Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:36
Tabular Output Report in Format: HTML
Building: RetailStripmall
Environment: RUNPERIOD 1 ** Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280
Simulation Timestamp: 2023-10-16 08:36:59
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:59
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1493.79 | 714.62 | 714.62 |
Net Site Energy | 1493.79 | 714.62 | 714.62 |
Total Source Energy | 3247.39 | 1553.54 | 1553.54 |
Net Source Energy | 3247.39 | 1553.54 | 1553.54 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 2090.32 |
Net Conditioned Building Area | 2090.32 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 712.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 63.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 366.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 60.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 128.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 98.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 65.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 781.62 | 712.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 712.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 63.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 366.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 60.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 128.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 98.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 65.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 712.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 63.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 366.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 60.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 128.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 98.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 65.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 204.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 108.42 | 340.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Other | 61.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 373.93 | 340.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 204.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 108.42 | 340.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Other | 61.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 373.93 | 340.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 781.623 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 781.623 | 100.00 |
Total On-Site and Utility Electric Sources | 781.623 | 100.00 |
Total Electricity End Uses | 781.623 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 87.30 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 87.30 | 100.00 |
Total Water End Uses | 87.30 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 5.67 |
Time Setpoint Not Met During Occupied Cooling | 0.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 2652.83 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTRIPMALL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5A
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_BUFFALO
| Environment |ZoneCoolingSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ZoneHeatingSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ZoneElectricSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |SpaceGainsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |PeakSpaceGainsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |SpaceGainComponentsAtCoolingPeakMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ComfortReportSimple55Monthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |OccupantComfortDataSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |DXReportMonthly
| PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL | PSZ-AC_3:3 COOLING COIL | PSZ-AC_4:4 COOLING COIL | PSZ-AC_5:5 COOLING COIL | PSZ-AC_6:6 COOLING COIL | PSZ-AC_7:7 COOLING COIL | PSZ-AC_8:8 COOLING COIL | PSZ-AC_9:9 COOLING COIL | PSZ-AC_10:10 COOLING COIL |WindowReportMonthly
| LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR |WindowEnergyReportMonthly
| LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR |WindowZoneSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |WindowEnergyZoneSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| GAS TANK1 | GAS TANK2 | GAS TANK3 | GAS TANK4 | GAS TANK5 | GAS TANK6 | GAS TANK7 |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC_1:1 HEATING COIL | PSZ-AC_2:2 HEATING COIL | PSZ-AC_3:3 HEATING COIL | PSZ-AC_4:4 HEATING COIL | PSZ-AC_5:5 HEATING COIL | PSZ-AC_6:6 HEATING COIL | PSZ-AC_7:7 HEATING COIL | PSZ-AC_8:8 HEATING COIL | PSZ-AC_9:9 HEATING COIL | PSZ-AC_10:10 HEATING COIL | PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL | PSZ-AC_3:3 COOLING COIL | PSZ-AC_4:4 COOLING COIL | PSZ-AC_5:5 COOLING COIL | PSZ-AC_6:6 COOLING COIL | PSZ-AC_7:7 COOLING COIL | PSZ-AC_8:8 COOLING COIL | PSZ-AC_9:9 COOLING COIL | PSZ-AC_10:10 COOLING COIL |FanReportMonthly
| PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN |ZoneTemperatureOscillationReportMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |MechanicalVentilationLoadsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:59
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:36 |
RunPeriod | RUNPERIOD 1 |
Weather File | Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280 |
Latitude [deg] | 42.93 |
Longitude [deg] | -78.7 |
Elevation [m] | 215.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Above Ground Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Window Opening Area [m2] | 124.40 | 0.00 | 0.00 | 124.40 | 0.00 |
Gross Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Above Ground Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Above Ground Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Window Opening Area [m2] | 124.40 | 0.00 | 0.00 | 124.40 | 0.00 |
Gross Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Above Ground Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Total | |
Gross Roof Area [m2] | 2090.32 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
LGSTORE1 | 348.39 | Yes | Yes | 1805.20 | 1.00 | 276.30 | 0.00 | 20.77 | 20.77 | 15.3022 | 6.19 | 4.3000 |
SMSTORE1 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.38 | 10.38 | 18.2890 | 6.19 | 4.3000 |
SMSTORE2 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 16.6533 | 6.19 | 4.3000 |
SMSTORE3 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 16.6533 | 6.19 | 4.3000 |
SMSTORE4 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 16.6533 | 6.19 | 4.3000 |
LGSTORE2 | 348.39 | Yes | Yes | 1805.20 | 1.00 | 157.89 | 0.00 | 20.72 | 20.72 | 9.5842 | 6.19 | 4.3000 |
SMSTORE5 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 9.6995 | 6.19 | 4.3000 |
SMSTORE6 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 9.6995 | 6.19 | 4.3000 |
SMSTORE7 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 9.6995 | 6.19 | 4.3000 |
SMSTORE8 | 174.19 | Yes | Yes | 902.60 | 1.00 | 197.36 | 0.00 | 10.36 | 10.36 | 9.6995 | 6.19 | 4.3000 |
Total | 2090.32 | 10831.20 | 1184.15 | 0.00 | 124.40 | 124.40 | 13.0683 | 6.19 | 4.3000 | |||
Conditioned Total | 2090.32 | 10831.20 | 1184.15 | 0.00 | 124.40 | 124.40 | 13.0683 | 6.19 | 4.3000 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
LGSTORE1 | 348.39 | Yes | Yes | 1.00 | LGSTORE1 | GENERAL | LGSTORE1 | 15.3022 | 6.19 | 4.3000 | |
SMSTORE1 | 174.19 | Yes | Yes | 1.00 | SMSTORE1 | GENERAL | SMSTORE1 | 18.2890 | 6.19 | 4.3000 | |
SMSTORE2 | 174.19 | Yes | Yes | 1.00 | SMSTORE2 | GENERAL | SMSTORE2 | 16.6533 | 6.19 | 4.3000 | |
SMSTORE3 | 174.19 | Yes | Yes | 1.00 | SMSTORE3 | GENERAL | SMSTORE3 | 16.6533 | 6.19 | 4.3000 | |
SMSTORE4 | 174.19 | Yes | Yes | 1.00 | SMSTORE4 | GENERAL | SMSTORE4 | 16.6533 | 6.19 | 4.3000 | |
LGSTORE2 | 348.39 | Yes | Yes | 1.00 | LGSTORE2 | GENERAL | LGSTORE2 | 9.5842 | 6.19 | 4.3000 | |
SMSTORE5 | 174.19 | Yes | Yes | 1.00 | SMSTORE5 | GENERAL | SMSTORE5 | 9.6995 | 6.19 | 4.3000 | |
SMSTORE6 | 174.19 | Yes | Yes | 1.00 | SMSTORE6 | GENERAL | SMSTORE6 | 9.6995 | 6.19 | 4.3000 | |
SMSTORE7 | 174.19 | Yes | Yes | 1.00 | SMSTORE7 | GENERAL | SMSTORE7 | 9.6995 | 6.19 | 4.3000 | |
SMSTORE8 | 174.19 | Yes | Yes | 1.00 | SMSTORE8 | GENERAL | SMSTORE8 | 9.6995 | 6.19 | 4.3000 | |
Total | 2090.32 | 13.0683 | 3.10 | 4.3000 | |||||||
Conditioned Total | 2090.32 | 13.0683 | 3.10 | 4.3000 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 2090.32 | 2090.32 | 0.00 | 0.00 | 13.0683 | 6.19 | 4.3000 |
Total | 2090.32 | 2090.32 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:59
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 15-JUL-14:20 | 06-FEB-12:09 | - | - | - | - | - | - | - | - | - | - | 06-JAN-13:09 |
Heating | 0.00 | 249234.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 36429.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 23459.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 8059.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 6356.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 6606.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 80911.64 | 249234.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 249234.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 36429.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 23459.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 8059.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 6356.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 6606.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:59
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 771.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 200.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1161.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 190.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 405.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 310.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 206.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2475.40 | 771.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 369.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 96.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 555.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 91.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 194.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 148.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 98.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1184.22 | 369.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 369.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 96.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 555.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 91.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 194.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 148.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 98.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1184.22 | 369.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:59
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
LGSTORE1 DIRECT AIR | 1.86 |
SMSTORE1 DIRECT AIR | 0.995759 |
SMSTORE2 DIRECT AIR | 1.00 |
SMSTORE3 DIRECT AIR | 0.994416 |
SMSTORE4 DIRECT AIR | 0.991276 |
LGSTORE2 DIRECT AIR | 1.78 |
SMSTORE5 DIRECT AIR | 0.914165 |
SMSTORE6 DIRECT AIR | 0.907721 |
SMSTORE7 DIRECT AIR | 0.896825 |
SMSTORE8 DIRECT AIR | 0.934906 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC_1:1 | 1.86 | 1.86 | 1.86 | 1.86 | 1.86 | 1.86 | 1.00 | 1.000000 | 1.86 |
PSZ-AC_2:2 | 0.995759 | 0.995759 | 0.995759 | 0.995759 | 1.01 | 1.01 | 1.00 | 0.982975 | 1.01 |
PSZ-AC_3:3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.02 | 1.02 | 1.00 | 0.981341 | 1.02 |
PSZ-AC_4:4 | 0.994416 | 0.994416 | 0.994416 | 0.994416 | 1.02 | 1.02 | 1.00 | 0.972375 | 1.02 |
PSZ-AC_5:5 | 0.991276 | 0.991276 | 0.991276 | 0.991276 | 1.01 | 1.01 | 1.00 | 0.979155 | 1.01 |
PSZ-AC_6:6 | 1.78 | 1.78 | 1.78 | 1.78 | 1.78 | 1.78 | 1.00 | 1.00 | 1.78 |
PSZ-AC_7:7 | 0.914165 | 0.914165 | 0.914165 | 0.914165 | 0.921140 | 0.921140 | 1.00 | 0.992427 | 0.921140 |
PSZ-AC_8:8 | 0.907721 | 0.907721 | 0.907721 | 0.907721 | 0.915113 | 0.915113 | 1.00 | 0.991923 | 0.915113 |
PSZ-AC_9:9 | 0.896825 | 0.896825 | 0.896825 | 0.896825 | 0.905562 | 0.905562 | 1.00 | 0.990352 | 0.905562 |
PSZ-AC_10:10 | 0.934906 | 0.934906 | 0.934906 | 0.934906 | 0.961301 | 0.961301 | 1.00 | 0.972542 | 0.961301 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC_1:1_OA_CONTROLLER | 1.86 | 0.411479 |
PSZ-AC_2:2_OA_CONTROLLER | 1.01 | 0.205739 |
PSZ-AC_3:3_OA_CONTROLLER | 1.02 | 0.205739 |
PSZ-AC_4:4_OA_CONTROLLER | 1.02 | 0.205739 |
PSZ-AC_5:5_OA_CONTROLLER | 1.01 | 0.205739 |
PSZ-AC_6:6_OA_CONTROLLER | 1.78 | 0.411479 |
PSZ-AC_7:7_OA_CONTROLLER | 0.921140 | 0.205739 |
PSZ-AC_8:8_OA_CONTROLLER | 0.915113 | 0.205739 |
PSZ-AC_9:9_OA_CONTROLLER | 0.905562 | 0.205739 |
PSZ-AC_10:10_OA_CONTROLLER | 0.961301 | 0.205739 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | 1.86 | 1994.18 |
PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | 1.01 | 1121.56 |
PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | 1.02 | 1128.28 |
PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | 1.02 | 1132.25 |
PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | 1.01 | 1120.86 |
PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | 1.78 | 1899.53 |
PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | 0.921140 | 1019.85 |
PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | 0.915113 | 1013.18 |
PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | 0.905562 | 1002.60 |
PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | 0.961301 | 1064.31 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC_1:1_UNITARY_PACKAGE_DX | 1.86 | 1.86 | 1.86 | 1.23 | 40181.26 | 59694.63 | 40.00 | 1.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_DX | 1.01 | 1.01 | 1.01 | 0.668583 | 21420.44 | 31272.07 | 40.00 | 1.00 |
PSZ-AC_3:3_UNITARY_PACKAGE_DX | 1.02 | 1.02 | 1.02 | 0.672590 | 21521.61 | 31367.96 | 40.00 | 1.00 |
PSZ-AC_4:4_UNITARY_PACKAGE_DX | 1.02 | 1.02 | 1.02 | 0.674960 | 21580.24 | 31242.14 | 40.00 | 1.00 |
PSZ-AC_5:5_UNITARY_PACKAGE_DX | 1.01 | 1.01 | 1.01 | 0.668170 | 21414.15 | 31172.14 | 40.00 | 1.00 |
PSZ-AC_6:6_UNITARY_PACKAGE_DX | 1.78 | 1.78 | 1.78 | 1.17 | 38591.68 | 57721.90 | 40.00 | 1.00 |
PSZ-AC_7:7_UNITARY_PACKAGE_DX | 0.921140 | 0.921140 | 0.921140 | 0.607952 | 19962.88 | 29453.43 | 40.00 | 1.00 |
PSZ-AC_8:8_UNITARY_PACKAGE_DX | 0.915113 | 0.915113 | 0.915113 | 0.603975 | 19866.44 | 29309.82 | 40.00 | 1.00 |
PSZ-AC_9:9_UNITARY_PACKAGE_DX | 0.905562 | 0.905562 | 0.905562 | 0.597671 | 19692.33 | 29066.94 | 40.00 | 1.00 |
PSZ-AC_10:10_UNITARY_PACKAGE_DX | 0.961301 | 0.961301 | 0.961301 | 0.634459 | 20616.94 | 29916.79 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-AC_1:1 COOLING COIL | 1.86 | 0.931819 | 1.24 | 40181.26 | 20090.63 | 0.748270 | 0.748270 |
PSZ-AC_2:2 COOLING COIL | 1.01 | 0.506503 | 0.675340 | 21420.44 | 10710.22 | 0.754820 | 0.754820 |
PSZ-AC_3:3 COOLING COIL | 1.02 | 0.509538 | 0.679387 | 21521.61 | 10760.81 | 0.755180 | 0.755180 |
PSZ-AC_4:4 COOLING COIL | 1.02 | 0.511333 | 0.681780 | 21580.24 | 10790.12 | 0.755410 | 0.755410 |
PSZ-AC_5:5 COOLING COIL | 1.01 | 0.506190 | 0.674920 | 21414.15 | 10707.08 | 0.754720 | 0.754720 |
PSZ-AC_6:6 COOLING COIL | 1.78 | 0.887591 | 1.18 | 38591.68 | 19295.84 | 0.744950 | 0.744950 |
PSZ-AC_7:7 COOLING COIL | 0.921140 | 0.460570 | 0.614093 | 19962.88 | 9981.44 | 0.745820 | 0.745820 |
PSZ-AC_8:8 COOLING COIL | 0.915110 | 0.457557 | 0.610073 | 19866.44 | 9933.22 | 0.745340 | 0.745340 |
PSZ-AC_9:9 COOLING COIL | 0.905560 | 0.452781 | 0.603707 | 19692.33 | 9846.17 | 0.744870 | 0.744870 |
PSZ-AC_10:10 COOLING COIL | 0.961300 | 0.480651 | 0.640867 | 20616.94 | 10308.47 | 0.749770 | 0.749770 |
Design Size Nominal Capacity [W] | |
PSZ-AC_1:1 HEATING COIL | 59694.63 |
PSZ-AC_2:2 HEATING COIL | 31272.07 |
PSZ-AC_3:3 HEATING COIL | 31367.96 |
PSZ-AC_4:4 HEATING COIL | 31242.14 |
PSZ-AC_5:5 HEATING COIL | 31172.14 |
PSZ-AC_6:6 HEATING COIL | 57721.90 |
PSZ-AC_7:7 HEATING COIL | 29453.43 |
PSZ-AC_8:8 HEATING COIL | 29309.82 |
PSZ-AC_9:9 HEATING COIL | 29066.94 |
PSZ-AC_10:10 HEATING COIL | 29916.79 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:59
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
LGSTORE1_WALL_3 | LGSTORE1_WALL_3_DOOR_1 | LGSTORE1_WALL_3_DOOR_2 | |
LGSTORE1_WALL_1 | LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | |
SMSTORE1_WALL_1 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | |
SMSTORE1_WALL_3 | SMSTORE1_WALL_3_DOOR | |
SMSTORE2_WALL_1 | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | |
SMSTORE2_WALL_3 | SMSTORE2_WALL_3_DOOR | |
SMSTORE3_WALL_1 | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | |
SMSTORE3_WALL_3 | SMSTORE3_WALL_3_DOOR | |
SMSTORE4_WALL_1 | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | |
SMSTORE4_WALL_3 | SMSTORE4_WALL_3_DOOR | |
LGSTORE2_WALL_3 | LGSTORE2_WALL_3_DOOR_1 | LGSTORE2_WALL_3_DOOR_2 | |
LGSTORE2_WALL_1 | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | |
SMSTORE5_WALL_1 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | |
SMSTORE5_WALL_3 | SMSTORE5_WALL_3_DOOR | |
SMSTORE6_WALL_1 | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | |
SMSTORE6_WALL_3 | SMSTORE6_WALL_3_DOOR | |
SMSTORE7_WALL_1 | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | |
SMSTORE7_WALL_3 | SMSTORE7_WALL_3_DOOR | |
SMSTORE8_WALL_1 | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR | |
SMSTORE8_WALL_3 | SMSTORE8_WALL_3_DOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:59
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:59
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 9.70 | 6.00 | -2.20 | -3.40 | -4.20 | 2.70 | 7.50 | 13.70 | 18.60 | 22.00 | 20.70 | 16.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280 | 42.93 | -78.73 | -5.00 | 215.00 | 98769 | 1.1739 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 8.97 | 26.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RetailStripmall | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 10 | 118 | 48 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | LGSTORE1 | 0.0 | 0.00 | 0.00 | 0.00 | 7.62 | 11.43 | 2.59 | 1 | 1 | 1 | 0.00 | 15.24 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 1805.20 | TARP | TARP | 348.39 | 276.30 | 247.74 | 20.77 | 6 | 8 | 0 | Yes |
2 | SMSTORE1 | 0.0 | 0.00 | 0.00 | 0.00 | 19.05 | 11.43 | 2.59 | 1 | 1 | 1 | 15.24 | 22.86 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.66 | 10.38 | 6 | 4 | 0 | Yes |
3 | SMSTORE2 | 0.0 | 0.00 | 0.00 | 0.00 | 26.67 | 11.43 | 2.59 | 1 | 1 | 1 | 22.86 | 30.48 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
4 | SMSTORE3 | 0.0 | 0.00 | 0.00 | 0.00 | 34.29 | 11.43 | 2.59 | 1 | 1 | 1 | 30.48 | 38.10 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
5 | SMSTORE4 | 0.0 | 0.00 | 0.00 | 0.00 | 41.91 | 11.43 | 2.59 | 1 | 1 | 1 | 38.10 | 45.72 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
6 | LGSTORE2 | 0.0 | 0.00 | 0.00 | 0.00 | 53.34 | 11.43 | 2.59 | 1 | 1 | 1 | 45.72 | 60.96 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 1805.20 | TARP | TARP | 348.39 | 157.89 | 129.41 | 20.72 | 6 | 8 | 0 | Yes |
7 | SMSTORE5 | 0.0 | 0.00 | 0.00 | 0.00 | 64.77 | 11.43 | 2.59 | 1 | 1 | 1 | 60.96 | 68.58 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
8 | SMSTORE6 | 0.0 | 0.00 | 0.00 | 0.00 | 72.39 | 11.43 | 2.59 | 1 | 1 | 1 | 68.58 | 76.20 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
9 | SMSTORE7 | 0.0 | 0.00 | 0.00 | 0.00 | 80.01 | 11.43 | 2.59 | 1 | 1 | 1 | 76.20 | 83.82 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
10 | SMSTORE8 | 0.0 | 0.00 | 0.00 | 0.00 | 87.63 | 11.43 | 2.59 | 1 | 1 | 1 | 83.82 | 91.44 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 197.36 | 183.12 | 10.36 | 6 | 4 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | LGSTORE1 | 348.39 | 56.3 | 6.193 | 0.161 | 15.302 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 19.602 | No |
2 | SMSTORE1 | 174.19 | 28.1 | 6.194 | 0.161 | 18.289 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 22.589 | No |
3 | SMSTORE2 | 174.19 | 28.1 | 6.194 | 0.161 | 16.653 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 20.953 | No |
4 | SMSTORE3 | 174.19 | 28.1 | 6.194 | 0.161 | 16.653 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 20.953 | No |
5 | SMSTORE4 | 174.19 | 28.1 | 6.194 | 0.161 | 16.653 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 20.953 | No |
6 | LGSTORE2 | 348.39 | 56.3 | 6.193 | 0.161 | 9.584 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 13.884 | No |
7 | SMSTORE5 | 174.19 | 28.1 | 6.194 | 0.161 | 9.699 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 13.999 | No |
8 | SMSTORE6 | 174.19 | 28.1 | 6.194 | 0.161 | 9.699 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 13.999 | No |
9 | SMSTORE7 | 174.19 | 28.1 | 6.194 | 0.161 | 9.699 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 13.999 | No |
10 | SMSTORE8 | 174.19 | 28.1 | 6.194 | 0.161 | 9.699 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 13.999 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | LGSTORE1 | TYPE1_OCC_SCH | LGSTORE1 | 348.39 | 56.3 | 56.3 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 56 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | SMSTORE1 | TYPE1_OCC_SCH | SMSTORE1 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | SMSTORE2 | TYPE2_OCC_SCH | SMSTORE2 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | SMSTORE3 | TYPE2_OCC_SCH | SMSTORE3 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | SMSTORE4 | TYPE2_OCC_SCH | SMSTORE4 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | LGSTORE2 | TYPE3_OCC_SCH | LGSTORE2 | 348.39 | 56.3 | 56.3 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 56 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | SMSTORE5 | TYPE3_OCC_SCH | SMSTORE5 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | SMSTORE6 | TYPE3_OCC_SCH | SMSTORE6 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | SMSTORE7 | TYPE3_OCC_SCH | SMSTORE7 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | SMSTORE8 | TYPE3_OCC_SCH | SMSTORE8 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | LGSTORE1_LIGHTS | LTG_SCH_BASE_LPD1 | LGSTORE1 | 348.39 | 56.3 | 3346.345 | 9.605 | 59.490 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3346.345 |
2 | LGSTORE1_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | LGSTORE1 | 348.39 | 56.3 | 1984.726 | 5.697 | 35.284 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1984.726 |
3 | SMSTORE1_LIGHTS | LTG_SCH_BASE_SMALL_LPD1 | SMSTORE1 | 174.19 | 28.1 | 1693.257 | 9.721 | 60.206 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1693.257 |
4 | SMSTORE1_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | SMSTORE1 | 174.19 | 28.1 | 1492.567 | 8.568 | 53.070 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1492.567 |
5 | SMSTORE2_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE2 | 174.19 | 28.1 | 1689.582 | 9.699 | 60.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1689.582 |
6 | SMSTORE2_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE2 | 174.19 | 28.1 | 1211.319 | 6.954 | 43.070 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1211.319 |
7 | SMSTORE3_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE3 | 174.19 | 28.1 | 1689.582 | 9.699 | 60.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1689.582 |
8 | SMSTORE3_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE3 | 174.19 | 28.1 | 1211.319 | 6.954 | 43.070 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1211.319 |
9 | SMSTORE4_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE4 | 174.19 | 28.1 | 1689.582 | 9.699 | 60.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1689.582 |
10 | SMSTORE4_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE4 | 174.19 | 28.1 | 1211.319 | 6.954 | 43.070 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1211.319 |
11 | LGSTORE2_LIGHTS | LTG_SCH_BASE_LPD2 | LGSTORE2 | 348.39 | 56.3 | 3338.998 | 9.584 | 59.359 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3338.998 |
12 | LGSTORE2_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | LGSTORE2 | 348.39 | 56.3 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
13 | SMSTORE5_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE5 | 174.19 | 28.1 | 1689.582 | 9.699 | 60.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1689.582 |
14 | SMSTORE5_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE5 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
15 | SMSTORE6_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE6 | 174.19 | 28.1 | 1689.582 | 9.699 | 60.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1689.582 |
16 | SMSTORE6_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE6 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
17 | SMSTORE7_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE7 | 174.19 | 28.1 | 1689.582 | 9.699 | 60.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1689.582 |
18 | SMSTORE7_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE7 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
19 | SMSTORE8_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE8 | 174.19 | 28.1 | 1689.582 | 9.699 | 60.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1689.582 |
20 | SMSTORE8_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE8 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LGSTORE1_MISCPLUG_EQUIP | TYPE1_EQUIP_SCH | LGSTORE1 | 348.39 | 56.3 | 1498.062 | 4.300 | 26.632 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1498.062 |
2 | SMSTORE1_MISCPLUG_EQUIP | TYPE1_EQUIP_SCH | SMSTORE1 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
3 | SMSTORE2_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE2 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
4 | SMSTORE3_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE3 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
5 | SMSTORE4_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE4 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
6 | LGSTORE2_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | LGSTORE2 | 348.39 | 56.3 | 1498.062 | 4.300 | 26.632 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1498.062 |
7 | SMSTORE5_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE5 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
8 | SMSTORE6_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE6 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
9 | SMSTORE7_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE7 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
10 | SMSTORE8_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE8 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.770 | 0.700 | Rough |
5 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 0.5398 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
6 | LGSTORE1_FLOOR_FFACTOR | 36 | 2 | 7 | 0.167 | 0.1408 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
7 | SMSTORE1_FLOOR_FFACTOR | 37 | 2 | 7 | 0.167 | 0.7972E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
8 | SMSTORE2_FLOOR_FFACTOR | 38 | 2 | 7 | 0.167 | 0.7972E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | SMSTORE3_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.7972E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
10 | SMSTORE4_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.7972E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
11 | LGSTORE2_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.7972E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | SMSTORE5_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.7972E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | SMSTORE6_FLOOR_FFACTOR | 43 | 2 | 7 | 0.167 | 0.7972E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | SMSTORE7_FLOOR_FFACTOR | 44 | 2 | 7 | 0.167 | 0.7972E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | SMSTORE8_FLOOR_FFACTOR | 45 | 2 | 7 | 0.167 | 0.2031 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
6 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
7 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
8 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
10 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.619 |
11 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
12 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 7.024 |
13 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
14 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.47 |
15 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
16 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.47 |
17 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
18 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.47 |
19 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
20 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.47 |
21 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
22 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.47 |
23 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
24 | ~FC_Insulation_7 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.47 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_8 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.47 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_9 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.47 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_10 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.847 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
14 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
15 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
16 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
17 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
18 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
19 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
20 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
21 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
22 | 7 | -0.34329049E-12 | 0.74065570E-15 | -0.11060681E-12 | 0.10726285E-15 |
23 | 6 | 0.31458623E-07 | 0.15582808E-09 | 0.71832143E-08 | -0.15023289E-12 |
24 | 5 | -0.20415818E-03 | 0.13111101E-05 | -0.10480723E-03 | 0.70917048E-08 |
25 | 4 | 0.30843928 | 0.62847427E-03 | 0.10555000 | -0.35885187E-04 |
26 | 3 | -7.5886440 | 0.19208290E-01 | -2.4345797 | 0.30589548E-01 |
27 | 2 | 41.933758 | 0.67466625E-01 | 15.656649 | -0.34517733 |
28 | 1 | -81.359657 | 0.30121645E-01 | -29.492494 | 1.0959638 |
29 | 0 | 46.824334 | 0.59962785E-03 | 16.283006 | |
30 | 7 | -0.30155247E-08 | -0.19705740E-14 | 0.18469307E-14 | -0.46079768E-16 |
31 | 6 | 0.40551627E-05 | 0.26926011E-08 | 0.31944497E-02 | -0.26797721E-04 |
32 | 5 | -0.28496186E-03 | 0.15923452E-05 | -0.22398486 | 0.19584477E-02 |
33 | 4 | 0.65115693E-02 | 0.72427529E-04 | 4.8338806 | -0.45306652E-01 |
34 | 3 | -0.57046066E-01 | 0.57554694E-03 | -38.045903 | 0.39892442 |
35 | 2 | 0.20237164 | 0.95689144E-03 | 116.53161 | -1.4185768 |
36 | 1 | -0.29197338 | 0.29127682E-03 | -143.93536 | 2.0495010 |
37 | 0 | 0.14232195 | 0.70641069E-05 | 60.838472 | |
38 | 7 | -0.53597813E-08 | -0.10943972E-13 | 0.15521545E-14 | -0.37274179E-16 |
39 | 6 | 0.25551035E-05 | 0.15319154E-08 | 0.31991935E-02 | -0.26837516E-04 |
40 | 5 | -0.16700335E-03 | 0.90227195E-06 | -0.22425438 | 0.19608267E-02 |
41 | 4 | 0.37302439E-02 | 0.40957222E-04 | 4.8383675 | -0.45349785E-01 |
42 | 3 | -0.32401395E-01 | 0.32489936E-03 | -38.071239 | 0.39920448 |
43 | 2 | 0.11454695 | 0.53930964E-03 | 116.58090 | -1.4192362 |
44 | 1 | -0.16500402 | 0.16380141E-03 | -143.96437 | 2.0499779 |
45 | 0 | 0.80366526E-01 | 0.39747064E-05 | 60.838472 | |
46 | 7 | -0.53597813E-08 | -0.10943972E-13 | 0.15521547E-14 | -0.37274182E-16 |
47 | 6 | 0.25551035E-05 | 0.15319154E-08 | 0.31991935E-02 | -0.26837516E-04 |
48 | 5 | -0.16700335E-03 | 0.90227195E-06 | -0.22425438 | 0.19608267E-02 |
49 | 4 | 0.37302439E-02 | 0.40957222E-04 | 4.8383675 | -0.45349785E-01 |
50 | 3 | -0.32401395E-01 | 0.32489936E-03 | -38.071239 | 0.39920448 |
51 | 2 | 0.11454695 | 0.53930964E-03 | 116.58090 | -1.4192362 |
52 | 1 | -0.16500402 | 0.16380141E-03 | -143.96437 | 2.0499779 |
53 | 0 | 0.80366526E-01 | 0.39747064E-05 | 60.838472 | |
54 | 7 | -0.53597813E-08 | -0.10943972E-13 | 0.15521549E-14 | -0.37274185E-16 |
55 | 6 | 0.25551035E-05 | 0.15319154E-08 | 0.31991935E-02 | -0.26837516E-04 |
56 | 5 | -0.16700335E-03 | 0.90227195E-06 | -0.22425438 | 0.19608267E-02 |
57 | 4 | 0.37302439E-02 | 0.40957222E-04 | 4.8383675 | -0.45349785E-01 |
58 | 3 | -0.32401395E-01 | 0.32489936E-03 | -38.071239 | 0.39920448 |
59 | 2 | 0.11454695 | 0.53930964E-03 | 116.58090 | -1.4192362 |
60 | 1 | -0.16500402 | 0.16380141E-03 | -143.96437 | 2.0499779 |
61 | 0 | 0.80366526E-01 | 0.39747064E-05 | 60.838472 | |
62 | 7 | -0.53597813E-08 | -0.10943972E-13 | 0.15521548E-14 | -0.37274183E-16 |
63 | 6 | 0.25551035E-05 | 0.15319154E-08 | 0.31991935E-02 | -0.26837516E-04 |
64 | 5 | -0.16700335E-03 | 0.90227195E-06 | -0.22425438 | 0.19608267E-02 |
65 | 4 | 0.37302439E-02 | 0.40957222E-04 | 4.8383675 | -0.45349785E-01 |
66 | 3 | -0.32401395E-01 | 0.32489936E-03 | -38.071239 | 0.39920448 |
67 | 2 | 0.11454695 | 0.53930964E-03 | 116.58090 | -1.4192362 |
68 | 1 | -0.16500402 | 0.16380141E-03 | -143.96437 | 2.0499779 |
69 | 0 | 0.80366526E-01 | 0.39747064E-05 | 60.838472 | |
70 | 7 | -0.53597813E-08 | -0.10943972E-13 | 0.15521547E-14 | -0.37274182E-16 |
71 | 6 | 0.25551035E-05 | 0.15319154E-08 | 0.31991935E-02 | -0.26837516E-04 |
72 | 5 | -0.16700335E-03 | 0.90227195E-06 | -0.22425438 | 0.19608267E-02 |
73 | 4 | 0.37302439E-02 | 0.40957222E-04 | 4.8383675 | -0.45349785E-01 |
74 | 3 | -0.32401395E-01 | 0.32489936E-03 | -38.071239 | 0.39920448 |
75 | 2 | 0.11454695 | 0.53930964E-03 | 116.58090 | -1.4192362 |
76 | 1 | -0.16500402 | 0.16380141E-03 | -143.96437 | 2.0499779 |
77 | 0 | 0.80366526E-01 | 0.39747064E-05 | 60.838472 | |
78 | 7 | -0.53597813E-08 | -0.10943972E-13 | 0.15521547E-14 | -0.37274181E-16 |
79 | 6 | 0.25551035E-05 | 0.15319154E-08 | 0.31991935E-02 | -0.26837516E-04 |
80 | 5 | -0.16700335E-03 | 0.90227195E-06 | -0.22425438 | 0.19608267E-02 |
81 | 4 | 0.37302439E-02 | 0.40957222E-04 | 4.8383675 | -0.45349785E-01 |
82 | 3 | -0.32401395E-01 | 0.32489936E-03 | -38.071239 | 0.39920448 |
83 | 2 | 0.11454695 | 0.53930964E-03 | 116.58090 | -1.4192362 |
84 | 1 | -0.16500402 | 0.16380141E-03 | -143.96437 | 2.0499779 |
85 | 0 | 0.80366526E-01 | 0.39747064E-05 | 60.838472 | |
86 | 7 | -0.53597813E-08 | -0.10943972E-13 | 0.15521545E-14 | -0.37274179E-16 |
87 | 6 | 0.25551035E-05 | 0.15319154E-08 | 0.31991935E-02 | -0.26837516E-04 |
88 | 5 | -0.16700335E-03 | 0.90227195E-06 | -0.22425438 | 0.19608267E-02 |
89 | 4 | 0.37302439E-02 | 0.40957222E-04 | 4.8383675 | -0.45349785E-01 |
90 | 3 | -0.32401395E-01 | 0.32489936E-03 | -38.071239 | 0.39920448 |
91 | 2 | 0.11454695 | 0.53930964E-03 | 116.58090 | -1.4192362 |
92 | 1 | -0.16500402 | 0.16380141E-03 | -143.96437 | 2.0499779 |
93 | 0 | 0.80366526E-01 | 0.39747064E-05 | 60.838472 | |
94 | 7 | -0.53597813E-08 | -0.10943972E-13 | 0.15521547E-14 | -0.37274182E-16 |
95 | 6 | 0.25551035E-05 | 0.15319154E-08 | 0.31991935E-02 | -0.26837516E-04 |
96 | 5 | -0.16700335E-03 | 0.90227195E-06 | -0.22425438 | 0.19608267E-02 |
97 | 4 | 0.37302439E-02 | 0.40957222E-04 | 4.8383675 | -0.45349785E-01 |
98 | 3 | -0.32401395E-01 | 0.32489936E-03 | -38.071239 | 0.39920448 |
99 | 2 | 0.11454695 | 0.53930964E-03 | 116.58090 | -1.4192362 |
100 | 1 | -0.16500402 | 0.16380141E-03 | -143.96437 | 2.0499779 |
101 | 0 | 0.80366526E-01 | 0.39747064E-05 | 60.838472 | |
102 | 7 | -0.20778300E-08 | -0.65167512E-15 | 0.79548166E-14 | -0.12010680E-15 |
103 | 6 | 0.57088823E-05 | 0.38884884E-08 | 0.31895855E-02 | -0.26756916E-04 |
104 | 5 | -0.40892418E-03 | 0.23023551E-05 | -0.22370841 | 0.19560076E-02 |
105 | 4 | 0.93961169E-02 | 0.10478953E-03 | 4.8292766 | -0.45262394E-01 |
106 | 3 | -0.82481111E-01 | 0.83319714E-03 | -38.019897 | 0.39863696 |
107 | 2 | 0.29283299 | 0.13859693E-02 | 116.48099 | -1.4178998 |
108 | 1 | -0.42263540 | 0.42218679E-03 | -143.90557 | 2.0490113 |
109 | 0 | 0.20604930 | 0.10232106E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.362_SHGC_0.379 | 35 | 1 | VerySmooth | 2.057 | 2.057 | 1.000 | 0.380 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 3.63679E-002 | 0.29270 | 0.50147 | 0.50147 | 0.41690 | 0.13592 | 0.17539 | 0.00000 | 0.84000 | 0.84000 | 0.11599 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | GAS TANK1 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
2 | WaterHeater:Mixed | GAS TANK2 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
3 | WaterHeater:Mixed | GAS TANK3 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
4 | WaterHeater:Mixed | GAS TANK4 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
5 | WaterHeater:Mixed | GAS TANK5 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
6 | WaterHeater:Mixed | GAS TANK6 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
7 | WaterHeater:Mixed | GAS TANK7 | 0.1514 | 11722.8 | 1.020 | 0.7252 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | LGSTORE1_WALL_2 | 0 | 118.41 | 56.08 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
2 | LGSTORE1_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
3 | LGSTORE1_WALL_3_DOOR_1 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
4 | LGSTORE1_WALL_3_DOOR_2 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
5 | LGSTORE1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
6 | LGSTORE1_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
7 | LGSTORE1_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
8 | LGSTORE1_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
9 | LGSTORE1_WALL_1_WINDOW_3 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
10 | LGSTORE1_WALL_1_WINDOW_4 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
11 | LGSTORE1_WALL_1_DOOR_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 1 | No | No |
12 | LGSTORE1_WALL_1_DOOR_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 1 | No | No |
13 | LGSTORE1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
14 | LGSTORE1_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
15 | LGSTORE1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
16 | SMSTORE1_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
17 | SMSTORE1_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
18 | SMSTORE1_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
19 | SMSTORE1_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
20 | SMSTORE1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
21 | SMSTORE1_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
22 | SMSTORE1_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
23 | SMSTORE1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
24 | SMSTORE1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
25 | SMSTORE1_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
26 | SMSTORE1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
27 | SMSTORE2_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
28 | SMSTORE2_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
29 | SMSTORE2_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
30 | SMSTORE2_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
31 | SMSTORE2_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
32 | SMSTORE2_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
33 | SMSTORE2_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
34 | SMSTORE2_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
35 | SMSTORE2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
36 | SMSTORE2_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
37 | SMSTORE2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
38 | SMSTORE3_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
39 | SMSTORE3_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
40 | SMSTORE3_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
41 | SMSTORE3_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
42 | SMSTORE3_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
43 | SMSTORE3_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
44 | SMSTORE3_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
45 | SMSTORE3_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
46 | SMSTORE3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
47 | SMSTORE3_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
48 | SMSTORE3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
49 | SMSTORE4_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
50 | SMSTORE4_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
51 | SMSTORE4_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
52 | SMSTORE4_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
53 | SMSTORE4_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
54 | SMSTORE4_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 3 | No | No |
55 | SMSTORE4_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
56 | SMSTORE4_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
57 | SMSTORE4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
58 | SMSTORE4_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
59 | SMSTORE4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
60 | LGSTORE2_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
61 | LGSTORE2_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 4 | No | No |
62 | LGSTORE2_WALL_3_DOOR_1 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
63 | LGSTORE2_WALL_3_DOOR_2 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
64 | LGSTORE2_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
65 | LGSTORE2_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 4 | No | No |
66 | LGSTORE2_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
67 | LGSTORE2_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
68 | LGSTORE2_WALL_1_WINDOW_3 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
69 | LGSTORE2_WALL_1_WINDOW_4 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
70 | LGSTORE2_WALL_1_DOOR_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
71 | LGSTORE2_WALL_1_DOOR_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
72 | LGSTORE2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
73 | LGSTORE2_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
74 | LGSTORE2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
75 | SMSTORE5_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
76 | SMSTORE5_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
77 | SMSTORE5_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
78 | SMSTORE5_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
79 | SMSTORE5_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
80 | SMSTORE5_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
81 | SMSTORE5_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
82 | SMSTORE5_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
83 | SMSTORE5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
84 | SMSTORE5_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
85 | SMSTORE5_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
86 | SMSTORE6_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
87 | SMSTORE6_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
88 | SMSTORE6_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
89 | SMSTORE6_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
90 | SMSTORE6_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
91 | SMSTORE6_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
92 | SMSTORE6_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
93 | SMSTORE6_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
94 | SMSTORE6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
95 | SMSTORE6_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
96 | SMSTORE6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
97 | SMSTORE7_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
98 | SMSTORE7_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
99 | SMSTORE7_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
100 | SMSTORE7_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
101 | SMSTORE7_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
102 | SMSTORE7_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 3 | No | No |
103 | SMSTORE7_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
104 | SMSTORE7_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
105 | SMSTORE7_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
106 | SMSTORE7_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
107 | SMSTORE7_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
108 | SMSTORE8_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 4 | No | No |
109 | SMSTORE8_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 2 | No | No |
110 | SMSTORE8_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 2 | No | No |
111 | SMSTORE8_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 1 | No | No |
112 | SMSTORE8_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
113 | SMSTORE8_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 3 | No | No |
114 | SMSTORE8_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
115 | SMSTORE8_WALL_4 | 0 | 118.41 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 3 | No | No |
116 | SMSTORE8_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
117 | SMSTORE8_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
118 | SMSTORE8_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | LGSTORE1_INFILTRATION | TYPE1_INFIL_SCH | LGSTORE1 | 348.39 | 56.3 | 0.157 | 4.517E-004 | 2.488E-004 | 0.314 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | LGSTORE1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LGSTORE1 | 348.39 | 56.3 | 0.241 | 6.922E-004 | 3.813E-004 | 0.481 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | SMSTORE1_INFILTRATION | TYPE1_INFIL_SCH | SMSTORE1 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | SMSTORE1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE1 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | SMSTORE2_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE2 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | SMSTORE2_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE2 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | SMSTORE3_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE3 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | SMSTORE3_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE3 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | SMSTORE4_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE4 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | SMSTORE4_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE4 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | LGSTORE2_INFILTRATION | TYPE3_INFIL_SCH | LGSTORE2 | 348.39 | 56.3 | 8.993E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | LGSTORE2_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LGSTORE2 | 348.39 | 56.3 | 0.241 | 6.922E-004 | 4.692E-004 | 0.481 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | SMSTORE5_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE5 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | SMSTORE5_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE5 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | SMSTORE6_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE6 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | SMSTORE6_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE6 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | SMSTORE7_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE7 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
18 | SMSTORE7_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE7 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | SMSTORE8_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE8 | 174.19 | 28.1 | 0.112 | 6.453E-004 | 2.994E-004 | 0.448 | 0.000 | 0.000 | 0.224 | 0.000 |
20 | SMSTORE8_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE8 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 3.583E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | LGSTORE1 | Mixing/Well-Stirred |
2 | SMSTORE1 | Mixing/Well-Stirred |
3 | SMSTORE2 | Mixing/Well-Stirred |
4 | SMSTORE3 | Mixing/Well-Stirred |
5 | SMSTORE4 | Mixing/Well-Stirred |
6 | LGSTORE2 | Mixing/Well-Stirred |
7 | SMSTORE5 | Mixing/Well-Stirred |
8 | SMSTORE6 | Mixing/Well-Stirred |
9 | SMSTORE7 | Mixing/Well-Stirred |
10 | SMSTORE8 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone LGSTORE1 | 1.2000 |
3 | Zone SMSTORE1 | 1.2000 |
4 | Zone SMSTORE2 | 1.2000 |
5 | Zone SMSTORE3 | 1.2000 |
6 | Zone SMSTORE4 | 1.2000 |
7 | Zone LGSTORE2 | 1.2000 |
8 | Zone SMSTORE5 | 1.2000 |
9 | Zone SMSTORE6 | 1.2000 |
10 | Zone SMSTORE7 | 1.2000 |
11 | Zone SMSTORE8 | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone LGSTORE1 | 1.2000 |
3 | Zone SMSTORE1 | 1.2000 |
4 | Zone SMSTORE2 | 1.2000 |
5 | Zone SMSTORE3 | 1.2000 |
6 | Zone SMSTORE4 | 1.2000 |
7 | Zone LGSTORE2 | 1.2000 |
8 | Zone SMSTORE5 | 1.2000 |
9 | Zone SMSTORE6 | 1.2000 |
10 | Zone SMSTORE7 | 1.2000 |
11 | Zone SMSTORE8 | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | LGSTORE1 | Cooling | 20627.43873 | 24752.92648 | 1.55303 | 1.86364 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 30.30000 | 1.33670E-002 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
2 | LGSTORE1 | Heating | 27807.21440 | 33368.65728 | 1.22941 | 1.47529 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -16.30000 | 9.24091E-004 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
3 | SMSTORE1 | Cooling | 11351.75907 | 13622.11088 | 0.82980 | 0.99576 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 26.76600 | 1.33607E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
4 | SMSTORE1 | Heating | 13109.84833 | 15731.81800 | 0.57962 | 0.69555 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -16.30000 | 9.24091E-004 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
5 | SMSTORE2 | Cooling | 11399.96637 | 13679.95965 | 0.83338 | 1.00006 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 25.18500 | 1.33579E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
6 | SMSTORE2 | Heating | 13257.62896 | 15909.15475 | 0.58616 | 0.70339 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -16.30000 | 9.24091E-004 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
7 | SMSTORE3 | Cooling | 11337.64794 | 13605.17752 | 0.82868 | 0.99442 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 25.18500 | 1.33579E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
8 | SMSTORE3 | Heating | 13337.19130 | 16004.62955 | 0.58968 | 0.70761 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -16.30000 | 9.24091E-004 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
9 | SMSTORE4 | Cooling | 11302.60123 | 13563.12147 | 0.82606 | 0.99128 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 25.18500 | 1.33579E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
10 | SMSTORE4 | Heating | 13480.22492 | 16176.26990 | 0.59600 | 0.71520 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -16.30000 | 9.24091E-004 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
11 | LGSTORE2 | Cooling | 19649.09890 | 23578.91868 | 1.47932 | 1.77518 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 30.06750 | 1.33665E-002 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
12 | LGSTORE2 | Heating | 25808.85431 | 30970.62517 | 1.14110 | 1.36932 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -16.30000 | 9.24091E-004 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
13 | SMSTORE5 | Cooling | 10445.54621 | 12534.65545 | 0.76180 | 0.91416 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 26.76600 | 1.33607E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
14 | SMSTORE5 | Heating | 13809.77071 | 16571.72485 | 0.61057 | 0.73269 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -16.30000 | 9.24091E-004 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
15 | SMSTORE6 | Cooling | 10374.21026 | 12449.05231 | 0.75643 | 0.90772 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 26.76600 | 1.33607E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
16 | SMSTORE6 | Heating | 13797.67040 | 16557.20449 | 0.61004 | 0.73204 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -16.30000 | 9.24091E-004 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
17 | SMSTORE7 | Cooling | 10253.71380 | 12304.45656 | 0.74735 | 0.89682 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 26.76600 | 1.33607E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
18 | SMSTORE7 | Heating | 14010.22035 | 16812.26442 | 0.61943 | 0.74332 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -16.30000 | 9.24091E-004 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
19 | SMSTORE8 | Cooling | 10675.10053 | 12810.12064 | 0.77909 | 0.93491 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 26.76600 | 1.33607E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
20 | SMSTORE8 | Heating | 17211.28273 | 20653.53927 | 0.76091 | 0.91309 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -16.30000 | 9.24091E-004 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC_1:1 | Cooling | Sensible | 27483.76 | 1.86364 | 1.86364 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-AC_1:1 | Heating | Sensible | 51038.80 | 1.47529 | 1.47529 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
3 | PSZ-AC_2:2 | Cooling | Sensible | 14793.78 | 1.01301 | 1.01301 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-AC_2:2 | Heating | Sensible | 24580.86 | 0.69555 | 0.69555 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
5 | PSZ-AC_3:3 | Cooling | Sensible | 14864.53 | 1.01908 | 1.01908 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
6 | PSZ-AC_3:3 | Heating | Sensible | 24755.62 | 0.70339 | 0.70339 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
7 | PSZ-AC_4:4 | Cooling | Sensible | 14909.42 | 1.02267 | 1.02267 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
8 | PSZ-AC_4:4 | Heating | Sensible | 24849.70 | 0.70761 | 0.70761 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
9 | PSZ-AC_5:5 | Cooling | Sensible | 14775.76 | 1.01238 | 1.01238 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
10 | PSZ-AC_5:5 | Heating | Sensible | 25018.85 | 0.71520 | 0.71520 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
11 | PSZ-AC_6:6 | Cooling | Sensible | 26290.22 | 1.77518 | 1.77518 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
12 | PSZ-AC_6:6 | Heating | Sensible | 48676.04 | 1.36932 | 1.36932 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
13 | PSZ-AC_7:7 | Cooling | Sensible | 13512.99 | 0.92114 | 0.92114 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
14 | PSZ-AC_7:7 | Heating | Sensible | 25408.55 | 0.73269 | 0.73269 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
15 | PSZ-AC_8:8 | Cooling | Sensible | 13429.65 | 0.91511 | 0.91511 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
16 | PSZ-AC_8:8 | Heating | Sensible | 25394.24 | 0.73204 | 0.73204 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
17 | PSZ-AC_9:9 | Cooling | Sensible | 13348.61 | 0.90556 | 0.90556 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
18 | PSZ-AC_9:9 | Heating | Sensible | 25645.59 | 0.74332 | 0.74332 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
19 | PSZ-AC_10:10 | Cooling | Sensible | 14015.75 | 0.96130 | 0.96130 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
20 | PSZ-AC_10:10 | Heating | Sensible | 29430.61 | 0.91309 | 0.91309 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | LGSTORE1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.86364 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.99576 |
3 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.00006 |
4 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.99442 |
5 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE4 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.99128 |
6 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | LGSTORE2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.77518 |
7 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE5 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.91416 |
8 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.90772 |
9 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE7 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.89682 |
10 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE8 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.93491 |
11 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.86364 |
12 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.86364 |
13 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.86364 |
14 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.86364 |
15 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.86364 |
16 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Main Design Air Flow Rate [m3/s] | 1.86364 |
17 | AirLoopHVAC | PSZ-AC_1:1 | User Heating Air Flow Ratio [] | 1.00000 |
18 | AirLoopHVAC | PSZ-AC_1:1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
19 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.99576 |
20 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.99576 |
21 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.99576 |
22 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.99576 |
23 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.01301 |
24 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Main Design Air Flow Rate [m3/s] | 1.01301 |
25 | AirLoopHVAC | PSZ-AC_2:2 | User Heating Air Flow Ratio [] | 1.00000 |
26 | AirLoopHVAC | PSZ-AC_2:2 | Calculated Heating Air Flow Ratio [] | 0.98298 |
27 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.00006 |
28 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.00006 |
29 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.00006 |
30 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.00006 |
31 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.01908 |
32 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Main Design Air Flow Rate [m3/s] | 1.01908 |
33 | AirLoopHVAC | PSZ-AC_3:3 | User Heating Air Flow Ratio [] | 1.00000 |
34 | AirLoopHVAC | PSZ-AC_3:3 | Calculated Heating Air Flow Ratio [] | 0.98134 |
35 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.99442 |
36 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.99442 |
37 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.99442 |
38 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.99442 |
39 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.02267 |
40 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Main Design Air Flow Rate [m3/s] | 1.02267 |
41 | AirLoopHVAC | PSZ-AC_4:4 | User Heating Air Flow Ratio [] | 1.00000 |
42 | AirLoopHVAC | PSZ-AC_4:4 | Calculated Heating Air Flow Ratio [] | 0.97238 |
43 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.99128 |
44 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.99128 |
45 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.99128 |
46 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.99128 |
47 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.01238 |
48 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Main Design Air Flow Rate [m3/s] | 1.01238 |
49 | AirLoopHVAC | PSZ-AC_5:5 | User Heating Air Flow Ratio [] | 1.00000 |
50 | AirLoopHVAC | PSZ-AC_5:5 | Calculated Heating Air Flow Ratio [] | 0.97915 |
51 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.77518 |
52 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.77518 |
53 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.77518 |
54 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.77518 |
55 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.77518 |
56 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Main Design Air Flow Rate [m3/s] | 1.77518 |
57 | AirLoopHVAC | PSZ-AC_6:6 | User Heating Air Flow Ratio [] | 1.00000 |
58 | AirLoopHVAC | PSZ-AC_6:6 | Calculated Heating Air Flow Ratio [] | 1.00000 |
59 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.91416 |
60 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.91416 |
61 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.91416 |
62 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.91416 |
63 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.92114 |
64 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Main Design Air Flow Rate [m3/s] | 0.92114 |
65 | AirLoopHVAC | PSZ-AC_7:7 | User Heating Air Flow Ratio [] | 1.00000 |
66 | AirLoopHVAC | PSZ-AC_7:7 | Calculated Heating Air Flow Ratio [] | 0.99243 |
67 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.90772 |
68 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.90772 |
69 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.90772 |
70 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.90772 |
71 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.91511 |
72 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Main Design Air Flow Rate [m3/s] | 0.91511 |
73 | AirLoopHVAC | PSZ-AC_8:8 | User Heating Air Flow Ratio [] | 1.00000 |
74 | AirLoopHVAC | PSZ-AC_8:8 | Calculated Heating Air Flow Ratio [] | 0.99192 |
75 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.89682 |
76 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.89682 |
77 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.89682 |
78 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.89682 |
79 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.90556 |
80 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Main Design Air Flow Rate [m3/s] | 0.90556 |
81 | AirLoopHVAC | PSZ-AC_9:9 | User Heating Air Flow Ratio [] | 1.00000 |
82 | AirLoopHVAC | PSZ-AC_9:9 | Calculated Heating Air Flow Ratio [] | 0.99035 |
83 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.93491 |
84 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.93491 |
85 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.93491 |
86 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.93491 |
87 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.96130 |
88 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Main Design Air Flow Rate [m3/s] | 0.96130 |
89 | AirLoopHVAC | PSZ-AC_10:10 | User Heating Air Flow Ratio [] | 1.00000 |
90 | AirLoopHVAC | PSZ-AC_10:10 | Calculated Heating Air Flow Ratio [] | 0.97254 |
91 | AirLoopHVAC | PSZ-AC_1:1 | Design Supply Air Flow Rate [m3/s] | 1.86364 |
92 | AirLoopHVAC | PSZ-AC_2:2 | Design Supply Air Flow Rate [m3/s] | 1.01301 |
93 | AirLoopHVAC | PSZ-AC_3:3 | Design Supply Air Flow Rate [m3/s] | 1.01908 |
94 | AirLoopHVAC | PSZ-AC_4:4 | Design Supply Air Flow Rate [m3/s] | 1.02267 |
95 | AirLoopHVAC | PSZ-AC_5:5 | Design Supply Air Flow Rate [m3/s] | 1.01238 |
96 | AirLoopHVAC | PSZ-AC_6:6 | Design Supply Air Flow Rate [m3/s] | 1.77518 |
97 | AirLoopHVAC | PSZ-AC_7:7 | Design Supply Air Flow Rate [m3/s] | 0.92114 |
98 | AirLoopHVAC | PSZ-AC_8:8 | Design Supply Air Flow Rate [m3/s] | 0.91511 |
99 | AirLoopHVAC | PSZ-AC_9:9 | Design Supply Air Flow Rate [m3/s] | 0.90556 |
100 | AirLoopHVAC | PSZ-AC_10:10 | Design Supply Air Flow Rate [m3/s] | 0.96130 |
101 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.86364 |
102 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41148 |
103 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.86364 |
104 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1994.18132 |
105 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.86364 |
106 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.86364 |
107 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.86364 |
108 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.23000 |
109 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.86364 |
110 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.93182 |
111 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.24243 |
112 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 40181.26000 |
113 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 20090.63000 |
114 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.74827 |
115 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.74827 |
116 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 40181.26000 |
117 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 59694.62831 |
118 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
119 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
120 | Coil:Heating:Fuel | PSZ-AC_1:1 HEATING COIL | Design Size Nominal Capacity [W] | 59694.62831 |
121 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.01301 |
122 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
123 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.01301 |
124 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1121.55763 |
125 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.01301 |
126 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.01301 |
127 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.01301 |
128 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.66858 |
129 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.01301 |
130 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.50650 |
131 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.67534 |
132 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 21420.44000 |
133 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 10710.22000 |
134 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.75482 |
135 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.75482 |
136 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 21420.44000 |
137 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 31272.07261 |
138 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
139 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
140 | Coil:Heating:Fuel | PSZ-AC_2:2 HEATING COIL | Design Size Nominal Capacity [W] | 31272.07261 |
141 | Controller:OutdoorAir | PSZ-AC_3:3_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.01908 |
142 | Controller:OutdoorAir | PSZ-AC_3:3_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
143 | Fan:SystemModel | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.01908 |
144 | Fan:SystemModel | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1128.27885 |
145 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.01908 |
146 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.01908 |
147 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.01908 |
148 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.67259 |
149 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.01908 |
150 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.50954 |
151 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.67939 |
152 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 21521.61000 |
153 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 10760.80500 |
154 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.75518 |
155 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.75518 |
156 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 21521.61000 |
157 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 31367.95740 |
158 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
159 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
160 | Coil:Heating:Fuel | PSZ-AC_3:3 HEATING COIL | Design Size Nominal Capacity [W] | 31367.95740 |
161 | Controller:OutdoorAir | PSZ-AC_4:4_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.02267 |
162 | Controller:OutdoorAir | PSZ-AC_4:4_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
163 | Fan:SystemModel | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.02267 |
164 | Fan:SystemModel | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1132.25464 |
165 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.02267 |
166 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.02267 |
167 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.02267 |
168 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.67496 |
169 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.02267 |
170 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.51133 |
171 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.68178 |
172 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 21580.24000 |
173 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 10790.12000 |
174 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.75541 |
175 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.75541 |
176 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 21580.24000 |
177 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 31242.13505 |
178 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
179 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
180 | Coil:Heating:Fuel | PSZ-AC_4:4 HEATING COIL | Design Size Nominal Capacity [W] | 31242.13505 |
181 | Controller:OutdoorAir | PSZ-AC_5:5_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.01238 |
182 | Controller:OutdoorAir | PSZ-AC_5:5_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
183 | Fan:SystemModel | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.01238 |
184 | Fan:SystemModel | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1120.86451 |
185 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.01238 |
186 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.01238 |
187 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.01238 |
