327 | 0.0000 | 0.6327 | 0.4115 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_7:7 | 0.3181 | 0.0000 | 0.3181 | 0.2057 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_8:8 | 0.3168 | 0.0000 | 0.3168 | 0.2057 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_9:9 | 0.3140 | 0.0000 | 0.3140 | 0.2057 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_10:10 | 0.3234 | 0.0000 | 0.3234 | 0.2057 | 0.00 | 0.00 | 4030.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-AC_1:1 | 0.00 | 5269.65 | 386.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_2:2 | 0.00 | 4296.21 | 671.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_3:3 | 0.00 | 4183.62 | 298.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_4:4 | 0.00 | 4195.95 | 284.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_5:5 | 0.00 | 4216.83 | 261.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_6:6 | 0.00 | 3894.24 | 211.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_7:7 | 0.00 | 3889.60 | 215.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_8:8 | 0.00 | 3892.47 | 210.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_9:9 | 0.00 | 3894.49 | 200.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_10:10 | 0.00 | 3864.93 | 207.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-AC_1:1 | 0.0000 | 0.6470 | 0.8167 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_2:2 | 0.0000 | 0.3176 | 0.3403 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_3:3 | 0.0000 | 0.3247 | 0.4625 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_4:4 | 0.0000 | 0.3242 | 0.4675 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_5:5 | 0.0000 | 0.3214 | 0.4700 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_6:6 | 0.0000 | 0.6232 | 0.8834 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_7:7 | 0.0000 | 0.3128 | 0.4529 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_8:8 | 0.0000 | 0.3115 | 0.4552 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_9:9 | 0.0000 | 0.3088 | 0.4539 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_10:10 | 0.0000 | 0.3154 | 0.5046 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:25
Surfaces by ClassTotal | Outdoors | |
Wall | 40 | 22 |
Floor | 10 | 10 |
Roof | 10 | 10 |
Internal Mass | 10 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 36 | 36 |
Door | 12 | 12 |
Glass Door | 12 | 12 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 10 |
Conditioned Zones | 10 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 830 |
Defaulted Fields | 823 |
Fields with Defaults | 2682 |
Autosized Fields | 184 |
Autosizable Fields | 458 |
Autocalculated Fields | 128 |
Autocalculatable Fields | 256 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:37:25
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 802.19 | 2102.83 | 15-JAN-07:50 | 96994.64 | 04-AUG-15:10 |
Electricity:Building | 494.83 | 891.83 | 01-JAN-00:20 | 31518.67 | 01-JAN-11:10 |
Electricity:Zone:LGSTORE1 | 113.36 | 148.64 | 01-JAN-00:20 | 5964.88 | 01-JAN-10:10 |
Electricity:SpaceType:GENERAL | 494.83 | 891.83 | 01-JAN-00:20 | 31518.67 | 01-JAN-11:10 |
InteriorLights:Electricity | 366.68 | 450.00 | 01-JAN-00:20 | 23459.17 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:LGSTORE1 | 87.12 | 75.00 | 01-JAN-00:20 | 4621.63 | 01-JAN-10:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 366.68 | 450.00 | 01-JAN-00:20 | 23459.17 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity | 366.68 | 450.00 | 01-JAN-00:20 | 23459.17 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:LGSTORE1 | 87.12 | 75.00 | 01-JAN-00:20 | 4621.63 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 366.68 | 450.00 | 01-JAN-00:20 | 23459.17 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE1 | 66.33 | 74.32 | 01-JAN-00:20 | 3498.69 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE1 | 53.20 | 37.50 | 01-JAN-00:20 | 2827.07 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE1 | 53.20 | 37.50 | 01-JAN-00:20 | 2827.07 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE2 | 47.99 | 74.32 | 01-JAN-00:10 | 3226.84 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE2 | 37.57 | 37.50 | 01-JAN-00:10 | 2555.22 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE2 | 37.57 | 37.50 | 01-JAN-00:10 | 2555.22 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE3 | 47.99 | 74.32 | 01-JAN-00:10 | 3226.84 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE3 | 37.57 | 37.50 | 01-JAN-00:10 | 2555.22 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE3 | 37.57 | 37.50 | 01-JAN-00:10 | 2555.22 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE4 | 47.99 | 74.32 | 01-JAN-00:10 | 3226.84 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE4 | 37.57 | 37.50 | 01-JAN-00:10 | 2555.22 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE4 | 37.57 | 37.50 | 01-JAN-00:10 | 2555.22 | 01-JAN-10:10 |
Electricity:Zone:LGSTORE2 | 56.34 | 148.64 | 01-JAN-00:10 | 4070.21 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:LGSTORE2 | 37.16 | 75.00 | 01-JAN-00:10 | 2726.96 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:LGSTORE2 | 37.16 | 75.00 | 01-JAN-00:10 | 2726.96 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE5 | 28.71 | 74.32 | 01-JAN-00:10 | 2076.09 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE5 | 19.12 | 37.50 | 01-JAN-00:10 | 1404.46 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE5 | 19.12 | 37.50 | 01-JAN-00:10 | 1404.46 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE6 | 28.71 | 74.32 | 01-JAN-00:10 | 2076.09 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE6 | 19.12 | 37.50 | 01-JAN-00:10 | 1404.46 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE6 | 19.12 | 37.50 | 01-JAN-00:10 | 1404.46 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE7 | 28.71 | 74.32 | 01-JAN-00:10 | 2076.09 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE7 | 19.12 | 37.50 | 01-JAN-00:10 | 1404.46 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE7 | 19.12 | 37.50 | 01-JAN-00:10 | 1404.46 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE8 | 28.71 | 74.32 | 01-JAN-00:10 | 2076.09 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE8 | 19.12 | 37.50 | 01-JAN-00:10 | 1404.46 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE8 | 19.12 | 37.50 | 01-JAN-00:10 | 1404.46 | 01-JAN-11:10 |
InteriorEquipment:Electricity | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:LGSTORE1 | 26.25 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-10:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LGSTORE1 | 26.25 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE1 | 13.12 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE1 | 13.12 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE2 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE2 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE3 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE3 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE4 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE4 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:LGSTORE2 | 19.17 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LGSTORE2 | 19.17 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE5 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE5 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE6 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE6 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE7 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE7 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE8 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE8 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
ElectricityPurchased:Facility | 802.19 | 2102.83 | 15-JAN-07:50 | 96994.64 | 04-AUG-15:10 |
ElectricityPurchased:Plant | 802.19 | 2102.83 | 15-JAN-07:50 | 96994.64 | 04-AUG-15:10 |
Cogeneration:ElectricityPurchased | 802.19 | 2102.83 | 15-JAN-07:50 | 96994.64 | 04-AUG-15:10 |
General:Cogeneration:ElectricityPurchased | 802.19 | 2102.83 | 15-JAN-07:50 | 96994.64 | 04-AUG-15:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 802.19 | 2102.83 | 15-JAN-07:50 | 96994.64 | 04-AUG-15:10 |
ElectricityNet:Plant | 802.19 | 2102.83 | 15-JAN-07:50 | 96994.64 | 04-AUG-15:10 |
Cogeneration:ElectricityNet | 802.19 | 2102.83 | 15-JAN-07:50 | 96994.64 | 04-AUG-15:10 |
General:Cogeneration:ElectricityNet | 802.19 | 2102.83 | 15-JAN-07:50 | 96994.64 | 04-AUG-15:10 |
Electricity:HVAC | 180.98 | 0.00 | 01-JAN-00:10 | 59054.28 | 04-AUG-14:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 74.87 | 0.00 | 01-JAN-00:10 | 50556.08 | 04-AUG-14:10 |
General:Cooling:Electricity | 74.87 | 0.00 | 01-JAN-00:10 | 50556.08 | 04-AUG-14:10 |
Fans:Electricity | 106.11 | 0.00 | 01-JAN-00:10 | 10910.34 | 02-FEB-12:10 |
General:Fans:Electricity | 106.11 | 0.00 | 01-JAN-00:10 | 10910.34 | 02-FEB-12:10 |
ExteriorLights:Electricity | 60.26 | 0.00 | 01-JAN-08:00 | 5507.06 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 60.26 | 0.00 | 01-JAN-08:00 | 5507.06 | 01-JAN-06:10 |
Electricity:Plant | 66.12 | 1211.00 | 06-JAN-00:10 | 12806.99 | 07-JAN-13:00 |
WaterSystems:Electricity | 66.12 | 1211.00 | 06-JAN-00:10 | 12806.99 | 07-JAN-13:00 |
Water Heater:WaterSystems:Electricity | 66.12 | 1211.00 | 06-JAN-00:10 | 12806.99 | 07-JAN-13:00 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 968.19 | 0.00 | 01-JAN-00:10 | 353922.28 | 02-FEB-12:10 |
NaturalGas:HVAC | 968.19 | 0.00 | 01-JAN-00:10 | 353922.28 | 02-FEB-12:10 |
Heating:NaturalGas | 968.19 | 0.00 | 01-JAN-00:10 | 353922.28 | 02-FEB-12:10 |
General:Heating:NaturalGas | 968.19 | 0.00 | 01-JAN-00:10 | 353922.28 | 02-FEB-12:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water:Plant | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
WaterSystems:Water | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water Heater:WaterSystems:Water | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
MainsWater:Facility | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
MainsWater:Plant | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
WaterSystems:MainsWater | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water Heater:WaterSystems:MainsWater | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 1662.98 | 0.00 | 01-JAN-00:10 | 446927.69 | 02-FEB-08:10 |
EnergyTransfer:Building | 587.01 | 0.00 | 01-JAN-00:10 | 205129.04 | 02-FEB-08:10 |
EnergyTransfer:Zone:LGSTORE1 | 113.06 | 0.00 | 01-JAN-00:10 | 39983.13 | 02-FEB-08:10 |
Heating:EnergyTransfer | 305.00 | 0.00 | 01-JAN-00:10 | 205129.04 | 02-FEB-08:10 |
Heating:EnergyTransfer:Zone:LGSTORE1 | 50.16 | 0.00 | 01-JAN-00:10 | 39983.13 | 02-FEB-08:10 |
General:Heating:EnergyTransfer | 305.00 | 0.00 | 01-JAN-00:10 | 205129.04 | 02-FEB-08:10 |
General:Heating:EnergyTransfer:Zone:LGSTORE1 | 50.16 | 0.00 | 01-JAN-00:10 | 39983.13 | 02-FEB-08:10 |
Cooling:EnergyTransfer | 282.02 | 0.00 | 01-JAN-00:10 | 86110.26 | 04-AUG-15:00 |
Cooling:EnergyTransfer:Zone:LGSTORE1 | 62.90 | 0.00 | 01-JAN-00:10 | 20958.18 | 03-FEB-00:10 |
General:Cooling:EnergyTransfer | 282.02 | 0.00 | 01-JAN-00:10 | 86110.26 | 04-AUG-15:00 |
General:Cooling:EnergyTransfer:Zone:LGSTORE1 | 62.90 | 0.00 | 01-JAN-00:10 | 20958.18 | 03-FEB-00:10 |
EnergyTransfer:Zone:SMSTORE1 | 52.69 | 0.00 | 01-JAN-00:10 | 18729.40 | 02-FEB-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE1 | 17.01 | 0.00 | 01-JAN-00:10 | 18729.40 | 02-FEB-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE1 | 17.01 | 0.00 | 01-JAN-00:10 | 18729.40 | 02-FEB-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE1 | 35.68 | 0.00 | 01-JAN-00:10 | 8073.61 | 01-SEP-20:20 |
General:Cooling:EnergyTransfer:Zone:SMSTORE1 | 35.68 | 0.00 | 01-JAN-00:10 | 8073.61 | 01-SEP-20:20 |
EnergyTransfer:Zone:SMSTORE2 | 45.96 | 0.00 | 01-JAN-00:10 | 18050.75 | 10-DEC-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE2 | 19.77 | 0.00 | 01-JAN-00:10 | 18050.75 | 10-DEC-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE2 | 19.77 | 0.00 | 01-JAN-00:10 | 18050.75 | 10-DEC-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE2 | 26.18 | 0.00 | 01-JAN-00:10 | 7482.77 | 04-AUG-14:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE2 | 26.18 | 0.00 | 01-JAN-00:10 | 7482.77 | 04-AUG-14:00 |
EnergyTransfer:Zone:SMSTORE3 | 46.47 | 0.00 | 01-JAN-00:10 | 17667.05 | 05-FEB-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE3 | 20.96 | 0.00 | 01-JAN-00:10 | 17667.05 | 05-FEB-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE3 | 20.96 | 0.00 | 01-JAN-00:10 | 17667.05 | 05-FEB-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE3 | 25.51 | 0.00 | 01-JAN-00:10 | 7481.96 | 04-AUG-14:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE3 | 25.51 | 0.00 | 01-JAN-00:10 | 7481.96 | 04-AUG-14:00 |
EnergyTransfer:Zone:SMSTORE4 | 46.75 | 0.00 | 01-JAN-00:10 | 17822.93 | 05-FEB-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE4 | 22.90 | 0.00 | 01-JAN-00:10 | 17822.93 | 05-FEB-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE4 | 22.90 | 0.00 | 01-JAN-00:10 | 17822.93 | 05-FEB-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE4 | 23.85 | 0.00 | 01-JAN-00:10 | 7345.62 | 04-AUG-14:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE4 | 23.85 | 0.00 | 01-JAN-00:10 | 7345.62 | 04-AUG-14:00 |
EnergyTransfer:Zone:LGSTORE2 | 84.30 | 0.00 | 01-JAN-00:10 | 36032.99 | 02-FEB-08:10 |
Heating:EnergyTransfer:Zone:LGSTORE2 | 46.35 | 0.00 | 01-JAN-00:10 | 36032.99 | 02-FEB-08:10 |
General:Heating:EnergyTransfer:Zone:LGSTORE2 | 46.35 | 0.00 | 01-JAN-00:10 | 36032.99 | 02-FEB-08:10 |
Cooling:EnergyTransfer:Zone:LGSTORE2 | 37.95 | 0.00 | 01-JAN-00:10 | 13636.61 | 04-AUG-14:50 |
General:Cooling:EnergyTransfer:Zone:LGSTORE2 | 37.95 | 0.00 | 01-JAN-00:10 | 13636.61 | 04-AUG-14:50 |
EnergyTransfer:Zone:SMSTORE5 | 44.72 | 0.00 | 01-JAN-00:10 | 19018.28 | 02-FEB-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE5 | 25.76 | 0.00 | 01-JAN-00:10 | 19018.28 | 02-FEB-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE5 | 25.76 | 0.00 | 01-JAN-00:10 | 19018.28 | 02-FEB-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE5 | 18.97 | 0.00 | 01-JAN-00:10 | 7113.90 | 04-AUG-14:50 |
General:Cooling:EnergyTransfer:Zone:SMSTORE5 | 18.97 | 0.00 | 01-JAN-00:10 | 7113.90 | 04-AUG-14:50 |
EnergyTransfer:Zone:SMSTORE6 | 44.64 | 0.00 | 01-JAN-00:10 | 19073.87 | 02-FEB-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE6 | 26.19 | 0.00 | 01-JAN-00:10 | 19073.87 | 02-FEB-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE6 | 26.19 | 0.00 | 01-JAN-00:10 | 19073.87 | 02-FEB-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE6 | 18.45 | 0.00 | 01-JAN-00:10 | 7065.98 | 04-AUG-14:50 |
General:Cooling:EnergyTransfer:Zone:SMSTORE6 | 18.45 | 0.00 | 01-JAN-00:10 | 7065.98 | 04-AUG-14:50 |
EnergyTransfer:Zone:SMSTORE7 | 45.92 | 0.00 | 01-JAN-00:10 | 19688.38 | 02-FEB-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE7 | 28.79 | 0.00 | 01-JAN-00:10 | 19688.38 | 02-FEB-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE7 | 28.79 | 0.00 | 01-JAN-00:10 | 19688.38 | 02-FEB-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE7 | 17.13 | 0.00 | 01-JAN-00:10 | 7020.26 | 04-AUG-15:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE7 | 17.13 | 0.00 | 01-JAN-00:10 | 7020.26 | 04-AUG-15:00 |
EnergyTransfer:Zone:SMSTORE8 | 62.50 | 0.00 | 01-JAN-00:10 | 24246.41 | 02-FEB-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE8 | 47.10 | 0.00 | 01-JAN-00:10 | 24246.41 | 02-FEB-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE8 | 47.10 | 0.00 | 01-JAN-00:10 | 24246.41 | 02-FEB-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE8 | 15.40 | 0.00 | 01-JAN-00:10 | 7515.90 | 04-AUG-14:50 |
General:Cooling:EnergyTransfer:Zone:SMSTORE8 | 15.40 | 0.00 | 01-JAN-00:10 | 7515.90 | 04-AUG-14:50 |
EnergyTransfer:HVAC | 1075.96 | 0.00 | 01-JAN-00:10 | 283137.83 | 02-FEB-12:10 |
HeatingCoils:EnergyTransfer | 774.55 | 0.00 | 01-JAN-00:10 | 283137.83 | 02-FEB-12:10 |
CoolingCoils:EnergyTransfer | 301.41 | 0.00 | 01-JAN-00:10 | 213838.81 | 04-AUG-13:00 |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:25
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
LGSTORE1 | 0.000 | 0.000 | 50.162 | -62.902 | 0.000 | 0.000 | 25.618 | 87.116 | 26.249 | 22.263 | 0.000 | 1.561 | 0.000 | 0.000 | -11.759 | 0.000 | -53.939 | -84.369 |
SMSTORE1 | 0.000 | 0.000 | 17.008 | -35.682 | 0.000 | 0.000 | 12.642 | 53.201 | 13.125 | 11.031 | 0.000 | 0.838 | 0.000 | 0.000 | -6.148 | 0.000 | -25.659 | -40.355 |
SMSTORE2 | 0.000 | 0.000 | 19.772 | -26.184 | 0.000 | 0.000 | 7.681 | 37.572 | 10.421 | 11.016 | 0.000 | 0.817 | 0.002 | 0.000 | -6.060 | 0.000 | -26.483 | -28.550 |
SMSTORE3 | 0.000 | 0.000 | 20.961 | -25.510 | 0.000 | 0.000 | 7.689 | 37.572 | 10.421 | 11.029 | 0.000 | 0.817 | 0.001 | 0.000 | -6.005 | 0.000 | -26.402 | -30.571 |
SMSTORE4 | 0.000 | 0.000 | 22.900 | -23.848 | 0.000 | 0.000 | 7.702 | 37.572 | 10.421 | 11.050 | 0.000 | 0.817 | 0.002 | 0.000 | -5.948 | 0.000 | -26.302 | -34.365 |
LGSTORE2 | 0.000 | 0.000 | 46.353 | -37.948 | 0.000 | 0.000 | 26.480 | 37.162 | 19.173 | 22.208 | 0.000 | 1.476 | 0.004 | 0.000 | -11.563 | 0.000 | -48.641 | -54.701 |
SMSTORE5 | 0.000 | 0.000 | 25.757 | -18.965 | 0.000 | 0.000 | 13.248 | 19.120 | 9.586 | 11.085 | 0.000 | 0.820 | 0.002 | 0.000 | -5.797 | 0.000 | -26.396 | -28.458 |
SMSTORE6 | 0.000 | 0.000 | 26.195 | -18.448 | 0.000 | 0.000 | 13.257 | 19.120 | 9.586 | 11.095 | 0.000 | 0.820 | 0.001 | 0.000 | -5.778 | 0.000 | -26.360 | -29.488 |
SMSTORE7 | 0.000 | 0.000 | 28.789 | -17.133 | 0.000 | 0.000 | 13.279 | 19.120 | 9.586 | 11.122 | 0.000 | 0.821 | 0.001 | 0.000 | -5.705 | 0.000 | -26.238 | -33.641 |
SMSTORE8 | 0.000 | 0.000 | 47.101 | -15.395 | 0.000 | 0.000 | 13.314 | 19.120 | 9.586 | 11.203 | 0.000 | 0.875 | 0.001 | 0.000 | -5.408 | 0.000 | -34.592 | -45.804 |
Total Facility | 0.000 | 0.000 | 304.998 | -282.015 | 0.000 | 0.000 | 140.909 | 366.677 | 128.154 | 133.102 | 0.000 | 9.661 | 0.015 | 0.000 | -70.170 | 0.000 | -321.012 | -410.304 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
LGSTORE1 | 04-JUL-07:02 | 0.00 | 0.00 | 0.00 | -27810.47 | 0.00 | 0.00 | 182.47 | 75.00 | 74.62 | 417.67 | 0.00 | 0.00 | 27228.78 | 0.00 | -0.00 | 0.00 | -168.07 | 0.00 |
SMSTORE1 | 04-JUL-07:02 | 0.00 | 0.00 | 0.00 | -15670.00 | 0.00 | 0.00 | 88.76 | 37.50 | 37.31 | 204.36 | 0.00 | 0.00 | 15388.25 | 0.00 | -0.00 | 0.00 | -86.19 | 0.00 |
SMSTORE2 | 11-SEP-06:03 | 0.00 | 0.00 | 0.00 | -16891.22 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 0.00 | 0.00 | 0.00 | 16886.77 | 0.00 | -49.46 | 0.00 | -20.41 | 0.00 |
SMSTORE3 | 11-SEP-06:03 | 0.00 | 0.00 | 0.00 | -16976.75 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 0.00 | 0.00 | 0.00 | 16973.12 | 0.00 | -50.13 | 0.00 | -20.55 | 0.00 |
SMSTORE4 | 11-SEP-06:03 | 0.00 | 0.00 | 0.00 | -16274.13 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 0.00 | 0.00 | 0.00 | 16268.91 | 0.00 | -48.77 | 0.00 | -20.33 | 0.00 |
LGSTORE2 | 11-SEP-07:03 | 0.00 | 0.00 | 0.00 | -28769.15 | 0.00 | 0.00 | 0.00 | 75.00 | 73.64 | 417.06 | 0.00 | 0.00 | 28372.90 | 0.00 | -0.00 | 0.00 | -169.44 | 0.00 |
SMSTORE5 | 11-SEP-07:03 | 0.00 | 0.00 | 0.00 | -14142.19 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 208.95 | 0.00 | 0.00 | 13951.04 | 0.00 | -0.00 | 0.00 | -92.12 | 0.00 |
SMSTORE6 | 11-SEP-07:03 | 0.00 | 0.00 | 0.00 | -13631.24 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 209.72 | 0.00 | 0.00 | 13439.18 | 0.00 | -0.00 | 0.00 | -91.98 | 0.00 |
SMSTORE7 | 03-JUL-07:03 | 0.00 | 0.00 | 0.00 | -13174.45 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 224.65 | 0.00 | 0.00 | 12969.72 | 0.00 | -0.00 | 0.00 | -94.23 | 0.00 |
SMSTORE8 | 04-JUL-08:62 | 0.00 | 0.00 | 0.00 | -14828.95 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 367.34 | 0.00 | 0.00 | 14433.52 | 0.00 | -0.00 | 0.00 | -46.22 | 0.00 |
Total Facility | 11-SEP-07:03 | 0.00 | 0.00 | 0.00 | -118879.62 | 0.00 | 0.00 | 570.20 | 450.00 | 1452.23 | 2545.75 | 0.00 | 0.00 | 114981.39 | 0.00 | 0.00 | 0.00 | -1119.95 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
LGSTORE1 | 02-FEB-00:42 | 0.00 | 0.00 | 65498.54 | 0.00 | 0.00 | 0.00 | 0.00 | 75.00 | 73.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1794.04 | 0.00 | -4467.97 | -59385.17 |
SMSTORE1 | 02-FEB-08:12 | 0.00 | 0.00 | 33757.01 | 0.00 | 0.00 | 0.00 | 115.61 | 148.79 | 37.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -541.16 | 0.00 | -1724.09 | -31793.48 |
SMSTORE2 | 02-FEB-07:01 | 0.00 | 0.00 | 33703.06 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -880.60 | 0.00 | -182.16 | -32714.63 |
SMSTORE3 | 10-DEC-08:61 | 0.00 | 0.00 | 34372.11 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 37.31 | 325.49 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -1136.63 | -33635.78 |
SMSTORE4 | 30-JAN-07:12 | 0.00 | 0.00 | 33692.69 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -795.32 | 0.00 | -226.84 | -32744.85 |
LGSTORE2 | 02-FEB-08:12 | 0.00 | 0.00 | 63095.33 | 0.00 | 0.00 | 0.00 | 0.00 | 75.00 | 73.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1057.24 | 0.00 | -3138.91 | -59047.82 |
SMSTORE5 | 02-FEB-08:12 | 0.00 | 0.00 | 32124.76 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -531.27 | 0.00 | -1719.12 | -29948.69 |
SMSTORE6 | 02-FEB-08:12 | 0.00 | 0.00 | 31979.73 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -531.08 | 0.00 | -1718.63 | -29804.34 |
SMSTORE7 | 02-FEB-08:12 | 0.00 | 0.00 | 31792.96 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -529.38 | 0.00 | -1716.92 | -29620.97 |
SMSTORE8 | 19-JAN-01:11 | 0.00 | 0.00 | 36812.06 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -644.87 | 0.00 | -4535.91 | -31705.60 |
Total Facility | 02-FEB-08:61 | 0.00 | 0.00 | 321479.86 | 0.00 | 0.00 | 0.00 | 785.50 | 450.00 | 1452.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -6629.40 | 0.00 | -19607.02 | -297931.17 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:25
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 1.9385 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 1.9385 | 0.2123 | 1.0000 | Not calculated | 0.4115 | 0.2123 | ||
PSZ-AC_2:2 | 1.0272 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0512 | 0.1957 | 1.0000 | Not calculated | 0.2057 | 0.1957 | ||
PSZ-AC_3:3 | 1.0309 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0575 | 0.1946 | 1.0000 | Not calculated | 0.2057 | 0.1946 | ||
PSZ-AC_4:4 | 1.0612 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0612 | 0.1939 | 1.0000 | Not calculated | 0.2057 | 0.1939 | ||
PSZ-AC_5:5 | 1.0221 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0507 | 0.1958 | 1.0000 | Not calculated | 0.2057 | 0.1958 | ||
PSZ-AC_6:6 | 1.8446 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 1.8446 | 0.2231 | 1.0000 | Not calculated | 0.4115 | 0.2231 | ||
PSZ-AC_7:7 | 0.9439 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9520 | 0.2161 | 1.0000 | Not calculated | 0.2057 | 0.2161 | ||
PSZ-AC_8:8 | 0.9370 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9453 | 0.2177 | 1.0000 | Not calculated | 0.2057 | 0.2177 | ||
PSZ-AC_9:9 | 0.9270 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9387 | 0.2192 | 1.0000 | Not calculated | 0.2057 | 0.2192 | ||
PSZ-AC_10:10 | 1.1460 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.1460 | 0.2065 | 1.0000 | Not calculated | 0.2057 | 0.1795 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 1.9385 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 1.9385 | 1.0000 | 1.0000 | Not calculated | 0.4115 | 0.2123 | ||
PSZ-AC_2:2 | 1.0272 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0272 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.2003 | ||
PSZ-AC_3:3 | 1.0309 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0309 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1996 | ||
PSZ-AC_4:4 | 1.0612 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0612 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1939 | ||
PSZ-AC_5:5 | 1.0221 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0221 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.2013 | ||
PSZ-AC_6:6 | 1.8446 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 1.8446 | 1.0000 | 1.0000 | Not calculated | 0.4115 | 0.2231 | ||
PSZ-AC_7:7 | 0.9439 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9439 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.2180 | ||
PSZ-AC_8:8 | 0.9370 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9370 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.2196 | ||
PSZ-AC_9:9 | 0.9270 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9270 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.2219 | ||
PSZ-AC_10:10 | 1.1460 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.1460 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1795 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
LGSTORE1 | PSZ-AC_1:1 | 0.000000 | 56.2505 | 0.001181 | 348.39 | 0.4115 | 1.0000 | 0.4115 | 1.000 | 0.4115 |
SMSTORE1 | PSZ-AC_2:2 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE2 | PSZ-AC_3:3 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE3 | PSZ-AC_4:4 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE4 | PSZ-AC_5:5 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
LGSTORE2 | PSZ-AC_6:6 | 0.000000 | 56.2505 | 0.001181 | 348.39 | 0.4115 | 1.0000 | 0.4115 | 1.000 | 0.4115 |
SMSTORE5 | PSZ-AC_7:7 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE6 | PSZ-AC_8:8 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE7 | PSZ-AC_9:9 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE8 | PSZ-AC_10:10 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC_1:1 | 0.000000 | 56.25 | 0.001181 | 348.3864 | 0.4115 | 0.4115 | 0.4115 |
PSZ-AC_2:2 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_3:3 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_4:4 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_5:5 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_6:6 | 0.000000 | 56.25 | 0.001181 | 348.3864 | 0.4115 | 0.4115 | 0.4115 |
PSZ-AC_7:7 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_8:8 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_9:9 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_10:10 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LGSTORE1 | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.9385 | 1.9385 | 1.9385 | No | 0.4115 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE1 | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0272 | 1.0272 | 1.0272 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE2 | PSZ-AC_3:3 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0309 | 1.0309 | 1.0309 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE3 | PSZ-AC_4:4 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0612 | 1.0612 | 1.0612 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE4 | PSZ-AC_5:5 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0221 | 1.0221 | 1.0221 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LGSTORE2 | PSZ-AC_6:6 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.8446 | 1.8446 | 1.8446 | No | 0.4115 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE5 | PSZ-AC_7:7 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9439 | 0.9439 | 0.9439 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE6 | PSZ-AC_8:8 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9370 | 0.9370 | 0.9370 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE7 | PSZ-AC_9:9 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9270 | 0.9270 | 0.9270 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE8 | PSZ-AC_10:10 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1460 | 1.1460 | 1.1460 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 1.9385 | 1.9385 | 1.9385 | 1.9385 | 0.4115 | 1.0000 |
PSZ-AC_2:2 | 1.0272 | 1.0512 | 1.0272 | 1.0272 | 0.2057 | 1.0000 |
PSZ-AC_3:3 | 1.0309 | 1.0575 | 1.0309 | 1.0309 | 0.2057 | 1.0000 |
PSZ-AC_4:4 | 1.0612 | 1.0612 | 1.0612 | 1.0612 | 0.2057 | 1.0000 |
PSZ-AC_5:5 | 1.0221 | 1.0507 | 1.0221 | 1.0221 | 0.2057 | 1.0000 |
PSZ-AC_6:6 | 1.8446 | 1.8446 | 1.8446 | 1.8446 | 0.4115 | 1.0000 |
PSZ-AC_7:7 | 0.9439 | 0.9520 | 0.9439 | 0.9439 | 0.2057 | 1.0000 |
PSZ-AC_8:8 | 0.9370 | 0.9453 | 0.9370 | 0.9370 | 0.2057 | 1.0000 |
PSZ-AC_9:9 | 0.9270 | 0.9387 | 0.9270 | 0.9270 | 0.2057 | 1.0000 |
PSZ-AC_10:10 | 1.1460 | 1.1460 | 1.1460 | 1.1460 | 0.2057 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LGSTORE1 | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.9385 | 1.9385 | 1.9385 | No | 0.4115 | 0.2207 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE1 | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0272 | 1.0272 | 1.0272 | No | 0.2057 | 0.2339 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE2 | PSZ-AC_3:3 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0309 | 1.0309 | 1.0309 | No | 0.2057 | 0.2318 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE3 | PSZ-AC_4:4 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0612 | 1.0612 | 1.0612 | No | 0.2057 | 0.2310 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE4 | PSZ-AC_5:5 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0221 | 1.0221 | 1.0221 | No | 0.2057 | 0.2291 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LGSTORE2 | PSZ-AC_6:6 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.8446 | 1.8446 | 1.8446 | No | 0.4115 | 0.2406 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE5 | PSZ-AC_7:7 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9439 | 0.9439 | 0.9439 | No | 0.2057 | 0.2246 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE6 | PSZ-AC_8:8 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9370 | 0.9370 | 0.9370 | No | 0.2057 | 0.2248 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE7 | PSZ-AC_9:9 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9270 | 0.9270 | 0.9270 | No | 0.2057 | 0.2219 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE8 | PSZ-AC_10:10 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1460 | 1.1460 | 1.1460 | No | 0.2057 | 0.1795 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 1.9385 | 1.9385 | 1.9385 | 1.9385 | 0.4115 | 1.0000 |
PSZ-AC_2:2 | 1.0272 | 1.0272 | 1.0272 | 1.0272 | 0.2057 | 1.0000 |
PSZ-AC_3:3 | 1.0309 | 1.0309 | 1.0309 | 1.0309 | 0.2057 | 1.0000 |
PSZ-AC_4:4 | 1.0612 | 1.0612 | 1.0612 | 1.0612 | 0.2057 | 1.0000 |
PSZ-AC_5:5 | 1.0221 | 1.0221 | 1.0221 | 1.0221 | 0.2057 | 1.0000 |
PSZ-AC_6:6 | 1.8446 | 1.8446 | 1.8446 | 1.8446 | 0.4115 | 1.0000 |
PSZ-AC_7:7 | 0.9439 | 0.9439 | 0.9439 | 0.9439 | 0.2057 | 1.0000 |
PSZ-AC_8:8 | 0.9370 | 0.9370 | 0.9370 | 0.9370 | 0.2057 | 1.0000 |
PSZ-AC_9:9 | 0.9270 | 0.9270 | 0.9270 | 0.9270 | 0.2057 | 1.0000 |
PSZ-AC_10:10 | 1.1460 | 1.1460 | 1.1460 | 1.1460 | 0.2057 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:25
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Rochester International Arpt MN USA TMY3 WMO#=726440 |
Total gross floor area [m2] | 2090.32 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
LGSTORE1 | 348.39 | 348.39 | 0.00 | 112.00 |
SMSTORE1 | 174.19 | 174.19 | 0.00 | 112.00 |
SMSTORE2 | 174.19 | 174.19 | 0.00 | 84.29 |
SMSTORE3 | 174.19 | 174.19 | 0.00 | 84.29 |
SMSTORE4 | 174.19 | 174.19 | 0.00 | 84.29 |
LGSTORE2 | 348.39 | 348.39 | 0.00 | 77.29 |
SMSTORE5 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE6 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE7 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE8 | 174.19 | 174.19 | 0.00 | 77.29 |
Totals | 2090.32 | 2090.32 | 0.00 |
Data | |
Number of hours heating loads not met | 7.83 |
Number of hours cooling loads not met | 0.00 |
Number of hours not met | 7.83 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 968.19 | 353922.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 74.87 | 50556.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 366.68 | 23459.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 60.26 | 5507.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 128.15 | 8059.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 106.11 | 10910.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 66.12 | 12806.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 128.15 | 802.19 |
Natural Gas | 0.00 | 968.19 |
Additional | 0.00 | 0.00 |
Total | 128.15 | 1770.38 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 175.42 |
Space Heating | 0.00 |
Space Cooling | 35.82 |
Fans (All) | 50.76 |
Service Water Heating | 31.63 |
Receptacle Equipment | 61.31 |
Miscellaneous (All) | 383.77 |
Subtotal | 383.77 |
Natural Gas [MJ/m2] | |
Space Heating | 463.18 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 463.18 |
Subtotal | 463.18 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 20.71 |
Space Heating | 54.69 |
Space Cooling | 4.23 |
Fans (All) | 5.99 |
Service Water Heating | 3.74 |
Receptacle Equipment | 7.24 |
Miscellaneous | 3.40 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
TYPE1_OCC_SCH | 1630. | 5840. |
TYPE2_OCC_SCH | 995. | 4429. |
TYPE3_OCC_SCH | 1709. | 4064. |
LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 3767. | 8760. |
LTG_SCH_BASE_LPD2 | 3238. | 8760. |
LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 3296. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | 5084. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | 5084. | 8760. |
LTG_SCH_BASE_SMALL_LPD1 | 4453. | 8760. |
LTG_SCH_BASE_LPD1 | 4376. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | 3767. | 8760. |
LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 3584. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 4096. | 8760. |
TYPE1_EQUIP_SCH | 4868. | 8760. |
TYPE2_EQUIP_SCH | 3893. | 8760. |
TYPE3_EQUIP_SCH | 3584. | 8760. |
TYPE1_INFIL_SCH | 4302. | 8760. |
TYPE2_INFIL_SCH | 5164. | 8760. |
TYPE3_INFIL_SCH | 5438. | 8760. |
INFIL_DOOR_OPENING_SCH | 2477. | 4380. |
TYPE1_MINOA_MOTORIZEDDAMPER_SCH | 5579. | 5579. |
TYPE2_MINOA_MOTORIZEDDAMPER_SCH | 4429. | 4429. |
TYPE3_MINOA_MOTORIZEDDAMPER_SCH | 4064. | 4064. |
TYPE1_SWH_SCH | 2063. | 6048. |
TYPE2_SWH_SCH | 1831. | 4429. |
TYPE3_SWH_SCH | 1733. | 4064. |
AVERAGE_SWH_SCH | 1863. | 6152. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 7118. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 5839. | 5839. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 7300. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6570. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
TYPE1_HTGSETP_SCH_NO_OPTIMUM | LGSTORE1 DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
TYPE1_CLGSETP_SCH_NO_OPTIMUM | LGSTORE1 DUAL SP CONTROL | July | 23.89 | 365 | 23.89 | 365 |
TYPE2_HTGSETP_SCH_NO_OPTIMUM | SMSTORE2 DUAL SP CONTROL | January | 21.11 | 365 | 15.56 | 365 |
TYPE2_CLGSETP_SCH_NO_OPTIMUM | SMSTORE2 DUAL SP CONTROL | July | 23.89 | 365 | 29.44 | 365 |
TYPE3_HTGSETP_SCH_NO_OPTIMUM | LGSTORE2 DUAL SP CONTROL | January | 21.11 | 365 | 15.56 | 365 |
TYPE3_CLGSETP_SCH_NO_OPTIMUM | LGSTORE2 DUAL SP CONTROL | July | 23.89 | 365 | 29.44 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:25
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
LGSTORE1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 8736.00 | 24.00 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 8734.50 | 25.50 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 8740.00 | 20.00 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 8747.50 | 12.50 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 8750.17 | 9.83 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 8751.33 | 8.67 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 8753.67 | 6.33 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 8752.17 | 7.83 | 0.00 | 0.00 | 0.00 |
Min | 8734.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 25.50 | 0.00 | 0.00 | 0.00 |
Average | 8748.53 | 11.47 | 0.00 | 0.00 | 0.00 |
Sum | 87485.33 | 114.67 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
LGSTORE1 | 89041.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 43777.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 25467.50 | 7.50 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 25467.83 | 7.17 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 25468.83 | 6.17 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 93188.00 | 23.00 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 45901.50 | 10.50 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 45902.00 | 10.00 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 45902.50 | 9.50 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 45902.50 | 9.50 | 0.00 | 0.00 | 0.00 |
Min | 25467.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 93188.00 | 23.00 | 0.00 | 0.00 | 0.00 |
Average | 48601.87 | 8.33 | 0.00 | 0.00 | 0.00 |
Sum | 486018.67 | 83.33 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
LGSTORE1 | 8192.83 | 567.17 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 8556.00 | 204.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 7982.00 | 778.00 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 7982.50 | 777.50 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 7994.67 | 765.33 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 7997.00 | 763.00 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 8002.50 | 757.50 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 8006.50 | 753.50 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 8015.17 | 744.83 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 8086.67 | 673.33 | 0.00 | 0.00 | 0.00 |
Min | 7982.00 | 204.00 | 0.00 | 0.00 | 0.00 |
Max | 8556.00 | 778.00 | 0.00 | 0.00 | 0.00 |
Average | 8081.58 | 678.42 | 0.00 | 0.00 | 0.00 |
Sum | 80815.83 | 6784.17 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
LGSTORE1 | 86256.00 | 2785.00 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 43108.33 | 668.67 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 24801.50 | 673.50 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 24787.00 | 688.00 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 24714.17 | 760.83 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 89177.67 | 4033.33 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 43877.67 | 2034.33 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 43845.00 | 2067.00 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 43687.67 | 2224.33 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 43519.33 | 2392.67 | 0.00 | 0.00 | 0.00 |
Min | 24714.17 | 668.67 | 0.00 | 0.00 | 0.00 |
Max | 89177.67 | 4033.33 | 0.00 | 0.00 | 0.00 |
Average | 46777.43 | 1832.77 | 0.00 | 0.00 | 0.00 |
Sum | 467774.33 | 18327.67 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:25
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:25
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
For: Environment
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTRIPMALL
For: Environment
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6A
For: Environment
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_ROCHESTER
For: Environment
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: ZoneCoolingSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.314395E+09 | 20469.35 | 06-JAN-00:01 | -25.1 | -25.3 | 0.106455E+10 | 1275.40 | 15-JAN-18:00 | -6.7 | -7.4 |
February | 0.447644E+09 | 24057.28 | 03-FEB-00:01 | -32.8 | -33.0 | 0.961171E+09 | 1275.40 | 05-FEB-18:00 | -18.9 | -19.4 |
March | 0.132852E+10 | 13292.95 | 11-MAR-00:02 | -9.8 | -10.4 | 0.106668E+10 | 1592.31 | 19-MAR-17:40 | 16.83 | 12.89 |
April | 0.313413E+10 | 9717.82 | 16-APR-16:05 | 28.80 | 20.54 | 0.110605E+10 | 1686.00 | 16-APR-16:49 | 28.40 | 20.34 |
May | 0.603328E+10 | 10351.90 | 31-MAY-17:00 | 28.90 | 19.84 | 0.130643E+10 | 1685.92 | 14-MAY-12:00 | 28.90 | 19.84 |
June | 0.100828E+11 | 24037.93 | 30-JUN-07:03 | 23.07 | 20.55 | 0.131288E+10 | 1686.02 | 11-JUN-12:00 | 23.07 | 20.55 |
July | 0.122092E+11 | 27824.91 | 04-JUL-07:02 | 20.87 | 18.54 | 0.141224E+10 | 1686.02 | 30-JUL-17:40 | 25.37 | 19.17 |
August | 0.123607E+11 | 22291.61 | 23-AUG-07:03 | 18.40 | 17.24 | 0.139362E+10 | 1686.01 | 13-AUG-17:10 | 18.40 | 17.24 |
September | 0.978235E+10 | 23703.41 | 11-SEP-07:03 | 20.37 | 17.95 | 0.128864E+10 | 1686.01 | 10-SEP-17:49 | 20.37 | 17.95 |
October | 0.479498E+10 | 8887.67 | 26-OCT-23:03 | -0.3 | -1.3 | 0.113445E+10 | 1685.86 | 20-OCT-12:00 | -0.3 | -1.3 |
November | 0.197081E+10 | 15006.76 | 25-NOV-00:01 | -13.4 | -13.7 | 0.104291E+10 | 1515.65 | 03-NOV-12:00 | -13.4 | -13.7 |
December | 0.443597E+09 | 19389.25 | 09-DEC-00:01 | -22.8 | -23.0 | 0.106991E+10 | 1275.40 | 10-DEC-18:00 | -20.0 | -20.7 |
Annual Sum or Average | 0.629023E+11 | 0.141595E+11 | ||||||||
Minimum of Months | 0.314395E+09 | 8887.67 | -32.8 | -33.0 | 0.961171E+09 | 1275.40 | -20.0 | -20.7 | ||
Maximum of Months | 0.123607E+11 | 27824.91 | 28.90 | 20.55 | 0.141224E+10 | 1686.02 | 28.90 | 20.55 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 67297187.75 | 7943.43 | 04-JAN-19:12 | -15.6 | -16.0 | 0.535058E+09 | 678.42 | 01-JAN-18:00 | -15.6 | -16.0 |
February | 0.208270E+09 | 4446.85 | 26-FEB-10:53 | -0.6 | -2.4 | 0.487909E+09 | 729.75 | 20-FEB-18:00 | -0.6 | -2.4 |
March | 0.795386E+09 | 5533.92 | 13-MAR-10:12 | -5.2 | -7.2 | 0.551534E+09 | 842.90 | 19-MAR-17:00 | 16.10 | 12.47 |
April | 0.186162E+10 | 11837.49 | 15-APR-22:33 | 20.77 | 16.30 | 0.577095E+09 | 842.97 | 16-APR-17:10 | 28.03 | 20.22 |
May | 0.364255E+10 | 14374.91 | 07-MAY-17:08 | 18.80 | 12.89 | 0.678419E+09 | 842.95 | 14-MAY-12:39 | 20.20 | 14.62 |
June | 0.588222E+10 | 15049.42 | 26-JUN-07:03 | 23.58 | 21.51 | 0.666413E+09 | 843.01 | 25-JUN-12:00 | 23.58 | 21.51 |
July | 0.706607E+10 | 15674.38 | 04-JUL-07:02 | 20.87 | 18.54 | 0.704551E+09 | 843.13 | 30-JUL-17:19 | 25.73 | 18.94 |
August | 0.708201E+10 | 15485.71 | 06-AUG-17:27 | 18.30 | 11.61 | 0.695702E+09 | 842.98 | 12-AUG-12:50 | 26.70 | 19.36 |
September | 0.545743E+10 | 14795.26 | 11-SEP-07:03 | 20.37 | 17.95 | 0.656996E+09 | 842.98 | 17-SEP-17:40 | 24.97 | 16.84 |
October | 0.249884E+10 | 4023.49 | 31-OCT-17:20 | 2.33 | -0.3 | 0.604920E+09 | 842.91 | 20-OCT-12:00 | 2.33 | -0.3 |
November | 0.963144E+09 | 4495.31 | 23-NOV-10:43 | -0.8 | -2.0 | 0.545155E+09 | 842.90 | 05-NOV-17:00 | -0.8 | -2.0 |
December | 0.157574E+09 | 6373.27 | 25-DEC-11:52 | -8.9 | -9.9 | 0.542507E+09 | 743.20 | 03-DEC-18:00 | -8.9 | -9.9 |
Annual Sum or Average | 0.356824E+11 | 0.724626E+10 | ||||||||
Minimum of Months | 67297187.75 | 4023.49 | -15.6 | -16.0 | 0.487909E+09 | 678.42 | -15.6 | -16.0 | ||
Maximum of Months | 0.708201E+10 | 15674.38 | 23.58 | 21.51 | 0.704551E+09 | 843.13 | 28.03 | 21.51 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 21364354.72 | 1350.10 | 13-JAN-18:10 | 1.93 | 0.58 | 0.317182E+09 | 637.68 | 07-JAN-13:09 | 1.93 | 0.58 |
February | 95285136.41 | 5053.78 | 14-FEB-19:23 | -3.3 | -3.9 | 0.288104E+09 | 637.68 | 04-FEB-13:09 | -3.3 | -3.9 |
March | 0.526254E+09 | 3884.22 | 27-MAR-08:43 | 1.60 | -0.2 | 0.329278E+09 | 641.57 | 25-MAR-12:00 | 1.60 | -0.2 |
April | 0.135373E+10 | 5267.37 | 18-APR-14:00 | 28.30 | 20.65 | 0.334134E+09 | 842.90 | 15-APR-12:09 | 28.30 | 20.65 |
May | 0.260437E+10 | 5817.05 | 31-MAY-13:00 | 30.00 | 19.70 | 0.403755E+09 | 842.92 | 27-MAY-12:09 | 30.00 | 19.70 |
June | 0.437173E+10 | 14731.34 | 12-JUN-06:03 | 17.88 | 17.07 | 0.406754E+09 | 842.98 | 24-JUN-12:39 | 26.70 | 20.10 |
July | 0.507802E+10 | 15992.69 | 03-JUL-06:02 | 19.08 | 17.92 | 0.419751E+09 | 842.98 | 29-JUL-12:09 | 26.88 | 20.28 |
August | 0.528275E+10 | 15915.81 | 23-AUG-06:03 | 17.88 | 17.07 | 0.431141E+09 | 842.98 | 12-AUG-12:00 | 17.88 | 17.07 |
September | 0.408495E+10 | 16896.94 | 11-SEP-06:03 | 19.50 | 17.29 | 0.389011E+09 | 842.96 | 02-SEP-12:09 | 19.50 | 17.29 |
October | 0.196567E+10 | 4223.36 | 31-OCT-07:01 | 1.28 | 0.04 | 0.340239E+09 | 842.89 | 21-OCT-12:39 | 1.28 | 0.04 |
November | 0.757440E+09 | 5267.87 | 20-NOV-20:12 | -4.3 | -5.8 | 0.312736E+09 | 756.47 | 04-NOV-12:00 | -4.3 | -5.8 |
December | 42934946.27 | 5604.27 | 05-DEC-10:22 | -5.5 | -7.9 | 0.316799E+09 | 637.68 | 02-DEC-13:00 | -5.5 | -7.9 |
Annual Sum or Average | 0.261845E+11 | 0.428888E+10 | ||||||||
Minimum of Months | 21364354.72 | 1350.10 | -5.5 | -7.9 | 0.288104E+09 | 637.68 | -5.5 | -7.9 | ||
Maximum of Months | 0.528275E+10 | 16896.94 | 30.00 | 20.65 | 0.431141E+09 | 842.98 | 30.00 | 20.65 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 17709596.00 | 1262.98 | 13-JAN-18:10 | 1.93 | 0.58 | 0.317182E+09 | 637.68 | 07-JAN-13:09 | 1.93 | 0.58 |
February | 79214090.06 | 6232.53 | 15-FEB-18:52 | -8.3 | -9.4 | 0.288103E+09 | 637.68 | 11-FEB-13:50 | -8.3 | -9.4 |
March | 0.462384E+09 | 5910.80 | 10-MAR-20:12 | -6.9 | -7.8 | 0.328890E+09 | 638.74 | 25-MAR-12:00 | 11.70 | 6.50 |
April | 0.126740E+10 | 5191.93 | 18-APR-14:00 | 28.30 | 20.65 | 0.333420E+09 | 842.90 | 15-APR-12:09 | 28.30 | 20.65 |
May | 0.247890E+10 | 5758.17 | 31-MAY-13:00 | 30.00 | 19.70 | 0.401672E+09 | 842.94 | 27-MAY-12:20 | 30.00 | 19.70 |
June | 0.432956E+10 | 14998.10 | 28-JUN-06:03 | 19.27 | 17.32 | 0.406063E+09 | 842.98 | 24-JUN-12:39 | 19.27 | 17.32 |
July | 0.507089E+10 | 16094.52 | 03-JUL-06:02 | 19.08 | 17.92 | 0.419740E+09 | 842.98 | 29-JUL-12:09 | 26.88 | 20.28 |
August | 0.526224E+10 | 15909.97 | 23-AUG-06:03 | 17.88 | 17.07 | 0.431130E+09 | 842.98 | 05-AUG-12:30 | 17.88 | 17.07 |
September | 0.402887E+10 | 16982.50 | 11-SEP-06:03 | 19.50 | 17.29 | 0.388145E+09 | 842.96 | 02-SEP-12:09 | 19.50 | 17.29 |
October | 0.178781E+10 | 4093.15 | 13-OCT-07:01 | 1.65 | 0.38 | 0.338077E+09 | 842.89 | 21-OCT-12:50 | 19.48 | 13.25 |
November | 0.687866E+09 | 5979.68 | 21-NOV-11:52 | -7.2 | -8.7 | 0.311560E+09 | 746.53 | 04-NOV-12:00 | -7.2 | -8.7 |
December | 37891462.24 | 6754.25 | 20-DEC-18:52 | -10.6 | -11.2 | 0.316799E+09 | 637.68 | 02-DEC-13:39 | -10.6 | -11.2 |
Annual Sum or Average | 0.255107E+11 | 0.428078E+10 | ||||||||
Minimum of Months | 17709596.00 | 1262.98 | -10.6 | -11.2 | 0.288103E+09 | 637.68 | -10.6 | -11.2 | ||
Maximum of Months | 0.526224E+10 | 16982.50 | 30.00 | 20.65 | 0.431130E+09 | 842.98 | 30.00 | 20.65 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 12746670.00 | 3893.44 | 12-JAN-20:03 | 1.60 | -0.1 | 0.317182E+09 | 637.68 | 07-JAN-13:20 | 1.60 | -0.1 |
February | 50841842.55 | 4470.64 | 21-FEB-19:03 | -0.7 | -2.3 | 0.288104E+09 | 637.68 | 04-FEB-13:09 | -0.7 | -2.3 |
March | 0.365640E+09 | 4071.37 | 30-MAR-09:23 | 1.10 | 0.61 | 0.328303E+09 | 637.68 | 04-MAR-13:30 | 1.10 | 0.61 |
April | 0.111724E+10 | 4975.90 | 18-APR-14:00 | 28.30 | 20.65 | 0.332194E+09 | 842.90 | 15-APR-12:09 | 28.30 | 20.65 |
May | 0.225248E+10 | 5556.25 | 31-MAY-13:00 | 30.00 | 19.70 | 0.397166E+09 | 842.92 | 27-MAY-12:20 | 30.00 | 19.70 |
June | 0.412269E+10 | 14330.89 | 30-JUN-06:03 | 21.38 | 19.39 | 0.404748E+09 | 842.98 | 24-JUN-12:39 | 21.38 | 19.39 |
July | 0.486843E+10 | 15866.56 | 03-JUL-06:02 | 19.08 | 17.92 | 0.419666E+09 | 842.98 | 29-JUL-12:09 | 26.88 | 20.28 |
August | 0.505444E+10 | 14357.62 | 23-AUG-06:03 | 17.88 | 17.07 | 0.431059E+09 | 842.98 | 05-AUG-12:30 | 17.88 | 17.07 |
September | 0.383734E+10 | 16279.45 | 11-SEP-06:03 | 19.50 | 17.29 | 0.386514E+09 | 842.96 | 02-SEP-12:09 | 19.50 | 17.29 |
October | 0.155183E+10 | 3006.01 | 12-OCT-07:02 | 6.78 | 3.34 | 0.335613E+09 | 842.89 | 21-OCT-12:00 | 19.60 | 13.32 |
November | 0.596693E+09 | 4926.85 | 13-NOV-19:42 | -2.7 | -3.5 | 0.310356E+09 | 732.76 | 04-NOV-12:00 | -2.7 | -3.5 |
December | 17929430.92 | 5708.36 | 01-DEC-19:12 | -5.9 | -6.7 | 0.316799E+09 | 637.68 | 02-DEC-13:50 | 6.93 | 3.77 |
Annual Sum or Average | 0.238483E+11 | 0.426771E+10 | ||||||||
Minimum of Months | 12746670.00 | 3006.01 | -5.9 | -6.7 | 0.288104E+09 | 637.68 | -2.7 | -3.5 | ||
Maximum of Months | 0.505444E+10 | 16279.45 | 30.00 | 20.65 | 0.431059E+09 | 842.98 | 30.00 | 20.65 |
Report: ZoneCoolingSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 2901460.14 | 1019.63 | 13-JAN-12:00 | 3.90 | 1.50 | 0.108442E+10 | 1700.53 | 07-JAN-15:39 | 3.90 | 1.50 |
February | 24468516.72 | 1998.65 | 25-FEB-12:00 | 3.30 | 1.60 | 0.987309E+09 | 1700.53 | 04-FEB-15:09 | 3.30 | 1.60 |
March | 0.431764E+09 | 9706.50 | 10-MAR-11:23 | -2.0 | -3.7 | 0.112604E+10 | 2033.63 | 25-MAR-14:00 | 18.90 | 10.43 |
April | 0.160913E+10 | 8886.05 | 18-APR-14:40 | 28.30 | 20.65 | 0.113430E+10 | 2247.80 | 15-APR-14:09 | 28.30 | 20.65 |
May | 0.353183E+10 | 9813.03 | 31-MAY-15:00 | 30.00 | 19.70 | 0.133034E+10 | 2247.80 | 27-MAY-14:00 | 30.00 | 19.70 |
June | 0.675050E+10 | 24599.43 | 28-JUN-07:03 | 21.57 | 18.56 | 0.138046E+10 | 2247.80 | 17-JUN-14:09 | 21.57 | 18.56 |
July | 0.804639E+10 | 26416.94 | 03-JUL-07:03 | 20.37 | 18.84 | 0.143681E+10 | 2247.96 | 01-JUL-14:00 | 20.37 | 18.84 |
August | 0.835959E+10 | 22767.89 | 23-AUG-07:03 | 18.40 | 17.24 | 0.147905E+10 | 2247.96 | 05-AUG-14:09 | 18.40 | 17.24 |
September | 0.624360E+10 | 28777.59 | 11-SEP-07:03 | 20.37 | 17.95 | 0.131834E+10 | 2247.96 | 02-SEP-14:20 | 20.37 | 17.95 |
October | 0.215355E+10 | 7045.91 | 16-OCT-09:13 | 3.73 | 1.85 | 0.113727E+10 | 2247.82 | 21-OCT-14:00 | 21.10 | 14.40 |
November | 0.789608E+09 | 4831.26 | 03-NOV-18:00 | 9.40 | 6.17 | 0.105373E+10 | 1996.76 | 04-NOV-14:00 | 14.40 | 6.81 |
December | 4716271.71 | 1545.06 | 02-DEC-12:00 | 5.00 | 2.79 | 0.108625E+10 | 1700.53 | 09-DEC-15:20 | -18.9 | -19.3 |
Annual Sum or Average | 0.379481E+11 | 0.145543E+11 | ||||||||
Minimum of Months | 2901460.14 | 1019.63 | -2.0 | -3.7 | 0.987309E+09 | 1700.53 | -18.9 | -19.3 | ||
Maximum of Months | 0.835959E+10 | 28777.59 | 30.00 | 20.65 | 0.147905E+10 | 2247.96 | 30.00 | 20.65 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 3481408.63 | 4069.67 | 13-JAN-18:23 | 1.40 | 0.18 | 0.542193E+09 | 850.24 | 07-JAN-15:39 | 1.40 | 0.18 |
February | 10217668.00 | 931.49 | 25-FEB-12:00 | 3.30 | 1.60 | 0.493640E+09 | 850.24 | 18-FEB-15:00 | 3.30 | 1.60 |
March | 0.193410E+09 | 4126.59 | 20-MAR-19:12 | 1.13 | -0.6 | 0.562700E+09 | 1006.41 | 25-MAR-14:00 | 18.90 | 10.43 |
April | 0.768556E+09 | 4568.75 | 18-APR-14:50 | 28.30 | 20.65 | 0.566344E+09 | 1123.87 | 15-APR-14:09 | 28.30 | 20.65 |
May | 0.168771E+10 | 5070.54 | 31-MAY-15:00 | 30.00 | 19.70 | 0.661017E+09 | 1123.87 | 27-MAY-14:00 | 30.00 | 19.70 |
June | 0.340972E+10 | 12141.98 | 30-JUN-07:03 | 23.07 | 20.55 | 0.689428E+09 | 1123.87 | 17-JUN-14:09 | 23.07 | 20.55 |
July | 0.410279E+10 | 13523.76 | 03-JUL-07:03 | 20.37 | 18.84 | 0.718340E+09 | 1123.95 | 01-JUL-14:00 | 20.37 | 18.84 |
August | 0.426457E+10 | 11434.79 | 03-AUG-07:02 | 24.18 | 22.74 | 0.739496E+09 | 1123.95 | 05-AUG-14:09 | 26.70 | 18.39 |
September | 0.314638E+10 | 14146.20 | 11-SEP-07:03 | 20.37 | 17.95 | 0.658494E+09 | 1123.95 | 02-SEP-14:20 | 20.37 | 17.95 |
October | 0.100195E+10 | 3531.16 | 13-OCT-09:03 | 3.55 | 1.83 | 0.567674E+09 | 1123.87 | 21-OCT-14:00 | 21.10 | 14.40 |
November | 0.374768E+09 | 4694.70 | 10-NOV-18:23 | -1.4 | -3.1 | 0.526690E+09 | 995.09 | 04-NOV-14:00 | -1.4 | -3.1 |
December | 1920351.15 | 709.95 | 02-DEC-12:00 | 5.00 | 2.79 | 0.543112E+09 | 850.24 | 02-DEC-15:00 | 5.60 | 3.10 |
Annual Sum or Average | 0.189655E+11 | 0.726913E+10 | ||||||||
Minimum of Months | 1920351.15 | 709.95 | -1.4 | -3.1 | 0.493640E+09 | 850.24 | -1.4 | -3.1 | ||
