Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:36
Tabular Output Report in Format: HTML
Building: RetailStripmall
Environment: RUNPERIOD 1 ** Denver-Aurora-Buckley AFB CO USA TMY3 WMO#=724695
Simulation Timestamp: 2023-10-16 08:37:01
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:01
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1213.39 | 580.48 | 580.48 |
Net Site Energy | 1213.39 | 580.48 | 580.48 |
Total Source Energy | 3092.64 | 1479.51 | 1479.51 |
Net Source Energy | 3092.64 | 1479.51 | 1479.51 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 2090.32 |
Net Conditioned Building Area | 2090.32 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 360.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 84.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 366.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 60.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 128.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 149.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 64.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 853.25 | 360.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 360.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 84.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 366.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 60.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 128.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 149.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 64.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 360.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 84.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 366.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 60.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 128.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 149.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 64.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 204.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 142.62 | 172.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Other | 61.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 408.19 | 172.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 204.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 142.62 | 172.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Other | 61.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 408.19 | 172.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 853.251 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 853.251 | 100.00 |
Total On-Site and Utility Electric Sources | 853.251 | 100.00 |
Total Electricity End Uses | 853.251 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 87.30 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 87.30 | 100.00 |
Total Water End Uses | 87.30 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 1.17 |
Time Setpoint Not Met During Occupied Cooling | 0.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 1781.67 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTRIPMALL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5B
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_CO_DENVER
| Environment |ZoneCoolingSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ZoneHeatingSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ZoneElectricSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |SpaceGainsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |PeakSpaceGainsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |SpaceGainComponentsAtCoolingPeakMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ComfortReportSimple55Monthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |OccupantComfortDataSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |DXReportMonthly
| PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL | PSZ-AC_3:3 COOLING COIL | PSZ-AC_4:4 COOLING COIL | PSZ-AC_5:5 COOLING COIL | PSZ-AC_6:6 COOLING COIL | PSZ-AC_7:7 COOLING COIL | PSZ-AC_8:8 COOLING COIL | PSZ-AC_9:9 COOLING COIL | PSZ-AC_10:10 COOLING COIL |WindowReportMonthly
| LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR |WindowEnergyReportMonthly
| LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR |WindowZoneSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |WindowEnergyZoneSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| GAS TANK1 | GAS TANK2 | GAS TANK3 | GAS TANK4 | GAS TANK5 | GAS TANK6 | GAS TANK7 |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC_1:1 HEATING COIL | PSZ-AC_2:2 HEATING COIL | PSZ-AC_3:3 HEATING COIL | PSZ-AC_4:4 HEATING COIL | PSZ-AC_5:5 HEATING COIL | PSZ-AC_6:6 HEATING COIL | PSZ-AC_7:7 HEATING COIL | PSZ-AC_8:8 HEATING COIL | PSZ-AC_9:9 HEATING COIL | PSZ-AC_10:10 HEATING COIL | PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL | PSZ-AC_3:3 COOLING COIL | PSZ-AC_4:4 COOLING COIL | PSZ-AC_5:5 COOLING COIL | PSZ-AC_6:6 COOLING COIL | PSZ-AC_7:7 COOLING COIL | PSZ-AC_8:8 COOLING COIL | PSZ-AC_9:9 COOLING COIL | PSZ-AC_10:10 COOLING COIL |FanReportMonthly
| PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN |ZoneTemperatureOscillationReportMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |MechanicalVentilationLoadsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:01
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:36 |
RunPeriod | RUNPERIOD 1 |
Weather File | Denver-Aurora-Buckley AFB CO USA TMY3 WMO#=724695 |
Latitude [deg] | 39.72 |
Longitude [deg] | -104.8 |
Elevation [m] | 1726.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Above Ground Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Window Opening Area [m2] | 124.40 | 0.00 | 0.00 | 124.40 | 0.00 |
Gross Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Above Ground Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Above Ground Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Window Opening Area [m2] | 124.40 | 0.00 | 0.00 | 124.40 | 0.00 |
Gross Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Above Ground Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Total | |
Gross Roof Area [m2] | 2090.32 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
LGSTORE1 | 348.39 | Yes | Yes | 1805.20 | 1.00 | 276.30 | 0.00 | 20.77 | 20.77 | 15.3022 | 6.19 | 4.3000 |
SMSTORE1 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.38 | 10.38 | 18.2890 | 6.19 | 4.3000 |
SMSTORE2 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 16.6533 | 6.19 | 4.3000 |
SMSTORE3 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 16.6533 | 6.19 | 4.3000 |
SMSTORE4 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 16.6533 | 6.19 | 4.3000 |
LGSTORE2 | 348.39 | Yes | Yes | 1805.20 | 1.00 | 157.89 | 0.00 | 20.72 | 20.72 | 9.5842 | 6.19 | 4.3000 |
SMSTORE5 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 9.6995 | 6.19 | 4.3000 |
SMSTORE6 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 9.6995 | 6.19 | 4.3000 |
SMSTORE7 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 9.6995 | 6.19 | 4.3000 |
SMSTORE8 | 174.19 | Yes | Yes | 902.60 | 1.00 | 197.36 | 0.00 | 10.36 | 10.36 | 9.6995 | 6.19 | 4.3000 |
Total | 2090.32 | 10831.20 | 1184.15 | 0.00 | 124.40 | 124.40 | 13.0683 | 6.19 | 4.3000 | |||
Conditioned Total | 2090.32 | 10831.20 | 1184.15 | 0.00 | 124.40 | 124.40 | 13.0683 | 6.19 | 4.3000 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
LGSTORE1 | 348.39 | Yes | Yes | 1.00 | LGSTORE1 | GENERAL | LGSTORE1 | 15.3022 | 6.19 | 4.3000 | |
SMSTORE1 | 174.19 | Yes | Yes | 1.00 | SMSTORE1 | GENERAL | SMSTORE1 | 18.2890 | 6.19 | 4.3000 | |
SMSTORE2 | 174.19 | Yes | Yes | 1.00 | SMSTORE2 | GENERAL | SMSTORE2 | 16.6533 | 6.19 | 4.3000 | |
SMSTORE3 | 174.19 | Yes | Yes | 1.00 | SMSTORE3 | GENERAL | SMSTORE3 | 16.6533 | 6.19 | 4.3000 | |
SMSTORE4 | 174.19 | Yes | Yes | 1.00 | SMSTORE4 | GENERAL | SMSTORE4 | 16.6533 | 6.19 | 4.3000 | |
LGSTORE2 | 348.39 | Yes | Yes | 1.00 | LGSTORE2 | GENERAL | LGSTORE2 | 9.5842 | 6.19 | 4.3000 | |
SMSTORE5 | 174.19 | Yes | Yes | 1.00 | SMSTORE5 | GENERAL | SMSTORE5 | 9.6995 | 6.19 | 4.3000 | |
SMSTORE6 | 174.19 | Yes | Yes | 1.00 | SMSTORE6 | GENERAL | SMSTORE6 | 9.6995 | 6.19 | 4.3000 | |
SMSTORE7 | 174.19 | Yes | Yes | 1.00 | SMSTORE7 | GENERAL | SMSTORE7 | 9.6995 | 6.19 | 4.3000 | |
SMSTORE8 | 174.19 | Yes | Yes | 1.00 | SMSTORE8 | GENERAL | SMSTORE8 | 9.6995 | 6.19 | 4.3000 | |
Total | 2090.32 | 13.0683 | 3.10 | 4.3000 | |||||||
Conditioned Total | 2090.32 | 13.0683 | 3.10 | 4.3000 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 2090.32 | 2090.32 | 0.00 | 0.00 | 13.0683 | 6.19 | 4.3000 |
Total | 2090.32 | 2090.32 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:01
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 26-JUN-14:00 | 21-DEC-17:00 | - | - | - | - | - | - | - | - | - | - | 06-JAN-13:09 |
Heating | 0.00 | 227604.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 43088.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 23459.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 8059.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 11082.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 3326.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 89016.25 | 227604.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 227604.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 43088.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 23459.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 8059.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 11082.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 3326.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:01
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 390.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 266.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1161.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 190.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 405.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 472.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 204.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2702.25 | 390.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 186.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 127.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 555.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 91.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 194.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 226.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 97.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1292.74 | 186.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 186.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 127.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 555.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 91.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 194.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 226.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 97.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1292.74 | 186.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:01
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
LGSTORE1 DIRECT AIR | 2.32 |
SMSTORE1 DIRECT AIR | 1.25 |
SMSTORE2 DIRECT AIR | 1.31 |
SMSTORE3 DIRECT AIR | 1.30 |
SMSTORE4 DIRECT AIR | 1.30 |
LGSTORE2 DIRECT AIR | 2.20 |
SMSTORE5 DIRECT AIR | 1.14 |
SMSTORE6 DIRECT AIR | 1.13 |
SMSTORE7 DIRECT AIR | 1.12 |
SMSTORE8 DIRECT AIR | 1.18 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC_1:1 | 2.32 | 2.32 | 2.32 | 2.32 | 2.32 | 2.32 | 1.00 | 1.00 | 2.32 |
PSZ-AC_2:2 | 1.25 | 1.25 | 1.25 | 1.25 | 1.25 | 1.25 | 1.00 | 1.00 | 1.25 |
PSZ-AC_3:3 | 1.31 | 1.31 | 1.31 | 1.31 | 1.31 | 1.31 | 1.00 | 1.00 | 1.31 |
PSZ-AC_4:4 | 1.30 | 1.30 | 1.30 | 1.30 | 1.30 | 1.30 | 1.00 | 1.00 | 1.30 |
PSZ-AC_5:5 | 1.30 | 1.30 | 1.30 | 1.30 | 1.30 | 1.30 | 1.00 | 1.00 | 1.30 |
PSZ-AC_6:6 | 2.20 | 2.20 | 2.20 | 2.20 | 2.20 | 2.20 | 1.00 | 1.00 | 2.20 |
PSZ-AC_7:7 | 1.14 | 1.14 | 1.14 | 1.14 | 1.14 | 1.14 | 1.00 | 1.00 | 1.14 |
PSZ-AC_8:8 | 1.13 | 1.13 | 1.13 | 1.13 | 1.13 | 1.13 | 1.00 | 1.000000 | 1.13 |
PSZ-AC_9:9 | 1.12 | 1.12 | 1.12 | 1.12 | 1.12 | 1.12 | 1.00 | 1.00 | 1.12 |
PSZ-AC_10:10 | 1.18 | 1.18 | 1.18 | 1.18 | 1.18 | 1.18 | 1.00 | 1.000000 | 1.18 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC_1:1_OA_CONTROLLER | 2.32 | 0.411479 |
PSZ-AC_2:2_OA_CONTROLLER | 1.25 | 0.205739 |
PSZ-AC_3:3_OA_CONTROLLER | 1.31 | 0.205739 |
PSZ-AC_4:4_OA_CONTROLLER | 1.30 | 0.205739 |
PSZ-AC_5:5_OA_CONTROLLER | 1.30 | 0.205739 |
PSZ-AC_6:6_OA_CONTROLLER | 2.20 | 0.411479 |
PSZ-AC_7:7_OA_CONTROLLER | 1.14 | 0.205739 |
PSZ-AC_8:8_OA_CONTROLLER | 1.13 | 0.205739 |
PSZ-AC_9:9_OA_CONTROLLER | 1.12 | 0.205739 |
PSZ-AC_10:10_OA_CONTROLLER | 1.18 | 0.205739 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | 2.32 | 2477.30 |
PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | 1.25 | 1388.41 |
PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | 1.31 | 1452.54 |
PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | 1.30 | 1444.40 |
PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | 1.30 | 1441.08 |
PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | 2.20 | 2349.35 |
PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | 1.14 | 1256.84 |
PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | 1.13 | 1247.81 |
PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | 1.12 | 1238.61 |
PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | 1.18 | 1300.93 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC_1:1_UNITARY_PACKAGE_DX | 2.32 | 2.32 | 2.32 | 1.53 | 38323.60 | 58726.78 | 40.00 | 1.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_DX | 1.25 | 1.25 | 1.25 | 0.827658 | 20758.61 | 31153.40 | 40.00 | 1.00 |
PSZ-AC_3:3_UNITARY_PACKAGE_DX | 1.31 | 1.31 | 1.31 | 0.865889 | 21717.49 | 32228.33 | 40.00 | 1.00 |
PSZ-AC_4:4_UNITARY_PACKAGE_DX | 1.30 | 1.30 | 1.30 | 0.861036 | 21595.75 | 32091.86 | 40.00 | 1.00 |
PSZ-AC_5:5_UNITARY_PACKAGE_DX | 1.30 | 1.30 | 1.30 | 0.859056 | 21546.09 | 32036.19 | 40.00 | 1.00 |
PSZ-AC_6:6_UNITARY_PACKAGE_DX | 2.20 | 2.20 | 2.20 | 1.45 | 36344.20 | 56507.16 | 40.00 | 1.00 |
PSZ-AC_7:7_UNITARY_PACKAGE_DX | 1.14 | 1.14 | 1.14 | 1.14 | 18791.44 | 28948.09 | 40.00 | 1.00 |
PSZ-AC_8:8_UNITARY_PACKAGE_DX | 1.13 | 1.13 | 1.13 | 1.13 | 18656.52 | 28796.84 | 40.00 | 1.00 |
PSZ-AC_9:9_UNITARY_PACKAGE_DX | 1.12 | 1.12 | 1.12 | 1.12 | 18518.96 | 28642.63 | 40.00 | 1.00 |
PSZ-AC_10:10_UNITARY_PACKAGE_DX | 1.18 | 1.18 | 1.18 | 0.775513 | 19450.75 | 29687.80 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-AC_1:1 COOLING COIL | 2.32 | 1.16 | 1.54 | 38323.60 | 19161.80 | 0.800660 | 0.800660 |
PSZ-AC_2:2 COOLING COIL | 1.25 | 0.627014 | 0.836020 | 20758.61 | 10379.31 | 0.800660 | 0.800660 |
PSZ-AC_3:3 COOLING COIL | 1.31 | 0.655977 | 0.874633 | 21717.49 | 10858.75 | 0.800660 | 0.800660 |
PSZ-AC_4:4 COOLING COIL | 1.30 | 0.652300 | 0.869733 | 21595.75 | 10797.88 | 0.800660 | 0.800660 |
PSZ-AC_5:5 COOLING COIL | 1.30 | 0.650800 | 0.867733 | 21546.09 | 10773.05 | 0.800660 | 0.800660 |
PSZ-AC_6:6 COOLING COIL | 2.20 | 1.10 | 1.46 | 36344.20 | 18172.10 | 0.800660 | 0.800660 |
PSZ-AC_7:7 COOLING COIL | 1.14 | 0.567595 | 0.756793 | 18791.44 | 9395.72 | 0.800660 | 0.800660 |
PSZ-AC_8:8 COOLING COIL | 1.13 | 0.563520 | 0.751360 | 18656.52 | 9328.26 | 0.800660 | 0.800660 |
PSZ-AC_9:9 COOLING COIL | 1.12 | 0.559365 | 0.745820 | 18518.96 | 9259.48 | 0.800660 | 0.800660 |
PSZ-AC_10:10 COOLING COIL | 1.18 | 0.587510 | 0.783347 | 19450.75 | 9725.38 | 0.800660 | 0.800660 |
Design Size Nominal Capacity [W] | |
PSZ-AC_1:1 HEATING COIL | 58726.78 |
PSZ-AC_2:2 HEATING COIL | 31153.40 |
PSZ-AC_3:3 HEATING COIL | 32228.33 |
PSZ-AC_4:4 HEATING COIL | 32091.86 |
PSZ-AC_5:5 HEATING COIL | 32036.19 |
PSZ-AC_6:6 HEATING COIL | 56507.16 |
PSZ-AC_7:7 HEATING COIL | 28948.09 |
PSZ-AC_8:8 HEATING COIL | 28796.84 |
PSZ-AC_9:9 HEATING COIL | 28642.63 |
PSZ-AC_10:10 HEATING COIL | 29687.80 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:01
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
LGSTORE1_WALL_3 | LGSTORE1_WALL_3_DOOR_1 | LGSTORE1_WALL_3_DOOR_2 | |
LGSTORE1_WALL_1 | LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | |
SMSTORE1_WALL_1 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | |
SMSTORE1_WALL_3 | SMSTORE1_WALL_3_DOOR | |
SMSTORE2_WALL_1 | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | |
SMSTORE2_WALL_3 | SMSTORE2_WALL_3_DOOR | |
SMSTORE3_WALL_1 | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | |
SMSTORE3_WALL_3 | SMSTORE3_WALL_3_DOOR | |
SMSTORE4_WALL_1 | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | |
SMSTORE4_WALL_3 | SMSTORE4_WALL_3_DOOR | |
LGSTORE2_WALL_3 | LGSTORE2_WALL_3_DOOR_1 | LGSTORE2_WALL_3_DOOR_2 | |
LGSTORE2_WALL_1 | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | |
SMSTORE5_WALL_1 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | |
SMSTORE5_WALL_3 | SMSTORE5_WALL_3_DOOR | |
SMSTORE6_WALL_1 | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | |
SMSTORE6_WALL_3 | SMSTORE6_WALL_3_DOOR | |
SMSTORE7_WALL_1 | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | |
SMSTORE7_WALL_3 | SMSTORE7_WALL_3_DOOR | |
SMSTORE8_WALL_1 | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR | |
SMSTORE8_WALL_3 | SMSTORE8_WALL_3_DOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:01
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:01
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 7.10 | 3.00 | -1.00 | 0.80 | -0.20 | 4.80 | 6.10 | 13.70 | 22.20 | 22.70 | 21.70 | 18.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Denver-Aurora-Buckley AFB CO USA TMY3 WMO#=724695 | 39.72 | -104.75 | -7.00 | 1726.00 | 82237 | 0.9774 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 9.95 | 23.70 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RetailStripmall | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 10 | 118 | 48 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | LGSTORE1 | 0.0 | 0.00 | 0.00 | 0.00 | 7.62 | 11.43 | 2.59 | 1 | 1 | 1 | 0.00 | 15.24 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 1805.20 | TARP | TARP | 348.39 | 276.30 | 247.74 | 20.77 | 6 | 8 | 0 | Yes |
2 | SMSTORE1 | 0.0 | 0.00 | 0.00 | 0.00 | 19.05 | 11.43 | 2.59 | 1 | 1 | 1 | 15.24 | 22.86 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.66 | 10.38 | 6 | 4 | 0 | Yes |
3 | SMSTORE2 | 0.0 | 0.00 | 0.00 | 0.00 | 26.67 | 11.43 | 2.59 | 1 | 1 | 1 | 22.86 | 30.48 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
4 | SMSTORE3 | 0.0 | 0.00 | 0.00 | 0.00 | 34.29 | 11.43 | 2.59 | 1 | 1 | 1 | 30.48 | 38.10 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
5 | SMSTORE4 | 0.0 | 0.00 | 0.00 | 0.00 | 41.91 | 11.43 | 2.59 | 1 | 1 | 1 | 38.10 | 45.72 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
6 | LGSTORE2 | 0.0 | 0.00 | 0.00 | 0.00 | 53.34 | 11.43 | 2.59 | 1 | 1 | 1 | 45.72 | 60.96 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 1805.20 | TARP | TARP | 348.39 | 157.89 | 129.41 | 20.72 | 6 | 8 | 0 | Yes |
7 | SMSTORE5 | 0.0 | 0.00 | 0.00 | 0.00 | 64.77 | 11.43 | 2.59 | 1 | 1 | 1 | 60.96 | 68.58 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
8 | SMSTORE6 | 0.0 | 0.00 | 0.00 | 0.00 | 72.39 | 11.43 | 2.59 | 1 | 1 | 1 | 68.58 | 76.20 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
9 | SMSTORE7 | 0.0 | 0.00 | 0.00 | 0.00 | 80.01 | 11.43 | 2.59 | 1 | 1 | 1 | 76.20 | 83.82 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
10 | SMSTORE8 | 0.0 | 0.00 | 0.00 | 0.00 | 87.63 | 11.43 | 2.59 | 1 | 1 | 1 | 83.82 | 91.44 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 197.36 | 183.12 | 10.36 | 6 | 4 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | LGSTORE1 | 348.39 | 56.3 | 6.193 | 0.161 | 15.302 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 19.602 | No |
2 | SMSTORE1 | 174.19 | 28.1 | 6.194 | 0.161 | 18.289 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 22.589 | No |
3 | SMSTORE2 | 174.19 | 28.1 | 6.194 | 0.161 | 16.653 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 20.953 | No |
4 | SMSTORE3 | 174.19 | 28.1 | 6.194 | 0.161 | 16.653 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 20.953 | No |
5 | SMSTORE4 | 174.19 | 28.1 | 6.194 | 0.161 | 16.653 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 20.953 | No |
6 | LGSTORE2 | 348.39 | 56.3 | 6.193 | 0.161 | 9.584 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 13.884 | No |
7 | SMSTORE5 | 174.19 | 28.1 | 6.194 | 0.161 | 9.699 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 13.999 | No |
8 | SMSTORE6 | 174.19 | 28.1 | 6.194 | 0.161 | 9.699 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 13.999 | No |
9 | SMSTORE7 | 174.19 | 28.1 | 6.194 | 0.161 | 9.699 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 13.999 | No |
10 | SMSTORE8 | 174.19 | 28.1 | 6.194 | 0.161 | 9.699 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 13.999 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | LGSTORE1 | TYPE1_OCC_SCH | LGSTORE1 | 348.39 | 56.3 | 56.3 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 56 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | SMSTORE1 | TYPE1_OCC_SCH | SMSTORE1 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | SMSTORE2 | TYPE2_OCC_SCH | SMSTORE2 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | SMSTORE3 | TYPE2_OCC_SCH | SMSTORE3 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | SMSTORE4 | TYPE2_OCC_SCH | SMSTORE4 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | LGSTORE2 | TYPE3_OCC_SCH | LGSTORE2 | 348.39 | 56.3 | 56.3 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 56 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | SMSTORE5 | TYPE3_OCC_SCH | SMSTORE5 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | SMSTORE6 | TYPE3_OCC_SCH | SMSTORE6 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | SMSTORE7 | TYPE3_OCC_SCH | SMSTORE7 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | SMSTORE8 | TYPE3_OCC_SCH | SMSTORE8 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | LGSTORE1_LIGHTS | LTG_SCH_BASE_LPD1 | LGSTORE1 | 348.39 | 56.3 | 3346.345 | 9.605 | 59.490 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3346.345 |
2 | LGSTORE1_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | LGSTORE1 | 348.39 | 56.3 | 1984.726 | 5.697 | 35.284 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1984.726 |
3 | SMSTORE1_LIGHTS | LTG_SCH_BASE_SMALL_LPD1 | SMSTORE1 | 174.19 | 28.1 | 1693.257 | 9.721 | 60.206 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1693.257 |
4 | SMSTORE1_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | SMSTORE1 | 174.19 | 28.1 | 1492.567 | 8.568 | 53.070 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1492.567 |
5 | SMSTORE2_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE2 | 174.19 | 28.1 | 1689.582 | 9.699 | 60.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1689.582 |
6 | SMSTORE2_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE2 | 174.19 | 28.1 | 1211.319 | 6.954 | 43.070 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1211.319 |
7 | SMSTORE3_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE3 | 174.19 | 28.1 | 1689.582 | 9.699 | 60.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1689.582 |
8 | SMSTORE3_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE3 | 174.19 | 28.1 | 1211.319 | 6.954 | 43.070 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1211.319 |
9 | SMSTORE4_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE4 | 174.19 | 28.1 | 1689.582 | 9.699 | 60.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1689.582 |
10 | SMSTORE4_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE4 | 174.19 | 28.1 | 1211.319 | 6.954 | 43.070 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1211.319 |
11 | LGSTORE2_LIGHTS | LTG_SCH_BASE_LPD2 | LGSTORE2 | 348.39 | 56.3 | 3338.998 | 9.584 | 59.359 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3338.998 |
12 | LGSTORE2_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | LGSTORE2 | 348.39 | 56.3 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
13 | SMSTORE5_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE5 | 174.19 | 28.1 | 1689.582 | 9.699 | 60.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1689.582 |
14 | SMSTORE5_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE5 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
15 | SMSTORE6_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE6 | 174.19 | 28.1 | 1689.582 | 9.699 | 60.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1689.582 |
16 | SMSTORE6_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE6 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
17 | SMSTORE7_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE7 | 174.19 | 28.1 | 1689.582 | 9.699 | 60.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1689.582 |
18 | SMSTORE7_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE7 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
19 | SMSTORE8_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE8 | 174.19 | 28.1 | 1689.582 | 9.699 | 60.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1689.582 |
20 | SMSTORE8_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE8 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LGSTORE1_MISCPLUG_EQUIP | TYPE1_EQUIP_SCH | LGSTORE1 | 348.39 | 56.3 | 1498.062 | 4.300 | 26.632 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1498.062 |
2 | SMSTORE1_MISCPLUG_EQUIP | TYPE1_EQUIP_SCH | SMSTORE1 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
3 | SMSTORE2_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE2 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
4 | SMSTORE3_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE3 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
5 | SMSTORE4_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE4 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
6 | LGSTORE2_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | LGSTORE2 | 348.39 | 56.3 | 1498.062 | 4.300 | 26.632 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1498.062 |
7 | SMSTORE5_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE5 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
8 | SMSTORE6_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE6 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
9 | SMSTORE7_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE7 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
10 | SMSTORE8_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE8 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.770 | 0.700 | Rough |
5 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 0.5398 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
6 | LGSTORE1_FLOOR_FFACTOR | 36 | 2 | 7 | 0.167 | 0.1408 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
7 | SMSTORE1_FLOOR_FFACTOR | 37 | 2 | 7 | 0.167 | 0.7972E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
8 | SMSTORE2_FLOOR_FFACTOR | 38 | 2 | 7 | 0.167 | 0.7972E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | SMSTORE3_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.7972E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
10 | SMSTORE4_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.7972E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
11 | LGSTORE2_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.7972E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | SMSTORE5_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.7972E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | SMSTORE6_FLOOR_FFACTOR | 43 | 2 | 7 | 0.167 | 0.7972E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | SMSTORE7_FLOOR_FFACTOR | 44 | 2 | 7 | 0.167 | 0.7972E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | SMSTORE8_FLOOR_FFACTOR | 45 | 2 | 7 | 0.167 | 0.2031 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
6 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
7 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
8 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
10 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.619 |
11 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
12 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 7.024 |
13 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
14 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.47 |
15 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
16 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.47 |
17 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
18 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.47 |
19 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
20 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.47 |
21 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
22 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.47 |
23 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
24 | ~FC_Insulation_7 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.47 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_8 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.47 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_9 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.47 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_10 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.847 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
14 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
15 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
16 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
17 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
18 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
19 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
20 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
21 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
22 | 7 | -0.34329049E-12 | 0.74065570E-15 | -0.11060681E-12 | 0.10726285E-15 |
23 | 6 | 0.31458623E-07 | 0.15582808E-09 | 0.71832143E-08 | -0.15023289E-12 |
24 | 5 | -0.20415818E-03 | 0.13111101E-05 | -0.10480723E-03 | 0.70917048E-08 |
25 | 4 | 0.30843928 | 0.62847427E-03 | 0.10555000 | -0.35885187E-04 |
26 | 3 | -7.5886440 | 0.19208290E-01 | -2.4345797 | 0.30589548E-01 |
27 | 2 | 41.933758 | 0.67466625E-01 | 15.656649 | -0.34517733 |
28 | 1 | -81.359657 | 0.30121645E-01 | -29.492494 | 1.0959638 |
29 | 0 | 46.824334 | 0.59962785E-03 | 16.283006 | |
30 | 7 | -0.30155247E-08 | -0.19705740E-14 | 0.18469307E-14 | -0.46079768E-16 |
31 | 6 | 0.40551627E-05 | 0.26926011E-08 | 0.31944497E-02 | -0.26797721E-04 |
32 | 5 | -0.28496186E-03 | 0.15923452E-05 | -0.22398486 | 0.19584477E-02 |
33 | 4 | 0.65115693E-02 | 0.72427529E-04 | 4.8338806 | -0.45306652E-01 |
34 | 3 | -0.57046066E-01 | 0.57554694E-03 | -38.045903 | 0.39892442 |
35 | 2 | 0.20237164 | 0.95689144E-03 | 116.53161 | -1.4185768 |
36 | 1 | -0.29197338 | 0.29127682E-03 | -143.93536 | 2.0495010 |
37 | 0 | 0.14232195 | 0.70641069E-05 | 60.838472 | |
38 | 7 | -0.53597813E-08 | -0.10943972E-13 | 0.15521545E-14 | -0.37274179E-16 |
39 | 6 | 0.25551035E-05 | 0.15319154E-08 | 0.31991935E-02 | -0.26837516E-04 |
40 | 5 | -0.16700335E-03 | 0.90227195E-06 | -0.22425438 | 0.19608267E-02 |
41 | 4 | 0.37302439E-02 | 0.40957222E-04 | 4.8383675 | -0.45349785E-01 |
42 | 3 | -0.32401395E-01 | 0.32489936E-03 | -38.071239 | 0.39920448 |
43 | 2 | 0.11454695 | 0.53930964E-03 | 116.58090 | -1.4192362 |
44 | 1 | -0.16500402 | 0.16380141E-03 | -143.96437 | 2.0499779 |
45 | 0 | 0.80366526E-01 | 0.39747064E-05 | 60.838472 | |
46 | 7 | -0.53597813E-08 | -0.10943972E-13 | 0.15521547E-14 | -0.37274182E-16 |
47 | 6 | 0.25551035E-05 | 0.15319154E-08 | 0.31991935E-02 | -0.26837516E-04 |
48 | 5 | -0.16700335E-03 | 0.90227195E-06 | -0.22425438 | 0.19608267E-02 |
49 | 4 | 0.37302439E-02 | 0.40957222E-04 | 4.8383675 | -0.45349785E-01 |
50 | 3 | -0.32401395E-01 | 0.32489936E-03 | -38.071239 | 0.39920448 |
51 | 2 | 0.11454695 | 0.53930964E-03 | 116.58090 | -1.4192362 |
52 | 1 | -0.16500402 | 0.16380141E-03 | -143.96437 | 2.0499779 |
53 | 0 | 0.80366526E-01 | 0.39747064E-05 | 60.838472 | |
54 | 7 | -0.53597813E-08 | -0.10943972E-13 | 0.15521549E-14 | -0.37274185E-16 |
55 | 6 | 0.25551035E-05 | 0.15319154E-08 | 0.31991935E-02 | -0.26837516E-04 |
56 | 5 | -0.16700335E-03 | 0.90227195E-06 | -0.22425438 | 0.19608267E-02 |
57 | 4 | 0.37302439E-02 | 0.40957222E-04 | 4.8383675 | -0.45349785E-01 |
58 | 3 | -0.32401395E-01 | 0.32489936E-03 | -38.071239 | 0.39920448 |
59 | 2 | 0.11454695 | 0.53930964E-03 | 116.58090 | -1.4192362 |
60 | 1 | -0.16500402 | 0.16380141E-03 | -143.96437 | 2.0499779 |
61 | 0 | 0.80366526E-01 | 0.39747064E-05 | 60.838472 | |
62 | 7 | -0.53597813E-08 | -0.10943972E-13 | 0.15521548E-14 | -0.37274183E-16 |
63 | 6 | 0.25551035E-05 | 0.15319154E-08 | 0.31991935E-02 | -0.26837516E-04 |
64 | 5 | -0.16700335E-03 | 0.90227195E-06 | -0.22425438 | 0.19608267E-02 |
65 | 4 | 0.37302439E-02 | 0.40957222E-04 | 4.8383675 | -0.45349785E-01 |
66 | 3 | -0.32401395E-01 | 0.32489936E-03 | -38.071239 | 0.39920448 |
67 | 2 | 0.11454695 | 0.53930964E-03 | 116.58090 | -1.4192362 |
68 | 1 | -0.16500402 | 0.16380141E-03 | -143.96437 | 2.0499779 |
69 | 0 | 0.80366526E-01 | 0.39747064E-05 | 60.838472 | |
70 | 7 | -0.53597813E-08 | -0.10943972E-13 | 0.15521547E-14 | -0.37274182E-16 |
71 | 6 | 0.25551035E-05 | 0.15319154E-08 | 0.31991935E-02 | -0.26837516E-04 |
72 | 5 | -0.16700335E-03 | 0.90227195E-06 | -0.22425438 | 0.19608267E-02 |
73 | 4 | 0.37302439E-02 | 0.40957222E-04 | 4.8383675 | -0.45349785E-01 |
74 | 3 | -0.32401395E-01 | 0.32489936E-03 | -38.071239 | 0.39920448 |
75 | 2 | 0.11454695 | 0.53930964E-03 | 116.58090 | -1.4192362 |
76 | 1 | -0.16500402 | 0.16380141E-03 | -143.96437 | 2.0499779 |
77 | 0 | 0.80366526E-01 | 0.39747064E-05 | 60.838472 | |
78 | 7 | -0.53597813E-08 | -0.10943972E-13 | 0.15521547E-14 | -0.37274181E-16 |
79 | 6 | 0.25551035E-05 | 0.15319154E-08 | 0.31991935E-02 | -0.26837516E-04 |
80 | 5 | -0.16700335E-03 | 0.90227195E-06 | -0.22425438 | 0.19608267E-02 |
81 | 4 | 0.37302439E-02 | 0.40957222E-04 | 4.8383675 | -0.45349785E-01 |
82 | 3 | -0.32401395E-01 | 0.32489936E-03 | -38.071239 | 0.39920448 |
83 | 2 | 0.11454695 | 0.53930964E-03 | 116.58090 | -1.4192362 |
84 | 1 | -0.16500402 | 0.16380141E-03 | -143.96437 | 2.0499779 |
85 | 0 | 0.80366526E-01 | 0.39747064E-05 | 60.838472 | |
86 | 7 | -0.53597813E-08 | -0.10943972E-13 | 0.15521545E-14 | -0.37274179E-16 |
87 | 6 | 0.25551035E-05 | 0.15319154E-08 | 0.31991935E-02 | -0.26837516E-04 |
88 | 5 | -0.16700335E-03 | 0.90227195E-06 | -0.22425438 | 0.19608267E-02 |
89 | 4 | 0.37302439E-02 | 0.40957222E-04 | 4.8383675 | -0.45349785E-01 |
90 | 3 | -0.32401395E-01 | 0.32489936E-03 | -38.071239 | 0.39920448 |
91 | 2 | 0.11454695 | 0.53930964E-03 | 116.58090 | -1.4192362 |
92 | 1 | -0.16500402 | 0.16380141E-03 | -143.96437 | 2.0499779 |
93 | 0 | 0.80366526E-01 | 0.39747064E-05 | 60.838472 | |
94 | 7 | -0.53597813E-08 | -0.10943972E-13 | 0.15521547E-14 | -0.37274182E-16 |
95 | 6 | 0.25551035E-05 | 0.15319154E-08 | 0.31991935E-02 | -0.26837516E-04 |
96 | 5 | -0.16700335E-03 | 0.90227195E-06 | -0.22425438 | 0.19608267E-02 |
97 | 4 | 0.37302439E-02 | 0.40957222E-04 | 4.8383675 | -0.45349785E-01 |
98 | 3 | -0.32401395E-01 | 0.32489936E-03 | -38.071239 | 0.39920448 |
99 | 2 | 0.11454695 | 0.53930964E-03 | 116.58090 | -1.4192362 |
100 | 1 | -0.16500402 | 0.16380141E-03 | -143.96437 | 2.0499779 |
101 | 0 | 0.80366526E-01 | 0.39747064E-05 | 60.838472 | |
102 | 7 | -0.20778300E-08 | -0.65167512E-15 | 0.79548166E-14 | -0.12010680E-15 |
103 | 6 | 0.57088823E-05 | 0.38884884E-08 | 0.31895855E-02 | -0.26756916E-04 |
104 | 5 | -0.40892418E-03 | 0.23023551E-05 | -0.22370841 | 0.19560076E-02 |
105 | 4 | 0.93961169E-02 | 0.10478953E-03 | 4.8292766 | -0.45262394E-01 |
106 | 3 | -0.82481111E-01 | 0.83319714E-03 | -38.019897 | 0.39863696 |
107 | 2 | 0.29283299 | 0.13859693E-02 | 116.48099 | -1.4178998 |
108 | 1 | -0.42263540 | 0.42218679E-03 | -143.90557 | 2.0490113 |
109 | 0 | 0.20604930 | 0.10232106E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.362_SHGC_0.379 | 35 | 1 | VerySmooth | 2.057 | 2.057 | 1.000 | 0.380 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 3.63679E-002 | 0.29270 | 0.50147 | 0.50147 | 0.41690 | 0.13592 | 0.17539 | 0.00000 | 0.84000 | 0.84000 | 0.11599 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | GAS TANK1 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
2 | WaterHeater:Mixed | GAS TANK2 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
3 | WaterHeater:Mixed | GAS TANK3 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
4 | WaterHeater:Mixed | GAS TANK4 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
5 | WaterHeater:Mixed | GAS TANK5 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
6 | WaterHeater:Mixed | GAS TANK6 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
7 | WaterHeater:Mixed | GAS TANK7 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | LGSTORE1_WALL_2 | 0 | 118.41 | 56.08 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
2 | LGSTORE1_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
3 | LGSTORE1_WALL_3_DOOR_1 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
4 | LGSTORE1_WALL_3_DOOR_2 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
5 | LGSTORE1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
6 | LGSTORE1_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
7 | LGSTORE1_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
8 | LGSTORE1_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
9 | LGSTORE1_WALL_1_WINDOW_3 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
10 | LGSTORE1_WALL_1_WINDOW_4 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
11 | LGSTORE1_WALL_1_DOOR_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 1 | No | No |
12 | LGSTORE1_WALL_1_DOOR_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 1 | No | No |
13 | LGSTORE1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
14 | LGSTORE1_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
15 | LGSTORE1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
16 | SMSTORE1_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
17 | SMSTORE1_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
18 | SMSTORE1_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
19 | SMSTORE1_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
20 | SMSTORE1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
21 | SMSTORE1_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
22 | SMSTORE1_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
23 | SMSTORE1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
24 | SMSTORE1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
25 | SMSTORE1_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
26 | SMSTORE1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
27 | SMSTORE2_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
28 | SMSTORE2_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
29 | SMSTORE2_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
30 | SMSTORE2_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
31 | SMSTORE2_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
32 | SMSTORE2_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
33 | SMSTORE2_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
34 | SMSTORE2_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
35 | SMSTORE2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
36 | SMSTORE2_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
37 | SMSTORE2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
38 | SMSTORE3_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
39 | SMSTORE3_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
40 | SMSTORE3_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
41 | SMSTORE3_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
42 | SMSTORE3_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
43 | SMSTORE3_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
44 | SMSTORE3_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
45 | SMSTORE3_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
46 | SMSTORE3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
47 | SMSTORE3_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
48 | SMSTORE3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
49 | SMSTORE4_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
50 | SMSTORE4_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
51 | SMSTORE4_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
52 | SMSTORE4_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
53 | SMSTORE4_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
54 | SMSTORE4_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 3 | No | No |
55 | SMSTORE4_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
56 | SMSTORE4_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
57 | SMSTORE4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
58 | SMSTORE4_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
59 | SMSTORE4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
60 | LGSTORE2_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
61 | LGSTORE2_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 4 | No | No |
62 | LGSTORE2_WALL_3_DOOR_1 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
63 | LGSTORE2_WALL_3_DOOR_2 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
64 | LGSTORE2_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
65 | LGSTORE2_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 4 | No | No |
66 | LGSTORE2_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
67 | LGSTORE2_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
68 | LGSTORE2_WALL_1_WINDOW_3 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
69 | LGSTORE2_WALL_1_WINDOW_4 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
70 | LGSTORE2_WALL_1_DOOR_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
71 | LGSTORE2_WALL_1_DOOR_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
72 | LGSTORE2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
73 | LGSTORE2_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
74 | LGSTORE2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
75 | SMSTORE5_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
76 | SMSTORE5_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
77 | SMSTORE5_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
78 | SMSTORE5_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
79 | SMSTORE5_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
80 | SMSTORE5_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
81 | SMSTORE5_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
82 | SMSTORE5_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
83 | SMSTORE5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
84 | SMSTORE5_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
85 | SMSTORE5_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
86 | SMSTORE6_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
87 | SMSTORE6_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
88 | SMSTORE6_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
89 | SMSTORE6_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
90 | SMSTORE6_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
91 | SMSTORE6_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
92 | SMSTORE6_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
93 | SMSTORE6_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
94 | SMSTORE6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
95 | SMSTORE6_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
96 | SMSTORE6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
97 | SMSTORE7_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
98 | SMSTORE7_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
99 | SMSTORE7_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
100 | SMSTORE7_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
101 | SMSTORE7_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
102 | SMSTORE7_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 3 | No | No |
103 | SMSTORE7_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
104 | SMSTORE7_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
105 | SMSTORE7_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
106 | SMSTORE7_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
107 | SMSTORE7_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
108 | SMSTORE8_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 4 | No | No |
109 | SMSTORE8_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 2 | No | No |
110 | SMSTORE8_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 2 | No | No |
111 | SMSTORE8_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 1 | No | No |
112 | SMSTORE8_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
113 | SMSTORE8_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 3 | No | No |
114 | SMSTORE8_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
115 | SMSTORE8_WALL_4 | 0 | 118.41 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 3 | No | No |
116 | SMSTORE8_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
117 | SMSTORE8_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
118 | SMSTORE8_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | LGSTORE1_INFILTRATION | TYPE1_INFIL_SCH | LGSTORE1 | 348.39 | 56.3 | 0.157 | 4.517E-004 | 2.488E-004 | 0.314 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | LGSTORE1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LGSTORE1 | 348.39 | 56.3 | 0.241 | 6.922E-004 | 3.813E-004 | 0.481 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | SMSTORE1_INFILTRATION | TYPE1_INFIL_SCH | SMSTORE1 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | SMSTORE1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE1 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | SMSTORE2_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE2 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | SMSTORE2_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE2 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | SMSTORE3_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE3 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | SMSTORE3_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE3 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | SMSTORE4_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE4 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | SMSTORE4_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE4 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | LGSTORE2_INFILTRATION | TYPE3_INFIL_SCH | LGSTORE2 | 348.39 | 56.3 | 8.993E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | LGSTORE2_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LGSTORE2 | 348.39 | 56.3 | 0.241 | 6.922E-004 | 4.692E-004 | 0.481 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | SMSTORE5_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE5 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | SMSTORE5_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE5 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | SMSTORE6_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE6 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | SMSTORE6_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE6 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | SMSTORE7_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE7 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
18 | SMSTORE7_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE7 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | SMSTORE8_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE8 | 174.19 | 28.1 | 0.112 | 6.453E-004 | 2.994E-004 | 0.448 | 0.000 | 0.000 | 0.224 | 0.000 |
20 | SMSTORE8_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE8 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 3.583E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | LGSTORE1 | Mixing/Well-Stirred |
2 | SMSTORE1 | Mixing/Well-Stirred |
3 | SMSTORE2 | Mixing/Well-Stirred |
4 | SMSTORE3 | Mixing/Well-Stirred |
5 | SMSTORE4 | Mixing/Well-Stirred |
6 | LGSTORE2 | Mixing/Well-Stirred |
7 | SMSTORE5 | Mixing/Well-Stirred |
8 | SMSTORE6 | Mixing/Well-Stirred |
9 | SMSTORE7 | Mixing/Well-Stirred |
10 | SMSTORE8 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone LGSTORE1 | 1.2000 |
3 | Zone SMSTORE1 | 1.2000 |
4 | Zone SMSTORE2 | 1.2000 |
5 | Zone SMSTORE3 | 1.2000 |
6 | Zone SMSTORE4 | 1.2000 |
7 | Zone LGSTORE2 | 1.2000 |
8 | Zone SMSTORE5 | 1.2000 |
9 | Zone SMSTORE6 | 1.2000 |
10 | Zone SMSTORE7 | 1.2000 |
11 | Zone SMSTORE8 | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone LGSTORE1 | 1.2000 |
3 | Zone SMSTORE1 | 1.2000 |
4 | Zone SMSTORE2 | 1.2000 |
5 | Zone SMSTORE3 | 1.2000 |
6 | Zone SMSTORE4 | 1.2000 |
7 | Zone LGSTORE2 | 1.2000 |
8 | Zone SMSTORE5 | 1.2000 |
9 | Zone SMSTORE6 | 1.2000 |
10 | Zone SMSTORE7 | 1.2000 |
11 | Zone SMSTORE8 | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | LGSTORE1 | Cooling | 21283.54363 | 25540.25235 | 1.92927 | 2.31513 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 33.90000 | 5.47527E-003 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
2 | LGSTORE1 | Heating | 24699.35782 | 29639.22938 | 1.31159 | 1.57391 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -17.90000 | 9.55238E-004 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
3 | SMSTORE1 | Cooling | 11528.67147 | 13834.40576 | 1.04502 | 1.25403 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 33.77667 | 5.47508E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
4 | SMSTORE1 | Heating | 11785.38517 | 14142.46220 | 0.62583 | 0.75100 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -17.90000 | 9.55238E-004 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
5 | SMSTORE2 | Cooling | 12331.86279 | 14798.23534 | 1.09329 | 1.31195 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 25.76000 | 5.46288E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
6 | SMSTORE2 | Heating | 11937.30134 | 14324.76161 | 0.63390 | 0.76068 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -17.90000 | 9.55238E-004 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
7 | SMSTORE3 | Cooling | 12264.66257 | 14717.59508 | 1.08717 | 1.30460 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 25.76000 | 5.46288E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
8 | SMSTORE3 | Heating | 12032.69306 | 14439.23167 | 0.63897 | 0.76676 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -17.90000 | 9.55238E-004 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
9 | SMSTORE4 | Cooling | 12236.03093 | 14683.23711 | 1.08467 | 1.30160 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 25.76000 | 5.46288E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
10 | SMSTORE4 | Heating | 12188.42034 | 14626.10441 | 0.64724 | 0.77668 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -17.90000 | 9.55238E-004 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
11 | LGSTORE2 | Cooling | 20184.05288 | 24220.86345 | 1.82963 | 2.19555 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 33.65333 | 5.47489E-003 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
12 | LGSTORE2 | Heating | 23433.73661 | 28120.48393 | 1.24441 | 1.49329 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -17.90000 | 9.55238E-004 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
13 | SMSTORE5 | Cooling | 10436.12482 | 12523.34979 | 0.94599 | 1.13519 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 33.65333 | 5.47489E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
14 | SMSTORE5 | Heating | 12523.85775 | 15028.62930 | 0.66505 | 0.79806 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -17.90000 | 9.55238E-004 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
15 | SMSTORE6 | Cooling | 10361.19535 | 12433.43442 | 0.93920 | 1.12704 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 33.65333 | 5.47489E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
16 | SMSTORE6 | Heating | 12510.53718 | 15012.64462 | 0.66434 | 0.79721 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -17.90000 | 9.55238E-004 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
17 | SMSTORE7 | Cooling | 10284.79794 | 12341.75753 | 0.93228 | 1.11873 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 33.65333 | 5.47489E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
18 | SMSTORE7 | Heating | 12723.47371 | 15268.16846 | 0.67565 | 0.81078 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -17.90000 | 9.55238E-004 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
19 | SMSTORE8 | Cooling | 10801.92283 | 12962.30740 | 0.97918 | 1.17502 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | 33.16000 | 5.47412E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
20 | SMSTORE8 | Heating | 15209.02619 | 18250.83143 | 0.80761 | 0.96914 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -17.90000 | 9.55238E-004 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC_1:1 | Cooling | Sensible | 29260.31 | 2.31513 | 2.31513 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-AC_1:1 | Heating | Sensible | 44971.82 | 1.57391 | 1.57391 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
3 | PSZ-AC_2:2 | Cooling | Sensible | 15675.02 | 1.25403 | 1.25403 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-AC_2:2 | Heating | Sensible | 21818.64 | 0.75100 | 0.75100 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
5 | PSZ-AC_3:3 | Cooling | Sensible | 15734.37 | 1.31195 | 1.31195 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
6 | PSZ-AC_3:3 | Heating | Sensible | 21998.28 | 0.76068 | 0.76068 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
7 | PSZ-AC_4:4 | Cooling | Sensible | 15775.72 | 1.30460 | 1.30460 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
8 | PSZ-AC_4:4 | Heating | Sensible | 22111.09 | 0.76676 | 0.76676 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
9 | PSZ-AC_5:5 | Cooling | Sensible | 15642.55 | 1.30160 | 1.30160 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
10 | PSZ-AC_5:5 | Heating | Sensible | 22295.24 | 0.77668 | 0.77668 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
11 | PSZ-AC_6:6 | Cooling | Sensible | 27929.50 | 2.19555 | 2.19555 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
12 | PSZ-AC_6:6 | Heating | Sensible | 43475.34 | 1.49329 | 1.49329 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
13 | PSZ-AC_7:7 | Cooling | Sensible | 14371.78 | 1.13519 | 1.13519 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
14 | PSZ-AC_7:7 | Heating | Sensible | 22691.90 | 0.79806 | 0.79806 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
15 | PSZ-AC_8:8 | Cooling | Sensible | 14283.54 | 1.12704 | 1.12704 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
16 | PSZ-AC_8:8 | Heating | Sensible | 22676.15 | 0.79721 | 0.79721 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
17 | PSZ-AC_9:9 | Cooling | Sensible | 14192.93 | 1.11873 | 1.11873 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
18 | PSZ-AC_9:9 | Heating | Sensible | 22927.96 | 0.81078 | 0.81078 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
19 | PSZ-AC_10:10 | Cooling | Sensible | 14698.34 | 1.17502 | 1.17502 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
20 | PSZ-AC_10:10 | Heating | Sensible | 25867.05 | 0.96914 | 0.96914 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | LGSTORE1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.31513 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.25403 |
3 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.31195 |
4 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.30460 |
5 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE4 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.30160 |
6 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | LGSTORE2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.19555 |
7 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE5 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.13519 |
8 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.12704 |
9 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE7 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.11873 |
10 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE8 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.17502 |
11 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.31513 |
12 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.31513 |
13 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.31513 |
14 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 2.31513 |
15 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.31513 |
16 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Main Design Air Flow Rate [m3/s] | 2.31513 |
17 | AirLoopHVAC | PSZ-AC_1:1 | User Heating Air Flow Ratio [] | 1.00000 |
18 | AirLoopHVAC | PSZ-AC_1:1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
19 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.25403 |
20 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.25403 |
21 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.25403 |
22 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.25403 |
23 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.25403 |
24 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Main Design Air Flow Rate [m3/s] | 1.25403 |
25 | AirLoopHVAC | PSZ-AC_2:2 | User Heating Air Flow Ratio [] | 1.00000 |
26 | AirLoopHVAC | PSZ-AC_2:2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
27 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.31195 |
28 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.31195 |
29 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.31195 |
30 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.31195 |
31 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.31195 |
32 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Main Design Air Flow Rate [m3/s] | 1.31195 |
33 | AirLoopHVAC | PSZ-AC_3:3 | User Heating Air Flow Ratio [] | 1.00000 |
34 | AirLoopHVAC | PSZ-AC_3:3 | Calculated Heating Air Flow Ratio [] | 1.00000 |
35 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.30460 |
36 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.30460 |
37 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.30460 |
38 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.30460 |
39 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.30460 |
40 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Main Design Air Flow Rate [m3/s] | 1.30460 |
41 | AirLoopHVAC | PSZ-AC_4:4 | User Heating Air Flow Ratio [] | 1.00000 |
42 | AirLoopHVAC | PSZ-AC_4:4 | Calculated Heating Air Flow Ratio [] | 1.00000 |
43 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.30160 |
44 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.30160 |
45 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.30160 |
46 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.30160 |
47 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.30160 |
48 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Main Design Air Flow Rate [m3/s] | 1.30160 |
49 | AirLoopHVAC | PSZ-AC_5:5 | User Heating Air Flow Ratio [] | 1.00000 |
50 | AirLoopHVAC | PSZ-AC_5:5 | Calculated Heating Air Flow Ratio [] | 1.00000 |
51 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.19555 |
52 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.19555 |
53 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.19555 |
54 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Heating Design Air Flow Rate [m3/s] | 2.19555 |
55 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.19555 |
56 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Main Design Air Flow Rate [m3/s] | 2.19555 |
57 | AirLoopHVAC | PSZ-AC_6:6 | User Heating Air Flow Ratio [] | 1.00000 |
58 | AirLoopHVAC | PSZ-AC_6:6 | Calculated Heating Air Flow Ratio [] | 1.00000 |
59 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.13519 |
60 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.13519 |
61 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.13519 |
62 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.13519 |
63 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.13519 |
64 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Main Design Air Flow Rate [m3/s] | 1.13519 |
65 | AirLoopHVAC | PSZ-AC_7:7 | User Heating Air Flow Ratio [] | 1.00000 |
66 | AirLoopHVAC | PSZ-AC_7:7 | Calculated Heating Air Flow Ratio [] | 1.00000 |
67 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.12704 |
68 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.12704 |
69 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.12704 |
70 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.12704 |
71 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.12704 |
72 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Main Design Air Flow Rate [m3/s] | 1.12704 |
73 | AirLoopHVAC | PSZ-AC_8:8 | User Heating Air Flow Ratio [] | 1.00000 |
74 | AirLoopHVAC | PSZ-AC_8:8 | Calculated Heating Air Flow Ratio [] | 1.00000 |
75 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.11873 |
76 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.11873 |
77 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.11873 |
78 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.11873 |
79 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.11873 |
80 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Main Design Air Flow Rate [m3/s] | 1.11873 |
81 | AirLoopHVAC | PSZ-AC_9:9 | User Heating Air Flow Ratio [] | 1.00000 |
82 | AirLoopHVAC | PSZ-AC_9:9 | Calculated Heating Air Flow Ratio [] | 1.00000 |
83 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.17502 |
84 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.17502 |
85 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.17502 |
86 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.17502 |
87 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.17502 |
88 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Main Design Air Flow Rate [m3/s] | 1.17502 |
89 | AirLoopHVAC | PSZ-AC_10:10 | User Heating Air Flow Ratio [] | 1.00000 |
90 | AirLoopHVAC | PSZ-AC_10:10 | Calculated Heating Air Flow Ratio [] | 1.00000 |
91 | AirLoopHVAC | PSZ-AC_1:1 | Design Supply Air Flow Rate [m3/s] | 2.31513 |
92 | AirLoopHVAC | PSZ-AC_2:2 | Design Supply Air Flow Rate [m3/s] | 1.25403 |
93 | AirLoopHVAC | PSZ-AC_3:3 | Design Supply Air Flow Rate [m3/s] | 1.31195 |
94 | AirLoopHVAC | PSZ-AC_4:4 | Design Supply Air Flow Rate [m3/s] | 1.30460 |
95 | AirLoopHVAC | PSZ-AC_5:5 | Design Supply Air Flow Rate [m3/s] | 1.30160 |
96 | AirLoopHVAC | PSZ-AC_6:6 | Design Supply Air Flow Rate [m3/s] | 2.19555 |
97 | AirLoopHVAC | PSZ-AC_7:7 | Design Supply Air Flow Rate [m3/s] | 1.13519 |
98 | AirLoopHVAC | PSZ-AC_8:8 | Design Supply Air Flow Rate [m3/s] | 1.12704 |
99 | AirLoopHVAC | PSZ-AC_9:9 | Design Supply Air Flow Rate [m3/s] | 1.11873 |
100 | AirLoopHVAC | PSZ-AC_10:10 | Design Supply Air Flow Rate [m3/s] | 1.17502 |
101 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.31513 |
102 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41148 |
103 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.31513 |
104 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 2477.29724 |
105 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.31513 |
106 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.31513 |
107 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.31513 |
108 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.52799 |
109 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.31513 |
110 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.15756 |
111 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.54342 |
112 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 38323.60000 |
113 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 19161.80000 |
114 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80066 |
115 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80066 |
116 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 38323.60000 |
117 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 58726.77636 |
118 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
119 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
120 | Coil:Heating:Fuel | PSZ-AC_1:1 HEATING COIL | Design Size Nominal Capacity [W] | 58726.77636 |
121 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.25403 |
122 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
123 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.25403 |
124 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1388.40778 |
125 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.25403 |
126 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.25403 |
127 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.25403 |
128 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.82766 |
129 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.25403 |
130 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.62701 |
131 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.83602 |
132 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 20758.61000 |
133 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 10379.30500 |
134 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80066 |
135 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80066 |
136 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 20758.61000 |
137 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 31153.39519 |
138 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
139 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
140 | Coil:Heating:Fuel | PSZ-AC_2:2 HEATING COIL | Design Size Nominal Capacity [W] | 31153.39519 |
141 | Controller:OutdoorAir | PSZ-AC_3:3_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.31195 |
142 | Controller:OutdoorAir | PSZ-AC_3:3_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
143 | Fan:SystemModel | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.31195 |
144 | Fan:SystemModel | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1452.54073 |
145 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.31195 |
146 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.31195 |
147 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.31195 |
148 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.86589 |
149 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.31195 |
150 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.65598 |
151 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.87463 |
152 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 21717.49000 |
153 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 10858.74500 |
154 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80066 |
155 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80066 |
156 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 21717.49000 |
157 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 32228.33316 |
158 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
159 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
160 | Coil:Heating:Fuel | PSZ-AC_3:3 HEATING COIL | Design Size Nominal Capacity [W] | 32228.33316 |
161 | Controller:OutdoorAir | PSZ-AC_4:4_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.30460 |
162 | Controller:OutdoorAir | PSZ-AC_4:4_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
163 | Fan:SystemModel | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.30460 |
164 | Fan:SystemModel | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1444.39864 |
165 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.30460 |
166 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.30460 |
167 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.30460 |
168 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.86104 |
169 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.30460 |
170 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.65230 |
171 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.86973 |
172 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 21595.75000 |
173 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 10797.87500 |
174 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80066 |
175 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80066 |
176 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 21595.75000 |
177 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 32091.86182 |
178 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
179 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
180 | Coil:Heating:Fuel | PSZ-AC_4:4 HEATING COIL | Design Size Nominal Capacity [W] | 32091.86182 |
181 | Controller:OutdoorAir | PSZ-AC_5:5_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.30160 |
182 | Controller:OutdoorAir | PSZ-AC_5:5_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
183 | Fan:SystemModel | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.30160 |
184 | Fan:SystemModel | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1441.07729 |
185 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.30160 |
186 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.30160 |
187 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.30160 |
188 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.85906 |
189 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.30160 |
190 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.65080 |
191 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.86773 |
192 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 21546.09000 |
193 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 10773.04500 |
194 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80066 |
195 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80066 |
196 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 21546.09000 |
197 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 32036.18827 |
198 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
199 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
200 | Coil:Heating:Fuel | PSZ-AC_5:5 HEATING COIL | Design Size Nominal Capacity [W] | 32036.18827 |
201 | Controller:OutdoorAir | PSZ-AC_6:6_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.19555 |
202 | Controller:OutdoorAir | PSZ-AC_6:6_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41148 |
203 | Fan:SystemModel | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.19555 |
204 | Fan:SystemModel | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 2349.34576 |
205 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.19555 |
206 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.19555 |
207 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.19555 |
208 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.44907 |
209 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.19555 |
210 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.09778 |
211 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.46370 |
212 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 36344.20000 |
213 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 18172.10000 |
214 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80066 |
215 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80066 |
216 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 36344.20000 |
217 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 56507.16135 |