188 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.66817 |
189 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.01238 |
190 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.50619 |
191 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.67492 |
192 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 21414.15000 |
193 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 10707.07500 |
194 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.75472 |
195 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.75472 |
196 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 21414.15000 |
197 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 31172.14402 |
198 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
199 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
200 | Coil:Heating:Fuel | PSZ-AC_5:5 HEATING COIL | Design Size Nominal Capacity [W] | 31172.14402 |
201 | Controller:OutdoorAir | PSZ-AC_6:6_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.77518 |
202 | Controller:OutdoorAir | PSZ-AC_6:6_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41148 |
203 | Fan:SystemModel | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.77518 |
204 | Fan:SystemModel | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1899.52897 |
205 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.77518 |
206 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.77518 |
207 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.77518 |
208 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.17162 |
209 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.77518 |
210 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.88759 |
211 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.18345 |
212 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 38591.68000 |
213 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 19295.84000 |
214 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.74495 |
215 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.74495 |
216 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 38591.68000 |
217 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 57721.90195 |
218 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
219 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
220 | Coil:Heating:Fuel | PSZ-AC_6:6 HEATING COIL | Design Size Nominal Capacity [W] | 57721.90195 |
221 | Controller:OutdoorAir | PSZ-AC_7:7_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.92114 |
222 | Controller:OutdoorAir | PSZ-AC_7:7_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
223 | Fan:SystemModel | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.92114 |
224 | Fan:SystemModel | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1019.84815 |
225 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.92114 |
226 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.92114 |
227 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.92114 |
228 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.60795 |
229 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.92114 |
230 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.46057 |
231 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.61409 |
232 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 19962.88000 |
233 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 9981.44000 |
234 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.74582 |
235 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.74582 |
236 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 19962.88000 |
237 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 29453.42504 |
238 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
239 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
240 | Coil:Heating:Fuel | PSZ-AC_7:7 HEATING COIL | Design Size Nominal Capacity [W] | 29453.42504 |
241 | Controller:OutdoorAir | PSZ-AC_8:8_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.91511 |
242 | Controller:OutdoorAir | PSZ-AC_8:8_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
243 | Fan:SystemModel | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.91511 |
244 | Fan:SystemModel | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1013.17554 |
245 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.91511 |
246 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.91511 |
247 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.91511 |
248 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.60397 |
249 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.91511 |
250 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.45756 |
251 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.61007 |
252 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 19866.44000 |
253 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 9933.22000 |
254 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.74534 |
255 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.74534 |
256 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 19866.44000 |
257 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 29309.81849 |
258 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
259 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
260 | Coil:Heating:Fuel | PSZ-AC_8:8 HEATING COIL | Design Size Nominal Capacity [W] | 29309.81849 |
261 | Controller:OutdoorAir | PSZ-AC_9:9_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.90556 |
262 | Controller:OutdoorAir | PSZ-AC_9:9_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
263 | Fan:SystemModel | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.90556 |
264 | Fan:SystemModel | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1002.60057 |
265 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.90556 |
266 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.90556 |
267 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.90556 |
268 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.59767 |
269 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.90556 |
270 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.45278 |
271 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.60371 |
272 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 19692.33000 |
273 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 9846.16500 |
274 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.74487 |
275 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.74487 |
276 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 19692.33000 |
277 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 29066.94219 |
278 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
279 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
280 | Coil:Heating:Fuel | PSZ-AC_9:9 HEATING COIL | Design Size Nominal Capacity [W] | 29066.94219 |
281 | Controller:OutdoorAir | PSZ-AC_10:10_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.96130 |
282 | Controller:OutdoorAir | PSZ-AC_10:10_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
283 | Fan:SystemModel | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.96130 |
284 | Fan:SystemModel | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1064.31328 |
285 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.96130 |
286 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.96130 |
287 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.96130 |
288 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.63446 |
289 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.96130 |
290 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.48065 |
291 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.64087 |
292 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 20616.94000 |
293 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 10308.47000 |
294 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.74977 |
295 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.74977 |
296 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 20616.94000 |
297 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 29916.79154 |
298 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
299 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
300 | Coil:Heating:Fuel | PSZ-AC_10:10 HEATING COIL | Design Size Nominal Capacity [W] | 29916.79154 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | 38714.8 | 11.51 | 11.51 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | 20623.6 | 11.64 | 11.64 | |||
3 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | 20720.0 | 11.64 | 11.64 | |||
4 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | 20775.8 | 11.64 | 11.64 | |||
5 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | 20617.8 | 11.64 | 11.64 | |||
6 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | 37194.7 | 11.70 | 11.70 | |||
7 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | 19238.0 | 11.69 | 11.69 | |||
8 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | 19146.3 | 11.70 | 11.70 | |||
9 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | 18979.7 | 11.70 | 11.70 | |||
10 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | 19860.6 | 11.67 | 11.67 |
Zone Name | # Surfaces | |
1 | LGSTORE1 | 15 |
2 | SMSTORE1 | 11 |
3 | SMSTORE2 | 11 |
4 | SMSTORE3 | 11 |
5 | SMSTORE4 | 11 |
6 | LGSTORE2 | 15 |
7 | SMSTORE5 | 11 |
8 | SMSTORE6 | 11 |
9 | SMSTORE7 | 11 |
10 | SMSTORE8 | 11 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | LGSTORE1_WALL_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.540 | 0.499 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | LGSTORE1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.540 | 0.499 | 71.15 | 78.94 | 71.15 | 0.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | LGSTORE1_WALL_3_DOOR_1 | Door | LGSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
4 | LGSTORE1_WALL_3_DOOR_2 | Door | LGSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
5 | LGSTORE1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
6 | LGSTORE1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.540 | 0.499 | 58.18 | 78.94 | 58.18 | 180.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
7 | LGSTORE1_WALL_1_WINDOW_1 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.362_SHGC_0.379 | N/A | 2.057 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
8 | LGSTORE1_WALL_1_WINDOW_2 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.362_SHGC_0.379 | N/A | 2.057 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
9 | LGSTORE1_WALL_1_WINDOW_3 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.362_SHGC_0.379 | N/A | 2.057 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
10 | LGSTORE1_WALL_1_WINDOW_4 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.362_SHGC_0.379 | N/A | 2.057 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
11 | LGSTORE1_WALL_1_DOOR_1 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.362_SHGC_0.379 | N/A | 2.057 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
12 | LGSTORE1_WALL_1_DOOR_2 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.362_SHGC_0.379 | N/A | 2.057 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
13 | LGSTORE1_FLOOR | Floor | CTF - ConductionTransferFunction | LGSTORE1_FLOOR_FFACTOR | 0.141 | 0.136 | 348.39 | 348.39 | 348.39 | 270.00 | 180.00 | 22.86 | 15.24 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | LGSTORE1_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 348.39 | 348.39 | 348.39 | 270.00 | 0.00 | 22.86 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
15 | LGSTORE1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 696.77 | 696.77 | 696.77 | 0.00 | 90.00 | 696.77 | 1.00 | 0.00 | LGSTORE1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
16 | SMSTORE1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.540 | 0.499 | 29.09 | 39.47 | 29.09 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
17 | SMSTORE1_WALL_1_WINDOW_1 | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.362_SHGC_0.379 | N/A | 2.057 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
18 | SMSTORE1_WALL_1_WINDOW_2 | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.362_SHGC_0.379 | N/A | 2.057 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
19 | SMSTORE1_WALL_1_DOOR | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.362_SHGC_0.379 | N/A | 2.057 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
20 | SMSTORE1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | SMSTORE1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.540 | 0.499 | 35.57 | 39.47 | 35.57 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | SMSTORE1_WALL_3_DOOR | Door | SMSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
23 | SMSTORE1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE2_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | SMSTORE1_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE1_FLOOR_FFACTOR | 7.972E-002 | 7.821E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | SMSTORE1_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
26 | SMSTORE1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
27 | SMSTORE2_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.540 | 0.499 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | SMSTORE2_WALL_1_WINDOW_1 | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.362_SHGC_0.379 | N/A | 2.057 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
29 | SMSTORE2_WALL_1_WINDOW_2 | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.362_SHGC_0.379 | N/A | 2.057 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
30 | SMSTORE2_WALL_1_DOOR | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.362_SHGC_0.379 | N/A | 2.057 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
31 | SMSTORE2_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | SMSTORE2_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.540 | 0.499 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | SMSTORE2_WALL_3_DOOR | Door | SMSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
34 | SMSTORE2_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE3_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | SMSTORE2_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE2_FLOOR_FFACTOR | 7.972E-002 | 7.821E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | SMSTORE2_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | SMSTORE2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | SMSTORE3_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.540 | 0.499 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | SMSTORE3_WALL_1_WINDOW_1 | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.362_SHGC_0.379 | N/A | 2.057 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
40 | SMSTORE3_WALL_1_WINDOW_2 | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.362_SHGC_0.379 | N/A | 2.057 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
41 | SMSTORE3_WALL_1_DOOR | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.362_SHGC_0.379 | N/A | 2.057 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
42 | SMSTORE3_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE2_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | SMSTORE3_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.540 | 0.499 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | SMSTORE3_WALL_3_DOOR | Door | SMSTORE3_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
45 | SMSTORE3_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE4_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | SMSTORE3_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE3_FLOOR_FFACTOR | 7.972E-002 | 7.821E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
47 | SMSTORE3_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
48 | SMSTORE3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
49 | SMSTORE4_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.540 | 0.499 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | SMSTORE4_WALL_1_WINDOW_1 | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.362_SHGC_0.379 | N/A | 2.057 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
51 | SMSTORE4_WALL_1_WINDOW_2 | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.362_SHGC_0.379 | N/A | 2.057 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
52 | SMSTORE4_WALL_1_DOOR | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.362_SHGC_0.379 | N/A | 2.057 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | SMSTORE4_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE3_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | SMSTORE4_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.540 | 0.499 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | SMSTORE4_WALL_3_DOOR | Door | SMSTORE4_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | SMSTORE4_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE2_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | SMSTORE4_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE4_FLOOR_FFACTOR | 7.972E-002 | 7.821E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | SMSTORE4_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | SMSTORE4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | LGSTORE2_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE4_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | LGSTORE2_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.540 | 0.499 | 71.19 | 78.94 | 71.19 | 0.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
62 | LGSTORE2_WALL_3_DOOR_1 | Door | LGSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
63 | LGSTORE2_WALL_3_DOOR_2 | Door | LGSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
64 | LGSTORE2_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE5_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LGSTORE2_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.540 | 0.499 | 58.22 | 78.94 | 58.22 | 180.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
66 | LGSTORE2_WALL_1_WINDOW_1 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.362_SHGC_0.379 | N/A | 2.057 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | LGSTORE2_WALL_1_WINDOW_2 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.362_SHGC_0.379 | N/A | 2.057 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | LGSTORE2_WALL_1_WINDOW_3 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.362_SHGC_0.379 | N/A | 2.057 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | LGSTORE2_WALL_1_WINDOW_4 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.362_SHGC_0.379 | N/A | 2.057 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LGSTORE2_WALL_1_DOOR_1 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.362_SHGC_0.379 | N/A | 2.057 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
71 | LGSTORE2_WALL_1_DOOR_2 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.362_SHGC_0.379 | N/A | 2.057 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
72 | LGSTORE2_FLOOR | Floor | CTF - ConductionTransferFunction | LGSTORE2_FLOOR_FFACTOR | 7.972E-002 | 7.821E-002 | 348.39 | 348.39 | 348.39 | 270.00 | 180.00 | 22.86 | 15.24 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
73 | LGSTORE2_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 348.39 | 348.39 | 348.39 | 270.00 | 0.00 | 22.86 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
74 | LGSTORE2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 696.77 | 696.77 | 696.77 | 0.00 | 90.00 | 696.77 | 1.00 | 0.00 | LGSTORE2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
75 | SMSTORE5_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.540 | 0.499 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | SMSTORE5_WALL_1_WINDOW_1 | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.362_SHGC_0.379 | N/A | 2.057 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
77 | SMSTORE5_WALL_1_WINDOW_2 | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.362_SHGC_0.379 | N/A | 2.057 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | SMSTORE5_WALL_1_DOOR | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.362_SHGC_0.379 | N/A | 2.057 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
79 | SMSTORE5_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE2_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | SMSTORE5_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.540 | 0.499 | 35.59 | 39.47 | 35.59 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | SMSTORE5_WALL_3_DOOR | Door | SMSTORE5_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
82 | SMSTORE5_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE6_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
83 | SMSTORE5_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE5_FLOOR_FFACTOR | 7.972E-002 | 7.821E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
84 | SMSTORE5_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
85 | SMSTORE5_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE5_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | SMSTORE6_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.540 | 0.499 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | SMSTORE6_WALL_1_WINDOW_1 | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.362_SHGC_0.379 | N/A | 2.057 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | SMSTORE6_WALL_1_WINDOW_2 | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.362_SHGC_0.379 | N/A | 2.057 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
89 | SMSTORE6_WALL_1_DOOR | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.362_SHGC_0.379 | N/A | 2.057 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | SMSTORE6_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE5_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | SMSTORE6_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.540 | 0.499 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | SMSTORE6_WALL_3_DOOR | Door | SMSTORE6_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
93 | SMSTORE6_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE7_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | SMSTORE6_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE6_FLOOR_FFACTOR | 7.972E-002 | 7.821E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
95 | SMSTORE6_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
96 | SMSTORE6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
97 | SMSTORE7_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.540 | 0.499 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | SMSTORE7_WALL_1_WINDOW_1 | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.362_SHGC_0.379 | N/A | 2.057 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | SMSTORE7_WALL_1_WINDOW_2 | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.362_SHGC_0.379 | N/A | 2.057 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
100 | SMSTORE7_WALL_1_DOOR | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.362_SHGC_0.379 | N/A | 2.057 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
101 | SMSTORE7_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE6_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
102 | SMSTORE7_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.540 | 0.499 | 35.59 | 39.47 | 35.59 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | SMSTORE7_WALL_3_DOOR | Door | SMSTORE7_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
104 | SMSTORE7_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE8_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | SMSTORE7_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE7_FLOOR_FFACTOR | 7.972E-002 | 7.821E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
106 | SMSTORE7_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
107 | SMSTORE7_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE7_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
108 | SMSTORE8_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.540 | 0.499 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | SMSTORE8_WALL_1_WINDOW_1 | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.362_SHGC_0.379 | N/A | 2.057 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
110 | SMSTORE8_WALL_1_WINDOW_2 | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.362_SHGC_0.379 | N/A | 2.057 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
111 | SMSTORE8_WALL_1_DOOR | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.362_SHGC_0.379 | N/A | 2.057 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
112 | SMSTORE8_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE7_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | SMSTORE8_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.540 | 0.499 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | SMSTORE8_WALL_3_DOOR | Door | SMSTORE8_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
115 | SMSTORE8_WALL_4 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.540 | 0.499 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | SMSTORE8_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE8_FLOOR_FFACTOR | 0.203 | 0.194 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | SMSTORE8_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | SMSTORE8_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE8_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | LGSTORE1 | RunPeriod: RUNPERIOD 1 | 4.4622255727E-002 | 0.2430240309 | Pass | Pass | 0.2198251162 | 1.2933151870 | Pass | Pass |
2 | SMSTORE1 | RunPeriod: RUNPERIOD 1 | 4.6648309900E-002 | 0.1831745027 | Pass | Pass | 0.1555300407 | 0.6526610114 | Pass | Pass |
3 | SMSTORE2 | RunPeriod: RUNPERIOD 1 | 4.6499429463E-002 | 0.2432104624 | Pass | Pass | 9.9140086137E-002 | 0.7341797562 | Pass | Pass |
4 | SMSTORE3 | RunPeriod: RUNPERIOD 1 | 5.2211974750E-002 | 0.2783772527 | Pass | Pass | 0.1014451201 | 0.7944108810 | Pass | Pass |
5 | SMSTORE4 | RunPeriod: RUNPERIOD 1 | 5.6527998527E-002 | 0.3056201011 | Pass | Pass | 8.3016185415E-002 | 0.6073723986 | Pass | Pass |
6 | LGSTORE2 | RunPeriod: RUNPERIOD 1 | 6.8027719521E-002 | 0.3469543659 | Pass | Pass | 2.7464784363E-002 | 9.6712288589E-002 | Pass | Pass |
7 | SMSTORE5 | RunPeriod: RUNPERIOD 1 | 6.7421599804E-002 | 0.3452672536 | Pass | Pass | 2.6028652887E-002 | 8.6767585207E-002 | Pass | Pass |
8 | SMSTORE6 | RunPeriod: RUNPERIOD 1 | 6.8482778610E-002 | 0.3504706295 | Pass | Pass | 2.5925483898E-002 | 8.6655649705E-002 | Pass | Pass |
9 | SMSTORE7 | RunPeriod: RUNPERIOD 1 | 7.3519272575E-002 | 0.3779103671 | Pass | Pass | 2.5281832324E-002 | 8.6274673552E-002 | Pass | Pass |
10 | SMSTORE8 | RunPeriod: RUNPERIOD 1 | 0.1069081218 | 0.4286554326 | Pass | Pass | 4.3368097999E-002 | 0.1832428791 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:59
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 3974.30 | 262.58 | 0.00 | 588.05 | 463.37 | 5288.32 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:59
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | -16.30 | 0.00 | -16.30 | Wetbulb [C] | 5.10 | 270.00 |
BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 30.30 | 9.30 | 21.80 | Wetbulb [C] | 5.70 | 240.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 44.00 | 33 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 0.00 | 0 | |||
Sep | 67.00 | 33 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:59
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_2 | NONRES_EXT_WALL_GRD | 0.30 | 0.499 | 0.540 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE1_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.499 | 0.540 | 78.94 | 71.15 | 0.00 | 90.00 | N |
LGSTORE1_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.499 | 0.540 | 78.94 | 58.18 | 180.00 | 90.00 | S |
LGSTORE1_FLOOR | LGSTORE1_FLOOR_FFACTOR | 1.00 | 0.138 | 0.141 | 348.39 | 348.39 | 270.00 | 180.00 | |
LGSTORE1_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 348.39 | 348.39 | 270.00 | 0.00 | |
SMSTORE1_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.499 | 0.540 | 39.47 | 29.09 | 180.00 | 90.00 | S |
SMSTORE1_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.499 | 0.540 | 39.47 | 35.57 | 0.00 | 90.00 | N |
SMSTORE1_FLOOR | SMSTORE1_FLOOR_FFACTOR | 1.00 | 0.079 | 0.080 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE1_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE2_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.499 | 0.540 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE2_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.499 | 0.540 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE2_FLOOR | SMSTORE2_FLOOR_FFACTOR | 1.00 | 0.079 | 0.080 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE2_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE3_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.499 | 0.540 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE3_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.499 | 0.540 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE3_FLOOR | SMSTORE3_FLOOR_FFACTOR | 1.00 | 0.079 | 0.080 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE3_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE4_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.499 | 0.540 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE4_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.499 | 0.540 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE4_FLOOR | SMSTORE4_FLOOR_FFACTOR | 1.00 | 0.079 | 0.080 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE4_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
LGSTORE2_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.499 | 0.540 | 78.94 | 71.19 | 0.00 | 90.00 | N |
LGSTORE2_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.499 | 0.540 | 78.94 | 58.22 | 180.00 | 90.00 | S |
LGSTORE2_FLOOR | LGSTORE2_FLOOR_FFACTOR | 1.00 | 0.079 | 0.080 | 348.39 | 348.39 | 270.00 | 180.00 | |
LGSTORE2_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 348.39 | 348.39 | 270.00 | 0.00 | |
SMSTORE5_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.499 | 0.540 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE5_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.499 | 0.540 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE5_FLOOR | SMSTORE5_FLOOR_FFACTOR | 1.00 | 0.079 | 0.080 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE5_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE6_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.499 | 0.540 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE6_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.499 | 0.540 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE6_FLOOR | SMSTORE6_FLOOR_FFACTOR | 1.00 | 0.079 | 0.080 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE6_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE7_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.499 | 0.540 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE7_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.499 | 0.540 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE7_FLOOR | SMSTORE7_FLOOR_FFACTOR | 1.00 | 0.079 | 0.080 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE7_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE8_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.499 | 0.540 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE8_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.499 | 0.540 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE8_WALL_4 | NONRES_EXT_WALL_GRD | 0.30 | 0.499 | 0.540 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE8_FLOOR | SMSTORE8_FLOOR_FFACTOR | 1.00 | 0.197 | 0.203 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE8_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 174.19 | 174.19 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE1_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE2_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE2_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE3_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE3_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE4_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE4_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
LGSTORE2_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE2_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE5_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE5_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE6_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE6_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE7_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE7_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE8_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 696.77 | 0.00 | 90.00 | N | ||
SMSTORE1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
LGSTORE2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 696.77 | 0.00 | 90.00 | N | ||
SMSTORE5_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE7_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE8_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.362_SHGC_0.379 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.057 | 0.380 | 0.418 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.362_SHGC_0.379 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.057 | 0.380 | 0.418 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_3 | NONRESWINDOW_U_0.362_SHGC_0.379 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.057 | 0.380 | 0.418 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_4 | NONRESWINDOW_U_0.362_SHGC_0.379 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.057 | 0.380 | 0.418 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_DOOR_1 | NONRESWINDOW_U_0.362_SHGC_0.379 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.057 | 0.380 | 0.418 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_DOOR_2 | NONRESWINDOW_U_0.362_SHGC_0.379 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.057 | 0.380 | 0.418 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.362_SHGC_0.379 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.057 | 0.380 | 0.418 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.362_SHGC_0.379 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.057 | 0.380 | 0.418 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_DOOR | NONRESWINDOW_U_0.362_SHGC_0.379 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.057 | 0.380 | 0.418 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.362_SHGC_0.379 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.057 | 0.380 | 0.418 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.362_SHGC_0.379 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.057 | 0.380 | 0.418 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_DOOR | NONRESWINDOW_U_0.362_SHGC_0.379 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.057 | 0.380 | 0.418 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.362_SHGC_0.379 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.057 | 0.380 | 0.418 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.362_SHGC_0.379 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.057 | 0.380 | 0.418 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_DOOR | NONRESWINDOW_U_0.362_SHGC_0.379 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.057 | 0.380 | 0.418 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.362_SHGC_0.379 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.057 | 0.380 | 0.418 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.362_SHGC_0.379 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.057 | 0.380 | 0.418 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_DOOR | NONRESWINDOW_U_0.362_SHGC_0.379 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.057 | 0.380 | 0.418 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.362_SHGC_0.379 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.057 | 0.380 | 0.418 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.362_SHGC_0.379 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.057 | 0.380 | 0.418 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_3 | NONRESWINDOW_U_0.362_SHGC_0.379 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.057 | 0.380 | 0.418 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_4 | NONRESWINDOW_U_0.362_SHGC_0.379 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.057 | 0.380 | 0.418 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_DOOR_1 | NONRESWINDOW_U_0.362_SHGC_0.379 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.057 | 0.380 | 0.418 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_DOOR_2 | NONRESWINDOW_U_0.362_SHGC_0.379 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.057 | 0.380 | 0.418 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.362_SHGC_0.379 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.057 | 0.380 | 0.418 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.362_SHGC_0.379 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.057 | 0.380 | 0.418 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_DOOR | NONRESWINDOW_U_0.362_SHGC_0.379 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.057 | 0.380 | 0.418 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.362_SHGC_0.379 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.057 | 0.380 | 0.418 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.362_SHGC_0.379 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.057 | 0.380 | 0.418 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_DOOR | NONRESWINDOW_U_0.362_SHGC_0.379 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.057 | 0.380 | 0.418 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.362_SHGC_0.379 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.057 | 0.380 | 0.418 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.362_SHGC_0.379 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.057 | 0.380 | 0.418 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_DOOR | NONRESWINDOW_U_0.362_SHGC_0.379 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.057 | 0.380 | 0.418 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.362_SHGC_0.379 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.057 | 0.380 | 0.418 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.362_SHGC_0.379 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.057 | 0.380 | 0.418 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_DOOR | NONRESWINDOW_U_0.362_SHGC_0.379 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.057 | 0.380 | 0.418 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
Total or Average | 124.40 | 2.057 | 0.380 | 0.418 | |||||||||||||||||
North Total or Average | 0.00 | - | - | - | |||||||||||||||||
Non-North Total or Average | 124.40 | 2.057 | 0.380 | 0.418 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
LGSTORE1_WALL_3_DOOR_1 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.90 | LGSTORE1_WALL_3 |
LGSTORE1_WALL_3_DOOR_2 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.90 | LGSTORE1_WALL_3 |
SMSTORE1_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.90 | SMSTORE1_WALL_3 |
SMSTORE2_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE2_WALL_3 |
SMSTORE3_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE3_WALL_3 |
SMSTORE4_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE4_WALL_3 |
LGSTORE2_WALL_3_DOOR_1 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | LGSTORE2_WALL_3 |
LGSTORE2_WALL_3_DOOR_2 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | LGSTORE2_WALL_3 |
SMSTORE5_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE5_WALL_3 |
SMSTORE6_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE6_WALL_3 |
SMSTORE7_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE7_WALL_3 |
SMSTORE8_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE8_WALL_3 |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:59
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
LGSTORE1_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_DOOR_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_DOOR_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_DOOR_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_DOOR_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:59
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
LGSTORE1_LIGHTS | LGSTORE1 | LGSTORE1 | GENERAL | 9.6053 | 348.39 | 3346.35 | LightsWired | LTG_SCH_BASE_LPD1 | 83.91 | 168.00 | 82.62 | 0.0000 | Y | 51.90 |
LGSTORE1_LIGHTS_ALLOWANCE | LGSTORE1 | LGSTORE1 | GENERAL | 5.6969 | 348.39 | 1984.73 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | 97.50 | 112.00 | 94.53 | 0.0000 | Y | 35.22 |
SMSTORE1_LIGHTS | SMSTORE1 | SMSTORE1 | GENERAL | 9.7206 | 174.19 | 1693.26 | LightsWired | LTG_SCH_BASE_SMALL_LPD1 | 85.41 | 168.00 | 84.05 | 0.0000 | Y | 26.72 |
SMSTORE1_LIGHTS_ALLOWANCE | SMSTORE1 | SMSTORE1 | GENERAL | 8.5685 | 174.19 | 1492.57 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | 97.50 | 112.00 | 94.53 | 0.0000 | Y | 26.49 |
SMSTORE2_LIGHTS | SMSTORE2 | SMSTORE2 | GENERAL | 9.6995 | 174.19 | 1689.58 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 68.73 | 168.00 | 65.95 | 0.0000 | Y | 20.92 |
SMSTORE2_LIGHTS_ALLOWANCE | SMSTORE2 | SMSTORE2 | GENERAL | 6.9539 | 174.19 | 1211.32 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 84.29 | 73.25 | 0.0000 | Y | 16.66 |
SMSTORE3_LIGHTS | SMSTORE3 | SMSTORE3 | GENERAL | 9.6995 | 174.19 | 1689.58 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 68.73 | 168.00 | 65.95 | 0.0000 | Y | 20.92 |
SMSTORE3_LIGHTS_ALLOWANCE | SMSTORE3 | SMSTORE3 | GENERAL | 6.9539 | 174.19 | 1211.32 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 84.29 | 73.25 | 0.0000 | Y | 16.66 |
SMSTORE4_LIGHTS | SMSTORE4 | SMSTORE4 | GENERAL | 9.6995 | 174.19 | 1689.58 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 68.73 | 168.00 | 65.95 | 0.0000 | Y | 20.92 |
SMSTORE4_LIGHTS_ALLOWANCE | SMSTORE4 | SMSTORE4 | GENERAL | 6.9539 | 174.19 | 1211.32 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 84.29 | 73.25 | 0.0000 | Y | 16.66 |
LGSTORE2_LIGHTS | LGSTORE2 | LGSTORE2 | GENERAL | 9.5842 | 348.39 | 3339.00 | LightsWired | LTG_SCH_BASE_LPD2 | 62.11 | 168.00 | 59.29 | 0.0000 | Y | 37.16 |
LGSTORE2_LIGHTS_ALLOWANCE | LGSTORE2 | LGSTORE2 | GENERAL | 0.0000 | 348.39 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE5_LIGHTS | SMSTORE5 | SMSTORE5 | GENERAL | 9.6995 | 174.19 | 1689.58 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 60.29 | 0.0000 | Y | 19.12 |
SMSTORE5_LIGHTS_ALLOWANCE | SMSTORE5 | SMSTORE5 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE6_LIGHTS | SMSTORE6 | SMSTORE6 | GENERAL | 9.6995 | 174.19 | 1689.58 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 60.29 | 0.0000 | Y | 19.12 |
SMSTORE6_LIGHTS_ALLOWANCE | SMSTORE6 | SMSTORE6 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE7_LIGHTS | SMSTORE7 | SMSTORE7 | GENERAL | 9.6995 | 174.19 | 1689.58 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 60.29 | 0.0000 | Y | 19.12 |
SMSTORE7_LIGHTS_ALLOWANCE | SMSTORE7 | SMSTORE7 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE8_LIGHTS | SMSTORE8 | SMSTORE8 | GENERAL | 9.6995 | 174.19 | 1689.58 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 60.29 | 0.0000 | Y | 19.12 |
SMSTORE8_LIGHTS_ALLOWANCE | SMSTORE8 | SMSTORE8 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
Interior Lighting Total | 6.5342 | 4180.64 | 27316.92 | 366.68 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 455.59 | AstronomicalClock | - | 42.04 | 42.04 | 3.60 | |
EXTERIOR_LIGHTS_B | 2744.24 | AstronomicalClock | - | 83.67 | 62.85 | 32.38 | |
EXTERIOR_LIGHTS_C | 2307.23 | AstronomicalClock | - | 83.67 | 55.85 | 24.19 | |
Exterior Lighting Total | 5507.06 | 60.16 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:59
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 40181.26 | 30066.43 | 10114.83 | 0.75 | 3.73 | |||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 21420.44 | 16168.58 | 5251.86 | 0.75 | 3.80 | |||
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 21521.61 | 16252.69 | 5268.92 | 0.76 | 3.80 | |||
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 21580.24 | 16301.93 | 5278.31 | 0.76 | 3.80 | |||
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 21414.15 | 16161.69 | 5252.46 | 0.75 | 3.80 | |||
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 38591.68 | 28748.87 | 9842.81 | 0.74 | 3.80 | |||
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 19962.88 | 14888.72 | 5074.16 | 0.75 | 3.80 | |||
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 19866.44 | 14807.25 | 5059.19 | 0.75 | 3.80 | |||
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 19692.33 | 14668.23 | 5024.10 | 0.74 | 3.80 | |||
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 20616.94 | 15457.96 | 5158.98 | 0.75 | 3.80 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC_1:1 COOLING COIL | 38714.8 | 11.51 | 11.51 | ||||
PSZ-AC_2:2 COOLING COIL | 20623.6 | 11.64 | 11.64 | ||||
PSZ-AC_3:3 COOLING COIL | 20720.0 | 11.64 | 11.64 | ||||
PSZ-AC_4:4 COOLING COIL | 20775.8 | 11.64 | 11.64 | ||||
PSZ-AC_5:5 COOLING COIL | 20617.8 | 11.64 | 11.64 | ||||
PSZ-AC_6:6 COOLING COIL | 37194.7 | 11.70 | 11.70 | ||||
PSZ-AC_7:7 COOLING COIL | 19238.0 | 11.69 | 11.69 | ||||
PSZ-AC_8:8 COOLING COIL | 19146.3 | 11.70 | 11.70 | ||||
PSZ-AC_9:9 COOLING COIL | 18979.7 | 11.70 | 11.70 | ||||
PSZ-AC_10:10 COOLING COIL | 19860.6 | 11.67 | 11.67 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | 59694.63 | 0.80 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | 31272.07 | 0.80 | |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | 31367.96 | 0.80 | |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | 31242.14 | 0.80 | |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | 31172.14 | 0.80 | |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | 57721.90 | 0.80 | |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | 29453.43 | 0.80 | |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | 29309.82 | 0.80 | |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | 29066.94 | 0.80 | |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | 29916.79 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 1.86 | 1994.18 | 1070.05 | 1.00 | 1.33 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 |
PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.01 | 1121.56 | 1107.16 | 1.00 | 1.40 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 |
PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.02 | 1128.28 | 1107.16 | 1.00 | 1.40 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 |
PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.02 | 1132.25 | 1107.16 | 1.00 | 1.40 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 |
PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.01 | 1120.86 | 1107.16 | 1.00 | 1.40 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 |
PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 1.78 | 1899.53 | 1070.05 | 1.00 | 1.33 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.92 | 1019.85 | 1107.16 | 1.00 | 1.42 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 |
PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.92 | 1013.18 | 1107.16 | 1.00 | 1.43 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 |
PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.91 | 1002.60 | 1107.16 | 1.00 | 1.43 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 |
PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.96 | 1064.31 | 1107.16 | 1.00 | 1.41 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
GAS TANK1 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK2 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK3 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK4 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK5 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK6 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
GAS TANK7 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.73 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:59
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
LGSTORE1 | 20627.44 | 24752.93 | 71.05 | 1.553 | 1.864 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 23.89 | 23.89 | 0.00976 | 30.30 | 0.01337 | 0.411 | 0.00 |
SMSTORE1 | 11351.76 | 13622.11 | 78.20 | 0.830 | 0.996 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 23.89 | 23.89 | 0.00942 | 26.77 | 0.01336 | 0.206 | 0.00 |
SMSTORE2 | 11399.97 | 13679.96 | 78.53 | 0.833 | 1.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 23.89 | 23.89 | 0.00961 | 25.18 | 0.01336 | 0.206 | 0.00 |
SMSTORE3 | 11337.65 | 13605.18 | 78.10 | 0.829 | 0.994 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 23.89 | 23.89 | 0.00959 | 25.18 | 0.01336 | 0.206 | 0.00 |
SMSTORE4 | 11302.60 | 13563.12 | 77.86 | 0.826 | 0.991 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 23.89 | 23.89 | 0.00963 | 25.18 | 0.01336 | 0.206 | 0.00 |
LGSTORE2 | 19649.10 | 23578.92 | 67.68 | 1.479 | 1.775 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 23.89 | 23.89 | 0.00976 | 30.07 | 0.01337 | 0.411 | 0.00 |
SMSTORE5 | 10445.55 | 12534.66 | 71.96 | 0.762 | 0.914 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 23.89 | 23.88 | 0.00967 | 26.77 | 0.01336 | 0.206 | 0.00 |
SMSTORE6 | 10374.21 | 12449.05 | 71.47 | 0.756 | 0.908 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 23.89 | 23.88 | 0.00968 | 26.77 | 0.01336 | 0.206 | 0.00 |
SMSTORE7 | 10253.71 | 12304.46 | 70.64 | 0.747 | 0.897 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 23.89 | 23.88 | 0.00970 | 26.77 | 0.01336 | 0.206 | 0.00 |
SMSTORE8 | 10675.10 | 12810.12 | 73.54 | 0.779 | 0.935 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 23.89 | 23.88 | 0.00971 | 26.77 | 0.01336 | 0.206 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
LGSTORE1 | 27807.21 | 33368.66 | 95.78 | 1.229 | 1.475 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00655 | -16.30 | 0.00092 | 0.411 | 0.00 |
SMSTORE1 | 13109.85 | 15731.82 | 90.31 | 0.580 | 0.696 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00647 | -16.30 | 0.00092 | 0.206 | 0.00 |
SMSTORE2 | 13257.63 | 15909.15 | 91.33 | 0.586 | 0.703 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00649 | -16.30 | 0.00092 | 0.206 | 0.00 |
SMSTORE3 | 13337.19 | 16004.63 | 91.88 | 0.590 | 0.708 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00649 | -16.30 | 0.00092 | 0.206 | 0.00 |
SMSTORE4 | 13480.22 | 16176.27 | 92.86 | 0.596 | 0.715 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00650 | -16.30 | 0.00092 | 0.206 | 0.00 |
LGSTORE2 | 25808.85 | 30970.63 | 88.90 | 1.141 | 1.369 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00658 | -16.30 | 0.00092 | 0.411 | 0.00 |
SMSTORE5 | 13809.77 | 16571.72 | 95.13 | 0.611 | 0.733 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00653 | -16.30 | 0.00092 | 0.206 | 0.00 |
SMSTORE6 | 13797.67 | 16557.20 | 95.05 | 0.610 | 0.732 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00653 | -16.30 | 0.00092 | 0.206 | 0.00 |
SMSTORE7 | 14010.22 | 16812.26 | 96.52 | 0.619 | 0.743 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00654 | -16.30 | 0.00092 | 0.206 | 0.00 |
SMSTORE8 | 17211.28 | 20653.54 | 118.57 | 0.761 | 0.913 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00658 | -16.30 | 0.00092 | 0.206 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC_1:1 | 1.86 | 1.86 | 1.48 | 1.48 | 1.8636 | 1.8636 | 1.8636 | 1.0000 | 1.0000 |
PSZ-AC_2:2 | 1.01 | 1.01 | 0.70 | 0.70 | 1.0130 | 0.9958 | 1.0130 | 0.9830 | 1.0000 |
PSZ-AC_3:3 | 1.02 | 1.02 | 0.70 | 0.70 | 1.0191 | 1.0001 | 1.0191 | 0.9813 | 1.0000 |
PSZ-AC_4:4 | 1.02 | 1.02 | 0.71 | 0.71 | 1.0227 | 0.9944 | 1.0227 | 0.9724 | 1.0000 |
PSZ-AC_5:5 | 1.01 | 1.01 | 0.72 | 0.72 | 1.0124 | 0.9913 | 1.0124 | 0.9792 | 1.0000 |
PSZ-AC_6:6 | 1.78 | 1.78 | 1.37 | 1.37 | 1.7752 | 1.7752 | 1.7752 | 1.0000 | 1.0000 |
PSZ-AC_7:7 | 0.92 | 0.92 | 0.73 | 0.73 | 0.9211 | 0.9142 | 0.9211 | 0.9924 | 1.0000 |
PSZ-AC_8:8 | 0.92 | 0.92 | 0.73 | 0.73 | 0.9151 | 0.9077 | 0.9151 | 0.9919 | 1.0000 |
PSZ-AC_9:9 | 0.91 | 0.91 | 0.74 | 0.74 | 0.9056 | 0.8968 | 0.9056 | 0.9904 | 1.0000 |
PSZ-AC_10:10 | 0.96 | 0.96 | 0.91 | 0.91 | 0.9613 | 0.9349 | 0.9613 | 0.9725 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 40181.260 | 30066.431 | 1.863640 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 20090.63 | 14958.14 | 1.242427 | 26.19 | 18.54 | 0.01055716 | 12.80 | 11.87 | 0.00850000 | 30.30 | 0.01336696 | 21.83 | 33.1190 | 23.89 | 0.00976099 | 51.4757 | 20627.44 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_1:1 | 59694.628 | 59694.628 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 59694.63 | 59694.63 | 1.863639 | 12.85 | 8.52 | 0.00530660 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 22.0793 | 21.10 | 0.00654841 | 41.1040 | 27807.21 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 21420.440 | 16168.577 | 1.013010 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 10710.22 | 8091.42 | 0.675340 | 26.11 | 18.42 | 0.01043000 | 12.80 | 11.87 | 0.00850000 | 30.30 | 0.01336696 | 21.83 | 30.4646 | 23.89 | 0.00968078 | 51.0588 | 11204.10 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_2:2 | 31272.073 | 31272.073 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 31272.07 | 31272.07 | 1.013005 | 13.51 | 8.87 | 0.00534691 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 20.3098 | 21.10 | 0.00647411 | 40.6418 | 13109.85 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_3:3 | 21521.610 | 16252.689 | 1.019080 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 10760.81 | 8137.23 | 0.679387 | 26.10 | 18.41 | 0.01042175 | 12.80 | 11.87 | 0.00850000 | 30.30 | 0.01336696 | 21.83 | 30.2831 | 23.89 | 0.00967543 | 51.0310 | 11263.98 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_3:3 | 31367.957 | 31367.957 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 31367.96 | 31367.96 | 1.019076 | 13.55 | 8.90 | 0.00536314 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 20.1888 | 21.10 | 0.00648603 | 40.7159 | 13257.63 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_4:4 | 21580.240 | 16301.929 | 1.022670 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 10790.12 | 8164.21 | 0.681780 | 26.10 | 18.40 | 0.01041655 | 12.80 | 11.87 | 0.00850000 | 30.30 | 0.01336696 | 21.83 | 30.1768 | 23.89 | 0.00967206 | 51.0135 | 11301.98 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_4:4 | 31242.135 | 31242.135 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 31242.14 | 31242.14 | 1.022667 | 13.58 | 8.93 | 0.00537207 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 20.1179 | 21.10 | 0.00649228 | 40.7547 | 13337.19 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_5:5 | 21414.150 | 16161.687 | 1.012380 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 10707.08 | 8087.10 | 0.674920 | 26.11 | 18.42 | 0.01043212 | 12.80 | 11.87 | 0.00850000 | 30.30 | 0.01336696 | 21.83 | 30.4835 | 23.89 | 0.00968216 | 51.0659 | 11188.85 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_5:5 | 31172.144 | 31172.144 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 31172.14 | 31172.14 | 1.012379 | 13.50 | 8.89 | 0.00536967 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 20.3224 | 21.10 | 0.00650355 | 40.8248 | 13480.22 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_6:6 | 38591.680 | 28748.872 | 1.775180 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 19295.84 | 14302.94 | 1.183453 | 26.26 | 18.60 | 0.01060298 | 12.80 | 11.87 | 0.00850000 | 30.30 | 0.01336696 | 21.83 | 34.7693 | 23.89 | 0.00976725 | 51.5076 | 19617.28 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_6:6 | 57721.902 | 57721.902 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 57721.90 | 57721.90 | 1.775182 | 12.44 | 8.29 | 0.00526783 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 23.1795 | 21.10 | 0.00657849 | 41.2892 | 25808.85 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_7:7 | 19962.880 | 14888.715 | 0.921140 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | 9981.44 | 7406.35 | 0.614093 | 26.25 | 18.59 | 0.01059251 | 12.80 | 11.87 | 0.00850000 | 30.30 | 0.01336696 | 21.83 | 33.5030 | 23.89 | 0.00978692 | 51.6098 | 10120.02 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_7:7 | 29453.425 | 29453.425 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 29453.43 | 29453.43 | 0.921140 | 12.75 | 8.44 | 0.00527701 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 22.3353 | 21.10 | 0.00652885 | 40.9819 | 13809.77 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_8:8 | 19866.440 | 14807.252 | 0.915110 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | 9933.22 | 7361.40 | 0.610073 | 26.26 | 18.60 | 0.01060402 | 12.80 | 11.87 | 0.00850000 | 30.30 | 0.01336696 | 21.83 | 33.7237 | 23.89 | 0.00979448 | 51.6491 | 10049.48 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_8:8 | 29309.818 | 29309.818 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 29309.82 | 29309.82 | 0.915113 | 12.70 | 8.41 | 0.00526808 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 22.4824 | 21.10 | 0.00652797 | 40.9764 | 13797.67 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_9:9 | 19692.330 | 14668.226 | 0.905560 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | 9846.17 | 7287.98 | 0.603707 | 26.27 | 18.61 | 0.01061533 | 12.80 | 11.87 | 0.00850000 | 30.30 | 0.01336696 | 21.83 | 34.0794 | 23.89 | 0.00980193 | 51.6877 | 9980.88 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_9:9 | 29066.942 | 29066.942 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 29066.94 | 29066.94 | 0.905562 | 12.61 | 8.36 | 0.00526687 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 22.7195 | 21.10 | 0.00654360 | 41.0736 | 14010.22 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_10:10 | 20616.940 | 15457.963 | 0.961300 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | 10308.47 | 7643.79 | 0.640867 | 26.10 | 18.53 | 0.01057716 | 12.80 | 11.87 | 0.00850000 | 29.91 | 0.01336627 | 21.72 | 32.1033 | 23.89 | 0.00981629 | 51.7631 | 10625.23 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_10:10 | 29916.792 | 29916.792 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 29916.79 | 29916.79 | 0.961301 | 13.10 | 8.71 | 0.00537013 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 21.4022 | 21.10 | 0.00658078 | 41.3076 | 17211.28 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:36:59
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 40181.260 | 30066.431 | 1.863640 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.4652 | 1004.8586 | 1.1739 | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.863639 | 2.18777244 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | Sensible | 20090.63 | 14958.14 | 1.0000 | 1.45851611 | 1.242427 | 26.19 | 18.54 | 0.01055716 | 53235.1 | 12.80 | 11.87 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 20090.63 | 30.30 | 0.01336696 | 21.83 | 0.41147883 | 33.1190 | 23.89 | 0.00976099 | 23.89 | 0.00976099 | 51.4757 | 20627.44 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 59694.628 | 59694.628 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.863639 | 2.18777244 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 59694.63 | 59694.63 | 1.0000 | 2.18777244 | 1.863639 | 12.85 | 8.52 | 0.00530660 | 26306.7 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 59694.63 | -16.30 | 0.00092409 | -16.30 | 0.41147883 | 22.0793 | 21.11 | 0.00654841 | 21.10 | 0.00654841 | 41.1040 | 27807.21 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 21420.440 | 16168.577 | 1.013010 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.2288 | 1004.8586 | 1.1739 | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.013005 | 1.18919253 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | Sensible | 10710.22 | 8091.42 | 1.0000 | 0.79279872 | 0.675340 | 26.11 | 18.42 | 0.01043000 | 52827.5 | 12.80 | 11.87 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10710.22 | 30.30 | 0.01336696 | 21.83 | 0.20573941 | 30.4646 | 23.89 | 0.00968078 | 23.89 | 0.00968078 | 51.0588 | 11204.10 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 31272.073 | 31272.073 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.013005 | 1.18919253 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 31272.07 | 31272.07 | 1.0000 | 1.18919253 | 1.013005 | 13.51 | 8.87 | 0.00534691 | 27080.5 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 31272.07 | -16.30 | 0.00092409 | -16.30 | 0.20573941 | 20.3098 | 21.11 | 0.00647411 | 21.10 | 0.00647411 | 40.6418 | 13109.85 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 21521.610 | 16252.689 | 1.019080 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.2135 | 1004.8586 | 1.1739 | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.019076 | 1.19631906 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | Sensible | 10760.81 | 8137.23 | 1.0000 | 0.79754921 | 0.679387 | 26.10 | 18.41 | 0.01042175 | 52799.4 | 12.80 | 11.87 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10760.81 | 30.30 | 0.01336696 | 21.83 | 0.20573941 | 30.2831 | 23.89 | 0.00967543 | 23.89 | 0.00967543 | 51.0310 | 11263.98 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 31367.957 | 31367.957 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.019076 | 1.19631906 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 31367.96 | 31367.96 | 1.0000 | 1.19631906 | 1.019076 | 13.55 | 8.90 | 0.00536314 | 27167.5 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 31367.96 | -16.30 | 0.00092409 | -16.30 | 0.20573941 | 20.1888 | 21.11 | 0.00648603 | 21.10 | 0.00648603 | 40.7159 | 13257.63 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 21580.240 | 16301.929 | 1.022670 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.2038 | 1004.8586 | 1.1739 | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.022667 | 1.20053461 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | Sensible | 10790.12 | 8164.21 | 1.0000 | 0.80035880 | 0.681780 | 26.10 | 18.40 | 0.01041655 | 52781.7 | 12.80 | 11.87 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10790.12 | 30.30 | 0.01336696 | 21.83 | 0.20573941 | 30.1768 | 23.89 | 0.00967206 | 23.89 | 0.00967206 | 51.0135 | 11301.98 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 31242.135 | 31242.135 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.022667 | 1.20053461 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 31242.14 | 31242.14 | 1.0000 | 1.20053461 | 1.022667 | 13.58 | 8.93 | 0.00537207 | 27216.9 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 31242.14 | -16.30 | 0.00092409 | -16.30 | 0.20573941 | 20.1179 | 21.11 | 0.00649228 | 21.10 | 0.00649228 | 40.7547 | 13337.19 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 21414.150 | 16161.687 | 1.012380 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.2328 | 1004.8586 | 1.1739 | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.012379 | 1.18845760 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | Sensible | 10707.08 | 8087.10 | 1.0000 | 0.79230567 | 0.674920 | 26.11 | 18.42 | 0.01043212 | 52834.7 | 12.80 | 11.87 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10707.08 | 30.30 | 0.01336696 | 21.83 | 0.20573941 | 30.4835 | 23.89 | 0.00968216 | 23.89 | 0.00968216 | 51.0659 | 11188.85 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 31172.144 | 31172.144 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.012379 | 1.18845760 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 31172.14 | 31172.14 | 1.0000 | 1.18845760 | 1.012379 | 13.50 | 8.89 | 0.00536967 | 27133.3 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 31172.14 | -16.30 | 0.00092409 | -16.30 | 0.20573941 | 20.3224 | 21.11 | 0.00650355 | 21.10 | 0.00650355 | 40.8248 | 13480.22 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 38591.680 | 28748.872 | 1.775180 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.5504 | 1004.8586 | 1.1739 | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.775182 | 2.08393143 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | Sensible | 19295.84 | 14302.94 | 1.0000 | 1.38928583 | 1.183453 | 26.26 | 18.60 | 0.01060298 | 53426.7 | 12.80 | 11.87 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 19295.84 | 30.30 | 0.01336696 | 21.83 | 0.41147883 | 34.7693 | 23.89 | 0.00976725 | 23.89 | 0.00976725 | 51.5076 | 19617.28 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 57721.902 | 57721.902 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.775182 | 2.08393143 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 57721.90 | 57721.90 | 1.0000 | 2.08393143 | 1.775182 | 12.44 | 8.29 | 0.00526783 | 25791.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 57721.90 | -16.30 | 0.00092409 | -16.30 | 0.41147883 | 23.1795 | 21.11 | 0.00657849 | 21.10 | 0.00657849 | 41.2892 | 25808.85 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 19962.880 | 14888.715 | 0.921140 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.5309 | 1004.8586 | 1.1739 | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.921140 | 1.08134951 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | Sensible | 9981.44 | 7406.35 | 1.0000 | 0.72089971 | 0.614093 | 26.25 | 18.59 | 0.01059251 | 53384.7 | 12.80 | 11.87 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9981.44 | 30.30 | 0.01336696 | 21.83 | 0.20573941 | 33.5030 | 23.89 | 0.00978692 | 23.89 | 0.00978692 | 51.6098 | 10120.02 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 29453.425 | 29453.425 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.921140 | 1.08134951 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 29453.43 | 29453.43 | 1.0000 | 1.08134951 | 0.921140 | 12.75 | 8.44 | 0.00527701 | 26135.2 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 29453.43 | -16.30 | 0.00092409 | -16.30 | 0.20573941 | 22.3353 | 21.11 | 0.00652885 | 21.10 | 0.00652885 | 40.9819 | 13809.77 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 19866.440 | 14807.252 | 0.915110 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.5523 | 1004.8586 | 1.1739 | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.915113 | 1.07427452 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | Sensible | 9933.22 | 7361.40 | 1.0000 | 0.71618053 | 0.610073 | 26.26 | 18.60 | 0.01060402 | 53424.4 | 12.80 | 11.87 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9933.22 | 30.30 | 0.01336696 | 21.83 | 0.20573941 | 33.7237 | 23.89 | 0.00979448 | 23.89 | 0.00979448 | 51.6491 | 10049.48 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 29309.818 | 29309.818 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.915113 | 1.07427452 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 29309.82 | 29309.82 | 1.0000 | 1.07427452 | 0.915113 | 12.70 | 8.41 | 0.00526808 | 26056.9 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 29309.82 | -16.30 | 0.00092409 | -16.30 | 0.20573941 | 22.4824 | 21.11 | 0.00652797 | 21.10 | 0.00652797 | 40.9764 | 13797.67 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 19692.330 | 14668.226 | 0.905560 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.5734 | 1004.8586 | 1.1739 | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.905562 | 1.06306183 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | Sensible | 9846.17 | 7287.98 | 1.0000 | 0.70870654 | 0.603707 | 26.27 | 18.61 | 0.01061533 | 53463.4 | 12.80 | 11.87 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9846.17 | 30.30 | 0.01336696 | 21.83 | 0.20573941 | 34.0794 | 23.89 | 0.00980193 | 23.89 | 0.00980193 | 51.6877 | 9980.88 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 29066.942 | 29066.942 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.905562 | 1.06306183 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 29066.94 | 29066.94 | 1.0000 | 1.06306183 | 0.905562 | 12.61 | 8.36 | 0.00526687 | 25963.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 29066.94 | -16.30 | 0.00092409 | -16.30 | 0.20573941 | 22.7195 | 21.11 | 0.00654360 | 21.10 | 0.00654360 | 41.0736 | 14010.22 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 20616.940 | 15457.963 | 0.961300 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.5024 | 1004.8586 | 1.1739 | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.961301 | 1.12849608 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | Sensible | 10308.47 | 7643.79 | 1.0000 | 0.75232960 | 0.640867 | 26.10 | 18.53 | 0.01057716 | 53190.4 | 12.80 | 11.87 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10308.47 | 29.91 | 0.01336627 | 21.72 | 0.20573941 | 32.1033 | 23.89 | 0.00981629 | 23.89 | 0.00981629 | 51.7631 | 10625.23 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 29916.792 | 29916.792 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.961301 | 1.12849608 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 29916.79 | 29916.79 | 1.0000 | 1.12849608 | 0.961301 | 13.10 | 8.71 | 0.00537013 | 26723.6 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 29916.79 | -16.30 | 0.00092409 | -16.30 | 0.20573941 | 21.4022 | 21.10 | 0.00658078 | 21.10 | 0.00658078 | 41.3076 | 17211.28 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:59
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-AC_1:1_OA_CONTROLLER | DifferentialDryBulb | 0.41 | 1.86 | - | |||
PSZ-AC_2:2_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.01 | - | |||
PSZ-AC_3:3_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.02 | - | |||
PSZ-AC_4:4_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.02 | - | |||
PSZ-AC_5:5_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.01 | - | |||
PSZ-AC_6:6_OA_CONTROLLER | DifferentialDryBulb | 0.41 | 1.78 | - | |||