Maximum of Months | 0.426457E+10 | 14146.20 | 30.00 | 22.74 | 0.739496E+09 | 1123.95 | 30.00 | 20.65 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 863181.89 | 415.50 | 13-JAN-12:00 | 3.90 | 1.50 | 0.542193E+09 | 850.24 | 07-JAN-15:50 | 3.90 | 1.50 |
February | 9041967.97 | 877.58 | 25-FEB-12:00 | 3.30 | 1.60 | 0.493640E+09 | 850.24 | 11-FEB-15:39 | 3.30 | 1.60 |
March | 0.181162E+09 | 4980.65 | 21-MAR-18:03 | -2.7 | -5.5 | 0.562433E+09 | 1000.97 | 25-MAR-14:00 | 18.90 | 10.43 |
April | 0.726614E+09 | 4452.73 | 18-APR-14:50 | 28.30 | 20.65 | 0.565569E+09 | 1123.87 | 15-APR-14:09 | 28.30 | 20.65 |
May | 0.160383E+10 | 4969.96 | 31-MAY-15:00 | 30.00 | 19.70 | 0.656301E+09 | 1123.90 | 27-MAY-14:09 | 30.00 | 19.70 |
June | 0.332928E+10 | 12033.66 | 30-JUN-07:03 | 23.07 | 20.55 | 0.688482E+09 | 1123.87 | 17-JUN-14:09 | 23.07 | 20.55 |
July | 0.402963E+10 | 13404.24 | 03-JUL-07:03 | 20.37 | 18.84 | 0.718257E+09 | 1123.95 | 01-JUL-14:00 | 20.37 | 18.84 |
August | 0.419287E+10 | 11335.85 | 03-AUG-07:02 | 24.18 | 22.74 | 0.739467E+09 | 1123.95 | 05-AUG-14:09 | 26.70 | 18.39 |
September | 0.307829E+10 | 13634.96 | 11-SEP-07:03 | 20.37 | 17.95 | 0.657498E+09 | 1123.95 | 02-SEP-14:20 | 20.37 | 17.95 |
October | 0.941825E+09 | 3026.20 | 16-OCT-16:27 | 5.85 | 2.36 | 0.566659E+09 | 1123.87 | 21-OCT-14:00 | 21.10 | 14.40 |
November | 0.353197E+09 | 4012.07 | 16-NOV-19:23 | 1.65 | -0.4 | 0.526401E+09 | 989.16 | 04-NOV-14:00 | 1.65 | -0.4 |
December | 1692963.40 | 670.59 | 02-DEC-12:00 | 5.00 | 2.79 | 0.543112E+09 | 850.24 | 23-DEC-15:30 | -7.0 | -7.6 |
Annual Sum or Average | 0.184483E+11 | 0.726001E+10 | ||||||||
Minimum of Months | 863181.89 | 415.50 | -2.7 | -5.5 | 0.493640E+09 | 850.24 | -7.0 | -7.6 | ||
Maximum of Months | 0.419287E+10 | 13634.96 | 30.00 | 22.74 | 0.739467E+09 | 1123.95 | 30.00 | 20.65 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 160562.54 | 163.71 | 13-JAN-12:00 | 3.90 | 1.50 | 0.542193E+09 | 850.24 | 07-JAN-15:50 | 3.90 | 1.50 |
February | 4023889.73 | 628.60 | 25-FEB-12:00 | 3.30 | 1.60 | 0.493640E+09 | 850.24 | 04-FEB-15:09 | 3.30 | 1.60 |
March | 0.130753E+09 | 3960.41 | 27-MAR-18:43 | 1.65 | 0.18 | 0.561593E+09 | 981.80 | 25-MAR-14:00 | 1.65 | 0.18 |
April | 0.607462E+09 | 4162.32 | 18-APR-14:50 | 28.30 | 20.65 | 0.563287E+09 | 1123.87 | 15-APR-14:09 | 28.30 | 20.65 |
May | 0.140759E+10 | 4745.66 | 31-MAY-15:00 | 30.00 | 19.70 | 0.645672E+09 | 1123.89 | 27-MAY-14:00 | 30.00 | 19.70 |
June | 0.312725E+10 | 11576.74 | 26-JUN-07:03 | 23.58 | 21.51 | 0.686091E+09 | 1123.87 | 17-JUN-14:09 | 23.58 | 21.51 |
July | 0.385335E+10 | 13181.80 | 03-JUL-07:03 | 20.37 | 18.84 | 0.717941E+09 | 1123.95 | 01-JUL-14:00 | 20.37 | 18.84 |
August | 0.402089E+10 | 11159.77 | 03-AUG-07:02 | 24.18 | 22.74 | 0.739350E+09 | 1123.95 | 05-AUG-14:09 | 26.70 | 18.39 |
September | 0.291373E+10 | 11971.05 | 11-SEP-07:03 | 20.37 | 17.95 | 0.655033E+09 | 1123.95 | 02-SEP-14:20 | 20.37 | 17.95 |
October | 0.775183E+09 | 2915.29 | 22-OCT-09:03 | 6.70 | 5.35 | 0.564107E+09 | 1123.85 | 21-OCT-14:30 | 6.70 | 5.35 |
November | 0.291118E+09 | 3832.97 | 16-NOV-18:53 | 2.20 | -0.3 | 0.525708E+09 | 974.41 | 04-NOV-14:00 | 2.20 | -0.3 |
December | 1805184.47 | 3382.45 | 02-DEC-11:13 | 4.27 | 2.22 | 0.543111E+09 | 850.24 | 02-DEC-15:50 | 5.68 | 3.15 |
Annual Sum or Average | 0.171333E+11 | 0.723773E+10 | ||||||||
Minimum of Months | 160562.54 | 163.71 | 1.65 | -0.3 | 0.493640E+09 | 850.24 | 1.65 | -0.3 | ||
Maximum of Months | 0.402089E+10 | 13181.80 | 30.00 | 22.74 | 0.739350E+09 | 1123.95 | 30.00 | 21.51 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | -2.8 | -3.2 | 0.542193E+09 | 850.24 | 07-JAN-15:09 | -16.2 | -17.3 |
February | 3345.05 | 55.75 | 25-FEB-08:04 | 0.10 | -0.7 | 0.493640E+09 | 850.24 | 04-FEB-15:09 | 0.10 | -0.7 |
March | 32073521.27 | 1541.11 | 24-MAR-12:05 | 11.78 | 6.31 | 0.560033E+09 | 920.95 | 25-MAR-14:00 | 18.90 | 10.43 |
April | 0.374539E+09 | 3873.95 | 18-APR-14:30 | 28.30 | 20.65 | 0.558782E+09 | 1123.87 | 15-APR-14:09 | 28.30 | 20.65 |
May | 0.991744E+09 | 4804.03 | 31-MAY-13:00 | 30.00 | 19.70 | 0.629780E+09 | 1123.87 | 06-MAY-14:50 | 30.00 | 19.70 |
June | 0.290867E+10 | 8757.91 | 26-JUN-07:03 | 23.58 | 21.51 | 0.682075E+09 | 1123.87 | 10-JUN-14:09 | 23.58 | 21.51 |
July | 0.376427E+10 | 14837.66 | 04-JUL-08:62 | 22.30 | 19.61 | 0.716995E+09 | 1123.99 | 29-JUL-14:39 | 28.13 | 19.94 |
August | 0.396284E+10 | 11300.83 | 03-AUG-07:02 | 24.18 | 22.74 | 0.738957E+09 | 1123.99 | 05-AUG-14:39 | 26.70 | 18.75 |
September | 0.275835E+10 | 7272.71 | 07-SEP-14:10 | 32.12 | 18.42 | 0.651156E+09 | 1123.97 | 02-SEP-14:00 | 32.12 | 18.42 |
October | 0.438640E+09 | 3791.09 | 13-OCT-18:43 | 1.78 | 0.04 | 0.561144E+09 | 1123.85 | 21-OCT-14:00 | 21.10 | 14.40 |
November | 0.164201E+09 | 2019.79 | 04-NOV-11:00 | 10.60 | 5.26 | 0.524761E+09 | 950.14 | 04-NOV-14:00 | 14.40 | 6.81 |
December | 0.00 | 0.00 | 01-DEC-00:02 | -0.7 | -1.3 | 0.543112E+09 | 850.24 | 02-DEC-15:20 | 5.93 | 3.29 |
Annual Sum or Average | 0.153953E+11 | 0.720263E+10 | ||||||||
Minimum of Months | 0.00 | 0.00 | -2.8 | -3.2 | 0.493640E+09 | 850.24 | -16.2 | -17.3 | ||
Maximum of Months | 0.396284E+10 | 14837.66 | 32.12 | 22.74 | 0.738957E+09 | 1123.99 | 32.12 | 21.51 |
Report: ZoneHeatingSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.150906E+11 | 65014.70 | 20-JAN-08:12 | -22.8 |
February | 0.100509E+11 | 65498.38 | 02-FEB-00:42 | -33.7 |
March | 0.572142E+10 | 64683.49 | 06-MAR-08:61 | -11.8 |
April | 0.242822E+10 | 64672.00 | 04-APR-07:01 | -4.8 |
May | 0.158473E+09 | 64631.74 | 03-MAY-07:01 | 5.65 |
June | 39074305.53 | 8445.87 | 03-JUN-07:02 | 7.38 |
July | 21609407.36 | 1499.58 | 05-JUL-07:05 | 20.78 |
August | 19842793.97 | 1423.53 | 23-AUG-07:05 | 18.40 |
September | 0.103875E+09 | 64631.70 | 30-SEP-07:01 | 0.97 |
October | 0.467205E+09 | 64652.47 | 28-OCT-07:01 | 0.05 |
November | 0.506895E+10 | 64733.30 | 26-NOV-08:61 | -25.2 |
December | 0.109915E+11 | 64861.81 | 12-DEC-08:12 | -19.2 |
Annual Sum or Average | 0.501617E+11 | |||
Minimum of Months | 19842793.97 | 1423.53 | -33.7 | |
Maximum of Months | 0.150906E+11 | 65498.38 | 20.78 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.545582E+10 | 33628.37 | 06-JAN-08:61 | -28.1 |
February | 0.346086E+10 | 33757.00 | 02-FEB-08:12 | -36.3 |
March | 0.170381E+10 | 33586.64 | 15-MAR-07:01 | -6.7 |
April | 0.624062E+09 | 33590.35 | 04-APR-07:01 | -4.8 |
May | 44727181.28 | 30679.38 | 02-MAY-07:01 | 2.98 |
June | 18128199.45 | 928.38 | 26-JUN-07:05 | 23.58 |
July | 13172239.92 | 922.58 | 05-JUL-07:05 | 20.78 |
August | 12040201.02 | 915.49 | 23-AUG-07:05 | 18.40 |
September | 30894190.73 | 29225.37 | 30-SEP-07:01 | 0.97 |
October | 81346740.28 | 33557.09 | 27-OCT-07:01 | 1.73 |
November | 0.168409E+10 | 33596.99 | 26-NOV-08:61 | -25.2 |
December | 0.387930E+10 | 33609.64 | 12-DEC-08:61 | -19.3 |
Annual Sum or Average | 0.170083E+11 | |||
Minimum of Months | 12040201.02 | 915.49 | -36.3 | |
Maximum of Months | 0.545582E+10 | 33757.00 | 23.58 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.613530E+10 | 33697.99 | 30-JAN-07:01 | -29.0 |
February | 0.395582E+10 | 33703.05 | 02-FEB-07:01 | -36.7 |
March | 0.204572E+10 | 33648.99 | 08-MAR-07:01 | -11.3 |
April | 0.797007E+09 | 33658.93 | 04-APR-06:01 | -5.5 |
May | 52854524.34 | 25595.82 | 02-MAY-06:02 | 2.30 |
June | 44874663.55 | 2233.09 | 11-JUN-16:02 | 32.62 |
July | 29329596.02 | 1474.27 | 02-JUL-16:02 | 29.32 |
August | 18910134.07 | 971.25 | 27-AUG-16:03 | 27.20 |
September | 42691697.80 | 19150.53 | 30-SEP-06:02 | 0.60 |
October | 0.137869E+09 | 26754.34 | 08-OCT-07:02 | 2.43 |
November | 0.206108E+10 | 33685.94 | 26-NOV-08:61 | -25.2 |
December | 0.445019E+10 | 33691.21 | 11-DEC-07:01 | -21.7 |
Annual Sum or Average | 0.197716E+11 | |||
Minimum of Months | 18910134.07 | 971.25 | -36.7 | |
Maximum of Months | 0.613530E+10 | 33703.05 | 32.62 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.641682E+10 | 34347.11 | 30-JAN-07:01 | -29.0 |
February | 0.417085E+10 | 34369.41 | 04-FEB-07:01 | -31.0 |
March | 0.219783E+10 | 34286.79 | 08-MAR-07:01 | -11.3 |
April | 0.884422E+09 | 34296.91 | 04-APR-06:01 | -5.5 |
May | 59803017.09 | 30142.94 | 02-MAY-06:02 | 2.30 |
June | 44919670.39 | 2235.38 | 11-JUN-16:02 | 32.62 |
July | 29229052.32 | 1475.04 | 02-JUL-16:02 | 29.32 |
August | 18949931.55 | 973.74 | 27-AUG-16:03 | 27.20 |
September | 46832473.07 | 22022.37 | 30-SEP-06:02 | 0.60 |
October | 0.176407E+09 | 31246.75 | 08-OCT-07:02 | 2.43 |
November | 0.221749E+10 | 34324.04 | 26-NOV-08:61 | -25.2 |
December | 0.469713E+10 | 34372.11 | 10-DEC-08:61 | -21.2 |
Annual Sum or Average | 0.209607E+11 | |||
Minimum of Months | 18949931.55 | 973.74 | -31.0 | |
Maximum of Months | 0.641682E+10 | 34372.11 | 32.62 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.686318E+10 | 33692.70 | 30-JAN-07:12 | -29.1 |
February | 0.451308E+10 | 33564.54 | 02-FEB-07:01 | -36.7 |
March | 0.247859E+10 | 33465.68 | 08-MAR-07:01 | -11.3 |
April | 0.103761E+10 | 33475.66 | 04-APR-06:01 | -5.5 |
May | 71848371.45 | 32724.62 | 02-MAY-06:02 | 2.30 |
June | 45495812.26 | 2241.29 | 11-JUN-16:02 | 32.62 |
July | 29443267.33 | 1478.96 | 02-JUL-16:02 | 29.32 |
August | 18552276.20 | 979.68 | 27-AUG-16:03 | 27.20 |
September | 53213589.03 | 25266.53 | 30-SEP-06:02 | 0.60 |
October | 0.225064E+09 | 32740.65 | 08-OCT-07:02 | 2.43 |
November | 0.246809E+10 | 33502.29 | 26-NOV-08:61 | -25.2 |
December | 0.509560E+10 | 33561.11 | 10-DEC-08:61 | -21.2 |
Annual Sum or Average | 0.228998E+11 | |||
Minimum of Months | 18552276.20 | 979.68 | -36.7 | |
Maximum of Months | 0.686318E+10 | 33692.70 | 32.62 |
Report: ZoneHeatingSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.136476E+11 | 63042.76 | 30-JAN-08:12 | -29.2 |
February | 0.907131E+10 | 63095.36 | 02-FEB-08:12 | -36.3 |
March | 0.513176E+10 | 62770.95 | 06-MAR-08:61 | -11.8 |
April | 0.216515E+10 | 62695.33 | 04-APR-07:01 | -4.8 |
May | 0.148867E+09 | 62655.11 | 02-MAY-07:01 | 2.98 |
June | 79670978.75 | 10714.90 | 05-JUN-07:01 | 9.50 |
July | 42898746.77 | 2950.41 | 02-JUL-16:02 | 29.32 |
August | 28287192.95 | 1960.95 | 27-AUG-16:03 | 27.20 |
September | 0.111233E+09 | 62654.39 | 30-SEP-07:01 | 0.97 |
October | 0.528040E+09 | 62673.35 | 23-OCT-07:01 | -1.2 |
November | 0.505686E+10 | 62725.66 | 26-NOV-09:01 | -22.7 |
December | 0.103409E+11 | 62964.35 | 12-DEC-08:12 | -19.2 |
Annual Sum or Average | 0.463525E+11 | |||
Minimum of Months | 28287192.95 | 1960.95 | -36.3 | |
Maximum of Months | 0.136476E+11 | 63095.36 | 29.32 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.744991E+10 | 32100.22 | 30-JAN-08:12 | -29.2 |
February | 0.501675E+10 | 32124.77 | 02-FEB-08:12 | -36.3 |
March | 0.291920E+10 | 31854.98 | 06-MAR-08:61 | -11.8 |
April | 0.127392E+10 | 31843.91 | 04-APR-07:01 | -4.8 |
May | 90883922.92 | 31821.62 | 03-MAY-07:01 | 5.65 |
June | 43098314.64 | 7897.08 | 05-JUN-07:01 | 9.50 |
July | 22607732.19 | 1488.08 | 02-JUL-16:02 | 29.32 |
August | 15336744.49 | 993.64 | 27-AUG-16:03 | 27.20 |
September | 62954319.58 | 31822.16 | 30-SEP-07:01 | 0.97 |
October | 0.325326E+09 | 31832.11 | 23-OCT-07:01 | -1.2 |
November | 0.284676E+10 | 31861.46 | 26-NOV-09:01 | -22.7 |
December | 0.568989E+10 | 32039.24 | 12-DEC-08:12 | -19.2 |
Annual Sum or Average | 0.257566E+11 | |||
Minimum of Months | 15336744.49 | 993.64 | -36.3 | |
Maximum of Months | 0.744991E+10 | 32124.77 | 29.32 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.751464E+10 | 31955.54 | 30-JAN-08:12 | -29.2 |
February | 0.508287E+10 | 31979.75 | 02-FEB-08:12 | -36.3 |
March | 0.299802E+10 | 31736.45 | 06-MAR-08:61 | -11.8 |
April | 0.133306E+10 | 31695.93 | 04-APR-07:01 | -4.8 |
May | 99211190.71 | 31673.74 | 02-MAY-07:01 | 2.98 |
June | 45451274.21 | 11711.16 | 05-JUN-07:01 | 9.50 |
July | 22931471.40 | 1489.07 | 02-JUL-16:02 | 29.32 |
August | 15858532.44 | 994.83 | 27-AUG-16:03 | 27.20 |
September | 64930891.72 | 31674.57 | 30-SEP-07:01 | 0.97 |
October | 0.350564E+09 | 31684.40 | 23-OCT-07:01 | -1.2 |
November | 0.290710E+10 | 31713.64 | 26-NOV-09:01 | -22.7 |
December | 0.576030E+10 | 31896.39 | 12-DEC-08:12 | -19.2 |
Annual Sum or Average | 0.261949E+11 | |||
Minimum of Months | 15858532.44 | 994.83 | -36.3 | |
Maximum of Months | 0.751464E+10 | 31979.75 | 29.32 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.798723E+10 | 31766.66 | 30-JAN-08:12 | -29.2 |
February | 0.552767E+10 | 31792.97 | 02-FEB-08:12 | -36.3 |
March | 0.341038E+10 | 31508.70 | 06-MAR-08:61 | -11.8 |
April | 0.161998E+10 | 31489.12 | 04-APR-07:01 | -4.8 |
May | 0.142736E+09 | 31467.72 | 03-MAY-07:01 | 5.65 |
June | 58420197.24 | 22136.83 | 05-JUN-07:01 | 9.50 |
July | 25584229.53 | 1491.66 | 02-JUL-16:02 | 29.32 |
August | 18345931.35 | 999.26 | 27-AUG-16:03 | 27.20 |
September | 81763023.01 | 31466.47 | 30-SEP-07:01 | 0.97 |
October | 0.475104E+09 | 31476.82 | 23-OCT-07:01 | -1.2 |
November | 0.321884E+10 | 31510.53 | 26-NOV-09:01 | -22.7 |
December | 0.622278E+10 | 31700.83 | 12-DEC-08:12 | -19.2 |
Annual Sum or Average | 0.287888E+11 | |||
Minimum of Months | 18345931.35 | 999.26 | -36.3 | |
Maximum of Months | 0.798723E+10 | 31792.97 | 29.32 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.124936E+11 | 36811.88 | 19-JAN-01:11 | -22.4 |
February | 0.892944E+10 | 36614.14 | 02-FEB-08:12 | -36.3 |
March | 0.596250E+10 | 36348.06 | 06-MAR-08:61 | -11.8 |
April | 0.311845E+10 | 36174.91 | 04-APR-07:01 | -4.8 |
May | 0.395883E+09 | 36066.65 | 03-MAY-07:01 | 5.65 |
June | 0.137434E+09 | 35467.06 | 05-JUN-07:01 | 9.50 |
July | 34723392.37 | 1522.71 | 02-JUL-16:02 | 29.32 |
August | 33598353.30 | 1037.37 | 27-AUG-16:03 | 27.20 |
September | 0.184047E+09 | 36063.10 | 30-SEP-07:01 | 0.97 |
October | 0.105505E+10 | 36079.37 | 28-OCT-07:01 | 0.05 |
November | 0.515563E+10 | 36215.18 | 26-NOV-09:01 | -22.7 |
December | 0.960052E+10 | 36442.44 | 09-DEC-05:12 | -22.8 |
Annual Sum or Average | 0.471009E+11 | |||
Minimum of Months | 33598353.30 | 1037.37 | -36.3 | |
Maximum of Months | 0.124936E+11 | 36811.88 | 29.32 |
Report: ZoneElectricSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.739462E+10 | 4621.63 | 01-JAN-10:09 | 0.222596E+10 | 1343.25 | 01-JAN-10:09 |
February | 0.668410E+10 | 4621.63 | 01-FEB-10:09 | 0.201408E+10 | 1343.25 | 01-FEB-10:09 |
March | 0.740180E+10 | 4621.63 | 01-MAR-10:09 | 0.223295E+10 | 1343.25 | 01-MAR-10:09 |
April | 0.716384E+10 | 4621.63 | 01-APR-09:09 | 0.215748E+10 | 1343.25 | 01-APR-09:09 |
May | 0.739462E+10 | 4621.63 | 01-MAY-09:09 | 0.222596E+10 | 1343.25 | 01-MAY-09:09 |
June | 0.716485E+10 | 4621.63 | 01-JUN-09:09 | 0.216232E+10 | 1343.25 | 01-JUN-09:09 |
July | 0.740069E+10 | 4621.63 | 01-JUL-09:09 | 0.222811E+10 | 1343.25 | 01-JUL-09:09 |
August | 0.739513E+10 | 4621.63 | 01-AUG-09:09 | 0.222838E+10 | 1343.25 | 01-AUG-09:09 |
September | 0.717041E+10 | 4621.63 | 01-SEP-09:09 | 0.216205E+10 | 1343.25 | 01-SEP-09:09 |
October | 0.739462E+10 | 4621.63 | 01-OCT-09:09 | 0.222596E+10 | 1343.25 | 01-OCT-09:09 |
November | 0.714323E+10 | 4621.63 | 01-NOV-09:09 | 0.215077E+10 | 1343.25 | 01-NOV-09:09 |
December | 0.740776E+10 | 4621.63 | 01-DEC-10:09 | 0.223509E+10 | 1343.25 | 01-DEC-10:09 |
Annual Sum or Average | 0.871157E+11 | 0.262491E+11 | ||||
Minimum of Months | 0.668410E+10 | 4621.63 | 0.201408E+10 | 1343.25 | ||
Maximum of Months | 0.740776E+10 | 4621.63 | 0.223509E+10 | 1343.25 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.451584E+10 | 2827.07 | 01-JAN-10:09 | 0.111298E+10 | 671.63 | 01-JAN-10:09 |
February | 0.408193E+10 | 2827.07 | 01-FEB-10:09 | 0.100704E+10 | 671.63 | 01-FEB-10:09 |
March | 0.452026E+10 | 2827.07 | 01-MAR-10:09 | 0.111647E+10 | 671.63 | 01-MAR-10:09 |
April | 0.437489E+10 | 2827.07 | 01-APR-09:09 | 0.107874E+10 | 671.63 | 01-APR-09:09 |
May | 0.451584E+10 | 2827.07 | 01-MAY-09:09 | 0.111298E+10 | 671.63 | 01-MAY-09:09 |
June | 0.437556E+10 | 2827.07 | 01-JUN-09:09 | 0.108116E+10 | 671.63 | 01-JUN-09:09 |
July | 0.451952E+10 | 2827.07 | 01-JUL-09:09 | 0.111405E+10 | 671.63 | 01-JUL-09:09 |
August | 0.451617E+10 | 2827.07 | 01-AUG-09:09 | 0.111419E+10 | 671.63 | 01-AUG-09:09 |
September | 0.437891E+10 | 2827.07 | 01-SEP-09:09 | 0.108102E+10 | 671.63 | 01-SEP-09:09 |
October | 0.451584E+10 | 2827.07 | 01-OCT-09:09 | 0.111298E+10 | 671.63 | 01-OCT-09:09 |
November | 0.436230E+10 | 2827.07 | 01-NOV-09:09 | 0.107538E+10 | 671.63 | 01-NOV-09:09 |
December | 0.452388E+10 | 2827.07 | 01-DEC-10:09 | 0.111755E+10 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.532009E+11 | 0.131245E+11 | ||||
Minimum of Months | 0.408193E+10 | 2827.07 | 0.100704E+10 | 671.63 | ||
Maximum of Months | 0.452388E+10 | 2827.07 | 0.111755E+10 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.317044E+10 | 2555.22 | 01-JAN-10:09 | 0.879849E+09 | 671.63 | 01-JAN-10:09 |
February | 0.287181E+10 | 2555.22 | 01-FEB-09:09 | 0.796766E+09 | 671.63 | 01-FEB-09:09 |
March | 0.324295E+10 | 2555.22 | 01-MAR-09:09 | 0.898128E+09 | 671.63 | 01-MAR-09:09 |
April | 0.307694E+10 | 2555.22 | 01-APR-08:09 | 0.853677E+09 | 671.63 | 01-APR-08:09 |
May | 0.320669E+10 | 2555.22 | 01-MAY-08:09 | 0.888989E+09 | 671.63 | 01-MAY-08:09 |
June | 0.313132E+10 | 2555.22 | 01-JUN-08:09 | 0.867387E+09 | 671.63 | 01-JUN-08:09 |
July | 0.315231E+10 | 2555.22 | 01-JUL-08:09 | 0.875279E+09 | 671.63 | 01-JUL-08:09 |
August | 0.324295E+10 | 2555.22 | 01-AUG-08:09 | 0.898128E+09 | 671.63 | 01-AUG-08:09 |
September | 0.307694E+10 | 2555.22 | 01-SEP-08:09 | 0.853677E+09 | 671.63 | 01-SEP-08:09 |
October | 0.317044E+10 | 2555.22 | 01-OCT-09:09 | 0.879849E+09 | 671.63 | 01-OCT-09:09 |
November | 0.307694E+10 | 2555.22 | 01-NOV-08:09 | 0.853679E+09 | 671.63 | 01-NOV-08:09 |
December | 0.315231E+10 | 2555.22 | 01-DEC-09:09 | 0.875279E+09 | 671.63 | 01-DEC-09:09 |
Annual Sum or Average | 0.375720E+11 | 0.104207E+11 | ||||
Minimum of Months | 0.287181E+10 | 2555.22 | 0.796766E+09 | 671.63 | ||
Maximum of Months | 0.324295E+10 | 2555.22 | 0.898128E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.317044E+10 | 2555.22 | 01-JAN-10:09 | 0.879849E+09 | 671.63 | 01-JAN-10:09 |
February | 0.287181E+10 | 2555.22 | 01-FEB-09:09 | 0.796766E+09 | 671.63 | 01-FEB-09:09 |
March | 0.324295E+10 | 2555.22 | 01-MAR-09:09 | 0.898128E+09 | 671.63 | 01-MAR-09:09 |
April | 0.307694E+10 | 2555.22 | 01-APR-08:09 | 0.853677E+09 | 671.63 | 01-APR-08:09 |
May | 0.320669E+10 | 2555.22 | 01-MAY-08:09 | 0.888989E+09 | 671.63 | 01-MAY-08:09 |
June | 0.313132E+10 | 2555.22 | 01-JUN-08:09 | 0.867387E+09 | 671.63 | 01-JUN-08:09 |
July | 0.315231E+10 | 2555.22 | 01-JUL-08:09 | 0.875279E+09 | 671.63 | 01-JUL-08:09 |
August | 0.324295E+10 | 2555.22 | 01-AUG-08:09 | 0.898128E+09 | 671.63 | 01-AUG-08:09 |
September | 0.307694E+10 | 2555.22 | 01-SEP-08:09 | 0.853677E+09 | 671.63 | 01-SEP-08:09 |
October | 0.317044E+10 | 2555.22 | 01-OCT-09:09 | 0.879849E+09 | 671.63 | 01-OCT-09:09 |
November | 0.307694E+10 | 2555.22 | 01-NOV-08:09 | 0.853679E+09 | 671.63 | 01-NOV-08:09 |
December | 0.315231E+10 | 2555.22 | 01-DEC-09:09 | 0.875279E+09 | 671.63 | 01-DEC-09:09 |
Annual Sum or Average | 0.375720E+11 | 0.104207E+11 | ||||
Minimum of Months | 0.287181E+10 | 2555.22 | 0.796766E+09 | 671.63 | ||
Maximum of Months | 0.324295E+10 | 2555.22 | 0.898128E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.317044E+10 | 2555.22 | 01-JAN-10:09 | 0.879849E+09 | 671.63 | 01-JAN-10:09 |
February | 0.287181E+10 | 2555.22 | 01-FEB-09:09 | 0.796766E+09 | 671.63 | 01-FEB-09:09 |
March | 0.324295E+10 | 2555.22 | 01-MAR-09:09 | 0.898128E+09 | 671.63 | 01-MAR-09:09 |
April | 0.307694E+10 | 2555.22 | 01-APR-08:09 | 0.853677E+09 | 671.63 | 01-APR-08:09 |
May | 0.320669E+10 | 2555.22 | 01-MAY-08:09 | 0.888989E+09 | 671.63 | 01-MAY-08:09 |
June | 0.313132E+10 | 2555.22 | 01-JUN-08:09 | 0.867387E+09 | 671.63 | 01-JUN-08:09 |
July | 0.315231E+10 | 2555.22 | 01-JUL-08:09 | 0.875279E+09 | 671.63 | 01-JUL-08:09 |
August | 0.324295E+10 | 2555.22 | 01-AUG-08:09 | 0.898128E+09 | 671.63 | 01-AUG-08:09 |
September | 0.307694E+10 | 2555.22 | 01-SEP-08:09 | 0.853677E+09 | 671.63 | 01-SEP-08:09 |
October | 0.317044E+10 | 2555.22 | 01-OCT-09:09 | 0.879849E+09 | 671.63 | 01-OCT-09:09 |
November | 0.307694E+10 | 2555.22 | 01-NOV-08:09 | 0.853679E+09 | 671.63 | 01-NOV-08:09 |
December | 0.315231E+10 | 2555.22 | 01-DEC-09:09 | 0.875279E+09 | 671.63 | 01-DEC-09:09 |
Annual Sum or Average | 0.375720E+11 | 0.104207E+11 | ||||
Minimum of Months | 0.287181E+10 | 2555.22 | 0.796766E+09 | 671.63 | ||
Maximum of Months | 0.324295E+10 | 2555.22 | 0.898128E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.313454E+10 | 2726.96 | 01-JAN-11:09 | 0.161799E+10 | 1343.25 | 01-JAN-11:09 |
February | 0.283982E+10 | 2726.96 | 01-FEB-10:09 | 0.146554E+10 | 1343.25 | 01-FEB-10:09 |
March | 0.321092E+10 | 2726.96 | 01-MAR-10:09 | 0.165455E+10 | 1343.25 | 01-MAR-10:09 |
April | 0.304266E+10 | 2726.96 | 01-APR-09:09 | 0.157022E+10 | 1343.25 | 01-APR-09:09 |
May | 0.317273E+10 | 2726.96 | 01-MAY-09:09 | 0.163627E+10 | 1343.25 | 01-MAY-09:09 |
June | 0.309995E+10 | 2726.96 | 01-JUN-09:09 | 0.159764E+10 | 1343.25 | 01-JUN-09:09 |
July | 0.311545E+10 | 2726.96 | 01-JUL-09:09 | 0.160885E+10 | 1343.25 | 01-JUL-09:09 |
August | 0.321092E+10 | 2726.96 | 01-AUG-09:09 | 0.165455E+10 | 1343.25 | 01-AUG-09:09 |
September | 0.304266E+10 | 2726.96 | 01-SEP-09:09 | 0.157022E+10 | 1343.25 | 01-SEP-09:09 |
October | 0.313454E+10 | 2726.96 | 01-OCT-10:09 | 0.161799E+10 | 1343.25 | 01-OCT-10:09 |
November | 0.304266E+10 | 2726.96 | 01-NOV-09:09 | 0.157022E+10 | 1343.25 | 01-NOV-09:09 |
December | 0.311545E+10 | 2726.96 | 01-DEC-10:09 | 0.160885E+10 | 1343.25 | 01-DEC-10:09 |
Annual Sum or Average | 0.371623E+11 | 0.191729E+11 | ||||
Minimum of Months | 0.283982E+10 | 2726.96 | 0.146554E+10 | 1343.25 | ||
Maximum of Months | 0.321092E+10 | 2726.96 | 0.165455E+10 | 1343.25 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.161274E+10 | 1404.46 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.146111E+10 | 1404.46 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.165211E+10 | 1404.46 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.156548E+10 | 1404.46 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.163243E+10 | 1404.46 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.159501E+10 | 1404.46 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.160290E+10 | 1404.46 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.165211E+10 | 1404.46 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.156548E+10 | 1404.46 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.161274E+10 | 1404.46 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.156548E+10 | 1404.46 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.160290E+10 | 1404.46 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.191205E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.146111E+10 | 1404.46 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.165211E+10 | 1404.46 | 0.827277E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.161274E+10 | 1404.46 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.146111E+10 | 1404.46 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.165211E+10 | 1404.46 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.156548E+10 | 1404.46 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.163243E+10 | 1404.46 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.159501E+10 | 1404.46 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.160290E+10 | 1404.46 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.165211E+10 | 1404.46 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.156548E+10 | 1404.46 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.161274E+10 | 1404.46 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.156548E+10 | 1404.46 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.160290E+10 | 1404.46 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.191205E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.146111E+10 | 1404.46 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.165211E+10 | 1404.46 | 0.827277E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.161274E+10 | 1404.46 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.146111E+10 | 1404.46 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.165211E+10 | 1404.46 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.156548E+10 | 1404.46 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.163243E+10 | 1404.46 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.159501E+10 | 1404.46 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.160290E+10 | 1404.46 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.165211E+10 | 1404.46 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.156548E+10 | 1404.46 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.161274E+10 | 1404.46 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.156548E+10 | 1404.46 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.160290E+10 | 1404.46 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.191205E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.146111E+10 | 1404.46 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.165211E+10 | 1404.46 | 0.827277E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.161274E+10 | 1404.46 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.146111E+10 | 1404.46 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.165211E+10 | 1404.46 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.156548E+10 | 1404.46 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.163243E+10 | 1404.46 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.159501E+10 | 1404.46 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.160290E+10 | 1404.46 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.165211E+10 | 1404.46 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.156548E+10 | 1404.46 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.161274E+10 | 1404.46 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.156548E+10 | 1404.46 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.160290E+10 | 1404.46 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.191205E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.146111E+10 | 1404.46 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.165211E+10 | 1404.46 | 0.827277E+09 | 671.63 |
Report: SpaceGainsMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.338624E+10 | 0.739462E+10 | 0.222596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108708E+11 |
February | 0.305697E+10 | 0.668410E+10 | 0.201408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.815203E+10 |
March | 0.335708E+10 | 0.740180E+10 | 0.223295E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.620391E+10 |
April | 0.327081E+10 | 0.716384E+10 | 0.215748E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 80398470.67 | 0.393042E+10 |
May | 0.336680E+10 | 0.739462E+10 | 0.222596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 68080003.00 | 0.191365E+10 |
June | 0.325380E+10 | 0.716485E+10 | 0.216232E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.419131E+09 | 0.975618E+09 |
July | 0.339353E+10 | 0.740069E+10 | 0.222811E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.343176E+09 | 0.525296E+09 |
August | 0.334857E+10 | 0.739513E+10 | 0.222838E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.370733E+09 | 0.688719E+09 |
September | 0.327932E+10 | 0.717041E+10 | 0.216205E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.279427E+09 | 0.164220E+10 |
October | 0.338624E+10 | 0.739462E+10 | 0.222596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.358413E+10 |
November | 0.327446E+10 | 0.714323E+10 | 0.215077E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.633453E+10 |
December | 0.340325E+10 | 0.740776E+10 | 0.223509E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.911748E+10 |
Annual Sum or Average | 0.397770E+11 | 0.871157E+11 | 0.262491E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156095E+10 | 0.539388E+11 |
Minimum of Months | 0.305697E+10 | 0.668410E+10 | 0.201408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.525296E+09 |
Maximum of Months | 0.340325E+10 | 0.740776E+10 | 0.223509E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.419131E+09 | 0.108708E+11 |
Report: SpaceGainsMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.169307E+10 | 0.451584E+10 | 0.111298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.521776E+10 |
February | 0.152844E+10 | 0.408193E+10 | 0.100704E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.391598E+10 |
March | 0.167849E+10 | 0.452026E+10 | 0.111647E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.292871E+10 |
April | 0.163536E+10 | 0.437489E+10 | 0.107874E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41837974.32 | 0.188476E+10 |
May | 0.168335E+10 | 0.451584E+10 | 0.111298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36598189.84 | 0.931567E+09 |
June | 0.162685E+10 | 0.437556E+10 | 0.108116E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.223235E+09 | 0.452678E+09 |
July | 0.169671E+10 | 0.451952E+10 | 0.111405E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185663E+09 | 0.213728E+09 |
August | 0.167424E+10 | 0.451617E+10 | 0.111419E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.199826E+09 | 0.268512E+09 |
September | 0.163961E+10 | 0.437891E+10 | 0.108102E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150760E+09 | 0.757773E+09 |
October | 0.169307E+10 | 0.451584E+10 | 0.111298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171816E+10 |
November | 0.163718E+10 | 0.436230E+10 | 0.107538E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.301185E+10 |
December | 0.170157E+10 | 0.452388E+10 | 0.111755E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.435766E+10 |
Annual Sum or Average | 0.198880E+11 | 0.532009E+11 | 0.131245E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.837920E+09 | 0.256591E+11 |
Minimum of Months | 0.152844E+10 | 0.408193E+10 | 0.100704E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.213728E+09 |
Maximum of Months | 0.170157E+10 | 0.452388E+10 | 0.111755E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.223235E+09 | 0.521776E+10 |
Report: SpaceGainsMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.317044E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.538244E+10 |
February | 0.914877E+09 | 0.287181E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.404768E+10 |
March | 0.103395E+10 | 0.324295E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.301376E+10 |
April | 0.984131E+09 | 0.307694E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 39746437.83 | 0.192968E+10 |
May | 0.102058E+10 | 0.320669E+10 | 0.888989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 36583574.34 | 0.958266E+09 |
June | 0.998711E+09 | 0.313132E+10 | 0.867387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.216994E+09 | 0.468824E+09 |
July | 0.100600E+10 | 0.315231E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178848E+09 | 0.237039E+09 |
August | 0.103395E+10 | 0.324295E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.196795E+09 | 0.300453E+09 |
September | 0.984131E+09 | 0.307694E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147692E+09 | 0.792282E+09 |
October | 0.100722E+10 | 0.317044E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175012E+10 |
November | 0.973196E+09 | 0.307694E+10 | 0.853679E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.310492E+10 |
December | 0.100600E+10 | 0.315231E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.449794E+10 |
Annual Sum or Average | 0.119700E+11 | 0.375720E+11 | 0.104207E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.816660E+09 | 0.264834E+11 |
Minimum of Months | 0.914877E+09 | 0.287181E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.237039E+09 |
Maximum of Months | 0.103395E+10 | 0.324295E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.216994E+09 | 0.538244E+10 |
Report: SpaceGainsMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.317044E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.537475E+10 |
February | 0.914877E+09 | 0.287181E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.404131E+10 |
March | 0.103395E+10 | 0.324295E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.300521E+10 |
April | 0.984131E+09 | 0.307694E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 39805632.78 | 0.192129E+10 |
May | 0.102058E+10 | 0.320669E+10 | 0.888989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 36583737.53 | 0.947719E+09 |
June | 0.998711E+09 | 0.313132E+10 | 0.867387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.216945E+09 | 0.465641E+09 |
July | 0.100600E+10 | 0.315231E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178826E+09 | 0.237028E+09 |
August | 0.103395E+10 | 0.324295E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.196802E+09 | 0.300240E+09 |
September | 0.984131E+09 | 0.307694E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147695E+09 | 0.787895E+09 |
October | 0.100722E+10 | 0.317044E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.173627E+10 |
November | 0.973196E+09 | 0.307694E+10 | 0.853679E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.309348E+10 |
December | 0.100600E+10 | 0.315231E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.449094E+10 |
Annual Sum or Average | 0.119700E+11 | 0.375720E+11 | 0.104207E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.816658E+09 | 0.264018E+11 |
Minimum of Months | 0.914877E+09 | 0.287181E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.237028E+09 |
Maximum of Months | 0.103395E+10 | 0.324295E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.216945E+09 | 0.537475E+10 |
Report: SpaceGainsMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.317044E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.536900E+10 |
February | 0.914877E+09 | 0.287181E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.403631E+10 |
March | 0.103395E+10 | 0.324295E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.299665E+10 |
April | 0.984131E+09 | 0.307694E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 39962668.48 | 0.191108E+10 |
May | 0.102058E+10 | 0.320669E+10 | 0.888989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 36584008.21 | 0.927454E+09 |
June | 0.998711E+09 | 0.313132E+10 | 0.867387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.217176E+09 | 0.458547E+09 |
July | 0.100600E+10 | 0.315231E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178950E+09 | 0.234645E+09 |
August | 0.103395E+10 | 0.324295E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.196840E+09 | 0.297656E+09 |
September | 0.984131E+09 | 0.307694E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147719E+09 | 0.779317E+09 |
October | 0.100722E+10 | 0.317044E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172259E+10 |
November | 0.973196E+09 | 0.307694E+10 | 0.853679E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.308319E+10 |
December | 0.100600E+10 | 0.315231E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.448534E+10 |
Annual Sum or Average | 0.119700E+11 | 0.375720E+11 | 0.104207E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.817232E+09 | 0.263018E+11 |
Minimum of Months | 0.914877E+09 | 0.287181E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.234645E+09 |
Maximum of Months | 0.103395E+10 | 0.324295E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.217176E+09 | 0.536900E+10 |
Report: SpaceGainsMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.344359E+10 | 0.313454E+10 | 0.161799E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.992516E+10 |
February | 0.313522E+10 | 0.283982E+10 | 0.146554E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.745498E+10 |
March | 0.355148E+10 | 0.321092E+10 | 0.165455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.555603E+10 |
April | 0.338259E+10 | 0.304266E+10 | 0.157022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 72997302.32 | 0.352733E+10 |
May | 0.349753E+10 | 0.317273E+10 | 0.163627E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 65920721.45 | 0.167212E+10 |
June | 0.343071E+10 | 0.309995E+10 | 0.159764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.393143E+09 | 0.847418E+09 |
July | 0.344942E+10 | 0.311545E+10 | 0.160885E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.323106E+09 | 0.446626E+09 |
August | 0.355148E+10 | 0.321092E+10 | 0.165455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.354780E+09 | 0.574505E+09 |
September | 0.338259E+10 | 0.304266E+10 | 0.157022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.266144E+09 | 0.144681E+10 |
October | 0.344359E+10 | 0.313454E+10 | 0.161799E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.318330E+10 |
November | 0.331698E+10 | 0.304266E+10 | 0.157022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.570640E+10 |
December | 0.344942E+10 | 0.311545E+10 | 0.160885E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.830050E+10 |
Annual Sum or Average | 0.410346E+11 | 0.371623E+11 | 0.191729E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147609E+10 | 0.486412E+11 |
Minimum of Months | 0.313522E+10 | 0.283982E+10 | 0.146554E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.446626E+09 |
Maximum of Months | 0.355148E+10 | 0.321092E+10 | 0.165455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.393143E+09 | 0.992516E+10 |
Report: SpaceGainsMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.161274E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.540840E+10 |
February | 0.156756E+10 | 0.146111E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.406132E+10 |
March | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.301537E+10 |
April | 0.169125E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 40453602.12 | 0.191362E+10 |
May | 0.174872E+10 | 0.163243E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 36599842.70 | 0.893598E+09 |
June | 0.171530E+10 | 0.159501E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.218151E+09 | 0.452296E+09 |
July | 0.172466E+10 | 0.160290E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179688E+09 | 0.235094E+09 |
August | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.197063E+09 | 0.300568E+09 |
September | 0.169125E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147859E+09 | 0.775866E+09 |
October | 0.172174E+10 | 0.161274E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172258E+10 |
November | 0.165844E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.309879E+10 |
December | 0.172466E+10 | 0.160290E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.451867E+10 |
Annual Sum or Average | 0.205167E+11 | 0.191205E+11 | 0.958644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.819815E+09 | 0.263962E+11 |
Minimum of Months | 0.156756E+10 | 0.146111E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235094E+09 |
Maximum of Months | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.218151E+09 | 0.540840E+10 |
Report: SpaceGainsMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.161274E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.540745E+10 |
February | 0.156756E+10 | 0.146111E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.406014E+10 |
March | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.301278E+10 |
April | 0.169125E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 40536449.91 | 0.190959E+10 |
May | 0.174872E+10 | 0.163243E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 36599867.86 | 0.881554E+09 |
June | 0.171530E+10 | 0.159501E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.218261E+09 | 0.449089E+09 |
July | 0.172466E+10 | 0.160290E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179742E+09 | 0.234126E+09 |
August | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.197079E+09 | 0.299677E+09 |
September | 0.169125E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147873E+09 | 0.772520E+09 |
October | 0.172174E+10 | 0.161274E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171864E+10 |
November | 0.165844E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.309658E+10 |
December | 0.172466E+10 | 0.160290E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.451745E+10 |
Annual Sum or Average | 0.205167E+11 | 0.191205E+11 | 0.958644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.820091E+09 | 0.263596E+11 |
Minimum of Months | 0.156756E+10 | 0.146111E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.234126E+09 |
Maximum of Months | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.218261E+09 | 0.540745E+10 |
Report: SpaceGainsMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.161274E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.540100E+10 |
February | 0.156756E+10 | 0.146111E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.405310E+10 |
March | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.300093E+10 |
April | 0.169125E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 40767196.88 | 0.189521E+10 |
May | 0.174872E+10 | 0.163243E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 36600477.37 | 0.853009E+09 |
June | 0.171530E+10 | 0.159501E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.218541E+09 | 0.440228E+09 |
July | 0.172466E+10 | 0.160290E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179868E+09 | 0.230788E+09 |
August | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.197114E+09 | 0.296630E+09 |
September | 0.169125E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147906E+09 | 0.763545E+09 |
October | 0.172174E+10 | 0.161274E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.170673E+10 |
November | 0.165844E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.308736E+10 |
December | 0.172466E+10 | 0.160290E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.450979E+10 |
Annual Sum or Average | 0.205167E+11 | 0.191205E+11 | 0.958644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.820797E+09 | 0.262383E+11 |
Minimum of Months | 0.156756E+10 | 0.146111E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230788E+09 |
Maximum of Months | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.218541E+09 | 0.540100E+10 |
Report: SpaceGainsMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.161274E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.702686E+10 |
February | 0.156756E+10 | 0.146111E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.524777E+10 |
March | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.396671E+10 |
April | 0.169125E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 46674746.27 | 0.244211E+10 |
May | 0.174872E+10 | 0.163243E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 38762326.70 | 0.111085E+10 |
June | 0.171530E+10 | 0.159501E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.237165E+09 | 0.613076E+09 |
July | 0.172466E+10 | 0.160290E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188793E+09 | 0.366217E+09 |
August | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.207826E+09 | 0.504700E+09 |
September | 0.169125E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155520E+09 | 0.107705E+10 |
October | 0.172174E+10 | 0.161274E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.226991E+10 |
November | 0.165844E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.408394E+10 |
December | 0.172466E+10 | 0.160290E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.588297E+10 |
Annual Sum or Average | 0.205167E+11 | 0.191205E+11 | 0.958644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.874741E+09 | 0.345922E+11 |
Minimum of Months | 0.156756E+10 | 0.146111E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.366217E+09 |
Maximum of Months | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.237165E+09 | 0.702686E+10 |
Report: PeakSpaceGainsMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 4050.04 | 01-JAN-13:09 | 4621.63 | 01-JAN-10:09 | 1343.25 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 16712.86 | 30-JAN-18:00 |
February | 4050.04 | 03-FEB-13:09 | 4621.63 | 01-FEB-10:09 | 1343.25 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 18838.26 | 02-FEB-12:10 |
March | 4050.04 | 03-MAR-13:09 | 4621.63 | 01-MAR-10:09 | 1343.25 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 11241.26 | 05-MAR-18:00 |
April | 4050.04 | 01-APR-12:09 | 4621.63 | 01-APR-09:09 | 1343.25 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1868.66 | 15-APR-15:00 | 8212.63 | 03-APR-11:10 |
May | 4050.04 | 05-MAY-12:09 | 4621.63 | 01-MAY-09:09 | 1343.25 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1747.78 | 31-MAY-13:00 | 4178.66 | 01-MAY-17:00 |
June | 4050.04 | 02-JUN-12:09 | 4621.63 | 01-JUN-09:09 | 1343.25 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2764.43 | 11-JUN-15:00 | 3365.42 | 01-JUN-14:00 |
July | 4050.04 | 01-JUL-12:09 | 4621.63 | 01-JUL-09:09 | 1343.25 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1760.63 | 26-JUL-16:00 | 2410.04 | 10-JUL-12:00 |
August | 4050.04 | 04-AUG-12:09 | 4621.63 | 01-AUG-09:09 | 1343.25 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2774.17 | 04-AUG-15:00 | 2496.10 | 06-AUG-11:10 |
September | 4050.04 | 01-SEP-12:09 | 4621.63 | 01-SEP-09:09 | 1343.25 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2380.99 | 06-SEP-14:00 | 4172.20 | 29-SEP-17:00 |
October | 4050.04 | 01-OCT-12:09 | 4621.63 | 01-OCT-09:09 | 1343.25 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 5383.80 | 31-OCT-17:00 |
November | 4050.04 | 03-NOV-12:09 | 4621.63 | 01-NOV-09:09 | 1343.25 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 14684.46 | 25-NOV-18:00 |
December | 4050.04 | 01-DEC-13:09 | 4621.63 | 01-DEC-10:09 | 1343.25 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 15639.94 | 09-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 4050.04 | 4621.63 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2410.04 | |||||
Maximum of Months | 4050.04 | 4621.63 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 2774.17 | 18838.26 |
Report: PeakSpaceGainsMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 01-JAN-13:09 | 2827.07 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 9133.76 | 30-JAN-18:00 |
February | 2024.96 | 03-FEB-13:09 | 2827.07 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 10241.54 | 02-FEB-12:10 |
March | 2024.96 | 03-MAR-13:09 | 2827.07 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 6068.75 | 05-MAR-18:00 |
April | 2024.96 | 01-APR-12:09 | 2827.07 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 977.36 | 15-APR-15:00 | 4437.12 | 03-APR-11:10 |
May | 2024.96 | 05-MAY-12:09 | 2827.07 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 945.78 | 31-MAY-13:00 | 2214.87 | 01-MAY-17:00 |
June | 2024.96 | 02-JUN-12:09 | 2827.07 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1468.46 | 11-JUN-15:00 | 1930.81 | 01-JUN-14:00 |
July | 2024.96 | 01-JUL-12:09 | 2827.07 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 952.70 | 26-JUL-16:00 | 1358.64 | 10-JUL-12:00 |
August | 2024.96 | 04-AUG-12:09 | 2827.07 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1512.49 | 04-AUG-15:00 | 1349.11 | 06-AUG-11:10 |
September | 2024.96 | 01-SEP-12:09 | 2827.07 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1288.37 | 06-SEP-14:00 | 2252.42 | 29-SEP-17:00 |
October | 2024.96 | 01-OCT-12:09 | 2827.07 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2974.08 | 31-OCT-17:00 |
November | 2024.96 | 03-NOV-12:09 | 2827.07 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 7891.37 | 25-NOV-18:00 |
December | 2024.96 | 01-DEC-13:09 | 2827.07 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 8193.31 | 09-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 2827.07 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1349.11 | |||||
Maximum of Months | 2024.96 | 2827.07 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1512.49 | 10241.54 |
Report: PeakSpaceGainsMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 2555.22 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 9133.76 | 30-JAN-18:00 |
February | 2024.96 | 04-FEB-13:09 | 2555.22 | 01-FEB-09:09 | 671.63 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 10241.54 | 02-FEB-12:10 |
March | 2024.96 | 04-MAR-13:09 | 2555.22 | 01-MAR-09:09 | 671.63 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 6068.75 | 05-MAR-18:00 |
April | 2024.96 | 01-APR-12:09 | 2555.22 | 01-APR-08:09 | 671.63 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 977.38 | 15-APR-15:00 | 4437.12 | 03-APR-11:10 |
May | 2024.96 | 06-MAY-12:09 | 2555.22 | 01-MAY-08:09 | 671.63 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 945.77 | 31-MAY-13:00 | 2214.87 | 01-MAY-17:00 |
June | 2024.96 | 03-JUN-12:09 | 2555.22 | 01-JUN-08:09 | 671.63 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1468.46 | 11-JUN-15:00 | 1918.91 | 01-JUN-14:00 |
July | 2024.96 | 01-JUL-12:09 | 2555.22 | 01-JUL-08:09 | 671.63 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 952.70 | 26-JUL-16:00 | 1351.13 | 10-JUL-12:00 |
August | 2024.96 | 05-AUG-12:09 | 2555.22 | 01-AUG-08:09 | 671.63 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1512.49 | 04-AUG-15:00 | 1349.11 | 06-AUG-11:10 |
September | 2024.96 | 02-SEP-12:09 | 2555.22 | 01-SEP-08:09 | 671.63 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1288.44 | 06-SEP-14:00 | 2252.42 | 29-SEP-17:00 |
October | 2024.96 | 07-OCT-12:09 | 2555.22 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2974.08 | 31-OCT-17:00 |
November | 2024.96 | 04-NOV-12:09 | 2555.22 | 01-NOV-08:09 | 671.63 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 7891.37 | 25-NOV-18:00 |
December | 2024.96 | 02-DEC-13:09 | 2555.22 | 01-DEC-09:09 | 671.63 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 8193.31 | 09-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 2555.22 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1349.11 | |||||
Maximum of Months | 2024.96 | 2555.22 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1512.49 | 10241.54 |
Report: PeakSpaceGainsMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 2555.22 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 9133.76 | 30-JAN-18:00 |
February | 2024.96 | 04-FEB-13:09 | 2555.22 | 01-FEB-09:09 | 671.63 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 10241.54 | 02-FEB-12:10 |
March | 2024.96 | 04-MAR-13:09 | 2555.22 | 01-MAR-09:09 | 671.63 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 6068.75 | 05-MAR-18:00 |
April | 2024.96 | 01-APR-12:09 | 2555.22 | 01-APR-08:09 | 671.63 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 977.51 | 15-APR-15:00 | 4437.12 | 03-APR-11:10 |
May | 2024.96 | 06-MAY-12:09 | 2555.22 | 01-MAY-08:09 | 671.63 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 945.77 | 31-MAY-13:00 | 2214.87 | 01-MAY-17:00 |
June | 2024.96 | 03-JUN-12:09 | 2555.22 | 01-JUN-08:09 | 671.63 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1468.46 | 11-JUN-15:00 | 1915.75 | 01-JUN-14:00 |