218 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
219 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
220 | Coil:Heating:Fuel | PSZ-AC_6:6 HEATING COIL | Design Size Nominal Capacity [W] | 56507.16135 |
221 | Controller:OutdoorAir | PSZ-AC_7:7_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.13519 |
222 | Controller:OutdoorAir | PSZ-AC_7:7_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
223 | Fan:SystemModel | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.13519 |
224 | Fan:SystemModel | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1256.83626 |
225 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.13519 |
226 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.13519 |
227 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.13519 |
228 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.13519 |
229 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.13519 |
230 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.56760 |
231 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.75679 |
232 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 18791.44000 |
233 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 9395.72000 |
234 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80066 |
235 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80066 |
236 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 18791.44000 |
237 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 28948.08898 |
238 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
239 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
240 | Coil:Heating:Fuel | PSZ-AC_7:7 HEATING COIL | Design Size Nominal Capacity [W] | 28948.08898 |
241 | Controller:OutdoorAir | PSZ-AC_8:8_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.12704 |
242 | Controller:OutdoorAir | PSZ-AC_8:8_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
243 | Fan:SystemModel | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.12704 |
244 | Fan:SystemModel | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1247.81256 |
245 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.12704 |
246 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.12704 |
247 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.12704 |
248 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.12704 |
249 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.12704 |
250 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.56352 |
251 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.75136 |
252 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 18656.52000 |
253 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 9328.26000 |
254 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80066 |
255 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80066 |
256 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 18656.52000 |
257 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 28796.84185 |
258 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
259 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
260 | Coil:Heating:Fuel | PSZ-AC_8:8 HEATING COIL | Design Size Nominal Capacity [W] | 28796.84185 |
261 | Controller:OutdoorAir | PSZ-AC_9:9_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.11873 |
262 | Controller:OutdoorAir | PSZ-AC_9:9_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
263 | Fan:SystemModel | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.11873 |
264 | Fan:SystemModel | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1238.61198 |
265 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.11873 |
266 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.11873 |
267 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.11873 |
268 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.11873 |
269 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.11873 |
270 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.55937 |
271 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.74582 |
272 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 18518.96000 |
273 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 9259.48000 |
274 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80066 |
275 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80066 |
276 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 18518.96000 |
277 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 28642.62998 |
278 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
279 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
280 | Coil:Heating:Fuel | PSZ-AC_9:9 HEATING COIL | Design Size Nominal Capacity [W] | 28642.62998 |
281 | Controller:OutdoorAir | PSZ-AC_10:10_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.17502 |
282 | Controller:OutdoorAir | PSZ-AC_10:10_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
283 | Fan:SystemModel | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.17502 |
284 | Fan:SystemModel | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1300.93314 |
285 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.17502 |
286 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.17502 |
287 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.17502 |
288 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.77551 |
289 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.17502 |
290 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.58751 |
291 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.78335 |
292 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 19450.75000 |
293 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 9725.37500 |
294 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80066 |
295 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80066 |
296 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 19450.75000 |
297 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 29687.79500 |
298 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
299 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
300 | Coil:Heating:Fuel | PSZ-AC_10:10 HEATING COIL | Design Size Nominal Capacity [W] | 29687.79500 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | 36509.2 | 11.11 | 11.11 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | 19775.8 | 11.11 | 11.11 | |||
3 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | 20689.3 | 11.11 | 11.11 | |||
4 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | 20573.3 | 11.11 | 11.11 | |||
5 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | 20526.0 | 11.11 | 11.11 | |||
6 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | 34623.5 | 11.11 | 11.11 | |||
7 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | 17901.8 | 11.83 | 11.83 | |||
8 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | 17773.2 | 11.83 | 11.83 | |||
9 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | 17642.2 | 11.83 | 11.83 | |||
10 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | 18529.9 | 11.11 | 11.11 |
Zone Name | # Surfaces | |
1 | LGSTORE1 | 15 |
2 | SMSTORE1 | 11 |
3 | SMSTORE2 | 11 |
4 | SMSTORE3 | 11 |
5 | SMSTORE4 | 11 |
6 | LGSTORE2 | 15 |
7 | SMSTORE5 | 11 |
8 | SMSTORE6 | 11 |
9 | SMSTORE7 | 11 |
10 | SMSTORE8 | 11 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | LGSTORE1_WALL_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.540 | 0.499 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | LGSTORE1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.540 | 0.499 | 71.15 | 78.94 | 71.15 | 0.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | LGSTORE1_WALL_3_DOOR_1 | Door | LGSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
4 | LGSTORE1_WALL_3_DOOR_2 | Door | LGSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
5 | LGSTORE1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
6 | LGSTORE1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.540 | 0.499 | 58.18 | 78.94 | 58.18 | 180.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
7 | LGSTORE1_WALL_1_WINDOW_1 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.362_SHGC_0.379 | N/A | 2.057 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
8 | LGSTORE1_WALL_1_WINDOW_2 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.362_SHGC_0.379 | N/A | 2.057 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
9 | LGSTORE1_WALL_1_WINDOW_3 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.362_SHGC_0.379 | N/A | 2.057 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
10 | LGSTORE1_WALL_1_WINDOW_4 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.362_SHGC_0.379 | N/A | 2.057 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
11 | LGSTORE1_WALL_1_DOOR_1 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.362_SHGC_0.379 | N/A | 2.057 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
12 | LGSTORE1_WALL_1_DOOR_2 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.362_SHGC_0.379 | N/A | 2.057 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
13 | LGSTORE1_FLOOR | Floor | CTF - ConductionTransferFunction | LGSTORE1_FLOOR_FFACTOR | 0.141 | 0.136 | 348.39 | 348.39 | 348.39 | 270.00 | 180.00 | 22.86 | 15.24 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | LGSTORE1_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 348.39 | 348.39 | 348.39 | 270.00 | 0.00 | 22.86 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
15 | LGSTORE1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 696.77 | 696.77 | 696.77 | 0.00 | 90.00 | 696.77 | 1.00 | 0.00 | LGSTORE1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
16 | SMSTORE1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.540 | 0.499 | 29.09 | 39.47 | 29.09 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
17 | SMSTORE1_WALL_1_WINDOW_1 | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.362_SHGC_0.379 | N/A | 2.057 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
18 | SMSTORE1_WALL_1_WINDOW_2 | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.362_SHGC_0.379 | N/A | 2.057 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
19 | SMSTORE1_WALL_1_DOOR | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.362_SHGC_0.379 | N/A | 2.057 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
20 | SMSTORE1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | SMSTORE1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.540 | 0.499 | 35.57 | 39.47 | 35.57 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | SMSTORE1_WALL_3_DOOR | Door | SMSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
23 | SMSTORE1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE2_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | SMSTORE1_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE1_FLOOR_FFACTOR | 7.972E-002 | 7.821E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | SMSTORE1_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
26 | SMSTORE1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
27 | SMSTORE2_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.540 | 0.499 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | SMSTORE2_WALL_1_WINDOW_1 | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.362_SHGC_0.379 | N/A | 2.057 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
29 | SMSTORE2_WALL_1_WINDOW_2 | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.362_SHGC_0.379 | N/A | 2.057 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
30 | SMSTORE2_WALL_1_DOOR | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.362_SHGC_0.379 | N/A | 2.057 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
31 | SMSTORE2_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | SMSTORE2_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.540 | 0.499 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | SMSTORE2_WALL_3_DOOR | Door | SMSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
34 | SMSTORE2_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE3_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | SMSTORE2_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE2_FLOOR_FFACTOR | 7.972E-002 | 7.821E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | SMSTORE2_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | SMSTORE2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | SMSTORE3_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.540 | 0.499 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | SMSTORE3_WALL_1_WINDOW_1 | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.362_SHGC_0.379 | N/A | 2.057 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
40 | SMSTORE3_WALL_1_WINDOW_2 | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.362_SHGC_0.379 | N/A | 2.057 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
41 | SMSTORE3_WALL_1_DOOR | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.362_SHGC_0.379 | N/A | 2.057 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
42 | SMSTORE3_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE2_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | SMSTORE3_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.540 | 0.499 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | SMSTORE3_WALL_3_DOOR | Door | SMSTORE3_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
45 | SMSTORE3_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE4_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | SMSTORE3_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE3_FLOOR_FFACTOR | 7.972E-002 | 7.821E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
47 | SMSTORE3_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
48 | SMSTORE3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
49 | SMSTORE4_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.540 | 0.499 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | SMSTORE4_WALL_1_WINDOW_1 | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.362_SHGC_0.379 | N/A | 2.057 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
51 | SMSTORE4_WALL_1_WINDOW_2 | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.362_SHGC_0.379 | N/A | 2.057 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
52 | SMSTORE4_WALL_1_DOOR | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.362_SHGC_0.379 | N/A | 2.057 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | SMSTORE4_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE3_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | SMSTORE4_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.540 | 0.499 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | SMSTORE4_WALL_3_DOOR | Door | SMSTORE4_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | SMSTORE4_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE2_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | SMSTORE4_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE4_FLOOR_FFACTOR | 7.972E-002 | 7.821E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | SMSTORE4_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | SMSTORE4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | LGSTORE2_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE4_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | LGSTORE2_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.540 | 0.499 | 71.19 | 78.94 | 71.19 | 0.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
62 | LGSTORE2_WALL_3_DOOR_1 | Door | LGSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
63 | LGSTORE2_WALL_3_DOOR_2 | Door | LGSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
64 | LGSTORE2_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE5_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LGSTORE2_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.540 | 0.499 | 58.22 | 78.94 | 58.22 | 180.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
66 | LGSTORE2_WALL_1_WINDOW_1 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.362_SHGC_0.379 | N/A | 2.057 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | LGSTORE2_WALL_1_WINDOW_2 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.362_SHGC_0.379 | N/A | 2.057 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | LGSTORE2_WALL_1_WINDOW_3 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.362_SHGC_0.379 | N/A | 2.057 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | LGSTORE2_WALL_1_WINDOW_4 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.362_SHGC_0.379 | N/A | 2.057 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LGSTORE2_WALL_1_DOOR_1 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.362_SHGC_0.379 | N/A | 2.057 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
71 | LGSTORE2_WALL_1_DOOR_2 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.362_SHGC_0.379 | N/A | 2.057 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
72 | LGSTORE2_FLOOR | Floor | CTF - ConductionTransferFunction | LGSTORE2_FLOOR_FFACTOR | 7.972E-002 | 7.821E-002 | 348.39 | 348.39 | 348.39 | 270.00 | 180.00 | 22.86 | 15.24 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
73 | LGSTORE2_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 348.39 | 348.39 | 348.39 | 270.00 | 0.00 | 22.86 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
74 | LGSTORE2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 696.77 | 696.77 | 696.77 | 0.00 | 90.00 | 696.77 | 1.00 | 0.00 | LGSTORE2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
75 | SMSTORE5_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.540 | 0.499 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | SMSTORE5_WALL_1_WINDOW_1 | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.362_SHGC_0.379 | N/A | 2.057 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
77 | SMSTORE5_WALL_1_WINDOW_2 | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.362_SHGC_0.379 | N/A | 2.057 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | SMSTORE5_WALL_1_DOOR | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.362_SHGC_0.379 | N/A | 2.057 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
79 | SMSTORE5_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE2_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | SMSTORE5_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.540 | 0.499 | 35.59 | 39.47 | 35.59 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | SMSTORE5_WALL_3_DOOR | Door | SMSTORE5_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
82 | SMSTORE5_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE6_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
83 | SMSTORE5_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE5_FLOOR_FFACTOR | 7.972E-002 | 7.821E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
84 | SMSTORE5_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
85 | SMSTORE5_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE5_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | SMSTORE6_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.540 | 0.499 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | SMSTORE6_WALL_1_WINDOW_1 | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.362_SHGC_0.379 | N/A | 2.057 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | SMSTORE6_WALL_1_WINDOW_2 | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.362_SHGC_0.379 | N/A | 2.057 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
89 | SMSTORE6_WALL_1_DOOR | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.362_SHGC_0.379 | N/A | 2.057 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | SMSTORE6_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE5_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | SMSTORE6_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.540 | 0.499 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | SMSTORE6_WALL_3_DOOR | Door | SMSTORE6_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
93 | SMSTORE6_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE7_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | SMSTORE6_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE6_FLOOR_FFACTOR | 7.972E-002 | 7.821E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
95 | SMSTORE6_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
96 | SMSTORE6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
97 | SMSTORE7_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.540 | 0.499 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | SMSTORE7_WALL_1_WINDOW_1 | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.362_SHGC_0.379 | N/A | 2.057 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | SMSTORE7_WALL_1_WINDOW_2 | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.362_SHGC_0.379 | N/A | 2.057 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
100 | SMSTORE7_WALL_1_DOOR | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.362_SHGC_0.379 | N/A | 2.057 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
101 | SMSTORE7_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE6_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
102 | SMSTORE7_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.540 | 0.499 | 35.59 | 39.47 | 35.59 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | SMSTORE7_WALL_3_DOOR | Door | SMSTORE7_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
104 | SMSTORE7_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE8_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | SMSTORE7_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE7_FLOOR_FFACTOR | 7.972E-002 | 7.821E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
106 | SMSTORE7_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
107 | SMSTORE7_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE7_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
108 | SMSTORE8_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.540 | 0.499 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | SMSTORE8_WALL_1_WINDOW_1 | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.362_SHGC_0.379 | N/A | 2.057 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
110 | SMSTORE8_WALL_1_WINDOW_2 | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.362_SHGC_0.379 | N/A | 2.057 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
111 | SMSTORE8_WALL_1_DOOR | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.362_SHGC_0.379 | N/A | 2.057 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
112 | SMSTORE8_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE7_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | SMSTORE8_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.540 | 0.499 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | SMSTORE8_WALL_3_DOOR | Door | SMSTORE8_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
115 | SMSTORE8_WALL_4 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.540 | 0.499 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | SMSTORE8_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE8_FLOOR_FFACTOR | 0.203 | 0.194 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | SMSTORE8_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | SMSTORE8_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE8_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | LGSTORE1 | RunPeriod: RUNPERIOD 1 | 3.1704624392E-002 | 0.1785537069 | Pass | Pass | 0.3854870871 | 1.2918702092 | Pass | Pass |
2 | SMSTORE1 | RunPeriod: RUNPERIOD 1 | 5.2595713438E-002 | 0.1432626662 | Pass | Pass | 0.1454271768 | 0.6053186616 | Pass | Pass |
3 | SMSTORE2 | RunPeriod: RUNPERIOD 1 | 3.5297430893E-002 | 0.1758142689 | Pass | Pass | 0.4447805674 | 2.8191970973 | Pass | Pass |
4 | SMSTORE3 | RunPeriod: RUNPERIOD 1 | 3.3324178104E-002 | 0.1823275089 | Pass | Pass | 0.3014630510 | 1.2493091226 | Pass | Pass |
5 | SMSTORE4 | RunPeriod: RUNPERIOD 1 | 3.7095698364E-002 | 0.1961367065 | Pass | Pass | 0.2779477902 | 1.2707196259 | Pass | Pass |
6 | LGSTORE2 | RunPeriod: RUNPERIOD 1 | 4.4803004878E-002 | 0.2258829264 | Pass | Pass | 0.1557620358 | 0.6071953331 | Pass | Pass |
7 | SMSTORE5 | RunPeriod: RUNPERIOD 1 | 4.8264585739E-002 | 0.2374079644 | Pass | Pass | 0.2527318569 | 0.7470875351 | Pass | Pass |
8 | SMSTORE6 | RunPeriod: RUNPERIOD 1 | 4.7148697088E-002 | 0.2434394995 | Pass | Pass | 0.1837058273 | 0.8015381989 | Pass | Pass |
9 | SMSTORE7 | RunPeriod: RUNPERIOD 1 | 5.3463408237E-002 | 0.2603004690 | Pass | Pass | 0.1604483922 | 0.8233522057 | Pass | Pass |
10 | SMSTORE8 | RunPeriod: RUNPERIOD 1 | 7.6858300339E-002 | 0.3764181574 | Pass | Pass | 4.6969930058E-002 | 0.1095688699 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:01
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 4686.30 | 179.04 | 0.00 | 478.09 | 483.87 | 5827.31 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:01
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | -17.90 | 0.00 | -17.90 | Wetbulb [C] | 2.50 | 180.00 |
DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 33.90 | 14.80 | 15.00 | Wetbulb [C] | 3.60 | 30.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 11.00 | 10 | |||
Feb | 15.00 | 16 | |||
Mar | 88.00 | 32 | |||
Apr | 159.00 | 54 | |||
May | 30.00 | 24 | |||
Jun | 11.00 | 4 | |||
Jul | 167.00 | 26 | |||
Aug | 33.00 | 24 | |||
Sep | 8.00 | 8 | |||
Oct | 13.00 | 10 | |||
Nov | 12.00 | 22 | |||
Dec | 11.00 | 18 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:01
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_2 | NONRES_EXT_WALL_GRD | 0.30 | 0.499 | 0.540 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE1_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.499 | 0.540 | 78.94 | 71.15 | 0.00 | 90.00 | N |
LGSTORE1_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.499 | 0.540 | 78.94 | 58.18 | 180.00 | 90.00 | S |
LGSTORE1_FLOOR | LGSTORE1_FLOOR_FFACTOR | 1.00 | 0.138 | 0.141 | 348.39 | 348.39 | 270.00 | 180.00 | |
LGSTORE1_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 348.39 | 348.39 | 270.00 | 0.00 | |
SMSTORE1_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.499 | 0.540 | 39.47 | 29.09 | 180.00 | 90.00 | S |
SMSTORE1_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.499 | 0.540 | 39.47 | 35.57 | 0.00 | 90.00 | N |
SMSTORE1_FLOOR | SMSTORE1_FLOOR_FFACTOR | 1.00 | 0.079 | 0.080 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE1_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE2_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.499 | 0.540 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE2_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.499 | 0.540 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE2_FLOOR | SMSTORE2_FLOOR_FFACTOR | 1.00 | 0.079 | 0.080 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE2_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE3_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.499 | 0.540 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE3_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.499 | 0.540 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE3_FLOOR | SMSTORE3_FLOOR_FFACTOR | 1.00 | 0.079 | 0.080 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE3_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE4_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.499 | 0.540 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE4_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.499 | 0.540 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE4_FLOOR | SMSTORE4_FLOOR_FFACTOR | 1.00 | 0.079 | 0.080 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE4_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
LGSTORE2_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.499 | 0.540 | 78.94 | 71.19 | 0.00 | 90.00 | N |
LGSTORE2_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.499 | 0.540 | 78.94 | 58.22 | 180.00 | 90.00 | S |
LGSTORE2_FLOOR | LGSTORE2_FLOOR_FFACTOR | 1.00 | 0.079 | 0.080 | 348.39 | 348.39 | 270.00 | 180.00 | |
LGSTORE2_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 348.39 | 348.39 | 270.00 | 0.00 | |
SMSTORE5_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.499 | 0.540 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE5_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.499 | 0.540 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE5_FLOOR | SMSTORE5_FLOOR_FFACTOR | 1.00 | 0.079 | 0.080 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE5_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE6_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.499 | 0.540 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE6_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.499 | 0.540 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE6_FLOOR | SMSTORE6_FLOOR_FFACTOR | 1.00 | 0.079 | 0.080 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE6_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE7_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.499 | 0.540 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE7_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.499 | 0.540 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE7_FLOOR | SMSTORE7_FLOOR_FFACTOR | 1.00 | 0.079 | 0.080 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE7_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE8_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.499 | 0.540 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE8_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.499 | 0.540 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE8_WALL_4 | NONRES_EXT_WALL_GRD | 0.30 | 0.499 | 0.540 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE8_FLOOR | SMSTORE8_FLOOR_FFACTOR | 1.00 | 0.197 | 0.203 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE8_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE1_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE2_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE2_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE3_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE3_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE4_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE4_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
LGSTORE2_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE2_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE5_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE5_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE6_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE6_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE7_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE7_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE8_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 696.77 | 0.00 | 90.00 | N | ||
SMSTORE1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
LGSTORE2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 696.77 | 0.00 | 90.00 | N | ||
SMSTORE5_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE7_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE8_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.362_SHGC_0.379 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.057 | 0.380 | 0.418 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.362_SHGC_0.379 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.057 | 0.380 | 0.418 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_3 | NONRESWINDOW_U_0.362_SHGC_0.379 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.057 | 0.380 | 0.418 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_4 | NONRESWINDOW_U_0.362_SHGC_0.379 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.057 | 0.380 | 0.418 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_DOOR_1 | NONRESWINDOW_U_0.362_SHGC_0.379 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.057 | 0.380 | 0.418 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_DOOR_2 | NONRESWINDOW_U_0.362_SHGC_0.379 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.057 | 0.380 | 0.418 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.362_SHGC_0.379 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.057 | 0.380 | 0.418 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.362_SHGC_0.379 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.057 | 0.380 | 0.418 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_DOOR | NONRESWINDOW_U_0.362_SHGC_0.379 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.057 | 0.380 | 0.418 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.362_SHGC_0.379 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.057 | 0.380 | 0.418 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.362_SHGC_0.379 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.057 | 0.380 | 0.418 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_DOOR | NONRESWINDOW_U_0.362_SHGC_0.379 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.057 | 0.380 | 0.418 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.362_SHGC_0.379 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.057 | 0.380 | 0.418 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.362_SHGC_0.379 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.057 | 0.380 | 0.418 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_DOOR | NONRESWINDOW_U_0.362_SHGC_0.379 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.057 | 0.380 | 0.418 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.362_SHGC_0.379 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.057 | 0.380 | 0.418 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.362_SHGC_0.379 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.057 | 0.380 | 0.418 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_DOOR | NONRESWINDOW_U_0.362_SHGC_0.379 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.057 | 0.380 | 0.418 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.362_SHGC_0.379 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.057 | 0.380 | 0.418 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.362_SHGC_0.379 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.057 | 0.380 | 0.418 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_3 | NONRESWINDOW_U_0.362_SHGC_0.379 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.057 | 0.380 | 0.418 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_4 | NONRESWINDOW_U_0.362_SHGC_0.379 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.057 | 0.380 | 0.418 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_DOOR_1 | NONRESWINDOW_U_0.362_SHGC_0.379 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.057 | 0.380 | 0.418 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_DOOR_2 | NONRESWINDOW_U_0.362_SHGC_0.379 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.057 | 0.380 | 0.418 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.362_SHGC_0.379 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.057 | 0.380 | 0.418 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.362_SHGC_0.379 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.057 | 0.380 | 0.418 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_DOOR | NONRESWINDOW_U_0.362_SHGC_0.379 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.057 | 0.380 | 0.418 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.362_SHGC_0.379 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.057 | 0.380 | 0.418 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.362_SHGC_0.379 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.057 | 0.380 | 0.418 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_DOOR | NONRESWINDOW_U_0.362_SHGC_0.379 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.057 | 0.380 | 0.418 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.362_SHGC_0.379 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.057 | 0.380 | 0.418 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.362_SHGC_0.379 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.057 | 0.380 | 0.418 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_DOOR | NONRESWINDOW_U_0.362_SHGC_0.379 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.057 | 0.380 | 0.418 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.362_SHGC_0.379 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.057 | 0.380 | 0.418 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.362_SHGC_0.379 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.057 | 0.380 | 0.418 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_DOOR | NONRESWINDOW_U_0.362_SHGC_0.379 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.057 | 0.380 | 0.418 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
Total or Average | 124.40 | 2.057 | 0.380 | 0.418 | |||||||||||||||||
North Total or Average | 0.00 | - | - | - | |||||||||||||||||
Non-North Total or Average | 124.40 | 2.057 | 0.380 | 0.418 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
LGSTORE1_WALL_3_DOOR_1 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.90 | LGSTORE1_WALL_3 |
LGSTORE1_WALL_3_DOOR_2 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.90 | LGSTORE1_WALL_3 |
SMSTORE1_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.90 | SMSTORE1_WALL_3 |
SMSTORE2_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE2_WALL_3 |
SMSTORE3_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE3_WALL_3 |
SMSTORE4_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE4_WALL_3 |
LGSTORE2_WALL_3_DOOR_1 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | LGSTORE2_WALL_3 |
LGSTORE2_WALL_3_DOOR_2 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | LGSTORE2_WALL_3 |
SMSTORE5_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE5_WALL_3 |
SMSTORE6_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE6_WALL_3 |
SMSTORE7_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE7_WALL_3 |
SMSTORE8_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE8_WALL_3 |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:01
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
LGSTORE1_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_DOOR_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_DOOR_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_DOOR_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_DOOR_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:01
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
LGSTORE1_LIGHTS | LGSTORE1 | LGSTORE1 | GENERAL | 9.6053 | 348.39 | 3346.35 | LightsWired | LTG_SCH_BASE_LPD1 | 83.91 | 168.00 | 82.62 | 0.0000 | Y | 51.90 |
LGSTORE1_LIGHTS_ALLOWANCE | LGSTORE1 | LGSTORE1 | GENERAL | 5.6969 | 348.39 | 1984.73 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | 97.50 | 112.00 | 94.53 | 0.0000 | Y | 35.22 |
SMSTORE1_LIGHTS | SMSTORE1 | SMSTORE1 | GENERAL | 9.7206 | 174.19 | 1693.26 | LightsWired | LTG_SCH_BASE_SMALL_LPD1 | 85.41 | 168.00 | 84.05 | 0.0000 | Y | 26.72 |
SMSTORE1_LIGHTS_ALLOWANCE | SMSTORE1 | SMSTORE1 | GENERAL | 8.5685 | 174.19 | 1492.57 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | 97.50 | 112.00 | 94.53 | 0.0000 | Y | 26.49 |
SMSTORE2_LIGHTS | SMSTORE2 | SMSTORE2 | GENERAL | 9.6995 | 174.19 | 1689.58 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 68.73 | 168.00 | 65.95 | 0.0000 | Y | 20.92 |
SMSTORE2_LIGHTS_ALLOWANCE | SMSTORE2 | SMSTORE2 | GENERAL | 6.9539 | 174.19 | 1211.32 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 84.29 | 73.25 | 0.0000 | Y | 16.66 |
SMSTORE3_LIGHTS | SMSTORE3 | SMSTORE3 | GENERAL | 9.6995 | 174.19 | 1689.58 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 68.73 | 168.00 | 65.95 | 0.0000 | Y | 20.92 |
SMSTORE3_LIGHTS_ALLOWANCE | SMSTORE3 | SMSTORE3 | GENERAL | 6.9539 | 174.19 | 1211.32 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 84.29 | 73.25 | 0.0000 | Y | 16.66 |
SMSTORE4_LIGHTS | SMSTORE4 | SMSTORE4 | GENERAL | 9.6995 | 174.19 | 1689.58 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 68.73 | 168.00 | 65.95 | 0.0000 | Y | 20.92 |
SMSTORE4_LIGHTS_ALLOWANCE | SMSTORE4 | SMSTORE4 | GENERAL | 6.9539 | 174.19 | 1211.32 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 84.29 | 73.25 | 0.0000 | Y | 16.66 |
LGSTORE2_LIGHTS | LGSTORE2 | LGSTORE2 | GENERAL | 9.5842 | 348.39 | 3339.00 | LightsWired | LTG_SCH_BASE_LPD2 | 62.11 | 168.00 | 59.29 | 0.0000 | Y | 37.16 |
LGSTORE2_LIGHTS_ALLOWANCE | LGSTORE2 | LGSTORE2 | GENERAL | 0.0000 | 348.39 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE5_LIGHTS | SMSTORE5 | SMSTORE5 | GENERAL | 9.6995 | 174.19 | 1689.58 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 60.29 | 0.0000 | Y | 19.12 |
SMSTORE5_LIGHTS_ALLOWANCE | SMSTORE5 | SMSTORE5 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE6_LIGHTS | SMSTORE6 | SMSTORE6 | GENERAL | 9.6995 | 174.19 | 1689.58 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 60.29 | 0.0000 | Y | 19.12 |
SMSTORE6_LIGHTS_ALLOWANCE | SMSTORE6 | SMSTORE6 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE7_LIGHTS | SMSTORE7 | SMSTORE7 | GENERAL | 9.6995 | 174.19 | 1689.58 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 60.29 | 0.0000 | Y | 19.12 |
SMSTORE7_LIGHTS_ALLOWANCE | SMSTORE7 | SMSTORE7 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE8_LIGHTS | SMSTORE8 | SMSTORE8 | GENERAL | 9.6995 | 174.19 | 1689.58 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 60.29 | 0.0000 | Y | 19.12 |
SMSTORE8_LIGHTS_ALLOWANCE | SMSTORE8 | SMSTORE8 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
Interior Lighting Total | 6.5342 | 4180.64 | 27316.92 | 366.68 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 455.59 | AstronomicalClock | - | 42.26 | 42.26 | 3.61 | |
EXTERIOR_LIGHTS_B | 2744.24 | AstronomicalClock | - | 83.67 | 62.97 | 32.44 | |
EXTERIOR_LIGHTS_C | 2307.23 | AstronomicalClock | - | 83.67 | 55.97 | 24.24 | |
Exterior Lighting Total | 5507.06 | 60.29 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:01
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 38323.60 | 30684.17 | 7639.43 | 0.80 | 3.80 | |||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 20758.61 | 16620.59 | 4138.02 | 0.80 | 3.80 | |||
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 21717.49 | 17388.33 | 4329.16 | 0.80 | 3.80 | |||
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 21595.75 | 17290.85 | 4304.90 | 0.80 | 3.80 | |||
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 21546.09 | 17251.09 | 4295.00 | 0.80 | 3.80 | |||
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 36344.20 | 29099.35 | 7244.85 | 0.80 | 3.80 | |||
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 18791.44 | 15045.55 | 3745.89 | 0.80 | 4.12 | |||
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 18656.52 | 14937.53 | 3718.99 | 0.80 | 4.12 | |||
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 18518.96 | 14827.39 | 3691.57 | 0.80 | 4.12 | |||
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 19450.75 | 15573.44 | 3877.31 | 0.80 | 3.80 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC_1:1 COOLING COIL | 36509.2 | 11.11 | 11.11 | ||||
PSZ-AC_2:2 COOLING COIL | 19775.8 | 11.11 | 11.11 | ||||
PSZ-AC_3:3 COOLING COIL | 20689.3 | 11.11 | 11.11 | ||||
PSZ-AC_4:4 COOLING COIL | 20573.3 | 11.11 | 11.11 | ||||
PSZ-AC_5:5 COOLING COIL | 20526.0 | 11.11 | 11.11 | ||||
PSZ-AC_6:6 COOLING COIL | 34623.5 | 11.11 | 11.11 | ||||
PSZ-AC_7:7 COOLING COIL | 17901.8 | 11.83 | 11.83 | ||||
PSZ-AC_8:8 COOLING COIL | 17773.2 | 11.83 | 11.83 | ||||
PSZ-AC_9:9 COOLING COIL | 17642.2 | 11.83 | 11.83 | ||||
PSZ-AC_10:10 COOLING COIL | 18529.9 | 11.11 | 11.11 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | 58726.78 | 0.80 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | 31153.40 | 0.80 | |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | 32228.33 | 0.80 | |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | 32091.86 | 0.80 | |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | 32036.19 | 0.80 | |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | 56507.16 | 0.80 | |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | 28948.09 | 0.80 | |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | 28796.84 | 0.80 | |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | 28642.63 | 0.80 | |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | 29687.80 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 2.32 | 2477.30 | 1070.05 | 1.00 | 1.29 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.25 | 1388.41 | 1107.16 | 1.00 | 1.35 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.31 | 1452.54 | 1107.16 | 1.00 | 1.34 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.30 | 1444.40 | 1107.16 | 1.00 | 1.34 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.30 | 1441.08 | 1107.16 | 1.00 | 1.34 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 2.20 | 2349.35 | 1070.05 | 1.00 | 1.30 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.14 | 1256.84 | 1107.16 | 1.00 | 1.37 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.13 | 1247.81 | 1107.16 | 1.00 | 1.37 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 |
PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.12 | 1238.61 | 1107.16 | 1.00 | 1.38 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.18 | 1300.93 | 1107.16 | 1.00 | 1.36 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
GAS TANK1 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK2 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK3 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK4 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK5 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK6 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK7 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:01
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
LGSTORE1 | 21283.54 | 25540.25 | 73.31 | 1.929 | 2.315 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 23.89 | 23.89 | 0.00733 | 33.90 | 0.00548 | 0.411 | 0.00 |
SMSTORE1 | 11528.67 | 13834.41 | 79.42 | 1.045 | 1.254 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 23.89 | 23.89 | 0.00730 | 33.78 | 0.00548 | 0.206 | 0.00 |
SMSTORE2 | 12331.86 | 14798.24 | 84.95 | 1.093 | 1.312 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 23.89 | 23.89 | 0.00772 | 25.76 | 0.00546 | 0.206 | 0.00 |
SMSTORE3 | 12264.66 | 14717.60 | 84.49 | 1.087 | 1.305 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 23.89 | 23.89 | 0.00771 | 25.76 | 0.00546 | 0.206 | 0.00 |
SMSTORE4 | 12236.03 | 14683.24 | 84.29 | 1.085 | 1.302 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 23.89 | 23.89 | 0.00774 | 25.76 | 0.00546 | 0.206 | 0.00 |
LGSTORE2 | 20184.05 | 24220.86 | 69.52 | 1.830 | 2.196 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 23.89 | 23.89 | 0.00736 | 33.65 | 0.00547 | 0.411 | 0.00 |
SMSTORE5 | 10436.12 | 12523.35 | 71.89 | 0.946 | 1.135 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 23.89 | 23.89 | 0.00733 | 33.65 | 0.00547 | 0.206 | 0.00 |
SMSTORE6 | 10361.20 | 12433.43 | 71.38 | 0.939 | 1.127 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 23.89 | 23.89 | 0.00733 | 33.65 | 0.00547 | 0.206 | 0.00 |
SMSTORE7 | 10284.80 | 12341.76 | 70.85 | 0.932 | 1.119 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 23.89 | 23.89 | 0.00733 | 33.65 | 0.00547 | 0.206 | 0.00 |
SMSTORE8 | 10801.92 | 12962.31 | 74.41 | 0.979 | 1.175 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | 23.89 | 23.89 | 0.00730 | 33.16 | 0.00547 | 0.206 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
LGSTORE1 | 24699.36 | 29639.23 | 85.08 | 1.312 | 1.574 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.10 | 0.00673 | -17.90 | 0.00096 | 0.411 | 0.00 |
SMSTORE1 | 11785.39 | 14142.46 | 81.19 | 0.626 | 0.751 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.10 | 0.00662 | -17.90 | 0.00096 | 0.206 | 0.00 |
SMSTORE2 | 11937.30 | 14324.76 | 82.23 | 0.634 | 0.761 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.10 | 0.00663 | -17.90 | 0.00096 | 0.206 | 0.00 |
SMSTORE3 | 12032.69 | 14439.23 | 82.89 | 0.639 | 0.767 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.10 | 0.00664 | -17.90 | 0.00096 | 0.206 | 0.00 |
SMSTORE4 | 12188.42 | 14626.10 | 83.96 | 0.647 | 0.777 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.10 | 0.00665 | -17.90 | 0.00096 | 0.206 | 0.00 |
LGSTORE2 | 23433.74 | 28120.48 | 80.72 | 1.244 | 1.493 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.10 | 0.00673 | -17.90 | 0.00096 | 0.411 | 0.00 |
SMSTORE5 | 12523.86 | 15028.63 | 86.28 | 0.665 | 0.798 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.10 | 0.00668 | -17.90 | 0.00096 | 0.206 | 0.00 |
SMSTORE6 | 12510.54 | 15012.64 | 86.18 | 0.664 | 0.797 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.10 | 0.00668 | -17.90 | 0.00096 | 0.206 | 0.00 |
SMSTORE7 | 12723.47 | 15268.17 | 87.65 | 0.676 | 0.811 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.10 | 0.00669 | -17.90 | 0.00096 | 0.206 | 0.00 |
SMSTORE8 | 15209.03 | 18250.83 | 104.77 | 0.808 | 0.969 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.10 | 0.00677 | -17.90 | 0.00096 | 0.206 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC_1:1 | 2.32 | 2.32 | 1.57 | 1.57 | 2.3151 | 2.3151 | 2.3151 | 1.0000 | 1.0000 |
PSZ-AC_2:2 | 1.25 | 1.25 | 0.75 | 0.75 | 1.2540 | 1.2540 | 1.2540 | 1.0000 | 1.0000 |
PSZ-AC_3:3 | 1.31 | 1.31 | 0.76 | 0.76 | 1.3120 | 1.3120 | 1.3120 | 1.0000 | 1.0000 |
PSZ-AC_4:4 | 1.30 | 1.30 | 0.77 | 0.77 | 1.3046 | 1.3046 | 1.3046 | 1.0000 | 1.0000 |
PSZ-AC_5:5 | 1.30 | 1.30 | 0.78 | 0.78 | 1.3016 | 1.3016 | 1.3016 | 1.0000 | 1.0000 |
PSZ-AC_6:6 | 2.20 | 2.20 | 1.49 | 1.49 | 2.1956 | 2.1956 | 2.1956 | 1.0000 | 1.0000 |
PSZ-AC_7:7 | 1.14 | 1.14 | 0.80 | 0.80 | 1.1352 | 1.1352 | 1.1352 | 1.0000 | 1.0000 |
PSZ-AC_8:8 | 1.13 | 1.13 | 0.80 | 0.80 | 1.1270 | 1.1270 | 1.1270 | 1.0000 | 1.0000 |
PSZ-AC_9:9 | 1.12 | 1.12 | 0.81 | 0.81 | 1.1187 | 1.1187 | 1.1187 | 1.0000 | 1.0000 |
PSZ-AC_10:10 | 1.18 | 1.18 | 0.97 | 0.97 | 1.1750 | 1.1750 | 1.1750 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 38323.600 | 30684.174 | 2.315130 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 19161.80 | 19156.75 | 1.543420 | 26.74 | 13.94 | 0.00700221 | 12.80 | 8.76 | 0.00700000 | 33.90 | 0.00547527 | 15.07 | 26.6602 | 23.89 | 0.00733226 | 32.3136 | 21283.54 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_1:1 | 58726.776 | 58726.776 | -999.0 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 58726.78 | 58726.78 | 2.315129 | 14.17 | 8.01 | 0.00570166 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 17.7735 | 21.10 | 0.00672761 | 35.1488 | 24699.36 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 20758.610 | 16620.589 | 1.254030 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 10379.31 | 10378.03 | 0.836020 | 26.64 | 13.91 | 0.00700103 | 12.80 | 8.76 | 0.00700000 | 33.90 | 0.00547527 | 15.07 | 24.6094 | 23.89 | 0.00730063 | 32.1755 | 11523.77 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_2:2 | 31153.395 | 31153.395 | -999.0 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 31153.40 | 31153.40 | 1.254028 | 14.71 | 8.22 | 0.00569073 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 16.4063 | 21.10 | 0.00662013 | 34.5932 | 11785.39 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_3:3 | 21717.490 | 17388.326 | 1.311950 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 10858.75 | 10856.96 | 0.874633 | 26.64 | 13.91 | 0.00700137 | 12.80 | 8.76 | 0.00700000 | 33.90 | 0.00547527 | 15.07 | 23.5229 | 23.89 | 0.00729949 | 32.1706 | 12331.86 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_3:3 | 32228.333 | 32228.333 | -999.0 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 32228.33 | 32228.33 | 1.311953 | 14.99 | 8.39 | 0.00574199 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 15.6819 | 21.10 | 0.00663225 | 34.6559 | 11937.30 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_4:4 | 21595.750 | 17290.853 | 1.304600 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 10797.88 | 10795.80 | 0.869733 | 26.63 | 13.91 | 0.00700160 | 12.80 | 8.76 | 0.00700000 | 33.90 | 0.00547527 | 15.07 | 23.6555 | 23.89 | 0.00729870 | 32.1671 | 11608.77 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_4:4 | 32091.862 | 32091.862 | -999.0 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 32091.86 | 32091.86 | 1.304599 | 14.95 | 8.38 | 0.00574328 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 15.7703 | 21.10 | 0.00663974 | 34.6947 | 12032.69 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_5:5 | 21546.090 | 17251.092 | 1.301600 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 10773.05 | 10771.94 | 0.867733 | 26.65 | 13.91 | 0.00700086 | 12.80 | 8.76 | 0.00700000 | 33.90 | 0.00547527 | 15.07 | 23.7100 | 23.89 | 0.00730128 | 32.1784 | 12236.03 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_5:5 | 32036.188 | 32036.188 | -999.0 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 32036.19 | 32036.19 | 1.301600 | 14.94 | 8.38 | 0.00575144 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 15.8067 | 21.10 | 0.00665189 | 34.7575 | 12188.42 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_6:6 | 36344.200 | 29099.347 | 2.195550 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 18172.10 | 18155.18 | 1.463700 | 26.84 | 13.98 | 0.00700787 | 12.80 | 8.76 | 0.00700000 | 33.90 | 0.00547527 | 15.07 | 28.1122 | 23.89 | 0.00736186 | 32.4426 | 20160.17 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_6:6 | 56507.161 | 56507.161 | -999.0 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 56507.16 | 56507.16 | 2.195553 | 13.80 | 7.79 | 0.00564866 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 18.7415 | 21.10 | 0.00673115 | 35.1664 | 23433.74 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_7:7 | 18791.440 | 15045.554 | 1.135190 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 9395.72 | 9395.72 | 0.756793 | 26.82 | 13.96 | 0.00699216 | 12.80 | 8.75 | 0.00699216 | 33.90 | 0.00547527 | 15.07 | 27.1857 | 23.89 | 0.00732842 | 32.2966 | 10423.70 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_7:7 | 28948.089 | 28948.089 | -999.0 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 28948.09 | 28948.09 | 1.135191 | 14.04 | 7.89 | 0.00564025 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 18.1238 | 21.10 | 0.00667731 | 34.8889 | 12523.86 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_8:8 | 18656.520 | 14937.529 | 1.127040 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 9328.26 | 9328.26 | 0.751360 | 26.83 | 13.97 | 0.00699143 | 12.80 | 8.75 | 0.00699143 | 33.90 | 0.00547527 | 15.07 | 27.3823 | 23.89 | 0.00733049 | 32.3056 | 10349.21 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_8:8 | 28796.842 | 28796.842 | -999.0 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 28796.84 | 28796.84 | 1.127040 | 13.99 | 7.86 | 0.00563196 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 18.2548 | 21.10 | 0.00667633 | 34.8839 | 12510.54 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_9:9 | 18518.960 | 14827.391 | 1.118730 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 9259.48 | 9259.48 | 0.745820 | 26.84 | 13.97 | 0.00699066 | 12.80 | 8.75 | 0.00699066 | 33.90 | 0.00547527 | 15.07 | 27.5857 | 23.89 | 0.00733264 | 32.3150 | 10272.73 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_9:9 | 28642.630 | 28642.630 | -999.0 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 28642.63 | 28642.63 | 1.118730 | 13.93 | 7.84 | 0.00563688 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 18.3904 | 21.10 | 0.00669188 | 34.9643 | 12723.47 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_10:10 | 19450.750 | 15573.437 | 1.175020 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | 9725.38 | 9725.38 | 0.783347 | 26.70 | 13.91 | 0.00697603 | 12.80 | 8.73 | 0.00697603 | 33.53 | 0.00547470 | 14.95 | 26.2642 | 23.89 | 0.00729614 | 32.1558 | 10762.46 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_10:10 | 29687.795 | 29687.795 | -999.0 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 29687.80 | 29687.80 | 1.175020 | 14.28 | 8.10 | 0.00575295 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 17.5094 | 21.10 | 0.00677132 | 35.3763 | 15209.03 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:37:01
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 38323.600 | 30684.174 | 2.315130 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.8568 | 1004.8586 | 0.9774 | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.315129 | 2.26289396 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | Sensible | 19161.80 | 19156.75 | 1.0000 | 1.50859676 | 1.543420 | 26.74 | 13.94 | 0.00700221 | 44733.2 | 12.80 | 8.76 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 19161.80 | 33.90 | 0.00547527 | 15.07 | 0.41147883 | 26.6602 | 23.89 | 0.00733226 | 23.89 | 0.00733226 | 32.3136 | 21283.54 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 58726.776 | 58726.776 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.315129 | 2.26289396 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | Sensible | 58726.78 | 58726.78 | 1.0000 | 2.26289396 | 2.315129 | 14.17 | 8.01 | 0.00570166 | 28651.7 | 40.00 | 18.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 58726.78 | -17.90 | 0.00095524 | -17.90 | 0.41147883 | 17.7735 | 21.11 | 0.00672761 | 21.10 | 0.00672761 | 35.1488 | 24699.36 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 20758.610 | 16620.589 | 1.254030 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.8546 | 1004.8586 | 0.9774 | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.254028 | 1.22573389 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | Sensible | 10379.31 | 10378.03 | 1.0000 | 0.81715739 | 0.836020 | 26.64 | 13.91 | 0.00700103 | 44629.6 | 12.80 | 8.76 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10379.31 | 33.90 | 0.00547527 | 15.07 | 0.20573941 | 24.6094 | 23.89 | 0.00730063 | 23.89 | 0.00730063 | 32.1755 | 11523.77 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 31153.395 | 31153.395 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.254028 | 1.22573389 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | Sensible | 31153.40 | 31153.40 | 1.0000 | 1.22573389 | 1.254028 | 14.71 | 8.22 | 0.00569073 | 29165.7 | 40.00 | 18.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 31153.40 | -17.90 | 0.00095524 | -17.90 | 0.20573941 | 16.4063 | 21.11 | 0.00662013 | 21.10 | 0.00662013 | 34.5932 | 11785.39 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 21717.490 | 17388.326 | 1.311950 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.8552 | 1004.8586 | 0.9774 | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.311953 | 1.28235265 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | Sensible | 10858.75 | 10856.96 | 1.0000 | 0.85489952 | 0.874633 | 26.64 | 13.91 | 0.00700137 | 44623.2 | 12.80 | 8.76 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10858.75 | 33.90 | 0.00547527 | 15.07 | 0.20573941 | 23.5229 | 23.89 | 0.00729949 | 23.89 | 0.00729949 | 32.1706 | 12331.86 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 32228.333 | 32228.333 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.311953 | 1.28235265 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | Sensible | 32228.33 | 32228.33 | 1.0000 | 1.28235265 | 1.311953 | 14.99 | 8.39 | 0.00574199 | 29582.2 | 40.00 | 18.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 32228.33 | -17.90 | 0.00095524 | -17.90 | 0.20573941 | 15.6819 | 21.11 | 0.00663225 | 21.10 | 0.00663225 | 34.6559 | 11937.30 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 21595.750 | 17290.853 | 1.304600 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.8556 | 1004.8586 | 0.9774 | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.304599 | 1.27516454 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | Sensible | 10797.88 | 10795.80 | 1.0000 | 0.85011007 | 0.869733 | 26.63 | 13.91 | 0.00700160 | 44618.8 | 12.80 | 8.76 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10797.88 | 33.90 | 0.00547527 | 15.07 | 0.20573941 | 23.6555 | 23.89 | 0.00729870 | 23.89 | 0.00729870 | 32.1671 | 11608.77 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 32091.862 | 32091.862 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.304599 | 1.27516454 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | Sensible | 32091.86 | 32091.86 | 1.0000 | 1.27516454 | 1.304599 | 14.95 | 8.38 | 0.00574328 | 29550.5 | 40.00 | 18.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 32091.86 | -17.90 | 0.00095524 | -17.90 | 0.20573941 | 15.7703 | 21.11 | 0.00663974 | 21.10 | 0.00663974 | 34.6947 | 12032.69 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 21546.090 | 17251.092 | 1.301600 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.8542 | 1004.8586 | 0.9774 | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.301600 | 1.27223233 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | Sensible | 10773.05 | 10771.94 | 1.0000 | 0.84815520 | 0.867733 | 26.65 | 13.91 | 0.00700086 | 44633.1 | 12.80 | 8.76 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10773.05 | 33.90 | 0.00547527 | 15.07 | 0.20573941 | 23.7100 | 23.89 | 0.00730128 | 23.89 | 0.00730128 | 32.1784 | 12236.03 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 32036.188 | 32036.188 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.301600 | 1.27223233 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | Sensible | 32036.19 | 32036.19 | 1.0000 | 1.27223233 | 1.301600 | 14.94 | 8.38 | 0.00575144 | 29556.7 | 40.00 | 18.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 32036.19 | -17.90 | 0.00095524 | -17.90 | 0.20573941 | 15.8067 | 21.11 | 0.00665189 | 21.10 | 0.00665189 | 34.7575 | 12188.42 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 36344.200 | 29099.347 | 2.195550 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.8673 | 1004.8586 | 0.9774 | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.195553 | 2.14601632 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | Sensible | 18172.10 | 18155.18 | 1.0000 | 1.43067543 | 1.463700 | 26.84 | 13.98 | 0.00700787 | 44848.4 | 12.80 | 8.76 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 18172.10 | 33.90 | 0.00547527 | 15.07 | 0.41147883 | 28.1122 | 23.89 | 0.00736186 | 23.89 | 0.00736186 | 32.4426 | 20160.17 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 56507.161 | 56507.161 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.195553 | 2.14601632 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | Sensible | 56507.16 | 56507.16 | 1.0000 | 2.14601632 | 2.195553 | 13.80 | 7.79 | 0.00564866 | 28134.7 | 40.00 | 18.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 56507.16 | -17.90 | 0.00095524 | -17.90 | 0.41147883 | 18.7415 | 21.11 | 0.00673115 | 21.10 | 0.00673115 | 35.1664 | 23433.74 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 18791.440 | 15045.554 | 1.135190 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.8381 | 1004.8586 | 0.9774 | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.135191 | 1.10957805 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | Sensible | 9395.72 | 9395.72 | 1.0000 | 0.73971827 | 0.756793 | 26.82 | 13.96 | 0.00699216 | 44783.5 | 12.80 | 8.75 | 0.00699216 | 30515.3 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9395.72 | 33.90 | 0.00547527 | 15.07 | 0.20573941 | 27.1857 | 23.89 | 0.00732842 | 23.89 | 0.00732842 | 32.2966 | 10423.70 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 28948.089 | 28948.089 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.135191 | 1.10957805 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | Sensible | 28948.09 | 28948.09 | 1.0000 | 1.10957805 | 1.135191 | 14.04 | 7.89 | 0.00564025 | 28357.9 | 40.00 | 18.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28948.09 | -17.90 | 0.00095524 | -17.90 | 0.20573941 | 18.1238 | 21.11 | 0.00667731 | 21.10 | 0.00667731 | 34.8889 | 12523.86 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 18656.520 | 14937.529 | 1.127040 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.8367 | 1004.8586 | 0.9774 | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.127040 | 1.10161162 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | Sensible | 9328.26 | 9328.26 | 1.0000 | 0.73440752 | 0.751360 | 26.83 | 13.97 | 0.00699143 | 44794.9 | 12.80 | 8.75 | 0.00699143 | 30513.5 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9328.26 | 33.90 | 0.00547527 | 15.07 | 0.20573941 | 27.3823 | 23.89 | 0.00733049 | 23.89 | 0.00733049 | 32.3056 | 10349.21 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 28796.842 | 28796.842 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.127040 | 1.10161162 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | Sensible | 28796.84 | 28796.84 | 1.0000 | 1.10161162 | 1.127040 | 13.99 | 7.86 | 0.00563196 | 28285.0 | 40.00 | 18.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28796.84 | -17.90 | 0.00095524 | -17.90 | 0.20573941 | 18.2548 | 21.11 | 0.00667633 | 21.10 | 0.00667633 | 34.8839 | 12510.54 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 18518.960 | 14827.391 | 1.118730 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.8353 | 1004.8586 | 0.9774 | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.118730 | 1.09348903 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | Sensible | 9259.48 | 9259.48 | 1.0000 | 0.72899252 | 0.745820 | 26.84 | 13.97 | 0.00699066 | 44806.8 | 12.80 | 8.75 | 0.00699066 | 30511.5 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9259.48 | 33.90 | 0.00547527 | 15.07 | 0.20573941 | 27.5857 | 23.89 | 0.00733264 | 23.89 | 0.00733264 | 32.3150 | 10272.73 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 28642.630 | 28642.630 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.118730 | 1.09348903 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | Sensible | 28642.63 | 28642.63 | 1.0000 | 1.09348903 | 1.118730 | 13.93 | 7.84 | 0.00563688 | 28243.8 | 40.00 | 18.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28642.63 | -17.90 | 0.00095524 | -17.90 | 0.20573941 | 18.3904 | 21.11 | 0.00669188 | 21.10 | 0.00669188 | 34.9643 | 12723.47 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 19450.750 | 15573.437 | 1.175020 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.8081 | 1004.8586 | 0.9774 | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.175020 | 1.14850829 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | Sensible | 9725.38 | 9725.38 | 1.0000 | 0.76567250 | 0.783347 | 26.70 | 13.91 | 0.00697603 | 44618.0 | 12.80 | 8.73 | 0.00697603 | 30474.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9725.38 | 33.53 | 0.00547470 | 14.95 | 0.20573941 | 26.2642 | 23.89 | 0.00729614 | 23.89 | 0.00729614 | 32.1558 | 10762.46 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 29687.795 | 29687.795 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.175020 | 1.14850829 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | Sensible | 29687.80 | 29687.80 | 1.0000 | 1.14850829 | 1.175020 | 14.28 | 8.10 | 0.00575295 | 28885.5 | 40.00 | 18.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 29687.80 | -17.90 | 0.00095524 | -17.90 | 0.20573941 | 17.5094 | 21.11 | 0.00677132 | 21.10 | 0.00677132 | 35.3763 | 15209.03 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:01
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-AC_1:1_OA_CONTROLLER | DifferentialDryBulb | 0.41 | 2.32 | - | |||
PSZ-AC_2:2_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.25 | - | |||
PSZ-AC_3:3_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.31 | - | |||
PSZ-AC_4:4_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.30 | - | |||
PSZ-AC_5:5_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.30 | - | |||
PSZ-AC_6:6_OA_CONTROLLER | DifferentialDryBulb | 0.41 | 2.20 | - | |||
PSZ-AC_7:7_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.14 | - | |||
PSZ-AC_8:8_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.13 | - | |||
PSZ-AC_9:9_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.12 | - | |||
PSZ-AC_10:10_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.18 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
LGSTORE1 | 1816.50 | 3834.83 | 1039.83 |
SMSTORE1 | 1163.83 | 3609.50 | 409.83 |
SMSTORE2 | 1158.00 | 2712.00 | 488.33 |
SMSTORE3 | 1200.67 | 2753.00 | 534.83 |
SMSTORE4 | 1242.67 | 2806.33 | 608.00 |
LGSTORE2 | 1252.17 | 2673.17 | 749.50 |
SMSTORE5 | 1195.67 | 2704.50 | 753.67 |
SMSTORE6 | 1222.83 | 2719.83 | 790.33 |
SMSTORE7 | 1327.83 | 2775.00 | 912.17 |
SMSTORE8 | 1739.33 | 2833.17 | 1305.67 |
Facility | 2668.17 | 4264.67 | 1781.67 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
LGSTORE1 | 5.67 | 0.00 | 1.17 | 0.00 |
SMSTORE1 | 2.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 0.17 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 0.50 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 1.83 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 1.50 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 1.83 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 2.67 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 24.33 | 0.00 | 0.00 | 0.00 |
Facility | 30.83 | 0.00 | 1.17 | 0.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:01
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
LGSTORE1 | 16.93 | 56.25 | 1805.20 | 1.072 | 0.230 | 0.000 | 0.000 |
SMSTORE1 | 8.47 | 28.12 | 902.60 | 0.958 | 0.245 | 0.000 | 0.000 |
SMSTORE2 | 7.08 | 28.12 | 902.60 | 1.135 | 0.320 | 0.000 | 0.000 |
SMSTORE3 | 7.08 | 28.12 | 902.60 | 1.126 | 0.320 | 0.000 | 0.000 |
SMSTORE4 | 7.08 | 28.12 | 902.60 | 1.110 | 0.320 | 0.000 | 0.000 |
LGSTORE2 | 24.75 | 56.25 | 1805.20 | 1.039 | 0.307 | 0.000 | 0.000 |
SMSTORE5 | 12.38 | 28.12 | 902.60 | 1.242 | 0.341 | 0.000 | 0.000 |
SMSTORE6 | 12.38 | 28.12 | 902.60 | 1.233 | 0.341 | 0.000 | 0.000 |
SMSTORE7 | 12.38 | 28.12 | 902.60 | 1.205 | 0.341 | 0.000 | 0.000 |
SMSTORE8 | 12.38 | 28.12 | 902.60 | 1.017 | 0.359 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
LGSTORE1 | 16.93 | 56.25 | 1805.20 | 0.000 | 0.000 | 0.000 | 0.000 |
SMSTORE1 | 8.47 | 28.12 | 902.60 | 0.000 | 0.000 | 0.000 | 0.000 |
SMSTORE2 | 7.08 | 28.12 | 902.60 | 0.810 | 0.000 | 0.000 | 0.000 |
SMSTORE3 | 7.08 | 28.12 | 902.60 | 0.810 | 0.000 | 0.000 | 0.000 |
SMSTORE4 | 7.08 | 28.12 | 902.60 | 0.810 | 0.000 | 0.000 | 0.000 |
LGSTORE2 | 24.75 | 56.25 | 1805.20 | 0.810 | 0.000 | 0.000 | 0.000 |
SMSTORE5 | 12.38 | 28.12 | 902.60 | 0.810 | 0.000 | 0.000 | 0.000 |
SMSTORE6 | 12.38 | 28.12 | 902.60 | 0.810 | 0.000 | 0.000 | 0.000 |
SMSTORE7 | 12.38 | 28.12 | 902.60 | 0.810 | 0.000 | 0.000 | 0.000 |
SMSTORE8 | 12.38 | 28.12 | 902.60 | 0.809 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:37:01
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
LGSTORE1 | PSZ-AC_1:1 | 16.93 | 56.25 | 1805.20 | 348.39 | 0.4115 | 0.411 |
SMSTORE1 | PSZ-AC_2:2 | 8.47 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE2 | PSZ-AC_3:3 | 7.08 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE3 | PSZ-AC_4:4 | 7.08 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE4 | PSZ-AC_5:5 | 7.08 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
LGSTORE2 | PSZ-AC_6:6 | 24.75 | 56.25 | 1805.20 | 348.39 | 0.4115 | 0.411 |
SMSTORE5 | PSZ-AC_7:7 | 12.38 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE6 | PSZ-AC_8:8 | 12.38 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE7 | PSZ-AC_9:9 | 12.38 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE8 | PSZ-AC_10:10 | 12.38 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
Total Facility | 120.88 | 337.50 | 10831.20 | 2090.32 | 2.4689 | 2.469 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