PSZ-AC_7:7_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 0.92 | - | |||
PSZ-AC_8:8_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 0.92 | - | |||
PSZ-AC_9:9_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 0.91 | - | |||
PSZ-AC_10:10_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 0.96 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
LGSTORE1 | 3118.67 | 4151.67 | 1985.50 |
SMSTORE1 | 2408.50 | 3762.50 | 1127.50 |
SMSTORE2 | 2129.83 | 2992.83 | 1169.17 |
SMSTORE3 | 2183.67 | 3020.67 | 1238.83 |
SMSTORE4 | 2237.17 | 3083.33 | 1334.33 |
LGSTORE2 | 2209.00 | 2961.50 | 1497.00 |
SMSTORE5 | 2171.83 | 2989.67 | 1514.67 |
SMSTORE6 | 2179.00 | 3011.33 | 1537.33 |
SMSTORE7 | 2225.67 | 3063.67 | 1616.67 |
SMSTORE8 | 2469.83 | 3149.83 | 1893.50 |
Facility | 3829.17 | 4612.17 | 2652.83 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
LGSTORE1 | 15.17 | 0.00 | 5.67 | 0.00 |
SMSTORE1 | 2.83 | 0.00 | 0.33 | 0.00 |
SMSTORE2 | 1.17 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 2.50 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 3.33 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 8.33 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 8.17 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 8.50 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 12.50 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 45.83 | 0.00 | 0.00 | 0.00 |
Facility | 58.17 | 0.00 | 5.67 | 0.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:59
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
LGSTORE1 | 16.93 | 56.25 | 1805.20 | 0.994 | 0.241 | 0.000 | 0.000 |
SMSTORE1 | 8.46 | 28.12 | 902.60 | 0.865 | 0.252 | 0.000 | 0.000 |
SMSTORE2 | 7.08 | 28.12 | 902.60 | 1.047 | 0.328 | 0.000 | 0.000 |
SMSTORE3 | 7.08 | 28.12 | 902.60 | 1.045 | 0.328 | 0.000 | 0.000 |
SMSTORE4 | 7.08 | 28.12 | 902.60 | 1.032 | 0.328 | 0.000 | 0.000 |
LGSTORE2 | 24.77 | 56.25 | 1805.20 | 0.990 | 0.315 | 0.000 | 0.000 |
SMSTORE5 | 12.39 | 28.12 | 902.60 | 0.997 | 0.350 | 0.000 | 0.000 |
SMSTORE6 | 12.39 | 28.12 | 902.60 | 0.992 | 0.350 | 0.000 | 0.000 |
SMSTORE7 | 12.39 | 28.12 | 902.60 | 0.981 | 0.350 | 0.000 | 0.000 |
SMSTORE8 | 12.39 | 28.12 | 902.60 | 0.984 | 0.377 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
LGSTORE1 | 16.93 | 56.25 | 1805.20 | 0.000 | 0.000 | 0.000 | 0.000 |
SMSTORE1 | 8.46 | 28.12 | 902.60 | 0.000 | 0.000 | 0.000 | 0.000 |
SMSTORE2 | 7.08 | 28.12 | 902.60 | 0.797 | 0.000 | 0.000 | 0.000 |
SMSTORE3 | 7.08 | 28.12 | 902.60 | 0.797 | 0.000 | 0.000 | 0.000 |
SMSTORE4 | 7.08 | 28.12 | 902.60 | 0.797 | 0.000 | 0.000 | 0.000 |
LGSTORE2 | 24.77 | 56.25 | 1805.20 | 0.798 | 0.000 | 0.000 | 0.000 |
SMSTORE5 | 12.39 | 28.12 | 902.60 | 0.798 | 0.000 | 0.000 | 0.000 |
SMSTORE6 | 12.39 | 28.12 | 902.60 | 0.798 | 0.000 | 0.000 | 0.000 |
SMSTORE7 | 12.39 | 28.12 | 902.60 | 0.798 | 0.000 | 0.000 | 0.000 |
SMSTORE8 | 12.39 | 28.12 | 902.60 | 0.798 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:36:59
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
LGSTORE1 | PSZ-AC_1:1 | 16.93 | 56.25 | 1805.20 | 348.39 | 0.4115 | 0.411 |
SMSTORE1 | PSZ-AC_2:2 | 8.46 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE2 | PSZ-AC_3:3 | 7.08 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE3 | PSZ-AC_4:4 | 7.08 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE4 | PSZ-AC_5:5 | 7.08 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
LGSTORE2 | PSZ-AC_6:6 | 24.77 | 56.25 | 1805.20 | 348.39 | 0.4115 | 0.411 |
SMSTORE5 | PSZ-AC_7:7 | 12.39 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE6 | PSZ-AC_8:8 | 12.39 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE7 | PSZ-AC_9:9 | 12.39 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE8 | PSZ-AC_10:10 | 12.39 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
Total Facility | 120.95 | 337.50 | 10831.20 | 2090.32 | 2.4689 | 2.469 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
LGSTORE1 | 10340303.65 | 0.00 | 10340303.65 | 2993858.48 | 13334162.13 | 12976396.34 | 3152.54 | 4276.92 | 1330.54 | 21.66 |
SMSTORE1 | 4502835.03 | 0.00 | 4502835.03 | 1454836.47 | 5957671.50 | 6488198.17 | 4333.66 | 3088.53 | 1337.81 | 26.49 |
SMSTORE2 | 4158541.63 | 0.00 | 4158541.63 | 1502250.16 | 5660791.79 | 6488198.17 | 4326.87 | 3474.75 | 958.38 | 92.15 |
SMSTORE3 | 4147239.58 | 0.00 | 4147239.58 | 1502250.16 | 5649489.74 | 6488198.17 | 4326.89 | 3492.42 | 940.69 | 89.81 |
SMSTORE4 | 4092749.15 | 0.00 | 4092749.15 | 1502250.16 | 5594999.31 | 6488198.17 | 4330.06 | 3529.00 | 900.94 | 85.76 |
LGSTORE2 | 7193397.18 | 0.00 | 7193397.18 | 2777494.96 | 9970892.14 | 12976396.34 | 4698.99 | 3257.33 | 803.68 | 72.26 |
SMSTORE5 | 3625538.05 | 0.00 | 3625538.05 | 1515968.53 | 5141506.58 | 6488198.17 | 4698.21 | 3269.08 | 792.71 | 71.18 |
SMSTORE6 | 3604830.18 | 0.00 | 3604830.18 | 1515968.53 | 5120798.71 | 6488198.17 | 4699.64 | 3285.17 | 775.19 | 69.82 |
SMSTORE7 | 3557585.65 | 0.00 | 3557585.65 | 1515968.53 | 5073554.18 | 6488198.17 | 4703.80 | 3328.33 | 727.87 | 62.40 |
SMSTORE8 | 3554866.01 | 0.00 | 3554866.01 | 1946294.26 | 5501160.27 | 6488198.17 | 4713.34 | 3392.58 | 654.08 | 44.47 |
Total Facility | 48777886.13 | 0.00 | 48777886.13 | 18227140.23 | 67005026.35 | 77858378.04 | 4714.84 | 4822.11 | 1586.04 | 184.55 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
LGSTORE1 | 0.4903 | 0.0000 | 0.4903 | 0.1189 | 0.6092 | 0.4115 | 241.70 | 4276.92 | 1321.39 |
SMSTORE1 | 0.2131 | 0.0000 | 0.2131 | 0.0623 | 0.2754 | 0.2057 | 1427.23 | 3088.53 | 1324.24 |
SMSTORE2 | 0.2583 | 0.0000 | 0.2583 | 0.0811 | 0.3394 | 0.2057 | 0.00 | 3474.33 | 920.67 |
SMSTORE3 | 0.2577 | 0.0000 | 0.2577 | 0.0811 | 0.3387 | 0.2057 | 0.00 | 3491.92 | 903.08 |
SMSTORE4 | 0.2546 | 0.0000 | 0.2546 | 0.0811 | 0.3357 | 0.2057 | 0.00 | 3528.67 | 866.33 |
LGSTORE2 | 0.4883 | 0.0000 | 0.4883 | 0.1559 | 0.6442 | 0.4115 | 0.00 | 3256.67 | 773.33 |
SMSTORE5 | 0.2461 | 0.0000 | 0.2461 | 0.0864 | 0.3325 | 0.2057 | 0.00 | 3268.58 | 761.42 |
SMSTORE6 | 0.2448 | 0.0000 | 0.2448 | 0.0864 | 0.3312 | 0.2057 | 0.00 | 3284.83 | 745.17 |
SMSTORE7 | 0.2421 | 0.0000 | 0.2421 | 0.0864 | 0.3285 | 0.2057 | 0.00 | 3327.83 | 702.17 |
SMSTORE8 | 0.2428 | 0.0000 | 0.2428 | 0.0931 | 0.3359 | 0.2057 | 0.00 | 3392.33 | 637.67 |
Total Facility | 2.9380 | 0.0000 | 2.9380 | 0.9327 | 3.8707 | 2.4689 | 1529.24 | 4819.11 | 1555.49 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-AC_1:1 | 14250427.25 | 0.00 | 14250427.25 | 12976396.34 | 3145.79 | 0.50 | 5613.71 | 21.66 |
PSZ-AC_2:2 | 6205506.91 | 0.00 | 6205506.91 | 6488198.17 | 4276.14 | 2.59 | 4481.27 | 26.49 |
PSZ-AC_3:3 | 5731057.30 | 0.00 | 5731057.30 | 6488198.17 | 4319.92 | 0.58 | 4439.49 | 91.99 |
PSZ-AC_4:4 | 5715476.92 | 0.00 | 5715476.92 | 6488198.17 | 4320.89 | 0.33 | 4438.77 | 89.47 |
PSZ-AC_5:5 | 5640383.23 | 0.00 | 5640383.23 | 6488198.17 | 4323.31 | 0.92 | 4435.78 | 85.76 |
PSZ-AC_6:6 | 9913570.45 | 0.00 | 9913570.45 | 12976396.34 | 4691.91 | 0.33 | 4067.76 | 72.26 |
PSZ-AC_7:7 | 4996510.04 | 0.00 | 4996510.04 | 6488198.17 | 4691.62 | 0.00 | 4068.38 | 71.10 |
PSZ-AC_8:8 | 4967969.58 | 0.00 | 4967969.58 | 6488198.17 | 4692.69 | 0.67 | 4066.64 | 69.82 |
PSZ-AC_9:9 | 4902845.88 | 0.00 | 4902845.88 | 6488198.17 | 4699.16 | 0.33 | 4060.51 | 62.24 |
PSZ-AC_10:10 | 4899024.89 | 0.00 | 4899024.89 | 6488198.17 | 4709.41 | 0.06 | 4050.54 | 44.47 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-AC_1:1 | 0.6757 | 0.0000 | 0.6757 | 0.4115 | 237.11 | 0.00 | 5602.89 |
PSZ-AC_2:2 | 0.2937 | 0.0000 | 0.2937 | 0.2057 | 1371.80 | 2.42 | 4465.78 |
PSZ-AC_3:3 | 0.3560 | 0.0000 | 0.3560 | 0.2057 | 0.00 | 0.00 | 4395.00 |
PSZ-AC_4:4 | 0.3551 | 0.0000 | 0.3551 | 0.2057 | 0.00 | 0.00 | 4395.00 |
PSZ-AC_5:5 | 0.3509 | 0.0000 | 0.3509 | 0.2057 | 0.00 | 0.00 | 4395.00 |
PSZ-AC_6:6 | 0.6730 | 0.0000 | 0.6730 | 0.4115 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_7:7 | 0.3391 | 0.0000 | 0.3391 | 0.2057 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_8:8 | 0.3374 | 0.0000 | 0.3374 | 0.2057 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_9:9 | 0.3336 | 0.0000 | 0.3336 | 0.2057 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_10:10 | 0.3346 | 0.0000 | 0.3346 | 0.2057 | 0.00 | 0.00 | 4030.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-AC_1:1 | 0.00 | 5162.99 | 490.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_2:2 | 0.00 | 4108.32 | 778.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_3:3 | 0.00 | 4115.89 | 371.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_4:4 | 0.00 | 4121.97 | 362.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_5:5 | 0.00 | 4135.29 | 345.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_6:6 | 0.00 | 3826.53 | 275.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_7:7 | 0.00 | 3826.24 | 274.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_8:8 | 0.00 | 3832.24 | 267.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_9:9 | 0.00 | 3848.60 | 243.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_10:10 | 0.00 | 3859.90 | 214.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-AC_1:1 | 0.0000 | 0.6880 | 0.8405 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_2:2 | 0.0000 | 0.3507 | 0.3648 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_3:3 | 0.0000 | 0.3465 | 0.4891 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_4:4 | 0.0000 | 0.3457 | 0.4896 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_5:5 | 0.0000 | 0.3422 | 0.4842 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_6:6 | 0.0000 | 0.6610 | 0.8833 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_7:7 | 0.0000 | 0.3328 | 0.4512 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_8:8 | 0.0000 | 0.3314 | 0.4481 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_9:9 | 0.0000 | 0.3280 | 0.4476 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_10:10 | 0.0000 | 0.3282 | 0.4760 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:59
Surfaces by ClassTotal | Outdoors | |
Wall | 40 | 22 |
Floor | 10 | 10 |
Roof | 10 | 10 |
Internal Mass | 10 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 36 | 36 |
Door | 12 | 12 |
Glass Door | 12 | 12 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 10 |
Conditioned Zones | 10 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 830 |
Defaulted Fields | 823 |
Fields with Defaults | 2682 |
Autosized Fields | 184 |
Autosizable Fields | 458 |
Autocalculated Fields | 128 |
Autocalculatable Fields | 256 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:36:59
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 781.62 | 2102.83 | 08-JAN-08:00 | 80911.64 | 15-JUL-14:20 |
Electricity:Building | 494.83 | 891.83 | 01-JAN-00:20 | 31518.67 | 01-JAN-11:10 |
Electricity:Zone:LGSTORE1 | 113.36 | 148.64 | 01-JAN-00:20 | 5964.88 | 01-JAN-10:10 |
Electricity:SpaceType:GENERAL | 494.83 | 891.83 | 01-JAN-00:20 | 31518.67 | 01-JAN-11:10 |
InteriorLights:Electricity | 366.68 | 450.00 | 01-JAN-00:20 | 23459.17 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:LGSTORE1 | 87.12 | 75.00 | 01-JAN-00:20 | 4621.63 | 01-JAN-10:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 366.68 | 450.00 | 01-JAN-00:20 | 23459.17 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity | 366.68 | 450.00 | 01-JAN-00:20 | 23459.17 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:LGSTORE1 | 87.12 | 75.00 | 01-JAN-00:20 | 4621.63 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 366.68 | 450.00 | 01-JAN-00:20 | 23459.17 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE1 | 66.33 | 74.32 | 01-JAN-00:20 | 3498.69 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE1 | 53.20 | 37.50 | 01-JAN-00:20 | 2827.07 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE1 | 53.20 | 37.50 | 01-JAN-00:20 | 2827.07 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE2 | 47.99 | 74.32 | 01-JAN-00:10 | 3226.84 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE2 | 37.57 | 37.50 | 01-JAN-00:10 | 2555.22 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE2 | 37.57 | 37.50 | 01-JAN-00:10 | 2555.22 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE3 | 47.99 | 74.32 | 01-JAN-00:10 | 3226.84 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE3 | 37.57 | 37.50 | 01-JAN-00:10 | 2555.22 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE3 | 37.57 | 37.50 | 01-JAN-00:10 | 2555.22 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE4 | 47.99 | 74.32 | 01-JAN-00:10 | 3226.84 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE4 | 37.57 | 37.50 | 01-JAN-00:10 | 2555.22 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE4 | 37.57 | 37.50 | 01-JAN-00:10 | 2555.22 | 01-JAN-10:10 |
Electricity:Zone:LGSTORE2 | 56.34 | 148.64 | 01-JAN-00:10 | 4070.21 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:LGSTORE2 | 37.16 | 75.00 | 01-JAN-00:10 | 2726.96 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:LGSTORE2 | 37.16 | 75.00 | 01-JAN-00:10 | 2726.96 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE5 | 28.71 | 74.32 | 01-JAN-00:10 | 2076.09 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE5 | 19.12 | 37.50 | 01-JAN-00:10 | 1404.46 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE5 | 19.12 | 37.50 | 01-JAN-00:10 | 1404.46 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE6 | 28.71 | 74.32 | 01-JAN-00:10 | 2076.09 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE6 | 19.12 | 37.50 | 01-JAN-00:10 | 1404.46 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE6 | 19.12 | 37.50 | 01-JAN-00:10 | 1404.46 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE7 | 28.71 | 74.32 | 01-JAN-00:10 | 2076.09 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE7 | 19.12 | 37.50 | 01-JAN-00:10 | 1404.46 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE7 | 19.12 | 37.50 | 01-JAN-00:10 | 1404.46 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE8 | 28.71 | 74.32 | 01-JAN-00:10 | 2076.09 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE8 | 19.12 | 37.50 | 01-JAN-00:10 | 1404.46 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE8 | 19.12 | 37.50 | 01-JAN-00:10 | 1404.46 | 01-JAN-11:10 |
InteriorEquipment:Electricity | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:LGSTORE1 | 26.25 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-10:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LGSTORE1 | 26.25 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 128.15 | 441.83 | 01-JAN-00:10 | 8059.50 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE1 | 13.12 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE1 | 13.12 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE2 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE2 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE3 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE3 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE4 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE4 | 10.42 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:LGSTORE2 | 19.17 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LGSTORE2 | 19.17 | 73.64 | 01-JAN-00:10 | 1343.25 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE5 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE5 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE6 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE6 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE7 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE7 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE8 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE8 | 9.59 | 36.82 | 01-JAN-00:10 | 671.63 | 01-JAN-11:10 |
ElectricityPurchased:Facility | 781.62 | 2102.83 | 08-JAN-08:00 | 80911.64 | 15-JUL-14:20 |
ElectricityPurchased:Plant | 781.62 | 2102.83 | 08-JAN-08:00 | 80911.64 | 15-JUL-14:20 |
Cogeneration:ElectricityPurchased | 781.62 | 2102.83 | 08-JAN-08:00 | 80911.64 | 15-JUL-14:20 |
General:Cogeneration:ElectricityPurchased | 781.62 | 2102.83 | 08-JAN-08:00 | 80911.64 | 15-JUL-14:20 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 781.62 | 2102.83 | 08-JAN-08:00 | 80911.64 | 15-JUL-14:20 |
ElectricityNet:Plant | 781.62 | 2102.83 | 08-JAN-08:00 | 80911.64 | 15-JUL-14:20 |
Cogeneration:ElectricityNet | 781.62 | 2102.83 | 08-JAN-08:00 | 80911.64 | 15-JUL-14:20 |
General:Cogeneration:ElectricityNet | 781.62 | 2102.83 | 08-JAN-08:00 | 80911.64 | 15-JUL-14:20 |
Electricity:HVAC | 161.51 | 0.00 | 01-JAN-00:10 | 43236.35 | 15-JUL-14:00 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 63.40 | 0.00 | 01-JAN-00:10 | 36777.71 | 15-JUL-14:00 |
General:Cooling:Electricity | 63.40 | 0.00 | 01-JAN-00:10 | 36777.71 | 15-JUL-14:00 |
Fans:Electricity | 98.12 | 0.00 | 01-JAN-00:10 | 9145.54 | 06-FEB-12:10 |
General:Fans:Electricity | 98.12 | 0.00 | 01-JAN-00:10 | 9145.54 | 06-FEB-12:10 |
ExteriorLights:Electricity | 60.16 | 0.00 | 01-JAN-08:00 | 5507.06 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 60.16 | 0.00 | 01-JAN-08:00 | 5507.06 | 01-JAN-06:10 |
Electricity:Plant | 65.11 | 1211.00 | 06-JAN-00:20 | 12298.30 | 07-JAN-15:50 |
WaterSystems:Electricity | 65.11 | 1211.00 | 06-JAN-00:20 | 12298.30 | 07-JAN-15:50 |
Water Heater:WaterSystems:Electricity | 65.11 | 1211.00 | 06-JAN-00:20 | 12298.30 | 07-JAN-15:50 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 712.17 | 0.00 | 01-JAN-00:10 | 249234.25 | 06-FEB-12:10 |
NaturalGas:HVAC | 712.17 | 0.00 | 01-JAN-00:10 | 249234.25 | 06-FEB-12:10 |
Heating:NaturalGas | 712.17 | 0.00 | 01-JAN-00:10 | 249234.25 | 06-FEB-12:10 |
General:Heating:NaturalGas | 712.17 | 0.00 | 01-JAN-00:10 | 249234.25 | 06-FEB-12:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water:Plant | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
WaterSystems:Water | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water Heater:WaterSystems:Water | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
MainsWater:Facility | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
MainsWater:Plant | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
WaterSystems:MainsWater | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water Heater:WaterSystems:MainsWater | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 1316.98 | 0.00 | 01-JAN-00:10 | 366570.51 | 07-FEB-08:10 |
EnergyTransfer:Building | 489.71 | 0.00 | 01-JAN-00:10 | 171741.13 | 07-FEB-08:10 |
EnergyTransfer:Zone:LGSTORE1 | 96.56 | 0.00 | 01-JAN-00:10 | 33781.88 | 06-FEB-08:10 |
Heating:EnergyTransfer | 200.10 | 0.00 | 01-JAN-00:10 | 171741.13 | 07-FEB-08:10 |
Heating:EnergyTransfer:Zone:LGSTORE1 | 31.38 | 0.00 | 01-JAN-00:10 | 33781.88 | 06-FEB-08:10 |
General:Heating:EnergyTransfer | 200.10 | 0.00 | 01-JAN-00:10 | 171741.13 | 07-FEB-08:10 |
General:Heating:EnergyTransfer:Zone:LGSTORE1 | 31.38 | 0.00 | 01-JAN-00:10 | 33781.88 | 06-FEB-08:10 |
Cooling:EnergyTransfer | 289.61 | 0.00 | 01-JAN-00:10 | 80761.27 | 21-JUL-13:00 |
Cooling:EnergyTransfer:Zone:LGSTORE1 | 65.18 | 0.00 | 01-JAN-00:10 | 13477.64 | 21-JUL-13:00 |
General:Cooling:EnergyTransfer | 289.61 | 0.00 | 01-JAN-00:10 | 80761.27 | 21-JUL-13:00 |
General:Cooling:EnergyTransfer:Zone:LGSTORE1 | 65.18 | 0.00 | 01-JAN-00:10 | 13477.64 | 21-JUL-13:00 |
EnergyTransfer:Zone:SMSTORE1 | 46.90 | 0.00 | 01-JAN-00:10 | 14254.34 | 07-FEB-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE1 | 9.76 | 0.00 | 01-JAN-00:10 | 14254.34 | 07-FEB-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE1 | 9.76 | 0.00 | 01-JAN-00:10 | 14254.34 | 07-FEB-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE1 | 37.13 | 0.00 | 01-JAN-00:10 | 8818.72 | 03-JUN-18:20 |
General:Cooling:EnergyTransfer:Zone:SMSTORE1 | 37.13 | 0.00 | 01-JAN-00:10 | 8818.72 | 03-JUN-18:20 |
EnergyTransfer:Zone:SMSTORE2 | 39.11 | 0.00 | 01-JAN-00:10 | 15255.24 | 06-FEB-07:10 |
Heating:EnergyTransfer:Zone:SMSTORE2 | 12.16 | 0.00 | 01-JAN-00:10 | 15255.24 | 06-FEB-07:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE2 | 12.16 | 0.00 | 01-JAN-00:10 | 15255.24 | 06-FEB-07:10 |
Cooling:EnergyTransfer:Zone:SMSTORE2 | 26.94 | 0.00 | 01-JAN-00:10 | 7064.21 | 21-JUL-13:40 |
General:Cooling:EnergyTransfer:Zone:SMSTORE2 | 26.94 | 0.00 | 01-JAN-00:10 | 7064.21 | 21-JUL-13:40 |
EnergyTransfer:Zone:SMSTORE3 | 39.31 | 0.00 | 01-JAN-00:10 | 16181.12 | 06-FEB-07:10 |
Heating:EnergyTransfer:Zone:SMSTORE3 | 13.14 | 0.00 | 01-JAN-00:10 | 16181.12 | 06-FEB-07:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE3 | 13.14 | 0.00 | 01-JAN-00:10 | 16181.12 | 06-FEB-07:10 |
Cooling:EnergyTransfer:Zone:SMSTORE3 | 26.17 | 0.00 | 01-JAN-00:10 | 7071.35 | 21-JUL-13:40 |
General:Cooling:EnergyTransfer:Zone:SMSTORE3 | 26.17 | 0.00 | 01-JAN-00:10 | 7071.35 | 21-JUL-13:40 |
EnergyTransfer:Zone:SMSTORE4 | 39.19 | 0.00 | 01-JAN-00:10 | 16905.41 | 06-FEB-07:10 |
Heating:EnergyTransfer:Zone:SMSTORE4 | 14.79 | 0.00 | 01-JAN-00:10 | 16905.41 | 06-FEB-07:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE4 | 14.79 | 0.00 | 01-JAN-00:10 | 16905.41 | 06-FEB-07:10 |
Cooling:EnergyTransfer:Zone:SMSTORE4 | 24.40 | 0.00 | 01-JAN-00:10 | 6936.33 | 21-JUL-13:40 |
General:Cooling:EnergyTransfer:Zone:SMSTORE4 | 24.40 | 0.00 | 01-JAN-00:10 | 6936.33 | 21-JUL-13:40 |
EnergyTransfer:Zone:LGSTORE2 | 69.15 | 0.00 | 01-JAN-00:10 | 33569.91 | 07-FEB-08:10 |
Heating:EnergyTransfer:Zone:LGSTORE2 | 30.54 | 0.00 | 01-JAN-00:10 | 33569.91 | 07-FEB-08:10 |
General:Heating:EnergyTransfer:Zone:LGSTORE2 | 30.54 | 0.00 | 01-JAN-00:10 | 33569.91 | 07-FEB-08:10 |
Cooling:EnergyTransfer:Zone:LGSTORE2 | 38.61 | 0.00 | 01-JAN-00:10 | 12526.74 | 21-JUL-13:00 |
General:Cooling:EnergyTransfer:Zone:LGSTORE2 | 38.61 | 0.00 | 01-JAN-00:10 | 12526.74 | 21-JUL-13:00 |
EnergyTransfer:Zone:SMSTORE5 | 36.55 | 0.00 | 01-JAN-00:10 | 16903.46 | 26-DEC-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE5 | 17.33 | 0.00 | 01-JAN-00:10 | 16903.46 | 26-DEC-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE5 | 17.33 | 0.00 | 01-JAN-00:10 | 16903.46 | 26-DEC-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE5 | 19.23 | 0.00 | 01-JAN-00:10 | 6497.58 | 21-JUL-14:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE5 | 19.23 | 0.00 | 01-JAN-00:10 | 6497.58 | 21-JUL-14:10 |
EnergyTransfer:Zone:SMSTORE6 | 36.47 | 0.00 | 01-JAN-00:10 | 17192.10 | 06-FEB-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE6 | 17.77 | 0.00 | 01-JAN-00:10 | 17192.10 | 06-FEB-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE6 | 17.77 | 0.00 | 01-JAN-00:10 | 17192.10 | 06-FEB-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE6 | 18.70 | 0.00 | 01-JAN-00:10 | 6449.32 | 21-JUL-14:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE6 | 18.70 | 0.00 | 01-JAN-00:10 | 6449.32 | 21-JUL-14:10 |
EnergyTransfer:Zone:SMSTORE7 | 37.45 | 0.00 | 01-JAN-00:10 | 17560.64 | 11-DEC-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE7 | 20.05 | 0.00 | 01-JAN-00:10 | 17560.64 | 11-DEC-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE7 | 20.05 | 0.00 | 01-JAN-00:10 | 17560.64 | 11-DEC-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE7 | 17.40 | 0.00 | 01-JAN-00:10 | 6406.25 | 21-JUL-14:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE7 | 17.40 | 0.00 | 01-JAN-00:10 | 6406.25 | 21-JUL-14:10 |
EnergyTransfer:Zone:SMSTORE8 | 49.03 | 0.00 | 01-JAN-00:10 | 20127.23 | 06-FEB-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE8 | 33.18 | 0.00 | 01-JAN-00:10 | 20127.23 | 06-FEB-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE8 | 33.18 | 0.00 | 01-JAN-00:10 | 20127.23 | 06-FEB-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE8 | 15.84 | 0.00 | 01-JAN-00:10 | 7057.66 | 21-JUL-13:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE8 | 15.84 | 0.00 | 01-JAN-00:10 | 7057.66 | 21-JUL-13:00 |
EnergyTransfer:HVAC | 827.27 | 0.00 | 01-JAN-00:10 | 199387.40 | 06-FEB-12:10 |
HeatingCoils:EnergyTransfer | 569.73 | 0.00 | 01-JAN-00:10 | 199387.40 | 06-FEB-12:10 |
CoolingCoils:EnergyTransfer | 257.54 | 0.00 | 01-JAN-00:10 | 156583.00 | 15-JUL-14:00 |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:59
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
LGSTORE1 | 0.000 | 0.000 | 31.381 | -65.176 | 0.000 | 0.000 | 25.502 | 87.116 | 26.249 | 19.197 | 0.000 | 1.058 | 0.001 | 0.000 | -10.251 | 0.000 | -44.083 | -70.992 |
SMSTORE1 | 0.000 | 0.000 | 9.765 | -37.131 | 0.000 | 0.000 | 12.569 | 53.201 | 13.125 | 9.497 | 0.000 | 0.566 | 0.000 | 0.000 | -5.398 | 0.000 | -21.264 | -34.930 |
SMSTORE2 | 0.000 | 0.000 | 12.165 | -26.944 | 0.000 | 0.000 | 7.645 | 37.572 | 10.421 | 9.488 | 0.000 | 0.552 | 0.001 | 0.000 | -5.313 | 0.000 | -21.938 | -23.647 |
SMSTORE3 | 0.000 | 0.000 | 13.139 | -26.169 | 0.000 | 0.000 | 7.653 | 37.572 | 10.421 | 9.502 | 0.000 | 0.552 | 0.003 | 0.000 | -5.256 | 0.000 | -21.859 | -25.555 |
SMSTORE4 | 0.000 | 0.000 | 14.786 | -24.405 | 0.000 | 0.000 | 7.667 | 37.572 | 10.421 | 9.525 | 0.000 | 0.552 | 0.002 | 0.000 | -5.195 | 0.000 | -21.759 | -29.165 |
LGSTORE2 | 0.000 | 0.000 | 30.539 | -38.607 | 0.000 | 0.000 | 26.367 | 37.162 | 19.173 | 19.163 | 0.000 | 0.998 | 0.002 | 0.000 | -10.052 | 0.000 | -40.061 | -44.683 |
SMSTORE5 | 0.000 | 0.000 | 17.329 | -19.226 | 0.000 | 0.000 | 13.191 | 19.120 | 9.586 | 9.564 | 0.000 | 0.554 | 0.000 | 0.000 | -5.036 | 0.000 | -21.772 | -23.312 |
SMSTORE6 | 0.000 | 0.000 | 17.767 | -18.702 | 0.000 | 0.000 | 13.201 | 19.120 | 9.586 | 9.574 | 0.000 | 0.554 | 0.000 | 0.000 | -5.014 | 0.000 | -21.735 | -24.352 |
SMSTORE7 | 0.000 | 0.000 | 20.051 | -17.400 | 0.000 | 0.000 | 13.225 | 19.120 | 9.586 | 9.602 | 0.000 | 0.554 | 0.000 | 0.000 | -4.936 | 0.000 | -21.615 | -28.187 |
SMSTORE8 | 0.000 | 0.000 | 33.183 | -15.842 | 0.000 | 0.000 | 13.262 | 19.120 | 9.586 | 9.681 | 0.000 | 0.591 | 0.001 | 0.000 | -4.637 | 0.000 | -27.868 | -37.077 |
Total Facility | 0.000 | 0.000 | 200.103 | -289.602 | 0.000 | 0.000 | 140.283 | 366.677 | 128.154 | 114.793 | 0.000 | 6.532 | 0.010 | 0.000 | -61.087 | 0.000 | -263.953 | -341.900 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
LGSTORE1 | 06-AUG-07:02 | 0.00 | 0.00 | 0.00 | -32826.43 | 0.00 | 0.00 | 183.05 | 75.00 | 74.62 | 291.08 | 0.00 | 0.00 | 32378.77 | 0.00 | -0.00 | 0.00 | -176.10 | 0.00 |
SMSTORE1 | 06-AUG-07:02 | 0.00 | 0.00 | 0.00 | -18415.62 | 0.00 | 0.00 | 89.39 | 37.50 | 37.31 | 140.77 | 0.00 | 0.00 | 18202.81 | 0.00 | -0.00 | 0.00 | -92.17 | 0.00 |
SMSTORE2 | 06-AUG-07:02 | 0.00 | 0.00 | 0.00 | -18501.20 | 0.00 | 0.00 | 0.00 | 37.50 | 37.31 | 137.43 | 0.00 | 0.00 | 18384.66 | 0.00 | -0.00 | 0.00 | -95.70 | 0.00 |
SMSTORE3 | 06-AUG-07:02 | 0.00 | 0.00 | 0.00 | -18578.16 | 0.00 | 0.00 | 0.00 | 37.50 | 37.31 | 136.99 | 0.00 | 0.00 | 18462.51 | 0.00 | -0.00 | 0.00 | -96.15 | 0.00 |
SMSTORE4 | 06-AUG-07:02 | 0.00 | 0.00 | 0.00 | -18302.83 | 0.00 | 0.00 | 0.00 | 37.50 | 37.31 | 138.63 | 0.00 | 0.00 | 18183.02 | 0.00 | -0.00 | 0.00 | -93.63 | 0.00 |
LGSTORE2 | 06-AUG-08:62 | 0.00 | 0.00 | 0.00 | -30476.98 | 0.00 | 0.00 | 0.00 | 75.00 | 73.64 | 757.17 | 0.00 | 0.00 | 29662.80 | 0.00 | -0.00 | 0.00 | -91.64 | 0.00 |
SMSTORE5 | 06-AUG-08:62 | 0.00 | 0.00 | 0.00 | -15002.77 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 379.25 | 0.00 | 0.00 | 14598.25 | 0.00 | -0.00 | 0.00 | -49.05 | 0.00 |
SMSTORE6 | 06-AUG-08:62 | 0.00 | 0.00 | 0.00 | -14478.00 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 380.07 | 0.00 | 0.00 | 14072.52 | 0.00 | -0.00 | 0.00 | -48.92 | 0.00 |
SMSTORE7 | 07-AUG-07:02 | 0.00 | 0.00 | 0.00 | -13120.55 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 127.20 | 0.00 | 0.00 | 12999.56 | 0.00 | -0.00 | 0.00 | -80.53 | 0.00 |
SMSTORE8 | 07-AUG-07:02 | 0.00 | 0.00 | 0.00 | -13175.10 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 133.33 | 0.00 | 0.00 | 13056.27 | 0.00 | -0.00 | 0.00 | -88.81 | 0.00 |
Total Facility | 07-AUG-07:02 | 0.00 | 0.00 | 0.00 | -127137.10 | 0.00 | 0.00 | 565.70 | 450.00 | 1452.23 | 1541.02 | 0.00 | 0.00 | 124072.01 | 0.00 | 0.00 | 0.00 | -943.86 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
LGSTORE1 | 06-FEB-08:12 | 0.00 | 0.00 | 60011.46 | 0.00 | 0.00 | 0.00 | 231.22 | 243.23 | 74.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1046.92 | 0.00 | -2509.09 | -57004.53 |
SMSTORE1 | 07-MAR-08:61 | 0.00 | 0.00 | 31330.26 | 0.00 | 0.00 | 0.00 | 131.92 | 37.50 | 37.31 | 271.46 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -823.42 | -30985.04 |
SMSTORE2 | 05-MAR-08:61 | 0.00 | 0.00 | 31414.45 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 37.31 | 260.72 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -742.05 | -31007.93 |
SMSTORE3 | 10-DEC-08:61 | 0.00 | 0.00 | 31293.59 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 37.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -67.18 | 0.00 | -860.86 | -30440.36 |
SMSTORE4 | 10-DEC-08:61 | 0.00 | 0.00 | 31226.25 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 37.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -62.51 | 0.00 | -853.47 | -30385.08 |
LGSTORE2 | 06-FEB-08:12 | 0.00 | 0.00 | 58149.45 | 0.00 | 0.00 | 0.00 | 0.00 | 75.00 | 73.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1036.18 | 0.00 | -2089.38 | -55172.52 |
SMSTORE5 | 06-FEB-08:12 | 0.00 | 0.00 | 29760.66 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -521.02 | 0.00 | -1131.72 | -28182.24 |
SMSTORE6 | 06-FEB-08:12 | 0.00 | 0.00 | 29634.09 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -520.22 | 0.00 | -1127.92 | -28060.27 |
SMSTORE7 | 06-FEB-08:12 | 0.00 | 0.00 | 29427.07 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -518.03 | 0.00 | -1125.79 | -27857.58 |
SMSTORE8 | 06-FEB-08:12 | 0.00 | 0.00 | 30399.81 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 36.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -506.32 | 0.00 | -1542.37 | -28425.45 |
Total Facility | 06-FEB-08:61 | 0.00 | 0.00 | 289103.37 | 0.00 | 0.00 | 0.00 | 774.50 | 450.00 | 1452.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -6095.59 | 0.00 | -12731.28 | -272953.23 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:59
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 1.8636 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 1.8636 | 0.2208 | 1.0000 | Not calculated | 0.4115 | 0.2208 | ||
PSZ-AC_2:2 | 0.9958 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0130 | 0.2031 | 1.0000 | Not calculated | 0.2057 | 0.2031 | ||
PSZ-AC_3:3 | 1.0001 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0191 | 0.2019 | 1.0000 | Not calculated | 0.2057 | 0.2019 | ||
PSZ-AC_4:4 | 0.9944 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0227 | 0.2012 | 1.0000 | Not calculated | 0.2057 | 0.2012 | ||
PSZ-AC_5:5 | 0.9913 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0124 | 0.2032 | 1.0000 | Not calculated | 0.2057 | 0.2032 | ||
PSZ-AC_6:6 | 1.7752 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 1.7752 | 0.2318 | 1.0000 | Not calculated | 0.4115 | 0.2318 | ||
PSZ-AC_7:7 | 0.9142 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9211 | 0.2234 | 1.0000 | Not calculated | 0.2057 | 0.2234 | ||
PSZ-AC_8:8 | 0.9077 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9151 | 0.2248 | 1.0000 | Not calculated | 0.2057 | 0.2248 | ||
PSZ-AC_9:9 | 0.8968 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9056 | 0.2272 | 1.0000 | Not calculated | 0.2057 | 0.2272 | ||
PSZ-AC_10:10 | 0.9349 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9613 | 0.2140 | 1.0000 | Not calculated | 0.2057 | 0.2140 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 1.8636 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 1.8636 | 1.0000 | 1.0000 | Not calculated | 0.4115 | 0.2208 | ||
PSZ-AC_2:2 | 0.9958 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9958 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.2066 | ||
PSZ-AC_3:3 | 1.0001 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0001 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.2057 | ||
PSZ-AC_4:4 | 0.9944 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9944 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.2069 | ||
PSZ-AC_5:5 | 0.9913 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9913 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.2076 | ||
PSZ-AC_6:6 | 1.7752 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 1.7752 | 1.0000 | 1.0000 | Not calculated | 0.4115 | 0.2318 | ||
PSZ-AC_7:7 | 0.9142 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9142 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.2251 | ||
PSZ-AC_8:8 | 0.9077 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9077 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.2267 | ||
PSZ-AC_9:9 | 0.8968 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.8968 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.2294 | ||
PSZ-AC_10:10 | 0.9349 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9349 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.2201 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
LGSTORE1 | PSZ-AC_1:1 | 0.000000 | 56.2505 | 0.001181 | 348.39 | 0.4115 | 1.0000 | 0.4115 | 1.000 | 0.4115 |
SMSTORE1 | PSZ-AC_2:2 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE2 | PSZ-AC_3:3 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE3 | PSZ-AC_4:4 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE4 | PSZ-AC_5:5 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
LGSTORE2 | PSZ-AC_6:6 | 0.000000 | 56.2505 | 0.001181 | 348.39 | 0.4115 | 1.0000 | 0.4115 | 1.000 | 0.4115 |
SMSTORE5 | PSZ-AC_7:7 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE6 | PSZ-AC_8:8 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE7 | PSZ-AC_9:9 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE8 | PSZ-AC_10:10 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC_1:1 | 0.000000 | 56.25 | 0.001181 | 348.3864 | 0.4115 | 0.4115 | 0.4115 |
PSZ-AC_2:2 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_3:3 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_4:4 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_5:5 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_6:6 | 0.000000 | 56.25 | 0.001181 | 348.3864 | 0.4115 | 0.4115 | 0.4115 |
PSZ-AC_7:7 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_8:8 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_9:9 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_10:10 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LGSTORE1 | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.8636 | 1.8636 | 1.8636 | No | 0.4115 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE1 | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9958 | 0.9958 | 0.9958 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE2 | PSZ-AC_3:3 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0001 | 1.0001 | 1.0001 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE3 | PSZ-AC_4:4 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9944 | 0.9944 | 0.9944 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE4 | PSZ-AC_5:5 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9913 | 0.9913 | 0.9913 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LGSTORE2 | PSZ-AC_6:6 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.7752 | 1.7752 | 1.7752 | No | 0.4115 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE5 | PSZ-AC_7:7 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9142 | 0.9142 | 0.9142 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE6 | PSZ-AC_8:8 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9077 | 0.9077 | 0.9077 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE7 | PSZ-AC_9:9 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8968 | 0.8968 | 0.8968 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE8 | PSZ-AC_10:10 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9349 | 0.9349 | 0.9349 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 1.8636 | 1.8636 | 1.8636 | 1.8636 | 0.4115 | 1.0000 |
PSZ-AC_2:2 | 0.9958 | 1.0130 | 0.9958 | 0.9958 | 0.2057 | 1.0000 |
PSZ-AC_3:3 | 1.0001 | 1.0191 | 1.0001 | 1.0001 | 0.2057 | 1.0000 |
PSZ-AC_4:4 | 0.9944 | 1.0227 | 0.9944 | 0.9944 | 0.2057 | 1.0000 |
PSZ-AC_5:5 | 0.9913 | 1.0124 | 0.9913 | 0.9913 | 0.2057 | 1.0000 |
PSZ-AC_6:6 | 1.7752 | 1.7752 | 1.7752 | 1.7752 | 0.4115 | 1.0000 |
PSZ-AC_7:7 | 0.9142 | 0.9211 | 0.9142 | 0.9142 | 0.2057 | 1.0000 |
PSZ-AC_8:8 | 0.9077 | 0.9151 | 0.9077 | 0.9077 | 0.2057 | 1.0000 |
PSZ-AC_9:9 | 0.8968 | 0.9056 | 0.8968 | 0.8968 | 0.2057 | 1.0000 |
PSZ-AC_10:10 | 0.9349 | 0.9613 | 0.9349 | 0.9349 | 0.2057 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LGSTORE1 | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.8636 | 1.8636 | 1.8636 | No | 0.4115 | 0.2789 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE1 | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9958 | 0.9958 | 0.9958 | No | 0.2057 | 0.2958 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE2 | PSZ-AC_3:3 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0001 | 1.0001 | 1.0001 | No | 0.2057 | 0.2925 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE3 | PSZ-AC_4:4 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9944 | 0.9944 | 0.9944 | No | 0.2057 | 0.2908 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE4 | PSZ-AC_5:5 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9913 | 0.9913 | 0.9913 | No | 0.2057 | 0.2877 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LGSTORE2 | PSZ-AC_6:6 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.7752 | 1.7752 | 1.7752 | No | 0.4115 | 0.3005 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE5 | PSZ-AC_7:7 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9142 | 0.9142 | 0.9142 | No | 0.2057 | 0.2808 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE6 | PSZ-AC_8:8 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9077 | 0.9077 | 0.9077 | No | 0.2057 | 0.2810 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE7 | PSZ-AC_9:9 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8968 | 0.8968 | 0.8968 | No | 0.2057 | 0.2768 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE8 | PSZ-AC_10:10 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9349 | 0.9349 | 0.9349 | No | 0.2057 | 0.2253 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 1.8636 | 1.8636 | 1.8636 | 1.8636 | 0.4115 | 1.0000 |
PSZ-AC_2:2 | 0.9958 | 0.9958 | 0.9958 | 0.9958 | 0.2057 | 1.0000 |
PSZ-AC_3:3 | 1.0001 | 1.0001 | 1.0001 | 1.0001 | 0.2057 | 1.0000 |
PSZ-AC_4:4 | 0.9944 | 0.9944 | 0.9944 | 0.9944 | 0.2057 | 1.0000 |
PSZ-AC_5:5 | 0.9913 | 0.9913 | 0.9913 | 0.9913 | 0.2057 | 1.0000 |
PSZ-AC_6:6 | 1.7752 | 1.7752 | 1.7752 | 1.7752 | 0.4115 | 1.0000 |
PSZ-AC_7:7 | 0.9142 | 0.9142 | 0.9142 | 0.9142 | 0.2057 | 1.0000 |
PSZ-AC_8:8 | 0.9077 | 0.9077 | 0.9077 | 0.9077 | 0.2057 | 1.0000 |
PSZ-AC_9:9 | 0.8968 | 0.8968 | 0.8968 | 0.8968 | 0.2057 | 1.0000 |
PSZ-AC_10:10 | 0.9349 | 0.9349 | 0.9349 | 0.9349 | 0.2057 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:59
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280 |
Total gross floor area [m2] | 2090.32 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
LGSTORE1 | 348.39 | 348.39 | 0.00 | 112.00 |
SMSTORE1 | 174.19 | 174.19 | 0.00 | 112.00 |
SMSTORE2 | 174.19 | 174.19 | 0.00 | 84.29 |
SMSTORE3 | 174.19 | 174.19 | 0.00 | 84.29 |
SMSTORE4 | 174.19 | 174.19 | 0.00 | 84.29 |
LGSTORE2 | 348.39 | 348.39 | 0.00 | 77.29 |
SMSTORE5 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE6 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE7 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE8 | 174.19 | 174.19 | 0.00 | 77.29 |
Totals | 2090.32 | 2090.32 | 0.00 |
Data | |
Number of hours heating loads not met | 5.67 |
Number of hours cooling loads not met | 0.00 |
Number of hours not met | 5.67 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 712.17 | 249234.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 63.40 | 36777.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 366.68 | 23459.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 60.16 | 5507.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 128.15 | 8059.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 98.12 | 9145.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 65.11 | 12298.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 128.15 | 781.62 |
Natural Gas | 0.00 | 712.17 |
Additional | 0.00 | 0.00 |
Total | 128.15 | 1493.79 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 175.42 |
Space Heating | 0.00 |
Space Cooling | 30.33 |
Fans (All) | 46.94 |
Service Water Heating | 31.15 |
Receptacle Equipment | 61.31 |
Miscellaneous (All) | 373.93 |
Subtotal | 373.93 |
Natural Gas [MJ/m2] | |
Space Heating | 340.70 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 340.70 |
Subtotal | 340.70 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 24.55 |
Space Heating | 47.68 |
Space Cooling | 4.24 |
Fans (All) | 6.57 |
Service Water Heating | 4.36 |
Receptacle Equipment | 8.58 |
Miscellaneous | 4.03 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
TYPE1_OCC_SCH | 1630. | 5840. |
TYPE2_OCC_SCH | 995. | 4429. |
TYPE3_OCC_SCH | 1709. | 4064. |
LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 3767. | 8760. |
LTG_SCH_BASE_LPD2 | 3238. | 8760. |
LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 3296. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | 5084. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | 5084. | 8760. |
LTG_SCH_BASE_SMALL_LPD1 | 4453. | 8760. |
LTG_SCH_BASE_LPD1 | 4376. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | 3767. | 8760. |
LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 3584. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 4096. | 8760. |
TYPE1_EQUIP_SCH | 4868. | 8760. |
TYPE2_EQUIP_SCH | 3893. | 8760. |
TYPE3_EQUIP_SCH | 3584. | 8760. |
TYPE1_INFIL_SCH | 4302. | 8760. |
TYPE2_INFIL_SCH | 5164. | 8760. |
TYPE3_INFIL_SCH | 5438. | 8760. |
INFIL_DOOR_OPENING_SCH | 2477. | 4380. |
TYPE1_MINOA_MOTORIZEDDAMPER_SCH | 5579. | 5579. |
TYPE2_MINOA_MOTORIZEDDAMPER_SCH | 4429. | 4429. |
TYPE3_MINOA_MOTORIZEDDAMPER_SCH | 4064. | 4064. |
TYPE1_SWH_SCH | 2063. | 6048. |
TYPE2_SWH_SCH | 1831. | 4429. |
TYPE3_SWH_SCH | 1733. | 4064. |
AVERAGE_SWH_SCH | 1863. | 6152. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 7118. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 5839. | 5839. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 7300. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6570. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
TYPE1_HTGSETP_SCH_NO_OPTIMUM | LGSTORE1 DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
TYPE1_CLGSETP_SCH_NO_OPTIMUM | LGSTORE1 DUAL SP CONTROL | July | 23.89 | 365 | 23.89 | 365 |
TYPE2_HTGSETP_SCH_NO_OPTIMUM | SMSTORE2 DUAL SP CONTROL | January | 21.11 | 365 | 15.56 | 365 |
TYPE2_CLGSETP_SCH_NO_OPTIMUM | SMSTORE2 DUAL SP CONTROL | July | 23.89 | 365 | 29.44 | 365 |
TYPE3_HTGSETP_SCH_NO_OPTIMUM | LGSTORE2 DUAL SP CONTROL | January | 21.11 | 365 | 15.56 | 365 |
TYPE3_CLGSETP_SCH_NO_OPTIMUM | LGSTORE2 DUAL SP CONTROL | July | 23.89 | 365 | 29.44 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:59
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
LGSTORE1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 8747.33 | 12.67 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 8744.83 | 15.17 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 8750.33 | 9.67 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 8753.83 | 6.17 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 8755.50 | 4.50 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 8756.33 | 3.67 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 8757.17 | 2.83 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 8756.17 | 3.83 | 0.00 | 0.00 | 0.00 |
Min | 8744.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 15.17 | 0.00 | 0.00 | 0.00 |
Average | 8754.15 | 5.85 | 0.00 | 0.00 | 0.00 |
Sum | 87541.50 | 58.50 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
LGSTORE1 | 89041.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 43777.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 25471.33 | 3.67 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 25471.50 | 3.50 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 25471.67 | 3.33 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 93198.00 | 13.00 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 45906.00 | 6.00 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 45906.50 | 5.50 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 45907.50 | 4.50 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 45907.50 | 4.50 | 0.00 | 0.00 | 0.00 |
Min | 25471.33 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 93198.00 | 13.00 | 0.00 | 0.00 | 0.00 |
Average | 48605.80 | 4.40 | 0.00 | 0.00 | 0.00 |
Sum | 486058.00 | 44.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
LGSTORE1 | 8219.50 | 540.50 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 8517.00 | 243.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 8066.67 | 693.33 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 8064.83 | 695.17 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 8066.67 | 693.33 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 8060.67 | 699.33 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 8064.17 | 695.83 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 8064.83 | 695.17 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 8067.17 | 692.83 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 8089.50 | 670.50 | 0.00 | 0.00 | 0.00 |
Min | 8060.67 | 243.00 | 0.00 | 0.00 | 0.00 |
Max | 8517.00 | 699.33 | 0.00 | 0.00 | 0.00 |
Average | 8128.10 | 631.90 | 0.00 | 0.00 | 0.00 |
Sum | 81281.00 | 6319.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
LGSTORE1 | 86126.17 | 2914.83 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 42847.67 | 929.33 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 24648.00 | 827.00 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 24628.83 | 846.17 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 24592.17 | 882.83 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 89108.50 | 4102.50 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 43853.50 | 2058.50 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 43812.67 | 2099.33 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 43709.83 | 2202.17 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 43556.17 | 2355.83 | 0.00 | 0.00 | 0.00 |
Min | 24592.17 | 827.00 | 0.00 | 0.00 | 0.00 |
Max | 89108.50 | 4102.50 | 0.00 | 0.00 | 0.00 |
Average | 46688.35 | 1921.85 | 0.00 | 0.00 | 0.00 |
Sum | 466883.50 | 19218.50 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:59
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:36:59
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
For: Environment
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTRIPMALL
For: Environment
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5A
For: Environment
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_BUFFALO
For: Environment
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: ZoneCoolingSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.404080E+09 | 13728.84 | 06-JAN-00:02 | -10.0 | -10.7 | 0.106492E+10 | 1275.40 | 29-JAN-18:00 | -6.7 | -7.2 |
February | 0.392320E+09 | 13740.50 | 11-FEB-00:02 | -10.0 | -10.7 | 0.961221E+09 | 1275.40 | 20-FEB-18:00 | -1.1 | -2.5 |
March | 0.182851E+10 | 13470.40 | 04-MAR-00:02 | -9.4 | -10.8 | 0.108259E+10 | 1409.56 | 12-MAR-17:00 | 13.30 | 11.37 |
April | 0.331099E+10 | 8190.62 | 13-APR-23:03 | 1.78 | 0.76 | 0.107898E+10 | 1685.69 | 08-APR-12:00 | 1.78 | 0.76 |
May | 0.588799E+10 | 6870.21 | 14-MAY-15:00 | 26.10 | 17.84 | 0.128486E+10 | 1685.88 | 13-MAY-12:00 | 26.10 | 17.84 |
June | 0.969589E+10 | 20424.14 | 18-JUN-07:03 | 23.48 | 21.14 | 0.134615E+10 | 1685.99 | 18-JUN-12:09 | 26.10 | 20.65 |
July | 0.130418E+11 | 24590.61 | 15-JUL-07:03 | 23.07 | 19.55 | 0.141265E+10 | 1685.99 | 30-JUL-17:00 | 24.40 | 20.25 |
August | 0.126811E+11 | 32834.41 | 06-AUG-07:02 | 20.28 | 15.40 | 0.139323E+10 | 1685.99 | 13-AUG-12:39 | 29.63 | 22.57 |
September | 0.929131E+10 | 25403.67 | 17-SEP-07:02 | 22.12 | 19.56 | 0.134721E+10 | 1685.98 | 16-SEP-12:09 | 22.12 | 19.56 |
October | 0.546561E+10 | 6641.81 | 23-OCT-17:10 | 4.40 | 2.51 | 0.118114E+10 | 1685.93 | 22-OCT-12:00 | 4.40 | 2.51 |
November | 0.256502E+10 | 9895.18 | 24-NOV-00:02 | -1.8 | -2.5 | 0.105166E+10 | 1662.86 | 05-NOV-12:00 | -1.8 | -2.5 |
December | 0.612126E+09 | 13423.28 | 29-DEC-00:02 | -9.4 | -10.3 | 0.107027E+10 | 1275.40 | 10-DEC-18:00 | -9.4 | -10.3 |
Annual Sum or Average | 0.651768E+11 | 0.142749E+11 | ||||||||
Minimum of Months | 0.392320E+09 | 6641.81 | -10.0 | -10.8 | 0.961221E+09 | 1275.40 | -9.4 | -10.3 | ||
Maximum of Months | 0.130418E+11 | 32834.41 | 26.10 | 21.14 | 0.141265E+10 | 1685.99 | 29.63 | 22.57 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.182844E+09 | 6773.16 | 23-JAN-18:42 | -9.9 | -11.5 | 0.541874E+09 | 743.70 | 16-JAN-18:00 | -9.9 | -11.5 |
February | 0.174498E+09 | 6161.15 | 13-FEB-18:42 | -7.2 | -7.5 | 0.487803E+09 | 720.94 | 19-FEB-18:00 | 2.20 | 1.05 |
March | 0.103060E+10 | 12669.89 | 15-MAR-20:09 | 20.73 | 14.37 | 0.561397E+09 | 842.88 | 12-MAR-17:00 | 20.73 | 14.37 |
April | 0.179254E+10 | 4157.09 | 09-APR-17:10 | 12.75 | 9.86 | 0.576188E+09 | 842.91 | 08-APR-12:00 | 12.75 | 9.86 |
May | 0.338858E+10 | 16126.96 | 21-MAY-17:56 | 16.70 | 9.85 | 0.673405E+09 | 842.93 | 13-MAY-12:00 | 16.70 | 9.85 |
June | 0.580450E+10 | 16084.74 | 03-JUN-18:08 | 17.80 | 10.05 | 0.673541E+09 | 842.97 | 02-JUN-12:50 | 17.80 | 10.05 |
July | 0.751134E+10 | 15607.15 | 26-JUL-07:03 | 20.87 | 17.48 | 0.704710E+09 | 842.97 | 23-JUL-12:00 | 20.87 | 17.48 |
August | 0.725450E+10 | 18418.35 | 06-AUG-07:02 | 20.28 | 15.40 | 0.694875E+09 | 842.98 | 13-AUG-12:39 | 29.63 | 22.57 |
September | 0.543462E+10 | 15540.56 | 10-SEP-17:47 | 16.10 | 10.54 | 0.678084E+09 | 842.96 | 09-SEP-12:00 | 16.10 | 10.54 |
October | 0.289297E+10 | 12750.58 | 22-OCT-17:43 | 19.18 | 14.09 | 0.626835E+09 | 842.94 | 22-OCT-12:00 | 19.18 | 14.09 |
November | 0.139846E+10 | 3624.63 | 18-NOV-17:43 | 3.40 | 1.16 | 0.553135E+09 | 842.90 | 05-NOV-17:00 | 3.40 | 1.16 |
December | 0.265666E+09 | 6801.07 | 26-DEC-18:42 | -10.0 | -11.3 | 0.547181E+09 | 742.34 | 24-DEC-18:00 | -10.0 | -11.3 |
Annual Sum or Average | 0.371311E+11 | 0.731903E+10 | ||||||||
Minimum of Months | 0.174498E+09 | 3624.63 | -10.0 | -11.5 | 0.487803E+09 | 720.94 | -10.0 | -11.5 | ||
Maximum of Months | 0.751134E+10 | 18418.35 | 20.87 | 17.48 | 0.704710E+09 | 842.98 | 29.63 | 22.57 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 59103046.14 | 4969.95 | 20-JAN-20:03 | -2.3 | -4.0 | 0.317181E+09 | 637.68 | 14-JAN-13:09 | -2.3 | -4.0 |
February | 61536728.65 | 5947.55 | 10-FEB-11:32 | -6.3 | -7.5 | 0.288104E+09 | 637.68 | 18-FEB-13:30 | 2.25 | 0.43 |
March | 0.729069E+09 | 5838.40 | 05-MAR-11:22 | -5.8 | -8.1 | 0.335695E+09 | 702.46 | 15-MAR-17:00 | 23.90 | 15.62 |
April | 0.139280E+10 | 3951.68 | 24-APR-07:01 | 3.17 | 1.61 | 0.328989E+09 | 842.91 | 08-APR-12:00 | 3.17 | 1.61 |
May | 0.252001E+10 | 3859.12 | 27-MAY-13:00 | 21.70 | 12.35 | 0.397663E+09 | 842.93 | 13-MAY-12:00 | 21.70 | 12.35 |
June | 0.415611E+10 | 14145.25 | 26-JUN-06:03 | 20.50 | 17.42 | 0.414350E+09 | 842.97 | 17-JUN-12:00 | 20.50 | 17.42 |
July | 0.540850E+10 | 16100.03 | 26-JUL-06:03 | 20.60 | 17.13 | 0.419845E+09 | 842.95 | 29-JUL-12:09 | 25.68 | 21.35 |
August | 0.538685E+10 | 18505.33 | 06-AUG-07:02 | 20.28 | 15.40 | 0.431169E+09 | 842.97 | 12-AUG-12:09 | 23.40 | 16.43 |
September | 0.388429E+10 | 13905.46 | 17-SEP-07:02 | 22.12 | 19.56 | 0.406010E+09 | 842.96 | 09-SEP-12:00 | 22.12 | 19.56 |
October | 0.222851E+10 | 4227.99 | 24-OCT-07:01 | 1.78 | 0.45 | 0.356031E+09 | 842.88 | 21-OCT-12:00 | 1.78 | 0.45 |
November | 0.100388E+10 | 3615.50 | 02-NOV-07:01 | 4.40 | 3.64 | 0.313484E+09 | 732.10 | 04-NOV-12:00 | 16.70 | 13.41 |
December | 0.113373E+09 | 4309.36 | 21-DEC-10:43 | 0.60 | 0.13 | 0.316799E+09 | 637.68 | 02-DEC-13:30 | 0.60 | 0.13 |
Annual Sum or Average | 0.269440E+11 | 0.432532E+10 | ||||||||
Minimum of Months | 59103046.14 | 3615.50 | -6.3 | -8.1 | 0.288104E+09 | 637.68 | -2.3 | -4.0 | ||
Maximum of Months | 0.540850E+10 | 18505.33 | 22.12 | 19.56 | 0.431169E+09 | 842.97 | 25.68 | 21.35 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 42695395.93 | 4476.15 | 07-JAN-11:02 | -0.2 | -2.5 | 0.317182E+09 | 637.68 | 14-JAN-13:09 | 4.32 | 3.15 |
February | 46666505.20 | 6407.80 | 08-FEB-18:42 | -8.3 | -9.7 | 0.288104E+09 | 637.68 | 04-FEB-13:39 | -8.3 | -9.7 |
March | 0.655083E+09 | 5893.13 | 04-MAR-11:52 | -6.1 | -7.8 | 0.335286E+09 | 702.46 | 15-MAR-17:00 | 23.90 | 15.62 |
April | 0.126997E+10 | 3878.27 | 24-APR-07:01 | 3.17 | 1.61 | 0.327159E+09 | 842.90 | 08-APR-12:00 | 3.17 | 1.61 |
May | 0.238669E+10 | 3740.37 | 27-MAY-13:00 | 21.70 | 12.35 | 0.394756E+09 | 842.92 | 13-MAY-12:00 | 21.70 | 12.35 |
June | 0.410938E+10 | 14095.21 | 26-JUN-06:03 | 20.50 | 17.42 | 0.414241E+09 | 842.97 | 17-JUN-12:00 | 20.50 | 17.42 |
July | 0.541004E+10 | 16149.81 | 26-JUL-06:03 | 20.60 | 17.13 | 0.419842E+09 | 842.95 | 29-JUL-12:09 | 25.68 | 21.35 |
August | 0.538486E+10 | 18582.31 | 06-AUG-07:02 | 20.28 | 15.40 | 0.431153E+09 | 842.97 | 12-AUG-12:09 | 23.40 | 16.43 |
September | 0.382807E+10 | 13944.65 | 17-SEP-07:02 | 22.12 | 19.56 | 0.405642E+09 | 842.96 | 09-SEP-12:00 | 22.12 | 19.56 |
October | 0.206745E+10 | 4180.80 | 24-OCT-07:01 | 1.78 | 0.45 | 0.353710E+09 | 842.88 | 21-OCT-12:00 | 1.78 | 0.45 |
November | 0.879044E+09 | 3574.47 | 02-NOV-07:01 | 4.40 | 3.64 | 0.312693E+09 | 726.04 | 04-NOV-12:00 | 16.70 | 13.41 |
December | 89325746.38 | 6290.51 | 07-DEC-18:52 | -7.8 | -9.0 | 0.316799E+09 | 637.68 | 09-DEC-13:30 | -5.0 | -5.0 |
Annual Sum or Average | 0.261693E+11 | 0.431657E+10 | ||||||||
Minimum of Months | 42695395.93 | 3574.47 | -8.3 | -9.7 | 0.288104E+09 | 637.68 | -8.3 | -9.7 | ||
Maximum of Months | 0.541004E+10 | 18582.31 | 22.12 | 19.56 | 0.431153E+09 | 842.97 | 25.68 | 21.35 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 26325856.05 | 6296.04 | 12-JAN-18:32 | -7.8 | -9.7 | 0.317182E+09 | 637.68 | 07-JAN-13:09 | -7.8 | -9.7 |
February | 29097492.33 | 6461.50 | 10-FEB-18:02 | -8.5 | -9.1 | 0.288103E+09 | 637.68 | 04-FEB-13:09 | -8.5 | -9.1 |
March | 0.537516E+09 | 4949.07 | 24-MAR-19:42 | -2.2 | -4.4 | 0.334632E+09 | 702.45 | 15-MAR-17:49 | -2.2 | -4.4 |
April | 0.108818E+10 | 3561.83 | 13-APR-08:23 | 3.60 | 1.77 | 0.324538E+09 | 842.88 | 08-APR-12:00 | 3.60 | 1.77 |
May | 0.216872E+10 | 3439.81 | 27-MAY-13:00 | 21.70 | 12.35 | 0.389777E+09 | 842.92 | 13-MAY-12:00 | 21.70 | 12.35 |
June | 0.389550E+10 | 12504.48 | 26-JUN-06:03 | 20.50 | 17.42 | 0.413799E+09 | 842.97 | 17-JUN-12:50 | 20.50 | 17.42 |
July | 0.521605E+10 | 14783.57 | 26-JUL-06:03 | 20.60 | 17.13 | 0.419796E+09 | 842.96 | 29-JUL-12:09 | 25.68 | 21.35 |
August | 0.518631E+10 | 18306.92 | 06-AUG-07:02 | 20.28 | 15.40 | 0.431046E+09 | 842.97 | 12-AUG-12:09 | 23.40 | 16.43 |
September | 0.363675E+10 | 13700.79 | 17-SEP-07:02 | 22.12 | 19.56 | 0.404729E+09 | 842.96 | 09-SEP-12:00 | 22.12 | 19.56 |
October | 0.184520E+10 | 3457.97 | 03-OCT-07:02 | 5.47 | 4.84 | 0.350374E+09 | 842.83 | 21-OCT-12:00 | 19.40 | 12.11 |
November | 0.711418E+09 | 4843.33 | 22-NOV-20:53 | -1.7 | -2.5 | 0.311728E+09 | 715.54 | 04-NOV-12:00 | -1.7 | -2.5 |
December | 63901817.64 | 4996.70 | 04-DEC-19:33 | -2.4 | -4.1 | 0.316799E+09 | 637.68 | 02-DEC-13:00 | -2.4 | -4.1 |
Annual Sum or Average | 0.244050E+11 | 0.430250E+10 | ||||||||
Minimum of Months | 26325856.05 | 3439.81 | -8.5 | -9.7 | 0.288103E+09 | 637.68 | -8.5 | -9.7 | ||
Maximum of Months | 0.521605E+10 | 18306.92 | 22.12 | 19.56 | 0.431046E+09 | 842.97 | 25.68 | 21.35 |
Report: ZoneCoolingSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 888081.83 | 487.57 | 21-JAN-12:00 | -0.6 | -3.2 | 0.108442E+10 | 1700.53 | 07-JAN-15:39 | -0.6 | -3.2 |
February | 5980396.87 | 3192.27 | 22-FEB-19:35 | 12.40 | 6.06 | 0.987308E+09 | 1700.53 | 04-FEB-15:30 | 12.40 | 6.06 |
March | 0.632058E+09 | 8063.07 | 21-MAR-19:03 | 2.20 | 0.12 | 0.114720E+10 | 1994.92 | 14-MAR-12:00 | 2.20 | 0.12 |
April | 0.153690E+10 | 6674.45 | 11-APR-09:43 | 5.00 | 3.28 | 0.110314E+10 | 2247.77 | 08-APR-14:20 | 5.00 | 3.28 |
May | 0.342702E+10 | 5662.89 | 27-MAY-14:20 | 21.70 | 12.29 | 0.130466E+10 | 2247.88 | 13-MAY-14:00 | 21.70 | 12.29 |
June | 0.628883E+10 | 19989.24 | 27-JUN-07:03 | 23.58 | 21.23 | 0.141700E+10 | 2247.89 | 10-JUN-14:20 | 23.58 | 21.23 |
July | 0.871286E+10 | 24820.79 | 26-JUL-07:03 | 20.87 | 17.48 | 0.143748E+10 | 2247.90 | 08-JUL-14:09 | 20.87 | 17.48 |
August | 0.863719E+10 | 30483.70 | 06-AUG-08:62 | 22.07 | 16.34 | 0.147806E+10 | 2247.97 | 26-AUG-14:09 | 25.37 | 21.59 |
September | 0.582680E+10 | 23999.54 | 17-SEP-08:62 | 21.70 | 19.45 | 0.138533E+10 | 2247.98 | 09-SEP-14:09 | 21.70 | 19.45 |
October | 0.274035E+10 | 6513.77 | 29-OCT-10:33 | 5.40 | 4.90 | 0.117763E+10 | 2247.76 | 21-OCT-14:09 | 5.40 | 4.90 |
November | 0.780137E+09 | 9278.66 | 22-NOV-18:42 | -0.4 | -1.7 | 0.105892E+10 | 2032.97 | 04-NOV-14:00 | -0.4 | -1.7 |
December | 18791604.54 | 2285.71 | 16-DEC-12:00 | 4.40 | 1.70 | 0.108625E+10 | 1700.53 | 02-DEC-15:30 | 4.40 | 1.70 |
Annual Sum or Average | 0.386078E+11 | 0.146674E+11 | ||||||||
Minimum of Months | 888081.83 | 487.57 | -0.6 | -3.2 | 0.987308E+09 | 1700.53 | -0.6 | -3.2 | ||
Maximum of Months | 0.871286E+10 | 30483.70 | 23.58 | 21.23 | 0.147806E+10 | 2247.98 | 25.37 | 21.59 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 235589.24 | 164.68 | 21-JAN-12:00 | -0.6 | -3.2 | 0.542193E+09 | 850.24 | 07-JAN-15:39 | -0.6 | -3.2 |
February | 2349062.02 | 1500.55 | 22-FEB-19:05 | 12.70 | 6.24 | 0.493640E+09 | 850.24 | 04-FEB-15:39 | 12.70 | 6.24 |
March | 0.297432E+09 | 3457.47 | 10-MAR-11:53 | 4.40 | 4.13 | 0.573368E+09 | 997.43 | 14-MAR-12:00 | 25.00 | 17.83 |
April | 0.706616E+09 | 2767.35 | 11-APR-12:15 | 7.07 | 4.71 | 0.550252E+09 | 1123.86 | 08-APR-14:20 | 7.07 | 4.71 |
May | 0.162740E+10 | 2801.53 | 27-MAY-14:30 | 21.70 | 12.26 | 0.648499E+09 | 1123.91 | 13-MAY-14:00 | 21.70 | 12.26 |
June | 0.315192E+10 | 9450.17 | 27-JUN-07:03 | 23.58 | 21.23 | 0.708104E+09 | 1123.91 | 10-JUN-14:20 | 23.58 | 21.23 |
July | 0.445327E+10 | 12249.38 | 18-JUL-07:03 | 20.18 | 18.92 | 0.718704E+09 | 1123.92 | 08-JUL-14:09 | 20.18 | 18.92 |
August | 0.440809E+10 | 15006.02 | 06-AUG-08:62 | 22.07 | 16.34 | 0.738978E+09 | 1123.96 | 26-AUG-14:09 | 25.37 | 21.59 |
September | 0.292482E+10 | 12338.16 | 17-SEP-08:62 | 21.70 | 19.45 | 0.692284E+09 | 1123.96 | 09-SEP-14:09 | 21.70 | 19.45 |
October | 0.128833E+10 | 3193.89 | 14-OCT-08:63 | 6.10 | 5.58 | 0.587191E+09 | 1123.85 | 21-OCT-14:20 | 19.40 | 12.01 |
November | 0.357832E+09 | 4511.64 | 22-NOV-18:23 | 0.00 | -1.4 | 0.528973E+09 | 1006.82 | 04-NOV-14:00 | 0.00 | -1.4 |
December | 7744619.99 | 1095.80 | 16-DEC-12:00 | 4.40 | 1.70 | 0.543112E+09 | 850.24 | 02-DEC-15:20 | 4.40 | 1.70 |
Annual Sum or Average | 0.192260E+11 | 0.732530E+10 | ||||||||
Minimum of Months | 235589.24 | 164.68 | -0.6 | -3.2 | 0.493640E+09 | 850.24 | -0.6 | -3.2 | ||
Maximum of Months | 0.445327E+10 | 15006.02 | 23.58 | 21.23 | 0.738978E+09 | 1123.96 | 25.37 | 21.59 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 121752.33 | 114.89 | 21-JAN-12:00 | -0.6 | -3.2 | 0.542193E+09 | 850.24 | 07-JAN-15:00 | -0.6 | -3.2 |
February | 1351196.98 | 277.90 | 18-FEB-12:00 | 1.10 | 0.02 | 0.493640E+09 | 850.24 | 04-FEB-15:50 | 1.10 | 0.02 |
March | 0.274716E+09 | 4055.17 | 25-MAR-17:03 | 1.70 | -1.7 | 0.573120E+09 | 997.43 | 14-MAR-16:10 | 1.70 | -1.7 |
April | 0.662228E+09 | 3762.70 | 14-APR-10:23 | 3.05 | 2.56 | 0.549084E+09 | 1123.86 | 08-APR-14:00 | 3.05 | 2.56 |
May | 0.155269E+10 | 2669.87 | 27-MAY-14:40 | 21.70 | 12.23 | 0.644251E+09 | 1123.91 | 13-MAY-14:00 | 21.70 | 12.23 |
June | 0.306239E+10 | 8862.88 | 27-JUN-07:03 | 23.58 | 21.23 | 0.707450E+09 | 1123.91 | 10-JUN-14:20 | 23.58 | 21.23 |
July | 0.438386E+10 | 11846.93 | 19-JUL-07:02 | 22.20 | 20.31 | 0.718691E+09 | 1123.92 | 08-JUL-14:09 | 22.20 | 20.31 |
August | 0.434104E+10 | 14481.04 | 06-AUG-08:62 | 22.07 | 16.34 | 0.738887E+09 | 1123.96 | 26-AUG-14:09 | 25.37 | 21.59 |
September | 0.285752E+10 | 12241.48 | 17-SEP-08:62 | 21.70 | 19.45 | 0.691491E+09 | 1123.96 | 09-SEP-14:09 | 21.70 | 19.45 |
October | 0.122808E+10 | 3170.77 | 14-OCT-08:63 | 6.10 | 5.58 | 0.585230E+09 | 1123.85 | 21-OCT-14:50 | 19.40 | 11.87 |
November | 0.331324E+09 | 3949.75 | 21-NOV-18:53 | 2.20 | 0.29 | 0.528634E+09 | 1001.97 | 04-NOV-14:00 | 2.20 | 0.29 |
December | 6899078.93 | 1057.39 | 16-DEC-12:00 | 4.40 | 1.70 | 0.543112E+09 | 850.24 | 16-DEC-15:00 | 4.40 | 2.29 |
Annual Sum or Average | 0.187022E+11 | 0.731578E+10 | ||||||||
Minimum of Months | 121752.33 | 114.89 | -0.6 | -3.2 | 0.493640E+09 | 850.24 | -0.6 | -3.2 | ||
Maximum of Months | 0.438386E+10 | 14481.04 | 23.58 | 21.23 | 0.738887E+09 | 1123.96 | 25.37 | 21.59 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | -1.0 | -1.6 | 0.542193E+09 | 850.24 | 07-JAN-15:30 | -1.7 | -3.6 |
February | 1139258.34 | 3468.93 | 17-FEB-11:43 | 4.32 | 1.26 | 0.493640E+09 | 850.24 | 04-FEB-15:00 | 4.32 | 1.26 |
March | 0.218227E+09 | 3970.83 | 02-MAR-18:03 | 2.12 | 0.39 | 0.572382E+09 | 997.43 | 14-MAR-16:10 | 23.72 | 16.32 |
April | 0.531489E+09 | 2254.58 | 01-APR-14:55 | 9.40 | 6.20 | 0.546120E+09 | 1123.86 | 08-APR-14:20 | 20.20 | 13.55 |
May | 0.136757E+10 | 2436.88 | 18-MAY-08:13 | 9.40 | 6.18 | 0.634462E+09 | 1123.90 | 13-MAY-14:00 | 9.40 | 6.18 |
June | 0.284340E+10 | 6415.82 | 27-JUN-07:03 | 23.58 | 21.23 | 0.705456E+09 | 1123.91 | 10-JUN-14:20 | 23.58 | 21.23 |
July | 0.422741E+10 | 11610.97 | 19-JUL-07:02 | 22.20 | 20.31 | 0.718652E+09 | 1123.93 | 08-JUL-14:09 | 22.20 | 20.31 |
August | 0.419205E+10 | 13123.51 | 07-AUG-07:02 | 21.20 | 18.87 | 0.738520E+09 | 1123.94 | 26-AUG-14:20 | 25.73 | 21.65 |
September | 0.268825E+10 | 12031.38 | 17-SEP-08:62 | 21.70 | 19.45 | 0.689099E+09 | 1123.96 | 09-SEP-14:09 | 21.70 | 19.45 |
October | 0.107996E+10 | 3777.22 | 24-OCT-09:13 | 2.97 | 0.67 | 0.580918E+09 | 1120.32 | 21-OCT-14:00 | 2.97 | 0.67 |
November | 0.247142E+09 | 3089.89 | 08-NOV-20:03 | 6.02 | 5.21 | 0.527621E+09 | 986.71 | 04-NOV-14:00 | 6.02 | 5.21 |
December | 3770093.33 | 857.81 | 16-DEC-12:00 | 4.40 | 1.70 | 0.543112E+09 | 850.24 | 02-DEC-15:30 | 4.40 | 1.70 |
Annual Sum or Average | 0.174004E+11 | 0.729217E+10 | ||||||||
Minimum of Months | 0.00 | 0.00 | -1.0 | -1.6 | 0.493640E+09 | 850.24 | -1.7 | -3.6 | ||
Maximum of Months | 0.422741E+10 | 13123.51 | 23.58 | 21.23 | 0.738520E+09 | 1123.96 | 25.73 | 21.65 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | -1.0 | -1.6 | 0.542193E+09 | 850.24 | 07-JAN-15:30 | -1.7 | -3.6 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -3.3 | -4.7 | 0.493640E+09 | 850.24 | 04-FEB-15:30 | -5.6 | -7.1 |
March | 0.105732E+09 | 2431.36 | 16-MAR-17:10 | 9.50 | 8.92 | 0.571072E+09 | 997.43 | 14-MAR-16:10 | 9.50 | 8.92 |
April | 0.298486E+09 | 3155.43 | 13-APR-17:23 | 5.55 | 3.07 | 0.541857E+09 | 1095.89 | 08-APR-14:09 | 5.55 | 3.07 |
May | 0.968612E+09 | 2331.30 | 11-MAY-19:15 | 8.90 | 8.33 | 0.620304E+09 | 1123.89 | 13-MAY-14:00 | 22.80 | 14.76 |
June | 0.262763E+10 | 5974.10 | 27-JUN-13:00 | 30.60 | 23.75 | 0.700244E+09 | 1123.90 | 10-JUN-14:20 | 30.60 | 23.75 |
July | 0.424057E+10 | 11193.37 | 22-JUL-07:02 | 21.10 | 20.28 | 0.718617E+09 | 1123.96 | 08-JUL-14:39 | 21.10 | 20.28 |
August | 0.421357E+10 | 13179.36 | 07-AUG-07:02 | 21.20 | 18.87 | 0.737424E+09 | 1123.95 | 26-AUG-14:30 | 26.10 | 21.71 |
September | 0.251167E+10 | 9625.87 | 17-SEP-08:62 | 21.70 | 19.45 | 0.683898E+09 | 1123.96 | 09-SEP-14:09 | 21.70 | 19.45 |
October | 0.772315E+09 | 3290.36 | 14-OCT-17:23 | 5.00 | 4.51 | 0.575880E+09 | 1109.38 | 21-OCT-14:00 | 19.40 | 11.82 |
November | 0.103948E+09 | 2222.31 | 01-NOV-16:25 | 9.40 | 6.45 | 0.526043E+09 | 956.09 | 04-NOV-14:00 | 18.30 | 13.74 |
December | 109057.40 | 157.12 | 16-DEC-12:00 | 4.40 | 1.70 | 0.543112E+09 | 850.24 | 02-DEC-15:30 | 4.40 | 1.70 |
Annual Sum or Average | 0.158426E+11 | 0.725429E+10 | ||||||||
Minimum of Months | 0.00 | 0.00 | -3.3 | -4.7 | 0.493640E+09 | 850.24 | -5.6 | -7.1 | ||
Maximum of Months | 0.424057E+10 | 13179.36 | 30.60 | 23.75 | 0.737424E+09 | 1123.96 | 30.60 | 23.75 |
Report: ZoneHeatingSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.855643E+10 | 59797.51 | 30-JAN-08:61 | -10.5 |
February | 0.826857E+10 | 60011.36 | 06-FEB-08:12 | -15.0 |
March | 0.385994E+10 | 59816.55 | 07-MAR-08:61 | -10.8 |
April | 0.119614E+10 | 59774.32 | 17-APR-07:01 | -2.9 |
May | 0.124447E+09 | 59723.95 | 01-MAY-07:01 | 6.05 |
June | 40663752.05 | 1344.44 | 18-JUN-07:05 | 23.48 |
July | 21137244.07 | 1481.08 | 15-JUL-07:05 | 23.07 |
August | 24184114.68 | 1541.49 | 06-AUG-07:04 | 20.28 |
September | 41100612.55 | 1353.48 | 14-SEP-07:05 | 20.60 |
October | 0.259252E+09 | 59772.19 | 17-OCT-07:01 | -2.4 |
November | 0.149816E+10 | 59778.00 | 22-NOV-08:61 | 1.10 |
December | 0.749074E+10 | 59810.62 | 11-DEC-08:61 | -14.8 |
Annual Sum or Average | 0.313808E+11 | |||
Minimum of Months | 21137244.07 | 1344.44 | -15.0 | |
Maximum of Months | 0.855643E+10 | 60011.36 | 23.48 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.282721E+10 | 31316.87 | 10-JAN-08:61 | -9.9 |
February | 0.275802E+10 | 31314.97 | 10-FEB-08:61 | -9.7 |
March | 0.102087E+10 | 31330.27 | 07-MAR-08:61 | -10.8 |
April | 0.221208E+09 | 31299.76 | 17-APR-07:01 | -2.9 |
May | 38734514.72 | 446.15 | 11-MAY-08:00 | 10.00 |
June | 12795718.98 | 813.37 | 12-JUN-07:07 | 24.08 |
July | 14479317.11 | 921.52 | 26-JUL-07:05 | 20.87 |
August | 14066301.92 | 911.59 | 11-AUG-07:05 | 18.40 |
September | 12572522.00 | 855.63 | 14-SEP-07:05 | 20.60 |
October | 55599052.42 | 28427.79 | 30-OCT-07:01 | 0.87 |
November | 0.304828E+09 | 31297.85 | 24-NOV-08:61 | -2.6 |
December | 0.248427E+10 | 31323.81 | 11-DEC-08:61 | -14.8 |
Annual Sum or Average | 0.976466E+10 | |||
Minimum of Months | 12572522.00 | 446.15 | -14.8 | |
Maximum of Months | 0.282721E+10 | 31330.27 | 24.08 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.343611E+10 | 31403.63 | 29-JAN-08:61 | -8.1 |
February | 0.326319E+10 | 31413.68 | 05-FEB-08:61 | -13.0 |
March | 0.133358E+10 | 31414.46 | 05-MAR-08:61 | -9.7 |
April | 0.343877E+09 | 31373.35 | 16-APR-07:01 | -3.7 |
May | 43128081.88 | 7828.58 | 01-MAY-06:03 | 2.35 |
June | 19055554.03 | 1402.34 | 17-JUN-17:03 | 28.80 |
July | 30554917.11 | 1663.06 | 16-JUL-16:02 | 30.03 |
August | 25754378.66 | 1376.41 | 13-AUG-16:03 | 29.03 |
September | 13814392.16 | 838.83 | 14-SEP-06:05 | 20.60 |
October | 89099554.61 | 29486.17 | 30-OCT-06:02 | -0.4 |
November | 0.544335E+09 | 31122.09 | 24-NOV-07:01 | -3.2 |
December | 0.302226E+10 | 31414.42 | 10-DEC-08:61 | -13.0 |
Annual Sum or Average | 0.121648E+11 | |||
Minimum of Months | 13814392.16 | 838.83 | -13.0 | |
Maximum of Months | 0.343611E+10 | 31414.46 | 30.03 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.367046E+10 | 31282.75 | 29-JAN-08:61 | -8.1 |
February | 0.346201E+10 | 31292.77 | 05-FEB-08:61 | -13.0 |
March | 0.147081E+10 | 31293.56 | 05-MAR-08:61 | -9.7 |
April | 0.407145E+09 | 31252.62 | 16-APR-07:01 | -3.7 |
May | 49070277.65 | 12242.63 | 01-MAY-06:03 | 2.35 |
June | 20091447.88 | 1405.23 | 17-JUN-17:03 | 28.80 |
July | 30567693.76 | 1664.22 | 16-JUL-16:02 | 30.03 |
August | 25793208.41 | 1377.45 | 13-AUG-16:03 | 29.03 |
September | 15439253.60 | 842.92 | 14-SEP-06:05 | 20.60 |
October | 0.111455E+09 | 30602.67 | 30-OCT-06:02 | -0.4 |
November | 0.645444E+09 | 31001.64 | 24-NOV-07:01 | -3.2 |
December | 0.323032E+10 | 31293.60 | 10-DEC-08:61 | -13.0 |
Annual Sum or Average | 0.131386E+11 | |||
Minimum of Months | 15439253.60 | 842.92 | -13.0 | |
Maximum of Months | 0.367046E+10 | 31293.60 | 30.03 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.406175E+10 | 31215.57 | 29-JAN-08:61 | -8.1 |
February | 0.381032E+10 | 31225.40 | 05-FEB-08:61 | -13.0 |
March | 0.170923E+10 | 31226.22 | 05-MAR-08:61 | -9.7 |
April | 0.512954E+09 | 31185.48 | 16-APR-07:01 | -3.7 |
May | 57891763.53 | 15828.15 | 01-MAY-06:03 | 2.35 |
June | 22688360.88 | 1412.14 | 17-JUN-17:03 | 28.80 |
July | 30649122.08 | 1668.25 | 16-JUL-16:02 | 30.03 |
August | 25746847.39 | 1383.05 | 13-AUG-16:03 | 29.03 |
September | 18293076.77 | 815.73 | 14-SEP-06:05 | 20.60 |
October | 0.141009E+09 | 30544.22 | 30-OCT-06:02 | -0.4 |
November | 0.801157E+09 | 30938.20 | 24-NOV-07:01 | -3.2 |
December | 0.359426E+10 | 31226.26 | 10-DEC-08:61 | -13.0 |
Annual Sum or Average | 0.147859E+11 | |||
Minimum of Months | 18293076.77 | 815.73 | -13.0 | |
Maximum of Months | 0.406175E+10 | 31226.26 | 30.03 |
Report: ZoneHeatingSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.831183E+10 | 57888.03 | 10-JAN-08:61 | -9.9 |
February | 0.772863E+10 | 58149.46 | 06-FEB-08:12 | -15.0 |
March | 0.354281E+10 | 57908.32 | 07-MAR-08:61 | -10.8 |
April | 0.115416E+10 | 57863.29 | 17-APR-07:01 | -2.9 |
May | 0.141748E+09 | 57824.73 | 08-MAY-07:01 | 5.87 |
June | 51883950.85 | 2820.87 | 17-JUN-17:03 | 28.80 |
July | 38615021.98 | 3332.78 | 16-JUL-16:02 | 30.03 |
August | 39241147.79 | 2782.75 | 13-AUG-16:03 | 29.03 |
September | 44319962.38 | 1382.97 | 17-SEP-08:05 | 21.70 |
October | 0.364458E+09 | 57860.73 | 17-OCT-07:01 | -2.4 |
November | 0.174466E+10 | 57861.58 | 22-NOV-08:61 | 1.10 |
December | 0.737701E+10 | 58080.95 | 11-DEC-08:12 | -14.6 |
Annual Sum or Average | 0.305394E+11 | |||
Minimum of Months | 38615021.98 | 1382.97 | -15.0 | |
Maximum of Months | 0.831183E+10 | 58149.46 | 30.03 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.463503E+10 | 29559.38 | 10-JAN-08:61 | -9.9 |