July | 2024.96 | 01-JUL-12:09 | 2555.22 | 01-JUL-08:09 | 671.63 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 952.70 | 26-JUL-16:00 | 1347.73 | 10-JUL-12:00 |
August | 2024.96 | 05-AUG-12:09 | 2555.22 | 01-AUG-08:09 | 671.63 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1512.49 | 04-AUG-15:00 | 1349.11 | 06-AUG-11:10 |
September | 2024.96 | 02-SEP-12:09 | 2555.22 | 01-SEP-08:09 | 671.63 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1288.46 | 06-SEP-14:00 | 2252.42 | 29-SEP-17:00 |
October | 2024.96 | 07-OCT-12:09 | 2555.22 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2974.08 | 31-OCT-17:00 |
November | 2024.96 | 04-NOV-12:09 | 2555.22 | 01-NOV-08:09 | 671.63 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 7891.37 | 25-NOV-18:00 |
December | 2024.96 | 02-DEC-13:09 | 2555.22 | 01-DEC-09:09 | 671.63 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 8193.31 | 09-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 2555.22 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1347.73 | |||||
Maximum of Months | 2024.96 | 2555.22 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1512.49 | 10241.54 |
Report: PeakSpaceGainsMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 2555.22 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 9133.76 | 30-JAN-18:00 |
February | 2024.96 | 04-FEB-13:09 | 2555.22 | 01-FEB-09:09 | 671.63 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 10241.54 | 02-FEB-12:10 |
March | 2024.96 | 04-MAR-13:09 | 2555.22 | 01-MAR-09:09 | 671.63 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 6068.75 | 05-MAR-18:00 |
April | 2024.96 | 01-APR-12:09 | 2555.22 | 01-APR-08:09 | 671.63 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 977.51 | 15-APR-15:00 | 4437.12 | 03-APR-11:10 |
May | 2024.96 | 06-MAY-12:09 | 2555.22 | 01-MAY-08:09 | 671.63 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 945.76 | 31-MAY-13:00 | 2214.87 | 01-MAY-17:00 |
June | 2024.96 | 03-JUN-12:09 | 2555.22 | 01-JUN-08:09 | 671.63 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1468.46 | 11-JUN-15:00 | 1896.23 | 01-JUN-14:00 |
July | 2024.96 | 01-JUL-12:09 | 2555.22 | 01-JUL-08:09 | 671.63 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 952.70 | 26-JUL-16:00 | 1331.96 | 10-JUL-12:00 |
August | 2024.96 | 05-AUG-12:09 | 2555.22 | 01-AUG-08:09 | 671.63 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1512.49 | 04-AUG-15:00 | 1349.11 | 06-AUG-11:10 |
September | 2024.96 | 02-SEP-12:09 | 2555.22 | 01-SEP-08:09 | 671.63 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1288.47 | 06-SEP-14:00 | 2252.42 | 29-SEP-17:00 |
October | 2024.96 | 07-OCT-12:09 | 2555.22 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2974.08 | 31-OCT-17:00 |
November | 2024.96 | 04-NOV-12:09 | 2555.22 | 01-NOV-08:09 | 671.63 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 7891.37 | 25-NOV-18:00 |
December | 2024.96 | 02-DEC-13:09 | 2555.22 | 01-DEC-09:09 | 671.63 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 8193.31 | 09-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 2555.22 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1331.96 | |||||
Maximum of Months | 2024.96 | 2555.22 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1512.49 | 10241.54 |
Report: PeakSpaceGainsMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 5400.05 | 07-JAN-15:09 | 2726.96 | 01-JAN-11:09 | 1343.25 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 16417.44 | 30-JAN-18:00 |
February | 5400.05 | 04-FEB-15:09 | 2726.96 | 01-FEB-10:09 | 1343.25 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 18420.55 | 02-FEB-12:10 |
March | 5400.05 | 04-MAR-15:09 | 2726.96 | 01-MAR-10:09 | 1343.25 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 10924.83 | 05-MAR-18:00 |
April | 5400.05 | 01-APR-14:09 | 2726.96 | 01-APR-09:09 | 1343.25 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1766.72 | 15-APR-15:00 | 7986.84 | 03-APR-11:10 |
May | 5400.05 | 06-MAY-14:09 | 2726.96 | 01-MAY-09:09 | 1343.25 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1702.04 | 31-MAY-13:00 | 3996.38 | 01-MAY-17:00 |
June | 5400.05 | 03-JUN-14:09 | 2726.96 | 01-JUN-09:09 | 1343.25 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2648.88 | 11-JUN-15:00 | 3284.42 | 01-JUN-14:00 |
July | 5400.05 | 01-JUL-14:09 | 2726.96 | 01-JUL-09:09 | 1343.25 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1714.54 | 26-JUL-16:00 | 2322.27 | 10-JUL-12:00 |
August | 5400.05 | 05-AUG-14:09 | 2726.96 | 01-AUG-09:09 | 1343.25 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2719.43 | 04-AUG-15:00 | 2424.48 | 06-AUG-11:10 |
September | 5400.05 | 02-SEP-14:09 | 2726.96 | 01-SEP-09:09 | 1343.25 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2318.79 | 06-SEP-14:00 | 4054.75 | 29-SEP-17:00 |
October | 5400.05 | 07-OCT-14:09 | 2726.96 | 01-OCT-10:09 | 1343.25 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 5338.70 | 31-OCT-17:00 |
November | 5400.05 | 04-NOV-14:09 | 2726.96 | 01-NOV-09:09 | 1343.25 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 14214.02 | 25-NOV-18:00 |
December | 5400.05 | 02-DEC-15:09 | 2726.96 | 01-DEC-10:09 | 1343.25 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 14805.60 | 09-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 5400.05 | 2726.96 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2322.27 | |||||
Maximum of Months | 5400.05 | 2726.96 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 2719.43 | 18420.55 |
Report: PeakSpaceGainsMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1404.46 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 9133.76 | 30-JAN-18:00 |
February | 2699.95 | 04-FEB-15:09 | 1404.46 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 10241.54 | 02-FEB-12:10 |
March | 2699.95 | 04-MAR-15:09 | 1404.46 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 6068.75 | 05-MAR-18:00 |
April | 2699.95 | 01-APR-14:09 | 1404.46 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 977.51 | 15-APR-15:00 | 4437.12 | 03-APR-11:10 |
May | 2699.95 | 06-MAY-14:09 | 1404.46 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 945.76 | 31-MAY-13:00 | 2214.87 | 01-MAY-17:00 |
June | 2699.95 | 03-JUN-14:09 | 1404.46 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1468.46 | 11-JUN-15:00 | 1827.83 | 01-JUN-14:00 |
July | 2699.95 | 01-JUL-14:09 | 1404.46 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 952.70 | 26-JUL-16:00 | 1286.56 | 10-JUL-12:00 |
August | 2699.95 | 05-AUG-14:09 | 1404.46 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1512.49 | 04-AUG-15:00 | 1343.33 | 06-AUG-11:10 |
September | 2699.95 | 02-SEP-14:09 | 1404.46 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1288.44 | 06-SEP-14:00 | 2251.64 | 29-SEP-17:00 |
October | 2699.95 | 07-OCT-14:09 | 1404.46 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2974.08 | 31-OCT-17:00 |
November | 2699.95 | 04-NOV-14:09 | 1404.46 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 7891.37 | 25-NOV-18:00 |
December | 2699.95 | 02-DEC-15:09 | 1404.46 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 8193.31 | 09-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1286.56 | |||||
Maximum of Months | 2699.95 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1512.49 | 10241.54 |
Report: PeakSpaceGainsMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1404.46 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 9133.76 | 30-JAN-18:00 |
February | 2699.95 | 04-FEB-15:09 | 1404.46 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 10241.54 | 02-FEB-12:10 |
March | 2699.95 | 04-MAR-15:09 | 1404.46 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 6068.75 | 05-MAR-18:00 |
April | 2699.95 | 01-APR-14:09 | 1404.46 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 977.51 | 15-APR-15:00 | 4437.12 | 03-APR-11:10 |
May | 2699.95 | 06-MAY-14:09 | 1404.46 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 945.75 | 31-MAY-13:00 | 2214.87 | 01-MAY-17:00 |
June | 2699.95 | 03-JUN-14:09 | 1404.46 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1468.46 | 11-JUN-15:00 | 1816.67 | 01-JUN-14:00 |
July | 2699.95 | 01-JUL-14:09 | 1404.46 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 952.70 | 26-JUL-16:00 | 1277.92 | 10-JUL-12:00 |
August | 2699.95 | 05-AUG-14:09 | 1404.46 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1512.49 | 04-AUG-15:00 | 1342.37 | 06-AUG-11:10 |
September | 2699.95 | 02-SEP-14:09 | 1404.46 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1288.45 | 06-SEP-14:00 | 2252.42 | 29-SEP-17:00 |
October | 2699.95 | 07-OCT-14:09 | 1404.46 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2974.08 | 31-OCT-17:00 |
November | 2699.95 | 04-NOV-14:09 | 1404.46 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 7891.37 | 25-NOV-18:00 |
December | 2699.95 | 02-DEC-15:09 | 1404.46 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 8193.31 | 09-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1277.92 | |||||
Maximum of Months | 2699.95 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1512.49 | 10241.54 |
Report: PeakSpaceGainsMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1404.46 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 9133.76 | 30-JAN-18:00 |
February | 2699.95 | 04-FEB-15:09 | 1404.46 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 10241.54 | 02-FEB-12:10 |
March | 2699.95 | 04-MAR-15:09 | 1404.46 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 6068.75 | 05-MAR-18:00 |
April | 2699.95 | 01-APR-14:09 | 1404.46 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 977.51 | 15-APR-15:00 | 4437.12 | 03-APR-11:10 |
May | 2699.95 | 06-MAY-14:09 | 1404.46 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 945.74 | 31-MAY-13:00 | 2214.87 | 01-MAY-17:00 |
June | 2699.95 | 03-JUN-14:09 | 1404.46 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1468.46 | 11-JUN-15:00 | 1788.46 | 01-JUN-14:00 |
July | 2699.95 | 01-JUL-14:09 | 1404.46 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 952.70 | 26-JUL-16:00 | 1248.76 | 10-JUL-12:00 |
August | 2699.95 | 05-AUG-14:09 | 1404.46 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1512.49 | 04-AUG-15:00 | 1326.49 | 06-AUG-11:10 |
September | 2699.95 | 02-SEP-14:09 | 1404.46 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1288.46 | 06-SEP-14:00 | 2252.42 | 29-SEP-17:00 |
October | 2699.95 | 07-OCT-14:09 | 1404.46 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2974.08 | 31-OCT-17:00 |
November | 2699.95 | 04-NOV-14:09 | 1404.46 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 7891.37 | 25-NOV-18:00 |
December | 2699.95 | 02-DEC-15:09 | 1404.46 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 8193.31 | 09-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1248.76 | |||||
Maximum of Months | 2699.95 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1512.49 | 10241.54 |
Report: PeakSpaceGainsMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1404.46 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 9429.18 | 30-JAN-18:00 |
February | 2699.95 | 04-FEB-15:09 | 1404.46 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 10659.25 | 02-FEB-12:10 |
March | 2699.95 | 04-MAR-15:09 | 1404.46 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 6385.18 | 05-MAR-18:00 |
April | 2699.95 | 01-APR-14:09 | 1404.46 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1079.44 | 15-APR-15:00 | 4662.92 | 03-APR-11:10 |
May | 2699.95 | 06-MAY-14:09 | 1404.46 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 991.62 | 31-MAY-13:00 | 2397.15 | 01-MAY-17:00 |
June | 2699.95 | 03-JUN-14:09 | 1404.46 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1583.92 | 11-JUN-15:00 | 1778.42 | 01-JUN-14:00 |
July | 2699.95 | 01-JUL-14:09 | 1404.46 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 998.77 | 26-JUL-16:00 | 1245.69 | 10-JUL-12:00 |
August | 2699.95 | 05-AUG-14:09 | 1404.46 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1567.23 | 04-AUG-15:00 | 1331.09 | 06-AUG-11:10 |
September | 2699.95 | 02-SEP-14:09 | 1404.46 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1350.75 | 06-SEP-14:00 | 2369.86 | 29-SEP-17:00 |
October | 2699.95 | 07-OCT-14:09 | 1404.46 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 3019.18 | 31-OCT-17:00 |
November | 2699.95 | 04-NOV-14:09 | 1404.46 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 8361.81 | 25-NOV-18:00 |
December | 2699.95 | 02-DEC-15:09 | 1404.46 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 9027.64 | 09-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1245.69 | |||||
Maximum of Months | 2699.95 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1583.92 | 10659.25 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 20469.35 | 06-JAN-00:01 | 3037.53 | 2189.07 | 6716.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 660.91 |
February | 24057.28 | 03-FEB-00:01 | 3375.03 | 2432.30 | 7462.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 488.12 |
March | 13292.95 | 11-MAR-00:02 | 2025.02 | 14594.58 | 4477.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 308.64 |
April | 9717.82 | 16-APR-16:05 | 16200.15 | 18486.52 | 5373.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1512.66 | 0.00 |
May | 10351.90 | 31-MAY-17:00 | 3375.03 | 4621.63 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 1428.10 | 0.00 |
June | 24037.93 | 30-JUN-07:03 | 0.00 | 300.00 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.56 |
July | 27824.91 | 04-JUL-07:02 | 1687.52 | 375.00 | 373.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 168.07 |
August | 22291.61 | 23-AUG-07:03 | 1350.01 | 300.00 | 298.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 269.34 |
September | 23703.41 | 11-SEP-07:03 | 1350.01 | 300.00 | 298.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 195.12 |
October | 8887.67 | 26-OCT-23:03 | 1350.01 | 972.92 | 2985.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 232.10 |
November | 15006.76 | 25-NOV-00:01 | 2362.52 | 17027.00 | 5223.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 517.80 |
December | 19389.25 | 09-DEC-00:01 | 3037.53 | 21891.86 | 6716.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2002.03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 8887.67 | 0.00 | 300.00 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 27824.91 | 16200.15 | 21891.86 | 7462.50 | 0.00 | 0.00 | 0.00 | 0.00 | 1512.66 | 2002.03 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7943.43 | 04-JAN-19:12 | 10124.81 | 16962.41 | 4029.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 952.88 |
February | 4446.85 | 26-FEB-10:53 | 1349.97 | 11308.27 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 585.64 |
March | 5533.92 | 13-MAR-10:12 | 1687.47 | 14135.34 | 3358.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 663.03 |
April | 11837.49 | 15-APR-22:33 | 4724.91 | 19789.47 | 4701.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.29 |
May | 14374.91 | 07-MAY-17:08 | 12149.77 | 16962.41 | 4029.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 119.20 |
June | 15049.42 | 26-JUN-07:03 | 674.99 | 150.00 | 149.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.62 |
July | 15674.38 | 04-JUL-07:02 | 843.73 | 187.50 | 186.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.19 |
August | 15485.71 | 06-AUG-17:27 | 14174.73 | 19789.47 | 4701.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 132.30 |
September | 14795.26 | 11-SEP-07:03 | 674.99 | 150.00 | 149.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.38 |
October | 4023.49 | 31-OCT-17:20 | 1687.47 | 2827.07 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 443.72 |
November | 4495.31 | 23-NOV-10:43 | 1349.97 | 11308.27 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 472.78 |
December | 6373.27 | 25-DEC-11:52 | 3374.94 | 14135.34 | 3358.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 831.79 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4023.49 | 674.99 | 150.00 | 149.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.62 | |
Maximum of Months | 15674.38 | 14174.73 | 19789.47 | 4701.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 952.88 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1350.10 | 13-JAN-18:10 | 1687.47 | 2555.22 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 488.46 |
February | 5053.78 | 14-FEB-19:23 | 2699.95 | 10220.87 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 607.26 |
March | 3884.22 | 27-MAR-08:43 | 1012.48 | 7665.65 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 545.42 |
April | 5267.37 | 18-APR-14:00 | 1012.48 | 2555.22 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 708.44 | 0.00 |
May | 5817.05 | 31-MAY-13:00 | 1349.97 | 2555.22 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 945.77 | 0.00 |
June | 14731.34 | 12-JUN-06:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.25 |
July | 15992.69 | 03-JUL-06:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.85 |
August | 15915.81 | 23-AUG-06:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.36 |
September | 16896.94 | 11-SEP-06:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.41 |
October | 4223.36 | 31-OCT-07:01 | 1349.97 | 300.00 | 2985.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 475.38 |
November | 5267.87 | 20-NOV-20:12 | 674.99 | 5379.41 | 1492.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 373.19 |
December | 5604.27 | 05-DEC-10:22 | 1687.47 | 12776.09 | 3358.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 933.07 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1350.10 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16896.94 | 2699.95 | 12776.09 | 3358.13 | 0.00 | 0.00 | 0.00 | 0.00 | 945.77 | 933.07 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1262.98 | 13-JAN-18:10 | 1687.47 | 2555.22 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 488.46 |
February | 6232.53 | 15-FEB-18:52 | 8437.34 | 12776.09 | 3358.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 865.72 |
March | 5910.80 | 10-MAR-20:12 | 843.73 | 6724.26 | 1865.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.03 |
April | 5191.93 | 18-APR-14:00 | 1012.48 | 2555.22 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 708.44 | 0.00 |
May | 5758.17 | 31-MAY-13:00 | 1349.97 | 2555.22 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 945.77 | 0.00 |
June | 14998.10 | 28-JUN-06:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.07 |
July | 16094.52 | 03-JUL-06:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.12 |
August | 15909.97 | 23-AUG-06:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.36 |
September | 16982.50 | 11-SEP-06:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.55 |
October | 4093.15 | 13-OCT-07:01 | 1518.72 | 337.50 | 3358.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 512.76 |
November | 5979.68 | 21-NOV-11:52 | 1687.47 | 12776.09 | 3358.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 902.70 |
December | 6754.25 | 20-DEC-18:52 | 8437.34 | 12776.09 | 3358.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 926.83 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1262.98 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16982.50 | 8437.34 | 12776.09 | 3358.13 | 0.00 | 0.00 | 0.00 | 0.00 | 945.77 | 926.83 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3893.44 | 12-JAN-20:03 | 506.24 | 4034.55 | 1119.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.86 |
February | 4470.64 | 21-FEB-19:03 | 2699.95 | 10220.87 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 553.90 |
March | 4071.37 | 30-MAR-09:23 | 1349.97 | 10220.87 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 622.93 |
April | 4975.90 | 18-APR-14:00 | 1012.48 | 2555.22 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 708.59 | 0.00 |
May | 5556.25 | 31-MAY-13:00 | 1349.97 | 2555.22 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 945.76 | 0.00 |
June | 14330.89 | 30-JUN-06:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.24 |
July | 15866.56 | 03-JUL-06:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.63 |
August | 14357.62 | 23-AUG-06:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.29 |
September | 16279.45 | 11-SEP-06:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.33 |
October | 3006.01 | 12-OCT-07:02 | 843.73 | 187.50 | 1865.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 376.06 |
November | 4926.85 | 13-NOV-19:42 | 2699.95 | 10220.87 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 586.70 |
December | 5708.36 | 01-DEC-19:12 | 3374.94 | 12776.09 | 3358.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 668.88 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3006.01 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16279.45 | 3374.94 | 12776.09 | 3358.13 | 0.00 | 0.00 | 0.00 | 0.00 | 945.76 | 668.88 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1019.63 | 13-JAN-12:00 | 2902.53 | 2726.96 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 862.09 |
February | 1998.65 | 25-FEB-12:00 | 3915.04 | 2726.96 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 883.06 |
March | 9706.50 | 10-MAR-11:23 | 11610.11 | 10907.84 | 5373.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1130.61 |
April | 8886.05 | 18-APR-14:40 | 4657.54 | 2726.96 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 1277.10 | 0.00 |
May | 9813.03 | 31-MAY-15:00 | 4657.54 | 2726.96 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 1695.37 | 0.00 |
June | 24599.43 | 28-JUN-07:03 | 0.00 | 300.00 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.75 |
July | 26416.94 | 03-JUL-07:03 | 0.00 | 300.00 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 184.76 |
August | 22767.89 | 23-AUG-07:03 | 0.00 | 300.00 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 241.79 |
September | 28777.59 | 11-SEP-07:03 | 0.00 | 300.00 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 169.44 |
October | 7045.91 | 16-OCT-09:13 | 2227.52 | 8180.88 | 4029.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 760.80 |
November | 4831.26 | 03-NOV-18:00 | 2295.02 | 2726.96 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 521.69 |
December | 1545.06 | 02-DEC-12:00 | 3915.04 | 2726.96 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 817.15 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1019.63 | 0.00 | 300.00 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 28777.59 | 11610.11 | 10907.84 | 5373.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1695.37 | 1130.61 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4069.67 | 13-JAN-18:23 | 4589.91 | 5617.86 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 492.42 |
February | 931.49 | 25-FEB-12:00 | 1957.46 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 481.24 |
March | 4126.59 | 20-MAR-19:12 | 1484.97 | 2956.77 | 1492.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 231.47 |
April | 4568.75 | 18-APR-14:50 | 2328.71 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 706.50 | 0.00 |
May | 5070.54 | 31-MAY-15:00 | 2328.71 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 942.32 | 0.00 |
June | 12141.98 | 30-JUN-07:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.22 |
July | 13523.76 | 03-JUL-07:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.96 |
August | 11434.79 | 03-AUG-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.31 |
September | 14146.20 | 11-SEP-07:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.12 |
October | 3531.16 | 13-OCT-09:03 | 1113.73 | 4213.39 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 470.75 |
November | 4694.70 | 10-NOV-18:23 | 4589.91 | 5617.86 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 707.33 |
December | 709.95 | 02-DEC-12:00 | 1957.46 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 444.06 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 709.95 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14146.20 | 4589.91 | 5617.86 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 942.32 | 707.33 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 415.50 | 13-JAN-12:00 | 1451.22 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 469.14 |
February | 877.58 | 25-FEB-12:00 | 1957.46 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 481.24 |
March | 4980.65 | 21-MAR-18:03 | 3509.93 | 5617.86 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 654.26 |
April | 4452.73 | 18-APR-14:50 | 2328.71 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 706.50 | 0.00 |
May | 4969.96 | 31-MAY-15:00 | 2328.71 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 942.32 | 0.00 |
June | 12033.66 | 30-JUN-07:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.29 |
July | 13404.24 | 03-JUL-07:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.85 |
August | 11335.85 | 03-AUG-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.30 |
September | 13634.96 | 11-SEP-07:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.98 |
October | 3026.20 | 16-OCT-16:27 | 7188.61 | 4213.39 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2526.91 |
November | 4012.07 | 16-NOV-19:23 | 3509.93 | 5617.86 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 507.95 |
December | 670.59 | 02-DEC-12:00 | 1957.46 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 444.06 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 415.50 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13634.96 | 7188.61 | 5617.86 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 942.32 | 2526.91 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 163.71 | 13-JAN-12:00 | 1451.22 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 469.14 |
February | 628.60 | 25-FEB-12:00 | 1957.46 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 481.24 |
March | 3960.41 | 27-MAR-18:43 | 2632.45 | 4213.39 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 478.74 |
April | 4162.32 | 18-APR-14:50 | 2328.71 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 706.50 | 0.00 |
May | 4745.66 | 31-MAY-15:00 | 2328.71 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 942.31 | 0.00 |
June | 11576.74 | 26-JUN-07:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.32 |
July | 13181.80 | 03-JUL-07:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.23 |
August | 11159.77 | 03-AUG-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.09 |
September | 11971.05 | 11-SEP-07:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.56 |
October | 2915.29 | 22-OCT-09:03 | 1113.73 | 112.50 | 1119.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 402.91 |
November | 3832.97 | 16-NOV-18:53 | 3442.43 | 4213.39 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 490.49 |
December | 3382.45 | 02-DEC-11:13 | 5872.39 | 4213.39 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 501.05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 163.71 | 0.00 | 112.50 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13181.80 | 5872.39 | 4213.39 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 942.31 | 501.05 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:05 | 0.00 | 75.00 | 73.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 916.53 |
February | 55.75 | 25-FEB-08:04 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 679.46 |
March | 1541.11 | 24-MAR-12:05 | 4792.41 | 2808.93 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1679.24 |
April | 3873.95 | 18-APR-14:30 | 2328.71 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 777.38 | 0.00 |
May | 4804.03 | 31-MAY-13:00 | 2396.20 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 991.62 | 0.00 |
June | 8757.91 | 26-JUN-07:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.84 |
July | 14837.66 | 04-JUL-08:62 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.22 |
August | 11300.83 | 03-AUG-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.46 | 0.00 |
September | 7272.71 | 07-SEP-14:10 | 2328.71 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1281.71 | 0.00 |
October | 3791.09 | 13-OCT-18:43 | 2632.45 | 4213.39 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 548.01 |
November | 2019.79 | 04-NOV-11:00 | 1957.46 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 345.52 |
December | 0.00 | 01-DEC-00:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1080.33 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 75.00 | 73.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14837.66 | 4792.41 | 4213.39 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 1281.71 | 1679.24 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.662226E+11 | 55744.24 | 07-JAN-16:49 | 0.253759E+12 | 310047.61 | 30-JAN-17:00 |
February | 0.585371E+11 | 56830.14 | 03-FEB-17:49 | 0.181373E+12 | 353922.28 | 02-FEB-12:09 |
March | 0.632692E+11 | 53427.76 | 01-MAR-18:10 | 0.119419E+12 | 230625.96 | 06-MAR-08:09 |
April | 0.605880E+11 | 70082.81 | 18-APR-14:09 | 0.598454E+11 | 198465.66 | 03-APR-07:10 |
May | 0.625978E+11 | 69905.04 | 31-MAY-13:20 | 0.429462E+10 | 95733.46 | 02-MAY-07:10 |
June | 0.733760E+11 | 83732.15 | 11-JUN-14:50 | 0.919718E+09 | 24016.07 | 05-JUN-08:20 |
July | 0.803391E+11 | 83280.21 | 26-JUL-15:20 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.809356E+11 | 96994.64 | 04-AUG-15:09 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.681180E+11 | 77590.64 | 06-SEP-13:00 | 0.428315E+10 | 89553.01 | 30-SEP-07:10 |
October | 0.613071E+11 | 50541.51 | 31-OCT-17:40 | 0.306990E+11 | 93744.14 | 27-OCT-07:10 |
November | 0.615596E+11 | 52046.21 | 29-NOV-17:19 | 0.112482E+12 | 260153.44 | 25-NOV-17:00 |
December | 0.653429E+11 | 53820.52 | 04-DEC-16:49 | 0.201116E+12 | 297551.98 | 09-DEC-12:09 |
Annual Sum or Average | 0.802193E+12 | 0.968191E+12 | ||||
Minimum of Months | 0.585371E+11 | 50541.51 | 0.00 | 0.00 | ||
Maximum of Months | 0.809356E+11 | 96994.64 | 0.253759E+12 | 353922.28 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.310073E+11 | 0.687913E+10 | 0.108325E+11 | 0.00 | 0.116909E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.581285E+10 | 0.00 |
February | 0.280657E+11 | 0.557398E+10 | 0.980803E+10 | 0.00 | 0.979746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.529186E+10 | 0.00 |
March | 0.314703E+11 | 0.528648E+10 | 0.110075E+11 | 0.00 | 0.963217E+10 | 0.00 | 0.00 | 290116.60 | 0.00 | 0.00 | 0.00 | 0.587251E+10 | 0.00 |
April | 0.300741E+11 | 0.420931E+10 | 0.105079E+11 | 0.00 | 0.833489E+10 | 0.00 | 0.00 | 0.189908E+10 | 0.00 | 0.00 | 0.00 | 0.556265E+10 | 0.00 |
May | 0.312330E+11 | 0.364065E+10 | 0.109147E+11 | 0.00 | 0.783349E+10 | 0.00 | 0.00 | 0.335492E+10 | 0.00 | 0.00 | 0.00 | 0.562101E+10 | 0.00 |
June | 0.304143E+11 | 0.320721E+10 | 0.106386E+11 | 0.00 | 0.760172E+10 | 0.00 | 0.00 | 0.161797E+11 | 0.00 | 0.00 | 0.00 | 0.533440E+10 | 0.00 |
July | 0.309042E+11 | 0.341554E+10 | 0.107945E+11 | 0.00 | 0.771026E+10 | 0.00 | 0.00 | 0.221423E+11 | 0.00 | 0.00 | 0.00 | 0.537226E+10 | 0.00 |
August | 0.314595E+11 | 0.400114E+10 | 0.110006E+11 | 0.00 | 0.792584E+10 | 0.00 | 0.00 | 0.211638E+11 | 0.00 | 0.00 | 0.00 | 0.538478E+10 | 0.00 |
September | 0.300847E+11 | 0.471156E+10 | 0.105148E+11 | 0.00 | 0.752616E+10 | 0.00 | 0.00 | 0.100626E+11 | 0.00 | 0.00 | 0.00 | 0.521819E+10 | 0.00 |
October | 0.310073E+11 | 0.580525E+10 | 0.108325E+11 | 0.00 | 0.810014E+10 | 0.00 | 0.00 | 66957905.98 | 0.00 | 0.00 | 0.00 | 0.549503E+10 | 0.00 |
November | 0.300409E+11 | 0.642646E+10 | 0.104978E+11 | 0.00 | 0.915919E+10 | 0.00 | 0.00 | 1055769.05 | 0.00 | 0.00 | 0.00 | 0.543416E+10 | 0.00 |
December | 0.309156E+11 | 0.710051E+10 | 0.108050E+11 | 0.00 | 0.107973E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.572453E+10 | 0.00 |
Annual Sum or Average | 0.366677E+12 | 0.602572E+11 | 0.128154E+12 | 0.00 | 0.106110E+12 | 0.00 | 0.00 | 0.748707E+11 | 0.00 | 0.00 | 0.00 | 0.661242E+11 | 0.00 |
Minimum of Months | 0.280657E+11 | 0.320721E+10 | 0.980803E+10 | 0.00 | 0.752616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.521819E+10 | 0.00 |
Maximum of Months | 0.314703E+11 | 0.710051E+10 | 0.110075E+11 | 0.00 | 0.116909E+11 | 0.00 | 0.00 | 0.221423E+11 | 0.00 | 0.00 | 0.00 | 0.587251E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.253759E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.181373E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.119419E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.598454E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.429462E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.919718E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.428315E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.306990E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.112482E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.201116E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.968191E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.253759E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 23459.17 | 01-JAN-11:09 | 5507.06 | 01-JAN-06:10 | 8059.50 | 01-JAN-11:09 | 0.00 | 10209.62 | 30-JAN-17:00 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 23459.17 | 01-FEB-10:09 | 5507.06 | 01-FEB-06:10 | 8059.50 | 01-FEB-10:09 | 0.00 | 10910.34 | 02-FEB-12:09 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 23459.17 | 01-MAR-10:09 | 5507.06 | 01-MAR-06:10 | 8059.50 | 01-MAR-10:09 | 0.00 | 8936.84 | 06-MAR-08:09 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 23459.17 | 01-APR-09:09 | 5507.06 | 01-APR-05:10 | 8059.50 | 01-APR-09:09 | 0.00 | 8418.21 | 03-APR-07:10 | 0.00 | 0.00 | 01-APR-00:10 |
May | 23459.17 | 01-MAY-09:09 | 5507.06 | 01-MAY-19:10 | 8059.50 | 01-MAY-09:09 | 0.00 | 6783.92 | 02-MAY-07:10 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 23459.17 | 01-JUN-09:09 | 5507.06 | 01-JUN-19:40 | 8059.50 | 01-JUN-09:09 | 0.00 | 6825.81 | 11-JUN-14:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 23459.17 | 01-JUL-09:09 | 5507.06 | 01-JUL-19:00 | 8059.50 | 01-JUL-09:09 | 0.00 | 6684.67 | 26-JUL-16:10 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 23459.17 | 01-AUG-09:09 | 5507.06 | 01-AUG-19:40 | 8059.50 | 01-AUG-09:09 | 0.00 | 8680.43 | 04-AUG-12:00 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 23459.17 | 01-SEP-09:09 | 5507.06 | 01-SEP-05:10 | 8059.50 | 01-SEP-09:09 | 0.00 | 6685.78 | 30-SEP-07:10 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 23459.17 | 01-OCT-10:09 | 5507.06 | 01-OCT-05:10 | 8059.50 | 01-OCT-10:09 | 0.00 | 6752.31 | 27-OCT-07:10 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 23459.17 | 01-NOV-09:09 | 5507.06 | 01-NOV-05:10 | 8059.50 | 01-NOV-09:09 | 0.00 | 9411.47 | 25-NOV-17:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 23459.17 | 01-DEC-10:09 | 5507.06 | 01-DEC-06:10 | 8059.50 | 01-DEC-10:09 | 0.00 | 10008.95 | 09-DEC-12:09 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||||
Minimum of Months | 23459.17 | 5507.06 | 8059.50 | 0.00 | 6684.67 | 0.00 | 0.00 | |||||
Maximum of Months | 23459.17 | 5507.06 | 8059.50 | 0.00 | 10910.34 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 12806.99 | 07-JAN-12:00 | 0.00 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 9758.35 | 03-FEB-13:00 | 0.00 |
March | 226.34 | 19-MAR-17:10 | 0.00 | 0.00 | 0.00 | 10981.56 | 30-MAR-13:20 | 0.00 |
April | 26589.12 | 18-APR-14:09 | 0.00 | 0.00 | 0.00 | 9753.69 | 01-APR-12:20 | 0.00 |
May | 28089.46 | 31-MAY-12:00 | 0.00 | 0.00 | 0.00 | 9734.64 | 20-MAY-12:20 | 0.00 |
June | 42874.02 | 11-JUN-14:00 | 0.00 | 0.00 | 0.00 | 9722.59 | 05-JUN-13:09 | 0.00 |
July | 40421.91 | 26-JUL-16:10 | 0.00 | 0.00 | 0.00 | 9708.20 | 12-JUL-13:09 | 0.00 |
August | 50556.08 | 04-AUG-14:09 | 0.00 | 0.00 | 0.00 | 9706.16 | 29-AUG-12:50 | 0.00 |
September | 35697.13 | 06-SEP-14:20 | 0.00 | 0.00 | 0.00 | 9710.77 | 08-SEP-12:20 | 0.00 |
October | 7514.99 | 20-OCT-14:00 | 0.00 | 0.00 | 0.00 | 11788.43 | 13-OCT-15:39 | 0.00 |
November | 371.46 | 07-NOV-21:30 | 0.00 | 0.00 | 0.00 | 8115.91 | 07-NOV-13:39 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 9890.73 | 04-DEC-12:50 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 8115.91 | 0.00 | ||
Maximum of Months | 50556.08 | 0.00 | 0.00 | 0.00 | 12806.99 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 55744.24 | 07-JAN-16:49 | 23459.17 | 8059.50 | 5507.06 | 0.00 | 9392.04 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 56830.14 | 03-FEB-17:49 | 23459.17 | 8059.50 | 5507.06 | 0.00 | 10363.37 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 53427.76 | 01-MAR-18:10 | 23459.17 | 8059.50 | 5507.06 | 0.00 | 6899.50 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 70082.81 | 18-APR-14:09 | 23459.17 | 8059.50 | 0.00 | 0.00 | 5251.86 | 0.00 | 0.00 | 26589.12 | 0.00 |
May | 69905.04 | 31-MAY-13:20 | 23459.17 | 8059.50 | 0.00 | 0.00 | 5251.86 | 0.00 | 0.00 | 27312.37 | 0.00 |
June | 83732.15 | 11-JUN-14:50 | 23459.17 | 8059.50 | 0.00 | 0.00 | 6707.81 | 0.00 | 0.00 | 42185.37 | 0.00 |
July | 83280.21 | 26-JUL-15:20 | 23459.17 | 8059.50 | 0.00 | 0.00 | 6524.94 | 0.00 | 0.00 | 39798.38 | 0.00 |
August | 96994.64 | 04-AUG-15:09 | 23459.17 | 8059.50 | 0.00 | 0.00 | 8121.62 | 0.00 | 0.00 | 49149.89 | 0.00 |
September | 77590.64 | 06-SEP-13:00 | 23459.17 | 8059.50 | 0.00 | 0.00 | 5460.75 | 0.00 | 0.00 | 35447.94 | 0.00 |
October | 50541.51 | 31-OCT-17:40 | 23459.17 | 8059.50 | 5507.06 | 0.00 | 5757.69 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 52046.21 | 29-NOV-17:19 | 23459.17 | 8059.50 | 5507.06 | 0.00 | 7447.97 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 53820.52 | 04-DEC-16:49 | 23459.17 | 8059.50 | 5507.06 | 0.00 | 7107.18 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 50541.51 | 23459.17 | 8059.50 | 0.00 | 0.00 | 5251.86 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 96994.64 | 23459.17 | 8059.50 | 5507.06 | 0.00 | 10363.37 | 0.00 | 0.00 | 49149.89 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 310047.61 | 30-JAN-17:00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 353922.28 | 02-FEB-12:09 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 230625.96 | 06-MAR-08:09 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 198465.66 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 95733.46 | 02-MAY-07:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 24016.07 | 05-JUN-08:20 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 89553.01 | 30-SEP-07:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 93744.14 | 27-OCT-07:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 260153.44 | 25-NOV-17:00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 297551.98 | 09-DEC-12:09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 353922.28 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 7.83 | 19.67 | 2.83 | 19.82 | 0.00 | 19.82 | 0.00 | 19.82 |
February | 4.83 | 19.31 | 1.67 | 19.55 | 0.00 | 19.55 | 0.00 | 19.55 |
March | 3.67 | 20.38 | 1.33 | 20.38 | 0.00 | 20.38 | 0.00 | 20.38 |
April | 0.67 | 20.42 | 0.17 | 20.42 | 0.00 | 20.42 | 0.00 | 20.42 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.33 | 20.54 | 0.00 | 20.54 | 0.00 | 20.54 | 0.00 | 20.54 |
November | 2.00 | 20.26 | 0.67 | 20.26 | 0.00 | 20.26 | 0.00 | 20.26 |
December | 5.50 | 19.35 | 1.17 | 19.51 | 0.00 | 19.51 | 0.00 | 19.51 |
Annual Sum or Average | 24.83 | 19.71 | 7.83 | 19.85 | 0.00 | 19.85 | 0.00 | 19.85 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 7.83 | 20.54 | 2.83 | 20.54 | 0.00 | 20.54 | 0.00 | 20.54 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.17 | 20.34 | 1.17 | 20.34 | 0.00 | 20.34 | 0.00 | 20.34 |
February | 2.17 | 20.30 | 0.67 | 20.29 | 0.00 | 20.29 | 0.00 | 20.29 |
March | 0.83 | 20.50 | 0.17 | 20.50 | 0.00 | 20.50 | 0.00 | 20.50 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.50 | 20.43 | 0.17 | 20.46 | 0.00 | 20.46 | 0.00 | 20.46 |
December | 1.33 | 20.34 | 0.67 | 20.35 | 0.00 | 20.35 | 0.00 | 20.35 |
Annual Sum or Average | 8.00 | 20.35 | 2.83 | 20.35 | 0.00 | 20.35 | 0.00 | 20.35 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3.17 | 20.50 | 1.17 | 20.50 | 0.00 | 20.50 | 0.00 | 20.50 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.50 | 20.30 | 0.00 | 20.30 | 0.00 | 20.30 | 0.00 | 20.30 |
February | 1.17 | 20.18 | 0.00 | 20.18 | 0.00 | 20.18 | 0.00 | 20.18 |
March | 0.17 | 20.29 | 0.00 | 20.29 | 0.00 | 20.29 | 0.00 | 20.29 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.50 | 20.39 | 0.00 | 20.39 | 0.00 | 20.39 | 0.00 | 20.39 |
December | 0.83 | 20.20 | 0.00 | 20.20 | 0.00 | 20.20 | 0.00 | 20.20 |
Annual Sum or Average | 5.17 | 20.27 | 0.00 | 20.27 | 0.00 | 20.27 | 0.00 | 20.27 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.50 | 20.39 | 0.00 | 20.39 | 0.00 | 20.39 | 0.00 | 20.39 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.83 | 19.97 | 0.00 | 19.97 | 0.00 | 19.97 | 0.00 | 19.97 |
February | 1.17 | 20.21 | 0.00 | 20.21 | 0.00 | 20.21 | 0.00 | 20.21 |
March | 0.17 | 20.21 | 0.00 | 20.21 | 0.00 | 20.21 | 0.00 | 20.21 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.50 | 20.31 | 0.00 | 20.31 | 0.00 | 20.31 | 0.00 | 20.31 |
December | 1.17 | 19.51 | 0.00 | 19.51 | 0.00 | 19.51 | 0.00 | 19.51 |
Annual Sum or Average | 5.83 | 19.96 | 0.00 | 19.96 | 0.00 | 19.96 | 0.00 | 19.96 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.83 | 20.31 | 0.00 | 20.31 | 0.00 | 20.31 | 0.00 | 20.31 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.67 | 20.30 | 0.00 | 20.30 | 0.00 | 20.30 | 0.00 | 20.30 |
February | 1.33 | 20.24 | 0.00 | 20.24 | 0.00 | 20.24 | 0.00 | 20.24 |
March | 0.67 | 20.41 | 0.00 | 20.41 | 0.00 | 20.41 | 0.00 | 20.41 |
April | 0.17 | 20.52 | 0.00 | 20.52 | 0.00 | 20.52 | 0.00 | 20.52 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.67 | 20.29 | 0.00 | 20.29 | 0.00 | 20.29 | 0.00 | 20.29 |
December | 1.00 | 20.23 | 0.00 | 20.23 | 0.00 | 20.23 | 0.00 | 20.23 |
Annual Sum or Average | 7.50 | 20.30 | 0.00 | 20.30 | 0.00 | 20.30 | 0.00 | 20.30 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3.67 | 20.52 | 0.00 | 20.52 | 0.00 | 20.52 | 0.00 | 20.52 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 4.83 | 19.79 | 0.00 | 19.79 | 0.00 | 19.79 | 0.00 | 19.79 |
February | 2.83 | 19.95 | 0.00 | 19.95 | 0.00 | 19.95 | 0.00 | 19.95 |
March | 1.50 | 20.38 | 0.00 | 20.38 | 0.00 | 20.38 | 0.00 | 20.38 |
April | 0.17 | 20.32 | 0.00 | 20.32 | 0.00 | 20.32 | 0.00 | 20.32 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1.17 | 20.24 | 0.00 | 20.24 | 0.00 | 20.24 | 0.00 | 20.24 |
December | 2.83 | 19.98 | 0.00 | 19.98 | 0.00 | 19.98 | 0.00 | 19.98 |
Annual Sum or Average | 13.33 | 19.98 | 0.00 | 19.98 | 0.00 | 19.98 | 0.00 | 19.98 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4.83 | 20.38 | 0.00 | 20.38 | 0.00 | 20.38 | 0.00 | 20.38 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 4.67 | 20.02 | 0.00 | 20.02 | 0.00 | 20.02 | 0.00 | 20.02 |
February | 2.83 | 19.94 | 0.00 | 19.94 | 0.00 | 19.94 | 0.00 | 19.94 |
March | 1.50 | 20.39 | 0.00 | 20.39 | 0.00 | 20.39 | 0.00 | 20.39 |
April | 0.17 | 20.32 | 0.00 | 20.32 | 0.00 | 20.32 | 0.00 | 20.32 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1.17 | 20.26 | 0.00 | 20.26 | 0.00 | 20.26 | 0.00 | 20.26 |
December | 2.50 | 20.32 | 0.00 | 20.32 | 0.00 | 20.32 | 0.00 | 20.32 |
Annual Sum or Average | 12.83 | 20.13 | 0.00 | 20.13 | 0.00 | 20.13 | 0.00 | 20.13 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4.67 | 20.39 | 0.00 | 20.39 | 0.00 | 20.39 | 0.00 | 20.39 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 4.83 | 19.80 | 0.00 | 19.80 | 0.00 | 19.80 | 0.00 | 19.80 |
February | 2.83 | 19.92 | 0.00 | 19.92 | 0.00 | 19.92 | 0.00 | 19.92 |
March | 1.50 | 20.37 | 0.00 | 20.37 | 0.00 | 20.37 | 0.00 | 20.37 |
April | 0.17 | 20.30 | 0.00 | 20.30 | 0.00 | 20.30 | 0.00 | 20.30 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1.17 | 20.24 | 0.00 | 20.24 | 0.00 | 20.24 | 0.00 | 20.24 |
December | 2.83 | 20.32 | 0.00 | 20.32 | 0.00 | 20.32 | 0.00 | 20.32 |
Annual Sum or Average | 13.33 | 20.05 | 0.00 | 20.05 | 0.00 | 20.05 | 0.00 | 20.05 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4.83 | 20.37 | 0.00 | 20.37 | 0.00 | 20.37 | 0.00 | 20.37 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 5.33 | 19.63 | 0.00 | 19.63 | 0.00 | 19.63 | 0.00 | 19.63 |
February | 3.67 | 19.76 | 0.00 | 19.76 | 0.00 | 19.76 | 0.00 | 19.76 |
March | 2.00 | 20.32 | 0.00 | 20.32 | 0.00 | 20.32 | 0.00 | 20.32 |
April | 0.50 | 20.37 | 0.00 | 20.37 | 0.00 | 20.37 | 0.00 | 20.37 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1.83 | 19.79 | 0.00 | 19.79 | 0.00 | 19.79 | 0.00 | 19.79 |
December | 4.67 | 20.13 | 0.00 | 20.13 | 0.00 | 20.13 | 0.00 | 20.13 |
Annual Sum or Average | 18.00 | 19.90 | 0.00 | 19.90 | 0.00 | 19.90 | 0.00 | 19.90 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 5.33 | 20.37 | 0.00 | 20.37 | 0.00 | 20.37 | 0.00 | 20.37 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 37.33 | 15.46 | 0.00 | 15.46 | 0.00 | 15.46 | 0.00 | 15.46 |
February | 24.00 | 15.75 | 0.00 | 15.75 | 0.00 | 15.75 | 0.00 | 15.75 |
March | 11.17 | 16.95 | 0.00 | 16.95 | 0.00 | 16.95 | 0.00 | 16.95 |
April | 3.83 | 18.21 | 0.00 | 18.21 | 0.00 | 18.21 | 0.00 | 18.21 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 10.00 | 16.47 | 0.00 | 16.47 | 0.00 | 16.47 | 0.00 | 16.47 |
December | 19.83 | 16.12 | 0.00 | 16.12 | 0.00 | 16.12 | 0.00 | 16.12 |
Annual Sum or Average | 106.17 | 16.00 | 0.00 | 16.00 | 0.00 | 16.00 | 0.00 | 16.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 37.33 | 18.21 | 0.00 | 18.21 | 0.00 | 18.21 | 0.00 | 18.21 |
Report: ComfortReportSimple55Monthly
For: LGSTORE1
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 496.00 | 21.03 | 484.33 | 21.03 | 484.33 | 21.03 |
February | 448.00 | 21.04 | 396.17 | 21.04 | 396.17 | 21.03 |
March | 497.00 | 21.11 | 322.50 | 21.07 | 322.50 | 21.06 |
April | 424.17 | 21.34 | 187.67 | 21.43 | 150.17 | 21.35 |
May | 307.83 | 22.33 | 117.33 | 22.71 | 21.67 | 22.72 |
June | 177.83 | 22.82 | 326.17 | 23.51 | 69.33 | 23.56 |
July | 152.17 | 23.88 | 474.00 | 23.88 | 149.17 | 23.88 |
August | 165.17 | 23.87 | 454.33 | 23.88 | 157.67 | 23.88 |
September | 189.50 | 22.07 | 212.17 | 22.99 | 6.17 | 22.96 |
October | 483.17 | 21.48 | 33.17 | 21.44 | 33.17 | 21.40 |
November | 480.00 | 21.16 | 265.50 | 21.12 | 265.50 | 21.10 |
December | 496.00 | 21.03 | 472.67 | 21.03 | 472.67 | 21.03 |
Annual Sum or Average | 4316.83 | 21.56 | 3746.00 | 21.88 | 2528.50 | 21.78 |
Minimum of Months | 152.17 | 21.03 | 33.17 | 21.03 | 6.17 | 21.03 |
Maximum of Months | 497.00 | 23.88 | 484.33 | 23.88 | 484.33 | 23.88 |
Report: ComfortReportSimple55Monthly
For: SMSTORE1
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 496.00 | 21.13 | 439.17 | 21.12 | 439.17 | 21.11 |
February | 448.00 | 21.23 | 266.67 | 21.18 | 266.67 | 21.16 |
March | 497.00 | 21.47 | 171.83 | 21.38 | 171.83 | 21.32 |
April | 411.33 | 21.82 | 81.33 | 21.93 | 42.00 | 21.86 |
May | 211.17 | 22.87 | 176.50 | 23.33 | 11.83 | 23.35 |
June | 118.67 | 23.17 | 332.33 | 23.69 | 44.17 | 23.71 |
July | 83.50 | 23.88 | 471.33 | 23.86 | 83.17 | 23.87 |
August | 100.50 | 23.88 | 457.33 | 23.87 | 99.00 | 23.87 |
September | 144.17 | 22.53 | 196.00 | 23.30 | 0.00 | 23.30 |
October | 450.83 | 22.09 | 3.50 | 22.09 | 2.17 | 22.09 |
November | 480.00 | 21.62 | 146.33 | 21.50 | 146.33 | 21.43 |
December | 496.00 | 21.21 | 364.83 | 21.17 | 364.83 | 21.15 |
Annual Sum or Average | 3937.17 | 21.77 | 3107.17 | 22.14 | 1671.17 | 22.01 |
Minimum of Months | 83.50 | 21.13 | 3.50 | 21.12 | 0.00 | 21.11 |
Maximum of Months | 497.00 | 23.88 | 471.33 | 23.87 | 439.17 | 23.87 |
Report: ComfortReportSimple55Monthly
For: SMSTORE2
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 371.00 | 21.11 | 351.33 | 21.11 | 351.33 | 21.11 |
February | 336.00 | 21.11 | 249.00 | 21.11 | 249.00 | 21.11 |
March | 379.00 | 21.19 | 185.17 | 21.17 | 185.17 | 21.15 |
April | 313.17 | 21.40 | 95.00 | 21.55 | 65.33 | 21.49 |
May | 191.50 | 22.58 | 124.50 | 23.10 | 11.83 | 23.12 |
June | 124.67 | 23.11 | 265.67 | 23.74 | 54.50 | 23.78 |
July | 94.33 | 24.11 | 361.67 | 24.04 | 94.00 | 24.05 |
August | 109.50 | 24.03 | 356.00 | 24.01 | 106.17 | 24.01 |
September | 124.33 | 22.08 | 168.83 | 23.18 | 1.33 | 23.17 |
October | 354.33 | 21.53 | 10.17 | 21.52 | 10.17 | 21.51 |
November | 360.00 | 21.26 | 147.83 | 21.22 | 147.83 | 21.19 |
December | 369.00 | 21.11 | 334.17 | 21.11 | 334.17 | 21.11 |
Annual Sum or Average | 3126.83 | 21.62 | 2649.33 | 22.04 | 1610.83 | 21.94 |
Minimum of Months | 94.33 | 21.11 | 10.17 | 21.11 | 1.33 | 21.11 |
Maximum of Months | 379.00 | 24.11 | 361.67 | 24.04 | 351.33 | 24.05 |
Report: ComfortReportSimple55Monthly
For: SMSTORE3
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 371.00 | 21.11 | 352.17 | 21.11 | 352.17 | 21.11 |
February | 336.00 | 21.11 | 263.83 | 21.11 | 263.83 | 21.11 |
March | 379.00 | 21.19 | 196.17 | 21.16 | 196.17 | 21.15 |
April | 314.00 | 21.38 | 104.33 | 21.51 | 76.17 | 21.45 |
May | 201.50 | 22.53 | 116.33 | 23.02 | 12.83 | 23.04 |
June | 127.17 | 23.06 | 264.67 | 23.72 | 55.00 | 23.76 |
July | 94.67 | 24.11 | 361.67 | 24.04 | 94.33 | 24.05 |
August | 111.17 | 24.02 | 355.00 | 24.01 | 107.17 | 24.01 |
September | 128.00 | 22.06 | 168.33 | 23.16 | 1.67 | 23.14 |
October | 360.00 | 21.51 | 13.17 | 21.49 | 13.17 | 21.48 |
November | 360.00 | 21.23 | 160.83 | 21.19 | 160.83 | 21.17 |
December | 369.00 | 21.11 | 340.83 | 21.11 | 340.83 | 21.11 |
Annual Sum or Average | 3151.50 | 21.61 | 2697.33 | 22.02 | 1674.17 | 21.92 |
Minimum of Months | 94.67 | 21.11 | 13.17 | 21.11 | 1.67 | 21.11 |
Maximum of Months | 379.00 | 24.11 | 361.67 | 24.04 | 352.17 | 24.05 |
Report: ComfortReportSimple55Monthly
For: SMSTORE4
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 371.00 | 21.11 | 353.67 | 21.11 | 353.67 | 21.11 |
February | 336.00 | 21.11 | 278.17 | 21.11 | 278.17 | 21.11 |
March | 379.00 | 21.17 | 214.50 | 21.15 | 214.50 | 21.14 |
April | 316.83 | 21.36 | 111.00 | 21.49 | 84.00 | 21.43 |
May | 223.00 | 22.43 | 100.50 | 22.87 | 13.67 | 22.89 |
June | 133.17 | 22.99 | 258.67 | 23.67 | 57.67 | 23.72 |
July | 98.83 | 24.09 | 360.17 | 24.03 | 98.33 | 24.04 |
August | 114.33 | 24.00 | 352.50 | 24.00 | 109.33 | 24.01 |
September | 134.83 | 22.02 | 165.33 | 23.10 | 2.17 | 23.08 |
October | 364.17 | 21.47 | 17.50 | 21.46 | 17.50 | 21.44 |
November | 360.00 | 21.20 | 173.67 | 21.17 | 173.67 | 21.15 |
December | 369.00 | 21.11 | 347.33 | 21.11 | 347.33 | 21.11 |
Annual Sum or Average | 3200.17 | 21.60 | 2733.00 | 21.99 | 1750.00 | 21.89 |
Minimum of Months | 98.83 | 21.11 | 17.50 | 21.11 | 2.17 | 21.11 |
Maximum of Months | 379.00 | 24.09 | 360.17 | 24.03 | 353.67 | 24.04 |
Report: ComfortReportSimple55Monthly
For: LGSTORE2
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.11 | 333.00 | 21.11 | 333.00 | 21.11 |
February | 308.00 | 21.11 | 282.83 | 21.11 | 282.83 | 21.11 |
March | 348.00 | 21.16 | 227.67 | 21.14 | 227.67 | 21.13 |
April | 294.00 | 21.34 | 124.33 | 21.44 | 101.00 | 21.38 |
May | 247.17 | 22.36 | 69.00 | 22.65 | 21.00 | 22.68 |
June | 122.00 | 22.80 | 213.67 | 23.54 | 50.33 | 23.60 |
July | 108.50 | 23.93 | 328.67 | 23.94 | 108.50 | 23.94 |
August | 112.67 | 23.91 | 319.33 | 23.92 | 109.67 | 23.92 |
September | 131.67 | 21.94 | 144.50 | 22.98 | 2.00 | 22.96 |