LGSTORE1 | 11242521.37 | 0.00 | 11242521.37 | 2812665.34 | 14055186.72 | 12976396.34 | 3139.13 | 4202.00 | 1418.87 | 24.92 |
SMSTORE1 | 5027449.84 | 0.00 | 5027449.84 | 1400999.48 | 6428449.32 | 6488198.17 | 4268.60 | 3025.21 | 1466.20 | 26.53 |
SMSTORE2 | 4573243.79 | 0.00 | 4573243.79 | 1437500.89 | 6010744.68 | 6488198.17 | 4306.77 | 3412.00 | 1041.22 | 107.72 |
SMSTORE3 | 4537572.97 | 0.00 | 4537572.97 | 1437500.89 | 5975073.86 | 6488198.17 | 4306.77 | 3443.33 | 1009.89 | 103.55 |
SMSTORE4 | 4468734.33 | 0.00 | 4468734.33 | 1437500.89 | 5906235.22 | 6488198.17 | 4311.94 | 3491.58 | 956.47 | 101.02 |
LGSTORE2 | 7662452.53 | 0.00 | 7662452.53 | 2643892.63 | 10306345.16 | 12976396.34 | 4687.21 | 3249.00 | 823.79 | 82.21 |
SMSTORE5 | 4635917.53 | 0.00 | 4635917.53 | 1448728.57 | 6084646.10 | 6488198.17 | 4656.59 | 3101.67 | 1001.75 | 106.47 |
SMSTORE6 | 4599381.67 | 0.00 | 4599381.67 | 1448728.57 | 6048110.25 | 6488198.17 | 4657.31 | 3114.75 | 987.94 | 103.78 |
SMSTORE7 | 4489811.42 | 0.00 | 4489811.42 | 1448728.57 | 5938539.99 | 6488198.17 | 4663.35 | 3180.00 | 916.65 | 97.80 |
SMSTORE8 | 3734885.87 | 0.00 | 3734885.87 | 1784553.10 | 5519438.97 | 6488198.17 | 4696.49 | 3403.14 | 660.37 | 64.24 |
Total Facility | 54971971.32 | 0.00 | 54971971.32 | 17300798.94 | 72272770.26 | 77858378.04 | 4702.63 | 4754.43 | 1747.39 | 221.61 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
LGSTORE1 | 0.5325 | 0.0000 | 0.5325 | 0.1144 | 0.6469 | 0.4115 | 229.86 | 4202.00 | 1408.14 |
SMSTORE1 | 0.2377 | 0.0000 | 0.2377 | 0.0609 | 0.2987 | 0.2057 | 1364.12 | 3024.87 | 1451.00 |
SMSTORE2 | 0.2819 | 0.0000 | 0.2819 | 0.0795 | 0.3614 | 0.2057 | 0.00 | 3411.00 | 984.00 |
SMSTORE3 | 0.2797 | 0.0000 | 0.2797 | 0.0795 | 0.3592 | 0.2057 | 0.00 | 3442.17 | 952.83 |
SMSTORE4 | 0.2758 | 0.0000 | 0.2758 | 0.0795 | 0.3552 | 0.2057 | 0.00 | 3490.58 | 904.42 |
LGSTORE2 | 0.5164 | 0.0000 | 0.5164 | 0.1526 | 0.6690 | 0.4115 | 0.00 | 3248.33 | 781.67 |
SMSTORE5 | 0.3084 | 0.0000 | 0.3084 | 0.0848 | 0.3932 | 0.2057 | 0.00 | 3101.08 | 928.92 |
SMSTORE6 | 0.3062 | 0.0000 | 0.3062 | 0.0848 | 0.3909 | 0.2057 | 0.00 | 3114.17 | 915.83 |
SMSTORE7 | 0.2992 | 0.0000 | 0.2992 | 0.0848 | 0.3840 | 0.2057 | 0.00 | 3179.00 | 851.00 |
SMSTORE8 | 0.2528 | 0.0000 | 0.2528 | 0.0893 | 0.3422 | 0.2057 | 0.00 | 3402.58 | 627.42 |
Total Facility | 3.2907 | 0.0000 | 3.2907 | 0.9099 | 4.2006 | 2.4689 | 1467.37 | 4748.96 | 1697.53 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-AC_1:1 | 10741180.92 | 0.00 | 10741180.92 | 12976396.34 | 7353.36 | 10.08 | 1396.56 | 24.92 |
PSZ-AC_2:2 | 4803214.00 | 0.00 | 4803214.00 | 6488198.17 | 7307.64 | 10.33 | 1442.03 | 26.53 |
PSZ-AC_3:3 | 4369276.91 | 0.00 | 4369276.91 | 6488198.17 | 7726.44 | 5.75 | 1027.81 | 107.38 |
PSZ-AC_4:4 | 4335198.23 | 0.00 | 4335198.23 | 6488198.17 | 7757.28 | 5.17 | 997.56 | 103.22 |
PSZ-AC_5:5 | 4269430.05 | 0.00 | 4269430.05 | 6488198.17 | 7810.28 | 5.33 | 944.39 | 100.61 |
PSZ-AC_6:6 | 7320760.27 | 0.00 | 7320760.27 | 12976396.34 | 7941.13 | 4.00 | 814.87 | 82.04 |
PSZ-AC_7:7 | 4429082.75 | 0.00 | 4429082.75 | 6488198.17 | 7765.00 | 4.00 | 991.00 | 106.30 |
PSZ-AC_8:8 | 4394176.98 | 0.00 | 4394176.98 | 6488198.17 | 7778.84 | 6.17 | 975.00 | 103.78 |
PSZ-AC_9:9 | 4289495.27 | 0.00 | 4289495.27 | 6488198.17 | 7849.52 | 4.58 | 905.90 | 97.80 |
PSZ-AC_10:10 | 3568283.69 | 0.00 | 3568283.69 | 6488198.17 | 8103.76 | 2.67 | 653.57 | 64.24 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-AC_1:1 | 0.5088 | 0.0000 | 0.5088 | 0.4115 | 4444.08 | 10.08 | 1385.84 |
PSZ-AC_2:2 | 0.2271 | 0.0000 | 0.2271 | 0.2057 | 4402.67 | 9.83 | 1427.50 |
PSZ-AC_3:3 | 0.2693 | 0.0000 | 0.2693 | 0.2057 | 3417.00 | 4.92 | 973.08 |
PSZ-AC_4:4 | 0.2672 | 0.0000 | 0.2672 | 0.2057 | 3447.33 | 4.50 | 943.17 |
PSZ-AC_5:5 | 0.2635 | 0.0000 | 0.2635 | 0.2057 | 3496.58 | 4.33 | 894.08 |
PSZ-AC_6:6 | 0.4934 | 0.0000 | 0.4934 | 0.4115 | 3252.83 | 3.83 | 773.33 |
PSZ-AC_7:7 | 0.2947 | 0.0000 | 0.2947 | 0.2057 | 3106.92 | 3.42 | 919.67 |
PSZ-AC_8:8 | 0.2925 | 0.0000 | 0.2925 | 0.2057 | 3119.67 | 5.50 | 904.83 |
PSZ-AC_9:9 | 0.2859 | 0.0000 | 0.2859 | 0.2057 | 3184.58 | 3.17 | 842.25 |
PSZ-AC_10:10 | 0.2415 | 0.0000 | 0.2415 | 0.2057 | 3406.08 | 2.17 | 621.75 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-AC_1:1 | 0.00 | 5024.62 | 645.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_2:2 | 0.00 | 3988.39 | 1018.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_3:3 | 0.00 | 3995.56 | 506.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_4:4 | 0.00 | 4019.14 | 479.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_5:5 | 0.00 | 4039.14 | 456.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_6:6 | 0.00 | 3755.98 | 356.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_7:7 | 0.00 | 3558.36 | 577.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_8:8 | 0.00 | 3567.29 | 566.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_9:9 | 0.00 | 3609.91 | 517.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_10:10 | 0.00 | 3819.27 | 274.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-AC_1:1 | 0.0000 | 0.5081 | 0.6741 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_2:2 | 0.0000 | 0.2639 | 0.2764 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_3:3 | 0.0000 | 0.2571 | 0.3859 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_4:4 | 0.0000 | 0.2553 | 0.3883 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_5:5 | 0.0000 | 0.2521 | 0.3867 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_6:6 | 0.0000 | 0.4772 | 0.6980 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_7:7 | 0.0000 | 0.2722 | 0.4547 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_8:8 | 0.0000 | 0.2707 | 0.4515 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_9:9 | 0.0000 | 0.2656 | 0.4507 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_10:10 | 0.0000 | 0.2345 | 0.3603 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:01
Surfaces by ClassTotal | Outdoors | |
Wall | 40 | 22 |
Floor | 10 | 10 |
Roof | 10 | 10 |
Internal Mass | 10 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 36 | 36 |
Door | 12 | 12 |
Glass Door | 12 | 12 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 10 |
Conditioned Zones | 10 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 830 |
Defaulted Fields | 823 |
Fields with Defaults | 2682 |
Autosized Fields | 184 |
Autosizable Fields | 458 |
Autocalculated Fields | 128 |
Autocalculatable Fields | 256 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:37:01
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 853.25 | 2102.83 | 01-JAN-07:50 | 89016.25 | 26-JUN-15:00 |
Electricity:Building | 494.83 | 891.83 | 01-JAN-00:20 | 31518.67 | 01-JAN-11:10 |
Electricity:Zone:LGSTORE1 | 113.36 | 148.64 | 01-JAN-00:20 | 5964.88 | 01-JAN-10:10 |
Electricity:SpaceType:GENERAL | 494.83 | 891.83 | 01-JAN-00:20 | 31518.67 | 01-JAN-11:10 |
InteriorLights:Electricity | 366.68 | 450.00 | 01-JAN-00:20 | 23459.17 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:LGSTORE1 | 87.12 | 75.00 | 01-JAN-00:20 | 4621.63 | 01-JAN-10:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 366.68 | 450.00 | 01-JAN-00:20 | 23459.17 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity | 366.68 | 450.00 | 01-JAN-00:20 | 23459.17 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:LGSTORE1 | 87.12 | 75.00 | 01-JAN-00:20 | 4621.63 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 366.68 | 450.00 | 01-JAN-00:20 | 23459.17 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE1 | 66.33 | 74.32 | 01-JAN-00:20 | 3498.69 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE1 | 53.20 | 37.50 | 01-JAN-00:20 | 2827.07 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE1 | 53.20 | 37.50 | 01-JAN-00:20 | 2827.07 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE2 | 47.99 | 74.32 | 01-JAN-00:10 | 3226.84 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE2 | 37.57 | 37.50 | 01-JAN-00:10 | 2555.22 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE2 | 37.57 | 37.50 | 01-JAN-00:10 | 2555.22 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE3 | 47.99 | 74.32 | 01-JAN-00:10 | 3226.84 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE3 | 37.57 | 37.50 | 01-JAN-00:10 | 2555.22 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE3 | 37.57 | 37.50 | 01-JAN-00:10 | 2555.22 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE4 | 47.99 | 74.32 | 01-JAN-00:10 | 3226.84 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE4 | 37.57 | 37.50 | 01-JAN-00:10 | 2555.22 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE4 | 37.57 | 37.50 | 01-JAN-00:10 | 2555.22 | 01-JAN-10:10 |
Electricity:Zone:LGSTORE2 | 56.34 | 148.64 | 01-JAN-00:10 | 4070.21 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:LGSTORE2 | 37.16 | 75.00 | 01-JAN-00:10 | 2726.96 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:LGSTORE2 | 37.16 | 75.00 | 01-JAN-00:10 | 2726.96 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE5 | 28.71 | 74.32 | 01-JAN-00:10 | 2076.09 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE5 | 19.12 | 37.50 | 01-JAN-00:10 | 1404.46 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE5 | 19.12 | 37.50 | 01-JAN-00:10 | 1404.46 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE6 | 28.71 | 74.32 | 01-JAN-00:10 | 2076.09 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE6 | 19.12 | 37.50 | 01-JAN-00:10 | 1404.46 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE6 | 19.12 | 37.50 | 01-JAN-00:10 | 1404.46 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE7 | 28.71 | 74.32 | 01-JAN-00:10 | 2076.09 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE7 | 19.12 | 37.50 | 01-JAN-00:10 | 1404.46 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE7 | 19.12 | 37.50 | 01-JAN-00:10 | 1404.46 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE8 | 28.71 | 74.32 | 01-JAN-00:10 | 2076.09 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE8 | 19.12 | 37.50 | 01-JAN-00:10 | 1404.46 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE8 | 19.12 | 37.50 | 01-JAN-00:10 | 1404.46 | 01-JAN-11:10 |
InteriorEquipment:Electricity | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:LGSTORE1 | 26.25 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-10:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LGSTORE1 | 26.25 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE1 | 13.12 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE1 | 13.12 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE2 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE2 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE3 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE3 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE4 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE4 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:LGSTORE2 | 19.17 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LGSTORE2 | 19.17 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE5 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE5 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE6 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE6 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE7 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE7 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE8 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE8 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
ElectricityPurchased:Facility | 853.25 | 2102.83 | 01-JAN-07:50 | 89016.25 | 26-JUN-15:00 |
ElectricityPurchased:Plant | 853.25 | 2102.83 | 01-JAN-07:50 | 89016.25 | 26-JUN-15:00 |
Cogeneration:ElectricityPurchased | 853.25 | 2102.83 | 01-JAN-07:50 | 89016.25 | 26-JUN-15:00 |
General:Cogeneration:ElectricityPurchased | 853.25 | 2102.83 | 01-JAN-07:50 | 89016.25 | 26-JUN-15:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 853.25 | 2102.83 | 01-JAN-07:50 | 89016.25 | 26-JUN-15:00 |
ElectricityNet:Plant | 853.25 | 2102.83 | 01-JAN-07:50 | 89016.25 | 26-JUN-15:00 |
Cogeneration:ElectricityNet | 853.25 | 2102.83 | 01-JAN-07:50 | 89016.25 | 26-JUN-15:00 |
General:Cogeneration:ElectricityNet | 853.25 | 2102.83 | 01-JAN-07:50 | 89016.25 | 26-JUN-15:00 |
Electricity:HVAC | 233.50 | 0.00 | 01-JAN-00:10 | 54170.71 | 26-JUN-15:00 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 84.27 | 0.00 | 01-JAN-00:10 | 43088.59 | 26-JUN-15:00 |
General:Cooling:Electricity | 84.27 | 0.00 | 01-JAN-00:10 | 43088.59 | 26-JUN-15:00 |
Fans:Electricity | 149.24 | 0.00 | 01-JAN-00:10 | 12037.59 | 21-DEC-17:00 |
General:Fans:Electricity | 149.24 | 0.00 | 01-JAN-00:10 | 12037.59 | 21-DEC-17:00 |
ExteriorLights:Electricity | 60.29 | 0.00 | 01-JAN-07:30 | 5507.06 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 60.29 | 0.00 | 01-JAN-07:30 | 5507.06 | 01-JAN-06:10 |
Electricity:Plant | 64.63 | 1211.00 | 01-JAN-08:10 | 11861.00 | 08-DEC-13:10 |
WaterSystems:Electricity | 64.63 | 1211.00 | 01-JAN-08:10 | 11861.00 | 08-DEC-13:10 |
Water Heater:WaterSystems:Electricity | 64.63 | 1211.00 | 01-JAN-08:10 | 11861.00 | 08-DEC-13:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 360.14 | 0.00 | 01-JAN-00:10 | 227604.68 | 21-DEC-18:00 |
NaturalGas:HVAC | 360.14 | 0.00 | 01-JAN-00:10 | 227604.68 | 21-DEC-18:00 |
Heating:NaturalGas | 360.14 | 0.00 | 01-JAN-00:10 | 227604.68 | 21-DEC-18:00 |
General:Heating:NaturalGas | 360.14 | 0.00 | 01-JAN-00:10 | 227604.68 | 21-DEC-18:00 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water:Plant | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
WaterSystems:Water | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water Heater:WaterSystems:Water | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
MainsWater:Facility | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
MainsWater:Plant | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
WaterSystems:MainsWater | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water Heater:WaterSystems:MainsWater | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 1103.27 | 0.00 | 01-JAN-00:10 | 324561.74 | 23-DEC-08:10 |
EnergyTransfer:Building | 487.57 | 0.00 | 01-JAN-00:10 | 152979.17 | 23-DEC-08:10 |
EnergyTransfer:Zone:LGSTORE1 | 99.85 | 0.00 | 01-JAN-00:10 | 30528.26 | 23-DEC-08:10 |
Heating:EnergyTransfer | 96.52 | 0.00 | 01-JAN-00:10 | 152979.17 | 23-DEC-08:10 |
Heating:EnergyTransfer:Zone:LGSTORE1 | 14.69 | 0.00 | 01-JAN-00:10 | 30528.26 | 23-DEC-08:10 |
General:Heating:EnergyTransfer | 96.52 | 0.00 | 01-JAN-00:10 | 152979.17 | 23-DEC-08:10 |
General:Heating:EnergyTransfer:Zone:LGSTORE1 | 14.69 | 0.00 | 01-JAN-00:10 | 30528.26 | 23-DEC-08:10 |
Cooling:EnergyTransfer | 391.05 | 0.00 | 01-JAN-00:10 | 88702.49 | 16-AUG-14:10 |
Cooling:EnergyTransfer:Zone:LGSTORE1 | 85.16 | 0.00 | 01-JAN-00:10 | 15241.75 | 16-AUG-16:10 |
General:Cooling:EnergyTransfer | 391.05 | 0.00 | 01-JAN-00:10 | 88702.49 | 16-AUG-14:10 |
General:Cooling:EnergyTransfer:Zone:LGSTORE1 | 85.16 | 0.00 | 01-JAN-00:10 | 15241.75 | 16-AUG-16:10 |
EnergyTransfer:Zone:SMSTORE1 | 52.75 | 0.00 | 01-JAN-00:10 | 11967.67 | 23-DEC-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE1 | 3.94 | 0.00 | 01-JAN-00:10 | 11967.67 | 23-DEC-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE1 | 3.94 | 0.00 | 01-JAN-00:10 | 11967.67 | 23-DEC-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE1 | 48.81 | 0.00 | 01-JAN-00:10 | 8816.84 | 12-MAR-17:20 |
General:Cooling:EnergyTransfer:Zone:SMSTORE1 | 48.81 | 0.00 | 01-JAN-00:10 | 8816.84 | 12-MAR-17:20 |
EnergyTransfer:Zone:SMSTORE2 | 41.75 | 0.00 | 01-JAN-00:10 | 12883.77 | 24-DEC-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE2 | 5.29 | 0.00 | 01-JAN-00:10 | 12883.77 | 24-DEC-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE2 | 5.29 | 0.00 | 01-JAN-00:10 | 12883.77 | 24-DEC-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE2 | 36.46 | 0.00 | 01-JAN-00:10 | 7829.97 | 16-AUG-14:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE2 | 36.46 | 0.00 | 01-JAN-00:10 | 7829.97 | 16-AUG-14:00 |
EnergyTransfer:Zone:SMSTORE3 | 41.43 | 0.00 | 01-JAN-00:10 | 13396.08 | 24-DEC-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE3 | 5.83 | 0.00 | 01-JAN-00:10 | 13396.08 | 24-DEC-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE3 | 5.83 | 0.00 | 01-JAN-00:10 | 13396.08 | 24-DEC-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE3 | 35.60 | 0.00 | 01-JAN-00:10 | 7834.02 | 16-AUG-14:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE3 | 35.60 | 0.00 | 01-JAN-00:10 | 7834.02 | 16-AUG-14:00 |
EnergyTransfer:Zone:SMSTORE4 | 40.12 | 0.00 | 01-JAN-00:10 | 14015.64 | 24-DEC-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE4 | 6.73 | 0.00 | 01-JAN-00:10 | 14015.64 | 24-DEC-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE4 | 6.73 | 0.00 | 01-JAN-00:10 | 14015.64 | 24-DEC-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE4 | 33.39 | 0.00 | 01-JAN-00:10 | 7689.21 | 16-AUG-14:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE4 | 33.39 | 0.00 | 01-JAN-00:10 | 7689.21 | 16-AUG-14:00 |
EnergyTransfer:Zone:LGSTORE2 | 67.73 | 0.00 | 01-JAN-00:10 | 28921.68 | 23-DEC-08:10 |
Heating:EnergyTransfer:Zone:LGSTORE2 | 14.07 | 0.00 | 01-JAN-00:10 | 28921.68 | 23-DEC-08:10 |
General:Heating:EnergyTransfer:Zone:LGSTORE2 | 14.07 | 0.00 | 01-JAN-00:10 | 28921.68 | 23-DEC-08:10 |
Cooling:EnergyTransfer:Zone:LGSTORE2 | 53.66 | 0.00 | 01-JAN-00:10 | 14134.78 | 26-JUN-15:00 |
General:Cooling:EnergyTransfer:Zone:LGSTORE2 | 53.66 | 0.00 | 01-JAN-00:10 | 14134.78 | 26-JUN-15:00 |
EnergyTransfer:Zone:SMSTORE5 | 34.23 | 0.00 | 01-JAN-00:10 | 14966.54 | 23-DEC-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE5 | 8.37 | 0.00 | 01-JAN-00:10 | 14966.54 | 23-DEC-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE5 | 8.37 | 0.00 | 01-JAN-00:10 | 14966.54 | 23-DEC-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE5 | 25.87 | 0.00 | 01-JAN-00:10 | 7447.92 | 26-JUN-15:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE5 | 25.87 | 0.00 | 01-JAN-00:10 | 7447.92 | 26-JUN-15:00 |
EnergyTransfer:Zone:SMSTORE6 | 34.02 | 0.00 | 01-JAN-00:10 | 15084.26 | 23-DEC-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE6 | 8.70 | 0.00 | 01-JAN-00:10 | 15084.26 | 23-DEC-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE6 | 8.70 | 0.00 | 01-JAN-00:10 | 15084.26 | 23-DEC-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE6 | 25.33 | 0.00 | 01-JAN-00:10 | 7398.22 | 26-JUN-15:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE6 | 25.33 | 0.00 | 01-JAN-00:10 | 7398.22 | 26-JUN-15:00 |
EnergyTransfer:Zone:SMSTORE7 | 33.81 | 0.00 | 01-JAN-00:10 | 15770.61 | 23-DEC-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE7 | 10.33 | 0.00 | 01-JAN-00:10 | 15770.61 | 23-DEC-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE7 | 10.33 | 0.00 | 01-JAN-00:10 | 15770.61 | 23-DEC-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE7 | 23.47 | 0.00 | 01-JAN-00:10 | 7309.96 | 26-JUN-15:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE7 | 23.47 | 0.00 | 01-JAN-00:10 | 7309.96 | 26-JUN-15:00 |
EnergyTransfer:Zone:SMSTORE8 | 41.89 | 0.00 | 01-JAN-00:10 | 18387.62 | 23-DEC-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE8 | 18.58 | 0.00 | 01-JAN-00:10 | 18387.62 | 23-DEC-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE8 | 18.58 | 0.00 | 01-JAN-00:10 | 18387.62 | 23-DEC-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE8 | 23.31 | 0.00 | 01-JAN-00:10 | 7815.10 | 16-AUG-14:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE8 | 23.31 | 0.00 | 01-JAN-00:10 | 7815.10 | 16-AUG-14:10 |
EnergyTransfer:HVAC | 615.69 | 0.00 | 01-JAN-00:10 | 182083.74 | 21-DEC-18:00 |
HeatingCoils:EnergyTransfer | 288.11 | 0.00 | 01-JAN-00:10 | 182083.74 | 21-DEC-18:00 |
CoolingCoils:EnergyTransfer | 327.58 | 0.00 | 01-JAN-00:10 | 137388.46 | 26-JUN-15:00 |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:01
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
LGSTORE1 | 0.000 | 0.000 | 14.690 | -85.158 | 0.000 | 0.000 | 25.067 | 87.116 | 26.249 | 31.710 | 0.000 | 3.048 | 0.004 | 0.000 | -10.996 | 0.000 | -29.601 | -62.126 |
SMSTORE1 | 0.000 | 0.000 | 3.938 | -48.810 | 0.000 | 0.000 | 12.333 | 53.201 | 13.125 | 15.753 | 0.000 | 1.650 | 0.001 | 0.000 | -5.751 | 0.000 | -14.464 | -30.975 |
SMSTORE2 | 0.000 | 0.000 | 5.293 | -36.455 | 0.000 | 0.000 | 7.485 | 37.572 | 10.421 | 15.726 | 0.000 | 1.625 | 0.000 | 0.000 | -5.708 | 0.000 | -14.899 | -21.061 |
SMSTORE3 | 0.000 | 0.000 | 5.828 | -35.601 | 0.000 | 0.000 | 7.494 | 37.572 | 10.421 | 15.740 | 0.000 | 1.625 | 0.000 | 0.000 | -5.661 | 0.000 | -14.848 | -22.570 |
SMSTORE4 | 0.000 | 0.000 | 6.729 | -33.391 | 0.000 | 0.000 | 7.509 | 37.572 | 10.421 | 15.762 | 0.000 | 1.626 | 0.001 | 0.000 | -5.605 | 0.000 | -14.774 | -25.849 |
LGSTORE2 | 0.000 | 0.000 | 14.066 | -53.664 | 0.000 | 0.000 | 25.822 | 37.162 | 19.173 | 31.628 | 0.000 | 2.930 | 0.000 | 0.000 | -10.916 | 0.000 | -27.138 | -39.062 |
SMSTORE5 | 0.000 | 0.000 | 8.367 | -25.867 | 0.000 | 0.000 | 12.835 | 19.120 | 9.586 | 15.782 | 0.000 | 1.627 | 0.001 | 0.000 | -5.482 | 0.000 | -14.910 | -21.059 |
SMSTORE6 | 0.000 | 0.000 | 8.695 | -25.329 | 0.000 | 0.000 | 12.842 | 19.120 | 9.586 | 15.792 | 0.000 | 1.627 | 0.001 | 0.000 | -5.463 | 0.000 | -14.887 | -21.984 |
SMSTORE7 | 0.000 | 0.000 | 10.335 | -23.472 | 0.000 | 0.000 | 12.875 | 19.120 | 9.586 | 15.826 | 0.000 | 1.627 | 0.000 | 0.000 | -5.379 | 0.000 | -14.781 | -25.738 |
SMSTORE8 | 0.000 | 0.000 | 18.579 | -23.307 | 0.000 | 0.000 | 13.004 | 19.120 | 9.586 | 15.922 | 0.000 | 1.709 | 0.002 | 0.000 | -5.065 | 0.000 | -18.586 | -30.962 |
Total Facility | 0.000 | 0.000 | 96.520 | -391.054 | 0.000 | 0.000 | 137.266 | 366.677 | 128.154 | 189.642 | 0.000 | 19.094 | 0.012 | 0.000 | -66.025 | 0.000 | -178.888 | -301.386 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
LGSTORE1 | 18-JUL-07:02 | 0.00 | 0.00 | 0.00 | -31635.82 | 0.00 | 0.00 | 180.71 | 75.00 | 74.62 | 547.05 | 0.00 | 14.98 | 30743.47 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 18-JUL-07:02 | 0.00 | 0.00 | 0.00 | -17688.55 | 0.00 | 0.00 | 88.21 | 37.50 | 37.31 | 269.44 | 0.00 | 3.77 | 17252.32 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 18-JUL-06:02 | 0.00 | 0.00 | 0.00 | -20091.84 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 108.02 | 0.00 | 0.00 | 19914.76 | 0.00 | -0.00 | 0.00 | -5.26 | 0.00 |
SMSTORE3 | 11-SEP-06:02 | 0.00 | 0.00 | 0.00 | -20056.89 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 0.00 | 0.00 | 0.00 | 20063.37 | 0.00 | -69.32 | 0.00 | -11.47 | 0.00 |
SMSTORE4 | 17-JUL-06:02 | 0.00 | 0.00 | 0.00 | -19640.34 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 78.45 | 0.00 | 0.00 | 19492.20 | 0.00 | -0.00 | 0.00 | -4.63 | 0.00 |
LGSTORE2 | 18-JUL-07:02 | 0.00 | 0.00 | 0.00 | -31173.46 | 0.00 | 0.00 | 0.00 | 75.00 | 73.64 | 537.89 | 0.00 | 3.95 | 30482.98 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 18-JUL-07:02 | 0.00 | 0.00 | 0.00 | -15996.04 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 270.77 | 0.00 | 4.02 | 15646.93 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 18-JUL-07:02 | 0.00 | 0.00 | 0.00 | -15859.78 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 271.46 | 0.00 | 4.58 | 15509.42 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 18-JUL-07:02 | 0.00 | 0.00 | 0.00 | -15653.78 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 273.17 | 0.00 | 6.83 | 15299.46 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 16-JUL-08:62 | 0.00 | 0.00 | 0.00 | -15398.56 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 500.64 | 0.00 | 158.24 | 14665.37 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 18-JUL-07:02 | 0.00 | 0.00 | 0.00 | -146515.30 | 0.00 | 0.00 | 564.44 | 450.00 | 1452.23 | 3282.91 | 0.00 | 75.27 | 140690.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
LGSTORE1 | 22-DEC-08:61 | 0.00 | 0.00 | 58888.31 | 0.00 | 0.00 | 0.00 | 0.00 | 75.00 | 73.64 | 2131.12 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -1584.33 | -59583.74 |
SMSTORE1 | 22-DEC-08:61 | 0.00 | 0.00 | 31212.19 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 1034.59 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -846.30 | -31474.80 |
SMSTORE2 | 12-FEB-08:61 | 0.00 | 0.00 | 32248.17 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 37.31 | 545.03 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -791.32 | -32076.69 |
SMSTORE3 | 12-FEB-08:61 | 0.00 | 0.00 | 32118.04 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 37.31 | 549.42 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -785.97 | -31956.31 |
SMSTORE4 | 12-FEB-08:61 | 0.00 | 0.00 | 32065.68 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 37.31 | 553.73 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -780.29 | -31913.94 |
LGSTORE2 | 22-DEC-08:61 | 0.00 | 0.00 | 56743.13 | 0.00 | 0.00 | 0.00 | 0.00 | 75.00 | 73.64 | 2115.44 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -1478.63 | -57528.57 |
SMSTORE5 | 22-DEC-08:61 | 0.00 | 0.00 | 29091.11 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 1055.03 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -816.78 | -29403.67 |
SMSTORE6 | 22-DEC-08:61 | 0.00 | 0.00 | 28944.35 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 1056.12 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -815.37 | -29259.43 |
SMSTORE7 | 23-DEC-08:12 | 0.00 | 0.00 | 28963.35 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 1310.05 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -913.33 | -29434.39 |
SMSTORE8 | 23-DEC-08:12 | 0.00 | 0.00 | 30180.71 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 1325.53 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -1134.28 | -30446.27 |
Total Facility | 21-DEC-08:61 | 0.00 | 0.00 | 281808.16 | 0.00 | 0.00 | 0.00 | 769.44 | 450.00 | 1452.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -9475.27 | 0.00 | -10584.07 | -264420.48 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:01
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 2.3151 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 2.3151 | 0.1777 | 1.0000 | Not calculated | 0.4115 | 0.1777 | ||
PSZ-AC_2:2 | 1.2540 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.2540 | 0.1641 | 1.0000 | Not calculated | 0.2057 | 0.1641 | ||
PSZ-AC_3:3 | 1.3120 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.3120 | 0.1568 | 1.0000 | Not calculated | 0.2057 | 0.1568 | ||
PSZ-AC_4:4 | 1.3046 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.3046 | 0.1577 | 1.0000 | Not calculated | 0.2057 | 0.1577 | ||
PSZ-AC_5:5 | 1.3016 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.3016 | 0.1581 | 1.0000 | Not calculated | 0.2057 | 0.1581 | ||
PSZ-AC_6:6 | 2.1956 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 2.1956 | 0.1874 | 1.0000 | Not calculated | 0.4115 | 0.1874 | ||
PSZ-AC_7:7 | 1.1352 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.1352 | 0.1812 | 1.0000 | Not calculated | 0.2057 | 0.1812 | ||
PSZ-AC_8:8 | 1.1270 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.1270 | 0.1825 | 1.0000 | Not calculated | 0.2057 | 0.1825 | ||
PSZ-AC_9:9 | 1.1187 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.1187 | 0.1839 | 1.0000 | Not calculated | 0.2057 | 0.1839 | ||
PSZ-AC_10:10 | 1.1750 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.1750 | 0.1751 | 1.0000 | Not calculated | 0.2057 | 0.1751 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 2.3151 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 2.3151 | 1.0000 | 1.0000 | Not calculated | 0.4115 | 0.1777 | ||
PSZ-AC_2:2 | 1.2540 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.2540 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1641 | ||
PSZ-AC_3:3 | 1.3120 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.3120 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1568 | ||
PSZ-AC_4:4 | 1.3046 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.3046 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1577 | ||
PSZ-AC_5:5 | 1.3016 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.3016 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1581 | ||
PSZ-AC_6:6 | 2.1956 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 2.1956 | 1.0000 | 1.0000 | Not calculated | 0.4115 | 0.1874 | ||
PSZ-AC_7:7 | 1.1352 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.1352 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1812 | ||
PSZ-AC_8:8 | 1.1270 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.1270 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1825 | ||
PSZ-AC_9:9 | 1.1187 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.1187 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1839 | ||
PSZ-AC_10:10 | 1.1750 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.1750 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1751 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
LGSTORE1 | PSZ-AC_1:1 | 0.000000 | 56.2505 | 0.001181 | 348.39 | 0.4115 | 1.0000 | 0.4115 | 1.000 | 0.4115 |
SMSTORE1 | PSZ-AC_2:2 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE2 | PSZ-AC_3:3 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE3 | PSZ-AC_4:4 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE4 | PSZ-AC_5:5 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
LGSTORE2 | PSZ-AC_6:6 | 0.000000 | 56.2505 | 0.001181 | 348.39 | 0.4115 | 1.0000 | 0.4115 | 1.000 | 0.4115 |
SMSTORE5 | PSZ-AC_7:7 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE6 | PSZ-AC_8:8 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE7 | PSZ-AC_9:9 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE8 | PSZ-AC_10:10 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC_1:1 | 0.000000 | 56.25 | 0.001181 | 348.3864 | 0.4115 | 0.4115 | 0.4115 |
PSZ-AC_2:2 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_3:3 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_4:4 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_5:5 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_6:6 | 0.000000 | 56.25 | 0.001181 | 348.3864 | 0.4115 | 0.4115 | 0.4115 |
PSZ-AC_7:7 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_8:8 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_9:9 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_10:10 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LGSTORE1 | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.3151 | 2.3151 | 2.3151 | No | 0.4115 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE1 | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2540 | 1.2540 | 1.2540 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE2 | PSZ-AC_3:3 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.3120 | 1.3120 | 1.3120 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE3 | PSZ-AC_4:4 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.3046 | 1.3046 | 1.3046 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE4 | PSZ-AC_5:5 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.3016 | 1.3016 | 1.3016 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LGSTORE2 | PSZ-AC_6:6 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.1956 | 2.1956 | 2.1956 | No | 0.4115 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE5 | PSZ-AC_7:7 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1352 | 1.1352 | 1.1352 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE6 | PSZ-AC_8:8 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1270 | 1.1270 | 1.1270 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE7 | PSZ-AC_9:9 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1187 | 1.1187 | 1.1187 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE8 | PSZ-AC_10:10 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1750 | 1.1750 | 1.1750 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 2.3151 | 2.3151 | 2.3151 | 2.3151 | 0.4115 | 1.0000 |
PSZ-AC_2:2 | 1.2540 | 1.2540 | 1.2540 | 1.2540 | 0.2057 | 1.0000 |
PSZ-AC_3:3 | 1.3120 | 1.3120 | 1.3120 | 1.3120 | 0.2057 | 1.0000 |
PSZ-AC_4:4 | 1.3046 | 1.3046 | 1.3046 | 1.3046 | 0.2057 | 1.0000 |
PSZ-AC_5:5 | 1.3016 | 1.3016 | 1.3016 | 1.3016 | 0.2057 | 1.0000 |
PSZ-AC_6:6 | 2.1956 | 2.1956 | 2.1956 | 2.1956 | 0.4115 | 1.0000 |
PSZ-AC_7:7 | 1.1352 | 1.1352 | 1.1352 | 1.1352 | 0.2057 | 1.0000 |
PSZ-AC_8:8 | 1.1270 | 1.1270 | 1.1270 | 1.1270 | 0.2057 | 1.0000 |
PSZ-AC_9:9 | 1.1187 | 1.1187 | 1.1187 | 1.1187 | 0.2057 | 1.0000 |
PSZ-AC_10:10 | 1.1750 | 1.1750 | 1.1750 | 1.1750 | 0.2057 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LGSTORE1 | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.3151 | 2.3151 | 2.3151 | No | 0.4115 | 0.2614 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE1 | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2540 | 1.2540 | 1.2540 | No | 0.2057 | 0.2740 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE2 | PSZ-AC_3:3 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.3120 | 1.3120 | 1.3120 | No | 0.2057 | 0.2705 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE3 | PSZ-AC_4:4 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.3046 | 1.3046 | 1.3046 | No | 0.2057 | 0.2683 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE4 | PSZ-AC_5:5 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.3016 | 1.3016 | 1.3016 | No | 0.2057 | 0.2649 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LGSTORE2 | PSZ-AC_6:6 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.1956 | 2.1956 | 2.1956 | No | 0.4115 | 0.2756 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE5 | PSZ-AC_7:7 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1352 | 1.1352 | 1.1352 | No | 0.2057 | 0.2578 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE6 | PSZ-AC_8:8 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1270 | 1.1270 | 1.1270 | No | 0.2057 | 0.2581 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE7 | PSZ-AC_9:9 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1187 | 1.1187 | 1.1187 | No | 0.2057 | 0.2538 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE8 | PSZ-AC_10:10 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1750 | 1.1750 | 1.1750 | No | 0.2057 | 0.2123 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 2.3151 | 2.3151 | 2.3151 | 2.3151 | 0.4115 | 1.0000 |
PSZ-AC_2:2 | 1.2540 | 1.2540 | 1.2540 | 1.2540 | 0.2057 | 1.0000 |
PSZ-AC_3:3 | 1.3120 | 1.3120 | 1.3120 | 1.3120 | 0.2057 | 1.0000 |
PSZ-AC_4:4 | 1.3046 | 1.3046 | 1.3046 | 1.3046 | 0.2057 | 1.0000 |
PSZ-AC_5:5 | 1.3016 | 1.3016 | 1.3016 | 1.3016 | 0.2057 | 1.0000 |
PSZ-AC_6:6 | 2.1956 | 2.1956 | 2.1956 | 2.1956 | 0.4115 | 1.0000 |
PSZ-AC_7:7 | 1.1352 | 1.1352 | 1.1352 | 1.1352 | 0.2057 | 1.0000 |
PSZ-AC_8:8 | 1.1270 | 1.1270 | 1.1270 | 1.1270 | 0.2057 | 1.0000 |
PSZ-AC_9:9 | 1.1187 | 1.1187 | 1.1187 | 1.1187 | 0.2057 | 1.0000 |
PSZ-AC_10:10 | 1.1750 | 1.1750 | 1.1750 | 1.1750 | 0.2057 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:01
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Denver-Aurora-Buckley AFB CO USA TMY3 WMO#=724695 |
Total gross floor area [m2] | 2090.32 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
LGSTORE1 | 348.39 | 348.39 | 0.00 | 112.00 |
SMSTORE1 | 174.19 | 174.19 | 0.00 | 112.00 |
SMSTORE2 | 174.19 | 174.19 | 0.00 | 84.29 |
SMSTORE3 | 174.19 | 174.19 | 0.00 | 84.29 |
SMSTORE4 | 174.19 | 174.19 | 0.00 | 84.29 |
LGSTORE2 | 348.39 | 348.39 | 0.00 | 77.29 |
SMSTORE5 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE6 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE7 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE8 | 174.19 | 174.19 | 0.00 | 77.29 |
Totals | 2090.32 | 2090.32 | 0.00 |
Data | |
Number of hours heating loads not met | 1.17 |
Number of hours cooling loads not met | 0.00 |
Number of hours not met | 1.17 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 360.14 | 227604.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 84.27 | 43088.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 366.68 | 23459.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 60.29 | 5507.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 128.15 | 8059.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 149.24 | 12037.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 64.63 | 11861.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 128.15 | 853.25 |
Natural Gas | 0.00 | 360.14 |
Additional | 0.00 | 0.00 |
Total | 128.15 | 1213.39 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 175.42 |
Space Heating | 0.00 |
Space Cooling | 40.31 |
Fans (All) | 71.40 |
Service Water Heating | 30.92 |
Receptacle Equipment | 61.31 |
Miscellaneous (All) | 408.19 |
Subtotal | 408.19 |
Natural Gas [MJ/m2] | |
Space Heating | 172.29 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 172.29 |
Subtotal | 172.29 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 30.22 |
Space Heating | 29.68 |
Space Cooling | 6.94 |
Fans (All) | 12.30 |
Service Water Heating | 5.33 |
Receptacle Equipment | 10.56 |
Miscellaneous | 4.97 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
TYPE1_OCC_SCH | 1630. | 5840. |
TYPE2_OCC_SCH | 995. | 4429. |
TYPE3_OCC_SCH | 1709. | 4064. |
LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 3767. | 8760. |
LTG_SCH_BASE_LPD2 | 3238. | 8760. |
LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 3296. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | 5084. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | 5084. | 8760. |
LTG_SCH_BASE_SMALL_LPD1 | 4453. | 8760. |
LTG_SCH_BASE_LPD1 | 4376. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | 3767. | 8760. |
LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 3584. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 4096. | 8760. |
TYPE1_EQUIP_SCH | 4868. | 8760. |
TYPE2_EQUIP_SCH | 3893. | 8760. |
TYPE3_EQUIP_SCH | 3584. | 8760. |
TYPE1_INFIL_SCH | 4302. | 8760. |
TYPE2_INFIL_SCH | 5164. | 8760. |
TYPE3_INFIL_SCH | 5438. | 8760. |
INFIL_DOOR_OPENING_SCH | 2477. | 4380. |
TYPE1_MINOA_MOTORIZEDDAMPER_SCH | 5579. | 5579. |
TYPE2_MINOA_MOTORIZEDDAMPER_SCH | 4429. | 4429. |
TYPE3_MINOA_MOTORIZEDDAMPER_SCH | 4064. | 4064. |
TYPE1_SWH_SCH | 2063. | 6048. |
TYPE2_SWH_SCH | 1831. | 4429. |
TYPE3_SWH_SCH | 1733. | 4064. |
AVERAGE_SWH_SCH | 1863. | 6152. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 7118. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 5839. | 5839. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 7300. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6570. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
TYPE1_HTGSETP_SCH_NO_OPTIMUM | LGSTORE1 DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
TYPE1_CLGSETP_SCH_NO_OPTIMUM | LGSTORE1 DUAL SP CONTROL | July | 23.89 | 365 | 23.89 | 365 |
TYPE2_HTGSETP_SCH_NO_OPTIMUM | SMSTORE2 DUAL SP CONTROL | January | 21.11 | 365 | 15.56 | 365 |
TYPE2_CLGSETP_SCH_NO_OPTIMUM | SMSTORE2 DUAL SP CONTROL | July | 23.89 | 365 | 29.44 | 365 |
TYPE3_HTGSETP_SCH_NO_OPTIMUM | LGSTORE2 DUAL SP CONTROL | January | 21.11 | 365 | 15.56 | 365 |
TYPE3_CLGSETP_SCH_NO_OPTIMUM | LGSTORE2 DUAL SP CONTROL | July | 23.89 | 365 | 29.44 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:01
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
LGSTORE1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 8758.83 | 1.17 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 8758.83 | 1.17 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 8759.17 | 0.83 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 8759.33 | 0.67 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 8758.17 | 1.83 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 8758.50 | 1.50 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 8758.83 | 1.17 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 8759.50 | 0.50 | 0.00 | 0.00 | 0.00 |
Min | 8758.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 1.83 | 0.00 | 0.00 | 0.00 |
Average | 8759.12 | 0.88 | 0.00 | 0.00 | 0.00 |
Sum | 87591.17 | 8.83 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
LGSTORE1 | 89041.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 43777.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 25474.17 | 0.83 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 25474.17 | 0.83 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 25474.33 | 0.67 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 93207.00 | 4.00 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 45907.00 | 5.00 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 45907.50 | 4.50 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 45908.50 | 3.50 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 45910.50 | 1.50 | 0.00 | 0.00 | 0.00 |
Min | 25474.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 93207.00 | 5.00 | 0.00 | 0.00 | 0.00 |
Average | 48608.12 | 2.08 | 0.00 | 0.00 | 0.00 |
Sum | 486081.17 | 20.83 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
LGSTORE1 | 8738.83 | 21.17 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 8745.33 | 14.67 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 8720.17 | 39.83 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 8721.17 | 38.83 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 8727.67 | 32.33 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 8736.50 | 23.50 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 8733.17 | 26.83 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 8733.50 | 26.50 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 8735.67 | 24.33 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 8750.33 | 9.67 | 0.00 | 0.00 | 0.00 |
Min | 8720.17 | 9.67 | 0.00 | 0.00 | 0.00 |
Max | 8750.33 | 39.83 | 0.00 | 0.00 | 0.00 |
Average | 8734.23 | 25.77 | 0.00 | 0.00 | 0.00 |
Sum | 87342.33 | 257.67 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
LGSTORE1 | 88996.33 | 44.67 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 43777.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 25461.50 | 13.50 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 25461.67 | 13.33 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 25456.83 | 18.17 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 93139.00 | 72.00 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 45860.83 | 51.17 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 45857.17 | 54.83 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 45855.67 | 56.33 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 45862.83 | 49.17 | 0.00 | 0.00 | 0.00 |
Min | 25456.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 93139.00 | 72.00 | 0.00 | 0.00 | 0.00 |
Average | 48572.88 | 37.32 | 0.00 | 0.00 | 0.00 |
Sum | 485728.83 | 373.17 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:01
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:37:01
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
For: Environment
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTRIPMALL
For: Environment
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5B
For: Environment
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_CO_DENVER
For: Environment
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: ZoneCoolingSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.293099E+10 | 13275.25 | 06-JAN-00:01 | -15.8 | -15.8 | 0.109643E+10 | 1685.85 | 20-JAN-13:00 | 21.00 | 6.96 |
February | 0.227924E+10 | 10169.04 | 10-FEB-00:02 | -8.0 | -8.7 | 0.986598E+09 | 1685.81 | 18-FEB-13:39 | 20.00 | 7.73 |
March | 0.350127E+10 | 7819.31 | 04-MAR-00:03 | -1.8 | -4.2 | 0.115476E+10 | 1685.85 | 12-MAR-17:19 | 17.33 | 5.43 |
April | 0.320822E+10 | 8720.07 | 02-APR-18:03 | -4.2 | -4.6 | 0.113325E+10 | 1685.85 | 07-APR-12:00 | 21.00 | 8.54 |
May | 0.649791E+10 | 8997.19 | 31-MAY-16:10 | 27.83 | 14.82 | 0.134668E+10 | 1685.89 | 21-MAY-16:10 | 27.83 | 14.82 |
June | 0.128445E+11 | 23367.38 | 14-JUN-07:03 | 28.30 | 11.72 | 0.135443E+10 | 1686.00 | 18-JUN-17:00 | 22.20 | 16.55 |
July | 0.134349E+11 | 31634.07 | 18-JUL-07:02 | 24.33 | 12.85 | 0.141262E+10 | 1685.99 | 29-JUL-12:39 | 24.67 | 18.58 |
August | 0.140022E+11 | 23182.94 | 03-AUG-07:03 | 21.33 | 15.03 | 0.139392E+10 | 1685.97 | 27-AUG-17:10 | 20.67 | 14.82 |
September | 0.123289E+11 | 24453.95 | 13-SEP-07:03 | 20.18 | 12.26 | 0.135223E+10 | 1685.95 | 01-SEP-12:00 | 20.18 | 12.26 |
October | 0.690419E+10 | 11549.11 | 11-OCT-14:00 | 27.00 | 9.73 | 0.126831E+10 | 1685.85 | 01-OCT-12:00 | 27.00 | 9.73 |
November | 0.455503E+10 | 10288.39 | 28-NOV-21:22 | -8.0 | -8.0 | 0.109957E+10 | 1685.85 | 05-NOV-12:00 | -8.0 | -8.0 |
December | 0.267036E+10 | 15016.10 | 22-DEC-00:01 | -20.2 | -20.3 | 0.111082E+10 | 1685.85 | 02-DEC-13:00 | -20.2 | -20.3 |
Annual Sum or Average | 0.851576E+11 | 0.147096E+11 | ||||||||
Minimum of Months | 0.227924E+10 | 7819.31 | -20.2 | -20.3 | 0.986598E+09 | 1685.81 | -20.2 | -20.3 | ||
Maximum of Months | 0.140022E+11 | 31634.07 | 28.30 | 15.03 | 0.141262E+10 | 1686.00 | 27.83 | 18.58 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.167966E+10 | 3631.14 | 22-JAN-09:01 | 1.33 | 0.34 | 0.582924E+09 | 842.90 | 20-JAN-13:00 | 1.33 | 0.34 |
February | 0.137772E+10 | 3447.44 | 28-FEB-09:03 | 1.17 | 0.63 | 0.516424E+09 | 842.90 | 18-FEB-13:00 | 1.17 | 0.63 |
March | 0.208855E+10 | 15646.35 | 12-MAR-17:08 | 17.67 | 5.51 | 0.600836E+09 | 842.90 | 12-MAR-16:40 | 17.67 | 5.51 |
April | 0.179928E+10 | 3737.47 | 22-APR-08:62 | 0.00 | -0.1 | 0.599006E+09 | 842.90 | 09-APR-17:00 | 0.00 | -0.1 |
May | 0.403387E+10 | 15683.15 | 17-MAY-20:07 | 17.83 | 8.54 | 0.687003E+09 | 842.93 | 21-MAY-16:10 | 21.83 | 12.79 |
June | 0.740941E+10 | 15702.18 | 10-JUN-20:25 | 17.45 | 8.95 | 0.673823E+09 | 842.96 | 03-JUN-12:30 | 17.45 | 8.95 |
July | 0.777468E+10 | 17688.35 | 18-JUL-07:02 | 24.33 | 12.85 | 0.703171E+09 | 842.97 | 16-JUL-12:00 | 24.33 | 12.85 |
August | 0.797452E+10 | 15580.06 | 18-AUG-22:09 | 18.00 | 8.15 | 0.693389E+09 | 842.97 | 27-AUG-17:10 | 20.67 | 14.82 |
September | 0.699157E+10 | 16297.74 | 16-SEP-19:39 | 16.80 | 8.31 | 0.675946E+09 | 842.95 | 01-SEP-12:00 | 16.80 | 8.31 |
October | 0.382763E+10 | 16243.13 | 07-OCT-18:07 | 16.83 | 7.37 | 0.655459E+09 | 842.90 | 01-OCT-12:00 | 16.83 | 7.37 |
November | 0.239944E+10 | 4698.49 | 07-NOV-14:30 | 22.00 | 7.34 | 0.585642E+09 | 842.90 | 05-NOV-16:10 | 22.00 | 7.34 |
December | 0.145333E+10 | 3642.91 | 05-DEC-09:03 | 0.33 | -3.1 | 0.581612E+09 | 842.90 | 02-DEC-13:00 | 0.33 | -3.1 |
Annual Sum or Average | 0.488097E+11 | 0.755523E+10 | ||||||||
Minimum of Months | 0.137772E+10 | 3447.44 | 0.00 | -3.1 | 0.516424E+09 | 842.90 | 0.00 | -3.1 | ||
Maximum of Months | 0.797452E+10 | 17688.35 | 24.33 | 12.85 | 0.703171E+09 | 842.97 | 24.33 | 14.82 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.130524E+10 | 3840.21 | 30-JAN-09:43 | -2.0 | -2.0 | 0.335411E+09 | 824.90 | 21-JAN-13:00 | -2.0 | -2.0 |
February | 0.104914E+10 | 4466.95 | 08-FEB-19:33 | -5.3 | -5.3 | 0.298927E+09 | 842.90 | 18-FEB-13:00 | 20.00 | 7.73 |
March | 0.160515E+10 | 5271.73 | 04-MAR-11:02 | -9.3 | -9.6 | 0.360983E+09 | 842.90 | 11-MAR-13:00 | 18.00 | 5.91 |
April | 0.139590E+10 | 4177.41 | 02-APR-10:02 | -3.8 | -4.8 | 0.349815E+09 | 842.88 | 08-APR-12:00 | 16.00 | 5.15 |
May | 0.283762E+10 | 4886.41 | 17-MAY-13:00 | 29.00 | 11.92 | 0.412591E+09 | 842.90 | 06-MAY-12:30 | 29.00 | 11.92 |
June | 0.550541E+10 | 14933.26 | 27-JUN-06:03 | 20.78 | 8.99 | 0.416933E+09 | 842.97 | 03-JUN-12:30 | 20.78 | 8.99 |
July | 0.572425E+10 | 20090.67 | 18-JUL-06:02 | 22.33 | 11.85 | 0.420082E+09 | 842.98 | 29-JUL-12:30 | 24.50 | 18.54 |
August | 0.600029E+10 | 14323.91 | 20-AUG-07:03 | 21.00 | 14.01 | 0.431549E+09 | 842.93 | 12-AUG-12:09 | 21.00 | 14.01 |
September | 0.516770E+10 | 19183.63 | 11-SEP-06:02 | 19.00 | 9.04 | 0.407506E+09 | 842.92 | 09-SEP-12:00 | 19.00 | 9.04 |
October | 0.287382E+10 | 6160.06 | 11-OCT-14:00 | 27.00 | 9.73 | 0.382177E+09 | 842.90 | 07-OCT-12:20 | 27.00 | 9.73 |
November | 0.188728E+10 | 4297.17 | 07-NOV-14:00 | 22.00 | 7.34 | 0.335675E+09 | 793.98 | 25-NOV-13:00 | 15.00 | 4.95 |
December | 0.110344E+10 | 4184.95 | 18-DEC-08:61 | -2.5 | -4.2 | 0.333643E+09 | 842.90 | 02-DEC-13:00 | -2.5 | -4.2 |
Annual Sum or Average | 0.364552E+11 | 0.448529E+10 | ||||||||
Minimum of Months | 0.104914E+10 | 3840.21 | -9.3 | -9.6 | 0.298927E+09 | 793.98 | -2.5 | -4.2 | ||
Maximum of Months | 0.600029E+10 | 20090.67 | 29.00 | 14.01 | 0.431549E+09 | 842.98 | 29.00 | 18.54 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.118556E+10 | 4519.69 | 07-JAN-10:02 | -5.7 | -8.0 | 0.333899E+09 | 813.26 | 21-JAN-13:00 | 13.00 | 4.88 |
February | 0.948932E+09 | 4152.23 | 01-FEB-11:02 | -3.7 | -4.6 | 0.298175E+09 | 842.90 | 18-FEB-13:00 | 20.00 | 7.73 |
March | 0.150116E+10 | 5300.59 | 04-MAR-11:42 | -9.5 | -9.7 | 0.359977E+09 | 842.88 | 11-MAR-13:09 | 17.17 | 5.55 |
April | 0.128185E+10 | 3839.22 | 22-APR-07:01 | 0.00 | -0.0 | 0.348240E+09 | 842.88 | 08-APR-12:00 | 0.00 | -0.0 |
May | 0.272669E+10 | 4817.00 | 17-MAY-13:00 | 29.00 | 11.92 | 0.411519E+09 | 842.90 | 06-MAY-12:50 | 29.00 | 11.92 |
June | 0.550742E+10 | 15461.03 | 27-JUN-06:03 | 20.78 | 8.99 | 0.416928E+09 | 842.97 | 03-JUN-12:30 | 20.78 | 8.99 |
July | 0.574468E+10 | 20027.66 | 18-JUL-06:02 | 22.33 | 11.85 | 0.420081E+09 | 842.98 | 29-JUL-12:30 | 24.50 | 18.54 |
August | 0.600896E+10 | 14876.83 | 21-AUG-06:03 | 19.75 | 12.40 | 0.431544E+09 | 842.93 | 12-AUG-12:09 | 19.75 | 12.40 |
September | 0.515582E+10 | 20055.22 | 11-SEP-06:02 | 19.00 | 9.04 | 0.407400E+09 | 842.93 | 09-SEP-12:00 | 19.00 | 9.04 |
October | 0.278142E+10 | 6111.80 | 11-OCT-14:00 | 27.00 | 9.73 | 0.381141E+09 | 842.90 | 07-OCT-12:09 | 27.00 | 9.73 |
November | 0.175673E+10 | 4970.77 | 28-NOV-19:53 | -8.0 | -8.0 | 0.334155E+09 | 785.67 | 25-NOV-13:00 | -8.0 | -8.0 |
December | 0.100152E+10 | 4341.10 | 07-DEC-09:02 | -4.7 | -6.0 | 0.332737E+09 | 842.90 | 02-DEC-13:00 | -4.7 | -6.0 |
Annual Sum or Average | 0.356007E+11 | 0.447580E+10 | ||||||||
Minimum of Months | 0.948932E+09 | 3839.22 | -9.5 | -9.7 | 0.298175E+09 | 785.67 | -8.0 | -8.0 | ||
Maximum of Months | 0.600896E+10 | 20055.22 | 29.00 | 12.40 | 0.431544E+09 | 842.98 | 29.00 | 18.54 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.101773E+10 | 3513.67 | 26-JAN-08:61 | 0.67 | -0.7 | 0.331745E+09 | 793.80 | 21-JAN-13:00 | 0.67 | -0.7 |
February | 0.803945E+09 | 3836.84 | 02-FEB-20:53 | -2.0 | -4.1 | 0.297235E+09 | 842.90 | 18-FEB-13:00 | 20.00 | 7.73 |
March | 0.133242E+10 | 4172.77 | 14-MAR-13:00 | 24.00 | 7.90 | 0.358182E+09 | 842.89 | 11-MAR-13:09 | 24.00 | 7.90 |
April | 0.109503E+10 | 3780.49 | 22-APR-07:01 | 0.00 | -0.0 | 0.345715E+09 | 842.85 | 08-APR-12:00 | 0.00 | -0.0 |
May | 0.249444E+10 | 4604.31 | 17-MAY-13:00 | 29.00 | 11.92 | 0.409459E+09 | 842.90 | 13-MAY-12:09 | 29.00 | 11.92 |
June | 0.529754E+10 | 14188.19 | 27-JUN-06:03 | 20.78 | 8.99 | 0.416878E+09 | 842.97 | 03-JUN-12:30 | 20.78 | 8.99 |
July | 0.555033E+10 | 19639.12 | 17-JUL-06:02 | 22.50 | 11.12 | 0.420038E+09 | 842.98 | 29-JUL-12:39 | 24.67 | 18.58 |
August | 0.580556E+10 | 13888.95 | 21-AUG-06:03 | 19.75 | 12.40 | 0.431498E+09 | 842.93 | 12-AUG-12:09 | 19.75 | 12.40 |
September | 0.496414E+10 | 18896.42 | 11-SEP-06:02 | 19.00 | 9.04 | 0.407095E+09 | 842.92 | 09-SEP-12:00 | 19.00 | 9.04 |
October | 0.260639E+10 | 5951.91 | 11-OCT-14:00 | 27.00 | 9.73 | 0.379239E+09 | 842.90 | 07-OCT-12:20 | 27.00 | 9.73 |
November | 0.156861E+10 | 3788.82 | 07-NOV-14:00 | 22.00 | 7.34 | 0.332006E+09 | 773.16 | 25-NOV-13:00 | 15.00 | 4.95 |
December | 0.855061E+09 | 3838.70 | 09-DEC-10:13 | -2.0 | -4.3 | 0.331378E+09 | 842.90 | 02-DEC-13:00 | -2.0 | -4.3 |
Annual Sum or Average | 0.333912E+11 | 0.446047E+10 | ||||||||
Minimum of Months | 0.803945E+09 | 3513.67 | -2.0 | -4.3 | 0.297235E+09 | 773.16 | -2.0 | -4.3 | ||
Maximum of Months | 0.580556E+10 | 19639.12 | 29.00 | 12.40 | 0.431498E+09 | 842.98 | 29.00 | 18.58 |
Report: ZoneCoolingSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.138526E+10 | 5488.21 | 25-JAN-18:50 | 5.17 | 1.37 | 0.112883E+10 | 2135.86 | 21-JAN-15:20 | 5.17 | 1.37 |
February | 0.104607E+10 | 4947.24 | 19-FEB-10:05 | 5.67 | 3.98 | 0.101555E+10 | 2247.76 | 18-FEB-15:00 | 5.67 | 3.98 |
March | 0.194678E+10 | 7163.06 | 14-MAR-13:00 | 24.00 | 7.90 | 0.122102E+10 | 2247.70 | 11-MAR-15:20 | 24.00 | 7.90 |
April | 0.158553E+10 | 6892.70 | 22-APR-08:20 | 0.00 | -0.2 | 0.117236E+10 | 2247.75 | 08-APR-14:00 | 0.00 | -0.2 |
May | 0.389342E+10 | 7976.15 | 17-MAY-14:10 | 28.67 | 11.73 | 0.138991E+10 | 2247.80 | 06-MAY-14:39 | 28.67 | 11.73 |
June | 0.886747E+10 | 28809.68 | 25-JUN-08:62 | 28.08 | 13.27 | 0.142959E+10 | 2247.92 | 03-JUN-14:00 | 28.08 | 13.27 |
July | 0.928597E+10 | 31171.27 | 18-JUL-07:02 | 24.33 | 12.85 | 0.143831E+10 | 2247.96 | 15-JUL-14:30 | 24.33 | 12.85 |
August | 0.980051E+10 | 27604.66 | 20-AUG-08:62 | 23.50 | 14.21 | 0.147964E+10 | 2247.98 | 05-AUG-14:39 | 23.50 | 14.21 |
September | 0.826425E+10 | 28203.45 | 11-SEP-07:03 | 20.63 | 10.22 | 0.139653E+10 | 2247.82 | 09-SEP-14:09 | 20.63 | 10.22 |
October | 0.415817E+10 | 10775.74 | 11-OCT-14:10 | 26.83 | 9.68 | 0.128634E+10 | 2247.80 | 07-OCT-14:30 | 26.83 | 9.68 |
November | 0.230489E+10 | 8350.00 | 21-NOV-20:33 | -3.0 | -3.0 | 0.112239E+10 | 2007.86 | 25-NOV-15:09 | 13.50 | 4.91 |
December | 0.112609E+10 | 6878.02 | 18-DEC-09:07 | 0.50 | -2.0 | 0.113200E+10 | 2247.80 | 02-DEC-15:20 | 0.50 | -2.0 |
Annual Sum or Average | 0.536644E+11 | 0.152125E+11 | ||||||||
Minimum of Months | 0.104607E+10 | 4947.24 | -3.0 | -3.0 | 0.101555E+10 | 2007.86 | 0.00 | -2.0 | ||
Maximum of Months | 0.980051E+10 | 31171.27 | 28.67 | 14.21 | 0.147964E+10 | 2247.98 | 28.67 | 14.21 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.539895E+09 | 3473.69 | 03-JAN-19:13 | -4.3 | -4.3 | 0.573361E+09 | 1123.53 | 21-JAN-15:20 | 13.67 | 5.40 |
February | 0.413911E+09 | 3354.16 | 09-FEB-18:17 | -3.7 | -6.1 | 0.512696E+09 | 1123.85 | 18-FEB-15:00 | 18.00 | 7.48 |
March | 0.797738E+09 | 3729.68 | 14-MAR-13:00 | 24.00 | 7.90 | 0.618676E+09 | 1123.83 | 11-MAR-15:20 | 24.00 | 7.90 |
April | 0.550640E+09 | 2876.56 | 22-APR-08:62 | 0.00 | -0.1 | 0.597817E+09 | 1123.85 | 08-APR-14:20 | 0.00 | -0.1 |
May | 0.172385E+10 | 4134.53 | 17-MAY-14:10 | 28.67 | 11.73 | 0.705797E+09 | 1123.87 | 13-MAY-14:00 | 28.67 | 11.73 |
June | 0.455374E+10 | 14824.82 | 25-JUN-08:62 | 28.08 | 13.27 | 0.714922E+09 | 1123.91 | 17-JUN-14:00 | 28.08 | 13.27 |
July | 0.478036E+10 | 15994.88 | 18-JUL-07:02 | 24.33 | 12.85 | 0.719299E+09 | 1123.96 | 29-JUL-14:00 | 23.00 | 17.56 |
August | 0.503429E+10 | 13120.60 | 20-AUG-08:62 | 23.50 | 14.21 | 0.739946E+09 | 1123.96 | 05-AUG-14:50 | 23.50 | 14.21 |
September | 0.420380E+10 | 13763.46 | 11-SEP-07:03 | 20.63 | 10.22 | 0.700265E+09 | 1123.87 | 02-SEP-14:09 | 20.63 | 10.22 |
October | 0.187024E+10 | 5613.94 | 11-OCT-14:10 | 26.83 | 9.68 | 0.654384E+09 | 1123.87 | 07-OCT-14:20 | 26.83 | 9.68 |
November | 0.958678E+09 | 3342.86 | 07-NOV-14:00 | 22.00 | 7.34 | 0.572162E+09 | 1063.48 | 25-NOV-15:09 | 13.50 | 4.91 |
December | 0.440094E+09 | 3513.74 | 07-DEC-19:23 | -4.6 | -7.8 | 0.572599E+09 | 1123.87 | 02-DEC-15:30 | -4.6 | -7.8 |
Annual Sum or Average | 0.258672E+11 | 0.768192E+10 | ||||||||
Minimum of Months | 0.413911E+09 | 2876.56 | -4.6 | -7.8 | 0.512696E+09 | 1063.48 | -4.6 | -7.8 | ||
Maximum of Months | 0.503429E+10 | 15994.88 | 28.67 | 14.21 | 0.739946E+09 | 1123.96 | 28.67 | 17.56 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.509756E+09 | 4071.05 | 12-JAN-19:23 | -7.0 | -7.0 | 0.572331E+09 | 1123.24 | 21-JAN-15:20 | 13.67 | 5.40 |
February | 0.383873E+09 | 4014.79 | 11-FEB-11:32 | -6.7 | -7.0 | 0.512039E+09 | 1123.85 | 18-FEB-15:00 | 18.00 | 7.48 |
March | 0.767048E+09 | 3619.34 | 14-MAR-13:00 | 24.00 | 7.90 | 0.617855E+09 | 1123.84 | 11-MAR-15:20 | 24.00 | 7.90 |
April | 0.524531E+09 | 2873.88 | 22-APR-08:62 | 0.00 | -0.1 | 0.596752E+09 | 1123.85 | 08-APR-14:20 | 0.00 | -0.1 |
May | 0.166298E+10 | 4055.02 | 17-MAY-14:10 | 28.67 | 11.73 | 0.704802E+09 | 1123.87 | 06-MAY-14:39 | 28.67 | 11.73 |
June | 0.448221E+10 | 14717.58 | 25-JUN-08:62 | 28.08 | 13.27 | 0.714912E+09 | 1123.91 | 17-JUN-14:00 | 28.08 | 13.27 |
July | 0.471421E+10 | 15858.63 | 18-JUL-07:02 | 24.33 | 12.85 | 0.719288E+09 | 1123.96 | 29-JUL-14:50 | 23.00 | 17.56 |
August | 0.496765E+10 | 12710.03 | 20-AUG-08:62 | 23.50 | 14.21 | 0.739938E+09 | 1123.94 | 05-AUG-14:39 | 23.50 | 14.21 |
September | 0.414598E+10 | 13419.42 | 11-SEP-07:03 | 20.63 | 10.22 | 0.700168E+09 | 1123.87 | 02-SEP-14:20 | 20.63 | 10.22 |
October | 0.183155E+10 | 5544.60 | 11-OCT-14:10 | 26.83 | 9.68 | 0.653644E+09 | 1123.87 | 07-OCT-14:09 | 26.83 | 9.68 |
November | 0.924419E+09 | 3266.39 | 07-NOV-14:00 | 22.00 | 7.34 | 0.571241E+09 | 1058.11 | 25-NOV-15:09 | 13.50 | 4.91 |
December | 0.414519E+09 | 4933.90 | 18-DEC-20:33 | -11.7 | -12.0 | 0.571898E+09 | 1123.87 | 02-DEC-15:30 | -11.7 | -12.0 |
Annual Sum or Average | 0.253287E+11 | 0.767487E+10 | ||||||||
Minimum of Months | 0.383873E+09 | 2873.88 | -11.7 | -12.0 | 0.512039E+09 | 1058.11 | -11.7 | -12.0 | ||
Maximum of Months | 0.496765E+10 | 15858.63 | 28.67 | 14.21 | 0.739938E+09 | 1123.96 | 28.67 | 17.56 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.383610E+09 | 3353.29 | 03-JAN-18:23 | -3.5 | -3.5 | 0.568014E+09 | 1097.22 | 21-JAN-15:20 | 13.67 | 5.40 |
February | 0.272076E+09 | 2780.51 | 15-FEB-19:33 | -0.3 | -1.1 | 0.509557E+09 | 1123.86 | 18-FEB-15:00 | 18.00 | 7.48 |
March | 0.610585E+09 | 3380.69 | 27-MAR-17:33 | -3.7 | -3.7 | 0.614139E+09 | 1123.84 | 11-MAR-15:20 | -3.7 | -3.7 |
April | 0.394512E+09 | 2802.03 | 22-APR-08:62 | 0.00 | -0.1 | 0.591705E+09 | 1123.86 | 08-APR-14:20 | 0.00 | -0.1 |
May | 0.139942E+10 | 3826.06 | 17-MAY-14:10 | 28.67 | 11.73 | 0.699344E+09 | 1123.87 | 06-MAY-14:39 | 28.67 | 11.73 |
June | 0.430891E+10 | 14578.68 | 25-JUN-08:62 | 28.08 | 13.27 | 0.714886E+09 | 1123.91 | 17-JUN-14:00 | 28.08 | 13.27 |
July | 0.455904E+10 | 15652.65 | 18-JUL-07:02 | 24.33 | 12.85 | 0.719262E+09 | 1123.96 | 29-JUL-14:20 | 23.00 | 17.56 |
August | 0.482554E+10 | 11372.62 | 20-AUG-08:62 | 23.50 | 14.21 | 0.739923E+09 | 1123.94 | 05-AUG-14:39 | 23.50 | 14.21 |
September | 0.399731E+10 | 12169.47 | 11-SEP-07:03 | 20.63 | 10.22 | 0.699626E+09 | 1123.87 | 02-SEP-14:50 | 20.63 | 10.22 |
October | 0.164043E+10 | 5380.22 | 11-OCT-14:10 | 26.83 | 9.68 | 0.649237E+09 | 1123.87 | 07-OCT-14:20 | 26.83 | 9.68 |
November | 0.773118E+09 | 3257.97 | 21-NOV-19:03 | -3.0 | -3.0 | 0.566900E+09 | 1034.43 | 25-NOV-15:09 | 13.50 | 4.91 |
December | 0.307414E+09 | 2435.70 | 30-DEC-18:35 | 1.00 | 0.07 | 0.569172E+09 | 1123.87 | 02-DEC-15:30 | 1.00 | 0.07 |
Annual Sum or Average | 0.234720E+11 | 0.764177E+10 | ||||||||
Minimum of Months | 0.272076E+09 | 2435.70 | -3.7 | -3.7 | 0.509557E+09 | 1034.43 | -3.7 | -3.7 | ||
Maximum of Months | 0.482554E+10 | 15652.65 | 28.67 | 14.21 | 0.739923E+09 | 1123.96 | 28.67 | 17.56 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.231743E+09 | 2738.30 | 27-JAN-19:03 | 4.00 | 3.02 | 0.555039E+09 | 997.42 | 20-JAN-13:00 | 4.00 | 3.02 |
February | 0.154410E+09 | 1681.00 | 25-FEB-11:20 | 10.33 | 3.43 | 0.501538E+09 | 1121.89 | 18-FEB-15:09 | 10.33 | 3.43 |
March | 0.481992E+09 | 2828.80 | 14-MAR-13:00 | 24.00 | 7.90 | 0.599674E+09 | 1123.85 | 11-MAR-15:09 | 24.00 | 7.90 |
April | 0.369624E+09 | 2141.21 | 21-APR-19:00 | 8.00 | 4.94 | 0.572098E+09 | 1047.43 | 08-APR-14:00 | 8.00 | 4.94 |
May | 0.127667E+10 | 3766.24 | 17-MAY-14:10 | 28.67 | 11.73 | 0.673078E+09 | 1123.87 | 06-MAY-14:09 | 28.67 | 11.73 |
June | 0.444918E+10 | 15230.51 | 25-JUN-08:62 | 28.08 | 13.27 | 0.714518E+09 | 1123.94 | 17-JUN-14:00 | 28.08 | 13.27 |
July | 0.469820E+10 | 15398.57 | 16-JUL-08:62 | 30.50 | 14.31 | 0.718983E+09 | 1123.95 | 15-JUL-14:20 | 30.50 | 14.31 |
August | 0.509596E+10 | 8253.04 | 20-AUG-08:62 | 23.50 | 14.21 | 0.739684E+09 | 1123.95 | 05-AUG-14:39 | 23.50 | 14.21 |
September | 0.415081E+10 | 7837.46 | 11-SEP-07:03 | 20.63 | 10.22 | 0.696330E+09 | 1123.90 | 09-SEP-14:09 | 20.63 | 10.22 |
October | 0.156055E+10 | 5412.34 | 11-OCT-14:10 | 26.83 | 9.68 | 0.630690E+09 | 1123.87 | 07-OCT-14:09 | 26.83 | 9.68 |
November | 0.624573E+09 | 2602.21 | 07-NOV-14:00 | 22.00 | 7.34 | 0.552279E+09 | 997.43 | 09-NOV-13:00 | 20.00 | 8.60 |
December | 0.213541E+09 | 2815.65 | 18-DEC-10:23 | 3.50 | -0.7 | 0.559002E+09 | 1123.87 | 02-DEC-15:20 | 3.50 | -0.7 |
Annual Sum or Average | 0.233073E+11 | 0.751291E+10 | ||||||||
Minimum of Months | 0.154410E+09 | 1681.00 | 3.50 | -0.7 | 0.501538E+09 | 997.42 | 3.50 | -0.7 | ||
Maximum of Months | 0.509596E+10 | 15398.57 | 30.50 | 14.31 | 0.739684E+09 | 1123.95 | 30.50 | 14.31 |
Report: ZoneHeatingSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.207056E+10 | 58882.97 | 05-JAN-08:61 | -17.0 |
February | 0.290498E+10 | 58879.21 | 12-FEB-08:61 | -16.5 |
March | 0.208759E+10 | 58861.26 | 29-MAR-07:01 | -5.5 |
April | 0.139042E+10 | 58855.82 | 17-APR-07:01 | -5.5 |
May | 0.161908E+09 | 58828.96 | 03-MAY-07:01 | 4.33 |
June | 19032668.79 | 1722.33 | 14-JUN-07:05 | 28.30 |
July | 20627784.54 | 1835.60 | 18-JUL-07:04 | 24.33 |
August | 20278750.51 | 1682.70 | 03-AUG-07:05 | 21.33 |
September | 32584658.89 | 11424.55 | 22-SEP-07:02 | 0.37 |
October | 0.103237E+10 | 58869.25 | 31-OCT-07:01 | -9.0 |
November | 0.122544E+10 | 58867.96 | 29-NOV-08:61 | -9.8 |
December | 0.372452E+10 | 58888.31 | 22-DEC-08:61 | -20.0 |
Annual Sum or Average | 0.146903E+11 | |||
Minimum of Months | 19032668.79 | 1682.70 | -20.0 | |
Maximum of Months | 0.372452E+10 | 58888.31 | 28.30 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.512498E+09 | 31203.56 | 05-JAN-08:61 | -17.0 |
February | 0.800274E+09 | 31204.28 | 12-FEB-08:61 | -16.5 |
March | 0.487286E+09 | 31197.54 | 29-MAR-07:01 | -5.5 |
April | 0.294199E+09 | 31191.95 | 17-APR-07:01 | -5.5 |
May | 44082919.54 | 20452.71 | 03-MAY-07:01 | 4.33 |
June | 12307316.20 | 1014.93 | 14-JUN-07:05 | 28.30 |
July | 15123818.94 | 1080.92 | 18-JUL-07:04 | 24.33 |
August | 14460260.10 | 1022.10 | 03-AUG-07:05 | 21.33 |
September | 15310455.53 | 1007.72 | 13-SEP-07:05 | 20.18 |
October | 0.303659E+09 | 31198.99 | 31-OCT-07:01 | -9.0 |
November | 0.318297E+09 | 31198.16 | 29-NOV-08:61 | -9.8 |
December | 0.112014E+10 | 31212.22 | 22-DEC-08:61 | -20.0 |
Annual Sum or Average | 0.393763E+10 | |||
Minimum of Months | 12307316.20 | 1007.72 | -20.0 | |
Maximum of Months | 0.112014E+10 | 31212.22 | 28.30 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.720555E+09 | 32231.95 | 15-JAN-08:61 | -9.3 |
February | 0.102201E+10 | 32248.18 | 12-FEB-08:61 | -16.5 |
March | 0.652153E+09 | 32221.01 | 19-MAR-07:01 | -15.2 |
April | 0.436312E+09 | 32218.10 | 17-APR-06:01 | -7.7 |
May | 58557683.09 | 20786.93 | 02-MAY-06:02 | 0.17 |
June | 53763469.53 | 2477.78 | 26-JUN-19:02 | 35.03 |
July | 68941633.73 | 2327.31 | 16-JUL-16:02 | 34.33 |
August | 42002557.12 | 1648.04 | 26-AUG-17:02 | 30.83 |
September | 31407763.65 | 1791.40 | 10-SEP-16:02 | 31.92 |
October | 0.383024E+09 | 32065.57 | 31-OCT-06:01 | -9.0 |
November | 0.436066E+09 | 32205.09 | 30-NOV-07:01 | -11.3 |
December | 0.138870E+10 | 32246.20 | 24-DEC-08:61 | -15.7 |
Annual Sum or Average | 0.529349E+10 | |||
Minimum of Months | 31407763.65 | 1648.04 | -16.5 | |
Maximum of Months | 0.138870E+10 | 32248.18 | 35.03 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.813964E+09 | 32101.97 | 15-JAN-08:61 | -9.3 |
February | 0.111268E+10 | 32118.05 | 12-FEB-08:61 | -16.5 |
March | 0.724525E+09 | 32091.25 | 19-MAR-07:01 | -15.2 |
April | 0.501442E+09 | 32088.81 | 17-APR-06:01 | -7.7 |
May | 68126658.63 | 25492.58 | 02-MAY-06:02 | 0.17 |
June | 53597395.20 | 2475.78 | 26-JUN-19:02 | 35.03 |
July | 68526596.71 | 2325.56 | 16-JUL-16:02 | 34.33 |
August | 41902126.80 | 1647.17 | 26-AUG-17:02 | 30.83 |
September | 31677005.11 | 1790.14 | 10-SEP-16:02 | 31.92 |
October | 0.419452E+09 | 31937.33 | 31-OCT-06:01 | -9.0 |
November | 0.494515E+09 | 32075.29 | 30-NOV-07:01 | -11.3 |
December | 0.149771E+10 | 32116.19 | 24-DEC-08:61 | -15.7 |
Annual Sum or Average | 0.582812E+10 | |||
Minimum of Months | 31677005.11 | 1647.17 | -16.5 | |
Maximum of Months | 0.149771E+10 | 32118.05 | 35.03 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.960954E+09 | 32049.79 | 15-JAN-08:61 | -9.3 |
February | 0.127661E+10 | 32065.69 | 12-FEB-08:61 | -16.5 |
March | 0.860977E+09 | 32038.99 | 19-MAR-07:01 | -15.2 |
April | 0.604517E+09 | 32037.02 | 17-APR-06:01 | -7.7 |
May | 81927963.29 | 30116.06 | 02-MAY-06:02 | 0.17 |
June | 53611394.75 | 2481.34 | 26-JUN-19:02 | 35.03 |
July | 68873008.73 | 2330.49 | 16-JUL-16:02 | 34.33 |
August | 41740031.19 | 1653.40 | 26-AUG-17:02 | 30.83 |
September | 32990472.14 | 1795.91 | 10-SEP-16:02 | 31.92 |
October | 0.477821E+09 | 31886.04 | 31-OCT-06:01 | -9.0 |
November | 0.582772E+09 | 32023.27 | 30-NOV-07:01 | -11.3 |
December | 0.168605E+10 | 32063.87 | 24-DEC-08:61 | -15.7 |
Annual Sum or Average | 0.672884E+10 | |||
Minimum of Months | 32990472.14 | 1653.40 | -16.5 | |
Maximum of Months | 0.168605E+10 | 32065.69 | 35.03 |
Report: ZoneHeatingSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.207327E+10 | 56734.27 | 05-JAN-08:61 | -17.0 |
February | 0.267295E+10 | 56732.60 | 06-FEB-08:61 | -7.5 |
March | 0.184239E+10 | 56725.10 | 29-MAR-07:01 | -5.5 |
April | 0.133003E+10 | 56724.12 | 17-APR-07:01 | -5.5 |
May | 0.164543E+09 | 56694.46 | 03-MAY-07:01 | 4.33 |
June | 58794443.43 | 3911.68 | 25-JUN-16:02 | 32.70 |
July | 89792681.65 | 4627.15 | 16-JUL-16:02 | 34.33 |
August | 47380103.08 | 3267.60 | 26-AUG-17:02 | 30.83 |
September | 59108982.64 | 3580.38 | 10-SEP-16:02 | 31.92 |
October | 0.101340E+10 | 56729.46 | 30-OCT-07:01 | -10.0 |
November | 0.123734E+10 | 56726.02 | 29-NOV-08:61 | -9.8 |
December | 0.347677E+10 | 56743.14 | 22-DEC-08:61 | -20.0 |
Annual Sum or Average | 0.140658E+11 | |||
Minimum of Months | 47380103.08 | 3267.60 | -20.0 | |
Maximum of Months | 0.347677E+10 | 56743.14 | 34.33 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.122506E+10 | 29085.54 | 05-JAN-08:61 | -17.0 |
February | 0.153912E+10 | 29084.84 | 06-FEB-08:61 | -7.5 |
March | 0.109381E+10 | 29080.42 | 29-MAR-07:01 | -5.5 |
April | 0.809580E+09 | 29079.61 | 17-APR-07:01 | -5.5 |
May | 0.159637E+09 | 29062.67 | 03-MAY-07:01 | 4.33 |
June | 46384578.76 | 2579.02 | 25-JUN-16:12 | 32.70 |
July | 68459933.23 | 2891.70 | 16-JUL-16:02 | 34.33 |
August | 36365720.11 | 2231.01 | 26-AUG-17:02 | 30.83 |
September | 56434381.35 | 2369.81 | 10-SEP-16:12 | 31.63 |
October | 0.611404E+09 | 29082.17 | 30-OCT-07:01 | -10.0 |
November | 0.742752E+09 | 29080.31 | 29-NOV-08:61 | -9.8 |
December | 0.197819E+10 | 29091.11 | 22-DEC-08:61 | -20.0 |
Annual Sum or Average | 0.836719E+10 | |||
Minimum of Months | 36365720.11 | 2231.01 | -20.0 | |
Maximum of Months | 0.197819E+10 | 29091.11 | 34.33 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.129074E+10 | 28938.56 | 05-JAN-08:61 | -17.0 |
February | 0.159331E+10 | 28938.23 | 06-FEB-08:61 | -7.5 |
March | 0.114824E+10 | 28933.64 | 29-MAR-07:01 | -5.5 |
April | 0.850518E+09 | 28932.88 | 17-APR-07:01 | -5.5 |
May | 0.166985E+09 | 28915.67 | 03-MAY-07:01 | 4.33 |
June | 46814929.06 | 2573.34 | 25-JUN-16:12 | 32.70 |
July | 67940612.59 | 2888.95 | 16-JUL-16:02 | 34.33 |
August | 35866010.64 | 2228.52 | 26-AUG-17:02 | 30.83 |
September | 57089244.66 | 2363.47 | 10-SEP-16:12 | 31.63 |
October | 0.627488E+09 | 28935.12 | 30-OCT-07:01 | -10.0 |
November | 0.775899E+09 | 28933.34 | 29-NOV-08:61 | -9.8 |
December | 0.203418E+10 | 28944.36 | 22-DEC-08:61 | -20.0 |
Annual Sum or Average | 0.869506E+10 | |||
Minimum of Months | 35866010.64 | 2228.52 | -20.0 | |
Maximum of Months | 0.203418E+10 | 28944.36 | 34.33 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.158264E+10 | 28792.98 | 05-JAN-08:61 | -17.0 |
February | 0.187356E+10 | 28788.50 | 06-FEB-08:61 | -7.5 |
March | 0.139658E+10 | 28787.90 | 29-MAR-07:01 | -5.5 |
April | 0.107348E+10 | 28786.28 | 17-APR-07:01 | -5.5 |
May | 0.201968E+09 | 28771.49 | 03-MAY-07:01 | 4.33 |
June | 49598025.14 | 2570.19 | 25-JUN-16:12 | 32.70 |
July | 66126931.07 | 2887.19 | 16-JUL-16:02 | 34.33 |
August | 34422291.66 | 2227.20 | 26-AUG-17:02 | 30.83 |
September | 60733215.02 | 2360.55 | 10-SEP-16:12 | 31.63 |
October | 0.726104E+09 | 28790.04 | 30-OCT-07:01 | -10.0 |
November | 0.947207E+09 | 28788.06 | 29-NOV-08:61 | -9.8 |
December | 0.232244E+10 | 28963.37 | 23-DEC-08:12 | -17.3 |
Annual Sum or Average | 0.103349E+11 | |||
Minimum of Months | 34422291.66 | 2227.20 | -17.3 | |
Maximum of Months | 0.232244E+10 | 28963.37 | 34.33 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.299046E+10 | 29969.44 | 05-JAN-08:13 | -17.0 |
February | 0.346017E+10 | 30048.32 | 06-FEB-08:13 | -7.0 |
March | 0.264942E+10 | 29875.36 | 19-MAR-08:61 | -13.0 |
April | 0.210189E+10 | 29848.99 | 17-APR-07:01 | -5.5 |
May | 0.260189E+09 | 29781.78 | 03-MAY-07:01 | 4.33 |
June | 38653260.07 | 1973.00 | 25-JUN-16:02 | 32.70 |
July | 49064968.80 | 2318.98 | 16-JUL-16:02 | 34.33 |
August | 26010255.65 | 1654.71 | 26-AUG-17:02 | 30.83 |
September | 48946573.01 | 22019.15 | 22-SEP-07:02 | 0.37 |
October | 0.118700E+10 | 29807.86 | 31-OCT-07:01 | -9.0 |
November | 0.172565E+10 | 29806.94 | 29-NOV-08:61 | -9.8 |
December | 0.404109E+10 | 30180.71 | 23-DEC-08:12 | -17.3 |
Annual Sum or Average | 0.185785E+11 | |||
Minimum of Months | 26010255.65 | 1654.71 | -17.3 | |
Maximum of Months | 0.404109E+10 | 30180.71 | 34.33 |
Report: ZoneElectricSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.739462E+10 | 4621.63 | 01-JAN-10:09 | 0.222596E+10 | 1343.25 | 01-JAN-10:09 |
February | 0.668410E+10 | 4621.63 | 01-FEB-10:09 | 0.201408E+10 | 1343.25 | 01-FEB-10:09 |
March | 0.740180E+10 | 4621.63 | 01-MAR-10:09 | 0.223295E+10 | 1343.25 | 01-MAR-10:09 |
April | 0.716384E+10 | 4621.63 | 01-APR-09:09 | 0.215748E+10 | 1343.25 | 01-APR-09:09 |
May | 0.739462E+10 | 4621.63 | 01-MAY-09:09 | 0.222596E+10 | 1343.25 | 01-MAY-09:09 |
June | 0.716485E+10 | 4621.63 | 01-JUN-09:09 | 0.216232E+10 | 1343.25 | 01-JUN-09:09 |
July | 0.740069E+10 | 4621.63 | 01-JUL-09:09 | 0.222811E+10 | 1343.25 | 01-JUL-09:09 |
August | 0.739513E+10 | 4621.63 | 01-AUG-09:09 | 0.222838E+10 | 1343.25 | 01-AUG-09:09 |
September | 0.717041E+10 | 4621.63 | 01-SEP-09:09 | 0.216205E+10 | 1343.25 | 01-SEP-09:09 |
October | 0.739462E+10 | 4621.63 | 01-OCT-09:09 | 0.222596E+10 | 1343.25 | 01-OCT-09:09 |
November | 0.714323E+10 | 4621.63 | 01-NOV-09:09 | 0.215077E+10 | 1343.25 | 01-NOV-09:09 |
December | 0.740776E+10 | 4621.63 | 01-DEC-10:09 | 0.223509E+10 | 1343.25 | 01-DEC-10:09 |
Annual Sum or Average | 0.871157E+11 | 0.262491E+11 | ||||
Minimum of Months | 0.668410E+10 | 4621.63 | 0.201408E+10 | 1343.25 | ||
Maximum of Months | 0.740776E+10 | 4621.63 | 0.223509E+10 | 1343.25 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.451584E+10 | 2827.07 | 01-JAN-10:09 | 0.111298E+10 | 671.63 | 01-JAN-10:09 |
February | 0.408193E+10 | 2827.07 | 01-FEB-10:09 | 0.100704E+10 | 671.63 | 01-FEB-10:09 |
March | 0.452026E+10 | 2827.07 | 01-MAR-10:09 | 0.111647E+10 | 671.63 | 01-MAR-10:09 |
April | 0.437489E+10 | 2827.07 | 01-APR-09:09 | 0.107874E+10 | 671.63 | 01-APR-09:09 |
May | 0.451584E+10 | 2827.07 | 01-MAY-09:09 | 0.111298E+10 | 671.63 | 01-MAY-09:09 |
June | 0.437556E+10 | 2827.07 | 01-JUN-09:09 | 0.108116E+10 | 671.63 | 01-JUN-09:09 |
July | 0.451952E+10 | 2827.07 | 01-JUL-09:09 | 0.111405E+10 | 671.63 | 01-JUL-09:09 |
August | 0.451617E+10 | 2827.07 | 01-AUG-09:09 | 0.111419E+10 | 671.63 | 01-AUG-09:09 |
September | 0.437891E+10 | 2827.07 | 01-SEP-09:09 | 0.108102E+10 | 671.63 | 01-SEP-09:09 |