February | 0.431189E+10 | 29760.67 | 06-FEB-08:12 | -15.0 |
March | 0.208040E+10 | 29570.11 | 07-MAR-08:61 | -10.8 |
April | 0.708922E+09 | 29545.42 | 17-APR-07:01 | -2.9 |
May | 82645245.80 | 29525.98 | 08-MAY-07:01 | 5.87 |
June | 28646998.70 | 1428.99 | 17-JUN-17:03 | 28.80 |
July | 20014559.82 | 1678.86 | 16-JUL-16:02 | 30.03 |
August | 20330660.73 | 1402.13 | 13-AUG-16:03 | 29.03 |
September | 25345534.04 | 732.95 | 17-SEP-08:05 | 21.70 |
October | 0.220079E+09 | 29543.93 | 17-OCT-07:01 | -2.4 |
November | 0.105779E+10 | 29542.99 | 22-NOV-08:61 | 1.10 |
December | 0.413778E+10 | 29715.73 | 11-DEC-08:12 | -14.6 |
Annual Sum or Average | 0.173289E+11 | |||
Minimum of Months | 20014559.82 | 732.95 | -15.0 | |
Maximum of Months | 0.463503E+10 | 29760.67 | 30.03 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.471505E+10 | 29419.44 | 10-JAN-08:61 | -9.9 |
February | 0.437938E+10 | 29634.10 | 06-FEB-08:12 | -15.0 |
March | 0.215532E+10 | 29430.05 | 07-MAR-08:61 | -10.8 |
April | 0.760457E+09 | 29405.16 | 17-APR-07:01 | -2.9 |
May | 92925991.55 | 29386.19 | 08-MAY-07:01 | 5.87 |
June | 29356633.94 | 1431.48 | 17-JUN-17:03 | 28.80 |
July | 19703600.57 | 1679.85 | 16-JUL-16:02 | 30.03 |
August | 20252549.26 | 1403.69 | 13-AUG-16:03 | 29.03 |
September | 26863948.94 | 726.28 | 17-SEP-08:05 | 21.70 |
October | 0.237106E+09 | 29404.01 | 17-OCT-07:01 | -2.4 |
November | 0.111498E+10 | 29403.32 | 22-NOV-08:61 | 1.10 |
December | 0.421505E+10 | 29589.06 | 11-DEC-08:12 | -14.6 |
Annual Sum or Average | 0.177664E+11 | |||
Minimum of Months | 19703600.57 | 726.28 | -15.0 | |
Maximum of Months | 0.471505E+10 | 29634.10 | 30.03 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.517803E+10 | 29291.81 | 31-JAN-08:12 | -11.3 |
February | 0.479362E+10 | 29427.08 | 06-FEB-08:12 | -15.0 |
March | 0.253779E+10 | 29193.91 | 07-MAR-08:61 | -10.8 |
April | 0.984104E+09 | 29172.17 | 17-APR-07:01 | -2.9 |
May | 0.132554E+09 | 29152.66 | 08-MAY-07:01 | 5.87 |
June | 33380083.73 | 1438.28 | 17-JUN-17:03 | 28.80 |
July | 19085163.80 | 1681.28 | 16-JUL-16:02 | 30.03 |
August | 20749420.42 | 1407.18 | 13-AUG-16:03 | 29.03 |
September | 32424742.55 | 5710.61 | 30-SEP-07:02 | 8.17 |
October | 0.325351E+09 | 29169.62 | 17-OCT-07:01 | -2.4 |
November | 0.134641E+10 | 29170.01 | 22-NOV-08:61 | 1.10 |
December | 0.464697E+10 | 29404.41 | 11-DEC-08:12 | -14.6 |
Annual Sum or Average | 0.200505E+11 | |||
Minimum of Months | 19085163.80 | 1407.18 | -15.0 | |
Maximum of Months | 0.517803E+10 | 29427.08 | 30.03 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.807958E+10 | 30309.38 | 31-JAN-08:12 | -11.3 |
February | 0.768604E+10 | 30399.81 | 06-FEB-08:12 | -15.0 |
March | 0.449963E+10 | 30184.42 | 25-MAR-07:12 | -4.6 |
April | 0.202363E+10 | 30042.37 | 17-APR-07:01 | -2.9 |
May | 0.362179E+09 | 29977.64 | 08-MAY-07:01 | 5.87 |
June | 41299236.50 | 6977.22 | 14-JUN-07:03 | 10.18 |
July | 22437040.36 | 1680.69 | 16-JUL-16:02 | 30.03 |
August | 27594234.88 | 1404.85 | 13-AUG-16:03 | 29.03 |
September | 47790317.67 | 26631.30 | 30-SEP-07:02 | 8.17 |
October | 0.706740E+09 | 30000.83 | 17-OCT-07:01 | -2.4 |
November | 0.243312E+10 | 30005.43 | 22-NOV-08:61 | 1.10 |
December | 0.725245E+10 | 30358.30 | 11-DEC-08:12 | -14.6 |
Annual Sum or Average | 0.331825E+11 | |||
Minimum of Months | 22437040.36 | 1404.85 | -15.0 | |
Maximum of Months | 0.807958E+10 | 30399.81 | 30.03 |
Report: ZoneElectricSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.739462E+10 | 4621.63 | 01-JAN-10:09 | 0.222596E+10 | 1343.25 | 01-JAN-10:09 |
February | 0.668410E+10 | 4621.63 | 01-FEB-10:09 | 0.201408E+10 | 1343.25 | 01-FEB-10:09 |
March | 0.740180E+10 | 4621.63 | 01-MAR-10:09 | 0.223295E+10 | 1343.25 | 01-MAR-10:09 |
April | 0.716384E+10 | 4621.63 | 01-APR-09:09 | 0.215748E+10 | 1343.25 | 01-APR-09:09 |
May | 0.739462E+10 | 4621.63 | 01-MAY-09:09 | 0.222596E+10 | 1343.25 | 01-MAY-09:09 |
June | 0.716485E+10 | 4621.63 | 01-JUN-09:09 | 0.216232E+10 | 1343.25 | 01-JUN-09:09 |
July | 0.740069E+10 | 4621.63 | 01-JUL-09:09 | 0.222811E+10 | 1343.25 | 01-JUL-09:09 |
August | 0.739513E+10 | 4621.63 | 01-AUG-09:09 | 0.222838E+10 | 1343.25 | 01-AUG-09:09 |
September | 0.717041E+10 | 4621.63 | 01-SEP-09:09 | 0.216205E+10 | 1343.25 | 01-SEP-09:09 |
October | 0.739462E+10 | 4621.63 | 01-OCT-09:09 | 0.222596E+10 | 1343.25 | 01-OCT-09:09 |
November | 0.714323E+10 | 4621.63 | 01-NOV-09:09 | 0.215077E+10 | 1343.25 | 01-NOV-09:09 |
December | 0.740776E+10 | 4621.63 | 01-DEC-10:09 | 0.223509E+10 | 1343.25 | 01-DEC-10:09 |
Annual Sum or Average | 0.871157E+11 | 0.262491E+11 | ||||
Minimum of Months | 0.668410E+10 | 4621.63 | 0.201408E+10 | 1343.25 | ||
Maximum of Months | 0.740776E+10 | 4621.63 | 0.223509E+10 | 1343.25 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.451584E+10 | 2827.07 | 01-JAN-10:09 | 0.111298E+10 | 671.63 | 01-JAN-10:09 |
February | 0.408193E+10 | 2827.07 | 01-FEB-10:09 | 0.100704E+10 | 671.63 | 01-FEB-10:09 |
March | 0.452026E+10 | 2827.07 | 01-MAR-10:09 | 0.111647E+10 | 671.63 | 01-MAR-10:09 |
April | 0.437489E+10 | 2827.07 | 01-APR-09:09 | 0.107874E+10 | 671.63 | 01-APR-09:09 |
May | 0.451584E+10 | 2827.07 | 01-MAY-09:09 | 0.111298E+10 | 671.63 | 01-MAY-09:09 |
June | 0.437556E+10 | 2827.07 | 01-JUN-09:09 | 0.108116E+10 | 671.63 | 01-JUN-09:09 |
July | 0.451952E+10 | 2827.07 | 01-JUL-09:09 | 0.111405E+10 | 671.63 | 01-JUL-09:09 |
August | 0.451617E+10 | 2827.07 | 01-AUG-09:09 | 0.111419E+10 | 671.63 | 01-AUG-09:09 |
September | 0.437891E+10 | 2827.07 | 01-SEP-09:09 | 0.108102E+10 | 671.63 | 01-SEP-09:09 |
October | 0.451584E+10 | 2827.07 | 01-OCT-09:09 | 0.111298E+10 | 671.63 | 01-OCT-09:09 |
November | 0.436230E+10 | 2827.07 | 01-NOV-09:09 | 0.107538E+10 | 671.63 | 01-NOV-09:09 |
December | 0.452388E+10 | 2827.07 | 01-DEC-10:09 | 0.111755E+10 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.532009E+11 | 0.131245E+11 | ||||
Minimum of Months | 0.408193E+10 | 2827.07 | 0.100704E+10 | 671.63 | ||
Maximum of Months | 0.452388E+10 | 2827.07 | 0.111755E+10 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.317044E+10 | 2555.22 | 01-JAN-10:09 | 0.879849E+09 | 671.63 | 01-JAN-10:09 |
February | 0.287181E+10 | 2555.22 | 01-FEB-09:09 | 0.796766E+09 | 671.63 | 01-FEB-09:09 |
March | 0.324295E+10 | 2555.22 | 01-MAR-09:09 | 0.898128E+09 | 671.63 | 01-MAR-09:09 |
April | 0.307694E+10 | 2555.22 | 01-APR-08:09 | 0.853677E+09 | 671.63 | 01-APR-08:09 |
May | 0.320669E+10 | 2555.22 | 01-MAY-08:09 | 0.888989E+09 | 671.63 | 01-MAY-08:09 |
June | 0.313132E+10 | 2555.22 | 01-JUN-08:09 | 0.867387E+09 | 671.63 | 01-JUN-08:09 |
July | 0.315231E+10 | 2555.22 | 01-JUL-08:09 | 0.875279E+09 | 671.63 | 01-JUL-08:09 |
August | 0.324295E+10 | 2555.22 | 01-AUG-08:09 | 0.898128E+09 | 671.63 | 01-AUG-08:09 |
September | 0.307694E+10 | 2555.22 | 01-SEP-08:09 | 0.853677E+09 | 671.63 | 01-SEP-08:09 |
October | 0.317044E+10 | 2555.22 | 01-OCT-09:09 | 0.879849E+09 | 671.63 | 01-OCT-09:09 |
November | 0.307694E+10 | 2555.22 | 01-NOV-08:09 | 0.853679E+09 | 671.63 | 01-NOV-08:09 |
December | 0.315231E+10 | 2555.22 | 01-DEC-09:09 | 0.875279E+09 | 671.63 | 01-DEC-09:09 |
Annual Sum or Average | 0.375720E+11 | 0.104207E+11 | ||||
Minimum of Months | 0.287181E+10 | 2555.22 | 0.796766E+09 | 671.63 | ||
Maximum of Months | 0.324295E+10 | 2555.22 | 0.898128E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.317044E+10 | 2555.22 | 01-JAN-10:09 | 0.879849E+09 | 671.63 | 01-JAN-10:09 |
February | 0.287181E+10 | 2555.22 | 01-FEB-09:09 | 0.796766E+09 | 671.63 | 01-FEB-09:09 |
March | 0.324295E+10 | 2555.22 | 01-MAR-09:09 | 0.898128E+09 | 671.63 | 01-MAR-09:09 |
April | 0.307694E+10 | 2555.22 | 01-APR-08:09 | 0.853677E+09 | 671.63 | 01-APR-08:09 |
May | 0.320669E+10 | 2555.22 | 01-MAY-08:09 | 0.888989E+09 | 671.63 | 01-MAY-08:09 |
June | 0.313132E+10 | 2555.22 | 01-JUN-08:09 | 0.867387E+09 | 671.63 | 01-JUN-08:09 |
July | 0.315231E+10 | 2555.22 | 01-JUL-08:09 | 0.875279E+09 | 671.63 | 01-JUL-08:09 |
August | 0.324295E+10 | 2555.22 | 01-AUG-08:09 | 0.898128E+09 | 671.63 | 01-AUG-08:09 |
September | 0.307694E+10 | 2555.22 | 01-SEP-08:09 | 0.853677E+09 | 671.63 | 01-SEP-08:09 |
October | 0.317044E+10 | 2555.22 | 01-OCT-09:09 | 0.879849E+09 | 671.63 | 01-OCT-09:09 |
November | 0.307694E+10 | 2555.22 | 01-NOV-08:09 | 0.853679E+09 | 671.63 | 01-NOV-08:09 |
December | 0.315231E+10 | 2555.22 | 01-DEC-09:09 | 0.875279E+09 | 671.63 | 01-DEC-09:09 |
Annual Sum or Average | 0.375720E+11 | 0.104207E+11 | ||||
Minimum of Months | 0.287181E+10 | 2555.22 | 0.796766E+09 | 671.63 | ||
Maximum of Months | 0.324295E+10 | 2555.22 | 0.898128E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.317044E+10 | 2555.22 | 01-JAN-10:09 | 0.879849E+09 | 671.63 | 01-JAN-10:09 |
February | 0.287181E+10 | 2555.22 | 01-FEB-09:09 | 0.796766E+09 | 671.63 | 01-FEB-09:09 |
March | 0.324295E+10 | 2555.22 | 01-MAR-09:09 | 0.898128E+09 | 671.63 | 01-MAR-09:09 |
April | 0.307694E+10 | 2555.22 | 01-APR-08:09 | 0.853677E+09 | 671.63 | 01-APR-08:09 |
May | 0.320669E+10 | 2555.22 | 01-MAY-08:09 | 0.888989E+09 | 671.63 | 01-MAY-08:09 |
June | 0.313132E+10 | 2555.22 | 01-JUN-08:09 | 0.867387E+09 | 671.63 | 01-JUN-08:09 |
July | 0.315231E+10 | 2555.22 | 01-JUL-08:09 | 0.875279E+09 | 671.63 | 01-JUL-08:09 |
August | 0.324295E+10 | 2555.22 | 01-AUG-08:09 | 0.898128E+09 | 671.63 | 01-AUG-08:09 |
September | 0.307694E+10 | 2555.22 | 01-SEP-08:09 | 0.853677E+09 | 671.63 | 01-SEP-08:09 |
October | 0.317044E+10 | 2555.22 | 01-OCT-09:09 | 0.879849E+09 | 671.63 | 01-OCT-09:09 |
November | 0.307694E+10 | 2555.22 | 01-NOV-08:09 | 0.853679E+09 | 671.63 | 01-NOV-08:09 |
December | 0.315231E+10 | 2555.22 | 01-DEC-09:09 | 0.875279E+09 | 671.63 | 01-DEC-09:09 |
Annual Sum or Average | 0.375720E+11 | 0.104207E+11 | ||||
Minimum of Months | 0.287181E+10 | 2555.22 | 0.796766E+09 | 671.63 | ||
Maximum of Months | 0.324295E+10 | 2555.22 | 0.898128E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.313454E+10 | 2726.96 | 01-JAN-11:09 | 0.161799E+10 | 1343.25 | 01-JAN-11:09 |
February | 0.283982E+10 | 2726.96 | 01-FEB-10:09 | 0.146554E+10 | 1343.25 | 01-FEB-10:09 |
March | 0.321092E+10 | 2726.96 | 01-MAR-10:09 | 0.165455E+10 | 1343.25 | 01-MAR-10:09 |
April | 0.304266E+10 | 2726.96 | 01-APR-09:09 | 0.157022E+10 | 1343.25 | 01-APR-09:09 |
May | 0.317273E+10 | 2726.96 | 01-MAY-09:09 | 0.163627E+10 | 1343.25 | 01-MAY-09:09 |
June | 0.309995E+10 | 2726.96 | 01-JUN-09:09 | 0.159764E+10 | 1343.25 | 01-JUN-09:09 |
July | 0.311545E+10 | 2726.96 | 01-JUL-09:09 | 0.160885E+10 | 1343.25 | 01-JUL-09:09 |
August | 0.321092E+10 | 2726.96 | 01-AUG-09:09 | 0.165455E+10 | 1343.25 | 01-AUG-09:09 |
September | 0.304266E+10 | 2726.96 | 01-SEP-09:09 | 0.157022E+10 | 1343.25 | 01-SEP-09:09 |
October | 0.313454E+10 | 2726.96 | 01-OCT-10:09 | 0.161799E+10 | 1343.25 | 01-OCT-10:09 |
November | 0.304266E+10 | 2726.96 | 01-NOV-09:09 | 0.157022E+10 | 1343.25 | 01-NOV-09:09 |
December | 0.311545E+10 | 2726.96 | 01-DEC-10:09 | 0.160885E+10 | 1343.25 | 01-DEC-10:09 |
Annual Sum or Average | 0.371623E+11 | 0.191729E+11 | ||||
Minimum of Months | 0.283982E+10 | 2726.96 | 0.146554E+10 | 1343.25 | ||
Maximum of Months | 0.321092E+10 | 2726.96 | 0.165455E+10 | 1343.25 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.161274E+10 | 1404.46 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.146111E+10 | 1404.46 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.165211E+10 | 1404.46 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.156548E+10 | 1404.46 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.163243E+10 | 1404.46 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.159501E+10 | 1404.46 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.160290E+10 | 1404.46 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.165211E+10 | 1404.46 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.156548E+10 | 1404.46 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.161274E+10 | 1404.46 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.156548E+10 | 1404.46 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.160290E+10 | 1404.46 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.191205E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.146111E+10 | 1404.46 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.165211E+10 | 1404.46 | 0.827277E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.161274E+10 | 1404.46 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.146111E+10 | 1404.46 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.165211E+10 | 1404.46 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.156548E+10 | 1404.46 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.163243E+10 | 1404.46 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.159501E+10 | 1404.46 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.160290E+10 | 1404.46 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.165211E+10 | 1404.46 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.156548E+10 | 1404.46 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.161274E+10 | 1404.46 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.156548E+10 | 1404.46 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.160290E+10 | 1404.46 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.191205E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.146111E+10 | 1404.46 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.165211E+10 | 1404.46 | 0.827277E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.161274E+10 | 1404.46 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.146111E+10 | 1404.46 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.165211E+10 | 1404.46 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.156548E+10 | 1404.46 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.163243E+10 | 1404.46 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.159501E+10 | 1404.46 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.160290E+10 | 1404.46 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.165211E+10 | 1404.46 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.156548E+10 | 1404.46 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.161274E+10 | 1404.46 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.156548E+10 | 1404.46 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.160290E+10 | 1404.46 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.191205E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.146111E+10 | 1404.46 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.165211E+10 | 1404.46 | 0.827277E+09 | 671.63 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.161274E+10 | 1404.46 | 01-JAN-11:09 | 0.808994E+09 | 671.63 | 01-JAN-11:09 |
February | 0.146111E+10 | 1404.46 | 01-FEB-10:09 | 0.732769E+09 | 671.63 | 01-FEB-10:09 |
March | 0.165211E+10 | 1404.46 | 01-MAR-10:09 | 0.827277E+09 | 671.63 | 01-MAR-10:09 |
April | 0.156548E+10 | 1404.46 | 01-APR-09:09 | 0.785109E+09 | 671.63 | 01-APR-09:09 |
May | 0.163243E+10 | 1404.46 | 01-MAY-09:09 | 0.818135E+09 | 671.63 | 01-MAY-09:09 |
June | 0.159501E+10 | 1404.46 | 01-JUN-09:09 | 0.798821E+09 | 671.63 | 01-JUN-09:09 |
July | 0.160290E+10 | 1404.46 | 01-JUL-09:09 | 0.804424E+09 | 671.63 | 01-JUL-09:09 |
August | 0.165211E+10 | 1404.46 | 01-AUG-09:09 | 0.827277E+09 | 671.63 | 01-AUG-09:09 |
September | 0.156548E+10 | 1404.46 | 01-SEP-09:09 | 0.785109E+09 | 671.63 | 01-SEP-09:09 |
October | 0.161274E+10 | 1404.46 | 01-OCT-10:09 | 0.808994E+09 | 671.63 | 01-OCT-10:09 |
November | 0.156548E+10 | 1404.46 | 01-NOV-09:09 | 0.785109E+09 | 671.63 | 01-NOV-09:09 |
December | 0.160290E+10 | 1404.46 | 01-DEC-10:09 | 0.804424E+09 | 671.63 | 01-DEC-10:09 |
Annual Sum or Average | 0.191205E+11 | 0.958644E+10 | ||||
Minimum of Months | 0.146111E+10 | 1404.46 | 0.732769E+09 | 671.63 | ||
Maximum of Months | 0.165211E+10 | 1404.46 | 0.827277E+09 | 671.63 |
Report: SpaceGainsMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.338624E+10 | 0.739462E+10 | 0.222596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.769967E+10 |
February | 0.305697E+10 | 0.668410E+10 | 0.201408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.746639E+10 |
March | 0.335708E+10 | 0.740180E+10 | 0.223295E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11414036.15 | 0.527380E+10 |
April | 0.327081E+10 | 0.716384E+10 | 0.215748E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.349272E+10 |
May | 0.336680E+10 | 0.739462E+10 | 0.222596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10366661.45 | 0.195807E+10 |
June | 0.325380E+10 | 0.716485E+10 | 0.216232E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.184212E+09 | 0.103568E+10 |
July | 0.339353E+10 | 0.740069E+10 | 0.222811E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.443745E+09 | 0.365624E+09 |
August | 0.334857E+10 | 0.739513E+10 | 0.222838E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.372461E+09 | 0.542714E+09 |
September | 0.327932E+10 | 0.717041E+10 | 0.216205E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35643837.90 | 0.132512E+10 |
October | 0.338624E+10 | 0.739462E+10 | 0.222596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.310644E+10 |
November | 0.327446E+10 | 0.714323E+10 | 0.215077E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.426208E+10 |
December | 0.340325E+10 | 0.740776E+10 | 0.223509E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.755492E+10 |
Annual Sum or Average | 0.397770E+11 | 0.871157E+11 | 0.262491E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105784E+10 | 0.440832E+11 |
Minimum of Months | 0.305697E+10 | 0.668410E+10 | 0.201408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.365624E+09 |
Maximum of Months | 0.340325E+10 | 0.740776E+10 | 0.223509E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.443745E+09 | 0.769967E+10 |
Report: SpaceGainsMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.169307E+10 | 0.451584E+10 | 0.111298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.371476E+10 |
February | 0.152844E+10 | 0.408193E+10 | 0.100704E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.354745E+10 |
March | 0.167849E+10 | 0.452026E+10 | 0.111647E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6181521.12 | 0.257850E+10 |
April | 0.163536E+10 | 0.437489E+10 | 0.107874E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171053E+10 |
May | 0.168335E+10 | 0.451584E+10 | 0.111298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5593653.37 | 0.993857E+09 |
June | 0.162685E+10 | 0.437556E+10 | 0.108116E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 97855355.48 | 0.474076E+09 |
July | 0.169671E+10 | 0.451952E+10 | 0.111405E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.236800E+09 | 0.145918E+09 |
August | 0.167424E+10 | 0.451617E+10 | 0.111419E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.200316E+09 | 0.229965E+09 |
September | 0.163961E+10 | 0.437891E+10 | 0.108102E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19255646.18 | 0.637674E+09 |
October | 0.169307E+10 | 0.451584E+10 | 0.111298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154312E+10 |
November | 0.163718E+10 | 0.436230E+10 | 0.107538E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.207121E+10 |
December | 0.170157E+10 | 0.452388E+10 | 0.111755E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.361670E+10 |
Annual Sum or Average | 0.198880E+11 | 0.532009E+11 | 0.131245E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.566003E+09 | 0.212638E+11 |
Minimum of Months | 0.152844E+10 | 0.408193E+10 | 0.100704E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.145918E+09 |
Maximum of Months | 0.170157E+10 | 0.452388E+10 | 0.111755E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.236800E+09 | 0.371476E+10 |
Report: SpaceGainsMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.317044E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.382606E+10 |
February | 0.914877E+09 | 0.287181E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.365993E+10 |
March | 0.103395E+10 | 0.324295E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6181588.78 | 0.264459E+10 |
April | 0.984131E+09 | 0.307694E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.176219E+10 |
May | 0.102058E+10 | 0.320669E+10 | 0.888989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5593736.93 | 0.101777E+10 |
June | 0.998711E+09 | 0.313132E+10 | 0.867387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 94586405.33 | 0.499138E+09 |
July | 0.100600E+10 | 0.315231E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230847E+09 | 0.169611E+09 |
August | 0.103395E+10 | 0.324295E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.195843E+09 | 0.254311E+09 |
September | 0.984131E+09 | 0.307694E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19086448.18 | 0.664751E+09 |
October | 0.100722E+10 | 0.317044E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157354E+10 |
November | 0.973196E+09 | 0.307694E+10 | 0.853679E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.212029E+10 |
December | 0.100600E+10 | 0.315231E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.374553E+10 |
Annual Sum or Average | 0.119700E+11 | 0.375720E+11 | 0.104207E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.552138E+09 | 0.219377E+11 |
Minimum of Months | 0.914877E+09 | 0.287181E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169611E+09 |
Maximum of Months | 0.103395E+10 | 0.324295E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230847E+09 | 0.382606E+10 |
Report: SpaceGainsMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.317044E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.381883E+10 |
February | 0.914877E+09 | 0.287181E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.365253E+10 |
March | 0.103395E+10 | 0.324295E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6181641.43 | 0.263818E+10 |
April | 0.984131E+09 | 0.307694E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175039E+10 |
May | 0.102058E+10 | 0.320669E+10 | 0.888989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5593736.63 | 0.100397E+10 |
June | 0.998711E+09 | 0.313132E+10 | 0.867387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 94593964.11 | 0.498156E+09 |
July | 0.100600E+10 | 0.315231E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230816E+09 | 0.169783E+09 |
August | 0.103395E+10 | 0.324295E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.195833E+09 | 0.254398E+09 |
September | 0.984131E+09 | 0.307694E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19086555.66 | 0.662614E+09 |
October | 0.100722E+10 | 0.317044E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156076E+10 |
November | 0.973196E+09 | 0.307694E+10 | 0.853679E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.211137E+10 |
December | 0.100600E+10 | 0.315231E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.373780E+10 |
Annual Sum or Average | 0.119700E+11 | 0.375720E+11 | 0.104207E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.552105E+09 | 0.218588E+11 |
Minimum of Months | 0.914877E+09 | 0.287181E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169783E+09 |
Maximum of Months | 0.103395E+10 | 0.324295E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230816E+09 | 0.381883E+10 |
Report: SpaceGainsMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.317044E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.381262E+10 |
February | 0.914877E+09 | 0.287181E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.364638E+10 |
March | 0.103395E+10 | 0.324295E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6181755.40 | 0.263126E+10 |
April | 0.984131E+09 | 0.307694E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.173630E+10 |
May | 0.102058E+10 | 0.320669E+10 | 0.888989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5593736.27 | 0.982460E+09 |
June | 0.998711E+09 | 0.313132E+10 | 0.867387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 94659259.79 | 0.494157E+09 |
July | 0.100600E+10 | 0.315231E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230982E+09 | 0.167560E+09 |
August | 0.103395E+10 | 0.324295E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.195904E+09 | 0.252175E+09 |
September | 0.984131E+09 | 0.307694E+10 | 0.853677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19088254.16 | 0.657449E+09 |
October | 0.100722E+10 | 0.317044E+10 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154485E+10 |
November | 0.973196E+09 | 0.307694E+10 | 0.853679E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.210254E+10 |
December | 0.100600E+10 | 0.315231E+10 | 0.875279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.373110E+10 |
Annual Sum or Average | 0.119700E+11 | 0.375720E+11 | 0.104207E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.552409E+09 | 0.217589E+11 |
Minimum of Months | 0.914877E+09 | 0.287181E+10 | 0.796766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.167560E+09 |
Maximum of Months | 0.103395E+10 | 0.324295E+10 | 0.898128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230982E+09 | 0.381262E+10 |
Report: SpaceGainsMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.344359E+10 | 0.313454E+10 | 0.161799E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.702971E+10 |
February | 0.313522E+10 | 0.283982E+10 | 0.146554E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.674749E+10 |
March | 0.355148E+10 | 0.321092E+10 | 0.165455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11125693.14 | 0.484122E+10 |
April | 0.338259E+10 | 0.304266E+10 | 0.157022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.318570E+10 |
May | 0.349753E+10 | 0.317273E+10 | 0.163627E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10070360.91 | 0.175796E+10 |
June | 0.343071E+10 | 0.309995E+10 | 0.159764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171128E+09 | 0.916393E+09 |
July | 0.344942E+10 | 0.311545E+10 | 0.160885E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.417514E+09 | 0.318000E+09 |
August | 0.355148E+10 | 0.321092E+10 | 0.165455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.353377E+09 | 0.475245E+09 |
September | 0.338259E+10 | 0.304266E+10 | 0.157022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34363744.00 | 0.121044E+10 |
October | 0.344359E+10 | 0.313454E+10 | 0.161799E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.281561E+10 |
November | 0.331698E+10 | 0.304266E+10 | 0.157022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.387093E+10 |
December | 0.344942E+10 | 0.311545E+10 | 0.160885E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.689227E+10 |
Annual Sum or Average | 0.410346E+11 | 0.371623E+11 | 0.191729E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.997580E+09 | 0.400610E+11 |
Minimum of Months | 0.313522E+10 | 0.283982E+10 | 0.146554E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.318000E+09 |
Maximum of Months | 0.355148E+10 | 0.321092E+10 | 0.165455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.417514E+09 | 0.702971E+10 |
Report: SpaceGainsMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.161274E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.383275E+10 |
February | 0.156756E+10 | 0.146111E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.367022E+10 |
March | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6184079.87 | 0.264135E+10 |
April | 0.169125E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172811E+10 |
May | 0.174872E+10 | 0.163243E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5593734.70 | 0.945689E+09 |
June | 0.171530E+10 | 0.159501E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 94936868.75 | 0.491957E+09 |
July | 0.172466E+10 | 0.160290E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.231797E+09 | 0.166524E+09 |
August | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.196353E+09 | 0.252005E+09 |
September | 0.169125E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19094706.66 | 0.655546E+09 |
October | 0.172174E+10 | 0.161274E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.152964E+10 |
November | 0.165844E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.210685E+10 |
December | 0.172466E+10 | 0.160290E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.375135E+10 |
Annual Sum or Average | 0.205167E+11 | 0.191205E+11 | 0.958644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.553960E+09 | 0.217720E+11 |
Minimum of Months | 0.156756E+10 | 0.146111E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166524E+09 |
Maximum of Months | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.231797E+09 | 0.383275E+10 |
Report: SpaceGainsMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.161274E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.383126E+10 |
February | 0.156756E+10 | 0.146111E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.366887E+10 |
March | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6185066.80 | 0.263927E+10 |
April | 0.169125E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172354E+10 |
May | 0.174872E+10 | 0.163243E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5593734.54 | 0.934541E+09 |
June | 0.171530E+10 | 0.159501E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 94968594.32 | 0.489432E+09 |
July | 0.172466E+10 | 0.160290E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.231862E+09 | 0.165814E+09 |
August | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.196390E+09 | 0.251233E+09 |
September | 0.169125E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19095158.85 | 0.653091E+09 |
October | 0.172174E+10 | 0.161274E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.152389E+10 |
November | 0.165844E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.210431E+10 |
December | 0.172466E+10 | 0.160290E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.374969E+10 |
Annual Sum or Average | 0.205167E+11 | 0.191205E+11 | 0.958644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.554094E+09 | 0.217349E+11 |
Minimum of Months | 0.156756E+10 | 0.146111E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165814E+09 |
Maximum of Months | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.231862E+09 | 0.383126E+10 |
Report: SpaceGainsMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.161274E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.382212E+10 |
February | 0.156756E+10 | 0.146111E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.366078E+10 |
March | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6211358.03 | 0.263044E+10 |
April | 0.169125E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.170955E+10 |
May | 0.174872E+10 | 0.163243E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5593734.41 | 0.907739E+09 |
June | 0.171530E+10 | 0.159501E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 95061398.08 | 0.481556E+09 |
July | 0.172466E+10 | 0.160290E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.232022E+09 | 0.163508E+09 |
August | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.196468E+09 | 0.248648E+09 |
September | 0.169125E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19096292.99 | 0.645468E+09 |
October | 0.172174E+10 | 0.161274E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150963E+10 |
November | 0.165844E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.209518E+10 |
December | 0.172466E+10 | 0.160290E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.374021E+10 |
Annual Sum or Average | 0.205167E+11 | 0.191205E+11 | 0.958644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.554452E+09 | 0.216148E+11 |
Minimum of Months | 0.156756E+10 | 0.146111E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163508E+09 |
Maximum of Months | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.232022E+09 | 0.382212E+10 |
Report: SpaceGainsMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.161274E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.488299E+10 |
February | 0.156756E+10 | 0.146111E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.480509E+10 |
March | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6645261.32 | 0.329560E+10 |
April | 0.169125E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219516E+10 |
May | 0.174872E+10 | 0.163243E+10 | 0.818135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6010380.40 | 0.112987E+10 |
June | 0.171530E+10 | 0.159501E+10 | 0.798821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102680E+09 | 0.651145E+09 |
July | 0.172466E+10 | 0.160290E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.248653E+09 | 0.266188E+09 |
August | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.207369E+09 | 0.381050E+09 |
September | 0.169125E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20018763.91 | 0.835481E+09 |
October | 0.172174E+10 | 0.161274E+10 | 0.808994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190855E+10 |
November | 0.165844E+10 | 0.156548E+10 | 0.785109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.266816E+10 |
December | 0.172466E+10 | 0.160290E+10 | 0.804424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.484894E+10 |
Annual Sum or Average | 0.205167E+11 | 0.191205E+11 | 0.958644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.591376E+09 | 0.278682E+11 |
Minimum of Months | 0.156756E+10 | 0.146111E+10 | 0.732769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.266188E+09 |
Maximum of Months | 0.177569E+10 | 0.165211E+10 | 0.827277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.248653E+09 | 0.488299E+10 |
Report: PeakSpaceGainsMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 4050.04 | 01-JAN-13:09 | 4621.63 | 01-JAN-10:09 | 1343.25 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 11393.74 | 31-JAN-18:00 |
February | 4050.04 | 03-FEB-13:09 | 4621.63 | 01-FEB-10:09 | 1343.25 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 12700.39 | 06-FEB-17:00 |
March | 4050.04 | 03-MAR-13:09 | 4621.63 | 01-MAR-10:09 | 1343.25 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 659.70 | 15-MAR-14:00 | 10040.83 | 06-MAR-18:00 |
April | 4050.04 | 01-APR-12:09 | 4621.63 | 01-APR-09:09 | 1343.25 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 8058.18 | 16-APR-11:10 |
May | 4050.04 | 05-MAY-12:09 | 4621.63 | 01-MAY-09:09 | 1343.25 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 675.88 | 14-MAY-15:00 | 3955.51 | 11-MAY-15:00 |
June | 4050.04 | 02-JUN-12:09 | 4621.63 | 01-JUN-09:09 | 1343.25 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2026.26 | 27-JUN-13:00 | 3904.01 | 13-JUN-11:10 |
July | 4050.04 | 01-JUL-12:09 | 4621.63 | 01-JUL-09:09 | 1343.25 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2263.15 | 21-JUL-14:00 | 1647.28 | 02-JUL-11:10 |
August | 4050.04 | 04-AUG-12:09 | 4621.63 | 01-AUG-09:09 | 1343.25 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1958.04 | 10-AUG-14:00 | 2777.60 | 30-AUG-17:00 |
September | 4050.04 | 01-SEP-12:09 | 4621.63 | 01-SEP-09:09 | 1343.25 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1007.74 | 16-SEP-13:00 | 3457.00 | 28-SEP-16:40 |
October | 4050.04 | 01-OCT-12:09 | 4621.63 | 01-OCT-09:09 | 1343.25 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 5309.52 | 23-OCT-17:00 |
November | 4050.04 | 03-NOV-12:09 | 4621.63 | 01-NOV-09:09 | 1343.25 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 6512.23 | 22-NOV-18:00 |
December | 4050.04 | 01-DEC-13:09 | 4621.63 | 01-DEC-10:09 | 1343.25 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 11348.04 | 10-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 4050.04 | 4621.63 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1647.28 | |||||
Maximum of Months | 4050.04 | 4621.63 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 2263.15 | 12700.39 |
Report: PeakSpaceGainsMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 01-JAN-13:09 | 2827.07 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 6179.73 | 31-JAN-18:00 |
February | 2024.96 | 03-FEB-13:09 | 2827.07 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 6778.27 | 06-FEB-18:00 |
March | 2024.96 | 03-MAR-13:09 | 2827.07 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 356.15 | 15-MAR-14:00 | 5458.76 | 06-MAR-18:00 |
April | 2024.96 | 01-APR-12:09 | 2827.07 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 4348.64 | 16-APR-11:10 |
May | 2024.96 | 05-MAY-12:09 | 2827.07 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 358.91 | 14-MAY-15:00 | 2106.64 | 11-MAY-15:00 |
June | 2024.96 | 02-JUN-12:09 | 2827.07 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1081.11 | 27-JUN-13:00 | 2212.71 | 13-JUN-11:10 |
July | 2024.96 | 01-JUL-12:09 | 2827.07 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1230.37 | 21-JUL-14:00 | 894.57 | 02-JUL-11:10 |
August | 2024.96 | 04-AUG-12:09 | 2827.07 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1061.99 | 10-AUG-14:00 | 1528.02 | 31-AUG-11:10 |
September | 2024.96 | 01-SEP-12:09 | 2827.07 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 538.89 | 16-SEP-13:00 | 1985.48 | 28-SEP-16:30 |
October | 2024.96 | 01-OCT-12:09 | 2827.07 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2894.78 | 23-OCT-17:00 |
November | 2024.96 | 03-NOV-12:09 | 2827.07 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3585.02 | 22-NOV-18:00 |
December | 2024.96 | 01-DEC-13:09 | 2827.07 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 6247.17 | 10-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 2827.07 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 894.57 | |||||
Maximum of Months | 2024.96 | 2827.07 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1230.37 | 6778.27 |
Report: PeakSpaceGainsMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 2555.22 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 6179.73 | 31-JAN-18:00 |
February | 2024.96 | 04-FEB-13:09 | 2555.22 | 01-FEB-09:09 | 671.63 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 6778.27 | 06-FEB-18:00 |
March | 2024.96 | 04-MAR-13:09 | 2555.22 | 01-MAR-09:09 | 671.63 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 356.16 | 15-MAR-14:00 | 5458.76 | 06-MAR-18:00 |
April | 2024.96 | 01-APR-12:09 | 2555.22 | 01-APR-08:09 | 671.63 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 4348.64 | 16-APR-11:10 |
May | 2024.96 | 06-MAY-12:09 | 2555.22 | 01-MAY-08:09 | 671.63 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 359.03 | 14-MAY-15:00 | 2105.78 | 11-MAY-15:00 |
June | 2024.96 | 03-JUN-12:09 | 2555.22 | 01-JUN-08:09 | 671.63 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1081.11 | 27-JUN-13:00 | 2214.91 | 13-JUN-11:10 |
July | 2024.96 | 01-JUL-12:09 | 2555.22 | 01-JUL-08:09 | 671.63 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1230.37 | 21-JUL-14:00 | 894.56 | 02-JUL-11:10 |
August | 2024.96 | 05-AUG-12:09 | 2555.22 | 01-AUG-08:09 | 671.63 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1062.06 | 10-AUG-14:00 | 1526.15 | 31-AUG-11:10 |
September | 2024.96 | 02-SEP-12:09 | 2555.22 | 01-SEP-08:09 | 671.63 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 538.88 | 16-SEP-13:00 | 1969.94 | 28-SEP-16:30 |
October | 2024.96 | 07-OCT-12:09 | 2555.22 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2894.78 | 23-OCT-17:00 |
November | 2024.96 | 04-NOV-12:09 | 2555.22 | 01-NOV-08:09 | 671.63 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3585.02 | 22-NOV-18:00 |
December | 2024.96 | 02-DEC-13:09 | 2555.22 | 01-DEC-09:09 | 671.63 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 6247.17 | 10-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 2555.22 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 894.56 | |||||
Maximum of Months | 2024.96 | 2555.22 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1230.37 | 6778.27 |
Report: PeakSpaceGainsMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 2555.22 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 6179.73 | 31-JAN-18:00 |
February | 2024.96 | 04-FEB-13:09 | 2555.22 | 01-FEB-09:09 | 671.63 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 6778.27 | 06-FEB-18:00 |
March | 2024.96 | 04-MAR-13:09 | 2555.22 | 01-MAR-09:09 | 671.63 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 356.16 | 15-MAR-14:00 | 5458.76 | 06-MAR-18:00 |
April | 2024.96 | 01-APR-12:09 | 2555.22 | 01-APR-08:09 | 671.63 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 4348.64 | 16-APR-11:10 |
May | 2024.96 | 06-MAY-12:09 | 2555.22 | 01-MAY-08:09 | 671.63 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 359.03 | 14-MAY-15:00 | 2105.78 | 11-MAY-15:00 |
June | 2024.96 | 03-JUN-12:09 | 2555.22 | 01-JUN-08:09 | 671.63 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1081.11 | 27-JUN-13:00 | 2212.17 | 13-JUN-11:10 |
July | 2024.96 | 01-JUL-12:09 | 2555.22 | 01-JUL-08:09 | 671.63 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1230.37 | 21-JUL-14:00 | 894.56 | 02-JUL-11:10 |
August | 2024.96 | 05-AUG-12:09 | 2555.22 | 01-AUG-08:09 | 671.63 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1062.05 | 10-AUG-14:00 | 1524.24 | 31-AUG-11:10 |
September | 2024.96 | 02-SEP-12:09 | 2555.22 | 01-SEP-08:09 | 671.63 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 538.88 | 16-SEP-13:00 | 1960.72 | 28-SEP-16:30 |
October | 2024.96 | 07-OCT-12:09 | 2555.22 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2894.78 | 23-OCT-17:00 |
November | 2024.96 | 04-NOV-12:09 | 2555.22 | 01-NOV-08:09 | 671.63 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3585.02 | 22-NOV-18:00 |
December | 2024.96 | 02-DEC-13:09 | 2555.22 | 01-DEC-09:09 | 671.63 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 6247.17 | 10-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 2555.22 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 894.56 | |||||
Maximum of Months | 2024.96 | 2555.22 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1230.37 | 6778.27 |
Report: PeakSpaceGainsMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 2555.22 | 01-JAN-10:09 | 671.63 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 6179.73 | 31-JAN-18:00 |
February | 2024.96 | 04-FEB-13:09 | 2555.22 | 01-FEB-09:09 | 671.63 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 6778.27 | 06-FEB-18:00 |
March | 2024.96 | 04-MAR-13:09 | 2555.22 | 01-MAR-09:09 | 671.63 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 356.16 | 15-MAR-14:00 | 5458.76 | 06-MAR-18:00 |
April | 2024.96 | 01-APR-12:09 | 2555.22 | 01-APR-08:09 | 671.63 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 4348.64 | 16-APR-11:10 |
May | 2024.96 | 06-MAY-12:09 | 2555.22 | 01-MAY-08:09 | 671.63 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 359.03 | 14-MAY-15:00 | 2105.78 | 11-MAY-15:00 |
June | 2024.96 | 03-JUN-12:09 | 2555.22 | 01-JUN-08:09 | 671.63 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1081.11 | 27-JUN-13:00 | 2190.80 | 13-JUN-11:10 |
July | 2024.96 | 01-JUL-12:09 | 2555.22 | 01-JUL-08:09 | 671.63 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1230.37 | 21-JUL-14:00 | 894.50 | 02-JUL-11:10 |
August | 2024.96 | 05-AUG-12:09 | 2555.22 | 01-AUG-08:09 | 671.63 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1062.05 | 10-AUG-14:00 | 1506.32 | 31-AUG-11:10 |
September | 2024.96 | 02-SEP-12:09 | 2555.22 | 01-SEP-08:09 | 671.63 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 538.87 | 16-SEP-13:00 | 1937.01 | 28-SEP-16:30 |
October | 2024.96 | 07-OCT-12:09 | 2555.22 | 01-OCT-09:09 | 671.63 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2894.78 | 23-OCT-17:00 |
November | 2024.96 | 04-NOV-12:09 | 2555.22 | 01-NOV-08:09 | 671.63 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3585.02 | 22-NOV-18:00 |
December | 2024.96 | 02-DEC-13:09 | 2555.22 | 01-DEC-09:09 | 671.63 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 6247.17 | 10-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 2555.22 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 894.50 | |||||
Maximum of Months | 2024.96 | 2555.22 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1230.37 | 6778.27 |
Report: PeakSpaceGainsMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 5400.05 | 07-JAN-15:09 | 2726.96 | 01-JAN-11:09 | 1343.25 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 11118.18 | 31-JAN-18:00 |
February | 5400.05 | 04-FEB-15:09 | 2726.96 | 01-FEB-10:09 | 1343.25 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 12216.69 | 06-FEB-18:00 |
March | 5400.05 | 04-MAR-15:09 | 2726.96 | 01-MAR-10:09 | 1343.25 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 641.12 | 15-MAR-14:00 | 9818.19 | 06-MAR-18:00 |
April | 5400.05 | 01-APR-14:09 | 2726.96 | 01-APR-09:09 | 1343.25 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 7828.71 | 16-APR-11:10 |
May | 5400.05 | 06-MAY-14:09 | 2726.96 | 01-MAY-09:09 | 1343.25 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 647.63 | 14-MAY-15:00 | 3797.45 | 11-MAY-15:00 |
June | 5400.05 | 03-JUN-14:09 | 2726.96 | 01-JUN-09:09 | 1343.25 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1949.06 | 27-JUN-13:00 | 3855.41 | 13-JUN-11:10 |
July | 5400.05 | 01-JUL-14:09 | 2726.96 | 01-JUL-09:09 | 1343.25 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2212.97 | 21-JUL-14:00 | 1609.11 | 02-JUL-11:10 |
August | 5400.05 | 05-AUG-14:09 | 2726.96 | 01-AUG-09:09 | 1343.25 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1910.77 | 10-AUG-14:00 | 2690.05 | 30-AUG-17:00 |
September | 5400.05 | 02-SEP-14:09 | 2726.96 | 01-SEP-09:09 | 1343.25 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 971.21 | 16-SEP-13:00 | 3369.39 | 28-SEP-16:30 |
October | 5400.05 | 07-OCT-14:09 | 2726.96 | 01-OCT-10:09 | 1343.25 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 5204.75 | 23-OCT-17:00 |
November | 5400.05 | 04-NOV-14:09 | 2726.96 | 01-NOV-09:09 | 1343.25 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 6438.11 | 22-NOV-18:00 |
December | 5400.05 | 02-DEC-15:09 | 2726.96 | 01-DEC-10:09 | 1343.25 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 11218.88 | 10-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 5400.05 | 2726.96 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1609.11 | |||||
Maximum of Months | 5400.05 | 2726.96 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 2212.97 | 12216.69 |
Report: PeakSpaceGainsMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1404.46 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 6179.73 | 31-JAN-18:00 |
February | 2699.95 | 04-FEB-15:09 | 1404.46 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 6778.27 | 06-FEB-18:00 |
March | 2699.95 | 04-MAR-15:09 | 1404.46 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 356.14 | 15-MAR-14:00 | 5458.76 | 06-MAR-18:00 |
April | 2699.95 | 01-APR-14:09 | 1404.46 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 4348.64 | 16-APR-11:10 |
May | 2699.95 | 06-MAY-14:09 | 1404.46 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 359.03 | 14-MAY-15:00 | 2105.78 | 11-MAY-15:00 |
June | 2699.95 | 03-JUN-14:09 | 1404.46 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1081.11 | 27-JUN-13:00 | 2139.17 | 13-JUN-11:10 |
July | 2699.95 | 01-JUL-14:09 | 1404.46 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1230.37 | 21-JUL-14:00 | 894.51 | 02-JUL-11:10 |
August | 2699.95 | 05-AUG-14:09 | 1404.46 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1062.05 | 10-AUG-14:00 | 1492.59 | 30-AUG-17:00 |
September | 2699.95 | 02-SEP-14:09 | 1404.46 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 538.86 | 16-SEP-13:00 | 1873.30 | 28-SEP-16:20 |
October | 2699.95 | 07-OCT-14:09 | 1404.46 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2894.78 | 23-OCT-17:00 |
November | 2699.95 | 04-NOV-14:09 | 1404.46 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3585.02 | 22-NOV-18:00 |
December | 2699.95 | 02-DEC-15:09 | 1404.46 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 6247.17 | 10-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 894.51 | |||||
Maximum of Months | 2699.95 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1230.37 | 6778.27 |
Report: PeakSpaceGainsMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1404.46 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 6179.73 | 31-JAN-18:00 |
February | 2699.95 | 04-FEB-15:09 | 1404.46 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 6778.27 | 06-FEB-18:00 |
March | 2699.95 | 04-MAR-15:09 | 1404.46 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 356.14 | 15-MAR-14:00 | 5458.76 | 06-MAR-18:00 |
April | 2699.95 | 01-APR-14:09 | 1404.46 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 4348.64 | 16-APR-11:10 |
May | 2699.95 | 06-MAY-14:09 | 1404.46 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 359.03 | 14-MAY-15:00 | 2105.78 | 11-MAY-15:00 |
June | 2699.95 | 03-JUN-14:09 | 1404.46 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1081.11 | 27-JUN-13:00 | 2128.17 | 13-JUN-11:10 |
July | 2699.95 | 01-JUL-14:09 | 1404.46 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1230.37 | 21-JUL-14:00 | 894.51 | 02-JUL-11:10 |
August | 2699.95 | 05-AUG-14:09 | 1404.46 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1062.05 | 10-AUG-14:00 | 1490.74 | 30-AUG-17:00 |
September | 2699.95 | 02-SEP-14:09 | 1404.46 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 538.86 | 16-SEP-13:00 | 1862.54 | 28-SEP-16:20 |
October | 2699.95 | 07-OCT-14:09 | 1404.46 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2894.78 | 23-OCT-17:00 |
November | 2699.95 | 04-NOV-14:09 | 1404.46 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3585.02 | 22-NOV-18:00 |
December | 2699.95 | 02-DEC-15:09 | 1404.46 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 6247.17 | 10-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 894.51 | |||||
Maximum of Months | 2699.95 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1230.37 | 6778.27 |
Report: PeakSpaceGainsMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1404.46 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 6179.73 | 31-JAN-18:00 |
February | 2699.95 | 04-FEB-15:09 | 1404.46 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 6778.27 | 06-FEB-18:00 |
March | 2699.95 | 04-MAR-15:09 | 1404.46 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 356.14 | 15-MAR-14:00 | 5458.76 | 06-MAR-18:00 |
April | 2699.95 | 01-APR-14:09 | 1404.46 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 4348.64 | 16-APR-11:10 |
May | 2699.95 | 06-MAY-14:09 | 1404.46 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 359.03 | 14-MAY-15:00 | 2105.78 | 11-MAY-15:00 |
June | 2699.95 | 03-JUN-14:09 | 1404.46 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1081.11 | 27-JUN-13:00 | 2093.58 | 13-JUN-11:10 |
July | 2699.95 | 01-JUL-14:09 | 1404.46 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1230.37 | 21-JUL-14:00 | 894.51 | 02-JUL-11:10 |
August | 2699.95 | 05-AUG-14:09 | 1404.46 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1062.05 | 10-AUG-14:00 | 1483.61 | 30-AUG-17:00 |
September | 2699.95 | 02-SEP-14:09 | 1404.46 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 538.86 | 16-SEP-13:00 | 1829.76 | 28-SEP-16:20 |
October | 2699.95 | 07-OCT-14:09 | 1404.46 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2894.78 | 23-OCT-17:00 |
November | 2699.95 | 04-NOV-14:09 | 1404.46 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3585.02 | 22-NOV-18:00 |
December | 2699.95 | 02-DEC-15:09 | 1404.46 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 6247.17 | 10-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 894.51 | |||||
Maximum of Months | 2699.95 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1230.37 | 6778.27 |
Report: PeakSpaceGainsMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1404.46 | 01-JAN-11:09 | 671.63 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 6455.29 | 31-JAN-18:00 |
February | 2699.95 | 04-FEB-15:09 | 1404.46 | 01-FEB-10:09 | 671.63 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 7285.77 | 06-FEB-17:00 |
March | 2699.95 | 04-MAR-15:09 | 1404.46 | 01-MAR-10:09 | 671.63 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 374.79 | 15-MAR-14:00 | 5681.40 | 06-MAR-18:00 |
April | 2699.95 | 01-APR-14:09 | 1404.46 | 01-APR-09:09 | 671.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 4578.11 | 16-APR-11:10 |
May | 2699.95 | 06-MAY-14:09 | 1404.46 | 01-MAY-09:09 | 671.63 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 387.28 | 14-MAY-15:00 | 2263.84 | 11-MAY-15:00 |
June | 2699.95 | 03-JUN-14:09 | 1404.46 | 01-JUN-09:09 | 671.63 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1158.31 | 27-JUN-13:00 | 2088.05 | 13-JUN-11:10 |
July | 2699.95 | 01-JUL-14:09 | 1404.46 | 01-JUL-09:09 | 671.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1284.48 | 15-JUL-15:00 | 932.71 | 02-JUL-11:10 |
August | 2699.95 | 05-AUG-14:09 | 1404.46 | 01-AUG-09:09 | 671.63 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1109.38 | 10-AUG-14:00 | 1541.76 | 30-AUG-17:00 |
September | 2699.95 | 02-SEP-14:09 | 1404.46 | 01-SEP-09:09 | 671.63 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 575.37 | 16-SEP-13:00 | 1841.09 | 28-SEP-17:00 |
October | 2699.95 | 07-OCT-14:09 | 1404.46 | 01-OCT-10:09 | 671.63 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 3011.82 | 23-OCT-15:00 |
November | 2699.95 | 04-NOV-14:09 | 1404.46 | 01-NOV-09:09 | 671.63 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3659.14 | 22-NOV-18:00 |
December | 2699.95 | 02-DEC-15:09 | 1404.46 | 01-DEC-10:09 | 671.63 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 6376.32 | 10-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 932.71 | |||||
Maximum of Months | 2699.95 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1284.48 | 7285.77 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 13728.84 | 06-JAN-00:02 | 2025.02 | 1459.38 | 4477.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 301.43 |
February | 13740.50 | 11-FEB-00:02 | 2025.02 | 14594.58 | 4477.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 236.02 |
March | 13470.40 | 04-MAR-00:02 | 2025.02 | 14594.58 | 4477.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 404.10 |
April | 8190.62 | 13-APR-23:03 | 1350.01 | 972.92 | 2985.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 249.51 |
May | 6870.21 | 14-MAY-15:00 | 2700.03 | 4621.63 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 675.88 | 0.00 |
June | 20424.14 | 18-JUN-07:03 | 1350.01 | 300.00 | 298.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.42 |
July | 24590.61 | 15-JUL-07:03 | 0.00 | 300.00 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.31 |
August | 32834.41 | 06-AUG-07:02 | 1687.52 | 375.00 | 373.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 176.10 |
September | 25403.67 | 17-SEP-07:02 | 1687.52 | 375.00 | 373.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 137.81 |
October | 6641.81 | 23-OCT-17:10 | 3375.03 | 4621.63 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 931.17 |
November | 9895.18 | 24-NOV-00:02 | 1687.52 | 1216.15 | 3731.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 177.32 |
December | 13423.28 | 29-DEC-00:02 | 2025.02 | 1459.38 | 4477.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 621.68 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 6641.81 | 0.00 | 300.00 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 32834.41 | 3375.03 | 14594.58 | 4477.50 | 0.00 | 0.00 | 0.00 | 0.00 | 675.88 | 931.17 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6773.16 | 23-JAN-18:42 | 8437.34 | 14135.34 | 3358.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 914.98 |
February | 6161.15 | 13-FEB-18:42 | 8437.34 | 14135.34 | 3358.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 883.49 |
March | 12669.89 | 15-MAR-20:09 | 7087.36 | 19789.47 | 4701.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 |
April | 4157.09 | 09-APR-17:10 | 4049.92 | 5654.14 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 283.37 |
May | 16126.96 | 21-MAY-17:56 | 10124.81 | 14135.34 | 3358.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 168.50 |
June | 16084.74 | 03-JUN-18:08 | 10124.81 | 16962.41 | 4029.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 144.12 |
July | 15607.15 | 26-JUL-07:03 | 674.99 | 150.00 | 149.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.67 |
August | 18418.35 | 06-AUG-07:02 | 843.73 | 187.50 | 186.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.17 |
September | 15540.56 | 10-SEP-17:47 | 8099.84 | 11308.27 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 178.92 |
October | 12750.58 | 22-OCT-17:43 | 12149.77 | 16962.41 | 4029.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.30 |
November | 3624.63 | 18-NOV-17:43 | 5062.40 | 8481.20 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3016.24 |
December | 6801.07 | 26-DEC-18:42 | 8437.34 | 14135.34 | 3358.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 905.31 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3624.63 | 674.99 | 150.00 | 149.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 | |
Maximum of Months | 18418.35 | 12149.77 | 19789.47 | 4701.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3016.24 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4969.95 | 20-JAN-20:03 | 674.99 | 5379.41 | 1492.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 129.45 |
February | 5947.55 | 10-FEB-11:32 | 1687.47 | 12776.09 | 3358.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 722.24 |
March | 5838.40 | 05-MAR-11:22 | 3374.94 | 12776.09 | 3358.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 716.20 |
April | 3951.68 | 24-APR-07:01 | 1687.47 | 375.00 | 3731.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 459.71 |
May | 3859.12 | 27-MAY-13:00 | 2024.96 | 2555.22 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 360.05 |
June | 14145.25 | 26-JUN-06:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.43 |
July | 16100.03 | 26-JUL-06:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.08 |
August | 18505.33 | 06-AUG-07:02 | 0.00 | 187.50 | 186.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.70 |
September | 13905.46 | 17-SEP-07:02 | 0.00 | 187.50 | 186.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.49 |
October | 4227.99 | 24-OCT-07:01 | 1181.23 | 262.50 | 2611.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 471.66 |
November | 3615.50 | 02-NOV-07:01 | 1349.97 | 300.00 | 2985.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 443.99 |
December | 4309.36 | 21-DEC-10:43 | 1349.97 | 10220.87 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 495.82 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3615.50 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.08 | |
Maximum of Months | 18505.33 | 3374.94 | 12776.09 | 3731.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 722.24 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4476.15 | 07-JAN-11:02 | 2699.95 | 10220.87 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 795.78 |
February | 6407.80 | 08-FEB-18:42 | 8437.34 | 12776.09 | 3358.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 776.81 |
March | 5893.13 | 04-MAR-11:52 | 3374.94 | 12776.09 | 3358.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 736.02 |
April | 3878.27 | 24-APR-07:01 | 1687.47 | 375.00 | 3731.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 452.22 |
May | 3740.37 | 27-MAY-13:00 | 2024.96 | 2555.22 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 360.05 |
June | 14095.21 | 26-JUN-06:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.43 |
July | 16149.81 | 26-JUL-06:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.09 |
August | 18582.31 | 06-AUG-07:02 | 0.00 | 187.50 | 186.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.15 |
September | 13944.65 | 17-SEP-07:02 | 0.00 | 187.50 | 186.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.45 |
October | 4180.80 | 24-OCT-07:01 | 1181.23 | 262.50 | 2611.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 467.09 |
November | 3574.47 | 02-NOV-07:01 | 1349.97 | 300.00 | 2985.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 439.70 |
December | 6290.51 | 07-DEC-18:52 | 8437.34 | 12776.09 | 3358.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 799.25 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3574.47 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.09 | |
Maximum of Months | 18582.31 | 8437.34 | 12776.09 | 3731.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 799.25 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6296.04 | 12-JAN-18:32 | 8437.34 | 12776.09 | 3358.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 916.83 |
February | 6461.50 | 10-FEB-18:02 | 8437.34 | 12776.09 | 3358.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 758.17 |
March | 4949.07 | 24-MAR-19:42 | 674.99 | 5379.41 | 1492.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.88 |
April | 3561.83 | 13-APR-08:23 | 1012.48 | 7665.65 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 516.95 |
May | 3439.81 | 27-MAY-13:00 | 2024.96 | 2555.22 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 360.05 |
June | 12504.48 | 26-JUN-06:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.37 |
July | 14783.57 | 26-JUL-06:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 |
August | 18306.92 | 06-AUG-07:02 | 0.00 | 187.50 | 186.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.63 |
September | 13700.79 | 17-SEP-07:02 | 0.00 | 187.50 | 186.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.39 |
October | 3457.97 | 03-OCT-07:02 | 1012.48 | 225.00 | 2238.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 399.32 |
November | 4843.33 | 22-NOV-20:53 | 674.99 | 5379.41 | 1492.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.52 |
December | 4996.70 | 04-DEC-19:33 | 2699.95 | 10220.87 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 631.18 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3439.81 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 | |
Maximum of Months | 18306.92 | 8437.34 | 12776.09 | 3358.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 916.83 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 487.57 | 21-JAN-12:00 | 3915.04 | 2726.96 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1160.69 |
February | 3192.27 | 22-FEB-19:35 | 3510.03 | 5453.92 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 523.66 |
March | 8063.07 | 21-MAR-19:03 | 2970.03 | 5740.94 | 2985.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 148.61 |
April | 6674.45 | 11-APR-09:43 | 2227.52 | 8180.88 | 4029.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 852.15 |
May | 5662.89 | 27-MAY-14:20 | 5400.05 | 2726.96 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 649.90 |
June | 19989.24 | 27-JUN-07:03 | 0.00 | 300.00 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.73 |
July | 24820.79 | 26-JUL-07:03 | 0.00 | 300.00 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 132.30 |
August | 30483.70 | 06-AUG-08:62 | 0.00 | 300.00 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.64 |
September | 23999.54 | 17-SEP-08:62 | 0.00 | 300.00 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 123.88 |
October | 6513.77 | 29-OCT-10:33 | 2227.52 | 8180.88 | 4029.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 732.16 |
November | 9278.66 | 22-NOV-18:42 | 9180.09 | 10907.84 | 5373.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 979.44 |
December | 2285.71 | 16-DEC-12:00 | 3915.04 | 2726.96 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 662.76 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 487.57 | 0.00 | 300.00 | 294.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.73 | |
Maximum of Months | 30483.70 | 9180.09 | 10907.84 | 5373.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1160.69 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 164.68 | 21-JAN-12:00 | 1957.46 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 630.74 |
February | 1500.55 | 22-FEB-19:05 | 1754.97 | 2808.93 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 265.48 |
March | 3457.47 | 10-MAR-11:53 | 4353.67 | 4213.39 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 433.03 |
April | 2767.35 | 11-APR-12:15 | 4792.41 | 2808.93 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2399.25 |
May | 2801.53 | 27-MAY-14:30 | 2699.95 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 360.90 |
June | 9450.17 | 27-JUN-07:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.79 |
July | 12249.38 | 18-JUL-07:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.91 |
August | 15006.02 | 06-AUG-08:62 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.05 |
September | 12338.16 | 17-SEP-08:62 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.70 |
October | 3193.89 | 14-OCT-08:63 | 1113.73 | 112.50 | 1119.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 393.75 |
November | 4511.64 | 22-NOV-18:23 | 4589.91 | 5617.86 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 525.47 |
December | 1095.80 | 16-DEC-12:00 | 1957.46 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 369.64 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 164.68 | 0.00 | 112.50 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.79 | |
Maximum of Months | 15006.02 | 4792.41 | 5617.86 | 2686.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2399.25 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 114.89 | 21-JAN-12:00 | 1957.46 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 630.74 |
February | 277.90 | 18-FEB-12:00 | 1957.46 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 554.94 |
March | 4055.17 | 25-MAR-17:03 | 1113.73 | 2217.58 | 1119.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 601.99 |
April | 3762.70 | 14-APR-10:23 | 4353.67 | 4213.39 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 520.73 |
May | 2669.87 | 27-MAY-14:40 | 2699.95 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 360.49 |
June | 8862.88 | 27-JUN-07:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.62 |
July | 11846.93 | 19-JUL-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.88 |
August | 14481.04 | 06-AUG-08:62 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.92 |
September | 12241.48 | 17-SEP-08:62 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.88 |
October | 3170.77 | 14-OCT-08:63 | 1113.73 | 112.50 | 1119.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 390.73 |
November | 3949.75 | 21-NOV-18:53 | 3442.43 | 4213.39 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 494.46 |
December | 1057.39 | 16-DEC-12:00 | 1957.46 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 369.64 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 114.89 | 0.00 | 112.50 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.62 | |
Maximum of Months | 14481.04 | 4353.67 | 4213.39 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 630.74 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:05 | 0.00 | 75.00 | 73.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 288.44 |
February | 3468.93 | 17-FEB-11:43 | 4353.67 | 4213.39 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 514.12 |
March | 3970.83 | 02-MAR-18:03 | 3442.43 | 4213.39 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 536.24 |
April | 2254.58 | 01-APR-14:55 | 5399.90 | 2808.93 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1957.11 |
May | 2436.88 | 18-MAY-08:13 | 1113.73 | 2217.58 | 1119.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 284.66 |
June | 6415.82 | 27-JUN-07:03 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.07 |
July | 11610.97 | 19-JUL-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.78 |
August | 13123.51 | 07-AUG-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.53 |
September | 12031.38 | 17-SEP-08:62 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.23 |
October | 3777.22 | 24-OCT-09:13 | 1113.73 | 4213.39 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 447.48 |
November | 3089.89 | 08-NOV-20:03 | 1113.73 | 2217.58 | 1119.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.24 |
December | 857.81 | 16-DEC-12:00 | 1957.46 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 369.64 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 75.00 | 73.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.07 | |
Maximum of Months | 13123.51 | 5399.90 | 4213.39 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1957.11 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:05 | 0.00 | 75.00 | 73.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 659.95 |
February | 0.00 | 01-FEB-00:03 | 0.00 | 112.50 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 846.01 |
March | 2431.36 | 16-MAR-17:10 | 1147.48 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 362.26 |
April | 3155.43 | 13-APR-17:23 | 3442.43 | 4213.39 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 504.88 |
May | 2331.30 | 11-MAY-19:15 | 742.49 | 1478.38 | 746.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 201.92 |
June | 5974.10 | 27-JUN-13:00 | 2396.20 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1158.31 | 0.00 |
July | 11193.37 | 22-JUL-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.54 |
August | 13179.36 | 07-AUG-07:02 | 0.00 | 187.50 | 184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.81 |
September | 9625.87 | 17-SEP-08:62 | 0.00 | 150.00 | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.27 |
October | 3290.36 | 14-OCT-17:23 | 1113.73 | 2217.58 | 1119.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 467.51 |