October | 339.50 | 21.44 | 19.17 | 21.42 | 19.17 | 21.41 |
November | 330.00 | 21.16 | 197.33 | 21.14 | 197.33 | 21.13 |
December | 338.00 | 21.11 | 328.50 | 21.11 | 328.50 | 21.11 |
Annual Sum or Average | 3019.50 | 21.59 | 2588.00 | 21.92 | 1781.00 | 21.83 |
Minimum of Months | 108.50 | 21.11 | 19.17 | 21.11 | 2.00 | 21.11 |
Maximum of Months | 348.00 | 23.93 | 333.00 | 23.94 | 333.00 | 23.94 |
Report: ComfortReportSimple55Monthly
For: SMSTORE5
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.11 | 332.50 | 21.11 | 332.50 | 21.11 |
February | 308.00 | 21.11 | 282.17 | 21.11 | 282.17 | 21.11 |
March | 348.00 | 21.15 | 229.67 | 21.14 | 229.67 | 21.13 |
April | 297.67 | 21.36 | 125.00 | 21.45 | 103.33 | 21.38 |
May | 267.00 | 22.38 | 65.00 | 22.63 | 22.33 | 22.65 |
June | 124.50 | 22.79 | 195.67 | 23.50 | 50.50 | 23.58 |
July | 110.00 | 23.94 | 326.17 | 23.94 | 110.00 | 23.94 |
August | 113.00 | 23.91 | 310.67 | 23.92 | 109.33 | 23.92 |
September | 136.83 | 21.99 | 132.67 | 22.94 | 2.33 | 22.93 |
October | 340.00 | 21.43 | 21.83 | 21.41 | 21.83 | 21.40 |
November | 330.00 | 21.16 | 199.00 | 21.14 | 199.00 | 21.13 |
December | 338.00 | 21.11 | 328.50 | 21.11 | 328.50 | 21.11 |
Annual Sum or Average | 3053.00 | 21.61 | 2548.83 | 21.91 | 1791.50 | 21.82 |
Minimum of Months | 110.00 | 21.11 | 21.83 | 21.11 | 2.33 | 21.11 |
Maximum of Months | 348.00 | 23.94 | 332.50 | 23.94 | 332.50 | 23.94 |
Report: ComfortReportSimple55Monthly
For: SMSTORE6
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.11 | 333.33 | 21.11 | 333.33 | 21.11 |
February | 308.00 | 21.11 | 283.67 | 21.11 | 283.67 | 21.11 |
March | 348.00 | 21.15 | 233.17 | 21.13 | 233.17 | 21.13 |
April | 298.83 | 21.36 | 131.67 | 21.43 | 110.67 | 21.37 |
May | 278.50 | 22.35 | 62.17 | 22.57 | 23.67 | 22.60 |
June | 127.33 | 22.78 | 189.33 | 23.48 | 51.50 | 23.56 |
July | 112.00 | 23.93 | 324.83 | 23.94 | 111.83 | 23.94 |
August | 115.00 | 23.90 | 309.17 | 23.92 | 110.67 | 23.92 |
September | 139.50 | 21.99 | 129.67 | 22.92 | 2.33 | 22.90 |
October | 340.00 | 21.42 | 23.83 | 21.40 | 23.83 | 21.38 |
November | 330.00 | 21.16 | 202.67 | 21.14 | 202.67 | 21.13 |
December | 338.00 | 21.11 | 329.00 | 21.11 | 329.00 | 21.11 |
Annual Sum or Average | 3075.17 | 21.61 | 2552.50 | 21.90 | 1816.33 | 21.82 |
Minimum of Months | 112.00 | 21.11 | 23.83 | 21.11 | 2.33 | 21.11 |
Maximum of Months | 348.00 | 23.93 | 333.33 | 23.94 | 333.33 | 23.94 |
Report: ComfortReportSimple55Monthly
For: SMSTORE7
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.11 | 336.00 | 21.11 | 336.00 | 21.11 |
February | 308.00 | 21.11 | 289.00 | 21.11 | 289.00 | 21.11 |
March | 348.00 | 21.14 | 246.50 | 21.13 | 246.50 | 21.12 |
April | 302.50 | 21.35 | 165.67 | 21.40 | 147.17 | 21.34 |
May | 295.67 | 22.24 | 59.50 | 22.44 | 28.00 | 22.47 |
June | 134.33 | 22.73 | 185.00 | 23.44 | 53.67 | 23.52 |
July | 118.00 | 23.91 | 317.83 | 23.93 | 114.33 | 23.93 |
August | 118.83 | 23.89 | 305.83 | 23.91 | 112.33 | 23.91 |
September | 144.17 | 21.94 | 124.67 | 22.85 | 3.00 | 22.83 |
October | 340.00 | 21.38 | 32.67 | 21.36 | 32.67 | 21.34 |
November | 330.00 | 21.15 | 211.67 | 21.13 | 211.67 | 21.13 |
December | 338.00 | 21.11 | 332.33 | 21.11 | 332.33 | 21.11 |
Annual Sum or Average | 3117.50 | 21.60 | 2606.67 | 21.87 | 1906.67 | 21.79 |
Minimum of Months | 118.00 | 21.11 | 32.67 | 21.11 | 3.00 | 21.11 |
Maximum of Months | 348.00 | 23.91 | 336.00 | 23.93 | 336.00 | 23.93 |
Report: ComfortReportSimple55Monthly
For: SMSTORE8
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.11 | 340.00 | 21.11 | 340.00 | 21.11 |
February | 308.00 | 21.11 | 304.00 | 21.11 | 304.00 | 21.11 |
March | 348.00 | 21.12 | 290.67 | 21.12 | 290.67 | 21.11 |
April | 310.33 | 21.34 | 219.83 | 21.34 | 207.83 | 21.29 |
May | 308.33 | 22.03 | 62.17 | 22.17 | 40.17 | 22.18 |
June | 151.33 | 22.69 | 176.50 | 23.37 | 59.33 | 23.46 |
July | 135.33 | 23.84 | 308.83 | 23.90 | 124.00 | 23.90 |
August | 126.83 | 23.85 | 298.67 | 23.90 | 114.50 | 23.90 |
September | 157.17 | 21.94 | 125.33 | 22.75 | 10.33 | 22.70 |
October | 340.00 | 21.34 | 76.17 | 21.30 | 76.17 | 21.27 |
November | 330.00 | 21.14 | 237.00 | 21.13 | 237.00 | 21.12 |
December | 338.00 | 21.11 | 338.00 | 21.11 | 338.00 | 21.11 |
Annual Sum or Average | 3193.33 | 21.59 | 2777.17 | 21.82 | 2142.00 | 21.74 |
Minimum of Months | 126.83 | 21.11 | 62.17 | 21.11 | 10.33 | 21.11 |
Maximum of Months | 348.00 | 23.85 | 340.00 | 23.90 | 340.00 | 23.90 |
Report: OccupantComfortDataSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 496.00000 | 21.03447 | 11.36993 | -0.7595 | 17.51635 |
February | 448.00000 | 21.04065 | 15.87532 | -0.6910 | 15.51731 |
March | 497.00000 | 21.11175 | 22.53493 | -0.5757 | 12.65573 |
April | 479.00000 | 21.63479 | 31.13422 | -0.3358 | 10.01171 |
May | 496.00000 | 22.89685 | 45.54361 | -0.8743 | 24.07427 |
June | 481.00000 | 23.48826 | 52.49563 | -0.5396 | 13.51362 |
July | 495.00000 | 23.88135 | 57.39149 | -0.3342 | 7.47936 |
August | 497.00000 | 23.87833 | 55.41049 | -0.3464 | 7.71776 |
September | 479.00000 | 23.15785 | 39.57478 | -0.7341 | 20.25151 |
October | 496.00000 | 21.54125 | 30.66084 | -0.2947 | 7.99898 |
November | 480.00000 | 21.16258 | 24.06030 | -0.5241 | 11.68597 |
December | 496.00000 | 21.02951 | 14.14564 | -0.7063 | 15.84961 |
Annual Sum or Average | 5840.00000 | 22.16167 | 33.45580 | -0.5589 | 13.67173 |
Minimum of Months | 448.00000 | 21.02951 | 11.36993 | -0.8743 | 7.47936 |
Maximum of Months | 497.00000 | 23.88135 | 57.39149 | -0.2947 | 24.07427 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 496.00000 | 21.13195 | 13.39096 | -0.6557 | 14.28441 |
February | 448.00000 | 21.22826 | 17.94384 | -0.5716 | 12.32010 |
March | 497.00000 | 21.47092 | 24.17911 | -0.4317 | 9.87475 |
April | 479.00000 | 22.11105 | 32.04549 | -0.1851 | 8.18016 |
May | 496.00000 | 23.44173 | 44.22319 | -0.6774 | 16.55586 |
June | 481.00000 | 23.68742 | 50.57522 | -0.4736 | 10.77952 |
July | 495.00000 | 23.85447 | 54.89823 | -0.3495 | 7.69736 |
August | 497.00000 | 23.86434 | 53.53776 | -0.3564 | 7.82046 |
September | 479.00000 | 23.45122 | 38.86059 | -0.6402 | 16.03627 |
October | 496.00000 | 22.25034 | 31.46687 | -0.1236 | 6.69193 |
November | 480.00000 | 21.62128 | 25.37705 | -0.3761 | 9.40832 |
December | 496.00000 | 21.21402 | 16.35704 | -0.5904 | 12.62911 |
Annual Sum or Average | 5840.00000 | 22.45084 | 33.66570 | -0.4520 | 11.01109 |
Minimum of Months | 448.00000 | 21.13195 | 13.39096 | -0.6774 | 6.69193 |
Maximum of Months | 497.00000 | 23.86434 | 54.89823 | -0.1236 | 16.55586 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 21.11000 | 10.40021 | -0.6960 | 15.36728 |
February | 336.00000 | 21.10989 | 15.08530 | -0.6253 | 13.50555 |
March | 379.00000 | 21.19479 | 21.42359 | -0.5098 | 10.96572 |
April | 360.00000 | 21.73636 | 30.20347 | -0.2731 | 9.14331 |
May | 375.00000 | 23.22389 | 44.18138 | -0.7431 | 19.21144 |
June | 366.00000 | 23.68776 | 51.29635 | -0.4678 | 11.64861 |
July | 369.00000 | 24.01774 | 56.19209 | -0.2936 | 7.11486 |
August | 379.00000 | 23.98661 | 54.26875 | -0.3145 | 7.36840 |
September | 360.00000 | 23.32058 | 38.56487 | -0.6745 | 18.25341 |
October | 371.00000 | 21.63685 | 30.01818 | -0.2538 | 7.47198 |
November | 360.00000 | 21.26112 | 23.74304 | -0.4653 | 10.45783 |
December | 369.00000 | 21.10992 | 13.21360 | -0.6454 | 13.93652 |
Annual Sum or Average | 4395.00000 | 22.29375 | 32.53892 | -0.4960 | 12.01892 |
Minimum of Months | 336.00000 | 21.10989 | 10.40021 | -0.7431 | 7.11486 |
Maximum of Months | 379.00000 | 24.01774 | 56.19209 | -0.2538 | 19.21144 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 21.11000 | 10.40027 | -0.7059 | 15.65686 |
February | 336.00000 | 21.10981 | 15.08529 | -0.6353 | 13.76759 |
March | 379.00000 | 21.18580 | 21.44092 | -0.5211 | 11.18562 |
April | 360.00000 | 21.71550 | 30.26487 | -0.2858 | 9.27536 |
May | 375.00000 | 23.15786 | 44.39868 | -0.7727 | 20.25358 |
June | 366.00000 | 23.66599 | 51.38331 | -0.4773 | 12.00830 |
July | 369.00000 | 24.01683 | 56.20684 | -0.2942 | 7.12376 |
August | 379.00000 | 23.98544 | 54.30108 | -0.3156 | 7.38307 |
September | 360.00000 | 23.29384 | 38.62351 | -0.6865 | 18.76281 |
October | 371.00000 | 21.57918 | 30.14349 | -0.2755 | 7.63146 |
November | 360.00000 | 21.22905 | 23.82054 | -0.4827 | 10.72534 |
December | 369.00000 | 21.10974 | 13.21376 | -0.6551 | 14.19999 |
Annual Sum or Average | 4395.00000 | 22.27394 | 32.59700 | -0.5081 | 12.31328 |
Minimum of Months | 336.00000 | 21.10974 | 10.40027 | -0.7727 | 7.12376 |
Maximum of Months | 379.00000 | 24.01683 | 56.20684 | -0.2755 | 20.25358 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 21.10994 | 10.40059 | -0.7188 | 16.04844 |
February | 336.00000 | 21.10991 | 15.08546 | -0.6487 | 14.13093 |
March | 379.00000 | 21.17249 | 21.46715 | -0.5374 | 11.52283 |
April | 360.00000 | 21.67924 | 30.37457 | -0.3053 | 9.47123 |
May | 375.00000 | 23.01930 | 44.85285 | -0.8290 | 22.28097 |
June | 366.00000 | 23.62273 | 51.67134 | -0.4980 | 12.67425 |
July | 369.00000 | 24.00986 | 56.44877 | -0.3018 | 7.21498 |
August | 379.00000 | 23.97787 | 54.53111 | -0.3234 | 7.48830 |
September | 360.00000 | 23.24055 | 38.79134 | -0.7109 | 19.67927 |
October | 371.00000 | 21.51594 | 30.28151 | -0.2993 | 7.82422 |
November | 360.00000 | 21.19759 | 23.89548 | -0.5025 | 11.06753 |
December | 369.00000 | 21.10993 | 13.21379 | -0.6683 | 14.57092 |
Annual Sum or Average | 4395.00000 | 22.24089 | 32.74271 | -0.5278 | 12.81492 |
Minimum of Months | 336.00000 | 21.10991 | 10.40059 | -0.8290 | 7.21498 |
Maximum of Months | 379.00000 | 24.00986 | 56.44877 | -0.2993 | 22.28097 |
Report: OccupantComfortDataSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.11000 | 11.79754 | -0.7610 | 17.35258 |
February | 308.00000 | 21.11000 | 16.52184 | -0.6893 | 15.25549 |
March | 348.00000 | 21.15629 | 22.99298 | -0.5781 | 12.44148 |
April | 330.00000 | 21.63170 | 31.95558 | -0.3455 | 10.00401 |
May | 344.00000 | 22.77916 | 47.02593 | -0.9323 | 26.07314 |
June | 336.00000 | 23.50992 | 53.10883 | -0.5488 | 14.01170 |
July | 338.00000 | 23.93454 | 57.76110 | -0.3349 | 7.56186 |
August | 348.00000 | 23.91317 | 55.84817 | -0.3526 | 7.80573 |
September | 330.00000 | 23.13683 | 40.06601 | -0.7602 | 21.43844 |
October | 340.00000 | 21.44226 | 31.91411 | -0.3376 | 8.20045 |
November | 330.00000 | 21.16346 | 25.38066 | -0.5463 | 11.98947 |
December | 338.00000 | 21.11000 | 14.63664 | -0.7109 | 15.79663 |
Annual Sum or Average | 4030.00000 | 22.17662 | 34.24865 | -0.5741 | 13.97954 |
Minimum of Months | 308.00000 | 21.11000 | 11.79754 | -0.9323 | 7.56186 |
Maximum of Months | 348.00000 | 23.93454 | 57.76110 | -0.3349 | 26.07314 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.10990 | 11.70119 | -0.7512 | 17.03095 |
February | 308.00000 | 21.11000 | 16.42686 | -0.6835 | 15.06969 |
March | 348.00000 | 21.15300 | 22.90852 | -0.5788 | 12.42217 |
April | 330.00000 | 21.62127 | 31.90112 | -0.3531 | 10.03331 |
May | 344.00000 | 22.72008 | 47.14524 | -0.9677 | 27.45429 |
June | 336.00000 | 23.49877 | 53.14159 | -0.5715 | 14.56580 |
July | 338.00000 | 23.93316 | 57.80485 | -0.3554 | 7.84864 |
August | 348.00000 | 23.91264 | 55.88075 | -0.3729 | 8.10747 |
September | 330.00000 | 23.12923 | 40.01636 | -0.7809 | 22.03995 |
October | 340.00000 | 21.43222 | 31.84331 | -0.3479 | 8.32008 |
November | 330.00000 | 21.16185 | 25.28730 | -0.5471 | 11.95659 |
December | 338.00000 | 21.11000 | 14.53866 | -0.7036 | 15.56735 |
Annual Sum or Average | 4030.00000 | 22.16774 | 34.21501 | -0.5839 | 14.19056 |
Minimum of Months | 308.00000 | 21.10990 | 11.70119 | -0.9677 | 7.84864 |
Maximum of Months | 348.00000 | 23.93316 | 57.80485 | -0.3479 | 27.45429 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.11000 | 11.70115 | -0.7531 | 17.09141 |
February | 308.00000 | 21.11000 | 16.42720 | -0.6863 | 15.14908 |
March | 348.00000 | 21.14941 | 22.91584 | -0.5837 | 12.52947 |
April | 330.00000 | 21.60821 | 31.94866 | -0.3611 | 10.12097 |
May | 344.00000 | 22.64298 | 47.40471 | -1.0005 | 28.80606 |
June | 336.00000 | 23.48276 | 53.26113 | -0.5816 | 14.91634 |
July | 338.00000 | 23.93085 | 57.90273 | -0.3596 | 7.91569 |
August | 348.00000 | 23.91117 | 55.96174 | -0.3767 | 8.17116 |
September | 330.00000 | 23.11091 | 40.08062 | -0.7913 | 22.44766 |
October | 340.00000 | 21.41797 | 31.87609 | -0.3555 | 8.40592 |
November | 330.00000 | 21.15810 | 25.29433 | -0.5517 | 12.04671 |
December | 338.00000 | 21.11000 | 14.53896 | -0.7062 | 15.64419 |
Annual Sum or Average | 4030.00000 | 22.15513 | 34.27550 | -0.5918 | 14.42836 |
Minimum of Months | 308.00000 | 21.11000 | 11.70115 | -1.0005 | 7.91569 |
Maximum of Months | 348.00000 | 23.93085 | 57.90273 | -0.3555 | 28.80606 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.11000 | 11.70140 | -0.7646 | 17.45724 |
February | 308.00000 | 21.11000 | 16.42747 | -0.7000 | 15.54532 |
March | 348.00000 | 21.13850 | 22.93745 | -0.6024 | 12.96703 |
April | 330.00000 | 21.56942 | 32.08217 | -0.3862 | 10.46097 |
May | 344.00000 | 22.47071 | 47.98036 | -1.0717 | 31.85689 |
June | 336.00000 | 23.44118 | 53.55027 | -0.6045 | 15.76231 |
July | 338.00000 | 23.92239 | 58.14597 | -0.3676 | 8.06117 |
August | 348.00000 | 23.90566 | 56.15276 | -0.3834 | 8.29795 |
September | 330.00000 | 23.06350 | 40.23287 | -0.8148 | 23.41820 |
October | 340.00000 | 21.38203 | 31.95711 | -0.3750 | 8.65397 |
November | 330.00000 | 21.14928 | 25.31003 | -0.5667 | 12.37879 |
December | 338.00000 | 21.10994 | 14.53920 | -0.7194 | 16.03854 |
Annual Sum or Average | 4030.00000 | 22.12401 | 34.41909 | -0.6126 | 15.06990 |
Minimum of Months | 308.00000 | 21.10994 | 11.70140 | -1.0717 | 8.06117 |
Maximum of Months | 348.00000 | 23.92239 | 58.14597 | -0.3676 | 31.85689 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.11000 | 11.48757 | -0.8373 | 19.95062 |
February | 308.00000 | 21.11000 | 16.22104 | -0.7751 | 17.92633 |
March | 348.00000 | 21.11949 | 22.72144 | -0.6790 | 15.03192 |
April | 330.00000 | 21.49776 | 32.10902 | -0.4679 | 12.01032 |
May | 344.00000 | 22.22003 | 48.53802 | -1.2039 | 37.90151 |
June | 336.00000 | 23.36776 | 53.92055 | -0.6528 | 17.73352 |
July | 338.00000 | 23.90147 | 58.61099 | -0.3798 | 8.37319 |
August | 348.00000 | 23.89058 | 56.48454 | -0.3909 | 8.52649 |
September | 330.00000 | 22.98462 | 40.30825 | -0.8570 | 25.44757 |
October | 340.00000 | 21.34205 | 31.83257 | -0.4236 | 9.47973 |
November | 330.00000 | 21.13760 | 25.18464 | -0.6249 | 13.89904 |
December | 338.00000 | 21.11000 | 14.34311 | -0.7898 | 18.31029 |
Annual Sum or Average | 4030.00000 | 22.07514 | 34.48390 | -0.6730 | 17.04450 |
Minimum of Months | 308.00000 | 21.11000 | 11.48757 | -1.2039 | 8.37319 |
Maximum of Months | 348.00000 | 23.90147 | 58.61099 | -0.3798 | 37.90151 |
Report: DXReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 |
April | 0.152756E+10 | 0.398723E+09 | 46.58 | 0.105909E+10 | 0.468470E+09 | 0.00 | 0.84 | 16-APR-16:10 | 0.00 | 01-APR-00:05 | 18204.31 | 16-APR-16:10 | 12912.23 | 16-APR-16:05 | 5740.85 | 18-APR-12:40 | 4598.32 | 16-APR-16:10 | 0.00 | 01-APR-00:05 |
May | 0.253264E+10 | 0.665296E+09 | 98.60 | 0.176992E+10 | 0.762722E+09 | 0.00 | 0.83 | 31-MAY-13:30 | 0.00 | 01-MAY-00:10 | 17702.38 | 31-MAY-17:00 | 13907.77 | 31-MAY-15:00 | 5929.88 | 29-MAY-14:00 | 4615.83 | 31-MAY-13:00 | 0.00 | 01-MAY-00:10 |
June | 0.127936E+11 | 0.323658E+10 | 317.17 | 0.859408E+10 | 0.419955E+10 | 0.00 | 1.00 | 11-JUN-12:10 | 0.00 | 01-JUN-00:10 | 48670.56 | 27-JUN-07:03 | 27928.30 | 26-JUN-07:03 | 23579.23 | 30-JUN-07:03 | 10547.24 | 27-JUN-07:03 | 0.00 | 01-JUN-00:10 |
July | 0.178686E+11 | 0.441061E+10 | 431.34 | 0.110864E+11 | 0.678215E+10 | 0.00 | 1.00 | 02-JUL-07:03 | 0.00 | 01-JUL-00:05 | 47378.88 | 04-JUL-07:02 | 24588.09 | 04-JUL-07:02 | 24940.47 | 07-JUL-07:03 | 10125.22 | 04-JUL-07:02 | 0.00 | 01-JUL-00:05 |
August | 0.161643E+11 | 0.401638E+10 | 410.42 | 0.103090E+11 | 0.585523E+10 | 0.00 | 1.00 | 02-AUG-16:10 | 0.00 | 01-AUG-00:10 | 49606.16 | 04-AUG-07:02 | 25382.55 | 03-AUG-07:02 | 24414.29 | 04-AUG-07:02 | 10594.79 | 04-AUG-07:02 | 0.00 | 01-AUG-00:10 |
September | 0.754283E+10 | 0.195355E+10 | 224.51 | 0.604185E+10 | 0.150098E+10 | 0.00 | 1.00 | 06-SEP-13:30 | 0.00 | 01-SEP-00:10 | 36557.87 | 11-SEP-07:03 | 20338.17 | 11-SEP-07:03 | 16219.71 | 11-SEP-07:03 | 7862.96 | 11-SEP-07:03 | 0.00 | 01-SEP-00:10 |
October | 41524702.85 | 11685102.53 | 4.83 | 39798503.74 | 1726199.11 | 0.00 | 0.26 | 20-OCT-15:00 | 0.00 | 01-OCT-00:10 | 4448.15 | 20-OCT-15:00 | 4339.13 | 20-OCT-15:00 | 153.96 | 20-OCT-15:30 | 1246.10 | 20-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 |
Annual Sum or Average | 0.584710E+11 | 0.146928E+11 | 1533.46 | 0.389002E+11 | 0.195708E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.178686E+11 | 0.441061E+10 | 431.34 | 0.110864E+11 | 0.678215E+10 | 0.00 | 1.00 | 0.00 | 49606.16 | 27928.30 | 24940.47 | 10594.79 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 |
March | 1050323.69 | 290116.60 | 0.58 | 807637.02 | 242686.67 | 0.00 | 0.18 | 19-MAR-17:10 | 0.00 | 01-MAR-00:03 | 1667.80 | 19-MAR-17:10 | 1278.58 | 19-MAR-17:10 | 389.22 | 19-MAR-17:10 | 452.68 | 19-MAR-17:10 | 0.00 | 01-MAR-00:03 |
April | 0.996685E+09 | 0.249401E+09 | 51.72 | 0.707667E+09 | 0.289018E+09 | 0.00 | 1.00 | 15-APR-20:02 | 0.00 | 01-APR-00:05 | 24652.50 | 16-APR-19:40 | 17677.32 | 15-APR-20:10 | 9699.89 | 16-APR-21:52 | 5379.85 | 16-APR-19:40 | 0.00 | 01-APR-00:05 |
May | 0.185986E+10 | 0.464119E+09 | 120.84 | 0.130986E+10 | 0.550004E+09 | 0.00 | 1.00 | 07-MAY-17:02 | 0.00 | 01-MAY-00:10 | 24846.97 | 29-MAY-17:03 | 18297.00 | 07-MAY-17:08 | 11613.51 | 29-MAY-19:34 | 5315.11 | 31-MAY-20:12 | 0.00 | 01-MAY-00:10 |
June | 0.769358E+10 | 0.188223E+10 | 317.69 | 0.527231E+10 | 0.242127E+10 | 0.00 | 1.00 | 08-JUN-20:02 | 0.00 | 01-JUN-00:10 | 25653.96 | 27-JUN-07:03 | 18643.21 | 23-JUN-20:08 | 12608.52 | 14-JUN-20:10 | 5484.87 | 27-JUN-07:03 | 0.00 | 01-JUN-00:10 |
July | 0.110118E+11 | 0.261564E+10 | 417.24 | 0.696938E+10 | 0.404246E+10 | 0.00 | 1.00 | 01-JUL-19:12 | 0.00 | 01-JUL-00:05 | 25667.58 | 26-JUL-22:33 | 19721.78 | 23-JUL-18:50 | 14106.34 | 17-JUL-20:03 | 5447.22 | 16-JUL-19:03 | 0.00 | 01-JUL-00:05 |
August | 0.979430E+10 | 0.235212E+10 | 402.78 | 0.632362E+10 | 0.347069E+10 | 0.00 | 1.00 | 01-AUG-20:03 | 0.00 | 01-AUG-00:10 | 25776.75 | 28-AUG-20:03 | 19929.93 | 06-AUG-17:01 | 14413.30 | 28-AUG-20:03 | 5478.72 | 03-AUG-07:02 | 0.00 | 01-AUG-00:10 |
September | 0.475009E+10 | 0.117369E+10 | 218.05 | 0.381830E+10 | 0.931793E+09 | 0.00 | 1.00 | 01-SEP-20:01 | 0.00 | 01-SEP-00:10 | 24841.02 | 11-SEP-22:44 | 20132.15 | 09-SEP-18:02 | 12040.19 | 11-SEP-20:03 | 5281.16 | 02-SEP-18:02 | 0.00 | 01-SEP-00:10 |
October | 43951120.59 | 11963233.61 | 10.11 | 41541929.88 | 2409190.72 | 0.00 | 0.33 | 20-OCT-15:00 | 0.00 | 01-OCT-00:10 | 3051.54 | 20-OCT-15:00 | 3015.30 | 20-OCT-15:00 | 638.37 | 02-OCT-20:10 | 823.96 | 20-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 3826783.54 | 1055769.05 | 1.92 | 3235422.78 | 591360.76 | 0.00 | 0.15 | 07-NOV-21:30 | 0.00 | 01-NOV-00:10 | 1356.99 | 07-NOV-21:30 | 1187.83 | 03-NOV-20:30 | 347.31 | 07-NOV-21:30 | 371.46 | 07-NOV-21:30 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 |
Annual Sum or Average | 0.361552E+11 | 0.875051E+10 | 1540.93 | 0.244467E+11 | 0.117085E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.110118E+11 | 0.261564E+10 | 417.24 | 0.696938E+10 | 0.404246E+10 | 0.00 | 1.00 | 0.00 | 25776.75 | 20132.15 | 14413.30 | 5484.87 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_3:3 COOLING COIL
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 |
April | 0.670496E+09 | 0.170430E+09 | 35.83 | 0.470892E+09 | 0.199604E+09 | 0.00 | 0.84 | 18-APR-14:00 | 0.00 | 01-APR-00:05 | 9726.80 | 18-APR-14:00 | 6796.31 | 18-APR-14:00 | 3124.06 | 18-APR-12:40 | 2391.09 | 18-APR-14:00 | 0.00 | 01-APR-00:05 |
May | 0.126307E+10 | 0.325358E+09 | 96.33 | 0.906801E+09 | 0.356272E+09 | 0.00 | 0.86 | 31-MAY-13:00 | 0.00 | 01-MAY-00:10 | 9742.38 | 31-MAY-13:00 | 7755.50 | 31-MAY-13:00 | 3216.43 | 29-MAY-14:00 | 2484.38 | 31-MAY-13:00 | 0.00 | 01-MAY-00:10 |
June | 0.556326E+10 | 0.137762E+10 | 256.59 | 0.380210E+10 | 0.176117E+10 | 0.00 | 1.00 | 11-JUN-07:03 | 0.00 | 01-JUN-00:10 | 26003.74 | 26-JUN-06:02 | 13453.07 | 27-JUN-06:02 | 13715.75 | 26-JUN-06:02 | 5434.16 | 26-JUN-06:02 | 0.00 | 01-JUN-00:10 |
July | 0.762816E+10 | 0.184779E+10 | 330.65 | 0.488665E+10 | 0.274151E+10 | 0.00 | 1.00 | 02-JUL-07:03 | 0.00 | 01-JUL-00:05 | 25738.47 | 27-JUL-06:03 | 13852.24 | 02-JUL-07:03 | 14611.45 | 20-JUL-06:03 | 5379.78 | 26-JUL-06:03 | 0.00 | 01-JUL-00:05 |
August | 0.747167E+10 | 0.182532E+10 | 341.13 | 0.491466E+10 | 0.255701E+10 | 0.00 | 1.00 | 02-AUG-16:10 | 0.00 | 01-AUG-00:10 | 26636.13 | 04-AUG-06:02 | 14286.44 | 03-AUG-06:02 | 13347.03 | 04-AUG-06:02 | 5500.71 | 03-AUG-06:02 | 0.00 | 01-AUG-00:10 |
September | 0.333489E+10 | 0.849130E+09 | 175.28 | 0.274830E+10 | 0.586591E+09 | 0.00 | 1.00 | 06-SEP-13:50 | 0.00 | 01-SEP-00:10 | 24570.12 | 11-SEP-06:03 | 14185.20 | 11-SEP-06:03 | 10384.91 | 11-SEP-06:03 | 5203.60 | 11-SEP-06:03 | 0.00 | 01-SEP-00:10 |
October | 28520885.89 | 7824879.04 | 6.00 | 27449210.21 | 1071675.68 | 0.00 | 0.30 | 20-OCT-15:00 | 0.00 | 01-OCT-00:10 | 2698.05 | 20-OCT-15:00 | 2669.20 | 20-OCT-15:00 | 146.84 | 21-OCT-15:00 | 735.85 | 20-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 |
Annual Sum or Average | 0.259601E+11 | 0.640348E+10 | 1241.82 | 0.177569E+11 | 0.820322E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.762816E+10 | 0.184779E+10 | 341.13 | 0.491466E+10 | 0.274151E+10 | 0.00 | 1.00 | 0.00 | 26636.13 | 14286.44 | 14611.45 | 5500.71 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_4:4 COOLING COIL
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 |
April | 0.650531E+09 | 0.165824E+09 | 35.67 | 0.455945E+09 | 0.194587E+09 | 0.00 | 0.83 | 18-APR-14:00 | 0.00 | 01-APR-00:05 | 9632.14 | 18-APR-14:00 | 6722.70 | 18-APR-14:00 | 3098.49 | 18-APR-12:40 | 2373.72 | 18-APR-14:00 | 0.00 | 01-APR-00:05 |
May | 0.120456E+10 | 0.311165E+09 | 90.83 | 0.865336E+09 | 0.339224E+09 | 0.00 | 0.85 | 31-MAY-13:00 | 0.00 | 01-MAY-00:10 | 9675.19 | 31-MAY-13:00 | 7698.40 | 31-MAY-13:00 | 3116.19 | 29-MAY-14:00 | 2472.21 | 31-MAY-13:00 | 0.00 | 01-MAY-00:10 |
June | 0.553573E+10 | 0.137161E+10 | 254.51 | 0.378299E+10 | 0.175274E+10 | 0.00 | 1.00 | 11-JUN-07:03 | 0.00 | 01-JUN-00:10 | 26072.83 | 26-JUN-06:02 | 13496.77 | 27-JUN-06:02 | 13743.06 | 26-JUN-06:02 | 5448.40 | 26-JUN-06:02 | 0.00 | 01-JUN-00:10 |
July | 0.762127E+10 | 0.184699E+10 | 330.48 | 0.488231E+10 | 0.273896E+10 | 0.00 | 1.00 | 02-JUL-07:03 | 0.00 | 01-JUL-00:05 | 25806.20 | 27-JUL-06:03 | 13896.97 | 02-JUL-07:03 | 14607.70 | 20-JUL-06:03 | 5393.80 | 26-JUL-06:03 | 0.00 | 01-JUL-00:05 |
August | 0.744441E+10 | 0.182004E+10 | 340.47 | 0.489686E+10 | 0.254755E+10 | 0.00 | 1.00 | 03-AUG-06:02 | 0.00 | 01-AUG-00:10 | 26709.71 | 04-AUG-06:02 | 14333.66 | 03-AUG-06:02 | 13363.88 | 04-AUG-06:02 | 5515.11 | 03-AUG-06:02 | 0.00 | 01-AUG-00:10 |
September | 0.331952E+10 | 0.845740E+09 | 175.11 | 0.273439E+10 | 0.585137E+09 | 0.00 | 1.00 | 06-SEP-13:50 | 0.00 | 01-SEP-00:10 | 24635.54 | 11-SEP-06:03 | 14232.68 | 11-SEP-06:03 | 10402.86 | 11-SEP-06:03 | 5217.38 | 11-SEP-06:03 | 0.00 | 01-SEP-00:10 |
October | 25134915.66 | 6920183.11 | 5.50 | 24315948.81 | 818966.84 | 0.00 | 0.28 | 20-OCT-15:00 | 0.00 | 01-OCT-00:10 | 2554.90 | 20-OCT-15:00 | 2528.26 | 20-OCT-15:00 | 108.69 | 21-OCT-15:00 | 699.69 | 20-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 |
Annual Sum or Average | 0.258012E+11 | 0.636828E+10 | 1232.57 | 0.176421E+11 | 0.815902E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.762127E+10 | 0.184699E+10 | 340.47 | 0.489686E+10 | 0.273896E+10 | 0.00 | 1.00 | 0.00 | 26709.71 | 14333.66 | 14607.70 | 5515.11 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_5:5 COOLING COIL
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 |
April | 0.608106E+09 | 0.155705E+09 | 34.17 | 0.423949E+09 | 0.184157E+09 | 0.00 | 0.81 | 18-APR-14:00 | 0.00 | 01-APR-00:05 | 9356.86 | 18-APR-14:00 | 6502.63 | 18-APR-14:00 | 3031.67 | 18-APR-12:40 | 2315.30 | 18-APR-14:00 | 0.00 | 01-APR-00:05 |
May | 0.109385E+10 | 0.284006E+09 | 83.17 | 0.786032E+09 | 0.307814E+09 | 0.00 | 0.84 | 31-MAY-13:00 | 0.00 | 01-MAY-00:10 | 9439.28 | 31-MAY-13:00 | 7492.05 | 31-MAY-13:00 | 2915.77 | 29-MAY-13:50 | 2420.25 | 31-MAY-13:00 | 0.00 | 01-MAY-00:10 |
June | 0.533772E+10 | 0.132550E+10 | 250.01 | 0.363934E+10 | 0.169837E+10 | 0.00 | 1.00 | 11-JUN-12:40 | 0.00 | 01-JUN-00:10 | 25881.56 | 26-JUN-06:02 | 13360.71 | 27-JUN-06:02 | 13673.46 | 26-JUN-06:02 | 5408.97 | 26-JUN-06:02 | 0.00 | 01-JUN-00:10 |
July | 0.737407E+10 | 0.179085E+10 | 325.27 | 0.471339E+10 | 0.266068E+10 | 0.00 | 1.00 | 02-JUL-07:03 | 0.00 | 01-JUL-00:05 | 25618.62 | 27-JUL-06:03 | 13760.55 | 02-JUL-07:03 | 14208.97 | 07-JUL-06:03 | 5354.65 | 26-JUL-06:03 | 0.00 | 01-JUL-00:05 |
August | 0.719669E+10 | 0.176342E+10 | 337.28 | 0.472558E+10 | 0.247112E+10 | 0.00 | 1.00 | 03-AUG-06:02 | 0.00 | 01-AUG-00:10 | 26507.40 | 04-AUG-06:02 | 14079.45 | 03-AUG-06:02 | 13412.56 | 04-AUG-06:02 | 5474.95 | 03-AUG-06:02 | 0.00 | 01-AUG-00:10 |
September | 0.320944E+10 | 0.819548E+09 | 170.61 | 0.263989E+10 | 0.569548E+09 | 0.00 | 1.00 | 06-SEP-14:00 | 0.00 | 01-SEP-00:10 | 23658.11 | 11-SEP-06:03 | 13627.42 | 11-SEP-06:03 | 10030.69 | 11-SEP-06:03 | 5010.91 | 11-SEP-06:03 | 0.00 | 01-SEP-00:10 |
October | 20338031.59 | 5630947.33 | 4.83 | 19772031.59 | 566000.00 | 0.00 | 0.26 | 20-OCT-15:00 | 0.00 | 01-OCT-00:10 | 2308.05 | 20-OCT-15:00 | 2281.94 | 20-OCT-15:00 | 56.82 | 20-OCT-15:30 | 636.12 | 20-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 |
Annual Sum or Average | 0.248402E+11 | 0.614466E+10 | 1205.33 | 0.169480E+11 | 0.789226E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.737407E+10 | 0.179085E+10 | 337.28 | 0.472558E+10 | 0.266068E+10 | 0.00 | 1.00 | 0.00 | 26507.40 | 14079.45 | 14208.97 | 5474.95 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_6:6 COOLING COIL
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 |
April | 0.102742E+10 | 0.267336E+09 | 30.67 | 0.694878E+09 | 0.332544E+09 | 0.00 | 0.83 | 18-APR-14:20 | 0.00 | 01-APR-00:05 | 17431.92 | 18-APR-14:20 | 11796.67 | 18-APR-14:40 | 5968.55 | 18-APR-12:40 | 4353.88 | 18-APR-14:20 | 0.00 | 01-APR-00:05 |
May | 0.179592E+10 | 0.476514E+09 | 72.42 | 0.126539E+10 | 0.530528E+09 | 0.00 | 0.85 | 31-MAY-13:00 | 0.00 | 01-MAY-00:10 | 17460.06 | 31-MAY-13:00 | 13542.44 | 31-MAY-15:00 | 5055.90 | 30-MAY-13:00 | 4523.76 | 31-MAY-13:00 | 0.00 | 01-MAY-00:10 |
June | 0.938430E+10 | 0.236889E+10 | 237.90 | 0.627251E+10 | 0.311179E+10 | 0.00 | 1.00 | 11-JUN-13:00 | 0.00 | 01-JUN-00:10 | 46712.81 | 26-JUN-07:03 | 26940.08 | 26-JUN-07:03 | 21951.21 | 30-JUN-07:03 | 10117.33 | 27-JUN-07:03 | 0.00 | 01-JUN-00:10 |
July | 0.131583E+11 | 0.324614E+10 | 315.39 | 0.816608E+10 | 0.499226E+10 | 0.00 | 1.00 | 02-JUL-08:62 | 0.00 | 01-JUL-00:05 | 46327.94 | 07-JUL-07:03 | 25979.38 | 02-JUL-08:62 | 25539.60 | 07-JUL-07:03 | 10105.29 | 02-JUL-08:62 | 0.00 | 01-JUL-00:05 |
August | 0.127061E+11 | 0.316421E+10 | 327.83 | 0.812861E+10 | 0.457752E+10 | 0.00 | 1.00 | 02-AUG-14:30 | 0.00 | 01-AUG-00:10 | 47356.31 | 04-AUG-07:02 | 25645.03 | 03-AUG-07:02 | 22504.78 | 04-AUG-07:02 | 10158.06 | 04-AUG-07:02 | 0.00 | 01-AUG-00:10 |
September | 0.570771E+10 | 0.148077E+10 | 162.12 | 0.458633E+10 | 0.112138E+10 | 0.00 | 1.00 | 06-SEP-13:50 | 0.00 | 01-SEP-00:10 | 44659.81 | 11-SEP-07:03 | 25341.60 | 11-SEP-07:03 | 19318.21 | 11-SEP-07:03 | 9603.82 | 11-SEP-07:03 | 0.00 | 01-SEP-00:10 |
October | 32953492.11 | 9317280.38 | 4.83 | 31333121.62 | 1620370.49 | 0.00 | 0.26 | 20-OCT-15:00 | 0.00 | 01-OCT-00:10 | 4275.71 | 20-OCT-15:00 | 4132.89 | 20-OCT-15:00 | 157.06 | 21-OCT-15:00 | 1197.80 | 20-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 |
Annual Sum or Average | 0.438128E+11 | 0.110132E+11 | 1151.16 | 0.291451E+11 | 0.146676E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.131583E+11 | 0.324614E+10 | 327.83 | 0.816608E+10 | 0.499226E+10 | 0.00 | 1.00 | 0.00 | 47356.31 | 26940.08 | 25539.60 | 10158.06 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_7:7 COOLING COIL
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 |
April | 0.515192E+09 | 0.131867E+09 | 30.25 | 0.348468E+09 | 0.166724E+09 | 0.00 | 0.83 | 18-APR-14:50 | 0.00 | 01-APR-00:05 | 8925.99 | 18-APR-14:20 | 6050.61 | 18-APR-14:50 | 3034.82 | 18-APR-12:40 | 2193.01 | 18-APR-14:50 | 0.00 | 01-APR-00:05 |
May | 0.884663E+09 | 0.231001E+09 | 68.00 | 0.625232E+09 | 0.259431E+09 | 0.00 | 0.85 | 31-MAY-13:00 | 0.00 | 01-MAY-00:10 | 8953.79 | 31-MAY-13:00 | 6961.82 | 31-MAY-15:00 | 2569.69 | 30-MAY-13:00 | 2281.30 | 31-MAY-13:00 | 0.00 | 01-MAY-00:10 |
June | 0.478716E+10 | 0.118808E+10 | 235.61 | 0.320455E+10 | 0.158262E+10 | 0.00 | 1.00 | 11-JUN-13:00 | 0.00 | 01-JUN-00:10 | 24039.63 | 26-JUN-07:03 | 13859.72 | 26-JUN-07:03 | 11273.18 | 30-JUN-07:03 | 5114.84 | 27-JUN-07:03 | 0.00 | 01-JUN-00:10 |
July | 0.672423E+10 | 0.163070E+10 | 314.02 | 0.418203E+10 | 0.254220E+10 | 0.00 | 1.00 | 02-JUL-08:62 | 0.00 | 01-JUL-00:05 | 23826.31 | 02-JUL-08:62 | 13385.03 | 02-JUL-08:62 | 12708.22 | 07-JUL-07:03 | 5108.95 | 02-JUL-08:62 | 0.00 | 01-JUL-00:05 |
August | 0.649034E+10 | 0.158888E+10 | 324.56 | 0.416259E+10 | 0.232776E+10 | 0.00 | 1.00 | 02-AUG-14:30 | 0.00 | 01-AUG-00:10 | 24358.53 | 04-AUG-07:02 | 13199.09 | 03-AUG-07:02 | 11568.03 | 04-AUG-07:02 | 5135.08 | 04-AUG-07:02 | 0.00 | 01-AUG-00:10 |
September | 0.292435E+10 | 0.745318E+09 | 159.46 | 0.235353E+10 | 0.570818E+09 | 0.00 | 1.00 | 06-SEP-13:50 | 0.00 | 01-SEP-00:10 | 21919.45 | 11-SEP-07:03 | 12441.64 | 11-SEP-07:03 | 9477.82 | 11-SEP-07:03 | 4631.31 | 11-SEP-07:03 | 0.00 | 01-SEP-00:10 |
October | 15100562.31 | 4201510.72 | 4.33 | 14430000.30 | 670562.01 | 0.00 | 0.26 | 20-OCT-15:00 | 0.00 | 01-OCT-00:10 | 2144.64 | 20-OCT-15:00 | 2076.55 | 20-OCT-15:00 | 70.03 | 20-OCT-15:20 | 591.25 | 20-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 |
Annual Sum or Average | 0.223410E+11 | 0.552004E+10 | 1136.22 | 0.148908E+11 | 0.745022E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.672423E+10 | 0.163070E+10 | 324.56 | 0.418203E+10 | 0.254220E+10 | 0.00 | 1.00 | 0.00 | 24358.53 | 13859.72 | 12708.22 | 5135.08 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_8:8 COOLING COIL
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 |
April | 0.498752E+09 | 0.127911E+09 | 29.17 | 0.336369E+09 | 0.162382E+09 | 0.00 | 0.82 | 18-APR-14:40 | 0.00 | 01-APR-00:05 | 8772.93 | 18-APR-14:40 | 5931.84 | 18-APR-14:50 | 2989.20 | 18-APR-12:40 | 2160.53 | 18-APR-14:40 | 0.00 | 01-APR-00:05 |
May | 0.842038E+09 | 0.220418E+09 | 66.00 | 0.595565E+09 | 0.246473E+09 | 0.00 | 0.84 | 31-MAY-15:00 | 0.00 | 01-MAY-00:10 | 8819.68 | 31-MAY-13:00 | 6858.38 | 31-MAY-15:00 | 2523.49 | 30-MAY-13:00 | 2251.49 | 31-MAY-13:00 | 0.00 | 01-MAY-00:10 |
June | 0.471158E+10 | 0.116997E+10 | 233.49 | 0.314960E+10 | 0.156198E+10 | 0.00 | 1.00 | 11-JUN-13:00 | 0.00 | 01-JUN-00:10 | 23911.07 | 26-JUN-07:03 | 13738.07 | 26-JUN-07:03 | 11232.15 | 30-JUN-07:03 | 5088.79 | 27-JUN-07:03 | 0.00 | 01-JUN-00:10 |
July | 0.663254E+10 | 0.160927E+10 | 311.47 | 0.411951E+10 | 0.251302E+10 | 0.00 | 1.00 | 02-JUL-08:62 | 0.00 | 01-JUL-00:05 | 23703.69 | 02-JUL-08:62 | 13299.32 | 02-JUL-08:62 | 12149.33 | 05-JUL-07:03 | 5082.87 | 02-JUL-08:62 | 0.00 | 01-JUL-00:05 |
August | 0.640472E+10 | 0.156863E+10 | 322.17 | 0.410312E+10 | 0.230160E+10 | 0.00 | 1.00 | 02-AUG-14:30 | 0.00 | 01-AUG-00:10 | 24234.50 | 04-AUG-07:02 | 13080.66 | 03-AUG-07:02 | 11559.15 | 04-AUG-07:02 | 5108.96 | 04-AUG-07:02 | 0.00 | 01-AUG-00:10 |
September | 0.288453E+10 | 0.735589E+09 | 158.12 | 0.231967E+10 | 0.564869E+09 | 0.00 | 1.00 | 06-SEP-13:50 | 0.00 | 01-SEP-00:10 | 21107.11 | 11-SEP-07:03 | 11956.69 | 11-SEP-07:03 | 9150.42 | 11-SEP-07:03 | 4460.09 | 11-SEP-07:03 | 0.00 | 01-SEP-00:10 |
October | 14031510.59 | 3909914.81 | 4.17 | 13417949.20 | 613561.39 | 0.00 | 0.25 | 20-OCT-15:00 | 0.00 | 01-OCT-00:10 | 2072.86 | 20-OCT-15:00 | 2005.70 | 20-OCT-15:00 | 67.54 | 20-OCT-15:20 | 572.51 | 20-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 |
Annual Sum or Average | 0.219882E+11 | 0.543568E+10 | 1124.58 | 0.146372E+11 | 0.735094E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.663254E+10 | 0.160927E+10 | 322.17 | 0.411951E+10 | 0.251302E+10 | 0.00 | 1.00 | 0.00 | 24234.50 | 13738.07 | 12149.33 | 5108.96 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_9:9 COOLING COIL
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 |
April | 0.458520E+09 | 0.118332E+09 | 24.83 | 0.306895E+09 | 0.151624E+09 | 0.00 | 0.79 | 18-APR-14:40 | 0.00 | 01-APR-00:05 | 8394.13 | 18-APR-14:40 | 5639.22 | 18-APR-14:50 | 2886.71 | 18-APR-12:40 | 2082.56 | 18-APR-14:40 | 0.00 | 01-APR-00:05 |
May | 0.750836E+09 | 0.197712E+09 | 62.17 | 0.531461E+09 | 0.219375E+09 | 0.00 | 0.82 | 31-MAY-15:00 | 0.00 | 01-MAY-00:10 | 8549.40 | 31-MAY-13:00 | 6631.52 | 31-MAY-15:00 | 2432.33 | 30-MAY-13:00 | 2194.84 | 31-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 0.452958E+10 | 0.112717E+10 | 224.31 | 0.301730E+10 | 0.151228E+10 | 0.00 | 1.00 | 11-JUN-13:10 | 0.00 | 01-JUN-00:10 | 23768.23 | 26-JUN-07:03 | 13492.46 | 26-JUN-07:03 | 11136.64 | 27-JUN-07:03 | 5063.48 | 27-JUN-07:03 | 0.00 | 01-JUN-00:10 |
July | 0.642083E+10 | 0.156064E+10 | 302.96 | 0.397631E+10 | 0.244452E+10 | 0.00 | 1.00 | 02-JUL-08:62 | 0.00 | 01-JUL-00:05 | 23581.42 | 02-JUL-08:62 | 13178.05 | 02-JUL-08:62 | 12127.79 | 05-JUL-07:03 | 5057.45 | 02-JUL-08:62 | 0.00 | 01-JUL-00:05 |
August | 0.620705E+10 | 0.152271E+10 | 316.79 | 0.396702E+10 | 0.224003E+10 | 0.00 | 1.00 | 02-AUG-14:40 | 0.00 | 01-AUG-00:10 | 24104.17 | 04-AUG-07:02 | 12872.30 | 03-AUG-07:02 | 11628.05 | 04-AUG-07:02 | 5083.42 | 04-AUG-07:02 | 0.00 | 01-AUG-00:10 |
September | 0.279815E+10 | 0.714733E+09 | 151.46 | 0.224483E+10 | 0.553321E+09 | 0.00 | 1.00 | 06-SEP-13:50 | 0.00 | 01-SEP-00:10 | 18423.60 | 11-SEP-07:03 | 10361.43 | 11-SEP-07:03 | 8062.17 | 11-SEP-07:03 | 3894.52 | 11-SEP-07:03 | 0.00 | 01-SEP-00:10 |
October | 11336289.69 | 3172314.66 | 3.50 | 10840864.72 | 495424.97 | 0.00 | 0.23 | 20-OCT-15:00 | 0.00 | 01-OCT-00:10 | 1896.42 | 20-OCT-15:00 | 1830.33 | 20-OCT-15:00 | 66.09 | 20-OCT-15:00 | 526.43 | 20-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 |
Annual Sum or Average | 0.211763E+11 | 0.524446E+10 | 1086.01 | 0.140547E+11 | 0.712164E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.642083E+10 | 0.156064E+10 | 316.79 | 0.397631E+10 | 0.244452E+10 | 0.00 | 1.00 | 0.00 | 24104.17 | 13492.46 | 12127.79 | 5083.42 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_10:10 COOLING COIL
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 |
April | 0.425938E+09 | 0.113555E+09 | 21.17 | 0.283763E+09 | 0.142175E+09 | 0.00 | 0.67 | 18-APR-14:10 | 0.00 | 01-APR-00:05 | 8169.31 | 18-APR-14:10 | 5444.76 | 18-APR-14:30 | 2855.43 | 18-APR-12:30 | 2108.67 | 18-APR-14:10 | 0.00 | 01-APR-00:05 |
May | 0.664450E+09 | 0.179330E+09 | 52.08 | 0.473995E+09 | 0.190456E+09 | 0.00 | 0.73 | 31-MAY-13:00 | 0.00 | 01-MAY-00:10 | 8837.76 | 31-MAY-13:00 | 6782.13 | 31-MAY-13:00 | 2379.68 | 30-MAY-13:00 | 2340.97 | 31-MAY-13:00 | 0.00 | 01-MAY-00:10 |
June | 0.442526E+10 | 0.113209E+10 | 212.03 | 0.295965E+10 | 0.146561E+10 | 0.00 | 1.00 | 11-JUN-14:40 | 0.00 | 01-JUN-00:10 | 19975.56 | 26-JUN-07:03 | 10181.26 | 26-JUN-07:03 | 9794.30 | 26-JUN-07:03 | 4210.32 | 26-JUN-07:03 | 0.00 | 01-JUN-00:10 |
July | 0.634571E+10 | 0.158367E+10 | 287.93 | 0.397034E+10 | 0.237537E+10 | 0.00 | 1.00 | 02-JUL-08:62 | 0.00 | 01-JUL-00:05 | 28350.05 | 04-JUL-08:62 | 14590.54 | 04-JUL-08:62 | 13759.51 | 04-JUL-08:62 | 5977.73 | 04-JUL-08:62 | 0.00 | 01-JUL-00:05 |
August | 0.614558E+10 | 0.154205E+10 | 289.22 | 0.396970E+10 | 0.217588E+10 | 0.00 | 1.00 | 03-AUG-07:02 | 0.00 | 01-AUG-00:10 | 29651.01 | 04-AUG-07:02 | 13397.47 | 03-AUG-07:02 | 16519.23 | 04-AUG-07:02 | 6142.66 | 04-AUG-07:02 | 0.00 | 01-AUG-00:10 |
September | 0.284789E+10 | 0.744576E+09 | 140.63 | 0.229418E+10 | 0.553716E+09 | 0.00 | 0.94 | 06-SEP-14:20 | 0.00 | 01-SEP-00:10 | 12114.87 | 06-SEP-14:20 | 9756.76 | 07-SEP-14:10 | 3925.66 | 11-SEP-07:03 | 3115.52 | 06-SEP-14:20 | 0.00 | 01-SEP-00:10 |
October | 8240781.00 | 2332539.78 | 2.67 | 7956346.95 | 284434.05 | 0.00 | 0.18 | 20-OCT-15:00 | 0.00 | 01-OCT-00:10 | 1723.19 | 20-OCT-15:00 | 1675.21 | 20-OCT-15:00 | 47.98 | 20-OCT-15:00 | 485.25 | 20-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 |
Annual Sum or Average | 0.208631E+11 | 0.529760E+10 | 1005.72 | 0.139596E+11 | 0.690349E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.634571E+10 | 0.158367E+10 | 289.22 | 0.397034E+10 | 0.237537E+10 | 0.00 | 1.00 | 0.00 | 29651.01 | 14590.54 | 16519.23 | 6142.66 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 112.21 | 76.78 | 35.42 | 103.56 | 120.26 | 0.00 | 0.00 | 0.00 |
February | 120.23 | 81.23 | 39.00 | 116.24 | 95.78 | 0.00 | 0.00 | 0.00 |
March | 104.62 | 55.09 | 49.53 | 107.80 | 67.11 | 0.00 | 0.00 | 0.00 |
April | 94.26 | 44.07 | 50.19 | 108.12 | 48.90 | 0.00 | 0.00 | 0.00 |
May | 78.09 | 21.17 | 56.92 | 95.59 | 30.23 | 0.00 | 0.00 | 0.00 |
June | 75.81 | 15.44 | 60.38 | 101.24 | 20.84 | 0.00 | 0.00 | 0.00 |
July | 80.25 | 20.22 | 60.03 | 110.98 | 18.50 | 0.00 | 0.00 | 0.00 |
August | 90.42 | 32.43 | 57.99 | 126.15 | 22.49 | 0.00 | 0.00 | 0.00 |
September | 109.57 | 57.73 | 51.84 | 143.34 | 36.90 | 0.00 | 0.00 | 0.00 |
October | 114.41 | 71.78 | 42.64 | 132.97 | 53.06 | 0.00 | 0.00 | 0.00 |
November | 86.32 | 54.04 | 32.28 | 85.13 | 78.17 | 0.00 | 0.00 | 0.00 |
December | 92.05 | 69.73 | 22.32 | 91.03 | 111.54 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 96.38 | 49.80 | 46.58 | 110.14 | 58.48 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 75.81 | 15.44 | 22.32 | 85.13 | 18.50 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 120.23 | 81.23 | 60.38 | 143.34 | 120.26 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 112.21 | 76.78 | 35.42 | 103.56 | 120.26 | 0.00 | 0.00 | 0.00 |
February | 120.23 | 81.23 | 39.00 | 116.24 | 95.78 | 0.00 | 0.00 | 0.00 |
March | 104.62 | 55.09 | 49.53 | 107.80 | 67.11 | 0.00 | 0.00 | 0.00 |
April | 94.26 | 44.07 | 50.19 | 108.12 | 48.90 | 0.00 | 0.00 | 0.00 |
May | 78.09 | 21.17 | 56.92 | 95.59 | 30.23 | 0.00 | 0.00 | 0.00 |
June | 75.81 | 15.44 | 60.38 | 101.24 | 20.84 | 0.00 | 0.00 | 0.00 |
July | 80.25 | 20.22 | 60.03 | 110.98 | 18.50 | 0.00 | 0.00 | 0.00 |
August | 90.42 | 32.43 | 57.99 | 126.15 | 22.49 | 0.00 | 0.00 | 0.00 |
September | 109.57 | 57.73 | 51.84 | 143.34 | 36.90 | 0.00 | 0.00 | 0.00 |
October | 114.41 | 71.78 | 42.64 | 132.97 | 53.06 | 0.00 | 0.00 | 0.00 |
November | 86.32 | 54.04 | 32.28 | 85.13 | 78.17 | 0.00 | 0.00 | 0.00 |
December | 92.05 | 69.73 | 22.32 | 91.03 | 111.54 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 96.38 | 49.80 | 46.58 | 110.14 | 58.48 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 75.81 | 15.44 | 22.32 | 85.13 | 18.50 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 120.23 | 81.23 | 60.38 | 143.34 | 120.26 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 112.21 | 76.78 | 35.42 | 103.56 | 120.26 | 0.00 | 0.00 | 0.00 |
February | 120.23 | 81.23 | 39.00 | 116.24 | 95.78 | 0.00 | 0.00 | 0.00 |
March | 104.62 | 55.09 | 49.53 | 107.80 | 67.11 | 0.00 | 0.00 | 0.00 |
April | 94.26 | 44.07 | 50.19 | 108.12 | 48.90 | 0.00 | 0.00 | 0.00 |
May | 78.09 | 21.17 | 56.92 | 95.59 | 30.23 | 0.00 | 0.00 | 0.00 |
June | 75.81 | 15.44 | 60.38 | 101.24 | 20.84 | 0.00 | 0.00 | 0.00 |
July | 80.25 | 20.22 | 60.03 | 110.98 | 18.50 | 0.00 | 0.00 | 0.00 |
August | 90.42 | 32.43 | 57.99 | 126.15 | 22.49 | 0.00 | 0.00 | 0.00 |
September | 109.57 | 57.73 | 51.84 | 143.34 | 36.90 | 0.00 | 0.00 | 0.00 |
October | 114.41 | 71.78 | 42.64 | 132.97 | 53.06 | 0.00 | 0.00 | 0.00 |
November | 86.32 | 54.04 | 32.28 | 85.13 | 78.17 | 0.00 | 0.00 | 0.00 |
December | 92.05 | 69.73 | 22.32 | 91.03 | 111.54 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 96.38 | 49.80 | 46.58 | 110.14 | 58.48 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 75.81 | 15.44 | 22.32 | 85.13 | 18.50 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 120.23 | 81.23 | 60.38 | 143.34 | 120.26 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 112.21 | 76.78 | 35.42 | 103.56 | 120.26 | 0.00 | 0.00 | 0.00 |
February | 120.23 | 81.23 | 39.00 | 116.24 | 95.78 | 0.00 | 0.00 | 0.00 |
March | 104.62 | 55.09 | 49.53 | 107.80 | 67.11 | 0.00 | 0.00 | 0.00 |
April | 94.26 | 44.07 | 50.19 | 108.12 | 48.90 | 0.00 | 0.00 | 0.00 |
May | 78.09 | 21.17 | 56.92 | 95.59 | 30.23 | 0.00 | 0.00 | 0.00 |
June | 75.81 | 15.44 | 60.38 | 101.24 | 20.84 | 0.00 | 0.00 | 0.00 |
July | 80.25 | 20.22 | 60.03 | 110.98 | 18.50 | 0.00 | 0.00 | 0.00 |
August | 90.42 | 32.43 | 57.99 | 126.15 | 22.49 | 0.00 | 0.00 | 0.00 |
September | 109.57 | 57.73 | 51.84 | 143.34 | 36.90 | 0.00 | 0.00 | 0.00 |
October | 114.41 | 71.78 | 42.64 | 132.97 | 53.06 | 0.00 | 0.00 | 0.00 |
November | 86.32 | 54.04 | 32.28 | 85.13 | 78.17 | 0.00 | 0.00 | 0.00 |
December | 92.05 | 69.73 | 22.32 | 91.03 | 111.54 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 96.38 | 49.80 | 46.58 | 110.14 | 58.48 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 75.81 | 15.44 | 22.32 | 85.13 | 18.50 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 120.23 | 81.23 | 60.38 | 143.34 | 120.26 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 134.89 | 92.31 | 42.58 | 125.15 | 142.62 | 0.00 | 0.00 | 0.00 |
February | 144.53 | 97.65 | 46.88 | 140.41 | 113.62 | 0.00 | 0.00 | 0.00 |
March | 125.77 | 66.23 | 59.55 | 130.17 | 79.62 | 0.00 | 0.00 | 0.00 |
April | 113.31 | 52.98 | 60.34 | 130.27 | 58.09 | 0.00 | 0.00 | 0.00 |
May | 93.88 | 25.45 | 68.43 | 115.13 | 36.03 | 0.00 | 0.00 | 0.00 |
June | 91.14 | 18.56 | 72.58 | 121.70 | 24.91 | 0.00 | 0.00 | 0.00 |
July | 96.48 | 24.31 | 72.17 | 133.36 | 22.16 | 0.00 | 0.00 | 0.00 |
August | 108.70 | 38.98 | 69.72 | 151.67 | 26.88 | 0.00 | 0.00 | 0.00 |
September | 131.72 | 69.41 | 62.31 | 172.41 | 44.06 | 0.00 | 0.00 | 0.00 |
October | 137.54 | 86.29 | 51.25 | 160.21 | 63.16 | 0.00 | 0.00 | 0.00 |
November | 103.78 | 64.97 | 38.81 | 102.78 | 92.72 | 0.00 | 0.00 | 0.00 |
December | 110.66 | 83.83 | 26.84 | 109.83 | 132.31 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 115.87 | 59.86 | 56.00 | 132.71 | 69.48 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 91.14 | 18.56 | 26.84 | 102.78 | 22.16 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 144.53 | 97.65 | 72.58 | 172.41 | 142.62 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 134.89 | 92.31 | 42.58 | 125.15 | 142.62 | 0.00 | 0.00 | 0.00 |
February | 144.53 | 97.65 | 46.88 | 140.41 | 113.62 | 0.00 | 0.00 | 0.00 |
March | 125.77 | 66.23 | 59.55 | 130.17 | 79.62 | 0.00 | 0.00 | 0.00 |
April | 113.31 | 52.98 | 60.34 | 130.27 | 58.09 | 0.00 | 0.00 | 0.00 |
May | 93.88 | 25.45 | 68.43 | 115.13 | 36.03 | 0.00 | 0.00 | 0.00 |
June | 91.14 | 18.56 | 72.58 | 121.70 | 24.91 | 0.00 | 0.00 | 0.00 |
July | 96.48 | 24.31 | 72.17 | 133.36 | 22.16 | 0.00 | 0.00 | 0.00 |
August | 108.70 | 38.98 | 69.72 | 151.67 | 26.88 | 0.00 | 0.00 | 0.00 |
September | 131.72 | 69.41 | 62.31 | 172.41 | 44.06 | 0.00 | 0.00 | 0.00 |
October | 137.54 | 86.29 | 51.25 | 160.21 | 63.16 | 0.00 | 0.00 | 0.00 |
November | 103.78 | 64.97 | 38.81 | 102.78 | 92.72 | 0.00 | 0.00 | 0.00 |
December | 110.66 | 83.83 | 26.84 | 109.83 | 132.31 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 115.87 | 59.86 | 56.00 | 132.71 | 69.48 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 91.14 | 18.56 | 26.84 | 102.78 | 22.16 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 144.53 | 97.65 | 72.58 | 172.41 | 142.62 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 112.21 | 76.78 | 35.42 | 102.50 | 124.03 | 0.00 | 0.00 | 0.00 |
February | 120.23 | 81.23 | 39.00 | 114.99 | 99.51 | 0.00 | 0.00 | 0.00 |
March | 104.62 | 55.09 | 49.53 | 106.38 | 70.99 | 0.00 | 0.00 | 0.00 |
April | 94.26 | 44.07 | 50.19 | 106.85 | 52.60 | 0.00 | 0.00 | 0.00 |
May | 78.09 | 21.17 | 56.92 | 93.79 | 32.76 | 0.00 | 0.00 | 0.00 |
June | 75.81 | 15.44 | 60.38 | 100.44 | 22.00 | 0.00 | 0.00 | 0.00 |
July | 80.25 | 20.22 | 60.03 | 110.69 | 18.85 | 0.00 | 0.00 | 0.00 |
August | 90.42 | 32.43 | 57.99 | 125.88 | 22.93 | 0.00 | 0.00 | 0.00 |
September | 109.57 | 57.73 | 51.84 | 142.62 | 38.41 | 0.00 | 0.00 | 0.00 |
October | 114.41 | 71.78 | 42.64 | 131.70 | 56.46 | 0.00 | 0.00 | 0.00 |
November | 86.32 | 54.04 | 32.28 | 84.04 | 81.98 | 0.00 | 0.00 | 0.00 |
December | 92.05 | 69.73 | 22.32 | 90.24 | 115.51 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 96.38 | 49.80 | 46.58 | 109.14 | 61.16 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 75.81 | 15.44 | 22.32 | 84.04 | 18.85 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 120.23 | 81.23 | 60.38 | 142.62 | 124.03 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 112.21 | 76.78 | 35.42 | 102.50 | 124.03 | 0.00 | 0.00 | 0.00 |
February | 120.23 | 81.23 | 39.00 | 114.99 | 99.51 | 0.00 | 0.00 | 0.00 |
March | 104.62 | 55.09 | 49.53 | 106.38 | 70.99 | 0.00 | 0.00 | 0.00 |
April | 94.26 | 44.07 | 50.19 | 106.85 | 52.60 | 0.00 | 0.00 | 0.00 |
May | 78.09 | 21.17 | 56.92 | 93.79 | 32.76 | 0.00 | 0.00 | 0.00 |
June | 75.81 | 15.44 | 60.38 | 100.44 | 22.00 | 0.00 | 0.00 | 0.00 |
July | 80.25 | 20.22 | 60.03 | 110.69 | 18.85 | 0.00 | 0.00 | 0.00 |
August | 90.42 | 32.43 | 57.99 | 125.88 | 22.93 | 0.00 | 0.00 | 0.00 |
September | 109.57 | 57.73 | 51.84 | 142.62 | 38.41 | 0.00 | 0.00 | 0.00 |
October | 114.41 | 71.78 | 42.64 | 131.70 | 56.46 | 0.00 | 0.00 | 0.00 |
November | 86.32 | 54.04 | 32.28 | 84.04 | 81.98 | 0.00 | 0.00 | 0.00 |
December | 92.05 | 69.73 | 22.32 | 90.24 | 115.51 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 96.38 | 49.80 | 46.58 | 109.14 | 61.16 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 75.81 | 15.44 | 22.32 | 84.04 | 18.85 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 120.23 | 81.23 | 60.38 | 142.62 | 124.03 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 134.89 | 92.31 | 42.58 | 123.91 | 147.05 | 0.00 | 0.00 | 0.00 |
February | 144.53 | 97.65 | 46.88 | 138.94 | 118.00 | 0.00 | 0.00 | 0.00 |
March | 125.77 | 66.23 | 59.55 | 128.49 | 84.18 | 0.00 | 0.00 | 0.00 |
April | 113.31 | 52.98 | 60.34 | 128.78 | 62.45 | 0.00 | 0.00 | 0.00 |
May | 93.88 | 25.45 | 68.43 | 113.00 | 39.00 | 0.00 | 0.00 | 0.00 |
June | 91.14 | 18.56 | 72.58 | 120.76 | 26.28 | 0.00 | 0.00 | 0.00 |
July | 96.48 | 24.31 | 72.17 | 133.03 | 22.58 | 0.00 | 0.00 | 0.00 |
August | 108.70 | 38.98 | 69.72 | 151.37 | 27.40 | 0.00 | 0.00 | 0.00 |
September | 131.72 | 69.41 | 62.31 | 171.57 | 45.84 | 0.00 | 0.00 | 0.00 |
October | 137.54 | 86.29 | 51.25 | 158.73 | 67.14 | 0.00 | 0.00 | 0.00 |
November | 103.78 | 64.97 | 38.81 | 101.50 | 97.19 | 0.00 | 0.00 | 0.00 |
December | 110.66 | 83.83 | 26.84 | 108.90 | 136.98 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 115.87 | 59.86 | 56.00 | 131.53 | 72.63 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 91.14 | 18.56 | 26.84 | 101.50 | 22.58 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 144.53 | 97.65 | 72.58 | 171.57 | 147.05 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 112.21 | 76.78 | 35.42 | 102.64 | 121.68 | 0.00 | 0.00 | 0.00 |
February | 120.23 | 81.23 | 39.00 | 115.14 | 97.41 | 0.00 | 0.00 | 0.00 |
March | 104.62 | 55.09 | 49.53 | 106.55 | 69.43 | 0.00 | 0.00 | 0.00 |
April | 94.26 | 44.07 | 50.19 | 106.98 | 51.42 | 0.00 | 0.00 | 0.00 |
May | 78.09 | 21.17 | 56.92 | 93.94 | 32.62 | 0.00 | 0.00 | 0.00 |
June | 75.81 | 15.44 | 60.38 | 100.22 | 22.74 | 0.00 | 0.00 | 0.00 |
July | 80.25 | 20.22 | 60.03 | 110.32 | 20.13 | 0.00 | 0.00 | 0.00 |
August | 90.42 | 32.43 | 57.99 | 125.73 | 24.12 | 0.00 | 0.00 | 0.00 |
September | 109.57 | 57.73 | 51.84 | 142.62 | 38.99 | 0.00 | 0.00 | 0.00 |
October | 114.41 | 71.78 | 42.64 | 132.15 | 54.86 | 0.00 | 0.00 | 0.00 |
November | 86.32 | 54.04 | 32.28 | 84.31 | 80.03 | 0.00 | 0.00 | 0.00 |
December | 92.05 | 69.73 | 22.32 | 90.36 | 113.45 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 96.38 | 49.80 | 46.58 | 109.20 | 60.40 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 75.81 | 15.44 | 22.32 | 84.31 | 20.13 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 120.23 | 81.23 | 60.38 | 142.62 | 121.68 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 112.21 | 76.78 | 35.42 | 102.64 | 121.68 | 0.00 | 0.00 | 0.00 |
February | 120.23 | 81.23 | 39.00 | 115.14 | 97.41 | 0.00 | 0.00 | 0.00 |
March | 104.62 | 55.09 | 49.53 | 106.55 | 69.43 | 0.00 | 0.00 | 0.00 |
April | 94.26 | 44.07 | 50.19 | 106.98 | 51.42 | 0.00 | 0.00 | 0.00 |
May | 78.09 | 21.17 | 56.92 | 93.94 | 32.62 | 0.00 | 0.00 | 0.00 |
June | 75.81 | 15.44 | 60.38 | 100.22 | 22.74 | 0.00 | 0.00 | 0.00 |
July | 80.25 | 20.22 | 60.03 | 110.32 | 20.13 | 0.00 | 0.00 | 0.00 |
August | 90.42 | 32.43 | 57.99 | 125.73 | 24.12 | 0.00 | 0.00 | 0.00 |
September | 109.57 | 57.73 | 51.84 | 142.62 | 38.99 | 0.00 | 0.00 | 0.00 |
October | 114.41 | 71.78 | 42.64 | 132.15 | 54.86 | 0.00 | 0.00 | 0.00 |
November | 86.32 | 54.04 | 32.28 | 84.31 | 80.03 | 0.00 | 0.00 | 0.00 |
December | 92.05 | 69.73 | 22.32 | 90.36 | 113.45 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 96.38 | 49.80 | 46.58 | 109.20 | 60.40 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 75.81 | 15.44 | 22.32 | 84.31 | 20.13 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 120.23 | 81.23 | 60.38 | 142.62 | 121.68 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 134.15 | 91.80 | 42.35 | 123.40 | 143.48 | 0.00 | 0.00 | 0.00 |
February | 143.74 | 97.11 | 46.63 | 138.36 | 114.90 | 0.00 | 0.00 | 0.00 |
March | 125.09 | 65.87 | 59.22 | 128.00 | 81.90 | 0.00 | 0.00 | 0.00 |
April | 112.69 | 52.69 | 60.01 | 128.23 | 60.72 | 0.00 | 0.00 | 0.00 |
May | 93.36 | 25.31 | 68.05 | 112.56 | 38.63 | 0.00 | 0.00 | 0.00 |
June | 90.64 | 18.46 | 72.19 | 119.85 | 27.00 | 0.00 | 0.00 | 0.00 |
July | 95.95 | 24.18 | 71.77 | 131.86 | 23.96 | 0.00 | 0.00 | 0.00 |
August | 108.10 | 38.77 | 69.34 | 150.36 | 28.63 | 0.00 | 0.00 | 0.00 |
September | 131.00 | 69.03 | 61.97 | 170.64 | 46.25 | 0.00 | 0.00 | 0.00 |
October | 136.79 | 85.82 | 50.97 | 158.40 | 64.91 | 0.00 | 0.00 | 0.00 |
November | 103.21 | 64.61 | 38.60 | 101.27 | 94.38 | 0.00 | 0.00 | 0.00 |
December | 110.06 | 83.37 | 26.69 | 108.45 | 133.82 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 115.23 | 59.54 | 55.70 | 130.90 | 71.35 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 90.64 | 18.46 | 26.69 | 101.27 | 23.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 143.74 | 97.11 | 72.19 | 170.64 | 143.48 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 112.21 | 76.78 | 35.42 | 102.74 | 120.79 | 0.00 | 0.00 | 0.00 |
February | 120.23 | 81.23 | 39.00 | 115.26 | 96.60 | 0.00 | 0.00 | 0.00 |