October | 0.451584E+10 | 2827.07 | 01-OCT-09:09 | 0.111298E+10 | 671.63 | 01-OCT-09:09 |
November | 0.436230E+10 | 2827.07 | 01-NOV-09:09 | 0.107538E+10 | 671.63 | 01-NOV-09:09 |
December | 0.452388E+10 | 2827.07 | 01-DEC-10:09 | 0.111755E+10 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.532009E+11 | 0.131245E+11 | ||||
Minimum of Months | 0.408193E+10 | 2827.07 | 0.100704E+10 | 671.63 | ||
Maximum of Months | 0.452388E+10 | 2827.07 | 0.111755E+10 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.317044E+10 | 2555.22 | 01-JAN-10:09 | 0.879849E+09 | 671.63 | 01-JAN-10:09 |
February | 0.287181E+10 | 2555.22 | 01-FEB-09:09 | 0.796766E+09 | 671.63 | 01-FEB-09:09 |
March | 0.324295E+10 | 2555.22 | 01-MAR-09:09 | 0.898128E+09 | 671.63 | 01-MAR-09:09 |
April | 0.307694E+10 | 2555.22 | 01-APR-08:09 | 0.853677E+09 | 671.63 | 01-APR-08:09 |
May | 0.320669E+10 | 2555.22 | 01-MAY-08:09 | 0.888989E+09 | 671.63 | 01-MAY-08:09 |
June | 0.313132E+10 | 2555.22 | 01-JUN-08:09 | 0.867387E+09 | 671.63 | 01-JUN-08:09 |
July | 0.315231E+10 | 2555.22 | 01-JUL-08:09 | 0.875279E+09 | 671.63 | 01-JUL-08:09 |
August | 0.324295E+10 | 2555.22 | 01-AUG-08:09 | 0.898128E+09 | 671.63 | 01-AUG-08:09 |
September | 0.307694E+10 | 2555.22 | 01-SEP-08:09 | 0.853677E+09 | 671.63 | 01-SEP-08:09 |
October | 0.317044E+10 | 2555.22 | 01-OCT-09:09 | 0.879849E+09 | 671.63 | 01-OCT-09:09 |
November | 0.307694E+10 | 2555.22 | 01-NOV-08:09 | 0.853679E+09 | 671.63 | 01-NOV-08:09 |
December | 0.315231E+10 | 2555.22 | 01-DEC-09:09 | 0.875279E+09 | 671.63 | 01-DEC-09:09 |
Annual Sum or Average | 0.375720E+11 | 0.104207E+11 | ||||
Minimum of Months | 0.287181E+10 | 2555.22 | 0.796766E+09 | 671.63 | ||
Maximum of Months | 0.324295E+10 | 2555.22 | 0.898128E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.317044E+10 | 2555.22 | 01-JAN-10:09 | 0.879849E+09 | 671.63 | 01-JAN-10:09 |
February | 0.287181E+10 | 2555.22 | 01-FEB-09:09 | 0.796766E+09 | 671.63 | 01-FEB-09:09 |
March | 0.324295E+10 | 2555.22 | 01-MAR-09:09 | 0.898128E+09 | 671.63 | 01-MAR-09:09 |
April | 0.307694E+10 | 2555.22 | 01-APR-08:09 | 0.853677E+09 | 671.63 | 01-APR-08:09 |
May | 0.320669E+10 | 2555.22 | 01-MAY-08:09 | 0.888989E+09 | 671.63 | 01-MAY-08:09 |
June | 0.313132E+10 | 2555.22 | 01-JUN-08:09 | 0.867387E+09 | 671.63 | 01-JUN-08:09 |
July | 0.315231E+10 | 2555.22 | 01-JUL-08:09 | 0.875279E+09 | 671.63 | 01-JUL-08:09 |
August | 0.324295E+10 | 2555.22 | 01-AUG-08:09 | 0.898128E+09 | 671.63 | 01-AUG-08:09 |
September | 0.307694E+10 | 2555.22 | 01-SEP-08:09 | 0.853677E+09 | 671.63 | 01-SEP-08:09 |
October | 0.317044E+10 | 2555.22 | 01-OCT-09:09 | 0.879849E+09 | 671.63 | 01-OCT-09:09 |
November | 0.307694E+10 | 2555.22 | 01-NOV-08:09 | 0.853679E+09 | 671.63 | 01-NOV-08:09 |
December | 0.315231E+10 | 2555.22 | 01-DEC-09:09 | 0.875279E+09 | 671.63 | 01-DEC-09:09 |
Annual Sum or Average | 0.375720E+11 | 0.104207E+11 | ||||
Minimum of Months | 0.287181E+10 | 2555.22 | 0.796766E+09 | 671.63 | ||
Maximum of Months | 0.324295E+10 | 2555.22 | 0.898128E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.317044E+10 | 2555.22 | 01-JAN-10:09 | 0.879849E+09 | 671.63 | 01-JAN-10:09 |
February | 0.287181E+10 | 2555.22 | 01-FEB-09:09 | 0.796766E+09 | 671.63 | 01-FEB-09:09 |
March | 0.324295E+10 | 2555.22 | 01-MAR-09:09 | 0.898128E+09 | 671.63 | 01-MAR-09:09 |
April | 0.307694E+10 | 2555.22 | 01-APR-08:09 | 0.853677E+09 | 671.63 | 01-APR-08:09 |
May | 0.320669E+10 | 2555.22 | 01-MAY-08:09 | 0.888989E+09 | 671.63 | 01-MAY-08:09 |
June | 0.313132E+10 | 2555.22 | 01-JUN-08:09 | 0.867387E+09 | 671.63 | 01-JUN-08:09 |
July | 0.315231E+10 | 2555.22 | 01-JUL-08:09 | 0.875279E+09 | 671.63 | 01-JUL-08:09 |
August | 0.324295E+10 | 2555.22 | 01-AUG-08:09 | 0.898128E+09 | 671.63 | 01-AUG-08:09 |
September | 0.307694E+10 | 2555.22 | 01-SEP-08:09 | 0.853677E+09 | 671.63 | 01-SEP-08:09 |
October | 0.317044E+10 | 2555.22 | 01-OCT-09:09 | 0.879849E+09 | 671.63 | 01-OCT-09:09 |
November | 0.307694E+10 | 2555.22 | 01-NOV-08:09 | 0.853679E+09 | 671.63 | 01-NOV-08:09 |
December | 0.315231E+10 | 2555.22 | 01-DEC-09:09 | 0.875279E+09 | 671.63 | 01-DEC-09:09 |
Annual Sum or Average | 0.375720E+11 | 0.104207E+11 | ||||
Minimum of Months | 0.287181E+10 | 2555.22 | 0.796766E+09 | 671.63 | ||
Maximum of Months | 0.324295E+10 | 2555.22 | 0.898128E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.313454E+10 | 2726.96 | 01-JAN-11:09 | 0.161799E+10 | 1343.25 | 01-JAN-11:09 |
February | 0.283982E+10 | 2726.96 | 01-FEB-10:09 | 0.146554E+10 | 1343.25 | 01-FEB-10:09 |
March | 0.321092E+10 | 2726.96 | 01-MAR-10:09 | 0.165455E+10 | 1343.25 | 01-MAR-10:09 |
April | 0.304266E+10 | 2726.96 | 01-APR-09:09 | 0.157022E+10 | 1343.25 | 01-APR-09:09 |
May | 0.317273E+10 | 2726.96 | 01-MAY-09:09 | 0.163627E+10 | 1343.25 | 01-MAY-09:09 |
June | 0.309995E+10 | 2726.96 | 01-JUN-09:09 | 0.159764E+10 | 1343.25 | 01-JUN-09:09 |
July | 0.311545E+10 | 2726.96 | 01-JUL-09:09 | 0.160885E+10 | 1343.25 | 01-JUL-09:09 |
August | 0.321092E+10 | 2726.96 | 01-AUG-09:09 | 0.165455E+10 | 1343.25 | 01-AUG-09:09 |
September | 0.304266E+10 | 2726.96 | 01-SEP-09:09 | 0.157022E+10 | 1343.25 | 01-SEP-09:09 |
October | 0.313454E+10 | 2726.96 | 01-OCT-10:09 | 0.161799E+10 | 1343.25 | 01-OCT-10:09 |
November | 0.304266E+10 | 2726.96 | 01-NOV-09:09 | 0.157022E+10 | 1343.25 | 01-NOV-09:09 |
December | 0.311545E+10 | 2726.96 | 01-DEC-10:09 | 0.160885E+10 | 1343.25 | 01-DEC-10:09 |
Annual Sum or Average | 0.371623E+11 | 0.191729E+11 | ||||
Minimum of Months | 0.283982E+10 | 2726.96 | 0.146554E+10 | 1343.25 | ||
Maximum of Months | 0.321092E+10 | 2726.96 | 0.165455E+10 | 1343.25 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.161274E+10 | 1404.46 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.146111E+10 | 1404.46 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.165211E+10 | 1404.46 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.156548E+10 | 1404.46 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.163243E+10 | 1404.46 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.159501E+10 | 1404.46 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.160290E+10 | 1404.46 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.165211E+10 | 1404.46 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.156548E+10 | 1404.46 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.161274E+10 | 1404.46 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.156548E+10 | 1404.46 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.160290E+10 | 1404.46 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.191205E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.146111E+10 | 1404.46 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.165211E+10 | 1404.46 | 0.827277E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.161274E+10 | 1404.46 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.146111E+10 | 1404.46 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.165211E+10 | 1404.46 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.156548E+10 | 1404.46 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.163243E+10 | 1404.46 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.159501E+10 | 1404.46 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.160290E+10 | 1404.46 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.165211E+10 | 1404.46 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.156548E+10 | 1404.46 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.161274E+10 | 1404.46 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.156548E+10 | 1404.46 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.160290E+10 | 1404.46 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.191205E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.146111E+10 | 1404.46 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.165211E+10 | 1404.46 | 0.827277E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.161274E+10 | 1404.46 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.146111E+10 | 1404.46 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.165211E+10 | 1404.46 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.156548E+10 | 1404.46 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.163243E+10 | 1404.46 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.159501E+10 | 1404.46 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.160290E+10 | 1404.46 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.165211E+10 | 1404.46 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.156548E+10 | 1404.46 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.161274E+10 | 1404.46 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.156548E+10 | 1404.46 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.160290E+10 | 1404.46 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.191205E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.146111E+10 | 1404.46 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.165211E+10 | 1404.46 | 0.827277E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.161274E+10 | 1404.46 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.146111E+10 | 1404.46 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.165211E+10 | 1404.46 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.156548E+10 | 1404.46 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.163243E+10 | 1404.46 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.159501E+10 | 1404.46 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.160290E+10 | 1404.46 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.165211E+10 | 1404.46 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.156548E+10 | 1404.46 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.161274E+10 | 1404.46 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.156548E+10 | 1404.46 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.160290E+10 | 1404.46 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.191205E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.146111E+10 | 1404.46 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.165211E+10 | 1404.46 | 0.827277E+09 | 671.63 |
Report: SpaceGainsMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.338624E+10 | 0.739462E+10 | 0.222596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.379978E+10 |
February | 0.305697E+10 | 0.668410E+10 | 0.201408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.404239E+10 |
March | 0.335708E+10 | 0.740180E+10 | 0.223295E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14988.76 | 0.358383E+10 |
April | 0.327081E+10 | 0.716384E+10 | 0.215748E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.328639E+10 |
May | 0.336680E+10 | 0.739462E+10 | 0.222596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 62243848.68 | 0.153286E+10 |
June | 0.325380E+10 | 0.716485E+10 | 0.216232E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.858791E+09 | 0.360740E+09 |
July | 0.339353E+10 | 0.740069E+10 | 0.222811E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.913764E+09 | 0.362579E+09 |
August | 0.334857E+10 | 0.739513E+10 | 0.222838E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.778289E+09 | 0.407471E+09 |
September | 0.327932E+10 | 0.717041E+10 | 0.216205E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.424057E+09 | 0.765510E+09 |
October | 0.338624E+10 | 0.739462E+10 | 0.222596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11031803.90 | 0.293722E+10 |
November | 0.327446E+10 | 0.714323E+10 | 0.215077E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.349578E+10 |
December | 0.340325E+10 | 0.740776E+10 | 0.223509E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.502650E+10 |
Annual Sum or Average | 0.397770E+11 | 0.871157E+11 | 0.262491E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.304819E+10 | 0.296010E+11 |
Minimum of Months | 0.305697E+10 | 0.668410E+10 | 0.201408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.360740E+09 |
Maximum of Months | 0.340325E+10 | 0.740776E+10 | 0.223509E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.913764E+09 | 0.502650E+10 |
Report: SpaceGainsMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.169307E+10 | 0.451584E+10 | 0.111298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.197916E+10 |
February | 0.152844E+10 | 0.408193E+10 | 0.100704E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.201968E+10 |
March | 0.167849E+10 | 0.452026E+10 | 0.111647E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8231.24 | 0.173840E+10 |
April | 0.163536E+10 | 0.437489E+10 | 0.107874E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158446E+10 |
May | 0.168335E+10 | 0.451584E+10 | 0.111298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33847372.54 | 0.720512E+09 |
June | 0.162685E+10 | 0.437556E+10 | 0.108116E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.463462E+09 | 0.130962E+09 |
July | 0.169671E+10 | 0.451952E+10 | 0.111405E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.493068E+09 | 0.132984E+09 |
August | 0.167424E+10 | 0.451617E+10 | 0.111419E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.422702E+09 | 0.155400E+09 |
September | 0.163961E+10 | 0.437891E+10 | 0.108102E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.231136E+09 | 0.318666E+09 |
October | 0.169307E+10 | 0.451584E+10 | 0.111298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6027890.46 | 0.144550E+10 |
November | 0.163718E+10 | 0.436230E+10 | 0.107538E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.177765E+10 |
December | 0.170157E+10 | 0.452388E+10 | 0.111755E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.246054E+10 |
Annual Sum or Average | 0.198880E+11 | 0.532009E+11 | 0.131245E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165025E+10 | 0.144639E+11 |
Minimum of Months | 0.152844E+10 | 0.408193E+10 | 0.100704E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130962E+09 |
Maximum of Months | 0.170157E+10 | 0.452388E+10 | 0.111755E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.493068E+09 | 0.246054E+10 |
Report: SpaceGainsMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.317044E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.200317E+10 |
February | 0.914877E+09 | 0.287181E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.207078E+10 |
March | 0.103395E+10 | 0.324295E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8231.24 | 0.178447E+10 |
April | 0.984131E+09 | 0.307694E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163827E+10 |
May | 0.102058E+10 | 0.320669E+10 | 0.888989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 33842605.25 | 0.750061E+09 |
June | 0.998711E+09 | 0.313132E+10 | 0.867387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.457823E+09 | 0.153424E+09 |
July | 0.100600E+10 | 0.315231E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.483521E+09 | 0.152343E+09 |
August | 0.103395E+10 | 0.324295E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.418900E+09 | 0.175974E+09 |
September | 0.984131E+09 | 0.307694E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.225121E+09 | 0.346341E+09 |
October | 0.100722E+10 | 0.317044E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6027890.46 | 0.148915E+10 |
November | 0.973196E+09 | 0.307694E+10 | 0.853679E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179992E+10 |
December | 0.100600E+10 | 0.315231E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.253517E+10 |
Annual Sum or Average | 0.119700E+11 | 0.375720E+11 | 0.104207E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162524E+10 | 0.148991E+11 |
Minimum of Months | 0.914877E+09 | 0.287181E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.152343E+09 |
Maximum of Months | 0.103395E+10 | 0.324295E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.483521E+09 | 0.253517E+10 |
Report: SpaceGainsMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.317044E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.199672E+10 |
February | 0.914877E+09 | 0.287181E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.206536E+10 |
March | 0.103395E+10 | 0.324295E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8231.24 | 0.177811E+10 |
April | 0.984131E+09 | 0.307694E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162940E+10 |
May | 0.102058E+10 | 0.320669E+10 | 0.888989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 33842651.42 | 0.744715E+09 |
June | 0.998711E+09 | 0.313132E+10 | 0.867387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.457799E+09 | 0.153559E+09 |
July | 0.100600E+10 | 0.315231E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.483441E+09 | 0.152724E+09 |
August | 0.103395E+10 | 0.324295E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.418892E+09 | 0.176200E+09 |
September | 0.984131E+09 | 0.307694E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.225098E+09 | 0.345879E+09 |
October | 0.100722E+10 | 0.317044E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6027890.46 | 0.148430E+10 |
November | 0.973196E+09 | 0.307694E+10 | 0.853679E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179328E+10 |
December | 0.100600E+10 | 0.315231E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.252795E+10 |
Annual Sum or Average | 0.119700E+11 | 0.375720E+11 | 0.104207E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162511E+10 | 0.148482E+11 |
Minimum of Months | 0.914877E+09 | 0.287181E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.152724E+09 |
Maximum of Months | 0.103395E+10 | 0.324295E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.483441E+09 | 0.252795E+10 |
Report: SpaceGainsMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.317044E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.198867E+10 |
February | 0.914877E+09 | 0.287181E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205979E+10 |
March | 0.103395E+10 | 0.324295E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8231.24 | 0.176981E+10 |
April | 0.984131E+09 | 0.307694E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161800E+10 |
May | 0.102058E+10 | 0.320669E+10 | 0.888989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 33842740.37 | 0.735649E+09 |
June | 0.998711E+09 | 0.313132E+10 | 0.867387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.457952E+09 | 0.151697E+09 |
July | 0.100600E+10 | 0.315231E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.483690E+09 | 0.150930E+09 |
August | 0.103395E+10 | 0.324295E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.418965E+09 | 0.174461E+09 |
September | 0.984131E+09 | 0.307694E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.225176E+09 | 0.343140E+09 |
October | 0.100722E+10 | 0.317044E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6027890.46 | 0.147683E+10 |
November | 0.973196E+09 | 0.307694E+10 | 0.853679E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178522E+10 |
December | 0.100600E+10 | 0.315231E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.251986E+10 |
Annual Sum or Average | 0.119700E+11 | 0.375720E+11 | 0.104207E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162566E+10 | 0.147741E+11 |
Minimum of Months | 0.914877E+09 | 0.287181E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150930E+09 |
Maximum of Months | 0.103395E+10 | 0.324295E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.483690E+09 | 0.251986E+10 |
Report: SpaceGainsMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.344359E+10 | 0.313454E+10 | 0.161799E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.360791E+10 |
February | 0.313522E+10 | 0.283982E+10 | 0.146554E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.377299E+10 |
March | 0.355148E+10 | 0.321092E+10 | 0.165455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14786.40 | 0.325947E+10 |
April | 0.338259E+10 | 0.304266E+10 | 0.157022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.297889E+10 |
May | 0.349753E+10 | 0.317273E+10 | 0.163627E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 60868468.36 | 0.134986E+10 |
June | 0.343071E+10 | 0.309995E+10 | 0.159764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.825959E+09 | 0.292463E+09 |
July | 0.344942E+10 | 0.311545E+10 | 0.160885E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.872467E+09 | 0.291750E+09 |
August | 0.355148E+10 | 0.321092E+10 | 0.165455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.754493E+09 | 0.336660E+09 |
September | 0.338259E+10 | 0.304266E+10 | 0.157022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.405350E+09 | 0.654098E+09 |
October | 0.344359E+10 | 0.313454E+10 | 0.161799E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10835055.43 | 0.271154E+10 |
November | 0.331698E+10 | 0.304266E+10 | 0.157022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.325190E+10 |
December | 0.344942E+10 | 0.311545E+10 | 0.160885E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.463071E+10 |
Annual Sum or Average | 0.410346E+11 | 0.371623E+11 | 0.191729E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.292999E+10 | 0.271382E+11 |
Minimum of Months | 0.313522E+10 | 0.283982E+10 | 0.146554E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.291750E+09 |
Maximum of Months | 0.355148E+10 | 0.321092E+10 | 0.165455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.872467E+09 | 0.463071E+10 |
Report: SpaceGainsMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.161274E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.200049E+10 |
February | 0.156756E+10 | 0.146111E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.207299E+10 |
March | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8231.24 | 0.178743E+10 |
April | 0.169125E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163639E+10 |
May | 0.174872E+10 | 0.163243E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 33842769.45 | 0.747384E+09 |
June | 0.171530E+10 | 0.159501E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.458408E+09 | 0.151539E+09 |
July | 0.172466E+10 | 0.160290E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.484000E+09 | 0.151332E+09 |
August | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.419154E+09 | 0.176310E+09 |
September | 0.169125E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.225124E+09 | 0.350404E+09 |
October | 0.172174E+10 | 0.161274E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6027890.46 | 0.149665E+10 |
November | 0.165844E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180107E+10 |
December | 0.172466E+10 | 0.160290E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.253773E+10 |
Annual Sum or Average | 0.205167E+11 | 0.191205E+11 | 0.958644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162657E+10 | 0.149097E+11 |
Minimum of Months | 0.156756E+10 | 0.146111E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151332E+09 |
Maximum of Months | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.484000E+09 | 0.253773E+10 |
Report: SpaceGainsMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.161274E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.199799E+10 |
February | 0.156756E+10 | 0.146111E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.207081E+10 |
March | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8231.24 | 0.178475E+10 |
April | 0.169125E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163329E+10 |
May | 0.174872E+10 | 0.163243E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 33842792.49 | 0.744453E+09 |
June | 0.171530E+10 | 0.159501E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.458476E+09 | 0.150936E+09 |
July | 0.172466E+10 | 0.160290E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.484089E+09 | 0.150768E+09 |
August | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.419181E+09 | 0.175801E+09 |
September | 0.169125E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.225151E+09 | 0.349672E+09 |
October | 0.172174E+10 | 0.161274E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6027890.46 | 0.149467E+10 |
November | 0.165844E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179885E+10 |
December | 0.172466E+10 | 0.160290E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.253522E+10 |
Annual Sum or Average | 0.205167E+11 | 0.191205E+11 | 0.958644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162678E+10 | 0.148872E+11 |
Minimum of Months | 0.156756E+10 | 0.146111E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150768E+09 |
Maximum of Months | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.484089E+09 | 0.253522E+10 |
Report: SpaceGainsMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.161274E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.198726E+10 |
February | 0.156756E+10 | 0.146111E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.206141E+10 |
March | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8231.24 | 0.177223E+10 |
April | 0.169125E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161763E+10 |
May | 0.174872E+10 | 0.163243E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 33842885.98 | 0.729123E+09 |
June | 0.171530E+10 | 0.159501E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.458682E+09 | 0.148739E+09 |
July | 0.172466E+10 | 0.160290E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.484313E+09 | 0.148715E+09 |
August | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.419238E+09 | 0.174057E+09 |
September | 0.169125E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.225207E+09 | 0.346483E+09 |
October | 0.172174E+10 | 0.161274E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6027890.46 | 0.148324E+10 |
November | 0.165844E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178806E+10 |
December | 0.172466E+10 | 0.160290E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.252416E+10 |
Annual Sum or Average | 0.205167E+11 | 0.191205E+11 | 0.958644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162732E+10 | 0.147811E+11 |
Minimum of Months | 0.156756E+10 | 0.146111E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148715E+09 |
Maximum of Months | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.484313E+09 | 0.252416E+10 |
Report: SpaceGainsMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.161274E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.226293E+10 |
February | 0.156756E+10 | 0.146111E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.251437E+10 |
March | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8433.60 | 0.224466E+10 |
April | 0.169125E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.208010E+10 |
May | 0.174872E+10 | 0.163243E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 35229252.00 | 0.946883E+09 |
June | 0.171530E+10 | 0.159501E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.484567E+09 | 0.271095E+09 |
July | 0.172466E+10 | 0.160290E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.511532E+09 | 0.269063E+09 |
August | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.437273E+09 | 0.301350E+09 |
September | 0.169125E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.233735E+09 | 0.547270E+09 |
October | 0.172174E+10 | 0.161274E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6224638.93 | 0.184807E+10 |
November | 0.165844E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.211803E+10 |
December | 0.172466E+10 | 0.160290E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.318188E+10 |
Annual Sum or Average | 0.205167E+11 | 0.191205E+11 | 0.958644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.170857E+10 | 0.185857E+11 |
Minimum of Months | 0.156756E+10 | 0.146111E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.269063E+09 |
Maximum of Months | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.511532E+09 | 0.318188E+10 |
Report: PeakSpaceGainsMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 4050.04 | 01-JAN-13:09 | 4621.63 | 01-JAN-10:09 | 1343.25 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 10692.65 | 05-JAN-18:00 |
February | 4050.04 | 03-FEB-13:09 | 4621.63 | 01-FEB-10:09 | 1343.25 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 9042.84 | 11-FEB-18:00 |
March | 4050.04 | 03-MAR-13:09 | 4621.63 | 01-MAR-10:09 | 1343.25 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 24.98 | 14-MAR-13:00 | 8386.82 | 04-MAR-13:00 |
April | 4050.04 | 01-APR-12:09 | 4621.63 | 01-APR-09:09 | 1343.25 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 6954.34 | 16-APR-15:30 |
May | 4050.04 | 05-MAY-12:09 | 4621.63 | 01-MAY-09:09 | 1343.25 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1251.05 | 17-MAY-13:00 | 3665.15 | 26-MAY-11:05 |
June | 4050.04 | 02-JUN-12:09 | 4621.63 | 01-JUN-09:09 | 1343.25 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3669.02 | 26-JUN-15:00 | 2016.29 | 02-JUN-15:00 |
July | 4050.04 | 01-JUL-12:09 | 4621.63 | 01-JUL-09:09 | 1343.25 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3092.86 | 16-JUL-13:00 | 1777.08 | 19-JUL-16:00 |
August | 4050.04 | 04-AUG-12:09 | 4621.63 | 01-AUG-09:09 | 1343.25 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3091.42 | 16-AUG-14:00 | 2079.24 | 29-AUG-16:00 |
September | 4050.04 | 01-SEP-12:09 | 4621.63 | 01-SEP-09:09 | 1343.25 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2110.23 | 10-SEP-13:00 | 5609.52 | 21-SEP-16:00 |
October | 4050.04 | 01-OCT-12:09 | 4621.63 | 01-OCT-09:09 | 1343.25 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 758.05 | 11-OCT-14:00 | 8111.92 | 31-OCT-15:00 |
November | 4050.04 | 03-NOV-12:09 | 4621.63 | 01-NOV-09:09 | 1343.25 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:03 | 9331.47 | 29-NOV-18:00 |
December | 4050.04 | 01-DEC-13:09 | 4621.63 | 01-DEC-10:09 | 1343.25 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 12802.01 | 21-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 4050.04 | 4621.63 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1777.08 | |||||
Maximum of Months | 4050.04 | 4621.63 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 3669.02 | 12802.01 |
Report: PeakSpaceGainsMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 01-JAN-13:09 | 2827.07 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 5918.54 | 05-JAN-18:00 |
February | 2024.96 | 03-FEB-13:09 | 2827.07 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 4990.43 | 11-FEB-18:00 |
March | 2024.96 | 03-MAR-13:09 | 2827.07 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 13.72 | 14-MAR-13:00 | 4594.54 | 04-MAR-13:00 |
April | 2024.96 | 01-APR-12:09 | 2827.07 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 3707.84 | 02-APR-13:00 |
May | 2024.96 | 05-MAY-12:09 | 2827.07 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 680.46 | 17-MAY-13:00 | 2080.99 | 26-MAY-11:05 |
June | 2024.96 | 02-JUN-12:09 | 2827.07 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2000.36 | 26-JUN-15:00 | 1093.59 | 02-JUN-15:00 |
July | 2024.96 | 01-JUL-12:09 | 2827.07 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1698.47 | 16-JUL-13:00 | 963.85 | 19-JUL-16:00 |
August | 2024.96 | 04-AUG-12:09 | 2827.07 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1693.57 | 16-AUG-14:00 | 1117.37 | 29-AUG-16:00 |
September | 2024.96 | 01-SEP-12:09 | 2827.07 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1156.05 | 10-SEP-13:00 | 3060.84 | 21-SEP-16:00 |
October | 2024.96 | 01-OCT-12:09 | 2827.07 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 413.29 | 11-OCT-14:00 | 4399.74 | 31-OCT-15:00 |
November | 2024.96 | 03-NOV-12:09 | 2827.07 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:03 | 5137.04 | 29-NOV-18:00 |
December | 2024.96 | 01-DEC-13:09 | 2827.07 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 6911.34 | 21-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 2827.07 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 963.85 | |||||
Maximum of Months | 2024.96 | 2827.07 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 2000.36 | 6911.34 |
Report: PeakSpaceGainsMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 2555.22 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 5918.54 | 05-JAN-18:00 |
February | 2024.96 | 04-FEB-13:09 | 2555.22 | 01-FEB-09:09 | 671.63 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 4990.43 | 11-FEB-18:00 |
March | 2024.96 | 04-MAR-13:09 | 2555.22 | 01-MAR-09:09 | 671.63 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 13.72 | 14-MAR-13:00 | 4594.54 | 04-MAR-13:00 |
April | 2024.96 | 01-APR-12:09 | 2555.22 | 01-APR-08:09 | 671.63 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 3707.84 | 02-APR-13:00 |
May | 2024.96 | 06-MAY-12:09 | 2555.22 | 01-MAY-08:09 | 671.63 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 680.46 | 17-MAY-13:00 | 2080.37 | 26-MAY-11:05 |
June | 2024.96 | 03-JUN-12:09 | 2555.22 | 01-JUN-08:09 | 671.63 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2000.37 | 26-JUN-15:00 | 1093.59 | 02-JUN-15:00 |
July | 2024.96 | 01-JUL-12:09 | 2555.22 | 01-JUL-08:09 | 671.63 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1698.50 | 16-JUL-13:00 | 1070.34 | 30-JUL-17:00 |
August | 2024.96 | 05-AUG-12:09 | 2555.22 | 01-AUG-08:09 | 671.63 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1693.58 | 16-AUG-14:00 | 1117.38 | 29-AUG-16:00 |
September | 2024.96 | 02-SEP-12:09 | 2555.22 | 01-SEP-08:09 | 671.63 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1156.08 | 10-SEP-13:00 | 3048.30 | 21-SEP-16:00 |
October | 2024.96 | 07-OCT-12:09 | 2555.22 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 413.29 | 11-OCT-14:00 | 4399.74 | 31-OCT-15:00 |
November | 2024.96 | 04-NOV-12:09 | 2555.22 | 01-NOV-08:09 | 671.63 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:03 | 5137.04 | 29-NOV-18:00 |
December | 2024.96 | 02-DEC-13:09 | 2555.22 | 01-DEC-09:09 | 671.63 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 6911.34 | 21-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 2555.22 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1070.34 | |||||
Maximum of Months | 2024.96 | 2555.22 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 2000.37 | 6911.34 |
Report: PeakSpaceGainsMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 2555.22 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 5918.54 | 05-JAN-18:00 |
February | 2024.96 | 04-FEB-13:09 | 2555.22 | 01-FEB-09:09 | 671.63 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 4990.43 | 11-FEB-18:00 |
March | 2024.96 | 04-MAR-13:09 | 2555.22 | 01-MAR-09:09 | 671.63 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 13.72 | 14-MAR-13:00 | 4594.54 | 04-MAR-13:00 |
April | 2024.96 | 01-APR-12:09 | 2555.22 | 01-APR-08:09 | 671.63 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 3707.84 | 02-APR-13:00 |
May | 2024.96 | 06-MAY-12:09 | 2555.22 | 01-MAY-08:09 | 671.63 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 680.46 | 17-MAY-13:00 | 2070.90 | 26-MAY-11:05 |
June | 2024.96 | 03-JUN-12:09 | 2555.22 | 01-JUN-08:09 | 671.63 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2000.37 | 26-JUN-15:00 | 1093.59 | 02-JUN-15:00 |
July | 2024.96 | 01-JUL-12:09 | 2555.22 | 01-JUL-08:09 | 671.63 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1698.50 | 16-JUL-13:00 | 1067.85 | 30-JUL-17:00 |
August | 2024.96 | 05-AUG-12:09 | 2555.22 | 01-AUG-08:09 | 671.63 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1693.58 | 16-AUG-14:00 | 1117.38 | 29-AUG-16:00 |
September | 2024.96 | 02-SEP-12:09 | 2555.22 | 01-SEP-08:09 | 671.63 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1156.09 | 10-SEP-13:00 | 3046.32 | 21-SEP-16:00 |
October | 2024.96 | 07-OCT-12:09 | 2555.22 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 413.29 | 11-OCT-14:00 | 4399.74 | 31-OCT-15:00 |
November | 2024.96 | 04-NOV-12:09 | 2555.22 | 01-NOV-08:09 | 671.63 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:03 | 5137.04 | 29-NOV-18:00 |
December | 2024.96 | 02-DEC-13:09 | 2555.22 | 01-DEC-09:09 | 671.63 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 6911.34 | 21-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 2555.22 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1067.85 | |||||
Maximum of Months | 2024.96 | 2555.22 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 2000.37 | 6911.34 |
Report: PeakSpaceGainsMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 2555.22 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 5918.54 | 05-JAN-18:00 |
February | 2024.96 | 04-FEB-13:09 | 2555.22 | 01-FEB-09:09 | 671.63 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 4990.43 | 11-FEB-18:00 |
March | 2024.96 | 04-MAR-13:09 | 2555.22 | 01-MAR-09:09 | 671.63 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 13.72 | 14-MAR-13:00 | 4594.54 | 04-MAR-13:00 |
April | 2024.96 | 01-APR-12:09 | 2555.22 | 01-APR-08:09 | 671.63 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 3707.84 | 02-APR-13:00 |
May | 2024.96 | 06-MAY-12:09 | 2555.22 | 01-MAY-08:09 | 671.63 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 680.46 | 17-MAY-13:00 | 2042.64 | 26-MAY-11:05 |
June | 2024.96 | 03-JUN-12:09 | 2555.22 | 01-JUN-08:09 | 671.63 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2000.37 | 26-JUN-15:00 | 1093.59 | 02-JUN-15:00 |
July | 2024.96 | 01-JUL-12:09 | 2555.22 | 01-JUL-08:09 | 671.63 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1698.51 | 16-JUL-13:00 | 1057.80 | 30-JUL-17:00 |
August | 2024.96 | 05-AUG-12:09 | 2555.22 | 01-AUG-08:09 | 671.63 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1693.58 | 16-AUG-14:00 | 1117.38 | 29-AUG-16:00 |
September | 2024.96 | 02-SEP-12:09 | 2555.22 | 01-SEP-08:09 | 671.63 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1156.09 | 10-SEP-13:00 | 3044.30 | 21-SEP-16:00 |
October | 2024.96 | 07-OCT-12:09 | 2555.22 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 413.29 | 11-OCT-14:00 | 4399.74 | 31-OCT-15:00 |
November | 2024.96 | 04-NOV-12:09 | 2555.22 | 01-NOV-08:09 | 671.63 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:03 | 5137.04 | 29-NOV-18:00 |
December | 2024.96 | 02-DEC-13:09 | 2555.22 | 01-DEC-09:09 | 671.63 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 6911.34 | 21-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 2555.22 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1057.80 | |||||
Maximum of Months | 2024.96 | 2555.22 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 2000.37 | 6911.34 |
Report: PeakSpaceGainsMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 5400.05 | 07-JAN-15:09 | 2726.96 | 01-JAN-11:09 | 1343.25 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 10621.64 | 05-JAN-18:00 |
February | 5400.05 | 04-FEB-15:09 | 2726.96 | 01-FEB-10:09 | 1343.25 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 8959.29 | 11-FEB-18:00 |
March | 5400.05 | 04-MAR-15:09 | 2726.96 | 01-MAR-10:09 | 1343.25 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 24.64 | 14-MAR-13:00 | 8255.99 | 04-MAR-13:00 |
April | 5400.05 | 01-APR-14:09 | 2726.96 | 01-APR-09:09 | 1343.25 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 6670.90 | 02-APR-13:00 |
May | 5400.05 | 06-MAY-14:09 | 2726.96 | 01-MAY-09:09 | 1343.25 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1223.82 | 17-MAY-13:00 | 3572.40 | 26-MAY-11:05 |
June | 5400.05 | 03-JUN-14:09 | 2726.96 | 01-JUN-09:09 | 1343.25 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3596.63 | 26-JUN-15:00 | 1967.49 | 02-JUN-15:00 |
July | 5400.05 | 01-JUL-14:09 | 2726.96 | 01-JUL-09:09 | 1343.25 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3051.14 | 16-JUL-13:00 | 1825.50 | 30-JUL-17:00 |
August | 5400.05 | 05-AUG-14:09 | 2726.96 | 01-AUG-09:09 | 1343.25 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3043.22 | 16-AUG-14:00 | 2012.59 | 29-AUG-16:00 |
September | 5400.05 | 02-SEP-14:09 | 2726.96 | 01-SEP-09:09 | 1343.25 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2077.37 | 10-SEP-13:00 | 5476.11 | 21-SEP-16:00 |
October | 5400.05 | 07-OCT-14:09 | 2726.96 | 01-OCT-10:09 | 1343.25 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 743.09 | 11-OCT-14:00 | 7915.73 | 31-OCT-15:00 |
November | 5400.05 | 04-NOV-14:09 | 2726.96 | 01-NOV-09:09 | 1343.25 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:03 | 9225.27 | 29-NOV-18:00 |
December | 5400.05 | 02-DEC-15:09 | 2726.96 | 01-DEC-10:09 | 1343.25 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 12441.64 | 21-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 5400.05 | 2726.96 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1825.50 | |||||
Maximum of Months | 5400.05 | 2726.96 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 3596.63 | 12441.64 |
Report: PeakSpaceGainsMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1404.46 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 5918.54 | 05-JAN-18:00 |
February | 2699.95 | 04-FEB-15:09 | 1404.46 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 4990.43 | 11-FEB-18:00 |
March | 2699.95 | 04-MAR-15:09 | 1404.46 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 13.72 | 14-MAR-13:00 | 4594.54 | 04-MAR-13:00 |
April | 2699.95 | 01-APR-14:09 | 1404.46 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 3707.84 | 02-APR-13:00 |
May | 2699.95 | 06-MAY-14:09 | 1404.46 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 680.46 | 17-MAY-13:00 | 2069.77 | 26-MAY-11:05 |
June | 2699.95 | 03-JUN-14:09 | 1404.46 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2000.52 | 26-JUN-15:00 | 1093.57 | 02-JUN-15:00 |
July | 2699.95 | 01-JUL-14:09 | 1404.46 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1698.59 | 16-JUL-13:00 | 1080.05 | 30-JUL-17:00 |
August | 2699.95 | 05-AUG-14:09 | 1404.46 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1693.71 | 16-AUG-14:00 | 1117.38 | 29-AUG-16:00 |
September | 2699.95 | 02-SEP-14:09 | 1404.46 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1156.11 | 10-SEP-13:00 | 3061.25 | 21-SEP-16:00 |
October | 2699.95 | 07-OCT-14:09 | 1404.46 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 413.29 | 11-OCT-14:00 | 4399.74 | 31-OCT-15:00 |
November | 2699.95 | 04-NOV-14:09 | 1404.46 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:03 | 5137.04 | 29-NOV-18:00 |
December | 2699.95 | 02-DEC-15:09 | 1404.46 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 6911.34 | 21-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1080.05 | |||||
Maximum of Months | 2699.95 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 2000.52 | 6911.34 |
Report: PeakSpaceGainsMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1404.46 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 5918.54 | 05-JAN-18:00 |
February | 2699.95 | 04-FEB-15:09 | 1404.46 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 4990.43 | 11-FEB-18:00 |
March | 2699.95 | 04-MAR-15:09 | 1404.46 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 13.72 | 14-MAR-13:00 | 4594.54 | 04-MAR-13:00 |
April | 2699.95 | 01-APR-14:09 | 1404.46 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 3707.84 | 02-APR-13:00 |
May | 2699.95 | 06-MAY-14:09 | 1404.46 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 680.46 | 17-MAY-13:00 | 2060.14 | 26-MAY-11:05 |
June | 2699.95 | 03-JUN-14:09 | 1404.46 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2000.52 | 26-JUN-15:00 | 1093.57 | 02-JUN-15:00 |
July | 2699.95 | 01-JUL-14:09 | 1404.46 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1698.59 | 16-JUL-13:00 | 1076.12 | 30-JUL-17:00 |
August | 2699.95 | 05-AUG-14:09 | 1404.46 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1693.71 | 16-AUG-14:00 | 1117.38 | 29-AUG-16:00 |
September | 2699.95 | 02-SEP-14:09 | 1404.46 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1156.11 | 10-SEP-13:00 | 3058.52 | 21-SEP-16:00 |
October | 2699.95 | 07-OCT-14:09 | 1404.46 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 413.29 | 11-OCT-14:00 | 4399.74 | 31-OCT-15:00 |
November | 2699.95 | 04-NOV-14:09 | 1404.46 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:03 | 5137.04 | 29-NOV-18:00 |
December | 2699.95 | 02-DEC-15:09 | 1404.46 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 6911.34 | 21-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1076.12 | |||||
Maximum of Months | 2699.95 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 2000.52 | 6911.34 |
Report: PeakSpaceGainsMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1404.46 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 5918.54 | 05-JAN-18:00 |
February | 2699.95 | 04-FEB-15:09 | 1404.46 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 4990.43 | 11-FEB-18:00 |
March | 2699.95 | 04-MAR-15:09 | 1404.46 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 13.72 | 14-MAR-13:00 | 4594.54 | 04-MAR-13:00 |
April | 2699.95 | 01-APR-14:09 | 1404.46 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 3707.84 | 02-APR-13:00 |
May | 2699.95 | 06-MAY-14:09 | 1404.46 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 680.46 | 17-MAY-13:00 | 2009.83 | 26-MAY-11:05 |
June | 2699.95 | 03-JUN-14:09 | 1404.46 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2000.52 | 26-JUN-15:00 | 1093.57 | 02-JUN-15:00 |
July | 2699.95 | 01-JUL-14:09 | 1404.46 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1698.59 | 16-JUL-13:00 | 1064.71 | 30-JUL-17:00 |
August | 2699.95 | 05-AUG-14:09 | 1404.46 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1693.71 | 16-AUG-14:00 | 1117.38 | 29-AUG-16:00 |
September | 2699.95 | 02-SEP-14:09 | 1404.46 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1156.11 | 10-SEP-13:00 | 3046.33 | 21-SEP-16:00 |
October | 2699.95 | 07-OCT-14:09 | 1404.46 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 413.29 | 11-OCT-14:00 | 4399.74 | 31-OCT-15:00 |
November | 2699.95 | 04-NOV-14:09 | 1404.46 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:03 | 5137.04 | 29-NOV-18:00 |
December | 2699.95 | 02-DEC-15:09 | 1404.46 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 6911.34 | 21-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1064.71 | |||||
Maximum of Months | 2699.95 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 2000.52 | 6911.34 |
Report: PeakSpaceGainsMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1404.46 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 5989.55 | 05-JAN-18:00 |
February | 2699.95 | 04-FEB-15:09 | 1404.46 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 5073.99 | 11-FEB-18:00 |
March | 2699.95 | 04-MAR-15:09 | 1404.46 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 14.06 | 14-MAR-13:00 | 4725.37 | 04-MAR-13:00 |
April | 2699.95 | 01-APR-14:09 | 1404.46 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 3989.46 | 16-APR-15:50 |
May | 2699.95 | 06-MAY-14:09 | 1404.46 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 707.70 | 17-MAY-13:00 | 2064.40 | 02-MAY-11:10 |
June | 2699.95 | 03-JUN-14:09 | 1404.46 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2072.77 | 26-JUN-15:00 | 1142.34 | 02-JUN-15:00 |
July | 2699.95 | 01-JUL-14:09 | 1404.46 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1740.24 | 16-JUL-13:00 | 1020.20 | 30-JUL-17:00 |
August | 2699.95 | 05-AUG-14:09 | 1404.46 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1741.79 | 16-AUG-14:00 | 1183.98 | 29-AUG-16:00 |
September | 2699.95 | 02-SEP-14:09 | 1404.46 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1188.99 | 10-SEP-13:00 | 3177.33 | 21-SEP-16:00 |
October | 2699.95 | 07-OCT-14:09 | 1404.46 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 428.25 | 11-OCT-14:00 | 4595.92 | 31-OCT-15:00 |
November | 2699.95 | 04-NOV-14:09 | 1404.46 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:03 | 5243.24 | 29-NOV-18:00 |
December | 2699.95 | 02-DEC-15:09 | 1404.46 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 7271.71 | 21-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1020.20 | |||||
Maximum of Months | 2699.95 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 2072.77 | 7271.71 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 13275.25 | 06-JAN-00:01 | 2362.52 | 1702.61 | 5223.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 153.21 |
February | 10169.04 | 10-FEB-00:02 | 1687.52 | 1216.15 | 3731.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 245.80 |
March | 7819.31 | 04-MAR-00:03 | 1350.01 | 9729.72 | 2985.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 210.43 |
April | 8720.07 | 02-APR-18:03 | 10800.10 | 18486.52 | 5373.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1012.76 |
May | 8997.19 | 31-MAY-16:10 | 3375.03 | 4621.63 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 970.07 | 0.00 |
June | 23367.38 | 14-JUN-07:03 | 1350.01 | 300.00 | 298.50 | 0.00 | 0.00 | 0.00 | 0.00 | 203.34 | 0.00 |
July | 31634.07 | 18-JUL-07:02 | 1687.52 | 375.00 | 373.12 | 0.00 | 0.00 | 0.00 | 0.00 | 14.98 | 0.00 |
August | 23182.94 | 03-AUG-07:03 | 1350.01 | 300.00 | 298.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.75 |
September | 24453.95 | 13-SEP-07:03 | 1350.01 | 300.00 | 298.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 151.99 |
October | 11549.11 | 11-OCT-14:00 | 2700.03 | 4621.63 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 758.05 | 0.00 |
November | 10288.39 | 28-NOV-21:22 | 10125.10 | 23108.15 | 6716.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 263.80 |
December | 15016.10 | 22-DEC-00:01 | 2700.03 | 1945.84 | 5970.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 542.48 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 7819.31 | 1350.01 | 300.00 | 298.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 31634.07 | 10800.10 | 23108.15 | 6716.25 | 0.00 | 0.00 | 0.00 | 0.00 | 970.07 | 1012.76 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3631.14 | 22-JAN-09:01 | 1349.97 | 11903.44 | 2985.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 445.92 |
February | 3447.44 | 28-FEB-09:03 | 506.24 | 4463.79 | 1119.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 424.36 |
March | 15646.35 | 12-MAR-17:08 | 12149.77 | 16962.41 | 4029.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.15 |
April | 3737.47 | 22-APR-08:62 | 674.99 | 150.00 | 1492.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 494.28 |
May | 15683.15 | 17-MAY-20:07 | 7087.36 | 19789.47 | 4701.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.06 |
June | 15702.18 | 10-JUN-20:25 | 6074.88 | 16962.41 | 4029.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.97 |
July | 17688.35 | 18-JUL-07:02 | 843.73 | 187.50 | 186.56 | 0.00 | 0.00 | 0.00 | 0.00 | 3.77 | 0.00 |
August | 15580.06 | 18-AUG-22:09 | 4724.91 | 10415.51 | 4701.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.10 |
September | 16297.74 | 16-SEP-19:39 | 7087.36 | 19789.47 | 4701.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.27 |
October | 16243.13 | 07-OCT-18:07 | 11812.27 | 19789.47 | 4701.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 125.62 |
November | 4698.49 | 07-NOV-14:30 | 1349.97 | 2827.07 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 257.60 |
December | 3642.91 | 05-DEC-09:03 | 506.24 | 4463.79 | 1119.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 504.67 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3447.44 | 506.24 | 150.00 | 186.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17688.35 | 12149.77 | 19789.47 | 4701.38 | 0.00 | 0.00 | 0.00 | 0.00 | 3.77 | 504.67 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3840.21 | 30-JAN-09:43 | 1349.97 | 10220.87 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 441.52 |
February | 4466.95 | 08-FEB-19:33 | 2699.95 | 10220.87 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 558.62 |
March | 5271.73 | 04-MAR-11:02 | 3374.94 | 12776.09 | 3358.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 659.12 |
April | 4177.41 | 02-APR-10:02 | 2699.95 | 10220.87 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 577.49 |
May | 4886.41 | 17-MAY-13:00 | 1349.97 | 2555.22 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 680.46 | 0.00 |
June | 14933.26 | 27-JUN-06:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.68 |
July | 20090.67 | 18-JUL-06:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.26 |
August | 14323.91 | 20-AUG-07:03 | 0.00 | 150.00 | 149.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.24 |
September | 19183.63 | 11-SEP-06:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.46 |
October | 6160.06 | 11-OCT-14:00 | 1012.48 | 2555.22 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 413.29 | 0.00 |
November | 4297.17 | 07-NOV-14:00 | 1349.97 | 2555.22 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 258.43 |
December | 4184.95 | 18-DEC-08:61 | 1518.72 | 337.50 | 3358.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 499.91 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3840.21 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 20090.67 | 3374.94 | 12776.09 | 3358.13 | 0.00 | 0.00 | 0.00 | 0.00 | 680.46 | 659.12 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4519.69 | 07-JAN-10:02 | 1349.97 | 10220.87 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 576.69 |
February | 4152.23 | 01-FEB-11:02 | 1349.97 | 10220.87 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 481.14 |
March | 5300.59 | 04-MAR-11:42 | 3374.94 | 12776.09 | 3358.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 638.83 |
April | 3839.22 | 22-APR-07:01 | 1181.23 | 262.50 | 2611.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 484.90 |
May | 4817.00 | 17-MAY-13:00 | 1349.97 | 2555.22 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 680.46 | 0.00 |
June | 15461.03 | 27-JUN-06:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.70 |
July | 20027.66 | 18-JUL-06:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.40 |
August | 14876.83 | 21-AUG-06:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.28 |
September | 20055.22 | 11-SEP-06:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.47 |
October | 6111.80 | 11-OCT-14:00 | 1012.48 | 2555.22 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 413.29 | 0.00 |
November | 4970.77 | 28-NOV-19:53 | 2699.95 | 10220.87 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 638.33 |
December | 4341.10 | 07-DEC-09:02 | 1349.97 | 10220.87 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 563.40 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3839.22 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 20055.22 | 3374.94 | 12776.09 | 3358.13 | 0.00 | 0.00 | 0.00 | 0.00 | 680.46 | 638.83 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3513.67 | 26-JAN-08:61 | 1518.72 | 337.50 | 3358.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 415.23 |
February | 3836.84 | 02-FEB-20:53 | 674.99 | 5379.41 | 1492.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.07 |
March | 4172.77 | 14-MAR-13:00 | 1349.97 | 2555.22 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 13.72 | 0.00 |
April | 3780.49 | 22-APR-07:01 | 1181.23 | 262.50 | 2611.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 478.27 |
May | 4604.31 | 17-MAY-13:00 | 1349.97 | 2555.22 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 680.46 | 0.00 |
June | 14188.19 | 27-JUN-06:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.65 |
July | 19639.12 | 17-JUL-06:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.63 |
August | 13888.95 | 21-AUG-06:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.24 |
September | 18896.42 | 11-SEP-06:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.45 |
October | 5951.91 | 11-OCT-14:00 | 1012.48 | 2555.22 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 413.29 | 0.00 |
November | 3788.82 | 07-NOV-14:00 | 1349.97 | 2555.22 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 258.43 |
December | 3838.70 | 09-DEC-10:13 | 1349.97 | 10220.87 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 574.22 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3513.67 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19639.12 | 1518.72 | 10220.87 | 3358.13 | 0.00 | 0.00 | 0.00 | 0.00 | 680.46 | 574.22 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5488.21 | 25-JAN-18:50 | 2295.02 | 2726.96 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 574.01 |
February | 4947.24 | 19-FEB-10:05 | 1485.01 | 150.00 | 1492.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 583.78 |
March | 7163.06 | 14-MAR-13:00 | 4792.55 | 2726.96 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 24.64 | 0.00 |
April | 6892.70 | 22-APR-08:20 | 1485.01 | 2870.47 | 1492.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 844.84 |
May | 7976.15 | 17-MAY-14:10 | 4657.54 | 2726.96 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 1145.96 | 0.00 |
June | 28809.68 | 25-JUN-08:62 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 139.71 | 0.00 |
July | 31171.27 | 18-JUL-07:02 | 0.00 | 375.00 | 368.20 | 0.00 | 0.00 | 0.00 | 0.00 | 3.95 | 0.00 |
August | 27604.66 | 20-AUG-08:62 | 0.00 | 300.00 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.90 |
September | 28203.45 | 11-SEP-07:03 | 0.00 | 300.00 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 125.37 |
October | 10775.74 | 11-OCT-14:10 | 4657.54 | 2726.96 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 704.33 | 0.00 |
November | 8350.00 | 21-NOV-20:33 | 2970.03 | 5740.94 | 2985.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6878.02 | 18-DEC-09:07 | 2227.52 | 225.00 | 2238.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 801.49 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4947.24 | 0.00 | 150.00 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 31171.27 | 4792.55 | 5740.94 | 2985.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1145.96 | 844.84 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3473.69 | 03-JAN-19:13 | 2632.45 | 4213.39 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 505.43 |
February | 3354.16 | 09-FEB-18:17 | 3442.43 | 4213.39 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 516.17 |
March | 3729.68 | 14-MAR-13:00 | 2396.20 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 13.72 | 0.00 |
April | 2876.56 | 22-APR-08:62 | 1484.97 | 150.00 | 1492.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 485.64 |
May | 4134.53 | 17-MAY-14:10 | 2328.71 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 637.03 | 0.00 |
June | 14824.82 | 25-JUN-08:62 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 78.00 | 0.00 |
July | 15994.88 | 18-JUL-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.02 | 0.00 |
August | 13120.60 | 20-AUG-08:62 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.45 |
September | 13763.46 | 11-SEP-07:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.15 |
October | 5613.94 | 11-OCT-14:10 | 2328.71 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 391.69 | 0.00 |
November | 3342.86 | 07-NOV-14:00 | 2396.20 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 258.43 |
December | 3513.74 | 07-DEC-19:23 | 2632.45 | 4213.39 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 542.52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2876.56 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15994.88 | 3442.43 | 4213.39 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 637.03 | 542.52 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4071.05 | 12-JAN-19:23 | 3509.93 | 5617.86 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 589.83 |
February | 4014.79 | 11-FEB-11:32 | 7829.85 | 5617.86 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 665.91 |
March | 3619.34 | 14-MAR-13:00 | 2396.20 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 13.72 | 0.00 |
April | 2873.88 | 22-APR-08:62 | 1484.97 | 150.00 | 1492.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 483.94 |
May | 4055.02 | 17-MAY-14:10 | 2328.71 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 637.03 | 0.00 |
June | 14717.58 | 25-JUN-08:62 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 78.82 | 0.00 |
July | 15858.63 | 18-JUL-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.58 | 0.00 |
August | 12710.03 | 20-AUG-08:62 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.36 |
September | 13419.42 | 11-SEP-07:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.08 |
October | 5544.60 | 11-OCT-14:10 | 2328.71 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 391.69 | 0.00 |
November | 3266.39 | 07-NOV-14:00 | 2396.20 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 258.43 |
December | 4933.90 | 18-DEC-20:33 | 1484.97 | 2956.77 | 1492.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 202.04 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2873.88 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15858.63 | 7829.85 | 5617.86 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 637.03 | 665.91 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3353.29 | 03-JAN-18:23 | 3442.43 | 4213.39 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 489.71 |
February | 2780.51 | 15-FEB-19:33 | 2632.45 | 4213.39 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 445.47 |
March | 3380.69 | 27-MAR-17:33 | 3442.43 | 4213.39 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 592.26 |
April | 2802.03 | 22-APR-08:62 | 1484.97 | 150.00 | 1492.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 474.06 |
May | 3826.06 | 17-MAY-14:10 | 2328.71 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 637.03 | 0.00 |
June | 14578.68 | 25-JUN-08:62 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 82.48 | 0.00 |
July | 15652.65 | 18-JUL-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 0.00 |
August | 11372.62 | 20-AUG-08:62 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.07 |
September | 12169.47 | 11-SEP-07:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.83 |
October | 5380.22 | 11-OCT-14:10 | 2328.71 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 391.69 | 0.00 |
November | 3257.97 | 21-NOV-19:03 | 2632.45 | 4213.39 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 461.90 |
December | 2435.70 | 30-DEC-18:35 | 742.49 | 1478.38 | 746.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 401.39 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2435.70 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15652.65 | 3442.43 | 4213.39 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 637.03 | 592.26 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2738.30 | 27-JAN-19:03 | 2632.45 | 4213.39 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 335.36 |
February | 1681.00 | 25-FEB-11:20 | 1957.46 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 208.03 |
March | 2828.80 | 14-MAR-13:00 | 2396.20 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 14.06 | 0.00 |
April | 2141.21 | 21-APR-19:00 | 877.48 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 336.93 |
May | 3766.24 | 17-MAY-14:10 | 2328.71 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 664.31 | 0.00 |
June | 15230.51 | 25-JUN-08:62 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 106.84 | 0.00 |
July | 15398.57 | 16-JUL-08:62 | 0.00 | 225.00 | 220.92 | 0.00 | 0.00 | 0.00 | 0.00 | 158.24 | 0.00 |
August | 8253.04 | 20-AUG-08:62 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.18 |
September | 7837.46 | 11-SEP-07:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.53 |
October | 5412.34 | 11-OCT-14:10 | 2328.71 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 406.42 | 0.00 |
November | 2602.21 | 07-NOV-14:00 | 2396.20 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 266.79 |
December | 2815.65 | 18-DEC-10:23 | 1113.73 | 4213.39 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 516.69 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1681.00 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15398.57 | 2632.45 | 4213.39 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 664.31 | 516.69 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.671436E+11 | 58517.30 | 07-JAN-17:19 | 0.612085E+11 | 194069.49 | 05-JAN-12:09 |
February | 0.604286E+11 | 55488.98 | 07-FEB-18:49 | 0.668483E+11 | 186876.54 | 06-FEB-08:09 |
March | 0.669680E+11 | 58219.00 | 14-MAR-12:00 | 0.470127E+11 | 174345.22 | 19-MAR-08:09 |
April | 0.626302E+11 | 54084.99 | 04-APR-18:40 | 0.349314E+11 | 149330.68 | 17-APR-07:10 |
May | 0.673298E+11 | 62761.00 | 31-MAY-14:20 | 0.213014E+10 | 77413.27 | 02-MAY-07:10 |
June | 0.826069E+11 | 89016.25 | 26-JUN-14:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 0.848961E+11 | 81006.77 | 16-JUL-14:50 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.853710E+11 | 87587.89 | 16-AUG-13:50 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.766142E+11 | 75035.92 | 10-SEP-14:20 | 0.249958E+09 | 27730.88 | 22-SEP-08:20 |
October | 0.671230E+11 | 66716.73 | 11-OCT-13:00 | 0.246454E+11 | 144640.85 | 31-OCT-11:09 |
November | 0.646604E+11 | 57375.65 | 21-NOV-17:30 | 0.407336E+11 | 155030.14 | 29-NOV-17:00 |
December | 0.674794E+11 | 55375.94 | 26-DEC-17:30 | 0.823803E+11 | 227604.68 | 21-DEC-17:00 |
Annual Sum or Average | 0.853251E+12 | 0.360140E+12 | ||||
Minimum of Months | 0.604286E+11 | 54084.99 | 0.00 | 0.00 | ||
Maximum of Months | 0.853710E+11 | 89016.25 | 0.823803E+11 | 227604.68 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.310073E+11 | 0.663131E+10 | 0.108325E+11 | 0.00 | 0.130065E+11 | 0.00 | 0.00 | 13232102.00 | 0.00 | 0.00 | 0.00 | 0.565284E+10 | 0.00 |
February | 0.280657E+11 | 0.544512E+10 | 0.980803E+10 | 0.00 | 0.119678E+11 | 0.00 | 0.00 | 2788588.58 | 0.00 | 0.00 | 0.00 | 0.513912E+10 | 0.00 |
March | 0.314703E+11 | 0.526005E+10 | 0.110075E+11 | 0.00 | 0.130439E+11 | 0.00 | 0.00 | 0.491314E+09 | 0.00 | 0.00 | 0.00 | 0.569500E+10 | 0.00 |
April | 0.300741E+11 | 0.431174E+10 | 0.105079E+11 | 0.00 | 0.122559E+11 | 0.00 | 0.00 | 69330565.88 | 0.00 | 0.00 | 0.00 | 0.541125E+10 | 0.00 |
May | 0.312330E+11 | 0.386204E+10 | 0.109147E+11 | 0.00 | 0.123348E+11 | 0.00 | 0.00 | 0.350660E+10 | 0.00 | 0.00 | 0.00 | 0.547867E+10 | 0.00 |
June | 0.304143E+11 | 0.346164E+10 | 0.106386E+11 | 0.00 | 0.120355E+11 | 0.00 | 0.00 | 0.208435E+11 | 0.00 | 0.00 | 0.00 | 0.521327E+10 | 0.00 |
July | 0.309042E+11 | 0.365924E+10 | 0.107945E+11 | 0.00 | 0.121644E+11 | 0.00 | 0.00 | 0.220929E+11 | 0.00 | 0.00 | 0.00 | 0.528084E+10 | 0.00 |
August | 0.314595E+11 | 0.415644E+10 | 0.110006E+11 | 0.00 | 0.124169E+11 | 0.00 | 0.00 | 0.210313E+11 | 0.00 | 0.00 | 0.00 | 0.530621E+10 | 0.00 |
September | 0.300847E+11 | 0.475121E+10 | 0.105148E+11 | 0.00 | 0.118297E+11 | 0.00 | 0.00 | 0.142990E+11 | 0.00 | 0.00 | 0.00 | 0.513477E+10 | 0.00 |
October | 0.310073E+11 | 0.571273E+10 | 0.108325E+11 | 0.00 | 0.125387E+11 | 0.00 | 0.00 | 0.163831E+10 | 0.00 | 0.00 | 0.00 | 0.539349E+10 | 0.00 |
November | 0.300409E+11 | 0.621498E+10 | 0.104978E+11 | 0.00 | 0.123389E+11 | 0.00 | 0.00 | 0.243162E+09 | 0.00 | 0.00 | 0.00 | 0.532457E+10 | 0.00 |
December | 0.309156E+11 | 0.682295E+10 | 0.108050E+11 | 0.00 | 0.133062E+11 | 0.00 | 0.00 | 33930682.72 | 0.00 | 0.00 | 0.00 | 0.559569E+10 | 0.00 |
Annual Sum or Average | 0.366677E+12 | 0.602894E+11 | 0.128154E+12 | 0.00 | 0.149239E+12 | 0.00 | 0.00 | 0.842653E+11 | 0.00 | 0.00 | 0.00 | 0.646257E+11 | 0.00 |
Minimum of Months | 0.280657E+11 | 0.346164E+10 | 0.980803E+10 | 0.00 | 0.118297E+11 | 0.00 | 0.00 | 2788588.58 | 0.00 | 0.00 | 0.00 | 0.513477E+10 | 0.00 |
Maximum of Months | 0.314703E+11 | 0.682295E+10 | 0.110075E+11 | 0.00 | 0.133062E+11 | 0.00 | 0.00 | 0.220929E+11 | 0.00 | 0.00 | 0.00 | 0.569500E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.612085E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.668483E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.470127E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.349314E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.213014E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.249958E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.246454E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.407336E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.823803E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.360140E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.823803E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 23459.17 | 01-JAN-11:09 | 5507.06 | 01-JAN-06:10 | 8059.50 | 01-JAN-11:09 | 0.00 | 11512.39 | 05-JAN-12:09 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 23459.17 | 01-FEB-10:09 | 5507.06 | 01-FEB-06:10 | 8059.50 | 01-FEB-10:09 | 0.00 | 11305.79 | 06-FEB-08:09 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 23459.17 | 01-MAR-10:09 | 5507.06 | 01-MAR-06:10 | 8059.50 | 01-MAR-10:09 | 0.00 | 11160.93 | 19-MAR-08:09 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 23459.17 | 01-APR-09:09 | 5507.06 | 01-APR-05:10 | 8059.50 | 01-APR-09:09 | 0.00 | 10748.89 | 17-APR-07:10 | 0.00 | 0.00 | 01-APR-00:10 |
May | 23459.17 | 01-MAY-09:09 | 5507.06 | 01-MAY-18:49 | 8059.50 | 01-MAY-09:09 | 0.00 | 9688.00 | 02-MAY-07:10 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 23459.17 | 01-JUN-09:09 | 5507.06 | 01-JUN-19:19 | 8059.50 | 01-JUN-09:09 | 0.00 | 11082.12 | 26-JUN-14:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 23459.17 | 01-JUL-09:09 | 5507.06 | 01-JUL-19:30 | 8059.50 | 01-JUL-09:09 | 0.00 | 9796.87 | 16-JUL-12:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 23459.17 | 01-AUG-09:09 | 5507.06 | 01-AUG-19:10 | 8059.50 | 01-AUG-09:09 | 0.00 | 10571.00 | 16-AUG-13:00 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 23459.17 | 01-SEP-09:09 | 5507.06 | 01-SEP-05:10 | 8059.50 | 01-SEP-09:09 | 0.00 | 9184.48 | 09-SEP-12:00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 23459.17 | 01-OCT-10:09 | 5507.06 | 01-OCT-05:10 | 8059.50 | 01-OCT-10:09 | 0.00 | 10744.96 | 31-OCT-11:09 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 23459.17 | 01-NOV-09:09 | 5507.06 | 01-NOV-05:10 | 8059.50 | 01-NOV-09:09 | 0.00 | 10908.85 | 29-NOV-17:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 23459.17 | 01-DEC-10:09 | 5507.06 | 01-DEC-06:10 | 8059.50 | 01-DEC-10:09 | 0.00 | 12037.59 | 21-DEC-16:00 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||||
Minimum of Months | 23459.17 | 5507.06 | 8059.50 | 0.00 | 9184.48 | 0.00 | 0.00 | |||||
Maximum of Months | 23459.17 | 5507.06 | 8059.50 | 0.00 | 12037.59 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 2550.14 | 20-JAN-13:00 | 0.00 | 0.00 | 0.00 | 11562.16 | 08-JAN-15:00 | 0.00 |
February | 683.90 | 18-FEB-13:00 | 0.00 | 0.00 | 0.00 | 8753.30 | 07-FEB-18:49 | 0.00 |
March | 13484.72 | 14-MAR-12:00 | 0.00 | 0.00 | 0.00 | 9733.38 | 31-MAR-12:50 | 0.00 |
April | 5420.13 | 20-APR-12:00 | 0.00 | 0.00 | 0.00 | 9728.83 | 04-APR-13:00 | 0.00 |
May | 18958.38 | 17-MAY-12:00 | 0.00 | 0.00 | 0.00 | 7597.41 | 05-MAY-12:50 | 0.00 |
June | 43088.59 | 26-JUN-14:00 | 0.00 | 0.00 | 0.00 | 7584.72 | 08-JUN-12:50 | 0.00 |
July | 35465.77 | 16-JUL-12:00 | 0.00 | 0.00 | 0.00 | 7559.67 | 12-JUL-11:30 | 0.00 |
August | 38630.29 | 16-AUG-13:00 | 0.00 | 0.00 | 0.00 | 7575.76 | 12-AUG-12:39 | 0.00 |
September | 30538.33 | 09-SEP-12:00 | 0.00 | 0.00 | 0.00 | 7583.86 | 30-SEP-12:20 | 0.00 |
October | 20428.40 | 11-OCT-13:00 | 0.00 | 0.00 | 0.00 | 9712.53 | 23-OCT-12:00 | 0.00 |
November | 9074.73 | 07-NOV-13:00 | 0.00 | 0.00 | 0.00 | 11808.28 | 09-NOV-15:50 | 0.00 |
December | 4852.18 | 02-DEC-14:00 | 0.00 | 0.00 | 0.00 | 11861.00 | 08-DEC-13:09 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 683.90 | 0.00 | 0.00 | 0.00 | 7559.67 | 0.00 | ||