November | 2222.31 | 01-NOV-16:25 | 4792.41 | 2808.93 | 1343.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1990.18 |
December | 157.12 | 16-DEC-12:00 | 1957.46 | 1404.46 | 671.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 369.64 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 75.00 | 73.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13179.36 | 4792.41 | 4213.39 | 2014.88 | 0.00 | 0.00 | 0.00 | 0.00 | 1158.31 | 1990.18 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.644385E+11 | 54296.17 | 07-JAN-17:19 | 0.169930E+12 | 221282.48 | 24-JAN-08:09 |
February | 0.577994E+11 | 52950.95 | 03-FEB-17:00 | 0.158666E+12 | 249234.25 | 06-FEB-12:09 |
March | 0.629341E+11 | 54473.01 | 15-MAR-13:50 | 0.980863E+11 | 200881.40 | 06-MAR-08:09 |
April | 0.580073E+11 | 50582.49 | 04-APR-18:00 | 0.423990E+11 | 148704.29 | 17-APR-07:10 |
May | 0.600028E+11 | 57968.44 | 10-MAY-14:20 | 0.358378E+10 | 59434.58 | 01-MAY-07:10 |
June | 0.680547E+11 | 78912.07 | 27-JUN-12:50 | 8456503.88 | 2898.80 | 14-JUN-07:10 |
July | 0.816322E+11 | 80911.64 | 15-JUL-14:20 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.786652E+11 | 77947.67 | 13-AUG-14:39 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.646965E+11 | 68092.93 | 16-SEP-13:09 | 0.101995E+09 | 14570.24 | 30-SEP-08:20 |
October | 0.608812E+11 | 52655.87 | 11-OCT-12:50 | 0.209416E+11 | 102873.53 | 30-OCT-07:10 |
November | 0.603020E+11 | 52277.70 | 17-NOV-18:30 | 0.618800E+11 | 136781.53 | 24-NOV-08:09 |
December | 0.642088E+11 | 53188.76 | 15-DEC-17:49 | 0.156571E+12 | 230549.04 | 11-DEC-08:09 |
Annual Sum or Average | 0.781623E+12 | 0.712167E+12 | ||||
Minimum of Months | 0.577994E+11 | 50582.49 | 0.00 | 0.00 | ||
Maximum of Months | 0.816322E+11 | 80911.64 | 0.169930E+12 | 249234.25 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.310073E+11 | 0.682956E+10 | 0.108325E+11 | 0.00 | 0.100560E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.571324E+10 | 0.00 |
February | 0.280657E+11 | 0.554424E+10 | 0.980803E+10 | 0.00 | 0.919189E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.518955E+10 | 0.00 |
March | 0.314703E+11 | 0.527657E+10 | 0.110075E+11 | 0.00 | 0.898577E+10 | 0.00 | 0.00 | 0.439501E+09 | 0.00 | 0.00 | 0.00 | 0.575449E+10 | 0.00 |
April | 0.300741E+11 | 0.423575E+10 | 0.105079E+11 | 0.00 | 0.772681E+10 | 0.00 | 0.00 | 3554506.31 | 0.00 | 0.00 | 0.00 | 0.545916E+10 | 0.00 |
May | 0.312330E+11 | 0.365953E+10 | 0.109147E+11 | 0.00 | 0.744294E+10 | 0.00 | 0.00 | 0.122618E+10 | 0.00 | 0.00 | 0.00 | 0.552647E+10 | 0.00 |
June | 0.304143E+11 | 0.323285E+10 | 0.106386E+11 | 0.00 | 0.722848E+10 | 0.00 | 0.00 | 0.112914E+11 | 0.00 | 0.00 | 0.00 | 0.524909E+10 | 0.00 |
July | 0.309042E+11 | 0.343030E+10 | 0.107945E+11 | 0.00 | 0.737753E+10 | 0.00 | 0.00 | 0.238217E+11 | 0.00 | 0.00 | 0.00 | 0.530401E+10 | 0.00 |
August | 0.314595E+11 | 0.403418E+10 | 0.110006E+11 | 0.00 | 0.747833E+10 | 0.00 | 0.00 | 0.193657E+11 | 0.00 | 0.00 | 0.00 | 0.532688E+10 | 0.00 |
September | 0.300847E+11 | 0.473138E+10 | 0.105148E+11 | 0.00 | 0.716380E+10 | 0.00 | 0.00 | 0.704528E+10 | 0.00 | 0.00 | 0.00 | 0.515661E+10 | 0.00 |
October | 0.310073E+11 | 0.578212E+10 | 0.108325E+11 | 0.00 | 0.762521E+10 | 0.00 | 0.00 | 0.203370E+09 | 0.00 | 0.00 | 0.00 | 0.543076E+10 | 0.00 |
November | 0.300409E+11 | 0.637028E+10 | 0.104978E+11 | 0.00 | 0.803312E+10 | 0.00 | 0.00 | 326308.54 | 0.00 | 0.00 | 0.00 | 0.535953E+10 | 0.00 |
December | 0.309156E+11 | 0.703773E+10 | 0.108050E+11 | 0.00 | 0.980614E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.564427E+10 | 0.00 |
Annual Sum or Average | 0.366677E+12 | 0.601645E+11 | 0.128154E+12 | 0.00 | 0.981160E+11 | 0.00 | 0.00 | 0.633969E+11 | 0.00 | 0.00 | 0.00 | 0.651141E+11 | 0.00 |
Minimum of Months | 0.280657E+11 | 0.323285E+10 | 0.980803E+10 | 0.00 | 0.716380E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.515661E+10 | 0.00 |
Maximum of Months | 0.314703E+11 | 0.703773E+10 | 0.110075E+11 | 0.00 | 0.100560E+11 | 0.00 | 0.00 | 0.238217E+11 | 0.00 | 0.00 | 0.00 | 0.575449E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.169930E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.158666E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.980863E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.423990E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.358378E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 8456503.88 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.101995E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.209416E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.618800E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.156571E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.712167E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.169930E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 23459.17 | 01-JAN-11:09 | 5507.06 | 01-JAN-06:10 | 8059.50 | 01-JAN-11:09 | 0.00 | 8673.21 | 24-JAN-08:09 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 23459.17 | 01-FEB-10:09 | 5507.06 | 01-FEB-06:10 | 8059.50 | 01-FEB-10:09 | 0.00 | 9145.54 | 06-FEB-12:09 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 23459.17 | 01-MAR-10:09 | 5507.06 | 01-MAR-06:10 | 8059.50 | 01-MAR-10:09 | 0.00 | 8334.32 | 06-MAR-08:09 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 23459.17 | 01-APR-09:09 | 5507.06 | 01-APR-05:10 | 8059.50 | 01-APR-09:09 | 0.00 | 7469.63 | 17-APR-07:10 | 0.00 | 0.00 | 01-APR-00:10 |
May | 23459.17 | 01-MAY-09:09 | 5507.06 | 01-MAY-05:10 | 8059.50 | 01-MAY-09:09 | 0.00 | 5988.71 | 01-MAY-07:10 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 23459.17 | 01-JUN-09:09 | 5507.06 | 01-JUN-19:49 | 8059.50 | 01-JUN-09:09 | 0.00 | 6355.96 | 27-JUN-12:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 23459.17 | 01-JUL-09:09 | 5507.06 | 01-JUL-19:00 | 8059.50 | 01-JUL-09:09 | 0.00 | 6821.68 | 21-JUL-07:10 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 23459.17 | 01-AUG-09:09 | 5507.06 | 01-AUG-19:40 | 8059.50 | 01-AUG-09:09 | 0.00 | 6531.14 | 14-AUG-07:10 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 23459.17 | 01-SEP-09:09 | 5507.06 | 01-SEP-05:10 | 8059.50 | 01-SEP-09:09 | 0.00 | 5824.76 | 17-SEP-08:09 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 23459.17 | 01-OCT-10:09 | 5507.06 | 01-OCT-05:10 | 8059.50 | 01-OCT-10:09 | 0.00 | 6710.35 | 30-OCT-07:10 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 23459.17 | 01-NOV-09:09 | 5507.06 | 01-NOV-05:10 | 8059.50 | 01-NOV-09:09 | 0.00 | 7273.00 | 24-NOV-08:09 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 23459.17 | 01-DEC-10:09 | 5507.06 | 01-DEC-06:10 | 8059.50 | 01-DEC-10:09 | 0.00 | 8830.19 | 11-DEC-08:09 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||||
Minimum of Months | 23459.17 | 5507.06 | 8059.50 | 0.00 | 5824.76 | 0.00 | 0.00 | |||||
Maximum of Months | 23459.17 | 5507.06 | 8059.50 | 0.00 | 9145.54 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 12298.30 | 07-JAN-15:50 | 0.00 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 11000.30 | 16-FEB-13:09 | 0.00 |
March | 12952.19 | 15-MAR-14:09 | 0.00 | 0.00 | 0.00 | 9707.48 | 22-MAR-14:09 | 0.00 |
April | 713.15 | 08-APR-12:00 | 0.00 | 0.00 | 0.00 | 9708.65 | 13-APR-11:09 | 0.00 |
May | 15981.76 | 14-MAY-14:00 | 0.00 | 0.00 | 0.00 | 11846.74 | 20-MAY-12:00 | 0.00 |
June | 36329.82 | 27-JUN-12:00 | 0.00 | 0.00 | 0.00 | 9643.02 | 30-JUN-10:20 | 0.00 |
July | 36777.71 | 15-JUL-13:00 | 0.00 | 0.00 | 0.00 | 9700.99 | 07-JUL-13:09 | 0.00 |
August | 35183.12 | 13-AUG-14:00 | 0.00 | 0.00 | 0.00 | 9655.44 | 30-AUG-18:49 | 0.00 |
September | 26625.26 | 16-SEP-13:00 | 0.00 | 0.00 | 0.00 | 9296.67 | 11-SEP-12:00 | 0.00 |
October | 7795.77 | 11-OCT-14:00 | 0.00 | 0.00 | 0.00 | 9709.43 | 16-OCT-13:20 | 0.00 |
November | 126.63 | 05-NOV-22:10 | 0.00 | 0.00 | 0.00 | 9724.64 | 20-NOV-13:50 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 11370.66 | 14-DEC-14:50 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 9296.67 | 0.00 | ||
Maximum of Months | 36777.71 | 0.00 | 0.00 | 0.00 | 12298.30 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 54296.17 | 07-JAN-17:19 | 23459.17 | 8059.50 | 5507.06 | 0.00 | 7271.14 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 52950.95 | 03-FEB-17:00 | 23459.17 | 8059.50 | 5507.06 | 0.00 | 7229.94 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 54473.01 | 15-MAR-13:50 | 23459.17 | 8059.50 | 0.00 | 0.00 | 4998.64 | 0.00 | 0.00 | 12624.27 | 0.00 |
April | 50582.49 | 04-APR-18:00 | 23459.17 | 8059.50 | 5507.06 | 0.00 | 5991.74 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 57968.44 | 10-MAY-14:20 | 23459.17 | 8059.50 | 0.00 | 0.00 | 4998.64 | 0.00 | 0.00 | 14205.16 | 0.00 |
June | 78912.07 | 27-JUN-12:50 | 23459.17 | 8059.50 | 0.00 | 0.00 | 6219.00 | 0.00 | 0.00 | 35715.29 | 0.00 |
July | 80911.64 | 15-JUL-14:20 | 23459.17 | 8059.50 | 0.00 | 0.00 | 6356.97 | 0.00 | 0.00 | 36429.40 | 0.00 |
August | 77947.67 | 13-AUG-14:39 | 23459.17 | 8059.50 | 0.00 | 0.00 | 6083.03 | 0.00 | 0.00 | 34922.10 | 0.00 |
September | 68092.93 | 16-SEP-13:09 | 23459.17 | 8059.50 | 0.00 | 0.00 | 4998.64 | 0.00 | 0.00 | 26121.36 | 0.00 |
October | 52655.87 | 11-OCT-12:50 | 23459.17 | 8059.50 | 0.00 | 0.00 | 4998.64 | 0.00 | 0.00 | 6676.38 | 0.00 |
November | 52277.70 | 17-NOV-18:30 | 23459.17 | 8059.50 | 5507.06 | 0.00 | 5570.05 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 53188.76 | 15-DEC-17:49 | 23459.17 | 8059.50 | 5507.06 | 0.00 | 6473.26 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 50582.49 | 23459.17 | 8059.50 | 0.00 | 0.00 | 4998.64 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 80911.64 | 23459.17 | 8059.50 | 5507.06 | 0.00 | 7271.14 | 0.00 | 0.00 | 36429.40 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 221282.48 | 24-JAN-08:09 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 249234.25 | 06-FEB-12:09 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 200881.40 | 06-MAR-08:09 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 148704.29 | 17-APR-07:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 59434.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 2898.80 | 14-JUN-07:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 14570.24 | 30-SEP-08:20 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 102873.53 | 30-OCT-07:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 136781.53 | 24-NOV-08:09 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 230549.04 | 11-DEC-08:09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 249234.25 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 4.67 | 20.38 | 2.00 | 20.37 | 0.00 | 20.37 | 0.00 | 20.37 |
February | 4.50 | 20.27 | 1.83 | 20.26 | 0.00 | 20.26 | 0.00 | 20.26 |
March | 1.83 | 20.47 | 0.67 | 20.46 | 0.00 | 20.46 | 0.00 | 20.46 |
April | 0.83 | 20.52 | 0.00 | 20.52 | 0.00 | 20.52 | 0.00 | 20.52 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.67 | 20.52 | 0.00 | 20.52 | 0.00 | 20.52 | 0.00 | 20.52 |
December | 2.67 | 20.34 | 1.17 | 20.34 | 0.00 | 20.34 | 0.00 | 20.34 |
Annual Sum or Average | 15.17 | 20.36 | 5.67 | 20.35 | 0.00 | 20.35 | 0.00 | 20.35 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4.67 | 20.52 | 2.00 | 20.52 | 0.00 | 20.52 | 0.00 | 20.52 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 20.50 | 0.00 | 20.50 | 0.00 | 20.50 | 0.00 | 20.50 |
February | 1.83 | 20.46 | 0.33 | 20.46 | 0.00 | 20.46 | 0.00 | 20.46 |
March | 0.33 | 20.48 | 0.00 | 20.48 | 0.00 | 20.48 | 0.00 | 20.48 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.50 | 20.52 | 0.00 | 20.52 | 0.00 | 20.52 | 0.00 | 20.52 |
Annual Sum or Average | 2.83 | 20.48 | 0.33 | 20.47 | 0.00 | 20.47 | 0.00 | 20.47 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.83 | 20.52 | 0.33 | 20.52 | 0.00 | 20.52 | 0.00 | 20.52 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 20.54 | 0.00 | 20.54 | 0.00 | 20.54 | 0.00 | 20.54 |
February | 0.67 | 20.35 | 0.00 | 20.35 | 0.00 | 20.35 | 0.00 | 20.35 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.33 | 20.48 | 0.00 | 20.48 | 0.00 | 20.48 | 0.00 | 20.48 |
Annual Sum or Average | 1.17 | 20.42 | 0.00 | 20.42 | 0.00 | 20.42 | 0.00 | 20.42 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.67 | 20.54 | 0.00 | 20.54 | 0.00 | 20.54 | 0.00 | 20.54 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.67 | 20.48 | 0.00 | 20.48 | 0.00 | 20.48 | 0.00 | 20.48 |
February | 1.00 | 20.30 | 0.00 | 20.30 | 0.00 | 20.30 | 0.00 | 20.30 |
March | 0.17 | 20.55 | 0.00 | 20.55 | 0.00 | 20.55 | 0.00 | 20.55 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.67 | 20.45 | 0.00 | 20.45 | 0.00 | 20.45 | 0.00 | 20.45 |
Annual Sum or Average | 2.50 | 20.41 | 0.00 | 20.41 | 0.00 | 20.41 | 0.00 | 20.41 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.00 | 20.55 | 0.00 | 20.55 | 0.00 | 20.55 | 0.00 | 20.55 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.00 | 20.43 | 0.00 | 20.43 | 0.00 | 20.43 | 0.00 | 20.43 |
February | 1.33 | 20.28 | 0.00 | 20.28 | 0.00 | 20.28 | 0.00 | 20.28 |
March | 0.17 | 20.45 | 0.00 | 20.45 | 0.00 | 20.45 | 0.00 | 20.45 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.83 | 20.39 | 0.00 | 20.39 | 0.00 | 20.39 | 0.00 | 20.39 |
Annual Sum or Average | 3.33 | 20.36 | 0.00 | 20.36 | 0.00 | 20.36 | 0.00 | 20.36 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.33 | 20.45 | 0.00 | 20.45 | 0.00 | 20.45 | 0.00 | 20.45 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.33 | 20.35 | 0.00 | 20.35 | 0.00 | 20.35 | 0.00 | 20.35 |
February | 2.83 | 20.26 | 0.00 | 20.26 | 0.00 | 20.26 | 0.00 | 20.26 |
March | 0.67 | 20.40 | 0.00 | 20.40 | 0.00 | 20.40 | 0.00 | 20.40 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1.50 | 20.23 | 0.00 | 20.23 | 0.00 | 20.23 | 0.00 | 20.23 |
Annual Sum or Average | 8.33 | 20.30 | 0.00 | 20.30 | 0.00 | 20.30 | 0.00 | 20.30 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3.33 | 20.40 | 0.00 | 20.40 | 0.00 | 20.40 | 0.00 | 20.40 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.17 | 20.36 | 0.00 | 20.36 | 0.00 | 20.36 | 0.00 | 20.36 |
February | 2.83 | 20.29 | 0.00 | 20.29 | 0.00 | 20.29 | 0.00 | 20.29 |
March | 0.67 | 20.40 | 0.00 | 20.40 | 0.00 | 20.40 | 0.00 | 20.40 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1.50 | 20.25 | 0.00 | 20.25 | 0.00 | 20.25 | 0.00 | 20.25 |
Annual Sum or Average | 8.17 | 20.32 | 0.00 | 20.32 | 0.00 | 20.32 | 0.00 | 20.32 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3.17 | 20.40 | 0.00 | 20.40 | 0.00 | 20.40 | 0.00 | 20.40 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.33 | 20.35 | 0.00 | 20.35 | 0.00 | 20.35 | 0.00 | 20.35 |
February | 3.00 | 20.27 | 0.00 | 20.27 | 0.00 | 20.27 | 0.00 | 20.27 |
March | 0.67 | 20.37 | 0.00 | 20.37 | 0.00 | 20.37 | 0.00 | 20.37 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1.50 | 20.23 | 0.00 | 20.23 | 0.00 | 20.23 | 0.00 | 20.23 |
Annual Sum or Average | 8.50 | 20.30 | 0.00 | 20.30 | 0.00 | 20.30 | 0.00 | 20.30 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3.33 | 20.37 | 0.00 | 20.37 | 0.00 | 20.37 | 0.00 | 20.37 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.83 | 20.25 | 0.00 | 20.25 | 0.00 | 20.25 | 0.00 | 20.25 |
February | 3.67 | 19.99 | 0.00 | 19.99 | 0.00 | 19.99 | 0.00 | 19.99 |
March | 1.67 | 20.36 | 0.00 | 20.36 | 0.00 | 20.36 | 0.00 | 20.36 |
April | 0.33 | 20.47 | 0.00 | 20.47 | 0.00 | 20.47 | 0.00 | 20.47 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 3.00 | 20.30 | 0.00 | 20.30 | 0.00 | 20.30 | 0.00 | 20.30 |
Annual Sum or Average | 12.50 | 20.21 | 0.00 | 20.21 | 0.00 | 20.21 | 0.00 | 20.21 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3.83 | 20.47 | 0.00 | 20.47 | 0.00 | 20.47 | 0.00 | 20.47 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 9.67 | 17.66 | 0.00 | 17.66 | 0.00 | 17.66 | 0.00 | 17.66 |
February | 16.50 | 16.28 | 0.00 | 16.28 | 0.00 | 16.28 | 0.00 | 16.28 |
March | 6.50 | 18.15 | 0.00 | 18.15 | 0.00 | 18.15 | 0.00 | 18.15 |
April | 2.33 | 19.97 | 0.00 | 19.97 | 0.00 | 19.97 | 0.00 | 19.97 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.17 | 20.45 | 0.00 | 20.45 | 0.00 | 20.45 | 0.00 | 20.45 |
November | 1.33 | 20.44 | 0.00 | 20.44 | 0.00 | 20.44 | 0.00 | 20.44 |
December | 9.33 | 17.69 | 0.00 | 17.69 | 0.00 | 17.69 | 0.00 | 17.69 |
Annual Sum or Average | 45.83 | 17.45 | 0.00 | 17.45 | 0.00 | 17.45 | 0.00 | 17.45 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 16.50 | 20.45 | 0.00 | 20.45 | 0.00 | 20.45 | 0.00 | 20.45 |
Report: ComfortReportSimple55Monthly
For: LGSTORE1
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 496.00 | 21.05 | 461.00 | 21.05 | 461.00 | 21.05 |
February | 448.00 | 21.04 | 425.17 | 21.04 | 425.17 | 21.04 |
March | 479.33 | 21.17 | 246.00 | 21.12 | 246.00 | 21.09 |
April | 479.00 | 21.40 | 64.67 | 21.35 | 64.67 | 21.31 |
May | 364.17 | 22.33 | 23.17 | 22.39 | 3.50 | 22.38 |
June | 142.83 | 23.46 | 269.17 | 23.74 | 66.00 | 23.76 |
July | 118.83 | 23.88 | 464.50 | 23.89 | 117.17 | 23.89 |
August | 84.17 | 23.82 | 420.17 | 23.88 | 73.17 | 23.88 |
September | 129.33 | 23.16 | 244.50 | 23.63 | 38.33 | 23.66 |
October | 434.00 | 21.67 | 24.00 | 21.70 | 14.17 | 21.68 |
November | 480.00 | 21.23 | 80.33 | 21.19 | 80.33 | 21.16 |
December | 496.00 | 21.05 | 396.00 | 21.04 | 396.00 | 21.04 |
Annual Sum or Average | 4151.67 | 21.59 | 3118.67 | 21.91 | 1985.50 | 21.81 |
Minimum of Months | 84.17 | 21.04 | 23.17 | 21.04 | 3.50 | 21.04 |
Maximum of Months | 496.00 | 23.88 | 464.50 | 23.89 | 461.00 | 23.89 |
Report: ComfortReportSimple55Monthly
For: SMSTORE1
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 496.00 | 21.25 | 324.17 | 21.20 | 324.17 | 21.18 |
February | 448.00 | 21.23 | 295.33 | 21.19 | 295.33 | 21.17 |
March | 468.00 | 21.54 | 88.67 | 21.48 | 87.50 | 21.43 |
April | 459.50 | 22.01 | 10.33 | 21.99 | 10.33 | 21.97 |
May | 275.67 | 22.97 | 48.83 | 23.11 | 0.00 | 23.11 |
June | 87.83 | 23.61 | 267.67 | 23.81 | 39.33 | 23.82 |
July | 65.83 | 23.88 | 447.17 | 23.86 | 65.17 | 23.86 |
August | 38.50 | 23.85 | 401.17 | 23.87 | 35.83 | 23.87 |
September | 76.83 | 23.46 | 261.33 | 23.78 | 23.67 | 23.79 |
October | 378.83 | 22.24 | 18.00 | 22.31 | 0.33 | 22.31 |
November | 471.50 | 21.74 | 8.83 | 21.72 | 8.83 | 21.71 |
December | 496.00 | 21.31 | 237.00 | 21.25 | 237.00 | 21.21 |
Annual Sum or Average | 3762.50 | 21.84 | 2408.50 | 22.21 | 1127.50 | 22.10 |
Minimum of Months | 38.50 | 21.23 | 8.83 | 21.19 | 0.00 | 21.17 |
Maximum of Months | 496.00 | 23.88 | 447.17 | 23.87 | 324.17 | 23.87 |
Report: ComfortReportSimple55Monthly
For: SMSTORE2
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 371.00 | 21.11 | 307.33 | 21.11 | 307.33 | 21.11 |
February | 336.00 | 21.11 | 269.17 | 21.11 | 269.17 | 21.11 |
March | 359.67 | 21.22 | 115.83 | 21.20 | 115.67 | 21.18 |
April | 356.33 | 21.52 | 19.17 | 21.50 | 19.17 | 21.48 |
May | 231.33 | 22.49 | 34.67 | 22.68 | 0.00 | 22.68 |
June | 84.83 | 23.58 | 225.33 | 23.90 | 42.83 | 23.92 |
July | 83.17 | 24.08 | 348.50 | 24.05 | 82.67 | 24.05 |
August | 45.83 | 24.11 | 336.67 | 24.03 | 41.50 | 24.04 |
September | 83.00 | 23.28 | 200.83 | 23.77 | 27.50 | 23.80 |
October | 312.67 | 21.76 | 12.50 | 21.81 | 3.50 | 21.80 |
November | 360.00 | 21.28 | 25.17 | 21.27 | 25.17 | 21.26 |
December | 369.00 | 21.11 | 234.67 | 21.11 | 234.67 | 21.11 |
Annual Sum or Average | 2992.83 | 21.63 | 2129.83 | 22.07 | 1169.17 | 21.98 |
Minimum of Months | 45.83 | 21.11 | 12.50 | 21.11 | 0.00 | 21.11 |
Maximum of Months | 371.00 | 24.11 | 348.50 | 24.05 | 307.33 | 24.05 |
Report: ComfortReportSimple55Monthly
For: SMSTORE3
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 371.00 | 21.11 | 318.50 | 21.11 | 318.50 | 21.11 |
February | 336.00 | 21.11 | 282.67 | 21.11 | 282.67 | 21.11 |
March | 360.67 | 21.22 | 131.17 | 21.19 | 131.17 | 21.17 |
April | 357.17 | 21.48 | 24.50 | 21.46 | 24.50 | 21.44 |
May | 241.50 | 22.42 | 27.67 | 22.56 | 0.67 | 22.56 |
June | 87.00 | 23.56 | 223.17 | 23.89 | 43.33 | 23.91 |
July | 83.17 | 24.08 | 348.33 | 24.05 | 82.67 | 24.05 |
August | 46.00 | 24.10 | 336.67 | 24.03 | 41.50 | 24.04 |
September | 87.00 | 23.26 | 197.50 | 23.75 | 28.33 | 23.78 |
October | 322.17 | 21.74 | 12.67 | 21.78 | 4.67 | 21.77 |
November | 360.00 | 21.26 | 31.50 | 21.25 | 31.50 | 21.24 |
December | 369.00 | 21.11 | 249.33 | 21.11 | 249.33 | 21.11 |
Annual Sum or Average | 3020.67 | 21.62 | 2183.67 | 22.04 | 1238.83 | 21.95 |
Minimum of Months | 46.00 | 21.11 | 12.67 | 21.11 | 0.67 | 21.11 |
Maximum of Months | 371.00 | 24.10 | 348.33 | 24.05 | 318.50 | 24.05 |
Report: ComfortReportSimple55Monthly
For: SMSTORE4
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 371.00 | 21.11 | 330.50 | 21.11 | 330.50 | 21.11 |
February | 336.00 | 21.11 | 298.17 | 21.11 | 298.17 | 21.11 |
March | 364.00 | 21.22 | 149.50 | 21.19 | 149.50 | 21.17 |
April | 359.17 | 21.43 | 31.33 | 21.40 | 31.33 | 21.38 |
May | 262.50 | 22.33 | 20.50 | 22.42 | 1.67 | 22.42 |
June | 99.17 | 23.54 | 214.67 | 23.87 | 46.17 | 23.88 |
July | 85.67 | 24.08 | 348.17 | 24.04 | 84.83 | 24.05 |
August | 49.17 | 24.05 | 330.67 | 24.02 | 43.17 | 24.03 |
September | 94.33 | 23.19 | 188.00 | 23.71 | 30.00 | 23.74 |
October | 333.33 | 21.70 | 13.83 | 21.73 | 7.17 | 21.72 |
November | 360.00 | 21.23 | 41.50 | 21.22 | 41.50 | 21.21 |
December | 369.00 | 21.11 | 270.33 | 21.11 | 270.33 | 21.11 |
Annual Sum or Average | 3083.33 | 21.61 | 2237.17 | 22.00 | 1334.33 | 21.92 |
Minimum of Months | 49.17 | 21.11 | 13.83 | 21.11 | 1.67 | 21.11 |
Maximum of Months | 371.00 | 24.08 | 348.17 | 24.04 | 330.50 | 24.05 |
Report: ComfortReportSimple55Monthly
For: LGSTORE2
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.11 | 323.83 | 21.11 | 323.83 | 21.11 |
February | 308.00 | 21.11 | 303.33 | 21.11 | 303.33 | 21.11 |
March | 343.50 | 21.27 | 183.17 | 21.22 | 183.17 | 21.19 |
April | 330.00 | 21.35 | 47.67 | 21.32 | 47.67 | 21.29 |
May | 299.50 | 22.35 | 8.67 | 22.36 | 5.83 | 22.36 |
June | 110.83 | 23.50 | 175.33 | 23.77 | 55.50 | 23.79 |
July | 81.33 | 23.98 | 316.83 | 23.95 | 81.00 | 23.96 |
August | 63.83 | 23.87 | 284.67 | 23.92 | 56.50 | 23.93 |
September | 96.33 | 23.10 | 155.17 | 23.60 | 33.50 | 23.63 |
October | 320.17 | 21.64 | 11.50 | 21.66 | 7.83 | 21.64 |
November | 330.00 | 21.20 | 93.17 | 21.18 | 93.17 | 21.17 |
December | 338.00 | 21.11 | 305.67 | 21.11 | 305.67 | 21.11 |
Annual Sum or Average | 2961.50 | 21.64 | 2209.00 | 21.93 | 1497.00 | 21.84 |
Minimum of Months | 63.83 | 21.11 | 8.67 | 21.11 | 5.83 | 21.11 |
Maximum of Months | 343.50 | 23.98 | 323.83 | 23.95 | 323.83 | 23.96 |
Report: ComfortReportSimple55Monthly
For: SMSTORE5
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.11 | 323.50 | 21.11 | 323.50 | 21.11 |
February | 308.00 | 21.11 | 303.17 | 21.11 | 303.17 | 21.11 |
March | 344.17 | 21.27 | 187.17 | 21.22 | 187.17 | 21.19 |
April | 330.00 | 21.33 | 53.00 | 21.30 | 53.00 | 21.28 |
May | 310.00 | 22.35 | 7.50 | 22.34 | 7.00 | 22.32 |
June | 116.67 | 23.50 | 164.83 | 23.76 | 55.50 | 23.79 |
July | 82.17 | 23.97 | 311.50 | 23.95 | 81.67 | 23.96 |
August | 66.00 | 23.87 | 264.67 | 23.92 | 57.67 | 23.93 |
September | 100.00 | 23.11 | 141.67 | 23.58 | 33.83 | 23.62 |
October | 324.67 | 21.65 | 12.00 | 21.66 | 9.33 | 21.64 |
November | 330.00 | 21.20 | 97.33 | 21.18 | 97.33 | 21.17 |
December | 338.00 | 21.11 | 305.50 | 21.11 | 305.50 | 21.11 |
Annual Sum or Average | 2989.67 | 21.65 | 2171.83 | 21.91 | 1514.67 | 21.83 |
Minimum of Months | 66.00 | 21.11 | 7.50 | 21.11 | 7.00 | 21.11 |
Maximum of Months | 344.17 | 23.97 | 323.50 | 23.95 | 323.50 | 23.96 |
Report: ComfortReportSimple55Monthly
For: SMSTORE6
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.11 | 324.33 | 21.11 | 324.33 | 21.11 |
February | 308.00 | 21.11 | 303.50 | 21.11 | 303.50 | 21.11 |
March | 345.17 | 21.28 | 191.50 | 21.22 | 191.50 | 21.19 |
April | 330.00 | 21.31 | 57.17 | 21.28 | 57.17 | 21.26 |
May | 315.50 | 22.30 | 8.00 | 22.28 | 8.00 | 22.27 |
June | 121.00 | 23.47 | 162.50 | 23.74 | 56.50 | 23.77 |
July | 83.17 | 23.97 | 309.67 | 23.95 | 82.67 | 23.96 |
August | 67.17 | 23.86 | 261.00 | 23.92 | 58.50 | 23.93 |
September | 103.67 | 23.09 | 138.33 | 23.56 | 34.00 | 23.60 |
October | 329.67 | 21.66 | 12.00 | 21.65 | 10.17 | 21.64 |
November | 330.00 | 21.19 | 103.50 | 21.17 | 103.50 | 21.16 |
December | 338.00 | 21.11 | 307.50 | 21.11 | 307.50 | 21.11 |
Annual Sum or Average | 3011.33 | 21.65 | 2179.00 | 21.90 | 1537.33 | 21.82 |
Minimum of Months | 67.17 | 21.11 | 8.00 | 21.11 | 8.00 | 21.11 |
Maximum of Months | 345.17 | 23.97 | 324.33 | 23.95 | 324.33 | 23.96 |
Report: ComfortReportSimple55Monthly
For: SMSTORE7
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.11 | 327.83 | 21.11 | 327.83 | 21.11 |
February | 308.00 | 21.11 | 304.50 | 21.11 | 304.50 | 21.11 |
March | 348.00 | 21.29 | 209.67 | 21.22 | 209.67 | 21.19 |
April | 330.00 | 21.27 | 71.00 | 21.24 | 71.00 | 21.22 |
May | 330.67 | 22.20 | 10.00 | 22.18 | 10.00 | 22.16 |
June | 134.33 | 23.40 | 152.67 | 23.68 | 58.50 | 23.72 |
July | 86.83 | 23.96 | 307.00 | 23.95 | 85.33 | 23.95 |
August | 73.83 | 23.83 | 257.33 | 23.91 | 61.83 | 23.92 |
September | 112.33 | 23.02 | 131.33 | 23.50 | 34.67 | 23.54 |
October | 331.67 | 21.60 | 14.17 | 21.59 | 13.17 | 21.57 |
November | 330.00 | 21.18 | 125.00 | 21.16 | 125.00 | 21.15 |
December | 338.00 | 21.11 | 315.17 | 21.11 | 315.17 | 21.11 |
Annual Sum or Average | 3063.67 | 21.64 | 2225.67 | 21.87 | 1616.67 | 21.79 |
Minimum of Months | 73.83 | 21.11 | 10.00 | 21.11 | 10.00 | 21.11 |
Maximum of Months | 348.00 | 23.96 | 327.83 | 23.95 | 327.83 | 23.95 |
Report: ComfortReportSimple55Monthly
For: SMSTORE8
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.11 | 335.50 | 21.11 | 335.50 | 21.11 |
February | 308.00 | 21.11 | 308.00 | 21.11 | 308.00 | 21.11 |
March | 348.00 | 21.27 | 273.17 | 21.20 | 273.17 | 21.17 |
April | 330.00 | 21.22 | 137.50 | 21.18 | 137.50 | 21.17 |
May | 340.83 | 22.02 | 23.50 | 21.97 | 23.50 | 21.92 |
June | 166.50 | 23.27 | 145.33 | 23.56 | 60.83 | 23.61 |
July | 91.83 | 23.95 | 304.83 | 23.95 | 89.17 | 23.95 |
August | 84.67 | 23.73 | 259.00 | 23.88 | 64.33 | 23.89 |
September | 138.17 | 22.90 | 116.67 | 23.36 | 35.17 | 23.43 |
October | 333.83 | 21.53 | 36.83 | 21.49 | 36.83 | 21.45 |
November | 330.00 | 21.16 | 199.17 | 21.14 | 199.17 | 21.13 |
December | 338.00 | 21.11 | 330.33 | 21.11 | 330.33 | 21.11 |
Annual Sum or Average | 3149.83 | 21.63 | 2469.83 | 21.82 | 1893.50 | 21.73 |
Minimum of Months | 84.67 | 21.11 | 23.50 | 21.11 | 23.50 | 21.11 |
Maximum of Months | 348.00 | 23.95 | 335.50 | 23.95 | 335.50 | 23.95 |
Report: OccupantComfortDataSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 496.00000 | 21.05432 | 16.67417 | -0.6720 | 14.77273 |
February | 448.00000 | 21.04435 | 16.62030 | -0.6775 | 14.92952 |
March | 497.00000 | 21.26269 | 25.84079 | -0.4841 | 11.30369 |
April | 479.00000 | 21.39811 | 31.73524 | -0.3622 | 8.54662 |
May | 496.00000 | 22.72790 | 36.89131 | -0.9856 | 27.92393 |
June | 481.00000 | 23.75812 | 46.89739 | -0.4842 | 10.79025 |
July | 495.00000 | 23.88706 | 56.14253 | -0.3260 | 7.36948 |
August | 497.00000 | 23.87405 | 50.90784 | -0.3722 | 8.10938 |
September | 479.00000 | 23.67911 | 47.03273 | -0.5122 | 11.55300 |
October | 496.00000 | 21.94680 | 36.89572 | -0.1462 | 7.26833 |
November | 480.00000 | 21.22848 | 29.50483 | -0.4249 | 9.34795 |
December | 496.00000 | 21.04929 | 20.18922 | -0.6322 | 13.68881 |
Annual Sum or Average | 5840.00000 | 22.24936 | 34.71112 | -0.5059 | 12.13386 |
Minimum of Months | 448.00000 | 21.04435 | 16.62030 | -0.9856 | 7.26833 |
Maximum of Months | 497.00000 | 23.88706 | 56.14253 | -0.1462 | 27.92393 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 496.00000 | 21.25410 | 19.04702 | -0.5497 | 11.63672 |
February | 448.00000 | 21.23023 | 18.73525 | -0.5583 | 11.77666 |
March | 497.00000 | 21.67258 | 27.34128 | -0.3372 | 8.88997 |
April | 479.00000 | 22.08539 | 32.87396 | -0.1773 | 6.84642 |
May | 496.00000 | 23.37109 | 36.08972 | -0.7640 | 18.82087 |
June | 481.00000 | 23.81235 | 45.57765 | -0.4584 | 9.86034 |
July | 495.00000 | 23.84801 | 53.70848 | -0.3472 | 7.69251 |
August | 497.00000 | 23.85063 | 49.34345 | -0.3840 | 8.26309 |
September | 479.00000 | 23.80081 | 45.97081 | -0.4676 | 10.03034 |
October | 496.00000 | 22.62188 | 37.29095 | 0.01491 | 6.69983 |
November | 480.00000 | 21.77308 | 31.04569 | -0.2707 | 7.47879 |
December | 496.00000 | 21.30569 | 22.33518 | -0.5063 | 10.74617 |
Annual Sum or Average | 5840.00000 | 22.55949 | 35.03514 | -0.3998 | 9.89479 |
Minimum of Months | 448.00000 | 21.23023 | 18.73525 | -0.7640 | 6.69983 |
Maximum of Months | 497.00000 | 23.85063 | 53.70848 | 0.01491 | 18.82087 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 21.10974 | 15.92592 | -0.6130 | 13.03879 |
February | 336.00000 | 21.10987 | 15.89143 | -0.6126 | 13.01918 |
March | 379.00000 | 21.35816 | 24.91310 | -0.4171 | 9.98265 |
April | 360.00000 | 21.54581 | 30.68612 | -0.2987 | 7.69541 |
May | 375.00000 | 23.02978 | 35.46970 | -0.8661 | 23.05513 |
June | 366.00000 | 23.88586 | 45.83236 | -0.4368 | 9.76369 |
July | 369.00000 | 24.02861 | 55.01596 | -0.2868 | 7.04872 |
August | 379.00000 | 23.99481 | 49.75086 | -0.3385 | 7.72353 |
September | 360.00000 | 23.78111 | 46.01918 | -0.4724 | 10.53121 |
October | 371.00000 | 22.08524 | 35.91306 | -0.1005 | 7.01322 |
November | 360.00000 | 21.28093 | 29.22016 | -0.3840 | 8.61100 |
December | 369.00000 | 21.10985 | 19.68674 | -0.5761 | 12.13615 |
Annual Sum or Average | 4395.00000 | 22.37095 | 33.82108 | -0.4496 | 10.80417 |
Minimum of Months | 336.00000 | 21.10974 | 15.89143 | -0.8661 | 7.01322 |
Maximum of Months | 379.00000 | 24.02861 | 55.01596 | -0.1005 | 23.05513 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 21.10984 | 15.92568 | -0.6242 | 13.32875 |
February | 336.00000 | 21.10992 | 15.89113 | -0.6229 | 13.29032 |
March | 379.00000 | 21.34570 | 24.95062 | -0.4293 | 10.16612 |
April | 360.00000 | 21.49929 | 30.76722 | -0.3178 | 7.87279 |
May | 375.00000 | 22.94272 | 35.64696 | -0.9032 | 24.55545 |
June | 366.00000 | 23.87974 | 45.87412 | -0.4410 | 9.86700 |
July | 369.00000 | 24.02823 | 55.02268 | -0.2868 | 7.04781 |
August | 379.00000 | 23.99377 | 49.76093 | -0.3389 | 7.73089 |
September | 360.00000 | 23.76725 | 46.08858 | -0.4796 | 10.73736 |
October | 371.00000 | 22.01689 | 36.08317 | -0.1236 | 7.04952 |
November | 360.00000 | 21.25800 | 29.27213 | -0.3992 | 8.81239 |
December | 369.00000 | 21.10991 | 19.68654 | -0.5869 | 12.40342 |
Annual Sum or Average | 4395.00000 | 22.34924 | 33.87524 | -0.4622 | 11.07579 |
Minimum of Months | 336.00000 | 21.10984 | 15.89113 | -0.9032 | 7.04781 |
Maximum of Months | 379.00000 | 24.02823 | 55.02268 | -0.1236 | 24.55545 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 21.10987 | 15.92603 | -0.6389 | 13.72322 |
February | 336.00000 | 21.10985 | 15.89158 | -0.6374 | 13.67957 |
March | 379.00000 | 21.32617 | 25.01175 | -0.4469 | 10.44063 |
April | 360.00000 | 21.43399 | 30.88149 | -0.3433 | 8.13016 |
May | 375.00000 | 22.79460 | 35.96819 | -0.9624 | 26.94290 |
June | 366.00000 | 23.85623 | 46.06220 | -0.4557 | 10.22064 |
July | 369.00000 | 24.02276 | 55.23272 | -0.2935 | 7.12204 |
August | 379.00000 | 23.98536 | 49.91722 | -0.3470 | 7.85055 |
September | 360.00000 | 23.73118 | 46.28713 | -0.4975 | 11.23492 |
October | 371.00000 | 21.92037 | 36.33030 | -0.1538 | 7.10305 |
November | 360.00000 | 21.23181 | 29.33430 | -0.4174 | 9.07097 |
December | 369.00000 | 21.10960 | 19.68741 | -0.6015 | 12.77357 |
Annual Sum or Average | 4395.00000 | 22.31315 | 34.00641 | -0.4824 | 11.53084 |
Minimum of Months | 336.00000 | 21.10960 | 15.89158 | -0.9624 | 7.10305 |
Maximum of Months | 379.00000 | 24.02276 | 55.23272 | -0.1538 | 26.94290 |
Report: OccupantComfortDataSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.11000 | 17.37431 | -0.6813 | 14.89394 |
February | 308.00000 | 21.10993 | 17.30006 | -0.6796 | 14.83532 |
March | 348.00000 | 21.30597 | 26.60692 | -0.4870 | 11.17388 |
April | 330.00000 | 21.34722 | 32.52710 | -0.3887 | 8.68985 |
May | 344.00000 | 22.55164 | 37.77585 | -1.0659 | 31.17161 |
June | 336.00000 | 23.78154 | 47.41650 | -0.4948 | 11.01212 |
July | 338.00000 | 23.94138 | 56.36739 | -0.3261 | 7.43965 |
August | 348.00000 | 23.90630 | 51.10539 | -0.3798 | 8.28282 |
September | 330.00000 | 23.65956 | 47.69701 | -0.5349 | 12.14653 |
October | 340.00000 | 21.77446 | 38.12025 | -0.2047 | 7.27757 |
November | 330.00000 | 21.20445 | 30.83210 | -0.4587 | 9.77251 |
December | 338.00000 | 21.11000 | 21.08092 | -0.6442 | 13.88152 |
Annual Sum or Average | 4030.00000 | 22.24364 | 35.48223 | -0.5283 | 12.55810 |
Minimum of Months | 308.00000 | 21.10993 | 17.30006 | -1.0659 | 7.27757 |
Maximum of Months | 348.00000 | 23.94138 | 56.36739 | -0.2047 | 31.17161 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.11000 | 17.27804 | -0.6758 | 14.72873 |
February | 308.00000 | 21.10994 | 17.20304 | -0.6746 | 14.68621 |
March | 348.00000 | 21.30343 | 26.52408 | -0.4902 | 11.20777 |
April | 330.00000 | 21.33152 | 32.46398 | -0.3996 | 8.83070 |
May | 344.00000 | 22.49917 | 37.80710 | -1.0990 | 32.56200 |
June | 336.00000 | 23.77557 | 47.42934 | -0.5162 | 11.48231 |
July | 338.00000 | 23.94032 | 56.41405 | -0.3477 | 7.73657 |
August | 348.00000 | 23.90606 | 51.10301 | -0.4007 | 8.61359 |
September | 330.00000 | 23.65721 | 47.67726 | -0.5531 | 12.56629 |
October | 340.00000 | 21.75425 | 38.07985 | -0.2186 | 7.35026 |
November | 330.00000 | 21.19829 | 30.75169 | -0.4640 | 9.85147 |
December | 338.00000 | 21.11000 | 20.98338 | -0.6399 | 13.75907 |
Annual Sum or Average | 4030.00000 | 22.23465 | 35.44202 | -0.5396 | 12.79527 |
Minimum of Months | 308.00000 | 21.10994 | 17.20304 | -1.0990 | 7.35026 |
Maximum of Months | 348.00000 | 23.94032 | 56.41405 | -0.2186 | 32.56200 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.11000 | 17.27830 | -0.6787 | 14.81322 |
February | 308.00000 | 21.11000 | 17.20327 | -0.6774 | 14.76479 |
March | 348.00000 | 21.29949 | 26.53949 | -0.4958 | 11.31213 |
April | 330.00000 | 21.31489 | 32.49326 | -0.4086 | 8.96049 |
May | 344.00000 | 22.42939 | 37.97464 | -1.1287 | 33.84626 |
June | 336.00000 | 23.76019 | 47.53783 | -0.5265 | 11.77553 |
July | 338.00000 | 23.93952 | 56.48545 | -0.3512 | 7.78797 |
August | 348.00000 | 23.90372 | 51.15715 | -0.4046 | 8.68620 |
September | 330.00000 | 23.64089 | 47.76614 | -0.5624 | 12.85355 |
October | 340.00000 | 21.72254 | 38.16559 | -0.2300 | 7.40962 |
November | 330.00000 | 21.19343 | 30.76434 | -0.4698 | 9.95179 |
December | 338.00000 | 21.11000 | 20.98364 | -0.6430 | 13.84268 |
Annual Sum or Average | 4030.00000 | 22.22104 | 35.49537 | -0.5478 | 13.01646 |
Minimum of Months | 308.00000 | 21.11000 | 17.20327 | -1.1287 | 7.40962 |
Maximum of Months | 348.00000 | 23.93952 | 56.48545 | -0.2300 | 33.84626 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.11000 | 17.27860 | -0.6930 | 15.22906 |
February | 308.00000 | 21.10994 | 17.20370 | -0.6908 | 15.15469 |
March | 348.00000 | 21.28705 | 26.58574 | -0.5152 | 11.70879 |
April | 330.00000 | 21.27330 | 32.56567 | -0.4335 | 9.35401 |
May | 344.00000 | 22.26924 | 38.36008 | -1.1947 | 36.80249 |
June | 336.00000 | 23.71277 | 47.83773 | -0.5520 | 12.56464 |
July | 338.00000 | 23.93720 | 56.68074 | -0.3557 | 7.85972 |
August | 348.00000 | 23.89517 | 51.31411 | -0.4111 | 8.82662 |
September | 330.00000 | 23.58947 | 48.02859 | -0.5862 | 13.63757 |
October | 340.00000 | 21.65270 | 38.34687 | -0.2549 | 7.58573 |
November | 330.00000 | 21.17952 | 30.80042 | -0.4867 | 10.26542 |
December | 338.00000 | 21.11000 | 20.98388 | -0.6569 | 14.22555 |
Annual Sum or Average | 4030.00000 | 22.18675 | 35.63295 | -0.5690 | 13.62094 |
Minimum of Months | 308.00000 | 21.10994 | 17.20370 | -1.1947 | 7.58573 |
Maximum of Months | 348.00000 | 23.93720 | 56.68074 | -0.2549 | 36.80249 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.11000 | 17.07897 | -0.7634 | 17.42765 |
February | 308.00000 | 21.11000 | 17.03937 | -0.7591 | 17.27325 |
March | 348.00000 | 21.26752 | 26.46686 | -0.5869 | 13.44751 |
April | 330.00000 | 21.21549 | 32.44608 | -0.5018 | 10.67675 |
May | 344.00000 | 22.03597 | 38.86258 | -1.3159 | 42.58435 |
June | 336.00000 | 23.59527 | 48.29870 | -0.6099 | 14.54702 |
July | 338.00000 | 23.93527 | 56.99492 | -0.3546 | 7.86840 |
August | 348.00000 | 23.86947 | 51.56599 | -0.4174 | 9.08877 |
September | 330.00000 | 23.47290 | 48.40451 | -0.6361 | 15.50613 |
October | 340.00000 | 21.56942 | 38.38598 | -0.3040 | 8.18616 |
November | 330.00000 | 21.15796 | 30.68155 | -0.5418 | 11.46516 |
December | 338.00000 | 21.11000 | 20.82106 | -0.7229 | 16.18650 |
Annual Sum or Average | 4030.00000 | 22.12991 | 35.72361 | -0.6259 | 15.37536 |
Minimum of Months | 308.00000 | 21.11000 | 17.03937 | -1.3159 | 7.86840 |
Maximum of Months | 348.00000 | 23.93527 | 56.99492 | -0.3040 | 42.58435 |
Report: DXReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 |
March | 0.297453E+09 | 82414625.81 | 16.83 | 0.252144E+09 | 45309443.96 | 0.00 | 0.50 | 15-MAR-14:00 | 0.00 | 01-MAR-00:05 | 8518.16 | 15-MAR-14:00 | 7820.13 | 15-MAR-14:00 | 1568.31 | 14-MAR-13:20 | 2333.29 | 15-MAR-14:00 | 0.00 | 01-MAR-00:05 |
April | 28455.60 | 8216.17 | 0.17 | 25523.09 | 2932.50 | 0.00 | 0.00 | 08-APR-13:00 | 0.00 | 01-APR-00:05 | 47.43 | 08-APR-13:00 | 42.54 | 08-APR-13:00 | 4.89 | 08-APR-13:00 | 13.69 | 08-APR-13:00 | 0.00 | 01-APR-00:05 |
May | 0.872700E+09 | 0.236787E+09 | 67.08 | 0.769546E+09 | 0.103154E+09 | 0.00 | 0.62 | 14-MAY-15:00 | 0.00 | 01-MAY-00:10 | 11138.09 | 14-MAY-15:00 | 8750.21 | 14-MAY-15:00 | 2630.08 | 14-MAY-16:10 | 2915.92 | 14-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 0.902121E+10 | 0.227180E+10 | 304.53 | 0.645245E+10 | 0.256876E+10 | 0.00 | 1.00 | 12-JUN-07:03 | 0.00 | 01-JUN-00:10 | 44331.30 | 18-JUN-07:03 | 21808.41 | 18-JUN-07:03 | 22522.90 | 18-JUN-07:03 | 9488.29 | 18-JUN-07:03 | 0.00 | 01-JUN-00:10 |
July | 0.196820E+11 | 0.483428E+10 | 472.77 | 0.129981E+11 | 0.668395E+10 | 0.00 | 1.00 | 02-JUL-07:03 | 0.00 | 01-JUL-00:10 | 45290.73 | 21-JUL-07:02 | 26224.75 | 20-JUL-07:02 | 24510.29 | 22-JUL-07:02 | 9761.42 | 21-JUL-07:03 | 0.00 | 01-JUL-00:10 |
August | 0.153218E+11 | 0.384183E+10 | 428.77 | 0.113464E+11 | 0.397540E+10 | 0.00 | 1.00 | 06-AUG-07:02 | 0.00 | 01-AUG-00:10 | 44364.92 | 14-AUG-07:02 | 29132.92 | 06-AUG-07:02 | 22105.81 | 15-AUG-07:02 | 9489.86 | 14-AUG-07:02 | 0.00 | 01-AUG-00:10 |
September | 0.557685E+10 | 0.141346E+10 | 242.54 | 0.382452E+10 | 0.175233E+10 | 0.00 | 1.00 | 14-SEP-07:03 | 0.00 | 01-SEP-00:10 | 43137.20 | 17-SEP-07:02 | 23831.20 | 17-SEP-07:02 | 19306.00 | 17-SEP-07:02 | 9274.27 | 17-SEP-07:02 | 0.00 | 01-SEP-00:10 |
October | 0.175788E+09 | 47953595.46 | 15.17 | 0.151683E+09 | 24105056.08 | 0.00 | 0.35 | 11-OCT-16:10 | 0.00 | 01-OCT-00:10 | 5730.14 | 11-OCT-16:10 | 4884.16 | 11-OCT-16:10 | 856.63 | 11-OCT-17:10 | 1524.77 | 11-OCT-16:10 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.509479E+11 | 0.127285E+11 | 1547.86 | 0.357949E+11 | 0.151530E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.196820E+11 | 0.483428E+10 | 472.77 | 0.129981E+11 | 0.668395E+10 | 0.00 | 1.00 | 0.00 | 45290.73 | 29132.92 | 24510.29 | 9761.42 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 |
March | 0.219490E+09 | 58112251.54 | 20.10 | 0.186430E+09 | 33059797.72 | 0.00 | 1.00 | 15-MAR-20:01 | 0.00 | 01-MAR-00:05 | 21052.18 | 15-MAR-20:01 | 17380.28 | 15-MAR-20:09 | 3863.32 | 15-MAR-20:20 | 4482.66 | 15-MAR-20:01 | 0.00 | 01-MAR-00:05 |
April | 9156525.18 | 2534239.07 | 4.92 | 8314514.68 | 842010.50 | 0.00 | 0.16 | 09-APR-21:10 | 0.00 | 01-APR-00:05 | 1324.37 | 09-APR-21:10 | 1212.15 | 23-APR-17:10 | 243.07 | 09-APR-21:10 | 361.05 | 09-APR-21:10 | 0.00 | 01-APR-00:05 |
May | 0.787805E+09 | 0.200188E+09 | 85.91 | 0.704657E+09 | 83147971.21 | 0.00 | 1.00 | 13-MAY-18:01 | 0.00 | 01-MAY-00:10 | 21359.19 | 13-MAY-18:01 | 20157.96 | 27-MAY-18:01 | 5569.47 | 13-MAY-18:47 | 4548.02 | 13-MAY-18:01 | 0.00 | 01-MAY-00:10 |
June | 0.593442E+10 | 0.142729E+10 | 305.74 | 0.433435E+10 | 0.160007E+10 | 0.00 | 1.00 | 01-JUN-20:02 | 0.00 | 01-JUN-00:10 | 23519.30 | 18-JUN-07:03 | 20382.87 | 10-JUN-18:02 | 12355.37 | 27-JUN-20:33 | 4964.33 | 27-JUN-07:03 | 0.00 | 01-JUN-00:10 |
July | 0.120209E+11 | 0.283725E+10 | 441.67 | 0.809782E+10 | 0.392312E+10 | 0.00 | 1.00 | 01-JUL-18:02 | 0.00 | 01-JUL-00:10 | 23488.82 | 21-JUL-20:05 | 18248.82 | 06-JUL-20:01 | 12504.87 | 29-JUL-07:03 | 5100.61 | 21-JUL-07:02 | 0.00 | 01-JUL-00:10 |
August | 0.941603E+10 | 0.226697E+10 | 407.10 | 0.702274E+10 | 0.239329E+10 | 0.00 | 1.00 | 01-AUG-20:02 | 0.00 | 01-AUG-00:10 | 23370.97 | 15-AUG-07:02 | 19571.58 | 03-AUG-20:02 | 12739.88 | 28-AUG-20:03 | 4930.76 | 15-AUG-07:02 | 0.00 | 01-AUG-00:10 |
September | 0.371950E+10 | 0.902229E+09 | 252.17 | 0.258620E+10 | 0.113330E+10 | 0.00 | 1.00 | 02-SEP-18:02 | 0.00 | 01-SEP-00:10 | 23325.67 | 15-SEP-20:03 | 18139.27 | 07-SEP-20:10 | 12437.22 | 15-SEP-20:03 | 4887.38 | 15-SEP-20:03 | 0.00 | 01-SEP-00:10 |
October | 0.155404E+09 | 40398946.85 | 27.84 | 0.133808E+09 | 21596012.35 | 0.00 | 1.00 | 22-OCT-17:01 | 0.00 | 01-OCT-00:10 | 21038.94 | 22-OCT-17:09 | 17036.89 | 22-OCT-17:01 | 4762.77 | 22-OCT-17:43 | 4479.74 | 22-OCT-17:09 | 0.00 | 01-OCT-00:10 |
November | 1162423.55 | 326308.54 | 1.08 | 1015293.68 | 147129.87 | 0.00 | 0.06 | 05-NOV-22:10 | 0.00 | 01-NOV-00:10 | 451.80 | 05-NOV-22:10 | 358.09 | 05-NOV-22:10 | 93.71 | 05-NOV-22:10 | 126.63 | 05-NOV-22:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.322639E+11 | 0.773530E+10 | 1546.52 | 0.230753E+11 | 0.918857E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.120209E+11 | 0.283725E+10 | 441.67 | 0.809782E+10 | 0.392312E+10 | 0.00 | 1.00 | 0.00 | 23519.30 | 20382.87 | 12739.88 | 5100.61 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_3:3 COOLING COIL
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 |
March | 0.171709E+09 | 46465456.55 | 16.33 | 0.147144E+09 | 24564499.72 | 0.00 | 0.52 | 15-MAR-14:00 | 0.00 | 01-MAR-00:05 | 4713.13 | 15-MAR-14:00 | 4384.93 | 15-MAR-14:00 | 900.73 | 14-MAR-13:00 | 1263.42 | 15-MAR-14:00 | 0.00 | 01-MAR-00:05 |
April | 2308263.14 | 645412.41 | 1.50 | 2053148.21 | 255114.94 | 0.00 | 0.10 | 08-APR-13:00 | 0.00 | 01-APR-00:05 | 759.21 | 08-APR-13:00 | 688.13 | 08-APR-13:00 | 71.07 | 08-APR-13:00 | 210.41 | 08-APR-13:00 | 0.00 | 01-APR-00:05 |
May | 0.510478E+09 | 0.135180E+09 | 68.17 | 0.456536E+09 | 53942585.25 | 0.00 | 0.58 | 14-MAY-15:00 | 0.00 | 01-MAY-00:10 | 5563.10 | 14-MAY-15:00 | 4447.48 | 14-MAY-15:00 | 1315.72 | 14-MAY-14:00 | 1446.92 | 14-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 0.397218E+10 | 0.982299E+09 | 243.49 | 0.291139E+10 | 0.106079E+10 | 0.00 | 1.00 | 12-JUN-06:03 | 0.00 | 01-JUN-00:10 | 23788.77 | 18-JUN-07:03 | 12431.79 | 26-JUN-06:03 | 12027.79 | 18-JUN-07:03 | 4994.97 | 18-JUN-07:03 | 0.00 | 01-JUN-00:10 |
July | 0.820797E+10 | 0.197862E+10 | 347.44 | 0.556680E+10 | 0.264116E+10 | 0.00 | 1.00 | 02-JUL-07:03 | 0.00 | 01-JUL-00:10 | 24229.10 | 21-JUL-06:02 | 15433.68 | 15-JUL-06:03 | 13457.32 | 29-JUL-06:03 | 5109.97 | 21-JUL-06:03 | 0.00 | 01-JUL-00:10 |
August | 0.660030E+10 | 0.162578E+10 | 327.71 | 0.503619E+10 | 0.156411E+10 | 0.00 | 1.00 | 06-AUG-07:02 | 0.00 | 01-AUG-00:10 | 24021.61 | 14-AUG-06:02 | 16254.53 | 06-AUG-07:02 | 13407.08 | 14-AUG-06:02 | 4977.30 | 14-AUG-06:02 | 0.00 | 01-AUG-00:10 |
September | 0.256201E+10 | 0.636512E+09 | 210.63 | 0.180635E+10 | 0.755660E+09 | 0.00 | 1.00 | 14-SEP-06:03 | 0.00 | 01-SEP-00:10 | 23224.50 | 16-SEP-06:03 | 12877.12 | 17-SEP-07:02 | 11793.56 | 14-SEP-06:03 | 4883.35 | 17-SEP-07:02 | 0.00 | 01-SEP-00:10 |
October | 84298004.63 | 22576066.87 | 15.00 | 74234975.04 | 10063029.59 | 0.00 | 0.35 | 11-OCT-15:00 | 0.00 | 01-OCT-00:10 | 3003.20 | 11-OCT-15:00 | 2699.11 | 11-OCT-13:00 | 413.47 | 11-OCT-16:10 | 792.70 | 11-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.221113E+11 | 0.542808E+10 | 1230.26 | 0.160007E+11 | 0.611056E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.820797E+10 | 0.197862E+10 | 347.44 | 0.556680E+10 | 0.264116E+10 | 0.00 | 1.00 | 0.00 | 24229.10 | 16254.53 | 13457.32 | 5109.97 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_4:4 COOLING COIL
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 |
March | 0.160464E+09 | 43641446.83 | 16.17 | 0.137679E+09 | 22784213.14 | 0.00 | 0.50 | 15-MAR-14:00 | 0.00 | 01-MAR-00:05 | 4534.51 | 15-MAR-14:00 | 4216.49 | 15-MAR-14:00 | 850.34 | 14-MAR-13:00 | 1221.94 | 15-MAR-14:00 | 0.00 | 01-MAR-00:05 |
April | 1191474.83 | 335069.28 | 1.33 | 1062277.05 | 129197.78 | 0.00 | 0.07 | 08-APR-13:00 | 0.00 | 01-APR-00:05 | 541.33 | 08-APR-13:00 | 490.56 | 08-APR-13:00 | 50.77 | 08-APR-13:00 | 151.07 | 08-APR-13:00 | 0.00 | 01-APR-00:05 |
May | 0.471364E+09 | 0.125376E+09 | 63.67 | 0.421491E+09 | 49872509.77 | 0.00 | 0.56 | 14-MAY-15:00 | 0.00 | 01-MAY-00:10 | 5348.69 | 14-MAY-15:00 | 4266.82 | 14-MAY-15:00 | 1269.59 | 14-MAY-14:00 | 1399.33 | 14-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 0.393507E+10 | 0.974064E+09 | 240.90 | 0.288255E+10 | 0.105252E+10 | 0.00 | 1.00 | 12-JUN-06:03 | 0.00 | 01-JUN-00:10 | 23853.00 | 18-JUN-07:03 | 12379.03 | 26-JUN-06:03 | 12063.94 | 18-JUN-07:03 | 5008.56 | 18-JUN-07:03 | 0.00 | 01-JUN-00:10 |
July | 0.820949E+10 | 0.197987E+10 | 347.28 | 0.556779E+10 | 0.264170E+10 | 0.00 | 1.00 | 02-JUL-07:03 | 0.00 | 01-JUL-00:10 | 24300.25 | 21-JUL-06:02 | 15481.60 | 15-JUL-06:03 | 13495.00 | 29-JUL-06:03 | 5123.91 | 21-JUL-06:03 | 0.00 | 01-JUL-00:10 |
August | 0.659908E+10 | 0.162625E+10 | 327.54 | 0.503619E+10 | 0.156289E+10 | 0.00 | 1.00 | 06-AUG-07:02 | 0.00 | 01-AUG-00:10 | 24088.08 | 14-AUG-06:02 | 16307.42 | 06-AUG-07:02 | 13473.15 | 14-AUG-06:04 | 4990.89 | 14-AUG-06:02 | 0.00 | 01-AUG-00:10 |
September | 0.251549E+10 | 0.625515E+09 | 205.88 | 0.177146E+10 | 0.744028E+09 | 0.00 | 1.00 | 14-SEP-06:03 | 0.00 | 01-SEP-00:10 | 23288.13 | 16-SEP-06:03 | 12914.93 | 17-SEP-07:02 | 11830.57 | 14-SEP-06:03 | 4896.66 | 17-SEP-07:02 | 0.00 | 01-SEP-00:10 |
October | 71970368.54 | 19419766.04 | 13.42 | 63418706.39 | 8551662.14 | 0.00 | 0.31 | 11-OCT-15:00 | 0.00 | 01-OCT-00:10 | 2688.33 | 11-OCT-15:00 | 2394.04 | 11-OCT-13:00 | 371.57 | 11-OCT-16:10 | 716.27 | 11-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.219641E+11 | 0.539447E+10 | 1216.18 | 0.158816E+11 | 0.608248E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.820949E+10 | 0.197987E+10 | 347.28 | 0.556779E+10 | 0.264170E+10 | 0.00 | 1.00 | 0.00 | 24300.25 | 16307.42 | 13495.00 | 5123.91 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_5:5 COOLING COIL
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 |
March | 0.143279E+09 | 39235738.52 | 15.50 | 0.122991E+09 | 20288267.74 | 0.00 | 0.47 | 15-MAR-14:00 | 0.00 | 01-MAR-00:05 | 4231.45 | 15-MAR-14:00 | 3928.40 | 15-MAR-14:00 | 781.44 | 14-MAR-13:00 | 1148.79 | 15-MAR-14:00 | 0.00 | 01-MAR-00:05 |
April | 111862.57 | 31569.38 | 0.17 | 101210.76 | 10651.80 | 0.00 | 0.02 | 08-APR-13:00 | 0.00 | 01-APR-00:05 | 186.44 | 08-APR-13:00 | 168.68 | 08-APR-13:00 | 17.75 | 08-APR-13:00 | 52.62 | 08-APR-13:00 | 0.00 | 01-APR-00:05 |
May | 0.406900E+09 | 0.109011E+09 | 55.67 | 0.363220E+09 | 43679084.39 | 0.00 | 0.54 | 14-MAY-15:00 | 0.00 | 01-MAY-00:10 | 5037.08 | 14-MAY-15:00 | 4002.68 | 14-MAY-15:00 | 1200.63 | 14-MAY-14:00 | 1326.99 | 14-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 0.375491E+10 | 0.931981E+09 | 235.44 | 0.274525E+10 | 0.100966E+10 | 0.00 | 1.00 | 12-JUN-06:03 | 0.00 | 01-JUN-00:10 | 23664.73 | 18-JUN-07:03 | 11651.31 | 18-JUN-07:03 | 12013.42 | 18-JUN-07:03 | 4969.80 | 18-JUN-07:03 | 0.00 | 01-JUN-00:10 |
July | 0.796066E+10 | 0.192441E+10 | 344.69 | 0.539229E+10 | 0.256837E+10 | 0.00 | 1.00 | 02-JUL-07:03 | 0.00 | 01-JUL-00:10 | 24098.59 | 21-JUL-06:02 | 15317.78 | 15-JUL-06:03 | 13425.44 | 29-JUL-06:03 | 5084.42 | 21-JUL-06:03 | 0.00 | 01-JUL-00:10 |
August | 0.639100E+10 | 0.157904E+10 | 323.65 | 0.487576E+10 | 0.151525E+10 | 0.00 | 1.00 | 06-AUG-07:02 | 0.00 | 01-AUG-00:10 | 23899.27 | 14-AUG-06:02 | 16144.59 | 06-AUG-07:02 | 13362.48 | 14-AUG-06:02 | 4952.37 | 14-AUG-06:02 | 0.00 | 01-AUG-00:10 |
September | 0.236944E+10 | 0.590747E+09 | 196.71 | 0.166443E+10 | 0.705009E+09 | 0.00 | 1.00 | 14-SEP-06:03 | 0.00 | 01-SEP-00:10 | 23015.63 | 17-SEP-07:02 | 12780.56 | 17-SEP-07:02 | 11486.20 | 14-SEP-06:03 | 4858.61 | 17-SEP-07:02 | 0.00 | 01-SEP-00:10 |
October | 58417759.57 | 15896278.82 | 11.83 | 51464270.75 | 6953488.82 | 0.00 | 0.28 | 11-OCT-15:00 | 0.00 | 01-OCT-00:10 | 2319.30 | 11-OCT-15:00 | 2054.72 | 11-OCT-13:00 | 324.11 | 11-OCT-16:10 | 624.33 | 11-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.210847E+11 | 0.519036E+10 | 1183.67 | 0.152155E+11 | 0.586922E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.796066E+10 | 0.192441E+10 | 344.69 | 0.539229E+10 | 0.256837E+10 | 0.00 | 1.00 | 0.00 | 24098.59 | 16144.59 | 13425.44 | 5084.42 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_6:6 COOLING COIL
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 |
March | 0.226723E+09 | 62377300.14 | 14.17 | 0.189173E+09 | 37550759.64 | 0.00 | 0.47 | 15-MAR-14:10 | 0.00 | 01-MAR-00:05 | 7503.68 | 15-MAR-14:10 | 6762.26 | 15-MAR-14:10 | 1500.45 | 14-MAR-13:00 | 2036.46 | 15-MAR-14:10 | 0.00 | 01-MAR-00:05 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 |
May | 0.617755E+09 | 0.166529E+09 | 49.75 | 0.541588E+09 | 76167247.76 | 0.00 | 0.56 | 14-MAY-15:00 | 0.00 | 01-MAY-00:10 | 9621.53 | 14-MAY-15:00 | 7378.56 | 14-MAY-15:00 | 2378.41 | 14-MAY-14:20 | 2509.95 | 14-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 0.648062E+10 | 0.160857E+10 | 220.96 | 0.462812E+10 | 0.185250E+10 | 0.00 | 1.00 | 12-JUN-07:03 | 0.00 | 01-JUN-00:10 | 42668.42 | 18-JUN-08:63 | 22895.77 | 18-JUN-08:63 | 20776.68 | 27-JUN-07:03 | 9045.51 | 18-JUN-08:63 | 0.00 | 01-JUN-00:10 |
July | 0.141347E+11 | 0.341556E+10 | 336.10 | 0.939670E+10 | 0.473795E+10 | 0.00 | 1.00 | 02-JUL-08:63 | 0.00 | 01-JUL-00:10 | 43180.19 | 16-JUL-08:62 | 25837.43 | 20-JUL-07:02 | 23474.95 | 29-JUL-07:03 | 9210.22 | 21-JUL-07:02 | 0.00 | 01-JUL-00:10 |
August | 0.113325E+11 | 0.280053E+10 | 316.12 | 0.850535E+10 | 0.282715E+10 | 0.00 | 1.00 | 06-AUG-08:62 | 0.00 | 01-AUG-00:10 | 43229.87 | 14-AUG-07:02 | 29778.73 | 06-AUG-08:62 | 21188.10 | 15-AUG-07:02 | 8975.73 | 14-AUG-07:02 | 0.00 | 01-AUG-00:10 |
September | 0.395896E+10 | 0.988029E+09 | 178.06 | 0.273647E+10 | 0.122249E+10 | 0.00 | 1.00 | 14-SEP-07:03 | 0.00 | 01-SEP-00:10 | 41449.74 | 17-SEP-08:62 | 22137.55 | 17-SEP-08:62 | 19312.19 | 17-SEP-08:62 | 8717.79 | 17-SEP-08:62 | 0.00 | 01-SEP-00:10 |
October | 81039497.71 | 22167840.40 | 9.50 | 70375864.39 | 10663633.31 | 0.00 | 0.28 | 11-OCT-15:00 | 0.00 | 01-OCT-00:10 | 4279.67 | 11-OCT-15:00 | 3696.29 | 11-OCT-15:00 | 583.38 | 11-OCT-15:00 | 1150.22 | 11-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.368323E+11 | 0.906376E+10 | 1124.65 | 0.260678E+11 | 0.107645E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.141347E+11 | 0.341556E+10 | 336.10 | 0.939670E+10 | 0.473795E+10 | 0.00 | 1.00 | 0.00 | 43229.87 | 29778.73 | 23474.95 | 9210.22 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_7:7 COOLING COIL
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 |
March | 0.110865E+09 | 30584938.28 | 13.67 | 92829375.25 | 18035244.15 | 0.00 | 0.46 | 15-MAR-14:10 | 0.00 | 01-MAR-00:05 | 3796.91 | 15-MAR-14:10 | 3426.74 | 15-MAR-14:10 | 719.11 | 14-MAR-13:00 | 1033.12 | 15-MAR-14:10 | 0.00 | 01-MAR-00:05 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 |
May | 0.291273E+09 | 78797062.22 | 47.00 | 0.255442E+09 | 35831548.94 | 0.00 | 0.55 | 14-MAY-15:00 | 0.00 | 01-MAY-00:10 | 4854.18 | 14-MAY-15:00 | 3722.29 | 14-MAY-15:00 | 1191.39 | 14-MAY-14:30 | 1270.65 | 14-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 0.328249E+10 | 0.815962E+09 | 216.12 | 0.234777E+10 | 0.934719E+09 | 0.00 | 1.00 | 12-JUN-07:03 | 0.00 | 01-JUN-00:10 | 20454.56 | 18-JUN-08:63 | 10917.33 | 18-JUN-08:63 | 9874.60 | 27-JUN-07:03 | 4337.73 | 18-JUN-08:63 | 0.00 | 01-JUN-00:10 |
July | 0.722349E+10 | 0.174839E+10 | 336.18 | 0.481403E+10 | 0.240946E+10 | 0.00 | 1.00 | 05-JUL-07:03 | 0.00 | 01-JUL-00:10 | 22339.27 | 16-JUL-08:62 | 13363.06 | 20-JUL-07:02 | 11844.31 | 22-JUL-07:02 | 4764.23 | 21-JUL-07:02 | 0.00 | 01-JUL-00:10 |
August | 0.579375E+10 | 0.143371E+10 | 314.07 | 0.435831E+10 | 0.143544E+10 | 0.00 | 1.00 | 06-AUG-08:62 | 0.00 | 01-AUG-00:10 | 22368.47 | 14-AUG-07:02 | 14686.81 | 06-AUG-08:62 | 10937.57 | 15-AUG-07:02 | 4643.14 | 14-AUG-07:02 | 0.00 | 01-AUG-00:10 |
September | 0.200558E+10 | 0.500935E+09 | 175.68 | 0.138764E+10 | 0.617935E+09 | 0.00 | 1.00 | 14-SEP-07:03 | 0.00 | 01-SEP-00:10 | 21444.34 | 17-SEP-08:62 | 11468.44 | 17-SEP-08:62 | 9975.90 | 17-SEP-08:62 | 4509.90 | 17-SEP-08:62 | 0.00 | 01-SEP-00:10 |
October | 37704126.87 | 10341336.65 | 9.33 | 32797945.04 | 4906181.82 | 0.00 | 0.27 | 11-OCT-15:00 | 0.00 | 01-OCT-00:10 | 2122.42 | 11-OCT-15:00 | 1836.67 | 11-OCT-15:00 | 285.75 | 11-OCT-15:00 | 572.09 | 11-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.187451E+11 | 0.461871E+10 | 1112.05 | 0.132888E+11 | 0.545632E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.722349E+10 | 0.174839E+10 | 336.18 | 0.481403E+10 | 0.240946E+10 | 0.00 | 1.00 | 0.00 | 22368.47 | 14686.81 | 11844.31 | 4764.23 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_8:8 COOLING COIL
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 |
March | 0.106532E+09 | 29441577.85 | 13.50 | 89176286.33 | 17356204.86 | 0.00 | 0.45 | 15-MAR-14:10 | 0.00 | 01-MAR-00:05 | 3711.66 | 15-MAR-14:10 | 3346.35 | 15-MAR-14:10 | 690.05 | 14-MAR-13:00 | 1011.94 | 15-MAR-14:10 | 0.00 | 01-MAR-00:05 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 |
May | 0.267609E+09 | 72635127.53 | 44.83 | 0.233967E+09 | 33642347.12 | 0.00 | 0.54 | 14-MAY-15:00 | 0.00 | 01-MAY-00:10 | 4724.28 | 14-MAY-15:00 | 3615.27 | 14-MAY-15:00 | 1163.18 | 14-MAY-14:30 | 1240.26 | 14-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 0.320748E+10 | 0.798167E+09 | 213.40 | 0.228959E+10 | 0.917888E+09 | 0.00 | 1.00 | 18-JUN-08:63 | 0.00 | 01-JUN-00:10 | 19002.48 | 18-JUN-08:63 | 10059.10 | 18-JUN-08:63 | 9310.76 | 27-JUN-07:03 | 4031.98 | 18-JUN-08:63 | 0.00 | 01-JUN-00:10 |
July | 0.713582E+10 | 0.172826E+10 | 335.68 | 0.475079E+10 | 0.238503E+10 | 0.00 | 1.00 | 05-JUL-07:03 | 0.00 | 01-JUL-00:10 | 22227.29 | 16-JUL-08:62 | 13252.18 | 20-JUL-07:02 | 11798.92 | 22-JUL-07:02 | 4741.20 | 21-JUL-07:02 | 0.00 | 01-JUL-00:10 |
August | 0.572228E+10 | 0.141693E+10 | 312.04 | 0.430218E+10 | 0.142010E+10 | 0.00 | 1.00 | 06-AUG-08:62 | 0.00 | 01-AUG-00:10 | 22256.04 | 14-AUG-07:02 | 14149.29 | 06-AUG-08:62 | 10900.38 | 15-AUG-07:02 | 4620.62 | 14-AUG-07:02 | 0.00 | 01-AUG-00:10 |
September | 0.195820E+10 | 0.489488E+09 | 173.18 | 0.135282E+10 | 0.605381E+09 | 0.00 | 1.00 | 14-SEP-07:03 | 0.00 | 01-SEP-00:10 | 21339.75 | 17-SEP-08:62 | 11401.16 | 17-SEP-08:62 | 9938.59 | 17-SEP-08:62 | 4488.01 | 17-SEP-08:62 | 0.00 | 01-SEP-00:10 |
October | 34637473.07 | 9522410.67 | 9.00 | 30108608.45 | 4528864.62 | 0.00 | 0.26 | 11-OCT-15:00 | 0.00 | 01-OCT-00:10 | 2020.49 | 11-OCT-15:00 | 1746.79 | 11-OCT-15:00 | 273.70 | 11-OCT-15:00 | 546.22 | 11-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.184326E+11 | 0.454444E+10 | 1101.64 | 0.130486E+11 | 0.538393E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.713582E+10 | 0.172826E+10 | 335.68 | 0.475079E+10 | 0.238503E+10 | 0.00 | 1.00 | 0.00 | 22256.04 | 14149.29 | 11798.92 | 4741.20 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_9:9 COOLING COIL
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 |
March | 93386048.82 | 25966370.99 | 12.83 | 78298563.05 | 15087485.77 | 0.00 | 0.43 | 15-MAR-14:10 | 0.00 | 01-MAR-00:05 | 3472.95 | 15-MAR-14:10 | 3126.87 | 15-MAR-14:10 | 590.77 | 14-MAR-13:00 | 952.81 | 15-MAR-14:10 | 0.00 | 01-MAR-00:05 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 |
May | 0.217351E+09 | 59444230.11 | 40.67 | 0.188728E+09 | 28622679.33 | 0.00 | 0.51 | 14-MAY-15:00 | 0.00 | 01-MAY-00:10 | 4385.08 | 14-MAY-15:00 | 3342.21 | 14-MAY-15:00 | 1085.85 | 14-MAY-14:30 | 1160.80 | 14-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 0.302841E+10 | 0.755736E+09 | 203.46 | 0.215408E+10 | 0.874331E+09 | 0.00 | 1.00 | 18-JUN-08:63 | 0.00 | 01-JUN-00:10 | 14148.07 | 18-JUN-08:63 | 7817.16 | 27-JUN-13:00 | 6886.52 | 27-JUN-07:03 | 3008.37 | 18-JUN-08:63 | 0.00 | 01-JUN-00:10 |
July | 0.693733E+10 | 0.168275E+10 | 332.34 | 0.461458E+10 | 0.232275E+10 | 0.00 | 1.00 | 05-JUL-07:03 | 0.00 | 01-JUL-00:10 | 22016.98 | 16-JUL-08:62 | 13002.03 | 20-JUL-07:02 | 11719.15 | 22-JUL-07:02 | 4699.56 | 21-JUL-07:02 | 0.00 | 01-JUL-00:10 |
August | 0.556377E+10 | 0.137944E+10 | 306.48 | 0.418448E+10 | 0.137929E+10 | 0.00 | 1.00 | 06-AUG-08:62 | 0.00 | 01-AUG-00:10 | 22043.53 | 14-AUG-07:02 | 12515.02 | 06-AUG-08:62 | 10841.11 | 14-AUG-07:02 | 4579.73 | 14-AUG-07:02 | 0.00 | 01-AUG-00:10 |
September | 0.184050E+10 | 0.460968E+09 | 159.10 | 0.126843E+10 | 0.572072E+09 | 0.00 | 1.00 | 16-SEP-07:03 | 0.00 | 01-SEP-00:10 | 21149.47 | 17-SEP-08:62 | 11277.52 | 17-SEP-08:62 | 9871.95 | 17-SEP-08:62 | 4448.33 | 17-SEP-08:62 | 0.00 | 01-SEP-00:10 |
October | 28436980.62 | 7854414.29 | 8.17 | 24723011.03 | 3713969.60 | 0.00 | 0.24 | 11-OCT-15:00 | 0.00 | 01-OCT-00:10 | 1809.98 | 11-OCT-15:00 | 1563.55 | 11-OCT-15:00 | 246.43 | 11-OCT-15:00 | 492.38 | 11-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.177092E+11 | 0.437216E+10 | 1063.04 | 0.125133E+11 | 0.519587E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.693733E+10 | 0.168275E+10 | 332.34 | 0.461458E+10 | 0.232275E+10 | 0.00 | 1.00 | 0.00 | 22043.53 | 13002.03 | 11719.15 | 4699.56 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_10:10 COOLING COIL
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 |
March | 75616367.68 | 21261566.85 | 12.00 | 64082273.90 | 11534093.78 | 0.00 | 0.38 | 15-MAR-14:10 | 0.00 | 01-MAR-00:05 | 3226.12 | 15-MAR-14:10 | 2915.52 | 15-MAR-14:10 | 467.67 | 14-MAR-14:10 | 895.84 | 15-MAR-14:10 | 0.00 | 01-MAR-00:05 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 |
May | 0.152261E+09 | 42233568.61 | 33.33 | 0.130976E+09 | 21285578.18 | 0.00 | 0.44 | 14-MAY-15:00 | 0.00 | 01-MAY-00:10 | 3951.92 | 14-MAY-15:00 | 3005.55 | 14-MAY-15:00 | 971.68 | 14-MAY-14:30 | 1064.51 | 14-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 0.289081E+10 | 0.725494E+09 | 187.81 | 0.206106E+10 | 0.829752E+09 | 0.00 | 1.00 | 27-JUN-11:50 | 0.00 | 01-JUN-00:10 | 12990.84 | 27-JUN-13:00 | 8171.45 | 27-JUN-13:00 | 4819.39 | 27-JUN-13:00 | 3051.94 | 27-JUN-13:00 | 0.00 | 01-JUN-00:10 |
July | 0.694383E+10 | 0.169226E+10 | 325.02 | 0.466472E+10 | 0.227911E+10 | 0.00 | 1.00 | 15-JUL-13:20 | 0.00 | 01-JUL-00:10 | 23426.94 | 21-JUL-07:02 | 12058.26 | 20-JUL-07:02 | 12832.39 | 21-JUL-07:03 | 4918.99 | 21-JUL-07:03 | 0.00 | 01-JUL-00:10 |
August | 0.561561E+10 | 0.139518E+10 | 295.08 | 0.427027E+10 | 0.134533E+10 | 0.00 | 1.00 | 07-AUG-07:02 | 0.00 | 01-AUG-00:10 | 23182.75 | 14-AUG-07:02 | 12006.31 | 07-AUG-07:02 | 12152.58 | 14-AUG-07:02 | 4796.80 | 14-AUG-07:02 | 0.00 | 01-AUG-00:10 |
September | 0.174098E+10 | 0.437401E+09 | 141.72 | 0.120941E+10 | 0.531569E+09 | 0.00 | 1.00 | 17-SEP-08:62 | 0.00 | 01-SEP-00:10 | 17021.33 | 17-SEP-08:62 | 8877.64 | 17-SEP-08:62 | 8143.69 | 17-SEP-08:62 | 3580.76 | 17-SEP-08:62 | 0.00 | 01-SEP-00:10 |
October | 26126607.04 | 7239745.70 | 7.50 | 22941717.68 | 3184889.36 | 0.00 | 0.22 | 11-OCT-15:00 | 0.00 | 01-OCT-00:10 | 1723.88 | 11-OCT-15:00 | 1498.97 | 11-OCT-15:00 | 224.90 | 11-OCT-15:00 | 471.46 | 11-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.174452E+11 | 0.432108E+10 | 1002.46 | 0.124235E+11 | 0.502177E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.694383E+10 | 0.169226E+10 | 325.02 | 0.466472E+10 | 0.227911E+10 | 0.00 | 1.00 | 0.00 | 23426.94 | 12058.26 | 12832.39 | 4918.99 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.30 | 45.12 | 32.18 | 66.17 | 91.18 | 0.00 | 0.00 | 0.00 |
February | 88.26 | 42.56 | 45.70 | 75.06 | 88.20 | 0.00 | 0.00 | 0.00 |
March | 107.72 | 60.53 | 47.19 | 113.01 | 63.55 | 0.00 | 0.00 | 0.00 |
April | 89.21 | 35.65 | 53.56 | 98.73 | 48.29 | 0.00 | 0.00 | 0.00 |
May | 78.07 | 22.67 | 55.39 | 93.05 | 32.96 | 0.00 | 0.00 | 0.00 |
June | 75.86 | 16.07 | 59.78 | 98.24 | 22.52 | 0.00 | 0.00 | 0.00 |
July | 77.44 | 18.79 | 58.65 | 110.32 | 15.21 | 0.00 | 0.00 | 0.00 |
August | 86.94 | 28.19 | 58.75 | 121.15 | 20.41 | 0.00 | 0.00 | 0.00 |
September | 101.08 | 49.23 | 51.85 | 130.11 | 33.05 | 0.00 | 0.00 | 0.00 |
October | 96.72 | 55.25 | 41.47 | 110.13 | 48.14 | 0.00 | 0.00 | 0.00 |
November | 69.27 | 39.10 | 30.16 | 69.62 | 61.27 | 0.00 | 0.00 | 0.00 |
December | 64.64 | 33.45 | 31.18 | 52.40 | 89.48 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 84.35 | 37.20 | 47.15 | 94.95 | 50.99 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 64.64 | 16.07 | 30.16 | 52.40 | 15.21 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 107.72 | 60.53 | 59.78 | 130.11 | 91.18 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.30 | 45.12 | 32.18 | 66.17 | 91.18 | 0.00 | 0.00 | 0.00 |
February | 88.26 | 42.56 | 45.70 | 75.06 | 88.20 | 0.00 | 0.00 | 0.00 |
March | 107.72 | 60.53 | 47.19 | 113.01 | 63.55 | 0.00 | 0.00 | 0.00 |
April | 89.21 | 35.65 | 53.56 | 98.73 | 48.29 | 0.00 | 0.00 | 0.00 |
May | 78.07 | 22.67 | 55.39 | 93.05 | 32.96 | 0.00 | 0.00 | 0.00 |
June | 75.86 | 16.07 | 59.78 | 98.24 | 22.52 | 0.00 | 0.00 | 0.00 |
July | 77.44 | 18.79 | 58.65 | 110.32 | 15.21 | 0.00 | 0.00 | 0.00 |
August | 86.94 | 28.19 | 58.75 | 121.15 | 20.41 | 0.00 | 0.00 | 0.00 |
September | 101.08 | 49.23 | 51.85 | 130.11 | 33.05 | 0.00 | 0.00 | 0.00 |
October | 96.72 | 55.25 | 41.47 | 110.13 | 48.14 | 0.00 | 0.00 | 0.00 |
November | 69.27 | 39.10 | 30.16 | 69.62 | 61.27 | 0.00 | 0.00 | 0.00 |
December | 64.64 | 33.45 | 31.18 | 52.40 | 89.48 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 84.35 | 37.20 | 47.15 | 94.95 | 50.99 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 64.64 | 16.07 | 30.16 | 52.40 | 15.21 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 107.72 | 60.53 | 59.78 | 130.11 | 91.18 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.30 | 45.12 | 32.18 | 66.17 | 91.18 | 0.00 | 0.00 | 0.00 |
February | 88.26 | 42.56 | 45.70 | 75.06 | 88.20 | 0.00 | 0.00 | 0.00 |
March | 107.72 | 60.53 | 47.19 | 113.01 | 63.55 | 0.00 | 0.00 | 0.00 |
April | 89.21 | 35.65 | 53.56 | 98.73 | 48.29 | 0.00 | 0.00 | 0.00 |
May | 78.07 | 22.67 | 55.39 | 93.05 | 32.96 | 0.00 | 0.00 | 0.00 |
June | 75.86 | 16.07 | 59.78 | 98.24 | 22.52 | 0.00 | 0.00 | 0.00 |
July | 77.44 | 18.79 | 58.65 | 110.32 | 15.21 | 0.00 | 0.00 | 0.00 |
August | 86.94 | 28.19 | 58.75 | 121.15 | 20.41 | 0.00 | 0.00 | 0.00 |
September | 101.08 | 49.23 | 51.85 | 130.11 | 33.05 | 0.00 | 0.00 | 0.00 |
October | 96.72 | 55.25 | 41.47 | 110.13 | 48.14 | 0.00 | 0.00 | 0.00 |
November | 69.27 | 39.10 | 30.16 | 69.62 | 61.27 | 0.00 | 0.00 | 0.00 |
December | 64.64 | 33.45 | 31.18 | 52.40 | 89.48 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 84.35 | 37.20 | 47.15 | 94.95 | 50.99 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 64.64 | 16.07 | 30.16 | 52.40 | 15.21 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 107.72 | 60.53 | 59.78 | 130.11 | 91.18 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.30 | 45.12 | 32.18 | 66.17 | 91.18 | 0.00 | 0.00 | 0.00 |
February | 88.26 | 42.56 | 45.70 | 75.06 | 88.20 | 0.00 | 0.00 | 0.00 |
March | 107.72 | 60.53 | 47.19 | 113.01 | 63.55 | 0.00 | 0.00 | 0.00 |
April | 89.21 | 35.65 | 53.56 | 98.73 | 48.29 | 0.00 | 0.00 | 0.00 |
May | 78.07 | 22.67 | 55.39 | 93.05 | 32.96 | 0.00 | 0.00 | 0.00 |
June | 75.86 | 16.07 | 59.78 | 98.24 | 22.52 | 0.00 | 0.00 | 0.00 |
July | 77.44 | 18.79 | 58.65 | 110.32 | 15.21 | 0.00 | 0.00 | 0.00 |
August | 86.94 | 28.19 | 58.75 | 121.15 | 20.41 | 0.00 | 0.00 | 0.00 |
September | 101.08 | 49.23 | 51.85 | 130.11 | 33.05 | 0.00 | 0.00 | 0.00 |
October | 96.72 | 55.25 | 41.47 | 110.13 | 48.14 | 0.00 | 0.00 | 0.00 |
November | 69.27 | 39.10 | 30.16 | 69.62 | 61.27 | 0.00 | 0.00 | 0.00 |
December | 64.64 | 33.45 | 31.18 | 52.40 | 89.48 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 84.35 | 37.20 | 47.15 | 94.95 | 50.99 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 64.64 | 16.07 | 30.16 | 52.40 | 15.21 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 107.72 | 60.53 | 59.78 | 130.11 | 91.18 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 92.93 | 54.24 | 38.68 | 80.07 | 108.03 | 0.00 | 0.00 | 0.00 |
February | 106.10 | 51.16 | 54.94 | 91.01 | 104.39 | 0.00 | 0.00 | 0.00 |
March | 129.50 | 72.76 | 56.73 | 136.46 | 75.45 | 0.00 | 0.00 | 0.00 |
April | 107.25 | 42.86 | 64.39 | 119.11 | 57.36 | 0.00 | 0.00 | 0.00 |
May | 93.85 | 27.26 | 66.59 | 112.13 | 39.25 | 0.00 | 0.00 | 0.00 |
June | 91.19 | 19.32 | 71.87 | 118.23 | 26.89 | 0.00 | 0.00 | 0.00 |
July | 93.09 | 22.59 | 70.50 | 132.60 | 18.21 | 0.00 | 0.00 | 0.00 |
August | 104.51 | 33.88 | 70.63 | 145.64 | 24.39 | 0.00 | 0.00 | 0.00 |
September | 121.51 | 59.19 | 62.33 | 156.53 | 39.44 | 0.00 | 0.00 | 0.00 |
October | 116.27 | 66.42 | 49.85 | 132.75 | 57.28 | 0.00 | 0.00 | 0.00 |
November | 83.27 | 47.01 | 36.26 | 84.05 | 72.73 | 0.00 | 0.00 | 0.00 |
December | 77.70 | 40.22 | 37.49 | 63.50 | 105.91 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 101.40 | 44.72 | 56.68 | 114.48 | 60.55 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 77.70 | 19.32 | 36.26 | 63.50 | 18.21 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 129.50 | 72.76 | 71.87 | 156.53 | 108.03 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 92.93 | 54.24 | 38.68 | 80.07 | 108.03 | 0.00 | 0.00 | 0.00 |
February | 106.10 | 51.16 | 54.94 | 91.01 | 104.39 | 0.00 | 0.00 | 0.00 |
March | 129.50 | 72.76 | 56.73 | 136.46 | 75.45 | 0.00 | 0.00 | 0.00 |
April | 107.25 | 42.86 | 64.39 | 119.11 | 57.36 | 0.00 | 0.00 | 0.00 |
May | 93.85 | 27.26 | 66.59 | 112.13 | 39.25 | 0.00 | 0.00 | 0.00 |
June | 91.19 | 19.32 | 71.87 | 118.23 | 26.89 | 0.00 | 0.00 | 0.00 |
July | 93.09 | 22.59 | 70.50 | 132.60 | 18.21 | 0.00 | 0.00 | 0.00 |
August | 104.51 | 33.88 | 70.63 | 145.64 | 24.39 | 0.00 | 0.00 | 0.00 |
September | 121.51 | 59.19 | 62.33 | 156.53 | 39.44 | 0.00 | 0.00 | 0.00 |
October | 116.27 | 66.42 | 49.85 | 132.75 | 57.28 | 0.00 | 0.00 | 0.00 |
November | 83.27 | 47.01 | 36.26 | 84.05 | 72.73 | 0.00 | 0.00 | 0.00 |
December | 77.70 | 40.22 | 37.49 | 63.50 | 105.91 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 101.40 | 44.72 | 56.68 | 114.48 | 60.55 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 77.70 | 19.32 | 36.26 | 63.50 | 18.21 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 129.50 | 72.76 | 71.87 | 156.53 | 108.03 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.30 | 45.12 | 32.18 | 65.17 | 95.32 | 0.00 | 0.00 | 0.00 |
February | 88.26 | 42.56 | 45.70 | 73.73 | 92.33 | 0.00 | 0.00 | 0.00 |
March | 107.72 | 60.53 | 47.19 | 111.48 | 67.36 | 0.00 | 0.00 | 0.00 |
April | 89.21 | 35.65 | 53.56 | 97.12 | 52.28 | 0.00 | 0.00 | 0.00 |
May | 78.07 | 22.67 | 55.39 | 91.20 | 35.92 | 0.00 | 0.00 | 0.00 |
June | 75.86 | 16.07 | 59.78 | 97.56 | 23.30 | 0.00 | 0.00 | 0.00 |
July | 77.44 | 18.79 | 58.65 | 110.07 | 15.53 | 0.00 | 0.00 | 0.00 |
August | 86.94 | 28.19 | 58.75 | 120.91 | 20.76 | 0.00 | 0.00 | 0.00 |
September | 101.08 | 49.23 | 51.85 | 129.52 | 34.04 | 0.00 | 0.00 | 0.00 |
October | 96.72 | 55.25 | 41.47 | 108.88 | 51.36 | 0.00 | 0.00 | 0.00 |
November | 69.27 | 39.10 | 30.16 | 68.67 | 65.07 | 0.00 | 0.00 | 0.00 |
December | 64.64 | 33.45 | 31.18 | 51.54 | 93.73 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 84.35 | 37.20 | 47.15 | 93.94 | 53.71 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 64.64 | 16.07 | 30.16 | 51.54 | 15.53 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 107.72 | 60.53 | 59.78 | 129.52 | 95.32 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.30 | 45.12 | 32.18 | 65.17 | 95.32 | 0.00 | 0.00 | 0.00 |
February | 88.26 | 42.56 | 45.70 | 73.73 | 92.33 | 0.00 | 0.00 | 0.00 |
March | 107.72 | 60.53 | 47.19 | 111.48 | 67.36 | 0.00 | 0.00 | 0.00 |
April | 89.21 | 35.65 | 53.56 | 97.12 | 52.28 | 0.00 | 0.00 | 0.00 |
May | 78.07 | 22.67 | 55.39 | 91.20 | 35.92 | 0.00 | 0.00 | 0.00 |
June | 75.86 | 16.07 | 59.78 | 97.56 | 23.30 | 0.00 | 0.00 | 0.00 |
July | 77.44 | 18.79 | 58.65 | 110.07 | 15.53 | 0.00 | 0.00 | 0.00 |
August | 86.94 | 28.19 | 58.75 | 120.91 | 20.76 | 0.00 | 0.00 | 0.00 |
September | 101.08 | 49.23 | 51.85 | 129.52 | 34.04 | 0.00 | 0.00 | 0.00 |
October | 96.72 | 55.25 | 41.47 | 108.88 | 51.36 | 0.00 | 0.00 | 0.00 |
November | 69.27 | 39.10 | 30.16 | 68.67 | 65.07 | 0.00 | 0.00 | 0.00 |
December | 64.64 | 33.45 | 31.18 | 51.54 | 93.73 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 84.35 | 37.20 | 47.15 | 93.94 | 53.71 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 64.64 | 16.07 | 30.16 | 51.54 | 15.53 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 107.72 | 60.53 | 59.78 | 129.52 | 95.32 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_DOOR
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 92.93 | 54.24 | 38.68 | 78.88 | 112.89 | 0.00 | 0.00 | 0.00 |
February | 106.10 | 51.16 | 54.94 | 89.45 | 109.23 | 0.00 | 0.00 | 0.00 |
March | 129.50 | 72.76 | 56.73 | 134.66 | 79.93 | 0.00 | 0.00 | 0.00 |
April | 107.25 | 42.86 | 64.39 | 117.20 | 62.04 | 0.00 | 0.00 | 0.00 |
May | 93.85 | 27.26 | 66.59 | 109.94 | 42.74 | 0.00 | 0.00 | 0.00 |