March | 104.62 | 55.09 | 49.53 | 106.71 | 68.70 | 0.00 | 0.00 | 0.00 |
April | 94.26 | 44.07 | 50.19 | 107.14 | 50.75 | 0.00 | 0.00 | 0.00 |
May | 78.09 | 21.17 | 56.92 | 94.23 | 32.08 | 0.00 | 0.00 | 0.00 |
June | 75.81 | 15.44 | 60.38 | 100.32 | 22.58 | 0.00 | 0.00 | 0.00 |
July | 80.25 | 20.22 | 60.03 | 110.32 | 20.14 | 0.00 | 0.00 | 0.00 |
August | 90.42 | 32.43 | 57.99 | 125.74 | 24.09 | 0.00 | 0.00 | 0.00 |
September | 109.57 | 57.73 | 51.84 | 142.71 | 38.74 | 0.00 | 0.00 | 0.00 |
October | 114.41 | 71.78 | 42.64 | 132.41 | 54.06 | 0.00 | 0.00 | 0.00 |
November | 86.32 | 54.04 | 32.28 | 84.49 | 79.14 | 0.00 | 0.00 | 0.00 |
December | 92.05 | 69.73 | 22.32 | 90.44 | 112.62 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 96.38 | 49.80 | 46.58 | 109.34 | 59.86 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 75.81 | 15.44 | 22.32 | 84.49 | 20.14 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 120.23 | 81.23 | 60.38 | 142.71 | 120.79 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 112.21 | 76.78 | 35.42 | 102.74 | 120.79 | 0.00 | 0.00 | 0.00 |
February | 120.23 | 81.23 | 39.00 | 115.26 | 96.60 | 0.00 | 0.00 | 0.00 |
March | 104.62 | 55.09 | 49.53 | 106.71 | 68.70 | 0.00 | 0.00 | 0.00 |
April | 94.26 | 44.07 | 50.19 | 107.14 | 50.75 | 0.00 | 0.00 | 0.00 |
May | 78.09 | 21.17 | 56.92 | 94.23 | 32.08 | 0.00 | 0.00 | 0.00 |
June | 75.81 | 15.44 | 60.38 | 100.32 | 22.58 | 0.00 | 0.00 | 0.00 |
July | 80.25 | 20.22 | 60.03 | 110.32 | 20.14 | 0.00 | 0.00 | 0.00 |
August | 90.42 | 32.43 | 57.99 | 125.74 | 24.09 | 0.00 | 0.00 | 0.00 |
September | 109.57 | 57.73 | 51.84 | 142.71 | 38.74 | 0.00 | 0.00 | 0.00 |
October | 114.41 | 71.78 | 42.64 | 132.41 | 54.06 | 0.00 | 0.00 | 0.00 |
November | 86.32 | 54.04 | 32.28 | 84.49 | 79.14 | 0.00 | 0.00 | 0.00 |
December | 92.05 | 69.73 | 22.32 | 90.44 | 112.62 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 96.38 | 49.80 | 46.58 | 109.34 | 59.86 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 75.81 | 15.44 | 22.32 | 84.49 | 20.14 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 120.23 | 81.23 | 60.38 | 142.71 | 120.79 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 134.15 | 91.80 | 42.35 | 123.52 | 142.43 | 0.00 | 0.00 | 0.00 |
February | 143.74 | 97.11 | 46.63 | 138.51 | 113.93 | 0.00 | 0.00 | 0.00 |
March | 125.09 | 65.87 | 59.22 | 128.19 | 81.04 | 0.00 | 0.00 | 0.00 |
April | 112.69 | 52.69 | 60.01 | 128.43 | 59.94 | 0.00 | 0.00 | 0.00 |
May | 93.36 | 25.31 | 68.05 | 112.91 | 38.00 | 0.00 | 0.00 | 0.00 |
June | 90.64 | 18.46 | 72.19 | 119.96 | 26.81 | 0.00 | 0.00 | 0.00 |
July | 95.95 | 24.18 | 71.77 | 131.87 | 23.96 | 0.00 | 0.00 | 0.00 |
August | 108.10 | 38.77 | 69.34 | 150.38 | 28.60 | 0.00 | 0.00 | 0.00 |
September | 131.00 | 69.03 | 61.97 | 170.75 | 45.96 | 0.00 | 0.00 | 0.00 |
October | 136.79 | 85.82 | 50.97 | 158.70 | 63.97 | 0.00 | 0.00 | 0.00 |
November | 103.21 | 64.61 | 38.60 | 101.48 | 93.33 | 0.00 | 0.00 | 0.00 |
December | 110.06 | 83.37 | 26.69 | 108.56 | 132.84 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 115.23 | 59.54 | 55.70 | 131.05 | 70.70 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 90.64 | 18.46 | 26.69 | 101.48 | 23.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 143.74 | 97.11 | 72.19 | 170.75 | 142.43 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 112.21 | 76.78 | 35.42 | 102.87 | 120.11 | 0.00 | 0.00 | 0.00 |
February | 120.23 | 81.23 | 39.00 | 115.43 | 95.95 | 0.00 | 0.00 | 0.00 |
March | 104.62 | 55.09 | 49.53 | 106.92 | 68.04 | 0.00 | 0.00 | 0.00 |
April | 94.26 | 44.07 | 50.19 | 107.38 | 50.10 | 0.00 | 0.00 | 0.00 |
May | 78.09 | 21.17 | 56.92 | 94.76 | 31.34 | 0.00 | 0.00 | 0.00 |
June | 75.81 | 15.44 | 60.38 | 100.55 | 22.19 | 0.00 | 0.00 | 0.00 |
July | 80.25 | 20.22 | 60.03 | 110.44 | 19.89 | 0.00 | 0.00 | 0.00 |
August | 90.42 | 32.43 | 57.99 | 125.85 | 23.83 | 0.00 | 0.00 | 0.00 |
September | 109.57 | 57.73 | 51.84 | 142.91 | 38.30 | 0.00 | 0.00 | 0.00 |
October | 114.41 | 71.78 | 42.64 | 132.68 | 53.41 | 0.00 | 0.00 | 0.00 |
November | 86.32 | 54.04 | 32.28 | 84.70 | 78.39 | 0.00 | 0.00 | 0.00 |
December | 92.05 | 69.73 | 22.32 | 90.56 | 111.93 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 96.38 | 49.80 | 46.58 | 109.55 | 59.29 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 75.81 | 15.44 | 22.32 | 84.70 | 19.89 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 120.23 | 81.23 | 60.38 | 142.91 | 120.11 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 112.21 | 76.78 | 35.42 | 102.87 | 120.11 | 0.00 | 0.00 | 0.00 |
February | 120.23 | 81.23 | 39.00 | 115.43 | 95.95 | 0.00 | 0.00 | 0.00 |
March | 104.62 | 55.09 | 49.53 | 106.92 | 68.04 | 0.00 | 0.00 | 0.00 |
April | 94.26 | 44.07 | 50.19 | 107.38 | 50.10 | 0.00 | 0.00 | 0.00 |
May | 78.09 | 21.17 | 56.92 | 94.76 | 31.34 | 0.00 | 0.00 | 0.00 |
June | 75.81 | 15.44 | 60.38 | 100.55 | 22.19 | 0.00 | 0.00 | 0.00 |
July | 80.25 | 20.22 | 60.03 | 110.44 | 19.89 | 0.00 | 0.00 | 0.00 |
August | 90.42 | 32.43 | 57.99 | 125.85 | 23.83 | 0.00 | 0.00 | 0.00 |
September | 109.57 | 57.73 | 51.84 | 142.91 | 38.30 | 0.00 | 0.00 | 0.00 |
October | 114.41 | 71.78 | 42.64 | 132.68 | 53.41 | 0.00 | 0.00 | 0.00 |
November | 86.32 | 54.04 | 32.28 | 84.70 | 78.39 | 0.00 | 0.00 | 0.00 |
December | 92.05 | 69.73 | 22.32 | 90.56 | 111.93 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 96.38 | 49.80 | 46.58 | 109.55 | 59.29 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 75.81 | 15.44 | 22.32 | 84.70 | 19.89 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 120.23 | 81.23 | 60.38 | 142.91 | 120.11 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 134.15 | 91.80 | 42.35 | 123.68 | 141.62 | 0.00 | 0.00 | 0.00 |
February | 143.74 | 97.11 | 46.63 | 138.71 | 113.16 | 0.00 | 0.00 | 0.00 |
March | 125.09 | 65.87 | 59.22 | 128.45 | 80.25 | 0.00 | 0.00 | 0.00 |
April | 112.69 | 52.69 | 60.01 | 128.71 | 59.16 | 0.00 | 0.00 | 0.00 |
May | 93.36 | 25.31 | 68.05 | 113.54 | 37.12 | 0.00 | 0.00 | 0.00 |
June | 90.64 | 18.46 | 72.19 | 120.24 | 26.36 | 0.00 | 0.00 | 0.00 |
July | 95.95 | 24.18 | 71.77 | 132.02 | 23.67 | 0.00 | 0.00 | 0.00 |
August | 108.10 | 38.77 | 69.34 | 150.51 | 28.29 | 0.00 | 0.00 | 0.00 |
September | 131.00 | 69.03 | 61.97 | 170.98 | 45.45 | 0.00 | 0.00 | 0.00 |
October | 136.79 | 85.82 | 50.97 | 159.03 | 63.20 | 0.00 | 0.00 | 0.00 |
November | 103.21 | 64.61 | 38.60 | 101.73 | 92.44 | 0.00 | 0.00 | 0.00 |
December | 110.06 | 83.37 | 26.69 | 108.70 | 132.01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 115.23 | 59.54 | 55.70 | 131.31 | 70.03 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 90.64 | 18.46 | 26.69 | 101.73 | 23.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 143.74 | 97.11 | 72.19 | 170.98 | 141.62 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 112.21 | 76.78 | 35.42 | 103.61 | 117.41 | 0.00 | 0.00 | 0.00 |
February | 120.23 | 81.23 | 39.00 | 116.29 | 93.66 | 0.00 | 0.00 | 0.00 |
March | 104.62 | 55.09 | 49.53 | 107.75 | 65.92 | 0.00 | 0.00 | 0.00 |
April | 94.26 | 44.07 | 50.19 | 108.03 | 48.32 | 0.00 | 0.00 | 0.00 |
May | 78.09 | 21.17 | 56.92 | 95.72 | 29.75 | 0.00 | 0.00 | 0.00 |
June | 75.81 | 15.44 | 60.38 | 100.82 | 21.24 | 0.00 | 0.00 | 0.00 |
July | 80.25 | 20.22 | 60.03 | 110.48 | 19.17 | 0.00 | 0.00 | 0.00 |
August | 90.42 | 32.43 | 57.99 | 125.89 | 23.05 | 0.00 | 0.00 | 0.00 |
September | 109.57 | 57.73 | 51.84 | 143.18 | 37.27 | 0.00 | 0.00 | 0.00 |
October | 114.41 | 71.78 | 42.64 | 133.33 | 51.97 | 0.00 | 0.00 | 0.00 |
November | 86.32 | 54.04 | 32.28 | 85.35 | 76.27 | 0.00 | 0.00 | 0.00 |
December | 92.05 | 69.73 | 22.32 | 91.13 | 109.36 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 96.38 | 49.80 | 46.58 | 110.09 | 57.62 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 75.81 | 15.44 | 22.32 | 85.35 | 19.17 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 120.23 | 81.23 | 60.38 | 143.18 | 117.41 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 112.21 | 76.78 | 35.42 | 103.61 | 117.41 | 0.00 | 0.00 | 0.00 |
February | 120.23 | 81.23 | 39.00 | 116.29 | 93.66 | 0.00 | 0.00 | 0.00 |
March | 104.62 | 55.09 | 49.53 | 107.75 | 65.92 | 0.00 | 0.00 | 0.00 |
April | 94.26 | 44.07 | 50.19 | 108.03 | 48.32 | 0.00 | 0.00 | 0.00 |
May | 78.09 | 21.17 | 56.92 | 95.72 | 29.75 | 0.00 | 0.00 | 0.00 |
June | 75.81 | 15.44 | 60.38 | 100.82 | 21.24 | 0.00 | 0.00 | 0.00 |
July | 80.25 | 20.22 | 60.03 | 110.48 | 19.17 | 0.00 | 0.00 | 0.00 |
August | 90.42 | 32.43 | 57.99 | 125.89 | 23.05 | 0.00 | 0.00 | 0.00 |
September | 109.57 | 57.73 | 51.84 | 143.18 | 37.27 | 0.00 | 0.00 | 0.00 |
October | 114.41 | 71.78 | 42.64 | 133.33 | 51.97 | 0.00 | 0.00 | 0.00 |
November | 86.32 | 54.04 | 32.28 | 85.35 | 76.27 | 0.00 | 0.00 | 0.00 |
December | 92.05 | 69.73 | 22.32 | 91.13 | 109.36 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 96.38 | 49.80 | 46.58 | 110.09 | 57.62 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 75.81 | 15.44 | 22.32 | 85.35 | 19.17 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 120.23 | 81.23 | 60.38 | 143.18 | 117.41 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 112.21 | 76.78 | 35.42 | 103.61 | 117.41 | 0.00 | 0.00 | 0.00 |
February | 120.23 | 81.23 | 39.00 | 116.29 | 93.66 | 0.00 | 0.00 | 0.00 |
March | 104.62 | 55.09 | 49.53 | 107.75 | 65.92 | 0.00 | 0.00 | 0.00 |
April | 94.26 | 44.07 | 50.19 | 108.03 | 48.32 | 0.00 | 0.00 | 0.00 |
May | 78.09 | 21.17 | 56.92 | 95.72 | 29.75 | 0.00 | 0.00 | 0.00 |
June | 75.81 | 15.44 | 60.38 | 100.82 | 21.24 | 0.00 | 0.00 | 0.00 |
July | 80.25 | 20.22 | 60.03 | 110.48 | 19.17 | 0.00 | 0.00 | 0.00 |
August | 90.42 | 32.43 | 57.99 | 125.89 | 23.05 | 0.00 | 0.00 | 0.00 |
September | 109.57 | 57.73 | 51.84 | 143.18 | 37.27 | 0.00 | 0.00 | 0.00 |
October | 114.41 | 71.78 | 42.64 | 133.33 | 51.97 | 0.00 | 0.00 | 0.00 |
November | 86.32 | 54.04 | 32.28 | 85.35 | 76.27 | 0.00 | 0.00 | 0.00 |
December | 92.05 | 69.73 | 22.32 | 91.13 | 109.36 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 96.38 | 49.80 | 46.58 | 110.09 | 57.62 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 75.81 | 15.44 | 22.32 | 85.35 | 19.17 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 120.23 | 81.23 | 60.38 | 143.18 | 117.41 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 112.21 | 76.78 | 35.42 | 103.61 | 117.41 | 0.00 | 0.00 | 0.00 |
February | 120.23 | 81.23 | 39.00 | 116.29 | 93.66 | 0.00 | 0.00 | 0.00 |
March | 104.62 | 55.09 | 49.53 | 107.75 | 65.92 | 0.00 | 0.00 | 0.00 |
April | 94.26 | 44.07 | 50.19 | 108.03 | 48.32 | 0.00 | 0.00 | 0.00 |
May | 78.09 | 21.17 | 56.92 | 95.72 | 29.75 | 0.00 | 0.00 | 0.00 |
June | 75.81 | 15.44 | 60.38 | 100.82 | 21.24 | 0.00 | 0.00 | 0.00 |
July | 80.25 | 20.22 | 60.03 | 110.48 | 19.17 | 0.00 | 0.00 | 0.00 |
August | 90.42 | 32.43 | 57.99 | 125.89 | 23.05 | 0.00 | 0.00 | 0.00 |
September | 109.57 | 57.73 | 51.84 | 143.18 | 37.27 | 0.00 | 0.00 | 0.00 |
October | 114.41 | 71.78 | 42.64 | 133.33 | 51.97 | 0.00 | 0.00 | 0.00 |
November | 86.32 | 54.04 | 32.28 | 85.35 | 76.27 | 0.00 | 0.00 | 0.00 |
December | 92.05 | 69.73 | 22.32 | 91.13 | 109.36 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 96.38 | 49.80 | 46.58 | 110.09 | 57.62 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 75.81 | 15.44 | 22.32 | 85.35 | 19.17 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 120.23 | 81.23 | 60.38 | 143.18 | 117.41 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 134.15 | 91.80 | 42.35 | 124.53 | 138.50 | 0.00 | 0.00 | 0.00 |
February | 143.74 | 97.11 | 46.63 | 139.70 | 110.51 | 0.00 | 0.00 | 0.00 |
March | 125.09 | 65.87 | 59.22 | 129.40 | 77.79 | 0.00 | 0.00 | 0.00 |
April | 112.69 | 52.69 | 60.01 | 129.47 | 57.09 | 0.00 | 0.00 | 0.00 |
May | 93.36 | 25.31 | 68.05 | 114.65 | 35.26 | 0.00 | 0.00 | 0.00 |
June | 90.64 | 18.46 | 72.19 | 120.55 | 25.24 | 0.00 | 0.00 | 0.00 |
July | 95.95 | 24.18 | 71.77 | 132.05 | 22.81 | 0.00 | 0.00 | 0.00 |
August | 108.10 | 38.77 | 69.34 | 150.54 | 27.38 | 0.00 | 0.00 | 0.00 |
September | 131.00 | 69.03 | 61.97 | 171.29 | 44.24 | 0.00 | 0.00 | 0.00 |
October | 136.79 | 85.82 | 50.97 | 159.77 | 61.52 | 0.00 | 0.00 | 0.00 |
November | 103.21 | 64.61 | 38.60 | 102.49 | 89.98 | 0.00 | 0.00 | 0.00 |
December | 110.06 | 83.37 | 26.69 | 109.35 | 129.03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 115.23 | 59.54 | 55.70 | 131.93 | 68.09 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 90.64 | 18.46 | 26.69 | 102.49 | 22.81 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 143.74 | 97.11 | 72.19 | 171.29 | 138.50 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 134.15 | 91.80 | 42.35 | 124.53 | 138.50 | 0.00 | 0.00 | 0.00 |
February | 143.74 | 97.11 | 46.63 | 139.70 | 110.51 | 0.00 | 0.00 | 0.00 |
March | 125.09 | 65.87 | 59.22 | 129.40 | 77.79 | 0.00 | 0.00 | 0.00 |
April | 112.69 | 52.69 | 60.01 | 129.47 | 57.09 | 0.00 | 0.00 | 0.00 |
May | 93.36 | 25.31 | 68.05 | 114.65 | 35.26 | 0.00 | 0.00 | 0.00 |
June | 90.64 | 18.46 | 72.19 | 120.55 | 25.24 | 0.00 | 0.00 | 0.00 |
July | 95.95 | 24.18 | 71.77 | 132.05 | 22.81 | 0.00 | 0.00 | 0.00 |
August | 108.10 | 38.77 | 69.34 | 150.54 | 27.38 | 0.00 | 0.00 | 0.00 |
September | 131.00 | 69.03 | 61.97 | 171.29 | 44.24 | 0.00 | 0.00 | 0.00 |
October | 136.79 | 85.82 | 50.97 | 159.77 | 61.52 | 0.00 | 0.00 | 0.00 |
November | 103.21 | 64.61 | 38.60 | 102.49 | 89.98 | 0.00 | 0.00 | 0.00 |
December | 110.06 | 83.37 | 26.69 | 109.35 | 129.03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 115.23 | 59.54 | 55.70 | 131.93 | 68.09 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 90.64 | 18.46 | 26.69 | 102.49 | 22.81 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 143.74 | 97.11 | 72.19 | 171.29 | 138.50 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 112.21 | 76.78 | 35.42 | 103.16 | 118.25 | 0.00 | 0.00 | 0.00 |
February | 120.23 | 81.23 | 39.00 | 115.82 | 94.26 | 0.00 | 0.00 | 0.00 |
March | 104.62 | 55.09 | 49.53 | 107.35 | 66.27 | 0.00 | 0.00 | 0.00 |
April | 94.26 | 44.07 | 50.19 | 107.82 | 48.41 | 0.00 | 0.00 | 0.00 |
May | 78.09 | 21.17 | 56.92 | 95.78 | 29.49 | 0.00 | 0.00 | 0.00 |
June | 75.81 | 15.44 | 60.38 | 100.86 | 21.03 | 0.00 | 0.00 | 0.00 |
July | 80.25 | 20.22 | 60.03 | 110.50 | 18.96 | 0.00 | 0.00 | 0.00 |
August | 90.42 | 32.43 | 57.99 | 125.83 | 22.86 | 0.00 | 0.00 | 0.00 |
September | 109.57 | 57.73 | 51.84 | 143.08 | 37.10 | 0.00 | 0.00 | 0.00 |
October | 114.41 | 71.78 | 42.64 | 133.08 | 51.97 | 0.00 | 0.00 | 0.00 |
November | 86.32 | 54.04 | 32.28 | 85.07 | 76.67 | 0.00 | 0.00 | 0.00 |
December | 92.05 | 69.73 | 22.32 | 90.83 | 110.12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 96.38 | 49.80 | 46.58 | 109.89 | 57.79 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 75.81 | 15.44 | 22.32 | 85.07 | 18.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 120.23 | 81.23 | 60.38 | 143.08 | 118.25 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 112.21 | 76.78 | 35.42 | 103.16 | 118.25 | 0.00 | 0.00 | 0.00 |
February | 120.23 | 81.23 | 39.00 | 115.82 | 94.26 | 0.00 | 0.00 | 0.00 |
March | 104.62 | 55.09 | 49.53 | 107.35 | 66.27 | 0.00 | 0.00 | 0.00 |
April | 94.26 | 44.07 | 50.19 | 107.82 | 48.41 | 0.00 | 0.00 | 0.00 |
May | 78.09 | 21.17 | 56.92 | 95.78 | 29.49 | 0.00 | 0.00 | 0.00 |
June | 75.81 | 15.44 | 60.38 | 100.86 | 21.03 | 0.00 | 0.00 | 0.00 |
July | 80.25 | 20.22 | 60.03 | 110.50 | 18.96 | 0.00 | 0.00 | 0.00 |
August | 90.42 | 32.43 | 57.99 | 125.83 | 22.86 | 0.00 | 0.00 | 0.00 |
September | 109.57 | 57.73 | 51.84 | 143.08 | 37.10 | 0.00 | 0.00 | 0.00 |
October | 114.41 | 71.78 | 42.64 | 133.08 | 51.97 | 0.00 | 0.00 | 0.00 |
November | 86.32 | 54.04 | 32.28 | 85.07 | 76.67 | 0.00 | 0.00 | 0.00 |
December | 92.05 | 69.73 | 22.32 | 90.83 | 110.12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 96.38 | 49.80 | 46.58 | 109.89 | 57.79 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 75.81 | 15.44 | 22.32 | 85.07 | 18.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 120.23 | 81.23 | 60.38 | 143.08 | 118.25 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 134.15 | 91.80 | 42.35 | 124.04 | 139.43 | 0.00 | 0.00 | 0.00 |
February | 143.74 | 97.11 | 46.63 | 139.20 | 111.17 | 0.00 | 0.00 | 0.00 |
March | 125.09 | 65.87 | 59.22 | 128.97 | 78.17 | 0.00 | 0.00 | 0.00 |
April | 112.69 | 52.69 | 60.01 | 129.24 | 57.18 | 0.00 | 0.00 | 0.00 |
May | 93.36 | 25.31 | 68.05 | 114.75 | 34.93 | 0.00 | 0.00 | 0.00 |
June | 90.64 | 18.46 | 72.19 | 120.62 | 24.99 | 0.00 | 0.00 | 0.00 |
July | 95.95 | 24.18 | 71.77 | 132.10 | 22.57 | 0.00 | 0.00 | 0.00 |
August | 108.10 | 38.77 | 69.34 | 150.49 | 27.15 | 0.00 | 0.00 | 0.00 |
September | 131.00 | 69.03 | 61.97 | 171.20 | 44.03 | 0.00 | 0.00 | 0.00 |
October | 136.79 | 85.82 | 50.97 | 159.52 | 61.50 | 0.00 | 0.00 | 0.00 |
November | 103.21 | 64.61 | 38.60 | 102.19 | 90.41 | 0.00 | 0.00 | 0.00 |
December | 110.06 | 83.37 | 26.69 | 109.03 | 129.87 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 115.23 | 59.54 | 55.70 | 131.73 | 68.26 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 90.64 | 18.46 | 26.69 | 102.19 | 22.57 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 143.74 | 97.11 | 72.19 | 171.20 | 139.43 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 112.21 | 76.78 | 35.42 | 103.18 | 118.14 | 0.00 | 0.00 | 0.00 |
February | 120.23 | 81.23 | 39.00 | 115.86 | 94.11 | 0.00 | 0.00 | 0.00 |
March | 104.62 | 55.09 | 49.53 | 107.42 | 66.06 | 0.00 | 0.00 | 0.00 |
April | 94.26 | 44.07 | 50.19 | 107.93 | 48.13 | 0.00 | 0.00 | 0.00 |
May | 78.09 | 21.17 | 56.92 | 96.11 | 29.07 | 0.00 | 0.00 | 0.00 |
June | 75.81 | 15.44 | 60.38 | 101.00 | 20.85 | 0.00 | 0.00 | 0.00 |
July | 80.25 | 20.22 | 60.03 | 110.58 | 18.85 | 0.00 | 0.00 | 0.00 |
August | 90.42 | 32.43 | 57.99 | 125.89 | 22.76 | 0.00 | 0.00 | 0.00 |
September | 109.57 | 57.73 | 51.84 | 143.18 | 36.91 | 0.00 | 0.00 | 0.00 |
October | 114.41 | 71.78 | 42.64 | 133.18 | 51.74 | 0.00 | 0.00 | 0.00 |
November | 86.32 | 54.04 | 32.28 | 85.13 | 76.47 | 0.00 | 0.00 | 0.00 |
December | 92.05 | 69.73 | 22.32 | 90.86 | 109.97 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 96.38 | 49.80 | 46.58 | 109.99 | 57.59 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 75.81 | 15.44 | 22.32 | 85.13 | 18.85 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 120.23 | 81.23 | 60.38 | 143.18 | 118.14 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 112.21 | 76.78 | 35.42 | 103.18 | 118.14 | 0.00 | 0.00 | 0.00 |
February | 120.23 | 81.23 | 39.00 | 115.86 | 94.11 | 0.00 | 0.00 | 0.00 |
March | 104.62 | 55.09 | 49.53 | 107.42 | 66.06 | 0.00 | 0.00 | 0.00 |
April | 94.26 | 44.07 | 50.19 | 107.93 | 48.13 | 0.00 | 0.00 | 0.00 |
May | 78.09 | 21.17 | 56.92 | 96.11 | 29.07 | 0.00 | 0.00 | 0.00 |
June | 75.81 | 15.44 | 60.38 | 101.00 | 20.85 | 0.00 | 0.00 | 0.00 |
July | 80.25 | 20.22 | 60.03 | 110.58 | 18.85 | 0.00 | 0.00 | 0.00 |
August | 90.42 | 32.43 | 57.99 | 125.89 | 22.76 | 0.00 | 0.00 | 0.00 |
September | 109.57 | 57.73 | 51.84 | 143.18 | 36.91 | 0.00 | 0.00 | 0.00 |
October | 114.41 | 71.78 | 42.64 | 133.18 | 51.74 | 0.00 | 0.00 | 0.00 |
November | 86.32 | 54.04 | 32.28 | 85.13 | 76.47 | 0.00 | 0.00 | 0.00 |
December | 92.05 | 69.73 | 22.32 | 90.86 | 109.97 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 96.38 | 49.80 | 46.58 | 109.99 | 57.59 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 75.81 | 15.44 | 22.32 | 85.13 | 18.85 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 120.23 | 81.23 | 60.38 | 143.18 | 118.14 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 134.15 | 91.80 | 42.35 | 124.06 | 139.29 | 0.00 | 0.00 | 0.00 |
February | 143.74 | 97.11 | 46.63 | 139.24 | 110.99 | 0.00 | 0.00 | 0.00 |
March | 125.09 | 65.87 | 59.22 | 129.06 | 77.92 | 0.00 | 0.00 | 0.00 |
April | 112.69 | 52.69 | 60.01 | 129.38 | 56.84 | 0.00 | 0.00 | 0.00 |
May | 93.36 | 25.31 | 68.05 | 115.15 | 34.44 | 0.00 | 0.00 | 0.00 |
June | 90.64 | 18.46 | 72.19 | 120.78 | 24.78 | 0.00 | 0.00 | 0.00 |
July | 95.95 | 24.18 | 71.77 | 132.19 | 22.45 | 0.00 | 0.00 | 0.00 |
August | 108.10 | 38.77 | 69.34 | 150.57 | 27.03 | 0.00 | 0.00 | 0.00 |
September | 131.00 | 69.03 | 61.97 | 171.31 | 43.80 | 0.00 | 0.00 | 0.00 |
October | 136.79 | 85.82 | 50.97 | 159.64 | 61.22 | 0.00 | 0.00 | 0.00 |
November | 103.21 | 64.61 | 38.60 | 102.26 | 90.18 | 0.00 | 0.00 | 0.00 |
December | 110.06 | 83.37 | 26.69 | 109.06 | 129.69 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 115.23 | 59.54 | 55.70 | 131.84 | 68.03 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 90.64 | 18.46 | 26.69 | 102.26 | 22.45 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 143.74 | 97.11 | 72.19 | 171.31 | 139.29 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 112.21 | 76.78 | 35.42 | 103.31 | 117.35 | 0.00 | 0.00 | 0.00 |
February | 120.23 | 81.23 | 39.00 | 116.05 | 93.24 | 0.00 | 0.00 | 0.00 |
March | 104.62 | 55.09 | 49.53 | 107.71 | 65.06 | 0.00 | 0.00 | 0.00 |
April | 94.26 | 44.07 | 50.19 | 108.28 | 47.07 | 0.00 | 0.00 | 0.00 |
May | 78.09 | 21.17 | 56.92 | 96.84 | 28.07 | 0.00 | 0.00 | 0.00 |
June | 75.81 | 15.44 | 60.38 | 101.33 | 20.37 | 0.00 | 0.00 | 0.00 |
July | 80.25 | 20.22 | 60.03 | 110.76 | 18.58 | 0.00 | 0.00 | 0.00 |
August | 90.42 | 32.43 | 57.99 | 126.03 | 22.49 | 0.00 | 0.00 | 0.00 |
September | 109.57 | 57.73 | 51.84 | 143.41 | 36.41 | 0.00 | 0.00 | 0.00 |
October | 114.41 | 71.78 | 42.64 | 133.46 | 50.99 | 0.00 | 0.00 | 0.00 |
November | 86.32 | 54.04 | 32.28 | 85.34 | 75.64 | 0.00 | 0.00 | 0.00 |
December | 92.05 | 69.73 | 22.32 | 90.99 | 109.07 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 96.38 | 49.80 | 46.58 | 110.25 | 56.86 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 75.81 | 15.44 | 22.32 | 85.34 | 18.58 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 120.23 | 81.23 | 60.38 | 143.41 | 117.35 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 112.21 | 76.78 | 35.42 | 103.31 | 117.35 | 0.00 | 0.00 | 0.00 |
February | 120.23 | 81.23 | 39.00 | 116.05 | 93.24 | 0.00 | 0.00 | 0.00 |
March | 104.62 | 55.09 | 49.53 | 107.71 | 65.06 | 0.00 | 0.00 | 0.00 |
April | 94.26 | 44.07 | 50.19 | 108.28 | 47.07 | 0.00 | 0.00 | 0.00 |
May | 78.09 | 21.17 | 56.92 | 96.84 | 28.07 | 0.00 | 0.00 | 0.00 |
June | 75.81 | 15.44 | 60.38 | 101.33 | 20.37 | 0.00 | 0.00 | 0.00 |
July | 80.25 | 20.22 | 60.03 | 110.76 | 18.58 | 0.00 | 0.00 | 0.00 |
August | 90.42 | 32.43 | 57.99 | 126.03 | 22.49 | 0.00 | 0.00 | 0.00 |
September | 109.57 | 57.73 | 51.84 | 143.41 | 36.41 | 0.00 | 0.00 | 0.00 |
October | 114.41 | 71.78 | 42.64 | 133.46 | 50.99 | 0.00 | 0.00 | 0.00 |
November | 86.32 | 54.04 | 32.28 | 85.34 | 75.64 | 0.00 | 0.00 | 0.00 |
December | 92.05 | 69.73 | 22.32 | 90.99 | 109.07 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 96.38 | 49.80 | 46.58 | 110.25 | 56.86 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 75.81 | 15.44 | 22.32 | 85.34 | 18.58 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 120.23 | 81.23 | 60.38 | 143.41 | 117.35 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 134.15 | 91.80 | 42.35 | 124.22 | 138.36 | 0.00 | 0.00 | 0.00 |
February | 143.74 | 97.11 | 46.63 | 139.47 | 109.96 | 0.00 | 0.00 | 0.00 |
March | 125.09 | 65.87 | 59.22 | 129.41 | 76.74 | 0.00 | 0.00 | 0.00 |
April | 112.69 | 52.69 | 60.01 | 129.80 | 55.59 | 0.00 | 0.00 | 0.00 |
May | 93.36 | 25.31 | 68.05 | 116.03 | 33.26 | 0.00 | 0.00 | 0.00 |
June | 90.64 | 18.46 | 72.19 | 121.18 | 24.21 | 0.00 | 0.00 | 0.00 |
July | 95.95 | 24.18 | 71.77 | 132.41 | 22.12 | 0.00 | 0.00 | 0.00 |
August | 108.10 | 38.77 | 69.34 | 150.74 | 26.71 | 0.00 | 0.00 | 0.00 |
September | 131.00 | 69.03 | 61.97 | 171.59 | 43.21 | 0.00 | 0.00 | 0.00 |
October | 136.79 | 85.82 | 50.97 | 159.98 | 60.34 | 0.00 | 0.00 | 0.00 |
November | 103.21 | 64.61 | 38.60 | 102.51 | 89.20 | 0.00 | 0.00 | 0.00 |
December | 110.06 | 83.37 | 26.69 | 109.22 | 128.62 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 115.23 | 59.54 | 55.70 | 132.16 | 67.17 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 90.64 | 18.46 | 26.69 | 102.51 | 22.12 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 143.74 | 97.11 | 72.19 | 171.59 | 138.36 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 112.21 | 76.78 | 35.42 | 104.03 | 113.53 | 0.00 | 0.00 | 0.00 |
February | 120.23 | 81.23 | 39.00 | 116.98 | 89.06 | 0.00 | 0.00 | 0.00 |
March | 104.62 | 55.09 | 49.53 | 108.81 | 60.75 | 0.00 | 0.00 | 0.00 |
April | 94.26 | 44.07 | 50.19 | 109.40 | 42.86 | 0.00 | 0.00 | 0.00 |
May | 78.09 | 21.17 | 56.92 | 98.44 | 25.17 | 0.00 | 0.00 | 0.00 |
June | 75.81 | 15.44 | 60.38 | 102.17 | 18.70 | 0.00 | 0.00 | 0.00 |
July | 80.25 | 20.22 | 60.03 | 111.19 | 17.51 | 0.00 | 0.00 | 0.00 |
August | 90.42 | 32.43 | 57.99 | 126.32 | 21.42 | 0.00 | 0.00 | 0.00 |
September | 109.57 | 57.73 | 51.84 | 143.89 | 34.68 | 0.00 | 0.00 | 0.00 |
October | 114.41 | 71.78 | 42.64 | 134.24 | 48.27 | 0.00 | 0.00 | 0.00 |
November | 86.32 | 54.04 | 32.28 | 86.10 | 72.13 | 0.00 | 0.00 | 0.00 |
December | 92.05 | 69.73 | 22.32 | 91.59 | 104.76 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 96.38 | 49.80 | 46.58 | 111.06 | 53.91 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 75.81 | 15.44 | 22.32 | 86.10 | 17.51 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 120.23 | 81.23 | 60.38 | 143.89 | 113.53 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 112.21 | 76.78 | 35.42 | 104.03 | 113.53 | 0.00 | 0.00 | 0.00 |
February | 120.23 | 81.23 | 39.00 | 116.98 | 89.06 | 0.00 | 0.00 | 0.00 |
March | 104.62 | 55.09 | 49.53 | 108.81 | 60.75 | 0.00 | 0.00 | 0.00 |
April | 94.26 | 44.07 | 50.19 | 109.40 | 42.86 | 0.00 | 0.00 | 0.00 |
May | 78.09 | 21.17 | 56.92 | 98.44 | 25.17 | 0.00 | 0.00 | 0.00 |
June | 75.81 | 15.44 | 60.38 | 102.17 | 18.70 | 0.00 | 0.00 | 0.00 |
July | 80.25 | 20.22 | 60.03 | 111.19 | 17.51 | 0.00 | 0.00 | 0.00 |
August | 90.42 | 32.43 | 57.99 | 126.32 | 21.42 | 0.00 | 0.00 | 0.00 |
September | 109.57 | 57.73 | 51.84 | 143.89 | 34.68 | 0.00 | 0.00 | 0.00 |
October | 114.41 | 71.78 | 42.64 | 134.24 | 48.27 | 0.00 | 0.00 | 0.00 |
November | 86.32 | 54.04 | 32.28 | 86.10 | 72.13 | 0.00 | 0.00 | 0.00 |
December | 92.05 | 69.73 | 22.32 | 91.59 | 104.76 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 96.38 | 49.80 | 46.58 | 111.06 | 53.91 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 75.81 | 15.44 | 22.32 | 86.10 | 17.51 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 120.23 | 81.23 | 60.38 | 143.89 | 113.53 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 134.15 | 91.80 | 42.35 | 125.09 | 133.80 | 0.00 | 0.00 | 0.00 |
February | 143.74 | 97.11 | 46.63 | 140.61 | 105.00 | 0.00 | 0.00 | 0.00 |
March | 125.09 | 65.87 | 59.22 | 130.75 | 71.64 | 0.00 | 0.00 | 0.00 |
April | 112.69 | 52.69 | 60.01 | 131.16 | 50.62 | 0.00 | 0.00 | 0.00 |
May | 93.36 | 25.31 | 68.05 | 117.93 | 29.85 | 0.00 | 0.00 | 0.00 |
June | 90.64 | 18.46 | 72.19 | 122.18 | 22.24 | 0.00 | 0.00 | 0.00 |
July | 95.95 | 24.18 | 71.77 | 132.92 | 20.86 | 0.00 | 0.00 | 0.00 |
August | 108.10 | 38.77 | 69.34 | 151.08 | 25.45 | 0.00 | 0.00 | 0.00 |
September | 131.00 | 69.03 | 61.97 | 172.16 | 41.18 | 0.00 | 0.00 | 0.00 |
October | 136.79 | 85.82 | 50.97 | 160.92 | 57.14 | 0.00 | 0.00 | 0.00 |
November | 103.21 | 64.61 | 38.60 | 103.43 | 85.04 | 0.00 | 0.00 | 0.00 |
December | 110.06 | 83.37 | 26.69 | 109.95 | 123.50 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 115.23 | 59.54 | 55.70 | 133.13 | 63.68 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 90.64 | 18.46 | 26.69 | 103.43 | 20.86 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 143.74 | 97.11 | 72.19 | 172.16 | 133.80 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.300530E+09 | 0.205659E+09 | 94870799.55 | 0.277372E+09 | 0.322108E+09 |
February | 0.290850E+09 | 0.196501E+09 | 94349415.32 | 0.281217E+09 | 0.231719E+09 |
March | 0.280223E+09 | 0.147556E+09 | 0.132667E+09 | 0.288727E+09 | 0.179745E+09 |
April | 0.244318E+09 | 0.114224E+09 | 0.130095E+09 | 0.280235E+09 | 0.126736E+09 |
May | 0.209156E+09 | 56705164.61 | 0.152451E+09 | 0.256041E+09 | 80970339.53 |
June | 0.196509E+09 | 40010314.16 | 0.156499E+09 | 0.262403E+09 | 54004416.56 |
July | 0.214952E+09 | 54162372.82 | 0.160790E+09 | 0.297249E+09 | 49547635.15 |
August | 0.242180E+09 | 86851594.76 | 0.155328E+09 | 0.337879E+09 | 60240589.92 |
September | 0.284004E+09 | 0.149647E+09 | 0.134357E+09 | 0.371543E+09 | 95639100.78 |
October | 0.306446E+09 | 0.192252E+09 | 0.114194E+09 | 0.356136E+09 | 0.142120E+09 |
November | 0.223754E+09 | 0.140074E+09 | 83679834.65 | 0.220663E+09 | 0.202604E+09 |
December | 0.246555E+09 | 0.186762E+09 | 59792482.78 | 0.243817E+09 | 0.298743E+09 |
Annual Sum or Average | 0.303948E+10 | 0.157040E+10 | 0.146907E+10 | 0.347328E+10 | 0.184418E+10 |
Minimum of Months | 0.196509E+09 | 40010314.16 | 59792482.78 | 0.220663E+09 | 49547635.15 |
Maximum of Months | 0.306446E+09 | 0.205659E+09 | 0.160790E+09 | 0.371543E+09 | 0.322108E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.300530E+09 | 0.205659E+09 | 94870799.55 | 0.277372E+09 | 0.322108E+09 |
February | 0.290850E+09 | 0.196501E+09 | 94349415.32 | 0.281217E+09 | 0.231719E+09 |
March | 0.280223E+09 | 0.147556E+09 | 0.132667E+09 | 0.288727E+09 | 0.179745E+09 |
April | 0.244318E+09 | 0.114224E+09 | 0.130095E+09 | 0.280235E+09 | 0.126736E+09 |
May | 0.209156E+09 | 56705164.61 | 0.152451E+09 | 0.256041E+09 | 80970339.53 |
June | 0.196509E+09 | 40010314.16 | 0.156499E+09 | 0.262403E+09 | 54004416.56 |
July | 0.214952E+09 | 54162372.82 | 0.160790E+09 | 0.297249E+09 | 49547635.15 |
August | 0.242180E+09 | 86851594.76 | 0.155328E+09 | 0.337879E+09 | 60240589.92 |
September | 0.284004E+09 | 0.149647E+09 | 0.134357E+09 | 0.371543E+09 | 95639100.78 |
October | 0.306446E+09 | 0.192252E+09 | 0.114194E+09 | 0.356136E+09 | 0.142120E+09 |
November | 0.223754E+09 | 0.140074E+09 | 83679834.65 | 0.220663E+09 | 0.202604E+09 |
December | 0.246555E+09 | 0.186762E+09 | 59792482.78 | 0.243817E+09 | 0.298743E+09 |
Annual Sum or Average | 0.303948E+10 | 0.157040E+10 | 0.146907E+10 | 0.347328E+10 | 0.184418E+10 |
Minimum of Months | 0.196509E+09 | 40010314.16 | 59792482.78 | 0.220663E+09 | 49547635.15 |
Maximum of Months | 0.306446E+09 | 0.205659E+09 | 0.160790E+09 | 0.371543E+09 | 0.322108E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.300530E+09 | 0.205659E+09 | 94870799.55 | 0.277372E+09 | 0.322108E+09 |
February | 0.290850E+09 | 0.196501E+09 | 94349415.32 | 0.281217E+09 | 0.231719E+09 |
March | 0.280223E+09 | 0.147556E+09 | 0.132667E+09 | 0.288727E+09 | 0.179745E+09 |
April | 0.244318E+09 | 0.114224E+09 | 0.130095E+09 | 0.280235E+09 | 0.126736E+09 |
May | 0.209156E+09 | 56705164.61 | 0.152451E+09 | 0.256041E+09 | 80970339.53 |
June | 0.196509E+09 | 40010314.16 | 0.156499E+09 | 0.262403E+09 | 54004416.56 |
July | 0.214952E+09 | 54162372.82 | 0.160790E+09 | 0.297249E+09 | 49547635.15 |
August | 0.242180E+09 | 86851594.76 | 0.155328E+09 | 0.337879E+09 | 60240589.92 |
September | 0.284004E+09 | 0.149647E+09 | 0.134357E+09 | 0.371543E+09 | 95639100.78 |
October | 0.306446E+09 | 0.192252E+09 | 0.114194E+09 | 0.356136E+09 | 0.142120E+09 |
November | 0.223754E+09 | 0.140074E+09 | 83679834.65 | 0.220663E+09 | 0.202604E+09 |
December | 0.246555E+09 | 0.186762E+09 | 59792482.78 | 0.243817E+09 | 0.298743E+09 |
Annual Sum or Average | 0.303948E+10 | 0.157040E+10 | 0.146907E+10 | 0.347328E+10 | 0.184418E+10 |
Minimum of Months | 0.196509E+09 | 40010314.16 | 59792482.78 | 0.220663E+09 | 49547635.15 |
Maximum of Months | 0.306446E+09 | 0.205659E+09 | 0.160790E+09 | 0.371543E+09 | 0.322108E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.300530E+09 | 0.205659E+09 | 94870799.55 | 0.277372E+09 | 0.322108E+09 |
February | 0.290850E+09 | 0.196501E+09 | 94349415.32 | 0.281217E+09 | 0.231719E+09 |
March | 0.280223E+09 | 0.147556E+09 | 0.132667E+09 | 0.288727E+09 | 0.179745E+09 |
April | 0.244318E+09 | 0.114224E+09 | 0.130095E+09 | 0.280235E+09 | 0.126736E+09 |
May | 0.209156E+09 | 56705164.61 | 0.152451E+09 | 0.256041E+09 | 80970339.53 |
June | 0.196509E+09 | 40010314.16 | 0.156499E+09 | 0.262403E+09 | 54004416.56 |
July | 0.214952E+09 | 54162372.82 | 0.160790E+09 | 0.297249E+09 | 49547635.15 |
August | 0.242180E+09 | 86851594.76 | 0.155328E+09 | 0.337879E+09 | 60240589.92 |
September | 0.284004E+09 | 0.149647E+09 | 0.134357E+09 | 0.371543E+09 | 95639100.78 |
October | 0.306446E+09 | 0.192252E+09 | 0.114194E+09 | 0.356136E+09 | 0.142120E+09 |
November | 0.223754E+09 | 0.140074E+09 | 83679834.65 | 0.220663E+09 | 0.202604E+09 |
December | 0.246555E+09 | 0.186762E+09 | 59792482.78 | 0.243817E+09 | 0.298743E+09 |
Annual Sum or Average | 0.303948E+10 | 0.157040E+10 | 0.146907E+10 | 0.347328E+10 | 0.184418E+10 |
Minimum of Months | 0.196509E+09 | 40010314.16 | 59792482.78 | 0.220663E+09 | 49547635.15 |
Maximum of Months | 0.306446E+09 | 0.205659E+09 | 0.160790E+09 | 0.371543E+09 | 0.322108E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.361283E+09 | 0.247234E+09 | 0.114049E+09 | 0.335199E+09 | 0.381994E+09 |
February | 0.349646E+09 | 0.236224E+09 | 0.113423E+09 | 0.339685E+09 | 0.274862E+09 |
March | 0.336871E+09 | 0.177385E+09 | 0.159486E+09 | 0.348649E+09 | 0.213257E+09 |
April | 0.293708E+09 | 0.137314E+09 | 0.156394E+09 | 0.337670E+09 | 0.150559E+09 |
May | 0.251438E+09 | 68168337.68 | 0.183270E+09 | 0.308368E+09 | 96493438.75 |
June | 0.236234E+09 | 48098557.24 | 0.188135E+09 | 0.315444E+09 | 64560375.73 |
July | 0.258406E+09 | 65111510.48 | 0.193294E+09 | 0.357197E+09 | 59359134.09 |
August | 0.291138E+09 | 0.104409E+09 | 0.186729E+09 | 0.406234E+09 | 71994106.12 |
September | 0.341417E+09 | 0.179899E+09 | 0.161518E+09 | 0.446888E+09 | 0.114196E+09 |
October | 0.368395E+09 | 0.231116E+09 | 0.137279E+09 | 0.429109E+09 | 0.169177E+09 |
November | 0.268987E+09 | 0.168391E+09 | 0.100596E+09 | 0.266414E+09 | 0.240334E+09 |
December | 0.296397E+09 | 0.224517E+09 | 71879769.41 | 0.294166E+09 | 0.354383E+09 |
Annual Sum or Average | 0.365392E+10 | 0.188787E+10 | 0.176605E+10 | 0.418502E+10 | 0.219117E+10 |
Minimum of Months | 0.236234E+09 | 48098557.24 | 71879769.41 | 0.266414E+09 | 59359134.09 |
Maximum of Months | 0.368395E+09 | 0.247234E+09 | 0.193294E+09 | 0.446888E+09 | 0.381994E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.361283E+09 | 0.247234E+09 | 0.114049E+09 | 0.335199E+09 | 0.381994E+09 |
February | 0.349646E+09 | 0.236224E+09 | 0.113423E+09 | 0.339685E+09 | 0.274862E+09 |
March | 0.336871E+09 | 0.177385E+09 | 0.159486E+09 | 0.348649E+09 | 0.213257E+09 |
April | 0.293708E+09 | 0.137314E+09 | 0.156394E+09 | 0.337670E+09 | 0.150559E+09 |
May | 0.251438E+09 | 68168337.68 | 0.183270E+09 | 0.308368E+09 | 96493438.75 |
June | 0.236234E+09 | 48098557.24 | 0.188135E+09 | 0.315444E+09 | 64560375.73 |
July | 0.258406E+09 | 65111510.48 | 0.193294E+09 | 0.357197E+09 | 59359134.09 |
August | 0.291138E+09 | 0.104409E+09 | 0.186729E+09 | 0.406234E+09 | 71994106.12 |
September | 0.341417E+09 | 0.179899E+09 | 0.161518E+09 | 0.446888E+09 | 0.114196E+09 |
October | 0.368395E+09 | 0.231116E+09 | 0.137279E+09 | 0.429109E+09 | 0.169177E+09 |
November | 0.268987E+09 | 0.168391E+09 | 0.100596E+09 | 0.266414E+09 | 0.240334E+09 |
December | 0.296397E+09 | 0.224517E+09 | 71879769.41 | 0.294166E+09 | 0.354383E+09 |
Annual Sum or Average | 0.365392E+10 | 0.188787E+10 | 0.176605E+10 | 0.418502E+10 | 0.219117E+10 |
Minimum of Months | 0.236234E+09 | 48098557.24 | 71879769.41 | 0.266414E+09 | 59359134.09 |
Maximum of Months | 0.368395E+09 | 0.247234E+09 | 0.193294E+09 | 0.446888E+09 | 0.381994E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.300530E+09 | 0.205659E+09 | 94870799.55 | 0.274528E+09 | 0.332192E+09 |
February | 0.290850E+09 | 0.196501E+09 | 94349415.32 | 0.278180E+09 | 0.240733E+09 |
March | 0.280223E+09 | 0.147556E+09 | 0.132667E+09 | 0.284916E+09 | 0.190149E+09 |
April | 0.244318E+09 | 0.114224E+09 | 0.130095E+09 | 0.276964E+09 | 0.136343E+09 |
May | 0.209156E+09 | 56705164.61 | 0.152451E+09 | 0.251216E+09 | 87735639.54 |
June | 0.196509E+09 | 40010314.16 | 0.156499E+09 | 0.260336E+09 | 57014835.48 |
July | 0.214952E+09 | 54162372.82 | 0.160790E+09 | 0.296481E+09 | 50498102.08 |
August | 0.242180E+09 | 86851594.76 | 0.155328E+09 | 0.337154E+09 | 61422324.80 |
September | 0.284004E+09 | 0.149647E+09 | 0.134357E+09 | 0.369665E+09 | 99568057.82 |
October | 0.306446E+09 | 0.192252E+09 | 0.114194E+09 | 0.352738E+09 | 0.151220E+09 |
November | 0.223754E+09 | 0.140074E+09 | 83679834.65 | 0.217826E+09 | 0.212489E+09 |
December | 0.246555E+09 | 0.186762E+09 | 59792482.78 | 0.241690E+09 | 0.309370E+09 |
Annual Sum or Average | 0.303948E+10 | 0.157040E+10 | 0.146907E+10 | 0.344169E+10 | 0.192873E+10 |
Minimum of Months | 0.196509E+09 | 40010314.16 | 59792482.78 | 0.217826E+09 | 50498102.08 |
Maximum of Months | 0.306446E+09 | 0.205659E+09 | 0.160790E+09 | 0.369665E+09 | 0.332192E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.300530E+09 | 0.205659E+09 | 94870799.55 | 0.274528E+09 | 0.332192E+09 |
February | 0.290850E+09 | 0.196501E+09 | 94349415.32 | 0.278180E+09 | 0.240733E+09 |
March | 0.280223E+09 | 0.147556E+09 | 0.132667E+09 | 0.284916E+09 | 0.190149E+09 |
April | 0.244318E+09 | 0.114224E+09 | 0.130095E+09 | 0.276964E+09 | 0.136343E+09 |
May | 0.209156E+09 | 56705164.61 | 0.152451E+09 | 0.251216E+09 | 87735639.54 |
June | 0.196509E+09 | 40010314.16 | 0.156499E+09 | 0.260336E+09 | 57014835.48 |
July | 0.214952E+09 | 54162372.82 | 0.160790E+09 | 0.296481E+09 | 50498102.08 |
August | 0.242180E+09 | 86851594.76 | 0.155328E+09 | 0.337154E+09 | 61422324.80 |
September | 0.284004E+09 | 0.149647E+09 | 0.134357E+09 | 0.369665E+09 | 99568057.82 |
October | 0.306446E+09 | 0.192252E+09 | 0.114194E+09 | 0.352738E+09 | 0.151220E+09 |
November | 0.223754E+09 | 0.140074E+09 | 83679834.65 | 0.217826E+09 | 0.212489E+09 |
December | 0.246555E+09 | 0.186762E+09 | 59792482.78 | 0.241690E+09 | 0.309370E+09 |
Annual Sum or Average | 0.303948E+10 | 0.157040E+10 | 0.146907E+10 | 0.344169E+10 | 0.192873E+10 |
Minimum of Months | 0.196509E+09 | 40010314.16 | 59792482.78 | 0.217826E+09 | 50498102.08 |
Maximum of Months | 0.306446E+09 | 0.205659E+09 | 0.160790E+09 | 0.369665E+09 | 0.332192E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.361283E+09 | 0.247234E+09 | 0.114049E+09 | 0.331876E+09 | 0.393847E+09 |
February | 0.349646E+09 | 0.236224E+09 | 0.113423E+09 | 0.336122E+09 | 0.285461E+09 |
March | 0.336871E+09 | 0.177385E+09 | 0.159486E+09 | 0.344148E+09 | 0.225480E+09 |
April | 0.293708E+09 | 0.137314E+09 | 0.156394E+09 | 0.333796E+09 | 0.161871E+09 |
May | 0.251438E+09 | 68168337.68 | 0.183270E+09 | 0.302659E+09 | 0.104468E+09 |
June | 0.236234E+09 | 48098557.24 | 0.188135E+09 | 0.313003E+09 | 68113656.09 |
July | 0.258406E+09 | 65111510.48 | 0.193294E+09 | 0.356313E+09 | 60488647.88 |
August | 0.291138E+09 | 0.104409E+09 | 0.186729E+09 | 0.405422E+09 | 73376429.62 |
September | 0.341417E+09 | 0.179899E+09 | 0.161518E+09 | 0.444704E+09 | 0.118808E+09 |
October | 0.368395E+09 | 0.231116E+09 | 0.137279E+09 | 0.425130E+09 | 0.179839E+09 |
November | 0.268987E+09 | 0.168391E+09 | 0.100596E+09 | 0.263077E+09 | 0.251926E+09 |
December | 0.296397E+09 | 0.224517E+09 | 71879769.41 | 0.291672E+09 | 0.366880E+09 |
Annual Sum or Average | 0.365392E+10 | 0.188787E+10 | 0.176605E+10 | 0.414792E+10 | 0.229056E+10 |
Minimum of Months | 0.236234E+09 | 48098557.24 | 71879769.41 | 0.263077E+09 | 60488647.88 |
Maximum of Months | 0.368395E+09 | 0.247234E+09 | 0.193294E+09 | 0.444704E+09 | 0.393847E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.300530E+09 | 0.205659E+09 | 94870799.55 | 0.274899E+09 | 0.325899E+09 |
February | 0.290850E+09 | 0.196501E+09 | 94349415.32 | 0.278540E+09 | 0.235663E+09 |
March | 0.280223E+09 | 0.147556E+09 | 0.132667E+09 | 0.285382E+09 | 0.185967E+09 |
April | 0.244318E+09 | 0.114224E+09 | 0.130095E+09 | 0.277299E+09 | 0.133272E+09 |
May | 0.209156E+09 | 56705164.61 | 0.152451E+09 | 0.251602E+09 | 87365170.23 |
June | 0.196509E+09 | 40010314.16 | 0.156499E+09 | 0.259783E+09 | 58945800.68 |
July | 0.214952E+09 | 54162372.82 | 0.160790E+09 | 0.295468E+09 | 53925186.26 |
August | 0.242180E+09 | 86851594.76 | 0.155328E+09 | 0.336744E+09 | 64606328.55 |
September | 0.284004E+09 | 0.149647E+09 | 0.134357E+09 | 0.369680E+09 | 0.101051E+09 |
October | 0.306446E+09 | 0.192252E+09 | 0.114194E+09 | 0.353947E+09 | 0.146934E+09 |
November | 0.223754E+09 | 0.140074E+09 | 83679834.65 | 0.218531E+09 | 0.207428E+09 |
December | 0.246555E+09 | 0.186762E+09 | 59792482.78 | 0.242008E+09 | 0.303871E+09 |
Annual Sum or Average | 0.303948E+10 | 0.157040E+10 | 0.146907E+10 | 0.344388E+10 | 0.190493E+10 |
Minimum of Months | 0.196509E+09 | 40010314.16 | 59792482.78 | 0.218531E+09 | 53925186.26 |
Maximum of Months | 0.306446E+09 | 0.205659E+09 | 0.160790E+09 | 0.369680E+09 | 0.325899E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.300530E+09 | 0.205659E+09 | 94870799.55 | 0.274899E+09 | 0.325899E+09 |
February | 0.290850E+09 | 0.196501E+09 | 94349415.32 | 0.278540E+09 | 0.235663E+09 |
March | 0.280223E+09 | 0.147556E+09 | 0.132667E+09 | 0.285382E+09 | 0.185967E+09 |
April | 0.244318E+09 | 0.114224E+09 | 0.130095E+09 | 0.277299E+09 | 0.133272E+09 |
May | 0.209156E+09 | 56705164.61 | 0.152451E+09 | 0.251602E+09 | 87365170.23 |
June | 0.196509E+09 | 40010314.16 | 0.156499E+09 | 0.259783E+09 | 58945800.68 |
July | 0.214952E+09 | 54162372.82 | 0.160790E+09 | 0.295468E+09 | 53925186.26 |
August | 0.242180E+09 | 86851594.76 | 0.155328E+09 | 0.336744E+09 | 64606328.55 |
September | 0.284004E+09 | 0.149647E+09 | 0.134357E+09 | 0.369680E+09 | 0.101051E+09 |
October | 0.306446E+09 | 0.192252E+09 | 0.114194E+09 | 0.353947E+09 | 0.146934E+09 |
November | 0.223754E+09 | 0.140074E+09 | 83679834.65 | 0.218531E+09 | 0.207428E+09 |
December | 0.246555E+09 | 0.186762E+09 | 59792482.78 | 0.242008E+09 | 0.303871E+09 |
Annual Sum or Average | 0.303948E+10 | 0.157040E+10 | 0.146907E+10 | 0.344388E+10 | 0.190493E+10 |
Minimum of Months | 0.196509E+09 | 40010314.16 | 59792482.78 | 0.218531E+09 | 53925186.26 |
Maximum of Months | 0.306446E+09 | 0.205659E+09 | 0.160790E+09 | 0.369680E+09 | 0.325899E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.359309E+09 | 0.245883E+09 | 0.113426E+09 | 0.330514E+09 | 0.384306E+09 |
February | 0.347736E+09 | 0.234933E+09 | 0.112803E+09 | 0.334728E+09 | 0.277964E+09 |
March | 0.335030E+09 | 0.176416E+09 | 0.158614E+09 | 0.342827E+09 | 0.219357E+09 |
April | 0.292103E+09 | 0.136564E+09 | 0.155539E+09 | 0.332378E+09 | 0.157399E+09 |
May | 0.250064E+09 | 67795833.10 | 0.182268E+09 | 0.301467E+09 | 0.103456E+09 |
June | 0.234943E+09 | 47835723.60 | 0.187107E+09 | 0.310652E+09 | 69996815.15 |
July | 0.256994E+09 | 64755709.87 | 0.192238E+09 | 0.353178E+09 | 64162531.01 |
August | 0.289547E+09 | 0.103838E+09 | 0.185708E+09 | 0.402722E+09 | 76691032.40 |
September | 0.339551E+09 | 0.178916E+09 | 0.160636E+09 | 0.442296E+09 | 0.119892E+09 |
October | 0.366382E+09 | 0.229853E+09 | 0.136529E+09 | 0.424249E+09 | 0.173850E+09 |
November | 0.267517E+09 | 0.167471E+09 | 0.100046E+09 | 0.262485E+09 | 0.244627E+09 |
December | 0.294777E+09 | 0.223290E+09 | 71486983.78 | 0.290472E+09 | 0.358426E+09 |
Annual Sum or Average | 0.363395E+10 | 0.187755E+10 | 0.175640E+10 | 0.412797E+10 | 0.225013E+10 |
Minimum of Months | 0.234943E+09 | 47835723.60 | 71486983.78 | 0.262485E+09 | 64162531.01 |
Maximum of Months | 0.366382E+09 | 0.245883E+09 | 0.192238E+09 | 0.442296E+09 | 0.384306E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.300530E+09 | 0.205659E+09 | 94870799.55 | 0.275169E+09 | 0.323527E+09 |
February | 0.290850E+09 | 0.196501E+09 | 94349415.32 | 0.278842E+09 | 0.233690E+09 |
March | 0.280223E+09 | 0.147556E+09 | 0.132667E+09 | 0.285799E+09 | 0.184013E+09 |
April | 0.244318E+09 | 0.114224E+09 | 0.130095E+09 | 0.277718E+09 | 0.131557E+09 |
May | 0.209156E+09 | 56705164.61 | 0.152451E+09 | 0.252396E+09 | 85935494.13 |
June | 0.196509E+09 | 40010314.16 | 0.156499E+09 | 0.260019E+09 | 58515463.72 |
July | 0.214952E+09 | 54162372.82 | 0.160790E+09 | 0.295475E+09 | 53930336.51 |
August | 0.242180E+09 | 86851594.76 | 0.155328E+09 | 0.336781E+09 | 64521280.40 |
September | 0.284004E+09 | 0.149647E+09 | 0.134357E+09 | 0.369915E+09 | 0.100415E+09 |
October | 0.306446E+09 | 0.192252E+09 | 0.114194E+09 | 0.354635E+09 | 0.144805E+09 |
November | 0.223754E+09 | 0.140074E+09 | 83679834.65 | 0.218998E+09 | 0.205130E+09 |
December | 0.246555E+09 | 0.186762E+09 | 59792482.78 | 0.242243E+09 | 0.301648E+09 |
Annual Sum or Average | 0.303948E+10 | 0.157040E+10 | 0.146907E+10 | 0.344799E+10 | 0.188769E+10 |
Minimum of Months | 0.196509E+09 | 40010314.16 | 59792482.78 | 0.218998E+09 | 53930336.51 |
Maximum of Months | 0.306446E+09 | 0.205659E+09 | 0.160790E+09 | 0.369915E+09 | 0.323527E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.300530E+09 | 0.205659E+09 | 94870799.55 | 0.275169E+09 | 0.323527E+09 |
February | 0.290850E+09 | 0.196501E+09 | 94349415.32 | 0.278842E+09 | 0.233690E+09 |
March | 0.280223E+09 | 0.147556E+09 | 0.132667E+09 | 0.285799E+09 | 0.184013E+09 |
April | 0.244318E+09 | 0.114224E+09 | 0.130095E+09 | 0.277718E+09 | 0.131557E+09 |
May | 0.209156E+09 | 56705164.61 | 0.152451E+09 | 0.252396E+09 | 85935494.13 |
June | 0.196509E+09 | 40010314.16 | 0.156499E+09 | 0.260019E+09 | 58515463.72 |
July | 0.214952E+09 | 54162372.82 | 0.160790E+09 | 0.295475E+09 | 53930336.51 |
August | 0.242180E+09 | 86851594.76 | 0.155328E+09 | 0.336781E+09 | 64521280.40 |
September | 0.284004E+09 | 0.149647E+09 | 0.134357E+09 | 0.369915E+09 | 0.100415E+09 |
October | 0.306446E+09 | 0.192252E+09 | 0.114194E+09 | 0.354635E+09 | 0.144805E+09 |
November | 0.223754E+09 | 0.140074E+09 | 83679834.65 | 0.218998E+09 | 0.205130E+09 |
December | 0.246555E+09 | 0.186762E+09 | 59792482.78 | 0.242243E+09 | 0.301648E+09 |
Annual Sum or Average | 0.303948E+10 | 0.157040E+10 | 0.146907E+10 | 0.344799E+10 | 0.188769E+10 |
Minimum of Months | 0.196509E+09 | 40010314.16 | 59792482.78 | 0.218998E+09 | 53930336.51 |
Maximum of Months | 0.306446E+09 | 0.205659E+09 | 0.160790E+09 | 0.369915E+09 | 0.323527E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.359309E+09 | 0.245883E+09 | 0.113426E+09 | 0.330840E+09 | 0.381490E+09 |
February | 0.347736E+09 | 0.234933E+09 | 0.112803E+09 | 0.335094E+09 | 0.275625E+09 |
March | 0.335030E+09 | 0.176416E+09 | 0.158614E+09 | 0.343331E+09 | 0.217045E+09 |
April | 0.292103E+09 | 0.136564E+09 | 0.155539E+09 | 0.332882E+09 | 0.155369E+09 |
May | 0.250064E+09 | 67795833.10 | 0.182268E+09 | 0.302414E+09 | 0.101768E+09 |
June | 0.234943E+09 | 47835723.60 | 0.187107E+09 | 0.310935E+09 | 69489821.48 |
July | 0.256994E+09 | 64755709.87 | 0.192238E+09 | 0.353188E+09 | 64168630.22 |
August | 0.289547E+09 | 0.103838E+09 | 0.185708E+09 | 0.402767E+09 | 76590551.90 |
September | 0.339551E+09 | 0.178916E+09 | 0.160636E+09 | 0.442577E+09 | 0.119141E+09 |
October | 0.366382E+09 | 0.229853E+09 | 0.136529E+09 | 0.425071E+09 | 0.171335E+09 |
November | 0.267517E+09 | 0.167471E+09 | 0.100046E+09 | 0.263048E+09 | 0.241907E+09 |
December | 0.294777E+09 | 0.223290E+09 | 71486983.78 | 0.290756E+09 | 0.355787E+09 |
Annual Sum or Average | 0.363395E+10 | 0.187755E+10 | 0.175640E+10 | 0.413290E+10 | 0.222972E+10 |
Minimum of Months | 0.234943E+09 | 47835723.60 | 71486983.78 | 0.263048E+09 | 64168630.22 |
Maximum of Months | 0.366382E+09 | 0.245883E+09 | 0.192238E+09 | 0.442577E+09 | 0.381490E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.300530E+09 | 0.205659E+09 | 94870799.55 | 0.275525E+09 | 0.321696E+09 |
February | 0.290850E+09 | 0.196501E+09 | 94349415.32 | 0.279239E+09 | 0.232113E+09 |
March | 0.280223E+09 | 0.147556E+09 | 0.132667E+09 | 0.286384E+09 | 0.182234E+09 |
April | 0.244318E+09 | 0.114224E+09 | 0.130095E+09 | 0.278339E+09 | 0.129846E+09 |
May | 0.209156E+09 | 56705164.61 | 0.152451E+09 | 0.253813E+09 | 83939291.68 |
June | 0.196509E+09 | 40010314.16 | 0.156499E+09 | 0.260634E+09 | 57516368.36 |
July | 0.214952E+09 | 54162372.82 | 0.160790E+09 | 0.295814E+09 | 53262281.44 |
August | 0.242180E+09 | 86851594.76 | 0.155328E+09 | 0.337075E+09 | 63821781.17 |
September | 0.284004E+09 | 0.149647E+09 | 0.134357E+09 | 0.370427E+09 | 99270472.87 |
October | 0.306446E+09 | 0.192252E+09 | 0.114194E+09 | 0.355363E+09 | 0.143055E+09 |
November | 0.223754E+09 | 0.140074E+09 | 83679834.65 | 0.219530E+09 | 0.203182E+09 |
December | 0.246555E+09 | 0.186762E+09 | 59792482.78 | 0.242552E+09 | 0.299784E+09 |
Annual Sum or Average | 0.303948E+10 | 0.157040E+10 | 0.146907E+10 | 0.345470E+10 | 0.186972E+10 |
Minimum of Months | 0.196509E+09 | 40010314.16 | 59792482.78 | 0.219530E+09 | 53262281.44 |
Maximum of Months | 0.306446E+09 | 0.205659E+09 | 0.160790E+09 | 0.370427E+09 | 0.321696E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.300530E+09 | 0.205659E+09 | 94870799.55 | 0.275525E+09 | 0.321696E+09 |
February | 0.290850E+09 | 0.196501E+09 | 94349415.32 | 0.279239E+09 | 0.232113E+09 |
March | 0.280223E+09 | 0.147556E+09 | 0.132667E+09 | 0.286384E+09 | 0.182234E+09 |
April | 0.244318E+09 | 0.114224E+09 | 0.130095E+09 | 0.278339E+09 | 0.129846E+09 |
May | 0.209156E+09 | 56705164.61 | 0.152451E+09 | 0.253813E+09 | 83939291.68 |
June | 0.196509E+09 | 40010314.16 | 0.156499E+09 | 0.260634E+09 | 57516368.36 |
July | 0.214952E+09 | 54162372.82 | 0.160790E+09 | 0.295814E+09 | 53262281.44 |
August | 0.242180E+09 | 86851594.76 | 0.155328E+09 | 0.337075E+09 | 63821781.17 |
September | 0.284004E+09 | 0.149647E+09 | 0.134357E+09 | 0.370427E+09 | 99270472.87 |
October | 0.306446E+09 | 0.192252E+09 | 0.114194E+09 | 0.355363E+09 | 0.143055E+09 |
November | 0.223754E+09 | 0.140074E+09 | 83679834.65 | 0.219530E+09 | 0.203182E+09 |
December | 0.246555E+09 | 0.186762E+09 | 59792482.78 | 0.242552E+09 | 0.299784E+09 |
Annual Sum or Average | 0.303948E+10 | 0.157040E+10 | 0.146907E+10 | 0.345470E+10 | 0.186972E+10 |
Minimum of Months | 0.196509E+09 | 40010314.16 | 59792482.78 | 0.219530E+09 | 53262281.44 |
Maximum of Months | 0.306446E+09 | 0.205659E+09 | 0.160790E+09 | 0.370427E+09 | 0.321696E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.359309E+09 | 0.245883E+09 | 0.113426E+09 | 0.331272E+09 | 0.379316E+09 |
February | 0.347736E+09 | 0.234933E+09 | 0.112803E+09 | 0.335575E+09 | 0.273755E+09 |
March | 0.335030E+09 | 0.176416E+09 | 0.158614E+09 | 0.344038E+09 | 0.214942E+09 |
April | 0.292103E+09 | 0.136564E+09 | 0.155539E+09 | 0.333626E+09 | 0.153348E+09 |
May | 0.250064E+09 | 67795833.10 | 0.182268E+09 | 0.304104E+09 | 99416790.62 |
June | 0.234943E+09 | 47835723.60 | 0.187107E+09 | 0.311672E+09 | 68314855.41 |
July | 0.256994E+09 | 64755709.87 | 0.192238E+09 | 0.353595E+09 | 63384390.67 |
August | 0.289547E+09 | 0.103838E+09 | 0.185708E+09 | 0.403121E+09 | 75769483.73 |
September | 0.339551E+09 | 0.178916E+09 | 0.160636E+09 | 0.443191E+09 | 0.117794E+09 |
October | 0.366382E+09 | 0.229853E+09 | 0.136529E+09 | 0.425944E+09 | 0.169273E+09 |
November | 0.267517E+09 | 0.167471E+09 | 0.100046E+09 | 0.263689E+09 | 0.239605E+09 |