Maximum of Months | 43088.59 | 0.00 | 0.00 | 0.00 | 11861.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 58517.30 | 07-JAN-17:19 | 23459.17 | 8059.50 | 5507.06 | 0.00 | 10171.31 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 55488.98 | 07-FEB-18:49 | 23459.17 | 8059.50 | 5507.06 | 0.00 | 9709.95 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 58219.00 | 14-MAR-12:00 | 23459.17 | 8059.50 | 0.00 | 0.00 | 8484.86 | 0.00 | 0.00 | 13484.72 | 0.00 |
April | 54084.99 | 04-APR-18:40 | 23459.17 | 8059.50 | 5507.06 | 0.00 | 9026.90 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 62761.00 | 31-MAY-14:20 | 23459.17 | 8059.50 | 0.00 | 0.00 | 8484.86 | 0.00 | 0.00 | 17308.33 | 0.00 |
June | 89016.25 | 26-JUN-14:00 | 23459.17 | 8059.50 | 0.00 | 0.00 | 11082.12 | 0.00 | 0.00 | 43088.59 | 0.00 |
July | 81006.77 | 16-JUL-14:50 | 23459.17 | 8059.50 | 0.00 | 0.00 | 9614.12 | 0.00 | 0.00 | 34449.44 | 0.00 |
August | 87587.89 | 16-AUG-13:50 | 23459.17 | 8059.50 | 0.00 | 0.00 | 10538.74 | 0.00 | 0.00 | 38203.89 | 0.00 |
September | 75035.92 | 10-SEP-14:20 | 23459.17 | 8059.50 | 0.00 | 0.00 | 8883.99 | 0.00 | 0.00 | 29208.83 | 0.00 |
October | 66716.73 | 11-OCT-13:00 | 23459.17 | 8059.50 | 0.00 | 0.00 | 8484.86 | 0.00 | 0.00 | 20428.40 | 0.00 |
November | 57375.65 | 21-NOV-17:30 | 23459.17 | 8059.50 | 5507.06 | 0.00 | 9758.33 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 55375.94 | 26-DEC-17:30 | 23459.17 | 8059.50 | 5507.06 | 0.00 | 9257.01 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 54084.99 | 23459.17 | 8059.50 | 0.00 | 0.00 | 8484.86 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 89016.25 | 23459.17 | 8059.50 | 5507.06 | 0.00 | 11082.12 | 0.00 | 0.00 | 43088.59 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 194069.49 | 05-JAN-12:09 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 186876.54 | 06-FEB-08:09 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 174345.22 | 19-MAR-08:09 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 149330.68 | 17-APR-07:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 77413.27 | 02-MAY-07:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 27730.88 | 22-SEP-08:20 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 144640.85 | 31-OCT-11:09 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 155030.14 | 29-NOV-17:00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 227604.68 | 21-DEC-17:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 227604.68 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.50 | 20.46 | 0.00 | 20.46 | 0.00 | 20.46 | 0.00 | 20.46 |
February | 1.50 | 20.40 | 0.50 | 20.41 | 0.00 | 20.41 | 0.00 | 20.41 |
March | 0.33 | 20.45 | 0.17 | 20.41 | 0.00 | 20.41 | 0.00 | 20.41 |
April | 0.67 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 |
May | 0.17 | 20.52 | 0.00 | 20.52 | 0.00 | 20.52 | 0.00 | 20.52 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.50 | 20.45 | 0.00 | 20.45 | 0.00 | 20.45 | 0.00 | 20.45 |
November | 0.50 | 20.44 | 0.00 | 20.44 | 0.00 | 20.44 | 0.00 | 20.44 |
December | 1.50 | 20.28 | 0.50 | 20.28 | 0.00 | 20.28 | 0.00 | 20.28 |
Annual Sum or Average | 5.67 | 20.40 | 1.17 | 20.39 | 0.00 | 20.39 | 0.00 | 20.39 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.50 | 20.52 | 0.50 | 20.52 | 0.00 | 20.52 | 0.00 | 20.52 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.17 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 |
March | 0.33 | 20.54 | 0.00 | 20.54 | 0.00 | 20.54 | 0.00 | 20.54 |
April | 0.50 | 20.50 | 0.00 | 20.50 | 0.00 | 20.50 | 0.00 | 20.50 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.33 | 20.48 | 0.00 | 20.48 | 0.00 | 20.48 | 0.00 | 20.48 |
December | 0.67 | 20.49 | 0.00 | 20.49 | 0.00 | 20.49 | 0.00 | 20.49 |
Annual Sum or Average | 2.00 | 20.50 | 0.00 | 20.50 | 0.00 | 20.50 | 0.00 | 20.50 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.67 | 20.54 | 0.00 | 20.54 | 0.00 | 20.54 | 0.00 | 20.54 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.17 | 20.49 | 0.00 | 20.49 | 0.00 | 20.49 | 0.00 | 20.49 |
Annual Sum or Average | 0.17 | 20.49 | 0.00 | 20.49 | 0.00 | 20.49 | 0.00 | 20.49 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 20.49 | 0.00 | 20.49 | 0.00 | 20.49 | 0.00 | 20.49 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.50 | 20.45 | 0.00 | 20.45 | 0.00 | 20.45 | 0.00 | 20.45 |
Annual Sum or Average | 0.50 | 20.45 | 0.00 | 20.45 | 0.00 | 20.45 | 0.00 | 20.45 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.50 | 20.45 | 0.00 | 20.45 | 0.00 | 20.45 | 0.00 | 20.45 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.83 | 20.44 | 0.00 | 20.44 | 0.00 | 20.44 | 0.00 | 20.44 |
March | 0.17 | 20.41 | 0.00 | 20.41 | 0.00 | 20.41 | 0.00 | 20.41 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.83 | 20.28 | 0.00 | 20.28 | 0.00 | 20.28 | 0.00 | 20.28 |
Annual Sum or Average | 1.83 | 20.37 | 0.00 | 20.37 | 0.00 | 20.37 | 0.00 | 20.37 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.83 | 20.44 | 0.00 | 20.44 | 0.00 | 20.44 | 0.00 | 20.44 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.50 | 20.39 | 0.00 | 20.39 | 0.00 | 20.39 | 0.00 | 20.39 |
March | 0.17 | 20.44 | 0.00 | 20.44 | 0.00 | 20.44 | 0.00 | 20.44 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.83 | 20.30 | 0.00 | 20.30 | 0.00 | 20.30 | 0.00 | 20.30 |
Annual Sum or Average | 1.50 | 20.35 | 0.00 | 20.35 | 0.00 | 20.35 | 0.00 | 20.35 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.83 | 20.44 | 0.00 | 20.44 | 0.00 | 20.44 | 0.00 | 20.44 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.83 | 20.42 | 0.00 | 20.42 | 0.00 | 20.42 | 0.00 | 20.42 |
March | 0.17 | 20.40 | 0.00 | 20.40 | 0.00 | 20.40 | 0.00 | 20.40 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.83 | 20.28 | 0.00 | 20.28 | 0.00 | 20.28 | 0.00 | 20.28 |
Annual Sum or Average | 1.83 | 20.36 | 0.00 | 20.36 | 0.00 | 20.36 | 0.00 | 20.36 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.83 | 20.42 | 0.00 | 20.42 | 0.00 | 20.42 | 0.00 | 20.42 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.33 | 20.45 | 0.00 | 20.45 | 0.00 | 20.45 | 0.00 | 20.45 |
February | 1.00 | 20.31 | 0.00 | 20.31 | 0.00 | 20.31 | 0.00 | 20.31 |
March | 0.17 | 20.26 | 0.00 | 20.26 | 0.00 | 20.26 | 0.00 | 20.26 |
April | 0.17 | 20.42 | 0.00 | 20.42 | 0.00 | 20.42 | 0.00 | 20.42 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1.00 | 20.22 | 0.00 | 20.22 | 0.00 | 20.22 | 0.00 | 20.22 |
Annual Sum or Average | 2.67 | 20.30 | 0.00 | 20.30 | 0.00 | 20.30 | 0.00 | 20.30 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.00 | 20.45 | 0.00 | 20.45 | 0.00 | 20.45 | 0.00 | 20.45 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.33 | 19.51 | 0.00 | 19.51 | 0.00 | 19.51 | 0.00 | 19.51 |
February | 5.67 | 17.42 | 0.00 | 17.42 | 0.00 | 17.42 | 0.00 | 17.42 |
March | 3.83 | 18.16 | 0.00 | 18.16 | 0.00 | 18.16 | 0.00 | 18.16 |
April | 1.33 | 20.27 | 0.00 | 20.27 | 0.00 | 20.27 | 0.00 | 20.27 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.33 | 20.20 | 0.00 | 20.20 | 0.00 | 20.20 | 0.00 | 20.20 |
November | 1.17 | 18.72 | 0.00 | 18.72 | 0.00 | 18.72 | 0.00 | 18.72 |
December | 8.67 | 16.50 | 0.00 | 16.50 | 0.00 | 16.50 | 0.00 | 16.50 |
Annual Sum or Average | 24.33 | 17.75 | 0.00 | 17.75 | 0.00 | 17.75 | 0.00 | 17.75 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 8.67 | 20.27 | 0.00 | 20.27 | 0.00 | 20.27 | 0.00 | 20.27 |
Report: ComfortReportSimple55Monthly
For: LGSTORE1
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 496.00 | 21.29 | 139.50 | 21.22 | 139.50 | 21.18 |
February | 448.00 | 21.24 | 207.00 | 21.17 | 207.00 | 21.13 |
March | 494.33 | 21.76 | 131.83 | 21.61 | 131.83 | 21.50 |
April | 478.00 | 21.81 | 98.83 | 21.68 | 98.83 | 21.60 |
May | 318.67 | 22.91 | 17.50 | 22.90 | 8.17 | 22.85 |
June | 32.67 | 23.85 | 205.00 | 23.88 | 11.33 | 23.88 |
July | 87.17 | 23.88 | 253.50 | 23.89 | 70.17 | 23.89 |
August | 33.00 | 23.88 | 286.67 | 23.89 | 18.83 | 23.89 |
September | 86.83 | 23.16 | 123.00 | 23.58 | 0.50 | 23.57 |
October | 401.00 | 22.27 | 47.50 | 22.14 | 47.50 | 22.04 |
November | 463.17 | 21.54 | 74.67 | 21.47 | 74.67 | 21.41 |
December | 496.00 | 21.32 | 231.50 | 21.22 | 231.50 | 21.17 |
Annual Sum or Average | 3834.83 | 21.83 | 1816.50 | 22.01 | 1039.83 | 21.90 |
Minimum of Months | 32.67 | 21.24 | 17.50 | 21.17 | 0.50 | 21.13 |
Maximum of Months | 496.00 | 23.88 | 286.67 | 23.89 | 231.50 | 23.89 |
Report: ComfortReportSimple55Monthly
For: SMSTORE1
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 496.00 | 21.93 | 45.67 | 21.86 | 45.67 | 21.80 |
February | 448.00 | 21.73 | 79.17 | 21.64 | 79.17 | 21.57 |
March | 473.50 | 22.19 | 34.67 | 22.12 | 34.67 | 22.06 |
April | 460.33 | 22.40 | 18.17 | 22.35 | 18.17 | 22.30 |
May | 212.17 | 23.27 | 30.67 | 23.33 | 1.50 | 23.32 |
June | 33.83 | 23.48 | 191.17 | 23.81 | 9.50 | 23.82 |
July | 73.00 | 23.72 | 240.17 | 23.83 | 54.50 | 23.84 |
August | 37.00 | 23.57 | 263.33 | 23.83 | 12.83 | 23.84 |
September | 85.17 | 23.43 | 107.00 | 23.68 | 0.00 | 23.68 |
October | 351.17 | 22.70 | 25.33 | 22.59 | 25.33 | 22.50 |
November | 445.33 | 22.18 | 18.50 | 22.14 | 18.50 | 22.10 |
December | 494.00 | 21.83 | 110.00 | 21.69 | 110.00 | 21.60 |
Annual Sum or Average | 3609.50 | 22.27 | 1163.83 | 22.47 | 409.83 | 22.40 |
Minimum of Months | 33.83 | 21.73 | 18.17 | 21.64 | 0.00 | 21.57 |
Maximum of Months | 496.00 | 23.72 | 263.33 | 23.83 | 110.00 | 23.84 |
Report: ComfortReportSimple55Monthly
For: SMSTORE2
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 371.00 | 21.53 | 60.83 | 21.47 | 60.83 | 21.43 |
February | 336.00 | 21.37 | 92.33 | 21.32 | 92.33 | 21.28 |
March | 362.67 | 21.88 | 51.50 | 21.79 | 51.50 | 21.71 |
April | 353.00 | 22.03 | 35.33 | 21.95 | 35.33 | 21.88 |
May | 186.17 | 23.04 | 18.50 | 23.11 | 2.67 | 23.08 |
June | 14.50 | 23.91 | 177.50 | 24.18 | 6.67 | 24.17 |
July | 47.00 | 24.01 | 205.67 | 24.15 | 42.67 | 24.14 |
August | 14.33 | 23.97 | 225.83 | 24.11 | 9.50 | 24.11 |
September | 48.33 | 23.14 | 102.17 | 23.87 | 0.00 | 23.87 |
October | 273.17 | 22.33 | 31.00 | 22.22 | 29.50 | 22.12 |
November | 336.83 | 21.71 | 34.67 | 21.65 | 34.67 | 21.61 |
December | 369.00 | 21.50 | 122.67 | 21.40 | 122.67 | 21.34 |
Annual Sum or Average | 2712.00 | 21.92 | 1158.00 | 22.26 | 488.33 | 22.17 |
Minimum of Months | 14.33 | 21.37 | 18.50 | 21.32 | 0.00 | 21.28 |
Maximum of Months | 371.00 | 24.01 | 225.83 | 24.18 | 122.67 | 24.17 |
Report: ComfortReportSimple55Monthly
For: SMSTORE3
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 371.00 | 21.49 | 66.83 | 21.43 | 66.83 | 21.39 |
February | 336.00 | 21.35 | 101.33 | 21.30 | 101.33 | 21.26 |
March | 372.00 | 21.90 | 58.50 | 21.79 | 58.50 | 21.71 |
April | 357.83 | 22.01 | 44.50 | 21.91 | 44.50 | 21.83 |
May | 199.83 | 23.02 | 14.83 | 23.06 | 3.33 | 23.03 |
June | 14.50 | 23.96 | 178.17 | 24.18 | 6.83 | 24.18 |
July | 47.00 | 24.03 | 206.67 | 24.15 | 43.00 | 24.14 |
August | 14.17 | 23.97 | 225.67 | 24.11 | 9.33 | 24.11 |
September | 49.17 | 23.12 | 101.83 | 23.85 | 0.00 | 23.85 |
October | 282.33 | 22.33 | 31.83 | 22.22 | 30.67 | 22.13 |
November | 340.17 | 21.69 | 40.83 | 21.62 | 40.83 | 21.57 |
December | 369.00 | 21.47 | 129.67 | 21.38 | 129.67 | 21.32 |
Annual Sum or Average | 2753.00 | 21.91 | 1200.67 | 22.23 | 534.83 | 22.14 |
Minimum of Months | 14.17 | 21.35 | 14.83 | 21.30 | 0.00 | 21.26 |
Maximum of Months | 372.00 | 24.03 | 225.67 | 24.18 | 129.67 | 24.18 |
Report: ComfortReportSimple55Monthly
For: SMSTORE4
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 371.00 | 21.44 | 76.83 | 21.38 | 76.83 | 21.34 |
February | 336.00 | 21.33 | 117.50 | 21.27 | 117.50 | 21.24 |
March | 374.83 | 21.86 | 70.17 | 21.74 | 70.17 | 21.66 |
April | 358.67 | 21.94 | 57.50 | 21.82 | 57.50 | 21.74 |
May | 222.67 | 22.98 | 11.67 | 22.98 | 4.83 | 22.95 |
June | 16.83 | 23.89 | 170.00 | 24.17 | 6.83 | 24.17 |
July | 48.17 | 24.00 | 202.50 | 24.15 | 43.50 | 24.13 |
August | 16.33 | 23.97 | 218.50 | 24.11 | 10.00 | 24.11 |
September | 54.17 | 23.12 | 96.33 | 23.81 | 0.00 | 23.81 |
October | 292.50 | 22.31 | 33.17 | 22.20 | 32.33 | 22.10 |
November | 346.17 | 21.66 | 46.50 | 21.60 | 46.50 | 21.55 |
December | 369.00 | 21.44 | 142.00 | 21.35 | 142.00 | 21.30 |
Annual Sum or Average | 2806.33 | 21.89 | 1242.67 | 22.18 | 608.00 | 22.08 |
Minimum of Months | 16.33 | 21.33 | 11.67 | 21.27 | 0.00 | 21.24 |
Maximum of Months | 374.83 | 24.00 | 218.50 | 24.17 | 142.00 | 24.17 |
Report: ComfortReportSimple55Monthly
For: LGSTORE2
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.37 | 97.33 | 21.31 | 97.33 | 21.27 |
February | 308.00 | 21.29 | 145.50 | 21.23 | 145.50 | 21.20 |
March | 348.00 | 21.81 | 109.83 | 21.64 | 109.83 | 21.54 |
April | 330.00 | 21.84 | 63.67 | 21.72 | 63.67 | 21.64 |
May | 253.50 | 23.02 | 8.67 | 22.96 | 8.17 | 22.90 |
June | 16.33 | 23.86 | 132.00 | 23.99 | 7.17 | 23.99 |
July | 48.17 | 23.93 | 172.17 | 24.01 | 44.50 | 24.00 |
August | 17.83 | 23.94 | 184.50 | 23.96 | 11.50 | 23.96 |
September | 64.33 | 23.27 | 76.67 | 23.72 | 0.00 | 23.72 |
October | 283.33 | 22.29 | 35.33 | 22.16 | 35.33 | 22.06 |
November | 325.67 | 21.63 | 55.83 | 21.55 | 55.83 | 21.50 |
December | 338.00 | 21.39 | 170.67 | 21.29 | 170.67 | 21.25 |
Annual Sum or Average | 2673.17 | 21.89 | 1252.17 | 22.06 | 749.50 | 21.94 |
Minimum of Months | 16.33 | 21.29 | 8.67 | 21.23 | 0.00 | 21.20 |
Maximum of Months | 348.00 | 23.94 | 184.50 | 24.01 | 170.67 | 24.00 |
Report: ComfortReportSimple55Monthly
For: SMSTORE5
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.49 | 98.67 | 21.41 | 98.67 | 21.35 |
February | 308.00 | 21.37 | 147.50 | 21.28 | 147.50 | 21.24 |
March | 348.00 | 21.95 | 107.50 | 21.76 | 107.50 | 21.63 |
April | 330.00 | 22.05 | 64.00 | 21.90 | 64.00 | 21.79 |
May | 255.00 | 23.32 | 9.83 | 23.26 | 8.33 | 23.20 |
June | 24.67 | 23.89 | 115.83 | 24.02 | 9.33 | 24.01 |
July | 52.00 | 23.94 | 163.00 | 24.03 | 45.00 | 24.02 |
August | 22.17 | 23.96 | 166.17 | 23.99 | 11.83 | 23.99 |
September | 74.67 | 23.51 | 61.17 | 23.81 | 0.00 | 23.81 |
October | 284.83 | 22.56 | 35.50 | 22.41 | 35.00 | 22.28 |
November | 327.17 | 21.82 | 55.50 | 21.71 | 55.50 | 21.64 |
December | 338.00 | 21.49 | 171.00 | 21.36 | 171.00 | 21.30 |
Annual Sum or Average | 2704.50 | 22.07 | 1195.67 | 22.16 | 753.67 | 22.03 |
Minimum of Months | 22.17 | 21.37 | 9.83 | 21.28 | 0.00 | 21.24 |
Maximum of Months | 348.00 | 23.96 | 171.00 | 24.03 | 171.00 | 24.02 |
Report: ComfortReportSimple55Monthly
For: SMSTORE6
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.48 | 107.00 | 21.39 | 107.00 | 21.34 |
February | 308.00 | 21.36 | 152.00 | 21.27 | 152.00 | 21.23 |
March | 348.00 | 21.94 | 115.00 | 21.73 | 115.00 | 21.61 |
April | 330.00 | 22.03 | 68.17 | 21.87 | 68.17 | 21.76 |
May | 262.00 | 23.31 | 10.50 | 23.25 | 9.17 | 23.18 |
June | 26.17 | 23.89 | 113.67 | 24.02 | 9.33 | 24.01 |
July | 53.00 | 23.94 | 162.17 | 24.03 | 45.17 | 24.02 |
August | 23.17 | 23.95 | 162.67 | 23.99 | 12.00 | 23.99 |
September | 77.33 | 23.52 | 58.83 | 23.81 | 0.00 | 23.81 |
October | 286.83 | 22.55 | 36.50 | 22.40 | 36.17 | 22.27 |
November | 327.33 | 21.80 | 59.00 | 21.70 | 59.00 | 21.62 |
December | 338.00 | 21.48 | 177.33 | 21.35 | 177.33 | 21.29 |
Annual Sum or Average | 2719.83 | 22.07 | 1222.83 | 22.14 | 790.33 | 22.01 |
Minimum of Months | 23.17 | 21.36 | 10.50 | 21.27 | 0.00 | 21.23 |
Maximum of Months | 348.00 | 23.95 | 177.33 | 24.03 | 177.33 | 24.02 |
Report: ComfortReportSimple55Monthly
For: SMSTORE7
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.42 | 129.67 | 21.33 | 129.67 | 21.28 |
February | 308.00 | 21.32 | 165.00 | 21.25 | 165.00 | 21.21 |
March | 348.00 | 21.87 | 137.50 | 21.66 | 137.50 | 21.54 |
April | 330.00 | 21.94 | 83.50 | 21.78 | 83.50 | 21.66 |
May | 290.33 | 23.24 | 16.17 | 23.13 | 15.50 | 23.04 |
June | 30.67 | 23.89 | 109.17 | 24.01 | 10.00 | 24.01 |
July | 54.83 | 23.93 | 160.50 | 24.03 | 45.50 | 24.01 |
August | 24.67 | 23.95 | 155.67 | 23.99 | 12.00 | 23.99 |
September | 85.67 | 23.51 | 57.17 | 23.79 | 0.00 | 23.79 |
October | 295.50 | 22.49 | 43.67 | 22.31 | 43.67 | 22.18 |
November | 329.33 | 21.75 | 72.00 | 21.63 | 72.00 | 21.55 |
December | 338.00 | 21.43 | 197.83 | 21.31 | 197.83 | 21.26 |
Annual Sum or Average | 2775.00 | 22.04 | 1327.83 | 22.08 | 912.17 | 21.94 |
Minimum of Months | 24.67 | 21.32 | 16.17 | 21.25 | 0.00 | 21.21 |
Maximum of Months | 348.00 | 23.95 | 197.83 | 24.03 | 197.83 | 24.01 |
Report: ComfortReportSimple55Monthly
For: SMSTORE8
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.26 | 216.33 | 21.20 | 216.33 | 21.17 |
February | 308.00 | 21.20 | 212.83 | 21.17 | 212.83 | 21.15 |
March | 348.00 | 21.63 | 207.00 | 21.43 | 207.00 | 21.35 |
April | 330.00 | 21.63 | 144.00 | 21.47 | 144.00 | 21.39 |
May | 329.00 | 22.78 | 28.83 | 22.65 | 28.83 | 22.53 |
June | 31.83 | 23.77 | 105.83 | 23.96 | 7.83 | 23.96 |
July | 57.67 | 23.87 | 162.00 | 23.99 | 46.83 | 23.97 |
August | 27.83 | 23.86 | 166.67 | 23.95 | 11.83 | 23.95 |
September | 88.00 | 23.28 | 66.50 | 23.62 | 0.83 | 23.61 |
October | 304.83 | 22.16 | 66.33 | 21.97 | 66.33 | 21.84 |
November | 330.00 | 21.52 | 114.67 | 21.42 | 114.67 | 21.35 |
December | 338.00 | 21.29 | 248.33 | 21.21 | 248.33 | 21.18 |
Annual Sum or Average | 2833.17 | 21.82 | 1739.33 | 21.87 | 1305.67 | 21.73 |
Minimum of Months | 27.83 | 21.20 | 28.83 | 21.17 | 0.83 | 21.15 |
Maximum of Months | 348.00 | 23.87 | 248.33 | 23.99 | 248.33 | 23.97 |
Report: OccupantComfortDataSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 496.00000 | 21.29057 | 20.87841 | -0.4725 | 10.47716 |
February | 448.00000 | 21.24133 | 18.31312 | -0.5194 | 11.48906 |
March | 497.00000 | 21.77524 | 18.39553 | -0.3731 | 9.68888 |
April | 479.00000 | 21.81260 | 23.47624 | -0.3277 | 8.77904 |
May | 496.00000 | 23.25918 | 27.26478 | -0.8691 | 22.85301 |
June | 481.00000 | 23.88620 | 32.11289 | -0.4974 | 10.34029 |
July | 495.00000 | 23.88754 | 35.34986 | -0.4716 | 9.83552 |
August | 497.00000 | 23.88837 | 33.07453 | -0.4728 | 9.82357 |
September | 479.00000 | 23.75694 | 25.02886 | -0.5900 | 13.23628 |
October | 496.00000 | 22.57582 | 20.66762 | -0.0940 | 7.43815 |
November | 480.00000 | 21.62479 | 22.24802 | -0.3414 | 8.79838 |
December | 496.00000 | 21.32314 | 14.56460 | -0.5218 | 11.82946 |
Annual Sum or Average | 5840.00000 | 22.53472 | 24.31448 | -0.4623 | 11.22330 |
Minimum of Months | 448.00000 | 21.24133 | 14.56460 | -0.8691 | 7.43815 |
Maximum of Months | 497.00000 | 23.88837 | 35.34986 | -0.0940 | 22.85301 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 496.00000 | 21.92611 | 22.98673 | -0.2855 | 7.85259 |
February | 448.00000 | 21.73322 | 20.25493 | -0.3597 | 8.88550 |
March | 497.00000 | 22.27378 | 19.67281 | -0.2205 | 7.65982 |
April | 479.00000 | 22.45247 | 24.51519 | -0.1502 | 7.08165 |
May | 496.00000 | 23.61101 | 26.83747 | -0.7296 | 17.44869 |
June | 481.00000 | 23.82751 | 31.97893 | -0.5088 | 10.61119 |
July | 495.00000 | 23.83189 | 35.07511 | -0.4814 | 10.06484 |
August | 497.00000 | 23.82763 | 32.68421 | -0.4902 | 10.21489 |
September | 479.00000 | 23.78164 | 25.02155 | -0.5776 | 12.47617 |
October | 496.00000 | 23.04376 | 20.96171 | 0.02607 | 6.71870 |
November | 480.00000 | 22.30216 | 23.76609 | -0.1648 | 7.07716 |
December | 496.00000 | 21.83436 | 16.40328 | -0.3635 | 9.17834 |
Annual Sum or Average | 5840.00000 | 22.87737 | 25.03790 | -0.3589 | 9.61475 |
Minimum of Months | 448.00000 | 21.73322 | 16.40328 | -0.7296 | 6.71870 |
Maximum of Months | 497.00000 | 23.83189 | 35.07511 | 0.02607 | 17.44869 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 21.53175 | 19.69921 | -0.3788 | 8.98204 |
February | 336.00000 | 21.37397 | 17.19563 | -0.4468 | 10.03459 |
March | 379.00000 | 21.96980 | 17.28647 | -0.2924 | 8.57671 |
April | 360.00000 | 22.06455 | 21.93790 | -0.2417 | 7.89709 |
May | 375.00000 | 23.48583 | 25.30435 | -0.7782 | 19.54134 |
June | 366.00000 | 24.04203 | 30.57324 | -0.4571 | 9.74091 |
July | 369.00000 | 24.05436 | 33.90464 | -0.4246 | 9.18883 |
August | 379.00000 | 24.03237 | 31.25093 | -0.4387 | 9.33364 |
September | 360.00000 | 23.90405 | 23.63021 | -0.5477 | 12.17769 |
October | 371.00000 | 22.75232 | 19.33982 | -0.0395 | 7.14726 |
November | 360.00000 | 21.84947 | 20.92462 | -0.2661 | 7.93610 |
December | 369.00000 | 21.50020 | 13.48354 | -0.4466 | 10.31797 |
Annual Sum or Average | 4395.00000 | 22.72504 | 22.92593 | -0.3966 | 10.08389 |
Minimum of Months | 336.00000 | 21.37397 | 13.48354 | -0.7782 | 7.14726 |
Maximum of Months | 379.00000 | 24.05436 | 33.90464 | -0.0395 | 19.54134 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 21.49361 | 19.73988 | -0.3969 | 9.21007 |
February | 336.00000 | 21.35207 | 17.21983 | -0.4604 | 10.24619 |
March | 379.00000 | 21.93913 | 17.32039 | -0.3070 | 8.74150 |
April | 360.00000 | 22.01764 | 22.00945 | -0.2609 | 8.06178 |
May | 375.00000 | 23.44797 | 25.37712 | -0.7979 | 20.26709 |
June | 366.00000 | 24.04142 | 30.57524 | -0.4572 | 9.74145 |
July | 369.00000 | 24.05427 | 33.90491 | -0.4237 | 9.16972 |
August | 379.00000 | 24.03189 | 31.25089 | -0.4385 | 9.32808 |
September | 360.00000 | 23.89891 | 23.63723 | -0.5502 | 12.26761 |
October | 371.00000 | 22.71793 | 19.38904 | -0.0526 | 7.20436 |
November | 360.00000 | 21.80757 | 20.97928 | -0.2836 | 8.09712 |
December | 369.00000 | 21.47476 | 13.50836 | -0.4615 | 10.55117 |
Annual Sum or Average | 4395.00000 | 22.70144 | 22.95768 | -0.4076 | 10.25186 |
Minimum of Months | 336.00000 | 21.35207 | 13.50836 | -0.7979 | 7.20436 |
Maximum of Months | 379.00000 | 24.05427 | 33.90491 | -0.0526 | 20.26709 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 21.44005 | 19.79274 | -0.4203 | 9.51934 |
February | 336.00000 | 21.32560 | 17.24859 | -0.4779 | 10.54177 |
March | 379.00000 | 21.88502 | 17.37823 | -0.3299 | 8.98870 |
April | 360.00000 | 21.94340 | 22.12242 | -0.2888 | 8.29673 |
May | 375.00000 | 23.37188 | 25.53031 | -0.8342 | 21.59158 |
June | 366.00000 | 24.03542 | 30.61907 | -0.4662 | 9.90567 |
July | 369.00000 | 24.04909 | 33.96191 | -0.4314 | 9.29481 |
August | 379.00000 | 24.02643 | 31.29385 | -0.4464 | 9.46510 |
September | 360.00000 | 23.88330 | 23.66125 | -0.5619 | 12.59216 |
October | 371.00000 | 22.65532 | 19.47808 | -0.0739 | 7.28289 |
November | 360.00000 | 21.75028 | 21.05192 | -0.3061 | 8.31466 |
December | 369.00000 | 21.43810 | 13.54351 | -0.4816 | 10.87983 |
Annual Sum or Average | 4395.00000 | 22.66192 | 23.02218 | -0.4266 | 10.56876 |
Minimum of Months | 336.00000 | 21.32560 | 13.54351 | -0.8342 | 7.28289 |
Maximum of Months | 379.00000 | 24.04909 | 33.96191 | -0.0739 | 21.59158 |
Report: OccupantComfortDataSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.36863 | 21.36483 | -0.4655 | 10.24985 |
February | 308.00000 | 21.29025 | 18.69877 | -0.5169 | 11.30362 |
March | 348.00000 | 21.80665 | 18.81861 | -0.3737 | 9.57047 |
April | 330.00000 | 21.84175 | 23.66633 | -0.3381 | 8.77111 |
May | 344.00000 | 23.25233 | 26.84488 | -0.9011 | 23.98859 |
June | 336.00000 | 23.93664 | 31.84412 | -0.5037 | 10.52589 |
July | 338.00000 | 23.96372 | 35.27563 | -0.4632 | 9.76531 |
August | 348.00000 | 23.92919 | 32.32749 | -0.4809 | 10.02643 |
September | 330.00000 | 23.81808 | 24.80272 | -0.5902 | 13.26495 |
October | 340.00000 | 22.56707 | 20.71481 | -0.1090 | 7.49015 |
November | 330.00000 | 21.66058 | 22.44962 | -0.3489 | 8.80229 |
December | 338.00000 | 21.38581 | 14.99988 | -0.5262 | 11.73807 |
Annual Sum or Average | 4030.00000 | 22.57990 | 24.36617 | -0.4683 | 11.30680 |
Minimum of Months | 308.00000 | 21.29025 | 14.99988 | -0.9011 | 7.49015 |
Maximum of Months | 348.00000 | 23.96372 | 35.27563 | -0.1090 | 23.98859 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.49301 | 21.11597 | -0.4464 | 10.06918 |
February | 308.00000 | 21.36746 | 18.49136 | -0.5061 | 11.19705 |
March | 348.00000 | 21.95483 | 18.47478 | -0.3531 | 9.38375 |
April | 330.00000 | 22.04916 | 23.16741 | -0.3073 | 8.57420 |
May | 344.00000 | 23.48516 | 26.09991 | -0.8556 | 22.05355 |
June | 336.00000 | 23.94565 | 31.88279 | -0.5224 | 10.95703 |
July | 338.00000 | 23.97344 | 35.37615 | -0.4816 | 10.17270 |
August | 348.00000 | 23.93792 | 32.36824 | -0.5006 | 10.45760 |
September | 330.00000 | 23.86584 | 24.53447 | -0.5996 | 13.35008 |
October | 340.00000 | 22.78800 | 20.14444 | -0.0775 | 7.32495 |
November | 330.00000 | 21.83446 | 22.08460 | -0.3230 | 8.62396 |
December | 338.00000 | 21.48591 | 14.75827 | -0.5100 | 11.52981 |
Annual Sum or Average | 4030.00000 | 22.69345 | 24.09013 | -0.4571 | 11.15430 |
Minimum of Months | 308.00000 | 21.36746 | 14.75827 | -0.8556 | 7.32495 |
Maximum of Months | 348.00000 | 23.97344 | 35.37615 | -0.0775 | 22.05355 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.47825 | 21.13305 | -0.4546 | 10.20196 |
February | 308.00000 | 21.35668 | 18.50463 | -0.5131 | 11.32093 |
March | 348.00000 | 21.93978 | 18.49651 | -0.3606 | 9.48194 |
April | 330.00000 | 22.03101 | 23.20049 | -0.3151 | 8.66604 |
May | 344.00000 | 23.46469 | 26.14987 | -0.8677 | 22.50261 |
June | 336.00000 | 23.94510 | 31.89156 | -0.5266 | 11.04835 |
July | 338.00000 | 23.97279 | 35.38802 | -0.4853 | 10.24553 |
August | 348.00000 | 23.93751 | 32.37646 | -0.5041 | 10.53099 |
September | 330.00000 | 23.86357 | 24.54056 | -0.6036 | 13.45855 |
October | 340.00000 | 22.77332 | 20.17258 | -0.0834 | 7.35101 |
November | 330.00000 | 21.81993 | 22.10479 | -0.3298 | 8.70726 |
December | 338.00000 | 21.47519 | 14.77077 | -0.5163 | 11.64557 |
Annual Sum or Average | 4030.00000 | 22.68320 | 24.10944 | -0.4635 | 11.27697 |
Minimum of Months | 308.00000 | 21.35668 | 14.77077 | -0.8677 | 7.35101 |
Maximum of Months | 348.00000 | 23.97279 | 35.38802 | -0.0834 | 22.50261 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.41746 | 21.19896 | -0.4854 | 10.70901 |
February | 308.00000 | 21.31771 | 18.54588 | -0.5388 | 11.79731 |
March | 348.00000 | 21.87085 | 18.58819 | -0.3923 | 9.89522 |
April | 330.00000 | 21.94461 | 23.34870 | -0.3500 | 9.07774 |
May | 344.00000 | 23.35092 | 26.41109 | -0.9253 | 24.75585 |
June | 336.00000 | 23.94353 | 31.91422 | -0.5337 | 11.20691 |
July | 338.00000 | 23.97133 | 35.41868 | -0.4907 | 10.35475 |
August | 348.00000 | 23.93661 | 32.39583 | -0.5083 | 10.62337 |
September | 330.00000 | 23.85143 | 24.56101 | -0.6134 | 13.78531 |
October | 340.00000 | 22.68531 | 20.32162 | -0.1145 | 7.50730 |
November | 330.00000 | 21.74955 | 22.19607 | -0.3594 | 9.06125 |
December | 338.00000 | 21.43297 | 14.81803 | -0.5407 | 12.10498 |
Annual Sum or Average | 4030.00000 | 22.63430 | 24.19233 | -0.4879 | 11.75571 |
Minimum of Months | 308.00000 | 21.31771 | 14.81803 | -0.9253 | 7.50730 |
Maximum of Months | 348.00000 | 23.97133 | 35.41868 | -0.1145 | 24.75585 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.25613 | 21.21257 | -0.5832 | 12.69441 |
February | 308.00000 | 21.20485 | 18.47879 | -0.6273 | 13.80891 |
March | 348.00000 | 21.62819 | 18.75516 | -0.4958 | 11.62945 |
April | 330.00000 | 21.63022 | 23.65938 | -0.4615 | 10.74154 |
May | 344.00000 | 22.82862 | 27.62693 | -1.1138 | 33.07411 |
June | 336.00000 | 23.92245 | 31.83255 | -0.5377 | 11.29231 |
July | 338.00000 | 23.95516 | 35.33982 | -0.4909 | 10.33914 |
August | 348.00000 | 23.92265 | 32.25824 | -0.4997 | 10.45631 |
September | 330.00000 | 23.77446 | 24.70784 | -0.6282 | 14.58641 |
October | 340.00000 | 22.33952 | 20.87567 | -0.2139 | 8.40303 |
November | 330.00000 | 21.52461 | 22.34911 | -0.4502 | 10.44930 |
December | 338.00000 | 21.29121 | 14.82182 | -0.6261 | 14.02741 |
Annual Sum or Average | 4030.00000 | 22.45068 | 24.37830 | -0.5608 | 13.48045 |
Minimum of Months | 308.00000 | 21.20485 | 14.82182 | -1.1138 | 8.40303 |
Maximum of Months | 348.00000 | 23.95516 | 35.33982 | -0.2139 | 33.07411 |
Report: DXReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 7941317.63 | 2191850.99 | 2.67 | 7941317.63 | -0.0 | 0.00 | 0.13 | 20-JAN-14:00 | 0.00 | 01-JAN-00:10 | 1821.27 | 20-JAN-14:00 | 1821.27 | 20-JAN-14:00 | 0.00 | 20-JAN-14:00 | 498.02 | 20-JAN-14:00 | 0.00 | 01-JAN-00:10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 |
March | 0.308091E+09 | 80979451.15 | 21.50 | 0.308091E+09 | 0.00 | 0.00 | 0.53 | 14-MAR-13:00 | 0.00 | 01-MAR-00:10 | 8184.49 | 14-MAR-13:00 | 8184.49 | 14-MAR-13:00 | 0.00 | 14-MAR-12:10 | 2116.22 | 14-MAR-13:00 | 0.00 | 01-MAR-00:10 |
April | 43393318.56 | 11955397.87 | 10.83 | 43393318.56 | 0.00 | 0.00 | 0.23 | 20-APR-13:00 | 0.00 | 01-APR-00:05 | 3337.58 | 20-APR-13:00 | 3337.58 | 20-APR-13:00 | 0.00 | 20-APR-13:30 | 902.50 | 20-APR-13:00 | 0.00 | 01-APR-00:05 |
May | 0.230098E+10 | 0.615834E+09 | 145.86 | 0.228196E+10 | 19017989.12 | 0.00 | 0.75 | 17-MAY-14:00 | 0.00 | 01-MAY-00:05 | 11791.70 | 17-MAY-14:00 | 11791.70 | 17-MAY-14:00 | 690.14 | 31-MAY-19:00 | 3185.05 | 17-MAY-14:00 | 0.00 | 01-MAY-00:05 |
June | 0.146433E+11 | 0.392669E+10 | 424.43 | 0.139730E+11 | 0.670284E+09 | 0.00 | 1.00 | 13-JUN-12:20 | 0.00 | 01-JUN-00:10 | 27273.46 | 14-JUN-07:03 | 27273.46 | 14-JUN-07:03 | 4274.82 | 18-JUN-12:10 | 7118.14 | 26-JUN-15:00 | 0.00 | 01-JUN-00:10 |
July | 0.157846E+11 | 0.420528E+10 | 445.20 | 0.148341E+11 | 0.950529E+09 | 0.00 | 1.00 | 01-JUL-07:03 | 0.00 | 01-JUL-00:02 | 35291.19 | 18-JUL-07:02 | 35291.19 | 18-JUL-07:02 | 6087.87 | 24-JUL-07:03 | 7942.97 | 16-JUL-07:02 | 0.00 | 01-JUL-00:02 |
August | 0.150718E+11 | 0.396557E+10 | 442.26 | 0.143765E+11 | 0.695318E+09 | 0.00 | 1.00 | 03-AUG-07:03 | 0.00 | 01-AUG-00:10 | 27755.38 | 03-AUG-07:03 | 22001.12 | 16-AUG-16:10 | 6792.03 | 04-AUG-07:03 | 6615.29 | 16-AUG-14:00 | 0.00 | 01-AUG-00:10 |
September | 0.103041E+11 | 0.266928E+10 | 348.59 | 0.101774E+11 | 0.126742E+09 | 0.00 | 1.00 | 03-SEP-07:03 | 0.00 | 01-SEP-00:05 | 23447.87 | 13-SEP-07:03 | 21353.46 | 13-SEP-07:03 | 3004.55 | 03-SEP-07:03 | 5130.05 | 09-SEP-13:00 | 0.00 | 01-SEP-00:05 |
October | 0.117193E+10 | 0.299577E+09 | 71.67 | 0.117172E+10 | 219513.48 | 0.00 | 0.84 | 11-OCT-14:00 | 0.00 | 01-OCT-00:10 | 13797.63 | 11-OCT-14:00 | 13797.63 | 11-OCT-14:00 | 29.84 | 01-OCT-14:20 | 3465.03 | 11-OCT-14:00 | 0.00 | 01-OCT-00:10 |
November | 0.181555E+09 | 48450806.44 | 20.50 | 0.181555E+09 | 0.00 | 0.00 | 0.42 | 07-NOV-15:00 | 0.00 | 01-NOV-00:03 | 6334.42 | 07-NOV-15:00 | 6334.42 | 07-NOV-15:00 | 0.00 | 07-NOV-15:30 | 1627.47 | 07-NOV-15:00 | 0.00 | 01-NOV-00:03 |
December | 19325938.96 | 5337598.94 | 4.33 | 19325938.96 | 0.00 | 0.00 | 0.20 | 02-DEC-15:00 | 0.00 | 01-DEC-00:03 | 2882.16 | 02-DEC-15:00 | 2882.16 | 02-DEC-15:00 | 0.00 | 02-DEC-14:30 | 785.62 | 02-DEC-15:00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.598370E+11 | 0.158311E+11 | 1937.84 | 0.573749E+11 | 0.246211E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.157846E+11 | 0.420528E+10 | 445.20 | 0.148341E+11 | 0.950529E+09 | 0.00 | 1.00 | 0.00 | 35291.19 | 35291.19 | 6792.03 | 7942.97 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 15602869.25 | 4217092.98 | 7.44 | 15589789.76 | 13079.49 | 0.00 | 0.25 | 20-JAN-14:00 | 0.00 | 01-JAN-00:10 | 1972.85 | 20-JAN-14:00 | 1972.85 | 20-JAN-14:00 | 17.08 | 22-JAN-19:00 | 522.42 | 20-JAN-14:00 | 0.00 | 01-JAN-00:10 |
February | 6150512.82 | 1685508.58 | 3.56 | 6124850.26 | 25662.56 | 0.00 | 0.33 | 26-FEB-18:10 | 0.00 | 01-FEB-00:05 | 2597.39 | 26-FEB-18:10 | 2597.39 | 26-FEB-18:10 | 33.43 | 19-FEB-20:30 | 674.31 | 26-FEB-18:10 | 0.00 | 01-FEB-00:05 |
March | 0.256157E+09 | 65777083.90 | 35.02 | 0.256147E+09 | 10248.88 | 0.00 | 1.00 | 12-MAR-17:02 | 0.00 | 01-MAR-00:10 | 19535.15 | 12-MAR-17:08 | 19535.15 | 12-MAR-17:08 | 13.55 | 17-MAR-21:20 | 4135.93 | 12-MAR-17:08 | 0.00 | 01-MAR-00:10 |
April | 70070063.43 | 19040989.29 | 24.31 | 69901741.12 | 168322.31 | 0.00 | 0.33 | 20-APR-13:00 | 0.00 | 01-APR-00:05 | 2589.10 | 20-APR-13:00 | 2589.10 | 20-APR-13:00 | 184.83 | 13-APR-20:10 | 682.86 | 20-APR-13:00 | 0.00 | 01-APR-00:05 |
May | 0.174339E+10 | 0.450312E+09 | 163.79 | 0.171604E+10 | 27351085.02 | 0.00 | 1.00 | 06-MAY-18:01 | 0.00 | 01-MAY-00:05 | 19673.30 | 31-MAY-20:55 | 19535.15 | 06-MAY-18:07 | 4354.79 | 31-MAY-20:55 | 4171.35 | 31-MAY-20:55 | 0.00 | 01-MAY-00:05 |
June | 0.889492E+10 | 0.232019E+10 | 399.01 | 0.842228E+10 | 0.472645E+09 | 0.00 | 1.00 | 01-JUN-20:01 | 0.00 | 01-JUN-00:10 | 20942.26 | 17-JUN-18:40 | 19535.15 | 12-JUN-21:25 | 8273.75 | 21-JUN-20:10 | 4628.97 | 17-JUN-18:40 | 0.00 | 01-JUN-00:10 |
July | 0.963369E+10 | 0.249940E+10 | 424.91 | 0.894444E+10 | 0.689253E+09 | 0.00 | 1.00 | 01-JUL-07:03 | 0.00 | 01-JUL-00:02 | 21587.23 | 29-JUL-18:03 | 19646.94 | 18-JUL-07:02 | 11290.51 | 30-JUL-19:30 | 4660.90 | 29-JUL-18:03 | 0.00 | 01-JUL-00:02 |
August | 0.926253E+10 | 0.236732E+10 | 415.47 | 0.874308E+10 | 0.519449E+09 | 0.00 | 1.00 | 01-AUG-20:01 | 0.00 | 01-AUG-00:10 | 21171.02 | 03-AUG-22:34 | 19576.01 | 26-AUG-19:32 | 9376.72 | 04-AUG-22:50 | 4559.06 | 25-AUG-22:10 | 0.00 | 01-AUG-00:10 |
September | 0.641742E+10 | 0.161802E+10 | 335.67 | 0.630888E+10 | 0.108536E+09 | 0.00 | 1.00 | 01-SEP-20:02 | 0.00 | 01-SEP-00:05 | 20151.49 | 02-SEP-19:58 | 19535.15 | 07-SEP-20:01 | 4987.77 | 03-SEP-21:57 | 4421.80 | 02-SEP-19:18 | 0.00 | 01-SEP-00:05 |
October | 0.821856E+09 | 0.207254E+09 | 85.45 | 0.820652E+09 | 1204049.03 | 0.00 | 1.00 | 07-OCT-18:01 | 0.00 | 01-OCT-00:10 | 19535.15 | 07-OCT-18:07 | 19535.15 | 09-OCT-17:01 | 1348.31 | 08-OCT-18:27 | 4135.93 | 07-OCT-18:07 | 0.00 | 01-OCT-00:10 |
November | 0.162803E+09 | 42776065.43 | 28.19 | 0.162625E+09 | 177580.00 | 0.00 | 0.49 | 07-NOV-14:40 | 0.00 | 01-NOV-00:03 | 4095.43 | 07-NOV-14:40 | 4095.43 | 07-NOV-14:40 | 129.91 | 09-NOV-23:30 | 1031.18 | 07-NOV-14:40 | 0.00 | 01-NOV-00:03 |
December | 32938041.88 | 8918780.10 | 9.28 | 32938041.88 | -0.0 | 0.00 | 0.35 | 03-DEC-18:20 | 0.00 | 01-DEC-00:03 | 2842.37 | 03-DEC-18:20 | 2842.37 | 03-DEC-18:20 | 0.00 | 17-DEC-18:20 | 732.28 | 03-DEC-18:20 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.373175E+11 | 0.960493E+10 | 1932.09 | 0.354987E+11 | 0.181883E+10 | 0.00 | ||||||||||||||
Minimum of Months | 6150512.82 | 1685508.58 | 3.56 | 6124850.26 | -0.0 | 0.00 | 0.25 | 0.00 | 1972.85 | 1972.85 | 0.00 | 522.42 | 0.00 | |||||||
Maximum of Months | 0.963369E+10 | 0.249940E+10 | 424.91 | 0.894444E+10 | 0.689253E+09 | 0.00 | 1.00 | 0.00 | 21587.23 | 19646.94 | 11290.51 | 4660.90 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_3:3 COOLING COIL
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 8086374.24 | 2213312.54 | 3.67 | 8086374.24 | -0.0 | 0.00 | 0.17 | 20-JAN-14:00 | 0.00 | 01-JAN-00:10 | 1347.26 | 20-JAN-14:00 | 1347.26 | 20-JAN-14:00 | 0.00 | 20-JAN-14:20 | 364.77 | 20-JAN-14:00 | 0.00 | 01-JAN-00:10 |
February | 2161608.69 | 601515.32 | 1.50 | 2161608.69 | -0.0 | 0.00 | 0.09 | 18-FEB-14:00 | 0.00 | 01-FEB-00:05 | 674.13 | 18-FEB-14:00 | 674.13 | 18-FEB-14:00 | 0.00 | 01-FEB-00:05 | 186.45 | 18-FEB-14:00 | 0.00 | 01-FEB-00:05 |
March | 0.203527E+09 | 53067289.56 | 24.00 | 0.203527E+09 | -0.0 | 0.00 | 0.59 | 14-MAR-13:00 | 0.00 | 01-MAR-00:10 | 5175.98 | 14-MAR-13:00 | 5175.98 | 14-MAR-13:00 | 0.00 | 13-MAR-16:40 | 1317.95 | 14-MAR-13:00 | 0.00 | 01-MAR-00:10 |
April | 38285556.59 | 10486405.02 | 14.33 | 38285556.59 | -0.0 | 0.00 | 0.28 | 20-APR-13:00 | 0.00 | 01-APR-00:05 | 2309.00 | 20-APR-13:00 | 2309.00 | 20-APR-13:00 | 0.00 | 20-APR-13:20 | 616.41 | 20-APR-13:00 | 0.00 | 01-APR-00:05 |
May | 0.132238E+10 | 0.353368E+09 | 137.33 | 0.131408E+10 | 8299260.21 | 0.00 | 0.73 | 17-MAY-13:00 | 0.00 | 01-MAY-00:05 | 6505.05 | 17-MAY-13:00 | 6505.05 | 17-MAY-13:00 | 320.93 | 30-MAY-17:10 | 1766.21 | 17-MAY-13:00 | 0.00 | 01-MAY-00:05 |
June | 0.666531E+10 | 0.180789E+10 | 337.57 | 0.637195E+10 | 0.293355E+09 | 0.00 | 1.00 | 13-JUN-13:20 | 0.00 | 01-JUN-00:10 | 16974.06 | 25-JUN-07:03 | 16974.06 | 25-JUN-07:03 | 4224.97 | 18-JUN-07:03 | 3941.41 | 25-JUN-07:03 | 0.00 | 01-JUN-00:10 |
July | 0.710824E+10 | 0.191141E+10 | 343.08 | 0.669199E+10 | 0.416257E+09 | 0.00 | 1.00 | 01-JUL-06:03 | 0.00 | 01-JUL-00:02 | 20335.38 | 18-JUL-06:02 | 20335.38 | 18-JUL-06:02 | 5475.11 | 24-JUL-06:03 | 4755.25 | 16-JUL-07:02 | 0.00 | 01-JUL-00:02 |
August | 0.677508E+10 | 0.180252E+10 | 342.46 | 0.651403E+10 | 0.261051E+09 | 0.00 | 1.00 | 03-AUG-06:03 | 0.00 | 01-AUG-00:10 | 15919.61 | 20-AUG-07:03 | 13221.60 | 20-AUG-07:03 | 5075.00 | 04-AUG-06:03 | 3418.78 | 16-AUG-14:00 | 0.00 | 01-AUG-00:10 |
September | 0.482685E+10 | 0.126165E+10 | 290.20 | 0.477874E+10 | 48106659.69 | 0.00 | 1.00 | 03-SEP-07:03 | 0.00 | 01-SEP-00:05 | 16468.43 | 11-SEP-06:02 | 16468.43 | 11-SEP-06:02 | 1732.61 | 03-SEP-07:03 | 3487.78 | 11-SEP-06:02 | 0.00 | 01-SEP-00:05 |
October | 0.632585E+09 | 0.162667E+09 | 72.17 | 0.632497E+09 | 87515.58 | 0.00 | 0.80 | 11-OCT-14:00 | 0.00 | 01-OCT-00:10 | 7370.29 | 11-OCT-14:00 | 7370.29 | 11-OCT-14:00 | 56.87 | 01-OCT-07:10 | 1873.40 | 11-OCT-14:00 | 0.00 | 01-OCT-00:10 |
November | 0.112377E+09 | 29923016.24 | 21.00 | 0.112377E+09 | 0.00 | 0.00 | 0.43 | 07-NOV-14:00 | 0.00 | 01-NOV-00:03 | 3665.48 | 07-NOV-14:00 | 3665.48 | 07-NOV-14:00 | 0.00 | 07-NOV-14:20 | 939.66 | 07-NOV-14:00 | 0.00 | 01-NOV-00:03 |
December | 18339311.68 | 5016431.96 | 6.50 | 18339311.68 | 0.00 | 0.00 | 0.25 | 02-DEC-15:00 | 0.00 | 01-DEC-00:03 | 2055.35 | 02-DEC-15:00 | 2055.35 | 02-DEC-15:00 | 0.00 | 01-DEC-14:00 | 552.98 | 02-DEC-15:00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.277132E+11 | 0.740082E+10 | 1593.81 | 0.266861E+11 | 0.102716E+10 | 0.00 | ||||||||||||||
Minimum of Months | 2161608.69 | 601515.32 | 1.50 | 2161608.69 | -0.0 | 0.00 | 0.09 | 0.00 | 674.13 | 674.13 | 0.00 | 186.45 | 0.00 | |||||||
Maximum of Months | 0.710824E+10 | 0.191141E+10 | 343.08 | 0.669199E+10 | 0.416257E+09 | 0.00 | 1.00 | 0.00 | 20335.38 | 20335.38 | 5475.11 | 4755.25 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_4:4 COOLING COIL
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 6382276.08 | 1754285.90 | 3.33 | 6382276.08 | 0.00 | 0.00 | 0.15 | 20-JAN-14:00 | 0.00 | 01-JAN-00:10 | 1165.87 | 20-JAN-14:00 | 1165.87 | 20-JAN-14:00 | 0.00 | 20-JAN-14:20 | 317.39 | 20-JAN-14:00 | 0.00 | 01-JAN-00:10 |
February | 1406983.13 | 392870.55 | 1.33 | 1406983.13 | -0.0 | 0.00 | 0.07 | 18-FEB-14:00 | 0.00 | 01-FEB-00:05 | 529.97 | 18-FEB-14:00 | 529.97 | 18-FEB-14:00 | 0.00 | 18-FEB-13:20 | 147.24 | 18-FEB-14:00 | 0.00 | 01-FEB-00:05 |
March | 0.193027E+09 | 50455946.16 | 22.33 | 0.193027E+09 | 0.00 | 0.00 | 0.58 | 14-MAR-13:00 | 0.00 | 01-MAR-00:10 | 5041.51 | 14-MAR-13:00 | 5041.51 | 14-MAR-13:00 | 0.00 | 14-MAR-13:20 | 1287.57 | 14-MAR-13:00 | 0.00 | 01-MAR-00:10 |
April | 30665252.43 | 8426601.60 | 11.67 | 30665252.43 | 0.00 | 0.00 | 0.26 | 20-APR-13:00 | 0.00 | 01-APR-00:05 | 2148.50 | 20-APR-13:00 | 2148.50 | 20-APR-13:00 | 0.00 | 20-APR-12:40 | 576.17 | 20-APR-13:00 | 0.00 | 01-APR-00:05 |
May | 0.126873E+10 | 0.339809E+09 | 135.00 | 0.126146E+10 | 7266620.17 | 0.00 | 0.73 | 17-MAY-13:00 | 0.00 | 01-MAY-00:05 | 6432.40 | 17-MAY-13:00 | 6432.40 | 17-MAY-13:00 | 287.34 | 30-MAY-17:10 | 1748.29 | 17-MAY-13:00 | 0.00 | 01-MAY-00:05 |
June | 0.666637E+10 | 0.180679E+10 | 337.07 | 0.637360E+10 | 0.292768E+09 | 0.00 | 1.00 | 13-JUN-13:20 | 0.00 | 01-JUN-00:10 | 17422.03 | 25-JUN-07:03 | 17422.03 | 25-JUN-07:03 | 4320.71 | 18-JUN-07:03 | 4045.23 | 25-JUN-07:03 | 0.00 | 01-JUN-00:10 |
July | 0.712632E+10 | 0.191413E+10 | 343.11 | 0.671032E+10 | 0.416001E+09 | 0.00 | 1.00 | 01-JUL-06:03 | 0.00 | 01-JUL-00:02 | 20224.11 | 18-JUL-06:02 | 20224.11 | 18-JUL-06:02 | 5662.84 | 24-JUL-06:03 | 4731.61 | 16-JUL-07:02 | 0.00 | 01-JUL-00:02 |
August | 0.678244E+10 | 0.180271E+10 | 342.79 | 0.652041E+10 | 0.262028E+09 | 0.00 | 1.00 | 03-AUG-06:03 | 0.00 | 01-AUG-00:10 | 16285.35 | 20-AUG-07:03 | 13541.06 | 20-AUG-07:03 | 5220.18 | 04-AUG-06:03 | 3467.44 | 20-AUG-07:03 | 0.00 | 01-AUG-00:10 |
September | 0.482100E+10 | 0.125916E+10 | 289.45 | 0.477224E+10 | 48755909.58 | 0.00 | 1.00 | 03-SEP-07:03 | 0.00 | 01-SEP-00:05 | 17309.29 | 11-SEP-06:02 | 17309.29 | 11-SEP-06:02 | 1756.12 | 03-SEP-07:03 | 3665.53 | 11-SEP-06:02 | 0.00 | 01-SEP-00:05 |
October | 0.610178E+09 | 0.156930E+09 | 70.50 | 0.610110E+09 | 67919.64 | 0.00 | 0.80 | 11-OCT-14:00 | 0.00 | 01-OCT-00:10 | 7318.78 | 11-OCT-14:00 | 7318.78 | 11-OCT-14:00 | 40.51 | 01-OCT-07:10 | 1860.83 | 11-OCT-14:00 | 0.00 | 01-OCT-00:10 |
November | 98679746.63 | 26378643.08 | 20.33 | 98679746.63 | 0.00 | 0.00 | 0.41 | 07-NOV-14:00 | 0.00 | 01-NOV-00:03 | 3462.37 | 07-NOV-14:00 | 3462.37 | 07-NOV-14:00 | 0.00 | 07-NOV-14:00 | 892.39 | 07-NOV-14:00 | 0.00 | 01-NOV-00:03 |
December | 14929432.87 | 4092869.48 | 5.50 | 14929432.87 | 0.00 | 0.00 | 0.24 | 02-DEC-15:00 | 0.00 | 01-DEC-00:03 | 1902.03 | 02-DEC-15:00 | 1902.03 | 02-DEC-15:00 | 0.00 | 02-DEC-13:40 | 513.98 | 02-DEC-15:00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.276201E+11 | 0.737105E+10 | 1582.42 | 0.265932E+11 | 0.102689E+10 | 0.00 | ||||||||||||||
Minimum of Months | 1406983.13 | 392870.55 | 1.33 | 1406983.13 | -0.0 | 0.00 | 0.07 | 0.00 | 529.97 | 529.97 | 0.00 | 147.24 | 0.00 | |||||||
Maximum of Months | 0.712632E+10 | 0.191413E+10 | 343.11 | 0.671032E+10 | 0.416001E+09 | 0.00 | 1.00 | 0.00 | 20224.11 | 20224.11 | 5662.84 | 4731.61 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_5:5 COOLING COIL
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 3855842.36 | 1068290.81 | 3.00 | 3855842.36 | 0.00 | 0.00 | 0.11 | 20-JAN-14:00 | 0.00 | 01-JAN-00:10 | 857.84 | 20-JAN-14:00 | 857.84 | 20-JAN-14:00 | 0.00 | 20-JAN-13:50 | 235.82 | 20-JAN-14:00 | 0.00 | 01-JAN-00:10 |
February | 386874.61 | 108653.35 | 0.67 | 386874.61 | -0.0 | 0.00 | 0.03 | 18-FEB-14:00 | 0.00 | 01-FEB-00:05 | 260.63 | 18-FEB-14:00 | 260.63 | 18-FEB-14:00 | 0.00 | 18-FEB-13:50 | 73.05 | 18-FEB-14:00 | 0.00 | 01-FEB-00:05 |
March | 0.173050E+09 | 45524702.12 | 20.50 | 0.173050E+09 | 0.00 | 0.00 | 0.55 | 14-MAR-13:00 | 0.00 | 01-MAR-00:10 | 4770.78 | 14-MAR-13:00 | 4770.78 | 14-MAR-13:00 | 0.00 | 14-MAR-13:00 | 1227.53 | 14-MAR-13:00 | 0.00 | 01-MAR-00:10 |
April | 19070421.45 | 5271937.97 | 9.83 | 19070421.45 | 0.00 | 0.00 | 0.23 | 20-APR-13:00 | 0.00 | 01-APR-00:05 | 1838.58 | 20-APR-13:00 | 1838.58 | 20-APR-13:00 | 0.00 | 19-APR-14:00 | 497.75 | 20-APR-13:00 | 0.00 | 01-APR-00:05 |
May | 0.115313E+10 | 0.310786E+09 | 128.67 | 0.114766E+10 | 5465149.06 | 0.00 | 0.71 | 17-MAY-13:00 | 0.00 | 01-MAY-00:05 | 6218.46 | 17-MAY-13:00 | 6218.46 | 17-MAY-13:00 | 256.68 | 31-MAY-19:00 | 1699.73 | 17-MAY-13:00 | 0.00 | 01-MAY-00:05 |
June | 0.646912E+10 | 0.176031E+10 | 335.49 | 0.619067E+10 | 0.278454E+09 | 0.00 | 1.00 | 13-JUN-13:30 | 0.00 | 01-JUN-00:10 | 15798.79 | 25-JUN-07:03 | 15798.79 | 25-JUN-07:03 | 3592.76 | 18-JUN-07:03 | 3690.73 | 26-JUN-15:00 | 0.00 | 01-JUN-00:10 |
July | 0.693031E+10 | 0.186846E+10 | 341.58 | 0.653408E+10 | 0.396238E+09 | 0.00 | 1.00 | 09-JUL-14:00 | 0.00 | 01-JUL-00:02 | 20067.81 | 17-JUL-06:02 | 20067.81 | 17-JUL-06:02 | 5232.90 | 24-JUL-06:03 | 4713.60 | 16-JUL-07:02 | 0.00 | 01-JUL-00:02 |
August | 0.659788E+10 | 0.176015E+10 | 341.26 | 0.634800E+10 | 0.249874E+09 | 0.00 | 1.00 | 03-AUG-06:03 | 0.00 | 01-AUG-00:10 | 15047.29 | 20-AUG-07:03 | 12470.55 | 20-AUG-07:03 | 4222.68 | 04-AUG-06:03 | 3372.34 | 16-AUG-14:00 | 0.00 | 01-AUG-00:10 |
September | 0.466624E+10 | 0.122333E+10 | 285.56 | 0.462036E+10 | 45880336.97 | 0.00 | 1.00 | 03-SEP-07:03 | 0.00 | 01-SEP-00:05 | 16207.26 | 11-SEP-06:02 | 16207.26 | 11-SEP-06:02 | 1651.12 | 03-SEP-07:03 | 3432.51 | 11-SEP-06:02 | 0.00 | 01-SEP-00:05 |
October | 0.559303E+09 | 0.144150E+09 | 63.50 | 0.559287E+09 | 16445.82 | 0.00 | 0.78 | 11-OCT-14:00 | 0.00 | 01-OCT-00:10 | 7157.60 | 11-OCT-14:00 | 7157.60 | 11-OCT-14:00 | 4.53 | 09-OCT-11:00 | 1827.05 | 11-OCT-14:00 | 0.00 | 01-OCT-00:10 |
November | 79217187.26 | 21296543.17 | 18.83 | 79217187.26 | -0.0 | 0.00 | 0.38 | 07-NOV-14:00 | 0.00 | 01-NOV-00:03 | 3162.45 | 07-NOV-14:00 | 3162.45 | 07-NOV-14:00 | 0.00 | 07-NOV-15:00 | 822.22 | 07-NOV-14:00 | 0.00 | 01-NOV-00:03 |
December | 10254718.55 | 2826545.91 | 4.33 | 10254718.55 | -0.0 | 0.00 | 0.20 | 02-DEC-15:00 | 0.00 | 01-DEC-00:03 | 1623.67 | 02-DEC-15:00 | 1623.67 | 02-DEC-15:00 | 0.00 | 02-DEC-13:50 | 442.53 | 02-DEC-15:00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.266618E+11 | 0.714330E+10 | 1553.22 | 0.256859E+11 | 0.975928E+09 | 0.00 | ||||||||||||||
Minimum of Months | 386874.61 | 108653.35 | 0.67 | 386874.61 | -0.0 | 0.00 | 0.03 | 0.00 | 260.63 | 260.63 | 0.00 | 73.05 | 0.00 | |||||||
Maximum of Months | 0.693031E+10 | 0.186846E+10 | 341.58 | 0.653408E+10 | 0.396238E+09 | 0.00 | 1.00 | 0.00 | 20067.81 | 20067.81 | 5232.90 | 4713.60 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_6:6 COOLING COIL
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 3752462.14 | 1042038.64 | 1.33 | 3752462.14 | -0.0 | 0.00 | 0.09 | 20-JAN-14:00 | 0.00 | 01-JAN-00:10 | 1141.16 | 20-JAN-14:00 | 1141.16 | 20-JAN-14:00 | 0.00 | 01-JAN-00:10 | 315.54 | 20-JAN-14:00 | 0.00 | 01-JAN-00:10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 |
March | 0.278993E+09 | 73387220.44 | 18.50 | 0.278993E+09 | -0.0 | 0.00 | 0.56 | 14-MAR-13:00 | 0.00 | 01-MAR-00:10 | 8144.77 | 14-MAR-13:00 | 8144.77 | 14-MAR-13:00 | 0.00 | 13-MAR-14:40 | 2092.19 | 14-MAR-13:00 | 0.00 | 01-MAR-00:10 |
April | 22621381.34 | 6285065.22 | 8.00 | 22621381.34 | -0.0 | 0.00 | 0.21 | 20-APR-13:00 | 0.00 | 01-APR-00:05 | 2825.82 | 20-APR-13:00 | 2825.82 | 20-APR-13:00 | 0.00 | 20-APR-13:00 | 768.94 | 20-APR-13:00 | 0.00 | 01-APR-00:05 |
May | 0.183870E+10 | 0.495754E+09 | 117.50 | 0.183004E+10 | 8654974.33 | 0.00 | 0.73 | 17-MAY-13:00 | 0.00 | 01-MAY-00:05 | 10959.38 | 17-MAY-13:00 | 10959.38 | 17-MAY-13:00 | 369.86 | 31-MAY-18:40 | 2975.39 | 17-MAY-13:00 | 0.00 | 01-MAY-00:05 |
June | 0.113918E+11 | 0.308636E+10 | 328.56 | 0.108930E+11 | 0.498803E+09 | 0.00 | 1.00 | 13-JUN-12:10 | 0.00 | 01-JUN-00:10 | 33382.48 | 25-JUN-08:62 | 33382.48 | 25-JUN-08:62 | 6282.63 | 18-JUN-08:63 | 8132.52 | 25-JUN-08:62 | 0.00 | 01-JUN-00:10 |
July | 0.121060E+11 | 0.324363E+10 | 328.77 | 0.114137E+11 | 0.692306E+09 | 0.00 | 1.00 | 01-JUL-07:03 | 0.00 | 01-JUL-00:02 | 35531.89 | 24-JUL-07:03 | 34340.32 | 18-JUL-07:02 | 6780.44 | 24-JUL-07:03 | 8485.08 | 16-JUL-08:62 | 0.00 | 01-JUL-00:02 |
August | 0.117587E+11 | 0.311829E+10 | 336.06 | 0.112924E+11 | 0.466248E+09 | 0.00 | 1.00 | 03-AUG-07:03 | 0.00 | 01-AUG-00:10 | 31958.06 | 20-AUG-08:62 | 29511.99 | 20-AUG-08:62 | 6837.54 | 04-AUG-07:03 | 7072.66 | 20-AUG-08:62 | 0.00 | 01-AUG-00:10 |
September | 0.806596E+10 | 0.210118E+10 | 280.50 | 0.798505E+10 | 80907669.91 | 0.00 | 1.00 | 03-SEP-08:62 | 0.00 | 01-SEP-00:05 | 25896.21 | 11-SEP-07:03 | 25896.21 | 11-SEP-07:03 | 2674.28 | 03-SEP-08:62 | 5585.08 | 10-SEP-08:62 | 0.00 | 01-SEP-00:05 |
October | 0.944156E+09 | 0.241879E+09 | 59.67 | 0.944074E+09 | 81857.99 | 0.00 | 0.83 | 11-OCT-14:10 | 0.00 | 01-OCT-00:10 | 12904.04 | 11-OCT-14:10 | 12904.04 | 11-OCT-14:10 | 25.23 | 01-OCT-14:30 | 3239.11 | 11-OCT-14:10 | 0.00 | 01-OCT-00:10 |
November | 0.118396E+09 | 31870990.36 | 16.67 | 0.118396E+09 | -0.0 | 0.00 | 0.37 | 07-NOV-14:00 | 0.00 | 01-NOV-00:03 | 5153.62 | 07-NOV-14:00 | 5153.62 | 07-NOV-14:00 | 0.00 | 06-NOV-13:50 | 1344.22 | 07-NOV-14:00 | 0.00 | 01-NOV-00:03 |
December | 12330117.29 | 3404695.09 | 3.00 | 12330117.29 | 0.00 | 0.00 | 0.19 | 02-DEC-15:00 | 0.00 | 01-DEC-00:03 | 2525.69 | 02-DEC-15:00 | 2525.69 | 02-DEC-15:00 | 0.00 | 02-DEC-15:00 | 691.12 | 02-DEC-15:00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.465414E+11 | 0.124031E+11 | 1498.55 | 0.447944E+11 | 0.174700E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.121060E+11 | 0.324363E+10 | 336.06 | 0.114137E+11 | 0.692306E+09 | 0.00 | 1.00 | 0.00 | 35531.89 | 34340.32 | 6837.54 | 8485.08 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_7:7 COOLING COIL
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 1526489.69 | 370856.46 | 2.33 | 1526489.69 | 0.00 | 0.00 | 0.07 | 20-JAN-14:00 | 0.00 | 01-JAN-00:10 | 539.86 | 20-JAN-14:00 | 539.86 | 20-JAN-14:00 | 0.00 | 20-JAN-13:30 | 130.62 | 20-JAN-14:00 | 0.00 | 01-JAN-00:10 |
February | 120.20 | 29.63 | 0.50 | 120.20 | 0.00 | 0.00 | 0.00 | 26-FEB-13:20 | 0.00 | 01-FEB-00:05 | 0.11 | 26-FEB-13:20 | 0.11 | 26-FEB-13:20 | 0.00 | 26-FEB-13:20 | 0.03 | 26-FEB-13:20 | 0.00 | 01-FEB-00:05 |
March | 0.156011E+09 | 35603308.44 | 19.75 | 0.156011E+09 | -0.0 | 0.00 | 0.60 | 14-MAR-13:00 | 0.00 | 01-MAR-00:10 | 5008.18 | 14-MAR-13:00 | 5008.18 | 14-MAR-13:00 | 0.00 | 14-MAR-13:10 | 1108.17 | 14-MAR-13:00 | 0.00 | 01-MAR-00:10 |
April | 12205136.87 | 2950719.80 | 8.50 | 12205136.87 | -0.0 | 0.00 | 0.22 | 20-APR-13:00 | 0.00 | 01-APR-00:05 | 1688.70 | 20-APR-13:00 | 1688.70 | 20-APR-13:00 | 0.00 | 20-APR-12:50 | 399.45 | 20-APR-13:00 | 0.00 | 01-APR-00:05 |
May | 0.112988E+10 | 0.263140E+09 | 116.42 | 0.112823E+10 | 1644709.98 | 0.00 | 0.75 | 17-MAY-13:00 | 0.00 | 01-MAY-00:05 | 6401.48 | 17-MAY-13:00 | 6401.48 | 17-MAY-13:00 | 109.85 | 31-MAY-19:00 | 1507.60 | 17-MAY-13:00 | 0.00 | 01-MAY-00:05 |
June | 0.652107E+10 | 0.153987E+10 | 316.45 | 0.630773E+10 | 0.213334E+09 | 0.00 | 1.00 | 12-JUN-13:00 | 0.00 | 01-JUN-00:10 | 17255.78 | 25-JUN-08:62 | 17255.78 | 25-JUN-08:62 | 1937.95 | 18-JUN-12:00 | 3878.79 | 25-JUN-08:62 | 0.00 | 01-JUN-00:10 |
July | 0.691548E+10 | 0.161526E+10 | 321.65 | 0.660825E+10 | 0.307229E+09 | 0.00 | 1.00 | 01-JUL-07:03 | 0.00 | 01-JUL-00:02 | 18343.13 | 23-JUL-08:62 | 17759.55 | 18-JUL-07:02 | 3249.36 | 24-JUL-07:03 | 4046.74 | 16-JUL-08:62 | 0.00 | 01-JUL-00:02 |
August | 0.666819E+10 | 0.154221E+10 | 328.13 | 0.647982E+10 | 0.188370E+09 | 0.00 | 1.00 | 03-AUG-07:03 | 0.00 | 01-AUG-00:10 | 15295.98 | 20-AUG-08:62 | 14262.59 | 20-AUG-08:62 | 2927.58 | 05-AUG-14:30 | 3084.08 | 20-AUG-08:62 | 0.00 | 01-AUG-00:10 |
September | 0.459187E+10 | 0.104047E+10 | 268.10 | 0.457179E+10 | 20081941.21 | 0.00 | 1.00 | 03-SEP-08:62 | 0.00 | 01-SEP-00:05 | 12528.85 | 11-SEP-07:03 | 12528.85 | 11-SEP-07:03 | 911.32 | 03-SEP-08:62 | 2449.46 | 10-SEP-08:62 | 0.00 | 01-SEP-00:05 |
October | 0.506855E+09 | 0.112282E+09 | 47.83 | 0.506855E+09 | 17.73 | 0.00 | 0.84 | 11-OCT-14:10 | 0.00 | 01-OCT-00:10 | 7466.10 | 11-OCT-14:10 | 7466.10 | 11-OCT-14:10 | 0.02 | 01-OCT-08:10 | 1626.13 | 11-OCT-14:10 | 0.00 | 01-OCT-00:10 |
November | 56288014.93 | 13168135.39 | 15.25 | 56288014.93 | 0.00 | 0.00 | 0.38 | 07-NOV-14:00 | 0.00 | 01-NOV-00:03 | 3011.10 | 07-NOV-14:00 | 3011.10 | 07-NOV-14:00 | 0.00 | 06-NOV-14:00 | 682.68 | 07-NOV-14:00 | 0.00 | 01-NOV-00:03 |
December | 6670307.75 | 1604847.66 | 3.83 | 6670307.75 | -0.0 | 0.00 | 0.21 | 02-DEC-15:00 | 0.00 | 01-DEC-00:03 | 1583.65 | 02-DEC-15:00 | 1583.65 | 02-DEC-15:00 | 0.00 | 02-DEC-15:00 | 375.90 | 02-DEC-15:00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.265660E+11 | 0.616693E+10 | 1448.74 | 0.258354E+11 | 0.730660E+09 | 0.00 | ||||||||||||||
Minimum of Months | 120.20 | 29.63 | 0.50 | 120.20 | -0.0 | 0.00 | 0.00 | 0.00 | 0.11 | 0.11 | 0.00 | 0.03 | 0.00 | |||||||
Maximum of Months | 0.691548E+10 | 0.161526E+10 | 328.13 | 0.660825E+10 | 0.307229E+09 | 0.00 | 1.00 | 0.00 | 18343.13 | 17759.55 | 3249.36 | 4046.74 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_8:8 COOLING COIL
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 1272302.29 | 309593.68 | 2.33 | 1272302.29 | 0.00 | 0.00 | 0.07 | 20-JAN-14:00 | 0.00 | 01-JAN-00:10 | 484.70 | 20-JAN-14:00 | 484.70 | 20-JAN-14:00 | 0.00 | 20-JAN-13:30 | 117.48 | 20-JAN-14:00 | 0.00 | 01-JAN-00:10 |
February | 11.01 | 2.71 | 0.33 | 11.01 | 0.00 | 0.00 | 0.00 | 26-FEB-15:00 | 0.00 | 01-FEB-00:05 | 0.02 | 26-FEB-15:00 | 0.02 | 26-FEB-15:00 | 0.00 | 26-FEB-14:50 | 0.00 | 26-FEB-15:00 | 0.00 | 01-FEB-00:05 |
March | 0.149793E+09 | 34255800.91 | 18.58 | 0.149793E+09 | 0.00 | 0.00 | 0.59 | 14-MAR-13:00 | 0.00 | 01-MAR-00:10 | 4888.83 | 14-MAR-13:00 | 4888.83 | 14-MAR-13:00 | 0.00 | 14-MAR-13:10 | 1084.47 | 14-MAR-13:00 | 0.00 | 01-MAR-00:10 |
April | 11102545.80 | 2686978.76 | 7.50 | 11102545.59 | 0.21 | 0.00 | 0.22 | 20-APR-13:00 | 0.00 | 01-APR-00:05 | 1627.54 | 20-APR-13:00 | 1627.54 | 20-APR-13:00 | 0.00 | 28-APR-14:50 | 385.61 | 20-APR-13:00 | 0.00 | 01-APR-00:05 |
May | 0.109872E+10 | 0.256264E+09 | 115.83 | 0.109726E+10 | 1461352.73 | 0.00 | 0.74 | 17-MAY-13:00 | 0.00 | 01-MAY-00:05 | 6310.15 | 17-MAY-13:00 | 6310.15 | 17-MAY-13:00 | 106.31 | 31-MAY-19:00 | 1488.10 | 17-MAY-13:00 | 0.00 | 01-MAY-00:05 |
June | 0.644757E+10 | 0.152346E+10 | 316.11 | 0.623750E+10 | 0.210067E+09 | 0.00 | 1.00 | 12-JUN-13:00 | 0.00 | 01-JUN-00:10 | 17122.02 | 25-JUN-08:62 | 17122.02 | 25-JUN-08:62 | 1926.61 | 18-JUN-12:00 | 3848.72 | 25-JUN-08:62 | 0.00 | 01-JUN-00:10 |
July | 0.684396E+10 | 0.159929E+10 | 321.53 | 0.654123E+10 | 0.302734E+09 | 0.00 | 1.00 | 01-JUL-07:03 | 0.00 | 01-JUL-00:02 | 18210.15 | 23-JUL-08:62 | 17630.32 | 18-JUL-07:02 | 3145.74 | 24-JUL-07:03 | 4015.52 | 16-JUL-08:62 | 0.00 | 01-JUL-00:02 |
August | 0.660231E+10 | 0.152753E+10 | 328.10 | 0.641650E+10 | 0.185811E+09 | 0.00 | 1.00 | 03-AUG-07:03 | 0.00 | 01-AUG-00:10 | 14830.68 | 20-AUG-08:62 | 13838.03 | 20-AUG-08:62 | 2901.44 | 05-AUG-14:30 | 3010.55 | 16-AUG-14:10 | 0.00 | 01-AUG-00:10 |
September | 0.454134E+10 | 0.102939E+10 | 267.85 | 0.452163E+10 | 19700780.50 | 0.00 | 1.00 | 03-SEP-08:62 | 0.00 | 01-SEP-00:05 | 12188.31 | 11-SEP-07:03 | 12188.31 | 11-SEP-07:03 | 856.62 | 03-SEP-08:62 | 2372.64 | 10-SEP-08:62 | 0.00 | 01-SEP-00:05 |
October | 0.495920E+09 | 0.109932E+09 | 46.92 | 0.495920E+09 | 11.30 | 0.00 | 0.84 | 11-OCT-14:10 | 0.00 | 01-OCT-00:10 | 7387.74 | 11-OCT-14:10 | 7387.74 | 11-OCT-14:10 | 0.01 | 01-OCT-08:30 | 1610.19 | 11-OCT-14:10 | 0.00 | 01-OCT-00:10 |
November | 53073492.10 | 12427826.49 | 14.58 | 53073492.10 | 0.00 | 0.00 | 0.37 | 07-NOV-14:00 | 0.00 | 01-NOV-00:03 | 2937.05 | 07-NOV-14:00 | 2937.05 | 07-NOV-14:00 | 0.00 | 07-NOV-14:30 | 666.99 | 07-NOV-14:00 | 0.00 | 01-NOV-00:03 |
December | 6066182.49 | 1460252.99 | 4.00 | 6066182.49 | 0.00 | 0.00 | 0.20 | 02-DEC-15:00 | 0.00 | 01-DEC-00:03 | 1526.39 | 02-DEC-15:00 | 1526.39 | 02-DEC-15:00 | 0.00 | 02-DEC-15:00 | 362.86 | 02-DEC-15:00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.262511E+11 | 0.609700E+10 | 1443.66 | 0.255314E+11 | 0.719774E+09 | 0.00 | ||||||||||||||
Minimum of Months | 11.01 | 2.71 | 0.33 | 11.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 | 0.02 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.684396E+10 | 0.159929E+10 | 328.10 | 0.654123E+10 | 0.302734E+09 | 0.00 | 1.00 | 0.00 | 18210.15 | 17630.32 | 3145.74 | 4015.52 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_9:9 COOLING COIL
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 264231.82 | 64779.97 | 1.67 | 264231.82 | -0.0 | 0.00 | 0.03 | 20-JAN-14:00 | 0.00 | 01-JAN-00:10 | 196.49 | 20-JAN-14:00 | 196.49 | 20-JAN-14:00 | 0.00 | 20-JAN-13:50 | 48.10 | 20-JAN-14:00 | 0.00 | 01-JAN-00:10 |
February | 34.24 | 8.44 | 0.33 | 34.24 | -0.0 | 0.00 | 0.00 | 18-FEB-12:20 | 0.00 | 01-FEB-00:05 | 0.03 | 18-FEB-12:20 | 0.03 | 18-FEB-12:20 | 0.00 | 01-FEB-00:05 | 0.01 | 18-FEB-12:20 | 0.00 | 01-FEB-00:05 |
March | 0.127333E+09 | 29380908.28 | 18.25 | 0.127333E+09 | 0.00 | 0.00 | 0.55 | 14-MAR-13:00 | 0.00 | 01-MAR-00:10 | 4510.66 | 14-MAR-13:00 | 4510.66 | 14-MAR-13:00 | 0.00 | 14-MAR-12:50 | 1011.08 | 14-MAR-13:00 | 0.00 | 01-MAR-00:10 |
April | 6679172.99 | 1625895.56 | 6.00 | 6679172.99 | 0.00 | 0.00 | 0.18 | 20-APR-13:00 | 0.00 | 01-APR-00:05 | 1367.49 | 20-APR-13:00 | 1367.49 | 20-APR-13:00 | 0.00 | 19-APR-13:50 | 326.70 | 20-APR-13:00 | 0.00 | 01-APR-00:05 |
May | 0.986793E+09 | 0.231740E+09 | 109.75 | 0.985974E+09 | 819206.48 | 0.00 | 0.72 | 17-MAY-13:00 | 0.00 | 01-MAY-00:05 | 6066.30 | 17-MAY-13:00 | 6066.30 | 17-MAY-13:00 | 97.78 | 31-MAY-18:40 | 1439.02 | 17-MAY-13:00 | 0.00 | 01-MAY-00:05 |
June | 0.628634E+10 | 0.148908E+10 | 315.07 | 0.608439E+10 | 0.201946E+09 | 0.00 | 1.00 | 13-JUN-12:10 | 0.00 | 01-JUN-00:10 | 16958.00 | 25-JUN-08:62 | 16958.00 | 25-JUN-08:62 | 1904.42 | 18-JUN-12:00 | 3811.85 | 25-JUN-08:62 | 0.00 | 01-JUN-00:10 |
July | 0.669213E+10 | 0.156713E+10 | 319.46 | 0.640118E+10 | 0.290950E+09 | 0.00 | 1.00 | 09-JUL-13:30 | 0.00 | 01-JUL-00:02 | 18070.60 | 23-JUL-08:62 | 17493.89 | 18-JUL-07:02 | 2713.06 | 24-JUL-07:03 | 3978.55 | 16-JUL-08:62 | 0.00 | 01-JUL-00:02 |
August | 0.647862E+10 | 0.150111E+10 | 326.11 | 0.629819E+10 | 0.180422E+09 | 0.00 | 1.00 | 10-AUG-13:40 | 0.00 | 01-AUG-00:10 | 13321.85 | 20-AUG-08:62 | 12470.74 | 20-AUG-08:62 | 2870.58 | 05-AUG-14:30 | 2990.13 | 16-AUG-14:10 | 0.00 | 01-AUG-00:10 |
September | 0.443006E+10 | 0.100592E+10 | 264.61 | 0.441119E+10 | 18873035.77 | 0.00 | 1.00 | 09-SEP-11:50 | 0.00 | 01-SEP-00:05 | 10924.35 | 11-SEP-07:03 | 10924.35 | 11-SEP-07:03 | 699.36 | 03-SEP-08:62 | 2324.93 | 09-SEP-13:00 | 0.00 | 01-SEP-00:05 |
October | 0.456489E+09 | 0.101504E+09 | 42.67 | 0.456489E+09 | 11.49 | 0.00 | 0.83 | 11-OCT-14:10 | 0.00 | 01-OCT-00:10 | 7214.20 | 11-OCT-14:10 | 7214.20 | 11-OCT-14:10 | 0.01 | 01-OCT-08:30 | 1577.75 | 11-OCT-14:10 | 0.00 | 01-OCT-00:10 |
November | 40018007.39 | 9407946.60 | 13.00 | 40018007.39 | 0.00 | 0.00 | 0.34 | 07-NOV-14:00 | 0.00 | 01-NOV-00:03 | 2635.20 | 07-NOV-14:00 | 2635.20 | 07-NOV-14:00 | 0.00 | 07-NOV-14:30 | 603.85 | 07-NOV-14:00 | 0.00 | 01-NOV-00:03 |
December | 3819436.35 | 921885.21 | 3.50 | 3819436.35 | 0.00 | 0.00 | 0.18 | 02-DEC-15:00 | 0.00 | 01-DEC-00:03 | 1306.87 | 02-DEC-15:00 | 1306.87 | 02-DEC-15:00 | 0.00 | 02-DEC-14:50 | 312.85 | 02-DEC-15:00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.255085E+11 | 0.593788E+10 | 1420.42 | 0.248155E+11 | 0.693010E+09 | 0.00 | ||||||||||||||
Minimum of Months | 34.24 | 8.44 | 0.33 | 34.24 | -0.0 | 0.00 | 0.00 | 0.00 | 0.03 | 0.03 | 0.00 | 0.01 | 0.00 | |||||||
Maximum of Months | 0.669213E+10 | 0.156713E+10 | 326.11 | 0.640118E+10 | 0.290950E+09 | 0.00 | 1.00 | 0.00 | 18070.60 | 17493.89 | 2870.58 | 3978.55 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_10:10 COOLING COIL
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.13 | 0.04 | 0.17 | 0.13 | 0.00 | 0.00 | 0.00 | 20-JAN-13:20 | 0.00 | 01-JAN-00:10 | 0.00 | 20-JAN-13:20 | 0.00 | 20-JAN-13:20 | 0.00 | 20-JAN-13:20 | 0.00 | 20-JAN-13:20 | 0.00 | 01-JAN-00:10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 |
March | 84383815.29 | 22881995.84 | 15.67 | 84383815.29 | -0.0 | 0.00 | 0.44 | 14-MAR-13:00 | 0.00 | 01-MAR-00:10 | 3370.57 | 14-MAR-13:00 | 3370.57 | 14-MAR-13:00 | 0.00 | 14-MAR-13:10 | 893.98 | 14-MAR-13:00 | 0.00 | 01-MAR-00:10 |
April | 2148651.78 | 600574.80 | 1.50 | 2148651.78 | -0.0 | 0.00 | 0.13 | 20-APR-13:00 | 0.00 | 01-APR-00:05 | 950.30 | 20-APR-13:00 | 950.30 | 20-APR-13:00 | 0.00 | 20-APR-13:20 | 263.73 | 20-APR-13:00 | 0.00 | 01-APR-00:05 |
May | 0.688652E+09 | 0.189592E+09 | 90.17 | 0.686996E+09 | 1655783.58 | 0.00 | 0.67 | 17-MAY-13:00 | 0.00 | 01-MAY-00:05 | 5287.09 | 17-MAY-13:00 | 5287.09 | 17-MAY-13:00 | 141.90 | 31-MAY-18:40 | 1461.46 | 17-MAY-13:00 | 0.00 | 01-MAY-00:05 |
June | 0.580020E+10 | 0.158289E+10 | 316.62 | 0.556625E+10 | 0.233947E+09 | 0.00 | 1.00 | 13-JUN-12:10 | 0.00 | 01-JUN-00:10 | 17750.20 | 25-JUN-08:62 | 17750.20 | 25-JUN-08:62 | 2069.66 | 18-JUN-12:00 | 4324.29 | 25-JUN-08:62 | 0.00 | 01-JUN-00:10 |
July | 0.619028E+10 | 0.166888E+10 | 318.27 | 0.587410E+10 | 0.316182E+09 | 0.00 | 1.00 | 09-JUL-13:40 | 0.00 | 01-JUL-00:02 | 17748.42 | 16-JUL-08:62 | 17748.42 | 16-JUL-08:62 | 2494.29 | 30-JUL-12:20 | 4565.13 | 16-JUL-08:62 | 0.00 | 01-JUL-00:02 |
August | 0.619202E+10 | 0.164388E+10 | 325.69 | 0.595682E+10 | 0.235198E+09 | 0.00 | 1.00 | 05-AUG-11:20 | 0.00 | 01-AUG-00:10 | 11261.88 | 16-AUG-14:10 | 11261.88 | 16-AUG-14:10 | 3150.79 | 05-AUG-14:30 | 3392.15 | 16-AUG-14:10 | 0.00 | 01-AUG-00:10 |
September | 0.418077E+10 | 0.109056E+10 | 268.21 | 0.414184E+10 | 38933951.61 | 0.00 | 1.00 | 09-SEP-11:10 | 0.00 | 01-SEP-00:05 | 9840.43 | 09-SEP-13:00 | 9840.43 | 09-SEP-13:00 | 940.71 | 01-SEP-14:00 | 2674.25 | 09-SEP-13:00 | 0.00 | 01-SEP-00:05 |
October | 0.395440E+09 | 0.102134E+09 | 40.67 | 0.395438E+09 | 2833.97 | 0.00 | 0.79 | 11-OCT-14:10 | 0.00 | 01-OCT-00:10 | 6527.30 | 11-OCT-14:10 | 6527.30 | 11-OCT-14:10 | 1.75 | 01-OCT-14:50 | 1657.24 | 11-OCT-14:10 | 0.00 | 01-OCT-00:10 |
November | 27398380.84 | 7461527.22 | 10.17 | 27398380.84 | -0.0 | 0.00 | 0.28 | 07-NOV-14:00 | 0.00 | 01-NOV-00:03 | 2036.40 | 07-NOV-14:00 | 2036.40 | 07-NOV-14:00 | 0.00 | 07-NOV-13:50 | 544.23 | 07-NOV-14:00 | 0.00 | 01-NOV-00:03 |
December | 1233321.63 | 346775.40 | 1.17 | 1233321.63 | -0.0 | 0.00 | 0.09 | 02-DEC-15:00 | 0.00 | 01-DEC-00:03 | 658.17 | 02-DEC-15:00 | 658.17 | 02-DEC-15:00 | 0.00 | 02-DEC-14:30 | 184.57 | 02-DEC-15:00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.235625E+11 | 0.630922E+10 | 1388.29 | 0.227366E+11 | 0.825919E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.619202E+10 | 0.166888E+10 | 325.69 | 0.595682E+10 | 0.316182E+09 | 0.00 | 1.00 | 0.00 | 17750.20 | 17750.20 | 3150.79 | 4565.13 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 183.71 | 151.12 | 32.59 | 218.80 | 79.90 | 0.00 | 0.00 | 0.00 |
February | 176.21 | 140.49 | 35.72 | 209.02 | 82.90 | 0.00 | 0.00 | 0.00 |
March | 129.92 | 85.48 | 44.44 | 156.13 | 65.88 | 0.00 | 0.00 | 0.00 |
April | 84.14 | 33.83 | 50.31 | 93.25 | 59.64 | 0.00 | 0.00 | 0.00 |
May | 77.11 | 14.13 | 62.98 | 92.70 | 37.56 | 0.00 | 0.00 | 0.00 |
June | 71.09 | 12.99 | 58.10 | 105.42 | 21.03 | 0.00 | 0.00 | 0.00 |
July | 74.00 | 13.25 | 60.75 | 110.35 | 19.03 | 0.00 | 0.00 | 0.00 |
August | 94.22 | 39.39 | 54.83 | 140.11 | 22.22 | 0.00 | 0.00 | 0.00 |
September | 121.23 | 67.64 | 53.58 | 169.18 | 34.00 | 0.00 | 0.00 | 0.00 |
October | 144.95 | 102.85 | 42.11 | 181.06 | 68.07 | 0.00 | 0.00 | 0.00 |
November | 176.60 | 140.78 | 35.83 | 214.36 | 76.38 | 0.00 | 0.00 | 0.00 |
December | 168.88 | 136.69 | 32.19 | 196.72 | 91.05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 124.88 | 77.87 | 47.02 | 156.96 | 54.65 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 71.09 | 12.99 | 32.19 | 92.70 | 19.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 183.71 | 151.12 | 62.98 | 218.80 | 91.05 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 183.71 | 151.12 | 32.59 | 218.80 | 79.90 | 0.00 | 0.00 | 0.00 |
February | 176.21 | 140.49 | 35.72 | 209.02 | 82.90 | 0.00 | 0.00 | 0.00 |
March | 129.92 | 85.48 | 44.44 | 156.13 | 65.88 | 0.00 | 0.00 | 0.00 |
April | 84.14 | 33.83 | 50.31 | 93.25 | 59.64 | 0.00 | 0.00 | 0.00 |
May | 77.11 | 14.13 | 62.98 | 92.70 | 37.56 | 0.00 | 0.00 | 0.00 |
June | 71.09 | 12.99 | 58.10 | 105.42 | 21.03 | 0.00 | 0.00 | 0.00 |
July | 74.00 | 13.25 | 60.75 | 110.35 | 19.03 | 0.00 | 0.00 | 0.00 |
August | 94.22 | 39.39 | 54.83 | 140.11 | 22.22 | 0.00 | 0.00 | 0.00 |
September | 121.23 | 67.64 | 53.58 | 169.18 | 34.00 | 0.00 | 0.00 | 0.00 |
October | 144.95 | 102.85 | 42.11 | 181.06 | 68.07 | 0.00 | 0.00 | 0.00 |
November | 176.60 | 140.78 | 35.83 | 214.36 | 76.38 | 0.00 | 0.00 | 0.00 |
December | 168.88 | 136.69 | 32.19 | 196.72 | 91.05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 124.88 | 77.87 | 47.02 | 156.96 | 54.65 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 71.09 | 12.99 | 32.19 | 92.70 | 19.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 183.71 | 151.12 | 62.98 | 218.80 | 91.05 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 183.71 | 151.12 | 32.59 | 218.80 | 79.90 | 0.00 | 0.00 | 0.00 |
February | 176.21 | 140.49 | 35.72 | 209.02 | 82.90 | 0.00 | 0.00 | 0.00 |
March | 129.92 | 85.48 | 44.44 | 156.13 | 65.88 | 0.00 | 0.00 | 0.00 |
April | 84.14 | 33.83 | 50.31 | 93.25 | 59.64 | 0.00 | 0.00 | 0.00 |
May | 77.11 | 14.13 | 62.98 | 92.70 | 37.56 | 0.00 | 0.00 | 0.00 |
June | 71.09 | 12.99 | 58.10 | 105.42 | 21.03 | 0.00 | 0.00 | 0.00 |
July | 74.00 | 13.25 | 60.75 | 110.35 | 19.03 | 0.00 | 0.00 | 0.00 |
August | 94.22 | 39.39 | 54.83 | 140.11 | 22.22 | 0.00 | 0.00 | 0.00 |
September | 121.23 | 67.64 | 53.58 | 169.18 | 34.00 | 0.00 | 0.00 | 0.00 |
October | 144.95 | 102.85 | 42.11 | 181.06 | 68.07 | 0.00 | 0.00 | 0.00 |
November | 176.60 | 140.78 | 35.83 | 214.36 | 76.38 | 0.00 | 0.00 | 0.00 |
December | 168.88 | 136.69 | 32.19 | 196.72 | 91.05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 124.88 | 77.87 | 47.02 | 156.96 | 54.65 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 71.09 | 12.99 | 32.19 | 92.70 | 19.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 183.71 | 151.12 | 62.98 | 218.80 | 91.05 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 183.71 | 151.12 | 32.59 | 218.80 | 79.90 | 0.00 | 0.00 | 0.00 |
February | 176.21 | 140.49 | 35.72 | 209.02 | 82.90 | 0.00 | 0.00 | 0.00 |
March | 129.92 | 85.48 | 44.44 | 156.13 | 65.88 | 0.00 | 0.00 | 0.00 |
April | 84.14 | 33.83 | 50.31 | 93.25 | 59.64 | 0.00 | 0.00 | 0.00 |
May | 77.11 | 14.13 | 62.98 | 92.70 | 37.56 | 0.00 | 0.00 | 0.00 |
June | 71.09 | 12.99 | 58.10 | 105.42 | 21.03 | 0.00 | 0.00 | 0.00 |
July | 74.00 | 13.25 | 60.75 | 110.35 | 19.03 | 0.00 | 0.00 | 0.00 |
August | 94.22 | 39.39 | 54.83 | 140.11 | 22.22 | 0.00 | 0.00 | 0.00 |
September | 121.23 | 67.64 | 53.58 | 169.18 | 34.00 | 0.00 | 0.00 | 0.00 |
October | 144.95 | 102.85 | 42.11 | 181.06 | 68.07 | 0.00 | 0.00 | 0.00 |
November | 176.60 | 140.78 | 35.83 | 214.36 | 76.38 | 0.00 | 0.00 | 0.00 |
December | 168.88 | 136.69 | 32.19 | 196.72 | 91.05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 124.88 | 77.87 | 47.02 | 156.96 | 54.65 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 71.09 | 12.99 | 32.19 | 92.70 | 19.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 183.71 | 151.12 | 62.98 | 218.80 | 91.05 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 220.85 | 181.67 | 39.18 | 263.34 | 95.08 | 0.00 | 0.00 | 0.00 |
February | 211.83 | 168.89 | 42.95 | 251.74 | 98.47 | 0.00 | 0.00 | 0.00 |
March | 156.18 | 102.76 | 53.42 | 188.00 | 78.28 | 0.00 | 0.00 | 0.00 |
April | 101.15 | 40.67 | 60.48 | 112.40 | 70.82 | 0.00 | 0.00 | 0.00 |
May | 92.70 | 16.99 | 75.71 | 111.58 | 44.71 | 0.00 | 0.00 | 0.00 |
June | 85.46 | 15.62 | 69.84 | 126.53 | 25.19 | 0.00 | 0.00 | 0.00 |
July | 88.97 | 15.93 | 73.03 | 132.45 | 22.79 | 0.00 | 0.00 | 0.00 |
August | 113.27 | 47.35 | 65.92 | 168.27 | 26.60 | 0.00 | 0.00 | 0.00 |
September | 145.73 | 81.32 | 64.42 | 203.33 | 40.63 | 0.00 | 0.00 | 0.00 |
October | 174.26 | 123.64 | 50.62 | 217.79 | 81.00 | 0.00 | 0.00 | 0.00 |
November | 212.31 | 169.24 | 43.07 | 258.00 | 90.85 | 0.00 | 0.00 | 0.00 |
December | 203.02 | 164.32 | 38.70 | 236.96 | 108.15 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 150.13 | 93.61 | 56.52 | 188.84 | 65.03 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 85.46 | 15.62 | 38.70 | 111.58 | 22.79 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 220.85 | 181.67 | 75.71 | 263.34 | 108.15 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 220.85 | 181.67 | 39.18 | 263.34 | 95.08 | 0.00 | 0.00 | 0.00 |
February | 211.83 | 168.89 | 42.95 | 251.74 | 98.47 | 0.00 | 0.00 | 0.00 |
March | 156.18 | 102.76 | 53.42 | 188.00 | 78.28 | 0.00 | 0.00 | 0.00 |
April | 101.15 | 40.67 | 60.48 | 112.40 | 70.82 | 0.00 | 0.00 | 0.00 |
May | 92.70 | 16.99 | 75.71 | 111.58 | 44.71 | 0.00 | 0.00 | 0.00 |
June | 85.46 | 15.62 | 69.84 | 126.53 | 25.19 | 0.00 | 0.00 | 0.00 |
July | 88.97 | 15.93 | 73.03 | 132.45 | 22.79 | 0.00 | 0.00 | 0.00 |
August | 113.27 | 47.35 | 65.92 | 168.27 | 26.60 | 0.00 | 0.00 | 0.00 |
September | 145.73 | 81.32 | 64.42 | 203.33 | 40.63 | 0.00 | 0.00 | 0.00 |
October | 174.26 | 123.64 | 50.62 | 217.79 | 81.00 | 0.00 | 0.00 | 0.00 |
November | 212.31 | 169.24 | 43.07 | 258.00 | 90.85 | 0.00 | 0.00 | 0.00 |
December | 203.02 | 164.32 | 38.70 | 236.96 | 108.15 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 150.13 | 93.61 | 56.52 | 188.84 | 65.03 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 85.46 | 15.62 | 38.70 | 111.58 | 22.79 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 220.85 | 181.67 | 75.71 | 263.34 | 108.15 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 183.71 | 151.12 | 32.59 | 217.14 | 84.03 | 0.00 | 0.00 | 0.00 |
February | 176.21 | 140.49 | 35.72 | 207.39 | 86.86 | 0.00 | 0.00 | 0.00 |
March | 129.92 | 85.48 | 44.44 | 154.67 | 69.67 | 0.00 | 0.00 | 0.00 |
April | 84.14 | 33.83 | 50.31 | 91.86 | 63.92 | 0.00 | 0.00 | 0.00 |
May | 77.11 | 14.13 | 62.98 | 91.29 | 39.77 | 0.00 | 0.00 | 0.00 |
June | 71.09 | 12.99 | 58.10 | 105.25 | 21.32 | 0.00 | 0.00 | 0.00 |
July | 74.00 | 13.25 | 60.75 | 110.19 | 19.35 | 0.00 | 0.00 | 0.00 |
August | 94.22 | 39.39 | 54.83 | 139.97 | 22.44 | 0.00 | 0.00 | 0.00 |
September | 121.23 | 67.64 | 53.58 | 168.85 | 34.59 | 0.00 | 0.00 | 0.00 |
October | 144.95 | 102.85 | 42.11 | 180.03 | 70.95 | 0.00 | 0.00 | 0.00 |
November | 176.60 | 140.78 | 35.83 | 212.94 | 80.17 | 0.00 | 0.00 | 0.00 |
December | 168.88 | 136.69 | 32.19 | 195.28 | 95.05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 124.88 | 77.87 | 47.02 | 155.94 | 57.18 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 71.09 | 12.99 | 32.19 | 91.29 | 19.35 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 183.71 | 151.12 | 62.98 | 217.14 | 95.05 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 183.71 | 151.12 | 32.59 | 217.14 | 84.03 | 0.00 | 0.00 | 0.00 |
February | 176.21 | 140.49 | 35.72 | 207.39 | 86.86 | 0.00 | 0.00 | 0.00 |
March | 129.92 | 85.48 | 44.44 | 154.67 | 69.67 | 0.00 | 0.00 | 0.00 |
April | 84.14 | 33.83 | 50.31 | 91.86 | 63.92 | 0.00 | 0.00 | 0.00 |
May | 77.11 | 14.13 | 62.98 | 91.29 | 39.77 | 0.00 | 0.00 | 0.00 |
June | 71.09 | 12.99 | 58.10 | 105.25 | 21.32 | 0.00 | 0.00 | 0.00 |
July | 74.00 | 13.25 | 60.75 | 110.19 | 19.35 | 0.00 | 0.00 | 0.00 |
August | 94.22 | 39.39 | 54.83 | 139.97 | 22.44 | 0.00 | 0.00 | 0.00 |
September | 121.23 | 67.64 | 53.58 | 168.85 | 34.59 | 0.00 | 0.00 | 0.00 |
October | 144.95 | 102.85 | 42.11 | 180.03 | 70.95 | 0.00 | 0.00 | 0.00 |
November | 176.60 | 140.78 | 35.83 | 212.94 | 80.17 | 0.00 | 0.00 | 0.00 |
December | 168.88 | 136.69 | 32.19 | 195.28 | 95.05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 124.88 | 77.87 | 47.02 | 155.94 | 57.18 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 71.09 | 12.99 | 32.19 | 91.29 | 19.35 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 183.71 | 151.12 | 62.98 | 217.14 | 95.05 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 220.85 | 181.67 | 39.18 | 261.40 | 99.93 | 0.00 | 0.00 | 0.00 |
February | 211.83 | 168.89 | 42.95 | 249.85 | 103.13 | 0.00 | 0.00 | 0.00 |
March | 156.18 | 102.76 | 53.42 | 186.29 | 82.75 | 0.00 | 0.00 | 0.00 |
April | 101.15 | 40.67 | 60.48 | 110.75 | 75.85 | 0.00 | 0.00 | 0.00 |
May | 92.70 | 16.99 | 75.71 | 109.91 | 47.31 | 0.00 | 0.00 | 0.00 |
June | 85.46 | 15.62 | 69.84 | 126.33 | 25.53 | 0.00 | 0.00 | 0.00 |
July | 88.97 | 15.93 | 73.03 | 132.26 | 23.17 | 0.00 | 0.00 | 0.00 |
August | 113.27 | 47.35 | 65.92 | 168.13 | 26.86 | 0.00 | 0.00 | 0.00 |
September | 145.73 | 81.32 | 64.42 | 202.96 | 41.32 | 0.00 | 0.00 | 0.00 |
October | 174.26 | 123.64 | 50.62 | 216.59 | 84.37 | 0.00 | 0.00 | 0.00 |
November | 212.31 | 169.24 | 43.07 | 256.34 | 95.31 | 0.00 | 0.00 | 0.00 |
December | 203.02 | 164.32 | 38.70 | 235.27 | 112.83 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 150.13 | 93.61 | 56.52 | 187.65 | 68.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 85.46 | 15.62 | 38.70 | 109.91 | 23.17 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 220.85 | 181.67 | 75.71 | 261.40 | 112.83 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 183.71 | 151.12 | 32.59 | 217.44 | 82.36 | 0.00 | 0.00 | 0.00 |