June | 91.19 | 19.32 | 71.87 | 117.43 | 27.81 | 0.00 | 0.00 | 0.00 |
July | 93.09 | 22.59 | 70.50 | 132.32 | 18.58 | 0.00 | 0.00 | 0.00 |
August | 104.51 | 33.88 | 70.63 | 145.39 | 24.81 | 0.00 | 0.00 | 0.00 |
September | 121.51 | 59.19 | 62.33 | 155.85 | 40.61 | 0.00 | 0.00 | 0.00 |
October | 116.27 | 66.42 | 49.85 | 131.28 | 61.06 | 0.00 | 0.00 | 0.00 |
November | 83.27 | 47.01 | 36.26 | 82.93 | 77.17 | 0.00 | 0.00 | 0.00 |
December | 77.70 | 40.22 | 37.49 | 62.48 | 110.89 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 101.40 | 44.72 | 56.68 | 113.29 | 63.74 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 77.70 | 19.32 | 36.26 | 62.48 | 18.58 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 129.50 | 72.76 | 71.87 | 155.85 | 112.89 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.30 | 45.12 | 32.18 | 65.32 | 93.20 | 0.00 | 0.00 | 0.00 |
February | 88.26 | 42.56 | 45.70 | 73.89 | 90.25 | 0.00 | 0.00 | 0.00 |
March | 107.72 | 60.53 | 47.19 | 111.66 | 65.75 | 0.00 | 0.00 | 0.00 |
April | 89.21 | 35.65 | 53.56 | 97.45 | 50.68 | 0.00 | 0.00 | 0.00 |
May | 78.07 | 22.67 | 55.39 | 91.54 | 35.34 | 0.00 | 0.00 | 0.00 |
June | 75.86 | 16.07 | 59.78 | 97.39 | 24.24 | 0.00 | 0.00 | 0.00 |
July | 77.44 | 18.79 | 58.65 | 109.63 | 16.88 | 0.00 | 0.00 | 0.00 |
August | 86.94 | 28.19 | 58.75 | 120.66 | 22.10 | 0.00 | 0.00 | 0.00 |
September | 101.08 | 49.23 | 51.85 | 129.53 | 34.79 | 0.00 | 0.00 | 0.00 |
October | 96.72 | 55.25 | 41.47 | 109.28 | 49.99 | 0.00 | 0.00 | 0.00 |
November | 69.27 | 39.10 | 30.16 | 68.95 | 63.20 | 0.00 | 0.00 | 0.00 |
December | 64.64 | 33.45 | 31.18 | 51.69 | 91.63 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 84.35 | 37.20 | 47.15 | 94.03 | 52.97 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 64.64 | 16.07 | 30.16 | 51.69 | 16.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 107.72 | 60.53 | 59.78 | 129.53 | 93.20 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.30 | 45.12 | 32.18 | 65.32 | 93.20 | 0.00 | 0.00 | 0.00 |
February | 88.26 | 42.56 | 45.70 | 73.89 | 90.25 | 0.00 | 0.00 | 0.00 |
March | 107.72 | 60.53 | 47.19 | 111.66 | 65.75 | 0.00 | 0.00 | 0.00 |
April | 89.21 | 35.65 | 53.56 | 97.45 | 50.68 | 0.00 | 0.00 | 0.00 |
May | 78.07 | 22.67 | 55.39 | 91.54 | 35.34 | 0.00 | 0.00 | 0.00 |
June | 75.86 | 16.07 | 59.78 | 97.39 | 24.24 | 0.00 | 0.00 | 0.00 |
July | 77.44 | 18.79 | 58.65 | 109.63 | 16.88 | 0.00 | 0.00 | 0.00 |
August | 86.94 | 28.19 | 58.75 | 120.66 | 22.10 | 0.00 | 0.00 | 0.00 |
September | 101.08 | 49.23 | 51.85 | 129.53 | 34.79 | 0.00 | 0.00 | 0.00 |
October | 96.72 | 55.25 | 41.47 | 109.28 | 49.99 | 0.00 | 0.00 | 0.00 |
November | 69.27 | 39.10 | 30.16 | 68.95 | 63.20 | 0.00 | 0.00 | 0.00 |
December | 64.64 | 33.45 | 31.18 | 51.69 | 91.63 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 84.35 | 37.20 | 47.15 | 94.03 | 52.97 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 64.64 | 16.07 | 30.16 | 51.69 | 16.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 107.72 | 60.53 | 59.78 | 129.53 | 93.20 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_DOOR
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 92.42 | 53.95 | 38.47 | 78.64 | 109.80 | 0.00 | 0.00 | 0.00 |
February | 105.52 | 50.88 | 54.64 | 89.15 | 106.20 | 0.00 | 0.00 | 0.00 |
March | 128.79 | 72.37 | 56.42 | 134.14 | 77.62 | 0.00 | 0.00 | 0.00 |
April | 106.66 | 42.62 | 64.04 | 116.96 | 59.83 | 0.00 | 0.00 | 0.00 |
May | 93.34 | 27.11 | 66.23 | 109.74 | 41.83 | 0.00 | 0.00 | 0.00 |
June | 90.69 | 19.22 | 71.47 | 116.60 | 28.75 | 0.00 | 0.00 | 0.00 |
July | 92.58 | 22.46 | 70.12 | 131.08 | 20.05 | 0.00 | 0.00 | 0.00 |
August | 103.94 | 33.70 | 70.24 | 144.30 | 26.24 | 0.00 | 0.00 | 0.00 |
September | 120.85 | 58.86 | 61.99 | 155.02 | 41.25 | 0.00 | 0.00 | 0.00 |
October | 115.64 | 66.05 | 49.58 | 131.04 | 59.12 | 0.00 | 0.00 | 0.00 |
November | 82.82 | 46.75 | 36.06 | 82.82 | 74.57 | 0.00 | 0.00 | 0.00 |
December | 77.28 | 40.00 | 37.28 | 62.31 | 107.83 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 100.85 | 44.47 | 56.37 | 112.79 | 62.53 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 77.28 | 19.22 | 36.06 | 62.31 | 20.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 128.79 | 72.37 | 71.47 | 155.02 | 109.80 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.30 | 45.12 | 32.18 | 65.43 | 92.28 | 0.00 | 0.00 | 0.00 |
February | 88.26 | 42.56 | 45.70 | 74.03 | 89.38 | 0.00 | 0.00 | 0.00 |
March | 107.72 | 60.53 | 47.19 | 111.84 | 65.01 | 0.00 | 0.00 | 0.00 |
April | 89.21 | 35.65 | 53.56 | 97.70 | 49.88 | 0.00 | 0.00 | 0.00 |
May | 78.07 | 22.67 | 55.39 | 91.89 | 34.64 | 0.00 | 0.00 | 0.00 |
June | 75.86 | 16.07 | 59.78 | 97.45 | 24.13 | 0.00 | 0.00 | 0.00 |
July | 77.44 | 18.79 | 58.65 | 109.62 | 16.90 | 0.00 | 0.00 | 0.00 |
August | 86.94 | 28.19 | 58.75 | 120.66 | 22.11 | 0.00 | 0.00 | 0.00 |
September | 101.08 | 49.23 | 51.85 | 129.60 | 34.59 | 0.00 | 0.00 | 0.00 |
October | 96.72 | 55.25 | 41.47 | 109.55 | 49.19 | 0.00 | 0.00 | 0.00 |
November | 69.27 | 39.10 | 30.16 | 69.12 | 62.36 | 0.00 | 0.00 | 0.00 |
December | 64.64 | 33.45 | 31.18 | 51.79 | 90.72 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 84.35 | 37.20 | 47.15 | 94.17 | 52.41 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 64.64 | 16.07 | 30.16 | 51.79 | 16.90 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 107.72 | 60.53 | 59.78 | 129.60 | 92.28 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.30 | 45.12 | 32.18 | 65.43 | 92.28 | 0.00 | 0.00 | 0.00 |
February | 88.26 | 42.56 | 45.70 | 74.03 | 89.38 | 0.00 | 0.00 | 0.00 |
March | 107.72 | 60.53 | 47.19 | 111.84 | 65.01 | 0.00 | 0.00 | 0.00 |
April | 89.21 | 35.65 | 53.56 | 97.70 | 49.88 | 0.00 | 0.00 | 0.00 |
May | 78.07 | 22.67 | 55.39 | 91.89 | 34.64 | 0.00 | 0.00 | 0.00 |
June | 75.86 | 16.07 | 59.78 | 97.45 | 24.13 | 0.00 | 0.00 | 0.00 |
July | 77.44 | 18.79 | 58.65 | 109.62 | 16.90 | 0.00 | 0.00 | 0.00 |
August | 86.94 | 28.19 | 58.75 | 120.66 | 22.11 | 0.00 | 0.00 | 0.00 |
September | 101.08 | 49.23 | 51.85 | 129.60 | 34.59 | 0.00 | 0.00 | 0.00 |
October | 96.72 | 55.25 | 41.47 | 109.55 | 49.19 | 0.00 | 0.00 | 0.00 |
November | 69.27 | 39.10 | 30.16 | 69.12 | 62.36 | 0.00 | 0.00 | 0.00 |
December | 64.64 | 33.45 | 31.18 | 51.79 | 90.72 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 84.35 | 37.20 | 47.15 | 94.17 | 52.41 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 64.64 | 16.07 | 30.16 | 51.79 | 16.90 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 107.72 | 60.53 | 59.78 | 129.60 | 92.28 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_DOOR
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 92.42 | 53.95 | 38.47 | 78.78 | 108.70 | 0.00 | 0.00 | 0.00 |
February | 105.52 | 50.88 | 54.64 | 89.32 | 105.18 | 0.00 | 0.00 | 0.00 |
March | 128.79 | 72.37 | 56.42 | 134.36 | 76.74 | 0.00 | 0.00 | 0.00 |
April | 106.66 | 42.62 | 64.04 | 117.26 | 58.88 | 0.00 | 0.00 | 0.00 |
May | 93.34 | 27.11 | 66.23 | 110.16 | 41.00 | 0.00 | 0.00 | 0.00 |
June | 90.69 | 19.22 | 71.47 | 116.66 | 28.62 | 0.00 | 0.00 | 0.00 |
July | 92.58 | 22.46 | 70.12 | 131.07 | 20.08 | 0.00 | 0.00 | 0.00 |
August | 103.94 | 33.70 | 70.24 | 144.30 | 26.25 | 0.00 | 0.00 | 0.00 |
September | 120.85 | 58.86 | 61.99 | 155.10 | 41.02 | 0.00 | 0.00 | 0.00 |
October | 115.64 | 66.05 | 49.58 | 131.37 | 58.18 | 0.00 | 0.00 | 0.00 |
November | 82.82 | 46.75 | 36.06 | 83.02 | 73.58 | 0.00 | 0.00 | 0.00 |
December | 77.28 | 40.00 | 37.28 | 62.44 | 106.76 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 100.85 | 44.47 | 56.37 | 112.96 | 61.86 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 77.28 | 19.22 | 36.06 | 62.44 | 20.08 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 128.79 | 72.37 | 71.47 | 155.10 | 108.70 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.30 | 45.12 | 32.18 | 65.58 | 91.49 | 0.00 | 0.00 | 0.00 |
February | 88.26 | 42.56 | 45.70 | 74.22 | 88.64 | 0.00 | 0.00 | 0.00 |
March | 107.72 | 60.53 | 47.19 | 112.10 | 64.33 | 0.00 | 0.00 | 0.00 |
April | 89.21 | 35.65 | 53.56 | 98.03 | 49.14 | 0.00 | 0.00 | 0.00 |
May | 78.07 | 22.67 | 55.39 | 92.42 | 33.79 | 0.00 | 0.00 | 0.00 |
June | 75.86 | 16.07 | 59.78 | 97.64 | 23.80 | 0.00 | 0.00 | 0.00 |
July | 77.44 | 18.79 | 58.65 | 109.75 | 16.66 | 0.00 | 0.00 | 0.00 |
August | 86.94 | 28.19 | 58.75 | 120.77 | 21.85 | 0.00 | 0.00 | 0.00 |
September | 101.08 | 49.23 | 51.85 | 129.76 | 34.20 | 0.00 | 0.00 | 0.00 |
October | 96.72 | 55.25 | 41.47 | 109.89 | 48.44 | 0.00 | 0.00 | 0.00 |
November | 69.27 | 39.10 | 30.16 | 69.32 | 61.64 | 0.00 | 0.00 | 0.00 |
December | 64.64 | 33.45 | 31.18 | 51.93 | 89.92 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 84.35 | 37.20 | 47.15 | 94.40 | 51.80 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 64.64 | 16.07 | 30.16 | 51.93 | 16.66 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 107.72 | 60.53 | 59.78 | 129.76 | 91.49 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.30 | 45.12 | 32.18 | 65.58 | 91.49 | 0.00 | 0.00 | 0.00 |
February | 88.26 | 42.56 | 45.70 | 74.22 | 88.64 | 0.00 | 0.00 | 0.00 |
March | 107.72 | 60.53 | 47.19 | 112.10 | 64.33 | 0.00 | 0.00 | 0.00 |
April | 89.21 | 35.65 | 53.56 | 98.03 | 49.14 | 0.00 | 0.00 | 0.00 |
May | 78.07 | 22.67 | 55.39 | 92.42 | 33.79 | 0.00 | 0.00 | 0.00 |
June | 75.86 | 16.07 | 59.78 | 97.64 | 23.80 | 0.00 | 0.00 | 0.00 |
July | 77.44 | 18.79 | 58.65 | 109.75 | 16.66 | 0.00 | 0.00 | 0.00 |
August | 86.94 | 28.19 | 58.75 | 120.77 | 21.85 | 0.00 | 0.00 | 0.00 |
September | 101.08 | 49.23 | 51.85 | 129.76 | 34.20 | 0.00 | 0.00 | 0.00 |
October | 96.72 | 55.25 | 41.47 | 109.89 | 48.44 | 0.00 | 0.00 | 0.00 |
November | 69.27 | 39.10 | 30.16 | 69.32 | 61.64 | 0.00 | 0.00 | 0.00 |
December | 64.64 | 33.45 | 31.18 | 51.93 | 89.92 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 84.35 | 37.20 | 47.15 | 94.40 | 51.80 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 64.64 | 16.07 | 30.16 | 51.93 | 16.66 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 107.72 | 60.53 | 59.78 | 129.76 | 91.49 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_DOOR
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 92.42 | 53.95 | 38.47 | 78.96 | 107.76 | 0.00 | 0.00 | 0.00 |
February | 105.52 | 50.88 | 54.64 | 89.55 | 104.29 | 0.00 | 0.00 | 0.00 |
March | 128.79 | 72.37 | 56.42 | 134.67 | 75.93 | 0.00 | 0.00 | 0.00 |
April | 106.66 | 42.62 | 64.04 | 117.66 | 58.02 | 0.00 | 0.00 | 0.00 |
May | 93.34 | 27.11 | 66.23 | 110.79 | 40.00 | 0.00 | 0.00 | 0.00 |
June | 90.69 | 19.22 | 71.47 | 116.90 | 28.23 | 0.00 | 0.00 | 0.00 |
July | 92.58 | 22.46 | 70.12 | 131.22 | 19.80 | 0.00 | 0.00 | 0.00 |
August | 103.94 | 33.70 | 70.24 | 144.43 | 25.94 | 0.00 | 0.00 | 0.00 |
September | 120.85 | 58.86 | 61.99 | 155.30 | 40.56 | 0.00 | 0.00 | 0.00 |
October | 115.64 | 66.05 | 49.58 | 131.77 | 57.29 | 0.00 | 0.00 | 0.00 |
November | 82.82 | 46.75 | 36.06 | 83.27 | 72.73 | 0.00 | 0.00 | 0.00 |
December | 77.28 | 40.00 | 37.28 | 62.60 | 105.81 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 100.85 | 44.47 | 56.37 | 113.23 | 61.14 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 77.28 | 19.22 | 36.06 | 62.60 | 19.80 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 128.79 | 72.37 | 71.47 | 155.30 | 107.76 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.30 | 45.12 | 32.18 | 66.23 | 88.80 | 0.00 | 0.00 | 0.00 |
February | 88.26 | 42.56 | 45.70 | 75.13 | 86.01 | 0.00 | 0.00 | 0.00 |
March | 107.72 | 60.53 | 47.19 | 113.06 | 62.32 | 0.00 | 0.00 | 0.00 |
April | 89.21 | 35.65 | 53.56 | 98.85 | 47.32 | 0.00 | 0.00 | 0.00 |
May | 78.07 | 22.67 | 55.39 | 93.41 | 32.08 | 0.00 | 0.00 | 0.00 |
June | 75.86 | 16.07 | 59.78 | 97.95 | 22.90 | 0.00 | 0.00 | 0.00 |
July | 77.44 | 18.79 | 58.65 | 109.80 | 15.93 | 0.00 | 0.00 | 0.00 |
August | 86.94 | 28.19 | 58.75 | 120.82 | 21.05 | 0.00 | 0.00 | 0.00 |
September | 101.08 | 49.23 | 51.85 | 130.02 | 33.25 | 0.00 | 0.00 | 0.00 |
October | 96.72 | 55.25 | 41.47 | 110.61 | 46.88 | 0.00 | 0.00 | 0.00 |
November | 69.27 | 39.10 | 30.16 | 69.92 | 59.74 | 0.00 | 0.00 | 0.00 |
December | 64.64 | 33.45 | 31.18 | 52.51 | 87.23 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 84.35 | 37.20 | 47.15 | 94.97 | 50.10 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 64.64 | 16.07 | 30.16 | 52.51 | 15.93 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 107.72 | 60.53 | 59.78 | 130.02 | 88.80 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.30 | 45.12 | 32.18 | 66.23 | 88.80 | 0.00 | 0.00 | 0.00 |
February | 88.26 | 42.56 | 45.70 | 75.13 | 86.01 | 0.00 | 0.00 | 0.00 |
March | 107.72 | 60.53 | 47.19 | 113.06 | 62.32 | 0.00 | 0.00 | 0.00 |
April | 89.21 | 35.65 | 53.56 | 98.85 | 47.32 | 0.00 | 0.00 | 0.00 |
May | 78.07 | 22.67 | 55.39 | 93.41 | 32.08 | 0.00 | 0.00 | 0.00 |
June | 75.86 | 16.07 | 59.78 | 97.95 | 22.90 | 0.00 | 0.00 | 0.00 |
July | 77.44 | 18.79 | 58.65 | 109.80 | 15.93 | 0.00 | 0.00 | 0.00 |
August | 86.94 | 28.19 | 58.75 | 120.82 | 21.05 | 0.00 | 0.00 | 0.00 |
September | 101.08 | 49.23 | 51.85 | 130.02 | 33.25 | 0.00 | 0.00 | 0.00 |
October | 96.72 | 55.25 | 41.47 | 110.61 | 46.88 | 0.00 | 0.00 | 0.00 |
November | 69.27 | 39.10 | 30.16 | 69.92 | 59.74 | 0.00 | 0.00 | 0.00 |
December | 64.64 | 33.45 | 31.18 | 52.51 | 87.23 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 84.35 | 37.20 | 47.15 | 94.97 | 50.10 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 64.64 | 16.07 | 30.16 | 52.51 | 15.93 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 107.72 | 60.53 | 59.78 | 130.02 | 88.80 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.30 | 45.12 | 32.18 | 66.23 | 88.80 | 0.00 | 0.00 | 0.00 |
February | 88.26 | 42.56 | 45.70 | 75.13 | 86.01 | 0.00 | 0.00 | 0.00 |
March | 107.72 | 60.53 | 47.19 | 113.06 | 62.32 | 0.00 | 0.00 | 0.00 |
April | 89.21 | 35.65 | 53.56 | 98.85 | 47.32 | 0.00 | 0.00 | 0.00 |
May | 78.07 | 22.67 | 55.39 | 93.41 | 32.08 | 0.00 | 0.00 | 0.00 |
June | 75.86 | 16.07 | 59.78 | 97.95 | 22.90 | 0.00 | 0.00 | 0.00 |
July | 77.44 | 18.79 | 58.65 | 109.80 | 15.93 | 0.00 | 0.00 | 0.00 |
August | 86.94 | 28.19 | 58.75 | 120.82 | 21.05 | 0.00 | 0.00 | 0.00 |
September | 101.08 | 49.23 | 51.85 | 130.02 | 33.25 | 0.00 | 0.00 | 0.00 |
October | 96.72 | 55.25 | 41.47 | 110.61 | 46.88 | 0.00 | 0.00 | 0.00 |
November | 69.27 | 39.10 | 30.16 | 69.92 | 59.74 | 0.00 | 0.00 | 0.00 |
December | 64.64 | 33.45 | 31.18 | 52.51 | 87.23 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 84.35 | 37.20 | 47.15 | 94.97 | 50.10 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 64.64 | 16.07 | 30.16 | 52.51 | 15.93 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 107.72 | 60.53 | 59.78 | 130.02 | 88.80 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.30 | 45.12 | 32.18 | 66.23 | 88.80 | 0.00 | 0.00 | 0.00 |
February | 88.26 | 42.56 | 45.70 | 75.13 | 86.01 | 0.00 | 0.00 | 0.00 |
March | 107.72 | 60.53 | 47.19 | 113.06 | 62.32 | 0.00 | 0.00 | 0.00 |
April | 89.21 | 35.65 | 53.56 | 98.85 | 47.32 | 0.00 | 0.00 | 0.00 |
May | 78.07 | 22.67 | 55.39 | 93.41 | 32.08 | 0.00 | 0.00 | 0.00 |
June | 75.86 | 16.07 | 59.78 | 97.95 | 22.90 | 0.00 | 0.00 | 0.00 |
July | 77.44 | 18.79 | 58.65 | 109.80 | 15.93 | 0.00 | 0.00 | 0.00 |
August | 86.94 | 28.19 | 58.75 | 120.82 | 21.05 | 0.00 | 0.00 | 0.00 |
September | 101.08 | 49.23 | 51.85 | 130.02 | 33.25 | 0.00 | 0.00 | 0.00 |
October | 96.72 | 55.25 | 41.47 | 110.61 | 46.88 | 0.00 | 0.00 | 0.00 |
November | 69.27 | 39.10 | 30.16 | 69.92 | 59.74 | 0.00 | 0.00 | 0.00 |
December | 64.64 | 33.45 | 31.18 | 52.51 | 87.23 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 84.35 | 37.20 | 47.15 | 94.97 | 50.10 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 64.64 | 16.07 | 30.16 | 52.51 | 15.93 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 107.72 | 60.53 | 59.78 | 130.02 | 88.80 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 92.42 | 53.95 | 38.47 | 79.72 | 104.66 | 0.00 | 0.00 | 0.00 |
February | 105.52 | 50.88 | 54.64 | 90.61 | 101.27 | 0.00 | 0.00 | 0.00 |
March | 128.79 | 72.37 | 56.42 | 135.78 | 73.60 | 0.00 | 0.00 | 0.00 |
April | 106.66 | 42.62 | 64.04 | 118.60 | 55.90 | 0.00 | 0.00 | 0.00 |
May | 93.34 | 27.11 | 66.23 | 111.94 | 37.99 | 0.00 | 0.00 | 0.00 |
June | 90.69 | 19.22 | 71.47 | 117.24 | 27.18 | 0.00 | 0.00 | 0.00 |
July | 92.58 | 22.46 | 70.12 | 131.27 | 18.93 | 0.00 | 0.00 | 0.00 |
August | 103.94 | 33.70 | 70.24 | 144.47 | 25.00 | 0.00 | 0.00 | 0.00 |
September | 120.85 | 58.86 | 61.99 | 155.58 | 39.44 | 0.00 | 0.00 | 0.00 |
October | 115.64 | 66.05 | 49.58 | 132.59 | 55.47 | 0.00 | 0.00 | 0.00 |
November | 82.82 | 46.75 | 36.06 | 83.96 | 70.51 | 0.00 | 0.00 | 0.00 |
December | 77.28 | 40.00 | 37.28 | 63.29 | 102.70 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 100.85 | 44.47 | 56.37 | 113.89 | 59.17 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 77.28 | 19.22 | 36.06 | 63.29 | 18.93 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 128.79 | 72.37 | 71.47 | 155.58 | 104.66 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 92.42 | 53.95 | 38.47 | 79.72 | 104.66 | 0.00 | 0.00 | 0.00 |
February | 105.52 | 50.88 | 54.64 | 90.61 | 101.27 | 0.00 | 0.00 | 0.00 |
March | 128.79 | 72.37 | 56.42 | 135.78 | 73.60 | 0.00 | 0.00 | 0.00 |
April | 106.66 | 42.62 | 64.04 | 118.60 | 55.90 | 0.00 | 0.00 | 0.00 |
May | 93.34 | 27.11 | 66.23 | 111.94 | 37.99 | 0.00 | 0.00 | 0.00 |
June | 90.69 | 19.22 | 71.47 | 117.24 | 27.18 | 0.00 | 0.00 | 0.00 |
July | 92.58 | 22.46 | 70.12 | 131.27 | 18.93 | 0.00 | 0.00 | 0.00 |
August | 103.94 | 33.70 | 70.24 | 144.47 | 25.00 | 0.00 | 0.00 | 0.00 |
September | 120.85 | 58.86 | 61.99 | 155.58 | 39.44 | 0.00 | 0.00 | 0.00 |
October | 115.64 | 66.05 | 49.58 | 132.59 | 55.47 | 0.00 | 0.00 | 0.00 |
November | 82.82 | 46.75 | 36.06 | 83.96 | 70.51 | 0.00 | 0.00 | 0.00 |
December | 77.28 | 40.00 | 37.28 | 63.29 | 102.70 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 100.85 | 44.47 | 56.37 | 113.89 | 59.17 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 77.28 | 19.22 | 36.06 | 63.29 | 18.93 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 128.79 | 72.37 | 71.47 | 155.58 | 104.66 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.30 | 45.12 | 32.18 | 65.88 | 89.47 | 0.00 | 0.00 | 0.00 |
February | 88.26 | 42.56 | 45.70 | 74.65 | 86.70 | 0.00 | 0.00 | 0.00 |
March | 107.72 | 60.53 | 47.19 | 112.66 | 62.54 | 0.00 | 0.00 | 0.00 |
April | 89.21 | 35.65 | 53.56 | 98.62 | 47.34 | 0.00 | 0.00 | 0.00 |
May | 78.07 | 22.67 | 55.39 | 93.43 | 31.81 | 0.00 | 0.00 | 0.00 |
June | 75.86 | 16.07 | 59.78 | 97.92 | 22.71 | 0.00 | 0.00 | 0.00 |
July | 77.44 | 18.79 | 58.65 | 109.82 | 15.71 | 0.00 | 0.00 | 0.00 |
August | 86.94 | 28.19 | 58.75 | 120.78 | 20.84 | 0.00 | 0.00 | 0.00 |
September | 101.08 | 49.23 | 51.85 | 129.90 | 33.08 | 0.00 | 0.00 | 0.00 |
October | 96.72 | 55.25 | 41.47 | 110.44 | 46.77 | 0.00 | 0.00 | 0.00 |
November | 69.27 | 39.10 | 30.16 | 69.71 | 59.92 | 0.00 | 0.00 | 0.00 |
December | 64.64 | 33.45 | 31.18 | 52.20 | 87.91 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 84.35 | 37.20 | 47.15 | 94.78 | 50.21 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 64.64 | 16.07 | 30.16 | 52.20 | 15.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 107.72 | 60.53 | 59.78 | 129.90 | 89.47 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.30 | 45.12 | 32.18 | 65.88 | 89.47 | 0.00 | 0.00 | 0.00 |
February | 88.26 | 42.56 | 45.70 | 74.65 | 86.70 | 0.00 | 0.00 | 0.00 |
March | 107.72 | 60.53 | 47.19 | 112.66 | 62.54 | 0.00 | 0.00 | 0.00 |
April | 89.21 | 35.65 | 53.56 | 98.62 | 47.34 | 0.00 | 0.00 | 0.00 |
May | 78.07 | 22.67 | 55.39 | 93.43 | 31.81 | 0.00 | 0.00 | 0.00 |
June | 75.86 | 16.07 | 59.78 | 97.92 | 22.71 | 0.00 | 0.00 | 0.00 |
July | 77.44 | 18.79 | 58.65 | 109.82 | 15.71 | 0.00 | 0.00 | 0.00 |
August | 86.94 | 28.19 | 58.75 | 120.78 | 20.84 | 0.00 | 0.00 | 0.00 |
September | 101.08 | 49.23 | 51.85 | 129.90 | 33.08 | 0.00 | 0.00 | 0.00 |
October | 96.72 | 55.25 | 41.47 | 110.44 | 46.77 | 0.00 | 0.00 | 0.00 |
November | 69.27 | 39.10 | 30.16 | 69.71 | 59.92 | 0.00 | 0.00 | 0.00 |
December | 64.64 | 33.45 | 31.18 | 52.20 | 87.91 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 84.35 | 37.20 | 47.15 | 94.78 | 50.21 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 64.64 | 16.07 | 30.16 | 52.20 | 15.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 107.72 | 60.53 | 59.78 | 129.90 | 89.47 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_DOOR
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 92.42 | 53.95 | 38.47 | 79.33 | 105.39 | 0.00 | 0.00 | 0.00 |
February | 105.52 | 50.88 | 54.64 | 90.07 | 102.01 | 0.00 | 0.00 | 0.00 |
March | 128.79 | 72.37 | 56.42 | 135.35 | 73.83 | 0.00 | 0.00 | 0.00 |
April | 106.66 | 42.62 | 64.04 | 118.37 | 55.89 | 0.00 | 0.00 | 0.00 |
May | 93.34 | 27.11 | 66.23 | 111.99 | 37.66 | 0.00 | 0.00 | 0.00 |
June | 90.69 | 19.22 | 71.47 | 117.24 | 26.95 | 0.00 | 0.00 | 0.00 |
July | 92.58 | 22.46 | 70.12 | 131.32 | 18.68 | 0.00 | 0.00 | 0.00 |
August | 103.94 | 33.70 | 70.24 | 144.45 | 24.74 | 0.00 | 0.00 | 0.00 |
September | 120.85 | 58.86 | 61.99 | 155.47 | 39.24 | 0.00 | 0.00 | 0.00 |
October | 115.64 | 66.05 | 49.58 | 132.43 | 55.33 | 0.00 | 0.00 | 0.00 |
November | 82.82 | 46.75 | 36.06 | 83.74 | 70.69 | 0.00 | 0.00 | 0.00 |
December | 77.28 | 40.00 | 37.28 | 62.94 | 103.43 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 100.85 | 44.47 | 56.37 | 113.70 | 59.26 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 77.28 | 19.22 | 36.06 | 62.94 | 18.68 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 128.79 | 72.37 | 71.47 | 155.47 | 105.39 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.30 | 45.12 | 32.18 | 65.91 | 89.29 | 0.00 | 0.00 | 0.00 |
February | 88.26 | 42.56 | 45.70 | 74.69 | 86.53 | 0.00 | 0.00 | 0.00 |
March | 107.72 | 60.53 | 47.19 | 112.75 | 62.30 | 0.00 | 0.00 | 0.00 |
April | 89.21 | 35.65 | 53.56 | 98.75 | 47.04 | 0.00 | 0.00 | 0.00 |
May | 78.07 | 22.67 | 55.39 | 93.72 | 31.40 | 0.00 | 0.00 | 0.00 |
June | 75.86 | 16.07 | 59.78 | 98.08 | 22.52 | 0.00 | 0.00 | 0.00 |
July | 77.44 | 18.79 | 58.65 | 109.89 | 15.62 | 0.00 | 0.00 | 0.00 |
August | 86.94 | 28.19 | 58.75 | 120.85 | 20.73 | 0.00 | 0.00 | 0.00 |
September | 101.08 | 49.23 | 51.85 | 130.00 | 32.90 | 0.00 | 0.00 | 0.00 |
October | 96.72 | 55.25 | 41.47 | 110.58 | 46.48 | 0.00 | 0.00 | 0.00 |
November | 69.27 | 39.10 | 30.16 | 69.78 | 59.67 | 0.00 | 0.00 | 0.00 |
December | 64.64 | 33.45 | 31.18 | 52.23 | 87.71 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 84.35 | 37.20 | 47.15 | 94.89 | 49.99 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 64.64 | 16.07 | 30.16 | 52.23 | 15.62 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 107.72 | 60.53 | 59.78 | 130.00 | 89.29 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.30 | 45.12 | 32.18 | 65.91 | 89.29 | 0.00 | 0.00 | 0.00 |
February | 88.26 | 42.56 | 45.70 | 74.69 | 86.53 | 0.00 | 0.00 | 0.00 |
March | 107.72 | 60.53 | 47.19 | 112.75 | 62.30 | 0.00 | 0.00 | 0.00 |
April | 89.21 | 35.65 | 53.56 | 98.75 | 47.04 | 0.00 | 0.00 | 0.00 |
May | 78.07 | 22.67 | 55.39 | 93.72 | 31.40 | 0.00 | 0.00 | 0.00 |
June | 75.86 | 16.07 | 59.78 | 98.08 | 22.52 | 0.00 | 0.00 | 0.00 |
July | 77.44 | 18.79 | 58.65 | 109.89 | 15.62 | 0.00 | 0.00 | 0.00 |
August | 86.94 | 28.19 | 58.75 | 120.85 | 20.73 | 0.00 | 0.00 | 0.00 |
September | 101.08 | 49.23 | 51.85 | 130.00 | 32.90 | 0.00 | 0.00 | 0.00 |
October | 96.72 | 55.25 | 41.47 | 110.58 | 46.48 | 0.00 | 0.00 | 0.00 |
November | 69.27 | 39.10 | 30.16 | 69.78 | 59.67 | 0.00 | 0.00 | 0.00 |
December | 64.64 | 33.45 | 31.18 | 52.23 | 87.71 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 84.35 | 37.20 | 47.15 | 94.89 | 49.99 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 64.64 | 16.07 | 30.16 | 52.23 | 15.62 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 107.72 | 60.53 | 59.78 | 130.00 | 89.29 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_DOOR
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 92.42 | 53.95 | 38.47 | 79.37 | 105.17 | 0.00 | 0.00 | 0.00 |
February | 105.52 | 50.88 | 54.64 | 90.13 | 101.82 | 0.00 | 0.00 | 0.00 |
March | 128.79 | 72.37 | 56.42 | 135.46 | 73.54 | 0.00 | 0.00 | 0.00 |
April | 106.66 | 42.62 | 64.04 | 118.53 | 55.54 | 0.00 | 0.00 | 0.00 |
May | 93.34 | 27.11 | 66.23 | 112.35 | 37.18 | 0.00 | 0.00 | 0.00 |
June | 90.69 | 19.22 | 71.47 | 117.42 | 26.73 | 0.00 | 0.00 | 0.00 |
July | 92.58 | 22.46 | 70.12 | 131.41 | 18.57 | 0.00 | 0.00 | 0.00 |
August | 103.94 | 33.70 | 70.24 | 144.53 | 24.62 | 0.00 | 0.00 | 0.00 |
September | 120.85 | 58.86 | 61.99 | 155.59 | 39.02 | 0.00 | 0.00 | 0.00 |
October | 115.64 | 66.05 | 49.58 | 132.59 | 54.98 | 0.00 | 0.00 | 0.00 |
November | 82.82 | 46.75 | 36.06 | 83.82 | 70.40 | 0.00 | 0.00 | 0.00 |
December | 77.28 | 40.00 | 37.28 | 62.98 | 103.20 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 100.85 | 44.47 | 56.37 | 113.82 | 59.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 77.28 | 19.22 | 36.06 | 62.98 | 18.57 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 128.79 | 72.37 | 71.47 | 155.59 | 105.17 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.30 | 45.12 | 32.18 | 66.08 | 88.24 | 0.00 | 0.00 | 0.00 |
February | 88.26 | 42.56 | 45.70 | 74.90 | 85.59 | 0.00 | 0.00 | 0.00 |
March | 107.72 | 60.53 | 47.19 | 113.07 | 61.26 | 0.00 | 0.00 | 0.00 |
April | 89.21 | 35.65 | 53.56 | 99.13 | 46.01 | 0.00 | 0.00 | 0.00 |
May | 78.07 | 22.67 | 55.39 | 94.40 | 30.38 | 0.00 | 0.00 | 0.00 |
June | 75.86 | 16.07 | 59.78 | 98.46 | 22.01 | 0.00 | 0.00 | 0.00 |
July | 77.44 | 18.79 | 58.65 | 110.03 | 15.38 | 0.00 | 0.00 | 0.00 |
August | 86.94 | 28.19 | 58.75 | 120.97 | 20.48 | 0.00 | 0.00 | 0.00 |
September | 101.08 | 49.23 | 51.85 | 130.25 | 32.38 | 0.00 | 0.00 | 0.00 |
October | 96.72 | 55.25 | 41.47 | 110.90 | 45.70 | 0.00 | 0.00 | 0.00 |
November | 69.27 | 39.10 | 30.16 | 70.00 | 58.78 | 0.00 | 0.00 | 0.00 |
December | 64.64 | 33.45 | 31.18 | 52.38 | 86.69 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 84.35 | 37.20 | 47.15 | 95.16 | 49.22 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 64.64 | 16.07 | 30.16 | 52.38 | 15.38 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 107.72 | 60.53 | 59.78 | 130.25 | 88.24 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.30 | 45.12 | 32.18 | 66.08 | 88.24 | 0.00 | 0.00 | 0.00 |
February | 88.26 | 42.56 | 45.70 | 74.90 | 85.59 | 0.00 | 0.00 | 0.00 |
March | 107.72 | 60.53 | 47.19 | 113.07 | 61.26 | 0.00 | 0.00 | 0.00 |
April | 89.21 | 35.65 | 53.56 | 99.13 | 46.01 | 0.00 | 0.00 | 0.00 |
May | 78.07 | 22.67 | 55.39 | 94.40 | 30.38 | 0.00 | 0.00 | 0.00 |
June | 75.86 | 16.07 | 59.78 | 98.46 | 22.01 | 0.00 | 0.00 | 0.00 |
July | 77.44 | 18.79 | 58.65 | 110.03 | 15.38 | 0.00 | 0.00 | 0.00 |
August | 86.94 | 28.19 | 58.75 | 120.97 | 20.48 | 0.00 | 0.00 | 0.00 |
September | 101.08 | 49.23 | 51.85 | 130.25 | 32.38 | 0.00 | 0.00 | 0.00 |
October | 96.72 | 55.25 | 41.47 | 110.90 | 45.70 | 0.00 | 0.00 | 0.00 |
November | 69.27 | 39.10 | 30.16 | 70.00 | 58.78 | 0.00 | 0.00 | 0.00 |
December | 64.64 | 33.45 | 31.18 | 52.38 | 86.69 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 84.35 | 37.20 | 47.15 | 95.16 | 49.22 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 64.64 | 16.07 | 30.16 | 52.38 | 15.38 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 107.72 | 60.53 | 59.78 | 130.25 | 88.24 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_DOOR
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 92.42 | 53.95 | 38.47 | 79.58 | 103.93 | 0.00 | 0.00 | 0.00 |
February | 105.52 | 50.88 | 54.64 | 90.38 | 100.70 | 0.00 | 0.00 | 0.00 |
March | 128.79 | 72.37 | 56.42 | 135.85 | 72.31 | 0.00 | 0.00 | 0.00 |
April | 106.66 | 42.62 | 64.04 | 118.99 | 54.32 | 0.00 | 0.00 | 0.00 |
May | 93.34 | 27.11 | 66.23 | 113.15 | 35.97 | 0.00 | 0.00 | 0.00 |
June | 90.69 | 19.22 | 71.47 | 117.89 | 26.12 | 0.00 | 0.00 | 0.00 |
July | 92.58 | 22.46 | 70.12 | 131.57 | 18.29 | 0.00 | 0.00 | 0.00 |
August | 103.94 | 33.70 | 70.24 | 144.67 | 24.33 | 0.00 | 0.00 | 0.00 |
September | 120.85 | 58.86 | 61.99 | 155.89 | 38.41 | 0.00 | 0.00 | 0.00 |
October | 115.64 | 66.05 | 49.58 | 132.97 | 54.05 | 0.00 | 0.00 | 0.00 |
November | 82.82 | 46.75 | 36.06 | 84.09 | 69.34 | 0.00 | 0.00 | 0.00 |
December | 77.28 | 40.00 | 37.28 | 63.16 | 102.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 100.85 | 44.47 | 56.37 | 114.15 | 58.09 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 77.28 | 19.22 | 36.06 | 63.16 | 18.29 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 128.79 | 72.37 | 71.47 | 155.89 | 103.93 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.30 | 45.12 | 32.18 | 66.84 | 83.63 | 0.00 | 0.00 | 0.00 |
February | 88.26 | 42.56 | 45.70 | 75.82 | 81.23 | 0.00 | 0.00 | 0.00 |
March | 107.72 | 60.53 | 47.19 | 114.23 | 56.95 | 0.00 | 0.00 | 0.00 |
April | 89.21 | 35.65 | 53.56 | 100.25 | 42.10 | 0.00 | 0.00 | 0.00 |
May | 78.07 | 22.67 | 55.39 | 95.84 | 27.34 | 0.00 | 0.00 | 0.00 |
June | 75.86 | 16.07 | 59.78 | 99.40 | 20.23 | 0.00 | 0.00 | 0.00 |
July | 77.44 | 18.79 | 58.65 | 110.28 | 14.48 | 0.00 | 0.00 | 0.00 |
August | 86.94 | 28.19 | 58.75 | 121.17 | 19.53 | 0.00 | 0.00 | 0.00 |
September | 101.08 | 49.23 | 51.85 | 130.79 | 30.67 | 0.00 | 0.00 | 0.00 |
October | 96.72 | 55.25 | 41.47 | 111.61 | 43.19 | 0.00 | 0.00 | 0.00 |
November | 69.27 | 39.10 | 30.16 | 70.69 | 55.42 | 0.00 | 0.00 | 0.00 |
December | 64.64 | 33.45 | 31.18 | 53.02 | 82.18 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 84.35 | 37.20 | 47.15 | 95.94 | 46.23 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 64.64 | 16.07 | 30.16 | 53.02 | 14.48 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 107.72 | 60.53 | 59.78 | 130.79 | 83.63 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.30 | 45.12 | 32.18 | 66.84 | 83.63 | 0.00 | 0.00 | 0.00 |
February | 88.26 | 42.56 | 45.70 | 75.82 | 81.23 | 0.00 | 0.00 | 0.00 |
March | 107.72 | 60.53 | 47.19 | 114.23 | 56.95 | 0.00 | 0.00 | 0.00 |
April | 89.21 | 35.65 | 53.56 | 100.25 | 42.10 | 0.00 | 0.00 | 0.00 |
May | 78.07 | 22.67 | 55.39 | 95.84 | 27.34 | 0.00 | 0.00 | 0.00 |
June | 75.86 | 16.07 | 59.78 | 99.40 | 20.23 | 0.00 | 0.00 | 0.00 |
July | 77.44 | 18.79 | 58.65 | 110.28 | 14.48 | 0.00 | 0.00 | 0.00 |
August | 86.94 | 28.19 | 58.75 | 121.17 | 19.53 | 0.00 | 0.00 | 0.00 |
September | 101.08 | 49.23 | 51.85 | 130.79 | 30.67 | 0.00 | 0.00 | 0.00 |
October | 96.72 | 55.25 | 41.47 | 111.61 | 43.19 | 0.00 | 0.00 | 0.00 |
November | 69.27 | 39.10 | 30.16 | 70.69 | 55.42 | 0.00 | 0.00 | 0.00 |
December | 64.64 | 33.45 | 31.18 | 53.02 | 82.18 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 84.35 | 37.20 | 47.15 | 95.94 | 46.23 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 64.64 | 16.07 | 30.16 | 53.02 | 14.48 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 107.72 | 60.53 | 59.78 | 130.79 | 83.63 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_DOOR
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 92.42 | 53.95 | 38.47 | 80.51 | 98.48 | 0.00 | 0.00 | 0.00 |
February | 105.52 | 50.88 | 54.64 | 91.50 | 95.56 | 0.00 | 0.00 | 0.00 |
March | 128.79 | 72.37 | 56.42 | 137.26 | 67.23 | 0.00 | 0.00 | 0.00 |
April | 106.66 | 42.62 | 64.04 | 120.34 | 49.72 | 0.00 | 0.00 | 0.00 |
May | 93.34 | 27.11 | 66.23 | 114.88 | 32.40 | 0.00 | 0.00 | 0.00 |
June | 90.69 | 19.22 | 71.47 | 119.00 | 24.04 | 0.00 | 0.00 | 0.00 |
July | 92.58 | 22.46 | 70.12 | 131.87 | 17.23 | 0.00 | 0.00 | 0.00 |
August | 103.94 | 33.70 | 70.24 | 144.91 | 23.21 | 0.00 | 0.00 | 0.00 |
September | 120.85 | 58.86 | 61.99 | 156.53 | 36.39 | 0.00 | 0.00 | 0.00 |
October | 115.64 | 66.05 | 49.58 | 133.83 | 51.10 | 0.00 | 0.00 | 0.00 |
November | 82.82 | 46.75 | 36.06 | 84.93 | 65.39 | 0.00 | 0.00 | 0.00 |
December | 77.28 | 40.00 | 37.28 | 63.94 | 96.68 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 100.85 | 44.47 | 56.37 | 115.09 | 54.57 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 77.28 | 19.22 | 36.06 | 63.94 | 17.23 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 128.79 | 72.37 | 71.47 | 156.53 | 98.48 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.207038E+09 | 0.120854E+09 | 86183627.08 | 0.177225E+09 | 0.244213E+09 |
February | 0.213509E+09 | 0.102952E+09 | 0.110557E+09 | 0.181588E+09 | 0.213368E+09 |
March | 0.288524E+09 | 0.162120E+09 | 0.126404E+09 | 0.302679E+09 | 0.170207E+09 |
April | 0.231235E+09 | 92402253.73 | 0.138833E+09 | 0.255899E+09 | 0.125166E+09 |
May | 0.209096E+09 | 60730378.17 | 0.148366E+09 | 0.249232E+09 | 88274913.87 |
June | 0.196620E+09 | 41664801.23 | 0.154955E+09 | 0.254650E+09 | 58377206.57 |
July | 0.207408E+09 | 50323949.97 | 0.157084E+09 | 0.295479E+09 | 40749725.77 |
August | 0.232850E+09 | 75495666.65 | 0.157354E+09 | 0.324480E+09 | 54663292.58 |
September | 0.262001E+09 | 0.127614E+09 | 0.134387E+09 | 0.337238E+09 | 85656691.39 |
October | 0.259053E+09 | 0.147976E+09 | 0.111077E+09 | 0.294983E+09 | 0.128927E+09 |
November | 0.179544E+09 | 0.101358E+09 | 78185238.26 | 0.180447E+09 | 0.158824E+09 |
December | 0.173125E+09 | 89599800.50 | 83524723.31 | 0.140354E+09 | 0.239660E+09 |
Annual Sum or Average | 0.266000E+10 | 0.117309E+10 | 0.148691E+10 | 0.299426E+10 | 0.160809E+10 |
Minimum of Months | 0.173125E+09 | 41664801.23 | 78185238.26 | 0.140354E+09 | 40749725.77 |
Maximum of Months | 0.288524E+09 | 0.162120E+09 | 0.157354E+09 | 0.337238E+09 | 0.244213E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.207038E+09 | 0.120854E+09 | 86183627.08 | 0.177225E+09 | 0.244213E+09 |
February | 0.213509E+09 | 0.102952E+09 | 0.110557E+09 | 0.181588E+09 | 0.213368E+09 |
March | 0.288524E+09 | 0.162120E+09 | 0.126404E+09 | 0.302679E+09 | 0.170207E+09 |
April | 0.231235E+09 | 92402253.73 | 0.138833E+09 | 0.255899E+09 | 0.125166E+09 |
May | 0.209096E+09 | 60730378.17 | 0.148366E+09 | 0.249232E+09 | 88274913.87 |
June | 0.196620E+09 | 41664801.23 | 0.154955E+09 | 0.254650E+09 | 58377206.57 |
July | 0.207408E+09 | 50323949.97 | 0.157084E+09 | 0.295479E+09 | 40749725.77 |
August | 0.232850E+09 | 75495666.65 | 0.157354E+09 | 0.324480E+09 | 54663292.58 |
September | 0.262001E+09 | 0.127614E+09 | 0.134387E+09 | 0.337238E+09 | 85656691.39 |
October | 0.259053E+09 | 0.147976E+09 | 0.111077E+09 | 0.294983E+09 | 0.128927E+09 |
November | 0.179544E+09 | 0.101358E+09 | 78185238.26 | 0.180447E+09 | 0.158824E+09 |
December | 0.173125E+09 | 89599800.50 | 83524723.31 | 0.140354E+09 | 0.239660E+09 |
Annual Sum or Average | 0.266000E+10 | 0.117309E+10 | 0.148691E+10 | 0.299426E+10 | 0.160809E+10 |
Minimum of Months | 0.173125E+09 | 41664801.23 | 78185238.26 | 0.140354E+09 | 40749725.77 |
Maximum of Months | 0.288524E+09 | 0.162120E+09 | 0.157354E+09 | 0.337238E+09 | 0.244213E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.207038E+09 | 0.120854E+09 | 86183627.08 | 0.177225E+09 | 0.244213E+09 |
February | 0.213509E+09 | 0.102952E+09 | 0.110557E+09 | 0.181588E+09 | 0.213368E+09 |
March | 0.288524E+09 | 0.162120E+09 | 0.126404E+09 | 0.302679E+09 | 0.170207E+09 |
April | 0.231235E+09 | 92402253.73 | 0.138833E+09 | 0.255899E+09 | 0.125166E+09 |
May | 0.209096E+09 | 60730378.17 | 0.148366E+09 | 0.249232E+09 | 88274913.87 |
June | 0.196620E+09 | 41664801.23 | 0.154955E+09 | 0.254650E+09 | 58377206.57 |
July | 0.207408E+09 | 50323949.97 | 0.157084E+09 | 0.295479E+09 | 40749725.77 |
August | 0.232850E+09 | 75495666.65 | 0.157354E+09 | 0.324480E+09 | 54663292.58 |
September | 0.262001E+09 | 0.127614E+09 | 0.134387E+09 | 0.337238E+09 | 85656691.39 |
October | 0.259053E+09 | 0.147976E+09 | 0.111077E+09 | 0.294983E+09 | 0.128927E+09 |
November | 0.179544E+09 | 0.101358E+09 | 78185238.26 | 0.180447E+09 | 0.158824E+09 |
December | 0.173125E+09 | 89599800.50 | 83524723.31 | 0.140354E+09 | 0.239660E+09 |
Annual Sum or Average | 0.266000E+10 | 0.117309E+10 | 0.148691E+10 | 0.299426E+10 | 0.160809E+10 |
Minimum of Months | 0.173125E+09 | 41664801.23 | 78185238.26 | 0.140354E+09 | 40749725.77 |
Maximum of Months | 0.288524E+09 | 0.162120E+09 | 0.157354E+09 | 0.337238E+09 | 0.244213E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.207038E+09 | 0.120854E+09 | 86183627.08 | 0.177225E+09 | 0.244213E+09 |
February | 0.213509E+09 | 0.102952E+09 | 0.110557E+09 | 0.181588E+09 | 0.213368E+09 |
March | 0.288524E+09 | 0.162120E+09 | 0.126404E+09 | 0.302679E+09 | 0.170207E+09 |
April | 0.231235E+09 | 92402253.73 | 0.138833E+09 | 0.255899E+09 | 0.125166E+09 |
May | 0.209096E+09 | 60730378.17 | 0.148366E+09 | 0.249232E+09 | 88274913.87 |
June | 0.196620E+09 | 41664801.23 | 0.154955E+09 | 0.254650E+09 | 58377206.57 |
July | 0.207408E+09 | 50323949.97 | 0.157084E+09 | 0.295479E+09 | 40749725.77 |
August | 0.232850E+09 | 75495666.65 | 0.157354E+09 | 0.324480E+09 | 54663292.58 |
September | 0.262001E+09 | 0.127614E+09 | 0.134387E+09 | 0.337238E+09 | 85656691.39 |
October | 0.259053E+09 | 0.147976E+09 | 0.111077E+09 | 0.294983E+09 | 0.128927E+09 |
November | 0.179544E+09 | 0.101358E+09 | 78185238.26 | 0.180447E+09 | 0.158824E+09 |
December | 0.173125E+09 | 89599800.50 | 83524723.31 | 0.140354E+09 | 0.239660E+09 |
Annual Sum or Average | 0.266000E+10 | 0.117309E+10 | 0.148691E+10 | 0.299426E+10 | 0.160809E+10 |
Minimum of Months | 0.173125E+09 | 41664801.23 | 78185238.26 | 0.140354E+09 | 40749725.77 |
Maximum of Months | 0.288524E+09 | 0.162120E+09 | 0.157354E+09 | 0.337238E+09 | 0.244213E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.248891E+09 | 0.145285E+09 | 0.103606E+09 | 0.214466E+09 | 0.289355E+09 |
February | 0.256671E+09 | 0.123764E+09 | 0.132906E+09 | 0.220179E+09 | 0.252531E+09 |
March | 0.346850E+09 | 0.194893E+09 | 0.151957E+09 | 0.365492E+09 | 0.202099E+09 |
April | 0.277980E+09 | 0.111082E+09 | 0.166898E+09 | 0.308722E+09 | 0.148666E+09 |
May | 0.251366E+09 | 73007264.06 | 0.178359E+09 | 0.300324E+09 | 0.105123E+09 |
June | 0.236368E+09 | 50087505.41 | 0.186280E+09 | 0.306461E+09 | 69705899.10 |
July | 0.249336E+09 | 60497135.29 | 0.188839E+09 | 0.355156E+09 | 48763765.77 |
August | 0.279921E+09 | 90757413.95 | 0.189164E+09 | 0.390092E+09 | 65339544.79 |
September | 0.314966E+09 | 0.153412E+09 | 0.161554E+09 | 0.405735E+09 | 0.102217E+09 |
October | 0.311422E+09 | 0.177890E+09 | 0.133532E+09 | 0.355548E+09 | 0.153417E+09 |
November | 0.215839E+09 | 0.121848E+09 | 93990693.08 | 0.217866E+09 | 0.188513E+09 |
December | 0.208122E+09 | 0.107713E+09 | 0.100410E+09 | 0.170068E+09 | 0.283682E+09 |
Annual Sum or Average | 0.319773E+10 | 0.141024E+10 | 0.178750E+10 | 0.361011E+10 | 0.190941E+10 |
Minimum of Months | 0.208122E+09 | 50087505.41 | 93990693.08 | 0.170068E+09 | 48763765.77 |
Maximum of Months | 0.346850E+09 | 0.194893E+09 | 0.189164E+09 | 0.405735E+09 | 0.289355E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.248891E+09 | 0.145285E+09 | 0.103606E+09 | 0.214466E+09 | 0.289355E+09 |
February | 0.256671E+09 | 0.123764E+09 | 0.132906E+09 | 0.220179E+09 | 0.252531E+09 |
March | 0.346850E+09 | 0.194893E+09 | 0.151957E+09 | 0.365492E+09 | 0.202099E+09 |
April | 0.277980E+09 | 0.111082E+09 | 0.166898E+09 | 0.308722E+09 | 0.148666E+09 |
May | 0.251366E+09 | 73007264.06 | 0.178359E+09 | 0.300324E+09 | 0.105123E+09 |
June | 0.236368E+09 | 50087505.41 | 0.186280E+09 | 0.306461E+09 | 69705899.10 |
July | 0.249336E+09 | 60497135.29 | 0.188839E+09 | 0.355156E+09 | 48763765.77 |
August | 0.279921E+09 | 90757413.95 | 0.189164E+09 | 0.390092E+09 | 65339544.79 |
September | 0.314966E+09 | 0.153412E+09 | 0.161554E+09 | 0.405735E+09 | 0.102217E+09 |
October | 0.311422E+09 | 0.177890E+09 | 0.133532E+09 | 0.355548E+09 | 0.153417E+09 |
November | 0.215839E+09 | 0.121848E+09 | 93990693.08 | 0.217866E+09 | 0.188513E+09 |
December | 0.208122E+09 | 0.107713E+09 | 0.100410E+09 | 0.170068E+09 | 0.283682E+09 |
Annual Sum or Average | 0.319773E+10 | 0.141024E+10 | 0.178750E+10 | 0.361011E+10 | 0.190941E+10 |
Minimum of Months | 0.208122E+09 | 50087505.41 | 93990693.08 | 0.170068E+09 | 48763765.77 |
Maximum of Months | 0.346850E+09 | 0.194893E+09 | 0.189164E+09 | 0.405735E+09 | 0.289355E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.207038E+09 | 0.120854E+09 | 86183627.08 | 0.174540E+09 | 0.255296E+09 |
February | 0.213509E+09 | 0.102952E+09 | 0.110557E+09 | 0.178373E+09 | 0.223365E+09 |
March | 0.288524E+09 | 0.162120E+09 | 0.126404E+09 | 0.298588E+09 | 0.180418E+09 |
April | 0.231235E+09 | 92402253.73 | 0.138833E+09 | 0.251723E+09 | 0.135519E+09 |
May | 0.209096E+09 | 60730378.17 | 0.148366E+09 | 0.244279E+09 | 96214957.61 |
June | 0.196620E+09 | 41664801.23 | 0.154955E+09 | 0.252872E+09 | 60398566.90 |
July | 0.207408E+09 | 50323949.97 | 0.157084E+09 | 0.294808E+09 | 41599850.40 |
August | 0.232850E+09 | 75495666.65 | 0.157354E+09 | 0.323855E+09 | 55607791.69 |
September | 0.262001E+09 | 0.127614E+09 | 0.134387E+09 | 0.335704E+09 | 88236240.16 |
October | 0.259053E+09 | 0.147976E+09 | 0.111077E+09 | 0.291637E+09 | 0.137575E+09 |
November | 0.179544E+09 | 0.101358E+09 | 78185238.26 | 0.177989E+09 | 0.168653E+09 |
December | 0.173125E+09 | 89599800.50 | 83524723.31 | 0.138052E+09 | 0.251035E+09 |
Annual Sum or Average | 0.266000E+10 | 0.117309E+10 | 0.148691E+10 | 0.296242E+10 | 0.169392E+10 |
Minimum of Months | 0.173125E+09 | 41664801.23 | 78185238.26 | 0.138052E+09 | 41599850.40 |
Maximum of Months | 0.288524E+09 | 0.162120E+09 | 0.157354E+09 | 0.335704E+09 | 0.255296E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.207038E+09 | 0.120854E+09 | 86183627.08 | 0.174540E+09 | 0.255296E+09 |
February | 0.213509E+09 | 0.102952E+09 | 0.110557E+09 | 0.178373E+09 | 0.223365E+09 |
March | 0.288524E+09 | 0.162120E+09 | 0.126404E+09 | 0.298588E+09 | 0.180418E+09 |
April | 0.231235E+09 | 92402253.73 | 0.138833E+09 | 0.251723E+09 | 0.135519E+09 |
May | 0.209096E+09 | 60730378.17 | 0.148366E+09 | 0.244279E+09 | 96214957.61 |
June | 0.196620E+09 | 41664801.23 | 0.154955E+09 | 0.252872E+09 | 60398566.90 |
July | 0.207408E+09 | 50323949.97 | 0.157084E+09 | 0.294808E+09 | 41599850.40 |
August | 0.232850E+09 | 75495666.65 | 0.157354E+09 | 0.323855E+09 | 55607791.69 |
September | 0.262001E+09 | 0.127614E+09 | 0.134387E+09 | 0.335704E+09 | 88236240.16 |
October | 0.259053E+09 | 0.147976E+09 | 0.111077E+09 | 0.291637E+09 | 0.137575E+09 |
November | 0.179544E+09 | 0.101358E+09 | 78185238.26 | 0.177989E+09 | 0.168653E+09 |
December | 0.173125E+09 | 89599800.50 | 83524723.31 | 0.138052E+09 | 0.251035E+09 |
Annual Sum or Average | 0.266000E+10 | 0.117309E+10 | 0.148691E+10 | 0.296242E+10 | 0.169392E+10 |
Minimum of Months | 0.173125E+09 | 41664801.23 | 78185238.26 | 0.138052E+09 | 41599850.40 |
Maximum of Months | 0.288524E+09 | 0.162120E+09 | 0.157354E+09 | 0.335704E+09 | 0.255296E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_DOOR
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.248891E+09 | 0.145285E+09 | 0.103606E+09 | 0.211278E+09 | 0.302365E+09 |
February | 0.256671E+09 | 0.123764E+09 | 0.132906E+09 | 0.216391E+09 | 0.264252E+09 |
March | 0.346850E+09 | 0.194893E+09 | 0.151957E+09 | 0.360669E+09 | 0.214090E+09 |
April | 0.277980E+09 | 0.111082E+09 | 0.166898E+09 | 0.303789E+09 | 0.160816E+09 |
May | 0.251366E+09 | 73007264.06 | 0.178359E+09 | 0.294470E+09 | 0.114466E+09 |
June | 0.236368E+09 | 50087505.41 | 0.186280E+09 | 0.304388E+09 | 72086903.60 |
July | 0.249336E+09 | 60497135.29 | 0.188839E+09 | 0.354400E+09 | 49768517.39 |
August | 0.279921E+09 | 90757413.95 | 0.189164E+09 | 0.389400E+09 | 66450212.84 |
September | 0.314966E+09 | 0.153412E+09 | 0.161554E+09 | 0.403971E+09 | 0.105250E+09 |
October | 0.311422E+09 | 0.177890E+09 | 0.133532E+09 | 0.351631E+09 | 0.163549E+09 |
November | 0.215839E+09 | 0.121848E+09 | 93990693.08 | 0.214958E+09 | 0.200014E+09 |
December | 0.208122E+09 | 0.107713E+09 | 0.100410E+09 | 0.167337E+09 | 0.297010E+09 |
Annual Sum or Average | 0.319773E+10 | 0.141024E+10 | 0.178750E+10 | 0.357268E+10 | 0.201012E+10 |
Minimum of Months | 0.208122E+09 | 50087505.41 | 93990693.08 | 0.167337E+09 | 49768517.39 |
Maximum of Months | 0.346850E+09 | 0.194893E+09 | 0.189164E+09 | 0.403971E+09 | 0.302365E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.207038E+09 | 0.120854E+09 | 86183627.08 | 0.174942E+09 | 0.249640E+09 |
February | 0.213509E+09 | 0.102952E+09 | 0.110557E+09 | 0.178754E+09 | 0.218328E+09 |
March | 0.288524E+09 | 0.162120E+09 | 0.126404E+09 | 0.299078E+09 | 0.176113E+09 |
April | 0.231235E+09 | 92402253.73 | 0.138833E+09 | 0.252587E+09 | 0.131358E+09 |
May | 0.209096E+09 | 60730378.17 | 0.148366E+09 | 0.245185E+09 | 94667621.30 |
June | 0.196620E+09 | 41664801.23 | 0.154955E+09 | 0.252438E+09 | 62817149.47 |
July | 0.207408E+09 | 50323949.97 | 0.157084E+09 | 0.293630E+09 | 45199993.67 |
August | 0.232850E+09 | 75495666.65 | 0.157354E+09 | 0.323186E+09 | 59196552.84 |
September | 0.262001E+09 | 0.127614E+09 | 0.134387E+09 | 0.335745E+09 | 90164451.43 |
October | 0.259053E+09 | 0.147976E+09 | 0.111077E+09 | 0.292703E+09 | 0.133893E+09 |
November | 0.179544E+09 | 0.101358E+09 | 78185238.26 | 0.178713E+09 | 0.163825E+09 |
December | 0.173125E+09 | 89599800.50 | 83524723.31 | 0.138441E+09 | 0.245412E+09 |
Annual Sum or Average | 0.266000E+10 | 0.117309E+10 | 0.148691E+10 | 0.296540E+10 | 0.167061E+10 |
Minimum of Months | 0.173125E+09 | 41664801.23 | 78185238.26 | 0.138441E+09 | 45199993.67 |
Maximum of Months | 0.288524E+09 | 0.162120E+09 | 0.157354E+09 | 0.335745E+09 | 0.249640E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.207038E+09 | 0.120854E+09 | 86183627.08 | 0.174942E+09 | 0.249640E+09 |
February | 0.213509E+09 | 0.102952E+09 | 0.110557E+09 | 0.178754E+09 | 0.218328E+09 |
March | 0.288524E+09 | 0.162120E+09 | 0.126404E+09 | 0.299078E+09 | 0.176113E+09 |
April | 0.231235E+09 | 92402253.73 | 0.138833E+09 | 0.252587E+09 | 0.131358E+09 |
May | 0.209096E+09 | 60730378.17 | 0.148366E+09 | 0.245185E+09 | 94667621.30 |
June | 0.196620E+09 | 41664801.23 | 0.154955E+09 | 0.252438E+09 | 62817149.47 |
July | 0.207408E+09 | 50323949.97 | 0.157084E+09 | 0.293630E+09 | 45199993.67 |
August | 0.232850E+09 | 75495666.65 | 0.157354E+09 | 0.323186E+09 | 59196552.84 |
September | 0.262001E+09 | 0.127614E+09 | 0.134387E+09 | 0.335745E+09 | 90164451.43 |
October | 0.259053E+09 | 0.147976E+09 | 0.111077E+09 | 0.292703E+09 | 0.133893E+09 |
November | 0.179544E+09 | 0.101358E+09 | 78185238.26 | 0.178713E+09 | 0.163825E+09 |
December | 0.173125E+09 | 89599800.50 | 83524723.31 | 0.138441E+09 | 0.245412E+09 |
Annual Sum or Average | 0.266000E+10 | 0.117309E+10 | 0.148691E+10 | 0.296540E+10 | 0.167061E+10 |
Minimum of Months | 0.173125E+09 | 41664801.23 | 78185238.26 | 0.138441E+09 | 45199993.67 |
Maximum of Months | 0.288524E+09 | 0.162120E+09 | 0.157354E+09 | 0.335745E+09 | 0.249640E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_DOOR
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.247531E+09 | 0.144491E+09 | 0.103040E+09 | 0.210616E+09 | 0.294083E+09 |
February | 0.255268E+09 | 0.123088E+09 | 0.132180E+09 | 0.215670E+09 | 0.256917E+09 |
March | 0.344954E+09 | 0.193828E+09 | 0.151127E+09 | 0.359293E+09 | 0.207890E+09 |
April | 0.276461E+09 | 0.110475E+09 | 0.165986E+09 | 0.303162E+09 | 0.155082E+09 |
May | 0.249992E+09 | 72608317.26 | 0.177384E+09 | 0.293937E+09 | 0.112024E+09 |
June | 0.235076E+09 | 49813803.19 | 0.185262E+09 | 0.302215E+09 | 74508693.88 |
July | 0.247974E+09 | 60166549.85 | 0.187807E+09 | 0.351088E+09 | 53704564.79 |
August | 0.278391E+09 | 90261471.79 | 0.188130E+09 | 0.386486E+09 | 70276016.86 |
September | 0.313245E+09 | 0.152574E+09 | 0.160671E+09 | 0.401813E+09 | 0.106915E+09 |
October | 0.309720E+09 | 0.176918E+09 | 0.132802E+09 | 0.350981E+09 | 0.158349E+09 |
November | 0.214660E+09 | 0.121183E+09 | 93477082.74 | 0.214658E+09 | 0.193289E+09 |
December | 0.206985E+09 | 0.107124E+09 | 99860889.92 | 0.166899E+09 | 0.288807E+09 |
Annual Sum or Average | 0.318026E+10 | 0.140253E+10 | 0.177773E+10 | 0.355682E+10 | 0.197184E+10 |
Minimum of Months | 0.206985E+09 | 49813803.19 | 93477082.74 | 0.166899E+09 | 53704564.79 |
Maximum of Months | 0.344954E+09 | 0.193828E+09 | 0.188130E+09 | 0.401813E+09 | 0.294083E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.207038E+09 | 0.120854E+09 | 86183627.08 | 0.175248E+09 | 0.247157E+09 |
February | 0.213509E+09 | 0.102952E+09 | 0.110557E+09 | 0.179088E+09 | 0.216233E+09 |
March | 0.288524E+09 | 0.162120E+09 | 0.126404E+09 | 0.299561E+09 | 0.174136E+09 |
April | 0.231235E+09 | 92402253.73 | 0.138833E+09 | 0.253241E+09 | 0.129280E+09 |
May | 0.209096E+09 | 60730378.17 | 0.148366E+09 | 0.246114E+09 | 92792328.74 |
June | 0.196620E+09 | 41664801.23 | 0.154955E+09 | 0.252582E+09 | 62539718.92 |
July | 0.207408E+09 | 50323949.97 | 0.157084E+09 | 0.293614E+09 | 45269053.89 |
August | 0.232850E+09 | 75495666.65 | 0.157354E+09 | 0.323186E+09 | 59228584.12 |
September | 0.262001E+09 | 0.127614E+09 | 0.134387E+09 | 0.335916E+09 | 89660169.13 |
October | 0.259053E+09 | 0.147976E+09 | 0.111077E+09 | 0.293431E+09 | 0.131758E+09 |
November | 0.179544E+09 | 0.101358E+09 | 78185238.26 | 0.179161E+09 | 0.161647E+09 |
December | 0.173125E+09 | 89599800.50 | 83524723.31 | 0.138717E+09 | 0.242990E+09 |
Annual Sum or Average | 0.266000E+10 | 0.117309E+10 | 0.148691E+10 | 0.296986E+10 | 0.165269E+10 |
Minimum of Months | 0.173125E+09 | 41664801.23 | 78185238.26 | 0.138717E+09 | 45269053.89 |
Maximum of Months | 0.288524E+09 | 0.162120E+09 | 0.157354E+09 | 0.335916E+09 | 0.247157E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.207038E+09 | 0.120854E+09 | 86183627.08 | 0.175248E+09 | 0.247157E+09 |
February | 0.213509E+09 | 0.102952E+09 | 0.110557E+09 | 0.179088E+09 | 0.216233E+09 |
March | 0.288524E+09 | 0.162120E+09 | 0.126404E+09 | 0.299561E+09 | 0.174136E+09 |
April | 0.231235E+09 | 92402253.73 | 0.138833E+09 | 0.253241E+09 | 0.129280E+09 |
May | 0.209096E+09 | 60730378.17 | 0.148366E+09 | 0.246114E+09 | 92792328.74 |
June | 0.196620E+09 | 41664801.23 | 0.154955E+09 | 0.252582E+09 | 62539718.92 |
July | 0.207408E+09 | 50323949.97 | 0.157084E+09 | 0.293614E+09 | 45269053.89 |
August | 0.232850E+09 | 75495666.65 | 0.157354E+09 | 0.323186E+09 | 59228584.12 |
September | 0.262001E+09 | 0.127614E+09 | 0.134387E+09 | 0.335916E+09 | 89660169.13 |
October | 0.259053E+09 | 0.147976E+09 | 0.111077E+09 | 0.293431E+09 | 0.131758E+09 |
November | 0.179544E+09 | 0.101358E+09 | 78185238.26 | 0.179161E+09 | 0.161647E+09 |
December | 0.173125E+09 | 89599800.50 | 83524723.31 | 0.138717E+09 | 0.242990E+09 |
Annual Sum or Average | 0.266000E+10 | 0.117309E+10 | 0.148691E+10 | 0.296986E+10 | 0.165269E+10 |
Minimum of Months | 0.173125E+09 | 41664801.23 | 78185238.26 | 0.138717E+09 | 45269053.89 |
Maximum of Months | 0.288524E+09 | 0.162120E+09 | 0.157354E+09 | 0.335916E+09 | 0.247157E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_DOOR
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.247531E+09 | 0.144491E+09 | 0.103040E+09 | 0.210991E+09 | 0.291143E+09 |
February | 0.255268E+09 | 0.123088E+09 | 0.132180E+09 | 0.216076E+09 | 0.254441E+09 |
March | 0.344954E+09 | 0.193828E+09 | 0.151127E+09 | 0.359878E+09 | 0.205553E+09 |
April | 0.276461E+09 | 0.110475E+09 | 0.165986E+09 | 0.303947E+09 | 0.152628E+09 |
May | 0.249992E+09 | 72608317.26 | 0.177384E+09 | 0.295045E+09 | 0.109813E+09 |
June | 0.235076E+09 | 49813803.19 | 0.185262E+09 | 0.302388E+09 | 74181784.77 |
July | 0.247974E+09 | 60166549.85 | 0.187807E+09 | 0.351069E+09 | 53786517.32 |
August | 0.278391E+09 | 90261471.79 | 0.188130E+09 | 0.386485E+09 | 70313456.07 |
September | 0.313245E+09 | 0.152574E+09 | 0.160671E+09 | 0.402018E+09 | 0.106319E+09 |
October | 0.309720E+09 | 0.176918E+09 | 0.132802E+09 | 0.351852E+09 | 0.155830E+09 |
November | 0.214660E+09 | 0.121183E+09 | 93477082.74 | 0.215201E+09 | 0.190718E+09 |
December | 0.206985E+09 | 0.107124E+09 | 99860889.92 | 0.167237E+09 | 0.285940E+09 |
Annual Sum or Average | 0.318026E+10 | 0.140253E+10 | 0.177773E+10 | 0.356219E+10 | 0.195067E+10 |
Minimum of Months | 0.206985E+09 | 49813803.19 | 93477082.74 | 0.167237E+09 | 53786517.32 |
Maximum of Months | 0.344954E+09 | 0.193828E+09 | 0.188130E+09 | 0.402018E+09 | 0.291143E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.207038E+09 | 0.120854E+09 | 86183627.08 | 0.175658E+09 | 0.245035E+09 |
February | 0.213509E+09 | 0.102952E+09 | 0.110557E+09 | 0.179545E+09 | 0.214426E+09 |
March | 0.288524E+09 | 0.162120E+09 | 0.126404E+09 | 0.300247E+09 | 0.172298E+09 |
April | 0.231235E+09 | 92402253.73 | 0.138833E+09 | 0.254094E+09 | 0.127373E+09 |
May | 0.209096E+09 | 60730378.17 | 0.148366E+09 | 0.247537E+09 | 90513096.23 |
June | 0.196620E+09 | 41664801.23 | 0.154955E+09 | 0.253093E+09 | 61682439.50 |
July | 0.207408E+09 | 50323949.97 | 0.157084E+09 | 0.293948E+09 | 44614853.89 |
August | 0.232850E+09 | 75495666.65 | 0.157354E+09 | 0.323481E+09 | 58524054.85 |
September | 0.262001E+09 | 0.127614E+09 | 0.134387E+09 | 0.336344E+09 | 88651290.77 |
October | 0.259053E+09 | 0.147976E+09 | 0.111077E+09 | 0.294342E+09 | 0.129734E+09 |
November | 0.179544E+09 | 0.101358E+09 | 78185238.26 | 0.179682E+09 | 0.159769E+09 |
December | 0.173125E+09 | 89599800.50 | 83524723.31 | 0.139077E+09 | 0.240842E+09 |
Annual Sum or Average | 0.266000E+10 | 0.117309E+10 | 0.148691E+10 | 0.297705E+10 | 0.163346E+10 |
Minimum of Months | 0.173125E+09 | 41664801.23 | 78185238.26 | 0.139077E+09 | 44614853.89 |
Maximum of Months | 0.288524E+09 | 0.162120E+09 | 0.157354E+09 | 0.336344E+09 | 0.245035E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.207038E+09 | 0.120854E+09 | 86183627.08 | 0.175658E+09 | 0.245035E+09 |
February | 0.213509E+09 | 0.102952E+09 | 0.110557E+09 | 0.179545E+09 | 0.214426E+09 |
March | 0.288524E+09 | 0.162120E+09 | 0.126404E+09 | 0.300247E+09 | 0.172298E+09 |
April | 0.231235E+09 | 92402253.73 | 0.138833E+09 | 0.254094E+09 | 0.127373E+09 |
May | 0.209096E+09 | 60730378.17 | 0.148366E+09 | 0.247537E+09 | 90513096.23 |
June | 0.196620E+09 | 41664801.23 | 0.154955E+09 | 0.253093E+09 | 61682439.50 |
July | 0.207408E+09 | 50323949.97 | 0.157084E+09 | 0.293948E+09 | 44614853.89 |
August | 0.232850E+09 | 75495666.65 | 0.157354E+09 | 0.323481E+09 | 58524054.85 |
September | 0.262001E+09 | 0.127614E+09 | 0.134387E+09 | 0.336344E+09 | 88651290.77 |
October | 0.259053E+09 | 0.147976E+09 | 0.111077E+09 | 0.294342E+09 | 0.129734E+09 |
November | 0.179544E+09 | 0.101358E+09 | 78185238.26 | 0.179682E+09 | 0.159769E+09 |
December | 0.173125E+09 | 89599800.50 | 83524723.31 | 0.139077E+09 | 0.240842E+09 |
Annual Sum or Average | 0.266000E+10 | 0.117309E+10 | 0.148691E+10 | 0.297705E+10 | 0.163346E+10 |
Minimum of Months | 0.173125E+09 | 41664801.23 | 78185238.26 | 0.139077E+09 | 44614853.89 |
Maximum of Months | 0.288524E+09 | 0.162120E+09 | 0.157354E+09 | 0.336344E+09 | 0.245035E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_DOOR
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.247531E+09 | 0.144491E+09 | 0.103040E+09 | 0.211492E+09 | 0.288631E+09 |
February | 0.255268E+09 | 0.123088E+09 | 0.132180E+09 | 0.216632E+09 | 0.252305E+09 |
March | 0.344954E+09 | 0.193828E+09 | 0.151127E+09 | 0.360705E+09 | 0.203381E+09 |
April | 0.276461E+09 | 0.110475E+09 | 0.165986E+09 | 0.304970E+09 | 0.150381E+09 |
May | 0.249992E+09 | 72608317.26 | 0.177384E+09 | 0.296739E+09 | 0.107130E+09 |
June | 0.235076E+09 | 49813803.19 | 0.185262E+09 | 0.302999E+09 | 73174221.76 |
July | 0.247974E+09 | 60166549.85 | 0.187807E+09 | 0.351470E+09 | 53019814.34 |
August | 0.278391E+09 | 90261471.79 | 0.188130E+09 | 0.386841E+09 | 69485765.45 |
September | 0.313245E+09 | 0.152574E+09 | 0.160671E+09 | 0.402531E+09 | 0.105131E+09 |
October | 0.309720E+09 | 0.176918E+09 | 0.132802E+09 | 0.352936E+09 | 0.153443E+09 |
November | 0.214660E+09 | 0.121183E+09 | 93477082.74 | 0.215831E+09 | 0.188503E+09 |
December | 0.206985E+09 | 0.107124E+09 | 99860889.92 | 0.167676E+09 | 0.283399E+09 |
Annual Sum or Average | 0.318026E+10 | 0.140253E+10 | 0.177773E+10 | 0.357082E+10 | 0.192799E+10 |
Minimum of Months | 0.206985E+09 | 49813803.19 | 93477082.74 | 0.167676E+09 | 53019814.34 |
Maximum of Months | 0.344954E+09 | 0.193828E+09 | 0.188130E+09 | 0.402531E+09 | 0.288631E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.207038E+09 | 0.120854E+09 | 86183627.08 | 0.177393E+09 | 0.237855E+09 |
February | 0.213509E+09 | 0.102952E+09 | 0.110557E+09 | 0.181764E+09 | 0.208085E+09 |
March | 0.288524E+09 | 0.162120E+09 | 0.126404E+09 | 0.302810E+09 | 0.166926E+09 |
April | 0.231235E+09 | 92402253.73 | 0.138833E+09 | 0.256208E+09 | 0.122666E+09 |
May | 0.209096E+09 | 60730378.17 | 0.148366E+09 | 0.250179E+09 | 85929983.08 |
June | 0.196620E+09 | 41664801.23 | 0.154955E+09 | 0.253873E+09 | 59352754.63 |
July | 0.207408E+09 | 50323949.97 | 0.157084E+09 | 0.294089E+09 | 42654605.31 |
August | 0.232850E+09 | 75495666.65 | 0.157354E+09 | 0.323609E+09 | 56376809.88 |
September | 0.262001E+09 | 0.127614E+09 | 0.134387E+09 | 0.337009E+09 | 86190322.37 |
October | 0.259053E+09 | 0.147976E+09 | 0.111077E+09 | 0.296259E+09 | 0.125552E+09 |
November | 0.179544E+09 | 0.101358E+09 | 78185238.26 | 0.181235E+09 | 0.154836E+09 |
December | 0.173125E+09 | 89599800.50 | 83524723.31 | 0.140655E+09 | 0.233630E+09 |
Annual Sum or Average | 0.266000E+10 | 0.117309E+10 | 0.148691E+10 | 0.299508E+10 | 0.158005E+10 |
Minimum of Months | 0.173125E+09 | 41664801.23 | 78185238.26 | 0.140655E+09 | 42654605.31 |
Maximum of Months | 0.288524E+09 | 0.162120E+09 | 0.157354E+09 | 0.337009E+09 | 0.237855E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.207038E+09 | 0.120854E+09 | 86183627.08 | 0.177393E+09 | 0.237855E+09 |
February | 0.213509E+09 | 0.102952E+09 | 0.110557E+09 | 0.181764E+09 | 0.208085E+09 |
March | 0.288524E+09 | 0.162120E+09 | 0.126404E+09 | 0.302810E+09 | 0.166926E+09 |
April | 0.231235E+09 | 92402253.73 | 0.138833E+09 | 0.256208E+09 | 0.122666E+09 |
May | 0.209096E+09 | 60730378.17 | 0.148366E+09 | 0.250179E+09 | 85929983.08 |
June | 0.196620E+09 | 41664801.23 | 0.154955E+09 | 0.253873E+09 | 59352754.63 |
July | 0.207408E+09 | 50323949.97 | 0.157084E+09 | 0.294089E+09 | 42654605.31 |
August | 0.232850E+09 | 75495666.65 | 0.157354E+09 | 0.323609E+09 | 56376809.88 |
September | 0.262001E+09 | 0.127614E+09 | 0.134387E+09 | 0.337009E+09 | 86190322.37 |
October | 0.259053E+09 | 0.147976E+09 | 0.111077E+09 | 0.296259E+09 | 0.125552E+09 |
November | 0.179544E+09 | 0.101358E+09 | 78185238.26 | 0.181235E+09 | 0.154836E+09 |
December | 0.173125E+09 | 89599800.50 | 83524723.31 | 0.140655E+09 | 0.233630E+09 |
Annual Sum or Average | 0.266000E+10 | 0.117309E+10 | 0.148691E+10 | 0.299508E+10 | 0.158005E+10 |
Minimum of Months | 0.173125E+09 | 41664801.23 | 78185238.26 | 0.140655E+09 | 42654605.31 |
Maximum of Months | 0.288524E+09 | 0.162120E+09 | 0.157354E+09 | 0.337009E+09 | 0.237855E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.207038E+09 | 0.120854E+09 | 86183627.08 | 0.177393E+09 | 0.237855E+09 |
February | 0.213509E+09 | 0.102952E+09 | 0.110557E+09 | 0.181764E+09 | 0.208085E+09 |
March | 0.288524E+09 | 0.162120E+09 | 0.126404E+09 | 0.302810E+09 | 0.166926E+09 |
April | 0.231235E+09 | 92402253.73 | 0.138833E+09 | 0.256208E+09 | 0.122666E+09 |
May | 0.209096E+09 | 60730378.17 | 0.148366E+09 | 0.250179E+09 | 85929983.08 |
June | 0.196620E+09 | 41664801.23 | 0.154955E+09 | 0.253873E+09 | 59352754.63 |
July | 0.207408E+09 | 50323949.97 | 0.157084E+09 | 0.294089E+09 | 42654605.31 |
August | 0.232850E+09 | 75495666.65 | 0.157354E+09 | 0.323609E+09 | 56376809.88 |
September | 0.262001E+09 | 0.127614E+09 | 0.134387E+09 | 0.337009E+09 | 86190322.37 |
October | 0.259053E+09 | 0.147976E+09 | 0.111077E+09 | 0.296259E+09 | 0.125552E+09 |
November | 0.179544E+09 | 0.101358E+09 | 78185238.26 | 0.181235E+09 | 0.154836E+09 |
December | 0.173125E+09 | 89599800.50 | 83524723.31 | 0.140655E+09 | 0.233630E+09 |
Annual Sum or Average | 0.266000E+10 | 0.117309E+10 | 0.148691E+10 | 0.299508E+10 | 0.158005E+10 |
Minimum of Months | 0.173125E+09 | 41664801.23 | 78185238.26 | 0.140655E+09 | 42654605.31 |
Maximum of Months | 0.288524E+09 | 0.162120E+09 | 0.157354E+09 | 0.337009E+09 | 0.237855E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.207038E+09 | 0.120854E+09 | 86183627.08 | 0.177393E+09 | 0.237855E+09 |
February | 0.213509E+09 | 0.102952E+09 | 0.110557E+09 | 0.181764E+09 | 0.208085E+09 |
March | 0.288524E+09 | 0.162120E+09 | 0.126404E+09 | 0.302810E+09 | 0.166926E+09 |
April | 0.231235E+09 | 92402253.73 | 0.138833E+09 | 0.256208E+09 | 0.122666E+09 |
May | 0.209096E+09 | 60730378.17 | 0.148366E+09 | 0.250179E+09 | 85929983.08 |
June | 0.196620E+09 | 41664801.23 | 0.154955E+09 | 0.253873E+09 | 59352754.63 |
July | 0.207408E+09 | 50323949.97 | 0.157084E+09 | 0.294089E+09 | 42654605.31 |
August | 0.232850E+09 | 75495666.65 | 0.157354E+09 | 0.323609E+09 | 56376809.88 |
September | 0.262001E+09 | 0.127614E+09 | 0.134387E+09 | 0.337009E+09 | 86190322.37 |
October | 0.259053E+09 | 0.147976E+09 | 0.111077E+09 | 0.296259E+09 | 0.125552E+09 |
November | 0.179544E+09 | 0.101358E+09 | 78185238.26 | 0.181235E+09 | 0.154836E+09 |
December | 0.173125E+09 | 89599800.50 | 83524723.31 | 0.140655E+09 | 0.233630E+09 |
Annual Sum or Average | 0.266000E+10 | 0.117309E+10 | 0.148691E+10 | 0.299508E+10 | 0.158005E+10 |
Minimum of Months | 0.173125E+09 | 41664801.23 | 78185238.26 | 0.140655E+09 | 42654605.31 |
Maximum of Months | 0.288524E+09 | 0.162120E+09 | 0.157354E+09 | 0.337009E+09 | 0.237855E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.247531E+09 | 0.144491E+09 | 0.103040E+09 | 0.213511E+09 | 0.280324E+09 |
February | 0.255268E+09 | 0.123088E+09 | 0.132180E+09 | 0.219194E+09 | 0.244986E+09 |
March | 0.344954E+09 | 0.193828E+09 | 0.151127E+09 | 0.363664E+09 | 0.197140E+09 |
April | 0.276461E+09 | 0.110475E+09 | 0.165986E+09 | 0.307416E+09 | 0.144898E+09 |
May | 0.249992E+09 | 72608317.26 | 0.177384E+09 | 0.299820E+09 | 0.101760E+09 |
June | 0.235076E+09 | 49813803.19 | 0.185262E+09 | 0.303887E+09 | 70441083.42 |
July | 0.247974E+09 | 60166549.85 | 0.187807E+09 | 0.351606E+09 | 50707638.98 |
August | 0.278391E+09 | 90261471.79 | 0.188130E+09 | 0.386955E+09 | 66959448.32 |
September | 0.313245E+09 | 0.152574E+09 | 0.160671E+09 | 0.403267E+09 | 0.102241E+09 |
October | 0.309720E+09 | 0.176918E+09 | 0.132802E+09 | 0.355138E+09 | 0.148564E+09 |
November | 0.214660E+09 | 0.121183E+09 | 93477082.74 | 0.217630E+09 | 0.182762E+09 |
December | 0.206985E+09 | 0.107124E+09 | 99860889.92 | 0.169513E+09 | 0.275062E+09 |
Annual Sum or Average | 0.318026E+10 | 0.140253E+10 | 0.177773E+10 | 0.359160E+10 | 0.186585E+10 |
Minimum of Months | 0.206985E+09 | 49813803.19 | 93477082.74 | 0.169513E+09 | 50707638.98 |
Maximum of Months | 0.344954E+09 | 0.193828E+09 | 0.188130E+09 | 0.403267E+09 | 0.280324E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.247531E+09 | 0.144491E+09 | 0.103040E+09 | 0.213511E+09 | 0.280324E+09 |
February | 0.255268E+09 | 0.123088E+09 | 0.132180E+09 | 0.219194E+09 | 0.244986E+09 |
March | 0.344954E+09 | 0.193828E+09 | 0.151127E+09 | 0.363664E+09 | 0.197140E+09 |
April | 0.276461E+09 | 0.110475E+09 | 0.165986E+09 | 0.307416E+09 | 0.144898E+09 |
May | 0.249992E+09 | 72608317.26 | 0.177384E+09 | 0.299820E+09 | 0.101760E+09 |
June | 0.235076E+09 | 49813803.19 | 0.185262E+09 | 0.303887E+09 | 70441083.42 |
July | 0.247974E+09 | 60166549.85 | 0.187807E+09 | 0.351606E+09 | 50707638.98 |
August | 0.278391E+09 | 90261471.79 | 0.188130E+09 | 0.386955E+09 | 66959448.32 |
September | 0.313245E+09 | 0.152574E+09 | 0.160671E+09 | 0.403267E+09 | 0.102241E+09 |
October | 0.309720E+09 | 0.176918E+09 | 0.132802E+09 | 0.355138E+09 | 0.148564E+09 |
November | 0.214660E+09 | 0.121183E+09 | 93477082.74 | 0.217630E+09 | 0.182762E+09 |
December | 0.206985E+09 | 0.107124E+09 | 99860889.92 | 0.169513E+09 | 0.275062E+09 |
Annual Sum or Average | 0.318026E+10 | 0.140253E+10 | 0.177773E+10 | 0.359160E+10 | 0.186585E+10 |
Minimum of Months | 0.206985E+09 | 49813803.19 | 93477082.74 | 0.169513E+09 | 50707638.98 |
Maximum of Months | 0.344954E+09 | 0.193828E+09 | 0.188130E+09 | 0.403267E+09 | 0.280324E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.207038E+09 | 0.120854E+09 | 86183627.08 | 0.176450E+09 | 0.239643E+09 |
February | 0.213509E+09 | 0.102952E+09 | 0.110557E+09 | 0.180588E+09 | 0.209733E+09 |
March | 0.288524E+09 | 0.162120E+09 | 0.126404E+09 | 0.301743E+09 | 0.167514E+09 |
April | 0.231235E+09 | 92402253.73 | 0.138833E+09 | 0.255612E+09 | 0.122700E+09 |
May | 0.209096E+09 | 60730378.17 | 0.148366E+09 | 0.250230E+09 | 85207899.84 |
June | 0.196620E+09 | 41664801.23 | 0.154955E+09 | 0.253817E+09 | 58858803.16 |
July | 0.207408E+09 | 50323949.97 | 0.157084E+09 | 0.294133E+09 | 42085311.37 |
August | 0.232850E+09 | 75495666.65 | 0.157354E+09 | 0.323507E+09 | 55805916.87 |
September | 0.262001E+09 | 0.127614E+09 | 0.134387E+09 | 0.336704E+09 | 85750340.32 |
October | 0.259053E+09 | 0.147976E+09 | 0.111077E+09 | 0.295798E+09 | 0.125280E+09 |
November | 0.179544E+09 | 0.101358E+09 | 78185238.26 | 0.180685E+09 | 0.155317E+09 |
December | 0.173125E+09 | 89599800.50 | 83524723.31 | 0.139804E+09 | 0.235449E+09 |
Annual Sum or Average | 0.266000E+10 | 0.117309E+10 | 0.148691E+10 | 0.298907E+10 | 0.158334E+10 |
Minimum of Months | 0.173125E+09 | 41664801.23 | 78185238.26 | 0.139804E+09 | 42085311.37 |
Maximum of Months | 0.288524E+09 | 0.162120E+09 | 0.157354E+09 | 0.336704E+09 | 0.239643E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.207038E+09 | 0.120854E+09 | 86183627.08 | 0.176450E+09 | 0.239643E+09 |
February | 0.213509E+09 | 0.102952E+09 | 0.110557E+09 | 0.180588E+09 | 0.209733E+09 |
March | 0.288524E+09 | 0.162120E+09 | 0.126404E+09 | 0.301743E+09 | 0.167514E+09 |
April | 0.231235E+09 | 92402253.73 | 0.138833E+09 | 0.255612E+09 | 0.122700E+09 |
May | 0.209096E+09 | 60730378.17 | 0.148366E+09 | 0.250230E+09 | 85207899.84 |
June | 0.196620E+09 | 41664801.23 | 0.154955E+09 | 0.253817E+09 | 58858803.16 |
July | 0.207408E+09 | 50323949.97 | 0.157084E+09 | 0.294133E+09 | 42085311.37 |
August | 0.232850E+09 | 75495666.65 | 0.157354E+09 | 0.323507E+09 | 55805916.87 |
September | 0.262001E+09 | 0.127614E+09 | 0.134387E+09 | 0.336704E+09 | 85750340.32 |
October | 0.259053E+09 | 0.147976E+09 | 0.111077E+09 | 0.295798E+09 | 0.125280E+09 |
November | 0.179544E+09 | 0.101358E+09 | 78185238.26 | 0.180685E+09 | 0.155317E+09 |
December | 0.173125E+09 | 89599800.50 | 83524723.31 | 0.139804E+09 | 0.235449E+09 |
Annual Sum or Average | 0.266000E+10 | 0.117309E+10 | 0.148691E+10 | 0.298907E+10 | 0.158334E+10 |
Minimum of Months | 0.173125E+09 | 41664801.23 | 78185238.26 | 0.139804E+09 | 42085311.37 |
Maximum of Months | 0.288524E+09 | 0.162120E+09 | 0.157354E+09 | 0.336704E+09 | 0.239643E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_DOOR
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.247531E+09 | 0.144491E+09 | 0.103040E+09 | 0.212473E+09 | 0.282273E+09 |
February | 0.255268E+09 | 0.123088E+09 | 0.132180E+09 | 0.217907E+09 | 0.246781E+09 |
March | 0.344954E+09 | 0.193828E+09 | 0.151127E+09 | 0.362523E+09 | 0.197737E+09 |
April | 0.276461E+09 | 0.110475E+09 | 0.165986E+09 | 0.306809E+09 | 0.144870E+09 |
May | 0.249992E+09 | 72608317.26 | 0.177384E+09 | 0.299961E+09 | 0.100878E+09 |
June | 0.235076E+09 | 49813803.19 | 0.185262E+09 | 0.303888E+09 | 69845487.69 |
July | 0.247974E+09 | 60166549.85 | 0.187807E+09 | 0.351719E+09 | 50033609.61 |
August | 0.278391E+09 | 90261471.79 | 0.188130E+09 | 0.386905E+09 | 66275820.02 |
September | 0.313245E+09 | 0.152574E+09 | 0.160671E+09 | 0.402986E+09 | 0.101700E+09 |
October | 0.309720E+09 | 0.176918E+09 | 0.132802E+09 | 0.354690E+09 | 0.148184E+09 |
November | 0.214660E+09 | 0.121183E+09 | 93477082.74 | 0.217049E+09 | 0.183238E+09 |
December | 0.206985E+09 | 0.107124E+09 | 99860889.92 | 0.168575E+09 | 0.277035E+09 |
Annual Sum or Average | 0.318026E+10 | 0.140253E+10 | 0.177773E+10 | 0.358549E+10 | 0.186885E+10 |
Minimum of Months | 0.206985E+09 | 49813803.19 | 93477082.74 | 0.168575E+09 | 50033609.61 |
Maximum of Months | 0.344954E+09 | 0.193828E+09 | 0.188130E+09 | 0.402986E+09 | 0.282273E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.207038E+09 | 0.120854E+09 | 86183627.08 | 0.176544E+09 | 0.239146E+09 |
February | 0.213509E+09 | 0.102952E+09 | 0.110557E+09 | 0.180690E+09 | 0.209337E+09 |
March | 0.288524E+09 | 0.162120E+09 | 0.126404E+09 | 0.301983E+09 | 0.166856E+09 |
April | 0.231235E+09 | 92402253.73 | 0.138833E+09 | 0.255959E+09 | 0.121921E+09 |
May | 0.209096E+09 | 60730378.17 | 0.148366E+09 | 0.251025E+09 | 84106997.54 |
June | 0.196620E+09 | 41664801.23 | 0.154955E+09 | 0.254216E+09 | 58381556.36 |
July | 0.207408E+09 | 50323949.97 | 0.157084E+09 | 0.294333E+09 | 41830025.23 |
August | 0.232850E+09 | 75495666.65 | 0.157354E+09 | 0.323677E+09 | 55533422.12 |
September | 0.262001E+09 | 0.127614E+09 | 0.134387E+09 | 0.336956E+09 | 85276177.64 |
October | 0.259053E+09 | 0.147976E+09 | 0.111077E+09 | 0.296171E+09 | 0.124492E+09 |
November | 0.179544E+09 | 0.101358E+09 | 78185238.26 | 0.180871E+09 | 0.154664E+09 |
December | 0.173125E+09 | 89599800.50 | 83524723.31 | 0.139890E+09 | 0.234932E+09 |
Annual Sum or Average | 0.266000E+10 | 0.117309E+10 | 0.148691E+10 | 0.299231E+10 | 0.157648E+10 |
Minimum of Months | 0.173125E+09 | 41664801.23 | 78185238.26 | 0.139890E+09 | 41830025.23 |
Maximum of Months | 0.288524E+09 | 0.162120E+09 | 0.157354E+09 | 0.336956E+09 | 0.239146E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.207038E+09 | 0.120854E+09 | 86183627.08 | 0.176544E+09 | 0.239146E+09 |