December | 0.294777E+09 | 0.223290E+09 | 71486983.78 | 0.291131E+09 | 0.353573E+09 |
Annual Sum or Average | 0.363395E+10 | 0.187755E+10 | 0.175640E+10 | 0.414096E+10 | 0.220849E+10 |
Minimum of Months | 0.234943E+09 | 47835723.60 | 71486983.78 | 0.263689E+09 | 63384390.67 |
Maximum of Months | 0.366382E+09 | 0.245883E+09 | 0.192238E+09 | 0.443191E+09 | 0.379316E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.300530E+09 | 0.205659E+09 | 94870799.55 | 0.277504E+09 | 0.314473E+09 |
February | 0.290850E+09 | 0.196501E+09 | 94349415.32 | 0.281330E+09 | 0.226570E+09 |
March | 0.280223E+09 | 0.147556E+09 | 0.132667E+09 | 0.288584E+09 | 0.176553E+09 |
April | 0.244318E+09 | 0.114224E+09 | 0.130095E+09 | 0.280023E+09 | 0.125236E+09 |
May | 0.209156E+09 | 56705164.61 | 0.152451E+09 | 0.256371E+09 | 79694992.61 |
June | 0.196509E+09 | 40010314.16 | 0.156499E+09 | 0.261329E+09 | 55051658.77 |
July | 0.214952E+09 | 54162372.82 | 0.160790E+09 | 0.295912E+09 | 51331679.40 |
August | 0.242180E+09 | 86851594.76 | 0.155328E+09 | 0.337178E+09 | 61742107.99 |
September | 0.284004E+09 | 0.149647E+09 | 0.134357E+09 | 0.371131E+09 | 96609401.29 |
October | 0.306446E+09 | 0.192252E+09 | 0.114194E+09 | 0.357098E+09 | 0.139206E+09 |
November | 0.223754E+09 | 0.140074E+09 | 83679834.65 | 0.221234E+09 | 0.197683E+09 |
December | 0.246555E+09 | 0.186762E+09 | 59792482.78 | 0.244088E+09 | 0.292900E+09 |
Annual Sum or Average | 0.303948E+10 | 0.157040E+10 | 0.146907E+10 | 0.347178E+10 | 0.181705E+10 |
Minimum of Months | 0.196509E+09 | 40010314.16 | 59792482.78 | 0.221234E+09 | 51331679.40 |
Maximum of Months | 0.306446E+09 | 0.205659E+09 | 0.160790E+09 | 0.371131E+09 | 0.314473E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.300530E+09 | 0.205659E+09 | 94870799.55 | 0.277504E+09 | 0.314473E+09 |
February | 0.290850E+09 | 0.196501E+09 | 94349415.32 | 0.281330E+09 | 0.226570E+09 |
March | 0.280223E+09 | 0.147556E+09 | 0.132667E+09 | 0.288584E+09 | 0.176553E+09 |
April | 0.244318E+09 | 0.114224E+09 | 0.130095E+09 | 0.280023E+09 | 0.125236E+09 |
May | 0.209156E+09 | 56705164.61 | 0.152451E+09 | 0.256371E+09 | 79694992.61 |
June | 0.196509E+09 | 40010314.16 | 0.156499E+09 | 0.261329E+09 | 55051658.77 |
July | 0.214952E+09 | 54162372.82 | 0.160790E+09 | 0.295912E+09 | 51331679.40 |
August | 0.242180E+09 | 86851594.76 | 0.155328E+09 | 0.337178E+09 | 61742107.99 |
September | 0.284004E+09 | 0.149647E+09 | 0.134357E+09 | 0.371131E+09 | 96609401.29 |
October | 0.306446E+09 | 0.192252E+09 | 0.114194E+09 | 0.357098E+09 | 0.139206E+09 |
November | 0.223754E+09 | 0.140074E+09 | 83679834.65 | 0.221234E+09 | 0.197683E+09 |
December | 0.246555E+09 | 0.186762E+09 | 59792482.78 | 0.244088E+09 | 0.292900E+09 |
Annual Sum or Average | 0.303948E+10 | 0.157040E+10 | 0.146907E+10 | 0.347178E+10 | 0.181705E+10 |
Minimum of Months | 0.196509E+09 | 40010314.16 | 59792482.78 | 0.221234E+09 | 51331679.40 |
Maximum of Months | 0.306446E+09 | 0.205659E+09 | 0.160790E+09 | 0.371131E+09 | 0.314473E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.300530E+09 | 0.205659E+09 | 94870799.55 | 0.277504E+09 | 0.314473E+09 |
February | 0.290850E+09 | 0.196501E+09 | 94349415.32 | 0.281330E+09 | 0.226570E+09 |
March | 0.280223E+09 | 0.147556E+09 | 0.132667E+09 | 0.288584E+09 | 0.176553E+09 |
April | 0.244318E+09 | 0.114224E+09 | 0.130095E+09 | 0.280023E+09 | 0.125236E+09 |
May | 0.209156E+09 | 56705164.61 | 0.152451E+09 | 0.256371E+09 | 79694992.61 |
June | 0.196509E+09 | 40010314.16 | 0.156499E+09 | 0.261329E+09 | 55051658.77 |
July | 0.214952E+09 | 54162372.82 | 0.160790E+09 | 0.295912E+09 | 51331679.40 |
August | 0.242180E+09 | 86851594.76 | 0.155328E+09 | 0.337178E+09 | 61742107.99 |
September | 0.284004E+09 | 0.149647E+09 | 0.134357E+09 | 0.371131E+09 | 96609401.29 |
October | 0.306446E+09 | 0.192252E+09 | 0.114194E+09 | 0.357098E+09 | 0.139206E+09 |
November | 0.223754E+09 | 0.140074E+09 | 83679834.65 | 0.221234E+09 | 0.197683E+09 |
December | 0.246555E+09 | 0.186762E+09 | 59792482.78 | 0.244088E+09 | 0.292900E+09 |
Annual Sum or Average | 0.303948E+10 | 0.157040E+10 | 0.146907E+10 | 0.347178E+10 | 0.181705E+10 |
Minimum of Months | 0.196509E+09 | 40010314.16 | 59792482.78 | 0.221234E+09 | 51331679.40 |
Maximum of Months | 0.306446E+09 | 0.205659E+09 | 0.160790E+09 | 0.371131E+09 | 0.314473E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.300530E+09 | 0.205659E+09 | 94870799.55 | 0.277504E+09 | 0.314473E+09 |
February | 0.290850E+09 | 0.196501E+09 | 94349415.32 | 0.281330E+09 | 0.226570E+09 |
March | 0.280223E+09 | 0.147556E+09 | 0.132667E+09 | 0.288584E+09 | 0.176553E+09 |
April | 0.244318E+09 | 0.114224E+09 | 0.130095E+09 | 0.280023E+09 | 0.125236E+09 |
May | 0.209156E+09 | 56705164.61 | 0.152451E+09 | 0.256371E+09 | 79694992.61 |
June | 0.196509E+09 | 40010314.16 | 0.156499E+09 | 0.261329E+09 | 55051658.77 |
July | 0.214952E+09 | 54162372.82 | 0.160790E+09 | 0.295912E+09 | 51331679.40 |
August | 0.242180E+09 | 86851594.76 | 0.155328E+09 | 0.337178E+09 | 61742107.99 |
September | 0.284004E+09 | 0.149647E+09 | 0.134357E+09 | 0.371131E+09 | 96609401.29 |
October | 0.306446E+09 | 0.192252E+09 | 0.114194E+09 | 0.357098E+09 | 0.139206E+09 |
November | 0.223754E+09 | 0.140074E+09 | 83679834.65 | 0.221234E+09 | 0.197683E+09 |
December | 0.246555E+09 | 0.186762E+09 | 59792482.78 | 0.244088E+09 | 0.292900E+09 |
Annual Sum or Average | 0.303948E+10 | 0.157040E+10 | 0.146907E+10 | 0.347178E+10 | 0.181705E+10 |
Minimum of Months | 0.196509E+09 | 40010314.16 | 59792482.78 | 0.221234E+09 | 51331679.40 |
Maximum of Months | 0.306446E+09 | 0.205659E+09 | 0.160790E+09 | 0.371131E+09 | 0.314473E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.359309E+09 | 0.245883E+09 | 0.113426E+09 | 0.333535E+09 | 0.370970E+09 |
February | 0.347736E+09 | 0.234933E+09 | 0.112803E+09 | 0.337974E+09 | 0.267347E+09 |
March | 0.335030E+09 | 0.176416E+09 | 0.158614E+09 | 0.346582E+09 | 0.208357E+09 |
April | 0.292103E+09 | 0.136564E+09 | 0.155539E+09 | 0.335580E+09 | 0.147969E+09 |
May | 0.250064E+09 | 67795833.10 | 0.182268E+09 | 0.307092E+09 | 94438468.90 |
June | 0.234943E+09 | 47835723.60 | 0.187107E+09 | 0.312477E+09 | 65410901.65 |
July | 0.256994E+09 | 64755709.87 | 0.192238E+09 | 0.353693E+09 | 61100750.82 |
August | 0.289547E+09 | 0.103838E+09 | 0.185708E+09 | 0.403206E+09 | 73328429.61 |
September | 0.339551E+09 | 0.178916E+09 | 0.160636E+09 | 0.443976E+09 | 0.114670E+09 |
October | 0.366382E+09 | 0.229853E+09 | 0.136529E+09 | 0.427928E+09 | 0.164787E+09 |
November | 0.267517E+09 | 0.167471E+09 | 0.100046E+09 | 0.265654E+09 | 0.233226E+09 |
December | 0.294777E+09 | 0.223290E+09 | 71486983.78 | 0.292892E+09 | 0.345596E+09 |
Annual Sum or Average | 0.363395E+10 | 0.187755E+10 | 0.175640E+10 | 0.416059E+10 | 0.214720E+10 |
Minimum of Months | 0.234943E+09 | 47835723.60 | 71486983.78 | 0.265654E+09 | 61100750.82 |
Maximum of Months | 0.366382E+09 | 0.245883E+09 | 0.192238E+09 | 0.443976E+09 | 0.370970E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.359309E+09 | 0.245883E+09 | 0.113426E+09 | 0.333535E+09 | 0.370970E+09 |
February | 0.347736E+09 | 0.234933E+09 | 0.112803E+09 | 0.337974E+09 | 0.267347E+09 |
March | 0.335030E+09 | 0.176416E+09 | 0.158614E+09 | 0.346582E+09 | 0.208357E+09 |
April | 0.292103E+09 | 0.136564E+09 | 0.155539E+09 | 0.335580E+09 | 0.147969E+09 |
May | 0.250064E+09 | 67795833.10 | 0.182268E+09 | 0.307092E+09 | 94438468.90 |
June | 0.234943E+09 | 47835723.60 | 0.187107E+09 | 0.312477E+09 | 65410901.65 |
July | 0.256994E+09 | 64755709.87 | 0.192238E+09 | 0.353693E+09 | 61100750.82 |
August | 0.289547E+09 | 0.103838E+09 | 0.185708E+09 | 0.403206E+09 | 73328429.61 |
September | 0.339551E+09 | 0.178916E+09 | 0.160636E+09 | 0.443976E+09 | 0.114670E+09 |
October | 0.366382E+09 | 0.229853E+09 | 0.136529E+09 | 0.427928E+09 | 0.164787E+09 |
November | 0.267517E+09 | 0.167471E+09 | 0.100046E+09 | 0.265654E+09 | 0.233226E+09 |
December | 0.294777E+09 | 0.223290E+09 | 71486983.78 | 0.292892E+09 | 0.345596E+09 |
Annual Sum or Average | 0.363395E+10 | 0.187755E+10 | 0.175640E+10 | 0.416059E+10 | 0.214720E+10 |
Minimum of Months | 0.234943E+09 | 47835723.60 | 71486983.78 | 0.265654E+09 | 61100750.82 |
Maximum of Months | 0.366382E+09 | 0.245883E+09 | 0.192238E+09 | 0.443976E+09 | 0.370970E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.300530E+09 | 0.205659E+09 | 94870799.55 | 0.276294E+09 | 0.316729E+09 |
February | 0.290850E+09 | 0.196501E+09 | 94349415.32 | 0.280196E+09 | 0.228045E+09 |
March | 0.280223E+09 | 0.147556E+09 | 0.132667E+09 | 0.287522E+09 | 0.177510E+09 |
April | 0.244318E+09 | 0.114224E+09 | 0.130095E+09 | 0.279463E+09 | 0.125489E+09 |
May | 0.209156E+09 | 56705164.61 | 0.152451E+09 | 0.256530E+09 | 78978323.39 |
June | 0.196509E+09 | 40010314.16 | 0.156499E+09 | 0.261420E+09 | 54509084.64 |
July | 0.214952E+09 | 54162372.82 | 0.160790E+09 | 0.295964E+09 | 50778293.72 |
August | 0.242180E+09 | 86851594.76 | 0.155328E+09 | 0.337015E+09 | 61238355.20 |
September | 0.284004E+09 | 0.149647E+09 | 0.134357E+09 | 0.370867E+09 | 96161360.78 |
October | 0.306446E+09 | 0.192252E+09 | 0.114194E+09 | 0.356441E+09 | 0.139192E+09 |
November | 0.223754E+09 | 0.140074E+09 | 83679834.65 | 0.220504E+09 | 0.198734E+09 |
December | 0.246555E+09 | 0.186762E+09 | 59792482.78 | 0.243282E+09 | 0.294951E+09 |
Annual Sum or Average | 0.303948E+10 | 0.157040E+10 | 0.146907E+10 | 0.346550E+10 | 0.182232E+10 |
Minimum of Months | 0.196509E+09 | 40010314.16 | 59792482.78 | 0.220504E+09 | 50778293.72 |
Maximum of Months | 0.306446E+09 | 0.205659E+09 | 0.160790E+09 | 0.370867E+09 | 0.316729E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.300530E+09 | 0.205659E+09 | 94870799.55 | 0.276294E+09 | 0.316729E+09 |
February | 0.290850E+09 | 0.196501E+09 | 94349415.32 | 0.280196E+09 | 0.228045E+09 |
March | 0.280223E+09 | 0.147556E+09 | 0.132667E+09 | 0.287522E+09 | 0.177510E+09 |
April | 0.244318E+09 | 0.114224E+09 | 0.130095E+09 | 0.279463E+09 | 0.125489E+09 |
May | 0.209156E+09 | 56705164.61 | 0.152451E+09 | 0.256530E+09 | 78978323.39 |
June | 0.196509E+09 | 40010314.16 | 0.156499E+09 | 0.261420E+09 | 54509084.64 |
July | 0.214952E+09 | 54162372.82 | 0.160790E+09 | 0.295964E+09 | 50778293.72 |
August | 0.242180E+09 | 86851594.76 | 0.155328E+09 | 0.337015E+09 | 61238355.20 |
September | 0.284004E+09 | 0.149647E+09 | 0.134357E+09 | 0.370867E+09 | 96161360.78 |
October | 0.306446E+09 | 0.192252E+09 | 0.114194E+09 | 0.356441E+09 | 0.139192E+09 |
November | 0.223754E+09 | 0.140074E+09 | 83679834.65 | 0.220504E+09 | 0.198734E+09 |
December | 0.246555E+09 | 0.186762E+09 | 59792482.78 | 0.243282E+09 | 0.294951E+09 |
Annual Sum or Average | 0.303948E+10 | 0.157040E+10 | 0.146907E+10 | 0.346550E+10 | 0.182232E+10 |
Minimum of Months | 0.196509E+09 | 40010314.16 | 59792482.78 | 0.220504E+09 | 50778293.72 |
Maximum of Months | 0.306446E+09 | 0.205659E+09 | 0.160790E+09 | 0.370867E+09 | 0.316729E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.359309E+09 | 0.245883E+09 | 0.113426E+09 | 0.332222E+09 | 0.373450E+09 |
February | 0.347736E+09 | 0.234933E+09 | 0.112803E+09 | 0.336744E+09 | 0.268950E+09 |
March | 0.335030E+09 | 0.176416E+09 | 0.158614E+09 | 0.345433E+09 | 0.209374E+09 |
April | 0.292103E+09 | 0.136564E+09 | 0.155539E+09 | 0.334996E+09 | 0.148200E+09 |
May | 0.250064E+09 | 67795833.10 | 0.182268E+09 | 0.307355E+09 | 93562932.70 |
June | 0.234943E+09 | 47835723.60 | 0.187107E+09 | 0.312635E+09 | 64763365.64 |
July | 0.256994E+09 | 64755709.87 | 0.192238E+09 | 0.353806E+09 | 60448561.09 |
August | 0.289547E+09 | 0.103838E+09 | 0.185708E+09 | 0.403082E+09 | 72723362.62 |
September | 0.339551E+09 | 0.178916E+09 | 0.160636E+09 | 0.443739E+09 | 0.114119E+09 |
October | 0.366382E+09 | 0.229853E+09 | 0.136529E+09 | 0.427254E+09 | 0.164709E+09 |
November | 0.267517E+09 | 0.167471E+09 | 0.100046E+09 | 0.264872E+09 | 0.234347E+09 |
December | 0.294777E+09 | 0.223290E+09 | 71486983.78 | 0.292018E+09 | 0.347846E+09 |
Annual Sum or Average | 0.363395E+10 | 0.187755E+10 | 0.175640E+10 | 0.415416E+10 | 0.215249E+10 |
Minimum of Months | 0.234943E+09 | 47835723.60 | 71486983.78 | 0.264872E+09 | 60448561.09 |
Maximum of Months | 0.366382E+09 | 0.245883E+09 | 0.192238E+09 | 0.443739E+09 | 0.373450E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.300530E+09 | 0.205659E+09 | 94870799.55 | 0.276354E+09 | 0.316425E+09 |
February | 0.290850E+09 | 0.196501E+09 | 94349415.32 | 0.280289E+09 | 0.227674E+09 |
March | 0.280223E+09 | 0.147556E+09 | 0.132667E+09 | 0.287720E+09 | 0.176940E+09 |
April | 0.244318E+09 | 0.114224E+09 | 0.130095E+09 | 0.279751E+09 | 0.124763E+09 |
May | 0.209156E+09 | 56705164.61 | 0.152451E+09 | 0.257413E+09 | 77867469.29 |
June | 0.196509E+09 | 40010314.16 | 0.156499E+09 | 0.261783E+09 | 54049478.06 |
July | 0.214952E+09 | 54162372.82 | 0.160790E+09 | 0.296179E+09 | 50501033.02 |
August | 0.242180E+09 | 86851594.76 | 0.155328E+09 | 0.337188E+09 | 60961245.98 |
September | 0.284004E+09 | 0.149647E+09 | 0.134357E+09 | 0.371125E+09 | 95669106.57 |
October | 0.306446E+09 | 0.192252E+09 | 0.114194E+09 | 0.356716E+09 | 0.138569E+09 |
November | 0.223754E+09 | 0.140074E+09 | 83679834.65 | 0.220664E+09 | 0.198221E+09 |
December | 0.246555E+09 | 0.186762E+09 | 59792482.78 | 0.243358E+09 | 0.294550E+09 |
Annual Sum or Average | 0.303948E+10 | 0.157040E+10 | 0.146907E+10 | 0.346854E+10 | 0.181619E+10 |
Minimum of Months | 0.196509E+09 | 40010314.16 | 59792482.78 | 0.220664E+09 | 50501033.02 |
Maximum of Months | 0.306446E+09 | 0.205659E+09 | 0.160790E+09 | 0.371125E+09 | 0.316425E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.300530E+09 | 0.205659E+09 | 94870799.55 | 0.276354E+09 | 0.316425E+09 |
February | 0.290850E+09 | 0.196501E+09 | 94349415.32 | 0.280289E+09 | 0.227674E+09 |
March | 0.280223E+09 | 0.147556E+09 | 0.132667E+09 | 0.287720E+09 | 0.176940E+09 |
April | 0.244318E+09 | 0.114224E+09 | 0.130095E+09 | 0.279751E+09 | 0.124763E+09 |
May | 0.209156E+09 | 56705164.61 | 0.152451E+09 | 0.257413E+09 | 77867469.29 |
June | 0.196509E+09 | 40010314.16 | 0.156499E+09 | 0.261783E+09 | 54049478.06 |
July | 0.214952E+09 | 54162372.82 | 0.160790E+09 | 0.296179E+09 | 50501033.02 |
August | 0.242180E+09 | 86851594.76 | 0.155328E+09 | 0.337188E+09 | 60961245.98 |
September | 0.284004E+09 | 0.149647E+09 | 0.134357E+09 | 0.371125E+09 | 95669106.57 |
October | 0.306446E+09 | 0.192252E+09 | 0.114194E+09 | 0.356716E+09 | 0.138569E+09 |
November | 0.223754E+09 | 0.140074E+09 | 83679834.65 | 0.220664E+09 | 0.198221E+09 |
December | 0.246555E+09 | 0.186762E+09 | 59792482.78 | 0.243358E+09 | 0.294550E+09 |
Annual Sum or Average | 0.303948E+10 | 0.157040E+10 | 0.146907E+10 | 0.346854E+10 | 0.181619E+10 |
Minimum of Months | 0.196509E+09 | 40010314.16 | 59792482.78 | 0.220664E+09 | 50501033.02 |
Maximum of Months | 0.306446E+09 | 0.205659E+09 | 0.160790E+09 | 0.371125E+09 | 0.316425E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.359309E+09 | 0.245883E+09 | 0.113426E+09 | 0.332294E+09 | 0.373088E+09 |
February | 0.347736E+09 | 0.234933E+09 | 0.112803E+09 | 0.336857E+09 | 0.268511E+09 |
March | 0.335030E+09 | 0.176416E+09 | 0.158614E+09 | 0.345673E+09 | 0.208701E+09 |
April | 0.292103E+09 | 0.136564E+09 | 0.155539E+09 | 0.335342E+09 | 0.147340E+09 |
May | 0.250064E+09 | 67795833.10 | 0.182268E+09 | 0.308408E+09 | 92251721.02 |
June | 0.234943E+09 | 47835723.60 | 0.187107E+09 | 0.313069E+09 | 64220405.27 |
July | 0.256994E+09 | 64755709.87 | 0.192238E+09 | 0.354064E+09 | 60120507.93 |
August | 0.289547E+09 | 0.103838E+09 | 0.185708E+09 | 0.403291E+09 | 72396333.42 |
September | 0.339551E+09 | 0.178916E+09 | 0.160636E+09 | 0.444048E+09 | 0.113537E+09 |
October | 0.366382E+09 | 0.229853E+09 | 0.136529E+09 | 0.427585E+09 | 0.163973E+09 |
November | 0.267517E+09 | 0.167471E+09 | 0.100046E+09 | 0.265065E+09 | 0.233739E+09 |
December | 0.294777E+09 | 0.223290E+09 | 71486983.78 | 0.292109E+09 | 0.347369E+09 |
Annual Sum or Average | 0.363395E+10 | 0.187755E+10 | 0.175640E+10 | 0.415780E+10 | 0.214525E+10 |
Minimum of Months | 0.234943E+09 | 47835723.60 | 71486983.78 | 0.265065E+09 | 60120507.93 |
Maximum of Months | 0.366382E+09 | 0.245883E+09 | 0.192238E+09 | 0.444048E+09 | 0.373088E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.300530E+09 | 0.205659E+09 | 94870799.55 | 0.276696E+09 | 0.314323E+09 |
February | 0.290850E+09 | 0.196501E+09 | 94349415.32 | 0.280746E+09 | 0.225572E+09 |
March | 0.280223E+09 | 0.147556E+09 | 0.132667E+09 | 0.288482E+09 | 0.174264E+09 |
April | 0.244318E+09 | 0.114224E+09 | 0.130095E+09 | 0.280657E+09 | 0.122006E+09 |
May | 0.209156E+09 | 56705164.61 | 0.152451E+09 | 0.259389E+09 | 75169847.58 |
June | 0.196509E+09 | 40010314.16 | 0.156499E+09 | 0.262652E+09 | 52802543.99 |
July | 0.214952E+09 | 54162372.82 | 0.160790E+09 | 0.296659E+09 | 49756538.81 |
August | 0.242180E+09 | 86851594.76 | 0.155328E+09 | 0.337555E+09 | 60232296.13 |
September | 0.284004E+09 | 0.149647E+09 | 0.134357E+09 | 0.371725E+09 | 94364240.57 |
October | 0.306446E+09 | 0.192252E+09 | 0.114194E+09 | 0.357469E+09 | 0.136578E+09 |
November | 0.223754E+09 | 0.140074E+09 | 83679834.65 | 0.221205E+09 | 0.196069E+09 |
December | 0.246555E+09 | 0.186762E+09 | 59792482.78 | 0.243714E+09 | 0.292138E+09 |
Annual Sum or Average | 0.303948E+10 | 0.157040E+10 | 0.146907E+10 | 0.347695E+10 | 0.179328E+10 |
Minimum of Months | 0.196509E+09 | 40010314.16 | 59792482.78 | 0.221205E+09 | 49756538.81 |
Maximum of Months | 0.306446E+09 | 0.205659E+09 | 0.160790E+09 | 0.371725E+09 | 0.314323E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.300530E+09 | 0.205659E+09 | 94870799.55 | 0.276696E+09 | 0.314323E+09 |
February | 0.290850E+09 | 0.196501E+09 | 94349415.32 | 0.280746E+09 | 0.225572E+09 |
March | 0.280223E+09 | 0.147556E+09 | 0.132667E+09 | 0.288482E+09 | 0.174264E+09 |
April | 0.244318E+09 | 0.114224E+09 | 0.130095E+09 | 0.280657E+09 | 0.122006E+09 |
May | 0.209156E+09 | 56705164.61 | 0.152451E+09 | 0.259389E+09 | 75169847.58 |
June | 0.196509E+09 | 40010314.16 | 0.156499E+09 | 0.262652E+09 | 52802543.99 |
July | 0.214952E+09 | 54162372.82 | 0.160790E+09 | 0.296659E+09 | 49756538.81 |
August | 0.242180E+09 | 86851594.76 | 0.155328E+09 | 0.337555E+09 | 60232296.13 |
September | 0.284004E+09 | 0.149647E+09 | 0.134357E+09 | 0.371725E+09 | 94364240.57 |
October | 0.306446E+09 | 0.192252E+09 | 0.114194E+09 | 0.357469E+09 | 0.136578E+09 |
November | 0.223754E+09 | 0.140074E+09 | 83679834.65 | 0.221205E+09 | 0.196069E+09 |
December | 0.246555E+09 | 0.186762E+09 | 59792482.78 | 0.243714E+09 | 0.292138E+09 |
Annual Sum or Average | 0.303948E+10 | 0.157040E+10 | 0.146907E+10 | 0.347695E+10 | 0.179328E+10 |
Minimum of Months | 0.196509E+09 | 40010314.16 | 59792482.78 | 0.221205E+09 | 49756538.81 |
Maximum of Months | 0.306446E+09 | 0.205659E+09 | 0.160790E+09 | 0.371725E+09 | 0.314323E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.359309E+09 | 0.245883E+09 | 0.113426E+09 | 0.332709E+09 | 0.370590E+09 |
February | 0.347736E+09 | 0.234933E+09 | 0.112803E+09 | 0.337414E+09 | 0.266023E+09 |
March | 0.335030E+09 | 0.176416E+09 | 0.158614E+09 | 0.346599E+09 | 0.205542E+09 |
April | 0.292103E+09 | 0.136564E+09 | 0.155539E+09 | 0.336434E+09 | 0.144085E+09 |
May | 0.250064E+09 | 67795833.10 | 0.182268E+09 | 0.310763E+09 | 89074991.68 |
June | 0.234943E+09 | 47835723.60 | 0.187107E+09 | 0.314108E+09 | 62753005.49 |
July | 0.256994E+09 | 64755709.87 | 0.192238E+09 | 0.354638E+09 | 59245933.56 |
August | 0.289547E+09 | 0.103838E+09 | 0.185708E+09 | 0.403731E+09 | 71540367.15 |
September | 0.339551E+09 | 0.178916E+09 | 0.160636E+09 | 0.444766E+09 | 0.112001E+09 |
October | 0.366382E+09 | 0.229853E+09 | 0.136529E+09 | 0.428490E+09 | 0.161625E+09 |
November | 0.267517E+09 | 0.167471E+09 | 0.100046E+09 | 0.265719E+09 | 0.231196E+09 |
December | 0.294777E+09 | 0.223290E+09 | 71486983.78 | 0.292541E+09 | 0.344507E+09 |
Annual Sum or Average | 0.363395E+10 | 0.187755E+10 | 0.175640E+10 | 0.416791E+10 | 0.211818E+10 |
Minimum of Months | 0.234943E+09 | 47835723.60 | 71486983.78 | 0.265719E+09 | 59245933.56 |
Maximum of Months | 0.366382E+09 | 0.245883E+09 | 0.192238E+09 | 0.444766E+09 | 0.370590E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.300530E+09 | 0.205659E+09 | 94870799.55 | 0.278628E+09 | 0.304081E+09 |
February | 0.290850E+09 | 0.196501E+09 | 94349415.32 | 0.283009E+09 | 0.215447E+09 |
March | 0.280223E+09 | 0.147556E+09 | 0.132667E+09 | 0.291444E+09 | 0.162704E+09 |
April | 0.244318E+09 | 0.114224E+09 | 0.130095E+09 | 0.283576E+09 | 0.111088E+09 |
May | 0.209156E+09 | 56705164.61 | 0.152451E+09 | 0.263655E+09 | 67423787.09 |
June | 0.196509E+09 | 40010314.16 | 0.156499E+09 | 0.264821E+09 | 48462081.67 |
July | 0.214952E+09 | 54162372.82 | 0.160790E+09 | 0.297816E+09 | 46893905.41 |
August | 0.242180E+09 | 86851594.76 | 0.155328E+09 | 0.338332E+09 | 57362536.75 |
September | 0.284004E+09 | 0.149647E+09 | 0.134357E+09 | 0.372954E+09 | 89885417.03 |
October | 0.306446E+09 | 0.192252E+09 | 0.114194E+09 | 0.359557E+09 | 0.129294E+09 |
November | 0.223754E+09 | 0.140074E+09 | 83679834.65 | 0.223166E+09 | 0.186950E+09 |
December | 0.246555E+09 | 0.186762E+09 | 59792482.78 | 0.245323E+09 | 0.280585E+09 |
Annual Sum or Average | 0.303948E+10 | 0.157040E+10 | 0.146907E+10 | 0.350228E+10 | 0.170018E+10 |
Minimum of Months | 0.196509E+09 | 40010314.16 | 59792482.78 | 0.223166E+09 | 46893905.41 |
Maximum of Months | 0.306446E+09 | 0.205659E+09 | 0.160790E+09 | 0.372954E+09 | 0.304081E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.300530E+09 | 0.205659E+09 | 94870799.55 | 0.278628E+09 | 0.304081E+09 |
February | 0.290850E+09 | 0.196501E+09 | 94349415.32 | 0.283009E+09 | 0.215447E+09 |
March | 0.280223E+09 | 0.147556E+09 | 0.132667E+09 | 0.291444E+09 | 0.162704E+09 |
April | 0.244318E+09 | 0.114224E+09 | 0.130095E+09 | 0.283576E+09 | 0.111088E+09 |
May | 0.209156E+09 | 56705164.61 | 0.152451E+09 | 0.263655E+09 | 67423787.09 |
June | 0.196509E+09 | 40010314.16 | 0.156499E+09 | 0.264821E+09 | 48462081.67 |
July | 0.214952E+09 | 54162372.82 | 0.160790E+09 | 0.297816E+09 | 46893905.41 |
August | 0.242180E+09 | 86851594.76 | 0.155328E+09 | 0.338332E+09 | 57362536.75 |
September | 0.284004E+09 | 0.149647E+09 | 0.134357E+09 | 0.372954E+09 | 89885417.03 |
October | 0.306446E+09 | 0.192252E+09 | 0.114194E+09 | 0.359557E+09 | 0.129294E+09 |
November | 0.223754E+09 | 0.140074E+09 | 83679834.65 | 0.223166E+09 | 0.186950E+09 |
December | 0.246555E+09 | 0.186762E+09 | 59792482.78 | 0.245323E+09 | 0.280585E+09 |
Annual Sum or Average | 0.303948E+10 | 0.157040E+10 | 0.146907E+10 | 0.350228E+10 | 0.170018E+10 |
Minimum of Months | 0.196509E+09 | 40010314.16 | 59792482.78 | 0.223166E+09 | 46893905.41 |
Maximum of Months | 0.306446E+09 | 0.205659E+09 | 0.160790E+09 | 0.372954E+09 | 0.304081E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.359309E+09 | 0.245883E+09 | 0.113426E+09 | 0.335052E+09 | 0.358368E+09 |
February | 0.347736E+09 | 0.234933E+09 | 0.112803E+09 | 0.340163E+09 | 0.254007E+09 |
March | 0.335030E+09 | 0.176416E+09 | 0.158614E+09 | 0.350192E+09 | 0.191891E+09 |
April | 0.292103E+09 | 0.136564E+09 | 0.155539E+09 | 0.339963E+09 | 0.131205E+09 |
May | 0.250064E+09 | 67795833.10 | 0.182268E+09 | 0.315860E+09 | 79951399.34 |
June | 0.234943E+09 | 47835723.60 | 0.187107E+09 | 0.316702E+09 | 57639581.80 |
July | 0.256994E+09 | 64755709.87 | 0.192238E+09 | 0.356017E+09 | 55874422.97 |
August | 0.289547E+09 | 0.103838E+09 | 0.185708E+09 | 0.404657E+09 | 68171962.28 |
September | 0.339551E+09 | 0.178916E+09 | 0.160636E+09 | 0.446235E+09 | 0.106732E+09 |
October | 0.366382E+09 | 0.229853E+09 | 0.136529E+09 | 0.431005E+09 | 0.153051E+09 |
November | 0.267517E+09 | 0.167471E+09 | 0.100046E+09 | 0.268090E+09 | 0.220423E+09 |
December | 0.294777E+09 | 0.223290E+09 | 71486983.78 | 0.294494E+09 | 0.330793E+09 |
Annual Sum or Average | 0.363395E+10 | 0.187755E+10 | 0.175640E+10 | 0.419843E+10 | 0.200811E+10 |
Minimum of Months | 0.234943E+09 | 47835723.60 | 71486983.78 | 0.268090E+09 | 55874422.97 |
Maximum of Months | 0.366382E+09 | 0.245883E+09 | 0.192238E+09 | 0.446235E+09 | 0.358368E+09 |
Report: WindowZoneSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 664.53 | 766.28 | 718.60 | 491.75 | 226.85 | 0.00 | 0.00 |
February | 745.80 | 610.37 | 769.96 | 520.19 | 249.77 | 0.00 | 0.00 |
March | 691.53 | 427.67 | 670.04 | 352.82 | 317.22 | 0.00 | 0.00 |
April | 693.01 | 311.75 | 603.66 | 282.22 | 321.44 | 0.00 | 0.00 |
May | 612.64 | 192.98 | 500.11 | 135.59 | 364.53 | 0.00 | 0.00 |
June | 648.34 | 133.15 | 485.53 | 98.86 | 386.68 | 0.00 | 0.00 |
July | 710.64 | 118.32 | 513.97 | 129.51 | 384.46 | 0.00 | 0.00 |
August | 807.94 | 143.72 | 579.08 | 207.67 | 371.41 | 0.00 | 0.00 |
September | 918.19 | 235.70 | 701.72 | 369.75 | 331.97 | 0.00 | 0.00 |
October | 852.29 | 338.57 | 732.74 | 459.69 | 273.05 | 0.00 | 0.00 |
November | 546.10 | 498.10 | 552.85 | 346.10 | 206.76 | 0.00 | 0.00 |
December | 583.78 | 710.77 | 589.54 | 446.57 | 142.97 | 0.00 | 0.00 |
Annual Sum or Average | 705.96 | 372.88 | 617.25 | 318.92 | 298.34 | 0.00 | 0.00 |
Minimum of Months | 546.10 | 118.32 | 485.53 | 98.86 | 142.97 | 0.00 | 0.00 |
Maximum of Months | 918.19 | 766.28 | 769.96 | 520.19 | 386.68 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 328.90 | 395.10 | 359.30 | 245.88 | 113.42 | 0.00 | 0.00 |
February | 368.92 | 317.02 | 384.98 | 260.10 | 124.88 | 0.00 | 0.00 |
March | 341.24 | 226.17 | 335.02 | 176.41 | 158.61 | 0.00 | 0.00 |
April | 342.49 | 167.65 | 301.83 | 141.11 | 160.72 | 0.00 | 0.00 |
May | 300.59 | 104.52 | 250.06 | 67.79 | 182.26 | 0.00 | 0.00 |
June | 321.63 | 70.27 | 242.77 | 49.43 | 193.34 | 0.00 | 0.00 |
July | 354.42 | 60.29 | 256.99 | 64.75 | 192.23 | 0.00 | 0.00 |
August | 403.13 | 73.26 | 289.54 | 103.84 | 185.70 | 0.00 | 0.00 |
September | 456.80 | 122.66 | 350.86 | 184.87 | 165.98 | 0.00 | 0.00 |
October | 422.12 | 180.06 | 366.37 | 229.85 | 136.52 | 0.00 | 0.00 |
November | 269.57 | 261.15 | 276.43 | 173.05 | 103.38 | 0.00 | 0.00 |
December | 289.37 | 367.99 | 294.77 | 223.28 | 71.48 | 0.00 | 0.00 |
Annual Sum or Average | 349.80 | 194.95 | 308.63 | 159.46 | 149.17 | 0.00 | 0.00 |
Minimum of Months | 269.57 | 60.29 | 242.77 | 49.43 | 71.48 | 0.00 | 0.00 |
Maximum of Months | 456.80 | 395.10 | 384.98 | 260.10 | 193.34 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 328.67 | 386.84 | 358.56 | 245.37 | 113.19 | 0.00 | 0.00 |
February | 368.64 | 309.73 | 384.19 | 259.56 | 124.63 | 0.00 | 0.00 |
March | 341.09 | 220.76 | 334.33 | 176.05 | 158.28 | 0.00 | 0.00 |
April | 342.20 | 163.56 | 301.21 | 140.82 | 160.39 | 0.00 | 0.00 |
May | 300.43 | 103.86 | 249.54 | 67.65 | 181.89 | 0.00 | 0.00 |
June | 320.30 | 72.49 | 242.27 | 49.33 | 192.94 | 0.00 | 0.00 |
July | 352.49 | 64.22 | 256.46 | 64.62 | 191.84 | 0.00 | 0.00 |
August | 401.81 | 76.88 | 288.94 | 103.62 | 185.32 | 0.00 | 0.00 |
September | 455.89 | 124.23 | 350.14 | 184.49 | 165.64 | 0.00 | 0.00 |
October | 422.69 | 174.63 | 365.62 | 229.37 | 136.24 | 0.00 | 0.00 |
November | 269.89 | 254.43 | 275.86 | 172.69 | 103.17 | 0.00 | 0.00 |
December | 289.16 | 360.73 | 294.16 | 222.83 | 71.34 | 0.00 | 0.00 |
Annual Sum or Average | 349.31 | 192.16 | 307.99 | 159.13 | 148.86 | 0.00 | 0.00 |
Minimum of Months | 269.89 | 64.22 | 242.27 | 49.33 | 71.34 | 0.00 | 0.00 |
Maximum of Months | 455.89 | 386.84 | 384.19 | 259.56 | 192.94 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 328.99 | 384.01 | 358.56 | 245.37 | 113.19 | 0.00 | 0.00 |
February | 369.04 | 307.13 | 384.19 | 259.56 | 124.63 | 0.00 | 0.00 |
March | 341.60 | 218.44 | 334.33 | 176.05 | 158.28 | 0.00 | 0.00 |
April | 342.72 | 161.45 | 301.21 | 140.82 | 160.39 | 0.00 | 0.00 |
May | 301.38 | 102.16 | 249.54 | 67.65 | 181.89 | 0.00 | 0.00 |
June | 320.59 | 71.96 | 242.27 | 49.33 | 192.94 | 0.00 | 0.00 |
July | 352.50 | 64.23 | 256.46 | 64.62 | 191.84 | 0.00 | 0.00 |
August | 401.86 | 76.77 | 288.94 | 103.62 | 185.32 | 0.00 | 0.00 |
September | 456.18 | 123.44 | 350.14 | 184.49 | 165.64 | 0.00 | 0.00 |
October | 423.51 | 172.10 | 365.62 | 229.37 | 136.24 | 0.00 | 0.00 |
November | 270.46 | 251.61 | 275.86 | 172.69 | 103.17 | 0.00 | 0.00 |
December | 289.44 | 358.08 | 294.16 | 222.83 | 71.34 | 0.00 | 0.00 |
Annual Sum or Average | 349.72 | 190.42 | 307.99 | 159.13 | 148.86 | 0.00 | 0.00 |
Minimum of Months | 270.46 | 64.23 | 242.27 | 49.33 | 71.34 | 0.00 | 0.00 |
Maximum of Months | 456.18 | 384.01 | 384.19 | 259.56 | 192.94 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 329.42 | 381.83 | 358.56 | 245.37 | 113.19 | 0.00 | 0.00 |
February | 369.56 | 305.05 | 384.19 | 259.56 | 124.63 | 0.00 | 0.00 |
March | 342.30 | 216.33 | 334.33 | 176.05 | 158.28 | 0.00 | 0.00 |
April | 343.48 | 159.35 | 301.21 | 140.82 | 160.39 | 0.00 | 0.00 |
May | 303.07 | 99.80 | 249.54 | 67.65 | 181.89 | 0.00 | 0.00 |
June | 321.35 | 70.74 | 242.27 | 49.33 | 192.94 | 0.00 | 0.00 |
July | 352.91 | 63.44 | 256.46 | 64.62 | 191.84 | 0.00 | 0.00 |
August | 402.21 | 75.95 | 288.94 | 103.62 | 185.32 | 0.00 | 0.00 |
September | 456.81 | 122.04 | 350.14 | 184.49 | 165.64 | 0.00 | 0.00 |
October | 424.38 | 170.02 | 365.62 | 229.37 | 136.24 | 0.00 | 0.00 |
November | 271.12 | 249.22 | 275.86 | 172.69 | 103.17 | 0.00 | 0.00 |
December | 289.81 | 355.86 | 294.16 | 222.83 | 71.34 | 0.00 | 0.00 |
Annual Sum or Average | 350.40 | 188.61 | 307.99 | 159.13 | 148.86 | 0.00 | 0.00 |
Minimum of Months | 271.12 | 63.44 | 242.27 | 49.33 | 71.34 | 0.00 | 0.00 |
Maximum of Months | 456.81 | 381.83 | 384.19 | 259.56 | 192.94 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 663.49 | 746.65 | 717.12 | 490.74 | 226.38 | 0.00 | 0.00 |
February | 744.57 | 595.64 | 768.38 | 519.13 | 249.26 | 0.00 | 0.00 |
March | 689.77 | 419.25 | 668.67 | 352.10 | 316.57 | 0.00 | 0.00 |
April | 691.07 | 307.44 | 602.42 | 281.64 | 320.78 | 0.00 | 0.00 |
May | 612.18 | 189.54 | 499.09 | 135.31 | 363.78 | 0.00 | 0.00 |
June | 644.39 | 135.43 | 484.54 | 98.65 | 385.88 | 0.00 | 0.00 |
July | 706.03 | 122.28 | 512.92 | 129.24 | 383.68 | 0.00 | 0.00 |
August | 804.63 | 146.96 | 577.89 | 207.24 | 370.64 | 0.00 | 0.00 |
September | 915.31 | 237.57 | 700.28 | 368.99 | 331.29 | 0.00 | 0.00 |
October | 852.84 | 330.94 | 731.24 | 458.75 | 272.49 | 0.00 | 0.00 |
November | 546.39 | 485.02 | 551.72 | 345.39 | 206.33 | 0.00 | 0.00 |
December | 583.23 | 695.49 | 588.33 | 445.65 | 142.68 | 0.00 | 0.00 |
Annual Sum or Average | 704.22 | 366.65 | 615.99 | 318.26 | 297.73 | 0.00 | 0.00 |
Minimum of Months | 546.39 | 122.28 | 484.54 | 98.65 | 142.68 | 0.00 | 0.00 |
Maximum of Months | 915.31 | 746.65 | 768.38 | 519.13 | 385.88 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 330.35 | 375.94 | 358.56 | 245.37 | 113.19 | 0.00 | 0.00 |
February | 370.84 | 299.70 | 384.19 | 259.56 | 124.63 | 0.00 | 0.00 |
March | 343.66 | 210.72 | 334.33 | 176.05 | 158.28 | 0.00 | 0.00 |
April | 344.88 | 154.00 | 301.21 | 140.82 | 160.39 | 0.00 | 0.00 |
May | 306.31 | 93.91 | 249.54 | 67.65 | 181.89 | 0.00 | 0.00 |
June | 322.33 | 67.05 | 242.27 | 49.33 | 192.94 | 0.00 | 0.00 |
July | 353.10 | 60.49 | 256.46 | 64.62 | 191.84 | 0.00 | 0.00 |
August | 402.15 | 72.88 | 288.94 | 103.62 | 185.32 | 0.00 | 0.00 |
September | 457.36 | 118.23 | 350.14 | 184.49 | 165.64 | 0.00 | 0.00 |
October | 425.68 | 165.43 | 365.62 | 229.37 | 136.24 | 0.00 | 0.00 |
November | 272.33 | 243.76 | 275.86 | 172.69 | 103.17 | 0.00 | 0.00 |
December | 290.69 | 350.11 | 294.16 | 222.83 | 71.34 | 0.00 | 0.00 |
Annual Sum or Average | 351.51 | 183.83 | 307.99 | 159.13 | 148.86 | 0.00 | 0.00 |
Minimum of Months | 272.33 | 60.49 | 242.27 | 49.33 | 71.34 | 0.00 | 0.00 |
Maximum of Months | 457.36 | 375.94 | 384.19 | 259.56 | 192.94 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 330.42 | 375.57 | 358.56 | 245.37 | 113.19 | 0.00 | 0.00 |
February | 370.96 | 299.21 | 384.19 | 259.56 | 124.63 | 0.00 | 0.00 |
March | 343.90 | 210.04 | 334.33 | 176.05 | 158.28 | 0.00 | 0.00 |
April | 345.23 | 153.11 | 301.21 | 140.82 | 160.39 | 0.00 | 0.00 |
May | 307.36 | 92.59 | 249.54 | 67.65 | 181.89 | 0.00 | 0.00 |
June | 322.78 | 66.48 | 242.27 | 49.33 | 192.94 | 0.00 | 0.00 |
July | 353.35 | 60.16 | 256.46 | 64.62 | 191.84 | 0.00 | 0.00 |
August | 402.35 | 72.55 | 288.94 | 103.62 | 185.32 | 0.00 | 0.00 |
September | 457.68 | 117.62 | 350.14 | 184.49 | 165.64 | 0.00 | 0.00 |
October | 426.01 | 164.69 | 365.62 | 229.37 | 136.24 | 0.00 | 0.00 |
November | 272.53 | 243.12 | 275.86 | 172.69 | 103.17 | 0.00 | 0.00 |
December | 290.78 | 349.64 | 294.16 | 222.83 | 71.34 | 0.00 | 0.00 |
Annual Sum or Average | 351.82 | 183.21 | 307.99 | 159.13 | 148.86 | 0.00 | 0.00 |
Minimum of Months | 272.53 | 60.16 | 242.27 | 49.33 | 71.34 | 0.00 | 0.00 |
Maximum of Months | 457.68 | 375.57 | 384.19 | 259.56 | 192.94 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 330.83 | 373.07 | 358.56 | 245.37 | 113.19 | 0.00 | 0.00 |
February | 371.57 | 296.45 | 384.19 | 259.56 | 124.63 | 0.00 | 0.00 |
March | 344.82 | 206.86 | 334.33 | 176.05 | 158.28 | 0.00 | 0.00 |
April | 346.35 | 149.73 | 301.21 | 140.82 | 160.39 | 0.00 | 0.00 |
May | 309.72 | 89.39 | 249.54 | 67.65 | 181.89 | 0.00 | 0.00 |
June | 323.85 | 64.95 | 242.27 | 49.33 | 192.94 | 0.00 | 0.00 |
July | 353.93 | 59.27 | 256.46 | 64.62 | 191.84 | 0.00 | 0.00 |
August | 402.79 | 71.69 | 288.94 | 103.62 | 185.32 | 0.00 | 0.00 |
September | 458.42 | 116.02 | 350.14 | 184.49 | 165.64 | 0.00 | 0.00 |
October | 426.91 | 162.33 | 365.62 | 229.37 | 136.24 | 0.00 | 0.00 |
November | 273.20 | 240.48 | 275.86 | 172.69 | 103.17 | 0.00 | 0.00 |
December | 291.21 | 346.77 | 294.16 | 222.83 | 71.34 | 0.00 | 0.00 |
Annual Sum or Average | 352.67 | 180.90 | 307.99 | 159.13 | 148.86 | 0.00 | 0.00 |
Minimum of Months | 273.20 | 59.27 | 242.27 | 49.33 | 71.34 | 0.00 | 0.00 |
Maximum of Months | 458.42 | 373.07 | 384.19 | 259.56 | 192.94 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 333.15 | 360.86 | 358.56 | 245.37 | 113.19 | 0.00 | 0.00 |
February | 374.58 | 283.11 | 384.19 | 259.56 | 124.63 | 0.00 | 0.00 |
March | 348.37 | 193.14 | 334.33 | 176.05 | 158.28 | 0.00 | 0.00 |
April | 349.97 | 136.33 | 301.21 | 140.82 | 160.39 | 0.00 | 0.00 |
May | 314.80 | 80.20 | 249.54 | 67.65 | 181.89 | 0.00 | 0.00 |
June | 326.52 | 59.63 | 242.27 | 49.33 | 192.94 | 0.00 | 0.00 |
July | 355.31 | 55.88 | 256.46 | 64.62 | 191.84 | 0.00 | 0.00 |
August | 403.72 | 68.29 | 288.94 | 103.62 | 185.32 | 0.00 | 0.00 |
September | 459.93 | 110.53 | 350.14 | 184.49 | 165.64 | 0.00 | 0.00 |
October | 429.41 | 153.69 | 365.62 | 229.37 | 136.24 | 0.00 | 0.00 |
November | 275.62 | 229.29 | 275.86 | 172.69 | 103.17 | 0.00 | 0.00 |
December | 293.14 | 333.02 | 294.16 | 222.83 | 71.34 | 0.00 | 0.00 |
Annual Sum or Average | 355.24 | 171.50 | 307.99 | 159.13 | 148.86 | 0.00 | 0.00 |
Minimum of Months | 275.62 | 55.88 | 242.27 | 49.33 | 71.34 | 0.00 | 0.00 |
Maximum of Months | 459.93 | 360.86 | 384.19 | 259.56 | 192.94 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.177988E+10 | 0.205242E+10 | 0.192469E+10 | 0.131711E+10 | 0.607582E+09 | 0.00 | 0.00 |
February | 0.180423E+10 | 0.147660E+10 | 0.186269E+10 | 0.125845E+10 | 0.604243E+09 | 0.00 | 0.00 |
March | 0.185220E+10 | 0.114548E+10 | 0.179463E+10 | 0.944996E+09 | 0.849639E+09 | 0.00 | 0.00 |
April | 0.179628E+10 | 0.808059E+09 | 0.156469E+10 | 0.731524E+09 | 0.833167E+09 | 0.00 | 0.00 |
May | 0.164090E+10 | 0.516868E+09 | 0.133950E+10 | 0.363157E+09 | 0.976345E+09 | 0.00 | 0.00 |
June | 0.168050E+10 | 0.345138E+09 | 0.125850E+10 | 0.256238E+09 | 0.100226E+10 | 0.00 | 0.00 |
July | 0.190339E+10 | 0.316908E+09 | 0.137662E+10 | 0.346873E+09 | 0.102975E+10 | 0.00 | 0.00 |
August | 0.216398E+10 | 0.384950E+09 | 0.155100E+10 | 0.556224E+09 | 0.994771E+09 | 0.00 | 0.00 |
September | 0.237995E+10 | 0.610947E+09 | 0.181885E+10 | 0.958385E+09 | 0.860466E+09 | 0.00 | 0.00 |
October | 0.228276E+10 | 0.906833E+09 | 0.196257E+10 | 0.123124E+10 | 0.731334E+09 | 0.00 | 0.00 |
November | 0.141548E+10 | 0.129108E+10 | 0.143299E+10 | 0.897079E+09 | 0.535911E+09 | 0.00 | 0.00 |
December | 0.156360E+10 | 0.190373E+10 | 0.157901E+10 | 0.119608E+10 | 0.382929E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.222631E+11 | 0.117590E+11 | 0.194658E+11 | 0.100574E+11 | 0.940840E+10 | 0.00 | 0.00 |
Minimum of Months | 0.141548E+10 | 0.316908E+09 | 0.125850E+10 | 0.256238E+09 | 0.382929E+09 | 0.00 | 0.00 |
Maximum of Months | 0.237995E+10 | 0.205242E+10 | 0.196257E+10 | 0.131711E+10 | 0.102975E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.880930E+09 | 0.105823E+10 | 0.962343E+09 | 0.658553E+09 | 0.303791E+09 | 0.00 | 0.00 |
February | 0.892480E+09 | 0.766925E+09 | 0.931346E+09 | 0.629225E+09 | 0.302121E+09 | 0.00 | 0.00 |
March | 0.913979E+09 | 0.605776E+09 | 0.897317E+09 | 0.472498E+09 | 0.424820E+09 | 0.00 | 0.00 |
April | 0.887725E+09 | 0.434557E+09 | 0.782345E+09 | 0.365762E+09 | 0.416583E+09 | 0.00 | 0.00 |
May | 0.805090E+09 | 0.279939E+09 | 0.669751E+09 | 0.181579E+09 | 0.488173E+09 | 0.00 | 0.00 |
June | 0.833675E+09 | 0.182143E+09 | 0.629251E+09 | 0.128119E+09 | 0.501132E+09 | 0.00 | 0.00 |
July | 0.949275E+09 | 0.161485E+09 | 0.688311E+09 | 0.173436E+09 | 0.514875E+09 | 0.00 | 0.00 |
August | 0.107973E+10 | 0.196221E+09 | 0.775498E+09 | 0.278112E+09 | 0.497386E+09 | 0.00 | 0.00 |
September | 0.118403E+10 | 0.317944E+09 | 0.909425E+09 | 0.479193E+09 | 0.430233E+09 | 0.00 | 0.00 |
October | 0.113061E+10 | 0.482278E+09 | 0.981286E+09 | 0.615619E+09 | 0.365667E+09 | 0.00 | 0.00 |
November | 0.698729E+09 | 0.676902E+09 | 0.716495E+09 | 0.448540E+09 | 0.267956E+09 | 0.00 | 0.00 |
December | 0.775049E+09 | 0.985617E+09 | 0.789506E+09 | 0.598042E+09 | 0.191465E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.110313E+11 | 0.614802E+10 | 0.973288E+10 | 0.502868E+10 | 0.470420E+10 | 0.00 | 0.00 |
Minimum of Months | 0.698729E+09 | 0.161485E+09 | 0.629251E+09 | 0.128119E+09 | 0.191465E+09 | 0.00 | 0.00 |
Maximum of Months | 0.118403E+10 | 0.105823E+10 | 0.981286E+09 | 0.658553E+09 | 0.514875E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.880311E+09 | 0.103610E+10 | 0.960369E+09 | 0.657202E+09 | 0.303168E+09 | 0.00 | 0.00 |
February | 0.891805E+09 | 0.749289E+09 | 0.929436E+09 | 0.627934E+09 | 0.301502E+09 | 0.00 | 0.00 |
March | 0.913589E+09 | 0.591289E+09 | 0.895477E+09 | 0.471528E+09 | 0.423948E+09 | 0.00 | 0.00 |
April | 0.886977E+09 | 0.423942E+09 | 0.780740E+09 | 0.365011E+09 | 0.415729E+09 | 0.00 | 0.00 |
May | 0.804672E+09 | 0.278186E+09 | 0.668377E+09 | 0.181206E+09 | 0.487171E+09 | 0.00 | 0.00 |
June | 0.830217E+09 | 0.187888E+09 | 0.627961E+09 | 0.127856E+09 | 0.500104E+09 | 0.00 | 0.00 |
July | 0.944114E+09 | 0.172013E+09 | 0.686899E+09 | 0.173080E+09 | 0.513818E+09 | 0.00 | 0.00 |
August | 0.107621E+10 | 0.205903E+09 | 0.773907E+09 | 0.277542E+09 | 0.496365E+09 | 0.00 | 0.00 |
September | 0.118166E+10 | 0.321994E+09 | 0.907560E+09 | 0.478210E+09 | 0.429350E+09 | 0.00 | 0.00 |
October | 0.113214E+10 | 0.467718E+09 | 0.979273E+09 | 0.614356E+09 | 0.364917E+09 | 0.00 | 0.00 |
November | 0.699544E+09 | 0.659481E+09 | 0.715025E+09 | 0.447619E+09 | 0.267406E+09 | 0.00 | 0.00 |
December | 0.774486E+09 | 0.966167E+09 | 0.787887E+09 | 0.596815E+09 | 0.191072E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.110157E+11 | 0.605997E+10 | 0.971291E+10 | 0.501836E+10 | 0.469455E+10 | 0.00 | 0.00 |
Minimum of Months | 0.699544E+09 | 0.172013E+09 | 0.627961E+09 | 0.127856E+09 | 0.191072E+09 | 0.00 | 0.00 |
Maximum of Months | 0.118166E+10 | 0.103610E+10 | 0.979273E+09 | 0.657202E+09 | 0.513818E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.881176E+09 | 0.102854E+10 | 0.960369E+09 | 0.657202E+09 | 0.303168E+09 | 0.00 | 0.00 |
February | 0.892775E+09 | 0.743002E+09 | 0.929436E+09 | 0.627934E+09 | 0.301502E+09 | 0.00 | 0.00 |
March | 0.914928E+09 | 0.585070E+09 | 0.895477E+09 | 0.471528E+09 | 0.423948E+09 | 0.00 | 0.00 |
April | 0.888318E+09 | 0.418482E+09 | 0.780740E+09 | 0.365011E+09 | 0.415729E+09 | 0.00 | 0.00 |
May | 0.807205E+09 | 0.273639E+09 | 0.668377E+09 | 0.181206E+09 | 0.487171E+09 | 0.00 | 0.00 |
June | 0.830973E+09 | 0.186520E+09 | 0.627961E+09 | 0.127856E+09 | 0.500104E+09 | 0.00 | 0.00 |
July | 0.944138E+09 | 0.172029E+09 | 0.686899E+09 | 0.173080E+09 | 0.513818E+09 | 0.00 | 0.00 |
August | 0.107633E+10 | 0.205633E+09 | 0.773907E+09 | 0.277542E+09 | 0.496365E+09 | 0.00 | 0.00 |
September | 0.118241E+10 | 0.319969E+09 | 0.907560E+09 | 0.478210E+09 | 0.429350E+09 | 0.00 | 0.00 |
October | 0.113434E+10 | 0.460945E+09 | 0.979273E+09 | 0.614356E+09 | 0.364917E+09 | 0.00 | 0.00 |
November | 0.701041E+09 | 0.652163E+09 | 0.715025E+09 | 0.447619E+09 | 0.267406E+09 | 0.00 | 0.00 |
December | 0.775240E+09 | 0.959083E+09 | 0.787887E+09 | 0.596815E+09 | 0.191072E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.110289E+11 | 0.600508E+10 | 0.971291E+10 | 0.501836E+10 | 0.469455E+10 | 0.00 | 0.00 |
Minimum of Months | 0.701041E+09 | 0.172029E+09 | 0.627961E+09 | 0.127856E+09 | 0.191072E+09 | 0.00 | 0.00 |
Maximum of Months | 0.118241E+10 | 0.102854E+10 | 0.979273E+09 | 0.657202E+09 | 0.513818E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.882319E+09 | 0.102271E+10 | 0.960369E+09 | 0.657202E+09 | 0.303168E+09 | 0.00 | 0.00 |
February | 0.894051E+09 | 0.737980E+09 | 0.929436E+09 | 0.627934E+09 | 0.301502E+09 | 0.00 | 0.00 |
March | 0.916805E+09 | 0.579409E+09 | 0.895477E+09 | 0.471528E+09 | 0.423948E+09 | 0.00 | 0.00 |
April | 0.890302E+09 | 0.413039E+09 | 0.780740E+09 | 0.365011E+09 | 0.415729E+09 | 0.00 | 0.00 |
May | 0.811731E+09 | 0.267295E+09 | 0.668377E+09 | 0.181206E+09 | 0.487171E+09 | 0.00 | 0.00 |
June | 0.832939E+09 | 0.183347E+09 | 0.627961E+09 | 0.127856E+09 | 0.500104E+09 | 0.00 | 0.00 |
July | 0.945222E+09 | 0.169909E+09 | 0.686899E+09 | 0.173080E+09 | 0.513818E+09 | 0.00 | 0.00 |
August | 0.107727E+10 | 0.203413E+09 | 0.773907E+09 | 0.277542E+09 | 0.496365E+09 | 0.00 | 0.00 |
September | 0.118404E+10 | 0.316334E+09 | 0.907560E+09 | 0.478210E+09 | 0.429350E+09 | 0.00 | 0.00 |
October | 0.113667E+10 | 0.455383E+09 | 0.979273E+09 | 0.614356E+09 | 0.364917E+09 | 0.00 | 0.00 |
November | 0.702747E+09 | 0.645968E+09 | 0.715025E+09 | 0.447619E+09 | 0.267406E+09 | 0.00 | 0.00 |
December | 0.776235E+09 | 0.953141E+09 | 0.787887E+09 | 0.596815E+09 | 0.191072E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.110503E+11 | 0.594792E+10 | 0.971291E+10 | 0.501836E+10 | 0.469455E+10 | 0.00 | 0.00 |
Minimum of Months | 0.702747E+09 | 0.169909E+09 | 0.627961E+09 | 0.127856E+09 | 0.191072E+09 | 0.00 | 0.00 |
Maximum of Months | 0.118404E+10 | 0.102271E+10 | 0.979273E+09 | 0.657202E+09 | 0.513818E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.177708E+10 | 0.199983E+10 | 0.192074E+10 | 0.131440E+10 | 0.606335E+09 | 0.00 | 0.00 |
February | 0.180127E+10 | 0.144097E+10 | 0.185887E+10 | 0.125587E+10 | 0.603003E+09 | 0.00 | 0.00 |
March | 0.184749E+10 | 0.112292E+10 | 0.179095E+10 | 0.943057E+09 | 0.847896E+09 | 0.00 | 0.00 |
April | 0.179125E+10 | 0.796876E+09 | 0.156148E+10 | 0.730023E+09 | 0.831457E+09 | 0.00 | 0.00 |
May | 0.163967E+10 | 0.507657E+09 | 0.133675E+10 | 0.362412E+09 | 0.974342E+09 | 0.00 | 0.00 |
June | 0.167027E+10 | 0.351028E+09 | 0.125592E+10 | 0.255713E+09 | 0.100021E+10 | 0.00 | 0.00 |
July | 0.189103E+10 | 0.327528E+09 | 0.137380E+10 | 0.346161E+09 | 0.102764E+10 | 0.00 | 0.00 |
August | 0.215512E+10 | 0.393625E+09 | 0.154781E+10 | 0.555083E+09 | 0.992731E+09 | 0.00 | 0.00 |
September | 0.237247E+10 | 0.615777E+09 | 0.181512E+10 | 0.956419E+09 | 0.858701E+09 | 0.00 | 0.00 |
October | 0.228425E+10 | 0.886398E+09 | 0.195855E+10 | 0.122871E+10 | 0.729834E+09 | 0.00 | 0.00 |
November | 0.141624E+10 | 0.125718E+10 | 0.143005E+10 | 0.895239E+09 | 0.534812E+09 | 0.00 | 0.00 |
December | 0.156213E+10 | 0.186279E+10 | 0.157577E+10 | 0.119363E+10 | 0.382144E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.222083E+11 | 0.115626E+11 | 0.194258E+11 | 0.100367E+11 | 0.938910E+10 | 0.00 | 0.00 |
Minimum of Months | 0.141624E+10 | 0.327528E+09 | 0.125592E+10 | 0.255713E+09 | 0.382144E+09 | 0.00 | 0.00 |
Maximum of Months | 0.237247E+10 | 0.199983E+10 | 0.195855E+10 | 0.131440E+10 | 0.102764E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.884808E+09 | 0.100691E+10 | 0.960369E+09 | 0.657202E+09 | 0.303168E+09 | 0.00 | 0.00 |
February | 0.897132E+09 | 0.725036E+09 | 0.929436E+09 | 0.627934E+09 | 0.301502E+09 | 0.00 | 0.00 |
March | 0.920472E+09 | 0.564390E+09 | 0.895477E+09 | 0.471528E+09 | 0.423948E+09 | 0.00 | 0.00 |
April | 0.893920E+09 | 0.399176E+09 | 0.780740E+09 | 0.365011E+09 | 0.415729E+09 | 0.00 | 0.00 |
May | 0.820415E+09 | 0.251519E+09 | 0.668377E+09 | 0.181206E+09 | 0.487171E+09 | 0.00 | 0.00 |
June | 0.835475E+09 | 0.173781E+09 | 0.627961E+09 | 0.127856E+09 | 0.500104E+09 | 0.00 | 0.00 |
July | 0.945735E+09 | 0.162005E+09 | 0.686899E+09 | 0.173080E+09 | 0.513818E+09 | 0.00 | 0.00 |
August | 0.107711E+10 | 0.195200E+09 | 0.773907E+09 | 0.277542E+09 | 0.496365E+09 | 0.00 | 0.00 |
September | 0.118547E+10 | 0.306441E+09 | 0.907560E+09 | 0.478210E+09 | 0.429350E+09 | 0.00 | 0.00 |
October | 0.114014E+10 | 0.443093E+09 | 0.979273E+09 | 0.614356E+09 | 0.364917E+09 | 0.00 | 0.00 |
November | 0.705878E+09 | 0.631814E+09 | 0.715025E+09 | 0.447619E+09 | 0.267406E+09 | 0.00 | 0.00 |
December | 0.778581E+09 | 0.937746E+09 | 0.787887E+09 | 0.596815E+09 | 0.191072E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.110851E+11 | 0.579711E+10 | 0.971291E+10 | 0.501836E+10 | 0.469455E+10 | 0.00 | 0.00 |
Minimum of Months | 0.705878E+09 | 0.162005E+09 | 0.627961E+09 | 0.127856E+09 | 0.191072E+09 | 0.00 | 0.00 |
Maximum of Months | 0.118547E+10 | 0.100691E+10 | 0.979273E+09 | 0.657202E+09 | 0.513818E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.885000E+09 | 0.100594E+10 | 0.960369E+09 | 0.657202E+09 | 0.303168E+09 | 0.00 | 0.00 |
February | 0.897430E+09 | 0.723854E+09 | 0.929436E+09 | 0.627934E+09 | 0.301502E+09 | 0.00 | 0.00 |
March | 0.921108E+09 | 0.562576E+09 | 0.895477E+09 | 0.471528E+09 | 0.423948E+09 | 0.00 | 0.00 |
April | 0.894843E+09 | 0.396864E+09 | 0.780740E+09 | 0.365011E+09 | 0.415729E+09 | 0.00 | 0.00 |
May | 0.823234E+09 | 0.247986E+09 | 0.668377E+09 | 0.181206E+09 | 0.487171E+09 | 0.00 | 0.00 |
June | 0.836634E+09 | 0.172319E+09 | 0.627961E+09 | 0.127856E+09 | 0.500104E+09 | 0.00 | 0.00 |
July | 0.946423E+09 | 0.161123E+09 | 0.686899E+09 | 0.173080E+09 | 0.513818E+09 | 0.00 | 0.00 |
August | 0.107767E+10 | 0.194319E+09 | 0.773907E+09 | 0.277542E+09 | 0.496365E+09 | 0.00 | 0.00 |
September | 0.118630E+10 | 0.304875E+09 | 0.907560E+09 | 0.478210E+09 | 0.429350E+09 | 0.00 | 0.00 |
October | 0.114102E+10 | 0.441110E+09 | 0.979273E+09 | 0.614356E+09 | 0.364917E+09 | 0.00 | 0.00 |
November | 0.706390E+09 | 0.630178E+09 | 0.715025E+09 | 0.447619E+09 | 0.267406E+09 | 0.00 | 0.00 |
December | 0.778822E+09 | 0.936468E+09 | 0.787887E+09 | 0.596815E+09 | 0.191072E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.110949E+11 | 0.577761E+10 | 0.971291E+10 | 0.501836E+10 | 0.469455E+10 | 0.00 | 0.00 |
Minimum of Months | 0.706390E+09 | 0.161123E+09 | 0.627961E+09 | 0.127856E+09 | 0.191072E+09 | 0.00 | 0.00 |
Maximum of Months | 0.118630E+10 | 0.100594E+10 | 0.979273E+09 | 0.657202E+09 | 0.513818E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.886100E+09 | 0.999235E+09 | 0.960369E+09 | 0.657202E+09 | 0.303168E+09 | 0.00 | 0.00 |
February | 0.898904E+09 | 0.717166E+09 | 0.929436E+09 | 0.627934E+09 | 0.301502E+09 | 0.00 | 0.00 |
March | 0.923559E+09 | 0.554067E+09 | 0.895477E+09 | 0.471528E+09 | 0.423948E+09 | 0.00 | 0.00 |
April | 0.897745E+09 | 0.388094E+09 | 0.780740E+09 | 0.365011E+09 | 0.415729E+09 | 0.00 | 0.00 |
May | 0.829541E+09 | 0.239414E+09 | 0.668377E+09 | 0.181206E+09 | 0.487171E+09 | 0.00 | 0.00 |
June | 0.839410E+09 | 0.168358E+09 | 0.627961E+09 | 0.127856E+09 | 0.500104E+09 | 0.00 | 0.00 |
July | 0.947955E+09 | 0.158759E+09 | 0.686899E+09 | 0.173080E+09 | 0.513818E+09 | 0.00 | 0.00 |
August | 0.107884E+10 | 0.192005E+09 | 0.773907E+09 | 0.277542E+09 | 0.496365E+09 | 0.00 | 0.00 |
September | 0.118822E+10 | 0.300729E+09 | 0.907560E+09 | 0.478210E+09 | 0.429350E+09 | 0.00 | 0.00 |
October | 0.114343E+10 | 0.434780E+09 | 0.979273E+09 | 0.614356E+09 | 0.364917E+09 | 0.00 | 0.00 |
November | 0.708125E+09 | 0.623331E+09 | 0.715025E+09 | 0.447619E+09 | 0.267406E+09 | 0.00 | 0.00 |
December | 0.779968E+09 | 0.928783E+09 | 0.787887E+09 | 0.596815E+09 | 0.191072E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.111218E+11 | 0.570472E+10 | 0.971291E+10 | 0.501836E+10 | 0.469455E+10 | 0.00 | 0.00 |
Minimum of Months | 0.708125E+09 | 0.158759E+09 | 0.627961E+09 | 0.127856E+09 | 0.191072E+09 | 0.00 | 0.00 |
Maximum of Months | 0.118822E+10 | 0.999235E+09 | 0.979273E+09 | 0.657202E+09 | 0.513818E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.892304E+09 | 0.966526E+09 | 0.960369E+09 | 0.657202E+09 | 0.303168E+09 | 0.00 | 0.00 |
February | 0.906180E+09 | 0.684898E+09 | 0.929436E+09 | 0.627934E+09 | 0.301502E+09 | 0.00 | 0.00 |
March | 0.933077E+09 | 0.517296E+09 | 0.895477E+09 | 0.471528E+09 | 0.423948E+09 | 0.00 | 0.00 |
April | 0.907112E+09 | 0.353378E+09 | 0.780740E+09 | 0.365011E+09 | 0.415729E+09 | 0.00 | 0.00 |
May | 0.843169E+09 | 0.214799E+09 | 0.668377E+09 | 0.181206E+09 | 0.487171E+09 | 0.00 | 0.00 |
June | 0.846343E+09 | 0.154564E+09 | 0.627961E+09 | 0.127856E+09 | 0.500104E+09 | 0.00 | 0.00 |
July | 0.951649E+09 | 0.149662E+09 | 0.686899E+09 | 0.173080E+09 | 0.513818E+09 | 0.00 | 0.00 |
August | 0.108132E+10 | 0.182897E+09 | 0.773907E+09 | 0.277542E+09 | 0.496365E+09 | 0.00 | 0.00 |
September | 0.119214E+10 | 0.286503E+09 | 0.907560E+09 | 0.478210E+09 | 0.429350E+09 | 0.00 | 0.00 |
October | 0.115012E+10 | 0.411639E+09 | 0.979273E+09 | 0.614356E+09 | 0.364917E+09 | 0.00 | 0.00 |
November | 0.714420E+09 | 0.594322E+09 | 0.715025E+09 | 0.447619E+09 | 0.267406E+09 | 0.00 | 0.00 |
December | 0.785139E+09 | 0.891962E+09 | 0.787887E+09 | 0.596815E+09 | 0.191072E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.112030E+11 | 0.540844E+10 | 0.971291E+10 | 0.501836E+10 | 0.469455E+10 | 0.00 | 0.00 |
Minimum of Months | 0.714420E+09 | 0.149662E+09 | 0.627961E+09 | 0.127856E+09 | 0.191072E+09 | 0.00 | 0.00 |
Maximum of Months | 0.119214E+10 | 0.966526E+09 | 0.979273E+09 | 0.657202E+09 | 0.513818E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -12.6 | -13.1 | -15.2 | 6.10 | -26.1 | 37.55 | 107.22 | 0.02 |
February | -7.7 | -8.6 | -10.9 | 6.39 | -21.3 | 45.57 | 135.04 | 0.00 |
March | 0.33 | -1.4 | -4.2 | 6.99 | -10.6 | 74.69 | 127.11 | 0.00 |
April | 7.02 | 4.40 | 1.63 | 6.38 | -3.6 | 77.59 | 184.47 | 0.02 |
May | 14.19 | 11.30 | 8.94 | 5.14 | 4.70 | 102.33 | 182.89 | 0.00 |
June | 19.16 | 15.71 | 13.79 | 4.87 | 8.84 | 110.26 | 213.51 | 0.04 |
July | 20.92 | 17.87 | 16.31 | 4.22 | 9.95 | 102.99 | 231.93 | 0.03 |
August | 20.05 | 17.00 | 15.28 | 4.97 | 11.01 | 95.97 | 190.14 | 0.00 |
September | 15.39 | 11.24 | 8.10 | 4.97 | 3.18 | 72.67 | 177.74 | 0.01 |
October | 7.43 | 4.69 | 1.56 | 5.55 | -3.9 | 55.50 | 131.91 | 0.00 |