February | 176.21 | 140.49 | 35.72 | 207.64 | 85.16 | 0.00 | 0.00 | 0.00 |
March | 129.92 | 85.48 | 44.44 | 154.88 | 68.44 | 0.00 | 0.00 | 0.00 |
April | 84.14 | 33.83 | 50.31 | 92.13 | 62.40 | 0.00 | 0.00 | 0.00 |
May | 77.11 | 14.13 | 62.98 | 91.42 | 39.75 | 0.00 | 0.00 | 0.00 |
June | 71.09 | 12.99 | 58.10 | 104.88 | 22.77 | 0.00 | 0.00 | 0.00 |
July | 74.00 | 13.25 | 60.75 | 109.69 | 20.88 | 0.00 | 0.00 | 0.00 |
August | 94.22 | 39.39 | 54.83 | 139.75 | 24.01 | 0.00 | 0.00 | 0.00 |
September | 121.23 | 67.64 | 53.58 | 168.69 | 35.91 | 0.00 | 0.00 | 0.00 |
October | 144.95 | 102.85 | 42.11 | 180.18 | 70.51 | 0.00 | 0.00 | 0.00 |
November | 176.60 | 140.78 | 35.83 | 213.28 | 78.77 | 0.00 | 0.00 | 0.00 |
December | 168.88 | 136.69 | 32.19 | 195.52 | 93.24 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 124.88 | 77.87 | 47.02 | 156.00 | 56.86 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 71.09 | 12.99 | 32.19 | 91.42 | 20.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 183.71 | 151.12 | 62.98 | 217.44 | 93.24 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 183.71 | 151.12 | 32.59 | 217.44 | 82.36 | 0.00 | 0.00 | 0.00 |
February | 176.21 | 140.49 | 35.72 | 207.64 | 85.16 | 0.00 | 0.00 | 0.00 |
March | 129.92 | 85.48 | 44.44 | 154.88 | 68.44 | 0.00 | 0.00 | 0.00 |
April | 84.14 | 33.83 | 50.31 | 92.13 | 62.40 | 0.00 | 0.00 | 0.00 |
May | 77.11 | 14.13 | 62.98 | 91.42 | 39.75 | 0.00 | 0.00 | 0.00 |
June | 71.09 | 12.99 | 58.10 | 104.88 | 22.77 | 0.00 | 0.00 | 0.00 |
July | 74.00 | 13.25 | 60.75 | 109.69 | 20.88 | 0.00 | 0.00 | 0.00 |
August | 94.22 | 39.39 | 54.83 | 139.75 | 24.01 | 0.00 | 0.00 | 0.00 |
September | 121.23 | 67.64 | 53.58 | 168.69 | 35.91 | 0.00 | 0.00 | 0.00 |
October | 144.95 | 102.85 | 42.11 | 180.18 | 70.51 | 0.00 | 0.00 | 0.00 |
November | 176.60 | 140.78 | 35.83 | 213.28 | 78.77 | 0.00 | 0.00 | 0.00 |
December | 168.88 | 136.69 | 32.19 | 195.52 | 93.24 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 124.88 | 77.87 | 47.02 | 156.00 | 56.86 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 71.09 | 12.99 | 32.19 | 91.42 | 20.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 183.71 | 151.12 | 62.98 | 217.44 | 93.24 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 219.64 | 180.68 | 38.96 | 260.33 | 97.44 | 0.00 | 0.00 | 0.00 |
February | 210.68 | 167.97 | 42.71 | 248.78 | 100.58 | 0.00 | 0.00 | 0.00 |
March | 155.33 | 102.20 | 53.13 | 185.52 | 80.86 | 0.00 | 0.00 | 0.00 |
April | 100.60 | 40.45 | 60.15 | 110.46 | 73.66 | 0.00 | 0.00 | 0.00 |
May | 92.19 | 16.90 | 75.29 | 109.46 | 47.03 | 0.00 | 0.00 | 0.00 |
June | 85.00 | 15.53 | 69.46 | 125.21 | 27.08 | 0.00 | 0.00 | 0.00 |
July | 88.48 | 15.84 | 72.64 | 130.96 | 24.83 | 0.00 | 0.00 | 0.00 |
August | 112.65 | 47.09 | 65.56 | 166.95 | 28.54 | 0.00 | 0.00 | 0.00 |
September | 144.94 | 80.87 | 64.06 | 201.67 | 42.64 | 0.00 | 0.00 | 0.00 |
October | 173.30 | 122.96 | 50.34 | 215.59 | 83.39 | 0.00 | 0.00 | 0.00 |
November | 211.15 | 168.31 | 42.83 | 255.35 | 93.14 | 0.00 | 0.00 | 0.00 |
December | 201.91 | 163.42 | 38.49 | 234.28 | 110.09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 149.31 | 93.10 | 56.21 | 186.69 | 67.26 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 85.00 | 15.53 | 38.49 | 109.46 | 24.83 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 219.64 | 180.68 | 75.29 | 260.33 | 110.09 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 183.71 | 151.12 | 32.59 | 217.68 | 81.52 | 0.00 | 0.00 | 0.00 |
February | 176.21 | 140.49 | 35.72 | 207.83 | 84.39 | 0.00 | 0.00 | 0.00 |
March | 129.92 | 85.48 | 44.44 | 155.07 | 67.74 | 0.00 | 0.00 | 0.00 |
April | 84.14 | 33.83 | 50.31 | 92.35 | 61.56 | 0.00 | 0.00 | 0.00 |
May | 77.11 | 14.13 | 62.98 | 91.63 | 39.31 | 0.00 | 0.00 | 0.00 |
June | 71.09 | 12.99 | 58.10 | 104.88 | 22.80 | 0.00 | 0.00 | 0.00 |
July | 74.00 | 13.25 | 60.75 | 109.67 | 20.95 | 0.00 | 0.00 | 0.00 |
August | 94.22 | 39.39 | 54.83 | 139.75 | 24.05 | 0.00 | 0.00 | 0.00 |
September | 121.23 | 67.64 | 53.58 | 168.71 | 35.87 | 0.00 | 0.00 | 0.00 |
October | 144.95 | 102.85 | 42.11 | 180.31 | 69.98 | 0.00 | 0.00 | 0.00 |
November | 176.60 | 140.78 | 35.83 | 213.50 | 78.02 | 0.00 | 0.00 | 0.00 |
December | 168.88 | 136.69 | 32.19 | 195.71 | 92.41 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 124.88 | 77.87 | 47.02 | 156.13 | 56.40 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 71.09 | 12.99 | 32.19 | 91.63 | 20.95 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 183.71 | 151.12 | 62.98 | 217.68 | 92.41 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 183.71 | 151.12 | 32.59 | 217.68 | 81.52 | 0.00 | 0.00 | 0.00 |
February | 176.21 | 140.49 | 35.72 | 207.83 | 84.39 | 0.00 | 0.00 | 0.00 |
March | 129.92 | 85.48 | 44.44 | 155.07 | 67.74 | 0.00 | 0.00 | 0.00 |
April | 84.14 | 33.83 | 50.31 | 92.35 | 61.56 | 0.00 | 0.00 | 0.00 |
May | 77.11 | 14.13 | 62.98 | 91.63 | 39.31 | 0.00 | 0.00 | 0.00 |
June | 71.09 | 12.99 | 58.10 | 104.88 | 22.80 | 0.00 | 0.00 | 0.00 |
July | 74.00 | 13.25 | 60.75 | 109.67 | 20.95 | 0.00 | 0.00 | 0.00 |
August | 94.22 | 39.39 | 54.83 | 139.75 | 24.05 | 0.00 | 0.00 | 0.00 |
September | 121.23 | 67.64 | 53.58 | 168.71 | 35.87 | 0.00 | 0.00 | 0.00 |
October | 144.95 | 102.85 | 42.11 | 180.31 | 69.98 | 0.00 | 0.00 | 0.00 |
November | 176.60 | 140.78 | 35.83 | 213.50 | 78.02 | 0.00 | 0.00 | 0.00 |
December | 168.88 | 136.69 | 32.19 | 195.71 | 92.41 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 124.88 | 77.87 | 47.02 | 156.13 | 56.40 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 71.09 | 12.99 | 32.19 | 91.63 | 20.95 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 183.71 | 151.12 | 62.98 | 217.68 | 92.41 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 219.64 | 180.68 | 38.96 | 260.62 | 96.44 | 0.00 | 0.00 | 0.00 |
February | 210.68 | 167.97 | 42.71 | 249.00 | 99.66 | 0.00 | 0.00 | 0.00 |
March | 155.33 | 102.20 | 53.13 | 185.75 | 80.02 | 0.00 | 0.00 | 0.00 |
April | 100.60 | 40.45 | 60.15 | 110.73 | 72.67 | 0.00 | 0.00 | 0.00 |
May | 92.19 | 16.90 | 75.29 | 109.72 | 46.50 | 0.00 | 0.00 | 0.00 |
June | 85.00 | 15.53 | 69.46 | 125.21 | 27.11 | 0.00 | 0.00 | 0.00 |
July | 88.48 | 15.84 | 72.64 | 130.93 | 24.90 | 0.00 | 0.00 | 0.00 |
August | 112.65 | 47.09 | 65.56 | 166.94 | 28.59 | 0.00 | 0.00 | 0.00 |
September | 144.94 | 80.87 | 64.06 | 201.69 | 42.60 | 0.00 | 0.00 | 0.00 |
October | 173.30 | 122.96 | 50.34 | 215.75 | 82.76 | 0.00 | 0.00 | 0.00 |
November | 211.15 | 168.31 | 42.83 | 255.61 | 92.25 | 0.00 | 0.00 | 0.00 |
December | 201.91 | 163.42 | 38.49 | 234.51 | 109.11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 149.31 | 93.10 | 56.21 | 186.85 | 66.71 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 85.00 | 15.53 | 38.49 | 109.72 | 24.90 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 219.64 | 180.68 | 75.29 | 260.62 | 109.11 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 183.71 | 151.12 | 32.59 | 217.97 | 80.78 | 0.00 | 0.00 | 0.00 |
February | 176.21 | 140.49 | 35.72 | 208.06 | 83.72 | 0.00 | 0.00 | 0.00 |
March | 129.92 | 85.48 | 44.44 | 155.35 | 67.03 | 0.00 | 0.00 | 0.00 |
April | 84.14 | 33.83 | 50.31 | 92.66 | 60.72 | 0.00 | 0.00 | 0.00 |
May | 77.11 | 14.13 | 62.98 | 92.01 | 38.71 | 0.00 | 0.00 | 0.00 |
June | 71.09 | 12.99 | 58.10 | 105.02 | 22.52 | 0.00 | 0.00 | 0.00 |
July | 74.00 | 13.25 | 60.75 | 109.79 | 20.70 | 0.00 | 0.00 | 0.00 |
August | 94.22 | 39.39 | 54.83 | 139.85 | 23.78 | 0.00 | 0.00 | 0.00 |
September | 121.23 | 67.64 | 53.58 | 168.83 | 35.56 | 0.00 | 0.00 | 0.00 |
October | 144.95 | 102.85 | 42.11 | 180.53 | 69.37 | 0.00 | 0.00 | 0.00 |
November | 176.60 | 140.78 | 35.83 | 213.76 | 77.34 | 0.00 | 0.00 | 0.00 |
December | 168.88 | 136.69 | 32.19 | 195.95 | 91.67 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 124.88 | 77.87 | 47.02 | 156.35 | 55.84 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 71.09 | 12.99 | 32.19 | 92.01 | 20.70 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 183.71 | 151.12 | 62.98 | 217.97 | 91.67 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 183.71 | 151.12 | 32.59 | 217.97 | 80.78 | 0.00 | 0.00 | 0.00 |
February | 176.21 | 140.49 | 35.72 | 208.06 | 83.72 | 0.00 | 0.00 | 0.00 |
March | 129.92 | 85.48 | 44.44 | 155.35 | 67.03 | 0.00 | 0.00 | 0.00 |
April | 84.14 | 33.83 | 50.31 | 92.66 | 60.72 | 0.00 | 0.00 | 0.00 |
May | 77.11 | 14.13 | 62.98 | 92.01 | 38.71 | 0.00 | 0.00 | 0.00 |
June | 71.09 | 12.99 | 58.10 | 105.02 | 22.52 | 0.00 | 0.00 | 0.00 |
July | 74.00 | 13.25 | 60.75 | 109.79 | 20.70 | 0.00 | 0.00 | 0.00 |
August | 94.22 | 39.39 | 54.83 | 139.85 | 23.78 | 0.00 | 0.00 | 0.00 |
September | 121.23 | 67.64 | 53.58 | 168.83 | 35.56 | 0.00 | 0.00 | 0.00 |
October | 144.95 | 102.85 | 42.11 | 180.53 | 69.37 | 0.00 | 0.00 | 0.00 |
November | 176.60 | 140.78 | 35.83 | 213.76 | 77.34 | 0.00 | 0.00 | 0.00 |
December | 168.88 | 136.69 | 32.19 | 195.95 | 91.67 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 124.88 | 77.87 | 47.02 | 156.35 | 55.84 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 71.09 | 12.99 | 32.19 | 92.01 | 20.70 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 183.71 | 151.12 | 62.98 | 217.97 | 91.67 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 219.64 | 180.68 | 38.96 | 260.96 | 95.56 | 0.00 | 0.00 | 0.00 |
February | 210.68 | 167.97 | 42.71 | 249.29 | 98.87 | 0.00 | 0.00 | 0.00 |
March | 155.33 | 102.20 | 53.13 | 186.09 | 79.18 | 0.00 | 0.00 | 0.00 |
April | 100.60 | 40.45 | 60.15 | 111.10 | 71.67 | 0.00 | 0.00 | 0.00 |
May | 92.19 | 16.90 | 75.29 | 110.17 | 45.79 | 0.00 | 0.00 | 0.00 |
June | 85.00 | 15.53 | 69.46 | 125.37 | 26.78 | 0.00 | 0.00 | 0.00 |
July | 88.48 | 15.84 | 72.64 | 131.07 | 24.61 | 0.00 | 0.00 | 0.00 |
August | 112.65 | 47.09 | 65.56 | 167.06 | 28.28 | 0.00 | 0.00 | 0.00 |
September | 144.94 | 80.87 | 64.06 | 201.83 | 42.23 | 0.00 | 0.00 | 0.00 |
October | 173.30 | 122.96 | 50.34 | 216.01 | 82.05 | 0.00 | 0.00 | 0.00 |
November | 211.15 | 168.31 | 42.83 | 255.92 | 91.44 | 0.00 | 0.00 | 0.00 |
December | 201.91 | 163.42 | 38.49 | 234.80 | 108.25 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 149.31 | 93.10 | 56.21 | 187.12 | 66.05 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 85.00 | 15.53 | 38.49 | 110.17 | 24.61 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 219.64 | 180.68 | 75.29 | 260.96 | 108.25 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 183.71 | 151.12 | 32.59 | 218.87 | 78.97 | 0.00 | 0.00 | 0.00 |
February | 176.21 | 140.49 | 35.72 | 209.00 | 81.78 | 0.00 | 0.00 | 0.00 |
March | 129.92 | 85.48 | 44.44 | 156.14 | 65.15 | 0.00 | 0.00 | 0.00 |
April | 84.14 | 33.83 | 50.31 | 93.41 | 58.65 | 0.00 | 0.00 | 0.00 |
May | 77.11 | 14.13 | 62.98 | 92.70 | 37.30 | 0.00 | 0.00 | 0.00 |
June | 71.09 | 12.99 | 58.10 | 105.04 | 21.63 | 0.00 | 0.00 | 0.00 |
July | 74.00 | 13.25 | 60.75 | 109.76 | 19.90 | 0.00 | 0.00 | 0.00 |
August | 94.22 | 39.39 | 54.83 | 139.84 | 22.94 | 0.00 | 0.00 | 0.00 |
September | 121.23 | 67.64 | 53.58 | 168.92 | 34.70 | 0.00 | 0.00 | 0.00 |
October | 144.95 | 102.85 | 42.11 | 180.96 | 67.92 | 0.00 | 0.00 | 0.00 |
November | 176.60 | 140.78 | 35.83 | 214.49 | 75.68 | 0.00 | 0.00 | 0.00 |
December | 168.88 | 136.69 | 32.19 | 196.92 | 89.61 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 124.88 | 77.87 | 47.02 | 156.87 | 54.37 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 71.09 | 12.99 | 32.19 | 92.70 | 19.90 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 183.71 | 151.12 | 62.98 | 218.87 | 89.61 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 183.71 | 151.12 | 32.59 | 218.87 | 78.97 | 0.00 | 0.00 | 0.00 |
February | 176.21 | 140.49 | 35.72 | 209.00 | 81.78 | 0.00 | 0.00 | 0.00 |
March | 129.92 | 85.48 | 44.44 | 156.14 | 65.15 | 0.00 | 0.00 | 0.00 |
April | 84.14 | 33.83 | 50.31 | 93.41 | 58.65 | 0.00 | 0.00 | 0.00 |
May | 77.11 | 14.13 | 62.98 | 92.70 | 37.30 | 0.00 | 0.00 | 0.00 |
June | 71.09 | 12.99 | 58.10 | 105.04 | 21.63 | 0.00 | 0.00 | 0.00 |
July | 74.00 | 13.25 | 60.75 | 109.76 | 19.90 | 0.00 | 0.00 | 0.00 |
August | 94.22 | 39.39 | 54.83 | 139.84 | 22.94 | 0.00 | 0.00 | 0.00 |
September | 121.23 | 67.64 | 53.58 | 168.92 | 34.70 | 0.00 | 0.00 | 0.00 |
October | 144.95 | 102.85 | 42.11 | 180.96 | 67.92 | 0.00 | 0.00 | 0.00 |
November | 176.60 | 140.78 | 35.83 | 214.49 | 75.68 | 0.00 | 0.00 | 0.00 |
December | 168.88 | 136.69 | 32.19 | 196.92 | 89.61 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 124.88 | 77.87 | 47.02 | 156.87 | 54.37 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 71.09 | 12.99 | 32.19 | 92.70 | 19.90 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 183.71 | 151.12 | 62.98 | 218.87 | 89.61 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 183.71 | 151.12 | 32.59 | 218.87 | 78.97 | 0.00 | 0.00 | 0.00 |
February | 176.21 | 140.49 | 35.72 | 209.00 | 81.78 | 0.00 | 0.00 | 0.00 |
March | 129.92 | 85.48 | 44.44 | 156.14 | 65.15 | 0.00 | 0.00 | 0.00 |
April | 84.14 | 33.83 | 50.31 | 93.41 | 58.65 | 0.00 | 0.00 | 0.00 |
May | 77.11 | 14.13 | 62.98 | 92.70 | 37.30 | 0.00 | 0.00 | 0.00 |
June | 71.09 | 12.99 | 58.10 | 105.04 | 21.63 | 0.00 | 0.00 | 0.00 |
July | 74.00 | 13.25 | 60.75 | 109.76 | 19.90 | 0.00 | 0.00 | 0.00 |
August | 94.22 | 39.39 | 54.83 | 139.84 | 22.94 | 0.00 | 0.00 | 0.00 |
September | 121.23 | 67.64 | 53.58 | 168.92 | 34.70 | 0.00 | 0.00 | 0.00 |
October | 144.95 | 102.85 | 42.11 | 180.96 | 67.92 | 0.00 | 0.00 | 0.00 |
November | 176.60 | 140.78 | 35.83 | 214.49 | 75.68 | 0.00 | 0.00 | 0.00 |
December | 168.88 | 136.69 | 32.19 | 196.92 | 89.61 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 124.88 | 77.87 | 47.02 | 156.87 | 54.37 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 71.09 | 12.99 | 32.19 | 92.70 | 19.90 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 183.71 | 151.12 | 62.98 | 218.87 | 89.61 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 183.71 | 151.12 | 32.59 | 218.87 | 78.97 | 0.00 | 0.00 | 0.00 |
February | 176.21 | 140.49 | 35.72 | 209.00 | 81.78 | 0.00 | 0.00 | 0.00 |
March | 129.92 | 85.48 | 44.44 | 156.14 | 65.15 | 0.00 | 0.00 | 0.00 |
April | 84.14 | 33.83 | 50.31 | 93.41 | 58.65 | 0.00 | 0.00 | 0.00 |
May | 77.11 | 14.13 | 62.98 | 92.70 | 37.30 | 0.00 | 0.00 | 0.00 |
June | 71.09 | 12.99 | 58.10 | 105.04 | 21.63 | 0.00 | 0.00 | 0.00 |
July | 74.00 | 13.25 | 60.75 | 109.76 | 19.90 | 0.00 | 0.00 | 0.00 |
August | 94.22 | 39.39 | 54.83 | 139.84 | 22.94 | 0.00 | 0.00 | 0.00 |
September | 121.23 | 67.64 | 53.58 | 168.92 | 34.70 | 0.00 | 0.00 | 0.00 |
October | 144.95 | 102.85 | 42.11 | 180.96 | 67.92 | 0.00 | 0.00 | 0.00 |
November | 176.60 | 140.78 | 35.83 | 214.49 | 75.68 | 0.00 | 0.00 | 0.00 |
December | 168.88 | 136.69 | 32.19 | 196.92 | 89.61 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 124.88 | 77.87 | 47.02 | 156.87 | 54.37 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 71.09 | 12.99 | 32.19 | 92.70 | 19.90 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 183.71 | 151.12 | 62.98 | 218.87 | 89.61 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 219.64 | 180.68 | 38.96 | 261.99 | 93.46 | 0.00 | 0.00 | 0.00 |
February | 210.68 | 167.97 | 42.71 | 250.35 | 96.62 | 0.00 | 0.00 | 0.00 |
March | 155.33 | 102.20 | 53.13 | 187.00 | 77.00 | 0.00 | 0.00 | 0.00 |
April | 100.60 | 40.45 | 60.15 | 111.97 | 69.27 | 0.00 | 0.00 | 0.00 |
May | 92.19 | 16.90 | 75.29 | 110.97 | 44.15 | 0.00 | 0.00 | 0.00 |
June | 85.00 | 15.53 | 69.46 | 125.40 | 25.74 | 0.00 | 0.00 | 0.00 |
July | 88.48 | 15.84 | 72.64 | 131.04 | 23.67 | 0.00 | 0.00 | 0.00 |
August | 112.65 | 47.09 | 65.56 | 167.04 | 27.28 | 0.00 | 0.00 | 0.00 |
September | 144.94 | 80.87 | 64.06 | 201.93 | 41.22 | 0.00 | 0.00 | 0.00 |
October | 173.30 | 122.96 | 50.34 | 216.49 | 80.36 | 0.00 | 0.00 | 0.00 |
November | 211.15 | 168.31 | 42.83 | 256.75 | 89.52 | 0.00 | 0.00 | 0.00 |
December | 201.91 | 163.42 | 38.49 | 235.90 | 105.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 149.31 | 93.10 | 56.21 | 187.71 | 64.34 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 85.00 | 15.53 | 38.49 | 110.97 | 23.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 219.64 | 180.68 | 75.29 | 261.99 | 105.86 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 219.64 | 180.68 | 38.96 | 261.99 | 93.46 | 0.00 | 0.00 | 0.00 |
February | 210.68 | 167.97 | 42.71 | 250.35 | 96.62 | 0.00 | 0.00 | 0.00 |
March | 155.33 | 102.20 | 53.13 | 187.00 | 77.00 | 0.00 | 0.00 | 0.00 |
April | 100.60 | 40.45 | 60.15 | 111.97 | 69.27 | 0.00 | 0.00 | 0.00 |
May | 92.19 | 16.90 | 75.29 | 110.97 | 44.15 | 0.00 | 0.00 | 0.00 |
June | 85.00 | 15.53 | 69.46 | 125.40 | 25.74 | 0.00 | 0.00 | 0.00 |
July | 88.48 | 15.84 | 72.64 | 131.04 | 23.67 | 0.00 | 0.00 | 0.00 |
August | 112.65 | 47.09 | 65.56 | 167.04 | 27.28 | 0.00 | 0.00 | 0.00 |
September | 144.94 | 80.87 | 64.06 | 201.93 | 41.22 | 0.00 | 0.00 | 0.00 |
October | 173.30 | 122.96 | 50.34 | 216.49 | 80.36 | 0.00 | 0.00 | 0.00 |
November | 211.15 | 168.31 | 42.83 | 256.75 | 89.52 | 0.00 | 0.00 | 0.00 |
December | 201.91 | 163.42 | 38.49 | 235.90 | 105.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 149.31 | 93.10 | 56.21 | 187.71 | 64.34 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 85.00 | 15.53 | 38.49 | 110.97 | 23.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 219.64 | 180.68 | 75.29 | 261.99 | 105.86 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 183.71 | 151.12 | 32.59 | 218.39 | 79.34 | 0.00 | 0.00 | 0.00 |
February | 176.21 | 140.49 | 35.72 | 208.50 | 82.21 | 0.00 | 0.00 | 0.00 |
March | 129.92 | 85.48 | 44.44 | 155.67 | 65.57 | 0.00 | 0.00 | 0.00 |
April | 84.14 | 33.83 | 50.31 | 92.94 | 59.20 | 0.00 | 0.00 | 0.00 |
May | 77.11 | 14.13 | 62.98 | 92.22 | 37.63 | 0.00 | 0.00 | 0.00 |
June | 71.09 | 12.99 | 58.10 | 105.12 | 21.44 | 0.00 | 0.00 | 0.00 |
July | 74.00 | 13.25 | 60.75 | 109.84 | 19.71 | 0.00 | 0.00 | 0.00 |
August | 94.22 | 39.39 | 54.83 | 139.85 | 22.72 | 0.00 | 0.00 | 0.00 |
September | 121.23 | 67.64 | 53.58 | 168.78 | 34.61 | 0.00 | 0.00 | 0.00 |
October | 144.95 | 102.85 | 42.11 | 180.46 | 68.44 | 0.00 | 0.00 | 0.00 |
November | 176.60 | 140.78 | 35.83 | 213.95 | 76.16 | 0.00 | 0.00 | 0.00 |
December | 168.88 | 136.69 | 32.19 | 196.40 | 90.14 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 124.88 | 77.87 | 47.02 | 156.54 | 54.61 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 71.09 | 12.99 | 32.19 | 92.22 | 19.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 183.71 | 151.12 | 62.98 | 218.39 | 90.14 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 183.71 | 151.12 | 32.59 | 218.39 | 79.34 | 0.00 | 0.00 | 0.00 |
February | 176.21 | 140.49 | 35.72 | 208.50 | 82.21 | 0.00 | 0.00 | 0.00 |
March | 129.92 | 85.48 | 44.44 | 155.67 | 65.57 | 0.00 | 0.00 | 0.00 |
April | 84.14 | 33.83 | 50.31 | 92.94 | 59.20 | 0.00 | 0.00 | 0.00 |
May | 77.11 | 14.13 | 62.98 | 92.22 | 37.63 | 0.00 | 0.00 | 0.00 |
June | 71.09 | 12.99 | 58.10 | 105.12 | 21.44 | 0.00 | 0.00 | 0.00 |
July | 74.00 | 13.25 | 60.75 | 109.84 | 19.71 | 0.00 | 0.00 | 0.00 |
August | 94.22 | 39.39 | 54.83 | 139.85 | 22.72 | 0.00 | 0.00 | 0.00 |
September | 121.23 | 67.64 | 53.58 | 168.78 | 34.61 | 0.00 | 0.00 | 0.00 |
October | 144.95 | 102.85 | 42.11 | 180.46 | 68.44 | 0.00 | 0.00 | 0.00 |
November | 176.60 | 140.78 | 35.83 | 213.95 | 76.16 | 0.00 | 0.00 | 0.00 |
December | 168.88 | 136.69 | 32.19 | 196.40 | 90.14 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 124.88 | 77.87 | 47.02 | 156.54 | 54.61 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 71.09 | 12.99 | 32.19 | 92.22 | 19.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 183.71 | 151.12 | 62.98 | 218.39 | 90.14 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 219.64 | 180.68 | 38.96 | 261.48 | 93.85 | 0.00 | 0.00 | 0.00 |
February | 210.68 | 167.97 | 42.71 | 249.82 | 97.08 | 0.00 | 0.00 | 0.00 |
March | 155.33 | 102.20 | 53.13 | 186.48 | 77.46 | 0.00 | 0.00 | 0.00 |
April | 100.60 | 40.45 | 60.15 | 111.45 | 69.88 | 0.00 | 0.00 | 0.00 |
May | 92.19 | 16.90 | 75.29 | 110.44 | 44.53 | 0.00 | 0.00 | 0.00 |
June | 85.00 | 15.53 | 69.46 | 125.50 | 25.52 | 0.00 | 0.00 | 0.00 |
July | 88.48 | 15.84 | 72.64 | 131.15 | 23.45 | 0.00 | 0.00 | 0.00 |
August | 112.65 | 47.09 | 65.56 | 167.07 | 27.03 | 0.00 | 0.00 | 0.00 |
September | 144.94 | 80.87 | 64.06 | 201.79 | 41.11 | 0.00 | 0.00 | 0.00 |
October | 173.30 | 122.96 | 50.34 | 215.93 | 80.94 | 0.00 | 0.00 | 0.00 |
November | 211.15 | 168.31 | 42.83 | 256.16 | 90.05 | 0.00 | 0.00 | 0.00 |
December | 201.91 | 163.42 | 38.49 | 235.34 | 106.43 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 149.31 | 93.10 | 56.21 | 187.36 | 64.60 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 85.00 | 15.53 | 38.49 | 110.44 | 23.45 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 219.64 | 180.68 | 75.29 | 261.48 | 106.43 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 183.71 | 151.12 | 32.59 | 218.51 | 79.06 | 0.00 | 0.00 | 0.00 |
February | 176.21 | 140.49 | 35.72 | 208.61 | 81.95 | 0.00 | 0.00 | 0.00 |
March | 129.92 | 85.48 | 44.44 | 155.77 | 65.31 | 0.00 | 0.00 | 0.00 |
April | 84.14 | 33.83 | 50.31 | 93.04 | 58.94 | 0.00 | 0.00 | 0.00 |
May | 77.11 | 14.13 | 62.98 | 92.38 | 37.42 | 0.00 | 0.00 | 0.00 |
June | 71.09 | 12.99 | 58.10 | 105.20 | 21.34 | 0.00 | 0.00 | 0.00 |
July | 74.00 | 13.25 | 60.75 | 109.91 | 19.62 | 0.00 | 0.00 | 0.00 |
August | 94.22 | 39.39 | 54.83 | 139.90 | 22.63 | 0.00 | 0.00 | 0.00 |
September | 121.23 | 67.64 | 53.58 | 168.84 | 34.51 | 0.00 | 0.00 | 0.00 |
October | 144.95 | 102.85 | 42.11 | 180.53 | 68.26 | 0.00 | 0.00 | 0.00 |
November | 176.60 | 140.78 | 35.83 | 214.04 | 75.94 | 0.00 | 0.00 | 0.00 |
December | 168.88 | 136.69 | 32.19 | 196.49 | 89.91 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 124.88 | 77.87 | 47.02 | 156.64 | 54.42 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 71.09 | 12.99 | 32.19 | 92.38 | 19.62 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 183.71 | 151.12 | 62.98 | 218.51 | 89.91 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 183.71 | 151.12 | 32.59 | 218.51 | 79.06 | 0.00 | 0.00 | 0.00 |
February | 176.21 | 140.49 | 35.72 | 208.61 | 81.95 | 0.00 | 0.00 | 0.00 |
March | 129.92 | 85.48 | 44.44 | 155.77 | 65.31 | 0.00 | 0.00 | 0.00 |
April | 84.14 | 33.83 | 50.31 | 93.04 | 58.94 | 0.00 | 0.00 | 0.00 |
May | 77.11 | 14.13 | 62.98 | 92.38 | 37.42 | 0.00 | 0.00 | 0.00 |
June | 71.09 | 12.99 | 58.10 | 105.20 | 21.34 | 0.00 | 0.00 | 0.00 |
July | 74.00 | 13.25 | 60.75 | 109.91 | 19.62 | 0.00 | 0.00 | 0.00 |
August | 94.22 | 39.39 | 54.83 | 139.90 | 22.63 | 0.00 | 0.00 | 0.00 |
September | 121.23 | 67.64 | 53.58 | 168.84 | 34.51 | 0.00 | 0.00 | 0.00 |
October | 144.95 | 102.85 | 42.11 | 180.53 | 68.26 | 0.00 | 0.00 | 0.00 |
November | 176.60 | 140.78 | 35.83 | 214.04 | 75.94 | 0.00 | 0.00 | 0.00 |
December | 168.88 | 136.69 | 32.19 | 196.49 | 89.91 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 124.88 | 77.87 | 47.02 | 156.64 | 54.42 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 71.09 | 12.99 | 32.19 | 92.38 | 19.62 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 183.71 | 151.12 | 62.98 | 218.51 | 89.91 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 219.64 | 180.68 | 38.96 | 261.62 | 93.52 | 0.00 | 0.00 | 0.00 |
February | 210.68 | 167.97 | 42.71 | 249.95 | 96.77 | 0.00 | 0.00 | 0.00 |
March | 155.33 | 102.20 | 53.13 | 186.61 | 77.16 | 0.00 | 0.00 | 0.00 |
April | 100.60 | 40.45 | 60.15 | 111.57 | 69.57 | 0.00 | 0.00 | 0.00 |
May | 92.19 | 16.90 | 75.29 | 110.62 | 44.28 | 0.00 | 0.00 | 0.00 |
June | 85.00 | 15.53 | 69.46 | 125.60 | 25.39 | 0.00 | 0.00 | 0.00 |
July | 88.48 | 15.84 | 72.64 | 131.23 | 23.34 | 0.00 | 0.00 | 0.00 |
August | 112.65 | 47.09 | 65.56 | 167.14 | 26.92 | 0.00 | 0.00 | 0.00 |
September | 144.94 | 80.87 | 64.06 | 201.86 | 40.99 | 0.00 | 0.00 | 0.00 |
October | 173.30 | 122.96 | 50.34 | 216.02 | 80.72 | 0.00 | 0.00 | 0.00 |
November | 211.15 | 168.31 | 42.83 | 256.28 | 89.79 | 0.00 | 0.00 | 0.00 |
December | 201.91 | 163.42 | 38.49 | 235.44 | 106.16 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 149.31 | 93.10 | 56.21 | 187.47 | 64.37 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 85.00 | 15.53 | 38.49 | 110.62 | 23.34 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 219.64 | 180.68 | 75.29 | 261.62 | 106.16 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 183.71 | 151.12 | 32.59 | 218.97 | 77.88 | 0.00 | 0.00 | 0.00 |
February | 176.21 | 140.49 | 35.72 | 209.03 | 80.82 | 0.00 | 0.00 | 0.00 |
March | 129.92 | 85.48 | 44.44 | 156.22 | 64.11 | 0.00 | 0.00 | 0.00 |
April | 84.14 | 33.83 | 50.31 | 93.47 | 57.64 | 0.00 | 0.00 | 0.00 |
May | 77.11 | 14.13 | 62.98 | 93.07 | 36.40 | 0.00 | 0.00 | 0.00 |
June | 71.09 | 12.99 | 58.10 | 105.37 | 21.04 | 0.00 | 0.00 | 0.00 |
July | 74.00 | 13.25 | 60.75 | 110.05 | 19.37 | 0.00 | 0.00 | 0.00 |
August | 94.22 | 39.39 | 54.83 | 140.01 | 22.40 | 0.00 | 0.00 | 0.00 |
September | 121.23 | 67.64 | 53.58 | 168.98 | 34.18 | 0.00 | 0.00 | 0.00 |
October | 144.95 | 102.85 | 42.11 | 180.90 | 67.27 | 0.00 | 0.00 | 0.00 |
November | 176.60 | 140.78 | 35.83 | 214.44 | 74.92 | 0.00 | 0.00 | 0.00 |
December | 168.88 | 136.69 | 32.19 | 196.83 | 88.84 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 124.88 | 77.87 | 47.02 | 156.98 | 53.59 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 71.09 | 12.99 | 32.19 | 93.07 | 19.37 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 183.71 | 151.12 | 62.98 | 218.97 | 88.84 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 183.71 | 151.12 | 32.59 | 218.97 | 77.88 | 0.00 | 0.00 | 0.00 |
February | 176.21 | 140.49 | 35.72 | 209.03 | 80.82 | 0.00 | 0.00 | 0.00 |
March | 129.92 | 85.48 | 44.44 | 156.22 | 64.11 | 0.00 | 0.00 | 0.00 |
April | 84.14 | 33.83 | 50.31 | 93.47 | 57.64 | 0.00 | 0.00 | 0.00 |
May | 77.11 | 14.13 | 62.98 | 93.07 | 36.40 | 0.00 | 0.00 | 0.00 |
June | 71.09 | 12.99 | 58.10 | 105.37 | 21.04 | 0.00 | 0.00 | 0.00 |
July | 74.00 | 13.25 | 60.75 | 110.05 | 19.37 | 0.00 | 0.00 | 0.00 |
August | 94.22 | 39.39 | 54.83 | 140.01 | 22.40 | 0.00 | 0.00 | 0.00 |
September | 121.23 | 67.64 | 53.58 | 168.98 | 34.18 | 0.00 | 0.00 | 0.00 |
October | 144.95 | 102.85 | 42.11 | 180.90 | 67.27 | 0.00 | 0.00 | 0.00 |
November | 176.60 | 140.78 | 35.83 | 214.44 | 74.92 | 0.00 | 0.00 | 0.00 |
December | 168.88 | 136.69 | 32.19 | 196.83 | 88.84 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 124.88 | 77.87 | 47.02 | 156.98 | 53.59 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 71.09 | 12.99 | 32.19 | 93.07 | 19.37 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 183.71 | 151.12 | 62.98 | 218.97 | 88.84 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 219.64 | 180.68 | 38.96 | 262.17 | 92.12 | 0.00 | 0.00 | 0.00 |
February | 210.68 | 167.97 | 42.71 | 250.45 | 95.43 | 0.00 | 0.00 | 0.00 |
March | 155.33 | 102.20 | 53.13 | 187.15 | 75.73 | 0.00 | 0.00 | 0.00 |
April | 100.60 | 40.45 | 60.15 | 112.09 | 68.04 | 0.00 | 0.00 | 0.00 |
May | 92.19 | 16.90 | 75.29 | 111.45 | 43.07 | 0.00 | 0.00 | 0.00 |
June | 85.00 | 15.53 | 69.46 | 125.81 | 25.05 | 0.00 | 0.00 | 0.00 |
July | 88.48 | 15.84 | 72.64 | 131.39 | 23.04 | 0.00 | 0.00 | 0.00 |
August | 112.65 | 47.09 | 65.56 | 167.27 | 26.65 | 0.00 | 0.00 | 0.00 |
September | 144.94 | 80.87 | 64.06 | 202.02 | 40.60 | 0.00 | 0.00 | 0.00 |
October | 173.30 | 122.96 | 50.34 | 216.47 | 79.56 | 0.00 | 0.00 | 0.00 |
November | 211.15 | 168.31 | 42.83 | 256.75 | 88.57 | 0.00 | 0.00 | 0.00 |
December | 201.91 | 163.42 | 38.49 | 235.86 | 104.90 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 149.31 | 93.10 | 56.21 | 187.88 | 63.39 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 85.00 | 15.53 | 38.49 | 111.45 | 23.04 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 219.64 | 180.68 | 75.29 | 262.17 | 104.90 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 183.71 | 151.12 | 32.59 | 220.41 | 73.46 | 0.00 | 0.00 | 0.00 |
February | 176.21 | 140.49 | 35.72 | 210.39 | 76.26 | 0.00 | 0.00 | 0.00 |
March | 129.92 | 85.48 | 44.44 | 157.56 | 59.46 | 0.00 | 0.00 | 0.00 |
April | 84.14 | 33.83 | 50.31 | 94.69 | 52.87 | 0.00 | 0.00 | 0.00 |
May | 77.11 | 14.13 | 62.98 | 95.04 | 33.01 | 0.00 | 0.00 | 0.00 |
June | 71.09 | 12.99 | 58.10 | 105.66 | 19.87 | 0.00 | 0.00 | 0.00 |
July | 74.00 | 13.25 | 60.75 | 110.27 | 18.34 | 0.00 | 0.00 | 0.00 |
August | 94.22 | 39.39 | 54.83 | 140.05 | 21.50 | 0.00 | 0.00 | 0.00 |
September | 121.23 | 67.64 | 53.58 | 169.19 | 32.92 | 0.00 | 0.00 | 0.00 |
October | 144.95 | 102.85 | 42.11 | 181.96 | 63.69 | 0.00 | 0.00 | 0.00 |
November | 176.60 | 140.78 | 35.83 | 215.61 | 71.18 | 0.00 | 0.00 | 0.00 |
December | 168.88 | 136.69 | 32.19 | 197.96 | 84.66 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 124.88 | 77.87 | 47.02 | 157.94 | 50.46 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 71.09 | 12.99 | 32.19 | 94.69 | 18.34 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 183.71 | 151.12 | 62.98 | 220.41 | 84.66 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 183.71 | 151.12 | 32.59 | 220.41 | 73.46 | 0.00 | 0.00 | 0.00 |
February | 176.21 | 140.49 | 35.72 | 210.39 | 76.26 | 0.00 | 0.00 | 0.00 |
March | 129.92 | 85.48 | 44.44 | 157.56 | 59.46 | 0.00 | 0.00 | 0.00 |
April | 84.14 | 33.83 | 50.31 | 94.69 | 52.87 | 0.00 | 0.00 | 0.00 |
May | 77.11 | 14.13 | 62.98 | 95.04 | 33.01 | 0.00 | 0.00 | 0.00 |
June | 71.09 | 12.99 | 58.10 | 105.66 | 19.87 | 0.00 | 0.00 | 0.00 |
July | 74.00 | 13.25 | 60.75 | 110.27 | 18.34 | 0.00 | 0.00 | 0.00 |
August | 94.22 | 39.39 | 54.83 | 140.05 | 21.50 | 0.00 | 0.00 | 0.00 |
September | 121.23 | 67.64 | 53.58 | 169.19 | 32.92 | 0.00 | 0.00 | 0.00 |
October | 144.95 | 102.85 | 42.11 | 181.96 | 63.69 | 0.00 | 0.00 | 0.00 |
November | 176.60 | 140.78 | 35.83 | 215.61 | 71.18 | 0.00 | 0.00 | 0.00 |
December | 168.88 | 136.69 | 32.19 | 197.96 | 84.66 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 124.88 | 77.87 | 47.02 | 157.94 | 50.46 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 71.09 | 12.99 | 32.19 | 94.69 | 18.34 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 183.71 | 151.12 | 62.98 | 220.41 | 84.66 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 219.64 | 180.68 | 38.96 | 263.90 | 86.89 | 0.00 | 0.00 | 0.00 |
February | 210.68 | 167.97 | 42.71 | 252.09 | 90.04 | 0.00 | 0.00 | 0.00 |
March | 155.33 | 102.20 | 53.13 | 188.75 | 70.24 | 0.00 | 0.00 | 0.00 |
April | 100.60 | 40.45 | 60.15 | 113.55 | 62.42 | 0.00 | 0.00 | 0.00 |
May | 92.19 | 16.90 | 75.29 | 113.79 | 39.09 | 0.00 | 0.00 | 0.00 |
June | 85.00 | 15.53 | 69.46 | 126.15 | 23.67 | 0.00 | 0.00 | 0.00 |
July | 88.48 | 15.84 | 72.64 | 131.65 | 21.83 | 0.00 | 0.00 | 0.00 |
August | 112.65 | 47.09 | 65.56 | 167.32 | 25.59 | 0.00 | 0.00 | 0.00 |
September | 144.94 | 80.87 | 64.06 | 202.28 | 39.12 | 0.00 | 0.00 | 0.00 |
October | 173.30 | 122.96 | 50.34 | 217.73 | 75.33 | 0.00 | 0.00 | 0.00 |
November | 211.15 | 168.31 | 42.83 | 258.15 | 84.16 | 0.00 | 0.00 | 0.00 |
December | 201.91 | 163.42 | 38.49 | 237.21 | 99.95 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 149.31 | 93.10 | 56.21 | 189.02 | 59.70 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 85.00 | 15.53 | 38.49 | 113.55 | 21.83 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 219.64 | 180.68 | 75.29 | 263.90 | 99.95 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.492050E+09 | 0.404765E+09 | 87285918.10 | 0.586024E+09 | 0.214010E+09 |
February | 0.426293E+09 | 0.339868E+09 | 86425364.41 | 0.505652E+09 | 0.200541E+09 |
March | 0.347971E+09 | 0.228945E+09 | 0.119026E+09 | 0.418168E+09 | 0.176451E+09 |
April | 0.218102E+09 | 87699567.97 | 0.130402E+09 | 0.241713E+09 | 0.154579E+09 |
May | 0.206528E+09 | 37855190.50 | 0.168673E+09 | 0.248297E+09 | 0.100600E+09 |
June | 0.184270E+09 | 33679383.33 | 0.150591E+09 | 0.273241E+09 | 54513098.47 |
July | 0.198215E+09 | 35494756.84 | 0.162720E+09 | 0.295563E+09 | 50980684.45 |
August | 0.252368E+09 | 0.105499E+09 | 0.146869E+09 | 0.375266E+09 | 59514576.63 |
September | 0.314222E+09 | 0.175334E+09 | 0.138888E+09 | 0.438507E+09 | 88127128.95 |
October | 0.388241E+09 | 0.275466E+09 | 0.112775E+09 | 0.484955E+09 | 0.182332E+09 |
November | 0.457759E+09 | 0.364901E+09 | 92858727.99 | 0.555618E+09 | 0.197965E+09 |
December | 0.452329E+09 | 0.366109E+09 | 86219998.75 | 0.526905E+09 | 0.243879E+09 |
Annual Sum or Average | 0.393835E+10 | 0.245562E+10 | 0.148273E+10 | 0.494991E+10 | 0.172349E+10 |
Minimum of Months | 0.184270E+09 | 33679383.33 | 86219998.75 | 0.241713E+09 | 50980684.45 |
Maximum of Months | 0.492050E+09 | 0.404765E+09 | 0.168673E+09 | 0.586024E+09 | 0.243879E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.492050E+09 | 0.404765E+09 | 87285918.10 | 0.586024E+09 | 0.214010E+09 |
February | 0.426293E+09 | 0.339868E+09 | 86425364.41 | 0.505652E+09 | 0.200541E+09 |
March | 0.347971E+09 | 0.228945E+09 | 0.119026E+09 | 0.418168E+09 | 0.176451E+09 |
April | 0.218102E+09 | 87699567.97 | 0.130402E+09 | 0.241713E+09 | 0.154579E+09 |
May | 0.206528E+09 | 37855190.50 | 0.168673E+09 | 0.248297E+09 | 0.100600E+09 |
June | 0.184270E+09 | 33679383.33 | 0.150591E+09 | 0.273241E+09 | 54513098.47 |
July | 0.198215E+09 | 35494756.84 | 0.162720E+09 | 0.295563E+09 | 50980684.45 |
August | 0.252368E+09 | 0.105499E+09 | 0.146869E+09 | 0.375266E+09 | 59514576.63 |
September | 0.314222E+09 | 0.175334E+09 | 0.138888E+09 | 0.438507E+09 | 88127128.95 |
October | 0.388241E+09 | 0.275466E+09 | 0.112775E+09 | 0.484955E+09 | 0.182332E+09 |
November | 0.457759E+09 | 0.364901E+09 | 92858727.99 | 0.555618E+09 | 0.197965E+09 |
December | 0.452329E+09 | 0.366109E+09 | 86219998.75 | 0.526905E+09 | 0.243879E+09 |
Annual Sum or Average | 0.393835E+10 | 0.245562E+10 | 0.148273E+10 | 0.494991E+10 | 0.172349E+10 |
Minimum of Months | 0.184270E+09 | 33679383.33 | 86219998.75 | 0.241713E+09 | 50980684.45 |
Maximum of Months | 0.492050E+09 | 0.404765E+09 | 0.168673E+09 | 0.586024E+09 | 0.243879E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.492050E+09 | 0.404765E+09 | 87285918.10 | 0.586024E+09 | 0.214010E+09 |
February | 0.426293E+09 | 0.339868E+09 | 86425364.41 | 0.505652E+09 | 0.200541E+09 |
March | 0.347971E+09 | 0.228945E+09 | 0.119026E+09 | 0.418168E+09 | 0.176451E+09 |
April | 0.218102E+09 | 87699567.97 | 0.130402E+09 | 0.241713E+09 | 0.154579E+09 |
May | 0.206528E+09 | 37855190.50 | 0.168673E+09 | 0.248297E+09 | 0.100600E+09 |
June | 0.184270E+09 | 33679383.33 | 0.150591E+09 | 0.273241E+09 | 54513098.47 |
July | 0.198215E+09 | 35494756.84 | 0.162720E+09 | 0.295563E+09 | 50980684.45 |
August | 0.252368E+09 | 0.105499E+09 | 0.146869E+09 | 0.375266E+09 | 59514576.63 |
September | 0.314222E+09 | 0.175334E+09 | 0.138888E+09 | 0.438507E+09 | 88127128.95 |
October | 0.388241E+09 | 0.275466E+09 | 0.112775E+09 | 0.484955E+09 | 0.182332E+09 |
November | 0.457759E+09 | 0.364901E+09 | 92858727.99 | 0.555618E+09 | 0.197965E+09 |
December | 0.452329E+09 | 0.366109E+09 | 86219998.75 | 0.526905E+09 | 0.243879E+09 |
Annual Sum or Average | 0.393835E+10 | 0.245562E+10 | 0.148273E+10 | 0.494991E+10 | 0.172349E+10 |
Minimum of Months | 0.184270E+09 | 33679383.33 | 86219998.75 | 0.241713E+09 | 50980684.45 |
Maximum of Months | 0.492050E+09 | 0.404765E+09 | 0.168673E+09 | 0.586024E+09 | 0.243879E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.492050E+09 | 0.404765E+09 | 87285918.10 | 0.586024E+09 | 0.214010E+09 |
February | 0.426293E+09 | 0.339868E+09 | 86425364.41 | 0.505652E+09 | 0.200541E+09 |
March | 0.347971E+09 | 0.228945E+09 | 0.119026E+09 | 0.418168E+09 | 0.176451E+09 |
April | 0.218102E+09 | 87699567.97 | 0.130402E+09 | 0.241713E+09 | 0.154579E+09 |
May | 0.206528E+09 | 37855190.50 | 0.168673E+09 | 0.248297E+09 | 0.100600E+09 |
June | 0.184270E+09 | 33679383.33 | 0.150591E+09 | 0.273241E+09 | 54513098.47 |
July | 0.198215E+09 | 35494756.84 | 0.162720E+09 | 0.295563E+09 | 50980684.45 |
August | 0.252368E+09 | 0.105499E+09 | 0.146869E+09 | 0.375266E+09 | 59514576.63 |
September | 0.314222E+09 | 0.175334E+09 | 0.138888E+09 | 0.438507E+09 | 88127128.95 |
October | 0.388241E+09 | 0.275466E+09 | 0.112775E+09 | 0.484955E+09 | 0.182332E+09 |
November | 0.457759E+09 | 0.364901E+09 | 92858727.99 | 0.555618E+09 | 0.197965E+09 |
December | 0.452329E+09 | 0.366109E+09 | 86219998.75 | 0.526905E+09 | 0.243879E+09 |
Annual Sum or Average | 0.393835E+10 | 0.245562E+10 | 0.148273E+10 | 0.494991E+10 | 0.172349E+10 |
Minimum of Months | 0.184270E+09 | 33679383.33 | 86219998.75 | 0.241713E+09 | 50980684.45 |
Maximum of Months | 0.492050E+09 | 0.404765E+09 | 0.168673E+09 | 0.586024E+09 | 0.243879E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.591520E+09 | 0.486589E+09 | 0.104931E+09 | 0.705334E+09 | 0.254658E+09 |
February | 0.512470E+09 | 0.408574E+09 | 0.103897E+09 | 0.609006E+09 | 0.238209E+09 |
March | 0.418315E+09 | 0.275227E+09 | 0.143087E+09 | 0.503546E+09 | 0.209677E+09 |
April | 0.262192E+09 | 0.105428E+09 | 0.156764E+09 | 0.291342E+09 | 0.183574E+09 |
May | 0.248279E+09 | 45507766.82 | 0.202771E+09 | 0.298856E+09 | 0.119754E+09 |
June | 0.221521E+09 | 40487803.74 | 0.181033E+09 | 0.327960E+09 | 65280312.81 |
July | 0.238285E+09 | 42670162.17 | 0.195615E+09 | 0.354753E+09 | 61034049.28 |
August | 0.303385E+09 | 0.126826E+09 | 0.176559E+09 | 0.450696E+09 | 71244305.14 |
September | 0.377743E+09 | 0.210778E+09 | 0.166964E+09 | 0.527032E+09 | 0.105322E+09 |
October | 0.466726E+09 | 0.331153E+09 | 0.135573E+09 | 0.583335E+09 | 0.216953E+09 |
November | 0.550297E+09 | 0.438667E+09 | 0.111630E+09 | 0.668729E+09 | 0.235471E+09 |
December | 0.543769E+09 | 0.440119E+09 | 0.103650E+09 | 0.634674E+09 | 0.289661E+09 |
Annual Sum or Average | 0.473450E+10 | 0.295203E+10 | 0.178247E+10 | 0.595526E+10 | 0.205084E+10 |
Minimum of Months | 0.221521E+09 | 40487803.74 | 0.103650E+09 | 0.291342E+09 | 61034049.28 |
Maximum of Months | 0.591520E+09 | 0.486589E+09 | 0.202771E+09 | 0.705334E+09 | 0.289661E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.591520E+09 | 0.486589E+09 | 0.104931E+09 | 0.705334E+09 | 0.254658E+09 |
February | 0.512470E+09 | 0.408574E+09 | 0.103897E+09 | 0.609006E+09 | 0.238209E+09 |
March | 0.418315E+09 | 0.275227E+09 | 0.143087E+09 | 0.503546E+09 | 0.209677E+09 |
April | 0.262192E+09 | 0.105428E+09 | 0.156764E+09 | 0.291342E+09 | 0.183574E+09 |
May | 0.248279E+09 | 45507766.82 | 0.202771E+09 | 0.298856E+09 | 0.119754E+09 |
June | 0.221521E+09 | 40487803.74 | 0.181033E+09 | 0.327960E+09 | 65280312.81 |
July | 0.238285E+09 | 42670162.17 | 0.195615E+09 | 0.354753E+09 | 61034049.28 |
August | 0.303385E+09 | 0.126826E+09 | 0.176559E+09 | 0.450696E+09 | 71244305.14 |
September | 0.377743E+09 | 0.210778E+09 | 0.166964E+09 | 0.527032E+09 | 0.105322E+09 |
October | 0.466726E+09 | 0.331153E+09 | 0.135573E+09 | 0.583335E+09 | 0.216953E+09 |
November | 0.550297E+09 | 0.438667E+09 | 0.111630E+09 | 0.668729E+09 | 0.235471E+09 |
December | 0.543769E+09 | 0.440119E+09 | 0.103650E+09 | 0.634674E+09 | 0.289661E+09 |
Annual Sum or Average | 0.473450E+10 | 0.295203E+10 | 0.178247E+10 | 0.595526E+10 | 0.205084E+10 |
Minimum of Months | 0.221521E+09 | 40487803.74 | 0.103650E+09 | 0.291342E+09 | 61034049.28 |
Maximum of Months | 0.591520E+09 | 0.486589E+09 | 0.202771E+09 | 0.705334E+09 | 0.289661E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.492050E+09 | 0.404765E+09 | 87285918.10 | 0.581593E+09 | 0.225056E+09 |
February | 0.426293E+09 | 0.339868E+09 | 86425364.41 | 0.501730E+09 | 0.210136E+09 |
March | 0.347971E+09 | 0.228945E+09 | 0.119026E+09 | 0.414260E+09 | 0.186599E+09 |
April | 0.218102E+09 | 87699567.97 | 0.130402E+09 | 0.238098E+09 | 0.165675E+09 |
May | 0.206528E+09 | 37855190.50 | 0.168673E+09 | 0.244514E+09 | 0.106531E+09 |
June | 0.184270E+09 | 33679383.33 | 0.150591E+09 | 0.272803E+09 | 55270071.63 |
July | 0.198215E+09 | 35494756.84 | 0.162720E+09 | 0.295123E+09 | 51837835.32 |
August | 0.252368E+09 | 0.105499E+09 | 0.146869E+09 | 0.374906E+09 | 60093674.06 |
September | 0.314222E+09 | 0.175334E+09 | 0.138888E+09 | 0.437663E+09 | 89654808.34 |
October | 0.388241E+09 | 0.275466E+09 | 0.112775E+09 | 0.482183E+09 | 0.190019E+09 |
November | 0.457759E+09 | 0.364901E+09 | 92858727.99 | 0.551932E+09 | 0.207811E+09 |
December | 0.452329E+09 | 0.366109E+09 | 86219998.75 | 0.523031E+09 | 0.254580E+09 |
Annual Sum or Average | 0.393835E+10 | 0.245562E+10 | 0.148273E+10 | 0.491784E+10 | 0.180326E+10 |
Minimum of Months | 0.184270E+09 | 33679383.33 | 86219998.75 | 0.238098E+09 | 51837835.32 |
Maximum of Months | 0.492050E+09 | 0.404765E+09 | 0.168673E+09 | 0.581593E+09 | 0.254580E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.492050E+09 | 0.404765E+09 | 87285918.10 | 0.581593E+09 | 0.225056E+09 |
February | 0.426293E+09 | 0.339868E+09 | 86425364.41 | 0.501730E+09 | 0.210136E+09 |
March | 0.347971E+09 | 0.228945E+09 | 0.119026E+09 | 0.414260E+09 | 0.186599E+09 |
April | 0.218102E+09 | 87699567.97 | 0.130402E+09 | 0.238098E+09 | 0.165675E+09 |
May | 0.206528E+09 | 37855190.50 | 0.168673E+09 | 0.244514E+09 | 0.106531E+09 |
June | 0.184270E+09 | 33679383.33 | 0.150591E+09 | 0.272803E+09 | 55270071.63 |
July | 0.198215E+09 | 35494756.84 | 0.162720E+09 | 0.295123E+09 | 51837835.32 |
August | 0.252368E+09 | 0.105499E+09 | 0.146869E+09 | 0.374906E+09 | 60093674.06 |
September | 0.314222E+09 | 0.175334E+09 | 0.138888E+09 | 0.437663E+09 | 89654808.34 |
October | 0.388241E+09 | 0.275466E+09 | 0.112775E+09 | 0.482183E+09 | 0.190019E+09 |
November | 0.457759E+09 | 0.364901E+09 | 92858727.99 | 0.551932E+09 | 0.207811E+09 |
December | 0.452329E+09 | 0.366109E+09 | 86219998.75 | 0.523031E+09 | 0.254580E+09 |
Annual Sum or Average | 0.393835E+10 | 0.245562E+10 | 0.148273E+10 | 0.491784E+10 | 0.180326E+10 |
Minimum of Months | 0.184270E+09 | 33679383.33 | 86219998.75 | 0.238098E+09 | 51837835.32 |
Maximum of Months | 0.492050E+09 | 0.404765E+09 | 0.168673E+09 | 0.581593E+09 | 0.254580E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.591520E+09 | 0.486589E+09 | 0.104931E+09 | 0.700129E+09 | 0.267663E+09 |
February | 0.512470E+09 | 0.408574E+09 | 0.103897E+09 | 0.604428E+09 | 0.249482E+09 |
March | 0.418315E+09 | 0.275227E+09 | 0.143087E+09 | 0.498963E+09 | 0.221625E+09 |
April | 0.262192E+09 | 0.105428E+09 | 0.156764E+09 | 0.287058E+09 | 0.196613E+09 |
May | 0.248279E+09 | 45507766.82 | 0.202771E+09 | 0.294378E+09 | 0.126728E+09 |
June | 0.221521E+09 | 40487803.74 | 0.181033E+09 | 0.327448E+09 | 66178554.93 |
July | 0.238285E+09 | 42670162.17 | 0.195615E+09 | 0.354244E+09 | 62054760.83 |
August | 0.303385E+09 | 0.126826E+09 | 0.176559E+09 | 0.450311E+09 | 71931000.31 |
September | 0.377743E+09 | 0.210778E+09 | 0.166964E+09 | 0.526085E+09 | 0.107109E+09 |
October | 0.466726E+09 | 0.331153E+09 | 0.135573E+09 | 0.580117E+09 | 0.225982E+09 |
November | 0.550297E+09 | 0.438667E+09 | 0.111630E+09 | 0.664434E+09 | 0.247031E+09 |
December | 0.543769E+09 | 0.440119E+09 | 0.103650E+09 | 0.630154E+09 | 0.302203E+09 |
Annual Sum or Average | 0.473450E+10 | 0.295203E+10 | 0.178247E+10 | 0.591775E+10 | 0.214460E+10 |
Minimum of Months | 0.221521E+09 | 40487803.74 | 0.103650E+09 | 0.287058E+09 | 62054760.83 |
Maximum of Months | 0.591520E+09 | 0.486589E+09 | 0.202771E+09 | 0.700129E+09 | 0.302203E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.492050E+09 | 0.404765E+09 | 87285918.10 | 0.582403E+09 | 0.220600E+09 |
February | 0.426293E+09 | 0.339868E+09 | 86425364.41 | 0.502324E+09 | 0.206024E+09 |
March | 0.347971E+09 | 0.228945E+09 | 0.119026E+09 | 0.414818E+09 | 0.183315E+09 |
April | 0.218102E+09 | 87699567.97 | 0.130402E+09 | 0.238789E+09 | 0.161738E+09 |
May | 0.206528E+09 | 37855190.50 | 0.168673E+09 | 0.244861E+09 | 0.106479E+09 |
June | 0.184270E+09 | 33679383.33 | 0.150591E+09 | 0.271858E+09 | 59022190.70 |
July | 0.198215E+09 | 35494756.84 | 0.162720E+09 | 0.293800E+09 | 55936499.18 |
August | 0.252368E+09 | 0.105499E+09 | 0.146869E+09 | 0.374316E+09 | 64298294.50 |
September | 0.314222E+09 | 0.175334E+09 | 0.138888E+09 | 0.437243E+09 | 93090197.90 |
October | 0.388241E+09 | 0.275466E+09 | 0.112775E+09 | 0.482590E+09 | 0.188854E+09 |
November | 0.457759E+09 | 0.364901E+09 | 92858727.99 | 0.552812E+09 | 0.204182E+09 |
December | 0.452329E+09 | 0.366109E+09 | 86219998.75 | 0.523692E+09 | 0.249724E+09 |
Annual Sum or Average | 0.393835E+10 | 0.245562E+10 | 0.148273E+10 | 0.491951E+10 | 0.179326E+10 |
Minimum of Months | 0.184270E+09 | 33679383.33 | 86219998.75 | 0.238789E+09 | 55936499.18 |
Maximum of Months | 0.492050E+09 | 0.404765E+09 | 0.168673E+09 | 0.582403E+09 | 0.249724E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.492050E+09 | 0.404765E+09 | 87285918.10 | 0.582403E+09 | 0.220600E+09 |
February | 0.426293E+09 | 0.339868E+09 | 86425364.41 | 0.502324E+09 | 0.206024E+09 |
March | 0.347971E+09 | 0.228945E+09 | 0.119026E+09 | 0.414818E+09 | 0.183315E+09 |
April | 0.218102E+09 | 87699567.97 | 0.130402E+09 | 0.238789E+09 | 0.161738E+09 |
May | 0.206528E+09 | 37855190.50 | 0.168673E+09 | 0.244861E+09 | 0.106479E+09 |
June | 0.184270E+09 | 33679383.33 | 0.150591E+09 | 0.271858E+09 | 59022190.70 |
July | 0.198215E+09 | 35494756.84 | 0.162720E+09 | 0.293800E+09 | 55936499.18 |
August | 0.252368E+09 | 0.105499E+09 | 0.146869E+09 | 0.374316E+09 | 64298294.50 |
September | 0.314222E+09 | 0.175334E+09 | 0.138888E+09 | 0.437243E+09 | 93090197.90 |
October | 0.388241E+09 | 0.275466E+09 | 0.112775E+09 | 0.482590E+09 | 0.188854E+09 |
November | 0.457759E+09 | 0.364901E+09 | 92858727.99 | 0.552812E+09 | 0.204182E+09 |
December | 0.452329E+09 | 0.366109E+09 | 86219998.75 | 0.523692E+09 | 0.249724E+09 |
Annual Sum or Average | 0.393835E+10 | 0.245562E+10 | 0.148273E+10 | 0.491951E+10 | 0.179326E+10 |
Minimum of Months | 0.184270E+09 | 33679383.33 | 86219998.75 | 0.238789E+09 | 55936499.18 |
Maximum of Months | 0.492050E+09 | 0.404765E+09 | 0.168673E+09 | 0.582403E+09 | 0.249724E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.588288E+09 | 0.483930E+09 | 0.104358E+09 | 0.697279E+09 | 0.260979E+09 |
February | 0.509670E+09 | 0.406341E+09 | 0.103329E+09 | 0.601842E+09 | 0.243312E+09 |
March | 0.416029E+09 | 0.273723E+09 | 0.142305E+09 | 0.496906E+09 | 0.216569E+09 |
April | 0.260759E+09 | 0.104852E+09 | 0.155907E+09 | 0.286316E+09 | 0.190931E+09 |
May | 0.246922E+09 | 45259090.50 | 0.201663E+09 | 0.293183E+09 | 0.125960E+09 |
June | 0.220310E+09 | 40266558.91 | 0.180044E+09 | 0.324549E+09 | 70198819.11 |
July | 0.236983E+09 | 42436991.88 | 0.194546E+09 | 0.350758E+09 | 66500489.41 |
August | 0.301727E+09 | 0.126133E+09 | 0.175594E+09 | 0.447151E+09 | 76446091.24 |
September | 0.375679E+09 | 0.209627E+09 | 0.166052E+09 | 0.522717E+09 | 0.110535E+09 |
October | 0.464175E+09 | 0.329343E+09 | 0.134832E+09 | 0.577428E+09 | 0.223363E+09 |
November | 0.547290E+09 | 0.436270E+09 | 0.111020E+09 | 0.661855E+09 | 0.241424E+09 |
December | 0.540797E+09 | 0.437714E+09 | 0.103083E+09 | 0.627507E+09 | 0.294875E+09 |
Annual Sum or Average | 0.470863E+10 | 0.293590E+10 | 0.177273E+10 | 0.588749E+10 | 0.212109E+10 |
Minimum of Months | 0.220310E+09 | 40266558.91 | 0.103083E+09 | 0.286316E+09 | 66500489.41 |
Maximum of Months | 0.588288E+09 | 0.483930E+09 | 0.201663E+09 | 0.697279E+09 | 0.294875E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.492050E+09 | 0.404765E+09 | 87285918.10 | 0.583033E+09 | 0.218351E+09 |
February | 0.426293E+09 | 0.339868E+09 | 86425364.41 | 0.502783E+09 | 0.204154E+09 |
March | 0.347971E+09 | 0.228945E+09 | 0.119026E+09 | 0.415332E+09 | 0.181430E+09 |
April | 0.218102E+09 | 87699567.97 | 0.130402E+09 | 0.239365E+09 | 0.159558E+09 |
May | 0.206528E+09 | 37855190.50 | 0.168673E+09 | 0.245431E+09 | 0.105279E+09 |
June | 0.184270E+09 | 33679383.33 | 0.150591E+09 | 0.271848E+09 | 59087605.22 |
July | 0.198215E+09 | 35494756.84 | 0.162720E+09 | 0.293737E+09 | 56105901.11 |
August | 0.252368E+09 | 0.105499E+09 | 0.146869E+09 | 0.374295E+09 | 64414608.83 |
September | 0.314222E+09 | 0.175334E+09 | 0.138888E+09 | 0.437289E+09 | 92983786.02 |
October | 0.388241E+09 | 0.275466E+09 | 0.112775E+09 | 0.482946E+09 | 0.187426E+09 |
November | 0.457759E+09 | 0.364901E+09 | 92858727.99 | 0.553383E+09 | 0.202227E+09 |
December | 0.452329E+09 | 0.366109E+09 | 86219998.75 | 0.524192E+09 | 0.247505E+09 |
Annual Sum or Average | 0.393835E+10 | 0.245562E+10 | 0.148273E+10 | 0.492363E+10 | 0.177852E+10 |
Minimum of Months | 0.184270E+09 | 33679383.33 | 86219998.75 | 0.239365E+09 | 56105901.11 |
Maximum of Months | 0.492050E+09 | 0.404765E+09 | 0.168673E+09 | 0.583033E+09 | 0.247505E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.492050E+09 | 0.404765E+09 | 87285918.10 | 0.583033E+09 | 0.218351E+09 |
February | 0.426293E+09 | 0.339868E+09 | 86425364.41 | 0.502783E+09 | 0.204154E+09 |
March | 0.347971E+09 | 0.228945E+09 | 0.119026E+09 | 0.415332E+09 | 0.181430E+09 |
April | 0.218102E+09 | 87699567.97 | 0.130402E+09 | 0.239365E+09 | 0.159558E+09 |
May | 0.206528E+09 | 37855190.50 | 0.168673E+09 | 0.245431E+09 | 0.105279E+09 |
June | 0.184270E+09 | 33679383.33 | 0.150591E+09 | 0.271848E+09 | 59087605.22 |
July | 0.198215E+09 | 35494756.84 | 0.162720E+09 | 0.293737E+09 | 56105901.11 |
August | 0.252368E+09 | 0.105499E+09 | 0.146869E+09 | 0.374295E+09 | 64414608.83 |
September | 0.314222E+09 | 0.175334E+09 | 0.138888E+09 | 0.437289E+09 | 92983786.02 |
October | 0.388241E+09 | 0.275466E+09 | 0.112775E+09 | 0.482946E+09 | 0.187426E+09 |
November | 0.457759E+09 | 0.364901E+09 | 92858727.99 | 0.553383E+09 | 0.202227E+09 |
December | 0.452329E+09 | 0.366109E+09 | 86219998.75 | 0.524192E+09 | 0.247505E+09 |
Annual Sum or Average | 0.393835E+10 | 0.245562E+10 | 0.148273E+10 | 0.492363E+10 | 0.177852E+10 |
Minimum of Months | 0.184270E+09 | 33679383.33 | 86219998.75 | 0.239365E+09 | 56105901.11 |
Maximum of Months | 0.492050E+09 | 0.404765E+09 | 0.168673E+09 | 0.583033E+09 | 0.247505E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.588288E+09 | 0.483930E+09 | 0.104358E+09 | 0.698034E+09 | 0.258314E+09 |
February | 0.509670E+09 | 0.406341E+09 | 0.103329E+09 | 0.602393E+09 | 0.241100E+09 |
March | 0.416029E+09 | 0.273723E+09 | 0.142305E+09 | 0.497522E+09 | 0.214339E+09 |
April | 0.260759E+09 | 0.104852E+09 | 0.155907E+09 | 0.287008E+09 | 0.188355E+09 |
May | 0.246922E+09 | 45259090.50 | 0.201663E+09 | 0.293865E+09 | 0.124545E+09 |
June | 0.220310E+09 | 40266558.91 | 0.180044E+09 | 0.324537E+09 | 70275944.38 |
July | 0.236983E+09 | 42436991.88 | 0.194546E+09 | 0.350681E+09 | 66700512.87 |
August | 0.301727E+09 | 0.126133E+09 | 0.175594E+09 | 0.447126E+09 | 76583358.47 |
September | 0.375679E+09 | 0.209627E+09 | 0.166052E+09 | 0.522772E+09 | 0.110409E+09 |
October | 0.464175E+09 | 0.329343E+09 | 0.134832E+09 | 0.577854E+09 | 0.221672E+09 |
November | 0.547290E+09 | 0.436270E+09 | 0.111020E+09 | 0.662538E+09 | 0.239109E+09 |
December | 0.540797E+09 | 0.437714E+09 | 0.103083E+09 | 0.628108E+09 | 0.292252E+09 |
Annual Sum or Average | 0.470863E+10 | 0.293590E+10 | 0.177273E+10 | 0.589244E+10 | 0.210365E+10 |
Minimum of Months | 0.220310E+09 | 40266558.91 | 0.103083E+09 | 0.287008E+09 | 66700512.87 |
Maximum of Months | 0.588288E+09 | 0.483930E+09 | 0.201663E+09 | 0.698034E+09 | 0.292252E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.492050E+09 | 0.404765E+09 | 87285918.10 | 0.583801E+09 | 0.216362E+09 |
February | 0.426293E+09 | 0.339868E+09 | 86425364.41 | 0.503349E+09 | 0.202529E+09 |
March | 0.347971E+09 | 0.228945E+09 | 0.119026E+09 | 0.416079E+09 | 0.179520E+09 |
April | 0.218102E+09 | 87699567.97 | 0.130402E+09 | 0.240179E+09 | 0.157375E+09 |
May | 0.206528E+09 | 37855190.50 | 0.168673E+09 | 0.246443E+09 | 0.103668E+09 |
June | 0.184270E+09 | 33679383.33 | 0.150591E+09 | 0.272199E+09 | 58362408.42 |
July | 0.198215E+09 | 35494756.84 | 0.162720E+09 | 0.294058E+09 | 55432128.42 |
August | 0.252368E+09 | 0.105499E+09 | 0.146869E+09 | 0.374578E+09 | 63700431.90 |
September | 0.314222E+09 | 0.175334E+09 | 0.138888E+09 | 0.437602E+09 | 92176462.00 |
October | 0.388241E+09 | 0.275466E+09 | 0.112775E+09 | 0.483530E+09 | 0.185800E+09 |
November | 0.457759E+09 | 0.364901E+09 | 92858727.99 | 0.554060E+09 | 0.200461E+09 |
December | 0.452329E+09 | 0.366109E+09 | 86219998.75 | 0.524839E+09 | 0.245539E+09 |
Annual Sum or Average | 0.393835E+10 | 0.245562E+10 | 0.148273E+10 | 0.493072E+10 | 0.176093E+10 |
Minimum of Months | 0.184270E+09 | 33679383.33 | 86219998.75 | 0.240179E+09 | 55432128.42 |
Maximum of Months | 0.492050E+09 | 0.404765E+09 | 0.168673E+09 | 0.583801E+09 | 0.245539E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.492050E+09 | 0.404765E+09 | 87285918.10 | 0.583801E+09 | 0.216362E+09 |
February | 0.426293E+09 | 0.339868E+09 | 86425364.41 | 0.503349E+09 | 0.202529E+09 |
March | 0.347971E+09 | 0.228945E+09 | 0.119026E+09 | 0.416079E+09 | 0.179520E+09 |
April | 0.218102E+09 | 87699567.97 | 0.130402E+09 | 0.240179E+09 | 0.157375E+09 |
May | 0.206528E+09 | 37855190.50 | 0.168673E+09 | 0.246443E+09 | 0.103668E+09 |
June | 0.184270E+09 | 33679383.33 | 0.150591E+09 | 0.272199E+09 | 58362408.42 |
July | 0.198215E+09 | 35494756.84 | 0.162720E+09 | 0.294058E+09 | 55432128.42 |
August | 0.252368E+09 | 0.105499E+09 | 0.146869E+09 | 0.374578E+09 | 63700431.90 |
September | 0.314222E+09 | 0.175334E+09 | 0.138888E+09 | 0.437602E+09 | 92176462.00 |
October | 0.388241E+09 | 0.275466E+09 | 0.112775E+09 | 0.483530E+09 | 0.185800E+09 |
November | 0.457759E+09 | 0.364901E+09 | 92858727.99 | 0.554060E+09 | 0.200461E+09 |
December | 0.452329E+09 | 0.366109E+09 | 86219998.75 | 0.524839E+09 | 0.245539E+09 |
Annual Sum or Average | 0.393835E+10 | 0.245562E+10 | 0.148273E+10 | 0.493072E+10 | 0.176093E+10 |
Minimum of Months | 0.184270E+09 | 33679383.33 | 86219998.75 | 0.240179E+09 | 55432128.42 |
Maximum of Months | 0.492050E+09 | 0.404765E+09 | 0.168673E+09 | 0.583801E+09 | 0.245539E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.588288E+09 | 0.483930E+09 | 0.104358E+09 | 0.698956E+09 | 0.255961E+09 |
February | 0.509670E+09 | 0.406341E+09 | 0.103329E+09 | 0.603073E+09 | 0.239178E+09 |
March | 0.416029E+09 | 0.273723E+09 | 0.142305E+09 | 0.498417E+09 | 0.212083E+09 |
April | 0.260759E+09 | 0.104852E+09 | 0.155907E+09 | 0.287983E+09 | 0.185779E+09 |
May | 0.246922E+09 | 45259090.50 | 0.201663E+09 | 0.295076E+09 | 0.122650E+09 |
June | 0.220310E+09 | 40266558.91 | 0.180044E+09 | 0.324960E+09 | 69424713.17 |
July | 0.236983E+09 | 42436991.88 | 0.194546E+09 | 0.351068E+09 | 65910262.68 |
August | 0.301727E+09 | 0.126133E+09 | 0.175594E+09 | 0.447466E+09 | 75744872.19 |
September | 0.375679E+09 | 0.209627E+09 | 0.166052E+09 | 0.523149E+09 | 0.109461E+09 |
October | 0.464175E+09 | 0.329343E+09 | 0.134832E+09 | 0.578551E+09 | 0.219750E+09 |
November | 0.547290E+09 | 0.436270E+09 | 0.111020E+09 | 0.663347E+09 | 0.237019E+09 |
December | 0.540797E+09 | 0.437714E+09 | 0.103083E+09 | 0.628885E+09 | 0.289931E+09 |
Annual Sum or Average | 0.470863E+10 | 0.293590E+10 | 0.177273E+10 | 0.590093E+10 | 0.208289E+10 |
Minimum of Months | 0.220310E+09 | 40266558.91 | 0.103083E+09 | 0.287983E+09 | 65910262.68 |
Maximum of Months | 0.588288E+09 | 0.483930E+09 | 0.201663E+09 | 0.698956E+09 | 0.289931E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.492050E+09 | 0.404765E+09 | 87285918.10 | 0.586215E+09 | 0.211520E+09 |
February | 0.426293E+09 | 0.339868E+09 | 86425364.41 | 0.505618E+09 | 0.197842E+09 |
March | 0.347971E+09 | 0.228945E+09 | 0.119026E+09 | 0.418212E+09 | 0.174492E+09 |
April | 0.218102E+09 | 87699567.97 | 0.130402E+09 | 0.242109E+09 | 0.152023E+09 |
May | 0.206528E+09 | 37855190.50 | 0.168673E+09 | 0.248284E+09 | 99905251.56 |
June | 0.184270E+09 | 33679383.33 | 0.150591E+09 | 0.272262E+09 | 56070829.80 |
July | 0.198215E+09 | 35494756.84 | 0.162720E+09 | 0.293984E+09 | 53300180.38 |
August | 0.252368E+09 | 0.105499E+09 | 0.146869E+09 | 0.374539E+09 | 61432602.90 |
September | 0.314222E+09 | 0.175334E+09 | 0.138888E+09 | 0.437845E+09 | 89943330.75 |
October | 0.388241E+09 | 0.275466E+09 | 0.112775E+09 | 0.484678E+09 | 0.181911E+09 |
November | 0.457759E+09 | 0.364901E+09 | 92858727.99 | 0.555950E+09 | 0.196168E+09 |
December | 0.452329E+09 | 0.366109E+09 | 86219998.75 | 0.527422E+09 | 0.240011E+09 |
Annual Sum or Average | 0.393835E+10 | 0.245562E+10 | 0.148273E+10 | 0.494712E+10 | 0.171462E+10 |
Minimum of Months | 0.184270E+09 | 33679383.33 | 86219998.75 | 0.242109E+09 | 53300180.38 |
Maximum of Months | 0.492050E+09 | 0.404765E+09 | 0.168673E+09 | 0.586215E+09 | 0.240011E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.492050E+09 | 0.404765E+09 | 87285918.10 | 0.586215E+09 | 0.211520E+09 |
February | 0.426293E+09 | 0.339868E+09 | 86425364.41 | 0.505618E+09 | 0.197842E+09 |
March | 0.347971E+09 | 0.228945E+09 | 0.119026E+09 | 0.418212E+09 | 0.174492E+09 |
April | 0.218102E+09 | 87699567.97 | 0.130402E+09 | 0.242109E+09 | 0.152023E+09 |
May | 0.206528E+09 | 37855190.50 | 0.168673E+09 | 0.248284E+09 | 99905251.56 |
June | 0.184270E+09 | 33679383.33 | 0.150591E+09 | 0.272262E+09 | 56070829.80 |
July | 0.198215E+09 | 35494756.84 | 0.162720E+09 | 0.293984E+09 | 53300180.38 |
August | 0.252368E+09 | 0.105499E+09 | 0.146869E+09 | 0.374539E+09 | 61432602.90 |
September | 0.314222E+09 | 0.175334E+09 | 0.138888E+09 | 0.437845E+09 | 89943330.75 |
October | 0.388241E+09 | 0.275466E+09 | 0.112775E+09 | 0.484678E+09 | 0.181911E+09 |
November | 0.457759E+09 | 0.364901E+09 | 92858727.99 | 0.555950E+09 | 0.196168E+09 |
December | 0.452329E+09 | 0.366109E+09 | 86219998.75 | 0.527422E+09 | 0.240011E+09 |
Annual Sum or Average | 0.393835E+10 | 0.245562E+10 | 0.148273E+10 | 0.494712E+10 | 0.171462E+10 |
Minimum of Months | 0.184270E+09 | 33679383.33 | 86219998.75 | 0.242109E+09 | 53300180.38 |
Maximum of Months | 0.492050E+09 | 0.404765E+09 | 0.168673E+09 | 0.586215E+09 | 0.240011E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.492050E+09 | 0.404765E+09 | 87285918.10 | 0.586215E+09 | 0.211520E+09 |
February | 0.426293E+09 | 0.339868E+09 | 86425364.41 | 0.505618E+09 | 0.197842E+09 |
March | 0.347971E+09 | 0.228945E+09 | 0.119026E+09 | 0.418212E+09 | 0.174492E+09 |
April | 0.218102E+09 | 87699567.97 | 0.130402E+09 | 0.242109E+09 | 0.152023E+09 |
May | 0.206528E+09 | 37855190.50 | 0.168673E+09 | 0.248284E+09 | 99905251.56 |
June | 0.184270E+09 | 33679383.33 | 0.150591E+09 | 0.272262E+09 | 56070829.80 |
July | 0.198215E+09 | 35494756.84 | 0.162720E+09 | 0.293984E+09 | 53300180.38 |
August | 0.252368E+09 | 0.105499E+09 | 0.146869E+09 | 0.374539E+09 | 61432602.90 |
September | 0.314222E+09 | 0.175334E+09 | 0.138888E+09 | 0.437845E+09 | 89943330.75 |
October | 0.388241E+09 | 0.275466E+09 | 0.112775E+09 | 0.484678E+09 | 0.181911E+09 |
November | 0.457759E+09 | 0.364901E+09 | 92858727.99 | 0.555950E+09 | 0.196168E+09 |
December | 0.452329E+09 | 0.366109E+09 | 86219998.75 | 0.527422E+09 | 0.240011E+09 |
Annual Sum or Average | 0.393835E+10 | 0.245562E+10 | 0.148273E+10 | 0.494712E+10 | 0.171462E+10 |
Minimum of Months | 0.184270E+09 | 33679383.33 | 86219998.75 | 0.242109E+09 | 53300180.38 |
Maximum of Months | 0.492050E+09 | 0.404765E+09 | 0.168673E+09 | 0.586215E+09 | 0.240011E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.492050E+09 | 0.404765E+09 | 87285918.10 | 0.586215E+09 | 0.211520E+09 |
February | 0.426293E+09 | 0.339868E+09 | 86425364.41 | 0.505618E+09 | 0.197842E+09 |
March | 0.347971E+09 | 0.228945E+09 | 0.119026E+09 | 0.418212E+09 | 0.174492E+09 |
April | 0.218102E+09 | 87699567.97 | 0.130402E+09 | 0.242109E+09 | 0.152023E+09 |
May | 0.206528E+09 | 37855190.50 | 0.168673E+09 | 0.248284E+09 | 99905251.56 |
June | 0.184270E+09 | 33679383.33 | 0.150591E+09 | 0.272262E+09 | 56070829.80 |
July | 0.198215E+09 | 35494756.84 | 0.162720E+09 | 0.293984E+09 | 53300180.38 |
August | 0.252368E+09 | 0.105499E+09 | 0.146869E+09 | 0.374539E+09 | 61432602.90 |
September | 0.314222E+09 | 0.175334E+09 | 0.138888E+09 | 0.437845E+09 | 89943330.75 |
October | 0.388241E+09 | 0.275466E+09 | 0.112775E+09 | 0.484678E+09 | 0.181911E+09 |
November | 0.457759E+09 | 0.364901E+09 | 92858727.99 | 0.555950E+09 | 0.196168E+09 |
December | 0.452329E+09 | 0.366109E+09 | 86219998.75 | 0.527422E+09 | 0.240011E+09 |
Annual Sum or Average | 0.393835E+10 | 0.245562E+10 | 0.148273E+10 | 0.494712E+10 | 0.171462E+10 |
Minimum of Months | 0.184270E+09 | 33679383.33 | 86219998.75 | 0.242109E+09 | 53300180.38 |
Maximum of Months | 0.492050E+09 | 0.404765E+09 | 0.168673E+09 | 0.586215E+09 | 0.240011E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.588288E+09 | 0.483930E+09 | 0.104358E+09 | 0.701721E+09 | 0.250317E+09 |
February | 0.509670E+09 | 0.406341E+09 | 0.103329E+09 | 0.605645E+09 | 0.233737E+09 |
March | 0.416029E+09 | 0.273723E+09 | 0.142305E+09 | 0.500858E+09 | 0.206225E+09 |
April | 0.260759E+09 | 0.104852E+09 | 0.155907E+09 | 0.290230E+09 | 0.179552E+09 |
May | 0.246922E+09 | 45259090.50 | 0.201663E+09 | 0.297228E+09 | 0.118256E+09 |
June | 0.220310E+09 | 40266558.91 | 0.180044E+09 | 0.325039E+09 | 66724633.03 |
July | 0.236983E+09 | 42436991.88 | 0.194546E+09 | 0.350981E+09 | 63399446.31 |
August | 0.301727E+09 | 0.126133E+09 | 0.175594E+09 | 0.447399E+09 | 73072879.62 |
September | 0.375679E+09 | 0.209627E+09 | 0.166052E+09 | 0.523392E+09 | 0.106841E+09 |
October | 0.464175E+09 | 0.329343E+09 | 0.134832E+09 | 0.579835E+09 | 0.215230E+09 |
November | 0.547290E+09 | 0.436270E+09 | 0.111020E+09 | 0.665487E+09 | 0.232031E+09 |
December | 0.540797E+09 | 0.437714E+09 | 0.103083E+09 | 0.631833E+09 | 0.283524E+09 |
Annual Sum or Average | 0.470863E+10 | 0.293590E+10 | 0.177273E+10 | 0.591965E+10 | 0.202891E+10 |
Minimum of Months | 0.220310E+09 | 40266558.91 | 0.103083E+09 | 0.290230E+09 | 63399446.31 |
Maximum of Months | 0.588288E+09 | 0.483930E+09 | 0.201663E+09 | 0.701721E+09 | 0.283524E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.588288E+09 | 0.483930E+09 | 0.104358E+09 | 0.701721E+09 | 0.250317E+09 |
February | 0.509670E+09 | 0.406341E+09 | 0.103329E+09 | 0.605645E+09 | 0.233737E+09 |
March | 0.416029E+09 | 0.273723E+09 | 0.142305E+09 | 0.500858E+09 | 0.206225E+09 |
April | 0.260759E+09 | 0.104852E+09 | 0.155907E+09 | 0.290230E+09 | 0.179552E+09 |
May | 0.246922E+09 | 45259090.50 | 0.201663E+09 | 0.297228E+09 | 0.118256E+09 |
June | 0.220310E+09 | 40266558.91 | 0.180044E+09 | 0.325039E+09 | 66724633.03 |
July | 0.236983E+09 | 42436991.88 | 0.194546E+09 | 0.350981E+09 | 63399446.31 |
August | 0.301727E+09 | 0.126133E+09 | 0.175594E+09 | 0.447399E+09 | 73072879.62 |
September | 0.375679E+09 | 0.209627E+09 | 0.166052E+09 | 0.523392E+09 | 0.106841E+09 |
October | 0.464175E+09 | 0.329343E+09 | 0.134832E+09 | 0.579835E+09 | 0.215230E+09 |
November | 0.547290E+09 | 0.436270E+09 | 0.111020E+09 | 0.665487E+09 | 0.232031E+09 |
December | 0.540797E+09 | 0.437714E+09 | 0.103083E+09 | 0.631833E+09 | 0.283524E+09 |
Annual Sum or Average | 0.470863E+10 | 0.293590E+10 | 0.177273E+10 | 0.591965E+10 | 0.202891E+10 |
Minimum of Months | 0.220310E+09 | 40266558.91 | 0.103083E+09 | 0.290230E+09 | 63399446.31 |
Maximum of Months | 0.588288E+09 | 0.483930E+09 | 0.201663E+09 | 0.701721E+09 | 0.283524E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.492050E+09 | 0.404765E+09 | 87285918.10 | 0.584934E+09 | 0.212495E+09 |
February | 0.426293E+09 | 0.339868E+09 | 86425364.41 | 0.504411E+09 | 0.198870E+09 |
March | 0.347971E+09 | 0.228945E+09 | 0.119026E+09 | 0.416937E+09 | 0.175624E+09 |
April | 0.218102E+09 | 87699567.97 | 0.130402E+09 | 0.240890E+09 | 0.153434E+09 |
May | 0.206528E+09 | 37855190.50 | 0.168673E+09 | 0.247009E+09 | 0.100795E+09 |
June | 0.184270E+09 | 33679383.33 | 0.150591E+09 | 0.272464E+09 | 55572427.02 |
July | 0.198215E+09 | 35494756.84 | 0.162720E+09 | 0.294191E+09 | 52793284.10 |
August | 0.252368E+09 | 0.105499E+09 | 0.146869E+09 | 0.374561E+09 | 60862902.39 |
September | 0.314222E+09 | 0.175334E+09 | 0.138888E+09 | 0.437479E+09 | 89710955.30 |
October | 0.388241E+09 | 0.275466E+09 | 0.112775E+09 | 0.483333E+09 | 0.183312E+09 |
November | 0.457759E+09 | 0.364901E+09 | 92858727.99 | 0.554556E+09 | 0.197414E+09 |
December | 0.452329E+09 | 0.366109E+09 | 86219998.75 | 0.526030E+09 | 0.241428E+09 |
Annual Sum or Average | 0.393835E+10 | 0.245562E+10 | 0.148273E+10 | 0.493680E+10 | 0.172231E+10 |
Minimum of Months | 0.184270E+09 | 33679383.33 | 86219998.75 | 0.240890E+09 | 52793284.10 |
Maximum of Months | 0.492050E+09 | 0.404765E+09 | 0.168673E+09 | 0.584934E+09 | 0.241428E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.492050E+09 | 0.404765E+09 | 87285918.10 | 0.584934E+09 | 0.212495E+09 |
February | 0.426293E+09 | 0.339868E+09 | 86425364.41 | 0.504411E+09 | 0.198870E+09 |
March | 0.347971E+09 | 0.228945E+09 | 0.119026E+09 | 0.416937E+09 | 0.175624E+09 |
April | 0.218102E+09 | 87699567.97 | 0.130402E+09 | 0.240890E+09 | 0.153434E+09 |
May | 0.206528E+09 | 37855190.50 | 0.168673E+09 | 0.247009E+09 | 0.100795E+09 |
June | 0.184270E+09 | 33679383.33 | 0.150591E+09 | 0.272464E+09 | 55572427.02 |
July | 0.198215E+09 | 35494756.84 | 0.162720E+09 | 0.294191E+09 | 52793284.10 |
August | 0.252368E+09 | 0.105499E+09 | 0.146869E+09 | 0.374561E+09 | 60862902.39 |
September | 0.314222E+09 | 0.175334E+09 | 0.138888E+09 | 0.437479E+09 | 89710955.30 |
October | 0.388241E+09 | 0.275466E+09 | 0.112775E+09 | 0.483333E+09 | 0.183312E+09 |
November | 0.457759E+09 | 0.364901E+09 | 92858727.99 | 0.554556E+09 | 0.197414E+09 |
December | 0.452329E+09 | 0.366109E+09 | 86219998.75 | 0.526030E+09 | 0.241428E+09 |
Annual Sum or Average | 0.393835E+10 | 0.245562E+10 | 0.148273E+10 | 0.493680E+10 | 0.172231E+10 |
Minimum of Months | 0.184270E+09 | 33679383.33 | 86219998.75 | 0.240890E+09 | 52793284.10 |
Maximum of Months | 0.492050E+09 | 0.404765E+09 | 0.168673E+09 | 0.584934E+09 | 0.241428E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.588288E+09 | 0.483930E+09 | 0.104358E+09 | 0.700340E+09 | 0.251371E+09 |
February | 0.509670E+09 | 0.406341E+09 | 0.103329E+09 | 0.604361E+09 | 0.234844E+09 |
March | 0.416029E+09 | 0.273723E+09 | 0.142305E+09 | 0.499473E+09 | 0.207468E+09 |
April | 0.260759E+09 | 0.104852E+09 | 0.155907E+09 | 0.288874E+09 | 0.181119E+09 |
May | 0.246922E+09 | 45259090.50 | 0.201663E+09 | 0.295796E+09 | 0.119259E+09 |
June | 0.220310E+09 | 40266558.91 | 0.180044E+09 | 0.325307E+09 | 66136184.35 |
July | 0.236983E+09 | 42436991.88 | 0.194546E+09 | 0.351260E+09 | 62799543.69 |
August | 0.301727E+09 | 0.126133E+09 | 0.175594E+09 | 0.447483E+09 | 72396022.89 |
September | 0.375679E+09 | 0.209627E+09 | 0.166052E+09 | 0.523037E+09 | 0.106550E+09 |
October | 0.464175E+09 | 0.329343E+09 | 0.134832E+09 | 0.578355E+09 | 0.216791E+09 |
November | 0.547290E+09 | 0.436270E+09 | 0.111020E+09 | 0.663973E+09 | 0.233401E+09 |
December | 0.540797E+09 | 0.437714E+09 | 0.103083E+09 | 0.630330E+09 | 0.285064E+09 |
Annual Sum or Average | 0.470863E+10 | 0.293590E+10 | 0.177273E+10 | 0.590859E+10 | 0.203720E+10 |
Minimum of Months | 0.220310E+09 | 40266558.91 | 0.103083E+09 | 0.288874E+09 | 62799543.69 |
Maximum of Months | 0.588288E+09 | 0.483930E+09 | 0.201663E+09 | 0.700340E+09 | 0.285064E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.492050E+09 | 0.404765E+09 | 87285918.10 | 0.585255E+09 | 0.211744E+09 |
February | 0.426293E+09 | 0.339868E+09 | 86425364.41 | 0.504680E+09 | 0.198254E+09 |
March | 0.347971E+09 | 0.228945E+09 | 0.119026E+09 | 0.417226E+09 | 0.174938E+09 |
April | 0.218102E+09 | 87699567.97 | 0.130402E+09 | 0.241149E+09 | 0.152770E+09 |
May | 0.206528E+09 | 37855190.50 | 0.168673E+09 | 0.247420E+09 | 0.100228E+09 |
June | 0.184270E+09 | 33679383.33 | 0.150591E+09 | 0.272668E+09 | 55304093.95 |
July | 0.198215E+09 | 35494756.84 | 0.162720E+09 | 0.294375E+09 | 52548078.93 |
August | 0.252368E+09 | 0.105499E+09 | 0.146869E+09 | 0.374719E+09 | 60615678.95 |
September | 0.314222E+09 | 0.175334E+09 | 0.138888E+09 | 0.437622E+09 | 89444791.98 |
October | 0.388241E+09 | 0.275466E+09 | 0.112775E+09 | 0.483532E+09 | 0.182820E+09 |
November | 0.457759E+09 | 0.364901E+09 | 92858727.99 | 0.554803E+09 | 0.196848E+09 |
December | 0.452329E+09 | 0.366109E+09 | 86219998.75 | 0.526266E+09 | 0.240805E+09 |
Annual Sum or Average | 0.393835E+10 | 0.245562E+10 | 0.148273E+10 | 0.493971E+10 | 0.171632E+10 |
Minimum of Months | 0.184270E+09 | 33679383.33 | 86219998.75 | 0.241149E+09 | 52548078.93 |
Maximum of Months | 0.492050E+09 | 0.404765E+09 | 0.168673E+09 | 0.585255E+09 | 0.240805E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.492050E+09 | 0.404765E+09 | 87285918.10 | 0.585255E+09 | 0.211744E+09 |
February | 0.426293E+09 | 0.339868E+09 | 86425364.41 | 0.504680E+09 | 0.198254E+09 |
March | 0.347971E+09 | 0.228945E+09 | 0.119026E+09 | 0.417226E+09 | 0.174938E+09 |
April | 0.218102E+09 | 87699567.97 | 0.130402E+09 | 0.241149E+09 | 0.152770E+09 |
May | 0.206528E+09 | 37855190.50 | 0.168673E+09 | 0.247420E+09 | 0.100228E+09 |
June | 0.184270E+09 | 33679383.33 | 0.150591E+09 | 0.272668E+09 | 55304093.95 |
July | 0.198215E+09 | 35494756.84 | 0.162720E+09 | 0.294375E+09 | 52548078.93 |
August | 0.252368E+09 | 0.105499E+09 | 0.146869E+09 | 0.374719E+09 | 60615678.95 |
September | 0.314222E+09 | 0.175334E+09 | 0.138888E+09 | 0.437622E+09 | 89444791.98 |
October | 0.388241E+09 | 0.275466E+09 | 0.112775E+09 | 0.483532E+09 | 0.182820E+09 |
November | 0.457759E+09 | 0.364901E+09 | 92858727.99 | 0.554803E+09 | 0.196848E+09 |
December | 0.452329E+09 | 0.366109E+09 | 86219998.75 | 0.526266E+09 | 0.240805E+09 |
Annual Sum or Average | 0.393835E+10 | 0.245562E+10 | 0.148273E+10 | 0.493971E+10 | 0.171632E+10 |
Minimum of Months | 0.184270E+09 | 33679383.33 | 86219998.75 | 0.241149E+09 | 52548078.93 |
Maximum of Months | 0.492050E+09 | 0.404765E+09 | 0.168673E+09 | 0.585255E+09 | 0.240805E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.588288E+09 | 0.483930E+09 | 0.104358E+09 | 0.700725E+09 | 0.250479E+09 |
February | 0.509670E+09 | 0.406341E+09 | 0.103329E+09 | 0.604684E+09 | 0.234114E+09 |
March | 0.416029E+09 | 0.273723E+09 | 0.142305E+09 | 0.499819E+09 | 0.206658E+09 |
April | 0.260759E+09 | 0.104852E+09 | 0.155907E+09 | 0.289185E+09 | 0.180334E+09 |
May | 0.246922E+09 | 45259090.50 | 0.201663E+09 | 0.296288E+09 | 0.118589E+09 |
June | 0.220310E+09 | 40266558.91 | 0.180044E+09 | 0.325552E+09 | 65819414.53 |
July | 0.236983E+09 | 42436991.88 | 0.194546E+09 | 0.351480E+09 | 62510096.83 |
August | 0.301727E+09 | 0.126133E+09 | 0.175594E+09 | 0.447672E+09 | 72103815.71 |
September | 0.375679E+09 | 0.209627E+09 | 0.166052E+09 | 0.523209E+09 | 0.106236E+09 |
October | 0.464175E+09 | 0.329343E+09 | 0.134832E+09 | 0.578592E+09 | 0.216208E+09 |
November | 0.547290E+09 | 0.436270E+09 | 0.111020E+09 | 0.664269E+09 | 0.232730E+09 |
December | 0.540797E+09 | 0.437714E+09 | 0.103083E+09 | 0.630612E+09 | 0.284327E+09 |
Annual Sum or Average | 0.470863E+10 | 0.293590E+10 | 0.177273E+10 | 0.591209E+10 | 0.203011E+10 |
Minimum of Months | 0.220310E+09 | 40266558.91 | 0.103083E+09 | 0.289185E+09 | 62510096.83 |
Maximum of Months | 0.588288E+09 | 0.483930E+09 | 0.201663E+09 | 0.700725E+09 | 0.284327E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.492050E+09 | 0.404765E+09 | 87285918.10 | 0.586478E+09 | 0.208587E+09 |
February | 0.426293E+09 | 0.339868E+09 | 86425364.41 | 0.505695E+09 | 0.195513E+09 |
March | 0.347971E+09 | 0.228945E+09 | 0.119026E+09 | 0.418429E+09 | 0.171714E+09 |