February | 0.213509E+09 | 0.102952E+09 | 0.110557E+09 | 0.180690E+09 | 0.209337E+09 |
March | 0.288524E+09 | 0.162120E+09 | 0.126404E+09 | 0.301983E+09 | 0.166856E+09 |
April | 0.231235E+09 | 92402253.73 | 0.138833E+09 | 0.255959E+09 | 0.121921E+09 |
May | 0.209096E+09 | 60730378.17 | 0.148366E+09 | 0.251025E+09 | 84106997.54 |
June | 0.196620E+09 | 41664801.23 | 0.154955E+09 | 0.254216E+09 | 58381556.36 |
July | 0.207408E+09 | 50323949.97 | 0.157084E+09 | 0.294333E+09 | 41830025.23 |
August | 0.232850E+09 | 75495666.65 | 0.157354E+09 | 0.323677E+09 | 55533422.12 |
September | 0.262001E+09 | 0.127614E+09 | 0.134387E+09 | 0.336956E+09 | 85276177.64 |
October | 0.259053E+09 | 0.147976E+09 | 0.111077E+09 | 0.296171E+09 | 0.124492E+09 |
November | 0.179544E+09 | 0.101358E+09 | 78185238.26 | 0.180871E+09 | 0.154664E+09 |
December | 0.173125E+09 | 89599800.50 | 83524723.31 | 0.139890E+09 | 0.234932E+09 |
Annual Sum or Average | 0.266000E+10 | 0.117309E+10 | 0.148691E+10 | 0.299231E+10 | 0.157648E+10 |
Minimum of Months | 0.173125E+09 | 41664801.23 | 78185238.26 | 0.139890E+09 | 41830025.23 |
Maximum of Months | 0.288524E+09 | 0.162120E+09 | 0.157354E+09 | 0.336956E+09 | 0.239146E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_DOOR
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.247531E+09 | 0.144491E+09 | 0.103040E+09 | 0.212588E+09 | 0.281685E+09 |
February | 0.255268E+09 | 0.123088E+09 | 0.132180E+09 | 0.218032E+09 | 0.246313E+09 |
March | 0.344954E+09 | 0.193828E+09 | 0.151127E+09 | 0.362815E+09 | 0.196960E+09 |
April | 0.276461E+09 | 0.110475E+09 | 0.165986E+09 | 0.307226E+09 | 0.143949E+09 |
May | 0.249992E+09 | 72608317.26 | 0.177384E+09 | 0.300910E+09 | 99581885.78 |
June | 0.235076E+09 | 49813803.19 | 0.185262E+09 | 0.304366E+09 | 69282323.10 |
July | 0.247974E+09 | 60166549.85 | 0.187807E+09 | 0.351959E+09 | 49732234.61 |
August | 0.278391E+09 | 90261471.79 | 0.188130E+09 | 0.387109E+09 | 65953971.36 |
September | 0.313245E+09 | 0.152574E+09 | 0.160671E+09 | 0.403289E+09 | 0.101139E+09 |
October | 0.309720E+09 | 0.176918E+09 | 0.132802E+09 | 0.355135E+09 | 0.147255E+09 |
November | 0.214660E+09 | 0.121183E+09 | 93477082.74 | 0.217272E+09 | 0.182465E+09 |
December | 0.206985E+09 | 0.107124E+09 | 99860889.92 | 0.168681E+09 | 0.276424E+09 |
Annual Sum or Average | 0.318026E+10 | 0.140253E+10 | 0.177773E+10 | 0.358938E+10 | 0.186074E+10 |
Minimum of Months | 0.206985E+09 | 49813803.19 | 93477082.74 | 0.168681E+09 | 49732234.61 |
Maximum of Months | 0.344954E+09 | 0.193828E+09 | 0.188130E+09 | 0.403289E+09 | 0.281685E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.207038E+09 | 0.120854E+09 | 86183627.08 | 0.176999E+09 | 0.236345E+09 |
February | 0.213509E+09 | 0.102952E+09 | 0.110557E+09 | 0.181187E+09 | 0.207049E+09 |
March | 0.288524E+09 | 0.162120E+09 | 0.126404E+09 | 0.302842E+09 | 0.164075E+09 |
April | 0.231235E+09 | 92402253.73 | 0.138833E+09 | 0.256951E+09 | 0.119249E+09 |
May | 0.209096E+09 | 60730378.17 | 0.148366E+09 | 0.252836E+09 | 81359930.03 |
June | 0.196620E+09 | 41664801.23 | 0.154955E+09 | 0.255219E+09 | 57043822.69 |
July | 0.207408E+09 | 50323949.97 | 0.157084E+09 | 0.294702E+09 | 41195074.22 |
August | 0.232850E+09 | 75495666.65 | 0.157354E+09 | 0.323993E+09 | 54866871.96 |
September | 0.262001E+09 | 0.127614E+09 | 0.134387E+09 | 0.337597E+09 | 83938571.66 |
October | 0.259053E+09 | 0.147976E+09 | 0.111077E+09 | 0.297024E+09 | 0.122391E+09 |
November | 0.179544E+09 | 0.101358E+09 | 78185238.26 | 0.181442E+09 | 0.152351E+09 |
December | 0.173125E+09 | 89599800.50 | 83524723.31 | 0.140286E+09 | 0.232200E+09 |
Annual Sum or Average | 0.266000E+10 | 0.117309E+10 | 0.148691E+10 | 0.300108E+10 | 0.155206E+10 |
Minimum of Months | 0.173125E+09 | 41664801.23 | 78185238.26 | 0.140286E+09 | 41195074.22 |
Maximum of Months | 0.288524E+09 | 0.162120E+09 | 0.157354E+09 | 0.337597E+09 | 0.236345E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.207038E+09 | 0.120854E+09 | 86183627.08 | 0.176999E+09 | 0.236345E+09 |
February | 0.213509E+09 | 0.102952E+09 | 0.110557E+09 | 0.181187E+09 | 0.207049E+09 |
March | 0.288524E+09 | 0.162120E+09 | 0.126404E+09 | 0.302842E+09 | 0.164075E+09 |
April | 0.231235E+09 | 92402253.73 | 0.138833E+09 | 0.256951E+09 | 0.119249E+09 |
May | 0.209096E+09 | 60730378.17 | 0.148366E+09 | 0.252836E+09 | 81359930.03 |
June | 0.196620E+09 | 41664801.23 | 0.154955E+09 | 0.255219E+09 | 57043822.69 |
July | 0.207408E+09 | 50323949.97 | 0.157084E+09 | 0.294702E+09 | 41195074.22 |
August | 0.232850E+09 | 75495666.65 | 0.157354E+09 | 0.323993E+09 | 54866871.96 |
September | 0.262001E+09 | 0.127614E+09 | 0.134387E+09 | 0.337597E+09 | 83938571.66 |
October | 0.259053E+09 | 0.147976E+09 | 0.111077E+09 | 0.297024E+09 | 0.122391E+09 |
November | 0.179544E+09 | 0.101358E+09 | 78185238.26 | 0.181442E+09 | 0.152351E+09 |
December | 0.173125E+09 | 89599800.50 | 83524723.31 | 0.140286E+09 | 0.232200E+09 |
Annual Sum or Average | 0.266000E+10 | 0.117309E+10 | 0.148691E+10 | 0.300108E+10 | 0.155206E+10 |
Minimum of Months | 0.173125E+09 | 41664801.23 | 78185238.26 | 0.140286E+09 | 41195074.22 |
Maximum of Months | 0.288524E+09 | 0.162120E+09 | 0.157354E+09 | 0.337597E+09 | 0.236345E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_DOOR
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.247531E+09 | 0.144491E+09 | 0.103040E+09 | 0.213146E+09 | 0.278373E+09 |
February | 0.255268E+09 | 0.123088E+09 | 0.132180E+09 | 0.218637E+09 | 0.243613E+09 |
March | 0.344954E+09 | 0.193828E+09 | 0.151127E+09 | 0.363854E+09 | 0.193679E+09 |
April | 0.276461E+09 | 0.110475E+09 | 0.165986E+09 | 0.308419E+09 | 0.140799E+09 |
May | 0.249992E+09 | 72608317.26 | 0.177384E+09 | 0.303068E+09 | 96350949.70 |
June | 0.235076E+09 | 49813803.19 | 0.185262E+09 | 0.305560E+09 | 67707477.46 |
July | 0.247974E+09 | 60166549.85 | 0.187807E+09 | 0.352400E+09 | 48987892.79 |
August | 0.278391E+09 | 90261471.79 | 0.188130E+09 | 0.387487E+09 | 65170674.68 |
September | 0.313245E+09 | 0.152574E+09 | 0.160671E+09 | 0.404054E+09 | 99562992.66 |
October | 0.309720E+09 | 0.176918E+09 | 0.132802E+09 | 0.356156E+09 | 0.144778E+09 |
November | 0.214660E+09 | 0.121183E+09 | 93477082.74 | 0.217961E+09 | 0.179733E+09 |
December | 0.206985E+09 | 0.107124E+09 | 99860889.92 | 0.169165E+09 | 0.273196E+09 |
Annual Sum or Average | 0.318026E+10 | 0.140253E+10 | 0.177773E+10 | 0.359991E+10 | 0.183195E+10 |
Minimum of Months | 0.206985E+09 | 49813803.19 | 93477082.74 | 0.169165E+09 | 48987892.79 |
Maximum of Months | 0.344954E+09 | 0.193828E+09 | 0.188130E+09 | 0.404054E+09 | 0.278373E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.207038E+09 | 0.120854E+09 | 86183627.08 | 0.179033E+09 | 0.223986E+09 |
February | 0.213509E+09 | 0.102952E+09 | 0.110557E+09 | 0.183423E+09 | 0.196522E+09 |
March | 0.288524E+09 | 0.162120E+09 | 0.126404E+09 | 0.305958E+09 | 0.152529E+09 |
April | 0.231235E+09 | 92402253.73 | 0.138833E+09 | 0.259841E+09 | 0.109118E+09 |
May | 0.209096E+09 | 60730378.17 | 0.148366E+09 | 0.256708E+09 | 73232627.98 |
June | 0.196620E+09 | 41664801.23 | 0.154955E+09 | 0.257643E+09 | 52446008.44 |
July | 0.207408E+09 | 50323949.97 | 0.157084E+09 | 0.295376E+09 | 38785074.99 |
August | 0.232850E+09 | 75495666.65 | 0.157354E+09 | 0.324530E+09 | 52307851.04 |
September | 0.262001E+09 | 0.127614E+09 | 0.134387E+09 | 0.339000E+09 | 79487384.11 |
October | 0.259053E+09 | 0.147976E+09 | 0.111077E+09 | 0.298935E+09 | 0.115678E+09 |
November | 0.179544E+09 | 0.101358E+09 | 78185238.26 | 0.183237E+09 | 0.143654E+09 |
December | 0.173125E+09 | 89599800.50 | 83524723.31 | 0.142003E+09 | 0.220122E+09 |
Annual Sum or Average | 0.266000E+10 | 0.117309E+10 | 0.148691E+10 | 0.302569E+10 | 0.145787E+10 |
Minimum of Months | 0.173125E+09 | 41664801.23 | 78185238.26 | 0.142003E+09 | 38785074.99 |
Maximum of Months | 0.288524E+09 | 0.162120E+09 | 0.157354E+09 | 0.339000E+09 | 0.223986E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.207038E+09 | 0.120854E+09 | 86183627.08 | 0.179033E+09 | 0.223986E+09 |
February | 0.213509E+09 | 0.102952E+09 | 0.110557E+09 | 0.183423E+09 | 0.196522E+09 |
March | 0.288524E+09 | 0.162120E+09 | 0.126404E+09 | 0.305958E+09 | 0.152529E+09 |
April | 0.231235E+09 | 92402253.73 | 0.138833E+09 | 0.259841E+09 | 0.109118E+09 |
May | 0.209096E+09 | 60730378.17 | 0.148366E+09 | 0.256708E+09 | 73232627.98 |
June | 0.196620E+09 | 41664801.23 | 0.154955E+09 | 0.257643E+09 | 52446008.44 |
July | 0.207408E+09 | 50323949.97 | 0.157084E+09 | 0.295376E+09 | 38785074.99 |
August | 0.232850E+09 | 75495666.65 | 0.157354E+09 | 0.324530E+09 | 52307851.04 |
September | 0.262001E+09 | 0.127614E+09 | 0.134387E+09 | 0.339000E+09 | 79487384.11 |
October | 0.259053E+09 | 0.147976E+09 | 0.111077E+09 | 0.298935E+09 | 0.115678E+09 |
November | 0.179544E+09 | 0.101358E+09 | 78185238.26 | 0.183237E+09 | 0.143654E+09 |
December | 0.173125E+09 | 89599800.50 | 83524723.31 | 0.142003E+09 | 0.220122E+09 |
Annual Sum or Average | 0.266000E+10 | 0.117309E+10 | 0.148691E+10 | 0.302569E+10 | 0.145787E+10 |
Minimum of Months | 0.173125E+09 | 41664801.23 | 78185238.26 | 0.142003E+09 | 38785074.99 |
Maximum of Months | 0.288524E+09 | 0.162120E+09 | 0.157354E+09 | 0.339000E+09 | 0.223986E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_DOOR
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.247531E+09 | 0.144491E+09 | 0.103040E+09 | 0.215627E+09 | 0.263765E+09 |
February | 0.255268E+09 | 0.123088E+09 | 0.132180E+09 | 0.221364E+09 | 0.231180E+09 |
March | 0.344954E+09 | 0.193828E+09 | 0.151127E+09 | 0.367627E+09 | 0.180058E+09 |
April | 0.276461E+09 | 0.110475E+09 | 0.165986E+09 | 0.311910E+09 | 0.128871E+09 |
May | 0.249992E+09 | 72608317.26 | 0.177384E+09 | 0.307697E+09 | 86787206.90 |
June | 0.235076E+09 | 49813803.19 | 0.185262E+09 | 0.308447E+09 | 62298982.62 |
July | 0.247974E+09 | 60166549.85 | 0.187807E+09 | 0.353201E+09 | 46153166.51 |
August | 0.278391E+09 | 90261471.79 | 0.188130E+09 | 0.388126E+09 | 62162102.49 |
September | 0.313245E+09 | 0.152574E+09 | 0.160671E+09 | 0.405727E+09 | 94318852.66 |
October | 0.309720E+09 | 0.176918E+09 | 0.132802E+09 | 0.358455E+09 | 0.136879E+09 |
November | 0.214660E+09 | 0.121183E+09 | 93477082.74 | 0.220134E+09 | 0.169490E+09 |
December | 0.206985E+09 | 0.107124E+09 | 99860889.92 | 0.171264E+09 | 0.258942E+09 |
Annual Sum or Average | 0.318026E+10 | 0.140253E+10 | 0.177773E+10 | 0.362958E+10 | 0.172090E+10 |
Minimum of Months | 0.206985E+09 | 49813803.19 | 93477082.74 | 0.171264E+09 | 46153166.51 |
Maximum of Months | 0.344954E+09 | 0.193828E+09 | 0.188130E+09 | 0.405727E+09 | 0.263765E+09 |
Report: WindowZoneSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 424.82 | 580.78 | 495.05 | 288.97 | 206.07 | 0.00 | 0.00 |
February | 482.27 | 561.56 | 565.22 | 272.54 | 292.68 | 0.00 | 0.00 |
March | 724.95 | 405.10 | 689.89 | 387.64 | 302.24 | 0.00 | 0.00 |
April | 633.12 | 307.87 | 571.34 | 228.31 | 343.03 | 0.00 | 0.00 |
May | 596.47 | 210.33 | 499.97 | 145.21 | 354.76 | 0.00 | 0.00 |
June | 629.45 | 143.87 | 485.81 | 102.95 | 382.86 | 0.00 | 0.00 |
July | 706.48 | 97.27 | 495.93 | 120.33 | 375.60 | 0.00 | 0.00 |
August | 775.88 | 130.43 | 556.77 | 180.52 | 376.25 | 0.00 | 0.00 |
September | 833.50 | 211.06 | 647.35 | 315.31 | 332.04 | 0.00 | 0.00 |
October | 706.03 | 307.10 | 619.42 | 353.82 | 265.60 | 0.00 | 0.00 |
November | 446.57 | 390.55 | 443.62 | 250.44 | 193.18 | 0.00 | 0.00 |
December | 336.60 | 569.74 | 413.96 | 214.24 | 199.72 | 0.00 | 0.00 |
Annual Sum or Average | 608.74 | 325.06 | 540.19 | 238.23 | 301.96 | 0.00 | 0.00 |
Minimum of Months | 336.60 | 97.27 | 413.96 | 102.95 | 193.18 | 0.00 | 0.00 |
Maximum of Months | 833.50 | 580.78 | 689.89 | 387.64 | 382.86 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 209.21 | 303.52 | 247.52 | 144.49 | 103.04 | 0.00 | 0.00 |
February | 236.91 | 293.89 | 282.61 | 136.27 | 146.34 | 0.00 | 0.00 |
March | 357.62 | 214.65 | 344.94 | 193.82 | 151.12 | 0.00 | 0.00 |
April | 311.43 | 166.61 | 285.67 | 114.15 | 171.51 | 0.00 | 0.00 |
May | 292.35 | 114.58 | 249.98 | 72.61 | 177.38 | 0.00 | 0.00 |
June | 312.55 | 74.42 | 242.90 | 51.47 | 191.43 | 0.00 | 0.00 |
July | 352.46 | 49.64 | 247.97 | 60.16 | 187.80 | 0.00 | 0.00 |
August | 387.21 | 66.33 | 278.38 | 90.26 | 188.12 | 0.00 | 0.00 |
September | 414.88 | 108.69 | 323.68 | 157.65 | 166.02 | 0.00 | 0.00 |
October | 349.05 | 163.79 | 309.71 | 176.91 | 132.80 | 0.00 | 0.00 |
November | 220.27 | 207.30 | 221.81 | 125.22 | 96.59 | 0.00 | 0.00 |
December | 165.56 | 298.34 | 206.98 | 107.12 | 99.86 | 0.00 | 0.00 |
Annual Sum or Average | 301.16 | 171.17 | 270.10 | 119.12 | 150.98 | 0.00 | 0.00 |
Minimum of Months | 165.56 | 49.64 | 206.98 | 51.47 | 96.59 | 0.00 | 0.00 |
Maximum of Months | 414.88 | 303.52 | 344.94 | 193.82 | 191.43 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 209.26 | 296.21 | 247.02 | 144.19 | 102.83 | 0.00 | 0.00 |
February | 236.93 | 286.69 | 282.03 | 135.99 | 146.04 | 0.00 | 0.00 |
March | 357.47 | 209.12 | 344.24 | 193.42 | 150.81 | 0.00 | 0.00 |
April | 311.86 | 161.19 | 285.08 | 113.92 | 171.16 | 0.00 | 0.00 |
May | 292.83 | 112.51 | 249.47 | 72.46 | 177.01 | 0.00 | 0.00 |
June | 311.38 | 77.22 | 242.41 | 51.37 | 191.04 | 0.00 | 0.00 |
July | 350.34 | 53.80 | 247.46 | 60.04 | 187.42 | 0.00 | 0.00 |
August | 385.63 | 70.44 | 277.81 | 90.07 | 187.74 | 0.00 | 0.00 |
September | 414.08 | 110.82 | 323.01 | 157.33 | 165.68 | 0.00 | 0.00 |
October | 349.61 | 159.10 | 309.07 | 176.55 | 132.53 | 0.00 | 0.00 |
November | 220.71 | 200.98 | 221.35 | 124.96 | 96.39 | 0.00 | 0.00 |
December | 165.69 | 291.08 | 206.55 | 106.90 | 99.65 | 0.00 | 0.00 |
Annual Sum or Average | 300.85 | 168.48 | 269.54 | 118.87 | 150.67 | 0.00 | 0.00 |
Minimum of Months | 165.69 | 53.80 | 206.55 | 51.37 | 96.39 | 0.00 | 0.00 |
Maximum of Months | 414.08 | 296.21 | 344.24 | 193.42 | 191.04 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 209.63 | 293.25 | 247.02 | 144.19 | 102.83 | 0.00 | 0.00 |
February | 237.37 | 283.94 | 282.03 | 135.99 | 146.04 | 0.00 | 0.00 |
March | 358.05 | 206.77 | 344.24 | 193.42 | 150.81 | 0.00 | 0.00 |
April | 312.67 | 158.64 | 285.08 | 113.92 | 171.16 | 0.00 | 0.00 |
May | 293.93 | 110.29 | 249.47 | 72.46 | 177.01 | 0.00 | 0.00 |
June | 311.56 | 76.88 | 242.41 | 51.37 | 191.04 | 0.00 | 0.00 |
July | 350.32 | 53.88 | 247.46 | 60.04 | 187.42 | 0.00 | 0.00 |
August | 385.62 | 70.48 | 277.81 | 90.07 | 187.74 | 0.00 | 0.00 |
September | 414.29 | 110.20 | 323.01 | 157.33 | 165.68 | 0.00 | 0.00 |
October | 350.48 | 156.57 | 309.07 | 176.55 | 132.53 | 0.00 | 0.00 |
November | 221.27 | 198.31 | 221.35 | 124.96 | 96.39 | 0.00 | 0.00 |
December | 166.02 | 288.20 | 206.55 | 106.90 | 99.65 | 0.00 | 0.00 |
Annual Sum or Average | 301.30 | 166.67 | 269.54 | 118.87 | 150.67 | 0.00 | 0.00 |
Minimum of Months | 166.02 | 53.88 | 206.55 | 51.37 | 96.39 | 0.00 | 0.00 |
Maximum of Months | 414.29 | 293.25 | 344.24 | 193.42 | 191.04 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 210.13 | 290.73 | 247.02 | 144.19 | 102.83 | 0.00 | 0.00 |
February | 237.98 | 281.56 | 282.03 | 135.99 | 146.04 | 0.00 | 0.00 |
March | 358.87 | 204.59 | 344.24 | 193.42 | 150.81 | 0.00 | 0.00 |
April | 313.72 | 156.30 | 285.08 | 113.92 | 171.16 | 0.00 | 0.00 |
May | 295.63 | 107.58 | 249.47 | 72.46 | 177.01 | 0.00 | 0.00 |
June | 312.19 | 75.83 | 242.41 | 51.37 | 191.04 | 0.00 | 0.00 |
July | 350.72 | 53.11 | 247.46 | 60.04 | 187.42 | 0.00 | 0.00 |
August | 385.98 | 69.64 | 277.81 | 90.07 | 187.74 | 0.00 | 0.00 |
September | 414.82 | 108.96 | 323.01 | 157.33 | 165.68 | 0.00 | 0.00 |
October | 351.56 | 154.16 | 309.07 | 176.55 | 132.53 | 0.00 | 0.00 |
November | 221.91 | 196.00 | 221.35 | 124.96 | 96.39 | 0.00 | 0.00 |
December | 166.45 | 285.65 | 206.55 | 106.90 | 99.65 | 0.00 | 0.00 |
Annual Sum or Average | 302.03 | 164.73 | 269.54 | 118.87 | 150.67 | 0.00 | 0.00 |
Minimum of Months | 166.45 | 53.11 | 206.55 | 51.37 | 96.39 | 0.00 | 0.00 |
Maximum of Months | 414.82 | 290.73 | 344.24 | 193.42 | 191.04 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 424.35 | 564.54 | 494.03 | 288.38 | 205.65 | 0.00 | 0.00 |
February | 481.74 | 546.59 | 564.06 | 271.98 | 292.07 | 0.00 | 0.00 |
March | 723.78 | 396.50 | 688.47 | 386.85 | 301.62 | 0.00 | 0.00 |
April | 632.59 | 301.10 | 570.16 | 227.84 | 342.32 | 0.00 | 0.00 |
May | 597.50 | 204.32 | 498.94 | 144.91 | 354.03 | 0.00 | 0.00 |
June | 626.26 | 145.95 | 484.81 | 102.73 | 382.08 | 0.00 | 0.00 |
July | 701.75 | 101.57 | 494.91 | 120.08 | 374.83 | 0.00 | 0.00 |
August | 772.23 | 134.19 | 555.62 | 180.15 | 375.48 | 0.00 | 0.00 |
September | 831.24 | 211.90 | 646.02 | 314.66 | 331.36 | 0.00 | 0.00 |
October | 707.63 | 298.44 | 618.15 | 353.10 | 265.05 | 0.00 | 0.00 |
November | 447.61 | 379.96 | 442.71 | 249.92 | 192.78 | 0.00 | 0.00 |
December | 336.63 | 554.30 | 413.11 | 213.80 | 199.31 | 0.00 | 0.00 |
Annual Sum or Average | 607.67 | 318.74 | 539.08 | 237.74 | 301.34 | 0.00 | 0.00 |
Minimum of Months | 336.63 | 101.57 | 413.11 | 102.73 | 192.78 | 0.00 | 0.00 |
Maximum of Months | 831.24 | 564.54 | 688.47 | 386.85 | 382.08 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 211.08 | 284.33 | 247.02 | 144.19 | 102.83 | 0.00 | 0.00 |
February | 239.37 | 275.40 | 282.03 | 135.99 | 146.04 | 0.00 | 0.00 |
March | 360.67 | 198.91 | 344.24 | 193.42 | 150.81 | 0.00 | 0.00 |
April | 315.60 | 150.57 | 285.08 | 113.92 | 171.16 | 0.00 | 0.00 |
May | 298.84 | 101.29 | 249.47 | 72.46 | 177.01 | 0.00 | 0.00 |
June | 313.09 | 72.36 | 242.41 | 51.37 | 191.04 | 0.00 | 0.00 |
July | 350.95 | 50.11 | 247.46 | 60.04 | 187.42 | 0.00 | 0.00 |
August | 386.02 | 66.42 | 277.81 | 90.07 | 187.74 | 0.00 | 0.00 |
September | 415.28 | 105.40 | 323.01 | 157.33 | 165.68 | 0.00 | 0.00 |
October | 353.30 | 148.87 | 309.07 | 176.55 | 132.53 | 0.00 | 0.00 |
November | 223.16 | 190.54 | 221.35 | 124.96 | 96.39 | 0.00 | 0.00 |
December | 167.33 | 279.24 | 206.55 | 106.90 | 99.65 | 0.00 | 0.00 |
Annual Sum or Average | 303.26 | 159.68 | 269.54 | 118.87 | 150.67 | 0.00 | 0.00 |
Minimum of Months | 167.33 | 50.11 | 206.55 | 51.37 | 96.39 | 0.00 | 0.00 |
Maximum of Months | 415.28 | 284.33 | 344.24 | 193.42 | 191.04 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 211.20 | 283.74 | 247.02 | 144.19 | 102.83 | 0.00 | 0.00 |
February | 239.50 | 274.88 | 282.03 | 135.99 | 146.04 | 0.00 | 0.00 |
March | 360.95 | 198.13 | 344.24 | 193.42 | 150.81 | 0.00 | 0.00 |
April | 316.03 | 149.61 | 285.08 | 113.92 | 171.16 | 0.00 | 0.00 |
May | 299.79 | 99.98 | 249.47 | 72.46 | 177.01 | 0.00 | 0.00 |
June | 313.58 | 71.78 | 242.41 | 51.37 | 191.04 | 0.00 | 0.00 |
July | 351.19 | 49.80 | 247.46 | 60.04 | 187.42 | 0.00 | 0.00 |
August | 386.22 | 66.09 | 277.81 | 90.07 | 187.74 | 0.00 | 0.00 |
September | 415.59 | 104.82 | 323.01 | 157.33 | 165.68 | 0.00 | 0.00 |
October | 353.75 | 147.94 | 309.07 | 176.55 | 132.53 | 0.00 | 0.00 |
November | 223.38 | 189.73 | 221.35 | 124.96 | 96.39 | 0.00 | 0.00 |
December | 167.43 | 278.63 | 206.55 | 106.90 | 99.65 | 0.00 | 0.00 |
Annual Sum or Average | 303.59 | 158.98 | 269.54 | 118.87 | 150.67 | 0.00 | 0.00 |
Minimum of Months | 167.43 | 49.80 | 206.55 | 51.37 | 96.39 | 0.00 | 0.00 |
Maximum of Months | 415.59 | 283.74 | 344.24 | 193.42 | 191.04 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 211.75 | 280.41 | 247.02 | 144.19 | 102.83 | 0.00 | 0.00 |
February | 240.16 | 271.87 | 282.03 | 135.99 | 146.04 | 0.00 | 0.00 |
March | 361.98 | 194.83 | 344.24 | 193.42 | 150.81 | 0.00 | 0.00 |
April | 317.25 | 146.33 | 285.08 | 113.92 | 171.16 | 0.00 | 0.00 |
May | 301.95 | 96.73 | 249.47 | 72.46 | 177.01 | 0.00 | 0.00 |
June | 314.81 | 70.14 | 242.41 | 51.37 | 191.04 | 0.00 | 0.00 |
July | 351.63 | 49.05 | 247.46 | 60.04 | 187.42 | 0.00 | 0.00 |
August | 386.60 | 65.30 | 277.81 | 90.07 | 187.74 | 0.00 | 0.00 |
September | 416.38 | 103.18 | 323.01 | 157.33 | 165.68 | 0.00 | 0.00 |
October | 354.77 | 145.44 | 309.07 | 176.55 | 132.53 | 0.00 | 0.00 |
November | 224.09 | 186.90 | 221.35 | 124.96 | 96.39 | 0.00 | 0.00 |
December | 167.91 | 275.38 | 206.55 | 106.90 | 99.65 | 0.00 | 0.00 |
Annual Sum or Average | 304.48 | 156.52 | 269.54 | 118.87 | 150.67 | 0.00 | 0.00 |
Minimum of Months | 167.91 | 49.05 | 206.55 | 51.37 | 96.39 | 0.00 | 0.00 |
Maximum of Months | 416.38 | 280.41 | 344.24 | 193.42 | 191.04 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 214.19 | 265.73 | 247.02 | 144.19 | 102.83 | 0.00 | 0.00 |
February | 243.14 | 258.03 | 282.03 | 135.99 | 146.04 | 0.00 | 0.00 |
March | 365.72 | 181.12 | 344.24 | 193.42 | 150.81 | 0.00 | 0.00 |
April | 320.83 | 133.91 | 285.08 | 113.92 | 171.16 | 0.00 | 0.00 |
May | 306.57 | 87.09 | 249.47 | 72.46 | 177.01 | 0.00 | 0.00 |
June | 317.80 | 64.50 | 242.41 | 51.37 | 191.04 | 0.00 | 0.00 |
July | 352.43 | 46.19 | 247.46 | 60.04 | 187.42 | 0.00 | 0.00 |
August | 387.24 | 62.27 | 277.81 | 90.07 | 187.74 | 0.00 | 0.00 |
September | 418.10 | 97.72 | 323.01 | 157.33 | 165.68 | 0.00 | 0.00 |
October | 357.05 | 137.48 | 309.07 | 176.55 | 132.53 | 0.00 | 0.00 |
November | 226.31 | 176.23 | 221.35 | 124.96 | 96.39 | 0.00 | 0.00 |
December | 169.98 | 261.04 | 206.55 | 106.90 | 99.65 | 0.00 | 0.00 |
Annual Sum or Average | 306.98 | 147.03 | 269.54 | 118.87 | 150.67 | 0.00 | 0.00 |
Minimum of Months | 169.98 | 46.19 | 206.55 | 51.37 | 96.39 | 0.00 | 0.00 |
Maximum of Months | 418.10 | 265.73 | 344.24 | 193.42 | 191.04 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.113783E+10 | 0.155556E+10 | 0.132593E+10 | 0.773986E+09 | 0.551946E+09 | 0.00 | 0.00 |
February | 0.116670E+10 | 0.135853E+10 | 0.136738E+10 | 0.659338E+09 | 0.708040E+09 | 0.00 | 0.00 |
March | 0.194170E+10 | 0.108502E+10 | 0.184779E+10 | 0.103826E+10 | 0.809530E+09 | 0.00 | 0.00 |
April | 0.164104E+10 | 0.797990E+09 | 0.148090E+10 | 0.591772E+09 | 0.889128E+09 | 0.00 | 0.00 |
May | 0.159757E+10 | 0.563344E+09 | 0.133912E+10 | 0.388936E+09 | 0.950181E+09 | 0.00 | 0.00 |
June | 0.163152E+10 | 0.372921E+09 | 0.125922E+10 | 0.266834E+09 | 0.992382E+09 | 0.00 | 0.00 |
July | 0.189223E+10 | 0.260526E+09 | 0.132830E+10 | 0.322290E+09 | 0.100601E+10 | 0.00 | 0.00 |
August | 0.207810E+10 | 0.349332E+09 | 0.149124E+10 | 0.483497E+09 | 0.100774E+10 | 0.00 | 0.00 |
September | 0.216042E+10 | 0.547061E+09 | 0.167794E+10 | 0.817280E+09 | 0.860657E+09 | 0.00 | 0.00 |
October | 0.189102E+10 | 0.822536E+09 | 0.165906E+10 | 0.947684E+09 | 0.711371E+09 | 0.00 | 0.00 |
November | 0.115752E+10 | 0.101231E+10 | 0.114985E+10 | 0.649131E+09 | 0.500722E+09 | 0.00 | 0.00 |
December | 0.901544E+09 | 0.152600E+10 | 0.110874E+10 | 0.573825E+09 | 0.534918E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.191972E+11 | 0.102511E+11 | 0.170355E+11 | 0.751284E+10 | 0.952263E+10 | 0.00 | 0.00 |
Minimum of Months | 0.901544E+09 | 0.260526E+09 | 0.110874E+10 | 0.266834E+09 | 0.500722E+09 | 0.00 | 0.00 |
Maximum of Months | 0.216042E+10 | 0.155556E+10 | 0.184779E+10 | 0.103826E+10 | 0.100774E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.560351E+09 | 0.812951E+09 | 0.662966E+09 | 0.386993E+09 | 0.275973E+09 | 0.00 | 0.00 |
February | 0.573134E+09 | 0.710978E+09 | 0.683689E+09 | 0.329669E+09 | 0.354020E+09 | 0.00 | 0.00 |
March | 0.957842E+09 | 0.574922E+09 | 0.923897E+09 | 0.519132E+09 | 0.404765E+09 | 0.00 | 0.00 |
April | 0.807234E+09 | 0.431853E+09 | 0.740450E+09 | 0.295886E+09 | 0.444564E+09 | 0.00 | 0.00 |
May | 0.783026E+09 | 0.306895E+09 | 0.669559E+09 | 0.194468E+09 | 0.475091E+09 | 0.00 | 0.00 |
June | 0.810131E+09 | 0.192884E+09 | 0.629608E+09 | 0.133417E+09 | 0.496191E+09 | 0.00 | 0.00 |
July | 0.944016E+09 | 0.132968E+09 | 0.664152E+09 | 0.161145E+09 | 0.503007E+09 | 0.00 | 0.00 |
August | 0.103711E+10 | 0.177665E+09 | 0.745620E+09 | 0.241749E+09 | 0.503871E+09 | 0.00 | 0.00 |
September | 0.107538E+10 | 0.281722E+09 | 0.838969E+09 | 0.408640E+09 | 0.430329E+09 | 0.00 | 0.00 |
October | 0.934905E+09 | 0.438699E+09 | 0.829528E+09 | 0.473842E+09 | 0.355685E+09 | 0.00 | 0.00 |
November | 0.570931E+09 | 0.537315E+09 | 0.574926E+09 | 0.324565E+09 | 0.250361E+09 | 0.00 | 0.00 |
December | 0.443438E+09 | 0.799076E+09 | 0.554371E+09 | 0.286912E+09 | 0.267459E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.949750E+10 | 0.539793E+10 | 0.851774E+10 | 0.375642E+10 | 0.476132E+10 | 0.00 | 0.00 |
Minimum of Months | 0.443438E+09 | 0.132968E+09 | 0.554371E+09 | 0.133417E+09 | 0.250361E+09 | 0.00 | 0.00 |
Maximum of Months | 0.107538E+10 | 0.812951E+09 | 0.923897E+09 | 0.519132E+09 | 0.503871E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.560495E+09 | 0.793358E+09 | 0.661606E+09 | 0.386199E+09 | 0.275407E+09 | 0.00 | 0.00 |
February | 0.573176E+09 | 0.693571E+09 | 0.682286E+09 | 0.328992E+09 | 0.353294E+09 | 0.00 | 0.00 |
March | 0.957443E+09 | 0.560110E+09 | 0.922002E+09 | 0.518067E+09 | 0.403935E+09 | 0.00 | 0.00 |
April | 0.808334E+09 | 0.417797E+09 | 0.738931E+09 | 0.295279E+09 | 0.443652E+09 | 0.00 | 0.00 |
May | 0.784306E+09 | 0.301358E+09 | 0.668185E+09 | 0.194069E+09 | 0.474116E+09 | 0.00 | 0.00 |
June | 0.807091E+09 | 0.200143E+09 | 0.628317E+09 | 0.133143E+09 | 0.495173E+09 | 0.00 | 0.00 |
July | 0.938349E+09 | 0.144104E+09 | 0.662790E+09 | 0.160814E+09 | 0.501975E+09 | 0.00 | 0.00 |
August | 0.103286E+10 | 0.188669E+09 | 0.744090E+09 | 0.241253E+09 | 0.502838E+09 | 0.00 | 0.00 |
September | 0.107330E+10 | 0.287244E+09 | 0.837248E+09 | 0.407802E+09 | 0.429446E+09 | 0.00 | 0.00 |
October | 0.936386E+09 | 0.426134E+09 | 0.827826E+09 | 0.472870E+09 | 0.354956E+09 | 0.00 | 0.00 |
November | 0.572079E+09 | 0.520934E+09 | 0.573747E+09 | 0.323899E+09 | 0.249848E+09 | 0.00 | 0.00 |
December | 0.443778E+09 | 0.779627E+09 | 0.553234E+09 | 0.286324E+09 | 0.266910E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.948760E+10 | 0.531305E+10 | 0.850026E+10 | 0.374871E+10 | 0.475155E+10 | 0.00 | 0.00 |
Minimum of Months | 0.443778E+09 | 0.144104E+09 | 0.553234E+09 | 0.133143E+09 | 0.249848E+09 | 0.00 | 0.00 |
Maximum of Months | 0.107330E+10 | 0.793358E+09 | 0.922002E+09 | 0.518067E+09 | 0.502838E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.561484E+09 | 0.785454E+09 | 0.661606E+09 | 0.386199E+09 | 0.275407E+09 | 0.00 | 0.00 |
February | 0.574248E+09 | 0.686905E+09 | 0.682286E+09 | 0.328992E+09 | 0.353294E+09 | 0.00 | 0.00 |
March | 0.958997E+09 | 0.553821E+09 | 0.922002E+09 | 0.518067E+09 | 0.403935E+09 | 0.00 | 0.00 |
April | 0.810429E+09 | 0.411186E+09 | 0.738931E+09 | 0.295279E+09 | 0.443652E+09 | 0.00 | 0.00 |
May | 0.787272E+09 | 0.295397E+09 | 0.668185E+09 | 0.194069E+09 | 0.474116E+09 | 0.00 | 0.00 |
June | 0.807552E+09 | 0.199261E+09 | 0.628317E+09 | 0.133143E+09 | 0.495173E+09 | 0.00 | 0.00 |
July | 0.938298E+09 | 0.144324E+09 | 0.662790E+09 | 0.160814E+09 | 0.501975E+09 | 0.00 | 0.00 |
August | 0.103286E+10 | 0.188770E+09 | 0.744090E+09 | 0.241253E+09 | 0.502838E+09 | 0.00 | 0.00 |
September | 0.107385E+10 | 0.285639E+09 | 0.837248E+09 | 0.407802E+09 | 0.429446E+09 | 0.00 | 0.00 |
October | 0.938713E+09 | 0.419345E+09 | 0.827826E+09 | 0.472870E+09 | 0.354956E+09 | 0.00 | 0.00 |
November | 0.573519E+09 | 0.514008E+09 | 0.573747E+09 | 0.323899E+09 | 0.249848E+09 | 0.00 | 0.00 |
December | 0.444667E+09 | 0.771914E+09 | 0.553234E+09 | 0.286324E+09 | 0.266910E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.950188E+10 | 0.525602E+10 | 0.850026E+10 | 0.374871E+10 | 0.475155E+10 | 0.00 | 0.00 |
Minimum of Months | 0.444667E+09 | 0.144324E+09 | 0.553234E+09 | 0.133143E+09 | 0.249848E+09 | 0.00 | 0.00 |
Maximum of Months | 0.107385E+10 | 0.785454E+09 | 0.922002E+09 | 0.518067E+09 | 0.502838E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.562802E+09 | 0.778694E+09 | 0.661606E+09 | 0.386199E+09 | 0.275407E+09 | 0.00 | 0.00 |
February | 0.575718E+09 | 0.681153E+09 | 0.682286E+09 | 0.328992E+09 | 0.353294E+09 | 0.00 | 0.00 |
March | 0.961198E+09 | 0.547977E+09 | 0.922002E+09 | 0.518067E+09 | 0.403935E+09 | 0.00 | 0.00 |
April | 0.813158E+09 | 0.405125E+09 | 0.738931E+09 | 0.295279E+09 | 0.443652E+09 | 0.00 | 0.00 |
May | 0.791811E+09 | 0.288155E+09 | 0.668185E+09 | 0.194069E+09 | 0.474116E+09 | 0.00 | 0.00 |
June | 0.809184E+09 | 0.196539E+09 | 0.628317E+09 | 0.133143E+09 | 0.495173E+09 | 0.00 | 0.00 |
July | 0.939366E+09 | 0.142249E+09 | 0.662790E+09 | 0.160814E+09 | 0.501975E+09 | 0.00 | 0.00 |
August | 0.103380E+10 | 0.186534E+09 | 0.744090E+09 | 0.241253E+09 | 0.502838E+09 | 0.00 | 0.00 |
September | 0.107522E+10 | 0.282433E+09 | 0.837248E+09 | 0.407802E+09 | 0.429446E+09 | 0.00 | 0.00 |
October | 0.941621E+09 | 0.412911E+09 | 0.827826E+09 | 0.472870E+09 | 0.354956E+09 | 0.00 | 0.00 |
November | 0.575191E+09 | 0.508036E+09 | 0.573747E+09 | 0.323899E+09 | 0.249848E+09 | 0.00 | 0.00 |
December | 0.445824E+09 | 0.765077E+09 | 0.553234E+09 | 0.286324E+09 | 0.266910E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.952489E+10 | 0.519488E+10 | 0.850026E+10 | 0.374871E+10 | 0.475155E+10 | 0.00 | 0.00 |
Minimum of Months | 0.445824E+09 | 0.142249E+09 | 0.553234E+09 | 0.133143E+09 | 0.249848E+09 | 0.00 | 0.00 |
Maximum of Months | 0.107522E+10 | 0.778694E+09 | 0.922002E+09 | 0.518067E+09 | 0.502838E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.113658E+10 | 0.151206E+10 | 0.132321E+10 | 0.772398E+09 | 0.550814E+09 | 0.00 | 0.00 |
February | 0.116544E+10 | 0.132231E+10 | 0.136457E+10 | 0.657985E+09 | 0.706588E+09 | 0.00 | 0.00 |
March | 0.193856E+10 | 0.106198E+10 | 0.184400E+10 | 0.103613E+10 | 0.807869E+09 | 0.00 | 0.00 |
April | 0.163966E+10 | 0.780456E+09 | 0.147786E+10 | 0.590558E+09 | 0.887304E+09 | 0.00 | 0.00 |
May | 0.160035E+10 | 0.547238E+09 | 0.133637E+10 | 0.388138E+09 | 0.948232E+09 | 0.00 | 0.00 |
June | 0.162327E+10 | 0.378293E+09 | 0.125663E+10 | 0.266287E+09 | 0.990346E+09 | 0.00 | 0.00 |
July | 0.187957E+10 | 0.272034E+09 | 0.132558E+10 | 0.321629E+09 | 0.100395E+10 | 0.00 | 0.00 |
August | 0.206835E+10 | 0.359426E+09 | 0.148818E+10 | 0.482506E+09 | 0.100568E+10 | 0.00 | 0.00 |
September | 0.215457E+10 | 0.549242E+09 | 0.167450E+10 | 0.815604E+09 | 0.858891E+09 | 0.00 | 0.00 |
October | 0.189531E+10 | 0.799334E+09 | 0.165565E+10 | 0.945740E+09 | 0.709912E+09 | 0.00 | 0.00 |
November | 0.116019E+10 | 0.984866E+09 | 0.114749E+10 | 0.647799E+09 | 0.499695E+09 | 0.00 | 0.00 |
December | 0.901638E+09 | 0.148464E+10 | 0.110647E+10 | 0.572648E+09 | 0.533821E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.191635E+11 | 0.100519E+11 | 0.170005E+11 | 0.749743E+10 | 0.950310E+10 | 0.00 | 0.00 |
Minimum of Months | 0.901638E+09 | 0.272034E+09 | 0.110647E+10 | 0.266287E+09 | 0.499695E+09 | 0.00 | 0.00 |
Maximum of Months | 0.215457E+10 | 0.151206E+10 | 0.184400E+10 | 0.103613E+10 | 0.100568E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.565364E+09 | 0.761552E+09 | 0.661606E+09 | 0.386199E+09 | 0.275407E+09 | 0.00 | 0.00 |
February | 0.579078E+09 | 0.666241E+09 | 0.682286E+09 | 0.328992E+09 | 0.353294E+09 | 0.00 | 0.00 |
March | 0.966007E+09 | 0.532763E+09 | 0.922002E+09 | 0.518067E+09 | 0.403935E+09 | 0.00 | 0.00 |
April | 0.818033E+09 | 0.390270E+09 | 0.738931E+09 | 0.295279E+09 | 0.443652E+09 | 0.00 | 0.00 |
May | 0.800419E+09 | 0.271293E+09 | 0.668185E+09 | 0.194069E+09 | 0.474116E+09 | 0.00 | 0.00 |
June | 0.811521E+09 | 0.187563E+09 | 0.628317E+09 | 0.133143E+09 | 0.495173E+09 | 0.00 | 0.00 |
July | 0.939985E+09 | 0.134204E+09 | 0.662790E+09 | 0.160814E+09 | 0.501975E+09 | 0.00 | 0.00 |
August | 0.103392E+10 | 0.177887E+09 | 0.744090E+09 | 0.241253E+09 | 0.502838E+09 | 0.00 | 0.00 |
September | 0.107639E+10 | 0.273200E+09 | 0.837248E+09 | 0.407802E+09 | 0.429446E+09 | 0.00 | 0.00 |
October | 0.946287E+09 | 0.398743E+09 | 0.827826E+09 | 0.472870E+09 | 0.354956E+09 | 0.00 | 0.00 |
November | 0.578419E+09 | 0.493872E+09 | 0.573747E+09 | 0.323899E+09 | 0.249848E+09 | 0.00 | 0.00 |
December | 0.448176E+09 | 0.747927E+09 | 0.553234E+09 | 0.286324E+09 | 0.266910E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.956360E+10 | 0.503551E+10 | 0.850026E+10 | 0.374871E+10 | 0.475155E+10 | 0.00 | 0.00 |
Minimum of Months | 0.448176E+09 | 0.134204E+09 | 0.553234E+09 | 0.133143E+09 | 0.249848E+09 | 0.00 | 0.00 |
Maximum of Months | 0.107639E+10 | 0.761552E+09 | 0.922002E+09 | 0.518067E+09 | 0.502838E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.565667E+09 | 0.759970E+09 | 0.661606E+09 | 0.386199E+09 | 0.275407E+09 | 0.00 | 0.00 |
February | 0.579406E+09 | 0.664982E+09 | 0.682286E+09 | 0.328992E+09 | 0.353294E+09 | 0.00 | 0.00 |
March | 0.966778E+09 | 0.530669E+09 | 0.922002E+09 | 0.518067E+09 | 0.403935E+09 | 0.00 | 0.00 |
April | 0.819143E+09 | 0.387790E+09 | 0.738931E+09 | 0.295279E+09 | 0.443652E+09 | 0.00 | 0.00 |
May | 0.802958E+09 | 0.267795E+09 | 0.668185E+09 | 0.194069E+09 | 0.474116E+09 | 0.00 | 0.00 |
June | 0.812798E+09 | 0.186045E+09 | 0.628317E+09 | 0.133143E+09 | 0.495173E+09 | 0.00 | 0.00 |
July | 0.940624E+09 | 0.133392E+09 | 0.662790E+09 | 0.160814E+09 | 0.501975E+09 | 0.00 | 0.00 |
August | 0.103446E+10 | 0.177021E+09 | 0.744090E+09 | 0.241253E+09 | 0.502838E+09 | 0.00 | 0.00 |
September | 0.107720E+10 | 0.271691E+09 | 0.837248E+09 | 0.407802E+09 | 0.429446E+09 | 0.00 | 0.00 |
October | 0.947476E+09 | 0.396237E+09 | 0.827826E+09 | 0.472870E+09 | 0.354956E+09 | 0.00 | 0.00 |
November | 0.579013E+09 | 0.491792E+09 | 0.573747E+09 | 0.323899E+09 | 0.249848E+09 | 0.00 | 0.00 |
December | 0.448455E+09 | 0.746283E+09 | 0.553234E+09 | 0.286324E+09 | 0.266910E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.957398E+10 | 0.501367E+10 | 0.850026E+10 | 0.374871E+10 | 0.475155E+10 | 0.00 | 0.00 |
Minimum of Months | 0.448455E+09 | 0.133392E+09 | 0.553234E+09 | 0.133143E+09 | 0.249848E+09 | 0.00 | 0.00 |
Maximum of Months | 0.107720E+10 | 0.759970E+09 | 0.922002E+09 | 0.518067E+09 | 0.502838E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.567140E+09 | 0.751058E+09 | 0.661606E+09 | 0.386199E+09 | 0.275407E+09 | 0.00 | 0.00 |
February | 0.581006E+09 | 0.657706E+09 | 0.682286E+09 | 0.328992E+09 | 0.353294E+09 | 0.00 | 0.00 |
March | 0.969535E+09 | 0.521827E+09 | 0.922002E+09 | 0.518067E+09 | 0.403935E+09 | 0.00 | 0.00 |
April | 0.822319E+09 | 0.379295E+09 | 0.738931E+09 | 0.295279E+09 | 0.443652E+09 | 0.00 | 0.00 |
May | 0.808739E+09 | 0.259070E+09 | 0.668185E+09 | 0.194069E+09 | 0.474116E+09 | 0.00 | 0.00 |
June | 0.815998E+09 | 0.181795E+09 | 0.628317E+09 | 0.133143E+09 | 0.495173E+09 | 0.00 | 0.00 |
July | 0.941804E+09 | 0.131378E+09 | 0.662790E+09 | 0.160814E+09 | 0.501975E+09 | 0.00 | 0.00 |
August | 0.103547E+10 | 0.174904E+09 | 0.744090E+09 | 0.241253E+09 | 0.502838E+09 | 0.00 | 0.00 |
September | 0.107925E+10 | 0.267440E+09 | 0.837248E+09 | 0.407802E+09 | 0.429446E+09 | 0.00 | 0.00 |
October | 0.950204E+09 | 0.389559E+09 | 0.827826E+09 | 0.472870E+09 | 0.354956E+09 | 0.00 | 0.00 |
November | 0.580843E+09 | 0.484432E+09 | 0.573747E+09 | 0.323899E+09 | 0.249848E+09 | 0.00 | 0.00 |
December | 0.449732E+09 | 0.737591E+09 | 0.553234E+09 | 0.286324E+09 | 0.266910E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.960204E+10 | 0.493605E+10 | 0.850026E+10 | 0.374871E+10 | 0.475155E+10 | 0.00 | 0.00 |
Minimum of Months | 0.449732E+09 | 0.131378E+09 | 0.553234E+09 | 0.133143E+09 | 0.249848E+09 | 0.00 | 0.00 |
Maximum of Months | 0.107925E+10 | 0.751058E+09 | 0.922002E+09 | 0.518067E+09 | 0.502838E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.573690E+09 | 0.711734E+09 | 0.661606E+09 | 0.386199E+09 | 0.275407E+09 | 0.00 | 0.00 |
February | 0.588204E+09 | 0.624218E+09 | 0.682286E+09 | 0.328992E+09 | 0.353294E+09 | 0.00 | 0.00 |
March | 0.979543E+09 | 0.485115E+09 | 0.922002E+09 | 0.518067E+09 | 0.403935E+09 | 0.00 | 0.00 |
April | 0.831591E+09 | 0.347105E+09 | 0.738931E+09 | 0.295279E+09 | 0.443652E+09 | 0.00 | 0.00 |
May | 0.821113E+09 | 0.233252E+09 | 0.668185E+09 | 0.194069E+09 | 0.474116E+09 | 0.00 | 0.00 |
June | 0.823733E+09 | 0.167191E+09 | 0.628317E+09 | 0.133143E+09 | 0.495173E+09 | 0.00 | 0.00 |
July | 0.943953E+09 | 0.123723E+09 | 0.662790E+09 | 0.160814E+09 | 0.501975E+09 | 0.00 | 0.00 |
August | 0.103719E+10 | 0.166777E+09 | 0.744090E+09 | 0.241253E+09 | 0.502838E+09 | 0.00 | 0.00 |
September | 0.108373E+10 | 0.253294E+09 | 0.837248E+09 | 0.407802E+09 | 0.429446E+09 | 0.00 | 0.00 |
October | 0.956324E+09 | 0.368234E+09 | 0.827826E+09 | 0.472870E+09 | 0.354956E+09 | 0.00 | 0.00 |
November | 0.586606E+09 | 0.456797E+09 | 0.573747E+09 | 0.323899E+09 | 0.249848E+09 | 0.00 | 0.00 |
December | 0.455263E+09 | 0.699179E+09 | 0.553234E+09 | 0.286324E+09 | 0.266910E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.968093E+10 | 0.463662E+10 | 0.850026E+10 | 0.374871E+10 | 0.475155E+10 | 0.00 | 0.00 |
Minimum of Months | 0.455263E+09 | 0.123723E+09 | 0.553234E+09 | 0.133143E+09 | 0.249848E+09 | 0.00 | 0.00 |
Maximum of Months | 0.108373E+10 | 0.711734E+09 | 0.922002E+09 | 0.518067E+09 | 0.502838E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -3.4 | -4.9 | -8.7 | 5.96 | -14.4 | 41.15 | 62.17 | 0.00 |
February | -4.2 | -5.4 | -8.1 | 6.66 | -15.1 | 65.72 | 71.39 | 0.00 |
March | 2.67 | 0.66 | -2.8 | 5.20 | -8.9 | 69.76 | 141.76 | 0.00 |
April | 7.47 | 4.95 | 1.92 | 5.29 | -2.7 | 89.32 | 159.79 | 0.00 |
May | 13.73 | 9.66 | 5.81 | 4.79 | 3.34 | 93.75 | 203.34 | 0.03 |
June | 18.63 | 14.47 | 11.49 | 5.10 | 8.69 | 105.42 | 236.95 | 0.00 |
July | 22.03 | 18.19 | 16.11 | 4.43 | 13.39 | 102.98 | 214.28 | 0.00 |
August | 20.69 | 16.39 | 13.72 | 4.23 | 11.88 | 99.24 | 178.64 | 0.00 |
September | 16.55 | 13.42 | 11.22 | 4.10 | 7.08 | 75.66 | 154.97 | 0.03 |
October | 9.73 | 7.36 | 4.97 | 4.79 | 0.13 | 58.70 | 104.01 | 0.00 |
November | 6.03 | 3.70 | 0.77 | 5.87 | -3.2 | 41.19 | 58.47 | 0.00 |
December | -2.2 | -3.2 | -5.3 | 6.59 | -12.0 | 40.52 | 44.30 | 0.00 |
Annual Sum or Average | 9.05 | 6.33 | 3.49 | 5.24 | -0.9 | 73.64 | 136.19 | 0.01 |
Minimum of Months | -4.2 | -5.4 | -8.7 | 4.10 | -15.1 | 40.52 | 44.30 | 0.00 |
Maximum of Months | 22.03 | 18.19 | 16.11 | 6.66 | 13.39 | 105.42 | 236.95 | 0.03 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 11.70 | 11-JAN-15:00 | 10.14 | 8.90 | 13.40 | 7.15 | 65.50 | 1.00 |
February | 12.80 | 22-FEB-17:00 | 6.18 | -2.2 | 14.90 | 3.48 | 0.00 | 0.00 |
March | 26.10 | 15-MAR-13:00 | 16.06 | 9.40 | 6.70 | 14.65 | 249.50 | 400.00 |
April | 21.10 | 08-APR-12:00 | 13.43 | 7.80 | 8.20 | 11.46 | 330.00 | 283.50 |
May | 26.10 | 10-MAY-13:00 | 17.84 | 13.30 | 5.20 | 13.35 | 258.50 | 457.00 |
June | 30.60 | 12-JUN-13:00 | 20.23 | 15.00 | 8.20 | 17.93 | 252.00 | 572.00 |
July | 31.70 | 21-JUL-13:00 | 21.73 | 17.20 | 5.20 | 22.47 | 330.00 | 231.00 |
August | 30.60 | 10-AUG-13:00 | 20.24 | 15.00 | 5.70 | 19.70 | 220.50 | 635.00 |
September | 27.20 | 16-SEP-13:09 | 19.53 | 15.68 | 8.80 | 17.30 | 207.00 | 564.67 |
October | 22.20 | 11-OCT-12:00 | 14.14 | 8.30 | 6.20 | 6.95 | 121.00 | 665.00 |
November | 19.40 | 05-NOV-13:00 | 13.85 | 10.00 | 12.40 | 14.84 | 133.00 | 3.50 |
December | 15.00 | 01-DEC-10:00 | 12.41 | 10.60 | 12.90 | 10.69 | 56.50 | 11.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 11.70 | 6.18 | -2.2 | 5.20 | 3.48 | 0.00 | 0.00 | |
Maximum of Months | 31.70 | 21.73 | 17.20 | 14.90 | 22.47 | 330.00 | 665.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -13.9 | 31-JAN-01:00 | -14.5 | -17.2 | 1.50 | -25.9 | 0.00 | 0.00 |
February | -16.7 | 07-FEB-06:00 | -17.3 | -20.6 | 6.20 | -35.1 | 0.00 | 0.00 |
March | -13.3 | 07-MAR-05:19 | -13.9 | -16.7 | 2.43 | -32.2 | 0.00 | 0.00 |
April | -4.4 | 17-APR-05:00 | -5.4 | -7.8 | 2.10 | -20.5 | 35.00 | 151.50 |
May | 1.70 | 01-MAY-04:00 | 0.96 | 0.00 | 0.00 | -14.2 | 0.00 | 0.00 |
June | 6.70 | 04-JUN-04:00 | 5.40 | 3.90 | 2.10 | -7.3 | 20.00 | 104.00 |
July | 11.70 | 03-JUL-03:00 | 11.07 | 10.60 | 2.10 | -1.2 | 0.00 | 0.00 |
August | 11.10 | 01-AUG-04:00 | 10.75 | 10.60 | 2.10 | -0.8 | 0.00 | 0.00 |
September | 6.10 | 05-SEP-05:00 | 5.59 | 5.00 | 2.10 | -6.2 | 24.50 | 41.00 |
October | -2.8 | 17-OCT-04:10 | -3.2 | -4.0 | 2.18 | -19.4 | 0.00 | 0.00 |
November | -3.9 | 24-NOV-05:00 | -4.5 | -5.6 | 2.10 | -18.1 | 0.00 | 0.00 |
December | -18.9 | 11-DEC-05:00 | -19.4 | -23.3 | 2.10 | -35.1 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -18.9 | -19.4 | -23.3 | 0.00 | -35.1 | 0.00 | 0.00 | |
Maximum of Months | 11.70 | 11.07 | 10.60 | 6.20 | -0.8 | 35.00 | 151.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.21 | 11-JAN-17:00 | 11.10 | 9.40 | 10.30 | 6.55 | 0.00 | 0.00 |
February | 6.89 | 01-FEB-03:00 | 7.20 | 6.70 | 3.60 | 2.22 | 0.00 | 0.00 |
March | 17.83 | 14-MAR-12:00 | 25.00 | 13.90 | 6.20 | 14.10 | 197.00 | 562.50 |
April | 13.78 | 08-APR-13:00 | 20.60 | 8.90 | 10.30 | 9.72 | 268.50 | 325.50 |
May | 18.19 | 10-MAY-14:00 | 26.10 | 13.90 | 5.20 | 16.85 | 273.00 | 238.00 |
June | 23.75 | 27-JUN-12:00 | 30.60 | 21.10 | 9.30 | 21.09 | 304.00 | 606.00 |
July | 24.79 | 21-JUL-01:00 | 28.90 | 23.30 | 8.80 | 27.46 | 0.00 | 0.00 |
August | 23.42 | 13-AUG-15:00 | 29.40 | 21.10 | 9.80 | 19.87 | 212.00 | 276.00 |
September | 21.17 | 15-SEP-11:00 | 26.10 | 18.90 | 3.60 | 16.30 | 204.00 | 464.50 |
October | 15.23 | 12-OCT-14:00 | 18.30 | 13.30 | 10.30 | 9.13 | 148.00 | 367.50 |
November | 13.96 | 05-NOV-14:00 | 18.30 | 11.10 | 11.30 | 14.10 | 72.00 | 6.00 |
December | 12.41 | 01-DEC-10:00 | 15.00 | 10.60 | 12.90 | 10.69 | 56.50 | 11.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.89 | 7.20 | 6.70 | 3.60 | 2.22 | 0.00 | 0.00 | |
Maximum of Months | 24.79 | 30.60 | 23.30 | 12.90 | 27.46 | 304.00 | 606.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 9.40 | 11-JAN-13:00 | 10.00 | 9.66 | 12.90 | 5.54 | 95.50 | 2.00 |
February | 6.70 | 01-FEB-04:10 | 7.20 | 6.89 | 3.52 | 2.22 | 0.00 | 0.00 |
March | 15.00 | 14-MAR-10:20 | 20.33 | 16.97 | 4.80 | 10.50 | 159.17 | 592.83 |
April | 11.10 | 08-APR-21:00 | 13.90 | 12.23 | 12.90 | 9.72 | 0.00 | 0.00 |
May | 15.60 | 17-MAY-12:00 | 16.70 | 15.97 | 6.70 | 13.54 | 184.00 | 0.00 |
June | 21.70 | 27-JUN-14:00 | 25.60 | 22.78 | 8.20 | 16.85 | 255.50 | 530.00 |
July | 23.30 | 20-JUL-20:00 | 25.60 | 24.03 | 4.60 | 24.16 | 0.00 | 0.00 |
August | 21.70 | 14-AUG-03:20 | 23.70 | 22.19 | 5.00 | 21.90 | 0.00 | 0.00 |
September | 20.00 | 15-SEP-18:00 | 21.70 | 20.51 | 0.00 | 19.52 | 0.00 | 0.00 |
October | 14.40 | 01-OCT-07:19 | 14.60 | 14.50 | 3.77 | 10.56 | 67.50 | 30.17 |
November | 11.70 | 05-NOV-15:00 | 12.80 | 12.14 | 7.20 | 8.74 | 28.00 | 4.50 |
December | 11.10 | 01-DEC-12:00 | 13.90 | 12.22 | 10.30 | 6.35 | 158.00 | 84.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.70 | 7.20 | 6.89 | 0.00 | 2.22 | 0.00 | 0.00 | |
Maximum of Months | 23.30 | 25.60 | 24.03 | 12.90 | 24.16 | 255.50 | 592.83 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 7.32 | 12.49 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 6.57 | 19.26 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 7.29 | 28.63 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 9.34 | 37.44 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 12.19 | 46.60 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 15.07 | 54.01 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 17.20 | 50.29 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 18.01 | 43.20 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 17.27 | 32.93 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 15.18 | 21.28 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 12.32 | 12.54 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 9.45 | 10.96 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 12.30 | 30.86 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 6.57 | 10.96 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 18.01 | 54.01 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK1
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.379355E+09 | -253685432.8 | 0.00 | 0.00 | 744.00 | 0.00 | -125669661.6 | 58.99 | 0.00 | 0.00 |
February | 0.347518E+09 | -233701026.2 | 0.00 | 0.00 | 672.00 | 0.00 | -113816475.1 | 58.99 | 0.00 | 0.00 |
March | 0.383373E+09 | -259382786.1 | 0.00 | 0.00 | 744.00 | 0.00 | -123989906.6 | 58.99 | 0.00 | 0.00 |
April | 0.356863E+09 | -237980860.0 | 0.00 | 0.00 | 720.00 | 0.00 | -118881755.4 | 58.99 | 0.00 | 0.00 |
May | 0.350120E+09 | -232233212.1 | 0.00 | 0.00 | 744.00 | 0.00 | -117886598.2 | 58.99 | 0.00 | 0.00 |
June | 0.322996E+09 | -213008720.4 | 0.00 | 0.00 | 720.00 | 0.00 | -109987742.5 | 58.99 | 0.00 | 0.00 |
July | 0.317722E+09 | -205138361.9 | 0.00 | 0.00 | 744.00 | 0.00 | -112583850.6 | 58.99 | 0.00 | 0.00 |
August | 0.318106E+09 | -205442420.5 | 0.00 | 0.00 | 744.00 | 0.00 | -112663623.7 | 58.99 | 0.00 | 0.00 |
September | 0.310265E+09 | -200159726.2 | 0.00 | 0.00 | 720.00 | 0.00 | -110104971.2 | 58.99 | 0.00 | 0.00 |
October | 0.335229E+09 | -215144236.0 | 0.00 | 0.00 | 744.00 | 0.00 | -120084989.4 | 58.99 | 0.00 | 0.00 |
November | 0.340297E+09 | -221154929.3 | 0.00 | 0.00 | 720.00 | 0.00 | -119141762.8 | 58.99 | 0.00 | 0.00 |
December | 0.368861E+09 | -243514181.3 | 0.00 | 0.00 | 744.00 | 0.00 | -125346360.7 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.413070E+10 | -0.272055E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.141016E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.310265E+09 | -259382786.1 | 0.00 | 0.00 | 672.00 | 0.00 | -125669661.6 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.383373E+09 | -200159726.2 | 0.00 | 0.00 | 744.00 | 0.00 | -109987742.5 | 58.99 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK2
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.377661E+09 | -253684675.9 | 0.00 | 0.00 | 744.00 | 0.00 | -123975856.9 | 58.99 | 0.00 | 0.00 |
February | 0.345944E+09 | -233700331.6 | 0.00 | 0.00 | 672.00 | 0.00 | -112243626.8 | 58.99 | 0.00 | 0.00 |
March | 0.381236E+09 | -259396438.4 | 0.00 | 0.00 | 744.00 | 0.00 | -121840037.2 | 58.99 | 0.00 | 0.00 |
April | 0.354144E+09 | -237979377.9 | 0.00 | 0.00 | 720.00 | 0.00 | -116164644.3 | 58.99 | 0.00 | 0.00 |
May | 0.347545E+09 | -232223921.8 | 0.00 | 0.00 | 744.00 | 0.00 | -115321167.5 | 58.99 | 0.00 | 0.00 |
June | 0.322413E+09 | -213010778.8 | 0.00 | 0.00 | 720.00 | 0.00 | -109401731.6 | 58.99 | 0.00 | 0.00 |
July | 0.317577E+09 | -205141459.8 | 0.00 | 0.00 | 744.00 | 0.00 | -112435751.9 | 58.99 | 0.00 | 0.00 |
August | 0.317908E+09 | -205440836.0 | 0.00 | 0.00 | 744.00 | 0.00 | -112467008.7 | 58.99 | 0.00 | 0.00 |
September | 0.309560E+09 | -200159044.8 | 0.00 | 0.00 | 720.00 | 0.00 | -109400856.6 | 58.99 | 0.00 | 0.00 |
October | 0.332714E+09 | -215147378.2 | 0.00 | 0.00 | 744.00 | 0.00 | -117566600.1 | 58.99 | 0.00 | 0.00 |
November | 0.338059E+09 | -221152718.6 | 0.00 | 0.00 | 720.00 | 0.00 | -116906240.2 | 58.99 | 0.00 | 0.00 |
December | 0.367084E+09 | -243520487.3 | 0.00 | 0.00 | 744.00 | 0.00 | -123563377.1 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.411184E+10 | -0.272056E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.139129E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.309560E+09 | -259396438.4 | 0.00 | 0.00 | 672.00 | 0.00 | -123975856.9 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.381236E+09 | -200159044.8 | 0.00 | 0.00 | 744.00 | 0.00 | -109400856.6 | 58.99 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK3
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.348798E+09 | -223082815.0 | 0.00 | 0.00 | 744.00 | 0.00 | -125714816.1 | 58.99 | 0.00 | 0.00 |
February | 0.319477E+09 | -205665410.3 | 0.00 | 0.00 | 672.00 | 0.00 | -113811265.8 | 58.99 | 0.00 | 0.00 |
March | 0.354821E+09 | -231506594.2 | 0.00 | 0.00 | 744.00 | 0.00 | -123314497.4 | 58.99 | 0.00 | 0.00 |
April | 0.327087E+09 | -209307478.3 | 0.00 | 0.00 | 720.00 | 0.00 | -117780006.8 | 58.99 | 0.00 | 0.00 |
May | 0.322115E+09 | -205980011.1 | 0.00 | 0.00 | 744.00 | 0.00 | -116134945.8 | 58.99 | 0.00 | 0.00 |
June | 0.298271E+09 | -189703902.1 | 0.00 | 0.00 | 720.00 | 0.00 | -108566853.5 | 58.99 | 0.00 | 0.00 |
July | 0.290249E+09 | -179340142.2 | 0.00 | 0.00 | 744.00 | 0.00 | -110909259.8 | 58.99 | 0.00 | 0.00 |
August | 0.294718E+09 | -183489022.4 | 0.00 | 0.00 | 744.00 | 0.00 | -111228596.7 | 59.00 | 0.00 | 0.00 |
September | 0.284839E+09 | -175886484.2 | 0.00 | 0.00 | 720.00 | 0.00 | -108952758.7 | 59.01 | 0.00 | 0.00 |
October | 0.308262E+09 | -189217924.6 | 0.00 | 0.00 | 744.00 | 0.00 | -119044198.9 | 58.99 | 0.00 | 0.00 |
November | 0.313831E+09 | -195258681.0 | 0.00 | 0.00 | 720.00 | 0.00 | -118571982.7 | 58.99 | 0.00 | 0.00 |
December | 0.337866E+09 | -212553220.9 | 0.00 | 0.00 | 744.00 | 0.00 | -125313156.6 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.380033E+10 | -0.240099E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.139934E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.284839E+09 | -231506594.2 | 0.00 | 0.00 | 672.00 | 0.00 | -125714816.1 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.354821E+09 | -175886484.2 | 0.00 | 0.00 | 744.00 | 0.00 | -108566853.5 | 59.01 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK4
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.349214E+09 | -223087804.2 | 0.00 | 0.00 | 744.00 | 0.00 | -126125733.2 | 58.99 | 0.00 | 0.00 |
February | 0.319831E+09 | -205670976.4 | 0.00 | 0.00 | 672.00 | 0.00 | -114160373.8 | 58.99 | 0.00 | 0.00 |
March | 0.355196E+09 | -231506626.1 | 0.00 | 0.00 | 744.00 | 0.00 | -123689247.0 | 58.99 | 0.00 | 0.00 |
April | 0.327542E+09 | -209314936.5 | 0.00 | 0.00 | 720.00 | 0.00 | -118227111.9 | 58.99 | 0.00 | 0.00 |
May | 0.322622E+09 | -205961409.0 | 0.00 | 0.00 | 744.00 | 0.00 | -116660949.4 | 59.00 | 0.00 | 0.00 |
June | 0.298333E+09 | -189702869.0 | 0.00 | 0.00 | 720.00 | 0.00 | -108630404.0 | 58.99 | 0.00 | 0.00 |
July | 0.290235E+09 | -179332834.3 | 0.00 | 0.00 | 744.00 | 0.00 | -110902125.8 | 58.99 | 0.00 | 0.00 |
August | 0.294699E+09 | -183519040.8 | 0.00 | 0.00 | 744.00 | 0.00 | -111180096.0 | 58.98 | 0.00 | 0.00 |
September | 0.284947E+09 | -175953768.5 | 0.00 | 0.00 | 720.00 | 0.00 | -108993527.6 | 58.98 | 0.00 | 0.00 |
October | 0.308752E+09 | -189218548.0 | 0.00 | 0.00 | 744.00 | 0.00 | -119533680.2 | 58.99 | 0.00 | 0.00 |
November | 0.314227E+09 | -195277847.9 | 0.00 | 0.00 | 720.00 | 0.00 | -118949113.5 | 58.98 | 0.00 | 0.00 |
December | 0.338263E+09 | -212564281.3 | 0.00 | 0.00 | 744.00 | 0.00 | -125698854.1 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.380386E+10 | -0.240111E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.140275E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.284947E+09 | -231506626.1 | 0.00 | 0.00 | 672.00 | 0.00 | -126125733.2 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.355196E+09 | -175953768.5 | 0.00 | 0.00 | 744.00 | 0.00 | -108630404.0 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK5
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.338643E+09 | -210854058.0 | 0.00 | 0.00 | 744.00 | 0.00 | -127788453.9 | 58.99 | 0.00 | 0.00 |
February | 0.310178E+09 | -194487648.2 | 0.00 | 0.00 | 672.00 | 0.00 | -115690322.2 | 58.99 | 0.00 | 0.00 |
March | 0.344262E+09 | -219054741.4 | 0.00 | 0.00 | 744.00 | 0.00 | -125207709.7 | 58.99 | 0.00 | 0.00 |
April | 0.317829E+09 | -198055211.1 | 0.00 | 0.00 | 720.00 | 0.00 | -119773913.2 | 59.00 | 0.00 | 0.00 |
May | 0.313479E+09 | -194801410.5 | 0.00 | 0.00 | 744.00 | 0.00 | -118677407.9 | 58.99 | 0.00 | 0.00 |
June | 0.288981E+09 | -179493174.1 | 0.00 | 0.00 | 720.00 | 0.00 | -109487390.3 | 59.00 | 0.00 | 0.00 |
July | 0.281155E+09 | -169614282.4 | 0.00 | 0.00 | 744.00 | 0.00 | -111540260.3 | 58.98 | 0.00 | 0.00 |
August | 0.285502E+09 | -173629877.5 | 0.00 | 0.00 | 744.00 | 0.00 | -111872364.1 | 58.99 | 0.00 | 0.00 |
September | 0.276330E+09 | -166479354.2 | 0.00 | 0.00 | 720.00 | 0.00 | -109850325.3 | 58.99 | 0.00 | 0.00 |
October | 0.299925E+09 | -178840841.7 | 0.00 | 0.00 | 744.00 | 0.00 | -121083764.2 | 58.99 | 0.00 | 0.00 |
November | 0.304670E+09 | -184425204.9 | 0.00 | 0.00 | 720.00 | 0.00 | -120245003.3 | 58.99 | 0.00 | 0.00 |
December | 0.328334E+09 | -201026519.1 | 0.00 | 0.00 | 744.00 | 0.00 | -127307278.1 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.368929E+10 | -0.227076E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.141852E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.276330E+09 | -219054741.4 | 0.00 | 0.00 | 672.00 | 0.00 | -127788453.9 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.344262E+09 | -166479354.2 | 0.00 | 0.00 | 744.00 | 0.00 | -109487390.3 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK6
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.338516E+09 | -210850417.9 | 0.00 | 0.00 | 744.00 | 0.00 | -127665920.9 | 58.99 | 0.00 | 0.00 |
February | 0.310071E+09 | -194481862.1 | 0.00 | 0.00 | 672.00 | 0.00 | -115589334.3 | 59.00 | 0.00 | 0.00 |
March | 0.344236E+09 | -219045586.5 | 0.00 | 0.00 | 744.00 | 0.00 | -125189941.1 | 58.99 | 0.00 | 0.00 |
April | 0.317887E+09 | -198067165.5 | 0.00 | 0.00 | 720.00 | 0.00 | -119820200.0 | 58.99 | 0.00 | 0.00 |
May | 0.313709E+09 | -194800928.0 | 0.00 | 0.00 | 744.00 | 0.00 | -118908198.7 | 58.99 | 0.00 | 0.00 |
June | 0.289083E+09 | -179491801.7 | 0.00 | 0.00 | 720.00 | 0.00 | -109591129.8 | 59.00 | 0.00 | 0.00 |
July | 0.281258E+09 | -169616161.4 | 0.00 | 0.00 | 744.00 | 0.00 | -111641998.6 | 58.98 | 0.00 | 0.00 |
August | 0.285592E+09 | -173637295.0 | 0.00 | 0.00 | 744.00 | 0.00 | -111954541.0 | 58.99 | 0.00 | 0.00 |
September | 0.276408E+09 | -166467078.8 | 0.00 | 0.00 | 720.00 | 0.00 | -109940942.5 | 59.00 | 0.00 | 0.00 |
October | 0.300041E+09 | -178839444.4 | 0.00 | 0.00 | 744.00 | 0.00 | -121201965.5 | 58.99 | 0.00 | 0.00 |
November | 0.304694E+09 | -184407756.5 | 0.00 | 0.00 | 720.00 | 0.00 | -120285762.2 | 59.00 | 0.00 | 0.00 |
December | 0.328222E+09 | -201044396.4 | 0.00 | 0.00 | 744.00 | 0.00 | -127177436.0 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.368972E+10 | -0.227075E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.141897E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.276408E+09 | -219045586.5 | 0.00 | 0.00 | 672.00 | 0.00 | -127665920.9 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.344236E+09 | -166467078.8 | 0.00 | 0.00 | 744.00 | 0.00 | -109591129.8 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK7
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.338598E+09 | -210852958.5 | 0.00 | 0.00 | 744.00 | 0.00 | -127744689.6 | 58.99 | 0.00 | 0.00 |
February | 0.310134E+09 | -194483628.4 | 0.00 | 0.00 | 672.00 | 0.00 | -115650357.7 | 59.00 | 0.00 | 0.00 |
March | 0.344358E+09 | -219054666.3 | 0.00 | 0.00 | 744.00 | 0.00 | -125303488.1 | 58.99 | 0.00 | 0.00 |
April | 0.318054E+09 | -198064774.2 | 0.00 | 0.00 | 720.00 | 0.00 | -119989661.1 | 58.99 | 0.00 | 0.00 |
May | 0.314047E+09 | -194792826.2 | 0.00 | 0.00 | 744.00 | 0.00 | -119253839.6 | 58.99 | 0.00 | 0.00 |
June | 0.289200E+09 | -179510076.0 | 0.00 | 0.00 | 720.00 | 0.00 | -109689942.3 | 58.99 | 0.00 | 0.00 |
July | 0.281329E+09 | -169599369.1 | 0.00 | 0.00 | 744.00 | 0.00 | -111729748.8 | 58.99 | 0.00 | 0.00 |
August | 0.285656E+09 | -173624533.7 | 0.00 | 0.00 | 744.00 | 0.00 | -112031243.4 | 58.99 | 0.00 | 0.00 |
September | 0.276528E+09 | -166463630.8 | 0.00 | 0.00 | 720.00 | 0.00 | -110064802.6 | 59.00 | 0.00 | 0.00 |
October | 0.300228E+09 | -178827862.1 | 0.00 | 0.00 | 744.00 | 0.00 | -121400015.1 | 59.00 | 0.00 | 0.00 |
November | 0.304807E+09 | -184405747.5 | 0.00 | 0.00 | 720.00 | 0.00 | -120401702.1 | 59.00 | 0.00 | 0.00 |
December | 0.328311E+09 | -201034869.4 | 0.00 | 0.00 | 744.00 | 0.00 | -127275851.9 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.369125E+10 | -0.227071E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.142054E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.276528E+09 | -219054666.3 | 0.00 | 0.00 | 672.00 | 0.00 | -127744689.6 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.344358E+09 | -166463630.8 | 0.00 | 0.00 | 744.00 | 0.00 | -109689942.3 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 255.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 262.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 339.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 371.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 332.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 430.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 439.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 406.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 289.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 314.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 258.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 230.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3928.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 230.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 439.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 HEATING COIL
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.260556E+11 | 59694.63 | 01-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.245666E+11 | 59694.63 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.151647E+11 | 59694.63 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.646709E+10 | 59694.63 | 01-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.384188E+09 | 59694.63 | 01-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6538320.82 | 3602.69 | 30-SEP-08:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.299276E+10 | 59694.63 | 16-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.912661E+10 | 59694.63 | 03-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.240937E+11 | 59694.63 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.108858E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.260556E+11 | 59694.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 HEATING COIL
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.908093E+10 | 31272.07 | 01-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.854519E+10 | 31272.07 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.477898E+10 | 31272.07 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.154913E+10 | 31272.07 | 01-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 15020719.84 | 2179.65 | 01-MAY-08:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.549187E+09 | 28336.95 | 30-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.255984E+10 | 31272.07 | 21-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.831584E+10 | 31272.07 | 02-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.353941E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.908093E+10 | 31272.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3 HEATING COIL
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.103081E+11 | 31367.96 | 01-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.962701E+10 | 31367.96 | 01-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.570715E+10 | 31367.96 | 01-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.217170E+10 | 31367.96 | 03-APR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 70091514.02 | 7717.11 | 01-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.956541E+09 | 30064.65 | 30-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.338719E+10 | 31367.96 | 24-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.945377E+10 | 31367.96 | 02-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.416816E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.103081E+11 | 31367.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4 HEATING COIL
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.105507E+11 | 31242.14 | 01-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.983354E+10 | 31242.14 | 01-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.589672E+10 | 31242.14 | 01-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.233420E+10 | 31242.14 | 01-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.102873E+09 | 12368.49 | 01-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 218747.15 | 295.03 | 30-SEP-07:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.107512E+10 | 31242.14 | 30-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.359909E+10 | 31242.14 | 12-NOV-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.967837E+10 | 31242.14 | 02-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.430708E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.105507E+11 | 31242.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5 HEATING COIL
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.109590E+11 | 31172.14 | 01-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.102001E+11 | 31172.14 | 01-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.623110E+10 | 31172.14 | 01-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.259797E+10 | 31172.14 | 01-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.157182E+09 | 16171.39 | 01-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 1464942.86 | 736.67 | 30-SEP-07:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.124965E+10 | 31172.14 | 30-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.391520E+10 | 31172.14 | 12-NOV-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.100686E+11 | 31172.14 | 02-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.453802E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.109590E+11 | 31172.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6 HEATING COIL
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.211091E+11 | 57721.90 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.195803E+11 | 57721.90 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.121618E+11 | 57721.90 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.535268E+10 | 57721.90 | 01-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.425123E+09 | 57721.90 | 01-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6340544.07 | 3703.04 | 30-SEP-08:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.281566E+10 | 57721.90 | 09-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.806076E+10 | 57721.90 | 03-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.194791E+11 | 57721.90 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.889908E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.211091E+11 | 57721.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7 HEATING COIL
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.109770E+11 | 29453.43 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.101863E+11 | 29453.43 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.635600E+10 | 29453.43 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.282229E+10 | 29453.43 | 01-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.235341E+09 | 29453.43 | 01-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3245800.47 | 1620.89 | 30-SEP-08:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.147531E+10 | 29453.43 | 09-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.420257E+10 | 29453.43 | 03-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.101351E+11 | 29453.43 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.463931E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.109770E+11 | 29453.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8 HEATING COIL
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.110595E+11 | 29309.82 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.102571E+11 | 29309.82 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.645041E+10 | 29309.82 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.291431E+10 | 29309.82 | 01-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.268744E+09 | 29309.82 | 01-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 4561590.70 | 1945.99 | 30-SEP-08:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.153746E+10 | 29309.82 | 09-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.428689E+10 | 29309.82 | 02-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.102157E+11 | 29309.82 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.469946E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.110595E+11 | 29309.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9 HEATING COIL
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.115204E+11 | 29066.94 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.106692E+11 | 29066.94 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.687216E+10 | 29066.94 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.325442E+10 | 29066.94 | 01-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.382578E+09 | 29066.94 | 01-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 332363.21 | 553.94 | 14-JUN-08:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 10195229.87 | 5448.54 | 30-SEP-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174196E+10 | 29066.94 | 08-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.459866E+10 | 29066.94 | 02-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.106488E+11 | 29066.94 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.496987E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.115204E+11 | 29066.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10 HEATING COIL
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.143234E+11 | 29916.79 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.134674E+11 | 29916.79 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.885005E+10 | 29916.79 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.445544E+10 | 29916.79 | 01-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.825882E+09 | 29916.79 | 01-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6432839.89 | 6957.13 | 14-JUN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 49030697.37 | 27313.70 | 30-SEP-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.235962E+10 | 29916.79 | 03-OCT-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.576721E+10 | 29916.79 | 01-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.131677E+11 | 29916.79 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.632721E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.143234E+11 | 29916.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.297453E+09 | 0.252144E+09 | 8518.16 | 15-MAR-14:00 | 7820.13 | 0.00 |
April | 0.00 | 0.00 | 28455.60 | 25523.09 | 47.43 | 08-APR-13:00 | 42.54 | 0.00 |
May | 0.00 | 0.00 | 0.872700E+09 | 0.769546E+09 | 11138.09 | 14-MAY-15:00 | 8750.21 | 0.00 |
June | 0.00 | 0.00 | 0.902121E+10 | 0.645245E+10 | 44331.30 | 18-JUN-07:03 | 21808.41 | 0.00 |
July | 0.00 | 0.00 | 0.196820E+11 | 0.129981E+11 | 45290.73 | 21-JUL-07:02 | 22584.59 | 0.00 |
August | 0.00 | 0.00 | 0.153218E+11 | 0.113464E+11 | 44364.92 | 14-AUG-07:02 | 25029.21 | 0.00 |
September | 0.00 | 0.00 | 0.557685E+10 | 0.382452E+10 | 43137.20 | 17-SEP-07:02 | 23831.20 | 0.00 |
October | 0.00 | 0.00 | 0.175788E+09 | 0.151683E+09 | 5730.14 | 11-OCT-16:10 | 4884.16 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.509479E+11 | 0.357949E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.196820E+11 | 0.129981E+11 | 45290.73 | 25029.21 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.219490E+09 | 0.186430E+09 | 21052.18 | 15-MAR-20:01 | 17372.68 | 0.00 |
April | 0.00 | 0.00 | 9156525.18 | 8314514.68 | 1324.37 | 09-APR-21:10 | 1081.30 | 0.00 |
May | 0.00 | 0.00 | 0.787805E+09 | 0.704657E+09 | 21359.19 | 13-MAY-18:01 | 16038.44 | 0.00 |
June | 0.00 | 0.00 | 0.593442E+10 | 0.433435E+10 | 23519.30 | 18-JUN-07:03 | 12207.30 | 0.00 |
July | 0.00 | 0.00 | 0.120209E+11 | 0.809782E+10 | 23488.82 | 21-JUL-20:05 | 11257.08 | 0.00 |
August | 0.00 | 0.00 | 0.941603E+10 | 0.702274E+10 | 23370.97 | 15-AUG-07:02 | 12391.78 | 0.00 |
September | 0.00 | 0.00 | 0.371950E+10 | 0.258620E+10 | 23325.67 | 15-SEP-20:03 | 10888.45 | 0.00 |
October | 0.00 | 0.00 | 0.155404E+09 | 0.133808E+09 | 21038.94 | 22-OCT-17:09 | 17034.03 | 0.00 |
November | 0.00 | 0.00 | 1162423.55 | 1015293.68 | 451.80 | 05-NOV-22:10 | 358.09 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.322639E+11 | 0.230753E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.120209E+11 | 0.809782E+10 | 23519.30 | 17372.68 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3 COOLING COIL
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.171709E+09 | 0.147144E+09 | 4713.13 | 15-MAR-14:00 | 4384.93 | 0.00 |
April | 0.00 | 0.00 | 2308263.14 | 2053148.21 | 759.21 | 08-APR-13:00 | 688.13 | 0.00 |
May | 0.00 | 0.00 | 0.510478E+09 | 0.456536E+09 | 5563.10 | 14-MAY-15:00 | 4447.48 | 0.00 |
June | 0.00 | 0.00 | 0.397218E+10 | 0.291139E+10 | 23788.77 | 18-JUN-07:03 | 11760.98 | 0.00 |
July | 0.00 | 0.00 | 0.820797E+10 | 0.556680E+10 | 24229.10 | 21-JUL-06:02 | 12765.08 | 0.00 |
August | 0.00 | 0.00 | 0.660030E+10 | 0.503619E+10 | 24021.61 | 14-AUG-06:02 | 10614.53 | 0.00 |
September | 0.00 | 0.00 | 0.256201E+10 | 0.180635E+10 | 23224.50 | 16-SEP-06:03 | 12106.93 | 0.00 |
October | 0.00 | 0.00 | 84298004.63 | 74234975.04 | 3003.20 | 11-OCT-15:00 | 2651.34 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.221113E+11 | 0.160007E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.820797E+10 | 0.556680E+10 | 24229.10 | 12765.08 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4 COOLING COIL
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.160464E+09 | 0.137679E+09 | 4534.51 | 15-MAR-14:00 | 4216.49 | 0.00 |
April | 0.00 | 0.00 | 1191474.83 | 1062277.05 | 541.33 | 08-APR-13:00 | 490.56 | 0.00 |
May | 0.00 | 0.00 | 0.471364E+09 | 0.421491E+09 | 5348.69 | 14-MAY-15:00 | 4266.82 | 0.00 |
June | 0.00 | 0.00 | 0.393507E+10 | 0.288255E+10 | 23853.00 | 18-JUN-07:03 | 11789.06 | 0.00 |
July | 0.00 | 0.00 | 0.820949E+10 | 0.556779E+10 | 24300.25 | 21-JUL-06:02 | 12834.05 | 0.00 |
August | 0.00 | 0.00 | 0.659908E+10 | 0.503619E+10 | 24088.08 | 14-AUG-06:02 | 10651.87 | 0.00 |