November | -0.0 | -1.5 | -3.9 | 6.30 | -10.9 | 41.35 | 79.05 | 0.00 |
December | -7.6 | -8.4 | -10.6 | 6.09 | -20.0 | 22.97 | 92.59 | 0.00 |
Annual Sum or Average | 6.46 | 4.16 | 1.81 | 5.66 | -4.8 | 70.09 | 154.52 | 0.01 |
Minimum of Months | -12.6 | -13.1 | -15.2 | 4.22 | -26.1 | 22.97 | 79.05 | 0.00 |
Maximum of Months | 20.92 | 17.87 | 16.31 | 6.99 | 11.01 | 110.26 | 231.93 | 0.04 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 6.10 | 17-JAN-23:19 | 3.74 | 0.93 | 10.63 | -0.4 | 0.00 | 0.00 |
February | 8.30 | 24-FEB-14:00 | 5.62 | 2.80 | 5.20 | -7.3 | 71.00 | 794.50 |
March | 18.90 | 19-MAR-15:00 | 13.93 | 10.60 | 8.80 | 7.95 | 139.50 | 237.50 |
April | 30.00 | 15-APR-15:20 | 19.12 | 13.53 | 12.70 | 15.70 | 115.83 | 790.83 |
May | 30.00 | 31-MAY-12:00 | 19.70 | 14.40 | 6.20 | 19.52 | 251.00 | 580.50 |
June | 33.30 | 11-JUN-14:00 | 24.81 | 21.70 | 10.30 | 24.50 | 281.00 | 458.50 |
July | 30.00 | 26-JUL-15:20 | 25.67 | 24.23 | 5.13 | 20.98 | 260.33 | 436.00 |
August | 33.90 | 04-AUG-14:00 | 25.31 | 22.20 | 4.60 | 23.82 | 194.50 | 612.00 |
September | 32.20 | 06-SEP-13:00 | 21.19 | 16.10 | 6.20 | 18.28 | 135.00 | 769.00 |
October | 23.30 | 20-OCT-14:00 | 13.36 | 5.60 | 7.20 | 7.35 | 55.00 | 745.50 |
November | 16.10 | 03-NOV-13:00 | 10.47 | 5.60 | 6.70 | 0.51 | 82.00 | 691.00 |
December | 7.20 | 02-DEC-13:00 | 3.94 | 0.00 | 7.70 | -3.9 | 75.00 | 301.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.10 | 3.74 | 0.00 | 4.60 | -7.3 | 0.00 | 0.00 | |
Maximum of Months | 33.90 | 25.67 | 24.23 | 12.70 | 24.50 | 281.00 | 794.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -31.1 | 31-JAN-03:00 | -31.3 | -34.4 | 4.60 | -46.7 | 0.00 | 0.00 |
February | -36.7 | 02-FEB-05:00 | -36.8 | -40.2 | 3.10 | -59.6 | 0.00 | 0.00 |
March | -17.2 | 06-MAR-00:00 | -17.6 | -20.0 | 5.20 | -36.8 | 0.00 | 0.00 |
April | -7.2 | 03-APR-05:19 | -8.0 | -9.8 | 7.37 | -15.9 | 0.00 | 0.00 |
May | 0.60 | 03-MAY-02:00 | -0.1 | -1.1 | 1.50 | -15.5 | 0.00 | 0.00 |
June | 5.00 | 01-JUN-04:00 | 5.00 | 5.00 | 3.10 | -7.8 | 30.50 | 132.50 |
July | 10.00 | 23-JUL-03:00 | 9.66 | 9.40 | 2.60 | -4.3 | 0.00 | 0.00 |
August | 8.30 | 07-AUG-03:00 | 7.41 | 6.70 | 3.10 | -3.2 | 0.00 | 0.00 |
September | -1.1 | 30-SEP-00:00 | -2.4 | -4.4 | 4.10 | -17.8 | 0.00 | 0.00 |
October | -3.3 | 23-OCT-05:00 | -4.2 | -6.1 | 3.60 | -19.1 | 0.00 | 0.00 |
November | -28.9 | 26-NOV-06:00 | -29.0 | -30.6 | 1.50 | -50.2 | 0.00 | 0.00 |
December | -22.8 | 09-DEC-00:20 | -23.0 | -25.0 | 13.40 | -37.7 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -36.7 | -36.8 | -40.2 | 1.50 | -59.6 | 0.00 | 0.00 | |
Maximum of Months | 10.00 | 9.66 | 9.40 | 13.40 | -3.2 | 30.50 | 132.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 5.60 | 18-JAN-00:00 | 5.60 | 5.60 | 7.70 | 0.30 | 0.00 | 0.00 |
February | 5.88 | 24-FEB-15:00 | 8.30 | 3.30 | 5.70 | -7.3 | 54.50 | 665.50 |
March | 13.93 | 19-MAR-15:00 | 18.90 | 10.60 | 8.80 | 7.95 | 139.50 | 237.50 |
April | 20.94 | 18-APR-11:00 | 27.80 | 17.80 | 13.90 | 17.57 | 334.00 | 447.00 |
May | 19.93 | 29-MAY-13:00 | 23.30 | 18.30 | 6.20 | 20.75 | 379.00 | 52.00 |
June | 24.81 | 11-JUN-14:00 | 33.30 | 21.70 | 10.30 | 24.50 | 281.00 | 458.50 |
July | 26.15 | 26-JUL-18:00 | 27.80 | 25.60 | 3.10 | 19.35 | 33.50 | 51.00 |
August | 26.64 | 04-AUG-12:00 | 31.70 | 25.00 | 4.60 | 25.66 | 235.00 | 593.50 |
September | 21.19 | 06-SEP-13:00 | 32.20 | 16.10 | 6.20 | 18.28 | 135.00 | 769.00 |
October | 14.84 | 02-OCT-14:00 | 18.30 | 12.80 | 3.60 | 12.41 | 202.00 | 164.00 |
November | 13.04 | 09-NOV-04:00 | 15.00 | 11.70 | 10.30 | 10.88 | 0.00 | 0.00 |
December | 3.94 | 02-DEC-13:00 | 7.20 | 0.00 | 7.70 | -3.9 | 75.00 | 301.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 3.94 | 5.60 | 0.00 | 3.10 | -7.3 | 0.00 | 0.00 | |
Maximum of Months | 26.64 | 33.30 | 25.60 | 13.90 | 25.66 | 379.00 | 769.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 5.60 | 18-JAN-00:00 | 5.60 | 5.60 | 7.70 | 0.30 | 0.00 | 0.00 |
February | 3.30 | 24-FEB-15:00 | 8.30 | 5.88 | 5.70 | -7.3 | 54.50 | 665.50 |
March | 11.10 | 26-MAR-05:00 | 13.30 | 12.04 | 8.20 | 9.13 | 0.00 | 0.00 |
April | 18.30 | 18-APR-09:00 | 25.60 | 20.52 | 14.40 | 15.57 | 196.00 | 741.50 |
May | 18.30 | 29-MAY-13:00 | 23.30 | 19.93 | 6.20 | 20.75 | 379.00 | 52.00 |
June | 22.20 | 13-JUN-11:00 | 26.70 | 23.35 | 8.80 | 16.85 | 273.50 | 600.50 |
July | 25.60 | 26-JUL-18:00 | 27.80 | 26.15 | 3.10 | 19.35 | 33.50 | 51.00 |
August | 25.00 | 04-AUG-12:00 | 31.70 | 26.64 | 4.60 | 25.66 | 235.00 | 593.50 |
September | 18.30 | 12-SEP-02:00 | 18.90 | 18.46 | 5.70 | 14.28 | 0.00 | 0.00 |
October | 12.80 | 02-OCT-13:00 | 17.40 | 14.50 | 3.40 | 11.65 | 249.50 | 141.50 |
November | 11.70 | 08-NOV-10:00 | 13.90 | 12.62 | 7.20 | 9.91 | 158.00 | 0.50 |
December | 0.00 | 02-DEC-11:00 | 5.00 | 2.79 | 7.20 | -8.3 | 115.50 | 562.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 0.00 | 5.00 | 2.79 | 3.10 | -8.3 | 0.00 | 0.00 | |
Maximum of Months | 25.60 | 31.70 | 26.64 | 14.40 | 25.66 | 379.00 | 741.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 4.29 | 14.52 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 3.18 | 19.75 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 3.75 | 28.43 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 5.88 | 38.20 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 9.06 | 44.89 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 12.40 | 51.07 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 15.02 | 51.61 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 16.22 | 43.31 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 15.63 | 34.41 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 13.44 | 22.83 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 10.25 | 13.98 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 6.92 | 10.24 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 9.71 | 31.16 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 3.18 | 10.24 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 16.22 | 51.61 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK1
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.395280E+09 | -268564856.1 | 0.00 | 0.00 | 744.00 | 0.00 | -126715281.1 | 58.99 | 0.00 | 0.00 |
February | 0.362726E+09 | -248805453.2 | 0.00 | 0.00 | 672.00 | 0.00 | -113920480.2 | 58.99 | 0.00 | 0.00 |
March | 0.402319E+09 | -277177163.5 | 0.00 | 0.00 | 744.00 | 0.00 | -125141671.8 | 58.99 | 0.00 | 0.00 |
April | 0.373136E+09 | -254533348.3 | 0.00 | 0.00 | 720.00 | 0.00 | -118602608.1 | 58.99 | 0.00 | 0.00 |
May | 0.365248E+09 | -247772775.9 | 0.00 | 0.00 | 744.00 | 0.00 | -117475206.2 | 58.99 | 0.00 | 0.00 |
June | 0.336773E+09 | -225931494.9 | 0.00 | 0.00 | 720.00 | 0.00 | -110841945.8 | 58.99 | 0.00 | 0.00 |
July | 0.328638E+09 | -215808414.2 | 0.00 | 0.00 | 744.00 | 0.00 | -112830004.1 | 59.00 | 0.00 | 0.00 |
August | 0.327319E+09 | -214447920.1 | 0.00 | 0.00 | 744.00 | 0.00 | -112871042.3 | 58.99 | 0.00 | 0.00 |
September | 0.319887E+09 | -208010465.5 | 0.00 | 0.00 | 720.00 | 0.00 | -111876969.9 | 58.99 | 0.00 | 0.00 |
October | 0.345530E+09 | -223676409.1 | 0.00 | 0.00 | 744.00 | 0.00 | -121853603.0 | 58.99 | 0.00 | 0.00 |
November | 0.351249E+09 | -230934444.6 | 0.00 | 0.00 | 720.00 | 0.00 | -120315030.0 | 58.99 | 0.00 | 0.00 |
December | 0.382102E+09 | -255969156.0 | 0.00 | 0.00 | 744.00 | 0.00 | -126132933.2 | 59.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.429021E+10 | -0.287163E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.141858E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.319887E+09 | -277177163.5 | 0.00 | 0.00 | 672.00 | 0.00 | -126715281.1 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.402319E+09 | -208010465.5 | 0.00 | 0.00 | 744.00 | 0.00 | -110841945.8 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK2
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.393888E+09 | -268562743.1 | 0.00 | 0.00 | 744.00 | 0.00 | -125325365.5 | 59.00 | 0.00 | 0.00 |
February | 0.361267E+09 | -248800589.7 | 0.00 | 0.00 | 672.00 | 0.00 | -112466669.3 | 58.99 | 0.00 | 0.00 |
March | 0.400176E+09 | -277175783.1 | 0.00 | 0.00 | 744.00 | 0.00 | -123000554.4 | 58.99 | 0.00 | 0.00 |
April | 0.370867E+09 | -254530570.6 | 0.00 | 0.00 | 720.00 | 0.00 | -116336516.8 | 59.00 | 0.00 | 0.00 |
May | 0.362894E+09 | -247771303.9 | 0.00 | 0.00 | 744.00 | 0.00 | -115122748.9 | 58.99 | 0.00 | 0.00 |
June | 0.335745E+09 | -225932377.4 | 0.00 | 0.00 | 720.00 | 0.00 | -109812600.7 | 58.99 | 0.00 | 0.00 |
July | 0.328388E+09 | -215825330.6 | 0.00 | 0.00 | 744.00 | 0.00 | -112562389.4 | 58.99 | 0.00 | 0.00 |
August | 0.327020E+09 | -214452778.9 | 0.00 | 0.00 | 744.00 | 0.00 | -112567132.2 | 58.99 | 0.00 | 0.00 |
September | 0.318634E+09 | -208011353.0 | 0.00 | 0.00 | 720.00 | 0.00 | -110623131.8 | 58.99 | 0.00 | 0.00 |
October | 0.342803E+09 | -223678734.8 | 0.00 | 0.00 | 744.00 | 0.00 | -119124370.3 | 58.99 | 0.00 | 0.00 |
November | 0.349082E+09 | -230935897.4 | 0.00 | 0.00 | 720.00 | 0.00 | -118145902.6 | 58.99 | 0.00 | 0.00 |
December | 0.380465E+09 | -255975218.7 | 0.00 | 0.00 | 744.00 | 0.00 | -124489540.4 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.427123E+10 | -0.287165E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.139958E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.318634E+09 | -277175783.1 | 0.00 | 0.00 | 672.00 | 0.00 | -125325365.5 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.400176E+09 | -208011353.0 | 0.00 | 0.00 | 744.00 | 0.00 | -109812600.7 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK3
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.363516E+09 | -236168583.9 | 0.00 | 0.00 | 744.00 | 0.00 | -127347345.9 | 59.00 | 0.00 | 0.00 |
February | 0.333105E+09 | -218975124.3 | 0.00 | 0.00 | 672.00 | 0.00 | -114130062.1 | 58.98 | 0.00 | 0.00 |
March | 0.371947E+09 | -247364734.2 | 0.00 | 0.00 | 744.00 | 0.00 | -124582687.5 | 59.00 | 0.00 | 0.00 |
April | 0.341427E+09 | -223874139.7 | 0.00 | 0.00 | 720.00 | 0.00 | -117552569.5 | 58.99 | 0.00 | 0.00 |
May | 0.335266E+09 | -219770575.1 | 0.00 | 0.00 | 744.00 | 0.00 | -115495245.8 | 58.99 | 0.00 | 0.00 |
June | 0.310342E+09 | -201200089.9 | 0.00 | 0.00 | 720.00 | 0.00 | -109141434.9 | 58.99 | 0.00 | 0.00 |
July | 0.299871E+09 | -188667324.7 | 0.00 | 0.00 | 744.00 | 0.00 | -111203303.0 | 58.99 | 0.00 | 0.00 |
August | 0.303046E+09 | -191547314.8 | 0.00 | 0.00 | 744.00 | 0.00 | -111498387.1 | 58.99 | 0.00 | 0.00 |
September | 0.293165E+09 | -182835359.4 | 0.00 | 0.00 | 720.00 | 0.00 | -110329642.5 | 58.99 | 0.00 | 0.00 |
October | 0.317646E+09 | -196741577.0 | 0.00 | 0.00 | 744.00 | 0.00 | -120904378.0 | 58.98 | 0.00 | 0.00 |
November | 0.323854E+09 | -203913485.2 | 0.00 | 0.00 | 720.00 | 0.00 | -119940362.5 | 58.99 | 0.00 | 0.00 |
December | 0.349765E+09 | -223419755.6 | 0.00 | 0.00 | 744.00 | 0.00 | -126345402.9 | 59.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.394295E+10 | -0.253448E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.140847E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.293165E+09 | -247364734.2 | 0.00 | 0.00 | 672.00 | 0.00 | -127347345.9 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.371947E+09 | -182835359.4 | 0.00 | 0.00 | 744.00 | 0.00 | -109141434.9 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK4
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.363924E+09 | -236164903.3 | 0.00 | 0.00 | 744.00 | 0.00 | -127759192.9 | 59.00 | 0.00 | 0.00 |
February | 0.333476E+09 | -218953189.1 | 0.00 | 0.00 | 672.00 | 0.00 | -114522320.6 | 59.00 | 0.00 | 0.00 |
March | 0.372313E+09 | -247379123.7 | 0.00 | 0.00 | 744.00 | 0.00 | -124933956.2 | 58.99 | 0.00 | 0.00 |
April | 0.341785E+09 | -223878461.3 | 0.00 | 0.00 | 720.00 | 0.00 | -117906538.7 | 58.99 | 0.00 | 0.00 |
May | 0.335686E+09 | -219778139.5 | 0.00 | 0.00 | 744.00 | 0.00 | -115907869.1 | 58.99 | 0.00 | 0.00 |
June | 0.310457E+09 | -201195868.7 | 0.00 | 0.00 | 720.00 | 0.00 | -109261540.6 | 58.99 | 0.00 | 0.00 |
July | 0.299867E+09 | -188650844.1 | 0.00 | 0.00 | 744.00 | 0.00 | -111216211.7 | 58.99 | 0.00 | 0.00 |
August | 0.303079E+09 | -191545622.1 | 0.00 | 0.00 | 744.00 | 0.00 | -111533077.0 | 58.99 | 0.00 | 0.00 |
September | 0.293324E+09 | -182824785.3 | 0.00 | 0.00 | 720.00 | 0.00 | -110498910.8 | 58.99 | 0.00 | 0.00 |
October | 0.318139E+09 | -196729674.8 | 0.00 | 0.00 | 744.00 | 0.00 | -121409328.9 | 58.99 | 0.00 | 0.00 |
November | 0.324313E+09 | -203907051.9 | 0.00 | 0.00 | 720.00 | 0.00 | -120406275.1 | 58.99 | 0.00 | 0.00 |
December | 0.350150E+09 | -223429610.7 | 0.00 | 0.00 | 744.00 | 0.00 | -126720692.1 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.394651E+10 | -0.253444E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.141208E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.293324E+09 | -247379123.7 | 0.00 | 0.00 | 672.00 | 0.00 | -127759192.9 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.372313E+09 | -182824785.3 | 0.00 | 0.00 | 744.00 | 0.00 | -109261540.6 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK5
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.352695E+09 | -223215303.3 | 0.00 | 0.00 | 744.00 | 0.00 | -129479638.4 | 58.99 | 0.00 | 0.00 |
February | 0.323009E+09 | -207068007.5 | 0.00 | 0.00 | 672.00 | 0.00 | -115940861.0 | 58.99 | 0.00 | 0.00 |
March | 0.360597E+09 | -234068273.0 | 0.00 | 0.00 | 744.00 | 0.00 | -126528525.7 | 58.99 | 0.00 | 0.00 |
April | 0.331217E+09 | -211845415.9 | 0.00 | 0.00 | 720.00 | 0.00 | -119371091.4 | 58.99 | 0.00 | 0.00 |
May | 0.325827E+09 | -207840615.2 | 0.00 | 0.00 | 744.00 | 0.00 | -117986814.9 | 58.99 | 0.00 | 0.00 |
June | 0.300663E+09 | -190388769.0 | 0.00 | 0.00 | 720.00 | 0.00 | -110274442.2 | 58.99 | 0.00 | 0.00 |
July | 0.290326E+09 | -178426856.9 | 0.00 | 0.00 | 744.00 | 0.00 | -111898832.3 | 58.99 | 0.00 | 0.00 |
August | 0.293453E+09 | -181188870.2 | 0.00 | 0.00 | 744.00 | 0.00 | -112263864.6 | 59.01 | 0.00 | 0.00 |
September | 0.284503E+09 | -173014180.7 | 0.00 | 0.00 | 720.00 | 0.00 | -111489002.6 | 58.99 | 0.00 | 0.00 |
October | 0.308729E+09 | -185936680.1 | 0.00 | 0.00 | 744.00 | 0.00 | -122792307.0 | 58.99 | 0.00 | 0.00 |
November | 0.314503E+09 | -192577563.8 | 0.00 | 0.00 | 720.00 | 0.00 | -121925081.5 | 58.99 | 0.00 | 0.00 |
December | 0.339657E+09 | -211311143.8 | 0.00 | 0.00 | 744.00 | 0.00 | -128346132.7 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.382518E+10 | -0.239688E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.142830E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.284503E+09 | -234068273.0 | 0.00 | 0.00 | 672.00 | 0.00 | -129479638.4 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.360597E+09 | -173014180.7 | 0.00 | 0.00 | 744.00 | 0.00 | -110274442.2 | 59.01 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK6
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.352537E+09 | -223214582.7 | 0.00 | 0.00 | 744.00 | 0.00 | -129322255.8 | 58.99 | 0.00 | 0.00 |
February | 0.322909E+09 | -207059962.1 | 0.00 | 0.00 | 672.00 | 0.00 | -115848572.2 | 59.00 | 0.00 | 0.00 |
March | 0.360538E+09 | -234070556.7 | 0.00 | 0.00 | 744.00 | 0.00 | -126466969.2 | 58.99 | 0.00 | 0.00 |
April | 0.331235E+09 | -211857051.9 | 0.00 | 0.00 | 720.00 | 0.00 | -119378066.2 | 58.99 | 0.00 | 0.00 |
May | 0.326078E+09 | -207834465.7 | 0.00 | 0.00 | 744.00 | 0.00 | -118243208.2 | 58.99 | 0.00 | 0.00 |
June | 0.300785E+09 | -190383777.0 | 0.00 | 0.00 | 720.00 | 0.00 | -110401282.2 | 58.99 | 0.00 | 0.00 |
July | 0.290423E+09 | -178422799.5 | 0.00 | 0.00 | 744.00 | 0.00 | -111999734.4 | 58.99 | 0.00 | 0.00 |
August | 0.293537E+09 | -181191607.3 | 0.00 | 0.00 | 744.00 | 0.00 | -112345531.6 | 59.01 | 0.00 | 0.00 |
September | 0.284602E+09 | -172991801.9 | 0.00 | 0.00 | 720.00 | 0.00 | -111610097.2 | 59.00 | 0.00 | 0.00 |
October | 0.308785E+09 | -185947258.1 | 0.00 | 0.00 | 744.00 | 0.00 | -122837485.8 | 58.99 | 0.00 | 0.00 |
November | 0.314462E+09 | -192580605.0 | 0.00 | 0.00 | 720.00 | 0.00 | -121881785.1 | 58.99 | 0.00 | 0.00 |
December | 0.339529E+09 | -211297877.8 | 0.00 | 0.00 | 744.00 | 0.00 | -128230847.4 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.382542E+10 | -0.239685E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.142857E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.284602E+09 | -234070556.7 | 0.00 | 0.00 | 672.00 | 0.00 | -129322255.8 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.360538E+09 | -172991801.9 | 0.00 | 0.00 | 744.00 | 0.00 | -110401282.2 | 59.01 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK7
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.352588E+09 | -223214377.9 | 0.00 | 0.00 | 744.00 | 0.00 | -129373277.9 | 58.99 | 0.00 | 0.00 |
February | 0.322973E+09 | -207064052.0 | 0.00 | 0.00 | 672.00 | 0.00 | -115908907.4 | 58.99 | 0.00 | 0.00 |
March | 0.360643E+09 | -234070766.9 | 0.00 | 0.00 | 744.00 | 0.00 | -126572135.9 | 58.99 | 0.00 | 0.00 |
April | 0.331390E+09 | -211845055.0 | 0.00 | 0.00 | 720.00 | 0.00 | -119544719.6 | 58.99 | 0.00 | 0.00 |
May | 0.326458E+09 | -207836377.8 | 0.00 | 0.00 | 744.00 | 0.00 | -118621428.7 | 59.00 | 0.00 | 0.00 |
June | 0.300914E+09 | -190381853.5 | 0.00 | 0.00 | 720.00 | 0.00 | -110532344.8 | 58.99 | 0.00 | 0.00 |
July | 0.290485E+09 | -178443510.2 | 0.00 | 0.00 | 744.00 | 0.00 | -112041058.2 | 58.98 | 0.00 | 0.00 |
August | 0.293597E+09 | -181218973.3 | 0.00 | 0.00 | 744.00 | 0.00 | -112377957.7 | 59.00 | 0.00 | 0.00 |
September | 0.284721E+09 | -173017371.9 | 0.00 | 0.00 | 720.00 | 0.00 | -111703967.6 | 58.99 | 0.00 | 0.00 |
October | 0.308921E+09 | -185945095.1 | 0.00 | 0.00 | 744.00 | 0.00 | -122976312.2 | 58.99 | 0.00 | 0.00 |
November | 0.314563E+09 | -192583567.1 | 0.00 | 0.00 | 720.00 | 0.00 | -121979746.0 | 58.99 | 0.00 | 0.00 |
December | 0.339599E+09 | -211288440.2 | 0.00 | 0.00 | 744.00 | 0.00 | -128310131.1 | 59.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.382685E+10 | -0.239691E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.142994E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.284721E+09 | -234070766.9 | 0.00 | 0.00 | 672.00 | 0.00 | -129373277.9 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.360643E+09 | -173017371.9 | 0.00 | 0.00 | 744.00 | 0.00 | -110532344.8 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 214.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 226.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 334.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 285.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 428.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 400.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 414.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 410.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 326.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 325.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 254.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 186.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3807.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 186.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 428.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 HEATING COIL
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.392177E+11 | 64741.21 | 01-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.281627E+11 | 64741.21 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.185329E+11 | 64741.21 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.922808E+10 | 64741.21 | 01-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.563287E+09 | 64741.21 | 01-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 95594985.61 | 7814.26 | 03-JUN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.672847E+09 | 64741.21 | 29-SEP-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.452852E+10 | 64741.21 | 06-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.173263E+11 | 64741.21 | 10-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.311865E+11 | 64741.21 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.149514E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.392177E+11 | 64741.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 HEATING COIL
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.143230E+11 | 33633.97 | 01-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.996187E+10 | 33633.97 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.596525E+10 | 33633.97 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.271657E+10 | 33633.97 | 01-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 74815021.23 | 30669.56 | 02-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 61536014.79 | 29175.96 | 30-SEP-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.832749E+09 | 33633.97 | 27-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.577605E+10 | 33633.97 | 10-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.110772E+11 | 33633.97 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.507890E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.143230E+11 | 33633.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3 HEATING COIL
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.156812E+11 | 33714.65 | 01-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.110652E+11 | 33714.65 | 01-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.700184E+10 | 33714.65 | 01-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.334094E+10 | 33714.65 | 01-APR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.151631E+09 | 26015.21 | 02-MAY-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 2588845.58 | 744.18 | 05-JUN-07:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.146749E+09 | 19459.62 | 30-SEP-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.142476E+10 | 27214.44 | 08-OCT-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.664124E+10 | 33714.65 | 11-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.123021E+11 | 33714.65 | 01-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.577582E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.156812E+11 | 33714.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4 HEATING COIL
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.159641E+11 | 34375.17 | 01-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.112936E+11 | 34375.17 | 01-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.721118E+10 | 34375.17 | 01-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.348414E+10 | 34375.17 | 01-APR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.176752E+09 | 30804.21 | 02-MAY-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 11797368.42 | 949.78 | 05-JUN-07:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.175777E+09 | 22495.16 | 30-SEP-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.160595E+10 | 31952.65 | 08-OCT-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.685334E+10 | 34375.17 | 11-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.125514E+11 | 34375.17 | 01-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.593280E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.159641E+11 | 34375.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5 HEATING COIL
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.164087E+11 | 33522.34 | 01-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.116598E+11 | 33522.34 | 01-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.758226E+10 | 33522.34 | 01-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.373288E+10 | 33522.34 | 01-APR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.219833E+09 | 33522.34 | 02-MAY-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 28333898.54 | 2504.10 | 05-JUN-07:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.226417E+09 | 25925.51 | 30-SEP-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.185787E+10 | 33522.34 | 08-OCT-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.718359E+10 | 33522.34 | 10-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129648E+11 | 33522.34 | 01-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.618645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.164087E+11 | 33522.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6 HEATING COIL
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.312478E+11 | 62691.16 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.223044E+11 | 62691.16 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.147632E+11 | 62691.16 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.738467E+10 | 62691.16 | 01-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491257E+09 | 62691.16 | 01-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.112061E+09 | 10087.41 | 05-JUN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.569674E+09 | 62691.16 | 29-SEP-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.412835E+10 | 62691.16 | 01-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.140525E+11 | 62691.16 | 05-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.248812E+11 | 62691.16 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.119935E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.312478E+11 | 62691.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7 HEATING COIL
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.161857E+11 | 31817.90 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.115837E+11 | 31817.90 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.770635E+10 | 31817.90 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.387580E+10 | 31817.90 | 01-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.268386E+09 | 31817.90 | 01-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 62817540.73 | 7601.57 | 05-JUN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.301133E+09 | 31817.90 | 29-SEP-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.215593E+10 | 31817.90 | 01-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.731692E+10 | 31817.90 | 05-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129035E+11 | 31817.90 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.623602E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.161857E+11 | 31817.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8 HEATING COIL
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.162566E+11 | 31665.50 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.116538E+11 | 31665.50 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.779904E+10 | 31665.50 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.396014E+10 | 31665.50 | 01-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.296593E+09 | 31665.50 | 01-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 74614333.65 | 11497.74 | 05-JUN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.321808E+09 | 31665.50 | 29-SEP-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.223730E+10 | 31665.50 | 01-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.740044E+10 | 31665.50 | 05-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129774E+11 | 31665.50 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.629777E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.162566E+11 | 31665.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9 HEATING COIL
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.167245E+11 | 31449.28 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.120987E+11 | 31449.28 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.825461E+10 | 31449.28 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.431454E+10 | 31449.28 | 01-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.398682E+09 | 31449.28 | 01-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.111793E+09 | 22214.19 | 05-JUN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.385540E+09 | 31449.28 | 28-SEP-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.251141E+10 | 31449.28 | 01-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.776926E+10 | 31449.28 | 01-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.134353E+11 | 31449.28 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.660043E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.167245E+11 | 31449.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10 HEATING COIL
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.209980E+11 | 36225.34 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.153146E+11 | 36225.34 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.107185E+11 | 36225.34 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.583860E+10 | 36225.34 | 01-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.794459E+09 | 36225.34 | 01-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.236174E+09 | 36225.34 | 03-JUN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.565040E+09 | 36225.34 | 27-SEP-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.327635E+10 | 36225.34 | 01-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.966586E+10 | 36225.34 | 01-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.166136E+11 | 36225.34 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.840212E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.209980E+11 | 36225.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.152756E+10 | 0.105909E+10 | 18204.31 | 16-APR-16:10 | 12907.58 | 0.00 |
May | 0.00 | 0.00 | 0.253264E+10 | 0.176992E+10 | 17702.38 | 31-MAY-17:00 | 13596.51 | 0.00 |
June | 0.00 | 0.00 | 0.127936E+11 | 0.859408E+10 | 48670.56 | 27-JUN-07:03 | 25778.62 | 0.00 |
July | 0.00 | 0.00 | 0.178686E+11 | 0.110864E+11 | 47378.88 | 04-JUL-07:02 | 24588.09 | 0.00 |
August | 0.00 | 0.00 | 0.161643E+11 | 0.103090E+11 | 49606.16 | 04-AUG-07:02 | 25191.87 | 0.00 |
September | 0.00 | 0.00 | 0.754283E+10 | 0.604185E+10 | 36557.87 | 11-SEP-07:03 | 20338.17 | 0.00 |
October | 0.00 | 0.00 | 41524702.85 | 39798503.74 | 4448.15 | 20-OCT-15:00 | 4339.13 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.584710E+11 | 0.389002E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.178686E+11 | 0.110864E+11 | 49606.16 | 25778.62 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 1050323.69 | 807637.02 | 1667.80 | 19-MAR-17:10 | 1278.58 | 0.00 |
April | 0.00 | 0.00 | 0.996685E+09 | 0.707667E+09 | 24652.50 | 16-APR-19:40 | 16164.64 | 0.00 |
May | 0.00 | 0.00 | 0.185986E+10 | 0.130986E+10 | 24846.97 | 29-MAY-17:03 | 14323.25 | 0.00 |
June | 0.00 | 0.00 | 0.769358E+10 | 0.527231E+10 | 25653.96 | 27-JUN-07:03 | 14369.33 | 0.00 |
July | 0.00 | 0.00 | 0.110118E+11 | 0.696938E+10 | 25667.58 | 26-JUL-22:33 | 12765.58 | 0.00 |
August | 0.00 | 0.00 | 0.979430E+10 | 0.632362E+10 | 25776.75 | 28-AUG-20:03 | 11363.45 | 0.00 |
September | 0.00 | 0.00 | 0.475009E+10 | 0.381830E+10 | 24841.02 | 11-SEP-22:44 | 12810.70 | 0.00 |
October | 0.00 | 0.00 | 43951120.59 | 41541929.88 | 3051.54 | 20-OCT-15:00 | 3015.30 | 0.00 |
November | 0.00 | 0.00 | 3826783.54 | 3235422.78 | 1356.99 | 07-NOV-21:30 | 1009.67 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.361552E+11 | 0.244467E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.110118E+11 | 0.696938E+10 | 25776.75 | 16164.64 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3 COOLING COIL
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.670496E+09 | 0.470892E+09 | 9726.80 | 18-APR-14:00 | 6796.31 | 0.00 |
May | 0.00 | 0.00 | 0.126307E+10 | 0.906801E+09 | 9742.38 | 31-MAY-13:00 | 7755.50 | 0.00 |
June | 0.00 | 0.00 | 0.556326E+10 | 0.380210E+10 | 26003.74 | 26-JUN-06:02 | 12287.99 | 0.00 |
July | 0.00 | 0.00 | 0.762816E+10 | 0.488665E+10 | 25738.47 | 27-JUL-06:03 | 11513.64 | 0.00 |
August | 0.00 | 0.00 | 0.747167E+10 | 0.491466E+10 | 26636.13 | 04-AUG-06:02 | 13289.09 | 0.00 |
September | 0.00 | 0.00 | 0.333489E+10 | 0.274830E+10 | 24570.12 | 11-SEP-06:03 | 14185.20 | 0.00 |
October | 0.00 | 0.00 | 28520885.89 | 27449210.21 | 2698.05 | 20-OCT-15:00 | 2669.20 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.259601E+11 | 0.177569E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.762816E+10 | 0.491466E+10 | 26636.13 | 14185.20 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4 COOLING COIL
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.650531E+09 | 0.455945E+09 | 9632.14 | 18-APR-14:00 | 6722.70 | 0.00 |
May | 0.00 | 0.00 | 0.120456E+10 | 0.865336E+09 | 9675.19 | 31-MAY-13:00 | 7698.40 | 0.00 |
June | 0.00 | 0.00 | 0.553573E+10 | 0.378299E+10 | 26072.83 | 26-JUN-06:02 | 12329.77 | 0.00 |
July | 0.00 | 0.00 | 0.762127E+10 | 0.488231E+10 | 25806.20 | 27-JUL-06:03 | 11544.72 | 0.00 |
August | 0.00 | 0.00 | 0.744441E+10 | 0.489686E+10 | 26709.71 | 04-AUG-06:02 | 13345.83 | 0.00 |
September | 0.00 | 0.00 | 0.331952E+10 | 0.273439E+10 | 24635.54 | 11-SEP-06:03 | 14232.68 | 0.00 |
October | 0.00 | 0.00 | 25134915.66 | 24315948.81 | 2554.90 | 20-OCT-15:00 | 2528.26 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.258012E+11 | 0.176421E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.762127E+10 | 0.489686E+10 | 26709.71 | 14232.68 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5 COOLING COIL
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.608106E+09 | 0.423949E+09 | 9356.86 | 18-APR-14:00 | 6502.63 | 0.00 |
May | 0.00 | 0.00 | 0.109385E+10 | 0.786032E+09 | 9439.28 | 31-MAY-13:00 | 7492.05 | 0.00 |
June | 0.00 | 0.00 | 0.533772E+10 | 0.363934E+10 | 25881.56 | 26-JUN-06:02 | 12208.09 | 0.00 |
July | 0.00 | 0.00 | 0.737407E+10 | 0.471339E+10 | 25618.62 | 27-JUL-06:03 | 11418.31 | 0.00 |
August | 0.00 | 0.00 | 0.719669E+10 | 0.472558E+10 | 26507.40 | 04-AUG-06:02 | 13094.84 | 0.00 |
September | 0.00 | 0.00 | 0.320944E+10 | 0.263989E+10 | 23658.11 | 11-SEP-06:03 | 13627.42 | 0.00 |
October | 0.00 | 0.00 | 20338031.59 | 19772031.59 | 2308.05 | 20-OCT-15:00 | 2281.94 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.248402E+11 | 0.169480E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.737407E+10 | 0.472558E+10 | 26507.40 | 13627.42 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6 COOLING COIL
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.102742E+10 | 0.694878E+09 | 17431.92 | 18-APR-14:20 | 11787.98 | 0.00 |
May | 0.00 | 0.00 | 0.179592E+10 | 0.126539E+10 | 17460.06 | 31-MAY-13:00 | 13472.66 | 0.00 |
June | 0.00 | 0.00 | 0.938430E+10 | 0.627251E+10 | 46712.81 | 26-JUN-07:03 | 26940.08 | 0.00 |
July | 0.00 | 0.00 | 0.131583E+11 | 0.816608E+10 | 46327.94 | 07-JUL-07:03 | 20788.34 | 0.00 |
August | 0.00 | 0.00 | 0.127061E+11 | 0.812861E+10 | 47356.31 | 04-AUG-07:02 | 24851.52 | 0.00 |
September | 0.00 | 0.00 | 0.570771E+10 | 0.458633E+10 | 44659.81 | 11-SEP-07:03 | 25341.60 | 0.00 |
October | 0.00 | 0.00 | 32953492.11 | 31333121.62 | 4275.71 | 20-OCT-15:00 | 4132.89 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.438128E+11 | 0.291451E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.131583E+11 | 0.816608E+10 | 47356.31 | 26940.08 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7 COOLING COIL
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.515192E+09 | 0.348468E+09 | 8925.99 | 18-APR-14:20 | 6038.66 | 0.00 |
May | 0.00 | 0.00 | 0.884663E+09 | 0.625232E+09 | 8953.79 | 31-MAY-13:00 | 6909.49 | 0.00 |
June | 0.00 | 0.00 | 0.478716E+10 | 0.320455E+10 | 24039.63 | 26-JUN-07:03 | 13859.72 | 0.00 |
July | 0.00 | 0.00 | 0.672423E+10 | 0.418203E+10 | 23826.31 | 02-JUL-08:62 | 13385.03 | 0.00 |
August | 0.00 | 0.00 | 0.649034E+10 | 0.416259E+10 | 24358.53 | 04-AUG-07:02 | 12790.50 | 0.00 |
September | 0.00 | 0.00 | 0.292435E+10 | 0.235353E+10 | 21919.45 | 11-SEP-07:03 | 12441.64 | 0.00 |
October | 0.00 | 0.00 | 15100562.31 | 14430000.30 | 2144.64 | 20-OCT-15:00 | 2076.55 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.223410E+11 | 0.148908E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.672423E+10 | 0.418203E+10 | 24358.53 | 13859.72 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8 COOLING COIL
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.498752E+09 | 0.336369E+09 | 8772.93 | 18-APR-14:40 | 5930.68 | 0.00 |
May | 0.00 | 0.00 | 0.842038E+09 | 0.595565E+09 | 8819.68 | 31-MAY-13:00 | 6795.97 | 0.00 |
June | 0.00 | 0.00 | 0.471158E+10 | 0.314960E+10 | 23911.07 | 26-JUN-07:03 | 13738.07 | 0.00 |
July | 0.00 | 0.00 | 0.663254E+10 | 0.411951E+10 | 23703.69 | 02-JUL-08:62 | 13299.32 | 0.00 |
August | 0.00 | 0.00 | 0.640472E+10 | 0.410312E+10 | 24234.50 | 04-AUG-07:02 | 12675.35 | 0.00 |
September | 0.00 | 0.00 | 0.288453E+10 | 0.231967E+10 | 21107.11 | 11-SEP-07:03 | 11956.69 | 0.00 |
October | 0.00 | 0.00 | 14031510.59 | 13417949.20 | 2072.86 | 20-OCT-15:00 | 2005.70 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.219882E+11 | 0.146372E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.663254E+10 | 0.411951E+10 | 24234.50 | 13738.07 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9 COOLING COIL
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.458520E+09 | 0.306895E+09 | 8394.13 | 18-APR-14:40 | 5636.70 | 0.00 |
May | 0.00 | 0.00 | 0.750836E+09 | 0.531461E+09 | 8549.40 | 31-MAY-13:00 | 6559.58 | 0.00 |
June | 0.00 | 0.00 | 0.452958E+10 | 0.301730E+10 | 23768.23 | 26-JUN-07:03 | 13492.46 | 0.00 |
July | 0.00 | 0.00 | 0.642083E+10 | 0.397631E+10 | 23581.42 | 02-JUL-08:62 | 13178.05 | 0.00 |
August | 0.00 | 0.00 | 0.620705E+10 | 0.396702E+10 | 24104.17 | 04-AUG-07:02 | 12476.12 | 0.00 |
September | 0.00 | 0.00 | 0.279815E+10 | 0.224483E+10 | 18423.60 | 11-SEP-07:03 | 10361.43 | 0.00 |
October | 0.00 | 0.00 | 11336289.69 | 10840864.72 | 1896.42 | 20-OCT-15:00 | 1830.33 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.211763E+11 | 0.140547E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.642083E+10 | 0.397631E+10 | 24104.17 | 13492.46 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10 COOLING COIL
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.425938E+09 | 0.283763E+09 | 8169.31 | 18-APR-14:10 | 5437.83 | 0.00 |
May | 0.00 | 0.00 | 0.664450E+09 | 0.473995E+09 | 8837.76 | 31-MAY-13:00 | 6782.13 | 0.00 |
June | 0.00 | 0.00 | 0.442526E+10 | 0.295965E+10 | 19975.56 | 26-JUN-07:03 | 10181.26 | 0.00 |
July | 0.00 | 0.00 | 0.634571E+10 | 0.397034E+10 | 28350.05 | 04-JUL-08:62 | 14590.54 | 0.00 |
August | 0.00 | 0.00 | 0.614558E+10 | 0.396970E+10 | 29651.01 | 04-AUG-07:02 | 13131.77 | 0.00 |
September | 0.00 | 0.00 | 0.284789E+10 | 0.229418E+10 | 12114.87 | 06-SEP-14:20 | 9376.68 | 0.00 |
October | 0.00 | 0.00 | 8240781.00 | 7956346.95 | 1723.19 | 20-OCT-15:00 | 1675.21 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.208631E+11 | 0.139596E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.634571E+10 | 0.397034E+10 | 29651.01 | 14590.54 | 0.00 |
Report: FanReportMonthly
For: PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.226976E+10 | 0.52 | 2074.32 | 01-JAN-08:61 | 0.92 |
February | 0.191101E+10 | 0.50 | 2074.32 | 01-FEB-08:61 | 0.93 |
March | 0.187117E+10 | 0.44 | 2074.32 | 01-MAR-08:61 | 0.92 |
April | 0.163603E+10 | 0.41 | 2074.32 | 01-APR-07:01 | 0.92 |
May | 0.151639E+10 | 0.38 | 2074.32 | 01-MAY-07:01 | 0.92 |
June | 0.147122E+10 | 0.38 | 2074.32 | 26-JUN-07:03 | 0.90 |
July | 0.151194E+10 | 0.37 | 2074.32 | 04-JUL-07:02 | 0.91 |
August | 0.152212E+10 | 0.38 | 2074.32 | 03-AUG-07:02 | 0.90 |
September | 0.147397E+10 | 0.38 | 2074.32 | 29-SEP-07:01 | 0.92 |
October | 0.159261E+10 | 0.39 | 2074.32 | 06-OCT-07:01 | 0.92 |
November | 0.179010E+10 | 0.43 | 2074.32 | 10-NOV-08:61 | 0.92 |
December | 0.211715E+10 | 0.49 | 2074.32 | 01-DEC-08:61 | 0.92 |
Annual Sum or Average | 0.206835E+11 | 0.42 | |||
Minimum of Months | 0.147122E+10 | 0.37 | 2074.32 | 0.90 | |
Maximum of Months | 0.226976E+10 | 0.52 | 2074.32 | 0.93 |
Report: FanReportMonthly
For: PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.935011E+09 | 0.47 | 1163.80 | 01-JAN-08:61 | 0.95 |
February | 0.782004E+09 | 0.40 | 1163.80 | 01-FEB-08:61 | 0.96 |
March | 0.771243E+09 | 0.36 | 1163.80 | 01-MAR-08:61 | 0.96 |
April | 0.696251E+09 | 0.34 | 1163.80 | 01-APR-07:01 | 0.95 |
May | 0.762576E+09 | 0.38 | 1102.26 | 02-MAY-07:01 | 0.93 |
June | 0.737474E+09 | 0.38 | 1163.80 | 26-JUN-07:03 | 0.94 |
July | 0.758381E+09 | 0.37 | 1163.80 | 03-JUL-07:03 | 0.94 |
August | 0.791396E+09 | 0.38 | 1163.80 | 03-AUG-07:02 | 0.94 |
September | 0.716815E+09 | 0.37 | 1071.25 | 30-SEP-07:01 | 0.92 |
October | 0.681279E+09 | 0.34 | 1163.80 | 27-OCT-07:01 | 0.95 |
November | 0.739137E+09 | 0.37 | 1163.80 | 10-NOV-08:61 | 0.95 |
December | 0.861557E+09 | 0.40 | 1163.80 | 01-DEC-08:61 | 0.95 |
Annual Sum or Average | 0.923312E+10 | 0.38 | |||
Minimum of Months | 0.681279E+09 | 0.34 | 1071.25 | 0.92 | |
Maximum of Months | 0.935011E+09 | 0.47 | 1163.80 | 0.96 |
Report: FanReportMonthly
For: PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.100472E+10 | 0.40 | 1170.80 | 01-JAN-08:61 | 0.95 |
February | 0.844362E+09 | 0.38 | 1170.80 | 01-FEB-07:01 | 0.96 |
March | 0.837128E+09 | 0.36 | 1170.80 | 01-MAR-07:01 | 0.96 |
April | 0.727131E+09 | 0.33 | 1170.80 | 01-APR-06:01 | 0.95 |
May | 0.687653E+09 | 0.31 | 1010.37 | 02-MAY-06:02 | 0.89 |
June | 0.669480E+09 | 0.31 | 1170.80 | 26-JUN-06:02 | 0.93 |
July | 0.677797E+09 | 0.31 | 1170.80 | 02-JUL-07:03 | 0.94 |
August | 0.698044E+09 | 0.32 | 1170.80 | 03-AUG-06:02 | 0.93 |
September | 0.660869E+09 | 0.31 | 1170.80 | 11-SEP-06:03 | 0.94 |
October | 0.707436E+09 | 0.32 | 1035.36 | 08-OCT-07:02 | 0.90 |
November | 0.795896E+09 | 0.35 | 1170.80 | 11-NOV-08:61 | 0.96 |
December | 0.930790E+09 | 0.38 | 1170.80 | 01-DEC-07:01 | 0.95 |
Annual Sum or Average | 0.924130E+10 | 0.34 | |||
Minimum of Months | 0.660869E+09 | 0.31 | 1010.37 | 0.89 | |
Maximum of Months | 0.100472E+10 | 0.40 | 1170.80 | 0.96 |
Report: FanReportMonthly
For: PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.100806E+10 | 0.40 | 1174.93 | 01-JAN-08:61 | 0.95 |
February | 0.847888E+09 | 0.39 | 1174.93 | 01-FEB-07:01 | 0.96 |
March | 0.841561E+09 | 0.36 | 1174.93 | 01-MAR-07:01 | 0.96 |
April | 0.731290E+09 | 0.33 | 1174.93 | 01-APR-06:01 | 0.95 |
May | 0.690534E+09 | 0.31 | 1101.69 | 02-MAY-06:02 | 0.93 |
June | 0.671908E+09 | 0.31 | 1174.93 | 26-JUN-06:02 | 0.93 |
July | 0.680119E+09 | 0.31 | 1174.93 | 02-JUL-07:03 | 0.94 |
August | 0.700372E+09 | 0.32 | 1174.93 | 03-AUG-06:02 | 0.93 |
September | 0.663732E+09 | 0.31 | 1174.93 | 11-SEP-06:03 | 0.94 |
October | 0.713076E+09 | 0.32 | 1125.25 | 08-OCT-07:02 | 0.93 |
November | 0.800385E+09 | 0.35 | 1174.93 | 11-NOV-08:61 | 0.96 |
December | 0.934510E+09 | 0.38 | 1174.93 | 01-DEC-07:01 | 0.95 |
Annual Sum or Average | 0.928343E+10 | 0.34 | |||
Minimum of Months | 0.663732E+09 | 0.31 | 1101.69 | 0.93 | |
Maximum of Months | 0.100806E+10 | 0.40 | 1174.93 | 0.96 |
Report: FanReportMonthly
For: PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.101597E+10 | 0.41 | 1163.33 | 01-JAN-08:61 | 0.95 |
February | 0.853233E+09 | 0.39 | 1163.33 | 01-FEB-07:01 | 0.96 |
March | 0.844710E+09 | 0.36 | 1163.33 | 01-MAR-07:01 | 0.96 |
April | 0.731054E+09 | 0.33 | 1163.33 | 01-APR-06:01 | 0.95 |
May | 0.684709E+09 | 0.31 | 1163.33 | 02-MAY-06:02 | 0.95 |
June | 0.665327E+09 | 0.31 | 1163.33 | 26-JUN-06:02 | 0.93 |
July | 0.673157E+09 | 0.31 | 1163.33 | 02-JUL-07:03 | 0.94 |
August | 0.693089E+09 | 0.32 | 1163.33 | 03-AUG-06:02 | 0.93 |
September | 0.658267E+09 | 0.31 | 1118.09 | 11-SEP-06:03 | 0.92 |
October | 0.712115E+09 | 0.32 | 1163.33 | 08-OCT-07:02 | 0.95 |
November | 0.802905E+09 | 0.35 | 1163.33 | 10-NOV-07:02 | 0.95 |
December | 0.940705E+09 | 0.39 | 1163.33 | 01-DEC-07:01 | 0.95 |
Annual Sum or Average | 0.927524E+10 | 0.34 | |||
Minimum of Months | 0.658267E+09 | 0.31 | 1118.09 | 0.92 | |
Maximum of Months | 0.101597E+10 | 0.41 | 1163.33 | 0.96 |
Report: FanReportMonthly
For: PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.164936E+10 | 0.39 | 1973.81 | 01-JAN-09:01 | 0.92 |
February | 0.137983E+10 | 0.37 | 1973.81 | 01-FEB-08:61 | 0.93 |
March | 0.135641E+10 | 0.33 | 1973.81 | 01-MAR-08:61 | 0.92 |
April | 0.116272E+10 | 0.30 | 1973.81 | 01-APR-07:01 | 0.92 |
May | 0.107514E+10 | 0.28 | 1973.81 | 01-MAY-07:01 | 0.92 |
June | 0.104659E+10 | 0.28 | 1973.81 | 26-JUN-07:03 | 0.90 |
July | 0.105572E+10 | 0.27 | 1973.81 | 02-JUL-08:62 | 0.90 |
August | 0.109029E+10 | 0.28 | 1973.81 | 03-AUG-07:02 | 0.90 |
September | 0.103447E+10 | 0.28 | 1973.81 | 11-SEP-07:03 | 0.91 |
October | 0.113247E+10 | 0.29 | 1973.81 | 01-OCT-08:61 | 0.92 |
November | 0.128907E+10 | 0.32 | 1973.81 | 05-NOV-08:61 | 0.92 |
December | 0.152164E+10 | 0.36 | 1973.81 | 01-DEC-08:61 | 0.92 |
Annual Sum or Average | 0.147937E+11 | 0.31 | |||
Minimum of Months | 0.103447E+10 | 0.27 | 1973.81 | 0.90 | |
Maximum of Months | 0.164936E+10 | 0.39 | 1973.81 | 0.93 |
Report: FanReportMonthly
For: PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.886907E+09 | 0.40 | 1054.00 | 01-JAN-09:01 | 0.95 |
February | 0.741857E+09 | 0.38 | 1054.00 | 01-FEB-08:61 | 0.96 |
March | 0.728572E+09 | 0.34 | 1054.00 | 01-MAR-08:61 | 0.96 |
April | 0.623429E+09 | 0.31 | 1054.00 | 01-APR-07:01 | 0.95 |
May | 0.574496E+09 | 0.29 | 1054.00 | 01-MAY-07:01 | 0.95 |
June | 0.559047E+09 | 0.29 | 1054.00 | 26-JUN-07:03 | 0.94 |
July | 0.563719E+09 | 0.28 | 1054.00 | 02-JUL-08:62 | 0.94 |
August | 0.582264E+09 | 0.29 | 1054.00 | 03-AUG-07:02 | 0.93 |
September | 0.552646E+09 | 0.29 | 1054.00 | 29-SEP-07:01 | 0.95 |
October | 0.605941E+09 | 0.30 | 1054.00 | 01-OCT-08:61 | 0.95 |
November | 0.691971E+09 | 0.34 | 1054.00 | 05-NOV-08:61 | 0.95 |
December | 0.817827E+09 | 0.38 | 1054.00 | 01-DEC-08:61 | 0.95 |
Annual Sum or Average | 0.792868E+10 | 0.32 | |||
Minimum of Months | 0.552646E+09 | 0.28 | 1054.00 | 0.93 | |
Maximum of Months | 0.886907E+09 | 0.40 | 1054.00 | 0.96 |
Report: FanReportMonthly
For: PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.883682E+09 | 0.40 | 1046.55 | 01-JAN-09:01 | 0.95 |
February | 0.739121E+09 | 0.38 | 1046.55 | 01-FEB-08:61 | 0.96 |
March | 0.725978E+09 | 0.34 | 1046.55 | 01-MAR-08:61 | 0.96 |
April | 0.621062E+09 | 0.31 | 1046.55 | 01-APR-07:01 | 0.95 |
May | 0.571019E+09 | 0.29 | 1046.55 | 01-MAY-07:01 | 0.95 |
June | 0.555215E+09 | 0.29 | 1046.55 | 26-JUN-07:03 | 0.94 |
July | 0.559645E+09 | 0.28 | 1046.55 | 02-JUL-08:62 | 0.94 |
August | 0.578111E+09 | 0.29 | 1046.55 | 03-AUG-07:02 | 0.93 |
September | 0.549159E+09 | 0.29 | 1046.55 | 29-SEP-07:01 | 0.95 |
October | 0.603475E+09 | 0.30 | 1046.55 | 01-OCT-08:61 | 0.95 |
November | 0.689469E+09 | 0.34 | 1046.55 | 05-NOV-08:61 | 0.95 |
December | 0.814755E+09 | 0.38 | 1046.55 | 01-DEC-08:61 | 0.95 |
Annual Sum or Average | 0.789069E+10 | 0.33 | |||
Minimum of Months | 0.549159E+09 | 0.28 | 1046.55 | 0.93 | |
Maximum of Months | 0.883682E+09 | 0.40 | 1046.55 | 0.96 |
Report: FanReportMonthly
For: PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.890081E+09 | 0.42 | 1039.34 | 01-JAN-09:01 | 0.95 |
February | 0.745173E+09 | 0.40 | 1039.34 | 01-FEB-08:61 | 0.96 |
March | 0.731150E+09 | 0.35 | 1039.34 | 01-MAR-08:61 | 0.96 |
April | 0.624343E+09 | 0.32 | 1039.34 | 01-APR-07:01 | 0.95 |
May | 0.569146E+09 | 0.29 | 1039.34 | 01-MAY-07:01 | 0.95 |
June | 0.551734E+09 | 0.29 | 1039.34 | 26-JUN-07:03 | 0.94 |
July | 0.555454E+09 | 0.28 | 1039.34 | 02-JUL-08:62 | 0.94 |
August | 0.574027E+09 | 0.29 | 1039.34 | 03-AUG-07:02 | 0.93 |
September | 0.546624E+09 | 0.29 | 1039.34 | 28-SEP-07:01 | 0.95 |
October | 0.605053E+09 | 0.30 | 1039.34 | 01-OCT-08:61 | 0.95 |
November | 0.693297E+09 | 0.34 | 1039.34 | 01-NOV-07:01 | 0.95 |
December | 0.820471E+09 | 0.39 | 1039.34 | 01-DEC-08:61 | 0.95 |
Annual Sum or Average | 0.790655E+10 | 0.33 | |||
Minimum of Months | 0.546624E+09 | 0.28 | 1039.34 | 0.93 | |
Maximum of Months | 0.890081E+09 | 0.42 | 1039.34 | 0.96 |
Report: FanReportMonthly
For: PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.114736E+10 | 0.57 | 1268.78 | 01-JAN-09:01 | 0.95 |
February | 0.952981E+09 | 0.49 | 1268.78 | 01-FEB-08:61 | 0.96 |
March | 0.924240E+09 | 0.40 | 1268.78 | 01-MAR-08:61 | 0.96 |
April | 0.781573E+09 | 0.33 | 1268.78 | 01-APR-07:01 | 0.95 |
May | 0.701835E+09 | 0.29 | 1268.78 | 01-MAY-07:01 | 0.95 |
June | 0.673728E+09 | 0.29 | 1268.78 | 03-JUN-07:02 | 0.95 |
July | 0.674332E+09 | 0.28 | 1268.78 | 04-JUL-08:62 | 0.94 |
August | 0.696124E+09 | 0.29 | 1268.78 | 03-AUG-07:02 | 0.93 |
September | 0.669608E+09 | 0.29 | 1268.78 | 27-SEP-07:01 | 0.95 |
October | 0.746683E+09 | 0.31 | 1268.78 | 01-OCT-08:61 | 0.95 |
November | 0.866956E+09 | 0.39 | 1268.78 | 01-NOV-07:01 | 0.95 |
December | 0.103787E+10 | 0.47 | 1268.78 | 01-DEC-08:61 | 0.95 |
Annual Sum or Average | 0.987330E+10 | 0.37 | |||
Minimum of Months | 0.669608E+09 | 0.28 | 1268.78 | 0.93 | |
Maximum of Months | 0.114736E+10 | 0.57 | 1268.78 | 0.96 |
Report: ZoneTemperatureOscillationReportMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.226976E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.191101E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.187117E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.203475E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.218169E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.470780E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.592255E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.553850E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.342752E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.160430E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.179010E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.211715E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.353763E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.160430E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.592255E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.935011E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.782004E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.771534E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.945653E+09 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.122669E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.261971E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.337402E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.314352E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.189050E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.693242E+09 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.740193E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.861557E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.179836E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.693242E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.337402E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_3:3
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.100472E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.844362E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.837128E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.897560E+09 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.101301E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.204710E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.252559E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.252337E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.151000E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.715261E+09 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.795896E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.930790E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.156448E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.715261E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.252559E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_4:4