April | 0.218102E+09 | 87699567.97 | 0.130402E+09 | 0.242272E+09 | 0.149406E+09 |
May | 0.206528E+09 | 37855190.50 | 0.168673E+09 | 0.249283E+09 | 97481200.82 |
June | 0.184270E+09 | 33679383.33 | 0.150591E+09 | 0.273127E+09 | 54536252.86 |
July | 0.198215E+09 | 35494756.84 | 0.162720E+09 | 0.294749E+09 | 51876547.08 |
August | 0.252368E+09 | 0.105499E+09 | 0.146869E+09 | 0.374996E+09 | 59998366.90 |
September | 0.314222E+09 | 0.175334E+09 | 0.138888E+09 | 0.437985E+09 | 88583857.59 |
October | 0.388241E+09 | 0.275466E+09 | 0.112775E+09 | 0.484536E+09 | 0.180175E+09 |
November | 0.457759E+09 | 0.364901E+09 | 92858727.99 | 0.555841E+09 | 0.194183E+09 |
December | 0.452329E+09 | 0.366109E+09 | 86219998.75 | 0.527195E+09 | 0.237961E+09 |
Annual Sum or Average | 0.393835E+10 | 0.245562E+10 | 0.148273E+10 | 0.495059E+10 | 0.169001E+10 |
Minimum of Months | 0.184270E+09 | 33679383.33 | 86219998.75 | 0.242272E+09 | 51876547.08 |
Maximum of Months | 0.492050E+09 | 0.404765E+09 | 0.168673E+09 | 0.586478E+09 | 0.237961E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.492050E+09 | 0.404765E+09 | 87285918.10 | 0.586478E+09 | 0.208587E+09 |
February | 0.426293E+09 | 0.339868E+09 | 86425364.41 | 0.505695E+09 | 0.195513E+09 |
March | 0.347971E+09 | 0.228945E+09 | 0.119026E+09 | 0.418429E+09 | 0.171714E+09 |
April | 0.218102E+09 | 87699567.97 | 0.130402E+09 | 0.242272E+09 | 0.149406E+09 |
May | 0.206528E+09 | 37855190.50 | 0.168673E+09 | 0.249283E+09 | 97481200.82 |
June | 0.184270E+09 | 33679383.33 | 0.150591E+09 | 0.273127E+09 | 54536252.86 |
July | 0.198215E+09 | 35494756.84 | 0.162720E+09 | 0.294749E+09 | 51876547.08 |
August | 0.252368E+09 | 0.105499E+09 | 0.146869E+09 | 0.374996E+09 | 59998366.90 |
September | 0.314222E+09 | 0.175334E+09 | 0.138888E+09 | 0.437985E+09 | 88583857.59 |
October | 0.388241E+09 | 0.275466E+09 | 0.112775E+09 | 0.484536E+09 | 0.180175E+09 |
November | 0.457759E+09 | 0.364901E+09 | 92858727.99 | 0.555841E+09 | 0.194183E+09 |
December | 0.452329E+09 | 0.366109E+09 | 86219998.75 | 0.527195E+09 | 0.237961E+09 |
Annual Sum or Average | 0.393835E+10 | 0.245562E+10 | 0.148273E+10 | 0.495059E+10 | 0.169001E+10 |
Minimum of Months | 0.184270E+09 | 33679383.33 | 86219998.75 | 0.242272E+09 | 51876547.08 |
Maximum of Months | 0.492050E+09 | 0.404765E+09 | 0.168673E+09 | 0.586478E+09 | 0.237961E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.588288E+09 | 0.483930E+09 | 0.104358E+09 | 0.702191E+09 | 0.246741E+09 |
February | 0.509670E+09 | 0.406341E+09 | 0.103329E+09 | 0.605899E+09 | 0.230874E+09 |
March | 0.416029E+09 | 0.273723E+09 | 0.142305E+09 | 0.501259E+09 | 0.202845E+09 |
April | 0.260759E+09 | 0.104852E+09 | 0.155907E+09 | 0.290535E+09 | 0.176366E+09 |
May | 0.246922E+09 | 45259090.50 | 0.201663E+09 | 0.298515E+09 | 0.115356E+09 |
June | 0.220310E+09 | 40266558.91 | 0.180044E+09 | 0.326101E+09 | 64916939.76 |
July | 0.236983E+09 | 42436991.88 | 0.194546E+09 | 0.351928E+09 | 61722621.97 |
August | 0.301727E+09 | 0.126133E+09 | 0.175594E+09 | 0.448004E+09 | 71379471.91 |
September | 0.375679E+09 | 0.209627E+09 | 0.166052E+09 | 0.523646E+09 | 0.105225E+09 |
October | 0.464175E+09 | 0.329343E+09 | 0.134832E+09 | 0.579791E+09 | 0.213081E+09 |
November | 0.547290E+09 | 0.436270E+09 | 0.111020E+09 | 0.665509E+09 | 0.229575E+09 |
December | 0.540797E+09 | 0.437714E+09 | 0.103083E+09 | 0.631726E+09 | 0.280966E+09 |
Annual Sum or Average | 0.470863E+10 | 0.293590E+10 | 0.177273E+10 | 0.592510E+10 | 0.199905E+10 |
Minimum of Months | 0.220310E+09 | 40266558.91 | 0.103083E+09 | 0.290535E+09 | 61722621.97 |
Maximum of Months | 0.588288E+09 | 0.483930E+09 | 0.201663E+09 | 0.702191E+09 | 0.280966E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.492050E+09 | 0.404765E+09 | 87285918.10 | 0.590353E+09 | 0.196754E+09 |
February | 0.426293E+09 | 0.339868E+09 | 86425364.41 | 0.508987E+09 | 0.184482E+09 |
March | 0.347971E+09 | 0.228945E+09 | 0.119026E+09 | 0.422012E+09 | 0.159256E+09 |
April | 0.218102E+09 | 87699567.97 | 0.130402E+09 | 0.245425E+09 | 0.137051E+09 |
May | 0.206528E+09 | 37855190.50 | 0.168673E+09 | 0.254547E+09 | 88416148.05 |
June | 0.184270E+09 | 33679383.33 | 0.150591E+09 | 0.273879E+09 | 51508813.92 |
July | 0.198215E+09 | 35494756.84 | 0.162720E+09 | 0.295338E+09 | 49116494.84 |
August | 0.252368E+09 | 0.105499E+09 | 0.146869E+09 | 0.375117E+09 | 57575455.50 |
September | 0.314222E+09 | 0.175334E+09 | 0.138888E+09 | 0.438547E+09 | 85331647.37 |
October | 0.388241E+09 | 0.275466E+09 | 0.112775E+09 | 0.487371E+09 | 0.170594E+09 |
November | 0.457759E+09 | 0.364901E+09 | 92858727.99 | 0.558869E+09 | 0.184508E+09 |
December | 0.452329E+09 | 0.366109E+09 | 86219998.75 | 0.530224E+09 | 0.226753E+09 |
Annual Sum or Average | 0.393835E+10 | 0.245562E+10 | 0.148273E+10 | 0.498067E+10 | 0.159135E+10 |
Minimum of Months | 0.184270E+09 | 33679383.33 | 86219998.75 | 0.245425E+09 | 49116494.84 |
Maximum of Months | 0.492050E+09 | 0.404765E+09 | 0.168673E+09 | 0.590353E+09 | 0.226753E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.492050E+09 | 0.404765E+09 | 87285918.10 | 0.590353E+09 | 0.196754E+09 |
February | 0.426293E+09 | 0.339868E+09 | 86425364.41 | 0.508987E+09 | 0.184482E+09 |
March | 0.347971E+09 | 0.228945E+09 | 0.119026E+09 | 0.422012E+09 | 0.159256E+09 |
April | 0.218102E+09 | 87699567.97 | 0.130402E+09 | 0.245425E+09 | 0.137051E+09 |
May | 0.206528E+09 | 37855190.50 | 0.168673E+09 | 0.254547E+09 | 88416148.05 |
June | 0.184270E+09 | 33679383.33 | 0.150591E+09 | 0.273879E+09 | 51508813.92 |
July | 0.198215E+09 | 35494756.84 | 0.162720E+09 | 0.295338E+09 | 49116494.84 |
August | 0.252368E+09 | 0.105499E+09 | 0.146869E+09 | 0.375117E+09 | 57575455.50 |
September | 0.314222E+09 | 0.175334E+09 | 0.138888E+09 | 0.438547E+09 | 85331647.37 |
October | 0.388241E+09 | 0.275466E+09 | 0.112775E+09 | 0.487371E+09 | 0.170594E+09 |
November | 0.457759E+09 | 0.364901E+09 | 92858727.99 | 0.558869E+09 | 0.184508E+09 |
December | 0.452329E+09 | 0.366109E+09 | 86219998.75 | 0.530224E+09 | 0.226753E+09 |
Annual Sum or Average | 0.393835E+10 | 0.245562E+10 | 0.148273E+10 | 0.498067E+10 | 0.159135E+10 |
Minimum of Months | 0.184270E+09 | 33679383.33 | 86219998.75 | 0.245425E+09 | 49116494.84 |
Maximum of Months | 0.492050E+09 | 0.404765E+09 | 0.168673E+09 | 0.590353E+09 | 0.226753E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_DOOR
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.588288E+09 | 0.483930E+09 | 0.104358E+09 | 0.706837E+09 | 0.232735E+09 |
February | 0.509670E+09 | 0.406341E+09 | 0.103329E+09 | 0.609845E+09 | 0.217825E+09 |
March | 0.416029E+09 | 0.273723E+09 | 0.142305E+09 | 0.505545E+09 | 0.188134E+09 |
April | 0.260759E+09 | 0.104852E+09 | 0.155907E+09 | 0.294316E+09 | 0.161801E+09 |
May | 0.246922E+09 | 45259090.50 | 0.201663E+09 | 0.304772E+09 | 0.104697E+09 |
June | 0.220310E+09 | 40266558.91 | 0.180044E+09 | 0.326988E+09 | 61355755.60 |
July | 0.236983E+09 | 42436991.88 | 0.194546E+09 | 0.352622E+09 | 58476718.86 |
August | 0.301727E+09 | 0.126133E+09 | 0.175594E+09 | 0.448137E+09 | 68531304.93 |
September | 0.375679E+09 | 0.209627E+09 | 0.166052E+09 | 0.524304E+09 | 0.101405E+09 |
October | 0.464175E+09 | 0.329343E+09 | 0.134832E+09 | 0.583158E+09 | 0.201771E+09 |
November | 0.547290E+09 | 0.436270E+09 | 0.111020E+09 | 0.669120E+09 | 0.218134E+09 |
December | 0.540797E+09 | 0.437714E+09 | 0.103083E+09 | 0.635350E+09 | 0.267714E+09 |
Annual Sum or Average | 0.470863E+10 | 0.293590E+10 | 0.177273E+10 | 0.596100E+10 | 0.188258E+10 |
Minimum of Months | 0.220310E+09 | 40266558.91 | 0.103083E+09 | 0.294316E+09 | 58476718.86 |
Maximum of Months | 0.588288E+09 | 0.483930E+09 | 0.201663E+09 | 0.706837E+09 | 0.267714E+09 |
Report: WindowZoneSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1401.87 | 509.77 | 1176.54 | 967.83 | 208.71 | 0.00 | 0.00 |
February | 1339.54 | 528.51 | 1128.52 | 899.73 | 228.79 | 0.00 | 0.00 |
March | 1000.51 | 420.09 | 832.03 | 547.43 | 284.60 | 0.00 | 0.00 |
April | 597.81 | 380.19 | 538.89 | 216.69 | 322.20 | 0.00 | 0.00 |
May | 593.97 | 239.66 | 493.83 | 90.52 | 403.31 | 0.00 | 0.00 |
June | 674.72 | 134.50 | 455.29 | 83.21 | 372.08 | 0.00 | 0.00 |
July | 706.30 | 121.71 | 473.95 | 84.87 | 389.08 | 0.00 | 0.00 |
August | 896.97 | 142.08 | 603.44 | 252.26 | 351.18 | 0.00 | 0.00 |
September | 1083.37 | 217.27 | 776.38 | 433.21 | 343.16 | 0.00 | 0.00 |
October | 1159.83 | 434.30 | 928.32 | 658.67 | 269.66 | 0.00 | 0.00 |
November | 1373.43 | 487.19 | 1131.03 | 901.60 | 229.44 | 0.00 | 0.00 |
December | 1260.82 | 580.51 | 1081.56 | 875.40 | 206.16 | 0.00 | 0.00 |
Annual Sum or Average | 1005.52 | 348.67 | 799.80 | 498.68 | 301.11 | 0.00 | 0.00 |
Minimum of Months | 593.97 | 121.71 | 455.29 | 83.21 | 206.16 | 0.00 | 0.00 |
Maximum of Months | 1401.87 | 580.51 | 1176.54 | 967.83 | 403.31 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 695.68 | 267.99 | 588.27 | 483.92 | 104.35 | 0.00 | 0.00 |
February | 664.64 | 276.85 | 564.26 | 449.86 | 114.40 | 0.00 | 0.00 |
March | 495.63 | 222.08 | 416.02 | 273.71 | 142.30 | 0.00 | 0.00 |
April | 294.46 | 203.69 | 269.44 | 108.34 | 161.10 | 0.00 | 0.00 |
May | 292.49 | 126.86 | 246.91 | 45.26 | 201.66 | 0.00 | 0.00 |
June | 336.83 | 68.18 | 227.65 | 41.61 | 186.04 | 0.00 | 0.00 |
July | 352.63 | 61.88 | 236.98 | 42.44 | 194.54 | 0.00 | 0.00 |
August | 448.07 | 71.73 | 301.72 | 126.13 | 175.59 | 0.00 | 0.00 |
September | 540.67 | 110.50 | 388.19 | 216.61 | 171.58 | 0.00 | 0.00 |
October | 576.64 | 226.26 | 464.16 | 329.33 | 134.83 | 0.00 | 0.00 |
November | 682.21 | 255.65 | 565.52 | 450.80 | 114.72 | 0.00 | 0.00 |
December | 625.83 | 302.93 | 540.78 | 437.70 | 103.08 | 0.00 | 0.00 |
Annual Sum or Average | 499.54 | 182.37 | 399.90 | 249.34 | 150.56 | 0.00 | 0.00 |
Minimum of Months | 292.49 | 61.88 | 227.65 | 41.61 | 103.08 | 0.00 | 0.00 |
Maximum of Months | 695.68 | 302.93 | 588.27 | 483.92 | 201.66 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 695.22 | 262.16 | 587.06 | 482.92 | 104.14 | 0.00 | 0.00 |
February | 664.06 | 270.90 | 563.10 | 448.94 | 114.16 | 0.00 | 0.00 |
March | 495.27 | 217.74 | 415.16 | 273.15 | 142.01 | 0.00 | 0.00 |
April | 294.71 | 198.46 | 268.89 | 108.12 | 160.77 | 0.00 | 0.00 |
May | 292.30 | 126.54 | 246.41 | 45.16 | 201.24 | 0.00 | 0.00 |
June | 334.98 | 72.62 | 227.18 | 41.52 | 185.66 | 0.00 | 0.00 |
July | 350.34 | 66.60 | 236.49 | 42.35 | 194.14 | 0.00 | 0.00 |
August | 446.45 | 76.55 | 301.10 | 125.87 | 175.23 | 0.00 | 0.00 |
September | 539.04 | 114.47 | 387.39 | 216.16 | 171.23 | 0.00 | 0.00 |
October | 575.94 | 224.41 | 463.21 | 328.66 | 134.55 | 0.00 | 0.00 |
November | 681.90 | 250.69 | 564.36 | 449.87 | 114.48 | 0.00 | 0.00 |
December | 625.33 | 296.57 | 539.67 | 436.80 | 102.87 | 0.00 | 0.00 |
Annual Sum or Average | 498.68 | 180.99 | 399.08 | 248.83 | 150.25 | 0.00 | 0.00 |
Minimum of Months | 292.30 | 66.60 | 227.18 | 41.52 | 102.87 | 0.00 | 0.00 |
Maximum of Months | 695.22 | 296.57 | 587.06 | 482.92 | 201.24 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 695.98 | 259.49 | 587.06 | 482.92 | 104.14 | 0.00 | 0.00 |
February | 664.67 | 268.44 | 563.10 | 448.94 | 114.16 | 0.00 | 0.00 |
March | 495.89 | 215.50 | 415.16 | 273.15 | 142.01 | 0.00 | 0.00 |
April | 295.42 | 195.78 | 268.89 | 108.12 | 160.77 | 0.00 | 0.00 |
May | 292.98 | 125.11 | 246.41 | 45.16 | 201.24 | 0.00 | 0.00 |
June | 334.97 | 72.70 | 227.18 | 41.52 | 185.66 | 0.00 | 0.00 |
July | 350.27 | 66.80 | 236.49 | 42.35 | 194.14 | 0.00 | 0.00 |
August | 446.43 | 76.69 | 301.10 | 125.87 | 175.23 | 0.00 | 0.00 |
September | 539.10 | 114.34 | 387.39 | 216.16 | 171.23 | 0.00 | 0.00 |
October | 576.37 | 222.72 | 463.21 | 328.66 | 134.55 | 0.00 | 0.00 |
November | 682.60 | 248.29 | 564.36 | 449.87 | 114.48 | 0.00 | 0.00 |
December | 625.93 | 293.93 | 539.67 | 436.80 | 102.87 | 0.00 | 0.00 |
Annual Sum or Average | 499.10 | 179.50 | 399.08 | 248.83 | 150.25 | 0.00 | 0.00 |
Minimum of Months | 292.98 | 66.80 | 227.18 | 41.52 | 102.87 | 0.00 | 0.00 |
Maximum of Months | 695.98 | 293.93 | 587.06 | 482.92 | 201.24 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 696.89 | 257.13 | 587.06 | 482.92 | 104.14 | 0.00 | 0.00 |
February | 665.41 | 266.30 | 563.10 | 448.94 | 114.16 | 0.00 | 0.00 |
March | 496.78 | 213.23 | 415.16 | 273.15 | 142.01 | 0.00 | 0.00 |
April | 296.43 | 193.10 | 268.89 | 108.12 | 160.77 | 0.00 | 0.00 |
May | 294.19 | 123.20 | 246.41 | 45.16 | 201.24 | 0.00 | 0.00 |
June | 335.40 | 71.82 | 227.18 | 41.52 | 185.66 | 0.00 | 0.00 |
July | 350.65 | 66.00 | 236.49 | 42.35 | 194.14 | 0.00 | 0.00 |
August | 446.77 | 75.85 | 301.10 | 125.87 | 175.23 | 0.00 | 0.00 |
September | 539.49 | 113.35 | 387.39 | 216.16 | 171.23 | 0.00 | 0.00 |
October | 577.07 | 220.78 | 463.21 | 328.66 | 134.55 | 0.00 | 0.00 |
November | 683.44 | 246.12 | 564.36 | 449.87 | 114.48 | 0.00 | 0.00 |
December | 626.70 | 291.59 | 539.67 | 436.80 | 102.87 | 0.00 | 0.00 |
Annual Sum or Average | 499.82 | 177.72 | 399.08 | 248.83 | 150.25 | 0.00 | 0.00 |
Minimum of Months | 294.19 | 66.00 | 227.18 | 41.52 | 102.87 | 0.00 | 0.00 |
Maximum of Months | 696.89 | 291.59 | 587.06 | 482.92 | 201.24 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1399.46 | 502.81 | 1174.13 | 965.84 | 208.28 | 0.00 | 0.00 |
February | 1336.71 | 520.35 | 1126.20 | 897.88 | 228.32 | 0.00 | 0.00 |
March | 998.57 | 414.58 | 830.32 | 546.31 | 284.02 | 0.00 | 0.00 |
April | 597.57 | 373.14 | 537.78 | 216.24 | 321.54 | 0.00 | 0.00 |
May | 592.74 | 237.50 | 492.82 | 90.33 | 402.49 | 0.00 | 0.00 |
June | 670.96 | 138.01 | 454.36 | 83.04 | 371.32 | 0.00 | 0.00 |
July | 701.13 | 126.94 | 472.98 | 84.70 | 388.28 | 0.00 | 0.00 |
August | 893.43 | 146.31 | 602.20 | 251.74 | 350.46 | 0.00 | 0.00 |
September | 1079.54 | 221.24 | 774.79 | 432.33 | 342.46 | 0.00 | 0.00 |
October | 1156.80 | 432.39 | 926.42 | 657.31 | 269.10 | 0.00 | 0.00 |
November | 1371.44 | 481.76 | 1128.71 | 899.75 | 228.96 | 0.00 | 0.00 |
December | 1259.47 | 570.15 | 1079.34 | 873.60 | 205.74 | 0.00 | 0.00 |
Annual Sum or Average | 1002.91 | 346.15 | 798.16 | 497.66 | 300.49 | 0.00 | 0.00 |
Minimum of Months | 592.74 | 126.94 | 454.36 | 83.04 | 205.74 | 0.00 | 0.00 |
Maximum of Months | 1399.46 | 570.15 | 1174.13 | 965.84 | 402.49 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 698.26 | 252.52 | 587.06 | 482.92 | 104.14 | 0.00 | 0.00 |
February | 666.82 | 261.49 | 563.10 | 448.94 | 114.16 | 0.00 | 0.00 |
March | 497.81 | 208.60 | 415.16 | 273.15 | 142.01 | 0.00 | 0.00 |
April | 297.32 | 188.27 | 268.89 | 108.12 | 160.77 | 0.00 | 0.00 |
May | 294.88 | 119.79 | 246.41 | 45.16 | 201.24 | 0.00 | 0.00 |
June | 335.74 | 68.40 | 227.18 | 41.52 | 185.66 | 0.00 | 0.00 |
July | 350.82 | 62.87 | 236.49 | 42.35 | 194.14 | 0.00 | 0.00 |
August | 446.76 | 72.48 | 301.10 | 125.87 | 175.23 | 0.00 | 0.00 |
September | 539.35 | 110.33 | 387.39 | 216.16 | 171.23 | 0.00 | 0.00 |
October | 576.84 | 217.82 | 463.21 | 328.66 | 134.55 | 0.00 | 0.00 |
November | 684.06 | 242.37 | 564.36 | 449.87 | 114.48 | 0.00 | 0.00 |
December | 628.13 | 286.71 | 539.67 | 436.80 | 102.87 | 0.00 | 0.00 |
Annual Sum or Average | 500.45 | 173.83 | 399.08 | 248.83 | 150.25 | 0.00 | 0.00 |
Minimum of Months | 294.88 | 62.87 | 227.18 | 41.52 | 102.87 | 0.00 | 0.00 |
Maximum of Months | 698.26 | 286.71 | 587.06 | 482.92 | 201.24 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 698.64 | 251.63 | 587.06 | 482.92 | 104.14 | 0.00 | 0.00 |
February | 667.18 | 260.67 | 563.10 | 448.94 | 114.16 | 0.00 | 0.00 |
March | 498.16 | 207.79 | 415.16 | 273.15 | 142.01 | 0.00 | 0.00 |
April | 297.64 | 187.45 | 268.89 | 108.12 | 160.77 | 0.00 | 0.00 |
May | 295.37 | 119.12 | 246.41 | 45.16 | 201.24 | 0.00 | 0.00 |
June | 335.99 | 68.07 | 227.18 | 41.52 | 185.66 | 0.00 | 0.00 |
July | 351.04 | 62.58 | 236.49 | 42.35 | 194.14 | 0.00 | 0.00 |
August | 446.95 | 72.18 | 301.10 | 125.87 | 175.23 | 0.00 | 0.00 |
September | 539.53 | 110.00 | 387.39 | 216.16 | 171.23 | 0.00 | 0.00 |
October | 577.08 | 217.24 | 463.21 | 328.66 | 134.55 | 0.00 | 0.00 |
November | 684.36 | 241.68 | 564.36 | 449.87 | 114.48 | 0.00 | 0.00 |
December | 628.41 | 285.97 | 539.67 | 436.80 | 102.87 | 0.00 | 0.00 |
Annual Sum or Average | 500.75 | 173.22 | 399.08 | 248.83 | 150.25 | 0.00 | 0.00 |
Minimum of Months | 295.37 | 62.58 | 227.18 | 41.52 | 102.87 | 0.00 | 0.00 |
Maximum of Months | 698.64 | 285.97 | 587.06 | 482.92 | 201.24 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 700.10 | 247.88 | 587.06 | 482.92 | 104.14 | 0.00 | 0.00 |
February | 668.52 | 257.07 | 563.10 | 448.94 | 114.16 | 0.00 | 0.00 |
March | 499.60 | 203.95 | 415.16 | 273.15 | 142.01 | 0.00 | 0.00 |
April | 299.03 | 183.32 | 268.89 | 108.12 | 160.77 | 0.00 | 0.00 |
May | 297.60 | 115.86 | 246.41 | 45.16 | 201.24 | 0.00 | 0.00 |
June | 336.56 | 67.13 | 227.18 | 41.52 | 185.66 | 0.00 | 0.00 |
July | 351.49 | 61.78 | 236.49 | 42.35 | 194.14 | 0.00 | 0.00 |
August | 447.28 | 71.45 | 301.10 | 125.87 | 175.23 | 0.00 | 0.00 |
September | 539.98 | 108.95 | 387.39 | 216.16 | 171.23 | 0.00 | 0.00 |
October | 578.28 | 214.09 | 463.21 | 328.66 | 134.55 | 0.00 | 0.00 |
November | 685.64 | 238.40 | 564.36 | 449.87 | 114.48 | 0.00 | 0.00 |
December | 629.52 | 282.59 | 539.67 | 436.80 | 102.87 | 0.00 | 0.00 |
Annual Sum or Average | 501.85 | 170.57 | 399.08 | 248.83 | 150.25 | 0.00 | 0.00 |
Minimum of Months | 297.60 | 61.78 | 227.18 | 41.52 | 102.87 | 0.00 | 0.00 |
Maximum of Months | 700.10 | 282.59 | 587.06 | 482.92 | 201.24 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 704.73 | 233.81 | 587.06 | 482.92 | 104.14 | 0.00 | 0.00 |
February | 672.88 | 242.55 | 563.10 | 448.94 | 114.16 | 0.00 | 0.00 |
March | 503.87 | 189.16 | 415.16 | 273.15 | 142.01 | 0.00 | 0.00 |
April | 302.92 | 168.17 | 268.89 | 108.12 | 160.77 | 0.00 | 0.00 |
May | 303.86 | 105.11 | 246.41 | 45.16 | 201.24 | 0.00 | 0.00 |
June | 337.48 | 63.42 | 227.18 | 41.52 | 185.66 | 0.00 | 0.00 |
July | 352.19 | 58.51 | 236.49 | 42.35 | 194.14 | 0.00 | 0.00 |
August | 447.42 | 68.58 | 301.10 | 125.87 | 175.23 | 0.00 | 0.00 |
September | 540.66 | 104.96 | 387.39 | 216.16 | 171.23 | 0.00 | 0.00 |
October | 581.65 | 202.72 | 463.21 | 328.66 | 134.55 | 0.00 | 0.00 |
November | 689.37 | 226.52 | 564.36 | 449.87 | 114.48 | 0.00 | 0.00 |
December | 633.14 | 269.27 | 539.67 | 436.80 | 102.87 | 0.00 | 0.00 |
Annual Sum or Average | 504.89 | 160.62 | 399.08 | 248.83 | 150.25 | 0.00 | 0.00 |
Minimum of Months | 302.92 | 58.51 | 227.18 | 41.52 | 102.87 | 0.00 | 0.00 |
Maximum of Months | 704.73 | 269.27 | 587.06 | 482.92 | 201.24 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.375476E+10 | 0.136536E+10 | 0.315124E+10 | 0.259224E+10 | 0.559006E+09 | 0.00 | 0.00 |
February | 0.324062E+10 | 0.127858E+10 | 0.273011E+10 | 0.217662E+10 | 0.553495E+09 | 0.00 | 0.00 |
March | 0.267976E+10 | 0.112516E+10 | 0.222851E+10 | 0.146624E+10 | 0.762278E+09 | 0.00 | 0.00 |
April | 0.154952E+10 | 0.985453E+09 | 0.139679E+10 | 0.561655E+09 | 0.835136E+09 | 0.00 | 0.00 |
May | 0.159090E+10 | 0.641905E+09 | 0.132267E+10 | 0.242436E+09 | 0.108024E+10 | 0.00 | 0.00 |
June | 0.174888E+10 | 0.348612E+09 | 0.118012E+10 | 0.215693E+09 | 0.964429E+09 | 0.00 | 0.00 |
July | 0.189176E+10 | 0.325990E+09 | 0.126943E+10 | 0.227319E+09 | 0.104211E+10 | 0.00 | 0.00 |
August | 0.240246E+10 | 0.380547E+09 | 0.161624E+10 | 0.675650E+09 | 0.940591E+09 | 0.00 | 0.00 |
September | 0.280809E+10 | 0.563151E+09 | 0.201237E+10 | 0.112289E+10 | 0.889480E+09 | 0.00 | 0.00 |
October | 0.310649E+10 | 0.116323E+10 | 0.248642E+10 | 0.176417E+10 | 0.722248E+09 | 0.00 | 0.00 |
November | 0.355993E+10 | 0.126280E+10 | 0.293163E+10 | 0.233694E+10 | 0.594696E+09 | 0.00 | 0.00 |
December | 0.337697E+10 | 0.155484E+10 | 0.289685E+10 | 0.234467E+10 | 0.552179E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.317101E+11 | 0.109956E+11 | 0.252224E+11 | 0.157265E+11 | 0.949588E+10 | 0.00 | 0.00 |
Minimum of Months | 0.154952E+10 | 0.325990E+09 | 0.118012E+10 | 0.215693E+09 | 0.552179E+09 | 0.00 | 0.00 |
Maximum of Months | 0.375476E+10 | 0.155484E+10 | 0.315124E+10 | 0.259224E+10 | 0.108024E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.186332E+10 | 0.717774E+09 | 0.157562E+10 | 0.129612E+10 | 0.279503E+09 | 0.00 | 0.00 |
February | 0.160789E+10 | 0.669753E+09 | 0.136506E+10 | 0.108831E+10 | 0.276747E+09 | 0.00 | 0.00 |
March | 0.132748E+10 | 0.594824E+09 | 0.111426E+10 | 0.733118E+09 | 0.381139E+09 | 0.00 | 0.00 |
April | 0.763252E+09 | 0.527961E+09 | 0.698395E+09 | 0.280828E+09 | 0.417568E+09 | 0.00 | 0.00 |
May | 0.783406E+09 | 0.339791E+09 | 0.661336E+09 | 0.121218E+09 | 0.540118E+09 | 0.00 | 0.00 |
June | 0.873054E+09 | 0.176718E+09 | 0.590061E+09 | 0.107847E+09 | 0.482214E+09 | 0.00 | 0.00 |
July | 0.944491E+09 | 0.165730E+09 | 0.634714E+09 | 0.113660E+09 | 0.521055E+09 | 0.00 | 0.00 |
August | 0.120012E+10 | 0.192118E+09 | 0.808121E+09 | 0.337825E+09 | 0.470296E+09 | 0.00 | 0.00 |
September | 0.140141E+10 | 0.286419E+09 | 0.100619E+10 | 0.561447E+09 | 0.444740E+09 | 0.00 | 0.00 |
October | 0.154448E+10 | 0.606020E+09 | 0.124321E+10 | 0.882085E+09 | 0.361124E+09 | 0.00 | 0.00 |
November | 0.176830E+10 | 0.662652E+09 | 0.146582E+10 | 0.116847E+10 | 0.297348E+09 | 0.00 | 0.00 |
December | 0.167621E+10 | 0.811361E+09 | 0.144843E+10 | 0.117234E+10 | 0.276090E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.157534E+11 | 0.575112E+10 | 0.126112E+11 | 0.786326E+10 | 0.474794E+10 | 0.00 | 0.00 |
Minimum of Months | 0.763252E+09 | 0.165730E+09 | 0.590061E+09 | 0.107847E+09 | 0.276090E+09 | 0.00 | 0.00 |
Maximum of Months | 0.186332E+10 | 0.811361E+09 | 0.157562E+10 | 0.129612E+10 | 0.540118E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.186208E+10 | 0.702179E+09 | 0.157239E+10 | 0.129346E+10 | 0.278930E+09 | 0.00 | 0.00 |
February | 0.160649E+10 | 0.655360E+09 | 0.136226E+10 | 0.108608E+10 | 0.276180E+09 | 0.00 | 0.00 |
March | 0.132654E+10 | 0.583197E+09 | 0.111197E+10 | 0.731614E+09 | 0.380357E+09 | 0.00 | 0.00 |
April | 0.763892E+09 | 0.514404E+09 | 0.696963E+09 | 0.280251E+09 | 0.416711E+09 | 0.00 | 0.00 |
May | 0.782906E+09 | 0.338918E+09 | 0.659979E+09 | 0.120969E+09 | 0.539010E+09 | 0.00 | 0.00 |
June | 0.868265E+09 | 0.188243E+09 | 0.588850E+09 | 0.107625E+09 | 0.481225E+09 | 0.00 | 0.00 |
July | 0.938358E+09 | 0.178373E+09 | 0.633412E+09 | 0.113427E+09 | 0.519986E+09 | 0.00 | 0.00 |
August | 0.119578E+10 | 0.205043E+09 | 0.806463E+09 | 0.337132E+09 | 0.469331E+09 | 0.00 | 0.00 |
September | 0.139720E+10 | 0.296715E+09 | 0.100412E+10 | 0.560295E+09 | 0.443828E+09 | 0.00 | 0.00 |
October | 0.154261E+10 | 0.601071E+09 | 0.124066E+10 | 0.880275E+09 | 0.360383E+09 | 0.00 | 0.00 |
November | 0.176748E+10 | 0.649787E+09 | 0.146281E+10 | 0.116607E+10 | 0.296738E+09 | 0.00 | 0.00 |
December | 0.167489E+10 | 0.794320E+09 | 0.144545E+10 | 0.116993E+10 | 0.275523E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.157265E+11 | 0.570761E+10 | 0.125853E+11 | 0.784713E+10 | 0.473820E+10 | 0.00 | 0.00 |
Minimum of Months | 0.763892E+09 | 0.178373E+09 | 0.588850E+09 | 0.107625E+09 | 0.275523E+09 | 0.00 | 0.00 |
Maximum of Months | 0.186208E+10 | 0.794320E+09 | 0.157239E+10 | 0.129346E+10 | 0.539010E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.186410E+10 | 0.695016E+09 | 0.157239E+10 | 0.129346E+10 | 0.278930E+09 | 0.00 | 0.00 |
February | 0.160796E+10 | 0.649408E+09 | 0.136226E+10 | 0.108608E+10 | 0.276180E+09 | 0.00 | 0.00 |
March | 0.132819E+10 | 0.577199E+09 | 0.111197E+10 | 0.731614E+09 | 0.380357E+09 | 0.00 | 0.00 |
April | 0.765736E+09 | 0.507468E+09 | 0.696963E+09 | 0.280251E+09 | 0.416711E+09 | 0.00 | 0.00 |
May | 0.784725E+09 | 0.335103E+09 | 0.659979E+09 | 0.120969E+09 | 0.539010E+09 | 0.00 | 0.00 |
June | 0.868232E+09 | 0.188451E+09 | 0.588850E+09 | 0.107625E+09 | 0.481225E+09 | 0.00 | 0.00 |
July | 0.938155E+09 | 0.178912E+09 | 0.633412E+09 | 0.113427E+09 | 0.519986E+09 | 0.00 | 0.00 |
August | 0.119572E+10 | 0.205412E+09 | 0.806463E+09 | 0.337132E+09 | 0.469331E+09 | 0.00 | 0.00 |
September | 0.139735E+10 | 0.296376E+09 | 0.100412E+10 | 0.560295E+09 | 0.443828E+09 | 0.00 | 0.00 |
October | 0.154375E+10 | 0.596524E+09 | 0.124066E+10 | 0.880275E+09 | 0.360383E+09 | 0.00 | 0.00 |
November | 0.176930E+10 | 0.643563E+09 | 0.146281E+10 | 0.116607E+10 | 0.296738E+09 | 0.00 | 0.00 |
December | 0.167649E+10 | 0.787259E+09 | 0.144545E+10 | 0.116993E+10 | 0.275523E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.157397E+11 | 0.566069E+10 | 0.125853E+11 | 0.784713E+10 | 0.473820E+10 | 0.00 | 0.00 |
Minimum of Months | 0.765736E+09 | 0.178912E+09 | 0.588850E+09 | 0.107625E+09 | 0.275523E+09 | 0.00 | 0.00 |
Maximum of Months | 0.186410E+10 | 0.787259E+09 | 0.157239E+10 | 0.129346E+10 | 0.539010E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.186656E+10 | 0.688685E+09 | 0.157239E+10 | 0.129346E+10 | 0.278930E+09 | 0.00 | 0.00 |
February | 0.160977E+10 | 0.644234E+09 | 0.136226E+10 | 0.108608E+10 | 0.276180E+09 | 0.00 | 0.00 |
March | 0.133057E+10 | 0.571123E+09 | 0.111197E+10 | 0.731614E+09 | 0.380357E+09 | 0.00 | 0.00 |
April | 0.768338E+09 | 0.500526E+09 | 0.696963E+09 | 0.280251E+09 | 0.416711E+09 | 0.00 | 0.00 |
May | 0.787962E+09 | 0.329985E+09 | 0.659979E+09 | 0.120969E+09 | 0.539010E+09 | 0.00 | 0.00 |
June | 0.869358E+09 | 0.186149E+09 | 0.588850E+09 | 0.107625E+09 | 0.481225E+09 | 0.00 | 0.00 |
July | 0.939183E+09 | 0.176774E+09 | 0.633412E+09 | 0.113427E+09 | 0.519986E+09 | 0.00 | 0.00 |
August | 0.119662E+10 | 0.203145E+09 | 0.806463E+09 | 0.337132E+09 | 0.469331E+09 | 0.00 | 0.00 |
September | 0.139835E+10 | 0.293814E+09 | 0.100412E+10 | 0.560295E+09 | 0.443828E+09 | 0.00 | 0.00 |
October | 0.154561E+10 | 0.591350E+09 | 0.124066E+10 | 0.880275E+09 | 0.360383E+09 | 0.00 | 0.00 |
November | 0.177147E+10 | 0.637941E+09 | 0.146281E+10 | 0.116607E+10 | 0.296738E+09 | 0.00 | 0.00 |
December | 0.167856E+10 | 0.781007E+09 | 0.144545E+10 | 0.116993E+10 | 0.275523E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.157624E+11 | 0.560473E+10 | 0.125853E+11 | 0.784713E+10 | 0.473820E+10 | 0.00 | 0.00 |
Minimum of Months | 0.768338E+09 | 0.176774E+09 | 0.588850E+09 | 0.107625E+09 | 0.275523E+09 | 0.00 | 0.00 |
Maximum of Months | 0.186656E+10 | 0.781007E+09 | 0.157239E+10 | 0.129346E+10 | 0.539010E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.374830E+10 | 0.134672E+10 | 0.314478E+10 | 0.258692E+10 | 0.557859E+09 | 0.00 | 0.00 |
February | 0.323376E+10 | 0.125884E+10 | 0.272451E+10 | 0.217215E+10 | 0.552359E+09 | 0.00 | 0.00 |
March | 0.267456E+10 | 0.111041E+10 | 0.222394E+10 | 0.146323E+10 | 0.760714E+09 | 0.00 | 0.00 |
April | 0.154889E+10 | 0.967191E+09 | 0.139393E+10 | 0.560503E+09 | 0.833423E+09 | 0.00 | 0.00 |
May | 0.158759E+10 | 0.636131E+09 | 0.131996E+10 | 0.241939E+09 | 0.107802E+10 | 0.00 | 0.00 |
June | 0.173912E+10 | 0.357732E+09 | 0.117770E+10 | 0.215251E+09 | 0.962450E+09 | 0.00 | 0.00 |
July | 0.187790E+10 | 0.339999E+09 | 0.126682E+10 | 0.226853E+09 | 0.103997E+10 | 0.00 | 0.00 |
August | 0.239295E+10 | 0.391876E+09 | 0.161293E+10 | 0.674264E+09 | 0.938662E+09 | 0.00 | 0.00 |
September | 0.279816E+10 | 0.573454E+09 | 0.200824E+10 | 0.112059E+10 | 0.887655E+09 | 0.00 | 0.00 |
October | 0.309838E+10 | 0.115810E+10 | 0.248132E+10 | 0.176055E+10 | 0.720766E+09 | 0.00 | 0.00 |
November | 0.355477E+10 | 0.124873E+10 | 0.292562E+10 | 0.233214E+10 | 0.593476E+09 | 0.00 | 0.00 |
December | 0.337335E+10 | 0.152709E+10 | 0.289091E+10 | 0.233986E+10 | 0.551047E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.316278E+11 | 0.109163E+11 | 0.251707E+11 | 0.156943E+11 | 0.947640E+10 | 0.00 | 0.00 |
Minimum of Months | 0.154889E+10 | 0.339999E+09 | 0.117770E+10 | 0.215251E+09 | 0.551047E+09 | 0.00 | 0.00 |
Maximum of Months | 0.374830E+10 | 0.152709E+10 | 0.314478E+10 | 0.258692E+10 | 0.107802E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.187021E+10 | 0.676362E+09 | 0.157239E+10 | 0.129346E+10 | 0.278930E+09 | 0.00 | 0.00 |
February | 0.161318E+10 | 0.632585E+09 | 0.136226E+10 | 0.108608E+10 | 0.276180E+09 | 0.00 | 0.00 |
March | 0.133335E+10 | 0.558714E+09 | 0.111197E+10 | 0.731614E+09 | 0.380357E+09 | 0.00 | 0.00 |
April | 0.770651E+09 | 0.487984E+09 | 0.696963E+09 | 0.280251E+09 | 0.416711E+09 | 0.00 | 0.00 |
May | 0.789813E+09 | 0.320849E+09 | 0.659979E+09 | 0.120969E+09 | 0.539010E+09 | 0.00 | 0.00 |
June | 0.870235E+09 | 0.177281E+09 | 0.588850E+09 | 0.107625E+09 | 0.481225E+09 | 0.00 | 0.00 |
July | 0.939642E+09 | 0.168385E+09 | 0.633412E+09 | 0.113427E+09 | 0.519986E+09 | 0.00 | 0.00 |
August | 0.119661E+10 | 0.194122E+09 | 0.806463E+09 | 0.337132E+09 | 0.469331E+09 | 0.00 | 0.00 |
September | 0.139799E+10 | 0.285972E+09 | 0.100412E+10 | 0.560295E+09 | 0.443828E+09 | 0.00 | 0.00 |
October | 0.154502E+10 | 0.583414E+09 | 0.124066E+10 | 0.880275E+09 | 0.360383E+09 | 0.00 | 0.00 |
November | 0.177308E+10 | 0.628229E+09 | 0.146281E+10 | 0.116607E+10 | 0.296738E+09 | 0.00 | 0.00 |
December | 0.168239E+10 | 0.767917E+09 | 0.144545E+10 | 0.116993E+10 | 0.275523E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.157822E+11 | 0.548181E+10 | 0.125853E+11 | 0.784713E+10 | 0.473820E+10 | 0.00 | 0.00 |
Minimum of Months | 0.770651E+09 | 0.168385E+09 | 0.588850E+09 | 0.107625E+09 | 0.275523E+09 | 0.00 | 0.00 |
Maximum of Months | 0.187021E+10 | 0.767917E+09 | 0.157239E+10 | 0.129346E+10 | 0.539010E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.187123E+10 | 0.673967E+09 | 0.157239E+10 | 0.129346E+10 | 0.278930E+09 | 0.00 | 0.00 |
February | 0.161404E+10 | 0.630622E+09 | 0.136226E+10 | 0.108608E+10 | 0.276180E+09 | 0.00 | 0.00 |
March | 0.133427E+10 | 0.556533E+09 | 0.111197E+10 | 0.731614E+09 | 0.380357E+09 | 0.00 | 0.00 |
April | 0.771481E+09 | 0.485870E+09 | 0.696963E+09 | 0.280251E+09 | 0.416711E+09 | 0.00 | 0.00 |
May | 0.791128E+09 | 0.319045E+09 | 0.659979E+09 | 0.120969E+09 | 0.539010E+09 | 0.00 | 0.00 |
June | 0.870887E+09 | 0.176427E+09 | 0.588850E+09 | 0.107625E+09 | 0.481225E+09 | 0.00 | 0.00 |
July | 0.940229E+09 | 0.167606E+09 | 0.633412E+09 | 0.113427E+09 | 0.519986E+09 | 0.00 | 0.00 |
August | 0.119711E+10 | 0.193335E+09 | 0.806463E+09 | 0.337132E+09 | 0.469331E+09 | 0.00 | 0.00 |
September | 0.139845E+10 | 0.285125E+09 | 0.100412E+10 | 0.560295E+09 | 0.443828E+09 | 0.00 | 0.00 |
October | 0.154566E+10 | 0.581848E+09 | 0.124066E+10 | 0.880275E+09 | 0.360383E+09 | 0.00 | 0.00 |
November | 0.177387E+10 | 0.626426E+09 | 0.146281E+10 | 0.116607E+10 | 0.296738E+09 | 0.00 | 0.00 |
December | 0.168314E+10 | 0.765933E+09 | 0.144545E+10 | 0.116993E+10 | 0.275523E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.157915E+11 | 0.546274E+10 | 0.125853E+11 | 0.784713E+10 | 0.473820E+10 | 0.00 | 0.00 |
Minimum of Months | 0.771481E+09 | 0.167606E+09 | 0.588850E+09 | 0.107625E+09 | 0.275523E+09 | 0.00 | 0.00 |
Maximum of Months | 0.187123E+10 | 0.765933E+09 | 0.157239E+10 | 0.129346E+10 | 0.539010E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.187515E+10 | 0.663915E+09 | 0.157239E+10 | 0.129346E+10 | 0.278930E+09 | 0.00 | 0.00 |
February | 0.161729E+10 | 0.621900E+09 | 0.136226E+10 | 0.108608E+10 | 0.276180E+09 | 0.00 | 0.00 |
March | 0.133812E+10 | 0.546272E+09 | 0.111197E+10 | 0.731614E+09 | 0.380357E+09 | 0.00 | 0.00 |
April | 0.775074E+09 | 0.475173E+09 | 0.696963E+09 | 0.280251E+09 | 0.416711E+09 | 0.00 | 0.00 |
May | 0.797080E+09 | 0.310317E+09 | 0.659979E+09 | 0.120969E+09 | 0.539010E+09 | 0.00 | 0.00 |
June | 0.872355E+09 | 0.173989E+09 | 0.588850E+09 | 0.107625E+09 | 0.481225E+09 | 0.00 | 0.00 |
July | 0.941425E+09 | 0.165476E+09 | 0.633412E+09 | 0.113427E+09 | 0.519986E+09 | 0.00 | 0.00 |
August | 0.119800E+10 | 0.191376E+09 | 0.806463E+09 | 0.337132E+09 | 0.469331E+09 | 0.00 | 0.00 |
September | 0.139962E+10 | 0.282392E+09 | 0.100412E+10 | 0.560295E+09 | 0.443828E+09 | 0.00 | 0.00 |
October | 0.154886E+10 | 0.573430E+09 | 0.124066E+10 | 0.880275E+09 | 0.360383E+09 | 0.00 | 0.00 |
November | 0.177719E+10 | 0.617941E+09 | 0.146281E+10 | 0.116607E+10 | 0.296738E+09 | 0.00 | 0.00 |
December | 0.168611E+10 | 0.756886E+09 | 0.144545E+10 | 0.116993E+10 | 0.275523E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.158263E+11 | 0.537907E+10 | 0.125853E+11 | 0.784713E+10 | 0.473820E+10 | 0.00 | 0.00 |
Minimum of Months | 0.775074E+09 | 0.165476E+09 | 0.588850E+09 | 0.107625E+09 | 0.275523E+09 | 0.00 | 0.00 |
Maximum of Months | 0.187515E+10 | 0.756886E+09 | 0.157239E+10 | 0.129346E+10 | 0.539010E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.188754E+10 | 0.626243E+09 | 0.157239E+10 | 0.129346E+10 | 0.278930E+09 | 0.00 | 0.00 |
February | 0.162782E+10 | 0.586788E+09 | 0.136226E+10 | 0.108608E+10 | 0.276180E+09 | 0.00 | 0.00 |
March | 0.134957E+10 | 0.506644E+09 | 0.111197E+10 | 0.731614E+09 | 0.380357E+09 | 0.00 | 0.00 |
April | 0.785166E+09 | 0.435903E+09 | 0.696963E+09 | 0.280251E+09 | 0.416711E+09 | 0.00 | 0.00 |
May | 0.813866E+09 | 0.281529E+09 | 0.659979E+09 | 0.120969E+09 | 0.539010E+09 | 0.00 | 0.00 |
June | 0.874746E+09 | 0.164373E+09 | 0.588850E+09 | 0.107625E+09 | 0.481225E+09 | 0.00 | 0.00 |
July | 0.943297E+09 | 0.156710E+09 | 0.633412E+09 | 0.113427E+09 | 0.519986E+09 | 0.00 | 0.00 |
August | 0.119837E+10 | 0.183682E+09 | 0.806463E+09 | 0.337132E+09 | 0.469331E+09 | 0.00 | 0.00 |
September | 0.140140E+10 | 0.272068E+09 | 0.100412E+10 | 0.560295E+09 | 0.443828E+09 | 0.00 | 0.00 |
October | 0.155790E+10 | 0.542959E+09 | 0.124066E+10 | 0.880275E+09 | 0.360383E+09 | 0.00 | 0.00 |
November | 0.178686E+10 | 0.587150E+09 | 0.146281E+10 | 0.116607E+10 | 0.296738E+09 | 0.00 | 0.00 |
December | 0.169580E+10 | 0.721220E+09 | 0.144545E+10 | 0.116993E+10 | 0.275523E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.159223E+11 | 0.506527E+10 | 0.125853E+11 | 0.784713E+10 | 0.473820E+10 | 0.00 | 0.00 |
Minimum of Months | 0.785166E+09 | 0.156710E+09 | 0.588850E+09 | 0.107625E+09 | 0.275523E+09 | 0.00 | 0.00 |
Maximum of Months | 0.188754E+10 | 0.721220E+09 | 0.157239E+10 | 0.129346E+10 | 0.539010E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 0.85 | -1.5 | -4.5 | 2.30 | -12.1 | 27.63 | 226.20 | 0.01 |
February | -0.2 | -2.7 | -6.1 | 3.74 | -13.6 | 32.55 | 253.27 | 0.01 |
March | 4.82 | 0.36 | -5.5 | 4.48 | -7.8 | 54.65 | 233.06 | 0.03 |
April | 6.08 | 2.29 | -2.0 | 5.23 | -4.9 | 81.86 | 179.11 | 0.05 |
May | 13.74 | 7.52 | 1.82 | 4.10 | 2.75 | 117.64 | 180.87 | 0.01 |
June | 22.16 | 12.46 | 5.10 | 4.19 | 9.76 | 95.26 | 290.95 | 0.00 |
July | 22.71 | 13.25 | 6.43 | 4.25 | 12.01 | 110.54 | 215.12 | 0.03 |
August | 21.74 | 12.79 | 6.20 | 3.81 | 10.76 | 77.72 | 272.61 | 0.02 |
September | 18.54 | 9.35 | 1.35 | 4.13 | 5.52 | 70.51 | 233.03 | 0.01 |
October | 7.12 | 2.51 | -2.7 | 3.54 | -5.8 | 44.60 | 216.74 | 0.01 |
November | 3.03 | 0.31 | -2.9 | 2.79 | -8.8 | 30.71 | 220.86 | 0.01 |
December | -1.0 | -4.5 | -9.5 | 4.43 | -15.4 | 27.45 | 194.75 | 0.01 |
Annual Sum or Average | 10.02 | 4.37 | -1.0 | 3.91 | -2.2 | 64.46 | 226.11 | 0.02 |
Minimum of Months | -1.0 | -4.5 | -9.5 | 2.30 | -15.4 | 27.45 | 179.11 | 0.00 |
Maximum of Months | 22.71 | 13.25 | 6.43 | 5.23 | 12.01 | 117.64 | 290.95 | 0.05 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 21.00 | 20-JAN-12:00 | 6.97 | -11.0 | 0.50 | 6.55 | 41.00 | 961.00 |
February | 20.00 | 18-FEB-12:00 | 7.74 | -5.0 | 3.60 | 6.35 | 56.00 | 998.00 |
March | 24.00 | 14-MAR-12:00 | 7.90 | -12.0 | 3.10 | 11.65 | 160.00 | 837.50 |
April | 22.00 | 19-APR-13:09 | 8.49 | -5.7 | 5.52 | 11.55 | 235.67 | 789.67 |
May | 29.00 | 17-MAY-12:00 | 11.92 | -3.0 | 5.10 | 18.99 | 432.50 | 162.00 |
June | 39.40 | 26-JUN-14:00 | 15.63 | -2.8 | 4.60 | 21.96 | 136.50 | 752.00 |
July | 37.00 | 16-JUL-12:00 | 14.90 | -3.0 | 3.10 | 26.65 | 319.50 | 109.50 |
August | 37.00 | 16-AUG-13:00 | 16.36 | 3.00 | 3.60 | 28.27 | 90.00 | 895.00 |
September | 32.70 | 09-SEP-12:00 | 13.05 | -3.9 | 3.00 | 16.30 | 270.50 | 562.00 |
October | 27.00 | 11-OCT-13:00 | 9.73 | -9.0 | 4.60 | 12.03 | 89.50 | 844.00 |
November | 22.00 | 06-NOV-13:09 | 7.10 | -13.0 | 2.60 | 4.92 | 88.67 | 883.33 |
December | 22.00 | 01-DEC-13:00 | 7.94 | -8.0 | 2.60 | 5.13 | 49.00 | 862.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 20.00 | 6.97 | -13.0 | 0.50 | 4.92 | 41.00 | 109.50 | |
Maximum of Months | 39.40 | 16.36 | 3.00 | 5.52 | 28.27 | 432.50 | 998.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -19.0 | 05-JAN-18:00 | -19.0 | -19.0 | 1.50 | -37.1 | 0.00 | 0.00 |
February | -20.0 | 12-FEB-04:00 | -20.0 | -20.0 | 3.60 | -39.1 | 0.00 | 0.00 |
March | -15.6 | 19-MAR-06:00 | -15.6 | -15.6 | 10.80 | -25.3 | 24.00 | 0.00 |
April | -8.0 | 03-APR-02:00 | -8.0 | -8.0 | 3.10 | -22.2 | 0.00 | 0.00 |
May | -1.0 | 03-MAY-01:00 | -2.4 | -4.0 | 4.10 | -15.7 | 0.00 | 0.00 |
June | 6.60 | 09-JUN-03:00 | 3.45 | 0.00 | 3.60 | -6.9 | 0.00 | 0.00 |
July | 9.00 | 02-JUL-04:00 | 3.30 | -3.0 | 3.60 | -5.3 | 20.00 | 184.50 |
August | 11.00 | 12-AUG-22:00 | 7.22 | 4.00 | 4.10 | 5.13 | 0.00 | 0.00 |
September | -1.7 | 22-SEP-05:10 | -2.9 | -4.3 | 3.60 | -15.8 | 0.00 | 0.00 |
October | -10.0 | 30-OCT-03:00 | -10.0 | -10.0 | 2.60 | -18.6 | 0.00 | 0.00 |
November | -15.0 | 29-NOV-20:00 | -15.0 | -15.0 | 3.10 | -33.5 | 0.00 | 0.00 |
December | -23.0 | 22-DEC-02:00 | -23.0 | -23.0 | 3.60 | -42.7 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -23.0 | -23.0 | -23.0 | 1.50 | -42.7 | 0.00 | 0.00 | |
Maximum of Months | 11.00 | 7.22 | 4.00 | 10.80 | 5.13 | 24.00 | 184.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 7.55 | 20-JAN-11:00 | 20.00 | -6.0 | 2.60 | 7.95 | 43.00 | 971.50 |
February | 7.98 | 18-FEB-14:00 | 19.00 | -3.0 | 3.60 | 5.94 | 151.00 | 410.00 |
March | 8.00 | 31-MAR-17:00 | 15.00 | 2.00 | 2.60 | 1.58 | 19.50 | 261.00 |
April | 12.50 | 28-APR-13:00 | 18.00 | 9.00 | 9.80 | 9.72 | 335.00 | 196.50 |
May | 14.87 | 31-MAY-13:00 | 28.00 | 7.00 | 4.60 | 14.47 | 157.50 | 830.50 |
June | 19.65 | 18-JUN-11:00 | 29.40 | 15.50 | 6.10 | 16.85 | 272.50 | 596.00 |
July | 19.75 | 30-JUL-13:00 | 29.00 | 16.00 | 3.60 | 18.99 | 217.50 | 412.00 |
August | 18.80 | 05-AUG-14:09 | 25.83 | 15.33 | 6.62 | 20.54 | 196.33 | 4.00 |
September | 14.95 | 01-SEP-11:00 | 24.40 | 9.40 | 3.00 | 10.69 | 193.50 | 684.00 |
October | 9.73 | 11-OCT-13:00 | 27.00 | -9.0 | 4.60 | 12.03 | 89.50 | 844.00 |
November | 9.33 | 09-NOV-10:00 | 20.00 | 0.00 | 1.50 | 11.07 | 112.00 | 860.50 |
December | 7.94 | 01-DEC-13:00 | 22.00 | -8.0 | 2.60 | 5.13 | 49.00 | 862.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 7.55 | 15.00 | -9.0 | 1.50 | 1.58 | 19.50 | 4.00 | |
Maximum of Months | 19.75 | 29.40 | 16.00 | 9.80 | 20.54 | 335.00 | 971.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 5.00 | 28-JAN-10:00 | 5.00 | 5.00 | 1.00 | -6.2 | 207.00 | 309.00 |
February | 5.00 | 19-FEB-14:30 | 5.00 | 5.00 | 1.80 | -0.4 | 188.00 | 467.00 |
March | 7.00 | 17-MAR-14:00 | 8.00 | 7.39 | 8.20 | 1.16 | 121.50 | 3.00 |
April | 9.00 | 28-APR-13:00 | 18.00 | 12.50 | 9.80 | 9.72 | 335.00 | 196.50 |
May | 11.00 | 21-MAY-21:10 | 12.83 | 11.73 | 2.68 | 6.78 | 0.00 | 0.00 |
June | 15.50 | 18-JUN-11:00 | 29.40 | 19.65 | 6.10 | 16.85 | 272.50 | 596.00 |
July | 17.00 | 28-JUL-16:00 | 20.00 | 17.92 | 5.70 | 15.02 | 155.00 | 32.00 |
August | 18.00 | 04-AUG-01:00 | 18.00 | 18.00 | 2.60 | 8.74 | 0.00 | 0.00 |
September | 12.20 | 30-SEP-14:00 | 17.20 | 13.90 | 5.10 | 9.72 | 209.00 | 82.50 |
October | 6.00 | 01-OCT-19:00 | 9.00 | 7.28 | 3.10 | 3.69 | 0.00 | 0.00 |
November | 7.00 | 09-NOV-23:00 | 8.00 | 7.40 | 4.10 | 3.06 | 0.00 | 0.00 |
December | 1.00 | 30-DEC-14:00 | 7.00 | 4.06 | 9.80 | -1.2 | 101.00 | 91.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 1.00 | 5.00 | 4.06 | 1.00 | -6.2 | 0.00 | 0.00 | |
Maximum of Months | 18.00 | 29.40 | 19.65 | 9.80 | 16.85 | 335.00 | 596.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 8.52 | 21.53 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 7.90 | 29.36 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 8.65 | 35.75 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 10.64 | 38.62 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 13.34 | 48.35 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 16.03 | 59.81 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 17.97 | 52.29 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 18.66 | 51.98 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 17.88 | 41.73 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 15.85 | 30.82 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 13.14 | 23.90 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 10.46 | 18.59 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 13.28 | 37.76 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 7.90 | 18.59 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 18.66 | 59.81 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK1
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.371375E+09 | -247797189.5 | 0.00 | 0.00 | 744.00 | 0.00 | -123577972.2 | 58.99 | 0.00 | 0.00 |
February | 0.339965E+09 | -227782282.3 | 0.00 | 0.00 | 672.00 | 0.00 | -112183127.4 | 59.00 | 0.00 | 0.00 |
March | 0.374662E+09 | -252567852.4 | 0.00 | 0.00 | 744.00 | 0.00 | -122094467.5 | 58.99 | 0.00 | 0.00 |
April | 0.349597E+09 | -231747028.7 | 0.00 | 0.00 | 720.00 | 0.00 | -117850142.8 | 58.99 | 0.00 | 0.00 |
May | 0.342901E+09 | -226494351.5 | 0.00 | 0.00 | 744.00 | 0.00 | -116406414.0 | 58.99 | 0.00 | 0.00 |
June | 0.317667E+09 | -208355759.4 | 0.00 | 0.00 | 720.00 | 0.00 | -109310900.4 | 58.99 | 0.00 | 0.00 |
July | 0.314130E+09 | -201329656.5 | 0.00 | 0.00 | 744.00 | 0.00 | -112800383.2 | 58.99 | 0.00 | 0.00 |
August | 0.314903E+09 | -202217478.5 | 0.00 | 0.00 | 744.00 | 0.00 | -112685619.7 | 58.99 | 0.00 | 0.00 |
September | 0.307003E+09 | -197248315.8 | 0.00 | 0.00 | 720.00 | 0.00 | -109755029.1 | 58.99 | 0.00 | 0.00 |
October | 0.330120E+09 | -211851397.7 | 0.00 | 0.00 | 744.00 | 0.00 | -118268887.1 | 58.99 | 0.00 | 0.00 |
November | 0.335272E+09 | -217274736.5 | 0.00 | 0.00 | 720.00 | 0.00 | -117996991.3 | 58.99 | 0.00 | 0.00 |
December | 0.362446E+09 | -238551829.7 | 0.00 | 0.00 | 744.00 | 0.00 | -123894121.7 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.406004E+10 | -0.266322E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.139682E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.307003E+09 | -252567852.4 | 0.00 | 0.00 | 672.00 | 0.00 | -123894121.7 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.374662E+09 | -197248315.8 | 0.00 | 0.00 | 744.00 | 0.00 | -109310900.4 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK2
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.368674E+09 | -247794058.4 | 0.00 | 0.00 | 744.00 | 0.00 | -120879934.9 | 58.99 | 0.00 | 0.00 |
February | 0.337833E+09 | -227800833.3 | 0.00 | 0.00 | 672.00 | 0.00 | -110031831.3 | 58.99 | 0.00 | 0.00 |
March | 0.372345E+09 | -252567576.3 | 0.00 | 0.00 | 744.00 | 0.00 | -119777159.4 | 58.99 | 0.00 | 0.00 |
April | 0.346957E+09 | -231744882.8 | 0.00 | 0.00 | 720.00 | 0.00 | -115212272.3 | 58.99 | 0.00 | 0.00 |
May | 0.341123E+09 | -226497006.6 | 0.00 | 0.00 | 744.00 | 0.00 | -114626011.9 | 58.99 | 0.00 | 0.00 |
June | 0.317464E+09 | -208354900.2 | 0.00 | 0.00 | 720.00 | 0.00 | -109109401.4 | 58.99 | 0.00 | 0.00 |
July | 0.313926E+09 | -201334421.3 | 0.00 | 0.00 | 744.00 | 0.00 | -112592072.8 | 58.99 | 0.00 | 0.00 |
August | 0.314767E+09 | -202203941.8 | 0.00 | 0.00 | 744.00 | 0.00 | -112563109.0 | 58.99 | 0.00 | 0.00 |
September | 0.306570E+09 | -197248532.4 | 0.00 | 0.00 | 720.00 | 0.00 | -109321635.5 | 58.99 | 0.00 | 0.00 |
October | 0.328152E+09 | -211851000.9 | 0.00 | 0.00 | 744.00 | 0.00 | -116300794.4 | 58.99 | 0.00 | 0.00 |
November | 0.332709E+09 | -217272125.4 | 0.00 | 0.00 | 720.00 | 0.00 | -115436896.8 | 58.99 | 0.00 | 0.00 |
December | 0.360105E+09 | -238553516.7 | 0.00 | 0.00 | 744.00 | 0.00 | -121551831.7 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.404063E+10 | -0.266322E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.137740E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.306570E+09 | -252567576.3 | 0.00 | 0.00 | 672.00 | 0.00 | -121551831.7 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.372345E+09 | -197248532.4 | 0.00 | 0.00 | 744.00 | 0.00 | -109109401.4 | 58.99 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK3
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.340428E+09 | -217906986.5 | 0.00 | 0.00 | 744.00 | 0.00 | -122521133.7 | 58.99 | 0.00 | 0.00 |
February | 0.311959E+09 | -200479193.8 | 0.00 | 0.00 | 672.00 | 0.00 | -111480044.8 | 58.99 | 0.00 | 0.00 |
March | 0.346401E+09 | -225416922.0 | 0.00 | 0.00 | 744.00 | 0.00 | -120983656.5 | 58.99 | 0.00 | 0.00 |
April | 0.320482E+09 | -203845582.2 | 0.00 | 0.00 | 720.00 | 0.00 | -116636623.5 | 58.98 | 0.00 | 0.00 |
May | 0.315701E+09 | -200906197.8 | 0.00 | 0.00 | 744.00 | 0.00 | -114794670.6 | 58.99 | 0.00 | 0.00 |
June | 0.293274E+09 | -185538120.2 | 0.00 | 0.00 | 720.00 | 0.00 | -107736259.6 | 59.00 | 0.00 | 0.00 |
July | 0.287005E+09 | -175963440.0 | 0.00 | 0.00 | 744.00 | 0.00 | -111041534.3 | 59.01 | 0.00 | 0.00 |
August | 0.291738E+09 | -180617209.6 | 0.00 | 0.00 | 744.00 | 0.00 | -111120376.4 | 58.99 | 0.00 | 0.00 |
September | 0.281622E+09 | -173386082.9 | 0.00 | 0.00 | 720.00 | 0.00 | -108235822.3 | 58.98 | 0.00 | 0.00 |
October | 0.303228E+09 | -186325053.9 | 0.00 | 0.00 | 744.00 | 0.00 | -116903099.1 | 58.99 | 0.00 | 0.00 |
November | 0.308707E+09 | -191815101.3 | 0.00 | 0.00 | 720.00 | 0.00 | -116892227.7 | 59.00 | 0.00 | 0.00 |
December | 0.331450E+09 | -208207282.7 | 0.00 | 0.00 | 744.00 | 0.00 | -123242228.3 | 59.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.373199E+10 | -0.235041E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.138159E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.281622E+09 | -225416922.0 | 0.00 | 0.00 | 672.00 | 0.00 | -123242228.3 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.346401E+09 | -173386082.9 | 0.00 | 0.00 | 744.00 | 0.00 | -107736259.6 | 59.01 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK4
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.340895E+09 | -217901260.1 | 0.00 | 0.00 | 744.00 | 0.00 | -122993252.0 | 58.99 | 0.00 | 0.00 |
February | 0.312337E+09 | -200481592.2 | 0.00 | 0.00 | 672.00 | 0.00 | -111855694.1 | 58.99 | 0.00 | 0.00 |
March | 0.346782E+09 | -225413259.8 | 0.00 | 0.00 | 744.00 | 0.00 | -121368401.8 | 58.99 | 0.00 | 0.00 |
April | 0.320946E+09 | -203812864.7 | 0.00 | 0.00 | 720.00 | 0.00 | -117132982.9 | 59.00 | 0.00 | 0.00 |
May | 0.316007E+09 | -200880647.3 | 0.00 | 0.00 | 744.00 | 0.00 | -115126623.2 | 59.00 | 0.00 | 0.00 |
June | 0.293251E+09 | -185568244.1 | 0.00 | 0.00 | 720.00 | 0.00 | -107682486.6 | 58.98 | 0.00 | 0.00 |
July | 0.286954E+09 | -176039780.4 | 0.00 | 0.00 | 744.00 | 0.00 | -110913772.7 | 58.98 | 0.00 | 0.00 |
August | 0.291711E+09 | -180606956.1 | 0.00 | 0.00 | 744.00 | 0.00 | -111104163.8 | 58.99 | 0.00 | 0.00 |
September | 0.281651E+09 | -173361719.1 | 0.00 | 0.00 | 720.00 | 0.00 | -108289196.5 | 58.99 | 0.00 | 0.00 |
October | 0.303532E+09 | -186325169.7 | 0.00 | 0.00 | 744.00 | 0.00 | -117206740.6 | 58.99 | 0.00 | 0.00 |
November | 0.309129E+09 | -191807859.3 | 0.00 | 0.00 | 720.00 | 0.00 | -117321026.4 | 59.00 | 0.00 | 0.00 |
December | 0.331879E+09 | -208214947.9 | 0.00 | 0.00 | 744.00 | 0.00 | -123663996.1 | 59.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.373507E+10 | -0.235041E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.138466E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.281651E+09 | -225413259.8 | 0.00 | 0.00 | 672.00 | 0.00 | -123663996.1 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.346782E+09 | -173361719.1 | 0.00 | 0.00 | 744.00 | 0.00 | -107682486.6 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK5
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.330533E+09 | -205930830.9 | 0.00 | 0.00 | 744.00 | 0.00 | -124602599.7 | 59.00 | 0.00 | 0.00 |
February | 0.302799E+09 | -189580302.3 | 0.00 | 0.00 | 672.00 | 0.00 | -113218780.9 | 58.99 | 0.00 | 0.00 |
March | 0.336252E+09 | -213269615.1 | 0.00 | 0.00 | 744.00 | 0.00 | -122982537.9 | 59.00 | 0.00 | 0.00 |
April | 0.311684E+09 | -192873605.6 | 0.00 | 0.00 | 720.00 | 0.00 | -118810166.4 | 58.99 | 0.00 | 0.00 |
May | 0.306608E+09 | -189984075.2 | 0.00 | 0.00 | 744.00 | 0.00 | -116623881.4 | 58.99 | 0.00 | 0.00 |
June | 0.284080E+09 | -175592897.3 | 0.00 | 0.00 | 720.00 | 0.00 | -108487267.8 | 58.98 | 0.00 | 0.00 |
July | 0.278122E+09 | -166448190.7 | 0.00 | 0.00 | 744.00 | 0.00 | -111674129.6 | 58.99 | 0.00 | 0.00 |
August | 0.282733E+09 | -170909150.8 | 0.00 | 0.00 | 744.00 | 0.00 | -111823912.2 | 58.99 | 0.00 | 0.00 |
September | 0.273053E+09 | -164063855.1 | 0.00 | 0.00 | 720.00 | 0.00 | -108988803.3 | 58.99 | 0.00 | 0.00 |
October | 0.294556E+09 | -176087507.7 | 0.00 | 0.00 | 744.00 | 0.00 | -118468356.3 | 59.00 | 0.00 | 0.00 |
November | 0.299835E+09 | -181193178.9 | 0.00 | 0.00 | 720.00 | 0.00 | -118642014.5 | 58.99 | 0.00 | 0.00 |
December | 0.322185E+09 | -196933576.4 | 0.00 | 0.00 | 744.00 | 0.00 | -125251355.2 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.362244E+10 | -0.222287E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.139957E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.273053E+09 | -213269615.1 | 0.00 | 0.00 | 672.00 | 0.00 | -125251355.2 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.336252E+09 | -164063855.1 | 0.00 | 0.00 | 744.00 | 0.00 | -108487267.8 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK6
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.330287E+09 | -205925856.2 | 0.00 | 0.00 | 744.00 | 0.00 | -124361550.2 | 59.00 | 0.00 | 0.00 |
February | 0.302633E+09 | -189574845.6 | 0.00 | 0.00 | 672.00 | 0.00 | -113058546.8 | 59.00 | 0.00 | 0.00 |
March | 0.335900E+09 | -213305567.8 | 0.00 | 0.00 | 744.00 | 0.00 | -122594130.2 | 58.98 | 0.00 | 0.00 |
April | 0.311210E+09 | -192881569.5 | 0.00 | 0.00 | 720.00 | 0.00 | -118328138.9 | 58.99 | 0.00 | 0.00 |
May | 0.306058E+09 | -189991489.5 | 0.00 | 0.00 | 744.00 | 0.00 | -116066783.8 | 58.99 | 0.00 | 0.00 |
June | 0.284134E+09 | -175561706.6 | 0.00 | 0.00 | 720.00 | 0.00 | -108572440.6 | 59.00 | 0.00 | 0.00 |
July | 0.278174E+09 | -166464060.8 | 0.00 | 0.00 | 744.00 | 0.00 | -111710004.0 | 58.99 | 0.00 | 0.00 |
August | 0.282796E+09 | -170907346.2 | 0.00 | 0.00 | 744.00 | 0.00 | -111888822.1 | 58.99 | 0.00 | 0.00 |
September | 0.272998E+09 | -164050453.4 | 0.00 | 0.00 | 720.00 | 0.00 | -108948044.3 | 58.99 | 0.00 | 0.00 |
October | 0.294052E+09 | -176115436.2 | 0.00 | 0.00 | 744.00 | 0.00 | -117936731.0 | 58.99 | 0.00 | 0.00 |
November | 0.299463E+09 | -181195691.4 | 0.00 | 0.00 | 720.00 | 0.00 | -118266943.3 | 58.99 | 0.00 | 0.00 |
December | 0.321941E+09 | -196924423.1 | 0.00 | 0.00 | 744.00 | 0.00 | -125016286.0 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.361965E+10 | -0.222290E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.139675E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.272998E+09 | -213305567.8 | 0.00 | 0.00 | 672.00 | 0.00 | -125016286.0 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.335900E+09 | -164050453.4 | 0.00 | 0.00 | 744.00 | 0.00 | -108572440.6 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK7
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.330443E+09 | -205930683.4 | 0.00 | 0.00 | 744.00 | 0.00 | -124512594.2 | 59.00 | 0.00 | 0.00 |
February | 0.302759E+09 | -189581836.5 | 0.00 | 0.00 | 672.00 | 0.00 | -113176787.5 | 58.99 | 0.00 | 0.00 |
March | 0.336049E+09 | -213279286.8 | 0.00 | 0.00 | 744.00 | 0.00 | -122769541.9 | 58.99 | 0.00 | 0.00 |
April | 0.311354E+09 | -192884465.6 | 0.00 | 0.00 | 720.00 | 0.00 | -118469230.6 | 58.99 | 0.00 | 0.00 |
May | 0.306214E+09 | -189994245.0 | 0.00 | 0.00 | 744.00 | 0.00 | -116219336.1 | 58.99 | 0.00 | 0.00 |
June | 0.284204E+09 | -175563364.9 | 0.00 | 0.00 | 720.00 | 0.00 | -108640800.5 | 59.00 | 0.00 | 0.00 |
July | 0.278229E+09 | -166458136.8 | 0.00 | 0.00 | 744.00 | 0.00 | -111770461.7 | 58.99 | 0.00 | 0.00 |
August | 0.282855E+09 | -170894444.8 | 0.00 | 0.00 | 744.00 | 0.00 | -111960430.5 | 58.99 | 0.00 | 0.00 |
September | 0.273054E+09 | -164058334.0 | 0.00 | 0.00 | 720.00 | 0.00 | -108995962.5 | 58.99 | 0.00 | 0.00 |
October | 0.294161E+09 | -176113781.0 | 0.00 | 0.00 | 744.00 | 0.00 | -118047250.3 | 58.99 | 0.00 | 0.00 |
November | 0.299588E+09 | -181198373.4 | 0.00 | 0.00 | 720.00 | 0.00 | -118389999.3 | 58.99 | 0.00 | 0.00 |
December | 0.322064E+09 | -196931623.1 | 0.00 | 0.00 | 744.00 | 0.00 | -125131924.8 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.362097E+10 | -0.222289E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.139808E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.273054E+09 | -213279286.8 | 0.00 | 0.00 | 672.00 | 0.00 | -125131924.8 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.336049E+09 | -164058334.0 | 0.00 | 0.00 | 744.00 | 0.00 | -108640800.5 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 276.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 245.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 296.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 296.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 415.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 421.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 430.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 394.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 354.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 262.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 257.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 251.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3902.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 245.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 430.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 HEATING COIL
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.101814E+11 | 58726.78 | 01-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.110881E+11 | 58726.78 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.780585E+10 | 58726.78 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.586167E+10 | 58726.78 | 02-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.315613E+09 | 58726.78 | 01-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 51372762.44 | 10802.47 | 22-SEP-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.390941E+10 | 58726.78 | 23-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.658187E+10 | 58726.78 | 01-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.134738E+11 | 58726.78 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.592691E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.134738E+11 | 58726.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 HEATING COIL
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.266866E+10 | 31153.40 | 03-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.305403E+10 | 31153.40 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.210420E+10 | 31153.40 | 02-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.142428E+10 | 31153.40 | 03-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 35064020.58 | 20143.95 | 03-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3216799.31 | 2051.69 | 22-SEP-08:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.116547E+10 | 31153.40 | 25-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.168964E+10 | 31153.40 | 01-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.401410E+10 | 31153.40 | 07-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.161587E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.401410E+10 | 31153.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3 HEATING COIL
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.343227E+10 | 32228.33 | 01-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.378713E+10 | 32228.33 | 01-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.262927E+10 | 32228.33 | 05-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.186588E+10 | 32228.33 | 02-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 83149471.82 | 21031.43 | 02-MAY-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 7556505.60 | 3677.62 | 22-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.142042E+10 | 32228.33 | 30-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.227033E+10 | 32228.33 | 01-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.479961E+10 | 32228.33 | 08-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.202956E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.479961E+10 | 32228.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4 HEATING COIL
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.362206E+10 | 32091.86 | 01-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.396617E+10 | 32091.86 | 01-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.275902E+10 | 32091.86 | 02-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.199878E+10 | 32091.86 | 02-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.102270E+09 | 26009.22 | 02-MAY-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 8704877.55 | 3146.48 | 22-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.148438E+10 | 32091.86 | 30-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.241759E+10 | 32091.86 | 01-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.498883E+10 | 32091.86 | 08-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.213478E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.498883E+10 | 32091.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5 HEATING COIL
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.390270E+10 | 32036.19 | 01-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.425490E+10 | 32036.19 | 01-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.297808E+10 | 32036.19 | 02-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.221131E+10 | 32036.19 | 02-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.130444E+09 | 30935.02 | 02-MAY-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 11786285.75 | 4993.96 | 22-SEP-07:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.158347E+10 | 32036.19 | 25-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.263198E+10 | 32036.19 | 01-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.528816E+10 | 32036.19 | 07-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.229928E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.528816E+10 | 32036.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6 HEATING COIL
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.798296E+10 | 56507.16 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.863685E+10 | 56507.16 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.607367E+10 | 56507.16 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.456973E+10 | 56507.16 | 02-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.301465E+09 | 56507.16 | 01-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 38812899.81 | 6430.11 | 22-SEP-08:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.323932E+10 | 56507.16 | 23-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.552748E+10 | 56507.16 | 01-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.105856E+11 | 56507.16 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.469559E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.105856E+11 | 56507.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7 HEATING COIL
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.344733E+10 | 28948.09 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.382276E+10 | 28948.09 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.261131E+10 | 28948.09 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.188857E+10 | 28948.09 | 02-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 90132122.76 | 28948.09 | 01-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 4290301.28 | 2428.15 | 22-SEP-08:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.141549E+10 | 28948.09 | 23-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.228623E+10 | 28948.09 | 01-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.481472E+10 | 28948.09 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.203808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.481472E+10 | 28948.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8 HEATING COIL
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.354674E+10 | 28796.84 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.391245E+10 | 28796.84 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.268242E+10 | 28796.84 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.194963E+10 | 28796.84 | 02-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 97551303.70 | 28796.84 | 01-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 4827462.83 | 2296.13 | 22-SEP-08:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.144171E+10 | 28796.84 | 23-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.235033E+10 | 28796.84 | 01-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.489997E+10 | 28796.84 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.208856E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.489997E+10 | 28796.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9 HEATING COIL
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.394605E+10 | 28642.63 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.429913E+10 | 28642.63 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.300095E+10 | 28642.63 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.224136E+10 | 28642.63 | 01-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.131954E+09 | 28642.63 | 01-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 8540253.62 | 3352.28 | 22-SEP-08:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.157361E+10 | 28642.63 | 23-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.262592E+10 | 28642.63 | 01-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.527743E+10 | 28642.63 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.231049E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.527743E+10 | 28642.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10 HEATING COIL
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.623663E+10 | 29687.80 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.665714E+10 | 29687.80 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.496541E+10 | 29687.80 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.393395E+10 | 29687.80 | 01-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.416467E+09 | 29687.80 | 01-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 60858522.67 | 22478.17 | 22-SEP-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.248307E+10 | 29687.80 | 23-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.420553E+10 | 29687.80 | 01-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.776205E+10 | 29687.80 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.367211E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.776205E+10 | 29687.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 7941317.63 | 7941317.63 | 1821.27 | 20-JAN-14:00 | 1821.27 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.308091E+09 | 0.308091E+09 | 8184.49 | 14-MAR-13:00 | 8184.49 | 0.00 |
April | 0.00 | 0.00 | 43393318.56 | 43393318.56 | 3337.58 | 20-APR-13:00 | 3337.58 | 0.00 |
May | 0.00 | 0.00 | 0.230098E+10 | 0.228196E+10 | 11791.70 | 17-MAY-14:00 | 11791.70 | 0.00 |
June | 0.00 | 0.00 | 0.146433E+11 | 0.139730E+11 | 27273.46 | 14-JUN-07:03 | 27273.46 | 0.00 |
July | 0.00 | 0.00 | 0.157846E+11 | 0.148341E+11 | 35291.19 | 18-JUL-07:02 | 35291.19 | 0.00 |
August | 0.00 | 0.00 | 0.150718E+11 | 0.143765E+11 | 27755.38 | 03-AUG-07:03 | 21586.43 | 0.00 |
September | 0.00 | 0.00 | 0.103041E+11 | 0.101774E+11 | 23447.87 | 13-SEP-07:03 | 21353.46 | 0.00 |
October | 0.00 | 0.00 | 0.117193E+10 | 0.117172E+10 | 13797.63 | 11-OCT-14:00 | 13797.63 | 0.00 |
November | 0.00 | 0.00 | 0.181555E+09 | 0.181555E+09 | 6334.42 | 07-NOV-15:00 | 6334.42 | 0.00 |
December | 0.00 | 0.00 | 19325938.96 | 19325938.96 | 2882.16 | 02-DEC-15:00 | 2882.16 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.598370E+11 | 0.573749E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.157846E+11 | 0.148341E+11 | 35291.19 | 35291.19 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 15602869.25 | 15589789.76 | 1972.85 | 20-JAN-14:00 | 1972.85 | 0.00 |
February | 0.00 | 0.00 | 6150512.82 | 6124850.26 | 2597.39 | 26-FEB-18:10 | 2597.39 | 0.00 |
March | 0.00 | 0.00 | 0.256157E+09 | 0.256147E+09 | 19535.15 | 12-MAR-17:08 | 19535.15 | 0.00 |
April | 0.00 | 0.00 | 70070063.43 | 69901741.12 | 2589.10 | 20-APR-13:00 | 2589.10 | 0.00 |
May | 0.00 | 0.00 | 0.174339E+10 | 0.171604E+10 | 19673.30 | 31-MAY-20:55 | 15318.51 | 0.00 |
June | 0.00 | 0.00 | 0.889492E+10 | 0.842228E+10 | 20942.26 | 17-JUN-18:40 | 15796.26 | 0.00 |
July | 0.00 | 0.00 | 0.963369E+10 | 0.894444E+10 | 21587.23 | 29-JUL-18:03 | 13238.39 | 0.00 |
August | 0.00 | 0.00 | 0.926253E+10 | 0.874308E+10 | 21171.02 | 03-AUG-22:34 | 12443.83 | 0.00 |
September | 0.00 | 0.00 | 0.641742E+10 | 0.630888E+10 | 20151.49 | 02-SEP-19:58 | 17444.82 | 0.00 |
October | 0.00 | 0.00 | 0.821856E+09 | 0.820652E+09 | 19535.15 | 07-OCT-18:07 | 19535.15 | 0.00 |
November | 0.00 | 0.00 | 0.162803E+09 | 0.162625E+09 | 4095.43 | 07-NOV-14:40 | 4095.43 | 0.00 |
December | 0.00 | 0.00 | 32938041.88 | 32938041.88 | 2842.37 | 03-DEC-18:20 | 2842.37 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.373175E+11 | 0.354987E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 6150512.82 | 6124850.26 | 1972.85 | 1972.85 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.963369E+10 | 0.894444E+10 | 21587.23 | 19535.15 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3 COOLING COIL
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 8086374.24 | 8086374.24 | 1347.26 | 20-JAN-14:00 | 1347.26 | 0.00 |
February | 0.00 | 0.00 | 2161608.69 | 2161608.69 | 674.13 | 18-FEB-14:00 | 674.13 | 0.00 |
March | 0.00 | 0.00 | 0.203527E+09 | 0.203527E+09 | 5175.98 | 14-MAR-13:00 | 5175.98 | 0.00 |
April | 0.00 | 0.00 | 38285556.59 | 38285556.59 | 2309.00 | 20-APR-13:00 | 2309.00 | 0.00 |
May | 0.00 | 0.00 | 0.132238E+10 | 0.131408E+10 | 6505.05 | 17-MAY-13:00 | 6505.05 | 0.00 |
June | 0.00 | 0.00 | 0.666531E+10 | 0.637195E+10 | 16974.06 | 25-JUN-07:03 | 16974.06 | 0.00 |
July | 0.00 | 0.00 | 0.710824E+10 | 0.669199E+10 | 20335.38 | 18-JUL-06:02 | 20335.38 | 0.00 |
August | 0.00 | 0.00 | 0.677508E+10 | 0.651403E+10 | 15919.61 | 20-AUG-07:03 | 13221.60 | 0.00 |
September | 0.00 | 0.00 | 0.482685E+10 | 0.477874E+10 | 16468.43 | 11-SEP-06:02 | 16468.43 | 0.00 |
October | 0.00 | 0.00 | 0.632585E+09 | 0.632497E+09 | 7370.29 | 11-OCT-14:00 | 7370.29 | 0.00 |
November | 0.00 | 0.00 | 0.112377E+09 | 0.112377E+09 | 3665.48 | 07-NOV-14:00 | 3665.48 | 0.00 |
December | 0.00 | 0.00 | 18339311.68 | 18339311.68 | 2055.35 | 02-DEC-15:00 | 2055.35 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.277132E+11 | 0.266861E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 2161608.69 | 2161608.69 | 674.13 | 674.13 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.710824E+10 | 0.669199E+10 | 20335.38 | 20335.38 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4 COOLING COIL
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 6382276.08 | 6382276.08 | 1165.87 | 20-JAN-14:00 | 1165.87 | 0.00 |
February | 0.00 | 0.00 | 1406983.13 | 1406983.13 | 529.97 | 18-FEB-14:00 | 529.97 | 0.00 |
March | 0.00 | 0.00 | 0.193027E+09 | 0.193027E+09 | 5041.51 | 14-MAR-13:00 | 5041.51 | 0.00 |
April | 0.00 | 0.00 | 30665252.43 | 30665252.43 | 2148.50 | 20-APR-13:00 | 2148.50 | 0.00 |
May | 0.00 | 0.00 | 0.126873E+10 | 0.126146E+10 | 6432.40 | 17-MAY-13:00 | 6432.40 | 0.00 |
June | 0.00 | 0.00 | 0.666637E+10 | 0.637360E+10 | 17422.03 | 25-JUN-07:03 | 17422.03 | 0.00 |
July | 0.00 | 0.00 | 0.712632E+10 | 0.671032E+10 | 20224.11 | 18-JUL-06:02 | 20224.11 | 0.00 |
August | 0.00 | 0.00 | 0.678244E+10 | 0.652041E+10 | 16285.35 | 20-AUG-07:03 | 13541.06 | 0.00 |
September | 0.00 | 0.00 | 0.482100E+10 | 0.477224E+10 | 17309.29 | 11-SEP-06:02 | 17309.29 | 0.00 |
October | 0.00 | 0.00 | 0.610178E+09 | 0.610110E+09 | 7318.78 | 11-OCT-14:00 | 7318.78 | 0.00 |
November | 0.00 | 0.00 | 98679746.63 | 98679746.63 | 3462.37 | 07-NOV-14:00 | 3462.37 | 0.00 |
December | 0.00 | 0.00 | 14929432.87 | 14929432.87 | 1902.03 | 02-DEC-15:00 | 1902.03 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.276201E+11 | 0.265932E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 1406983.13 | 1406983.13 | 529.97 | 529.97 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.712632E+10 | 0.671032E+10 | 20224.11 | 20224.11 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5 COOLING COIL
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 3855842.36 | 3855842.36 | 857.84 | 20-JAN-14:00 | 857.84 | 0.00 |
February | 0.00 | 0.00 | 386874.61 | 386874.61 | 260.63 | 18-FEB-14:00 | 260.63 | 0.00 |
March | 0.00 | 0.00 | 0.173050E+09 | 0.173050E+09 | 4770.78 | 14-MAR-13:00 | 4770.78 | 0.00 |
April | 0.00 | 0.00 | 19070421.45 | 19070421.45 | 1838.58 | 20-APR-13:00 | 1838.58 | 0.00 |
May | 0.00 | 0.00 | 0.115313E+10 | 0.114766E+10 | 6218.46 | 17-MAY-13:00 | 6218.46 | 0.00 |
June | 0.00 | 0.00 | 0.646912E+10 | 0.619067E+10 | 15798.79 | 25-JUN-07:03 | 15798.79 | 0.00 |
July | 0.00 | 0.00 | 0.693031E+10 | 0.653408E+10 | 20067.81 | 17-JUL-06:02 | 20067.81 | 0.00 |
August | 0.00 | 0.00 | 0.659788E+10 | 0.634800E+10 | 15047.29 | 20-AUG-07:03 | 12470.55 | 0.00 |
September | 0.00 | 0.00 | 0.466624E+10 | 0.462036E+10 | 16207.26 | 11-SEP-06:02 | 16207.26 | 0.00 |
October | 0.00 | 0.00 | 0.559303E+09 | 0.559287E+09 | 7157.60 | 11-OCT-14:00 | 7157.60 | 0.00 |
November | 0.00 | 0.00 | 79217187.26 | 79217187.26 | 3162.45 | 07-NOV-14:00 | 3162.45 | 0.00 |
December | 0.00 | 0.00 | 10254718.55 | 10254718.55 | 1623.67 | 02-DEC-15:00 | 1623.67 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.266618E+11 | 0.256859E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 386874.61 | 386874.61 | 260.63 | 260.63 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.693031E+10 | 0.653408E+10 | 20067.81 | 20067.81 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6 COOLING COIL
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 3752462.14 | 3752462.14 | 1141.16 | 20-JAN-14:00 | 1141.16 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.278993E+09 | 0.278993E+09 | 8144.77 | 14-MAR-13:00 | 8144.77 | 0.00 |
April | 0.00 | 0.00 | 22621381.34 | 22621381.34 | 2825.82 | 20-APR-13:00 | 2825.82 | 0.00 |
May | 0.00 | 0.00 | 0.183870E+10 | 0.183004E+10 | 10959.38 | 17-MAY-13:00 | 10959.38 | 0.00 |
June | 0.00 | 0.00 | 0.113918E+11 | 0.108930E+11 | 33382.48 | 25-JUN-08:62 | 33382.48 | 0.00 |
July | 0.00 | 0.00 | 0.121060E+11 | 0.114137E+11 | 35531.89 | 24-JUL-07:03 | 28751.45 | 0.00 |
August | 0.00 | 0.00 | 0.117587E+11 | 0.112924E+11 | 31958.06 | 20-AUG-08:62 | 29511.99 | 0.00 |
September | 0.00 | 0.00 | 0.806596E+10 | 0.798505E+10 | 25896.21 | 11-SEP-07:03 | 25896.21 | 0.00 |
October | 0.00 | 0.00 | 0.944156E+09 | 0.944074E+09 | 12904.04 | 11-OCT-14:10 | 12904.04 | 0.00 |
November | 0.00 | 0.00 | 0.118396E+09 | 0.118396E+09 | 5153.62 | 07-NOV-14:00 | 5153.62 | 0.00 |