September | 0.00 | 0.00 | 0.251549E+10 | 0.177146E+10 | 23288.13 | 16-SEP-06:03 | 12137.84 | 0.00 |
October | 0.00 | 0.00 | 71970368.54 | 63418706.39 | 2688.33 | 11-OCT-15:00 | 2373.10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.219641E+11 | 0.158816E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.820949E+10 | 0.556779E+10 | 24300.25 | 12834.05 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5 COOLING COIL
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.143279E+09 | 0.122991E+09 | 4231.45 | 15-MAR-14:00 | 3928.40 | 0.00 |
April | 0.00 | 0.00 | 111862.57 | 101210.76 | 186.44 | 08-APR-13:00 | 168.68 | 0.00 |
May | 0.00 | 0.00 | 0.406900E+09 | 0.363220E+09 | 5037.08 | 14-MAY-15:00 | 4002.68 | 0.00 |
June | 0.00 | 0.00 | 0.375491E+10 | 0.274525E+10 | 23664.73 | 18-JUN-07:03 | 11651.31 | 0.00 |
July | 0.00 | 0.00 | 0.796066E+10 | 0.539229E+10 | 24098.59 | 21-JUL-06:02 | 12583.66 | 0.00 |
August | 0.00 | 0.00 | 0.639100E+10 | 0.487576E+10 | 23899.27 | 14-AUG-06:02 | 10536.79 | 0.00 |
September | 0.00 | 0.00 | 0.236944E+10 | 0.166443E+10 | 23015.63 | 17-SEP-07:02 | 12780.56 | 0.00 |
October | 0.00 | 0.00 | 58417759.57 | 51464270.75 | 2319.30 | 11-OCT-15:00 | 2045.16 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.210847E+11 | 0.152155E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.796066E+10 | 0.539229E+10 | 24098.59 | 12780.56 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6 COOLING COIL
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.226723E+09 | 0.189173E+09 | 7503.68 | 15-MAR-14:10 | 6762.26 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.617755E+09 | 0.541588E+09 | 9621.53 | 14-MAY-15:00 | 7378.56 | 0.00 |
June | 0.00 | 0.00 | 0.648062E+10 | 0.462812E+10 | 42668.42 | 18-JUN-08:63 | 22895.77 | 0.00 |
July | 0.00 | 0.00 | 0.141347E+11 | 0.939670E+10 | 43180.19 | 16-JUL-08:62 | 22192.35 | 0.00 |
August | 0.00 | 0.00 | 0.113325E+11 | 0.850535E+10 | 43229.87 | 14-AUG-07:02 | 22329.66 | 0.00 |
September | 0.00 | 0.00 | 0.395896E+10 | 0.273647E+10 | 41449.74 | 17-SEP-08:62 | 22137.55 | 0.00 |
October | 0.00 | 0.00 | 81039497.71 | 70375864.39 | 4279.67 | 11-OCT-15:00 | 3696.29 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.368323E+11 | 0.260678E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.141347E+11 | 0.939670E+10 | 43229.87 | 22895.77 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7 COOLING COIL
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.110865E+09 | 92829375.25 | 3796.91 | 15-MAR-14:10 | 3426.74 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.291273E+09 | 0.255442E+09 | 4854.18 | 14-MAY-15:00 | 3722.29 | 0.00 |
June | 0.00 | 0.00 | 0.328249E+10 | 0.234777E+10 | 20454.56 | 18-JUN-08:63 | 10917.33 | 0.00 |
July | 0.00 | 0.00 | 0.722349E+10 | 0.481403E+10 | 22339.27 | 16-JUL-08:62 | 11450.80 | 0.00 |
August | 0.00 | 0.00 | 0.579375E+10 | 0.435831E+10 | 22368.47 | 14-AUG-07:02 | 11536.56 | 0.00 |
September | 0.00 | 0.00 | 0.200558E+10 | 0.138764E+10 | 21444.34 | 17-SEP-08:62 | 11468.44 | 0.00 |
October | 0.00 | 0.00 | 37704126.87 | 32797945.04 | 2122.42 | 11-OCT-15:00 | 1836.67 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.187451E+11 | 0.132888E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.722349E+10 | 0.481403E+10 | 22368.47 | 11536.56 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8 COOLING COIL
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.106532E+09 | 89176286.33 | 3711.66 | 15-MAR-14:10 | 3346.35 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.267609E+09 | 0.233967E+09 | 4724.28 | 14-MAY-15:00 | 3615.27 | 0.00 |
June | 0.00 | 0.00 | 0.320748E+10 | 0.228959E+10 | 19002.48 | 18-JUN-08:63 | 10059.10 | 0.00 |
July | 0.00 | 0.00 | 0.713582E+10 | 0.475079E+10 | 22227.29 | 16-JUL-08:62 | 11349.33 | 0.00 |
August | 0.00 | 0.00 | 0.572228E+10 | 0.430218E+10 | 22256.04 | 14-AUG-07:02 | 11438.37 | 0.00 |
September | 0.00 | 0.00 | 0.195820E+10 | 0.135282E+10 | 21339.75 | 17-SEP-08:62 | 11401.16 | 0.00 |
October | 0.00 | 0.00 | 34637473.07 | 30108608.45 | 2020.49 | 11-OCT-15:00 | 1746.79 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.184326E+11 | 0.130486E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.713582E+10 | 0.475079E+10 | 22256.04 | 11438.37 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9 COOLING COIL
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 93386048.82 | 78298563.05 | 3472.95 | 15-MAR-14:10 | 3126.87 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.217351E+09 | 0.188728E+09 | 4385.08 | 14-MAY-15:00 | 3342.21 | 0.00 |
June | 0.00 | 0.00 | 0.302841E+10 | 0.215408E+10 | 14148.07 | 18-JUN-08:63 | 7281.82 | 0.00 |
July | 0.00 | 0.00 | 0.693733E+10 | 0.461458E+10 | 22016.98 | 16-JUL-08:62 | 11115.65 | 0.00 |
August | 0.00 | 0.00 | 0.556377E+10 | 0.418448E+10 | 22043.53 | 14-AUG-07:02 | 11202.42 | 0.00 |
September | 0.00 | 0.00 | 0.184050E+10 | 0.126843E+10 | 21149.47 | 17-SEP-08:62 | 11277.52 | 0.00 |
October | 0.00 | 0.00 | 28436980.62 | 24723011.03 | 1809.98 | 11-OCT-15:00 | 1563.55 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.177092E+11 | 0.125133E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.693733E+10 | 0.461458E+10 | 22043.53 | 11277.52 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10 COOLING COIL
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 75616367.68 | 64082273.90 | 3226.12 | 15-MAR-14:10 | 2915.52 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.152261E+09 | 0.130976E+09 | 3951.92 | 14-MAY-15:00 | 3005.55 | 0.00 |
June | 0.00 | 0.00 | 0.289081E+10 | 0.206106E+10 | 12990.84 | 27-JUN-13:00 | 8171.45 | 0.00 |
July | 0.00 | 0.00 | 0.694383E+10 | 0.466472E+10 | 23426.94 | 21-JUL-07:02 | 10624.17 | 0.00 |
August | 0.00 | 0.00 | 0.561561E+10 | 0.427027E+10 | 23182.75 | 14-AUG-07:02 | 11030.18 | 0.00 |
September | 0.00 | 0.00 | 0.174098E+10 | 0.120941E+10 | 17021.33 | 17-SEP-08:62 | 8877.64 | 0.00 |
October | 0.00 | 0.00 | 26126607.04 | 22941717.68 | 1723.88 | 11-OCT-15:00 | 1498.97 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.174452E+11 | 0.124235E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.694383E+10 | 0.466472E+10 | 23426.94 | 11030.18 | 0.00 |
Report: FanReportMonthly
For: PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.197362E+10 | 0.46 | 1994.18 | 01-JAN-08:61 | 0.90 |
February | 0.180624E+10 | 0.46 | 1994.18 | 01-FEB-08:61 | 0.90 |
March | 0.175912E+10 | 0.42 | 1994.18 | 01-MAR-08:61 | 0.90 |
April | 0.153163E+10 | 0.39 | 1994.18 | 01-APR-07:01 | 0.90 |
May | 0.145500E+10 | 0.37 | 1994.18 | 01-MAY-07:01 | 0.90 |
June | 0.140844E+10 | 0.37 | 1994.18 | 18-JUN-07:03 | 0.88 |
July | 0.145949E+10 | 0.37 | 1994.18 | 15-JUL-07:03 | 0.89 |
August | 0.145421E+10 | 0.37 | 1994.18 | 07-AUG-07:02 | 0.89 |
September | 0.140475E+10 | 0.37 | 1994.18 | 17-SEP-07:02 | 0.89 |
October | 0.150732E+10 | 0.38 | 1994.18 | 16-OCT-07:01 | 0.90 |
November | 0.158178E+10 | 0.40 | 1994.18 | 03-NOV-07:01 | 0.90 |
December | 0.193907E+10 | 0.45 | 1994.18 | 01-DEC-08:61 | 0.90 |
Annual Sum or Average | 0.192807E+11 | 0.40 | |||
Minimum of Months | 0.140475E+10 | 0.37 | 1994.18 | 0.88 | |
Maximum of Months | 0.197362E+10 | 0.46 | 1994.18 | 0.90 |
Report: FanReportMonthly
For: PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.805590E+09 | 0.36 | 1121.56 | 01-JAN-08:61 | 0.93 |
February | 0.736481E+09 | 0.38 | 1121.56 | 01-FEB-08:61 | 0.93 |
March | 0.730524E+09 | 0.34 | 1121.56 | 01-MAR-08:61 | 0.93 |
April | 0.644994E+09 | 0.33 | 1121.56 | 01-APR-07:01 | 0.93 |
May | 0.719786E+09 | 0.37 | 495.53 | 01-MAY-08:10 | 0.60 |
June | 0.723553E+09 | 0.37 | 1121.56 | 18-JUN-07:03 | 0.91 |
July | 0.726812E+09 | 0.36 | 1121.56 | 15-JUL-07:03 | 0.92 |
August | 0.739319E+09 | 0.37 | 1121.56 | 06-AUG-07:02 | 0.92 |
September | 0.746599E+09 | 0.37 | 1121.56 | 14-SEP-07:03 | 0.92 |
October | 0.679783E+09 | 0.35 | 1058.40 | 30-OCT-07:01 | 0.90 |
November | 0.652734E+09 | 0.32 | 1121.56 | 21-NOV-08:61 | 0.93 |
December | 0.785595E+09 | 0.35 | 1121.56 | 02-DEC-08:61 | 0.93 |
Annual Sum or Average | 0.869177E+10 | 0.36 | |||
Minimum of Months | 0.644994E+09 | 0.32 | 495.53 | 0.60 | |
Maximum of Months | 0.805590E+09 | 0.38 | 1121.56 | 0.93 |
Report: FanReportMonthly
For: PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.875602E+09 | 0.37 | 1128.28 | 01-JAN-08:61 | 0.93 |
February | 0.799164E+09 | 0.37 | 1128.28 | 01-FEB-07:01 | 0.93 |
March | 0.789305E+09 | 0.35 | 1128.28 | 01-MAR-07:01 | 0.93 |
April | 0.680510E+09 | 0.32 | 1128.28 | 03-APR-06:01 | 0.93 |
May | 0.661150E+09 | 0.31 | 617.86 | 01-MAY-06:03 | 0.68 |
June | 0.644238E+09 | 0.31 | 1128.28 | 18-JUN-07:03 | 0.91 |
July | 0.656181E+09 | 0.30 | 1128.28 | 15-JUL-06:03 | 0.92 |
August | 0.667870E+09 | 0.31 | 1128.28 | 06-AUG-07:02 | 0.92 |
September | 0.633946E+09 | 0.30 | 1128.28 | 14-SEP-06:03 | 0.92 |
October | 0.673782E+09 | 0.31 | 1100.15 | 30-OCT-06:02 | 0.92 |
November | 0.706742E+09 | 0.33 | 1128.28 | 24-NOV-07:01 | 0.93 |
December | 0.853915E+09 | 0.36 | 1128.28 | 02-DEC-07:01 | 0.93 |
Annual Sum or Average | 0.864240E+10 | 0.33 | |||
Minimum of Months | 0.633946E+09 | 0.30 | 617.86 | 0.68 | |
Maximum of Months | 0.875602E+09 | 0.37 | 1128.28 | 0.93 |
Report: FanReportMonthly
For: PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.884862E+09 | 0.37 | 1132.25 | 01-JAN-08:61 | 0.93 |
February | 0.807311E+09 | 0.37 | 1132.25 | 01-FEB-07:01 | 0.93 |
March | 0.796706E+09 | 0.35 | 1132.25 | 01-MAR-07:01 | 0.93 |
April | 0.686631E+09 | 0.32 | 1132.25 | 01-APR-06:02 | 0.93 |
May | 0.664198E+09 | 0.31 | 721.85 | 01-MAY-06:03 | 0.74 |
June | 0.646472E+09 | 0.31 | 1132.25 | 18-JUN-07:03 | 0.91 |
July | 0.658356E+09 | 0.30 | 1132.25 | 15-JUL-06:03 | 0.92 |
August | 0.670167E+09 | 0.31 | 1132.25 | 06-AUG-07:02 | 0.92 |
September | 0.636182E+09 | 0.30 | 1132.25 | 14-SEP-06:03 | 0.92 |
October | 0.678818E+09 | 0.31 | 1132.25 | 30-OCT-06:02 | 0.93 |
November | 0.714136E+09 | 0.33 | 1132.25 | 12-NOV-08:62 | 0.93 |
December | 0.862633E+09 | 0.36 | 1132.25 | 02-DEC-07:01 | 0.93 |
Annual Sum or Average | 0.870647E+10 | 0.33 | |||
Minimum of Months | 0.636182E+09 | 0.30 | 721.85 | 0.74 | |
Maximum of Months | 0.884862E+09 | 0.37 | 1132.25 | 0.93 |
Report: FanReportMonthly
For: PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.885279E+09 | 0.37 | 1120.86 | 01-JAN-08:61 | 0.93 |
February | 0.807573E+09 | 0.37 | 1120.86 | 01-FEB-07:01 | 0.93 |
March | 0.796190E+09 | 0.35 | 1120.86 | 01-MAR-07:01 | 0.93 |
April | 0.685527E+09 | 0.32 | 1120.86 | 01-APR-06:02 | 0.93 |
May | 0.658693E+09 | 0.31 | 797.23 | 01-MAY-06:03 | 0.79 |
June | 0.639823E+09 | 0.31 | 1120.86 | 18-JUN-07:03 | 0.91 |
July | 0.651090E+09 | 0.30 | 1120.86 | 15-JUL-06:03 | 0.92 |
August | 0.663151E+09 | 0.31 | 1120.86 | 06-AUG-07:02 | 0.92 |
September | 0.629784E+09 | 0.30 | 1120.86 | 17-SEP-07:02 | 0.92 |
October | 0.675806E+09 | 0.31 | 1120.86 | 30-OCT-06:02 | 0.93 |
November | 0.713945E+09 | 0.33 | 1120.86 | 12-NOV-08:62 | 0.93 |
December | 0.862841E+09 | 0.36 | 1120.86 | 02-DEC-07:01 | 0.93 |
Annual Sum or Average | 0.866970E+10 | 0.33 | |||
Minimum of Months | 0.629784E+09 | 0.30 | 797.23 | 0.79 | |
Maximum of Months | 0.885279E+09 | 0.37 | 1120.86 | 0.93 |
Report: FanReportMonthly
For: PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.143160E+10 | 0.34 | 1899.53 | 01-JAN-09:01 | 0.90 |
February | 0.130628E+10 | 0.34 | 1899.53 | 01-FEB-08:61 | 0.90 |
March | 0.127682E+10 | 0.32 | 1899.53 | 01-MAR-08:61 | 0.90 |
April | 0.109040E+10 | 0.29 | 1899.53 | 01-APR-07:01 | 0.90 |
May | 0.103414E+10 | 0.28 | 1899.53 | 01-MAY-07:01 | 0.89 |
June | 0.100265E+10 | 0.28 | 1899.53 | 18-JUN-08:63 | 0.88 |
July | 0.102232E+10 | 0.27 | 1899.53 | 15-JUL-07:03 | 0.89 |
August | 0.104005E+10 | 0.28 | 1899.53 | 06-AUG-08:62 | 0.89 |
September | 0.985225E+09 | 0.27 | 1899.53 | 17-SEP-08:62 | 0.89 |
October | 0.107040E+10 | 0.28 | 1899.53 | 09-OCT-08:61 | 0.90 |
November | 0.114388E+10 | 0.30 | 1899.53 | 03-NOV-07:01 | 0.90 |
December | 0.139395E+10 | 0.33 | 1899.53 | 01-DEC-08:61 | 0.90 |
Annual Sum or Average | 0.137977E+11 | 0.30 | |||
Minimum of Months | 0.985225E+09 | 0.27 | 1899.53 | 0.88 | |
Maximum of Months | 0.143160E+10 | 0.34 | 1899.53 | 0.90 |
Report: FanReportMonthly
For: PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.772896E+09 | 0.35 | 1019.85 | 01-JAN-09:01 | 0.93 |
February | 0.705311E+09 | 0.35 | 1019.85 | 01-FEB-08:61 | 0.93 |
March | 0.688641E+09 | 0.33 | 1019.85 | 01-MAR-08:61 | 0.93 |
April | 0.587324E+09 | 0.30 | 1019.85 | 01-APR-07:01 | 0.93 |
May | 0.555607E+09 | 0.28 | 1019.85 | 01-MAY-07:01 | 0.93 |
June | 0.538218E+09 | 0.28 | 930.68 | 18-JUN-08:63 | 0.88 |
July | 0.548454E+09 | 0.28 | 1019.85 | 16-JUL-08:62 | 0.91 |
August | 0.558268E+09 | 0.29 | 1019.85 | 07-AUG-07:02 | 0.92 |
September | 0.528933E+09 | 0.28 | 1019.85 | 17-SEP-08:62 | 0.92 |
October | 0.575494E+09 | 0.29 | 1019.85 | 09-OCT-08:61 | 0.93 |
November | 0.616000E+09 | 0.31 | 1019.85 | 03-NOV-07:01 | 0.93 |
December | 0.752469E+09 | 0.34 | 1019.85 | 01-DEC-08:61 | 0.93 |
Annual Sum or Average | 0.742761E+10 | 0.31 | |||
Minimum of Months | 0.528933E+09 | 0.28 | 930.68 | 0.88 | |
Maximum of Months | 0.772896E+09 | 0.35 | 1019.85 | 0.93 |
Report: FanReportMonthly
For: PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.770661E+09 | 0.35 | 1013.18 | 01-JAN-09:01 | 0.93 |
February | 0.703208E+09 | 0.36 | 1013.18 | 01-FEB-08:61 | 0.93 |
March | 0.686737E+09 | 0.33 | 1013.18 | 01-MAR-08:61 | 0.93 |
April | 0.585675E+09 | 0.30 | 1013.18 | 01-APR-07:01 | 0.93 |
May | 0.552689E+09 | 0.29 | 1013.18 | 01-MAY-07:01 | 0.93 |
June | 0.534642E+09 | 0.28 | 850.77 | 27-JUN-07:03 | 0.84 |
July | 0.544707E+09 | 0.28 | 1013.18 | 16-JUL-08:62 | 0.91 |
August | 0.554550E+09 | 0.29 | 1013.18 | 07-AUG-07:02 | 0.92 |
September | 0.525485E+09 | 0.28 | 1013.18 | 17-SEP-08:62 | 0.92 |
October | 0.573167E+09 | 0.29 | 1013.18 | 09-OCT-08:61 | 0.93 |
November | 0.614143E+09 | 0.31 | 1013.18 | 02-NOV-07:01 | 0.93 |
December | 0.750240E+09 | 0.34 | 1013.18 | 01-DEC-08:61 | 0.93 |
Annual Sum or Average | 0.739590E+10 | 0.31 | |||
Minimum of Months | 0.525485E+09 | 0.28 | 850.77 | 0.84 | |
Maximum of Months | 0.770661E+09 | 0.36 | 1013.18 | 0.93 |
Report: FanReportMonthly
For: PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.774051E+09 | 0.35 | 1002.60 | 01-JAN-09:01 | 0.93 |
February | 0.706483E+09 | 0.36 | 1002.60 | 01-FEB-08:61 | 0.93 |
March | 0.689403E+09 | 0.33 | 1002.60 | 01-MAR-08:61 | 0.93 |
April | 0.587101E+09 | 0.30 | 1002.60 | 01-APR-07:01 | 0.93 |
May | 0.549322E+09 | 0.29 | 1002.60 | 01-MAY-07:01 | 0.93 |
June | 0.528930E+09 | 0.28 | 584.31 | 18-JUN-08:63 | 0.70 |
July | 0.538741E+09 | 0.28 | 1002.60 | 16-JUL-08:62 | 0.91 |
August | 0.548600E+09 | 0.28 | 1002.60 | 07-AUG-07:02 | 0.92 |
September | 0.520065E+09 | 0.28 | 1002.60 | 17-SEP-08:62 | 0.92 |
October | 0.571680E+09 | 0.29 | 1002.60 | 08-OCT-08:61 | 0.93 |
November | 0.614920E+09 | 0.31 | 1002.60 | 02-NOV-07:01 | 0.93 |
December | 0.753176E+09 | 0.35 | 1002.60 | 01-DEC-08:61 | 0.93 |
Annual Sum or Average | 0.738247E+10 | 0.31 | |||
Minimum of Months | 0.520065E+09 | 0.28 | 584.31 | 0.70 | |
Maximum of Months | 0.774051E+09 | 0.36 | 1002.60 | 0.93 |
Report: FanReportMonthly
For: PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.881850E+09 | 0.44 | 1064.31 | 01-JAN-09:01 | 0.93 |
February | 0.813843E+09 | 0.47 | 1064.31 | 01-FEB-08:61 | 0.93 |
March | 0.772320E+09 | 0.37 | 1064.31 | 01-MAR-08:61 | 0.94 |
April | 0.647013E+09 | 0.31 | 1064.31 | 01-APR-07:01 | 0.93 |
May | 0.592358E+09 | 0.29 | 1064.31 | 01-MAY-07:01 | 0.93 |
June | 0.561518E+09 | 0.28 | 574.23 | 14-JUN-07:03 | 0.68 |
July | 0.571383E+09 | 0.28 | 1064.31 | 16-JUL-08:62 | 0.91 |
August | 0.582143E+09 | 0.28 | 1064.31 | 07-AUG-07:02 | 0.92 |
September | 0.552838E+09 | 0.28 | 1008.75 | 30-SEP-07:02 | 0.91 |
October | 0.618966E+09 | 0.30 | 1064.31 | 03-OCT-07:02 | 0.93 |
November | 0.674844E+09 | 0.32 | 1064.31 | 01-NOV-07:02 | 0.93 |
December | 0.852251E+09 | 0.41 | 1064.31 | 01-DEC-08:61 | 0.93 |
Annual Sum or Average | 0.812133E+10 | 0.33 | |||
Minimum of Months | 0.552838E+09 | 0.28 | 574.23 | 0.68 | |
Maximum of Months | 0.881850E+09 | 0.47 | 1064.31 | 0.94 |
Report: ZoneTemperatureOscillationReportMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.197362E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.180624E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.184154E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.153164E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.169178E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.368024E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.629377E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.529604E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.281821E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.155527E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.158178E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.193907E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.320092E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.153164E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.629377E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.805590E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.736481E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.788636E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.647528E+09 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.919974E+09 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.215085E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.356406E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.300629E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.164883E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.720182E+09 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.653060E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.785595E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.164271E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.647528E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.356406E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_3:3
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.875602E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.799164E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.835770E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.681155E+09 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.796330E+09 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.162654E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.263480E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.229365E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.127046E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.696358E+09 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.706742E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.853915E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.140705E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.681155E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.263480E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_4:4
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.884862E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.807311E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.840347E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.686966E+09 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.789575E+09 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.162054E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.263823E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.229642E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.126170E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.698238E+09 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.714136E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.862633E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.141009E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.686966E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.263823E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_5:5
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.885279E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.807573E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.835426E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.685559E+09 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.767704E+09 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.157180E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.257550E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.224219E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.122053E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.691703E+09 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.713945E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.862841E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.138601E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.685559E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.257550E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_6:6
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.143160E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.130628E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.133920E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.109040E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.120067E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.261122E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.443788E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.384058E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.197325E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.109257E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.114388E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.139395E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.228615E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.109040E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.443788E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_7:7
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.772896E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.705311E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.719226E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.587324E+09 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.634404E+09 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.135418E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.229684E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.199197E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.102987E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.585835E+09 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.616000E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.752469E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.120463E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.585835E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.229684E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_8:8
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.770661E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.703208E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.716178E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.585675E+09 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.625324E+09 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.133281E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.227296E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.197148E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.101497E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.582689E+09 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.614143E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.750240E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.119403E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.582689E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.227296E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_9:9
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.774051E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.706483E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.715370E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.587101E+09 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.608766E+09 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.128467E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.222149E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.192804E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.981033E+09 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.579535E+09 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.614920E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.753176E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.117546E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.579535E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.222149E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_10:10
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.881850E+09 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.813843E+09 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.793582E+09 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.647013E+09 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.634592E+09 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.128701E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.226365E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.197733E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.990239E+09 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.626206E+09 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.674844E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.852251E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.124424E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.626206E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.226365E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.197362E+10 | 0.00 | 0.260556E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.180624E+10 | 0.00 | 0.245666E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.175912E+10 | 0.297453E+09 | 0.151647E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.153163E+10 | 28455.60 | 0.646709E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.145500E+10 | 0.872700E+09 | 0.384188E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.140844E+10 | 0.902121E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.145949E+10 | 0.196820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.145421E+10 | 0.153218E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.140475E+10 | 0.557685E+10 | 6538320.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.150732E+10 | 0.175788E+09 | 0.299276E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.158178E+10 | 0.00 | 0.912661E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.193907E+10 | 0.00 | 0.240937E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.192807E+11 | 0.509479E+11 | 0.108858E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.140475E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.197362E+10 | 0.196820E+11 | 0.260556E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.805590E+09 | 0.00 | 0.908093E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.736481E+09 | 0.00 | 0.854519E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.730524E+09 | 0.216119E+09 | 0.477898E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.644994E+09 | 9156525.18 | 0.154913E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.719786E+09 | 0.751106E+09 | 15020719.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.723553E+09 | 0.559892E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.726812E+09 | 0.113527E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.739319E+09 | 0.897379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.746599E+09 | 0.357136E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.679783E+09 | 0.152750E+09 | 0.549187E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.652734E+09 | 1162423.55 | 0.255984E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.785595E+09 | 0.00 | 0.831584E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.869177E+10 | 0.306271E+11 | 0.353941E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.644994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.805590E+09 | 0.113527E+11 | 0.908093E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_3:3
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.875602E+09 | 0.00 | 0.103081E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.799164E+09 | 0.00 | 0.962701E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.789305E+09 | 0.171709E+09 | 0.570715E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.680510E+09 | 2308263.14 | 0.217170E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.661150E+09 | 0.510478E+09 | 70091514.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.644238E+09 | 0.397218E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.656181E+09 | 0.820797E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.667870E+09 | 0.660030E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.633946E+09 | 0.256201E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.673782E+09 | 84298004.63 | 0.956541E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.706742E+09 | 0.00 | 0.338719E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.853915E+09 | 0.00 | 0.945377E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.864240E+10 | 0.221113E+11 | 0.416816E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.633946E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.875602E+09 | 0.820797E+10 | 0.103081E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_4:4
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.884862E+09 | 0.00 | 0.105507E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.807311E+09 | 0.00 | 0.983354E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.796706E+09 | 0.160464E+09 | 0.589672E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.686631E+09 | 1191474.83 | 0.233420E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.664198E+09 | 0.471364E+09 | 0.102873E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.646472E+09 | 0.393507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.658356E+09 | 0.820949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.670167E+09 | 0.659908E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.636182E+09 | 0.251549E+10 | 218747.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.678818E+09 | 71970368.54 | 0.107512E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.714136E+09 | 0.00 | 0.359909E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.862633E+09 | 0.00 | 0.967837E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.870647E+10 | 0.219641E+11 | 0.430708E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.636182E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.884862E+09 | 0.820949E+10 | 0.105507E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_5:5
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.885279E+09 | 0.00 | 0.109590E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.807573E+09 | 0.00 | 0.102001E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.796190E+09 | 0.143279E+09 | 0.623110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.685527E+09 | 111862.57 | 0.259797E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.658693E+09 | 0.406900E+09 | 0.157182E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.639823E+09 | 0.375491E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.651090E+09 | 0.796066E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.663151E+09 | 0.639100E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.629784E+09 | 0.236944E+10 | 1464942.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.675806E+09 | 58417759.57 | 0.124965E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.713945E+09 | 0.00 | 0.391520E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.862841E+09 | 0.00 | 0.100686E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.866970E+10 | 0.210847E+11 | 0.453802E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.629784E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.885279E+09 | 0.796066E+10 | 0.109590E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_6:6
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.143160E+10 | 0.00 | 0.211091E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.130628E+10 | 0.00 | 0.195803E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.127682E+10 | 0.226723E+09 | 0.121618E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.109040E+10 | 0.00 | 0.535268E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.103414E+10 | 0.617755E+09 | 0.425123E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.100265E+10 | 0.648062E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.102232E+10 | 0.141347E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.104005E+10 | 0.113325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.985225E+09 | 0.395896E+10 | 6340544.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.107040E+10 | 81039497.71 | 0.281566E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.114388E+10 | 0.00 | 0.806076E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.139395E+10 | 0.00 | 0.194791E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.137977E+11 | 0.368323E+11 | 0.889908E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.985225E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.143160E+10 | 0.141347E+11 | 0.211091E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_7:7
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.772896E+09 | 0.00 | 0.109770E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.705311E+09 | 0.00 | 0.101863E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.688641E+09 | 0.110865E+09 | 0.635600E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.587324E+09 | 0.00 | 0.282229E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.555607E+09 | 0.291273E+09 | 0.235341E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.538218E+09 | 0.328249E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.548454E+09 | 0.722349E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.558268E+09 | 0.579375E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.528933E+09 | 0.200558E+10 | 3245800.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.575494E+09 | 37704126.87 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.616000E+09 | 0.00 | 0.420257E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.752469E+09 | 0.00 | 0.101351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.742761E+10 | 0.187451E+11 | 0.463931E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.528933E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.772896E+09 | 0.722349E+10 | 0.109770E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_8:8
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.770661E+09 | 0.00 | 0.110595E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.703208E+09 | 0.00 | 0.102571E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.686737E+09 | 0.106532E+09 | 0.645041E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.585675E+09 | 0.00 | 0.291431E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.552689E+09 | 0.267609E+09 | 0.268744E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.534642E+09 | 0.320748E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.544707E+09 | 0.713582E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.554550E+09 | 0.572228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.525485E+09 | 0.195820E+10 | 4561590.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.573167E+09 | 34637473.07 | 0.153746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.614143E+09 | 0.00 | 0.428689E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.750240E+09 | 0.00 | 0.102157E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.739590E+10 | 0.184326E+11 | 0.469946E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.525485E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.770661E+09 | 0.713582E+10 | 0.110595E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_9:9
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.774051E+09 | 0.00 | 0.115204E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.706483E+09 | 0.00 | 0.106692E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.689403E+09 | 93386048.82 | 0.687216E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.587101E+09 | 0.00 | 0.325442E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.549322E+09 | 0.217351E+09 | 0.382578E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.528930E+09 | 0.302841E+10 | 332363.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.538741E+09 | 0.693733E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.548600E+09 | 0.556377E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.520065E+09 | 0.184050E+10 | 10195229.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.571680E+09 | 28436980.62 | 0.174196E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.614920E+09 | 0.00 | 0.459866E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.753176E+09 | 0.00 | 0.106488E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.738247E+10 | 0.177092E+11 | 0.496987E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.520065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.774051E+09 | 0.693733E+10 | 0.115204E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_10:10
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.881850E+09 | 0.00 | 0.143234E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.813843E+09 | 0.00 | 0.134674E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.772320E+09 | 75616367.68 | 0.885005E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.647013E+09 | 0.00 | 0.445544E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.592358E+09 | 0.152261E+09 | 0.825882E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.561518E+09 | 0.289081E+10 | 6432839.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.571383E+09 | 0.694383E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.582143E+09 | 0.561561E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.552838E+09 | 0.174098E+10 | 49030697.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.618966E+09 | 26126607.04 | 0.235962E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.674844E+09 | 0.00 | 0.576721E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.852251E+09 | 0.00 | 0.131677E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.812133E+10 | 0.174452E+11 | 0.632721E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.552838E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.881850E+09 | 0.694383E+10 | 0.143234E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.197362E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.180624E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.175912E+10 | 0.00 | 0.00 | 0.00 | 82414625.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.153163E+10 | 0.00 | 0.00 | 0.00 | 8216.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.145500E+10 | 0.00 | 0.00 | 0.00 | 0.236787E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.140844E+10 | 0.00 | 0.00 | 0.00 | 0.227180E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.145949E+10 | 0.00 | 0.00 | 0.00 | 0.483428E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.145421E+10 | 0.00 | 0.00 | 0.00 | 0.384183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.140475E+10 | 0.00 | 0.00 | 0.00 | 0.141346E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.150732E+10 | 0.00 | 0.00 | 0.00 | 47953595.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.158178E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.193907E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.192807E+11 | 0.00 | 0.00 | 0.00 | 0.127285E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.140475E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.197362E+10 | 0.00 | 0.00 | 0.00 | 0.483428E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.805590E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.736481E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.730524E+09 | 0.00 | 0.00 | 0.00 | 58112251.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.644994E+09 | 0.00 | 0.00 | 0.00 | 2534239.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.719786E+09 | 0.00 | 0.00 | 0.00 | 0.200188E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.723553E+09 | 0.00 | 0.00 | 0.00 | 0.142729E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.726812E+09 | 0.00 | 0.00 | 0.00 | 0.283725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.739319E+09 | 0.00 | 0.00 | 0.00 | 0.226697E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.746599E+09 | 0.00 | 0.00 | 0.00 | 0.902229E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.679783E+09 | 0.00 | 0.00 | 0.00 | 40398946.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.652734E+09 | 0.00 | 0.00 | 0.00 | 326308.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.785595E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.869177E+10 | 0.00 | 0.00 | 0.00 | 0.773530E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.644994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.805590E+09 | 0.00 | 0.00 | 0.00 | 0.283725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_3:3
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.875602E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.799164E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.789305E+09 | 0.00 | 0.00 | 0.00 | 46465456.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.680510E+09 | 0.00 | 0.00 | 0.00 | 645412.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.661150E+09 | 0.00 | 0.00 | 0.00 | 0.135180E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.644238E+09 | 0.00 | 0.00 | 0.00 | 0.982299E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.656181E+09 | 0.00 | 0.00 | 0.00 | 0.197862E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.667870E+09 | 0.00 | 0.00 | 0.00 | 0.162578E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.633946E+09 | 0.00 | 0.00 | 0.00 | 0.636512E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.673782E+09 | 0.00 | 0.00 | 0.00 | 22576066.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.706742E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.853915E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.864240E+10 | 0.00 | 0.00 | 0.00 | 0.542808E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.633946E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.875602E+09 | 0.00 | 0.00 | 0.00 | 0.197862E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_4:4
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.884862E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.807311E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.796706E+09 | 0.00 | 0.00 | 0.00 | 43641446.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.686631E+09 | 0.00 | 0.00 | 0.00 | 335069.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.664198E+09 | 0.00 | 0.00 | 0.00 | 0.125376E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.646472E+09 | 0.00 | 0.00 | 0.00 | 0.974064E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.658356E+09 | 0.00 | 0.00 | 0.00 | 0.197987E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.670167E+09 | 0.00 | 0.00 | 0.00 | 0.162625E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.636182E+09 | 0.00 | 0.00 | 0.00 | 0.625515E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.678818E+09 | 0.00 | 0.00 | 0.00 | 19419766.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.714136E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.862633E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.870647E+10 | 0.00 | 0.00 | 0.00 | 0.539447E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.636182E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.884862E+09 | 0.00 | 0.00 | 0.00 | 0.197987E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_5:5
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.885279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.807573E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.796190E+09 | 0.00 | 0.00 | 0.00 | 39235738.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.685527E+09 | 0.00 | 0.00 | 0.00 | 31569.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.658693E+09 | 0.00 | 0.00 | 0.00 | 0.109011E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.639823E+09 | 0.00 | 0.00 | 0.00 | 0.931981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.651090E+09 | 0.00 | 0.00 | 0.00 | 0.192441E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.663151E+09 | 0.00 | 0.00 | 0.00 | 0.157904E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.629784E+09 | 0.00 | 0.00 | 0.00 | 0.590747E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.675806E+09 | 0.00 | 0.00 | 0.00 | 15896278.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.713945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.862841E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.866970E+10 | 0.00 | 0.00 | 0.00 | 0.519036E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.629784E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.885279E+09 | 0.00 | 0.00 | 0.00 | 0.192441E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_6:6
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.143160E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.130628E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.127682E+10 | 0.00 | 0.00 | 0.00 | 62377300.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.109040E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.103414E+10 | 0.00 | 0.00 | 0.00 | 0.166529E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.100265E+10 | 0.00 | 0.00 | 0.00 | 0.160857E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.102232E+10 | 0.00 | 0.00 | 0.00 | 0.341556E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.104005E+10 | 0.00 | 0.00 | 0.00 | 0.280053E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.985225E+09 | 0.00 | 0.00 | 0.00 | 0.988029E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.107040E+10 | 0.00 | 0.00 | 0.00 | 22167840.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.114388E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.139395E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.137977E+11 | 0.00 | 0.00 | 0.00 | 0.906376E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.985225E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.143160E+10 | 0.00 | 0.00 | 0.00 | 0.341556E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_7:7
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.772896E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.705311E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.688641E+09 | 0.00 | 0.00 | 0.00 | 30584938.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.587324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.555607E+09 | 0.00 | 0.00 | 0.00 | 78797062.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.538218E+09 | 0.00 | 0.00 | 0.00 | 0.815962E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.548454E+09 | 0.00 | 0.00 | 0.00 | 0.174839E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.558268E+09 | 0.00 | 0.00 | 0.00 | 0.143371E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.528933E+09 | 0.00 | 0.00 | 0.00 | 0.500935E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.575494E+09 | 0.00 | 0.00 | 0.00 | 10341336.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.616000E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.752469E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.742761E+10 | 0.00 | 0.00 | 0.00 | 0.461871E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.528933E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.772896E+09 | 0.00 | 0.00 | 0.00 | 0.174839E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_8:8
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.770661E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.703208E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.686737E+09 | 0.00 | 0.00 | 0.00 | 29441577.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.585675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.552689E+09 | 0.00 | 0.00 | 0.00 | 72635127.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.534642E+09 | 0.00 | 0.00 | 0.00 | 0.798167E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.544707E+09 | 0.00 | 0.00 | 0.00 | 0.172826E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.554550E+09 | 0.00 | 0.00 | 0.00 | 0.141693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.525485E+09 | 0.00 | 0.00 | 0.00 | 0.489488E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.573167E+09 | 0.00 | 0.00 | 0.00 | 9522410.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.614143E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.750240E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.739590E+10 | 0.00 | 0.00 | 0.00 | 0.454444E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.525485E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.770661E+09 | 0.00 | 0.00 | 0.00 | 0.172826E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_9:9
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.774051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.706483E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.689403E+09 | 0.00 | 0.00 | 0.00 | 25966370.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.587101E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.549322E+09 | 0.00 | 0.00 | 0.00 | 59444230.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.528930E+09 | 0.00 | 0.00 | 0.00 | 0.755736E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.538741E+09 | 0.00 | 0.00 | 0.00 | 0.168275E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.548600E+09 | 0.00 | 0.00 | 0.00 | 0.137944E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.520065E+09 | 0.00 | 0.00 | 0.00 | 0.460968E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.571680E+09 | 0.00 | 0.00 | 0.00 | 7854414.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.614920E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.753176E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.738247E+10 | 0.00 | 0.00 | 0.00 | 0.437216E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.520065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.774051E+09 | 0.00 | 0.00 | 0.00 | 0.168275E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_10:10
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.881850E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.813843E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.772320E+09 | 0.00 | 0.00 | 0.00 | 21261566.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.647013E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.592358E+09 | 0.00 | 0.00 | 0.00 | 42233568.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.561518E+09 | 0.00 | 0.00 | 0.00 | 0.725494E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.571383E+09 | 0.00 | 0.00 | 0.00 | 0.169226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.582143E+09 | 0.00 | 0.00 | 0.00 | 0.139518E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.552838E+09 | 0.00 | 0.00 | 0.00 | 0.437401E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.618966E+09 | 0.00 | 0.00 | 0.00 | 7239745.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.674844E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.852251E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.812133E+10 | 0.00 | 0.00 | 0.00 | 0.432108E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.552838E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.881850E+09 | 0.00 | 0.00 | 0.00 | 0.169226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.201240E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.186720E+11 | 0.00 | 0.00 | 0.52 |
February | 0.189880E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.173115E+11 | 0.00 | 0.00 | 0.53 |
March | 0.565611E+10 | 13008842.89 | 0.00 | 274528.73 | 286431.44 | 0.963017E+10 | 0.127406E+09 | 0.00 | 0.53 |
April | 0.789620E+10 | 0.00 | 0.00 | 42619.82 | 0.00 | 0.298883E+10 | 65743622.52 | 0.00 | 0.53 |
May | 0.526928E+10 | 34943054.30 | 0.00 | 4034669.43 | 0.00 | 43913223.35 | 0.249996E+10 | 0.00 | 0.64 |
June | 0.908545E+09 | 0.152037E+10 | 0.00 | 11676526.99 | 934572.66 | 0.00 | 0.420359E+10 | 0.00 | 0.88 |
July | 18868299.04 | 0.432141E+10 | 0.00 | 9040893.15 | 191966.98 | 0.00 | 0.141879E+10 | 0.00 | 0.90 |
August | 0.140914E+09 | 0.251316E+10 | 0.00 | 13247673.79 | 361137.03 | 0.00 | 0.300254E+10 | 0.00 | 0.90 |
September | 0.137415E+10 | 0.576898E+09 | 0.00 | 12296420.15 | 29291.51 | 0.00 | 0.567577E+10 | 0.00 | 0.91 |
October | 0.878219E+10 | 0.00 | 0.00 | 1687656.58 | 0.00 | 0.500018E+09 | 0.118756E+10 | 0.00 | 0.57 |
November | 0.813285E+10 | 0.00 | 0.00 | 2658.24 | 0.00 | 0.444772E+10 | 14729106.96 | 0.00 | 0.53 |
December | 0.354617E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.164266E+11 | 0.00 | 0.00 | 0.53 |
Annual Sum or Average | 0.456365E+11 | 0.897979E+10 | 0.00 | 52303646.87 | 1803399.63 | 0.700207E+11 | 0.181961E+11 | 0.00 | 0.66 |
Minimum of Months | 18868299.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.52 |
Maximum of Months | 0.878219E+10 | 0.432141E+10 | 0.00 | 13247673.79 | 934572.66 | 0.186720E+11 | 0.567577E+10 | 0.00 | 0.91 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.180483E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.579113E+10 | 0.00 | 0.00 | 0.38 |
February | 0.145194E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.554436E+10 | 0.00 | 0.00 | 0.38 |
March | 0.268381E+10 | 8278407.78 | 0.00 | 218552.53 | 0.00 | 0.288905E+10 | 0.115070E+09 | 0.00 | 0.41 |
April | 0.312117E+10 | 0.00 | 0.00 | 376381.31 | 0.00 | 0.681356E+09 | 0.349855E+09 | 0.00 | 0.41 |
May | 0.153348E+10 | 21163508.85 | 0.00 | 3665395.16 | 2433.98 | 0.00 | 0.236855E+10 | 0.00 | 0.65 |
June | 0.243055E+09 | 0.845313E+09 | 0.00 | 5580497.61 | 839365.25 | 0.00 | 0.237850E+10 | 0.00 | 0.86 |
July | 75435.78 | 0.233395E+10 | 0.00 | 2550150.31 | 371545.42 | 0.00 | 0.479797E+09 | 0.00 | 0.78 |
August | 13768967.26 | 0.130865E+10 | 0.00 | 5360909.22 | 61205.37 | 0.00 | 0.127963E+10 | 0.00 | 0.83 |
September | 0.320287E+09 | 0.355017E+09 | 0.00 | 6691434.40 | 229574.59 | 0.00 | 0.336213E+10 | 0.00 | 0.95 |
October | 0.308384E+10 | 0.00 | 0.00 | 1719766.28 | 0.00 | 30771041.91 | 0.125574E+10 | 0.00 | 0.51 |
November | 0.336607E+10 | 0.00 | 0.00 | 119030.85 | 0.00 | 0.119181E+10 | 0.119834E+09 | 0.00 | 0.40 |
December | 0.187006E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.535612E+10 | 0.00 | 0.00 | 0.38 |
Annual Sum or Average | 0.194924E+11 | 0.487238E+10 | 0.00 | 26282117.66 | 1504124.60 | 0.214846E+11 | 0.117091E+11 | 0.00 | 0.58 |
Minimum of Months | 75435.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.336607E+10 | 0.233395E+10 | 0.00 | 6691434.40 | 839365.25 | 0.579113E+10 | 0.336213E+10 | 0.00 | 0.95 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.713332E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.729728E+10 | 0.00 | 0.00 | 0.41 |
February | 0.687768E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.671167E+10 | 0.00 | 0.00 | 0.41 |
March | 0.227564E+10 | 8030473.31 | 0.00 | 84513.32 | 16219.28 | 0.363849E+10 | 31158205.88 | 0.00 | 0.43 |
April | 0.308294E+10 | 0.00 | 0.00 | 47445.00 | 0.00 | 0.966654E+09 | 60421888.26 | 0.00 | 0.42 |
May | 0.189289E+10 | 20000817.77 | 0.00 | 1690522.80 | 542948.39 | 20014852.84 | 0.110837E+10 | 0.00 | 0.54 |
June | 0.452892E+09 | 0.662288E+09 | 0.00 | 3297689.68 | 27813202.87 | 0.00 | 0.161844E+10 | 0.00 | 0.72 |
July | 27247055.39 | 0.174360E+10 | 0.00 | 1951010.13 | 82133909.13 | 0.00 | 0.510073E+09 | 0.00 | 0.70 |
August | 0.100931E+09 | 0.104052E+10 | 0.00 | 3312931.22 | 38531312.59 | 0.00 | 0.107324E+10 | 0.00 | 0.72 |
September | 0.666463E+09 | 0.271040E+09 | 0.00 | 3779730.71 | 4960565.53 | 0.00 | 0.200588E+10 | 0.00 | 0.77 |
October | 0.327077E+10 | 0.00 | 0.00 | 654904.32 | 0.00 | 0.166616E+09 | 0.492777E+09 | 0.00 | 0.46 |
November | 0.292202E+10 | 0.00 | 0.00 | 1421.90 | 0.00 | 0.182165E+10 | 7635607.11 | 0.00 | 0.42 |
December | 0.103844E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.656331E+10 | 0.00 | 0.00 | 0.41 |
Annual Sum or Average | 0.171313E+11 | 0.374549E+10 | 0.00 | 14820169.08 | 0.153998E+09 | 0.271857E+11 | 0.690800E+10 | 0.00 | 0.53 |
Minimum of Months | 27247055.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.327077E+10 | 0.174360E+10 | 0.00 | 3779730.71 | 82133909.13 | 0.729728E+10 | 0.200588E+10 | 0.00 | 0.77 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.555015E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.745562E+10 | 0.00 | 0.00 | 0.41 |
February | 0.591516E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.680791E+10 | 0.00 | 0.00 | 0.41 |
March | 0.207173E+10 | 7575758.20 | 0.00 | 76589.01 | 59024.93 | 0.383877E+10 | 29625550.09 | 0.00 | 0.43 |
April | 0.297589E+10 | 0.00 | 0.00 | 34885.36 | 0.00 | 0.107843E+10 | 37874460.99 | 0.00 | 0.42 |
May | 0.194515E+10 | 19059085.17 | 0.00 | 1493004.46 | 526261.62 | 29219469.38 | 0.977352E+09 | 0.00 | 0.53 |
June | 0.458565E+09 | 0.659589E+09 | 0.00 | 3237515.84 | 27496784.22 | 0.00 | 0.159927E+10 | 0.00 | 0.72 |
July | 27289190.37 | 0.174377E+10 | 0.00 | 1960198.54 | 82431990.30 | 0.00 | 0.511935E+09 | 0.00 | 0.70 |
August | 0.105603E+09 | 0.104069E+10 | 0.00 | 3311470.42 | 38437312.62 | 0.00 | 0.106929E+10 | 0.00 | 0.72 |
September | 0.687279E+09 | 0.267206E+09 | 0.00 | 3697995.69 | 4915044.13 | 0.00 | 0.196949E+10 | 0.00 | 0.77 |
October | 0.320806E+10 | 0.00 | 0.00 | 542706.60 | 0.00 | 0.259409E+09 | 0.412242E+09 | 0.00 | 0.46 |
November | 0.281213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.193132E+10 | 0.00 | 0.00 | 0.42 |
December | 0.896608E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.670515E+10 | 0.00 | 0.00 | 0.41 |
Annual Sum or Average | 0.163348E+11 | 0.373789E+10 | 0.00 | 14354365.91 | 0.153866E+09 | 0.281058E+11 | 0.660708E+10 | 0.00 | 0.53 |
Minimum of Months | 27289190.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.320806E+10 | 0.174377E+10 | 0.00 | 3697995.69 | 82431990.30 | 0.745562E+10 | 0.196949E+10 | 0.00 | 0.77 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.335208E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.767549E+10 | 0.00 | 0.00 | 0.41 |
February | 0.359654E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.703980E+10 | 0.00 | 0.00 | 0.41 |
March | 0.167935E+10 | 6967330.40 | 0.00 | 64486.05 | 233469.62 | 0.423045E+10 | 22850862.88 | 0.00 | 0.43 |
April | 0.273224E+10 | 0.00 | 0.00 | 22955.53 | 0.00 | 0.130941E+10 | 25010746.06 | 0.00 | 0.42 |
May | 0.202089E+10 | 17377243.28 | 0.00 | 1170416.66 | 699806.14 | 39523500.59 | 0.769580E+09 | 0.00 | 0.52 |
June | 0.483402E+09 | 0.641425E+09 | 0.00 | 2972335.12 | 26939153.30 | 0.00 | 0.150528E+10 | 0.00 | 0.70 |
July | 36822154.26 | 0.170357E+10 | 0.00 | 1862121.94 | 80910622.94 | 0.00 | 0.498665E+09 | 0.00 | 0.69 |
August | 0.124799E+09 | 0.101936E+10 | 0.00 | 3113970.15 | 38261184.51 | 0.00 | 0.102661E+10 | 0.00 | 0.71 |
September | 0.725029E+09 | 0.251501E+09 | 0.00 | 3416794.55 | 4860101.49 | 0.00 | 0.185580E+10 | 0.00 | 0.75 |
October | 0.310976E+10 | 0.00 | 0.00 | 415861.61 | 0.00 | 0.389477E+09 | 0.310032E+09 | 0.00 | 0.45 |
November | 0.253888E+10 | 0.00 | 0.00 | 0.00 | 622.76 | 0.219560E+10 | 0.00 | 197.67 | 0.42 |
December | 0.567299E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.703441E+10 | 0.00 | 0.00 | 0.41 |
Annual Sum or Average | 0.147133E+11 | 0.364020E+10 | 0.00 | 13038941.61 | 0.151905E+09 | 0.299142E+11 | 0.601384E+10 | 197.67 | 0.53 |
Minimum of Months | 36822154.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.310976E+10 | 0.170357E+10 | 0.00 | 3416794.55 | 80910622.94 | 0.767549E+10 | 0.185580E+10 | 197.67 | 0.75 |
Report: MechanicalVentilationLoadsMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 34759435.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148814E+11 | 0.00 | 0.00 | 0.38 |
February | 84992036.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136866E+11 | 0.00 | 0.00 | 0.38 |
March | 0.214593E+10 | 3709085.26 | 0.00 | 171910.24 | 743119.97 | 0.883759E+10 | 53160153.43 | 0.00 | 0.39 |
April | 0.457231E+10 | 0.00 | 0.00 | 32481.21 | 0.00 | 0.291804E+10 | 44319295.08 | 0.00 | 0.38 |
May | 0.392534E+10 | 20223828.60 | 0.00 | 1467605.64 | 6769789.55 | 79146968.73 | 0.110436E+10 | 0.00 | 0.45 |
June | 0.818710E+09 | 0.111600E+10 | 0.00 | 4825897.65 | 23052392.20 | 0.00 | 0.261353E+10 | 0.00 | 0.59 |
July | 14057866.77 | 0.302214E+10 | 0.00 | 2871848.22 | 41907419.55 | 0.00 | 0.787478E+09 | 0.00 | 0.59 |
August | 0.149028E+09 | 0.176540E+10 | 0.00 | 5413259.64 | 31248884.69 | 0.00 | 0.172061E+10 | 0.00 | 0.61 |
September | 0.116596E+10 | 0.336673E+09 | 0.00 | 5846203.22 | 6264084.61 | 0.00 | 0.328977E+10 | 0.00 | 0.63 |
October | 0.567049E+10 | 0.00 | 0.00 | 481643.29 | 0.00 | 0.837720E+09 | 0.459424E+09 | 0.00 | 0.40 |
November | 0.363903E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.528357E+10 | 0.00 | 0.00 | 0.38 |
December | 0.179443E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140257E+11 | 0.00 | 0.00 | 0.38 |
Annual Sum or Average | 0.224001E+11 | 0.626414E+10 | 0.00 | 21110849.12 | 0.109986E+09 | 0.605498E+11 | 0.100726E+11 | 0.00 | 0.46 |
Minimum of Months | 14057866.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.567049E+10 | 0.302214E+10 | 0.00 | 5846203.22 | 41907419.55 | 0.148814E+11 | 0.328977E+10 | 0.00 | 0.63 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 14064988.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.743256E+10 | 0.00 | 0.00 | 0.38 |
February | 34251409.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.684113E+10 | 0.00 | 0.00 | 0.38 |
March | 0.958883E+09 | 1957537.46 | 0.00 | 78144.49 | 421629.09 | 0.452343E+10 | 23986912.49 | 0.00 | 0.39 |
April | 0.210823E+10 | 0.00 | 0.00 | 11895.92 | 0.00 | 0.162294E+10 | 18189927.73 | 0.00 | 0.38 |
May | 0.198377E+10 | 9781551.72 | 0.00 | 640476.39 | 3662420.35 | 49022442.24 | 0.486007E+09 | 0.00 | 0.45 |
June | 0.419820E+09 | 0.555937E+09 | 0.00 | 2386033.00 | 12010154.87 | 0.00 | 0.129996E+10 | 0.00 | 0.60 |
July | 9185645.40 | 0.151054E+10 | 0.00 | 1442303.76 | 20941797.33 | 0.00 | 0.405728E+09 | 0.00 | 0.60 |
August | 81249872.68 | 0.885914E+09 | 0.00 | 2713729.97 | 15513786.73 | 0.00 | 0.872853E+09 | 0.00 | 0.62 |
September | 0.581025E+09 | 0.167894E+09 | 0.00 | 2928187.19 | 3170255.74 | 0.00 | 0.166362E+10 | 0.00 | 0.64 |
October | 0.273354E+10 | 0.00 | 0.00 | 212572.60 | 0.00 | 0.528816E+09 | 0.197789E+09 | 0.00 | 0.40 |
November | 0.166115E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.278688E+10 | 0.00 | 0.00 | 0.38 |
December | 74287920.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.701670E+10 | 0.00 | 0.00 | 0.38 |
Annual Sum or Average | 0.106595E+11 | 0.313203E+10 | 0.00 | 10413343.33 | 55720044.12 | 0.308015E+11 | 0.496814E+10 | 0.00 | 0.47 |
Minimum of Months | 9185645.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.273354E+10 | 0.151054E+10 | 0.00 | 2928187.19 | 20941797.33 | 0.743256E+10 | 0.166362E+10 | 0.00 | 0.64 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 8556584.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.743810E+10 | 0.00 | 0.00 | 0.38 |
February | 32805169.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.684263E+10 | 0.00 | 0.00 | 0.38 |
March | 0.902701E+09 | 1910525.63 | 0.00 | 74471.60 | 462501.77 | 0.457940E+10 | 22737233.70 | 0.00 | 0.39 |
April | 0.202072E+10 | 0.00 | 0.00 | 9871.40 | 0.00 | 0.170685E+10 | 15251961.11 | 0.00 | 0.38 |
May | 0.201118E+10 | 9343656.22 | 0.00 | 549413.28 | 3933258.05 | 59067877.47 | 0.412758E+09 | 0.00 | 0.44 |
June | 0.442673E+09 | 0.549867E+09 | 0.00 | 2279786.24 | 10947531.66 | 0.00 | 0.124550E+10 | 0.00 | 0.59 |
July | 11089707.27 | 0.149631E+10 | 0.00 | 1407616.92 | 21080058.50 | 0.00 | 0.400672E+09 | 0.00 | 0.60 |
August | 87754222.67 | 0.879031E+09 | 0.00 | 2652954.06 | 15498339.22 | 0.00 | 0.857962E+09 | 0.00 | 0.62 |
September | 0.586624E+09 | 0.163696E+09 | 0.00 | 2828365.34 | 3210234.60 | 0.00 | 0.162643E+10 | 0.00 | 0.63 |
October | 0.269934E+10 | 0.00 | 0.00 | 190114.36 | 0.00 | 0.565922E+09 | 0.178502E+09 | 0.00 | 0.40 |
November | 0.156150E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.288495E+10 | 0.00 | 0.00 | 0.38 |
December | 68251641.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.702277E+10 | 0.00 | 0.00 | 0.38 |
Annual Sum or Average | 0.104332E+11 | 0.310016E+10 | 0.00 | 9992593.19 | 55131923.79 | 0.310997E+11 | 0.475981E+10 | 0.00 | 0.46 |
Minimum of Months | 8556584.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.269934E+10 | 0.149631E+10 | 0.00 | 2828365.34 | 21080058.50 | 0.743810E+10 | 0.162643E+10 | 0.00 | 0.63 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.744670E+10 | 0.00 | 0.00 | 0.38 |
February | 841532.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.687462E+10 | 0.00 | 0.00 | 0.38 |
March | 0.634891E+09 | 1761484.78 | 0.00 | 62369.13 | 646740.50 | 0.484591E+10 | 20142939.29 | 0.00 | 0.39 |
April | 0.166554E+10 | 0.00 | 0.00 | 4547.49 | 0.00 | 0.205189E+10 | 9366072.90 | 0.00 | 0.38 |
May | 0.198721E+10 | 8291931.01 | 161480.02 | 413620.98 | 4489772.76 | 0.106244E+09 | 0.314050E+09 | 53.59 | 0.44 |
June | 0.491079E+09 | 0.529635E+09 | 0.00 | 2021481.35 | 13135694.09 | 0.00 | 0.111571E+10 | 0.00 | 0.57 |
July | 15050820.55 | 0.145929E+10 | 0.00 | 1348188.32 | 22238568.07 | 0.00 | 0.389521E+09 | 0.00 | 0.59 |
August | 0.110458E+09 | 0.861688E+09 | 0.00 | 2482668.45 | 15442340.77 | 0.00 | 0.814811E+09 | 0.00 | 0.61 |
September | 0.634133E+09 | 0.153213E+09 | 0.00 | 2545906.27 | 3298817.18 | 742825.94 | 0.149946E+10 | 0.00 | 0.61 |
October | 0.251038E+10 | 0.00 | 0.00 | 140791.79 | 0.00 | 0.755645E+09 | 0.146014E+09 | 0.00 | 0.39 |
November | 0.119941E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.324239E+10 | 0.00 | 0.00 | 0.38 |
December | 37184486.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.705387E+10 | 0.00 | 0.00 | 0.38 |
Annual Sum or Average | 0.928617E+10 | 0.301388E+10 | 161480.02 | 9019573.78 | 59251933.37 | 0.323780E+11 | 0.430907E+10 | 53.59 | 0.46 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.251038E+10 | 0.145929E+10 | 161480.02 | 2545906.27 | 22238568.07 | 0.744670E+10 | 0.149946E+10 | 53.59 | 0.61 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.742128E+10 | 0.00 | 0.00 | 0.38 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.685679E+10 | 0.00 | 0.00 | 0.38 |
March | 0.214466E+09 | 1604570.79 | 40869.89 | 39935.88 | 873794.53 | 0.524151E+10 | 15158174.35 | 73.39 | 0.39 |
April | 0.846002E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.283365E+10 | 0.00 | 0.00 | 0.38 |
May | 0.168692E+10 | 6724322.38 | 622048.04 | 272331.83 | 2791939.27 | 0.359178E+09 | 0.255148E+09 | 3269.54 | 0.43 |
June | 0.588821E+09 | 0.499606E+09 | 0.00 | 1644127.32 | 15050396.68 | 924042.42 | 0.928054E+09 | 0.00 | 0.56 |
July | 17302488.49 | 0.139296E+10 | 0.00 | 1348839.09 | 21548499.72 | 0.00 | 0.409915E+09 | 0.00 | 0.59 |
August | 0.172720E+09 | 0.840546E+09 | 0.00 | 2289370.24 | 15000239.12 | 0.00 | 0.739282E+09 | 0.00 | 0.61 |
September | 0.721301E+09 | 0.142732E+09 | 0.00 | 2315883.87 | 3507341.33 | 13590765.00 | 0.133906E+10 | 0.00 | 0.61 |
October | 0.177455E+10 | 0.00 | 0.00 | 101014.42 | 0.00 | 0.148238E+10 | 0.103502E+09 | 0.00 | 0.39 |
November | 0.493667E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.391925E+10 | 0.00 | 0.00 | 0.38 |
December | 5348652.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.706529E+10 | 0.00 | 0.00 | 0.38 |
Annual Sum or Average | 0.652110E+10 | 0.288417E+10 | 662917.94 | 8011502.65 | 58772210.65 | 0.351939E+11 | 0.379012E+10 | 3342.92 | 0.46 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.177455E+10 | 0.139296E+10 | 622048.04 | 2315883.87 | 21548499.72 | 0.742128E+10 | 0.133906E+10 | 3269.54 | 0.61 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:36:59
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.109439E+12 | 0.483016E+11 | 0.00 | 0.998627E+11 | 0.339859E+11 |
February | 0.201017E+12 | 0.463334E+11 | 0.00 | 0.921676E+11 | 0.317332E+11 |
March | 0.333745E+12 | 0.336000E+11 | 0.00 | 0.742910E+11 | 0.216623E+11 |
April | 0.420630E+12 | 0.228206E+11 | 0.00 | 0.514472E+11 | 0.849616E+10 |
May | 0.538747E+12 | 0.132126E+11 | 0.00 | 0.353448E+11 | 0.653843E+10 |
June | 0.596205E+12 | 0.352486E+10 | 0.00 | 0.161040E+11 | 0.568007E+11 |
July | 0.557768E+12 | -0.647930E+10 | 0.00 | -0.152003E+11 | 0.122278E+12 |
August | 0.468640E+12 | -0.172073E+10 | 0.00 | 0.120731E+10 | 0.977218E+11 |
September | 0.343873E+12 | 0.760325E+10 | 0.00 | 0.290934E+11 | 0.353132E+11 |
October | 0.213994E+12 | 0.205518E+11 | 0.00 | 0.480202E+11 | 0.514551E+10 |
November | 0.955886E+11 | 0.274535E+11 | 0.00 | 0.602120E+11 | 0.123775E+11 |
December | 0.946571E+11 | 0.473738E+11 | 0.00 | 0.955024E+11 | 0.313142E+11 |
Annual Sum or Average | 0.397430E+13 | 0.262575E+12 | 0.00 | 0.588052E+12 | 0.463367E+12 |
Minimum of Months | 0.946571E+11 | -0.647930E+10 | 0.00 | -0.152003E+11 | 0.514551E+10 |
Maximum of Months | 0.596205E+12 | 0.483016E+11 | 0.00 | 0.998627E+11 | 0.122278E+12 |