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.100806E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.847888E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.841561E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.897114E+09 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.100170E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.204351E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.252711E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.252041E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.150947E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.719996E+09 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.800385E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.934510E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.156517E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.719996E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.252711E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_5:5
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.101597E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.853233E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.844710E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.886759E+09 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.968715E+09 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.199082E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.246401E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.245651E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.147781E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.717746E+09 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.802905E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.940705E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.154199E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.717746E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.246401E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_6:6
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.164936E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.137983E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.135641E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.143006E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.155165E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.341548E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.430186E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.425451E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.251524E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.114179E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.128907E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.152164E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.258069E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.114179E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.430186E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_7:7
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.886907E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.741857E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.728572E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.755296E+09 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.805497E+09 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.174713E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.219442E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.217114E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.129796E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.610142E+09 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.691971E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.817827E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.134487E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.610142E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.219442E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_8:8
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.883682E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.739121E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.725978E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.748972E+09 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.791436E+09 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.172518E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.216891E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.214674E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.128475E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.607385E+09 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.689469E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.814755E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.133264E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.607385E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.216891E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_9:9
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.890081E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.745173E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.731150E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.742675E+09 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.766859E+09 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.167890E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.211610E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.209673E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.126136E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.608225E+09 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.693297E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.820471E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.131510E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.608225E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.211610E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_10:10
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.114736E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.952981E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.924240E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.895127E+09 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.881164E+09 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.180582E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.225800E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.223818E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.141418E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.749015E+09 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.866956E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.103787E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.151709E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.749015E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.225800E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.226976E+10 | 0.00 | 0.392177E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.191101E+10 | 0.00 | 0.281627E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.187117E+10 | 0.00 | 0.185329E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.163603E+10 | 0.152756E+10 | 0.922808E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.151639E+10 | 0.253264E+10 | 0.563287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.147122E+10 | 0.127936E+11 | 95594985.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.151194E+10 | 0.178686E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.152212E+10 | 0.161643E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.147397E+10 | 0.754283E+10 | 0.672847E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.159261E+10 | 41524702.85 | 0.452852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.179010E+10 | 0.00 | 0.173263E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.211715E+10 | 0.00 | 0.311865E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.206835E+11 | 0.584710E+11 | 0.149514E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.147122E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.226976E+10 | 0.178686E+11 | 0.392177E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.935011E+09 | 0.00 | 0.143230E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.782004E+09 | 0.00 | 0.996187E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.771243E+09 | 1050323.69 | 0.596525E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.696251E+09 | 0.965371E+09 | 0.271657E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.762576E+09 | 0.178355E+10 | 74815021.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.737474E+09 | 0.743801E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.758381E+09 | 0.105116E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.791396E+09 | 0.948634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.716815E+09 | 0.451031E+10 | 61536014.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.681279E+09 | 43951120.59 | 0.832749E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.739137E+09 | 3826783.54 | 0.577605E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.861557E+09 | 0.00 | 0.110772E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.923312E+10 | 0.347440E+11 | 0.507890E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.681279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.935011E+09 | 0.105116E+11 | 0.143230E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_3:3
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.100472E+10 | 0.00 | 0.156812E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.844362E+09 | 0.00 | 0.110652E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.837128E+09 | 0.00 | 0.700184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.727131E+09 | 0.670496E+09 | 0.334094E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.687653E+09 | 0.126307E+10 | 0.151631E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.669480E+09 | 0.556326E+10 | 2588845.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.677797E+09 | 0.762816E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.698044E+09 | 0.747167E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.660869E+09 | 0.333489E+10 | 0.146749E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.707436E+09 | 28520885.89 | 0.142476E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.795896E+09 | 0.00 | 0.664124E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.930790E+09 | 0.00 | 0.123021E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.924130E+10 | 0.259601E+11 | 0.577582E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.660869E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.100472E+10 | 0.762816E+10 | 0.156812E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_4:4
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.100806E+10 | 0.00 | 0.159641E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.847888E+09 | 0.00 | 0.112936E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.841561E+09 | 0.00 | 0.721118E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.731290E+09 | 0.650531E+09 | 0.348414E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.690534E+09 | 0.120456E+10 | 0.176752E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.671908E+09 | 0.553573E+10 | 11797368.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.680119E+09 | 0.762127E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.700372E+09 | 0.744441E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.663732E+09 | 0.331952E+10 | 0.175777E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.713076E+09 | 25134915.66 | 0.160595E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.800385E+09 | 0.00 | 0.685334E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.934510E+09 | 0.00 | 0.125514E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.928343E+10 | 0.258012E+11 | 0.593280E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.663732E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.100806E+10 | 0.762127E+10 | 0.159641E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_5:5
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.101597E+10 | 0.00 | 0.164087E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.853233E+09 | 0.00 | 0.116598E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.844710E+09 | 0.00 | 0.758226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.731054E+09 | 0.608106E+09 | 0.373288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.684709E+09 | 0.109385E+10 | 0.219833E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.665327E+09 | 0.533772E+10 | 28333898.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.673157E+09 | 0.737407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.693089E+09 | 0.719669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.658267E+09 | 0.320944E+10 | 0.226417E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.712115E+09 | 20338031.59 | 0.185787E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.802905E+09 | 0.00 | 0.718359E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.940705E+09 | 0.00 | 0.129648E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.927524E+10 | 0.248402E+11 | 0.618645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.658267E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.101597E+10 | 0.737407E+10 | 0.164087E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_6:6
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.164936E+10 | 0.00 | 0.312478E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.137983E+10 | 0.00 | 0.223044E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.135641E+10 | 0.00 | 0.147632E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.116272E+10 | 0.102742E+10 | 0.738467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.107514E+10 | 0.179592E+10 | 0.491257E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.104659E+10 | 0.938430E+10 | 0.112061E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.105572E+10 | 0.131583E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.109029E+10 | 0.127061E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.103447E+10 | 0.570771E+10 | 0.569674E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.113247E+10 | 32953492.11 | 0.412835E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.128907E+10 | 0.00 | 0.140525E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.152164E+10 | 0.00 | 0.248812E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.147937E+11 | 0.438128E+11 | 0.119935E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.103447E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.164936E+10 | 0.131583E+11 | 0.312478E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_7:7
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.886907E+09 | 0.00 | 0.161857E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.741857E+09 | 0.00 | 0.115837E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.728572E+09 | 0.00 | 0.770635E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.623429E+09 | 0.515192E+09 | 0.387580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.574496E+09 | 0.884663E+09 | 0.268386E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.559047E+09 | 0.478716E+10 | 62817540.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.563719E+09 | 0.672423E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.582264E+09 | 0.649034E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.552646E+09 | 0.292435E+10 | 0.301133E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.605941E+09 | 15100562.31 | 0.215593E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.691971E+09 | 0.00 | 0.731692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.817827E+09 | 0.00 | 0.129035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.792868E+10 | 0.223410E+11 | 0.623602E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.552646E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.886907E+09 | 0.672423E+10 | 0.161857E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_8:8
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.883682E+09 | 0.00 | 0.162566E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.739121E+09 | 0.00 | 0.116538E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.725978E+09 | 0.00 | 0.779904E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.621062E+09 | 0.498752E+09 | 0.396014E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.571019E+09 | 0.842038E+09 | 0.296593E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.555215E+09 | 0.471158E+10 | 74614333.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.559645E+09 | 0.663254E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.578111E+09 | 0.640472E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.549159E+09 | 0.288453E+10 | 0.321808E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.603475E+09 | 14031510.59 | 0.223730E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.689469E+09 | 0.00 | 0.740044E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.814755E+09 | 0.00 | 0.129774E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.789069E+10 | 0.219882E+11 | 0.629777E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.549159E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.883682E+09 | 0.663254E+10 | 0.162566E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_9:9
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.890081E+09 | 0.00 | 0.167245E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.745173E+09 | 0.00 | 0.120987E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.731150E+09 | 0.00 | 0.825461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.624343E+09 | 0.458520E+09 | 0.431454E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.569146E+09 | 0.750836E+09 | 0.398682E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.551734E+09 | 0.452958E+10 | 0.111793E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.555454E+09 | 0.642083E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.574027E+09 | 0.620705E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.546624E+09 | 0.279815E+10 | 0.385540E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.605053E+09 | 11336289.69 | 0.251141E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.693297E+09 | 0.00 | 0.776926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.820471E+09 | 0.00 | 0.134353E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.790655E+10 | 0.211763E+11 | 0.660043E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.546624E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.890081E+09 | 0.642083E+10 | 0.167245E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_10:10
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.114736E+10 | 0.00 | 0.209980E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.952981E+09 | 0.00 | 0.153146E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.924240E+09 | 0.00 | 0.107185E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.781573E+09 | 0.425938E+09 | 0.583860E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.701835E+09 | 0.664450E+09 | 0.794459E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.673728E+09 | 0.442526E+10 | 0.236174E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.674332E+09 | 0.634571E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.696124E+09 | 0.614558E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.669608E+09 | 0.284789E+10 | 0.565040E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.746683E+09 | 8240781.00 | 0.327635E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.866956E+09 | 0.00 | 0.966586E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.103787E+10 | 0.00 | 0.166136E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.987330E+10 | 0.208631E+11 | 0.840212E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.669608E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.114736E+10 | 0.634571E+10 | 0.209980E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.226976E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.191101E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.187117E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.163603E+10 | 0.00 | 0.00 | 0.00 | 0.398723E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.151639E+10 | 0.00 | 0.00 | 0.00 | 0.665296E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.147122E+10 | 0.00 | 0.00 | 0.00 | 0.323658E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.151194E+10 | 0.00 | 0.00 | 0.00 | 0.441061E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.152212E+10 | 0.00 | 0.00 | 0.00 | 0.401638E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.147397E+10 | 0.00 | 0.00 | 0.00 | 0.195355E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.159261E+10 | 0.00 | 0.00 | 0.00 | 11685102.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.179010E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.211715E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.206835E+11 | 0.00 | 0.00 | 0.00 | 0.146928E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.147122E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.226976E+10 | 0.00 | 0.00 | 0.00 | 0.441061E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.935011E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.782004E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.771243E+09 | 0.00 | 0.00 | 0.00 | 290116.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.696251E+09 | 0.00 | 0.00 | 0.00 | 0.249401E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.762576E+09 | 0.00 | 0.00 | 0.00 | 0.464119E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.737474E+09 | 0.00 | 0.00 | 0.00 | 0.188223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.758381E+09 | 0.00 | 0.00 | 0.00 | 0.261564E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.791396E+09 | 0.00 | 0.00 | 0.00 | 0.235212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.716815E+09 | 0.00 | 0.00 | 0.00 | 0.117369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.681279E+09 | 0.00 | 0.00 | 0.00 | 11963233.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.739137E+09 | 0.00 | 0.00 | 0.00 | 1055769.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.861557E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.923312E+10 | 0.00 | 0.00 | 0.00 | 0.875051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.681279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.935011E+09 | 0.00 | 0.00 | 0.00 | 0.261564E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_3:3
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.100472E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.844362E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.837128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.727131E+09 | 0.00 | 0.00 | 0.00 | 0.170430E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.687653E+09 | 0.00 | 0.00 | 0.00 | 0.325358E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.669480E+09 | 0.00 | 0.00 | 0.00 | 0.137762E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.677797E+09 | 0.00 | 0.00 | 0.00 | 0.184779E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.698044E+09 | 0.00 | 0.00 | 0.00 | 0.182532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.660869E+09 | 0.00 | 0.00 | 0.00 | 0.849130E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.707436E+09 | 0.00 | 0.00 | 0.00 | 7824879.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.795896E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.930790E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.924130E+10 | 0.00 | 0.00 | 0.00 | 0.640348E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.660869E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.100472E+10 | 0.00 | 0.00 | 0.00 | 0.184779E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_4:4
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.100806E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.847888E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.841561E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.731290E+09 | 0.00 | 0.00 | 0.00 | 0.165824E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.690534E+09 | 0.00 | 0.00 | 0.00 | 0.311165E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.671908E+09 | 0.00 | 0.00 | 0.00 | 0.137161E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.680119E+09 | 0.00 | 0.00 | 0.00 | 0.184699E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.700372E+09 | 0.00 | 0.00 | 0.00 | 0.182004E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.663732E+09 | 0.00 | 0.00 | 0.00 | 0.845740E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.713076E+09 | 0.00 | 0.00 | 0.00 | 6920183.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.800385E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.934510E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.928343E+10 | 0.00 | 0.00 | 0.00 | 0.636828E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.663732E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.100806E+10 | 0.00 | 0.00 | 0.00 | 0.184699E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_5:5
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.101597E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.853233E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.844710E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.731054E+09 | 0.00 | 0.00 | 0.00 | 0.155705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.684709E+09 | 0.00 | 0.00 | 0.00 | 0.284006E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.665327E+09 | 0.00 | 0.00 | 0.00 | 0.132550E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.673157E+09 | 0.00 | 0.00 | 0.00 | 0.179085E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.693089E+09 | 0.00 | 0.00 | 0.00 | 0.176342E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.658267E+09 | 0.00 | 0.00 | 0.00 | 0.819548E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.712115E+09 | 0.00 | 0.00 | 0.00 | 5630947.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.802905E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.940705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.927524E+10 | 0.00 | 0.00 | 0.00 | 0.614466E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.658267E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.101597E+10 | 0.00 | 0.00 | 0.00 | 0.179085E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_6:6
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.164936E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.137983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.135641E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.116272E+10 | 0.00 | 0.00 | 0.00 | 0.267336E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.107514E+10 | 0.00 | 0.00 | 0.00 | 0.476514E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.104659E+10 | 0.00 | 0.00 | 0.00 | 0.236889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.105572E+10 | 0.00 | 0.00 | 0.00 | 0.324614E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.109029E+10 | 0.00 | 0.00 | 0.00 | 0.316421E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.103447E+10 | 0.00 | 0.00 | 0.00 | 0.148077E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.113247E+10 | 0.00 | 0.00 | 0.00 | 9317280.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.128907E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.152164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.147937E+11 | 0.00 | 0.00 | 0.00 | 0.110132E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.103447E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.164936E+10 | 0.00 | 0.00 | 0.00 | 0.324614E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_7:7
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.886907E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.741857E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.728572E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.623429E+09 | 0.00 | 0.00 | 0.00 | 0.131867E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.574496E+09 | 0.00 | 0.00 | 0.00 | 0.231001E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.559047E+09 | 0.00 | 0.00 | 0.00 | 0.118808E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.563719E+09 | 0.00 | 0.00 | 0.00 | 0.163070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.582264E+09 | 0.00 | 0.00 | 0.00 | 0.158888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.552646E+09 | 0.00 | 0.00 | 0.00 | 0.745318E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.605941E+09 | 0.00 | 0.00 | 0.00 | 4201510.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.691971E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.817827E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.792868E+10 | 0.00 | 0.00 | 0.00 | 0.552004E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.552646E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.886907E+09 | 0.00 | 0.00 | 0.00 | 0.163070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_8:8
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.883682E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.739121E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.725978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.621062E+09 | 0.00 | 0.00 | 0.00 | 0.127911E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.571019E+09 | 0.00 | 0.00 | 0.00 | 0.220418E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.555215E+09 | 0.00 | 0.00 | 0.00 | 0.116997E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.559645E+09 | 0.00 | 0.00 | 0.00 | 0.160927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.578111E+09 | 0.00 | 0.00 | 0.00 | 0.156863E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.549159E+09 | 0.00 | 0.00 | 0.00 | 0.735589E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.603475E+09 | 0.00 | 0.00 | 0.00 | 3909914.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.689469E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.814755E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.789069E+10 | 0.00 | 0.00 | 0.00 | 0.543568E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.549159E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.883682E+09 | 0.00 | 0.00 | 0.00 | 0.160927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_9:9
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.890081E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.745173E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.731150E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.624343E+09 | 0.00 | 0.00 | 0.00 | 0.118332E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.569146E+09 | 0.00 | 0.00 | 0.00 | 0.197712E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.551734E+09 | 0.00 | 0.00 | 0.00 | 0.112717E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.555454E+09 | 0.00 | 0.00 | 0.00 | 0.156064E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.574027E+09 | 0.00 | 0.00 | 0.00 | 0.152271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.546624E+09 | 0.00 | 0.00 | 0.00 | 0.714733E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.605053E+09 | 0.00 | 0.00 | 0.00 | 3172314.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.693297E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.820471E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.790655E+10 | 0.00 | 0.00 | 0.00 | 0.524446E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.546624E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.890081E+09 | 0.00 | 0.00 | 0.00 | 0.156064E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_10:10
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.114736E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.952981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.924240E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.781573E+09 | 0.00 | 0.00 | 0.00 | 0.113555E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.701835E+09 | 0.00 | 0.00 | 0.00 | 0.179330E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.673728E+09 | 0.00 | 0.00 | 0.00 | 0.113209E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.674332E+09 | 0.00 | 0.00 | 0.00 | 0.158367E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.696124E+09 | 0.00 | 0.00 | 0.00 | 0.154205E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.669608E+09 | 0.00 | 0.00 | 0.00 | 0.744576E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.746683E+09 | 0.00 | 0.00 | 0.00 | 2332539.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.866956E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.103787E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.987330E+10 | 0.00 | 0.00 | 0.00 | 0.529760E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.669608E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.114736E+10 | 0.00 | 0.00 | 0.00 | 0.158367E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.831953E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.266521E+11 | 0.00 | 0.00 | 0.52 |
February | 0.261243E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185599E+11 | 0.00 | 0.00 | 0.53 |
March | 0.478081E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120186E+11 | 0.00 | 0.00 | 0.53 |
April | 0.561782E+10 | 0.368599E+09 | 0.00 | 921021.37 | 14737270.33 | 0.526771E+10 | 0.481321E+09 | 0.00 | 0.57 |
May | 0.446252E+10 | 0.351547E+09 | 0.00 | 4394401.71 | 0.00 | 0.122394E+09 | 0.231513E+10 | 0.00 | 0.67 |
June | 0.180150E+10 | 0.319876E+10 | 0.00 | 6474817.29 | 150894.40 | 1713076.63 | 0.210517E+10 | 0.00 | 0.80 |
July | 65667468.58 | 0.432122E+10 | 0.00 | 10367324.03 | 0.00 | 0.00 | 0.245021E+10 | 0.00 | 0.93 |
August | 94700645.13 | 0.356253E+10 | 0.00 | 11565495.84 | 0.00 | 0.00 | 0.343511E+10 | 0.00 | 0.93 |
September | 0.346150E+10 | 0.107653E+10 | 0.00 | 9932866.82 | 0.00 | 52982458.13 | 0.317706E+10 | 0.00 | 0.77 |
October | 0.982259E+10 | 0.00 | 0.00 | 400772.55 | 0.00 | 0.980213E+09 | 0.470245E+09 | 0.00 | 0.54 |
November | 0.566548E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111216E+11 | 0.00 | 0.00 | 0.53 |
December | 0.176612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.217744E+11 | 0.00 | 0.00 | 0.52 |
Annual Sum or Average | 0.409831E+11 | 0.128792E+11 | 0.00 | 44056699.61 | 14888164.73 | 0.965516E+11 | 0.144342E+11 | 0.00 | 0.65 |
Minimum of Months | 65667468.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.52 |
Maximum of Months | 0.982259E+10 | 0.432122E+10 | 0.00 | 11565495.84 | 14737270.33 | 0.266521E+11 | 0.343511E+10 | 0.00 | 0.93 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.725788E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.948690E+10 | 0.00 | 0.00 | 0.39 |
February | 0.134127E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.645650E+10 | 0.00 | 0.00 | 0.39 |
March | 0.258412E+10 | 0.00 | 0.00 | 38329.16 | 0.00 | 0.354542E+10 | 34923014.98 | 0.00 | 0.40 |
April | 0.231941E+10 | 0.191405E+09 | 0.00 | 594063.58 | 912851.45 | 0.161938E+10 | 0.398127E+09 | 0.00 | 0.45 |
May | 0.118879E+10 | 0.210896E+09 | 0.00 | 3486452.87 | 35547.14 | 9588032.50 | 0.225630E+10 | 0.00 | 0.69 |
June | 0.515309E+09 | 0.160122E+10 | 0.00 | 3132733.27 | 0.00 | 0.00 | 0.130192E+10 | 0.00 | 0.75 |
July | 69266.05 | 0.231598E+10 | 0.00 | 3308606.45 | 97310.52 | 0.00 | 0.939772E+09 | 0.00 | 0.84 |
August | 6056740.67 | 0.185821E+10 | 0.00 | 4869520.56 | 0.00 | 0.00 | 0.146989E+10 | 0.00 | 0.90 |
September | 0.100285E+10 | 0.559501E+09 | 0.00 | 4538554.80 | 0.00 | 3094792.18 | 0.195971E+10 | 0.00 | 0.70 |
October | 0.359795E+10 | 0.00 | 0.00 | 690244.78 | 0.00 | 70129919.31 | 0.630072E+09 | 0.00 | 0.44 |
November | 0.244514E+10 | 0.00 | 0.00 | 90604.21 | 0.00 | 0.361421E+10 | 77575109.16 | 0.00 | 0.39 |
December | 0.164351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.691054E+10 | 0.00 | 0.00 | 0.38 |
Annual Sum or Average | 0.173703E+11 | 0.673721E+10 | 0.00 | 20749109.68 | 1045709.10 | 0.317158E+11 | 0.906829E+10 | 0.00 | 0.56 |
Minimum of Months | 69266.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.359795E+10 | 0.231598E+10 | 0.00 | 4869520.56 | 912851.45 | 0.948690E+10 | 0.225630E+10 | 0.00 | 0.90 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.205697E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105733E+11 | 0.00 | 0.00 | 0.41 |
February | 0.797313E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.743065E+10 | 0.00 | 0.00 | 0.41 |
March | 0.201660E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.450213E+10 | 0.00 | 0.00 | 0.42 |
April | 0.226398E+10 | 0.150357E+09 | 0.00 | 272985.26 | 12127409.57 | 0.194301E+10 | 0.177080E+09 | 0.00 | 0.45 |
May | 0.156919E+10 | 0.179600E+09 | 0.00 | 1500076.47 | 4233154.40 | 30577754.33 | 0.103200E+10 | 0.00 | 0.56 |
June | 0.678003E+09 | 0.128674E+10 | 0.00 | 1933786.11 | 71851863.58 | 0.00 | 0.835075E+09 | 0.00 | 0.66 |
July | 42476846.03 | 0.169716E+10 | 0.00 | 2208940.02 | 94096453.59 | 0.00 | 0.781467E+09 | 0.00 | 0.72 |
August | 0.111809E+09 | 0.154860E+10 | 0.00 | 2658077.56 | 61812196.71 | 0.00 | 0.887958E+09 | 0.00 | 0.74 |
September | 0.126918E+10 | 0.490750E+09 | 0.00 | 2339553.07 | 13917456.41 | 33621694.90 | 0.116442E+10 | 0.00 | 0.60 |
October | 0.369948E+10 | 0.00 | 0.00 | 199587.24 | 0.00 | 0.277624E+09 | 0.171390E+09 | 0.00 | 0.43 |
November | 0.195460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.437518E+10 | 0.00 | 0.00 | 0.41 |
December | 0.643431E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.837844E+10 | 0.00 | 0.00 | 0.41 |
Annual Sum or Average | 0.152518E+11 | 0.535320E+10 | 0.00 | 11113005.74 | 0.258039E+09 | 0.375445E+11 | 0.504939E+10 | 0.00 | 0.52 |
Minimum of Months | 42476846.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.369948E+10 | 0.169716E+10 | 0.00 | 2658077.56 | 94096453.59 | 0.105733E+11 | 0.116442E+10 | 0.00 | 0.74 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.175589E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106034E+11 | 0.00 | 0.00 | 0.41 |
February | 0.704097E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.752384E+10 | 0.00 | 0.00 | 0.41 |
March | 0.182472E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.469085E+10 | 0.00 | 0.00 | 0.42 |
April | 0.214958E+10 | 0.147871E+09 | 0.00 | 257206.23 | 13124247.97 | 0.205412E+10 | 0.170113E+09 | 0.00 | 0.45 |
May | 0.161840E+10 | 0.174620E+09 | 0.00 | 1341088.28 | 4179434.17 | 40003413.23 | 0.915636E+09 | 0.00 | 0.55 |
June | 0.683974E+09 | 0.128478E+10 | 0.00 | 1900950.76 | 71792739.39 | 0.00 | 0.821246E+09 | 0.00 | 0.66 |
July | 46574012.16 | 0.169710E+10 | 0.00 | 2206955.86 | 93885331.74 | 0.00 | 0.777928E+09 | 0.00 | 0.72 |
August | 0.112931E+09 | 0.154491E+10 | 0.00 | 2641059.79 | 61655447.21 | 0.00 | 0.889763E+09 | 0.00 | 0.74 |
September | 0.128495E+10 | 0.490647E+09 | 0.00 | 2289582.82 | 13900783.60 | 37039169.97 | 0.113063E+10 | 0.00 | 0.60 |
October | 0.362478E+10 | 0.00 | 0.00 | 164699.18 | 0.00 | 0.355759E+09 | 0.139474E+09 | 0.00 | 0.43 |
November | 0.177100E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.454797E+10 | 0.00 | 0.00 | 0.41 |
December | 0.496906E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.852490E+10 | 0.00 | 0.00 | 0.41 |
Annual Sum or Average | 0.144935E+11 | 0.533993E+10 | 0.00 | 10801542.91 | 0.258538E+09 | 0.383779E+11 | 0.484480E+10 | 0.00 | 0.52 |
Minimum of Months | 46574012.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.362478E+10 | 0.169710E+10 | 0.00 | 2641059.79 | 93885331.74 | 0.106034E+11 | 0.113063E+10 | 0.00 | 0.74 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.149053E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106299E+11 | 0.00 | 0.00 | 0.41 |
February | 0.491600E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.773640E+10 | 0.00 | 0.00 | 0.41 |
March | 0.146137E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.504960E+10 | 0.00 | 0.00 | 0.42 |
April | 0.191989E+10 | 0.142991E+09 | 0.00 | 224643.08 | 14994158.22 | 0.227837E+10 | 0.156003E+09 | 0.00 | 0.44 |
May | 0.171715E+10 | 0.165094E+09 | 0.00 | 1007650.79 | 4061927.93 | 59196692.90 | 0.686066E+09 | 0.00 | 0.53 |
June | 0.707453E+09 | 0.125826E+10 | 0.00 | 1753958.27 | 71462840.96 | 230370.44 | 0.762114E+09 | 0.00 | 0.65 |
July | 51584281.51 | 0.165907E+10 | 0.00 | 2063927.18 | 92984658.60 | 0.00 | 0.760868E+09 | 0.00 | 0.71 |
August | 0.119719E+09 | 0.151004E+10 | 0.00 | 2491276.31 | 61023469.36 | 0.00 | 0.871289E+09 | 0.00 | 0.73 |
September | 0.131222E+10 | 0.484916E+09 | 0.00 | 2088304.65 | 13884631.03 | 39140621.19 | 0.104945E+10 | 0.00 | 0.59 |
October | 0.344552E+10 | 0.00 | 0.00 | 119351.11 | 0.00 | 0.533638E+09 | 0.109888E+09 | 0.00 | 0.43 |
November | 0.149880E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.480952E+10 | 0.00 | 0.00 | 0.41 |
December | 0.279943E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.874195E+10 | 0.00 | 0.00 | 0.41 |
Annual Sum or Average | 0.131543E+11 | 0.522037E+10 | 0.00 | 9749111.39 | 0.258412E+09 | 0.398780E+11 | 0.439568E+10 | 0.00 | 0.51 |
Minimum of Months | 51584281.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.344552E+10 | 0.165907E+10 | 0.00 | 2491276.31 | 92984658.60 | 0.106299E+11 | 0.104945E+10 | 0.00 | 0.73 |
Report: MechanicalVentilationLoadsMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 67134829.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.198696E+11 | 0.00 | 0.00 | 0.38 |
February | 0.303829E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149443E+11 | 0.00 | 0.00 | 0.38 |
March | 0.190119E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102065E+11 | 0.00 | 0.00 | 0.39 |
April | 0.284103E+10 | 0.253940E+09 | 0.00 | 312180.77 | 33444315.83 | 0.494428E+10 | 0.286022E+09 | 0.00 | 0.40 |
May | 0.340247E+10 | 0.275334E+09 | 0.00 | 1241576.48 | 0.00 | 0.137411E+09 | 0.863648E+09 | 0.00 | 0.46 |
June | 0.124286E+10 | 0.225545E+10 | 0.00 | 2966058.90 | 76889957.18 | 6307511.29 | 0.132539E+10 | 0.00 | 0.55 |
July | 71273317.24 | 0.308839E+10 | 0.00 | 3057006.05 | 53842716.51 | 0.00 | 0.119809E+10 | 0.00 | 0.60 |
August | 82988991.92 | 0.272188E+10 | 0.00 | 4521171.40 | 29155310.93 | 0.00 | 0.155695E+10 | 0.00 | 0.64 |
September | 0.245961E+10 | 0.886706E+09 | 0.00 | 3215287.44 | 14391599.87 | 66065413.59 | 0.167790E+10 | 0.00 | 0.52 |
October | 0.615717E+10 | 0.00 | 0.00 | 146883.55 | 71097.02 | 0.128541E+10 | 0.147551E+09 | 0.00 | 0.39 |
November | 0.211450E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.962883E+10 | 0.00 | 0.00 | 0.38 |
December | 70822155.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166657E+11 | 0.00 | 0.00 | 0.37 |
Annual Sum or Average | 0.207149E+11 | 0.948170E+10 | 0.00 | 15460164.58 | 0.207795E+09 | 0.777545E+11 | 0.705555E+10 | 0.00 | 0.45 |
Minimum of Months | 67134829.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.37 |
Maximum of Months | 0.615717E+10 | 0.308839E+10 | 0.00 | 4521171.40 | 76889957.18 | 0.198696E+11 | 0.167790E+10 | 0.00 | 0.64 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 28491133.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.992839E+10 | 0.00 | 0.00 | 0.38 |
February | 0.115882E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.749794E+10 | 0.00 | 0.00 | 0.38 |
March | 0.802868E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.523864E+10 | 0.00 | 0.00 | 0.39 |
April | 0.130492E+10 | 0.125345E+09 | 0.00 | 146152.07 | 17636641.98 | 0.258235E+10 | 0.135881E+09 | 0.00 | 0.40 |
May | 0.169793E+10 | 0.136331E+09 | 0.00 | 551752.86 | 0.00 | 0.105646E+09 | 0.361684E+09 | 0.00 | 0.46 |
June | 0.622236E+09 | 0.112706E+10 | 0.00 | 1473831.32 | 38236285.77 | 3147471.60 | 0.663818E+09 | 0.00 | 0.56 |
July | 48838898.50 | 0.154332E+10 | 0.00 | 1519477.37 | 26937560.97 | 0.00 | 0.598611E+09 | 0.00 | 0.61 |
August | 43817835.74 | 0.136039E+10 | 0.00 | 2259825.70 | 14492186.01 | 0.00 | 0.797811E+09 | 0.00 | 0.65 |
September | 0.120984E+10 | 0.445432E+09 | 0.00 | 1601453.02 | 7149947.49 | 47416443.51 | 0.845356E+09 | 0.00 | 0.52 |
October | 0.292588E+10 | 0.00 | 30125.97 | 65317.26 | 0.00 | 0.791426E+09 | 61681750.57 | 60.59 | 0.39 |
November | 0.101242E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.484746E+10 | 0.00 | 0.00 | 0.38 |
December | 23972976.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.833277E+10 | 0.00 | 0.00 | 0.37 |
Annual Sum or Average | 0.983710E+10 | 0.473788E+10 | 30125.97 | 7617809.61 | 0.104453E+09 | 0.393752E+11 | 0.346484E+10 | 60.59 | 0.46 |
Minimum of Months | 23972976.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.37 |
Maximum of Months | 0.292588E+10 | 0.154332E+10 | 30125.97 | 2259825.70 | 38236285.77 | 0.992839E+10 | 0.845356E+09 | 60.59 | 0.65 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 18755348.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.993816E+10 | 0.00 | 0.00 | 0.38 |
February | 0.110587E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.750327E+10 | 0.00 | 0.00 | 0.38 |
March | 0.750949E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.528940E+10 | 0.00 | 0.00 | 0.39 |
April | 0.121576E+10 | 0.122072E+09 | 0.00 | 133428.65 | 19361880.54 | 0.267481E+10 | 0.126310E+09 | 0.00 | 0.40 |
May | 0.167911E+10 | 0.132920E+09 | 0.00 | 485441.57 | 32764.55 | 0.123985E+09 | 0.326573E+09 | 0.00 | 0.45 |
June | 0.626205E+09 | 0.111757E+10 | 0.00 | 1423689.77 | 38032760.20 | 2236711.95 | 0.646227E+09 | 0.00 | 0.55 |
July | 58934379.53 | 0.152747E+10 | 0.00 | 1471199.87 | 26837333.68 | 0.00 | 0.581351E+09 | 0.00 | 0.61 |
August | 45677066.10 | 0.134884E+10 | 0.00 | 2211553.32 | 14419596.73 | 0.00 | 0.789118E+09 | 0.00 | 0.64 |
September | 0.120369E+10 | 0.442859E+09 | 0.00 | 1545562.90 | 7150213.90 | 53644001.95 | 0.827393E+09 | 0.00 | 0.52 |
October | 0.288193E+10 | 0.00 | 30090.21 | 60280.82 | 0.00 | 0.832501E+09 | 58365738.24 | 137.01 | 0.39 |
November | 0.965340E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.489329E+10 | 0.00 | 0.00 | 0.38 |
December | 23974781.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.833281E+10 | 0.00 | 0.00 | 0.37 |
Annual Sum or Average | 0.958091E+10 | 0.469174E+10 | 30090.21 | 7331156.91 | 0.105835E+09 | 0.396441E+11 | 0.335534E+10 | 137.01 | 0.46 |
Minimum of Months | 18755348.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.37 |
Maximum of Months | 0.288193E+10 | 0.152747E+10 | 30090.21 | 2211553.32 | 38032760.20 | 0.993816E+10 | 0.827393E+09 | 137.01 | 0.64 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 7723251.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.994923E+10 | 0.00 | 0.00 | 0.38 |
February | 60410710.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.755348E+10 | 0.00 | 0.00 | 0.38 |
March | 0.565415E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.547121E+10 | 0.00 | 0.00 | 0.39 |
April | 0.970312E+09 | 0.114766E+09 | 0.00 | 107686.31 | 22993907.93 | 0.291847E+10 | 0.109979E+09 | 0.00 | 0.39 |
May | 0.164534E+10 | 0.125180E+09 | 0.00 | 367051.57 | 1215990.38 | 0.168372E+09 | 0.244418E+09 | 0.00 | 0.44 |
June | 0.616174E+09 | 0.109532E+10 | 0.00 | 1273122.80 | 38445488.20 | 26509751.36 | 0.597265E+09 | 0.00 | 0.54 |
July | 81078448.45 | 0.149180E+10 | 0.00 | 1343630.47 | 26780243.36 | 0.00 | 0.540228E+09 | 0.00 | 0.60 |
August | 60111237.69 | 0.132389E+10 | 0.00 | 2046957.30 | 14603814.52 | 0.00 | 0.759243E+09 | 0.00 | 0.63 |
September | 0.119053E+10 | 0.438591E+09 | 0.00 | 1399708.39 | 7224983.74 | 90029385.08 | 0.761682E+09 | 0.00 | 0.51 |
October | 0.255178E+10 | 0.00 | 30027.55 | 47787.01 | 0.00 | 0.115739E+10 | 48222499.68 | 452.66 | 0.39 |
November | 0.863214E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.499242E+10 | 0.00 | 0.00 | 0.38 |
December | 7573137.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.834921E+10 | 0.00 | 0.00 | 0.37 |
Annual Sum or Average | 0.861966E+10 | 0.458954E+10 | 30027.55 | 6585943.83 | 0.111264E+09 | 0.406763E+11 | 0.306104E+10 | 452.66 | 0.45 |
Minimum of Months | 7573137.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.37 |
Maximum of Months | 0.255178E+10 | 0.149180E+10 | 30027.55 | 2046957.30 | 38445488.20 | 0.994923E+10 | 0.761682E+09 | 452.66 | 0.63 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.992961E+10 | 0.00 | 0.00 | 0.38 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.759006E+10 | 0.00 | 0.00 | 0.38 |
March | 0.140218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.585631E+10 | 0.00 | 0.00 | 0.39 |
April | 0.467521E+09 | 0.103610E+09 | 1150273.72 | 60364.53 | 25031789.35 | 0.339473E+10 | 67787756.30 | 481.63 | 0.39 |
May | 0.136076E+10 | 0.121105E+09 | 0.00 | 235549.27 | 2099076.97 | 0.393641E+09 | 0.181656E+09 | 0.00 | 0.44 |
June | 0.492569E+09 | 0.106386E+10 | 0.00 | 1103099.36 | 38693631.43 | 0.146435E+09 | 0.611999E+09 | 0.00 | 0.57 |
July | 0.105191E+09 | 0.144758E+10 | 0.00 | 1253551.61 | 26573154.32 | 0.00 | 0.560245E+09 | 0.00 | 0.65 |
August | 84484791.95 | 0.130899E+10 | 0.00 | 1872337.60 | 15245150.59 | 0.00 | 0.822852E+09 | 0.00 | 0.68 |
September | 0.997484E+09 | 0.435156E+09 | 0.00 | 1231559.29 | 7391378.09 | 0.304566E+09 | 0.717675E+09 | 0.00 | 0.53 |
October | 0.159047E+10 | 0.00 | 0.00 | 33511.64 | 0.00 | 0.208526E+10 | 39911916.88 | 0.00 | 0.39 |
November | 0.587443E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.524663E+10 | 0.00 | 0.00 | 0.38 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.833211E+10 | 0.00 | 0.00 | 0.37 |
Annual Sum or Average | 0.582615E+10 | 0.448030E+10 | 1150273.72 | 5789973.30 | 0.115034E+09 | 0.432794E+11 | 0.300213E+10 | 481.63 | 0.46 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.37 |
Maximum of Months | 0.159047E+10 | 0.144758E+10 | 1150273.72 | 1872337.60 | 38693631.43 | 0.992961E+10 | 0.822852E+09 | 481.63 | 0.68 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:37:25
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.164273E+12 | 0.674129E+11 | 0.00 | 0.131258E+12 | 0.507518E+11 |
February | 0.207105E+12 | 0.508586E+11 | 0.00 | 0.101465E+12 | 0.362746E+11 |
March | 0.348079E+12 | 0.387002E+11 | 0.00 | 0.811199E+11 | 0.238851E+11 |
April | 0.431669E+12 | 0.240300E+11 | 0.00 | 0.525418E+11 | 0.212474E+11 |
May | 0.516497E+12 | 0.117998E+11 | 0.00 | 0.290120E+11 | 0.171057E+11 |
June | 0.543424E+12 | -538382584.0 | 0.00 | 0.211421E+10 | 0.811255E+11 |
July | 0.547458E+12 | -0.539234E+10 | 0.00 | -0.115291E+11 | 0.112928E+12 |
August | 0.471997E+12 | -0.387637E+10 | 0.00 | -0.531271E+10 | 0.107189E+12 |
September | 0.319730E+12 | 0.791205E+10 | 0.00 | 0.239582E+11 | 0.502387E+11 |
October | 0.229094E+12 | 0.230681E+11 | 0.00 | 0.520797E+11 | 0.644789E+10 |
November | 0.122227E+12 | 0.395754E+11 | 0.00 | 0.789775E+11 | 0.225013E+11 |
December | 0.748782E+11 | 0.566710E+11 | 0.00 | 0.111967E+12 | 0.402233E+11 |
Annual Sum or Average | 0.397643E+13 | 0.310221E+12 | 0.00 | 0.647652E+12 | 0.569918E+12 |
Minimum of Months | 0.748782E+11 | -0.539234E+10 | 0.00 | -0.115291E+11 | 0.644789E+10 |