December | 0.00 | 0.00 | 12330117.29 | 12330117.29 | 2525.69 | 02-DEC-15:00 | 2525.69 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.465414E+11 | 0.447944E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.121060E+11 | 0.114137E+11 | 35531.89 | 33382.48 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7 COOLING COIL
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 1526489.69 | 1526489.69 | 539.86 | 20-JAN-14:00 | 539.86 | 0.00 |
February | 0.00 | 0.00 | 120.20 | 120.20 | 0.11 | 26-FEB-13:20 | 0.11 | 0.00 |
March | 0.00 | 0.00 | 0.156011E+09 | 0.156011E+09 | 5008.18 | 14-MAR-13:00 | 5008.18 | 0.00 |
April | 0.00 | 0.00 | 12205136.87 | 12205136.87 | 1688.70 | 20-APR-13:00 | 1688.70 | 0.00 |
May | 0.00 | 0.00 | 0.112988E+10 | 0.112823E+10 | 6401.48 | 17-MAY-13:00 | 6401.48 | 0.00 |
June | 0.00 | 0.00 | 0.652107E+10 | 0.630773E+10 | 17255.78 | 25-JUN-08:62 | 17255.78 | 0.00 |
July | 0.00 | 0.00 | 0.691548E+10 | 0.660825E+10 | 18343.13 | 23-JUL-08:62 | 17397.07 | 0.00 |
August | 0.00 | 0.00 | 0.666819E+10 | 0.647982E+10 | 15295.98 | 20-AUG-08:62 | 14262.59 | 0.00 |
September | 0.00 | 0.00 | 0.459187E+10 | 0.457179E+10 | 12528.85 | 11-SEP-07:03 | 12528.85 | 0.00 |
October | 0.00 | 0.00 | 0.506855E+09 | 0.506855E+09 | 7466.10 | 11-OCT-14:10 | 7466.10 | 0.00 |
November | 0.00 | 0.00 | 56288014.93 | 56288014.93 | 3011.10 | 07-NOV-14:00 | 3011.10 | 0.00 |
December | 0.00 | 0.00 | 6670307.75 | 6670307.75 | 1583.65 | 02-DEC-15:00 | 1583.65 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.265660E+11 | 0.258354E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 120.20 | 120.20 | 0.11 | 0.11 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.691548E+10 | 0.660825E+10 | 18343.13 | 17397.07 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8 COOLING COIL
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 1272302.29 | 1272302.29 | 484.70 | 20-JAN-14:00 | 484.70 | 0.00 |
February | 0.00 | 0.00 | 11.01 | 11.01 | 0.02 | 26-FEB-15:00 | 0.02 | 0.00 |
March | 0.00 | 0.00 | 0.149793E+09 | 0.149793E+09 | 4888.83 | 14-MAR-13:00 | 4888.83 | 0.00 |
April | 0.00 | 0.00 | 11102545.80 | 11102545.59 | 1627.54 | 20-APR-13:00 | 1627.54 | 0.00 |
May | 0.00 | 0.00 | 0.109872E+10 | 0.109726E+10 | 6310.15 | 17-MAY-13:00 | 6310.15 | 0.00 |
June | 0.00 | 0.00 | 0.644757E+10 | 0.623750E+10 | 17122.02 | 25-JUN-08:62 | 17122.02 | 0.00 |
July | 0.00 | 0.00 | 0.684396E+10 | 0.654123E+10 | 18210.15 | 23-JUL-08:62 | 17265.58 | 0.00 |
August | 0.00 | 0.00 | 0.660231E+10 | 0.641650E+10 | 14830.68 | 20-AUG-08:62 | 13838.03 | 0.00 |
September | 0.00 | 0.00 | 0.454134E+10 | 0.452163E+10 | 12188.31 | 11-SEP-07:03 | 12188.31 | 0.00 |
October | 0.00 | 0.00 | 0.495920E+09 | 0.495920E+09 | 7387.74 | 11-OCT-14:10 | 7387.74 | 0.00 |
November | 0.00 | 0.00 | 53073492.10 | 53073492.10 | 2937.05 | 07-NOV-14:00 | 2937.05 | 0.00 |
December | 0.00 | 0.00 | 6066182.49 | 6066182.49 | 1526.39 | 02-DEC-15:00 | 1526.39 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.262511E+11 | 0.255314E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 11.01 | 11.01 | 0.02 | 0.02 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.684396E+10 | 0.654123E+10 | 18210.15 | 17265.58 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9 COOLING COIL
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 264231.82 | 264231.82 | 196.49 | 20-JAN-14:00 | 196.49 | 0.00 |
February | 0.00 | 0.00 | 34.24 | 34.24 | 0.03 | 18-FEB-12:20 | 0.03 | 0.00 |
March | 0.00 | 0.00 | 0.127333E+09 | 0.127333E+09 | 4510.66 | 14-MAR-13:00 | 4510.66 | 0.00 |
April | 0.00 | 0.00 | 6679172.99 | 6679172.99 | 1367.49 | 20-APR-13:00 | 1367.49 | 0.00 |
May | 0.00 | 0.00 | 0.986793E+09 | 0.985974E+09 | 6066.30 | 17-MAY-13:00 | 6066.30 | 0.00 |
June | 0.00 | 0.00 | 0.628634E+10 | 0.608439E+10 | 16958.00 | 25-JUN-08:62 | 16958.00 | 0.00 |
July | 0.00 | 0.00 | 0.669213E+10 | 0.640118E+10 | 18070.60 | 23-JUL-08:62 | 17111.94 | 0.00 |
August | 0.00 | 0.00 | 0.647862E+10 | 0.629819E+10 | 13321.85 | 20-AUG-08:62 | 12470.74 | 0.00 |
September | 0.00 | 0.00 | 0.443006E+10 | 0.441119E+10 | 10924.35 | 11-SEP-07:03 | 10924.35 | 0.00 |
October | 0.00 | 0.00 | 0.456489E+09 | 0.456489E+09 | 7214.20 | 11-OCT-14:10 | 7214.20 | 0.00 |
November | 0.00 | 0.00 | 40018007.39 | 40018007.39 | 2635.20 | 07-NOV-14:00 | 2635.20 | 0.00 |
December | 0.00 | 0.00 | 3819436.35 | 3819436.35 | 1306.87 | 02-DEC-15:00 | 1306.87 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.255085E+11 | 0.248155E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 34.24 | 34.24 | 0.03 | 0.03 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.669213E+10 | 0.640118E+10 | 18070.60 | 17111.94 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10 COOLING COIL
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.13 | 0.13 | 0.00 | 20-JAN-13:20 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 84383815.29 | 84383815.29 | 3370.57 | 14-MAR-13:00 | 3370.57 | 0.00 |
April | 0.00 | 0.00 | 2148651.78 | 2148651.78 | 950.30 | 20-APR-13:00 | 950.30 | 0.00 |
May | 0.00 | 0.00 | 0.688652E+09 | 0.686996E+09 | 5287.09 | 17-MAY-13:00 | 5287.09 | 0.00 |
June | 0.00 | 0.00 | 0.580020E+10 | 0.556625E+10 | 17750.20 | 25-JUN-08:62 | 17750.20 | 0.00 |
July | 0.00 | 0.00 | 0.619028E+10 | 0.587410E+10 | 17748.42 | 16-JUL-08:62 | 17748.42 | 0.00 |
August | 0.00 | 0.00 | 0.619202E+10 | 0.595682E+10 | 11261.88 | 16-AUG-14:10 | 11261.88 | 0.00 |
September | 0.00 | 0.00 | 0.418077E+10 | 0.414184E+10 | 9840.43 | 09-SEP-13:00 | 9840.43 | 0.00 |
October | 0.00 | 0.00 | 0.395440E+09 | 0.395438E+09 | 6527.30 | 11-OCT-14:10 | 6527.30 | 0.00 |
November | 0.00 | 0.00 | 27398380.84 | 27398380.84 | 2036.40 | 07-NOV-14:00 | 2036.40 | 0.00 |
December | 0.00 | 0.00 | 1233321.63 | 1233321.63 | 658.17 | 02-DEC-15:00 | 658.17 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.235625E+11 | 0.227366E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.619202E+10 | 0.595682E+10 | 17750.20 | 17750.20 | 0.00 |
Report: FanReportMonthly
For: PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.205673E+10 | 0.49 | 2477.30 | 01-JAN-08:61 | 1.08 |
February | 0.190961E+10 | 0.50 | 2477.30 | 01-FEB-08:61 | 1.08 |
March | 0.200410E+10 | 0.48 | 2477.30 | 01-MAR-08:61 | 1.08 |
April | 0.189023E+10 | 0.47 | 2477.30 | 02-APR-07:01 | 1.08 |
May | 0.180601E+10 | 0.44 | 2477.30 | 01-MAY-07:01 | 1.08 |
June | 0.176858E+10 | 0.45 | 1857.30 | 14-JUN-07:03 | 0.95 |
July | 0.181079E+10 | 0.44 | 2404.38 | 18-JUL-07:02 | 1.06 |
August | 0.181738E+10 | 0.44 | 1682.41 | 03-AUG-07:03 | 0.89 |
September | 0.174825E+10 | 0.44 | 1433.18 | 13-SEP-07:03 | 0.82 |
October | 0.189769E+10 | 0.46 | 2477.30 | 23-OCT-07:01 | 1.08 |
November | 0.190488E+10 | 0.47 | 2477.30 | 01-NOV-07:01 | 1.08 |
December | 0.214836E+10 | 0.51 | 2477.30 | 01-DEC-08:61 | 1.08 |
Annual Sum or Average | 0.227626E+11 | 0.47 | |||
Minimum of Months | 0.174825E+10 | 0.44 | 1433.18 | 0.82 | |
Maximum of Months | 0.214836E+10 | 0.51 | 2477.30 | 1.08 |
Report: FanReportMonthly
For: PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.829124E+09 | 0.39 | 1388.41 | 03-JAN-08:61 | 1.12 |
February | 0.771664E+09 | 0.41 | 1388.41 | 01-FEB-08:61 | 1.12 |
March | 0.869784E+09 | 0.40 | 1388.41 | 02-MAR-08:61 | 1.12 |
April | 0.803682E+09 | 0.40 | 1388.41 | 03-APR-07:01 | 1.12 |
May | 0.941041E+09 | 0.45 | 1094.01 | 03-MAY-07:01 | 1.00 |
June | 0.891735E+09 | 0.44 | 1186.32 | 14-JUN-07:03 | 1.04 |
July | 0.909094E+09 | 0.44 | 1388.41 | 16-JUL-07:02 | 1.12 |
August | 0.905856E+09 | 0.44 | 1069.32 | 03-AUG-07:03 | 0.98 |
September | 0.894016E+09 | 0.44 | 831.20 | 13-SEP-07:03 | 0.86 |
October | 0.912903E+09 | 0.44 | 1388.41 | 25-OCT-07:01 | 1.11 |
November | 0.807782E+09 | 0.41 | 1388.41 | 01-NOV-07:01 | 1.12 |
December | 0.865950E+09 | 0.42 | 1388.41 | 07-DEC-08:61 | 1.12 |
Annual Sum or Average | 0.104026E+11 | 0.42 | |||
Minimum of Months | 0.771664E+09 | 0.39 | 831.20 | 0.86 | |
Maximum of Months | 0.941041E+09 | 0.45 | 1388.41 | 1.12 |
Report: FanReportMonthly
For: PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.933663E+09 | 0.39 | 1452.54 | 01-JAN-08:61 | 1.12 |
February | 0.863776E+09 | 0.40 | 1452.54 | 01-FEB-07:01 | 1.12 |
March | 0.928681E+09 | 0.39 | 1452.54 | 05-MAR-08:61 | 1.12 |
April | 0.866204E+09 | 0.38 | 1452.54 | 02-APR-07:01 | 1.12 |
May | 0.851462E+09 | 0.37 | 1149.75 | 02-MAY-06:02 | 1.01 |
June | 0.833912E+09 | 0.37 | 1180.18 | 25-JUN-07:03 | 1.02 |
July | 0.840277E+09 | 0.36 | 1452.54 | 16-JUL-07:02 | 1.12 |
August | 0.861251E+09 | 0.37 | 1021.67 | 20-AUG-07:03 | 0.94 |
September | 0.816297E+09 | 0.37 | 1114.73 | 11-SEP-06:02 | 0.99 |
October | 0.879258E+09 | 0.38 | 1452.54 | 30-OCT-06:01 | 1.12 |
November | 0.877142E+09 | 0.38 | 1452.54 | 01-NOV-06:01 | 1.12 |
December | 0.966455E+09 | 0.40 | 1452.54 | 08-DEC-07:01 | 1.12 |
Annual Sum or Average | 0.105184E+11 | 0.38 | |||
Minimum of Months | 0.816297E+09 | 0.36 | 1021.67 | 0.94 | |
Maximum of Months | 0.966455E+09 | 0.40 | 1452.54 | 1.12 |
Report: FanReportMonthly
For: PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.933947E+09 | 0.39 | 1444.40 | 01-JAN-08:61 | 1.12 |
February | 0.864202E+09 | 0.40 | 1444.40 | 01-FEB-07:01 | 1.12 |
March | 0.927280E+09 | 0.39 | 1444.40 | 02-MAR-07:02 | 1.12 |
April | 0.865151E+09 | 0.38 | 1444.40 | 02-APR-07:01 | 1.12 |
May | 0.847215E+09 | 0.37 | 1280.14 | 02-MAY-06:02 | 1.06 |
June | 0.829766E+09 | 0.37 | 1219.51 | 25-JUN-07:03 | 1.04 |
July | 0.836082E+09 | 0.36 | 1444.40 | 16-JUL-07:02 | 1.12 |
August | 0.856727E+09 | 0.37 | 1053.10 | 20-AUG-07:03 | 0.95 |
September | 0.811843E+09 | 0.37 | 1187.90 | 11-SEP-06:02 | 1.02 |
October | 0.876219E+09 | 0.38 | 1444.40 | 30-OCT-06:01 | 1.12 |
November | 0.876461E+09 | 0.39 | 1444.40 | 01-NOV-06:01 | 1.12 |
December | 0.966697E+09 | 0.40 | 1444.40 | 08-DEC-07:01 | 1.12 |
Annual Sum or Average | 0.104916E+11 | 0.38 | |||
Minimum of Months | 0.811843E+09 | 0.36 | 1053.10 | 0.95 | |
Maximum of Months | 0.966697E+09 | 0.40 | 1444.40 | 1.12 |
Report: FanReportMonthly
For: PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.939543E+09 | 0.39 | 1441.08 | 01-JAN-08:61 | 1.12 |
February | 0.870193E+09 | 0.40 | 1441.08 | 01-FEB-07:01 | 1.12 |
March | 0.931189E+09 | 0.40 | 1441.08 | 02-MAR-07:02 | 1.12 |
April | 0.868992E+09 | 0.38 | 1441.08 | 02-APR-07:01 | 1.12 |
May | 0.846032E+09 | 0.37 | 1411.36 | 02-MAY-06:02 | 1.11 |
June | 0.827009E+09 | 0.37 | 1083.25 | 25-JUN-07:03 | 0.98 |
July | 0.833392E+09 | 0.36 | 1441.08 | 16-JUL-07:02 | 1.12 |
August | 0.854107E+09 | 0.37 | 952.65 | 20-AUG-07:03 | 0.91 |
September | 0.809906E+09 | 0.37 | 1094.76 | 11-SEP-06:02 | 0.98 |
October | 0.876948E+09 | 0.38 | 1441.08 | 25-OCT-06:02 | 1.12 |
November | 0.880345E+09 | 0.39 | 1441.08 | 01-NOV-06:01 | 1.12 |
December | 0.972786E+09 | 0.40 | 1441.08 | 07-DEC-07:02 | 1.12 |
Annual Sum or Average | 0.105104E+11 | 0.38 | |||
Minimum of Months | 0.809906E+09 | 0.36 | 952.65 | 0.91 | |
Maximum of Months | 0.972786E+09 | 0.40 | 1441.08 | 1.12 |
Report: FanReportMonthly
For: PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.145425E+10 | 0.36 | 2349.35 | 01-JAN-09:01 | 1.08 |
February | 0.135216E+10 | 0.37 | 2349.35 | 01-FEB-08:61 | 1.08 |
March | 0.143369E+10 | 0.36 | 2349.35 | 01-MAR-08:61 | 1.08 |
April | 0.133190E+10 | 0.35 | 2349.35 | 02-APR-08:61 | 1.08 |
May | 0.127617E+10 | 0.33 | 2349.35 | 01-MAY-07:01 | 1.08 |
June | 0.125642E+10 | 0.33 | 2349.35 | 25-JUN-08:62 | 1.08 |
July | 0.126216E+10 | 0.32 | 2349.35 | 16-JUL-08:62 | 1.08 |
August | 0.129564E+10 | 0.33 | 2085.88 | 20-AUG-08:62 | 1.02 |
September | 0.122080E+10 | 0.33 | 1666.11 | 11-SEP-07:03 | 0.92 |
October | 0.133592E+10 | 0.34 | 2349.35 | 23-OCT-07:01 | 1.08 |
November | 0.135579E+10 | 0.35 | 2349.35 | 01-NOV-07:01 | 1.08 |
December | 0.151241E+10 | 0.37 | 2349.35 | 01-DEC-08:61 | 1.08 |
Annual Sum or Average | 0.160873E+11 | 0.34 | |||
Minimum of Months | 0.122080E+10 | 0.32 | 1666.11 | 0.92 | |
Maximum of Months | 0.151241E+10 | 0.37 | 2349.35 | 1.08 |
Report: FanReportMonthly
For: PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.167863E+10 | 0.56 | 1256.84 | 01-JAN-15:30 | 1.12 |
February | 0.152027E+10 | 0.56 | 1256.84 | 01-FEB-08:05 | 1.12 |
March | 0.171483E+10 | 0.57 | 1256.84 | 01-MAR-13:00 | 1.12 |
April | 0.162886E+10 | 0.56 | 1256.84 | 01-APR-09:20 | 1.12 |
May | 0.169673E+10 | 0.56 | 1256.84 | 02-MAY-09:13 | 1.12 |
June | 0.165601E+10 | 0.57 | 1256.84 | 02-JUN-09:50 | 1.11 |
July | 0.166958E+10 | 0.55 | 1256.84 | 01-JUL-13:00 | 1.12 |
August | 0.171483E+10 | 0.57 | 1256.84 | 01-AUG-07:30 | 1.11 |
September | 0.162886E+10 | 0.56 | 1256.84 | 01-SEP-13:30 | 1.11 |
October | 0.167863E+10 | 0.56 | 1256.84 | 08-OCT-12:20 | 1.12 |
November | 0.162886E+10 | 0.56 | 1256.84 | 01-NOV-09:50 | 1.12 |
December | 0.166958E+10 | 0.56 | 1256.84 | 02-DEC-13:20 | 1.12 |
Annual Sum or Average | 0.198857E+11 | 0.56 | |||
Minimum of Months | 0.152027E+10 | 0.55 | 1256.84 | 1.11 | |
Maximum of Months | 0.171483E+10 | 0.57 | 1256.84 | 1.12 |
Report: FanReportMonthly
For: PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.166658E+10 | 0.56 | 1247.81 | 02-JAN-17:40 | 1.12 |
February | 0.150935E+10 | 0.56 | 1247.81 | 01-FEB-13:40 | 1.12 |
March | 0.170252E+10 | 0.57 | 1247.81 | 01-MAR-13:30 | 1.12 |
April | 0.161717E+10 | 0.56 | 1247.81 | 01-APR-13:20 | 1.12 |
May | 0.168455E+10 | 0.56 | 1247.81 | 02-MAY-10:10 | 1.12 |
June | 0.164412E+10 | 0.57 | 1247.81 | 01-JUN-11:30 | 1.11 |
July | 0.165759E+10 | 0.55 | 1247.81 | 03-JUL-19:20 | 1.12 |
August | 0.170252E+10 | 0.57 | 1247.81 | 01-AUG-14:30 | 1.12 |
September | 0.161717E+10 | 0.56 | 1247.81 | 01-SEP-18:10 | 1.11 |
October | 0.166658E+10 | 0.56 | 1247.81 | 01-OCT-09:00 | 1.11 |
November | 0.161717E+10 | 0.56 | 1247.81 | 01-NOV-10:10 | 1.12 |
December | 0.165759E+10 | 0.56 | 1247.81 | 01-DEC-09:00 | 1.12 |
Annual Sum or Average | 0.197429E+11 | 0.56 | |||
Minimum of Months | 0.150935E+10 | 0.55 | 1247.81 | 1.11 | |
Maximum of Months | 0.170252E+10 | 0.57 | 1247.81 | 1.12 |
Report: FanReportMonthly
For: PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.165429E+10 | 0.56 | 1238.61 | 01-JAN-15:50 | 1.12 |
February | 0.149823E+10 | 0.56 | 1238.61 | 01-FEB-17:10 | 1.12 |
March | 0.168996E+10 | 0.57 | 1238.61 | 01-MAR-09:00 | 1.12 |
April | 0.160524E+10 | 0.56 | 1238.61 | 01-APR-08:30 | 1.12 |
May | 0.167213E+10 | 0.56 | 1238.61 | 01-MAY-10:10 | 1.12 |
June | 0.163200E+10 | 0.57 | 1238.61 | 01-JUN-19:03 | 1.11 |
July | 0.164537E+10 | 0.55 | 1238.61 | 03-JUL-17:00 | 1.12 |
August | 0.168996E+10 | 0.57 | 1238.61 | 04-AUG-09:30 | 1.10 |
September | 0.160524E+10 | 0.56 | 1238.61 | 04-SEP-13:00 | 1.11 |
October | 0.165429E+10 | 0.56 | 1238.61 | 02-OCT-14:00 | 1.11 |
November | 0.160524E+10 | 0.56 | 1238.61 | 01-NOV-09:40 | 1.12 |
December | 0.164556E+10 | 0.56 | 1238.61 | 01-DEC-09:10 | 1.12 |
Annual Sum or Average | 0.195975E+11 | 0.56 | |||
Minimum of Months | 0.149823E+10 | 0.55 | 1238.61 | 1.10 | |
Maximum of Months | 0.168996E+10 | 0.57 | 1238.61 | 1.12 |
Report: FanReportMonthly
For: PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.859748E+09 | 0.39 | 1300.93 | 01-JAN-09:01 | 1.12 |
February | 0.808311E+09 | 0.44 | 1300.93 | 01-FEB-08:61 | 1.12 |
March | 0.841837E+09 | 0.39 | 1300.93 | 01-MAR-08:61 | 1.12 |
April | 0.778443E+09 | 0.38 | 1300.93 | 01-APR-07:01 | 1.12 |
May | 0.713454E+09 | 0.34 | 1300.93 | 01-MAY-07:01 | 1.12 |
June | 0.695986E+09 | 0.35 | 1288.03 | 25-JUN-08:62 | 1.11 |
July | 0.700079E+09 | 0.34 | 1300.93 | 16-JUL-08:62 | 1.12 |
August | 0.718630E+09 | 0.35 | 799.56 | 16-AUG-14:10 | 0.88 |
September | 0.677366E+09 | 0.34 | 1111.38 | 22-SEP-07:02 | 1.04 |
October | 0.760296E+09 | 0.36 | 1300.93 | 23-OCT-07:01 | 1.12 |
November | 0.785222E+09 | 0.38 | 1300.93 | 01-NOV-07:01 | 1.12 |
December | 0.900814E+09 | 0.44 | 1300.93 | 01-DEC-08:61 | 1.12 |
Annual Sum or Average | 0.924019E+10 | 0.37 | |||
Minimum of Months | 0.677366E+09 | 0.34 | 799.56 | 0.88 | |
Maximum of Months | 0.900814E+09 | 0.44 | 1300.93 | 1.12 |
Report: ZoneTemperatureOscillationReportMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.205892E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.190961E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.208508E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.190218E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.242185E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.569527E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.601606E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.578295E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.441753E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.219727E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.195333E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.215369E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.385937E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.190218E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.601606E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.833341E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.773349E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.935561E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.822723E+09 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.139135E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.321193E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.340850E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.327318E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.251204E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.112016E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.850558E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.874869E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.200076E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.773349E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.340850E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_3:3
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.935876E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.864378E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.981748E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.876691E+09 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.120483E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.264180E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.275169E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.266377E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.207795E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.104192E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.907065E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.971472E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.179192E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.864378E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.275169E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_4:4
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.935701E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.864595E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.977736E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.873578E+09 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.118702E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.263656E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.275021E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.265944E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.207101E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.103315E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.902840E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.970790E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.178626E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.864595E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.275021E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_5:5
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.940612E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.870302E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.976714E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.874264E+09 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.115682E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.258732E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.270185E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.261426E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.203324E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.102110E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.901642E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.975613E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.176537E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.870302E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.270185E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_6:6
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.145530E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.135216E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.150708E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.133818E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.177192E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.434278E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.450580E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.441393E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.332198E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.157780E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.138766E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.151582E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.284904E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.133818E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.450580E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_7:7
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.167900E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.152027E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.175043E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.163181E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.195987E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.319588E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.328485E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.325704E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.266933E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.179091E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.164203E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.167119E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.260526E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.152027E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.328485E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_8:8
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.166689E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.150935E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.173677E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.161985E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.194081E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.316757E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.325688E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.323004E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.264655E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.177651E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.162959E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.165905E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.258399E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.150935E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.325688E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_9:9
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.165435E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.149823E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.171934E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.160687E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.190387E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.312107E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.321250E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.319107E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.261116E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.175579E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.161465E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.164648E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.255354E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.149823E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.321250E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_10:10
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.859748E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.808311E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.864719E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.779043E+09 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.903045E+09 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.227887E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.236896E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.236251E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.176792E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.862430E+09 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.792683E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.901161E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.155494E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.779043E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.236896E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.205673E+10 | 7941317.63 | 0.101814E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.190961E+10 | 0.00 | 0.110881E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.200410E+10 | 0.308091E+09 | 0.780585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.189023E+10 | 43393318.56 | 0.586167E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.180601E+10 | 0.230098E+10 | 0.315613E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.176858E+10 | 0.146433E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.181079E+10 | 0.157846E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.181738E+10 | 0.150718E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.174825E+10 | 0.103041E+11 | 51372762.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.189769E+10 | 0.117193E+10 | 0.390941E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.190488E+10 | 0.181555E+09 | 0.658187E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.214836E+10 | 19325938.96 | 0.134738E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.227626E+11 | 0.598370E+11 | 0.592691E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.174825E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.214836E+10 | 0.157846E+11 | 0.134738E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.829124E+09 | 15602869.25 | 0.266866E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.771664E+09 | 6150512.82 | 0.305403E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.869784E+09 | 0.253500E+09 | 0.210420E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.803682E+09 | 70070063.43 | 0.142428E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.941041E+09 | 0.168965E+10 | 35064020.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.891735E+09 | 0.851497E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.909094E+09 | 0.924587E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.905856E+09 | 0.882716E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.894016E+09 | 0.612949E+10 | 3216799.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.912903E+09 | 0.810242E+09 | 0.116547E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.807782E+09 | 0.162803E+09 | 0.168964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.865950E+09 | 32938041.88 | 0.401410E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.104026E+11 | 0.357584E+11 | 0.161587E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.771664E+09 | 6150512.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.941041E+09 | 0.924587E+10 | 0.401410E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_3:3
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.933663E+09 | 8086374.24 | 0.343227E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.863776E+09 | 2161608.69 | 0.378713E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.928681E+09 | 0.203527E+09 | 0.262927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.866204E+09 | 38285556.59 | 0.186588E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.851462E+09 | 0.132238E+10 | 83149471.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.833912E+09 | 0.666531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.840277E+09 | 0.710824E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.861251E+09 | 0.677508E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.816297E+09 | 0.482685E+10 | 7556505.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.879258E+09 | 0.632585E+09 | 0.142042E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.877142E+09 | 0.112377E+09 | 0.227033E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.966455E+09 | 18339311.68 | 0.479961E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.105184E+11 | 0.277132E+11 | 0.202956E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.816297E+09 | 2161608.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.966455E+09 | 0.710824E+10 | 0.479961E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_4:4
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.933947E+09 | 6382276.08 | 0.362206E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.864202E+09 | 1406983.13 | 0.396617E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.927280E+09 | 0.193027E+09 | 0.275902E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.865151E+09 | 30665252.43 | 0.199878E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.847215E+09 | 0.126873E+10 | 0.102270E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.829766E+09 | 0.666637E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.836082E+09 | 0.712632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.856727E+09 | 0.678244E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.811843E+09 | 0.482100E+10 | 8704877.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.876219E+09 | 0.610178E+09 | 0.148438E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.876461E+09 | 98679746.63 | 0.241759E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.966697E+09 | 14929432.87 | 0.498883E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.104916E+11 | 0.276201E+11 | 0.213478E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.811843E+09 | 1406983.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.966697E+09 | 0.712632E+10 | 0.498883E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_5:5
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.939543E+09 | 3855842.36 | 0.390270E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.870193E+09 | 386874.61 | 0.425490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.931189E+09 | 0.173050E+09 | 0.297808E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.868992E+09 | 19070421.45 | 0.221131E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.846032E+09 | 0.115313E+10 | 0.130444E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.827009E+09 | 0.646912E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.833392E+09 | 0.693031E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.854107E+09 | 0.659788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.809906E+09 | 0.466624E+10 | 11786285.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.876948E+09 | 0.559303E+09 | 0.158347E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.880345E+09 | 79217187.26 | 0.263198E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.972786E+09 | 10254718.55 | 0.528816E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.105104E+11 | 0.266618E+11 | 0.229928E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.809906E+09 | 386874.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.972786E+09 | 0.693031E+10 | 0.528816E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_6:6
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.145425E+10 | 3752462.14 | 0.798296E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.135216E+10 | 0.00 | 0.863685E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.143369E+10 | 0.278993E+09 | 0.607367E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.133190E+10 | 22621381.34 | 0.456973E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.127617E+10 | 0.183870E+10 | 0.301465E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.125642E+10 | 0.113918E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.126216E+10 | 0.121060E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.129564E+10 | 0.117587E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.122080E+10 | 0.806596E+10 | 38812899.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.133592E+10 | 0.944156E+09 | 0.323932E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.135579E+10 | 0.118396E+09 | 0.552748E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.151241E+10 | 12330117.29 | 0.105856E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160873E+11 | 0.465414E+11 | 0.469559E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.122080E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.151241E+10 | 0.121060E+11 | 0.105856E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_7:7
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.167863E+10 | 1526489.69 | 0.344733E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.152027E+10 | 120.20 | 0.382276E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.171483E+10 | 0.156011E+09 | 0.261131E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.162886E+10 | 12205136.87 | 0.188857E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.169673E+10 | 0.112988E+10 | 90132122.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.165601E+10 | 0.652107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.166958E+10 | 0.691548E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.171483E+10 | 0.666819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.162886E+10 | 0.459187E+10 | 4290301.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.167863E+10 | 0.506855E+09 | 0.141549E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.162886E+10 | 56288014.93 | 0.228623E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.166958E+10 | 6670307.75 | 0.481472E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.198857E+11 | 0.265660E+11 | 0.203808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.152027E+10 | 120.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.171483E+10 | 0.691548E+10 | 0.481472E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_8:8
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.166658E+10 | 1272302.29 | 0.354674E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.150935E+10 | 11.01 | 0.391245E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.170252E+10 | 0.149793E+09 | 0.268242E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.161717E+10 | 11102545.80 | 0.194963E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.168455E+10 | 0.109872E+10 | 97551303.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.164412E+10 | 0.644757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.165759E+10 | 0.684396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.170252E+10 | 0.660231E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.161717E+10 | 0.454134E+10 | 4827462.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.166658E+10 | 0.495920E+09 | 0.144171E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.161717E+10 | 53073492.10 | 0.235033E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.165759E+10 | 6066182.49 | 0.489997E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.197429E+11 | 0.262511E+11 | 0.208856E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.150935E+10 | 11.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.170252E+10 | 0.684396E+10 | 0.489997E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_9:9
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.165429E+10 | 264231.82 | 0.394605E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.149823E+10 | 34.24 | 0.429913E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.168996E+10 | 0.127333E+09 | 0.300095E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.160524E+10 | 6679172.99 | 0.224136E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.167213E+10 | 0.986793E+09 | 0.131954E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.163200E+10 | 0.628634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.164537E+10 | 0.669213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.168996E+10 | 0.647862E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.160524E+10 | 0.443006E+10 | 8540253.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.165429E+10 | 0.456489E+09 | 0.157361E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.160524E+10 | 40018007.39 | 0.262592E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.164556E+10 | 3819436.35 | 0.527743E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.195975E+11 | 0.255085E+11 | 0.231049E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.149823E+10 | 34.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.168996E+10 | 0.669213E+10 | 0.527743E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_10:10
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.859748E+09 | 0.13 | 0.623663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.808311E+09 | 0.00 | 0.665714E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.841837E+09 | 84383815.29 | 0.496541E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.778443E+09 | 2148651.78 | 0.393395E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.713454E+09 | 0.688652E+09 | 0.416467E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.695986E+09 | 0.580020E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.700079E+09 | 0.619028E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.718630E+09 | 0.619202E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.677366E+09 | 0.418077E+10 | 60858522.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.760296E+09 | 0.395440E+09 | 0.248307E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.785222E+09 | 27398380.84 | 0.420553E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.900814E+09 | 1233321.63 | 0.776205E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.924019E+10 | 0.235625E+11 | 0.367211E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.677366E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.900814E+09 | 0.619202E+10 | 0.776205E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.205673E+10 | 0.00 | 0.00 | 0.00 | 2191850.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.190961E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.200410E+10 | 0.00 | 0.00 | 0.00 | 80979451.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.189023E+10 | 0.00 | 0.00 | 0.00 | 11955397.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.180601E+10 | 0.00 | 0.00 | 0.00 | 0.615834E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.176858E+10 | 0.00 | 0.00 | 0.00 | 0.392669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.181079E+10 | 0.00 | 0.00 | 0.00 | 0.420528E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.181738E+10 | 0.00 | 0.00 | 0.00 | 0.396557E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.174825E+10 | 0.00 | 0.00 | 0.00 | 0.266928E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.189769E+10 | 0.00 | 0.00 | 0.00 | 0.299577E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.190488E+10 | 0.00 | 0.00 | 0.00 | 48450806.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.214836E+10 | 0.00 | 0.00 | 0.00 | 5337598.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.227626E+11 | 0.00 | 0.00 | 0.00 | 0.158311E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.174825E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.214836E+10 | 0.00 | 0.00 | 0.00 | 0.420528E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.829124E+09 | 0.00 | 0.00 | 0.00 | 4217092.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.771664E+09 | 0.00 | 0.00 | 0.00 | 1685508.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.869784E+09 | 0.00 | 0.00 | 0.00 | 65777083.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.803682E+09 | 0.00 | 0.00 | 0.00 | 19040989.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.941041E+09 | 0.00 | 0.00 | 0.00 | 0.450312E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.891735E+09 | 0.00 | 0.00 | 0.00 | 0.232019E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.909094E+09 | 0.00 | 0.00 | 0.00 | 0.249940E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.905856E+09 | 0.00 | 0.00 | 0.00 | 0.236732E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.894016E+09 | 0.00 | 0.00 | 0.00 | 0.161802E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.912903E+09 | 0.00 | 0.00 | 0.00 | 0.207254E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.807782E+09 | 0.00 | 0.00 | 0.00 | 42776065.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.865950E+09 | 0.00 | 0.00 | 0.00 | 8918780.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.104026E+11 | 0.00 | 0.00 | 0.00 | 0.960493E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.771664E+09 | 0.00 | 0.00 | 0.00 | 1685508.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.941041E+09 | 0.00 | 0.00 | 0.00 | 0.249940E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_3:3
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.933663E+09 | 0.00 | 0.00 | 0.00 | 2213312.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.863776E+09 | 0.00 | 0.00 | 0.00 | 601515.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.928681E+09 | 0.00 | 0.00 | 0.00 | 53067289.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.866204E+09 | 0.00 | 0.00 | 0.00 | 10486405.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.851462E+09 | 0.00 | 0.00 | 0.00 | 0.353368E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.833912E+09 | 0.00 | 0.00 | 0.00 | 0.180789E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.840277E+09 | 0.00 | 0.00 | 0.00 | 0.191141E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.861251E+09 | 0.00 | 0.00 | 0.00 | 0.180252E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.816297E+09 | 0.00 | 0.00 | 0.00 | 0.126165E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.879258E+09 | 0.00 | 0.00 | 0.00 | 0.162667E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.877142E+09 | 0.00 | 0.00 | 0.00 | 29923016.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.966455E+09 | 0.00 | 0.00 | 0.00 | 5016431.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.105184E+11 | 0.00 | 0.00 | 0.00 | 0.740082E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.816297E+09 | 0.00 | 0.00 | 0.00 | 601515.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.966455E+09 | 0.00 | 0.00 | 0.00 | 0.191141E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_4:4
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.933947E+09 | 0.00 | 0.00 | 0.00 | 1754285.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.864202E+09 | 0.00 | 0.00 | 0.00 | 392870.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.927280E+09 | 0.00 | 0.00 | 0.00 | 50455946.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.865151E+09 | 0.00 | 0.00 | 0.00 | 8426601.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.847215E+09 | 0.00 | 0.00 | 0.00 | 0.339809E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.829766E+09 | 0.00 | 0.00 | 0.00 | 0.180679E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.836082E+09 | 0.00 | 0.00 | 0.00 | 0.191413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.856727E+09 | 0.00 | 0.00 | 0.00 | 0.180271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.811843E+09 | 0.00 | 0.00 | 0.00 | 0.125916E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.876219E+09 | 0.00 | 0.00 | 0.00 | 0.156930E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.876461E+09 | 0.00 | 0.00 | 0.00 | 26378643.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.966697E+09 | 0.00 | 0.00 | 0.00 | 4092869.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.104916E+11 | 0.00 | 0.00 | 0.00 | 0.737105E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.811843E+09 | 0.00 | 0.00 | 0.00 | 392870.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.966697E+09 | 0.00 | 0.00 | 0.00 | 0.191413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_5:5
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.939543E+09 | 0.00 | 0.00 | 0.00 | 1068290.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.870193E+09 | 0.00 | 0.00 | 0.00 | 108653.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.931189E+09 | 0.00 | 0.00 | 0.00 | 45524702.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.868992E+09 | 0.00 | 0.00 | 0.00 | 5271937.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.846032E+09 | 0.00 | 0.00 | 0.00 | 0.310786E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.827009E+09 | 0.00 | 0.00 | 0.00 | 0.176031E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.833392E+09 | 0.00 | 0.00 | 0.00 | 0.186846E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.854107E+09 | 0.00 | 0.00 | 0.00 | 0.176015E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.809906E+09 | 0.00 | 0.00 | 0.00 | 0.122333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.876948E+09 | 0.00 | 0.00 | 0.00 | 0.144150E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.880345E+09 | 0.00 | 0.00 | 0.00 | 21296543.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.972786E+09 | 0.00 | 0.00 | 0.00 | 2826545.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.105104E+11 | 0.00 | 0.00 | 0.00 | 0.714330E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.809906E+09 | 0.00 | 0.00 | 0.00 | 108653.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.972786E+09 | 0.00 | 0.00 | 0.00 | 0.186846E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_6:6
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.145425E+10 | 0.00 | 0.00 | 0.00 | 1042038.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.135216E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.143369E+10 | 0.00 | 0.00 | 0.00 | 73387220.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.133190E+10 | 0.00 | 0.00 | 0.00 | 6285065.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.127617E+10 | 0.00 | 0.00 | 0.00 | 0.495754E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.125642E+10 | 0.00 | 0.00 | 0.00 | 0.308636E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.126216E+10 | 0.00 | 0.00 | 0.00 | 0.324363E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.129564E+10 | 0.00 | 0.00 | 0.00 | 0.311829E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.122080E+10 | 0.00 | 0.00 | 0.00 | 0.210118E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.133592E+10 | 0.00 | 0.00 | 0.00 | 0.241879E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.135579E+10 | 0.00 | 0.00 | 0.00 | 31870990.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.151241E+10 | 0.00 | 0.00 | 0.00 | 3404695.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160873E+11 | 0.00 | 0.00 | 0.00 | 0.124031E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.122080E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.151241E+10 | 0.00 | 0.00 | 0.00 | 0.324363E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_7:7
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.167863E+10 | 0.00 | 0.00 | 0.00 | 370856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.152027E+10 | 0.00 | 0.00 | 0.00 | 29.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.171483E+10 | 0.00 | 0.00 | 0.00 | 35603308.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.162886E+10 | 0.00 | 0.00 | 0.00 | 2950719.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.169673E+10 | 0.00 | 0.00 | 0.00 | 0.263140E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.165601E+10 | 0.00 | 0.00 | 0.00 | 0.153987E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.166958E+10 | 0.00 | 0.00 | 0.00 | 0.161526E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.171483E+10 | 0.00 | 0.00 | 0.00 | 0.154221E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.162886E+10 | 0.00 | 0.00 | 0.00 | 0.104047E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.167863E+10 | 0.00 | 0.00 | 0.00 | 0.112282E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.162886E+10 | 0.00 | 0.00 | 0.00 | 13168135.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.166958E+10 | 0.00 | 0.00 | 0.00 | 1604847.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.198857E+11 | 0.00 | 0.00 | 0.00 | 0.616693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.152027E+10 | 0.00 | 0.00 | 0.00 | 29.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.171483E+10 | 0.00 | 0.00 | 0.00 | 0.161526E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_8:8
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.166658E+10 | 0.00 | 0.00 | 0.00 | 309593.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.150935E+10 | 0.00 | 0.00 | 0.00 | 2.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.170252E+10 | 0.00 | 0.00 | 0.00 | 34255800.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.161717E+10 | 0.00 | 0.00 | 0.00 | 2686978.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.168455E+10 | 0.00 | 0.00 | 0.00 | 0.256264E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.164412E+10 | 0.00 | 0.00 | 0.00 | 0.152346E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.165759E+10 | 0.00 | 0.00 | 0.00 | 0.159929E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.170252E+10 | 0.00 | 0.00 | 0.00 | 0.152753E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.161717E+10 | 0.00 | 0.00 | 0.00 | 0.102939E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.166658E+10 | 0.00 | 0.00 | 0.00 | 0.109932E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.161717E+10 | 0.00 | 0.00 | 0.00 | 12427826.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.165759E+10 | 0.00 | 0.00 | 0.00 | 1460252.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.197429E+11 | 0.00 | 0.00 | 0.00 | 0.609700E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.150935E+10 | 0.00 | 0.00 | 0.00 | 2.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.170252E+10 | 0.00 | 0.00 | 0.00 | 0.159929E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_9:9
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.165429E+10 | 0.00 | 0.00 | 0.00 | 64779.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.149823E+10 | 0.00 | 0.00 | 0.00 | 8.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.168996E+10 | 0.00 | 0.00 | 0.00 | 29380908.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.160524E+10 | 0.00 | 0.00 | 0.00 | 1625895.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.167213E+10 | 0.00 | 0.00 | 0.00 | 0.231740E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.163200E+10 | 0.00 | 0.00 | 0.00 | 0.148908E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.164537E+10 | 0.00 | 0.00 | 0.00 | 0.156713E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.168996E+10 | 0.00 | 0.00 | 0.00 | 0.150111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.160524E+10 | 0.00 | 0.00 | 0.00 | 0.100592E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.165429E+10 | 0.00 | 0.00 | 0.00 | 0.101504E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.160524E+10 | 0.00 | 0.00 | 0.00 | 9407946.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.164556E+10 | 0.00 | 0.00 | 0.00 | 921885.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.195975E+11 | 0.00 | 0.00 | 0.00 | 0.593788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.149823E+10 | 0.00 | 0.00 | 0.00 | 8.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.168996E+10 | 0.00 | 0.00 | 0.00 | 0.156713E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_10:10
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.859748E+09 | 0.00 | 0.00 | 0.00 | 0.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.808311E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.841837E+09 | 0.00 | 0.00 | 0.00 | 22881995.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.778443E+09 | 0.00 | 0.00 | 0.00 | 600574.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.713454E+09 | 0.00 | 0.00 | 0.00 | 0.189592E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.695986E+09 | 0.00 | 0.00 | 0.00 | 0.158289E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.700079E+09 | 0.00 | 0.00 | 0.00 | 0.166888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.718630E+09 | 0.00 | 0.00 | 0.00 | 0.164388E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.677366E+09 | 0.00 | 0.00 | 0.00 | 0.109056E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.760296E+09 | 0.00 | 0.00 | 0.00 | 0.102134E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.785222E+09 | 0.00 | 0.00 | 0.00 | 7461527.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.900814E+09 | 0.00 | 0.00 | 0.00 | 346775.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.924019E+10 | 0.00 | 0.00 | 0.00 | 0.630922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.677366E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.900814E+09 | 0.00 | 0.00 | 0.00 | 0.166888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.849745E+10 | 0.00 | 0.00 | 164826.64 | 0.00 | 0.528151E+10 | 0.169168E+09 | 0.00 | 0.54 |
February | 0.663813E+10 | 0.00 | 0.00 | 96982.74 | 0.00 | 0.635559E+10 | 0.118458E+09 | 0.00 | 0.53 |
March | 0.572458E+10 | 0.00 | 0.00 | 2038658.02 | 0.00 | 0.462071E+10 | 0.145505E+10 | 0.00 | 0.60 |
April | 0.614598E+10 | 0.00 | 0.00 | 933654.60 | 0.00 | 0.326260E+10 | 0.934872E+09 | 0.00 | 0.58 |
May | 0.315140E+10 | 59047847.94 | 0.00 | 7563356.76 | 0.00 | 95063155.41 | 0.402928E+10 | 0.00 | 0.80 |
June | 45013130.16 | 0.166925E+10 | 0.00 | 13176963.41 | 1506293.26 | 0.00 | 0.272756E+10 | 0.00 | 0.89 |
July | 17623253.04 | 0.191956E+10 | 0.00 | 12933919.29 | 20913.12 | 0.00 | 0.256230E+10 | 0.00 | 0.89 |
August | 8061386.37 | 0.143170E+10 | 0.00 | 17100601.57 | 0.00 | 0.00 | 0.334541E+10 | 0.00 | 0.95 |
September | 0.741599E+09 | 0.540825E+09 | 0.00 | 17792471.34 | 0.00 | 1519154.51 | 0.461780E+10 | 0.00 | 0.99 |
October | 0.505880E+10 | 4036683.16 | 0.00 | 6490451.45 | 0.00 | 0.235252E+10 | 0.412781E+10 | 0.00 | 0.71 |
November | 0.836335E+10 | 0.00 | 0.00 | 1321576.63 | 0.00 | 0.311071E+10 | 0.101896E+10 | 0.00 | 0.58 |
December | 0.731082E+10 | 0.00 | 0.00 | 281140.36 | 0.00 | 0.779972E+10 | 0.281676E+09 | 0.00 | 0.54 |
Annual Sum or Average | 0.517028E+11 | 0.562441E+10 | 0.00 | 79894602.81 | 1527206.38 | 0.328799E+11 | 0.253884E+11 | 0.00 | 0.72 |
Minimum of Months | 8061386.37 | 0.00 | 0.00 | 96982.74 | 0.00 | 0.00 | 0.118458E+09 | 0.00 | 0.53 |
Maximum of Months | 0.849745E+10 | 0.191956E+10 | 0.00 | 17792471.34 | 1506293.26 | 0.779972E+10 | 0.461780E+10 | 0.00 | 0.99 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.345032E+10 | 0.00 | 0.00 | 378026.55 | 0.00 | 0.129366E+10 | 0.351629E+09 | 0.00 | 0.42 |
February | 0.278487E+10 | 0.00 | 0.00 | 277285.23 | 0.00 | 0.171831E+10 | 0.254911E+09 | 0.00 | 0.41 |
March | 0.224104E+10 | 0.00 | 0.00 | 1920351.82 | 0.00 | 0.122306E+10 | 0.128976E+10 | 0.00 | 0.54 |
April | 0.219967E+10 | 0.00 | 0.00 | 1283946.50 | 0.00 | 0.759103E+09 | 0.110218E+10 | 0.00 | 0.51 |
May | 0.692222E+09 | 30339071.27 | 0.00 | 5548928.64 | 0.00 | 4318874.85 | 0.316258E+10 | 0.00 | 0.87 |
June | 2768335.73 | 0.828787E+09 | 0.00 | 5353667.28 | 10399.37 | 0.00 | 0.121461E+10 | 0.00 | 0.80 |
July | 3572425.46 | 0.985236E+09 | 0.00 | 4865315.37 | 0.00 | 0.00 | 0.106331E+10 | 0.00 | 0.77 |
August | 2690359.23 | 0.735784E+09 | 0.00 | 6623418.87 | 0.00 | 0.00 | 0.141975E+10 | 0.00 | 0.83 |
September | 0.202386E+09 | 0.267836E+09 | 0.00 | 8211767.59 | 0.00 | 0.00 | 0.235543E+10 | 0.00 | 0.95 |
October | 0.159243E+10 | 2161154.63 | 0.00 | 4830308.44 | 0.00 | 0.749796E+09 | 0.296721E+10 | 0.00 | 0.70 |
November | 0.322321E+10 | 0.00 | 0.00 | 1336640.68 | 0.00 | 0.743039E+09 | 0.889241E+09 | 0.00 | 0.48 |
December | 0.266095E+10 | 0.00 | 0.00 | 471589.75 | 0.00 | 0.250438E+10 | 0.406055E+09 | 0.00 | 0.42 |
Annual Sum or Average | 0.190561E+11 | 0.285014E+10 | 0.00 | 41101246.72 | 10399.37 | 0.899567E+10 | 0.164767E+11 | 0.00 | 0.64 |
Minimum of Months | 2690359.23 | 0.00 | 0.00 | 277285.23 | 0.00 | 0.00 | 0.254911E+09 | 0.00 | 0.41 |
Maximum of Months | 0.345032E+10 | 0.985236E+09 | 0.00 | 8211767.59 | 10399.37 | 0.250438E+10 | 0.316258E+10 | 0.00 | 0.95 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.302799E+10 | 0.00 | 0.00 | 202673.22 | 0.00 | 0.194545E+10 | 0.199872E+09 | 0.00 | 0.43 |
February | 0.254001E+10 | 0.00 | 0.00 | 97327.41 | 0.00 | 0.221569E+10 | 0.108665E+09 | 0.00 | 0.42 |
March | 0.216599E+10 | 0.00 | 0.00 | 1174761.05 | 0.00 | 0.161012E+10 | 0.774880E+09 | 0.00 | 0.53 |
April | 0.222118E+10 | 0.00 | 0.00 | 647568.61 | 0.00 | 0.103413E+10 | 0.622436E+09 | 0.00 | 0.49 |
May | 0.103289E+10 | 32252897.77 | 0.00 | 2884496.50 | 0.00 | 34573128.88 | 0.166309E+10 | 0.00 | 0.71 |
June | 64648459.20 | 0.797297E+09 | 0.00 | 2304736.22 | 26364139.32 | 0.00 | 0.743477E+09 | 0.00 | 0.69 |
July | 58519684.81 | 0.904451E+09 | 0.00 | 1999686.31 | 36625481.73 | 0.00 | 0.624303E+09 | 0.00 | 0.67 |
August | 56952538.47 | 0.693108E+09 | 0.00 | 2961400.81 | 11674448.63 | 0.00 | 0.109252E+10 | 0.00 | 0.72 |
September | 0.352483E+09 | 0.263483E+09 | 0.00 | 4223166.00 | 6005021.30 | 555027.09 | 0.134147E+10 | 0.00 | 0.79 |
October | 0.183929E+10 | 2631983.64 | 0.00 | 2670052.71 | 0.00 | 0.949685E+09 | 0.167260E+10 | 0.00 | 0.62 |
November | 0.301155E+10 | 0.00 | 0.00 | 771992.86 | 0.00 | 0.118777E+10 | 0.515773E+09 | 0.00 | 0.49 |
December | 0.243463E+10 | 0.00 | 0.00 | 222358.53 | 0.00 | 0.303878E+10 | 0.203500E+09 | 0.00 | 0.44 |
Annual Sum or Average | 0.188061E+11 | 0.269322E+10 | 0.00 | 20160220.24 | 80669090.99 | 0.120168E+11 | 0.956259E+10 | 0.00 | 0.58 |
Minimum of Months | 56952538.47 | 0.00 | 0.00 | 97327.41 | 0.00 | 0.00 | 0.108665E+09 | 0.00 | 0.42 |
Maximum of Months | 0.302799E+10 | 0.904451E+09 | 0.00 | 4223166.00 | 36625481.73 | 0.303878E+10 | 0.167260E+10 | 0.00 | 0.79 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.285211E+10 | 0.00 | 0.00 | 153648.76 | 0.00 | 0.213299E+10 | 0.165072E+09 | 0.00 | 0.43 |
February | 0.243218E+10 | 0.00 | 0.00 | 79602.16 | 0.00 | 0.233792E+10 | 82376128.14 | 0.00 | 0.42 |
March | 0.206904E+10 | 0.00 | 0.00 | 1079178.70 | 0.00 | 0.172539E+10 | 0.717080E+09 | 0.00 | 0.52 |
April | 0.214956E+10 | 0.00 | 0.00 | 545065.87 | 0.00 | 0.115484E+10 | 0.531243E+09 | 0.00 | 0.48 |
May | 0.107344E+10 | 32234051.81 | 0.00 | 2701261.72 | 0.00 | 39856996.61 | 0.156288E+10 | 0.00 | 0.70 |
June | 64561549.76 | 0.797047E+09 | 0.00 | 2303329.18 | 26376534.13 | 0.00 | 0.740114E+09 | 0.00 | 0.68 |
July | 55988788.70 | 0.904255E+09 | 0.00 | 2013776.72 | 36599795.18 | 0.00 | 0.625215E+09 | 0.00 | 0.67 |
August | 56816260.75 | 0.693118E+09 | 0.00 | 2973555.89 | 11695307.30 | 0.00 | 0.108941E+10 | 0.00 | 0.71 |
September | 0.356247E+09 | 0.263518E+09 | 0.00 | 4201580.41 | 6004482.34 | 0.00 | 0.132847E+10 | 0.00 | 0.79 |
October | 0.184780E+10 | 2628727.07 | 0.00 | 2530147.38 | 0.00 | 0.963945E+09 | 0.160249E+10 | 0.00 | 0.61 |
November | 0.292399E+10 | 0.00 | 0.00 | 703907.43 | 0.00 | 0.127351E+10 | 0.486991E+09 | 0.00 | 0.48 |
December | 0.231774E+10 | 0.00 | 0.00 | 185702.63 | 0.00 | 0.316256E+10 | 0.177186E+09 | 0.00 | 0.43 |
Annual Sum or Average | 0.181995E+11 | 0.269280E+10 | 0.00 | 19470756.86 | 80676118.95 | 0.127910E+11 | 0.910852E+10 | 0.00 | 0.58 |
Minimum of Months | 55988788.70 | 0.00 | 0.00 | 79602.16 | 0.00 | 0.00 | 82376128.14 | 0.00 | 0.42 |
Maximum of Months | 0.292399E+10 | 0.904255E+09 | 0.00 | 4201580.41 | 36599795.18 | 0.316256E+10 | 0.160249E+10 | 0.00 | 0.79 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.264172E+10 | 0.00 | 0.00 | 97667.06 | 0.00 | 0.237572E+10 | 0.104493E+09 | 0.00 | 0.43 |
February | 0.224104E+10 | 0.00 | 0.00 | 58323.56 | 0.00 | 0.252817E+10 | 68456177.49 | 0.00 | 0.42 |
March | 0.191983E+10 | 0.00 | 0.00 | 901940.26 | 0.00 | 0.191829E+10 | 0.608044E+09 | 0.00 | 0.51 |
April | 0.202637E+10 | 0.00 | 0.00 | 398326.85 | 0.00 | 0.133732E+10 | 0.406798E+09 | 0.00 | 0.47 |
May | 0.117094E+10 | 32199635.17 | 0.00 | 2320538.88 | 0.00 | 49530767.62 | 0.134796E+10 | 0.00 | 0.68 |
June | 71754412.92 | 0.793600E+09 | 0.00 | 2146588.69 | 26659212.71 | 0.00 | 0.713194E+09 | 0.00 | 0.68 |
July | 59083661.63 | 0.897191E+09 | 0.00 | 1897226.72 | 37029344.28 | 0.00 | 0.612463E+09 | 0.00 | 0.66 |
August | 59575563.02 | 0.689886E+09 | 0.00 | 2803694.72 | 11927260.58 | 0.00 | 0.106276E+10 | 0.00 | 0.71 |
September | 0.367964E+09 | 0.263442E+09 | 0.00 | 3962308.11 | 6153019.39 | 1913470.81 | 0.127760E+10 | 0.00 | 0.78 |
October | 0.185244E+10 | 2627499.76 | 0.00 | 2255709.09 | 0.00 | 0.102429E+10 | 0.145147E+10 | 0.00 | 0.60 |
November | 0.277481E+10 | 0.00 | 0.00 | 597032.64 | 0.00 | 0.142395E+10 | 0.444682E+09 | 0.00 | 0.48 |
December | 0.214260E+10 | 0.00 | 0.00 | 137760.49 | 0.00 | 0.334503E+10 | 0.143231E+09 | 0.00 | 0.43 |
Annual Sum or Average | 0.173281E+11 | 0.267895E+10 | 0.00 | 17577117.09 | 81768836.96 | 0.140042E+11 | 0.824115E+10 | 0.00 | 0.57 |
Minimum of Months | 59083661.63 | 0.00 | 0.00 | 58323.56 | 0.00 | 0.00 | 68456177.49 | 0.00 | 0.42 |
Maximum of Months | 0.277481E+10 | 0.897191E+09 | 0.00 | 3962308.11 | 37029344.28 | 0.334503E+10 | 0.145147E+10 | 0.00 | 0.78 |
Report: MechanicalVentilationLoadsMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.409503E+10 | 0.00 | 0.00 | 133377.57 | 0.00 | 0.525315E+10 | 0.158181E+09 | 0.00 | 0.39 |
February | 0.346534E+10 | 0.00 | 0.00 | 74672.06 | 0.00 | 0.544809E+10 | 98267305.73 | 0.00 | 0.38 |
March | 0.308481E+10 | 0.00 | 0.00 | 1275214.29 | 0.00 | 0.412414E+10 | 0.950260E+09 | 0.00 | 0.44 |
April | 0.340923E+10 | 0.00 | 0.00 | 439115.52 | 0.00 | 0.292944E+10 | 0.558789E+09 | 0.00 | 0.41 |
May | 0.224794E+10 | 28692839.55 | 0.00 | 3575273.05 | 0.00 | 0.104690E+09 | 0.217314E+10 | 0.00 | 0.56 |
June | 36508427.57 | 0.131672E+10 | 0.00 | 3636100.54 | 17848493.17 | 0.00 | 0.113841E+10 | 0.00 | 0.56 |
July | 16469758.48 | 0.146679E+10 | 0.00 | 3360731.45 | 40640254.76 | 0.00 | 0.993137E+09 | 0.00 | 0.55 |
August | 33078621.01 | 0.107657E+10 | 0.00 | 4793340.23 | 4787123.12 | 0.00 | 0.158911E+10 | 0.00 | 0.60 |
September | 0.560815E+09 | 0.355985E+09 | 0.00 | 7505478.15 | 6435355.28 | 0.00 | 0.222806E+10 | 0.00 | 0.65 |
October | 0.325908E+10 | 323688.82 | 0.00 | 3635670.81 | 0.00 | 0.212953E+10 | 0.236376E+10 | 0.00 | 0.51 |
November | 0.482702E+10 | 0.00 | 0.00 | 721826.62 | 0.00 | 0.318416E+10 | 0.589514E+09 | 0.00 | 0.42 |
December | 0.338663E+10 | 0.00 | 0.00 | 173172.18 | 0.00 | 0.686433E+10 | 0.215765E+09 | 0.00 | 0.39 |
Annual Sum or Average | 0.284220E+11 | 0.424508E+10 | 0.00 | 29323972.47 | 69711226.33 | 0.300375E+11 | 0.130564E+11 | 0.00 | 0.49 |
Minimum of Months | 16469758.48 | 0.00 | 0.00 | 74672.06 | 0.00 | 0.00 | 98267305.73 | 0.00 | 0.38 |
Maximum of Months | 0.482702E+10 | 0.146679E+10 | 0.00 | 7505478.15 | 40640254.76 | 0.686433E+10 | 0.236376E+10 | 0.00 | 0.65 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.191480E+10 | 0.00 | 0.00 | 84777.93 | 0.00 | 0.273000E+10 | 0.169573E+09 | 0.00 | 0.40 |
February | 0.163038E+10 | 0.00 | 0.00 | 43987.05 | 0.00 | 0.281337E+10 | 88894056.73 | 0.00 | 0.39 |
March | 0.141760E+10 | 0.00 | 0.00 | 734419.36 | 0.00 | 0.211292E+10 | 0.754550E+09 | 0.00 | 0.50 |
April | 0.159807E+10 | 0.00 | 0.00 | 269709.99 | 0.00 | 0.152213E+10 | 0.501131E+09 | 0.00 | 0.46 |
May | 0.978978E+09 | 15394100.38 | 0.00 | 1981866.12 | 0.00 | 57415507.85 | 0.172142E+10 | 0.00 | 0.75 |
June | 29387553.99 | 0.655813E+09 | 0.00 | 1926903.93 | 9631728.27 | 0.00 | 0.846940E+09 | 0.00 | 0.72 |
July | 17345873.62 | 0.724945E+09 | 0.00 | 1800312.42 | 20245073.13 | 0.00 | 0.743400E+09 | 0.00 | 0.69 |
August | 35596849.81 | 0.539311E+09 | 0.00 | 2561573.34 | 1748727.76 | 0.00 | 0.116336E+10 | 0.00 | 0.78 |
September | 0.255137E+09 | 0.182999E+09 | 0.00 | 3849628.21 | 2738325.65 | 0.00 | 0.162644E+10 | 0.00 | 0.90 |
October | 0.145340E+10 | 255509.35 | 0.00 | 2083602.31 | 0.00 | 0.106172E+10 | 0.182946E+10 | 0.00 | 0.63 |
November | 0.225432E+10 | 0.00 | 0.00 | 464659.65 | 0.00 | 0.167313E+10 | 0.528946E+09 | 0.00 | 0.47 |
December | 0.165561E+10 | 0.00 | 0.00 | 101327.93 | 0.00 | 0.345773E+10 | 0.184261E+09 | 0.00 | 0.41 |
Annual Sum or Average | 0.132406E+11 | 0.211872E+10 | 0.00 | 15902768.23 | 34363854.82 | 0.154284E+11 | 0.101584E+11 | 0.00 | 0.59 |
Minimum of Months | 17345873.62 | 0.00 | 0.00 | 43987.05 | 0.00 | 0.00 | 88894056.73 | 0.00 | 0.39 |
Maximum of Months | 0.225432E+10 | 0.724945E+09 | 0.00 | 3849628.21 | 20245073.13 | 0.345773E+10 | 0.182946E+10 | 0.00 | 0.90 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.184816E+10 | 0.00 | 0.00 | 73844.34 | 0.00 | 0.281111E+10 | 0.145723E+09 | 0.00 | 0.40 |
February | 0.153553E+10 | 0.00 | 0.00 | 39022.59 | 0.00 | 0.290765E+10 | 83439688.64 | 0.00 | 0.39 |
March | 0.138485E+10 | 0.00 | 0.00 | 694080.02 | 0.00 | 0.215880E+10 | 0.719633E+09 | 0.00 | 0.50 |
April | 0.156141E+10 | 0.00 | 0.00 | 250537.67 | 0.00 | 0.156957E+10 | 0.472360E+09 | 0.00 | 0.46 |
May | 0.990464E+09 | 15379094.26 | 0.00 | 1886516.16 | 0.00 | 60465103.54 | 0.166220E+10 | 0.00 | 0.74 |
June | 31088058.75 | 0.654821E+09 | 0.00 | 1883469.72 | 9701217.23 | 0.00 | 0.832897E+09 | 0.00 | 0.72 |
July | 16574171.75 | 0.722955E+09 | 0.00 | 1762709.54 | 20316877.23 | 0.00 | 0.735458E+09 | 0.00 | 0.69 |
August | 37919523.56 | 0.538426E+09 | 0.00 | 2506094.25 | 1770440.53 | 0.00 | 0.114690E+10 | 0.00 | 0.77 |
September | 0.254089E+09 | 0.183015E+09 | 0.00 | 3778857.31 | 2766776.34 | 0.00 | 0.160781E+10 | 0.00 | 0.89 |
October | 0.146300E+10 | 254629.63 | 0.00 | 2018199.68 | 0.00 | 0.107677E+10 | 0.177325E+10 | 0.00 | 0.62 |
November | 0.219212E+10 | 0.00 | 0.00 | 442363.30 | 0.00 | 0.173513E+10 | 0.516220E+09 | 0.00 | 0.46 |
December | 0.159595E+10 | 0.00 | 0.00 | 92288.82 | 0.00 | 0.351607E+10 | 0.176990E+09 | 0.00 | 0.40 |
Annual Sum or Average | 0.129112E+11 | 0.211485E+10 | 0.00 | 15427983.38 | 34555311.33 | 0.158355E+11 | 0.987288E+10 | 0.00 | 0.59 |
Minimum of Months | 16574171.75 | 0.00 | 0.00 | 39022.59 | 0.00 | 0.00 | 83439688.64 | 0.00 | 0.39 |
Maximum of Months | 0.219212E+10 | 0.722955E+09 | 0.00 | 3778857.31 | 20316877.23 | 0.351607E+10 | 0.177325E+10 | 0.00 | 0.89 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.153274E+10 | 0.00 | 0.00 | 42480.24 | 0.00 | 0.314148E+10 | 95622783.36 | 0.00 | 0.39 |
February | 0.128838E+10 | 0.00 | 0.00 | 23823.54 | 0.00 | 0.316629E+10 | 52366905.12 | 0.00 | 0.39 |
March | 0.120936E+10 | 0.00 | 0.00 | 532845.15 | 0.00 | 0.238829E+10 | 0.581724E+09 | 0.00 | 0.48 |
April | 0.134496E+10 | 0.00 | 0.00 | 163356.62 | 0.00 | 0.181229E+10 | 0.371260E+09 | 0.00 | 0.44 |
May | 0.106111E+10 | 15321479.45 | 0.00 | 1475692.98 | 0.00 | 88362061.74 | 0.138552E+10 | 0.00 | 0.69 |
June | 36373408.69 | 0.652469E+09 | 0.00 | 1745285.45 | 9740913.47 | 0.00 | 0.794904E+09 | 0.00 | 0.71 |
July | 20618109.99 | 0.718076E+09 | 0.00 | 1646753.76 | 20366384.61 | 0.00 | 0.710534E+09 | 0.00 | 0.68 |
August | 40444188.39 | 0.537000E+09 | 0.00 | 2364693.18 | 1810549.48 | 0.00 | 0.111186E+10 | 0.00 | 0.76 |
September | 0.272399E+09 | 0.182943E+09 | 0.00 | 3574795.46 | 2815894.35 | 806334.19 | 0.153687E+10 | 0.00 | 0.88 |
October | 0.148588E+10 | 253756.44 | 0.00 | 1712501.97 | 0.00 | 0.116679E+10 | 0.152087E+10 | 0.00 | 0.60 |
November | 0.192941E+10 | 0.00 | 0.00 | 343813.05 | 0.00 | 0.202473E+10 | 0.437929E+09 | 0.00 | 0.45 |
December | 0.132720E+10 | 0.00 | 0.00 | 59763.00 | 0.00 | 0.379833E+10 | 0.131720E+09 | 0.00 | 0.40 |
Annual Sum or Average | 0.115489E+11 | 0.210606E+10 | 0.00 | 13685804.41 | 34733741.91 | 0.175874E+11 | 0.873118E+10 | 0.00 | 0.57 |
Minimum of Months | 20618109.99 | 0.00 | 0.00 | 23823.54 | 0.00 | 0.00 | 52366905.12 | 0.00 | 0.39 |
Maximum of Months | 0.192941E+10 | 0.718076E+09 | 0.00 | 3574795.46 | 20366384.61 | 0.379833E+10 | 0.153687E+10 | 0.00 | 0.88 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.767267E+09 | 0.00 | 0.00 | 9674.97 | 0.00 | 0.388538E+10 | 16383189.10 | 0.00 | 0.38 |
February | 0.493448E+09 | 0.00 | 0.00 | 4118.67 | 0.00 | 0.393245E+10 | 9701605.31 | 0.00 | 0.38 |
March | 0.810581E+09 | 0.00 | 0.00 | 277883.29 | 0.00 | 0.288274E+10 | 0.218391E+09 | 0.00 | 0.43 |
April | 0.916079E+09 | 0.00 | 0.00 | 48889.29 | 0.00 | 0.229475E+10 | 88051840.85 | 0.00 | 0.39 |
May | 0.113447E+10 | 15223315.50 | 0.00 | 878127.58 | 37127.26 | 0.231267E+09 | 0.558758E+09 | 0.00 | 0.50 |
June | 42416955.16 | 0.665526E+09 | 0.00 | 1551563.16 | 9654085.66 | 0.00 | 0.503092E+09 | 0.00 | 0.56 |
July | 29609718.45 | 0.728531E+09 | 0.00 | 1350081.72 | 21198716.93 | 0.00 | 0.440687E+09 | 0.00 | 0.54 |
August | 37797860.49 | 0.555817E+09 | 0.00 | 2111682.74 | 2645603.87 | 0.00 | 0.751190E+09 | 0.00 | 0.60 |
September | 0.293468E+09 | 0.184490E+09 | 0.00 | 3425609.63 | 3479671.93 | 12887954.26 | 0.103651E+10 | 0.00 | 0.66 |
October | 0.141991E+10 | 259459.21 | 0.00 | 1285904.02 | 0.00 | 0.140666E+10 | 0.837798E+09 | 0.00 | 0.48 |
November | 0.130165E+10 | 0.00 | 0.00 | 225610.93 | 0.00 | 0.268620E+10 | 0.212331E+09 | 0.00 | 0.42 |
December | 0.630117E+09 | 0.00 | 0.00 | 16065.73 | 0.00 | 0.449152E+10 | 24890862.77 | 0.00 | 0.38 |
Annual Sum or Average | 0.787681E+10 | 0.214985E+10 | 0.00 | 11185211.73 | 37015205.65 | 0.218238E+11 | 0.469779E+10 | 0.00 | 0.48 |
Minimum of Months | 29609718.45 | 0.00 | 0.00 | 4118.67 | 0.00 | 0.00 | 9701605.31 | 0.00 | 0.38 |
Maximum of Months | 0.141991E+10 | 0.728531E+09 | 0.00 | 3425609.63 | 21198716.93 | 0.449152E+10 | 0.103651E+10 | 0.00 | 0.66 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:37:01
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.232764E+12 | 0.253890E+11 | 0.00 | 0.652843E+11 | 0.123036E+11 |
February | 0.305603E+12 | 0.264246E+11 | 0.00 | 0.614097E+11 | 0.133826E+11 |
March | 0.400513E+12 | 0.233977E+11 | 0.00 | 0.564825E+11 | 0.118242E+11 |
April | 0.431923E+12 | 0.216075E+11 | 0.00 | 0.482164E+11 | 0.731186E+10 |
May | 0.533479E+12 | 0.101716E+11 | 0.00 | 0.334590E+11 | 0.174640E+11 |
June | 0.582493E+12 | -0.210615E+10 | 0.00 | 0.179292E+10 | 0.100630E+12 |
July | 0.539094E+12 | -0.284089E+10 | 0.00 | -723190249.8 | 0.107424E+12 |
August | 0.528832E+12 | -0.132559E+10 | 0.00 | 0.669141E+10 | 0.103221E+12 |
September | 0.388010E+12 | 0.336127E+10 | 0.00 | 0.200607E+11 | 0.711946E+11 |
October | 0.310085E+12 | 0.194905E+11 | 0.00 | 0.549980E+11 | 0.131621E+11 |
November | 0.255680E+12 | 0.231315E+11 | 0.00 | 0.589874E+11 | 0.931969E+10 |
December | 0.177827E+12 | 0.323366E+11 | 0.00 | 0.714278E+11 | 0.166359E+11 |
Annual Sum or Average | 0.468630E+13 | 0.179038E+12 | 0.00 | 0.478087E+12 | 0.483873E+12 |
Minimum of Months | 0.177827E+12 | -0.284089E+10 | 0.00 | -723190249.8 | 0.731186E+10 |
Maximum of Months | 0.582493E+12 | 0.323366E+11 | 0.00 | 0.714278E+11 | 0.107424E+12 |